Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:25
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2024-07-03 12:25:51
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:51
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 30386.40 | 656.00 | 656.00 |
Net Site Energy | 30386.40 | 656.00 | 656.00 |
Total Source Energy | 90904.47 | 1962.52 | 1962.52 |
Net Source Energy | 90904.47 | 1962.52 | 1962.52 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 2558.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1535.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3221.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 353.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2566.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2534.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 364.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 528.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3712.47 |
Humidification | 1517.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 564.62 |
Heat Recovery | 44.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 484.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 27827.95 | 2558.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6557.26 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 2558.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1535.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3221.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 353.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 55.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2505.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2534.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 364.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 528.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3712.47 |
Humidification | General | 1517.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 564.62 |
Heat Recovery | General | 44.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 484.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 2558.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1535.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3221.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 353.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 2566.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2534.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 364.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 528.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3712.47 |
Humidification | Unassigned | 1517.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 564.62 |
Heat Recovery | Unassigned | 44.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 484.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 77.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 150.38 | 55.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Other | 373.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 600.77 | 55.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 77.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 150.38 | 55.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Other | 373.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 600.77 | 55.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 27827.950 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 27827.950 | 100.00 |
Total On-Site and Utility Electric Sources | 27827.950 | 100.00 |
Total Electricity End Uses | 27827.950 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 203.05 | 8.59 |
Air to Air Heat Recovery for Heating | 2161.83 | 91.41 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 2364.88 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 6557.26 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 6557.26 | 100.00 |
Total Water End Uses | 6557.26 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 162.67 |
Time Setpoint Not Met During Occupied Cooling | 1041.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:51
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:25 |
RunPeriod | RUNPERIOD 1 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 8.6849 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 8.6849 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 8.7339 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 8.7339 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.6849 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 8.6849 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 8.6849 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 8.6849 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 8.6849 | 18.58 | 484.4232 | |
Total | 46320.38 | 8.7339 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 8.7339 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.6845 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:51
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 04-AUG-07:19 | 30-JAN-07:30 | - | - | - | - | - | - | - | - | - | - | 01-SEP-15:50 |
Heating | 0.00 | 2470555.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 655208.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 280450.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 233414.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 151802.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 56095.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 92515.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 28106.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2275966.21 | 2470555.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 2470555.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 655208.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 280450.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3430.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 151802.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 56095.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 92515.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 28106.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:51
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 2773.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4861.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 10201.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1120.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8128.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8028.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1155.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1672.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 4806.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 141.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1534.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 88131.12 | 2773.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 59.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 104.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 220.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 24.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 173.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 24.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 36.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 103.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 3.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 33.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1902.64 | 59.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 59.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 104.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 220.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 24.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 173.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 24.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 36.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 103.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 3.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 33.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1902.64 | 59.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:51
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 5.81 | 0.364223 | 0.000000 | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 6.13 | 0.310330 | 0.321000 | 1.97 | 0.827548 | 0.500000 | 0.001228 | 0.000227 | 1.97 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 57.69 | 0.329708 | 0.335000 | 19.33 | 0.879221 | 0.500000 | 0.001156 | 0.004487 | 19.33 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.75 | 0.330842 | 0.344000 | 1.98 | 0.882244 | 0.500000 | 0.001152 | 0.000948 | 3.39 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.03 | 0.232561 | 0.240000 | 0.246460 | 0.620162 | 0.500000 | 0.001638 | 0.000177 | 0.632982 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.45 | 0.105829 | 0.200000 | 0.290856 | 0.300000 | 0.500000 | 0.003600 | 0.000119 | 0.426058 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.62 | 0.147436 | 0.200000 | 0.323971 | 0.393164 | 0.500000 | 0.002584 | 0.000189 | 0.675289 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.74 | 0.088286 | 0.200000 | 0.348651 | 0.300000 | 0.500000 | 0.004316 | 0.000100 | 0.356323 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 9.63 | 0.247980 | 0.252000 | 2.43 | 0.661279 | 0.500000 | 0.001536 | 0.002538 | 9.08 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 15.48 | 0.099446 | 0.200000 | 3.10 | 0.300000 | 0.500000 | 0.003831 | 0.001658 | 5.93 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 16.21 | 0.147341 | 0.200000 | 3.24 | 0.392908 | 0.500000 | 0.002586 | 0.002498 | 8.93 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 16.27 | 0.094571 | 0.200000 | 3.25 | 0.300000 | 0.500000 | 0.004029 | 0.001631 | 5.83 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.16 | 0.206542 | 0.228000 | 0.263632 | 0.550779 | 0.500000 | 0.001845 | 0.000323 | 1.16 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.56 | 0.098851 | 0.200000 | 0.311388 | 0.300000 | 0.500000 | 0.003854 | 0.000210 | 0.752957 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.74 | 0.137423 | 0.200000 | 0.347578 | 0.366461 | 0.500000 | 0.002772 | 0.000319 | 1.14 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.71 | 0.090101 | 0.200000 | 0.341628 | 0.300000 | 0.500000 | 0.004229 | 0.000210 | 0.751530 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | User-Specified Rated Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 25967.85 | 0.000227 | 543.55 | |
CORE_MID VAV BOX REHEAT COIL | 512857.57 | 0.004487 | 12560.25 | |
CORE_TOP VAV BOX REHEAT COIL | 108398.79 | 0.000948 | 2860.62 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 20244.82 | 0.000177 | 533.95 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 13625.45 | 0.000119 | 359.35 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 21595.45 | 0.000189 | 569.54 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 11399.82 | 0.000100 | 300.71 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 290057.07 | 0.002538 | 7647.63 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 189495.39 | 0.001658 | 4996.17 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 285531.69 | 0.002498 | 7528.39 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 186444.55 | 0.001631 | 4915.77 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 36943.35 | 0.000323 | 973.91 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 24056.73 | 0.000210 | 634.18 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 36450.77 | 0.000319 | 960.93 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 24011.03 | 0.000210 | 632.98 | |
VAV_BOT WITH REHEAT HEATING COIL | 109767.78 | 0.000960 | 1657.37 | |
VAV_MID WITH REHEAT HEATING COIL | 1118393.64 | 0.009784 | 16518.76 | |
VAV_TOP WITH REHEAT HEATING COIL | 112315.04 | 0.000983 | 1693.43 | |
CAV_BAS HEATING COIL | 304738.27 | 0.000875 | 2622.25 | 100000.00 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.525262 |
DATACENTER_MID_ZN_6 DIRECT AIR | 5.05 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.513274 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 25.73 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.99 | 3.18 | 11.97 | 3.18 | 10.27 | 10.27 | 0.300000 | 0.309315 | 10.27 |
VAV_MID WITH REHEAT | 57.64 | 31.34 | 115.28 | 44.28 | 96.22 | 96.22 | 0.300000 | 0.460167 | 96.22 |
VAV_TOP WITH REHEAT | 5.95 | 3.24 | 11.91 | 7.19 | 10.45 | 10.45 | 0.300000 | 0.687419 | 10.45 |
CAV_BAS | 0.000000 | 0.000000 | 5.81 | 1.20 | 5.81 | 5.81 | 1.00 | 0.206393 | 5.81 |
AIRLOOP DATACENTER BASEMENT | 25.73 | 25.73 | 25.73 | 25.73 | 25.73 | 25.73 | 1.00 | 0.999994 | 25.73 |
AIRLOOP DATACENTER BOT | 0.525262 | 0.525262 | 0.525262 | 0.525262 | 0.525262 | 0.525262 | 1.00 | 1.00 | 0.525262 |
AIRLOOP DATACENTER MID | 5.05 | 5.05 | 5.05 | 5.05 | 5.05 | 5.05 | 1.00 | 1.00 | 5.05 |
AIRLOOP DATACENTER TOP | 0.513274 | 0.513274 | 0.513274 | 0.513274 | 0.513274 | 0.513274 | 1.00 | 1.00 | 0.513274 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 10.27 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 96.22 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 10.45 | |
CAV_BAS_OA_CONTROLLER | 5.81 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 25.73 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.525262 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 5.05 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.513274 | 0.015632 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT OA HEAT RECOVERY | 2.54 |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 25.38 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.54 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 25.84 | 6.67 | 10.87 | 0.010523 | 0.008500 | 241066.66 | 0.006894 | 10.27 |
VAV_MID WITH REHEAT COOLING COIL | 26.01 | 6.67 | 10.87 | 0.010741 | 0.008500 | 2338855.11 | 0.066891 | 96.22 |
VAV_TOP WITH REHEAT COOLING COIL | 25.75 | 6.67 | 10.87 | 0.010483 | 0.008500 | 243051.90 | 0.006951 | 10.45 |
CAV_BAS COOLING COIL | 25.33 | 6.67 | 10.85 | 0.010445 | 0.008500 | 131817.44 | 0.003770 | 5.81 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 10.27 |
VAV_MID WITH REHEAT FAN | 96.22 |
VAV_TOP WITH REHEAT FAN | 10.45 |
CAV_BAS FAN | 5.81 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.006894 | 0.000069 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000960 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.066891 | 0.000007 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.009784 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.006951 | 0.000069 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000983 | |
CAV_BAS_COOLC_CONTROLLER | 0.003770 | 0.000126 |
CAV_BAS_HEATC_CONTROLLER | 0.000875 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 25.73 | 504595.10 | 346136.20 | 0.012358 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.525262 | 10221.60 | 7029.21 | 0.000250 |
AIRLOOP DATACENTER MID COOLING COIL | 5.05 | 98371.86 | 67591.54 | 0.002409 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.513274 | 9997.12 | 6871.47 | 0.000245 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 25.73 | 25.73 | 25.73 | 25.73 | 504595.10 | 504595.10 | 25854.50 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.525262 | 0.525262 | 0.525262 | 0.525262 | 10221.60 | 10221.60 | 1194.37 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 5.05 | 5.05 | 5.05 | 5.05 | 98371.86 | 98371.86 | 11943.71 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.513274 | 0.513274 | 0.513274 | 0.513274 | 9997.12 | 9997.12 | 1194.37 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 25.73 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.525262 |
AIRLOOP DATACENTER MID SUPPLY FAN | 5.05 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.513274 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 25.73 | 504595.10 | 0.012358 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.525262 | 10221.60 | 0.000250 |
AIRLOOP DATACENTER MID HEATING COIL | 5.05 | 98371.86 | 0.002409 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.513274 | 9997.12 | 0.000245 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 25854.50 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 1194.37 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 11943.71 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 1194.37 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000232 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.084507 | 13797.35 | |
HEATSYS1 PUMP | 0.028236 | 8503.47 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.084507 | 10.14 |
HEATSYS1 | 0.028236 | 3.39 |
COOLSYS1_SUPPLY | 0.084507 | 10.14 |
SINGLE WATER PLANT LOOP | 0.015262 | 1.83 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.084507 | 0.084507 | 354716.82 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 3227556.78 | 3227556.78 | 0.028236 |
CENTRAL BOILER | 628654.39 | 615895.36 | 0.015262 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.042253 | 4776.19 |
COOLSYS1 CHILLER2 PUMP | 0.042253 | 4776.19 |
PLANT CIRC PUMP | 0.015262 | 3892.52 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.084507 | 0.042424 | 1483352.73 | 1483353.21 | 0.074514 |
COOLSYS1 CHILLER2 | 0.084507 | 0.042424 | 1483352.73 | 1483353.21 | 0.074514 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | U-factor Times Area Value at High Fan Speed [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/K] | |
CENTRAL TOWER | 0.015262 | 151538.13 | 76713.63 | 75769.06 | 7879.72 | 46028.18 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.149029 | 17.88 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.149029 | 36896.23 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 59.69 | 1775593.52 | 11.94 | 221949.19 |
TOWERWATERSYS COOLTOWER 2 | 59.69 | 1775593.52 | 11.94 | 221949.19 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.076923 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:51
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:51
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:51
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.40 | -0.00 | -7.60 | -12.60 | -7.70 | 0.30 | 7.00 | 14.20 | 19.20 | 20.90 | 20.00 | 15.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Rochester International Arpt MN USA TMY3 WMO#=726440 | 43.90 | -92.50 | -6.00 | 398.00 | 96634 | 1.1486 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 6.38 | 33.50 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 8.685 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 13.527 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 8.685 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 493.108 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 24139.153 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 24139.153 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 6806.209 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6806.209 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 0.8952 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 0.8506 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.077 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9497 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.008 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7608 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | -0.25194710E-14 | 0.31545203E-16 | -0.15133332E-09 | 0.44281407E-16 |
51 | 8 | 0.22101568E-07 | 0.12077324E-12 | 0.38017447E-03 | -0.25130244E-09 |
52 | 7 | -0.12312625E-01 | 0.62550027E-08 | -0.23188143E-01 | 0.13999903E-03 |
53 | 6 | 0.40728147 | 0.21773539E-05 | 0.47373573 | -0.47705255E-02 |
54 | 5 | -5.2094091 | 0.81341902E-04 | -4.4538940 | 0.63417525E-01 |
55 | 4 | 33.086216 | 0.66572093E-03 | 21.489723 | -0.42322968 |
56 | 3 | -111.40360 | 0.14515221E-02 | -55.721658 | 1.5177572 |
57 | 2 | 197.30704 | 0.81680373E-03 | 77.964377 | -2.9035099 |
58 | 1 | -171.22951 | 0.87228510E-04 | -55.280715 | 2.7467265 |
59 | 0 | 57.057407 | 0.49677855E-06 | 15.554344 | |
60 | 9 | -0.24471812E-14 | 0.33150161E-16 | -0.15341684E-09 | 0.41895861E-16 |
61 | 8 | 0.22394247E-07 | 0.11501389E-12 | 0.38323131E-03 | -0.25463030E-09 |
62 | 7 | -0.12403778E-01 | 0.59379868E-08 | -0.23319368E-01 | 0.14103548E-03 |
63 | 6 | 0.40975819 | 0.20644311E-05 | 0.47584355 | -0.47997200E-02 |
64 | 5 | -5.2335779 | 0.77040749E-04 | -4.4700764 | 0.63717207E-01 |
65 | 4 | 33.193114 | 0.62990908E-03 | 21.552961 | -0.42464900 |
66 | 3 | -111.63102 | 0.13722529E-02 | -55.846672 | 1.5210429 |
67 | 2 | 197.53241 | 0.77160263E-03 | 78.079059 | -2.9070889 |
68 | 1 | -171.31275 | 0.82342669E-04 | -55.314112 | 2.7481854 |
69 | 0 | 57.057407 | 0.46858505E-06 | 15.548868 | |
70 | 9 | -0.15654789E-15 | 0.36780279E-16 | -0.14275499E-09 | -0.53833073E-18 |
71 | 8 | 0.20895136E-07 | 0.14393424E-12 | 0.36742668E-03 | -0.23758489E-09 |
72 | 7 | -0.11931991E-01 | 0.75543961E-08 | -0.22640018E-01 | 0.13567108E-03 |
73 | 6 | 0.39693859 | 0.26436989E-05 | 0.46492102 | -0.46486079E-02 |
74 | 5 | -5.1084706 | 0.99216708E-04 | -4.3861655 | 0.62165936E-01 |
75 | 4 | 32.639712 | 0.81537030E-03 | 21.224928 | -0.41730137 |
76 | 3 | -110.45353 | 0.17843548E-02 | -55.198128 | 1.5040313 |
77 | 2 | 196.36533 | 0.10073836E-02 | 77.484335 | -2.8885557 |
78 | 1 | -170.88163 | 0.10790658E-03 | -55.141337 | 2.7406295 |
79 | 0 | 57.057407 | 0.61658484E-06 | 15.577537 | |
80 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
81 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
82 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
83 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
84 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
85 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
86 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
87 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
88 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
89 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
90 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
91 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
92 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
93 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
94 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
95 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
96 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
97 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
98 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
99 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
100 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
101 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
102 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
103 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
104 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
105 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
106 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
107 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
108 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
109 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
110 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
111 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
112 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
113 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
114 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
115 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
116 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
117 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
118 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
119 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
120 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
121 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
122 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
123 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
124 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
125 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
126 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
127 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.36_SHGC_EAST_0.4 | 35 | 1 | VerySmooth | 2.045 | 2.045 | 1.000 | 0.401 | ||
2 | WINDOW_U_0.36_SHGC_SOUTH_0.4 | 36 | 1 | VerySmooth | 2.045 | 2.045 | 1.000 | 0.401 | ||
3 | WINDOW_U_0.36_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.045 | 2.045 | 1.000 | 0.401 | ||
4 | WINDOW_U_0.36_SHGC_NORTH_0.4 | 38 | 1 | VerySmooth | 2.045 | 2.045 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.65598E-002 | 0.31435 | 0.48154 | 0.48154 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.65598E-002 | 0.31435 | 0.48154 | 0.48154 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.65598E-002 | 0.31435 | 0.48154 | 0.48154 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.65598E-002 | 0.31435 | 0.48154 | 0.48154 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 1.973E-005 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.4596E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.4620E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2632E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2651E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0368E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.0383E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7740E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7748E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.5132E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.6704E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.3084E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.4453E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0752E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1886E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7969E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8551E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1799 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.2440E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.2047 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1055 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1228 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9791E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0165E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7447E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.5206E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.7084E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.3163E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.4868E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0816E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.2133E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7974E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8568E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.4594E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.4620E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2629E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2651E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0367E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.0384E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7739E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7747E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.4568E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.8498E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.2220E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.6661E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.7453E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.8947E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.7428E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.7830E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.2950E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5489E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.9225E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.2751E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.9709E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8992E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.2230E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9536E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.3331E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.4495E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.0604E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.1452E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6983E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.7317E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.7430E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.7836E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9585E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9608E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5094E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5113E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2088E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2102E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7740E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7749E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.0109E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.1451E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5526E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6601E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2444E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3235E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7975E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8569E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.8063E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5388E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6867E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9237E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.3089E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2866E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.0165E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7442E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.0087E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.1436E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5497E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6551E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2393E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3080E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7969E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8551E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9583E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9606E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5093E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5111E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2086E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2099E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7739E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7748E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7519E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.8722E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3242E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.4111E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2601E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.2911E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7431E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.7837E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.2813E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1406E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6472E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7601E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.1608E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.5730E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2230E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9536E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.8513E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.1534E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.4549E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.7822E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3043E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.4402E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7428E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.7829E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1791 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1262 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1977 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1423 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1362 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 7.3357E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.1425E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.0380E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.6718E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 5.1010E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.2579E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.7764E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.2507E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.2602E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.2997E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.0728E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.9517E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.9644E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.6848E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.1251E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.2723E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.3273E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 6.1425E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.0375E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.5252E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.5376E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.8142E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.0644E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.3433E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.8279E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.2997E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.0728E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1791 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1264 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1978 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1426 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1364 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 7.3537E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.1557E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.0447E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.6778E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 5.1089E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.2648E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.7841E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.2633E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.2693E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.3129E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.0795E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.9521E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.9689E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.6856E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.1287E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.2791E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.3317E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 6.1557E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.0442E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.5294E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.5442E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.8190E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.0704E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.3545E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.8358E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.3129E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.0795E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 77024.51984 | 77024.51984 | 5.81490 | 5.81490 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.35600 | 1.53506E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 81191.74920 | 81191.74920 | 6.12909 | 6.12909 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.35600 | 1.53506E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 7072.99780 | 7072.99780 | 0.31414 | 1.07782 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 764390.25551 | 764390.25551 | 57.68876 | 57.68876 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.35600 | 1.53506E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 327256.99785 | 327256.99785 | 14.50554 | 14.50554 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 76174.42954 | 76174.42954 | 5.74911 | 5.74911 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.35600 | 1.53506E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 75889.78512 | 75889.78512 | 3.38501 | 3.38501 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 13480.86248 | 13480.86248 | 1.02692 | 1.02692 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 31.20000 | 1.53651E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 14169.12472 | 14169.12472 | 0.63298 | 0.63298 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 19091.78042 | 19091.78042 | 1.45428 | 1.45428 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 24.02733 | 1.53519E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 9535.85839 | 9535.85839 | 0.42606 | 0.42606 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 21264.83889 | 21264.83889 | 1.61986 | 1.61986 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 30.75833 | 1.53643E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 15113.36189 | 15113.36189 | 0.67529 | 0.67529 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 22884.93006 | 22884.93006 | 1.74325 | 1.74325 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 29.53933 | 1.53620E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 7980.30666 | 7980.30666 | 0.35632 | 0.35632 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 126420.06637 | 126420.06637 | 9.63065 | 9.63065 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 31.20000 | 1.53651E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 202972.14869 | 202972.14869 | 9.07562 | 9.07562 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 203157.56572 | 203157.56572 | 15.47625 | 15.47625 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.37000 | 1.53543E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 132602.14108 | 132602.14108 | 5.92927 | 5.92927 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 212776.33556 | 212776.33556 | 16.20910 | 16.20910 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 30.84667 | 1.53644E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 199808.24346 | 199808.24346 | 8.93382 | 8.93382 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 213630.50989 | 213630.50989 | 16.27405 | 16.27405 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 29.36267 | 1.53617E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 130468.88716 | 130468.88716 | 5.83372 | 5.83372 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 14258.81133 | 14258.81133 | 1.08625 | 1.08625 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 31.20000 | 1.53651E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 25848.53153 | 25848.53153 | 1.15628 | 1.15628 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 20437.65772 | 20437.65772 | 1.55694 | 1.55694 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 25.67033 | 1.53549E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 16832.05691 | 16832.05691 | 0.75296 | 0.75296 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 22812.82738 | 22812.82738 | 1.73789 | 1.73789 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.93500 | 1.53646E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 25504.12629 | 25504.12629 | 1.14085 | 1.14085 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 22422.47688 | 22422.47688 | 1.70814 | 1.70814 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 29.36267 | 1.53617E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 16800.06965 | 16800.06965 | 0.75153 | 0.75153 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20000 | 3.61342E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8742.63552 | 8742.63552 | 0.52526 | 0.52526 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 26.87167 | 1.53571E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -26.20000 | 3.61342E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 84010.67655 | 84010.67655 | 5.04743 | 5.04743 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 26.87167 | 1.53571E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -26.20000 | 3.61342E-004 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8543.08881 | 8543.08881 | 0.51327 | 0.51327 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 26.87167 | 1.53571E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -26.20000 | 3.61342E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 372391.95487 | 428250.74810 | 22.37322 | 25.72921 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 21.55400 | 1.53473E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:30:00 | -26.20000 | 3.61342E-004 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 149721.63 | 10.27230 | 10.27230 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 114209.09 | 3.16848 | 3.16848 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1386946.20 | 96.22149 | 96.22149 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 1141048.60 | 44.27798 | 44.27798 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 155995.66 | 10.45451 | 10.45451 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 114026.89 | 7.18663 | 7.18663 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 |
7 | CAV_BAS | Cooling | Sensible | 76009.81 | 5.81490 | 5.81490 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 91696.53 | 1.20016 | 1.20016 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 422782.96 | 25.72936 | 25.72936 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 25854.50 | 0.33839 | 0.33839 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8605.16 | 0.52526 | 0.52526 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 1194.37 | 1.56323E-002 | 1.56323E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 82688.73 | 5.04743 | 5.04743 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 11943.71 | 0.15632 | 0.15632 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8408.70 | 0.51327 | 0.51327 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 1194.37 | 1.56323E-002 | 1.56323E-002 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 5.81490 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.36422 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.00000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 0.00000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.12909 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31033 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32100 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.96744 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.82755 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.22772E-003 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.27178E-004 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.96744 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
16 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 25967.85075 |
17 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.27178E-004 |
18 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 543.54694 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 57.68876 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32971 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33500 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 19.32573 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.87922 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.15557E-003 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.48670E-003 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 19.32573 |
28 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
30 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 512857.56816 |
31 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.48670E-003 |
32 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 12560.25108 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.74911 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33084 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34400 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.97769 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.88224 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.15161E-003 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.48320E-004 |
41 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.38501 |
42 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
43 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
44 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 108398.79155 |
45 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.48320E-004 |
46 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2860.61922 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.02692 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23256 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24646 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.62016 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.63828E-003 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.77110E-004 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.63298 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
58 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20244.81781 |
59 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.77110E-004 |
60 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 533.95106 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.45428 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10583 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29086 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.60015E-003 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.19201E-004 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.42606 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
72 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13625.44693 |
73 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.19201E-004 |
74 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 359.35172 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.61986 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14744 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.32397 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39316 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.58417E-003 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.88926E-004 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.67529 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
86 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21595.44657 |
87 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.88926E-004 |
88 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 569.54361 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.74325 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.82861E-002 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.34865 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.31551E-003 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.97306E-005 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.35632 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
100 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11399.81550 |
101 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.97306E-005 |
102 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 300.70844 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.63065 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24798 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25200 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.42692 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66128 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.53642E-003 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.53755E-003 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.07562 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
114 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 290057.06520 |
115 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.53755E-003 |
116 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7647.63362 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 15.47625 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.94459E-002 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.09525 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.83123E-003 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.65779E-003 |
125 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.92927 |
126 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
128 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 189495.39112 |
129 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.65779E-003 |
130 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4996.17454 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 16.20910 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14734 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.24182 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39291 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.58585E-003 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.49796E-003 |
139 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.93382 |
140 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
142 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 285531.69249 |
143 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.49796E-003 |
144 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7528.39361 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 16.27405 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.45709E-002 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.25481 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.02872E-003 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.63110E-003 |
153 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.83372 |
154 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
156 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 186444.55028 |
157 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.63110E-003 |
158 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4915.77354 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.15628 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20654 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22800 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26363 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55078 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.84466E-003 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.23197E-004 |
167 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.15628 |
168 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
170 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 36943.34711 |
171 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.23197E-004 |
172 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 973.90950 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.55694 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.88508E-002 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.31139 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.85429E-003 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.10459E-004 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.75296 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
184 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 24056.73291 |
185 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.10459E-004 |
186 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 634.18474 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.73789 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13742 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.34758 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36646 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.77247E-003 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.18887E-004 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.14085 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
198 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 36450.76801 |
199 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.18887E-004 |
200 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 960.93013 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.70814 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.01010E-002 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.34163 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.22859E-003 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.10059E-004 |
209 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.75153 |
210 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
211 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
212 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 24011.03142 |
213 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.10059E-004 |
214 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 632.97893 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.52526 |
216 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.04743 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.51327 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 25.72921 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.98670 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.17738 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.97340 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.17738 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.27230 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.27230 |
225 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
226 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.30932 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 57.63940 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 31.34454 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 115.27881 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 44.27798 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 96.22149 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 96.22149 |
233 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
234 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.46017 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.95418 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.24192 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.90836 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 7.18663 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.45451 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.45451 |
241 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
242 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.68742 |
243 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.00000 |
244 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.00000 |
245 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.81490 |
246 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 1.20016 |
247 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.81490 |
248 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.81490 |
249 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
250 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.20639 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 25.72921 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 25.72921 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 25.72921 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 25.72921 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 25.72936 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 25.72936 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.52526 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.52526 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.52526 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.52526 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.52526 |
264 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.52526 |
265 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
266 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.04743 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.04743 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.04743 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 5.04743 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.04743 |
272 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.04743 |
273 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
274 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.51327 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.51327 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.51327 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.51327 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.51327 |
280 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.51327 |
281 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
282 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
283 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.27230 |
284 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 96.22149 |
285 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.45451 |
286 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.81490 |
287 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 25.72936 |
288 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.52526 |
289 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 5.04743 |
290 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.51327 |
291 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.27230 |
292 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_BOT WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.83528 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.86933 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.05233E-002 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
298 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 241066.66489 |
299 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.89448E-003 |
300 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.27230 |
301 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 109767.78202 |
302 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.60296E-004 |
303 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1657.36847 |
304 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.27230 |
305 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.89448E-003 |
306 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.90684E-005 |
307 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.60296E-004 |
308 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 96.22149 |
309 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 25.38195 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.00726 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.87009 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.07412E-002 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
315 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2338855.11276 |
316 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.68910E-002 |
317 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 96.22149 |
318 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 1118393.64158 |
319 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.78420E-003 |
320 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 16518.75756 |
321 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 96.22149 |
322 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.68910E-002 |
323 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.11891E-006 |
324 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.78420E-003 |
325 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.45451 |
326 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.74955 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.86919 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.04829E-002 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
332 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 243051.90022 |
333 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.95125E-003 |
334 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.45451 |
335 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 112315.04410 |
336 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.82581E-004 |
337 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1693.42883 |
338 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.45451 |
339 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.95125E-003 |
340 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.85043E-005 |
341 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.82581E-004 |
342 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.81490 |
343 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.32814 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.84622 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.04450E-002 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
349 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 131817.43611 |
350 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.76996E-003 |
351 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.81490 |
352 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 304738.27328 |
353 | Coil:Heating:Water | CAV_BAS HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
354 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
355 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2622.25111 |
356 | Fan:VariableVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.81490 |
357 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.76996E-003 |
358 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.26312E-004 |
359 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.74844E-004 |
360 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 25.72936 |
361 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
362 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 25.72936 |
363 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 504595.09983 |
364 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 346136.20459 |
365 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.23575E-002 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 25.72936 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 25.72936 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 25.72936 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 25.72936 |
370 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 504595.09983 |
371 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 504595.09983 |
372 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 25854.49862 |
373 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
374 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 25.72936 |
375 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 25.72936 |
376 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 504595.09983 |
377 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.23575E-002 |
378 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 25854.49862 |
379 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 2.31648E-004 |
380 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
381 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
382 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
383 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.52526 |
384 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
385 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.52526 |
386 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10221.60128 |
387 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 7029.20676 |
388 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.50326E-004 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.52526 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.52526 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.52526 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.52526 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10221.60128 |
394 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10221.60128 |
395 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1194.37073 |
396 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
397 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.52526 |
398 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.52526 |
399 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 10221.60128 |
400 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.50326E-004 |
401 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1194.37073 |
402 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.04743 |
403 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
404 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.04743 |
405 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 98371.86381 |
406 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 67591.53786 |
407 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.40912E-003 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 5.04743 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 5.04743 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 5.04743 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.04743 |
412 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 98371.86381 |
413 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 98371.86381 |
414 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 11943.70727 |
415 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
416 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 5.04743 |
417 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.04743 |
418 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 98371.86381 |
419 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.40912E-003 |
420 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 11943.70727 |
421 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.51327 |
422 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
423 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.51327 |
424 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9997.12401 |
425 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6871.46834 |
426 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.44829E-004 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.51327 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.51327 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.51327 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.51327 |
431 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9997.12401 |
432 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9997.12401 |
433 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1194.37073 |
434 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
435 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.51327 |
436 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.51327 |
437 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9997.12401 |
438 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.44829E-004 |
439 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1194.37073 |
440 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 8.45067E-002 |
441 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 13797.35400 |
442 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 8.45067E-002 |
443 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 10.14080 |
444 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 8.45067E-002 |
445 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 8.45067E-002 |
446 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 354716.82041 |
447 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
448 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.82361E-002 |
449 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 3.38833 |
450 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.82361E-002 |
451 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 8503.46572 |
452 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
453 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 3227556.78351 |
454 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 3227556.78000 |
455 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.82361E-002 |
456 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 8.45067E-002 |
457 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 10.14080 |
458 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 4.22533E-002 |
459 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 4776.18674 |
460 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 4.22533E-002 |
461 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 4776.18674 |
462 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 8.45067E-002 |
463 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.24237E-002 |
464 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1483352.73469 |
465 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1483353.21000 |
466 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 7.45144E-002 |
467 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 8.45067E-002 |
468 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.24237E-002 |
469 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1483352.73469 |
470 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1483353.21000 |
471 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 7.45144E-002 |
472 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.52618E-002 |
473 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.83141 |
474 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.52618E-002 |
475 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3892.51644 |
476 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.52618E-002 |
477 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 151538.12778 |
478 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at High Fan Speed [W/K] | 76713.62731 |
479 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 75769.06389 |
480 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
481 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/K] | 46028.17638 |
482 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 628654.38943 |
483 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 615895.36000 |
484 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.52618E-002 |
485 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
486 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
487 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
488 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
489 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
490 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.14903 |
491 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 17.88346 |
492 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.14903 |
493 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 36896.23106 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 59.69398 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1775593.52056 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 11.93880 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 221949.19007 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 59.69398 |
499 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1775593.52056 |
500 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 11.93880 |
501 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 221949.19007 |
502 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 7.69225E-002 |
503 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 7.69225E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 24619.51 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 485847.57 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 102721.84 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 19182.53 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 12910.39 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 20462.09 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 10801.92 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 274820.11 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 179540.66 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 270532.96 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 176650.34 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 35001.75 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 22792.38 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 34535.10 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 22749.07 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 72114.15 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 715510.27 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 73664.51 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 94839.65 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 271097.05 | 182198.81 | 88898.23 | 0.67 | 45355.66 | 460.02 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2574590.74 | 1721068.49 | 853522.25 | 0.67 | 425466.55 | 4315.32 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 274946.25 | 185042.32 | 89903.93 | 0.67 | 46192.48 | 468.51 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 151671.41 | 102424.41 | 49247.01 | 0.68 | 25900.35 | 262.70 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 9.21 | 31.42 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 9.21 | 31.42 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.354 | 0.336 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.354 | 0.336 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.354 | 0.336 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_NORTH_0.4 | N/A | 2.045 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_NORTH_0.4 | N/A | 2.045 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_NORTH_0.4 | N/A | 2.045 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_NORTH_0.4 | N/A | 2.045 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_NORTH_0.4 | N/A | 2.045 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_EAST_0.4 | N/A | 2.045 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_EAST_0.4 | N/A | 2.045 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_EAST_0.4 | N/A | 2.045 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_SOUTH_0.4 | N/A | 2.045 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_SOUTH_0.4 | N/A | 2.045 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_SOUTH_0.4 | N/A | 2.045 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_SOUTH_0.4 | N/A | 2.045 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_SOUTH_0.4 | N/A | 2.045 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_WEST_0.4 | N/A | 2.045 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_WEST_0.4 | N/A | 2.045 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_WEST_0.4 | N/A | 2.045 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_NORTH_0.4 | N/A | 2.045 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_EAST_0.4 | N/A | 2.045 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_SOUTH_0.4 | N/A | 2.045 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_WEST_0.4 | N/A | 2.045 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_NORTH_0.4 | N/A | 2.045 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_EAST_0.4 | N/A | 2.045 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_SOUTH_0.4 | N/A | 2.045 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_WEST_0.4 | N/A | 2.045 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.354 | 0.336 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.354 | 0.336 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.354 | 0.336 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.0712801436E-003 | 1.6189177081E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 3.4612798417E-003 | 6.5133244245E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 3.9343910064E-002 | 2.0686606205E-002 | Pass | Pass | 0.5044366094 | 0.5076585433 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 4.6776092257E-002 | 5.7872193887E-002 | Pass | Pass | 9.6447632391 | 58.6248036632 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.8537529762E-002 | 1.7892129296E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 2.4879536223E-002 | 3.9077805079E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 3.6438987009E-002 | 6.5258984007E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 1.9219835020E-002 | 1.8982350565E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3023344244 | 0.2935927991 | Pass | Pass | 13.9808513350 | 71.2112973254 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3211351453 | 0.3205523585 | Pass | Pass | 7.2624465185 | 41.8728231667 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2721891529 | 0.2914239852 | Pass | Pass | 9.1245390276 | 81.7266547803 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2072232585 | 0.2176661725 | Pass | Pass | 4.4020485459 | 22.2829096934 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.4612320967 | 0.4372924823 | Pass | Pass | 10.8983389056 | 35.0830853105 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.4908443414 | 0.4811838166 | Pass | Pass | 11.8142661827 | 51.8095805878 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4369112317 | 0.4512366627 | Pass | Pass | 18.8448035765 | 71.5272107536 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3799047935 | 0.3791587784 | Pass | Pass | 6.9347623464 | 28.1889913211 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.4420683260E-003 | 3.2124910216E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.8150766443E-002 | 2.6099137774E-002 | Pass | Pass | 0.4985502195 | 0.4639900263 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1383201853 | 9.1050971960E-002 | Pass | Pass | 0.4944954203 | 0.4771580644 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.9729182813E-006 | 5.1028187876E-006 | Pass | Pass | 4.5995401815E-003 | 4.4358781492E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.3808411347E-003 | 4.7467879359E-003 | Pass | Pass | 1.7577160964E-003 | 1.6662992441E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 8.0532677370E-003 | 7.5022783933E-003 | Pass | Pass | 3.0480676723E-003 | 2.6986846990E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.4716652280E-006 | 3.9852918771E-006 | Pass | Pass | 4.1982478781E-005 | 1.0959110403E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:51
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 6828.46 | 186.29 | 0.00 | 27820.47 | 11522.56 | 46357.78 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:51
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 26.00 | 35 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 29.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 107.00 | 45 | |||
Jul | 72.00 | 29 | |||
Aug | 0.00 | 0 | |||
Sep | 20.00 | 11 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 4.00 | 8 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:51
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.340 | 0.354 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.340 | 0.354 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.340 | 0.354 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.340 | 0.354 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.340 | 0.354 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.340 | 0.354 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.36_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.36_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.36_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.36_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.36_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.36_SHGC_EAST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.36_SHGC_EAST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.36_SHGC_EAST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.36_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.36_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.36_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.36_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.36_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.36_SHGC_WEST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.36_SHGC_WEST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.36_SHGC_WEST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.36_SHGC_NORTH_0.4 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.045 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.36_SHGC_EAST_0.4 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.045 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.36_SHGC_SOUTH_0.4 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.045 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.36_SHGC_WEST_0.4 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.045 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.36_SHGC_NORTH_0.4 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.045 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.36_SHGC_EAST_0.4 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.045 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.36_SHGC_SOUTH_0.4 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.045 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.36_SHGC_WEST_0.4 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.045 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.045 | 0.401 | 0.442 | |||||||||||||||||
North Total or Average | 1390.74 | 2.045 | 0.401 | 0.442 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.045 | 0.401 | 0.442 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:51
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:51
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.6849 | 2779.43 | 24139.15 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 216.17 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 8.6849 | 2496.12 | 21678.66 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 194.14 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 8.6849 | 24961.20 | 216786.56 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 1941.36 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 8.6849 | 2496.12 | 21678.66 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 194.14 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 8.6849 | 313.41 | 2721.97 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.65 | 0.0000 | Y | 14.13 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.39 | 0.0000 | Y | 9.02 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 8.6849 | 313.42 | 2722.03 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.09 | 0.0000 | Y | 13.84 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.28 | 0.0000 | Y | 8.98 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 8.6849 | 3134.13 | 27219.72 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.58 | 0.0000 | Y | 140.92 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 8.6849 | 2019.75 | 17541.42 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.34 | 0.0000 | Y | 90.03 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 8.6849 | 3134.20 | 27220.31 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.06 | 0.0000 | Y | 138.26 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 8.6849 | 2019.75 | 17541.42 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.24 | 0.0000 | Y | 89.69 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 8.6849 | 313.41 | 2721.97 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.58 | 0.0000 | Y | 14.09 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.34 | 0.0000 | Y | 9.00 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 8.6849 | 313.42 | 2722.03 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.06 | 0.0000 | Y | 13.83 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.24 | 0.0000 | Y | 8.97 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 8.6849 | 783.68 | 6806.21 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 62.65 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 13.9016 | 36.20 | 503.28 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.16 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 13.9016 | 362.03 | 5032.75 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 51.55 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 13.9016 | 36.20 | 503.28 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.16 |
Interior Lighting Total | 8.7339 | 46320.38 | 404555.99 | 1014.44 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13271.55 | AstronomicalClock | - | 42.24 | 42.24 | 105.23 | |
EXTERIOR_LIGHTS_B | 989.48 | AstronomicalClock | - | 83.63 | 62.93 | 11.69 | |
EXTERIOR_LIGHTS_C | 26594.85 | AstronomicalClock | - | 83.63 | 47.43 | 236.79 | |
Exterior Lighting Total | 40855.88 | 353.71 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:51
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2945690.09 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 3227556.78 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1483353.21 | 6.01 | 1475087.31 | 5.99 | 9.21 | 31.42 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 1483353.21 | 6.01 | 1475087.31 | 5.99 | 9.21 | 31.42 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 631535.15 | |||||
