Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2024-07-03 12:21:46
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 31970.79 | 690.21 | 690.21 |
Net Site Energy | 31970.79 | 690.21 | 690.21 |
Total Source Energy | 91682.20 | 1979.31 | 1979.31 |
Net Source Energy | 91682.20 | 1979.31 | 1979.31 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 4593.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 772.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3295.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 385.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2566.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2543.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 231.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 204.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1290.77 |
Humidification | 2094.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 779.22 |
Heat Recovery | 52.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 553.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 27376.80 | 4593.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4350.16 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 4593.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 772.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3295.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 385.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 55.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2505.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2543.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 231.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 204.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1290.77 |
Humidification | General | 2094.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 779.22 |
Heat Recovery | General | 52.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 553.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 4593.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 772.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3295.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 385.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 2566.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2543.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 231.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 204.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1290.77 |
Humidification | Unassigned | 2094.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 779.22 |
Heat Recovery | Unassigned | 52.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 553.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 79.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 138.18 | 99.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.09 |
Other | 373.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 591.03 | 99.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.09 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 79.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 138.18 | 99.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.09 |
Other | 373.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 591.03 | 99.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.09 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 27376.797 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 27376.797 | 100.00 |
Total On-Site and Utility Electric Sources | 27376.797 | 100.00 |
Total Electricity End Uses | 27376.797 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 1.75 | 0.05 |
Air to Air Heat Recovery for Heating | 3679.46 | 99.95 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 3681.22 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 4350.16 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 4350.16 | 100.00 |
Total Water End Uses | 4350.16 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 229.83 |
Time Setpoint Not Met During Occupied Cooling | 3244.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 8.6849 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 8.6849 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 8.7339 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 8.7339 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.6849 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 8.6849 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 8.6849 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 8.6849 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 8.6849 | 18.58 | 484.4232 | |
Total | 46320.38 | 8.7339 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 8.7339 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.6845 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 11-AUG-15:20 | 27-FEB-07:30 | - | - | - | - | - | - | - | - | - | - | 21-JUL-15:50 |
Heating | 0.00 | 2541901.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 342267.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 280450.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 233302.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 266753.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 41241.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 50651.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 52966.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 1871.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 44126.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2092003.05 | 2541901.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 2541901.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 342267.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 280450.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3430.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 266753.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 41241.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 50651.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 52966.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 1871.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 44126.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 4979.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2446.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 10436.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1219.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8128.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8055.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 733.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 648.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 6633.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 166.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1752.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 86702.32 | 4979.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 107.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 52.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 225.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 26.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 173.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 15.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 14.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 143.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 3.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 37.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1871.80 | 107.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 107.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 52.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 225.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 26.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 173.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 15.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 14.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 143.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 3.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 37.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1871.80 | 107.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 5.72 | 0.370511 | 0.000000 | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 6.04 | 0.314888 | 0.326000 | 1.97 | 0.839702 | 0.500000 | 0.001210 | 0.000230 | 1.97 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 57.03 | 0.333542 | 0.339000 | 19.33 | 0.889444 | 0.500000 | 0.001142 | 0.004242 | 19.33 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.60 | 0.339541 | 0.352000 | 1.97 | 0.905442 | 0.500000 | 0.001122 | 0.001002 | 3.47 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.06 | 0.224892 | 0.233000 | 0.247431 | 0.599711 | 0.500000 | 0.001694 | 0.000173 | 0.600600 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.52 | 0.101299 | 0.200000 | 0.303863 | 0.300000 | 0.500000 | 0.003761 | 0.000119 | 0.411206 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 2.31 | 0.103356 | 0.200000 | 0.462142 | 0.300000 | 0.500000 | 0.003686 | 0.000188 | 0.651781 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.76 | 0.087596 | 0.200000 | 0.351397 | 0.300000 | 0.500000 | 0.004350 | 0.000097 | 0.351397 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 9.97 | 0.239616 | 0.243000 | 2.42 | 0.638976 | 0.500000 | 0.001590 | 0.002286 | 7.92 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 16.35 | 0.094152 | 0.200000 | 3.27 | 0.300000 | 0.500000 | 0.004047 | 0.001518 | 5.26 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 24.66 | 0.096857 | 0.200000 | 4.93 | 0.300000 | 0.500000 | 0.003934 | 0.002271 | 7.87 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 16.63 | 0.092527 | 0.200000 | 3.33 | 0.300000 | 0.500000 | 0.004118 | 0.001454 | 5.03 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.05 | 0.227238 | 0.242000 | 0.254336 | 0.605967 | 0.500000 | 0.001677 | 0.000303 | 1.05 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.63 | 0.094413 | 0.200000 | 0.326026 | 0.300000 | 0.500000 | 0.004035 | 0.000200 | 0.692802 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 2.54 | 0.094113 | 0.200000 | 0.507533 | 0.300000 | 0.500000 | 0.004048 | 0.000302 | 1.05 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.71 | 0.090008 | 0.200000 | 0.341982 | 0.300000 | 0.500000 | 0.004233 | 0.000196 | 0.678428 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | User-Specified Rated Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 26263.76 | 0.000230 | 548.12 | |
CORE_MID VAV BOX REHEAT COIL | 484850.71 | 0.004242 | 11539.07 | |
CORE_TOP VAV BOX REHEAT COIL | 114551.90 | 0.001002 | 3022.92 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 19830.93 | 0.000173 | 523.09 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 13575.53 | 0.000119 | 358.07 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 21517.13 | 0.000188 | 567.53 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 11123.15 | 0.000097 | 288.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 261330.38 | 0.002286 | 6891.55 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 173501.09 | 0.001518 | 4575.29 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 259636.42 | 0.002271 | 6846.91 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 166153.38 | 0.001454 | 4381.67 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 34667.91 | 0.000303 | 914.05 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 22852.43 | 0.000200 | 602.52 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 34471.62 | 0.000302 | 908.88 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 22378.80 | 0.000196 | 590.04 | |
VAV_BOT WITH REHEAT HEATING COIL | 160468.17 | 0.001404 | 2203.12 | |
VAV_MID WITH REHEAT HEATING COIL | 1627921.07 | 0.014242 | 21785.35 | |
VAV_TOP WITH REHEAT HEATING COIL | 163291.12 | 0.001429 | 2235.77 | |
CAV_BAS HEATING COIL | 332267.79 | 0.000875 | 2622.58 | 100000.00 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.524555 |
DATACENTER_MID_ZN_6 DIRECT AIR | 5.06 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.510674 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 25.02 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 6.34 | 3.33 | 12.69 | 3.33 | 10.34 | 10.34 | 0.300000 | 0.322476 | 10.34 |
VAV_MID WITH REHEAT | 62.32 | 33.28 | 124.63 | 38.65 | 96.33 | 96.33 | 0.300000 | 0.401188 | 96.33 |
VAV_TOP WITH REHEAT | 6.27 | 3.40 | 12.53 | 6.93 | 10.43 | 10.43 | 0.300000 | 0.665008 | 10.43 |
CAV_BAS | 0.000000 | 0.000000 | 5.72 | 1.20 | 5.72 | 5.72 | 1.00 | 0.209956 | 5.72 |
AIRLOOP DATACENTER BASEMENT | 25.02 | 25.02 | 25.02 | 25.02 | 25.02 | 25.02 | 1.00 | 1.00 | 25.02 |
AIRLOOP DATACENTER BOT | 0.524555 | 0.524555 | 0.524555 | 0.524555 | 0.524555 | 0.524555 | 1.00 | 1.00 | 0.524555 |
AIRLOOP DATACENTER MID | 5.06 | 5.06 | 5.06 | 5.06 | 5.06 | 5.06 | 1.00 | 1.00 | 5.06 |
AIRLOOP DATACENTER TOP | 0.510674 | 0.510674 | 0.510674 | 0.510674 | 0.510674 | 0.510674 | 1.00 | 1.00 | 0.510674 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 10.34 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 96.33 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 10.43 | |
CAV_BAS_OA_CONTROLLER | 5.72 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 25.02 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.524555 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 5.06 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.510674 | 0.015632 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT OA HEAT RECOVERY | 2.54 |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 25.38 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.54 |
CAV_BAS OA HEAT RECOVERY | 1.20 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 24.84 | 6.67 | 10.92 | 0.007233 | 0.007000 | 180924.25 | 0.005174 | 10.34 |
VAV_MID WITH REHEAT COOLING COIL | 24.90 | 6.67 | 10.92 | 0.007243 | 0.007000 | 1695613.65 | 0.048494 | 96.33 |
VAV_TOP WITH REHEAT COOLING COIL | 24.83 | 6.67 | 10.92 | 0.007231 | 0.007000 | 182282.94 | 0.005213 | 10.43 |
CAV_BAS COOLING COIL | 24.48 | 6.67 | 10.90 | 0.007372 | 0.007000 | 100104.17 | 0.002863 | 5.72 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 10.34 |
VAV_MID WITH REHEAT FAN | 96.33 |
VAV_TOP WITH REHEAT FAN | 10.43 |
CAV_BAS FAN | 5.72 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.005174 | 0.000092 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.001404 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.048494 | 0.000010 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.014242 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.005213 | 0.000091 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.001429 | |
CAV_BAS_COOLC_CONTROLLER | 0.002863 | 0.000166 |
CAV_BAS_HEATC_CONTROLLER | 0.000875 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 25.02 | 510538.05 | 323604.73 | 0.012503 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.524555 | 10406.59 | 6671.01 | 0.000255 |
AIRLOOP DATACENTER MID COOLING COIL | 5.06 | 100477.32 | 64404.31 | 0.002461 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.510674 | 10131.87 | 6494.46 | 0.000248 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 25.02 | 25.02 | 25.02 | 25.02 | 510538.05 | 510538.05 | 33013.32 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.524555 | 0.524555 | 0.524555 | 0.524555 | 10406.59 | 10406.59 | 1525.08 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 5.06 | 5.06 | 5.06 | 5.06 | 100477.32 | 100477.32 | 15250.79 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.510674 | 0.510674 | 0.510674 | 0.510674 | 10131.87 | 10131.87 | 1525.08 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 25.02 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.524555 |
AIRLOOP DATACENTER MID SUPPLY FAN | 5.06 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.510674 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 25.02 | 510538.05 | 0.012503 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.524555 | 10406.59 | 0.000255 |
AIRLOOP DATACENTER MID HEATING COIL | 5.06 | 100477.32 | 0.002461 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.510674 | 10131.87 | 0.000248 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 33013.32 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 1525.08 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 15250.79 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 1525.08 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000227 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.061745 | 10081.07 | |
HEATSYS1 PUMP | 0.032530 | 9796.63 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.061745 | 7.41 |
HEATSYS1 | 0.032530 | 3.90 |
COOLSYS1_SUPPLY | 0.061745 | 7.41 |
SINGLE WATER PLANT LOOP | 0.015467 | 1.86 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.061745 | 0.061745 | 259174.67 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 3718385.50 | 3718385.50 | 0.032530 |
CENTRAL BOILER | 637095.97 | 624479.74 | 0.015467 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.030872 | 3489.73 |
COOLSYS1 CHILLER2 PUMP | 0.030872 | 3489.73 |
PLANT CIRC PUMP | 0.015467 | 3944.79 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.061745 | 0.031044 | 1085445.37 | 1085445.00 | 0.054658 |
COOLSYS1 CHILLER2 | 0.061745 | 0.031044 | 1085445.37 | 1085445.00 | 0.054658 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | U-factor Times Area Value at High Fan Speed [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/K] | |
CENTRAL TOWER | 0.015467 | 153572.98 | 77743.22 | 76786.49 | 7879.72 | 46645.93 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.109315 | 13.12 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.109315 | 27064.02 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 42.55 | 1300904.75 | 8.51 | 162613.09 |
TOWERWATERSYS COOLTOWER 2 | 42.55 | 1300904.75 | 8.51 | 162613.09 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.056287 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | -3.10 | -17.70 | -19.30 | -17.60 | -15.40 | -10.30 | 0.70 | 10.60 | 16.00 | 16.90 | 14.20 | 6.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 | 64.82 | -147.85 | -9.00 | 133.00 | 99737 | 1.1854 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | -1.53 | 36.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 8.685 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 13.527 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 8.685 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 493.108 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 24139.153 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 24139.153 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 6806.209 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6806.209 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 0.6685 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 0.6266 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 0.8399 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.329 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.429 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.023 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
47 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
48 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
49 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
50 | 9 | -0.21299096E-14 | 0.28894800E-16 | -0.16188973E-09 | 0.38579871E-16 |
51 | 8 | 0.23581069E-07 | 0.91092976E-13 | 0.39549172E-03 | -0.26812487E-09 |
52 | 7 | -0.12768924E-01 | 0.46460358E-08 | -0.23844895E-01 | 0.14518732E-03 |
53 | 6 | 0.41967891 | 0.16074080E-05 | 0.48427557 | -0.49166618E-02 |
54 | 5 | -5.3303803 | 0.59734123E-04 | -4.5347620 | 0.64917525E-01 |
55 | 4 | 33.621223 | 0.48654995E-03 | 21.805629 | -0.43033321 |
56 | 3 | -112.54166 | 0.10563465E-02 | -56.346116 | 1.5341997 |
57 | 2 | 198.43470 | 0.59216919E-03 | 78.537424 | -2.9214177 |
58 | 1 | -171.64594 | 0.63016798E-04 | -55.447962 | 2.7540249 |
59 | 0 | 57.057407 | 0.35742999E-06 | 15.527221 | |
60 | 9 | 0.75071082E-15 | -0.32535972E-15 | -0.16381989E-09 | -0.10550086E-16 |
61 | 8 | 0.23851931E-07 | 0.85286513E-13 | 0.39826052E-03 | -0.27120466E-09 |
62 | 7 | -0.12851287E-01 | 0.43498253E-08 | -0.23963405E-01 | 0.14612382E-03 |
63 | 6 | 0.42191652 | 0.15033070E-05 | 0.48617502 | -0.49430380E-02 |
64 | 5 | -5.3522123 | 0.55813756E-04 | -4.5493227 | 0.65188236E-01 |
65 | 4 | 33.717764 | 0.45423475E-03 | 21.862480 | -0.43161506 |
66 | 3 | -112.74698 | 0.98544308E-03 | -56.458481 | 1.5371663 |
67 | 2 | 198.63811 | 0.55204883E-03 | 78.640589 | -2.9246480 |
68 | 1 | -171.72104 | 0.58710654E-04 | -55.478167 | 2.7553411 |
69 | 0 | 57.057407 | 0.33274243E-06 | 15.522401 | |
70 | 9 | -0.19159632E-14 | 0.31671484E-16 | -0.15392039E-09 | 0.39566669E-16 |
71 | 8 | 0.22464981E-07 | 0.11360995E-12 | 0.38396804E-03 | -0.25543456E-09 |
72 | 7 | -0.12425740E-01 | 0.58612731E-08 | -0.23350983E-01 | 0.14128520E-03 |
73 | 6 | 0.41035492 | 0.20371532E-05 | 0.47635123 | -0.48067540E-02 |
74 | 5 | -5.2394009 | 0.76003274E-04 | -4.4739732 | 0.63789410E-01 |
75 | 4 | 33.218868 | 0.62128211E-03 | 21.568188 | -0.42499095 |
76 | 3 | -111.68581 | 0.13531787E-02 | -55.876772 | 1.5218344 |
77 | 2 | 197.58670 | 0.76073673E-03 | 78.106675 | -2.9079511 |
78 | 1 | -171.33281 | 0.81169205E-04 | -55.322159 | 2.7485368 |
79 | 0 | 57.057407 | 0.46182178E-06 | 15.547553 | |
80 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
81 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
82 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
83 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
84 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
85 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
86 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
87 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
88 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
89 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
90 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
91 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
92 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
93 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
94 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
95 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
96 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
97 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
98 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
99 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
100 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
101 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
102 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
103 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
104 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
105 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
106 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
107 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
108 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
109 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
110 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
111 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
112 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
113 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
114 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
115 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
116 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
117 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
118 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
119 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
120 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
121 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
122 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
123 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
124 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
125 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
126 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
127 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.29_SHGC_EAST_0.45 | 35 | 1 | VerySmooth | 1.647 | 1.647 | 1.000 | 0.451 | ||
2 | WINDOW_U_0.29_SHGC_SOUTH_0.45 | 36 | 1 | VerySmooth | 1.647 | 1.647 | 1.000 | 0.451 | ||
3 | WINDOW_U_0.29_SHGC_WEST_0.45 | 37 | 1 | VerySmooth | 1.647 | 1.647 | 1.000 | 0.451 | ||
4 | WINDOW_U_0.29_SHGC_NORTH_0.45 | 38 | 1 | VerySmooth | 1.647 | 1.647 | 1.000 | 0.451 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 4.26414E-002 | 0.36619 | 0.44111 | 0.44111 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 9.85326E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 4.26414E-002 | 0.36619 | 0.44111 | 0.44111 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 9.85326E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 4.26414E-002 | 0.36619 | 0.44111 | 0.44111 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 9.85326E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 4.26414E-002 | 0.36619 | 0.44111 | 0.44111 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 9.85326E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 1.973E-005 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.4818E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.4851E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1152E-002 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1155E-002 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.8952E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.8969E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1533E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1543E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.5552E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.7550E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1217E-002 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1398E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.9394E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.0629E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1802E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2472E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1913 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1183 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.2249 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1436 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1081 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5295E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.6903E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9742E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.5821E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.9063E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1250E-002 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1581E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.9537E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1163E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1808E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2491E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.4817E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.4860E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.1152E-002 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.1156E-002 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.8951E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.8974E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1531E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1541E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 9.3390E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.0711E-002 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 9.7615E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.1589E-002 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.8140E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.9881E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3920E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.4383E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 0.1093 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.6227E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 0.1140 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.8157E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.3491E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5317E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.9249E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.2116E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.9768E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 9.1458E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 9.2487E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 9.3803E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.7679E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.8191E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3921E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.4390E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.0347E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.0382E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4562E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4594E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8252E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8272E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1533E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.1543E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1135E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3036E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.5274E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.6934E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8746E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9860E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1809E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.2492E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 7.2680E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.7897E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.7931E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9945E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6601E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7705E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.6903E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9736E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1097E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.3155E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.5187E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.6855E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8625E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9474E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1802E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.2472E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.0344E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 4.0378E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4558E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4587E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8250E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8265E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1532E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.1542E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 7.0276E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 7.2152E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.4971E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.6394E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.8681E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.9090E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3922E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.4391E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 7.8098E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.0605E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 7.0089E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.6113E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.7252E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8190E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9249E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.2116E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 7.1747E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 7.5643E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.7093E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 7.1550E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9073E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.0396E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3919E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.4382E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.2158 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1679 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.2512 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.2028 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1262 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.8664E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.9736E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.4447E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 0.1287 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 7.9597E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 0.1342 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 8.3002E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 9.8575E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 5.1461E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.1497E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.4843E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 8.8000E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 5.7490E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 7.1395E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 4.6667E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.8814E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.1054E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 6.9736E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.4441E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 9.3131E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 5.7734E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 8.4162E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 5.2139E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 8.0390E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.2138E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.1497E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.4843E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.2156 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1680 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.2510 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.2029 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1263 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.8809E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.9886E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.4523E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 0.1287 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 7.9713E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 0.1342 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 8.3125E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 9.8719E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 5.1568E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.1647E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.4919E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 8.8010E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 5.7562E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 7.1407E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 4.6726E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.8914E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.1115E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 6.9886E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.4517E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 9.3160E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 5.7814E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 8.4192E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 5.2211E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 8.0513E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.2224E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.1647E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.4919E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 77941.88504 | 77941.88504 | 5.71623 | 5.71623 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 82365.75220 | 82365.75220 | 6.04038 | 6.04038 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 6745.15804 | 6745.15804 | 0.29015 | 1.07782 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 777782.57420 | 777782.57420 | 57.02568 | 57.02568 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 293230.76594 | 293230.76594 | 12.56789 | 12.56789 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 76407.22349 | 76407.22349 | 5.60181 | 5.60181 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 19.85200 | 6.99585E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 80195.52755 | 80195.52755 | 3.46607 | 3.46607 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 14349.50663 | 14349.50663 | 1.06194 | 1.06194 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 21.38200 | 6.99811E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 13877.86810 | 13877.86810 | 0.60060 | 0.60060 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 20530.13589 | 20530.13589 | 1.51932 | 1.51932 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 21.79000 | 6.99871E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 9499.70174 | 9499.70174 | 0.41121 | 0.41121 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 31224.05725 | 31224.05725 | 2.31071 | 2.31071 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 27.31500 | 7.00701E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 15056.74237 | 15056.74237 | 0.65178 | 0.65178 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 23741.75909 | 23741.75909 | 1.75699 | 1.75699 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.69700 | 7.00305E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 7640.22616 | 7640.22616 | 0.33045 | 0.33045 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 134677.39501 | 134677.39501 | 9.96680 | 9.96680 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | 21.22900 | 6.99788E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 182839.80406 | 182839.80406 | 7.91905 | 7.91905 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 220886.91247 | 220886.91247 | 16.34653 | 16.34653 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 22.36800 | 6.99957E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 121387.38072 | 121387.38072 | 5.25784 | 5.25784 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 333192.47010 | 333192.47010 | 24.65761 | 24.65761 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 27.40000 | 7.00714E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 181655.57228 | 181655.57228 | 7.86762 | 7.86762 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 224763.98236 | 224763.98236 | 16.63344 | 16.63344 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 24.44200 | 7.00266E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 116250.34887 | 116250.34887 | 5.03482 | 5.03482 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 13814.84814 | 13814.84814 | 1.02237 | 1.02237 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 21.38200 | 6.99811E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 24251.04911 | 24251.04911 | 1.05097 | 1.05097 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 22027.56499 | 22027.56499 | 1.63013 | 1.63013 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 22.65700 | 7.00000E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 15985.63871 | 15985.63871 | 0.69280 | 0.69280 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 34290.84994 | 34290.84994 | 2.53766 | 2.53766 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 27.40000 | 7.00714E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 24113.82276 | 24113.82276 | 1.04501 | 1.04501 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 23105.66269 | 23105.66269 | 1.70991 | 1.70991 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 24.44200 | 7.00266E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 15654.48009 | 15654.48009 | 0.67843 | 0.67843 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90000 | 6.45023E-005 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8986.66325 | 8986.66325 | 0.52456 | 0.52456 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | 21.84100 | 6.99878E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -41.90000 | 6.45023E-005 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 86760.65777 | 86760.65777 | 5.06427 | 5.06427 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | 21.84100 | 6.99878E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -41.90000 | 6.45023E-005 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8748.82652 | 8748.82652 | 0.51067 | 0.51067 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | 21.84100 | 6.99878E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -41.90000 | 6.45023E-005 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 372769.05245 | 428684.41032 | 21.75847 | 25.02224 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 18.11800 | 6.99333E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:30:00 | -41.90000 | 6.45023E-005 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 147612.50 | 10.33875 | 10.33875 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 165034.12 | 3.07186 | 3.07186 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1385337.46 | 96.33185 | 96.33185 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 1652170.98 | 38.64722 | 38.64722 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 148941.18 | 10.42587 | 10.42587 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 165237.19 | 6.93328 | 6.93328 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 |
7 | CAV_BAS | Cooling | Sensible | 72002.63 | 5.71623 | 5.71623 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 117086.28 | 1.20016 | 1.20016 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 422828.08 | 25.02224 | 25.02224 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 33013.32 | 0.33839 | 0.33839 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8775.90 | 0.52456 | 0.52456 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 1525.08 | 1.56323E-002 | 1.56323E-002 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 84692.67 | 5.06427 | 5.06427 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 15250.79 | 0.15632 | 0.15632 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8541.10 | 0.51067 | 0.51067 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 1525.08 | 1.56323E-002 | 1.56323E-002 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 5.71623 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.37051 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.00000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 0.00000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.04038 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31489 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32600 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.96916 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83970 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.20995E-003 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.29767E-004 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.96916 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
16 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26263.75716 |
17 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.29767E-004 |
18 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 548.11959 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 57.02568 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33354 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33900 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 19.33171 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.88944 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.14229E-003 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.24169E-003 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 19.33171 |
28 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
30 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 484850.71460 |
31 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.24169E-003 |
32 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 11539.07432 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.60181 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33954 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35200 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.97184 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.90544 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.12210E-003 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.00215E-003 |
41 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.46607 |
42 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
43 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
44 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 114551.90020 |
45 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.00215E-003 |
46 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3022.91620 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.06194 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22489 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23300 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24743 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59971 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.69415E-003 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.73490E-004 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.60060 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
58 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19830.92778 |
59 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.73490E-004 |
60 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 523.09436 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.51932 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10130 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.30386 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.76114E-003 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.18765E-004 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.41121 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
72 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13575.52717 |
73 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.18765E-004 |
74 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 358.06835 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.31071 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10336 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.46214 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.68629E-003 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.88241E-004 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.65178 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
86 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21517.12672 |
87 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.88241E-004 |
88 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 567.52765 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.75699 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.75961E-002 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.35140 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.34951E-003 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.73102E-005 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.35140 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
100 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11123.15128 |
101 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.73102E-005 |
102 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 287.99844 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.96680 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23962 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24300 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.42193 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.63898 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.59004E-003 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.28623E-003 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.91905 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
114 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 261330.37610 |
115 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.28623E-003 |
116 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6891.54900 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 16.34653 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.41515E-002 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.26931 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.04667E-003 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.51786E-003 |
125 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.25784 |
126 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
128 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 173501.09260 |
129 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.51786E-003 |
130 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4575.29359 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 24.65761 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.68568E-002 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 4.93152 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.93364E-003 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.27141E-003 |
139 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.86762 |
140 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
142 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 259636.41850 |
143 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.27141E-003 |
144 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6846.91441 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 16.63344 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.25275E-002 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.32669 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.11770E-003 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.45358E-003 |
153 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.03482 |
154 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
156 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 166153.37956 |
157 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.45358E-003 |
158 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4381.67400 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.05097 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22724 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24200 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25434 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.60597 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.67666E-003 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.03290E-004 |
167 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.05097 |
168 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
170 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 34667.90961 |
171 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.03290E-004 |
172 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 914.05417 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.63013 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.44128E-002 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.32603 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.03547E-003 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.99923E-004 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.69280 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
184 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22852.43081 |
185 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.99923E-004 |
186 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 602.51919 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.53766 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.41125E-002 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.50753 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.04835E-003 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.01573E-004 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.04501 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
198 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 34471.62125 |
199 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.01573E-004 |
200 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 908.88202 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.70991 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.00076E-002 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.34198 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.23297E-003 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.95780E-004 |
209 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.67843 |
210 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
211 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
212 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22378.80108 |
213 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.95780E-004 |
214 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 590.03749 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.52456 |
216 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.06427 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.51067 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 25.02224 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.34466 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.33400 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.68933 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.33400 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.33875 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.33875 |
225 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
226 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.32248 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 62.31504 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 33.28116 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 124.63007 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 38.64722 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 96.33185 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 96.33185 |
233 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
234 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.40119 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.26525 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.40171 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.53049 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 6.93328 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.42587 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.42587 |
241 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
242 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.66501 |
243 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.00000 |
244 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.00000 |
245 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.71623 |
246 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 1.20016 |
247 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.71623 |
248 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.71623 |
249 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
250 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.20996 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 25.02224 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 25.02224 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 25.02224 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 25.02224 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 25.02224 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 25.02224 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 1.00000 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.52456 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.52456 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.52456 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.52456 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.52456 |
264 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.52456 |
265 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
266 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.06427 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.06427 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.06427 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 5.06427 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.06427 |
272 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.06427 |
273 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
274 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.51067 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.51067 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.51067 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.51067 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.51067 |
280 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.51067 |
281 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
282 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
283 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.33875 |
284 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 96.33185 |
285 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.42587 |
286 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.71623 |
287 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 25.02224 |
288 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.52456 |
289 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 5.06427 |
290 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.51067 |
291 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.33875 |
292 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_BOT WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.83742 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.91817 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.23336E-003 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
298 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 180924.25275 |
299 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.17441E-003 |
300 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.33875 |
301 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 160468.17343 |
302 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.40385E-003 |
303 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2203.12034 |
304 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.33875 |
305 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.17441E-003 |
306 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.20280E-005 |
307 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.40385E-003 |
308 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 96.33185 |
309 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 25.38195 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.89678 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.91820 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.24348E-003 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
315 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1695613.65493 |
316 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.84943E-002 |
317 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 96.33185 |
318 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 1627921.07461 |
319 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.42418E-002 |
320 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 21785.34874 |
321 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 96.33185 |
322 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.84943E-002 |
323 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.81951E-006 |
324 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.42418E-002 |
325 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.42587 |
326 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.82938 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.91816 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.23130E-003 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
332 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 182282.94119 |
333 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.21327E-003 |
334 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.42587 |
335 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 163291.12030 |
336 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.42854E-003 |
337 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2235.77134 |
338 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.42587 |
339 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.21327E-003 |
340 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.13420E-005 |
341 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.42854E-003 |
342 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.71623 |
343 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
344 | HeatExchanger:AirToAir:SensibleAndLatent | CAV_BAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 1.20016 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.47996 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.89639 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.37179E-003 |
349 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
350 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 100104.16501 |
351 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.86297E-003 |
352 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.71623 |
353 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 332267.78504 |
354 | Coil:Heating:Water | CAV_BAS HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
355 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
356 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2622.57515 |
357 | Fan:VariableVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.71623 |
358 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.86297E-003 |
359 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.66328E-004 |
360 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.74844E-004 |
361 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 25.02224 |
362 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
363 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 25.02224 |
364 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 510538.05280 |
365 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 323604.72822 |
366 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.25030E-002 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 25.02224 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 25.02224 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 25.02224 |
370 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 25.02224 |
371 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 510538.05280 |
372 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 510538.05280 |
373 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 33013.32304 |
374 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
375 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 25.02224 |
376 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 25.02224 |
377 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 510538.05280 |
378 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.25030E-002 |
379 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 33013.32304 |
380 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 2.27323E-004 |
381 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
382 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
383 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
384 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.52456 |
385 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
386 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.52456 |
387 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10406.59393 |
388 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6671.01369 |
389 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.54857E-004 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.52456 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.52456 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.52456 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.52456 |
394 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10406.59393 |
395 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10406.59393 |
396 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1525.07876 |
397 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
398 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.52456 |
399 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.52456 |
400 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 10406.59393 |
401 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.54857E-004 |
402 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1525.07876 |
403 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.06427 |
404 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
405 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.06427 |
406 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 100477.31926 |
407 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 64404.30777 |
408 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.46068E-003 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 5.06427 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 5.06427 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 5.06427 |
412 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.06427 |
413 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 100477.31926 |
414 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 100477.31926 |
415 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 15250.78758 |
416 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
417 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 5.06427 |
418 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.06427 |
419 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 100477.31926 |
420 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.46068E-003 |
421 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 15250.78758 |
422 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.51067 |
423 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
424 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.51067 |
425 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10131.86885 |
426 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6494.46413 |
427 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.48129E-004 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.51067 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.51067 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.51067 |
431 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.51067 |
432 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10131.86885 |
433 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10131.86885 |
434 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1525.07876 |
435 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
436 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.51067 |
437 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.51067 |
438 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 10131.86885 |
439 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.48129E-004 |
440 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1525.07876 |
441 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 6.17450E-002 |
442 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 10081.06886 |
443 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 6.17450E-002 |
444 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 7.40940 |
445 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 6.17450E-002 |
446 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 6.17450E-002 |
447 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 259174.67153 |
448 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
449 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 3.25301E-002 |
450 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 3.90361 |
451 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 3.25301E-002 |
452 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 9796.62506 |
453 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
454 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 3718385.50277 |
455 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 3718385.50000 |
456 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 3.25301E-002 |
457 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 6.17450E-002 |
458 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 7.40940 |
459 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 3.08725E-002 |
460 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 3489.73197 |
461 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 3.08725E-002 |
462 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 3489.73197 |
463 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 6.17450E-002 |
464 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.10436E-002 |
465 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1085445.37498 |
466 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1085445.00500 |
467 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 5.46576E-002 |
468 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 6.17450E-002 |
469 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.10436E-002 |
470 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1085445.37498 |
471 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1085445.00500 |
472 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 5.46576E-002 |
473 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.54667E-002 |
474 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.85601 |
475 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.54667E-002 |
476 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3944.78521 |
477 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.54667E-002 |
478 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 153572.98382 |
479 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at High Fan Speed [W/K] | 77743.21886 |
480 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 76786.49191 |
481 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
482 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/K] | 46645.93132 |
483 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 637095.96913 |
484 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 624479.74000 |
485 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.54667E-002 |
486 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
487 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
488 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
489 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
490 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
491 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.10932 |
492 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 13.11782 |
493 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.10932 |
494 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 27064.01806 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 42.54766 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1300904.74759 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 8.50953 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 162613.09345 |
499 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 42.54766 |
500 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1300904.74759 |
501 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 8.50953 |
502 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 162613.09345 |
503 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.62875E-002 |
504 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.62875E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 24899.49 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 459333.48 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 108545.48 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 18789.60 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 12862.52 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 20386.96 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 10533.47 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 247596.16 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 164382.02 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 245991.47 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 157421.46 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 32844.77 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 21650.60 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 32658.82 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 21201.91 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 93669.80 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 918988.37 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 94983.78 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 94837.77 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 264715.23 | 185219.02 | 79496.21 | 0.70 | 109715.24 | 1112.79 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2472867.28 | 1728387.50 | 744479.78 | 0.70 | 1003963.98 | 10182.76 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 266835.29 | 186734.65 | 80100.64 | 0.70 | 110944.82 | 1125.26 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 146918.42 | 102634.99 | 44283.43 | 0.70 | 63518.45 | 644.24 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 8.97 | 30.62 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 8.97 | 30.62 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.270 | 0.259 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.270 | 0.259 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.270 | 0.259 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.669 | 0.608 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_NORTH_0.45 | N/A | 1.647 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_NORTH_0.45 | N/A | 1.647 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_NORTH_0.45 | N/A | 1.647 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_NORTH_0.45 | N/A | 1.647 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_NORTH_0.45 | N/A | 1.647 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.669 | 0.608 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_EAST_0.45 | N/A | 1.647 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_EAST_0.45 | N/A | 1.647 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_EAST_0.45 | N/A | 1.647 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.669 | 0.608 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_SOUTH_0.45 | N/A | 1.647 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_SOUTH_0.45 | N/A | 1.647 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_SOUTH_0.45 | N/A | 1.647 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_SOUTH_0.45 | N/A | 1.647 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_SOUTH_0.45 | N/A | 1.647 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.669 | 0.608 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_WEST_0.45 | N/A | 1.647 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_WEST_0.45 | N/A | 1.647 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_WEST_0.45 | N/A | 1.647 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.627 | 0.573 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_NORTH_0.45 | N/A | 1.647 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.627 | 0.573 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_EAST_0.45 | N/A | 1.647 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.627 | 0.573 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_SOUTH_0.45 | N/A | 1.647 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.627 | 0.573 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_WEST_0.45 | N/A | 1.647 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.840 | 0.746 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_NORTH_0.45 | N/A | 1.647 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.840 | 0.746 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_EAST_0.45 | N/A | 1.647 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.840 | 0.746 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_SOUTH_0.45 | N/A | 1.647 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.840 | 0.746 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.29_SHGC_WEST_0.45 | N/A | 1.647 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.669 | 0.608 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.669 | 0.608 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.669 | 0.608 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.669 | 0.608 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.627 | 0.573 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.627 | 0.573 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.627 | 0.573 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.627 | 0.573 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.840 | 0.746 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.840 | 0.746 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.840 | 0.746 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.840 | 0.746 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.270 | 0.259 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.270 | 0.259 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.270 | 0.259 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 8.6086147106E-004 | 1.6273188434E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 2.7106071290E-003 | 5.6563265698E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 1.5844395164E-002 | 9.3279649806E-003 | Pass | Pass | 0.4819962208 | 0.4869668999 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1517462569 | 0.1340780245 | Pass | Pass | 0.7970335243 | 0.6927693777 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 9.9229447971E-003 | 9.8053511956E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 1.1256460798E-002 | 1.3139465966E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 1.3248041212E-002 | 2.4659671910E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 1.0307944608E-002 | 9.3777355579E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.5482060665 | 0.4950456178 | Pass | Pass | 0.7135906716 | 0.5983514253 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.6334014470 | 0.5828669333 | Pass | Pass | 0.7033262662 | 0.6048346769 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.5937274485 | 0.5429588558 | Pass | Pass | 0.7194517540 | 0.6164752460 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.5257119661 | 0.4811334088 | Pass | Pass | 0.7380483604 | 0.6311723707 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.7423566491 | 0.6277186963 | Pass | Pass | 0.6216913593 | 0.5811441775 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.7872122843 | 0.7727945243 | Pass | Pass | 0.6330469293 | 0.6124997712 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.7762188301 | 0.7356069517 | Pass | Pass | 0.6494406830 | 0.6004870683 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.7445403065 | 0.6885054625 | Pass | Pass | 0.6865454490 | 0.5933425040 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.9678059865E-003 | 3.5866277804E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.6340176906E-002 | 4.2893717326E-002 | Pass | Pass | 0.4837666021 | 0.4777196964 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.2188398441 | 0.1354639664 | Pass | Pass | 0.4869638444 | 0.4927710803 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.1376297847E-008 | 1.0289994285E-007 | Pass | Pass | 2.9929325201E-003 | 2.9523547607E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.0771917199E-003 | 1.8169881458E-003 | Pass | Pass | 1.5833567973E-003 | 1.4659457793E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.8904811615E-003 | 2.6107103123E-003 | Pass | Pass | 2.9063321152E-003 | 1.8105155084E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.3158410962E-004 | 6.7233574909E-005 | Pass | Pass | 2.5152957346E-005 | 1.1388165807E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 4214.93 | 104.70 | 0.00 | 37440.72 | 6109.79 | 47870.14 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.261 | 0.270 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.261 | 0.270 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.261 | 0.270 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.608 | 0.669 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.608 | 0.669 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.608 | 0.669 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.608 | 0.669 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.573 | 0.627 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.573 | 0.627 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.573 | 0.627 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.573 | 0.627 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.746 | 0.840 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.746 | 0.840 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.746 | 0.840 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.746 | 0.840 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.608 | 0.669 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.608 | 0.669 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.608 | 0.669 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.608 | 0.669 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.573 | 0.627 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.573 | 0.627 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.573 | 0.627 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.573 | 0.627 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.746 | 0.840 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.746 | 0.840 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.746 | 0.840 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.746 | 0.840 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.159 | 0.163 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.261 | 0.270 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.261 | 0.270 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.261 | 0.270 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.29_SHGC_NORTH_0.45 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.647 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.29_SHGC_NORTH_0.45 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.647 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.29_SHGC_NORTH_0.45 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.647 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.29_SHGC_NORTH_0.45 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.647 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.29_SHGC_NORTH_0.45 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.647 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.29_SHGC_EAST_0.45 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.647 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.29_SHGC_EAST_0.45 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.647 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.29_SHGC_EAST_0.45 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.647 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.29_SHGC_SOUTH_0.45 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.647 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.29_SHGC_SOUTH_0.45 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.647 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.29_SHGC_SOUTH_0.45 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.647 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.29_SHGC_SOUTH_0.45 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.647 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.29_SHGC_SOUTH_0.45 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.647 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.29_SHGC_WEST_0.45 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.647 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.29_SHGC_WEST_0.45 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.647 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.29_SHGC_WEST_0.45 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.647 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.29_SHGC_NORTH_0.45 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 1.647 | 0.451 | 0.497 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.29_SHGC_EAST_0.45 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 1.647 | 0.451 | 0.497 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.29_SHGC_SOUTH_0.45 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 1.647 | 0.451 | 0.497 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.29_SHGC_WEST_0.45 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 1.647 | 0.451 | 0.497 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.29_SHGC_NORTH_0.45 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 1.647 | 0.451 | 0.497 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.29_SHGC_EAST_0.45 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 1.647 | 0.451 | 0.497 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.29_SHGC_SOUTH_0.45 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 1.647 | 0.451 | 0.497 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.29_SHGC_WEST_0.45 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 1.647 | 0.451 | 0.497 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 1.647 | 0.451 | 0.497 | |||||||||||||||||
