Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2024-07-03 12:21:46
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 26966.71 | 582.18 | 582.18 |
Net Site Energy | 26966.71 | 582.18 | 582.18 |
Total Source Energy | 85340.23 | 1842.39 | 1842.39 |
Net Source Energy | 85340.23 | 1842.39 | 1842.39 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 30.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1661.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3220.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 347.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2566.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2450.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 405.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 735.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4071.80 |
Humidification | 480.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.63 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 392.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 26936.30 | 30.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6530.60 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 30.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1661.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3220.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 347.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 55.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2505.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2450.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 405.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 735.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4071.80 |
Humidification | General | 480.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.63 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 392.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 30.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1661.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3220.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 347.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 2566.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2450.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 405.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 735.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4071.80 |
Humidification | Unassigned | 480.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.63 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 392.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 77.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 132.24 | 0.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Other | 372.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 581.52 | 0.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 77.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 132.24 | 0.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Other | 372.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 581.52 | 0.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 26936.301 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 26936.301 | 100.00 |
Total On-Site and Utility Electric Sources | 26936.301 | 100.00 |
Total Electricity End Uses | 26936.301 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 6530.60 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 6530.60 | 100.00 |
Total Water End Uses | 6530.60 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 873.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5918.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [m] | 159.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 8.6849 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 8.6849 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 8.7339 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 8.7339 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.6849 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 8.6849 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 8.6849 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 8.6849 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 8.6849 | 18.58 | 484.4232 | |
Total | 46320.38 | 8.7339 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 8.7339 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.6845 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 18-AUG-15:50 | 09-JAN-06:10 | - | - | - | - | - | - | - | - | - | - | 16-OCT-11:09 |
Heating | 0.00 | 282618.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 430824.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 280450.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 233302.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 185313.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 40305.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 80352.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 31562.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2060483.20 | 282618.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 282618.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 430824.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 280450.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3430.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 185313.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 40305.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 80352.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 31562.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 32.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5260.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 10198.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1100.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8128.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7761.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1283.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2329.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 1520.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1243.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 85307.27 | 32.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 113.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 220.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 23.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 167.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 27.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 50.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 32.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1841.68 | 0.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 113.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 220.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 23.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 167.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 27.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 50.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 32.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1841.68 | 0.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 5.52 | 0.383826 | 0.000000 | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.86 | 0.324772 | 0.327000 | 1.92 | 0.866058 | 0.500000 | 0.001173 | 0.000166 | 1.92 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 55.22 | 0.344428 | 0.339000 | 18.72 | 0.918475 | 0.500000 | 0.001106 | 0.003091 | 18.72 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.39 | 0.352799 | 0.353000 | 1.90 | 0.940798 | 0.500000 | 0.001080 | 0.000527 | 1.90 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.890152 | 0.268292 | 0.270000 | 0.240341 | 0.715445 | 0.500000 | 0.001420 | 0.000048 | 0.240341 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.08 | 0.142535 | 0.200000 | 0.215955 | 0.380092 | 0.500000 | 0.002673 | 0.000039 | 0.215955 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.24 | 0.192658 | 0.200000 | 0.247928 | 0.513753 | 0.500000 | 0.001978 | 0.000063 | 0.247928 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.35 | 0.114334 | 0.200000 | 0.269220 | 0.304890 | 0.500000 | 0.003332 | 0.000031 | 0.269220 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 8.15 | 0.293031 | 0.289000 | 2.36 | 0.781416 | 0.500000 | 0.001300 | 0.001202 | 4.17 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 11.06 | 0.139114 | 0.200000 | 2.21 | 0.370971 | 0.500000 | 0.002739 | 0.000809 | 2.81 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 11.87 | 0.201280 | 0.200000 | 2.37 | 0.536747 | 0.500000 | 0.001893 | 0.001211 | 4.20 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 11.69 | 0.131658 | 0.200000 | 2.34 | 0.351087 | 0.500000 | 0.002894 | 0.000709 | 2.46 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.913186 | 0.261525 | 0.261000 | 0.238341 | 0.697399 | 0.500000 | 0.001457 | 0.000163 | 0.564517 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.10 | 0.139661 | 0.200000 | 0.220398 | 0.372430 | 0.500000 | 0.002728 | 0.000108 | 0.374826 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.28 | 0.186871 | 0.200000 | 0.255606 | 0.498321 | 0.500000 | 0.002039 | 0.000163 | 0.567592 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.23 | 0.124623 | 0.200000 | 0.246992 | 0.332329 | 0.500000 | 0.003057 | 0.000100 | 0.348418 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | User-Specified Rated Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 18924.20 | 0.000166 | 381.50 | |
CORE_MID VAV BOX REHEAT COIL | 353334.99 | 0.003091 | 7829.14 | |
CORE_TOP VAV BOX REHEAT COIL | 60274.53 | 0.000527 | 1563.06 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 5444.46 | 0.000048 | 125.97 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4489.32 | 0.000039 | 101.65 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 7245.90 | 0.000063 | 181.87 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 3523.01 | 0.000031 | 73.36 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 137403.94 | 0.001202 | 3625.80 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 92483.25 | 0.000809 | 2440.31 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 138478.99 | 0.001211 | 3654.13 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 81061.89 | 0.000709 | 2139.27 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 18583.92 | 0.000163 | 490.23 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 12338.39 | 0.000108 | 325.46 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 18684.90 | 0.000163 | 492.89 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 11470.92 | 0.000100 | 302.60 | |
VAV_BOT WITH REHEAT HEATING COIL | 29005.44 | 0.000254 | 499.61 | |
VAV_MID WITH REHEAT HEATING COIL | 264504.36 | 0.002314 | 4561.24 | |
VAV_TOP WITH REHEAT HEATING COIL | 25218.18 | 0.000221 | 437.15 | |
CAV_BAS HEATING COIL | 256690.46 | 0.000875 | 2622.54 | 100000.00 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.484415 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.62 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.469655 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 24.92 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.21 | 2.89 | 10.41 | 2.89 | 9.35 | 9.35 | 0.300000 | 0.308871 | 9.35 |
VAV_MID WITH REHEAT | 49.00 | 28.00 | 97.99 | 28.00 | 86.99 | 86.99 | 0.300000 | 0.321862 | 86.99 |
VAV_TOP WITH REHEAT | 4.96 | 2.86 | 9.92 | 3.65 | 9.11 | 9.11 | 0.300000 | 0.399933 | 9.11 |
CAV_BAS | 0.000000 | 0.000000 | 5.52 | 1.20 | 5.52 | 5.52 | 1.00 | 0.217501 | 5.52 |
AIRLOOP DATACENTER BASEMENT | 24.92 | 24.92 | 24.92 | 24.92 | 24.92 | 24.92 | 1.00 | 0.999991 | 24.92 |
AIRLOOP DATACENTER BOT | 0.484415 | 0.484415 | 0.484415 | 0.484415 | 0.484415 | 0.484415 | 1.00 | 1.00 | 0.484415 |
AIRLOOP DATACENTER MID | 4.62 | 4.62 | 4.62 | 4.62 | 4.62 | 4.62 | 1.00 | 1.00 | 4.62 |
AIRLOOP DATACENTER TOP | 0.469655 | 0.469655 | 0.469655 | 0.469655 | 0.469655 | 0.469655 | 1.00 | 1.00 | 0.469655 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.35 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 86.99 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 9.11 | |
CAV_BAS_OA_CONTROLLER | 5.52 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 24.92 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.484415 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.62 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.469655 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 26.07 | 6.67 | 11.01 | 0.008678 | 0.008500 | 174917.00 | 0.005003 | 9.35 |
VAV_MID WITH REHEAT COOLING COIL | 26.31 | 6.67 | 11.01 | 0.008683 | 0.008500 | 1653399.33 | 0.047287 | 86.99 |
VAV_TOP WITH REHEAT COOLING COIL | 26.03 | 6.67 | 11.01 | 0.008674 | 0.008500 | 169919.03 | 0.004860 | 9.11 |
CAV_BAS COOLING COIL | 25.24 | 6.67 | 11.00 | 0.008813 | 0.008500 | 100000.63 | 0.002860 | 5.52 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.35 |
VAV_MID WITH REHEAT FAN | 86.99 |
VAV_TOP WITH REHEAT FAN | 9.11 |
CAV_BAS FAN | 5.52 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.005003 | 0.000095 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000254 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.047287 | 0.000010 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.002314 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.004860 | 0.000098 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000221 | |
CAV_BAS_COOLC_CONTROLLER | 0.002860 | 0.000166 |
CAV_BAS_HEATC_CONTROLLER | 0.000875 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 24.92 | 491371.78 | 350264.97 | 0.012034 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.484415 | 9367.68 | 6742.60 | 0.000229 |
AIRLOOP DATACENTER MID COOLING COIL | 4.62 | 89471.25 | 64376.51 | 0.002191 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.469655 | 9089.43 | 6539.51 | 0.000223 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 24.92 | 24.92 | 24.92 | 24.92 | 491371.78 | 491371.78 | 14546.91 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.484415 | 0.484415 | 0.484415 | 0.484415 | 9367.68 | 9367.68 | 672.01 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.62 | 4.62 | 4.62 | 4.62 | 89471.25 | 89471.25 | 6720.07 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.469655 | 0.469655 | 0.469655 | 0.469655 | 9089.43 | 9089.43 | 672.01 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 24.92 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.484415 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.62 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.469655 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 24.92 | 491371.78 | 0.012034 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.484415 | 9367.68 | 0.000229 |
AIRLOOP DATACENTER MID HEATING COIL | 4.62 | 89471.25 | 0.002191 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.469655 | 9089.43 | 0.000223 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 14546.91 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 672.01 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 6720.07 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 672.01 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000098 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.060009 | 9797.68 | |
HEATSYS1 PUMP | 0.012094 | 3642.32 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.060009 | 7.20 |
HEATSYS1 | 0.012094 | 1.45 |
COOLSYS1_SUPPLY | 0.060009 | 7.20 |
SINGLE WATER PLANT LOOP | 0.014677 | 1.76 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.060009 | 0.060009 | 251889.07 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1382470.62 | 1382470.62 | 0.012094 |
CENTRAL BOILER | 604559.24 | 592254.13 | 0.014677 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.030005 | 3391.63 |
COOLSYS1 CHILLER2 PUMP | 0.030005 | 3391.63 |
PLANT CIRC PUMP | 0.014677 | 3743.32 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.060009 | 0.030336 | 1060693.52 | 1060692.94 | 0.053411 |
COOLSYS1 CHILLER2 | 0.060009 | 0.030336 | 1060693.52 | 1060692.94 | 0.053411 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | U-factor Times Area Value at High Fan Speed [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/K] | |
CENTRAL TOWER | 0.014677 | 145729.95 | 73772.89 | 72864.98 | 7879.72 | 44263.73 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.106822 | 12.82 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.106822 | 26446.86 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 41.71 | 1270528.13 | 8.34 | 158816.02 |
TOWERWATERSYS COOLTOWER 2 | 41.71 | 1270528.13 | 8.34 | 158816.02 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.055005 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.80 | 14.30 | 13.60 | 13.20 | 13.30 | 12.60 | 15.30 | 15.60 | 17.70 | 19.40 | 19.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 | 32.58 | -116.98 | -8.00 | 159.00 | 99429 | 1.1818 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.00 | 7.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 8.685 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 13.527 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 8.685 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 493.108 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 24139.153 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 24139.153 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 6806.209 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6806.209 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.223 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.174 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.421 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6505 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6842 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5363 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
47 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
48 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
49 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