CENTRAL BOILER | Boiler:HotWater | 615895.36 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1775593.52 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1775593.52 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 241066.66 | 271097.05 | 182198.81 | 88898.23 | 0.67 | - | 45355.66 | 460.02 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2338855.11 | 2574590.74 | 1721068.49 | 853522.25 | 0.67 | - | 425466.55 | 4315.32 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 243051.90 | 274946.25 | 185042.32 | 89903.93 | 0.67 | - | 46192.48 | 468.51 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 131817.44 | 151671.41 | 102424.41 | 49247.01 | 0.68 | - | 25900.35 | 262.70 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 504595.10 | 346136.20 | 158458.90 | 0.69 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10221.60 | 7029.21 | 3192.39 | 0.69 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 98371.86 | 67591.54 | 30780.33 | 0.69 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9997.12 | 6871.47 | 3125.66 | 0.69 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 25967.85 | 24619.51 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 512857.57 | 485847.57 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 108398.79 | 102721.84 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 20244.82 | 19182.53 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 13625.45 | 12910.39 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 21595.45 | 20462.09 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 11399.82 | 10801.92 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 290057.07 | 274820.11 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 189495.39 | 179540.66 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 285531.69 | 270532.96 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 186444.55 | 176650.34 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 36943.35 | 35001.75 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 24056.73 | 22792.38 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 36450.77 | 34535.10 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 24011.03 | 22749.07 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 109767.78 | 72114.15 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 1118393.64 | 715510.27 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 112315.04 | 73664.51 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 100000.00 | 94839.65 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 504595.10 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10221.60 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 98371.86 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9997.12 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 25854.50 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 1194.37 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 11943.71 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 1194.37 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 10.27 | 23334.48 | 2271.59 | 1.00 | 1.12 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 96.22 | 218576.09 | 2271.59 | 1.00 | 1.08 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 10.45 | 23748.40 | 2271.59 | 1.00 | 1.12 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
CAV_BAS FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.81 | 13365.33 | 2298.46 | 1.00 | 1.13 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 25.73 | 42434.07 | 1649.25 | 1.00 | 1.14 | General | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.53 | 588.35 | 1120.11 | 1.00 | 1.58 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 5.05 | 5653.66 | 1120.11 | 1.00 | 1.15 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.51 | 574.92 | 1120.11 | 1.00 | 1.59 | General | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.084507 | 13797.35 | 163269.45 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.028236 | 8503.47 | 301156.09 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.042253 | 4776.19 | 113036.94 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.042253 | 4776.19 | 113036.94 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.015262 | 3892.52 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.149029 | 36896.23 | 247577.87 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:51
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 77024.52 | 77024.52 | 27.71 | 5.815 | 5.815 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00895 | 23.36 | 0.01535 | 1.200 | 0.00 |
CORE_BOTTOM | 81191.75 | 81191.75 | 32.53 | 6.129 | 6.129 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00888 | 23.36 | 0.01535 | 1.078 | 0.00 |
CORE_MID | 764390.26 | 764390.26 | 306.23 | 57.689 | 57.689 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 23.36 | 0.01535 | 10.778 | 0.00 |
CORE_TOP | 76174.43 | 76174.43 | 30.52 | 5.749 | 5.749 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 23.36 | 0.01535 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 13480.86 | 13480.86 | 43.01 | 1.027 | 1.027 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00889 | 31.20 | 0.01537 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 19091.78 | 19091.78 | 94.53 | 1.454 | 1.454 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 24.00 | 24.00 | 0.00868 | 24.03 | 0.01535 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 21264.84 | 21264.84 | 67.85 | 1.620 | 1.620 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 24.00 | 24.00 | 0.00875 | 30.76 | 0.01536 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 22884.93 | 22884.93 | 113.31 | 1.743 | 1.743 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00865 | 29.54 | 0.01536 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 126420.07 | 126420.07 | 403.37 | 9.631 | 9.631 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00906 | 31.20 | 0.01537 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 203157.57 | 203157.57 | 1005.85 | 15.476 | 15.476 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00874 | 25.37 | 0.01535 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 212776.34 | 212776.34 | 678.89 | 16.209 | 16.209 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00884 | 30.85 | 0.01536 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 213630.51 | 213630.51 | 1057.71 | 16.274 | 16.274 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00872 | 29.36 | 0.01536 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 14258.81 | 14258.81 | 45.50 | 1.086 | 1.086 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00905 | 31.20 | 0.01537 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 20437.66 | 20437.66 | 101.19 | 1.557 | 1.557 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00876 | 25.67 | 0.01535 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 22812.83 | 22812.83 | 72.79 | 1.738 | 1.738 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00885 | 30.93 | 0.01536 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 22422.48 | 22422.48 | 111.02 | 1.708 | 1.708 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00874 | 29.36 | 0.01536 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8742.64 | 8742.64 | 241.49 | 0.525 | 0.525 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 27.00 | 27.00 | 0.00858 | 26.87 | 0.01536 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 84010.68 | 84010.68 | 2320.56 | 5.047 | 5.047 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 27.00 | 27.00 | 0.00859 | 26.87 | 0.01536 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8543.09 | 8543.09 | 235.98 | 0.513 | 0.513 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 27.00 | 27.00 | 0.00858 | 26.87 | 0.01536 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 372391.95 | 428250.75 | 546.46 | 22.373 | 25.729 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 21.55 | 0.01535 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 22.75 | 0.00036 | -26.20 | 0.00036 | 1.200 | 0.00 |
CORE_BOTTOM | 7073.00 | 7073.00 | 2.83 | 0.314 | 1.078 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -26.20 | 0.00036 | 1.078 | 0.00 |
CORE_MID | 327257.00 | 327257.00 | 131.11 | 14.506 | 14.506 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -26.20 | 0.00036 | 10.778 | 0.00 |
CORE_TOP | 75889.79 | 75889.79 | 30.40 | 3.385 | 3.385 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -26.20 | 0.00036 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 14169.12 | 14169.12 | 45.21 | 0.633 | 0.633 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -26.20 | 0.00036 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 9535.86 | 9535.86 | 47.21 | 0.426 | 0.426 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -26.20 | 0.00036 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 15113.36 | 15113.36 | 48.22 | 0.675 | 0.675 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00779 | -26.20 | 0.00036 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 7980.31 | 7980.31 | 39.51 | 0.356 | 0.356 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00768 | -26.20 | 0.00036 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 202972.15 | 202972.15 | 647.62 | 9.076 | 9.076 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -26.20 | 0.00036 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 132602.14 | 132602.14 | 656.53 | 5.929 | 5.929 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -26.20 | 0.00036 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 199808.24 | 199808.24 | 637.51 | 8.934 | 8.934 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -26.20 | 0.00036 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 130468.89 | 130468.89 | 645.97 | 5.834 | 5.834 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -26.20 | 0.00036 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 25848.53 | 25848.53 | 82.47 | 1.156 | 1.156 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -26.20 | 0.00036 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 16832.06 | 16832.06 | 83.34 | 0.753 | 0.753 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -26.20 | 0.00036 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 25504.13 | 25504.13 | 81.37 | 1.141 | 1.141 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -26.20 | 0.00036 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 16800.07 | 16800.07 | 83.18 | 0.752 | 0.752 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -26.20 | 0.00036 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 24.31 | 0.00100 | -26.20 | 0.00036 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 22.33 | 0.00100 | -26.20 | 0.00036 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 19.91 | 0.00100 | -26.20 | 0.00036 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:30:00 | 18.00 | 27.00 | 0.00850 | -26.20 | 0.00036 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 10.27 | 10.27 | 3.17 | 3.17 | 10.2723 | 3.1774 | 10.2723 | 0.3093 | 0.3000 |
VAV_MID WITH REHEAT | 96.22 | 96.22 | 44.28 | 44.28 | 96.2215 | 44.2780 | 96.2215 | 0.4602 | 0.3000 |
VAV_TOP WITH REHEAT | 10.45 | 10.45 | 7.19 | 7.19 | 10.4545 | 7.1866 | 10.4545 | 0.6874 | 0.3000 |
CAV_BAS | 5.81 | 5.81 | 1.20 | 1.20 | 5.8149 | 1.2002 | 5.8149 | 0.2064 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 25.73 | 25.73 | 0.34 | 0.34 | 25.7294 | 25.7292 | 25.7294 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.53 | 0.53 | 0.02 | 0.02 | 0.5253 | 0.5253 | 0.5253 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 5.05 | 5.05 | 0.16 | 0.16 | 5.0474 | 5.0474 | 5.0474 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.51 | 0.51 | 0.02 | 0.02 | 0.5133 | 0.5133 | 0.5133 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 25967.851 | 25967.851 | 1.967439 | 0.00022718 | 543.547 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25967.85 | 25967.85 | 1.967439 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00799878 | 49.3215 | 7073.00 | 0.00 | 26061.87 | 26061.87 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 512857.568 | 512857.568 | 19.325733 | 0.00448670 | 12560.251 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 512857.57 | 512857.57 | 19.325733 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00800000 | 49.3289 | 327257.00 | 0.00 | 514507.61 | 514507.61 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 108398.792 | 108398.792 | 3.385013 | 0.00094832 | 2860.619 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 108398.79 | 108398.79 | 3.385013 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00800000 | 49.3289 | 75889.79 | 0.00 | 108767.80 | 108767.80 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 20244.818 | 20244.818 | 0.632982 | 0.00017711 | 533.951 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20244.82 | 20244.82 | 0.632982 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00776547 | 47.9036 | 14169.12 | 0.00 | 20311.54 | 20311.54 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 13625.447 | 13625.447 | 0.426058 | 0.00011920 | 359.352 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13625.45 | 13625.45 | 0.426058 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00777248 | 47.9463 | 9535.86 | 0.00 | 13670.24 | 13670.24 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 21595.447 | 21595.447 | 0.675289 | 0.00018893 | 569.544 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21595.45 | 21595.45 | 0.675289 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00778705 | 48.0349 | 15113.36 | 0.00 | 21666.40 | 21666.40 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 11399.815 | 11399.815 | 0.356323 | 0.00009973 | 300.708 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11399.82 | 11399.82 | 0.356323 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00767953 | 47.3808 | 7980.31 | 0.00 | 11437.69 | 11437.69 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 290057.065 | 290057.065 | 9.075615 | 0.00253755 | 7647.634 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 290057.07 | 290057.07 | 9.075615 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00765215 | 47.2157 | 202972.15 | 0.00 | 290994.74 | 290994.74 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 189495.391 | 189495.391 | 5.929274 | 0.00165779 | 4996.175 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 189495.39 | 189495.39 | 5.929274 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00764559 | 47.1758 | 132602.14 | 0.00 | 190107.59 | 190107.59 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 285531.692 | 285531.692 | 8.933824 | 0.00249796 | 7528.394 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 285531.69 | 285531.69 | 8.933824 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00764664 | 47.1821 | 199808.24 | 0.00 | 286455.29 | 286455.29 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 186444.550 | 186444.550 | 5.833719 | 0.00163110 | 4915.774 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 186444.55 | 186444.55 | 5.833719 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00763980 | 47.1406 | 130468.89 | 0.00 | 187047.16 | 187047.16 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 36943.347 | 36943.347 | 1.156280 | 0.00032320 | 973.910 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 36943.35 | 36835.06 | 1.156280 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00766183 | 47.2756 | 25848.53 | 0.00 | 37061.78 | 37061.78 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 24056.733 | 24056.733 | 0.752957 | 0.00021046 | 634.185 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24056.73 | 24056.73 | 0.752957 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00765411 | 47.2287 | 16832.06 | 0.00 | 24133.82 | 24133.82 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 36450.768 | 36450.768 | 1.140847 | 0.00031889 | 960.930 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 36450.77 | 36450.77 | 1.140847 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00765745 | 47.2490 | 25504.13 | 0.00 | 36567.67 | 36567.67 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 24011.031 | 24011.031 | 0.751530 | 0.00021006 | 632.979 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24011.03 | 24011.03 | 0.751530 | 12.80 | 11.18 | 0.00800000 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 0.0000 | 21.00 | 0.00765364 | 47.2259 | 16800.07 | 0.00 | 24087.97 | 24087.97 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 241066.665 | -999.000 | 10.272297 | 0.00689448 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 241066.66 | 180167.62 | 10.272297 | 25.84 | 18.17 | 0.01052335 | 10.87 | 10.87 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 24.7091 | 24.00 | 0.00886572 | 45.4983 | 130645.94 | 0.00 | 248999.92 | 178453.23 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 109767.782 | 109767.782 | 3.081689 | 0.00096030 | 1657.368 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 109767.78 | 109767.78 | 3.081689 | -18.06 | -18.06 | 0.00165800 | 12.80 | 11.18 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 82.3636 | 19.82 | 0.00765351 | 50.7770 | 35721.83 | 0.00 | 87212.25 | 87212.25 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2338855.113 | -999.000 | 96.221492 | 0.06689096 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 2338855.11 | 1706949.29 | 96.221492 | 26.01 | 18.39 | 0.01074121 | 10.87 | 10.87 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 26.3787 | 24.00 | 0.00895233 | 45.9373 | 1194448.38 | 0.00 | 2414044.45 | 1692202.72 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1118393.642 | 1118393.642 | 28.866448 | 0.00978420 | 16518.758 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 1118393.64 | 1118393.64 | 28.866448 | -20.77 | -20.77 | 0.00123310 | 12.80 | 11.18 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 87.9289 | 17.87 | 0.00754936 | 56.5936 | 395538.16 | 0.00 | 865117.70 | 865117.70 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 243051.900 | -999.000 | 10.454513 | 0.00695125 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 243051.90 | 182314.72 | 10.454513 | 25.75 | 18.11 | 0.01048289 | 10.87 | 10.87 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | 24.2784 | 24.00 | 0.00891418 | 45.7444 | 137017.46 | 0.00 | 251100.48 | 180543.53 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 112315.044 | 112315.044 | 3.136354 | 0.00098258 | 1693.429 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 112315.04 | 112315.04 | 3.136354 | -18.23 | -18.23 | 0.00172688 | 12.80 | 11.18 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 80.9280 | 15.60 | 0.00722844 | 62.6447 | 44925.80 | 0.00 | 89088.08 | 89088.08 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 131817.436 | -999.000 | 5.814901 | 0.00376996 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 131817.44 | 98649.65 | 5.814901 | 25.33 | 17.94 | 0.01044505 | 10.85 | 10.85 | 0.00850000 | 29.82 | 0.01536253 | 22.76 | 20.6393 | 24.00 | 0.00899023 | 46.1281 | 69010.78 | 0.00 | 136231.89 | 97592.66 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 100000.000 | 100000.000 | 3.185474 | 0.00087484 | 2622.251 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 100000.00 | 100000.00 | 3.185474 | -5.41 | -9.38 | 0.00036134 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 37.6759 | 22.85 | 0.00036134 | 2.0146 | 0.00 | 0.00 | 100071.45 | 100071.45 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 504595.100 | 346136.205 | 25.729359 | 0.01235750 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 466065.44 | 457491.34 | -999.0 | 28.51 | 17.55 | 0.00863202 | 12.80 | 11.68 | 0.00850000 | 31.20 | 0.01536508 | 23.13 | -999.0000 | 27.00 | 0.00854219 | 36.7051 | 371961.85 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10221.601 | 7029.207 | 0.525262 | 0.00025033 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 9427.66 | 9051.25 | -999.0 | 27.99 | 17.50 | 0.00878431 | 12.80 | 11.68 | 0.00850000 | 26.87 | 0.01535708 | 21.94 | -999.0000 | 27.00 | 0.00858270 | 36.8743 | 8742.64 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 98371.864 | 67591.538 | 5.047426 | 0.00240912 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 90753.64 | 86990.61 | -999.0 | 27.99 | 17.51 | 0.00879573 | 12.80 | 11.68 | 0.00850000 | 26.87 | 0.01535708 | 21.94 | -999.0000 | 27.00 | 0.00858603 | 36.8885 | 84010.68 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9997.124 | 6871.468 | 0.513274 | 0.00024483 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 9221.95 | 8845.51 | -999.0 | 27.99 | 17.50 | 0.00879095 | 12.80 | 11.68 | 0.00850000 | 26.87 | 0.01535708 | 21.94 | -999.0000 | 27.00 | 0.00858469 | 36.8828 | 8543.09 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 504595.100 | 504595.100 | 25.729359 | 0.01235750 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 504595.10 | 504595.10 | 25.729359 | -26.20 | -26.20 | 0.00036134 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 1.3152 | 27.00 | 0.00850000 | 36.5206 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10221.601 | 10221.601 | 0.525262 | 0.00025033 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10221.60 | 10221.60 | 0.525262 | -26.20 | -26.20 | 0.00036134 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 2.9761 | 25.14 | 0.00099659 | 4.8386 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 98371.864 | 98371.864 | 5.047426 | 0.00240912 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 98371.86 | 98371.86 | 5.047426 | -26.20 | -26.20 | 0.00036134 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 3.0971 | 23.56 | 0.00099661 | 5.3186 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9997.124 | 9997.124 | 0.513274 | 0.00024483 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9997.12 | 9997.12 | 0.513274 | -26.20 | -26.20 | 0.00036134 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 3.0456 | 22.13 | 0.00099595 | 5.7952 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 25854.499 | 25854.499 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 25854.50 | 25854.50 | 25.729359 | -0.34 | -0.34 | 0.00839296 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 1.3152 | 27.00 | 0.00850000 | 36.5206 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 1194.371 | 1194.371 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1194.37 | 1194.37 | 0.525262 | -0.78 | -5.20 | 0.00097768 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 2.9761 | 25.14 | 0.00099659 | 4.8386 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 11943.707 | 11943.707 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 11943.71 | 11943.71 | 5.047426 | -0.81 | -5.22 | 0.00097693 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 3.0971 | 23.56 | 0.00099661 | 5.3186 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 1194.371 | 1194.371 | -999.0 | -999.0 | -999.000 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1194.37 | 1194.37 | 0.513274 | -0.80 | -5.22 | 0.00097662 | 40.00 | 20.63 | 0.00800000 | -26.20 | 0.00036134 | -26.20 | 3.0456 | 22.13 | 0.00099595 | 5.7952 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:25:51
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 25967.851 | 25967.851 | 1.967439 | 0.00022718 | 543.547 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.23319435 | 54.44 | 82.22 | 27.78 | 3292512.65 | 0.7887 | 0.804567 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25967.85 | 25967.85 | 1.0000 | 2.25971297 | 1.967439 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.22715491 | 60.00 | 32.22 | 27.78 | 0.000 | 25967.85 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.83 | 0.00799878 | 21.00 | 0.00799878 | 49.3215 | 7073.00 | 0.00 | 26061.87 | 26061.87 | 2.25971297 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 24.11 | 15.99 | 0.00800000 | 44593.1 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 512857.568 | 512857.568 | 19.325733 | 0.00448670 | 12560.251 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.23319435 | 54.44 | 82.22 | 27.78 | 3292512.65 | 15.5765 | 15.889963 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 512857.57 | 512857.57 | 1.0000 | 22.19668374 | 19.325733 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 4.48624404 | 60.00 | 32.22 | 27.78 | 0.000 | 512857.57 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 49.3289 | 327257.00 | 0.00 | 514507.61 | 514507.61 | 22.19668374 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 35.53 | 19.82 | 0.00800000 | 56239.3 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 108398.792 | 108398.792 | 3.385013 | 0.00094832 | 2860.619 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.23319435 | 54.44 | 82.22 | 27.78 | 3292512.65 | 3.2923 | 3.358540 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 108398.79 | 108398.79 | 1.0000 | 3.88787671 | 3.385013 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.94822318 | 60.00 | 32.22 | 27.78 | 0.000 | 108398.79 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 49.3289 | 75889.79 | 0.00 | 108767.80 | 108767.80 | 3.88787671 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.24 | 21.25 | 0.00800000 | 61036.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20244.818 | 20244.818 | 0.632982 | 0.00017711 | 533.951 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.23319435 | 54.44 | 82.22 | 27.78 | 3292512.65 | 0.6149 | 0.627249 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20244.82 | 20244.82 | 1.0000 | 0.72701550 | 0.632982 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.17709243 | 60.00 | 32.22 | 27.78 | 0.000 | 20244.82 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00776547 | 21.00 | 0.00776547 | 47.9036 | 14169.12 | 0.00 | 20311.54 | 20311.54 | 0.72701550 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60998.1 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13625.447 | 13625.447 | 0.426058 | 0.00011920 | 359.352 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.23319435 | 54.44 | 82.22 | 27.78 | 3292512.65 | 0.4138 | 0.422160 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13625.45 | 13625.45 | 1.0000 | 0.48935188 | 0.426058 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.11918919 | 60.00 | 32.22 | 27.78 | 0.000 | 13625.45 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00777248 | 21.00 | 0.00777248 | 47.9463 | 9535.86 | 0.00 | 13670.24 | 13670.24 | 0.48935188 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60995.2 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21595.447 | 21595.447 | 0.675289 | 0.00018893 | 569.544 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.23319435 | 54.44 | 82.22 | 27.78 | 3292512.65 | 0.6559 | 0.669096 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21595.45 | 21595.45 | 1.0000 | 0.77560719 | 0.675289 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.18890711 | 60.00 | 32.22 | 27.78 | 0.000 | 21595.45 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00778705 | 21.00 | 0.00778705 | 48.0349 | 15113.36 | 0.00 | 21666.40 | 21666.40 | 0.77560719 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60994.6 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11399.815 | 11399.815 | 0.356323 | 0.00009973 | 300.708 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.23319435 | 54.44 | 82.22 | 27.78 | 3292512.65 | 0.3462 | 0.353203 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11399.82 | 11399.82 | 1.0000 | 0.40925689 | 0.356323 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.09972039 | 60.00 | 32.22 | 27.78 | 0.000 | 11399.82 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00767953 | 21.00 | 0.00767953 | 47.3808 | 7980.31 | 0.00 | 11437.69 | 11437.69 | 0.40925689 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61007.3 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 290057.065 | 290057.065 | 9.075615 | 0.00253755 | 7647.634 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.23319435 | 54.44 | 82.22 | 27.78 | 3292512.65 | 8.8096 | 8.986893 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 290057.07 | 290057.07 | 1.0000 | 10.42385062 | 9.075615 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 2.53728688 | 60.00 | 32.22 | 27.78 | 0.000 | 290057.07 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00765215 | 21.00 | 0.00765215 | 47.2157 | 202972.15 | 0.00 | 290994.74 | 290994.74 | 10.42385062 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60976.1 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 189495.391 | 189495.391 | 5.929274 | 0.00165779 | 4996.175 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.23319435 | 54.44 | 82.22 | 27.78 | 3292512.65 | 5.7553 | 5.871171 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 189495.39 | 189495.39 | 1.0000 | 6.81010200 | 5.929274 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 1.65761924 | 60.00 | 32.22 | 27.78 | 0.000 | 189495.39 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00764559 | 21.00 | 0.00764559 | 47.1758 | 132602.14 | 0.00 | 190107.59 | 190107.59 | 6.81010200 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60975.4 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 285531.692 | 285531.692 | 8.933824 | 0.00249796 | 7528.394 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.23319435 | 54.44 | 82.22 | 27.78 | 3292512.65 | 8.6722 | 8.846682 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 285531.69 | 285531.69 | 1.0000 | 10.26099510 | 8.933824 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 2.49770099 | 60.00 | 32.22 | 27.78 | 0.000 | 285531.69 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00764664 | 21.00 | 0.00764664 | 47.1821 | 199808.24 | 0.00 | 286455.29 | 286455.29 | 10.26099510 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60976.7 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 186444.550 | 186444.550 | 5.833719 | 0.00163110 | 4915.774 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.23319435 | 54.44 | 82.22 | 27.78 | 3292512.65 | 5.6627 | 5.776647 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 186444.55 | 186444.55 | 1.0000 | 6.70035174 | 5.833719 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 1.63093187 | 60.00 | 32.22 | 27.78 | 0.000 | 186444.55 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00763980 | 21.00 | 0.00763980 | 47.1406 | 130468.89 | 0.00 | 187047.16 | 187047.16 | 6.70035174 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60975.8 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 36943.347 | 36943.347 | 1.156280 | 0.00032320 | 973.910 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.23319435 | 54.44 | 82.22 | 27.78 | 3292512.65 | 1.1220 | 1.144623 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 36943.35 | 36835.06 | 1.0000 | 1.32805207 | 1.156280 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.32316355 | 60.00 | 32.22 | 27.78 | 0.000 | 36943.35 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00766183 | 21.00 | 0.00766183 | 47.2756 | 25848.53 | 0.00 | 37061.78 | 37061.78 | 1.32805207 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60966.7 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24056.733 | 24056.733 | 0.752957 | 0.00021046 | 634.185 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.23319435 | 54.44 | 82.22 | 27.78 | 3292512.65 | 0.7306 | 0.745354 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24056.73 | 24056.73 | 1.0000 | 0.86481371 | 0.752957 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.21043733 | 60.00 | 32.22 | 27.78 | 0.000 | 24056.73 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00765411 | 21.00 | 0.00765411 | 47.2287 | 16832.06 | 0.00 | 24133.82 | 24133.82 | 0.86481371 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60966.2 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 36450.768 | 36450.768 | 1.140847 | 0.00031889 | 960.930 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.23319435 | 54.44 | 82.22 | 27.78 | 3292512.65 | 1.1071 | 1.129361 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 36450.77 | 36450.77 | 1.0000 | 1.31032640 | 1.140847 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.31885469 | 60.00 | 32.22 | 27.78 | 0.000 | 36450.77 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00765745 | 21.00 | 0.00765745 | 47.2490 | 25504.13 | 0.00 | 36567.67 | 36567.67 | 1.31032640 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60967.1 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24011.031 | 24011.031 | 0.751530 | 0.00021006 | 632.979 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 28.23319435 | 54.44 | 82.22 | 27.78 | 3292512.65 | 0.7293 | 0.743938 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24011.03 | 24011.03 | 1.0000 | 0.86317385 | 0.751530 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.21003755 | 60.00 | 32.22 | 27.78 | 0.000 | 24011.03 | -26.20 | 0.00036134 | -26.20 | 0.00000000 | 0.0000 | 20.95 | 0.00765364 | 21.00 | 0.00765364 | 47.2259 | 16800.07 | 0.00 | 24087.97 | 24087.97 | 0.86317385 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60966.1 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 241066.665 | -999.000 | 10.272297 | 0.00689448 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.4024 | 1004.8586 | 1.1486 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.272297 | 11.79830604 | 4197.9300 | 999.8980 | 84.49803127 | 15.00 | 6.67 | 8.33 | 2954791.11 | 8.1585 | 8.158501 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 241066.66 | 180167.62 | 1.0000 | 11.79830604 | 10.272297 | 25.84 | 18.17 | 0.01052335 | 52784.0 | 10.87 | 10.87 | 0.00850000 | 32351.7 | 6.89377279 | 6.67 | 15.00 | 8.33 | 23334.479 | 217732.19 | 31.20 | 0.01536508 | 23.13 | 2.53819000 | 24.7091 | 24.00 | 0.00886572 | 24.00 | 0.00886572 | 45.4983 | 130645.94 | 0.00 | 248999.92 | 178453.23 | 11.79830604 | 25.84 | 18.68 | 0.01052335 | 52784.0 | 11.07 | 11.02 | 0.00815200 | 31679.3 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 109767.782 | 109767.782 | 3.081689 | 0.00096030 | 1657.368 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.272297 | 11.79830604 | 4197.9300 | 999.8980 | 28.23319435 | 54.44 | 82.22 | 27.78 | 3292512.65 | 3.3339 | 3.400956 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 109767.78 | 109767.78 | 1.0000 | 3.53949181 | 3.081689 | -18.06 | -18.06 | 0.00165800 | -14058.9 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 0.96019848 | 60.00 | 32.22 | 27.78 | 0.000 | 109767.78 | -26.20 | 0.00036134 | -26.20 | 2.53819000 | 82.3636 | 19.94 | 0.00771353 | 19.82 | 0.00765351 | 50.7770 | 35721.83 | 0.00 | 87212.25 | 87212.25 | 3.53949181 | 2.80 | -1.72 | 0.00165800 | 6968.8 | 27.25 | 11.12 | 0.00165800 | 31608.5 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2338855.113 | -999.000 | 96.221492 | 0.06689096 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8074 | 1004.8586 | 1.1486 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 96.221492 | 110.51575571 | 4197.9300 | 999.8980 | 84.49803127 | 15.00 | 6.67 | 8.33 | 2954791.11 | 79.1547 | 79.154669 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 2338855.11 | 1706949.29 | 1.0000 | 110.51575571 | 96.221492 | 26.01 | 18.39 | 0.01074121 | 53515.5 | 10.87 | 10.87 | 0.00850000 | 32352.5 | 66.88413659 | 6.67 | 15.00 | 8.33 | 218576.091 | 2120279.02 | 31.20 | 0.01536508 | 23.13 | 25.38195000 | 26.3787 | 24.00 | 0.00895233 | 24.00 | 0.00895233 | 45.9373 | 1194448.38 | 0.00 | 2414044.45 | 1692202.72 | 110.51575571 | 26.01 | 18.91 | 0.01074121 | 53515.5 | 11.07 | 11.01 | 0.00815087 | 31672.1 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 1118393.642 | 1118393.642 | 28.866448 | 0.00978420 | 16518.758 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 96.221492 | 110.51575571 | 4197.9300 | 999.8980 | 28.23319435 | 54.44 | 82.22 | 27.78 | 3292512.65 | 33.9678 | 34.651401 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 1118393.64 | 1118393.64 | 1.0000 | 33.15472671 | 28.866448 | -20.77 | -20.77 | 0.00123310 | -17833.7 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 9.78319737 | 60.00 | 32.22 | 27.78 | 0.000 | 1118393.64 | -26.20 | 0.00036134 | -26.20 | 25.38195000 | 87.9289 | 18.79 | 0.00758322 | 17.87 | 0.00754936 | 56.5936 | 395538.16 | 0.00 | 865117.70 | 865117.70 | 33.15472671 | 2.80 | -2.41 | 0.00123310 | 5903.9 | 28.71 | 11.30 | 0.00123310 | 31997.2 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 243051.900 | -999.000 | 10.454513 | 0.00695125 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.3272 | 1004.8586 | 1.1486 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.454513 | 12.00759180 | 4197.9300 | 999.8980 | 84.49803127 | 15.00 | 6.67 | 8.33 | 2954791.11 | 8.2257 | 8.225688 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 243051.90 | 182314.72 | 1.0000 | 12.00759180 | 10.454513 | 25.75 | 18.11 | 0.01048289 | 52593.0 | 10.87 | 10.87 | 0.00850000 | 32351.5 | 6.95054448 | 6.67 | 15.00 | 8.33 | 23748.401 | 219303.50 | 31.20 | 0.01536508 | 23.13 | 2.53819000 | 24.2784 | 24.00 | 0.00891418 | 24.00 | 0.00891418 | 45.7444 | 137017.46 | 0.00 | 251100.48 | 180543.53 | 12.00759180 | 25.75 | 18.62 | 0.01048289 | 52593.0 | 11.07 | 11.02 | 0.00815254 | 31681.2 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 112315.044 | 112315.044 | 3.136354 | 0.00098258 | 1693.429 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.454513 | 12.00759180 | 4197.9300 | 999.8980 | 28.23319435 | 54.44 | 82.22 | 27.78 | 3292512.65 | 3.4112 | 3.479878 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:00:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 112315.04 | 112315.04 | 1.0000 | 3.60227754 | 3.136354 | -18.23 | -18.23 | 0.00172688 | -14056.1 | 12.80 | 11.18 | 0.00800000 | 33059.8 | 0.98248077 | 60.00 | 32.22 | 27.78 | 0.000 | 112315.04 | -26.20 | 0.00036134 | -26.20 | 2.53819000 | 80.9280 | 15.60 | 0.00752125 | 15.60 | 0.00722844 | 62.6447 | 44925.80 | 0.00 | 89088.08 | 89088.08 | 3.60227754 | 2.80 | -1.61 | 0.00172688 | 7141.4 | 27.33 | 11.23 | 0.00172688 | 31872.4 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 131817.436 | -999.000 | 5.814901 | 0.00376996 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2568 | 1004.8586 | 1.1486 | CAV_BAS FAN | Fan:VariableVolume | 5.814901 | 6.67873830 | 4197.9300 | 999.8980 | 84.49803127 | 15.00 | 6.67 | 8.33 | 2954791.11 | 4.4611 | 4.461142 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 131817.44 | 98649.65 | 1.0000 | 6.67873830 | 5.814901 | 25.33 | 17.94 | 0.01044505 | 52065.0 | 10.85 | 10.85 | 0.00850000 | 32328.1 | 3.76957741 | 6.67 | 15.00 | 8.33 | 13365.326 | 118452.11 | 29.82 | 0.01536253 | 22.76 | 1.20015641 | 20.6393 | 24.00 | 0.00899023 | 24.00 | 0.00899023 | 46.1281 | 69010.78 | 0.00 | 136231.89 | 97592.66 | 6.67873830 | 25.33 | 18.45 | 0.01044505 | 52065.0 | 11.06 | 11.01 | 0.00815062 | 31667.1 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.185474 | 0.00087484 | 2622.251 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | CAV_BAS FAN | Fan:VariableVolume | 5.814901 | 6.67873830 | 4197.9300 | 999.8980 | 28.23319435 | 54.44 | 82.22 | 27.78 | 3292512.65 | 3.0372 | 3.098319 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.185474 | -5.41 | -9.38 | 0.00036134 | -4533.6 | 40.00 | 20.63 | 0.00800000 | 60796.0 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | -26.20 | 0.00036134 | -26.20 | 1.20015641 | 37.6759 | 0.00 | 0.00036134 | 22.85 | 0.00036134 | 2.0146 | 0.00 | 0.00 | 100071.45 | 100071.45 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.02 | 14.59 | 0.00000000 | 40238.9 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 504595.100 | 346136.205 | 25.729359 | 0.01235750 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8865 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 466065.44 | 457491.34 | 0.9236 | -999.0 | -999.0 | 28.51 | 17.55 | 0.00863202 | 50696.7 | 12.80 | 11.68 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 466065.44 | 31.20 | 0.01536508 | 23.13 | 0.33839277 | -999.0000 | 27.00 | 0.00854219 | 27.00 | 0.00854219 | 36.7051 | 371961.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10221.601 | 7029.207 | 0.525262 | 0.00025033 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1696 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | Sensible | 9427.66 | 9051.25 | 0.9223 | -999.0 | -999.0 | 27.99 | 17.50 | 0.00878431 | 50547.8 | 12.80 | 11.68 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9427.66 | 26.87 | 0.01535708 | 21.94 | 0.01563234 | -999.0000 | 27.00 | 0.00858270 | 27.00 | 0.00858270 | 36.8743 | 8742.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 98371.864 | 67591.538 | 5.047426 | 0.00240912 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1908 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | Sensible | 90753.64 | 86990.61 | 0.9226 | -999.0 | -999.0 | 27.99 | 17.51 | 0.00879573 | 50576.7 | 12.80 | 11.68 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 90753.64 | 26.87 | 0.01535708 | 21.94 | 0.15632344 | -999.0000 | 27.00 | 0.00858603 | 27.00 | 0.00858603 | 36.8885 | 84010.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9997.124 | 6871.468 | 0.513274 | 0.00024483 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1819 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | Sensible | 9221.95 | 8845.51 | 0.9225 | -999.0 | -999.0 | 27.99 | 17.50 | 0.00879095 | 50564.6 | 12.80 | 11.68 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9221.95 | 26.87 | 0.01535708 | 21.94 | 0.01563234 | -999.0000 | 27.00 | 0.00858469 | 27.00 | 0.00858469 | 36.8828 | 8543.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 504595.100 | 504595.100 | 25.729359 | 0.01235750 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 504595.10 | 504595.10 | 1.0000 | 29.55160517 | 25.729359 | -26.20 | -26.20 | 0.00036134 | -25440.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 504595.10 | -26.20 | 0.00036134 | -26.20 | 0.33839277 | 1.3152 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 36.5206 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10221.601 | 10221.601 | 0.525262 | 0.00025033 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 10221.60 | 10221.60 | 1.0000 | 0.60329254 | 0.525262 | -26.20 | -26.20 | 0.00036134 | -25440.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10221.60 | -26.20 | 0.00036134 | -26.20 | 0.01563234 | 2.9761 | 0.00 | 0.00099659 | 25.14 | 0.00099659 | 4.8386 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 98371.864 | 98371.864 | 5.047426 | 0.00240912 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 98371.86 | 98371.86 | 1.0000 | 5.79725004 | 5.047426 | -26.20 | -26.20 | 0.00036134 | -25440.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 98371.86 | -26.20 | 0.00036134 | -26.20 | 0.15632344 | 3.0971 | 0.00 | 0.00099661 | 23.56 | 0.00099661 | 5.3186 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9997.124 | 9997.124 | 0.513274 | 0.00024483 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1486 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9997.12 | 9997.12 | 1.0000 | 0.58952387 | 0.513274 | -26.20 | -26.20 | 0.00036134 | -25440.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9997.12 | -26.20 | 0.00036134 | -26.20 | 0.01563234 | 3.0456 | 0.00 | 0.00099595 | 22.13 | 0.00099595 | 5.7952 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25854.499 | 25854.499 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 25.729359 | 29.55160517 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 25854.50 | 25854.50 | 1.0000 | 29.55160517 | 25.729359 | -0.34 | -0.34 | 0.00839296 | 20638.7 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25854.50 | -26.20 | 0.00036134 | -26.20 | 0.33839277 | 1.3152 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 36.5206 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1194.371 | 1194.371 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.525262 | 0.60329254 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1194.37 | 1194.37 | 1.0000 | 0.60329254 | 0.525262 | -0.78 | -5.20 | 0.00097768 | 1660.2 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1194.37 | -26.20 | 0.00036134 | -26.20 | 0.01563234 | 2.9761 | 0.00 | 0.00099659 | 25.14 | 0.00099659 | 4.8386 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11943.707 | 11943.707 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 5.047426 | 5.79725004 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 11943.71 | 11943.71 | 1.0000 | 5.79725004 | 5.047426 | -0.81 | -5.22 | 0.00097693 | 1626.4 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11943.71 | -26.20 | 0.00036134 | -26.20 | 0.15632344 | 3.0971 | 0.00 | 0.00099661 | 23.56 | 0.00099661 | 5.3186 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1194.371 | 1194.371 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1486 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.513274 | 0.58952387 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1194.37 | 1194.37 | 1.0000 | 0.58952387 | 0.513274 | -0.80 | -5.22 | 0.00097662 | 1639.2 | 40.00 | 20.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1194.37 | -26.20 | 0.00036134 | -26.20 | 0.01563234 | 3.0456 | 0.00 | 0.00099595 | 22.13 | 0.00099595 | 5.7952 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:51
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 10.27 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 96.22 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 10.45 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 5.81 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 25.73 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2851.50 | 1838.17 | 630.17 |
CORE_BOTTOM | 2463.33 | 1722.50 | 12.67 |
CORE_MID | 2257.50 | 3124.00 | 339.00 |
CORE_TOP | 2944.33 | 3716.83 | 1226.83 |
PERIMETER_BOT_ZN_3 | 2894.17 | 3406.17 | 970.33 |
PERIMETER_BOT_ZN_2 | 3033.83 | 3496.17 | 1107.33 |
PERIMETER_BOT_ZN_1 | 3162.67 | 2984.50 | 960.00 |
PERIMETER_BOT_ZN_4 | 3059.33 | 2819.33 | 713.33 |
PERIMETER_MID_ZN_3 | 3810.50 | 3932.83 | 2159.50 |
PERIMETER_MID_ZN_2 | 3164.17 | 3409.50 | 1828.67 |
PERIMETER_MID_ZN_1 | 3503.67 | 3389.50 | 1535.17 |
PERIMETER_MID_ZN_4 | 3615.67 | 3882.17 | 1874.67 |
PERIMETER_TOP_ZN_3 | 4106.00 | 4169.67 | 2626.67 |
PERIMETER_TOP_ZN_2 | 4004.17 | 4074.33 | 2427.83 |
PERIMETER_TOP_ZN_1 | 3697.50 | 3679.83 | 1922.17 |
PERIMETER_TOP_ZN_4 | 3853.33 | 4078.00 | 2274.67 |
DATACENTER_BOT_ZN_6 | 5762.50 | 1022.83 | 1022.83 |
DATACENTER_MID_ZN_6 | 4886.50 | 552.50 | 282.83 |
DATACENTER_TOP_ZN_6 | 4376.17 | 984.17 | 468.83 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5535.50 | 5535.50 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 1455.00 | 0.00 | 825.50 |
CORE_BOTTOM | 0.00 | 3.67 | 0.00 | 0.00 |
CORE_MID | 1.83 | 0.00 | 0.50 | 0.00 |
CORE_TOP | 26.00 | 0.00 | 5.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 9.50 | 9.17 | 1.67 | 5.50 |
PERIMETER_BOT_ZN_2 | 8.33 | 29.33 | 0.00 | 29.17 |
PERIMETER_BOT_ZN_1 | 9.67 | 45.50 | 0.17 | 43.83 |
PERIMETER_BOT_ZN_4 | 3.83 | 87.67 | 0.00 | 41.50 |
PERIMETER_MID_ZN_3 | 183.17 | 3.00 | 70.33 | 1.67 |
PERIMETER_MID_ZN_2 | 86.67 | 28.83 | 8.17 | 28.67 |
PERIMETER_MID_ZN_1 | 65.00 | 53.00 | 5.00 | 51.17 |
PERIMETER_MID_ZN_4 | 66.00 | 37.17 | 6.67 | 20.17 |
PERIMETER_TOP_ZN_3 | 377.83 | 6.33 | 148.50 | 3.83 |
PERIMETER_TOP_ZN_2 | 208.33 | 31.33 | 39.83 | 30.17 |
PERIMETER_TOP_ZN_1 | 176.17 | 38.00 | 27.17 | 34.83 |
PERIMETER_TOP_ZN_4 | 155.00 | 37.50 | 28.00 | 20.17 |
DATACENTER_BOT_ZN_6 | 0.00 | 1.83 | 0.00 | 1.83 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 214.67 | 0.00 | 191.50 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 439.00 | 1707.00 | 162.67 | 1041.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:51
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.91 | 149.60 | 6779.02 | 0.979 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.60 | 134.35 | 6849.35 | 0.948 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.60 | 134.35 | 6849.35 | 0.714 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.60 | 134.35 | 6849.35 | 0.688 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.98 | 16.87 | 860.00 | 0.932 | 0.029 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.50 | 10.87 | 554.22 | 1.525 | 0.030 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.98 | 16.87 | 860.02 | 1.397 | 0.029 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.50 | 10.87 | 554.22 | 1.976 | 0.030 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.98 | 16.87 | 860.00 | 0.775 | 0.067 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.93 | 10.87 | 554.22 | 1.413 | 0.073 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.98 | 16.87 | 860.02 | 1.304 | 0.067 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.50 | 10.87 | 554.22 | 1.532 | 0.069 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.98 | 16.87 | 860.00 | 0.814 | 0.083 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.50 | 10.87 | 554.22 | 1.511 | 0.086 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.98 | 16.87 | 860.02 | 1.303 | 0.083 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.50 | 10.87 | 554.22 | 1.574 | 0.086 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.46 | 42.18 | 1911.37 | 26.265 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.91 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.60 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.60 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.60 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.98 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.50 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.98 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.50 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.98 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.93 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.98 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.50 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.98 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.50 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.98 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.50 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.46 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:25:51
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 61.91 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.60 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.60 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.60 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.98 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.50 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.98 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.50 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.98 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.93 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.98 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.50 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.98 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.50 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.98 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.50 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.46 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1026.00 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 38556954.62 | 0.00 | 38556954.62 | 0.00 | 38556954.62 | 37848132.68 | 4838.79 | 1325.20 | 2596.01 | 0.00 |
CORE_BOTTOM | 40486122.10 | 0.00 | 40486122.10 | 0.00 | 40486122.10 | 33990283.35 | 4819.48 | 53.96 | 3886.56 | 453.94 |
CORE_MID | 0.30E+09 | 0.00 | 0.30E+09 | 0.00 | 0.30E+09 | 0.34E+09 | 6279.88 | 25.09 | 2455.04 | 454.45 |
CORE_TOP | 28278385.62 | 0.00 | 28278385.62 | 0.00 | 28278385.62 | 33990283.35 | 6505.12 | 27.22 | 2227.66 | 420.05 |
PERIMETER_BOT_ZN_3 | 4988453.50 | 0.00 | 4988453.50 | 292645.21 | 5281098.71 | 4267819.30 | 5566.82 | 41.09 | 3152.09 | 453.94 |
PERIMETER_BOT_ZN_2 | 5306723.86 | 0.00 | 5306723.86 | 195096.68 | 5501820.54 | 2750345.05 | 3514.59 | 5.98 | 5239.43 | 453.94 |
PERIMETER_BOT_ZN_1 | 7417531.45 | 0.00 | 7417531.45 | 292645.21 | 7710176.66 | 4267912.63 | 3747.56 | 76.61 | 4935.82 | 453.94 |
PERIMETER_BOT_ZN_4 | 6878364.67 | 0.00 | 6878364.67 | 195096.68 | 7073461.34 | 2750345.05 | 3469.43 | 4.95 | 5285.62 | 453.94 |
PERIMETER_MID_ZN_3 | 40311663.32 | 0.00 | 40311663.32 | 686338.17 | 40998001.49 | 42678193.03 | 5774.02 | 39.50 | 2946.48 | 454.45 |
PERIMETER_MID_ZN_2 | 50676545.22 | 0.00 | 50676545.22 | 457558.47 | 51134103.68 | 27503450.52 | 3885.26 | 1.61 | 4873.13 | 1363.45 |
PERIMETER_MID_ZN_1 | 67184281.79 | 0.00 | 67184281.79 | 686338.17 | 67870619.96 | 42679126.28 | 3957.11 | 4.15 | 4798.73 | 454.45 |
PERIMETER_MID_ZN_4 | 51614408.65 | 0.00 | 51614408.65 | 457558.47 | 52071967.11 | 27503450.52 | 3879.41 | 2.56 | 4878.02 | 454.45 |
PERIMETER_TOP_ZN_3 | 4198487.67 | 0.00 | 4198487.67 | 852165.91 | 5050653.58 | 4267819.30 | 4608.04 | 938.96 | 3213.00 | 420.01 |
PERIMETER_TOP_ZN_2 | 5013244.96 | 0.00 | 5013244.96 | 568110.22 | 5581355.17 | 2750345.05 | 3976.28 | 2.40 | 4781.32 | 420.01 |
PERIMETER_TOP_ZN_1 | 6674568.26 | 0.00 | 6674568.26 | 852165.91 | 7526734.17 | 4267912.63 | 4011.45 | 2.91 | 4745.64 | 420.01 |
PERIMETER_TOP_ZN_4 | 5258982.25 | 0.00 | 5258982.25 | 568110.22 | 5827092.46 | 2750345.05 | 3968.92 | 2.05 | 4789.03 | 420.01 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.42E+09 | 0.00 | 0.42E+09 | 0.00 | 0.42E+09 | 10671554.30 | 48.67 | 149.33 | 8562.00 | 2805.50 |
Total Facility | 0.57E+10 | 0.00 | 0.57E+10 | 26693968.68 | 0.57E+10 | 0.50E+10 | 7105.96 | 4381.40 | 8713.35 | 3714.81 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.8022 | 0.0000 | 1.8022 | 0.0000 | 1.8022 | 1.2002 | 2021.79 | 1325.20 | 2596.01 |
CORE_BOTTOM | 1.7615 | 0.0000 | 1.7615 | 0.0000 | 1.7615 | 1.0778 | 2366.23 | 52.30 | 3524.47 |
CORE_MID | 13.2913 | 0.0000 | 13.2913 | 0.0000 | 13.2913 | 10.7782 | 3579.27 | 24.78 | 2338.95 |
CORE_TOP | 1.2814 | 0.0000 | 1.2814 | 0.0000 | 1.2814 | 1.0778 | 3782.27 | 26.88 | 2133.86 |
PERIMETER_BOT_ZN_3 | 0.2176 | 0.0000 | 0.2176 | 0.0067 | 0.2243 | 0.1353 | 3110.79 | 39.27 | 2792.94 |
PERIMETER_BOT_ZN_2 | 0.2299 | 0.0000 | 0.2299 | 0.0045 | 0.2344 | 0.0872 | 1097.86 | 5.25 | 4839.88 |
PERIMETER_BOT_ZN_1 | 0.3264 | 0.0000 | 0.3264 | 0.0067 | 0.3331 | 0.1353 | 1312.80 | 74.76 | 4555.44 |
PERIMETER_BOT_ZN_4 | 0.2974 | 0.0000 | 0.2974 | 0.0045 | 0.3019 | 0.0872 | 1062.49 | 3.81 | 4876.69 |
PERIMETER_MID_ZN_3 | 1.8146 | 0.0000 | 1.8146 | 0.0158 | 1.8304 | 1.3533 | 3074.66 | 39.02 | 2829.32 |
PERIMETER_MID_ZN_2 | 2.1330 | 0.0000 | 2.1330 | 0.0111 | 2.1442 | 0.8721 | 1213.14 | 0.77 | 3820.08 |
PERIMETER_MID_ZN_1 | 3.0497 | 0.0000 | 3.0497 | 0.0158 | 3.0655 | 1.3533 | 1263.02 | 3.97 | 4676.01 |
PERIMETER_MID_ZN_4 | 2.3117 | 0.0000 | 2.3117 | 0.0105 | 2.3222 | 0.8721 | 1208.57 | 1.67 | 4732.76 |
PERIMETER_TOP_ZN_3 | 0.1907 | 0.0000 | 0.1907 | 0.0196 | 0.2103 | 0.1353 | 1887.09 | 938.81 | 3117.10 |
PERIMETER_TOP_ZN_2 | 0.2280 | 0.0000 | 0.2280 | 0.0131 | 0.2411 | 0.0872 | 1269.67 | 1.60 | 4671.73 |
PERIMETER_TOP_ZN_1 | 0.3048 | 0.0000 | 0.3048 | 0.0196 | 0.3244 | 0.1353 | 1293.72 | 2.49 | 4646.79 |
PERIMETER_TOP_ZN_4 | 0.2376 | 0.0000 | 0.2376 | 0.0131 | 0.2507 | 0.0872 | 1264.83 | 1.27 | 4676.90 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 13.4635 | 0.0000 | 13.4635 | 0.0000 | 13.4635 | 0.3384 | 37.17 | 149.33 | 5756.50 |
Total Facility | 247.5091 | 0.0000 | 247.5091 | 0.6198 | 248.1289 | 158.4706 | 4288.96 | 4371.09 | 5907.54 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 85854404.18 | 0.00 | 85854404.18 | 48026705.38 | 3542.61 | 4.95 | 5212.43 | 453.94 |
VAV_MID WITH REHEAT | 0.67E+09 | 0.00 | 0.67E+09 | 0.48E+09 | 3943.52 | 7.69 | 4808.79 | 454.45 |
VAV_TOP WITH REHEAT | 65198767.35 | 0.00 | 65198767.35 | 48026705.38 | 4001.18 | 1.70 | 4757.12 | 419.63 |
CAV_BAS | 50863589.82 | 0.00 | 50863589.82 | 37848132.68 | 4807.69 | 0.08 | 3952.22 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.55E+09 | 0.00 | 0.55E+09 | 10671554.30 | 48.67 | 0.00 | 8711.33 | 2805.50 |
AIRLOOP DATACENTER BOT | 322270.54 | 0.00 | 322270.54 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3222705.41 | 0.00 | 3222705.41 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 322270.54 | 0.00 | 322270.54 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.7373 | 0.0000 | 3.7373 | 1.5229 | 1119.57 | 4.13 | 4819.30 |
VAV_MID WITH REHEAT | 30.0123 | 0.0000 | 30.0123 | 15.2292 | 1249.85 | 6.02 | 4687.12 |
VAV_TOP WITH REHEAT | 2.9582 | 0.0000 | 2.9582 | 1.5229 | 1285.53 | 1.49 | 4655.98 |
CAV_BAS | 2.3774 | 0.0000 | 2.3774 | 1.2002 | 1990.69 | 0.08 | 3952.22 |
AIRLOOP DATACENTER BASEMENT | 17.7608 | 0.0000 | 17.7608 | 0.3384 | 37.17 | 0.00 | 5905.83 |
AIRLOOP DATACENTER BOT | 0.0151 | 0.0000 | 0.0151 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1506 | 0.0000 | 0.1506 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0151 | 0.0000 | 0.0151 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 1.62 | 3476.03 | 0.00 | 0.00 | 0.00 | 1904.35 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.10 | 3214.22 | 0.00 | 0.00 | 0.00 | 2143.04 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.00 | 2949.81 | 0.00 | 0.00 | 0.00 | 2364.19 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 1306.91 | 2611.47 | 0.00 | 56.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 149.33 | 8562.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 20.7782 | 5.8851 | 0.0000 | 0.0000 | 0.0000 | 2.3136 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 47.2501 | 0.0000 | 0.0000 | 0.0000 | 22.3960 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 4.8753 | 0.0000 | 0.0000 | 0.0000 | 2.2192 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.5843 | 4.5937 | 0.0000 | 1.1712 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4474 | 18.3263 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0206 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2063 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0206 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:51
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1498 |
Defaulted Fields | 1184 |
Fields with Defaults | 3937 |
Autosized Fields | 337 |
Autosizable Fields | 416 |
Autocalculated Fields | 227 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:25:51
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 27827.95 | 298926.66 | 13-MAY-05:00 | 2275966.21 | 04-AUG-07:20 |
Electricity:Building | 17897.48 | 217189.06 | 07-MAY-17:20 | 1104084.83 | 01-DEC-16:30 |
Electricity:Zone:BASEMENT | 640.57 | 14055.89 | 01-JAN-00:10 | 32859.63 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 17897.48 | 217189.06 | 07-MAY-17:20 | 1104084.83 | 01-DEC-16:30 |
InteriorLights:Electricity | 3221.08 | 9932.90 | 09-APR-17:20 | 325713.14 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:BASEMENT | 216.17 | 598.35 | 01-JAN-00:10 | 19402.09 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3221.08 | 9932.90 | 09-APR-17:20 | 325713.14 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity | 3221.08 | 9932.90 | 09-APR-17:20 | 325713.14 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 216.17 | 598.35 | 01-JAN-00:10 | 19402.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3221.08 | 9932.90 | 09-APR-17:20 | 325713.14 | 02-JAN-16:40 |
Electricity:Zone:CORE_BOTTOM | 483.75 | 4990.59 | 01-JAN-00:10 | 34631.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4837.49 | 49905.77 | 01-JAN-00:10 | 346310.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1941.37 | 5373.60 | 01-JAN-00:10 | 174244.37 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1941.37 | 5373.60 | 01-JAN-00:10 | 174244.37 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 483.75 | 4990.58 | 01-JAN-00:10 | 34631.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 50.49 | 617.00 | 09-APR-17:10 | 4348.36 | 02-JAN-16:20 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 14.13 | 57.83 | 01-JAN-10:10 | 2187.81 | 02-JAN-16:20 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 14.13 | 57.83 | 01-JAN-10:10 | 2187.81 | 02-JAN-16:20 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 32.45 | 397.62 | 09-APR-17:10 | 2802.25 | 02-JAN-16:20 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 9.02 | 37.27 | 01-JAN-09:40 | 1409.91 | 02-JAN-16:20 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 9.02 | 37.27 | 01-JAN-09:40 | 1409.91 | 02-JAN-16:20 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 50.21 | 617.01 | 26-MAR-17:10 | 4348.44 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 13.84 | 57.83 | 01-JAN-09:40 | 2187.86 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 13.84 | 57.83 | 01-JAN-09:40 | 2187.86 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 32.42 | 397.61 | 12-MAR-17:10 | 2802.24 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 8.98 | 37.27 | 01-JAN-10:00 | 1409.91 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 8.98 | 37.27 | 01-JAN-10:00 | 1409.91 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 504.57 | 6169.98 | 26-MAR-17:10 | 43483.64 | 02-JAN-16:20 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 140.92 | 578.27 | 01-JAN-10:00 | 21878.12 | 02-JAN-16:20 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 140.92 | 578.27 | 01-JAN-10:00 | 21878.12 | 02-JAN-16:20 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 324.39 | 3976.17 | 09-APR-17:10 | 28022.51 | 02-JAN-16:20 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 90.03 | 372.66 | 01-JAN-09:40 | 14099.09 | 02-JAN-16:20 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 90.03 | 372.66 | 01-JAN-09:40 | 14099.09 | 02-JAN-16:20 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 501.92 | 6170.07 | 26-MAR-17:10 | 43484.45 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 138.26 | 578.28 | 01-JAN-09:40 | 21878.60 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 138.26 | 578.28 | 01-JAN-09:40 | 21878.60 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 324.04 | 3976.14 | 12-MAR-17:10 | 28022.42 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 89.69 | 372.66 | 01-JAN-10:00 | 14099.09 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 89.69 | 372.66 | 01-JAN-10:00 | 14099.09 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 50.46 | 617.00 | 26-MAR-17:10 | 4348.36 | 02-JAN-16:20 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 14.09 | 57.83 | 01-JAN-10:00 | 2187.81 | 02-JAN-16:20 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 14.09 | 57.83 | 01-JAN-10:00 | 2187.81 | 02-JAN-16:20 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 32.44 | 397.62 | 09-APR-17:10 | 2802.25 | 02-JAN-16:20 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 9.00 | 37.27 | 01-JAN-09:40 | 1409.91 | 02-JAN-16:20 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 9.00 | 37.27 | 01-JAN-09:40 | 1409.91 | 02-JAN-16:20 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 50.19 | 617.01 | 26-MAR-17:10 | 4348.44 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 13.83 | 57.83 | 01-JAN-09:40 | 2187.86 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 13.83 | 57.83 | 01-JAN-09:40 | 2187.86 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 32.40 | 397.61 | 12-MAR-17:10 | 2802.24 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 8.97 | 37.27 | 01-JAN-10:00 | 1409.91 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 8.97 | 37.27 | 01-JAN-10:00 | 1409.91 | 02-JAN-16:40 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7557.51 | 95212.03 | 01-JAN-00:10 | 385103.08 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 62.65 | 303.90 | 01-JAN-00:10 | 5470.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 62.65 | 303.90 | 01-JAN-00:10 | 5470.56 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 159.04 | 1973.61 | 01-JAN-00:10 | 8244.54 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1590.36 | 19736.13 | 01-JAN-00:10 | 82445.36 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 51.55 | 250.08 | 01-JAN-00:10 | 4501.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 51.55 | 250.08 | 01-JAN-00:10 | 4501.14 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 159.04 | 1973.61 | 01-JAN-00:10 | 8244.54 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 1940.76 | 3932.32 | 31-JAN-03:50 | 659223.98 | 04-AUG-07:20 |
HeatRejection:Electricity | 528.25 | 36.11 | 31-JAN-07:20 | 92515.43 | 15-APR-13:00 |
General:HeatRejection:Electricity | 528.25 | 36.11 | 31-JAN-07:20 | 92515.43 | 15-APR-13:00 |
Electricity:HVAC | 5124.41 | 55937.83 | 14-MAY-06:00 | 499463.56 | 04-AUG-15:20 |
ExteriorEquipment:Electricity | 2566.60 | 20217.42 | 01-JAN-00:10 | 233439.18 | 17-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 55.01 | 979.82 | 01-JAN-00:10 | 3454.84 | 01-DEC-16:40 |
ElectricityPurchased:Facility | 27827.95 | 298926.66 | 13-MAY-05:00 | 2275966.21 | 04-AUG-07:20 |
ElectricityPurchased:Plant | 27827.95 | 298926.66 | 13-MAY-05:00 | 2275966.21 | 04-AUG-07:20 |
Cogeneration:ElectricityPurchased | 27827.95 | 298926.66 | 13-MAY-05:00 | 2275966.21 | 04-AUG-07:20 |
General:Cogeneration:ElectricityPurchased | 27827.95 | 298926.66 | 13-MAY-05:00 | 2275966.21 | 04-AUG-07:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 27827.95 | 298926.66 | 13-MAY-05:00 | 2275966.21 | 04-AUG-07:20 |
ElectricityNet:Plant | 27827.95 | 298926.66 | 13-MAY-05:00 | 2275966.21 | 04-AUG-07:20 |
Cogeneration:ElectricityNet | 27827.95 | 298926.66 | 13-MAY-05:00 | 2275966.21 | 04-AUG-07:20 |
General:Cogeneration:ElectricityNet | 27827.95 | 298926.66 | 13-MAY-05:00 | 2275966.21 | 04-AUG-07:20 |
Fans:Electricity | 2534.90 | 49251.00 | 01-JAN-18:40 | 287238.60 | 02-AUG-15:20 |
General:Fans:Electricity | 2534.90 | 49251.00 | 01-JAN-18:40 | 287238.60 | 02-AUG-15:20 |
ExteriorLights:Electricity | 353.71 | 0.00 | 01-JAN-08:00 | 40855.88 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 353.71 | 0.00 | 01-JAN-08:00 | 40855.88 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 2505.76 | 19200.00 | 01-JAN-00:10 | 229608.34 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 44.62 | 0.00 | 01-JAN-00:10 | 5613.48 | 02-JAN-07:10 |
General:HeatRecovery:Electricity | 44.62 | 0.00 | 01-JAN-00:10 | 5613.48 | 02-JAN-07:10 |
Cooling:Electricity | 1535.18 | 1583.31 | 30-JAN-08:10 | 655208.40 | 04-AUG-07:20 |
General:Cooling:Electricity | 1535.18 | 1583.31 | 30-JAN-08:10 | 655208.40 | 04-AUG-07:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1517.79 | 0.00 | 19-MAR-11:40 | 100000.00 | 20-FEB-15:10 |
General:Humidifier:Electricity | 1517.79 | 0.00 | 19-MAR-11:40 | 100000.00 | 20-FEB-15:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 484.61 | 0.00 | 01-JAN-00:10 | 60476.62 | 21-FEB-13:00 |
Water Heater:WaterSystems:Electricity | 484.61 | 0.00 | 01-JAN-00:10 | 60476.62 | 21-FEB-13:00 |
Pumps:Electricity | 364.82 | 3892.52 | 01-JAN-00:40 | 56095.39 | 04-AUG-07:20 |
General:Pumps:Electricity | 364.82 | 3892.52 | 01-JAN-00:40 | 56095.39 | 04-AUG-07:20 |
WIRED_LTG_ELECTRICITY | 90.51 | 0.00 | 01-JAN-00:10 | 9152.54 | 02-JAN-16:50 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 2558.45 | 0.00 | 01-JAN-00:40 | 2470555.89 | 30-JAN-07:30 |
NaturalGas:Plant | 2558.45 | 0.00 | 01-JAN-00:40 | 2470555.89 | 30-JAN-07:30 |
Heating:NaturalGas | 2558.45 | 0.00 | 01-JAN-00:40 | 2470555.89 | 30-JAN-07:30 |
Boiler:Heating:NaturalGas | 2558.45 | 0.00 | 01-JAN-00:40 | 2470555.89 | 30-JAN-07:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 9393.72 | 3435.13 | 30-JAN-08:10 | 3835359.21 | 04-AUG-07:20 |
PlantLoopCoolingDemand:HVAC | 9393.72 | 3435.13 | 30-JAN-08:10 | 3835359.21 | 04-AUG-07:20 |
CoolingCoils:PlantLoopCoolingDemand | 9393.72 | 3435.13 | 30-JAN-08:10 | 3835359.21 | 04-AUG-07:20 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 6557.26 | 0.00 | 19-MAR-23:10 | 0.00 | 01-SEP-15:50 |
Water:HVAC | 564.62 | 0.00 | 19-MAR-11:40 | 0.00 | 01-MAR-04:10 |
Humidifier:Water | 564.62 | 0.00 | 19-MAR-11:40 | 0.00 | 01-MAR-04:10 |
General:Humidifier:Water | 564.62 | 0.00 | 19-MAR-11:40 | 0.00 | 01-MAR-04:10 |
MainsWater:Facility | 6557.26 | 0.00 | 19-MAR-23:10 | 0.00 | 01-SEP-15:50 |
MainsWater:HVAC | 564.62 | 0.00 | 19-MAR-11:40 | 0.00 | 01-MAR-04:10 |
Humidifier:MainsWater | 564.62 | 0.00 | 19-MAR-11:40 | 0.00 | 01-MAR-04:10 |
General:Humidifier:MainsWater | 564.62 | 0.00 | 19-MAR-11:40 | 0.00 | 01-MAR-04:10 |
Water:Plant | 5992.64 | 0.00 | 01-JAN-00:10 | 0.00 | 01-SEP-15:50 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 5992.64 | 0.00 | 01-JAN-00:10 | 0.00 | 01-SEP-15:50 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 3712.47 | 0.00 | 01-JAN-00:10 | 0.00 | 01-SEP-15:50 |
General:HeatRejection:Water | 3712.47 | 0.00 | 01-JAN-00:10 | 0.00 | 01-SEP-15:50 |
HeatRejection:MainsWater | 3712.47 | 0.00 | 01-JAN-00:10 | 0.00 | 01-SEP-15:50 |
General:HeatRejection:MainsWater | 3712.47 | 0.00 | 01-JAN-00:10 | 0.00 | 01-SEP-15:50 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 49763.11 | 94743.52 | 09-JAN-04:50 | 14425888.07 | 04-AUG-07:20 |
EnergyTransfer:Building | 18958.28 | 88762.48 | 14-JAN-18:10 | 1696937.50 | 29-AUG-15:10 |
EnergyTransfer:Zone:BASEMENT | 576.93 | 0.00 | 01-JAN-00:10 | 105860.79 | 05-SEP-06:10 |
Heating:EnergyTransfer | 1250.78 | 0.00 | 01-FEB-22:10 | 1315870.02 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 468.99 | 21-JUN-06:30 |
General:Heating:EnergyTransfer | 1250.78 | 0.00 | 01-FEB-22:10 | 1315870.02 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 468.99 | 21-JUN-06:30 |
Cooling:EnergyTransfer | 17707.50 | 84716.32 | 30-JAN-06:00 | 1696937.50 | 29-AUG-15:10 |
Cooling:EnergyTransfer:Zone:BASEMENT | 576.93 | 0.00 | 01-JAN-00:10 | 105860.79 | 05-SEP-06:10 |
General:Cooling:EnergyTransfer | 17707.50 | 84716.32 | 30-JAN-06:00 | 1696937.50 | 29-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 576.93 | 0.00 | 01-JAN-00:10 | 105860.79 | 05-SEP-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 610.89 | 0.00 | 01-JAN-00:10 | 65387.78 | 05-JUL-07:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 610.89 | 0.00 | 01-JAN-00:10 | 65387.78 | 05-JUL-07:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 610.89 | 0.00 | 01-JAN-00:10 | 65387.78 | 05-JUL-07:20 |
EnergyTransfer:Zone:CORE_MID | 4187.77 | 0.00 | 01-JAN-00:40 | 489362.85 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 22.24 | 0.00 | 01-JAN-00:10 | 489362.85 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 22.24 | 0.00 | 01-JAN-00:10 | 489362.85 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4165.54 | 0.00 | 01-JAN-00:40 | 431298.74 | 30-JUN-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4165.54 | 0.00 | 01-JAN-00:40 | 431298.74 | 30-JUN-13:10 |
EnergyTransfer:Zone:CORE_TOP | 383.77 | 0.00 | 01-JAN-00:40 | 73097.07 | 30-JAN-05:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 27.40 | 0.00 | 01-JAN-00:40 | 73097.07 | 30-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 27.40 | 0.00 | 01-JAN-00:40 | 73097.07 | 30-JAN-05:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 356.37 | 0.00 | 01-JAN-00:20 | 50679.94 | 26-JUN-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 356.37 | 0.00 | 01-JAN-00:20 | 50679.94 | 26-JUN-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 70.32 | 0.00 | 01-JAN-00:10 | 12272.61 | 04-AUG-15:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 4.54 | 0.00 | 01-JAN-00:10 | 11837.32 | 30-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 4.54 | 0.00 | 01-JAN-00:10 | 11837.32 | 30-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 65.78 | 0.00 | 01-JAN-00:10 | 12272.61 | 04-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 65.78 | 0.00 | 01-JAN-00:10 | 12272.61 | 04-AUG-15:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 69.06 | 0.00 | 01-JAN-00:10 | 16680.58 | 05-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 3.04 | 0.00 | 01-JAN-00:10 | 8933.77 | 02-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 3.04 | 0.00 | 01-JAN-00:10 | 8933.77 | 02-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 66.02 | 0.00 | 01-JAN-00:10 | 16680.58 | 05-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 66.02 | 0.00 | 01-JAN-00:10 | 16680.58 | 05-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 110.24 | 0.00 | 01-JAN-00:10 | 22170.87 | 07-SEP-13:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 4.32 | 0.00 | 01-JAN-00:10 | 13566.69 | 19-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 4.32 | 0.00 | 01-JAN-00:10 | 13566.69 | 19-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 105.92 | 0.00 | 01-JAN-00:10 | 22170.87 | 07-SEP-13:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 105.92 | 0.00 | 01-JAN-00:10 | 22170.87 | 07-SEP-13:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 98.98 | 0.00 | 01-JAN-00:10 | 20173.65 | 02-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.99 | 0.00 | 01-JAN-00:10 | 6712.29 | 19-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.99 | 0.00 | 01-JAN-00:10 | 6712.29 | 19-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 97.99 | 0.00 | 01-JAN-00:10 | 20173.65 | 02-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 97.99 | 0.00 | 01-JAN-00:10 | 20173.65 | 02-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 717.19 | 0.00 | 01-JAN-00:40 | 136344.25 | 30-JAN-04:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 289.32 | 0.00 | 01-JAN-00:40 | 136344.25 | 30-JAN-04:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 289.32 | 0.00 | 01-JAN-00:40 | 136344.25 | 30-JAN-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 427.87 | 0.00 | 01-JAN-00:20 | 104563.89 | 26-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 427.87 | 0.00 | 01-JAN-00:20 | 104563.89 | 26-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 701.53 | 0.00 | 01-JAN-00:40 | 164585.81 | 02-AUG-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 165.40 | 0.00 | 01-JAN-00:40 | 159732.90 | 30-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 165.40 | 0.00 | 01-JAN-00:40 | 159732.90 | 30-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 536.12 | 0.00 | 01-JAN-00:20 | 164585.81 | 02-AUG-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 536.12 | 0.00 | 01-JAN-00:20 | 164585.81 | 02-AUG-08:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1059.15 | 0.00 | 01-JAN-00:40 | 228947.34 | 07-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 163.94 | 0.00 | 01-JAN-00:40 | 205625.03 | 09-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 163.94 | 0.00 | 01-JAN-00:40 | 205625.03 | 09-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 895.21 | 0.00 | 01-JAN-00:20 | 228947.34 | 07-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 895.21 | 0.00 | 01-JAN-00:20 | 228947.34 | 07-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 722.46 | 0.00 | 01-JAN-00:40 | 180367.06 | 25-JUN-17:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 133.92 | 0.00 | 01-JAN-00:40 | 151531.34 | 09-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 133.92 | 0.00 | 01-JAN-00:40 | 151531.34 | 09-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 588.55 | 0.00 | 01-JAN-00:20 | 180367.06 | 25-JUN-17:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 588.55 | 0.00 | 01-JAN-00:20 | 180367.06 | 25-JUN-17:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 94.53 | 0.00 | 01-JAN-00:40 | 17317.53 | 30-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 54.35 | 0.00 | 01-JAN-00:40 | 17317.53 | 30-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 54.35 | 0.00 | 01-JAN-00:40 | 17317.53 | 30-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 40.18 | 0.00 | 01-JAN-00:10 | 11591.46 | 26-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 40.18 | 0.00 | 01-JAN-00:10 | 11591.46 | 26-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 81.55 | 0.00 | 01-JAN-00:40 | 19320.03 | 09-DEC-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 31.32 | 0.00 | 01-JAN-00:40 | 19320.03 | 09-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 31.32 | 0.00 | 01-JAN-00:40 | 19320.03 | 09-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 50.24 | 0.00 | 01-JAN-00:20 | 16476.75 | 26-JUN-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 50.24 | 0.00 | 01-JAN-00:20 | 16476.75 | 26-JUN-08:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 117.73 | 0.00 | 01-JAN-00:40 | 24174.51 | 07-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 35.41 | 0.00 | 01-JAN-00:40 | 23332.66 | 09-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 35.41 | 0.00 | 01-JAN-00:40 | 23332.66 | 09-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 82.31 | 0.00 | 01-JAN-00:20 | 24174.51 | 07-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 82.31 | 0.00 | 01-JAN-00:20 | 24174.51 | 07-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 81.70 | 0.00 | 01-JAN-00:40 | 19405.95 | 09-DEC-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 25.91 | 0.00 | 01-JAN-00:40 | 19405.95 | 09-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 25.91 | 0.00 | 01-JAN-00:40 | 19405.95 | 09-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 55.79 | 0.00 | 01-JAN-00:20 | 19047.96 | 25-JUN-17:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 55.79 | 0.00 | 01-JAN-00:20 | 19047.96 | 25-JUN-17:10 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 61.46 | 0.00 | 01-JAN-00:10 | 12330.20 | 05-JUL-07:10 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 5.97 | 0.00 | 01-JAN-00:10 | 6010.72 | 30-JAN-13:20 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 5.97 | 0.00 | 01-JAN-00:10 | 6010.72 | 30-JAN-13:20 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 55.48 | 0.00 | 01-JAN-00:10 | 12330.20 | 05-JUL-07:10 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 55.48 | 0.00 | 01-JAN-00:10 | 12330.20 | 05-JUL-07:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 543.07 | 0.00 | 01-JAN-00:40 | 176107.14 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 198.95 | 0.00 | 01-JAN-00:40 | 176107.14 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 198.95 | 0.00 | 01-JAN-00:40 | 176107.14 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 344.12 | 0.00 | 01-JAN-00:10 | 77267.13 | 04-AUG-15:40 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 344.12 | 0.00 | 01-JAN-00:10 | 77267.13 | 04-AUG-15:40 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 125.42 | 0.00 | 01-JAN-00:40 | 34895.01 | 30-JAN-05:30 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 75.54 | 0.00 | 01-JAN-00:40 | 34895.01 | 30-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 75.54 | 0.00 | 01-JAN-00:40 | 34895.01 | 30-JAN-05:30 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 49.88 | 0.00 | 01-JAN-00:10 | 20835.08 | 26-JUN-13:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 49.88 | 0.00 | 01-JAN-00:10 | 20835.08 | 26-JUN-13:50 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 135.16 | 7.10 | 31-JAN-04:00 | 8501.03 | 16-APR-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 224.22 | 29-JAN-23:30 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 224.22 | 29-JAN-23:30 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 135.15 | 0.00 | 30-JAN-00:10 | 8501.03 | 16-APR-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 135.15 | 0.00 | 30-JAN-00:10 | 8501.03 | 16-APR-18:00 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1144.74 | 0.88 | 09-JAN-19:40 | 80706.74 | 29-AUG-17:50 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 7.25 | 0.00 | 02-JAN-07:50 | 5991.35 | 31-JAN-00:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 7.25 | 0.00 | 02-JAN-07:50 | 5991.35 | 31-JAN-00:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1137.49 | 0.00 | 01-JAN-00:10 | 80706.74 | 29-AUG-17:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1137.49 | 0.00 | 01-JAN-00:10 | 80706.74 | 29-AUG-17:50 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 103.94 | 0.52 | 11-JAN-11:40 | 8223.45 | 16-APR-17:50 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.96 | 0.00 | 02-JAN-07:40 | 631.72 | 28-JAN-19:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.96 | 0.00 | 02-JAN-07:40 | 631.72 | 28-JAN-19:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 102.98 | 0.00 | 01-JAN-00:10 | 8223.45 | 16-APR-17:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 102.98 | 0.00 | 01-JAN-00:10 | 8223.45 | 16-APR-17:50 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7160.70 | 84716.32 | 30-JAN-06:00 | 385163.42 | 04-AUG-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7160.70 | 84716.32 | 30-JAN-06:00 | 385163.42 | 04-AUG-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7160.70 | 84716.32 | 30-JAN-06:00 | 385163.42 | 04-AUG-18:00 |
PlantLoopHeatingDemand:Facility | 2414.32 | 0.00 | 01-JAN-00:40 | 2083385.06 | 30-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 479.24 | 0.00 | 01-JAN-00:10 | 59652.47 | 21-FEB-12:30 |
WaterSystems:PlantLoopHeatingDemand | 479.24 | 0.00 | 01-JAN-00:10 | 59652.47 | 21-FEB-12:30 |
General:WaterSystems:PlantLoopHeatingDemand | 479.24 | 0.00 | 01-JAN-00:10 | 59652.47 | 21-FEB-12:30 |
EnergyTransfer:HVAC | 12721.58 | 2165.95 | 18-JAN-01:40 | 3662657.19 | 04-AUG-07:20 |
HeatingCoils:EnergyTransfer | 1935.08 | 0.00 | 01-JAN-00:40 | 2063642.80 | 30-JAN-07:10 |
PlantLoopHeatingDemand:HVAC | 1935.08 | 0.00 | 01-JAN-00:40 | 2063642.80 | 30-JAN-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 1935.08 | 0.00 | 01-JAN-00:40 | 2063642.80 | 30-JAN-07:10 |
CoolingCoils:EnergyTransfer | 8421.63 | 1851.83 | 30-JAN-08:10 | 3662657.19 | 04-AUG-07:20 |
HeatRecoveryForHeating:EnergyTransfer | 2161.83 | 0.00 | 01-JAN-00:10 | 839998.79 | 05-JAN-19:10 |
HeatRecoveryForCooling:EnergyTransfer | 203.05 | 0.00 | 01-JAN-00:10 | 491820.62 | 04-AUG-13:00 |
EnergyTransfer:Plant | 18083.25 | 0.00 | 01-JAN-00:40 | 9475881.70 | 04-AUG-07:20 |
LoopToLoop:EnergyTransfer | 5043.04 | 0.00 | 01-JAN-00:10 | 3031662.48 | 04-AUG-07:20 |
WaterSystems:EnergyTransfer | 479.24 | 0.00 | 01-JAN-00:10 | 59652.47 | 21-FEB-12:30 |
WaterUse:WaterSystems:EnergyTransfer | 479.24 | 0.00 | 01-JAN-00:10 | 59652.47 | 21-FEB-12:30 |
Boilers:EnergyTransfer | 1924.97 | 0.00 | 01-JAN-00:40 | 2047417.00 | 30-JAN-07:30 |
Chillers:EnergyTransfer | 5036.46 | 0.00 | 01-JAN-00:10 | 2966706.42 | 04-AUG-07:20 |
HeatRejection:EnergyTransfer | 5599.54 | 0.00 | 01-JAN-00:10 | 3449212.80 | 04-AUG-07:20 |
General:HeatRejection:EnergyTransfer | 5599.54 | 0.00 | 01-JAN-00:10 | 3449212.80 | 04-AUG-07:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:51
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -576.913 | 0.000 | 0.000 | 90.144 | 216.171 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -153.799 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -610.887 | 0.000 | 0.000 | 83.585 | 194.137 | 289.614 | 0.000 | 0.000 | 0.000 | 43.551 | 0.000 | 0.000 | 0.000 | 0.000 | -0.009 |
CORE_MID | 0.000 | 0.000 | 22.237 | -4165.524 | 0.000 | 0.000 | 862.952 | 1941.366 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1557.158 |
CORE_TOP | 0.000 | 0.000 | 27.401 | -356.370 | 0.000 | 0.000 | 89.317 | 194.137 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -244.097 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 4.544 | -65.779 | 0.000 | 0.000 | 11.069 | 14.126 | 36.365 | 30.496 | 0.000 | 0.037 | 61.510 | 0.000 | -86.177 | 0.000 | -6.192 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 3.040 | -66.020 | 0.000 | 0.000 | 7.190 | 9.019 | 23.435 | 59.762 | 0.000 | 0.027 | 19.980 | 0.000 | -52.358 | 0.000 | -4.075 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 4.321 | -105.920 | 0.000 | 0.000 | 10.915 | 13.842 | 36.366 | 123.506 | 0.000 | 0.035 | 0.000 | 0.000 | -76.082 | 0.000 | -6.212 | -0.772 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.992 | -97.985 | 0.000 | 0.000 | 7.022 | 8.984 | 23.435 | 61.257 | 0.000 | 0.023 | 59.410 | 0.000 | -58.730 | 0.000 | -4.406 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 289.315 | -427.871 | 0.000 | 0.000 | 114.896 | 140.918 | 363.654 | 315.805 | 0.000 | 0.873 | 128.006 | 0.000 | -793.726 | 0.000 | -131.871 | -0.001 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 165.402 | -536.125 | 0.000 | 0.000 | 54.408 | 90.035 | 234.352 | 600.333 | 0.000 | 0.604 | 0.018 | 0.000 | -492.336 | 0.000 | -88.962 | -27.713 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 163.942 | -895.202 | 0.000 | 0.000 | 111.139 | 138.257 | 363.660 | 1232.989 | 0.000 | 0.801 | 0.017 | 0.000 | -733.908 | 0.000 | -138.791 | -242.886 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 133.916 | -588.545 | 0.000 | 0.000 | 74.135 | 89.688 | 234.351 | 625.441 | 0.000 | 0.541 | 45.616 | 0.000 | -523.935 | 0.000 | -91.208 | -0.008 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 54.355 | -40.175 | 0.000 | 0.000 | 11.656 | 14.090 | 36.365 | 32.095 | 0.000 | 0.102 | 0.000 | 0.000 | -76.072 | 0.000 | -15.745 | -16.671 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 31.317 | -50.236 | 0.000 | 0.000 | 7.450 | 9.003 | 23.435 | 60.365 | 0.000 | 0.068 | 0.001 | 0.000 | -47.365 | 0.000 | -10.669 | -23.368 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 35.412 | -82.314 | 0.000 | 0.000 | 11.293 | 13.825 | 36.366 | 123.942 | 0.000 | 0.094 | 0.000 | 0.000 | -70.162 | 0.000 | -16.523 | -51.933 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 25.908 | -55.790 | 0.000 | 0.000 | 7.500 | 8.968 | 23.435 | 62.739 | 0.000 | 0.064 | 0.001 | 0.000 | -50.517 | 0.000 | -10.940 | -11.367 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.005 | -135.152 | 0.000 | 0.000 | 0.950 | 5.155 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -24.839 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 7.253 | -1137.487 | 0.000 | 0.000 | 9.546 | 51.551 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -469.669 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.961 | -102.976 | 0.000 | 0.000 | 0.960 | 5.155 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -57.981 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7160.695 | 0.000 | 0.000 | 20.293 | 62.653 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -417.108 |
GROUNDFLOOR_PLENUM | 5.973 | -55.482 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.069 | 62.681 | 0.000 | 0.000 | 0.000 | -13.240 | -0.001 |
MIDFLOOR_PLENUM | 198.952 | -344.123 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.354 | 366.674 | 0.000 | 0.000 | 0.000 | -222.857 | -0.007 |
TOPFLOOR_PLENUM | 75.540 | -49.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.091 | 0.001 | 0.000 | 0.000 | 0.000 | -23.811 | -1.939 |
Total Facility | 280.465 | -449.487 | 970.322 | -17257.967 | 0.000 | 0.000 | 1586.421 | 3221.080 | 14676.396 | 3328.730 | 0.000 | 4.784 | 787.465 | 0.000 | -3061.367 | 0.000 | -785.505 | -3301.324 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 01-JUN-06:11 | 0.00 | 0.00 | 0.00 | -120682.38 | 0.00 | 0.00 | 1519.67 | 6467.36 | 13457.54 | 0.00 | 0.00 | 0.00 | 99237.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 12-SEP-04:13 | 0.00 | 0.00 | 0.00 | -100282.76 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 93807.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 12-SEP-04:11 | 0.00 | 0.00 | 0.00 | -835961.32 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 771211.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 12-JUN-04:13 | 0.00 | 0.00 | 0.00 | -87971.05 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 81496.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 04-JUL-16:32 | 0.00 | 0.00 | 0.00 | -17531.13 | 0.00 | 0.00 | 41.17 | 57.83 | 720.18 | 4214.91 | 0.00 | 17.47 | 12479.57 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-JUL-07:51 | 0.00 | 0.00 | 0.00 | -28525.50 | 0.00 | 0.00 | 17.22 | 37.27 | 464.11 | 21704.61 | 0.00 | 0.00 | 6342.03 | 0.00 | -0.00 | 0.00 | -39.75 | 0.00 |
PERIMETER_BOT_ZN_1 | 04-SEP-11:51 | 0.00 | 0.00 | 0.00 | -30836.57 | 0.00 | 0.00 | 30.80 | 57.83 | 720.19 | 29102.07 | 0.00 | 0.00 | 1058.00 | 0.00 | -0.00 | 0.00 | -132.32 | 0.00 |
PERIMETER_BOT_ZN_4 | 02-JUL-16:51 | 0.00 | 0.00 | 0.00 | -35686.83 | 0.00 | 0.00 | 12.72 | 37.27 | 464.11 | 21211.61 | 0.00 | 0.00 | 13984.37 | 0.00 | -0.00 | 0.00 | -23.24 | 0.00 |