North Total or Average | 1390.74 | 1.647 | 0.451 | 0.497 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 1.647 | 0.451 | 0.497 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.6849 | 2779.43 | 24139.15 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 216.17 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 8.6849 | 2496.12 | 21678.66 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 194.14 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 8.6849 | 24961.20 | 216786.56 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 1941.36 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 8.6849 | 2496.12 | 21678.66 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 194.14 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 8.6849 | 313.41 | 2721.97 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 31.66 | 0.0000 | Y | 16.18 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 31.14 | 0.0000 | Y | 10.25 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 8.6849 | 313.42 | 2722.03 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 30.38 | 0.0000 | Y | 15.52 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 31.00 | 0.0000 | Y | 10.21 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 8.6849 | 3134.13 | 27219.72 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 31.59 | 0.0000 | Y | 161.43 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 8.6849 | 2019.75 | 17541.42 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 31.09 | 0.0000 | Y | 102.36 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 8.6849 | 3134.20 | 27220.31 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 30.37 | 0.0000 | Y | 155.17 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 8.6849 | 2019.75 | 17541.42 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 30.95 | 0.0000 | Y | 101.92 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 8.6849 | 313.41 | 2721.97 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 31.59 | 0.0000 | Y | 16.14 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 31.08 | 0.0000 | Y | 10.24 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 8.6849 | 313.42 | 2722.03 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 30.37 | 0.0000 | Y | 15.52 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 30.95 | 0.0000 | Y | 10.19 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 8.6849 | 783.68 | 6806.21 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 62.65 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 13.9016 | 36.20 | 503.28 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.16 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 13.9016 | 362.03 | 5032.75 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 51.55 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 13.9016 | 36.20 | 503.28 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.16 |
Interior Lighting Total | 8.7339 | 46320.38 | 404555.99 | 1033.03 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13271.55 | AstronomicalClock | - | 44.84 | 44.84 | 111.72 | |
EXTERIOR_LIGHTS_B | 989.48 | AstronomicalClock | - | 83.06 | 63.95 | 11.88 | |
EXTERIOR_LIGHTS_C | 26594.85 | AstronomicalClock | - | 83.06 | 52.41 | 261.62 | |
Exterior Lighting Total | 40855.88 | 385.22 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2152275.33 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 3718385.50 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1085445.00 | 5.91 | 1079177.10 | 5.88 | 8.97 | 30.62 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 1085445.00 | 5.91 | 1079177.10 | 5.88 | 8.97 | 30.62 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 640015.41 | |||||
CENTRAL BOILER | Boiler:HotWater | 624479.74 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1300904.75 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1300904.75 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 180924.25 | 264715.23 | 185219.02 | 79496.21 | 0.70 | - | 109715.24 | 1112.79 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1695613.65 | 2472867.28 | 1728387.50 | 744479.78 | 0.70 | - | 1003963.98 | 10182.76 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 182282.94 | 266835.29 | 186734.65 | 80100.64 | 0.70 | - | 110944.82 | 1125.26 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 100104.17 | 146918.42 | 102634.99 | 44283.43 | 0.70 | - | 63518.45 | 644.24 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 510538.05 | 323604.73 | 186933.32 | 0.63 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10406.59 | 6671.01 | 3735.58 | 0.64 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 100477.32 | 64404.31 | 36073.01 | 0.64 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10131.87 | 6494.46 | 3637.40 | 0.64 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 26263.76 | 24899.49 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 484850.71 | 459333.48 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 114551.90 | 108545.48 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 19830.93 | 18789.60 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 13575.53 | 12862.52 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 21517.13 | 20386.96 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 11123.15 | 10533.47 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 261330.38 | 247596.16 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 173501.09 | 164382.02 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 259636.42 | 245991.47 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 166153.38 | 157421.46 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 34667.91 | 32844.77 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 22852.43 | 21650.60 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 34471.62 | 32658.82 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 22378.80 | 21201.91 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 160468.17 | 93669.80 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 1627921.07 | 918988.37 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 163291.12 | 94983.78 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 100000.00 | 94837.77 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 510538.05 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10406.59 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 100477.32 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10131.87 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 33013.32 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 1525.08 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 15250.79 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 1525.08 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 10.34 | 23485.44 | 2271.59 | 1.00 | 1.12 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 96.33 | 218826.77 | 2271.59 | 1.00 | 1.08 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:50:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 10.43 | 23683.33 | 2271.59 | 1.00 | 1.12 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
CAV_BAS FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.72 | 13138.53 | 2298.46 | 1.00 | 1.13 | General | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 25.02 | 41267.85 | 1649.25 | 1.00 | 1.14 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.52 | 587.56 | 1120.11 | 1.00 | 1.58 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 5.06 | 5672.53 | 1120.11 | 1.00 | 1.15 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.51 | 572.01 | 1120.11 | 1.00 | 1.60 | General | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.061745 | 10081.07 | 163269.45 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.032530 | 9796.63 | 301156.09 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.030872 | 3489.73 | 113036.94 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.030872 | 3489.73 | 113036.94 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.015467 | 3944.79 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.109315 | 27064.02 | 247577.87 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 77941.89 | 77941.89 | 28.04 | 5.716 | 5.716 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00745 | 19.85 | 0.00700 | 1.200 | 0.00 |
CORE_BOTTOM | 82365.75 | 82365.75 | 33.00 | 6.040 | 6.040 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00738 | 19.85 | 0.00700 | 1.078 | 0.00 |
CORE_MID | 777782.57 | 777782.57 | 311.60 | 57.026 | 57.026 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00740 | 19.85 | 0.00700 | 10.778 | 0.00 |
CORE_TOP | 76407.22 | 76407.22 | 30.61 | 5.602 | 5.602 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00741 | 19.85 | 0.00700 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 14349.51 | 14349.51 | 45.78 | 1.062 | 1.062 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 24.00 | 24.00 | 0.00726 | 21.38 | 0.00700 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 20530.14 | 20530.14 | 101.65 | 1.519 | 1.519 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00712 | 21.79 | 0.00700 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 31224.06 | 31224.06 | 99.62 | 2.311 | 2.311 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00712 | 27.31 | 0.00701 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 23741.76 | 23741.76 | 117.55 | 1.757 | 1.757 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 24.00 | 24.00 | 0.00710 | 24.70 | 0.00700 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 134677.40 | 134677.40 | 429.71 | 9.967 | 9.967 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:10:00 | 24.00 | 24.00 | 0.00728 | 21.23 | 0.00700 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 220886.91 | 220886.91 | 1093.63 | 16.347 | 16.347 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00711 | 22.37 | 0.00700 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 333192.47 | 333192.47 | 1063.09 | 24.658 | 24.658 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00711 | 27.40 | 0.00701 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 224763.98 | 224763.98 | 1112.83 | 16.633 | 16.633 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 24.00 | 24.00 | 0.00711 | 24.44 | 0.00700 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 13814.85 | 13814.85 | 44.08 | 1.022 | 1.022 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:00:00 | 24.00 | 24.00 | 0.00727 | 21.38 | 0.00700 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 22027.56 | 22027.56 | 109.06 | 1.630 | 1.630 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00711 | 22.66 | 0.00700 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 34290.85 | 34290.85 | 109.41 | 2.538 | 2.538 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00711 | 27.40 | 0.00701 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 23105.66 | 23105.66 | 114.40 | 1.710 | 1.710 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | 24.00 | 24.00 | 0.00711 | 24.44 | 0.00700 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8986.66 | 8986.66 | 248.23 | 0.525 | 0.525 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | 27.00 | 27.00 | 0.00708 | 21.84 | 0.00700 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 86760.66 | 86760.66 | 2396.52 | 5.064 | 5.064 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | 27.00 | 27.00 | 0.00708 | 21.84 | 0.00700 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8748.83 | 8748.83 | 241.66 | 0.511 | 0.511 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | 27.00 | 27.00 | 0.00708 | 21.84 | 0.00700 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 372769.05 | 428684.41 | 547.02 | 21.758 | 25.022 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 18.12 | 0.00699 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 22.62 | 0.00006 | -41.90 | 0.00006 | 1.200 | 0.00 |
CORE_BOTTOM | 6745.16 | 6745.16 | 2.70 | 0.290 | 1.078 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 1.078 | 0.00 |
CORE_MID | 293230.77 | 293230.77 | 117.47 | 12.568 | 12.568 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 10.778 | 0.00 |
CORE_TOP | 80195.53 | 80195.53 | 32.13 | 3.466 | 3.466 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -41.90 | 0.00006 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 13877.87 | 13877.87 | 44.28 | 0.601 | 0.601 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 9499.70 | 9499.70 | 47.03 | 0.411 | 0.411 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | -41.90 | 0.00006 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 15056.74 | 15056.74 | 48.04 | 0.652 | 0.652 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00799 | -41.90 | 0.00006 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 7640.23 | 7640.23 | 37.83 | 0.330 | 0.330 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 182839.80 | 182839.80 | 583.38 | 7.919 | 7.919 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 121387.38 | 121387.38 | 601.00 | 5.258 | 5.258 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 181655.57 | 181655.57 | 579.59 | 7.868 | 7.868 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 116250.35 | 116250.35 | 575.57 | 5.035 | 5.035 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00797 | -41.90 | 0.00006 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 24251.05 | 24251.05 | 77.38 | 1.051 | 1.051 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 15985.64 | 15985.64 | 79.15 | 0.693 | 0.693 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 24113.82 | 24113.82 | 76.94 | 1.045 | 1.045 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 15654.48 | 15654.48 | 77.51 | 0.678 | 0.678 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -41.90 | 0.00006 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 24.33 | 0.00056 | -41.90 | 0.00006 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 22.48 | 0.00056 | -41.90 | 0.00006 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 19.67 | 0.00056 | -41.90 | 0.00006 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:30:00 | 18.00 | 27.00 | 0.00700 | -41.90 | 0.00006 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 10.34 | 10.34 | 3.07 | 3.07 | 10.3388 | 3.3340 | 10.3388 | 0.3225 | 0.3000 |
VAV_MID WITH REHEAT | 96.33 | 96.33 | 38.65 | 38.65 | 96.3318 | 38.6472 | 96.3318 | 0.4012 | 0.3000 |
VAV_TOP WITH REHEAT | 10.43 | 10.43 | 6.93 | 6.93 | 10.4259 | 6.9333 | 10.4259 | 0.6650 | 0.3000 |
CAV_BAS | 5.72 | 5.72 | 1.20 | 1.20 | 5.7162 | 1.2002 | 5.7162 | 0.2100 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 25.02 | 25.02 | 0.34 | 0.34 | 25.0222 | 25.0222 | 25.0222 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.52 | 0.52 | 0.02 | 0.02 | 0.5246 | 0.5246 | 0.5246 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 5.06 | 5.06 | 0.16 | 0.16 | 5.0643 | 5.0643 | 5.0643 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.51 | 0.51 | 0.02 | 0.02 | 0.5107 | 0.5107 | 0.5107 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 26263.757 | 26263.757 | 1.969163 | 0.00022977 | 548.120 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 26263.76 | 26263.76 | 1.969163 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00799549 | 50.8847 | 6745.16 | 0.00 | 26358.97 | 26358.97 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 484850.715 | 484850.715 | 19.331706 | 0.00424169 | 11539.074 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 484850.71 | 484850.71 | 19.331706 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00800000 | 50.9130 | 293230.77 | 0.00 | 486429.50 | 486429.50 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 114551.900 | 114551.900 | 3.466066 | 0.00100215 | 3022.916 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 114551.90 | 114551.90 | 3.466066 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00800000 | 50.9130 | 80195.53 | 0.00 | 114941.26 | 114941.26 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 19830.928 | 19830.928 | 0.600600 | 0.00017349 | 523.094 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19830.93 | 19830.93 | 0.600600 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798444 | 50.8155 | 13877.87 | 0.00 | 19896.71 | 19896.71 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 13575.527 | 13575.527 | 0.411206 | 0.00011876 | 358.068 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13575.53 | 13575.53 | 0.411206 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798548 | 50.8220 | 9499.70 | 0.00 | 13620.40 | 13620.40 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 21517.127 | 21517.127 | 0.651781 | 0.00018824 | 567.528 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21517.13 | 21517.13 | 0.651781 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00798652 | 50.8285 | 15056.74 | 0.00 | 21588.18 | 21588.18 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 11123.151 | 11123.151 | 0.351397 | 0.00009731 | 287.998 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11123.15 | 11123.15 | 0.351397 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797551 | 50.7595 | 7640.23 | 0.00 | 11157.25 | 11157.25 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 261330.376 | 261330.376 | 7.919048 | 0.00228623 | 6891.549 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 261330.38 | 261330.38 | 7.919048 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797531 | 50.7583 | 182839.80 | 0.00 | 262184.72 | 262184.72 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 173501.093 | 173501.093 | 5.257843 | 0.00151786 | 4575.294 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 173501.09 | 173501.09 | 5.257843 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797531 | 50.7583 | 121387.38 | 0.00 | 174067.53 | 174067.53 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 259636.418 | 259636.418 | 7.867624 | 0.00227141 | 6846.914 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 259636.42 | 259636.42 | 7.867624 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797513 | 50.7571 | 181655.57 | 0.00 | 260485.49 | 260485.49 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 166153.380 | 166153.380 | 5.034817 | 0.00145358 | 4381.674 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 166153.38 | 166153.38 | 5.034817 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797404 | 50.7503 | 116250.35 | 0.00 | 166696.86 | 166696.86 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 34667.910 | 34667.910 | 1.050973 | 0.00030329 | 914.054 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 34667.91 | 34555.50 | 1.050973 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797731 | 50.7709 | 24251.05 | 0.00 | 34779.99 | 34779.99 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 22852.431 | 22852.431 | 0.692802 | 0.00019992 | 602.519 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22852.43 | 22852.43 | 0.692802 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797705 | 50.7693 | 15985.64 | 0.00 | 22926.26 | 22926.26 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 34471.621 | 34471.621 | 1.045015 | 0.00030157 | 908.882 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 34471.62 | 34471.62 | 1.045015 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797717 | 50.7701 | 24113.82 | 0.00 | 34583.09 | 34583.09 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 22378.801 | 22378.801 | 0.678428 | 0.00019578 | 590.037 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22378.80 | 22378.80 | 0.678428 | 12.80 | 11.46 | 0.00800000 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 0.0000 | 21.00 | 0.00797656 | 50.7662 | 15654.48 | 0.00 | 22451.14 | 22451.14 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 180924.253 | -999.000 | 10.338751 | 0.00517441 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | 180924.25 | 174680.01 | 10.338751 | 24.84 | 15.43 | 0.00723336 | 10.92 | 9.60 | 0.00700000 | 27.40 | 0.00700714 | 16.15 | 24.5503 | 24.00 | 0.00730739 | 38.8006 | 139104.94 | 0.00 | 183746.11 | 183746.11 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 160468.173 | 160468.173 | 3.101625 | 0.00140385 | 2203.120 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 160468.17 | 160468.17 | 3.101625 | -30.63 | -30.63 | 0.00150214 | 12.80 | 11.46 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 81.8342 | 19.84 | 0.00797540 | 54.5375 | 37398.91 | 0.00 | 113228.32 | 113228.32 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1695613.655 | -999.000 | 96.331847 | 0.04849434 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:50:00 | 1695613.65 | 1634856.84 | 96.331847 | 24.90 | 15.46 | 0.00724348 | 10.92 | 9.60 | 0.00700000 | 27.40 | 0.00700714 | 16.15 | 26.3485 | 24.00 | 0.00732826 | 38.9102 | 1299087.67 | 0.00 | 1721915.56 | 1721915.56 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1627921.075 | 1627921.075 | 28.899554 | 0.01424176 | 21785.349 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 1627921.07 | 1627921.07 | 28.899554 | -34.49 | -34.49 | 0.00102692 | 12.80 | 11.46 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 87.8282 | 19.30 | 0.00795606 | 56.2694 | 442483.10 | 0.00 | 1110532.55 | 1110532.55 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 182282.941 | -999.000 | 10.425870 | 0.00521327 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 182282.94 | 176042.53 | 10.425870 | 24.83 | 15.42 | 0.00723130 | 10.92 | 9.60 | 0.00700000 | 27.40 | 0.00700714 | 16.15 | 24.3451 | 24.00 | 0.00730372 | 38.7814 | 140450.82 | 0.00 | 185128.29 | 185128.29 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 163291.120 | 163291.120 | 3.127761 | 0.00142854 | 2235.771 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 163291.12 | 163291.12 | 3.127761 | -31.03 | -31.03 | 0.00155435 | 12.80 | 11.46 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 81.1504 | 17.39 | 0.00796100 | 63.4384 | 60852.94 | 0.00 | 114817.24 | 114817.24 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 100104.165 | -999.000 | 5.716227 | 0.00286297 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 100104.17 | 94597.61 | 5.716227 | 24.48 | 15.42 | 0.00737179 | 10.90 | 9.59 | 0.00700000 | 26.07 | 0.00700513 | 15.67 | 20.9956 | 24.00 | 0.00748249 | 39.7197 | 69928.42 | 0.00 | 101664.17 | 101664.17 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 100000.000 | 100000.000 | 3.086362 | 0.00087484 | 2622.575 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 100000.00 | 100000.00 | 3.086362 | -8.80 | -12.33 | 0.00006450 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 38.8858 | 22.73 | 0.00006450 | 0.3741 | 0.00 | 0.00 | 100078.50 | 100078.50 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 510538.053 | 323604.728 | 25.022241 | 0.01250304 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 458430.46 | 456042.36 | -999.0 | 28.42 | 16.53 | 0.00704157 | 12.80 | 10.42 | 0.00700000 | 27.40 | 0.00700714 | 16.15 | -999.0000 | 27.00 | 0.00704204 | 31.3052 | 372288.16 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10406.594 | 6671.014 | 0.524555 | 0.00025486 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | 9295.96 | 9202.78 | -999.0 | 27.81 | 16.35 | 0.00707794 | 12.80 | 10.42 | 0.00700000 | 21.84 | 0.00699878 | 14.10 | -999.0000 | 27.00 | 0.00708037 | 31.4715 | 8986.66 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 100477.319 | 64404.308 | 5.064270 | 0.00246068 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | 89754.83 | 88824.53 | -999.0 | 27.80 | 16.35 | 0.00708060 | 12.80 | 10.42 | 0.00700000 | 21.84 | 0.00699878 | 14.10 | -999.0000 | 27.00 | 0.00708320 | 31.4841 | 86760.66 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10131.869 | 6494.464 | 0.510674 | 0.00024813 | -999.000 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | 9050.63 | 8957.51 | -999.0 | 27.80 | 16.35 | 0.00708001 | 12.80 | 10.42 | 0.00700000 | 21.84 | 0.00699878 | 14.10 | -999.0000 | 27.00 | 0.00708257 | 31.4813 | 8748.83 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 510538.053 | 510538.053 | 25.022241 | 0.01250304 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 510538.05 | 510538.05 | 25.022241 | -41.90 | -41.90 | 0.00006450 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 1.3524 | 27.00 | 0.00700000 | 31.1156 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10406.594 | 10406.594 | 0.524555 | 0.00025486 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10406.59 | 10406.59 | 0.524555 | -41.90 | -41.90 | 0.00006450 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 2.9801 | 25.17 | 0.00055877 | 2.7961 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 100477.319 | 100477.319 | 5.064270 | 0.00246068 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 100477.32 | 100477.32 | 5.064270 | -41.90 | -41.90 | 0.00006450 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 3.0868 | 23.70 | 0.00055879 | 3.0529 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10131.869 | 10131.869 | 0.510674 | 0.00024813 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10131.87 | 10131.87 | 0.510674 | -41.90 | -41.90 | 0.00006450 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 3.0611 | 21.96 | 0.00055829 | 3.3893 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 33013.323 | 33013.323 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 33013.32 | 33013.32 | 25.022241 | -0.57 | -0.57 | 0.00690621 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 1.3524 | 27.00 | 0.00700000 | 31.1156 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 1525.079 | 1525.079 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1525.08 | 1525.08 | 0.524555 | -1.25 | -6.13 | 0.00054404 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 2.9801 | 25.17 | 0.00055877 | 2.7961 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 15250.788 | 15250.788 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 15250.79 | 15250.79 | 5.064270 | -1.29 | -6.16 | 0.00054353 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 3.0868 | 23.70 | 0.00055879 | 3.0529 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 1525.079 | 1525.079 | -999.0 | -999.0 | -999.000 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1525.08 | 1525.08 | 0.510674 | -1.28 | -6.16 | 0.00054317 | 40.00 | 21.00 | 0.00800000 | -41.90 | 0.00006450 | -41.90 | 3.0611 | 21.96 | 0.00055829 | 3.3893 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 26263.757 | 26263.757 | 1.969163 | 0.00022977 | 548.120 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 32.52674008 | 54.44 | 82.22 | 27.78 | 3793219.49 | 0.6924 | 0.706322 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 26263.76 | 26263.76 | 1.0000 | 2.33432359 | 1.969163 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.22974337 | 60.00 | 32.22 | 27.78 | 0.000 | 26263.76 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.84 | 0.00799549 | 21.00 | 0.00799549 | 50.8847 | 6745.16 | 0.00 | 26358.97 | 26358.97 | 2.33432359 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 23.87 | 15.91 | 0.00800000 | 44351.7 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 484850.715 | 484850.715 | 19.331706 | 0.00424169 | 11539.074 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 32.52674008 | 54.44 | 82.22 | 27.78 | 3793219.49 | 12.7820 | 13.039280 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 484850.71 | 484850.71 | 1.0000 | 22.91656427 | 19.331706 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 4.24125287 | 60.00 | 32.22 | 27.78 | 0.000 | 484850.71 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 50.9130 | 293230.77 | 0.00 | 486429.50 | 486429.50 | 22.91656427 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 33.62 | 19.22 | 0.00800000 | 54285.9 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 114551.900 | 114551.900 | 3.466066 | 0.00100215 | 3022.916 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 32.52674008 | 54.44 | 82.22 | 27.78 | 3793219.49 | 3.0199 | 3.080689 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 114551.90 | 114551.90 | 1.0000 | 4.10881032 | 3.466066 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 1.00204777 | 60.00 | 32.22 | 27.78 | 0.000 | 114551.90 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 50.9130 | 80195.53 | 0.00 | 114941.26 | 114941.26 | 4.10881032 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61034.2 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19830.928 | 19830.928 | 0.600600 | 0.00017349 | 523.094 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 32.52674008 | 54.44 | 82.22 | 27.78 | 3793219.49 | 0.5228 | 0.533321 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19830.93 | 19830.93 | 1.0000 | 0.71197510 | 0.600600 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.17347191 | 60.00 | 32.22 | 27.78 | 0.000 | 19830.93 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798444 | 21.00 | 0.00798444 | 50.8155 | 13877.87 | 0.00 | 19896.71 | 19896.71 | 0.71197510 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61005.6 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13575.527 | 13575.527 | 0.411206 | 0.00011876 | 358.068 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 32.52674008 | 54.44 | 82.22 | 27.78 | 3793219.49 | 0.3579 | 0.365092 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13575.53 | 13575.53 | 1.0000 | 0.48746021 | 0.411206 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.11875252 | 60.00 | 32.22 | 27.78 | 0.000 | 13575.53 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798548 | 21.00 | 0.00798548 | 50.8220 | 9499.70 | 0.00 | 13620.40 | 13620.40 | 0.48746021 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61001.4 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21517.127 | 21517.127 | 0.651781 | 0.00018824 | 567.528 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 32.52674008 | 54.44 | 82.22 | 27.78 | 3793219.49 | 0.5673 | 0.578669 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21517.13 | 21517.13 | 1.0000 | 0.77264663 | 0.651781 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.18822201 | 60.00 | 32.22 | 27.78 | 0.000 | 21517.13 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00798652 | 21.00 | 0.00798652 | 50.8285 | 15056.74 | 0.00 | 21588.18 | 21588.18 | 0.77264663 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61000.4 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11123.151 | 11123.151 | 0.351397 | 0.00009731 | 287.998 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 32.52674008 | 54.44 | 82.22 | 27.78 | 3793219.49 | 0.2932 | 0.299139 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11123.15 | 11123.15 | 1.0000 | 0.41655994 | 0.351397 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.09730025 | 60.00 | 32.22 | 27.78 | 0.000 | 11123.15 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797551 | 21.00 | 0.00797551 | 50.7595 | 7640.23 | 0.00 | 11157.25 | 11157.25 | 0.41655994 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 39.07 | 20.90 | 0.00800000 | 59844.1 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 261330.376 | 261330.376 | 7.919048 | 0.00228623 | 6891.549 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 32.52674008 | 54.44 | 82.22 | 27.78 | 3793219.49 | 6.8894 | 7.028060 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 261330.38 | 261330.38 | 1.0000 | 9.38755043 | 7.919048 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 2.28599891 | 60.00 | 32.22 | 27.78 | 0.000 | 261330.38 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797531 | 21.00 | 0.00797531 | 50.7583 | 182839.80 | 0.00 | 262184.72 | 262184.72 | 9.38755043 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60988.8 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 173501.093 | 173501.093 | 5.257843 | 0.00151786 | 4575.294 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 32.52674008 | 54.44 | 82.22 | 27.78 | 3793219.49 | 4.5740 | 4.666033 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 173501.09 | 173501.09 | 1.0000 | 6.23285351 | 5.257843 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 1.51770841 | 60.00 | 32.22 | 27.78 | 0.000 | 173501.09 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797531 | 21.00 | 0.00797531 | 50.7583 | 121387.38 | 0.00 | 174067.53 | 174067.53 | 6.23285351 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60987.3 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 259636.418 | 259636.418 | 7.867624 | 0.00227141 | 6846.914 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 32.52674008 | 54.44 | 82.22 | 27.78 | 3793219.49 | 6.8448 | 6.982504 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 259636.42 | 259636.42 | 1.0000 | 9.32659016 | 7.867624 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 2.27118094 | 60.00 | 32.22 | 27.78 | 0.000 | 259636.42 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797513 | 21.00 | 0.00797513 | 50.7571 | 181655.57 | 0.00 | 260485.49 | 260485.49 | 9.32659016 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60989.2 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 166153.380 | 166153.380 | 5.034817 | 0.00145358 | 4381.674 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 32.52674008 | 54.44 | 82.22 | 27.78 | 3793219.49 | 4.3803 | 4.468428 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 166153.38 | 166153.38 | 1.0000 | 5.96846945 | 5.034817 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 1.45343397 | 60.00 | 32.22 | 27.78 | 0.000 | 166153.38 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797404 | 21.00 | 0.00797404 | 50.7503 | 116250.35 | 0.00 | 166696.86 | 166696.86 | 5.96846945 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60989.4 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 34667.910 | 34667.910 | 1.050973 | 0.00030329 | 914.054 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 32.52674008 | 54.44 | 82.22 | 27.78 | 3793219.49 | 0.9139 | 0.932338 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 34667.91 | 34555.50 | 1.0000 | 1.24586490 | 1.050973 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.30325906 | 60.00 | 32.22 | 27.78 | 0.000 | 34667.91 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797731 | 21.00 | 0.00797731 | 50.7709 | 24251.05 | 0.00 | 34779.99 | 34779.99 | 1.24586490 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60976.2 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22852.431 | 22852.431 | 0.692802 | 0.00019992 | 602.519 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 32.52674008 | 54.44 | 82.22 | 27.78 | 3793219.49 | 0.6025 | 0.614579 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22852.43 | 22852.43 | 1.0000 | 0.82127459 | 0.692802 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.19990264 | 60.00 | 32.22 | 27.78 | 0.000 | 22852.43 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797705 | 21.00 | 0.00797705 | 50.7693 | 15985.64 | 0.00 | 22926.26 | 22926.26 | 0.82127459 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60975.3 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 34471.621 | 34471.621 | 1.045015 | 0.00030157 | 908.882 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 32.52674008 | 54.44 | 82.22 | 27.78 | 3793219.49 | 0.9088 | 0.927059 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 34471.62 | 34471.62 | 1.0000 | 1.23880135 | 1.045015 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.30154202 | 60.00 | 32.22 | 27.78 | 0.000 | 34471.62 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797717 | 21.00 | 0.00797717 | 50.7701 | 24113.82 | 0.00 | 34583.09 | 34583.09 | 1.23880135 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60976.4 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22378.801 | 22378.801 | 0.678428 | 0.00019578 | 590.037 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 32.52674008 | 54.44 | 82.22 | 27.78 | 3793219.49 | 0.5900 | 0.601842 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22378.80 | 22378.80 | 1.0000 | 0.80423573 | 0.678428 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.19575954 | 60.00 | 32.22 | 27.78 | 0.000 | 22378.80 | -41.90 | 0.00006450 | -41.90 | 0.00000000 | 0.0000 | 20.95 | 0.00797656 | 21.00 | 0.00797656 | 50.7662 | 15654.48 | 0.00 | 22451.14 | 22451.14 | 0.80423573 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60975.9 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 180924.253 | -999.000 | 10.338751 | 0.00517441 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.2865 | 1004.8586 | 1.1854 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.338751 | 12.25596126 | 4197.9300 | 999.8980 | 61.73868348 | 15.00 | 6.67 | 8.33 | 2158925.01 | 8.3803 | 8.380294 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:40:00 | Sensible | 180924.25 | 174680.01 | 1.0000 | 12.25596126 | 10.338751 | 24.84 | 15.43 | 0.00723336 | 43381.8 | 10.92 | 9.60 | 0.00700000 | 28619.7 | 5.17388288 | 6.67 | 15.00 | 8.33 | 23485.436 | 157438.82 | 27.40 | 0.00700714 | 16.15 | 2.53819000 | 24.5503 | 24.00 | 0.00730739 | 24.00 | 0.00730739 | 38.8006 | 139104.94 | 0.00 | 183746.11 | 183746.11 | 12.25596126 | 24.84 | 15.58 | 0.00723336 | 43381.8 | 10.11 | 9.62 | 0.00723336 | 28389.4 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 160468.173 | 160468.173 | 3.101625 | 0.00140385 | 2203.120 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.338751 | 12.25596126 | 4197.9300 | 999.8980 | 32.52674008 | 54.44 | 82.22 | 27.78 | 3793219.49 | 4.2304 | 4.315534 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 160468.17 | 160468.17 | 1.0000 | 3.67678838 | 3.101625 | -30.63 | -30.63 | 0.00150214 | -27109.6 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 1.40370238 | 60.00 | 32.22 | 27.78 | 0.000 | 160468.17 | -41.90 | 0.00006450 | -41.90 | 2.53819000 | 81.8342 | 20.13 | 0.00797848 | 19.84 | 0.00797540 | 54.5375 | 37398.91 | 0.00 | 113228.32 | 113228.32 | 3.67678838 | 2.80 | -1.97 | 0.00150214 | 6578.1 | 33.36 | 13.47 | 0.00150214 | 37373.6 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1695613.655 | -999.000 | 96.331847 | 0.04849434 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.3053 | 1004.8586 | 1.1854 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 96.331847 | 114.19555616 | 4197.9300 | 999.8980 | 61.73868348 | 15.00 | 6.67 | 8.33 | 2158925.01 | 78.5397 | 78.539720 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 11:50:00 | Sensible | 1695613.65 | 1634856.84 | 1.0000 | 114.19555616 | 96.331847 | 24.90 | 15.46 | 0.00724348 | 43468.0 | 10.92 | 9.60 | 0.00700000 | 28619.7 | 48.48938896 | 6.67 | 15.00 | 8.33 | 218826.771 | 1476786.88 | 27.40 | 0.00700714 | 16.15 | 25.38195000 | 26.3485 | 24.00 | 0.00732826 | 24.00 | 0.00732826 | 38.9102 | 1299087.67 | 0.00 | 1721915.56 | 1721915.56 | 114.19555616 | 24.90 | 15.61 | 0.00724348 | 43468.0 | 10.09 | 9.62 | 0.00724348 | 28389.4 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 1627921.075 | 1627921.075 | 28.899554 | 0.01424176 | 21785.349 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 96.331847 | 114.19555616 | 4197.9300 | 999.8980 | 32.52674008 | 54.44 | 82.22 | 27.78 | 3793219.49 | 42.9166 | 43.780320 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 1627921.07 | 1627921.07 | 1.0000 | 34.25866685 | 28.899554 | -34.49 | -34.49 | 0.00102692 | -32153.3 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 14.24031092 | 60.00 | 32.22 | 27.78 | 0.000 | 1627921.07 | -41.90 | 0.00006450 | -41.90 | 25.38195000 | 87.8282 | 18.99 | 0.00797144 | 19.30 | 0.00795606 | 56.2694 | 442483.10 | 0.00 | 1110532.55 | 1110532.55 | 34.25866685 | 2.80 | -2.74 | 0.00102692 | 5387.2 | 35.00 | 13.65 | 0.00102692 | 37803.3 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 182282.941 | -999.000 | 10.425870 | 0.00521327 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.2826 | 1004.8586 | 1.1854 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.425870 | 12.35923551 | 4197.9300 | 999.8980 | 61.73868348 | 15.00 | 6.67 | 8.33 | 2158925.01 | 8.4432 | 8.443227 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 182282.94 | 176042.53 | 1.0000 | 12.35923551 | 10.425870 | 24.83 | 15.42 | 0.00723130 | 43368.4 | 10.92 | 9.60 | 0.00700000 | 28619.7 | 5.21273724 | 6.67 | 15.00 | 8.33 | 23683.335 | 158599.61 | 27.40 | 0.00700714 | 16.15 | 2.53819000 | 24.3451 | 24.00 | 0.00730372 | 24.00 | 0.00730372 | 38.7814 | 140450.82 | 0.00 | 185128.29 | 185128.29 | 12.35923551 | 24.83 | 15.58 | 0.00723130 | 43368.4 | 10.12 | 9.62 | 0.00723130 | 28389.4 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 163291.120 | 163291.120 | 3.127761 | 0.00142854 | 2235.771 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.425870 | 12.35923551 | 4197.9300 | 999.8980 | 32.52674008 | 54.44 | 82.22 | 27.78 | 3793219.49 | 4.3048 | 4.391452 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 163291.12 | 163291.12 | 1.0000 | 3.70777065 | 3.127761 | -31.03 | -31.03 | 0.00155435 | -27379.8 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 1.42839623 | 60.00 | 32.22 | 27.78 | 0.000 | 163291.12 | -41.90 | 0.00006450 | -41.90 | 2.53819000 | 81.1504 | 15.78 | 0.00796839 | 17.39 | 0.00796100 | 63.4384 | 60852.94 | 0.00 | 114817.24 | 114817.24 | 3.70777065 | 2.80 | -1.89 | 0.00155435 | 6709.0 | 33.53 | 13.59 | 0.00155435 | 37675.6 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 100104.165 | -999.000 | 5.716227 | 0.00286297 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.5438 | 1004.8586 | 1.1854 | CAV_BAS FAN | Fan:VariableVolume | 5.716227 | 6.77623953 | 4197.9300 | 999.8980 | 61.73868348 | 15.00 | 6.67 | 8.33 | 2158925.01 | 4.6368 | 4.636760 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 100104.17 | 94597.61 | 1.0000 | 6.77623953 | 5.716227 | 24.48 | 15.42 | 0.00737179 | 43370.3 | 10.90 | 9.59 | 0.00700000 | 28597.5 | 2.86267440 | 6.67 | 15.00 | 8.33 | 13138.527 | 86965.64 | 26.07 | 0.00700513 | 15.67 | 1.20015641 | 20.9956 | 24.00 | 0.00748249 | 24.00 | 0.00748249 | 39.7197 | 69928.42 | 0.00 | 101664.17 | 101664.17 | 6.77623953 | 24.48 | 15.57 | 0.00737179 | 43370.3 | 9.75 | 9.61 | 0.00737179 | 28367.3 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.086362 | 0.00087484 | 2622.575 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | CAV_BAS FAN | Fan:VariableVolume | 5.716227 | 6.77623953 | 4197.9300 | 999.8980 | 32.52674008 | 54.44 | 82.22 | 27.78 | 3793219.49 | 2.6363 | 2.689339 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.086362 | -8.80 | -12.33 | 0.00006450 | -8679.5 | 40.00 | 21.00 | 0.00800000 | 60796.0 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | -41.90 | 0.00006450 | -41.90 | 1.20015641 | 38.8858 | 0.00 | 0.00006450 | 22.73 | 0.00006450 | 0.3741 | 0.00 | 0.00 | 100078.50 | 100078.50 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.02 | 14.59 | 0.00000000 | 40240.8 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 510538.053 | 323604.728 | 25.022241 | 0.01250304 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9299 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | Sensible | 458430.46 | 456042.36 | 0.8979 | -999.0 | -999.0 | 28.42 | 16.53 | 0.00704157 | 46538.1 | 12.80 | 10.42 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 458430.46 | 27.40 | 0.00700714 | 16.15 | 0.33839277 | -999.0000 | 27.00 | 0.00704204 | 27.00 | 0.00704204 | 31.3052 | 372288.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10406.594 | 6671.014 | 0.524555 | 0.00025486 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9975 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | Sensible | 9295.96 | 9202.78 | 0.8933 | -999.0 | -999.0 | 27.81 | 16.35 | 0.00707794 | 46007.4 | 12.80 | 10.42 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9295.96 | 21.84 | 0.00699878 | 14.10 | 0.01563234 | -999.0000 | 27.00 | 0.00708037 | 27.00 | 0.00708037 | 31.4715 | 8986.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 100477.319 | 64404.308 | 5.064270 | 0.00246068 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.0025 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | Sensible | 89754.83 | 88824.53 | 0.8933 | -999.0 | -999.0 | 27.80 | 16.35 | 0.00708060 | 46008.5 | 12.80 | 10.42 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 89754.83 | 21.84 | 0.00699878 | 14.10 | 0.15632344 | -999.0000 | 27.00 | 0.00708320 | 27.00 | 0.00708320 | 31.4841 | 86760.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10131.869 | 6494.464 | 0.510674 | 0.00024813 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.0014 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 20:30:00 | Sensible | 9050.63 | 8957.51 | 0.8933 | -999.0 | -999.0 | 27.80 | 16.35 | 0.00708001 | 46008.4 | 12.80 | 10.42 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9050.63 | 21.84 | 0.00699878 | 14.10 | 0.01563234 | -999.0000 | 27.00 | 0.00708257 | 27.00 | 0.00708257 | 31.4813 | 8748.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 510538.053 | 510538.053 | 25.022241 | 0.01250304 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 510538.05 | 510538.05 | 1.0000 | 29.66234756 | 25.022241 | -41.90 | -41.90 | 0.00006450 | -41946.5 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 510538.05 | -41.90 | 0.00006450 | -41.90 | 0.33839277 | 1.3524 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 31.1156 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10406.594 | 10406.594 | 0.524555 | 0.00025486 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 10406.59 | 10406.59 | 1.0000 | 0.62182811 | 0.524555 | -41.90 | -41.90 | 0.00006450 | -41946.5 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10406.59 | -41.90 | 0.00006450 | -41.90 | 0.01563234 | 2.9801 | 0.00 | 0.00055877 | 25.17 | 0.00055877 | 2.7961 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 100477.319 | 100477.319 | 5.064270 | 0.00246068 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 100477.32 | 100477.32 | 1.0000 | 6.00338506 | 5.064270 | -41.90 | -41.90 | 0.00006450 | -41946.5 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 100477.32 | -41.90 | 0.00006450 | -41.90 | 0.15632344 | 3.0868 | 0.00 | 0.00055879 | 23.70 | 0.00055879 | 3.0529 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10131.869 | 10131.869 | 0.510674 | 0.00024813 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1854 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 10131.87 | 10131.87 | 1.0000 | 0.60537249 | 0.510674 | -41.90 | -41.90 | 0.00006450 | -41946.5 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10131.87 | -41.90 | 0.00006450 | -41.90 | 0.01563234 | 3.0611 | 0.00 | 0.00055829 | 21.96 | 0.00055829 | 3.3893 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33013.323 | 33013.323 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 25.022241 | 29.66234756 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 33013.32 | 33013.32 | 1.0000 | 29.66234756 | 25.022241 | -0.57 | -0.57 | 0.00690621 | 16695.3 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33013.32 | -41.90 | 0.00006450 | -41.90 | 0.33839277 | 1.3524 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 31.1156 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1525.079 | 1525.079 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.524555 | 0.62182811 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1525.08 | 1525.08 | 1.0000 | 0.62182811 | 0.524555 | -1.25 | -6.13 | 0.00054404 | 104.6 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1525.08 | -41.90 | 0.00006450 | -41.90 | 0.01563234 | 2.9801 | 0.00 | 0.00055877 | 25.17 | 0.00055877 | 2.7961 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 15250.788 | 15250.788 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 5.064270 | 6.00338506 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 15250.79 | 15250.79 | 1.0000 | 6.00338506 | 5.064270 | -1.29 | -6.16 | 0.00054353 | 58.4 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15250.79 | -41.90 | 0.00006450 | -41.90 | 0.15632344 | 3.0868 | 0.00 | 0.00055879 | 23.70 | 0.00055879 | 3.0529 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1525.079 | 1525.079 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1854 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.510674 | 0.60537249 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1525.08 | 1525.08 | 1.0000 | 0.60537249 | 0.510674 | -1.28 | -6.16 | 0.00054317 | 68.3 | 40.00 | 21.00 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1525.08 | -41.90 | 0.00006450 | -41.90 | 0.01563234 | 3.0611 | 0.00 | 0.00055829 | 21.96 | 0.00055829 | 3.3893 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 10.34 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 96.33 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 10.43 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 5.72 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 25.02 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 3241.83 | 4888.17 | 3001.17 |
CORE_BOTTOM | 1780.67 | 2512.33 | 14.83 |
CORE_MID | 1209.83 | 3939.67 | 592.33 |
CORE_TOP | 2614.00 | 4406.00 | 2120.17 |
PERIMETER_BOT_ZN_3 | 3273.50 | 3484.33 | 1862.67 |
PERIMETER_BOT_ZN_2 | 3790.17 | 3364.50 | 2030.00 |
PERIMETER_BOT_ZN_1 | 3703.33 | 3355.00 | 1902.33 |
PERIMETER_BOT_ZN_4 | 2706.33 | 3346.83 | 959.17 |
PERIMETER_MID_ZN_3 | 3599.33 | 4333.50 | 2830.67 |
PERIMETER_MID_ZN_2 | 3215.83 | 3531.00 | 2256.83 |
PERIMETER_MID_ZN_1 | 3673.17 | 3926.50 | 2301.33 |
PERIMETER_MID_ZN_4 | 3701.50 | 4238.17 | 2645.33 |
PERIMETER_TOP_ZN_3 | 3928.50 | 4543.17 | 3242.17 |
PERIMETER_TOP_ZN_2 | 4107.33 | 4226.33 | 2964.67 |
PERIMETER_TOP_ZN_1 | 3937.83 | 4176.17 | 2709.17 |
PERIMETER_TOP_ZN_4 | 3957.83 | 4479.50 | 3010.67 |
DATACENTER_BOT_ZN_6 | 5655.33 | 527.50 | 527.50 |
DATACENTER_MID_ZN_6 | 3883.83 | 435.17 | 53.17 |
DATACENTER_TOP_ZN_6 | 3308.17 | 984.67 | 116.17 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5442.33 | 5442.33 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 4763.67 | 0.00 | 3234.17 |
CORE_BOTTOM | 0.00 | 60.33 | 0.00 | 6.83 |
CORE_MID | 3.50 | 0.00 | 1.67 | 0.00 |
CORE_TOP | 35.83 | 0.00 | 6.83 | 0.00 |
PERIMETER_BOT_ZN_3 | 4.50 | 35.67 | 0.00 | 14.50 |
PERIMETER_BOT_ZN_2 | 8.50 | 41.00 | 0.00 | 30.00 |
PERIMETER_BOT_ZN_1 | 11.33 | 39.50 | 0.00 | 36.50 |
PERIMETER_BOT_ZN_4 | 1.67 | 56.67 | 0.00 | 20.67 |
PERIMETER_MID_ZN_3 | 148.00 | 6.67 | 46.67 | 0.33 |
PERIMETER_MID_ZN_2 | 104.00 | 21.33 | 18.33 | 16.17 |
PERIMETER_MID_ZN_1 | 75.83 | 32.33 | 10.50 | 30.17 |
PERIMETER_MID_ZN_4 | 66.00 | 23.67 | 8.50 | 7.33 |
PERIMETER_TOP_ZN_3 | 519.50 | 4.17 | 218.83 | 0.00 |
PERIMETER_TOP_ZN_2 | 279.67 | 18.00 | 65.83 | 14.83 |
PERIMETER_TOP_ZN_1 | 233.00 | 24.67 | 50.00 | 23.00 |
PERIMETER_TOP_ZN_4 | 208.17 | 22.50 | 47.83 | 7.50 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 567.50 | 4776.50 | 229.83 | 3244.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.11 | 149.60 | 6779.02 | 0.246 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.78 | 134.35 | 6849.35 | 1.140 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.78 | 134.35 | 6849.35 | 0.698 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.78 | 134.35 | 6849.35 | 0.655 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.00 | 16.87 | 860.00 | 1.160 | 0.013 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 1.903 | 0.013 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.00 | 16.87 | 860.02 | 1.959 | 0.012 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 1.925 | 0.013 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.00 | 16.87 | 860.00 | 0.811 | 0.029 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 1.547 | 0.032 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.00 | 16.87 | 860.02 | 1.828 | 0.029 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 1.504 | 0.030 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.00 | 16.87 | 860.00 | 0.820 | 0.036 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 1.650 | 0.037 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.00 | 16.87 | 860.02 | 1.773 | 0.036 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 1.486 | 0.037 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.429 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.428 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.428 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.51 | 42.18 | 1911.37 | 21.153 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.11 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.51 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.11 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.94 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.51 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1029.47 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 9663036.98 | 0.00 | 9663036.98 | 0.00 | 9663036.98 | 37848132.68 | 6877.03 | 1242.62 | 640.35 | 0.00 |
CORE_BOTTOM | 48976773.98 | 0.00 | 48976773.98 | 0.00 | 48976773.98 | 33990283.35 | 4614.80 | 44.10 | 4101.09 | 702.44 |
CORE_MID | 0.29E+09 | 0.00 | 0.29E+09 | 0.00 | 0.29E+09 | 0.34E+09 | 6470.10 | 33.31 | 2256.59 | 504.91 |
CORE_TOP | 26815563.43 | 0.00 | 26815563.43 | 0.00 | 26815563.43 | 33990283.35 | 6785.05 | 20.70 | 1954.24 | 442.37 |
PERIMETER_BOT_ZN_3 | 6256002.79 | 0.00 | 6256002.79 | 129862.25 | 6385865.04 | 4267819.30 | 5875.57 | 21.14 | 2863.29 | 702.44 |
PERIMETER_BOT_ZN_2 | 6649267.96 | 0.00 | 6649267.96 | 86574.77 | 6735842.73 | 2750345.05 | 3323.48 | 8.07 | 5428.45 | 702.44 |
PERIMETER_BOT_ZN_1 | 10557307.19 | 0.00 | 10557307.19 | 129862.25 | 10687169.43 | 4267912.63 | 3319.52 | 4.31 | 5436.17 | 702.44 |
PERIMETER_BOT_ZN_4 | 6829906.22 | 0.00 | 6829906.22 | 86574.77 | 6916480.99 | 2750345.05 | 3288.28 | 4.10 | 5467.62 | 702.44 |
PERIMETER_MID_ZN_3 | 42100350.18 | 0.00 | 42100350.18 | 304566.00 | 42404916.18 | 42678193.03 | 6301.51 | 47.89 | 2410.60 | 504.91 |
PERIMETER_MID_ZN_2 | 56868711.43 | 0.00 | 56868711.43 | 203043.86 | 57071755.29 | 27503450.52 | 3940.07 | 1.86 | 4818.07 | 1413.91 |
PERIMETER_MID_ZN_1 | 94159845.90 | 0.00 | 94159845.90 | 304566.00 | 94464411.90 | 42679126.28 | 3939.03 | 5.59 | 4815.38 | 504.91 |
PERIMETER_MID_ZN_4 | 50681018.54 | 0.00 | 50681018.54 | 203043.86 | 50884062.40 | 27503450.52 | 3941.07 | 1.14 | 4817.79 | 504.91 |
PERIMETER_TOP_ZN_3 | 4208281.40 | 0.00 | 4208281.40 | 378154.45 | 4586435.85 | 4267819.30 | 5755.15 | 45.93 | 2958.91 | 442.37 |
PERIMETER_TOP_ZN_2 | 5443295.03 | 0.00 | 5443295.03 | 252102.79 | 5695397.83 | 2750345.05 | 4053.40 | 3.29 | 4703.31 | 442.37 |
PERIMETER_TOP_ZN_1 | 9054869.97 | 0.00 | 9054869.97 | 378154.45 | 9433024.42 | 4267912.63 | 4053.03 | 3.58 | 4703.39 | 442.37 |
PERIMETER_TOP_ZN_4 | 4949457.30 | 0.00 | 4949457.30 | 252102.79 | 5201560.10 | 2750345.05 | 4050.66 | 1.58 | 4707.76 | 442.37 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.33E+09 | 0.00 | 0.33E+09 | 0.00 | 0.33E+09 | 10671554.30 | 1.33 | 8.83 | 8749.83 | 2816.67 |
Total Facility | 0.58E+10 | 0.00 | 0.58E+10 | 11845585.74 | 0.58E+10 | 0.50E+10 | 8755.00 | 4391.11 | 8758.67 | 3725.67 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 0.4517 | 0.0000 | 0.4517 | 0.0000 | 0.4517 | 1.2002 | 4060.03 | 1242.62 | 640.35 |
CORE_BOTTOM | 2.1155 | 0.0000 | 2.1155 | 0.0000 | 2.1155 | 1.0778 | 2289.78 | 38.38 | 3614.84 |
CORE_MID | 12.9771 | 0.0000 | 12.9771 | 0.0000 | 12.9771 | 10.7782 | 3768.22 | 32.14 | 2142.64 |
CORE_TOP | 1.2192 | 0.0000 | 1.2192 | 0.0000 | 1.2192 | 1.0778 | 4057.41 | 20.25 | 1865.34 |
PERIMETER_BOT_ZN_3 | 0.2707 | 0.0000 | 0.2707 | 0.0029 | 0.2736 | 0.1353 | 3529.59 | 14.61 | 2398.79 |
PERIMETER_BOT_ZN_2 | 0.2864 | 0.0000 | 0.2864 | 0.0019 | 0.2883 | 0.0872 | 1124.16 | 6.47 | 4812.37 |
PERIMETER_BOT_ZN_1 | 0.4574 | 0.0000 | 0.4574 | 0.0029 | 0.4603 | 0.1353 | 1119.88 | 3.35 | 4819.77 |
PERIMETER_BOT_ZN_4 | 0.2896 | 0.0000 | 0.2896 | 0.0019 | 0.2915 | 0.0872 | 1093.48 | 3.69 | 4845.83 |
PERIMETER_MID_ZN_3 | 1.8956 | 0.0000 | 1.8956 | 0.0068 | 1.9024 | 1.3533 | 3600.14 | 46.85 | 2296.02 |
PERIMETER_MID_ZN_2 | 2.3317 | 0.0000 | 2.3317 | 0.0049 | 2.3366 | 0.8721 | 1266.62 | 1.04 | 3766.33 |
PERIMETER_MID_ZN_1 | 4.2735 | 0.0000 | 4.2735 | 0.0068 | 4.2803 | 1.3533 | 1263.32 | 4.49 | 4675.19 |
PERIMETER_MID_ZN_4 | 2.2676 | 0.0000 | 2.2676 | 0.0046 | 2.2722 | 0.8721 | 1266.76 | 0.46 | 4675.78 |
PERIMETER_TOP_ZN_3 | 0.1917 | 0.0000 | 0.1917 | 0.0085 | 0.2002 | 0.1353 | 3029.79 | 45.49 | 2867.72 |
PERIMETER_TOP_ZN_2 | 0.2486 | 0.0000 | 0.2486 | 0.0057 | 0.2543 | 0.0872 | 1334.42 | 2.65 | 4605.93 |
PERIMETER_TOP_ZN_1 | 0.4144 | 0.0000 | 0.4144 | 0.0085 | 0.4229 | 0.1353 | 1334.08 | 2.70 | 4606.22 |
PERIMETER_TOP_ZN_4 | 0.2240 | 0.0000 | 0.2240 | 0.0057 | 0.2296 | 0.0872 | 1332.44 | 1.16 | 4609.41 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 10.8289 | 0.0000 | 10.8289 | 0.0000 | 10.8289 | 0.3384 | 1.00 | 8.83 | 5933.17 |
Total Facility | 255.6170 | 0.0000 | 255.6170 | 0.2696 | 255.8866 | 158.4706 | 5938.00 | 4374.85 | 5942.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 0.11E+09 | 0.00 | 0.11E+09 | 48026705.38 | 3337.31 | 5.11 | 5417.58 | 702.44 |
VAV_MID WITH REHEAT | 0.75E+09 | 0.00 | 0.75E+09 | 0.48E+09 | 3985.47 | 2.53 | 4771.99 | 504.91 |
VAV_TOP WITH REHEAT | 70926006.53 | 0.00 | 70926006.53 | 48026705.38 | 4074.61 | 1.09 | 4684.30 | 441.85 |
CAV_BAS | 13579854.97 | 0.00 | 13579854.97 | 37848132.68 | 6762.02 | 0.53 | 1997.45 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.46E+09 | 0.00 | 0.46E+09 | 10671554.30 | 1.33 | 0.00 | 8758.67 | 2816.67 |
AIRLOOP DATACENTER BOT | 343300.97 | 0.00 | 343300.97 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3433009.67 | 0.00 | 3433009.67 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 343300.97 | 0.00 | 343300.97 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 4.8055 | 0.0000 | 4.8055 | 1.5229 | 1129.16 | 2.32 | 4811.53 |
VAV_MID WITH REHEAT | 33.7062 | 0.0000 | 33.7062 | 15.2292 | 1298.02 | 2.36 | 4642.61 |
VAV_TOP WITH REHEAT | 3.2292 | 0.0000 | 3.2292 | 1.5229 | 1352.26 | 1.07 | 4589.67 |
CAV_BAS | 0.6347 | 0.0000 | 0.6347 | 1.2002 | 3945.02 | 0.53 | 1997.45 |
AIRLOOP DATACENTER BASEMENT | 15.2175 | 0.0000 | 15.2175 | 0.3384 | 1.00 | 0.00 | 5942.00 |
AIRLOOP DATACENTER BOT | 0.0160 | 0.0000 | 0.0160 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1605 | 0.0000 | 0.1605 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0160 | 0.0000 | 0.0160 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 56.06 | 3526.25 | 0.00 | 0.00 | 0.00 | 2085.28 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.00 | 3014.01 | 0.00 | 0.00 | 0.00 | 2424.64 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.00 | 2732.35 | 0.00 | 0.00 | 0.00 | 2549.25 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 1213.50 | 658.63 | 0.00 | 157.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 8.83 | 8749.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 14.5440 | 7.9592 | 0.0000 | 0.0000 | 0.0000 | 2.5303 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 56.4142 | 0.0000 | 0.0000 | 0.0000 | 24.2462 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 5.7055 | 0.0000 | 0.0000 | 0.0000 | 2.4030 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.6872 | 2.2906 | 0.0000 | 1.3907 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.5251 | 15.2424 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0220 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2197 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0220 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1500 |
Defaulted Fields | 1184 |
Fields with Defaults | 3957 |
Autosized Fields | 338 |
Autosizable Fields | 417 |
Autocalculated Fields | 227 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 27376.80 | 300535.12 | 04-SEP-17:40 | 2092003.05 | 11-AUG-15:20 |
Electricity:Building | 17971.85 | 217189.06 | 06-MAY-18:20 | 1104084.83 | 01-DEC-08:10 |
Electricity:Zone:BASEMENT | 640.57 | 14055.89 | 01-JAN-00:10 | 32859.63 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 17971.85 | 217189.06 | 06-MAY-18:20 | 1104084.83 | 01-DEC-08:10 |
InteriorLights:Electricity | 3295.46 | 9932.90 | 02-APR-17:20 | 325713.14 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 216.17 | 598.35 | 01-JAN-00:10 | 19402.09 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3295.46 | 9932.90 | 02-APR-17:20 | 325713.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 3295.46 | 9932.90 | 02-APR-17:20 | 325713.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 216.17 | 598.35 | 01-JAN-00:10 | 19402.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3295.46 | 9932.90 | 02-APR-17:20 | 325713.14 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 483.75 | 4990.59 | 01-JAN-00:10 | 34631.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4837.49 | 49905.77 | 01-JAN-00:10 | 346310.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1941.37 | 5373.60 | 01-JAN-00:10 | 174244.37 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1941.37 | 5373.60 | 01-JAN-00:10 | 174244.37 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 483.75 | 4990.58 | 01-JAN-00:10 | 34631.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 52.54 | 617.00 | 02-APR-17:10 | 4348.36 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 16.18 | 57.83 | 12-FEB-12:00 | 2187.81 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 16.18 | 57.83 | 12-FEB-12:00 | 2187.81 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 33.69 | 397.62 | 02-APR-17:10 | 2802.25 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 10.25 | 37.27 | 16-JAN-12:20 | 1409.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 10.25 | 37.27 | 16-JAN-12:20 | 1409.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 51.89 | 617.01 | 12-MAR-17:10 | 4348.44 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 15.52 | 57.83 | 15-JAN-11:50 | 2187.86 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 15.52 | 57.83 | 15-JAN-11:50 | 2187.86 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 33.64 | 397.61 | 12-MAR-17:10 | 2802.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 10.21 | 37.27 | 05-FEB-12:10 | 1409.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 10.21 | 37.27 | 05-FEB-12:10 | 1409.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 525.08 | 6169.98 | 02-APR-17:10 | 43483.64 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 161.43 | 578.27 | 12-FEB-11:10 | 21878.12 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 161.43 | 578.27 | 12-FEB-11:10 | 21878.12 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 336.72 | 3976.17 | 02-APR-17:10 | 28022.51 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 102.36 | 372.66 | 16-JAN-12:00 | 14099.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 102.36 | 372.66 | 16-JAN-12:00 | 14099.09 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 518.83 | 6170.07 | 12-MAR-17:10 | 43484.45 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 155.17 | 578.28 | 15-JAN-11:50 | 21878.60 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 155.17 | 578.28 | 15-JAN-11:50 | 21878.60 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 336.27 | 3976.14 | 12-MAR-17:10 | 28022.42 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 101.92 | 372.66 | 05-FEB-12:10 | 14099.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 101.92 | 372.66 | 05-FEB-12:10 | 14099.09 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 52.51 | 617.00 | 02-APR-17:10 | 4348.36 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 16.14 | 57.83 | 12-FEB-11:10 | 2187.81 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 16.14 | 57.83 | 12-FEB-11:10 | 2187.81 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 33.67 | 397.62 | 02-APR-17:10 | 2802.25 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 10.24 | 37.27 | 16-JAN-12:00 | 1409.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 10.24 | 37.27 | 16-JAN-12:00 | 1409.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 51.88 | 617.01 | 12-MAR-17:10 | 4348.44 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 15.52 | 57.83 | 15-JAN-11:40 | 2187.86 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 15.52 | 57.83 | 15-JAN-11:40 | 2187.86 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 33.63 | 397.61 | 12-MAR-17:10 | 2802.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 10.19 | 37.27 | 05-FEB-11:50 | 1409.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 10.19 | 37.27 | 05-FEB-11:50 | 1409.91 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7557.51 | 95212.03 | 01-JAN-00:10 | 385103.08 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 62.65 | 303.90 | 01-JAN-00:10 | 5470.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 62.65 | 303.90 | 01-JAN-00:10 | 5470.56 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 159.04 | 1973.61 | 01-JAN-00:10 | 8244.54 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1590.36 | 19736.13 | 01-JAN-00:10 | 82445.36 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 51.55 | 250.08 | 01-JAN-00:10 | 4501.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 51.55 | 250.08 | 01-JAN-00:10 | 4501.14 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 159.04 | 1973.61 | 01-JAN-00:10 | 8244.54 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 1188.06 | 3981.08 | 12-JAN-03:20 | 368940.66 | 30-JUN-12:30 |
HeatRejection:Electricity | 204.77 | 29.83 | 12-JAN-08:10 | 81077.84 | 29-JUN-10:50 |
General:HeatRejection:Electricity | 204.77 | 29.83 | 12-JAN-08:10 | 81077.84 | 29-JUN-10:50 |
Electricity:HVAC | 5320.07 | 54534.28 | 04-SEP-17:40 | 514599.32 | 10-AUG-15:50 |
ExteriorEquipment:Electricity | 2566.64 | 20217.42 | 01-JAN-00:10 | 233439.18 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 55.05 | 979.82 | 01-JAN-00:10 | 3454.84 | 01-DEC-08:20 |
ElectricityPurchased:Facility | 27376.80 | 300535.12 | 04-SEP-17:40 | 2092003.05 | 11-AUG-15:20 |
ElectricityPurchased:Plant | 27376.80 | 300535.12 | 04-SEP-17:40 | 2092003.05 | 11-AUG-15:20 |
Cogeneration:ElectricityPurchased | 27376.80 | 300535.12 | 04-SEP-17:40 | 2092003.05 | 11-AUG-15:20 |
General:Cogeneration:ElectricityPurchased | 27376.80 | 300535.12 | 04-SEP-17:40 | 2092003.05 | 11-AUG-15:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 27376.80 | 300535.12 | 04-SEP-17:40 | 2092003.05 | 11-AUG-15:20 |
ElectricityNet:Plant | 27376.80 | 300535.12 | 04-SEP-17:40 | 2092003.05 | 11-AUG-15:20 |
Cogeneration:ElectricityNet | 27376.80 | 300535.12 | 04-SEP-17:40 | 2092003.05 | 11-AUG-15:20 |
General:Cogeneration:ElectricityNet | 27376.80 | 300535.12 | 04-SEP-17:40 | 2092003.05 | 11-AUG-15:20 |
Fans:Electricity | 2543.56 | 48099.95 | 02-JAN-06:00 | 291366.09 | 10-AUG-15:50 |
General:Fans:Electricity | 2543.56 | 48099.95 | 02-JAN-06:00 | 291366.09 | 10-AUG-15:50 |
ExteriorLights:Electricity | 385.22 | 0.00 | 01-JAN-11:20 | 40855.88 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 385.22 | 0.00 | 01-JAN-11:20 | 40855.88 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 2505.76 | 19200.00 | 01-JAN-00:10 | 229608.34 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 52.57 | 0.00 | 01-JAN-00:10 | 6524.59 | 02-JAN-08:20 |
General:HeatRecovery:Electricity | 52.57 | 0.00 | 01-JAN-00:10 | 6524.59 | 02-JAN-08:20 |
Cooling:Electricity | 772.41 | 1557.21 | 12-JAN-08:10 | 342267.28 | 11-AUG-15:20 |
General:Cooling:Electricity | 772.41 | 1557.21 | 12-JAN-08:10 | 342267.28 | 11-AUG-15:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 2094.67 | 0.00 | 02-JUN-21:00 | 100000.00 | 01-MAR-22:10 |
General:Humidifier:Electricity | 2094.67 | 0.00 | 02-JUN-21:00 | 100000.00 | 01-MAR-22:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 553.36 | 0.00 | 01-JAN-00:10 | 63524.99 | 03-APR-11:40 |
Water Heater:WaterSystems:Electricity | 553.36 | 0.00 | 01-JAN-00:10 | 63524.99 | 03-APR-11:40 |
Pumps:Electricity | 231.74 | 3944.79 | 01-JAN-00:40 | 42500.93 | 19-JUL-12:50 |
General:Pumps:Electricity | 231.74 | 3944.79 | 01-JAN-00:40 | 42500.93 | 19-JUL-12:50 |
WIRED_LTG_ELECTRICITY | 92.60 | 0.00 | 01-JAN-00:10 | 9152.54 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 4593.99 | 0.00 | 01-JAN-00:40 | 2541901.65 | 27-FEB-07:30 |
NaturalGas:Plant | 4593.99 | 0.00 | 01-JAN-00:40 | 2541901.65 | 27-FEB-07:30 |
Heating:NaturalGas | 4593.99 | 0.00 | 01-JAN-00:40 | 2541901.65 | 27-FEB-07:30 |
Boiler:Heating:NaturalGas | 4593.99 | 0.00 | 01-JAN-00:40 | 2541901.65 | 27-FEB-07:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 4374.31 | 3271.80 | 12-JAN-08:10 | 2093858.07 | 11-AUG-15:40 |
PlantLoopCoolingDemand:HVAC | 4374.31 | 3271.80 | 12-JAN-08:10 | 2093858.07 | 11-AUG-15:40 |
CoolingCoils:PlantLoopCoolingDemand | 4374.31 | 3271.80 | 12-JAN-08:10 | 2093858.07 | 11-AUG-15:40 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 4350.16 | 0.00 | 06-JUN-02:20 | 0.00 | 21-JUL-15:50 |
Water:HVAC | 779.22 | 0.00 | 02-JUN-21:00 | 0.00 | 02-MAR-04:10 |
Humidifier:Water | 779.22 | 0.00 | 02-JUN-21:00 | 0.00 | 02-MAR-04:10 |
General:Humidifier:Water | 779.22 | 0.00 | 02-JUN-21:00 | 0.00 | 02-MAR-04:10 |
MainsWater:Facility | 4350.16 | 0.00 | 06-JUN-02:20 | 0.00 | 21-JUL-15:50 |
MainsWater:HVAC | 779.22 | 0.00 | 02-JUN-21:00 | 0.00 | 02-MAR-04:10 |
Humidifier:MainsWater | 779.22 | 0.00 | 02-JUN-21:00 | 0.00 | 02-MAR-04:10 |
General:Humidifier:MainsWater | 779.22 | 0.00 | 02-JUN-21:00 | 0.00 | 02-MAR-04:10 |
Water:Plant | 3570.94 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-15:50 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 3570.94 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-15:50 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 1290.77 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-15:50 |
General:HeatRejection:Water | 1290.77 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-15:50 |
HeatRejection:MainsWater | 1290.77 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-15:50 |
General:HeatRejection:MainsWater | 1290.77 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-15:50 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 39748.86 | 91882.43 | 02-JAN-06:00 | 8788111.47 | 11-AUG-15:20 |
EnergyTransfer:Building | 19070.01 | 88770.29 | 06-JAN-22:10 | 1713509.91 | 10-AUG-15:30 |
EnergyTransfer:Zone:BASEMENT | 233.42 | 0.00 | 01-JAN-00:10 | 118633.85 | 13-OCT-07:20 |
Heating:EnergyTransfer | 1784.04 | 0.00 | 01-FEB-00:20 | 1403455.39 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 545.32 | 11-FEB-07:30 |
General:Heating:EnergyTransfer | 1784.04 | 0.00 | 01-FEB-00:20 | 1403455.39 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 545.32 | 11-FEB-07:30 |
Cooling:EnergyTransfer | 17285.97 | 82708.70 | 02-JAN-04:40 | 1713509.91 | 10-AUG-15:30 |
Cooling:EnergyTransfer:Zone:BASEMENT | 233.42 | 0.00 | 01-JAN-00:10 | 118633.85 | 13-OCT-07:20 |
General:Cooling:EnergyTransfer | 17285.97 | 82708.70 | 02-JAN-04:40 | 1713509.91 | 10-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 233.42 | 0.00 | 01-JAN-00:10 | 118633.85 | 13-OCT-07:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 748.22 | 0.00 | 01-JAN-00:10 | 71263.84 | 24-AUG-13:30 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 748.22 | 0.00 | 01-JAN-00:10 | 71263.84 | 24-AUG-13:30 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 748.22 | 0.00 | 01-JAN-00:10 | 71263.84 | 24-AUG-13:30 |
EnergyTransfer:Zone:CORE_MID | 4047.67 | 0.00 | 01-JAN-00:40 | 460874.15 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 31.47 | 0.00 | 01-JAN-00:20 | 460874.15 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 31.47 | 0.00 | 01-JAN-00:20 | 460874.15 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4016.20 | 0.00 | 01-JAN-00:40 | 433930.28 | 24-JUL-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4016.20 | 0.00 | 01-JAN-00:40 | 433930.28 | 24-JUL-13:10 |
EnergyTransfer:Zone:CORE_TOP | 356.16 | 0.00 | 01-JAN-00:40 | 72824.10 | 11-DEC-05:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 48.47 | 0.00 | 01-JAN-00:40 | 72824.10 | 11-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 48.47 | 0.00 | 01-JAN-00:40 | 72824.10 | 11-DEC-05:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 307.69 | 0.00 | 01-JAN-00:20 | 47129.43 | 21-JUL-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 307.69 | 0.00 | 01-JAN-00:20 | 47129.43 | 21-JUL-15:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 82.11 | 0.00 | 01-JAN-00:10 | 15421.89 | 07-JUL-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 5.57 | 0.00 | 01-JAN-00:10 | 9577.00 | 12-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 5.57 | 0.00 | 01-JAN-00:10 | 9577.00 | 12-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 76.53 | 0.00 | 01-JAN-00:10 | 15421.89 | 07-JUL-05:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 76.53 | 0.00 | 01-JAN-00:10 | 15421.89 | 07-JUL-05:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 85.47 | 0.00 | 01-JAN-00:10 | 20776.15 | 07-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 5.24 | 0.00 | 01-JAN-00:10 | 7028.63 | 27-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 5.24 | 0.00 | 01-JAN-00:10 | 7028.63 | 27-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 80.23 | 0.00 | 01-JAN-00:10 | 20776.15 | 07-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 80.23 | 0.00 | 01-JAN-00:10 | 20776.15 | 07-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 139.09 | 0.00 | 01-JAN-00:10 | 30990.73 | 31-AUG-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 8.87 | 0.00 | 01-JAN-00:10 | 12663.30 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 8.87 | 0.00 | 01-JAN-00:10 | 12663.30 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 130.22 | 0.00 | 01-JAN-00:10 | 30990.73 | 31-AUG-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 130.22 | 0.00 | 01-JAN-00:10 | 30990.73 | 31-AUG-13:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 90.35 | 0.00 | 01-JAN-00:10 | 18745.46 | 06-JUL-17:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.73 | 0.00 | 01-JAN-00:10 | 5576.35 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.73 | 0.00 | 01-JAN-00:10 | 5576.35 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 89.63 | 0.00 | 01-JAN-00:10 | 18745.46 | 06-JUL-17:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 89.63 | 0.00 | 01-JAN-00:10 | 18745.46 | 06-JUL-17:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 760.41 | 0.00 | 01-JAN-00:40 | 140460.96 | 11-JUL-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 375.27 | 0.00 | 01-JAN-00:40 | 137489.96 | 30-JAN-04:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 375.27 | 0.00 | 01-JAN-00:40 | 137489.96 | 30-JAN-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 385.15 | 0.00 | 01-JAN-00:10 | 140460.96 | 11-JUL-05:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 385.15 | 0.00 | 01-JAN-00:10 | 140460.96 | 11-JUL-05:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 802.65 | 0.00 | 01-JAN-00:40 | 207716.55 | 07-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 240.14 | 0.00 | 01-JAN-00:40 | 139221.07 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 240.14 | 0.00 | 01-JAN-00:40 | 139221.07 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 562.51 | 0.00 | 01-JAN-00:20 | 207716.55 | 07-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 562.51 | 0.00 | 01-JAN-00:20 | 207716.55 | 07-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1302.74 | 0.00 | 01-JAN-00:40 | 316585.87 | 31-AUG-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 280.21 | 0.00 | 01-JAN-00:40 | 206413.61 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 280.21 | 0.00 | 01-JAN-00:40 | 206413.61 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1022.53 | 0.00 | 01-JAN-00:20 | 316585.87 | 31-AUG-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1022.53 | 0.00 | 01-JAN-00:20 | 316585.87 | 31-AUG-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 661.74 | 0.00 | 01-JAN-00:40 | 174517.90 | 06-JUL-17:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 190.84 | 0.00 | 01-JAN-00:40 | 130683.65 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 190.84 | 0.00 | 01-JAN-00:40 | 130683.65 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 470.91 | 0.00 | 01-JAN-00:20 | 174517.90 | 06-JUL-17:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 470.91 | 0.00 | 01-JAN-00:20 | 174517.90 | 06-JUL-17:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 108.12 | 0.00 | 01-JAN-00:40 | 15229.18 | 30-JAN-04:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 74.48 | 0.00 | 01-JAN-00:40 | 15229.18 | 30-JAN-04:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 74.48 | 0.00 | 01-JAN-00:40 | 15229.18 | 30-JAN-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 33.64 | 0.00 | 01-JAN-00:10 | 12868.74 | 11-JUL-05:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 33.64 | 0.00 | 01-JAN-00:10 | 12868.74 | 11-JUL-05:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 96.74 | 0.00 | 01-JAN-00:40 | 20778.27 | 07-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 45.66 | 0.00 | 01-JAN-00:40 | 18825.77 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 45.66 | 0.00 | 01-JAN-00:40 | 18825.77 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 51.08 | 0.00 | 01-JAN-00:20 | 20778.27 | 07-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 51.08 | 0.00 | 01-JAN-00:20 | 20778.27 | 07-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 149.81 | 0.00 | 01-JAN-00:40 | 31304.14 | 10-AUG-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 58.38 | 0.00 | 01-JAN-00:40 | 28393.36 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 58.38 | 0.00 | 01-JAN-00:40 | 28393.36 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 91.43 | 0.00 | 01-JAN-00:20 | 31304.14 | 10-AUG-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 91.43 | 0.00 | 01-JAN-00:20 | 31304.14 | 10-AUG-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 80.92 | 0.00 | 01-JAN-00:40 | 18144.02 | 30-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 38.24 | 0.00 | 01-JAN-00:40 | 18144.02 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 38.24 | 0.00 | 01-JAN-00:40 | 18144.02 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 42.67 | 0.00 | 01-JAN-00:20 | 17601.19 | 06-JUL-17:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 42.67 | 0.00 | 01-JAN-00:20 | 17601.19 | 06-JUL-17:40 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 80.92 | 0.00 | 01-JAN-00:10 | 13634.58 | 24-JUL-05:30 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 7.28 | 0.00 | 01-JAN-00:10 | 5442.18 | 02-JAN-10:40 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 7.28 | 0.00 | 01-JAN-00:10 | 5442.18 | 02-JAN-10:40 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 73.64 | 0.00 | 01-JAN-00:10 | 13634.58 | 24-JUL-05:30 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 73.64 | 0.00 | 01-JAN-00:10 | 13634.58 | 24-JUL-05:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 599.11 | 0.00 | 01-JAN-00:40 | 198033.77 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 244.39 | 0.00 | 01-JAN-00:40 | 198033.77 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 244.39 | 0.00 | 01-JAN-00:40 | 198033.77 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 354.72 | 0.00 | 01-JAN-00:10 | 76092.06 | 24-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 354.72 | 0.00 | 01-JAN-00:10 | 76092.06 | 24-JUL-15:30 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 153.54 | 0.00 | 01-JAN-00:40 | 35377.15 | 27-FEB-05:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 120.13 | 0.00 | 01-JAN-00:40 | 35377.15 | 27-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 120.13 | 0.00 | 01-JAN-00:40 | 35377.15 | 27-FEB-05:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 33.41 | 0.00 | 01-JAN-00:10 | 16008.89 | 21-JUL-14:40 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 33.41 | 0.00 | 01-JAN-00:10 | 16008.89 | 21-JUL-14:40 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 132.82 | 3.22 | 15-JAN-05:50 | 9002.37 | 20-APR-19:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.05 | 0.00 | 02-JAN-07:10 | 418.09 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.05 | 0.00 | 02-JAN-07:10 | 418.09 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 132.78 | 0.00 | 01-JAN-00:10 | 9002.37 | 20-APR-19:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 132.78 | 0.00 | 01-JAN-00:10 | 9002.37 | 20-APR-19:00 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1090.62 | 11.99 | 19-JAN-07:40 | 85675.08 | 20-APR-19:00 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 7.39 | 0.00 | 02-JAN-07:20 | 5929.80 | 31-JAN-01:50 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 7.39 | 0.00 | 02-JAN-07:20 | 5929.80 | 31-JAN-01:50 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1083.23 | 0.00 | 01-JAN-00:10 | 85675.08 | 20-APR-19:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1083.23 | 0.00 | 01-JAN-00:10 | 85675.08 | 20-APR-19:00 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 95.71 | 0.15 | 26-SEP-07:40 | 8555.74 | 20-APR-19:00 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 1.25 | 0.00 | 02-JAN-07:20 | 621.63 | 11-JAN-24:00 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 1.25 | 0.00 | 02-JAN-07:20 | 621.63 | 11-JAN-24:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 94.47 | 0.00 | 01-JAN-00:10 | 8555.74 | 20-APR-19:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 94.47 | 0.00 | 01-JAN-00:10 | 8555.74 | 20-APR-19:00 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7171.67 | 82706.95 | 02-JAN-05:00 | 371218.76 | 11-AUG-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7171.67 | 82706.95 | 02-JAN-05:00 | 371218.76 | 11-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7171.67 | 82706.95 | 02-JAN-05:00 | 371218.76 | 11-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 4112.07 | 0.00 | 01-JAN-00:40 | 2168869.74 | 27-FEB-07:10 |
PlantLoopHeatingDemand:Plant | 548.24 | 0.00 | 01-JAN-00:10 | 62900.66 | 02-JAN-12:10 |
WaterSystems:PlantLoopHeatingDemand | 548.24 | 0.00 | 01-JAN-00:10 | 62900.66 | 02-JAN-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 548.24 | 0.00 | 01-JAN-00:10 | 62900.66 | 02-JAN-12:10 |
EnergyTransfer:HVAC | 11045.14 | 2616.42 | 02-JAN-05:20 | 2154375.77 | 27-FEB-07:10 |
HeatingCoils:EnergyTransfer | 3563.83 | 0.00 | 01-JAN-00:40 | 2147902.86 | 27-FEB-07:10 |
PlantLoopHeatingDemand:HVAC | 3563.83 | 0.00 | 01-JAN-00:40 | 2147902.86 | 27-FEB-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 3563.83 | 0.00 | 01-JAN-00:40 | 2147902.86 | 27-FEB-07:10 |
CoolingCoils:EnergyTransfer | 3800.09 | 1714.59 | 12-JAN-08:10 | 1947261.08 | 11-AUG-15:40 |
HeatRecoveryForHeating:EnergyTransfer | 3679.46 | 0.00 | 01-JAN-00:10 | 899880.87 | 25-JAN-21:10 |
HeatRecoveryForCooling:EnergyTransfer | 1.75 | 0.00 | 01-JAN-00:10 | 132667.65 | 29-JUL-16:00 |
EnergyTransfer:Plant | 9633.70 | 0.00 | 01-JAN-00:40 | 5162714.70 | 11-AUG-15:20 |
LoopToLoop:EnergyTransfer | 1781.25 | 0.00 | 01-JAN-00:10 | 1652209.92 | 11-AUG-15:20 |
WaterSystems:EnergyTransfer | 548.24 | 0.00 | 01-JAN-00:10 | 62900.66 | 02-JAN-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 548.24 | 0.00 | 01-JAN-00:10 | 62900.66 | 02-JAN-12:10 |
Boilers:EnergyTransfer | 3545.27 | 0.00 | 01-JAN-00:40 | 2114473.96 | 27-FEB-07:30 |
Chillers:EnergyTransfer | 1780.37 | 0.00 | 01-JAN-00:10 | 1633071.21 | 11-AUG-15:20 |
HeatRejection:EnergyTransfer | 1978.57 | 0.00 | 01-JAN-00:10 | 1833722.50 | 11-AUG-15:20 |
General:HeatRejection:EnergyTransfer | 1978.57 | 0.00 | 01-JAN-00:10 | 1833722.50 | 11-AUG-15:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -233.408 | 0.000 | 0.000 | 68.532 | 216.171 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -475.692 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -748.226 | 0.000 | 0.000 | 83.646 | 194.137 | 289.614 | 0.000 | 0.000 | 0.000 | 180.829 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
CORE_MID | 0.000 | 0.000 | 31.467 | -4016.196 | 0.000 | 0.000 | 873.206 | 1941.366 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1725.971 |