50 | 9 | 0.12806887E-14 | 0.42271709E-16 | -0.13586671E-09 | -0.40936836E-17 |
51 | 8 | 0.19922932E-07 | 0.16187222E-12 | 0.35697139E-03 | -0.22653060E-09 |
52 | 7 | -0.11619186E-01 | 0.85920355E-08 | -0.22189363E-01 | 0.13211437E-03 |
53 | 6 | 0.38843793 | 0.30204786E-05 | 0.45766083 | -0.45484060E-02 |
54 | 5 | -5.0254998 | 0.11379910E-03 | -4.3303126 | 0.61137149E-01 |
55 | 4 | 32.272621 | 0.93848507E-03 | 21.006408 | -0.41242756 |
56 | 3 | -109.67225 | 0.20601564E-02 | -54.766020 | 1.4927443 |
57 | 2 | 195.59070 | 0.11662962E-02 | 77.088399 | -2.8762550 |
58 | 1 | -170.59539 | 0.12524661E-03 | -55.026900 | 2.7356126 |
59 | 0 | 57.057407 | 0.71759292E-06 | 15.597005 | |
60 | 9 | 0.14110139E-14 | 0.39742576E-16 | -0.13817129E-09 | -0.60843190E-17 |
61 | 8 | 0.20247994E-07 | 0.15595569E-12 | 0.36048606E-03 | -0.23022666E-09 |
62 | 7 | -0.11724403E-01 | 0.82461052E-08 | -0.22340970E-01 | 0.13331073E-03 |
63 | 6 | 0.39129736 | 0.28944083E-05 | 0.46010459 | -0.45821116E-02 |
64 | 5 | -5.0534104 | 0.10890513E-03 | -4.3491197 | 0.61483222E-01 |
65 | 4 | 32.396114 | 0.89705981E-03 | 21.080005 | -0.41406715 |
66 | 3 | -109.93510 | 0.19671505E-02 | -54.911560 | 1.4965416 |
67 | 2 | 195.85133 | 0.11126060E-02 | 77.221727 | -2.8803937 |
68 | 1 | -170.69171 | 0.11937799E-03 | -55.065382 | 2.7373008 |
69 | 0 | 57.057407 | 0.68337402E-06 | 15.590414 | |
70 | 9 | 0.11953810E-14 | 0.45347951E-16 | -0.12637851E-09 | -0.31580148E-17 |
71 | 8 | 0.18583176E-07 | 0.18541820E-12 | 0.34227377E-03 | -0.21129711E-09 |
72 | 7 | -0.11178467E-01 | 0.10005971E-07 | -0.21554080E-01 | 0.12710323E-03 |
73 | 6 | 0.37645972 | 0.35409928E-05 | 0.44740546 | -0.44072130E-02 |
74 | 5 | -4.9085688 | 0.13417224E-03 | -4.2513079 | 0.59687292E-01 |
75 | 4 | 31.755172 | 0.11121548E-02 | 20.697061 | -0.40555762 |
76 | 3 | -108.57065 | 0.24524110E-02 | -54.154201 | 1.4768303 |
77 | 2 | 194.49811 | 0.13939007E-02 | 76.528253 | -2.8589059 |
78 | 1 | -170.19150 | 0.15023953E-03 | -54.865849 | 2.7285341 |
79 | 0 | 57.057407 | 0.86422455E-06 | 15.625098 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.45_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 2.557 | 2.557 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.45_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 2.557 | 2.557 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.45_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 2.557 | 2.557 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.45_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 2.557 | 2.557 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.66719E-002 | 0.16139 | 0.61727 | 0.61727 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12129 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.66719E-002 | 0.16139 | 0.61727 | 0.61727 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12129 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.66719E-002 | 0.16139 | 0.61727 | 0.61727 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12129 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.66719E-002 | 0.16139 | 0.61727 | 0.61727 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 0.12129 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 1.973E-005 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1763E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1779E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5026E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5039E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1514E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1525E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7585E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7591E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.2123E-003 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3193E-003 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5333E-003 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6280E-003 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1773E-003 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2531E-003 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7734E-003 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8107E-003 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1055 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6626E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1181 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1130E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7885E-002 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9689E-002 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1622E-002 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0968E-002 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.2105E-003 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3089E-003 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5312E-003 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6160E-003 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1754E-003 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2456E-003 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7738E-003 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8117E-003 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1761E-003 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1776E-003 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5024E-003 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5036E-003 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1513E-003 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1522E-003 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7585E-003 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7590E-003 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.6016E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7612E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3480E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5141E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2892E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3711E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0071E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0329E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8319E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.8835E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4349E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.6451E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7513E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5463E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2931E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.2292E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5566E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6262E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2902E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3405E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2626E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.2813E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0072E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0333E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7794E-003 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7808E-003 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5188E-003 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5199E-003 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3459E-003 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3467E-003 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7586E-003 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7591E-003 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8110E-003 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8933E-003 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5441E-003 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6080E-003 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3650E-003 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4065E-003 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7738E-003 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8118E-003 |
81 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7875E-002 |
82 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4606E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1424E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1081E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9212E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 7.4790E-003 |
87 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1622E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0965E-002 |
89 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8109E-003 |
90 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8908E-003 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5444E-003 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6076E-003 |
93 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3664E-003 |
94 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4113E-003 |
95 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7735E-003 |
96 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8107E-003 |
97 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7793E-003 |
98 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7807E-003 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5188E-003 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5199E-003 |
101 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3459E-003 |
102 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3467E-003 |
103 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7585E-003 |
104 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7591E-003 |
105 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7931E-003 |
106 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8613E-003 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.5817E-003 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.6313E-003 |
109 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4663E-003 |
110 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4859E-003 |
111 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0073E-003 |
112 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0334E-003 |
113 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2421E-002 |
114 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0409E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.9365E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.8376E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.1247E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.6911E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2931E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.2292E-002 |
121 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8435E-003 |
122 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.0263E-003 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6461E-003 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8413E-003 |
125 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.4937E-003 |
126 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5805E-003 |
127 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0071E-003 |
128 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0328E-003 |
129 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1037 |
130 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.5863E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1122 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 7.1622E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.5202E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.4422E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.8788E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.9168E-002 |
137 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.6023E-002 |
138 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7412E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.1569E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.4431E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.4869E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.3243E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.9762E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9389E-002 |
145 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.4873E-002 |
146 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.3168E-002 |
147 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.7545E-002 |
148 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.8338E-002 |
149 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.5085E-002 |
150 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.3806E-002 |
151 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.8788E-002 |
152 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9165E-002 |
153 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.0667E-002 |
154 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.9590E-002 |
155 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.7252E-002 |
156 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.7101E-002 |
157 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.9058E-002 |
158 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.5181E-002 |
159 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.9762E-002 |
160 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9389E-002 |
161 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1038 |
162 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.6005E-002 |
163 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1123 |
164 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 7.1786E-002 |
165 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.5341E-002 |
166 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.4533E-002 |
167 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.8871E-002 |
168 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.9210E-002 |
169 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.6055E-002 |
170 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7453E-002 |
171 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.1604E-002 |
172 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.4468E-002 |
173 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.4940E-002 |
174 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.3291E-002 |
175 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.9845E-002 |
176 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9432E-002 |
177 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.4877E-002 |
178 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.3194E-002 |
179 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.7551E-002 |
180 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.8359E-002 |
181 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.5125E-002 |
182 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.3831E-002 |
183 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.8871E-002 |
184 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9207E-002 |
185 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.0708E-002 |
186 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.9636E-002 |
187 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.7298E-002 |
188 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.7145E-002 |
189 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.9137E-002 |
190 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.5234E-002 |
191 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.9845E-002 |
192 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9432E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 75219.93040 | 75219.93040 | 5.51793 | 5.51793 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.22310E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | 00:10:00 | 3.80000 | 5.05843E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 79838.25586 | 79838.25586 | 5.85656 | 5.85656 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.22310E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | 00:10:00 | 3.80000 | 5.05843E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 | |