PERIMETER_MID_ZN_3 | 25-JUN-18:22 | 0.00 | 0.00 | 0.00 | -164312.26 | 0.00 | 0.00 | 0.00 | 578.27 | 5591.71 | 74943.47 | 0.00 | 1977.35 | 81221.47 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 02-JUL-09:01 | 0.00 | 0.00 | 0.00 | -312337.17 | 0.00 | 0.00 | 161.11 | 372.66 | 4641.14 | 195636.51 | 0.00 | 0.00 | 112780.76 | 0.00 | -0.00 | 0.00 | -1255.00 | 0.00 |
PERIMETER_MID_ZN_1 | 17-SEP-13:21 | 0.00 | 0.00 | 0.00 | -320597.86 | 0.00 | 0.00 | 278.11 | 578.28 | 7201.95 | 253588.90 | 0.00 | 0.00 | 61734.74 | 0.00 | -0.00 | 0.00 | -2784.12 | 0.00 |
PERIMETER_MID_ZN_4 | 25-JUN-17:01 | 0.00 | 0.00 | 0.00 | -334109.30 | 0.00 | 0.00 | 0.00 | 372.66 | 3603.49 | 219000.28 | 0.00 | 304.22 | 110828.65 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 25-JUN-18:22 | 0.00 | 0.00 | 0.00 | -20036.65 | 0.00 | 0.00 | 0.00 | 57.83 | 559.17 | 7359.81 | 0.00 | 225.55 | 11834.29 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 25-JUN-07:41 | 0.00 | 0.00 | 0.00 | -29987.14 | 0.00 | 0.00 | 18.54 | 37.27 | 464.11 | 21549.52 | 0.00 | 0.00 | 8176.43 | 0.00 | -0.00 | 0.00 | -258.72 | 0.00 |
PERIMETER_TOP_ZN_1 | 04-SEP-13:21 | 0.00 | 0.00 | 0.00 | -34473.16 | 0.00 | 0.00 | 27.75 | 57.83 | 720.19 | 26578.07 | 0.00 | 0.00 | 7331.31 | 0.00 | -0.00 | 0.00 | -241.99 | 0.00 |
PERIMETER_TOP_ZN_4 | 25-JUN-17:01 | 0.00 | 0.00 | 0.00 | -35744.90 | 0.00 | 0.00 | 0.00 | 37.27 | 360.35 | 21788.19 | 0.00 | 14.35 | 13544.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 16-APR-17:52 | 0.00 | 0.00 | 0.00 | -8501.03 | 0.00 | 0.00 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 681.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 29-AUG-17:50 | 0.00 | 0.00 | 0.00 | -80704.08 | 0.00 | 0.00 | 106.16 | 1500.36 | 77944.22 | 0.00 | 0.00 | 0.00 | 1153.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 16-APR-17:42 | 0.00 | 0.00 | 0.00 | -8223.45 | 0.00 | 0.00 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 404.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 04-AUG-17:53 | 0.00 | 0.00 | 0.00 | -392660.53 | 0.00 | 0.00 | 193.62 | 1823.52 | 379632.52 | 0.00 | 0.00 | 0.00 | 11010.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 05-JUL-05:10 | 0.00 | -15727.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15759.56 | 0.00 | -0.00 | 0.00 | -31.64 | 0.00 |
MIDFLOOR_PLENUM | 24-NOV-04:01 | 0.00 | -120118.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141721.63 | 0.00 | -0.00 | 0.00 | -21602.90 | 0.00 |
TOPFLOOR_PLENUM | 26-JUN-13:50 | 0.00 | -20835.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.76 | 20738.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 03-JUL-04:12 | 0.00 | 44016.39 | 0.00 | -1862666.96 | 0.00 | 0.00 | 0.00 | 10917.52 | 469008.02 | 0.00 | 0.00 | 0.00 | 1422619.95 | 0.00 | -71050.11 | 0.00 | -12844.81 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 21-JUN-06:30 | 0.00 | 0.00 | 468.91 | 0.00 | 0.00 | 0.00 | 1961.59 | 6467.36 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -22355.41 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-04:01 | 0.00 | 0.00 | 565691.98 | 0.00 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -630441.82 |
CORE_TOP | 11-DEC-04:01 | 0.00 | 0.00 | 81075.82 | 0.00 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -87550.81 |
PERIMETER_BOT_ZN_3 | 30-JAN-04:01 | 0.00 | 0.00 | 14039.51 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9077.95 | 0.00 | -1010.70 | -4763.89 |
PERIMETER_BOT_ZN_2 | 30-JAN-04:01 | 0.00 | 0.00 | 16056.45 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5896.53 | 0.00 | -680.77 | -10003.10 |
PERIMETER_BOT_ZN_1 | 30-JAN-04:01 | 0.00 | 0.00 | 21953.27 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8800.80 | 0.00 | -1015.58 | -12949.94 |
PERIMETER_BOT_ZN_4 | 30-JAN-05:01 | 0.00 | 0.00 | 13578.05 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6387.30 | 0.00 | -707.02 | -7007.68 |
PERIMETER_MID_ZN_3 | 29-JAN-22:52 | 0.00 | 0.00 | 146510.70 | 0.00 | 0.00 | 0.00 | 0.00 | 674.71 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -82140.82 | 0.00 | -20853.33 | -49782.96 |
PERIMETER_MID_ZN_2 | 29-JAN-07:32 | 0.00 | 0.00 | 217479.32 | 0.00 | 0.00 | 0.00 | 586.37 | 646.37 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -48702.73 | 0.00 | -23274.14 | -151376.32 |
PERIMETER_MID_ZN_1 | 29-JAN-06:12 | 0.00 | 0.00 | 238988.11 | 0.00 | 0.00 | 0.00 | 905.56 | 1215.39 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -75778.01 | 0.00 | -38638.34 | -133894.66 |
PERIMETER_MID_ZN_4 | 30-JAN-04:11 | 0.00 | 0.00 | 218470.32 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -58322.42 | 0.00 | -15415.24 | -149972.12 |
PERIMETER_TOP_ZN_3 | 30-JAN-05:11 | 0.00 | 0.00 | 18713.69 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8527.19 | 0.00 | -2647.91 | -8351.63 |
PERIMETER_TOP_ZN_2 | 30-JAN-05:11 | 0.00 | 0.00 | 23703.54 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5635.65 | 0.00 | -1837.34 | -16754.50 |
PERIMETER_TOP_ZN_1 | 30-JAN-05:11 | 0.00 | 0.00 | 26309.81 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8544.65 | 0.00 | -2764.52 | -15813.68 |
PERIMETER_TOP_ZN_4 | 30-JAN-05:11 | 0.00 | 0.00 | 25704.71 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5875.53 | 0.00 | -1849.44 | -18503.68 |
DATACENTER_BOT_ZN_6 | 29-JAN-23:49 | 0.00 | 0.00 | 497.99 | 0.00 | 0.00 | 0.00 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2471.60 |
DATACENTER_MID_ZN_6 | 29-JAN-18:02 | 0.00 | 0.00 | 6281.94 | 0.00 | 0.00 | 0.00 | 0.00 | 250.08 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -26018.07 |
DATACENTER_TOP_ZN_6 | 29-JAN-18:02 | 0.00 | 0.00 | 650.82 | 0.00 | 0.00 | 0.00 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2624.43 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 01-OCT-14:42 | 13664.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -264.78 | -13399.41 |
MIDFLOOR_PLENUM | 02-JAN-06:12 | 199455.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -4926.22 | -194529.45 |
TOPFLOOR_PLENUM | 30-JAN-05:22 | 38153.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -4092.24 | -34061.18 |
Total Facility | 02-JAN-05:21 | 25859.72 | 105060.41 | 1440658.66 | -105060.41 | 0.00 | 0.00 | 0.00 | 10917.52 | 232425.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -175072.81 | 0.00 | -62581.98 | -1472206.35 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:51
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 11.9734 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.2723 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 115.2788 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 96.2215 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 11.9084 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.4545 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.8149 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.8149 | 0.2064 | 1.0000 | Not calculated | 1.2002 | 0.2064 | ||
AIRLOOP DATACENTER BASEMENT | 25.7292 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 25.7294 | 0.0132 | 1.0000 | Not calculated | 0.3384 | 0.0132 | ||
AIRLOOP DATACENTER BOT | 0.5253 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5253 | 0.0298 | 1.0000 | Not calculated | 0.0156 | 0.0298 | ||
AIRLOOP DATACENTER MID | 5.0474 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.0474 | 0.0310 | 1.0000 | Not calculated | 0.1563 | 0.0310 | ||
AIRLOOP DATACENTER TOP | 0.5133 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5133 | 0.0305 | 1.0000 | Not calculated | 0.0156 | 0.0305 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.9867 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.1774 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 57.6394 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 31.3445 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.9542 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.2419 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 0.0000 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 0.0000 | 1.0000 | 1.0000 | Not calculated | 1.2002 | |||
AIRLOOP DATACENTER BASEMENT | 25.7292 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 25.7292 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0132 | ||
AIRLOOP DATACENTER BOT | 0.5253 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5253 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0298 | ||
AIRLOOP DATACENTER MID | 5.0474 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.0474 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0310 | ||
AIRLOOP DATACENTER TOP | 0.5133 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5133 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0305 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 5.8149 | 5.8149 | 0.0000 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.1291 | 6.1291 | 1.9674 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 57.6888 | 57.6888 | 19.3257 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.7491 | 5.7491 | 1.9777 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0269 | 1.0269 | 0.2465 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4543 | 1.4543 | 0.2909 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6199 | 1.6199 | 0.3240 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7433 | 1.7433 | 0.3487 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.6306 | 9.6306 | 2.4269 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 15.4763 | 15.4763 | 3.0953 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 16.2091 | 16.2091 | 3.2418 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 16.2740 | 16.2740 | 3.2548 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1563 | 1.1563 | 0.2636 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5569 | 1.5569 | 0.3114 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7379 | 1.7379 | 0.3476 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7081 | 1.7081 | 0.3416 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5253 | 0.5253 | 0.5253 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.0474 | 5.0474 | 5.0474 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5133 | 0.5133 | 0.5133 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 25.7292 | 25.7292 | 25.7292 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 11.9734 | 10.2723 | 11.9734 | 3.1774 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 115.2788 | 96.2215 | 115.2788 | 31.3445 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 11.9084 | 10.4545 | 11.9084 | 3.2419 | 0.0000 | 1.0000 |
CAV_BAS | 5.8149 | 5.8149 | 5.8149 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 25.7292 | 25.7294 | 25.7292 | 25.7292 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5253 | 0.5253 | 0.5253 | 0.5253 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.0474 | 5.0474 | 5.0474 | 5.0474 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5133 | 0.5133 | 0.5133 | 0.5133 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 0.0000 | 0.0000 | 0.0000 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0645 | 3.0645 | 1.9674 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 28.8444 | 28.8444 | 19.3257 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8746 | 2.8746 | 1.9777 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5135 | 0.5135 | 0.2465 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7271 | 0.7271 | 0.2909 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8099 | 0.8099 | 0.3240 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8716 | 0.8716 | 0.3487 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.8153 | 4.8153 | 2.4269 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.7381 | 7.7381 | 3.0953 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.1046 | 8.1046 | 3.2418 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.1370 | 8.1370 | 3.2548 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5781 | 0.5781 | 0.2636 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7785 | 0.7785 | 0.3114 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8689 | 0.8689 | 0.3476 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8541 | 0.8541 | 0.3416 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5253 | 0.5253 | 0.5253 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.0474 | 5.0474 | 5.0474 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5133 | 0.5133 | 0.5133 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 25.7292 | 25.7292 | 25.7292 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.9867 | 3.1774 | 3.1774 | 3.1774 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 57.6394 | 31.3445 | 31.3445 | 31.3445 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.9542 | 3.2419 | 3.2419 | 3.2419 | 0.0000 | 1.0000 |
CAV_BAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 25.7292 | 25.7292 | 25.7292 | 25.7292 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5253 | 0.5253 | 0.5253 | 0.5253 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.0474 | 5.0474 | 5.0474 | 5.0474 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5133 | 0.5133 | 0.5133 | 0.5133 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:51
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Rochester International Arpt MN USA TMY3 WMO#=726440 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 162.67 |
Number of hours cooling loads not met | 1041.17 |
Number of hours not met | 1152.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 2558.45 | 2470555.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1535.18 | 655208.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3221.08 | 325713.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 353.71 | 40855.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 55.01 | 3454.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 2505.76 | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2534.90 | 287238.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 364.82 | 56095.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 528.25 | 92515.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1517.79 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 44.62 | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 484.61 | 60476.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 27827.95 |
Natural Gas | 0.00 | 2558.45 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 30386.40 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 69.54 |
Space Heating | 0.00 |
Space Cooling | 33.14 |
Fans (All) | 54.73 |
Service Water Heating | 10.46 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 600.77 |
Subtotal | 600.77 |
Natural Gas [MJ/m2] | |
Space Heating | 55.23 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 55.23 |
Subtotal | 55.23 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 10.60 |
Space Heating | 8.42 |
Space Cooling | 5.05 |
Fans (All) | 8.34 |
Service Water Heating | 1.59 |
Receptacle Equipment | 48.30 |
Miscellaneous | 17.69 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:51
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 7572.00 | 800.50 | 218.83 | 168.67 | 0.00 |
CORE_BOTTOM | 8723.50 | 36.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8725.33 | 34.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8691.17 | 68.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8671.33 | 88.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8278.33 | 481.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8745.17 | 14.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8680.50 | 79.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8665.17 | 94.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8568.50 | 191.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8734.67 | 25.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8672.67 | 87.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8669.83 | 90.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8572.33 | 187.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8113.50 | 646.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8088.83 | 671.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8075.83 | 684.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6251.17 | 2474.33 | 33.00 | 1.50 | 0.00 |
GROUNDFLOOR_PLENUM | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8692.50 | 67.50 | 0.00 | 0.00 | 0.00 |
Min | 6251.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2474.33 | 218.83 | 168.67 | 0.00 |
Average | 8444.84 | 296.81 | 10.95 | 7.40 | 0.00 |
Sum | 194231.33 | 6826.67 | 251.83 | 170.17 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 339265.67 | 11222.33 | 9177.67 | 8950.33 | 0.00 |
CORE_BOTTOM | 330804.00 | 9.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1855.67 | 412.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1844.33 | 423.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1834.83 | 433.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 72318.17 | 30135.83 | 880.50 | 60.50 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 339265.67 | 30135.83 | 9177.67 | 8950.33 | 0.00 |
Average | 77652.07 | 1853.75 | 437.31 | 391.78 | 0.00 |
Sum | 1785997.67 | 42636.33 | 10058.17 | 9010.83 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 7165.83 | 1217.50 | 175.17 | 201.50 | 0.00 |
CORE_BOTTOM | 8014.17 | 745.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8165.33 | 594.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8201.83 | 558.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8120.00 | 640.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8379.00 | 381.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8182.17 | 577.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7794.50 | 965.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8182.33 | 577.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8218.50 | 541.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8131.00 | 629.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7993.67 | 766.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8241.00 | 519.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8239.17 | 520.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8184.50 | 575.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8046.83 | 713.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8500.83 | 259.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8476.00 | 284.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8470.67 | 289.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6536.33 | 2206.83 | 16.83 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 7938.67 | 821.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8050.67 | 709.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7798.00 | 962.00 | 0.00 | 0.00 | 0.00 |
Min | 6536.33 | 259.17 | 0.00 | 0.00 | 0.00 |
Max | 8500.83 | 2206.83 | 175.17 | 201.50 | 0.00 |
Average | 8044.83 | 698.07 | 8.35 | 8.76 | 0.00 |
Sum | 185031.00 | 16055.50 | 192.00 | 201.50 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 337506.33 | 13413.33 | 7703.00 | 9993.33 | 0.00 |
CORE_BOTTOM | 329559.83 | 1253.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330045.00 | 768.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330054.00 | 759.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38923.83 | 1.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38924.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38922.50 | 2.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38924.17 | 0.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2072.00 | 196.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2055.00 | 213.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2047.67 | 220.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 75755.67 | 27145.17 | 494.17 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 337506.33 | 27145.17 | 7703.00 | 9993.33 | 0.00 |
Average | 77632.16 | 1911.86 | 356.40 | 434.49 | 0.00 |
Sum | 1785539.67 | 43972.83 | 8197.17 | 9993.33 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:51
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:51
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6A
For: Environment
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_ROCHESTER
For: Environment
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -12.56 |
February | -7.67 |
March | 0.331 |
April | 7.021 |
May | 14.194 |
June | 19.161 |
July | 20.915 |
August | 20.049 |
September | 15.390 |
October | 7.428 |
November | -0.02 |
December | -7.58 |
Annual Sum or Average | 6.460 |
Minimum of Months | -12.56 |
Maximum of Months | 20.915 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.360483E+11 | 102399.68 | 02-JAN-07:03 | -5.9 | -6.6 | 0.566575E+10 | 7499.11 | 06-JAN-10:30 | -23.9 | -24.3 |
February | 0.364284E+11 | 102559.12 | 27-FEB-07:03 | -3.1 | -3.1 | 0.514371E+10 | 7499.12 | 24-FEB-14:09 | -3.1 | -3.1 |
March | 0.485941E+11 | 104445.59 | 29-MAR-06:12 | 7.80 | 6.92 | 0.614692E+10 | 7499.17 | 27-MAR-13:09 | 7.80 | 6.92 |
April | 0.477375E+11 | 107515.72 | 10-APR-06:11 | 7.03 | 4.83 | 0.546490E+10 | 7499.45 | 11-APR-13:09 | 12.33 | 12.10 |
May | 0.500932E+11 | 110159.77 | 08-MAY-06:11 | 11.10 | 8.91 | 0.601796E+10 | 10563.82 | 31-MAY-13:00 | 29.40 | 19.44 |
June | 0.466699E+11 | 120784.50 | 01-JUN-06:11 | 9.07 | 7.80 | 0.657253E+10 | 12063.29 | 27-JUN-13:00 | 30.00 | 22.48 |
July | 0.466054E+11 | 116573.11 | 07-JUL-20:31 | 19.07 | 16.24 | 0.649850E+10 | 12231.56 | 27-JUL-13:00 | 27.20 | 19.78 |
August | 0.578991E+11 | 112260.90 | 07-AUG-06:05 | 8.87 | 8.15 | 0.662335E+10 | 11763.88 | 04-AUG-13:00 | 8.87 | 8.15 |
September | 0.560289E+11 | 116284.85 | 12-SEP-06:11 | 15.73 | 15.05 | 0.560360E+10 | 11340.61 | 11-SEP-13:00 | 15.73 | 15.05 |
October | 0.556579E+11 | 116743.64 | 10-OCT-06:11 | 11.30 | 10.37 | 0.569396E+10 | 7499.21 | 20-OCT-09:09 | 12.70 | 8.99 |
November | 0.502354E+11 | 114088.58 | 06-NOV-07:11 | 10.60 | 9.72 | 0.563196E+10 | 7499.28 | 20-NOV-10:09 | 13.15 | 11.78 |
December | 0.449275E+11 | 106011.14 | 04-DEC-07:03 | -9.7 | -10.0 | 0.548008E+10 | 7499.09 | 28-DEC-10:09 | -12.2 | -12.5 |
Annual Sum or Average | 0.576925E+12 | 0.705432E+11 | ||||||||
Minimum of Months | 0.360483E+11 | 102399.68 | -9.7 | -10.0 | 0.514371E+10 | 7499.09 | -23.9 | -24.3 | ||
Maximum of Months | 0.578991E+11 | 120784.50 | 19.07 | 16.24 | 0.662335E+10 | 12231.56 | 30.00 | 22.48 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.304730E+11 | 79270.90 | 14-JAN-06:01 | -3.4 | -4.1 | 0.498949E+10 | 6734.80 | 20-JAN-10:30 | -20.2 | -20.7 |
February | 0.320486E+11 | 83245.91 | 25-FEB-06:02 | 0.00 | -0.6 | 0.456298E+10 | 6746.87 | 10-FEB-14:20 | 0.00 | -0.6 |
March | 0.461450E+11 | 87043.20 | 28-MAR-04:01 | 0.60 | -0.3 | 0.548800E+10 | 6747.63 | 13-MAR-13:30 | 0.60 | -0.3 |
April | 0.520972E+11 | 91274.87 | 19-APR-04:12 | 6.67 | 5.57 | 0.487817E+10 | 6734.91 | 11-APR-13:09 | 6.67 | 5.57 |
May | 0.533068E+11 | 95094.65 | 30-MAY-04:13 | 14.40 | 14.40 | 0.528364E+10 | 6734.90 | 05-MAY-09:09 | 14.40 | 14.40 |
June | 0.645051E+11 | 96709.06 | 14-JUN-04:13 | 17.80 | 17.37 | 0.527051E+10 | 6741.88 | 28-JUN-09:00 | 26.70 | 19.54 |
July | 0.738131E+11 | 98026.29 | 01-JUL-04:13 | 15.20 | 13.63 | 0.489928E+10 | 6763.19 | 28-JUL-09:00 | 24.40 | 18.88 |
August | 0.760794E+11 | 96815.17 | 07-AUG-04:11 | 8.50 | 7.60 | 0.549764E+10 | 6735.21 | 08-AUG-09:09 | 20.28 | 15.58 |
September | 0.532296E+11 | 100314.86 | 12-SEP-04:13 | 16.83 | 16.52 | 0.488175E+10 | 6790.51 | 05-SEP-13:00 | 16.83 | 16.52 |
October | 0.481761E+11 | 91849.43 | 10-OCT-04:12 | 11.43 | 10.68 | 0.507619E+10 | 6734.74 | 17-OCT-09:20 | 6.20 | 3.21 |
November | 0.428700E+11 | 91014.32 | 06-NOV-05:12 | 10.60 | 9.72 | 0.501766E+10 | 6734.87 | 20-NOV-10:09 | 13.15 | 11.78 |
December | 0.381437E+11 | 85325.92 | 04-DEC-05:01 | -9.6 | -9.9 | 0.487772E+10 | 6766.97 | 20-DEC-14:00 | -7.2 | -8.6 |
Annual Sum or Average | 0.610888E+12 | 0.607230E+11 | ||||||||
Minimum of Months | 0.304730E+11 | 79270.90 | -9.6 | -9.9 | 0.456298E+10 | 6734.74 | -20.2 | -20.7 | ||
Maximum of Months | 0.760794E+11 | 100314.86 | 17.80 | 17.37 | 0.549764E+10 | 6790.51 | 26.70 | 19.54 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.218974E+11 | 29497.48 | 12-JAN-10:10 | -2.3 | -2.9 | 0.420050E+10 | 6734.35 | 13-JAN-14:00 | 3.90 | 1.72 |
February | 0.215498E+11 | 24554.92 | 16-FEB-13:25 | -8.9 | -10.4 | 0.408028E+10 | 6734.43 | 10-FEB-14:39 | -8.9 | -10.4 |
March | 0.294303E+11 | 72359.79 | 24-MAR-05:02 | 7.12 | 4.33 | 0.522427E+10 | 6738.17 | 23-MAR-09:20 | 7.12 | 4.33 |
April | 0.333586E+11 | 80590.00 | 19-APR-04:12 | 6.67 | 5.57 | 0.477577E+10 | 6760.58 | 05-APR-13:09 | 6.67 | 5.57 |
May | 0.423940E+11 | 81593.73 | 31-MAY-04:12 | 16.50 | 15.12 | 0.526214E+10 | 6734.87 | 05-MAY-09:09 | 16.50 | 15.12 |
June | 0.471510E+11 | 83093.75 | 29-JUN-04:12 | 17.60 | 16.30 | 0.526104E+10 | 6734.80 | 01-JUN-09:00 | 17.60 | 16.30 |
July | 0.478939E+11 | 82396.97 | 18-JUL-04:12 | 15.73 | 15.40 | 0.488946E+10 | 6734.68 | 18-JUL-09:00 | 22.20 | 15.19 |
August | 0.497033E+11 | 82769.61 | 15-AUG-04:11 | 15.40 | 14.38 | 0.549309E+10 | 6735.13 | 08-AUG-09:09 | 15.40 | 14.38 |
September | 0.411621E+11 | 83610.01 | 12-SEP-04:11 | 16.83 | 16.52 | 0.485870E+10 | 6734.82 | 05-SEP-13:00 | 16.83 | 16.52 |
October | 0.319918E+11 | 74415.91 | 12-OCT-05:02 | 6.10 | 2.83 | 0.500433E+10 | 6738.61 | 17-OCT-09:30 | 6.50 | 3.40 |
November | 0.268153E+11 | 73073.99 | 09-NOV-06:03 | 14.82 | 12.81 | 0.469637E+10 | 6788.98 | 10-NOV-10:20 | -2.2 | -2.4 |
December | 0.232065E+11 | 30026.35 | 01-DEC-09:00 | -3.3 | -4.6 | 0.426734E+10 | 6734.45 | 07-DEC-14:39 | -3.3 | -7.2 |
Annual Sum or Average | 0.416554E+12 | 0.580133E+11 | ||||||||
Minimum of Months | 0.215498E+11 | 24554.92 | -8.9 | -10.4 | 0.408028E+10 | 6734.35 | -8.9 | -10.4 | ||
Maximum of Months | 0.497033E+11 | 83610.01 | 17.60 | 16.52 | 0.549309E+10 | 6788.98 | 22.20 | 16.52 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.123583E+11 | 18104.45 | 13-JAN-17:00 | 2.20 | 0.77 | 0.387375E+10 | 6276.45 | 13-JAN-14:00 | 2.20 | 0.77 |
February | 0.144742E+11 | 21303.12 | 24-FEB-14:10 | 7.88 | 5.25 | 0.365993E+10 | 6327.96 | 24-FEB-16:00 | 7.20 | 5.13 |
March | 0.220137E+11 | 32174.27 | 24-MAR-16:00 | 10.60 | 5.50 | 0.473771E+10 | 6734.50 | 28-MAR-13:50 | 16.52 | 10.22 |
April | 0.279368E+11 | 78314.22 | 17-APR-05:03 | 11.42 | 9.68 | 0.450525E+10 | 6734.73 | 11-APR-13:00 | 11.42 | 9.68 |
May | 0.396011E+11 | 80001.40 | 30-MAY-04:12 | 14.40 | 14.40 | 0.519737E+10 | 6734.85 | 05-MAY-09:09 | 14.40 | 14.40 |
June | 0.474504E+11 | 87995.65 | 12-JUN-04:13 | 18.13 | 17.48 | 0.523879E+10 | 6734.76 | 01-JUN-09:00 | 18.13 | 17.48 |
July | 0.491018E+11 | 81841.51 | 28-JUL-04:12 | 18.13 | 16.81 | 0.488228E+10 | 6734.68 | 19-JUL-09:09 | 18.13 | 16.81 |
August | 0.495212E+11 | 81151.06 | 29-AUG-04:12 | 18.70 | 18.22 | 0.547994E+10 | 6735.08 | 08-AUG-09:09 | 18.70 | 18.22 |
September | 0.365595E+11 | 81242.98 | 12-SEP-04:11 | 16.83 | 16.52 | 0.475922E+10 | 6734.84 | 05-SEP-13:00 | 16.83 | 16.52 |
October | 0.241837E+11 | 33257.94 | 20-OCT-16:00 | 21.30 | 12.72 | 0.462015E+10 | 6734.56 | 20-OCT-13:39 | 21.30 | 12.72 |
November | 0.189644E+11 | 31470.51 | 03-NOV-16:00 | 15.00 | 9.33 | 0.422692E+10 | 6734.42 | 08-NOV-14:00 | 13.90 | 12.22 |
December | 0.142072E+11 | 17714.02 | 01-DEC-16:40 | -3.2 | -5.0 | 0.381028E+10 | 6196.56 | 01-DEC-14:00 | -3.2 | -5.0 |
Annual Sum or Average | 0.356372E+12 | 0.549916E+11 | ||||||||
Minimum of Months | 0.123583E+11 | 17714.02 | -3.2 | -5.0 | 0.365993E+10 | 6196.56 | -3.2 | -5.0 | ||
Maximum of Months | 0.495212E+11 | 87995.65 | 21.30 | 18.22 | 0.547994E+10 | 6735.08 | 21.30 | 18.22 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.652829E+09 | 2122.45 | 13-JAN-14:40 | 3.90 | 1.72 | 0.476884E+09 | 768.41 | 13-JAN-14:30 | 3.90 | 1.72 |
February | 0.154021E+10 | 2882.14 | 24-FEB-13:30 | 7.25 | 4.63 | 0.465927E+09 | 806.93 | 24-FEB-14:00 | 8.30 | 5.62 |
March | 0.326221E+10 | 5415.77 | 28-MAR-14:00 | 16.70 | 10.30 | 0.621991E+09 | 845.63 | 28-MAR-13:09 | 16.70 | 10.30 |
April | 0.493191E+10 | 16726.59 | 16-APR-15:41 | 28.80 | 20.54 | 0.591685E+09 | 845.64 | 11-APR-13:09 | 28.80 | 20.54 |
May | 0.700415E+10 | 12909.65 | 30-MAY-04:12 | 14.40 | 14.40 | 0.660269E+09 | 845.64 | 05-MAY-09:09 | 14.40 | 14.40 |
June | 0.103511E+11 | 16842.21 | 25-JUN-18:31 | 29.97 | 21.56 | 0.661703E+09 | 846.68 | 28-JUN-09:00 | 26.70 | 19.54 |
July | 0.117690E+11 | 17535.05 | 04-JUL-16:32 | 27.80 | 21.59 | 0.615958E+09 | 849.62 | 28-JUL-09:00 | 24.40 | 18.88 |
August | 0.114270E+11 | 15538.25 | 27-AUG-13:22 | 26.70 | 20.38 | 0.690297E+09 | 846.34 | 03-AUG-13:20 | 26.70 | 20.38 |
September | 0.642223E+10 | 13183.44 | 12-SEP-04:11 | 16.83 | 16.52 | 0.605816E+09 | 846.36 | 05-SEP-13:00 | 16.83 | 16.52 |
October | 0.399405E+10 | 6408.01 | 10-OCT-13:30 | 16.65 | 13.06 | 0.613309E+09 | 845.62 | 10-OCT-09:39 | 16.65 | 13.06 |
November | 0.283584E+10 | 4961.53 | 07-NOV-13:30 | 12.80 | 11.17 | 0.561974E+09 | 845.61 | 03-NOV-09:50 | 12.80 | 11.17 |
December | 0.158862E+10 | 2621.77 | 03-DEC-11:32 | 4.80 | 2.32 | 0.484416E+09 | 757.82 | 04-DEC-14:09 | -0.5 | -2.3 |
Annual Sum or Average | 0.657791E+11 | 0.705023E+10 | ||||||||
Minimum of Months | 0.652829E+09 | 2122.45 | 3.90 | 1.72 | 0.465927E+09 | 757.82 | -0.5 | -2.3 | ||
Maximum of Months | 0.117690E+11 | 17535.05 | 29.97 | 21.59 | 0.690297E+09 | 849.62 | 28.80 | 20.54 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.903094E+09 | 2807.90 | 12-JAN-10:10 | -2.3 | -2.9 | 0.311511E+09 | 539.92 | 12-JAN-10:20 | -1.9 | -2.6 |
February | 0.177017E+10 | 7256.77 | 24-FEB-09:25 | 3.60 | 0.91 | 0.301367E+09 | 544.95 | 21-FEB-10:20 | 3.60 | 0.91 |
March | 0.371171E+10 | 10483.85 | 28-MAR-08:55 | 7.20 | 4.38 | 0.397125E+09 | 545.44 | 14-MAR-09:09 | 7.20 | 4.38 |
April | 0.539927E+10 | 21096.36 | 30-APR-08:42 | 9.72 | 5.05 | 0.368818E+09 | 544.96 | 18-APR-09:09 | 9.72 | 5.05 |
May | 0.755199E+10 | 26349.46 | 29-MAY-09:31 | 23.33 | 18.40 | 0.424325E+09 | 545.99 | 31-MAY-09:39 | 26.83 | 19.51 |
June | 0.995334E+10 | 25442.32 | 25-JUN-08:32 | 25.37 | 20.95 | 0.424153E+09 | 546.83 | 28-JUN-09:00 | 26.70 | 19.54 |
July | 0.112465E+11 | 28543.73 | 04-JUL-07:51 | 22.20 | 19.58 | 0.396429E+09 | 549.83 | 28-JUL-09:00 | 24.40 | 18.88 |
August | 0.102728E+11 | 25590.52 | 27-AUG-10:01 | 24.68 | 19.58 | 0.443138E+09 | 546.18 | 02-AUG-09:39 | 24.68 | 19.58 |
September | 0.713416E+10 | 24970.99 | 04-SEP-09:11 | 16.83 | 13.06 | 0.386855E+09 | 546.12 | 05-SEP-09:20 | 21.50 | 14.87 |
October | 0.419472E+10 | 9611.27 | 20-OCT-08:50 | 11.70 | 8.40 | 0.386928E+09 | 544.96 | 20-OCT-09:09 | 12.70 | 8.99 |
November | 0.259758E+10 | 6274.16 | 04-NOV-09:20 | 6.87 | 3.64 | 0.341853E+09 | 544.88 | 03-NOV-09:00 | 6.87 | 3.64 |
December | 0.128478E+10 | 3789.21 | 05-DEC-09:35 | -6.3 | -8.4 | 0.304215E+09 | 544.95 | 05-DEC-10:09 | -5.9 | -8.1 |
Annual Sum or Average | 0.660201E+11 | 0.448672E+10 | ||||||||
Minimum of Months | 0.903094E+09 | 2807.90 | -6.3 | -8.4 | 0.301367E+09 | 539.92 | -5.9 | -8.1 | ||
Maximum of Months | 0.112465E+11 | 28543.73 | 25.37 | 20.95 | 0.443138E+09 | 549.83 | 26.83 | 19.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.338456E+10 | 16337.65 | 12-JAN-12:30 | 1.95 | 0.38 | 0.541134E+09 | 845.65 | 19-JAN-14:09 | -23.2 | -23.5 |
February | 0.458494E+10 | 26520.41 | 20-FEB-13:13 | 2.80 | 0.58 | 0.514383E+09 | 847.01 | 13-FEB-14:50 | 2.80 | 0.58 |
March | 0.692257E+10 | 28091.80 | 19-MAR-12:52 | 16.70 | 12.78 | 0.633882E+09 | 848.14 | 16-MAR-13:30 | 16.70 | 12.78 |
April | 0.875350E+10 | 30373.01 | 16-APR-13:41 | 27.62 | 20.47 | 0.582040E+09 | 846.93 | 10-APR-13:50 | 27.62 | 20.47 |
May | 0.938707E+10 | 26892.54 | 14-MAY-13:22 | 20.85 | 14.94 | 0.656414E+09 | 847.01 | 30-MAY-13:00 | 26.70 | 19.86 |
June | 0.121037E+11 | 26166.27 | 25-JUN-14:32 | 32.20 | 22.49 | 0.659570E+09 | 846.88 | 28-JUN-09:00 | 26.70 | 19.54 |
July | 0.144371E+11 | 28247.77 | 02-JUL-13:32 | 28.70 | 22.08 | 0.615676E+09 | 850.59 | 28-JUL-09:00 | 24.40 | 18.88 |
August | 0.157827E+11 | 28901.13 | 13-AUG-13:22 | 25.55 | 19.87 | 0.690118E+09 | 874.78 | 29-AUG-13:30 | 23.60 | 16.39 |
September | 0.120509E+11 | 30835.77 | 04-SEP-11:51 | 20.00 | 13.69 | 0.605461E+09 | 978.59 | 05-SEP-13:00 | 27.20 | 16.61 |
October | 0.915421E+10 | 30334.25 | 01-OCT-12:41 | 18.63 | 12.19 | 0.615221E+09 | 876.49 | 20-OCT-13:20 | 22.07 | 12.75 |
November | 0.523601E+10 | 28538.31 | 05-NOV-14:02 | 15.10 | 10.18 | 0.571034E+09 | 856.79 | 03-NOV-13:09 | 15.10 | 10.18 |
December | 0.412303E+10 | 26849.72 | 03-DEC-12:52 | 5.60 | 2.41 | 0.519435E+09 | 862.97 | 20-DEC-14:20 | -6.9 | -8.3 |
Annual Sum or Average | 0.105920E+12 | 0.720437E+10 | ||||||||
Minimum of Months | 0.338456E+10 | 16337.65 | 1.95 | 0.38 | 0.514383E+09 | 845.65 | -23.2 | -23.5 | ||
Maximum of Months | 0.157827E+11 | 30835.77 | 32.20 | 22.49 | 0.690118E+09 | 978.59 | 27.62 | 20.47 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.169377E+10 | 5888.18 | 12-JAN-15:30 | 2.80 | 1.13 | 0.319207E+09 | 544.94 | 12-JAN-14:50 | 2.80 | 1.13 |
February | 0.330878E+10 | 10878.41 | 24-FEB-16:20 | 7.93 | 5.63 | 0.319223E+09 | 545.72 | 13-FEB-14:50 | 7.93 | 5.63 |
March | 0.615049E+10 | 26589.53 | 19-MAR-14:52 | 18.30 | 13.68 | 0.418910E+09 | 545.94 | 16-MAR-13:30 | 18.30 | 13.68 |
April | 0.973604E+10 | 35380.09 | 16-APR-16:21 | 28.60 | 20.44 | 0.391769E+09 | 544.97 | 11-APR-13:09 | 28.60 | 20.44 |
May | 0.894734E+10 | 34504.47 | 14-MAY-16:41 | 21.70 | 15.70 | 0.424651E+09 | 544.97 | 08-MAY-13:00 | 21.70 | 15.70 |
June | 0.125660E+11 | 31519.02 | 25-JUN-16:31 | 31.87 | 21.81 | 0.426948E+09 | 545.70 | 28-JUN-09:00 | 26.70 | 19.54 |
July | 0.153954E+11 | 35697.89 | 02-JUL-16:51 | 28.90 | 21.17 | 0.397834E+09 | 548.01 | 28-JUL-09:00 | 24.40 | 18.88 |
August | 0.165203E+11 | 31805.71 | 13-AUG-16:01 | 25.50 | 20.53 | 0.446022E+09 | 545.00 | 08-AUG-09:09 | 25.50 | 20.53 |
September | 0.857323E+10 | 33454.83 | 04-SEP-16:31 | 22.20 | 14.41 | 0.388703E+09 | 545.06 | 05-SEP-13:00 | 27.20 | 16.61 |
October | 0.643243E+10 | 29354.73 | 01-OCT-14:42 | 19.33 | 12.32 | 0.398451E+09 | 544.95 | 10-OCT-09:39 | 13.53 | 11.84 |
November | 0.479404E+10 | 21381.05 | 05-NOV-14:02 | 15.10 | 10.18 | 0.377554E+09 | 544.95 | 02-NOV-09:00 | 15.10 | 10.18 |
December | 0.386748E+10 | 8146.69 | 01-DEC-15:30 | -1.4 | -3.8 | 0.345879E+09 | 544.95 | 14-DEC-14:09 | 1.20 | 0.19 |
Annual Sum or Average | 0.979852E+11 | 0.465515E+10 | ||||||||
Minimum of Months | 0.169377E+10 | 5888.18 | -1.4 | -3.8 | 0.319207E+09 | 544.94 | 1.20 | 0.19 | ||
Maximum of Months | 0.165203E+11 | 35697.89 | 31.87 | 21.81 | 0.446022E+09 | 548.01 | 28.60 | 20.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 63964795.98 | 1711.02 | 13-JAN-13:50 | 3.90 | 1.72 | 0.461796E+09 | 647.03 | 13-JAN-14:39 | 3.90 | 1.72 |
February | 0.266962E+09 | 2455.61 | 24-FEB-14:30 | 8.05 | 5.40 | 0.421630E+09 | 664.13 | 24-FEB-14:00 | 8.30 | 5.62 |
March | 0.136712E+10 | 2804.79 | 24-MAR-13:30 | 12.75 | 6.50 | 0.541958E+09 | 824.89 | 28-MAR-13:00 | 16.70 | 10.30 |
April | 0.285412E+10 | 8585.59 | 16-APR-15:51 | 28.90 | 20.59 | 0.528699E+09 | 845.60 | 18-APR-09:39 | 24.67 | 19.90 |
May | 0.544613E+10 | 8955.39 | 31-MAY-14:40 | 29.80 | 19.61 | 0.647047E+09 | 845.64 | 05-MAY-09:09 | 29.80 | 19.61 |
June | 0.808884E+10 | 16434.84 | 25-JUN-18:22 | 30.25 | 21.63 | 0.657229E+09 | 846.09 | 27-JUN-13:20 | 29.60 | 22.39 |
July | 0.836599E+10 | 15893.56 | 02-JUL-18:21 | 27.75 | 21.00 | 0.614561E+09 | 846.08 | 03-JUL-13:00 | 29.40 | 24.07 |
August | 0.787667E+10 | 10127.28 | 03-AUG-05:03 | 23.30 | 22.56 | 0.687455E+09 | 845.67 | 08-AUG-09:09 | 20.28 | 15.58 |
September | 0.485422E+10 | 11269.69 | 11-SEP-05:03 | 19.90 | 17.36 | 0.585440E+09 | 845.63 | 05-SEP-13:00 | 19.90 | 17.36 |
October | 0.240372E+10 | 3513.91 | 02-OCT-14:50 | 18.15 | 14.79 | 0.542424E+09 | 845.61 | 02-OCT-13:09 | 18.15 | 14.79 |
November | 0.116689E+10 | 3022.50 | 03-NOV-14:10 | 16.10 | 10.33 | 0.494215E+09 | 829.67 | 07-NOV-14:39 | 13.13 | 11.29 |
December | 32633777.95 | 1449.57 | 02-DEC-17:03 | 1.70 | 0.90 | 0.447299E+09 | 625.96 | 11-DEC-10:09 | -20.9 | -21.5 |
Annual Sum or Average | 0.427873E+11 | 0.662975E+10 | ||||||||
Minimum of Months | 32633777.95 | 1449.57 | 1.70 | 0.90 | 0.421630E+09 | 625.96 | -20.9 | -21.5 | ||
Maximum of Months | 0.836599E+10 | 16434.84 | 30.25 | 22.56 | 0.687455E+09 | 846.09 | 29.80 | 24.07 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.184614E+09 | 4323.02 | 12-JAN-10:10 | -2.3 | -2.9 | 0.219186E+09 | 434.34 | 13-JAN-11:30 | 3.05 | 1.02 |
February | 0.665846E+09 | 4890.34 | 24-FEB-09:45 | 4.13 | 1.21 | 0.203601E+09 | 521.20 | 24-FEB-11:30 | 5.85 | 2.78 |
March | 0.228854E+10 | 8595.12 | 28-MAR-08:55 | 7.20 | 4.38 | 0.266026E+09 | 522.96 | 22-MAR-10:30 | 7.20 | 4.38 |
April | 0.419838E+10 | 26649.92 | 30-APR-09:52 | 11.10 | 5.92 | 0.252114E+09 | 521.23 | 18-APR-07:10 | 11.10 | 5.92 |
May | 0.707479E+10 | 28106.95 | 29-MAY-09:41 | 23.62 | 18.42 | 0.306458E+09 | 521.53 | 31-MAY-08:00 | 26.10 | 19.69 |
June | 0.932973E+10 | 29926.22 | 25-JUN-07:41 | 23.35 | 20.28 | 0.307104E+09 | 521.65 | 09-JUN-08:00 | 23.35 | 20.28 |
July | 0.987322E+10 | 31246.94 | 02-JUL-09:01 | 25.78 | 21.09 | 0.291194E+09 | 522.02 | 05-JUL-08:00 | 22.80 | 20.41 |
August | 0.887902E+10 | 27868.50 | 27-AUG-10:01 | 24.68 | 19.58 | 0.323791E+09 | 521.56 | 01-AUG-08:00 | 24.68 | 19.58 |
September | 0.649354E+10 | 27946.16 | 03-SEP-08:51 | 17.20 | 12.64 | 0.275968E+09 | 521.24 | 08-SEP-07:10 | 17.03 | 15.57 |
October | 0.310908E+10 | 8265.08 | 20-OCT-09:00 | 12.20 | 8.72 | 0.256863E+09 | 521.20 | 19-OCT-10:20 | 12.20 | 8.72 |
November | 0.128455E+10 | 4366.36 | 04-NOV-09:30 | 7.50 | 4.04 | 0.226448E+09 | 510.36 | 03-NOV-10:50 | 7.50 | 4.04 |
December | 0.231149E+09 | 3011.79 | 07-DEC-09:35 | -10.6 | -12.3 | 0.212181E+09 | 445.39 | 05-DEC-09:00 | -10.6 | -12.3 |
Annual Sum or Average | 0.536125E+11 | 0.314094E+10 | ||||||||
Minimum of Months | 0.184614E+09 | 3011.79 | -10.6 | -12.3 | 0.203601E+09 | 434.34 | -10.6 | -12.3 | ||
Maximum of Months | 0.987322E+10 | 31246.94 | 25.78 | 21.09 | 0.323791E+09 | 522.96 | 26.10 | 20.41 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.269873E+10 | 17508.12 | 12-JAN-12:30 | 1.95 | 0.38 | 0.524206E+09 | 853.01 | 12-JAN-14:50 | 2.70 | 1.03 |
February | 0.369824E+10 | 27604.84 | 20-FEB-14:22 | 2.80 | 0.24 | 0.493839E+09 | 866.84 | 16-FEB-13:30 | 2.80 | 0.24 |
March | 0.556750E+10 | 20826.01 | 19-MAR-13:02 | 16.97 | 12.93 | 0.604162E+09 | 846.06 | 28-MAR-13:00 | 16.70 | 10.30 |
April | 0.722772E+10 | 30705.07 | 16-APR-13:51 | 27.80 | 20.59 | 0.552298E+09 | 854.67 | 05-APR-13:09 | 27.80 | 20.59 |
May | 0.852261E+10 | 26651.14 | 14-MAY-13:02 | 20.68 | 14.89 | 0.647141E+09 | 846.68 | 30-MAY-13:00 | 26.70 | 19.86 |
June | 0.104460E+11 | 28309.19 | 25-JUN-12:22 | 31.15 | 22.56 | 0.653759E+09 | 846.46 | 30-JUN-13:00 | 29.40 | 21.96 |
July | 0.115739E+11 | 28433.08 | 02-JUL-13:02 | 28.40 | 22.34 | 0.613612E+09 | 846.59 | 27-JUL-13:00 | 27.20 | 19.78 |
August | 0.128930E+11 | 29282.62 | 13-AUG-12:52 | 25.00 | 19.70 | 0.687423E+09 | 880.62 | 29-AUG-13:39 | 23.70 | 16.28 |
September | 0.116187E+11 | 32062.81 | 17-SEP-13:21 | 26.40 | 17.95 | 0.597028E+09 | 913.30 | 07-SEP-13:20 | 26.40 | 17.95 |
October | 0.842649E+10 | 29862.00 | 29-OCT-11:51 | 11.70 | 6.53 | 0.594874E+09 | 914.76 | 20-OCT-13:30 | 11.70 | 6.53 |
November | 0.399744E+10 | 29138.91 | 12-NOV-12:12 | -0.7 | -3.3 | 0.538182E+09 | 872.55 | 03-NOV-13:39 | -0.7 | -3.3 |
December | 0.285037E+10 | 28543.24 | 03-DEC-13:22 | 5.60 | 2.33 | 0.499347E+09 | 863.76 | 15-DEC-13:20 | -8.1 | -9.7 |
Annual Sum or Average | 0.895208E+11 | 0.700587E+10 | ||||||||
Minimum of Months | 0.269873E+10 | 17508.12 | -0.7 | -3.3 | 0.493839E+09 | 846.06 | -8.1 | -9.7 | ||
Maximum of Months | 0.128930E+11 | 32062.81 | 31.15 | 22.56 | 0.687423E+09 | 914.76 | 29.40 | 21.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.381052E+09 | 3112.47 | 12-JAN-15:50 | 2.80 | 1.13 | 0.302796E+09 | 511.56 | 12-JAN-15:00 | 2.80 | 1.13 |
February | 0.995500E+09 | 7872.96 | 24-FEB-16:30 | 7.75 | 5.51 | 0.282547E+09 | 544.87 | 24-FEB-14:00 | 7.75 | 5.51 |
March | 0.255066E+10 | 9246.22 | 21-MAR-16:00 | -0.6 | -4.1 | 0.353329E+09 | 544.93 | 10-MAR-14:00 | -0.6 | -4.1 |
April | 0.530021E+10 | 32261.90 | 16-APR-16:31 | 28.50 | 20.39 | 0.341269E+09 | 544.94 | 13-APR-13:00 | 28.50 | 20.39 |
May | 0.704227E+10 | 28915.49 | 07-MAY-16:41 | 18.62 | 12.78 | 0.406677E+09 | 544.97 | 08-MAY-13:00 | 19.40 | 13.87 |
June | 0.953719E+10 | 33422.62 | 25-JUN-17:01 | 31.60 | 21.70 | 0.417694E+09 | 544.98 | 20-JUN-13:50 | 31.60 | 21.70 |
July | 0.104668E+11 | 33033.48 | 02-JUL-17:01 | 28.80 | 21.14 | 0.394890E+09 | 544.95 | 18-JUL-09:00 | 22.20 | 15.19 |
August | 0.988962E+10 | 31352.70 | 13-AUG-16:51 | 25.00 | 20.46 | 0.441046E+09 | 544.98 | 30-AUG-13:50 | 23.62 | 17.87 |
September | 0.668079E+10 | 28936.82 | 17-SEP-16:41 | 26.20 | 17.70 | 0.366029E+09 | 544.96 | 05-SEP-13:00 | 26.20 | 17.70 |
October | 0.379071E+10 | 26325.88 | 01-OCT-15:11 | 18.97 | 12.13 | 0.346262E+09 | 544.93 | 02-OCT-13:00 | 17.40 | 14.50 |
November | 0.173549E+10 | 8010.75 | 03-NOV-15:30 | 15.55 | 9.47 | 0.315983E+09 | 544.22 | 03-NOV-13:00 | 15.55 | 9.47 |
December | 0.484430E+09 | 3134.98 | 01-DEC-15:50 | -1.6 | -4.0 | 0.294746E+09 | 515.18 | 01-DEC-15:00 | -1.7 | -4.1 |
Annual Sum or Average | 0.588547E+11 | 0.426327E+10 | ||||||||
Minimum of Months | 0.381052E+09 | 3112.47 | -1.6 | -4.1 | 0.282547E+09 | 511.56 | -1.7 | -4.1 | ||
Maximum of Months | 0.104668E+11 | 33422.62 | 31.60 | 21.70 | 0.441046E+09 | 544.98 | 31.60 | 21.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 31502109.83 | 1524.23 | 21-JAN-17:02 | -3.9 | -4.9 | 0.458527E+09 | 626.01 | 30-JAN-14:50 | -24.0 | -24.3 |
February | 0.106910E+09 | 2258.57 | 24-FEB-14:10 | 7.88 | 5.25 | 0.417700E+09 | 646.86 | 24-FEB-14:00 | 8.30 | 5.62 |
March | 0.885517E+09 | 2640.98 | 24-MAR-13:50 | 13.12 | 6.51 | 0.522305E+09 | 785.26 | 28-MAR-13:00 | 16.70 | 10.30 |
April | 0.236842E+10 | 8878.46 | 18-APR-15:00 | 28.30 | 20.65 | 0.503202E+09 | 845.60 | 18-APR-09:39 | 28.30 | 20.65 |
May | 0.520809E+10 | 9843.15 | 31-MAY-14:40 | 29.80 | 19.61 | 0.629221E+09 | 845.64 | 05-MAY-09:09 | 29.80 | 19.61 |
June | 0.823809E+10 | 20041.71 | 25-JUN-18:22 | 30.25 | 21.63 | 0.649737E+09 | 845.73 | 26-JUN-13:00 | 31.70 | 22.11 |
July | 0.854144E+10 | 18720.53 | 02-JUL-18:31 | 27.57 | 20.99 | 0.613144E+09 | 845.62 | 18-JUL-09:00 | 22.20 | 15.19 |
August | 0.789404E+10 | 12170.09 | 04-AUG-05:03 | 22.80 | 22.80 | 0.682860E+09 | 845.65 | 30-AUG-13:50 | 23.62 | 17.87 |
September | 0.450702E+10 | 11060.58 | 11-SEP-05:03 | 19.90 | 17.36 | 0.562327E+09 | 845.63 | 05-SEP-13:00 | 19.90 | 17.36 |
October | 0.166743E+10 | 3245.73 | 20-OCT-14:30 | 22.95 | 13.19 | 0.504761E+09 | 821.29 | 11-OCT-13:00 | 22.95 | 13.19 |
November | 0.712552E+09 | 2987.52 | 03-NOV-13:30 | 15.85 | 10.76 | 0.473820E+09 | 764.70 | 03-NOV-13:00 | 16.10 | 10.47 |
December | 14827402.60 | 1543.51 | 02-DEC-17:03 | 1.70 | 0.90 | 0.445339E+09 | 625.94 | 11-DEC-10:50 | -20.2 | -20.9 |
Annual Sum or Average | 0.401758E+11 | 0.646294E+10 | ||||||||
Minimum of Months | 14827402.60 | 1524.23 | -3.9 | -4.9 | 0.417700E+09 | 625.94 | -24.0 | -24.3 | ||
Maximum of Months | 0.854144E+10 | 20041.71 | 30.25 | 22.80 | 0.682860E+09 | 845.73 | 31.70 | 22.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108273E+09 | 2126.14 | 12-JAN-10:30 | -1.4 | -2.2 | 0.298610E+09 | 424.00 | 12-JAN-10:39 | -0.9 | -1.9 |
February | 0.410938E+09 | 3225.50 | 24-FEB-10:20 | 4.80 | 1.70 | 0.275579E+09 | 544.94 | 24-FEB-10:39 | 5.20 | 2.05 |
March | 0.171646E+10 | 6980.04 | 28-MAR-09:40 | 9.07 | 5.68 | 0.354978E+09 | 544.95 | 28-MAR-13:09 | 15.78 | 9.88 |
April | 0.353329E+10 | 25856.77 | 30-APR-09:52 | 11.10 | 5.92 | 0.336879E+09 | 544.96 | 13-APR-09:09 | 11.10 | 5.92 |
May | 0.677174E+10 | 26417.86 | 14-MAY-10:12 | 17.57 | 13.65 | 0.413636E+09 | 546.14 | 31-MAY-09:00 | 27.20 | 19.40 |
June | 0.946021E+10 | 30000.68 | 25-JUN-07:41 | 23.35 | 20.28 | 0.415260E+09 | 546.05 | 26-JUN-09:39 | 27.93 | 22.45 |
July | 0.100372E+11 | 28203.68 | 23-JUL-08:41 | 18.43 | 14.21 | 0.394652E+09 | 546.40 | 05-JUL-09:20 | 18.43 | 14.21 |
August | 0.892587E+10 | 22881.64 | 20-AUG-08:52 | 20.60 | 18.33 | 0.440322E+09 | 546.20 | 02-AUG-09:00 | 20.60 | 18.33 |
September | 0.603210E+10 | 27651.20 | 03-SEP-09:01 | 17.38 | 12.76 | 0.370948E+09 | 544.99 | 07-SEP-09:20 | 25.53 | 18.00 |
October | 0.232467E+10 | 6866.45 | 20-OCT-09:40 | 14.20 | 9.74 | 0.335943E+09 | 544.95 | 20-OCT-09:09 | 14.20 | 9.74 |
November | 0.816715E+09 | 3342.54 | 03-NOV-13:30 | 15.85 | 10.76 | 0.301933E+09 | 480.96 | 03-NOV-10:50 | 15.85 | 10.76 |
December | 98999408.69 | 2134.96 | 30-DEC-06:04 | -1.7 | -2.2 | 0.288229E+09 | 416.53 | 05-DEC-10:09 | -1.7 | -2.2 |
Annual Sum or Average | 0.502364E+11 | 0.422697E+10 | ||||||||
Minimum of Months | 98999408.69 | 2126.14 | -1.7 | -2.2 | 0.275579E+09 | 416.53 | -1.7 | -2.2 | ||
Maximum of Months | 0.100372E+11 | 30000.68 | 23.35 | 20.28 | 0.440322E+09 | 546.40 | 27.93 | 22.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.214883E+10 | 14146.65 | 12-JAN-12:40 | 2.03 | 0.42 | 0.513256E+09 | 845.64 | 31-JAN-14:30 | -20.0 | -20.5 |
February | 0.285114E+10 | 20924.01 | 24-FEB-13:40 | 7.43 | 4.81 | 0.480290E+09 | 845.70 | 24-FEB-14:00 | 8.30 | 5.62 |
March | 0.451303E+10 | 19138.36 | 24-MAR-13:20 | 12.57 | 6.49 | 0.582488E+09 | 846.69 | 21-MAR-13:39 | 12.57 | 6.49 |
April | 0.635365E+10 | 30364.37 | 16-APR-13:22 | 27.25 | 20.22 | 0.531653E+09 | 846.45 | 19-APR-13:00 | 10.60 | 7.03 |
May | 0.817396E+10 | 28630.89 | 14-MAY-13:32 | 20.93 | 14.96 | 0.632130E+09 | 846.89 | 30-MAY-13:00 | 26.70 | 19.86 |
June | 0.106254E+11 | 31003.62 | 25-JUN-14:21 | 32.20 | 22.49 | 0.644748E+09 | 846.80 | 26-JUN-13:39 | 31.50 | 21.88 |
July | 0.118053E+11 | 30050.23 | 30-JUL-13:42 | 27.12 | 19.61 | 0.610919E+09 | 846.47 | 31-JUL-13:00 | 26.10 | 21.45 |
August | 0.129053E+11 | 29035.82 | 13-AUG-13:42 | 25.92 | 19.97 | 0.682404E+09 | 865.82 | 29-AUG-13:39 | 23.70 | 16.28 |
September | 0.109567E+11 | 34471.74 | 04-SEP-13:21 | 21.40 | 14.09 | 0.580367E+09 | 912.43 | 05-SEP-13:00 | 27.20 | 16.61 |
October | 0.691593E+10 | 29531.69 | 01-OCT-13:32 | 18.90 | 12.26 | 0.568077E+09 | 875.86 | 20-OCT-13:39 | 22.33 | 12.89 |
November | 0.288488E+10 | 21943.91 | 03-NOV-13:30 | 15.85 | 10.76 | 0.510917E+09 | 845.71 | 03-NOV-13:20 | 15.85 | 10.76 |
December | 0.218020E+10 | 18586.95 | 03-DEC-13:22 | 5.60 | 2.33 | 0.489848E+09 | 845.64 | 14-DEC-14:09 | 1.20 | 0.19 |
Annual Sum or Average | 0.823144E+11 | 0.682710E+10 | ||||||||
Minimum of Months | 0.214883E+10 | 14146.65 | 2.03 | 0.42 | 0.480290E+09 | 845.64 | -20.0 | -20.5 | ||
Maximum of Months | 0.129053E+11 | 34471.74 | 32.20 | 22.49 | 0.682404E+09 | 912.43 | 31.50 | 21.88 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.291658E+09 | 3110.77 | 12-JAN-15:50 | 2.80 | 1.13 | 0.300927E+09 | 493.01 | 12-JAN-15:00 | 2.80 | 1.13 |
February | 0.741670E+09 | 7598.11 | 24-FEB-16:30 | 7.75 | 5.51 | 0.279335E+09 | 544.73 | 24-FEB-14:00 | 7.75 | 5.51 |
March | 0.199248E+10 | 8672.69 | 21-MAR-16:00 | -0.6 | -4.1 | 0.345309E+09 | 544.44 | 07-MAR-14:00 | -0.6 | -4.1 |
April | 0.472115E+10 | 30230.33 | 16-APR-16:41 | 28.40 | 20.34 | 0.329741E+09 | 544.94 | 13-APR-13:00 | 28.40 | 20.34 |
May | 0.689973E+10 | 33946.80 | 14-MAY-16:51 | 21.70 | 15.79 | 0.395234E+09 | 544.97 | 08-MAY-13:00 | 21.70 | 15.79 |
June | 0.966073E+10 | 35757.24 | 25-JUN-17:01 | 31.60 | 21.70 | 0.411847E+09 | 544.96 | 16-JUN-13:00 | 31.60 | 21.70 |
July | 0.106192E+11 | 34227.11 | 23-JUL-17:21 | 22.50 | 14.96 | 0.392554E+09 | 544.95 | 18-JUL-09:00 | 22.50 | 14.96 |
August | 0.991116E+10 | 30007.61 | 13-AUG-16:21 | 25.30 | 20.50 | 0.436759E+09 | 544.97 | 30-AUG-13:50 | 23.62 | 17.87 |
September | 0.634579E+10 | 32662.17 | 04-SEP-16:41 | 22.20 | 14.41 | 0.354402E+09 | 544.96 | 05-SEP-13:00 | 27.20 | 16.61 |
October | 0.303702E+10 | 11844.88 | 11-OCT-16:00 | 17.80 | 11.96 | 0.333169E+09 | 544.93 | 11-OCT-13:00 | 17.80 | 11.96 |
November | 0.121089E+10 | 7685.19 | 03-NOV-15:30 | 15.55 | 9.47 | 0.306031E+09 | 540.05 | 03-NOV-13:00 | 15.55 | 9.47 |
December | 0.358778E+09 | 3138.49 | 01-DEC-15:50 | -1.6 | -4.0 | 0.291814E+09 | 496.99 | 01-DEC-15:00 | -1.7 | -4.1 |
Annual Sum or Average | 0.557903E+11 | 0.417712E+10 | ||||||||
Minimum of Months | 0.291658E+09 | 3110.77 | -1.6 | -4.1 | 0.279335E+09 | 493.01 | -1.7 | -4.1 | ||
Maximum of Months | 0.106192E+11 | 35757.24 | 31.60 | 21.70 | 0.436759E+09 | 544.97 | 31.60 | 21.70 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.221737E+09 | 9965.23 | 06-JAN-05:11 | -26.7 | -26.9 | 0.00 | 0.00 | 01-JAN-00:10 | -26.7 | -26.9 |
February | 0.619780E+09 | 7849.35 | 04-FEB-05:01 | -30.6 | -30.8 | 0.00 | 0.00 | 01-FEB-00:10 | -30.6 | -30.8 |
March | 0.200714E+10 | 6026.62 | 13-MAR-05:01 | -9.6 | -10.8 | 0.00 | 0.00 | 01-MAR-00:10 | -9.6 | -10.8 |
April | 0.418815E+10 | 8129.39 | 17-APR-05:13 | 11.13 | 9.50 | 0.00 | 0.00 | 01-APR-00:10 | 11.13 | 9.50 |
May | 0.578844E+10 | 9531.26 | 30-MAY-05:15 | 14.60 | 14.60 | 0.00 | 0.00 | 01-MAY-00:10 | 14.60 | 14.60 |
June | 0.905337E+10 | 12440.41 | 27-JUN-05:10 | 20.28 | 18.95 | 0.00 | 0.00 | 01-JUN-00:10 | 20.28 | 18.95 |
July | 0.105270E+11 | 15729.97 | 05-JUL-05:10 | 18.07 | 17.58 | 0.00 | 0.00 | 01-JUL-00:10 | 18.07 | 17.58 |
August | 0.103220E+11 | 11267.57 | 28-AUG-05:15 | 18.50 | 18.02 | 0.00 | 0.00 | 01-AUG-00:10 | 18.50 | 18.02 |
September | 0.649092E+10 | 10405.71 | 11-SEP-05:03 | 19.90 | 17.36 | 0.00 | 0.00 | 01-SEP-00:10 | 19.90 | 17.36 |
October | 0.367573E+10 | 5640.67 | 10-OCT-05:15 | 11.23 | 10.40 | 0.00 | 0.00 | 01-OCT-00:10 | 11.23 | 10.40 |
November | 0.203960E+10 | 6382.29 | 25-NOV-06:01 | -16.9 | -17.2 | 0.00 | 0.00 | 01-NOV-00:10 | -16.9 | -17.2 |
December | 0.548517E+09 | 9034.00 | 09-DEC-05:01 | -22.8 | -23.0 | 0.00 | 0.00 | 01-DEC-00:10 | -22.8 | -23.0 |
Annual Sum or Average | 0.554824E+11 | 0.00 | ||||||||
Minimum of Months | 0.221737E+09 | 5640.67 | -30.6 | -30.8 | 0.00 | 0.00 | -30.6 | -30.8 | ||
Maximum of Months | 0.105270E+11 | 15729.97 | 20.28 | 18.95 | 0.00 | 0.00 | 20.28 | 18.95 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.602772E+09 | 11545.86 | 07-JAN-04:11 | -24.8 | -25.1 | 0.00 | 0.00 | 01-JAN-00:10 | -24.8 | -25.1 |
February | 0.291982E+09 | 11962.45 | 28-FEB-04:01 | -16.2 | -16.7 | 0.00 | 0.00 | 01-FEB-00:10 | -16.2 | -16.7 |
March | 0.687469E+09 | 11170.65 | 13-MAR-03:01 | -8.5 | -10.0 | 0.00 | 0.00 | 01-MAR-00:10 | -8.5 | -10.0 |
April | 0.197406E+10 | 11110.99 | 03-APR-03:01 | -6.2 | -7.2 | 0.00 | 0.00 | 01-APR-00:10 | -6.2 | -7.2 |
May | 0.367979E+10 | 6456.47 | 31-MAY-15:20 | 29.43 | 19.40 | 0.00 | 0.00 | 01-MAY-00:10 | 29.43 | 19.40 |
June | 0.629674E+10 | 8251.63 | 30-JUN-05:15 | 21.10 | 19.18 | 0.00 | 0.00 | 01-JUN-00:10 | 21.10 | 19.18 |
July | 0.685090E+10 | 7457.07 | 03-JUL-15:10 | 29.82 | 24.29 | 0.00 | 0.00 | 01-JUL-00:10 | 29.82 | 24.29 |
August | 0.683604E+10 | 7726.71 | 04-AUG-15:40 | 33.90 | 26.00 | 0.00 | 0.00 | 01-AUG-00:10 | 33.90 | 26.00 |
September | 0.444305E+10 | 7185.77 | 08-SEP-16:00 | 29.40 | 18.44 | 0.00 | 0.00 | 01-SEP-00:10 | 29.40 | 18.44 |
October | 0.146426E+10 | 7058.08 | 23-OCT-05:01 | -2.7 | -3.7 | 0.00 | 0.00 | 01-OCT-00:10 | -2.7 | -3.7 |
November | 0.902123E+09 | 12011.51 | 24-NOV-04:01 | -15.0 | -15.2 | 0.00 | 0.00 | 01-NOV-00:10 | -15.0 | -15.2 |
December | 0.383287E+09 | 10491.02 | 09-DEC-04:01 | -22.8 | -23.0 | 0.00 | 0.00 | 01-DEC-00:10 | -22.8 | -23.0 |
Annual Sum or Average | 0.344125E+11 | 0.00 | ||||||||
Minimum of Months | 0.291982E+09 | 6456.47 | -24.8 | -25.1 | 0.00 | 0.00 | -24.8 | -25.1 | ||
Maximum of Months | 0.685090E+10 | 12011.51 | 33.90 | 26.00 | 0.00 | 0.00 | 33.90 | 26.00 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -2.8 | -3.2 | 0.00 | 0.00 | 01-JAN-00:10 | -2.8 | -3.2 |
February | 20708827.24 | 1470.75 | 24-FEB-14:05 | 7.88 | 5.25 | 0.00 | 0.00 | 01-FEB-00:10 | 7.88 | 5.25 |
March | 0.455843E+09 | 5756.16 | 24-MAR-14:40 | 12.97 | 6.49 | 0.00 | 0.00 | 01-MAR-00:10 | 12.97 | 6.49 |
April | 0.280906E+10 | 15806.49 | 18-APR-15:10 | 27.75 | 20.46 | 0.00 | 0.00 | 01-APR-00:10 | 27.75 | 20.46 |
May | 0.631236E+10 | 18266.29 | 31-MAY-14:00 | 29.40 | 19.44 | 0.00 | 0.00 | 01-MAY-00:10 | 29.40 | 19.44 |
June | 0.108408E+11 | 20835.08 | 26-JUN-13:50 | 31.60 | 21.99 | 0.00 | 0.00 | 01-JUN-00:10 | 31.60 | 21.99 |
July | 0.118256E+11 | 19775.14 | 05-JUL-14:00 | 27.20 | 19.77 | 0.00 | 0.00 | 01-JUL-00:10 | 27.20 | 19.77 |
August | 0.109326E+11 | 20440.24 | 04-AUG-15:20 | 33.90 | 25.66 | 0.00 | 0.00 | 01-AUG-00:10 | 33.90 | 25.66 |
September | 0.559852E+10 | 17470.67 | 05-SEP-13:43 | 27.20 | 16.61 | 0.00 | 0.00 | 01-SEP-00:10 | 27.20 | 16.61 |
October | 0.920566E+09 | 7482.08 | 20-OCT-15:00 | 23.30 | 13.36 | 0.00 | 0.00 | 01-OCT-00:10 | 23.30 | 13.36 |
November | 0.165931E+09 | 4255.16 | 03-NOV-14:40 | 16.10 | 9.89 | 0.00 | 0.00 | 01-NOV-00:10 | 16.10 | 9.89 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.3 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.3 |
Annual Sum or Average | 0.498820E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -2.8 | -3.2 | 0.00 | 0.00 | -2.8 | -3.2 | ||
Maximum of Months | 0.118256E+11 | 20835.08 | 33.90 | 25.66 | 0.00 | 0.00 | 33.90 | 25.66 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.180670E+10 | 2067.14 | 12-JAN-16:30 | 2.25 | 0.82 | 95198468.71 | 126.82 | 02-JAN-10:09 | 2.25 | 0.82 |
February | 0.701411E+10 | 4370.13 | 24-FEB-17:00 | 7.20 | 5.13 | 86396443.52 | 126.82 | 02-FEB-14:09 | 7.20 | 5.13 |
March | 0.137938E+11 | 6971.46 | 31-MAR-24:00 | -1.0 | -2.0 | 0.103236E+09 | 126.83 | 29-MAR-13:00 | -1.0 | -2.0 |
April | 0.187950E+11 | 8501.03 | 16-APR-17:52 | 26.70 | 19.84 | 91605628.35 | 126.83 | 11-APR-13:00 | 26.70 | 19.84 |
May | 0.443097E+10 | 3558.45 | 31-MAY-24:00 | 15.10 | 10.22 | 99241619.45 | 126.85 | 11-MAY-13:00 | 15.10 | 10.22 |
June | 0.950795E+10 | 5447.51 | 30-JUN-23:40 | 19.43 | 15.96 | 98971191.06 | 126.86 | 13-JUN-13:20 | 19.43 | 15.96 |
July | 0.150094E+11 | 7260.83 | 31-JUL-23:52 | 18.20 | 17.87 | 91891337.23 | 126.85 | 20-JUL-09:09 | 18.20 | 17.87 |
August | 0.199933E+11 | 8431.30 | 29-AUG-17:50 | 21.38 | 14.81 | 0.103301E+09 | 130.36 | 04-AUG-13:00 | 21.38 | 14.81 |
September | 0.435536E+10 | 3071.79 | 30-SEP-24:00 | 3.90 | 1.09 | 91611002.72 | 126.86 | 11-SEP-13:09 | 3.90 | 1.09 |
October | 0.912124E+10 | 5060.98 | 31-OCT-24:00 | 1.50 | -0.9 | 95230773.46 | 126.84 | 02-OCT-13:00 | 1.50 | -0.9 |
November | 0.131727E+11 | 6241.47 | 05-NOV-16:17 | 13.70 | 9.80 | 94301240.60 | 126.84 | 08-NOV-10:00 | 13.90 | 12.62 |
December | 0.181514E+11 | 7945.08 | 05-DEC-16:10 | -5.1 | -8.3 | 91880811.54 | 126.82 | 05-DEC-10:09 | -5.1 | -8.3 |
Annual Sum or Average | 0.135152E+12 | 0.114287E+10 | ||||||||
Minimum of Months | 0.180670E+10 | 2067.14 | -5.1 | -8.3 | 86396443.52 | 126.82 | -5.1 | -8.3 | ||
Maximum of Months | 0.199933E+11 | 8501.03 | 26.70 | 19.84 | 0.103301E+09 | 130.36 | 26.70 | 19.84 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.403143E+09 | 1680.27 | 12-JAN-16:40 | 2.07 | 0.72 | 90736072.22 | 126.82 | 18-JAN-14:50 | -17.1 | -17.4 |
February | 0.444812E+10 | 3979.05 | 24-FEB-17:00 | 7.20 | 5.13 | 86396462.43 | 126.82 | 02-FEB-14:09 | 7.20 | 5.13 |
March | 0.112961E+11 | 6160.19 | 31-MAR-23:30 | -0.5 | -1.5 | 0.103236E+09 | 126.83 | 29-MAR-13:00 | -0.5 | -1.5 |
April | 0.167573E+11 | 7962.05 | 16-APR-17:52 | 26.70 | 19.84 | 91605750.72 | 126.83 | 11-APR-13:00 | 26.70 | 19.84 |
May | 0.366310E+10 | 3344.67 | 31-MAY-24:00 | 15.10 | 10.22 | 99239059.89 | 126.85 | 31-MAY-13:00 | 15.10 | 10.22 |
June | 0.874575E+10 | 5230.05 | 30-JUN-23:53 | 19.10 | 15.95 | 98971343.75 | 126.86 | 13-JUN-13:50 | 19.10 | 15.95 |
July | 0.141024E+11 | 6897.96 | 31-JUL-23:52 | 18.20 | 17.87 | 91892811.08 | 126.85 | 17-JUL-13:00 | 18.20 | 17.87 |
August | 0.188464E+11 | 8070.67 | 29-AUG-17:50 | 21.38 | 14.81 | 0.103249E+09 | 126.83 | 31-AUG-09:00 | 21.10 | 20.75 |
September | 0.353320E+10 | 2668.31 | 04-SEP-17:50 | 20.87 | 14.10 | 91609947.77 | 126.85 | 06-SEP-13:00 | 32.20 | 21.19 |
October | 0.730008E+10 | 4328.45 | 31-OCT-23:50 | 1.35 | -1.0 | 95230734.60 | 126.84 | 02-OCT-13:00 | 1.35 | -1.0 |
November | 0.103848E+11 | 5695.05 | 03-NOV-16:00 | 15.00 | 9.33 | 94301146.30 | 126.83 | 08-NOV-10:00 | 13.90 | 12.62 |
December | 0.142683E+11 | 7191.06 | 01-DEC-16:20 | -2.4 | -4.5 | 91880831.46 | 126.82 | 05-DEC-10:09 | -5.9 | -8.1 |
Annual Sum or Average | 0.113749E+12 | 0.113835E+10 | ||||||||
Minimum of Months | 0.403143E+09 | 1680.27 | -2.4 | -4.5 | 86396462.43 | 126.82 | -17.1 | -17.4 | ||
Maximum of Months | 0.188464E+11 | 8070.67 | 26.70 | 19.84 | 0.103249E+09 | 126.86 | 32.20 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.286293E+09 | 1567.83 | 12-JAN-16:40 | 2.07 | 0.72 | 85280180.75 | 126.84 | 09-JAN-14:30 | 2.07 | 0.72 |
February | 0.291901E+10 | 3936.52 | 24-FEB-17:00 | 7.20 | 5.13 | 86381549.76 | 126.82 | 02-FEB-14:09 | 7.20 | 5.13 |
March | 0.979243E+10 | 5813.94 | 21-MAR-17:40 | -1.8 | -4.9 | 0.103236E+09 | 126.83 | 29-MAR-13:00 | 8.90 | 7.98 |
April | 0.156721E+11 | 8223.45 | 16-APR-17:42 | 26.97 | 19.92 | 91605792.77 | 126.83 | 11-APR-13:00 | 26.97 | 19.92 |
May | 0.322712E+10 | 3307.57 | 31-MAY-23:40 | 15.90 | 10.90 | 99239000.24 | 126.86 | 30-MAY-13:39 | 15.90 | 10.90 |
June | 0.857296E+10 | 5208.00 | 30-JUN-23:53 | 19.10 | 15.95 | 98971406.30 | 126.87 | 13-JUN-13:30 | 19.10 | 15.95 |
July | 0.140524E+11 | 6796.14 | 31-JUL-23:52 | 18.20 | 17.87 | 91892802.04 | 126.85 | 07-JUL-13:09 | 18.20 | 17.87 |
August | 0.187305E+11 | 8130.32 | 29-AUG-17:40 | 21.67 | 14.89 | 0.103248E+09 | 126.83 | 31-AUG-09:00 | 21.10 | 20.75 |
September | 0.299467E+10 | 2702.76 | 04-SEP-17:50 | 20.87 | 14.10 | 91598698.67 | 126.85 | 11-SEP-13:00 | 28.90 | 20.23 |
October | 0.579019E+10 | 4170.28 | 11-OCT-17:00 | 16.70 | 11.06 | 95230712.08 | 126.84 | 02-OCT-13:00 | 16.70 | 11.06 |
November | 0.854605E+10 | 5674.04 | 03-NOV-16:00 | 15.00 | 9.33 | 94301148.79 | 126.83 | 08-NOV-10:00 | 13.90 | 12.62 |
December | 0.123926E+11 | 7058.11 | 01-DEC-16:20 | -2.4 | -4.5 | 91880837.67 | 126.82 | 05-DEC-10:09 | -5.9 | -8.1 |
Annual Sum or Average | 0.102976E+12 | 0.113287E+10 | ||||||||
Minimum of Months | 0.286293E+09 | 1567.83 | -2.4 | -4.9 | 85280180.75 | 126.82 | -5.9 | -8.1 | ||
Maximum of Months | 0.187305E+11 | 8223.45 | 26.97 | 19.92 | 0.103248E+09 | 126.87 | 28.90 | 20.75 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.233906E+12 | 91275.89 | 13-JAN-17:00 | 2.20 | 0.77 | 0.206144E+10 | 2745.29 | 04-JAN-14:00 | 2.20 | 0.77 |
February | 0.432736E+12 | 183136.53 | 24-FEB-17:00 | 7.20 | 5.13 | 0.187024E+10 | 2745.42 | 06-FEB-10:30 | 7.20 | 5.13 |
March | 0.727018E+12 | 358311.84 | 31-MAR-24:00 | -1.0 | -2.0 | 0.223477E+10 | 2745.40 | 16-MAR-09:09 | -1.0 | -2.0 |
April | 0.941377E+12 | 368026.96 | 17-APR-16:00 | 19.40 | 11.31 | 0.199394E+10 | 3253.76 | 18-APR-13:00 | 28.30 | 20.65 |
May | 0.240504E+12 | 176666.46 | 31-MAY-24:00 | 15.10 | 10.22 | 0.214807E+10 | 2746.53 | 04-MAY-13:39 | 15.10 | 10.22 |
June | 0.471548E+12 | 269277.70 | 30-JUN-23:57 | 19.10 | 15.95 | 0.214244E+10 | 2748.79 | 21-JUN-13:00 | 19.10 | 15.95 |
July | 0.733957E+12 | 360596.12 | 31-JUL-23:52 | 18.20 | 17.87 | 0.202848E+10 | 3709.03 | 26-JUL-15:09 | 18.20 | 17.87 |
August | 0.976970E+12 | 392716.94 | 04-AUG-17:53 | 20.60 | 19.43 | 0.245989E+10 | 5004.01 | 04-AUG-13:09 | 20.60 | 19.43 |
September | 0.236545E+12 | 175419.04 | 30-SEP-24:00 | 3.90 | 1.09 | 0.198303E+10 | 2746.66 | 11-SEP-13:00 | 3.90 | 1.09 |
October | 0.486795E+12 | 268159.32 | 31-OCT-24:00 | 1.50 | -0.9 | 0.206143E+10 | 2745.67 | 11-OCT-09:09 | 1.50 | -0.9 |
November | 0.706452E+12 | 276767.59 | 03-NOV-16:00 | 15.00 | 9.33 | 0.204129E+10 | 2746.23 | 02-NOV-13:09 | 15.00 | 9.33 |
December | 0.972889E+12 | 367619.77 | 05-DEC-17:00 | -5.6 | -8.5 | 0.198895E+10 | 2745.46 | 14-DEC-10:00 | -1.7 | -2.6 |
Annual Sum or Average | 0.716070E+13 | 0.250140E+11 | ||||||||
Minimum of Months | 0.233906E+12 | 91275.89 | -5.6 | -8.5 | 0.187024E+10 | 2745.29 | -1.7 | -2.6 | ||
Maximum of Months | 0.976970E+12 | 392716.94 | 20.60 | 19.43 | 0.245989E+10 | 5004.01 | 28.30 | 20.65 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -2.8 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -24.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 281393.73 | 468.99 | 21-JUN-06:30 | 15.30 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 |
Annual Sum or Average | 281393.73 | |||
Minimum of Months | 0.00 | 0.00 | -24.1 | |
Maximum of Months | 281393.73 | 468.99 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -2.8 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -24.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -24.1 | |
Maximum of Months | 0.00 | 0.00 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134035E+10 | 56569.33 | 02-JAN-04:01 | -4.0 |
February | 0.262029E+09 | 50337.72 | 06-FEB-05:11 | -14.6 |
March | 15819454.39 | 45174.76 | 06-MAR-06:01 | -14.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.198196E+09 | 49961.60 | 27-NOV-05:01 | -9.4 |
December | 0.407289E+09 | 50099.35 | 11-DEC-05:11 | -22.2 |
Annual Sum or Average | 0.222368E+10 | |||
Minimum of Months | 0.00 | 0.00 | -22.2 | |
Maximum of Months | 0.134035E+10 | 56569.33 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.974507E+10 | 80834.96 | 02-JAN-04:01 | -4.0 |
February | 0.535179E+10 | 80599.52 | 06-FEB-04:01 | -14.4 |
March | 0.178470E+10 | 78494.86 | 06-MAR-04:01 | -16.0 |
April | 0.581107E+09 | 76937.91 | 03-APR-03:01 | -6.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.15 |
September | 1907589.81 | 15896.58 | 30-SEP-05:02 | 0.10 |
October | 0.183401E+09 | 67819.11 | 16-OCT-04:11 | 1.57 |
November | 0.350670E+10 | 80605.17 | 27-NOV-04:11 | -10.2 |
December | 0.624663E+10 | 81075.91 | 11-DEC-04:01 | -21.8 |
Annual Sum or Average | 0.274013E+11 | |||
Minimum of Months | 0.00 | 0.00 | -21.8 | |
Maximum of Months | 0.974507E+10 | 81075.91 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.240586E+10 | 14039.30 | 30-JAN-04:01 | -27.3 |
February | 0.128783E+10 | 13901.53 | 02-FEB-04:01 | -35.2 |
March | 60058517.52 | 12362.65 | 06-MAR-05:01 | -15.4 |
April | 1312287.35 | 11513.58 | 03-APR-05:01 | -7.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.200602E+09 | 12482.45 | 27-NOV-05:01 | -9.4 |
December | 0.588702E+09 | 13240.46 | 11-DEC-04:01 | -21.8 |
Annual Sum or Average | 0.454436E+10 | |||
Minimum of Months | 0.00 | 0.00 | -35.2 | |
Maximum of Months | 0.240586E+10 | 14039.30 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.144585E+10 | 16055.93 | 30-JAN-04:01 | -27.3 |
February | 0.701383E+09 | 15993.70 | 02-FEB-04:01 | -35.2 |
March | 75454970.21 | 14022.03 | 06-MAR-05:01 | -15.4 |
April | 4494791.71 | 12775.64 | 03-APR-05:01 | -7.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 10505.47 | 70.04 | 28-OCT-05:05 | -1.7 |
November | 0.171475E+09 | 14386.67 | 27-NOV-05:01 | -9.4 |
December | 0.641400E+09 | 15384.70 | 11-DEC-04:01 | -21.8 |
Annual Sum or Average | 0.304007E+10 | |||
Minimum of Months | 0.00 | 0.00 | -35.2 | |
Maximum of Months | 0.144585E+10 | 16055.93 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.201722E+10 | 21952.86 | 30-JAN-04:01 | -27.3 |
February | 0.867246E+09 | 21578.60 | 02-FEB-04:01 | -35.2 |
March | 0.170181E+09 | 19937.96 | 06-MAR-05:01 | -15.4 |
April | 26620987.87 | 18510.29 | 03-APR-04:01 | -6.8 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 122515.39 | 1429.35 | 23-OCT-05:01 | -2.7 |
November | 0.299241E+09 | 20357.43 | 28-NOV-05:01 | -21.1 |
December | 0.940104E+09 | 21455.19 | 11-DEC-04:01 | -21.8 |
Annual Sum or Average | 0.432074E+10 | |||
Minimum of Months | 0.00 | 0.00 | -35.2 | |
Maximum of Months | 0.201722E+10 | 21952.86 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.686591E+09 | 13577.65 | 30-JAN-05:01 | -27.9 |
February | 0.269940E+09 | 13572.31 | 02-FEB-05:01 | -36.2 |
March | 1524881.90 | 11310.29 | 06-MAR-06:01 | -14.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 7107783.40 | 11202.95 | 25-NOV-06:01 | -16.9 |
December | 26937315.19 | 12446.94 | 09-DEC-05:01 | -22.8 |
Annual Sum or Average | 0.992101E+09 | |||
Minimum of Months | 0.00 | 0.00 | -36.2 | |
Maximum of Months | 0.686591E+09 | 13577.65 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106343E+11 | 14651.34 | 29-JAN-22:52 | -25.0 |
February | 0.572268E+10 | 14209.22 | 03-FEB-03:32 | -33.7 |
March | 0.196200E+10 | 13768.16 | 06-MAR-03:43 | -16.2 |
April | 0.372256E+09 | 13159.14 | 03-APR-03:01 | -6.2 |
May | 3453335.14 | 10046.31 | 02-MAY-05:03 | 2.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.15 |
September | 19378139.43 | 10995.60 | 30-SEP-05:02 | 0.10 |
October | 0.200226E+09 | 11459.36 | 16-OCT-04:11 | 1.57 |
November | 0.296158E+10 | 14236.16 | 26-NOV-22:52 | -13.3 |
December | 0.705565E+10 | 14132.30 | 11-DEC-01:51 | -21.7 |
Annual Sum or Average | 0.289315E+11 | |||
Minimum of Months | 0.00 | 0.00 | -33.7 | |
Maximum of Months | 0.106343E+11 | 14651.34 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.610727E+10 | 21748.15 | 29-JAN-07:32 | -22.6 |
February | 0.301081E+10 | 21200.86 | 03-FEB-04:11 | -33.9 |
March | 0.102774E+10 | 20261.85 | 06-MAR-04:01 | -16.0 |
April | 0.214930E+09 | 19934.87 | 03-APR-03:01 | -6.2 |
May | 1385122.99 | 5588.98 | 02-MAY-05:03 | 2.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.15 |
September | 9939218.13 | 12311.89 | 30-SEP-05:02 | 0.10 |
October | 0.112424E+09 | 15220.98 | 19-OCT-05:02 | 1.62 |
November | 0.174836E+10 | 21331.35 | 26-NOV-22:52 | -13.3 |
December | 0.430745E+10 | 21266.15 | 11-DEC-01:51 | -21.7 |
Annual Sum or Average | 0.165403E+11 | |||
Minimum of Months | 0.00 | 0.00 | -33.9 | |
Maximum of Months | 0.610727E+10 | 21748.15 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.593853E+10 | 23899.22 | 29-JAN-06:12 | -21.5 |
February | 0.266123E+10 | 22948.18 | 03-FEB-04:11 | -33.9 |
March | 0.114312E+10 | 22304.07 | 06-MAR-04:01 | -16.0 |
April | 0.242869E+09 | 21757.80 | 03-APR-03:01 | -6.2 |
May | 1201062.38 | 5496.69 | 02-MAY-05:03 | 2.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.15 |
September | 11200624.61 | 15826.24 | 30-SEP-05:02 | 0.10 |
October | 74618310.08 | 18073.53 | 23-OCT-05:01 | -2.7 |
November | 0.174400E+10 | 23432.08 | 27-NOV-03:32 | -10.6 |
December | 0.457751E+10 | 23202.07 | 09-DEC-05:01 | -22.8 |
Annual Sum or Average | 0.163943E+11 | |||
Minimum of Months | 0.00 | 0.00 | -33.9 | |
Maximum of Months | 0.593853E+10 | 23899.22 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.533080E+10 | 21846.97 | 30-JAN-04:11 | -27.4 |
February | 0.247441E+10 | 21341.81 | 03-FEB-04:11 | -33.9 |
March | 0.748714E+09 | 20517.47 | 06-MAR-04:01 | -16.0 |
April | 0.112113E+09 | 19612.83 | 03-APR-03:01 | -6.2 |
May | 891961.51 | 3820.85 | 02-MAY-05:03 | 2.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.15 |
September | 12110352.09 | 13764.42 | 30-SEP-05:02 | 0.10 |
October | 63976908.08 | 14588.45 | 23-OCT-05:01 | -2.7 |
November | 0.134861E+10 | 21139.83 | 27-NOV-04:11 | -10.2 |
December | 0.330002E+10 | 21305.48 | 09-DEC-05:01 | -22.8 |
Annual Sum or Average | 0.133916E+11 | |||
Minimum of Months | 0.00 | 0.00 | -33.9 | |
Maximum of Months | 0.533080E+10 | 21846.97 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.166835E+11 | 18713.91 | 30-JAN-05:11 | -28.0 |
February | 0.103545E+11 | 17929.74 | 01-FEB-04:11 | -29.6 |
March | 0.490837E+10 | 17483.53 | 06-MAR-00:42 | -17.0 |
April | 0.157875E+10 | 16932.81 | 03-APR-01:42 | -6.1 |
May | 60001266.05 | 13830.83 | 02-MAY-04:12 | 2.60 |
June | 1963517.95 | 6893.90 | 02-JUN-05:02 | 7.20 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.15 |
September | 0.225872E+09 | 14712.64 | 30-SEP-04:01 | -0.5 |
October | 0.128972E+10 | 16069.34 | 16-OCT-04:11 | 1.57 |
November | 0.646072E+10 | 17853.26 | 26-NOV-06:12 | -27.0 |
December | 0.127914E+11 | 18004.83 | 09-DEC-05:01 | -22.8 |
Annual Sum or Average | 0.543548E+11 | |||
Minimum of Months | 0.00 | 0.00 | -29.6 | |
Maximum of Months | 0.166835E+11 | 18713.91 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.987287E+10 | 23704.07 | 30-JAN-05:11 | -28.0 |
February | 0.566472E+10 | 23567.58 | 01-FEB-04:11 | -29.6 |
March | 0.255416E+10 | 22643.39 | 06-MAR-04:01 | -16.0 |
April | 0.868616E+09 | 22135.64 | 03-APR-03:01 | -6.2 |
May | 19188190.66 | 12815.31 | 02-MAY-04:12 | 2.60 |
June | 958507.88 | 3464.33 | 02-JUN-05:02 | 7.20 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.15 |
September | 0.116820E+09 | 19049.65 | 30-SEP-04:01 | -0.5 |
October | 0.652429E+09 | 20735.60 | 16-OCT-04:11 | 1.57 |
November | 0.382617E+10 | 23228.87 | 26-NOV-22:52 | -13.3 |
December | 0.774086E+10 | 23297.82 | 09-DEC-05:01 | -22.8 |
Annual Sum or Average | 0.313168E+11 | |||
Minimum of Months | 0.00 | 0.00 | -29.6 | |
Maximum of Months | 0.987287E+10 | 23704.07 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108089E+11 | 26310.24 | 30-JAN-05:11 | -28.0 |
February | 0.594962E+10 | 26136.32 | 01-FEB-04:11 | -29.6 |
March | 0.329038E+10 | 25264.32 | 06-MAR-04:01 | -16.0 |
April | 0.122471E+10 | 24937.19 | 03-APR-03:01 | -6.2 |
May | 41304567.39 | 17493.35 | 03-MAY-05:02 | 1.38 |
June | 2772111.13 | 7017.05 | 03-JUN-05:03 | 5.78 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.15 |
September | 0.151539E+09 | 21380.95 | 30-SEP-04:01 | -0.5 |
October | 0.722108E+09 | 23150.95 | 16-OCT-04:11 | 1.57 |
November | 0.420727E+10 | 26242.68 | 27-NOV-02:12 | -10.9 |
December | 0.901311E+10 | 26211.59 | 09-DEC-05:01 | -22.8 |
Annual Sum or Average | 0.354117E+11 | |||
Minimum of Months | 0.00 | 0.00 | -29.6 | |
Maximum of Months | 0.108089E+11 | 26310.24 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.905620E+10 | 25705.37 | 30-JAN-05:11 | -28.0 |
February | 0.467936E+10 | 25280.94 | 01-FEB-04:11 | -29.6 |
March | 0.202117E+10 | 24244.74 | 06-MAR-04:01 | -16.0 |
April | 0.541870E+09 | 23818.90 | 03-APR-03:01 | -6.2 |
May | 18459475.61 | 9483.85 | 02-MAY-05:03 | 2.20 |
June | 503239.37 | 2705.75 | 02-JUN-05:02 | 7.20 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.15 |
September | 96447727.93 | 20714.14 | 30-SEP-04:01 | -0.5 |
October | 0.472287E+09 | 22029.78 | 16-OCT-04:11 | 1.57 |
November | 0.288397E+10 | 24882.19 | 26-NOV-06:12 | -27.0 |
December | 0.613796E+10 | 25333.13 | 09-DEC-05:01 | -22.8 |
Annual Sum or Average | 0.259082E+11 | |||
Minimum of Months | 0.00 | 0.00 | -29.6 | |
Maximum of Months | 0.905620E+10 | 25705.37 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.221698E+10 | 9363.27 | 13-JAN-06:01 | -1.7 |
February | 0.127796E+10 | 10996.67 | 08-FEB-06:03 | 1.70 |
March | 0.339751E+09 | 12940.63 | 19-MAR-14:52 | 18.30 |
April | 0.151592E+09 | 12936.26 | 24-APR-04:12 | 11.70 |
May | 88300878.20 | 9703.19 | 14-MAY-14:42 | 21.60 |
June | 0.106051E+09 | 11446.06 | 25-JUN-15:11 | 32.20 |
July | 0.160593E+09 | 11701.17 | 02-JUL-15:31 | 29.40 |
August | 0.128774E+09 | 11302.98 | 13-AUG-15:21 | 25.85 |
September | 79392294.09 | 10178.32 | 01-SEP-04:12 | 13.30 |
October | 0.112601E+09 | 13664.34 | 01-OCT-14:42 | 19.33 |
November | 0.431725E+09 | 11937.57 | 20-NOV-05:11 | 7.77 |
December | 0.879035E+09 | 11989.57 | 05-DEC-05:01 | 0.37 |
Annual Sum or Average | 0.597275E+10 | |||
Minimum of Months | 79392294.09 | 9363.27 | -1.7 | |
Maximum of Months | 0.221698E+10 | 13664.34 | 32.20 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.684204E+10 | 19945.66 | 02-JAN-06:12 | -5.2 |
February | 0.370812E+10 | 13282.87 | 20-FEB-14:22 | 2.80 |
March | 0.179916E+10 | 9398.35 | 19-MAR-13:02 | 16.97 |
April | 0.608148E+09 | 15745.68 | 23-APR-15:31 | 17.03 |
May | 91325531.16 | 9053.07 | 21-MAY-15:12 | 18.17 |
June | 64801403.19 | 14162.52 | 11-JUN-15:11 | 33.13 |
July | 85259849.70 | 12704.14 | 02-JUL-15:41 | 29.40 |
August | 55460712.75 | 10120.90 | 13-AUG-15:31 | 25.77 |
September | 68915784.73 | 11848.70 | 17-SEP-14:41 | 27.20 |
October | 0.326291E+09 | 14574.50 | 01-OCT-15:11 | 18.97 |
November | 0.197380E+10 | 10521.01 | 27-NOV-06:05 | -9.4 |
December | 0.427142E+10 | 12793.01 | 11-DEC-06:12 | -22.0 |
Annual Sum or Average | 0.198947E+11 | |||
Minimum of Months | 55460712.75 | 9053.07 | -22.0 | |
Maximum of Months | 0.684204E+10 | 19945.66 | 33.13 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.211920E+11 | 38153.46 | 30-JAN-05:22 | -28.1 |
February | 0.136533E+11 | 36314.31 | 02-FEB-05:06 | -36.2 |
March | 0.712600E+10 | 30736.44 | 06-MAR-05:31 | -14.8 |
April | 0.297811E+10 | 25286.41 | 03-APR-05:12 | -7.2 |
May | 0.480382E+09 | 14170.07 | 06-MAY-05:03 | 9.40 |
June | 0.179888E+09 | 15053.89 | 22-JUN-05:03 | 9.68 |
July | 89932496.13 | 13317.54 | 12-JUL-05:03 | 12.98 |
August | 0.124958E+09 | 14857.00 | 07-AUG-05:03 | 8.80 |
September | 0.901706E+09 | 13501.67 | 02-SEP-05:03 | 9.40 |
October | 0.269950E+10 | 13585.59 | 16-OCT-05:02 | 0.48 |
November | 0.930561E+10 | 28937.78 | 27-NOV-05:13 | -9.4 |
December | 0.168083E+11 | 33781.72 | 11-DEC-05:32 | -22.2 |
Annual Sum or Average | 0.755397E+11 | |||
Minimum of Months | 89932496.13 | 13317.54 | -36.2 | |
Maximum of Months | 0.211920E+11 | 38153.46 | 12.98 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4632077.28 | 497.99 | 29-JAN-23:49 | -25.5 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -24.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 |
Annual Sum or Average | 4632077.28 | |||
Minimum of Months | 0.00 | 0.00 | -25.5 | |
Maximum of Months | 4632077.28 | 497.99 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.725282E+09 | 628.19 | 29-JAN-18:02 | -22.9 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -24.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 |
Annual Sum or Average | 0.725282E+09 | |||
Minimum of Months | 0.00 | 0.00 | -24.1 | |
Maximum of Months | 0.725282E+09 | 628.19 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.805349E+09 | 650.82 | 29-JAN-18:02 | -22.9 |
February | 0.137419E+09 | 591.68 | 05-FEB-20:02 | -19.7 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 1466222.71 | 386.46 | 02-MAY-02:45 | 2.80 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.15 |
September | 16811367.80 | 562.53 | 30-SEP-04:15 | -0.4 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 |
Annual Sum or Average | 0.961045E+09 | |||
Minimum of Months | 0.00 | 0.00 | -22.9 | |
Maximum of Months | 0.805349E+09 | 650.82 | 18.93 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -2.8 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -24.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -11.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | -1.2 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 8.22 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14.70 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 18.93 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.15 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 3.92 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 1.65 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -24.1 | |
Maximum of Months | 0.00 | 0.00 | 18.93 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180249E+11 | 19402.09 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.163527E+11 | 19402.09 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.194806E+11 | 19402.09 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.173504E+11 | 19402.09 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.187528E+11 | 19402.09 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.186803E+11 | 19402.09 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.174228E+11 | 19402.09 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.194803E+11 | 19402.09 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.173504E+11 | 19402.09 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.180252E+11 | 19402.09 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.178272E+11 | 19402.09 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.174231E+11 | 19402.09 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.216171E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.163527E+11 | 19402.09 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.194806E+11 | 19402.09 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135351E+10 | 2187.81 | 02-JAN-16:19 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.113093E+10 | 1906.53 | 01-FEB-16:49 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.123112E+10 | 1524.25 | 01-MAR-16:49 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.106320E+10 | 1524.25 | 10-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.110171E+10 | 1040.96 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.109154E+10 | 1242.97 | 13-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.102387E+10 | 1242.97 | 20-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.115263E+10 | 1141.96 | 28-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.108032E+10 | 1524.25 | 21-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.119012E+10 | 2187.81 | 30-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.131290E+10 | 2187.81 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.139466E+10 | 2187.81 | 01-DEC-16:10 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.141265E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.102387E+10 | 1040.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.139466E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.849858E+09 | 1409.91 | 02-JAN-16:19 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.715394E+09 | 1228.64 | 01-FEB-16:49 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.789695E+09 | 982.28 | 01-MAR-16:40 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.683562E+09 | 801.02 | 10-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.716241E+09 | 735.93 | 09-MAY-15:20 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.708005E+09 | 735.93 | 05-JUN-15:30 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.662944E+09 | 735.93 | 20-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.746209E+09 | 670.83 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.695482E+09 | 801.02 | 13-SEP-15:39 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.753119E+09 | 1409.91 | 31-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.830839E+09 | 1409.91 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.867281E+09 | 1409.91 | 01-DEC-16:10 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.901863E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.662944E+09 | 670.83 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.867281E+09 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.128408E+10 | 2187.86 | 02-JAN-16:40 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.108815E+10 | 1906.57 | 14-FEB-16:49 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.122012E+10 | 1524.28 | 01-MAR-16:00 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.106193E+10 | 1524.28 | 10-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.110950E+10 | 1040.98 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.109843E+10 | 1243.00 | 13-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.102894E+10 | 1243.00 | 20-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.115896E+10 | 1141.99 | 28-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.107471E+10 | 1524.28 | 21-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.115643E+10 | 2187.86 | 31-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.126140E+10 | 2187.86 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.129975E+10 | 2187.86 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.138424E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.102894E+10 | 1040.98 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.129975E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.845790E+09 | 1409.91 | 02-JAN-16:40 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.710259E+09 | 1228.64 | 14-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.789345E+09 | 982.28 | 13-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.683273E+09 | 982.28 | 10-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.710391E+09 | 735.93 | 15-MAY-08:20 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.702811E+09 | 801.02 | 13-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.660640E+09 | 801.02 | 20-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.743433E+09 | 735.93 | 23-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.691781E+09 | 982.28 | 12-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.759296E+09 | 1409.91 | 30-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.824489E+09 | 1409.91 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.862119E+09 | 1409.91 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.898363E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.660640E+09 | 735.93 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.862119E+09 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.134881E+10 | 2187.81 | 02-JAN-16:19 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.112690E+10 | 1906.53 | 01-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.122902E+10 | 1524.25 | 01-MAR-16:49 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.106109E+10 | 1524.25 | 10-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.110108E+10 | 1040.96 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.109051E+10 | 1141.96 | 05-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.102298E+10 | 1141.96 | 20-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.115161E+10 | 1141.96 | 31-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.107802E+10 | 1524.25 | 21-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.118662E+10 | 2187.81 | 30-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.130816E+10 | 2187.81 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.138700E+10 | 2187.81 | 01-DEC-16:10 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.140918E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.102298E+10 | 1040.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.138700E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.847420E+09 | 1409.91 | 02-JAN-16:19 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.714091E+09 | 1228.64 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.788729E+09 | 982.28 | 01-MAR-16:40 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.682763E+09 | 801.02 | 10-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.715611E+09 | 735.93 | 09-MAY-15:20 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.707551E+09 | 735.93 | 09-JUN-15:50 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.662516E+09 | 735.93 | 20-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.745780E+09 | 670.83 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.694259E+09 | 801.02 | 13-SEP-15:50 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.752195E+09 | 1409.91 | 31-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.828660E+09 | 1409.91 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.863924E+09 | 1409.91 | 01-DEC-16:10 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.900350E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.662516E+09 | 670.83 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.863924E+09 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.128313E+10 | 2187.86 | 02-JAN-16:40 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.108489E+10 | 1906.57 | 14-FEB-16:49 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.121906E+10 | 1524.28 | 01-MAR-16:00 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.105966E+10 | 1524.28 | 10-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.110880E+10 | 1040.98 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.109755E+10 | 1243.00 | 13-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.102815E+10 | 1243.00 | 20-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.115806E+10 | 1141.99 | 31-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.107366E+10 | 1524.28 | 21-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.115541E+10 | 2187.86 | 31-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.126043E+10 | 2187.86 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.129694E+10 | 2187.86 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.138257E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.102815E+10 | 1040.98 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.129694E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.843569E+09 | 1409.91 | 02-JAN-16:40 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.708742E+09 | 1228.64 | 14-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.788233E+09 | 982.28 | 13-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.682072E+09 | 982.28 | 10-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.709851E+09 | 735.93 | 15-MAY-08:30 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.702193E+09 | 801.02 | 13-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.659893E+09 | 801.02 | 20-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.742971E+09 | 735.93 | 23-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.690929E+09 | 982.28 | 21-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.757728E+09 | 1409.91 | 30-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.822884E+09 | 1409.91 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.859718E+09 | 1409.91 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.896878E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.659893E+09 | 735.93 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.859718E+09 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.134875E+10 | 2187.81 | 02-JAN-16:19 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.112672E+10 | 1906.53 | 01-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.122882E+10 | 1524.25 | 01-MAR-16:49 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.106109E+10 | 1524.25 | 10-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.110107E+10 | 1040.96 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.109051E+10 | 1141.96 | 05-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.102290E+10 | 1141.96 | 20-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.115155E+10 | 1141.96 | 31-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.107777E+10 | 1524.25 | 21-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.118653E+10 | 2187.81 | 30-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.130779E+10 | 2187.81 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.138661E+10 | 2187.81 | 01-DEC-16:10 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.140901E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.102290E+10 | 1040.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.138661E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.847407E+09 | 1409.91 | 02-JAN-16:19 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.714013E+09 | 1228.64 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.788664E+09 | 982.28 | 01-MAR-16:40 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.682755E+09 | 801.02 | 10-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.715550E+09 | 735.93 | 09-MAY-15:20 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.707538E+09 | 735.93 | 09-JUN-15:50 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.662516E+09 | 735.93 | 20-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.745780E+09 | 670.83 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.694211E+09 | 801.02 | 13-SEP-15:50 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.752113E+09 | 1409.91 | 31-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.828660E+09 | 1409.91 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.863808E+09 | 1409.91 | 01-DEC-16:10 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.900302E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.662516E+09 | 670.83 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.863808E+09 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.128307E+10 | 2187.86 | 02-JAN-16:40 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.108483E+10 | 1906.57 | 14-FEB-16:49 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.121891E+10 | 1524.28 | 01-MAR-16:00 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.105956E+10 | 1524.28 | 10-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.110876E+10 | 1040.98 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.109755E+10 | 1243.00 | 13-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.102805E+10 | 1243.00 | 20-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.115806E+10 | 1141.99 | 31-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.107350E+10 | 1524.28 | 21-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.115538E+10 | 2187.86 | 31-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.126004E+10 | 2187.86 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.129770E+10 | 2187.86 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.138254E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.102805E+10 | 1040.98 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.129770E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.843262E+09 | 1409.91 | 02-JAN-16:40 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.708736E+09 | 1228.64 | 14-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.788122E+09 | 982.28 | 13-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.682072E+09 | 982.28 | 10-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.709797E+09 | 735.93 | 15-MAY-08:30 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.702189E+09 | 801.02 | 13-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.659870E+09 | 801.02 | 20-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.742922E+09 | 735.93 | 23-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.690912E+09 | 982.28 | 21-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.757650E+09 | 1409.91 | 30-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.822862E+09 | 1409.91 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.859529E+09 | 1409.91 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.896792E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.659870E+09 | 735.93 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.859529E+09 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.522764E+10 | 5470.56 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.474186E+10 | 5470.56 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.563465E+10 | 5470.56 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.503289E+10 | 5470.56 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.543115E+10 | 5470.56 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.540489E+10 | 5470.56 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.505915E+10 | 5470.56 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.563465E+10 | 5470.56 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.503289E+10 | 5470.56 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.522764E+10 | 5470.56 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.516637E+10 | 5470.56 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.505915E+10 | 5470.56 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.626529E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.474186E+10 | 5470.56 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.563465E+10 | 5470.56 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.180249E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.163527E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.194806E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.173504E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.187528E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.186803E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.174228E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.194803E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.173504E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.180252E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.178272E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.174231E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.216171E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.163527E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.194806E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.135351E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109747E+10 |