CORE_TOP | 0.000 | 0.000 | 48.472 | -307.687 | 0.000 | 0.000 | 91.293 | 194.137 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -315.827 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 5.572 | -76.535 | 0.000 | 0.000 | 11.280 | 16.178 | 36.365 | 28.117 | 0.000 | 0.001 | 87.293 | 0.000 | -104.901 | 0.000 | -3.372 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 5.237 | -80.233 | 0.000 | 0.000 | 7.270 | 10.255 | 23.435 | 66.459 | 0.000 | 0.001 | 35.643 | 0.000 | -65.845 | 0.000 | -2.222 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 8.865 | -130.222 | 0.000 | 0.000 | 11.241 | 15.521 | 36.366 | 131.384 | 0.000 | 0.001 | 23.395 | 0.000 | -93.224 | 0.000 | -3.327 | 0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.728 | -89.625 | 0.000 | 0.000 | 7.219 | 10.207 | 23.435 | 45.703 | 0.000 | 0.001 | 75.234 | 0.000 | -70.586 | 0.000 | -2.316 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 375.264 | -385.144 | 0.000 | 0.000 | 116.264 | 161.429 | 363.654 | 294.358 | 0.000 | 0.038 | 122.738 | 0.000 | -975.963 | 0.000 | -72.637 | -0.007 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 240.139 | -562.513 | 0.000 | 0.000 | 54.752 | 102.364 | 234.352 | 670.301 | 0.000 | 0.027 | 0.019 | 0.000 | -621.299 | 0.000 | -48.926 | -69.198 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 280.205 | -1022.522 | 0.000 | 0.000 | 114.565 | 155.171 | 363.660 | 1318.263 | 0.000 | 0.036 | 0.050 | 0.000 | -899.297 | 0.000 | -75.307 | -234.774 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 190.836 | -470.905 | 0.000 | 0.000 | 75.355 | 101.923 | 234.351 | 466.386 | 0.000 | 0.022 | 99.771 | 0.000 | -647.712 | 0.000 | -50.026 | -0.013 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 74.477 | -33.643 | 0.000 | 0.000 | 11.775 | 16.142 | 36.365 | 29.974 | 0.000 | 0.004 | 0.001 | 0.000 | -94.094 | 0.000 | -8.686 | -32.315 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 45.663 | -51.079 | 0.000 | 0.000 | 7.498 | 10.235 | 23.435 | 67.414 | 0.000 | 0.003 | 0.001 | 0.000 | -60.113 | 0.000 | -5.877 | -37.180 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 58.385 | -91.426 | 0.000 | 0.000 | 11.596 | 15.516 | 36.366 | 132.541 | 0.000 | 0.004 | 0.001 | 0.000 | -86.716 | 0.000 | -9.020 | -67.246 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 38.243 | -42.672 | 0.000 | 0.000 | 7.613 | 10.191 | 23.435 | 46.893 | 0.000 | 0.002 | 0.001 | 0.000 | -62.751 | 0.000 | -6.017 | -14.937 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.049 | -132.775 | 0.000 | 0.000 | 0.950 | 5.155 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -27.260 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 7.388 | -1083.233 | 0.000 | 0.000 | 9.566 | 51.551 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -524.077 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 1.247 | -94.466 | 0.000 | 0.000 | 0.965 | 5.155 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -66.781 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7171.668 | 0.000 | 0.000 | 20.566 | 62.653 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -406.408 |
GROUNDFLOOR_PLENUM | 7.279 | -73.641 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.002 | 73.426 | 0.000 | 0.000 | 0.000 | -7.066 | -0.001 |
MIDFLOOR_PLENUM | 244.395 | -354.714 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.040 | 230.373 | 0.000 | 0.000 | 0.000 | -120.094 | -0.002 |
TOPFLOOR_PLENUM | 120.130 | -33.409 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.003 | 0.000 | 0.000 | 0.000 | 0.000 | -13.068 | -73.656 |
Total Facility | 371.804 | -461.764 | 1412.236 | -16824.179 | 0.000 | 0.000 | 1585.153 | 3295.457 | 14676.396 | 3297.792 | 0.000 | 0.186 | 928.775 | 0.000 | -3782.500 | 0.000 | -427.961 | -4071.347 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 13-OCT-07:11 | 0.00 | 0.00 | 0.00 | -139310.77 | 0.00 | 0.00 | 5253.56 | 19402.09 | 13457.54 | 0.00 | 0.00 | 0.00 | 101197.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 18-SEP-04:02 | 0.00 | 0.00 | 0.00 | -100714.07 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 94239.06 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 05-JUL-04:12 | 0.00 | 0.00 | 0.00 | -882703.58 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 817953.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 03-AUG-04:12 | 0.00 | 0.00 | 0.00 | -80567.81 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 74092.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 23-JUL-13:22 | 0.00 | 0.00 | 0.00 | -19330.62 | 0.00 | 0.00 | 41.08 | 57.83 | 720.18 | 4424.02 | 0.00 | 0.00 | 14099.94 | 0.00 | -0.00 | 0.00 | -12.44 | 0.00 |
PERIMETER_BOT_ZN_2 | 21-MAY-08:21 | 0.00 | 0.00 | 0.00 | -32463.32 | 0.00 | 0.00 | 13.86 | 37.27 | 464.11 | 26249.52 | 0.00 | 0.00 | 5870.43 | 0.00 | -0.00 | 0.00 | -171.88 | 0.00 |
PERIMETER_BOT_ZN_1 | 23-JUL-13:22 | 0.00 | 0.00 | 0.00 | -48178.41 | 0.00 | 0.00 | 21.96 | 57.83 | 720.19 | 34523.91 | 0.00 | 0.00 | 12881.49 | 0.00 | -0.00 | 0.00 | -26.97 | 0.00 |
PERIMETER_BOT_ZN_4 | 28-MAY-17:51 | 0.00 | 0.00 | 0.00 | -34612.18 | 0.00 | 0.00 | 0.00 | 37.27 | 360.35 | 20938.36 | 0.00 | 0.00 | 13347.44 | 0.00 | -0.00 | 0.00 | -71.23 | 0.00 |
PERIMETER_MID_ZN_3 | 09-JUN-04:23 | 0.00 | 0.00 | 0.00 | -167025.76 | 0.00 | 0.00 | 0.00 | 674.71 | 7455.61 | 151924.95 | 0.00 | 0.00 | 10062.04 | 0.00 | -0.00 | 0.00 | -3091.54 | 0.00 |
PERIMETER_MID_ZN_2 | 14-MAY-09:31 | 0.00 | 0.00 | 0.00 | -344088.68 | 0.00 | 0.00 | 143.15 | 372.66 | 4641.14 | 220672.12 | 0.00 | 0.00 | 120815.21 | 0.00 | -0.00 | 0.00 | -2555.59 | 0.00 |
PERIMETER_MID_ZN_1 | 23-JUL-13:31 | 0.00 | 0.00 | 0.00 | -525400.58 | 0.00 | 0.00 | 206.50 | 578.28 | 7201.95 | 339226.99 | 0.00 | 0.00 | 179092.19 | 0.00 | -0.00 | 0.00 | -905.33 | 0.00 |
PERIMETER_MID_ZN_4 | 28-MAY-17:51 | 0.00 | 0.00 | 0.00 | -327553.82 | 0.00 | 0.00 | 0.00 | 372.66 | 3603.49 | 208775.16 | 0.00 | 0.00 | 116491.62 | 0.00 | -0.00 | 0.00 | -1689.11 | 0.00 |
PERIMETER_TOP_ZN_3 | 07-JUL-04:13 | 0.00 | 0.00 | 0.00 | -17371.49 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 16008.72 | 0.00 | 0.00 | 798.30 | 0.00 | -0.00 | 0.00 | -248.57 | 0.00 |
PERIMETER_TOP_ZN_2 | 14-MAY-09:21 | 0.00 | 0.00 | 0.00 | -33733.35 | 0.00 | 0.00 | 15.54 | 37.27 | 464.11 | 23584.87 | 0.00 | 0.00 | 9963.91 | 0.00 | -0.00 | 0.00 | -332.35 | 0.00 |
PERIMETER_TOP_ZN_1 | 27-AUG-13:41 | 0.00 | 0.00 | 0.00 | -53079.80 | 0.00 | 0.00 | 23.52 | 57.83 | 720.19 | 31875.98 | 0.00 | 0.00 | 20658.47 | 0.00 | -0.00 | 0.00 | -256.20 | 0.00 |
PERIMETER_TOP_ZN_4 | 14-MAY-18:41 | 0.00 | 0.00 | 0.00 | -33140.61 | 0.00 | 0.00 | 0.00 | 37.27 | 360.35 | 18547.94 | 0.00 | 0.00 | 14657.59 | 0.00 | -0.00 | 0.00 | -462.54 | 0.00 |
DATACENTER_BOT_ZN_6 | 20-APR-19:00 | 0.00 | 0.00 | 0.00 | -9001.81 | 0.00 | 0.00 | 10.62 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 1046.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 20-APR-19:00 | 0.00 | 0.00 | 0.00 | -85669.72 | 0.00 | 0.00 | 106.16 | 1500.36 | 77944.22 | 0.00 | 0.00 | 0.00 | 6118.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 20-APR-19:00 | 0.00 | 0.00 | 0.00 | -8555.20 | 0.00 | 0.00 | 10.62 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 600.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 11-AUG-16:00 | 0.00 | 0.00 | 0.00 | -371219.38 | 0.00 | 0.00 | 2183.10 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -16066.79 |
GROUNDFLOOR_PLENUM | 24-JUL-05:15 | 0.00 | -15676.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15714.82 | 0.00 | -0.00 | 0.00 | -38.45 | 0.00 |
MIDFLOOR_PLENUM | 31-MAR-04:01 | 0.00 | -140911.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156219.11 | 0.00 | -0.00 | 0.00 | -15307.20 | 0.00 |
TOPFLOOR_PLENUM | 21-JUL-14:40 | 0.00 | -16010.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.77 | 15999.06 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-JUL-04:12 | 0.00 | 99038.92 | 0.00 | -1946246.14 | 0.00 | 0.00 | 0.00 | 10917.52 | 469008.02 | 285716.36 | 0.00 | 0.00 | 1117471.70 | 0.00 | -15636.20 | 0.00 | -20270.17 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 11-FEB-07:30 | 0.00 | 0.00 | 545.29 | 0.00 | 0.00 | 0.00 | 1018.06 | 2155.87 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -17176.76 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-04:01 | 0.00 | 0.00 | 547417.11 | 0.00 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -612166.94 |
CORE_TOP | 30-JAN-04:11 | 0.00 | 0.00 | 81600.02 | 0.00 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -88075.01 |
PERIMETER_BOT_ZN_3 | 02-JAN-04:01 | 0.00 | 0.00 | 14212.85 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5468.31 | 0.00 | -231.75 | -9325.83 |
PERIMETER_BOT_ZN_2 | 02-JAN-04:01 | 0.00 | 0.00 | 15940.75 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3595.23 | 0.00 | -153.76 | -12715.70 |
PERIMETER_BOT_ZN_1 | 30-JAN-04:01 | 0.00 | 0.00 | 26297.06 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6891.92 | 0.00 | -478.70 | -19739.48 |
PERIMETER_BOT_ZN_4 | 13-JAN-05:01 | 0.00 | 0.00 | 13043.54 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5567.16 | 0.00 | 0.00 | -8000.33 |
PERIMETER_MID_ZN_3 | 01-JAN-22:42 | 0.00 | 0.00 | 152037.32 | 0.00 | 0.00 | 0.00 | 0.00 | 674.71 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -49341.06 | 0.00 | -6785.46 | -102177.22 |
PERIMETER_MID_ZN_2 | 29-JAN-02:12 | 0.00 | 0.00 | 213105.91 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 3603.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -47919.04 | 0.00 | -14143.53 | -155081.67 |
PERIMETER_MID_ZN_1 | 02-JAN-04:01 | 0.00 | 0.00 | 317535.51 | 0.00 | 0.00 | 0.00 | 0.00 | 674.72 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -48262.22 | 0.00 | -5102.58 | -272301.16 |
PERIMETER_MID_ZN_4 | 30-JAN-04:11 | 0.00 | 0.00 | 207016.44 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -45805.25 | 0.00 | -7358.00 | -159092.65 |
PERIMETER_TOP_ZN_3 | 28-JAN-23:32 | 0.00 | 0.00 | 16764.41 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 559.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6917.66 | 0.00 | -3945.27 | -6528.12 |
PERIMETER_TOP_ZN_2 | 28-JAN-23:32 | 0.00 | 0.00 | 25074.18 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 360.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4607.44 | 0.00 | -2694.73 | -18175.84 |
PERIMETER_TOP_ZN_1 | 29-JAN-08:52 | 0.00 | 0.00 | 38650.74 | 0.00 | 0.00 | 0.00 | 91.58 | 121.54 | 720.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6585.34 | 0.00 | -1575.73 | -31422.99 |
PERIMETER_TOP_ZN_4 | 29-JAN-08:52 | 0.00 | 0.00 | 25507.92 | 0.00 | 0.00 | 0.00 | 58.98 | 78.32 | 464.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4406.99 | 0.00 | -1052.67 | -20649.66 |
DATACENTER_BOT_ZN_6 | 29-JAN-08:06 | 0.00 | 0.00 | 485.64 | 0.00 | 0.00 | 0.00 | 5.29 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2464.54 |
DATACENTER_MID_ZN_6 | 12-JAN-22:13 | 0.00 | 0.00 | 5984.12 | 0.00 | 0.00 | 0.00 | 54.89 | 500.10 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -26025.18 |
DATACENTER_TOP_ZN_6 | 11-JAN-24:00 | 0.00 | 0.00 | 621.64 | 0.00 | 0.00 | 0.00 | 6.36 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2601.61 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 09-APR-15:12 | 14028.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -71.13 | -13957.84 |
MIDFLOOR_PLENUM | 02-JAN-06:13 | 237568.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -881.54 | -236687.13 |
TOPFLOOR_PLENUM | 27-FEB-05:12 | 40131.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -40131.52 |
Total Facility | 02-JAN-04:01 | -67535.03 | 98567.42 | 1679157.24 | -98567.42 | 0.00 | 0.00 | 0.00 | 10313.53 | 232425.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -196758.95 | 0.00 | -28836.48 | -1628765.53 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 12.6893 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.3388 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 124.6301 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 96.3318 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 12.5305 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.4259 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.7162 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.7162 | 0.2100 | 1.0000 | Not calculated | 1.2002 | 0.2100 | ||
AIRLOOP DATACENTER BASEMENT | 25.0222 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 25.0222 | 0.0135 | 1.0000 | Not calculated | 0.3384 | 0.0135 | ||
AIRLOOP DATACENTER BOT | 0.5246 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5246 | 0.0298 | 1.0000 | Not calculated | 0.0156 | 0.0298 | ||
AIRLOOP DATACENTER MID | 5.0643 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.0643 | 0.0309 | 1.0000 | Not calculated | 0.1563 | 0.0309 | ||
AIRLOOP DATACENTER TOP | 0.5107 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5107 | 0.0306 | 1.0000 | Not calculated | 0.0156 | 0.0306 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 6.3447 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.3340 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 62.3150 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 33.2812 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 6.2652 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.4017 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 0.0000 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 0.0000 | 1.0000 | 1.0000 | Not calculated | 1.2002 | |||
AIRLOOP DATACENTER BASEMENT | 25.0222 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 25.0222 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0135 | ||
AIRLOOP DATACENTER BOT | 0.5246 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5246 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0298 | ||
AIRLOOP DATACENTER MID | 5.0643 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.0643 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0309 | ||
AIRLOOP DATACENTER TOP | 0.5107 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5107 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0306 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 5.7162 | 5.7162 | 0.0000 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.0404 | 6.0404 | 1.9692 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 57.0257 | 57.0257 | 19.3317 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.6018 | 5.6018 | 1.9718 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0619 | 1.0619 | 0.2474 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5193 | 1.5193 | 0.3039 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3107 | 2.3107 | 0.4621 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7570 | 1.7570 | 0.3514 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.9668 | 9.9668 | 2.4219 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 16.3465 | 16.3465 | 3.2693 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 24.6576 | 24.6576 | 4.9315 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 16.6334 | 16.6334 | 3.3267 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0510 | 1.0510 | 0.2543 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6301 | 1.6301 | 0.3260 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5377 | 2.5377 | 0.5075 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7099 | 1.7099 | 0.3420 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5246 | 0.5246 | 0.5246 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.0643 | 5.0643 | 5.0643 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5107 | 0.5107 | 0.5107 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 25.0222 | 25.0222 | 25.0222 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 12.6893 | 10.3388 | 12.6893 | 3.3340 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 124.6301 | 96.3318 | 124.6301 | 33.2812 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 12.5305 | 10.4259 | 12.5305 | 3.4017 | 0.0000 | 1.0000 |
CAV_BAS | 5.7162 | 5.7162 | 5.7162 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 25.0222 | 25.0222 | 25.0222 | 25.0222 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5246 | 0.5246 | 0.5246 | 0.5246 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.0643 | 5.0643 | 5.0643 | 5.0643 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5107 | 0.5107 | 0.5107 | 0.5107 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 0.0000 | 0.0000 | 0.0000 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0202 | 3.0202 | 1.9692 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 28.5128 | 28.5128 | 19.3317 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8009 | 2.8009 | 1.9718 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5310 | 0.5310 | 0.2474 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7597 | 0.7597 | 0.3039 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1554 | 1.1554 | 0.4621 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8785 | 0.8785 | 0.3514 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.9834 | 4.9834 | 2.4219 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.1733 | 8.1733 | 3.2693 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.3288 | 12.3288 | 4.9315 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.3167 | 8.3167 | 3.3267 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5255 | 0.5255 | 0.2543 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8151 | 0.8151 | 0.3260 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2688 | 1.2688 | 0.5075 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8550 | 0.8550 | 0.3420 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5246 | 0.5246 | 0.5246 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.0643 | 5.0643 | 5.0643 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5107 | 0.5107 | 0.5107 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 25.0222 | 25.0222 | 25.0222 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 6.3447 | 3.3340 | 3.3340 | 3.3340 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 62.3150 | 33.2812 | 33.2812 | 33.2812 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 6.2652 | 3.4017 | 3.4017 | 3.4017 | 0.0000 | 1.0000 |
CAV_BAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 25.0222 | 25.0222 | 25.0222 | 25.0222 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5246 | 0.5246 | 0.5246 | 0.5246 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.0643 | 5.0643 | 5.0643 | 5.0643 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5107 | 0.5107 | 0.5107 | 0.5107 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 229.83 |
Number of hours cooling loads not met | 3244.33 |
Number of hours not met | 3384.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 4593.99 | 2541901.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 772.41 | 342267.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3295.46 | 325713.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 385.22 | 40855.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 55.05 | 3454.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 2505.76 | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2543.56 | 291366.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 231.74 | 42500.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 204.77 | 81077.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 2094.67 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 52.57 | 6524.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 553.36 | 63524.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 27376.80 |
Natural Gas | 0.00 | 4593.99 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 31970.79 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 71.14 |
Space Heating | 0.00 |
Space Cooling | 16.68 |
Fans (All) | 54.91 |
Service Water Heating | 11.95 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 591.03 |
Subtotal | 591.03 |
Natural Gas [MJ/m2] | |
Space Heating | 99.18 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 99.18 |
Subtotal | 99.18 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 10.31 |
Space Heating | 14.37 |
Space Cooling | 2.42 |
Fans (All) | 7.96 |
Service Water Heating | 1.73 |
Receptacle Equipment | 45.91 |
Miscellaneous | 17.31 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 4349.83 | 107.00 | 32.67 | 4269.83 | 0.67 |
CORE_BOTTOM | 8680.83 | 79.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8735.00 | 25.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8734.17 | 25.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8728.50 | 31.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8672.83 | 87.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8758.33 | 1.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8740.67 | 19.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8729.83 | 30.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8728.00 | 32.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8741.83 | 18.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8735.83 | 24.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8733.33 | 26.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8378.00 | 382.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8757.17 | 2.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8758.17 | 1.83 | 0.00 | 0.00 | 0.00 |
Min | 4349.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 382.00 | 32.67 | 4269.83 | 0.67 |
Average | 8533.99 | 38.91 | 1.42 | 185.64 | 0.03 |
Sum | 196281.83 | 895.00 | 32.67 | 4269.83 | 0.67 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 179706.83 | 7107.33 | 786.83 | 180920.33 | 94.67 |
CORE_BOTTOM | 330731.00 | 82.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 99326.33 | 4068.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 330813.00 | 7107.33 | 786.83 | 180920.33 | 94.67 |
Average | 71941.01 | 489.48 | 34.21 | 7866.10 | 4.12 |
Sum | 1654643.17 | 11258.00 | 786.83 | 180920.33 | 94.67 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 4347.17 | 110.83 | 31.17 | 3119.50 | 1151.33 |
CORE_BOTTOM | 8658.17 | 101.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8717.67 | 42.33 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8741.17 | 18.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8688.67 | 71.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8725.50 | 34.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8728.33 | 31.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8676.33 | 83.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8756.50 | 3.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8744.00 | 16.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8742.50 | 17.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8725.17 | 34.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8742.17 | 17.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8746.00 | 14.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8737.33 | 22.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8478.83 | 281.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8695.83 | 64.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8753.33 | 6.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8757.00 | 3.00 | 0.00 | 0.00 | 0.00 |
Min | 4347.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 281.17 | 31.17 | 3119.50 | 1151.33 |
Average | 8530.45 | 42.51 | 1.36 | 135.63 | 50.06 |
Sum | 196200.33 | 977.67 | 31.17 | 3119.50 | 1151.33 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 179973.33 | 7006.50 | 573.83 | 83105.83 | 97956.50 |
CORE_BOTTOM | 330649.00 | 164.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330765.00 | 48.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330792.00 | 21.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 100533.83 | 2861.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 330792.00 | 7006.50 | 573.83 | 83105.83 | 97956.50 |
Average | 71998.53 | 439.16 | 24.95 | 3613.30 | 4258.98 |
Sum | 1655966.17 | 10100.67 | 573.83 | 83105.83 | 97956.50 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -17.62 |
February | -15.41 |
March | -10.29 |
April | 0.726 |
May | 10.596 |
June | 15.955 |
July | 16.857 |
August | 14.239 |
September | 6.723 |
October | -3.07 |
November | -17.64 |
December | -19.26 |
Annual Sum or Average | -1.44 |
Minimum of Months | -19.26 |
Maximum of Months | 16.857 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.292468E+11 | 102109.34 | 19-JAN-08:12 | -5.0 | -5.5 | 0.569418E+10 | 8383.28 | 19-JAN-08:20 | -5.0 | -5.5 |
February | 0.310367E+11 | 115281.62 | 07-FEB-17:01 | -3.0 | -4.2 | 0.523283E+10 | 9552.77 | 07-FEB-14:00 | -3.0 | -4.2 |
March | 0.442479E+11 | 118622.47 | 23-MAR-19:01 | -2.8 | -4.7 | 0.625982E+10 | 10122.47 | 23-MAR-13:00 | -2.8 | -4.7 |
April | 0.209139E+11 | 121727.18 | 15-APR-06:11 | -4.1 | -6.0 | 0.736552E+10 | 12928.72 | 28-APR-13:00 | 11.70 | 4.88 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 6.70 | 2.18 | 0.979402E+10 | 12950.23 | 12-MAY-13:00 | 20.60 | 9.86 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 | 8.14 | 0.996188E+10 | 13133.58 | 16-JUN-13:00 | 19.40 | 10.50 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 14.88 | 13.77 | 0.941868E+10 | 13405.77 | 14-JUL-13:00 | 21.10 | 14.79 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 16.35 | 11.83 | 0.107314E+11 | 13601.82 | 11-AUG-13:00 | 23.90 | 13.74 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 8.08 | 5.90 | 0.921030E+10 | 13396.48 | 01-SEP-13:00 | 15.00 | 10.77 |
October | 0.299456E+11 | 139476.55 | 13-OCT-07:11 | -9.4 | -9.9 | 0.732543E+10 | 13018.06 | 06-OCT-13:00 | -9.4 | -9.9 |
November | 0.405669E+11 | 107321.45 | 13-NOV-07:11 | -17.0 | -17.4 | 0.564689E+10 | 7709.01 | 16-NOV-10:30 | -18.0 | -18.3 |
December | 0.374581E+11 | 112105.93 | 26-DEC-07:11 | -11.3 | -11.7 | 0.551448E+10 | 7792.00 | 07-DEC-14:30 | -11.3 | -11.7 |
Annual Sum or Average | 0.233416E+12 | 0.921554E+11 | ||||||||
Minimum of Months | 0.00 | 0.00 | -17.0 | -17.4 | 0.523283E+10 | 7709.01 | -18.0 | -18.3 | ||
Maximum of Months | 0.442479E+11 | 139476.55 | 16.35 | 13.77 | 0.107314E+11 | 13601.82 | 23.90 | 14.79 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.284320E+11 | 29446.77 | 25-JAN-14:10 | -18.9 | -19.2 | 0.491350E+10 | 6734.76 | 10-JAN-14:20 | -18.9 | -19.2 |
February | 0.306019E+11 | 83603.40 | 10-FEB-06:01 | -9.5 | -10.1 | 0.454971E+10 | 6734.87 | 09-FEB-10:09 | -9.5 | -10.1 |
March | 0.448474E+11 | 88914.45 | 20-MAR-04:01 | -4.5 | -5.7 | 0.548234E+10 | 6774.51 | 30-MAR-13:00 | -10.0 | -12.1 |
April | 0.671519E+11 | 98251.32 | 20-APR-04:02 | 1.52 | -0.6 | 0.488664E+10 | 6789.13 | 03-APR-13:39 | 1.52 | -0.6 |
May | 0.845671E+11 | 99309.00 | 26-MAY-04:12 | 4.07 | 0.68 | 0.530016E+10 | 6756.96 | 15-MAY-13:50 | 4.07 | 0.68 |
June | 0.925676E+11 | 97606.00 | 24-JUN-04:13 | 12.40 | 11.57 | 0.528806E+10 | 6792.32 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.965812E+11 | 97456.76 | 20-JUL-04:13 | 12.40 | 11.35 | 0.491778E+10 | 6787.07 | 19-JUL-13:00 | 12.40 | 11.35 |
August | 0.104410E+12 | 97835.63 | 15-AUG-04:12 | 10.60 | 9.62 | 0.551558E+10 | 6867.75 | 24-AUG-13:30 | 22.50 | 14.98 |
September | 0.761596E+11 | 100717.08 | 18-SEP-04:02 | 1.70 | 1.02 | 0.489449E+10 | 6737.07 | 01-SEP-09:50 | 1.70 | 1.02 |
October | 0.546621E+11 | 99310.57 | 07-OCT-04:12 | 4.03 | 2.43 | 0.507423E+10 | 6754.65 | 17-OCT-13:00 | -1.7 | -2.5 |
November | 0.342453E+11 | 84009.09 | 03-NOV-05:02 | -16.4 | -16.8 | 0.498878E+10 | 6734.75 | 29-NOV-14:00 | -25.6 | -25.8 |
December | 0.339987E+11 | 69218.26 | 21-DEC-06:01 | -13.9 | -14.2 | 0.485076E+10 | 6734.76 | 29-DEC-10:09 | -11.6 | -12.1 |
Annual Sum or Average | 0.748225E+12 | 0.606620E+11 | ||||||||
Minimum of Months | 0.284320E+11 | 29446.77 | -18.9 | -19.2 | 0.454971E+10 | 6734.75 | -25.6 | -25.8 | ||
Maximum of Months | 0.104410E+12 | 100717.08 | 12.40 | 11.57 | 0.551558E+10 | 6867.75 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.207938E+11 | 18268.58 | 27-JAN-17:00 | -12.2 | -12.5 | 0.416062E+10 | 6325.68 | 26-JAN-14:00 | -12.2 | -12.5 |
February | 0.221453E+11 | 22199.44 | 16-FEB-17:00 | -5.6 | -7.7 | 0.400198E+10 | 6734.68 | 17-FEB-14:20 | -13.0 | -14.1 |
March | 0.285964E+11 | 48824.79 | 23-MAR-05:02 | -2.8 | -4.2 | 0.516554E+10 | 6734.74 | 31-MAR-09:30 | -17.0 | -18.1 |
April | 0.342449E+11 | 80636.80 | 21-APR-05:02 | -2.0 | -3.0 | 0.478744E+10 | 6742.28 | 12-APR-09:50 | -2.0 | -3.0 |
May | 0.457127E+11 | 80912.69 | 19-MAY-04:12 | 4.07 | 1.56 | 0.526791E+10 | 6734.74 | 19-MAY-13:00 | 13.30 | 8.13 |
June | 0.492528E+11 | 82646.14 | 24-JUN-04:12 | 12.40 | 11.57 | 0.526391E+10 | 6734.77 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.477749E+11 | 88282.06 | 05-JUL-04:12 | 8.30 | 7.90 | 0.489062E+10 | 6735.72 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.479022E+11 | 84138.74 | 14-AUG-04:12 | 11.50 | 10.36 | 0.548940E+10 | 6734.73 | 18-AUG-13:09 | 13.62 | 12.18 |
September | 0.349096E+11 | 81411.55 | 05-SEP-05:02 | 5.00 | 4.09 | 0.483604E+10 | 6774.46 | 22-SEP-09:09 | 2.88 | 1.48 |
October | 0.270758E+11 | 74188.96 | 06-OCT-05:02 | 6.60 | 2.71 | 0.480933E+10 | 6734.74 | 13-OCT-09:30 | -7.8 | -8.6 |
November | 0.219675E+11 | 18953.12 | 03-NOV-16:00 | -11.1 | -11.5 | 0.429074E+10 | 6491.72 | 03-NOV-13:00 | -11.1 | -11.5 |
December | 0.212442E+11 | 17741.91 | 22-DEC-17:00 | -21.7 | -22.0 | 0.402430E+10 | 6177.14 | 22-DEC-14:00 | -21.7 | -22.0 |
Annual Sum or Average | 0.401620E+12 | 0.569878E+11 | ||||||||
Minimum of Months | 0.207938E+11 | 17741.91 | -21.7 | -22.0 | 0.400198E+10 | 6177.14 | -21.7 | -22.0 | ||
Maximum of Months | 0.492528E+11 | 88282.06 | 12.40 | 11.57 | 0.548940E+10 | 6774.46 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.926797E+10 | 15455.78 | 20-JAN-17:00 | -11.1 | -11.2 | 0.375934E+10 | 5504.83 | 20-JAN-14:00 | -11.1 | -11.2 |
February | 0.118155E+11 | 17873.13 | 09-FEB-17:00 | -2.2 | -2.6 | 0.353127E+10 | 6147.58 | 09-FEB-14:00 | -2.2 | -2.6 |
March | 0.193148E+11 | 20654.67 | 22-MAR-16:00 | 5.60 | 2.61 | 0.446623E+10 | 6511.25 | 22-MAR-13:00 | 5.60 | 2.61 |
April | 0.260446E+11 | 38424.17 | 21-APR-16:00 | 14.40 | 5.45 | 0.442400E+10 | 6734.72 | 28-APR-09:20 | 6.70 | 3.17 |
May | 0.401087E+11 | 72305.48 | 11-MAY-05:03 | 4.68 | 1.21 | 0.520869E+10 | 6734.73 | 19-MAY-13:00 | 13.30 | 8.13 |
June | 0.481784E+11 | 79681.44 | 24-JUN-04:12 | 12.40 | 11.57 | 0.525031E+10 | 6734.74 | 30-JUN-09:09 | 17.57 | 14.96 |
July | 0.463678E+11 | 80339.80 | 05-JUL-05:02 | 8.30 | 7.78 | 0.488016E+10 | 6735.58 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.432204E+11 | 80564.09 | 03-AUG-04:12 | 15.00 | 13.08 | 0.545054E+10 | 6734.68 | 18-AUG-13:09 | 13.62 | 12.18 |
September | 0.259521E+11 | 35761.21 | 01-SEP-16:00 | 15.60 | 10.82 | 0.453783E+10 | 6734.72 | 08-SEP-13:09 | 11.28 | 7.64 |
October | 0.177704E+11 | 23205.82 | 04-OCT-16:00 | 10.00 | 4.57 | 0.414837E+10 | 6734.02 | 04-OCT-13:00 | 10.00 | 4.57 |
November | 0.105173E+11 | 15732.38 | 02-NOV-16:00 | -8.9 | -9.4 | 0.375387E+10 | 5546.28 | 02-NOV-13:00 | -8.9 | -9.4 |
December | 0.913002E+10 | 14516.15 | 21-DEC-17:00 | -16.7 | -17.3 | 0.360478E+10 | 5281.99 | 21-DEC-14:00 | -16.7 | -17.3 |
Annual Sum or Average | 0.307688E+12 | 0.530154E+11 | ||||||||
Minimum of Months | 0.913002E+10 | 14516.15 | -16.7 | -17.3 | 0.353127E+10 | 5281.99 | -16.7 | -17.3 | ||
Maximum of Months | 0.481784E+11 | 80564.09 | 15.60 | 13.08 | 0.545054E+10 | 6735.58 | 17.57 | 14.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.424336E+09 | 1786.21 | 19-JAN-16:10 | -5.3 | -6.1 | 0.468751E+09 | 662.78 | 20-JAN-14:20 | -9.6 | -9.9 |
February | 0.113986E+10 | 2552.17 | 09-FEB-06:03 | 0.00 | -0.5 | 0.443333E+09 | 755.21 | 09-FEB-14:00 | 0.00 | -1.0 |
March | 0.255551E+10 | 4002.80 | 22-MAR-13:50 | 5.40 | 1.85 | 0.585124E+09 | 845.61 | 21-MAR-13:20 | 5.40 | 1.85 |
April | 0.613491E+10 | 8650.11 | 26-APR-15:30 | 11.15 | 4.21 | 0.593280E+09 | 848.15 | 28-APR-13:00 | 11.70 | 4.88 |
May | 0.110668E+11 | 17546.11 | 21-MAY-05:42 | 5.22 | 2.61 | 0.664932E+09 | 848.92 | 31-MAY-13:09 | 19.50 | 10.32 |
June | 0.151412E+11 | 18210.38 | 07-JUN-03:32 | 5.97 | 4.64 | 0.664337E+09 | 854.48 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.150366E+11 | 19332.14 | 23-JUL-13:22 | 25.00 | 15.26 | 0.618168E+09 | 853.47 | 10-JUL-13:09 | 25.00 | 15.26 |
August | 0.133189E+11 | 16745.26 | 06-AUG-14:02 | 16.78 | 13.08 | 0.691900E+09 | 851.89 | 01-AUG-13:39 | 16.78 | 13.08 |
September | 0.664339E+10 | 8669.48 | 01-SEP-13:30 | 14.45 | 10.52 | 0.609578E+09 | 845.65 | 08-SEP-13:09 | 11.28 | 7.64 |
October | 0.348812E+10 | 5952.18 | 04-OCT-14:30 | 11.10 | 4.80 | 0.571670E+09 | 845.62 | 03-OCT-09:09 | 11.10 | 4.80 |
November | 0.102174E+10 | 2562.72 | 03-NOV-05:02 | -16.4 | -16.8 | 0.473023E+09 | 704.68 | 02-NOV-13:00 | -16.4 | -16.8 |
December | 0.563094E+09 | 1897.49 | 23-DEC-06:03 | -3.8 | -5.0 | 0.455222E+09 | 690.22 | 26-DEC-10:00 | -10.0 | -10.8 |
Annual Sum or Average | 0.765345E+11 | 0.683932E+10 | ||||||||
Minimum of Months | 0.424336E+09 | 1786.21 | -16.4 | -16.8 | 0.443333E+09 | 662.78 | -16.4 | -16.8 | ||
Maximum of Months | 0.151412E+11 | 19332.14 | 25.00 | 15.26 | 0.691900E+09 | 854.48 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.272753E+09 | 2078.68 | 23-JAN-06:03 | -11.2 | -11.4 | 0.300749E+09 | 403.38 | 11-JAN-14:39 | -11.2 | -11.4 |
February | 0.120358E+10 | 3070.56 | 15-FEB-10:45 | -16.0 | -16.2 | 0.284881E+09 | 544.94 | 15-FEB-10:00 | -15.6 | -15.8 |
March | 0.381136E+10 | 12479.95 | 27-MAR-10:15 | -9.0 | -11.2 | 0.396953E+09 | 553.32 | 27-MAR-09:00 | -9.0 | -11.2 |
April | 0.754231E+10 | 25765.57 | 23-APR-09:22 | 8.85 | 3.02 | 0.382324E+09 | 546.85 | 28-APR-13:00 | 11.70 | 4.88 |
May | 0.135883E+11 | 32461.28 | 21-MAY-08:21 | 10.80 | 5.33 | 0.428914E+09 | 548.79 | 15-MAY-09:00 | 10.80 | 5.33 |
June | 0.144253E+11 | 27485.01 | 18-JUN-09:11 | 13.67 | 10.90 | 0.428099E+09 | 551.83 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.147131E+11 | 31031.06 | 23-JUL-09:22 | 19.70 | 14.45 | 0.398245E+09 | 550.71 | 10-JUL-13:09 | 19.70 | 14.45 |
August | 0.129829E+11 | 22722.48 | 27-AUG-10:32 | 13.17 | 10.82 | 0.445505E+09 | 549.40 | 01-AUG-13:39 | 13.17 | 10.82 |
September | 0.725162E+10 | 26815.70 | 10-SEP-08:52 | 11.10 | 6.28 | 0.391408E+09 | 544.98 | 08-SEP-13:09 | 11.10 | 6.28 |
October | 0.372678E+10 | 11312.12 | 03-OCT-09:35 | 2.97 | 2.01 | 0.359882E+09 | 544.95 | 17-OCT-09:09 | -3.3 | -3.5 |
November | 0.557189E+09 | 2680.29 | 04-NOV-05:02 | -7.9 | -9.6 | 0.298958E+09 | 445.48 | 08-NOV-10:00 | -17.8 | -18.2 |
December | 0.157232E+09 | 2318.31 | 23-DEC-06:03 | -3.8 | -5.0 | 0.290719E+09 | 403.39 | 12-DEC-14:20 | -3.8 | -5.0 |
Annual Sum or Average | 0.802325E+11 | 0.440664E+10 | ||||||||
Minimum of Months | 0.157232E+09 | 2078.68 | -16.0 | -16.2 | 0.284881E+09 | 403.38 | -17.8 | -18.2 | ||
Maximum of Months | 0.147131E+11 | 32461.28 | 19.70 | 14.45 | 0.445505E+09 | 553.32 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.707334E+09 | 4669.38 | 25-JAN-13:30 | -19.8 | -20.0 | 0.473721E+09 | 825.10 | 25-JAN-14:09 | -18.9 | -19.2 |
February | 0.305491E+10 | 15740.18 | 15-FEB-13:30 | -8.9 | -9.7 | 0.472163E+09 | 845.64 | 17-FEB-14:20 | -13.0 | -14.1 |
March | 0.885773E+10 | 31087.26 | 12-MAR-13:22 | -7.8 | -9.3 | 0.620629E+09 | 867.96 | 28-MAR-13:09 | -6.7 | -9.7 |
April | 0.158534E+11 | 44122.64 | 23-APR-12:01 | 10.00 | 3.76 | 0.588179E+09 | 851.53 | 26-APR-13:00 | 10.60 | 4.23 |
May | 0.182019E+11 | 46700.19 | 21-MAY-13:01 | 14.60 | 6.77 | 0.661755E+09 | 853.52 | 31-MAY-13:09 | 19.50 | 10.32 |
June | 0.200171E+11 | 42313.16 | 18-JUN-11:51 | 16.10 | 12.32 | 0.664189E+09 | 863.05 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.208282E+11 | 48180.04 | 23-JUL-13:22 | 25.00 | 15.26 | 0.617742E+09 | 861.02 | 10-JUL-13:09 | 25.00 | 15.26 |
August | 0.212635E+11 | 43178.92 | 27-AUG-13:11 | 18.33 | 13.81 | 0.691086E+09 | 881.67 | 24-AUG-13:30 | 18.33 | 13.81 |
September | 0.127065E+11 | 40452.84 | 10-SEP-11:32 | 15.20 | 8.17 | 0.595928E+09 | 847.27 | 08-SEP-13:20 | 15.20 | 8.17 |
October | 0.678449E+10 | 25621.52 | 03-OCT-13:20 | 10.57 | 6.12 | 0.561678E+09 | 847.09 | 03-OCT-13:00 | 11.70 | 6.58 |
November | 0.162543E+10 | 12164.03 | 08-NOV-13:30 | -13.6 | -14.4 | 0.481532E+09 | 845.64 | 08-NOV-14:39 | -13.7 | -14.4 |
December | 0.322417E+09 | 3429.50 | 27-DEC-12:50 | -22.9 | -23.1 | 0.450607E+09 | 646.59 | 27-DEC-13:20 | -23.5 | -23.7 |
Annual Sum or Average | 0.130223E+12 | 0.687921E+10 | ||||||||
Minimum of Months | 0.322417E+09 | 3429.50 | -22.9 | -23.1 | 0.450607E+09 | 646.59 | -23.5 | -23.7 | ||
Maximum of Months | 0.212635E+11 | 48180.04 | 25.00 | 15.26 | 0.691086E+09 | 881.67 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.943468E+09 | 2453.72 | 23-JAN-14:40 | -10.0 | -10.5 | 0.302278E+09 | 421.87 | 23-JAN-14:50 | -10.3 | -10.7 |
February | 0.240034E+10 | 4079.86 | 09-FEB-06:03 | 0.00 | -0.5 | 0.294201E+09 | 531.30 | 09-FEB-14:00 | 0.00 | -1.0 |
March | 0.508391E+10 | 11809.72 | 26-MAR-16:53 | -7.2 | -9.2 | 0.401435E+09 | 544.95 | 21-MAR-13:00 | -7.2 | -9.2 |
April | 0.108904E+11 | 31653.72 | 23-APR-15:21 | 8.60 | 2.78 | 0.391330E+09 | 547.37 | 28-APR-13:00 | 11.70 | 4.88 |
May | 0.105252E+11 | 34612.20 | 28-MAY-17:51 | 16.70 | 8.41 | 0.426057E+09 | 547.29 | 15-MAY-13:50 | 16.70 | 8.41 |
June | 0.139148E+11 | 31533.95 | 10-JUN-17:41 | 21.60 | 11.19 | 0.428120E+09 | 551.36 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.144429E+11 | 31378.88 | 23-JUL-15:22 | 25.60 | 15.14 | 0.398333E+09 | 551.01 | 20-JUL-13:00 | 25.60 | 15.14 |
August | 0.144563E+11 | 31902.97 | 27-AUG-17:11 | 20.93 | 12.63 | 0.446318E+09 | 550.33 | 01-AUG-13:50 | 20.93 | 12.63 |
September | 0.674877E+10 | 22363.27 | 02-SEP-17:05 | 16.70 | 10.21 | 0.379837E+09 | 544.97 | 08-SEP-13:09 | 11.28 | 7.64 |
October | 0.456886E+10 | 8183.39 | 03-OCT-14:50 | 12.62 | 6.87 | 0.364745E+09 | 544.94 | 04-OCT-13:09 | 11.60 | 5.09 |
November | 0.285538E+10 | 3976.17 | 03-NOV-05:02 | -16.4 | -16.8 | 0.319404E+09 | 523.74 | 08-NOV-14:00 | -13.9 | -14.6 |
December | 0.279495E+10 | 3304.04 | 26-DEC-05:03 | -12.2 | -12.5 | 0.305543E+09 | 472.29 | 26-DEC-10:00 | -10.0 | -10.8 |
Annual Sum or Average | 0.896253E+11 | 0.445760E+10 | ||||||||
Minimum of Months | 0.943468E+09 | 2453.72 | -16.4 | -16.8 | 0.294201E+09 | 421.87 | -13.9 | -14.6 | ||
Maximum of Months | 0.144563E+11 | 34612.20 | 25.60 | 15.14 | 0.446318E+09 | 551.36 | 25.60 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14619109.14 | 1483.37 | 07-JAN-17:02 | -9.0 | -9.0 | 0.463587E+09 | 626.00 | 30-JAN-10:39 | -25.2 | -25.6 |
February | 0.103677E+09 | 1589.77 | 09-FEB-16:10 | 0.13 | -0.8 | 0.421349E+09 | 625.95 | 24-FEB-10:00 | -24.4 | -24.9 |
March | 0.772344E+09 | 2210.43 | 22-MAR-15:00 | 5.60 | 2.22 | 0.517428E+09 | 777.36 | 22-MAR-13:00 | 5.60 | 2.22 |
April | 0.264001E+10 | 4819.06 | 28-APR-14:00 | 11.70 | 4.88 | 0.531302E+09 | 845.61 | 14-APR-13:00 | 11.70 | 4.88 |
May | 0.619036E+10 | 14642.72 | 31-MAY-04:52 | 11.70 | 7.43 | 0.657780E+09 | 845.63 | 19-MAY-13:39 | 11.70 | 7.43 |
June | 0.976352E+10 | 16702.10 | 09-JUN-04:23 | 10.00 | 7.05 | 0.661445E+09 | 845.65 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.882045E+10 | 16538.21 | 11-JUL-04:22 | 13.35 | 11.22 | 0.615105E+09 | 845.75 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.628999E+10 | 12924.28 | 01-AUG-05:03 | 10.00 | 9.66 | 0.682073E+09 | 845.62 | 18-AUG-13:09 | 13.62 | 12.18 |
September | 0.286789E+10 | 4732.11 | 01-SEP-13:40 | 14.63 | 10.60 | 0.549392E+09 | 845.63 | 08-SEP-13:09 | 11.28 | 7.64 |
October | 0.101807E+10 | 2309.83 | 06-OCT-05:02 | 6.60 | 2.71 | 0.486745E+09 | 786.22 | 04-OCT-13:00 | 6.60 | 2.71 |
November | 16603133.02 | 1482.23 | 04-NOV-16:02 | -9.6 | -11.3 | 0.459584E+09 | 626.00 | 27-NOV-10:00 | -27.2 | -27.4 |
December | 16981476.39 | 1479.05 | 23-DEC-17:02 | -2.6 | -3.4 | 0.447201E+09 | 625.98 | 05-DEC-14:00 | -2.6 | -3.4 |
Annual Sum or Average | 0.385145E+11 | 0.649299E+10 | ||||||||
Minimum of Months | 14619109.14 | 1479.05 | -9.6 | -11.3 | 0.421349E+09 | 625.95 | -27.2 | -27.4 | ||
Maximum of Months | 0.976352E+10 | 16702.10 | 14.63 | 11.22 | 0.682073E+09 | 845.75 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 28226615.72 | 2290.27 | 18-JAN-06:04 | -20.0 | -20.2 | 0.218886E+09 | 385.84 | 03-JAN-09:00 | -20.0 | -20.2 |
February | 0.322671E+09 | 2635.44 | 15-FEB-11:15 | -14.3 | -14.6 | 0.199729E+09 | 443.41 | 15-FEB-11:30 | -13.6 | -14.0 |
March | 0.246674E+10 | 8970.91 | 31-MAR-10:05 | -15.9 | -17.2 | 0.263960E+09 | 521.22 | 16-MAR-10:00 | -15.9 | -17.2 |
April | 0.524891E+10 | 18526.66 | 23-APR-10:12 | 9.60 | 3.55 | 0.266543E+09 | 522.26 | 26-APR-08:20 | 2.23 | -1.6 |
May | 0.108698E+11 | 34410.47 | 14-MAY-09:31 | 15.73 | 8.25 | 0.311793E+09 | 522.83 | 31-MAY-10:30 | 18.05 | 10.24 |
June | 0.113488E+11 | 31120.52 | 04-JUN-09:41 | 17.43 | 11.50 | 0.312179E+09 | 525.34 | 08-JUN-07:19 | 11.83 | 8.21 |
July | 0.111687E+11 | 34213.41 | 23-JUL-09:31 | 20.17 | 14.57 | 0.291148E+09 | 524.99 | 11-JUL-07:19 | 20.17 | 14.57 |
August | 0.887416E+10 | 25209.46 | 27-AUG-10:21 | 12.80 | 10.67 | 0.322448E+09 | 523.33 | 10-AUG-10:50 | 12.80 | 10.67 |
September | 0.432469E+10 | 25897.41 | 10-SEP-09:32 | 12.23 | 6.85 | 0.259448E+09 | 524.70 | 08-SEP-07:00 | 12.23 | 6.85 |
October | 0.154158E+10 | 7177.78 | 03-OCT-10:10 | 4.27 | 2.93 | 0.232396E+09 | 521.20 | 03-OCT-10:20 | 4.63 | 3.18 |
November | 28507146.27 | 2228.34 | 14-NOV-06:04 | -15.6 | -15.9 | 0.216924E+09 | 385.85 | 07-NOV-09:09 | -15.6 | -15.9 |
December | 28518756.66 | 2203.97 | 07-DEC-06:04 | -22.8 | -23.1 | 0.211043E+09 | 385.83 | 28-DEC-08:09 | -27.9 | -28.1 |
Annual Sum or Average | 0.562513E+11 | 0.310650E+10 | ||||||||
Minimum of Months | 28226615.72 | 2203.97 | -22.8 | -23.1 | 0.199729E+09 | 385.83 | -27.9 | -28.1 | ||
Maximum of Months | 0.113488E+11 | 34410.47 | 20.17 | 14.57 | 0.322448E+09 | 525.34 | 20.17 | 14.57 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.372014E+09 | 4536.30 | 25-JAN-13:40 | -19.5 | -19.7 | 0.467552E+09 | 777.87 | 25-JAN-14:09 | -18.9 | -19.2 |
February | 0.223122E+10 | 15019.87 | 15-FEB-13:40 | -8.7 | -9.6 | 0.454715E+09 | 845.64 | 17-FEB-14:20 | -13.0 | -14.1 |
March | 0.800531E+10 | 43564.53 | 26-MAR-14:02 | -9.7 | -11.1 | 0.593265E+09 | 854.00 | 27-MAR-13:20 | -5.7 | -8.8 |
April | 0.136467E+11 | 42993.15 | 23-APR-12:51 | 10.00 | 3.85 | 0.567636E+09 | 847.01 | 12-APR-09:50 | 10.00 | 3.85 |
May | 0.154147E+11 | 49558.48 | 14-MAY-12:11 | 18.17 | 9.44 | 0.645389E+09 | 848.05 | 12-MAY-13:00 | 18.17 | 9.44 |
June | 0.159257E+11 | 47139.51 | 18-JUN-12:41 | 16.60 | 11.66 | 0.654464E+09 | 846.61 | 29-JUN-13:39 | 25.20 | 16.06 |
July | 0.158223E+11 | 52536.99 | 23-JUL-13:31 | 25.00 | 15.26 | 0.608052E+09 | 847.40 | 20-JUL-13:50 | 25.00 | 15.26 |
August | 0.158314E+11 | 51800.91 | 27-AUG-13:41 | 19.13 | 14.11 | 0.674343E+09 | 846.35 | 09-AUG-13:39 | 19.13 | 14.11 |
September | 0.968521E+10 | 42582.86 | 10-SEP-11:32 | 15.20 | 8.17 | 0.558799E+09 | 845.70 | 08-SEP-13:09 | 15.20 | 8.17 |
October | 0.448096E+10 | 23958.42 | 03-OCT-13:30 | 10.85 | 6.24 | 0.522264E+09 | 845.63 | 04-OCT-13:39 | 11.30 | 4.92 |
November | 0.783925E+09 | 10337.03 | 08-NOV-13:30 | -13.6 | -14.4 | 0.469338E+09 | 845.64 | 08-NOV-14:39 | -13.7 | -14.4 |
December | 53479818.05 | 3341.12 | 09-DEC-06:04 | -23.2 | -23.5 | 0.447410E+09 | 626.07 | 22-DEC-10:50 | -24.1 | -24.4 |
Annual Sum or Average | 0.102253E+12 | 0.666323E+10 | ||||||||
Minimum of Months | 53479818.05 | 3341.12 | -23.2 | -23.5 | 0.447410E+09 | 626.07 | -24.1 | -24.4 | ||
Maximum of Months | 0.159257E+11 | 52536.99 | 25.00 | 15.26 | 0.674343E+09 | 854.00 | 25.20 | 16.06 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 30080063.20 | 2321.92 | 18-JAN-06:04 | -20.0 | -20.2 | 0.299176E+09 | 403.42 | 02-JAN-10:30 | -20.0 | -20.2 |
February | 0.283702E+09 | 2455.27 | 16-FEB-15:40 | -4.6 | -6.8 | 0.272548E+09 | 423.87 | 09-FEB-14:00 | -4.6 | -6.8 |
March | 0.166051E+10 | 6507.47 | 27-MAR-16:50 | -4.9 | -8.2 | 0.338290E+09 | 521.18 | 31-MAR-15:00 | -9.4 | -11.8 |
April | 0.573881E+10 | 28669.22 | 22-APR-17:41 | 13.07 | 5.65 | 0.342736E+09 | 544.94 | 26-APR-13:00 | 10.60 | 4.23 |
May | 0.771245E+10 | 32755.43 | 28-MAY-17:51 | 16.70 | 8.41 | 0.410568E+09 | 544.96 | 19-MAY-13:39 | 16.70 | 8.41 |
June | 0.981202E+10 | 30458.51 | 04-JUN-19:01 | 18.80 | 11.66 | 0.423260E+09 | 544.97 | 29-JUN-13:30 | 25.00 | 15.96 |
July | 0.880422E+10 | 29138.75 | 30-JUL-18:42 | 17.38 | 11.82 | 0.392671E+09 | 544.97 | 07-JUL-13:09 | 17.38 | 11.82 |
August | 0.760713E+10 | 30024.02 | 27-AUG-17:41 | 20.68 | 12.29 | 0.430111E+09 | 544.95 | 14-AUG-13:09 | 20.68 | 12.29 |
September | 0.395809E+10 | 18544.80 | 02-SEP-17:05 | 16.70 | 10.21 | 0.336461E+09 | 544.93 | 01-SEP-13:00 | 16.70 | 10.21 |
October | 0.135340E+10 | 3972.98 | 03-OCT-15:10 | 12.62 | 6.83 | 0.310151E+09 | 521.18 | 03-OCT-15:00 | 11.70 | 6.37 |
November | 88935965.65 | 2367.05 | 08-NOV-15:40 | -15.4 | -15.8 | 0.296733E+09 | 408.22 | 08-NOV-15:50 | -15.7 | -16.1 |
December | 41395595.13 | 2336.07 | 19-DEC-06:04 | -21.1 | -21.4 | 0.288601E+09 | 403.43 | 22-DEC-10:50 | -24.1 | -24.4 |
Annual Sum or Average | 0.470907E+11 | 0.414131E+10 | ||||||||
Minimum of Months | 30080063.20 | 2321.92 | -21.1 | -21.4 | 0.272548E+09 | 403.42 | -24.1 | -24.4 | ||
Maximum of Months | 0.981202E+10 | 32755.43 | 20.68 | 12.29 | 0.430111E+09 | 544.97 | 25.00 | 15.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10810158.00 | 1530.12 | 07-JAN-17:02 | -9.0 | -9.0 | 0.460515E+09 | 625.99 | 03-JAN-10:09 | -9.0 | -9.0 |
February | 18571664.76 | 1545.85 | 11-FEB-17:02 | -1.2 | -2.7 | 0.418691E+09 | 626.03 | 24-FEB-10:30 | -25.0 | -25.5 |
March | 0.243775E+09 | 2099.27 | 22-MAR-15:40 | 5.60 | 2.48 | 0.505731E+09 | 714.73 | 22-MAR-13:00 | 5.60 | 2.48 |
April | 0.191827E+10 | 4110.85 | 28-APR-15:20 | 12.20 | 4.90 | 0.496575E+09 | 845.60 | 27-APR-13:00 | 12.20 | 4.90 |
May | 0.536127E+10 | 14553.49 | 31-MAY-05:01 | 12.07 | 7.63 | 0.645187E+09 | 845.63 | 19-MAY-13:39 | 12.07 | 7.63 |
June | 0.943789E+10 | 17021.95 | 12-JUN-04:11 | 7.57 | 6.07 | 0.660339E+09 | 845.64 | 29-JUN-13:00 | 25.60 | 16.24 |
July | 0.850722E+10 | 17373.60 | 07-JUL-04:13 | 13.87 | 10.90 | 0.613921E+09 | 845.73 | 19-JUL-09:09 | 17.38 | 14.45 |
August | 0.573240E+10 | 12260.43 | 05-AUG-05:02 | 13.98 | 12.01 | 0.669762E+09 | 845.62 | 18-AUG-13:09 | 13.62 | 12.18 |
September | 0.201849E+10 | 3787.48 | 01-SEP-16:00 | 15.60 | 10.82 | 0.502957E+09 | 845.59 | 01-SEP-13:20 | 15.60 | 10.82 |
October | 0.370194E+09 | 2107.39 | 04-OCT-15:40 | 10.37 | 4.66 | 0.469585E+09 | 716.85 | 04-OCT-13:00 | 10.37 | 4.66 |
November | 10296837.14 | 1521.63 | 18-NOV-17:02 | -13.0 | -13.3 | 0.457118E+09 | 626.00 | 29-NOV-14:39 | -25.2 | -25.5 |
December | 13598670.84 | 1521.66 | 23-DEC-17:02 | -2.6 | -3.4 | 0.444356E+09 | 626.12 | 22-DEC-10:50 | -2.6 | -3.4 |
Annual Sum or Average | 0.336428E+11 | 0.634474E+10 | ||||||||
Minimum of Months | 10296837.14 | 1521.63 | -13.0 | -13.3 | 0.418691E+09 | 625.99 | -25.2 | -25.5 | ||
Maximum of Months | 0.943789E+10 | 17373.60 | 15.60 | 12.01 | 0.669762E+09 | 845.73 | 25.60 | 16.24 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 24357085.45 | 2283.46 | 21-JAN-06:04 | -10.8 | -10.9 | 0.298565E+09 | 403.46 | 12-JAN-14:39 | -10.8 | -10.9 |
February | 0.106285E+09 | 2301.38 | 04-FEB-06:04 | -18.9 | -19.1 | 0.271312E+09 | 416.67 | 15-FEB-10:00 | -15.6 | -15.8 |
March | 0.154894E+10 | 6166.76 | 31-MAR-10:15 | -15.7 | -17.0 | 0.347974E+09 | 544.95 | 31-MAR-09:00 | -15.7 | -17.0 |
April | 0.420208E+10 | 12770.97 | 22-APR-09:25 | 9.15 | 3.96 | 0.354398E+09 | 544.95 | 28-APR-09:20 | 6.70 | 3.17 |
May | 0.101617E+11 | 33734.80 | 14-MAY-09:21 | 15.55 | 8.14 | 0.422880E+09 | 546.05 | 15-MAY-09:50 | 12.70 | 5.47 |
June | 0.112595E+11 | 30704.70 | 04-JUN-09:51 | 17.80 | 11.67 | 0.424426E+09 | 546.16 | 08-JUN-09:39 | 16.33 | 10.32 |
July | 0.110788E+11 | 30438.68 | 09-JUL-08:21 | 16.95 | 12.65 | 0.394223E+09 | 546.63 | 07-JUL-09:50 | 16.95 | 12.65 |
August | 0.845112E+10 | 23144.70 | 27-AUG-10:21 | 12.80 | 10.67 | 0.437591E+09 | 545.93 | 11-AUG-09:30 | 12.80 | 10.67 |
September | 0.335627E+10 | 26540.90 | 10-SEP-09:21 | 11.95 | 6.71 | 0.335867E+09 | 544.97 | 08-SEP-13:09 | 11.95 | 6.71 |
October | 0.840038E+09 | 4938.10 | 03-OCT-10:00 | 3.90 | 2.68 | 0.308439E+09 | 544.95 | 03-OCT-09:00 | 3.90 | 2.68 |
November | 23064973.25 | 2302.88 | 03-NOV-05:04 | -16.4 | -16.8 | 0.295763E+09 | 403.44 | 30-NOV-10:30 | -28.6 | -28.8 |
December | 27043242.14 | 1919.90 | 30-DEC-17:02 | -10.0 | -10.4 | 0.287850E+09 | 403.50 | 22-DEC-10:00 | -10.0 | -10.4 |
Annual Sum or Average | 0.510792E+11 | 0.417929E+10 | ||||||||
Minimum of Months | 23064973.25 | 1919.90 | -18.9 | -19.1 | 0.271312E+09 | 403.44 | -28.6 | -28.8 | ||
Maximum of Months | 0.112595E+11 | 33734.80 | 17.80 | 12.65 | 0.437591E+09 | 546.63 | 16.95 | 12.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.203206E+09 | 3915.87 | 25-JAN-13:40 | -19.5 | -19.7 | 0.464200E+09 | 685.42 | 25-JAN-14:09 | -18.9 | -19.2 |
February | 0.140033E+10 | 11853.27 | 15-FEB-13:40 | -8.7 | -9.6 | 0.442345E+09 | 845.64 | 17-FEB-14:20 | -13.0 | -14.1 |
March | 0.593805E+10 | 22917.69 | 31-MAR-13:50 | -11.2 | -13.1 | 0.574626E+09 | 845.64 | 01-MAR-14:50 | -11.2 | -13.1 |
April | 0.115977E+11 | 38893.76 | 30-APR-13:31 | 8.70 | 4.53 | 0.552153E+09 | 846.12 | 27-APR-13:00 | 8.70 | 4.53 |
May | 0.144050E+11 | 51307.98 | 21-MAY-13:41 | 15.40 | 7.26 | 0.632887E+09 | 848.09 | 12-MAY-13:00 | 15.40 | 7.26 |
June | 0.157390E+11 | 48831.13 | 04-JUN-14:31 | 19.23 | 11.76 | 0.649029E+09 | 846.15 | 16-JUN-13:00 | 19.40 | 10.50 |
July | 0.156460E+11 | 47981.92 | 23-JUL-13:41 | 25.00 | 15.26 | 0.602463E+09 | 847.50 | 20-JUL-13:50 | 25.00 | 15.26 |
August | 0.151328E+11 | 53081.29 | 27-AUG-13:41 | 19.13 | 14.11 | 0.662784E+09 | 846.49 | 09-AUG-13:39 | 19.13 | 14.11 |
September | 0.789747E+10 | 43605.94 | 10-SEP-12:02 | 15.68 | 8.36 | 0.531606E+09 | 845.69 | 08-SEP-13:09 | 15.68 | 8.36 |
October | 0.299008E+10 | 21719.05 | 03-OCT-13:30 | 10.85 | 6.24 | 0.501105E+09 | 845.63 | 04-OCT-13:30 | 11.40 | 4.98 |
November | 0.434013E+09 | 7085.40 | 08-NOV-13:40 | -13.5 | -14.3 | 0.463444E+09 | 845.64 | 08-NOV-14:39 | -13.7 | -14.4 |
December | 43650852.16 | 2996.35 | 30-DEC-17:02 | -10.0 | -10.4 | 0.446748E+09 | 626.19 | 22-DEC-10:00 | -10.0 | -10.4 |
Annual Sum or Average | 0.914272E+11 | 0.652339E+10 | ||||||||
Minimum of Months | 43650852.16 | 2996.35 | -19.5 | -19.7 | 0.442345E+09 | 626.19 | -18.9 | -19.2 | ||
Maximum of Months | 0.157390E+11 | 53081.29 | 25.00 | 15.26 | 0.662784E+09 | 848.09 | 25.00 | 15.26 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 27770148.21 | 2378.24 | 27-JAN-06:04 | -13.8 | -14.1 | 0.298681E+09 | 403.45 | 03-JAN-14:00 | -13.8 | -14.1 |
February | 0.124458E+09 | 2434.65 | 16-FEB-06:04 | -19.6 | -19.9 | 0.271414E+09 | 404.95 | 09-FEB-14:00 | -19.6 | -19.9 |
March | 0.102001E+10 | 5231.97 | 27-MAR-17:00 | -5.0 | -8.2 | 0.332381E+09 | 521.14 | 31-MAR-15:00 | -9.4 | -11.8 |
April | 0.483635E+10 | 29144.02 | 22-APR-17:41 | 13.07 | 5.65 | 0.327927E+09 | 544.89 | 28-APR-13:00 | 11.70 | 4.88 |
May | 0.718808E+10 | 33138.76 | 14-MAY-18:41 | 16.70 | 9.10 | 0.398481E+09 | 544.96 | 19-MAY-13:39 | 13.87 | 8.18 |
June | 0.969741E+10 | 31952.16 | 11-JUN-18:31 | 18.30 | 10.93 | 0.420014E+09 | 544.97 | 29-JUN-13:00 | 25.60 | 16.24 |
July | 0.868876E+10 | 27203.24 | 08-JUL-19:02 | 19.90 | 15.26 | 0.388999E+09 | 544.97 | 07-JUL-13:09 | 19.90 | 15.26 |
August | 0.723506E+10 | 30872.81 | 27-AUG-17:41 | 20.68 | 12.29 | 0.419836E+09 | 544.95 | 25-AUG-13:00 | 20.68 | 12.29 |
September | 0.307969E+10 | 15589.87 | 02-SEP-17:05 | 16.70 | 10.21 | 0.318508E+09 | 539.95 | 01-SEP-13:00 | 16.70 | 10.21 |
October | 0.704934E+09 | 3331.91 | 03-OCT-15:20 | 12.43 | 6.74 | 0.303668E+09 | 506.58 | 03-OCT-15:30 | 12.25 | 6.65 |
November | 38082109.58 | 2385.19 | 15-NOV-06:04 | -17.6 | -17.8 | 0.295986E+09 | 403.44 | 28-NOV-14:00 | -25.6 | -25.8 |
December | 31824353.56 | 2373.79 | 09-DEC-06:04 | -23.2 | -23.5 | 0.288064E+09 | 403.48 | 27-DEC-14:09 | -23.9 | -24.1 |
Annual Sum or Average | 0.426724E+11 | 0.406396E+10 | ||||||||
Minimum of Months | 27770148.21 | 2373.79 | -23.2 | -23.5 | 0.271414E+09 | 403.44 | -25.6 | -25.8 | ||
Maximum of Months | 0.969741E+10 | 33138.76 | 20.68 | 15.26 | 0.420014E+09 | 544.97 | 25.60 | 16.24 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.182181E+09 | 10170.41 | 12-JAN-05:01 | -37.9 | -38.0 | 0.00 | 0.00 | 01-JAN-00:10 | -37.9 | -38.0 |
February | 0.591590E+09 | 9060.42 | 27-FEB-05:01 | -36.1 | -36.2 | 0.00 | 0.00 | 01-FEB-00:10 | -36.1 | -36.2 |
March | 0.172355E+10 | 7667.12 | 04-MAR-06:01 | -26.3 | -26.7 | 0.00 | 0.00 | 01-MAR-00:10 | -26.3 | -26.7 |
April | 0.627241E+10 | 10233.15 | 24-APR-05:10 | -3.4 | -6.0 | 0.00 | 0.00 | 01-APR-00:10 | -3.4 | -6.0 |
May | 0.112256E+11 | 13410.42 | 22-MAY-05:10 | 3.98 | 0.99 | 0.00 | 0.00 | 01-MAY-00:10 | 3.98 | 0.99 |
June | 0.135167E+11 | 14059.15 | 05-JUN-05:15 | 10.77 | 8.82 | 0.00 | 0.00 | 01-JUN-00:10 | 10.77 | 8.82 |
July | 0.138448E+11 | 15676.82 | 24-JUL-05:15 | 13.17 | 12.61 | 0.00 | 0.00 | 01-JUL-00:10 | 13.17 | 12.61 |
August | 0.136616E+11 | 13769.80 | 07-AUG-05:10 | 10.60 | 10.26 | 0.00 | 0.00 | 01-AUG-00:10 | 10.60 | 10.26 |
September | 0.806671E+10 | 10988.65 | 11-SEP-05:10 | 4.18 | 3.47 | 0.00 | 0.00 | 01-SEP-00:10 | 4.18 | 3.47 |
October | 0.392884E+10 | 8608.48 | 02-OCT-05:15 | 5.73 | 4.64 | 0.00 | 0.00 | 01-OCT-00:10 | 5.73 | 4.64 |
November | 0.444707E+09 | 7818.32 | 27-NOV-05:01 | -25.8 | -26.0 | 0.00 | 0.00 | 01-NOV-00:10 | -25.8 | -26.0 |
December | 0.182160E+09 | 7315.27 | 15-DEC-05:01 | -33.2 | -33.3 | 0.00 | 0.00 | 01-DEC-00:10 | -33.2 | -33.3 |
Annual Sum or Average | 0.736408E+11 | 0.00 | ||||||||
Minimum of Months | 0.182160E+09 | 7315.27 | -37.9 | -38.0 | 0.00 | 0.00 | -37.9 | -38.0 | ||
Maximum of Months | 0.138448E+11 | 15676.82 | 13.17 | 12.61 | 0.00 | 0.00 | 13.17 | 12.61 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.761701E+09 | 13963.94 | 29-JAN-02:12 | -26.0 | -26.5 | 0.00 | 0.00 | 01-JAN-00:10 | -26.0 | -26.5 |
February | 0.824736E+09 | 13969.86 | 25-FEB-04:11 | -25.2 | -25.6 | 0.00 | 0.00 | 01-FEB-00:10 | -25.2 | -25.6 |
March | 0.634806E+09 | 14091.35 | 31-MAR-04:01 | -24.5 | -25.0 | 0.00 | 0.00 | 01-MAR-00:10 | -24.5 | -25.0 |
April | 0.211141E+10 | 10202.25 | 03-APR-04:01 | -21.1 | -21.6 | 0.00 | 0.00 | 01-APR-00:10 | -21.1 | -21.6 |
May | 0.512271E+10 | 5549.10 | 12-MAY-14:00 | 20.60 | 9.86 | 0.00 | 0.00 | 01-MAY-00:10 | 20.60 | 9.86 |
June | 0.727485E+10 | 7174.43 | 30-JUN-12:10 | 25.78 | 18.15 | 0.00 | 0.00 | 01-JUN-00:10 | 25.78 | 18.15 |
July | 0.716215E+10 | 8435.75 | 05-JUL-05:13 | 8.30 | 7.82 | 0.00 | 0.00 | 01-JUL-00:10 | 8.30 | 7.82 |
August | 0.615850E+10 | 7783.96 | 02-AUG-05:13 | 11.10 | 10.22 | 0.00 | 0.00 | 01-AUG-00:10 | 11.10 | 10.22 |
September | 0.288926E+10 | 6056.00 | 05-SEP-05:10 | 5.00 | 4.09 | 0.00 | 0.00 | 01-SEP-00:10 | 5.00 | 4.09 |
October | 0.980837E+09 | 11923.54 | 30-OCT-03:01 | -13.5 | -14.2 | 0.00 | 0.00 | 01-OCT-00:10 | -13.5 | -14.2 |
November | 0.666158E+09 | 12388.39 | 30-NOV-04:01 | -28.2 | -28.4 | 0.00 | 0.00 | 01-NOV-00:10 | -28.2 | -28.4 |
December | 0.884418E+09 | 14070.82 | 15-DEC-04:01 | -32.4 | -32.5 | 0.00 | 0.00 | 01-DEC-00:10 | -32.4 | -32.5 |
Annual Sum or Average | 0.354715E+11 | 0.00 | ||||||||
Minimum of Months | 0.634806E+09 | 5549.10 | -32.4 | -32.5 | 0.00 | 0.00 | -32.4 | -32.5 | ||
Maximum of Months | 0.727485E+10 | 14091.35 | 25.78 | 18.15 | 0.00 | 0.00 | 25.78 | 18.15 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -14.9 | -15.4 | 0.00 | 0.00 | 01-JAN-00:10 | -14.9 | -15.4 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -20.2 | -20.7 | 0.00 | 0.00 | 01-FEB-00:10 | -20.2 | -20.7 |
March | 11814234.67 | 1301.35 | 22-MAR-16:30 | 5.60 | 2.18 | 0.00 | 0.00 | 01-MAR-00:10 | 5.60 | 2.18 |
April | 0.162119E+10 | 8567.75 | 21-APR-15:40 | 14.23 | 5.51 | 0.00 | 0.00 | 01-APR-00:10 | 14.23 | 5.51 |
May | 0.563878E+10 | 14150.11 | 31-MAY-14:30 | 20.55 | 10.45 | 0.00 | 0.00 | 01-MAY-00:10 | 20.55 | 10.45 |
June | 0.959788E+10 | 15409.98 | 29-JUN-14:40 | 25.93 | 16.13 | 0.00 | 0.00 | 01-JUN-00:10 | 25.93 | 16.13 |
July | 0.930248E+10 | 16008.89 | 21-JUL-14:40 | 27.23 | 14.65 | 0.00 | 0.00 | 01-JUL-00:10 | 27.23 | 14.65 |
August | 0.626097E+10 | 13402.09 | 11-AUG-15:30 | 25.00 | 14.43 | 0.00 | 0.00 | 01-AUG-00:10 | 25.00 | 14.43 |
September | 0.957321E+09 | 5809.07 | 07-SEP-15:20 | 16.47 | 8.91 | 0.00 | 0.00 | 01-SEP-00:10 | 16.47 | 8.91 |
October | 18887689.69 | 1196.33 | 03-OCT-16:20 | 11.50 | 5.96 | 0.00 | 0.00 | 01-OCT-00:10 | 11.50 | 5.96 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 | -10.9 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 | -26.0 |
Annual Sum or Average | 0.334093E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -25.8 | -26.0 | 0.00 | 0.00 | -25.8 | -26.0 | ||
Maximum of Months | 0.959788E+10 | 16008.89 | 27.23 | 16.13 | 0.00 | 0.00 | 27.23 | 16.13 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.135710E+10 | 1189.48 | 23-JAN-15:20 | -10.4 | -10.8 | 95146755.12 | 126.82 | 18-JAN-10:09 | -10.4 | -10.8 |
February | 0.657326E+10 | 3664.24 | 15-FEB-16:15 | -7.4 | -8.8 | 86396465.15 | 126.82 | 15-FEB-14:09 | -7.4 | -8.8 |
March | 0.134756E+11 | 6824.48 | 31-MAR-24:00 | -11.8 | -13.4 | 0.103236E+09 | 126.82 | 03-MAR-14:09 | -11.8 | -13.4 |
April | 0.190573E+11 | 9002.37 | 20-APR-19:00 | 11.10 | 4.63 | 91604972.15 | 126.82 | 07-APR-13:09 | 11.10 | 4.63 |
May | 0.484553E+10 | 3551.39 | 31-MAY-23:20 | 13.33 | 8.32 | 99233126.27 | 126.82 | 17-MAY-09:00 | 13.33 | 8.32 |
June | 0.973225E+10 | 5487.78 | 30-JUN-23:42 | 15.32 | 13.53 | 98962243.66 | 126.85 | 27-JUN-09:00 | 15.32 | 13.53 |
July | 0.151344E+11 | 7405.68 | 31-JUL-23:35 | 17.10 | 11.88 | 91886107.44 | 126.84 | 25-JUL-09:00 | 17.10 | 11.88 |
August | 0.200798E+11 | 8808.94 | 27-AUG-18:45 | 19.60 | 11.80 | 0.103239E+09 | 126.83 | 04-AUG-09:09 | 19.60 | 11.80 |
September | 0.427325E+10 | 3262.47 | 30-SEP-24:00 | 1.30 | -0.1 | 91606792.97 | 126.83 | 05-SEP-13:00 | 1.30 | -0.1 |
October | 0.857938E+10 | 4548.50 | 31-OCT-24:00 | -10.1 | -11.0 | 95230019.61 | 126.82 | 04-OCT-13:09 | -10.1 | -11.0 |
November | 0.121562E+11 | 5675.45 | 08-NOV-16:00 | -16.1 | -16.4 | 94300263.49 | 126.82 | 10-NOV-14:00 | -11.7 | -12.6 |
December | 0.175114E+11 | 7062.67 | 26-DEC-15:00 | -14.4 | -14.9 | 91880857.34 | 126.82 | 08-DEC-14:50 | -14.4 | -14.9 |
Annual Sum or Average | 0.132776E+12 | 0.114272E+10 | ||||||||
Minimum of Months | 0.135710E+10 | 1189.48 | -16.1 | -16.4 | 86396465.15 | 126.82 | -14.4 | -14.9 | ||
Maximum of Months | 0.200798E+11 | 9002.37 | 19.60 | 13.53 | 0.103239E+09 | 126.85 | 19.60 | 13.53 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.379135E+09 | 634.18 | 12-JAN-10:00 | -38.3 | -38.4 | 88771469.03 | 126.82 | 20-JAN-14:00 | -11.1 | -11.3 |
February | 0.389363E+10 | 3160.59 | 16-FEB-16:15 | -4.8 | -7.1 | 86396473.83 | 126.82 | 15-FEB-14:09 | -4.8 | -7.1 |
March | 0.107648E+11 | 5985.05 | 31-MAR-23:20 | -12.1 | -13.7 | 0.103236E+09 | 126.82 | 03-MAR-14:09 | -12.1 | -13.7 |
April | 0.170387E+11 | 8567.51 | 20-APR-19:00 | 11.10 | 4.63 | 91605006.03 | 126.82 | 07-APR-13:09 | 11.10 | 4.63 |
May | 0.386837E+10 | 3262.10 | 31-MAY-24:00 | 12.40 | 8.53 | 99233128.66 | 126.82 | 17-MAY-09:00 | 12.40 | 8.53 |
June | 0.888414E+10 | 5154.06 | 30-JUN-23:55 | 15.10 | 14.10 | 98962521.20 | 126.85 | 27-JUN-13:00 | 15.10 | 14.10 |
July | 0.140001E+11 | 7060.62 | 31-JUL-23:27 | 17.35 | 12.09 | 91887088.62 | 126.84 | 25-JUL-13:00 | 17.35 | 12.09 |
August | 0.186023E+11 | 7996.41 | 27-AUG-18:50 | 19.60 | 11.80 | 0.103240E+09 | 126.83 | 04-AUG-09:50 | 19.60 | 11.80 |
September | 0.275641E+10 | 2331.86 | 02-SEP-18:10 | 16.52 | 10.34 | 91606510.92 | 126.83 | 05-SEP-13:00 | 8.90 | 7.75 |
October | 0.595213E+10 | 3531.88 | 03-OCT-16:00 | 11.70 | 6.37 | 95230025.21 | 126.82 | 04-OCT-13:09 | 11.60 | 5.09 |
November | 0.873851E+10 | 4973.68 | 08-NOV-15:55 | -16.1 | -16.4 | 94300269.88 | 126.82 | 24-NOV-14:09 | -15.7 | -16.1 |
December | 0.134451E+11 | 6004.52 | 21-DEC-17:00 | -16.7 | -17.3 | 91880863.25 | 126.82 | 12-DEC-14:39 | -16.7 | -17.3 |
Annual Sum or Average | 0.108323E+12 | 0.113635E+10 | ||||||||
Minimum of Months | 0.379135E+09 | 634.18 | -38.3 | -38.4 | 86396473.83 | 126.82 | -16.7 | -17.3 | ||
Maximum of Months | 0.186023E+11 | 8567.51 | 19.60 | 14.10 | 0.103240E+09 | 126.85 | 19.60 | 14.10 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.309309E+09 | 617.03 | 12-JAN-08:15 | -38.1 | -38.2 | 80987309.24 | 125.84 | 19-JAN-14:00 | -6.1 | -6.7 |
February | 0.233849E+10 | 2725.99 | 15-FEB-16:10 | -7.3 | -8.7 | 86341649.00 | 126.82 | 15-FEB-14:09 | -7.3 | -8.7 |
March | 0.865678E+10 | 5532.04 | 31-MAR-17:40 | -9.4 | -11.7 | 0.103236E+09 | 126.82 | 03-MAR-14:09 | -9.4 | -11.7 |
April | 0.156415E+11 | 8555.74 | 20-APR-19:00 | 11.10 | 4.63 | 91605023.37 | 126.82 | 07-APR-13:09 | 11.10 | 4.63 |
May | 0.330618E+10 | 3202.26 | 31-MAY-23:33 | 12.87 | 8.44 | 99233128.79 | 126.82 | 17-MAY-09:00 | 12.87 | 8.44 |
June | 0.870712E+10 | 5112.39 | 30-JUN-23:32 | 15.53 | 12.93 | 98962536.92 | 126.85 | 28-JUN-13:00 | 15.53 | 12.93 |
July | 0.138456E+11 | 7024.99 | 31-JUL-23:17 | 17.60 | 12.30 | 91887058.12 | 126.84 | 25-JUL-13:00 | 17.60 | 12.30 |
August | 0.182474E+11 | 8024.71 | 27-AUG-18:50 | 19.60 | 11.80 | 0.103240E+09 | 126.83 | 04-AUG-09:30 | 19.60 | 11.80 |
September | 0.161166E+10 | 2179.02 | 02-SEP-18:10 | 16.52 | 10.34 | 91460618.60 | 126.83 | 05-SEP-13:00 | 8.90 | 7.75 |
October | 0.377920E+10 | 3385.08 | 03-OCT-16:00 | 11.70 | 6.37 | 95230028.95 | 126.82 | 04-OCT-13:09 | 11.60 | 5.09 |
November | 0.659607E+10 | 4532.22 | 08-NOV-15:50 | -15.7 | -16.1 | 94300272.76 | 126.82 | 27-NOV-14:50 | -23.9 | -24.2 |
December | 0.114267E+11 | 5532.36 | 21-DEC-17:00 | -16.7 | -17.3 | 91880865.22 | 126.82 | 22-DEC-14:30 | -23.4 | -23.6 |
Annual Sum or Average | 0.944660E+11 | 0.112836E+10 | ||||||||
Minimum of Months | 0.309309E+09 | 617.03 | -38.1 | -38.2 | 80987309.24 | 125.84 | -23.9 | -24.2 | ||
Maximum of Months | 0.182474E+11 | 8555.74 | 19.60 | 12.93 | 0.103240E+09 | 126.85 | 19.60 | 12.93 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.231860E+12 | 90055.14 | 20-JAN-17:00 | -11.1 | -11.2 | 0.206146E+10 | 2745.33 | 18-JAN-10:00 | -11.1 | -11.2 |
February | 0.430524E+12 | 182034.03 | 09-FEB-17:00 | -2.2 | -2.6 | 0.187028E+10 | 2745.39 | 14-FEB-14:09 | -0.9 | -2.8 |
March | 0.725906E+12 | 358047.68 | 31-MAR-24:00 | -11.8 | -13.4 | 0.223479E+10 | 2745.59 | 02-MAR-10:00 | -11.8 | -13.4 |
April | 0.944869E+12 | 369485.29 | 21-APR-16:00 | 14.40 | 5.45 | 0.198299E+10 | 2745.53 | 20-APR-09:39 | 14.40 | 5.45 |
May | 0.244819E+12 | 177543.12 | 31-MAY-24:00 | 12.40 | 8.53 | 0.214812E+10 | 2745.34 | 19-MAY-09:30 | 12.40 | 8.53 |
June | 0.474892E+12 | 269572.98 | 30-JUN-24:00 | 15.10 | 14.10 | 0.214225E+10 | 2747.99 | 29-JUN-13:50 | 15.10 | 14.10 |
July | 0.737554E+12 | 362266.29 | 31-JUL-23:55 | 16.60 | 11.46 | 0.199013E+10 | 2751.02 | 06-JUL-13:39 | 16.60 | 11.46 |
August | 0.983964E+12 | 371218.76 | 11-AUG-16:00 | 25.60 | 14.77 | 0.223641E+10 | 2754.33 | 04-AUG-13:00 | 25.60 | 14.77 |
September | 0.238525E+12 | 176704.48 | 30-SEP-24:00 | 1.30 | -0.1 | 0.198300E+10 | 2745.33 | 26-SEP-13:00 | 1.30 | -0.1 |
October | 0.486108E+12 | 266184.06 | 31-OCT-24:00 | -10.1 | -11.0 | 0.206150E+10 | 2745.39 | 30-OCT-13:00 | -10.1 | -11.0 |
November | 0.702462E+12 | 274539.90 | 08-NOV-17:00 | -18.3 | -18.6 | 0.204137E+10 | 2745.49 | 30-NOV-10:30 | -28.6 | -28.8 |
December | 0.970186E+12 | 366108.22 | 26-DEC-17:00 | -15.6 | -15.9 | 0.198897E+10 | 2745.50 | 15-DEC-10:00 | -15.6 | -15.9 |
Annual Sum or Average | 0.717167E+13 | 0.247413E+11 | ||||||||
Minimum of Months | 0.231860E+12 | 90055.14 | -18.3 | -18.6 | 0.187028E+10 | 2745.33 | -28.6 | -28.8 | ||
Maximum of Months | 0.983964E+12 | 371218.76 | 25.60 | 14.77 | 0.223641E+10 | 2754.33 | 25.60 | 14.77 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -14.9 |
February | 327192.91 | 545.32 | 11-FEB-07:30 | -6.4 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 |
Annual Sum or Average | 327192.91 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 327192.91 | 545.32 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -14.9 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -20.2 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.00 | 0.00 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.158895E+10 | 54741.76 | 02-JAN-04:01 | -15.1 |
February | 0.403184E+09 | 46270.03 | 27-FEB-05:01 | -36.1 |
March | 12845052.81 | 40062.85 | 06-MAR-06:01 | -21.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 8.08 |
October | 12621919.94 | 39946.36 | 30-OCT-05:03 | -14.5 |
November | 0.399152E+09 | 46316.52 | 27-NOV-05:01 | -25.8 |
December | 0.729907E+09 | 46587.16 | 04-DEC-05:01 | -19.9 |
Annual Sum or Average | 0.314666E+10 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.158895E+10 | 54741.76 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.123450E+11 | 81600.08 | 30-JAN-04:11 | -25.2 |
February | 0.752843E+10 | 81470.96 | 21-FEB-04:01 | -22.8 |
March | 0.395091E+10 | 79685.84 | 06-MAR-04:01 | -20.0 |
April | 0.821657E+09 | 75177.28 | 03-APR-03:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 16.35 |
September | 94970101.11 | 68084.91 | 25-SEP-04:01 | -1.1 |
October | 0.285685E+10 | 79724.66 | 30-OCT-03:01 | -13.5 |
November | 0.935698E+10 | 81520.33 | 27-NOV-04:11 | -25.9 |
December | 0.115171E+11 | 81374.39 | 04-DEC-04:01 | -20.0 |
Annual Sum or Average | 0.484719E+11 | |||
Minimum of Months | 0.00 | 0.00 | -25.9 | |
Maximum of Months | 0.123450E+11 | 81600.08 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.215595E+10 | 14213.07 | 02-JAN-04:01 | -15.1 |
February | 0.939238E+09 | 13813.02 | 27-FEB-05:01 | -36.1 |
March | 0.311302E+09 | 13329.67 | 01-MAR-05:01 | -28.3 |
April | 7081890.04 | 12165.96 | 03-APR-05:01 | -21.2 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 8.08 |
October | 63200252.13 | 12434.51 | 27-OCT-05:01 | -17.4 |
November | 0.781179E+09 | 13456.62 | 27-NOV-05:01 | -25.8 |
December | 0.131464E+10 | 13330.77 | 04-DEC-05:01 | -19.9 |
Annual Sum or Average | 0.557259E+10 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.215595E+10 | 14213.07 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.171206E+10 | 15941.21 | 02-JAN-04:01 | -15.1 |
February | 0.713676E+09 | 15052.19 | 27-FEB-05:01 | -36.1 |
March | 0.242194E+09 | 14547.75 | 01-MAR-05:01 | -28.3 |
April | 8430058.11 | 11382.16 | 03-APR-05:01 | -21.2 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 8.08 |
October | 73286023.38 | 12922.95 | 31-OCT-05:01 | -18.2 |
November | 0.890403E+09 | 14750.62 | 27-NOV-05:01 | -25.8 |
December | 0.159680E+10 | 14781.43 | 15-DEC-05:01 | -33.2 |
Annual Sum or Average | 0.523684E+10 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.171206E+10 | 15941.21 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.304378E+10 | 26296.59 | 30-JAN-04:01 | -25.1 |
February | 0.111362E+10 | 24808.78 | 27-FEB-04:01 | -34.7 |
March | 0.359466E+09 | 23007.37 | 01-MAR-05:01 | -28.3 |
April | 12742389.21 | 18024.82 | 03-APR-05:01 | -21.2 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 8.08 |
October | 0.156746E+09 | 22860.93 | 30-OCT-04:01 | -14.4 |
November | 0.145007E+10 | 23581.36 | 13-NOV-05:01 | -20.2 |
December | 0.272894E+10 | 24793.59 | 04-DEC-04:01 | -20.0 |
Annual Sum or Average | 0.886536E+10 | |||
Minimum of Months | 0.00 | 0.00 | -34.7 | |
Maximum of Months | 0.304378E+10 | 26296.59 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.568585E+09 | 13043.49 | 13-JAN-05:01 | -32.9 |
February | 0.101414E+09 | 12602.78 | 27-FEB-05:01 | -36.1 |
March | 12860998.64 | 10900.35 | 01-MAR-06:01 | -28.4 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 8.08 |
October | 2476578.48 | 10629.91 | 31-OCT-05:01 | -18.2 |
November | 24608419.91 | 10870.34 | 29-NOV-06:01 | -28.9 |
December | 18058280.91 | 10889.95 | 06-DEC-06:01 | -28.7 |
Annual Sum or Average | 0.728003E+09 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.568585E+09 | 13043.49 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.961608E+10 | 15203.86 | 01-JAN-22:42 | -15.0 |
February | 0.595441E+10 | 15128.51 | 27-FEB-03:02 | -34.9 |
March | 0.316350E+10 | 14524.35 | 06-MAR-04:01 | -20.0 |
April | 0.466982E+09 | 14250.04 | 03-APR-03:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 16.35 |
September | 51028054.99 | 11757.33 | 30-SEP-05:02 | -4.5 |
October | 0.182498E+10 | 14496.88 | 23-OCT-03:01 | -11.6 |
November | 0.701309E+10 | 14782.71 | 27-NOV-04:11 | -25.9 |
December | 0.943645E+10 | 14761.78 | 04-DEC-04:11 | -20.0 |
Annual Sum or Average | 0.375265E+11 | |||
Minimum of Months | 0.00 | 0.00 | -34.9 | |
Maximum of Months | 0.961608E+10 | 15203.86 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.659301E+10 | 21310.73 | 29-JAN-02:12 | -26.0 |
February | 0.340274E+10 | 21141.62 | 27-FEB-03:02 | -34.9 |
March | 0.134859E+10 | 20448.21 | 01-MAR-04:01 | -27.9 |
April | 0.196450E+09 | 19044.31 | 03-APR-03:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 16.35 |
September | 31940766.49 | 14553.91 | 30-SEP-05:02 | -4.5 |
October | 0.101254E+10 | 19850.03 | 23-OCT-03:01 | -11.6 |
November | 0.478174E+10 | 20910.44 | 27-NOV-04:11 | -25.9 |
December | 0.664709E+10 | 20822.26 | 04-DEC-04:11 | -20.0 |
Annual Sum or Average | 0.240141E+11 | |||
Minimum of Months | 0.00 | 0.00 | -34.9 | |
Maximum of Months | 0.664709E+10 | 21310.73 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.815677E+10 | 31753.47 | 02-JAN-04:01 | -15.1 |
February | 0.338244E+10 | 30701.67 | 26-FEB-09:02 | -26.8 |
March | 0.136562E+10 | 30240.52 | 01-MAR-04:01 | -27.9 |
April | 0.150333E+09 | 26914.31 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 16.35 |
September | 23965944.81 | 14390.99 | 30-SEP-05:02 | -4.5 |
October | 0.984571E+09 | 29757.64 | 30-OCT-03:01 | -13.5 |
November | 0.507879E+10 | 31254.77 | 27-NOV-04:11 | -25.9 |
December | 0.887827E+10 | 31206.89 | 04-DEC-04:11 | -20.0 |
Annual Sum or Average | 0.280208E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.9 | |
Maximum of Months | 0.887827E+10 | 31753.47 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.550813E+10 | 20701.64 | 30-JAN-04:11 | -25.2 |
February | 0.282381E+10 | 20082.01 | 21-FEB-04:01 | -22.8 |
March | 0.125980E+10 | 19783.15 | 01-MAR-04:01 | -27.9 |
April | 96430565.40 | 17447.54 | 03-APR-04:01 | -21.1 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 16.35 |
September | 18522359.37 | 12452.06 | 30-SEP-05:02 | -4.5 |
October | 0.832325E+09 | 19424.16 | 30-OCT-03:01 | -13.5 |
November | 0.349614E+10 | 20270.46 | 27-NOV-04:11 | -25.9 |
December | 0.504855E+10 | 20148.41 | 04-DEC-04:11 | -20.0 |
Annual Sum or Average | 0.190837E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.9 | |
Maximum of Months | 0.550813E+10 | 20701.64 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.159151E+11 | 16764.91 | 28-JAN-23:32 | -24.8 |
February | 0.118126E+11 | 16759.14 | 27-FEB-03:02 | -34.9 |
March | 0.799881E+10 | 15974.05 | 13-MAR-01:03 | -21.0 |
April | 0.208408E+10 | 15958.86 | 03-APR-02:42 | -20.7 |
May | 5714747.92 | 12129.57 | 27-MAY-05:03 | 0.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 14.88 |
August | 22671980.40 | 12293.10 | 30-AUG-05:02 | 0.00 |
September | 0.670291E+09 | 13844.76 | 30-SEP-04:01 | -4.0 |
October | 0.575099E+10 | 16028.18 | 23-OCT-00:23 | -13.9 |
November | 0.137859E+11 | 16417.63 | 26-NOV-18:52 | -24.4 |
December | 0.164309E+11 | 16656.94 | 04-DEC-00:02 | -22.1 |
Annual Sum or Average | 0.744771E+11 | |||
Minimum of Months | 0.00 | 0.00 | -34.9 | |
Maximum of Months | 0.164309E+11 | 16764.91 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106629E+11 | 25074.48 | 28-JAN-23:32 | -24.8 |
February | 0.686837E+10 | 24957.42 | 27-FEB-03:02 | -34.9 |
March | 0.345160E+10 | 24007.20 | 06-MAR-04:01 | -20.0 |
April | 0.875669E+09 | 22706.69 | 04-APR-03:01 | -10.5 |
May | 1866017.21 | 8475.25 | 27-MAY-05:03 | 0.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 14.88 |
August | 10900439.89 | 14021.50 | 30-AUG-05:02 | 0.00 |
September | 0.309971E+09 | 20749.18 | 30-SEP-04:01 | -4.0 |
October | 0.311988E+10 | 23845.98 | 23-OCT-03:01 | -11.6 |
November | 0.913516E+10 | 24440.67 | 27-NOV-04:11 | -25.9 |
December | 0.112268E+11 | 24858.53 | 04-DEC-00:02 | -22.1 |
Annual Sum or Average | 0.456631E+11 | |||
Minimum of Months | 0.00 | 0.00 | -34.9 | |
Maximum of Months | 0.112268E+11 | 25074.48 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.142923E+11 | 38650.89 | 29-JAN-08:52 | -25.6 |
February | 0.776419E+10 | 38462.38 | 26-FEB-09:02 | -26.8 |
March | 0.410002E+10 | 37203.86 | 06-MAR-04:01 | -20.0 |
April | 0.973547E+09 | 35162.11 | 03-APR-03:01 | -21.1 |
May | 9008684.70 | 16332.77 | 27-MAY-05:03 | 0.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 14.88 |
August | 10804022.91 | 18282.57 | 30-AUG-05:02 | 0.00 |
September | 0.374351E+09 | 31790.41 | 25-SEP-04:01 | -1.1 |
October | 0.367547E+10 | 36544.58 | 23-OCT-03:01 | -11.6 |
November | 0.111486E+11 | 37754.10 | 27-NOV-04:11 | -25.9 |
December | 0.160367E+11 | 38521.75 | 04-DEC-00:02 | -22.1 |
Annual Sum or Average | 0.583850E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.8 | |
Maximum of Months | 0.160367E+11 | 38650.89 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.960305E+10 | 25508.00 | 29-JAN-08:52 | -25.6 |
February | 0.591598E+10 | 25195.18 | 27-FEB-03:02 | -34.9 |
March | 0.332498E+10 | 24331.53 | 06-MAR-04:01 | -20.0 |
April | 0.569826E+09 | 23255.50 | 03-APR-03:01 | -21.1 |
May | 4918529.56 | 9767.69 | 27-MAY-05:03 | 0.10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 14.88 |
August | 4601062.75 | 9115.51 | 30-AUG-05:02 | 0.00 |
September | 0.231946E+09 | 20906.74 | 25-SEP-04:01 | -1.1 |
October | 0.257427E+10 | 24154.22 | 23-OCT-03:01 | -11.6 |
November | 0.708258E+10 | 24661.16 | 27-NOV-04:11 | -25.9 |
December | 0.893090E+10 | 24900.79 | 04-DEC-00:02 | -22.1 |
Annual Sum or Average | 0.382430E+11 | |||
Minimum of Months | 0.00 | 0.00 | -34.9 | |
Maximum of Months | 0.960305E+10 | 25508.00 | 14.88 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.213357E+10 | 5442.18 | 02-JAN-10:40 | -17.6 |
February | 0.913364E+09 | 9477.81 | 09-FEB-06:03 | 0.00 |
March | 0.455970E+09 | 12461.52 | 12-MAR-13:22 | -7.8 |
April | 0.225865E+09 | 14029.01 | 09-APR-15:12 | 3.90 |
May | 0.199141E+09 | 13339.33 | 28-MAY-15:52 | 16.10 |
June | 0.232003E+09 | 12242.86 | 04-JUN-15:22 | 19.70 |
July | 0.300576E+09 | 13928.28 | 23-JUL-12:02 | 24.08 |
August | 0.330170E+09 | 13114.34 | 27-AUG-15:52 | 20.60 |
September | 0.166758E+09 | 11667.05 | 10-SEP-11:32 | 15.20 |
October | 0.213868E+09 | 11676.26 | 13-OCT-03:02 | -9.3 |
November | 0.786660E+09 | 9316.06 | 01-NOV-05:03 | -9.6 |
December | 0.132066E+10 | 8153.32 | 26-DEC-05:01 | -12.2 |
Annual Sum or Average | 0.727860E+10 | |||
Minimum of Months | 0.166758E+09 | 5442.18 | -17.6 | |
Maximum of Months | 0.213357E+10 | 14029.01 | 24.08 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.649183E+10 | 23756.91 | 02-JAN-06:13 | -15.2 |
February | 0.361491E+10 | 12098.41 | 21-FEB-06:12 | -23.3 |
March | 0.245773E+10 | 18022.06 | 12-MAR-12:32 | -8.7 |
April | 0.536605E+09 | 16899.07 | 02-APR-13:02 | -7.6 |
May | 0.111699E+09 | 18134.03 | 28-MAY-15:52 | 16.10 |
June | 70202155.06 | 13868.21 | 04-JUN-15:01 | 19.50 |
July | 81680090.63 | 16671.15 | 23-JUL-14:51 | 25.60 |
August | 54818766.29 | 15566.59 | 27-AUG-15:41 | 20.68 |
September | 71336785.50 | 15399.61 | 10-SEP-10:52 | 14.40 |
October | 0.110747E+10 | 9275.33 | 22-OCT-13:13 | -11.8 |
November | 0.423988E+10 | 10565.65 | 27-NOV-06:15 | -26.7 |
December | 0.560090E+10 | 11886.76 | 04-DEC-06:02 | -19.4 |
Annual Sum or Average | 0.244391E+11 | |||
Minimum of Months | 54818766.29 | 9275.33 | -26.7 | |
Maximum of Months | 0.649183E+10 | 23756.91 | 25.60 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.243278E+11 | 37032.37 | 30-JAN-05:12 | -25.6 |
February | 0.181438E+11 | 40131.52 | 27-FEB-05:12 | -36.1 |
March | 0.131170E+11 | 33086.76 | 01-MAR-06:13 | -28.5 |
April | 0.417253E+10 | 29215.90 | 03-APR-05:01 | -21.2 |
May | 0.494464E+09 | 19966.23 | 10-MAY-05:03 | 5.28 |
June | 0.113615E+09 | 18390.17 | 09-JUN-04:12 | 10.00 |
July | 0.107360E+09 | 18260.15 | 07-JUL-04:11 | 13.87 |
August | 0.340013E+09 | 14408.25 | 29-AUG-05:02 | 7.20 |
September | 0.221531E+10 | 17770.77 | 10-SEP-11:21 | 15.00 |
October | 0.976312E+10 | 32370.67 | 30-OCT-04:12 | -14.4 |
November | 0.218781E+11 | 35033.90 | 29-NOV-06:12 | -28.9 |
December | 0.254565E+11 | 34942.17 | 06-DEC-06:12 | -28.5 |
Annual Sum or Average | 0.120130E+12 | |||
Minimum of Months | 0.107360E+09 | 14408.25 | -36.1 | |
Maximum of Months | 0.254565E+11 | 40131.52 | 15.00 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 49464937.65 | 485.64 | 29-JAN-08:06 | -26.0 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -20.2 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 |
Annual Sum or Average | 49464937.65 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 49464937.65 | 485.64 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.738770E+09 | 598.41 | 12-JAN-22:13 | -36.3 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -20.2 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 |
Annual Sum or Average | 0.738770E+09 | |||
Minimum of Months | 0.00 | 0.00 | -36.3 | |
Maximum of Months | 0.738770E+09 | 598.41 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.801111E+09 | 621.63 | 11-JAN-24:00 | -36.1 |
February | 0.255654E+09 | 600.00 | 26-FEB-19:30 | -27.8 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 2581429.82 | 184.82 | 28-MAY-04:50 | 2.12 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 16.35 |
September | 0.113730E+09 | 588.88 | 25-SEP-03:25 | -0.9 |
October | 73658834.50 | 580.08 | 30-OCT-02:30 | -13.1 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 |
Annual Sum or Average | 0.124673E+10 | |||
Minimum of Months | 0.00 | 0.00 | -36.1 | |
Maximum of Months | 0.801111E+09 | 621.63 | 16.35 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -14.9 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -20.2 |
March | 0.00 | 0.00 | 01-MAR-00:05 | -28.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | -11.7 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 6.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.17 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 14.88 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 16.35 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 8.08 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 1.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -10.0 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -25.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -28.9 | |
Maximum of Months | 0.00 | 0.00 | 16.35 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180249E+11 | 19402.09 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.163527E+11 | 19402.09 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.194806E+11 | 19402.09 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.173504E+11 | 19402.09 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.187528E+11 | 19402.09 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.186803E+11 | 19402.09 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.174228E+11 | 19402.09 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.194803E+11 | 19402.09 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.173504E+11 | 19402.09 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.180252E+11 | 19402.09 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.178272E+11 | 19402.09 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.174231E+11 | 19402.09 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.216171E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.163527E+11 | 19402.09 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.194806E+11 | 19402.09 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.192516E+10 | 2187.81 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.143325E+10 | 2187.81 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.131968E+10 | 2187.81 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.101528E+10 | 1242.97 | 04-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.106674E+10 | 1040.96 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.104404E+10 | 1040.96 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.985965E+09 | 1141.96 | 26-JUL-14:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.113301E+10 | 1141.96 | 18-AUG-14:50 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.111298E+10 | 2187.81 | 28-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.140702E+10 | 2187.81 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.178796E+10 | 2187.81 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.194708E+10 | 2187.81 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.161782E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.985965E+09 | 1040.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.194708E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.119415E+10 | 1409.91 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.885190E+09 | 1409.91 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.834629E+09 | 1409.91 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.654889E+09 | 735.93 | 04-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.699100E+09 | 670.83 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.682556E+09 | 670.83 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.644228E+09 | 670.83 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.736591E+09 | 735.93 | 18-AUG-15:09 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.709955E+09 | 1228.64 | 28-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.876448E+09 | 1409.91 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.109728E+10 | 1409.91 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.123966E+10 | 1409.91 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.102547E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.644228E+09 | 670.83 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.123966E+10 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.177276E+10 | 2187.86 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.130619E+10 | 2187.86 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.127310E+10 | 2187.86 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.102062E+10 | 1243.00 | 04-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.107974E+10 | 1040.98 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.105663E+10 | 1040.98 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.996440E+09 | 1040.98 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.113838E+10 | 1040.98 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.109095E+10 | 2187.86 | 28-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.131907E+10 | 2187.86 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.160233E+10 | 2187.86 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.186461E+10 | 2187.86 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.155208E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.996440E+09 | 1040.98 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.186461E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.120532E+10 | 1409.91 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.871912E+09 | 1409.91 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.831414E+09 | 1409.91 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.659136E+09 | 982.28 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.685249E+09 | 670.83 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.672334E+09 | 670.83 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.634060E+09 | 735.93 | 25-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.726632E+09 | 735.93 | 03-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.708623E+09 | 1409.91 | 28-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.869727E+09 | 1409.91 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.109541E+10 | 1409.91 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.124753E+10 | 1409.91 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.102074E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.634060E+09 | 670.83 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.124753E+10 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.192185E+10 | 2187.81 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.142750E+10 | 2187.81 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.131623E+10 | 2187.81 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.101395E+10 | 1242.97 | 04-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.106546E+10 | 1040.96 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.104405E+10 | 1040.96 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.985427E+09 | 1040.96 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.113191E+10 | 1141.96 | 18-AUG-15:09 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.110919E+10 | 2187.81 | 28-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.139687E+10 | 2187.81 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.178373E+10 | 2187.81 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.194672E+10 | 2187.81 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.161429E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.985427E+09 | 1040.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.194672E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.119232E+10 | 1409.91 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.882417E+09 | 1409.91 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.833766E+09 | 1409.91 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.654441E+09 | 670.83 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.698416E+09 | 670.83 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.681912E+09 | 670.83 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.643579E+09 | 670.83 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.735854E+09 | 735.93 | 18-AUG-15:20 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.708560E+09 | 1228.64 | 28-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.874327E+09 | 1409.91 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.109210E+10 | 1409.91 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.123874E+10 | 1409.91 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.102364E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.643579E+09 | 670.83 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.123874E+10 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.177577E+10 | 2187.86 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.130455E+10 | 2187.86 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.127219E+10 | 2187.86 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.101937E+10 | 1243.00 | 04-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.107914E+10 | 1040.98 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.105615E+10 | 1040.98 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.995793E+09 | 1040.98 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.113749E+10 | 1040.98 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.108943E+10 | 2187.86 | 28-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.131745E+10 | 2187.86 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.160074E+10 | 2187.86 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.186905E+10 | 2187.86 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.155171E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.995793E+09 | 1040.98 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.186905E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.120324E+10 | 1409.91 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.869592E+09 | 1409.91 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.830622E+09 | 1409.91 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.657726E+09 | 982.28 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.685331E+09 | 670.83 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.672195E+09 | 670.83 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.633836E+09 | 735.93 | 25-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.725864E+09 | 735.93 | 07-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.706648E+09 | 1409.91 | 28-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.867664E+09 | 1409.91 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.109273E+10 | 1409.91 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.124685E+10 | 1409.91 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.101923E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.633836E+09 | 670.83 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.124685E+10 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.192185E+10 | 2187.81 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.142750E+10 | 2187.81 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.131616E+10 | 2187.81 | 01-MAR-08:09 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.101393E+10 | 1242.97 | 04-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.106546E+10 | 1040.96 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.104404E+10 | 1040.96 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.985376E+09 | 1040.96 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.113191E+10 | 1141.96 | 18-AUG-15:09 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.110907E+10 | 2187.81 | 28-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.139657E+10 | 2187.81 | 02-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.178327E+10 | 2187.81 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.194672E+10 | 2187.81 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.161419E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.985376E+09 | 1040.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.194672E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.119206E+10 | 1409.91 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.882238E+09 | 1409.91 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.833764E+09 | 1409.91 | 01-MAR-08:09 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.654430E+09 | 670.83 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.698381E+09 | 670.83 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.681903E+09 | 670.83 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.643531E+09 | 670.83 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.735854E+09 | 735.93 | 18-AUG-15:20 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.708520E+09 | 1228.64 | 28-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.874023E+09 | 1409.91 | 02-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.109210E+10 | 1409.91 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.123870E+10 | 1409.91 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.102355E+11 | 0.234352E+11 | ||||