5 | CORE_MID | Cooling | 753010.28959 | 753010.28959 | 55.22322 | 55.22322 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.22310E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 168344.75197 | 168344.75197 | 7.16990 | 10.77825 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 73517.96790 | 73517.96790 | 5.39129 | 5.39129 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71400 | 8.22310E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 41468.59563 | 41468.59563 | 1.78972 | 1.78972 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 12023.96717 | 12023.96717 | 0.89015 | 0.89015 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 31.30000 | 8.23349E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 3072.41453 | 3072.41453 | 0.13174 | 0.13533 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 14585.55019 | 14585.55019 | 1.07977 | 1.07977 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 25.27767 | 8.22398E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 2357.67195 | 2357.67195 | 0.10136 | 0.10136 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 16744.82291 | 16744.82291 | 1.23964 | 1.23964 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:50:00 | 30.73633 | 8.23260E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 4798.04358 | 4798.04358 | 0.20697 | 0.20697 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 18183.02770 | 18183.02770 | 1.34610 | 1.34610 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.23207E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 867.74000 | 867.74000 | 3.75139E-002 | 8.72129E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 110088.70070 | 110088.70070 | 8.15001 | 8.15001 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 31.30000 | 8.23349E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 96215.22898 | 96215.22898 | 4.17080 | 4.17080 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 149440.96178 | 149440.96178 | 11.06322 | 11.06322 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 25.84133 | 8.22486E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 64756.28114 | 64756.28114 | 2.80757 | 2.80757 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 160275.40630 | 160275.40630 | 11.86536 | 11.86536 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 30.85500 | 8.23278E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 96966.81186 | 96966.81186 | 4.20352 | 4.20352 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 157904.46267 | 157904.46267 | 11.68978 | 11.68978 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.23207E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 56771.20331 | 56771.20331 | 2.46003 | 2.46003 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 12335.15859 | 12335.15859 | 0.91319 | 0.91319 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 31.30000 | 8.23349E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 13007.79582 | 13007.79582 | 0.56452 | 0.56452 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 14885.58685 | 14885.58685 | 1.10199 | 1.10199 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 26.40500 | 8.22575E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 8635.93831 | 8635.93831 | 0.37483 | 0.37483 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 17263.44959 | 17263.44959 | 1.27803 | 1.27803 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 31.00333 | 8.23302E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 13078.37746 | 13078.37746 | 0.56759 | 0.56759 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 16681.77900 | 16681.77900 | 1.23496 | 1.23496 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41000 | 8.23207E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 8029.58577 | 8029.58577 | 0.34842 | 0.34842 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80000 | 5.05843E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8295.95710 | 8295.95710 | 0.48441 | 0.48441 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 28.94150 | 8.22975E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 3.80000 | 5.05843E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 79184.85948 | 79184.85948 | 4.62377 | 4.62377 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 28.94150 | 8.22975E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | 00:10:00 | 3.80000 | 5.05843E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8043.15936 | 8043.15936 | 0.46966 | 0.46966 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 28.94150 | 8.22975E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 3.80000 | 5.05843E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 371039.46737 | 426695.38747 | 21.66526 | 24.91505 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 23.20100 | 8.22076E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | 00:10:00 | 3.80000 | 5.05843E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 140867.20 | 9.35192 | 9.35192 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 17193.27 | 1.60870 | 1.60870 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1286487.34 | 86.99278 | 86.99278 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 260995.03 | 24.42017 | 24.42017 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 143214.94 | 9.11419 | 9.11419 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 27117.38 | 3.64507 | 3.64507 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 |
7 | CAV_BAS | Cooling | Sensible | 74946.64 | 5.51793 | 5.51793 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 51592.61 | 1.20016 | 1.20016 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 421337.76 | 24.91527 | 24.91527 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 14546.91 | 0.33839 | 0.33839 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8203.75 | 0.48441 | 0.48441 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 672.01 | 1.56323E-002 | 1.56323E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 78321.13 | 4.62377 | 4.62377 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 6720.07 | 0.15632 | 0.15632 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7958.32 | 0.46966 | 0.46966 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 672.01 | 1.56323E-002 | 1.56323E-002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 5.51793 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.38383 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.00000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 0.00000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.85656 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32477 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32700 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.91509 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.86606 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.17313E-003 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.65557E-004 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.91509 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
16 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18924.20012 |
17 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.65557E-004 |
18 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 381.49702 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 55.22322 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34443 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33900 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 18.72067 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.91848 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.10618E-003 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.09113E-003 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 18.72067 |
28 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
30 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 353334.99131 |
31 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.09113E-003 |
32 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7829.13633 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.39129 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35280 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35300 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.90313 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.94080 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.07993E-003 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.27308E-004 |
41 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.90313 |
42 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
43 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
44 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 60274.53130 |
45 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.27308E-004 |
46 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1563.05969 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.89015 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26829 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24034 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71545 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.42009E-003 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.76305E-005 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.24034 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
58 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5444.46220 |
59 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.76305E-005 |
60 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 125.97151 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.07977 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14253 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.21595 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38009 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.67303E-003 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.92746E-005 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.21595 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
72 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4489.32423 |
73 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.92746E-005 |
74 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 101.65352 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.23964 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19266 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24793 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51375 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.97760E-003 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.33903E-005 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.24793 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
86 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7245.89853 |
87 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.33903E-005 |
88 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 181.87464 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.34610 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11433 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26922 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30489 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.33234E-003 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.08208E-005 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.26922 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
100 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3523.01114 |
101 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.08208E-005 |
102 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 73.36458 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 8.15001 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29303 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28900 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.35535 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.78142 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.30020E-003 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.20207E-003 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.17080 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
114 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 137403.94458 |
115 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.20207E-003 |
116 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3625.79661 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.06322 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13911 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.21264 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37097 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.73876E-003 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.09084E-004 |
125 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.80757 |
126 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
128 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 92483.25339 |
129 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.09084E-004 |
130 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2440.31386 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.86536 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20128 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.37307 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53675 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.89289E-003 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.21147E-003 |
139 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.20352 |
140 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
142 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 138478.98586 |
143 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.21147E-003 |
144 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3654.13027 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.68978 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13166 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.33796 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35109 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.89387E-003 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.09165E-004 |
153 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.46003 |
154 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
156 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 81061.88753 |
157 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.09165E-004 |
158 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2139.27007 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.91319 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26152 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26100 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23834 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69740 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.45684E-003 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.62580E-004 |
167 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.56452 |
168 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
170 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18583.92449 |
171 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.62580E-004 |
172 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 490.22513 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.10199 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13966 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.22040 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37243 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.72803E-003 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.07942E-004 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.37483 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
184 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12338.39450 |
185 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.07942E-004 |
186 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 325.46365 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.27803 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18687 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25561 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49832 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.03885E-003 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.63464E-004 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.56759 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
198 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18684.90308 |
199 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.63464E-004 |
200 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 492.88583 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.23496 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12462 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24699 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33233 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.05721E-003 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.00353E-004 |
209 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.34842 |
210 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
211 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
212 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11470.92435 |
213 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.00353E-004 |
214 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 302.60336 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.48441 |
216 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.62377 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.46966 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 24.91505 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.20611 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.88854 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.41222 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.88854 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.35192 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.35192 |
225 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
226 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.30887 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 48.99579 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 27.99970 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 97.99159 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 27.99970 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 86.99278 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 86.99278 |
233 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
234 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.32186 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.95973 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.86446 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.91946 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.64507 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.11419 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.11419 |
241 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
242 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.39993 |
243 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.00000 |
244 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.00000 |
245 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.51793 |
246 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 1.20016 |
247 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.51793 |
248 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.51793 |
249 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