February | 0.136985E+10 | 0.113093E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.833448E+09 |
March | 0.163685E+10 | 0.123112E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.748580E+09 |
April | 0.145243E+10 | 0.106320E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3400296.67 | 0.478343E+09 |
May | 0.157338E+10 | 0.110171E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1261535.96 | 0.251951E+09 |
June | 0.156900E+10 | 0.109154E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15973889.56 | 0.146172E+09 |
July | 0.145680E+10 | 0.102387E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5345775.39 | 0.103699E+09 |
August | 0.163685E+10 | 0.115263E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6082204.14 | 0.139747E+09 |
September | 0.145243E+10 | 0.108032E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4625631.28 | 0.230392E+09 |
October | 0.150991E+10 | 0.119012E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.467597E+09 |
November | 0.149516E+10 | 0.131290E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.740015E+09 |
December | 0.145680E+10 | 0.139466E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.954651E+09 |
Annual Sum or Average | 0.181194E+11 | 0.141265E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36689333.00 | 0.619206E+10 |
Minimum of Months | 0.136985E+10 | 0.102387E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103699E+09 |
Maximum of Months | 0.163685E+10 | 0.139466E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15973889.56 | 0.109747E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.849858E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.732148E+09 |
February | 0.882782E+09 | 0.715394E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553552E+09 |
March | 0.105485E+10 | 0.789695E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.493585E+09 |
April | 0.936002E+09 | 0.683562E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2873534.75 | 0.310977E+09 |
May | 0.101394E+10 | 0.716241E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 841222.15 | 0.166900E+09 |
June | 0.101113E+10 | 0.708005E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11744810.08 | 93970989.78 |
July | 0.938820E+09 | 0.662944E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3888553.73 | 63130879.06 |
August | 0.105485E+10 | 0.746209E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4452663.14 | 83940041.16 |
September | 0.936002E+09 | 0.695482E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3382571.73 | 0.152795E+09 |
October | 0.973041E+09 | 0.753119E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310293E+09 |
November | 0.963541E+09 | 0.830839E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484610E+09 |
December | 0.938820E+09 | 0.867281E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.629268E+09 |
Annual Sum or Average | 0.116768E+11 | 0.901863E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27183355.58 | 0.407517E+10 |
Minimum of Months | 0.882782E+09 | 0.662944E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63130879.06 |
Maximum of Months | 0.105485E+10 | 0.867281E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11744810.08 | 0.732148E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.128408E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110526E+10 |
February | 0.136988E+10 | 0.108815E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.841258E+09 |
March | 0.163688E+10 | 0.122012E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.750025E+09 |
April | 0.145246E+10 | 0.106193E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2936731.01 | 0.474428E+09 |
May | 0.157341E+10 | 0.110950E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1261335.01 | 0.251364E+09 |
June | 0.156904E+10 | 0.109843E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15990479.25 | 0.142553E+09 |
July | 0.145684E+10 | 0.102894E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5242991.98 | 0.100508E+09 |
August | 0.163688E+10 | 0.115896E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6059509.12 | 0.139474E+09 |
September | 0.145246E+10 | 0.107471E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3911859.73 | 0.237726E+09 |
October | 0.150994E+10 | 0.115643E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.476216E+09 |
November | 0.149520E+10 | 0.126140E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.736139E+09 |
December | 0.145684E+10 | 0.129975E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.957179E+09 |
Annual Sum or Average | 0.181198E+11 | 0.138424E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35402906.11 | 0.621213E+10 |
Minimum of Months | 0.136988E+10 | 0.102894E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100508E+09 |
Maximum of Months | 0.163688E+10 | 0.129975E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15990479.25 | 0.110526E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.845790E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.752258E+09 |
February | 0.882782E+09 | 0.710259E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.583620E+09 |
March | 0.105485E+10 | 0.789345E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536309E+09 |
April | 0.936002E+09 | 0.683273E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1761544.30 | 0.354804E+09 |
May | 0.101394E+10 | 0.710391E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 841036.48 | 0.179839E+09 |
June | 0.101113E+10 | 0.702811E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9977370.25 | 0.106735E+09 |
July | 0.938820E+09 | 0.660640E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3419633.95 | 77778965.19 |
August | 0.105485E+10 | 0.743433E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4033803.45 | 0.107196E+09 |
September | 0.936002E+09 | 0.691781E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2707730.84 | 0.166414E+09 |
October | 0.973041E+09 | 0.759296E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335830E+09 |
November | 0.963541E+09 | 0.824489E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525311E+09 |
December | 0.938820E+09 | 0.862119E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.680191E+09 |
Annual Sum or Average | 0.116768E+11 | 0.898363E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22741119.27 | 0.440629E+10 |
Minimum of Months | 0.882782E+09 | 0.660640E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77778965.19 |
Maximum of Months | 0.105485E+10 | 0.862119E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9977370.25 | 0.752258E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.134881E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239384E+10 |
February | 0.136985E+10 | 0.112690E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178714E+10 |
March | 0.163685E+10 | 0.122902E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156620E+10 |
April | 0.145243E+10 | 0.106109E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8717090.22 | 0.987415E+09 |
May | 0.157338E+10 | 0.110108E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2831863.34 | 0.552853E+09 |
June | 0.156900E+10 | 0.109051E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37379174.25 | 0.324993E+09 |
July | 0.145680E+10 | 0.102298E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12794452.96 | 0.233035E+09 |
August | 0.163685E+10 | 0.115161E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14134677.91 | 0.317536E+09 |
September | 0.145243E+10 | 0.107802E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11473580.62 | 0.493469E+09 |
October | 0.150991E+10 | 0.118662E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.952463E+09 |
November | 0.149516E+10 | 0.130816E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154656E+10 |
December | 0.145680E+10 | 0.138700E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203158E+10 |
Annual Sum or Average | 0.181194E+11 | 0.140918E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 87330839.30 | 0.131871E+11 |
Minimum of Months | 0.136985E+10 | 0.102298E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233035E+09 |
Maximum of Months | 0.163685E+10 | 0.138700E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37379174.25 | 0.239384E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.847420E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160321E+10 |
February | 0.649041E+09 | 0.714091E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120296E+10 |
March | 0.773965E+09 | 0.788729E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106345E+10 |
April | 0.688021E+09 | 0.682763E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6393209.42 | 0.675309E+09 |
May | 0.744847E+09 | 0.715611E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1893012.51 | 0.374839E+09 |
June | 0.742030E+09 | 0.707551E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26185402.02 | 0.217205E+09 |
July | 0.690839E+09 | 0.662516E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8609669.87 | 0.154553E+09 |
August | 0.773965E+09 | 0.745780E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9696035.05 | 0.210808E+09 |
September | 0.688021E+09 | 0.694259E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7660546.36 | 0.338088E+09 |
October | 0.715730E+09 | 0.752195E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.657048E+09 |
November | 0.708685E+09 | 0.828660E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103638E+10 |
December | 0.690839E+09 | 0.863924E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136235E+10 |
Annual Sum or Average | 0.858171E+10 | 0.900350E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 60437875.22 | 0.889620E+10 |
Minimum of Months | 0.649041E+09 | 0.662516E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154553E+09 |
Maximum of Months | 0.773965E+09 | 0.863924E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26185402.02 | 0.160321E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.128313E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246627E+10 |
February | 0.136988E+10 | 0.108489E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187922E+10 |
March | 0.163688E+10 | 0.121906E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166542E+10 |
April | 0.145246E+10 | 0.105966E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6492613.30 | 0.104926E+10 |
May | 0.157341E+10 | 0.110880E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2831348.81 | 0.569644E+09 |
June | 0.156904E+10 | 0.109755E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36635739.72 | 0.325086E+09 |
July | 0.145684E+10 | 0.102815E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11810486.57 | 0.235626E+09 |
August | 0.163688E+10 | 0.115806E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13710767.79 | 0.334327E+09 |
September | 0.145246E+10 | 0.107366E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8578275.79 | 0.541950E+09 |
October | 0.150994E+10 | 0.115541E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106463E+10 |
November | 0.149520E+10 | 0.126043E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162706E+10 |
December | 0.145684E+10 | 0.129694E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212065E+10 |
Annual Sum or Average | 0.181198E+11 | 0.138257E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 80059231.99 | 0.138791E+11 |
Minimum of Months | 0.136988E+10 | 0.102815E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235626E+09 |
Maximum of Months | 0.163688E+10 | 0.129694E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36635739.72 | 0.246627E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.843569E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161561E+10 |
February | 0.882782E+09 | 0.708742E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122728E+10 |
March | 0.105485E+10 | 0.788233E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108562E+10 |
April | 0.936002E+09 | 0.682072E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4104008.21 | 0.708859E+09 |
May | 0.101394E+10 | 0.709851E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1892081.15 | 0.387631E+09 |
June | 0.101113E+10 | 0.702193E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24039093.31 | 0.228491E+09 |
July | 0.938820E+09 | 0.659893E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8129897.59 | 0.173387E+09 |
August | 0.105485E+10 | 0.742971E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9358397.66 | 0.234147E+09 |
September | 0.936002E+09 | 0.690929E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6529175.04 | 0.353458E+09 |
October | 0.973041E+09 | 0.757728E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.668978E+09 |
November | 0.963541E+09 | 0.822884E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105584E+10 |
December | 0.938820E+09 | 0.859718E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138155E+10 |
Annual Sum or Average | 0.116768E+11 | 0.896878E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54052652.95 | 0.912085E+10 |
Minimum of Months | 0.882782E+09 | 0.659893E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173387E+09 |
Maximum of Months | 0.105485E+10 | 0.859718E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24039093.31 | 0.161561E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.134875E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294795E+10 |
February | 0.136985E+10 | 0.112672E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215606E+10 |
March | 0.163685E+10 | 0.122882E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185047E+10 |
April | 0.145243E+10 | 0.106109E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9492924.17 | 0.114562E+10 |
May | 0.157338E+10 | 0.110107E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3361755.93 | 0.656802E+09 |
June | 0.156900E+10 | 0.109051E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43711265.02 | 0.391122E+09 |
July | 0.145680E+10 | 0.102290E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14465166.42 | 0.287249E+09 |
August | 0.163685E+10 | 0.115155E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16897245.63 | 0.386865E+09 |
September | 0.145243E+10 | 0.107777E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13909391.95 | 0.576193E+09 |
October | 0.150991E+10 | 0.118653E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105573E+10 |
November | 0.149516E+10 | 0.130779E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182310E+10 |
December | 0.145680E+10 | 0.138661E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246826E+10 |
Annual Sum or Average | 0.181194E+11 | 0.140901E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101838E+09 | 0.157454E+11 |
Minimum of Months | 0.136985E+10 | 0.102290E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287249E+09 |
Maximum of Months | 0.163685E+10 | 0.138661E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43711265.02 | 0.294795E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.847407E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197682E+10 |
February | 0.882782E+09 | 0.714013E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144864E+10 |
March | 0.105485E+10 | 0.788664E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125593E+10 |
April | 0.936002E+09 | 0.682755E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6791675.92 | 0.796202E+09 |
May | 0.101394E+10 | 0.715550E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2241043.75 | 0.451627E+09 |
June | 0.101113E+10 | 0.707538E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29913073.15 | 0.264195E+09 |
July | 0.938820E+09 | 0.662516E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9561104.52 | 0.193176E+09 |
August | 0.105485E+10 | 0.745780E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11304304.57 | 0.259678E+09 |
September | 0.936002E+09 | 0.694211E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8642556.99 | 0.402917E+09 |
October | 0.973041E+09 | 0.752113E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739307E+09 |
November | 0.963541E+09 | 0.828660E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122461E+10 |
December | 0.938820E+09 | 0.863808E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165592E+10 |
Annual Sum or Average | 0.116768E+11 | 0.900302E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 68453758.91 | 0.106690E+11 |
Minimum of Months | 0.882782E+09 | 0.662516E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193176E+09 |
Maximum of Months | 0.105485E+10 | 0.863808E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29913073.15 | 0.197682E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.128307E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300708E+10 |
February | 0.136988E+10 | 0.108483E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224333E+10 |
March | 0.163688E+10 | 0.121891E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195901E+10 |
April | 0.145246E+10 | 0.105956E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7547936.23 | 0.122868E+10 |
May | 0.157341E+10 | 0.110876E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3361086.80 | 0.680534E+09 |
June | 0.156904E+10 | 0.109755E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42965885.82 | 0.391691E+09 |
July | 0.145684E+10 | 0.102805E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13747828.52 | 0.290750E+09 |
August | 0.163688E+10 | 0.115806E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16345084.74 | 0.408650E+09 |
September | 0.145246E+10 | 0.107350E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10341805.71 | 0.643121E+09 |
October | 0.150994E+10 | 0.115538E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121020E+10 |
November | 0.149520E+10 | 0.126004E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190734E+10 |
December | 0.145684E+10 | 0.129770E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255280E+10 |
Annual Sum or Average | 0.181198E+11 | 0.138254E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94309627.83 | 0.165232E+11 |
Minimum of Months | 0.136988E+10 | 0.102805E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290750E+09 |
Maximum of Months | 0.163688E+10 | 0.129770E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42965885.82 | 0.300708E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.843262E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198511E+10 |
February | 0.882782E+09 | 0.708736E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147644E+10 |
March | 0.105485E+10 | 0.788122E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128876E+10 |
April | 0.936002E+09 | 0.682072E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4886452.39 | 0.836262E+09 |
May | 0.101394E+10 | 0.709797E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2254419.29 | 0.465153E+09 |
June | 0.101113E+10 | 0.702189E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28472766.70 | 0.277216E+09 |
July | 0.938820E+09 | 0.659870E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9571514.04 | 0.214393E+09 |
August | 0.105485E+10 | 0.742922E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11252390.36 | 0.287066E+09 |
September | 0.936002E+09 | 0.690912E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8021558.44 | 0.421225E+09 |
October | 0.973041E+09 | 0.757650E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766539E+09 |
November | 0.963541E+09 | 0.822862E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124773E+10 |
December | 0.938820E+09 | 0.859529E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167456E+10 |
Annual Sum or Average | 0.116768E+11 | 0.896792E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64459101.21 | 0.109405E+11 |
Minimum of Months | 0.882782E+09 | 0.659870E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214393E+09 |
Maximum of Months | 0.105485E+10 | 0.859529E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28472766.70 | 0.198511E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.522764E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.474186E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.563465E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.503289E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.543115E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.540489E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.505915E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.563465E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.503289E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.522764E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.516637E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.505915E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.626529E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.474186E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.563465E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235547E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178868E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159403E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6989975.50 | 0.101534E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1859258.53 | 0.530133E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33557083.05 | 0.303569E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9093379.85 | 0.218522E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9340203.54 | 0.300343E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8044507.14 | 0.489843E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.997538E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159008E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205671E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68884407.61 | 0.132403E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218522E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33557083.05 | 0.235547E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393281E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300949E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268081E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14983263.06 | 0.171301E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3404377.37 | 0.921891E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64874654.00 | 0.527201E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18631337.27 | 0.375195E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17398299.61 | 0.526837E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16148683.48 | 0.847788E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168335E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265749E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340985E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135441E+09 | 0.222857E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375195E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64874654.00 | 0.393281E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427643E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321386E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284930E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8226886.44 | 0.181125E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2523612.85 | 0.103371E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46941125.56 | 0.592622E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9536009.05 | 0.436210E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13687444.10 | 0.602179E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10271018.08 | 0.912135E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169913E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275377E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363073E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91186096.08 | 0.238113E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436210E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46941125.56 | 0.427643E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 19402.09 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 19402.09 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 19402.09 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 19402.09 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 19402.09 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 19402.09 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 19402.09 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 19402.09 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 19402.09 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 19402.09 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 19402.09 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 19402.09 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 19402.09 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 19402.09 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2187.81 | 02-JAN-16:19 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2055.32 | 29-JAN-11:00 |
February | 2010.79 | 01-FEB-10:09 | 1906.53 | 01-FEB-16:49 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1413.79 | 04-FEB-22:53 |
March | 2010.79 | 01-MAR-10:09 | 1524.25 | 01-MAR-16:49 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1328.33 | 12-MAR-16:00 |
April | 2010.79 | 03-APR-09:09 | 1524.25 | 10-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.27 | 15-APR-17:10 | 983.92 | 02-APR-24:00 |
May | 2010.79 | 01-MAY-09:09 | 1040.96 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.81 | 31-MAY-13:00 | 627.31 | 01-MAY-24:00 |
June | 2010.79 | 01-JUN-09:09 | 1242.97 | 13-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.05 | 11-JUN-15:00 | 511.36 | 02-JUN-05:00 |
July | 2010.79 | 03-JUL-09:09 | 1242.97 | 20-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.08 | 02-JUL-15:34 | 229.30 | 09-JUL-09:53 |
August | 2010.79 | 01-AUG-09:09 | 1141.96 | 28-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.95 | 04-AUG-16:40 | 296.73 | 06-AUG-06:00 |
September | 2010.79 | 01-SEP-09:09 | 1524.25 | 21-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.97 | 17-SEP-15:00 | 445.83 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 2187.81 | 30-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 702.81 | 24-OCT-05:00 |
November | 2010.79 | 01-NOV-09:09 | 2187.81 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1546.44 | 20-NOV-22:10 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 01-DEC-16:10 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2445.21 | 09-DEC-01:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.30 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 211.05 | 2445.21 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-16:19 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1477.14 | 29-JAN-10:53 |
February | 1295.83 | 01-FEB-10:09 | 1228.64 | 01-FEB-16:49 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 937.36 | 04-FEB-22:53 |
March | 1295.83 | 01-MAR-10:09 | 982.28 | 01-MAR-16:40 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 905.74 | 05-MAR-09:53 |
April | 1295.83 | 03-APR-09:09 | 801.02 | 10-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.76 | 15-APR-17:10 | 640.71 | 02-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 735.93 | 09-MAY-15:20 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.54 | 31-MAY-13:00 | 414.85 | 01-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 735.93 | 05-JUN-15:30 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.46 | 18-JUN-16:10 | 333.20 | 02-JUN-05:00 |
July | 1295.83 | 03-JUL-09:09 | 735.93 | 20-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.12 | 02-JUL-15:40 | 150.55 | 09-JUL-09:53 |
August | 1295.83 | 01-AUG-09:09 | 670.83 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.64 | 04-AUG-16:40 | 188.46 | 06-AUG-08:50 |
September | 1295.83 | 01-SEP-09:09 | 801.02 | 13-SEP-15:39 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.32 | 17-SEP-15:00 | 292.66 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 31-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 460.35 | 24-OCT-05:00 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1018.44 | 20-NOV-22:02 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-16:10 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1608.94 | 09-DEC-01:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.55 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 156.46 | 1608.94 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2187.86 | 02-JAN-16:40 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2374.28 | 29-JAN-13:00 |
February | 2010.83 | 01-FEB-10:09 | 1906.57 | 14-FEB-16:49 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1439.79 | 04-FEB-22:53 |
March | 2010.83 | 01-MAR-10:09 | 1524.28 | 01-MAR-16:00 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1369.13 | 05-MAR-14:36 |
April | 2010.83 | 03-APR-09:09 | 1524.28 | 10-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.95 | 15-APR-17:10 | 918.69 | 02-APR-24:00 |
May | 2010.83 | 01-MAY-09:09 | 1040.98 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.81 | 31-MAY-13:00 | 620.34 | 01-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 1243.00 | 13-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.08 | 11-JUN-15:25 | 497.09 | 02-JUN-05:00 |
July | 2010.83 | 03-JUL-09:09 | 1243.00 | 20-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.64 | 02-JUL-15:34 | 222.70 | 09-JUL-09:53 |
August | 2010.83 | 01-AUG-09:09 | 1141.99 | 28-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.95 | 04-AUG-16:40 | 308.48 | 06-AUG-13:30 |
September | 2010.83 | 01-SEP-09:09 | 1524.28 | 21-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.32 | 06-SEP-16:00 | 472.48 | 24-SEP-13:00 |
October | 2010.83 | 02-OCT-09:09 | 2187.86 | 31-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 692.35 | 24-OCT-05:00 |
November | 2010.83 | 01-NOV-09:09 | 2187.86 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1528.18 | 20-NOV-22:02 |
December | 2010.83 | 01-DEC-10:09 | 2187.86 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2397.13 | 09-DEC-01:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.70 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 210.08 | 2397.13 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-16:40 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1409.93 | 29-JAN-11:00 |
February | 1295.83 | 01-FEB-10:09 | 1228.64 | 14-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 994.74 | 04-FEB-22:53 |
March | 1295.83 | 01-MAR-10:09 | 982.28 | 13-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 966.93 | 12-MAR-16:00 |
April | 1295.83 | 03-APR-09:09 | 982.28 | 10-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.94 | 15-APR-17:10 | 710.39 | 02-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 735.93 | 15-MAY-08:20 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.54 | 31-MAY-13:00 | 440.78 | 01-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 801.02 | 13-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 135.54 | 11-JUN-16:05 | 357.47 | 02-JUN-05:00 |
July | 1295.83 | 03-JUL-09:09 | 801.02 | 20-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.34 | 02-JUL-14:54 | 172.30 | 09-JUL-09:53 |
August | 1295.83 | 01-AUG-09:09 | 735.93 | 23-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.64 | 04-AUG-16:40 | 232.90 | 06-AUG-06:00 |
September | 1295.83 | 01-SEP-09:09 | 982.28 | 12-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.58 | 10-SEP-15:06 | 328.66 | 24-SEP-16:20 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 30-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 497.62 | 24-OCT-05:00 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1077.41 | 20-NOV-22:10 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1707.33 | 09-DEC-01:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 735.93 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.30 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 135.54 | 1707.33 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2187.81 | 02-JAN-16:19 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4627.27 | 29-JAN-11:00 |
February | 2010.79 | 01-FEB-10:09 | 1906.53 | 01-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3252.26 | 10-FEB-22:02 |
March | 2010.79 | 01-MAR-10:09 | 1524.25 | 01-MAR-16:49 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2592.19 | 12-MAR-16:00 |
April | 2010.79 | 03-APR-09:09 | 1524.25 | 10-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 427.20 | 15-APR-17:01 | 1902.17 | 02-APR-24:00 |
May | 2010.79 | 01-MAY-09:09 | 1040.96 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.04 | 31-MAY-13:00 | 1325.30 | 01-MAY-24:00 |
June | 2010.79 | 01-JUN-09:09 | 1141.96 | 05-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 479.71 | 11-JUN-15:14 | 1083.87 | 02-JUN-05:00 |
July | 2010.79 | 03-JUL-09:09 | 1141.96 | 20-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.40 | 02-JUL-15:10 | 494.91 | 09-JUL-10:00 |
August | 2010.79 | 01-AUG-09:09 | 1141.96 | 31-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.14 | 04-AUG-16:35 | 659.80 | 06-AUG-09:00 |
September | 2010.79 | 01-SEP-09:09 | 1524.25 | 21-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 165.55 | 17-SEP-14:50 | 968.22 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 2187.81 | 30-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1493.86 | 24-OCT-04:55 |
November | 2010.79 | 01-NOV-09:09 | 2187.81 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3560.24 | 20-NOV-22:02 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 01-DEC-16:10 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5426.54 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 494.91 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 479.71 | 5426.54 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1409.91 | 02-JAN-16:19 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3089.70 | 29-JAN-10:53 |
February | 1239.33 | 01-FEB-08:09 | 1228.64 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2168.00 | 10-FEB-22:02 |
March | 1239.33 | 01-MAR-08:09 | 982.28 | 01-MAR-16:40 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1900.56 | 05-MAR-10:00 |
April | 1239.33 | 03-APR-07:10 | 801.02 | 10-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 317.31 | 15-APR-17:10 | 1264.37 | 02-APR-24:00 |
May | 1239.33 | 01-MAY-07:10 | 735.93 | 09-MAY-15:20 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.69 | 31-MAY-13:00 | 889.61 | 01-MAY-24:00 |
June | 1239.33 | 01-JUN-07:10 | 735.93 | 09-JUN-15:50 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 371.65 | 18-JUN-16:00 | 717.83 | 02-JUN-05:00 |
July | 1239.33 | 03-JUL-07:10 | 735.93 | 20-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.23 | 02-JUL-15:44 | 357.57 | 09-JUL-10:00 |
August | 1239.33 | 01-AUG-07:10 | 670.83 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.10 | 04-AUG-16:35 | 452.74 | 06-AUG-09:00 |
September | 1239.33 | 01-SEP-07:10 | 801.02 | 13-SEP-15:50 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.86 | 17-SEP-14:50 | 638.57 | 18-SEP-23:00 |
October | 1239.33 | 02-OCT-07:10 | 1409.91 | 31-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 989.93 | 24-OCT-04:55 |
November | 1239.33 | 01-NOV-07:10 | 1409.91 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2373.14 | 20-NOV-22:02 |
December | 1239.33 | 01-DEC-08:09 | 1409.91 | 01-DEC-16:10 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3617.80 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357.57 | |||||
Maximum of Months | 1239.33 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 371.65 | 3617.80 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2187.86 | 02-JAN-16:40 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5152.15 | 29-JAN-12:53 |
February | 2010.83 | 01-FEB-10:09 | 1906.57 | 14-FEB-16:49 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3255.76 | 10-FEB-22:02 |
March | 2010.83 | 01-MAR-10:09 | 1524.28 | 01-MAR-16:00 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3214.45 | 05-MAR-14:20 |
April | 2010.83 | 03-APR-09:09 | 1524.28 | 10-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 315.49 | 15-APR-17:10 | 1918.59 | 02-APR-24:00 |
May | 2010.83 | 01-MAY-09:09 | 1040.98 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.04 | 31-MAY-13:00 | 1354.09 | 01-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 1243.00 | 13-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 490.44 | 11-JUN-15:14 | 1084.21 | 02-JUN-05:00 |
July | 2010.83 | 03-JUL-09:09 | 1243.00 | 20-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.79 | 02-JUL-15:44 | 513.78 | 09-JUL-10:00 |
August | 2010.83 | 01-AUG-09:09 | 1141.99 | 31-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.14 | 04-AUG-16:35 | 739.52 | 06-AUG-13:50 |
September | 2010.83 | 01-SEP-09:09 | 1524.28 | 21-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.25 | 06-SEP-16:00 | 1079.43 | 24-SEP-13:20 |
October | 2010.83 | 02-OCT-09:09 | 2187.86 | 31-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1488.90 | 29-OCT-10:30 |
November | 2010.83 | 01-NOV-09:09 | 2187.86 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3566.06 | 20-NOV-22:02 |
December | 2010.83 | 01-DEC-10:09 | 2187.86 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5426.95 | 09-DEC-01:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 513.78 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 490.44 | 5426.95 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-16:40 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3087.43 | 29-JAN-10:55 |
February | 1295.83 | 01-FEB-10:09 | 1228.64 | 14-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2170.11 | 10-FEB-22:02 |
March | 1295.83 | 01-MAR-10:09 | 982.28 | 13-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1835.32 | 05-MAR-15:00 |
April | 1295.83 | 03-APR-09:09 | 982.28 | 10-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.41 | 15-APR-17:10 | 1301.91 | 02-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 735.93 | 15-MAY-08:30 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.70 | 31-MAY-13:00 | 900.62 | 01-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 801.02 | 13-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 327.88 | 11-JUN-15:13 | 717.06 | 02-JUN-05:00 |
July | 1295.83 | 03-JUL-09:09 | 801.02 | 20-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.20 | 02-JUL-11:10 | 369.17 | 09-JUL-10:00 |
August | 1295.83 | 01-AUG-09:09 | 735.93 | 23-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.10 | 04-AUG-16:35 | 480.59 | 06-AUG-09:00 |
September | 1295.83 | 01-SEP-09:09 | 982.28 | 21-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.14 | 17-SEP-12:10 | 755.58 | 24-SEP-16:00 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 30-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 989.91 | 24-OCT-05:00 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2376.54 | 20-NOV-22:02 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3617.90 | 09-DEC-01:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 735.93 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 369.17 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 327.88 | 3617.90 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2187.81 | 02-JAN-16:19 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5762.15 | 29-JAN-11:00 |
February | 2010.79 | 01-FEB-10:09 | 1906.53 | 01-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4031.64 | 10-FEB-22:02 |
March | 2010.79 | 01-MAR-10:09 | 1524.25 | 01-MAR-16:49 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3067.17 | 20-MAR-21:03 |
April | 2010.79 | 03-APR-09:09 | 1524.25 | 10-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 498.27 | 15-APR-17:01 | 2303.13 | 02-APR-24:00 |
May | 2010.79 | 01-MAY-09:09 | 1040.96 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.04 | 31-MAY-13:00 | 1541.44 | 01-MAY-24:00 |
June | 2010.79 | 01-JUN-09:09 | 1141.96 | 05-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 596.99 | 11-JUN-15:14 | 1241.39 | 02-JUN-04:55 |
July | 2010.79 | 03-JUL-09:09 | 1141.96 | 20-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 178.66 | 02-JUL-15:56 | 595.39 | 09-JUL-20:53 |
August | 2010.79 | 01-AUG-09:09 | 1141.96 | 31-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.12 | 04-AUG-16:35 | 788.16 | 06-AUG-09:00 |
September | 2010.79 | 01-SEP-09:09 | 1524.25 | 21-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 214.72 | 17-SEP-15:00 | 1138.49 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 2187.81 | 30-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1854.71 | 24-OCT-04:57 |
November | 2010.79 | 01-NOV-09:09 | 2187.81 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4414.43 | 20-NOV-22:02 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 01-DEC-16:10 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6757.04 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 595.39 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 596.99 | 6757.04 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-16:19 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3841.40 | 29-JAN-10:53 |
February | 1295.83 | 01-FEB-10:09 | 1228.64 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2687.22 | 10-FEB-22:02 |
March | 1295.83 | 01-MAR-10:09 | 982.28 | 01-MAR-16:40 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2162.04 | 06-MAR-05:51 |
April | 1295.83 | 03-APR-09:09 | 801.02 | 10-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 363.43 | 15-APR-17:10 | 1535.30 | 02-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 735.93 | 09-MAY-15:20 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.03 | 31-MAY-13:00 | 1043.61 | 01-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 735.93 | 09-JUN-15:50 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 458.59 | 18-JUN-16:00 | 832.82 | 02-JUN-04:55 |
July | 1295.83 | 03-JUL-09:09 | 735.93 | 20-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.49 | 02-JUL-15:56 | 442.17 | 04-JUL-10:00 |
August | 1295.83 | 01-AUG-09:09 | 670.83 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.75 | 04-AUG-16:35 | 542.14 | 06-AUG-09:00 |
September | 1295.83 | 01-SEP-09:09 | 801.02 | 13-SEP-15:50 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.74 | 17-SEP-15:00 | 752.96 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 31-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1256.10 | 24-OCT-04:55 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2942.54 | 20-NOV-22:02 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-16:10 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4504.66 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442.17 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 458.59 | 4504.66 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2187.86 | 02-JAN-16:40 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 6020.59 | 29-JAN-13:00 |
February | 2010.83 | 01-FEB-10:09 | 1906.57 | 14-FEB-16:49 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4036.20 | 10-FEB-22:02 |
March | 2010.83 | 01-MAR-10:09 | 1524.28 | 01-MAR-16:00 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3636.76 | 05-MAR-14:00 |
April | 2010.83 | 03-APR-09:09 | 1524.28 | 10-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 360.75 | 15-APR-17:10 | 2303.21 | 02-APR-24:00 |
May | 2010.83 | 01-MAY-09:09 | 1040.98 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.04 | 31-MAY-13:00 | 1583.63 | 01-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 1243.00 | 13-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 614.20 | 11-JUN-15:14 | 1246.60 | 02-JUN-04:55 |
July | 2010.83 | 03-JUL-09:09 | 1243.00 | 20-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.16 | 02-JUL-15:54 | 605.92 | 09-JUL-20:53 |
August | 2010.83 | 01-AUG-09:09 | 1141.99 | 31-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.12 | 04-AUG-16:35 | 903.54 | 06-AUG-13:30 |
September | 2010.83 | 01-SEP-09:09 | 1524.28 | 21-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.85 | 06-SEP-16:00 | 1279.33 | 24-SEP-13:10 |
October | 2010.83 | 02-OCT-09:09 | 2187.86 | 31-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1877.85 | 24-OCT-04:55 |
November | 2010.83 | 01-NOV-09:09 | 2187.86 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4422.34 | 20-NOV-22:02 |
December | 2010.83 | 01-DEC-10:09 | 2187.86 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6756.98 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 605.92 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 614.20 | 6756.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-16:40 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3841.44 | 29-JAN-10:55 |
February | 1295.83 | 01-FEB-10:09 | 1228.64 | 14-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2691.94 | 10-FEB-22:02 |
March | 1295.83 | 01-MAR-10:09 | 982.28 | 13-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2168.04 | 06-MAR-05:51 |
April | 1295.83 | 03-APR-09:09 | 982.28 | 10-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.45 | 15-APR-17:10 | 1535.51 | 02-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 735.93 | 15-MAY-08:30 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.03 | 31-MAY-13:00 | 1059.41 | 01-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 801.02 | 13-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 395.91 | 11-JUN-15:13 | 836.92 | 02-JUN-04:55 |
July | 1295.83 | 03-JUL-09:09 | 801.02 | 20-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.17 | 02-JUL-11:20 | 442.59 | 09-JUL-20:53 |
August | 1295.83 | 01-AUG-09:09 | 735.93 | 23-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.75 | 04-AUG-16:35 | 576.20 | 06-AUG-09:00 |
September | 1295.83 | 01-SEP-09:09 | 982.28 | 21-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.04 | 17-SEP-11:40 | 909.42 | 24-SEP-16:30 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 30-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1249.17 | 24-OCT-04:55 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2948.00 | 20-NOV-22:02 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4504.55 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 735.93 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442.59 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 395.91 | 4504.55 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 5470.56 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 5470.56 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 5470.56 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 5470.56 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 5470.56 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 5470.56 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 5470.56 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 5470.56 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 5470.56 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 5470.56 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 5470.56 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 5470.56 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 5470.56 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4468.07 | 29-JAN-10:53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3119.51 | 04-FEB-22:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2736.95 | 12-MAR-16:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.35 | 15-APR-17:01 | 2124.20 | 02-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.34 | 31-MAY-13:00 | 1345.63 | 01-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 438.01 | 18-JUN-15:51 | 1106.77 | 02-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.84 | 02-JUL-15:20 | 435.74 | 09-JUL-10:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.18 | 04-AUG-16:35 | 609.47 | 06-AUG-06:08 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.13 | 17-SEP-14:41 | 952.39 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1545.22 | 24-OCT-04:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3316.73 | 20-NOV-22:02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5390.90 | 09-DEC-01:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 435.74 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 438.01 | 5390.90 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 7548.41 | 29-JAN-11:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 5274.67 | 04-FEB-22:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4476.57 | 12-MAR-16:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 659.39 | 15-APR-17:01 | 3526.13 | 02-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.38 | 31-MAY-13:00 | 2294.31 | 01-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 833.77 | 11-JUN-15:00 | 1937.87 | 02-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.58 | 02-JUL-15:30 | 737.43 | 09-JUL-20:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.57 | 04-AUG-16:35 | 1053.19 | 06-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.65 | 17-SEP-15:00 | 1672.94 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2621.11 | 24-OCT-04:53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5606.36 | 20-NOV-22:02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 9243.55 | 09-DEC-01:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 737.43 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 833.77 | 9243.55 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 8190.67 | 29-JAN-11:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 5845.54 | 10-FEB-22:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4657.93 | 20-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 583.92 | 15-APR-17:10 | 3307.32 | 02-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.31 | 31-MAY-13:00 | 2424.91 | 01-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 686.66 | 11-JUN-15:00 | 1972.95 | 02-JUN-04:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.25 | 25-JUL-16:00 | 852.62 | 09-JUL-20:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.14 | 04-AUG-16:30 | 1193.57 | 06-AUG-09:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.95 | 06-SEP-16:00 | 1757.81 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2600.34 | 24-OCT-05:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6293.21 | 20-NOV-22:02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 9793.86 | 09-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 852.62 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 686.66 | 9793.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 102399.68 | 02-JAN-07:03 | 10771.35 | 19402.09 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 102559.12 | 27-FEB-07:03 | 10771.35 | 19402.09 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 104445.59 | 29-MAR-06:12 | 21542.70 | 38804.17 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 107515.72 | 10-APR-06:11 | 25133.15 | 45271.53 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 110159.77 | 08-MAY-06:11 | 28723.60 | 51738.90 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 120784.50 | 01-JUN-06:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 116573.11 | 07-JUL-20:31 | 17952.25 | 43114.94 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 112260.90 | 07-AUG-06:05 | 7180.90 | 12934.72 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 116284.85 | 12-SEP-06:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 116743.64 | 10-OCT-06:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 114088.58 | 06-NOV-07:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 106011.14 | 04-DEC-07:03 | 10771.35 | 19402.09 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 102399.68 | 7180.90 | 12934.72 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 120784.50 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 79270.90 | 14-JAN-06:01 | 11285.67 | 3761.52 | 53531.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 83245.91 | 25-FEB-06:02 | 9673.43 | 3224.16 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 87043.20 | 28-MAR-04:01 | 0.00 | 4298.88 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 91274.87 | 19-APR-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 95094.65 | 30-MAY-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 96709.06 | 14-JUN-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 98026.29 | 01-JUL-04:13 | 0.00 | 3224.16 | 26719.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 96815.17 | 07-AUG-04:11 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 100314.86 | 12-SEP-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 91849.43 | 10-OCT-04:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 91014.32 | 06-NOV-05:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 85325.92 | 04-DEC-05:01 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 79270.90 | 0.00 | 2686.80 | 26719.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 100314.86 | 11285.67 | 4298.88 | 53531.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 29497.48 | 12-JAN-10:10 | 32029.16 | 34848.87 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 24554.92 | 16-FEB-13:25 | 30632.53 | 34848.87 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 72359.79 | 24-MAR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 80590.00 | 19-APR-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 81593.73 | 31-MAY-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 83093.75 | 29-JUN-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 82396.97 | 18-JUL-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 82769.61 | 15-AUG-04:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 83610.01 | 12-SEP-04:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 74415.91 | 12-OCT-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 73073.99 | 09-NOV-06:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 30026.35 | 01-DEC-09:00 | 30632.53 | 34848.87 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 24554.92 | 0.00 | 2149.44 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 83610.01 | 32029.16 | 34848.87 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 18104.45 | 13-JAN-17:00 | 30632.53 | 34848.87 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 21303.12 | 24-FEB-14:10 | 32029.16 | 34848.87 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 32174.27 | 24-MAR-16:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 78314.22 | 17-APR-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 80001.40 | 30-MAY-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 87995.65 | 12-JUN-04:13 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 81841.51 | 28-JUL-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 81151.06 | 29-AUG-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 81242.98 | 12-SEP-04:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 33257.94 | 20-OCT-16:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 31470.51 | 03-NOV-16:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17714.02 | 01-DEC-16:40 | 30632.53 | 34848.87 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 17714.02 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 87995.65 | 32029.16 | 34848.87 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2122.45 | 13-JAN-14:40 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.99 |
February | 2882.14 | 24-FEB-13:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.47 |
March | 5415.77 | 28-MAR-14:00 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.11 |
April | 16726.59 | 16-APR-15:41 | 1012.16 | 578.27 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 75.70 | 0.00 |
May | 12909.65 | 30-MAY-04:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.94 |
June | 16842.21 | 25-JUN-18:31 | 0.00 | 404.79 | 3914.20 | 0.00 | 0.00 | 0.00 | 0.00 | 75.51 | 0.00 |
July | 17535.05 | 04-JUL-16:32 | 1012.16 | 578.27 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 17.47 | 0.00 |
August | 15538.25 | 27-AUG-13:22 | 506.08 | 289.13 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
September | 13183.44 | 12-SEP-04:11 | 0.00 | 472.30 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.95 |
October | 6408.01 | 10-OCT-13:30 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.73 |
November | 4961.53 | 07-NOV-13:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.96 |
December | 2621.77 | 03-DEC-11:32 | 404.87 | 231.31 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 551.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2122.45 | 0.00 | 231.31 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17535.05 | 2010.79 | 1040.96 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 75.70 | 551.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2807.90 | 12-JAN-10:10 | 2591.66 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.30 |
February | 7256.77 | 24-FEB-09:25 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.49 |
March | 10483.85 | 28-MAR-08:55 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.98 |
April | 21096.36 | 30-APR-08:42 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.55 |
May | 26349.46 | 29-MAY-09:31 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.74 |
June | 25442.32 | 25-JUN-08:32 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.88 |
July | 28543.73 | 04-JUL-07:51 | 587.05 | 335.39 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.75 |
August | 25590.52 | 27-AUG-10:01 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.44 |
September | 24970.99 | 04-SEP-09:11 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.52 |
October | 9611.27 | 20-OCT-08:50 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.26 |
November | 6274.16 | 04-NOV-09:20 | 409.21 | 223.61 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.93 |
December | 3789.21 | 05-DEC-09:35 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2807.90 | 326.14 | 186.33 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.44 | |
Maximum of Months | 28543.73 | 2591.66 | 1341.67 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16337.65 | 12-JAN-12:30 | 2116.67 | 2081.97 | 3841.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.75 |
February | 26520.41 | 20-FEB-13:13 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 639.57 |
March | 28091.80 | 19-MAR-12:52 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.71 |
April | 30373.01 | 16-APR-13:41 | 809.75 | 462.62 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.24 |
May | 26892.54 | 14-MAY-13:22 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.15 |
June | 26166.27 | 25-JUN-14:32 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 145.56 | 0.00 |
July | 28247.77 | 02-JUL-13:32 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 8.63 | 0.00 |
August | 28901.13 | 13-AUG-13:22 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.91 |
September | 30835.77 | 04-SEP-11:51 | 809.75 | 462.62 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.32 |
October | 30334.25 | 01-OCT-12:41 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.38 |
November | 28538.31 | 05-NOV-14:02 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.13 |
December | 26849.72 | 03-DEC-12:52 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 722.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16337.65 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30835.77 | 2116.67 | 2081.97 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 145.56 | 722.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5888.18 | 12-JAN-15:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.38 |
February | 10878.41 | 24-FEB-16:20 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.00 |
March | 26589.53 | 19-MAR-14:52 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.92 |
April | 35380.09 | 16-APR-16:21 | 652.28 | 372.66 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.57 |
May | 34504.47 | 14-MAY-16:41 | 652.28 | 372.66 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.28 |
June | 31519.02 | 25-JUN-16:31 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 72.55 | 0.00 |
July | 35697.89 | 02-JUL-16:51 | 652.28 | 372.66 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.24 |
August | 31805.71 | 13-AUG-16:01 | 587.05 | 335.39 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.02 |
September | 33454.83 | 04-SEP-16:31 | 587.05 | 335.39 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.31 |
October | 29354.73 | 01-OCT-14:42 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.62 |
November | 21381.05 | 05-NOV-14:02 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.37 |
December | 8146.69 | 01-DEC-15:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5888.18 | 326.14 | 186.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35697.89 | 1239.33 | 670.83 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 72.55 | 154.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1711.02 | 13-JAN-13:50 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.52 |
February | 2455.61 | 24-FEB-14:30 | 4021.58 | 2081.92 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.24 |
March | 2804.79 | 24-MAR-13:30 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.51 |
April | 8585.59 | 16-APR-15:51 | 1012.16 | 578.27 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 211.33 | 0.00 |
May | 8955.39 | 31-MAY-14:40 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 56.88 | 0.00 |
June | 16434.84 | 25-JUN-18:22 | 0.00 | 578.27 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 197.74 | 0.00 |
July | 15893.56 | 02-JUL-18:21 | 0.00 | 578.27 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 14.40 | 0.00 |
August | 10127.28 | 03-AUG-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.96 |
September | 11269.69 | 11-SEP-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.19 |
October | 3513.91 | 02-OCT-14:50 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.80 |
November | 3022.50 | 03-NOV-14:10 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.46 |
December | 1449.57 | 02-DEC-17:03 | 404.87 | 486.14 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.73 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1449.57 | 0.00 | 269.88 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16434.84 | 4021.58 | 2081.92 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 211.33 | 238.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4323.02 | 12-JAN-10:10 | 0.00 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.24 |
February | 4890.34 | 24-FEB-09:45 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.84 |
March | 8595.12 | 28-MAR-08:55 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.53 |
April | 26649.92 | 30-APR-09:52 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.61 |
May | 28106.95 | 29-MAY-09:41 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.10 |
June | 29926.22 | 25-JUN-07:41 | 587.05 | 335.39 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.00 |
July | 31246.94 | 02-JUL-09:01 | 652.28 | 372.66 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.50 |
August | 27868.50 | 27-AUG-10:01 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.38 |
September | 27946.16 | 03-SEP-08:51 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 423.15 |
October | 8265.08 | 20-OCT-09:00 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.80 |
November | 4366.36 | 04-NOV-09:30 | 0.00 | 223.61 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.01 |
December | 3011.79 | 07-DEC-09:35 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3011.79 | 0.00 | 223.59 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.38 | |
Maximum of Months | 31246.94 | 2478.65 | 1341.67 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 423.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17508.12 | 12-JAN-12:30 | 2116.67 | 2081.97 | 3841.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.48 |
February | 27604.84 | 20-FEB-14:22 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1181.45 |
March | 20826.01 | 19-MAR-13:02 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 623.52 |
April | 30705.07 | 16-APR-13:51 | 809.75 | 462.62 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.06 |
May | 26651.14 | 14-MAY-13:02 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.38 |
June | 28309.19 | 25-JUN-12:22 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 189.96 | 0.00 |
July | 28433.08 | 02-JUL-13:02 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 7.10 | 0.00 |
August | 29282.62 | 13-AUG-12:52 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.91 |
September | 32062.81 | 17-SEP-13:21 | 910.97 | 520.45 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.41 |
October | 29862.00 | 29-OCT-11:51 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1323.20 |
November | 29138.91 | 12-NOV-12:12 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 681.64 |
December | 28543.24 | 03-DEC-13:22 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1774.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17508.12 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32062.81 | 2116.67 | 2081.97 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 189.96 | 1774.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3112.47 | 12-JAN-15:50 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.69 |
February | 7872.96 | 24-FEB-16:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.16 |
March | 9246.22 | 21-MAR-16:00 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 301.14 |
April | 32261.90 | 16-APR-16:31 | 652.28 | 372.66 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.20 |
May | 28915.49 | 07-MAY-16:41 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.77 |
June | 33422.62 | 25-JUN-17:01 | 0.00 | 372.66 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 30.42 | 0.00 |
July | 33033.48 | 02-JUL-17:01 | 0.00 | 372.66 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.68 |
August | 31352.70 | 13-AUG-16:51 | 587.05 | 335.39 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.49 |
September | 28936.82 | 17-SEP-16:41 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.59 |
October | 26325.88 | 01-OCT-15:11 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.16 |
November | 8010.75 | 03-NOV-15:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.67 |
December | 3134.98 | 01-DEC-15:50 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3112.47 | 0.00 | 260.86 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33422.62 | 1239.33 | 670.83 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 30.42 | 301.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1524.23 | 21-JAN-17:02 | 607.30 | 729.22 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 702.90 |
February | 2258.57 | 24-FEB-14:10 | 4021.58 | 2081.92 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.93 |
March | 2640.98 | 24-MAR-13:50 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.07 |
April | 8878.46 | 18-APR-15:00 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 114.63 | 0.00 |
May | 9843.15 | 31-MAY-14:40 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 69.26 | 0.00 |
June | 20041.71 | 25-JUN-18:22 | 0.00 | 578.27 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 225.55 | 0.00 |
July | 18720.53 | 02-JUL-18:31 | 0.00 | 404.79 | 3914.20 | 0.00 | 0.00 | 0.00 | 0.00 | 27.50 | 0.00 |
August | 12170.09 | 04-AUG-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.48 |
September | 11060.58 | 11-SEP-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.85 |
October | 3245.73 | 20-OCT-14:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.84 |
November | 2987.52 | 03-NOV-13:30 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.76 |
December | 1543.51 | 02-DEC-17:03 | 404.87 | 486.14 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1524.23 | 0.00 | 269.88 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20041.71 | 4021.58 | 2081.92 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 225.55 | 702.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2126.14 | 12-JAN-10:30 | 2591.66 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.75 |
February | 3225.50 | 24-FEB-10:20 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.51 |
March | 6980.04 | 28-MAR-09:40 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.85 |
April | 25856.77 | 30-APR-09:52 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.03 |
May | 26417.86 | 14-MAY-10:12 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.87 |
June | 30000.68 | 25-JUN-07:41 | 587.05 | 335.39 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.72 |
July | 28203.68 | 23-JUL-08:41 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.47 |
August | 22881.64 | 20-AUG-08:52 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.20 |
September | 27651.20 | 03-SEP-09:01 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 498.22 |
October | 6866.45 | 20-OCT-09:40 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.26 |
November | 3342.54 | 03-NOV-13:30 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.82 |
December | 2134.96 | 30-DEC-06:04 | 1043.64 | 347.85 | 4950.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2126.14 | 326.14 | 186.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.82 | |
Maximum of Months | 30000.68 | 2591.66 | 1341.67 | 4950.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 498.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14146.65 | 12-JAN-12:40 | 1058.33 | 1040.98 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.93 |
February | 20924.01 | 24-FEB-13:40 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.26 |
March | 19138.36 | 24-MAR-13:20 | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.74 |
April | 30364.37 | 16-APR-13:22 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.90 |
May | 28630.89 | 14-MAY-13:32 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.40 |
June | 31003.62 | 25-JUN-14:21 | 809.75 | 462.62 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 273.35 | 0.00 |
July | 30050.23 | 30-JUL-13:42 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.41 |
August | 29035.82 | 13-AUG-13:42 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.58 |
September | 34471.74 | 04-SEP-13:21 | 910.97 | 520.45 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.99 |
October | 29531.69 | 01-OCT-13:32 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 626.44 |
November | 21943.91 | 03-NOV-13:30 | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.72 |
December | 18586.95 | 03-DEC-13:22 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2088.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14146.65 | 506.09 | 289.14 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34471.74 | 2010.83 | 1040.98 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 273.35 | 2088.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3110.77 | 12-JAN-15:50 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.42 |
February | 7598.11 | 24-FEB-16:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.69 |
March | 8672.69 | 21-MAR-16:00 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375.55 |
April | 30230.33 | 16-APR-16:41 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 11.16 | 0.00 |
May | 33946.80 | 14-MAY-16:51 | 652.28 | 372.66 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.42 |
June | 35757.24 | 25-JUN-17:01 | 0.00 | 372.66 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 14.35 | 0.00 |
July | 34227.11 | 23-JUL-17:21 | 0.00 | 372.66 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.88 |
August | 30007.61 | 13-AUG-16:21 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.84 |
September | 32662.17 | 04-SEP-16:41 | 587.05 | 335.39 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.16 |
October | 11844.88 | 11-OCT-16:00 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.93 |
November | 7685.19 | 03-NOV-15:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.57 |
December | 3138.49 | 01-DEC-15:50 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3110.77 | 0.00 | 260.86 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35757.24 | 1239.33 | 670.83 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 14.35 | 375.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9965.23 | 06-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1245.87 |
February | 7849.35 | 04-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 824.71 |
March | 6026.62 | 13-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356.48 |
April | 8129.39 | 17-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.62 |
May | 9531.26 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.69 |
June | 12440.41 | 27-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.94 |
July | 15729.97 | 05-JUL-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.64 |
August | 11267.57 | 28-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.21 |
September | 10405.71 | 11-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.10 |
October | 5640.67 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.55 |
November | 6382.29 | 25-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444.16 |
December | 9034.00 | 09-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4258.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5640.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.94 | |
Maximum of Months | 15729.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4258.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11545.86 | 07-JAN-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1846.13 |
February | 11962.45 | 28-FEB-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4316.64 |
March | 11170.65 | 13-MAR-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2879.16 |
April | 11110.99 | 03-APR-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2536.34 |
May | 6456.47 | 31-MAY-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.55 | 0.00 |
June | 8251.63 | 30-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.78 |
July | 7457.07 | 03-JUL-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.35 | 0.00 |
August | 7726.71 | 04-AUG-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.01 | 0.00 |
September | 7185.77 | 08-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.65 | 0.00 |
October | 7058.08 | 23-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 301.91 |
November | 12011.51 | 24-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2160.29 |
December | 10491.02 | 09-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5994.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6456.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12011.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.01 | 5994.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1356.42 |
February | 1470.75 | 24-FEB-14:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.00 |
March | 5756.16 | 24-MAR-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 570.01 |
April | 15806.49 | 18-APR-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.76 | 0.00 |
May | 18266.29 | 31-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.79 | 0.00 |
June | 20835.08 | 26-JUN-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.76 | 0.00 |
July | 19775.14 | 05-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.64 | 0.00 |
August | 20440.24 | 04-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.54 | 0.00 |
September | 17470.67 | 05-SEP-13:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.34 | 0.00 |
October | 7482.08 | 20-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.10 |
November | 4255.16 | 03-NOV-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.08 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1887.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20835.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.54 | 1887.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2067.14 | 12-JAN-16:30 | 222.14 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4370.13 | 24-FEB-17:00 | 222.14 | 450.11 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6971.46 | 31-MAR-24:00 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8501.03 | 16-APR-17:52 | 0.00 | 200.06 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3558.45 | 31-MAY-24:00 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5447.51 | 30-JUN-23:40 | 0.00 | 75.02 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7260.83 | 31-JUL-23:52 | 0.00 | 125.04 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8431.30 | 29-AUG-17:50 | 23.38 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3071.79 | 30-SEP-24:00 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5060.98 | 31-OCT-24:00 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6241.47 | 05-NOV-16:17 | 35.07 | 75.02 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7945.08 | 05-DEC-16:10 | 222.14 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2067.14 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8501.03 | 222.14 | 450.11 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1680.27 | 12-JAN-16:40 | 222.14 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3979.05 | 24-FEB-17:00 | 222.14 | 450.11 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6160.19 | 31-MAR-23:30 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7962.05 | 16-APR-17:52 | 0.00 | 200.06 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3344.67 | 31-MAY-24:00 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5230.05 | 30-JUN-23:53 | 0.00 | 75.02 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6897.96 | 31-JUL-23:52 | 0.00 | 125.04 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8070.67 | 29-AUG-17:50 | 23.38 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2668.31 | 04-SEP-17:50 | 0.00 | 175.05 | 13640.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4328.45 | 31-OCT-23:50 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5695.05 | 03-NOV-16:00 | 222.14 | 450.11 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7191.06 | 01-DEC-16:20 | 222.14 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1680.27 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8070.67 | 222.14 | 450.11 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1567.83 | 12-JAN-16:40 | 222.14 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3936.52 | 24-FEB-17:00 | 222.14 | 450.11 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5813.94 | 21-MAR-17:40 | 23.38 | 150.04 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8223.45 | 16-APR-17:42 | 0.00 | 225.07 | 70149.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3307.57 | 31-MAY-23:40 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5208.00 | 30-JUN-23:53 | 0.00 | 75.02 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6796.14 | 31-JUL-23:52 | 0.00 | 125.04 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8130.32 | 29-AUG-17:40 | 23.38 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2702.76 | 04-SEP-17:50 | 0.00 | 175.05 | 13640.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4170.28 | 11-OCT-17:00 | 70.15 | 250.06 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5674.04 | 03-NOV-16:00 | 222.14 | 450.11 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7058.11 | 01-DEC-16:20 | 222.14 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1567.83 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8223.45 | 222.14 | 450.11 | 70149.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 91275.89 | 13-JAN-17:00 | 9617.36 | 10941.12 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 183136.53 | 24-FEB-17:00 | 4808.68 | 5470.56 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358311.84 | 31-MAR-24:00 | 0.00 | 303.90 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 368026.96 | 17-APR-16:00 | 4808.68 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176666.46 | 31-MAY-24:00 | 0.00 | 303.90 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 269277.70 | 30-JUN-23:57 | 0.00 | 911.69 | 854173.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 360596.12 | 31-JUL-23:52 | 0.00 | 1519.49 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 392716.94 | 04-AUG-17:53 | 1518.53 | 5470.56 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 175419.04 | 30-SEP-24:00 | 0.00 | 303.90 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 268159.32 | 31-OCT-24:00 | 0.00 | 303.90 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 276767.59 | 03-NOV-16:00 | 4808.68 | 5470.56 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 367619.77 | 05-DEC-17:00 | 4808.68 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 91275.89 | 0.00 | 303.90 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 392716.94 | 9617.36 | 10941.12 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.168156E+13 | 1225209.91 | 10-JAN-16:49 | 0.871884E+12 | 2470555.89 | 30-JAN-07:30 |
February | 0.189778E+13 | 1322080.21 | 14-FEB-16:00 | 0.600894E+12 | 2424964.99 | 02-FEB-07:10 |
March | 0.251051E+13 | 1547191.31 | 23-MAR-15:00 | 0.189768E+12 | 1165278.66 | 06-MAR-06:10 |
April | 0.273186E+13 | 2089169.13 | 18-APR-15:20 | 0.602411E+11 | 797378.76 | 03-APR-04:10 |
May | 0.173653E+13 | 1603887.87 | 30-MAY-15:30 | 0.165064E+10 | 244983.88 | 02-MAY-05:10 |
June | 0.224537E+13 | 1882412.50 | 26-JUN-07:49 | 0.241501E+09 | 18525.06 | 02-JUN-05:10 |
July | 0.279582E+13 | 2101934.53 | 05-JUL-10:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.325042E+13 | 2275966.21 | 04-AUG-07:19 | 143844.39 | 239.74 | 07-AUG-05:10 |