Minimum of Months | 0.643531E+09 | 670.83 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.123870E+10 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.177570E+10 | 2187.86 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.130449E+10 | 2187.86 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.127179E+10 | 2187.86 | 01-MAR-08:09 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.101936E+10 | 1243.00 | 04-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.107914E+10 | 1040.98 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.105614E+10 | 1040.98 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.995760E+09 | 1040.98 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.113741E+10 | 1040.98 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.108943E+10 | 2187.86 | 28-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.131731E+10 | 2187.86 | 02-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.160084E+10 | 2187.86 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.186900E+10 | 2187.86 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.155164E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.995760E+09 | 1040.98 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.186900E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.120313E+10 | 1409.91 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.869434E+09 | 1409.91 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.830620E+09 | 1409.91 | 01-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.657687E+09 | 982.28 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.685291E+09 | 670.83 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.672195E+09 | 670.83 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.633834E+09 | 735.93 | 25-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.725855E+09 | 735.93 | 07-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.706644E+09 | 1409.91 | 28-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.867354E+09 | 1409.91 | 02-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.109247E+10 | 1409.91 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.124685E+10 | 1409.91 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.101914E+11 | 0.234351E+11 | ||||
Minimum of Months | 0.633834E+09 | 670.83 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.124685E+10 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.522764E+10 | 5470.56 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.474186E+10 | 5470.56 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.563465E+10 | 5470.56 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.503289E+10 | 5470.56 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.543115E+10 | 5470.56 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.540489E+10 | 5470.56 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.505915E+10 | 5470.56 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.563465E+10 | 5470.56 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.503289E+10 | 5470.56 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.522764E+10 | 5470.56 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.516637E+10 | 5470.56 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.505915E+10 | 5470.56 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.626529E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.474186E+10 | 5470.56 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.563465E+10 | 5470.56 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.180249E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.163527E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.194806E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.173504E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.187528E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.186803E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.174228E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.194803E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.173504E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.180252E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.178272E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.174231E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.216171E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.163527E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.194806E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.192516E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353709E+09 |
February | 0.136985E+10 | 0.143325E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287933E+09 |
March | 0.163685E+10 | 0.131968E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.440224E+09 |
April | 0.145243E+10 | 0.101528E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.511412E+09 |
May | 0.157338E+10 | 0.106674E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308765E+09 |
June | 0.156900E+10 | 0.104404E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 357498.08 | 0.181995E+09 |
July | 0.145680E+10 | 0.985965E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 952607.80 | 0.133673E+09 |
August | 0.163685E+10 | 0.113301E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 163838.25 | 0.159073E+09 |
September | 0.145243E+10 | 0.111298E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194011E+09 |
October | 0.150991E+10 | 0.140702E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402472E+09 |
November | 0.149516E+10 | 0.178796E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134573E+09 |
December | 0.145680E+10 | 0.194708E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264408E+09 |
Annual Sum or Average | 0.181194E+11 | 0.161782E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1473944.13 | 0.337225E+10 |
Minimum of Months | 0.136985E+10 | 0.985965E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133673E+09 |
Maximum of Months | 0.163685E+10 | 0.194708E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 952607.80 | 0.511412E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.119415E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234304E+09 |
February | 0.882782E+09 | 0.885190E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191121E+09 |
March | 0.105485E+10 | 0.834629E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293599E+09 |
April | 0.936002E+09 | 0.654889E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338265E+09 |
May | 0.101394E+10 | 0.699100E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204971E+09 |
June | 0.101113E+10 | 0.682556E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 237559.14 | 0.116510E+09 |
July | 0.938820E+09 | 0.644228E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 712191.65 | 84142602.34 |
August | 0.105485E+10 | 0.736591E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108571.82 | 0.101131E+09 |
September | 0.936002E+09 | 0.709955E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129008E+09 |
October | 0.973041E+09 | 0.876448E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266195E+09 |
November | 0.963541E+09 | 0.109728E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88614852.39 |
December | 0.938820E+09 | 0.123966E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173773E+09 |
Annual Sum or Average | 0.116768E+11 | 0.102547E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1058322.61 | 0.222163E+10 |
Minimum of Months | 0.882782E+09 | 0.644228E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84142602.34 |
Maximum of Months | 0.105485E+10 | 0.123966E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 712191.65 | 0.338265E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.177276E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347517E+09 |
February | 0.136988E+10 | 0.130619E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287651E+09 |
March | 0.163688E+10 | 0.127310E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444333E+09 |
April | 0.145246E+10 | 0.102062E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.517136E+09 |
May | 0.157341E+10 | 0.107974E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303438E+09 |
June | 0.156904E+10 | 0.105663E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 350619.05 | 0.172648E+09 |
July | 0.145684E+10 | 0.996440E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 974031.50 | 0.126387E+09 |
August | 0.163688E+10 | 0.113838E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 155591.08 | 0.153574E+09 |
September | 0.145246E+10 | 0.109095E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190315E+09 |
October | 0.150994E+10 | 0.131907E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394512E+09 |
November | 0.149520E+10 | 0.160233E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132091E+09 |
December | 0.145684E+10 | 0.186461E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257265E+09 |
Annual Sum or Average | 0.181198E+11 | 0.155208E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1480241.63 | 0.332687E+10 |
Minimum of Months | 0.136988E+10 | 0.996440E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126387E+09 |
Maximum of Months | 0.163688E+10 | 0.186461E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 974031.50 | 0.517136E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.120532E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240568E+09 |
February | 0.882782E+09 | 0.871912E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197608E+09 |
March | 0.105485E+10 | 0.831414E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309240E+09 |
April | 0.936002E+09 | 0.659136E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366564E+09 |
May | 0.101394E+10 | 0.685249E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206194E+09 |
June | 0.101113E+10 | 0.672334E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 235192.11 | 0.119851E+09 |
July | 0.938820E+09 | 0.634060E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 604220.86 | 89002008.60 |
August | 0.105485E+10 | 0.726632E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 103983.66 | 0.108051E+09 |
September | 0.936002E+09 | 0.708623E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127153E+09 |
October | 0.973041E+09 | 0.869727E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274238E+09 |
November | 0.963541E+09 | 0.109541E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93552079.26 |
December | 0.938820E+09 | 0.124753E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184339E+09 |
Annual Sum or Average | 0.116768E+11 | 0.102074E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 943396.64 | 0.231636E+10 |
Minimum of Months | 0.882782E+09 | 0.634060E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89002008.60 |
Maximum of Months | 0.105485E+10 | 0.124753E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 604220.86 | 0.366564E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.192185E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.790194E+09 |
February | 0.136985E+10 | 0.142750E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.638396E+09 |
March | 0.163685E+10 | 0.131623E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.959088E+09 |
April | 0.145243E+10 | 0.101395E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108255E+10 |
May | 0.157338E+10 | 0.106546E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.661264E+09 |
June | 0.156900E+10 | 0.104405E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 795983.06 | 0.394852E+09 |
July | 0.145680E+10 | 0.985427E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2617610.87 | 0.292324E+09 |
August | 0.163685E+10 | 0.113191E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 351140.32 | 0.340663E+09 |
September | 0.145243E+10 | 0.110919E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398664E+09 |
October | 0.150991E+10 | 0.139687E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.838174E+09 |
November | 0.149516E+10 | 0.178373E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292855E+09 |
December | 0.145680E+10 | 0.194672E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.574645E+09 |
Annual Sum or Average | 0.181194E+11 | 0.161429E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3764734.25 | 0.726367E+10 |
Minimum of Months | 0.136985E+10 | 0.985427E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292324E+09 |
Maximum of Months | 0.163685E+10 | 0.194672E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2617610.87 | 0.108255E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.119232E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.526818E+09 |
February | 0.649041E+09 | 0.882417E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426594E+09 |
March | 0.773965E+09 | 0.833766E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.652264E+09 |
April | 0.688021E+09 | 0.654441E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.745208E+09 |
May | 0.744847E+09 | 0.698416E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446640E+09 |
June | 0.742030E+09 | 0.681912E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 535431.14 | 0.259187E+09 |
July | 0.690839E+09 | 0.643579E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1965041.39 | 0.193380E+09 |
August | 0.773965E+09 | 0.735854E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 248211.42 | 0.227214E+09 |
September | 0.688021E+09 | 0.708560E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272579E+09 |
October | 0.715730E+09 | 0.874327E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.565418E+09 |
November | 0.708685E+09 | 0.109210E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194892E+09 |
December | 0.690839E+09 | 0.123874E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382426E+09 |
Annual Sum or Average | 0.858171E+10 | 0.102364E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2748683.95 | 0.489262E+10 |
Minimum of Months | 0.649041E+09 | 0.643579E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193380E+09 |
Maximum of Months | 0.773965E+09 | 0.123874E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1965041.39 | 0.745208E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.177577E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.792994E+09 |
February | 0.136988E+10 | 0.130455E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.651992E+09 |
March | 0.163688E+10 | 0.127219E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101055E+10 |
April | 0.145246E+10 | 0.101937E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117903E+10 |
May | 0.157341E+10 | 0.107914E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.680987E+09 |
June | 0.156904E+10 | 0.105615E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 795816.63 | 0.392788E+09 |
July | 0.145684E+10 | 0.995793E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2436890.84 | 0.295221E+09 |
August | 0.163688E+10 | 0.113749E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 349444.20 | 0.354053E+09 |
September | 0.145246E+10 | 0.108943E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424654E+09 |
October | 0.150994E+10 | 0.131745E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.877024E+09 |
November | 0.149520E+10 | 0.160074E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295877E+09 |
December | 0.145684E+10 | 0.186905E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.575528E+09 |
Annual Sum or Average | 0.181198E+11 | 0.155171E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3582151.67 | 0.753070E+10 |
Minimum of Months | 0.136988E+10 | 0.995793E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295221E+09 |
Maximum of Months | 0.163688E+10 | 0.186905E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2436890.84 | 0.117903E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.120324E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529558E+09 |
February | 0.882782E+09 | 0.869592E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429262E+09 |
March | 0.105485E+10 | 0.830622E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655610E+09 |
April | 0.936002E+09 | 0.657726E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.783281E+09 |
May | 0.101394E+10 | 0.685331E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462476E+09 |
June | 0.101113E+10 | 0.672195E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 530654.20 | 0.271798E+09 |
July | 0.938820E+09 | 0.633836E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1399470.22 | 0.204076E+09 |
August | 0.105485E+10 | 0.725864E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 234085.90 | 0.238037E+09 |
September | 0.936002E+09 | 0.706648E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274170E+09 |
October | 0.973041E+09 | 0.867664E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.569610E+09 |
November | 0.963541E+09 | 0.109273E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197625E+09 |
December | 0.938820E+09 | 0.124685E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387124E+09 |
Annual Sum or Average | 0.116768E+11 | 0.101923E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2164210.32 | 0.500263E+10 |
Minimum of Months | 0.882782E+09 | 0.633836E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197625E+09 |
Maximum of Months | 0.105485E+10 | 0.124685E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1399470.22 | 0.783281E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.192185E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.970043E+09 |
February | 0.136985E+10 | 0.142750E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.779911E+09 |
March | 0.163685E+10 | 0.131616E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114750E+10 |
April | 0.145243E+10 | 0.101393E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126641E+10 |
May | 0.157338E+10 | 0.106546E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.784962E+09 |
June | 0.156900E+10 | 0.104404E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 913972.11 | 0.479287E+09 |
July | 0.145680E+10 | 0.985376E+09 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2934223.84 | 0.359414E+09 |
August | 0.163685E+10 | 0.113191E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 376975.71 | 0.408130E+09 |
September | 0.145243E+10 | 0.110907E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454919E+09 |
October | 0.150991E+10 | 0.139657E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.974807E+09 |
November | 0.149516E+10 | 0.178327E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357098E+09 |
December | 0.145680E+10 | 0.194672E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703309E+09 |
Annual Sum or Average | 0.181194E+11 | 0.161419E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4225171.66 | 0.868579E+10 |
Minimum of Months | 0.136985E+10 | 0.985376E+09 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357098E+09 |
Maximum of Months | 0.163685E+10 | 0.194672E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2934223.84 | 0.126641E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.119206E+10 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648782E+09 |
February | 0.882782E+09 | 0.882238E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521780E+09 |
March | 0.105485E+10 | 0.833764E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.776963E+09 |
April | 0.936002E+09 | 0.654430E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.876936E+09 |
May | 0.101394E+10 | 0.698381E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538204E+09 |
June | 0.101113E+10 | 0.681903E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 611076.60 | 0.316502E+09 |
July | 0.938820E+09 | 0.643531E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2170231.41 | 0.239420E+09 |
August | 0.105485E+10 | 0.735854E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 261082.14 | 0.275196E+09 |
September | 0.936002E+09 | 0.708520E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316703E+09 |
October | 0.973041E+09 | 0.874023E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.657623E+09 |
November | 0.963541E+09 | 0.109210E+10 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238493E+09 |
December | 0.938820E+09 | 0.123870E+10 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469967E+09 |
Annual Sum or Average | 0.116768E+11 | 0.102355E+11 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3042390.15 | 0.587657E+10 |
Minimum of Months | 0.882782E+09 | 0.643531E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238493E+09 |
Maximum of Months | 0.105485E+10 | 0.123870E+10 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2170231.41 | 0.876936E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.177570E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.974945E+09 |
February | 0.136988E+10 | 0.130449E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.790686E+09 |
March | 0.163688E+10 | 0.127179E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120047E+10 |
April | 0.145246E+10 | 0.101936E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139298E+10 |
May | 0.157341E+10 | 0.107914E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.818559E+09 |
June | 0.156904E+10 | 0.105614E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 913888.38 | 0.477091E+09 |
July | 0.145684E+10 | 0.995760E+09 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2742529.27 | 0.363294E+09 |
August | 0.163688E+10 | 0.113741E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 375327.08 | 0.428302E+09 |
September | 0.145246E+10 | 0.108943E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.495296E+09 |
October | 0.150994E+10 | 0.131731E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101377E+10 |
November | 0.149520E+10 | 0.160084E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359069E+09 |
December | 0.145684E+10 | 0.186900E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.705661E+09 |
Annual Sum or Average | 0.181198E+11 | 0.155164E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4031744.73 | 0.902013E+10 |
Minimum of Months | 0.136988E+10 | 0.995760E+09 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359069E+09 |
Maximum of Months | 0.163688E+10 | 0.186900E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2742529.27 | 0.139298E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.120313E+10 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.650987E+09 |
February | 0.882782E+09 | 0.869434E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524945E+09 |
March | 0.105485E+10 | 0.830620E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.784183E+09 |
April | 0.936002E+09 | 0.657687E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.927487E+09 |
May | 0.101394E+10 | 0.685291E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557795E+09 |
June | 0.101113E+10 | 0.672195E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 609310.45 | 0.330929E+09 |
July | 0.938820E+09 | 0.633834E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1608577.57 | 0.251275E+09 |
August | 0.105485E+10 | 0.725855E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 251308.47 | 0.287881E+09 |
September | 0.936002E+09 | 0.706644E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321282E+09 |
October | 0.973041E+09 | 0.867354E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.668151E+09 |
November | 0.963541E+09 | 0.109247E+10 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240138E+09 |
December | 0.938820E+09 | 0.124685E+10 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472368E+09 |
Annual Sum or Average | 0.116768E+11 | 0.101914E+11 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2469196.49 | 0.601742E+10 |
Minimum of Months | 0.882782E+09 | 0.633834E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240138E+09 |
Maximum of Months | 0.105485E+10 | 0.124685E+10 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1608577.57 | 0.927487E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.522764E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.474186E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.563465E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.503289E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.543115E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.540489E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.505915E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.563465E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.503289E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.522764E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.516637E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.505915E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.626529E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.474186E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.563465E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.749205E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.610815E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.935184E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107580E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.632840E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 374031.81 | 0.367139E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1344708.90 | 0.271986E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79395.12 | 0.330478E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401151E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.848250E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285861E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556799E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1798135.83 | 0.706551E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271986E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1344708.90 | 0.107580E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127160E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104563E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161187E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184287E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107743E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 725356.59 | 0.620735E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3115040.04 | 0.455814E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187618.13 | 0.559146E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.675187E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142676E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.486649E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.935742E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4028014.76 | 0.120094E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455814E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3115040.04 | 0.184287E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139763E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114164E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173288E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198137E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120436E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455618.26 | 0.718287E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2256427.11 | 0.537956E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40814.52 | 0.630622E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.711625E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147225E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520462E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101858E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2752859.89 | 0.130677E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.520462E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2256427.11 | 0.198137E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 19402.09 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 19402.09 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 19402.09 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 19402.09 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 19402.09 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 19402.09 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 19402.09 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 19402.09 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 19402.09 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 19402.09 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 19402.09 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 19402.09 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 19402.09 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 19402.09 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2187.81 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1553.95 | 28-JAN-24:00 |
February | 2010.79 | 01-FEB-10:09 | 2187.81 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 946.43 | 25-FEB-00:53 |
March | 2010.79 | 01-MAR-10:09 | 2187.81 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 683.45 | 25-MAR-04:00 |
April | 2010.79 | 03-APR-09:09 | 1242.97 | 04-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1064.10 | 01-APR-19:00 |
May | 2010.79 | 01-MAY-09:09 | 1040.96 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 524.92 | 26-MAY-02:00 |
June | 2010.79 | 01-JUN-09:09 | 1040.96 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.51 | 30-JUN-15:00 | 548.47 | 25-JUN-06:00 |
July | 2010.79 | 03-JUL-09:09 | 1141.96 | 26-JUL-14:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.86 | 21-JUL-16:00 | 358.19 | 04-JUL-17:10 |
August | 2010.79 | 01-AUG-09:09 | 1141.96 | 18-AUG-14:50 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.74 | 11-AUG-17:00 | 404.47 | 30-AUG-00:53 |
September | 2010.79 | 01-SEP-09:09 | 2187.81 | 28-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 333.42 | 04-SEP-13:53 |
October | 2010.79 | 02-OCT-09:09 | 2187.81 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 641.45 | 21-OCT-04:00 |
November | 2010.79 | 01-NOV-09:09 | 2187.81 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 520.01 | 10-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 550.79 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.42 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 50.86 | 1553.95 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1028.23 | 28-JAN-24:00 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 627.85 | 25-FEB-00:53 |
March | 1295.83 | 01-MAR-10:09 | 1409.91 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 448.17 | 25-MAR-04:00 |
April | 1295.83 | 03-APR-09:09 | 735.93 | 04-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 694.26 | 01-APR-19:00 |
May | 1295.83 | 01-MAY-09:09 | 670.83 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 350.99 | 26-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 670.83 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.66 | 30-JUN-15:00 | 359.04 | 25-JUN-06:00 |
July | 1295.83 | 03-JUL-09:09 | 670.83 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.88 | 21-JUL-16:00 | 226.33 | 04-JUL-17:10 |
August | 1295.83 | 01-AUG-09:09 | 735.93 | 18-AUG-15:09 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.16 | 11-AUG-17:00 | 263.16 | 30-AUG-00:53 |
September | 1295.83 | 01-SEP-09:09 | 1228.64 | 28-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 212.25 | 04-SEP-13:53 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 421.91 | 21-OCT-04:00 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 342.38 | 10-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 361.95 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.25 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 33.88 | 1028.23 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2187.86 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1531.87 | 28-JAN-24:00 |
February | 2010.83 | 01-FEB-10:09 | 2187.86 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 939.95 | 25-FEB-00:53 |
March | 2010.83 | 01-MAR-10:09 | 2187.86 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 757.20 | 12-MAR-14:40 |
April | 2010.83 | 03-APR-09:09 | 1243.00 | 04-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1115.35 | 01-APR-19:00 |
May | 2010.83 | 01-MAY-09:09 | 1040.98 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 518.17 | 26-MAY-02:00 |
June | 2010.83 | 01-JUN-09:09 | 1040.98 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.42 | 30-JUN-15:00 | 510.21 | 25-JUN-06:00 |
July | 2010.83 | 03-JUL-09:09 | 1040.98 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.72 | 21-JUL-16:00 | 341.83 | 04-JUL-17:10 |
August | 2010.83 | 01-AUG-09:09 | 1040.98 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.73 | 11-AUG-17:00 | 392.37 | 30-AUG-00:53 |
September | 2010.83 | 01-SEP-09:09 | 2187.86 | 28-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 316.43 | 30-SEP-21:00 |
October | 2010.83 | 02-OCT-09:09 | 2187.86 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 630.42 | 22-OCT-17:55 |
November | 2010.83 | 01-NOV-09:09 | 2187.86 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 514.80 | 10-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 2187.86 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 539.31 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.43 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 50.72 | 1531.87 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1060.07 | 28-JAN-24:00 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 649.00 | 25-FEB-00:53 |
March | 1295.83 | 01-MAR-10:09 | 1409.91 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 476.94 | 25-MAR-04:00 |
April | 1295.83 | 03-APR-09:09 | 982.28 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 884.08 | 01-APR-19:00 |
May | 1295.83 | 01-MAY-09:09 | 670.83 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 348.47 | 26-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 670.83 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.63 | 30-JUN-15:00 | 363.57 | 25-JUN-06:00 |
July | 1295.83 | 03-JUL-09:09 | 735.93 | 25-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.80 | 21-JUL-16:00 | 242.05 | 04-JUL-17:10 |
August | 1295.83 | 01-AUG-09:09 | 735.93 | 03-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.14 | 11-AUG-17:00 | 276.44 | 30-AUG-00:53 |
September | 1295.83 | 01-SEP-09:09 | 1409.91 | 28-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 208.91 | 30-SEP-21:00 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 443.69 | 21-OCT-04:00 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 362.95 | 10-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 384.22 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.91 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 33.80 | 1060.07 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2187.81 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3500.88 | 28-JAN-24:00 |
February | 2010.79 | 01-FEB-10:09 | 2187.81 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2071.47 | 24-FEB-05:50 |
March | 2010.79 | 01-MAR-10:09 | 2187.81 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1560.81 | 14-MAR-21:02 |
April | 2010.79 | 03-APR-09:09 | 1242.97 | 04-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2263.05 | 01-APR-19:00 |
May | 2010.79 | 01-MAY-09:09 | 1040.96 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 1097.16 | 26-MAY-02:00 |
June | 2010.79 | 01-JUN-09:09 | 1040.96 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.17 | 30-JUN-15:00 | 1079.47 | 25-JUN-06:00 |
July | 2010.79 | 03-JUL-09:09 | 1040.96 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.50 | 21-JUL-16:00 | 827.34 | 04-JUL-17:00 |
August | 2010.79 | 01-AUG-09:09 | 1141.96 | 18-AUG-15:09 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.95 | 11-AUG-16:00 | 847.32 | 30-AUG-00:53 |
September | 2010.79 | 01-SEP-09:09 | 2187.81 | 28-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 697.92 | 04-SEP-13:53 |
October | 2010.79 | 02-OCT-09:09 | 2187.81 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1406.76 | 21-OCT-05:00 |
November | 2010.79 | 01-NOV-09:09 | 2187.81 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1140.17 | 10-NOV-05:10 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1196.38 | 28-DEC-02:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 697.92 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 117.50 | 3500.88 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1409.91 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2334.01 | 28-JAN-24:00 |
February | 1239.33 | 01-FEB-08:09 | 1409.91 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1382.12 | 25-FEB-00:53 |
March | 1239.33 | 01-MAR-08:09 | 1409.91 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1041.99 | 14-MAR-21:02 |
April | 1239.33 | 03-APR-07:10 | 670.83 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1518.25 | 02-APR-11:32 |
May | 1239.33 | 01-MAY-07:10 | 670.83 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 734.36 | 26-MAY-02:00 |
June | 1239.33 | 01-JUN-07:10 | 670.83 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.45 | 30-JUN-15:00 | 713.26 | 25-JUN-06:00 |
July | 1239.33 | 03-JUL-07:10 | 670.83 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.43 | 29-JUL-20:00 | 558.06 | 04-JUL-17:00 |
August | 1239.33 | 01-AUG-07:10 | 735.93 | 18-AUG-15:20 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.30 | 11-AUG-16:00 | 559.17 | 30-AUG-00:53 |
September | 1239.33 | 01-SEP-07:10 | 1228.64 | 28-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 480.53 | 04-SEP-13:53 |
October | 1239.33 | 02-OCT-07:10 | 1409.91 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 937.82 | 21-OCT-04:56 |
November | 1239.33 | 01-NOV-07:10 | 1409.91 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 760.25 | 10-NOV-05:04 |
December | 1239.33 | 01-DEC-08:09 | 1409.91 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 798.36 | 28-DEC-02:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 480.53 | |||||
Maximum of Months | 1239.33 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 98.43 | 2334.01 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2187.86 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3500.93 | 28-JAN-24:00 |
February | 2010.83 | 01-FEB-10:09 | 2187.86 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2100.42 | 25-FEB-00:53 |
March | 2010.83 | 01-MAR-10:09 | 2187.86 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1846.42 | 12-MAR-15:10 |
April | 2010.83 | 03-APR-09:09 | 1243.00 | 04-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2569.82 | 01-APR-19:00 |
May | 2010.83 | 01-MAY-09:09 | 1040.98 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 1115.01 | 26-MAY-02:00 |
June | 2010.83 | 01-JUN-09:09 | 1040.98 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.17 | 30-JUN-15:00 | 1135.49 | 18-JUN-14:00 |
July | 2010.83 | 03-JUL-09:09 | 1040.98 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.50 | 21-JUL-16:00 | 855.10 | 04-JUL-17:00 |
August | 2010.83 | 01-AUG-09:09 | 1040.98 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.94 | 11-AUG-16:10 | 848.29 | 30-AUG-00:53 |
September | 2010.83 | 01-SEP-09:09 | 2187.86 | 28-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 730.27 | 04-SEP-13:53 |
October | 2010.83 | 02-OCT-09:09 | 2187.86 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1460.67 | 22-OCT-17:55 |
November | 2010.83 | 01-NOV-09:09 | 2187.86 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1147.73 | 10-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 2187.86 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1194.29 | 28-DEC-02:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 730.27 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 117.50 | 3500.93 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2333.98 | 28-JAN-24:00 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1393.42 | 25-FEB-00:53 |
March | 1295.83 | 01-MAR-10:09 | 1409.91 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1042.83 | 14-MAR-21:02 |
April | 1295.83 | 03-APR-09:09 | 982.28 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1961.18 | 01-APR-19:00 |
May | 1295.83 | 01-MAY-09:09 | 670.83 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 749.24 | 27-MAY-19:55 |
June | 1295.83 | 01-JUN-09:09 | 670.83 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.45 | 30-JUN-15:00 | 714.78 | 25-JUN-06:00 |
July | 1295.83 | 03-JUL-09:09 | 735.93 | 25-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.33 | 21-JUL-16:00 | 582.12 | 04-JUL-17:00 |
August | 1295.83 | 01-AUG-09:09 | 735.93 | 07-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.30 | 11-AUG-16:00 | 569.72 | 30-AUG-00:53 |
September | 1295.83 | 01-SEP-09:09 | 1409.91 | 28-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 475.82 | 04-SEP-13:53 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 946.39 | 21-OCT-04:03 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 761.40 | 10-NOV-05:04 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 798.64 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 475.82 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 78.33 | 2333.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2187.81 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4358.65 | 28-JAN-24:00 |
February | 2010.79 | 01-FEB-10:09 | 2187.81 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2583.42 | 25-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 2187.81 | 01-MAR-08:09 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1934.98 | 14-MAR-21:02 |
April | 2010.79 | 03-APR-09:09 | 1242.97 | 04-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2692.35 | 01-APR-18:53 |
May | 2010.79 | 01-MAY-09:09 | 1040.96 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 1284.94 | 26-MAY-02:00 |
June | 2010.79 | 01-JUN-09:09 | 1040.96 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.04 | 30-JUN-15:00 | 1233.17 | 24-JUN-20:53 |
July | 2010.79 | 03-JUL-09:09 | 1040.96 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.88 | 21-JUL-16:00 | 1006.00 | 04-JUL-17:00 |
August | 2010.79 | 01-AUG-09:09 | 1141.96 | 18-AUG-15:09 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.51 | 11-AUG-16:00 | 991.19 | 30-AUG-00:53 |
September | 2010.79 | 01-SEP-09:09 | 2187.81 | 28-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 777.49 | 30-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 2187.81 | 02-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1753.66 | 21-OCT-04:50 |
November | 2010.79 | 01-NOV-09:09 | 2187.81 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1409.26 | 10-NOV-04:58 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1473.28 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 777.49 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 142.88 | 4358.65 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2905.71 | 28-JAN-24:00 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1722.27 | 25-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 1409.91 | 01-MAR-08:09 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1291.92 | 14-MAR-21:02 |
April | 1295.83 | 03-APR-09:09 | 670.83 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1811.06 | 01-APR-18:53 |
May | 1295.83 | 01-MAY-09:09 | 670.83 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 863.56 | 26-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 670.83 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.03 | 30-JUN-15:00 | 801.73 | 24-JUN-20:53 |
July | 1295.83 | 03-JUL-09:09 | 670.83 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.51 | 29-JUL-19:50 | 683.03 | 04-JUL-17:00 |
August | 1295.83 | 01-AUG-09:09 | 735.93 | 18-AUG-15:20 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 11-AUG-16:00 | 655.37 | 30-AUG-00:53 |
September | 1295.83 | 01-SEP-09:09 | 1228.64 | 28-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 525.14 | 04-SEP-13:53 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 02-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1174.30 | 21-OCT-04:24 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 946.47 | 10-NOV-05:09 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 981.65 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 525.14 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 104.51 | 2905.71 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2187.86 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4358.92 | 28-JAN-24:00 |
February | 2010.83 | 01-FEB-10:09 | 2187.86 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2583.43 | 25-FEB-01:00 |
March | 2010.83 | 01-MAR-10:09 | 2187.86 | 01-MAR-08:09 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 2191.96 | 12-MAR-14:50 |
April | 2010.83 | 03-APR-09:09 | 1243.00 | 04-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3152.04 | 01-APR-18:53 |
May | 2010.83 | 01-MAY-09:09 | 1040.98 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 1310.24 | 26-MAY-02:00 |
June | 2010.83 | 01-JUN-09:09 | 1040.98 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.04 | 30-JUN-15:00 | 1375.23 | 18-JUN-14:10 |
July | 2010.83 | 03-JUL-09:09 | 1040.98 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.88 | 21-JUL-16:00 | 1046.31 | 04-JUL-17:00 |
August | 2010.83 | 01-AUG-09:09 | 1040.98 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 11-AUG-16:10 | 994.11 | 30-AUG-00:53 |
September | 2010.83 | 01-SEP-09:09 | 2187.86 | 28-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 815.73 | 30-SEP-21:00 |
October | 2010.83 | 02-OCT-09:09 | 2187.86 | 02-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1760.18 | 21-OCT-04:24 |
November | 2010.83 | 01-NOV-09:09 | 2187.86 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1419.70 | 10-NOV-05:06 |
December | 2010.83 | 01-DEC-10:09 | 2187.86 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1474.00 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 815.73 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 142.88 | 4358.92 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2905.85 | 28-JAN-24:00 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1722.31 | 25-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 1409.91 | 01-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1293.84 | 14-MAR-21:02 |
April | 1295.83 | 03-APR-09:09 | 982.28 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2447.55 | 01-APR-18:53 |
May | 1295.83 | 01-MAY-09:09 | 670.83 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 901.08 | 27-MAY-19:55 |
June | 1295.83 | 01-JUN-09:09 | 670.83 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.03 | 30-JUN-15:00 | 825.61 | 24-JUN-20:53 |
July | 1295.83 | 03-JUL-09:09 | 735.93 | 25-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.25 | 21-JUL-16:00 | 713.32 | 04-JUL-17:00 |
August | 1295.83 | 01-AUG-09:09 | 735.93 | 07-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 11-AUG-16:00 | 669.28 | 30-AUG-00:53 |
September | 1295.83 | 01-SEP-09:09 | 1409.91 | 28-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 532.64 | 04-SEP-13:53 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 02-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1173.26 | 21-OCT-04:24 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 946.45 | 10-NOV-05:09 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 984.18 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 532.64 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 95.25 | 2905.85 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 5470.56 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 5470.56 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 5470.56 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 5470.56 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 5470.56 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 5470.56 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 5470.56 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 5470.56 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 5470.56 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 5470.56 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 5470.56 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 5470.56 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 5470.56 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3377.31 | 28-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2030.38 | 25-FEB-00:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1463.16 | 25-MAR-04:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2279.73 | 01-APR-18:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 1073.29 | 26-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.71 | 30-JUN-15:00 | 1079.65 | 25-JUN-06:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.72 | 21-JUL-16:00 | 696.65 | 04-JUL-17:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.24 | 11-AUG-17:00 | 842.11 | 30-AUG-00:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 678.53 | 04-SEP-13:53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1368.68 | 21-OCT-04:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1118.16 | 10-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1178.45 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 678.53 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.72 | 3377.31 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 5794.42 | 28-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3520.68 | 25-FEB-00:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 2532.83 | 25-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3920.81 | 01-APR-18:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 1850.68 | 26-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.42 | 30-JUN-15:00 | 1795.74 | 25-JUN-06:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.84 | 29-JUL-17:01 | 1203.66 | 04-JUL-17:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 11-AUG-16:00 | 1436.92 | 30-AUG-00:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 1098.80 | 04-SEP-13:53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2332.21 | 21-OCT-04:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1937.72 | 10-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2000.03 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1098.80 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.84 | 5794.42 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 6253.98 | 28-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3864.28 | 25-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 2783.85 | 14-MAR-21:02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4407.74 | 01-APR-18:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 1977.27 | 26-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.86 | 30-JUN-15:00 | 1861.05 | 24-JUN-20:53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.23 | 21-JUL-16:00 | 1500.31 | 04-JUL-17:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.40 | 11-AUG-18:00 | 1511.41 | 30-AUG-00:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 1178.85 | 04-SEP-13:53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2437.18 | 21-OCT-04:50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2063.44 | 10-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2186.70 | 28-DEC-02:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1178.85 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.23 | 6253.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 102109.34 | 19-JAN-08:12 | 85273.20 | 97010.43 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 115281.62 | 07-FEB-17:01 | 48471.08 | 97009.71 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 118622.47 | 23-MAR-19:01 | 17952.25 | 43114.94 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 121727.18 | 15-APR-06:11 | 17952.25 | 21558.68 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 01-MAY-00:03 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 01-JUL-00:03 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 01-AUG-00:03 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 01-SEP-00:03 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 139476.55 | 13-OCT-07:11 | 170546.39 | 194020.86 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 107321.45 | 13-NOV-07:11 | 25133.15 | 45271.53 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 112105.93 | 26-DEC-07:11 | 28723.60 | 51738.90 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 0.00 | 0.00 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 139476.55 | 170546.39 | 194020.86 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 29446.77 | 25-JAN-14:10 | 16014.58 | 17424.44 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 83603.40 | 10-FEB-06:01 | 11285.67 | 3761.52 | 53531.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 88914.45 | 20-MAR-04:01 | 0.00 | 4836.24 | 53438.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 98251.32 | 20-APR-04:02 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 99309.00 | 26-MAY-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 97606.00 | 24-JUN-04:13 | 0.00 | 3224.16 | 26719.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 97456.76 | 20-JUL-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 97835.63 | 15-AUG-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 100717.08 | 18-SEP-04:02 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 99310.57 | 07-OCT-04:12 | 0.00 | 3224.16 | 26719.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 84009.09 | 03-NOV-05:02 | 12897.91 | 4298.88 | 61179.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 69218.26 | 21-DEC-06:01 | 11285.67 | 3761.52 | 53531.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 29446.77 | 0.00 | 3224.16 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 100717.08 | 16014.58 | 17424.44 | 61179.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 18268.58 | 27-JAN-17:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 22199.44 | 16-FEB-17:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 48824.79 | 23-MAR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 80636.80 | 21-APR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 80912.69 | 19-MAY-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 82646.14 | 24-JUN-04:12 | 0.00 | 3224.16 | 26719.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 88282.06 | 05-JUL-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 84138.74 | 14-AUG-04:12 | 0.00 | 2149.44 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 81411.55 | 05-SEP-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 74188.96 | 06-OCT-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18953.12 | 03-NOV-16:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17741.91 | 22-DEC-17:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 17741.91 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 88282.06 | 15316.26 | 17424.44 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 15455.78 | 20-JAN-17:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17873.13 | 09-FEB-17:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 20654.67 | 22-MAR-16:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 38424.17 | 21-APR-16:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 72305.48 | 11-MAY-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 79681.44 | 24-JUN-04:12 | 0.00 | 3224.16 | 26719.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 80339.80 | 05-JUL-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 80564.09 | 03-AUG-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 35761.21 | 01-SEP-16:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 23205.82 | 04-OCT-16:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 15732.38 | 02-NOV-16:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14516.15 | 21-DEC-17:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 14516.15 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 80564.09 | 15316.26 | 17424.44 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1786.21 | 19-JAN-16:10 | 1923.11 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.09 |
February | 2552.17 | 09-FEB-06:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.57 |
March | 4002.80 | 22-MAR-13:50 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8650.11 | 26-APR-15:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.29 |
May | 17546.11 | 21-MAY-05:42 | 607.30 | 346.96 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.74 |
June | 18210.38 | 07-JUN-03:32 | 0.00 | 269.88 | 2982.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.43 |
July | 19332.14 | 23-JUL-13:22 | 1012.16 | 578.27 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.44 |
August | 16745.26 | 06-AUG-14:02 | 506.08 | 289.13 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.37 |
September | 8669.48 | 01-SEP-13:30 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.10 |
October | 5952.18 | 04-OCT-14:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.69 |
November | 2562.72 | 03-NOV-05:02 | 1619.46 | 539.77 | 7681.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.66 |
December | 1897.49 | 23-DEC-06:03 | 1417.03 | 472.30 | 6721.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1786.21 | 0.00 | 269.88 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19332.14 | 2010.79 | 2187.81 | 7681.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2078.68 | 23-JAN-06:03 | 913.19 | 304.37 | 4331.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3070.56 | 15-FEB-10:45 | 2591.66 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.66 |
March | 12479.95 | 27-MAR-10:15 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.40 |
April | 25765.57 | 23-APR-09:22 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.75 |
May | 32461.28 | 21-MAY-08:21 | 652.28 | 372.66 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.88 |
June | 27485.01 | 18-JUN-09:11 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.62 |
July | 31031.06 | 23-JUL-09:22 | 652.28 | 372.66 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.61 |
August | 22722.48 | 27-AUG-10:32 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.49 |
September | 26815.70 | 10-SEP-08:52 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.70 |
October | 11312.12 | 03-OCT-09:35 | 2591.66 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.76 |
November | 2680.29 | 04-NOV-05:02 | 1043.64 | 347.85 | 4950.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.22 |
December | 2318.31 | 23-DEC-06:03 | 913.19 | 304.37 | 4331.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2078.68 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32461.28 | 2591.66 | 1341.67 | 4950.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4669.38 | 25-JAN-13:30 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.13 |
February | 15740.18 | 15-FEB-13:30 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 31087.26 | 12-MAR-13:22 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 594.74 |
April | 44122.64 | 23-APR-12:01 | 809.75 | 462.62 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.87 |
May | 46700.19 | 21-MAY-13:01 | 1012.19 | 578.28 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295.02 |
June | 42313.16 | 18-JUN-11:51 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.09 |
July | 48180.04 | 23-JUL-13:22 | 1012.19 | 578.28 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.97 |
August | 43178.92 | 27-AUG-13:11 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.63 |
September | 40452.84 | 10-SEP-11:32 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.17 |
October | 25621.52 | 03-OCT-13:20 | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.10 |
November | 12164.03 | 08-NOV-13:30 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.48 |
December | 3429.50 | 27-DEC-12:50 | 1058.33 | 1805.57 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3429.50 | 506.09 | 289.14 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 48180.04 | 2010.83 | 1805.57 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 594.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2453.72 | 23-JAN-14:40 | 1295.83 | 982.28 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.66 |
February | 4079.86 | 09-FEB-06:03 | 521.82 | 173.92 | 2475.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.29 |
March | 11809.72 | 26-MAR-16:53 | 260.91 | 149.06 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 31653.72 | 23-APR-15:21 | 521.82 | 298.13 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.31 |
May | 34612.20 | 28-MAY-17:51 | 0.00 | 335.39 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.23 |
June | 31533.95 | 10-JUN-17:41 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.01 |
July | 31378.88 | 23-JUL-15:22 | 587.05 | 335.39 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.73 |
August | 31902.97 | 27-AUG-17:11 | 0.00 | 260.86 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.90 |
September | 22363.27 | 02-SEP-17:05 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.58 |
October | 8183.39 | 03-OCT-14:50 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.06 |
November | 3976.17 | 03-NOV-05:02 | 1043.64 | 347.85 | 4950.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.58 |
December | 3304.04 | 26-DEC-05:03 | 0.00 | 304.37 | 3363.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2453.72 | 0.00 | 149.06 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34612.20 | 1295.83 | 982.28 | 4950.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 334.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1483.37 | 07-JAN-17:02 | 607.30 | 729.22 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.28 |
February | 1589.77 | 09-FEB-16:10 | 1923.11 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2210.43 | 22-MAR-15:00 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4819.06 | 28-APR-14:00 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14642.72 | 31-MAY-04:52 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16702.10 | 09-JUN-04:23 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.15 |
July | 16538.21 | 11-JUL-04:22 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.52 |
August | 12924.28 | 01-AUG-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.81 |
September | 4732.11 | 01-SEP-13:40 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.60 |
October | 2309.83 | 06-OCT-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.54 |
November | 1482.23 | 04-NOV-16:02 | 506.08 | 607.68 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1479.05 | 23-DEC-17:02 | 506.08 | 607.68 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1479.05 | 0.00 | 269.88 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16702.10 | 2010.79 | 2187.81 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2290.27 | 18-JAN-06:04 | 913.19 | 304.37 | 4331.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.91 |
February | 2635.44 | 15-FEB-11:15 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.36 |
March | 8970.91 | 31-MAR-10:05 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.12 |
April | 18526.66 | 23-APR-10:12 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 519.75 |
May | 34410.47 | 14-MAY-09:31 | 652.28 | 372.66 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.56 |
June | 31120.52 | 04-JUN-09:41 | 521.82 | 298.13 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.66 |
July | 34213.41 | 23-JUL-09:31 | 652.28 | 372.66 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.33 |
August | 25209.46 | 27-AUG-10:21 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.00 |
September | 25897.41 | 10-SEP-09:32 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.45 |
October | 7177.78 | 03-OCT-10:10 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.96 |
November | 2228.34 | 14-NOV-06:04 | 913.19 | 304.37 | 4331.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.02 |
December | 2203.97 | 07-DEC-06:04 | 913.19 | 304.37 | 4331.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2203.97 | 326.14 | 186.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34410.47 | 2478.65 | 1341.67 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 519.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4536.30 | 25-JAN-13:40 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.48 |
February | 15019.87 | 15-FEB-13:40 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 43564.53 | 26-MAR-14:02 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 42993.15 | 23-APR-12:51 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 615.80 |
May | 49558.48 | 14-MAY-12:11 | 1012.19 | 578.28 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.64 |
June | 47139.51 | 18-JUN-12:41 | 809.75 | 462.62 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 424.60 |
July | 52536.99 | 23-JUL-13:31 | 1012.19 | 578.28 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.53 |
August | 51800.91 | 27-AUG-13:41 | 1012.19 | 578.28 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.10 |
September | 42582.86 | 10-SEP-11:32 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.36 |
October | 23958.42 | 03-OCT-13:30 | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.13 |
November | 10337.03 | 08-NOV-13:30 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.25 |
December | 3341.12 | 09-DEC-06:04 | 1821.93 | 607.25 | 8642.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3341.12 | 607.31 | 346.97 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 52536.99 | 2010.83 | 1040.98 | 8642.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 615.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2321.92 | 18-JAN-06:04 | 913.19 | 304.37 | 4331.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.90 |
February | 2455.27 | 16-FEB-15:40 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.81 |
March | 6507.47 | 27-MAR-16:50 | 391.37 | 372.68 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.60 |
April | 28669.22 | 22-APR-17:41 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 580.72 |
May | 32755.43 | 28-MAY-17:51 | 0.00 | 335.39 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.91 |
June | 30458.51 | 04-JUN-19:01 | 0.00 | 260.86 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.62 |
July | 29138.75 | 30-JUL-18:42 | 0.00 | 223.59 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.18 |
August | 30024.02 | 27-AUG-17:41 | 0.00 | 372.66 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.35 |
September | 18544.80 | 02-SEP-17:05 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.05 |
October | 3972.98 | 03-OCT-15:10 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.88 |
November | 2367.05 | 08-NOV-15:40 | 1239.33 | 1163.55 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.40 |
December | 2336.07 | 19-DEC-06:04 | 1043.64 | 347.85 | 4950.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2321.92 | 0.00 | 223.59 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32755.43 | 1239.33 | 1163.55 | 4950.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 580.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1530.12 | 07-JAN-17:02 | 607.30 | 729.22 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.59 |
February | 1545.85 | 11-FEB-17:02 | 506.08 | 607.68 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.78 |
March | 2099.27 | 22-MAR-15:40 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4110.85 | 28-APR-15:20 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.50 |
May | 14553.49 | 31-MAY-05:01 | 1417.03 | 472.30 | 6721.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.54 |
June | 17021.95 | 12-JUN-04:11 | 0.00 | 472.30 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.26 |
July | 17373.60 | 07-JUL-04:13 | 0.00 | 472.30 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.57 |
August | 12260.43 | 05-AUG-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.78 |
September | 3787.48 | 01-SEP-16:00 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.47 |
October | 2107.39 | 04-OCT-15:40 | 1923.11 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.56 |
November | 1521.63 | 18-NOV-17:02 | 607.30 | 729.22 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1521.66 | 23-DEC-17:02 | 506.08 | 607.68 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1521.63 | 0.00 | 337.35 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17373.60 | 1923.11 | 1141.96 | 6721.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2283.46 | 21-JAN-06:04 | 1043.64 | 347.85 | 4950.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2301.38 | 04-FEB-06:04 | 1043.64 | 347.85 | 4950.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6166.76 | 31-MAR-10:15 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.05 |
April | 12770.97 | 22-APR-09:25 | 818.42 | 447.22 | 1547.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.28 |
May | 33734.80 | 14-MAY-09:21 | 652.28 | 372.66 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 332.35 |
June | 30704.70 | 04-JUN-09:51 | 521.82 | 298.13 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 390.75 |
July | 30438.68 | 09-JUL-08:21 | 521.82 | 298.13 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.63 |
August | 23144.70 | 27-AUG-10:21 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.72 |
September | 26540.90 | 10-SEP-09:21 | 587.05 | 335.39 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295.08 |
October | 4938.10 | 03-OCT-10:00 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.06 |
November | 2302.88 | 03-NOV-05:04 | 1043.64 | 347.85 | 4950.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.06 |
December | 1919.90 | 30-DEC-17:02 | 391.37 | 469.93 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1919.90 | 391.37 | 260.86 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33734.80 | 2478.65 | 1341.67 | 4950.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 390.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3915.87 | 25-JAN-13:40 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.91 |
February | 11853.27 | 15-FEB-13:40 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 22917.69 | 31-MAR-13:50 | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.05 |
April | 38893.76 | 30-APR-13:31 | 809.75 | 462.62 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1016.62 |
May | 51307.98 | 21-MAY-13:41 | 1012.19 | 578.28 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 624.01 |
June | 48831.13 | 04-JUN-14:31 | 910.97 | 520.45 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 406.28 |
July | 47981.92 | 23-JUL-13:41 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.93 |
August | 53081.29 | 27-AUG-13:41 | 1012.19 | 578.28 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.20 |
September | 43605.94 | 10-SEP-12:02 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.30 |
October | 21719.05 | 03-OCT-13:30 | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.16 |
November | 7085.40 | 08-NOV-13:40 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.41 |
December | 2996.35 | 30-DEC-17:02 | 607.31 | 729.23 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2996.35 | 607.31 | 346.97 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 53081.29 | 2010.83 | 1040.98 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1016.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2378.24 | 27-JAN-06:04 | 1043.64 | 347.85 | 4950.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.47 |
February | 2434.65 | 16-FEB-06:04 | 1043.64 | 347.85 | 4950.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.95 |
March | 5231.97 | 27-MAR-17:00 | 391.37 | 372.68 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.88 |
April | 29144.02 | 22-APR-17:41 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 716.64 |
May | 33138.76 | 14-MAY-18:41 | 0.00 | 335.39 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 462.54 |
June | 31952.16 | 11-JUN-18:31 | 0.00 | 298.13 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 378.33 |
July | 27203.24 | 08-JUL-19:02 | 0.00 | 223.59 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.81 |
August | 30872.81 | 27-AUG-17:41 | 0.00 | 372.66 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295.87 |
September | 15589.87 | 02-SEP-17:05 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.66 |
October | 3331.91 | 03-OCT-15:20 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.49 |
November | 2385.19 | 15-NOV-06:04 | 1043.64 | 347.85 | 4950.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2373.79 | 09-DEC-06:04 | 1174.10 | 391.33 | 5569.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2373.79 | 0.00 | 223.59 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33138.76 | 1239.33 | 670.83 | 5569.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 716.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10170.41 | 12-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9060.42 | 27-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7667.12 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.97 |
April | 10233.15 | 24-APR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.82 |
May | 13410.42 | 22-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.97 |
June | 14059.15 | 05-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.71 |
July | 15676.82 | 24-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.45 |
August | 13769.80 | 07-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.64 |
September | 10988.65 | 11-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.99 |
October | 8608.48 | 02-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.10 |
November | 7818.32 | 27-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7315.27 | 15-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 7315.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15676.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13963.94 | 29-JAN-02:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3532.57 |
February | 13969.86 | 25-FEB-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1414.13 |
March | 14091.35 | 31-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1530.72 |
April | 10202.25 | 03-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1458.00 |
May | 5549.10 | 12-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.57 |
June | 7174.43 | 30-JUN-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.04 | 0.00 |
July | 8435.75 | 05-JUL-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.37 |
August | 7783.96 | 02-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.77 |
September | 6056.00 | 05-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.75 |
October | 11923.54 | 30-OCT-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1696.83 |
November | 12388.39 | 30-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14070.82 | 15-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5549.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14091.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.04 | 3532.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.03 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1026.21 |
March | 1301.35 | 22-MAR-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8567.75 | 21-APR-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.92 |
May | 14150.11 | 31-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.18 |
June | 15409.98 | 29-JUN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.38 | 0.00 |
July | 16008.89 | 21-JUL-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.77 | 0.00 |
August | 13402.09 | 11-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.21 |
September | 5809.07 | 07-SEP-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.00 |
October | 1196.33 | 03-OCT-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.55 |
November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1163.72 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16008.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.77 | 1231.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1189.48 | 23-JAN-15:20 | 222.14 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3664.24 | 15-FEB-16:15 | 444.28 | 900.23 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6824.48 | 31-MAR-24:00 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9002.37 | 20-APR-19:00 | 23.38 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3551.39 | 31-MAY-23:20 | 0.00 | 50.02 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5487.78 | 30-JUN-23:42 | 0.00 | 100.03 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7405.68 | 31-JUL-23:35 | 0.00 | 50.02 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8808.94 | 27-AUG-18:45 | 0.00 | 50.02 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3262.47 | 30-SEP-24:00 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4548.50 | 31-OCT-24:00 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5675.45 | 08-NOV-16:00 | 444.28 | 900.23 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7062.67 | 26-DEC-15:00 | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1189.48 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9002.37 | 444.28 | 900.23 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 634.18 | 12-JAN-10:00 | 222.14 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3160.59 | 16-FEB-16:15 | 444.28 | 900.23 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5985.05 | 31-MAR-23:20 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8567.51 | 20-APR-19:00 | 23.38 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3262.10 | 31-MAY-24:00 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5154.06 | 30-JUN-23:55 | 0.00 | 50.02 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7060.62 | 31-JUL-23:27 | 0.00 | 75.02 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7996.41 | 27-AUG-18:50 | 0.00 | 50.02 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2331.86 | 02-SEP-18:10 | 0.00 | 50.02 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3531.88 | 03-OCT-16:00 | 222.14 | 450.11 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4973.68 | 08-NOV-15:55 | 444.28 | 900.23 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6004.52 | 21-DEC-17:00 | 222.14 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 634.18 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8567.51 | 444.28 | 900.23 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 617.03 | 12-JAN-08:15 | 444.28 | 900.23 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2725.99 | 15-FEB-16:10 | 222.14 | 450.11 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5532.04 | 31-MAR-17:40 | 23.38 | 150.04 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8555.74 | 20-APR-19:00 | 23.38 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3202.26 | 31-MAY-23:33 | 0.00 | 75.02 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5112.39 | 30-JUN-23:32 | 0.00 | 125.04 | 29229.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7024.99 | 31-JUL-23:17 | 0.00 | 75.02 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8024.71 | 27-AUG-18:50 | 0.00 | 50.02 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2179.02 | 02-SEP-18:10 | 0.00 | 50.02 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3385.08 | 03-OCT-16:00 | 222.14 | 450.11 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4532.22 | 08-NOV-15:50 | 222.14 | 450.11 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5532.36 | 21-DEC-17:00 | 222.14 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 617.03 | 0.00 | 50.02 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8555.74 | 444.28 | 900.23 | 29229.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 90055.14 | 20-JAN-17:00 | 4808.68 | 5470.56 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 182034.03 | 09-FEB-17:00 | 4808.68 | 5470.56 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358047.68 | 31-MAR-24:00 | 0.00 | 303.90 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 369485.29 | 21-APR-16:00 | 4808.68 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 177543.12 | 31-MAY-24:00 | 0.00 | 303.90 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 269572.98 | 30-JUN-24:00 | 0.00 | 607.79 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 362266.29 | 31-JUL-23:55 | 0.00 | 1215.59 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 371218.76 | 11-AUG-16:00 | 4808.68 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 176704.48 | 30-SEP-24:00 | 0.00 | 303.90 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 266184.06 | 31-OCT-24:00 | 0.00 | 303.90 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 274539.90 | 08-NOV-17:00 | 4808.68 | 5470.56 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 366108.22 | 26-DEC-17:00 | 4808.68 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 90055.14 | 0.00 | 303.90 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 371218.76 | 4808.68 | 5470.56 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.172277E+13 | 1239526.66 | 23-JAN-16:40 | 0.112701E+13 | 2336776.04 | 12-JAN-07:30 |