250 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.21750 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 24.91505 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 24.91505 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 24.91505 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 24.91505 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 24.91527 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 24.91527 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.48441 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.48441 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.48441 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.48441 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.48441 |
264 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.48441 |
265 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
266 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.62377 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.62377 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.62377 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.62377 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.62377 |
272 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.62377 |
273 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
274 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.46966 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.46966 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.46966 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.46966 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.46966 |
280 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.46966 |
281 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
282 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
283 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.35192 |
284 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 86.99278 |
285 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.11419 |
286 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.51793 |
287 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 24.91527 |
288 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.48441 |
289 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.62377 |
290 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.46966 |
291 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.35192 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.07225 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.00900 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.67757E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 174916.99779 |
298 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.00260E-003 |
299 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.35192 |
300 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 29005.43865 |
301 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.53752E-004 |
302 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 499.60507 |
303 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.35192 |
304 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.00260E-003 |
305 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.51885E-005 |
306 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.53752E-004 |
307 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 86.99278 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.30982 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.00902 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.68278E-003 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1653399.32918 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.72870E-002 |
315 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 86.99278 |
316 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 264504.36080 |
317 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.31400E-003 |
318 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 4561.24131 |
319 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 86.99278 |
320 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.72870E-002 |
321 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.00702E-005 |
322 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.31400E-003 |
323 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.11419 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.03211 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.00899 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.67356E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 169919.03410 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.85966E-003 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.11419 |
332 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 25218.18307 |
333 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.20620E-004 |
334 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 437.15387 |
335 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.11419 |
336 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.85966E-003 |
337 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.79884E-005 |
338 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.20620E-004 |
339 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.51793 |
340 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.24184 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.99789 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.81292E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 100000.62564 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.86001E-003 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.51793 |
349 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 256690.46193 |
350 | Coil:Heating:Water | CAV_BAS HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
351 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
352 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2622.54389 |
353 | Fan:VariableVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.51793 |
354 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.86001E-003 |
355 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.66500E-004 |
356 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.74844E-004 |
357 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 24.91527 |
358 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
359 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.91527 |
360 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 491371.77908 |
361 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 350264.96844 |
362 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.20337E-002 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 24.91527 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 24.91527 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 24.91527 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 24.91527 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 491371.77908 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 491371.77908 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 14546.90948 |
370 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
371 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 24.91527 |
372 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.91527 |
373 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 491371.77908 |
374 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.20337E-002 |
375 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 14546.90948 |
376 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 9.76141E-005 |
377 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
378 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
379 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
380 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.48441 |
381 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
382 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48441 |
383 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9367.68305 |
384 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6742.59775 |
385 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.29414E-004 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.48441 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.48441 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.48441 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.48441 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9367.68305 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9367.68305 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 672.00695 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
394 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.48441 |
395 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48441 |
396 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9367.68305 |
397 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.29414E-004 |
398 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 672.00695 |
399 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.62377 |
400 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
401 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.62377 |
402 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 89471.25126 |
403 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 64376.50616 |
404 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.19115E-003 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.62377 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.62377 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.62377 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.62377 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 89471.25126 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 89471.25126 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 6720.06953 |
412 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
413 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.62377 |
414 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.62377 |
415 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 89471.25126 |
416 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.19115E-003 |
417 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 6720.06953 |
418 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.46966 |
419 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
420 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46966 |
421 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9089.43443 |
422 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6539.50861 |
423 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.22600E-004 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.46966 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.46966 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.46966 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.46966 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9089.43443 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9089.43443 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 672.00695 |
431 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
432 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.46966 |
433 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46966 |
434 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9089.43443 |
435 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.22600E-004 |
436 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 672.00695 |
437 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 6.00093E-002 |
438 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 9797.68233 |
439 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 6.00093E-002 |
440 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 7.20111 |
441 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 6.00093E-002 |
442 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 6.00093E-002 |
443 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 251889.07403 |
444 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
445 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.20945E-002 |
446 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.45133 |
447 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.20945E-002 |
448 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 3642.31904 |
449 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
450 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1382470.61912 |
451 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1382470.62000 |
452 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.20945E-002 |
453 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 6.00093E-002 |
454 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 7.20111 |
455 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 3.00046E-002 |
456 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 3391.63295 |
457 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 3.00046E-002 |
458 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 3391.63295 |
459 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 6.00093E-002 |
460 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.03357E-002 |
461 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1060693.51692 |
462 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1060692.93500 |
463 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 5.34112E-002 |
464 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 6.00093E-002 |
465 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.03357E-002 |
466 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1060693.51692 |
467 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1060692.93500 |
468 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 5.34112E-002 |
469 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.46768E-002 |
470 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.76122 |
471 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.46768E-002 |
472 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3743.32357 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.46768E-002 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 145729.95496 |
475 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at High Fan Speed [W/K] | 73772.89164 |
476 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 72864.97748 |
477 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
478 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/K] | 44263.73498 |
479 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 604559.24326 |
480 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 592254.13000 |
481 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.46768E-002 |
482 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
483 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
484 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
485 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
486 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
487 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.10682 |
488 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 12.81869 |
489 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.10682 |
490 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 26446.86061 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 41.70701 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1270528.13305 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 8.34140 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 158816.01663 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 41.70701 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1270528.13305 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 8.34140 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 158816.01663 |
499 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.50050E-002 |