September | 0.173129E+13 | 1614975.10 | 07-SEP-15:00 | 0.765237E+10 | 437121.41 | 30-SEP-05:10 |
October | 0.207982E+13 | 1554341.39 | 20-OCT-14:00 | 0.416388E+11 | 476514.61 | 16-OCT-05:10 |
November | 0.236602E+13 | 1532462.58 | 03-NOV-15:30 | 0.250494E+12 | 1506244.66 | 27-NOV-06:10 |
December | 0.280097E+13 | 1655598.69 | 26-DEC-16:40 | 0.533980E+12 | 1701928.67 | 11-DEC-06:10 |
Annual Sum or Average | 0.278280E+14 | 0.255845E+13 | ||||
Minimum of Months | 0.168156E+13 | 1225209.91 | 0.00 | 0.00 | ||
Maximum of Months | 0.325042E+13 | 2275966.21 | 0.871884E+12 | 2470555.89 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.274550E+12 | 0.422136E+11 | 0.766053E+12 | 0.213344E+12 | 0.185799E+12 | 0.131298E+11 | 0.00 | 0.623944E+10 | 0.250882E+09 | 0.128093E+12 | 0.710479E+10 | 0.447801E+11 | 0.00 |
February | 0.245633E+12 | 0.333846E+11 | 0.978954E+12 | 0.195333E+12 | 0.163146E+12 | 0.113462E+11 | 0.00 | 0.220885E+11 | 0.117618E+10 | 0.198996E+12 | 0.623489E+10 | 0.414865E+11 | 0.00 |
March | 0.288924E+12 | 0.305895E+11 | 0.141687E+13 | 0.226058E+12 | 0.186262E+12 | 0.143718E+11 | 0.00 | 0.440831E+11 | 0.467152E+10 | 0.244707E+12 | 0.567223E+10 | 0.482990E+11 | 0.00 |
April | 0.256169E+12 | 0.237285E+11 | 0.165903E+13 | 0.211502E+12 | 0.195360E+12 | 0.221874E+11 | 0.00 | 0.104232E+12 | 0.243284E+11 | 0.190070E+12 | 0.308460E+10 | 0.421779E+11 | 0.00 |
May | 0.275268E+12 | 0.202472E+11 | 0.774844E+12 | 0.219699E+12 | 0.223275E+12 | 0.390178E+11 | 0.00 | 0.628663E+11 | 0.364905E+11 | 0.416766E+11 | 0.698878E+09 | 0.424449E+11 | 0.00 |
June | 0.273914E+12 | 0.179813E+11 | 0.106252E+13 | 0.217935E+12 | 0.257438E+12 | 0.509598E+11 | 0.00 | 0.216956E+12 | 0.103510E+12 | 0.299515E+10 | 0.186816E+10 | 0.392942E+11 | 0.00 |
July | 0.255725E+12 | 0.191145E+11 | 0.139340E+13 | 0.213265E+12 | 0.268324E+12 | 0.668450E+11 | 0.00 | 0.396685E+12 | 0.144870E+12 | 26240318.93 | 0.221620E+10 | 0.353440E+11 | 0.00 |
August | 0.286199E+12 | 0.224420E+11 | 0.173200E+13 | 0.226058E+12 | 0.272921E+12 | 0.655211E+11 | 0.00 | 0.459319E+12 | 0.141729E+12 | 0.425412E+10 | 0.229591E+10 | 0.376826E+11 | 0.00 |
September | 0.256783E+12 | 0.267684E+11 | 0.740713E+12 | 0.211501E+12 | 0.223167E+12 | 0.370039E+11 | 0.00 | 0.944388E+11 | 0.576346E+11 | 0.468994E+11 | 0.171922E+10 | 0.346629E+11 | 0.00 |
October | 0.268899E+12 | 0.342467E+11 | 0.108340E+13 | 0.213342E+12 | 0.197122E+12 | 0.181036E+11 | 0.00 | 0.357374E+11 | 0.764864E+10 | 0.181534E+12 | 0.228094E+10 | 0.375060E+11 | 0.00 |
November | 0.270866E+12 | 0.391398E+11 | 0.135889E+13 | 0.205298E+12 | 0.180622E+12 | 0.132308E+11 | 0.00 | 0.401215E+11 | 0.343895E+10 | 0.210694E+12 | 0.445036E+10 | 0.392652E+11 | 0.00 |
December | 0.268151E+12 | 0.438560E+11 | 0.170972E+13 | 0.213270E+12 | 0.181460E+12 | 0.130999E+11 | 0.00 | 0.524128E+11 | 0.250628E+10 | 0.267840E+12 | 0.698990E+10 | 0.416638E+11 | 0.00 |
Annual Sum or Average | 0.322108E+13 | 0.353712E+12 | 0.146764E+14 | 0.256660E+13 | 0.253490E+13 | 0.364817E+12 | 0.00 | 0.153518E+13 | 0.528255E+12 | 0.151779E+13 | 0.446161E+11 | 0.484607E+12 | 0.00 |
Minimum of Months | 0.245633E+12 | 0.179813E+11 | 0.740713E+12 | 0.195333E+12 | 0.163146E+12 | 0.113462E+11 | 0.00 | 0.623944E+10 | 0.250882E+09 | 26240318.93 | 0.698878E+09 | 0.346629E+11 | 0.00 |
Maximum of Months | 0.288924E+12 | 0.438560E+11 | 0.173200E+13 | 0.226058E+12 | 0.272921E+12 | 0.668450E+11 | 0.00 | 0.459319E+12 | 0.144870E+12 | 0.267840E+12 | 0.710479E+10 | 0.482990E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.871884E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.600894E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.189768E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.602411E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.165064E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.241501E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 143844.39 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.765237E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.416388E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.250494E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.533980E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.255845E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.871884E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 325713.14 | 02-JAN-16:40 | 40855.88 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 233439.18 | 17-JAN-08:20 | 103186.73 | 02-JAN-06:19 | 27544.01 | 17-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 314611.94 | 14-FEB-16:00 | 40855.88 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 233429.20 | 22-FEB-08:20 | 109705.91 | 24-FEB-15:50 | 27105.07 | 27-FEB-20:40 | 0.00 | 01-FEB-00:10 |
March | 297349.23 | 01-MAR-16:00 | 40855.88 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 233420.72 | 13-MAR-07:19 | 145554.59 | 24-MAR-14:50 | 27266.94 | 06-MAR-06:19 | 0.00 | 01-MAR-00:10 |
April | 297349.23 | 10-APR-07:10 | 40855.88 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 233424.00 | 10-APR-07:19 | 262638.37 | 18-APR-15:20 | 52578.70 | 18-APR-12:39 | 0.00 | 01-APR-00:10 |
May | 281231.72 | 09-MAY-15:20 | 27558.46 | 01-MAY-19:10 | 423497.50 | 01-MAY-07:10 | 233415.40 | 25-MAY-07:19 | 251195.29 | 30-MAY-15:30 | 52334.61 | 31-MAY-11:09 | 0.00 | 01-MAY-00:10 |
June | 286531.10 | 13-JUN-07:10 | 27558.46 | 01-JUN-19:40 | 541788.89 | 01-JUN-07:10 | 233418.23 | 13-JUN-07:19 | 270819.84 | 30-JUN-15:20 | 53945.07 | 26-JUN-07:49 | 0.00 | 01-JUN-00:10 |
July | 286531.10 | 20-JUL-07:10 | 27558.46 | 01-JUL-19:00 | 660080.29 | 03-JUL-07:10 | 233418.23 | 20-JUL-07:19 | 270041.26 | 05-JUL-15:20 | 54460.04 | 05-JUL-10:30 | 0.00 | 01-JUL-00:10 |
August | 283655.84 | 31-AUG-07:10 | 40855.88 | 08-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 233416.70 | 31-AUG-07:19 | 287238.60 | 02-AUG-15:20 | 56095.39 | 04-AUG-07:19 | 0.00 | 01-AUG-00:10 |
September | 297349.23 | 21-SEP-07:10 | 40855.88 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 233424.00 | 21-SEP-07:19 | 256700.70 | 08-SEP-15:00 | 54569.45 | 08-SEP-11:00 | 0.00 | 01-SEP-00:10 |
October | 325713.14 | 31-OCT-07:10 | 40855.88 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 233439.18 | 31-OCT-07:19 | 172459.50 | 20-OCT-15:00 | 27675.72 | 20-OCT-14:00 | 0.00 | 01-OCT-00:10 |
November | 325713.14 | 01-NOV-07:10 | 40855.88 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 233439.18 | 01-NOV-07:19 | 157872.51 | 03-NOV-15:30 | 27338.37 | 03-NOV-13:20 | 0.00 | 01-NOV-00:10 |
December | 325713.14 | 01-DEC-16:30 | 40855.88 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 233439.18 | 20-DEC-08:20 | 99978.45 | 11-DEC-06:10 | 27124.39 | 13-DEC-05:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 281231.72 | 27558.46 | 423497.50 | 233415.40 | 99978.45 | 27105.07 | 0.00 | |||||||
Maximum of Months | 325713.14 | 40855.88 | 778371.69 | 233439.18 | 287238.60 | 56095.39 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 9056.88 | 12-JAN-16:40 | 1820.38 | 12-JAN-16:49 | 56450.62 | 22-JAN-10:00 | 5613.48 | 02-JAN-07:10 | 60136.52 | 31-JAN-12:00 | 0.00 |
February | 15080.50 | 24-FEB-17:49 | 3177.31 | 10-FEB-10:50 | 100000.00 | 20-FEB-15:09 | 5613.48 | 01-FEB-07:19 | 60476.62 | 21-FEB-12:00 | 0.00 |
March | 61841.71 | 25-MAR-14:00 | 49594.41 | 19-MAR-14:50 | 100000.00 | 01-MAR-01:39 | 5613.48 | 01-MAR-07:10 | 60435.36 | 01-MAR-12:00 | 0.00 |
April | 392125.64 | 18-APR-10:00 | 92515.43 | 15-APR-12:00 | 100000.00 | 01-APR-04:19 | 5613.48 | 01-APR-06:10 | 58462.45 | 03-APR-11:39 | 0.00 |
May | 274802.82 | 30-MAY-13:00 | 92515.43 | 05-MAY-12:00 | 100000.00 | 05-MAY-16:30 | 5613.48 | 01-MAY-19:30 | 55770.59 | 01-MAY-11:39 | 0.00 |
June | 468364.85 | 26-JUN-07:49 | 92515.43 | 09-JUN-09:39 | 37194.40 | 01-JUN-03:00 | 5613.48 | 09-JUN-09:00 | 52182.29 | 01-JUN-11:00 | 0.00 |
July | 504257.96 | 07-JUL-10:00 | 92515.43 | 03-JUL-07:40 | 13516.67 | 25-JUL-11:20 | 5613.48 | 01-JUL-09:50 | 48398.00 | 03-JUL-11:30 | 0.00 |
August | 655208.40 | 04-AUG-07:19 | 92515.43 | 01-AUG-07:40 | 100000.00 | 07-AUG-10:30 | 5613.48 | 01-AUG-09:30 | 46577.20 | 02-AUG-11:30 | 0.00 |
September | 281648.32 | 06-SEP-15:50 | 92515.43 | 05-SEP-14:00 | 100000.00 | 24-SEP-14:50 | 5613.48 | 02-SEP-11:50 | 47559.93 | 29-SEP-11:39 | 0.00 |
October | 180025.48 | 20-OCT-14:00 | 51836.00 | 20-OCT-14:00 | 100000.00 | 08-OCT-13:39 | 5613.48 | 06-OCT-06:10 | 51275.58 | 31-OCT-11:39 | 0.00 |
November | 46503.92 | 03-NOV-14:20 | 6275.83 | 03-NOV-14:20 | 100000.00 | 03-NOV-21:10 | 5613.48 | 01-NOV-06:10 | 54573.65 | 30-NOV-12:39 | 0.00 |
December | 23843.86 | 07-DEC-16:30 | 2889.22 | 06-DEC-14:09 | 100000.00 | 01-DEC-04:49 | 5613.48 | 01-DEC-07:10 | 57655.42 | 29-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 9056.88 | 1820.38 | 13516.67 | 5613.48 | 46577.20 | 0.00 | |||||
Maximum of Months | 655208.40 | 92515.43 | 100000.00 | 5613.48 | 60476.62 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1225209.91 | 10-JAN-16:49 | 325713.14 | 423497.50 | 40855.88 | 233326.38 | 76200.00 | 27038.88 | 0.00 | 3755.07 | 161.31 |
February | 1322080.21 | 14-FEB-16:00 | 314611.94 | 541788.89 | 0.00 | 233318.85 | 77367.84 | 3949.94 | 0.00 | 10724.62 | 580.65 |
March | 1547191.31 | 23-MAR-15:00 | 280450.63 | 660080.29 | 0.00 | 233302.19 | 123399.96 | 27081.96 | 0.00 | 45973.86 | 31513.18 |
April | 2089169.13 | 18-APR-15:20 | 280450.63 | 778371.69 | 0.00 | 233302.19 | 262638.37 | 51644.84 | 0.00 | 341136.35 | 92515.43 |
May | 1603887.87 | 30-MAY-15:30 | 280450.63 | 423497.50 | 0.00 | 233302.19 | 251195.29 | 51691.65 | 0.00 | 225452.51 | 92515.43 |
June | 1882412.50 | 26-JUN-07:49 | 280450.63 | 541788.89 | 0.00 | 233414.99 | 182213.20 | 53945.07 | 0.00 | 468364.85 | 92515.43 |
July | 2101934.53 | 05-JUL-10:30 | 280450.63 | 660080.29 | 0.00 | 233151.79 | 242501.64 | 54460.04 | 0.00 | 498992.04 | 92515.43 |
August | 2275966.21 | 04-AUG-07:19 | 280450.63 | 778371.69 | 0.00 | 233414.99 | 151802.91 | 56095.39 | 0.00 | 655208.40 | 92515.43 |
September | 1614975.10 | 07-SEP-15:00 | 280450.63 | 423497.50 | 0.00 | 233302.19 | 247923.93 | 51893.28 | 0.00 | 243541.78 | 92515.43 |
October | 1554341.39 | 20-OCT-14:00 | 280450.63 | 541788.89 | 0.00 | 233151.79 | 132504.05 | 27675.72 | 0.00 | 180025.48 | 51836.00 |
November | 1532462.58 | 03-NOV-15:30 | 280616.72 | 660080.29 | 0.00 | 233302.19 | 157872.51 | 27044.26 | 0.00 | 28634.80 | 5460.52 |
December | 1655598.69 | 26-DEC-16:40 | 325713.14 | 778371.69 | 40855.88 | 233326.38 | 78673.93 | 27047.53 | 0.00 | 20550.10 | 1113.02 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1225209.91 | 280450.63 | 423497.50 | 0.00 | 233151.79 | 76200.00 | 3949.94 | 0.00 | 3755.07 | 161.31 | |
Maximum of Months | 2275966.21 | 325713.14 | 778371.69 | 40855.88 | 233414.99 | 262638.37 | 56095.39 | 0.00 | 655208.40 | 92515.43 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 2470555.89 | 30-JAN-07:30 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 2424964.99 | 02-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 1165278.66 | 06-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 797378.76 | 03-APR-04:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 244983.88 | 02-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 18525.06 | 02-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 239.74 | 07-AUG-05:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 437121.41 | 30-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 476514.61 | 16-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 1506244.66 | 27-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 1701928.67 | 11-DEC-06:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 2470555.89 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 33.00 | 25.57 | 25.00 | 25.55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 41.83 | 25.81 | 23.00 | 25.79 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 56.67 | 26.00 | 27.67 | 26.01 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 49.33 | 26.21 | 26.00 | 26.22 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 82.83 | 26.80 | 49.00 | 26.82 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 232.33 | 27.86 | 161.50 | 27.87 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 384.83 | 28.08 | 227.17 | 28.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 239.33 | 27.54 | 140.33 | 27.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 134.33 | 27.52 | 60.00 | 27.53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 75.83 | 26.79 | 33.50 | 26.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 71.33 | 26.60 | 27.33 | 26.56 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 53.33 | 26.09 | 25.00 | 26.09 |
Annual Sum or Average | 0.00 | 0.00 | 1455.00 | 27.35 | 825.50 | 27.37 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 33.00 | 25.57 | 23.00 | 25.55 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 384.83 | 28.08 | 227.17 | 28.09 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.60 | 0.00 | 25.60 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.65 | 0.00 | 25.65 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 25.78 | 0.00 | 25.78 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.70 | 0.00 | 25.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.63 | 0.00 | 25.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.67 | 25.72 | 0.00 | 25.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 25.78 | 0.00 | 25.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 19.24 | 0.50 | 19.46 | 0.00 | 19.46 | 0.00 | 19.46 |
February | 0.17 | 18.41 | 0.00 | 18.41 | 0.00 | 18.41 | 0.00 | 18.41 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 18.55 | 0.00 | 18.55 | 0.00 | 18.55 | 0.00 | 18.55 |
Annual Sum or Average | 1.83 | 19.04 | 0.50 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 19.24 | 0.50 | 19.46 | 0.00 | 19.46 | 0.00 | 19.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.83 | 18.75 | 2.00 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
February | 5.00 | 19.01 | 1.00 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
March | 1.50 | 19.06 | 0.33 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
April | 0.67 | 19.35 | 0.17 | 19.51 | 0.00 | 19.51 | 0.00 | 19.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3.67 | 18.67 | 0.50 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
December | 5.33 | 18.86 | 1.00 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
Annual Sum or Average | 26.00 | 18.85 | 5.00 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.83 | 19.35 | 2.00 | 19.51 | 0.00 | 19.51 | 0.00 | 19.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.00 | 18.89 | 0.67 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
February | 3.17 | 18.86 | 0.83 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.30 | 2.67 | 27.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.28 | 2.67 | 27.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.45 | 0.17 | 26.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
December | 1.17 | 19.03 | 0.17 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
Annual Sum or Average | 9.50 | 18.90 | 1.67 | 19.10 | 9.17 | 22.78 | 5.50 | 23.77 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.00 | 19.20 | 0.83 | 19.20 | 4.50 | 27.30 | 2.67 | 27.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.17 | 18.53 | 0.00 | 18.53 | 0.00 | 18.53 | 0.00 | 18.53 |
February | 2.33 | 18.20 | 0.00 | 18.20 | 0.00 | 18.20 | 0.00 | 18.20 |
March | 0.17 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.00 | 3.17 | 28.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.23 | 5.33 | 28.23 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.23 | 6.00 | 28.23 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 28.23 | 8.50 | 28.24 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.30 | 2.50 | 28.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.31 | 3.67 | 28.31 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.50 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 |
December | 1.17 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 |
Annual Sum or Average | 8.33 | 18.51 | 0.00 | 18.51 | 29.33 | 26.07 | 29.17 | 27.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.17 | 19.35 | 0.00 | 19.35 | 8.67 | 28.31 | 8.50 | 28.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.00 | 18.63 | 0.17 | 18.68 | 0.00 | 18.68 | 0.00 | 18.68 |
February | 2.33 | 18.37 | 0.00 | 18.37 | 0.83 | 20.86 | 0.83 | 22.32 |
March | 0.17 | 19.17 | 0.00 | 19.17 | 1.33 | 26.91 | 1.33 | 27.37 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.98 | 5.00 | 27.99 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.63 | 3.33 | 27.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.94 | 4.33 | 27.97 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.95 | 6.50 | 27.98 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.97 | 6.17 | 27.97 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 28.15 | 7.17 | 28.16 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.24 | 4.50 | 28.24 |
November | 0.83 | 19.05 | 0.00 | 19.05 | 3.17 | 26.12 | 3.17 | 26.94 |
December | 1.33 | 18.47 | 0.00 | 18.47 | 1.50 | 23.46 | 1.50 | 25.00 |
Annual Sum or Average | 9.67 | 18.59 | 0.17 | 18.62 | 45.50 | 26.32 | 43.83 | 27.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.68 | 0.00 | 18.68 |
Maximum of Months | 5.00 | 19.17 | 0.17 | 19.17 | 7.33 | 28.24 | 7.17 | 28.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
February | 1.33 | 19.00 | 0.00 | 19.00 | 0.33 | 20.73 | 0.33 | 21.89 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.68 | 1.67 | 27.68 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 28.33 | 5.33 | 28.48 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.43 | 3.33 | 28.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 28.21 | 4.83 | 28.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 27.92 | 10.33 | 28.08 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 | 27.50 | 8.17 | 27.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.35 | 4.33 | 28.40 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.92 | 2.17 | 27.93 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.00 | 1.00 | 28.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.83 | 18.99 | 0.00 | 18.99 | 87.67 | 27.57 | 41.50 | 27.84 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 19.00 | 0.00 | 19.00 | 25.67 | 28.43 | 10.33 | 28.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 74.83 | 17.42 | 30.67 | 17.82 | 0.00 | 17.82 | 0.00 | 17.82 |
February | 41.00 | 17.41 | 17.83 | 17.77 | 0.00 | 17.77 | 0.00 | 17.77 |
March | 8.67 | 18.12 | 1.50 | 18.40 | 0.00 | 18.40 | 0.00 | 18.40 |
April | 1.00 | 18.77 | 0.17 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.39 | 1.67 | 27.38 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.34 | 0.00 | 27.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18.50 | 16.98 | 6.33 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 |
December | 39.17 | 17.30 | 13.83 | 17.55 | 0.00 | 17.55 | 0.00 | 17.55 |
Annual Sum or Average | 183.17 | 17.39 | 70.33 | 17.71 | 3.00 | 17.83 | 1.67 | 17.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 74.83 | 18.77 | 30.67 | 18.94 | 2.83 | 27.39 | 1.67 | 27.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 32.00 | 15.64 | 3.83 | 15.57 | 0.00 | 15.57 | 0.00 | 15.57 |
February | 17.50 | 16.10 | 0.50 | 16.06 | 0.00 | 16.06 | 0.00 | 16.06 |
March | 4.50 | 18.06 | 0.00 | 18.06 | 0.00 | 18.06 | 0.00 | 18.06 |
April | 0.67 | 18.29 | 0.00 | 18.29 | 2.50 | 25.82 | 2.50 | 26.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.21 | 5.83 | 28.21 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.40 | 6.00 | 28.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.49 | 7.67 | 28.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.21 | 3.17 | 28.21 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.35 | 3.50 | 28.35 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11.50 | 15.97 | 1.83 | 15.81 | 0.00 | 15.81 | 0.00 | 15.81 |
December | 20.50 | 16.23 | 2.00 | 16.09 | 0.00 | 16.09 | 0.00 | 16.09 |
Annual Sum or Average | 86.67 | 16.06 | 8.17 | 15.96 | 28.83 | 18.84 | 28.67 | 20.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.00 | 18.29 | 3.83 | 18.29 | 7.67 | 28.49 | 7.67 | 28.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 24.67 | 16.27 | 2.33 | 16.20 | 0.00 | 16.20 | 0.00 | 16.20 |
February | 10.33 | 17.00 | 0.67 | 16.95 | 0.83 | 17.72 | 0.83 | 18.38 |
March | 3.33 | 18.56 | 0.00 | 18.56 | 1.17 | 20.99 | 1.17 | 22.42 |
April | 0.50 | 18.08 | 0.00 | 18.08 | 5.00 | 27.07 | 4.67 | 27.50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.64 | 3.67 | 27.64 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.91 | 4.17 | 27.96 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.00 | 5.67 | 28.01 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.94 | 5.83 | 27.94 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 15.00 | 26.49 | 14.67 | 26.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.26 | 6.67 | 27.26 |
November | 9.17 | 16.46 | 1.17 | 16.37 | 3.00 | 19.01 | 3.00 | 20.69 |
December | 17.00 | 16.68 | 0.83 | 16.58 | 0.83 | 17.09 | 0.83 | 17.56 |
Annual Sum or Average | 65.00 | 16.65 | 5.00 | 16.57 | 53.00 | 21.25 | 51.17 | 23.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.20 | 0.00 | 16.20 |
Maximum of Months | 24.67 | 18.56 | 2.33 | 18.56 | 15.00 | 28.00 | 14.67 | 28.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 23.50 | 15.93 | 2.67 | 15.83 | 0.00 | 15.83 | 0.00 | 15.83 |
February | 13.00 | 16.27 | 0.83 | 16.19 | 0.00 | 16.19 | 0.00 | 16.19 |
March | 3.00 | 18.50 | 0.00 | 18.50 | 0.00 | 18.50 | 0.00 | 18.50 |
April | 0.33 | 18.64 | 0.00 | 18.64 | 3.83 | 27.81 | 2.17 | 28.13 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.53 | 2.50 | 28.56 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.73 | 3.33 | 28.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 28.75 | 5.17 | 28.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.36 | 3.17 | 28.39 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.39 | 3.33 | 28.42 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.84 | 0.50 | 27.84 |
November | 9.17 | 16.25 | 1.17 | 16.09 | 0.00 | 16.09 | 0.00 | 16.09 |
December | 17.00 | 16.56 | 2.00 | 16.37 | 0.00 | 16.37 | 0.00 | 16.37 |
Annual Sum or Average | 66.00 | 16.34 | 6.67 | 16.20 | 37.17 | 20.39 | 20.17 | 21.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 0.00 | 15.83 |
Maximum of Months | 23.50 | 18.64 | 2.67 | 18.64 | 11.17 | 28.75 | 5.17 | 28.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 137.67 | 16.53 | 62.17 | 16.91 | 0.00 | 16.91 | 0.00 | 16.91 |
February | 76.67 | 16.70 | 31.83 | 17.08 | 0.00 | 17.08 | 0.00 | 17.08 |
March | 27.83 | 17.00 | 8.00 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 |
April | 7.83 | 17.09 | 1.67 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 |
May | 0.17 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.60 | 3.00 | 27.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.48 | 0.83 | 27.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.33 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
October | 3.17 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
November | 43.00 | 16.55 | 13.50 | 16.87 | 0.00 | 16.87 | 0.00 | 16.87 |
December | 81.17 | 16.60 | 31.33 | 16.90 | 0.00 | 16.90 | 0.00 | 16.90 |
Annual Sum or Average | 377.83 | 16.65 | 148.50 | 16.98 | 6.33 | 17.11 | 3.83 | 17.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 137.67 | 19.41 | 62.17 | 19.41 | 4.67 | 27.60 | 3.00 | 27.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 71.00 | 14.93 | 18.50 | 14.92 | 0.00 | 14.92 | 0.00 | 14.92 |
February | 37.83 | 15.29 | 5.50 | 15.25 | 0.00 | 15.25 | 0.00 | 15.25 |
March | 16.67 | 16.38 | 0.67 | 16.37 | 0.00 | 16.37 | 0.00 | 16.37 |
April | 6.33 | 16.52 | 0.83 | 16.47 | 2.33 | 19.21 | 2.33 | 20.87 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.08 | 5.33 | 28.08 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.36 | 6.67 | 28.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 28.36 | 9.00 | 28.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.03 | 3.50 | 28.03 |
September | 0.33 | 19.26 | 0.00 | 19.26 | 3.33 | 27.36 | 3.33 | 27.75 |
October | 2.83 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
November | 25.33 | 15.25 | 4.17 | 15.16 | 0.00 | 15.16 | 0.00 | 15.16 |
December | 48.00 | 15.12 | 10.17 | 15.03 | 0.00 | 15.03 | 0.00 | 15.03 |
Annual Sum or Average | 208.33 | 15.31 | 39.83 | 15.23 | 31.33 | 16.68 | 30.17 | 17.81 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.92 | 0.00 | 14.92 |
Maximum of Months | 71.00 | 19.26 | 18.50 | 19.26 | 9.33 | 28.36 | 9.00 | 28.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 64.00 | 15.59 | 12.33 | 15.66 | 0.00 | 15.66 | 0.00 | 15.66 |
February | 32.67 | 16.08 | 3.67 | 16.17 | 0.00 | 16.17 | 0.00 | 16.17 |
March | 14.67 | 16.89 | 0.83 | 16.89 | 0.83 | 17.43 | 0.83 | 17.93 |
April | 4.67 | 16.76 | 0.17 | 16.87 | 3.17 | 21.33 | 2.83 | 23.12 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.63 | 2.67 | 27.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.07 | 4.33 | 28.13 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 28.04 | 6.00 | 28.07 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.94 | 5.83 | 27.94 |
September | 0.17 | 19.19 | 0.00 | 19.19 | 9.00 | 27.07 | 8.67 | 27.13 |
October | 1.83 | 18.98 | 0.00 | 18.98 | 3.17 | 24.75 | 3.17 | 26.04 |
November | 19.33 | 15.88 | 3.00 | 15.75 | 0.50 | 16.01 | 0.50 | 16.26 |
December | 38.83 | 15.69 | 7.17 | 15.67 | 0.00 | 15.67 | 0.00 | 15.67 |
Annual Sum or Average | 176.17 | 15.91 | 27.17 | 15.92 | 38.00 | 17.79 | 34.83 | 19.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.66 | 0.00 | 15.66 |
Maximum of Months | 64.00 | 19.19 | 12.33 | 19.19 | 9.00 | 28.07 | 8.67 | 28.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 60.00 | 15.02 | 13.83 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 |
February | 27.17 | 15.58 | 3.83 | 15.52 | 0.00 | 15.52 | 0.00 | 15.52 |
March | 12.00 | 17.02 | 1.17 | 16.89 | 0.00 | 16.89 | 0.00 | 16.89 |
April | 3.67 | 17.16 | 0.17 | 17.31 | 3.83 | 22.91 | 2.17 | 24.18 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.52 | 2.50 | 28.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 28.83 | 3.67 | 28.91 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 28.86 | 5.17 | 28.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.41 | 3.50 | 28.44 |
September | 0.17 | 19.16 | 0.00 | 19.16 | 4.67 | 28.01 | 3.17 | 28.20 |
October | 1.83 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
November | 16.67 | 15.54 | 3.17 | 15.40 | 0.00 | 15.40 | 0.00 | 15.40 |
December | 33.50 | 15.50 | 5.83 | 15.37 | 0.00 | 15.37 | 0.00 | 15.37 |
Annual Sum or Average | 155.00 | 15.54 | 28.00 | 15.43 | 37.50 | 17.68 | 20.17 | 18.61 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.97 | 0.00 | 14.97 |
Maximum of Months | 60.00 | 19.16 | 13.83 | 19.16 | 11.33 | 28.86 | 5.17 | 28.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.71 | 1.83 | 27.71 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.83 | 27.71 | 1.83 | 27.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.71 | 1.83 | 27.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 28.61 | 16.17 | 28.63 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 31.17 | 29.51 | 31.17 | 29.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 165.50 | 29.99 | 144.17 | 30.02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 214.67 | 29.81 | 191.50 | 29.83 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 165.50 | 29.99 | 144.17 | 30.02 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 354.67 | 24.12 | 16.33 | 24.19 | 13.67 | 24.25 |
February | 230.67 | 24.06 | 35.33 | 24.32 | 0.00 | 24.32 |
March | 183.83 | 24.01 | 68.33 | 24.57 | 0.00 | 24.57 |
April | 89.00 | 24.16 | 173.17 | 24.94 | 12.00 | 24.95 |
May | 40.00 | 26.18 | 360.33 | 25.13 | 34.33 | 25.24 |
June | 141.17 | 28.07 | 468.33 | 26.24 | 141.17 | 26.58 |
July | 235.00 | 28.04 | 496.50 | 26.78 | 235.00 | 27.09 |
August | 157.67 | 27.27 | 514.00 | 25.75 | 157.67 | 26.04 |
September | 42.17 | 27.54 | 320.33 | 25.61 | 35.50 | 25.84 |
October | 22.67 | 24.14 | 180.67 | 25.72 | 0.83 | 25.73 |
November | 99.83 | 24.00 | 158.33 | 24.96 | 0.00 | 24.96 |
December | 241.50 | 24.01 | 59.83 | 24.44 | 0.00 | 24.44 |
Annual Sum or Average | 1838.17 | 25.28 | 2851.50 | 25.47 | 630.17 | 25.73 |
Minimum of Months | 22.67 | 24.00 | 16.33 | 24.19 | 0.00 | 24.25 |
Maximum of Months | 354.67 | 28.07 | 514.00 | 26.78 | 235.00 | 27.09 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 480.17 | 23.66 | 12.67 | 23.68 | 12.67 | 23.69 |
February | 328.17 | 23.77 | 5.00 | 23.80 | 0.00 | 23.80 |
March | 224.67 | 23.90 | 43.00 | 24.15 | 0.00 | 24.15 |
April | 83.33 | 23.97 | 125.50 | 24.35 | 0.00 | 24.35 |
May | 11.33 | 23.94 | 320.50 | 24.33 | 0.00 | 24.33 |
June | 0.00 | 0.00 | 464.67 | 24.28 | 0.00 | 24.28 |
July | 0.00 | 0.00 | 497.00 | 24.33 | 0.00 | 24.33 |
August | 0.00 | 0.00 | 510.17 | 24.25 | 0.00 | 24.25 |
September | 22.33 | 23.90 | 286.33 | 24.45 | 0.00 | 24.45 |
October | 68.50 | 23.94 | 102.33 | 24.73 | 0.00 | 24.73 |
November | 174.17 | 23.94 | 91.83 | 24.18 | 0.00 | 24.18 |
December | 329.83 | 23.90 | 4.33 | 23.93 | 0.00 | 23.93 |
Annual Sum or Average | 1722.50 | 23.82 | 2463.33 | 24.17 | 12.67 | 24.17 |
Minimum of Months | 0.00 | 0.00 | 4.33 | 23.68 | 0.00 | 23.69 |
Maximum of Months | 480.17 | 23.97 | 510.17 | 24.73 | 12.67 | 24.73 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.49 | 182.50 | 21.19 | 182.50 | 21.02 |
February | 454.00 | 22.30 | 52.00 | 22.12 | 52.00 | 21.98 |
March | 450.17 | 23.05 | 2.33 | 23.04 | 2.33 | 23.03 |
April | 302.00 | 23.30 | 49.00 | 23.43 | 0.00 | 23.43 |
May | 86.83 | 23.60 | 250.67 | 24.04 | 0.00 | 24.04 |
June | 12.00 | 23.51 | 422.00 | 24.17 | 0.00 | 24.17 |
July | 0.00 | 0.00 | 479.00 | 24.19 | 0.00 | 24.19 |
August | 0.00 | 0.00 | 488.83 | 24.19 | 0.00 | 24.19 |
September | 77.83 | 23.53 | 200.17 | 24.09 | 0.00 | 24.09 |
October | 338.50 | 23.54 | 15.50 | 23.58 | 0.00 | 23.58 |
November | 403.67 | 22.74 | 39.00 | 22.64 | 25.67 | 22.51 |
December | 497.00 | 22.03 | 76.50 | 21.82 | 76.50 | 21.66 |
Annual Sum or Average | 3124.00 | 22.59 | 2257.50 | 23.03 | 339.00 | 22.88 |
Minimum of Months | 0.00 | 0.00 | 2.33 | 21.19 | 0.00 | 21.02 |
Maximum of Months | 502.00 | 23.60 | 488.83 | 24.19 | 182.50 | 24.19 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.48 | 353.67 | 20.27 | 353.67 | 20.18 |
February | 454.00 | 20.97 | 229.00 | 20.66 | 229.00 | 20.51 |
March | 502.50 | 21.95 | 99.00 | 21.70 | 99.00 | 21.52 |
April | 383.00 | 22.33 | 93.17 | 22.31 | 42.00 | 22.12 |
May | 169.33 | 23.20 | 206.17 | 23.70 | 3.17 | 23.70 |
June | 50.00 | 23.10 | 378.33 | 24.06 | 1.83 | 24.06 |
July | 11.00 | 23.40 | 462.33 | 24.17 | 1.50 | 24.17 |
August | 14.67 | 23.48 | 460.50 | 24.14 | 2.67 | 24.14 |
September | 194.50 | 23.06 | 164.17 | 23.58 | 0.00 | 23.58 |
October | 469.67 | 22.41 | 49.00 | 22.25 | 47.00 | 22.10 |
November | 469.17 | 21.41 | 166.50 | 21.05 | 164.50 | 20.83 |
December | 497.00 | 20.70 | 282.50 | 20.43 | 282.50 | 20.31 |
Annual Sum or Average | 3716.83 | 21.63 | 2944.33 | 22.00 | 1226.83 | 21.70 |
Minimum of Months | 11.00 | 20.48 | 49.00 | 20.27 | 0.00 | 20.18 |
Maximum of Months | 502.50 | 23.48 | 462.33 | 24.17 | 353.67 | 24.17 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.71 | 383.83 | 20.62 | 383.83 | 20.58 |
February | 454.00 | 21.37 | 177.83 | 21.14 | 177.83 | 21.01 |
March | 462.83 | 22.36 | 58.33 | 22.23 | 52.83 | 22.10 |
April | 333.17 | 23.10 | 68.17 | 23.31 | 6.00 | 23.34 |
May | 103.17 | 23.63 | 249.33 | 24.09 | 2.83 | 24.11 |
June | 36.83 | 25.13 | 435.67 | 24.42 | 19.17 | 24.50 |
July | 27.00 | 26.68 | 496.00 | 24.55 | 27.00 | 24.65 |
August | 9.17 | 26.42 | 488.83 | 24.32 | 8.50 | 24.36 |
September | 156.17 | 23.31 | 213.67 | 23.95 | 2.00 | 23.97 |
October | 398.00 | 23.11 | 23.17 | 23.17 | 0.00 | 23.17 |
November | 426.83 | 22.07 | 84.33 | 21.87 | 75.33 | 21.69 |
December | 497.00 | 21.21 | 215.00 | 21.03 | 215.00 | 20.94 |
Annual Sum or Average | 3406.17 | 22.10 | 2894.17 | 22.59 | 970.33 | 22.37 |
Minimum of Months | 9.17 | 20.71 | 23.17 | 20.62 | 0.00 | 20.58 |
Maximum of Months | 502.00 | 26.68 | 496.00 | 24.55 | 383.83 | 24.65 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.80 | 355.33 | 20.68 | 355.33 | 20.64 |
February | 445.67 | 21.32 | 167.33 | 21.12 | 167.33 | 21.01 |
March | 430.50 | 21.96 | 78.67 | 21.95 | 57.67 | 21.83 |
April | 324.00 | 22.51 | 115.33 | 23.01 | 21.67 | 23.09 |
May | 139.33 | 23.73 | 290.83 | 24.21 | 25.50 | 24.36 |
June | 66.83 | 24.57 | 408.33 | 24.38 | 27.00 | 24.52 |
July | 41.00 | 26.80 | 487.50 | 24.56 | 40.33 | 24.73 |
August | 38.33 | 24.69 | 455.83 | 24.21 | 17.50 | 24.29 |
September | 179.50 | 23.22 | 247.00 | 23.96 | 17.83 | 24.08 |
October | 369.50 | 22.59 | 46.00 | 22.84 | 0.00 | 22.84 |
November | 464.67 | 21.74 | 102.50 | 21.55 | 98.67 | 21.40 |
December | 494.83 | 21.02 | 279.17 | 20.89 | 278.50 | 20.83 |
Annual Sum or Average | 3496.17 | 21.94 | 3033.83 | 22.51 | 1107.33 | 22.35 |
Minimum of Months | 38.33 | 20.80 | 46.00 | 20.68 | 0.00 | 20.64 |
Maximum of Months | 502.00 | 26.80 | 487.50 | 24.56 | 355.33 | 24.73 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 442.33 | 21.08 | 295.00 | 20.89 | 277.00 | 20.75 |
February | 371.33 | 21.63 | 163.83 | 21.53 | 136.00 | 21.35 |
March | 373.17 | 22.22 | 118.33 | 22.36 | 60.50 | 22.24 |
April | 290.50 | 22.73 | 150.83 | 23.23 | 33.33 | 23.26 |
May | 133.00 | 23.50 | 283.33 | 24.11 | 14.50 | 24.20 |
June | 61.50 | 24.45 | 407.50 | 24.36 | 20.50 | 24.47 |
July | 34.83 | 26.81 | 484.83 | 24.58 | 34.17 | 24.72 |
August | 36.83 | 25.92 | 485.83 | 24.42 | 26.17 | 24.54 |
September | 156.67 | 23.72 | 271.33 | 24.28 | 29.67 | 24.46 |
October | 285.67 | 23.06 | 121.67 | 23.50 | 16.33 | 23.62 |
November | 374.83 | 21.99 | 131.67 | 22.02 | 93.50 | 21.85 |
December | 423.83 | 21.31 | 248.50 | 21.26 | 218.33 | 21.11 |
Annual Sum or Average | 2984.50 | 22.23 | 3162.67 | 22.87 | 960.00 | 22.71 |
Minimum of Months | 34.83 | 21.08 | 118.33 | 20.89 | 14.50 | 20.75 |
Maximum of Months | 442.33 | 26.81 | 485.83 | 24.58 | 277.00 | 24.72 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 494.67 | 21.11 | 264.00 | 20.96 | 264.00 | 20.89 |
February | 412.17 | 21.97 | 94.83 | 21.86 | 79.83 | 21.71 |
March | 314.17 | 22.78 | 81.17 | 23.18 | 5.17 | 23.19 |
April | 136.00 | 24.00 | 223.83 | 24.43 | 27.50 | 24.60 |
May | 88.67 | 24.13 | 347.17 | 24.36 | 25.00 | 24.48 |
June | 51.83 | 25.81 | 469.33 | 24.61 | 42.50 | 24.74 |
July | 94.83 | 26.07 | 497.00 | 24.83 | 94.83 | 25.00 |
August | 77.33 | 25.90 | 514.00 | 24.66 | 77.33 | 24.80 |
September | 134.50 | 23.62 | 297.17 | 24.29 | 23.33 | 24.42 |
October | 240.33 | 23.24 | 127.67 | 23.75 | 5.67 | 23.80 |
November | 319.17 | 22.53 | 99.33 | 22.77 | 28.67 | 22.68 |
December | 455.67 | 22.26 | 43.83 | 22.18 | 39.50 | 22.07 |
Annual Sum or Average | 2819.33 | 22.69 | 3059.33 | 23.39 | 713.33 | 23.35 |
Minimum of Months | 51.83 | 21.11 | 43.83 | 20.96 | 5.17 | 20.89 |
Maximum of Months | 494.67 | 26.07 | 514.00 | 24.83 | 264.00 | 25.00 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.77 | 490.17 | 19.75 | 490.17 | 19.75 |
February | 454.00 | 20.14 | 392.17 | 20.07 | 392.17 | 20.05 |
March | 514.00 | 21.11 | 263.50 | 20.87 | 263.50 | 20.75 |
April | 410.83 | 21.68 | 135.17 | 21.63 | 96.00 | 21.44 |
May | 209.50 | 23.01 | 194.17 | 23.57 | 0.83 | 23.56 |
June | 74.50 | 23.95 | 388.33 | 24.25 | 23.50 | 24.34 |
July | 17.50 | 25.13 | 474.83 | 24.35 | 13.17 | 24.39 |
August | 34.33 | 23.44 | 433.67 | 24.13 | 7.50 | 24.14 |
September | 243.50 | 22.65 | 167.83 | 23.27 | 5.00 | 23.24 |
October | 486.67 | 21.76 | 91.83 | 21.59 | 88.83 | 21.45 |
November | 489.00 | 20.77 | 281.83 | 20.47 | 281.83 | 20.33 |
December | 497.00 | 19.99 | 497.00 | 19.99 | 497.00 | 19.99 |
Annual Sum or Average | 3932.83 | 21.07 | 3810.50 | 21.48 | 2159.50 | 21.19 |
Minimum of Months | 17.50 | 19.77 | 91.83 | 19.75 | 0.83 | 19.75 |
Maximum of Months | 514.00 | 25.13 | 497.00 | 24.35 | 497.00 | 24.39 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.69 | 412.00 | 19.67 | 412.00 | 19.66 |
February | 383.50 | 20.22 | 309.67 | 20.10 | 309.67 | 20.06 |
March | 412.67 | 21.17 | 193.33 | 20.97 | 187.83 | 20.84 |
April | 320.83 | 21.71 | 137.17 | 21.99 | 77.17 | 21.87 |
May | 192.33 | 23.23 | 197.50 | 23.92 | 26.67 | 24.10 |
June | 105.50 | 23.83 | 308.17 | 24.31 | 32.33 | 24.49 |
July | 58.67 | 25.91 | 386.17 | 24.67 | 45.33 | 24.87 |
August | 66.50 | 24.01 | 344.17 | 24.23 | 23.17 | 24.34 |
September | 208.33 | 22.66 | 172.67 | 23.52 | 20.67 | 23.65 |
October | 397.17 | 21.73 | 57.83 | 21.69 | 48.33 | 21.60 |
November | 415.00 | 20.62 | 239.50 | 20.39 | 239.50 | 20.28 |
December | 422.00 | 19.93 | 406.00 | 19.90 | 406.00 | 19.89 |
Annual Sum or Average | 3409.50 | 21.20 | 3164.17 | 21.63 | 1828.67 | 21.39 |
Minimum of Months | 58.67 | 19.69 | 57.83 | 19.67 | 20.67 | 19.66 |
Maximum of Months | 427.00 | 25.91 | 412.00 | 24.67 | 412.00 | 24.87 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 459.17 | 20.44 | 357.17 | 20.22 | 347.50 | 20.11 |
February | 387.50 | 21.03 | 249.50 | 20.86 | 224.17 | 20.68 |
March | 402.33 | 21.61 | 215.00 | 21.62 | 162.17 | 21.44 |
April | 329.67 | 21.98 | 181.67 | 22.38 | 79.50 | 22.26 |
May | 190.17 | 23.14 | 245.17 | 23.84 | 15.67 | 23.94 |
June | 99.17 | 23.75 | 363.83 | 24.22 | 25.67 | 24.34 |
July | 53.50 | 25.35 | 458.83 | 24.49 | 34.83 | 24.62 |
August | 62.33 | 24.71 | 455.67 | 24.36 | 30.50 | 24.48 |
September | 201.83 | 23.32 | 257.33 | 24.03 | 39.33 | 24.19 |
October | 344.83 | 22.55 | 136.33 | 22.95 | 41.67 | 22.97 |
November | 416.67 | 21.32 | 216.17 | 21.20 | 187.33 | 21.01 |
December | 442.33 | 20.64 | 367.00 | 20.54 | 346.83 | 20.44 |
Annual Sum or Average | 3389.50 | 21.72 | 3503.67 | 22.26 | 1535.17 | 22.02 |
Minimum of Months | 53.50 | 20.44 | 136.33 | 20.22 | 15.67 | 20.11 |
Maximum of Months | 459.17 | 25.35 | 458.83 | 24.49 | 347.50 | 24.62 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.01 | 453.50 | 19.93 | 453.50 | 19.91 |
February | 442.17 | 20.55 | 310.67 | 20.39 | 308.33 | 20.32 |
March | 468.67 | 21.23 | 204.83 | 21.10 | 191.00 | 20.97 |
April | 353.50 | 21.82 | 162.50 | 22.20 | 69.33 | 22.11 |
May | 229.67 | 22.93 | 225.83 | 23.62 | 16.83 | 23.73 |
June | 107.50 | 23.55 | 380.33 | 24.21 | 26.00 | 24.33 |
July | 59.00 | 25.51 | 459.83 | 24.57 | 46.50 | 24.71 |
August | 58.67 | 24.25 | 453.50 | 24.30 | 25.67 | 24.39 |
September | 246.50 | 22.61 | 211.83 | 23.45 | 22.83 | 23.55 |
October | 437.83 | 21.76 | 74.50 | 21.85 | 41.83 | 21.78 |
November | 479.67 | 20.86 | 240.50 | 20.64 | 235.00 | 20.50 |
December | 497.00 | 20.28 | 437.83 | 20.20 | 437.83 | 20.17 |
Annual Sum or Average | 3882.17 | 21.30 | 3615.67 | 21.81 | 1874.67 | 21.57 |
Minimum of Months | 58.67 | 20.01 | 74.50 | 19.93 | 16.83 | 19.91 |
Maximum of Months | 502.00 | 25.51 | 459.83 | 24.57 | 453.50 | 24.71 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.61 | 497.17 | 19.60 | 497.17 | 19.60 |
February | 454.00 | 19.80 | 425.67 | 19.76 | 425.67 | 19.75 |
March | 514.00 | 20.66 | 350.33 | 20.49 | 350.33 | 20.42 |
April | 425.67 | 21.14 | 212.33 | 21.01 | 179.50 | 20.82 |
May | 261.83 | 22.55 | 178.50 | 23.12 | 11.50 | 23.07 |
June | 120.00 | 23.40 | 359.17 | 24.08 | 31.00 | 24.19 |
July | 49.50 | 24.48 | 450.33 | 24.33 | 25.33 | 24.40 |
August | 75.67 | 23.22 | 395.67 | 24.01 | 13.83 | 24.03 |
September | 282.67 | 22.11 | 175.83 | 22.70 | 31.33 | 22.58 |
October | 498.33 | 20.97 | 219.67 | 20.68 | 219.67 | 20.53 |
November | 489.00 | 20.15 | 344.33 | 19.91 | 344.33 | 19.82 |
December | 497.00 | 19.74 | 497.00 | 19.74 | 497.00 | 19.74 |
Annual Sum or Average | 4169.67 | 20.74 | 4106.00 | 21.12 | 2626.67 | 20.84 |
Minimum of Months | 49.50 | 19.61 | 175.83 | 19.60 | 11.50 | 19.60 |
Maximum of Months | 514.00 | 24.48 | 497.17 | 24.33 | 497.17 | 24.40 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.76 | 485.33 | 19.74 | 485.33 | 19.73 |
February | 454.00 | 20.02 | 393.83 | 19.92 | 393.83 | 19.88 |
March | 496.33 | 20.89 | 265.83 | 20.65 | 264.50 | 20.52 |
April | 382.33 | 21.41 | 203.67 | 21.55 | 138.83 | 21.36 |
May | 225.50 | 22.91 | 243.50 | 23.68 | 27.17 | 23.83 |
June | 131.17 | 23.42 | 363.67 | 24.13 | 36.33 | 24.30 |
July | 75.83 | 25.42 | 450.83 | 24.56 | 50.67 | 24.75 |
August | 87.17 | 23.76 | 409.50 | 24.13 | 26.67 | 24.24 |
September | 244.33 | 22.34 | 217.00 | 23.22 | 35.83 | 23.27 |
October | 489.67 | 21.30 | 145.17 | 21.07 | 142.83 | 20.92 |
November | 489.00 | 20.23 | 334.67 | 20.03 | 334.67 | 19.95 |
December | 497.00 | 19.85 | 491.17 | 19.84 | 491.17 | 19.84 |
Annual Sum or Average | 4074.33 | 20.97 | 4004.17 | 21.40 | 2427.83 | 21.16 |
Minimum of Months | 75.83 | 19.76 | 145.17 | 19.74 | 26.67 | 19.73 |
Maximum of Months | 502.00 | 25.42 | 491.17 | 24.56 | 491.17 | 24.75 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 466.83 | 20.10 | 389.17 | 19.91 | 383.00 | 19.82 |
February | 408.00 | 20.59 | 299.33 | 20.36 | 281.67 | 20.20 |
March | 428.33 | 21.16 | 262.33 | 21.07 | 224.83 | 20.91 |
April | 343.50 | 21.39 | 227.50 | 21.68 | 132.00 | 21.45 |
May | 228.17 | 22.61 | 223.00 | 23.43 | 19.50 | 23.48 |
June | 136.33 | 23.20 | 343.17 | 24.01 | 29.00 | 24.14 |
July | 79.00 | 24.55 | 433.33 | 24.41 | 38.83 | 24.55 |
August | 89.67 | 24.01 | 418.67 | 24.24 | 34.00 | 24.37 |
September | 233.50 | 22.76 | 250.83 | 23.58 | 49.50 | 23.67 |
October | 372.00 | 21.70 | 188.33 | 21.94 | 105.50 | 21.78 |
November | 440.00 | 20.70 | 266.83 | 20.51 | 242.67 | 20.30 |
December | 454.50 | 20.26 | 395.00 | 20.15 | 381.67 | 20.06 |
Annual Sum or Average | 3679.83 | 21.28 | 3697.50 | 21.77 | 1922.17 | 21.50 |
Minimum of Months | 79.00 | 20.10 | 188.33 | 19.91 | 19.50 | 19.82 |
Maximum of Months | 466.83 | 24.55 | 433.33 | 24.41 | 383.00 | 24.55 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.84 | 466.67 | 19.78 | 466.67 | 19.76 |
February | 446.67 | 20.23 | 356.67 | 20.09 | 354.67 | 20.03 |
March | 480.50 | 20.91 | 271.33 | 20.76 | 261.33 | 20.66 |
April | 364.00 | 21.34 | 205.33 | 21.61 | 119.67 | 21.43 |
May | 267.50 | 22.54 | 201.67 | 23.28 | 22.83 | 23.38 |
June | 136.83 | 23.15 | 360.83 | 24.05 | 32.50 | 24.18 |
July | 90.83 | 24.69 | 441.17 | 24.47 | 56.17 | 24.61 |
August | 88.17 | 23.70 | 426.00 | 24.19 | 30.83 | 24.28 |
September | 276.50 | 22.23 | 205.17 | 23.05 | 38.17 | 23.09 |
October | 446.67 | 21.18 | 159.17 | 21.09 | 135.33 | 20.94 |
November | 481.33 | 20.37 | 300.67 | 20.15 | 297.83 | 20.05 |
December | 497.00 | 19.99 | 458.67 | 19.92 | 458.67 | 19.90 |
Annual Sum or Average | 4078.00 | 21.01 | 3853.33 | 21.46 | 2274.67 | 21.22 |
Minimum of Months | 88.17 | 19.84 | 159.17 | 19.78 | 22.83 | 19.76 |
Maximum of Months | 502.00 | 24.69 | 466.67 | 24.47 | 466.67 | 24.61 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 365.67 | 27.00 | 0.00 | 27.00 |
February | 2.17 | 27.00 | 415.67 | 27.00 | 2.17 | 27.00 |
March | 3.83 | 27.00 | 514.00 | 27.00 | 3.83 | 27.00 |
April | 95.00 | 27.00 | 485.00 | 27.00 | 95.00 | 27.00 |
May | 20.00 | 27.00 | 508.00 | 27.00 | 20.00 | 27.00 |
June | 151.67 | 27.00 | 496.00 | 27.00 | 151.67 | 27.00 |
July | 293.17 | 27.00 | 497.00 | 27.00 | 293.17 | 27.00 |
August | 390.00 | 27.01 | 514.00 | 27.01 | 390.00 | 27.01 |
September | 50.33 | 27.00 | 485.00 | 27.00 | 50.33 | 27.00 |
October | 10.83 | 27.00 | 502.00 | 27.00 | 10.83 | 27.00 |
November | 5.17 | 27.00 | 485.67 | 27.00 | 5.17 | 27.00 |
December | 0.67 | 27.00 | 494.50 | 27.00 | 0.67 | 27.00 |
Annual Sum or Average | 1022.83 | 27.00 | 5762.50 | 27.00 | 1022.83 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 365.67 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 390.00 | 27.01 | 514.00 | 27.01 | 390.00 | 27.01 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 221.67 | 25.46 | 85.50 | 25.89 | 0.00 | 25.89 |
February | 15.50 | 27.00 | 256.17 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 444.33 | 27.00 | 0.00 | 27.00 |
April | 17.50 | 27.00 | 473.83 | 27.00 | 17.50 | 27.00 |
May | 8.50 | 27.00 | 508.00 | 27.00 | 8.50 | 27.00 |
June | 48.00 | 27.00 | 496.00 | 27.00 | 48.00 | 27.00 |
July | 76.50 | 27.00 | 497.00 | 27.00 | 76.50 | 27.00 |
August | 104.00 | 27.00 | 514.00 | 27.00 | 104.00 | 27.00 |
September | 24.17 | 27.00 | 485.00 | 27.00 | 24.17 | 27.00 |
October | 3.50 | 27.00 | 502.00 | 27.00 | 3.50 | 27.00 |
November | 14.00 | 27.00 | 374.83 | 27.00 | 0.67 | 27.00 |
December | 19.17 | 27.00 | 249.83 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 552.50 | 26.38 | 4886.50 | 26.94 | 282.83 | 26.94 |
Minimum of Months | 0.00 | 0.00 | 85.50 | 25.89 | 0.00 | 25.89 |
Maximum of Months | 221.67 | 27.00 | 514.00 | 27.00 | 104.00 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 361.17 | 24.63 | 113.00 | 24.54 | 68.00 | 24.27 |
February | 74.17 | 26.95 | 162.17 | 26.98 | 0.00 | 26.98 |
March | 11.67 | 27.00 | 342.83 | 27.00 | 0.00 | 27.00 |
April | 33.83 | 27.00 | 432.17 | 27.00 | 21.17 | 27.00 |
May | 16.17 | 27.00 | 508.00 | 27.00 | 16.17 | 27.00 |
June | 81.33 | 27.00 | 496.00 | 27.00 | 81.33 | 27.00 |
July | 111.83 | 27.00 | 497.00 | 27.00 | 111.83 | 27.00 |
August | 135.17 | 27.00 | 514.00 | 27.00 | 135.17 | 27.00 |
September | 31.83 | 27.00 | 479.17 | 27.00 | 31.83 | 27.00 |
October | 2.83 | 27.00 | 429.00 | 27.00 | 2.83 | 27.00 |
November | 45.83 | 27.00 | 278.50 | 27.00 | 0.50 | 27.00 |
December | 78.33 | 27.00 | 124.33 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 984.17 | 26.13 | 4376.17 | 26.78 | 468.83 | 26.75 |
Minimum of Months | 2.83 | 24.63 | 113.00 | 24.54 | 0.00 | 24.27 |
Maximum of Months | 361.17 | 27.00 | 514.00 | 27.00 | 135.17 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 94.50 | 27.00 | 502.00 | 27.00 | 94.50 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.06 | 485.00 | 27.06 | 485.00 | 27.06 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.17 | 497.00 | 27.17 | 497.00 | 27.17 |
August | 514.00 | 27.88 | 514.00 | 27.88 | 514.00 | 27.88 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5535.50 | 27.10 | 5943.00 | 27.10 | 5535.50 | 27.10 |
Minimum of Months | 94.50 | 27.00 | 454.00 | 27.00 | 94.50 | 27.00 |
Maximum of Months | 514.00 | 27.88 | 514.00 | 27.88 | 514.00 | 27.88 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99646 | 13.16087 | 0.60173 | 12.75310 |
February | 454.00000 | 27.00000 | 15.45026 | 0.69924 | 15.51571 |
March | 514.00000 | 27.00000 | 19.74902 | 0.81680 | 19.23897 |
April | 485.00000 | 27.00005 | 25.03747 | 0.93251 | 23.55117 |
May | 508.00000 | 27.00073 | 32.96489 | 0.25174 | 6.45014 |
June | 496.00000 | 27.00119 | 35.48086 | 0.36326 | 7.86589 |
July | 497.00000 | 27.00096 | 35.90088 | 0.42580 | 8.86982 |
August | 514.00000 | 27.00447 | 35.54585 | 0.46137 | 9.55212 |
September | 485.00000 | 27.00051 | 32.61385 | 0.25891 | 6.64157 |
October | 502.00000 | 27.00006 | 25.47348 | 0.86308 | 20.85364 |
November | 489.00000 | 27.00007 | 21.26784 | 0.81598 | 19.30730 |
December | 497.00000 | 26.99999 | 14.20324 | 0.74596 | 16.84501 |
Annual Sum or Average | 5943.00000 | 27.00039 | 25.64996 | 0.60189 | 13.92504 |
Minimum of Months | 454.00000 | 26.99646 | 13.16087 | 0.25174 | 6.45014 |
Maximum of Months | 514.00000 | 27.00447 | 35.90088 | 0.93251 | 23.55117 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.24614 | 13.31648 | 0.31864 | 8.29045 |
February | 454.00000 | 27.00000 | 15.43325 | 0.54781 | 11.58490 |
March | 514.00000 | 27.00000 | 19.74586 | 0.66400 | 14.53026 |
April | 485.00000 | 27.00005 | 25.01768 | 0.78518 | 18.33851 |
May | 508.00000 | 27.00057 | 33.04991 | 0.16931 | 5.81061 |
June | 496.00000 | 27.00121 | 35.51996 | 0.26828 | 6.69302 |
July | 497.00000 | 27.00106 | 35.92181 | 0.31089 | 7.14355 |
August | 514.00000 | 27.00103 | 35.55069 | 0.32528 | 7.35985 |
September | 485.00000 | 27.00044 | 32.65262 | 0.16649 | 5.93899 |
October | 502.00000 | 27.00006 | 25.44988 | 0.74514 | 16.89253 |
November | 489.00000 | 27.00006 | 21.23917 | 0.64711 | 14.21427 |
December | 497.00000 | 27.00000 | 14.19111 | 0.53584 | 11.20833 |
Annual Sum or Average | 5943.00000 | 26.93670 | 25.67041 | 0.45585 | 10.64625 |
Minimum of Months | 454.00000 | 26.24614 | 13.31648 | 0.16649 | 5.81061 |
Maximum of Months | 514.00000 | 27.00121 | 35.92181 | 0.78518 | 18.33851 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 25.23125 | 13.50561 | 0.07388 | 8.11113 |
February | 454.00000 | 26.99141 | 15.43432 | 0.47769 | 10.21900 |
March | 514.00000 | 27.00000 | 19.74788 | 0.60078 | 12.94224 |
April | 485.00000 | 27.00006 | 25.03067 | 0.73471 | 16.96401 |
May | 508.00000 | 27.00057 | 33.10031 | 0.14245 | 5.81379 |
June | 496.00000 | 27.00121 | 35.54162 | 0.26307 | 6.81025 |
July | 497.00000 | 27.00107 | 35.94244 | 0.31412 | 7.28279 |
August | 514.00000 | 27.00098 | 35.57609 | 0.32070 | 7.40291 |
September | 485.00000 | 26.99786 | 32.70306 | 0.12670 | 5.97108 |
October | 502.00000 | 27.00006 | 25.46945 | 0.67651 | 14.97480 |
November | 489.00000 | 27.00006 | 21.26134 | 0.57021 | 12.36151 |
December | 497.00000 | 27.00000 | 14.19620 | 0.46533 | 9.81200 |
Annual Sum or Average | 5943.00000 | 26.85010 | 25.70576 | 0.39610 | 9.87408 |
Minimum of Months | 454.00000 | 25.23125 | 13.50561 | 0.07388 | 5.81379 |
Maximum of Months | 514.00000 | 27.00121 | 35.94244 | 0.73471 | 16.96401 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99998 | 29.99913 | 0.99187 | 25.79888 |
February | 454.00000 | 27.00022 | 29.99216 | 1.17432 | 34.01948 |
March | 514.00000 | 27.00017 | 26.76018 | 1.31447 | 41.02839 |
April | 485.00000 | 27.05898 | 27.21588 | 1.47761 | 49.67422 |
May | 508.00000 | 26.99996 | 37.37191 | 0.54055 | 11.23962 |
June | 496.00000 | 27.00166 | 41.61986 | 0.82919 | 19.64323 |
July | 497.00000 | 27.16994 | 45.75953 | 1.13020 | 32.17246 |
August | 514.00000 | 27.87777 | 40.46141 | 1.48774 | 48.12641 |
September | 485.00000 | 27.00036 | 34.92004 | 0.58082 | 12.21402 |
October | 502.00000 | 27.00009 | 30.30541 | 1.24748 | 37.61083 |
November | 489.00000 | 26.99997 | 27.85631 | 1.34902 | 42.83684 |
December | 497.00000 | 27.00007 | 21.86176 | 1.40842 | 45.96610 |
Annual Sum or Average | 5943.00000 | 27.09515 | 32.88491 | 1.12792 | 33.37586 |
Minimum of Months | 454.00000 | 26.99996 | 21.86176 | 0.54055 | 11.23962 |
Maximum of Months | 514.00000 | 27.87777 | 45.75953 | 1.48774 | 49.67422 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.41604 | 14.00896 | 0.24368 | 6.70248 |
February | 454.00000 | 24.45602 | 15.84061 | 0.27633 | 6.88995 |
March | 514.00000 | 24.46197 | 20.31321 | 0.32771 | 7.62616 |
April | 485.00000 | 24.56688 | 27.51101 | 0.40844 | 9.11034 |
May | 508.00000 | 24.72784 | 41.72075 | -0.2853 | 8.98802 |
June | 496.00000 | 25.59421 | 55.53461 | 0.11326 | 14.49446 |
July | 497.00000 | 26.18734 | 63.65435 | 0.38154 | 18.65596 |
August | 514.00000 | 25.28898 | 56.86527 | 0.04118 | 10.76859 |
September | 485.00000 | 24.90815 | 38.85779 | -0.2169 | 9.70859 |
October | 502.00000 | 24.71677 | 25.28086 | 0.44088 | 9.76333 |
November | 489.00000 | 24.66090 | 21.68421 | 0.39131 | 8.79188 |
December | 497.00000 | 24.56095 | 14.31622 | 0.30212 | 7.29372 |
Annual Sum or Average | 5943.00000 | 24.88182 | 33.12603 | 0.20091 | 9.91542 |
Minimum of Months | 454.00000 | 24.41604 | 14.00896 | -0.2853 | 6.70248 |
Maximum of Months | 514.00000 | 26.18734 | 63.65435 | 0.44088 | 18.65596 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.68380 | 20.23586 | 0.11054 | 5.82067 |
February | 454.00000 | 23.94388 | 18.67388 | 0.17915 | 6.07094 |
March | 514.00000 | 24.17649 | 22.09486 | 0.28621 | 6.98450 |
April | 485.00000 | 24.24174 | 28.43918 | 0.36814 | 8.14577 |
May | 508.00000 | 24.23035 | 42.86427 | -0.3998 | 8.81780 |
June | 496.00000 | 24.26618 | 49.96100 | -0.2994 | 7.28875 |
July | 497.00000 | 24.33177 | 54.09696 | -0.2288 | 6.54083 |
August | 514.00000 | 24.25016 | 52.89056 | -0.2682 | 6.79609 |
September | 485.00000 | 24.30043 | 39.37870 | -0.3917 | 8.90804 |
October | 502.00000 | 24.32523 | 27.41066 | 0.36969 | 8.19548 |
November | 489.00000 | 24.24860 | 24.33407 | 0.31476 | 7.41832 |
December | 497.00000 | 24.13183 | 17.56641 | 0.22341 | 6.24844 |
Annual Sum or Average | 5943.00000 | 24.17875 | 33.30009 | 0.02017 | 7.27328 |
Minimum of Months | 454.00000 | 23.68380 | 17.56641 | -0.3998 | 5.82067 |
Maximum of Months | 514.00000 | 24.33177 | 54.09696 | 0.36969 | 8.90804 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.48553 | 19.86341 | -0.4562 | 11.23094 |
February | 454.00000 | 22.30198 | 21.61047 | -0.2362 | 7.69547 |
March | 514.00000 | 23.18593 | 25.57395 | 0.02199 | 6.03635 |
April | 485.00000 | 23.59266 | 31.04883 | 0.18146 | 6.50731 |
May | 508.00000 | 24.01918 | 43.92070 | -0.5028 | 10.82614 |
June | 496.00000 | 24.14223 | 51.26174 | -0.3902 | 8.49230 |
July | 497.00000 | 24.17928 | 55.85441 | -0.3418 | 7.69472 |
August | 514.00000 | 24.18265 | 54.40654 | -0.3496 | 7.83052 |
September | 485.00000 | 24.06085 | 40.43578 | -0.5095 | 11.12062 |
October | 502.00000 | 23.73834 | 29.58556 | 0.19979 | 6.24021 |
November | 489.00000 | 22.96909 | 27.58225 | -0.0190 | 7.02118 |
December | 497.00000 | 22.03252 | 21.54191 | -0.3027 | 8.44204 |
Annual Sum or Average | 5943.00000 | 23.33204 | 35.35349 | -0.2258 | 8.26292 |
Minimum of Months | 454.00000 | 21.48553 | 19.86341 | -0.5095 | 6.03635 |
Maximum of Months | 514.00000 | 24.18265 | 55.85441 | 0.19979 | 11.23094 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.47729 | 21.19975 | -0.7326 | 19.46213 |
February | 454.00000 | 20.96526 | 23.13526 | -0.5843 | 15.13403 |
March | 514.00000 | 21.99730 | 27.65753 | -0.2814 | 8.84014 |
April | 485.00000 | 22.69283 | 33.08352 | -0.0430 | 8.19813 |
May | 508.00000 | 23.75545 | 44.75834 | -0.5974 | 13.79020 |
June | 496.00000 | 24.04583 | 51.65440 | -0.4173 | 9.49302 |
July | 497.00000 | 24.14881 | 56.00294 | -0.3424 | 7.77320 |
August | 514.00000 | 24.11003 | 54.73214 | -0.3693 | 8.17882 |
September | 485.00000 | 23.67334 | 41.68305 | -0.6526 | 15.94343 |
October | 502.00000 | 22.51001 | 32.47660 | -0.1073 | 7.09588 |
November | 489.00000 | 21.51499 | 30.13966 | -0.3898 | 12.16532 |
December | 497.00000 | 20.69827 | 23.59935 | -0.6528 | 16.75987 |
Annual Sum or Average | 5943.00000 | 22.56250 | 36.80253 | -0.4298 | 11.86524 |
Minimum of Months | 454.00000 | 20.47729 | 21.19975 | -0.7326 | 7.09588 |
Maximum of Months | 514.00000 | 24.14881 | 56.00294 | -0.0430 | 19.46213 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.70975 | 19.00896 | -0.6708 | 15.56313 |
February | 454.00000 | 21.36747 | 19.85328 | -0.4779 | 11.56886 |
March | 514.00000 | 22.54247 | 23.50434 | -0.1376 | 7.25414 |
April | 485.00000 | 23.43216 | 29.06793 | 0.14019 | 7.14830 |
May | 508.00000 | 24.05765 | 42.39986 | -0.4729 | 10.89615 |
June | 496.00000 | 24.29678 | 49.19980 | -0.2685 | 7.70280 |
July | 497.00000 | 24.43019 | 53.26040 | -0.1728 | 6.60631 |
August | 514.00000 | 24.26054 | 52.26107 | -0.2565 | 6.98528 |
September | 485.00000 | 23.96541 | 39.44239 | -0.5321 | 13.12303 |
October | 502.00000 | 23.31995 | 28.39490 | 0.09136 | 6.17055 |
November | 489.00000 | 22.31544 | 25.67908 | -0.1824 | 8.46671 |
December | 497.00000 | 21.20685 | 19.16320 | -0.5116 | 11.41450 |
Annual Sum or Average | 5943.00000 | 23.00432 | 33.56468 | -0.2866 | 9.38341 |
Minimum of Months | 454.00000 | 20.70975 | 19.00896 | -0.6708 | 6.17055 |
Maximum of Months | 514.00000 | 24.43019 | 53.26040 | 0.14019 | 15.56313 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.79711 | 18.03805 | -0.6390 | 14.75764 |
February | 454.00000 | 21.36781 | 18.99096 | -0.4555 | 11.23024 |
March | 514.00000 | 22.32476 | 22.91826 | -0.1517 | 7.87788 |
April | 485.00000 | 23.07071 | 29.01002 | 0.10980 | 8.67308 |
May | 508.00000 | 24.01589 | 42.18852 | -0.3889 | 11.17101 |
June | 496.00000 | 24.18123 | 49.23127 | -0.2117 | 8.55455 |
July | 497.00000 | 24.35681 | 53.26207 | -0.0983 | 7.27424 |
August | 514.00000 | 24.06727 | 52.58539 | -0.2423 | 7.74410 |
September | 485.00000 | 23.84785 | 39.16704 | -0.4704 | 14.10851 |
October | 502.00000 | 23.05610 | 28.12578 | 0.06991 | 6.85337 |
November | 489.00000 | 21.86145 | 25.68889 | -0.2701 | 8.94767 |
December | 497.00000 | 21.04106 | 18.44206 | -0.5532 | 12.45927 |
Annual Sum or Average | 5943.00000 | 22.84423 | 33.26942 | -0.2740 | 9.94900 |
Minimum of Months | 454.00000 | 20.79711 | 18.03805 | -0.6390 | 6.85337 |
Maximum of Months | 514.00000 | 24.35681 | 53.26207 | 0.10980 | 14.75764 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.44391 | 17.72730 | -0.4566 | 13.66757 |
February | 454.00000 | 22.11221 | 18.43088 | -0.2551 | 10.56159 |
March | 514.00000 | 22.75730 | 22.48444 | -0.0416 | 8.44906 |
April | 485.00000 | 23.33486 | 28.59691 | 0.17173 | 9.45347 |
May | 508.00000 | 24.00281 | 42.29789 | -0.4415 | 11.63922 |
June | 496.00000 | 24.20916 | 49.30579 | -0.2651 | 8.38031 |
July | 497.00000 | 24.40239 | 53.20125 | -0.1352 | 6.91363 |
August | 514.00000 | 24.26571 | 51.97748 | -0.1776 | 7.11484 |
September | 485.00000 | 24.07330 | 38.71739 | -0.3802 | 12.89669 |
October | 502.00000 | 23.53509 | 27.24914 | 0.21334 | 8.47553 |
November | 489.00000 | 22.53521 | 24.98685 | -0.1009 | 9.76126 |
December | 497.00000 | 21.75910 | 17.95561 | -0.3590 | 12.01244 |
Annual Sum or Average | 5943.00000 | 23.21123 | 32.87787 | -0.1855 | 9.92754 |
Minimum of Months | 454.00000 | 21.44391 | 17.72730 | -0.4566 | 6.91363 |
Maximum of Months | 514.00000 | 24.40239 | 53.20125 | 0.21334 | 13.66757 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.15209 | 17.50244 | -0.5225 | 12.07500 |
February | 454.00000 | 22.18586 | 17.84277 | -0.2230 | 8.63831 |
March | 514.00000 | 23.38919 | 21.26576 | 0.13917 | 7.46474 |
April | 485.00000 | 24.19383 | 26.95474 | 0.44722 | 11.15404 |
May | 508.00000 | 24.16518 | 41.68995 | -0.3077 | 9.40848 |
June | 496.00000 | 24.42587 | 48.44536 | -0.0683 | 7.38762 |
July | 497.00000 | 24.59496 | 52.42330 | 0.07157 | 7.46325 |
August | 514.00000 | 24.47210 | 51.14561 | 0.03720 | 6.74719 |
September | 485.00000 | 24.11601 | 38.52373 | -0.3467 | 11.54197 |
October | 502.00000 | 23.80690 | 26.59509 | 0.28504 | 8.06701 |
November | 489.00000 | 23.11501 | 23.65529 | 0.06564 | 7.67927 |
December | 497.00000 | 22.43828 | 16.84981 | -0.1653 | 7.15869 |
Annual Sum or Average | 5943.00000 | 23.51383 | 32.04066 | -0.0481 | 8.71809 |
Minimum of Months | 454.00000 | 21.15209 | 16.84981 | -0.5225 | 6.74719 |
Maximum of Months | 514.00000 | 24.59496 | 52.42330 | 0.44722 | 12.07500 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.76836 | 19.37279 | -1.0083 | 28.90311 |
February | 454.00000 | 20.13847 | 21.54324 | -0.8514 | 22.56777 |
March | 514.00000 | 21.10740 | 26.38214 | -0.5193 | 12.96895 |
April | 485.00000 | 22.06200 | 32.02662 | -0.2036 | 9.47796 |
May | 508.00000 | 23.64712 | 43.65012 | -0.6353 | 15.69701 |
June | 496.00000 | 24.12610 | 50.52704 | -0.3628 | 9.45140 |
July | 497.00000 | 24.29485 | 55.00978 | -0.2665 | 7.23521 |
August | 514.00000 | 24.09939 | 53.95162 | -0.3577 | 8.35384 |
September | 485.00000 | 23.40753 | 40.98148 | -0.7444 | 20.17257 |
October | 502.00000 | 21.82803 | 31.32441 | -0.2741 | 8.24687 |
November | 489.00000 | 20.77220 | 28.69568 | -0.5996 | 16.43366 |
December | 497.00000 | 19.98503 | 21.38118 | -0.9113 | 24.70134 |
Annual Sum or Average | 5943.00000 | 22.11968 | 35.53176 | -0.5590 | 15.27949 |
Minimum of Months | 454.00000 | 19.76836 | 19.37279 | -1.0083 | 7.23521 |
Maximum of Months | 514.00000 | 24.29485 | 55.00978 | -0.2036 | 28.90311 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.69286 | 18.54245 | -1.0002 | 28.75304 |
February | 385.00000 | 20.23351 | 20.27022 | -0.7979 | 20.91651 |
March | 433.00000 | 21.31121 | 24.98279 | -0.4398 | 11.82257 |
April | 410.00000 | 22.28599 | 30.37573 | -0.1042 | 10.67829 |
May | 430.00000 | 23.72398 | 42.77937 | -0.5085 | 15.29534 |
June | 418.00000 | 24.06034 | 50.12915 | -0.2827 | 11.19106 |
July | 422.00000 | 24.37172 | 54.29598 | -0.1310 | 8.39771 |
August | 433.00000 | 24.04740 | 53.49931 | -0.2836 | 8.96120 |
September | 410.00000 | 23.42991 | 40.03438 | -0.6396 | 20.41186 |
October | 427.00000 | 21.91934 | 29.79575 | -0.2227 | 7.90915 |
November | 417.00000 | 20.63151 | 27.52338 | -0.6201 | 16.03669 |
December | 422.00000 | 19.93020 | 20.26785 | -0.9094 | 24.73530 |
Annual Sum or Average | 5034.00000 | 22.14926 | 34.48304 | -0.4931 | 15.37112 |
Minimum of Months | 385.00000 | 19.69286 | 18.54245 | -1.0002 | 7.90915 |
Maximum of Months | 433.00000 | 24.37172 | 54.29598 | -0.1042 | 28.75304 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.74863 | 18.15018 | -0.6678 | 20.36699 |
February | 454.00000 | 21.50030 | 19.56664 | -0.4269 | 14.72491 |
March | 514.00000 | 22.17194 | 24.22937 | -0.1998 | 10.55697 |
April | 485.00000 | 22.71192 | 30.20720 | 0.01402 | 10.66342 |
May | 508.00000 | 23.76150 | 43.02306 | -0.5322 | 14.51807 |
June | 496.00000 | 24.05196 | 50.45432 | -0.3408 | 10.14358 |
July | 497.00000 | 24.30225 | 54.71080 | -0.2014 | 7.66775 |
August | 514.00000 | 24.18712 | 53.23099 | -0.2329 | 8.08328 |
September | 485.00000 | 23.85136 | 39.33105 | -0.4581 | 15.95304 |
October | 502.00000 | 23.05082 | 28.37484 | 0.09764 | 8.94267 |
November | 489.00000 | 21.78484 | 26.89169 | -0.2998 | 13.31409 |
December | 497.00000 | 21.02612 | 19.77585 | -0.5854 | 18.02687 |
Annual Sum or Average | 5943.00000 | 22.77331 | 34.12930 | -0.3188 | 12.71678 |
Minimum of Months | 454.00000 | 20.74863 | 18.15018 | -0.6678 | 7.66775 |
Maximum of Months | 514.00000 | 24.30225 | 54.71080 | 0.09764 | 20.36699 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.01059 | 18.47836 | -0.9080 | 25.18563 |
February | 454.00000 | 20.64207 | 20.14740 | -0.6801 | 17.80541 |
March | 514.00000 | 21.48487 | 24.88034 | -0.3813 | 10.99778 |
April | 485.00000 | 22.44943 | 30.47262 | -0.0323 | 10.14397 |
May | 508.00000 | 23.54221 | 43.41850 | -0.5603 | 15.90341 |
June | 496.00000 | 24.03826 | 50.29501 | -0.2694 | 10.49937 |
July | 497.00000 | 24.35158 | 54.42944 | -0.1098 | 7.96748 |
August | 514.00000 | 24.16344 | 53.27760 | -0.2000 | 7.96222 |
September | 485.00000 | 23.37204 | 40.36238 | -0.6402 | 20.29315 |
October | 502.00000 | 22.05995 | 29.83170 | -0.1650 | 7.92782 |
November | 489.00000 | 20.93076 | 27.70062 | -0.5238 | 14.11758 |
December | 497.00000 | 20.28260 | 20.23878 | -0.8010 | 20.85600 |
Annual Sum or Average | 5943.00000 | 22.29149 | 34.59286 | -0.4374 | 14.08875 |
Minimum of Months | 454.00000 | 20.01059 | 18.47836 | -0.9080 | 7.92782 |
Maximum of Months | 514.00000 | 24.35158 | 54.42944 | -0.0323 | 25.18563 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.60504 | 19.74124 | -1.1033 | 32.98607 |
February | 454.00000 | 19.80106 | 22.32144 | -0.9853 | 28.38033 |
March | 514.00000 | 20.65526 | 27.51893 | -0.6690 | 16.89023 |
April | 485.00000 | 21.50339 | 33.18272 | -0.3601 | 13.08488 |
May | 508.00000 | 23.28813 | 44.49702 | -0.7580 | 20.71844 |
June | 496.00000 | 23.94798 | 51.04503 | -0.4157 | 11.72793 |
July | 497.00000 | 24.22538 | 55.32666 | -0.2814 | 7.81489 |
August | 514.00000 | 23.97334 | 54.43889 | -0.3951 | 9.47374 |
September | 485.00000 | 22.96643 | 42.07016 | -0.9025 | 27.14783 |
October | 502.00000 | 20.99477 | 33.12444 | -0.4996 | 12.82129 |
November | 489.00000 | 20.14806 | 30.31912 | -0.7931 | 22.60572 |
December | 497.00000 | 19.73990 | 22.64007 | -1.0272 | 29.68401 |
Annual Sum or Average | 5943.00000 | 21.75492 | 36.47902 | -0.6799 | 19.34664 |
Minimum of Months | 454.00000 | 19.60504 | 19.74124 | -1.1033 | 7.81489 |
Maximum of Months | 514.00000 | 24.22538 | 55.32666 | -0.2814 | 32.98607 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.76151 | 19.26406 | -1.0364 | 30.24613 |
February | 454.00000 | 20.01914 | 21.63740 | -0.8921 | 25.09469 |
March | 514.00000 | 20.99945 | 26.33436 | -0.5421 | 14.66870 |
April | 485.00000 | 22.01100 | 31.68427 | -0.1909 | 12.44524 |
May | 508.00000 | 23.56704 | 43.42874 | -0.5542 | 16.73558 |
June | 496.00000 | 23.91800 | 50.57067 | -0.3019 | 12.23708 |
July | 497.00000 | 24.28987 | 54.62394 | -0.1266 | 8.35981 |
August | 514.00000 | 23.97279 | 53.86530 | -0.2799 | 9.07088 |
September | 485.00000 | 23.25390 | 40.76437 | -0.6992 | 23.00991 |
October | 502.00000 | 21.36708 | 31.72853 | -0.3752 | 10.14287 |
November | 489.00000 | 20.22704 | 29.64823 | -0.7558 | 20.70005 |
December | 497.00000 | 19.85089 | 22.00985 | -0.9827 | 27.84018 |
Annual Sum or Average | 5943.00000 | 21.95336 | 35.59006 | -0.5586 | 17.45770 |
Minimum of Months | 454.00000 | 19.76151 | 19.26406 | -1.0364 | 8.35981 |
Maximum of Months | 514.00000 | 24.28987 | 54.62394 | -0.1266 | 30.24613 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.37499 | 18.85278 | -0.8019 | 24.90837 |
February | 454.00000 | 20.95571 | 20.70342 | -0.6008 | 19.65921 |
March | 514.00000 | 21.64568 | 25.48396 | -0.3610 | 13.22758 |
April | 485.00000 | 22.23713 | 31.33418 | -0.1249 | 13.16261 |
May | 508.00000 | 23.45461 | 43.80427 | -0.6399 | 18.71237 |
June | 496.00000 | 23.86114 | 51.03461 | -0.3970 | 12.54369 |
July | 497.00000 | 24.21265 | 55.10677 | -0.2214 | 8.48147 |
August | 514.00000 | 24.06436 | 53.72172 | -0.2685 | 9.17007 |
September | 485.00000 | 23.52274 | 40.24357 | -0.5831 | 20.86410 |
October | 502.00000 | 22.35179 | 29.98013 | -0.0983 | 10.44080 |
November | 489.00000 | 21.08657 | 28.63538 | -0.5083 | 17.27998 |
December | 497.00000 | 20.59577 | 21.29347 | -0.7370 | 22.58796 |
Annual Sum or Average | 5943.00000 | 22.37631 | 35.14719 | -0.4440 | 15.86823 |
Minimum of Months | 454.00000 | 20.37499 | 18.85278 | -0.8019 | 8.48147 |
Maximum of Months | 514.00000 | 24.21265 | 55.10677 | -0.0983 | 24.90837 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.83676 | 19.09731 | -1.0013 | 29.06973 |
February | 454.00000 | 20.29245 | 21.15484 | -0.8055 | 22.44755 |
March | 514.00000 | 21.11704 | 25.98670 | -0.5033 | 13.68591 |
April | 485.00000 | 22.03939 | 31.49975 | -0.1511 | 12.46948 |
May | 508.00000 | 23.23352 | 44.19186 | -0.6651 | 20.10769 |
June | 496.00000 | 23.87294 | 50.80293 | -0.3174 | 12.61207 |
July | 497.00000 | 24.26222 | 54.81135 | -0.1294 | 8.71288 |
August | 514.00000 | 24.03397 | 53.77758 | -0.2365 | 8.97903 |
September | 485.00000 | 23.05466 | 41.23642 | -0.7583 | 25.35431 |
October | 502.00000 | 21.49539 | 31.24998 | -0.3264 | 10.49248 |
November | 489.00000 | 20.43218 | 29.22322 | -0.6811 | 18.78653 |
December | 497.00000 | 19.98874 | 21.75945 | -0.9151 | 25.47547 |
Annual Sum or Average | 5943.00000 | 21.98678 | 35.52887 | -0.5386 | 17.27987 |
Minimum of Months | 454.00000 | 19.83676 | 19.09731 | -1.0013 | 8.71288 |
Maximum of Months | 514.00000 | 24.26222 | 54.81135 | -0.1294 | 29.06973 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 43531499.45 | 492.52 | 12-JAN-11:20 | 29.65 | 0.461326E+09 | 0.00 | 0.504858E+09 | 0.42 | 10.69 | 10-JAN-18:30 | 0.00 | 0.00 |
February | 30585793.22 | 672.24 | 24-FEB-10:40 | 20.51 | 0.324118E+09 | 0.00 | 0.354704E+09 | 0.32 | 10.68 | 21-FEB-21:30 | 0.00 | 0.00 |
March | 0.778953E+09 | 22061.89 | 25-MAR-15:00 | 46.00 | 0.824340E+10 | 0.00 | 0.902235E+10 | 0.66 | 10.69 | 16-MAR-06:50 | 0.00 | 0.00 |
April | 0.136684E+11 | 212874.70 | 18-APR-11:00 | 137.20 | 0.131595E+12 | 0.00 | 0.145263E+12 | 1.97 | 10.68 | 09-APR-12:32 | 0.00 | 0.00 |
May | 0.343848E+11 | 210251.93 | 30-MAY-14:00 | 325.24 | 0.327484E+12 | 0.00 | 0.361869E+12 | 4.52 | 10.65 | 20-MAY-14:50 | 0.00 | 0.00 |
June | 0.948101E+11 | 218642.11 | 09-JUN-11:40 | 418.66 | 0.859284E+12 | 0.00 | 0.954094E+12 | 5.66 | 10.65 | 03-JUN-05:50 | 0.00 | 0.00 |
July | 0.135997E+12 | 225685.26 | 05-JUL-17:00 | 570.28 | 0.119130E+13 | 0.00 | 0.132729E+13 | 7.36 | 10.63 | 24-JUL-06:30 | 0.00 | 0.00 |
August | 0.128759E+12 | 241253.19 | 04-AUG-07:20 | 551.26 | 0.112332E+13 | 0.00 | 0.125207E+13 | 7.14 | 10.64 | 06-AUG-19:23 | 0.00 | 0.00 |
September | 0.527144E+11 | 219713.52 | 06-SEP-09:40 | 292.36 | 0.484350E+12 | 0.00 | 0.537065E+12 | 4.07 | 10.68 | 30-SEP-06:40 | 0.00 | 0.00 |
October | 0.452789E+10 | 126213.86 | 20-OCT-15:00 | 90.82 | 0.463533E+11 | 0.00 | 0.508812E+11 | 1.29 | 10.68 | 19-OCT-06:00 | 0.00 | 0.00 |
November | 0.523990E+09 | 28481.39 | 03-NOV-14:20 | 36.26 | 0.554499E+10 | 0.00 | 0.606898E+10 | 0.53 | 10.69 | 21-NOV-21:20 | 0.00 | 0.00 |
December | 45287745.92 | 474.99 | 01-DEC-08:40 | 30.34 | 0.480010E+09 | 0.00 | 0.525298E+09 | 0.43 | 10.69 | 22-DEC-11:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.466284E+12 | 2548.59 | 0.417873E+13 | 0.00 | 0.464502E+13 | 2.88 | 0.00 | 0.00 | ||||
Minimum of Months | 30585793.22 | 474.99 | 20.51 | 0.324118E+09 | 0.00 | 0.354704E+09 | 0.32 | 10.63 | 0.00 | 0.00 | ||
Maximum of Months | 0.135997E+12 | 241253.19 | 570.28 | 0.119130E+13 | 0.00 | 0.132729E+13 | 7.36 | 10.69 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.173646E+10 | 113393.89 | 18-APR-09:55 | 5.67 | 0.159726E+11 | 0.00 | 0.177091E+11 | 0.07 | 9.42 | 18-APR-15:30 | 0.00 | 0.00 |
May | 0.441368E+10 | 103305.88 | 30-MAY-11:00 | 14.50 | 0.411402E+11 | 0.00 | 0.455539E+11 | 0.18 | 9.64 | 05-MAY-13:30 | 0.00 | 0.00 |
June | 0.205169E+11 | 185476.44 | 26-JUN-07:20 | 60.75 | 0.181416E+12 | 0.00 | 0.201933E+12 | 0.75 | 10.93 | 09-JUN-12:10 | 0.00 | 0.00 |
July | 0.308195E+11 | 175798.85 | 05-JUL-10:30 | 91.17 | 0.271849E+12 | 0.00 | 0.302668E+12 | 1.10 | 11.11 | 18-JUL-15:40 | 0.00 | 0.00 |
August | 0.320578E+11 | 241253.19 | 04-AUG-07:20 | 93.91 | 0.280383E+12 | 0.00 | 0.312441E+12 | 1.12 | 11.14 | 29-AUG-15:00 | 0.00 | 0.00 |
September | 0.725493E+10 | 175461.62 | 05-SEP-14:43 | 23.75 | 0.669627E+11 | 0.00 | 0.742176E+11 | 0.31 | 11.21 | 01-SEP-15:40 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.967992E+11 | 289.74 | 0.857724E+12 | 0.00 | 0.954523E+12 | 0.30 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.320578E+11 | 241253.19 | 93.91 | 0.280383E+12 | 0.00 | 0.312441E+12 | 1.12 | 11.21 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.250882E+09 | 744.00 | 2175.73 | 12-JAN-16:45 | 107315.98 | 12-JAN-16:50 | 18.51 | 18.33 | 16.24 |
February | 0.117618E+10 | 672.00 | 3177.31 | 10-FEB-10:50 | 145100.87 | 24-FEB-17:55 | 19.14 | 18.33 | 16.11 |
March | 0.466824E+10 | 744.00 | 49248.27 | 19-MAR-13:32 | 212129.59 | 14-MAR-12:55 | 19.89 | 18.34 | 16.00 |
April | 0.216991E+11 | 720.00 | 49248.27 | 10-APR-12:00 | 805160.09 | 16-APR-17:31 | 22.23 | 19.17 | 16.11 |
May | 0.314824E+11 | 744.00 | 49248.27 | 04-MAY-09:30 | 278581.60 | 30-MAY-14:10 | 19.84 | 19.12 | 16.25 |
June | 0.806230E+11 | 720.00 | 49248.27 | 07-JUN-10:00 | 690287.47 | 13-JUN-12:10 | 25.24 | 22.19 | 16.26 |
July | 0.110287E+12 | 744.00 | 49248.27 | 01-JUL-00:03 | 848109.82 | 26-JUL-19:00 | 30.96 | 23.93 | 16.26 |
August | 0.110660E+12 | 744.00 | 49248.27 | 01-AUG-00:03 | 891953.69 | 04-AUG-16:05 | 33.39 | 24.10 | 16.26 |
September | 0.498953E+11 | 720.00 | 49248.27 | 01-SEP-08:40 | 295254.52 | 11-SEP-10:50 | 21.24 | 20.24 | 16.25 |
October | 0.759205E+10 | 744.00 | 49248.27 | 01-OCT-11:42 | 225511.40 | 20-OCT-15:00 | 19.41 | 18.38 | 16.18 |
November | 0.343705E+10 | 720.00 | 6125.73 | 03-NOV-15:00 | 161913.45 | 16-NOV-08:45 | 19.74 | 18.33 | 16.12 |
December | 0.250628E+10 | 744.00 | 2889.22 | 06-DEC-14:10 | 235485.60 | 15-DEC-11:43 | 20.09 | 18.33 | 16.16 |
Annual Sum or Average | 0.424278E+12 | 8760.00 | 22.51 | 19.91 | 16.18 | ||||
Minimum of Months | 0.250882E+09 | 672.00 | 2175.73 | 107315.98 | 18.51 | 18.33 | 16.00 | ||
Maximum of Months | 0.110660E+12 | 744.00 | 49248.27 | 891953.69 | 33.39 | 24.10 | 16.26 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 284001.94 | 09-JAN-19:20 | 20.87 | 20.87 | 0.15 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 284021.55 | 27-FEB-09:00 | 20.91 | 20.91 | 0.13 |
March | 3273369.11 | 6.76 | 346.14 | 19-MAR-14:04 | 283931.39 | 16-MAR-20:20 | 20.95 | 20.94 | 1.69 |
April | 0.215552E+10 | 67.15 | 21633.58 | 15-APR-10:10 | 1397350.70 | 18-APR-08:50 | 21.26 | 21.07 | 9.81 |
May | 0.383983E+10 | 199.46 | 21633.58 | 04-MAY-13:10 | 1558694.74 | 04-MAY-16:00 | 21.60 | 21.15 | 25.95 |
June | 0.171338E+11 | 374.56 | 21633.58 | 08-JUN-15:40 | 1606419.88 | 23-JUN-16:00 | 23.06 | 21.85 | 40.58 |
July | 0.251761E+11 | 505.54 | 21633.58 | 01-JUL-07:50 | 1516464.86 | 18-JUL-15:30 | 23.76 | 22.13 | 53.20 |
August | 0.215306E+11 | 458.20 | 21633.58 | 01-AUG-07:05 | 1696551.74 | 04-AUG-07:20 | 23.52 | 21.97 | 49.97 |
September | 0.571892E+10 | 224.94 | 21633.58 | 01-SEP-14:50 | 1635857.30 | 05-SEP-14:00 | 22.00 | 21.31 | 26.61 |
October | 56599416.47 | 34.07 | 2587.73 | 20-OCT-15:00 | 1196018.25 | 20-OCT-15:00 | 21.05 | 20.98 | 5.37 |
November | 1898163.80 | 3.67 | 189.99 | 03-NOV-13:20 | 345078.75 | 03-NOV-14:20 | 20.92 | 20.90 | 1.03 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 284032.95 | 13-DEC-14:30 | 20.91 | 20.90 | 0.20 |
Annual Sum or Average | 0.756165E+11 | 1874.32 | 21.74 | 21.25 | 18.02 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 283931.39 | 20.87 | 20.87 | 0.13 | ||
Maximum of Months | 0.251761E+11 | 505.54 | 21633.58 | 1696551.74 | 23.76 | 22.13 | 53.20 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 20.87 | 20.87 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 20.91 | 20.91 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 20.95 | 20.95 | 0.00 |
April | 0.473775E+09 | 6.08 | 21633.58 | 15-APR-13:00 | 1061288.70 | 18-APR-09:00 | 21.26 | 21.23 | 0.61 |
May | 0.116821E+10 | 15.00 | 21633.58 | 05-MAY-13:00 | 1263023.01 | 05-MAY-15:40 | 21.60 | 21.54 | 1.45 |
June | 0.575345E+10 | 73.87 | 21633.58 | 09-JUN-09:40 | 1440233.82 | 26-JUN-07:50 | 23.06 | 22.72 | 6.93 |
July | 0.940628E+10 | 120.78 | 21633.58 | 03-JUL-07:40 | 1434053.44 | 05-JUL-10:30 | 23.76 | 23.20 | 10.56 |
August | 0.953760E+10 | 122.46 | 21633.58 | 01-AUG-07:35 | 1696551.74 | 04-AUG-07:20 | 23.52 | 22.94 | 10.66 |
September | 0.202040E+10 | 26.08 | 21633.58 | 05-SEP-14:05 | 1459770.03 | 01-SEP-15:50 | 22.00 | 21.88 | 2.54 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 21.05 | 21.05 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 20.92 | 20.92 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 20.91 | 20.91 | 0.00 |
Annual Sum or Average | 0.283597E+11 | 364.28 | 21.74 | 21.60 | 2.75 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.87 | 20.87 | 0.00 | ||
Maximum of Months | 0.953760E+10 | 122.46 | 21633.58 | 1696551.74 | 23.76 | 23.20 | 10.66 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.675730E+12 | 0.00 | 642.55 | 2198958.34 | 02-JAN-04:01 | 0.00 | 34.44 | 75.32 | 1.43 | 0.00 | 0.08 | 0.68 | 02-JAN-04:01 |
February | 0.466818E+12 | 0.00 | 512.65 | 2052412.88 | 02-FEB-07:02 | 0.00 | 31.57 | 69.54 | 1.14 | 0.00 | 0.06 | 0.64 | 02-FEB-07:02 |
March | 0.133138E+12 | 0.00 | 416.71 | 1801559.74 | 07-MAR-06:01 | 0.00 | 26.86 | 56.98 | 0.25 | 0.00 | 0.02 | 0.56 | 07-MAR-06:01 |
April | 0.407939E+11 | 0.00 | 239.70 | 1373515.24 | 03-APR-04:01 | 0.00 | 23.25 | 42.25 | 0.07 | 0.00 | 0.00 | 0.43 | 03-APR-04:01 |
May | 0.108863E+10 | 0.00 | 34.34 | 559398.25 | 02-MAY-05:03 | 0.00 | 23.05 | 25.76 | 0.00 | 0.00 | 0.00 | 0.17 | 02-MAY-05:03 |
June | 0.156780E+09 | 0.00 | 12.33 | 35775.05 | 02-JUN-05:02 | 0.00 | 21.72 | 22.75 | 0.00 | 0.00 | 0.00 | 0.01 | 02-JUN-05:02 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 21.61 | 21.61 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 93382.25 | 0.00 | 0.04 | 622.55 | 07-AUG-05:10 | 0.00 | 21.61 | 21.61 | 0.00 | 0.00 | 0.00 | 0.00 | 07-AUG-05:10 |
September | 0.503642E+10 | 0.00 | 77.09 | 1201868.44 | 30-SEP-05:02 | 0.00 | 21.53 | 27.94 | 0.01 | 0.00 | 0.00 | 0.37 | 30-SEP-05:02 |
October | 0.276683E+11 | 0.00 | 240.39 | 1459266.27 | 23-OCT-05:01 | 0.00 | 23.00 | 41.66 | 0.04 | 0.00 | 0.00 | 0.45 | 23-OCT-05:01 |
November | 0.180231E+12 | 0.00 | 438.80 | 1905170.97 | 29-NOV-06:01 | 0.00 | 27.51 | 59.91 | 0.37 | 0.00 | 0.02 | 0.59 | 29-NOV-06:01 |
December | 0.394311E+12 | 0.00 | 583.30 | 2002635.14 | 14-DEC-06:01 | 0.00 | 32.79 | 71.18 | 0.79 | 0.00 | 0.05 | 0.62 | 14-DEC-06:01 |
Annual Sum or Average | 0.192497E+13 | 0.00 | 3197.91 | 0.00 | 25.72 | 44.58 | 0.34 | 0.00 | 0.02 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.53 | 21.61 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.675730E+12 | 0.00 | 642.55 | 2198958.34 | 0.00 | 34.44 | 75.32 | 1.43 | 0.00 | 0.08 | 0.68 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 18.51 | 18.51 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 19.14 | 19.14 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 19.89 | 19.89 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 22.23 | 22.23 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 19.84 | 19.84 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 25.24 | 25.24 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 30.96 | 30.96 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 33.39 | 33.39 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 21.24 | 21.24 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 19.41 | 19.41 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 19.74 | 19.74 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 20.09 | 20.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 22.51 | 22.51 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.51 | 18.51 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.39 | 33.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 6487283.68 | 0.00 | 16.34 | 6487283.68 | 0.00 | 0.00 | 0.00 | 0.00 | 2079.91 | 10-JAN-13:10 | 2079.91 | 10-JAN-13:10 | 0.00 | 0.00 | 0.00 |
February | 5808442.14 | 0.00 | 14.60 | 5808442.14 | 0.00 | 0.00 | 0.00 | 0.00 | 7563.07 | 09-FEB-08:10 | 7563.07 | 09-FEB-08:10 | 0.00 | 0.00 | 0.00 |
March | 0.778716E+09 | 0.00 | 25.33 | 0.778716E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41069.00 | 19-MAR-14:52 | 41069.00 | 19-MAR-14:52 | 0.00 | 0.00 | 0.00 |
April | 0.147235E+11 | 0.00 | 101.92 | 0.134627E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 184935.20 | 18-APR-09:30 | 129902.30 | 18-APR-15:20 | 0.00 | 0.00 | 0.00 |
May | 0.327260E+11 | 0.00 | 254.90 | 0.287397E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 170639.88 | 30-MAY-10:50 | 123958.93 | 31-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.103584E+12 | 0.00 | 394.83 | 0.824451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 276501.45 | 27-JUN-07:50 | 141601.67 | 30-JUN-15:30 | 0.00 | 0.00 | 0.00 |
July | 0.155498E+12 | 0.00 | 547.12 | 0.110884E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 279501.38 | 07-JUL-12:10 | 144831.59 | 03-JUL-15:30 | 0.00 | 0.00 | 0.00 |
August | 0.148423E+12 | 0.00 | 532.80 | 0.106165E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 355032.53 | 04-AUG-07:10 | 155282.52 | 04-AUG-15:20 | 0.00 | 0.00 | 0.00 |
September | 0.491978E+11 | 0.00 | 255.66 | 0.466185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 200567.93 | 11-SEP-09:40 | 138053.75 | 05-SEP-13:50 | 0.00 | 0.00 | 0.00 |
October | 0.447415E+10 | 0.00 | 58.54 | 0.447415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88152.21 | 20-OCT-15:00 | 88152.21 | 20-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.477912E+09 | 0.00 | 22.95 | 0.477912E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30304.78 | 03-NOV-13:50 | 30304.78 | 03-NOV-13:50 | 0.00 | 0.00 | 0.00 |
December | 8440304.19 | 0.00 | 20.84 | 8440304.19 | 0.00 | 0.00 | 0.00 | 0.00 | 1012.77 | 01-DEC-08:40 | 1012.77 | 01-DEC-08:40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.509903E+12 | 0.00 | 2245.83 | 0.394067E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5808442.14 | 0.00 | 14.60 | 5808442.14 | 0.00 | 0.00 | 0.00 | 0.00 | 1012.77 | 1012.77 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.155498E+12 | 0.00 | 547.12 | 0.110884E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 355032.53 | 155282.52 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 15243042.34 | 0.00 | 15.66 | 15243042.34 | 0.00 | 0.00 | 0.00 | 0.00 | 11093.19 | 12-JAN-11:20 | 11093.19 | 12-JAN-11:20 | 0.00 | 0.00 | 0.00 |
February | 13470055.81 | 0.00 | 9.97 | 13470055.81 | 0.00 | 0.00 | 0.00 | 0.00 | 9535.81 | 24-FEB-10:40 | 9535.81 | 24-FEB-10:40 | 0.00 | 0.00 | 0.00 |
March | 0.561787E+10 | 0.00 | 29.97 | 0.561787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 192483.37 | 25-MAR-15:00 | 192483.37 | 25-MAR-15:00 | 0.00 | 0.00 | 0.00 |
April | 0.111140E+12 | 0.00 | 94.12 | 0.100925E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1395161.93 | 18-APR-09:30 | 1087669.74 | 18-APR-15:20 | 0.00 | 0.00 | 0.00 |
May | 0.276665E+12 | 0.00 | 251.95 | 0.244533E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1367978.95 | 30-MAY-11:00 | 1074974.82 | 31-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.797963E+12 | 0.00 | 363.38 | 0.648230E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2190835.01 | 26-JUN-04:12 | 1239355.03 | 25-JUN-17:01 | 0.00 | 0.00 | 0.00 |
July | 0.109346E+13 | 0.00 | 456.74 | 0.807491E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2024761.29 | 26-JUL-04:12 | 1237179.01 | 02-JUL-16:21 | 0.00 | 0.00 | 0.00 |
August | 0.104528E+13 | 0.00 | 437.15 | 0.781774E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 3264414.91 | 04-AUG-05:03 | 1229768.07 | 04-AUG-15:20 | 0.00 | 0.00 | 0.00 |
September | 0.416632E+12 | 0.00 | 248.74 | 0.394747E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1591795.94 | 11-SEP-05:03 | 1151203.13 | 07-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.345014E+11 | 0.00 | 58.01 | 0.345014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 744003.01 | 20-OCT-15:00 | 744003.01 | 20-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.401584E+10 | 0.00 | 23.65 | 0.401584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 246766.85 | 03-NOV-14:20 | 246766.85 | 03-NOV-14:20 | 0.00 | 0.00 | 0.00 |
December | 4438281.89 | 0.00 | 20.52 | 4438281.89 | 0.00 | 0.00 | 0.00 | 0.00 | 531.80 | 08-DEC-11:30 | 531.80 | 08-DEC-11:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.378530E+13 | 0.00 | 2009.86 | 0.302187E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4438281.89 | 0.00 | 9.97 | 4438281.89 | 0.00 | 0.00 | 0.00 | 0.00 | 531.80 | 531.80 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.109346E+13 | 0.00 | 456.74 | 0.807491E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 3264414.91 | 1239355.03 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 8229035.95 | 0.00 | 15.92 | 8229035.95 | 0.00 | 0.00 | 0.00 | 0.00 | 924.94 | 13-JAN-11:30 | 924.94 | 13-JAN-11:30 | 0.00 | 0.00 | 0.00 |
February | 9534763.10 | 0.00 | 9.37 | 9534763.10 | 0.00 | 0.00 | 0.00 | 0.00 | 968.59 | 08-FEB-10:30 | 968.59 | 08-FEB-10:30 | 0.00 | 0.00 | 0.00 |
March | 0.441598E+09 | 0.00 | 21.49 | 0.441598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18117.01 | 25-MAR-15:00 | 18117.01 | 25-MAR-15:00 | 0.00 | 0.00 | 0.00 |
April | 0.119688E+11 | 0.00 | 95.25 | 0.107918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 156961.04 | 18-APR-16:00 | 127295.74 | 18-APR-15:10 | 0.00 | 0.00 | 0.00 |
May | 0.292761E+11 | 0.00 | 247.25 | 0.259564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 142645.48 | 30-MAY-11:00 | 130553.36 | 31-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.881142E+11 | 0.00 | 358.30 | 0.718002E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 233466.46 | 26-JUN-04:12 | 156886.10 | 25-JUN-15:01 | 0.00 | 0.00 | 0.00 |
July | 0.119136E+12 | 0.00 | 450.78 | 0.875966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 230055.50 | 06-JUL-14:50 | 144683.15 | 02-JUL-16:31 | 0.00 | 0.00 | 0.00 |
August | 0.110097E+12 | 0.00 | 431.53 | 0.833159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 334085.89 | 04-AUG-05:03 | 151513.88 | 04-AUG-15:30 | 0.00 | 0.00 | 0.00 |
September | 0.431463E+11 | 0.00 | 243.78 | 0.409366E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 168324.52 | 11-SEP-10:00 | 137138.35 | 07-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.282526E+10 | 0.00 | 63.80 | 0.282526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71207.56 | 20-OCT-15:00 | 71207.56 | 20-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.242071E+09 | 0.00 | 19.78 | 0.242071E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19147.72 | 03-NOV-14:00 | 19147.72 | 03-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 4729351.70 | 0.00 | 14.48 | 4729351.70 | 0.00 | 0.00 | 0.00 | 0.00 | 669.82 | 15-DEC-11:30 | 669.82 | 15-DEC-11:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.405270E+12 | 0.00 | 1971.73 | 0.323929E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4729351.70 | 0.00 | 9.37 | 4729351.70 | 0.00 | 0.00 | 0.00 | 0.00 | 669.82 | 669.82 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.119136E+12 | 0.00 | 450.78 | 0.875966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 334085.89 | 156886.10 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 |
March | 0.847160E+09 | 0.00 | 19.92 | 0.847160E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24496.36 | 28-MAR-15:00 | 24496.36 | 28-MAR-15:00 | 0.00 | 0.00 | 0.00 |
April | 0.781182E+10 | 0.00 | 81.25 | 0.692383E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94049.12 | 18-APR-06:05 | 66639.98 | 18-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.197779E+11 | 0.00 | 220.05 | 0.159962E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 131836.77 | 30-MAY-10:00 | 76451.08 | 30-MAY-13:10 | 0.00 | 0.00 | 0.00 |
June | 0.367861E+11 | 0.00 | 202.41 | 0.283026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 167902.46 | 12-JUN-13:20 | 101093.04 | 28-JUN-11:00 | 0.00 | 0.00 | 0.00 |
July | 0.606401E+11 | 0.00 | 225.31 | 0.430158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 169527.09 | 17-JUL-08:50 | 99004.70 | 05-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.688467E+11 | 0.00 | 304.33 | 0.517056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 176306.43 | 28-AUG-09:55 | 92388.17 | 28-AUG-12:20 | 0.00 | 0.00 | 0.00 |
September | 0.309664E+11 | 0.00 | 198.19 | 0.287832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100557.35 | 05-SEP-13:57 | 93367.72 | 05-SEP-13:57 | 0.00 | 0.00 | 0.00 |
October | 0.323704E+10 | 0.00 | 59.24 | 0.322126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54680.61 | 20-OCT-15:00 | 54680.61 | 20-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.157464E+09 | 0.00 | 6.16 | 0.132750E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49203.95 | 08-NOV-07:11 | 35227.65 | 09-NOV-07:14 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.229071E+12 | 0.00 | 1316.85 | 0.178928E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.688467E+11 | 0.00 | 304.33 | 0.517056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 176306.43 | 101093.04 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.620845E+10 | 0.458685E+10 | 744.00 | 0.620843E+10 | 20575.35 | 0.00 | 0.02 | 22-JAN-11:00 | 0.01 | 18-JAN-01:00 | 2735.71 | 22-JAN-11:00 | 2735.71 | 22-JAN-11:00 | 4.61 | 18-JAN-02:00 | 2175.59 | 13-JAN-10:25 | 0.00 |