February | 0.192100E+13 | 1398727.12 | 01-FEB-16:00 | 0.678240E+12 | 2541901.65 | 27-FEB-07:30 |
March | 0.254755E+13 | 1561774.02 | 16-MAR-10:50 | 0.328634E+12 | 1912426.19 | 01-MAR-07:30 |
April | 0.273771E+13 | 1752316.77 | 21-APR-15:50 | 0.597440E+11 | 1354590.05 | 03-APR-06:10 |
May | 0.183546E+13 | 1580894.26 | 31-MAY-15:30 | 0.108612E+10 | 267377.23 | 27-MAY-06:10 |
June | 0.218660E+13 | 1806928.37 | 21-JUN-15:39 | 5599.44 | 6.09 | 01-JUN-18:30 |
July | 0.251101E+13 | 1980091.60 | 21-JUL-14:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.289663E+13 | 2092003.05 | 11-AUG-15:20 | 0.109762E+10 | 336070.78 | 31-AUG-06:10 |
September | 0.160243E+13 | 1331967.33 | 07-SEP-15:50 | 0.263361E+11 | 532633.07 | 29-SEP-06:10 |
October | 0.211136E+13 | 1385042.84 | 31-OCT-07:00 | 0.227669E+12 | 1402144.62 | 30-OCT-06:10 |
November | 0.244824E+13 | 1539916.46 | 22-NOV-16:30 | 0.890736E+12 | 2236478.09 | 27-NOV-07:19 |
December | 0.285604E+13 | 1667199.04 | 27-DEC-11:20 | 0.125344E+13 | 2073031.21 | 15-DEC-07:40 |
Annual Sum or Average | 0.273768E+14 | 0.459399E+13 | ||||
Minimum of Months | 0.160243E+13 | 1239526.66 | 0.00 | 0.00 | ||
Maximum of Months | 0.289663E+13 | 2092003.05 | 0.125344E+13 | 2541901.65 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.295787E+12 | 0.623637E+11 | 0.766053E+12 | 0.213355E+12 | 0.187782E+12 | 0.133226E+11 | 0.00 | 0.562867E+10 | 0.188543E+09 | 0.121743E+12 | 0.834377E+10 | 0.482016E+11 | 0.00 |
February | 0.255828E+12 | 0.426998E+11 | 0.978954E+12 | 0.195339E+12 | 0.170399E+12 | 0.119841E+11 | 0.00 | 0.205580E+11 | 0.780946E+09 | 0.193297E+12 | 0.736189E+10 | 0.437956E+11 | 0.00 |
March | 0.291658E+12 | 0.327220E+11 | 0.141687E+13 | 0.226059E+12 | 0.195557E+12 | 0.130565E+11 | 0.00 | 0.425573E+11 | 0.186264E+10 | 0.267699E+12 | 0.800780E+10 | 0.514970E+11 | 0.00 |
April | 0.254486E+12 | 0.190834E+11 | 0.165903E+13 | 0.211501E+12 | 0.208725E+12 | 0.115604E+11 | 0.00 | 0.597691E+11 | 0.456936E+10 | 0.259140E+12 | 0.316917E+10 | 0.466842E+11 | 0.00 |
May | 0.273984E+12 | 0.107131E+11 | 0.774844E+12 | 0.219699E+12 | 0.247036E+12 | 0.224100E+11 | 0.00 | 0.351362E+11 | 0.129523E+11 | 0.188909E+12 | 0.330634E+09 | 0.494459E+11 | 0.00 |
June | 0.272190E+12 | 0.503126E+10 | 0.106252E+13 | 0.217934E+12 | 0.272038E+12 | 0.362647E+11 | 0.00 | 0.109502E+12 | 0.530348E+11 | 0.110439E+12 | 0.394066E+09 | 0.472534E+11 | 0.00 |
July | 0.254346E+12 | 0.751282E+10 | 0.139340E+13 | 0.213265E+12 | 0.266969E+12 | 0.408117E+11 | 0.00 | 0.192723E+12 | 0.681979E+11 | 0.298575E+11 | 0.621973E+09 | 0.433008E+11 | 0.00 |
August | 0.285392E+12 | 0.152657E+11 | 0.173200E+13 | 0.226057E+12 | 0.253655E+12 | 0.320876E+11 | 0.00 | 0.174272E+12 | 0.564458E+11 | 0.749518E+11 | 0.245870E+09 | 0.462521E+11 | 0.00 |
September | 0.257710E+12 | 0.259693E+11 | 0.740713E+12 | 0.211501E+12 | 0.191383E+12 | 0.131343E+11 | 0.00 | 0.170641E+11 | 0.212638E+10 | 0.988948E+11 | 0.209963E+10 | 0.418352E+11 | 0.00 |
October | 0.276159E+12 | 0.406361E+11 | 0.108340E+13 | 0.213346E+12 | 0.184052E+12 | 0.114336E+11 | 0.00 | 0.277185E+11 | 0.177369E+10 | 0.222966E+12 | 0.584947E+10 | 0.440279E+11 | 0.00 |
November | 0.287060E+12 | 0.546324E+11 | 0.135889E+13 | 0.205306E+12 | 0.179965E+12 | 0.128419E+11 | 0.00 | 0.367260E+11 | 0.120801E+10 | 0.258937E+12 | 0.793954E+10 | 0.447335E+11 | 0.00 |
December | 0.290857E+12 | 0.685901E+11 | 0.170972E+13 | 0.213281E+12 | 0.186004E+12 | 0.128319E+11 | 0.00 | 0.507523E+11 | 0.163118E+10 | 0.267840E+12 | 0.820589E+10 | 0.463285E+11 | 0.00 |
Annual Sum or Average | 0.329546E+13 | 0.385220E+12 | 0.146764E+14 | 0.256664E+13 | 0.254356E+13 | 0.231739E+12 | 0.00 | 0.772407E+12 | 0.204771E+12 | 0.209467E+13 | 0.525697E+11 | 0.553356E+12 | 0.00 |
Minimum of Months | 0.254346E+12 | 0.503126E+10 | 0.740713E+12 | 0.195339E+12 | 0.170399E+12 | 0.114336E+11 | 0.00 | 0.562867E+10 | 0.188543E+09 | 0.298575E+11 | 0.245870E+09 | 0.418352E+11 | 0.00 |
Maximum of Months | 0.295787E+12 | 0.685901E+11 | 0.173200E+13 | 0.226059E+12 | 0.272038E+12 | 0.408117E+11 | 0.00 | 0.192723E+12 | 0.681979E+11 | 0.267840E+12 | 0.834377E+10 | 0.514970E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.112701E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.678240E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.328634E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.597440E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.108612E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 5599.44 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.109762E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.263361E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.227669E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.890736E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.125344E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.459399E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.125344E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 325713.14 | 02-JAN-08:09 | 40855.88 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 233439.18 | 02-JAN-08:20 | 109040.67 | 02-JAN-06:19 | 21005.68 | 10-JAN-07:40 | 0.00 | 01-JAN-00:10 |
February | 325713.14 | 01-FEB-08:09 | 40855.88 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 233439.18 | 01-FEB-08:20 | 104726.02 | 15-FEB-13:00 | 20997.37 | 06-FEB-07:49 | 0.00 | 01-FEB-00:10 |
March | 325713.14 | 01-MAR-08:09 | 40855.88 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 233439.18 | 01-MAR-08:20 | 192217.86 | 16-MAR-10:50 | 20967.78 | 16-MAR-06:30 | 0.00 | 01-MAR-00:10 |
April | 289101.35 | 04-APR-07:10 | 40855.88 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 233419.60 | 04-APR-07:19 | 245993.87 | 21-APR-15:50 | 20978.61 | 20-APR-13:00 | 0.00 | 01-APR-00:10 |
May | 280450.63 | 01-MAY-07:10 | 27558.46 | 01-MAY-21:10 | 423497.50 | 01-MAY-07:10 | 233414.99 | 01-MAY-07:19 | 260638.84 | 31-MAY-14:39 | 38531.78 | 31-MAY-15:20 | 0.00 | 01-MAY-00:10 |
June | 280450.63 | 01-JUN-07:10 | 27558.46 | 01-JUN-22:49 | 541788.89 | 01-JUN-07:10 | 233414.99 | 01-JUN-07:19 | 279655.46 | 30-JUN-12:09 | 41468.78 | 20-JUN-15:09 | 0.00 | 01-JUN-00:10 |
July | 281231.72 | 25-JUL-07:10 | 27558.46 | 11-JUL-22:00 | 660080.29 | 03-JUL-07:10 | 233415.40 | 25-JUL-07:19 | 288620.98 | 12-JUL-12:09 | 42500.93 | 19-JUL-12:50 | 0.00 | 01-JUL-00:10 |
August | 282443.77 | 18-AUG-15:20 | 40855.88 | 24-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 233415.40 | 07-AUG-07:19 | 291366.09 | 10-AUG-15:50 | 42202.43 | 11-AUG-15:39 | 0.00 | 01-AUG-00:10 |
September | 323537.93 | 28-SEP-07:10 | 40855.88 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 233438.02 | 28-SEP-07:19 | 193595.98 | 08-SEP-15:30 | 21015.57 | 07-SEP-15:00 | 0.00 | 01-SEP-00:10 |
October | 325713.14 | 02-OCT-07:10 | 40855.88 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 233439.18 | 02-OCT-07:19 | 153439.03 | 13-OCT-12:09 | 20981.31 | 30-OCT-06:49 | 0.00 | 01-OCT-00:10 |
November | 325713.14 | 01-NOV-07:10 | 40855.88 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 233439.18 | 01-NOV-07:19 | 99197.18 | 27-NOV-05:10 | 21055.04 | 13-NOV-07:49 | 0.00 | 01-NOV-00:10 |
December | 325713.14 | 01-DEC-08:09 | 40855.88 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 233439.18 | 01-DEC-08:20 | 99291.80 | 04-DEC-05:10 | 21142.60 | 04-DEC-07:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 280450.63 | 27558.46 | 423497.50 | 233414.99 | 99197.18 | 20967.78 | 0.00 | |||||||
Maximum of Months | 325713.14 | 40855.88 | 778371.69 | 233439.18 | 291366.09 | 42500.93 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 4170.52 | 27-JAN-16:10 | 606.83 | 30-JAN-17:00 | 53884.86 | 19-JAN-05:10 | 6524.59 | 02-JAN-08:20 | 63524.80 | 20-JAN-12:30 | 0.00 |
February | 13337.04 | 10-FEB-16:10 | 2852.46 | 08-FEB-15:00 | 100000.00 | 08-FEB-13:50 | 6524.59 | 01-FEB-07:10 | 63524.73 | 22-FEB-12:30 | 0.00 |
March | 22326.71 | 31-MAR-23:30 | 3282.41 | 22-MAR-11:30 | 100000.00 | 01-MAR-22:10 | 6524.59 | 01-MAR-07:19 | 63524.97 | 14-MAR-11:39 | 0.00 |
April | 53419.16 | 22-APR-13:00 | 8991.16 | 22-APR-13:00 | 100000.00 | 01-APR-04:30 | 6524.59 | 01-APR-06:10 | 63524.99 | 03-APR-11:39 | 0.00 |
May | 151272.15 | 31-MAY-15:30 | 50915.36 | 31-MAY-15:09 | 100000.00 | 06-MAY-16:10 | 5613.48 | 27-MAY-06:40 | 63448.56 | 09-MAY-11:50 | 0.00 |
June | 288036.21 | 30-JUN-12:30 | 81077.84 | 29-JUN-10:50 | 100000.00 | 01-JUN-21:10 | 5613.48 | 20-JUN-15:30 | 62085.42 | 01-JUN-11:50 | 0.00 |
July | 309252.87 | 21-JUL-14:39 | 81077.84 | 03-JUL-14:00 | 100000.00 | 12-JUL-21:00 | 5613.48 | 11-JUL-12:50 | 59146.47 | 03-JUL-11:39 | 0.00 |
August | 342267.28 | 11-AUG-15:20 | 81077.84 | 23-AUG-14:39 | 100000.00 | 10-AUG-21:10 | 5613.48 | 11-AUG-15:39 | 57697.31 | 04-AUG-11:20 | 0.00 |
September | 40056.96 | 07-SEP-15:00 | 5882.98 | 07-SEP-15:00 | 100000.00 | 10-SEP-13:39 | 5613.48 | 15-SEP-06:10 | 57199.21 | 28-SEP-11:50 | 0.00 |
October | 15413.80 | 31-OCT-23:10 | 2751.11 | 01-OCT-14:00 | 100000.00 | 01-OCT-14:50 | 6524.59 | 14-OCT-06:10 | 58681.92 | 31-OCT-11:39 | 0.00 |
November | 18411.53 | 08-NOV-16:40 | 1268.43 | 03-NOV-16:49 | 100000.00 | 01-NOV-03:30 | 6524.59 | 01-NOV-06:10 | 60917.01 | 30-NOV-12:00 | 0.00 |
December | 21863.29 | 27-DEC-15:20 | 1999.39 | 26-DEC-13:39 | 100000.00 | 01-DEC-01:30 | 6524.59 | 01-DEC-07:10 | 63523.83 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 4170.52 | 606.83 | 53884.86 | 5613.48 | 57199.21 | 0.00 | |||||
Maximum of Months | 342267.28 | 81077.84 | 100000.00 | 6524.59 | 63524.99 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1239526.66 | 23-JAN-16:40 | 325713.14 | 423497.50 | 40855.88 | 233326.38 | 88496.67 | 20919.61 | 0.00 | 3347.33 | 99.00 |
February | 1398727.12 | 01-FEB-16:00 | 325713.14 | 541788.89 | 40855.88 | 233326.38 | 88325.93 | 20920.04 | 0.00 | 9590.31 | 334.36 |
March | 1561774.02 | 16-MAR-10:50 | 280450.63 | 660080.29 | 0.00 | 233151.79 | 192217.86 | 20929.11 | 0.00 | 16636.91 | 589.86 |
April | 1752316.77 | 21-APR-15:50 | 280450.63 | 778371.69 | 0.00 | 233302.19 | 245993.87 | 20921.10 | 0.00 | 38562.29 | 5925.49 |
May | 1580894.26 | 31-MAY-15:30 | 280450.63 | 423497.50 | 0.00 | 233302.19 | 256202.06 | 38446.04 | 0.00 | 151272.15 | 50102.85 |
June | 1806928.37 | 21-JUN-15:39 | 280450.63 | 541788.89 | 0.00 | 233302.19 | 267562.72 | 41154.09 | 0.00 | 246271.62 | 51152.22 |
July | 1980091.60 | 21-JUL-14:30 | 280450.63 | 660080.29 | 0.00 | 233151.79 | 266906.62 | 41788.77 | 0.00 | 309068.62 | 50748.72 |
August | 2092003.05 | 11-AUG-15:20 | 280450.63 | 778371.69 | 0.00 | 233302.19 | 266753.76 | 41241.27 | 0.00 | 342267.28 | 50651.96 |
September | 1331967.33 | 07-SEP-15:50 | 280450.63 | 423497.50 | 0.00 | 233302.19 | 185696.79 | 21010.41 | 0.00 | 38745.22 | 5346.87 |
October | 1385042.84 | 31-OCT-07:00 | 325713.14 | 541788.89 | 40855.88 | 233439.18 | 88541.16 | 20927.50 | 0.00 | 8768.12 | 262.37 |
November | 1539916.46 | 22-NOV-16:30 | 325713.14 | 660080.29 | 40855.88 | 233326.38 | 89207.48 | 20919.28 | 0.00 | 16022.38 | 569.96 |
December | 1667199.04 | 27-DEC-11:20 | 325713.14 | 778371.69 | 40855.88 | 233175.98 | 89320.84 | 20929.33 | 0.00 | 19589.90 | 570.03 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1239526.66 | 280450.63 | 423497.50 | 0.00 | 233151.79 | 88325.93 | 20919.28 | 0.00 | 3347.33 | 99.00 | |
Maximum of Months | 2092003.05 | 325713.14 | 778371.69 | 40855.88 | 233439.18 | 267562.72 | 41788.77 | 0.00 | 342267.28 | 51152.22 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 2336776.04 | 12-JAN-07:30 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 2541901.65 | 27-FEB-07:30 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 1912426.19 | 01-MAR-07:30 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 1354590.05 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 267377.23 | 27-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 6.09 | 01-JUN-18:30 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 336070.78 | 31-AUG-06:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 532633.07 | 29-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 1402144.62 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 2236478.09 | 27-NOV-07:19 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 2073031.21 | 15-DEC-07:40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 2541901.65 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 27.00 | 25.26 | 27.00 | 25.26 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 49.83 | 25.78 | 39.83 | 25.79 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 85.00 | 26.23 | 56.00 | 26.26 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 432.67 | 29.13 | 295.67 | 29.16 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 29.94 | 508.00 | 30.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 720.00 | 30.25 | 496.00 | 30.30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 30.49 | 497.00 | 30.54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 30.73 | 514.00 | 30.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 720.00 | 30.25 | 485.00 | 30.29 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 380.50 | 29.35 | 250.00 | 29.40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 51.83 | 25.92 | 26.83 | 25.92 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 64.83 | 25.81 | 38.83 | 25.81 |
Annual Sum or Average | 0.00 | 0.00 | 4763.67 | 29.89 | 3234.17 | 29.93 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 27.00 | 25.26 | 26.83 | 25.26 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 30.73 | 514.00 | 30.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.63 | 0.00 | 25.63 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 26.31 | 0.33 | 26.37 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 26.10 | 0.33 | 26.16 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 26.64 | 1.33 | 26.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 26.72 | 0.50 | 26.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 26.57 | 1.67 | 26.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 26.46 | 1.50 | 26.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 26.34 | 1.17 | 26.57 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 60.33 | 26.51 | 6.83 | 26.56 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 26.72 | 1.67 | 26.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 19.37 | 1.67 | 19.56 | 0.00 | 19.56 | 0.00 | 19.56 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.50 | 19.35 | 1.67 | 19.54 | 0.00 | 19.54 | 0.00 | 19.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.33 | 19.37 | 1.67 | 19.56 | 0.00 | 19.56 | 0.00 | 19.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.83 | 18.55 | 1.67 | 18.79 | 0.00 | 18.79 | 0.00 | 18.79 |
February | 6.33 | 18.64 | 1.33 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 |
March | 2.50 | 19.10 | 0.50 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
April | 0.33 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2.00 | 18.69 | 0.33 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 |
November | 7.83 | 18.63 | 1.50 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
December | 8.00 | 18.76 | 1.50 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
Annual Sum or Average | 35.83 | 18.68 | 6.83 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.83 | 19.27 | 1.67 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
February | 1.00 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
March | 0.17 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 26.04 | 0.00 | 26.04 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 26.89 | 3.33 | 26.86 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 27.04 | 9.67 | 27.11 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 26.46 | 1.50 | 26.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
December | 0.50 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
Annual Sum or Average | 4.50 | 19.09 | 0.00 | 19.09 | 35.67 | 25.99 | 14.50 | 26.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 19.39 | 0.00 | 19.39 | 17.17 | 27.04 | 9.67 | 27.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
February | 1.33 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
March | 0.33 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.20 | 2.33 | 28.20 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.93 | 7.67 | 28.15 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.31 | 4.50 | 27.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.70 | 9.17 | 27.91 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.75 | 2.67 | 27.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.24 | 3.67 | 28.24 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
December | 2.83 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
Annual Sum or Average | 8.50 | 19.13 | 0.00 | 19.13 | 41.00 | 26.27 | 30.00 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 19.31 | 0.00 | 19.31 | 13.17 | 28.24 | 9.17 | 28.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.67 | 18.67 | 0.00 | 18.67 | 0.00 | 18.67 | 0.00 | 18.67 |
February | 1.67 | 18.81 | 0.00 | 18.81 | 0.00 | 18.81 | 0.00 | 18.81 |
March | 0.50 | 19.30 | 0.00 | 19.30 | 2.50 | 26.57 | 2.50 | 27.23 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.32 | 5.83 | 28.33 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 28.57 | 7.33 | 28.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.32 | 5.17 | 28.36 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 28.29 | 7.50 | 28.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.51 | 5.00 | 28.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.06 | 2.67 | 28.06 |
October | 0.17 | 19.31 | 0.00 | 19.31 | 0.50 | 25.47 | 0.50 | 26.35 |
November | 1.17 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
December | 3.17 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
Annual Sum or Average | 11.33 | 18.89 | 0.00 | 18.89 | 39.50 | 26.24 | 36.50 | 27.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 0.00 | 18.67 |
Maximum of Months | 4.67 | 19.31 | 0.00 | 19.31 | 8.67 | 28.57 | 7.50 | 28.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
February | 0.17 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.79 | 0.33 | 27.80 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 28.41 | 3.17 | 28.44 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 28.55 | 3.50 | 28.54 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.93 | 2.50 | 28.07 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 27.65 | 6.33 | 27.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.46 | 4.17 | 27.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.94 | 0.67 | 27.94 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.67 | 19.20 | 0.00 | 19.20 | 56.67 | 27.67 | 20.67 | 27.82 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 19.30 | 0.00 | 19.30 | 17.50 | 28.55 | 6.33 | 28.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 48.33 | 16.71 | 18.00 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 |
February | 28.33 | 17.26 | 9.67 | 17.43 | 0.00 | 17.43 | 0.00 | 17.43 |
March | 9.50 | 18.62 | 1.50 | 18.83 | 0.00 | 18.83 | 0.00 | 18.83 |
April | 1.67 | 18.95 | 0.17 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.82 | 0.00 | 25.82 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 26.25 | 0.17 | 26.19 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 26.04 | 0.17 | 25.97 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3.50 | 18.46 | 0.33 | 18.63 | 0.00 | 18.63 | 0.00 | 18.63 |
November | 23.83 | 17.72 | 6.83 | 17.94 | 0.00 | 17.94 | 0.00 | 17.94 |
December | 32.83 | 17.78 | 10.17 | 17.99 | 0.00 | 17.99 | 0.00 | 17.99 |
Annual Sum or Average | 148.00 | 17.40 | 46.67 | 17.54 | 6.67 | 17.83 | 0.33 | 17.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.33 | 18.95 | 18.00 | 19.08 | 4.33 | 26.25 | 0.17 | 26.19 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 37.00 | 15.60 | 10.33 | 15.41 | 0.00 | 15.41 | 0.00 | 15.41 |
February | 15.50 | 16.41 | 1.83 | 16.29 | 0.00 | 16.29 | 0.00 | 16.29 |
March | 6.50 | 18.27 | 0.00 | 18.27 | 0.00 | 18.27 | 0.00 | 18.27 |
April | 1.00 | 18.67 | 0.00 | 18.67 | 1.00 | 23.37 | 1.00 | 24.94 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.79 | 4.00 | 28.85 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.11 | 2.83 | 27.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.80 | 5.83 | 28.04 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.92 | 1.00 | 27.92 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.06 | 1.50 | 28.06 |
October | 2.67 | 18.27 | 0.00 | 18.27 | 0.00 | 18.27 | 0.00 | 18.27 |
November | 16.67 | 16.62 | 1.83 | 16.46 | 0.00 | 16.46 | 0.00 | 16.46 |
December | 24.67 | 16.17 | 4.33 | 15.98 | 0.00 | 15.98 | 0.00 | 15.98 |
Annual Sum or Average | 104.00 | 16.28 | 18.33 | 16.07 | 21.33 | 17.82 | 16.17 | 18.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.41 | 0.00 | 15.41 |
Maximum of Months | 37.00 | 18.67 | 10.33 | 18.67 | 7.83 | 28.79 | 5.83 | 28.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 28.17 | 15.87 | 6.17 | 15.67 | 0.00 | 15.67 | 0.00 | 15.67 |
February | 9.83 | 17.21 | 1.33 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 |
March | 5.17 | 18.68 | 0.00 | 18.68 | 2.17 | 21.53 | 2.17 | 23.07 |
April | 0.33 | 19.11 | 0.00 | 19.11 | 5.17 | 27.87 | 4.83 | 28.17 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 28.59 | 6.50 | 28.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.28 | 4.17 | 28.31 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.39 | 6.00 | 28.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.54 | 3.83 | 28.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.89 | 2.33 | 27.89 |
October | 2.00 | 18.58 | 0.00 | 18.58 | 0.33 | 19.83 | 0.33 | 20.78 |
November | 10.50 | 17.52 | 0.00 | 17.52 | 0.00 | 17.52 | 0.00 | 17.52 |
December | 19.83 | 16.54 | 3.00 | 16.33 | 0.00 | 16.33 | 0.00 | 16.33 |
Annual Sum or Average | 75.83 | 16.73 | 10.50 | 16.50 | 32.33 | 19.74 | 30.17 | 21.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 0.00 | 15.67 |
Maximum of Months | 28.17 | 19.11 | 6.17 | 19.11 | 7.17 | 28.59 | 6.50 | 28.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 26.33 | 15.98 | 7.00 | 15.73 | 0.00 | 15.73 | 0.00 | 15.73 |
February | 10.33 | 17.17 | 1.50 | 16.96 | 0.00 | 16.96 | 0.00 | 16.96 |
March | 5.50 | 18.55 | 0.00 | 18.55 | 0.00 | 18.55 | 0.00 | 18.55 |
April | 0.50 | 19.26 | 0.00 | 19.26 | 2.17 | 26.61 | 0.67 | 26.99 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 28.56 | 2.00 | 28.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.55 | 1.67 | 28.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.17 | 1.83 | 28.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.54 | 0.83 | 28.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.94 | 0.33 | 27.94 |
October | 2.00 | 18.48 | 0.00 | 18.48 | 0.00 | 18.48 | 0.00 | 18.48 |
November | 8.17 | 18.21 | 0.00 | 18.21 | 0.00 | 18.21 | 0.00 | 18.21 |
December | 13.17 | 17.46 | 0.00 | 17.46 | 0.00 | 17.46 | 0.00 | 17.46 |
Annual Sum or Average | 66.00 | 17.05 | 8.50 | 16.81 | 23.67 | 19.61 | 7.33 | 20.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.73 | 0.00 | 15.73 |
Maximum of Months | 26.33 | 19.26 | 7.00 | 19.26 | 7.17 | 28.56 | 2.00 | 28.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 110.50 | 16.70 | 48.83 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 |
February | 89.17 | 16.70 | 38.50 | 17.02 | 0.00 | 17.02 | 0.00 | 17.02 |
March | 56.83 | 17.67 | 20.83 | 18.11 | 0.00 | 18.11 | 0.00 | 18.11 |
April | 12.67 | 17.50 | 3.50 | 17.69 | 0.00 | 17.69 | 0.00 | 17.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.65 | 0.00 | 25.65 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 25.98 | 0.00 | 25.98 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.94 | 0.00 | 25.94 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1.17 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
October | 31.83 | 16.96 | 11.33 | 17.09 | 0.00 | 17.09 | 0.00 | 17.09 |
November | 98.33 | 16.76 | 44.33 | 17.02 | 0.00 | 17.02 | 0.00 | 17.02 |
December | 119.00 | 16.96 | 51.50 | 17.32 | 0.00 | 17.32 | 0.00 | 17.32 |
Annual Sum or Average | 519.50 | 16.92 | 218.83 | 17.23 | 4.17 | 17.27 | 0.00 | 17.27 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 119.00 | 19.06 | 51.50 | 19.06 | 2.67 | 25.98 | 0.00 | 25.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 60.00 | 14.81 | 16.67 | 14.68 | 0.00 | 14.68 | 0.00 | 14.68 |
February | 47.00 | 15.13 | 10.83 | 15.06 | 0.00 | 15.06 | 0.00 | 15.06 |
March | 22.33 | 16.16 | 1.00 | 16.11 | 0.00 | 16.11 | 0.00 | 16.11 |
April | 5.83 | 16.96 | 0.33 | 16.85 | 0.67 | 17.90 | 0.67 | 18.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.54 | 4.00 | 28.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.19 | 2.67 | 27.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.02 | 5.83 | 28.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.86 | 0.83 | 27.86 |
September | 1.17 | 19.11 | 0.00 | 19.11 | 0.83 | 22.79 | 0.83 | 24.31 |
October | 18.33 | 16.08 | 2.67 | 15.91 | 0.00 | 15.91 | 0.00 | 15.91 |
November | 58.50 | 15.10 | 18.00 | 15.00 | 0.00 | 15.00 | 0.00 | 15.00 |
December | 66.50 | 14.97 | 16.33 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
Annual Sum or Average | 279.67 | 15.22 | 65.83 | 15.09 | 18.00 | 15.72 | 14.83 | 16.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.68 | 0.00 | 14.68 |
Maximum of Months | 66.50 | 19.11 | 18.00 | 19.11 | 6.83 | 28.54 | 5.83 | 28.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 55.33 | 14.92 | 14.33 | 14.79 | 0.00 | 14.79 | 0.00 | 14.79 |
February | 36.50 | 15.43 | 5.17 | 15.36 | 0.00 | 15.36 | 0.00 | 15.36 |
March | 15.00 | 16.91 | 0.67 | 16.82 | 0.17 | 16.93 | 0.17 | 17.04 |
April | 2.83 | 18.34 | 0.00 | 18.34 | 3.00 | 23.49 | 3.00 | 25.14 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.55 | 5.83 | 28.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.25 | 4.00 | 28.28 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.49 | 5.67 | 28.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.36 | 3.83 | 28.39 |
September | 0.67 | 19.02 | 0.00 | 19.02 | 0.50 | 22.94 | 0.50 | 24.51 |
October | 15.00 | 16.36 | 2.17 | 16.16 | 0.00 | 16.16 | 0.00 | 16.16 |
November | 46.83 | 15.26 | 12.33 | 15.18 | 0.00 | 15.18 | 0.00 | 15.18 |
December | 60.83 | 15.02 | 15.33 | 14.93 | 0.00 | 14.93 | 0.00 | 14.93 |
Annual Sum or Average | 233.00 | 15.37 | 50.00 | 15.23 | 24.67 | 16.29 | 23.00 | 17.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.79 | 0.00 | 14.79 |
Maximum of Months | 60.83 | 19.02 | 15.33 | 19.02 | 6.33 | 28.55 | 5.83 | 28.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 54.17 | 14.95 | 15.17 | 14.81 | 0.00 | 14.81 | 0.00 | 14.81 |
February | 38.17 | 15.44 | 9.00 | 15.32 | 0.00 | 15.32 | 0.00 | 15.32 |
March | 14.33 | 17.06 | 0.17 | 17.04 | 0.00 | 17.04 | 0.00 | 17.04 |
April | 2.67 | 18.22 | 0.00 | 18.22 | 1.67 | 22.04 | 0.67 | 22.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.47 | 2.33 | 28.41 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.55 | 1.50 | 28.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.18 | 2.00 | 28.20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.49 | 0.83 | 28.54 |
September | 0.67 | 19.14 | 0.00 | 19.14 | 0.33 | 22.06 | 0.17 | 22.91 |
October | 12.67 | 16.65 | 1.17 | 16.50 | 0.00 | 16.50 | 0.00 | 16.50 |
November | 39.50 | 15.51 | 9.17 | 15.41 | 0.00 | 15.41 | 0.00 | 15.41 |
December | 46.00 | 15.37 | 13.17 | 15.26 | 0.00 | 15.26 | 0.00 | 15.26 |
Annual Sum or Average | 208.17 | 15.54 | 47.83 | 15.39 | 22.50 | 16.44 | 7.50 | 16.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.81 | 0.00 | 14.81 |
Maximum of Months | 54.17 | 19.14 | 15.17 | 19.14 | 6.67 | 28.55 | 2.33 | 28.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 422.67 | 24.16 | 0.00 | 24.16 | 0.00 | 24.16 |
February | 320.17 | 24.15 | 15.83 | 24.25 | 3.50 | 24.27 |
March | 318.00 | 24.12 | 60.17 | 24.49 | 7.33 | 24.54 |
April | 345.67 | 28.22 | 326.67 | 28.57 | 265.17 | 28.83 |
May | 508.00 | 30.07 | 508.00 | 30.07 | 508.00 | 30.07 |
June | 496.00 | 30.37 | 496.00 | 30.37 | 496.00 | 30.37 |
July | 497.00 | 30.61 | 497.00 | 30.61 | 497.00 | 30.61 |
August | 514.00 | 30.84 | 514.00 | 30.84 | 514.00 | 30.84 |
September | 485.00 | 30.35 | 485.00 | 30.35 | 485.00 | 30.35 |
October | 324.50 | 28.04 | 287.00 | 28.52 | 225.17 | 28.87 |
November | 329.83 | 24.06 | 17.50 | 24.17 | 0.00 | 24.17 |
December | 327.33 | 24.06 | 34.67 | 24.29 | 0.00 | 24.29 |
Annual Sum or Average | 4888.17 | 27.91 | 3241.83 | 28.75 | 3001.17 | 29.17 |
Minimum of Months | 318.00 | 24.06 | 0.00 | 24.16 | 0.00 | 24.16 |
Maximum of Months | 514.00 | 30.84 | 514.00 | 30.84 | 514.00 | 30.84 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 23.40 | 12.00 | 23.37 | 12.00 | 23.33 |
February | 419.17 | 23.78 | 0.00 | 23.78 | 0.00 | 23.78 |
March | 374.83 | 23.93 | 8.00 | 23.97 | 0.00 | 23.97 |
April | 131.33 | 24.00 | 58.33 | 24.68 | 0.00 | 24.68 |
May | 0.00 | 0.00 | 109.83 | 26.02 | 0.00 | 26.02 |
June | 0.33 | 27.22 | 369.83 | 24.56 | 0.33 | 24.56 |
July | 1.33 | 27.15 | 493.00 | 24.53 | 1.33 | 24.53 |
August | 1.17 | 26.99 | 459.33 | 24.50 | 1.17 | 24.51 |
September | 0.00 | 0.00 | 191.33 | 25.27 | 0.00 | 25.27 |
October | 183.00 | 23.93 | 73.00 | 24.58 | 0.00 | 24.58 |
November | 440.50 | 23.90 | 0.00 | 23.90 | 0.00 | 23.90 |
December | 458.67 | 23.85 | 6.00 | 23.87 | 0.00 | 23.87 |
Annual Sum or Average | 2512.33 | 23.79 | 1780.67 | 24.21 | 14.83 | 24.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 23.37 | 0.00 | 23.33 |
Maximum of Months | 502.00 | 27.22 | 493.00 | 26.02 | 12.00 | 26.02 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.35 | 183.83 | 21.04 | 183.83 | 20.86 |
February | 454.00 | 22.04 | 105.00 | 21.78 | 105.00 | 21.60 |
March | 514.00 | 22.98 | 7.67 | 22.95 | 7.67 | 22.92 |
April | 422.83 | 23.56 | 0.00 | 23.56 | 0.00 | 23.56 |
May | 231.67 | 23.84 | 4.67 | 23.87 | 0.00 | 23.87 |
June | 27.67 | 23.80 | 125.50 | 24.45 | 0.00 | 24.45 |
July | 2.33 | 23.62 | 283.67 | 24.38 | 0.00 | 24.38 |
August | 48.17 | 23.78 | 186.50 | 24.33 | 0.00 | 24.33 |
September | 269.33 | 23.63 | 17.17 | 23.74 | 0.00 | 23.74 |
October | 481.67 | 23.13 | 5.83 | 23.11 | 5.83 | 23.08 |
November | 489.00 | 21.93 | 92.83 | 21.73 | 92.83 | 21.59 |
December | 497.00 | 21.47 | 197.17 | 21.24 | 197.17 | 21.10 |
Annual Sum or Average | 3939.67 | 22.54 | 1209.83 | 22.54 | 592.33 | 22.33 |
Minimum of Months | 2.33 | 21.35 | 0.00 | 21.04 | 0.00 | 20.86 |
Maximum of Months | 514.00 | 23.84 | 283.67 | 24.45 | 197.17 | 24.45 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.29 | 434.33 | 20.21 | 434.33 | 20.18 |
February | 454.00 | 20.59 | 299.00 | 20.37 | 299.00 | 20.28 |
March | 514.00 | 21.33 | 225.00 | 21.05 | 225.00 | 20.90 |
April | 473.50 | 22.50 | 82.50 | 22.17 | 82.50 | 21.92 |
May | 318.17 | 23.45 | 1.17 | 23.46 | 0.00 | 23.46 |
June | 82.83 | 23.70 | 97.00 | 24.08 | 0.00 | 24.08 |
July | 23.17 | 23.44 | 253.83 | 24.29 | 0.00 | 24.29 |
August | 128.83 | 23.41 | 141.83 | 23.91 | 0.00 | 23.91 |
September | 421.50 | 22.74 | 10.17 | 22.70 | 10.17 | 22.66 |
October | 502.00 | 21.34 | 197.17 | 21.03 | 197.17 | 20.86 |
November | 489.00 | 20.40 | 400.83 | 20.30 | 400.83 | 20.26 |
December | 497.00 | 20.28 | 471.17 | 20.25 | 471.17 | 20.24 |
Annual Sum or Average | 4406.00 | 21.44 | 2614.00 | 21.27 | 2120.17 | 21.02 |
Minimum of Months | 23.17 | 20.28 | 1.17 | 20.21 | 0.00 | 20.18 |
Maximum of Months | 514.00 | 23.70 | 471.17 | 24.29 | 471.17 | 24.29 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.53 | 467.67 | 20.50 | 467.67 | 20.49 |
February | 454.00 | 20.93 | 296.17 | 20.78 | 296.17 | 20.72 |
March | 514.00 | 21.92 | 145.50 | 21.70 | 145.50 | 21.56 |
April | 333.83 | 23.21 | 28.83 | 23.23 | 13.83 | 23.15 |
May | 29.17 | 23.99 | 85.67 | 25.35 | 0.00 | 25.35 |
June | 3.00 | 27.34 | 397.00 | 24.57 | 3.00 | 24.59 |
July | 34.50 | 26.88 | 491.33 | 24.74 | 34.50 | 24.87 |
August | 22.00 | 24.76 | 405.67 | 24.48 | 6.00 | 24.52 |
September | 173.67 | 23.73 | 58.17 | 24.12 | 0.00 | 24.12 |
October | 432.17 | 22.41 | 89.33 | 22.15 | 87.83 | 21.96 |
November | 489.00 | 20.87 | 374.50 | 20.80 | 374.50 | 20.78 |
December | 497.00 | 20.81 | 433.67 | 20.77 | 433.67 | 20.76 |
Annual Sum or Average | 3484.33 | 21.65 | 3273.50 | 22.03 | 1862.67 | 21.76 |
Minimum of Months | 3.00 | 20.53 | 28.83 | 20.50 | 0.00 | 20.49 |
Maximum of Months | 514.00 | 27.34 | 491.33 | 25.35 | 467.67 | 25.35 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.45 | 479.17 | 20.43 | 479.17 | 20.43 |
February | 454.00 | 20.96 | 287.67 | 20.82 | 287.67 | 20.75 |
March | 451.17 | 21.91 | 121.33 | 21.76 | 110.33 | 21.62 |
April | 255.17 | 22.82 | 92.67 | 23.23 | 17.67 | 23.21 |
May | 49.00 | 25.13 | 274.50 | 24.79 | 19.17 | 24.93 |
June | 19.67 | 26.40 | 430.83 | 24.50 | 19.67 | 24.58 |
July | 49.00 | 26.19 | 490.00 | 24.65 | 49.00 | 24.78 |
August | 24.33 | 25.00 | 438.17 | 24.38 | 11.50 | 24.43 |
September | 162.83 | 23.49 | 137.83 | 24.12 | 11.67 | 24.23 |
October | 411.33 | 22.01 | 98.50 | 21.89 | 84.67 | 21.73 |
November | 489.00 | 20.68 | 457.50 | 20.67 | 457.50 | 20.67 |
December | 497.00 | 20.62 | 482.00 | 20.61 | 482.00 | 20.61 |
Annual Sum or Average | 3364.50 | 21.51 | 3790.17 | 22.06 | 2030.00 | 21.81 |
Minimum of Months | 19.67 | 20.45 | 92.67 | 20.43 | 11.50 | 20.43 |
Maximum of Months | 502.00 | 26.40 | 490.00 | 24.79 | 482.00 | 24.93 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.40 | 456.50 | 20.34 | 456.50 | 20.31 |
February | 418.17 | 21.18 | 240.67 | 20.99 | 233.00 | 20.87 |
March | 392.00 | 21.89 | 167.17 | 22.03 | 105.00 | 21.89 |
April | 224.33 | 22.93 | 176.17 | 23.52 | 34.17 | 23.54 |
May | 125.33 | 24.20 | 233.50 | 24.53 | 26.50 | 24.72 |
June | 27.50 | 26.22 | 392.50 | 24.56 | 21.67 | 24.67 |
July | 31.00 | 26.91 | 468.17 | 24.63 | 29.50 | 24.77 |
August | 43.83 | 25.21 | 409.17 | 24.49 | 23.83 | 24.61 |
September | 207.00 | 23.13 | 159.50 | 23.75 | 6.83 | 23.81 |
October | 402.17 | 21.94 | 118.33 | 21.92 | 83.67 | 21.75 |
November | 484.67 | 20.82 | 390.33 | 20.70 | 390.33 | 20.65 |
December | 497.00 | 20.47 | 491.33 | 20.47 | 491.33 | 20.47 |
Annual Sum or Average | 3355.00 | 21.58 | 3703.33 | 22.11 | 1902.33 | 21.85 |
Minimum of Months | 27.50 | 20.40 | 118.33 | 20.34 | 6.83 | 20.31 |
Maximum of Months | 502.00 | 26.91 | 491.33 | 24.63 | 491.33 | 24.77 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.74 | 384.00 | 20.70 | 384.00 | 20.68 |
February | 454.00 | 21.41 | 161.33 | 21.26 | 161.33 | 21.17 |
March | 434.33 | 22.57 | 35.50 | 22.56 | 23.00 | 22.49 |
April | 143.67 | 23.79 | 155.83 | 24.40 | 13.33 | 24.52 |
May | 92.00 | 23.89 | 173.67 | 24.55 | 13.00 | 24.67 |
June | 14.50 | 27.01 | 438.83 | 24.55 | 14.50 | 24.62 |
July | 34.50 | 26.50 | 496.17 | 24.66 | 34.50 | 24.78 |
August | 23.00 | 26.32 | 471.00 | 24.55 | 18.67 | 24.64 |
September | 242.00 | 23.07 | 88.83 | 23.49 | 3.50 | 23.53 |
October | 420.83 | 22.41 | 17.83 | 22.43 | 10.00 | 22.40 |
November | 489.00 | 21.52 | 108.67 | 21.43 | 108.67 | 21.36 |
December | 497.00 | 21.48 | 174.67 | 21.36 | 174.67 | 21.29 |
Annual Sum or Average | 3346.83 | 22.01 | 2706.33 | 22.63 | 959.17 | 22.46 |
Minimum of Months | 14.50 | 20.74 | 17.83 | 20.70 | 3.50 | 20.68 |
Maximum of Months | 502.00 | 27.01 | 496.17 | 24.66 | 384.00 | 24.78 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.91 | 502.00 | 19.91 | 502.00 | 19.91 |
February | 454.00 | 20.05 | 446.17 | 20.04 | 446.17 | 20.03 |
March | 514.00 | 20.64 | 420.50 | 20.54 | 420.50 | 20.51 |
April | 485.00 | 22.07 | 136.33 | 21.69 | 136.33 | 21.45 |
May | 291.67 | 23.68 | 0.67 | 23.68 | 0.00 | 23.68 |
June | 9.00 | 23.78 | 237.50 | 24.38 | 0.00 | 24.38 |
July | 3.00 | 23.88 | 389.17 | 24.43 | 0.17 | 24.43 |
August | 128.33 | 23.30 | 141.50 | 23.83 | 0.00 | 23.83 |
September | 458.50 | 22.43 | 31.17 | 22.34 | 31.17 | 22.25 |
October | 502.00 | 20.81 | 308.33 | 20.63 | 308.33 | 20.55 |
November | 489.00 | 19.95 | 489.00 | 19.95 | 489.00 | 19.95 |
December | 497.00 | 19.89 | 497.00 | 19.89 | 497.00 | 19.89 |
Annual Sum or Average | 4333.50 | 20.99 | 3599.33 | 21.00 | 2830.67 | 20.76 |
Minimum of Months | 3.00 | 19.89 | 0.67 | 19.89 | 0.00 | 19.89 |
Maximum of Months | 514.00 | 23.88 | 502.00 | 24.43 | 502.00 | 24.43 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.74 | 427.00 | 19.74 | 427.00 | 19.74 |
February | 385.00 | 20.04 | 369.00 | 20.01 | 369.00 | 20.00 |
March | 416.50 | 21.03 | 244.67 | 20.82 | 244.17 | 20.72 |
April | 313.00 | 22.07 | 98.17 | 22.06 | 69.17 | 21.87 |
May | 163.83 | 23.50 | 137.17 | 24.09 | 12.50 | 24.22 |
June | 60.83 | 23.90 | 253.67 | 24.30 | 11.33 | 24.37 |
July | 52.50 | 24.98 | 334.83 | 24.63 | 29.50 | 24.76 |
August | 119.67 | 23.07 | 222.33 | 23.91 | 3.67 | 23.95 |
September | 330.83 | 22.17 | 58.50 | 22.46 | 20.83 | 22.45 |
October | 422.83 | 20.90 | 231.50 | 20.70 | 230.67 | 20.61 |
November | 417.00 | 19.78 | 417.00 | 19.78 | 417.00 | 19.78 |
December | 422.00 | 19.68 | 422.00 | 19.68 | 422.00 | 19.68 |
Annual Sum or Average | 3531.00 | 20.93 | 3215.83 | 21.16 | 2256.83 | 20.91 |
Minimum of Months | 52.50 | 19.68 | 58.50 | 19.68 | 3.67 | 19.68 |
Maximum of Months | 427.00 | 24.98 | 427.00 | 24.63 | 427.00 | 24.76 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.02 | 481.83 | 19.98 | 481.83 | 19.97 |
February | 429.50 | 20.71 | 323.33 | 20.54 | 320.17 | 20.46 |
March | 401.50 | 21.31 | 261.33 | 21.43 | 200.00 | 21.28 |
April | 270.33 | 22.34 | 199.00 | 22.84 | 70.67 | 22.73 |
May | 231.00 | 23.31 | 179.83 | 23.89 | 23.33 | 24.07 |
June | 106.00 | 23.68 | 292.67 | 24.20 | 16.50 | 24.31 |
July | 95.33 | 24.01 | 365.50 | 24.40 | 24.00 | 24.53 |
August | 157.17 | 23.30 | 284.83 | 24.03 | 18.67 | 24.14 |
September | 308.33 | 22.31 | 126.17 | 22.88 | 14.17 | 22.88 |
October | 442.83 | 21.22 | 216.00 | 21.14 | 189.33 | 20.98 |
November | 485.50 | 20.21 | 445.67 | 20.14 | 445.67 | 20.12 |
December | 497.00 | 19.91 | 497.00 | 19.91 | 497.00 | 19.91 |
Annual Sum or Average | 3926.50 | 21.23 | 3673.17 | 21.55 | 2301.33 | 21.30 |
Minimum of Months | 95.33 | 19.91 | 126.17 | 19.91 | 14.17 | 19.91 |
Maximum of Months | 502.00 | 24.01 | 497.00 | 24.40 | 497.00 | 24.53 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.99 | 502.00 | 19.99 | 502.00 | 19.99 |
February | 454.00 | 20.19 | 426.67 | 20.16 | 426.67 | 20.15 |
March | 502.00 | 20.89 | 332.00 | 20.75 | 332.00 | 20.69 |
April | 357.33 | 22.05 | 138.00 | 22.11 | 81.50 | 21.93 |
May | 250.00 | 23.08 | 95.50 | 23.55 | 8.17 | 23.64 |
June | 67.83 | 23.63 | 294.50 | 24.32 | 8.17 | 24.39 |
July | 50.33 | 23.79 | 380.00 | 24.38 | 10.67 | 24.43 |
August | 155.83 | 22.97 | 238.67 | 23.84 | 5.17 | 23.88 |
September | 413.67 | 22.09 | 39.67 | 22.18 | 16.50 | 22.16 |
October | 499.17 | 20.88 | 270.33 | 20.73 | 270.33 | 20.66 |
November | 489.00 | 20.10 | 487.17 | 20.09 | 487.17 | 20.09 |
December | 497.00 | 20.00 | 497.00 | 20.00 | 497.00 | 20.00 |
Annual Sum or Average | 4238.17 | 21.01 | 3701.50 | 21.21 | 2645.33 | 20.98 |
Minimum of Months | 50.33 | 19.99 | 39.67 | 19.99 | 5.17 | 19.99 |
Maximum of Months | 502.00 | 23.79 | 502.00 | 24.38 | 502.00 | 24.43 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.69 | 502.00 | 19.69 | 502.00 | 19.69 |
February | 454.00 | 19.80 | 454.00 | 19.80 | 454.00 | 19.80 |
March | 514.00 | 20.18 | 484.17 | 20.15 | 484.17 | 20.13 |
April | 485.00 | 21.28 | 235.50 | 20.89 | 235.50 | 20.70 |
May | 360.83 | 23.25 | 7.33 | 23.20 | 7.33 | 23.15 |
June | 40.17 | 23.44 | 207.50 | 24.21 | 0.00 | 24.21 |
July | 21.33 | 23.49 | 360.50 | 24.35 | 0.00 | 24.35 |
August | 197.00 | 22.89 | 123.83 | 23.37 | 5.50 | 23.33 |
September | 480.83 | 21.60 | 129.67 | 21.37 | 129.67 | 21.23 |
October | 502.00 | 20.16 | 438.00 | 20.08 | 438.00 | 20.05 |
November | 489.00 | 19.72 | 489.00 | 19.72 | 489.00 | 19.72 |
December | 497.00 | 19.65 | 497.00 | 19.65 | 497.00 | 19.65 |
Annual Sum or Average | 4543.17 | 20.65 | 3928.50 | 20.65 | 3242.17 | 20.44 |
Minimum of Months | 21.33 | 19.65 | 7.33 | 19.65 | 0.00 | 19.65 |
Maximum of Months | 514.00 | 23.49 | 502.00 | 24.35 | 502.00 | 24.35 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.78 | 502.00 | 19.78 | 502.00 | 19.78 |
February | 454.00 | 19.91 | 445.33 | 19.90 | 445.33 | 19.90 |
March | 504.83 | 20.65 | 366.33 | 20.45 | 366.33 | 20.37 |
April | 382.17 | 21.64 | 169.83 | 21.44 | 142.50 | 21.21 |
May | 185.83 | 23.13 | 161.33 | 23.79 | 13.17 | 23.90 |
June | 75.00 | 23.58 | 319.67 | 24.15 | 11.50 | 24.21 |
July | 78.17 | 24.35 | 392.17 | 24.45 | 32.17 | 24.57 |
August | 153.83 | 22.82 | 271.33 | 23.72 | 5.50 | 23.72 |
September | 405.17 | 21.64 | 110.83 | 21.71 | 77.67 | 21.58 |
October | 499.33 | 20.36 | 382.50 | 20.22 | 382.50 | 20.16 |
November | 489.00 | 19.80 | 489.00 | 19.80 | 489.00 | 19.80 |
December | 497.00 | 19.74 | 497.00 | 19.74 | 497.00 | 19.74 |
Annual Sum or Average | 4226.33 | 20.72 | 4107.33 | 20.98 | 2964.67 | 20.74 |
Minimum of Months | 75.00 | 19.74 | 110.83 | 19.74 | 5.50 | 19.74 |
Maximum of Months | 504.83 | 24.35 | 502.00 | 24.45 | 502.00 | 24.57 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.82 | 494.17 | 19.81 | 494.17 | 19.80 |
February | 444.33 | 20.28 | 382.33 | 20.15 | 382.33 | 20.10 |
March | 420.83 | 20.77 | 330.17 | 20.77 | 285.00 | 20.61 |
April | 295.83 | 21.72 | 230.67 | 22.07 | 118.00 | 21.82 |
May | 255.67 | 22.84 | 174.00 | 23.48 | 27.33 | 23.61 |
June | 134.50 | 23.30 | 273.50 | 24.01 | 15.50 | 24.12 |
July | 124.17 | 23.58 | 340.17 | 24.25 | 23.50 | 24.39 |
August | 198.00 | 22.92 | 263.33 | 23.74 | 21.33 | 23.83 |
September | 344.83 | 21.70 | 159.50 | 22.10 | 65.67 | 21.95 |
October | 471.33 | 20.64 | 323.83 | 20.48 | 310.17 | 20.36 |
November | 487.67 | 19.90 | 469.17 | 19.86 | 469.17 | 19.85 |
December | 497.00 | 19.76 | 497.00 | 19.76 | 497.00 | 19.76 |
Annual Sum or Average | 4176.17 | 20.90 | 3937.83 | 21.17 | 2709.17 | 20.92 |
Minimum of Months | 124.17 | 19.76 | 159.50 | 19.76 | 15.50 | 19.76 |
Maximum of Months | 502.00 | 23.58 | 497.00 | 24.25 | 497.00 | 24.39 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.82 | 502.00 | 19.82 | 502.00 | 19.82 |
February | 454.00 | 19.96 | 446.33 | 19.95 | 446.33 | 19.95 |
March | 506.50 | 20.51 | 415.83 | 20.39 | 415.83 | 20.35 |
April | 381.67 | 21.49 | 198.50 | 21.43 | 149.00 | 21.21 |
May | 295.83 | 22.71 | 89.17 | 23.11 | 12.83 | 23.16 |
June | 105.67 | 23.25 | 272.17 | 24.12 | 8.33 | 24.18 |
July | 90.67 | 23.38 | 347.50 | 24.24 | 11.17 | 24.30 |
August | 213.50 | 22.68 | 212.17 | 23.49 | 9.17 | 23.51 |
September | 441.67 | 21.61 | 98.67 | 21.58 | 80.50 | 21.47 |
October | 502.00 | 20.38 | 390.17 | 20.27 | 390.17 | 20.23 |
November | 489.00 | 19.87 | 488.33 | 19.87 | 488.33 | 19.87 |
December | 497.00 | 19.81 | 497.00 | 19.81 | 497.00 | 19.81 |
Annual Sum or Average | 4479.50 | 20.78 | 3957.83 | 20.93 | 3010.67 | 20.71 |
Minimum of Months | 90.67 | 19.81 | 89.17 | 19.81 | 8.33 | 19.81 |
Maximum of Months | 506.50 | 23.38 | 502.00 | 24.24 | 502.00 | 24.30 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 286.50 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 385.17 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 512.00 | 27.00 | 0.00 | 27.00 |
April | 40.50 | 27.00 | 485.00 | 27.00 | 40.50 | 27.00 |
May | 1.67 | 27.00 | 508.00 | 27.00 | 1.67 | 27.00 |
June | 54.83 | 27.00 | 496.00 | 27.00 | 54.83 | 27.00 |
July | 184.17 | 27.00 | 497.00 | 27.00 | 184.17 | 27.00 |
August | 242.50 | 27.00 | 514.00 | 27.00 | 242.50 | 27.00 |
September | 3.83 | 27.00 | 485.00 | 27.00 | 3.83 | 27.00 |
October | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
November | 0.00 | 0.00 | 487.67 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 527.50 | 27.00 | 5655.33 | 27.00 | 527.50 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 286.50 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 242.50 | 27.00 | 514.00 | 27.00 | 242.50 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 281.50 | 25.33 | 28.33 | 25.30 | 12.00 | 25.18 |
February | 46.50 | 27.00 | 124.50 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 310.50 | 27.00 | 0.00 | 27.00 |
April | 11.67 | 27.00 | 440.17 | 27.00 | 11.67 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 5.67 | 27.00 | 496.00 | 27.00 | 5.67 | 27.00 |
July | 11.33 | 27.00 | 497.00 | 27.00 | 11.33 | 27.00 |
August | 12.50 | 27.00 | 514.00 | 27.00 | 12.50 | 27.00 |
September | 0.00 | 0.00 | 485.00 | 27.00 | 0.00 | 27.00 |
October | 0.00 | 0.00 | 377.00 | 27.00 | 0.00 | 27.00 |
November | 25.17 | 27.00 | 74.00 | 27.00 | 0.00 | 27.00 |
December | 40.83 | 27.00 | 29.33 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 435.17 | 25.92 | 3883.83 | 26.88 | 53.17 | 26.87 |
Minimum of Months | 0.00 | 0.00 | 28.33 | 25.30 | 0.00 | 25.18 |
Maximum of Months | 281.50 | 27.00 | 514.00 | 27.00 | 12.50 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 469.17 | 24.53 | 70.33 | 24.18 | 70.33 | 23.91 |
February | 106.33 | 26.83 | 45.33 | 26.88 | 0.00 | 26.88 |
March | 57.67 | 27.00 | 162.17 | 27.00 | 0.00 | 27.00 |
April | 29.17 | 27.00 | 366.17 | 27.00 | 10.50 | 27.00 |
May | 0.00 | 0.00 | 504.00 | 27.00 | 0.00 | 27.00 |
June | 6.67 | 27.00 | 496.00 | 27.00 | 6.67 | 27.00 |
July | 13.50 | 27.00 | 497.00 | 27.00 | 13.50 | 27.00 |
August | 15.17 | 27.00 | 514.00 | 27.00 | 15.17 | 27.00 |
September | 3.50 | 26.01 | 440.33 | 26.99 | 0.00 | 26.99 |
October | 39.50 | 27.00 | 206.83 | 27.00 | 0.00 | 27.00 |
November | 116.33 | 27.00 | 6.00 | 27.00 | 0.00 | 27.00 |
December | 127.67 | 27.00 | 0.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 984.67 | 25.80 | 3308.17 | 26.64 | 116.17 | 26.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 24.18 | 0.00 | 23.91 |
Maximum of Months | 469.17 | 27.00 | 514.00 | 27.00 | 70.33 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 27.00 | 502.00 | 27.00 | 1.33 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
August | 514.00 | 27.01 | 514.00 | 27.01 | 514.00 | 27.01 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5442.33 | 27.00 | 5943.00 | 27.00 | 5442.33 | 27.00 |
Minimum of Months | 1.33 | 27.00 | 454.00 | 27.00 | 1.33 | 27.00 |
Maximum of Months | 514.00 | 27.01 | 514.00 | 27.01 | 514.00 | 27.01 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99067 | 10.72532 | 0.54860 | 11.37167 |
February | 454.00000 | 27.00000 | 11.37917 | 0.63064 | 13.46841 |
March | 514.00000 | 26.99999 | 12.18931 | 0.73095 | 16.38036 |
April | 485.00000 | 26.99999 | 15.42936 | 0.87516 | 21.33910 |
May | 508.00000 | 27.00000 | 22.43314 | 0.21184 | 6.02387 |
June | 496.00000 | 27.00038 | 28.44992 | 0.33723 | 7.43782 |
July | 497.00000 | 27.00048 | 29.97655 | 0.39381 | 8.29381 |
August | 514.00000 | 27.00020 | 28.51800 | 0.40830 | 8.54820 |
September | 485.00000 | 27.00013 | 25.29224 | 0.18324 | 5.84022 |
October | 502.00000 | 27.00000 | 17.61250 | 0.75705 | 17.24526 |
November | 489.00000 | 27.00000 | 9.95558 | 0.65017 | 13.92546 |
December | 497.00000 | 27.00000 | 9.01282 | 0.65557 | 14.07806 |
Annual Sum or Average | 5943.00000 | 26.99931 | 18.47862 | 0.53088 | 11.97262 |
Minimum of Months | 454.00000 | 26.99067 | 9.01282 | 0.18324 | 5.84022 |
Maximum of Months | 514.00000 | 27.00048 | 29.97655 | 0.87516 | 21.33910 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 25.96652 | 10.71253 | 0.23082 | 7.48958 |
February | 454.00000 | 27.00000 | 11.36131 | 0.48139 | 10.04513 |
March | 514.00000 | 27.00000 | 12.18031 | 0.57311 | 12.07840 |
April | 485.00000 | 26.99999 | 15.42157 | 0.72366 | 16.34840 |
May | 508.00000 | 27.00000 | 22.42090 | 0.09991 | 5.37901 |
June | 496.00000 | 27.00040 | 28.46653 | 0.22322 | 6.15583 |
July | 497.00000 | 27.00054 | 30.00905 | 0.25075 | 6.41187 |
August | 514.00000 | 27.00025 | 28.52799 | 0.23209 | 6.26879 |
September | 485.00000 | 27.00011 | 25.33848 | 0.02967 | 5.25217 |
October | 502.00000 | 27.00000 | 17.59864 | 0.60379 | 12.84342 |
November | 489.00000 | 27.00000 | 9.94663 | 0.46870 | 9.70190 |
December | 497.00000 | 27.00000 | 9.00882 | 0.44898 | 9.31216 |
Annual Sum or Average | 5943.00000 | 26.91281 | 18.48022 | 0.36265 | 8.92130 |
Minimum of Months | 454.00000 | 25.96652 | 9.00882 | 0.02967 | 5.25217 |
Maximum of Months | 514.00000 | 27.00054 | 30.00905 | 0.72366 | 16.34840 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.66887 | 10.81234 | -0.0748 | 7.71424 |
February | 454.00000 | 26.96044 | 11.36242 | 0.39663 | 8.68602 |
March | 514.00000 | 27.00000 | 12.18243 | 0.48723 | 10.25696 |
April | 485.00000 | 26.99999 | 15.42343 | 0.65378 | 14.55026 |
May | 508.00000 | 27.00000 | 22.42431 | 0.06075 | 5.40990 |
June | 496.00000 | 27.00040 | 28.47475 | 0.21365 | 6.15231 |
July | 497.00000 | 27.00054 | 30.01606 | 0.24153 | 6.38765 |
August | 514.00000 | 27.00026 | 28.53753 | 0.20218 | 6.12596 |
September | 485.00000 | 26.97885 | 25.41181 | -0.0681 | 5.58324 |
October | 502.00000 | 27.00003 | 17.60168 | 0.51099 | 10.74417 |
November | 489.00000 | 27.00000 | 9.94876 | 0.38677 | 8.31596 |
December | 497.00000 | 27.00000 | 9.00977 | 0.37560 | 8.11230 |
Annual Sum or Average | 5943.00000 | 26.79845 | 18.49795 | 0.28102 | 8.15546 |
Minimum of Months | 454.00000 | 24.66887 | 9.00977 | -0.0748 | 5.40990 |
Maximum of Months | 514.00000 | 27.00054 | 30.01606 | 0.65378 | 14.55026 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00004 | 30.00123 | 0.96479 | 24.68952 |
February | 454.00000 | 27.00032 | 29.99569 | 1.14938 | 32.82764 |
March | 514.00000 | 27.00015 | 25.12490 | 1.29069 | 39.79841 |
April | 485.00000 | 27.00006 | 19.48448 | 1.42713 | 46.97291 |
May | 508.00000 | 27.00007 | 29.22824 | 0.54159 | 11.18011 |
June | 496.00000 | 27.00071 | 30.89433 | 0.78446 | 18.01419 |
July | 497.00000 | 27.00589 | 34.31068 | 1.02468 | 27.20148 |
August | 514.00000 | 27.00871 | 30.73190 | 1.19445 | 34.99870 |
September | 485.00000 | 27.00014 | 30.01273 | 0.56908 | 11.82781 |
October | 502.00000 | 27.00029 | 29.66103 | 1.23321 | 36.90254 |
November | 489.00000 | 27.00029 | 27.00490 | 1.30439 | 40.50086 |
December | 497.00000 | 27.00019 | 22.33912 | 1.38940 | 44.95231 |
Annual Sum or Average | 5943.00000 | 27.00143 | 28.23775 | 1.07229 | 30.80379 |
Minimum of Months | 454.00000 | 27.00004 | 19.48448 | 0.54159 | 11.18011 |
Maximum of Months | 514.00000 | 27.00871 | 34.31068 | 1.42713 | 46.97291 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.32718 | 14.43262 | 0.20586 | 5.98807 |
February | 454.00000 | 24.50374 | 13.15936 | 0.25282 | 6.68912 |
March | 514.00000 | 24.63504 | 13.98582 | 0.31224 | 7.85225 |
April | 485.00000 | 27.44477 | 57.13606 | 1.33196 | 47.44242 |
May | 508.00000 | 30.07259 | 99.99087 | 1.94783 | 74.04884 |
June | 496.00000 | 30.37328 | 99.99862 | 2.06477 | 79.28205 |
July | 497.00000 | 30.60668 | 99.99765 | 2.15728 | 82.94732 |
August | 514.00000 | 30.84447 | 99.99902 | 2.24957 | 86.31111 |
September | 485.00000 | 30.35353 | 99.99704 | 2.05823 | 78.98805 |
October | 502.00000 | 27.02769 | 51.13190 | 1.20050 | 42.24229 |
November | 489.00000 | 24.57909 | 10.61784 | 0.27010 | 6.79808 |
December | 497.00000 | 24.59938 | 10.53091 | 0.26535 | 6.92843 |
Annual Sum or Average | 5943.00000 | 27.46965 | 56.23507 | 1.19999 | 44.06873 |
Minimum of Months | 454.00000 | 24.32718 | 10.53091 | 0.20586 | 5.98807 |
Maximum of Months | 514.00000 | 30.84447 | 99.99902 | 2.24957 | 86.31111 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.40086 | 18.22014 | 0.02075 | 5.41557 |
February | 454.00000 | 23.84641 | 15.82789 | 0.13045 | 5.66236 |
March | 514.00000 | 24.12336 | 14.40661 | 0.21589 | 6.16802 |
April | 485.00000 | 24.35638 | 14.17717 | 0.32634 | 7.64819 |
May | 508.00000 | 24.45411 | 20.38985 | -0.3931 | 9.03263 |
June | 496.00000 | 24.41472 | 33.55883 | -0.2874 | 7.54285 |
July | 497.00000 | 24.51591 | 41.70533 | -0.1887 | 6.69179 |
August | 514.00000 | 24.44617 | 36.64426 | -0.2374 | 7.16132 |
September | 485.00000 | 24.50762 | 25.75880 | -0.3522 | 8.69723 |
October | 502.00000 | 24.37202 | 18.98621 | 0.33045 | 7.96268 |
November | 489.00000 | 24.00690 | 14.72144 | 0.16207 | 5.73611 |
December | 497.00000 | 23.94184 | 13.00987 | 0.13152 | 5.64897 |
Annual Sum or Average | 5943.00000 | 24.20113 | 22.35706 | -0.0134 | 6.95500 |
Minimum of Months | 454.00000 | 23.40086 | 13.00987 | -0.3931 | 5.41557 |
Maximum of Months | 514.00000 | 24.51591 | 41.70533 | 0.33045 | 9.03263 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.34798 | 17.34031 | -0.5031 | 12.47317 |
February | 454.00000 | 22.03923 | 17.93671 | -0.3204 | 8.85967 |
March | 514.00000 | 22.97921 | 17.72012 | -0.0824 | 6.05331 |
April | 485.00000 | 23.68238 | 16.69314 | 0.10911 | 5.84871 |
May | 508.00000 | 24.05235 | 22.05190 | -0.6340 | 13.74508 |
June | 496.00000 | 24.16526 | 34.78864 | -0.4899 | 10.33242 |
July | 497.00000 | 24.20671 | 43.64523 | -0.4175 | 8.99754 |
August | 514.00000 | 24.15777 | 38.39652 | -0.4765 | 10.11652 |
September | 485.00000 | 23.91246 | 28.82576 | -0.6668 | 14.94542 |
October | 502.00000 | 23.17397 | 23.47151 | 0.00161 | 5.94660 |
November | 489.00000 | 21.93050 | 17.98409 | -0.3541 | 8.71077 |
December | 497.00000 | 21.47275 | 14.94651 | -0.4840 | 10.94407 |
Annual Sum or Average | 5943.00000 | 23.10264 | 24.55381 | -0.3603 | 9.74986 |
Minimum of Months | 454.00000 | 21.34798 | 14.94651 | -0.6668 | 5.84871 |
Maximum of Months | 514.00000 | 24.20671 | 43.64523 | 0.10911 | 14.94542 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.28579 | 18.92207 | -0.8051 | 21.30827 |
February | 454.00000 | 20.58886 | 20.33523 | -0.7042 | 18.42270 |
March | 514.00000 | 21.33327 | 19.89330 | -0.5051 | 12.42208 |
April | 485.00000 | 22.53598 | 18.42152 | -0.1831 | 8.38354 |
May | 508.00000 | 23.71724 | 22.88624 | -0.7611 | 18.28394 |
June | 496.00000 | 24.07111 | 34.89268 | -0.5234 | 11.03263 |
July | 497.00000 | 24.13576 | 43.87450 | -0.4435 | 9.44029 |
August | 514.00000 | 23.95051 | 39.14317 | -0.5583 | 12.32470 |
September | 485.00000 | 22.90647 | 31.61501 | -1.0342 | 29.46379 |
October | 502.00000 | 21.33511 | 26.61938 | -0.4619 | 11.86608 |
November | 489.00000 | 20.40194 | 20.15728 | -0.7622 | 19.58968 |
December | 497.00000 | 20.28164 | 16.17877 | -0.8240 | 21.45600 |
Annual Sum or Average | 5943.00000 | 22.14304 | 26.13879 | -0.6296 | 16.11786 |
Minimum of Months | 454.00000 | 20.28164 | 16.17877 | -1.0342 | 8.38354 |
Maximum of Months | 514.00000 | 24.13576 | 43.87450 | -0.1831 | 29.46379 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.52745 | 17.04910 | -0.7379 | 17.57803 |
February | 454.00000 | 20.92918 | 16.79460 | -0.6087 | 13.97005 |
March | 514.00000 | 21.91599 | 15.49561 | -0.3527 | 8.99067 |
April | 485.00000 | 23.56338 | 14.40233 | 0.08783 | 6.69730 |
May | 508.00000 | 24.37819 | 19.98517 | -0.4466 | 9.88218 |
June | 496.00000 | 24.44127 | 32.90626 | -0.2525 | 7.20972 |
July | 497.00000 | 24.57819 | 41.01294 | -0.1522 | 6.81786 |
August | 514.00000 | 24.37692 | 36.35385 | -0.2983 | 7.86213 |
September | 485.00000 | 24.11778 | 26.23744 | -0.5835 | 13.00881 |
October | 502.00000 | 22.67705 | 20.27138 | -0.1277 | 7.75029 |
November | 489.00000 | 20.86994 | 15.93312 | -0.6311 | 13.80528 |
December | 497.00000 | 20.81289 | 13.74417 | -0.6735 | 15.00054 |
Annual Sum or Average | 5943.00000 | 22.78011 | 22.58120 | -0.3966 | 10.67941 |
Minimum of Months | 454.00000 | 20.52745 | 13.74417 | -0.7379 | 6.69730 |
Maximum of Months | 514.00000 | 24.57819 | 41.01294 | 0.08783 | 17.57803 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.44732 | 16.01596 | -0.7696 | 18.68619 |
February | 454.00000 | 20.95582 | 15.71177 | -0.5972 | 13.71077 |
March | 514.00000 | 22.20306 | 14.18128 | -0.2397 | 8.72638 |
April | 485.00000 | 23.51737 | 13.79540 | 0.15693 | 8.08812 |
May | 508.00000 | 24.42246 | 19.60039 | -0.2565 | 8.59439 |
June | 496.00000 | 24.36494 | 32.84110 | -0.1583 | 6.84337 |
July | 497.00000 | 24.48496 | 40.94665 | -0.0569 | 6.96895 |
August | 514.00000 | 24.28441 | 36.27312 | -0.2183 | 7.28982 |
September | 485.00000 | 24.02689 | 25.93318 | -0.5189 | 13.14621 |
October | 502.00000 | 22.44066 | 19.66558 | -0.1521 | 8.29278 |
November | 489.00000 | 20.68322 | 14.84533 | -0.6925 | 15.56477 |
December | 497.00000 | 20.62148 | 12.79099 | -0.7466 | 17.32565 |
Annual Sum or Average | 5943.00000 | 22.71931 | 21.95194 | -0.3519 | 11.06259 |
Minimum of Months | 454.00000 | 20.44732 | 12.79099 | -0.7696 | 6.84337 |
Maximum of Months | 514.00000 | 24.48496 | 40.94665 | 0.15693 | 18.68619 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.40377 | 16.07055 | -0.7833 | 19.95393 |
February | 454.00000 | 21.42800 | 15.33776 | -0.4712 | 12.94366 |
March | 514.00000 | 22.44656 | 13.82989 | -0.1469 | 9.50998 |
April | 485.00000 | 23.66166 | 13.52538 | 0.24099 | 9.80228 |
May | 508.00000 | 24.25404 | 19.84448 | -0.3610 | 10.63235 |
June | 496.00000 | 24.33385 | 32.94976 | -0.2046 | 7.47293 |
July | 497.00000 | 24.44278 | 41.10568 | -0.1038 | 7.14284 |
August | 514.00000 | 24.29503 | 36.24215 | -0.1993 | 8.06591 |
September | 485.00000 | 23.79974 | 26.22244 | -0.5679 | 15.31298 |
October | 502.00000 | 22.42051 | 19.69625 | -0.1458 | 8.83037 |
November | 489.00000 | 20.84608 | 14.75279 | -0.6476 | 15.43939 |
December | 497.00000 | 20.47357 | 12.93717 | -0.7893 | 19.06369 |
Annual Sum or Average | 5943.00000 | 22.74573 | 21.94691 | -0.3470 | 11.98441 |
Minimum of Months | 454.00000 | 20.40377 | 12.93717 | -0.7893 | 7.14284 |
Maximum of Months | 514.00000 | 24.44278 | 41.10568 | 0.24099 | 19.95393 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.74467 | 15.66478 | -0.6569 | 14.72377 |
February | 454.00000 | 21.41005 | 15.15455 | -0.4485 | 10.18137 |
March | 514.00000 | 22.83072 | 13.48783 | -0.0714 | 6.72739 |
April | 485.00000 | 24.21464 | 13.15993 | 0.37286 | 9.32868 |
May | 508.00000 | 24.23702 | 19.99696 | -0.4099 | 10.31955 |
June | 496.00000 | 24.40937 | 32.87978 | -0.1644 | 6.90111 |
July | 497.00000 | 24.53517 | 40.90734 | -0.0605 | 6.54065 |
August | 514.00000 | 24.42770 | 35.97558 | -0.1493 | 6.91804 |
September | 485.00000 | 23.65964 | 26.46560 | -0.6587 | 16.30025 |
October | 502.00000 | 22.74144 | 19.22303 | -0.0672 | 6.81153 |
November | 489.00000 | 21.52496 | 14.03826 | -0.4262 | 9.27118 |
December | 497.00000 | 21.48142 | 12.06327 | -0.4519 | 9.85716 |
Annual Sum or Average | 5943.00000 | 23.03137 | 21.65478 | -0.2645 | 9.46078 |
Minimum of Months | 454.00000 | 20.74467 | 12.06327 | -0.6587 | 6.54065 |
Maximum of Months | 514.00000 | 24.53517 | 40.90734 | 0.37286 | 16.30025 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.91202 | 16.85598 | -1.0024 | 28.29099 |
February | 454.00000 | 20.04583 | 17.94657 | -0.9194 | 25.13418 |
March | 514.00000 | 20.63721 | 17.72150 | -0.7180 | 17.42035 |
April | 485.00000 | 22.06626 | 16.85639 | -0.3028 | 9.85705 |
May | 508.00000 | 23.86506 | 21.28901 | -0.6995 | 16.00347 |
June | 496.00000 | 24.21407 | 33.51838 | -0.4156 | 8.95429 |
July | 497.00000 | 24.34288 | 42.17527 | -0.3311 | 7.90675 |
August | 514.00000 | 23.93006 | 38.03071 | -0.5626 | 12.74864 |
September | 485.00000 | 22.51774 | 30.38223 | -1.1703 | 35.59689 |
October | 502.00000 | 20.81237 | 24.05127 | -0.6182 | 14.98711 |
November | 489.00000 | 19.94797 | 17.74739 | -0.9638 | 26.72127 |
December | 497.00000 | 19.89088 | 14.35876 | -1.0244 | 28.98951 |
Annual Sum or Average | 5943.00000 | 21.86566 | 24.30866 | -0.7252 | 19.29392 |
Minimum of Months | 454.00000 | 19.89088 | 14.35876 | -1.1703 | 7.90675 |
Maximum of Months | 514.00000 | 24.34288 | 42.17527 | -0.3028 | 35.59689 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.73760 | 15.69277 | -1.0467 | 30.26786 |
February | 385.00000 | 20.03541 | 16.46553 | -0.9073 | 24.60725 |
March | 433.00000 | 21.15303 | 15.82309 | -0.5448 | 13.82112 |
April | 410.00000 | 22.61017 | 14.93007 | -0.1053 | 9.00839 |
May | 430.00000 | 23.97917 | 20.23805 | -0.4850 | 13.90305 |
June | 418.00000 | 24.16846 | 33.24195 | -0.3112 | 8.89953 |
July | 422.00000 | 24.35860 | 41.67957 | -0.1954 | 8.43655 |
August | 433.00000 | 23.88074 | 37.28229 | -0.4559 | 11.82642 |
September | 410.00000 | 22.63462 | 28.78165 | -1.0549 | 32.93033 |
October | 427.00000 | 20.92666 | 22.42725 | -0.5739 | 14.03414 |
November | 417.00000 | 19.77546 | 16.39408 | -1.0074 | 28.62104 |
December | 422.00000 | 19.68426 | 13.28989 | -1.0775 | 31.39406 |
Annual Sum or Average | 5034.00000 | 21.92554 | 23.07586 | -0.6449 | 18.89806 |
Minimum of Months | 385.00000 | 19.68426 | 13.28989 | -1.0775 | 8.43655 |
Maximum of Months | 433.00000 | 24.35860 | 41.67957 | -0.1053 | 32.93033 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.01695 | 15.84207 | -0.9525 | 26.53683 |
February | 454.00000 | 20.88682 | 16.21513 | -0.6480 | 17.60534 |
March | 514.00000 | 21.94940 | 15.45092 | -0.2805 | 12.14987 |
April | 485.00000 | 23.18604 | 14.61835 | 0.11735 | 10.52778 |
May | 508.00000 | 23.78526 | 20.67734 | -0.5463 | 16.29188 |
June | 496.00000 | 24.06173 | 33.56887 | -0.3477 | 9.91570 |
July | 497.00000 | 24.18517 | 42.17577 | -0.2507 | 9.17396 |
August | 514.00000 | 23.91009 | 37.39009 | -0.3894 | 12.10382 |
September | 485.00000 | 23.03454 | 28.34881 | -0.8516 | 26.19145 |
October | 502.00000 | 21.59433 | 22.10290 | -0.3699 | 11.66741 |
November | 489.00000 | 20.24080 | 16.29424 | -0.8570 | 23.07065 |
December | 497.00000 | 19.91423 | 13.41231 | -1.0147 | 28.59944 |
Annual Sum or Average | 5943.00000 | 22.24347 | 23.07905 | -0.5311 | 16.94363 |
Minimum of Months | 454.00000 | 19.91423 | 13.41231 | -1.0147 | 9.17396 |
Maximum of Months | 514.00000 | 24.18517 | 42.17577 | 0.11735 | 28.59944 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.98771 | 15.80887 | -0.9724 | 26.99877 |
February | 454.00000 | 20.19346 | 16.73167 | -0.8577 | 22.64878 |
March | 514.00000 | 20.96248 | 16.34679 | -0.5972 | 14.44094 |
April | 485.00000 | 22.62291 | 15.31391 | -0.0773 | 9.10910 |
May | 508.00000 | 23.68053 | 21.06346 | -0.6520 | 17.10884 |
June | 496.00000 | 24.16443 | 33.55031 | -0.3337 | 9.16668 |
July | 497.00000 | 24.21995 | 42.23995 | -0.2828 | 8.37146 |
August | 514.00000 | 23.81612 | 37.81571 | -0.4933 | 12.61622 |
September | 485.00000 | 22.39217 | 29.48966 | -1.1339 | 35.04101 |
October | 502.00000 | 20.90156 | 22.88432 | -0.5739 | 13.51316 |
November | 489.00000 | 20.09582 | 16.35913 | -0.9092 | 24.34010 |
December | 497.00000 | 20.00332 | 13.26779 | -0.9790 | 26.95970 |
Annual Sum or Average | 5943.00000 | 21.93570 | 23.47595 | -0.6532 | 18.28026 |
Minimum of Months | 454.00000 | 19.98771 | 13.26779 | -1.1339 | 8.37146 |
Maximum of Months | 514.00000 | 24.21995 | 42.23995 | -0.0773 | 35.04101 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.68630 | 17.63363 | -1.1184 | 33.22995 |
February | 454.00000 | 19.80012 | 19.41406 | -1.0471 | 30.43476 |
March | 514.00000 | 20.17850 | 19.11562 | -0.8908 | 23.99387 |
April | 485.00000 | 21.27611 | 17.94867 | -0.5207 | 14.63609 |
May | 508.00000 | 23.48753 | 21.97579 | -0.8402 | 21.59932 |
June | 496.00000 | 24.13204 | 33.62064 | -0.4471 | 9.74539 |
July | 497.00000 | 24.26904 | 42.30120 | -0.3604 | 8.38698 |
August | 514.00000 | 23.64653 | 38.76922 | -0.6672 | 16.49428 |
September | 485.00000 | 21.61920 | 32.45986 | -1.5066 | 51.56106 |
October | 502.00000 | 20.15962 | 26.13320 | -0.8347 | 22.28282 |
November | 489.00000 | 19.72405 | 19.11412 | -1.0923 | 32.16338 |
December | 497.00000 | 19.64641 | 14.76796 | -1.1537 | 34.65225 |
Annual Sum or Average | 5943.00000 | 21.48652 | 25.32990 | -0.8708 | 24.82347 |
Minimum of Months | 454.00000 | 19.64641 | 14.76796 | -1.5066 | 8.38698 |
Maximum of Months | 514.00000 | 24.26904 | 42.30120 | -0.3604 | 51.56106 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.78325 | 16.99165 | -1.1008 | 32.39437 |
February | 454.00000 | 19.91288 | 18.56986 | -0.9958 | 28.35802 |
March | 514.00000 | 20.70983 | 17.74842 | -0.6873 | 18.30135 |
April | 485.00000 | 22.17913 | 16.12419 | -0.2264 | 11.13415 |
May | 508.00000 | 23.79929 | 20.72255 | -0.5360 | 15.44526 |
June | 496.00000 | 24.07712 | 33.39156 | -0.3161 | 9.15652 |
July | 497.00000 | 24.25156 | 41.84518 | -0.2046 | 8.55309 |
August | 514.00000 | 23.73908 | 37.88234 | -0.4890 | 13.02906 |
September | 485.00000 | 22.10688 | 30.63086 | -1.2623 | 41.95572 |
October | 502.00000 | 20.38187 | 24.97536 | -0.7512 | 19.71091 |
November | 489.00000 | 19.79983 | 18.32043 | -1.0783 | 31.50900 |
December | 497.00000 | 19.74273 | 14.22666 | -1.1405 | 33.99804 |
Annual Sum or Average | 5943.00000 | 21.72444 | 24.34532 | -0.7292 | 21.84544 |
Minimum of Months | 454.00000 | 19.74273 | 14.22666 | -1.2623 | 8.55309 |
Maximum of Months | 514.00000 | 24.25156 | 41.84518 | -0.2046 | 41.95572 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.81979 | 16.95817 | -1.0622 | 30.98901 |
February | 454.00000 | 20.36000 | 18.08977 | -0.8282 | 23.32708 |
March | 514.00000 | 21.38762 | 17.02598 | -0.4712 | 16.23696 |
April | 485.00000 | 22.70746 | 15.46813 | -0.0373 | 12.21249 |
May | 508.00000 | 23.49443 | 21.13446 | -0.6599 | 20.73415 |
June | 496.00000 | 23.92323 | 33.77064 | -0.3945 | 11.47699 |
July | 497.00000 | 24.05781 | 42.43622 | -0.2937 | 10.42905 |
August | 514.00000 | 23.68359 | 37.98927 | -0.4748 | 14.94690 |
September | 485.00000 | 22.45528 | 29.90477 | -1.0939 | 36.49588 |
October | 502.00000 | 20.84104 | 24.37356 | -0.6037 | 17.01434 |
November | 489.00000 | 19.90872 | 18.20190 | -1.0050 | 28.95143 |
December | 497.00000 | 19.75905 | 14.21571 | -1.1235 | 33.31031 |
Annual Sum or Average | 5943.00000 | 21.88106 | 24.19456 | -0.6687 | 21.27907 |
Minimum of Months | 454.00000 | 19.75905 | 14.21571 | -1.1235 | 10.42905 |
Maximum of Months | 514.00000 | 24.05781 | 42.43622 | -0.0373 | 36.49588 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.82219 | 16.90355 | -1.0741 | 31.29174 |
February | 454.00000 | 19.96241 | 18.46853 | -0.9693 | 27.25329 |
March | 514.00000 | 20.55597 | 17.83064 | -0.7458 | 19.45635 |
April | 485.00000 | 22.06331 | 16.23184 | -0.2405 | 11.94861 |
May | 508.00000 | 23.34584 | 21.55967 | -0.7754 | 22.01154 |
June | 496.00000 | 24.03336 | 33.73383 | -0.3778 | 10.48387 |
July | 497.00000 | 24.09835 | 42.48598 | -0.3242 | 9.43970 |
August | 514.00000 | 23.54781 | 38.48563 | -0.5896 | 15.85921 |
September | 485.00000 | 21.83425 | 31.02909 | -1.3616 | 45.73457 |
October | 502.00000 | 20.38418 | 24.90435 | -0.7478 | 19.02846 |
November | 489.00000 | 19.87011 | 18.19145 | -1.0232 | 29.24765 |
December | 497.00000 | 19.81186 | 14.12063 | -1.0859 | 31.67164 |
Annual Sum or Average | 5943.00000 | 21.62650 | 24.55894 | -0.7741 | 22.69537 |
Minimum of Months | 454.00000 | 19.81186 | 14.12063 | -1.3616 | 9.43970 |
Maximum of Months | 514.00000 | 24.09835 | 42.48598 | -0.2405 | 45.73457 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 49564504.62 | 574.50 | 23-JAN-14:10 | 40.63 | 0.483695E+09 | 0.00 | 0.533259E+09 | 0.53 | 9.85 | 23-JAN-20:40 | 0.00 | 0.00 |
February | 58337358.71 | 1920.99 | 17-FEB-08:30 | 37.02 | 0.569427E+09 | 0.00 | 0.627765E+09 | 0.54 | 9.85 | 21-FEB-19:30 | 0.00 | 0.00 |
March | 77848672.37 | 2416.84 | 30-MAR-12:10 | 38.63 | 0.759814E+09 | 0.00 | 0.837663E+09 | 0.51 | 9.85 | 08-MAR-18:00 | 0.00 | 0.00 |
April | 0.268081E+09 | 17867.55 | 20-APR-14:10 | 20.11 | 0.261892E+10 | 0.00 | 0.288700E+10 | 0.27 | 9.85 | 01-APR-08:70 | 0.00 | 0.00 |
May | 0.135536E+11 | 129727.53 | 31-MAY-15:40 | 191.43 | 0.128661E+12 | 0.00 | 0.142214E+12 | 2.50 | 10.00 | 09-MAY-14:10 | 0.00 | 0.00 |
June | 0.529165E+11 | 151865.08 | 29-JUN-17:30 | 390.30 | 0.480962E+12 | 0.00 | 0.533879E+12 | 5.15 | 10.01 | 21-JUN-22:42 | 0.00 | 0.00 |
July | 0.683638E+11 | 159467.01 | 29-JUL-14:00 | 429.97 | 0.597338E+12 | 0.00 | 0.665702E+12 | 5.38 | 10.01 | 11-JUL-05:04 | 0.00 | 0.00 |
August | 0.376951E+11 | 155669.01 | 24-AUG-13:30 | 325.01 | 0.341143E+12 | 0.00 | 0.378839E+12 | 4.17 | 10.01 | 27-AUG-14:23 | 0.00 | 0.00 |
September | 0.862132E+09 | 30927.68 | 07-SEP-16:00 | 45.95 | 0.841129E+10 | 0.00 | 0.927343E+10 | 0.62 | 9.82 | 17-SEP-16:30 | 0.00 | 0.00 |
October | 24476167.72 | 1265.51 | 26-OCT-12:00 | 12.24 | 0.238909E+09 | 0.00 | 0.263385E+09 | 0.16 | 9.85 | 28-OCT-09:20 | 0.00 | 0.00 |
November | 75847329.45 | 2494.63 | 07-NOV-10:00 | 39.35 | 0.740184E+09 | 0.00 | 0.816032E+09 | 0.53 | 9.85 | 03-NOV-12:20 | 0.00 | 0.00 |
December | 54257718.42 | 2417.39 | 27-DEC-15:20 | 32.47 | 0.529765E+09 | 0.00 | 0.584023E+09 | 0.43 | 9.85 | 06-DEC-16:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174000E+12 | 1603.10 | 0.156246E+13 | 0.00 | 0.173646E+13 | 1.74 | 0.00 | 0.00 | ||||
Minimum of Months | 24476167.72 | 574.50 | 12.24 | 0.238909E+09 | 0.00 | 0.263385E+09 | 0.16 | 9.82 | 0.00 | 0.00 | ||
Maximum of Months | 0.683638E+11 | 159467.01 | 429.97 | 0.597338E+12 | 0.00 | 0.665702E+12 | 5.38 | 10.01 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 83771110.43 | 70217.98 | 31-MAY-15:30 | 0.50 | 0.766986E+09 | 0.00 | 0.850758E+09 | 0.01 | 10.70 | 31-MAY-15:20 | 0.00 | 0.00 |
June | 0.698096E+10 | 96259.20 | 20-JUN-13:10 | 27.33 | 0.622136E+11 | 0.00 | 0.691945E+11 | 0.34 | 10.71 | 21-JUN-19:10 | 0.00 | 0.00 |
July | 0.124008E+11 | 102260.73 | 03-JUL-15:00 | 51.67 | 0.112010E+12 | 0.00 | 0.124411E+12 | 0.63 | 10.70 | 10-JUL-16:20 | 0.00 | 0.00 |
August | 0.472799E+10 | 100325.65 | 11-AUG-15:20 | 19.67 | 0.429254E+11 | 0.00 | 0.476534E+11 | 0.24 | 10.69 | 11-AUG-12:10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.241935E+11 | 99.17 | 0.217916E+12 | 0.00 | 0.242109E+12 | 0.10 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.124008E+11 | 102260.73 | 51.67 | 0.112010E+12 | 0.00 | 0.124411E+12 | 0.63 | 10.71 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.188543E+09 | 744.00 | 606.83 | 30-JAN-18:00 | 52813.03 | 30-JAN-18:05 | 18.51 | 18.33 | 16.12 |
February | 0.780946E+09 | 672.00 | 2852.46 | 08-FEB-16:00 | 151748.50 | 15-FEB-22:03 | 19.06 | 18.33 | 16.18 |
March | 0.186264E+10 | 744.00 | 3282.41 | 22-MAR-11:30 | 252509.77 | 15-MAR-21:02 | 19.74 | 18.33 | 16.24 |
April | 0.456936E+10 | 720.00 | 8991.16 | 22-APR-14:00 | 226590.36 | 07-APR-15:00 | 20.42 | 18.33 | 16.34 |
May | 0.128886E+11 | 744.00 | 49248.27 | 07-MAY-15:32 | 67934.81 | 31-MAY-23:10 | 19.08 | 18.41 | 16.47 |
June | 0.512464E+11 | 720.00 | 49248.27 | 02-JUN-12:20 | 406289.96 | 30-JUN-12:20 | 21.02 | 19.45 | 16.48 |
July | 0.650408E+11 | 744.00 | 49248.27 | 02-JUL-14:52 | 616309.42 | 29-JUL-18:35 | 23.89 | 20.52 | 16.48 |
August | 0.552905E+11 | 744.00 | 49248.27 | 01-AUG-11:00 | 631439.54 | 23-AUG-16:00 | 23.83 | 19.67 | 16.48 |
September | 0.212551E+10 | 720.00 | 5738.51 | 07-SEP-16:00 | 122885.29 | 29-SEP-07:43 | 18.86 | 18.33 | 16.40 |
October | 0.177369E+10 | 744.00 | 2751.11 | 01-OCT-15:00 | 152013.14 | 12-OCT-08:55 | 19.23 | 18.33 | 16.33 |
November | 0.120801E+10 | 720.00 | 1268.43 | 03-NOV-16:50 | 127087.43 | 08-NOV-15:40 | 19.55 | 18.33 | 16.27 |
December | 0.163118E+10 | 744.00 | 1999.39 | 26-DEC-13:40 | 151848.57 | 26-DEC-13:50 | 19.99 | 18.33 | 16.28 |
Annual Sum or Average | 0.198606E+12 | 8760.00 | 20.28 | 18.73 | 16.34 | ||||
Minimum of Months | 0.188543E+09 | 672.00 | 606.83 | 52813.03 | 18.51 | 18.33 | 16.12 | ||
Maximum of Months | 0.650408E+11 | 744.00 | 49248.27 | 631439.54 | 23.89 | 20.52 | 16.48 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 214310.72 | 13-JAN-18:50 | 20.94 | 20.94 | 0.17 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 214320.34 | 03-FEB-17:10 | 20.84 | 20.84 | 0.18 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 214632.70 | 30-MAR-10:35 | 20.89 | 20.89 | 0.19 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 214033.69 | 12-APR-06:46 | 21.00 | 21.00 | 0.37 |
May | 63695643.59 | 68.33 | 1667.09 | 31-MAY-15:10 | 1085422.60 | 31-MAY-15:40 | 21.24 | 20.99 | 10.52 |
June | 0.137142E+10 | 291.78 | 15914.78 | 20-JUN-12:50 | 1195726.73 | 20-JUN-12:50 | 22.06 | 21.10 | 26.31 |
July | 0.277397E+10 | 330.57 | 15914.78 | 03-JUL-14:50 | 1219447.93 | 19-JUL-13:50 | 22.29 | 21.11 | 27.98 |
August | 0.101111E+10 | 211.24 | 15914.78 | 02-AUG-13:20 | 1232340.36 | 04-AUG-13:20 | 21.73 | 21.06 | 19.82 |
September | 874749.39 | 4.08 | 144.47 | 07-SEP-16:00 | 342505.20 | 07-SEP-16:00 | 21.01 | 20.98 | 1.86 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 214283.20 | 28-OCT-14:00 | 20.95 | 20.95 | 0.07 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 214300.00 | 13-NOV-07:50 | 20.86 | 20.86 | 0.08 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 214309.92 | 19-DEC-21:50 | 20.91 | 20.90 | 0.17 |
Annual Sum or Average | 0.522108E+10 | 906.00 | 21.23 | 20.97 | 7.37 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 214033.69 | 20.84 | 20.84 | 0.07 | ||
Maximum of Months | 0.277397E+10 | 330.57 | 15914.78 | 1232340.36 | 22.29 | 21.11 | 27.98 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 20.94 | 20.94 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 20.84 | 20.84 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 20.89 | 20.89 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 21.00 | 21.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 01-MAY-00:03 | 21.24 | 21.24 | 0.00 |
June | 0.416941E+09 | 22.00 | 15914.78 | 29-JUN-10:50 | 1128545.36 | 20-JUN-14:30 | 22.06 | 21.93 | 1.66 |
July | 0.383131E+09 | 37.50 | 15914.78 | 03-JUL-15:00 | 1122467.39 | 20-JUL-15:50 | 22.29 | 22.08 | 2.73 |
August | 0.144147E+09 | 13.50 | 15914.78 | 23-AUG-14:40 | 1114828.07 | 11-AUG-14:40 | 21.73 | 21.66 | 0.99 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 01-SEP-00:03 | 21.01 | 21.01 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 20.95 | 20.95 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 20.86 | 20.86 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 20.91 | 20.91 | 0.00 |
Annual Sum or Average | 0.944219E+09 | 73.00 | 21.23 | 21.19 | 0.45 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.84 | 20.84 | 0.00 | ||
Maximum of Months | 0.416941E+09 | 37.50 | 15914.78 | 1128545.36 | 22.29 | 22.08 | 2.73 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.881184E+12 | 0.00 | 610.65 | 2252308.03 | 02-JAN-04:01 | 0.00 | 33.99 | 73.15 | 1.82 | 0.00 | 0.09 | 0.61 | 02-JAN-04:01 |
February | 0.518497E+12 | 0.00 | 525.71 | 2223375.03 | 07-FEB-06:01 | 0.00 | 31.21 | 70.71 | 1.14 | 0.00 | 0.06 | 0.60 | 07-FEB-06:01 |
March | 0.239462E+12 | 0.00 | 527.28 | 1955073.57 | 01-MAR-06:01 | 0.00 | 26.82 | 65.34 | 0.45 | 0.00 | 0.02 | 0.53 | 01-MAR-06:01 |
April | 0.411754E+11 | 0.00 | 247.23 | 1662979.99 | 04-APR-04:01 | 0.00 | 24.73 | 44.17 | 0.07 | 0.00 | 0.00 | 0.45 | 04-APR-04:01 |
May | 0.705134E+09 | 0.00 | 36.90 | 173578.45 | 27-MAY-06:10 | 0.00 | 23.46 | 26.37 | 0.00 | 0.00 | 0.00 | 0.05 | 27-MAY-06:10 |
June | 3635.10 | 0.00 | 0.33 | 3.95 | 01-JUN-18:30 | 0.00 | 22.03 | 22.05 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-18:30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 22.03 | 22.03 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.723344E+09 | 0.00 | 16.62 | 231075.29 | 31-AUG-06:10 | 0.00 | 22.03 | 23.36 | 0.00 | 0.00 | 0.00 | 0.06 | 31-AUG-06:10 |
September | 0.174101E+11 | 0.00 | 199.40 | 1390166.06 | 30-SEP-05:02 | 0.00 | 22.95 | 39.28 | 0.03 | 0.00 | 0.00 | 0.37 | 30-SEP-05:02 |
October | 0.157244E+12 | 0.00 | 450.93 | 1775038.87 | 30-OCT-05:03 | 0.00 | 25.12 | 58.81 | 0.28 | 0.00 | 0.02 | 0.48 | 30-OCT-05:03 |
November | 0.690225E+12 | 0.00 | 576.33 | 2118482.23 | 20-NOV-05:11 | 0.00 | 33.35 | 72.13 | 1.43 | 0.00 | 0.07 | 0.57 | 20-NOV-05:11 |
December | 0.998644E+12 | 0.00 | 636.03 | 2154705.88 | 12-DEC-05:01 | 0.00 | 34.89 | 74.98 | 2.04 | 0.00 | 0.10 | 0.58 | 12-DEC-05:01 |
Annual Sum or Average | 0.354527E+13 | 0.00 | 3827.41 | 0.00 | 26.86 | 49.24 | 0.60 | 0.00 | 0.03 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.03 | 22.03 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.998644E+12 | 0.00 | 636.03 | 2252308.03 | 0.00 | 34.89 | 74.98 | 2.04 | 0.00 | 0.10 | 0.61 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 18.51 | 18.51 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 19.06 | 19.06 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 19.74 | 19.74 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 20.42 | 20.42 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 19.08 | 19.08 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 21.02 | 21.02 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 23.89 | 23.89 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 23.83 | 23.83 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 18.86 | 18.86 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 19.23 | 19.23 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 19.55 | 19.55 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 19.99 | 19.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 20.28 | 20.28 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.51 | 18.51 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.89 | 23.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 9586464.64 | 0.00 | 33.98 | 9586464.64 | 0.00 | 0.00 | 0.00 | 0.00 | 2079.86 | 25-JAN-13:10 | 2079.86 | 25-JAN-13:10 | 0.00 | 0.00 | 0.00 |
February | 13494518.46 | 0.00 | 27.39 | 13494518.46 | 0.00 | 0.00 | 0.00 | 0.00 | 3101.22 | 15-FEB-13:10 | 3101.22 | 15-FEB-13:10 | 0.00 | 0.00 | 0.00 |
March | 30259552.66 | 0.00 | 22.80 | 30259552.66 | 0.00 | 0.00 | 0.00 | 0.00 | 10068.27 | 10-MAR-08:10 | 10068.27 | 10-MAR-08:10 | 0.00 | 0.00 | 0.00 |
April | 0.578487E+09 | 0.00 | 18.16 | 0.578487E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28324.15 | 20-APR-14:00 | 28324.15 | 20-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.168832E+11 | 0.00 | 182.54 | 0.168832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109158.11 | 31-MAY-16:00 | 109158.11 | 31-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.683985E+11 | 0.00 | 379.22 | 0.680896E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 172336.86 | 30-JUN-12:30 | 153054.96 | 30-JUN-12:30 | 0.00 | 0.00 | 0.00 |
July | 0.893731E+11 | 0.00 | 414.04 | 0.886538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 186033.75 | 03-JUL-15:00 | 168559.57 | 23-JUL-15:21 | 0.00 | 0.00 | 0.00 |
August | 0.541274E+11 | 0.00 | 317.95 | 0.540682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 158372.23 | 11-AUG-15:40 | 158372.23 | 11-AUG-15:40 | 0.00 | 0.00 | 0.00 |
September | 0.138768E+10 | 0.00 | 44.21 | 0.138768E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42931.95 | 07-SEP-16:00 | 42931.95 | 07-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 5304234.63 | 0.00 | 8.86 | 5304234.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2932.38 | 27-OCT-12:10 | 2932.38 | 27-OCT-12:10 | 0.00 | 0.00 | 0.00 |
November | 14741916.28 | 0.00 | 28.44 | 14741916.28 | 0.00 | 0.00 | 0.00 | 0.00 | 4453.13 | 03-NOV-07:10 | 4453.13 | 03-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 10090178.88 | 0.00 | 27.38 | 10090178.88 | 0.00 | 0.00 | 0.00 | 0.00 | 5494.26 | 27-DEC-08:20 | 5494.26 | 27-DEC-08:20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.230832E+12 | 0.00 | 1504.97 | 0.229744E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5304234.63 | 0.00 | 8.86 | 5304234.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2079.86 | 2079.86 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.893731E+11 | 0.00 | 414.04 | 0.886538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 186033.75 | 168559.57 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 14918794.93 | 0.00 | 13.52 | 14918794.93 | 0.00 | 0.00 | 0.00 | 0.00 | 1997.79 | 27-JAN-08:50 | 1997.79 | 27-JAN-08:50 | 0.00 | 0.00 | 0.00 |
February | 25649979.51 | 0.00 | 18.99 | 25649979.51 | 0.00 | 0.00 | 0.00 | 0.00 | 4517.53 | 15-FEB-13:10 | 4517.53 | 15-FEB-13:10 | 0.00 | 0.00 | 0.00 |
March | 50228917.25 | 0.00 | 21.30 | 50228917.25 | 0.00 | 0.00 | 0.00 | 0.00 | 9582.80 | 30-MAR-12:10 | 9582.80 | 30-MAR-12:10 | 0.00 | 0.00 | 0.00 |
April | 0.167150E+10 | 0.00 | 11.56 | 0.167150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 139608.60 | 20-APR-14:00 | 139608.60 | 20-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.101219E+12 | 0.00 | 156.98 | 0.101219E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 829838.00 | 31-MAY-16:00 | 829838.00 | 31-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.428630E+12 | 0.00 | 334.91 | 0.427585E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1251518.97 | 30-JUN-12:30 | 1174807.84 | 29-JUN-14:30 | 0.00 | 0.00 | 0.00 |
July | 0.548012E+12 | 0.00 | 352.86 | 0.546650E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1387216.86 | 23-JUL-14:51 | 1387216.86 | 23-JUL-14:51 | 0.00 | 0.00 | 0.00 |
August | 0.295956E+12 | 0.00 | 257.46 | 0.295956E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1202756.10 | 11-AUG-15:40 | 1202756.10 | 11-AUG-15:40 | 0.00 | 0.00 | 0.00 |
September | 0.605070E+10 | 0.00 | 30.71 | 0.605070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 244463.46 | 07-SEP-16:00 | 244463.46 | 07-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 15924748.62 | 0.00 | 7.60 | 15924748.62 | 0.00 | 0.00 | 0.00 | 0.00 | 4885.28 | 26-OCT-12:00 | 4885.28 | 26-OCT-12:00 | 0.00 | 0.00 | 0.00 |
November | 27641483.67 | 0.00 | 18.89 | 27641483.67 | 0.00 | 0.00 | 0.00 | 0.00 | 3445.18 | 08-NOV-12:20 | 3445.18 | 08-NOV-12:20 | 0.00 | 0.00 | 0.00 |
December | 9780393.10 | 0.00 | 8.42 | 9780393.10 | 0.00 | 0.00 | 0.00 | 0.00 | 1096.57 | 21-DEC-09:00 | 1096.57 | 21-DEC-09:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.138168E+13 | 0.00 | 1233.20 | 0.137928E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9780393.10 | 0.00 | 7.60 | 9780393.10 | 0.00 | 0.00 | 0.00 | 0.00 | 1096.57 | 1096.57 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.548012E+12 | 0.00 | 352.86 | 0.546650E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1387216.86 | 1387216.86 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 512535.41 | 0.00 | 3.36 | 512535.41 | 0.00 | 0.00 | 0.00 | 0.00 | 448.31 | 09-JAN-05:45 | 448.31 | 09-JAN-05:45 | 0.00 | 0.00 | 0.00 |
February | 1558701.44 | 0.00 | 5.54 | 1558701.44 | 0.00 | 0.00 | 0.00 | 0.00 | 934.94 | 25-FEB-05:32 | 934.94 | 25-FEB-05:32 | 0.00 | 0.00 | 0.00 |
March | 6377036.16 | 0.00 | 6.69 | 6377036.16 | 0.00 | 0.00 | 0.00 | 0.00 | 705.18 | 03-MAR-12:00 | 705.18 | 03-MAR-12:00 | 0.00 | 0.00 | 0.00 |
April | 74219555.14 | 0.00 | 8.45 | 74219555.14 | 0.00 | 0.00 | 0.00 | 0.00 | 9979.75 | 20-APR-14:00 | 9979.75 | 20-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.977131E+10 | 0.00 | 151.21 | 0.977131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89081.03 | 31-MAY-16:00 | 89081.03 | 31-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.439538E+11 | 0.00 | 330.07 | 0.438385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 139421.47 | 30-JUN-12:30 | 132922.57 | 20-JUN-15:30 | 0.00 | 0.00 | 0.00 |
July | 0.562469E+11 | 0.00 | 349.73 | 0.561239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 136968.12 | 21-JUL-14:40 | 136968.12 | 21-JUL-14:40 | 0.00 | 0.00 | 0.00 |
August | 0.295228E+11 | 0.00 | 252.47 | 0.295228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 129943.92 | 11-AUG-15:40 | 129943.92 | 11-AUG-15:40 | 0.00 | 0.00 | 0.00 |
September | 0.490260E+09 | 0.00 | 27.82 | 0.490260E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22688.84 | 10-SEP-12:02 | 22688.84 | 10-SEP-12:02 | 0.00 | 0.00 | 0.00 |
October | 399195.64 | 0.00 | 2.22 | 399195.64 | 0.00 | 0.00 | 0.00 | 0.00 | 267.95 | 03-OCT-09:20 | 267.95 | 03-OCT-09:20 | 0.00 | 0.00 | 0.00 |
November | 127710.23 | 0.00 | 1.33 | 127710.23 | 0.00 | 0.00 | 0.00 | 0.00 | 58.62 | 04-NOV-11:20 | 58.62 | 04-NOV-11:20 | 0.00 | 0.00 | 0.00 |
December | 240975.64 | 0.00 | 1.67 | 240975.64 | 0.00 | 0.00 | 0.00 | 0.00 | 163.36 | 23-DEC-07:20 | 163.36 | 23-DEC-07:20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140068E+12 | 0.00 | 1140.57 | 0.139830E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 127710.23 | 0.00 | 1.33 | 127710.23 | 0.00 | 0.00 | 0.00 | 0.00 | 58.62 | 58.62 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.562469E+11 | 0.00 | 349.73 | 0.561239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 139421.47 | 136968.12 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 70858661.12 | 0.00 | 21.37 | 70858661.12 | 0.00 | 0.00 | 0.00 | 0.00 | 6696.26 | 19-JAN-17:30 | 6696.26 | 19-JAN-17:30 | 0.00 | 0.00 | 0.00 |
February | 0.181775E+09 | 0.00 | 24.97 | 0.181775E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29281.81 | 17-FEB-08:30 | 29281.81 | 17-FEB-08:30 | 0.00 | 0.00 | 0.00 |
March | 0.256117E+09 | 0.00 | 31.46 | 0.256117E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13402.31 | 28-MAR-07:20 | 13402.31 | 28-MAR-07:20 | 0.00 | 0.00 | 0.00 |