500 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.50050E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 17944.07 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 334866.76 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 57079.30 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 5158.60 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 4254.29 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 6862.67 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 3340.05 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 130198.97 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 87632.95 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 131217.41 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 76812.76 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 17608.34 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 11690.61 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 17704.00 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 10868.83 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 24435.44 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 223321.96 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 21504.44 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 94837.96 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 216940.75 | 156903.72 | 60037.03 | 0.72 | 35735.37 | 362.45 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2032422.33 | 1465172.73 | 567249.61 | 0.72 | 331652.55 | 3363.80 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 211120.62 | 152796.14 | 58324.48 | 0.72 | 34844.83 | 353.42 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 126597.38 | 92077.79 | 34519.59 | 0.73 | 21523.93 | 218.31 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 8.97 | 30.62 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 8.97 | 30.62 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_NORTH_0.25 | N/A | 2.557 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_NORTH_0.25 | N/A | 2.557 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_NORTH_0.25 | N/A | 2.557 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_NORTH_0.25 | N/A | 2.557 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_NORTH_0.25 | N/A | 2.557 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_EAST_0.25 | N/A | 2.557 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_EAST_0.25 | N/A | 2.557 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_EAST_0.25 | N/A | 2.557 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_SOUTH_0.25 | N/A | 2.557 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_SOUTH_0.25 | N/A | 2.557 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_SOUTH_0.25 | N/A | 2.557 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_SOUTH_0.25 | N/A | 2.557 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_SOUTH_0.25 | N/A | 2.557 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_WEST_0.25 | N/A | 2.557 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_WEST_0.25 | N/A | 2.557 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_WEST_0.25 | N/A | 2.557 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_NORTH_0.25 | N/A | 2.557 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_EAST_0.25 | N/A | 2.557 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_SOUTH_0.25 | N/A | 2.557 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_WEST_0.25 | N/A | 2.557 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_NORTH_0.25 | N/A | 2.557 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_EAST_0.25 | N/A | 2.557 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_SOUTH_0.25 | N/A | 2.557 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.45_SHGC_WEST_0.25 | N/A | 2.557 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.223 | 1.034 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.174 | 0.999 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.421 | 1.172 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 9.9185539720E-004 | 1.3078765609E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.2061755100 | 0.2774547583 | Pass | Pass | 8.9658223406E-002 | 0.2870452176 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 5.5704791650E-003 | 6.2863709499E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 1.5568762157E-002 | 9.5583141592E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1375434045 | 0.1822671711 | Pass | Pass | 8.5187061657E-002 | 0.2780487330 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2081431615 | 0.2687152206 | Pass | Pass | 8.5823143118E-002 | 0.2788685737 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1588663114 | 0.1882878089 | Pass | Pass | 8.5087977255E-002 | 0.2764184402 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2186598808 | 0.2946878077 | Pass | Pass | 8.6018772092E-002 | 0.2795215665 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.5658500583E-002 | 2.2461501469E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.3096040167E-002 | 0.1054909086 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 8.0967095569E-002 | 9.1317694570E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.1688403088E-002 | 4.1661239279E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.0974364896E-002 | 2.3528049223E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.3286023276E-002 | 0.1017694544 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 8.1267791716E-002 | 8.9349061933E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.6753557237E-002 | 3.9989489436E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.4041725055E-002 | 4.8594674558E-002 | Pass | Pass | 0.1781715587 | 0.7671403692 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.3014551916E-003 | 3.8316650962E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.6277601814E-002 | 3.4887656690E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.3915248751E-006 | 9.2395533661E-006 | Pass | Pass | 3.3707191819E-003 | 3.4326377928E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.2291044673E-006 | 7.5497520392E-006 | Pass | Pass | 1.0812180384E-002 | 6.6107790903E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.5892977147E-002 | 1.3388832254E-002 | Pass | Pass | 2.2484465237E-002 | 4.1126468200E-002 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 9.5779798793E-005 | 1.8882183252E-004 | Pass | Pass | 4.6450600629E-005 | 1.1068688482E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 6414.95 | 38.26 | 0.00 | 28608.21 | 12305.48 | 47366.90 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.00 | 2 | |||
Feb | 59.00 | 53 | |||
Mar | 58.58 | 43 | |||
Apr | 46.42 | 14 | |||
May | 18.00 | 12 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 3.00 | 6 | |||
Oct | 0.00 | 0 | |||
Nov | 18.00 | 12 | |||
Dec | 4.00 | 4 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.034 | 1.223 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.999 | 1.174 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.172 | 1.421 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.45_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.45_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.45_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.45_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.45_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.45_SHGC_EAST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.45_SHGC_EAST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.45_SHGC_EAST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.45_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.45_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.45_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.45_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.45_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.45_SHGC_WEST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.45_SHGC_WEST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.45_SHGC_WEST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.557 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.45_SHGC_NORTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.557 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.45_SHGC_EAST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.557 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.45_SHGC_SOUTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.557 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.45_SHGC_WEST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.557 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.45_SHGC_NORTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.557 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.45_SHGC_EAST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.557 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.45_SHGC_SOUTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.557 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.45_SHGC_WEST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.557 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.557 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 1390.74 | 2.557 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.557 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.6849 | 2779.43 | 24139.15 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 216.17 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 8.6849 | 2496.12 | 21678.66 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 194.14 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 8.6849 | 24961.20 | 216786.56 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 1941.36 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 8.6849 | 2496.12 | 21678.66 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 194.14 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 8.6849 | 313.41 | 2721.97 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.63 | 0.0000 | Y | 14.12 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.38 | 0.0000 | Y | 9.02 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 8.6849 | 313.42 | 2722.03 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.03 | 0.0000 | Y | 13.81 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.26 | 0.0000 | Y | 8.98 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 8.6849 | 3134.13 | 27219.72 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.54 | 0.0000 | Y | 140.73 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 8.6849 | 2019.75 | 17541.42 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.33 | 0.0000 | Y | 89.99 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 8.6849 | 3134.20 | 27220.31 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.01 | 0.0000 | Y | 138.00 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 8.6849 | 2019.75 | 17541.42 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.20 | 0.0000 | Y | 89.55 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 8.6849 | 313.41 | 2721.97 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.54 | 0.0000 | Y | 14.07 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.33 | 0.0000 | Y | 9.00 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 8.6849 | 313.42 | 2722.03 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.01 | 0.0000 | Y | 13.80 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.20 | 0.0000 | Y | 8.95 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 8.6849 | 783.68 | 6806.21 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 62.65 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 13.9016 | 36.20 | 503.28 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.16 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 13.9016 | 362.03 | 5032.75 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 51.55 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 13.9016 | 36.20 | 503.28 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.16 |
Interior Lighting Total | 8.7339 | 46320.38 | 404555.99 | 1014.27 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13271.55 | AstronomicalClock | - | 42.14 | 42.14 | 104.99 | |
EXTERIOR_LIGHTS_B | 989.48 | AstronomicalClock | - | 83.75 | 62.95 | 11.69 | |
EXTERIOR_LIGHTS_C | 26594.85 | AstronomicalClock | - | 83.75 | 46.20 | 230.67 | |
Exterior Lighting Total | 40855.88 | 347.35 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2091773.23 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1382470.62 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1060692.94 | 5.91 | 1054567.96 | 5.88 | 8.97 | 30.62 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 1060692.94 | 5.91 | 1054567.96 | 5.88 | 8.97 | 30.62 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 607329.59 | |||||
CENTRAL BOILER | Boiler:HotWater | 592254.13 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1270528.13 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1270528.13 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 174917.00 | 216940.75 | 156903.72 | 60037.03 | 0.72 | - | 35735.37 | 362.45 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1653399.33 | 2032422.33 | 1465172.73 | 567249.61 | 0.72 | - | 331652.55 | 3363.80 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 169919.03 | 211120.62 | 152796.14 | 58324.48 | 0.72 | - | 34844.83 | 353.42 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 100000.63 | 126597.38 | 92077.79 | 34519.59 | 0.73 | - | 21523.93 | 218.31 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 491371.78 | 350264.97 | 141106.81 | 0.71 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9367.68 | 6742.60 | 2625.09 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 89471.25 | 64376.51 | 25094.75 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9089.43 | 6539.51 | 2549.93 | 0.72 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 18924.20 | 17944.07 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 353334.99 | 334866.76 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 60274.53 | 57079.30 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 5444.46 | 5158.60 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 4489.32 | 4254.29 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 7245.90 | 6862.67 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 3523.01 | 3340.05 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 137403.94 | 130198.97 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 92483.25 | 87632.95 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 138478.99 | 131217.41 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 81061.89 | 76812.76 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 18583.92 | 17608.34 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 12338.39 | 11690.61 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 18684.90 | 17704.00 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 11470.92 | 10868.83 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 29005.44 | 24435.44 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 264504.36 | 223321.96 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 25218.18 | 21504.44 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 100000.00 | 94837.96 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 491371.78 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9367.68 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 89471.25 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9089.43 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 14546.91 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 672.01 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 6720.07 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 672.01 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.35 | 20209.01 | 2160.95 | 1.00 | 1.12 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 86.99 | 187986.75 | 2160.95 | 1.00 | 1.08 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.11 | 19695.29 | 2160.95 | 1.00 | 1.12 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 |
CAV_BAS FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.52 | 12000.89 | 2174.89 | 1.00 | 1.14 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 24.92 | 41091.44 | 1649.25 | 1.00 | 1.14 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.48 | 542.60 | 1120.11 | 1.00 | 1.62 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.62 | 5179.12 | 1120.11 | 1.00 | 1.16 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.47 | 526.06 | 1120.11 | 1.00 | 1.63 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.060009 | 9797.68 | 163269.45 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.012094 | 3642.32 | 301156.09 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.030005 | 3391.63 | 113036.94 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.030005 | 3391.63 | 113036.94 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.014677 | 3743.32 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.106822 | 26446.86 | 247577.87 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 75219.93 | 75219.93 | 27.06 | 5.518 | 5.518 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00897 | 24.71 | 0.00822 | 1.200 | 0.00 |
CORE_BOTTOM | 79838.26 | 79838.26 | 31.98 | 5.857 | 5.857 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00889 | 24.71 | 0.00822 | 1.078 | 0.00 |
CORE_MID | 753010.29 | 753010.29 | 301.67 | 55.223 | 55.223 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 24.71 | 0.00822 | 10.778 | 0.00 |
CORE_TOP | 73517.97 | 73517.97 | 29.45 | 5.391 | 5.391 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 24.71 | 0.00822 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 12023.97 | 12023.97 | 38.36 | 0.890 | 0.890 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00881 | 31.30 | 0.00823 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 14585.55 | 14585.55 | 72.21 | 1.080 | 1.080 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 24.00 | 24.00 | 0.00867 | 25.28 | 0.00822 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 16744.82 | 16744.82 | 53.43 | 1.240 | 1.240 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:50:00 | 24.00 | 24.00 | 0.00872 | 30.74 | 0.00823 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 18183.03 | 18183.03 | 90.03 | 1.346 | 1.346 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00863 | 30.41 | 0.00823 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 110088.70 | 110088.70 | 351.26 | 8.150 | 8.150 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00883 | 31.30 | 0.00823 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 149440.96 | 149440.96 | 739.90 | 11.063 | 11.063 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 24.00 | 24.00 | 0.00866 | 25.84 | 0.00822 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 160275.41 | 160275.41 | 511.38 | 11.865 | 11.865 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 24.00 | 24.00 | 0.00873 | 30.86 | 0.00823 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 157904.46 | 157904.46 | 781.80 | 11.690 | 11.690 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00865 | 30.41 | 0.00823 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 12335.16 | 12335.16 | 39.36 | 0.913 | 0.913 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 24.00 | 0.00879 | 31.30 | 0.00823 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 14885.59 | 14885.59 | 73.70 | 1.102 | 1.102 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 24.00 | 24.00 | 0.00866 | 26.41 | 0.00823 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 17263.45 | 17263.45 | 55.08 | 1.278 | 1.278 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00871 | 31.00 | 0.00823 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 16681.78 | 16681.78 | 82.59 | 1.235 | 1.235 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00864 | 30.41 | 0.00823 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8295.96 | 8295.96 | 229.15 | 0.484 | 0.484 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 27.00 | 27.00 | 0.00859 | 28.94 | 0.00823 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 79184.86 | 79184.86 | 2187.26 | 4.624 | 4.624 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 27.00 | 27.00 | 0.00859 | 28.94 | 0.00823 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8043.16 | 8043.16 | 222.17 | 0.470 | 0.470 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 27.00 | 27.00 | 0.00859 | 28.94 | 0.00823 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 371039.47 | 426695.39 | 544.48 | 21.665 | 24.915 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 23.20 | 0.00822 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | 00:10:00 | 15.60 | 24.90 | 0.00506 | 3.80 | 0.00506 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | 00:10:00 | 15.60 | 22.81 | 0.00506 | 3.80 | 0.00506 | 1.078 | 0.00 | |