February | 0.101580E+11 | 0.550029E+10 | 672.00 | 0.100659E+11 | 92127299.80 | 0.00 | 0.02 | 21-FEB-13:10 | 0.02 | 24-FEB-16:00 | 5068.84 | 20-FEB-15:08 | 5068.84 | 20-FEB-15:08 | 122.87 | 02-FEB-05:52 | 3209.60 | 21-FEB-13:10 | 0.00 |
March | 0.146441E+11 | 0.729970E+10 | 728.63 | 0.142041E+11 | 0.439945E+09 | 0.00 | 0.23 | 19-MAR-16:00 | 0.01 | 19-MAR-11:37 | 90613.00 | 19-MAR-15:53 | 75233.30 | 25-MAR-15:00 | 21751.78 | 19-MAR-15:53 | 26181.90 | 19-MAR-16:00 | 0.00 |
April | 0.122971E+12 | 0.383722E+11 | 682.20 | 0.927757E+11 | 0.301954E+11 | 0.00 | 1.00 | 15-APR-10:40 | 0.01 | 14-APR-23:03 | 508882.29 | 18-APR-09:55 | 427764.08 | 15-APR-13:35 | 199297.18 | 18-APR-09:35 | 155396.30 | 16-APR-16:00 | 0.00 |
May | 0.172627E+11 | 0.844823E+10 | 446.47 | 0.146377E+11 | 0.262495E+10 | 0.00 | 0.40 | 30-MAY-14:10 | 0.01 | 14-MAY-00:10 | 177462.49 | 30-MAY-14:10 | 136455.15 | 31-MAY-15:00 | 49121.47 | 30-MAY-14:00 | 55396.44 | 30-MAY-14:10 | 0.00 |
June | 0.214489E+12 | 0.686326E+11 | 481.25 | 0.158650E+12 | 0.558390E+11 | 0.00 | 0.90 | 13-JUN-12:10 | 0.01 | 22-JUN-03:50 | 477978.80 | 13-JUN-12:10 | 229749.38 | 26-JUN-16:00 | 256688.35 | 13-JUN-12:00 | 133048.26 | 13-JUN-12:10 | 0.00 |
July | 0.636638E+12 | 0.178777E+12 | 674.55 | 0.367796E+12 | 0.268842E+12 | 0.00 | 1.00 | 02-JUL-09:51 | 0.01 | 01-JUL-05:08 | 570353.06 | 26-JUL-19:00 | 321972.91 | 02-JUL-10:11 | 384115.13 | 26-JUL-19:00 | 160981.15 | 26-JUL-15:10 | 0.00 |
August | 0.854548E+12 | 0.234005E+12 | 702.63 | 0.485523E+12 | 0.369025E+12 | 0.00 | 1.00 | 01-AUG-07:30 | 0.01 | 08-AUG-03:10 | 561143.31 | 04-AUG-13:00 | 415843.95 | 11-AUG-11:00 | 400087.73 | 04-AUG-07:00 | 173499.13 | 04-AUG-16:00 | 0.00 |
September | 0.464644E+11 | 0.186686E+11 | 514.52 | 0.425815E+11 | 0.388297E+10 | 0.00 | 0.42 | 11-SEP-10:50 | 0.01 | 13-SEP-18:40 | 195365.73 | 11-SEP-10:50 | 138549.38 | 06-SEP-15:00 | 63936.82 | 11-SEP-10:50 | 59473.07 | 11-SEP-10:50 | 0.00 |
October | 0.109204E+11 | 0.616479E+10 | 684.60 | 0.107468E+11 | 0.173593E+09 | 0.00 | 0.31 | 20-OCT-15:00 | 0.00 | 02-OCT-03:50 | 119828.70 | 20-OCT-15:00 | 119828.70 | 20-OCT-15:00 | 7777.97 | 21-OCT-15:00 | 39805.34 | 20-OCT-15:00 | 0.00 |
November | 0.112637E+11 | 0.628035E+10 | 638.40 | 0.111074E+11 | 0.156311E+09 | 0.00 | 0.03 | 16-NOV-17:15 | 0.01 | 02-NOV-21:17 | 5590.13 | 03-NOV-18:00 | 5335.34 | 04-NOV-16:13 | 443.06 | 20-NOV-11:20 | 3470.46 | 16-NOV-17:15 | 0.00 |
December | 0.146883E+11 | 0.764876E+10 | 744.00 | 0.146824E+11 | 5928756.03 | 0.00 | 0.03 | 07-DEC-15:10 | 0.03 | 05-DEC-05:12 | 5745.32 | 01-DEC-00:10 | 5561.03 | 03-DEC-08:55 | 248.39 | 01-DEC-00:10 | 3783.42 | 07-DEC-13:10 | 0.00 |
Annual Sum or Average | 0.196026E+13 | 0.584384E+12 | 7713.25 | 0.122898E+13 | 0.731278E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.620845E+10 | 0.458685E+10 | 446.47 | 0.620843E+10 | 20575.35 | 0.00 | 0.02 | 0.00 | 2735.71 | 2735.71 | 4.61 | 2175.59 | 0.00 | ||||||
Maximum of Months | 0.854548E+12 | 0.234005E+12 | 744.00 | 0.485523E+12 | 0.369025E+12 | 0.00 | 1.00 | 0.03 | 570353.06 | 427764.08 | 400087.73 | 173499.13 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.244246E+10 | 0.711397E+09 | 735.16 | 0.244233E+10 | 123785.41 | 0.00 | 0.27 | 29-JAN-16:42 | 0.00 | 06-JAN-07:02 | 2205.76 | 12-JAN-16:30 | 2205.76 | 12-JAN-16:30 | 8.05 | 02-JAN-07:03 | 572.37 | 29-JAN-16:42 | 0.00 |
February | 0.769805E+10 | 0.200425E+10 | 672.00 | 0.769805E+10 | -0.0 | 0.00 | 0.57 | 19-FEB-17:03 | 0.22 | 02-FEB-07:02 | 4654.48 | 20-FEB-17:00 | 4654.48 | 20-FEB-17:00 | 0.00 | 08-FEB-22:25 | 1196.74 | 19-FEB-17:03 | 0.00 |
March | 0.147120E+11 | 0.354706E+10 | 744.00 | 0.147110E+11 | 985513.00 | 0.00 | 0.82 | 31-MAR-24:00 | 0.53 | 06-MAR-07:03 | 7559.81 | 31-MAR-24:00 | 7559.81 | 31-MAR-24:00 | 75.98 | 29-MAR-16:00 | 1731.23 | 31-MAR-24:00 | 0.00 |
April | 0.199080E+11 | 0.462955E+10 | 720.00 | 0.198727E+11 | 35290234.34 | 0.00 | 0.99 | 16-APR-17:51 | 0.30 | 30-APR-24:00 | 9089.38 | 16-APR-17:52 | 9089.38 | 16-APR-17:52 | 355.30 | 18-APR-16:00 | 2910.01 | 15-APR-17:31 | 0.00 |
May | 0.585171E+10 | 0.149170E+10 | 744.00 | 0.573369E+10 | 0.118022E+09 | 0.00 | 0.46 | 31-MAY-23:10 | 0.17 | 02-MAY-06:05 | 4224.25 | 31-MAY-23:10 | 4147.19 | 31-MAY-24:00 | 285.68 | 12-MAY-15:50 | 1008.03 | 31-MAY-15:00 | 0.00 |
June | 0.111275E+11 | 0.293714E+10 | 720.00 | 0.108780E+11 | 0.249509E+09 | 0.00 | 0.65 | 30-JUN-23:23 | 0.39 | 03-JUN-06:40 | 6067.64 | 30-JUN-23:03 | 6035.96 | 30-JUN-23:37 | 473.96 | 13-JUN-15:00 | 1844.49 | 25-JUN-18:11 | 0.00 |
July | 0.168501E+11 | 0.448288E+10 | 744.00 | 0.164914E+11 | 0.358710E+09 | 0.00 | 0.82 | 31-JUL-23:52 | 0.61 | 22-JUL-06:50 | 7850.99 | 31-JUL-24:00 | 7849.18 | 31-JUL-23:52 | 607.62 | 26-JUL-19:00 | 2509.92 | 26-JUL-16:00 | 0.00 |
August | 0.218086E+11 | 0.564894E+10 | 744.00 | 0.214552E+11 | 0.353496E+09 | 0.00 | 1.00 | 04-AUG-12:20 | 0.29 | 31-AUG-24:00 | 9284.65 | 04-AUG-17:03 | 8995.67 | 05-AUG-18:40 | 621.46 | 04-AUG-17:03 | 3332.89 | 04-AUG-16:00 | 0.00 |
September | 0.573315E+10 | 0.152545E+10 | 720.00 | 0.565077E+10 | 82375497.72 | 0.00 | 0.45 | 30-SEP-24:00 | 0.14 | 30-SEP-06:55 | 3660.14 | 30-SEP-24:00 | 3660.14 | 30-SEP-24:00 | 269.70 | 11-SEP-11:00 | 1109.43 | 06-SEP-17:00 | 0.00 |
October | 0.102786E+11 | 0.250765E+10 | 744.00 | 0.102686E+11 | 10065059.80 | 0.00 | 0.64 | 31-OCT-24:00 | 0.36 | 23-OCT-06:10 | 5649.33 | 31-OCT-24:00 | 5649.33 | 31-OCT-24:00 | 182.98 | 02-OCT-15:30 | 1348.08 | 31-OCT-24:00 | 0.00 |
November | 0.141379E+11 | 0.339174E+10 | 720.00 | 0.141219E+11 | 15992283.53 | 0.00 | 0.76 | 05-NOV-16:13 | 0.51 | 28-NOV-07:03 | 6829.82 | 05-NOV-16:17 | 6829.82 | 05-NOV-16:17 | 162.22 | 08-NOV-12:00 | 1592.39 | 05-NOV-16:13 | 0.00 |
December | 0.189338E+11 | 0.454707E+10 | 744.00 | 0.189338E+11 | 0.00 | 0.00 | 0.91 | 25-DEC-16:03 | 0.72 | 11-DEC-07:03 | 8085.02 | 25-DEC-16:08 | 8085.02 | 25-DEC-16:08 | 0.00 | 08-DEC-23:07 | 1900.27 | 25-DEC-16:03 | 0.00 |
Annual Sum or Average | 0.149482E+12 | 0.374248E+11 | 8751.16 | 0.148257E+12 | 0.122457E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.244246E+10 | 0.711397E+09 | 672.00 | 0.244233E+10 | -0.0 | 0.00 | 0.27 | 0.00 | 2205.76 | 2205.76 | 0.00 | 572.37 | 0.00 | ||||||
Maximum of Months | 0.218086E+11 | 0.564894E+10 | 744.00 | 0.214552E+11 | 0.358710E+09 | 0.00 | 1.00 | 0.72 | 9284.65 | 9089.38 | 621.46 | 3332.89 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.268740E+10 | 0.862162E+09 | 197.92 | 0.268740E+10 | 0.00 | 0.00 | 0.25 | 12-JAN-16:40 | 0.00 | 01-JAN-00:03 | 17926.03 | 12-JAN-16:40 | 17926.03 | 12-JAN-16:40 | 0.00 | 11-JAN-14:00 | 5928.28 | 12-JAN-16:40 | 0.00 |
February | 0.507652E+11 | 0.136169E+11 | 672.00 | 0.507652E+11 | 0.00 | 0.00 | 0.49 | 24-FEB-17:00 | 0.07 | 02-FEB-07:02 | 41836.40 | 24-FEB-17:00 | 41836.40 | 24-FEB-17:00 | 0.00 | 07-FEB-18:40 | 10603.30 | 24-FEB-17:50 | 0.00 |
March | 0.121528E+12 | 0.298105E+11 | 744.00 | 0.121517E+12 | 10329714.51 | 0.00 | 0.77 | 31-MAR-23:30 | 0.37 | 06-MAR-07:03 | 67255.54 | 31-MAR-23:30 | 67255.54 | 31-MAR-23:30 | 759.19 | 29-MAR-16:00 | 15567.69 | 31-MAR-23:30 | 0.00 |
April | 0.178108E+12 | 0.418516E+11 | 720.00 | 0.177755E+12 | 0.353256E+09 | 0.00 | 0.97 | 16-APR-17:41 | 0.20 | 30-APR-24:00 | 85473.05 | 15-APR-18:10 | 85274.12 | 16-APR-17:52 | 3533.71 | 18-APR-16:00 | 27553.11 | 15-APR-17:31 | 0.00 |
May | 0.502056E+11 | 0.129303E+11 | 744.00 | 0.490424E+11 | 0.116324E+10 | 0.00 | 0.45 | 31-MAY-23:20 | 0.10 | 02-MAY-06:05 | 39979.68 | 31-MAY-23:10 | 39104.43 | 31-MAY-24:00 | 2833.98 | 12-MAY-16:00 | 9551.13 | 31-MAY-15:00 | 0.00 |
June | 0.103042E+12 | 0.273471E+11 | 720.00 | 0.100562E+12 | 0.247937E+10 | 0.00 | 0.65 | 30-JUN-23:13 | 0.34 | 03-JUN-07:00 | 58249.61 | 30-JUN-23:03 | 57954.65 | 30-JUN-23:53 | 4716.97 | 13-JUN-15:00 | 17433.37 | 25-JUN-18:31 | 0.00 |
July | 0.158799E+12 | 0.423648E+11 | 744.00 | 0.155229E+12 | 0.357058E+10 | 0.00 | 0.81 | 31-JUL-23:52 | 0.58 | 22-JUL-06:40 | 74668.15 | 31-JUL-24:00 | 74633.30 | 31-JUL-23:52 | 6034.78 | 26-JUL-19:00 | 23780.48 | 26-JUL-16:00 | 0.00 |
August | 0.205998E+12 | 0.535010E+11 | 744.00 | 0.202470E+12 | 0.352850E+10 | 0.00 | 1.00 | 04-AUG-14:30 | 0.24 | 31-AUG-24:00 | 87434.70 | 01-AUG-18:30 | 85365.99 | 29-AUG-17:40 | 6423.35 | 04-AUG-13:00 | 32055.04 | 04-AUG-16:00 | 0.00 |
September | 0.485000E+11 | 0.130911E+11 | 720.00 | 0.476904E+11 | 0.809592E+09 | 0.00 | 0.39 | 30-SEP-23:30 | 0.07 | 30-SEP-06:05 | 32450.42 | 04-SEP-17:43 | 32337.54 | 04-SEP-17:44 | 2685.69 | 11-SEP-11:00 | 10616.15 | 06-SEP-17:00 | 0.00 |
October | 0.839609E+11 | 0.208006E+11 | 744.00 | 0.838590E+11 | 0.101843E+09 | 0.00 | 0.58 | 31-OCT-23:50 | 0.27 | 23-OCT-06:10 | 48938.21 | 31-OCT-23:50 | 48938.21 | 31-OCT-23:50 | 1825.32 | 02-OCT-15:30 | 11824.12 | 31-OCT-23:50 | 0.00 |
November | 0.112906E+12 | 0.275796E+11 | 720.00 | 0.112745E+12 | 0.160585E+09 | 0.00 | 0.70 | 05-NOV-16:23 | 0.34 | 27-NOV-04:00 | 60663.74 | 03-NOV-16:00 | 60411.51 | 03-NOV-16:00 | 1619.19 | 08-NOV-12:00 | 14107.37 | 05-NOV-16:23 | 0.00 |
December | 0.149893E+12 | 0.368879E+11 | 744.00 | 0.149893E+12 | -0.0 | 0.00 | 0.85 | 07-DEC-16:10 | 0.54 | 11-DEC-07:03 | 72260.72 | 01-DEC-16:10 | 72260.72 | 01-DEC-16:10 | 0.00 | 13-DEC-10:20 | 17119.24 | 07-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.126639E+13 | 0.320644E+12 | 8213.92 | 0.125422E+13 | 0.121773E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.268740E+10 | 0.862162E+09 | 197.92 | 0.268740E+10 | -0.0 | 0.00 | 0.25 | 0.00 | 17926.03 | 17926.03 | 0.00 | 5928.28 | 0.00 | ||||||
Maximum of Months | 0.205998E+12 | 0.535010E+11 | 744.00 | 0.202470E+12 | 0.357058E+10 | 0.00 | 1.00 | 0.58 | 87434.70 | 85365.99 | 6423.35 | 32055.04 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.114407E+09 | 35494809.54 | 70.75 | 0.114407E+09 | -0.0 | 0.00 | 0.22 | 12-JAN-16:40 | 0.00 | 01-JAN-00:03 | 1689.73 | 12-JAN-16:40 | 1689.73 | 12-JAN-16:40 | 0.00 | 02-JAN-14:40 | 447.49 | 12-JAN-16:40 | 0.00 |
February | 0.343294E+10 | 0.936502E+09 | 637.63 | 0.343294E+10 | -0.0 | 0.00 | 0.48 | 24-FEB-17:00 | 0.00 | 01-FEB-00:03 | 4150.67 | 24-FEB-17:00 | 4150.67 | 24-FEB-17:00 | 0.00 | 13-FEB-05:50 | 993.15 | 24-FEB-17:00 | 0.00 |
March | 0.106748E+11 | 0.264682E+10 | 744.00 | 0.106738E+11 | 1001042.38 | 0.00 | 0.71 | 31-MAR-23:10 | 0.22 | 06-MAR-04:18 | 6234.00 | 31-MAR-23:10 | 6234.00 | 31-MAR-23:10 | 75.37 | 29-MAR-16:00 | 1459.55 | 31-MAR-23:10 | 0.00 |
April | 0.167503E+11 | 0.397396E+10 | 720.00 | 0.167151E+11 | 35172458.74 | 0.00 | 0.99 | 16-APR-17:41 | 0.16 | 30-APR-24:00 | 8798.37 | 16-APR-17:42 | 8798.37 | 16-APR-17:42 | 353.86 | 18-APR-16:00 | 2811.49 | 16-APR-17:01 | 0.00 |
May | 0.460808E+10 | 0.119767E+10 | 743.83 | 0.449243E+10 | 0.115648E+09 | 0.00 | 0.44 | 31-MAY-23:10 | 0.00 | 02-MAY-02:45 | 3982.38 | 31-MAY-23:10 | 3883.07 | 31-MAY-23:40 | 285.37 | 12-MAY-15:40 | 987.35 | 31-MAY-15:00 | 0.00 |
June | 0.101559E+11 | 0.271217E+10 | 720.00 | 0.990819E+10 | 0.247731E+09 | 0.00 | 0.65 | 25-JUN-18:31 | 0.28 | 03-JUN-06:20 | 5817.67 | 30-JUN-23:03 | 5782.97 | 30-JUN-23:53 | 473.20 | 13-JUN-15:00 | 1856.25 | 25-JUN-18:11 | 0.00 |
July | 0.158551E+11 | 0.424443E+10 | 744.00 | 0.154985E+11 | 0.356690E+09 | 0.00 | 0.82 | 02-JUL-18:41 | 0.54 | 12-JUL-06:05 | 7375.30 | 31-JUL-24:00 | 7371.07 | 31-JUL-23:52 | 603.05 | 26-JUL-19:00 | 2415.37 | 26-JUL-16:00 | 0.00 |
August | 0.205090E+11 | 0.534693E+10 | 744.00 | 0.201566E+11 | 0.352342E+09 | 0.00 | 1.00 | 04-AUG-14:30 | 0.23 | 31-AUG-24:00 | 8824.99 | 01-AUG-18:30 | 8607.67 | 29-AUG-17:40 | 642.86 | 04-AUG-13:00 | 3257.49 | 04-AUG-16:00 | 0.00 |
September | 0.431903E+10 | 0.118425E+10 | 715.64 | 0.423862E+10 | 80406276.34 | 0.00 | 0.39 | 06-SEP-17:30 | 0.00 | 27-SEP-06:15 | 3289.25 | 04-SEP-17:43 | 3277.76 | 04-SEP-17:44 | 271.11 | 11-SEP-11:00 | 1094.65 | 06-SEP-17:00 | 0.00 |
October | 0.691161E+10 | 0.173639E+10 | 744.00 | 0.690165E+10 | 9968935.50 | 0.00 | 0.51 | 31-OCT-23:20 | 0.14 | 16-OCT-06:05 | 4609.18 | 11-OCT-16:50 | 4557.15 | 11-OCT-16:50 | 183.68 | 02-OCT-15:30 | 1168.01 | 20-OCT-15:00 | 0.00 |
November | 0.947644E+10 | 0.234579E+10 | 720.00 | 0.946059E+10 | 15851704.82 | 0.00 | 0.65 | 03-NOV-16:00 | 0.19 | 27-NOV-00:30 | 6054.86 | 03-NOV-16:00 | 6029.71 | 03-NOV-16:00 | 161.71 | 08-NOV-12:00 | 1352.99 | 03-NOV-16:00 | 0.00 |
December | 0.131392E+11 | 0.328381E+10 | 744.00 | 0.131392E+11 | -0.0 | 0.00 | 0.81 | 07-DEC-16:10 | 0.40 | 11-DEC-03:40 | 7105.13 | 01-DEC-16:10 | 7105.13 | 01-DEC-16:10 | 0.00 | 29-DEC-15:00 | 1659.94 | 01-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.115947E+12 | 0.296442E+11 | 8047.85 | 0.114732E+12 | 0.121481E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.114407E+09 | 35494809.54 | 70.75 | 0.114407E+09 | -0.0 | 0.00 | 0.22 | 0.00 | 1689.73 | 1689.73 | 0.00 | 447.49 | 0.00 | ||||||
Maximum of Months | 0.205090E+11 | 0.534693E+10 | 744.00 | 0.201566E+11 | 0.356690E+09 | 0.00 | 1.00 | 0.54 | 8824.99 | 8798.37 | 642.86 | 3257.49 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 138.52 | 0.00 | 138.52 | 0.13 | 1171.20 | 0.00 | 0.00 | 0.00 |
February | 175.61 | 0.00 | 175.61 | 5.05 | 965.85 | 0.00 | 0.00 | 0.00 |
March | 263.19 | 0.00 | 263.19 | 64.49 | 641.96 | 0.00 | 0.00 | 0.00 |
April | 303.84 | 1.50 | 302.34 | 148.37 | 453.21 | 0.00 | 0.00 | 0.00 |
May | 396.21 | 14.89 | 381.32 | 331.26 | 245.20 | 0.00 | 0.00 | 0.00 |
June | 463.08 | 42.03 | 421.05 | 509.60 | 169.73 | 0.00 | 0.00 | 0.00 |
July | 434.29 | 29.05 | 405.25 | 498.66 | 145.88 | 0.00 | 0.00 | 0.00 |
August | 363.63 | 6.44 | 357.19 | 413.74 | 171.05 | 0.00 | 0.00 | 0.00 |
September | 278.80 | 0.07 | 278.73 | 245.09 | 304.30 | 0.00 | 0.00 | 0.00 |
October | 207.29 | 0.00 | 207.29 | 76.08 | 492.09 | 0.00 | 0.00 | 0.00 |
November | 145.00 | 0.00 | 145.00 | 14.85 | 753.88 | 0.00 | 0.00 | 0.00 |
December | 94.06 | 0.00 | 94.06 | 0.00 | 1068.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 272.47 | 7.86 | 264.61 | 193.41 | 546.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.06 | 0.00 | 94.06 | 0.00 | 145.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 463.08 | 42.03 | 421.05 | 509.60 | 1171.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 138.52 | 0.00 | 138.52 | 0.13 | 1171.20 | 0.00 | 0.00 | 0.00 |
February | 175.61 | 0.00 | 175.61 | 5.05 | 965.85 | 0.00 | 0.00 | 0.00 |
March | 263.19 | 0.00 | 263.19 | 64.49 | 641.96 | 0.00 | 0.00 | 0.00 |
April | 303.84 | 1.50 | 302.34 | 148.37 | 453.21 | 0.00 | 0.00 | 0.00 |
May | 396.21 | 14.89 | 381.32 | 331.26 | 245.20 | 0.00 | 0.00 | 0.00 |
June | 463.08 | 42.03 | 421.05 | 509.60 | 169.73 | 0.00 | 0.00 | 0.00 |
July | 434.29 | 29.05 | 405.25 | 498.66 | 145.88 | 0.00 | 0.00 | 0.00 |
August | 363.63 | 6.44 | 357.19 | 413.74 | 171.05 | 0.00 | 0.00 | 0.00 |
September | 278.80 | 0.07 | 278.73 | 245.09 | 304.30 | 0.00 | 0.00 | 0.00 |
October | 207.29 | 0.00 | 207.29 | 76.08 | 492.09 | 0.00 | 0.00 | 0.00 |
November | 145.00 | 0.00 | 145.00 | 14.85 | 753.88 | 0.00 | 0.00 | 0.00 |
December | 94.06 | 0.00 | 94.06 | 0.00 | 1068.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 272.47 | 7.86 | 264.61 | 193.41 | 546.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.06 | 0.00 | 94.06 | 0.00 | 145.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 463.08 | 42.03 | 421.05 | 509.60 | 1171.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 138.52 | 0.00 | 138.52 | 0.13 | 1171.20 | 0.00 | 0.00 | 0.00 |
February | 175.61 | 0.00 | 175.61 | 5.05 | 965.85 | 0.00 | 0.00 | 0.00 |
March | 263.19 | 0.00 | 263.19 | 64.49 | 641.96 | 0.00 | 0.00 | 0.00 |
April | 303.84 | 1.50 | 302.34 | 148.37 | 453.21 | 0.00 | 0.00 | 0.00 |
May | 396.21 | 14.89 | 381.32 | 331.26 | 245.20 | 0.00 | 0.00 | 0.00 |
June | 463.08 | 42.03 | 421.05 | 509.60 | 169.73 | 0.00 | 0.00 | 0.00 |
July | 434.29 | 29.05 | 405.25 | 498.66 | 145.88 | 0.00 | 0.00 | 0.00 |
August | 363.63 | 6.44 | 357.19 | 413.74 | 171.05 | 0.00 | 0.00 | 0.00 |
September | 278.80 | 0.07 | 278.73 | 245.09 | 304.30 | 0.00 | 0.00 | 0.00 |
October | 207.29 | 0.00 | 207.29 | 76.08 | 492.09 | 0.00 | 0.00 | 0.00 |
November | 145.00 | 0.00 | 145.00 | 14.85 | 753.88 | 0.00 | 0.00 | 0.00 |
December | 94.06 | 0.00 | 94.06 | 0.00 | 1068.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 272.47 | 7.86 | 264.61 | 193.41 | 546.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.06 | 0.00 | 94.06 | 0.00 | 145.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 463.08 | 42.03 | 421.05 | 509.60 | 1171.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 138.52 | 0.00 | 138.52 | 0.13 | 1171.20 | 0.00 | 0.00 | 0.00 |
February | 175.61 | 0.00 | 175.61 | 5.05 | 965.85 | 0.00 | 0.00 | 0.00 |
March | 263.19 | 0.00 | 263.19 | 64.49 | 641.96 | 0.00 | 0.00 | 0.00 |
April | 303.84 | 1.50 | 302.34 | 148.37 | 453.21 | 0.00 | 0.00 | 0.00 |
May | 396.21 | 14.89 | 381.32 | 331.26 | 245.20 | 0.00 | 0.00 | 0.00 |
June | 463.08 | 42.03 | 421.05 | 509.60 | 169.73 | 0.00 | 0.00 | 0.00 |
July | 434.29 | 29.05 | 405.25 | 498.66 | 145.88 | 0.00 | 0.00 | 0.00 |
August | 363.63 | 6.44 | 357.19 | 413.74 | 171.05 | 0.00 | 0.00 | 0.00 |
September | 278.80 | 0.07 | 278.73 | 245.09 | 304.30 | 0.00 | 0.00 | 0.00 |
October | 207.29 | 0.00 | 207.29 | 76.08 | 492.09 | 0.00 | 0.00 | 0.00 |
November | 145.00 | 0.00 | 145.00 | 14.85 | 753.88 | 0.00 | 0.00 | 0.00 |
December | 94.06 | 0.00 | 94.06 | 0.00 | 1068.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 272.47 | 7.86 | 264.61 | 193.41 | 546.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.06 | 0.00 | 94.06 | 0.00 | 145.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 463.08 | 42.03 | 421.05 | 509.60 | 1171.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 138.51 | 0.00 | 138.51 | 0.13 | 1171.15 | 0.00 | 0.00 | 0.00 |
February | 175.61 | 0.00 | 175.61 | 5.05 | 965.82 | 0.00 | 0.00 | 0.00 |
March | 263.18 | 0.00 | 263.18 | 64.48 | 641.93 | 0.00 | 0.00 | 0.00 |
April | 303.83 | 1.50 | 302.33 | 148.37 | 453.19 | 0.00 | 0.00 | 0.00 |
May | 396.19 | 14.89 | 381.30 | 331.24 | 245.19 | 0.00 | 0.00 | 0.00 |
June | 463.06 | 42.03 | 421.03 | 509.58 | 169.72 | 0.00 | 0.00 | 0.00 |
July | 434.28 | 29.05 | 405.23 | 498.64 | 145.87 | 0.00 | 0.00 | 0.00 |
August | 363.62 | 6.44 | 357.17 | 413.72 | 171.04 | 0.00 | 0.00 | 0.00 |
September | 278.79 | 0.07 | 278.72 | 245.08 | 304.29 | 0.00 | 0.00 | 0.00 |
October | 207.29 | 0.00 | 207.29 | 76.08 | 492.07 | 0.00 | 0.00 | 0.00 |
November | 145.00 | 0.00 | 145.00 | 14.84 | 753.85 | 0.00 | 0.00 | 0.00 |
December | 94.05 | 0.00 | 94.05 | 0.00 | 1068.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 272.46 | 7.86 | 264.60 | 193.40 | 546.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.05 | 0.00 | 94.05 | 0.00 | 145.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 463.06 | 42.03 | 421.03 | 509.58 | 1171.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 329.80 | 135.71 | 194.08 | 134.16 | 1173.39 | 0.00 | 0.00 | 0.00 |
February | 437.14 | 192.22 | 244.92 | 234.83 | 947.86 | 0.00 | 0.00 | 0.00 |
March | 593.94 | 235.75 | 358.19 | 428.41 | 640.07 | 0.00 | 0.00 | 0.00 |
April | 729.31 | 319.39 | 409.92 | 671.71 | 461.83 | 0.00 | 0.00 | 0.00 |
May | 915.95 | 400.23 | 515.72 | 1000.06 | 268.95 | 0.00 | 0.00 | 0.00 |
June | 1007.98 | 438.96 | 569.02 | 1227.34 | 184.38 | 0.00 | 0.00 | 0.00 |
July | 1018.81 | 470.10 | 548.71 | 1271.89 | 154.92 | 0.00 | 0.00 | 0.00 |
August | 858.84 | 370.26 | 488.57 | 1074.79 | 177.39 | 0.00 | 0.00 | 0.00 |
September | 766.00 | 361.98 | 404.03 | 879.61 | 318.23 | 0.00 | 0.00 | 0.00 |
October | 488.15 | 203.90 | 284.25 | 404.18 | 497.08 | 0.00 | 0.00 | 0.00 |
November | 288.01 | 93.55 | 194.46 | 136.24 | 758.64 | 0.00 | 0.00 | 0.00 |
December | 223.10 | 95.80 | 127.29 | 91.04 | 1080.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 639.08 | 276.88 | 362.20 | 631.68 | 553.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 223.10 | 93.55 | 127.29 | 91.04 | 154.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1018.81 | 470.10 | 569.02 | 1271.89 | 1173.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 329.80 | 135.71 | 194.08 | 134.16 | 1173.39 | 0.00 | 0.00 | 0.00 |
February | 437.14 | 192.22 | 244.92 | 234.83 | 947.86 | 0.00 | 0.00 | 0.00 |
March | 593.94 | 235.75 | 358.19 | 428.41 | 640.07 | 0.00 | 0.00 | 0.00 |
April | 729.31 | 319.39 | 409.92 | 671.71 | 461.83 | 0.00 | 0.00 | 0.00 |
May | 915.95 | 400.23 | 515.72 | 1000.06 | 268.95 | 0.00 | 0.00 | 0.00 |
June | 1007.98 | 438.96 | 569.02 | 1227.34 | 184.38 | 0.00 | 0.00 | 0.00 |
July | 1018.81 | 470.10 | 548.71 | 1271.89 | 154.92 | 0.00 | 0.00 | 0.00 |
August | 858.84 | 370.26 | 488.57 | 1074.79 | 177.39 | 0.00 | 0.00 | 0.00 |
September | 766.00 | 361.98 | 404.03 | 879.61 | 318.23 | 0.00 | 0.00 | 0.00 |
October | 488.15 | 203.90 | 284.25 | 404.18 | 497.08 | 0.00 | 0.00 | 0.00 |
November | 288.01 | 93.55 | 194.46 | 136.24 | 758.64 | 0.00 | 0.00 | 0.00 |
December | 223.10 | 95.80 | 127.29 | 91.04 | 1080.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 639.08 | 276.88 | 362.20 | 631.68 | 553.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 223.10 | 93.55 | 127.29 | 91.04 | 154.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1018.81 | 470.10 | 569.02 | 1271.89 | 1173.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 329.79 | 135.71 | 194.08 | 134.16 | 1173.36 | 0.00 | 0.00 | 0.00 |
February | 437.14 | 192.22 | 244.92 | 234.82 | 947.84 | 0.00 | 0.00 | 0.00 |
March | 593.93 | 235.75 | 358.18 | 428.41 | 640.06 | 0.00 | 0.00 | 0.00 |
April | 729.29 | 319.38 | 409.91 | 671.70 | 461.82 | 0.00 | 0.00 | 0.00 |
May | 915.93 | 400.22 | 515.71 | 1000.04 | 268.95 | 0.00 | 0.00 | 0.00 |
June | 1007.96 | 438.95 | 569.01 | 1227.32 | 184.38 | 0.00 | 0.00 | 0.00 |
July | 1018.79 | 470.09 | 548.70 | 1271.87 | 154.92 | 0.00 | 0.00 | 0.00 |
August | 858.82 | 370.26 | 488.56 | 1074.77 | 177.39 | 0.00 | 0.00 | 0.00 |
September | 765.99 | 361.97 | 404.02 | 879.59 | 318.22 | 0.00 | 0.00 | 0.00 |
October | 488.14 | 203.89 | 284.25 | 404.17 | 497.07 | 0.00 | 0.00 | 0.00 |
November | 288.01 | 93.55 | 194.46 | 136.24 | 758.63 | 0.00 | 0.00 | 0.00 |
December | 223.09 | 95.80 | 127.29 | 91.04 | 1080.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 639.07 | 276.88 | 362.19 | 631.67 | 553.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 223.09 | 93.55 | 127.29 | 91.04 | 154.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1018.79 | 470.09 | 569.01 | 1271.87 | 1173.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 861.44 | 589.51 | 271.94 | 737.92 | 944.51 | 0.00 | 0.00 | 0.00 |
February | 923.02 | 623.60 | 299.42 | 821.69 | 777.95 | 0.00 | 0.00 | 0.00 |
March | 803.24 | 422.96 | 380.28 | 749.16 | 577.57 | 0.00 | 0.00 | 0.00 |
April | 723.66 | 338.33 | 385.34 | 756.98 | 440.33 | 0.00 | 0.00 | 0.00 |
May | 599.53 | 162.54 | 436.99 | 669.86 | 262.51 | 0.00 | 0.00 | 0.00 |
June | 582.05 | 118.51 | 463.54 | 723.99 | 179.36 | 0.00 | 0.00 | 0.00 |
July | 616.14 | 155.25 | 460.89 | 800.97 | 153.13 | 0.00 | 0.00 | 0.00 |
August | 694.19 | 248.95 | 445.24 | 918.15 | 180.59 | 0.00 | 0.00 | 0.00 |
September | 841.21 | 443.25 | 397.96 | 1038.40 | 301.56 | 0.00 | 0.00 | 0.00 |
October | 878.40 | 551.07 | 327.33 | 941.20 | 451.07 | 0.00 | 0.00 | 0.00 |
November | 662.75 | 414.90 | 247.86 | 596.41 | 643.17 | 0.00 | 0.00 | 0.00 |
December | 706.73 | 535.34 | 171.39 | 647.76 | 895.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 739.96 | 382.31 | 357.64 | 783.28 | 482.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 582.05 | 118.51 | 171.39 | 596.41 | 153.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 923.02 | 623.60 | 463.54 | 1038.40 | 944.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 861.44 | 589.50 | 271.94 | 737.92 | 944.51 | 0.00 | 0.00 | 0.00 |
February | 923.02 | 623.60 | 299.42 | 821.69 | 777.95 | 0.00 | 0.00 | 0.00 |
March | 803.24 | 422.96 | 380.28 | 749.16 | 577.57 | 0.00 | 0.00 | 0.00 |
April | 723.66 | 338.33 | 385.34 | 756.98 | 440.33 | 0.00 | 0.00 | 0.00 |
May | 599.53 | 162.54 | 436.99 | 669.86 | 262.51 | 0.00 | 0.00 | 0.00 |
June | 582.05 | 118.51 | 463.54 | 723.99 | 179.36 | 0.00 | 0.00 | 0.00 |
July | 616.14 | 155.25 | 460.89 | 800.97 | 153.13 | 0.00 | 0.00 | 0.00 |
August | 694.19 | 248.95 | 445.24 | 918.15 | 180.59 | 0.00 | 0.00 | 0.00 |
September | 841.21 | 443.25 | 397.96 | 1038.40 | 301.56 | 0.00 | 0.00 | 0.00 |
October | 878.40 | 551.07 | 327.33 | 941.20 | 451.07 | 0.00 | 0.00 | 0.00 |
November | 662.75 | 414.89 | 247.86 | 596.41 | 643.17 | 0.00 | 0.00 | 0.00 |
December | 706.73 | 535.34 | 171.39 | 647.76 | 895.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 739.96 | 382.31 | 357.64 | 783.28 | 482.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 582.05 | 118.51 | 171.39 | 596.41 | 153.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 923.02 | 623.60 | 463.54 | 1038.40 | 944.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 861.44 | 589.51 | 271.94 | 737.92 | 944.51 | 0.00 | 0.00 | 0.00 |
February | 923.02 | 623.60 | 299.42 | 821.69 | 777.95 | 0.00 | 0.00 | 0.00 |
March | 803.24 | 422.96 | 380.28 | 749.16 | 577.57 | 0.00 | 0.00 | 0.00 |
April | 723.66 | 338.33 | 385.34 | 756.98 | 440.33 | 0.00 | 0.00 | 0.00 |
May | 599.53 | 162.54 | 436.99 | 669.86 | 262.51 | 0.00 | 0.00 | 0.00 |
June | 582.05 | 118.51 | 463.54 | 723.99 | 179.36 | 0.00 | 0.00 | 0.00 |
July | 616.14 | 155.25 | 460.89 | 800.97 | 153.13 | 0.00 | 0.00 | 0.00 |
August | 694.19 | 248.95 | 445.24 | 918.15 | 180.59 | 0.00 | 0.00 | 0.00 |
September | 841.21 | 443.25 | 397.96 | 1038.40 | 301.56 | 0.00 | 0.00 | 0.00 |
October | 878.40 | 551.07 | 327.33 | 941.20 | 451.07 | 0.00 | 0.00 | 0.00 |
November | 662.75 | 414.90 | 247.86 | 596.41 | 643.17 | 0.00 | 0.00 | 0.00 |
December | 706.73 | 535.34 | 171.39 | 647.76 | 895.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 739.96 | 382.31 | 357.64 | 783.28 | 482.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 582.05 | 118.51 | 171.39 | 596.41 | 153.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 923.02 | 623.60 | 463.54 | 1038.40 | 944.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 861.44 | 589.50 | 271.94 | 737.92 | 944.51 | 0.00 | 0.00 | 0.00 |
February | 923.02 | 623.60 | 299.42 | 821.69 | 777.95 | 0.00 | 0.00 | 0.00 |
March | 803.24 | 422.96 | 380.28 | 749.16 | 577.57 | 0.00 | 0.00 | 0.00 |
April | 723.66 | 338.33 | 385.34 | 756.98 | 440.33 | 0.00 | 0.00 | 0.00 |
May | 599.53 | 162.54 | 436.99 | 669.86 | 262.51 | 0.00 | 0.00 | 0.00 |
June | 582.05 | 118.51 | 463.54 | 723.99 | 179.36 | 0.00 | 0.00 | 0.00 |
July | 616.14 | 155.25 | 460.89 | 800.97 | 153.13 | 0.00 | 0.00 | 0.00 |
August | 694.19 | 248.95 | 445.24 | 918.15 | 180.59 | 0.00 | 0.00 | 0.00 |
September | 841.21 | 443.25 | 397.96 | 1038.40 | 301.56 | 0.00 | 0.00 | 0.00 |
October | 878.40 | 551.07 | 327.33 | 941.20 | 451.07 | 0.00 | 0.00 | 0.00 |
November | 662.75 | 414.89 | 247.86 | 596.41 | 643.17 | 0.00 | 0.00 | 0.00 |
December | 706.73 | 535.34 | 171.39 | 647.76 | 895.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 739.96 | 382.31 | 357.64 | 783.28 | 482.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 582.05 | 118.51 | 171.39 | 596.41 | 153.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 923.02 | 623.60 | 463.54 | 1038.40 | 944.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 861.41 | 589.48 | 271.93 | 737.89 | 944.47 | 0.00 | 0.00 | 0.00 |
February | 922.99 | 623.58 | 299.41 | 821.66 | 777.92 | 0.00 | 0.00 | 0.00 |
March | 803.20 | 422.94 | 380.26 | 749.13 | 577.55 | 0.00 | 0.00 | 0.00 |
April | 723.63 | 338.31 | 385.32 | 756.95 | 440.31 | 0.00 | 0.00 | 0.00 |
May | 599.51 | 162.53 | 436.97 | 669.83 | 262.50 | 0.00 | 0.00 | 0.00 |
June | 582.03 | 118.50 | 463.52 | 723.96 | 179.35 | 0.00 | 0.00 | 0.00 |
July | 616.12 | 155.25 | 460.87 | 800.94 | 153.12 | 0.00 | 0.00 | 0.00 |
August | 694.16 | 248.94 | 445.22 | 918.11 | 180.59 | 0.00 | 0.00 | 0.00 |
September | 841.18 | 443.23 | 397.95 | 1038.36 | 301.55 | 0.00 | 0.00 | 0.00 |
October | 878.37 | 551.05 | 327.31 | 941.16 | 451.05 | 0.00 | 0.00 | 0.00 |
November | 662.73 | 414.88 | 247.85 | 596.39 | 643.15 | 0.00 | 0.00 | 0.00 |
December | 706.70 | 535.32 | 171.38 | 647.73 | 895.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 739.93 | 382.30 | 357.63 | 783.25 | 482.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 582.03 | 118.50 | 171.38 | 596.39 | 153.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 922.99 | 623.58 | 463.52 | 1038.36 | 944.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 327.08 | 132.34 | 194.74 | 136.99 | 1233.10 | 0.00 | 0.00 | 0.00 |
February | 479.60 | 236.33 | 243.27 | 286.86 | 1032.02 | 0.00 | 0.00 | 0.00 |
March | 572.54 | 213.02 | 359.53 | 389.15 | 724.89 | 0.00 | 0.00 | 0.00 |
April | 835.17 | 412.98 | 422.19 | 805.22 | 553.07 | 0.00 | 0.00 | 0.00 |
May | 837.59 | 334.60 | 502.99 | 904.64 | 307.31 | 0.00 | 0.00 | 0.00 |
June | 982.81 | 425.93 | 556.88 | 1188.12 | 223.04 | 0.00 | 0.00 | 0.00 |
July | 1055.24 | 501.25 | 553.98 | 1312.67 | 196.67 | 0.00 | 0.00 | 0.00 |
August | 922.54 | 423.39 | 499.16 | 1147.43 | 232.32 | 0.00 | 0.00 | 0.00 |
September | 746.77 | 354.46 | 392.32 | 851.51 | 357.53 | 0.00 | 0.00 | 0.00 |
October | 520.38 | 231.36 | 289.03 | 445.21 | 566.18 | 0.00 | 0.00 | 0.00 |
November | 311.48 | 115.19 | 196.30 | 166.63 | 849.05 | 0.00 | 0.00 | 0.00 |
December | 239.55 | 112.93 | 126.62 | 114.05 | 1197.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 653.26 | 291.20 | 362.05 | 647.48 | 620.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 239.55 | 112.93 | 126.62 | 114.05 | 196.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1055.24 | 501.25 | 556.88 | 1312.67 | 1233.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 327.08 | 132.34 | 194.74 | 136.99 | 1233.10 | 0.00 | 0.00 | 0.00 |
February | 479.60 | 236.33 | 243.27 | 286.86 | 1032.02 | 0.00 | 0.00 | 0.00 |
March | 572.54 | 213.02 | 359.53 | 389.15 | 724.89 | 0.00 | 0.00 | 0.00 |
April | 835.17 | 412.98 | 422.19 | 805.22 | 553.07 | 0.00 | 0.00 | 0.00 |
May | 837.59 | 334.60 | 502.99 | 904.64 | 307.31 | 0.00 | 0.00 | 0.00 |
June | 982.81 | 425.93 | 556.88 | 1188.12 | 223.04 | 0.00 | 0.00 | 0.00 |
July | 1055.24 | 501.25 | 553.98 | 1312.67 | 196.67 | 0.00 | 0.00 | 0.00 |
August | 922.54 | 423.39 | 499.16 | 1147.43 | 232.32 | 0.00 | 0.00 | 0.00 |
September | 746.77 | 354.46 | 392.32 | 851.51 | 357.53 | 0.00 | 0.00 | 0.00 |
October | 520.38 | 231.36 | 289.03 | 445.21 | 566.18 | 0.00 | 0.00 | 0.00 |
November | 311.48 | 115.19 | 196.30 | 166.63 | 849.05 | 0.00 | 0.00 | 0.00 |
December | 239.55 | 112.93 | 126.62 | 114.05 | 1197.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 653.26 | 291.20 | 362.05 | 647.48 | 620.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 239.55 | 112.93 | 126.62 | 114.05 | 196.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1055.24 | 501.25 | 556.88 | 1312.67 | 1233.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 327.07 | 132.34 | 194.73 | 136.99 | 1233.08 | 0.00 | 0.00 | 0.00 |
February | 479.59 | 236.33 | 243.26 | 286.86 | 1032.00 | 0.00 | 0.00 | 0.00 |
March | 572.53 | 213.01 | 359.52 | 389.14 | 724.87 | 0.00 | 0.00 | 0.00 |
April | 835.16 | 412.97 | 422.19 | 805.21 | 553.06 | 0.00 | 0.00 | 0.00 |
May | 837.57 | 334.59 | 502.98 | 904.63 | 307.30 | 0.00 | 0.00 | 0.00 |
June | 982.79 | 425.92 | 556.87 | 1188.10 | 223.04 | 0.00 | 0.00 | 0.00 |
July | 1055.22 | 501.25 | 553.97 | 1312.64 | 196.66 | 0.00 | 0.00 | 0.00 |
August | 922.53 | 423.38 | 499.15 | 1147.41 | 232.31 | 0.00 | 0.00 | 0.00 |
September | 746.76 | 354.45 | 392.31 | 851.49 | 357.52 | 0.00 | 0.00 | 0.00 |
October | 520.37 | 231.35 | 289.02 | 445.20 | 566.17 | 0.00 | 0.00 | 0.00 |
November | 311.48 | 115.18 | 196.29 | 166.63 | 849.04 | 0.00 | 0.00 | 0.00 |
December | 239.54 | 112.92 | 126.62 | 114.05 | 1197.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 653.24 | 291.20 | 362.05 | 647.47 | 620.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 239.54 | 112.92 | 126.62 | 114.05 | 196.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1055.22 | 501.25 | 556.87 | 1312.64 | 1233.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 692.58 | 0.00 | 692.58 | 2.62 | 5516.40 | 0.00 | 0.00 | 0.00 |
February | 878.06 | 0.00 | 878.06 | 46.80 | 4488.09 | 0.00 | 0.00 | 0.00 |
March | 1315.95 | 0.00 | 1315.95 | 383.53 | 2915.13 | 0.00 | 0.00 | 0.00 |
April | 1519.17 | 7.48 | 1511.68 | 810.09 | 2021.30 | 0.00 | 0.00 | 0.00 |
May | 1981.02 | 74.46 | 1906.56 | 1685.83 | 1162.76 | 0.00 | 0.00 | 0.00 |
June | 2315.36 | 210.15 | 2105.21 | 2569.48 | 801.52 | 0.00 | 0.00 | 0.00 |
July | 2171.45 | 145.25 | 2026.20 | 2528.58 | 686.62 | 0.00 | 0.00 | 0.00 |
August | 1818.14 | 32.22 | 1785.92 | 2100.18 | 812.85 | 0.00 | 0.00 | 0.00 |
September | 1393.99 | 0.35 | 1393.65 | 1263.15 | 1418.96 | 0.00 | 0.00 | 0.00 |
October | 1036.46 | 0.00 | 1036.46 | 453.11 | 2201.99 | 0.00 | 0.00 | 0.00 |
November | 725.01 | 0.00 | 725.01 | 104.79 | 3387.45 | 0.00 | 0.00 | 0.00 |
December | 470.29 | 0.00 | 470.29 | 0.31 | 4901.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1362.34 | 39.31 | 1323.03 | 1001.41 | 2516.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 470.29 | 0.00 | 470.29 | 0.31 | 686.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2315.36 | 210.15 | 2105.21 | 2569.48 | 5516.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 989.38 | 407.13 | 582.25 | 417.74 | 3327.03 | 0.00 | 0.00 | 0.00 |
February | 1311.42 | 576.66 | 734.76 | 727.36 | 2671.15 | 0.00 | 0.00 | 0.00 |
March | 1781.81 | 707.26 | 1074.56 | 1311.83 | 1795.37 | 0.00 | 0.00 | 0.00 |
April | 2187.90 | 958.15 | 1229.75 | 2026.46 | 1290.59 | 0.00 | 0.00 | 0.00 |
May | 2747.82 | 1200.67 | 1547.15 | 2985.07 | 777.02 | 0.00 | 0.00 | 0.00 |
June | 3023.91 | 1316.86 | 1707.04 | 3670.39 | 533.25 | 0.00 | 0.00 | 0.00 |
July | 3056.39 | 1410.29 | 1646.10 | 3804.46 | 455.94 | 0.00 | 0.00 | 0.00 |
August | 2576.48 | 1110.78 | 1465.70 | 3209.35 | 537.52 | 0.00 | 0.00 | 0.00 |
September | 2297.99 | 1085.92 | 1212.07 | 2639.47 | 906.89 | 0.00 | 0.00 | 0.00 |
October | 1464.44 | 611.68 | 852.75 | 1248.56 | 1376.11 | 0.00 | 0.00 | 0.00 |
November | 864.03 | 280.65 | 583.38 | 437.26 | 2097.96 | 0.00 | 0.00 | 0.00 |
December | 669.29 | 287.41 | 381.88 | 289.34 | 3027.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1917.23 | 830.65 | 1086.58 | 1903.64 | 1561.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 669.29 | 280.65 | 381.88 | 289.34 | 455.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3056.39 | 1410.29 | 1707.04 | 3804.46 | 3327.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4307.17 | 2947.49 | 1359.68 | 3687.55 | 4571.55 | 0.00 | 0.00 | 0.00 |
February | 4615.06 | 3117.97 | 1497.09 | 4096.71 | 3772.53 | 0.00 | 0.00 | 0.00 |
March | 4016.13 | 2114.76 | 1901.37 | 3736.40 | 2780.88 | 0.00 | 0.00 | 0.00 |
April | 3618.27 | 1691.61 | 1926.66 | 3778.40 | 2094.10 | 0.00 | 0.00 | 0.00 |
May | 2997.61 | 812.69 | 2184.92 | 3333.08 | 1278.68 | 0.00 | 0.00 | 0.00 |
June | 2910.23 | 592.54 | 2317.69 | 3619.66 | 860.94 | 0.00 | 0.00 | 0.00 |
July | 3080.68 | 776.25 | 2304.43 | 4010.40 | 737.33 | 0.00 | 0.00 | 0.00 |
August | 3470.90 | 1244.75 | 2226.15 | 4579.29 | 886.39 | 0.00 | 0.00 | 0.00 |
September | 4206.00 | 2216.22 | 1989.78 | 5166.23 | 1472.12 | 0.00 | 0.00 | 0.00 |
October | 4391.95 | 2755.33 | 1636.62 | 4687.27 | 2184.47 | 0.00 | 0.00 | 0.00 |
November | 3313.72 | 2074.45 | 1239.27 | 2988.12 | 3082.43 | 0.00 | 0.00 | 0.00 |
December | 3533.60 | 2676.66 | 856.94 | 3249.56 | 4286.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3699.75 | 1911.55 | 1788.20 | 3909.78 | 2327.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2910.23 | 592.54 | 856.94 | 2988.12 | 737.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4615.06 | 3117.97 | 2317.69 | 5166.23 | 4571.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 981.22 | 397.01 | 584.21 | 428.87 | 3447.01 | 0.00 | 0.00 | 0.00 |
February | 1438.79 | 708.99 | 729.80 | 895.09 | 2826.19 | 0.00 | 0.00 | 0.00 |
March | 1717.61 | 639.05 | 1078.57 | 1236.27 | 1898.38 | 0.00 | 0.00 | 0.00 |
April | 2505.49 | 1238.92 | 1266.57 | 2474.39 | 1404.55 | 0.00 | 0.00 | 0.00 |
May | 2512.74 | 1003.78 | 1508.96 | 2740.79 | 853.61 | 0.00 | 0.00 | 0.00 |
June | 2948.40 | 1277.76 | 1670.63 | 3592.67 | 602.34 | 0.00 | 0.00 | 0.00 |
July | 3165.68 | 1503.75 | 1661.93 | 3971.03 | 538.79 | 0.00 | 0.00 | 0.00 |
August | 2767.60 | 1270.15 | 1497.45 | 3486.11 | 618.69 | 0.00 | 0.00 | 0.00 |
September | 2240.30 | 1063.36 | 1176.94 | 2584.70 | 984.46 | 0.00 | 0.00 | 0.00 |
October | 1561.13 | 694.06 | 867.07 | 1402.60 | 1482.06 | 0.00 | 0.00 | 0.00 |
November | 934.44 | 345.56 | 588.88 | 549.48 | 2195.59 | 0.00 | 0.00 | 0.00 |
December | 718.63 | 338.77 | 379.86 | 372.75 | 3150.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1959.75 | 873.60 | 1086.15 | 1983.26 | 1661.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 718.63 | 338.77 | 379.86 | 372.75 | 538.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3165.68 | 1503.75 | 1670.63 | 3971.03 | 3447.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 692.58 | 0.00 | 692.58 | 3.27 | 5413.57 | 0.00 | 0.00 | 0.00 |
February | 878.06 | 0.00 | 878.06 | 56.74 | 4333.83 | 0.00 | 0.00 | 0.00 |
March | 1315.95 | 0.00 | 1315.95 | 414.45 | 2767.03 | 0.00 | 0.00 | 0.00 |
April | 1519.17 | 7.48 | 1511.68 | 842.57 | 1884.23 | 0.00 | 0.00 | 0.00 |
May | 1981.02 | 74.46 | 1906.56 | 1710.49 | 1113.41 | 0.00 | 0.00 | 0.00 |
June | 2315.36 | 210.15 | 2105.21 | 2568.62 | 777.35 | 0.00 | 0.00 | 0.00 |
July | 2171.45 | 145.25 | 2026.20 | 2516.94 | 678.52 | 0.00 | 0.00 | 0.00 |
August | 1818.14 | 32.22 | 1785.92 | 2097.15 | 796.37 | 0.00 | 0.00 | 0.00 |
September | 1393.99 | 0.35 | 1393.65 | 1288.64 | 1340.82 | 0.00 | 0.00 | 0.00 |
October | 1036.46 | 0.00 | 1036.46 | 513.61 | 2011.43 | 0.00 | 0.00 | 0.00 |
November | 725.01 | 0.00 | 725.01 | 129.98 | 3186.17 | 0.00 | 0.00 | 0.00 |
December | 470.29 | 0.00 | 470.29 | 1.55 | 4750.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1362.34 | 39.31 | 1323.03 | 1017.71 | 2412.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 470.29 | 0.00 | 470.29 | 1.55 | 678.52 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2315.36 | 210.15 | 2105.21 | 2568.62 | 5413.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 989.38 | 407.13 | 582.25 | 423.01 | 3267.48 | 0.00 | 0.00 | 0.00 |
February | 1311.42 | 576.66 | 734.76 | 743.64 | 2575.76 | 0.00 | 0.00 | 0.00 |
March | 1781.81 | 707.26 | 1074.56 | 1338.25 | 1706.86 | 0.00 | 0.00 | 0.00 |
April | 2187.90 | 958.15 | 1229.75 | 2042.48 | 1217.83 | 0.00 | 0.00 | 0.00 |
May | 2747.82 | 1200.67 | 1547.15 | 2989.40 | 751.95 | 0.00 | 0.00 | 0.00 |
June | 3023.91 | 1316.86 | 1707.04 | 3663.58 | 521.34 | 0.00 | 0.00 | 0.00 |
July | 3056.39 | 1410.29 | 1646.10 | 3791.30 | 453.99 | 0.00 | 0.00 | 0.00 |
August | 2576.48 | 1110.78 | 1465.70 | 3201.64 | 531.09 | 0.00 | 0.00 | 0.00 |
September | 2297.99 | 1085.92 | 1212.07 | 2647.45 | 869.65 | 0.00 | 0.00 | 0.00 |
October | 1464.44 | 611.68 | 852.75 | 1293.20 | 1271.40 | 0.00 | 0.00 | 0.00 |
November | 864.03 | 280.65 | 583.38 | 462.64 | 1980.34 | 0.00 | 0.00 | 0.00 |
December | 669.29 | 287.41 | 381.88 | 297.55 | 2933.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1917.23 | 830.65 | 1086.58 | 1914.17 | 1501.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 669.29 | 280.65 | 381.88 | 297.55 | 453.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3056.39 | 1410.29 | 1707.04 | 3791.30 | 3267.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4307.17 | 2947.49 | 1359.68 | 3709.23 | 4459.34 | 0.00 | 0.00 | 0.00 |
February | 4615.06 | 3117.97 | 1497.09 | 4133.93 | 3611.06 | 0.00 | 0.00 | 0.00 |
March | 4016.13 | 2114.76 | 1901.37 | 3773.93 | 2635.17 | 0.00 | 0.00 | 0.00 |
April | 3618.27 | 1691.61 | 1926.66 | 3800.41 | 1964.63 | 0.00 | 0.00 | 0.00 |
May | 2997.61 | 812.69 | 2184.92 | 3343.33 | 1227.06 | 0.00 | 0.00 | 0.00 |
June | 2910.23 | 592.54 | 2317.69 | 3614.82 | 835.02 | 0.00 | 0.00 | 0.00 |
July | 3080.68 | 776.25 | 2304.43 | 3996.06 | 728.42 | 0.00 | 0.00 | 0.00 |
August | 3470.90 | 1244.75 | 2226.15 | 4568.45 | 869.87 | 0.00 | 0.00 | 0.00 |
September | 4206.00 | 2216.22 | 1989.78 | 5177.96 | 1405.20 | 0.00 | 0.00 | 0.00 |
October | 4391.95 | 2755.33 | 1636.62 | 4742.21 | 2018.15 | 0.00 | 0.00 | 0.00 |
November | 3313.72 | 2074.45 | 1239.27 | 3041.56 | 2891.60 | 0.00 | 0.00 | 0.00 |
December | 3533.60 | 2676.66 | 856.94 | 3277.17 | 4128.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3699.75 | 1911.55 | 1788.20 | 3930.18 | 2224.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2910.23 | 592.54 | 856.94 | 3041.56 | 728.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4615.06 | 3117.97 | 2317.69 | 5177.96 | 4459.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 981.22 | 397.01 | 584.21 | 431.77 | 3381.01 | 0.00 | 0.00 | 0.00 |
February | 1438.79 | 708.99 | 729.80 | 903.42 | 2734.10 | 0.00 | 0.00 | 0.00 |
March | 1717.61 | 639.05 | 1078.57 | 1250.82 | 1815.47 | 0.00 | 0.00 | 0.00 |
April | 2505.49 | 1238.92 | 1266.57 | 2483.45 | 1329.53 | 0.00 | 0.00 | 0.00 |
May | 2512.74 | 1003.78 | 1508.96 | 2747.00 | 822.94 | 0.00 | 0.00 | 0.00 |
June | 2948.40 | 1277.76 | 1670.63 | 3587.01 | 587.48 | 0.00 | 0.00 | 0.00 |
July | 3165.68 | 1503.75 | 1661.93 | 3959.81 | 533.12 | 0.00 | 0.00 | 0.00 |
August | 2767.60 | 1270.15 | 1497.45 | 3478.93 | 608.90 | 0.00 | 0.00 | 0.00 |
September | 2240.30 | 1063.36 | 1176.94 | 2593.38 | 944.62 | 0.00 | 0.00 | 0.00 |
October | 1561.13 | 694.06 | 867.07 | 1429.40 | 1384.56 | 0.00 | 0.00 | 0.00 |
November | 934.44 | 345.56 | 588.88 | 566.98 | 2084.80 | 0.00 | 0.00 | 0.00 |
December | 718.63 | 338.77 | 379.86 | 377.30 | 3058.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1959.75 | 873.60 | 1086.15 | 1989.44 | 1601.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 718.63 | 338.77 | 379.86 | 377.30 | 533.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3165.68 | 1503.75 | 1670.63 | 3959.81 | 3381.01 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.371008E+09 | 0.00 | 0.371008E+09 | 353644.22 | 0.313694E+10 |
February | 0.424847E+09 | 0.00 | 0.424847E+09 | 12206321.12 | 0.233660E+10 |
March | 0.704934E+09 | 0.00 | 0.704934E+09 | 0.172722E+09 | 0.171943E+10 |
April | 0.787546E+09 | 3880204.98 | 0.783666E+09 | 0.384579E+09 | 0.117472E+10 |
May | 0.106121E+10 | 39888353.73 | 0.102132E+10 | 0.887239E+09 | 0.656741E+09 |
June | 0.120030E+10 | 0.108943E+09 | 0.109136E+10 | 0.132089E+10 | 0.439939E+09 |
July | 0.116322E+10 | 77806368.86 | 0.108541E+10 | 0.133561E+10 | 0.390720E+09 |
August | 0.973952E+09 | 17261160.59 | 0.956691E+09 | 0.110816E+10 | 0.458132E+09 |
September | 0.722654E+09 | 179185.83 | 0.722474E+09 | 0.635277E+09 | 0.788758E+09 |
October | 0.555217E+09 | 0.00 | 0.555217E+09 | 0.203783E+09 | 0.131802E+10 |
November | 0.375852E+09 | 0.00 | 0.375852E+09 | 38479263.48 | 0.195405E+10 |
December | 0.251926E+09 | 0.00 | 0.251926E+09 | 41.09 | 0.286158E+10 |
Annual Sum or Average | 0.859266E+10 | 0.247958E+09 | 0.834470E+10 | 0.609931E+10 | 0.172356E+11 |
Minimum of Months | 0.251926E+09 | 0.00 | 0.251926E+09 | 41.09 | 0.390720E+09 |
Maximum of Months | 0.120030E+10 | 0.108943E+09 | 0.109136E+10 | 0.133561E+10 | 0.313694E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.371008E+09 | 0.00 | 0.371008E+09 | 353638.63 | 0.313694E+10 |
February | 0.424846E+09 | 0.00 | 0.424846E+09 | 12206256.65 | 0.233660E+10 |
March | 0.704933E+09 | 0.00 | 0.704933E+09 | 0.172721E+09 | 0.171943E+10 |
April | 0.787546E+09 | 3880200.32 | 0.783666E+09 | 0.384578E+09 | 0.117472E+10 |
May | 0.106121E+10 | 39888305.87 | 0.102132E+10 | 0.887238E+09 | 0.656741E+09 |
June | 0.120030E+10 | 0.108943E+09 | 0.109136E+10 | 0.132089E+10 | 0.439939E+09 |
July | 0.116321E+10 | 77806275.50 | 0.108541E+10 | 0.133561E+10 | 0.390720E+09 |
August | 0.973952E+09 | 17261139.88 | 0.956691E+09 | 0.110816E+10 | 0.458132E+09 |
September | 0.722653E+09 | 179185.62 | 0.722474E+09 | 0.635276E+09 | 0.788758E+09 |
October | 0.555216E+09 | 0.00 | 0.555216E+09 | 0.203783E+09 | 0.131802E+10 |
November | 0.375851E+09 | 0.00 | 0.375851E+09 | 38479153.68 | 0.195405E+10 |
December | 0.251926E+09 | 0.00 | 0.251926E+09 | 40.81 | 0.286158E+10 |
Annual Sum or Average | 0.859265E+10 | 0.247958E+09 | 0.834469E+10 | 0.609930E+10 | 0.172356E+11 |
Minimum of Months | 0.251926E+09 | 0.00 | 0.251926E+09 | 40.81 | 0.390720E+09 |
Maximum of Months | 0.120030E+10 | 0.108943E+09 | 0.109136E+10 | 0.133561E+10 | 0.313694E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.371008E+09 | 0.00 | 0.371008E+09 | 353644.22 | 0.313694E+10 |
February | 0.424847E+09 | 0.00 | 0.424847E+09 | 12206321.12 | 0.233660E+10 |
March | 0.704934E+09 | 0.00 | 0.704934E+09 | 0.172722E+09 | 0.171943E+10 |
April | 0.787546E+09 | 3880204.98 | 0.783666E+09 | 0.384579E+09 | 0.117472E+10 |
May | 0.106121E+10 | 39888353.73 | 0.102132E+10 | 0.887239E+09 | 0.656741E+09 |
June | 0.120030E+10 | 0.108943E+09 | 0.109136E+10 | 0.132089E+10 | 0.439939E+09 |
July | 0.116322E+10 | 77806368.86 | 0.108541E+10 | 0.133561E+10 | 0.390720E+09 |
August | 0.973952E+09 | 17261160.59 | 0.956691E+09 | 0.110816E+10 | 0.458132E+09 |
September | 0.722654E+09 | 179185.83 | 0.722474E+09 | 0.635277E+09 | 0.788758E+09 |
October | 0.555217E+09 | 0.00 | 0.555217E+09 | 0.203783E+09 | 0.131802E+10 |
November | 0.375852E+09 | 0.00 | 0.375852E+09 | 38479263.48 | 0.195405E+10 |
December | 0.251926E+09 | 0.00 | 0.251926E+09 | 41.09 | 0.286158E+10 |
Annual Sum or Average | 0.859266E+10 | 0.247958E+09 | 0.834470E+10 | 0.609931E+10 | 0.172356E+11 |
Minimum of Months | 0.251926E+09 | 0.00 | 0.251926E+09 | 41.09 | 0.390720E+09 |
Maximum of Months | 0.120030E+10 | 0.108943E+09 | 0.109136E+10 | 0.133561E+10 | 0.313694E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.371008E+09 | 0.00 | 0.371008E+09 | 353638.63 | 0.313694E+10 |
February | 0.424846E+09 | 0.00 | 0.424846E+09 | 12206256.65 | 0.233660E+10 |
March | 0.704933E+09 | 0.00 | 0.704933E+09 | 0.172721E+09 | 0.171943E+10 |
April | 0.787546E+09 | 3880200.32 | 0.783666E+09 | 0.384578E+09 | 0.117472E+10 |
May | 0.106121E+10 | 39888305.87 | 0.102132E+10 | 0.887238E+09 | 0.656741E+09 |
June | 0.120030E+10 | 0.108943E+09 | 0.109136E+10 | 0.132089E+10 | 0.439939E+09 |
July | 0.116321E+10 | 77806275.50 | 0.108541E+10 | 0.133561E+10 | 0.390720E+09 |
August | 0.973952E+09 | 17261139.88 | 0.956691E+09 | 0.110816E+10 | 0.458132E+09 |
September | 0.722653E+09 | 179185.62 | 0.722474E+09 | 0.635276E+09 | 0.788758E+09 |
October | 0.555216E+09 | 0.00 | 0.555216E+09 | 0.203783E+09 | 0.131802E+10 |
November | 0.375851E+09 | 0.00 | 0.375851E+09 | 38479153.68 | 0.195405E+10 |
December | 0.251926E+09 | 0.00 | 0.251926E+09 | 40.81 | 0.286158E+10 |
Annual Sum or Average | 0.859265E+10 | 0.247958E+09 | 0.834469E+10 | 0.609930E+10 | 0.172356E+11 |
Minimum of Months | 0.251926E+09 | 0.00 | 0.251926E+09 | 40.81 | 0.390720E+09 |
Maximum of Months | 0.120030E+10 | 0.108943E+09 | 0.109136E+10 | 0.133561E+10 | 0.313694E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.370993E+09 | 0.00 | 0.370993E+09 | 353629.96 | 0.313681E+10 |
February | 0.424830E+09 | 0.00 | 0.424830E+09 | 12205829.16 | 0.233650E+10 |
March | 0.704906E+09 | 0.00 | 0.704906E+09 | 0.172715E+09 | 0.171936E+10 |
April | 0.787515E+09 | 3880048.59 | 0.783635E+09 | 0.384563E+09 | 0.117467E+10 |
May | 0.106117E+10 | 39886746.06 | 0.102128E+10 | 0.887203E+09 | 0.656715E+09 |
June | 0.120025E+10 | 0.108938E+09 | 0.109131E+10 | 0.132084E+10 | 0.439922E+09 |
July | 0.116317E+10 | 77803232.92 | 0.108537E+10 | 0.133556E+10 | 0.390704E+09 |
August | 0.973913E+09 | 17260464.89 | 0.956653E+09 | 0.110812E+10 | 0.458113E+09 |
September | 0.722625E+09 | 179178.61 | 0.722445E+09 | 0.635251E+09 | 0.788727E+09 |
October | 0.555194E+09 | 0.00 | 0.555194E+09 | 0.203775E+09 | 0.131797E+10 |
November | 0.375836E+09 | 0.00 | 0.375836E+09 | 38477712.60 | 0.195397E+10 |
December | 0.251916E+09 | 0.00 | 0.251916E+09 | 41.09 | 0.286146E+10 |
Annual Sum or Average | 0.859231E+10 | 0.247948E+09 | 0.834436E+10 | 0.609906E+10 | 0.172349E+11 |
Minimum of Months | 0.251916E+09 | 0.00 | 0.251916E+09 | 41.09 | 0.390704E+09 |
Maximum of Months | 0.120025E+10 | 0.108938E+09 | 0.109131E+10 | 0.133556E+10 | 0.313681E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.883326E+09 | 0.363492E+09 | 0.519835E+09 | 0.359340E+09 | 0.314280E+10 |
February | 0.105754E+10 | 0.465020E+09 | 0.592516E+09 | 0.568092E+09 | 0.229306E+10 |
March | 0.159082E+10 | 0.631444E+09 | 0.959376E+09 | 0.114746E+10 | 0.171436E+10 |
April | 0.189036E+10 | 0.827850E+09 | 0.106251E+10 | 0.174108E+10 | 0.119706E+10 |
May | 0.245328E+10 | 0.107197E+10 | 0.138131E+10 | 0.267856E+10 | 0.720355E+09 |
June | 0.261268E+10 | 0.113778E+10 | 0.147490E+10 | 0.318128E+10 | 0.477920E+09 |
July | 0.272878E+10 | 0.125912E+10 | 0.146966E+10 | 0.340664E+10 | 0.414941E+09 |
August | 0.230031E+10 | 0.991713E+09 | 0.130859E+10 | 0.287871E+10 | 0.475124E+09 |
September | 0.198548E+10 | 0.938245E+09 | 0.104724E+10 | 0.227995E+10 | 0.824847E+09 |
October | 0.130746E+10 | 0.546118E+09 | 0.761346E+09 | 0.108255E+10 | 0.133138E+10 |
November | 0.746531E+09 | 0.242487E+09 | 0.504044E+09 | 0.353147E+09 | 0.196640E+10 |
December | 0.597545E+09 | 0.256601E+09 | 0.340945E+09 | 0.243842E+09 | 0.289441E+10 |
Annual Sum or Average | 0.201541E+11 | 0.873185E+10 | 0.114223E+11 | 0.199206E+11 | 0.174527E+11 |
Minimum of Months | 0.597545E+09 | 0.242487E+09 | 0.340945E+09 | 0.243842E+09 | 0.414941E+09 |
Maximum of Months | 0.272878E+10 | 0.125912E+10 | 0.147490E+10 | 0.340664E+10 | 0.314280E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.883326E+09 | 0.363492E+09 | 0.519835E+09 | 0.359340E+09 | 0.314280E+10 |
February | 0.105754E+10 | 0.465020E+09 | 0.592516E+09 | 0.568092E+09 | 0.229306E+10 |
March | 0.159082E+10 | 0.631444E+09 | 0.959376E+09 | 0.114746E+10 | 0.171436E+10 |
April | 0.189036E+10 | 0.827850E+09 | 0.106251E+10 | 0.174108E+10 | 0.119706E+10 |
May | 0.245328E+10 | 0.107197E+10 | 0.138131E+10 | 0.267856E+10 | 0.720355E+09 |
June | 0.261268E+10 | 0.113778E+10 | 0.147490E+10 | 0.318128E+10 | 0.477920E+09 |
July | 0.272878E+10 | 0.125912E+10 | 0.146966E+10 | 0.340664E+10 | 0.414941E+09 |
August | 0.230031E+10 | 0.991713E+09 | 0.130859E+10 | 0.287871E+10 | 0.475124E+09 |
September | 0.198548E+10 | 0.938245E+09 | 0.104724E+10 | 0.227995E+10 | 0.824847E+09 |
October | 0.130746E+10 | 0.546118E+09 | 0.761346E+09 | 0.108255E+10 | 0.133138E+10 |
November | 0.746531E+09 | 0.242487E+09 | 0.504044E+09 | 0.353147E+09 | 0.196640E+10 |
December | 0.597545E+09 | 0.256601E+09 | 0.340945E+09 | 0.243842E+09 | 0.289441E+10 |
Annual Sum or Average | 0.201541E+11 | 0.873185E+10 | 0.114223E+11 | 0.199206E+11 | 0.174527E+11 |
Minimum of Months | 0.597545E+09 | 0.242487E+09 | 0.340945E+09 | 0.243842E+09 | 0.414941E+09 |
Maximum of Months | 0.272878E+10 | 0.125912E+10 | 0.147490E+10 | 0.340664E+10 | 0.314280E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.883310E+09 | 0.363485E+09 | 0.519825E+09 | 0.359333E+09 | 0.314274E+10 |
February | 0.105752E+10 | 0.465012E+09 | 0.592506E+09 | 0.568081E+09 | 0.229302E+10 |
March | 0.159079E+10 | 0.631432E+09 | 0.959358E+09 | 0.114744E+10 | 0.171433E+10 |
April | 0.189033E+10 | 0.827835E+09 | 0.106249E+10 | 0.174105E+10 | 0.119704E+10 |
May | 0.245324E+10 | 0.107195E+10 | 0.138128E+10 | 0.267851E+10 | 0.720342E+09 |
June | 0.261263E+10 | 0.113776E+10 | 0.147487E+10 | 0.318122E+10 | 0.477912E+09 |
July | 0.272873E+10 | 0.125910E+10 | 0.146963E+10 | 0.340658E+10 | 0.414933E+09 |
August | 0.230026E+10 | 0.991695E+09 | 0.130857E+10 | 0.287866E+10 | 0.475116E+09 |
September | 0.198545E+10 | 0.938228E+09 | 0.104722E+10 | 0.227991E+10 | 0.824832E+09 |
October | 0.130744E+10 | 0.546108E+09 | 0.761332E+09 | 0.108253E+10 | 0.133136E+10 |
November | 0.746517E+09 | 0.242483E+09 | 0.504035E+09 | 0.353140E+09 | 0.196636E+10 |
December | 0.597534E+09 | 0.256596E+09 | 0.340939E+09 | 0.243838E+09 | 0.289435E+10 |
Annual Sum or Average | 0.201537E+11 | 0.873169E+10 | 0.114221E+11 | 0.199203E+11 | 0.174523E+11 |
Minimum of Months | 0.597534E+09 | 0.242483E+09 | 0.340939E+09 | 0.243838E+09 | 0.414933E+09 |
Maximum of Months | 0.272873E+10 | 0.125910E+10 | 0.147487E+10 | 0.340658E+10 | 0.314274E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.230729E+10 | 0.157893E+10 | 0.728362E+09 | 0.197646E+10 | 0.252977E+10 |
February | 0.223298E+10 | 0.150862E+10 | 0.724360E+09 | 0.198784E+10 | 0.188202E+10 |
March | 0.215139E+10 | 0.113285E+10 | 0.101854E+10 | 0.200655E+10 | 0.154696E+10 |
April | 0.187573E+10 | 0.876943E+09 | 0.998791E+09 | 0.196209E+10 | 0.114133E+10 |
May | 0.160578E+10 | 0.435349E+09 | 0.117043E+10 | 0.179415E+10 | 0.703110E+09 |
June | 0.150868E+10 | 0.307176E+09 | 0.120150E+10 | 0.187659E+10 | 0.464904E+09 |
July | 0.165028E+10 | 0.415827E+09 | 0.123445E+10 | 0.214533E+10 | 0.410143E+09 |
August | 0.185932E+10 | 0.666796E+09 | 0.119252E+10 | 0.245917E+10 | 0.483705E+09 |
September | 0.218042E+10 | 0.114890E+10 | 0.103152E+10 | 0.269153E+10 | 0.781652E+09 |
October | 0.235271E+10 | 0.147599E+10 | 0.876715E+09 | 0.252091E+10 | 0.120814E+10 |
November | 0.171785E+10 | 0.107541E+10 | 0.642445E+09 | 0.154590E+10 | 0.166710E+10 |
December | 0.189290E+10 | 0.143385E+10 | 0.459052E+09 | 0.173496E+10 | 0.239772E+10 |
Annual Sum or Average | 0.233353E+11 | 0.120566E+11 | 0.112787E+11 | 0.247015E+11 | 0.152165E+11 |
Minimum of Months | 0.150868E+10 | 0.307176E+09 | 0.459052E+09 | 0.154590E+10 | 0.410143E+09 |
Maximum of Months | 0.235271E+10 | 0.157893E+10 | 0.123445E+10 | 0.269153E+10 | 0.252977E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.230729E+10 | 0.157893E+10 | 0.728362E+09 | 0.197645E+10 | 0.252977E+10 |
February | 0.223297E+10 | 0.150861E+10 | 0.724359E+09 | 0.198784E+10 | 0.188202E+10 |
March | 0.215139E+10 | 0.113285E+10 | 0.101854E+10 | 0.200654E+10 | 0.154696E+10 |
April | 0.187573E+10 | 0.876941E+09 | 0.998790E+09 | 0.196208E+10 | 0.114133E+10 |
May | 0.160578E+10 | 0.435349E+09 | 0.117043E+10 | 0.179415E+10 | 0.703110E+09 |
June | 0.150868E+10 | 0.307175E+09 | 0.120150E+10 | 0.187659E+10 | 0.464904E+09 |
July | 0.165028E+10 | 0.415826E+09 | 0.123445E+10 | 0.214532E+10 | 0.410143E+09 |
August | 0.185931E+10 | 0.666795E+09 | 0.119252E+10 | 0.245916E+10 | 0.483705E+09 |
September | 0.218042E+10 | 0.114890E+10 | 0.103152E+10 | 0.269153E+10 | 0.781652E+09 |
October | 0.235271E+10 | 0.147599E+10 | 0.876714E+09 | 0.252091E+10 | 0.120814E+10 |
November | 0.171785E+10 | 0.107541E+10 | 0.642444E+09 | 0.154590E+10 | 0.166710E+10 |
December | 0.189290E+10 | 0.143385E+10 | 0.459051E+09 | 0.173495E+10 | 0.239772E+10 |
Annual Sum or Average | 0.233353E+11 | 0.120566E+11 | 0.112787E+11 | 0.247014E+11 | 0.152165E+11 |
Minimum of Months | 0.150868E+10 | 0.307175E+09 | 0.459051E+09 | 0.154590E+10 | 0.410143E+09 |
Maximum of Months | 0.235271E+10 | 0.157893E+10 | 0.123445E+10 | 0.269153E+10 | 0.252977E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.230729E+10 | 0.157893E+10 | 0.728362E+09 | 0.197646E+10 | 0.252977E+10 |
February | 0.223298E+10 | 0.150862E+10 | 0.724360E+09 | 0.198784E+10 | 0.188202E+10 |
March | 0.215139E+10 | 0.113285E+10 | 0.101854E+10 | 0.200655E+10 | 0.154696E+10 |
April | 0.187573E+10 | 0.876943E+09 | 0.998791E+09 | 0.196209E+10 | 0.114133E+10 |
May | 0.160578E+10 | 0.435349E+09 | 0.117043E+10 | 0.179415E+10 | 0.703110E+09 |
June | 0.150868E+10 | 0.307176E+09 | 0.120150E+10 | 0.187659E+10 | 0.464904E+09 |
July | 0.165028E+10 | 0.415827E+09 | 0.123445E+10 | 0.214533E+10 | 0.410143E+09 |
August | 0.185932E+10 | 0.666796E+09 | 0.119252E+10 | 0.245917E+10 | 0.483705E+09 |
September | 0.218042E+10 | 0.114890E+10 | 0.103152E+10 | 0.269153E+10 | 0.781652E+09 |
October | 0.235271E+10 | 0.147599E+10 | 0.876715E+09 | 0.252091E+10 | 0.120814E+10 |
November | 0.171785E+10 | 0.107541E+10 | 0.642445E+09 | 0.154590E+10 | 0.166710E+10 |
December | 0.189290E+10 | 0.143385E+10 | 0.459052E+09 | 0.173496E+10 | 0.239772E+10 |
Annual Sum or Average | 0.233353E+11 | 0.120566E+11 | 0.112787E+11 | 0.247015E+11 | 0.152165E+11 |
Minimum of Months | 0.150868E+10 | 0.307176E+09 | 0.459052E+09 | 0.154590E+10 | 0.410143E+09 |
Maximum of Months | 0.235271E+10 | 0.157893E+10 | 0.123445E+10 | 0.269153E+10 | 0.252977E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.230729E+10 | 0.157893E+10 | 0.728362E+09 | 0.197645E+10 | 0.252977E+10 |
February | 0.223297E+10 | 0.150861E+10 | 0.724359E+09 | 0.198784E+10 | 0.188202E+10 |
March | 0.215139E+10 | 0.113285E+10 | 0.101854E+10 | 0.200654E+10 | 0.154696E+10 |
April | 0.187573E+10 | 0.876941E+09 | 0.998790E+09 | 0.196208E+10 | 0.114133E+10 |
May | 0.160578E+10 | 0.435349E+09 | 0.117043E+10 | 0.179415E+10 | 0.703110E+09 |
June | 0.150868E+10 | 0.307175E+09 | 0.120150E+10 | 0.187659E+10 | 0.464904E+09 |
July | 0.165028E+10 | 0.415826E+09 | 0.123445E+10 | 0.214532E+10 | 0.410143E+09 |
August | 0.185931E+10 | 0.666795E+09 | 0.119252E+10 | 0.245916E+10 | 0.483705E+09 |
September | 0.218042E+10 | 0.114890E+10 | 0.103152E+10 | 0.269153E+10 | 0.781652E+09 |
October | 0.235271E+10 | 0.147599E+10 | 0.876714E+09 | 0.252091E+10 | 0.120814E+10 |
November | 0.171785E+10 | 0.107541E+10 | 0.642444E+09 | 0.154590E+10 | 0.166710E+10 |
December | 0.189290E+10 | 0.143385E+10 | 0.459051E+09 | 0.173495E+10 | 0.239772E+10 |
Annual Sum or Average | 0.233353E+11 | 0.120566E+11 | 0.112787E+11 | 0.247014E+11 | 0.152165E+11 |
Minimum of Months | 0.150868E+10 | 0.307175E+09 | 0.459051E+09 | 0.154590E+10 | 0.410143E+09 |
Maximum of Months | 0.235271E+10 | 0.157893E+10 | 0.123445E+10 | 0.269153E+10 | 0.252977E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.230720E+10 | 0.157887E+10 | 0.728333E+09 | 0.197638E+10 | 0.252966E+10 |
February | 0.223289E+10 | 0.150856E+10 | 0.724330E+09 | 0.198776E+10 | 0.188194E+10 |
March | 0.215130E+10 | 0.113280E+10 | 0.101850E+10 | 0.200647E+10 | 0.154690E+10 |
April | 0.187566E+10 | 0.876907E+09 | 0.998751E+09 | 0.196201E+10 | 0.114128E+10 |
May | 0.160572E+10 | 0.435331E+09 | 0.117038E+10 | 0.179408E+10 | 0.703082E+09 |
June | 0.150862E+10 | 0.307163E+09 | 0.120146E+10 | 0.187651E+10 | 0.464885E+09 |
July | 0.165021E+10 | 0.415810E+09 | 0.123440E+10 | 0.214524E+10 | 0.410126E+09 |
August | 0.185924E+10 | 0.666769E+09 | 0.119247E+10 | 0.245907E+10 | 0.483686E+09 |
September | 0.218033E+10 | 0.114886E+10 | 0.103148E+10 | 0.269143E+10 | 0.781621E+09 |
October | 0.235261E+10 | 0.147594E+10 | 0.876680E+09 | 0.252081E+10 | 0.120810E+10 |
November | 0.171778E+10 | 0.107537E+10 | 0.642419E+09 | 0.154584E+10 | 0.166703E+10 |
December | 0.189283E+10 | 0.143379E+10 | 0.459033E+09 | 0.173489E+10 | 0.239762E+10 |
Annual Sum or Average | 0.233344E+11 | 0.120562E+11 | 0.112782E+11 | 0.247005E+11 | 0.152159E+11 |
Minimum of Months | 0.150862E+10 | 0.307163E+09 | 0.459033E+09 | 0.154584E+10 | 0.410126E+09 |
Maximum of Months | 0.235261E+10 | 0.157887E+10 | 0.123440E+10 | 0.269143E+10 | 0.252966E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.876043E+09 | 0.354458E+09 | 0.521585E+09 | 0.366916E+09 | 0.330274E+10 |
February | 0.116025E+10 | 0.571736E+09 | 0.588513E+09 | 0.693978E+09 | 0.249666E+10 |
March | 0.153350E+10 | 0.570547E+09 | 0.962955E+09 | 0.104229E+10 | 0.194153E+10 |
April | 0.216476E+10 | 0.107044E+10 | 0.109433E+10 | 0.208714E+10 | 0.143356E+10 |
May | 0.224339E+10 | 0.896183E+09 | 0.134721E+10 | 0.242300E+10 | 0.823099E+09 |
June | 0.254744E+10 | 0.110400E+10 | 0.144344E+10 | 0.307961E+10 | 0.578127E+09 |
July | 0.282635E+10 | 0.134256E+10 | 0.148379E+10 | 0.351584E+10 | 0.526754E+09 |
August | 0.247094E+10 | 0.113400E+10 | 0.133694E+10 | 0.307327E+10 | 0.622241E+09 |
September | 0.193564E+10 | 0.918753E+09 | 0.101688E+10 | 0.220711E+10 | 0.926719E+09 |
October | 0.139379E+10 | 0.619664E+09 | 0.774128E+09 | 0.119246E+10 | 0.151647E+10 |
November | 0.807364E+09 | 0.298563E+09 | 0.508802E+09 | 0.431907E+09 | 0.220075E+10 |
December | 0.641602E+09 | 0.302460E+09 | 0.339141E+09 | 0.305481E+09 | 0.320812E+10 |
Annual Sum or Average | 0.206011E+11 | 0.918336E+10 | 0.114177E+11 | 0.204190E+11 | 0.195768E+11 |
Minimum of Months | 0.641602E+09 | 0.298563E+09 | 0.339141E+09 | 0.305481E+09 | 0.526754E+09 |
Maximum of Months | 0.282635E+10 | 0.134256E+10 | 0.148379E+10 | 0.351584E+10 | 0.330274E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.876043E+09 | 0.354458E+09 | 0.521585E+09 | 0.366916E+09 | 0.330274E+10 |
February | 0.116025E+10 | 0.571736E+09 | 0.588513E+09 | 0.693978E+09 | 0.249666E+10 |
March | 0.153350E+10 | 0.570547E+09 | 0.962955E+09 | 0.104229E+10 | 0.194153E+10 |
April | 0.216476E+10 | 0.107044E+10 | 0.109433E+10 | 0.208714E+10 | 0.143356E+10 |
May | 0.224339E+10 | 0.896183E+09 | 0.134721E+10 | 0.242300E+10 | 0.823099E+09 |
June | 0.254744E+10 | 0.110400E+10 | 0.144344E+10 | 0.307961E+10 | 0.578127E+09 |
July | 0.282635E+10 | 0.134256E+10 | 0.148379E+10 | 0.351584E+10 | 0.526754E+09 |
August | 0.247094E+10 | 0.113400E+10 | 0.133694E+10 | 0.307327E+10 | 0.622241E+09 |
September | 0.193564E+10 | 0.918753E+09 | 0.101688E+10 | 0.220711E+10 | 0.926719E+09 |
October | 0.139379E+10 | 0.619664E+09 | 0.774128E+09 | 0.119246E+10 | 0.151647E+10 |
November | 0.807364E+09 | 0.298563E+09 | 0.508802E+09 | 0.431907E+09 | 0.220075E+10 |
December | 0.641602E+09 | 0.302460E+09 | 0.339141E+09 | 0.305481E+09 | 0.320812E+10 |
Annual Sum or Average | 0.206011E+11 | 0.918336E+10 | 0.114177E+11 | 0.204190E+11 | 0.195768E+11 |
Minimum of Months | 0.641602E+09 | 0.298563E+09 | 0.339141E+09 | 0.305481E+09 | 0.526754E+09 |
Maximum of Months | 0.282635E+10 | 0.134256E+10 | 0.148379E+10 | 0.351584E+10 | 0.330274E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.876027E+09 | 0.354451E+09 | 0.521576E+09 | 0.366909E+09 | 0.330267E+10 |
February | 0.116023E+10 | 0.571726E+09 | 0.588503E+09 | 0.693966E+09 | 0.249661E+10 |
March | 0.153347E+10 | 0.570536E+09 | 0.962937E+09 | 0.104227E+10 | 0.194150E+10 |
April | 0.216472E+10 | 0.107042E+10 | 0.109431E+10 | 0.208710E+10 | 0.143353E+10 |
May | 0.224335E+10 | 0.896166E+09 | 0.134719E+10 | 0.242296E+10 | 0.823084E+09 |
June | 0.254739E+10 | 0.110398E+10 | 0.144342E+10 | 0.307955E+10 | 0.578116E+09 |
July | 0.282630E+10 | 0.134254E+10 | 0.148376E+10 | 0.351578E+10 | 0.526744E+09 |
August | 0.247090E+10 | 0.113398E+10 | 0.133692E+10 | 0.307322E+10 | 0.622230E+09 |
September | 0.193560E+10 | 0.918736E+09 | 0.101687E+10 | 0.220707E+10 | 0.926702E+09 |
October | 0.139377E+10 | 0.619653E+09 | 0.774114E+09 | 0.119244E+10 | 0.151644E+10 |
November | 0.807350E+09 | 0.298557E+09 | 0.508792E+09 | 0.431899E+09 | 0.220071E+10 |
December | 0.641590E+09 | 0.302455E+09 | 0.339135E+09 | 0.305475E+09 | 0.320806E+10 |
Annual Sum or Average | 0.206007E+11 | 0.918319E+10 | 0.114175E+11 | 0.204186E+11 | 0.195764E+11 |
Minimum of Months | 0.641590E+09 | 0.298557E+09 | 0.339135E+09 | 0.305475E+09 | 0.526744E+09 |
Maximum of Months | 0.282630E+10 | 0.134254E+10 | 0.148376E+10 | 0.351578E+10 | 0.330267E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185502E+10 | 0.00 | 0.185502E+10 | 7014468.58 | 0.147751E+11 |
February | 0.212421E+10 | 0.00 | 0.212421E+10 | 0.113208E+09 | 0.108576E+11 |
March | 0.352463E+10 | 0.00 | 0.352463E+10 | 0.102724E+10 | 0.780788E+10 |
April | 0.393768E+10 | 19400790.29 | 0.391828E+10 | 0.209974E+10 | 0.523921E+10 |
May | 0.530598E+10 | 0.199439E+09 | 0.510654E+10 | 0.451533E+10 | 0.311435E+10 |
June | 0.600142E+10 | 0.544707E+09 | 0.545672E+10 | 0.666009E+10 | 0.207753E+10 |
July | 0.581601E+10 | 0.389027E+09 | 0.542698E+10 | 0.677255E+10 | 0.183903E+10 |
August | 0.486970E+10 | 86304759.35 | 0.478340E+10 | 0.562513E+10 | 0.217714E+10 |
September | 0.361322E+10 | 895918.34 | 0.361233E+10 | 0.327409E+10 | 0.367794E+10 |
October | 0.277605E+10 | 0.00 | 0.277605E+10 | 0.121361E+10 | 0.589780E+10 |
November | 0.187923E+10 | 0.00 | 0.187923E+10 | 0.271604E+09 | 0.878026E+10 |
December | 0.125962E+10 | 0.00 | 0.125962E+10 | 842734.89 | 0.131288E+11 |
Annual Sum or Average | 0.429628E+11 | 0.123978E+10 | 0.417230E+11 | 0.315805E+11 | 0.793726E+11 |
Minimum of Months | 0.125962E+10 | 0.00 | 0.125962E+10 | 842734.89 | 0.183903E+10 |
Maximum of Months | 0.600142E+10 | 0.544707E+09 | 0.545672E+10 | 0.677255E+10 | 0.147751E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.264995E+10 | 0.109046E+10 | 0.155949E+10 | 0.111888E+10 | 0.891113E+10 |
February | 0.317258E+10 | 0.139505E+10 | 0.177753E+10 | 0.175964E+10 | 0.646204E+10 |
March | 0.477241E+10 | 0.189431E+10 | 0.287810E+10 | 0.351360E+10 | 0.480871E+10 |
April | 0.567103E+10 | 0.248353E+10 | 0.318750E+10 | 0.525257E+10 | 0.334520E+10 |
May | 0.735977E+10 | 0.321589E+10 | 0.414388E+10 | 0.799522E+10 | 0.208118E+10 |
June | 0.783796E+10 | 0.341331E+10 | 0.442465E+10 | 0.951366E+10 | 0.138217E+10 |
July | 0.818625E+10 | 0.377732E+10 | 0.440893E+10 | 0.101899E+11 | 0.122119E+10 |
August | 0.690085E+10 | 0.297511E+10 | 0.392574E+10 | 0.859591E+10 | 0.143969E+10 |
September | 0.595639E+10 | 0.281471E+10 | 0.314169E+10 | 0.684150E+10 | 0.235066E+10 |
October | 0.392235E+10 | 0.163834E+10 | 0.228401E+10 | 0.334414E+10 | 0.368577E+10 |
November | 0.223957E+10 | 0.727454E+09 | 0.151212E+10 | 0.113337E+10 | 0.543790E+10 |
December | 0.179262E+10 | 0.769794E+09 | 0.102282E+10 | 0.774972E+09 | 0.810794E+10 |
Annual Sum or Average | 0.604617E+11 | 0.261953E+11 | 0.342665E+11 | 0.600333E+11 | 0.492336E+11 |
Minimum of Months | 0.179262E+10 | 0.727454E+09 | 0.102282E+10 | 0.774972E+09 | 0.122119E+10 |
Maximum of Months | 0.818625E+10 | 0.377732E+10 | 0.442465E+10 | 0.101899E+11 | 0.891113E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.115363E+11 | 0.789456E+10 | 0.364177E+10 | 0.987672E+10 | 0.122444E+11 |
February | 0.111647E+11 | 0.754299E+10 | 0.362175E+10 | 0.991077E+10 | 0.912652E+10 |
March | 0.107568E+11 | 0.566418E+10 | 0.509263E+10 | 0.100076E+11 | 0.744832E+10 |
April | 0.937855E+10 | 0.438466E+10 | 0.499390E+10 | 0.979363E+10 | 0.542792E+10 |
May | 0.802881E+10 | 0.217672E+10 | 0.585209E+10 | 0.892732E+10 | 0.342482E+10 |
June | 0.754331E+10 | 0.153586E+10 | 0.600745E+10 | 0.938217E+10 | 0.223156E+10 |
July | 0.825130E+10 | 0.207911E+10 | 0.617219E+10 | 0.107414E+11 | 0.197487E+10 |
August | 0.929647E+10 | 0.333394E+10 | 0.596253E+10 | 0.122652E+11 | 0.237411E+10 |
September | 0.109020E+11 | 0.574444E+10 | 0.515752E+10 | 0.133909E+11 | 0.381573E+10 |
October | 0.117634E+11 | 0.737988E+10 | 0.438352E+10 | 0.125544E+11 | 0.585090E+10 |
November | 0.858916E+10 | 0.537698E+10 | 0.321218E+10 | 0.774522E+10 | 0.798966E+10 |
December | 0.946440E+10 | 0.716917E+10 | 0.229523E+10 | 0.870361E+10 | 0.114819E+11 |
Annual Sum or Average | 0.116675E+12 | 0.602825E+11 | 0.563928E+11 | 0.123299E+12 | 0.733908E+11 |
Minimum of Months | 0.754331E+10 | 0.153586E+10 | 0.229523E+10 | 0.774522E+10 | 0.197487E+10 |
Maximum of Months | 0.117634E+11 | 0.789456E+10 | 0.617219E+10 | 0.133909E+11 | 0.122444E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.262810E+10 | 0.106336E+10 | 0.156474E+10 | 0.114868E+10 | 0.923247E+10 |
February | 0.348071E+10 | 0.171519E+10 | 0.176552E+10 | 0.216540E+10 | 0.683712E+10 |
March | 0.460046E+10 | 0.171162E+10 | 0.288883E+10 | 0.331123E+10 | 0.508462E+10 |
April | 0.649422E+10 | 0.321128E+10 | 0.328294E+10 | 0.641363E+10 | 0.364060E+10 |
May | 0.673011E+10 | 0.268852E+10 | 0.404159E+10 | 0.734092E+10 | 0.228632E+10 |
June | 0.764225E+10 | 0.331196E+10 | 0.433028E+10 | 0.931219E+10 | 0.156126E+10 |
July | 0.847896E+10 | 0.402764E+10 | 0.445132E+10 | 0.106360E+11 | 0.144311E+10 |
August | 0.741275E+10 | 0.340197E+10 | 0.401078E+10 | 0.933718E+10 | 0.165711E+10 |
September | 0.580685E+10 | 0.275623E+10 | 0.305062E+10 | 0.669953E+10 | 0.255172E+10 |
October | 0.418133E+10 | 0.185897E+10 | 0.232236E+10 | 0.375672E+10 | 0.396954E+10 |
November | 0.242207E+10 | 0.895679E+09 | 0.152639E+10 | 0.142426E+10 | 0.569096E+10 |
December | 0.192479E+10 | 0.907372E+09 | 0.101741E+10 | 0.998363E+09 | 0.843870E+10 |
Annual Sum or Average | 0.618026E+11 | 0.275498E+11 | 0.342528E+11 | 0.625441E+11 | 0.523935E+11 |
Minimum of Months | 0.192479E+10 | 0.895679E+09 | 0.101741E+10 | 0.998363E+09 | 0.144311E+10 |
Maximum of Months | 0.847896E+10 | 0.402764E+10 | 0.445132E+10 | 0.106360E+11 | 0.923247E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.185502E+10 | 0.00 | 0.185502E+10 | 8768660.64 | 0.144997E+11 |
February | 0.212421E+10 | 0.00 | 0.212421E+10 | 0.137269E+09 | 0.104844E+11 |
March | 0.352463E+10 | 0.00 | 0.352463E+10 | 0.111007E+10 | 0.741120E+10 |
April | 0.393768E+10 | 19400790.29 | 0.391828E+10 | 0.218394E+10 | 0.488393E+10 |
May | 0.530598E+10 | 0.199439E+09 | 0.510654E+10 | 0.458138E+10 | 0.298217E+10 |
June | 0.600142E+10 | 0.544707E+09 | 0.545672E+10 | 0.665787E+10 | 0.201489E+10 |
July | 0.581601E+10 | 0.389027E+09 | 0.542698E+10 | 0.674138E+10 | 0.181735E+10 |
August | 0.486970E+10 | 86304759.35 | 0.478340E+10 | 0.561701E+10 | 0.213299E+10 |
September | 0.361322E+10 | 895918.34 | 0.361233E+10 | 0.334016E+10 | 0.347542E+10 |
October | 0.277605E+10 | 0.00 | 0.277605E+10 | 0.137565E+10 | 0.538741E+10 |
November | 0.187923E+10 | 0.00 | 0.187923E+10 | 0.336921E+09 | 0.825855E+10 |
December | 0.125962E+10 | 0.00 | 0.125962E+10 | 4161876.18 | 0.127235E+11 |
Annual Sum or Average | 0.429628E+11 | 0.123978E+10 | 0.417230E+11 | 0.320946E+11 | 0.760715E+11 |
Minimum of Months | 0.125962E+10 | 0.00 | 0.125962E+10 | 4161876.18 | 0.181735E+10 |
Maximum of Months | 0.600142E+10 | 0.544707E+09 | 0.545672E+10 | 0.674138E+10 | 0.144997E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.264995E+10 | 0.109046E+10 | 0.155949E+10 | 0.113298E+10 | 0.875162E+10 |
February | 0.317258E+10 | 0.139505E+10 | 0.177753E+10 | 0.179900E+10 | 0.623128E+10 |
March | 0.477241E+10 | 0.189431E+10 | 0.287810E+10 | 0.358438E+10 | 0.457166E+10 |
April | 0.567103E+10 | 0.248353E+10 | 0.318750E+10 | 0.529410E+10 | 0.315662E+10 |
May | 0.735977E+10 | 0.321589E+10 | 0.414388E+10 | 0.800681E+10 | 0.201403E+10 |
June | 0.783796E+10 | 0.341331E+10 | 0.442465E+10 | 0.949599E+10 | 0.135130E+10 |
July | 0.818625E+10 | 0.377732E+10 | 0.440893E+10 | 0.101546E+11 | 0.121598E+10 |
August | 0.690085E+10 | 0.297511E+10 | 0.392574E+10 | 0.857527E+10 | 0.142248E+10 |
September | 0.595639E+10 | 0.281471E+10 | 0.314169E+10 | 0.686218E+10 | 0.225413E+10 |
October | 0.392235E+10 | 0.163834E+10 | 0.228401E+10 | 0.346372E+10 | 0.340532E+10 |
November | 0.223957E+10 | 0.727454E+09 | 0.151212E+10 | 0.119916E+10 | 0.513304E+10 |
December | 0.179262E+10 | 0.769794E+09 | 0.102282E+10 | 0.796961E+09 | 0.785727E+10 |
Annual Sum or Average | 0.604617E+11 | 0.261953E+11 | 0.342665E+11 | 0.603652E+11 | 0.473647E+11 |
Minimum of Months | 0.179262E+10 | 0.727454E+09 | 0.102282E+10 | 0.796961E+09 | 0.121598E+10 |
Maximum of Months | 0.818625E+10 | 0.377732E+10 | 0.442465E+10 | 0.101546E+11 | 0.875162E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.115363E+11 | 0.789456E+10 | 0.364177E+10 | 0.993480E+10 | 0.119439E+11 |
February | 0.111647E+11 | 0.754299E+10 | 0.362175E+10 | 0.100008E+11 | 0.873587E+10 |
March | 0.107568E+11 | 0.566418E+10 | 0.509263E+10 | 0.101081E+11 | 0.705804E+10 |
April | 0.937855E+10 | 0.438466E+10 | 0.499390E+10 | 0.985067E+10 | 0.509231E+10 |
May | 0.802881E+10 | 0.217672E+10 | 0.585209E+10 | 0.895477E+10 | 0.328656E+10 |
June | 0.754331E+10 | 0.153586E+10 | 0.600745E+10 | 0.936961E+10 | 0.216438E+10 |
July | 0.825130E+10 | 0.207911E+10 | 0.617219E+10 | 0.107031E+11 | 0.195101E+10 |
August | 0.929647E+10 | 0.333394E+10 | 0.596253E+10 | 0.122361E+11 | 0.232986E+10 |
September | 0.109020E+11 | 0.574444E+10 | 0.515752E+10 | 0.134213E+11 | 0.364228E+10 |
October | 0.117634E+11 | 0.737988E+10 | 0.438352E+10 | 0.127015E+11 | 0.540540E+10 |
November | 0.858916E+10 | 0.537698E+10 | 0.321218E+10 | 0.788373E+10 | 0.749502E+10 |
December | 0.946440E+10 | 0.716917E+10 | 0.229523E+10 | 0.877756E+10 | 0.110575E+11 |
Annual Sum or Average | 0.116675E+12 | 0.602825E+11 | 0.563928E+11 | 0.123942E+12 | 0.701621E+11 |
Minimum of Months | 0.754331E+10 | 0.153586E+10 | 0.229523E+10 | 0.788373E+10 | 0.195101E+10 |
Maximum of Months | 0.117634E+11 | 0.789456E+10 | 0.617219E+10 | 0.134213E+11 | 0.119439E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.262810E+10 | 0.106336E+10 | 0.156474E+10 | 0.115646E+10 | 0.905569E+10 |
February | 0.348071E+10 | 0.171519E+10 | 0.176552E+10 | 0.218556E+10 | 0.661433E+10 |
March | 0.460046E+10 | 0.171162E+10 | 0.288883E+10 | 0.335019E+10 | 0.486255E+10 |
April | 0.649422E+10 | 0.321128E+10 | 0.328294E+10 | 0.643710E+10 | 0.344614E+10 |
May | 0.673011E+10 | 0.268852E+10 | 0.404159E+10 | 0.735756E+10 | 0.220417E+10 |
June | 0.764225E+10 | 0.331196E+10 | 0.433028E+10 | 0.929752E+10 | 0.152275E+10 |
July | 0.847896E+10 | 0.402764E+10 | 0.445132E+10 | 0.106060E+11 | 0.142791E+10 |
August | 0.741275E+10 | 0.340197E+10 | 0.401078E+10 | 0.931796E+10 | 0.163086E+10 |
September | 0.580685E+10 | 0.275623E+10 | 0.305062E+10 | 0.672205E+10 | 0.244845E+10 |
October | 0.418133E+10 | 0.185897E+10 | 0.232236E+10 | 0.382851E+10 | 0.370840E+10 |
November | 0.242207E+10 | 0.895679E+09 | 0.152639E+10 | 0.146961E+10 | 0.540379E+10 |
December | 0.192479E+10 | 0.907372E+09 | 0.101741E+10 | 0.101055E+10 | 0.819167E+10 |
Annual Sum or Average | 0.618026E+11 | 0.275498E+11 | 0.342528E+11 | 0.627390E+11 | 0.505167E+11 |
Minimum of Months | 0.192479E+10 | 0.895679E+09 | 0.101741E+10 | 0.101055E+10 | 0.142791E+10 |
Maximum of Months | 0.847896E+10 | 0.402764E+10 | 0.445132E+10 | 0.106060E+11 | 0.905569E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.66 | 5855.95 | 692.59 | 0.00 | 692.59 | 0.00 | 0.00 |
February | 25.23 | 4829.23 | 878.07 | 0.00 | 878.07 | 0.00 | 0.00 |
March | 322.43 | 3209.78 | 1315.95 | 0.00 | 1315.95 | 0.00 | 0.00 |
April | 741.85 | 2266.03 | 1519.17 | 7.48 | 1511.69 | 0.00 | 0.00 |
May | 1656.27 | 1225.99 | 1981.03 | 74.46 | 1906.57 | 0.00 | 0.00 |
June | 2548.00 | 848.64 | 2315.37 | 210.15 | 2105.22 | 0.00 | 0.00 |
July | 2493.28 | 729.38 | 2171.46 | 145.25 | 2026.21 | 0.00 | 0.00 |
August | 2068.69 | 855.23 | 1818.15 | 32.22 | 1785.92 | 0.00 | 0.00 |
September | 1225.45 | 1521.51 | 1394.00 | 0.35 | 1393.65 | 0.00 | 0.00 |
October | 380.42 | 2460.44 | 1036.46 | 0.00 | 1036.46 | 0.00 | 0.00 |
November | 74.23 | 3769.35 | 725.02 | 0.00 | 725.02 | 0.00 | 0.00 |
December | 0.00 | 5341.91 | 470.29 | 0.00 | 470.29 | 0.00 | 0.00 |
Annual Sum or Average | 967.03 | 2732.67 | 1362.35 | 39.31 | 1323.03 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 729.38 | 470.29 | 0.00 | 470.29 | 0.00 | 0.00 |
Maximum of Months | 2548.00 | 5855.95 | 2315.37 | 210.15 | 2105.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 402.48 | 3520.14 | 989.38 | 407.13 | 582.25 | 0.00 | 0.00 |
February | 704.47 | 2843.57 | 1311.42 | 576.66 | 734.76 | 0.00 | 0.00 |
March | 1285.23 | 1920.19 | 1781.82 | 707.26 | 1074.56 | 0.00 | 0.00 |
April | 2015.13 | 1385.48 | 2187.91 | 958.15 | 1229.75 | 0.00 | 0.00 |
May | 3000.16 | 806.84 | 2747.84 | 1200.68 | 1547.16 | 0.00 | 0.00 |
June | 3682.01 | 553.15 | 3023.92 | 1316.87 | 1707.05 | 0.00 | 0.00 |
July | 3815.66 | 464.76 | 3056.41 | 1410.30 | 1646.11 | 0.00 | 0.00 |
August | 3224.34 | 532.17 | 2576.49 | 1110.78 | 1465.71 | 0.00 | 0.00 |
September | 2638.81 | 954.68 | 2298.00 | 1085.93 | 1212.08 | 0.00 | 0.00 |
October | 1212.52 | 1491.24 | 1464.44 | 611.69 | 852.76 | 0.00 | 0.00 |
November | 408.73 | 2275.91 | 864.04 | 280.65 | 583.38 | 0.00 | 0.00 |
December | 273.12 | 3241.92 | 669.29 | 287.41 | 381.88 | 0.00 | 0.00 |
Annual Sum or Average | 1895.03 | 1660.25 | 1917.24 | 830.65 | 1086.59 | 0.00 | 0.00 |
Minimum of Months | 273.12 | 464.76 | 669.29 | 280.65 | 381.88 | 0.00 | 0.00 |
Maximum of Months | 3815.66 | 3520.14 | 3056.41 | 1410.30 | 1707.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3689.59 | 4722.49 | 4307.19 | 2947.50 | 1359.69 | 0.00 | 0.00 |
February | 4108.43 | 3889.72 | 4615.07 | 3117.98 | 1497.09 | 0.00 | 0.00 |
March | 3745.76 | 2887.82 | 4016.15 | 2114.77 | 1901.38 | 0.00 | 0.00 |
April | 3784.86 | 2201.61 | 3618.28 | 1691.62 | 1926.66 | 0.00 | 0.00 |
May | 3349.26 | 1312.55 | 2997.62 | 812.70 | 2184.93 | 0.00 | 0.00 |
June | 3619.93 | 896.80 | 2910.24 | 592.54 | 2317.70 | 0.00 | 0.00 |
July | 4004.83 | 765.64 | 3080.69 | 776.25 | 2304.44 | 0.00 | 0.00 |
August | 4590.70 | 902.97 | 3470.92 | 1244.75 | 2226.16 | 0.00 | 0.00 |
September | 5191.96 | 1507.80 | 4206.02 | 2216.23 | 1989.79 | 0.00 | 0.00 |
October | 4705.96 | 2255.33 | 4391.97 | 2755.34 | 1636.63 | 0.00 | 0.00 |
November | 2982.04 | 3215.83 | 3313.73 | 2074.46 | 1239.27 | 0.00 | 0.00 |
December | 3238.77 | 4475.99 | 3533.62 | 2676.67 | 856.94 | 0.00 | 0.00 |
Annual Sum or Average | 3916.36 | 2412.55 | 3699.76 | 1911.55 | 1788.21 | 0.00 | 0.00 |
Minimum of Months | 2982.04 | 765.64 | 2910.24 | 592.54 | 856.94 | 0.00 | 0.00 |
Maximum of Months | 5191.96 | 4722.49 | 4615.07 | 3117.98 | 2317.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 410.97 | 3699.28 | 981.22 | 397.02 | 584.21 | 0.00 | 0.00 |
February | 860.58 | 3096.03 | 1438.79 | 708.99 | 729.80 | 0.00 | 0.00 |
March | 1167.44 | 2174.64 | 1717.62 | 639.05 | 1078.57 | 0.00 | 0.00 |
April | 2415.65 | 1659.20 | 2505.50 | 1238.93 | 1266.57 | 0.00 | 0.00 |
May | 2713.92 | 921.92 | 2512.75 | 1003.78 | 1508.96 | 0.00 | 0.00 |
June | 3564.34 | 669.12 | 2948.41 | 1277.77 | 1670.64 | 0.00 | 0.00 |
July | 3937.97 | 590.00 | 3165.70 | 1503.76 | 1661.94 | 0.00 | 0.00 |
August | 3442.27 | 696.95 | 2767.61 | 1270.15 | 1497.46 | 0.00 | 0.00 |
September | 2554.51 | 1072.58 | 2240.31 | 1063.36 | 1176.94 | 0.00 | 0.00 |
October | 1335.63 | 1698.54 | 1561.14 | 694.06 | 867.07 | 0.00 | 0.00 |
November | 499.89 | 2547.15 | 934.44 | 345.56 | 588.89 | 0.00 | 0.00 |
December | 342.16 | 3593.30 | 718.64 | 338.78 | 379.86 | 0.00 | 0.00 |
Annual Sum or Average | 1942.44 | 1862.31 | 1959.76 | 873.60 | 1086.15 | 0.00 | 0.00 |
Minimum of Months | 342.16 | 590.00 | 718.64 | 338.78 | 379.86 | 0.00 | 0.00 |
Maximum of Months | 3937.97 | 3699.28 | 3165.70 | 1503.76 | 1670.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2.62 | 5516.40 | 692.58 | 0.00 | 692.58 | 0.00 | 0.00 |
February | 46.80 | 4488.09 | 878.06 | 0.00 | 878.06 | 0.00 | 0.00 |
March | 383.53 | 2915.13 | 1315.95 | 0.00 | 1315.95 | 0.00 | 0.00 |
April | 810.09 | 2021.30 | 1519.17 | 7.48 | 1511.68 | 0.00 | 0.00 |
May | 1685.83 | 1162.76 | 1981.02 | 74.46 | 1906.56 | 0.00 | 0.00 |
June | 2569.48 | 801.52 | 2315.36 | 210.15 | 2105.21 | 0.00 | 0.00 |
July | 2528.58 | 686.62 | 2171.45 | 145.25 | 2026.20 | 0.00 | 0.00 |
August | 2100.18 | 812.85 | 1818.14 | 32.22 | 1785.92 | 0.00 | 0.00 |
September | 1263.15 | 1418.96 | 1393.99 | 0.35 | 1393.65 | 0.00 | 0.00 |
October | 453.11 | 2201.99 | 1036.46 | 0.00 | 1036.46 | 0.00 | 0.00 |
November | 104.79 | 3387.45 | 725.01 | 0.00 | 725.01 | 0.00 | 0.00 |
December | 0.31 | 4901.73 | 470.29 | 0.00 | 470.29 | 0.00 | 0.00 |
Annual Sum or Average | 1001.41 | 2516.89 | 1362.34 | 39.31 | 1323.03 | 0.00 | 0.00 |
Minimum of Months | 0.31 | 686.62 | 470.29 | 0.00 | 470.29 | 0.00 | 0.00 |
Maximum of Months | 2569.48 | 5516.40 | 2315.36 | 210.15 | 2105.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 417.74 | 3327.03 | 989.38 | 407.13 | 582.25 | 0.00 | 0.00 |
February | 727.36 | 2671.15 | 1311.42 | 576.66 | 734.76 | 0.00 | 0.00 |
March | 1311.83 | 1795.37 | 1781.81 | 707.26 | 1074.56 | 0.00 | 0.00 |
April | 2026.46 | 1290.59 | 2187.90 | 958.15 | 1229.75 | 0.00 | 0.00 |
May | 2985.07 | 777.02 | 2747.82 | 1200.67 | 1547.15 | 0.00 | 0.00 |
June | 3670.39 | 533.25 | 3023.91 | 1316.86 | 1707.04 | 0.00 | 0.00 |
July | 3804.46 | 455.94 | 3056.39 | 1410.29 | 1646.10 | 0.00 | 0.00 |
August | 3209.35 | 537.52 | 2576.48 | 1110.78 | 1465.70 | 0.00 | 0.00 |
September | 2639.47 | 906.89 | 2297.99 | 1085.92 | 1212.07 | 0.00 | 0.00 |
October | 1248.56 | 1376.11 | 1464.44 | 611.68 | 852.75 | 0.00 | 0.00 |
November | 437.26 | 2097.96 | 864.03 | 280.65 | 583.38 | 0.00 | 0.00 |
December | 289.34 | 3027.16 | 669.29 | 287.41 | 381.88 | 0.00 | 0.00 |
Annual Sum or Average | 1903.64 | 1561.19 | 1917.23 | 830.65 | 1086.58 | 0.00 | 0.00 |
Minimum of Months | 289.34 | 455.94 | 669.29 | 280.65 | 381.88 | 0.00 | 0.00 |
Maximum of Months | 3804.46 | 3327.03 | 3056.39 | 1410.29 | 1707.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3687.55 | 4571.55 | 4307.17 | 2947.49 | 1359.68 | 0.00 | 0.00 |
February | 4096.71 | 3772.53 | 4615.06 | 3117.97 | 1497.09 | 0.00 | 0.00 |
March | 3736.40 | 2780.88 | 4016.13 | 2114.76 | 1901.37 | 0.00 | 0.00 |
April | 3778.40 | 2094.10 | 3618.27 | 1691.61 | 1926.66 | 0.00 | 0.00 |
May | 3333.08 | 1278.68 | 2997.61 | 812.69 | 2184.92 | 0.00 | 0.00 |
June | 3619.66 | 860.94 | 2910.23 | 592.54 | 2317.69 | 0.00 | 0.00 |
July | 4010.40 | 737.33 | 3080.68 | 776.25 | 2304.43 | 0.00 | 0.00 |
August | 4579.29 | 886.39 | 3470.90 | 1244.75 | 2226.15 | 0.00 | 0.00 |
September | 5166.23 | 1472.12 | 4206.00 | 2216.22 | 1989.78 | 0.00 | 0.00 |
October | 4687.27 | 2184.47 | 4391.95 | 2755.33 | 1636.62 | 0.00 | 0.00 |
November | 2988.12 | 3082.43 | 3313.72 | 2074.45 | 1239.27 | 0.00 | 0.00 |
December | 3249.56 | 4286.86 | 3533.60 | 2676.66 | 856.94 | 0.00 | 0.00 |
Annual Sum or Average | 3909.78 | 2327.21 | 3699.75 | 1911.55 | 1788.20 | 0.00 | 0.00 |
Minimum of Months | 2988.12 | 737.33 | 2910.23 | 592.54 | 856.94 | 0.00 | 0.00 |
Maximum of Months | 5166.23 | 4571.55 | 4615.06 | 3117.97 | 2317.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 428.87 | 3447.01 | 981.22 | 397.01 | 584.21 | 0.00 | 0.00 |
February | 895.09 | 2826.19 | 1438.79 | 708.99 | 729.80 | 0.00 | 0.00 |
March | 1236.27 | 1898.38 | 1717.61 | 639.05 | 1078.57 | 0.00 | 0.00 |
April | 2474.39 | 1404.55 | 2505.49 | 1238.92 | 1266.57 | 0.00 | 0.00 |
May | 2740.79 | 853.61 | 2512.74 | 1003.78 | 1508.96 | 0.00 | 0.00 |
June | 3592.67 | 602.34 | 2948.40 | 1277.76 | 1670.63 | 0.00 | 0.00 |
July | 3971.03 | 538.79 | 3165.68 | 1503.75 | 1661.93 | 0.00 | 0.00 |
August | 3486.11 | 618.69 | 2767.60 | 1270.15 | 1497.45 | 0.00 | 0.00 |
September | 2584.70 | 984.46 | 2240.30 | 1063.36 | 1176.94 | 0.00 | 0.00 |
October | 1402.60 | 1482.06 | 1561.13 | 694.06 | 867.07 | 0.00 | 0.00 |
November | 549.48 | 2195.59 | 934.44 | 345.56 | 588.88 | 0.00 | 0.00 |
December | 372.75 | 3150.65 | 718.63 | 338.77 | 379.86 | 0.00 | 0.00 |
Annual Sum or Average | 1983.26 | 1661.39 | 1959.75 | 873.60 | 1086.15 | 0.00 | 0.00 |
Minimum of Months | 372.75 | 538.79 | 718.63 | 338.77 | 379.86 | 0.00 | 0.00 |
Maximum of Months | 3971.03 | 3447.01 | 3165.68 | 1503.75 | 1670.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3.27 | 5413.57 | 692.58 | 0.00 | 692.58 | 0.00 | 0.00 |
February | 56.74 | 4333.83 | 878.06 | 0.00 | 878.06 | 0.00 | 0.00 |
March | 414.45 | 2767.03 | 1315.95 | 0.00 | 1315.95 | 0.00 | 0.00 |
April | 842.57 | 1884.23 | 1519.17 | 7.48 | 1511.68 | 0.00 | 0.00 |
May | 1710.49 | 1113.41 | 1981.02 | 74.46 | 1906.56 | 0.00 | 0.00 |
June | 2568.62 | 777.35 | 2315.36 | 210.15 | 2105.21 | 0.00 | 0.00 |
July | 2516.94 | 678.52 | 2171.45 | 145.25 | 2026.20 | 0.00 | 0.00 |
August | 2097.15 | 796.37 | 1818.14 | 32.22 | 1785.92 | 0.00 | 0.00 |
September | 1288.64 | 1340.82 | 1393.99 | 0.35 | 1393.65 | 0.00 | 0.00 |
October | 513.61 | 2011.43 | 1036.46 | 0.00 | 1036.46 | 0.00 | 0.00 |
November | 129.98 | 3186.17 | 725.01 | 0.00 | 725.01 | 0.00 | 0.00 |
December | 1.55 | 4750.42 | 470.29 | 0.00 | 470.29 | 0.00 | 0.00 |
Annual Sum or Average | 1017.71 | 2412.21 | 1362.34 | 39.31 | 1323.03 | 0.00 | 0.00 |
Minimum of Months | 1.55 | 678.52 | 470.29 | 0.00 | 470.29 | 0.00 | 0.00 |
Maximum of Months | 2568.62 | 5413.57 | 2315.36 | 210.15 | 2105.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 423.01 | 3267.48 | 989.38 | 407.13 | 582.25 | 0.00 | 0.00 |
February | 743.64 | 2575.76 | 1311.42 | 576.66 | 734.76 | 0.00 | 0.00 |
March | 1338.25 | 1706.86 | 1781.81 | 707.26 | 1074.56 | 0.00 | 0.00 |
April | 2042.48 | 1217.83 | 2187.90 | 958.15 | 1229.75 | 0.00 | 0.00 |
May | 2989.40 | 751.95 | 2747.82 | 1200.67 | 1547.15 | 0.00 | 0.00 |
June | 3663.58 | 521.34 | 3023.91 | 1316.86 | 1707.04 | 0.00 | 0.00 |
July | 3791.30 | 453.99 | 3056.39 | 1410.29 | 1646.10 | 0.00 | 0.00 |
August | 3201.64 | 531.09 | 2576.48 | 1110.78 | 1465.70 | 0.00 | 0.00 |
September | 2647.45 | 869.65 | 2297.99 | 1085.92 | 1212.07 | 0.00 | 0.00 |
October | 1293.20 | 1271.40 | 1464.44 | 611.68 | 852.75 | 0.00 | 0.00 |
November | 462.64 | 1980.34 | 864.03 | 280.65 | 583.38 | 0.00 | 0.00 |
December | 297.55 | 2933.57 | 669.29 | 287.41 | 381.88 | 0.00 | 0.00 |
Annual Sum or Average | 1914.17 | 1501.93 | 1917.23 | 830.65 | 1086.58 | 0.00 | 0.00 |
Minimum of Months | 297.55 | 453.99 | 669.29 | 280.65 | 381.88 | 0.00 | 0.00 |
Maximum of Months | 3791.30 | 3267.48 | 3056.39 | 1410.29 | 1707.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3709.23 | 4459.34 | 4307.17 | 2947.49 | 1359.68 | 0.00 | 0.00 |
February | 4133.93 | 3611.06 | 4615.06 | 3117.97 | 1497.09 | 0.00 | 0.00 |
March | 3773.93 | 2635.17 | 4016.13 | 2114.76 | 1901.37 | 0.00 | 0.00 |
April | 3800.41 | 1964.63 | 3618.27 | 1691.61 | 1926.66 | 0.00 | 0.00 |
May | 3343.33 | 1227.06 | 2997.61 | 812.69 | 2184.92 | 0.00 | 0.00 |
June | 3614.82 | 835.02 | 2910.23 | 592.54 | 2317.69 | 0.00 | 0.00 |
July | 3996.06 | 728.42 | 3080.68 | 776.25 | 2304.43 | 0.00 | 0.00 |
August | 4568.45 | 869.87 | 3470.90 | 1244.75 | 2226.15 | 0.00 | 0.00 |
September | 5177.96 | 1405.20 | 4206.00 | 2216.22 | 1989.78 | 0.00 | 0.00 |
October | 4742.21 | 2018.15 | 4391.95 | 2755.33 | 1636.62 | 0.00 | 0.00 |
November | 3041.56 | 2891.60 | 3313.72 | 2074.45 | 1239.27 | 0.00 | 0.00 |
December | 3277.17 | 4128.39 | 3533.60 | 2676.66 | 856.94 | 0.00 | 0.00 |
Annual Sum or Average | 3930.18 | 2224.83 | 3699.75 | 1911.55 | 1788.20 | 0.00 | 0.00 |
Minimum of Months | 3041.56 | 728.42 | 2910.23 | 592.54 | 856.94 | 0.00 | 0.00 |
Maximum of Months | 5177.96 | 4459.34 | 4615.06 | 3117.97 | 2317.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 431.77 | 3381.01 | 981.22 | 397.01 | 584.21 | 0.00 | 0.00 |
February | 903.42 | 2734.10 | 1438.79 | 708.99 | 729.80 | 0.00 | 0.00 |
March | 1250.82 | 1815.47 | 1717.61 | 639.05 | 1078.57 | 0.00 | 0.00 |
April | 2483.45 | 1329.53 | 2505.49 | 1238.92 | 1266.57 | 0.00 | 0.00 |
May | 2747.00 | 822.94 | 2512.74 | 1003.78 | 1508.96 | 0.00 | 0.00 |
June | 3587.01 | 587.48 | 2948.40 | 1277.76 | 1670.63 | 0.00 | 0.00 |
July | 3959.81 | 533.12 | 3165.68 | 1503.75 | 1661.93 | 0.00 | 0.00 |
August | 3478.93 | 608.90 | 2767.60 | 1270.15 | 1497.45 | 0.00 | 0.00 |
September | 2593.38 | 944.62 | 2240.30 | 1063.36 | 1176.94 | 0.00 | 0.00 |
October | 1429.40 | 1384.56 | 1561.13 | 694.06 | 867.07 | 0.00 | 0.00 |
November | 566.98 | 2084.80 | 934.44 | 345.56 | 588.88 | 0.00 | 0.00 |
December | 377.30 | 3058.42 | 718.63 | 338.77 | 379.86 | 0.00 | 0.00 |