April | 40813055.79 | 0.00 | 4.20 | 40813055.79 | 0.00 | 0.00 | 0.00 | 0.00 | 23484.21 | 04-APR-06:15 | 23484.21 | 04-APR-06:15 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 |
October | 92631131.71 | 0.00 | 9.44 | 92518681.68 | 0.00 | 0.00 | 0.00 | 0.00 | 21273.00 | 25-OCT-06:15 | 21273.00 | 25-OCT-06:15 | 0.00 | 0.00 | 0.00 |
November | 0.259505E+09 | 0.00 | 28.80 | 0.259505E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29920.80 | 07-NOV-10:00 | 29920.80 | 07-NOV-10:00 | 0.00 | 0.00 | 0.00 |
December | 0.140921E+09 | 0.00 | 16.33 | 0.140921E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27757.46 | 27-DEC-13:10 | 27757.46 | 27-DEC-13:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104262E+10 | 0.00 | 136.56 | 0.104251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.259505E+09 | 0.00 | 31.46 | 0.259505E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29920.80 | 29920.80 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.629782E+10 | 0.466576E+10 | 744.00 | 0.589690E+10 | 0.400925E+09 | 0.00 | 0.02 | 19-JAN-05:01 | 0.01 | 12-JAN-08:10 | 2792.30 | 19-JAN-05:01 | 2635.12 | 19-JAN-05:01 | 173.65 | 26-JAN-22:02 | 2253.09 | 31-JAN-18:40 | 0.00 |
February | 0.107595E+11 | 0.570478E+10 | 672.00 | 0.976845E+10 | 0.991001E+09 | 0.00 | 0.03 | 08-FEB-15:00 | 0.02 | 27-FEB-08:10 | 5434.58 | 08-FEB-22:00 | 5057.64 | 10-FEB-16:00 | 441.36 | 13-FEB-20:00 | 3271.81 | 08-FEB-15:00 | 0.00 |
March | 0.145409E+11 | 0.734457E+10 | 744.00 | 0.140976E+11 | 0.443351E+09 | 0.00 | 0.03 | 28-MAR-13:40 | 0.02 | 19-MAR-12:53 | 6072.83 | 21-MAR-17:30 | 5492.85 | 31-MAR-23:10 | 802.10 | 21-MAR-17:20 | 3512.54 | 28-MAR-13:40 | 0.00 |
April | 0.159161E+11 | 0.807265E+10 | 720.00 | 0.158432E+11 | 72957064.56 | 0.00 | 0.21 | 22-APR-14:00 | 0.02 | 30-APR-23:20 | 69320.50 | 22-APR-14:00 | 69320.50 | 22-APR-14:00 | 712.26 | 30-APR-08:00 | 22875.42 | 22-APR-14:00 | 0.00 |
May | 0.951385E+10 | 0.556888E+10 | 744.00 | 0.917674E+10 | 0.337118E+09 | 0.00 | 0.02 | 31-MAY-16:00 | 0.01 | 16-MAY-20:00 | 4933.34 | 28-MAY-19:22 | 4889.92 | 14-MAY-14:22 | 416.28 | 31-MAY-23:15 | 2848.53 | 31-MAY-16:00 | 0.00 |
June | 0.506191E+11 | 0.190431E+11 | 589.26 | 0.472731E+11 | 0.334604E+10 | 0.00 | 0.56 | 30-JUN-13:30 | 0.00 | 02-JUN-22:47 | 254909.00 | 30-JUN-12:00 | 227824.09 | 30-JUN-15:00 | 70735.66 | 30-JUN-12:00 | 80754.16 | 30-JUN-13:30 | 0.00 |
July | 0.208474E+12 | 0.660920E+11 | 522.84 | 0.173798E+12 | 0.346756E+11 | 0.00 | 0.83 | 29-JUL-18:22 | 0.00 | 02-JUL-17:53 | 389239.87 | 29-JUL-18:22 | 322719.59 | 21-JUL-14:30 | 131133.90 | 03-JUL-15:00 | 121718.25 | 29-JUL-18:30 | 0.00 |
August | 0.256277E+12 | 0.760357E+11 | 619.61 | 0.198786E+12 | 0.574916E+11 | 0.00 | 0.86 | 11-AUG-17:00 | 0.00 | 09-AUG-23:23 | 377248.02 | 23-AUG-16:00 | 372123.05 | 11-AUG-16:00 | 129890.30 | 03-AUG-15:00 | 122777.00 | 11-AUG-17:00 | 0.00 |
September | 0.516386E+10 | 0.423709E+10 | 707.89 | 0.480293E+10 | 0.360931E+09 | 0.00 | 0.02 | 07-SEP-15:50 | 0.00 | 03-SEP-15:23 | 4926.11 | 07-SEP-15:50 | 4865.74 | 07-SEP-15:50 | 430.66 | 30-SEP-24:00 | 2456.91 | 07-SEP-15:50 | 0.00 |
October | 0.123142E+11 | 0.643045E+10 | 744.00 | 0.112863E+11 | 0.102793E+10 | 0.00 | 0.03 | 31-OCT-23:10 | 0.01 | 02-OCT-11:00 | 5863.04 | 31-OCT-23:10 | 5287.39 | 31-OCT-23:10 | 575.65 | 31-OCT-23:10 | 3274.29 | 14-OCT-11:00 | 0.00 |
November | 0.145205E+11 | 0.718898E+10 | 720.00 | 0.136371E+11 | 0.883418E+09 | 0.00 | 0.03 | 04-NOV-07:40 | 0.02 | 01-NOV-03:15 | 6083.34 | 27-NOV-05:43 | 5296.64 | 04-NOV-17:25 | 815.24 | 27-NOV-05:53 | 3487.58 | 04-NOV-07:40 | 0.00 |
December | 0.147717E+11 | 0.769559E+10 | 744.00 | 0.146701E+11 | 0.101622E+09 | 0.00 | 0.03 | 26-DEC-13:10 | 0.03 | 01-DEC-01:23 | 6287.23 | 01-DEC-00:10 | 5508.34 | 24-DEC-22:33 | 798.54 | 01-DEC-00:10 | 3699.64 | 26-DEC-13:10 | 0.00 |
Annual Sum or Average | 0.619169E+12 | 0.218080E+12 | 8271.61 | 0.519036E+12 | 0.100132E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.516386E+10 | 0.423709E+10 | 522.84 | 0.480293E+10 | 72957064.56 | 0.00 | 0.02 | 0.00 | 2792.30 | 2635.12 | 173.65 | 2253.09 | 0.00 | ||||||
Maximum of Months | 0.256277E+12 | 0.760357E+11 | 744.00 | 0.198786E+12 | 0.574916E+11 | 0.00 | 0.86 | 0.03 | 389239.87 | 372123.05 | 131133.90 | 122777.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.179336E+10 | 0.550069E+09 | 717.91 | 0.179336E+10 | 0.00 | 0.00 | 0.18 | 12-JAN-22:03 | 0.00 | 02-JAN-07:05 | 1306.70 | 22-JAN-15:20 | 1306.70 | 22-JAN-15:20 | 0.00 | 02-JAN-06:17 | 378.94 | 12-JAN-22:03 | 0.00 |
February | 0.710200E+10 | 0.190215E+10 | 672.00 | 0.710200E+10 | -0.0 | 0.00 | 0.46 | 26-FEB-16:23 | 0.21 | 27-FEB-07:03 | 3690.46 | 09-FEB-16:00 | 3690.46 | 09-FEB-16:00 | 0.00 | 09-FEB-16:40 | 970.23 | 26-FEB-16:23 | 0.00 |
March | 0.141141E+11 | 0.355193E+10 | 744.00 | 0.141141E+11 | -0.0 | 0.00 | 0.85 | 31-MAR-24:00 | 0.48 | 01-MAR-07:02 | 7412.03 | 31-MAR-24:00 | 7412.03 | 31-MAR-24:00 | 0.00 | 24-MAR-04:24 | 1813.40 | 31-MAR-24:00 | 0.00 |
April | 0.200160E+11 | 0.472054E+10 | 720.00 | 0.200160E+11 | 0.00 | 0.00 | 1.00 | 01-APR-18:22 | 0.32 | 30-APR-23:57 | 9375.21 | 22-APR-19:00 | 9375.21 | 22-APR-19:00 | 0.00 | 01-APR-19:07 | 2138.31 | 22-APR-19:00 | 0.00 |
May | 0.605933E+10 | 0.156891E+10 | 744.00 | 0.605918E+10 | 148731.45 | 0.00 | 0.46 | 31-MAY-23:20 | 0.18 | 27-MAY-07:00 | 4138.94 | 31-MAY-23:20 | 4138.94 | 31-MAY-23:20 | 16.07 | 16-MAY-16:10 | 996.47 | 31-MAY-23:20 | 0.00 |
June | 0.111055E+11 | 0.274112E+10 | 720.00 | 0.110273E+11 | 78176129.06 | 0.00 | 0.64 | 30-JUN-23:42 | 0.42 | 01-JUN-06:10 | 6084.47 | 30-JUN-23:42 | 6075.38 | 30-JUN-23:42 | 248.44 | 27-JUN-16:00 | 1577.93 | 30-JUN-15:00 | 0.00 |
July | 0.166860E+11 | 0.407352E+10 | 744.00 | 0.165240E+11 | 0.161970E+09 | 0.00 | 0.82 | 31-JUL-23:13 | 0.61 | 01-JUL-06:10 | 8017.31 | 31-JUL-23:45 | 7993.30 | 31-JUL-23:35 | 350.85 | 26-JUL-15:00 | 2248.30 | 21-JUL-16:00 | 0.00 |
August | 0.214937E+11 | 0.495666E+10 | 744.00 | 0.213607E+11 | 0.132994E+09 | 0.00 | 0.96 | 27-AUG-18:45 | 0.32 | 31-AUG-23:55 | 9396.50 | 27-AUG-18:45 | 9396.50 | 27-AUG-18:45 | 274.12 | 03-AUG-14:00 | 2586.21 | 11-AUG-18:00 | 0.00 |
September | 0.534581E+10 | 0.137015E+10 | 720.00 | 0.532904E+10 | 16768927.56 | 0.00 | 0.46 | 30-SEP-24:00 | 0.14 | 30-SEP-07:00 | 3850.03 | 30-SEP-24:00 | 3850.03 | 30-SEP-24:00 | 100.15 | 05-SEP-15:40 | 981.81 | 30-SEP-24:00 | 0.00 |
October | 0.943756E+10 | 0.240096E+10 | 744.00 | 0.943733E+10 | 228722.19 | 0.00 | 0.61 | 31-OCT-24:00 | 0.30 | 31-OCT-06:10 | 5136.06 | 31-OCT-24:00 | 5136.06 | 31-OCT-24:00 | 40.34 | 02-OCT-16:10 | 1302.73 | 31-OCT-24:00 | 0.00 |
November | 0.126365E+11 | 0.324915E+10 | 720.00 | 0.126365E+11 | 0.00 | 0.00 | 0.67 | 19-NOV-15:23 | 0.49 | 27-NOV-07:02 | 5631.81 | 19-NOV-15:30 | 5631.81 | 19-NOV-15:30 | 0.00 | 22-NOV-00:50 | 1426.31 | 19-NOV-15:23 | 0.00 |
December | 0.179509E+11 | 0.447028E+10 | 744.00 | 0.179509E+11 | -0.0 | 0.00 | 0.83 | 24-DEC-13:00 | 0.70 | 15-DEC-07:02 | 7436.95 | 24-DEC-17:55 | 7436.95 | 24-DEC-17:55 | 0.00 | 05-DEC-02:42 | 1779.91 | 24-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.143741E+12 | 0.355554E+11 | 8733.91 | 0.143350E+12 | 0.390287E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.179336E+10 | 0.550069E+09 | 672.00 | 0.179336E+10 | -0.0 | 0.00 | 0.18 | 0.00 | 1306.70 | 1306.70 | 0.00 | 378.94 | 0.00 | ||||||
Maximum of Months | 0.214937E+11 | 0.495666E+10 | 744.00 | 0.213607E+11 | 0.161970E+09 | 0.00 | 1.00 | 0.70 | 9396.50 | 9396.50 | 350.85 | 2586.21 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.928658E+09 | 0.363012E+09 | 138.86 | 0.928658E+09 | -0.0 | 0.00 | 0.11 | 27-JAN-22:03 | 0.00 | 01-JAN-00:02 | 7386.05 | 27-JAN-22:03 | 7386.05 | 27-JAN-22:03 | 0.00 | 06-JAN-12:20 | 2229.87 | 27-JAN-22:03 | 0.00 |
February | 0.437331E+11 | 0.121618E+11 | 672.00 | 0.437331E+11 | -0.0 | 0.00 | 0.40 | 16-FEB-16:05 | 0.03 | 27-FEB-07:03 | 31338.55 | 16-FEB-16:15 | 31338.55 | 16-FEB-16:15 | 0.00 | 09-FEB-22:30 | 8589.91 | 10-FEB-16:10 | 0.00 |
March | 0.113490E+12 | 0.291645E+11 | 744.00 | 0.113490E+12 | -0.0 | 0.00 | 0.79 | 31-MAR-23:20 | 0.35 | 01-MAR-07:02 | 65523.05 | 31-MAR-23:20 | 65523.05 | 31-MAR-23:20 | 0.00 | 17-MAR-03:04 | 16228.06 | 31-MAR-23:20 | 0.00 |
April | 0.179448E+12 | 0.427271E+11 | 720.00 | 0.179448E+12 | -0.0 | 0.00 | 0.98 | 22-APR-18:50 | 0.24 | 30-APR-23:57 | 88363.53 | 20-APR-19:00 | 88363.53 | 20-APR-19:00 | 0.00 | 11-APR-07:15 | 20230.27 | 22-APR-18:50 | 0.00 |
May | 0.502783E+11 | 0.131778E+11 | 744.00 | 0.502767E+11 | 1632682.49 | 0.00 | 0.45 | 31-MAY-24:00 | 0.11 | 27-MAY-07:00 | 38293.49 | 31-MAY-24:00 | 38293.49 | 31-MAY-24:00 | 183.24 | 16-MAY-16:10 | 9258.70 | 31-MAY-24:00 | 0.00 |
June | 0.102039E+12 | 0.253217E+11 | 720.00 | 0.101266E+12 | 0.773460E+09 | 0.00 | 0.63 | 30-JUN-23:32 | 0.39 | 24-JUN-17:00 | 57352.04 | 30-JUN-23:20 | 57213.43 | 30-JUN-23:55 | 2460.19 | 27-JUN-16:00 | 14842.51 | 30-JUN-15:00 | 0.00 |
July | 0.154957E+12 | 0.380155E+11 | 744.00 | 0.153354E+12 | 0.160361E+10 | 0.00 | 0.82 | 31-JUL-23:07 | 0.58 | 06-JUL-06:10 | 76605.14 | 31-JUL-23:03 | 76279.64 | 31-JUL-23:27 | 3460.34 | 26-JUL-15:00 | 21139.20 | 21-JUL-16:00 | 0.00 |
August | 0.199610E+12 | 0.462891E+11 | 744.00 | 0.198288E+12 | 0.132180E+10 | 0.00 | 0.93 | 10-AUG-19:00 | 0.24 | 31-AUG-23:55 | 85636.62 | 27-AUG-18:50 | 85636.62 | 27-AUG-18:50 | 2716.92 | 03-AUG-14:00 | 24500.29 | 11-AUG-18:10 | 0.00 |
September | 0.377551E+11 | 0.991433E+10 | 720.00 | 0.375961E+11 | 0.158986E+09 | 0.00 | 0.36 | 30-SEP-23:40 | 0.05 | 30-SEP-07:00 | 28991.18 | 02-SEP-18:10 | 28991.18 | 02-SEP-18:10 | 995.06 | 05-SEP-15:40 | 7486.85 | 30-SEP-23:40 | 0.00 |
October | 0.675603E+11 | 0.176516E+11 | 744.00 | 0.675577E+11 | 2604270.09 | 0.00 | 0.51 | 31-OCT-23:20 | 0.14 | 30-OCT-06:10 | 40222.15 | 31-OCT-23:20 | 40222.15 | 31-OCT-23:20 | 398.79 | 02-OCT-16:00 | 10435.22 | 31-OCT-23:20 | 0.00 |
November | 0.916625E+11 | 0.243056E+11 | 720.00 | 0.916625E+11 | 0.00 | 0.00 | 0.59 | 08-NOV-15:50 | 0.30 | 27-NOV-07:02 | 47418.25 | 08-NOV-15:50 | 47418.25 | 08-NOV-15:50 | 0.00 | 02-NOV-17:00 | 12641.44 | 08-NOV-16:40 | 0.00 |
December | 0.138304E+12 | 0.354493E+11 | 744.00 | 0.138304E+12 | 0.00 | 0.00 | 0.74 | 22-DEC-22:02 | 0.55 | 04-DEC-07:10 | 60177.58 | 29-DEC-22:06 | 60177.58 | 29-DEC-22:06 | 0.00 | 30-DEC-23:05 | 15111.14 | 22-DEC-22:02 | 0.00 |
Annual Sum or Average | 0.117977E+13 | 0.294541E+12 | 8154.86 | 0.117590E+13 | 0.386209E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.928658E+09 | 0.363012E+09 | 138.86 | 0.928658E+09 | -0.0 | 0.00 | 0.11 | 0.00 | 7386.05 | 7386.05 | 0.00 | 2229.87 | 0.00 | ||||||
Maximum of Months | 0.199610E+12 | 0.462891E+11 | 744.00 | 0.198288E+12 | 0.160361E+10 | 0.00 | 0.98 | 0.58 | 88363.53 | 88363.53 | 3460.34 | 24500.29 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 448256.29 | 259304.56 | 1.83 | 448256.29 | 0.00 | 0.00 | 0.02 | 19-JAN-17:00 | 0.00 | 01-JAN-00:02 | 94.05 | 19-JAN-17:00 | 94.05 | 19-JAN-17:00 | 0.00 | 19-JAN-16:50 | 46.35 | 19-JAN-17:00 | 0.00 |
February | 0.257430E+10 | 0.730865E+09 | 576.31 | 0.257430E+10 | 0.00 | 0.00 | 0.34 | 15-FEB-16:10 | 0.00 | 01-FEB-00:03 | 2770.26 | 09-FEB-16:00 | 2770.26 | 09-FEB-16:00 | 0.00 | 10-FEB-00:40 | 704.42 | 15-FEB-16:10 | 0.00 |
March | 0.925383E+10 | 0.241851E+10 | 744.00 | 0.925383E+10 | -0.0 | 0.00 | 0.69 | 31-MAR-23:10 | 0.22 | 06-MAR-04:12 | 5703.17 | 31-MAR-23:10 | 5703.17 | 31-MAR-23:10 | 0.00 | 10-MAR-06:04 | 1438.88 | 31-MAR-23:10 | 0.00 |
April | 0.165600E+11 | 0.398076E+10 | 720.00 | 0.165600E+11 | 0.00 | 0.00 | 0.96 | 22-APR-18:50 | 0.18 | 30-APR-23:53 | 8829.35 | 20-APR-19:00 | 8829.35 | 20-APR-19:00 | 0.00 | 16-APR-10:45 | 2002.34 | 22-APR-18:50 | 0.00 |
May | 0.447580E+10 | 0.118322E+10 | 744.00 | 0.447565E+10 | 151235.69 | 0.00 | 0.44 | 31-MAY-23:40 | 0.04 | 27-MAY-06:10 | 3774.27 | 31-MAY-23:40 | 3774.27 | 31-MAY-23:40 | 17.50 | 16-MAY-16:10 | 914.51 | 31-MAY-23:40 | 0.00 |
June | 0.100391E+11 | 0.249884E+10 | 720.00 | 0.996187E+10 | 77253277.16 | 0.00 | 0.62 | 30-JUN-23:20 | 0.34 | 25-JUN-05:00 | 5704.56 | 30-JUN-23:20 | 5684.53 | 30-JUN-23:32 | 246.20 | 27-JUN-16:00 | 1502.52 | 30-JUN-15:00 | 0.00 |
July | 0.153538E+11 | 0.377769E+10 | 744.00 | 0.151936E+11 | 0.160202E+09 | 0.00 | 0.81 | 31-JUL-23:07 | 0.54 | 06-JUL-06:10 | 7631.56 | 31-JUL-23:03 | 7597.09 | 31-JUL-23:17 | 345.91 | 26-JUL-15:00 | 2136.53 | 21-JUL-16:00 | 0.00 |
August | 0.196186E+11 | 0.456728E+10 | 744.00 | 0.194866E+11 | 0.131995E+09 | 0.00 | 0.92 | 10-AUG-19:00 | 0.20 | 31-AUG-23:55 | 8596.72 | 27-AUG-18:50 | 8596.72 | 27-AUG-18:50 | 271.71 | 03-AUG-14:00 | 2465.13 | 11-AUG-18:10 | 0.00 |
September | 0.252942E+10 | 0.680380E+09 | 678.76 | 0.251438E+10 | 15040309.35 | 0.00 | 0.32 | 02-SEP-18:10 | 0.00 | 05-SEP-05:55 | 2751.03 | 02-SEP-18:10 | 2751.03 | 02-SEP-18:10 | 100.53 | 05-SEP-15:50 | 677.06 | 02-SEP-18:10 | 0.00 |
October | 0.452236E+10 | 0.121102E+10 | 728.86 | 0.452213E+10 | 228721.21 | 0.00 | 0.42 | 31-OCT-23:10 | 0.00 | 09-OCT-22:15 | 3669.67 | 03-OCT-16:00 | 3669.67 | 03-OCT-16:00 | 36.17 | 02-OCT-16:10 | 884.18 | 03-OCT-16:00 | 0.00 |
November | 0.703620E+10 | 0.190648E+10 | 720.00 | 0.703620E+10 | 0.00 | 0.00 | 0.54 | 08-NOV-15:50 | 0.17 | 27-NOV-03:50 | 4306.80 | 08-NOV-15:50 | 4306.80 | 08-NOV-15:50 | 0.00 | 10-NOV-10:20 | 1112.30 | 08-NOV-15:50 | 0.00 |
December | 0.118247E+11 | 0.308279E+10 | 744.00 | 0.118247E+11 | -0.0 | 0.00 | 0.68 | 20-DEC-22:02 | 0.41 | 26-DEC-04:03 | 5657.82 | 19-DEC-22:05 | 5657.82 | 19-DEC-22:05 | 0.00 | 28-DEC-05:46 | 1406.51 | 19-DEC-22:03 | 0.00 |
Annual Sum or Average | 0.103789E+12 | 0.260381E+11 | 7865.77 | 0.103404E+12 | 0.384871E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 448256.29 | 259304.56 | 1.83 | 448256.29 | -0.0 | 0.00 | 0.02 | 0.00 | 94.05 | 94.05 | 0.00 | 46.35 | 0.00 | ||||||
Maximum of Months | 0.196186E+11 | 0.456728E+10 | 744.00 | 0.194866E+11 | 0.160202E+09 | 0.00 | 0.96 | 0.54 | 8829.35 | 8829.35 | 345.91 | 2465.13 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.86 | 0.00 | 16.86 | 0.00 | 1229.81 | 0.00 | 0.00 | 0.00 |
February | 74.51 | 0.00 | 74.51 | 0.00 | 1116.55 | 0.00 | 0.00 | 0.00 |
March | 199.28 | 0.00 | 199.28 | 11.29 | 848.43 | 0.00 | 0.00 | 0.00 |
April | 360.60 | 7.99 | 352.61 | 122.19 | 473.79 | 0.00 | 0.00 | 0.00 |
May | 552.81 | 88.07 | 464.74 | 393.34 | 207.51 | 0.00 | 0.00 | 0.00 |
June | 721.16 | 160.51 | 560.65 | 671.38 | 97.26 | 0.00 | 0.00 | 0.00 |
July | 605.27 | 98.51 | 506.76 | 571.54 | 118.71 | 0.00 | 0.00 | 0.00 |
August | 386.47 | 21.68 | 364.80 | 289.21 | 200.95 | 0.00 | 0.00 | 0.00 |
September | 215.56 | 0.22 | 215.35 | 65.19 | 422.45 | 0.00 | 0.00 | 0.00 |
October | 104.89 | 0.00 | 104.89 | 3.10 | 759.13 | 0.00 | 0.00 | 0.00 |
November | 32.55 | 0.00 | 32.55 | 0.00 | 1225.33 | 0.00 | 0.00 | 0.00 |
December | 5.11 | 0.00 | 5.11 | 0.00 | 1312.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 273.90 | 31.55 | 242.35 | 178.32 | 665.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 5.11 | 0.00 | 5.11 | 0.00 | 97.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 721.16 | 160.51 | 560.65 | 671.38 | 1312.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.86 | 0.00 | 16.86 | 0.00 | 1229.81 | 0.00 | 0.00 | 0.00 |
February | 74.51 | 0.00 | 74.51 | 0.00 | 1116.55 | 0.00 | 0.00 | 0.00 |
March | 199.28 | 0.00 | 199.28 | 11.29 | 848.43 | 0.00 | 0.00 | 0.00 |
April | 360.60 | 7.99 | 352.61 | 122.19 | 473.79 | 0.00 | 0.00 | 0.00 |
May | 552.81 | 88.07 | 464.74 | 393.34 | 207.51 | 0.00 | 0.00 | 0.00 |
June | 721.16 | 160.51 | 560.65 | 671.38 | 97.26 | 0.00 | 0.00 | 0.00 |
July | 605.27 | 98.51 | 506.76 | 571.54 | 118.71 | 0.00 | 0.00 | 0.00 |
August | 386.47 | 21.68 | 364.80 | 289.21 | 200.95 | 0.00 | 0.00 | 0.00 |
September | 215.56 | 0.22 | 215.35 | 65.19 | 422.45 | 0.00 | 0.00 | 0.00 |
October | 104.89 | 0.00 | 104.89 | 3.10 | 759.13 | 0.00 | 0.00 | 0.00 |
November | 32.55 | 0.00 | 32.55 | 0.00 | 1225.33 | 0.00 | 0.00 | 0.00 |
December | 5.11 | 0.00 | 5.11 | 0.00 | 1312.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 273.90 | 31.55 | 242.35 | 178.32 | 665.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 5.11 | 0.00 | 5.11 | 0.00 | 97.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 721.16 | 160.51 | 560.65 | 671.38 | 1312.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.86 | 0.00 | 16.86 | 0.00 | 1229.81 | 0.00 | 0.00 | 0.00 |
February | 74.51 | 0.00 | 74.51 | 0.00 | 1116.55 | 0.00 | 0.00 | 0.00 |
March | 199.28 | 0.00 | 199.28 | 11.29 | 848.43 | 0.00 | 0.00 | 0.00 |
April | 360.60 | 7.99 | 352.61 | 122.19 | 473.79 | 0.00 | 0.00 | 0.00 |
May | 552.81 | 88.07 | 464.74 | 393.34 | 207.51 | 0.00 | 0.00 | 0.00 |
June | 721.16 | 160.51 | 560.65 | 671.38 | 97.26 | 0.00 | 0.00 | 0.00 |
July | 605.27 | 98.51 | 506.76 | 571.54 | 118.71 | 0.00 | 0.00 | 0.00 |
August | 386.47 | 21.68 | 364.80 | 289.21 | 200.95 | 0.00 | 0.00 | 0.00 |
September | 215.56 | 0.22 | 215.35 | 65.19 | 422.45 | 0.00 | 0.00 | 0.00 |
October | 104.89 | 0.00 | 104.89 | 3.10 | 759.13 | 0.00 | 0.00 | 0.00 |
November | 32.55 | 0.00 | 32.55 | 0.00 | 1225.33 | 0.00 | 0.00 | 0.00 |
December | 5.11 | 0.00 | 5.11 | 0.00 | 1312.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 273.90 | 31.55 | 242.35 | 178.32 | 665.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 5.11 | 0.00 | 5.11 | 0.00 | 97.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 721.16 | 160.51 | 560.65 | 671.38 | 1312.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.86 | 0.00 | 16.86 | 0.00 | 1229.81 | 0.00 | 0.00 | 0.00 |
February | 74.51 | 0.00 | 74.51 | 0.00 | 1116.55 | 0.00 | 0.00 | 0.00 |
March | 199.28 | 0.00 | 199.28 | 11.29 | 848.43 | 0.00 | 0.00 | 0.00 |
April | 360.60 | 7.99 | 352.61 | 122.19 | 473.79 | 0.00 | 0.00 | 0.00 |
May | 552.81 | 88.07 | 464.74 | 393.34 | 207.51 | 0.00 | 0.00 | 0.00 |
June | 721.16 | 160.51 | 560.65 | 671.38 | 97.26 | 0.00 | 0.00 | 0.00 |
July | 605.27 | 98.51 | 506.76 | 571.54 | 118.71 | 0.00 | 0.00 | 0.00 |
August | 386.47 | 21.68 | 364.80 | 289.21 | 200.95 | 0.00 | 0.00 | 0.00 |
September | 215.56 | 0.22 | 215.35 | 65.19 | 422.45 | 0.00 | 0.00 | 0.00 |
October | 104.89 | 0.00 | 104.89 | 3.10 | 759.13 | 0.00 | 0.00 | 0.00 |
November | 32.55 | 0.00 | 32.55 | 0.00 | 1225.33 | 0.00 | 0.00 | 0.00 |
December | 5.11 | 0.00 | 5.11 | 0.00 | 1312.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 273.90 | 31.55 | 242.35 | 178.32 | 665.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 5.11 | 0.00 | 5.11 | 0.00 | 97.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 721.16 | 160.51 | 560.65 | 671.38 | 1312.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 16.85 | 0.00 | 16.85 | 0.00 | 1229.76 | 0.00 | 0.00 | 0.00 |
February | 74.51 | 0.00 | 74.51 | 0.00 | 1116.51 | 0.00 | 0.00 | 0.00 |
March | 199.27 | 0.00 | 199.27 | 11.29 | 848.39 | 0.00 | 0.00 | 0.00 |
April | 360.58 | 7.99 | 352.60 | 122.18 | 473.77 | 0.00 | 0.00 | 0.00 |
May | 552.79 | 88.06 | 464.72 | 393.33 | 207.50 | 0.00 | 0.00 | 0.00 |
June | 721.13 | 160.50 | 560.62 | 671.35 | 97.25 | 0.00 | 0.00 | 0.00 |
July | 605.25 | 98.51 | 506.74 | 571.52 | 118.71 | 0.00 | 0.00 | 0.00 |
August | 386.46 | 21.68 | 364.78 | 289.20 | 200.94 | 0.00 | 0.00 | 0.00 |
September | 215.56 | 0.22 | 215.34 | 65.19 | 422.43 | 0.00 | 0.00 | 0.00 |
October | 104.89 | 0.00 | 104.89 | 3.10 | 759.09 | 0.00 | 0.00 | 0.00 |
November | 32.55 | 0.00 | 32.55 | 0.00 | 1225.28 | 0.00 | 0.00 | 0.00 |
December | 5.11 | 0.00 | 5.11 | 0.00 | 1312.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 273.89 | 31.55 | 242.34 | 178.31 | 665.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 5.11 | 0.00 | 5.11 | 0.00 | 97.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 721.13 | 160.50 | 560.62 | 671.35 | 1312.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.39 | 15.58 | 33.81 | 4.30 | 1319.32 | 0.00 | 0.00 | 0.00 |
February | 272.70 | 130.19 | 142.51 | 135.92 | 1116.07 | 0.00 | 0.00 | 0.00 |
March | 777.34 | 393.58 | 383.76 | 625.33 | 835.62 | 0.00 | 0.00 | 0.00 |
April | 1068.36 | 540.31 | 528.05 | 942.00 | 469.47 | 0.00 | 0.00 | 0.00 |
May | 1551.79 | 873.26 | 678.53 | 1635.82 | 247.61 | 0.00 | 0.00 | 0.00 |
June | 1427.98 | 665.06 | 762.92 | 1559.13 | 120.78 | 0.00 | 0.00 | 0.00 |
July | 1356.30 | 656.57 | 699.73 | 1516.61 | 136.88 | 0.00 | 0.00 | 0.00 |
August | 1074.20 | 522.18 | 552.02 | 1145.84 | 216.40 | 0.00 | 0.00 | 0.00 |
September | 664.64 | 290.85 | 373.78 | 581.81 | 429.23 | 0.00 | 0.00 | 0.00 |
October | 351.19 | 140.94 | 210.25 | 231.37 | 753.67 | 0.00 | 0.00 | 0.00 |
November | 74.76 | 26.17 | 48.59 | 5.64 | 1298.73 | 0.00 | 0.00 | 0.00 |
December | 10.69 | 2.57 | 8.12 | 0.00 | 1433.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 726.04 | 356.33 | 369.71 | 702.47 | 695.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.69 | 2.57 | 8.12 | 0.00 | 120.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1551.79 | 873.26 | 762.92 | 1635.82 | 1433.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.39 | 15.58 | 33.81 | 4.30 | 1319.32 | 0.00 | 0.00 | 0.00 |
February | 272.70 | 130.19 | 142.51 | 135.92 | 1116.07 | 0.00 | 0.00 | 0.00 |
March | 777.34 | 393.58 | 383.76 | 625.33 | 835.62 | 0.00 | 0.00 | 0.00 |
April | 1068.36 | 540.31 | 528.05 | 942.00 | 469.47 | 0.00 | 0.00 | 0.00 |
May | 1551.79 | 873.26 | 678.53 | 1635.82 | 247.61 | 0.00 | 0.00 | 0.00 |
June | 1427.98 | 665.06 | 762.92 | 1559.13 | 120.78 | 0.00 | 0.00 | 0.00 |
July | 1356.30 | 656.57 | 699.73 | 1516.61 | 136.88 | 0.00 | 0.00 | 0.00 |
August | 1074.20 | 522.18 | 552.02 | 1145.84 | 216.40 | 0.00 | 0.00 | 0.00 |
September | 664.64 | 290.85 | 373.78 | 581.81 | 429.23 | 0.00 | 0.00 | 0.00 |
October | 351.19 | 140.94 | 210.25 | 231.37 | 753.67 | 0.00 | 0.00 | 0.00 |
November | 74.76 | 26.17 | 48.59 | 5.64 | 1298.73 | 0.00 | 0.00 | 0.00 |
December | 10.69 | 2.57 | 8.12 | 0.00 | 1433.66 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 726.04 | 356.33 | 369.71 | 702.47 | 695.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.69 | 2.57 | 8.12 | 0.00 | 120.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1551.79 | 873.26 | 762.92 | 1635.82 | 1433.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 49.38 | 15.58 | 33.81 | 4.30 | 1319.30 | 0.00 | 0.00 | 0.00 |
February | 272.69 | 130.19 | 142.51 | 135.92 | 1116.05 | 0.00 | 0.00 | 0.00 |
March | 777.33 | 393.57 | 383.75 | 625.32 | 835.60 | 0.00 | 0.00 | 0.00 |
April | 1068.34 | 540.30 | 528.04 | 941.98 | 469.46 | 0.00 | 0.00 | 0.00 |
May | 1551.76 | 873.24 | 678.52 | 1635.79 | 247.60 | 0.00 | 0.00 | 0.00 |
June | 1427.95 | 665.05 | 762.91 | 1559.10 | 120.78 | 0.00 | 0.00 | 0.00 |
July | 1356.27 | 656.56 | 699.72 | 1516.58 | 136.87 | 0.00 | 0.00 | 0.00 |
August | 1074.18 | 522.18 | 552.01 | 1145.82 | 216.39 | 0.00 | 0.00 | 0.00 |
September | 664.62 | 290.85 | 373.78 | 581.80 | 429.23 | 0.00 | 0.00 | 0.00 |
October | 351.18 | 140.94 | 210.24 | 231.37 | 753.66 | 0.00 | 0.00 | 0.00 |
November | 74.76 | 26.17 | 48.59 | 5.64 | 1298.71 | 0.00 | 0.00 | 0.00 |
December | 10.68 | 2.57 | 8.12 | 0.00 | 1433.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 726.03 | 356.33 | 369.70 | 702.45 | 695.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 10.68 | 2.57 | 8.12 | 0.00 | 120.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1551.76 | 873.24 | 762.91 | 1635.79 | 1433.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 201.93 | 132.95 | 68.99 | 114.07 | 1085.49 | 0.00 | 0.00 | 0.00 |
February | 695.08 | 483.27 | 211.80 | 567.45 | 887.93 | 0.00 | 0.00 | 0.00 |
March | 1194.24 | 809.27 | 384.97 | 1128.91 | 692.19 | 0.00 | 0.00 | 0.00 |
April | 1457.74 | 906.88 | 550.86 | 1537.51 | 462.79 | 0.00 | 0.00 | 0.00 |
May | 1202.55 | 623.38 | 579.17 | 1304.20 | 253.96 | 0.00 | 0.00 | 0.00 |
June | 1098.05 | 450.41 | 647.64 | 1223.49 | 135.09 | 0.00 | 0.00 | 0.00 |
July | 1057.86 | 460.97 | 596.88 | 1205.93 | 143.36 | 0.00 | 0.00 | 0.00 |
August | 1095.19 | 603.66 | 491.54 | 1231.10 | 213.66 | 0.00 | 0.00 | 0.00 |
September | 884.74 | 532.75 | 352.00 | 898.54 | 378.23 | 0.00 | 0.00 | 0.00 |
October | 636.68 | 403.78 | 232.91 | 552.64 | 609.38 | 0.00 | 0.00 | 0.00 |
November | 341.18 | 238.10 | 103.09 | 216.47 | 1028.89 | 0.00 | 0.00 | 0.00 |
December | 60.55 | 42.65 | 17.90 | 10.36 | 1220.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 826.94 | 473.29 | 353.65 | 833.24 | 591.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.55 | 42.65 | 17.90 | 10.36 | 135.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1457.74 | 906.88 | 647.64 | 1537.51 | 1220.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 201.93 | 132.95 | 68.99 | 114.07 | 1085.49 | 0.00 | 0.00 | 0.00 |
February | 695.08 | 483.27 | 211.80 | 567.45 | 887.93 | 0.00 | 0.00 | 0.00 |
March | 1194.24 | 809.27 | 384.97 | 1128.91 | 692.19 | 0.00 | 0.00 | 0.00 |
April | 1457.74 | 906.88 | 550.86 | 1537.50 | 462.79 | 0.00 | 0.00 | 0.00 |
May | 1202.55 | 623.38 | 579.17 | 1304.20 | 253.96 | 0.00 | 0.00 | 0.00 |
June | 1098.05 | 450.41 | 647.64 | 1223.49 | 135.09 | 0.00 | 0.00 | 0.00 |
July | 1057.86 | 460.97 | 596.88 | 1205.93 | 143.36 | 0.00 | 0.00 | 0.00 |
August | 1095.19 | 603.66 | 491.54 | 1231.10 | 213.66 | 0.00 | 0.00 | 0.00 |
September | 884.74 | 532.75 | 352.00 | 898.54 | 378.23 | 0.00 | 0.00 | 0.00 |
October | 636.68 | 403.78 | 232.91 | 552.64 | 609.38 | 0.00 | 0.00 | 0.00 |
November | 341.18 | 238.10 | 103.09 | 216.47 | 1028.89 | 0.00 | 0.00 | 0.00 |
December | 60.55 | 42.65 | 17.90 | 10.36 | 1220.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 826.94 | 473.29 | 353.65 | 833.24 | 591.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.55 | 42.65 | 17.90 | 10.36 | 135.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1457.74 | 906.88 | 647.64 | 1537.50 | 1220.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 201.93 | 132.95 | 68.99 | 114.07 | 1085.49 | 0.00 | 0.00 | 0.00 |
February | 695.08 | 483.27 | 211.80 | 567.45 | 887.93 | 0.00 | 0.00 | 0.00 |
March | 1194.24 | 809.27 | 384.97 | 1128.91 | 692.19 | 0.00 | 0.00 | 0.00 |
April | 1457.74 | 906.88 | 550.86 | 1537.51 | 462.79 | 0.00 | 0.00 | 0.00 |
May | 1202.55 | 623.38 | 579.17 | 1304.20 | 253.96 | 0.00 | 0.00 | 0.00 |
June | 1098.05 | 450.41 | 647.64 | 1223.49 | 135.09 | 0.00 | 0.00 | 0.00 |
July | 1057.86 | 460.97 | 596.88 | 1205.93 | 143.36 | 0.00 | 0.00 | 0.00 |
August | 1095.19 | 603.66 | 491.54 | 1231.10 | 213.66 | 0.00 | 0.00 | 0.00 |
September | 884.74 | 532.75 | 352.00 | 898.54 | 378.23 | 0.00 | 0.00 | 0.00 |
October | 636.68 | 403.78 | 232.91 | 552.64 | 609.38 | 0.00 | 0.00 | 0.00 |
November | 341.18 | 238.10 | 103.09 | 216.47 | 1028.89 | 0.00 | 0.00 | 0.00 |
December | 60.55 | 42.65 | 17.90 | 10.36 | 1220.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 826.94 | 473.29 | 353.65 | 833.24 | 591.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.55 | 42.65 | 17.90 | 10.36 | 135.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1457.74 | 906.88 | 647.64 | 1537.51 | 1220.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 201.93 | 132.95 | 68.99 | 114.07 | 1085.49 | 0.00 | 0.00 | 0.00 |
February | 695.08 | 483.27 | 211.80 | 567.45 | 887.93 | 0.00 | 0.00 | 0.00 |
March | 1194.24 | 809.27 | 384.97 | 1128.91 | 692.19 | 0.00 | 0.00 | 0.00 |
April | 1457.74 | 906.88 | 550.86 | 1537.50 | 462.79 | 0.00 | 0.00 | 0.00 |
May | 1202.55 | 623.38 | 579.17 | 1304.20 | 253.96 | 0.00 | 0.00 | 0.00 |
June | 1098.05 | 450.41 | 647.64 | 1223.49 | 135.09 | 0.00 | 0.00 | 0.00 |
July | 1057.86 | 460.97 | 596.88 | 1205.93 | 143.36 | 0.00 | 0.00 | 0.00 |
August | 1095.19 | 603.66 | 491.54 | 1231.10 | 213.66 | 0.00 | 0.00 | 0.00 |
September | 884.74 | 532.75 | 352.00 | 898.54 | 378.23 | 0.00 | 0.00 | 0.00 |
October | 636.68 | 403.78 | 232.91 | 552.64 | 609.38 | 0.00 | 0.00 | 0.00 |
November | 341.18 | 238.10 | 103.09 | 216.47 | 1028.89 | 0.00 | 0.00 | 0.00 |
December | 60.55 | 42.65 | 17.90 | 10.36 | 1220.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 826.94 | 473.29 | 353.65 | 833.24 | 591.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.55 | 42.65 | 17.90 | 10.36 | 135.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1457.74 | 906.88 | 647.64 | 1537.50 | 1220.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 201.93 | 132.94 | 68.98 | 114.07 | 1085.45 | 0.00 | 0.00 | 0.00 |
February | 695.05 | 483.25 | 211.80 | 567.43 | 887.89 | 0.00 | 0.00 | 0.00 |
March | 1194.19 | 809.24 | 384.95 | 1128.86 | 692.16 | 0.00 | 0.00 | 0.00 |
April | 1457.68 | 906.85 | 550.84 | 1537.44 | 462.77 | 0.00 | 0.00 | 0.00 |
May | 1202.50 | 623.36 | 579.15 | 1304.14 | 253.95 | 0.00 | 0.00 | 0.00 |
June | 1098.01 | 450.39 | 647.61 | 1223.44 | 135.08 | 0.00 | 0.00 | 0.00 |
July | 1057.81 | 460.95 | 596.86 | 1205.88 | 143.35 | 0.00 | 0.00 | 0.00 |
August | 1095.15 | 603.63 | 491.52 | 1231.05 | 213.65 | 0.00 | 0.00 | 0.00 |
September | 884.71 | 532.73 | 351.98 | 898.50 | 378.21 | 0.00 | 0.00 | 0.00 |
October | 636.66 | 403.76 | 232.90 | 552.61 | 609.36 | 0.00 | 0.00 | 0.00 |
November | 341.17 | 238.09 | 103.08 | 216.46 | 1028.85 | 0.00 | 0.00 | 0.00 |
December | 60.55 | 42.65 | 17.90 | 10.36 | 1220.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 826.91 | 473.27 | 353.63 | 833.21 | 591.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.55 | 42.65 | 17.90 | 10.36 | 135.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1457.68 | 906.85 | 647.61 | 1537.44 | 1220.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.97 | 4.65 | 21.32 | 0.00 | 1376.38 | 0.00 | 0.00 | 0.00 |
February | 153.30 | 53.37 | 99.93 | 27.14 | 1203.65 | 0.00 | 0.00 | 0.00 |
March | 459.90 | 197.75 | 262.15 | 239.54 | 911.37 | 0.00 | 0.00 | 0.00 |
April | 1090.76 | 565.07 | 525.69 | 983.29 | 546.48 | 0.00 | 0.00 | 0.00 |
May | 1060.62 | 482.84 | 577.78 | 1031.33 | 265.77 | 0.00 | 0.00 | 0.00 |
June | 1162.49 | 495.52 | 666.97 | 1230.48 | 145.18 | 0.00 | 0.00 | 0.00 |
July | 972.70 | 367.84 | 604.86 | 1030.69 | 160.39 | 0.00 | 0.00 | 0.00 |
August | 799.44 | 338.43 | 461.00 | 796.50 | 245.56 | 0.00 | 0.00 | 0.00 |
September | 483.89 | 202.62 | 281.27 | 369.42 | 438.58 | 0.00 | 0.00 | 0.00 |
October | 189.60 | 57.06 | 132.54 | 59.15 | 817.47 | 0.00 | 0.00 | 0.00 |
November | 75.89 | 27.62 | 48.28 | 6.51 | 1357.47 | 0.00 | 0.00 | 0.00 |
December | 6.81 | 0.72 | 6.09 | 0.00 | 1513.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 541.51 | 233.28 | 308.23 | 483.08 | 746.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 6.81 | 0.72 | 6.09 | 0.00 | 145.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1162.49 | 565.07 | 666.97 | 1230.48 | 1513.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.97 | 4.65 | 21.32 | 0.00 | 1376.38 | 0.00 | 0.00 | 0.00 |
February | 153.30 | 53.37 | 99.93 | 27.14 | 1203.65 | 0.00 | 0.00 | 0.00 |
March | 459.90 | 197.75 | 262.15 | 239.54 | 911.37 | 0.00 | 0.00 | 0.00 |
April | 1090.76 | 565.07 | 525.69 | 983.29 | 546.48 | 0.00 | 0.00 | 0.00 |
May | 1060.62 | 482.84 | 577.78 | 1031.33 | 265.77 | 0.00 | 0.00 | 0.00 |
June | 1162.49 | 495.52 | 666.97 | 1230.48 | 145.18 | 0.00 | 0.00 | 0.00 |
July | 972.70 | 367.84 | 604.86 | 1030.69 | 160.39 | 0.00 | 0.00 | 0.00 |
August | 799.44 | 338.43 | 461.00 | 796.50 | 245.56 | 0.00 | 0.00 | 0.00 |
September | 483.89 | 202.62 | 281.27 | 369.42 | 438.58 | 0.00 | 0.00 | 0.00 |
October | 189.60 | 57.06 | 132.54 | 59.15 | 817.47 | 0.00 | 0.00 | 0.00 |
November | 75.89 | 27.62 | 48.28 | 6.51 | 1357.47 | 0.00 | 0.00 | 0.00 |
December | 6.81 | 0.72 | 6.09 | 0.00 | 1513.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 541.51 | 233.28 | 308.23 | 483.08 | 746.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 6.81 | 0.72 | 6.09 | 0.00 | 145.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1162.49 | 565.07 | 666.97 | 1230.48 | 1513.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 25.97 | 4.65 | 21.32 | 0.00 | 1376.36 | 0.00 | 0.00 | 0.00 |
February | 153.30 | 53.37 | 99.92 | 27.14 | 1203.62 | 0.00 | 0.00 | 0.00 |
March | 459.89 | 197.75 | 262.15 | 239.53 | 911.35 | 0.00 | 0.00 | 0.00 |
April | 1090.74 | 565.06 | 525.68 | 983.27 | 546.47 | 0.00 | 0.00 | 0.00 |
May | 1060.60 | 482.83 | 577.77 | 1031.32 | 265.76 | 0.00 | 0.00 | 0.00 |
June | 1162.47 | 495.51 | 666.96 | 1230.46 | 145.18 | 0.00 | 0.00 | 0.00 |
July | 972.68 | 367.83 | 604.85 | 1030.67 | 160.39 | 0.00 | 0.00 | 0.00 |
August | 799.42 | 338.43 | 461.00 | 796.48 | 245.55 | 0.00 | 0.00 | 0.00 |
September | 483.88 | 202.62 | 281.26 | 369.41 | 438.57 | 0.00 | 0.00 | 0.00 |
October | 189.59 | 57.06 | 132.54 | 59.15 | 817.45 | 0.00 | 0.00 | 0.00 |
November | 75.89 | 27.62 | 48.27 | 6.51 | 1357.45 | 0.00 | 0.00 | 0.00 |
December | 6.81 | 0.72 | 6.09 | 0.00 | 1513.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 541.50 | 233.28 | 308.22 | 483.07 | 746.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 6.81 | 0.72 | 6.09 | 0.00 | 145.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1162.47 | 565.06 | 666.96 | 1230.46 | 1513.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.28 | 0.00 | 84.28 | 0.00 | 5885.81 | 0.00 | 0.00 | 0.00 |
February | 372.54 | 0.00 | 372.54 | 0.00 | 5285.35 | 0.00 | 0.00 | 0.00 |
March | 996.37 | 0.00 | 996.37 | 79.57 | 3954.70 | 0.00 | 0.00 | 0.00 |
April | 1802.96 | 39.93 | 1763.03 | 695.02 | 2134.13 | 0.00 | 0.00 | 0.00 |
May | 2764.01 | 440.33 | 2323.68 | 2055.95 | 948.83 | 0.00 | 0.00 | 0.00 |
June | 3605.74 | 802.54 | 2803.20 | 3425.10 | 439.93 | 0.00 | 0.00 | 0.00 |
July | 3026.32 | 492.56 | 2533.76 | 2934.67 | 536.15 | 0.00 | 0.00 | 0.00 |
August | 1932.34 | 108.39 | 1823.96 | 1526.47 | 892.87 | 0.00 | 0.00 | 0.00 |
September | 1077.81 | 1.10 | 1076.71 | 386.82 | 1828.89 | 0.00 | 0.00 | 0.00 |
October | 524.45 | 0.00 | 524.45 | 31.86 | 3400.40 | 0.00 | 0.00 | 0.00 |
November | 162.75 | 0.00 | 162.75 | 0.00 | 5767.23 | 0.00 | 0.00 | 0.00 |
December | 25.56 | 0.00 | 25.56 | 0.00 | 6203.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1369.49 | 157.77 | 1211.71 | 933.40 | 3094.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.56 | 0.00 | 25.56 | 0.00 | 439.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3605.74 | 802.54 | 2803.20 | 3425.10 | 6203.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 148.16 | 46.73 | 101.42 | 13.31 | 3801.02 | 0.00 | 0.00 | 0.00 |
February | 818.09 | 390.56 | 427.53 | 423.36 | 3194.00 | 0.00 | 0.00 | 0.00 |
March | 2332.00 | 1180.73 | 1151.27 | 1898.64 | 2393.71 | 0.00 | 0.00 | 0.00 |
April | 3205.06 | 1620.92 | 1584.14 | 2850.51 | 1321.57 | 0.00 | 0.00 | 0.00 |
May | 4655.31 | 2619.74 | 2035.57 | 4925.16 | 680.44 | 0.00 | 0.00 | 0.00 |
June | 4283.89 | 1995.15 | 2288.74 | 4696.07 | 331.24 | 0.00 | 0.00 | 0.00 |
July | 4068.86 | 1969.68 | 2099.17 | 4569.03 | 382.03 | 0.00 | 0.00 | 0.00 |
August | 3222.57 | 1566.54 | 1656.03 | 3462.30 | 598.72 | 0.00 | 0.00 | 0.00 |
September | 1993.89 | 872.55 | 1121.34 | 1787.80 | 1143.93 | 0.00 | 0.00 | 0.00 |
October | 1053.55 | 422.82 | 630.74 | 723.89 | 2070.18 | 0.00 | 0.00 | 0.00 |
November | 224.29 | 78.51 | 145.78 | 18.78 | 3695.53 | 0.00 | 0.00 | 0.00 |
December | 32.06 | 7.70 | 24.35 | 0.00 | 4102.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2178.10 | 1068.99 | 1109.11 | 2125.51 | 1970.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 32.06 | 7.70 | 24.35 | 0.00 | 331.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4655.31 | 2619.74 | 2288.74 | 4925.16 | 4102.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1009.66 | 664.73 | 344.93 | 579.45 | 5290.45 | 0.00 | 0.00 | 0.00 |
February | 3475.35 | 2416.34 | 1059.01 | 2861.10 | 4316.51 | 0.00 | 0.00 | 0.00 |
March | 5971.14 | 4046.31 | 1924.82 | 5646.30 | 3384.51 | 0.00 | 0.00 | 0.00 |
April | 7288.61 | 4534.36 | 2754.26 | 7673.84 | 2246.58 | 0.00 | 0.00 | 0.00 |
May | 6012.69 | 3116.87 | 2895.82 | 6525.44 | 1199.48 | 0.00 | 0.00 | 0.00 |
June | 5490.19 | 2252.03 | 3238.16 | 6134.24 | 635.53 | 0.00 | 0.00 | 0.00 |
July | 5289.22 | 2304.83 | 2984.39 | 6053.99 | 679.45 | 0.00 | 0.00 | 0.00 |
August | 5475.89 | 3018.25 | 2457.65 | 6175.64 | 1008.56 | 0.00 | 0.00 | 0.00 |
September | 4423.67 | 2663.71 | 1759.96 | 4518.24 | 1783.35 | 0.00 | 0.00 | 0.00 |
October | 3183.38 | 2018.86 | 1164.52 | 2793.25 | 2911.85 | 0.00 | 0.00 | 0.00 |
November | 1705.89 | 1190.47 | 515.42 | 1106.79 | 4957.20 | 0.00 | 0.00 | 0.00 |
December | 302.73 | 213.25 | 89.49 | 53.79 | 5890.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4134.65 | 2366.44 | 1768.21 | 4180.18 | 2851.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 302.73 | 213.25 | 89.49 | 53.79 | 635.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7288.61 | 4534.36 | 3238.16 | 7673.84 | 5890.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.92 | 13.96 | 63.96 | 0.00 | 3906.52 | 0.00 | 0.00 | 0.00 |
February | 459.90 | 160.12 | 299.78 | 92.56 | 3346.11 | 0.00 | 0.00 | 0.00 |
March | 1379.69 | 593.25 | 786.44 | 760.66 | 2467.25 | 0.00 | 0.00 | 0.00 |
April | 3272.26 | 1695.20 | 1577.06 | 3017.65 | 1470.31 | 0.00 | 0.00 | 0.00 |
May | 3181.84 | 1448.51 | 1733.33 | 3123.35 | 754.71 | 0.00 | 0.00 | 0.00 |
June | 3487.43 | 1486.53 | 2000.90 | 3719.18 | 410.81 | 0.00 | 0.00 | 0.00 |
July | 2918.06 | 1103.51 | 1814.56 | 3138.32 | 444.24 | 0.00 | 0.00 | 0.00 |
August | 2398.29 | 1015.29 | 1383.00 | 2446.94 | 658.04 | 0.00 | 0.00 | 0.00 |
September | 1451.66 | 607.86 | 843.80 | 1152.02 | 1192.83 | 0.00 | 0.00 | 0.00 |
October | 568.79 | 171.17 | 397.62 | 201.93 | 2182.02 | 0.00 | 0.00 | 0.00 |
November | 227.68 | 82.85 | 144.83 | 24.49 | 3729.30 | 0.00 | 0.00 | 0.00 |
December | 20.44 | 2.16 | 18.28 | 0.00 | 4163.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1624.50 | 699.83 | 924.67 | 1478.90 | 2053.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.44 | 2.16 | 18.28 | 0.00 | 410.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3487.43 | 1695.20 | 2000.90 | 3719.18 | 4163.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 84.28 | 0.00 | 84.28 | 0.00 | 5764.41 | 0.00 | 0.00 | 0.00 |
February | 372.54 | 0.00 | 372.54 | 0.00 | 5139.20 | 0.00 | 0.00 | 0.00 |
March | 996.37 | 0.00 | 996.37 | 94.41 | 3780.58 | 0.00 | 0.00 | 0.00 |
April | 1802.96 | 39.93 | 1763.03 | 752.27 | 1991.74 | 0.00 | 0.00 | 0.00 |
May | 2764.01 | 440.33 | 2323.68 | 2100.51 | 908.67 | 0.00 | 0.00 | 0.00 |
June | 3605.74 | 802.54 | 2803.20 | 3426.45 | 429.19 | 0.00 | 0.00 | 0.00 |
July | 3026.32 | 492.56 | 2533.76 | 2934.66 | 525.51 | 0.00 | 0.00 | 0.00 |
August | 1932.34 | 108.39 | 1823.96 | 1547.16 | 858.00 | 0.00 | 0.00 | 0.00 |
September | 1077.81 | 1.10 | 1076.71 | 436.16 | 1674.32 | 0.00 | 0.00 | 0.00 |
October | 524.45 | 0.00 | 524.45 | 48.37 | 3183.51 | 0.00 | 0.00 | 0.00 |
November | 162.75 | 0.00 | 162.75 | 0.00 | 5615.11 | 0.00 | 0.00 | 0.00 |
December | 25.56 | 0.00 | 25.56 | 0.00 | 6070.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1369.49 | 157.77 | 1211.71 | 950.48 | 2983.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 25.56 | 0.00 | 25.56 | 0.00 | 429.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3605.74 | 802.54 | 2803.20 | 3426.45 | 6070.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 148.16 | 46.73 | 101.42 | 13.72 | 3728.54 | 0.00 | 0.00 | 0.00 |
February | 818.09 | 390.56 | 427.53 | 433.38 | 3104.35 | 0.00 | 0.00 | 0.00 |
March | 2332.00 | 1180.73 | 1151.27 | 1929.15 | 2287.05 | 0.00 | 0.00 | 0.00 |
April | 3205.06 | 1620.92 | 1584.14 | 2887.44 | 1247.51 | 0.00 | 0.00 | 0.00 |
May | 4655.31 | 2619.74 | 2035.57 | 4936.21 | 658.70 | 0.00 | 0.00 | 0.00 |
June | 4283.89 | 1995.15 | 2288.74 | 4693.06 | 325.92 | 0.00 | 0.00 | 0.00 |
July | 4068.86 | 1969.68 | 2099.17 | 4564.50 | 376.51 | 0.00 | 0.00 | 0.00 |
August | 3222.57 | 1566.54 | 1656.03 | 3467.57 | 581.43 | 0.00 | 0.00 | 0.00 |
September | 1993.89 | 872.55 | 1121.34 | 1820.97 | 1066.74 | 0.00 | 0.00 | 0.00 |
October | 1053.55 | 422.82 | 630.74 | 749.38 | 1941.14 | 0.00 | 0.00 | 0.00 |
November | 224.29 | 78.51 | 145.78 | 19.93 | 3602.15 | 0.00 | 0.00 | 0.00 |
December | 32.06 | 7.70 | 24.35 | 0.00 | 4025.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2178.10 | 1068.99 | 1109.11 | 2137.68 | 1906.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 32.06 | 7.70 | 24.35 | 0.00 | 325.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4655.31 | 2619.74 | 2288.74 | 4936.21 | 4025.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1009.66 | 664.73 | 344.93 | 589.64 | 5179.05 | 0.00 | 0.00 | 0.00 |
February | 3475.35 | 2416.34 | 1059.01 | 2900.59 | 4168.48 | 0.00 | 0.00 | 0.00 |
March | 5971.14 | 4046.31 | 1924.82 | 5695.97 | 3224.11 | 0.00 | 0.00 | 0.00 |
April | 7288.61 | 4534.36 | 2754.26 | 7710.93 | 2126.96 | 0.00 | 0.00 | 0.00 |
May | 6012.69 | 3116.87 | 2895.82 | 6538.66 | 1150.91 | 0.00 | 0.00 | 0.00 |
June | 5490.19 | 2252.03 | 3238.16 | 6131.67 | 620.93 | 0.00 | 0.00 | 0.00 |
July | 5289.22 | 2304.83 | 2984.39 | 6049.96 | 665.59 | 0.00 | 0.00 | 0.00 |
August | 5475.89 | 3018.25 | 2457.65 | 6181.98 | 976.20 | 0.00 | 0.00 | 0.00 |
September | 4423.67 | 2663.71 | 1759.96 | 4561.38 | 1667.38 | 0.00 | 0.00 | 0.00 |
October | 3183.38 | 2018.86 | 1164.52 | 2851.08 | 2721.89 | 0.00 | 0.00 | 0.00 |
November | 1705.89 | 1190.47 | 515.42 | 1129.05 | 4807.61 | 0.00 | 0.00 | 0.00 |
December | 302.73 | 213.25 | 89.49 | 54.96 | 5767.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4134.65 | 2366.44 | 1768.21 | 4202.84 | 2749.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 302.73 | 213.25 | 89.49 | 54.96 | 620.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7288.61 | 4534.36 | 3238.16 | 7710.93 | 5767.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.92 | 13.96 | 63.96 | 0.00 | 3828.43 | 0.00 | 0.00 | 0.00 |
February | 459.90 | 160.12 | 299.78 | 95.67 | 3260.81 | 0.00 | 0.00 | 0.00 |
March | 1379.69 | 593.25 | 786.44 | 774.44 | 2367.84 | 0.00 | 0.00 | 0.00 |
April | 3272.26 | 1695.20 | 1577.06 | 3042.84 | 1393.41 | 0.00 | 0.00 | 0.00 |
May | 3181.84 | 1448.51 | 1733.33 | 3135.89 | 725.49 | 0.00 | 0.00 | 0.00 |
June | 3487.43 | 1486.53 | 2000.90 | 3717.51 | 402.01 | 0.00 | 0.00 | 0.00 |
July | 2918.06 | 1103.51 | 1814.56 | 3136.22 | 435.31 | 0.00 | 0.00 | 0.00 |
August | 2398.29 | 1015.29 | 1383.00 | 2454.38 | 637.05 | 0.00 | 0.00 | 0.00 |
September | 1451.66 | 607.86 | 843.80 | 1176.18 | 1119.90 | 0.00 | 0.00 | 0.00 |
October | 568.79 | 171.17 | 397.62 | 214.86 | 2064.97 | 0.00 | 0.00 | 0.00 |
November | 227.68 | 82.85 | 144.83 | 26.05 | 3636.27 | 0.00 | 0.00 | 0.00 |
December | 20.44 | 2.16 | 18.28 | 0.00 | 4084.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1624.50 | 699.83 | 924.67 | 1486.97 | 1989.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 20.44 | 2.16 | 18.28 | 0.00 | 402.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3487.43 | 1695.20 | 2000.90 | 3717.51 | 4084.02 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45144979.92 | 0.00 | 45144979.92 | 0.00 | 0.329393E+10 |
February | 0.180250E+09 | 0.00 | 0.180250E+09 | 0.00 | 0.270116E+10 |
March | 0.533743E+09 | 0.00 | 0.533743E+09 | 30247851.32 | 0.227242E+10 |
April | 0.934666E+09 | 20700799.60 | 0.913965E+09 | 0.316712E+09 | 0.122806E+10 |
May | 0.148064E+10 | 0.235876E+09 | 0.124476E+10 | 0.105353E+10 | 0.555802E+09 |
June | 0.186924E+10 | 0.416041E+09 | 0.145320E+10 | 0.174021E+10 | 0.252090E+09 |
July | 0.162116E+10 | 0.263859E+09 | 0.135730E+10 | 0.153081E+10 | 0.317961E+09 |
August | 0.103513E+10 | 58061489.25 | 0.977069E+09 | 0.774614E+09 | 0.538222E+09 |
September | 0.558744E+09 | 568642.42 | 0.558175E+09 | 0.168969E+09 | 0.109499E+10 |
October | 0.280938E+09 | 0.00 | 0.280938E+09 | 8312168.81 | 0.203324E+10 |
November | 84372750.00 | 0.00 | 84372750.00 | 0.00 | 0.317605E+10 |
December | 13694629.94 | 0.00 | 13694629.94 | 0.00 | 0.351643E+10 |
Annual Sum or Average | 0.863772E+10 | 0.995107E+09 | 0.764261E+10 | 0.562341E+10 | 0.209804E+11 |
Minimum of Months | 13694629.94 | 0.00 | 13694629.94 | 0.00 | 0.252090E+09 |
Maximum of Months | 0.186924E+10 | 0.416041E+09 | 0.145320E+10 | 0.174021E+10 | 0.351643E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45144938.15 | 0.00 | 45144938.15 | 0.00 | 0.329393E+10 |
February | 0.180250E+09 | 0.00 | 0.180250E+09 | 0.00 | 0.270116E+10 |
March | 0.533743E+09 | 0.00 | 0.533743E+09 | 30247707.91 | 0.227242E+10 |
April | 0.934666E+09 | 20700774.76 | 0.913965E+09 | 0.316711E+09 | 0.122806E+10 |
May | 0.148064E+10 | 0.235876E+09 | 0.124476E+10 | 0.105353E+10 | 0.555802E+09 |
June | 0.186924E+10 | 0.416040E+09 | 0.145320E+10 | 0.174021E+10 | 0.252090E+09 |
July | 0.162116E+10 | 0.263858E+09 | 0.135730E+10 | 0.153081E+10 | 0.317961E+09 |
August | 0.103513E+10 | 58061419.58 | 0.977068E+09 | 0.774613E+09 | 0.538222E+09 |
September | 0.558744E+09 | 568641.74 | 0.558175E+09 | 0.168969E+09 | 0.109499E+10 |
October | 0.280938E+09 | 0.00 | 0.280938E+09 | 8312123.66 | 0.203324E+10 |
November | 84372671.93 | 0.00 | 84372671.93 | 0.00 | 0.317605E+10 |
December | 13694616.71 | 0.00 | 13694616.71 | 0.00 | 0.351643E+10 |
Annual Sum or Average | 0.863771E+10 | 0.995106E+09 | 0.764261E+10 | 0.562340E+10 | 0.209804E+11 |
Minimum of Months | 13694616.71 | 0.00 | 13694616.71 | 0.00 | 0.252090E+09 |
Maximum of Months | 0.186924E+10 | 0.416040E+09 | 0.145320E+10 | 0.174021E+10 | 0.351643E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45144979.92 | 0.00 | 45144979.92 | 0.00 | 0.329393E+10 |
February | 0.180250E+09 | 0.00 | 0.180250E+09 | 0.00 | 0.270116E+10 |
March | 0.533743E+09 | 0.00 | 0.533743E+09 | 30247851.32 | 0.227242E+10 |
April | 0.934666E+09 | 20700799.60 | 0.913965E+09 | 0.316712E+09 | 0.122806E+10 |
May | 0.148064E+10 | 0.235876E+09 | 0.124476E+10 | 0.105353E+10 | 0.555802E+09 |
June | 0.186924E+10 | 0.416041E+09 | 0.145320E+10 | 0.174021E+10 | 0.252090E+09 |
July | 0.162116E+10 | 0.263859E+09 | 0.135730E+10 | 0.153081E+10 | 0.317961E+09 |
August | 0.103513E+10 | 58061489.25 | 0.977069E+09 | 0.774614E+09 | 0.538222E+09 |
September | 0.558744E+09 | 568642.42 | 0.558175E+09 | 0.168969E+09 | 0.109499E+10 |
October | 0.280938E+09 | 0.00 | 0.280938E+09 | 8312168.81 | 0.203324E+10 |
November | 84372750.00 | 0.00 | 84372750.00 | 0.00 | 0.317605E+10 |
December | 13694629.94 | 0.00 | 13694629.94 | 0.00 | 0.351643E+10 |
Annual Sum or Average | 0.863772E+10 | 0.995107E+09 | 0.764261E+10 | 0.562341E+10 | 0.209804E+11 |
Minimum of Months | 13694629.94 | 0.00 | 13694629.94 | 0.00 | 0.252090E+09 |
Maximum of Months | 0.186924E+10 | 0.416041E+09 | 0.145320E+10 | 0.174021E+10 | 0.351643E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45144938.15 | 0.00 | 45144938.15 | 0.00 | 0.329393E+10 |
February | 0.180250E+09 | 0.00 | 0.180250E+09 | 0.00 | 0.270116E+10 |
March | 0.533743E+09 | 0.00 | 0.533743E+09 | 30247707.91 | 0.227242E+10 |
April | 0.934666E+09 | 20700774.76 | 0.913965E+09 | 0.316711E+09 | 0.122806E+10 |
May | 0.148064E+10 | 0.235876E+09 | 0.124476E+10 | 0.105353E+10 | 0.555802E+09 |
June | 0.186924E+10 | 0.416040E+09 | 0.145320E+10 | 0.174021E+10 | 0.252090E+09 |
July | 0.162116E+10 | 0.263858E+09 | 0.135730E+10 | 0.153081E+10 | 0.317961E+09 |
August | 0.103513E+10 | 58061419.58 | 0.977068E+09 | 0.774613E+09 | 0.538222E+09 |
September | 0.558744E+09 | 568641.74 | 0.558175E+09 | 0.168969E+09 | 0.109499E+10 |
October | 0.280938E+09 | 0.00 | 0.280938E+09 | 8312123.66 | 0.203324E+10 |
November | 84372671.93 | 0.00 | 84372671.93 | 0.00 | 0.317605E+10 |
December | 13694616.71 | 0.00 | 13694616.71 | 0.00 | 0.351643E+10 |
Annual Sum or Average | 0.863771E+10 | 0.995106E+09 | 0.764261E+10 | 0.562340E+10 | 0.209804E+11 |
Minimum of Months | 13694616.71 | 0.00 | 13694616.71 | 0.00 | 0.252090E+09 |
Maximum of Months | 0.186924E+10 | 0.416040E+09 | 0.145320E+10 | 0.174021E+10 | 0.351643E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 45143160.38 | 0.00 | 45143160.38 | 0.00 | 0.329380E+10 |
February | 0.180243E+09 | 0.00 | 0.180243E+09 | 0.00 | 0.270105E+10 |
March | 0.533722E+09 | 0.00 | 0.533722E+09 | 30246632.20 | 0.227233E+10 |
April | 0.934629E+09 | 20699965.26 | 0.913929E+09 | 0.316699E+09 | 0.122801E+10 |
May | 0.148058E+10 | 0.235867E+09 | 0.124471E+10 | 0.105349E+10 | 0.555779E+09 |
June | 0.186916E+10 | 0.416024E+09 | 0.145314E+10 | 0.174014E+10 | 0.252080E+09 |
July | 0.162109E+10 | 0.263848E+09 | 0.135724E+10 | 0.153075E+10 | 0.317948E+09 |
August | 0.103509E+10 | 58059149.12 | 0.977030E+09 | 0.774583E+09 | 0.538200E+09 |
September | 0.558722E+09 | 568619.50 | 0.558153E+09 | 0.168962E+09 | 0.109494E+10 |
October | 0.280927E+09 | 0.00 | 0.280927E+09 | 8311833.80 | 0.203316E+10 |
November | 84369349.40 | 0.00 | 84369349.40 | 0.00 | 0.317592E+10 |
December | 13694077.98 | 0.00 | 13694077.98 | 0.00 | 0.351629E+10 |
Annual Sum or Average | 0.863737E+10 | 0.995067E+09 | 0.764231E+10 | 0.562318E+10 | 0.209795E+11 |
Minimum of Months | 13694077.98 | 0.00 | 13694077.98 | 0.00 | 0.252080E+09 |
Maximum of Months | 0.186916E+10 | 0.416024E+09 | 0.145314E+10 | 0.174014E+10 | 0.351629E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132275E+09 | 41722671.06 | 90552362.76 | 11525321.85 | 0.353367E+10 |
February | 0.659714E+09 | 0.314949E+09 | 0.344764E+09 | 0.328825E+09 | 0.270000E+10 |
March | 0.208203E+10 | 0.105416E+10 | 0.102787E+10 | 0.167488E+10 | 0.223812E+10 |
April | 0.276920E+10 | 0.140049E+10 | 0.136871E+10 | 0.244166E+10 | 0.121687E+10 |
May | 0.415631E+10 | 0.233893E+10 | 0.181737E+10 | 0.438137E+10 | 0.663194E+09 |
June | 0.370132E+10 | 0.172383E+10 | 0.197749E+10 | 0.404127E+10 | 0.313057E+09 |
July | 0.363271E+10 | 0.175855E+10 | 0.187416E+10 | 0.406208E+10 | 0.366610E+09 |
August | 0.287714E+10 | 0.139862E+10 | 0.147852E+10 | 0.306903E+10 | 0.579595E+09 |
September | 0.172274E+10 | 0.753888E+09 | 0.968849E+09 | 0.150806E+10 | 0.111258E+10 |
October | 0.940623E+09 | 0.377497E+09 | 0.563126E+09 | 0.619703E+09 | 0.201863E+10 |
November | 0.193786E+09 | 67832383.41 | 0.125954E+09 | 14607500.28 | 0.336631E+10 |
December | 28619006.56 | 6878621.69 | 21740384.87 | 0.00 | 0.383992E+10 |
Annual Sum or Average | 0.228965E+11 | 0.112374E+11 | 0.116591E+11 | 0.221530E+11 | 0.219486E+11 |
Minimum of Months | 28619006.56 | 6878621.69 | 21740384.87 | 0.00 | 0.313057E+09 |
Maximum of Months | 0.415631E+10 | 0.233893E+10 | 0.197749E+10 | 0.438137E+10 | 0.383992E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132275E+09 | 41722671.06 | 90552362.76 | 11525321.85 | 0.353367E+10 |
February | 0.659714E+09 | 0.314949E+09 | 0.344764E+09 | 0.328825E+09 | 0.270000E+10 |
March | 0.208203E+10 | 0.105416E+10 | 0.102787E+10 | 0.167488E+10 | 0.223812E+10 |
April | 0.276920E+10 | 0.140049E+10 | 0.136871E+10 | 0.244166E+10 | 0.121687E+10 |
May | 0.415631E+10 | 0.233893E+10 | 0.181737E+10 | 0.438137E+10 | 0.663194E+09 |
June | 0.370132E+10 | 0.172383E+10 | 0.197749E+10 | 0.404127E+10 | 0.313057E+09 |
July | 0.363271E+10 | 0.175855E+10 | 0.187416E+10 | 0.406208E+10 | 0.366610E+09 |
August | 0.287714E+10 | 0.139862E+10 | 0.147852E+10 | 0.306903E+10 | 0.579595E+09 |
September | 0.172274E+10 | 0.753888E+09 | 0.968849E+09 | 0.150806E+10 | 0.111258E+10 |
October | 0.940623E+09 | 0.377497E+09 | 0.563126E+09 | 0.619703E+09 | 0.201863E+10 |
November | 0.193786E+09 | 67832383.41 | 0.125954E+09 | 14607500.28 | 0.336631E+10 |
December | 28619006.56 | 6878621.69 | 21740384.87 | 0.00 | 0.383992E+10 |
Annual Sum or Average | 0.228965E+11 | 0.112374E+11 | 0.116591E+11 | 0.221530E+11 | 0.219486E+11 |
Minimum of Months | 28619006.56 | 6878621.69 | 21740384.87 | 0.00 | 0.313057E+09 |
Maximum of Months | 0.415631E+10 | 0.233893E+10 | 0.197749E+10 | 0.438137E+10 | 0.383992E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132273E+09 | 41721908.69 | 90550708.17 | 11525111.26 | 0.353361E+10 |
February | 0.659702E+09 | 0.314944E+09 | 0.344758E+09 | 0.328819E+09 | 0.269995E+10 |
March | 0.208199E+10 | 0.105414E+10 | 0.102785E+10 | 0.167485E+10 | 0.223808E+10 |
April | 0.276915E+10 | 0.140046E+10 | 0.136869E+10 | 0.244161E+10 | 0.121685E+10 |
May | 0.415623E+10 | 0.233889E+10 | 0.181734E+10 | 0.438129E+10 | 0.663182E+09 |
June | 0.370126E+10 | 0.172380E+10 | 0.197746E+10 | 0.404119E+10 | 0.313051E+09 |
July | 0.363265E+10 | 0.175852E+10 | 0.187413E+10 | 0.406200E+10 | 0.366604E+09 |
August | 0.287708E+10 | 0.139859E+10 | 0.147849E+10 | 0.306897E+10 | 0.579584E+09 |
September | 0.172270E+10 | 0.753874E+09 | 0.968831E+09 | 0.150803E+10 | 0.111256E+10 |
October | 0.940606E+09 | 0.377490E+09 | 0.563116E+09 | 0.619692E+09 | 0.201859E+10 |
November | 0.193783E+09 | 67831143.97 | 0.125951E+09 | 14607233.37 | 0.336625E+10 |
December | 28618483.63 | 6878496.00 | 21739987.63 | 0.00 | 0.383985E+10 |
Annual Sum or Average | 0.228960E+11 | 0.112371E+11 | 0.116589E+11 | 0.221526E+11 | 0.219482E+11 |
Minimum of Months | 28618483.63 | 6878496.00 | 21739987.63 | 0.00 | 0.313051E+09 |
Maximum of Months | 0.415623E+10 | 0.233889E+10 | 0.197746E+10 | 0.438129E+10 | 0.383985E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.540861E+09 | 0.356087E+09 | 0.184774E+09 | 0.305528E+09 | 0.290739E+10 |
February | 0.168153E+10 | 0.116914E+10 | 0.512395E+09 | 0.137278E+10 | 0.214808E+10 |
March | 0.319866E+10 | 0.216756E+10 | 0.103110E+10 | 0.302367E+10 | 0.185396E+10 |
April | 0.377846E+10 | 0.235064E+10 | 0.142782E+10 | 0.398522E+10 | 0.119956E+10 |
May | 0.322092E+10 | 0.166967E+10 | 0.155125E+10 | 0.349316E+10 | 0.680201E+09 |
June | 0.284615E+10 | 0.116747E+10 | 0.167868E+10 | 0.317129E+10 | 0.350147E+09 |
July | 0.283336E+10 | 0.123467E+10 | 0.159870E+10 | 0.322997E+10 | 0.383964E+09 |
August | 0.293336E+10 | 0.161683E+10 | 0.131653E+10 | 0.329738E+10 | 0.572258E+09 |
September | 0.229326E+10 | 0.138089E+10 | 0.912373E+09 | 0.232901E+10 | 0.980365E+09 |
October | 0.170529E+10 | 0.108147E+10 | 0.623819E+09 | 0.148018E+10 | 0.163216E+10 |
November | 0.884343E+09 | 0.617146E+09 | 0.267197E+09 | 0.561082E+09 | 0.266689E+10 |
December | 0.162171E+09 | 0.114233E+09 | 47938048.97 | 27759962.07 | 0.326999E+10 |
Annual Sum or Average | 0.260784E+11 | 0.149258E+11 | 0.111526E+11 | 0.262770E+11 | 0.186450E+11 |
Minimum of Months | 0.162171E+09 | 0.114233E+09 | 47938048.97 | 27759962.07 | 0.350147E+09 |
Maximum of Months | 0.377846E+10 | 0.235064E+10 | 0.167868E+10 | 0.398522E+10 | 0.326999E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.540860E+09 | 0.356087E+09 | 0.184773E+09 | 0.305528E+09 | 0.290739E+10 |
February | 0.168153E+10 | 0.116913E+10 | 0.512395E+09 | 0.137277E+10 | 0.214808E+10 |
March | 0.319865E+10 | 0.216755E+10 | 0.103110E+10 | 0.302367E+10 | 0.185396E+10 |
April | 0.377846E+10 | 0.235064E+10 | 0.142782E+10 | 0.398521E+10 | 0.119956E+10 |
May | 0.322091E+10 | 0.166966E+10 | 0.155125E+10 | 0.349316E+10 | 0.680201E+09 |
June | 0.284614E+10 | 0.116746E+10 | 0.167868E+10 | 0.317129E+10 | 0.350148E+09 |
July | 0.283336E+10 | 0.123467E+10 | 0.159869E+10 | 0.322997E+10 | 0.383964E+09 |
August | 0.293336E+10 | 0.161683E+10 | 0.131653E+10 | 0.329738E+10 | 0.572258E+09 |
September | 0.229326E+10 | 0.138088E+10 | 0.912372E+09 | 0.232901E+10 | 0.980365E+09 |
October | 0.170529E+10 | 0.108147E+10 | 0.623818E+09 | 0.148018E+10 | 0.163216E+10 |
November | 0.884342E+09 | 0.617145E+09 | 0.267197E+09 | 0.561081E+09 | 0.266689E+10 |
December | 0.162171E+09 | 0.114233E+09 | 47937994.65 | 27759865.10 | 0.326999E+10 |
Annual Sum or Average | 0.260783E+11 | 0.149258E+11 | 0.111526E+11 | 0.262770E+11 | 0.186450E+11 |
Minimum of Months | 0.162171E+09 | 0.114233E+09 | 47937994.65 | 27759865.10 | 0.350148E+09 |
Maximum of Months | 0.377846E+10 | 0.235064E+10 | 0.167868E+10 | 0.398521E+10 | 0.326999E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.540861E+09 | 0.356087E+09 | 0.184774E+09 | 0.305528E+09 | 0.290739E+10 |
February | 0.168153E+10 | 0.116914E+10 | 0.512395E+09 | 0.137278E+10 | 0.214808E+10 |
March | 0.319866E+10 | 0.216756E+10 | 0.103110E+10 | 0.302367E+10 | 0.185396E+10 |
April | 0.377846E+10 | 0.235064E+10 | 0.142782E+10 | 0.398522E+10 | 0.119956E+10 |
May | 0.322092E+10 | 0.166967E+10 | 0.155125E+10 | 0.349316E+10 | 0.680201E+09 |
June | 0.284615E+10 | 0.116747E+10 | 0.167868E+10 | 0.317129E+10 | 0.350147E+09 |
July | 0.283336E+10 | 0.123467E+10 | 0.159870E+10 | 0.322997E+10 | 0.383964E+09 |
August | 0.293336E+10 | 0.161683E+10 | 0.131653E+10 | 0.329738E+10 | 0.572258E+09 |
September | 0.229326E+10 | 0.138089E+10 | 0.912373E+09 | 0.232901E+10 | 0.980365E+09 |
October | 0.170529E+10 | 0.108147E+10 | 0.623819E+09 | 0.148018E+10 | 0.163216E+10 |
November | 0.884343E+09 | 0.617146E+09 | 0.267197E+09 | 0.561082E+09 | 0.266689E+10 |
December | 0.162171E+09 | 0.114233E+09 | 47938048.97 | 27759962.07 | 0.326999E+10 |
Annual Sum or Average | 0.260784E+11 | 0.149258E+11 | 0.111526E+11 | 0.262770E+11 | 0.186450E+11 |
Minimum of Months | 0.162171E+09 | 0.114233E+09 | 47938048.97 | 27759962.07 | 0.350147E+09 |
Maximum of Months | 0.377846E+10 | 0.235064E+10 | 0.167868E+10 | 0.398522E+10 | 0.326999E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.540860E+09 | 0.356087E+09 | 0.184773E+09 | 0.305528E+09 | 0.290739E+10 |
February | 0.168153E+10 | 0.116913E+10 | 0.512395E+09 | 0.137277E+10 | 0.214808E+10 |
March | 0.319865E+10 | 0.216755E+10 | 0.103110E+10 | 0.302367E+10 | 0.185396E+10 |
April | 0.377846E+10 | 0.235064E+10 | 0.142782E+10 | 0.398521E+10 | 0.119956E+10 |
May | 0.322091E+10 | 0.166966E+10 | 0.155125E+10 | 0.349316E+10 | 0.680201E+09 |
June | 0.284614E+10 | 0.116746E+10 | 0.167868E+10 | 0.317129E+10 | 0.350148E+09 |
July | 0.283336E+10 | 0.123467E+10 | 0.159869E+10 | 0.322997E+10 | 0.383964E+09 |
August | 0.293336E+10 | 0.161683E+10 | 0.131653E+10 | 0.329738E+10 | 0.572258E+09 |
September | 0.229326E+10 | 0.138088E+10 | 0.912372E+09 | 0.232901E+10 | 0.980365E+09 |
October | 0.170529E+10 | 0.108147E+10 | 0.623818E+09 | 0.148018E+10 | 0.163216E+10 |
November | 0.884342E+09 | 0.617145E+09 | 0.267197E+09 | 0.561081E+09 | 0.266689E+10 |
December | 0.162171E+09 | 0.114233E+09 | 47937994.65 | 27759865.10 | 0.326999E+10 |
Annual Sum or Average | 0.260783E+11 | 0.149258E+11 | 0.111526E+11 | 0.262770E+11 | 0.186450E+11 |
Minimum of Months | 0.162171E+09 | 0.114233E+09 | 47937994.65 | 27759865.10 | 0.350148E+09 |
Maximum of Months | 0.377846E+10 | 0.235064E+10 | 0.167868E+10 | 0.398521E+10 | 0.326999E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.540839E+09 | 0.356073E+09 | 0.184766E+09 | 0.305516E+09 | 0.290727E+10 |
February | 0.168146E+10 | 0.116909E+10 | 0.512375E+09 | 0.137272E+10 | 0.214800E+10 |
March | 0.319853E+10 | 0.216747E+10 | 0.103106E+10 | 0.302355E+10 | 0.185389E+10 |
April | 0.377831E+10 | 0.235054E+10 | 0.142777E+10 | 0.398505E+10 | 0.119951E+10 |
May | 0.322079E+10 | 0.166960E+10 | 0.155119E+10 | 0.349302E+10 | 0.680174E+09 |
June | 0.284603E+10 | 0.116742E+10 | 0.167861E+10 | 0.317117E+10 | 0.350133E+09 |
July | 0.283325E+10 | 0.123462E+10 | 0.159863E+10 | 0.322984E+10 | 0.383948E+09 |
August | 0.293324E+10 | 0.161677E+10 | 0.131648E+10 | 0.329725E+10 | 0.572235E+09 |
September | 0.229317E+10 | 0.138083E+10 | 0.912336E+09 | 0.232891E+10 | 0.980325E+09 |
October | 0.170522E+10 | 0.108143E+10 | 0.623793E+09 | 0.148012E+10 | 0.163210E+10 |
November | 0.884308E+09 | 0.617121E+09 | 0.267186E+09 | 0.561059E+09 | 0.266678E+10 |
December | 0.162164E+09 | 0.114228E+09 | 47936116.85 | 27758843.23 | 0.326986E+10 |
Annual Sum or Average | 0.260773E+11 | 0.149252E+11 | 0.111521E+11 | 0.262760E+11 | 0.186442E+11 |
Minimum of Months | 0.162164E+09 | 0.114228E+09 | 47936116.85 | 27758843.23 | 0.350133E+09 |
Maximum of Months | 0.377831E+10 | 0.235054E+10 | 0.167861E+10 | 0.398505E+10 | 0.326986E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 69564287.34 | 12459819.84 | 57104467.51 | 0.00 | 0.368651E+10 |
February | 0.370863E+09 | 0.129122E+09 | 0.241741E+09 | 65649377.66 | 0.291186E+10 |
March | 0.123180E+10 | 0.529656E+09 | 0.702145E+09 | 0.641581E+09 | 0.244102E+10 |
April | 0.282726E+10 | 0.146467E+10 | 0.136259E+10 | 0.254868E+10 | 0.141648E+10 |
May | 0.284077E+10 | 0.129324E+10 | 0.154753E+10 | 0.276232E+10 | 0.711836E+09 |
June | 0.301317E+10 | 0.128438E+10 | 0.172880E+10 | 0.318940E+10 | 0.376305E+09 |
July | 0.260527E+10 | 0.985220E+09 | 0.162006E+10 | 0.276059E+10 | 0.429590E+09 |
August | 0.214121E+10 | 0.906458E+09 | 0.123475E+10 | 0.213334E+10 | 0.657702E+09 |
September | 0.125425E+10 | 0.525199E+09 | 0.729049E+09 | 0.957535E+09 | 0.113680E+10 |
October | 0.507817E+09 | 0.152821E+09 | 0.354996E+09 | 0.158422E+09 | 0.218951E+10 |
November | 0.196716E+09 | 71585420.23 | 0.125130E+09 | 16865450.71 | 0.351857E+10 |
December | 18245257.75 | 1929022.56 | 16316235.19 | 0.00 | 0.405250E+10 |
Annual Sum or Average | 0.170769E+11 | 0.735673E+10 | 0.972022E+10 | 0.152344E+11 | 0.235287E+11 |
Minimum of Months | 18245257.75 | 1929022.56 | 16316235.19 | 0.00 | 0.376305E+09 |
Maximum of Months | 0.301317E+10 | 0.146467E+10 | 0.172880E+10 | 0.318940E+10 | 0.405250E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 69564287.34 | 12459819.84 | 57104467.51 | 0.00 | 0.368651E+10 |
February | 0.370863E+09 | 0.129122E+09 | 0.241741E+09 | 65649377.66 | 0.291186E+10 |
March | 0.123180E+10 | 0.529656E+09 | 0.702145E+09 | 0.641581E+09 | 0.244102E+10 |
April | 0.282726E+10 | 0.146467E+10 | 0.136259E+10 | 0.254868E+10 | 0.141648E+10 |
May | 0.284077E+10 | 0.129324E+10 | 0.154753E+10 | 0.276232E+10 | 0.711836E+09 |
June | 0.301317E+10 | 0.128438E+10 | 0.172880E+10 | 0.318940E+10 | 0.376305E+09 |
July | 0.260527E+10 | 0.985220E+09 | 0.162006E+10 | 0.276059E+10 | 0.429590E+09 |
August | 0.214121E+10 | 0.906458E+09 | 0.123475E+10 | 0.213334E+10 | 0.657702E+09 |
September | 0.125425E+10 | 0.525199E+09 | 0.729049E+09 | 0.957535E+09 | 0.113680E+10 |
October | 0.507817E+09 | 0.152821E+09 | 0.354996E+09 | 0.158422E+09 | 0.218951E+10 |
November | 0.196716E+09 | 71585420.23 | 0.125130E+09 | 16865450.71 | 0.351857E+10 |
December | 18245257.75 | 1929022.56 | 16316235.19 | 0.00 | 0.405250E+10 |
Annual Sum or Average | 0.170769E+11 | 0.735673E+10 | 0.972022E+10 | 0.152344E+11 | 0.235287E+11 |
Minimum of Months | 18245257.75 | 1929022.56 | 16316235.19 | 0.00 | 0.376305E+09 |
Maximum of Months | 0.301317E+10 | 0.146467E+10 | 0.172880E+10 | 0.318940E+10 | 0.405250E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 69563016.25 | 12459592.17 | 57103424.08 | 0.00 | 0.368644E+10 |
February | 0.370857E+09 | 0.129120E+09 | 0.241737E+09 | 65648178.11 | 0.291181E+10 |
March | 0.123178E+10 | 0.529646E+09 | 0.702132E+09 | 0.641570E+09 | 0.244097E+10 |
April | 0.282721E+10 | 0.146464E+10 | 0.136257E+10 | 0.254863E+10 | 0.141645E+10 |
May | 0.284072E+10 | 0.129321E+10 | 0.154751E+10 | 0.276227E+10 | 0.711823E+09 |
June | 0.301312E+10 | 0.128435E+10 | 0.172877E+10 | 0.318934E+10 | 0.376298E+09 |
July | 0.260523E+10 | 0.985202E+09 | 0.162003E+10 | 0.276054E+10 | 0.429582E+09 |
August | 0.214117E+10 | 0.906441E+09 | 0.123473E+10 | 0.213330E+10 | 0.657690E+09 |
September | 0.125422E+10 | 0.525189E+09 | 0.729036E+09 | 0.957517E+09 | 0.113678E+10 |
October | 0.507808E+09 | 0.152818E+09 | 0.354990E+09 | 0.158419E+09 | 0.218947E+10 |
November | 0.196712E+09 | 71584112.21 | 0.125128E+09 | 16865142.54 | 0.351851E+10 |
December | 18244924.37 | 1928987.31 | 16315937.06 | 0.00 | 0.405243E+10 |
Annual Sum or Average | 0.170766E+11 | 0.735660E+10 | 0.972004E+10 | 0.152341E+11 | 0.235282E+11 |
Minimum of Months | 18244924.37 | 1928987.31 | 16315937.06 | 0.00 | 0.376298E+09 |
Maximum of Months | 0.301312E+10 | 0.146464E+10 | 0.172877E+10 | 0.318934E+10 | 0.405243E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.225722E+09 | 0.00 | 0.225722E+09 | 0.00 | 0.157646E+11 |
February | 0.901239E+09 | 0.00 | 0.901239E+09 | 0.00 | 0.127863E+11 |
March | 0.266869E+10 | 0.00 | 0.266869E+10 | 0.213122E+09 | 0.105923E+11 |
April | 0.467327E+10 | 0.103503E+09 | 0.456977E+10 | 0.180150E+10 | 0.553166E+10 |
May | 0.740311E+10 | 0.117937E+10 | 0.622375E+10 | 0.550665E+10 | 0.254136E+10 |
June | 0.934608E+10 | 0.208018E+10 | 0.726590E+10 | 0.887787E+10 | 0.114029E+10 |
July | 0.810569E+10 | 0.131928E+10 | 0.678641E+10 | 0.786023E+10 | 0.143601E+10 |
August | 0.517559E+10 | 0.290304E+09 | 0.488529E+10 | 0.408849E+10 | 0.239146E+10 |
September | 0.279369E+10 | 2843177.71 | 0.279084E+10 | 0.100264E+10 | 0.474049E+10 |
October | 0.140467E+10 | 0.00 | 0.140467E+10 | 85324806.00 | 0.910763E+10 |
November | 0.421859E+09 | 0.00 | 0.421859E+09 | 0.00 | 0.149487E+11 |
December | 68472321.71 | 0.00 | 68472321.71 | 0.00 | 0.166156E+11 |
Annual Sum or Average | 0.431881E+11 | 0.497547E+10 | 0.382126E+11 | 0.294358E+11 | 0.975963E+11 |
Minimum of Months | 68472321.71 | 0.00 | 68472321.71 | 0.00 | 0.114029E+10 |
Maximum of Months | 0.934608E+10 | 0.208018E+10 | 0.726590E+10 | 0.887787E+10 | 0.166156E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.396821E+09 | 0.125167E+09 | 0.271654E+09 | 35639125.39 | 0.101807E+11 |
February | 0.197912E+10 | 0.944839E+09 | 0.103428E+10 | 0.102420E+10 | 0.772694E+10 |
March | 0.624603E+10 | 0.316246E+10 | 0.308357E+10 | 0.508531E+10 | 0.641131E+10 |
April | 0.830751E+10 | 0.420142E+10 | 0.410609E+10 | 0.738851E+10 | 0.342551E+10 |
May | 0.124688E+11 | 0.701672E+10 | 0.545207E+10 | 0.131915E+11 | 0.182248E+10 |
June | 0.111039E+11 | 0.517144E+10 | 0.593241E+10 | 0.121722E+11 | 0.858571E+09 |
July | 0.108980E+11 | 0.527560E+10 | 0.562243E+10 | 0.122377E+11 | 0.102322E+10 |
August | 0.863132E+10 | 0.419582E+10 | 0.443551E+10 | 0.927344E+10 | 0.160361E+10 |
September | 0.516816E+10 | 0.226164E+10 | 0.290652E+10 | 0.463399E+10 | 0.296506E+10 |
October | 0.282184E+10 | 0.113248E+10 | 0.168936E+10 | 0.193888E+10 | 0.554478E+10 |
November | 0.581353E+09 | 0.203495E+09 | 0.377858E+09 | 48667509.82 | 0.957880E+10 |
December | 85856144.56 | 20635654.73 | 65220489.83 | 0.00 | 0.109890E+11 |
Annual Sum or Average | 0.686887E+11 | 0.337117E+11 | 0.349770E+11 | 0.670301E+11 | 0.621299E+11 |
Minimum of Months | 85856144.56 | 20635654.73 | 65220489.83 | 0.00 | 0.858571E+09 |
Maximum of Months | 0.124688E+11 | 0.701672E+10 | 0.593241E+10 | 0.131915E+11 | 0.109890E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270427E+10 | 0.178041E+10 | 0.923856E+09 | 0.155201E+10 | 0.141699E+11 |
February | 0.840756E+10 | 0.584561E+10 | 0.256195E+10 | 0.692158E+10 | 0.104425E+11 |
March | 0.159931E+11 | 0.108376E+11 | 0.515545E+10 | 0.151230E+11 | 0.906507E+10 |
April | 0.188921E+11 | 0.117531E+11 | 0.713904E+10 | 0.198906E+11 | 0.582314E+10 |
May | 0.161044E+11 | 0.834823E+10 | 0.775616E+10 | 0.174777E+11 | 0.321269E+10 |
June | 0.142306E+11 | 0.583726E+10 | 0.839330E+10 | 0.158999E+11 | 0.164729E+10 |
July | 0.141666E+11 | 0.617326E+10 | 0.799338E+10 | 0.162150E+11 | 0.181985E+10 |
August | 0.146666E+11 | 0.808407E+10 | 0.658257E+10 | 0.165408E+11 | 0.270134E+10 |
September | 0.114662E+11 | 0.690435E+10 | 0.456181E+10 | 0.117113E+11 | 0.462245E+10 |
October | 0.852636E+10 | 0.540731E+10 | 0.311905E+10 | 0.748143E+10 | 0.779910E+10 |
November | 0.442166E+10 | 0.308569E+10 | 0.133597E+10 | 0.286879E+10 | 0.128491E+11 |
December | 0.810845E+09 | 0.571158E+09 | 0.239687E+09 | 0.144060E+09 | 0.157773E+11 |
Annual Sum or Average | 0.130390E+12 | 0.746280E+11 | 0.557622E+11 | 0.131826E+12 | 0.899297E+11 |
Minimum of Months | 0.810845E+09 | 0.571158E+09 | 0.239687E+09 | 0.144060E+09 | 0.164729E+10 |
Maximum of Months | 0.188921E+11 | 0.117531E+11 | 0.839330E+10 | 0.198906E+11 | 0.157773E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.208691E+09 | 37379078.50 | 0.171312E+09 | 0.00 | 0.104632E+11 |
February | 0.111258E+10 | 0.387362E+09 | 0.725216E+09 | 0.223918E+09 | 0.809491E+10 |
March | 0.369536E+10 | 0.158895E+10 | 0.210641E+10 | 0.203735E+10 | 0.660828E+10 |
April | 0.848170E+10 | 0.439396E+10 | 0.408774E+10 | 0.782175E+10 | 0.381105E+10 |
May | 0.852223E+10 | 0.387968E+10 | 0.464256E+10 | 0.836557E+10 | 0.202141E+10 |
June | 0.903943E+10 | 0.385309E+10 | 0.518634E+10 | 0.964012E+10 | 0.106481E+10 |
July | 0.781575E+10 | 0.295563E+10 | 0.486012E+10 | 0.840567E+10 | 0.118987E+10 |
August | 0.642357E+10 | 0.271935E+10 | 0.370422E+10 | 0.655387E+10 | 0.176250E+10 |
September | 0.376271E+10 | 0.157558E+10 | 0.218712E+10 | 0.298603E+10 | 0.309181E+10 |
October | 0.152344E+10 | 0.458457E+09 | 0.106498E+10 | 0.540838E+09 | 0.584431E+10 |
November | 0.590141E+09 | 0.214754E+09 | 0.375387E+09 | 63473572.89 | 0.966635E+10 |
December | 54735215.34 | 5787008.70 | 48948206.64 | 0.00 | 0.111526E+11 |
Annual Sum or Average | 0.512303E+11 | 0.220700E+11 | 0.291604E+11 | 0.466386E+11 | 0.647712E+11 |
Minimum of Months | 54735215.34 | 5787008.70 | 48948206.64 | 0.00 | 0.106481E+10 |
Maximum of Months | 0.903943E+10 | 0.439396E+10 | 0.518634E+10 | 0.964012E+10 | 0.111526E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.225722E+09 | 0.00 | 0.225722E+09 | 0.00 | 0.154394E+11 |
February | 0.901239E+09 | 0.00 | 0.901239E+09 | 0.00 | 0.124328E+11 |
March | 0.266869E+10 | 0.00 | 0.266869E+10 | 0.252877E+09 | 0.101259E+11 |
April | 0.467327E+10 | 0.103503E+09 | 0.456977E+10 | 0.194988E+10 | 0.516258E+10 |
May | 0.740311E+10 | 0.117937E+10 | 0.622375E+10 | 0.562601E+10 | 0.243379E+10 |
June | 0.934608E+10 | 0.208018E+10 | 0.726590E+10 | 0.888135E+10 | 0.111247E+10 |
July | 0.810569E+10 | 0.131928E+10 | 0.678641E+10 | 0.786020E+10 | 0.140752E+10 |
August | 0.517559E+10 | 0.290304E+09 | 0.488529E+10 | 0.414392E+10 | 0.229806E+10 |
September | 0.279369E+10 | 2843177.71 | 0.279084E+10 | 0.113052E+10 | 0.433983E+10 |
October | 0.140467E+10 | 0.00 | 0.140467E+10 | 0.129551E+09 | 0.852672E+10 |
November | 0.421859E+09 | 0.00 | 0.421859E+09 | 0.00 | 0.145544E+11 |
December | 68472321.71 | 0.00 | 68472321.71 | 0.00 | 0.162602E+11 |
Annual Sum or Average | 0.431881E+11 | 0.497547E+10 | 0.382126E+11 | 0.299743E+11 | 0.940936E+11 |
Minimum of Months | 68472321.71 | 0.00 | 68472321.71 | 0.00 | 0.111247E+10 |
Maximum of Months | 0.934608E+10 | 0.208018E+10 | 0.726590E+10 | 0.888135E+10 | 0.162602E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.396821E+09 | 0.125167E+09 | 0.271654E+09 | 36749606.70 | 0.998652E+10 |
February | 0.197912E+10 | 0.944839E+09 | 0.103428E+10 | 0.104843E+10 | 0.751005E+10 |
March | 0.624603E+10 | 0.316246E+10 | 0.308357E+10 | 0.516703E+10 | 0.612563E+10 |
April | 0.830751E+10 | 0.420142E+10 | 0.410609E+10 | 0.748424E+10 | 0.323355E+10 |
May | 0.124688E+11 | 0.701672E+10 | 0.545207E+10 | 0.132211E+11 | 0.176427E+10 |
June | 0.111039E+11 | 0.517144E+10 | 0.593241E+10 | 0.121644E+11 | 0.844786E+09 |
July | 0.108980E+11 | 0.527560E+10 | 0.562243E+10 | 0.122256E+11 | 0.100845E+10 |
August | 0.863132E+10 | 0.419582E+10 | 0.443551E+10 | 0.928754E+10 | 0.155730E+10 |
September | 0.516816E+10 | 0.226164E+10 | 0.290652E+10 | 0.471994E+10 | 0.276498E+10 |
October | 0.282184E+10 | 0.113248E+10 | 0.168936E+10 | 0.200713E+10 | 0.519914E+10 |
November | 0.581353E+09 | 0.203495E+09 | 0.377858E+09 | 51652436.42 | 0.933679E+10 |
December | 85856144.56 | 20635654.73 | 65220489.83 | 0.00 | 0.107812E+11 |
Annual Sum or Average | 0.686887E+11 | 0.337117E+11 | 0.349770E+11 | 0.674138E+11 | 0.601127E+11 |
Minimum of Months | 85856144.56 | 20635654.73 | 65220489.83 | 0.00 | 0.844786E+09 |
Maximum of Months | 0.124688E+11 | 0.701672E+10 | 0.593241E+10 | 0.132211E+11 | 0.107812E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270427E+10 | 0.178041E+10 | 0.923856E+09 | 0.157929E+10 | 0.138716E+11 |
February | 0.840756E+10 | 0.584561E+10 | 0.256195E+10 | 0.701710E+10 | 0.100844E+11 |
March | 0.159931E+11 | 0.108376E+11 | 0.515545E+10 | 0.152561E+11 | 0.863547E+10 |
April | 0.188921E+11 | 0.117531E+11 | 0.713904E+10 | 0.199867E+11 | 0.551308E+10 |
May | 0.161044E+11 | 0.834823E+10 | 0.775616E+10 | 0.175131E+11 | 0.308259E+10 |
June | 0.142306E+11 | 0.583726E+10 | 0.839330E+10 | 0.158933E+11 | 0.160946E+10 |
July | 0.141666E+11 | 0.617326E+10 | 0.799338E+10 | 0.162042E+11 | 0.178271E+10 |
August | 0.146666E+11 | 0.808407E+10 | 0.658257E+10 | 0.165578E+11 | 0.261465E+10 |
September | 0.114662E+11 | 0.690435E+10 | 0.456181E+10 | 0.118231E+11 | 0.432185E+10 |
October | 0.852636E+10 | 0.540731E+10 | 0.311905E+10 | 0.763633E+10 | 0.729030E+10 |
November | 0.442166E+10 | 0.308569E+10 | 0.133597E+10 | 0.292649E+10 | 0.124613E+11 |
December | 0.810845E+09 | 0.571158E+09 | 0.239687E+09 | 0.147211E+09 | 0.154485E+11 |
Annual Sum or Average | 0.130390E+12 | 0.746280E+11 | 0.557622E+11 | 0.132541E+12 | 0.867159E+11 |
Minimum of Months | 0.810845E+09 | 0.571158E+09 | 0.239687E+09 | 0.147211E+09 | 0.160946E+10 |
Maximum of Months | 0.188921E+11 | 0.117531E+11 | 0.839330E+10 | 0.199867E+11 | 0.154485E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.208691E+09 | 37379078.50 | 0.171312E+09 | 0.00 | 0.102541E+11 |
February | 0.111258E+10 | 0.387362E+09 | 0.725216E+09 | 0.231445E+09 | 0.788855E+10 |
March | 0.369536E+10 | 0.158895E+10 | 0.210641E+10 | 0.207425E+10 | 0.634201E+10 |
April | 0.848170E+10 | 0.439396E+10 | 0.408774E+10 | 0.788703E+10 | 0.361172E+10 |
May | 0.852223E+10 | 0.387968E+10 | 0.464256E+10 | 0.839916E+10 | 0.194315E+10 |
June | 0.903943E+10 | 0.385309E+10 | 0.518634E+10 | 0.963578E+10 | 0.104201E+10 |
July | 0.781575E+10 | 0.295563E+10 | 0.486012E+10 | 0.840006E+10 | 0.116593E+10 |
August | 0.642357E+10 | 0.271935E+10 | 0.370422E+10 | 0.657382E+10 | 0.170628E+10 |
September | 0.376271E+10 | 0.157558E+10 | 0.218712E+10 | 0.304867E+10 | 0.290277E+10 |
October | 0.152344E+10 | 0.458457E+09 | 0.106498E+10 | 0.575475E+09 | 0.553081E+10 |
November | 0.590141E+09 | 0.214754E+09 | 0.375387E+09 | 67523412.41 | 0.942522E+10 |
December | 54735215.34 | 5787008.70 | 48948206.64 | 0.00 | 0.109386E+11 |
Annual Sum or Average | 0.512303E+11 | 0.220700E+11 | 0.291604E+11 | 0.468932E+11 | 0.627511E+11 |
Minimum of Months | 54735215.34 | 5787008.70 | 48948206.64 | 0.00 | 0.104201E+10 |
Maximum of Months | 0.903943E+10 | 0.439396E+10 | 0.518634E+10 | 0.963578E+10 | 0.109386E+11 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 6149.01 | 84.28 | 0.00 | 84.28 | 0.00 | 0.00 |
February | 0.00 | 5582.71 | 372.54 | 0.00 | 372.54 | 0.00 | 0.00 |
March | 56.47 | 4242.10 | 996.38 | 0.00 | 996.38 | 0.00 | 0.00 |
April | 610.94 | 2368.93 | 1802.97 | 39.93 | 1763.04 | 0.00 | 0.00 |
May | 1966.70 | 1037.55 | 2764.02 | 440.33 | 2323.69 | 0.00 | 0.00 |
June | 3356.86 | 486.28 | 3605.75 | 802.54 | 2803.21 | 0.00 | 0.00 |
July | 2857.67 | 593.56 | 3026.33 | 492.56 | 2533.76 | 0.00 | 0.00 |
August | 1446.03 | 1004.74 | 1932.35 | 108.39 | 1823.96 | 0.00 | 0.00 |
September | 325.94 | 2112.23 | 1077.82 | 1.10 | 1076.72 | 0.00 | 0.00 |
October | 15.52 | 3795.60 | 524.45 | 0.00 | 524.45 | 0.00 | 0.00 |
November | 0.00 | 6126.58 | 162.75 | 0.00 | 162.75 | 0.00 | 0.00 |
December | 0.00 | 6564.37 | 25.56 | 0.00 | 25.56 | 0.00 | 0.00 |
Annual Sum or Average | 891.58 | 3326.39 | 1369.49 | 157.77 | 1211.72 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 486.28 | 25.56 | 0.00 | 25.56 | 0.00 | 0.00 |
Maximum of Months | 3356.86 | 6564.37 | 3605.75 | 802.54 | 2803.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 12.91 | 3957.94 | 148.16 | 46.73 | 101.42 | 0.00 | 0.00 |
February | 407.77 | 3348.19 | 818.09 | 390.56 | 427.53 | 0.00 | 0.00 |
March | 1875.98 | 2506.84 | 2332.01 | 1180.73 | 1151.28 | 0.00 | 0.00 |
April | 2825.98 | 1408.41 | 3205.07 | 1620.92 | 1584.15 | 0.00 | 0.00 |
May | 4907.42 | 742.82 | 4655.33 | 2619.75 | 2035.58 | 0.00 | 0.00 |
June | 4677.36 | 362.33 | 4283.91 | 1995.16 | 2288.75 | 0.00 | 0.00 |
July | 4549.79 | 410.63 | 4068.87 | 1969.69 | 2099.18 | 0.00 | 0.00 |
August | 3437.51 | 649.18 | 3222.58 | 1566.55 | 1656.04 | 0.00 | 0.00 |
September | 1745.43 | 1287.70 | 1993.90 | 872.55 | 1121.35 | 0.00 | 0.00 |
October | 694.11 | 2261.00 | 1053.56 | 422.82 | 630.74 | 0.00 | 0.00 |
November | 16.91 | 3896.17 | 224.29 | 78.51 | 145.78 | 0.00 | 0.00 |
December | 0.00 | 4300.96 | 32.06 | 7.70 | 24.35 | 0.00 | 0.00 |
Annual Sum or Average | 2107.39 | 2087.94 | 2178.11 | 1069.00 | 1109.12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 362.33 | 32.06 | 7.70 | 24.35 | 0.00 | 0.00 |
Maximum of Months | 4907.42 | 4300.96 | 4655.33 | 2619.75 | 2288.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 570.35 | 5427.43 | 1009.66 | 664.73 | 344.93 | 0.00 | 0.00 |
February | 2837.23 | 4439.62 | 3475.36 | 2416.35 | 1059.01 | 0.00 | 0.00 |
March | 5644.50 | 3460.93 | 5971.16 | 4046.33 | 1924.83 | 0.00 | 0.00 |
April | 7687.46 | 2313.94 | 7288.64 | 4534.37 | 2754.27 | 0.00 | 0.00 |
May | 6520.93 | 1269.78 | 6012.71 | 3116.88 | 2895.83 | 0.00 | 0.00 |
June | 6117.41 | 675.43 | 5490.21 | 2252.04 | 3238.17 | 0.00 | 0.00 |
July | 6029.62 | 716.77 | 5289.24 | 2304.84 | 2984.40 | 0.00 | 0.00 |
August | 6155.45 | 1068.28 | 5475.91 | 3018.26 | 2457.66 | 0.00 | 0.00 |
September | 4492.65 | 1891.12 | 4423.69 | 2663.72 | 1759.96 | 0.00 | 0.00 |
October | 2763.16 | 3046.88 | 3183.39 | 2018.86 | 1164.53 | 0.00 | 0.00 |
November | 1082.32 | 5144.42 | 1705.89 | 1190.47 | 515.42 | 0.00 | 0.00 |
December | 51.82 | 6104.32 | 302.74 | 213.25 | 89.49 | 0.00 | 0.00 |
Annual Sum or Average | 4166.16 | 2956.12 | 4134.66 | 2366.45 | 1768.21 | 0.00 | 0.00 |
Minimum of Months | 51.82 | 675.43 | 302.74 | 213.25 | 89.49 | 0.00 | 0.00 |
Maximum of Months | 7687.46 | 6104.32 | 7288.64 | 4534.37 | 3238.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 4129.13 | 77.92 | 13.96 | 63.96 | 0.00 | 0.00 |
February | 81.41 | 3610.92 | 459.90 | 160.12 | 299.78 | 0.00 | 0.00 |
March | 718.61 | 2734.10 | 1379.70 | 593.25 | 786.45 | 0.00 | 0.00 |
April | 2949.84 | 1639.43 | 3272.27 | 1695.21 | 1577.07 | 0.00 | 0.00 |
May | 3093.98 | 797.30 | 3181.85 | 1448.51 | 1733.34 | 0.00 | 0.00 |
June | 3691.41 | 435.54 | 3487.45 | 1486.54 | 2000.91 | 0.00 | 0.00 |
July | 3092.04 | 481.17 | 2918.08 | 1103.51 | 1814.57 | 0.00 | 0.00 |
August | 2389.48 | 736.67 | 2398.30 | 1015.29 | 1383.00 | 0.00 | 0.00 |
September | 1108.25 | 1315.74 | 1451.67 | 607.87 | 843.80 | 0.00 | 0.00 |
October | 177.44 | 2452.39 | 568.79 | 171.17 | 397.62 | 0.00 | 0.00 |
November | 19.52 | 4072.40 | 227.68 | 82.85 | 144.83 | 0.00 | 0.00 |
December | 0.00 | 4539.06 | 20.44 | 2.16 | 18.28 | 0.00 | 0.00 |
Annual Sum or Average | 1449.23 | 2238.25 | 1624.51 | 699.84 | 924.67 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 435.54 | 20.44 | 2.16 | 18.28 | 0.00 | 0.00 |
Maximum of Months | 3691.41 | 4539.06 | 3487.45 | 1695.21 | 2000.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 5885.81 | 84.28 | 0.00 | 84.28 | 0.00 | 0.00 |
February | 0.00 | 5285.35 | 372.54 | 0.00 | 372.54 | 0.00 | 0.00 |
March | 79.57 | 3954.70 | 996.37 | 0.00 | 996.37 | 0.00 | 0.00 |
April | 695.02 | 2134.13 | 1802.96 | 39.93 | 1763.03 | 0.00 | 0.00 |
May | 2055.95 | 948.83 | 2764.01 | 440.33 | 2323.68 | 0.00 | 0.00 |
June | 3425.10 | 439.93 | 3605.74 | 802.54 | 2803.20 | 0.00 | 0.00 |
July | 2934.67 | 536.15 | 3026.32 | 492.56 | 2533.76 | 0.00 | 0.00 |
August | 1526.47 | 892.87 | 1932.34 | 108.39 | 1823.96 | 0.00 | 0.00 |
September | 386.82 | 1828.89 | 1077.81 | 1.10 | 1076.71 | 0.00 | 0.00 |
October | 31.86 | 3400.40 | 524.45 | 0.00 | 524.45 | 0.00 | 0.00 |
November | 0.00 | 5767.23 | 162.75 | 0.00 | 162.75 | 0.00 | 0.00 |
December | 0.00 | 6203.55 | 25.56 | 0.00 | 25.56 | 0.00 | 0.00 |
Annual Sum or Average | 933.40 | 3094.76 | 1369.49 | 157.77 | 1211.71 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 439.93 | 25.56 | 0.00 | 25.56 | 0.00 | 0.00 |
Maximum of Months | 3425.10 | 6203.55 | 3605.74 | 802.54 | 2803.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 13.31 | 3801.02 | 148.16 | 46.73 | 101.42 | 0.00 | 0.00 |
February | 423.36 | 3194.00 | 818.09 | 390.56 | 427.53 | 0.00 | 0.00 |
March | 1898.64 | 2393.71 | 2332.00 | 1180.73 | 1151.27 | 0.00 | 0.00 |
April | 2850.51 | 1321.57 | 3205.06 | 1620.92 | 1584.14 | 0.00 | 0.00 |
May | 4925.16 | 680.44 | 4655.31 | 2619.74 | 2035.57 | 0.00 | 0.00 |
June | 4696.07 | 331.24 | 4283.89 | 1995.15 | 2288.74 | 0.00 | 0.00 |
July | 4569.03 | 382.03 | 4068.86 | 1969.68 | 2099.17 | 0.00 | 0.00 |
August | 3462.30 | 598.72 | 3222.57 | 1566.54 | 1656.03 | 0.00 | 0.00 |
September | 1787.80 | 1143.93 | 1993.89 | 872.55 | 1121.34 | 0.00 | 0.00 |
October | 723.89 | 2070.18 | 1053.55 | 422.82 | 630.74 | 0.00 | 0.00 |
November | 18.78 | 3695.53 | 224.29 | 78.51 | 145.78 | 0.00 | 0.00 |
December | 0.00 | 4102.81 | 32.06 | 7.70 | 24.35 | 0.00 | 0.00 |
Annual Sum or Average | 2125.51 | 1970.13 | 2178.10 | 1068.99 | 1109.11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 331.24 | 32.06 | 7.70 | 24.35 | 0.00 | 0.00 |
Maximum of Months | 4925.16 | 4102.81 | 4655.31 | 2619.74 | 2288.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 579.45 | 5290.45 | 1009.66 | 664.73 | 344.93 | 0.00 | 0.00 |
February | 2861.10 | 4316.51 | 3475.35 | 2416.34 | 1059.01 | 0.00 | 0.00 |
March | 5646.30 | 3384.51 | 5971.14 | 4046.31 | 1924.82 | 0.00 | 0.00 |
April | 7673.84 | 2246.58 | 7288.61 | 4534.36 | 2754.26 | 0.00 | 0.00 |
May | 6525.44 | 1199.48 | 6012.69 | 3116.87 | 2895.82 | 0.00 | 0.00 |
June | 6134.24 | 635.53 | 5490.19 | 2252.03 | 3238.16 | 0.00 | 0.00 |
July | 6053.99 | 679.45 | 5289.22 | 2304.83 | 2984.39 | 0.00 | 0.00 |
August | 6175.64 | 1008.56 | 5475.89 | 3018.25 | 2457.65 | 0.00 | 0.00 |
September | 4518.24 | 1783.35 | 4423.67 | 2663.71 | 1759.96 | 0.00 | 0.00 |
October | 2793.25 | 2911.85 | 3183.38 | 2018.86 | 1164.52 | 0.00 | 0.00 |
November | 1106.79 | 4957.20 | 1705.89 | 1190.47 | 515.42 | 0.00 | 0.00 |
December | 53.79 | 5890.58 | 302.73 | 213.25 | 89.49 | 0.00 | 0.00 |
Annual Sum or Average | 4180.18 | 2851.65 | 4134.65 | 2366.44 | 1768.21 | 0.00 | 0.00 |
Minimum of Months | 53.79 | 635.53 | 302.73 | 213.25 | 89.49 | 0.00 | 0.00 |
Maximum of Months | 7673.84 | 5890.58 | 7288.61 | 4534.36 | 3238.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 3906.52 | 77.92 | 13.96 | 63.96 | 0.00 | 0.00 |
February | 92.56 | 3346.11 | 459.90 | 160.12 | 299.78 | 0.00 | 0.00 |
March | 760.66 | 2467.25 | 1379.69 | 593.25 | 786.44 | 0.00 | 0.00 |
April | 3017.65 | 1470.31 | 3272.26 | 1695.20 | 1577.06 | 0.00 | 0.00 |
May | 3123.35 | 754.71 | 3181.84 | 1448.51 | 1733.33 | 0.00 | 0.00 |
June | 3719.18 | 410.81 | 3487.43 | 1486.53 | 2000.90 | 0.00 | 0.00 |
July | 3138.32 | 444.24 | 2918.06 | 1103.51 | 1814.56 | 0.00 | 0.00 |
August | 2446.94 | 658.04 | 2398.29 | 1015.29 | 1383.00 | 0.00 | 0.00 |
September | 1152.02 | 1192.83 | 1451.66 | 607.86 | 843.80 | 0.00 | 0.00 |
October | 201.93 | 2182.02 | 568.79 | 171.17 | 397.62 | 0.00 | 0.00 |
November | 24.49 | 3729.30 | 227.68 | 82.85 | 144.83 | 0.00 | 0.00 |
December | 0.00 | 4163.92 | 20.44 | 2.16 | 18.28 | 0.00 | 0.00 |
Annual Sum or Average | 1478.90 | 2053.88 | 1624.50 | 699.83 | 924.67 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 410.81 | 20.44 | 2.16 | 18.28 | 0.00 | 0.00 |
Maximum of Months | 3719.18 | 4163.92 | 3487.43 | 1695.20 | 2000.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 5764.41 | 84.28 | 0.00 | 84.28 | 0.00 | 0.00 |
February | 0.00 | 5139.20 | 372.54 | 0.00 | 372.54 | 0.00 | 0.00 |
March | 94.41 | 3780.58 | 996.37 | 0.00 | 996.37 | 0.00 | 0.00 |
April | 752.27 | 1991.74 | 1802.96 | 39.93 | 1763.03 | 0.00 | 0.00 |
May | 2100.51 | 908.67 | 2764.01 | 440.33 | 2323.68 | 0.00 | 0.00 |
June | 3426.45 | 429.19 | 3605.74 | 802.54 | 2803.20 | 0.00 | 0.00 |
July | 2934.66 | 525.51 | 3026.32 | 492.56 | 2533.76 | 0.00 | 0.00 |
August | 1547.16 | 858.00 | 1932.34 | 108.39 | 1823.96 | 0.00 | 0.00 |
September | 436.16 | 1674.32 | 1077.81 | 1.10 | 1076.71 | 0.00 | 0.00 |
October | 48.37 | 3183.51 | 524.45 | 0.00 | 524.45 | 0.00 | 0.00 |
November | 0.00 | 5615.11 | 162.75 | 0.00 | 162.75 | 0.00 | 0.00 |
December | 0.00 | 6070.87 | 25.56 | 0.00 | 25.56 | 0.00 | 0.00 |
Annual Sum or Average | 950.48 | 2983.69 | 1369.49 | 157.77 | 1211.71 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 429.19 | 25.56 | 0.00 | 25.56 | 0.00 | 0.00 |
Maximum of Months | 3426.45 | 6070.87 | 3605.74 | 802.54 | 2803.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 13.72 | 3728.54 | 148.16 | 46.73 | 101.42 | 0.00 | 0.00 |
February | 433.38 | 3104.35 | 818.09 | 390.56 | 427.53 | 0.00 | 0.00 |
March | 1929.15 | 2287.05 | 2332.00 | 1180.73 | 1151.27 | 0.00 | 0.00 |
April | 2887.44 | 1247.51 | 3205.06 | 1620.92 | 1584.14 | 0.00 | 0.00 |
May | 4936.21 | 658.70 | 4655.31 | 2619.74 | 2035.57 | 0.00 | 0.00 |
June | 4693.06 | 325.92 | 4283.89 | 1995.15 | 2288.74 | 0.00 | 0.00 |
July | 4564.50 | 376.51 | 4068.86 | 1969.68 | 2099.17 | 0.00 | 0.00 |
August | 3467.57 | 581.43 | 3222.57 | 1566.54 | 1656.03 | 0.00 | 0.00 |
September | 1820.97 | 1066.74 | 1993.89 | 872.55 | 1121.34 | 0.00 | 0.00 |
October | 749.38 | 1941.14 | 1053.55 | 422.82 | 630.74 | 0.00 | 0.00 |
November | 19.93 | 3602.15 | 224.29 | 78.51 | 145.78 | 0.00 | 0.00 |
December | 0.00 | 4025.23 | 32.06 | 7.70 | 24.35 | 0.00 | 0.00 |
Annual Sum or Average | 2137.68 | 1906.16 | 2178.10 | 1068.99 | 1109.11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 325.92 | 32.06 | 7.70 | 24.35 | 0.00 | 0.00 |
Maximum of Months | 4936.21 | 4025.23 | 4655.31 | 2619.74 | 2288.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 589.64 | 5179.05 | 1009.66 | 664.73 | 344.93 | 0.00 | 0.00 |
February | 2900.59 | 4168.48 | 3475.35 | 2416.34 | 1059.01 | 0.00 | 0.00 |
March | 5695.97 | 3224.11 | 5971.14 | 4046.31 | 1924.82 | 0.00 | 0.00 |
April | 7710.93 | 2126.96 | 7288.61 | 4534.36 | 2754.26 | 0.00 | 0.00 |
May | 6538.66 | 1150.91 | 6012.69 | 3116.87 | 2895.82 | 0.00 | 0.00 |
June | 6131.67 | 620.93 | 5490.19 | 2252.03 | 3238.16 | 0.00 | 0.00 |