CORE_MID | 168344.75 | 168344.75 | 67.44 | 7.170 | 10.778 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 10.778 | 0.00 |
CORE_TOP | 41468.60 | 41468.60 | 16.61 | 1.790 | 1.790 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 3.80 | 0.00506 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 3072.41 | 3072.41 | 9.80 | 0.132 | 0.135 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00737 | 3.80 | 0.00506 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 2357.67 | 2357.67 | 11.67 | 0.101 | 0.101 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00745 | 3.80 | 0.00506 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 4798.04 | 4798.04 | 15.31 | 0.207 | 0.207 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00758 | 3.80 | 0.00506 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 867.74 | 867.74 | 4.30 | 0.038 | 0.087 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00699 | 3.80 | 0.00506 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 96215.23 | 96215.23 | 306.99 | 4.171 | 4.171 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00772 | 3.80 | 0.00506 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 64756.28 | 64756.28 | 320.62 | 2.808 | 2.808 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00773 | 3.80 | 0.00506 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 96966.81 | 96966.81 | 309.38 | 4.204 | 4.204 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00772 | 3.80 | 0.00506 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 56771.20 | 56771.20 | 281.08 | 2.460 | 2.460 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00765 | 3.80 | 0.00506 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 13007.80 | 13007.80 | 41.50 | 0.565 | 0.565 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00783 | 3.80 | 0.00506 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 8635.94 | 8635.94 | 42.76 | 0.375 | 0.375 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00783 | 3.80 | 0.00506 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 13078.38 | 13078.38 | 41.73 | 0.568 | 0.568 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00783 | 3.80 | 0.00506 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 8029.59 | 8029.59 | 39.76 | 0.348 | 0.348 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00780 | 3.80 | 0.00506 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 3.80 | 0.00506 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | 00:10:00 | 18.00 | 25.05 | 0.00821 | 3.80 | 0.00506 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 24.12 | 0.00544 | 3.80 | 0.00506 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 3.80 | 0.00506 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 9.35 | 9.35 | 1.61 | 1.61 | 9.3519 | 2.8885 | 9.3519 | 0.3089 | 0.3000 |
VAV_MID WITH REHEAT | 86.99 | 86.99 | 24.42 | 24.42 | 86.9928 | 27.9997 | 86.9928 | 0.3219 | 0.3000 |
VAV_TOP WITH REHEAT | 9.11 | 9.11 | 3.65 | 3.65 | 9.1142 | 3.6451 | 9.1142 | 0.3999 | 0.3000 |
CAV_BAS | 5.52 | 5.52 | 1.20 | 1.20 | 5.5179 | 1.2002 | 5.5179 | 0.2175 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.92 | 24.92 | 0.34 | 0.34 | 24.9153 | 24.9150 | 24.9153 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.48 | 0.48 | 0.02 | 0.02 | 0.4844 | 0.4844 | 0.4844 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.62 | 4.62 | 0.16 | 0.16 | 4.6238 | 4.6238 | 4.6238 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.47 | 0.47 | 0.02 | 0.02 | 0.4697 | 0.4697 | 0.4697 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 18924.200 | 18924.200 | 1.915094 | 0.00016556 | 381.497 | 12/21 00:10:00 | 12/21 00:10:00 | 18924.20 | 18924.20 | 1.915094 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 0.00 | 0.00 | 18993.98 | 18993.98 | ||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 353334.991 | 353334.991 | 18.720672 | 0.00309113 | 7829.136 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 353334.99 | 353334.99 | 18.720672 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 168344.75 | 0.00 | 354551.33 | 354551.33 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 60274.531 | 60274.531 | 1.903126 | 0.00052731 | 1563.060 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 60274.53 | 60274.53 | 1.903126 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00800000 | 50.7558 | 41468.60 | 0.00 | 60459.20 | 60459.20 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 5444.462 | 5444.462 | 0.240341 | 0.00004763 | 125.972 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5444.46 | 5444.46 | 0.240341 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00737364 | 46.8304 | 3072.41 | 0.00 | 5462.46 | 5462.46 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 4489.324 | 4489.324 | 0.215955 | 0.00003927 | 101.654 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4489.32 | 4489.32 | 0.215955 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00745059 | 47.3135 | 2357.67 | 0.00 | 4504.63 | 4504.63 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 7245.899 | 7245.899 | 0.247928 | 0.00006339 | 181.875 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7245.90 | 7245.90 | 0.247928 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00758362 | 48.1480 | 4798.04 | 0.00 | 7268.44 | 7268.44 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 3523.011 | 3523.011 | 0.269220 | 0.00003082 | 73.365 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3523.01 | 3523.01 | 0.269220 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00698566 | 44.3930 | 867.74 | 0.00 | 3535.79 | 3535.79 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 137403.945 | 137403.945 | 4.170802 | 0.00120207 | 3625.797 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 137403.94 | 137403.94 | 4.170802 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00771966 | 49.0016 | 96215.23 | 0.00 | 137869.81 | 137869.81 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 92483.253 | 92483.253 | 2.807571 | 0.00080908 | 2440.314 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 92483.25 | 92483.25 | 2.807571 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00773481 | 49.0966 | 64756.28 | 0.00 | 92795.94 | 92795.94 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 138478.986 | 138478.986 | 4.203520 | 0.00121147 | 3654.130 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 138478.99 | 138478.99 | 4.203520 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00772380 | 49.0276 | 96966.81 | 0.00 | 138948.25 | 138948.25 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 81061.888 | 81061.888 | 2.460026 | 0.00070916 | 2139.270 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 81061.89 | 81061.89 | 2.460026 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00765437 | 48.5926 | 56771.20 | 0.00 | 81338.31 | 81338.31 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 18583.924 | 18583.924 | 0.564517 | 0.00016258 | 490.225 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 18583.92 | 18583.92 | 0.564517 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00782829 | 49.6820 | 13007.80 | 0.00 | 18645.75 | 18645.75 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 12338.395 | 12338.395 | 0.374826 | 0.00010794 | 325.464 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12338.39 | 12338.39 | 0.374826 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00783346 | 49.7144 | 8635.94 | 0.00 | 12379.36 | 12379.36 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 18684.903 | 18684.903 | 0.567592 | 0.00016346 | 492.886 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 18684.90 | 18684.90 | 0.567592 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00783024 | 49.6942 | 13078.38 | 0.00 | 18747.04 | 18747.04 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 11470.924 | 11470.924 | 0.348418 | 0.00010035 | 302.603 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11470.92 | 11470.92 | 0.348418 | 12.80 | 11.43 | 0.00800000 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 0.0000 | 21.00 | 0.00779863 | 49.4964 | 8029.59 | 0.00 | 11509.17 | 11509.17 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 174916.998 | -999.000 | 9.351923 | 0.00500260 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 174917.00 | 169813.11 | 9.351923 | 26.07 | 17.07 | 0.00867757 | 11.01 | 11.01 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 27.1408 | 24.00 | 0.00885370 | 46.7513 | 120727.12 | 0.00 | 177566.22 | 165615.14 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 29005.439 | 29005.439 | 2.805577 | 0.00025375 | 499.605 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 29005.44 | 29005.44 | 2.805577 | 4.09 | 4.05 | 0.00513228 | 12.80 | 11.43 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 90.4695 | 21.96 | 0.00614098 | 36.8504 | 11095.87 | 0.00 | 29580.22 | 29580.22 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1653399.329 | -999.000 | 86.992775 | 0.04728701 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 1653399.33 | 1604536.89 | 86.992775 | 26.31 | 17.15 | 0.00868278 | 11.01 | 11.01 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 29.1771 | 24.00 | 0.00889085 | 46.9447 | 1083166.85 | 0.00 | 1678495.58 | 1565356.67 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 264504.361 | 264504.361 | 26.097833 | 0.00231400 | 4561.241 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 264504.36 | 264504.36 | 26.097833 | 4.27 | 4.15 | 0.00513471 | 12.80 | 11.43 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 97.2569 | 21.00 | 0.00781140 | 49.5759 | 483054.28 | 0.00 | 270341.99 | 270341.99 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 169919.034 | -999.000 | 9.114194 | 0.00485966 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 169919.03 | 165057.09 | 9.114194 | 26.03 | 17.05 | 0.00867356 | 11.01 | 11.01 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 27.8488 | 24.00 | 0.00884341 | 46.6976 | 123111.78 | 0.00 | 172500.06 | 160968.64 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 25218.183 | 25218.183 | 2.734258 | 0.00022062 | 437.154 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 25218.18 | 25218.18 | 2.734258 | 5.03 | 4.71 | 0.00526301 | 12.80 | 11.43 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 92.8292 | 21.00 | 0.00791130 | 50.2009 | 58094.76 | 0.00 | 26032.76 | 26032.76 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 100000.626 | -999.000 | 5.517932 | 0.00286001 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 100000.63 | 94689.52 | 5.517932 | 25.24 | 16.89 | 0.00881292 | 11.00 | 11.00 | 0.00850000 | 29.25 | 0.00823024 | 17.77 | 21.7501 | 24.00 | 0.00899351 | 47.4793 | 74234.31 | 0.00 | 101547.40 | 92369.40 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 100000.000 | 100000.000 | 3.095922 | 0.00087484 | 2622.544 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 100000.00 | 100000.00 | 3.095922 | 0.83 | 0.83 | 0.00505843 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 38.7657 | 24.90 | 0.00505843 | 25.4620 | 0.00 | 0.00 | 100077.82 | 100077.82 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 491371.779 | 350264.968 | 24.915273 | 0.01203366 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | 456543.18 | 454017.61 | -999.0 | 28.48 | 17.76 | 0.00853815 | 12.80 | 11.93 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | -999.0000 | 27.00 | 0.00854235 | 37.7674 | 370608.01 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9367.683 | 6742.598 | 0.484415 | 0.00022941 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 8675.20 | 8577.97 | -999.0 | 28.03 | 17.64 | 0.00857573 | 12.80 | 11.93 | 0.00850000 | 28.94 | 0.00822975 | 17.67 | -999.0000 | 27.00 | 0.00858726 | 37.9610 | 8295.96 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 89471.251 | 64376.506 | 4.623768 | 0.00219115 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 82865.91 | 81895.55 | -999.0 | 28.03 | 17.65 | 0.00857917 | 12.80 | 11.93 | 0.00850000 | 28.94 | 0.00822975 | 17.67 | -999.0000 | 27.00 | 0.00859139 | 37.9792 | 79184.86 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9089.434 | 6539.509 | 0.469655 | 0.00022260 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | 8418.65 | 8321.67 | -999.0 | 28.03 | 17.65 | 0.00857789 | 12.80 | 11.93 | 0.00850000 | 29.16 | 0.00823009 | 17.74 | -999.0000 | 27.00 | 0.00858987 | 37.9724 | 8042.48 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 491371.779 | 491371.779 | 24.915273 | 0.01203366 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 491371.78 | 491371.78 | 24.915273 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 1.3582 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9367.683 | 9367.683 | 0.484415 | 0.00022941 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9367.68 | 9367.68 | 0.484415 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.2271 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 89471.251 | 89471.251 | 4.623768 | 0.00219115 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 89471.25 | 89471.25 | 4.623768 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.3809 | 25.05 | 0.00821304 | 40.7704 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9089.434 | 9089.434 | 0.469655 | 0.00022260 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9089.43 | 9089.43 | 0.469655 | 3.80 | 3.80 | 0.00505843 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.3285 | 24.12 | 0.00543841 | 28.6630 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 14546.909 | 14546.909 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 14546.91 | 14546.91 | 24.915273 | 0.05 | 0.05 | 0.00845326 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 1.3582 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 672.007 | 672.007 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 672.01 | 672.01 | 0.484415 | 0.12 | 0.12 | 0.00838894 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.2271 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 6720.070 | 6720.070 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 6720.07 | 6720.07 | 4.623768 | 0.13 | 0.13 | 0.00810639 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.3809 | 25.05 | 0.00821304 | 40.7704 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 672.007 | 672.007 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 672.01 | 672.01 | 0.469655 | 0.13 | 0.13 | 0.00542576 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 3.3285 | 24.12 | 0.00543841 | 28.6630 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 18924.200 | 18924.200 | 1.915094 | 0.00016556 | 381.497 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.09322230 | 54.44 | 82.22 | 27.78 | 1410293.39 | 1.3419 | 1.368868 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 18924.20 | 18924.20 | 1.0000 | 2.26321764 | 1.915094 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.16554027 | 60.00 | 32.22 | 27.78 | 0.000 | 18924.20 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 0.00 | 0.00 | 18993.98 | 18993.98 | 2.26321764 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |||