Annual Sum or Average | 1989.44 | 1601.87 | 1959.75 | 873.60 | 1086.15 | 0.00 | 0.00 |
Minimum of Months | 377.30 | 533.12 | 718.63 | 338.77 | 379.86 | 0.00 | 0.00 |
Maximum of Months | 3959.81 | 3381.01 | 3165.68 | 1503.75 | 1670.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 1768195.66 | 0.156846E+11 | 0.185503E+10 | 0.00 | 0.185503E+10 | 0.00 | 0.00 |
February | 61030984.71 | 0.116829E+11 | 0.212422E+10 | 0.00 | 0.212422E+10 | 0.00 | 0.00 |
March | 0.863601E+09 | 0.859707E+10 | 0.352464E+10 | 0.00 | 0.352464E+10 | 0.00 | 0.00 |
April | 0.192288E+10 | 0.587355E+10 | 0.393770E+10 | 19400859.18 | 0.391830E+10 | 0.00 | 0.00 |
May | 0.443616E+10 | 0.328368E+10 | 0.530599E+10 | 0.199440E+09 | 0.510655E+10 | 0.00 | 0.00 |
June | 0.660441E+10 | 0.219968E+10 | 0.600145E+10 | 0.544709E+09 | 0.545674E+10 | 0.00 | 0.00 |
July | 0.667801E+10 | 0.195358E+10 | 0.581603E+10 | 0.389029E+09 | 0.542700E+10 | 0.00 | 0.00 |
August | 0.554078E+10 | 0.229064E+10 | 0.486972E+10 | 86305065.82 | 0.478342E+10 | 0.00 | 0.00 |
September | 0.317636E+10 | 0.394376E+10 | 0.361324E+10 | 895921.52 | 0.361234E+10 | 0.00 | 0.00 |
October | 0.101891E+10 | 0.659004E+10 | 0.277606E+10 | 0.00 | 0.277606E+10 | 0.00 | 0.00 |
November | 0.192395E+09 | 0.977017E+10 | 0.187924E+10 | 0.00 | 0.187924E+10 | 0.00 | 0.00 |
December | 204.89 | 0.143078E+11 | 0.125962E+10 | 0.00 | 0.125962E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.304963E+11 | 0.861774E+11 | 0.429629E+11 | 0.123978E+10 | 0.417232E+11 | 0.00 | 0.00 |
Minimum of Months | 204.89 | 0.195358E+10 | 0.125962E+10 | 0.00 | 0.125962E+10 | 0.00 | 0.00 |
Maximum of Months | 0.667801E+10 | 0.156846E+11 | 0.600145E+10 | 0.544709E+09 | 0.545674E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.107801E+10 | 0.942833E+10 | 0.264996E+10 | 0.109047E+10 | 0.155949E+10 | 0.00 | 0.00 |
February | 0.170426E+10 | 0.687915E+10 | 0.317259E+10 | 0.139505E+10 | 0.177754E+10 | 0.00 | 0.00 |
March | 0.344237E+10 | 0.514304E+10 | 0.477243E+10 | 0.189432E+10 | 0.287811E+10 | 0.00 | 0.00 |
April | 0.522322E+10 | 0.359116E+10 | 0.567105E+10 | 0.248354E+10 | 0.318752E+10 | 0.00 | 0.00 |
May | 0.803562E+10 | 0.216105E+10 | 0.735980E+10 | 0.321590E+10 | 0.414390E+10 | 0.00 | 0.00 |
June | 0.954377E+10 | 0.143375E+10 | 0.783800E+10 | 0.341333E+10 | 0.442467E+10 | 0.00 | 0.00 |
July | 0.102199E+11 | 0.124482E+10 | 0.818628E+10 | 0.377734E+10 | 0.440894E+10 | 0.00 | 0.00 |
August | 0.863608E+10 | 0.142536E+10 | 0.690088E+10 | 0.297512E+10 | 0.392576E+10 | 0.00 | 0.00 |
September | 0.683981E+10 | 0.247452E+10 | 0.595642E+10 | 0.281472E+10 | 0.314170E+10 | 0.00 | 0.00 |
October | 0.324762E+10 | 0.399413E+10 | 0.392237E+10 | 0.163834E+10 | 0.228402E+10 | 0.00 | 0.00 |
November | 0.105943E+10 | 0.589916E+10 | 0.223958E+10 | 0.727457E+09 | 0.151212E+10 | 0.00 | 0.00 |
December | 0.731523E+09 | 0.868317E+10 | 0.179262E+10 | 0.769797E+09 | 0.102283E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.597616E+11 | 0.523577E+11 | 0.604620E+11 | 0.261954E+11 | 0.342666E+11 | 0.00 | 0.00 |
Minimum of Months | 0.731523E+09 | 0.124482E+10 | 0.179262E+10 | 0.727457E+09 | 0.102283E+10 | 0.00 | 0.00 |
Maximum of Months | 0.102199E+11 | 0.942833E+10 | 0.818628E+10 | 0.377734E+10 | 0.442467E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.988219E+10 | 0.126487E+11 | 0.115364E+11 | 0.789459E+10 | 0.364178E+10 | 0.00 | 0.00 |
February | 0.993911E+10 | 0.941001E+10 | 0.111648E+11 | 0.754302E+10 | 0.362177E+10 | 0.00 | 0.00 |
March | 0.100326E+11 | 0.773473E+10 | 0.107569E+11 | 0.566420E+10 | 0.509265E+10 | 0.00 | 0.00 |
April | 0.981035E+10 | 0.570659E+10 | 0.937859E+10 | 0.438468E+10 | 0.499391E+10 | 0.00 | 0.00 |
May | 0.897067E+10 | 0.351552E+10 | 0.802884E+10 | 0.217673E+10 | 0.585211E+10 | 0.00 | 0.00 |
June | 0.938287E+10 | 0.232450E+10 | 0.754333E+10 | 0.153587E+10 | 0.600747E+10 | 0.00 | 0.00 |
July | 0.107265E+11 | 0.205070E+10 | 0.825133E+10 | 0.207912E+10 | 0.617221E+10 | 0.00 | 0.00 |
August | 0.122957E+11 | 0.241851E+10 | 0.929650E+10 | 0.333395E+10 | 0.596255E+10 | 0.00 | 0.00 |
September | 0.134576E+11 | 0.390823E+10 | 0.109020E+11 | 0.574446E+10 | 0.515754E+10 | 0.00 | 0.00 |
October | 0.126045E+11 | 0.604068E+10 | 0.117634E+11 | 0.737991E+10 | 0.438354E+10 | 0.00 | 0.00 |
November | 0.772944E+10 | 0.833544E+10 | 0.858919E+10 | 0.537700E+10 | 0.321220E+10 | 0.00 | 0.00 |
December | 0.867471E+10 | 0.119885E+11 | 0.946443E+10 | 0.716920E+10 | 0.229524E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.123506E+12 | 0.760821E+11 | 0.116676E+12 | 0.602827E+11 | 0.563930E+11 | 0.00 | 0.00 |
Minimum of Months | 0.772944E+10 | 0.205070E+10 | 0.754333E+10 | 0.153587E+10 | 0.229524E+10 | 0.00 | 0.00 |
Maximum of Months | 0.134576E+11 | 0.126487E+11 | 0.117634E+11 | 0.789459E+10 | 0.617221E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.110074E+10 | 0.990814E+10 | 0.262811E+10 | 0.106337E+10 | 0.156475E+10 | 0.00 | 0.00 |
February | 0.208192E+10 | 0.748992E+10 | 0.348073E+10 | 0.171520E+10 | 0.176553E+10 | 0.00 | 0.00 |
March | 0.312686E+10 | 0.582457E+10 | 0.460048E+10 | 0.171163E+10 | 0.288885E+10 | 0.00 | 0.00 |
April | 0.626137E+10 | 0.430065E+10 | 0.649425E+10 | 0.321129E+10 | 0.328296E+10 | 0.00 | 0.00 |
May | 0.726896E+10 | 0.246928E+10 | 0.673014E+10 | 0.268853E+10 | 0.404161E+10 | 0.00 | 0.00 |
June | 0.923876E+10 | 0.173437E+10 | 0.764228E+10 | 0.331198E+10 | 0.433030E+10 | 0.00 | 0.00 |
July | 0.105475E+11 | 0.158025E+10 | 0.847900E+10 | 0.402766E+10 | 0.445134E+10 | 0.00 | 0.00 |
August | 0.921977E+10 | 0.186671E+10 | 0.741278E+10 | 0.340198E+10 | 0.401080E+10 | 0.00 | 0.00 |
September | 0.662128E+10 | 0.278014E+10 | 0.580687E+10 | 0.275624E+10 | 0.305063E+10 | 0.00 | 0.00 |
October | 0.357735E+10 | 0.454938E+10 | 0.418135E+10 | 0.185898E+10 | 0.232237E+10 | 0.00 | 0.00 |
November | 0.129571E+10 | 0.660221E+10 | 0.242208E+10 | 0.895683E+09 | 0.152640E+10 | 0.00 | 0.00 |
December | 0.916436E+09 | 0.962429E+10 | 0.192479E+10 | 0.907376E+09 | 0.101742E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.612566E+11 | 0.587299E+11 | 0.618029E+11 | 0.275499E+11 | 0.342529E+11 | 0.00 | 0.00 |
Minimum of Months | 0.916436E+09 | 0.158025E+10 | 0.192479E+10 | 0.895683E+09 | 0.101742E+10 | 0.00 | 0.00 |
Maximum of Months | 0.105475E+11 | 0.990814E+10 | 0.847900E+10 | 0.402766E+10 | 0.445134E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 7014468.58 | 0.147751E+11 | 0.185502E+10 | 0.00 | 0.185502E+10 | 0.00 | 0.00 |
February | 0.113208E+09 | 0.108576E+11 | 0.212421E+10 | 0.00 | 0.212421E+10 | 0.00 | 0.00 |
March | 0.102724E+10 | 0.780788E+10 | 0.352463E+10 | 0.00 | 0.352463E+10 | 0.00 | 0.00 |
April | 0.209974E+10 | 0.523921E+10 | 0.393768E+10 | 19400790.29 | 0.391828E+10 | 0.00 | 0.00 |
May | 0.451533E+10 | 0.311435E+10 | 0.530598E+10 | 0.199439E+09 | 0.510654E+10 | 0.00 | 0.00 |
June | 0.666009E+10 | 0.207753E+10 | 0.600142E+10 | 0.544707E+09 | 0.545672E+10 | 0.00 | 0.00 |
July | 0.677255E+10 | 0.183903E+10 | 0.581601E+10 | 0.389027E+09 | 0.542698E+10 | 0.00 | 0.00 |
August | 0.562513E+10 | 0.217714E+10 | 0.486970E+10 | 86304759.35 | 0.478340E+10 | 0.00 | 0.00 |
September | 0.327409E+10 | 0.367794E+10 | 0.361322E+10 | 895918.34 | 0.361233E+10 | 0.00 | 0.00 |
October | 0.121361E+10 | 0.589780E+10 | 0.277605E+10 | 0.00 | 0.277605E+10 | 0.00 | 0.00 |
November | 0.271604E+09 | 0.878026E+10 | 0.187923E+10 | 0.00 | 0.187923E+10 | 0.00 | 0.00 |
December | 842734.89 | 0.131288E+11 | 0.125962E+10 | 0.00 | 0.125962E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.315805E+11 | 0.793726E+11 | 0.429628E+11 | 0.123978E+10 | 0.417230E+11 | 0.00 | 0.00 |
Minimum of Months | 842734.89 | 0.183903E+10 | 0.125962E+10 | 0.00 | 0.125962E+10 | 0.00 | 0.00 |
Maximum of Months | 0.677255E+10 | 0.147751E+11 | 0.600142E+10 | 0.544707E+09 | 0.545672E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.111888E+10 | 0.891113E+10 | 0.264995E+10 | 0.109046E+10 | 0.155949E+10 | 0.00 | 0.00 |
February | 0.175964E+10 | 0.646204E+10 | 0.317258E+10 | 0.139505E+10 | 0.177753E+10 | 0.00 | 0.00 |
March | 0.351360E+10 | 0.480871E+10 | 0.477241E+10 | 0.189431E+10 | 0.287810E+10 | 0.00 | 0.00 |
April | 0.525257E+10 | 0.334520E+10 | 0.567103E+10 | 0.248353E+10 | 0.318750E+10 | 0.00 | 0.00 |
May | 0.799522E+10 | 0.208118E+10 | 0.735977E+10 | 0.321589E+10 | 0.414388E+10 | 0.00 | 0.00 |
June | 0.951366E+10 | 0.138217E+10 | 0.783796E+10 | 0.341331E+10 | 0.442465E+10 | 0.00 | 0.00 |
July | 0.101899E+11 | 0.122119E+10 | 0.818625E+10 | 0.377732E+10 | 0.440893E+10 | 0.00 | 0.00 |
August | 0.859591E+10 | 0.143969E+10 | 0.690085E+10 | 0.297511E+10 | 0.392574E+10 | 0.00 | 0.00 |
September | 0.684150E+10 | 0.235066E+10 | 0.595639E+10 | 0.281471E+10 | 0.314169E+10 | 0.00 | 0.00 |
October | 0.334414E+10 | 0.368577E+10 | 0.392235E+10 | 0.163834E+10 | 0.228401E+10 | 0.00 | 0.00 |
November | 0.113337E+10 | 0.543790E+10 | 0.223957E+10 | 0.727454E+09 | 0.151212E+10 | 0.00 | 0.00 |
December | 0.774972E+09 | 0.810794E+10 | 0.179262E+10 | 0.769794E+09 | 0.102282E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.600333E+11 | 0.492336E+11 | 0.604617E+11 | 0.261953E+11 | 0.342665E+11 | 0.00 | 0.00 |
Minimum of Months | 0.774972E+09 | 0.122119E+10 | 0.179262E+10 | 0.727454E+09 | 0.102282E+10 | 0.00 | 0.00 |
Maximum of Months | 0.101899E+11 | 0.891113E+10 | 0.818625E+10 | 0.377732E+10 | 0.442465E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.987672E+10 | 0.122444E+11 | 0.115363E+11 | 0.789456E+10 | 0.364177E+10 | 0.00 | 0.00 |
February | 0.991077E+10 | 0.912652E+10 | 0.111647E+11 | 0.754299E+10 | 0.362175E+10 | 0.00 | 0.00 |
March | 0.100076E+11 | 0.744832E+10 | 0.107568E+11 | 0.566418E+10 | 0.509263E+10 | 0.00 | 0.00 |
April | 0.979363E+10 | 0.542792E+10 | 0.937855E+10 | 0.438466E+10 | 0.499390E+10 | 0.00 | 0.00 |
May | 0.892732E+10 | 0.342482E+10 | 0.802881E+10 | 0.217672E+10 | 0.585209E+10 | 0.00 | 0.00 |
June | 0.938217E+10 | 0.223156E+10 | 0.754331E+10 | 0.153586E+10 | 0.600745E+10 | 0.00 | 0.00 |
July | 0.107414E+11 | 0.197487E+10 | 0.825130E+10 | 0.207911E+10 | 0.617219E+10 | 0.00 | 0.00 |
August | 0.122652E+11 | 0.237411E+10 | 0.929647E+10 | 0.333394E+10 | 0.596253E+10 | 0.00 | 0.00 |
September | 0.133909E+11 | 0.381573E+10 | 0.109020E+11 | 0.574444E+10 | 0.515752E+10 | 0.00 | 0.00 |
October | 0.125544E+11 | 0.585090E+10 | 0.117634E+11 | 0.737988E+10 | 0.438352E+10 | 0.00 | 0.00 |
November | 0.774522E+10 | 0.798966E+10 | 0.858916E+10 | 0.537698E+10 | 0.321218E+10 | 0.00 | 0.00 |
December | 0.870361E+10 | 0.114819E+11 | 0.946440E+10 | 0.716917E+10 | 0.229523E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.123299E+12 | 0.733908E+11 | 0.116675E+12 | 0.602825E+11 | 0.563928E+11 | 0.00 | 0.00 |
Minimum of Months | 0.774522E+10 | 0.197487E+10 | 0.754331E+10 | 0.153586E+10 | 0.229523E+10 | 0.00 | 0.00 |
Maximum of Months | 0.133909E+11 | 0.122444E+11 | 0.117634E+11 | 0.789456E+10 | 0.617219E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.114868E+10 | 0.923247E+10 | 0.262810E+10 | 0.106336E+10 | 0.156474E+10 | 0.00 | 0.00 |
February | 0.216540E+10 | 0.683712E+10 | 0.348071E+10 | 0.171519E+10 | 0.176552E+10 | 0.00 | 0.00 |
March | 0.331123E+10 | 0.508462E+10 | 0.460046E+10 | 0.171162E+10 | 0.288883E+10 | 0.00 | 0.00 |
April | 0.641363E+10 | 0.364060E+10 | 0.649422E+10 | 0.321128E+10 | 0.328294E+10 | 0.00 | 0.00 |
May | 0.734092E+10 | 0.228632E+10 | 0.673011E+10 | 0.268852E+10 | 0.404159E+10 | 0.00 | 0.00 |
June | 0.931219E+10 | 0.156126E+10 | 0.764225E+10 | 0.331196E+10 | 0.433028E+10 | 0.00 | 0.00 |
July | 0.106360E+11 | 0.144311E+10 | 0.847896E+10 | 0.402764E+10 | 0.445132E+10 | 0.00 | 0.00 |
August | 0.933718E+10 | 0.165711E+10 | 0.741275E+10 | 0.340197E+10 | 0.401078E+10 | 0.00 | 0.00 |
September | 0.669953E+10 | 0.255172E+10 | 0.580685E+10 | 0.275623E+10 | 0.305062E+10 | 0.00 | 0.00 |
October | 0.375672E+10 | 0.396954E+10 | 0.418133E+10 | 0.185897E+10 | 0.232236E+10 | 0.00 | 0.00 |
November | 0.142426E+10 | 0.569096E+10 | 0.242207E+10 | 0.895679E+09 | 0.152639E+10 | 0.00 | 0.00 |
December | 0.998363E+09 | 0.843870E+10 | 0.192479E+10 | 0.907372E+09 | 0.101741E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.625441E+11 | 0.523935E+11 | 0.618026E+11 | 0.275498E+11 | 0.342528E+11 | 0.00 | 0.00 |
Minimum of Months | 0.998363E+09 | 0.144311E+10 | 0.192479E+10 | 0.895679E+09 | 0.101741E+10 | 0.00 | 0.00 |
Maximum of Months | 0.106360E+11 | 0.923247E+10 | 0.847896E+10 | 0.402764E+10 | 0.445132E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 8768660.64 | 0.144997E+11 | 0.185502E+10 | 0.00 | 0.185502E+10 | 0.00 | 0.00 |
February | 0.137269E+09 | 0.104844E+11 | 0.212421E+10 | 0.00 | 0.212421E+10 | 0.00 | 0.00 |
March | 0.111007E+10 | 0.741120E+10 | 0.352463E+10 | 0.00 | 0.352463E+10 | 0.00 | 0.00 |
April | 0.218394E+10 | 0.488393E+10 | 0.393768E+10 | 19400790.29 | 0.391828E+10 | 0.00 | 0.00 |
May | 0.458138E+10 | 0.298217E+10 | 0.530598E+10 | 0.199439E+09 | 0.510654E+10 | 0.00 | 0.00 |
June | 0.665787E+10 | 0.201489E+10 | 0.600142E+10 | 0.544707E+09 | 0.545672E+10 | 0.00 | 0.00 |
July | 0.674138E+10 | 0.181735E+10 | 0.581601E+10 | 0.389027E+09 | 0.542698E+10 | 0.00 | 0.00 |
August | 0.561701E+10 | 0.213299E+10 | 0.486970E+10 | 86304759.35 | 0.478340E+10 | 0.00 | 0.00 |
September | 0.334016E+10 | 0.347542E+10 | 0.361322E+10 | 895918.34 | 0.361233E+10 | 0.00 | 0.00 |
October | 0.137565E+10 | 0.538741E+10 | 0.277605E+10 | 0.00 | 0.277605E+10 | 0.00 | 0.00 |
November | 0.336921E+09 | 0.825855E+10 | 0.187923E+10 | 0.00 | 0.187923E+10 | 0.00 | 0.00 |
December | 4161876.18 | 0.127235E+11 | 0.125962E+10 | 0.00 | 0.125962E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.320946E+11 | 0.760715E+11 | 0.429628E+11 | 0.123978E+10 | 0.417230E+11 | 0.00 | 0.00 |
Minimum of Months | 4161876.18 | 0.181735E+10 | 0.125962E+10 | 0.00 | 0.125962E+10 | 0.00 | 0.00 |
Maximum of Months | 0.674138E+10 | 0.144997E+11 | 0.600142E+10 | 0.544707E+09 | 0.545672E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.113298E+10 | 0.875162E+10 | 0.264995E+10 | 0.109046E+10 | 0.155949E+10 | 0.00 | 0.00 |
February | 0.179900E+10 | 0.623128E+10 | 0.317258E+10 | 0.139505E+10 | 0.177753E+10 | 0.00 | 0.00 |
March | 0.358438E+10 | 0.457166E+10 | 0.477241E+10 | 0.189431E+10 | 0.287810E+10 | 0.00 | 0.00 |
April | 0.529410E+10 | 0.315662E+10 | 0.567103E+10 | 0.248353E+10 | 0.318750E+10 | 0.00 | 0.00 |
May | 0.800681E+10 | 0.201403E+10 | 0.735977E+10 | 0.321589E+10 | 0.414388E+10 | 0.00 | 0.00 |
June | 0.949599E+10 | 0.135130E+10 | 0.783796E+10 | 0.341331E+10 | 0.442465E+10 | 0.00 | 0.00 |
July | 0.101546E+11 | 0.121598E+10 | 0.818625E+10 | 0.377732E+10 | 0.440893E+10 | 0.00 | 0.00 |
August | 0.857527E+10 | 0.142248E+10 | 0.690085E+10 | 0.297511E+10 | 0.392574E+10 | 0.00 | 0.00 |
September | 0.686218E+10 | 0.225413E+10 | 0.595639E+10 | 0.281471E+10 | 0.314169E+10 | 0.00 | 0.00 |
October | 0.346372E+10 | 0.340532E+10 | 0.392235E+10 | 0.163834E+10 | 0.228401E+10 | 0.00 | 0.00 |
November | 0.119916E+10 | 0.513304E+10 | 0.223957E+10 | 0.727454E+09 | 0.151212E+10 | 0.00 | 0.00 |
December | 0.796961E+09 | 0.785727E+10 | 0.179262E+10 | 0.769794E+09 | 0.102282E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.603652E+11 | 0.473647E+11 | 0.604617E+11 | 0.261953E+11 | 0.342665E+11 | 0.00 | 0.00 |
Minimum of Months | 0.796961E+09 | 0.121598E+10 | 0.179262E+10 | 0.727454E+09 | 0.102282E+10 | 0.00 | 0.00 |
Maximum of Months | 0.101546E+11 | 0.875162E+10 | 0.818625E+10 | 0.377732E+10 | 0.442465E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.993480E+10 | 0.119439E+11 | 0.115363E+11 | 0.789456E+10 | 0.364177E+10 | 0.00 | 0.00 |
February | 0.100008E+11 | 0.873587E+10 | 0.111647E+11 | 0.754299E+10 | 0.362175E+10 | 0.00 | 0.00 |
March | 0.101081E+11 | 0.705804E+10 | 0.107568E+11 | 0.566418E+10 | 0.509263E+10 | 0.00 | 0.00 |
April | 0.985067E+10 | 0.509231E+10 | 0.937855E+10 | 0.438466E+10 | 0.499390E+10 | 0.00 | 0.00 |
May | 0.895477E+10 | 0.328656E+10 | 0.802881E+10 | 0.217672E+10 | 0.585209E+10 | 0.00 | 0.00 |
June | 0.936961E+10 | 0.216438E+10 | 0.754331E+10 | 0.153586E+10 | 0.600745E+10 | 0.00 | 0.00 |
July | 0.107031E+11 | 0.195101E+10 | 0.825130E+10 | 0.207911E+10 | 0.617219E+10 | 0.00 | 0.00 |
August | 0.122361E+11 | 0.232986E+10 | 0.929647E+10 | 0.333394E+10 | 0.596253E+10 | 0.00 | 0.00 |
September | 0.134213E+11 | 0.364228E+10 | 0.109020E+11 | 0.574444E+10 | 0.515752E+10 | 0.00 | 0.00 |
October | 0.127015E+11 | 0.540540E+10 | 0.117634E+11 | 0.737988E+10 | 0.438352E+10 | 0.00 | 0.00 |
November | 0.788373E+10 | 0.749502E+10 | 0.858916E+10 | 0.537698E+10 | 0.321218E+10 | 0.00 | 0.00 |
December | 0.877756E+10 | 0.110575E+11 | 0.946440E+10 | 0.716917E+10 | 0.229523E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.123942E+12 | 0.701621E+11 | 0.116675E+12 | 0.602825E+11 | 0.563928E+11 | 0.00 | 0.00 |
Minimum of Months | 0.788373E+10 | 0.195101E+10 | 0.754331E+10 | 0.153586E+10 | 0.229523E+10 | 0.00 | 0.00 |
Maximum of Months | 0.134213E+11 | 0.119439E+11 | 0.117634E+11 | 0.789456E+10 | 0.617219E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.115646E+10 | 0.905569E+10 | 0.262810E+10 | 0.106336E+10 | 0.156474E+10 | 0.00 | 0.00 |
February | 0.218556E+10 | 0.661433E+10 | 0.348071E+10 | 0.171519E+10 | 0.176552E+10 | 0.00 | 0.00 |
March | 0.335019E+10 | 0.486255E+10 | 0.460046E+10 | 0.171162E+10 | 0.288883E+10 | 0.00 | 0.00 |
April | 0.643710E+10 | 0.344614E+10 | 0.649422E+10 | 0.321128E+10 | 0.328294E+10 | 0.00 | 0.00 |
May | 0.735756E+10 | 0.220417E+10 | 0.673011E+10 | 0.268852E+10 | 0.404159E+10 | 0.00 | 0.00 |
June | 0.929752E+10 | 0.152275E+10 | 0.764225E+10 | 0.331196E+10 | 0.433028E+10 | 0.00 | 0.00 |
July | 0.106060E+11 | 0.142791E+10 | 0.847896E+10 | 0.402764E+10 | 0.445132E+10 | 0.00 | 0.00 |
August | 0.931796E+10 | 0.163086E+10 | 0.741275E+10 | 0.340197E+10 | 0.401078E+10 | 0.00 | 0.00 |
September | 0.672205E+10 | 0.244845E+10 | 0.580685E+10 | 0.275623E+10 | 0.305062E+10 | 0.00 | 0.00 |
October | 0.382851E+10 | 0.370840E+10 | 0.418133E+10 | 0.185897E+10 | 0.232236E+10 | 0.00 | 0.00 |
November | 0.146961E+10 | 0.540379E+10 | 0.242207E+10 | 0.895679E+09 | 0.152639E+10 | 0.00 | 0.00 |
December | 0.101055E+10 | 0.819167E+10 | 0.192479E+10 | 0.907372E+09 | 0.101741E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.627390E+11 | 0.505167E+11 | 0.618026E+11 | 0.275498E+11 | 0.342528E+11 | 0.00 | 0.00 |
Minimum of Months | 0.101055E+10 | 0.142791E+10 | 0.192479E+10 | 0.895679E+09 | 0.101741E+10 | 0.00 | 0.00 |
Maximum of Months | 0.106060E+11 | 0.905569E+10 | 0.847896E+10 | 0.402764E+10 | 0.445132E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -12.6 | -13.1 | -15.2 | 6.10 | -26.1 | 37.55 | 107.22 | 0.02 |
February | -7.7 | -8.6 | -10.9 | 6.39 | -21.3 | 45.57 | 135.04 | 0.00 |
March | 0.33 | -1.4 | -4.2 | 6.99 | -10.6 | 74.69 | 127.11 | 0.00 |
April | 7.02 | 4.40 | 1.63 | 6.38 | -3.6 | 77.59 | 184.47 | 0.02 |
May | 14.19 | 11.30 | 8.94 | 5.14 | 4.70 | 102.33 | 182.89 | 0.00 |
June | 19.16 | 15.71 | 13.79 | 4.87 | 8.84 | 110.26 | 213.51 | 0.04 |
July | 20.92 | 17.87 | 16.31 | 4.22 | 9.95 | 102.99 | 231.93 | 0.03 |
August | 20.05 | 17.00 | 15.28 | 4.97 | 11.01 | 95.97 | 190.14 | 0.00 |
September | 15.39 | 11.24 | 8.10 | 4.97 | 3.18 | 72.67 | 177.74 | 0.01 |
October | 7.43 | 4.69 | 1.56 | 5.55 | -3.9 | 55.50 | 131.91 | 0.00 |
November | -0.0 | -1.5 | -3.9 | 6.30 | -10.9 | 41.35 | 79.05 | 0.00 |
December | -7.6 | -8.4 | -10.6 | 6.09 | -20.0 | 22.97 | 92.59 | 0.00 |
Annual Sum or Average | 6.46 | 4.16 | 1.81 | 5.66 | -4.8 | 70.09 | 154.52 | 0.01 |
Minimum of Months | -12.6 | -13.1 | -15.2 | 4.22 | -26.1 | 22.97 | 79.05 | 0.00 |
Maximum of Months | 20.92 | 17.87 | 16.31 | 6.99 | 11.01 | 110.26 | 231.93 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 6.10 | 17-JAN-23:19 | 3.74 | 0.93 | 10.63 | -0.4 | 0.00 | 0.00 |
February | 8.30 | 24-FEB-14:00 | 5.62 | 2.80 | 5.20 | -7.3 | 71.00 | 794.50 |
March | 18.90 | 19-MAR-15:00 | 13.93 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 30.00 | 15-APR-15:20 | 19.12 | 13.53 | 12.70 | 15.70 | 115.83 | 790.83 |
May | 30.00 | 31-MAY-12:00 | 19.70 | 14.40 | 6.20 | 19.52 | 251.00 | 580.50 |
June | 33.30 | 11-JUN-14:00 | 24.81 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 30.00 | 26-JUL-15:20 | 25.67 | 24.23 | 5.13 | 20.98 | 260.33 | 436.00 |
August | 33.90 | 04-AUG-14:00 | 25.31 | 22.20 | 4.60 | 23.82 | 194.50 | 612.00 |
September | 32.20 | 06-SEP-13:00 | 21.19 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 23.30 | 20-OCT-14:00 | 13.36 | 5.60 | 7.20 | 7.35 | 55.00 | 745.50 |
November | 16.10 | 03-NOV-13:00 | 10.47 | 5.60 | 6.70 | 0.51 | 82.00 | 691.00 |
December | 7.20 | 02-DEC-13:00 | 3.94 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 3.74 | 0.00 | 4.60 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 33.90 | 25.67 | 24.23 | 12.70 | 24.50 | 281.00 | 794.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -31.1 | 31-JAN-03:00 | -31.3 | -34.4 | 4.60 | -46.7 | 0.00 | 0.00 |
February | -36.7 | 02-FEB-05:00 | -36.8 | -40.2 | 3.10 | -59.6 | 0.00 | 0.00 |
March | -17.2 | 06-MAR-00:00 | -17.6 | -20.0 | 5.20 | -36.8 | 0.00 | 0.00 |
April | -7.2 | 03-APR-05:19 | -8.0 | -9.8 | 7.37 | -15.9 | 0.00 | 0.00 |
May | 0.60 | 03-MAY-02:00 | -0.1 | -1.1 | 1.50 | -15.5 | 0.00 | 0.00 |
June | 5.00 | 01-JUN-04:00 | 5.00 | 5.00 | 3.10 | -7.8 | 30.50 | 132.50 |
July | 10.00 | 23-JUL-03:00 | 9.66 | 9.40 | 2.60 | -4.3 | 0.00 | 0.00 |
August | 8.30 | 07-AUG-03:00 | 7.41 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
September | -1.1 | 30-SEP-00:00 | -2.4 | -4.4 | 4.10 | -17.8 | 0.00 | 0.00 |
October | -3.3 | 23-OCT-05:00 | -4.2 | -6.1 | 3.60 | -19.1 | 0.00 | 0.00 |
November | -28.9 | 26-NOV-06:00 | -29.0 | -30.6 | 1.50 | -50.2 | 0.00 | 0.00 |
December | -22.8 | 09-DEC-00:20 | -23.0 | -25.0 | 13.40 | -37.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -36.7 | -36.8 | -40.2 | 1.50 | -59.6 | 0.00 | 0.00 | |
Maximum of Months | 10.00 | 9.66 | 9.40 | 13.40 | -3.2 | 30.50 | 132.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 5.88 | 24-FEB-15:00 | 8.30 | 3.30 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 13.93 | 19-MAR-15:00 | 18.90 | 10.60 | 8.80 | 7.95 | 139.50 | 237.50 |
April | 20.94 | 18-APR-11:00 | 27.80 | 17.80 | 13.90 | 17.57 | 334.00 | 447.00 |
May | 19.93 | 29-MAY-13:00 | 23.30 | 18.30 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 24.81 | 11-JUN-14:00 | 33.30 | 21.70 | 10.30 | 24.50 | 281.00 | 458.50 |
July | 26.15 | 26-JUL-18:00 | 27.80 | 25.60 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 26.64 | 04-AUG-12:00 | 31.70 | 25.00 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 21.19 | 06-SEP-13:00 | 32.20 | 16.10 | 6.20 | 18.28 | 135.00 | 769.00 |
October | 14.84 | 02-OCT-14:00 | 18.30 | 12.80 | 3.60 | 12.41 | 202.00 | 164.00 |
November | 13.04 | 09-NOV-04:00 | 15.00 | 11.70 | 10.30 | 10.88 | 0.00 | 0.00 |
December | 3.94 | 02-DEC-13:00 | 7.20 | 0.00 | 7.70 | -3.9 | 75.00 | 301.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 3.94 | 5.60 | 0.00 | 3.10 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 26.64 | 33.30 | 25.60 | 13.90 | 25.66 | 379.00 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.60 | 18-JAN-00:00 | 5.60 | 5.60 | 7.70 | 0.30 | 0.00 | 0.00 |
February | 3.30 | 24-FEB-15:00 | 8.30 | 5.88 | 5.70 | -7.3 | 54.50 | 665.50 |
March | 11.10 | 26-MAR-05:00 | 13.30 | 12.04 | 8.20 | 9.13 | 0.00 | 0.00 |
April | 18.30 | 18-APR-09:00 | 25.60 | 20.52 | 14.40 | 15.57 | 196.00 | 741.50 |
May | 18.30 | 29-MAY-13:00 | 23.30 | 19.93 | 6.20 | 20.75 | 379.00 | 52.00 |
June | 22.20 | 13-JUN-11:00 | 26.70 | 23.35 | 8.80 | 16.85 | 273.50 | 600.50 |
July | 25.60 | 26-JUL-18:00 | 27.80 | 26.15 | 3.10 | 19.35 | 33.50 | 51.00 |
August | 25.00 | 04-AUG-12:00 | 31.70 | 26.64 | 4.60 | 25.66 | 235.00 | 593.50 |
September | 18.30 | 12-SEP-02:00 | 18.90 | 18.46 | 5.70 | 14.28 | 0.00 | 0.00 |
October | 12.80 | 02-OCT-13:00 | 17.40 | 14.50 | 3.40 | 11.65 | 249.50 | 141.50 |
November | 11.70 | 08-NOV-10:00 | 13.90 | 12.62 | 7.20 | 9.91 | 158.00 | 0.50 |
December | 0.00 | 02-DEC-11:00 | 5.00 | 2.79 | 7.20 | -8.3 | 115.50 | 562.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 5.00 | 2.79 | 3.10 | -8.3 | 0.00 | 0.00 | |
Maximum of Months | 25.60 | 31.70 | 26.64 | 14.40 | 25.66 | 379.00 | 741.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 4.29 | 14.52 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 3.18 | 19.75 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 3.75 | 28.43 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 5.88 | 38.20 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.06 | 44.89 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.40 | 51.07 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.02 | 51.61 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.22 | 43.31 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.63 | 34.41 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.44 | 22.83 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.25 | 13.98 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 6.92 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 9.71 | 31.16 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 3.18 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.22 | 51.61 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.447805E+11 | -0.443323E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -448209719.5 | 60.05 | 0.00 | 0.00 |
February | 0.414864E+11 | -0.410826E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -403791703.9 | 60.05 | 0.00 | 0.00 |
March | 0.482992E+11 | -0.478530E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -446228769.2 | 60.05 | 0.00 | 0.00 |
April | 0.421776E+11 | -0.417478E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -429893576.2 | 60.05 | 0.00 | 0.00 |
May | 0.424447E+11 | -0.420023E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -442354732.1 | 60.05 | 0.00 | 0.00 |
June | 0.392943E+11 | -0.388760E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -418332751.4 | 60.05 | 0.00 | 0.00 |
July | 0.353438E+11 | -0.349195E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -424286471.7 | 60.05 | 0.00 | 0.00 |
August | 0.376825E+11 | -0.372479E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -434662268.8 | 60.05 | 0.00 | 0.00 |
September | 0.346632E+11 | -0.342388E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -424401640.1 | 60.05 | 0.00 | 0.00 |
October | 0.375060E+11 | -0.370647E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -441326756.7 | 60.05 | 0.00 | 0.00 |
November | 0.392651E+11 | -0.388366E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -428425957.6 | 60.05 | 0.00 | 0.00 |
December | 0.416638E+11 | -0.412190E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -444779246.5 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.484607E+12 | -0.479420E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.518669E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.346632E+11 | -0.478530E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -448209719.5 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.482992E+11 | -0.342388E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -403791703.9 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.50 | 0.48 | 01-JAN-09:39 | 7570.71 | 37.78 | 207.00 | 246.50 | 6192.03 | 38.38 | 212.50 | 223.17 |
February | 226.83 | 0.50 | 0.48 | 01-FEB-08:09 | 8960.92 | 37.94 | 225.00 | 256.17 | 2468.89 | 27.74 | 198.50 | 234.00 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-07:00 | 8195.58 | 31.14 | 285.00 | 329.50 | 1549.77 | 22.79 | 248.17 | 297.00 |
April | 285.17 | 0.51 | 0.48 | 01-APR-07:19 | 2501.97 | 20.99 | 143.17 | 348.83 | 1468.26 | 22.39 | 218.17 | 308.50 |
May | 428.67 | 0.51 | 0.48 | 01-MAY-06:49 | 1942.38 | 20.59 | 171.17 | 399.33 | 1072.58 | 21.98 | 290.83 | 357.00 |
June | 400.67 | 0.51 | 0.48 | 01-JUN-05:49 | 1988.62 | 20.78 | 184.00 | 401.17 | 1115.46 | 22.20 | 306.33 | 362.00 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-05:00 | 2062.98 | 21.08 | 201.67 | 411.17 | 1167.38 | 22.49 | 317.00 | 371.33 |
August | 410.83 | 0.51 | 0.48 | 01-AUG-06:19 | 2273.24 | 21.02 | 219.00 | 382.33 | 1258.46 | 22.42 | 303.83 | 349.83 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:30 | 3269.48 | 22.69 | 188.00 | 335.50 | 1580.11 | 22.95 | 266.83 | 306.50 |
October | 325.17 | 0.50 | 0.48 | 01-OCT-06:49 | 7730.02 | 33.80 | 296.33 | 307.33 | 2046.30 | 24.18 | 242.50 | 285.83 |
November | 254.83 | 0.50 | 0.48 | 01-NOV-07:49 | 5415.63 | 33.37 | 241.00 | 249.17 | 2911.06 | 31.55 | 241.00 | 228.67 |
December | 186.17 | 0.50 | 0.48 | 01-DEC-07:00 | 6640.26 | 38.76 | 184.00 | 225.33 | 5990.63 | 39.93 | 184.50 | 189.33 |
Annual Sum or Average | 3807.33 | 0.50 | 4392.12 | 26.72 | 2545.33 | 3892.33 | 2040.38 | 25.26 | 3030.17 | 3513.17 | ||
Minimum of Months | 186.17 | 0.50 | 0.48 | 1942.38 | 20.59 | 143.17 | 225.33 | 1072.58 | 21.98 | 184.50 | 189.33 | |
Maximum of Months | 428.67 | 0.51 | 0.48 | 8960.92 | 38.76 | 296.33 | 411.17 | 6192.03 | 39.93 | 317.00 | 371.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.52 | 0.48 | 01-JAN-09:39 | 2027.97 | 24.41 | 100.50 | 233.67 | 1024.84 | 24.18 | 140.17 | 194.50 |
February | 226.83 | 0.52 | 0.48 | 01-FEB-07:49 | 2501.08 | 25.41 | 105.67 | 246.50 | 1368.67 | 25.42 | 148.33 | 212.83 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-07:00 | 3209.50 | 25.20 | 166.83 | 325.67 | 1347.83 | 24.49 | 218.00 | 288.00 |
April | 285.17 | 0.51 | 0.48 | 01-APR-06:49 | 3768.78 | 24.72 | 104.83 | 351.67 | 2215.67 | 25.35 | 171.83 | 318.83 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-05:19 | 3887.80 | 24.67 | 155.50 | 407.67 | 1665.59 | 24.17 | 239.00 | 368.33 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-04:00 | 3541.93 | 24.25 | 124.50 | 408.50 | 1923.14 | 24.87 | 264.83 | 381.17 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-05:40 | 4445.06 | 24.98 | 136.50 | 418.67 | 1927.25 | 24.59 | 250.67 | 386.00 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-05:40 | 3576.50 | 24.81 | 163.67 | 387.00 | 1598.16 | 24.49 | 258.67 | 360.33 |
September | 326.50 | 0.51 | 0.48 | 01-SEP-05:00 | 3583.19 | 24.84 | 130.83 | 333.67 | 1996.37 | 25.25 | 206.00 | 305.00 |
October | 325.17 | 0.51 | 0.48 | 01-OCT-06:40 | 2273.63 | 24.39 | 140.00 | 296.83 | 1219.48 | 24.65 | 201.17 | 267.83 |
November | 254.83 | 0.52 | 0.48 | 01-NOV-07:49 | 1767.54 | 23.69 | 105.83 | 238.00 | 932.19 | 23.92 | 150.83 | 199.67 |
December | 186.17 | 0.53 | 0.48 | 01-DEC-07:00 | 1613.63 | 25.12 | 84.50 | 205.67 | 841.25 | 24.57 | 94.17 | 136.50 |
Annual Sum or Average | 3807.33 | 0.51 | 3205.60 | 24.70 | 1519.17 | 3853.50 | 1574.31 | 24.65 | 2343.67 | 3419.00 | ||
Minimum of Months | 186.17 | 0.50 | 0.48 | 1613.63 | 23.69 | 84.50 | 205.67 | 841.25 | 23.92 | 94.17 | 136.50 | |
Maximum of Months | 428.67 | 0.53 | 0.48 | 4445.06 | 25.41 | 166.83 | 418.67 | 2215.67 | 25.42 | 264.83 | 386.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.55 | 0.48 | 01-JAN-10:09 | 728.52 | 17.75 | 0.00 | 217.67 | 440.97 | 19.44 | 27.83 | 147.67 |
February | 226.83 | 0.54 | 0.48 | 01-FEB-09:20 | 770.59 | 18.07 | 0.00 | 233.50 | 475.85 | 19.72 | 35.33 | 179.17 |
March | 334.33 | 0.51 | 0.48 | 01-MAR-08:20 | 1036.90 | 19.46 | 0.00 | 321.50 | 600.27 | 20.87 | 129.00 | 272.17 |
April | 285.17 | 0.51 | 0.48 | 01-APR-07:19 | 1230.15 | 20.27 | 41.17 | 351.50 | 753.95 | 21.66 | 181.50 | 301.67 |
May | 428.67 | 0.49 | 0.48 | 01-MAY-06:40 | 1380.63 | 21.58 | 121.83 | 417.67 | 779.18 | 22.79 | 295.83 | 382.17 |
June | 400.67 | 0.49 | 0.48 | 01-JUN-04:00 | 1666.38 | 24.10 | 202.83 | 417.00 | 931.92 | 23.60 | 330.67 | 392.17 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:40 | 1568.89 | 22.35 | 174.17 | 425.33 | 893.52 | 22.72 | 327.17 | 397.50 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-05:00 | 1287.66 | 20.61 | 75.50 | 391.33 | 757.05 | 21.95 | 288.50 | 363.33 |
September | 326.50 | 0.51 | 0.48 | 01-SEP-06:19 | 1086.93 | 20.02 | 1.67 | 333.83 | 663.70 | 21.44 | 191.17 | 292.17 |
October | 325.17 | 0.53 | 0.48 | 01-OCT-07:30 | 851.71 | 18.56 | 0.00 | 287.00 | 501.63 | 20.06 | 56.83 | 236.00 |
November | 254.83 | 0.54 | 0.48 | 01-NOV-08:30 | 718.86 | 17.64 | 0.00 | 227.50 | 406.51 | 19.09 | 4.00 | 157.67 |
December | 186.17 | 0.58 | 0.48 | 01-DEC-10:09 | 533.23 | 16.47 | 0.00 | 183.83 | 332.51 | 18.26 | 0.00 | 80.50 |
Annual Sum or Average | 3807.33 | 0.51 | 1150.57 | 20.21 | 617.17 | 3807.67 | 670.21 | 21.33 | 1867.83 | 3202.17 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 533.23 | 16.47 | 0.00 | 183.83 | 332.51 | 18.26 | 0.00 | 80.50 | |
Maximum of Months | 428.67 | 0.58 | 0.48 | 1666.38 | 24.10 | 202.83 | 425.33 | 931.92 | 23.60 | 330.67 | 397.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.52 | 0.48 | 01-JAN-09:00 | 2200.57 | 25.89 | 105.83 | 232.50 | 1259.22 | 25.74 | 140.50 | 194.17 |
February | 226.83 | 0.52 | 0.48 | 01-FEB-09:20 | 2576.28 | 25.32 | 102.33 | 245.83 | 1397.07 | 25.20 | 154.50 | 215.17 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-08:30 | 2720.81 | 23.90 | 150.83 | 327.50 | 1457.65 | 24.37 | 206.50 | 293.00 |
April | 285.17 | 0.50 | 0.48 | 02-APR-14:39 | 4853.88 | 24.94 | 103.17 | 353.33 | 2007.86 | 23.92 | 150.50 | 308.33 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-06:00 | 2930.59 | 20.98 | 74.50 | 407.33 | 1585.28 | 21.37 | 216.83 | 375.33 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-05:00 | 3732.27 | 21.44 | 69.17 | 408.67 | 1697.52 | 21.83 | 242.33 | 375.17 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-06:10 | 4174.31 | 21.90 | 85.17 | 417.17 | 1820.92 | 22.06 | 239.33 | 385.17 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-06:30 | 3484.63 | 23.00 | 123.83 | 390.50 | 1939.94 | 23.67 | 242.33 | 359.83 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-07:19 | 3650.48 | 25.17 | 129.17 | 338.50 | 2104.10 | 25.63 | 214.33 | 308.67 |
October | 325.17 | 0.51 | 0.48 | 01-OCT-07:40 | 2330.76 | 24.43 | 137.83 | 297.17 | 1242.58 | 24.60 | 204.00 | 265.83 |
November | 254.83 | 0.52 | 0.48 | 01-NOV-08:30 | 1826.31 | 23.59 | 103.17 | 239.33 | 981.42 | 23.76 | 146.67 | 201.33 |
December | 186.17 | 0.54 | 0.48 | 01-DEC-10:09 | 1718.76 | 24.65 | 75.83 | 209.00 | 943.55 | 24.40 | 86.83 | 136.17 |
Annual Sum or Average | 3807.33 | 0.51 | 3150.78 | 23.44 | 1260.83 | 3866.83 | 1595.30 | 23.62 | 2244.67 | 3418.17 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 1718.76 | 20.98 | 69.17 | 209.00 | 943.55 | 21.37 | 86.83 | 136.17 | |
Maximum of Months | 428.67 | 0.54 | 0.48 | 4853.88 | 25.89 | 150.83 | 417.17 | 2104.10 | 25.74 | 242.33 | 385.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.50 | 0.48 | 01-JAN-09:39 | 7621.70 | 37.17 | 205.17 | 246.50 | 6338.63 | 37.82 | 200.17 | 225.17 |
February | 226.83 | 0.50 | 0.48 | 01-FEB-07:00 | 9023.97 | 37.52 | 222.33 | 256.50 | 2716.72 | 26.30 | 105.67 | 241.67 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-07:00 | 8232.51 | 29.60 | 250.83 | 329.50 | 1657.54 | 18.10 | 5.83 | 300.17 |
April | 285.17 | 0.51 | 0.48 | 01-APR-07:10 | 2557.09 | 14.83 | 0.00 | 349.17 | 1576.39 | 18.34 | 17.83 | 315.50 |
May | 428.67 | 0.51 | 0.48 | 01-MAY-06:40 | 1972.64 | 14.42 | 0.00 | 399.50 | 1144.46 | 17.86 | 0.00 | 361.00 |
June | 400.67 | 0.51 | 0.48 | 01-JUN-05:40 | 2020.19 | 14.91 | 0.00 | 401.17 | 1189.74 | 18.35 | 0.00 | 367.00 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-05:00 | 2096.97 | 15.22 | 0.00 | 411.50 | 1246.34 | 18.68 | 2.00 | 376.00 |
August | 410.83 | 0.51 | 0.48 | 01-AUG-06:19 | 2308.77 | 14.92 | 0.00 | 382.83 | 1344.17 | 18.37 | 4.83 | 354.17 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:19 | 3323.82 | 16.87 | 26.00 | 335.50 | 1694.00 | 18.74 | 28.67 | 309.17 |
October | 325.17 | 0.50 | 0.48 | 01-OCT-06:49 | 7771.71 | 32.85 | 291.00 | 307.50 | 2160.89 | 19.58 | 31.17 | 287.50 |
November | 254.83 | 0.50 | 0.48 | 01-NOV-07:49 | 5446.59 | 32.70 | 232.33 | 249.17 | 3010.29 | 29.73 | 184.83 | 230.33 |
December | 186.17 | 0.50 | 0.48 | 01-DEC-07:00 | 6700.65 | 38.32 | 183.83 | 225.50 | 6128.94 | 39.60 | 184.17 | 194.83 |
Annual Sum or Average | 3807.33 | 0.50 | 4433.62 | 22.81 | 1411.50 | 3894.33 | 2147.65 | 21.82 | 765.17 | 3562.50 | ||
Minimum of Months | 186.17 | 0.50 | 0.48 | 1972.64 | 14.42 | 0.00 | 225.50 | 1144.46 | 17.86 | 0.00 | 194.83 | |
Maximum of Months | 428.67 | 0.51 | 0.48 | 9023.97 | 38.32 | 291.00 | 411.50 | 6338.63 | 39.60 | 200.17 | 376.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.52 | 0.48 | 01-JAN-09:39 | 2061.17 | 21.93 | 66.17 | 235.17 | 1073.26 | 22.33 | 76.83 | 199.50 |
February | 226.83 | 0.52 | 0.48 | 01-FEB-07:49 | 2543.05 | 22.98 | 78.50 | 246.83 | 1424.50 | 23.57 | 73.33 | 216.33 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-07:00 | 3263.96 | 22.61 | 117.83 | 326.17 | 1413.72 | 22.21 | 68.00 | 291.67 |
April | 285.17 | 0.51 | 0.48 | 01-APR-06:49 | 3789.97 | 20.90 | 77.33 | 351.50 | 2301.90 | 23.12 | 65.17 | 322.17 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-05:19 | 3937.82 | 21.70 | 135.67 | 408.00 | 1744.41 | 21.60 | 78.00 | 372.50 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-04:00 | 3580.38 | 20.38 | 95.67 | 409.00 | 2012.99 | 22.38 | 78.00 | 383.33 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-05:40 | 4496.25 | 22.03 | 124.33 | 419.33 | 2019.08 | 22.02 | 70.00 | 389.00 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-05:40 | 3631.71 | 21.93 | 127.50 | 387.67 | 1676.12 | 21.98 | 72.33 | 363.33 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-05:00 | 3649.18 | 21.96 | 96.67 | 334.67 | 2076.54 | 22.99 | 73.33 | 308.17 |
October | 325.17 | 0.51 | 0.48 | 01-OCT-06:40 | 2315.93 | 21.69 | 100.17 | 297.67 | 1274.42 | 22.59 | 77.67 | 270.50 |
November | 254.83 | 0.52 | 0.48 | 01-NOV-07:49 | 1795.48 | 21.03 | 82.17 | 238.83 | 971.46 | 22.03 | 74.33 | 204.00 |
December | 186.17 | 0.53 | 0.48 | 01-DEC-07:00 | 1614.36 | 21.56 | 64.17 | 206.50 | 880.39 | 22.97 | 66.83 | 145.67 |
Annual Sum or Average | 3807.33 | 0.51 | 3248.71 | 21.70 | 1166.17 | 3861.33 | 1645.43 | 22.39 | 873.83 | 3466.17 | ||
Minimum of Months | 186.17 | 0.50 | 0.48 | 1614.36 | 20.38 | 64.17 | 206.50 | 880.39 | 21.60 | 65.17 | 145.67 | |
Maximum of Months | 428.67 | 0.53 | 0.48 | 4496.25 | 22.98 | 135.67 | 419.33 | 2301.90 | 23.57 | 78.00 | 389.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.55 | 0.48 | 01-JAN-09:00 | 737.38 | 12.02 | 0.00 | 218.17 | 468.53 | 15.65 | 0.00 | 157.00 |
February | 226.83 | 0.54 | 0.48 | 01-FEB-09:09 | 782.20 | 12.48 | 0.00 | 233.83 | 506.30 | 16.10 | 0.00 | 186.83 |
March | 334.33 | 0.51 | 0.48 | 01-MAR-08:20 | 1052.43 | 13.81 | 0.00 | 321.67 | 638.45 | 17.23 | 0.00 | 277.83 |
April | 285.17 | 0.50 | 0.48 | 01-APR-07:19 | 1253.89 | 15.04 | 0.00 | 351.67 | 804.09 | 18.52 | 13.33 | 309.67 |
May | 428.67 | 0.49 | 0.48 | 01-MAY-06:40 | 1403.87 | 16.22 | 29.33 | 417.67 | 830.20 | 19.48 | 39.33 | 386.33 |
June | 400.67 | 0.49 | 0.48 | 01-JUN-04:00 | 1696.48 | 19.58 | 84.83 | 417.17 | 1026.22 | 21.77 | 89.33 | 397.50 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:40 | 1600.27 | 17.20 | 30.67 | 425.33 | 980.00 | 20.54 | 69.17 | 403.33 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-05:00 | 1324.96 | 15.15 | 0.00 | 393.50 | 806.47 | 18.61 | 9.17 | 367.00 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:19 | 1105.78 | 14.86 | 0.00 | 334.00 | 707.08 | 18.30 | 0.00 | 298.17 |
October | 325.17 | 0.52 | 0.48 | 01-OCT-07:30 | 863.71 | 12.87 | 0.00 | 287.67 | 533.43 | 16.37 | 0.00 | 243.17 |
November | 254.83 | 0.54 | 0.48 | 01-NOV-08:30 | 727.40 | 11.63 | 0.00 | 227.83 | 431.69 | 15.10 | 0.00 | 168.50 |
December | 186.17 | 0.57 | 0.48 | 01-DEC-09:00 | 539.36 | 10.34 | 0.00 | 184.83 | 353.36 | 14.15 | 0.00 | 88.83 |
Annual Sum or Average | 3807.33 | 0.51 | 1171.64 | 14.81 | 144.83 | 3813.33 | 720.23 | 18.13 | 220.33 | 3284.17 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 539.36 | 10.34 | 0.00 | 184.83 | 353.36 | 14.15 | 0.00 | 88.83 | |
Maximum of Months | 428.67 | 0.57 | 0.48 | 1696.48 | 19.58 | 84.83 | 425.33 | 1026.22 | 21.77 | 89.33 | 403.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.52 | 0.48 | 01-JAN-09:00 | 2234.93 | 23.76 | 84.50 | 233.17 | 1307.61 | 24.17 | 87.33 | 198.50 |
February | 226.83 | 0.52 | 0.48 | 01-FEB-09:09 | 2625.04 | 22.82 | 74.50 | 246.67 | 1458.07 | 23.29 | 66.67 | 218.33 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-08:30 | 2769.31 | 21.02 | 94.17 | 328.17 | 1519.20 | 22.17 | 76.17 | 295.83 |
April | 285.17 | 0.50 | 0.48 | 02-APR-14:39 | 4924.94 | 21.93 | 84.50 | 353.50 | 2103.84 | 21.20 | 39.17 | 313.33 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-06:00 | 2967.99 | 17.05 | 50.17 | 407.67 | 1658.29 | 18.10 | 0.00 | 379.00 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-05:00 | 3785.46 | 17.52 | 50.33 | 409.33 | 1784.24 | 18.50 | 0.00 | 377.83 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-06:10 | 4229.44 | 18.01 | 56.00 | 417.50 | 1914.32 | 18.73 | 2.17 | 389.67 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-06:19 | 3529.74 | 19.56 | 84.33 | 390.83 | 2021.86 | 20.97 | 55.00 | 362.83 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:00 | 3718.50 | 22.18 | 99.50 | 338.33 | 2184.66 | 23.40 | 75.00 | 312.83 |
October | 325.17 | 0.51 | 0.48 | 01-OCT-07:30 | 2825.66 | 22.00 | 112.33 | 297.83 | 1300.12 | 22.49 | 79.50 | 269.83 |
November | 254.83 | 0.52 | 0.48 | 01-NOV-08:30 | 1852.83 | 20.90 | 83.50 | 239.67 | 1023.16 | 21.82 | 70.33 | 205.00 |
December | 186.17 | 0.53 | 0.48 | 01-DEC-09:50 | 1703.49 | 20.82 | 56.33 | 209.33 | 983.66 | 22.75 | 57.50 | 143.50 |
Annual Sum or Average | 3807.33 | 0.51 | 3234.99 | 20.22 | 930.17 | 3872.00 | 1667.17 | 21.07 | 608.83 | 3466.50 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 1703.49 | 17.05 | 50.17 | 209.33 | 983.66 | 18.10 | 0.00 | 143.50 | |
Maximum of Months | 428.67 | 0.53 | 0.48 | 4924.94 | 23.76 | 112.33 | 417.50 | 2184.66 | 24.17 | 87.33 | 389.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.50 | 0.48 | 01-JAN-09:39 | 7623.01 | 37.16 | 205.17 | 246.50 | 6341.28 | 37.82 | 200.17 | 225.17 |
February | 226.83 | 0.50 | 0.48 | 01-FEB-07:00 | 9025.88 | 37.51 | 222.33 | 256.50 | 2719.41 | 26.29 | 105.67 | 241.67 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-07:00 | 8236.34 | 29.59 | 250.67 | 329.50 | 1660.21 | 18.09 | 5.67 | 300.50 |
April | 285.17 | 0.51 | 0.48 | 01-APR-07:10 | 2560.38 | 14.80 | 0.00 | 349.50 | 1578.51 | 18.32 | 17.50 | 315.67 |
May | 428.67 | 0.51 | 0.48 | 01-MAY-06:40 | 1975.57 | 14.39 | 0.00 | 399.50 | 1146.24 | 17.84 | 0.00 | 361.17 |
June | 400.67 | 0.51 | 0.48 | 01-JUN-05:40 | 2023.01 | 14.88 | 0.00 | 401.17 | 1191.51 | 18.34 | 0.00 | 367.00 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-05:00 | 2099.84 | 15.19 | 0.00 | 411.67 | 1248.15 | 18.66 | 1.83 | 376.00 |
August | 410.83 | 0.51 | 0.48 | 01-AUG-06:19 | 2312.14 | 14.89 | 0.00 | 382.83 | 1346.25 | 18.36 | 3.83 | 354.17 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:19 | 3327.36 | 16.84 | 26.00 | 335.83 | 1696.45 | 18.72 | 27.83 | 309.33 |
October | 325.17 | 0.50 | 0.48 | 01-OCT-06:49 | 7774.38 | 32.84 | 291.00 | 307.50 | 2163.44 | 19.57 | 30.83 | 287.50 |
November | 254.83 | 0.50 | 0.48 | 01-NOV-07:49 | 5447.97 | 32.52 | 230.50 | 249.17 | 3012.62 | 29.72 | 184.83 | 230.33 |
December | 186.17 | 0.50 | 0.48 | 01-DEC-07:00 | 6675.76 | 37.06 | 176.67 | 224.67 | 6130.82 | 39.60 | 184.17 | 194.83 |
Annual Sum or Average | 3807.33 | 0.50 | 4435.10 | 22.71 | 1402.33 | 3894.33 | 2149.84 | 21.81 | 762.33 | 3563.33 | ||
Minimum of Months | 186.17 | 0.50 | 0.48 | 1975.57 | 14.39 | 0.00 | 224.67 | 1146.24 | 17.84 | 0.00 | 194.83 | |
Maximum of Months | 428.67 | 0.51 | 0.48 | 9025.88 | 37.51 | 291.00 | 411.67 | 6341.28 | 39.60 | 200.17 | 376.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.52 | 0.48 | 01-JAN-09:39 | 2062.20 | 21.90 | 66.17 | 235.17 | 1074.47 | 22.32 | 76.83 | 199.67 |
February | 226.83 | 0.52 | 0.48 | 01-FEB-07:49 | 2544.17 | 22.95 | 78.50 | 246.83 | 1425.77 | 23.56 | 72.50 | 216.33 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-07:00 | 3265.97 | 22.58 | 117.83 | 326.17 | 1415.40 | 22.20 | 67.67 | 292.00 |
April | 285.17 | 0.51 | 0.48 | 01-APR-06:49 | 3791.68 | 20.87 | 77.33 | 351.50 | 2303.66 | 23.10 | 65.17 | 322.50 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-05:19 | 3940.27 | 21.68 | 135.67 | 408.00 | 1746.32 | 21.59 | 78.00 | 372.83 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-04:00 | 3582.92 | 20.35 | 95.67 | 409.00 | 2015.10 | 22.36 | 78.00 | 383.50 |
July | 414.00 | 0.50 | 0.48 | 01-JUL-05:40 | 4498.47 | 22.01 | 124.33 | 419.33 | 2021.11 | 22.00 | 70.00 | 389.00 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-05:40 | 3633.86 | 21.90 | 127.50 | 387.67 | 1678.02 | 21.97 | 72.33 | 363.33 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-05:00 | 3650.89 | 21.93 | 96.67 | 334.67 | 2078.37 | 22.98 | 73.33 | 308.17 |
October | 325.17 | 0.51 | 0.48 | 01-OCT-06:40 | 2317.40 | 21.66 | 100.17 | 297.83 | 1275.78 | 22.57 | 77.33 | 270.50 |
November | 254.83 | 0.52 | 0.48 | 01-NOV-07:49 | 1796.83 | 21.01 | 82.17 | 238.83 | 972.62 | 22.01 | 74.00 | 204.00 |
December | 186.17 | 0.53 | 0.48 | 01-DEC-07:00 | 1615.02 | 21.53 | 64.17 | 206.50 | 881.20 | 22.96 | 66.17 | 145.83 |
Annual Sum or Average | 3807.33 | 0.51 | 3250.56 | 21.67 | 1166.17 | 3861.50 | 1647.11 | 22.38 | 871.33 | 3467.67 | ||
Minimum of Months | 186.17 | 0.50 | 0.48 | 1615.02 | 20.35 | 64.17 | 206.50 | 881.20 | 21.59 | 65.17 | 145.83 | |
Maximum of Months | 428.67 | 0.53 | 0.48 | 4498.47 | 22.95 | 135.67 | 419.33 | 2303.66 | 23.56 | 78.00 | 389.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.55 | 0.48 | 01-JAN-09:00 | 737.97 | 11.99 | 0.00 | 218.17 | 469.14 | 15.64 | 0.00 | 157.17 |
February | 226.83 | 0.54 | 0.48 | 01-FEB-09:09 | 782.79 | 12.45 | 0.00 | 233.83 | 506.92 | 16.09 | 0.00 | 187.17 |
March | 334.33 | 0.51 | 0.48 | 01-MAR-08:20 | 1053.62 | 13.78 | 0.00 | 321.67 | 639.37 | 17.22 | 0.00 | 278.33 |
April | 285.17 | 0.50 | 0.48 | 01-APR-07:19 | 1254.93 | 15.01 | 0.00 | 351.67 | 805.07 | 18.50 | 13.00 | 309.67 |
May | 428.67 | 0.49 | 0.48 | 01-MAY-06:40 | 1405.46 | 16.19 | 29.33 | 417.67 | 831.39 | 19.46 | 38.67 | 386.33 |
June | 400.67 | 0.49 | 0.48 | 01-JUN-04:00 | 1698.14 | 19.55 | 84.83 | 417.17 | 1027.57 | 21.76 | 88.67 | 397.50 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-05:40 | 1601.74 | 17.18 | 30.67 | 425.33 | 981.26 | 20.52 | 68.67 | 403.83 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-05:00 | 1326.33 | 15.12 | 0.00 | 393.50 | 807.58 | 18.60 | 8.83 | 367.17 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:19 | 1106.72 | 14.83 | 0.00 | 334.00 | 707.96 | 18.28 | 0.00 | 298.83 |
October | 325.17 | 0.52 | 0.48 | 01-OCT-07:30 | 864.59 | 12.84 | 0.00 | 287.67 | 534.17 | 16.35 | 0.00 | 243.50 |
November | 254.83 | 0.54 | 0.48 | 01-NOV-08:30 | 728.27 | 11.60 | 0.00 | 227.83 | 432.35 | 15.09 | 0.00 | 169.33 |
December | 186.17 | 0.57 | 0.48 | 01-DEC-09:00 | 539.71 | 10.31 | 0.00 | 185.17 | 353.79 | 14.13 | 0.00 | 88.83 |
Annual Sum or Average | 3807.33 | 0.51 | 1172.78 | 14.78 | 144.83 | 3813.67 | 721.19 | 18.12 | 217.83 | 3287.67 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 539.71 | 10.31 | 0.00 | 185.17 | 353.79 | 14.13 | 0.00 | 88.83 | |
Maximum of Months | 428.67 | 0.57 | 0.48 | 1698.14 | 19.55 | 84.83 | 425.33 | 1027.57 | 21.76 | 88.67 | 403.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 214.17 | 0.52 | 0.48 | 01-JAN-09:00 | 2236.00 | 23.73 | 84.50 | 233.17 | 1308.78 | 24.16 | 87.00 | 198.83 |
February | 226.83 | 0.52 | 0.48 | 01-FEB-09:09 | 2626.08 | 22.80 | 74.50 | 246.67 | 1459.32 | 23.28 | 66.17 | 218.33 |
March | 334.33 | 0.50 | 0.48 | 01-MAR-08:30 | 2771.30 | 21.00 | 94.17 | 328.17 | 1520.88 | 22.16 | 75.83 | 296.00 |
April | 285.17 | 0.50 | 0.48 | 02-APR-14:39 | 4926.78 | 21.90 | 84.50 | 353.50 | 2105.73 | 21.18 | 39.17 | 313.33 |
May | 428.67 | 0.50 | 0.48 | 01-MAY-06:00 | 2970.30 | 17.02 | 50.17 | 407.67 | 1660.09 | 18.08 | 0.00 | 379.33 |
June | 400.67 | 0.50 | 0.48 | 01-JUN-05:00 | 3787.82 | 17.49 | 50.33 | 409.33 | 1786.28 | 18.49 | 0.00 | 378.00 |
July | 414.00 | 0.49 | 0.48 | 01-JUL-06:10 | 4231.77 | 17.98 | 56.00 | 417.67 | 1916.42 | 18.71 | 2.17 | 389.67 |
August | 410.83 | 0.50 | 0.48 | 01-AUG-06:19 | 3532.01 | 19.53 | 84.33 | 391.00 | 2023.84 | 20.95 | 55.00 | 362.83 |
September | 326.50 | 0.50 | 0.48 | 01-SEP-06:00 | 3720.24 | 22.16 | 99.50 | 338.33 | 2186.37 | 23.39 | 75.00 | 313.00 |
October | 325.17 | 0.51 | 0.48 | 01-OCT-07:30 | 2827.12 | 21.98 | 112.33 | 297.83 | 1301.51 | 22.48 | 79.50 | 270.00 |
November | 254.83 | 0.52 | 0.48 | 01-NOV-08:30 | 1854.15 | 20.88 | 83.50 | 239.67 | 1024.32 | 21.81 | 70.33 | 205.00 |
December | 186.17 | 0.53 | 0.48 | 01-DEC-09:50 | 1704.09 | 20.79 | 56.33 | 209.33 | 984.43 | 22.74 | 57.17 | 143.67 |
Annual Sum or Average | 3807.33 | 0.51 | 3236.83 | 20.19 | 930.17 | 3872.33 | 1668.84 | 21.05 | 607.33 | 3468.00 | ||
Minimum of Months | 186.17 | 0.49 | 0.48 | 1704.09 | 17.02 | 50.17 | 209.33 | 984.43 | 18.08 | 0.00 | 143.67 | |
Maximum of Months | 428.67 | 0.53 | 0.48 | 4926.78 | 23.73 | 112.33 | 417.67 | 2186.37 | 24.16 | 87.00 | 389.67 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.856862E+10 | 77176.91 | 31-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132342E+11 | 90511.32 | 02-FEB-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.243876E+09 | 17220.09 | 21-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 98949598.56 | 15248.57 | 04-APR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4038677.48 | 1517.13 | 03-MAY-06:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 407.01 | 0.34 | 15-JUN-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15637576.53 | 4789.26 | 29-SEP-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 41703682.14 | 4566.75 | 26-OCT-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.173450E+09 | 13565.95 | 14-NOV-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.354112E+09 | 17061.31 | 05-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.227346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.132342E+11 | 90511.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.405225E+10 | 15728.67 | 12-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.204551E+10 | 15701.32 | 17-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.228422E+09 | 15758.09 | 08-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10222205.28 | 14499.35 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.466964E+09 | 15800.02 | 22-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135542E+10 | 15837.39 | 21-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.815879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.405225E+10 | 15837.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.324814E+10 | 17490.33 | 12-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.165144E+10 | 17520.12 | 11-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.470975E+09 | 17526.83 | 08-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 80481111.44 | 17024.32 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3730173.92 | 764.16 | 30-SEP-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 25754519.69 | 2083.28 | 28-OCT-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.690071E+09 | 17536.57 | 22-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.205252E+10 | 17563.72 | 20-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.822310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.324814E+10 | 17563.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.349063E+10 | 23498.07 | 12-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.155252E+10 | 23537.25 | 11-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.529957E+09 | 23607.14 | 16-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 82301911.05 | 23095.28 | 03-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6876731.78 | 1894.76 | 30-SEP-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 22976558.07 | 4348.54 | 23-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.683856E+09 | 23555.99 | 22-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.206070E+10 | 23619.51 | 18-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.842982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.349063E+10 | 23619.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.234453E+10 | 16323.86 | 27-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.770264E+09 | 16322.34 | 01-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17666651.81 | 16293.80 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 99037916.93 | 16293.61 | 25-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.243347E+09 | 16300.48 | 09-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.347485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.234453E+10 | 16323.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.114548E+12 | 850941.40 | 31-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146766E+12 | 991451.97 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.317464E+10 | 256962.84 | 16-MAR-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.201923E+10 | 159652.62 | 01-APR-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 95239621.59 | 69587.63 | 02-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 97842.80 | 158.99 | 03-JUN-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142036E+09 | 90090.34 | 30-SEP-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.187648E+10 | 120567.30 | 16-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.464930E+10 | 336303.80 | 24-NOV-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.124355E+11 | 330640.91 | 15-DEC-20:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.285706E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.146766E+12 | 991451.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.385959E+11 | 600463.59 | 02-JAN-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.106665E+11 | 600298.46 | 07-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.107692E+10 | 599680.39 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.552661E+10 | 599947.02 | 27-NOV-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130729E+11 | 600052.14 | 12-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.689388E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.385959E+11 | 600463.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.132548E+12 | 138006.54 | 18-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.775114E+11 | 137960.76 | 13-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.322546E+11 | 148248.95 | 25-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.789345E+10 | 137016.09 | 04-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145631E+09 | 127789.42 | 02-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.672024E+09 | 134549.07 | 29-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.516014E+10 | 139420.77 | 14-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.422095E+11 | 137866.08 | 20-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.946741E+11 | 137948.84 | 14-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.393069E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.132548E+12 | 148248.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.885843E+11 | 210113.93 | 03-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.506838E+11 | 210262.27 | 21-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.236995E+11 | 209815.42 | 03-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.805246E+10 | 209678.42 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 78574695.45 | 74465.78 | 02-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 877092.72 | 786.93 | 02-JUN-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.938415E+09 | 151832.44 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.564046E+10 | 196933.74 | 19-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.337934E+11 | 210111.81 | 29-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.695127E+11 | 210134.01 | 18-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.280985E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.885843E+11 | 210262.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.806629E+11 | 232810.02 | 18-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.406242E+11 | 231487.71 | 21-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.217929E+11 | 230186.72 | 07-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.681617E+10 | 230133.25 | 03-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151241E+09 | 74473.83 | 02-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.555909E+09 | 195299.32 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.294517E+10 | 228596.85 | 23-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.277129E+11 | 231313.81 | 20-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.666553E+11 | 232208.46 | 14-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.247917E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.806629E+11 | 232810.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.804131E+11 | 213429.17 | 21-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.445232E+11 | 213389.17 | 01-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.211102E+11 | 212981.08 | 01-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.553966E+10 | 213034.17 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.164220E+09 | 57757.88 | 02-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2263302.54 | 2849.69 | 02-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.103828E+10 | 169623.23 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.449391E+10 | 186291.53 | 23-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.279516E+11 | 213476.84 | 29-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.587680E+11 | 213498.24 | 18-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.244004E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.804131E+11 | 213498.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.171090E+11 | 93545.14 | 31-JAN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168203E+11 | 109770.62 | 02-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.392460E+09 | 15412.54 | 06-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 88016959.32 | 6639.19 | 10-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6932932.29 | 4730.38 | 19-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1605135.81 | 2662.98 | 02-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6397791.52 | 663.71 | 30-SEP-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 45193510.21 | 4968.79 | 03-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154249E+10 | 17387.08 | 26-NOV-07:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.403089E+10 | 23062.67 | 11-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.400433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.171090E+11 | 109770.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.189386E+11 | 81907.46 | 02-JAN-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111724E+11 | 81928.19 | 07-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.466247E+10 | 81907.00 | 04-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141202E+10 | 81877.84 | 03-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 24743385.79 | 28105.07 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.767117E+09 | 81548.97 | 10-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.719595E+10 | 81962.14 | 20-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135427E+11 | 81895.83 | 15-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.577159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.189386E+11 | 81962.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.198538E+11 | 16565.67 | 02-JAN-04:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129335E+11 | 16566.62 | 23-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.689816E+10 | 16562.36 | 10-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.251369E+10 | 16520.11 | 05-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.130423E+09 | 16382.63 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 27598086.63 | 8841.54 | 02-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.480680E+09 | 16495.12 | 29-SEP-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.231333E+10 | 16571.78 | 23-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.838000E+10 | 16567.15 | 16-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156804E+11 | 16516.21 | 01-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.692116E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.198538E+11 | 16571.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.128294E+11 | 22182.36 | 24-JAN-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.804154E+10 | 22187.52 | 18-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.431367E+10 | 22193.74 | 03-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.186128E+10 | 22065.09 | 03-APR-04:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 64639794.75 | 15568.69 | 02-MAY-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 42865913.09 | 5423.19 | 02-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 100599.87 | 670.67 | 07-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.359675E+09 | 21951.78 | 29-SEP-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.160050E+10 | 22188.13 | 16-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.589076E+10 | 22181.31 | 25-NOV-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105911E+11 | 22193.93 | 21-DEC-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.455955E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.128294E+11 | 22193.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.134960E+11 | 24880.47 | 18-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.792474E+10 | 24888.70 | 23-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.493972E+10 | 24882.10 | 10-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.217391E+10 | 24798.81 | 03-APR-03:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140034E+09 | 22360.14 | 03-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 46109156.56 | 9202.97 | 03-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.384546E+09 | 24766.35 | 30-SEP-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138821E+10 | 24896.85 | 23-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.594586E+10 | 24875.52 | 18-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116602E+11 | 24876.43 | 01-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.480992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.134960E+11 | 24896.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.120704E+11 | 24274.76 | 25-JAN-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.706818E+10 | 24274.58 | 28-FEB-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.397965E+10 | 24278.84 | 13-MAR-03:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143966E+10 | 24160.55 | 03-APR-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114533E+09 | 12129.34 | 02-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 42783247.15 | 4855.65 | 02-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.420202E+09 | 24050.78 | 30-SEP-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146247E+10 | 24368.49 | 16-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.490464E+10 | 24270.89 | 30-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.898057E+10 | 24284.83 | 20-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.404831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120704E+11 | 24368.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.278989E+11 | 54597.19 | 31-JAN-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153104E+11 | 62640.12 | 02-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409574E+10 | 28414.67 | 06-MAR-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.951521E+09 | 14971.80 | 04-APR-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2894879.86 | 5775.72 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 401257.19 | 1337.52 | 03-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4466895.75 | 7511.95 | 29-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 24136523.46 | 14089.93 | 23-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.331711E+10 | 37506.07 | 25-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.106796E+11 | 38757.25 | 09-DEC-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.622852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.278989E+11 | 62640.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 6487283.68 | 6487283.68 | 2079.91 | 10-JAN-13:10 | 2079.91 | 0.00 |
February | 0.00 | 0.00 | 5808442.14 | 5808442.14 | 7563.07 | 09-FEB-08:10 | 7563.07 | 0.00 |
March | 0.00 | 0.00 | 0.778716E+09 | 0.778716E+09 | 41069.00 | 19-MAR-14:52 | 41069.00 | 0.01 |
April | 0.00 | 0.00 | 0.147235E+11 | 0.134627E+11 | 184935.20 | 18-APR-09:30 | 112113.69 | 0.12 |
May | 0.00 | 0.00 | 0.327260E+11 | 0.287397E+11 | 170639.88 | 30-MAY-10:50 | 103755.04 | 0.28 |
June | 0.00 | 0.00 | 0.103584E+12 | 0.824451E+11 | 276501.45 | 27-JUN-07:50 | 124693.38 | 0.55 |
July | 0.00 | 0.00 | 0.155498E+12 | 0.110884E+12 | 279501.38 | 07-JUL-12:10 | 116530.13 | 0.74 |
August | 0.00 | 0.00 | 0.148423E+12 | 0.106165E+12 | 355032.53 | 04-AUG-07:10 | 108972.75 | 0.71 |
September | 0.00 | 0.00 | 0.491978E+11 | 0.466185E+11 | 200567.93 | 11-SEP-09:40 | 119147.28 | 0.29 |
October | 0.00 | 0.00 | 0.447415E+10 | 0.447415E+10 | 88152.21 | 20-OCT-15:00 | 88152.21 | 0.04 |
November | 0.00 | 0.00 | 0.477912E+09 | 0.477912E+09 | 30304.78 | 03-NOV-13:50 | 30304.78 | 0.01 |
December | 0.00 | 0.00 | 8440304.19 | 8440304.19 | 1012.77 | 01-DEC-08:40 | 1012.77 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.509903E+12 | 0.394067E+12 | 0.23 | |||
Minimum of Months | 0.00 | 0.00 | 5808442.14 | 5808442.14 | 1012.77 | 1012.77 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.155498E+12 | 0.110884E+12 | 355032.53 | 124693.38 | 0.74 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 15243042.34 | 15243042.34 | 11093.19 | 12-JAN-11:20 | 11093.19 | 0.00 |
February | 0.00 | 0.00 | 13470055.81 | 13470055.81 | 9535.81 | 24-FEB-10:40 | 9535.81 | 0.00 |
March | 0.00 | 0.00 | 0.561787E+10 | 0.561787E+10 | 192483.37 | 25-MAR-15:00 | 192483.37 | 0.00 |
April | 0.00 | 0.00 | 0.111140E+12 | 0.100925E+12 | 1395161.93 | 18-APR-09:30 | 866946.16 | 0.10 |
May | 0.00 | 0.00 | 0.276665E+12 | 0.244533E+12 | 1367978.95 | 30-MAY-11:00 | 871668.43 | 0.28 |
June | 0.00 | 0.00 | 0.797963E+12 | 0.648230E+12 | 2190835.01 | 26-JUN-04:12 | 861710.09 | 0.50 |
July | 0.00 | 0.00 | 0.109346E+13 | 0.807491E+12 | 2024761.29 | 26-JUL-04:12 | 970328.96 | 0.61 |
August | 0.00 | 0.00 | 0.104528E+13 | 0.781774E+12 | 3264414.91 | 04-AUG-05:03 | 1019745.75 | 0.58 |
September | 0.00 | 0.00 | 0.416632E+12 | 0.394747E+12 | 1591795.94 | 11-SEP-05:03 | 859491.05 | 0.28 |
October | 0.00 | 0.00 | 0.345014E+11 | 0.345014E+11 | 744003.01 | 20-OCT-15:00 | 744003.01 | 0.04 |
November | 0.00 | 0.00 | 0.401584E+10 | 0.401584E+10 | 246766.85 | 03-NOV-14:20 | 246766.85 | 0.00 |
December | 0.00 | 0.00 | 4438281.89 | 4438281.89 | 531.80 | 08-DEC-11:30 | 531.80 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.378530E+13 | 0.302187E+13 | 0.20 | |||
Minimum of Months | 0.00 | 0.00 | 4438281.89 | 4438281.89 | 531.80 | 531.80 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.109346E+13 | 0.807491E+12 | 3264414.91 | 1019745.75 | 0.61 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 8229035.95 | 8229035.95 | 924.94 | 13-JAN-11:30 | 924.94 | 0.00 |
February | 0.00 | 0.00 | 9534763.10 | 9534763.10 | 968.59 | 08-FEB-10:30 | 968.59 | 0.00 |
March | 0.00 | 0.00 | 0.441598E+09 | 0.441598E+09 | 18117.01 | 25-MAR-15:00 | 18117.01 | 0.00 |
April | 0.00 | 0.00 | 0.119688E+11 | 0.107918E+11 | 156961.04 | 18-APR-16:00 | 108649.49 | 0.10 |
May | 0.00 | 0.00 | 0.292761E+11 | 0.259564E+11 | 142645.48 | 30-MAY-11:00 | 91395.35 | 0.27 |
June | 0.00 | 0.00 | 0.881142E+11 | 0.718002E+11 | 233466.46 | 26-JUN-04:12 | 91909.82 | 0.50 |
July | 0.00 | 0.00 | 0.119136E+12 | 0.875966E+11 | 230055.50 | 06-JUL-14:50 | 118374.67 | 0.61 |
August | 0.00 | 0.00 | 0.110097E+12 | 0.833159E+11 | 334085.89 | 04-AUG-05:03 | 105019.94 | 0.57 |
September | 0.00 | 0.00 | 0.431463E+11 | 0.409366E+11 | 168324.52 | 11-SEP-10:00 | 104456.35 | 0.28 |
October | 0.00 | 0.00 | 0.282526E+10 | 0.282526E+10 | 71207.56 | 20-OCT-15:00 | 71207.56 | 0.04 |
November | 0.00 | 0.00 | 0.242071E+09 | 0.242071E+09 | 19147.72 | 03-NOV-14:00 | 19147.72 | 0.00 |
December | 0.00 | 0.00 | 4729351.70 | 4729351.70 | 669.82 | 15-DEC-11:30 | 669.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.405270E+12 | 0.323929E+12 | 0.20 | |||
Minimum of Months | 0.00 | 0.00 | 4729351.70 | 4729351.70 | 669.82 | 669.82 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.119136E+12 | 0.875966E+11 | 334085.89 | 118374.67 | 0.61 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.847160E+09 | 0.847160E+09 | 24496.36 | 28-MAR-15:00 | 24496.36 | 0.00 |
April | 0.00 | 0.00 | 0.781182E+10 | 0.692383E+10 | 94049.12 | 18-APR-06:05 | 48839.01 | 0.09 |
May | 0.00 | 0.00 | 0.197779E+11 | 0.159962E+11 | 131836.77 | 30-MAY-10:00 | 66323.38 | 0.23 |
June | 0.00 | 0.00 | 0.367861E+11 | 0.283026E+11 | 167902.46 | 12-JUN-13:20 | 76078.11 | 0.28 |
July | 0.00 | 0.00 | 0.606401E+11 | 0.430158E+11 | 169527.09 | 17-JUL-08:50 | 76834.98 | 0.30 |
August | 0.00 | 0.00 | 0.688467E+11 | 0.517056E+11 | 176306.43 | 28-AUG-09:55 | 73409.13 | 0.40 |
September | 0.00 | 0.00 | 0.309664E+11 | 0.287832E+11 | 100557.35 | 05-SEP-13:57 | 93367.72 | 0.21 |
October | 0.00 | 0.00 | 0.323704E+10 | 0.322126E+10 | 54680.61 | 20-OCT-15:00 | 54680.61 | 0.04 |
November | 0.00 | 0.00 | 0.157464E+09 | 0.132750E+09 | 49203.95 | 08-NOV-07:11 | 28331.09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.229071E+12 | 0.178928E+12 | 0.13 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.688467E+11 | 0.517056E+11 | 176306.43 | 93367.72 | 0.40 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.620845E+10 | 0.620843E+10 | 2735.71 | 22-JAN-11:00 | 2735.71 | 0.00 |
February | 0.00 | 0.00 | 0.101580E+11 | 0.100659E+11 | 5068.84 | 20-FEB-15:08 | 5068.84 | 0.00 |
March | 0.00 | 0.00 | 0.146441E+11 | 0.142041E+11 | 90613.00 | 19-MAR-15:53 | 68861.22 | 0.00 |
April | 0.00 | 0.00 | 0.122971E+12 | 0.927757E+11 | 508882.29 | 18-APR-09:55 | 309720.86 | 0.00 |
May | 0.00 | 0.00 | 0.172627E+11 | 0.146377E+11 | 177462.49 | 30-MAY-14:10 | 131422.78 | 0.00 |
June | 0.00 | 0.00 | 0.214489E+12 | 0.158650E+12 | 477978.80 | 13-JUN-12:10 | 224142.84 | 0.00 |
July | 0.00 | 0.00 | 0.636638E+12 | 0.367796E+12 | 570353.06 | 26-JUL-19:00 | 186237.93 | 0.00 |
August | 0.00 | 0.00 | 0.854548E+12 | 0.485523E+12 | 561143.31 | 04-AUG-13:00 | 271869.73 | 0.00 |
September | 0.00 | 0.00 | 0.464644E+11 | 0.425815E+11 | 195365.73 | 11-SEP-10:50 | 131428.91 | 0.00 |
October | 0.00 | 0.00 | 0.109204E+11 | 0.107468E+11 | 119828.70 | 20-OCT-15:00 | 119828.70 | 0.00 |
November | 0.00 | 0.00 | 0.112637E+11 | 0.111074E+11 | 5590.13 | 03-NOV-18:00 | 5279.37 | 0.00 |
December | 0.00 | 0.00 | 0.146883E+11 | 0.146824E+11 | 5745.32 | 01-DEC-00:10 | 5496.93 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.196026E+13 | 0.122898E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.620845E+10 | 0.620843E+10 | 2735.71 | 2735.71 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.854548E+12 | 0.485523E+12 | 570353.06 | 309720.86 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.244246E+10 | 0.244233E+10 | 2205.76 | 12-JAN-16:30 | 2205.76 | 0.00 |
February | 0.00 | 0.00 | 0.769805E+10 | 0.769805E+10 | 4654.48 | 20-FEB-17:00 | 4654.48 | 0.00 |
March | 0.00 | 0.00 | 0.147120E+11 | 0.147110E+11 | 7559.81 | 31-MAR-24:00 | 7559.81 | 0.00 |
April | 0.00 | 0.00 | 0.199080E+11 | 0.198727E+11 | 9089.38 | 16-APR-17:52 | 9089.38 | 0.00 |
May | 0.00 | 0.00 | 0.585171E+10 | 0.573369E+10 | 4224.25 | 31-MAY-23:10 | 4112.12 | 0.00 |
June | 0.00 | 0.00 | 0.111275E+11 | 0.108780E+11 | 6067.64 | 30-JUN-23:03 | 6013.75 | 0.00 |
July | 0.00 | 0.00 | 0.168501E+11 | 0.164914E+11 | 7850.99 | 31-JUL-24:00 | 7849.17 | 0.00 |
August | 0.00 | 0.00 | 0.218086E+11 | 0.214552E+11 | 9284.65 | 04-AUG-17:03 | 8663.19 | 0.00 |
September | 0.00 | 0.00 | 0.573315E+10 | 0.565077E+10 | 3660.14 | 30-SEP-24:00 | 3660.14 | 0.00 |
October | 0.00 | 0.00 | 0.102786E+11 | 0.102686E+11 | 5649.33 | 31-OCT-24:00 | 5649.33 | 0.00 |
November | 0.00 | 0.00 | 0.141379E+11 | 0.141219E+11 | 6829.82 | 05-NOV-16:17 | 6829.82 | 0.00 |
December | 0.00 | 0.00 | 0.189338E+11 | 0.189338E+11 | 8085.02 | 25-DEC-16:08 | 8085.02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.149482E+12 | 0.148257E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.244246E+10 | 0.244233E+10 | 2205.76 | 2205.76 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.218086E+11 | 0.214552E+11 | 9284.65 | 9089.38 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.268740E+10 | 0.268740E+10 | 17926.03 | 12-JAN-16:40 | 17926.03 | 0.00 |
February | 0.00 | 0.00 | 0.507652E+11 | 0.507652E+11 | 41836.40 | 24-FEB-17:00 | 41836.40 | 0.00 |
March | 0.00 | 0.00 | 0.121528E+12 | 0.121517E+12 | 67255.54 | 31-MAR-23:30 | 67255.54 | 0.00 |
April | 0.00 | 0.00 | 0.178108E+12 | 0.177755E+12 | 85473.05 | 15-APR-18:10 | 85082.51 | 0.00 |
May | 0.00 | 0.00 | 0.502056E+11 | 0.490424E+11 | 39979.68 | 31-MAY-23:10 | 38826.61 | 0.00 |
June | 0.00 | 0.00 | 0.103042E+12 | 0.100562E+12 | 58249.61 | 30-JUN-23:03 | 57700.53 | 0.00 |
July | 0.00 | 0.00 | 0.158799E+12 | 0.155229E+12 | 74668.15 | 31-JUL-24:00 | 74633.28 | 0.00 |
August | 0.00 | 0.00 | 0.205998E+12 | 0.202470E+12 | 87434.70 | 01-AUG-18:30 | 84135.63 | 0.00 |
September | 0.00 | 0.00 | 0.485000E+11 | 0.476904E+11 | 32450.42 | 04-SEP-17:43 | 32337.49 | 0.00 |
October | 0.00 | 0.00 | 0.839609E+11 | 0.838590E+11 | 48938.21 | 31-OCT-23:50 | 48938.21 | 0.00 |
November | 0.00 | 0.00 | 0.112906E+12 | 0.112745E+12 | 60663.74 | 03-NOV-16:00 | 60411.51 | 0.00 |
December | 0.00 | 0.00 | 0.149893E+12 | 0.149893E+12 | 72260.72 | 01-DEC-16:10 | 72260.72 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.126639E+13 | 0.125422E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.268740E+10 | 0.268740E+10 | 17926.03 | 17926.03 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.205998E+12 | 0.202470E+12 | 87434.70 | 85082.51 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.114407E+09 | 0.114407E+09 | 1689.73 | 12-JAN-16:40 | 1689.73 | 0.00 |
February | 0.00 | 0.00 | 0.343294E+10 | 0.343294E+10 | 4150.67 | 24-FEB-17:00 | 4150.67 | 0.00 |
March | 0.00 | 0.00 | 0.106748E+11 | 0.106738E+11 | 6234.00 | 31-MAR-23:10 | 6234.00 | 0.00 |
April | 0.00 | 0.00 | 0.167503E+11 | 0.167151E+11 | 8798.37 | 16-APR-17:42 | 8798.37 | 0.00 |
May | 0.00 | 0.00 | 0.460808E+10 | 0.449243E+10 | 3982.38 | 31-MAY-23:10 | 3867.36 | 0.00 |
June | 0.00 | 0.00 | 0.101559E+11 | 0.990819E+10 | 5817.67 | 30-JUN-23:03 | 5762.40 | 0.00 |
July | 0.00 | 0.00 | 0.158551E+11 | 0.154985E+11 | 7375.30 | 31-JUL-24:00 | 7371.06 | 0.00 |
August | 0.00 | 0.00 | 0.205090E+11 | 0.201566E+11 | 8824.99 | 01-AUG-18:30 | 8495.29 | 0.00 |
September | 0.00 | 0.00 | 0.431903E+10 | 0.423862E+10 | 3289.25 | 04-SEP-17:43 | 3277.76 | 0.00 |
October | 0.00 | 0.00 | 0.691161E+10 | 0.690165E+10 | 4609.18 | 11-OCT-16:50 | 4557.15 | 0.00 |
November | 0.00 | 0.00 | 0.947644E+10 | 0.946059E+10 | 6054.86 | 03-NOV-16:00 | 6029.71 | 0.00 |
December | 0.00 | 0.00 | 0.131392E+11 | 0.131392E+11 | 7105.13 | 01-DEC-16:10 | 7105.13 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.115947E+12 | 0.114732E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.114407E+09 | 0.114407E+09 | 1689.73 | 1689.73 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.205090E+11 | 0.201566E+11 | 8824.99 | 8798.37 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 252288.76 | 2198958.34 | 02-JAN-04:01 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 192963.86 | 2052412.88 | 02-FEB-07:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 49708.08 | 1801559.74 | 07-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15738.39 | 1373515.24 | 03-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 406.45 | 559398.25 | 02-MAY-05:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 60.49 | 35775.05 | 02-JUN-05:02 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.03 | 622.55 | 07-AUG-05:10 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 1943.06 | 1201868.44 | 30-SEP-05:02 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10330.16 | 1459266.27 | 23-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 69533.41 | 1905170.97 | 29-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 147218.87 | 2002635.14 | 14-DEC-06:01 |
Annual Sum or Average | 0.00 | 61040.47 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 252288.76 | 2198958.34 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 172.24 | 5206.82 | 12-JAN-11:20 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 133.98 | 7108.16 | 24-FEB-10:40 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 3077.73 | 233005.27 | 25-MAR-15:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 57787.97 | 1912192.41 | 18-APR-09:55 | 0.00 | 0.00 | 01-APR-00:10 |
May | 138891.32 | 1810290.31 | 30-MAY-11:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 405171.20 | 2564472.97 | 26-JUN-07:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 554418.76 | 2507634.87 | 05-JUL-10:30 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 532252.27 | 3421606.45 | 03-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 214607.37 | 2598150.71 | 05-SEP-14:43 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 17306.34 | 1061743.19 | 20-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 2139.27 | 300804.36 | 03-NOV-14:20 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 179.22 | 5028.20 | 01-DEC-08:40 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 161726.46 | 0.00 | ||||
Minimum of Months | 133.98 | 5028.20 | 0.00 | 0.00 | ||
Maximum of Months | 554418.76 | 3421606.45 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1.10 | 1033.48 | 12-JAN-11:20 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 2.77 | 3003.72 | 24-FEB-10:40 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 2812.79 | 232353.63 | 25-MAR-15:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 56950.95 | 1776734.40 | 18-APR-09:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 137053.23 | 1805334.33 | 30-MAY-11:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 403664.83 | 3961929.21 | 26-JUN-04:12 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 551685.74 | 3795923.05 | 26-JUL-04:12 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 529946.63 | 4201124.10 | 04-AUG-04:12 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 214705.25 | 3089012.20 | 11-SEP-05:03 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 16794.10 | 1061395.25 | 20-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 1923.49 | 297208.12 | 03-NOV-14:20 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 3.94 | 844.91 | 01-DEC-08:40 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 160834.62 | 0.00 | ||||
Minimum of Months | 1.10 | 844.91 | 0.00 | 0.00 | ||
Maximum of Months | 551685.74 | 4201124.10 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 10092.38 | 107315.98 | 12-JAN-16:50 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 42410.18 | 145100.87 | 24-FEB-17:55 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 80471.16 | 303831.74 | 19-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 217324.11 | 1693659.13 | 16-APR-16:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 85745.46 | 994201.51 | 31-MAY-15:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 394660.32 | 1431339.09 | 13-JUN-12:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 723777.88 | 1826571.95 | 26-JUL-15:10 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 864610.83 | 2109365.63 | 04-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 165650.64 | 1137917.04 | 06-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 59828.64 | 587121.70 | 20-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 75681.13 | 161913.45 | 16-NOV-08:45 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 96628.16 | 235485.60 | 15-DEC-11:43 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 236555.51 | 0.00 | ||||
Minimum of Months | 10092.38 | 107315.98 | 0.00 | 0.00 | ||
Maximum of Months | 864610.83 | 2109365.63 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 16465.26 | 59152.49 | 31-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 16894.76 | 59537.43 | 21-FEB-12:20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17777.99 | 59447.92 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 16020.56 | 57771.79 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15596.57 | 55043.52 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14913.99 | 51404.48 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 12955.53 | 48011.42 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 13823.67 | 46092.58 | 01-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 13127.28 | 47179.80 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 13755.39 | 50235.49 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14898.82 | 53759.39 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 15304.55 | 56889.04 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 15117.59 | ||||
Minimum of Months | 0.00 | 0.00 | 12955.53 | 46092.58 | ||
Maximum of Months | 0.00 | 0.00 | 17777.99 | 59537.43 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 14.35 | 11212.69 | 09-JAN-19:20 | 2483.75 | 195810.16 | 05-JAN-07:02 |
February | 12.34 | 11601.38 | 27-FEB-09:00 | 1963.16 | 183681.08 | 18-FEB-07:03 |
March | 2475.56 | 269210.46 | 28-MAR-15:00 | 1936.89 | 180098.61 | 06-MAR-15:30 |
April | 86735.22 | 3841407.29 | 18-APR-12:10 | 2358.62 | 168903.50 | 25-APR-06:05 |
May | 185765.84 | 3291210.00 | 30-MAY-12:10 | 2664.97 | 125034.85 | 02-MAY-13:50 |
June | 739667.60 | 6096250.20 | 26-JUN-07:50 | 641.38 | 122188.87 | 02-JUN-06:00 |
July | 1030486.66 | 6387531.04 | 26-JUL-15:00 | 338.50 | 73131.49 | 23-JUL-22:40 |
August | 989773.73 | 8049673.38 | 04-AUG-07:20 | 579.79 | 56823.04 | 16-AUG-04:35 |
September | 293349.74 | 3816045.14 | 11-SEP-09:40 | 1342.53 | 123535.31 | 29-SEP-11:50 |
October | 17776.12 | 1196018.25 | 20-OCT-15:00 | 1801.85 | 163937.31 | 26-OCT-20:40 |
November | 1711.20 | 345078.75 | 03-NOV-14:20 | 2140.47 | 199460.13 | 12-NOV-11:50 |
December | 18.86 | 11827.22 | 13-DEC-14:30 | 2324.74 | 180563.86 | 26-DEC-15:10 |
Annual Sum or Average | 281260.01 | 1713.71 | ||||
Minimum of Months | 12.34 | 11212.69 | 338.50 | 56823.04 | ||
Maximum of Months | 1030486.66 | 8049673.38 | 2664.97 | 199460.13 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.361502E+10 | 0.32 | 14085.56 | 12-JAN-06:01 | 1.42 |
February | 0.385107E+10 | 0.34 | 14085.56 | 15-FEB-06:01 | 1.42 |
March | 0.614337E+10 | 0.41 | 14979.53 | 21-MAR-09:30 | 1.48 |
April | 0.827074E+10 | 0.49 | 21870.68 | 18-APR-15:20 | 1.85 |
May | 0.889174E+10 | 0.50 | 19086.35 | 30-MAY-04:12 | 1.70 |
June | 0.138907E+11 | 0.66 | 23325.15 | 14-JUN-04:12 | 1.93 |
July | 0.165632E+11 | 0.74 | 23325.15 | 01-JUL-04:12 | 1.94 |
August | 0.167220E+11 | 0.76 | 23325.15 | 22-AUG-15:00 | 1.93 |
September | 0.922022E+10 | 0.51 | 23325.15 | 05-SEP-13:45 | 1.94 |
October | 0.682469E+10 | 0.42 | 14478.70 | 11-OCT-15:20 | 1.44 |
November | 0.520084E+10 | 0.37 | 14085.56 | 21-NOV-06:01 | 1.43 |
December | 0.464273E+10 | 0.34 | 17710.71 | 20-DEC-14:50 | 1.64 |
Annual Sum or Average | 0.103836E+12 | 0.49 | |||
Minimum of Months | 0.361502E+10 | 0.32 | 14085.56 | 1.42 | |
Maximum of Months | 0.167220E+11 | 0.76 | 23325.15 | 1.94 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.435340E+11 | 0.42 | 59060.56 | 02-JAN-04:01 | 0.88 |
February | 0.343217E+11 | 0.37 | 59060.56 | 01-FEB-06:01 | 0.89 |
March | 0.398596E+11 | 0.36 | 106678.20 | 25-MAR-05:02 | 1.25 |
April | 0.489849E+11 | 0.39 | 161830.48 | 18-APR-15:20 | 1.60 |
May | 0.667277E+11 | 0.44 | 153109.81 | 30-MAY-15:30 | 1.54 |
June | 0.959430E+11 | 0.54 | 218488.66 | 12-JUN-05:03 | 1.93 |
July | 0.996376E+11 | 0.54 | 218488.66 | 03-JUL-04:12 | 1.93 |
August | 0.101372E+12 | 0.54 | 218488.66 | 04-AUG-04:12 | 1.93 |
September | 0.670959E+11 | 0.44 | 216841.59 | 11-SEP-05:03 | 1.92 |
October | 0.420723E+11 | 0.34 | 139764.81 | 26-OCT-05:02 | 1.47 |
November | 0.361004E+11 | 0.35 | 95500.78 | 01-NOV-05:03 | 1.17 |
December | 0.380315E+11 | 0.37 | 59060.56 | 11-DEC-05:11 | 0.89 |
Annual Sum or Average | 0.713680E+12 | 0.43 | |||
Minimum of Months | 0.343217E+11 | 0.34 | 59060.56 | 0.88 | |
Maximum of Months | 0.101372E+12 | 0.54 | 218488.66 | 1.93 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.516479E+10 | 0.47 | 5737.83 | 02-JAN-04:01 | 0.83 |
February | 0.417502E+10 | 0.43 | 5737.83 | 01-FEB-05:01 | 0.83 |
March | 0.401729E+10 | 0.37 | 6187.00 | 24-MAR-14:40 | 0.86 |
April | 0.459613E+10 | 0.38 | 17594.73 | 18-APR-15:20 | 1.60 |
May | 0.609060E+10 | 0.41 | 17724.58 | 31-MAY-15:00 | 1.60 |
June | 0.965449E+10 | 0.51 | 23738.90 | 30-JUN-05:03 | 1.93 |
July | 0.100303E+11 | 0.51 | 23077.92 | 03-JUL-04:12 | 1.90 |
August | 0.989733E+10 | 0.51 | 23738.90 | 04-AUG-04:12 | 1.93 |
September | 0.596398E+10 | 0.40 | 18743.80 | 08-SEP-16:00 | 1.66 |
October | 0.359630E+10 | 0.32 | 7734.08 | 20-OCT-15:50 | 0.98 |
November | 0.397835E+10 | 0.39 | 6284.04 | 03-NOV-15:10 | 0.87 |
December | 0.467001E+10 | 0.44 | 5737.83 | 20-DEC-06:01 | 0.83 |
Annual Sum or Average | 0.718346E+11 | 0.43 | |||
Minimum of Months | 0.359630E+10 | 0.32 | 5737.83 | 0.83 | |
Maximum of Months | 0.100303E+11 | 0.51 | 23738.90 | 1.93 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.157150E+10 | 0.29 | 13359.98 | 02-JAN-07:03 | 1.96 |
February | 0.164999E+10 | 0.30 | 13359.98 | 01-FEB-07:02 | 1.99 |
March | 0.432779E+10 | 0.42 | 13359.98 | 01-MAR-07:03 | 1.98 |
April | 0.584959E+10 | 0.48 | 13359.98 | 01-APR-06:03 | 1.98 |
May | 0.965142E+10 | 0.63 | 13359.98 | 01-MAY-06:05 | 1.97 |
June | 0.102913E+11 | 0.63 | 13359.98 | 01-JUN-06:10 | 1.91 |
July | 0.101792E+11 | 0.57 | 13359.98 | 01-JUL-06:05 | 1.96 |
August | 0.130159E+11 | 0.75 | 13359.98 | 01-AUG-06:05 | 1.96 |
September | 0.132286E+11 | 0.79 | 13359.98 | 01-SEP-06:05 | 1.96 |
October | 0.127153E+11 | 0.76 | 13359.98 | 02-OCT-06:10 | 1.98 |
November | 0.768424E+10 | 0.55 | 13359.98 | 01-NOV-06:05 | 1.97 |
December | 0.220202E+10 | 0.30 | 13359.98 | 01-DEC-07:05 | 1.98 |
Annual Sum or Average | 0.923669E+11 | 0.54 | |||
Minimum of Months | 0.157150E+10 | 0.29 | 13359.98 | 1.91 | |
Maximum of Months | 0.132286E+11 | 0.79 | 13359.98 | 1.99 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.113655E+12 | 1.41 | 42434.07 | 01-JAN-00:03 | 1.41 |