July | 6049.96 | 665.59 | 5289.22 | 2304.83 | 2984.39 | 0.00 | 0.00 |
August | 6181.98 | 976.20 | 5475.89 | 3018.25 | 2457.65 | 0.00 | 0.00 |
September | 4561.38 | 1667.38 | 4423.67 | 2663.71 | 1759.96 | 0.00 | 0.00 |
October | 2851.08 | 2721.89 | 3183.38 | 2018.86 | 1164.52 | 0.00 | 0.00 |
November | 1129.05 | 4807.61 | 1705.89 | 1190.47 | 515.42 | 0.00 | 0.00 |
December | 54.96 | 5767.81 | 302.73 | 213.25 | 89.49 | 0.00 | 0.00 |
Annual Sum or Average | 4202.84 | 2749.74 | 4134.65 | 2366.44 | 1768.21 | 0.00 | 0.00 |
Minimum of Months | 54.96 | 620.93 | 302.73 | 213.25 | 89.49 | 0.00 | 0.00 |
Maximum of Months | 7710.93 | 5767.81 | 7288.61 | 4534.36 | 3238.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 3828.43 | 77.92 | 13.96 | 63.96 | 0.00 | 0.00 |
February | 95.67 | 3260.81 | 459.90 | 160.12 | 299.78 | 0.00 | 0.00 |
March | 774.44 | 2367.84 | 1379.69 | 593.25 | 786.44 | 0.00 | 0.00 |
April | 3042.84 | 1393.41 | 3272.26 | 1695.20 | 1577.06 | 0.00 | 0.00 |
May | 3135.89 | 725.49 | 3181.84 | 1448.51 | 1733.33 | 0.00 | 0.00 |
June | 3717.51 | 402.01 | 3487.43 | 1486.53 | 2000.90 | 0.00 | 0.00 |
July | 3136.22 | 435.31 | 2918.06 | 1103.51 | 1814.56 | 0.00 | 0.00 |
August | 2454.38 | 637.05 | 2398.29 | 1015.29 | 1383.00 | 0.00 | 0.00 |
September | 1176.18 | 1119.90 | 1451.66 | 607.86 | 843.80 | 0.00 | 0.00 |
October | 214.86 | 2064.97 | 568.79 | 171.17 | 397.62 | 0.00 | 0.00 |
November | 26.05 | 3636.27 | 227.68 | 82.85 | 144.83 | 0.00 | 0.00 |
December | 0.00 | 4084.02 | 20.44 | 2.16 | 18.28 | 0.00 | 0.00 |
Annual Sum or Average | 1486.97 | 1989.83 | 1624.50 | 699.83 | 924.67 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 402.01 | 20.44 | 2.16 | 18.28 | 0.00 | 0.00 |
Maximum of Months | 3717.51 | 4084.02 | 3487.43 | 1695.20 | 2000.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.164695E+11 | 0.225723E+09 | 0.00 | 0.225723E+09 | 0.00 | 0.00 |
February | 0.00 | 0.135057E+11 | 0.901242E+09 | 0.00 | 0.901242E+09 | 0.00 | 0.00 |
March | 0.151238E+09 | 0.113620E+11 | 0.266869E+10 | 0.00 | 0.266869E+10 | 0.00 | 0.00 |
April | 0.158355E+10 | 0.614026E+10 | 0.467329E+10 | 0.103503E+09 | 0.456979E+10 | 0.00 | 0.00 |
May | 0.526760E+10 | 0.277899E+10 | 0.740314E+10 | 0.117937E+10 | 0.622377E+10 | 0.00 | 0.00 |
June | 0.870098E+10 | 0.126044E+10 | 0.934611E+10 | 0.208019E+10 | 0.726592E+10 | 0.00 | 0.00 |
July | 0.765399E+10 | 0.158979E+10 | 0.810572E+10 | 0.131928E+10 | 0.678643E+10 | 0.00 | 0.00 |
August | 0.387304E+10 | 0.269109E+10 | 0.517561E+10 | 0.290305E+09 | 0.488530E+10 | 0.00 | 0.00 |
September | 0.844838E+09 | 0.547489E+10 | 0.279370E+10 | 2843187.80 | 0.279085E+10 | 0.00 | 0.00 |
October | 41560418.73 | 0.101661E+11 | 0.140468E+10 | 0.00 | 0.140468E+10 | 0.00 | 0.00 |
November | 0.00 | 0.158801E+11 | 0.421860E+09 | 0.00 | 0.421860E+09 | 0.00 | 0.00 |
December | 0.00 | 0.175820E+11 | 68472571.27 | 0.00 | 68472571.27 | 0.00 | 0.00 |
Annual Sum or Average | 0.281168E+11 | 0.104901E+12 | 0.431882E+11 | 0.497549E+10 | 0.382127E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.126044E+10 | 68472571.27 | 0.00 | 68472571.27 | 0.00 | 0.00 |
Maximum of Months | 0.870098E+10 | 0.175820E+11 | 0.934611E+10 | 0.208019E+10 | 0.726592E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 34575754.96 | 0.106010E+11 | 0.396823E+09 | 0.125167E+09 | 0.271655E+09 | 0.00 | 0.00 |
February | 0.986469E+09 | 0.809995E+10 | 0.197913E+10 | 0.944843E+09 | 0.103429E+10 | 0.00 | 0.00 |
March | 0.502461E+10 | 0.671432E+10 | 0.624606E+10 | 0.316247E+10 | 0.308358E+10 | 0.00 | 0.00 |
April | 0.732493E+10 | 0.365059E+10 | 0.830754E+10 | 0.420144E+10 | 0.410611E+10 | 0.00 | 0.00 |
May | 0.131440E+11 | 0.198957E+10 | 0.124688E+11 | 0.701675E+10 | 0.545209E+10 | 0.00 | 0.00 |
June | 0.121237E+11 | 0.939164E+09 | 0.111039E+11 | 0.517146E+10 | 0.593244E+10 | 0.00 | 0.00 |
July | 0.121862E+11 | 0.109982E+10 | 0.108981E+11 | 0.527562E+10 | 0.562245E+10 | 0.00 | 0.00 |
August | 0.920704E+10 | 0.173877E+10 | 0.863136E+10 | 0.419583E+10 | 0.443553E+10 | 0.00 | 0.00 |
September | 0.452415E+10 | 0.333771E+10 | 0.516818E+10 | 0.226165E+10 | 0.290653E+10 | 0.00 | 0.00 |
October | 0.185910E+10 | 0.605585E+10 | 0.282185E+10 | 0.113248E+10 | 0.168937E+10 | 0.00 | 0.00 |
November | 43822233.92 | 0.100989E+11 | 0.581355E+09 | 0.203496E+09 | 0.377859E+09 | 0.00 | 0.00 |
December | 0.00 | 0.115197E+11 | 85856496.76 | 20635739.38 | 65220757.38 | 0.00 | 0.00 |
Annual Sum or Average | 0.664586E+11 | 0.658453E+11 | 0.686890E+11 | 0.337118E+11 | 0.349771E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.939164E+09 | 85856496.76 | 20635739.38 | 65220757.38 | 0.00 | 0.00 |
Maximum of Months | 0.131440E+11 | 0.115197E+11 | 0.124688E+11 | 0.701675E+10 | 0.593244E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.152763E+10 | 0.145368E+11 | 0.270428E+10 | 0.178042E+10 | 0.923860E+09 | 0.00 | 0.00 |
February | 0.686382E+10 | 0.107403E+11 | 0.840759E+10 | 0.584563E+10 | 0.256196E+10 | 0.00 | 0.00 |
March | 0.151182E+11 | 0.926975E+10 | 0.159931E+11 | 0.108377E+11 | 0.515546E+10 | 0.00 | 0.00 |
April | 0.199259E+11 | 0.599773E+10 | 0.188922E+11 | 0.117531E+11 | 0.713906E+10 | 0.00 | 0.00 |
May | 0.174657E+11 | 0.340098E+10 | 0.161044E+11 | 0.834826E+10 | 0.775618E+10 | 0.00 | 0.00 |
June | 0.158563E+11 | 0.175072E+10 | 0.142306E+11 | 0.583728E+10 | 0.839333E+10 | 0.00 | 0.00 |
July | 0.161497E+11 | 0.191980E+10 | 0.141667E+11 | 0.617328E+10 | 0.799341E+10 | 0.00 | 0.00 |
August | 0.164868E+11 | 0.286127E+10 | 0.146667E+11 | 0.808410E+10 | 0.658259E+10 | 0.00 | 0.00 |
September | 0.116449E+11 | 0.490178E+10 | 0.114662E+11 | 0.690437E+10 | 0.456183E+10 | 0.00 | 0.00 |
October | 0.740084E+10 | 0.816076E+10 | 0.852639E+10 | 0.540733E+10 | 0.311907E+10 | 0.00 | 0.00 |
November | 0.280538E+10 | 0.133343E+11 | 0.442168E+10 | 0.308570E+10 | 0.133597E+10 | 0.00 | 0.00 |
December | 0.138798E+09 | 0.163498E+11 | 0.810848E+09 | 0.571160E+09 | 0.239688E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.131384E+12 | 0.932241E+11 | 0.130391E+12 | 0.746283E+11 | 0.557624E+11 | 0.00 | 0.00 |
Minimum of Months | 0.138798E+09 | 0.175072E+10 | 0.810848E+09 | 0.571160E+09 | 0.239688E+09 | 0.00 | 0.00 |
Maximum of Months | 0.199259E+11 | 0.163498E+11 | 0.188922E+11 | 0.117531E+11 | 0.839333E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.110594E+11 | 0.208692E+09 | 37379231.84 | 0.171312E+09 | 0.00 | 0.00 |
February | 0.196947E+09 | 0.873553E+10 | 0.111258E+10 | 0.387364E+09 | 0.725219E+09 | 0.00 | 0.00 |
March | 0.192473E+10 | 0.732301E+10 | 0.369538E+10 | 0.158896E+10 | 0.210642E+10 | 0.00 | 0.00 |
April | 0.764598E+10 | 0.424940E+10 | 0.848173E+10 | 0.439397E+10 | 0.408776E+10 | 0.00 | 0.00 |
May | 0.828692E+10 | 0.213549E+10 | 0.852227E+10 | 0.387969E+10 | 0.464258E+10 | 0.00 | 0.00 |
June | 0.956815E+10 | 0.112891E+10 | 0.903946E+10 | 0.385310E+10 | 0.518636E+10 | 0.00 | 0.00 |
July | 0.828171E+10 | 0.128876E+10 | 0.781578E+10 | 0.295564E+10 | 0.486014E+10 | 0.00 | 0.00 |
August | 0.639997E+10 | 0.197310E+10 | 0.642359E+10 | 0.271936E+10 | 0.370424E+10 | 0.00 | 0.00 |
September | 0.287259E+10 | 0.341039E+10 | 0.376272E+10 | 0.157559E+10 | 0.218713E+10 | 0.00 | 0.00 |
October | 0.475264E+09 | 0.656849E+10 | 0.152344E+10 | 0.458459E+09 | 0.106498E+10 | 0.00 | 0.00 |
November | 50596043.95 | 0.105557E+11 | 0.590143E+09 | 0.214755E+09 | 0.375388E+09 | 0.00 | 0.00 |
December | 0.00 | 0.121574E+11 | 54735439.87 | 5787032.44 | 48948407.44 | 0.00 | 0.00 |
Annual Sum or Average | 0.457029E+11 | 0.705856E+11 | 0.512305E+11 | 0.220701E+11 | 0.291605E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.112891E+10 | 54735439.87 | 5787032.44 | 48948407.44 | 0.00 | 0.00 |
Maximum of Months | 0.956815E+10 | 0.121574E+11 | 0.903946E+10 | 0.439397E+10 | 0.518636E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.157646E+11 | 0.225722E+09 | 0.00 | 0.225722E+09 | 0.00 | 0.00 |
February | 0.00 | 0.127863E+11 | 0.901239E+09 | 0.00 | 0.901239E+09 | 0.00 | 0.00 |
March | 0.213122E+09 | 0.105923E+11 | 0.266869E+10 | 0.00 | 0.266869E+10 | 0.00 | 0.00 |
April | 0.180150E+10 | 0.553166E+10 | 0.467327E+10 | 0.103503E+09 | 0.456977E+10 | 0.00 | 0.00 |
May | 0.550665E+10 | 0.254136E+10 | 0.740311E+10 | 0.117937E+10 | 0.622375E+10 | 0.00 | 0.00 |
June | 0.887787E+10 | 0.114029E+10 | 0.934608E+10 | 0.208018E+10 | 0.726590E+10 | 0.00 | 0.00 |
July | 0.786023E+10 | 0.143601E+10 | 0.810569E+10 | 0.131928E+10 | 0.678641E+10 | 0.00 | 0.00 |
August | 0.408849E+10 | 0.239146E+10 | 0.517559E+10 | 0.290304E+09 | 0.488529E+10 | 0.00 | 0.00 |
September | 0.100264E+10 | 0.474049E+10 | 0.279369E+10 | 2843177.71 | 0.279084E+10 | 0.00 | 0.00 |
October | 85324806.00 | 0.910763E+10 | 0.140467E+10 | 0.00 | 0.140467E+10 | 0.00 | 0.00 |
November | 0.00 | 0.149487E+11 | 0.421859E+09 | 0.00 | 0.421859E+09 | 0.00 | 0.00 |
December | 0.00 | 0.166156E+11 | 68472321.71 | 0.00 | 68472321.71 | 0.00 | 0.00 |
Annual Sum or Average | 0.294358E+11 | 0.975963E+11 | 0.431881E+11 | 0.497547E+10 | 0.382126E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.114029E+10 | 68472321.71 | 0.00 | 68472321.71 | 0.00 | 0.00 |
Maximum of Months | 0.887787E+10 | 0.166156E+11 | 0.934608E+10 | 0.208018E+10 | 0.726590E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 35639125.39 | 0.101807E+11 | 0.396821E+09 | 0.125167E+09 | 0.271654E+09 | 0.00 | 0.00 |
February | 0.102420E+10 | 0.772694E+10 | 0.197912E+10 | 0.944839E+09 | 0.103428E+10 | 0.00 | 0.00 |
March | 0.508531E+10 | 0.641131E+10 | 0.624603E+10 | 0.316246E+10 | 0.308357E+10 | 0.00 | 0.00 |
April | 0.738851E+10 | 0.342551E+10 | 0.830751E+10 | 0.420142E+10 | 0.410609E+10 | 0.00 | 0.00 |
May | 0.131915E+11 | 0.182248E+10 | 0.124688E+11 | 0.701672E+10 | 0.545207E+10 | 0.00 | 0.00 |
June | 0.121722E+11 | 0.858571E+09 | 0.111039E+11 | 0.517144E+10 | 0.593241E+10 | 0.00 | 0.00 |
July | 0.122377E+11 | 0.102322E+10 | 0.108980E+11 | 0.527560E+10 | 0.562243E+10 | 0.00 | 0.00 |
August | 0.927344E+10 | 0.160361E+10 | 0.863132E+10 | 0.419582E+10 | 0.443551E+10 | 0.00 | 0.00 |
September | 0.463399E+10 | 0.296506E+10 | 0.516816E+10 | 0.226164E+10 | 0.290652E+10 | 0.00 | 0.00 |
October | 0.193888E+10 | 0.554478E+10 | 0.282184E+10 | 0.113248E+10 | 0.168936E+10 | 0.00 | 0.00 |
November | 48667509.82 | 0.957880E+10 | 0.581353E+09 | 0.203495E+09 | 0.377858E+09 | 0.00 | 0.00 |
December | 0.00 | 0.109890E+11 | 85856144.56 | 20635654.73 | 65220489.83 | 0.00 | 0.00 |
Annual Sum or Average | 0.670301E+11 | 0.621299E+11 | 0.686887E+11 | 0.337117E+11 | 0.349770E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.858571E+09 | 85856144.56 | 20635654.73 | 65220489.83 | 0.00 | 0.00 |
Maximum of Months | 0.131915E+11 | 0.109890E+11 | 0.124688E+11 | 0.701672E+10 | 0.593241E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.155201E+10 | 0.141699E+11 | 0.270427E+10 | 0.178041E+10 | 0.923856E+09 | 0.00 | 0.00 |
February | 0.692158E+10 | 0.104425E+11 | 0.840756E+10 | 0.584561E+10 | 0.256195E+10 | 0.00 | 0.00 |
March | 0.151230E+11 | 0.906507E+10 | 0.159931E+11 | 0.108376E+11 | 0.515545E+10 | 0.00 | 0.00 |
April | 0.198906E+11 | 0.582314E+10 | 0.188921E+11 | 0.117531E+11 | 0.713904E+10 | 0.00 | 0.00 |
May | 0.174777E+11 | 0.321269E+10 | 0.161044E+11 | 0.834823E+10 | 0.775616E+10 | 0.00 | 0.00 |
June | 0.158999E+11 | 0.164729E+10 | 0.142306E+11 | 0.583726E+10 | 0.839330E+10 | 0.00 | 0.00 |
July | 0.162150E+11 | 0.181985E+10 | 0.141666E+11 | 0.617326E+10 | 0.799338E+10 | 0.00 | 0.00 |
August | 0.165408E+11 | 0.270134E+10 | 0.146666E+11 | 0.808407E+10 | 0.658257E+10 | 0.00 | 0.00 |
September | 0.117113E+11 | 0.462245E+10 | 0.114662E+11 | 0.690435E+10 | 0.456181E+10 | 0.00 | 0.00 |
October | 0.748143E+10 | 0.779910E+10 | 0.852636E+10 | 0.540731E+10 | 0.311905E+10 | 0.00 | 0.00 |
November | 0.286879E+10 | 0.128491E+11 | 0.442166E+10 | 0.308569E+10 | 0.133597E+10 | 0.00 | 0.00 |
December | 0.144060E+09 | 0.157773E+11 | 0.810845E+09 | 0.571158E+09 | 0.239687E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.131826E+12 | 0.899297E+11 | 0.130390E+12 | 0.746280E+11 | 0.557622E+11 | 0.00 | 0.00 |
Minimum of Months | 0.144060E+09 | 0.164729E+10 | 0.810845E+09 | 0.571158E+09 | 0.239687E+09 | 0.00 | 0.00 |
Maximum of Months | 0.198906E+11 | 0.157773E+11 | 0.188921E+11 | 0.117531E+11 | 0.839330E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.104632E+11 | 0.208691E+09 | 37379078.50 | 0.171312E+09 | 0.00 | 0.00 |
February | 0.223918E+09 | 0.809491E+10 | 0.111258E+10 | 0.387362E+09 | 0.725216E+09 | 0.00 | 0.00 |
March | 0.203735E+10 | 0.660828E+10 | 0.369536E+10 | 0.158895E+10 | 0.210641E+10 | 0.00 | 0.00 |
April | 0.782175E+10 | 0.381105E+10 | 0.848170E+10 | 0.439396E+10 | 0.408774E+10 | 0.00 | 0.00 |
May | 0.836557E+10 | 0.202141E+10 | 0.852223E+10 | 0.387968E+10 | 0.464256E+10 | 0.00 | 0.00 |
June | 0.964012E+10 | 0.106481E+10 | 0.903943E+10 | 0.385309E+10 | 0.518634E+10 | 0.00 | 0.00 |
July | 0.840567E+10 | 0.118987E+10 | 0.781575E+10 | 0.295563E+10 | 0.486012E+10 | 0.00 | 0.00 |
August | 0.655387E+10 | 0.176250E+10 | 0.642357E+10 | 0.271935E+10 | 0.370422E+10 | 0.00 | 0.00 |
September | 0.298603E+10 | 0.309181E+10 | 0.376271E+10 | 0.157558E+10 | 0.218712E+10 | 0.00 | 0.00 |
October | 0.540838E+09 | 0.584431E+10 | 0.152344E+10 | 0.458457E+09 | 0.106498E+10 | 0.00 | 0.00 |
November | 63473572.89 | 0.966635E+10 | 0.590141E+09 | 0.214754E+09 | 0.375387E+09 | 0.00 | 0.00 |
December | 0.00 | 0.111526E+11 | 54735215.34 | 5787008.70 | 48948206.64 | 0.00 | 0.00 |
Annual Sum or Average | 0.466386E+11 | 0.647712E+11 | 0.512303E+11 | 0.220700E+11 | 0.291604E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.106481E+10 | 54735215.34 | 5787008.70 | 48948206.64 | 0.00 | 0.00 |
Maximum of Months | 0.964012E+10 | 0.111526E+11 | 0.903943E+10 | 0.439396E+10 | 0.518634E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.154394E+11 | 0.225722E+09 | 0.00 | 0.225722E+09 | 0.00 | 0.00 |
February | 0.00 | 0.124328E+11 | 0.901239E+09 | 0.00 | 0.901239E+09 | 0.00 | 0.00 |
March | 0.252877E+09 | 0.101259E+11 | 0.266869E+10 | 0.00 | 0.266869E+10 | 0.00 | 0.00 |
April | 0.194988E+10 | 0.516258E+10 | 0.467327E+10 | 0.103503E+09 | 0.456977E+10 | 0.00 | 0.00 |
May | 0.562601E+10 | 0.243379E+10 | 0.740311E+10 | 0.117937E+10 | 0.622375E+10 | 0.00 | 0.00 |
June | 0.888135E+10 | 0.111247E+10 | 0.934608E+10 | 0.208018E+10 | 0.726590E+10 | 0.00 | 0.00 |
July | 0.786020E+10 | 0.140752E+10 | 0.810569E+10 | 0.131928E+10 | 0.678641E+10 | 0.00 | 0.00 |
August | 0.414392E+10 | 0.229806E+10 | 0.517559E+10 | 0.290304E+09 | 0.488529E+10 | 0.00 | 0.00 |
September | 0.113052E+10 | 0.433983E+10 | 0.279369E+10 | 2843177.71 | 0.279084E+10 | 0.00 | 0.00 |
October | 0.129551E+09 | 0.852672E+10 | 0.140467E+10 | 0.00 | 0.140467E+10 | 0.00 | 0.00 |
November | 0.00 | 0.145544E+11 | 0.421859E+09 | 0.00 | 0.421859E+09 | 0.00 | 0.00 |
December | 0.00 | 0.162602E+11 | 68472321.71 | 0.00 | 68472321.71 | 0.00 | 0.00 |
Annual Sum or Average | 0.299743E+11 | 0.940936E+11 | 0.431881E+11 | 0.497547E+10 | 0.382126E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.111247E+10 | 68472321.71 | 0.00 | 68472321.71 | 0.00 | 0.00 |
Maximum of Months | 0.888135E+10 | 0.162602E+11 | 0.934608E+10 | 0.208018E+10 | 0.726590E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 36749606.70 | 0.998652E+10 | 0.396821E+09 | 0.125167E+09 | 0.271654E+09 | 0.00 | 0.00 |
February | 0.104843E+10 | 0.751005E+10 | 0.197912E+10 | 0.944839E+09 | 0.103428E+10 | 0.00 | 0.00 |
March | 0.516703E+10 | 0.612563E+10 | 0.624603E+10 | 0.316246E+10 | 0.308357E+10 | 0.00 | 0.00 |
April | 0.748424E+10 | 0.323355E+10 | 0.830751E+10 | 0.420142E+10 | 0.410609E+10 | 0.00 | 0.00 |
May | 0.132211E+11 | 0.176427E+10 | 0.124688E+11 | 0.701672E+10 | 0.545207E+10 | 0.00 | 0.00 |
June | 0.121644E+11 | 0.844786E+09 | 0.111039E+11 | 0.517144E+10 | 0.593241E+10 | 0.00 | 0.00 |
July | 0.122256E+11 | 0.100845E+10 | 0.108980E+11 | 0.527560E+10 | 0.562243E+10 | 0.00 | 0.00 |
August | 0.928754E+10 | 0.155730E+10 | 0.863132E+10 | 0.419582E+10 | 0.443551E+10 | 0.00 | 0.00 |
September | 0.471994E+10 | 0.276498E+10 | 0.516816E+10 | 0.226164E+10 | 0.290652E+10 | 0.00 | 0.00 |
October | 0.200713E+10 | 0.519914E+10 | 0.282184E+10 | 0.113248E+10 | 0.168936E+10 | 0.00 | 0.00 |
November | 51652436.42 | 0.933679E+10 | 0.581353E+09 | 0.203495E+09 | 0.377858E+09 | 0.00 | 0.00 |
December | 0.00 | 0.107812E+11 | 85856144.56 | 20635654.73 | 65220489.83 | 0.00 | 0.00 |
Annual Sum or Average | 0.674138E+11 | 0.601127E+11 | 0.686887E+11 | 0.337117E+11 | 0.349770E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.844786E+09 | 85856144.56 | 20635654.73 | 65220489.83 | 0.00 | 0.00 |
Maximum of Months | 0.132211E+11 | 0.107812E+11 | 0.124688E+11 | 0.701672E+10 | 0.593241E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.157929E+10 | 0.138716E+11 | 0.270427E+10 | 0.178041E+10 | 0.923856E+09 | 0.00 | 0.00 |
February | 0.701710E+10 | 0.100844E+11 | 0.840756E+10 | 0.584561E+10 | 0.256195E+10 | 0.00 | 0.00 |
March | 0.152561E+11 | 0.863547E+10 | 0.159931E+11 | 0.108376E+11 | 0.515545E+10 | 0.00 | 0.00 |
April | 0.199867E+11 | 0.551308E+10 | 0.188921E+11 | 0.117531E+11 | 0.713904E+10 | 0.00 | 0.00 |
May | 0.175131E+11 | 0.308259E+10 | 0.161044E+11 | 0.834823E+10 | 0.775616E+10 | 0.00 | 0.00 |
June | 0.158933E+11 | 0.160946E+10 | 0.142306E+11 | 0.583726E+10 | 0.839330E+10 | 0.00 | 0.00 |
July | 0.162042E+11 | 0.178271E+10 | 0.141666E+11 | 0.617326E+10 | 0.799338E+10 | 0.00 | 0.00 |
August | 0.165578E+11 | 0.261465E+10 | 0.146666E+11 | 0.808407E+10 | 0.658257E+10 | 0.00 | 0.00 |
September | 0.118231E+11 | 0.432185E+10 | 0.114662E+11 | 0.690435E+10 | 0.456181E+10 | 0.00 | 0.00 |
October | 0.763633E+10 | 0.729030E+10 | 0.852636E+10 | 0.540731E+10 | 0.311905E+10 | 0.00 | 0.00 |
November | 0.292649E+10 | 0.124613E+11 | 0.442166E+10 | 0.308569E+10 | 0.133597E+10 | 0.00 | 0.00 |
December | 0.147211E+09 | 0.154485E+11 | 0.810845E+09 | 0.571158E+09 | 0.239687E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.132541E+12 | 0.867159E+11 | 0.130390E+12 | 0.746280E+11 | 0.557622E+11 | 0.00 | 0.00 |
Minimum of Months | 0.147211E+09 | 0.160946E+10 | 0.810845E+09 | 0.571158E+09 | 0.239687E+09 | 0.00 | 0.00 |
Maximum of Months | 0.199867E+11 | 0.154485E+11 | 0.188921E+11 | 0.117531E+11 | 0.839330E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.102541E+11 | 0.208691E+09 | 37379078.50 | 0.171312E+09 | 0.00 | 0.00 |
February | 0.231445E+09 | 0.788855E+10 | 0.111258E+10 | 0.387362E+09 | 0.725216E+09 | 0.00 | 0.00 |
March | 0.207425E+10 | 0.634201E+10 | 0.369536E+10 | 0.158895E+10 | 0.210641E+10 | 0.00 | 0.00 |
April | 0.788703E+10 | 0.361172E+10 | 0.848170E+10 | 0.439396E+10 | 0.408774E+10 | 0.00 | 0.00 |
May | 0.839916E+10 | 0.194315E+10 | 0.852223E+10 | 0.387968E+10 | 0.464256E+10 | 0.00 | 0.00 |
June | 0.963578E+10 | 0.104201E+10 | 0.903943E+10 | 0.385309E+10 | 0.518634E+10 | 0.00 | 0.00 |
July | 0.840006E+10 | 0.116593E+10 | 0.781575E+10 | 0.295563E+10 | 0.486012E+10 | 0.00 | 0.00 |
August | 0.657382E+10 | 0.170628E+10 | 0.642357E+10 | 0.271935E+10 | 0.370422E+10 | 0.00 | 0.00 |
September | 0.304867E+10 | 0.290277E+10 | 0.376271E+10 | 0.157558E+10 | 0.218712E+10 | 0.00 | 0.00 |
October | 0.575475E+09 | 0.553081E+10 | 0.152344E+10 | 0.458457E+09 | 0.106498E+10 | 0.00 | 0.00 |
November | 67523412.41 | 0.942522E+10 | 0.590141E+09 | 0.214754E+09 | 0.375387E+09 | 0.00 | 0.00 |
December | 0.00 | 0.109386E+11 | 54735215.34 | 5787008.70 | 48948206.64 | 0.00 | 0.00 |
Annual Sum or Average | 0.468932E+11 | 0.627511E+11 | 0.512303E+11 | 0.220700E+11 | 0.291604E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.104201E+10 | 54735215.34 | 5787008.70 | 48948206.64 | 0.00 | 0.00 |
Maximum of Months | 0.963578E+10 | 0.109386E+11 | 0.903943E+10 | 0.439396E+10 | 0.518634E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -17.6 | -17.9 | -19.9 | 1.62 | -32.2 | 4.20 | 17.57 | 0.00 |
February | -15.4 | -16.0 | -18.9 | 1.58 | -31.2 | 17.68 | 68.90 | 0.00 |
March | -10.3 | -11.6 | -17.1 | 2.46 | -25.4 | 47.11 | 147.56 | 0.00 |
April | 0.73 | -2.7 | -8.8 | 3.74 | -14.2 | 75.81 | 230.75 | 0.00 |
May | 10.60 | 5.25 | -1.5 | 3.99 | -2.1 | 92.54 | 252.99 | 0.00 |
June | 15.96 | 10.88 | 6.41 | 3.45 | 5.66 | 116.77 | 222.76 | 0.00 |
July | 16.86 | 12.85 | 9.90 | 2.85 | 7.58 | 107.92 | 197.90 | 0.00 |
August | 14.24 | 10.70 | 7.59 | 2.94 | 4.33 | 81.01 | 176.65 | 0.00 |
September | 6.72 | 4.45 | 1.76 | 2.11 | -4.1 | 51.38 | 110.92 | 0.00 |
October | -3.1 | -4.4 | -7.1 | 2.79 | -14.3 | 26.50 | 62.95 | 0.00 |
November | -17.6 | -18.1 | -20.3 | 0.70 | -32.8 | 8.03 | 31.72 | 0.00 |
December | -19.3 | -19.6 | -21.9 | 1.25 | -33.6 | 1.27 | 5.23 | 0.00 |
Annual Sum or Average | -1.4 | -3.8 | -7.4 | 2.46 | -14.3 | 52.69 | 127.40 | 0.00 |
Minimum of Months | -19.3 | -19.6 | -21.9 | 0.70 | -33.6 | 1.27 | 5.23 | 0.00 |
Maximum of Months | 16.86 | 12.85 | 9.90 | 3.99 | 7.58 | 116.77 | 252.99 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 21-JAN-20:00 | -2.7 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 2.80 | 08-FEB-15:09 | -0.7 | -6.5 | 2.68 | -7.9 | 21.67 | 32.33 |
March | 6.70 | 20-MAR-14:09 | 2.60 | -3.5 | 1.37 | -7.5 | 138.33 | 487.67 |
April | 15.60 | 22-APR-13:00 | 7.03 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 22.20 | 31-MAY-15:00 | 10.79 | -1.1 | 3.10 | 7.75 | 143.50 | 516.50 |
June | 28.30 | 30-JUN-14:00 | 17.30 | 10.60 | 6.20 | 17.57 | 223.50 | 277.50 |
July | 30.00 | 29-JUL-16:19 | 18.34 | 11.70 | 4.67 | 18.88 | 163.67 | 322.83 |
August | 25.60 | 11-AUG-15:00 | 14.77 | 6.70 | 6.20 | 12.22 | 99.50 | 604.00 |
September | 17.20 | 07-SEP-15:00 | 8.91 | 0.00 | 1.50 | 2.64 | 77.00 | 480.50 |
October | 13.90 | 01-OCT-14:00 | 8.01 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -3.9 | 18-NOV-03:00 | -5.6 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | 1.70 | 24-DEC-11:00 | -0.1 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.9 | -5.6 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 18.34 | 11.70 | 6.20 | 18.88 | 223.50 | 760.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -38.3 | 12-JAN-05:00 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 |
February | -36.1 | 27-FEB-04:00 | -36.2 | -39.4 | 0.00 | -58.7 | 0.00 | 0.00 |
March | -28.9 | 01-MAR-00:10 | -29.2 | -34.0 | 0.65 | -51.0 | 0.00 | 0.00 |
April | -21.7 | 03-APR-05:00 | -22.3 | -27.2 | 2.60 | -42.7 | 0.00 | 0.00 |
May | 0.00 | 27-MAY-03:00 | -1.1 | -2.8 | 6.20 | -7.1 | 29.00 | 14.00 |
June | 3.30 | 02-JUN-03:00 | 2.38 | 1.10 | 1.50 | -11.2 | 45.50 | 266.00 |
July | 7.20 | 31-JUL-03:49 | 6.67 | 6.10 | 2.18 | -7.6 | 0.00 | 0.00 |
August | -1.7 | 31-AUG-05:00 | -2.9 | -5.0 | 2.60 | -18.6 | 25.00 | 538.50 |
September | -5.6 | 29-SEP-06:00 | -6.1 | -7.2 | 2.60 | -21.6 | 0.00 | 0.00 |
October | -20.6 | 22-OCT-05:00 | -20.8 | -22.2 | 2.60 | -40.2 | 0.00 | 0.00 |
November | -30.0 | 29-NOV-09:00 | -30.2 | -33.3 | 0.00 | -51.8 | 0.00 | 0.00 |
December | -33.9 | 15-DEC-07:00 | -34.0 | -37.8 | 0.00 | -56.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -38.3 | -38.4 | -40.4 | 0.00 | -60.9 | 0.00 | 0.00 | |
Maximum of Months | 7.20 | 6.67 | 6.10 | 6.20 | -7.1 | 45.50 | 538.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -2.7 | 21-JAN-20:00 | -1.1 | -5.6 | 0.00 | -9.0 | 0.00 | 0.00 |
February | 1.24 | 09-FEB-01:00 | 2.80 | -1.1 | 8.80 | -4.1 | 0.00 | 0.00 |
March | 2.65 | 20-MAR-13:00 | 6.70 | -3.3 | 0.00 | -7.6 | 139.00 | 515.00 |
April | 7.03 | 22-APR-13:00 | 15.60 | -3.3 | 4.10 | -0.8 | 117.50 | 760.50 |
May | 10.97 | 31-MAY-17:00 | 21.70 | 0.00 | 2.60 | 11.07 | 73.50 | 187.00 |
June | 18.33 | 30-JUN-11:00 | 25.60 | 14.40 | 1.50 | 15.21 | 221.00 | 616.00 |
July | 18.36 | 29-JUL-17:19 | 29.07 | 12.23 | 3.10 | 19.29 | 141.00 | 225.33 |
August | 16.14 | 04-AUG-19:00 | 21.70 | 12.80 | 3.10 | 14.28 | 25.50 | 28.50 |
September | 10.82 | 01-SEP-15:00 | 15.60 | 6.70 | 2.60 | 4.31 | 145.50 | 176.00 |
October | 8.01 | 01-OCT-14:00 | 13.90 | 1.70 | 2.60 | 1.58 | 78.50 | 227.50 |
November | -5.6 | 18-NOV-03:00 | -3.9 | -8.9 | 1.50 | -12.4 | 0.00 | 0.00 |
December | -0.1 | 24-DEC-11:00 | 1.70 | -2.8 | 2.60 | -8.8 | 13.50 | 31.50 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -3.9 | -8.9 | 0.00 | -12.4 | 0.00 | 0.00 | |
Maximum of Months | 18.36 | 29.07 | 14.40 | 8.80 | 19.29 | 221.00 | 760.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 06-JAN-19:00 | -1.7 | -2.7 | 2.60 | -12.4 | 0.00 | 0.00 |
February | -0.6 | 09-FEB-00:00 | 1.70 | 0.78 | 3.60 | -5.0 | 0.00 | 0.00 |
March | 0.00 | 21-MAR-15:00 | 1.10 | 0.62 | 2.10 | -5.5 | 70.50 | 4.00 |
April | 0.00 | 30-APR-07:00 | 3.30 | 1.91 | 2.60 | -8.3 | 198.00 | 170.00 |
May | 6.10 | 16-MAY-19:00 | 8.90 | 7.49 | 5.20 | 3.69 | 16.00 | 15.00 |
June | 15.60 | 30-JUN-17:00 | 18.90 | 16.75 | 3.60 | 12.22 | 99.50 | 223.00 |
July | 17.80 | 03-JUL-14:00 | 19.40 | 18.27 | 1.50 | 10.11 | 223.00 | 401.50 |
August | 15.00 | 12-AUG-22:00 | 16.10 | 15.38 | 0.00 | 12.79 | 0.00 | 0.00 |
September | 8.90 | 04-SEP-11:00 | 10.00 | 9.41 | 2.60 | 5.33 | 238.50 | 0.50 |
October | 5.60 | 02-OCT-11:09 | 7.30 | 6.41 | 4.95 | 0.30 | 123.67 | 16.00 |
November | -8.3 | 18-NOV-04:00 | -5.0 | -6.1 | 1.50 | -13.4 | 0.00 | 0.00 |
December | -2.8 | 24-DEC-09:00 | 1.10 | -0.5 | 3.10 | -6.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -8.3 | -5.0 | -6.1 | 0.00 | -13.4 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 19.40 | 18.27 | 5.20 | 12.79 | 238.50 | 401.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 0.00 | 1.10 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.00 | 5.89 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.00 | 18.25 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 0.00 | 35.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 0.44 | 43.39 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 2.62 | 46.67 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 4.74 | 42.09 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 6.08 | 32.30 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 6.25 | 18.21 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 5.21 | 8.04 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 3.27 | 2.12 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 0.94 | 0.28 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 2.48 | 21.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.00 | 0.28 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 6.25 | 46.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.482019E+11 | -0.477512E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -450717470.9 | 60.05 | 0.00 | 0.00 |
February | 0.437955E+11 | -0.433912E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -404226108.8 | 60.05 | 0.00 | 0.00 |
March | 0.514972E+11 | -0.510525E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -444723945.6 | 60.05 | 0.00 | 0.00 |
April | 0.466839E+11 | -0.462847E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -399155249.8 | 60.05 | 0.00 | 0.00 |
May | 0.494462E+11 | -0.490639E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -382292250.2 | 60.05 | 0.00 | 0.00 |
June | 0.472532E+11 | -0.468870E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -366201330.2 | 60.05 | 0.00 | 0.00 |
July | 0.433011E+11 | -0.429257E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -375409087.4 | 60.05 | 0.00 | 0.00 |
August | 0.462518E+11 | -0.458795E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -372287821.1 | 60.05 | 0.00 | 0.00 |
September | 0.418354E+11 | -0.414691E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -366258612.0 | 60.05 | 0.00 | 0.00 |
October | 0.440278E+11 | -0.436116E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -416151722.0 | 60.05 | 0.00 | 0.00 |
November | 0.447335E+11 | -0.443026E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -430916509.5 | 60.05 | 0.00 | 0.00 |
December | 0.463286E+11 | -0.458833E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -445379161.9 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.553356E+12 | -0.548502E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.485372E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.418354E+11 | -0.510525E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -450717470.9 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.514972E+11 | -0.414691E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -366201330.2 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.62 | 0.48 | 10-JAN-10:00 | 900.31 | 29.91 | 85.17 | 77.00 | 701.63 | 31.38 | 86.67 | 50.50 |
February | 205.83 | 0.54 | 0.48 | 01-FEB-11:39 | 3060.96 | 35.23 | 190.33 | 177.00 | 2579.79 | 36.40 | 191.83 | 161.17 |
March | 329.50 | 0.52 | 0.48 | 01-MAR-09:09 | 6800.59 | 33.34 | 285.67 | 302.17 | 5872.80 | 34.46 | 291.17 | 285.50 |
April | 421.83 | 0.52 | 0.48 | 01-APR-07:40 | 9592.17 | 32.12 | 309.17 | 390.33 | 1885.50 | 22.55 | 319.50 | 349.67 |
May | 545.00 | 0.54 | 0.48 | 01-MAY-05:40 | 5457.48 | 24.04 | 304.67 | 465.33 | 1377.68 | 21.25 | 347.33 | 412.83 |
June | 583.50 | 0.55 | 0.48 | 01-JUN-05:19 | 2304.85 | 19.60 | 270.83 | 489.50 | 1260.45 | 21.03 | 363.83 | 428.83 |
July | 562.83 | 0.54 | 0.48 | 01-JUL-04:00 | 2734.64 | 20.15 | 272.67 | 486.00 | 1286.30 | 21.06 | 340.50 | 418.00 |
August | 467.17 | 0.53 | 0.48 | 01-AUG-05:49 | 6857.26 | 27.88 | 305.83 | 415.17 | 1452.07 | 21.68 | 300.83 | 368.83 |
September | 356.33 | 0.53 | 0.48 | 01-SEP-06:49 | 5556.81 | 31.42 | 286.83 | 321.83 | 1899.24 | 23.02 | 250.17 | 287.00 |
October | 265.50 | 0.53 | 0.48 | 01-OCT-07:00 | 3105.95 | 32.81 | 235.83 | 238.33 | 2528.03 | 33.38 | 235.33 | 216.33 |
November | 135.83 | 0.56 | 0.48 | 01-NOV-09:00 | 1218.76 | 30.92 | 105.17 | 125.33 | 946.08 | 32.59 | 106.83 | 99.33 |
December | 71.17 | 0.82 | 0.48 | 05-DEC-11:30 | 215.37 | 9.03 | 0.00 | 14.33 | 140.07 | 12.31 | 0.00 | 1.83 |
Annual Sum or Average | 4053.17 | 0.54 | 4703.09 | 26.82 | 2652.17 | 3502.33 | 1902.90 | 24.67 | 2834.00 | 3079.83 | ||
Minimum of Months | 71.17 | 0.52 | 0.48 | 215.37 | 9.03 | 0.00 | 14.33 | 140.07 | 12.31 | 0.00 | 1.83 | |
Maximum of Months | 583.50 | 0.82 | 0.48 | 9592.17 | 35.23 | 309.17 | 489.50 | 5872.80 | 36.40 | 363.83 | 428.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.74 | 0.48 | 16-JAN-12:20 | 340.35 | 13.73 | 2.00 | 42.33 | 203.50 | 15.00 | 9.83 | 15.17 |
February | 205.83 | 0.60 | 0.48 | 02-FEB-10:09 | 1179.90 | 21.78 | 80.50 | 150.83 | 731.73 | 23.05 | 97.50 | 110.17 |
March | 329.50 | 0.54 | 0.48 | 01-MAR-09:09 | 2849.65 | 25.16 | 172.00 | 286.00 | 1766.13 | 25.36 | 209.17 | 254.83 |
April | 421.83 | 0.51 | 0.48 | 01-APR-06:00 | 3587.12 | 26.50 | 221.33 | 396.00 | 2183.26 | 26.89 | 299.50 | 359.17 |
May | 545.00 | 0.54 | 0.48 | 01-MAY-04:40 | 4690.39 | 25.74 | 261.00 | 474.00 | 2418.14 | 25.28 | 328.33 | 434.00 |
June | 583.50 | 0.54 | 0.48 | 01-JUN-03:49 | 4049.66 | 25.02 | 286.17 | 507.83 | 1784.29 | 24.28 | 364.33 | 454.00 |
July | 562.83 | 0.54 | 0.48 | 01-JUL-03:49 | 4026.18 | 24.98 | 281.00 | 493.67 | 2075.37 | 24.77 | 356.67 | 440.00 |
August | 467.17 | 0.53 | 0.48 | 01-AUG-04:00 | 3371.10 | 24.81 | 233.83 | 416.83 | 1687.26 | 24.40 | 279.67 | 373.83 |
September | 356.33 | 0.55 | 0.48 | 01-SEP-06:19 | 2614.77 | 24.57 | 175.33 | 309.67 | 1337.00 | 24.03 | 208.67 | 269.17 |
October | 265.50 | 0.56 | 0.48 | 01-OCT-07:49 | 1374.36 | 22.25 | 103.17 | 219.33 | 776.96 | 22.22 | 116.50 | 173.67 |
November | 135.83 | 0.68 | 0.48 | 01-NOV-10:09 | 461.39 | 18.64 | 35.00 | 81.17 | 227.27 | 16.85 | 8.67 | 18.83 |
December | 71.17 | 0.93 | 0.70 | 04-DEC-10:00 | 116.05 | 8.94 | 0.00 | 0.00 | 65.61 | 9.85 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.56 | 3172.76 | 24.07 | 1851.33 | 3377.67 | 1655.30 | 23.89 | 2278.83 | 2902.83 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 116.05 | 8.94 | 0.00 | 0.00 | 65.61 | 9.85 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.93 | 0.70 | 4690.39 | 26.50 | 286.17 | 507.83 | 2418.14 | 26.89 | 364.33 | 454.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.84 | 0.52 | 28-JAN-12:09 | 198.14 | 10.47 | 0.00 | 11.00 | 112.60 | 12.06 | 0.00 | 0.00 |
February | 205.83 | 0.65 | 0.48 | 12-FEB-11:00 | 437.10 | 14.71 | 0.00 | 127.33 | 252.90 | 16.28 | 0.00 | 45.50 |
March | 329.50 | 0.55 | 0.48 | 01-MAR-09:00 | 805.89 | 17.85 | 1.83 | 279.17 | 471.74 | 19.33 | 82.50 | 224.33 |
April | 421.83 | 0.51 | 0.48 | 01-APR-07:49 | 1067.06 | 20.02 | 38.50 | 402.00 | 652.84 | 21.45 | 246.50 | 358.33 |
May | 545.00 | 0.51 | 0.48 | 01-MAY-04:40 | 1314.06 | 24.08 | 212.83 | 506.50 | 748.03 | 23.97 | 406.33 | 473.83 |
June | 583.50 | 0.51 | 0.48 | 01-JUN-03:49 | 1564.85 | 25.18 | 293.50 | 544.17 | 884.42 | 25.31 | 491.50 | 507.67 |
July | 562.83 | 0.52 | 0.48 | 01-JUL-03:49 | 1411.18 | 23.90 | 241.67 | 524.00 | 792.61 | 24.09 | 424.50 | 475.50 |
August | 467.17 | 0.52 | 0.48 | 01-AUG-04:00 | 1092.71 | 21.37 | 105.17 | 431.50 | 642.50 | 22.62 | 280.33 | 384.50 |
September | 356.33 | 0.55 | 0.48 | 01-SEP-06:49 | 785.24 | 17.96 | 2.33 | 306.33 | 448.50 | 19.28 | 74.17 | 239.83 |
October | 265.50 | 0.59 | 0.48 | 01-OCT-08:20 | 545.04 | 16.08 | 0.00 | 205.00 | 299.25 | 17.44 | 0.00 | 81.17 |
November | 135.83 | 0.77 | 0.52 | 01-NOV-10:20 | 264.43 | 12.42 | 0.00 | 37.50 | 148.67 | 14.16 | 0.00 | 0.00 |
December | 71.17 | 0.97 | 0.83 | 05-DEC-11:30 | 78.27 | 5.61 | 0.00 | 0.00 | 44.71 | 7.13 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.56 | 1042.93 | 20.35 | 895.83 | 3374.50 | 598.98 | 21.21 | 2005.83 | 2790.67 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 78.27 | 5.61 | 0.00 | 0.00 | 44.71 | 7.13 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.97 | 0.83 | 1564.85 | 25.18 | 293.50 | 544.17 | 884.42 | 25.31 | 491.50 | 507.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.76 | 0.48 | 23-JAN-13:20 | 287.14 | 13.69 | 1.83 | 31.00 | 169.00 | 14.97 | 3.00 | 6.67 |
February | 205.83 | 0.58 | 0.48 | 02-FEB-11:30 | 949.30 | 22.18 | 72.67 | 161.17 | 574.15 | 23.53 | 94.83 | 102.67 |
March | 329.50 | 0.53 | 0.48 | 01-MAR-09:00 | 2124.85 | 24.67 | 153.33 | 297.67 | 1248.39 | 24.98 | 219.67 | 267.50 |
April | 421.83 | 0.52 | 0.48 | 01-APR-08:30 | 4089.06 | 25.49 | 195.33 | 396.33 | 2015.48 | 24.91 | 278.33 | 358.83 |
May | 545.00 | 0.52 | 0.48 | 01-MAY-06:40 | 3196.28 | 22.61 | 187.33 | 493.67 | 1580.78 | 22.64 | 298.50 | 450.00 |
June | 583.50 | 0.52 | 0.48 | 01-JUN-05:40 | 3374.47 | 22.18 | 186.00 | 523.00 | 1693.05 | 22.37 | 335.17 | 472.00 |
July | 562.83 | 0.52 | 0.48 | 01-JUL-04:00 | 2934.11 | 22.03 | 187.83 | 511.50 | 1503.15 | 22.23 | 306.17 | 460.33 |
August | 467.17 | 0.51 | 0.48 | 01-AUG-06:19 | 2665.44 | 23.11 | 183.67 | 431.17 | 1587.20 | 23.85 | 268.83 | 388.67 |
September | 356.33 | 0.53 | 0.48 | 01-SEP-06:00 | 2131.98 | 24.71 | 153.33 | 321.00 | 1277.32 | 25.04 | 217.50 | 276.67 |
October | 265.50 | 0.54 | 0.48 | 01-OCT-08:39 | 1085.96 | 23.38 | 97.17 | 227.50 | 616.58 | 23.66 | 105.83 | 170.00 |
November | 135.83 | 0.67 | 0.48 | 01-NOV-10:50 | 462.22 | 20.48 | 45.33 | 82.33 | 289.89 | 21.45 | 46.67 | 31.50 |
December | 71.17 | 0.95 | 0.70 | 04-DEC-11:20 | 100.90 | 8.78 | 0.00 | 0.00 | 56.71 | 9.67 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.54 | 2560.27 | 22.65 | 1463.83 | 3476.33 | 1356.29 | 22.96 | 2174.50 | 2984.83 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 100.90 | 8.78 | 0.00 | 0.00 | 56.71 | 9.67 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.95 | 0.70 | 4089.06 | 25.49 | 195.33 | 523.00 | 2015.48 | 25.04 | 335.17 | 472.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.63 | 0.48 | 10-JAN-10:00 | 717.43 | 7.52 | 6.00 | 73.33 | 737.00 | 30.13 | 85.17 | 53.33 |
February | 205.83 | 0.54 | 0.48 | 01-FEB-11:30 | 3088.37 | 34.71 | 188.67 | 177.33 | 2671.88 | 35.98 | 190.67 | 163.17 |
March | 329.50 | 0.52 | 0.48 | 01-MAR-09:09 | 6859.02 | 32.34 | 275.50 | 302.17 | 6011.38 | 33.82 | 282.33 | 286.83 |
April | 421.83 | 0.52 | 0.48 | 01-APR-07:40 | 9644.37 | 30.31 | 283.67 | 390.67 | 2023.51 | 18.22 | 29.50 | 354.33 |
May | 545.00 | 0.54 | 0.48 | 01-MAY-05:30 | 5499.00 | 20.02 | 144.33 | 465.67 | 1475.83 | 17.23 | 12.33 | 419.67 |
June | 583.50 | 0.55 | 0.48 | 01-JUN-05:19 | 2333.17 | 13.59 | 0.00 | 490.00 | 1345.37 | 16.93 | 7.50 | 436.00 |
July | 562.83 | 0.54 | 0.48 | 01-JUL-04:49 | 2764.34 | 14.28 | 15.67 | 486.17 | 1373.20 | 16.89 | 9.00 | 424.83 |
August | 467.17 | 0.53 | 0.48 | 01-AUG-05:49 | 6892.62 | 25.13 | 239.00 | 415.67 | 1553.99 | 17.31 | 11.33 | 375.00 |
September | 356.33 | 0.53 | 0.48 | 01-SEP-06:49 | 5591.64 | 30.08 | 270.67 | 322.17 | 2003.95 | 18.94 | 39.50 | 290.17 |
October | 265.50 | 0.53 | 0.48 | 01-OCT-07:00 | 3128.70 | 31.60 | 229.67 | 238.50 | 2605.59 | 33.35 | 235.67 | 218.17 |
November | 135.83 | 0.56 | 0.48 | 01-NOV-09:00 | 1191.39 | 26.47 | 94.17 | 124.33 | 987.74 | 31.02 | 105.17 | 102.17 |
December | 71.17 | 0.82 | 0.48 | 05-DEC-11:30 | 200.41 | 2.49 | 0.00 | 12.00 | 146.04 | 6.04 | 0.00 | 2.50 |
Annual Sum or Average | 4053.17 | 0.54 | 4730.99 | 22.92 | 1747.33 | 3498.00 | 1999.18 | 21.37 | 1008.17 | 3126.17 | ||
Minimum of Months | 71.17 | 0.52 | 0.48 | 200.41 | 2.49 | 0.00 | 12.00 | 146.04 | 6.04 | 0.00 | 2.50 | |
Maximum of Months | 583.50 | 0.82 | 0.48 | 9644.37 | 34.71 | 283.67 | 490.00 | 6011.38 | 35.98 | 282.33 | 436.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.73 | 0.48 | 16-JAN-11:00 | 344.84 | 10.68 | 2.00 | 43.83 | 212.32 | 13.45 | 5.00 | 15.83 |
February | 205.83 | 0.60 | 0.48 | 02-FEB-10:09 | 1199.32 | 19.67 | 65.83 | 151.83 | 760.85 | 21.78 | 83.00 | 115.00 |
March | 329.50 | 0.54 | 0.48 | 01-MAR-09:09 | 2826.65 | 21.46 | 113.83 | 286.00 | 1833.28 | 23.82 | 146.33 | 257.50 |
April | 421.83 | 0.51 | 0.48 | 01-APR-06:49 | 3627.43 | 22.92 | 135.50 | 396.00 | 2264.67 | 25.09 | 178.00 | 363.17 |
May | 545.00 | 0.53 | 0.48 | 01-MAY-04:40 | 4762.35 | 23.35 | 206.83 | 475.50 | 2508.85 | 23.25 | 158.67 | 438.33 |
June | 583.50 | 0.54 | 0.48 | 01-JUN-03:49 | 4110.81 | 22.55 | 219.83 | 509.33 | 1863.97 | 22.12 | 150.50 | 459.67 |
July | 562.83 | 0.54 | 0.48 | 01-JUL-03:49 | 4081.10 | 21.89 | 200.33 | 495.50 | 2155.52 | 22.77 | 171.33 | 444.17 |
August | 467.17 | 0.53 | 0.48 | 01-AUG-04:49 | 3407.64 | 22.11 | 167.50 | 417.17 | 1761.03 | 22.26 | 131.33 | 379.33 |
September | 356.33 | 0.55 | 0.48 | 01-SEP-06:19 | 2627.50 | 21.23 | 131.83 | 310.50 | 1391.89 | 22.17 | 129.50 | 274.17 |
October | 265.50 | 0.56 | 0.48 | 01-OCT-07:49 | 1396.74 | 19.93 | 96.67 | 220.17 | 822.76 | 20.81 | 83.00 | 178.83 |
November | 135.83 | 0.67 | 0.48 | 01-NOV-09:00 | 467.93 | 16.20 | 34.33 | 83.00 | 276.99 | 18.64 | 36.50 | 28.67 |
December | 71.17 | 0.93 | 0.57 | 04-DEC-11:30 | 117.36 | 6.44 | 0.00 | 0.17 | 68.67 | 8.80 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.56 | 3209.33 | 21.22 | 1374.50 | 3389.00 | 1723.80 | 22.14 | 1273.17 | 2954.67 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 117.36 | 6.44 | 0.00 | 0.17 | 68.67 | 8.80 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.93 | 0.57 | 4762.35 | 23.35 | 219.83 | 509.33 | 2508.85 | 25.09 | 178.00 | 459.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.84 | 0.52 | 26-JAN-12:09 | 198.66 | 4.60 | 0.00 | 11.00 | 119.07 | 7.83 | 0.00 | 0.00 |
February | 205.83 | 0.64 | 0.48 | 11-FEB-12:30 | 440.29 | 8.92 | 0.00 | 128.33 | 268.02 | 12.37 | 0.00 | 55.17 |
March | 329.50 | 0.55 | 0.48 | 01-MAR-09:00 | 815.80 | 12.56 | 0.00 | 279.67 | 501.07 | 15.92 | 0.00 | 232.50 |
April | 421.83 | 0.51 | 0.48 | 01-APR-07:49 | 1084.23 | 14.93 | 0.00 | 402.33 | 694.59 | 18.42 | 8.83 | 364.83 |
May | 545.00 | 0.51 | 0.48 | 01-MAY-04:40 | 1337.19 | 20.15 | 145.33 | 506.67 | 818.29 | 22.08 | 138.00 | 484.50 |
June | 583.50 | 0.51 | 0.48 | 01-JUN-03:39 | 1588.58 | 20.47 | 174.33 | 543.17 | 936.53 | 22.57 | 154.17 | 510.50 |
July | 562.83 | 0.51 | 0.48 | 01-JUL-03:49 | 1426.38 | 19.20 | 138.83 | 524.33 | 840.72 | 21.25 | 124.50 | 481.67 |
August | 467.17 | 0.52 | 0.48 | 01-AUG-04:00 | 1109.39 | 16.74 | 63.50 | 432.17 | 682.01 | 19.77 | 73.33 | 391.17 |
September | 356.33 | 0.55 | 0.48 | 01-SEP-06:49 | 795.47 | 12.59 | 0.00 | 306.50 | 476.42 | 15.89 | 0.83 | 252.17 |
October | 265.50 | 0.58 | 0.48 | 01-OCT-08:09 | 550.67 | 10.19 | 0.00 | 205.33 | 317.37 | 13.55 | 0.00 | 105.83 |
November | 135.83 | 0.77 | 0.48 | 01-NOV-13:30 | 265.64 | 6.20 | 0.00 | 38.50 | 157.31 | 9.78 | 0.00 | 1.33 |
December | 71.17 | 0.97 | 0.83 | 04-DEC-11:30 | 78.20 | 1.13 | 0.00 | 0.00 | 47.21 | 3.36 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.55 | 1057.56 | 15.41 | 522.00 | 3378.00 | 638.81 | 18.17 | 499.67 | 2879.67 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 78.20 | 1.13 | 0.00 | 0.00 | 47.21 | 3.36 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.97 | 0.83 | 1588.58 | 20.47 | 174.33 | 543.17 | 936.53 | 22.57 | 154.17 | 510.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.76 | 0.48 | 23-JAN-13:20 | 291.25 | 10.46 | 1.67 | 31.83 | 176.58 | 13.33 | 2.50 | 7.67 |
February | 205.83 | 0.58 | 0.48 | 02-FEB-11:20 | 964.71 | 19.94 | 61.83 | 161.67 | 597.34 | 22.18 | 75.33 | 110.83 |
March | 329.50 | 0.53 | 0.48 | 01-MAR-09:00 | 2133.97 | 21.20 | 99.00 | 296.83 | 1299.10 | 23.36 | 116.83 | 271.17 |
April | 421.83 | 0.51 | 0.48 | 01-APR-08:20 | 4150.99 | 22.88 | 139.50 | 396.83 | 2095.86 | 22.72 | 134.67 | 364.00 |
May | 545.00 | 0.52 | 0.48 | 01-MAY-06:40 | 3242.27 | 19.46 | 118.00 | 493.17 | 1649.43 | 20.01 | 63.17 | 455.17 |
June | 583.50 | 0.52 | 0.48 | 01-JUN-05:40 | 3423.77 | 18.87 | 111.50 | 523.33 | 1761.93 | 19.72 | 55.83 | 477.67 |
July | 562.83 | 0.52 | 0.48 | 01-JUL-04:00 | 2981.32 | 18.81 | 114.83 | 511.83 | 1566.93 | 19.61 | 66.33 | 464.67 |
August | 467.17 | 0.51 | 0.48 | 01-AUG-06:10 | 2712.45 | 20.13 | 117.67 | 432.67 | 1648.26 | 21.59 | 108.50 | 394.00 |
September | 356.33 | 0.53 | 0.48 | 01-SEP-06:00 | 2161.36 | 22.12 | 120.67 | 322.00 | 1324.22 | 23.27 | 115.50 | 282.50 |
October | 265.50 | 0.54 | 0.48 | 01-OCT-08:30 | 1100.25 | 20.14 | 86.83 | 227.50 | 642.17 | 22.04 | 76.33 | 177.67 |
November | 135.83 | 0.66 | 0.48 | 01-NOV-10:30 | 469.63 | 18.36 | 45.17 | 83.67 | 302.32 | 20.59 | 46.17 | 33.83 |
December | 71.17 | 0.95 | 0.70 | 04-DEC-11:20 | 102.15 | 6.14 | 0.00 | 0.00 | 59.37 | 8.56 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.54 | 2597.40 | 19.65 | 1016.67 | 3481.33 | 1411.47 | 20.82 | 861.17 | 3039.17 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 102.15 | 6.14 | 0.00 | 0.00 | 59.37 | 8.56 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.95 | 0.70 | 4150.99 | 22.88 | 139.50 | 523.33 | 2095.86 | 23.36 | 134.67 | 477.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.63 | 0.48 | 10-JAN-10:00 | 717.36 | 7.49 | 6.00 | 73.33 | 737.38 | 30.12 | 85.17 | 53.50 |
February | 205.83 | 0.54 | 0.48 | 01-FEB-11:30 | 3088.44 | 34.71 | 188.67 | 177.33 | 2673.16 | 35.97 | 190.67 | 163.33 |
March | 329.50 | 0.52 | 0.48 | 01-MAR-09:09 | 6860.43 | 32.33 | 275.50 | 302.17 | 6013.94 | 33.81 | 282.33 | 287.00 |
April | 421.83 | 0.52 | 0.48 | 01-APR-07:40 | 9647.11 | 30.29 | 283.67 | 390.67 | 2026.43 | 18.21 | 29.17 | 354.33 |
May | 545.00 | 0.54 | 0.48 | 01-MAY-05:30 | 5502.10 | 19.99 | 144.33 | 465.67 | 1478.02 | 17.21 | 12.17 | 419.67 |
June | 583.50 | 0.55 | 0.48 | 01-JUN-05:19 | 2336.56 | 13.56 | 0.00 | 490.00 | 1347.56 | 16.92 | 7.33 | 436.33 |
July | 562.83 | 0.54 | 0.48 | 01-JUL-04:49 | 2767.75 | 14.25 | 15.67 | 486.17 | 1375.46 | 16.88 | 8.67 | 425.00 |
August | 467.17 | 0.53 | 0.48 | 01-AUG-05:49 | 6895.69 | 25.11 | 239.00 | 416.00 | 1556.43 | 17.30 | 11.33 | 375.33 |
September | 356.33 | 0.53 | 0.48 | 01-SEP-06:49 | 5593.64 | 30.06 | 270.67 | 322.17 | 2006.27 | 18.93 | 39.50 | 290.17 |
October | 265.50 | 0.53 | 0.48 | 01-OCT-07:00 | 3129.80 | 31.59 | 229.67 | 238.67 | 2606.99 | 33.35 | 235.67 | 218.67 |
November | 135.83 | 0.56 | 0.48 | 01-NOV-09:00 | 1191.44 | 26.45 | 94.17 | 124.33 | 988.32 | 31.01 | 105.17 | 102.17 |
December | 71.17 | 0.82 | 0.48 | 05-DEC-11:30 | 200.36 | 2.46 | 0.00 | 12.17 | 146.17 | 6.02 | 0.00 | 2.50 |
Annual Sum or Average | 4053.17 | 0.54 | 4733.37 | 22.90 | 1747.33 | 3498.67 | 2001.29 | 21.36 | 1007.17 | 3128.00 | ||
Minimum of Months | 71.17 | 0.52 | 0.48 | 200.36 | 2.46 | 0.00 | 12.17 | 146.17 | 6.02 | 0.00 | 2.50 | |
Maximum of Months | 583.50 | 0.82 | 0.48 | 9647.11 | 34.71 | 283.67 | 490.00 | 6013.94 | 35.97 | 282.33 | 436.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.73 | 0.48 | 16-JAN-11:00 | 345.09 | 10.65 | 2.00 | 44.17 | 212.62 | 13.43 | 5.00 | 15.83 |
February | 205.83 | 0.60 | 0.48 | 01-FEB-12:30 | 1199.88 | 19.65 | 65.83 | 152.17 | 761.56 | 21.77 | 82.50 | 115.50 |
March | 329.50 | 0.54 | 0.48 | 01-MAR-09:09 | 2827.77 | 21.43 | 113.83 | 286.00 | 1834.74 | 23.81 | 145.83 | 257.67 |
April | 421.83 | 0.51 | 0.48 | 01-APR-06:49 | 3628.78 | 22.89 | 135.50 | 396.00 | 2266.45 | 25.08 | 177.50 | 363.50 |
May | 545.00 | 0.53 | 0.48 | 01-MAY-04:40 | 4764.02 | 23.32 | 206.83 | 475.50 | 2510.76 | 23.24 | 157.50 | 438.50 |
June | 583.50 | 0.54 | 0.48 | 01-JUN-03:49 | 4113.07 | 22.53 | 219.83 | 509.33 | 1866.03 | 22.10 | 148.83 | 459.83 |
July | 562.83 | 0.54 | 0.48 | 01-JUL-03:49 | 4083.19 | 21.87 | 200.33 | 495.67 | 2157.49 | 22.76 | 170.67 | 444.33 |
August | 467.17 | 0.53 | 0.48 | 01-AUG-04:49 | 3409.50 | 22.08 | 167.50 | 417.17 | 1762.86 | 22.25 | 130.67 | 379.33 |
September | 356.33 | 0.55 | 0.48 | 01-SEP-06:19 | 2628.86 | 21.21 | 131.83 | 310.50 | 1393.33 | 22.16 | 129.17 | 274.33 |
October | 265.50 | 0.56 | 0.48 | 01-OCT-07:49 | 1397.71 | 19.91 | 96.67 | 220.33 | 823.69 | 20.80 | 83.00 | 179.33 |
November | 135.83 | 0.67 | 0.48 | 01-NOV-09:00 | 468.28 | 16.18 | 34.33 | 83.00 | 277.38 | 18.63 | 36.50 | 28.67 |
December | 71.17 | 0.93 | 0.57 | 04-DEC-11:30 | 117.44 | 6.41 | 0.00 | 0.17 | 68.78 | 8.78 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.56 | 3210.85 | 21.19 | 1374.50 | 3390.00 | 1725.39 | 22.13 | 1267.17 | 2956.83 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 117.44 | 6.41 | 0.00 | 0.17 | 68.78 | 8.78 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.93 | 0.57 | 4764.02 | 23.32 | 219.83 | 509.33 | 2510.76 | 25.08 | 177.50 | 459.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.84 | 0.52 | 26-JAN-12:09 | 198.84 | 4.57 | 0.00 | 11.00 | 119.25 | 7.82 | 0.00 | 0.00 |
February | 205.83 | 0.64 | 0.48 | 11-FEB-12:30 | 440.69 | 8.89 | 0.00 | 128.33 | 268.41 | 12.35 | 0.00 | 55.17 |
March | 329.50 | 0.55 | 0.48 | 01-MAR-09:00 | 816.58 | 12.53 | 0.00 | 279.67 | 501.78 | 15.91 | 0.00 | 232.67 |
April | 421.83 | 0.51 | 0.48 | 01-APR-07:49 | 1085.07 | 14.90 | 0.00 | 402.33 | 695.47 | 18.40 | 8.67 | 365.00 |
May | 545.00 | 0.51 | 0.48 | 01-MAY-04:40 | 1338.20 | 20.12 | 145.33 | 506.67 | 819.29 | 22.06 | 137.50 | 484.83 |
June | 583.50 | 0.51 | 0.48 | 01-JUN-03:39 | 1589.87 | 20.44 | 174.33 | 543.17 | 937.72 | 22.56 | 153.67 | 510.67 |
July | 562.83 | 0.51 | 0.48 | 01-JUL-03:49 | 1427.72 | 19.18 | 138.83 | 524.33 | 841.86 | 21.24 | 124.17 | 482.00 |
August | 467.17 | 0.52 | 0.48 | 01-AUG-04:00 | 1110.53 | 16.71 | 63.50 | 432.17 | 682.97 | 19.76 | 73.00 | 391.17 |
September | 356.33 | 0.55 | 0.48 | 01-SEP-06:49 | 796.34 | 12.57 | 0.00 | 306.50 | 477.14 | 15.88 | 0.83 | 252.50 |
October | 265.50 | 0.58 | 0.48 | 01-OCT-08:09 | 551.37 | 10.16 | 0.00 | 205.33 | 317.90 | 13.53 | 0.00 | 106.67 |
November | 135.83 | 0.77 | 0.48 | 01-NOV-13:30 | 265.91 | 6.17 | 0.00 | 38.50 | 157.56 | 9.76 | 0.00 | 1.33 |
December | 71.17 | 0.97 | 0.83 | 04-DEC-11:30 | 78.26 | 1.12 | 0.00 | 0.00 | 47.28 | 3.35 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.55 | 1058.51 | 15.38 | 522.00 | 3378.00 | 639.66 | 18.15 | 497.83 | 2882.00 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 78.26 | 1.12 | 0.00 | 0.00 | 47.28 | 3.35 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.97 | 0.83 | 1589.87 | 20.44 | 174.33 | 543.17 | 937.72 | 22.56 | 153.67 | 510.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 108.67 | 0.76 | 0.48 | 23-JAN-13:20 | 291.49 | 10.43 | 1.67 | 31.83 | 176.84 | 13.32 | 2.33 | 8.00 |
February | 205.83 | 0.58 | 0.48 | 02-FEB-11:20 | 965.24 | 19.91 | 61.83 | 161.67 | 597.95 | 22.16 | 75.17 | 111.17 |
March | 329.50 | 0.53 | 0.48 | 01-MAR-09:00 | 2135.03 | 21.18 | 99.00 | 296.83 | 1300.23 | 23.34 | 116.67 | 271.17 |
April | 421.83 | 0.51 | 0.48 | 01-APR-08:20 | 4152.26 | 22.85 | 139.50 | 396.83 | 2097.57 | 22.71 | 134.17 | 364.17 |
May | 545.00 | 0.52 | 0.48 | 01-MAY-06:40 | 3243.84 | 19.44 | 118.00 | 493.33 | 1651.04 | 19.99 | 62.50 | 455.50 |
June | 583.50 | 0.52 | 0.48 | 01-JUN-05:40 | 3425.69 | 18.84 | 111.50 | 523.33 | 1763.67 | 19.71 | 54.83 | 477.67 |
July | 562.83 | 0.52 | 0.48 | 01-JUL-04:00 | 2983.31 | 18.78 | 114.83 | 511.83 | 1568.66 | 19.59 | 65.83 | 464.83 |
August | 467.17 | 0.51 | 0.48 | 01-AUG-06:10 | 2714.16 | 20.10 | 117.67 | 432.67 | 1649.79 | 21.58 | 108.17 | 394.00 |
September | 356.33 | 0.53 | 0.48 | 01-SEP-06:00 | 2162.57 | 22.10 | 120.67 | 322.00 | 1325.38 | 23.26 | 114.83 | 282.50 |
October | 265.50 | 0.54 | 0.48 | 01-OCT-08:30 | 1101.14 | 20.12 | 86.50 | 227.67 | 642.94 | 22.03 | 76.33 | 178.00 |
November | 135.83 | 0.66 | 0.48 | 01-NOV-10:30 | 469.98 | 18.34 | 45.17 | 83.83 | 302.70 | 20.57 | 46.17 | 34.00 |
December | 71.17 | 0.95 | 0.70 | 04-DEC-11:20 | 102.24 | 6.11 | 0.00 | 0.00 | 59.47 | 8.55 | 0.00 | 0.00 |
Annual Sum or Average | 4053.17 | 0.54 | 2598.79 | 19.62 | 1016.33 | 3481.83 | 1412.82 | 20.80 | 857.00 | 3041.00 | ||
Minimum of Months | 71.17 | 0.51 | 0.48 | 102.24 | 6.11 | 0.00 | 0.00 | 59.47 | 8.55 | 0.00 | 0.00 | |
Maximum of Months | 583.50 | 0.95 | 0.70 | 4152.26 | 22.85 | 139.50 | 523.33 | 2097.57 | 23.34 | 134.17 | 477.67 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.203606E+11 | 95274.68 | 12-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123622E+11 | 87723.61 | 27-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.451760E+10 | 75326.31 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.366790E+09 | 57344.48 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 418698.69 | 381.21 | 27-MAY-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1.43 | 0.00 | 22-JUL-03:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 738.30 | 0.77 | 03-AUG-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 35762614.13 | 11969.93 | 29-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.546625E+09 | 51764.92 | 27-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.189094E+11 | 77065.18 | 29-NOV-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.301654E+11 | 86517.52 | 15-DEC-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.872647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.301654E+11 | 95274.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 3350570.66 | 3875.21 | 02-JAN-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3350570.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 3350570.66 | 3875.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.405879E+10 | 15615.43 | 03-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.198220E+10 | 16768.53 | 15-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.744381E+09 | 16965.13 | 28-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 32353689.39 | 16868.80 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.289168E+09 | 16862.98 | 23-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.201547E+10 | 15572.82 | 08-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.304634E+10 | 16196.64 | 21-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.121687E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.405879E+10 | 16965.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.427148E+10 | 17553.50 | 09-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.216170E+10 | 18008.19 | 15-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.837019E+09 | 18092.55 | 28-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 66198889.26 | 18054.97 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.521314E+09 | 18022.70 | 26-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.304860E+10 | 18029.39 | 04-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.423059E+10 | 17804.28 | 21-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.151369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.427148E+10 | 18092.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.672079E+10 | 27396.15 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.292743E+10 | 28149.67 | 08-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.115047E+10 | 28152.48 | 25-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110033E+09 | 28138.18 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 318608.20 | 1722.20 | 25-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.842628E+09 | 28166.78 | 25-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.422285E+10 | 28146.01 | 02-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.665801E+10 | 27748.75 | 21-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.226325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.672079E+10 | 28166.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.290804E+10 | 15979.07 | 02-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.886352E+09 | 15965.44 | 27-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.132506E+09 | 15930.31 | 03-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 85538153.01 | 15930.80 | 31-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.541491E+09 | 15933.24 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.625014E+09 | 15931.68 | 22-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.517894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.290804E+10 | 15979.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.235286E+12 | 1018333.95 | 12-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139677E+12 | 953411.45 | 27-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.413440E+11 | 815203.59 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.406147E+10 | 631139.68 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.259577E+09 | 125077.03 | 27-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3769.46 | 3.77 | 01-JUN-18:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.307850E+09 | 173521.29 | 31-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.209313E+10 | 236408.03 | 29-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.503025E+10 | 566785.50 | 31-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.206552E+12 | 814270.51 | 29-NOV-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.342501E+12 | 914802.17 | 15-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.977112E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.342501E+12 | 1018333.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.442372E+11 | 563344.40 | 17-JAN-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139994E+11 | 563246.59 | 21-FEB-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121496E+10 | 562281.73 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.102704E+10 | 559340.86 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.156271E+11 | 563248.12 | 13-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.291549E+11 | 563295.93 | 18-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105261E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.442372E+11 | 563344.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.122182E+12 | 147574.87 | 03-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.812489E+11 | 147610.29 | 07-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.501110E+11 | 146736.05 | 10-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.888001E+10 | 159048.52 | 25-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6478089.41 | 5335.29 | 31-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.196091E+10 | 145779.59 | 25-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.318794E+11 | 146821.63 | 30-OCT-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.942325E+11 | 147562.68 | 06-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120387E+12 | 147590.77 | 27-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.510888E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.122182E+12 | 159048.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.968031E+11 | 208764.74 | 14-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.594007E+11 | 208941.99 | 21-FEB-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.288040E+11 | 208704.96 | 06-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.592904E+10 | 208270.81 | 03-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 75862371.57 | 20956.19 | 30-AUG-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.265671E+10 | 183786.85 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.272042E+11 | 208591.57 | 26-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.775719E+11 | 208856.68 | 20-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.969216E+11 | 208805.31 | 14-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.395367E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.969216E+11 | 208941.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.125212E+12 | 313526.61 | 14-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.625312E+11 | 313414.47 | 27-FEB-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.310235E+11 | 312840.30 | 04-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.622842E+10 | 312785.13 | 03-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 68921985.01 | 23710.05 | 27-MAY-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 59350927.01 | 17651.68 | 30-AUG-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.266461E+10 | 182323.17 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.290135E+11 | 313046.54 | 30-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.898630E+11 | 313461.40 | 27-NOV-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134575E+12 | 313658.03 | 04-DEC-05:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.481239E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.134575E+12 | 313658.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.863592E+11 | 205314.22 | 14-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.543464E+11 | 205243.92 | 27-FEB-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.327429E+11 | 204974.38 | 31-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.476350E+10 | 204506.83 | 01-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 54431118.23 | 15201.54 | 27-MAY-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 28837688.47 | 13802.10 | 30-AUG-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.269798E+10 | 157520.25 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.266187E+11 | 205025.89 | 23-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.645947E+11 | 205273.34 | 27-NOV-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.813004E+11 | 205289.81 | 05-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.353507E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.863592E+11 | 205314.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.328355E+11 | 111423.44 | 12-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.198614E+11 | 98525.93 | 27-FEB-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.637409E+10 | 88322.86 | 01-MAR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.611609E+09 | 69553.81 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 59118879.60 | 17233.49 | 27-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 199.59 | 0.32 | 21-JUN-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30775500.53 | 22681.63 | 31-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.219350E+09 | 29994.31 | 29-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.171322E+10 | 62419.36 | 27-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.292158E+11 | 88187.55 | 29-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.441273E+11 | 98959.23 | 15-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135048E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.441273E+11 | 111423.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.238835E+11 | 82673.91 | 24-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154087E+11 | 82685.13 | 11-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.907576E+10 | 82667.90 | 20-MAR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.199111E+10 | 82666.66 | 17-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.430131E+09 | 81022.24 | 25-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.719007E+10 | 82941.97 | 10-OCT-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.193600E+11 | 82684.65 | 13-NOV-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.235912E+11 | 82673.48 | 20-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100931E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.238835E+11 | 82941.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.190809E+11 | 15553.50 | 23-JAN-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144654E+11 | 15554.18 | 11-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.106741E+11 | 15550.86 | 21-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.305383E+10 | 15508.54 | 17-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 42859869.63 | 15366.20 | 27-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 49811859.04 | 15365.64 | 30-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137758E+10 | 15599.29 | 25-SEP-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.796094E+10 | 15601.18 | 10-OCT-03:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167439E+11 | 15552.16 | 02-NOV-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.197658E+11 | 15552.22 | 20-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.932151E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.197658E+11 | 15601.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.138440E+11 | 23859.51 | 23-JAN-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.968059E+10 | 23882.50 | 24-FEB-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.562901E+10 | 23888.78 | 27-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164139E+10 | 23781.29 | 03-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 30163746.37 | 10848.85 | 27-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 29978105.68 | 17905.98 | 30-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.967305E+09 | 23767.54 | 26-SEP-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.546684E+10 | 23981.23 | 27-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.122054E+11 | 23875.18 | 03-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143856E+11 | 23863.90 | 11-DEC-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.638803E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.143856E+11 | 23981.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.190547E+11 | 36800.39 | 23-JAN-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113142E+11 | 36836.16 | 24-FEB-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.685187E+10 | 36836.62 | 31-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.209932E+10 | 36781.16 | 01-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136537E+09 | 20888.88 | 27-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 77099569.10 | 23384.69 | 30-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133917E+10 | 36721.49 | 28-SEP-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.669941E+10 | 36813.71 | 10-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.155655E+11 | 36808.05 | 13-NOV-05:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.209171E+11 | 36807.47 | 11-DEC-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.840550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.209171E+11 | 36836.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.128872E+11 | 24340.22 | 23-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.880124E+10 | 24368.62 | 24-FEB-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.601103E+10 | 24368.92 | 31-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144469E+10 | 24332.27 | 01-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 78412916.03 | 12497.86 | 27-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 44056795.94 | 11668.80 | 30-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.108030E+10 | 24291.97 | 28-SEP-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.513832E+10 | 24352.95 | 10-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102256E+11 | 24340.62 | 13-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.121548E+11 | 24338.41 | 26-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.578657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.128872E+11 | 24368.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.158350E+11 | 67678.83 | 12-JAN-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.101045E+11 | 58870.49 | 27-FEB-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.360249E+10 | 53694.07 | 01-MAR-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.107023E+09 | 12304.70 | 01-APR-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.764574E+09 | 13165.52 | 30-OCT-20:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132566E+11 | 53604.50 | 29-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.194063E+11 | 56370.75 | 15-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.630765E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.194063E+11 | 67678.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 9586464.64 | 9586464.64 | 2079.86 | 25-JAN-13:10 | 2079.86 | 0.00 |
February | 0.00 | 0.00 | 13494518.46 | 13494518.46 | 3101.22 | 15-FEB-13:10 | 3101.22 | 0.00 |
March | 0.00 | 0.00 | 30259552.66 | 30259552.66 | 10068.27 | 10-MAR-08:10 | 10068.27 | 0.00 |
April | 0.00 | 0.00 | 0.578487E+09 | 0.578487E+09 | 28324.15 | 20-APR-14:00 | 28324.15 | 0.00 |
May | 0.00 | 0.00 | 0.168832E+11 | 0.168832E+11 | 109158.11 | 31-MAY-16:00 | 109158.11 | 0.00 |
June | 0.00 | 0.00 | 0.683985E+11 | 0.680896E+11 | 172336.86 | 30-JUN-12:30 | 153054.96 | 0.19 |
July | 0.00 | 0.00 | 0.893731E+11 | 0.886538E+11 | 186033.75 | 03-JUL-15:00 | 79902.72 | 0.48 |
August | 0.00 | 0.00 | 0.541274E+11 | 0.540682E+11 | 158372.23 | 11-AUG-15:40 | 158372.23 | 0.34 |
September | 0.00 | 0.00 | 0.138768E+10 | 0.138768E+10 | 42931.95 | 07-SEP-16:00 | 42931.95 | 0.00 |
October | 0.00 | 0.00 | 5304234.63 | 5304234.63 | 2932.38 | 27-OCT-12:10 | 2932.38 | 0.00 |
November | 0.00 | 0.00 | 14741916.28 | 14741916.28 | 4453.13 | 03-NOV-07:10 | 4453.13 | 0.00 |
December | 0.00 | 0.00 | 10090178.88 | 10090178.88 | 5494.26 | 27-DEC-08:20 | 5494.26 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.230832E+12 | 0.229744E+12 | 0.09 | |||
Minimum of Months | 0.00 | 0.00 | 5304234.63 | 5304234.63 | 2079.86 | 2079.86 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.893731E+11 | 0.886538E+11 | 186033.75 | 158372.23 | 0.48 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 14918794.93 | 14918794.93 | 1997.79 | 27-JAN-08:50 | 1997.79 | 0.00 |
February | 0.00 | 0.00 | 25649979.51 | 25649979.51 | 4517.53 | 15-FEB-13:10 | 4517.53 | 0.00 |
March | 0.00 | 0.00 | 50228917.25 | 50228917.25 | 9582.80 | 30-MAR-12:10 | 9582.80 | 0.00 |
April | 0.00 | 0.00 | 0.167150E+10 | 0.167150E+10 | 139608.60 | 20-APR-14:00 | 139608.60 | 0.00 |
May | 0.00 | 0.00 | 0.101219E+12 | 0.101219E+12 | 829838.00 | 31-MAY-16:00 | 829838.00 | 0.00 |
June | 0.00 | 0.00 | 0.428630E+12 | 0.427585E+12 | 1251518.97 | 30-JUN-12:30 | 1171970.28 | 0.16 |
July | 0.00 | 0.00 | 0.548012E+12 | 0.546650E+12 | 1387216.86 | 23-JUL-14:51 | 1387216.86 | 0.40 |
August | 0.00 | 0.00 | 0.295956E+12 | 0.295956E+12 | 1202756.10 | 11-AUG-15:40 | 1202756.10 | 0.27 |
September | 0.00 | 0.00 | 0.605070E+10 | 0.605070E+10 | 244463.46 | 07-SEP-16:00 | 244463.46 | 0.00 |
October | 0.00 | 0.00 | 15924748.62 | 15924748.62 | 4885.28 | 26-OCT-12:00 | 4885.28 | 0.00 |
November | 0.00 | 0.00 | 27641483.67 | 27641483.67 | 3445.18 | 08-NOV-12:20 | 3445.18 | 0.00 |
December | 0.00 | 0.00 | 9780393.10 | 9780393.10 | 1096.57 | 21-DEC-09:00 | 1096.57 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.138168E+13 | 0.137928E+13 | 0.07 | |||
Minimum of Months | 0.00 | 0.00 | 9780393.10 | 9780393.10 | 1096.57 | 1096.57 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.548012E+12 | 0.546650E+12 | 1387216.86 | 1387216.86 | 0.40 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 512535.41 | 512535.41 | 448.31 | 09-JAN-05:45 | 448.31 | 0.00 |
February | 0.00 | 0.00 | 1558701.44 | 1558701.44 | 934.94 | 25-FEB-05:32 | 934.94 | 0.00 |
March | 0.00 | 0.00 | 6377036.16 | 6377036.16 | 705.18 | 03-MAR-12:00 | 705.18 | 0.00 |
April | 0.00 | 0.00 | 74219555.14 | 74219555.14 | 9979.75 | 20-APR-14:00 | 9979.75 | 0.00 |
May | 0.00 | 0.00 | 0.977131E+10 | 0.977131E+10 | 89081.03 | 31-MAY-16:00 | 89081.03 | 0.00 |
June | 0.00 | 0.00 | 0.439538E+11 | 0.438385E+11 | 139421.47 | 30-JUN-12:30 | 129961.82 | 0.15 |
July | 0.00 | 0.00 | 0.562469E+11 | 0.561239E+11 | 136968.12 | 21-JUL-14:40 | 136968.12 | 0.40 |
August | 0.00 | 0.00 | 0.295228E+11 | 0.295228E+11 | 129943.92 | 11-AUG-15:40 | 129943.92 | 0.26 |
September | 0.00 | 0.00 | 0.490260E+09 | 0.490260E+09 | 22688.84 | 10-SEP-12:02 | 22688.84 | 0.00 |
October | 0.00 | 0.00 | 399195.64 | 399195.64 | 267.95 | 03-OCT-09:20 | 267.95 | 0.00 |
November | 0.00 | 0.00 | 127710.23 | 127710.23 | 58.62 | 04-NOV-11:20 | 58.62 | 0.00 |
December | 0.00 | 0.00 | 240975.64 | 240975.64 | 163.36 | 23-DEC-07:20 | 163.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.140068E+12 | 0.139830E+12 | 0.07 | |||
Minimum of Months | 0.00 | 0.00 | 127710.23 | 127710.23 | 58.62 | 58.62 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.562469E+11 | 0.561239E+11 | 139421.47 | 136968.12 | 0.40 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 70858661.12 | 70858661.12 | 6696.26 | 19-JAN-17:30 | 6696.26 | 0.00 |
February | 0.00 | 0.00 | 0.181775E+09 | 0.181775E+09 | 29281.81 | 17-FEB-08:30 | 29281.81 | 0.00 |
March | 0.00 | 0.00 | 0.256117E+09 | 0.256117E+09 | 13402.31 | 28-MAR-07:20 | 13402.31 | 0.00 |
April | 0.00 | 0.00 | 40813055.79 | 40813055.79 | 23484.21 | 04-APR-06:15 | 23484.21 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 92631131.71 | 92518681.68 | 21273.00 | 25-OCT-06:15 | 21273.00 | 0.00 |
November | 0.00 | 0.00 | 0.259505E+09 | 0.259505E+09 | 29920.80 | 07-NOV-10:00 | 29920.80 | 0.00 |
December | 0.00 | 0.00 | 0.140921E+09 | 0.140921E+09 | 27757.46 | 27-DEC-13:10 | 27757.46 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.104262E+10 | 0.104251E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.259505E+09 | 0.259505E+09 | 29920.80 | 29920.80 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.629782E+10 | 0.589690E+10 | 2792.30 | 19-JAN-05:01 | 2635.12 | 0.00 |
February | 0.00 | 0.00 | 0.107595E+11 | 0.976845E+10 | 5434.58 | 08-FEB-22:00 | 5046.17 | 0.00 |
March | 0.00 | 0.00 | 0.145409E+11 | 0.140976E+11 | 6072.83 | 21-MAR-17:30 | 5271.75 | 0.00 |
April | 0.00 | 0.00 | 0.159161E+11 | 0.158432E+11 | 69320.50 | 22-APR-14:00 | 69320.50 | 0.00 |
May | 0.00 | 0.00 | 0.951385E+10 | 0.917674E+10 | 4933.34 | 28-MAY-19:22 | 4862.26 | 0.00 |
June | 0.00 | 0.00 | 0.506191E+11 | 0.472731E+11 | 254909.00 | 30-JUN-12:00 | 184173.34 | 0.00 |
July | 0.00 | 0.00 | 0.208474E+12 | 0.173798E+12 | 389239.87 | 29-JUL-18:22 | 315158.05 | 0.00 |
August | 0.00 | 0.00 | 0.256277E+12 | 0.198786E+12 | 377248.02 | 23-AUG-16:00 | 351874.93 | 0.00 |
September | 0.00 | 0.00 | 0.516386E+10 | 0.480293E+10 | 4926.11 | 07-SEP-15:50 | 4865.74 | 0.00 |
October | 0.00 | 0.00 | 0.123142E+11 | 0.112863E+11 | 5863.04 | 31-OCT-23:10 | 5287.39 | 0.00 |
November | 0.00 | 0.00 | 0.145205E+11 | 0.136371E+11 | 6083.34 | 27-NOV-05:43 | 5272.66 | 0.00 |
December | 0.00 | 0.00 | 0.147717E+11 | 0.146701E+11 | 6287.23 | 01-DEC-00:10 | 5488.68 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.619169E+12 | 0.519036E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.516386E+10 | 0.480293E+10 | 2792.30 | 2635.12 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.256277E+12 | 0.198786E+12 | 389239.87 | 351874.93 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.179336E+10 | 0.179336E+10 | 1306.70 | 22-JAN-15:20 | 1306.70 | 0.00 |
February | 0.00 | 0.00 | 0.710200E+10 | 0.710200E+10 | 3690.46 | 09-FEB-16:00 | 3690.46 | 0.00 |
March | 0.00 | 0.00 | 0.141141E+11 | 0.141141E+11 | 7412.03 | 31-MAR-24:00 | 7412.03 | 0.00 |
April | 0.00 | 0.00 | 0.200160E+11 | 0.200160E+11 | 9375.21 | 22-APR-19:00 | 9375.21 | 0.00 |
May | 0.00 | 0.00 | 0.605933E+10 | 0.605918E+10 | 4138.94 | 31-MAY-23:20 | 4138.94 | 0.00 |
June | 0.00 | 0.00 | 0.111055E+11 | 0.110273E+11 | 6084.47 | 30-JUN-23:42 | 6075.38 | 0.00 |
July | 0.00 | 0.00 | 0.166860E+11 | 0.165240E+11 | 8017.31 | 31-JUL-23:45 | 7989.95 | 0.00 |
August | 0.00 | 0.00 | 0.214937E+11 | 0.213607E+11 | 9396.50 | 27-AUG-18:45 | 9396.50 | 0.00 |
September | 0.00 | 0.00 | 0.534581E+10 | 0.532904E+10 | 3850.03 | 30-SEP-24:00 | 3850.03 | 0.00 |
October | 0.00 | 0.00 | 0.943756E+10 | 0.943733E+10 | 5136.06 | 31-OCT-24:00 | 5136.06 | 0.00 |
November | 0.00 | 0.00 | 0.126365E+11 | 0.126365E+11 | 5631.81 | 19-NOV-15:30 | 5631.81 | 0.00 |
December | 0.00 | 0.00 | 0.179509E+11 | 0.179509E+11 | 7436.95 | 24-DEC-17:55 | 7436.95 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.143741E+12 | 0.143350E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.179336E+10 | 0.179336E+10 | 1306.70 | 1306.70 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.214937E+11 | 0.213607E+11 | 9396.50 | 9396.50 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.928658E+09 | 0.928658E+09 | 7386.05 | 27-JAN-22:03 | 7386.05 | 0.00 |
February | 0.00 | 0.00 | 0.437331E+11 | 0.437331E+11 | 31338.55 | 16-FEB-16:15 | 31338.55 | 0.00 |
March | 0.00 | 0.00 | 0.113490E+12 | 0.113490E+12 | 65523.05 | 31-MAR-23:20 | 65523.05 | 0.00 |
April | 0.00 | 0.00 | 0.179448E+12 | 0.179448E+12 | 88363.53 | 20-APR-19:00 | 88363.53 | 0.00 |
May | 0.00 | 0.00 | 0.502783E+11 | 0.502767E+11 | 38293.49 | 31-MAY-24:00 | 38293.49 | 0.00 |
June | 0.00 | 0.00 | 0.102039E+12 | 0.101266E+12 | 57352.04 | 30-JUN-23:20 | 57114.09 | 0.00 |
July | 0.00 | 0.00 | 0.154957E+12 | 0.153354E+12 | 76605.14 | 31-JUL-23:03 | 76232.73 | 0.00 |
August | 0.00 | 0.00 | 0.199610E+12 | 0.198288E+12 | 85636.62 | 27-AUG-18:50 | 85636.62 | 0.00 |
September | 0.00 | 0.00 | 0.377551E+11 | 0.375961E+11 | 28991.18 | 02-SEP-18:10 | 28991.18 | 0.00 |
October | 0.00 | 0.00 | 0.675603E+11 | 0.675577E+11 | 40222.15 | 31-OCT-23:20 | 40222.15 | 0.00 |
November | 0.00 | 0.00 | 0.916625E+11 | 0.916625E+11 | 47418.25 | 08-NOV-15:50 | 47418.25 | 0.00 |
December | 0.00 | 0.00 | 0.138304E+12 | 0.138304E+12 | 60177.58 | 29-DEC-22:06 | 60177.58 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.117977E+13 | 0.117590E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.928658E+09 | 0.928658E+09 | 7386.05 | 7386.05 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.199610E+12 | 0.198288E+12 | 88363.53 | 88363.53 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 448256.29 | 448256.29 | 94.05 | 19-JAN-17:00 | 94.05 | 0.00 |
February | 0.00 | 0.00 | 0.257430E+10 | 0.257430E+10 | 2770.26 | 09-FEB-16:00 | 2770.26 | 0.00 |
March | 0.00 | 0.00 | 0.925383E+10 | 0.925383E+10 | 5703.17 | 31-MAR-23:10 | 5703.17 | 0.00 |
April | 0.00 | 0.00 | 0.165600E+11 | 0.165600E+11 | 8829.35 | 20-APR-19:00 | 8829.35 | 0.00 |
May | 0.00 | 0.00 | 0.447580E+10 | 0.447565E+10 | 3774.27 | 31-MAY-23:40 | 3774.27 | 0.00 |
June | 0.00 | 0.00 | 0.100391E+11 | 0.996187E+10 | 5704.56 | 30-JUN-23:20 | 5680.48 | 0.00 |
July | 0.00 | 0.00 | 0.153538E+11 | 0.151936E+11 | 7631.56 | 31-JUL-23:03 | 7594.17 | 0.00 |
August | 0.00 | 0.00 | 0.196186E+11 | 0.194866E+11 | 8596.72 | 27-AUG-18:50 | 8596.72 | 0.00 |
September | 0.00 | 0.00 | 0.252942E+10 | 0.251438E+10 | 2751.03 | 02-SEP-18:10 | 2751.03 | 0.00 |
October | 0.00 | 0.00 | 0.452236E+10 | 0.452213E+10 | 3669.67 | 03-OCT-16:00 | 3669.67 | 0.00 |
November | 0.00 | 0.00 | 0.703620E+10 | 0.703620E+10 | 4306.80 | 08-NOV-15:50 | 4306.80 | 0.00 |
December | 0.00 | 0.00 | 0.118247E+11 | 0.118247E+11 | 5657.82 | 19-DEC-22:05 | 5657.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.103789E+12 | 0.103404E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 448256.29 | 448256.29 | 94.05 | 94.05 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.196186E+11 | 0.194866E+11 | 8829.35 | 8829.35 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 328996.59 | 2252308.03 | 02-JAN-04:01 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 214325.73 | 2223375.03 | 07-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 89404.82 | 1955073.57 | 01-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15885.58 | 1662979.99 | 04-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 263.27 | 173578.45 | 27-MAY-06:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 3.95 | 01-JUN-18:30 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 270.07 | 231075.29 | 31-AUG-06:10 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 6716.85 | 1390166.06 | 30-SEP-05:02 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 58708.19 | 1775038.87 | 30-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 266290.63 | 2118482.23 | 20-NOV-05:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 372850.85 | 2154705.88 | 12-DEC-05:01 |
Annual Sum or Average | 0.00 | 112419.78 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 372850.85 | 2252308.03 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 180.59 | 5596.78 | 23-JAN-14:10 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 235.38 | 18913.22 | 17-FEB-08:30 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 283.68 | 23572.24 | 30-MAR-12:10 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 1010.38 | 173624.41 | 20-APR-14:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 48501.12 | 1248764.61 | 31-MAY-15:30 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 214816.09 | 1588908.91 | 20-JUN-13:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 269130.26 | 1621580.28 | 03-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 145554.65 | 1633071.21 | 11-AUG-15:20 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 3245.10 | 302669.79 | 07-SEP-16:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 89.20 | 12428.03 | 26-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 285.56 | 24296.60 | 07-NOV-10:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 197.79 | 23641.24 | 27-DEC-15:20 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 57450.30 | 0.00 | ||||
Minimum of Months | 89.20 | 5596.78 | 0.00 | 0.00 | ||
Maximum of Months | 269130.26 | 1633071.21 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 9.22 | 2636.84 | 23-JAN-14:10 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 62.36 | 19674.67 | 17-FEB-08:30 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 120.64 | 25941.42 | 30-MAR-12:10 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 922.98 | 174978.55 | 20-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 47695.64 | 1115093.01 | 31-MAY-15:20 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 212607.70 | 1590281.57 | 20-JUN-14:40 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 268419.91 | 1673814.63 | 23-JUL-14:51 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 145297.59 | 1691496.69 | 24-AUG-13:15 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 3045.51 | 302583.76 | 07-SEP-16:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 37.59 | 14291.94 | 30-OCT-06:15 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 113.84 | 23920.19 | 07-NOV-10:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 60.75 | 23380.90 | 27-DEC-13:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 57022.82 | 0.00 | ||||
Minimum of Months | 9.22 | 2636.84 | 0.00 | 0.00 | ||
Maximum of Months | 268419.91 | 1691496.69 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 8994.16 | 52813.03 | 30-JAN-18:05 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 38531.72 | 151748.50 | 15-FEB-22:03 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 75993.15 | 252509.77 | 15-MAR-21:02 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 116209.24 | 226590.36 | 07-APR-15:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 42527.68 | 285096.22 | 31-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 154402.32 | 1106275.45 | 30-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 320439.75 | 1415656.78 | 29-JUL-17:00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 316989.19 | 1276877.10 | 11-AUG-17:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 29382.83 | 122885.29 | 29-SEP-07:43 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 48939.71 | 152013.14 | 12-OCT-08:55 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 66292.09 | 127087.43 | 08-NOV-15:40 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 90861.43 | 151848.57 | 26-DEC-13:50 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 109902.96 | 0.00 | ||||
Minimum of Months | 8994.16 | 52813.03 | 0.00 | 0.00 | ||
Maximum of Months | 320439.75 | 1415656.78 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 17739.75 | 62780.37 | 26-JAN-12:35 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17847.57 | 62780.46 | 02-FEB-12:45 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 18970.66 | 62780.06 | 28-MAR-11:15 |
April | 0.00 | 0.00 | 01-APR-00:10 | 17768.27 | 62780.02 | 03-APR-11:35 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 18229.21 | 62779.71 | 04-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18000.47 | 61218.34 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15940.88 | 58671.81 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17042.26 | 56912.72 | 01-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 15913.22 | 56528.85 | 29-SEP-11:25 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16196.61 | 58205.24 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17004.75 | 60510.60 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 17043.40 | 62780.46 | 29-DEC-12:25 |
Annual Sum or Average | 0.00 | 17305.15 | ||||
Minimum of Months | 0.00 | 0.00 | 15913.22 | 56528.85 | ||
Maximum of Months | 0.00 | 0.00 | 18970.66 | 62780.46 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 16.77 | 8610.34 | 13-JAN-18:50 | 2580.66 | 135887.67 | 09-JAN-18:00 |
February | 17.58 | 8796.40 | 03-FEB-17:10 | 2607.62 | 138309.85 | 06-FEB-07:15 |
March | 20.58 | 14839.17 | 30-MAR-10:35 | 2485.48 | 145784.59 | 12-MAR-14:04 |
April | 413.51 | 200399.96 | 20-APR-14:10 | 768.14 | 123209.46 | 03-APR-07:00 |
May | 48927.69 | 1469479.79 | 31-MAY-15:30 | 1648.20 | 97712.60 | 18-MAY-11:50 |
June | 247825.38 | 2315099.58 | 30-JUN-12:20 | 1089.06 | 82505.93 | 01-JUN-10:00 |
July | 327846.21 | 2420567.66 | 03-JUL-15:00 | 896.32 | 76242.87 | 13-JUL-08:70 |
August | 169804.45 | 2229656.14 | 11-AUG-14:40 | 1456.41 | 99606.27 | 31-AUG-13:20 |
September | 1895.25 | 342505.20 | 07-SEP-16:00 | 692.50 | 86018.63 | 15-SEP-16:20 |
October | 5.76 | 8077.71 | 28-OCT-14:00 | 823.35 | 144345.35 | 20-OCT-20:27 |
November | 4.67 | 8402.94 | 13-NOV-07:50 | 3147.83 | 135938.27 | 06-NOV-07:15 |
December | 16.35 | 8594.74 | 19-DEC-21:50 | 2170.10 | 129315.97 | 01-DEC-21:10 |
Annual Sum or Average | 66987.48 | 1692.64 | ||||
Minimum of Months | 4.67 | 8077.71 | 692.50 | 76242.87 | ||
Maximum of Months | 327846.21 | 2420567.66 | 3147.83 | 145784.59 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.337914E+10 | 0.30 | 4542.59 | 02-JAN-05:01 | 0.71 |
February | 0.354152E+10 | 0.32 | 15317.60 | 14-FEB-06:02 | 1.45 |
March | 0.628222E+10 | 0.40 | 23476.04 | 15-MAR-15:40 | 1.90 |
April | 0.136118E+11 | 0.63 | 23476.04 | 19-APR-15:20 | 1.89 |
May | 0.197775E+11 | 0.78 | 23476.04 | 01-MAY-12:10 | 1.89 |
June | 0.234729E+11 | 0.91 | 23476.04 | 01-JUN-12:10 | 1.89 |
July | 0.229665E+11 | 0.88 | 23476.04 | 03-JUL-10:10 | 1.88 |
August | 0.236143E+11 | 0.91 | 23476.04 | 01-AUG-10:00 | 1.88 |
September | 0.134347E+11 | 0.62 | 23476.04 | 07-SEP-14:40 | 1.89 |
October | 0.762319E+10 | 0.43 | 21734.17 | 03-OCT-14:20 | 1.80 |
November | 0.382089E+10 | 0.32 | 15049.25 | 03-NOV-05:01 | 1.43 |
December | 0.380914E+10 | 0.31 | 15317.60 | 21-DEC-06:01 | 1.45 |
Annual Sum or Average | 0.145334E+12 | 0.57 | |||
Minimum of Months | 0.337914E+10 | 0.30 | 4542.59 | 0.71 | |
Maximum of Months | 0.236143E+11 | 0.91 | 23476.04 | 1.90 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.435616E+11 | 0.40 | 70608.48 | 02-JAN-04:01 | 0.95 |
February | 0.371614E+11 | 0.38 | 70608.48 | 01-FEB-06:03 | 0.95 |
March | 0.427591E+11 | 0.36 | 218739.24 | 16-MAR-10:45 | 1.90 |
April | 0.599952E+11 | 0.41 | 161311.81 | 21-APR-15:50 | 1.57 |
May | 0.910616E+11 | 0.50 | 171066.55 | 31-MAY-14:40 | 1.62 |
June | 0.113527E+12 | 0.58 | 218739.24 | 08-JUN-05:02 | 1.89 |
July | 0.105542E+12 | 0.53 | 218739.24 | 11-JUL-05:01 | 1.88 |
August | 0.933713E+11 | 0.50 | 199592.28 | 10-AUG-15:50 | 1.78 |
September | 0.494603E+11 | 0.36 | 113539.23 | 08-SEP-15:30 | 1.25 |
October | 0.364993E+11 | 0.32 | 97049.45 | 04-OCT-05:03 | 1.14 |
November | 0.372421E+11 | 0.36 | 70608.48 | 06-NOV-06:01 | 0.95 |
December | 0.411417E+11 | 0.38 | 70608.48 | 04-DEC-05:01 | 0.95 |
Annual Sum or Average | 0.751324E+12 | 0.42 | |||
Minimum of Months | 0.364993E+11 | 0.32 | 70608.48 | 0.95 | |
Maximum of Months | 0.113527E+12 | 0.58 | 218739.24 | 1.90 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.511156E+10 | 0.45 | 6445.36 | 02-JAN-04:01 | 0.86 |
February | 0.442685E+10 | 0.43 | 6445.36 | 01-FEB-05:11 | 0.86 |