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 353334.991 | 353334.991 | 18.720672 | 0.00309113 | 7829.136 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.09322230 | 54.44 | 82.22 | 27.78 | 1410293.39 | 25.0540 | 25.558228 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 353334.99 | 353334.99 | 1.0000 | 22.12369115 | 18.720672 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 3.09081332 | 60.00 | 32.22 | 27.78 | 0.000 | 353334.99 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.58 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 168344.75 | 0.00 | 354551.33 | 354551.33 | 22.12369115 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.52 | 17.54 | 0.00800000 | 49085.7 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 60274.531 | 60274.531 | 1.903126 | 0.00052731 | 1563.060 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.09322230 | 54.44 | 82.22 | 27.78 | 1410293.39 | 4.2739 | 4.359914 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 60274.53 | 60274.53 | 1.0000 | 2.24907394 | 1.903126 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.52725410 | 60.00 | 32.22 | 27.78 | 0.000 | 60274.53 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 50.7558 | 41468.60 | 0.00 | 60459.20 | 60459.20 | 2.24907394 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 39.16 | 20.93 | 0.00800000 | 59941.6 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5444.462 | 5444.462 | 0.240341 | 0.00004763 | 125.972 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.09322230 | 54.44 | 82.22 | 27.78 | 1410293.39 | 0.3861 | 0.393821 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5444.46 | 5444.46 | 1.0000 | 0.28402982 | 0.240341 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.04762567 | 60.00 | 32.22 | 27.78 | 0.000 | 5444.46 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.82 | 0.00737364 | 21.00 | 0.00737364 | 46.8304 | 3072.41 | 0.00 | 5462.46 | 5462.46 | 0.28402982 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 31.66 | 18.59 | 0.00800000 | 52291.8 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4489.324 | 4489.324 | 0.215955 | 0.00003927 | 101.654 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.09322230 | 54.44 | 82.22 | 27.78 | 1410293.39 | 0.3183 | 0.324732 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 4489.32 | 4489.32 | 1.0000 | 0.25521060 | 0.215955 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.03927056 | 60.00 | 32.22 | 27.78 | 0.000 | 4489.32 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.87 | 0.00745059 | 21.00 | 0.00745059 | 47.3135 | 2357.67 | 0.00 | 4504.63 | 4504.63 | 0.25521060 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 30.11 | 18.07 | 0.00800000 | 50710.5 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7245.899 | 7245.899 | 0.247928 | 0.00006339 | 181.875 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.09322230 | 54.44 | 82.22 | 27.78 | 1410293.39 | 0.5138 | 0.524127 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7245.90 | 7245.90 | 1.0000 | 0.29299581 | 0.247928 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.06338381 | 60.00 | 32.22 | 27.78 | 0.000 | 7245.90 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.86 | 0.00758362 | 21.00 | 0.00758362 | 48.1480 | 4798.04 | 0.00 | 7268.44 | 7268.44 | 0.29299581 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 37.13 | 20.32 | 0.00800000 | 57867.1 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3523.011 | 3523.011 | 0.269220 | 0.00003082 | 73.365 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.09322230 | 54.44 | 82.22 | 27.78 | 1410293.39 | 0.2498 | 0.254834 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 3523.01 | 3523.01 | 1.0000 | 0.31815883 | 0.269220 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.03081769 | 60.00 | 32.22 | 27.78 | 0.000 | 3523.01 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.92 | 0.00698566 | 21.00 | 0.00698566 | 44.3930 | 867.74 | 0.00 | 3535.79 | 3535.79 | 0.31815883 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 23.70 | 15.85 | 0.00800000 | 44173.1 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 137403.945 | 137403.945 | 4.170802 | 0.00120207 | 3625.797 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.09322230 | 54.44 | 82.22 | 27.78 | 1410293.39 | 9.7429 | 9.939014 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 137403.94 | 137403.94 | 1.0000 | 4.92896477 | 4.170802 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 1.20194702 | 60.00 | 32.22 | 27.78 | 0.000 | 137403.94 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00771966 | 21.00 | 0.00771966 | 49.0016 | 96215.23 | 0.00 | 137869.81 | 137869.81 | 4.92896477 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61031.2 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 92483.253 | 92483.253 | 2.807571 | 0.00080908 | 2440.314 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.09322230 | 54.44 | 82.22 | 27.78 | 1410293.39 | 6.5577 | 6.689708 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 92483.25 | 92483.25 | 1.0000 | 3.31792734 | 2.807571 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.80900131 | 60.00 | 32.22 | 27.78 | 0.000 | 92483.25 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00773481 | 21.00 | 0.00773481 | 49.0966 | 64756.28 | 0.00 | 92795.94 | 92795.94 | 3.31792734 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61027.9 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 138478.986 | 138478.986 | 4.203520 | 0.00121147 | 3654.130 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.09322230 | 54.44 | 82.22 | 27.78 | 1410293.39 | 9.8192 | 10.016776 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 138478.99 | 138478.99 | 1.0000 | 4.96763074 | 4.203520 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 1.21135100 | 60.00 | 32.22 | 27.78 | 0.000 | 138478.99 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00772380 | 21.00 | 0.00772380 | 49.0276 | 96966.81 | 0.00 | 138948.25 | 138948.25 | 4.96763074 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61030.6 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 81061.888 | 81061.888 | 2.460026 | 0.00070916 | 2139.270 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.09322230 | 54.44 | 82.22 | 27.78 | 1410293.39 | 5.7479 | 5.863552 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 81061.89 | 81061.89 | 1.0000 | 2.90720565 | 2.460026 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.70909241 | 60.00 | 32.22 | 27.78 | 0.000 | 81061.89 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.91 | 0.00765437 | 21.00 | 0.00765437 | 48.5926 | 56771.20 | 0.00 | 81338.31 | 81338.31 | 2.90720565 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.24 | 21.25 | 0.00800000 | 61038.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18583.924 | 18583.924 | 0.564517 | 0.00016258 | 490.225 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.09322230 | 54.44 | 82.22 | 27.78 | 1410293.39 | 1.3177 | 1.344255 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 18583.92 | 18583.92 | 1.0000 | 0.66713390 | 0.564517 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.16256369 | 60.00 | 32.22 | 27.78 | 0.000 | 18583.92 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00782829 | 21.00 | 0.00782829 | 49.6820 | 13007.80 | 0.00 | 18645.75 | 18645.75 | 0.66713390 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61008.9 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12338.395 | 12338.395 | 0.374826 | 0.00010794 | 325.464 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.09322230 | 54.44 | 82.22 | 27.78 | 1410293.39 | 0.8749 | 0.892489 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 12338.39 | 12338.39 | 1.0000 | 0.44296100 | 0.374826 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.10793065 | 60.00 | 32.22 | 27.78 | 0.000 | 12338.39 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00783346 | 21.00 | 0.00783346 | 49.7144 | 8635.94 | 0.00 | 12379.36 | 12379.36 | 0.44296100 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61006.7 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18684.903 | 18684.903 | 0.567592 | 0.00016346 | 492.886 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.09322230 | 54.44 | 82.22 | 27.78 | 1410293.39 | 1.3249 | 1.351559 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 18684.90 | 18684.90 | 1.0000 | 0.67076783 | 0.567592 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.16344701 | 60.00 | 32.22 | 27.78 | 0.000 | 18684.90 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00783024 | 21.00 | 0.00783024 | 49.6942 | 13078.38 | 0.00 | 18747.04 | 18747.04 | 0.67076783 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61008.5 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11470.924 | 11470.924 | 0.348418 | 0.00010035 | 302.603 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 12.09322230 | 54.44 | 82.22 | 27.78 | 1410293.39 | 0.8134 | 0.829741 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11470.92 | 11470.92 | 1.0000 | 0.41175267 | 0.348418 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.10034241 | 60.00 | 32.22 | 27.78 | 0.000 | 11470.92 | 3.80 | 0.00505843 | 3.80 | 0.00000000 | 0.0000 | 20.95 | 0.00779863 | 21.00 | 0.00779863 | 49.4964 | 8029.59 | 0.00 | 11509.17 | 11509.17 | 0.41175267 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61011.5 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 174916.998 | -999.000 | 9.351923 | 0.00500260 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9712 | 1004.8586 | 1.1818 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.351923 | 11.05190294 | 4197.9300 | 999.8980 | 60.00316204 | 15.00 | 6.67 | 8.33 | 2098235.99 | 8.3364 | 8.336383 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 174917.00 | 169813.11 | 1.0000 | 11.05190294 | 9.351923 | 26.07 | 17.07 | 0.00867757 | 48321.1 | 11.01 | 11.01 | 0.00850000 | 32494.2 | 5.00209368 | 6.67 | 15.00 | 8.33 | 20209.007 | 154707.99 | 31.30 | 0.00823349 | 18.45 | 2.53819000 | 27.1408 | 24.00 | 0.00885370 | 24.00 | 0.00885370 | 46.7513 | 120727.12 | 0.00 | 177566.22 | 165615.14 | 11.05190294 | 26.07 | 17.26 | 0.00867757 | 48321.1 | 11.39 | 11.26 | 0.00824882 | 32254.5 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 29005.439 | 29005.439 | 2.805577 | 0.00025375 | 499.605 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.351923 | 11.05190294 | 4197.9300 | 999.8980 | 12.09322230 | 54.44 | 82.22 | 27.78 | 1410293.39 | 2.0567 | 2.098087 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 29005.44 | 29005.44 | 1.0000 | 3.31557088 | 2.805577 | 4.09 | 4.05 | 0.00513228 | 16988.4 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 0.25372635 | 60.00 | 32.22 | 27.78 | 0.000 | 29005.44 | 3.80 | 0.00505843 | 3.80 | 2.53819000 | 90.4695 | 6.89 | 0.00583329 | 21.96 | 0.00614098 | 36.8504 | 11095.87 | 0.00 | 29580.22 | 29580.22 | 3.31557088 | 2.80 | 2.80 | 0.00513228 | 15675.8 | 11.60 | 7.94 | 0.00513228 | 24597.4 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1653399.329 | -999.000 | 86.992775 | 0.04728701 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9808 | 1004.8586 | 1.1818 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 86.992775 | 102.80620585 | 4197.9300 | 999.8980 | 60.00316204 | 15.00 | 6.67 | 8.33 | 2098235.99 | 78.7995 | 78.799493 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 1653399.33 | 1604536.89 | 1.0000 | 102.80620585 | 86.992775 | 26.31 | 17.15 | 0.00868278 | 48576.9 | 11.01 | 11.01 | 0.00850000 | 32494.2 | 47.28218775 | 6.67 | 15.00 | 8.33 | 187986.755 | 1465412.57 | 31.30 | 0.00823349 | 18.45 | 25.38195000 | 29.1771 | 24.00 | 0.00889085 | 24.00 | 0.00889085 | 46.9447 | 1083166.85 | 0.00 | 1678495.58 | 1565356.67 | 102.80620585 | 26.31 | 17.35 | 0.00868278 | 48576.9 | 11.40 | 11.25 | 0.00824644 | 32250.1 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 264504.361 | 264504.361 | 26.097833 | 0.00231400 | 4561.241 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 86.992775 | 102.80620585 | 4197.9300 | 999.8980 | 12.09322230 | 54.44 | 82.22 | 27.78 | 1410293.39 | 18.7553 | 19.132729 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 264504.36 | 264504.36 | 1.0000 | 30.84186176 | 26.097833 | 4.27 | 4.15 | 0.00513471 | 17168.3 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 2.31376348 | 60.00 | 32.22 | 27.78 | 0.000 | 264504.36 | 3.80 | 0.00505843 | 3.80 | 25.38195000 | 97.2569 | 20.76 | 0.00783927 | 21.00 | 0.00781140 | 49.5759 | 483054.28 | 0.00 | 270341.99 | 270341.99 | 30.84186176 | 2.80 | 2.80 | 0.00513471 | 15681.9 | 11.44 | 7.87 | 0.00513471 | 24447.3 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 169919.034 | -999.000 | 9.114194 | 0.00485966 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9637 | 1004.8586 | 1.1818 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.114194 | 10.77096017 | 4197.9300 | 999.8980 | 60.00316204 | 15.00 | 6.67 | 8.33 | 2098235.99 | 8.0982 | 8.098185 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | Sensible | 169919.03 | 165057.09 | 1.0000 | 10.77096017 | 9.114194 | 26.03 | 17.05 | 0.00867356 | 48269.9 | 11.01 | 11.01 | 0.00850000 | 32494.2 | 4.85916713 | 6.67 | 15.00 | 8.33 | 19695.288 | 150223.75 | 31.30 | 0.00823349 | 18.45 | 2.53819000 | 27.8488 | 24.00 | 0.00884341 | 24.00 | 0.00884341 | 46.6976 | 123111.78 | 0.00 | 172500.06 | 160968.64 | 10.77096017 | 26.03 | 17.25 | 0.00867356 | 48269.9 | 11.39 | 11.26 | 0.00824907 | 32254.6 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 25218.183 | 25218.183 | 2.734258 | 0.00022062 | 437.154 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.114194 | 10.77096017 | 4197.9300 | 999.8980 | 12.09322230 | 54.44 | 82.22 | 27.78 | 1410293.39 | 1.7882 | 1.824139 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 12:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 25218.18 | 25218.18 | 1.0000 | 3.23128805 | 2.734258 | 5.03 | 4.71 | 0.00526301 | 18269.4 | 12.80 | 11.43 | 0.00800000 | 33059.8 | 0.22059716 | 60.00 | 32.22 | 27.78 | 0.000 | 25218.18 | 3.80 | 0.00505843 | 3.80 | 2.53819000 | 92.8292 | 21.00 | 0.00791130 | 21.00 | 0.00791130 | 50.2009 | 58094.76 | 0.00 | 26032.76 | 26032.76 | 3.23128805 | 2.80 | 2.80 | 0.00526301 | 16003.4 | 10.74 | 7.68 | 0.00526301 | 24059.9 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.626 | -999.000 | 5.517932 | 0.00286001 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2228 | 1004.8586 | 1.1818 | CAV_BAS FAN | Fan:VariableVolume | 5.517932 | 6.52097379 | 4197.9300 | 999.8980 | 60.00316204 | 15.00 | 6.67 | 8.33 | 2098235.99 | 4.7659 | 4.765938 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 100000.63 | 94689.52 | 1.0000 | 6.52097379 | 5.517932 | 25.24 | 16.89 | 0.00881292 | 47818.1 | 11.00 | 11.00 | 0.00850000 | 32482.9 | 2.85971348 | 6.67 | 15.00 | 8.33 | 12000.885 | 87999.74 | 29.25 | 0.00823024 | 17.77 | 1.20015641 | 21.7501 | 24.00 | 0.00899351 | 24.00 | 0.00899351 | 47.4793 | 74234.31 | 0.00 | 101547.40 | 92369.40 | 6.52097379 | 25.24 | 17.09 | 0.00881292 | 47818.1 | 11.37 | 11.25 | 0.00825486 | 32245.7 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.095922 | 0.00087484 | 2622.544 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | CAV_BAS FAN | Fan:VariableVolume | 5.517932 | 6.52097379 | 4197.9300 | 999.8980 | 12.09322230 | 54.44 | 82.22 | 27.78 | 1410293.39 | 7.0907 | 7.233427 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.095922 | 0.83 | 0.83 | 0.00505843 | 13489.1 | 40.00 | 20.96 | 0.00800000 | 60796.0 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | 3.80 | 0.00505843 | 3.80 | 1.20015641 | 38.7657 | 0.00 | 0.00505843 | 24.90 | 0.00505843 | 25.4620 | 0.00 | 0.00 | 100077.82 | 100077.82 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.02 | 14.59 | 0.00000000 | 40240.6 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 491371.779 | 350264.968 | 24.915273 | 0.01203366 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7120 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | Sensible | 456543.18 | 454017.61 | 0.9291 | -999.0 | -999.0 | 28.48 | 17.76 | 0.00853815 | 50418.4 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 456543.18 | 31.30 | 0.00823349 | 18.45 | 0.33839277 | -999.0000 | 27.00 | 0.00854235 | 27.00 | 0.00854235 | 37.7674 | 370608.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9367.683 | 6742.598 | 0.484415 | 0.00022941 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7818 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | Sensible | 8675.20 | 8577.97 | 0.9261 | -999.0 | -999.0 | 28.03 | 17.64 | 0.00857573 | 50054.9 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8675.20 | 28.94 | 0.00822975 | 17.67 | 0.01563234 | -999.0000 | 27.00 | 0.00858726 | 27.00 | 0.00858726 | 37.9610 | 8295.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 89471.251 | 64376.506 | 4.623768 | 0.00219115 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7882 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | Sensible | 82865.91 | 81895.55 | 0.9262 | -999.0 | -999.0 | 28.03 | 17.65 | 0.00857917 | 50066.6 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 82865.91 | 28.94 | 0.00822975 | 17.67 | 0.15632344 | -999.0000 | 27.00 | 0.00859139 | 27.00 | 0.00859139 | 37.9792 | 79184.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9089.434 | 6539.509 | 0.469655 | 0.00022260 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7859 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:10:00 | Sensible | 8418.65 | 8321.67 | 0.9262 | -999.0 | -999.0 | 28.03 | 17.65 | 0.00857789 | 50070.0 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8418.65 | 29.16 | 0.00823009 | 17.74 | 0.01563234 | -999.0000 | 27.00 | 0.00858987 | 27.00 | 0.00858987 | 37.9724 | 8042.48 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 491371.779 | 491371.779 | 24.915273 | 0.01203366 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 491371.78 | 491371.78 | 1.0000 | 29.44433749 | 24.915273 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 491371.78 | 3.80 | 0.00505843 | 3.80 | 0.33839277 | 1.3582 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9367.683 | 9367.683 | 0.484415 | 0.00022941 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9367.68 | 9367.68 | 1.0000 | 0.57247118 | 0.484415 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9367.68 | 3.80 | 0.00505843 | 3.80 | 0.01563234 | 3.2271 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 89471.251 | 89471.251 | 4.623768 | 0.00219115 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 89471.25 | 89471.25 | 1.0000 | 5.46427052 | 4.623768 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 89471.25 | 3.80 | 0.00505843 | 3.80 | 0.15632344 | 3.3809 | 0.00 | 0.00821304 | 25.05 | 0.00821304 | 40.7704 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9089.434 | 9089.434 | 0.469655 | 0.00022260 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1818 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9089.43 | 9089.43 | 1.0000 | 0.55502857 | 0.469655 | 3.80 | 3.80 | 0.00505843 | 16505.0 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9089.43 | 3.80 | 0.00505843 | 3.80 | 0.01563234 | 3.3285 | 0.00 | 0.00543841 | 24.12 | 0.00543841 | 28.6630 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14546.909 | 14546.909 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 24.915273 | 29.44433749 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 14546.91 | 14546.91 | 1.0000 | 29.44433749 | 24.915273 | 0.05 | 0.05 | 0.00845326 | 21193.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14546.91 | 3.80 | 0.00505843 | 3.80 | 0.33839277 | 1.3582 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 672.007 | 672.007 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.484415 | 0.57247118 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 672.01 | 672.01 | 1.0000 | 0.57247118 | 0.484415 | 0.12 | 0.12 | 0.00838894 | 21105.4 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 672.01 | 3.80 | 0.00505843 | 3.80 | 0.01563234 | 3.2271 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.5769 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6720.070 | 6720.070 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.623768 | 5.46427052 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 6720.07 | 6720.07 | 1.0000 | 5.46427052 | 4.623768 | 0.13 | 0.13 | 0.00810639 | 20404.6 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6720.07 | 3.80 | 0.00505843 | 3.80 | 0.15632344 | 3.3809 | 0.00 | 0.00821304 | 25.05 | 0.00821304 | 40.7704 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 672.007 | 672.007 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.469655 | 0.55502857 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 672.01 | 672.01 | 1.0000 | 0.55502857 | 0.469655 | 0.13 | 0.13 | 0.00542576 | 13697.9 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 672.01 | 3.80 | 0.00505843 | 3.80 | 0.01563234 | 3.3285 | 0.00 | 0.00543841 | 24.12 | 0.00543841 | 28.6630 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 9.35 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 86.99 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 9.11 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 5.52 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 24.92 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 4698.00 | 518.00 | 454.67 |