February | 0.102656E+12 | 1.41 | 42434.07 | 01-FEB-00:03 | 1.41 |
March | 0.113655E+12 | 1.42 | 42434.07 | 01-MAR-00:10 | 1.42 |
April | 0.109989E+12 | 1.41 | 42434.07 | 01-APR-00:10 | 1.42 |
May | 0.113655E+12 | 1.41 | 42434.07 | 01-MAY-00:20 | 1.41 |
June | 0.109989E+12 | 1.40 | 42434.07 | 01-JUN-00:10 | 1.41 |
July | 0.113655E+12 | 1.40 | 42434.07 | 01-JUL-00:03 | 1.40 |
August | 0.113655E+12 | 1.40 | 42434.07 | 01-AUG-00:03 | 1.39 |
September | 0.109989E+12 | 1.41 | 42434.07 | 01-SEP-00:05 | 1.40 |
October | 0.113655E+12 | 1.41 | 42434.07 | 01-OCT-00:10 | 1.41 |
November | 0.109989E+12 | 1.41 | 42434.07 | 01-NOV-00:10 | 1.42 |
December | 0.113655E+12 | 1.42 | 42434.07 | 01-DEC-00:10 | 1.42 |
Annual Sum or Average | 0.133820E+13 | 1.41 | |||
Minimum of Months | 0.102656E+12 | 1.40 | 42434.07 | 1.39 | |
Maximum of Months | 0.113655E+12 | 1.42 | 42434.07 | 1.42 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.157584E+10 | 0.97 | 588.35 | 01-JAN-00:03 | 0.96 |
February | 0.142334E+10 | 0.96 | 588.35 | 01-FEB-00:03 | 0.97 |
March | 0.157584E+10 | 0.96 | 588.35 | 01-MAR-00:10 | 0.97 |
April | 0.152500E+10 | 0.96 | 588.35 | 01-APR-00:10 | 0.96 |
May | 0.157584E+10 | 0.96 | 588.35 | 01-MAY-00:10 | 0.96 |
June | 0.152500E+10 | 0.96 | 588.35 | 01-JUN-00:10 | 0.96 |
July | 0.157584E+10 | 0.96 | 588.35 | 01-JUL-00:03 | 0.96 |
August | 0.157584E+10 | 0.96 | 588.35 | 01-AUG-00:03 | 0.96 |
September | 0.152500E+10 | 0.96 | 588.35 | 01-SEP-00:05 | 0.96 |
October | 0.157584E+10 | 0.96 | 588.35 | 01-OCT-00:10 | 0.96 |
November | 0.152500E+10 | 0.96 | 588.35 | 01-NOV-00:10 | 0.96 |
December | 0.157584E+10 | 0.96 | 588.35 | 01-DEC-00:10 | 0.96 |
Annual Sum or Average | 0.185542E+11 | 0.96 | |||
Minimum of Months | 0.142334E+10 | 0.96 | 588.35 | 0.96 | |
Maximum of Months | 0.157584E+10 | 0.97 | 588.35 | 0.97 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.151428E+11 | 0.97 | 5653.66 | 01-JAN-00:03 | 0.96 |
February | 0.136773E+11 | 0.96 | 5653.66 | 01-FEB-00:03 | 0.97 |
March | 0.151428E+11 | 0.96 | 5653.66 | 01-MAR-00:10 | 0.97 |
April | 0.146543E+11 | 0.96 | 5653.66 | 01-APR-00:10 | 0.96 |
May | 0.151428E+11 | 0.96 | 5653.66 | 01-MAY-00:10 | 0.96 |
June | 0.146543E+11 | 0.96 | 5653.66 | 01-JUN-00:10 | 0.96 |
July | 0.151428E+11 | 0.96 | 5653.66 | 01-JUL-00:03 | 0.96 |
August | 0.151428E+11 | 0.96 | 5653.66 | 01-AUG-00:03 | 0.96 |
September | 0.146543E+11 | 0.96 | 5653.66 | 01-SEP-00:05 | 0.96 |
October | 0.151428E+11 | 0.96 | 5653.66 | 01-OCT-00:10 | 0.96 |
November | 0.146543E+11 | 0.96 | 5653.66 | 01-NOV-00:10 | 0.96 |
December | 0.151428E+11 | 0.96 | 5653.66 | 01-DEC-00:10 | 0.96 |
Annual Sum or Average | 0.178294E+12 | 0.96 | |||
Minimum of Months | 0.136773E+11 | 0.96 | 5653.66 | 0.96 | |
Maximum of Months | 0.151428E+11 | 0.97 | 5653.66 | 0.97 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.153987E+10 | 0.97 | 574.92 | 01-JAN-00:03 | 0.96 |
February | 0.139085E+10 | 0.96 | 574.92 | 01-FEB-00:03 | 0.97 |
March | 0.153987E+10 | 0.96 | 574.92 | 01-MAR-00:10 | 0.97 |
April | 0.149020E+10 | 0.96 | 574.92 | 01-APR-00:10 | 0.96 |
May | 0.153987E+10 | 0.96 | 574.92 | 01-MAY-00:10 | 0.96 |
June | 0.149020E+10 | 0.96 | 574.92 | 01-JUN-00:20 | 0.96 |
July | 0.153987E+10 | 0.96 | 574.92 | 01-JUL-00:03 | 0.96 |
August | 0.153987E+10 | 0.96 | 574.92 | 01-AUG-00:03 | 0.96 |
September | 0.149020E+10 | 0.96 | 574.92 | 01-SEP-00:05 | 0.96 |
October | 0.153987E+10 | 0.96 | 574.92 | 01-OCT-00:10 | 0.96 |
November | 0.149020E+10 | 0.96 | 574.92 | 01-NOV-00:10 | 0.96 |
December | 0.153987E+10 | 0.96 | 574.92 | 01-DEC-00:10 | 0.96 |
Annual Sum or Average | 0.181308E+11 | 0.96 | |||
Minimum of Months | 0.139085E+10 | 0.96 | 574.92 | 0.96 | |
Maximum of Months | 0.153987E+10 | 0.97 | 574.92 | 0.97 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.127822E+09 | 0.115039E+09 | 1491.36 | 30-JAN-07:10 | 1342.22 | 1342.22 | 45.74 | 13.67 |
February | 0.123566E+09 | 0.111209E+09 | 1690.16 | 02-FEB-07:10 | 1521.14 | 1521.14 | 48.65 | 14.40 |
March | 9978335.63 | 8980502.06 | 1154.62 | 06-MAR-06:01 | 1039.15 | 1039.15 | 47.15 | 12.23 |
April | 2282724.29 | 2054451.86 | 410.52 | 03-APR-05:01 | 369.46 | 369.46 | 44.45 | 7.67 |
May | 36701.15 | 33031.04 | 43.50 | 02-MAY-05:03 | 39.15 | 39.15 | 26.40 | 2.41 |
June | 3958.02 | 3562.22 | 0.98 | 02-JUN-05:02 | 0.89 | 0.89 | 22.67 | 0.14 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 21.61 | 0.00 |
August | 2.29 | 2.06 | 0.02 | 07-AUG-05:10 | 0.01 | 0.01 | 21.61 | 0.00 |
September | 184727.73 | 166254.96 | 201.26 | 30-SEP-05:02 | 181.14 | 181.14 | 29.35 | 5.46 |
October | 1188447.72 | 1069602.95 | 339.57 | 23-OCT-05:01 | 305.62 | 305.62 | 32.40 | 7.04 |
November | 17564956.79 | 15808461.11 | 1151.94 | 27-NOV-06:02 | 1036.75 | 1036.75 | 47.11 | 12.21 |
December | 41187541.60 | 37068787.44 | 1158.86 | 11-DEC-06:02 | 1042.98 | 1042.98 | 47.55 | 12.24 |
Annual Sum or Average | 0.323815E+09 | 0.291433E+09 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.61 | 0.00 | |
Maximum of Months | 0.127822E+09 | 0.115039E+09 | 1690.16 | 1521.14 | 1521.14 | 48.65 | 14.40 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 3887.68 | 3498.91 | 1.19 | 12-JAN-11:20 | 1.07 | 1.07 | 6.70 | 0.33 |
February | 3030.90 | 2727.81 | 1.20 | 24-FEB-10:40 | 1.08 | 1.08 | 6.70 | 0.33 |
March | 1392827.20 | 1253544.48 | 57.16 | 19-MAR-14:23 | 51.44 | 51.44 | 6.70 | 6.39 |
April | 88792124.89 | 79912912.40 | 2305.09 | 18-APR-12:40 | 2074.59 | 2074.59 | 6.71 | 40.46 |
May | 0.202688E+09 | 0.182419E+09 | 2100.42 | 31-MAY-11:10 | 1890.38 | 1890.38 | 9.48 | 38.87 |
June | 0.773830E+09 | 0.696447E+09 | 12370.20 | 30-JUN-05:05 | 11133.18 | 11133.18 | 11.88 | 80.73 |
July | 0.105535E+10 | 0.949811E+09 | 12363.07 | 26-JUL-05:03 | 11126.76 | 11126.76 | 9.95 | 80.73 |
August | 0.110660E+10 | 0.995942E+09 | 13773.69 | 29-AUG-13:20 | 12396.32 | 12396.32 | 10.75 | 84.22 |
September | 0.477701E+09 | 0.429931E+09 | 13878.76 | 05-SEP-13:43 | 12490.88 | 12490.88 | 11.19 | 84.50 |
October | 16112627.16 | 14501364.45 | 666.89 | 01-OCT-15:11 | 600.20 | 600.20 | 6.70 | 23.17 |
November | 2197040.97 | 1977336.88 | 297.89 | 03-NOV-13:20 | 268.10 | 268.10 | 6.70 | 15.67 |
December | 1798.77 | 1618.89 | 0.15 | 01-DEC-08:40 | 0.14 | 0.14 | 6.70 | 0.04 |
Annual Sum or Average | 0.372467E+10 | 0.335220E+10 | ||||||
Minimum of Months | 1798.77 | 1618.89 | 0.15 | 0.14 | 0.14 | 6.70 | 0.04 | |
Maximum of Months | 0.110660E+10 | 0.995942E+09 | 13878.76 | 12490.88 | 12490.88 | 11.88 | 84.50 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.509870E+09 | 0.458883E+09 | 4776.19 | 02-JAN-07:03 | 4298.57 | 4298.57 | 6.71 | 42.25 |
February | 0.352674E+09 | 0.317406E+09 | 4776.19 | 06-FEB-07:03 | 4298.57 | 4298.57 | 6.72 | 42.25 |
March | 0.790937E+09 | 0.711843E+09 | 4776.19 | 01-MAR-07:03 | 4298.57 | 4298.57 | 6.72 | 42.25 |
April | 0.235902E+10 | 0.212311E+10 | 4776.19 | 01-APR-07:30 | 4298.57 | 4298.57 | 6.73 | 42.25 |
May | 0.559230E+10 | 0.503307E+10 | 4776.19 | 02-MAY-06:05 | 4298.57 | 4298.57 | 6.74 | 42.25 |
June | 0.719861E+10 | 0.647875E+10 | 4776.19 | 01-JUN-06:11 | 4298.57 | 4298.57 | 8.31 | 42.25 |
July | 0.980563E+10 | 0.882507E+10 | 4776.19 | 01-JUL-00:52 | 4298.57 | 4298.57 | 6.81 | 42.25 |
August | 0.947850E+10 | 0.853065E+10 | 4776.19 | 01-AUG-00:03 | 4298.57 | 4298.57 | 6.91 | 42.25 |
September | 0.502689E+10 | 0.452420E+10 | 4776.19 | 01-SEP-00:52 | 4298.57 | 4298.57 | 6.78 | 42.25 |
October | 0.156165E+10 | 0.140548E+10 | 4776.19 | 01-OCT-09:58 | 4298.57 | 4298.57 | 6.72 | 42.25 |
November | 0.623436E+09 | 0.561092E+09 | 4776.19 | 03-NOV-06:11 | 4298.57 | 4298.57 | 6.92 | 42.25 |
December | 0.521607E+09 | 0.469447E+09 | 4776.19 | 01-DEC-08:30 | 4298.57 | 4298.57 | 6.73 | 42.25 |
Annual Sum or Average | 0.438211E+11 | 0.394390E+11 | ||||||
Minimum of Months | 0.352674E+09 | 0.317406E+09 | 4776.19 | 4298.57 | 4298.57 | 6.71 | 42.25 | |
Maximum of Months | 0.980563E+10 | 0.882507E+10 | 4776.19 | 4298.57 | 4298.57 | 8.31 | 42.25 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 6.70 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 6.72 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
April | 0.116061E+09 | 0.104455E+09 | 4776.19 | 18-APR-09:00 | 4298.57 | 4298.57 | 15.63 | 21.12 |
May | 0.277974E+09 | 0.250177E+09 | 4776.19 | 05-MAY-13:00 | 4298.57 | 4298.57 | 15.17 | 21.12 |
June | 0.111619E+10 | 0.100458E+10 | 4776.19 | 09-JUN-09:40 | 4298.57 | 4298.57 | 15.44 | 21.12 |
July | 0.173089E+10 | 0.155780E+10 | 4776.19 | 03-JUL-07:30 | 4298.57 | 4298.57 | 14.93 | 21.12 |
August | 0.177297E+10 | 0.159567E+10 | 4776.19 | 01-AUG-07:30 | 4298.57 | 4298.57 | 14.89 | 21.12 |
September | 0.439887E+09 | 0.395898E+09 | 4776.19 | 01-SEP-15:40 | 4298.57 | 4298.57 | 15.85 | 21.12 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 6.73 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
Annual Sum or Average | 0.545398E+10 | 0.490858E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 | |
Maximum of Months | 0.177297E+10 | 0.159567E+10 | 4776.19 | 4298.57 | 4298.57 | 15.85 | 21.12 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.104257E+11 | 0.938314E+10 | 3892.52 | 01-JAN-00:03 | 3503.26 | 3503.26 | 18.49 | 16.26 |
February | 0.941678E+10 | 0.847510E+10 | 3892.52 | 01-FEB-00:03 | 3503.26 | 3503.26 | 18.73 | 16.26 |
March | 0.104257E+11 | 0.938314E+10 | 3892.52 | 01-MAR-00:10 | 3503.26 | 3503.26 | 19.54 | 16.26 |
April | 0.100894E+11 | 0.908046E+10 | 3892.52 | 01-APR-00:10 | 3503.26 | 3503.26 | 20.31 | 16.26 |
May | 0.104257E+11 | 0.938314E+10 | 3892.52 | 01-MAY-00:10 | 3503.26 | 3503.26 | 18.90 | 16.26 |
June | 0.100894E+11 | 0.908046E+10 | 3892.52 | 01-JUN-00:10 | 3503.26 | 3503.26 | 19.48 | 16.26 |
July | 0.104257E+11 | 0.938314E+10 | 3892.52 | 01-JUL-00:03 | 3503.26 | 3503.26 | 24.77 | 16.26 |
August | 0.104257E+11 | 0.938314E+10 | 3892.52 | 01-AUG-00:03 | 3503.26 | 3503.26 | 31.03 | 16.26 |
September | 0.100894E+11 | 0.908046E+10 | 3892.52 | 01-SEP-00:05 | 3503.26 | 3503.26 | 18.93 | 16.26 |
October | 0.104257E+11 | 0.938314E+10 | 3892.52 | 01-OCT-00:10 | 3503.26 | 3503.26 | 19.33 | 16.26 |
November | 0.100894E+11 | 0.908046E+10 | 3892.52 | 01-NOV-00:10 | 3503.26 | 3503.26 | 19.83 | 16.26 |
December | 0.104257E+11 | 0.938314E+10 | 3892.52 | 01-DEC-00:10 | 3503.26 | 3503.26 | 20.08 | 16.26 |
Annual Sum or Average | 0.122754E+12 | 0.110479E+12 | ||||||
Minimum of Months | 0.941678E+10 | 0.847510E+10 | 3892.52 | 3503.26 | 3503.26 | 18.49 | 16.26 | |
Maximum of Months | 0.104257E+11 | 0.938314E+10 | 3892.52 | 3503.26 | 3503.26 | 31.03 | 16.26 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:03 | 16.86 | 16.86 | 56.83 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:01 | 16.86 | 16.86 | 56.78 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:01 | 16.86 | 16.86 | 56.69 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:03 | 16.86 | 16.86 | 56.59 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:02 | 16.86 | 16.86 | 57.05 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 56.98 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 57.17 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 57.29 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 57.32 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 56.98 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:03 | 16.86 | 16.86 | 57.05 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:01 | 16.86 | 16.86 | 57.05 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 56.59 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.32 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.195353E+10 | 0.175818E+10 | 18302.70 | 09-JAN-19:20 | 16472.43 | 16472.43 | 21.14 | 74.20 |
February | 0.135124E+10 | 0.121611E+10 | 18302.72 | 27-FEB-09:00 | 16472.45 | 16472.45 | 21.14 | 74.20 |
March | 0.303091E+10 | 0.272782E+10 | 18313.65 | 28-MAR-15:00 | 16482.29 | 16482.29 | 21.97 | 74.20 |
April | 0.942262E+10 | 0.848036E+10 | 36778.09 | 18-APR-12:10 | 33100.28 | 33100.28 | 27.29 | 148.40 |
May | 0.224062E+11 | 0.201656E+11 | 36750.74 | 30-MAY-12:10 | 33075.67 | 33075.67 | 26.41 | 148.40 |
June | 0.316725E+11 | 0.285053E+11 | 36844.58 | 26-JUN-07:20 | 33160.12 | 33160.12 | 30.66 | 148.40 |
July | 0.437145E+11 | 0.393430E+11 | 36844.58 | 03-JUL-08:50 | 33160.12 | 33160.12 | 29.74 | 148.40 |
August | 0.426244E+11 | 0.383620E+11 | 36844.58 | 01-AUG-08:30 | 33160.12 | 33160.12 | 29.66 | 148.40 |
September | 0.208606E+11 | 0.187745E+11 | 36776.83 | 11-SEP-09:40 | 33099.14 | 33099.14 | 27.25 | 148.40 |
October | 0.598600E+10 | 0.538740E+10 | 18353.07 | 20-OCT-15:00 | 16517.77 | 16517.77 | 24.96 | 74.20 |
November | 0.238894E+10 | 0.215005E+10 | 18316.87 | 03-NOV-14:20 | 16485.19 | 16485.19 | 22.21 | 74.20 |
December | 0.199852E+10 | 0.179867E+10 | 18302.73 | 13-DEC-14:30 | 16472.46 | 16472.46 | 21.14 | 74.20 |
Annual Sum or Average | 0.187410E+12 | 0.168669E+12 | ||||||
Minimum of Months | 0.135124E+10 | 0.121611E+10 | 18302.70 | 16472.43 | 16472.43 | 21.14 | 74.20 | |
Maximum of Months | 0.437145E+11 | 0.393430E+11 | 36844.58 | 33160.12 | 33160.12 | 30.66 | 148.40 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 33.84 | 33.84 | 252288.76 | 2198958.34 | 02-JAN-04:01 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 35.90 | 35.90 | 192963.86 | 2052412.88 | 02-FEB-07:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 34.33 | 82.00 | 49708.08 | 1801559.74 | 07-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 26.94 | 26.94 | 15738.39 | 1373515.24 | 03-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 23.17 | 23.17 | 406.45 | 559398.25 | 02-MAY-05:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.60 | 22.60 | 60.49 | 35775.05 | 02-JUN-05:02 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 21.61 | 21.61 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 21.61 | 21.61 | 0.03 | 622.55 | 07-AUG-05:10 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 21.61 | 21.61 | 1943.06 | 1201868.44 | 30-SEP-05:02 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.82 | 22.82 | 10330.16 | 1459266.27 | 23-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 23.43 | 23.43 | 69533.41 | 1905170.97 | 29-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 27.18 | 27.18 | 147218.87 | 2002635.14 | 14-DEC-06:01 |
Annual Sum or Average | 0.00 | 61040.47 | ||||||
Minimum of Months | 0.00 | 0.00 | 21.61 | 21.61 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 35.90 | 82.00 | 252288.76 | 2198958.34 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 172.24 | 5206.82 | 12-JAN-11:20 | 6.73 | 6.70 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 133.98 | 7108.16 | 24-FEB-10:40 | 6.74 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 3077.73 | 233005.27 | 25-MAR-15:00 | 8.02 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 57787.97 | 1912192.41 | 18-APR-09:55 | 12.10 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 138891.32 | 1810290.31 | 30-MAY-11:00 | 11.81 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 405171.20 | 2564472.97 | 26-JUN-07:20 | 13.95 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 554418.76 | 2507634.87 | 05-JUL-10:30 | 13.79 | 6.70 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 532252.27 | 3421606.45 | 03-AUG-05:03 | 16.38 | 7.99 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 214607.37 | 2598150.71 | 05-SEP-14:43 | 14.05 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 17306.34 | 1061743.19 | 20-OCT-15:00 | 12.70 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 2139.27 | 300804.36 | 03-NOV-14:20 | 8.40 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 179.22 | 5028.20 | 01-DEC-08:40 | 6.73 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 161726.46 | 0.00 | ||||||
Minimum of Months | 133.98 | 5028.20 | 6.73 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 554418.76 | 3421606.45 | 16.38 | 7.99 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1.10 | 1033.48 | 12-JAN-11:20 | 7.45 | 6.70 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 2.77 | 3003.72 | 24-FEB-10:40 | 8.85 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 2812.79 | 232353.63 | 25-MAR-15:00 | 17.89 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 56950.95 | 1776734.40 | 18-APR-09:30 | 18.40 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 137053.23 | 1805334.33 | 30-MAY-11:00 | 18.15 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 403664.83 | 3961929.21 | 26-JUN-04:12 | 18.43 | 12.27 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 551685.74 | 3795923.05 | 26-JUL-04:12 | 17.94 | 12.04 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 529946.63 | 4201124.10 | 04-AUG-04:12 | 19.71 | 12.57 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 214705.25 | 3089012.20 | 11-SEP-05:03 | 15.84 | 11.05 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 16794.10 | 1061395.25 | 20-OCT-15:00 | 18.23 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 1923.49 | 297208.12 | 03-NOV-14:20 | 15.32 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 3.94 | 844.91 | 01-DEC-08:40 | 11.24 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 160834.62 | 0.00 | ||||||
Minimum of Months | 1.10 | 844.91 | 7.45 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 551685.74 | 4201124.10 | 19.71 | 12.57 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 10092.38 | 107315.98 | 12-JAN-16:50 | 20.23 | 18.33 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 42410.18 | 145100.87 | 24-FEB-17:55 | 20.90 | 18.33 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 80471.16 | 303831.74 | 19-MAR-16:00 | 23.70 | 20.14 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 217324.11 | 1693659.13 | 16-APR-16:00 | 47.59 | 33.87 | 0.00 | 0.00 | 01-APR-00:10 |
May | 85745.46 | 994201.51 | 31-MAY-15:00 | 35.70 | 31.49 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 394660.32 | 1431339.09 | 13-JUN-12:10 | 43.16 | 31.19 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 723777.88 | 1826571.95 | 26-JUL-15:10 | 49.82 | 35.28 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 864610.83 | 2109365.63 | 04-AUG-16:00 | 54.54 | 39.43 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 165650.64 | 1137917.04 | 06-SEP-15:00 | 38.17 | 33.77 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 59828.64 | 587121.70 | 20-OCT-15:00 | 28.66 | 24.69 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 75681.13 | 161913.45 | 16-NOV-08:45 | 21.20 | 18.33 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 96628.16 | 235485.60 | 15-DEC-11:43 | 22.50 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 236555.51 | 0.00 | ||||||
Minimum of Months | 10092.38 | 107315.98 | 20.23 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 864610.83 | 2109365.63 | 54.54 | 39.43 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 57.87 | 57.87 | 16465.26 | 59152.49 | 31-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 57.23 | 57.23 | 16894.76 | 59537.43 | 21-FEB-12:20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.22 | 57.22 | 17777.99 | 59447.92 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.29 | 57.29 | 16020.56 | 57771.79 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.95 | 57.95 | 15596.57 | 55043.52 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.59 | 57.59 | 14913.99 | 51404.48 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 57.75 | 57.75 | 12955.53 | 48011.42 | 03-JUL-12:00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 57.85 | 57.85 | 13823.67 | 46092.58 | 01-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 57.87 | 57.87 | 13127.28 | 47179.80 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.80 | 57.80 | 13755.39 | 50235.49 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.66 | 57.66 | 14898.82 | 53759.39 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.49 | 57.49 | 15304.55 | 56889.04 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 15117.59 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.22 | 57.22 | 12955.53 | 46092.58 | ||
Maximum of Months | 0.00 | 0.00 | 57.95 | 57.95 | 17777.99 | 59537.43 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 14.35 | 11212.69 | 09-JAN-19:20 | 21.14 | 20.22 | 2483.75 | 195810.16 | 05-JAN-07:02 |
February | 12.34 | 11601.38 | 27-FEB-09:00 | 21.14 | 20.22 | 1963.16 | 183681.08 | 18-FEB-07:03 |
March | 2475.56 | 269210.46 | 28-MAR-15:00 | 21.97 | 21.10 | 1936.89 | 180098.61 | 06-MAR-15:30 |
April | 86735.22 | 3841407.29 | 18-APR-12:10 | 27.29 | 24.17 | 2358.62 | 168903.50 | 25-APR-06:05 |
May | 185765.84 | 3291210.00 | 30-MAY-12:10 | 26.41 | 23.21 | 2664.97 | 125034.85 | 02-MAY-13:50 |
June | 739667.60 | 6096250.20 | 26-JUN-07:50 | 30.93 | 26.28 | 641.38 | 122188.87 | 02-JUN-06:00 |
July | 1030486.66 | 6387531.04 | 26-JUL-15:00 | 31.40 | 28.25 | 338.50 | 73131.49 | 23-JUL-22:40 |
August | 989773.73 | 8049673.38 | 04-AUG-07:20 | 34.08 | 28.61 | 579.79 | 56823.04 | 16-AUG-04:35 |
September | 293349.74 | 3816045.14 | 11-SEP-09:40 | 27.25 | 23.76 | 1342.53 | 123535.31 | 29-SEP-11:50 |
October | 17776.12 | 1196018.25 | 20-OCT-15:00 | 24.96 | 21.10 | 1801.85 | 163937.31 | 26-OCT-20:40 |
November | 1711.20 | 345078.75 | 03-NOV-14:20 | 22.21 | 21.10 | 2140.47 | 199460.13 | 12-NOV-11:50 |
December | 18.86 | 11827.22 | 13-DEC-14:30 | 21.14 | 20.22 | 2324.74 | 180563.86 | 26-DEC-15:10 |
Annual Sum or Average | 281260.01 | 1713.71 | ||||||
Minimum of Months | 12.34 | 11212.69 | 21.14 | 20.22 | 338.50 | 56823.04 | ||
Maximum of Months | 1030486.66 | 8049673.38 | 34.08 | 28.61 | 2664.97 | 199460.13 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.217042E+11 | 0.00 | 6487283.68 | 0.361502E+10 | 0.00 | 0.00 |
February | 0.192539E+11 | 0.00 | 5808442.14 | 0.385107E+10 | 0.00 | 0.00 |
March | 0.149090E+10 | 0.00 | 0.778716E+09 | 0.614337E+10 | 0.00 | 0.00 |
April | 0.271955E+09 | 0.00 | 0.147235E+11 | 0.827074E+10 | 0.00 | 0.00 |
May | 4038677.48 | 0.00 | 0.327260E+11 | 0.889174E+10 | 0.00 | 0.00 |
June | 407.01 | 0.00 | 0.103584E+12 | 0.138907E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.155498E+12 | 0.165632E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.148423E+12 | 0.167220E+11 | 0.00 | 0.00 |
September | 26244482.23 | 0.00 | 0.491978E+11 | 0.922022E+10 | 0.00 | 0.00 |
October | 90434759.91 | 0.00 | 0.447415E+10 | 0.682469E+10 | 0.00 | 0.00 |
November | 0.211338E+10 | 0.00 | 0.477912E+09 | 0.520084E+10 | 0.00 | 0.00 |
December | 0.606610E+10 | 0.00 | 8440304.19 | 0.464273E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.510211E+11 | 0.00 | 0.509903E+12 | 0.103836E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 5808442.14 | 0.361502E+10 | 0.00 | 0.00 |
Maximum of Months | 0.217042E+11 | 0.00 | 0.155498E+12 | 0.167220E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.535352E+12 | 0.00 | 15243042.34 | 0.435340E+11 | 0.00 | 0.00 |
February | 0.370776E+12 | 0.00 | 13470055.81 | 0.343217E+11 | 0.00 | 0.00 |
March | 0.103109E+12 | 0.00 | 0.561787E+10 | 0.398596E+11 | 0.00 | 0.00 |
April | 0.303210E+11 | 0.00 | 0.111140E+12 | 0.489849E+11 | 0.00 | 0.00 |
May | 0.634906E+09 | 0.00 | 0.276665E+12 | 0.667277E+11 | 0.00 | 0.00 |
June | 3238238.06 | 0.00 | 0.797963E+12 | 0.959430E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.109346E+13 | 0.996376E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.104528E+13 | 0.101372E+12 | 0.00 | 0.00 |
September | 0.334666E+10 | 0.00 | 0.416632E+12 | 0.670959E+11 | 0.00 | 0.00 |
October | 0.201162E+11 | 0.00 | 0.345014E+11 | 0.420723E+11 | 0.00 | 0.00 |
November | 0.141843E+12 | 0.00 | 0.401584E+10 | 0.361004E+11 | 0.00 | 0.00 |
December | 0.315118E+12 | 0.00 | 4438281.89 | 0.380315E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.152062E+13 | 0.00 | 0.378530E+13 | 0.713680E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 4438281.89 | 0.343217E+11 | 0.00 | 0.00 |
Maximum of Months | 0.535352E+12 | 0.00 | 0.109346E+13 | 0.101372E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.942972E+11 | 0.00 | 8229035.95 | 0.516479E+10 | 0.00 | 0.00 |
February | 0.639607E+11 | 0.00 | 9534763.10 | 0.417502E+10 | 0.00 | 0.00 |
March | 0.251861E+11 | 0.00 | 0.441598E+09 | 0.401729E+10 | 0.00 | 0.00 |
April | 0.948858E+10 | 0.00 | 0.119688E+11 | 0.459613E+10 | 0.00 | 0.00 |
May | 0.456562E+09 | 0.00 | 0.292761E+11 | 0.609060E+10 | 0.00 | 0.00 |
June | 0.160962E+09 | 0.00 | 0.881142E+11 | 0.965449E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.119136E+12 | 0.100303E+11 | 0.00 | 0.00 |
August | 100599.87 | 0.00 | 0.110097E+12 | 0.989733E+10 | 0.00 | 0.00 |
September | 0.167624E+10 | 0.00 | 0.431463E+11 | 0.596398E+10 | 0.00 | 0.00 |
October | 0.757683E+10 | 0.00 | 0.282526E+10 | 0.359630E+10 | 0.00 | 0.00 |
November | 0.338597E+11 | 0.00 | 0.242071E+09 | 0.397835E+10 | 0.00 | 0.00 |
December | 0.644858E+11 | 0.00 | 4729351.70 | 0.467001E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.301149E+12 | 0.00 | 0.405270E+12 | 0.718346E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 4729351.70 | 0.359630E+10 | 0.00 | 0.00 |
Maximum of Months | 0.942972E+11 | 0.00 | 0.119136E+12 | 0.100303E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.278989E+11 | 0.00 | 0.00 | 0.157150E+10 | 0.00 | 0.00 |
February | 0.153104E+11 | 0.00 | 0.00 | 0.164999E+10 | 0.00 | 0.00 |
March | 0.409574E+10 | 0.00 | 0.847160E+09 | 0.432779E+10 | 0.00 | 0.00 |
April | 0.951521E+09 | 0.00 | 0.781182E+10 | 0.584959E+10 | 0.00 | 0.00 |
May | 2894879.86 | 0.00 | 0.197779E+11 | 0.965142E+10 | 0.00 | 0.00 |
June | 401257.19 | 0.00 | 0.367861E+11 | 0.102913E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.606401E+11 | 0.101792E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.688467E+11 | 0.130159E+11 | 0.00 | 0.00 |
September | 4466895.75 | 0.00 | 0.309664E+11 | 0.132286E+11 | 0.00 | 0.00 |
October | 24136523.46 | 0.00 | 0.323704E+10 | 0.127153E+11 | 0.00 | 0.00 |
November | 0.331711E+10 | 0.00 | 0.157464E+09 | 0.768424E+10 | 0.00 | 0.00 |
December | 0.106796E+11 | 0.00 | 0.00 | 0.220202E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.622852E+11 | 0.00 | 0.229071E+12 | 0.923669E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.157150E+10 | 0.00 | 0.00 |
Maximum of Months | 0.278989E+11 | 0.00 | 0.688467E+11 | 0.132286E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.107953E+11 | 0.246335E+12 | 0.00 | 47.65 |
February | 0.00 | 0.00 | 0.156583E+11 | 0.307153E+12 | 0.00 | 74.03 |
March | 0.00 | 0.00 | 0.219438E+11 | 0.365662E+12 | 0.00 | 91.03 |
April | 0.00 | 0.00 | 0.161343E+12 | 0.338432E+12 | 0.00 | 70.71 |
May | 0.00 | 0.00 | 0.257109E+11 | 0.163780E+12 | 0.00 | 15.50 |
June | 0.00 | 0.00 | 0.283122E+12 | 0.181617E+12 | 0.00 | 1.11 |
July | 0.00 | 0.00 | 0.815415E+12 | 0.292458E+12 | 0.00 | 0.01 |
August | 0.00 | 0.00 | 0.108855E+13 | 0.351915E+12 | 0.00 | 1.58 |
September | 0.00 | 0.00 | 0.651331E+11 | 0.175557E+12 | 0.00 | 17.45 |
October | 0.00 | 0.00 | 0.170852E+11 | 0.301354E+12 | 0.00 | 67.53 |
November | 0.00 | 0.00 | 0.175441E+11 | 0.326964E+12 | 0.00 | 78.38 |
December | 0.00 | 0.00 | 0.223371E+11 | 0.389144E+12 | 0.00 | 99.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.254464E+13 | 0.344037E+13 | 0.00 | 564.62 |
Minimum of Months | 0.00 | 0.00 | 0.107953E+11 | 0.163780E+12 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.00 | 0.108855E+13 | 0.389144E+12 | 0.00 | 99.64 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.315385E+10 | 0.228723E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.970229E+10 | 0.342758E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.182590E+11 | 0.512290E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.245376E+11 | 0.615455E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.734340E+10 | 0.306753E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.140646E+11 | 0.446214E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.213330E+11 | 0.605871E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.274576E+11 | 0.722478E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.725860E+10 | 0.305045E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.127863E+11 | 0.408349E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.175297E+11 | 0.491674E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.234809E+11 | 0.612291E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.186907E+12 | 0.559790E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.315385E+10 | 0.228723E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.274576E+11 | 0.722478E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.354957E+10 | 0.160049E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.643820E+11 | 0.272942E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.151338E+12 | 0.449533E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.219960E+12 | 0.565058E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.631359E+11 | 0.280731E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.130389E+12 | 0.420014E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.201164E+12 | 0.575076E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.259499E+12 | 0.686438E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.615911E+11 | 0.277454E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.104762E+12 | 0.359434E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.140486E+12 | 0.422339E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.186781E+12 | 0.520306E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.158704E+13 | 0.498937E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.354957E+10 | 0.160049E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.259499E+12 | 0.686438E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.149902E+09 | 0.157537E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.436944E+10 | 0.232735E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.133216E+11 | 0.418669E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.207242E+11 | 0.546416E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.580575E+10 | 0.273755E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.128681E+11 | 0.420237E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.200996E+11 | 0.578430E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.258559E+11 | 0.688680E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.550328E+10 | 0.267445E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.864801E+10 | 0.327627E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.118222E+11 | 0.383599E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.164230E+11 | 0.482369E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.145591E+12 | 0.477750E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.149902E+09 | 0.157537E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.258559E+11 | 0.688680E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.361502E+10 | 6487283.68 | 0.217042E+11 | 0.489323E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.385107E+10 | 5808442.14 | 0.192539E+11 | 0.202693E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.614337E+10 | 0.778716E+09 | 0.149090E+10 | 0.140590E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.827074E+10 | 0.147235E+11 | 0.271955E+09 | 0.367467E+10 | 0.515766E+09 | 0.00 | 0.00 | 0.00 |
May | 0.889174E+10 | 0.327260E+11 | 4038677.48 | 0.205098E+09 | 0.387410E+09 | 0.00 | 0.00 | 0.00 |
June | 0.138907E+11 | 0.103584E+12 | 407.01 | 20536705.59 | 0.388679E+10 | 0.00 | 0.00 | 0.00 |
July | 0.165632E+11 | 0.155498E+12 | 0.00 | 34750574.87 | 0.560188E+10 | 0.00 | 0.00 | 0.00 |
August | 0.167220E+11 | 0.148423E+12 | 0.00 | 0.180567E+09 | 0.550848E+10 | 0.00 | 0.00 | 0.00 |
September | 0.922022E+10 | 0.491978E+11 | 26244482.23 | 0.318900E+09 | 0.123935E+10 | 0.00 | 0.00 | 0.00 |
October | 0.682469E+10 | 0.447415E+10 | 90434759.91 | 0.165448E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.520084E+10 | 0.477912E+09 | 0.211338E+10 | 0.152457E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.464273E+10 | 8440304.19 | 0.606610E+10 | 0.348542E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.103836E+12 | 0.509903E+12 | 0.510211E+11 | 0.139449E+12 | 0.171397E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.361502E+10 | 5808442.14 | 0.00 | 20536705.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167220E+11 | 0.155498E+12 | 0.217042E+11 | 0.489323E+11 | 0.560188E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.435340E+11 | 15243042.34 | 0.535352E+12 | 0.528589E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.343217E+11 | 13470055.81 | 0.370776E+12 | 0.269945E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.398596E+11 | 0.561787E+10 | 0.103109E+12 | 0.230658E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.489849E+11 | 0.111140E+12 | 0.303210E+11 | 0.744558E+11 | 0.536260E+10 | 0.00 | 0.00 | 0.00 |
May | 0.667277E+11 | 0.276665E+12 | 0.634906E+09 | 0.333791E+10 | 0.397222E+10 | 0.00 | 0.00 | 0.00 |
June | 0.959430E+11 | 0.797963E+12 | 3238238.06 | 0.298380E+09 | 0.385963E+11 | 0.00 | 0.00 | 0.00 |
July | 0.996376E+11 | 0.109346E+13 | 0.00 | 0.570505E+09 | 0.558527E+11 | 0.00 | 0.00 | 0.00 |
August | 0.101372E+12 | 0.104528E+13 | 0.00 | 0.214174E+10 | 0.545803E+11 | 0.00 | 0.00 | 0.00 |
September | 0.670959E+11 | 0.416632E+12 | 0.334666E+10 | 0.522498E+10 | 0.130900E+11 | 0.00 | 0.00 | 0.00 |
October | 0.420723E+11 | 0.345014E+11 | 0.201162E+11 | 0.346660E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.361004E+11 | 0.401584E+10 | 0.141843E+12 | 0.217034E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.380315E+11 | 4438281.89 | 0.315118E+12 | 0.455636E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.713680E+12 | 0.378530E+13 | 0.152062E+13 | 0.182256E+13 | 0.171454E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.343217E+11 | 4438281.89 | 0.00 | 0.298380E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101372E+12 | 0.109346E+13 | 0.535352E+12 | 0.528589E+12 | 0.558527E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.516479E+10 | 8229035.95 | 0.942972E+11 | 0.532770E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.417502E+10 | 9534763.10 | 0.639607E+11 | 0.291490E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.401729E+10 | 0.441598E+09 | 0.251861E+11 | 0.265539E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.459613E+10 | 0.119688E+11 | 0.948858E+10 | 0.997823E+10 | 0.403556E+09 | 0.00 | 0.00 | 0.00 |
May | 0.609060E+10 | 0.292761E+11 | 0.456562E+09 | 0.498959E+09 | 0.286580E+09 | 0.00 | 0.00 | 0.00 |
June | 0.965449E+10 | 0.881142E+11 | 0.160962E+09 | 46054876.34 | 0.329156E+10 | 0.00 | 0.00 | 0.00 |
July | 0.100303E+11 | 0.119136E+12 | 0.00 | 10262611.30 | 0.463360E+10 | 0.00 | 0.00 | 0.00 |
August | 0.989733E+10 | 0.110097E+12 | 100599.87 | 0.174959E+09 | 0.481526E+10 | 0.00 | 0.00 | 0.00 |
September | 0.596398E+10 | 0.431463E+11 | 0.167624E+10 | 0.986445E+09 | 0.102662E+10 | 0.00 | 0.00 | 0.00 |
October | 0.359630E+10 | 0.282526E+10 | 0.757683E+10 | 0.573475E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.397835E+10 | 0.242071E+09 | 0.338597E+11 | 0.244146E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.467001E+10 | 4729351.70 | 0.644858E+11 | 0.489948E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.718346E+11 | 0.405270E+12 | 0.301149E+12 | 0.199819E+12 | 0.144572E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.359630E+10 | 4729351.70 | 0.00 | 10262611.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.100303E+11 | 0.119136E+12 | 0.942972E+11 | 0.532770E+11 | 0.481526E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.157150E+10 | 0.00 | 0.278989E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164999E+10 | 0.00 | 0.153104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.432779E+10 | 0.847160E+09 | 0.409574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.584959E+10 | 0.781214E+10 | 0.951521E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.965142E+10 | 0.197779E+11 | 2894879.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.102913E+11 | 0.367861E+11 | 401257.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.101792E+11 | 0.606401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130159E+11 | 0.688467E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132286E+11 | 0.309664E+11 | 4466895.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.127153E+11 | 0.323704E+10 | 24136523.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.768424E+10 | 0.157464E+09 | 0.331711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.220202E+10 | 0.00 | 0.106796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.923669E+11 | 0.229071E+12 | 0.622852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.157150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.132286E+11 | 0.688467E+11 | 0.278989E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.113655E+12 | 0.620845E+10 | 0.00 | 0.00 | 0.00 | 0.127519E+12 | 0.00 | 0.00 |
February | 0.102656E+12 | 0.101580E+11 | 0.00 | 0.00 | 0.00 | 0.198104E+12 | 0.00 | 0.00 |
March | 0.113655E+12 | 0.146441E+11 | 0.00 | 0.00 | 0.00 | 0.243610E+12 | 0.00 | 0.00 |
April | 0.109989E+12 | 0.122971E+12 | 0.00 | 0.00 | 0.00 | 0.189219E+12 | 0.00 | 0.00 |
May | 0.113655E+12 | 0.172627E+11 | 0.00 | 0.00 | 0.00 | 0.414898E+11 | 0.00 | 0.00 |
June | 0.109989E+12 | 0.214489E+12 | 0.00 | 0.00 | 0.00 | 0.298173E+10 | 0.00 | 0.00 |
July | 0.113655E+12 | 0.636638E+12 | 0.00 | 0.00 | 0.00 | 26122729.93 | 0.00 | 0.00 |
August | 0.113655E+12 | 0.854548E+12 | 0.00 | 0.00 | 0.00 | 0.423506E+10 | 0.00 | 0.00 |
September | 0.109989E+12 | 0.464644E+11 | 0.00 | 0.00 | 0.00 | 0.466892E+11 | 0.00 | 0.00 |
October | 0.113655E+12 | 0.109204E+11 | 0.00 | 0.00 | 0.00 | 0.180720E+12 | 0.00 | 0.00 |
November | 0.109989E+12 | 0.112637E+11 | 0.00 | 0.00 | 0.00 | 0.209750E+12 | 0.00 | 0.00 |
December | 0.113655E+12 | 0.146883E+11 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.133820E+13 | 0.196026E+13 | 0.00 | 0.00 | 0.00 | 0.151098E+13 | 0.00 | 0.00 |
Minimum of Months | 0.102656E+12 | 0.620845E+10 | 0.00 | 0.00 | 0.00 | 26122729.93 | 0.00 | 0.00 |
Maximum of Months | 0.113655E+12 | 0.854548E+12 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.157584E+10 | 0.244246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142334E+10 | 0.769805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157584E+10 | 0.147120E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152500E+10 | 0.199080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157584E+10 | 0.585171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152500E+10 | 0.111275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157584E+10 | 0.168501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.157584E+10 | 0.218086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152500E+10 | 0.573315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157584E+10 | 0.102786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152500E+10 | 0.141379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157584E+10 | 0.189338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185542E+11 | 0.149482E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142334E+10 | 0.244246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.157584E+10 | 0.218086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.151428E+11 | 0.268740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136773E+11 | 0.507652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151428E+11 | 0.121528E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146543E+11 | 0.178108E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151428E+11 | 0.502056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.146543E+11 | 0.103042E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.151428E+11 | 0.158799E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.151428E+11 | 0.205998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.146543E+11 | 0.485000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151428E+11 | 0.839609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146543E+11 | 0.112906E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151428E+11 | 0.149893E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178294E+12 | 0.126639E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136773E+11 | 0.268740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.151428E+11 | 0.205998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.153987E+10 | 0.114407E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139085E+10 | 0.343294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153987E+10 | 0.106748E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.149020E+10 | 0.167503E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153987E+10 | 0.460808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.149020E+10 | 0.101559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153987E+10 | 0.158551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153987E+10 | 0.205090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.149020E+10 | 0.431903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153987E+10 | 0.691161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149020E+10 | 0.947644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153987E+10 | 0.131392E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181308E+11 | 0.115947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.139085E+10 | 0.114407E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153987E+10 | 0.205090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.361502E+10 | 0.217042E+11 | 6487283.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.385107E+10 | 0.192539E+11 | 5808442.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.614337E+10 | 0.149090E+10 | 0.778716E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.827074E+10 | 0.271955E+09 | 0.147235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.889174E+10 | 4038677.48 | 0.327260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138907E+11 | 407.01 | 0.103584E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.165632E+11 | 0.00 | 0.155498E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167220E+11 | 0.00 | 0.148423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.922022E+10 | 26244482.23 | 0.491978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.682469E+10 | 90434759.91 | 0.447415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.520084E+10 | 0.211338E+10 | 0.477912E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.464273E+10 | 0.606610E+10 | 8440304.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.103836E+12 | 0.510211E+11 | 0.509903E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.361502E+10 | 0.00 | 5808442.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167220E+11 | 0.217042E+11 | 0.155498E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.435340E+11 | 0.535352E+12 | 15243042.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.343217E+11 | 0.370776E+12 | 13470055.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.398596E+11 | 0.103109E+12 | 0.561787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.489849E+11 | 0.303210E+11 | 0.111140E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.667277E+11 | 0.634906E+09 | 0.276665E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.959430E+11 | 3238238.06 | 0.797963E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.996376E+11 | 0.00 | 0.109346E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.101372E+12 | 0.00 | 0.104528E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.670959E+11 | 0.334666E+10 | 0.416632E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.420723E+11 | 0.201162E+11 | 0.345014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.361004E+11 | 0.141843E+12 | 0.401584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.380315E+11 | 0.315118E+12 | 4438281.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.713680E+12 | 0.152062E+13 | 0.378530E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.343217E+11 | 0.00 | 4438281.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.101372E+12 | 0.535352E+12 | 0.109346E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.516479E+10 | 0.942972E+11 | 8229035.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.417502E+10 | 0.639607E+11 | 9534763.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.401729E+10 | 0.251861E+11 | 0.441598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.459613E+10 | 0.948858E+10 | 0.119688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.609060E+10 | 0.456562E+09 | 0.292761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.965449E+10 | 0.160962E+09 | 0.881142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.100303E+11 | 0.00 | 0.119136E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.989733E+10 | 100599.87 | 0.110097E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.596398E+10 | 0.167624E+10 | 0.431463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.359630E+10 | 0.757683E+10 | 0.282526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.397835E+10 | 0.338597E+11 | 0.242071E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.467001E+10 | 0.644858E+11 | 4729351.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.718346E+11 | 0.301149E+12 | 0.405270E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.359630E+10 | 0.00 | 4729351.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.100303E+11 | 0.942972E+11 | 0.119136E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.157150E+10 | 0.278989E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164999E+10 | 0.153104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.432779E+10 | 0.409574E+10 | 0.847160E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.584959E+10 | 0.951521E+09 | 0.781182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.965142E+10 | 2894879.86 | 0.197779E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.102913E+11 | 401257.19 | 0.367861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.101792E+11 | 0.00 | 0.606401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130159E+11 | 0.00 | 0.688467E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132286E+11 | 4466895.75 | 0.309664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.127153E+11 | 24136523.46 | 0.323704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.768424E+10 | 0.331711E+10 | 0.157464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.220202E+10 | 0.106796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.923669E+11 | 0.622852E+11 | 0.229071E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.157150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.132286E+11 | 0.278989E+11 | 0.688467E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.113655E+12 | 0.00 | 0.107953E+11 | 0.00 | 0.458685E+10 | 0.00 | 0.00 | 0.00 | 0.128093E+12 | 0.00 | 0.00 | 0.00 |
February | 0.102656E+12 | 0.00 | 0.156583E+11 | 0.00 | 0.550029E+10 | 0.00 | 0.00 | 0.00 | 0.198996E+12 | 0.00 | 0.00 | 0.00 |
March | 0.113655E+12 | 0.00 | 0.219438E+11 | 0.00 | 0.729970E+10 | 0.00 | 0.00 | 0.00 | 0.244707E+12 | 0.00 | 0.00 | 0.00 |
April | 0.109989E+12 | 0.00 | 0.161343E+12 | 0.00 | 0.383722E+11 | 0.00 | 0.00 | 0.00 | 0.190070E+12 | 0.00 | 0.00 | 0.00 |
May | 0.113655E+12 | 0.00 | 0.257109E+11 | 0.00 | 0.844823E+10 | 0.00 | 0.00 | 0.00 | 0.416766E+11 | 0.00 | 0.00 | 0.00 |
June | 0.109989E+12 | 0.00 | 0.283122E+12 | 0.00 | 0.686326E+11 | 0.00 | 0.00 | 0.00 | 0.299515E+10 | 0.00 | 0.00 | 0.00 |
July | 0.113655E+12 | 0.00 | 0.815415E+12 | 0.00 | 0.178777E+12 | 0.00 | 0.00 | 0.00 | 26240318.93 | 0.00 | 0.00 | 0.00 |
August | 0.113655E+12 | 0.00 | 0.108855E+13 | 0.00 | 0.234005E+12 | 0.00 | 0.00 | 0.00 | 0.425412E+10 | 0.00 | 0.00 | 0.00 |
September | 0.109989E+12 | 0.00 | 0.651331E+11 | 0.00 | 0.186686E+11 | 0.00 | 0.00 | 0.00 | 0.468994E+11 | 0.00 | 0.00 | 0.00 |
October | 0.113655E+12 | 0.00 | 0.170852E+11 | 0.00 | 0.616479E+10 | 0.00 | 0.00 | 0.00 | 0.181534E+12 | 0.00 | 0.00 | 0.00 |
November | 0.109989E+12 | 0.00 | 0.175441E+11 | 0.00 | 0.628035E+10 | 0.00 | 0.00 | 0.00 | 0.210694E+12 | 0.00 | 0.00 | 0.00 |
December | 0.113655E+12 | 0.00 | 0.223371E+11 | 0.00 | 0.764876E+10 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133820E+13 | 0.00 | 0.254464E+13 | 0.00 | 0.584384E+12 | 0.00 | 0.00 | 0.00 | 0.151779E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.102656E+12 | 0.00 | 0.107953E+11 | 0.00 | 0.458685E+10 | 0.00 | 0.00 | 0.00 | 26240318.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.113655E+12 | 0.00 | 0.108855E+13 | 0.00 | 0.234005E+12 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.157584E+10 | 0.00 | 0.315385E+10 | 0.00 | 0.711397E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142334E+10 | 0.00 | 0.970229E+10 | 0.00 | 0.200425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157584E+10 | 0.00 | 0.182590E+11 | 0.00 | 0.354706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152500E+10 | 0.00 | 0.245376E+11 | 0.00 | 0.462955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.157584E+10 | 0.00 | 0.734340E+10 | 0.00 | 0.149170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152500E+10 | 0.00 | 0.140646E+11 | 0.00 | 0.293714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157584E+10 | 0.00 | 0.213330E+11 | 0.00 | 0.448288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.157584E+10 | 0.00 | 0.274576E+11 | 0.00 | 0.564894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152500E+10 | 0.00 | 0.725860E+10 | 0.00 | 0.152545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157584E+10 | 0.00 | 0.127863E+11 | 0.00 | 0.250765E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152500E+10 | 0.00 | 0.175297E+11 | 0.00 | 0.339174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157584E+10 | 0.00 | 0.234809E+11 | 0.00 | 0.454707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185542E+11 | 0.00 | 0.186907E+12 | 0.00 | 0.374248E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142334E+10 | 0.00 | 0.315385E+10 | 0.00 | 0.711397E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.157584E+10 | 0.00 | 0.274576E+11 | 0.00 | 0.564894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.151428E+11 | 0.00 | 0.354957E+10 | 0.00 | 0.862162E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136773E+11 | 0.00 | 0.643820E+11 | 0.00 | 0.136169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151428E+11 | 0.00 | 0.151338E+12 | 0.00 | 0.298105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.146543E+11 | 0.00 | 0.219960E+12 | 0.00 | 0.418516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151428E+11 | 0.00 | 0.631359E+11 | 0.00 | 0.129303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.146543E+11 | 0.00 | 0.130389E+12 | 0.00 | 0.273471E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.151428E+11 | 0.00 | 0.201164E+12 | 0.00 | 0.423648E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.151428E+11 | 0.00 | 0.259499E+12 | 0.00 | 0.535010E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.146543E+11 | 0.00 | 0.615911E+11 | 0.00 | 0.130911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.151428E+11 | 0.00 | 0.104762E+12 | 0.00 | 0.208006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.146543E+11 | 0.00 | 0.140486E+12 | 0.00 | 0.275796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151428E+11 | 0.00 | 0.186781E+12 | 0.00 | 0.368879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178294E+12 | 0.00 | 0.158704E+13 | 0.00 | 0.320644E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136773E+11 | 0.00 | 0.354957E+10 | 0.00 | 0.862162E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.151428E+11 | 0.00 | 0.259499E+12 | 0.00 | 0.535010E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.153987E+10 | 0.00 | 0.149902E+09 | 0.00 | 35494809.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139085E+10 | 0.00 | 0.436944E+10 | 0.00 | 0.936502E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153987E+10 | 0.00 | 0.133216E+11 | 0.00 | 0.264682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.149020E+10 | 0.00 | 0.207242E+11 | 0.00 | 0.397396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153987E+10 | 0.00 | 0.580575E+10 | 0.00 | 0.119767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.149020E+10 | 0.00 | 0.128681E+11 | 0.00 | 0.271217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153987E+10 | 0.00 | 0.200996E+11 | 0.00 | 0.424443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153987E+10 | 0.00 | 0.258559E+11 | 0.00 | 0.534693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.149020E+10 | 0.00 | 0.550328E+10 | 0.00 | 0.118425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153987E+10 | 0.00 | 0.864801E+10 | 0.00 | 0.173639E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.149020E+10 | 0.00 | 0.118222E+11 | 0.00 | 0.234579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153987E+10 | 0.00 | 0.164230E+11 | 0.00 | 0.328381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181308E+11 | 0.00 | 0.145591E+12 | 0.00 | 0.296442E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.139085E+10 | 0.00 | 0.149902E+09 | 0.00 | 35494809.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153987E+10 | 0.00 | 0.258559E+11 | 0.00 | 0.534693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 75890903.90 | 0.00 | 0.00 | 0.713828E+11 | 0.00 | 0.31 |
February | 0.00 | 0.00 | 0.00 | 76698848.62 | 0.00 | 0.00 | 0.584035E+11 | 0.00 | 0.34 |
March | 0.00 | 0.00 | 0.00 | 0.101503E+09 | 0.00 | 0.00 | 0.622079E+11 | 0.00 | 0.46 |
April | 0.00 | 0.446064E+09 | 0.00 | 91137899.09 | 0.00 | 0.00 | 0.526200E+11 | 0.00 | 0.61 |
May | 0.00 | 0.629533E+09 | 0.00 | 99033799.23 | 0.00 | 0.00 | 0.461202E+11 | 0.00 | 0.93 |
June | 0.00 | 0.505284E+10 | 0.00 | 0.101058E+09 | 0.00 | 0.00 | 0.314966E+11 | 0.00 | 0.90 |
July | 0.00 | 0.927442E+10 | 0.00 | 89864732.43 | 0.00 | 0.00 | 0.121554E+11 | 0.00 | 0.73 |
August | 0.00 | 0.997936E+10 | 0.00 | 0.108449E+09 | 0.00 | 0.00 | 0.189054E+11 | 0.00 | 0.96 |
September | 0.00 | 0.809259E+09 | 0.00 | 0.107905E+09 | 0.00 | 0.00 | 0.452172E+11 | 0.00 | 0.95 |
October | 0.00 | 0.00 | 0.00 | 0.121701E+09 | 0.00 | 0.00 | 0.708605E+11 | 0.00 | 0.84 |
November | 0.00 | 0.00 | 0.00 | 0.107127E+09 | 0.00 | 0.00 | 0.666318E+11 | 0.00 | 0.60 |
December | 0.00 | 0.00 | 0.00 | 90841670.37 | 0.00 | 0.00 | 0.631618E+11 | 0.00 | 0.32 |
Annual Sum or Average | 0.00 | 0.261915E+11 | 0.00 | 0.117121E+10 | 0.00 | 0.00 | 0.599163E+12 | 0.00 | 0.66 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 75890903.90 | 0.00 | 0.00 | 0.121554E+11 | 0.00 | 0.31 |
Maximum of Months | 0.00 | 0.997936E+10 | 0.00 | 0.121701E+09 | 0.00 | 0.00 | 0.713828E+11 | 0.00 | 0.96 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.145469E+11 | 0.00 | 0.00 | 35570502.72 | 0.00 | 0.00 | 0.245928E+11 | 0.00 | 0.30 |
February | 0.898568E+10 | 0.00 | 0.00 | 50482567.78 | 0.00 | 0.00 | 0.359770E+11 | 0.00 | 0.33 |
March | 0.283881E+10 | 0.00 | 0.00 | 90805259.92 | 0.00 | 0.00 | 0.525029E+11 | 0.00 | 0.48 |
April | 0.461357E+10 | 0.190799E+09 | 0.00 | 92248908.91 | 54338598.07 | 0.00 | 0.523796E+11 | 0.00 | 0.67 |
May | 0.370043E+10 | 0.406478E+09 | 0.00 | 87690260.08 | 58683410.45 | 0.00 | 0.458872E+11 | 0.00 | 0.91 |
June | 0.179369E+10 | 0.548145E+10 | 0.00 | 78457569.59 | 0.834266E+09 | 0.00 | 0.294778E+11 | 0.00 | 0.99 |
July | 0.458310E+10 | 0.111844E+11 | 0.00 | 61189615.14 | 0.220114E+10 | 0.00 | 0.141641E+11 | 0.00 | 1.11 |
August | 0.721017E+10 | 0.112268E+11 | 0.00 | 74589354.07 | 0.225211E+10 | 0.00 | 0.189290E+11 | 0.00 | 1.16 |
September | 0.291855E+10 | 0.452598E+09 | 0.00 | 88912487.02 | 50562996.03 | 0.00 | 0.391406E+11 | 0.00 | 0.82 |
October | 0.265784E+10 | 0.00 | 0.00 | 95426009.74 | 0.00 | 0.00 | 0.546649E+11 | 0.00 | 0.64 |
November | 0.289706E+10 | 0.00 | 0.00 | 80517379.82 | 0.00 | 0.00 | 0.484087E+11 | 0.00 | 0.51 |
December | 0.372277E+10 | 0.00 | 0.00 | 67517896.20 | 0.00 | 0.00 | 0.399988E+11 | 0.00 | 0.34 |
Annual Sum or Average | 0.604686E+11 | 0.289426E+11 | 0.00 | 0.903408E+09 | 0.545110E+10 | 0.00 | 0.456123E+12 | 0.00 | 0.69 |
Minimum of Months | 0.179369E+10 | 0.00 | 0.00 | 35570502.72 | 0.00 | 0.00 | 0.141641E+11 | 0.00 | 0.30 |
Maximum of Months | 0.145469E+11 | 0.112268E+11 | 0.00 | 95426009.74 | 0.225211E+10 | 0.00 | 0.546649E+11 | 0.00 | 1.16 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.297254E+12 | 0.00 | 0.00 | 7071977.76 | 0.00 | 0.124646E+11 | 0.712440E+10 | 0.00 | 0.28 |
February | 0.289874E+12 | 0.00 | 0.00 | 29509202.30 | 0.00 | 0.156949E+10 | 0.362017E+11 | 0.00 | 0.28 |
March | 0.172723E+12 | 0.00 | 0.00 | 0.224621E+09 | 0.00 | 0.228824E+09 | 0.168034E+12 | 0.00 | 0.35 |
April | 0.112643E+12 | 0.132445E+10 | 0.00 | 0.350685E+09 | 0.685371E+09 | 0.00 | 0.239335E+12 | 0.00 | 0.45 |
May | 0.447970E+11 | 0.284210E+10 | 0.00 | 0.570896E+09 | 0.713210E+09 | 0.00 | 0.340577E+12 | 0.00 | 0.74 |
June | 0.145567E+11 | 0.367183E+11 | 0.00 | 0.535436E+09 | 0.329581E+10 | 0.00 | 0.214250E+12 | 0.00 | 0.73 |
July | 0.162136E+11 | 0.713606E+11 | 0.00 | 0.380104E+09 | 0.967882E+10 | 0.00 | 0.978918E+11 | 0.00 | 0.73 |
August | 0.176832E+11 | 0.750557E+11 | 0.00 | 0.533498E+09 | 0.459957E+10 | 0.00 | 0.137003E+12 | 0.00 | 0.75 |
September | 0.449962E+11 | 0.355923E+10 | 0.00 | 0.555938E+09 | 0.614811E+09 | 0.00 | 0.270378E+12 | 0.00 | 0.64 |
October | 0.101653E+12 | 0.00 | 0.00 | 0.384192E+09 | 317449.69 | 0.00 | 0.267601E+12 | 0.00 | 0.44 |
November | 0.166222E+12 | 0.00 | 0.00 | 0.185461E+09 | 0.00 | 0.121288E+10 | 0.146157E+12 | 0.00 | 0.36 |
December | 0.234283E+12 | 0.00 | 0.00 | 27153497.82 | 0.00 | 0.313359E+10 | 0.301671E+11 | 0.00 | 0.28 |
Annual Sum or Average | 0.151290E+13 | 0.190860E+12 | 0.00 | 0.378457E+10 | 0.195879E+11 | 0.186093E+11 | 0.195472E+13 | 0.00 | 0.50 |
Minimum of Months | 0.145567E+11 | 0.00 | 0.00 | 7071977.76 | 0.00 | 0.00 | 0.712440E+10 | 0.00 | 0.28 |
Maximum of Months | 0.297254E+12 | 0.750557E+11 | 0.00 | 0.570896E+09 | 0.967882E+10 | 0.124646E+11 | 0.340577E+12 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.167282E+11 | 0.00 | 0.00 | 404.96 | 0.00 | 0.750546E+10 | 25494275.54 | 0.00 | 0.26 |
February | 0.203157E+11 | 0.00 | 0.00 | 196586.18 | 0.00 | 0.565345E+10 | 0.411106E+09 | 0.00 | 0.27 |
March | 0.203725E+11 | 0.00 | 0.00 | 4988971.04 | 0.00 | 0.942020E+09 | 0.516858E+10 | 0.00 | 0.32 |
April | 0.146118E+11 | 0.181324E+09 | 0.00 | 17369412.99 | 77981709.75 | 0.224987E+09 | 0.139319E+11 | 0.00 | 0.42 |
May | 0.887568E+10 | 0.259246E+09 | 0.00 | 41182742.11 | 31611868.37 | 0.00 | 0.264895E+11 | 0.00 | 0.70 |
June | 0.288545E+10 | 0.392439E+10 | 0.00 | 42747246.49 | 0.488896E+09 | 0.00 | 0.182223E+11 | 0.00 | 0.74 |
July | 0.196064E+10 | 0.830148E+10 | 0.00 | 30870296.46 | 0.110832E+10 | 0.00 | 0.908666E+10 | 0.00 | 0.77 |
August | 0.231289E+10 | 0.744646E+10 | 0.00 | 44565138.44 | 0.561520E+09 | 0.00 | 0.118505E+11 | 0.00 | 0.76 |
September | 0.843539E+10 | 0.344393E+09 | 0.00 | 33774444.01 | 56167497.29 | 1269709.94 | 0.169485E+11 | 0.00 | 0.57 |
October | 0.178107E+11 | 0.00 | 0.00 | 10034962.29 | 17702550.03 | 0.176785E+09 | 0.980137E+10 | 0.00 | 0.37 |
November | 0.173133E+11 | 0.00 | 0.00 | 3883744.96 | 0.00 | 0.159511E+10 | 0.404421E+10 | 0.00 | 0.32 |
December | 0.154519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364669E+10 | 0.00 | 0.00 | 0.26 |
Annual Sum or Average | 0.147074E+12 | 0.204573E+11 | 0.00 | 0.229614E+09 | 0.234220E+10 | 0.197458E+11 | 0.115980E+12 | 0.00 | 0.48 |
Minimum of Months | 0.196064E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.203725E+11 | 0.830148E+10 | 0.00 | 44565138.44 | 0.110832E+10 | 0.750546E+10 | 0.264895E+11 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.156003E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284067E+10 | 0.00 | 0.00 | 0.26 |
February | 0.258140E+10 | 0.00 | 0.00 | 6832.05 | 0.00 | 0.195247E+10 | 23756849.83 | 0.00 | 0.26 |
March | 0.334589E+10 | 0.00 | 0.00 | 1586355.37 | 0.00 | 0.118919E+09 | 0.135629E+10 | 0.00 | 0.35 |
April | 0.230693E+10 | 35115736.40 | 0.00 | 4382219.26 | 6640972.59 | 3145922.71 | 0.299952E+10 | 0.00 | 0.55 |
May | 0.103989E+10 | 72573516.58 | 0.00 | 8644952.87 | 6341265.10 | 0.00 | 0.501847E+10 | 0.00 | 0.96 |
June | 0.448617E+09 | 0.985074E+09 | 0.00 | 9859928.00 | 0.104351E+09 | 0.00 | 0.375775E+10 | 0.00 | 1.22 |
July | 0.646684E+09 | 0.188799E+10 | 0.00 | 7956955.60 | 0.255144E+09 | 0.00 | 0.191300E+10 | 0.00 | 1.34 |
August | 0.101714E+10 | 0.186720E+10 | 0.00 | 8729844.08 | 0.280419E+09 | 0.00 | 0.219164E+10 | 0.00 | 1.32 |
September | 0.131314E+10 | 77495234.89 | 0.00 | 6827335.59 | 6334001.54 | 0.00 | 0.305183E+10 | 0.00 | 0.77 |
October | 0.239802E+10 | 0.00 | 0.00 | 3505992.40 | 0.00 | 0.00 | 0.266473E+10 | 0.00 | 0.47 |
November | 0.271599E+10 | 0.00 | 0.00 | 1547919.07 | 0.00 | 0.339964E+09 | 0.135757E+10 | 0.00 | 0.36 |
December | 0.308227E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.758238E+09 | 0.00 | 0.00 | 0.24 |
Annual Sum or Average | 0.224560E+11 | 0.492545E+10 | 0.00 | 53048334.28 | 0.659230E+09 | 0.601341E+10 | 0.243345E+11 | 0.00 | 0.68 |
Minimum of Months | 0.448617E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.334589E+10 | 0.188799E+10 | 0.00 | 9859928.00 | 0.280419E+09 | 0.284067E+10 | 0.501847E+10 | 0.00 | 1.34 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.225213E+10 | 0.00 | 0.00 | 33297.67 | 0.00 | 0.282382E+10 | 31249310.79 | 0.00 | 0.47 |
February | 0.319686E+10 | 0.00 | 0.00 | 578357.86 | 0.00 | 0.183994E+10 | 0.320498E+09 | 0.00 | 0.48 |
March | 0.368236E+10 | 0.00 | 0.00 | 3140363.90 | 0.00 | 0.288840E+09 | 0.196662E+10 | 0.00 | 0.64 |
April | 0.317862E+10 | 40606098.40 | 0.00 | 5652299.12 | 7262947.03 | 21030265.40 | 0.309547E+10 | 0.00 | 0.97 |
May | 0.148178E+10 | 76733179.35 | 0.00 | 11628020.72 | 7638382.97 | 0.00 | 0.532368E+10 | 0.00 | 1.60 |
June | 0.707856E+09 | 0.909530E+09 | 0.00 | 9389878.90 | 0.105470E+09 | 0.00 | 0.371553E+10 | 0.00 | 1.88 |
July | 0.810645E+09 | 0.164485E+10 | 0.00 | 8457210.24 | 0.303856E+09 | 0.00 | 0.202540E+10 | 0.00 | 2.14 |
August | 0.144015E+10 | 0.139301E+10 | 0.00 | 7788665.60 | 0.354986E+09 | 0.00 | 0.217680E+10 | 0.00 | 1.97 |
September | 0.171617E+10 | 80638704.01 | 0.00 | 9593419.63 | 6026382.17 | 0.00 | 0.347424E+10 | 0.00 | 1.38 |
October | 0.301633E+10 | 0.00 | 0.00 | 3514325.27 | 0.00 | 530245.55 | 0.263479E+10 | 0.00 | 0.78 |
November | 0.368345E+10 | 0.00 | 0.00 | 532643.82 | 0.00 | 0.462304E+09 | 0.703577E+09 | 0.00 | 0.59 |
December | 0.285030E+10 | 0.00 | 0.00 | 108612.64 | 0.00 | 0.161206E+10 | 72579784.61 | 0.00 | 0.44 |
Annual Sum or Average | 0.280167E+11 | 0.414537E+10 | 0.00 | 60417095.39 | 0.785240E+09 | 0.704853E+10 | 0.255404E+11 | 0.00 | 1.12 |
Minimum of Months | 0.707856E+09 | 0.00 | 0.00 | 33297.67 | 0.00 | 0.00 | 31249310.79 | 0.00 | 0.44 |
Maximum of Months | 0.368345E+10 | 0.164485E+10 | 0.00 | 11628020.72 | 0.354986E+09 | 0.282382E+10 | 0.532368E+10 | 0.00 | 2.14 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.203645E+10 | 0.00 | 0.00 | 4592659.59 | 0.00 | 0.239958E+10 | 0.325450E+10 | 0.00 | 0.44 |
February | 0.265946E+10 | 0.00 | 0.00 | 6788968.49 | 0.00 | 0.139654E+10 | 0.445490E+10 | 0.00 | 0.49 |
March | 0.311316E+10 | 0.00 | 0.00 | 10048859.71 | 0.00 | 0.363620E+09 | 0.609036E+10 | 0.00 | 0.70 |
April | 0.297523E+10 | 84807567.86 | 0.00 | 10475842.14 | 3890116.50 | 47531392.28 | 0.623321E+10 | 0.00 | 0.97 |
May | 0.175483E+10 | 0.113788E+09 | 0.00 | 11610144.87 | 3251181.18 | 0.00 | 0.613467E+10 | 0.00 | 1.28 |
June | 0.860861E+09 | 0.107012E+10 | 0.00 | 9515049.53 | 0.138545E+09 | 0.00 | 0.372696E+10 | 0.00 | 1.38 |
July | 0.906476E+09 | 0.212931E+10 | 0.00 | 8503689.40 | 0.341573E+09 | 0.00 | 0.193674E+10 | 0.00 | 1.58 |
August | 0.144761E+10 | 0.218199E+10 | 0.00 | 12256739.32 | 0.359489E+09 | 0.00 | 0.276866E+10 | 0.00 | 1.73 |
September | 0.151719E+10 | 0.144183E+09 | 0.00 | 16969751.86 | 5872245.07 | 0.00 | 0.557094E+10 | 0.00 | 1.35 |
October | 0.234646E+10 | 0.00 | 0.00 | 16424803.59 | 0.00 | 559412.36 | 0.859970E+10 | 0.00 | 1.07 |
November | 0.298149E+10 | 0.00 | 0.00 | 7603006.95 | 0.00 | 0.349756E+09 | 0.410063E+10 | 0.00 | 0.60 |
December | 0.247135E+10 | 0.00 | 0.00 | 5851288.68 | 0.00 | 0.139227E+10 | 0.345690E+10 | 0.00 | 0.43 |
Annual Sum or Average | 0.250706E+11 | 0.572420E+10 | 0.00 | 0.120641E+09 | 0.852620E+09 | 0.594986E+10 | 0.563282E+11 | 0.00 | 1.01 |
Minimum of Months | 0.860861E+09 | 0.00 | 0.00 | 4592659.59 | 0.00 | 0.00 | 0.193674E+10 | 0.00 | 0.43 |
Maximum of Months | 0.311316E+10 | 0.218199E+10 | 0.00 | 16969751.86 | 0.359489E+09 | 0.239958E+10 | 0.859970E+10 | 0.00 | 1.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.340336E+10 | 0.00 | 0.00 | 327861.16 | 0.00 | 0.238561E+10 | 0.350115E+09 | 0.00 | 0.57 |
February | 0.389301E+10 | 0.00 | 0.00 | 1805986.33 | 0.00 | 0.138919E+10 | 0.141854E+10 | 0.00 | 0.61 |
March | 0.292708E+10 | 0.00 | 0.00 | 6843647.66 | 0.00 | 1536771.25 | 0.497800E+10 | 0.00 | 0.89 |
April | 0.121057E+10 | 55283293.30 | 0.00 | 16164010.25 | 3778351.92 | 0.00 | 0.875667E+10 | 0.00 | 1.58 |
May | 0.109312E+10 | 79263536.38 | 0.00 | 15228674.12 | 9258168.55 | 0.00 | 0.642010E+10 | 0.00 | 1.84 |
June | 0.428327E+09 | 0.947873E+09 | 0.00 | 12291592.93 | 0.119082E+09 | 0.00 | 0.459238E+10 | 0.00 | 2.25 |
July | 0.687729E+09 | 0.222671E+10 | 0.00 | 14552352.16 | 0.244794E+09 | 0.00 | 0.255942E+10 | 0.00 | 2.60 |
August | 0.100561E+10 | 0.248775E+10 | 0.00 | 18363673.01 | 0.191102E+09 | 0.00 | 0.380943E+10 | 0.00 | 2.91 |
September | 0.148720E+10 | 90662981.14 | 0.00 | 10977103.20 | 6403362.18 | 0.00 | 0.404146E+10 | 0.00 | 1.55 |
October | 0.207325E+10 | 0.00 | 0.00 | 8047743.38 | 0.00 | 0.00 | 0.576851E+10 | 0.00 | 1.15 |
November | 0.293284E+10 | 0.00 | 0.00 | 4455206.96 | 0.00 | 25438122.35 | 0.351482E+10 | 0.00 | 0.81 |
December | 0.435096E+10 | 0.00 | 0.00 | 1469559.25 | 0.00 | 0.105007E+09 | 0.126813E+10 | 0.00 | 0.56 |
Annual Sum or Average | 0.254931E+11 | 0.588754E+10 | 0.00 | 0.110527E+09 | 0.574417E+09 | 0.390678E+10 | 0.474776E+11 | 0.00 | 1.45 |
Minimum of Months | 0.428327E+09 | 0.00 | 0.00 | 327861.16 | 0.00 | 0.00 | 0.350115E+09 | 0.00 | 0.56 |
Maximum of Months | 0.435096E+10 | 0.248775E+10 | 0.00 | 18363673.01 | 0.244794E+09 | 0.238561E+10 | 0.875667E+10 | 0.00 | 2.91 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.193017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.494734E+11 | 0.00 | 0.00 | 0.34 |
February | 0.750277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438463E+11 | 0.00 | 0.00 | 0.32 |
March | 0.227036E+11 | 0.00 | 0.00 | 671873.96 | 0.00 | 0.162193E+11 | 0.976774E+09 | 0.00 | 0.33 |
April | 0.267187E+11 | 0.282394E+09 | 0.00 | 10643733.54 | 52185521.92 | 0.457107E+10 | 0.710904E+10 | 0.00 | 0.41 |
May | 0.155063E+11 | 0.537543E+09 | 0.00 | 53135358.89 | 86158486.18 | 73062427.00 | 0.305677E+11 | 0.00 | 0.76 |
June | 0.516410E+10 | 0.747356E+10 | 0.00 | 68525502.16 | 0.406485E+09 | 0.00 | 0.257185E+11 | 0.00 | 0.95 |
July | 0.306750E+10 | 0.132270E+11 | 0.00 | 50624431.36 | 0.120309E+10 | 0.00 | 0.130555E+11 | 0.00 | 0.94 |
August | 0.575545E+10 | 0.130789E+11 | 0.00 | 55124628.08 | 0.670744E+09 | 0.00 | 0.133851E+11 | 0.00 | 0.89 |
September | 0.190390E+11 | 0.664984E+09 | 0.00 | 34700554.74 | 61679444.24 | 0.405345E+09 | 0.139589E+11 | 0.00 | 0.60 |
October | 0.321101E+11 | 0.00 | 0.00 | 4011392.19 | 39865.30 | 0.325779E+10 | 0.359097E+10 | 0.00 | 0.37 |
November | 0.189873E+11 | 0.00 | 0.00 | 365474.67 | 0.00 | 0.169078E+11 | 0.115287E+10 | 0.00 | 0.33 |
December | 0.165570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354877E+11 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.160141E+12 | 0.352644E+11 | 0.00 | 0.277803E+09 | 0.248039E+10 | 0.170242E+12 | 0.109515E+12 | 0.00 | 0.55 |
Minimum of Months | 0.165570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.321101E+11 | 0.132270E+11 | 0.00 | 68525502.16 | 0.120309E+10 | 0.494734E+11 | 0.305677E+11 | 0.00 | 0.95 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.628411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456917E+11 | 0.00 | 0.00 | 0.57 |
February | 0.153213E+11 | 0.00 | 0.00 | 1211503.22 | 0.00 | 0.373641E+11 | 0.711835E+09 | 0.00 | 0.56 |
March | 0.278458E+11 | 0.00 | 0.00 | 14747397.50 | 0.00 | 0.149011E+11 | 0.962010E+10 | 0.00 | 0.67 |
April | 0.291973E+11 | 0.435014E+09 | 0.00 | 38381448.78 | 44988268.24 | 0.510162E+10 | 0.205581E+11 | 0.00 | 0.90 |
May | 0.181608E+11 | 0.667178E+09 | 0.00 | 98726117.51 | 84453615.15 | 40378060.84 | 0.440096E+11 | 0.00 | 1.53 |
June | 0.972211E+10 | 0.774040E+10 | 0.00 | 82344444.80 | 0.411488E+09 | 0.00 | 0.315138E+11 | 0.00 | 1.77 |
July | 0.437601E+10 | 0.135685E+11 | 0.00 | 78867334.14 | 0.151343E+10 | 0.00 | 0.188502E+11 | 0.00 | 1.87 |
August | 0.798979E+10 | 0.124525E+11 | 0.00 | 74427762.60 | 0.883278E+09 | 0.00 | 0.195309E+11 | 0.00 | 1.65 |
September | 0.206660E+11 | 0.776222E+09 | 0.00 | 79383972.58 | 59161471.43 | 0.356768E+09 | 0.253774E+11 | 0.00 | 1.29 |
October | 0.392603E+11 | 69747.41 | 0.00 | 10107041.53 | 0.00 | 0.348744E+10 | 0.794618E+10 | 0.00 | 0.74 |
November | 0.261313E+11 | 0.00 | 0.00 | 810479.94 | 0.00 | 0.192147E+11 | 0.543883E+09 | 0.00 | 0.64 |
December | 0.756603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357944E+11 | 0.00 | 0.00 | 0.55 |
Annual Sum or Average | 0.212521E+12 | 0.356400E+11 | 0.00 | 0.479008E+09 | 0.299680E+10 | 0.161952E+12 | 0.178662E+12 | 0.00 | 1.06 |
Minimum of Months | 0.437601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 0.392603E+11 | 0.135685E+11 | 0.00 | 98726117.51 | 0.151343E+10 | 0.456917E+11 | 0.440096E+11 | 0.00 | 1.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.139754E+11 | 0.00 | 0.00 | 34716077.12 | 0.00 | 0.338608E+11 | 0.218085E+11 | 0.00 | 0.48 |
February | 0.186673E+11 | 0.00 | 0.00 | 58611951.56 | 0.00 | 0.237549E+11 | 0.357713E+11 | 0.00 | 0.53 |
March | 0.242172E+11 | 0.00 | 0.00 | 80504216.12 | 0.00 | 0.115799E+11 | 0.461104E+11 | 0.00 | 0.69 |
April | 0.271291E+11 | 0.876407E+09 | 0.00 | 85342679.19 | 27845269.61 | 0.422555E+10 | 0.462449E+11 | 0.00 | 0.87 |
May | 0.192758E+11 | 0.995890E+09 | 0.00 | 98678524.47 | 41378104.96 | 42290086.63 | 0.500854E+11 | 0.00 | 1.17 |
June | 0.103685E+11 | 0.864614E+10 | 0.00 | 75100748.10 | 0.570285E+09 | 0.00 | 0.282155E+11 | 0.00 | 1.18 |
July | 0.603415E+10 | 0.162495E+11 | 0.00 | 63192779.91 | 0.152933E+10 | 0.00 | 0.144381E+11 | 0.00 | 1.23 |
August | 0.734266E+10 | 0.170919E+11 | 0.00 | 0.108421E+09 | 0.811770E+09 | 0.00 | 0.225796E+11 | 0.00 | 1.37 |
September | 0.178604E+11 | 0.150430E+10 | 0.00 | 0.156531E+09 | 45081312.52 | 0.419537E+09 | 0.457383E+11 | 0.00 | 1.29 |
October | 0.236176E+11 | 148341.61 | 0.00 | 0.157568E+09 | 0.00 | 0.214853E+10 | 0.724855E+11 | 0.00 | 1.01 |
November | 0.249228E+11 | 0.00 | 0.00 | 59305165.52 | 0.00 | 0.117433E+11 | 0.260076E+11 | 0.00 | 0.59 |
December | 0.107404E+11 | 0.00 | 0.00 | 42518078.05 | 0.00 | 0.277777E+11 | 0.221919E+11 | 0.00 | 0.48 |
Annual Sum or Average | 0.204151E+12 | 0.453643E+11 | 0.00 | 0.102049E+10 | 0.302569E+10 | 0.115552E+12 | 0.431677E+12 | 0.00 | 0.91 |
Minimum of Months | 0.603415E+10 | 0.00 | 0.00 | 34716077.12 | 0.00 | 0.00 | 0.144381E+11 | 0.00 | 0.48 |
Maximum of Months | 0.271291E+11 | 0.170919E+11 | 0.00 | 0.157568E+09 | 0.152933E+10 | 0.338608E+11 | 0.724855E+11 | 0.00 | 1.37 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.876532E+10 | 0.00 | 0.00 | 178059.84 | 0.00 | 0.452078E+11 | 0.202904E+09 | 0.00 | 0.59 |
February | 0.201064E+11 | 0.00 | 0.00 | 3515528.92 | 0.00 | 0.337437E+11 | 0.252136E+10 | 0.00 | 0.60 |
March | 0.341306E+11 | 0.00 | 0.00 | 13384027.59 | 0.00 | 0.127046E+11 | 0.941088E+10 | 0.00 | 0.72 |
April | 0.314657E+11 | 0.357485E+09 | 0.00 | 53737412.56 | 59267128.51 | 0.304632E+10 | 0.282601E+11 | 0.00 | 1.04 |
May | 0.227490E+11 | 0.617484E+09 | 0.00 | 99751188.69 | 0.115484E+09 | 47791812.33 | 0.359367E+11 | 0.00 | 1.50 |
June | 0.111002E+11 | 0.678721E+10 | 0.00 | 69425529.33 | 0.446445E+09 | 0.00 | 0.251665E+11 | 0.00 | 1.69 |
July | 0.520977E+10 | 0.148163E+11 | 0.00 | 84801410.34 | 0.964109E+09 | 0.00 | 0.138396E+11 | 0.00 | 1.72 |
August | 0.725200E+10 | 0.131866E+11 | 0.00 | 89370517.78 | 0.721251E+09 | 0.00 | 0.181129E+11 | 0.00 | 1.71 |
September | 0.260302E+11 | 0.839057E+09 | 0.00 | 63029025.77 | 67928691.01 | 0.518879E+09 | 0.173542E+11 | 0.00 | 1.27 |
October | 0.389863E+11 | 0.00 | 0.00 | 22532068.83 | 53464.37 | 0.280927E+10 | 0.153440E+11 | 0.00 | 0.87 |
November | 0.317308E+11 | 0.00 | 0.00 | 2131076.14 | 0.00 | 0.152262E+11 | 0.163236E+10 | 0.00 | 0.68 |
December | 0.103408E+11 | 0.00 | 0.00 | 253739.04 | 0.00 | 0.345584E+11 | 0.451610E+09 | 0.00 | 0.58 |
Annual Sum or Average | 0.247867E+12 | 0.366041E+11 | 0.00 | 0.502110E+09 | 0.237454E+10 | 0.147863E+12 | 0.168233E+12 | 0.00 | 1.08 |
Minimum of Months | 0.520977E+10 | 0.00 | 0.00 | 178059.84 | 0.00 | 0.00 | 0.202904E+09 | 0.00 | 0.58 |
Maximum of Months | 0.389863E+11 | 0.148163E+11 | 0.00 | 99751188.69 | 0.964109E+09 | 0.452078E+11 | 0.359367E+11 | 0.00 | 1.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.112500E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.471332E+10 | 0.00 | 0.00 | 0.37 |
February | 0.320850E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.468665E+10 | 0.00 | 0.00 | 0.35 |
March | 0.164156E+10 | 0.00 | 0.00 | 7153.54 | 0.00 | 0.194027E+10 | 32444154.86 | 0.00 | 0.35 |
April | 0.221561E+10 | 31285392.44 | 0.00 | 811615.09 | 9906007.61 | 0.833407E+09 | 0.586442E+09 | 0.00 | 0.43 |
May | 0.193045E+10 | 48502244.82 | 0.00 | 4293504.23 | 4213947.88 | 52251268.37 | 0.254296E+10 | 0.00 | 0.75 |
June | 0.735507E+09 | 0.772610E+09 | 0.00 | 6025585.90 | 66978962.83 | 3782535.38 | 0.229647E+10 | 0.00 | 0.98 |
July | 0.392554E+09 | 0.151409E+10 | 0.00 | 4586598.51 | 0.140509E+09 | 0.00 | 0.123792E+10 | 0.00 | 1.01 |
August | 0.631848E+09 | 0.126216E+10 | 0.00 | 5393071.58 | 91974383.44 | 0.00 | 0.125632E+10 | 0.00 | 0.92 |
September | 0.195478E+10 | 61736716.12 | 0.00 | 2858043.22 | 6235448.03 | 0.181173E+09 | 0.101716E+10 | 0.00 | 0.59 |
October | 0.263739E+10 | 0.00 | 0.00 | 78121.39 | 2359797.98 | 0.885876E+09 | 0.101811E+09 | 0.00 | 0.38 |
November | 0.132296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189706E+10 | 0.00 | 0.00 | 0.35 |
December | 39974616.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302854E+10 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.139360E+11 | 0.369038E+10 | 0.00 | 24053693.46 | 0.322177E+09 | 0.182223E+11 | 0.907153E+10 | 0.00 | 0.57 |
Minimum of Months | 39974616.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.263739E+10 | 0.151409E+10 | 0.00 | 6025585.90 | 0.140509E+09 | 0.471332E+10 | 0.254296E+10 | 0.00 | 1.01 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.266315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371653E+10 | 0.00 | 0.00 | 0.51 |
February | 0.809998E+09 | 0.00 | 0.00 | 48993.09 | 0.00 | 0.346718E+10 | 38801043.48 | 0.00 | 0.53 |
March | 0.210023E+10 | 0.00 | 0.00 | 790047.47 | 0.00 | 0.148975E+10 | 0.615755E+09 | 0.00 | 0.63 |
April | 0.227894E+10 | 45945119.56 | 0.00 | 2931893.83 | 9974970.39 | 0.759708E+09 | 0.170145E+10 | 0.00 | 0.87 |
May | 0.183269E+10 | 58552348.30 | 0.00 | 9009906.26 | 1157846.09 | 20420005.75 | 0.404348E+10 | 0.00 | 1.49 |
June | 0.944649E+09 | 0.810468E+09 | 0.00 | 8057580.48 | 64136945.77 | 4005362.64 | 0.311105E+10 | 0.00 | 1.82 |
July | 0.391941E+09 | 0.152446E+10 | 0.00 | 7959899.92 | 0.157640E+09 | 0.00 | 0.191796E+10 | 0.00 | 1.99 |
August | 0.679389E+09 | 0.125014E+10 | 0.00 | 7706424.84 | 0.112177E+09 | 0.00 | 0.193994E+10 | 0.00 | 1.70 |
September | 0.183944E+10 | 74695260.16 | 0.00 | 7028461.77 | 5900986.84 | 0.146230E+09 | 0.205033E+10 | 0.00 | 1.24 |
October | 0.334164E+10 | 0.00 | 0.00 | 383211.40 | 2787272.88 | 0.651562E+09 | 0.290380E+09 | 0.00 | 0.70 |
November | 0.167195E+10 | 0.00 | 0.00 | 11959.88 | 0.00 | 0.190529E+10 | 14215205.45 | 0.00 | 0.61 |
December | 0.302612E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277175E+10 | 0.00 | 0.00 | 0.51 |
Annual Sum or Average | 0.164598E+11 | 0.376426E+10 | 0.00 | 43928378.94 | 0.353775E+09 | 0.149324E+11 | 0.157234E+11 | 0.00 | 1.05 |
Minimum of Months | 0.266315E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.334164E+10 | 0.152446E+10 | 0.00 | 9009906.26 | 0.157640E+09 | 0.371653E+10 | 0.404348E+10 | 0.00 | 1.99 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.949046E+09 | 0.00 | 0.00 | 2546235.07 | 0.00 | 0.301168E+10 | 0.159418E+10 | 0.00 | 0.44 |
February | 0.126044E+10 | 0.00 | 0.00 | 4011268.14 | 0.00 | 0.251885E+10 | 0.254393E+10 | 0.00 | 0.49 |
March | 0.187242E+10 | 0.00 | 0.00 | 6042820.00 | 0.00 | 0.137640E+10 | 0.366187E+10 | 0.00 | 0.65 |
April | 0.212513E+10 | 90164041.19 | 0.00 | 6648317.29 | 8141992.31 | 0.772103E+09 | 0.430266E+10 | 0.00 | 0.85 |
May | 0.223952E+10 | 82700748.10 | 0.00 | 8584863.35 | 850577.22 | 57090911.97 | 0.461366E+10 | 0.00 | 1.17 |
June | 0.114581E+10 | 0.910479E+09 | 0.00 | 6978301.18 | 89754096.39 | 7163975.65 | 0.278580E+10 | 0.00 | 1.24 |
July | 0.630622E+09 | 0.190992E+10 | 0.00 | 6518392.73 | 0.171274E+09 | 0.00 | 0.154653E+10 | 0.00 | 1.36 |
August | 0.718204E+09 | 0.167029E+10 | 0.00 | 11423498.24 | 0.105897E+09 | 0.00 | 0.239186E+10 | 0.00 | 1.44 |
September | 0.184073E+10 | 0.135533E+09 | 0.00 | 15803798.58 | 4338780.14 | 0.144865E+09 | 0.394528E+10 | 0.00 | 1.26 |
October | 0.222912E+10 | 3216815.23 | 0.00 | 11193147.76 | 727309.37 | 0.492265E+09 | 0.566942E+10 | 0.00 | 0.92 |
November | 0.198293E+10 | 0.00 | 0.00 | 2900214.74 | 0.00 | 0.139405E+10 | 0.162136E+10 | 0.00 | 0.55 |
December | 0.642580E+09 | 0.00 | 0.00 | 2751843.18 | 0.00 | 0.233203E+10 | 0.150997E+10 | 0.00 | 0.45 |
Annual Sum or Average | 0.176366E+11 | 0.480230E+10 | 0.00 | 85402700.25 | 0.380984E+09 | 0.121065E+11 | 0.361865E+11 | 0.00 | 0.90 |
Minimum of Months | 0.630622E+09 | 0.00 | 0.00 | 2546235.07 | 0.00 | 0.00 | 0.150997E+10 | 0.00 | 0.44 |
Maximum of Months | 0.223952E+10 | 0.190992E+10 | 0.00 | 15803798.58 | 0.171274E+09 | 0.301168E+10 | 0.566942E+10 | 0.00 | 1.44 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.591155E+09 | 0.00 | 0.00 | 5838.15 | 0.00 | 0.372059E+10 | 15418497.85 | 0.00 | 0.55 |
February | 0.138935E+10 | 0.00 | 0.00 | 273157.71 | 0.00 | 0.313004E+10 | 0.196884E+09 | 0.00 | 0.58 |
March | 0.248134E+10 | 0.00 | 0.00 | 1100639.94 | 0.00 | 0.150016E+10 | 0.826589E+09 | 0.00 | 0.71 |
April | 0.254803E+10 | 43238547.36 | 0.00 | 4431172.86 | 10508299.30 | 0.556732E+09 | 0.270396E+10 | 0.00 | 1.05 |
May | 0.251065E+10 | 55219128.37 | 0.00 | 9550646.49 | 5460656.30 | 32839701.59 | 0.343673E+10 | 0.00 | 1.53 |
June | 0.115573E+10 | 0.691189E+09 | 0.00 | 6636357.26 | 76311918.91 | 2427953.00 | 0.253391E+10 | 0.00 | 1.76 |
July | 0.535368E+09 | 0.171740E+10 | 0.00 | 9206386.75 | 0.114132E+09 | 0.00 | 0.146870E+10 | 0.00 | 1.87 |
August | 0.691704E+09 | 0.129451E+10 | 0.00 | 9287709.71 | 99168583.64 | 0.00 | 0.184814E+10 | 0.00 | 1.81 |
September | 0.246344E+10 | 74008650.05 | 0.00 | 6352461.96 | 6637128.33 | 0.154841E+09 | 0.157202E+10 | 0.00 | 1.28 |
October | 0.328172E+10 | 0.00 | 0.00 | 1757352.31 | 3057950.90 | 0.522561E+09 | 0.129426E+10 | 0.00 | 0.85 |
November | 0.222176E+10 | 0.00 | 0.00 | 174987.10 | 0.00 | 0.161431E+10 | 0.134522E+09 | 0.00 | 0.67 |
December | 0.660841E+09 | 0.00 | 0.00 | 6758.06 | 0.00 | 0.264302E+10 | 15801940.07 | 0.00 | 0.55 |
Annual Sum or Average | 0.205311E+11 | 0.387557E+10 | 0.00 | 48783468.29 | 0.315277E+09 | 0.138775E+11 | 0.160469E+11 | 0.00 | 1.10 |
Minimum of Months | 0.535368E+09 | 0.00 | 0.00 | 5838.15 | 0.00 | 0.00 | 15418497.85 | 0.00 | 0.55 |
Maximum of Months | 0.328172E+10 | 0.171740E+10 | 0.00 | 9550646.49 | 0.114132E+09 | 0.372059E+10 | 0.343673E+10 | 0.00 | 1.87 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 6269590.93 | 0.00 | 0.00 | 2418897.28 | 0.00 | 0.00 | 0.103009E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7569474.64 | 0.00 | 0.00 | 0.818659E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 14864641.07 | 0.00 | 0.00 | 0.743967E+09 | 0.00 | 0.31 |
April | 0.00 | 10476516.40 | 0.00 | 17114982.61 | 0.00 | 0.00 | 0.498516E+09 | 0.00 | 0.29 |
May | 0.00 | 11849151.07 | 0.00 | 3746463.25 | 0.00 | 0.00 | 0.262859E+09 | 0.00 | 0.29 |
June | 0.00 | 99573033.87 | 0.00 | 5174812.60 | 0.00 | 0.00 | 0.112060E+09 | 0.00 | 0.30 |
July | 0.00 | 0.170273E+09 | 0.00 | 2880272.39 | 0.00 | 0.00 | 14650650.37 | 0.00 | 0.28 |
August | 0.00 | 0.167095E+09 | 0.00 | 7158226.01 | 0.00 | 0.00 | 33681229.49 | 0.00 | 0.31 |
September | 0.00 | 19373236.80 | 0.00 | 3364981.03 | 0.00 | 0.00 | 0.267327E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 8796986.73 | 0.00 | 0.00 | 0.505018E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 12775953.54 | 0.00 | 0.00 | 0.642029E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 17423555.75 | 0.00 | 0.00 | 0.869079E+09 | 0.00 | 0.28 |
Annual Sum or Average | 6269590.93 | 0.478640E+09 | 0.00 | 0.103289E+09 | 0.00 | 0.00 | 0.579794E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2418897.28 | 0.00 | 0.00 | 14650650.37 | 0.00 | 0.28 |
Maximum of Months | 6269590.93 | 0.170273E+09 | 0.00 | 17423555.75 | 0.00 | 0.00 | 0.103009E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.597922E+10 | 0.00 | 0.00 | 5055106.35 | 0.00 | 0.00 | 0.421088E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 55398071.74 | 0.00 | 0.00 | 0.820616E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.126334E+09 | 0.00 | 0.00 | 0.746227E+10 | 0.00 | 0.31 |
April | 0.00 | 0.104627E+09 | 0.00 | 0.154774E+09 | 0.00 | 0.00 | 0.499990E+10 | 0.00 | 0.29 |
May | 0.00 | 0.115293E+09 | 0.00 | 31653807.74 | 0.00 | 0.00 | 0.264808E+10 | 0.00 | 0.29 |
June | 0.00 | 0.989300E+09 | 0.00 | 47626420.22 | 0.00 | 0.00 | 0.112671E+10 | 0.00 | 0.30 |
July | 0.00 | 0.169717E+10 | 0.00 | 27234088.04 | 0.00 | 0.00 | 0.148262E+09 | 0.00 | 0.28 |
August | 0.00 | 0.167002E+10 | 0.00 | 67879530.04 | 0.00 | 0.00 | 0.339608E+09 | 0.00 | 0.31 |
September | 0.00 | 0.190426E+09 | 0.00 | 27197694.13 | 0.00 | 0.00 | 0.268467E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 73725889.31 | 0.00 | 0.00 | 0.506330E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.106280E+09 | 0.00 | 0.00 | 0.644055E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.145696E+09 | 0.00 | 0.00 | 0.871890E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.597922E+10 | 0.476684E+10 | 0.00 | 0.868854E+09 | 0.00 | 0.00 | 0.520493E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 5055106.35 | 0.00 | 0.00 | 0.148262E+09 | 0.00 | 0.28 |
Maximum of Months | 0.597922E+10 | 0.169717E+10 | 0.00 | 0.154774E+09 | 0.00 | 0.00 | 0.871890E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.828545E+09 | 0.00 | 0.00 | 242853.51 | 0.00 | 0.00 | 0.167419E+09 | 0.00 | 0.28 |
February | 1865640.41 | 0.00 | 0.00 | 4540506.71 | 0.00 | 0.00 | 0.819595E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 11532485.15 | 0.00 | 0.00 | 0.747328E+09 | 0.00 | 0.31 |
April | 0.00 | 10446304.52 | 0.00 | 14765824.90 | 0.00 | 0.00 | 0.500831E+09 | 0.00 | 0.29 |
May | 1850864.26 | 11596034.85 | 0.00 | 2861892.45 | 0.00 | 0.00 | 0.264070E+09 | 0.00 | 0.29 |
June | 0.00 | 98936045.56 | 0.00 | 4624075.74 | 0.00 | 0.00 | 0.113131E+09 | 0.00 | 0.30 |
July | 0.00 | 0.169545E+09 | 0.00 | 2702834.88 | 0.00 | 0.00 | 14959512.36 | 0.00 | 0.28 |
August | 0.00 | 0.166768E+09 | 0.00 | 6736565.42 | 0.00 | 0.00 | 34177599.70 | 0.00 | 0.31 |
September | 11481201.56 | 19052103.34 | 0.00 | 2251697.74 | 0.00 | 0.00 | 0.258035E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 6375638.12 | 0.00 | 0.00 | 0.507534E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 9560899.83 | 0.00 | 0.00 | 0.645351E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 13503488.64 | 0.00 | 0.00 | 0.872974E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.843743E+09 | 0.476343E+09 | 0.00 | 79698763.08 | 0.00 | 0.00 | 0.494541E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 242853.51 | 0.00 | 0.00 | 14959512.36 | 0.00 | 0.28 |
Maximum of Months | 0.828545E+09 | 0.169545E+09 | 0.00 | 14765824.90 | 0.00 | 0.00 | 0.872974E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.865596E+09 | 0.00 | 0.00 | 0.470056E+12 | 0.00 | 5.79 |
February | 0.00 | 0.00 | 0.00 | 0.136219E+10 | 0.00 | 0.00 | 0.723848E+12 | 0.00 | 11.61 |
March | 0.00 | 0.00 | 0.00 | 0.183780E+10 | 0.00 | 0.00 | 0.107009E+13 | 0.00 | 21.59 |
April | 0.00 | 0.809096E+10 | 0.00 | 0.232140E+10 | 0.00 | 0.00 | 0.112540E+13 | 0.00 | 34.49 |
May | 0.00 | 0.761613E+09 | 0.00 | 0.603895E+09 | 0.00 | 0.00 | 0.380895E+12 | 0.00 | 19.75 |
June | 0.00 | 0.183626E+11 | 0.00 | 0.932597E+09 | 0.00 | 0.00 | 0.389773E+12 | 0.00 | 34.82 |
July | 0.00 | 0.986650E+11 | 0.00 | 0.167031E+10 | 0.00 | 0.00 | 0.310247E+12 | 0.00 | 46.65 |
August | 0.00 | 0.937417E+11 | 0.00 | 0.204381E+10 | 0.00 | 0.00 | 0.334012E+12 | 0.00 | 49.13 |
September | 0.00 | 0.112386E+10 | 0.00 | 0.558485E+09 | 0.00 | 0.00 | 0.349788E+12 | 0.00 | 21.13 |
October | 0.00 | 0.00 | 0.00 | 0.109418E+10 | 0.00 | 0.00 | 0.771267E+12 | 0.00 | 20.75 |
November | 0.00 | 0.00 | 0.00 | 0.190391E+10 | 0.00 | 0.00 | 0.101497E+13 | 0.00 | 22.07 |
December | 0.00 | 0.00 | 0.00 | 0.310443E+10 | 0.00 | 0.00 | 0.133739E+13 | 0.00 | 20.16 |
Annual Sum or Average | 0.00 | 0.220746E+12 | 0.00 | 0.182986E+11 | 0.00 | 0.00 | 0.827774E+13 | 0.00 | 25.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.558485E+09 | 0.00 | 0.00 | 0.310247E+12 | 0.00 | 5.79 |
Maximum of Months | 0.00 | 0.986650E+11 | 0.00 | 0.310443E+10 | 0.00 | 0.00 | 0.133739E+13 | 0.00 | 49.13 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:25:51
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.378078E+12 | 0.348989E+11 | 0.00 | 0.226800E+13 | 0.224937E+12 |
February | 0.409518E+12 | 0.261031E+11 | 0.00 | 0.245286E+13 | 0.239079E+12 |
March | 0.608188E+12 | 0.235191E+11 | 0.00 | 0.309607E+13 | 0.287225E+12 |
April | 0.724990E+12 | 0.142522E+11 | 0.00 | 0.306133E+13 | 0.653913E+12 |
May | 0.825052E+12 | 0.809494E+10 | 0.00 | 0.248549E+13 | 0.574275E+12 |
June | 0.863834E+12 | 0.230319E+10 | 0.00 | 0.153651E+13 | 0.173867E+13 |
July | 0.866507E+12 | 0.920700E+09 | 0.00 | 0.772603E+12 | 0.288555E+13 |
August | 0.747775E+12 | 0.260122E+10 | 0.00 | 0.110021E+13 | 0.316943E+13 |
September | 0.529046E+12 | 0.707522E+10 | 0.00 | 0.208388E+13 | 0.837953E+12 |
October | 0.404434E+12 | 0.138335E+11 | 0.00 | 0.290393E+13 | 0.230371E+12 |
November | 0.261456E+12 | 0.226249E+11 | 0.00 | 0.288430E+13 | 0.278104E+12 |
December | 0.209587E+12 | 0.300591E+11 | 0.00 | 0.317525E+13 | 0.403061E+12 |
Annual Sum or Average | 0.682846E+13 | 0.186286E+12 | 0.00 | 0.278204E+14 | 0.115226E+14 |
Minimum of Months | 0.209587E+12 | 0.920700E+09 | 0.00 | 0.772603E+12 | 0.224937E+12 |