March | 0.467681E+10 | 0.40 | 6445.36 | 01-MAR-05:01 | 0.86 |
April | 0.489486E+10 | 0.37 | 13326.92 | 21-APR-15:40 | 1.32 |
May | 0.736560E+10 | 0.43 | 18044.87 | 31-MAY-14:50 | 1.59 |
June | 0.103625E+11 | 0.53 | 19456.50 | 20-JUN-15:30 | 1.66 |
July | 0.962885E+10 | 0.48 | 20498.29 | 21-JUL-14:40 | 1.72 |
August | 0.783852E+10 | 0.44 | 20197.81 | 10-AUG-15:50 | 1.71 |
September | 0.381245E+10 | 0.32 | 8480.76 | 08-SEP-15:30 | 1.00 |
October | 0.395775E+10 | 0.35 | 6445.36 | 10-OCT-03:01 | 0.86 |
November | 0.481033E+10 | 0.44 | 6445.36 | 01-NOV-04:01 | 0.86 |
December | 0.522840E+10 | 0.46 | 6445.36 | 01-DEC-05:01 | 0.86 |
Annual Sum or Average | 0.721144E+11 | 0.42 | |||
Minimum of Months | 0.381245E+10 | 0.32 | 6445.36 | 0.86 | |
Maximum of Months | 0.103625E+11 | 0.53 | 20498.29 | 1.72 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.689927E+10 | 0.52 | 13133.27 | 05-JAN-07:05 | 1.92 |
February | 0.890608E+10 | 0.63 | 13133.27 | 01-FEB-07:12 | 1.92 |
March | 0.130076E+11 | 0.77 | 13133.27 | 01-MAR-07:02 | 1.93 |
April | 0.554768E+10 | 0.33 | 13133.27 | 01-APR-06:12 | 1.93 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 |
October | 0.714133E+10 | 0.42 | 13133.27 | 13-OCT-07:11 | 1.88 |
November | 0.941658E+10 | 0.62 | 13133.27 | 01-NOV-06:12 | 1.92 |
December | 0.699343E+10 | 0.50 | 13133.27 | 02-DEC-07:12 | 1.92 |
Annual Sum or Average | 0.579119E+11 | 0.31 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.130076E+11 | 0.77 | 13133.27 | 1.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.110532E+12 | 1.37 | 41267.85 | 01-JAN-00:02 | 1.37 |
February | 0.998352E+11 | 1.37 | 41267.85 | 01-FEB-00:03 | 1.37 |
March | 0.110532E+12 | 1.37 | 41267.85 | 01-MAR-00:05 | 1.37 |
April | 0.106966E+12 | 1.38 | 41267.85 | 01-APR-00:10 | 1.38 |
May | 0.110532E+12 | 1.37 | 41267.85 | 01-MAY-00:03 | 1.37 |
June | 0.106966E+12 | 1.37 | 41267.85 | 01-JUN-00:10 | 1.37 |
July | 0.110532E+12 | 1.36 | 41267.85 | 01-JUL-00:03 | 1.36 |
August | 0.110532E+12 | 1.37 | 41267.85 | 01-AUG-00:03 | 1.37 |
September | 0.106966E+12 | 1.37 | 41267.85 | 01-SEP-00:03 | 1.37 |
October | 0.110532E+12 | 1.37 | 41267.85 | 01-OCT-00:10 | 1.37 |
November | 0.106966E+12 | 1.37 | 41267.85 | 01-NOV-00:10 | 1.37 |
December | 0.110532E+12 | 1.37 | 41267.85 | 01-DEC-00:10 | 1.37 |
Annual Sum or Average | 0.130142E+13 | 1.37 | |||
Minimum of Months | 0.998352E+11 | 1.36 | 41267.85 | 1.36 | |
Maximum of Months | 0.110532E+12 | 1.38 | 41267.85 | 1.38 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.157372E+10 | 0.94 | 587.56 | 01-JAN-00:02 | 0.93 |
February | 0.142142E+10 | 0.94 | 587.56 | 01-FEB-00:03 | 0.94 |
March | 0.157372E+10 | 0.94 | 587.56 | 01-MAR-00:05 | 0.94 |
April | 0.152295E+10 | 0.93 | 587.56 | 01-APR-00:10 | 0.94 |
May | 0.157372E+10 | 0.93 | 587.56 | 01-MAY-00:03 | 0.93 |
June | 0.152295E+10 | 0.93 | 587.56 | 01-JUN-00:10 | 0.93 |
July | 0.157372E+10 | 0.93 | 587.56 | 01-JUL-00:03 | 0.93 |
August | 0.157372E+10 | 0.93 | 587.56 | 01-AUG-00:03 | 0.93 |
September | 0.152295E+10 | 0.93 | 587.56 | 01-SEP-00:03 | 0.93 |
October | 0.157372E+10 | 0.93 | 587.56 | 01-OCT-00:10 | 0.93 |
November | 0.152295E+10 | 0.94 | 587.56 | 01-NOV-00:10 | 0.94 |
December | 0.157372E+10 | 0.94 | 587.56 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.185292E+11 | 0.93 | |||
Minimum of Months | 0.142142E+10 | 0.93 | 587.56 | 0.93 | |
Maximum of Months | 0.157372E+10 | 0.94 | 587.56 | 0.94 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.151933E+11 | 0.94 | 5672.53 | 01-JAN-00:02 | 0.93 |
February | 0.137230E+11 | 0.94 | 5672.53 | 01-FEB-00:03 | 0.94 |
March | 0.151933E+11 | 0.94 | 5672.53 | 01-MAR-00:05 | 0.94 |
April | 0.147032E+11 | 0.93 | 5672.53 | 01-APR-00:10 | 0.94 |
May | 0.151933E+11 | 0.93 | 5672.53 | 01-MAY-00:03 | 0.93 |
June | 0.147032E+11 | 0.93 | 5672.53 | 01-JUN-00:10 | 0.93 |
July | 0.151933E+11 | 0.93 | 5672.53 | 01-JUL-00:03 | 0.93 |
August | 0.151933E+11 | 0.93 | 5672.53 | 01-AUG-00:03 | 0.93 |
September | 0.147032E+11 | 0.93 | 5672.53 | 01-SEP-00:03 | 0.93 |
October | 0.151933E+11 | 0.93 | 5672.53 | 01-OCT-00:10 | 0.93 |
November | 0.147032E+11 | 0.94 | 5672.53 | 01-NOV-00:10 | 0.94 |
December | 0.151933E+11 | 0.94 | 5672.53 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.178889E+12 | 0.93 | |||
Minimum of Months | 0.137230E+11 | 0.93 | 5672.53 | 0.93 | |
Maximum of Months | 0.151933E+11 | 0.94 | 5672.53 | 0.94 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.153207E+10 | 0.94 | 572.01 | 01-JAN-00:02 | 0.93 |
February | 0.138381E+10 | 0.94 | 572.01 | 01-FEB-00:03 | 0.94 |
March | 0.153207E+10 | 0.94 | 572.01 | 01-MAR-00:05 | 0.94 |
April | 0.148265E+10 | 0.93 | 572.01 | 01-APR-00:10 | 0.94 |
May | 0.153207E+10 | 0.93 | 572.01 | 01-MAY-00:03 | 0.93 |
June | 0.148265E+10 | 0.93 | 572.01 | 01-JUN-00:10 | 0.93 |
July | 0.153207E+10 | 0.93 | 572.01 | 01-JUL-00:03 | 0.93 |
August | 0.153207E+10 | 0.93 | 572.01 | 01-AUG-00:03 | 0.93 |
September | 0.148265E+10 | 0.93 | 572.01 | 01-SEP-00:03 | 0.93 |
October | 0.153207E+10 | 0.93 | 572.01 | 01-OCT-00:10 | 0.93 |
November | 0.148265E+10 | 0.94 | 572.01 | 01-NOV-00:10 | 0.94 |
December | 0.153207E+10 | 0.94 | 572.01 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.180389E+11 | 0.93 | |||
Minimum of Months | 0.138381E+10 | 0.93 | 572.01 | 0.93 | |
Maximum of Months | 0.153207E+10 | 0.94 | 572.01 | 0.94 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.170261E+09 | 0.153235E+09 | 1103.88 | 12-JAN-07:10 | 993.50 | 993.50 | 45.83 | 12.98 |
February | 84870409.73 | 76383368.75 | 1313.51 | 27-FEB-07:10 | 1182.16 | 1182.16 | 45.13 | 14.02 |
March | 27100747.87 | 24390673.08 | 994.79 | 06-MAR-06:01 | 895.31 | 895.31 | 45.06 | 12.40 |
April | 2367513.12 | 2130761.81 | 392.90 | 03-APR-05:01 | 353.61 | 353.61 | 42.90 | 8.09 |
May | 20136.32 | 18122.68 | 6.40 | 27-MAY-06:10 | 5.76 | 5.76 | 23.64 | 0.71 |
June | 0.10 | 0.09 | 0.00 | 01-JUN-18:30 | 0.00 | 0.00 | 22.03 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 22-JUL-03:20 | 0.00 | 0.00 | 22.03 | 0.00 |
August | 23211.59 | 20890.43 | 9.44 | 31-AUG-06:10 | 8.49 | 8.49 | 23.67 | 0.95 |
September | 626805.84 | 564125.26 | 226.35 | 30-SEP-05:02 | 203.72 | 203.72 | 28.51 | 6.22 |
October | 9830271.39 | 8847244.25 | 984.30 | 30-OCT-05:03 | 885.87 | 885.87 | 47.57 | 12.33 |
November | 0.113040E+09 | 0.101736E+09 | 1000.49 | 27-NOV-06:02 | 900.44 | 900.44 | 47.11 | 12.42 |
December | 0.176589E+09 | 0.158930E+09 | 998.24 | 06-DEC-06:01 | 898.42 | 898.42 | 46.49 | 12.41 |
Annual Sum or Average | 0.584729E+09 | 0.526256E+09 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.03 | 0.00 | |
Maximum of Months | 0.176589E+09 | 0.158930E+09 | 1313.51 | 1182.16 | 1182.16 | 47.57 | 14.02 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 7974.31 | 7176.88 | 1.23 | 10-JAN-16:25 | 1.11 | 1.11 | 6.70 | 0.33 |
February | 16731.87 | 15058.69 | 2.09 | 17-FEB-08:30 | 1.88 | 1.88 | 6.70 | 0.53 |
March | 26902.13 | 24211.91 | 2.35 | 30-MAR-12:10 | 2.12 | 2.12 | 6.70 | 0.59 |
April | 509314.99 | 458383.49 | 55.63 | 20-APR-14:00 | 50.07 | 50.07 | 6.70 | 5.52 |
May | 36581230.29 | 32923107.26 | 640.32 | 31-MAY-15:20 | 576.29 | 576.29 | 6.71 | 19.22 |
June | 0.346988E+09 | 0.312289E+09 | 3568.14 | 20-JUN-15:10 | 3211.32 | 3211.32 | 6.72 | 40.57 |
July | 0.680087E+09 | 0.612079E+09 | 4616.97 | 19-JUL-12:50 | 4155.28 | 4155.28 | 11.29 | 45.08 |
August | 0.355377E+09 | 0.319839E+09 | 6052.78 | 24-AUG-13:15 | 5447.50 | 5447.50 | 9.40 | 50.30 |
September | 1488983.80 | 1340085.42 | 85.31 | 07-SEP-16:00 | 76.78 | 76.78 | 6.70 | 7.01 |
October | 8799.53 | 7919.57 | 1.32 | 30-OCT-06:15 | 1.19 | 1.19 | 6.70 | 0.35 |
November | 24238.55 | 21814.69 | 2.15 | 07-NOV-10:00 | 1.93 | 1.93 | 6.70 | 0.54 |
December | 13800.35 | 12420.31 | 2.16 | 27-DEC-13:10 | 1.94 | 1.94 | 6.70 | 0.55 |
Annual Sum or Average | 0.142113E+10 | 0.127902E+10 | ||||||
Minimum of Months | 7974.31 | 7176.88 | 1.23 | 1.11 | 1.11 | 6.70 | 0.33 | |
Maximum of Months | 0.680087E+09 | 0.612079E+09 | 6052.78 | 5447.50 | 5447.50 | 11.29 | 50.30 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.510428E+09 | 0.459385E+09 | 3489.73 | 04-JAN-07:05 | 3140.76 | 3140.76 | 6.72 | 30.87 |
February | 0.465077E+09 | 0.418569E+09 | 3489.73 | 01-FEB-07:15 | 3140.76 | 3140.76 | 6.72 | 30.87 |
March | 0.485316E+09 | 0.436785E+09 | 3489.73 | 01-MAR-10:10 | 3140.76 | 3140.76 | 6.73 | 30.87 |
April | 0.252641E+09 | 0.227377E+09 | 3489.73 | 01-APR-06:15 | 3140.76 | 3140.76 | 6.73 | 30.87 |
May | 0.240496E+10 | 0.216446E+10 | 3489.73 | 01-MAY-12:00 | 3140.76 | 3140.76 | 6.73 | 30.87 |
June | 0.490341E+10 | 0.441307E+10 | 3489.73 | 01-JUN-08:40 | 3140.76 | 3140.76 | 6.88 | 30.87 |
July | 0.540168E+10 | 0.486151E+10 | 3489.73 | 01-JUL-11:00 | 3140.76 | 3140.76 | 6.75 | 30.87 |
August | 0.408308E+10 | 0.367477E+10 | 3489.73 | 01-AUG-00:03 | 3140.76 | 3140.76 | 6.78 | 30.87 |
September | 0.577248E+09 | 0.519523E+09 | 3489.73 | 01-SEP-12:50 | 3140.76 | 3140.76 | 6.74 | 30.87 |
October | 0.153743E+09 | 0.138368E+09 | 3489.73 | 03-OCT-09:20 | 3140.76 | 3140.76 | 6.73 | 30.87 |
November | 0.494395E+09 | 0.444956E+09 | 3489.73 | 01-NOV-06:15 | 3140.76 | 3140.76 | 6.73 | 30.87 |
December | 0.407862E+09 | 0.367076E+09 | 3489.73 | 01-DEC-07:30 | 3140.76 | 3140.76 | 6.72 | 30.87 |
Annual Sum or Average | 0.201398E+11 | 0.181258E+11 | ||||||
Minimum of Months | 0.153743E+09 | 0.138368E+09 | 3489.73 | 3140.76 | 3140.76 | 6.72 | 30.87 | |
Maximum of Months | 0.540168E+10 | 0.486151E+10 | 3489.73 | 3140.76 | 3140.76 | 6.88 | 30.87 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 6.70 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 6.72 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 6.73 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 6.73 | 0.00 |
May | 8375356.73 | 7537821.06 | 3489.73 | 31-MAY-15:20 | 3140.76 | 3140.76 | 15.82 | 15.43 |
June | 0.452269E+09 | 0.407042E+09 | 3489.73 | 12-JUN-14:50 | 3140.76 | 3140.76 | 14.73 | 15.43 |
July | 0.720281E+09 | 0.648253E+09 | 3489.73 | 03-JUL-14:50 | 3140.76 | 3140.76 | 15.82 | 15.43 |
August | 0.293137E+09 | 0.263824E+09 | 3489.73 | 02-AUG-12:50 | 3140.76 | 3140.76 | 14.95 | 15.43 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 6.73 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 6.73 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 6.73 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
Annual Sum or Average | 0.147406E+10 | 0.132666E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 | |
Maximum of Months | 0.720281E+09 | 0.648253E+09 | 3489.73 | 3140.76 | 3140.76 | 15.82 | 15.43 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.105657E+11 | 0.950914E+10 | 3944.79 | 01-JAN-00:02 | 3550.31 | 3550.31 | 18.47 | 16.48 |
February | 0.954322E+10 | 0.858890E+10 | 3944.79 | 01-FEB-00:03 | 3550.31 | 3550.31 | 18.80 | 16.48 |
March | 0.105657E+11 | 0.950914E+10 | 3944.79 | 01-MAR-00:05 | 3550.31 | 3550.31 | 19.41 | 16.48 |
April | 0.102249E+11 | 0.920239E+10 | 3944.79 | 01-APR-00:10 | 3550.31 | 3550.31 | 20.25 | 16.48 |
May | 0.105657E+11 | 0.950914E+10 | 3944.79 | 01-MAY-00:03 | 3550.31 | 3550.31 | 19.00 | 16.48 |
June | 0.102249E+11 | 0.920239E+10 | 3944.79 | 01-JUN-00:10 | 3550.31 | 3550.31 | 19.50 | 16.48 |
July | 0.105657E+11 | 0.950914E+10 | 3944.79 | 01-JUL-00:03 | 3550.31 | 3550.31 | 19.90 | 16.48 |
August | 0.105657E+11 | 0.950914E+10 | 3944.79 | 01-AUG-00:03 | 3550.31 | 3550.31 | 22.96 | 16.48 |
September | 0.102249E+11 | 0.920239E+10 | 3944.79 | 01-SEP-00:03 | 3550.31 | 3550.31 | 18.96 | 16.48 |
October | 0.105657E+11 | 0.950914E+10 | 3944.79 | 01-OCT-00:10 | 3550.31 | 3550.31 | 19.27 | 16.48 |
November | 0.102249E+11 | 0.920239E+10 | 3944.79 | 01-NOV-00:10 | 3550.31 | 3550.31 | 19.60 | 16.48 |
December | 0.105657E+11 | 0.950914E+10 | 3944.79 | 01-DEC-00:10 | 3550.31 | 3550.31 | 19.98 | 16.48 |
Annual Sum or Average | 0.124403E+12 | 0.111962E+12 | ||||||
Minimum of Months | 0.954322E+10 | 0.858890E+10 | 3944.79 | 3550.31 | 3550.31 | 18.47 | 16.48 | |
Maximum of Months | 0.105657E+11 | 0.950914E+10 | 3944.79 | 3550.31 | 3550.31 | 22.96 | 16.48 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:02 | 16.86 | 16.86 | 56.64 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:03 | 16.86 | 16.86 | 56.30 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:01 | 16.86 | 16.86 | 56.58 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:02 | 16.86 | 16.86 | 56.38 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 56.52 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 56.39 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:02 | 16.86 | 16.86 | 56.67 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 56.65 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:02 | 16.86 | 16.86 | 56.77 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 56.38 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:03 | 16.86 | 16.86 | 56.57 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:01 | 16.86 | 16.86 | 56.67 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 56.30 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 56.77 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.196333E+10 | 0.176699E+10 | 13425.36 | 13-JAN-18:50 | 12082.83 | 12082.83 | 21.14 | 54.43 |
February | 0.178888E+10 | 0.161000E+10 | 13425.37 | 03-FEB-17:10 | 12082.83 | 12082.83 | 21.14 | 54.43 |
March | 0.186539E+10 | 0.167885E+10 | 13425.63 | 30-MAR-10:35 | 12083.06 | 12083.06 | 21.17 | 54.43 |
April | 0.970719E+09 | 0.873648E+09 | 13433.50 | 20-APR-14:10 | 12090.15 | 12090.15 | 21.98 | 54.43 |
May | 0.928141E+10 | 0.835327E+10 | 26912.60 | 31-MAY-15:30 | 24221.34 | 24221.34 | 24.33 | 108.85 |
June | 0.202279E+11 | 0.182051E+11 | 26952.38 | 30-JUN-12:20 | 24257.14 | 24257.14 | 26.19 | 108.85 |
July | 0.233311E+11 | 0.209980E+11 | 26957.62 | 03-JUL-15:00 | 24261.86 | 24261.86 | 26.42 | 108.85 |
August | 0.166774E+11 | 0.150097E+11 | 26948.14 | 11-AUG-14:40 | 24253.32 | 24253.32 | 26.00 | 108.85 |
September | 0.222081E+10 | 0.199873E+10 | 13439.54 | 07-SEP-16:00 | 12095.58 | 12095.58 | 22.61 | 54.43 |
October | 0.591355E+09 | 0.532220E+09 | 13425.34 | 28-OCT-14:00 | 12082.81 | 12082.81 | 21.14 | 54.43 |
November | 0.190025E+10 | 0.171023E+10 | 13425.35 | 13-NOV-07:50 | 12082.82 | 12082.82 | 21.14 | 54.43 |
December | 0.156880E+10 | 0.141192E+10 | 13425.36 | 19-DEC-21:50 | 12082.83 | 12082.83 | 21.14 | 54.43 |
Annual Sum or Average | 0.823873E+11 | 0.741486E+11 | ||||||
Minimum of Months | 0.591355E+09 | 0.532220E+09 | 13425.34 | 12082.81 | 12082.81 | 21.14 | 54.43 | |
Maximum of Months | 0.233311E+11 | 0.209980E+11 | 26957.62 | 24261.86 | 24261.86 | 26.42 | 108.85 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 36.31 | 36.31 | 328996.59 | 2252308.03 | 02-JAN-04:01 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 34.49 | 34.49 | 214325.73 | 2223375.03 | 07-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 40.61 | 82.00 | 89404.82 | 1955073.57 | 01-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 24.39 | 24.39 | 15885.58 | 1662979.99 | 04-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 24.67 | 24.67 | 263.27 | 173578.45 | 27-MAY-06:10 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.03 | 22.03 | 0.00 | 3.95 | 01-JUN-18:30 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.03 | 22.03 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 22.03 | 22.03 | 270.07 | 231075.29 | 31-AUG-06:10 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.10 | 24.10 | 6716.85 | 1390166.06 | 30-SEP-05:02 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 21.24 | 21.24 | 58708.19 | 1775038.87 | 30-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 29.28 | 29.28 | 266290.63 | 2118482.23 | 20-NOV-05:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 39.75 | 39.75 | 372850.85 | 2154705.88 | 12-DEC-05:01 |
Annual Sum or Average | 0.00 | 112419.78 | ||||||
Minimum of Months | 0.00 | 0.00 | 21.24 | 21.24 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 40.61 | 82.00 | 372850.85 | 2252308.03 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 180.59 | 5596.78 | 23-JAN-14:10 | 6.74 | 6.70 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 235.38 | 18913.22 | 17-FEB-08:30 | 6.85 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 283.68 | 23572.24 | 30-MAR-12:10 | 6.88 | 6.70 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 1010.38 | 173624.41 | 20-APR-14:10 | 8.04 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 48501.12 | 1248764.61 | 31-MAY-15:30 | 11.53 | 6.70 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 214816.09 | 1588908.91 | 20-JUN-13:10 | 12.85 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 269130.26 | 1621580.28 | 03-JUL-15:00 | 12.97 | 6.70 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 145554.65 | 1633071.21 | 11-AUG-15:20 | 13.02 | 6.70 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 3245.10 | 302669.79 | 07-SEP-16:00 | 9.04 | 6.70 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 89.20 | 12428.03 | 26-OCT-12:00 | 6.80 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 285.56 | 24296.60 | 07-NOV-10:00 | 6.89 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 197.79 | 23641.24 | 27-DEC-15:20 | 6.88 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 57450.30 | 0.00 | ||||||
Minimum of Months | 89.20 | 5596.78 | 6.74 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 269130.26 | 1633071.21 | 13.02 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 9.22 | 2636.84 | 23-JAN-14:10 | 10.13 | 6.70 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 62.36 | 19674.67 | 17-FEB-08:30 | 15.54 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 120.64 | 25941.42 | 30-MAR-12:10 | 17.23 | 6.70 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 922.98 | 174978.55 | 20-APR-14:00 | 14.28 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 47695.64 | 1115093.01 | 31-MAY-15:20 | 20.57 | 9.14 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 212607.70 | 1590281.57 | 20-JUN-14:40 | 17.25 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 268419.91 | 1673814.63 | 23-JUL-14:51 | 15.83 | 9.38 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 145297.59 | 1691496.69 | 24-AUG-13:15 | 14.73 | 9.79 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 3045.51 | 302583.76 | 07-SEP-16:00 | 17.02 | 6.70 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 37.59 | 14291.94 | 30-OCT-06:15 | 16.35 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 113.84 | 23920.19 | 07-NOV-10:00 | 17.21 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 60.75 | 23380.90 | 27-DEC-13:10 | 16.93 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 57022.82 | 0.00 | ||||||
Minimum of Months | 9.22 | 2636.84 | 10.13 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 268419.91 | 1691496.69 | 20.57 | 9.79 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 8994.16 | 52813.03 | 30-JAN-18:05 | 19.26 | 18.33 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 38531.72 | 151748.50 | 15-FEB-22:03 | 20.98 | 18.33 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 75993.15 | 252509.77 | 15-MAR-21:02 | 22.74 | 18.33 | 0.00 | 0.00 | 01-MAR-00:05 |
April | 116209.24 | 226590.36 | 07-APR-15:00 | 22.29 | 18.33 | 0.00 | 0.00 | 01-APR-00:10 |
May | 42527.68 | 285096.22 | 31-MAY-16:00 | 23.30 | 22.48 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 154402.32 | 1106275.45 | 30-JUN-15:00 | 37.37 | 30.68 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 320439.75 | 1415656.78 | 29-JUL-17:00 | 42.58 | 33.32 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 316989.19 | 1276877.10 | 11-AUG-17:00 | 40.25 | 29.46 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 29382.83 | 122885.29 | 29-SEP-07:43 | 20.48 | 18.33 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 48939.71 | 152013.14 | 12-OCT-08:55 | 20.99 | 18.33 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 66292.09 | 127087.43 | 08-NOV-15:40 | 20.55 | 18.33 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 90861.43 | 151848.57 | 26-DEC-13:50 | 20.99 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 109902.96 | 0.00 | ||||||
Minimum of Months | 8994.16 | 52813.03 | 19.26 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 320439.75 | 1415656.78 | 42.58 | 33.32 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 57.66 | 57.66 | 17739.75 | 62780.37 | 26-JAN-12:35 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 57.06 | 57.06 | 17847.57 | 62780.46 | 02-FEB-12:45 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 57.06 | 57.06 | 18970.66 | 62780.06 | 28-MAR-11:15 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.06 | 57.06 | 17768.27 | 62780.02 | 03-APR-11:35 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 57.66 | 57.66 | 18229.21 | 62779.71 | 04-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.13 | 57.13 | 18000.47 | 61218.34 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 57.24 | 57.24 | 15940.88 | 58671.81 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 57.34 | 57.34 | 17042.26 | 56912.72 | 01-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 57.38 | 57.38 | 15913.22 | 56528.85 | 29-SEP-11:25 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.36 | 57.36 | 16196.61 | 58205.24 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.28 | 57.28 | 17004.75 | 60510.60 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.17 | 57.17 | 17043.40 | 62780.46 | 29-DEC-12:25 |
Annual Sum or Average | 0.00 | 17305.15 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.06 | 57.06 | 15913.22 | 56528.85 | ||
Maximum of Months | 0.00 | 0.00 | 57.66 | 57.66 | 18970.66 | 62780.46 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 16.77 | 8610.34 | 13-JAN-18:50 | 21.14 | 20.20 | 2580.66 | 135887.67 | 09-JAN-18:00 |
February | 17.58 | 8796.40 | 03-FEB-17:10 | 21.14 | 20.20 | 2607.62 | 138309.85 | 06-FEB-07:15 |
March | 20.58 | 14839.17 | 30-MAR-10:35 | 21.17 | 20.22 | 2485.48 | 145784.59 | 12-MAR-14:04 |
April | 413.51 | 200399.96 | 20-APR-14:10 | 21.98 | 21.10 | 768.14 | 123209.46 | 03-APR-07:00 |
May | 48927.69 | 1469479.79 | 31-MAY-15:30 | 24.33 | 22.66 | 1648.20 | 97712.60 | 18-MAY-11:50 |
June | 247825.38 | 2315099.58 | 30-JUN-12:20 | 26.19 | 22.32 | 1089.06 | 82505.93 | 01-JUN-10:00 |
July | 327846.21 | 2420567.66 | 03-JUL-15:00 | 26.42 | 22.56 | 896.32 | 76242.87 | 13-JUL-08:70 |
August | 169804.45 | 2229656.14 | 11-AUG-14:40 | 26.00 | 21.10 | 1456.41 | 99606.27 | 31-AUG-13:20 |
September | 1895.25 | 342505.20 | 07-SEP-16:00 | 22.61 | 21.10 | 692.50 | 86018.63 | 15-SEP-16:20 |
October | 5.76 | 8077.71 | 28-OCT-14:00 | 21.14 | 20.19 | 823.35 | 144345.35 | 20-OCT-20:27 |
November | 4.67 | 8402.94 | 13-NOV-07:50 | 21.14 | 20.20 | 3147.83 | 135938.27 | 06-NOV-07:15 |
December | 16.35 | 8594.74 | 19-DEC-21:50 | 21.14 | 20.20 | 2170.10 | 129315.97 | 01-DEC-21:10 |
Annual Sum or Average | 66987.48 | 1692.64 | ||||||
Minimum of Months | 4.67 | 8077.71 | 21.14 | 20.19 | 692.50 | 76242.87 | ||
Maximum of Months | 327846.21 | 2420567.66 | 26.42 | 22.66 | 3147.83 | 145784.59 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.383230E+11 | 0.00 | 9586464.64 | 0.337914E+10 | 0.00 | 0.00 |
February | 0.203198E+11 | 0.00 | 13494518.46 | 0.354152E+10 | 0.00 | 0.00 |
March | 0.738198E+10 | 0.00 | 30259552.66 | 0.628222E+10 | 0.00 | 0.00 |
April | 0.575375E+09 | 0.00 | 0.578487E+09 | 0.136118E+11 | 0.00 | 0.00 |
May | 418698.69 | 0.00 | 0.168832E+11 | 0.197775E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.683985E+11 | 0.234729E+11 | 0.00 | 0.00 |
July | 1.43 | 0.00 | 0.893731E+11 | 0.229665E+11 | 0.00 | 0.00 |
August | 738.30 | 0.00 | 0.541274E+11 | 0.236143E+11 | 0.00 | 0.00 |
September | 36081222.33 | 0.00 | 0.138768E+10 | 0.134347E+11 | 0.00 | 0.00 |
October | 0.228527E+10 | 0.00 | 5304234.63 | 0.762319E+10 | 0.00 | 0.00 |
November | 0.287378E+11 | 0.00 | 14741916.28 | 0.382089E+10 | 0.00 | 0.00 |
December | 0.447253E+11 | 0.00 | 10090178.88 | 0.380914E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.142385E+12 | 0.00 | 0.230832E+12 | 0.145334E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 5304234.63 | 0.337914E+10 | 0.00 | 0.00 |
Maximum of Months | 0.447253E+11 | 0.00 | 0.893731E+11 | 0.236143E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.710079E+12 | 0.00 | 14918794.93 | 0.435616E+11 | 0.00 | 0.00 |
February | 0.411204E+12 | 0.00 | 25649979.51 | 0.371614E+11 | 0.00 | 0.00 |
March | 0.185240E+12 | 0.00 | 50228917.25 | 0.427591E+11 | 0.00 | 0.00 |
April | 0.298624E+11 | 0.00 | 0.167150E+10 | 0.599952E+11 | 0.00 | 0.00 |
May | 0.382930E+09 | 0.00 | 0.101219E+12 | 0.910616E+11 | 0.00 | 0.00 |
June | 3769.46 | 0.00 | 0.428630E+12 | 0.113527E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.548012E+12 | 0.105542E+12 | 0.00 | 0.00 |
August | 0.478380E+09 | 0.00 | 0.295956E+12 | 0.933713E+11 | 0.00 | 0.00 |
September | 0.120733E+11 | 0.00 | 0.605070E+10 | 0.494603E+11 | 0.00 | 0.00 |
October | 0.120773E+12 | 0.00 | 15924748.62 | 0.364993E+11 | 0.00 | 0.00 |
November | 0.548441E+12 | 0.00 | 27641483.67 | 0.372421E+11 | 0.00 | 0.00 |
December | 0.804840E+12 | 0.00 | 9780393.10 | 0.411417E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.282337E+13 | 0.00 | 0.138168E+13 | 0.751324E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 9780393.10 | 0.364993E+11 | 0.00 | 0.00 |
Maximum of Months | 0.804840E+12 | 0.00 | 0.548012E+12 | 0.113527E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.121586E+12 | 0.00 | 512535.41 | 0.511156E+10 | 0.00 | 0.00 |
February | 0.795317E+11 | 0.00 | 1558701.44 | 0.442685E+10 | 0.00 | 0.00 |
March | 0.446158E+11 | 0.00 | 6377036.16 | 0.467681E+10 | 0.00 | 0.00 |
April | 0.108419E+11 | 0.00 | 74219555.14 | 0.489486E+10 | 0.00 | 0.00 |
May | 0.347093E+09 | 0.00 | 0.977131E+10 | 0.736560E+10 | 0.00 | 0.00 |
June | 199.59 | 0.00 | 0.439538E+11 | 0.103625E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.562469E+11 | 0.962885E+10 | 0.00 | 0.00 |
August | 0.231722E+09 | 0.00 | 0.295228E+11 | 0.783852E+10 | 0.00 | 0.00 |
September | 0.541384E+10 | 0.00 | 0.490260E+09 | 0.381245E+10 | 0.00 | 0.00 |
October | 0.341688E+11 | 0.00 | 399195.64 | 0.395775E+10 | 0.00 | 0.00 |
November | 0.103316E+12 | 0.00 | 127710.23 | 0.481033E+10 | 0.00 | 0.00 |
December | 0.134942E+12 | 0.00 | 240975.64 | 0.522840E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.534995E+12 | 0.00 | 0.140068E+12 | 0.721144E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 127710.23 | 0.381245E+10 | 0.00 | 0.00 |
Maximum of Months | 0.134942E+12 | 0.00 | 0.562469E+11 | 0.103625E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.158350E+11 | 0.00 | 70858661.12 | 0.689927E+10 | 0.00 | 0.00 |
February | 0.101045E+11 | 0.00 | 0.181775E+09 | 0.890608E+10 | 0.00 | 0.00 |
March | 0.360249E+10 | 0.00 | 0.256117E+09 | 0.130076E+11 | 0.00 | 0.00 |
April | 0.107023E+09 | 0.00 | 40813055.79 | 0.554768E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.764574E+09 | 0.00 | 92631131.71 | 0.714133E+10 | 0.00 | 0.00 |
November | 0.132566E+11 | 0.00 | 0.259505E+09 | 0.941658E+10 | 0.00 | 0.00 |
December | 0.194063E+11 | 0.00 | 0.140921E+09 | 0.699343E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.630765E+11 | 0.00 | 0.104262E+10 | 0.579119E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.194063E+11 | 0.00 | 0.259505E+09 | 0.130076E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.109636E+11 | 0.236941E+12 | 0.00 | 45.29 |
February | 0.00 | 0.00 | 0.164642E+11 | 0.298837E+12 | 0.00 | 71.91 |
March | 0.00 | 0.00 | 0.218855E+11 | 0.385575E+12 | 0.00 | 99.58 |
April | 0.00 | 0.00 | 0.239888E+11 | 0.374179E+12 | 0.00 | 96.40 |
May | 0.00 | 0.00 | 0.150827E+11 | 0.305010E+12 | 0.00 | 70.27 |
June | 0.00 | 0.00 | 0.696623E+11 | 0.236448E+12 | 0.00 | 41.08 |
July | 0.00 | 0.00 | 0.274566E+12 | 0.206481E+12 | 0.00 | 11.11 |
August | 0.00 | 0.00 | 0.332313E+12 | 0.261519E+12 | 0.00 | 27.88 |
September | 0.00 | 0.00 | 0.940095E+10 | 0.210098E+12 | 0.00 | 36.79 |
October | 0.00 | 0.00 | 0.187447E+11 | 0.339928E+12 | 0.00 | 82.94 |
November | 0.00 | 0.00 | 0.217095E+11 | 0.373092E+12 | 0.00 | 96.32 |
December | 0.00 | 0.00 | 0.224673E+11 | 0.386067E+12 | 0.00 | 99.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.837248E+12 | 0.361418E+13 | 0.00 | 779.22 |
Minimum of Months | 0.00 | 0.00 | 0.940095E+10 | 0.206481E+12 | 0.00 | 11.11 |
Maximum of Months | 0.00 | 0.00 | 0.332313E+12 | 0.386067E+12 | 0.00 | 99.64 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.234343E+10 | 0.212379E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.900415E+10 | 0.332357E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.176660E+11 | 0.512564E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.247365E+11 | 0.624349E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.762824E+10 | 0.314262E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.138466E+11 | 0.426407E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.207595E+11 | 0.564723E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.264504E+11 | 0.653037E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.671596E+10 | 0.289310E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.118385E+11 | 0.397467E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.158856E+11 | 0.477210E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.224212E+11 | 0.604400E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.179296E+12 | 0.540847E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.234343E+10 | 0.212379E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.264504E+11 | 0.653037E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.129167E+10 | 0.155563E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.558950E+11 | 0.258848E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.142655E+12 | 0.443578E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.222175E+12 | 0.574303E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.634561E+11 | 0.283711E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.127361E+12 | 0.400249E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.192973E+12 | 0.532088E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.245899E+12 | 0.614824E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.476694E+11 | 0.246175E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.852119E+11 | 0.328449E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.115968E+12 | 0.390088E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.173753E+12 | 0.506426E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.147431E+13 | 0.473430E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.129167E+10 | 0.155563E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.245899E+12 | 0.614824E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 707560.85 | 0.153233E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.330517E+10 | 0.211467E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.116723E+11 | 0.395058E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.205408E+11 | 0.546341E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.565901E+10 | 0.271529E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.125380E+11 | 0.398149E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.191314E+11 | 0.530976E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.241859E+11 | 0.609935E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.320980E+10 | 0.216303E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.573338E+10 | 0.274310E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.894269E+10 | 0.338913E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.149075E+11 | 0.461486E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.129827E+12 | 0.440770E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 707560.85 | 0.153233E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.241859E+11 | 0.609935E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.337914E+10 | 9586464.64 | 0.383230E+11 | 0.537406E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.354152E+10 | 13494518.46 | 0.203198E+11 | 0.401020E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.628222E+10 | 30259552.66 | 0.738198E+10 | 0.358568E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136118E+11 | 0.578487E+09 | 0.575375E+09 | 0.598339E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.197775E+11 | 0.168832E+11 | 418698.69 | 1592468.90 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.234729E+11 | 0.683985E+11 | 0.00 | 0.126455E+09 | 3839685.87 | 0.00 | 0.00 | 0.00 |
July | 0.229665E+11 | 0.893731E+11 | 1.43 | 0.321771E+09 | 0.119498E+09 | 0.00 | 0.00 | 0.00 |
August | 0.236143E+11 | 0.541274E+11 | 738.30 | 29031735.28 | 155396.58 | 0.00 | 0.00 | 0.00 |
September | 0.134347E+11 | 0.138768E+10 | 36081222.33 | 0.336800E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.762319E+10 | 5304234.63 | 0.228527E+10 | 0.206295E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.382089E+10 | 14741916.28 | 0.287378E+11 | 0.490557E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.380914E+10 | 10090178.88 | 0.447253E+11 | 0.468525E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145334E+12 | 0.230832E+12 | 0.142385E+12 | 0.253036E+12 | 0.123493E+09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.337914E+10 | 5304234.63 | 0.00 | 1592468.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.236143E+11 | 0.893731E+11 | 0.447253E+11 | 0.537406E+11 | 0.119498E+09 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.435616E+11 | 14918794.93 | 0.710079E+12 | 0.562954E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.371614E+11 | 25649979.51 | 0.411204E+12 | 0.456601E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.427591E+11 | 50228917.25 | 0.185240E+12 | 0.484174E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.599952E+11 | 0.167150E+10 | 0.298624E+11 | 0.114444E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.910616E+11 | 0.101219E+12 | 0.382930E+09 | 0.439182E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.113527E+12 | 0.428630E+12 | 3769.46 | 0.194134E+10 | 15349166.90 | 0.00 | 0.00 | 0.00 |
July | 0.105542E+12 | 0.548012E+12 | 0.00 | 0.390515E+10 | 0.148784E+10 | 0.00 | 0.00 | 0.00 |
August | 0.933713E+11 | 0.295956E+12 | 0.478380E+09 | 0.161416E+10 | 3446142.74 | 0.00 | 0.00 | 0.00 |
September | 0.494603E+11 | 0.605070E+10 | 0.120733E+11 | 0.426971E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.364993E+11 | 15924748.62 | 0.120773E+12 | 0.313963E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.372421E+11 | 27641483.67 | 0.548441E+12 | 0.548266E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.411417E+11 | 9780393.10 | 0.804840E+12 | 0.493942E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.751324E+12 | 0.138168E+13 | 0.282337E+13 | 0.302889E+13 | 0.150664E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.364993E+11 | 9780393.10 | 0.00 | 0.161416E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.113527E+12 | 0.548012E+12 | 0.804840E+12 | 0.562954E+12 | 0.148784E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.511156E+10 | 512535.41 | 0.121586E+12 | 0.556407E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.442685E+10 | 1558701.44 | 0.795317E+11 | 0.470657E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.467681E+10 | 6377036.16 | 0.446158E+11 | 0.528523E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.489486E+10 | 74219555.14 | 0.108419E+11 | 0.149034E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.736560E+10 | 0.977131E+10 | 0.347093E+09 | 0.746941E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.103625E+11 | 0.439538E+11 | 199.59 | 0.128417E+09 | 5969174.53 | 0.00 | 0.00 | 0.00 |
July | 0.962885E+10 | 0.562469E+11 | 0.00 | 0.245832E+09 | 0.115232E+09 | 0.00 | 0.00 | 0.00 |
August | 0.783852E+10 | 0.295228E+11 | 0.231722E+09 | 0.413615E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.381245E+10 | 0.490260E+09 | 0.541384E+10 | 0.752441E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.395775E+10 | 399195.64 | 0.341688E+11 | 0.363521E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.481033E+10 | 127710.23 | 0.103316E+12 | 0.544292E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.522840E+10 | 240975.64 | 0.134942E+12 | 0.476856E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.721144E+11 | 0.140068E+12 | 0.534995E+12 | 0.317988E+12 | 0.121201E+09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.381245E+10 | 127710.23 | 0.00 | 0.128417E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.103625E+11 | 0.562469E+11 | 0.134942E+12 | 0.556407E+11 | 0.115232E+09 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.689927E+10 | 70858661.12 | 0.158350E+11 | 0.232891E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.890608E+10 | 0.181775E+09 | 0.101045E+11 | 0.139356E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130076E+11 | 0.256117E+09 | 0.360249E+10 | 0.904314E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.554768E+10 | 40813055.79 | 0.107023E+09 | 0.721394E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.714133E+10 | 92631131.71 | 0.764574E+09 | 0.295368E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.941658E+10 | 0.259505E+09 | 0.132566E+11 | 0.129501E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.699343E+10 | 0.140921E+09 | 0.194063E+11 | 0.166538E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.579119E+11 | 0.104262E+10 | 0.630765E+11 | 0.795468E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130076E+11 | 0.259505E+09 | 0.194063E+11 | 0.232891E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.110532E+12 | 0.629782E+10 | 0.00 | 0.00 | 0.00 | 0.121197E+12 | 0.00 | 0.00 |
February | 0.998352E+11 | 0.107595E+11 | 0.00 | 0.00 | 0.00 | 0.192430E+12 | 0.00 | 0.00 |
March | 0.110532E+12 | 0.145409E+11 | 0.00 | 0.00 | 0.00 | 0.266499E+12 | 0.00 | 0.00 |
April | 0.106966E+12 | 0.159161E+11 | 0.00 | 0.00 | 0.00 | 0.257979E+12 | 0.00 | 0.00 |
May | 0.110532E+12 | 0.951385E+10 | 0.00 | 0.00 | 0.00 | 0.188062E+12 | 0.00 | 0.00 |
June | 0.106966E+12 | 0.506191E+11 | 0.00 | 0.00 | 0.00 | 0.109944E+12 | 0.00 | 0.00 |
July | 0.110532E+12 | 0.208474E+12 | 0.00 | 0.00 | 0.00 | 0.297237E+11 | 0.00 | 0.00 |
August | 0.110532E+12 | 0.256277E+12 | 0.00 | 0.00 | 0.00 | 0.746159E+11 | 0.00 | 0.00 |
September | 0.106966E+12 | 0.516386E+10 | 0.00 | 0.00 | 0.00 | 0.984517E+11 | 0.00 | 0.00 |
October | 0.110532E+12 | 0.123142E+11 | 0.00 | 0.00 | 0.00 | 0.221967E+12 | 0.00 | 0.00 |
November | 0.106966E+12 | 0.145205E+11 | 0.00 | 0.00 | 0.00 | 0.257776E+12 | 0.00 | 0.00 |
December | 0.110532E+12 | 0.147717E+11 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.130142E+13 | 0.619169E+12 | 0.00 | 0.00 | 0.00 | 0.208529E+13 | 0.00 | 0.00 |
Minimum of Months | 0.998352E+11 | 0.516386E+10 | 0.00 | 0.00 | 0.00 | 0.297237E+11 | 0.00 | 0.00 |
Maximum of Months | 0.110532E+12 | 0.256277E+12 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.157372E+10 | 0.179336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142142E+10 | 0.710200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157372E+10 | 0.141141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152295E+10 | 0.200160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157372E+10 | 0.605933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152295E+10 | 0.111055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157372E+10 | 0.166860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.157372E+10 | 0.214937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152295E+10 | 0.534581E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157372E+10 | 0.943756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152295E+10 | 0.126365E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157372E+10 | 0.179509E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185292E+11 | 0.143741E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142142E+10 | 0.179336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.157372E+10 | 0.214937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.151933E+11 | 0.928658E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137230E+11 | 0.437331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151933E+11 | 0.113490E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147032E+11 | 0.179448E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151933E+11 | 0.502783E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147032E+11 | 0.102039E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.151933E+11 | 0.154957E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.151933E+11 | 0.199610E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147032E+11 | 0.377551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151933E+11 | 0.675603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147032E+11 | 0.916625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151933E+11 | 0.138304E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178889E+12 | 0.117977E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137230E+11 | 0.928658E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.151933E+11 | 0.199610E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.153207E+10 | 448256.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138381E+10 | 0.257430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153207E+10 | 0.925383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148265E+10 | 0.165600E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153207E+10 | 0.447580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.148265E+10 | 0.100391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153207E+10 | 0.153538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153207E+10 | 0.196186E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.148265E+10 | 0.252942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153207E+10 | 0.452236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148265E+10 | 0.703620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153207E+10 | 0.118247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180389E+11 | 0.103789E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.138381E+10 | 448256.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153207E+10 | 0.196186E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.337914E+10 | 0.383230E+11 | 9586464.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.354152E+10 | 0.203198E+11 | 13494518.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.628222E+10 | 0.738198E+10 | 30259552.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136118E+11 | 0.575375E+09 | 0.578487E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.197775E+11 | 418698.69 | 0.168832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.234729E+11 | 0.00 | 0.683985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.229665E+11 | 1.43 | 0.893731E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.236143E+11 | 738.30 | 0.541274E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.134347E+11 | 36081222.33 | 0.138768E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.762319E+10 | 0.228527E+10 | 5304234.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.382089E+10 | 0.287378E+11 | 14741916.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.380914E+10 | 0.447253E+11 | 10090178.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145334E+12 | 0.142385E+12 | 0.230832E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.337914E+10 | 0.00 | 5304234.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.236143E+11 | 0.447253E+11 | 0.893731E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.435616E+11 | 0.710079E+12 | 14918794.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.371614E+11 | 0.411204E+12 | 25649979.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.427591E+11 | 0.185240E+12 | 50228917.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.599952E+11 | 0.298624E+11 | 0.167150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.910616E+11 | 0.382930E+09 | 0.101219E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.113527E+12 | 3769.46 | 0.428630E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.105542E+12 | 0.00 | 0.548012E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.933713E+11 | 0.478380E+09 | 0.295956E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.494603E+11 | 0.120733E+11 | 0.605070E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.364993E+11 | 0.120773E+12 | 15924748.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.372421E+11 | 0.548441E+12 | 27641483.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.411417E+11 | 0.804840E+12 | 9780393.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.751324E+12 | 0.282337E+13 | 0.138168E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.364993E+11 | 0.00 | 9780393.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.113527E+12 | 0.804840E+12 | 0.548012E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.511156E+10 | 0.121586E+12 | 512535.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.442685E+10 | 0.795317E+11 | 1558701.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.467681E+10 | 0.446158E+11 | 6377036.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.489486E+10 | 0.108419E+11 | 74219555.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.736560E+10 | 0.347093E+09 | 0.977131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.103625E+11 | 199.59 | 0.439538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.962885E+10 | 0.00 | 0.562469E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.783852E+10 | 0.231722E+09 | 0.295228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.381245E+10 | 0.541384E+10 | 0.490260E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.395775E+10 | 0.341688E+11 | 399195.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.481033E+10 | 0.103316E+12 | 127710.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.522840E+10 | 0.134942E+12 | 240975.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.721144E+11 | 0.534995E+12 | 0.140068E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.381245E+10 | 0.00 | 127710.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.103625E+11 | 0.134942E+12 | 0.562469E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.689927E+10 | 0.158350E+11 | 70858661.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.890608E+10 | 0.101045E+11 | 0.181775E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130076E+11 | 0.360249E+10 | 0.256117E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.554768E+10 | 0.107023E+09 | 40813055.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.714133E+10 | 0.764574E+09 | 92631131.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.941658E+10 | 0.132566E+11 | 0.259505E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.699343E+10 | 0.194063E+11 | 0.140921E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.579119E+11 | 0.630765E+11 | 0.104262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130076E+11 | 0.194063E+11 | 0.259505E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.110532E+12 | 0.00 | 0.109636E+11 | 0.00 | 0.466576E+10 | 0.00 | 0.00 | 0.00 | 0.121743E+12 | 0.00 | 0.00 | 0.00 |
February | 0.998352E+11 | 0.00 | 0.164642E+11 | 0.00 | 0.570478E+10 | 0.00 | 0.00 | 0.00 | 0.193297E+12 | 0.00 | 0.00 | 0.00 |
March | 0.110532E+12 | 0.00 | 0.218855E+11 | 0.00 | 0.734457E+10 | 0.00 | 0.00 | 0.00 | 0.267699E+12 | 0.00 | 0.00 | 0.00 |
April | 0.106966E+12 | 0.00 | 0.239888E+11 | 0.00 | 0.807265E+10 | 0.00 | 0.00 | 0.00 | 0.259140E+12 | 0.00 | 0.00 | 0.00 |
May | 0.110532E+12 | 0.00 | 0.150827E+11 | 0.00 | 0.556888E+10 | 0.00 | 0.00 | 0.00 | 0.188909E+12 | 0.00 | 0.00 | 0.00 |
June | 0.106966E+12 | 0.00 | 0.696623E+11 | 0.00 | 0.190431E+11 | 0.00 | 0.00 | 0.00 | 0.110439E+12 | 0.00 | 0.00 | 0.00 |
July | 0.110532E+12 | 0.00 | 0.274566E+12 | 0.00 | 0.660920E+11 | 0.00 | 0.00 | 0.00 | 0.298575E+11 | 0.00 | 0.00 | 0.00 |
August | 0.110532E+12 | 0.00 | 0.332313E+12 | 0.00 | 0.760357E+11 | 0.00 | 0.00 | 0.00 | 0.749518E+11 | 0.00 | 0.00 | 0.00 |
September | 0.106966E+12 | 0.00 | 0.940095E+10 | 0.00 | 0.423709E+10 | 0.00 | 0.00 | 0.00 | 0.988948E+11 | 0.00 | 0.00 | 0.00 |
October | 0.110532E+12 | 0.00 | 0.187447E+11 | 0.00 | 0.643045E+10 | 0.00 | 0.00 | 0.00 | 0.222966E+12 | 0.00 | 0.00 | 0.00 |
November | 0.106966E+12 | 0.00 | 0.217095E+11 | 0.00 | 0.718898E+10 | 0.00 | 0.00 | 0.00 | 0.258937E+12 | 0.00 | 0.00 | 0.00 |
December | 0.110532E+12 | 0.00 | 0.224673E+11 | 0.00 | 0.769559E+10 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130142E+13 | 0.00 | 0.837248E+12 | 0.00 | 0.218080E+12 | 0.00 | 0.00 | 0.00 | 0.209467E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.998352E+11 | 0.00 | 0.940095E+10 | 0.00 | 0.423709E+10 | 0.00 | 0.00 | 0.00 | 0.298575E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.110532E+12 | 0.00 | 0.332313E+12 | 0.00 | 0.760357E+11 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.157372E+10 | 0.00 | 0.234343E+10 | 0.00 | 0.550069E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142142E+10 | 0.00 | 0.900415E+10 | 0.00 | 0.190215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157372E+10 | 0.00 | 0.176660E+11 | 0.00 | 0.355193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152295E+10 | 0.00 | 0.247365E+11 | 0.00 | 0.472054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157372E+10 | 0.00 | 0.762824E+10 | 0.00 | 0.156891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152295E+10 | 0.00 | 0.138466E+11 | 0.00 | 0.274112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157372E+10 | 0.00 | 0.207595E+11 | 0.00 | 0.407352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.157372E+10 | 0.00 | 0.264504E+11 | 0.00 | 0.495666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152295E+10 | 0.00 | 0.671596E+10 | 0.00 | 0.137015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157372E+10 | 0.00 | 0.118385E+11 | 0.00 | 0.240096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152295E+10 | 0.00 | 0.158856E+11 | 0.00 | 0.324915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157372E+10 | 0.00 | 0.224212E+11 | 0.00 | 0.447028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185292E+11 | 0.00 | 0.179296E+12 | 0.00 | 0.355554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142142E+10 | 0.00 | 0.234343E+10 | 0.00 | 0.550069E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.157372E+10 | 0.00 | 0.264504E+11 | 0.00 | 0.495666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.151933E+11 | 0.00 | 0.129167E+10 | 0.00 | 0.363012E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137230E+11 | 0.00 | 0.558950E+11 | 0.00 | 0.121618E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151933E+11 | 0.00 | 0.142655E+12 | 0.00 | 0.291645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147032E+11 | 0.00 | 0.222175E+12 | 0.00 | 0.427271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151933E+11 | 0.00 | 0.634561E+11 | 0.00 | 0.131778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147032E+11 | 0.00 | 0.127361E+12 | 0.00 | 0.253217E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.151933E+11 | 0.00 | 0.192973E+12 | 0.00 | 0.380155E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.151933E+11 | 0.00 | 0.245899E+12 | 0.00 | 0.462891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147032E+11 | 0.00 | 0.476694E+11 | 0.00 | 0.991433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151933E+11 | 0.00 | 0.852119E+11 | 0.00 | 0.176516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147032E+11 | 0.00 | 0.115968E+12 | 0.00 | 0.243056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151933E+11 | 0.00 | 0.173753E+12 | 0.00 | 0.354493E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178889E+12 | 0.00 | 0.147431E+13 | 0.00 | 0.294541E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137230E+11 | 0.00 | 0.129167E+10 | 0.00 | 0.363012E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.151933E+11 | 0.00 | 0.245899E+12 | 0.00 | 0.462891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.153207E+10 | 0.00 | 707560.85 | 0.00 | 259304.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138381E+10 | 0.00 | 0.330517E+10 | 0.00 | 0.730865E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153207E+10 | 0.00 | 0.116723E+11 | 0.00 | 0.241851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148265E+10 | 0.00 | 0.205408E+11 | 0.00 | 0.398076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153207E+10 | 0.00 | 0.565901E+10 | 0.00 | 0.118322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.148265E+10 | 0.00 | 0.125380E+11 | 0.00 | 0.249884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153207E+10 | 0.00 | 0.191314E+11 | 0.00 | 0.377769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153207E+10 | 0.00 | 0.241859E+11 | 0.00 | 0.456728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.148265E+10 | 0.00 | 0.320980E+10 | 0.00 | 0.680380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153207E+10 | 0.00 | 0.573338E+10 | 0.00 | 0.121102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148265E+10 | 0.00 | 0.894269E+10 | 0.00 | 0.190648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153207E+10 | 0.00 | 0.149075E+11 | 0.00 | 0.308279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180389E+11 | 0.00 | 0.129827E+12 | 0.00 | 0.260381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.138381E+10 | 0.00 | 707560.85 | 0.00 | 259304.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153207E+10 | 0.00 | 0.241859E+11 | 0.00 | 0.456728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 63216848.70 | 0.00 | 0.00 | 0.574699E+11 | 0.00 | 0.29 |
February | 0.00 | 0.00 | 0.00 | 74830752.56 | 0.00 | 0.00 | 0.551090E+11 | 0.00 | 0.32 |
March | 0.00 | 0.00 | 0.00 | 0.122466E+09 | 0.00 | 0.00 | 0.669389E+11 | 0.00 | 0.36 |
April | 0.00 | 0.00 | 0.00 | 61499255.69 | 0.00 | 0.00 | 0.300166E+11 | 0.00 | 0.19 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 94562007.22 | 0.00 | 0.00 | 0.428546E+11 | 0.00 | 0.23 |
November | 0.00 | 0.00 | 0.00 | 93557171.59 | 0.00 | 0.00 | 0.684976E+11 | 0.00 | 0.32 |
December | 0.00 | 0.00 | 0.00 | 83206133.61 | 0.00 | 0.00 | 0.689931E+11 | 0.00 | 0.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.593338E+09 | 0.00 | 0.00 | 0.389880E+12 | 0.00 | 0.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.122466E+09 | 0.00 | 0.00 | 0.689931E+11 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.210174E+11 | 0.00 | 0.00 | 22880158.99 | 0.00 | 0.00 | 0.221128E+11 | 0.00 | 0.28 |
February | 0.129391E+11 | 0.00 | 0.00 | 40555541.12 | 0.00 | 0.00 | 0.289104E+11 | 0.00 | 0.31 |
March | 0.495372E+10 | 0.00 | 0.00 | 93202441.83 | 0.00 | 0.00 | 0.507902E+11 | 0.00 | 0.37 |
April | 0.826412E+10 | 0.00 | 0.00 | 0.133267E+09 | 0.00 | 0.00 | 0.749835E+11 | 0.00 | 0.74 |
May | 0.995579E+10 | 0.00 | 0.00 | 0.154228E+09 | 0.00 | 0.00 | 0.892941E+11 | 0.00 | 1.33 |
June | 0.115573E+11 | 3656467.55 | 0.00 | 0.166952E+09 | 0.00 | 0.00 | 0.689712E+11 | 0.00 | 1.63 |
July | 0.155145E+11 | 0.146075E+09 | 0.00 | 0.167443E+09 | 14800965.87 | 0.00 | 0.575192E+11 | 0.00 | 1.57 |
August | 0.135834E+11 | 0.00 | 0.00 | 0.193261E+09 | 0.00 | 0.00 | 0.881556E+11 | 0.00 | 1.68 |
September | 0.720376E+10 | 0.00 | 0.00 | 0.149793E+09 | 0.00 | 0.00 | 0.876962E+11 | 0.00 | 0.97 |
October | 0.441833E+10 | 0.00 | 0.00 | 0.107895E+09 | 0.00 | 0.00 | 0.619280E+11 | 0.00 | 0.51 |
November | 0.102841E+11 | 0.00 | 0.00 | 44391145.15 | 0.00 | 0.00 | 0.399100E+11 | 0.00 | 0.31 |
December | 0.132619E+11 | 0.00 | 0.00 | 39045206.01 | 0.00 | 0.00 | 0.428625E+11 | 0.00 | 0.30 |
Annual Sum or Average | 0.132953E+12 | 0.149731E+09 | 0.00 | 0.131291E+10 | 14800965.87 | 0.00 | 0.713134E+12 | 0.00 | 0.84 |
Minimum of Months | 0.441833E+10 | 0.00 | 0.00 | 22880158.99 | 0.00 | 0.00 | 0.221128E+11 | 0.00 | 0.28 |
Maximum of Months | 0.210174E+11 | 0.146075E+09 | 0.00 | 0.193261E+09 | 14800965.87 | 0.00 | 0.892941E+11 | 0.00 | 1.68 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.364833E+12 | 0.00 | 0.00 | 3295.75 | 0.00 | 0.159342E+11 | 0.118467E+09 | 0.00 | 0.27 |
February | 0.298852E+12 | 0.00 | 0.00 | 30321678.81 | 0.00 | 0.576371E+10 | 0.277553E+11 | 0.00 | 0.28 |
March | 0.227340E+12 | 0.00 | 0.00 | 0.160703E+09 | 0.00 | 0.107948E+09 | 0.122718E+12 | 0.00 | 0.29 |
April | 0.115000E+12 | 0.00 | 0.00 | 0.423572E+09 | 0.00 | 0.00 | 0.300583E+12 | 0.00 | 0.40 |
May | 0.593347E+11 | 0.00 | 0.00 | 0.688881E+09 | 0.00 | 0.00 | 0.470660E+12 | 0.00 | 0.75 |
June | 0.449911E+11 | 1618140.92 | 0.00 | 0.780179E+09 | 0.00 | 0.00 | 0.380312E+12 | 0.00 | 0.92 |
July | 0.534451E+11 | 0.103866E+10 | 0.00 | 0.736694E+09 | 0.220987E+09 | 0.00 | 0.299929E+12 | 0.00 | 0.84 |
August | 0.386035E+11 | 0.00 | 0.00 | 0.792223E+09 | 0.00 | 0.00 | 0.428870E+12 | 0.00 | 0.82 |
September | 0.810941E+11 | 0.00 | 0.00 | 0.470692E+09 | 0.00 | 0.00 | 0.345645E+12 | 0.00 | 0.47 |
October | 0.172934E+12 | 0.00 | 0.00 | 0.186843E+09 | 0.00 | 0.128782E+09 | 0.143337E+12 | 0.00 | 0.30 |
November | 0.356608E+12 | 0.00 | 0.00 | 3992847.06 | 0.00 | 0.574171E+10 | 0.107468E+11 | 0.00 | 0.27 |
December | 0.438937E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.656812E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.225197E+13 | 0.104028E+10 | 0.00 | 0.427410E+10 | 0.220987E+09 | 0.342444E+11 | 0.253068E+13 | 0.00 | 0.49 |
Minimum of Months | 0.386035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.438937E+12 | 0.103866E+10 | 0.00 | 0.792223E+09 | 0.220987E+09 | 0.159342E+11 | 0.470660E+12 | 0.00 | 0.92 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.180348E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127879E+11 | 0.00 | 0.00 | 0.25 |
February | 0.166416E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.890650E+10 | 0.00 | 0.00 | 0.26 |
March | 0.223504E+11 | 0.00 | 0.00 | 348378.03 | 0.00 | 0.350362E+10 | 0.642758E+09 | 0.00 | 0.28 |
April | 0.177020E+11 | 0.00 | 0.00 | 14565520.96 | 0.00 | 0.512195E+09 | 0.135083E+11 | 0.00 | 0.34 |
May | 0.101371E+11 | 0.00 | 0.00 | 48556927.94 | 0.00 | 0.00 | 0.362952E+11 | 0.00 | 0.68 |
June | 0.519527E+10 | 8543186.44 | 0.00 | 69270981.41 | 0.00 | 0.00 | 0.361423E+11 | 0.00 | 0.91 |
July | 0.575549E+10 | 94349512.71 | 0.00 | 64885677.59 | 18762695.06 | 0.00 | 0.276201E+11 | 0.00 | 0.84 |
August | 0.585975E+10 | 0.00 | 0.00 | 60847129.71 | 0.00 | 0.00 | 0.347969E+11 | 0.00 | 0.76 |
September | 0.169428E+11 | 0.00 | 0.00 | 14851520.12 | 0.00 | 0.110080E+09 | 0.138403E+11 | 0.00 | 0.38 |
October | 0.189735E+11 | 0.00 | 0.00 | 1436910.48 | 0.00 | 0.198479E+10 | 0.165333E+10 | 0.00 | 0.27 |
November | 0.195210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105680E+11 | 0.00 | 0.00 | 0.25 |
December | 0.214507E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153566E+11 | 0.00 | 0.00 | 0.25 |
Annual Sum or Average | 0.178564E+12 | 0.102893E+09 | 0.00 | 0.274763E+09 | 18762695.06 | 0.537297E+11 | 0.164499E+12 | 0.00 | 0.46 |
Minimum of Months | 0.519527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.223504E+11 | 94349512.71 | 0.00 | 69270981.41 | 18762695.06 | 0.153566E+11 | 0.362952E+11 | 0.00 | 0.91 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398793E+10 | 0.00 | 0.00 | 0.26 |
February | 0.230821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210605E+10 | 0.00 | 0.00 | 0.25 |
March | 0.371324E+10 | 0.00 | 0.00 | 481806.73 | 0.00 | 0.695089E+09 | 0.445256E+09 | 0.00 | 0.26 |
April | 0.251362E+10 | 0.00 | 0.00 | 7610681.56 | 0.00 | 22198661.68 | 0.557557E+10 | 0.00 | 0.60 |
May | 0.134170E+10 | 0.00 | 0.00 | 18929706.17 | 0.00 | 0.00 | 0.116266E+11 | 0.00 | 1.42 |
June | 0.120593E+10 | 663141.56 | 0.00 | 31382678.12 | 0.00 | 0.00 | 0.117877E+11 | 0.00 | 2.12 |
July | 0.161860E+10 | 25303649.62 | 0.00 | 30026290.93 | 1215217.06 | 0.00 | 0.930125E+10 | 0.00 | 1.95 |
August | 0.194136E+10 | 0.00 | 0.00 | 21578450.91 | 0.00 | 0.00 | 0.107129E+11 | 0.00 | 1.75 |
September | 0.177089E+10 | 0.00 | 0.00 | 9242090.17 | 0.00 | 0.00 | 0.674443E+10 | 0.00 | 0.73 |
October | 0.295763E+10 | 0.00 | 0.00 | 2568544.80 | 0.00 | 0.203813E+09 | 0.208161E+10 | 0.00 | 0.33 |
November | 0.263965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237154E+10 | 0.00 | 0.00 | 0.25 |
December | 0.219167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351583E+10 | 0.00 | 0.00 | 0.25 |
Annual Sum or Average | 0.253733E+11 | 25966791.18 | 0.00 | 0.121820E+09 | 1215217.06 | 0.129024E+11 | 0.582754E+11 | 0.00 | 0.85 |
Minimum of Months | 0.117083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.371324E+10 | 25303649.62 | 0.00 | 31382678.12 | 1215217.06 | 0.398793E+10 | 0.117877E+11 | 0.00 | 2.12 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.123105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508084E+10 | 0.00 | 0.00 | 0.50 |
February | 0.300288E+10 | 0.00 | 0.00 | 46461.77 | 0.00 | 0.236512E+10 | 40325065.50 | 0.00 | 0.48 |
March | 0.371789E+10 | 0.00 | 0.00 | 4206456.07 | 0.00 | 0.778204E+09 | 0.219999E+10 | 0.00 | 0.55 |
April | 0.301338E+10 | 0.00 | 0.00 | 11228495.72 | 0.00 | 50651627.31 | 0.708054E+10 | 0.00 | 1.10 |
May | 0.143976E+10 | 0.00 | 0.00 | 27780952.17 | 0.00 | 0.00 | 0.147187E+11 | 0.00 | 2.63 |
June | 0.175750E+10 | 670743.04 | 0.00 | 26027115.04 | 0.00 | 0.00 | 0.114408E+11 | 0.00 | 3.15 |
July | 0.240502E+10 | 17214455.21 | 0.00 | 27712508.41 | 2196149.26 | 0.00 | 0.877646E+10 | 0.00 | 3.00 |
August | 0.257673E+10 | 0.00 | 0.00 | 20024044.49 | 0.00 | 0.00 | 0.106030E+11 | 0.00 | 2.61 |
September | 0.232059E+10 | 0.00 | 0.00 | 11078292.25 | 0.00 | 0.00 | 0.706277E+10 | 0.00 | 1.18 |
October | 0.383515E+10 | 0.00 | 0.00 | 2664397.00 | 0.00 | 0.371824E+09 | 0.197689E+10 | 0.00 | 0.58 |
November | 0.217330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398067E+10 | 0.00 | 0.00 | 0.47 |
December | 0.833007E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.617475E+10 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.283062E+11 | 17885198.25 | 0.00 | 0.130769E+09 | 2196149.26 | 0.188021E+11 | 0.638994E+11 | 0.00 | 1.40 |
Minimum of Months | 0.833007E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.383515E+10 | 17214455.21 | 0.00 | 27780952.17 | 2196149.26 | 0.617475E+10 | 0.147187E+11 | 0.00 | 3.15 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.217963E+10 | 0.00 | 0.00 | 85215.60 | 0.00 | 0.729866E+10 | 0.132663E+09 | 0.00 | 0.49 |
February | 0.416253E+10 | 0.00 | 0.00 | 2321547.83 | 0.00 | 0.312823E+10 | 0.157644E+10 | 0.00 | 0.51 |
March | 0.483435E+10 | 0.00 | 0.00 | 13805546.06 | 0.00 | 0.108507E+10 | 0.770268E+10 | 0.00 | 0.70 |
April | 0.415126E+10 | 0.00 | 0.00 | 27216208.00 | 0.00 | 48015706.61 | 0.166690E+11 | 0.00 | 1.58 |
May | 0.306412E+10 | 0.00 | 0.00 | 34092404.93 | 0.00 | 0.00 | 0.179944E+11 | 0.00 | 2.45 |
June | 0.293508E+10 | 1343779.24 | 0.00 | 33329414.91 | 0.00 | 0.00 | 0.132759E+11 | 0.00 | 2.85 |
July | 0.400820E+10 | 40785391.18 | 0.00 | 36967095.99 | 1587132.90 | 0.00 | 0.970999E+10 | 0.00 | 2.69 |
August | 0.393918E+10 | 0.00 | 0.00 | 35082898.05 | 0.00 | 0.00 | 0.153157E+11 | 0.00 | 2.81 |
September | 0.421687E+10 | 0.00 | 0.00 | 17589110.80 | 0.00 | 0.00 | 0.124809E+11 | 0.00 | 1.46 |
October | 0.562292E+10 | 0.00 | 0.00 | 6291579.87 | 0.00 | 0.481125E+09 | 0.475302E+10 | 0.00 | 0.66 |
November | 0.411310E+10 | 0.00 | 0.00 | 539179.99 | 0.00 | 0.496284E+10 | 0.399062E+09 | 0.00 | 0.47 |
December | 0.194750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.872013E+10 | 0.00 | 0.00 | 0.46 |
Annual Sum or Average | 0.451747E+11 | 42129170.42 | 0.00 | 0.207320E+09 | 1587132.90 | 0.257241E+11 | 0.100010E+12 | 0.00 | 1.43 |
Minimum of Months | 0.194750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.562292E+10 | 40785391.18 | 0.00 | 36967095.99 | 1587132.90 | 0.872013E+10 | 0.179944E+11 | 0.00 | 2.85 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.358789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370164E+10 | 0.00 | 0.00 | 0.58 |
February | 0.526012E+10 | 0.00 | 0.00 | 65959.43 | 0.00 | 0.873712E+09 | 0.109765E+09 | 0.00 | 0.56 |
March | 0.443305E+10 | 0.00 | 0.00 | 3641619.81 | 0.00 | 82929243.68 | 0.300274E+10 | 0.00 | 0.62 |
April | 0.194299E+10 | 0.00 | 0.00 | 19466674.61 | 0.00 | 0.00 | 0.116134E+11 | 0.00 | 1.58 |
May | 0.206003E+10 | 0.00 | 0.00 | 19128224.48 | 0.00 | 0.00 | 0.100145E+11 | 0.00 | 2.14 |
June | 0.203050E+10 | 472974.90 | 0.00 | 24752519.70 | 0.00 | 0.00 | 0.893971E+10 | 0.00 | 3.02 |
July | 0.257758E+10 | 32464403.92 | 0.00 | 24212355.53 | 960537.01 | 0.00 | 0.725785E+10 | 0.00 | 2.87 |
August | 0.242742E+10 | 0.00 | 0.00 | 24976930.78 | 0.00 | 0.00 | 0.106629E+11 | 0.00 | 2.92 |
September | 0.359355E+10 | 0.00 | 0.00 | 6368973.08 | 0.00 | 0.00 | 0.545953E+10 | 0.00 | 1.20 |
October | 0.482356E+10 | 0.00 | 0.00 | 1760054.13 | 0.00 | 6893668.22 | 0.192287E+10 | 0.00 | 0.64 |
November | 0.686221E+10 | 0.00 | 0.00 | 25676.00 | 0.00 | 0.215821E+09 | 27949665.52 | 0.00 | 0.54 |
December | 0.799790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91501167.29 | 0.00 | 0.00 | 0.54 |
Annual Sum or Average | 0.475968E+11 | 32937378.83 | 0.00 | 0.124399E+09 | 960537.01 | 0.497249E+10 | 0.590112E+11 | 0.00 | 1.44 |
Minimum of Months | 0.194299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
Maximum of Months | 0.799790E+10 | 32464403.92 | 0.00 | 24976930.78 | 960537.01 | 0.370164E+10 | 0.116134E+11 | 0.00 | 3.02 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.570869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555450E+11 | 0.00 | 0.00 | 0.30 |
February | 0.390409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430148E+11 | 0.00 | 0.00 | 0.30 |
March | 0.168790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276517E+11 | 0.00 | 0.00 | 0.29 |
April | 0.287259E+11 | 0.00 | 0.00 | 10839364.09 | 0.00 | 0.502616E+10 | 0.103718E+11 | 0.00 | 0.34 |
May | 0.122466E+11 | 0.00 | 0.00 | 86825667.78 | 0.00 | 0.00 | 0.589342E+11 | 0.00 | 0.83 |
June | 0.444825E+10 | 356122.87 | 0.00 | 0.192771E+09 | 0.00 | 0.00 | 0.774793E+11 | 0.00 | 1.42 |
July | 0.599820E+10 | 0.212893E+09 | 0.00 | 0.151863E+09 | 27685877.03 | 0.00 | 0.548044E+11 | 0.00 | 1.22 |
August | 0.112743E+11 | 0.00 | 0.00 | 87333824.34 | 0.00 | 0.00 | 0.474098E+11 | 0.00 | 0.89 |
September | 0.304682E+11 | 0.00 | 0.00 | 11434444.20 | 0.00 | 0.130108E+10 | 0.110010E+11 | 0.00 | 0.38 |
October | 0.196006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177610E+11 | 0.00 | 0.00 | 0.28 |
November | 0.102567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.511686E+11 | 0.00 | 0.00 | 0.29 |
December | 0.659202E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.632468E+11 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.135801E+12 | 0.213249E+09 | 0.00 | 0.541068E+09 | 27685877.03 | 0.264715E+12 | 0.260000E+12 | 0.00 | 0.57 |
Minimum of Months | 0.570869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.304682E+11 | 0.212893E+09 | 0.00 | 0.192771E+09 | 27685877.03 | 0.632468E+11 | 0.774793E+11 | 0.00 | 1.42 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.950018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639857E+11 | 0.00 | 0.00 | 0.57 |
February | 0.111380E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454209E+11 | 0.00 | 0.00 | 0.58 |
March | 0.307208E+11 | 0.00 | 0.00 | 19891117.24 | 0.00 | 0.199863E+11 | 0.920876E+10 | 0.00 | 0.62 |
April | 0.268498E+11 | 0.00 | 0.00 | 67230952.82 | 0.00 | 0.364312E+10 | 0.437698E+11 | 0.00 | 0.88 |
May | 0.155981E+11 | 0.00 | 0.00 | 0.205311E+09 | 0.00 | 0.00 | 0.111389E+12 | 0.00 | 2.16 |
June | 0.854430E+10 | 414262.74 | 0.00 | 0.198299E+09 | 0.00 | 0.00 | 0.945987E+11 | 0.00 | 2.60 |
July | 0.973380E+10 | 0.182486E+09 | 0.00 | 0.211270E+09 | 36468143.39 | 0.00 | 0.716283E+11 | 0.00 | 2.44 |
August | 0.145298E+11 | 0.00 | 0.00 | 0.129233E+09 | 0.00 | 0.00 | 0.754189E+11 | 0.00 | 1.90 |
September | 0.352492E+11 | 0.00 | 0.00 | 38131640.16 | 0.00 | 0.162494E+10 | 0.262311E+11 | 0.00 | 0.85 |
October | 0.290150E+11 | 0.00 | 0.00 | 4143883.27 | 0.00 | 0.183422E+11 | 0.286709E+10 | 0.00 | 0.58 |
November | 0.147120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.620889E+11 | 0.00 | 0.00 | 0.57 |
December | 0.101186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.748414E+11 | 0.00 | 0.00 | 0.57 |
Annual Sum or Average | 0.184812E+12 | 0.182901E+09 | 0.00 | 0.873511E+09 | 36468143.39 | 0.289934E+12 | 0.435112E+12 | 0.00 | 1.20 |
Minimum of Months | 0.950018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.352492E+11 | 0.182486E+09 | 0.00 | 0.211270E+09 | 36468143.39 | 0.748414E+11 | 0.111389E+12 | 0.00 | 2.60 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.878812E+10 | 0.00 | 0.00 | 23403.64 | 0.00 | 0.889569E+11 | 84692712.12 | 0.00 | 0.56 |
February | 0.295972E+11 | 0.00 | 0.00 | 16070232.80 | 0.00 | 0.493114E+11 | 0.983599E+10 | 0.00 | 0.59 |
March | 0.386854E+11 | 0.00 | 0.00 | 0.130504E+09 | 0.00 | 0.234129E+11 | 0.630987E+11 | 0.00 | 0.81 |
April | 0.320188E+11 | 0.00 | 0.00 | 0.238639E+09 | 0.00 | 0.357196E+10 | 0.140655E+12 | 0.00 | 1.43 |
May | 0.323800E+11 | 0.00 | 0.00 | 0.278168E+09 | 0.00 | 0.00 | 0.142210E+12 | 0.00 | 2.15 |
June | 0.218556E+11 | 941286.68 | 0.00 | 0.261232E+09 | 0.00 | 0.00 | 0.102958E+12 | 0.00 | 2.37 |
July | 0.244332E+11 | 0.503300E+09 | 0.00 | 0.287239E+09 | 31418878.83 | 0.00 | 0.703279E+11 | 0.00 | 2.17 |
August | 0.269356E+11 | 0.00 | 0.00 | 0.269858E+09 | 0.00 | 0.00 | 0.112338E+12 | 0.00 | 2.23 |
September | 0.437509E+11 | 0.00 | 0.00 | 0.123272E+09 | 0.00 | 0.149679E+10 | 0.837958E+11 | 0.00 | 1.20 |
October | 0.439037E+11 | 0.00 | 0.00 | 38325270.24 | 0.00 | 0.188001E+11 | 0.261829E+11 | 0.00 | 0.65 |
November | 0.190618E+11 | 0.00 | 0.00 | 2624630.99 | 0.00 | 0.756996E+11 | 0.146697E+10 | 0.00 | 0.56 |
December | 0.297618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111385E+12 | 0.00 | 0.00 | 0.55 |
Annual Sum or Average | 0.324387E+12 | 0.504241E+09 | 0.00 | 0.164596E+10 | 31418878.83 | 0.372635E+12 | 0.752954E+12 | 0.00 | 1.28 |
Minimum of Months | 0.297618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 0.439037E+11 | 0.503300E+09 | 0.00 | 0.287239E+09 | 31418878.83 | 0.111385E+12 | 0.142210E+12 | 0.00 | 2.37 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.131670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645568E+11 | 0.00 | 0.00 | 0.58 |
February | 0.107828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465791E+11 | 0.00 | 0.00 | 0.59 |
March | 0.307755E+11 | 0.00 | 0.00 | 5733610.54 | 0.00 | 0.243459E+11 | 0.386433E+10 | 0.00 | 0.60 |
April | 0.317019E+11 | 0.00 | 0.00 | 67495127.71 | 0.00 | 0.230659E+10 | 0.461326E+11 | 0.00 | 1.01 |
May | 0.224443E+11 | 0.00 | 0.00 | 0.132939E+09 | 0.00 | 0.00 | 0.644758E+11 | 0.00 | 1.64 |
June | 0.103290E+11 | 253918.19 | 0.00 | 0.173097E+09 | 0.00 | 0.00 | 0.617826E+11 | 0.00 | 2.22 |
July | 0.122333E+11 | 0.327202E+09 | 0.00 | 0.129786E+09 | 29034445.13 | 0.00 | 0.411018E+11 | 0.00 | 1.86 |
August | 0.190970E+11 | 0.00 | 0.00 | 0.109929E+09 | 0.00 | 0.00 | 0.475600E+11 | 0.00 | 1.67 |
September | 0.425424E+11 | 0.00 | 0.00 | 20864184.56 | 0.00 | 0.132434E+10 | 0.173922E+11 | 0.00 | 0.85 |
October | 0.316849E+11 | 0.00 | 0.00 | 632144.97 | 0.00 | 0.181437E+11 | 0.764142E+09 | 0.00 | 0.58 |
November | 0.520568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.592773E+11 | 0.00 | 0.00 | 0.58 |
December | 0.228822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.747019E+11 | 0.00 | 0.00 | 0.58 |
Annual Sum or Average | 0.220402E+12 | 0.327456E+09 | 0.00 | 0.640475E+09 | 29034445.13 | 0.291236E+12 | 0.283074E+12 | 0.00 | 1.07 |
Minimum of Months | 0.131670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.425424E+11 | 0.327202E+09 | 0.00 | 0.173097E+09 | 29034445.13 | 0.747019E+11 | 0.644758E+11 | 0.00 | 2.22 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 25643685.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.584962E+10 | 0.00 | 0.00 | 0.34 |
February | 71431489.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436240E+10 | 0.00 | 0.00 | 0.32 |
March | 0.576670E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339422E+10 | 0.00 | 0.00 | 0.31 |
April | 0.257951E+10 | 0.00 | 0.00 | 402627.43 | 0.00 | 0.902161E+09 | 0.433003E+09 | 0.00 | 0.34 |
May | 0.162583E+10 | 0.00 | 0.00 | 6375836.92 | 0.00 | 16139523.64 | 0.458418E+10 | 0.00 | 0.74 |
June | 0.495985E+09 | 2492681.04 | 0.00 | 17542891.71 | 0.00 | 0.00 | 0.733945E+10 | 0.00 | 1.39 |
July | 0.710949E+09 | 19312043.53 | 0.00 | 13809436.48 | 2420086.15 | 0.00 | 0.500679E+10 | 0.00 | 1.20 |
August | 0.143245E+10 | 0.00 | 0.00 | 7244566.47 | 0.00 | 31431870.88 | 0.382031E+10 | 0.00 | 0.84 |
September | 0.277543E+10 | 0.00 | 0.00 | 242102.97 | 0.00 | 0.637328E+09 | 0.335476E+09 | 0.00 | 0.36 |
October | 0.887649E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219599E+10 | 0.00 | 0.00 | 0.29 |
November | 19919692.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535455E+10 | 0.00 | 0.00 | 0.33 |
December | 31522904.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.699653E+10 | 0.00 | 0.00 | 0.36 |
Annual Sum or Average | 0.112330E+11 | 21804724.57 | 0.00 | 45617461.99 | 2420086.15 | 0.297404E+11 | 0.215192E+11 | 0.00 | 0.57 |
Minimum of Months | 19919692.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.277543E+10 | 19312043.53 | 0.00 | 17542891.71 | 2420086.15 | 0.699653E+10 | 0.733945E+10 | 0.00 | 1.39 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 33885901.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516793E+10 | 0.00 | 0.00 | 0.52 |
February | 0.334437E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396546E+10 | 0.00 | 0.00 | 0.53 |
March | 0.209966E+10 | 0.00 | 0.00 | 820200.33 | 0.00 | 0.205157E+10 | 0.345057E+09 | 0.00 | 0.57 |
April | 0.219410E+10 | 0.00 | 0.00 | 4738766.63 | 0.00 | 0.604229E+09 | 0.316168E+10 | 0.00 | 0.79 |
May | 0.143704E+10 | 0.00 | 0.00 | 19492403.24 | 0.00 | 2875577.86 | 0.101811E+11 | 0.00 | 2.03 |
June | 0.820948E+09 | 1343237.32 | 0.00 | 19302767.75 | 0.00 | 0.00 | 0.936452E+10 | 0.00 | 2.59 |
July | 0.100762E+10 | 16049430.61 | 0.00 | 20433843.88 | 2999856.52 | 0.00 | 0.699950E+10 | 0.00 | 2.46 |
August | 0.137291E+10 | 0.00 | 0.00 | 12082739.55 | 0.00 | 24281432.20 | 0.690112E+10 | 0.00 | 1.84 |
September | 0.330221E+10 | 0.00 | 0.00 | 2402360.27 | 0.00 | 0.447074E+09 | 0.143624E+10 | 0.00 | 0.78 |
October | 0.164903E+10 | 0.00 | 0.00 | 122875.87 | 0.00 | 0.203766E+10 | 73201497.19 | 0.00 | 0.55 |
November | 27028777.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502443E+10 | 0.00 | 0.00 | 0.52 |
December | 40732835.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.614299E+10 | 0.00 | 0.00 | 0.51 |
Annual Sum or Average | 0.143196E+11 | 17392667.93 | 0.00 | 79395957.52 | 2999856.52 | 0.254685E+11 | 0.384624E+11 | 0.00 | 1.15 |
Minimum of Months | 27028777.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.330221E+10 | 16049430.61 | 0.00 | 20433843.88 | 2999856.52 | 0.614299E+10 | 0.101811E+11 | 0.00 | 2.59 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.435812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.760648E+10 | 0.00 | 0.00 | 0.52 |
February | 0.149688E+10 | 0.00 | 0.00 | 758567.76 | 0.00 | 0.480446E+10 | 0.441236E+09 | 0.00 | 0.54 |
March | 0.249361E+10 | 0.00 | 0.00 | 8463998.63 | 0.00 | 0.258368E+10 | 0.418707E+10 | 0.00 | 0.74 |
April | 0.234020E+10 | 0.00 | 0.00 | 19055880.31 | 0.00 | 0.774863E+09 | 0.121008E+11 | 0.00 | 1.31 |
May | 0.310314E+10 | 0.00 | 0.00 | 26573203.59 | 0.00 | 32965638.67 | 0.135547E+11 | 0.00 | 2.05 |
June | 0.221576E+10 | 2388854.32 | 0.00 | 25384340.34 | 0.00 | 0.00 | 0.104865E+11 | 0.00 | 2.38 |
July | 0.258758E+10 | 43046382.79 | 0.00 | 26820229.85 | 2084623.03 | 0.00 | 0.708763E+10 | 0.00 | 2.22 |
August | 0.280720E+10 | 0.00 | 0.00 | 24842425.04 | 0.00 | 37425365.63 | 0.106207E+11 | 0.00 | 2.19 |
September | 0.377037E+10 | 0.00 | 0.00 | 9228364.62 | 0.00 | 0.544886E+09 | 0.655595E+10 | 0.00 | 1.09 |
October | 0.245214E+10 | 0.00 | 0.00 | 2497963.54 | 0.00 | 0.248740E+10 | 0.169818E+10 | 0.00 | 0.61 |
November | 0.673516E+09 | 0.00 | 0.00 | 138939.85 | 0.00 | 0.709027E+10 | 61313946.01 | 0.00 | 0.52 |
December | 62993855.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.952376E+10 | 0.00 | 0.00 | 0.51 |
Annual Sum or Average | 0.244392E+11 | 45435237.11 | 0.00 | 0.143764E+09 | 2084623.03 | 0.354862E+11 | 0.667941E+11 | 0.00 | 1.23 |
Minimum of Months | 62993855.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.377037E+10 | 43046382.79 | 0.00 | 26820229.85 | 2084623.03 | 0.952376E+10 | 0.135547E+11 | 0.00 | 2.38 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 36389088.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.535637E+10 | 0.00 | 0.00 | 0.54 |
February | 0.409453E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403839E+10 | 0.00 | 0.00 | 0.55 |
March | 0.184547E+10 | 0.00 | 0.00 | 312903.12 | 0.00 | 0.257124E+10 | 0.218454E+09 | 0.00 | 0.59 |
April | 0.262460E+10 | 0.00 | 0.00 | 5376662.64 | 0.00 | 0.553616E+09 | 0.384539E+10 | 0.00 | 0.96 |
May | 0.249249E+10 | 0.00 | 0.00 | 12112744.33 | 0.00 | 18689608.06 | 0.573475E+10 | 0.00 | 1.57 |
June | 0.122779E+10 | 3891546.19 | 0.00 | 16840693.11 | 0.00 | 0.00 | 0.603327E+10 | 0.00 | 2.22 |
July | 0.150231E+10 | 29781031.87 | 0.00 | 12394957.38 | 2198260.38 | 0.00 | 0.380130E+10 | 0.00 | 1.90 |
August | 0.220313E+10 | 0.00 | 0.00 | 9754986.90 | 0.00 | 22470273.09 | 0.413022E+10 | 0.00 | 1.65 |
September | 0.365399E+10 | 0.00 | 0.00 | 1445943.85 | 0.00 | 0.434429E+09 | 0.124104E+10 | 0.00 | 0.82 |
October | 0.172697E+10 | 0.00 | 0.00 | 17016.38 | 0.00 | 0.216960E+10 | 27208132.49 | 0.00 | 0.58 |
November | 66647564.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516280E+10 | 0.00 | 0.00 | 0.54 |
December | 51256491.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.634636E+10 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.178405E+11 | 33672578.06 | 0.00 | 58255907.73 | 2198260.38 | 0.266740E+11 | 0.250316E+11 | 0.00 | 1.04 |
Minimum of Months | 36389088.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.365399E+10 | 29781031.87 | 0.00 | 16840693.11 | 2198260.38 | 0.634636E+10 | 0.603327E+10 | 0.00 | 2.22 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 13800205.94 | 0.00 | 0.00 | 1771711.02 | 0.00 | 0.00 | 0.117293E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 6932140.27 | 0.00 | 0.00 | 0.973116E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 16232372.76 | 0.00 | 0.00 | 0.102314E+10 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 19450082.91 | 0.00 | 0.00 | 0.635156E+09 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 4270836.34 | 0.00 | 0.00 | 0.454630E+09 | 0.00 | 0.30 |
June | 0.00 | 1694451.26 | 0.00 | 8348199.85 | 0.00 | 0.00 | 0.248640E+09 | 0.00 | 0.30 |
July | 0.00 | 2634675.50 | 0.00 | 11214308.36 | 0.00 | 0.00 | 0.121287E+09 | 0.00 | 0.28 |
August | 0.00 | 16445.12 | 0.00 | 18357045.18 | 0.00 | 0.00 | 0.256733E+09 | 0.00 | 0.30 |
September | 0.00 | 0.00 | 0.00 | 4055957.88 | 0.00 | 0.00 | 0.539424E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 8284662.26 | 0.00 | 0.00 | 0.804376E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 11839382.99 | 0.00 | 0.00 | 0.112629E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 16410472.45 | 0.00 | 0.00 | 0.120908E+10 | 0.00 | 0.28 |
Annual Sum or Average | 13800205.94 | 4345571.88 | 0.00 | 0.127167E+09 | 0.00 | 0.00 | 0.856480E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1771711.02 | 0.00 | 0.00 | 0.121287E+09 | 0.00 | 0.28 |
Maximum of Months | 13800205.94 | 2634675.50 | 0.00 | 19450082.91 | 0.00 | 0.00 | 0.120908E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.877507E+10 | 0.00 | 0.00 | 1765234.28 | 0.00 | 0.00 | 0.282143E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 49149497.08 | 0.00 | 0.00 | 0.975038E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.135696E+09 | 0.00 | 0.00 | 0.102582E+11 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 0.176097E+09 | 0.00 | 0.00 | 0.637040E+10 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 35854133.89 | 0.00 | 0.00 | 0.455319E+10 | 0.00 | 0.30 |
June | 0.00 | 16496964.73 | 0.00 | 77238557.55 | 0.00 | 0.00 | 0.249643E+10 | 0.00 | 0.30 |
July | 0.00 | 25914792.23 | 0.00 | 0.105064E+09 | 0.00 | 0.00 | 0.122542E+10 | 0.00 | 0.28 |
August | 0.00 | 158455.20 | 0.00 | 0.171263E+09 | 0.00 | 0.00 | 0.258196E+10 | 0.00 | 0.30 |
September | 0.00 | 0.00 | 0.00 | 28330371.44 | 0.00 | 0.00 | 0.541521E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 62471576.10 | 0.00 | 0.00 | 0.806339E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 93130734.42 | 0.00 | 0.00 | 0.112882E+11 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.135057E+09 | 0.00 | 0.00 | 0.121201E+11 | 0.00 | 0.28 |
Annual Sum or Average | 0.877507E+10 | 42570212.16 | 0.00 | 0.107112E+10 | 0.00 | 0.00 | 0.769443E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1765234.28 | 0.00 | 0.00 | 0.122542E+10 | 0.00 | 0.28 |
Maximum of Months | 0.877507E+10 | 25914792.23 | 0.00 | 0.176097E+09 | 0.00 | 0.00 | 0.121201E+11 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.111207E+10 | 0.00 | 0.00 | 2587.58 | 0.00 | 0.00 | 13940610.14 | 0.00 | 0.28 |
February | 6153836.05 | 0.00 | 0.00 | 3716842.19 | 0.00 | 0.00 | 0.969805E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 11835352.67 | 0.00 | 0.00 | 0.102755E+10 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 16580897.42 | 0.00 | 0.00 | 0.638058E+09 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 3285188.49 | 0.00 | 0.00 | 0.455627E+09 | 0.00 | 0.30 |
June | 0.00 | 1654715.04 | 0.00 | 7668130.08 | 0.00 | 0.00 | 0.249816E+09 | 0.00 | 0.30 |
July | 0.00 | 2592813.74 | 0.00 | 10446458.83 | 0.00 | 0.00 | 0.122722E+09 | 0.00 | 0.28 |
August | 0.00 | 15786.79 | 0.00 | 16889045.74 | 0.00 | 0.00 | 0.258598E+09 | 0.00 | 0.30 |
September | 50115188.80 | 0.00 | 0.00 | 1916347.53 | 0.00 | 0.00 | 0.492490E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 4811652.87 | 0.00 | 0.00 | 0.807804E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 8021552.23 | 0.00 | 0.00 | 0.113011E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 12314372.20 | 0.00 | 0.00 | 0.121319E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.116834E+10 | 4263315.56 | 0.00 | 97488427.84 | 0.00 | 0.00 | 0.737972E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2587.58 | 0.00 | 0.00 | 13940610.14 | 0.00 | 0.28 |
Maximum of Months | 0.111207E+10 | 2592813.74 | 0.00 | 16889045.74 | 0.00 | 0.00 | 0.121319E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.764056E+09 | 0.00 | 0.00 | 0.458582E+12 | 0.00 | 4.88 |
February | 0.00 | 0.00 | 0.00 | 0.133555E+10 | 0.00 | 0.00 | 0.712567E+12 | 0.00 | 8.85 |
March | 0.00 | 0.00 | 0.00 | 0.207215E+10 | 0.00 | 0.00 | 0.108863E+13 | 0.00 | 14.25 |
April | 0.00 | 0.00 | 0.00 | 0.282671E+10 | 0.00 | 0.00 | 0.129296E+13 | 0.00 | 27.23 |
May | 0.00 | 0.00 | 0.00 | 0.749906E+09 | 0.00 | 0.00 | 0.535362E+12 | 0.00 | 14.67 |
June | 0.00 | 81324787.84 | 0.00 | 0.157635E+10 | 0.00 | 0.00 | 0.641936E+12 | 0.00 | 34.35 |
July | 0.00 | 0.585170E+09 | 0.00 | 0.264129E+10 | 0.00 | 0.00 | 0.669339E+12 | 0.00 | 42.54 |
August | 0.00 | 0.00 | 0.00 | 0.328029E+10 | 0.00 | 0.00 | 0.912002E+12 | 0.00 | 44.36 |
September | 0.00 | 0.00 | 0.00 | 0.626077E+09 | 0.00 | 0.00 | 0.440133E+12 | 0.00 | 11.41 |
October | 0.00 | 0.00 | 0.00 | 0.124469E+10 | 0.00 | 0.00 | 0.807123E+12 | 0.00 | 13.00 |
November | 0.00 | 0.00 | 0.00 | 0.214458E+10 | 0.00 | 0.00 | 0.105259E+13 | 0.00 | 11.68 |
December | 0.00 | 0.00 | 0.00 | 0.318737E+10 | 0.00 | 0.00 | 0.133146E+13 | 0.00 | 14.70 |
Annual Sum or Average | 0.00 | 0.666494E+09 | 0.00 | 0.224490E+11 | 0.00 | 0.00 | 0.994269E+13 | 0.00 | 20.24 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.626077E+09 | 0.00 | 0.00 | 0.440133E+12 | 0.00 | 4.88 |
Maximum of Months | 0.00 | 0.585170E+09 | 0.00 | 0.328029E+10 | 0.00 | 0.00 | 0.133146E+13 | 0.00 | 44.36 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | -0.344352E+11 | 0.113616E+11 | 0.00 | 0.250992E+13 | 0.271876E+12 |
February | 0.586933E+11 | 0.930476E+10 | 0.00 | 0.264311E+13 | 0.255427E+12 |
March | 0.348295E+12 | 0.141736E+11 | 0.00 | 0.346342E+13 | 0.296598E+12 |
April | 0.632943E+12 | 0.156249E+11 | 0.00 | 0.370904E+13 | 0.327262E+12 |
May | 0.788793E+12 | 0.930854E+10 | 0.00 | 0.320406E+13 | 0.267911E+12 |
June | 0.817239E+12 | 0.516583E+10 | 0.00 | 0.283708E+13 | 0.925187E+12 |
July | 0.741792E+12 | 0.416519E+10 | 0.00 | 0.294031E+13 | 0.143160E+13 |
August | 0.555137E+12 | 0.486951E+10 | 0.00 | 0.334819E+13 | 0.115415E+13 |
September | 0.257218E+12 | 0.570565E+10 | 0.00 | 0.289387E+13 | 0.999123E+11 |
October | 0.107731E+12 | 0.123330E+11 | 0.00 | 0.311753E+13 | 0.203986E+12 |
November | -0.665301E+10 | 0.439224E+10 | 0.00 | 0.326671E+13 | 0.374340E+12 |
December | -0.518268E+11 | 0.829202E+10 | 0.00 | 0.350747E+13 | 0.501542E+12 |
Annual Sum or Average | 0.421493E+13 | 0.104697E+12 | 0.00 | 0.374407E+14 | 0.610979E+13 |
Minimum of Months | -0.518268E+11 | 0.416519E+10 | 0.00 | 0.250992E+13 | 0.999123E+11 |
Maximum of Months | 0.817239E+12 | 0.156249E+11 | 0.00 | 0.370904E+13 | 0.143160E+13 |