CORE_BOTTOM | 4469.00 | 85.67 | 2.00 |
CORE_MID | 3173.00 | 934.50 | 13.50 |
CORE_TOP | 2449.50 | 2295.33 | 19.17 |
PERIMETER_BOT_ZN_3 | 2856.83 | 1644.17 | 0.00 |
PERIMETER_BOT_ZN_2 | 3055.33 | 1708.50 | 93.67 |
PERIMETER_BOT_ZN_1 | 3855.83 | 1120.67 | 168.33 |
PERIMETER_BOT_ZN_4 | 4677.83 | 626.50 | 275.33 |
PERIMETER_MID_ZN_3 | 1729.67 | 3280.00 | 21.83 |
PERIMETER_MID_ZN_2 | 1877.83 | 2477.83 | 92.83 |
PERIMETER_MID_ZN_1 | 3201.67 | 1825.33 | 152.67 |
PERIMETER_MID_ZN_4 | 2776.67 | 2483.33 | 129.33 |
PERIMETER_TOP_ZN_3 | 1814.00 | 3773.33 | 307.00 |
PERIMETER_TOP_ZN_2 | 2280.00 | 3105.67 | 189.00 |
PERIMETER_TOP_ZN_1 | 2838.17 | 2423.67 | 187.00 |
PERIMETER_TOP_ZN_4 | 2539.00 | 3001.50 | 252.17 |
DATACENTER_BOT_ZN_6 | 5943.00 | 1233.50 | 1233.50 |
DATACENTER_MID_ZN_6 | 5943.00 | 95.83 | 95.83 |
DATACENTER_TOP_ZN_6 | 5921.17 | 236.50 | 233.83 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5906.17 | 5906.17 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5918.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 1131.67 | 0.00 | 635.50 |
CORE_BOTTOM | 0.00 | 4.83 | 0.00 | 0.17 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.17 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 23.50 | 0.00 | 23.50 |
PERIMETER_BOT_ZN_1 | 0.00 | 57.67 | 0.00 | 57.50 |
PERIMETER_BOT_ZN_4 | 0.00 | 96.33 | 0.00 | 54.50 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 19.00 | 0.00 | 19.00 |
PERIMETER_MID_ZN_1 | 0.00 | 78.50 | 0.00 | 78.33 |
PERIMETER_MID_ZN_4 | 0.00 | 33.67 | 0.00 | 25.50 |
PERIMETER_TOP_ZN_3 | 1.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.83 | 15.83 | 0.00 | 15.83 |
PERIMETER_TOP_ZN_1 | 0.33 | 42.67 | 0.00 | 42.50 |
PERIMETER_TOP_ZN_4 | 0.17 | 32.00 | 0.00 | 24.17 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.83 | 0.00 | 0.83 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 54.17 | 0.00 | 54.17 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 1.17 | 1398.17 | 0.00 | 873.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.22 | 149.60 | 6779.02 | 1.642 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.88 | 134.35 | 6849.35 | 1.425 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.88 | 134.35 | 6849.35 | 1.077 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.88 | 134.35 | 6849.35 | 1.011 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.02 | 16.87 | 860.00 | 1.258 | 0.013 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.52 | 10.87 | 554.22 | 1.810 | 0.014 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.02 | 16.87 | 860.02 | 1.936 | 0.013 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.52 | 10.87 | 554.22 | 2.822 | 0.014 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.02 | 16.87 | 860.00 | 0.948 | 0.031 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.95 | 10.87 | 554.22 | 1.494 | 0.034 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.02 | 16.87 | 860.02 | 1.689 | 0.031 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.52 | 10.87 | 554.22 | 1.843 | 0.032 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.02 | 16.87 | 860.00 | 0.944 | 0.039 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.52 | 10.87 | 554.22 | 1.590 | 0.040 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.02 | 16.87 | 860.02 | 1.652 | 0.039 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.52 | 10.87 | 554.22 | 1.870 | 0.040 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.428 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.428 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.428 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.54 | 42.18 | 1911.37 | 37.525 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.22 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.95 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.54 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.22 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.88 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.88 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.88 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.02 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.02 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.02 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.95 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.02 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.02 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.02 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.54 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1031.21 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 64561996.66 | 0.00 | 64561996.66 | 0.00 | 64561996.66 | 37848132.68 | 4601.33 | 251.87 | 3906.80 | 0.00 |
CORE_BOTTOM | 59462534.97 | 0.00 | 59462534.97 | 0.00 | 59462534.97 | 33990283.35 | 3486.07 | 6.38 | 5267.55 | 411.08 |
CORE_MID | 0.44E+09 | 0.00 | 0.44E+09 | 0.00 | 0.44E+09 | 0.34E+09 | 3954.14 | 15.37 | 4790.49 | 112.81 |
CORE_TOP | 40551998.04 | 0.00 | 40551998.04 | 0.00 | 40551998.04 | 33990283.35 | 4133.81 | 16.57 | 4609.61 | 70.31 |
PERIMETER_BOT_ZN_3 | 6597816.87 | 0.00 | 6597816.87 | 116163.57 | 6713980.44 | 4267819.30 | 3417.91 | 25.04 | 5317.06 | 411.08 |
PERIMETER_BOT_ZN_2 | 6112610.40 | 0.00 | 6112610.40 | 77442.33 | 6190052.73 | 2750345.05 | 3304.10 | 3.71 | 5452.19 | 411.08 |
PERIMETER_BOT_ZN_1 | 10000511.57 | 0.00 | 10000511.57 | 116163.57 | 10116675.15 | 4267912.63 | 3335.50 | 14.86 | 5409.65 | 411.08 |
PERIMETER_BOT_ZN_4 | 9479017.35 | 0.00 | 9479017.35 | 77442.33 | 9556459.68 | 2750345.05 | 3292.64 | 0.00 | 5467.36 | 411.08 |
PERIMETER_MID_ZN_3 | 48244420.87 | 0.00 | 48244420.87 | 272433.03 | 48516853.90 | 42678193.03 | 3875.58 | 20.28 | 4864.14 | 112.81 |
PERIMETER_MID_ZN_2 | 52827953.14 | 0.00 | 52827953.14 | 181621.90 | 53009575.04 | 27503450.52 | 3705.11 | 2.83 | 5052.06 | 1021.81 |
PERIMETER_MID_ZN_1 | 85281162.25 | 0.00 | 85281162.25 | 272433.03 | 85553595.29 | 42679126.28 | 3756.25 | 46.29 | 4957.46 | 112.81 |
PERIMETER_MID_ZN_4 | 60273580.12 | 0.00 | 60273580.12 | 181621.90 | 60455202.01 | 27503450.52 | 3706.34 | 1.00 | 5052.66 | 112.81 |
PERIMETER_TOP_ZN_3 | 4766235.47 | 0.00 | 4766235.47 | 338250.81 | 5104486.29 | 4267819.30 | 4064.30 | 19.93 | 4675.76 | 70.31 |
PERIMETER_TOP_ZN_2 | 5159067.14 | 0.00 | 5159067.14 | 225500.39 | 5384567.53 | 2750345.05 | 3814.64 | 5.22 | 4940.13 | 70.31 |
PERIMETER_TOP_ZN_1 | 8303037.49 | 0.00 | 8303037.49 | 338250.81 | 8641288.30 | 4267912.63 | 3862.07 | 2.27 | 4895.66 | 70.31 |
PERIMETER_TOP_ZN_4 | 6075563.11 | 0.00 | 6075563.11 | 225500.39 | 6301063.49 | 2750345.05 | 3800.13 | 3.17 | 4956.70 | 70.31 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.58E+09 | 0.00 | 0.58E+09 | 0.00 | 0.58E+09 | 10671554.30 | 9.57 | 60.33 | 8690.10 | 2817.00 |
Total Facility | 0.76E+10 | 0.00 | 0.76E+10 | 10595812.78 | 0.77E+10 | 0.50E+10 | 4857.12 | 4371.63 | 8750.43 | 3726.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 3.0176 | 0.0000 | 3.0176 | 0.0000 | 3.0176 | 1.2002 | 1784.33 | 251.87 | 3906.80 |
CORE_BOTTOM | 2.6445 | 0.0000 | 2.6445 | 0.0000 | 2.6445 | 1.0778 | 1069.55 | 3.67 | 4869.79 |
CORE_MID | 19.9863 | 0.0000 | 19.9863 | 0.0000 | 19.9863 | 10.7782 | 1249.94 | 15.21 | 4677.85 |
CORE_TOP | 1.8771 | 0.0000 | 1.8771 | 0.0000 | 1.8771 | 1.0778 | 1366.08 | 16.57 | 4560.35 |
PERIMETER_BOT_ZN_3 | 0.2931 | 0.0000 | 0.2931 | 0.0031 | 0.2962 | 0.1353 | 999.69 | 22.04 | 4921.27 |
PERIMETER_BOT_ZN_2 | 0.2720 | 0.0000 | 0.2720 | 0.0021 | 0.2741 | 0.0872 | 898.18 | 3.71 | 5041.11 |
PERIMETER_BOT_ZN_1 | 0.4516 | 0.0000 | 0.4516 | 0.0031 | 0.4548 | 0.1353 | 920.12 | 13.22 | 5009.65 |
PERIMETER_BOT_ZN_4 | 0.4237 | 0.0000 | 0.4237 | 0.0021 | 0.4258 | 0.0872 | 886.72 | 0.00 | 5056.28 |
PERIMETER_MID_ZN_3 | 2.2117 | 0.0000 | 2.2117 | 0.0073 | 2.2191 | 1.3533 | 1171.38 | 20.12 | 4751.50 |
PERIMETER_MID_ZN_2 | 2.2465 | 0.0000 | 2.2465 | 0.0051 | 2.2515 | 0.8721 | 997.92 | 1.67 | 4034.42 |
PERIMETER_MID_ZN_1 | 3.9422 | 0.0000 | 3.9422 | 0.0073 | 3.9496 | 1.3533 | 1052.06 | 46.29 | 4844.65 |
PERIMETER_MID_ZN_4 | 2.7697 | 0.0000 | 2.7697 | 0.0049 | 2.7746 | 0.8721 | 1002.15 | 1.00 | 4939.85 |
PERIMETER_TOP_ZN_3 | 0.2205 | 0.0000 | 0.2205 | 0.0091 | 0.2296 | 0.1353 | 1297.74 | 19.90 | 4625.36 |
PERIMETER_TOP_ZN_2 | 0.2390 | 0.0000 | 0.2390 | 0.0061 | 0.2451 | 0.0872 | 1056.52 | 3.43 | 4883.04 |
PERIMETER_TOP_ZN_1 | 0.3856 | 0.0000 | 0.3856 | 0.0091 | 0.3947 | 0.1353 | 1095.35 | 2.20 | 4845.45 |
PERIMETER_TOP_ZN_4 | 0.2812 | 0.0000 | 0.2812 | 0.0061 | 0.2872 | 0.0872 | 1047.24 | 2.10 | 4893.66 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 19.2596 | 0.0000 | 19.2596 | 0.0000 | 19.2596 | 0.3384 | 9.57 | 60.33 | 5873.10 |
Total Facility | 342.0950 | 0.0000 | 342.0950 | 0.2868 | 342.3818 | 158.4706 | 2040.12 | 4364.67 | 5933.43 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 0.13E+09 | 0.00 | 0.13E+09 | 48026705.38 | 3292.64 | 0.00 | 5467.36 | 411.08 |
VAV_MID WITH REHEAT | 0.95E+09 | 0.00 | 0.95E+09 | 0.48E+09 | 3701.34 | 0.60 | 5058.06 | 112.81 |
VAV_TOP WITH REHEAT | 90577805.14 | 0.00 | 90577805.14 | 48026705.38 | 3809.22 | 2.42 | 4948.36 | 70.31 |
CAV_BAS | 90167122.10 | 0.00 | 90167122.10 | 37848132.68 | 4600.33 | 0.40 | 4159.26 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.81E+09 | 0.00 | 0.81E+09 | 10671554.30 | 9.57 | 0.00 | 8750.43 | 2817.00 |
AIRLOOP DATACENTER BOT | 341184.02 | 0.00 | 341184.02 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3411840.17 | 0.00 | 3411840.17 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 341184.02 | 0.00 | 341184.02 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 5.7050 | 0.0000 | 5.7050 | 1.5229 | 886.72 | 0.00 | 5056.28 |
VAV_MID WITH REHEAT | 43.7675 | 0.0000 | 43.7675 | 15.2292 | 997.15 | 0.60 | 4945.25 |
VAV_TOP WITH REHEAT | 4.1945 | 0.0000 | 4.1945 | 1.5229 | 1051.72 | 1.92 | 4889.36 |
CAV_BAS | 4.2144 | 0.0000 | 4.2144 | 1.2002 | 1783.33 | 0.40 | 4159.26 |
AIRLOOP DATACENTER BASEMENT | 26.8980 | 0.0000 | 26.8980 | 0.3384 | 9.57 | 0.00 | 5933.43 |
AIRLOOP DATACENTER BOT | 0.0159 | 0.0000 | 0.0159 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1595 | 0.0000 | 0.1595 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0159 | 0.0000 | 0.0159 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.04 | 5292.49 | 0.00 | 0.00 | 0.00 | 174.83 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.03 | 4841.29 | 0.00 | 0.00 | 0.00 | 217.33 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.00 | 4718.77 | 0.00 | 0.00 | 0.00 | 257.58 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 251.62 | 3906.89 | 0.00 | 3.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 60.33 | 8690.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 6.8635 | 0.0000 | 0.0000 | 0.0000 | 2.3187 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 53.9158 | 0.0000 | 0.0000 | 0.0000 | 23.9288 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 5.2335 | 0.0000 | 0.0000 | 0.0000 | 2.3449 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.6803 | 6.3034 | 0.0000 | 1.2342 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4752 | 27.2137 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0218 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2184 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0218 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1492 |
Defaulted Fields | 1184 |
Fields with Defaults | 3877 |
Autosized Fields | 334 |
Autosizable Fields | 413 |
Autocalculated Fields | 227 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 26936.30 | 295565.99 | 13-MAY-05:00 | 2060483.20 | 18-AUG-15:50 |
Electricity:Building | 17896.74 | 217232.45 | 21-MAY-17:20 | 1104084.83 | 01-DEC-16:20 |
Electricity:Zone:BASEMENT | 640.57 | 14055.89 | 01-JAN-00:10 | 32859.63 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 17896.74 | 217232.45 | 21-MAY-17:20 | 1104084.83 | 01-DEC-16:20 |
InteriorLights:Electricity | 3220.35 | 9936.52 | 25-JUN-17:20 | 325713.14 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:BASEMENT | 216.17 | 598.35 | 01-JAN-00:10 | 19402.09 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3220.35 | 9936.52 | 25-JUN-17:20 | 325713.14 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity | 3220.35 | 9936.52 | 25-JUN-17:20 | 325713.14 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 216.17 | 598.35 | 01-JAN-00:10 | 19402.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3220.35 | 9936.52 | 25-JUN-17:20 | 325713.14 | 02-JAN-16:50 |
Electricity:Zone:CORE_BOTTOM | 483.75 | 4990.59 | 01-JAN-00:10 | 34631.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4837.49 | 49905.77 | 01-JAN-00:10 | 346310.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1941.37 | 5373.60 | 01-JAN-00:10 | 174244.37 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1941.37 | 5373.60 | 01-JAN-00:10 | 174244.37 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 483.75 | 4990.58 | 01-JAN-00:10 | 34631.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 50.48 | 617.00 | 16-APR-17:10 | 4348.36 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 14.12 | 57.83 | 01-JAN-09:10 | 2187.81 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 14.12 | 57.83 | 01-JAN-09:10 | 2187.81 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 32.45 | 397.62 | 18-JUN-17:10 | 2802.25 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 9.02 | 37.27 | 01-JAN-07:20 | 1409.91 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 9.02 | 37.27 | 01-JAN-07:20 | 1409.91 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 50.18 | 617.01 | 16-APR-17:10 | 4348.44 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 13.81 | 57.83 | 01-JAN-07:30 | 2187.86 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 13.81 | 57.83 | 01-JAN-07:30 | 2187.86 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 32.41 | 397.61 | 12-MAR-17:10 | 2802.24 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 8.98 | 37.27 | 01-JAN-09:00 | 1409.91 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 8.98 | 37.27 | 01-JAN-09:00 | 1409.91 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 504.38 | 6169.98 | 16-APR-17:10 | 43483.64 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 140.73 | 578.27 | 01-JAN-09:00 | 21878.12 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 140.73 | 578.27 | 01-JAN-09:00 | 21878.12 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 324.34 | 3976.17 | 21-MAY-17:10 | 28022.51 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 89.99 | 372.66 | 01-JAN-07:20 | 14099.09 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 89.99 | 372.66 | 01-JAN-07:20 | 14099.09 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 501.66 | 6170.07 | 16-APR-17:10 | 43484.45 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 138.00 | 578.28 | 01-JAN-07:30 | 21878.60 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 138.00 | 578.28 | 01-JAN-07:30 | 21878.60 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 323.90 | 3976.14 | 12-MAR-17:10 | 28022.42 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 89.55 | 372.66 | 01-JAN-09:00 | 14099.09 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 89.55 | 372.66 | 01-JAN-09:00 | 14099.09 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 50.44 | 617.00 | 16-APR-17:10 | 4348.36 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 14.07 | 57.83 | 01-JAN-09:00 | 2187.81 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 14.07 | 57.83 | 01-JAN-09:00 | 2187.81 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 32.43 | 397.62 | 21-MAY-17:10 | 2802.25 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 9.00 | 37.27 | 01-JAN-07:20 | 1409.91 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 9.00 | 37.27 | 01-JAN-07:20 | 1409.91 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 50.17 | 617.01 | 16-APR-17:10 | 4348.44 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 13.80 | 57.83 | 01-JAN-07:30 | 2187.86 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 13.80 | 57.83 | 01-JAN-07:30 | 2187.86 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 32.39 | 397.61 | 12-MAR-17:10 | 2802.24 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 8.95 | 37.27 | 01-JAN-09:00 | 1409.91 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 8.95 | 37.27 | 01-JAN-09:00 | 1409.91 | 02-JAN-16:50 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7557.51 | 95212.03 | 01-JAN-00:10 | 385103.08 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 62.65 | 303.90 | 01-JAN-00:10 | 5470.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 62.65 | 303.90 | 01-JAN-00:10 | 5470.56 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 159.04 | 1973.61 | 01-JAN-00:10 | 8244.54 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1590.36 | 19736.13 | 01-JAN-00:10 | 82445.36 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 51.55 | 250.08 | 01-JAN-00:10 | 4501.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 51.55 | 250.08 | 01-JAN-00:10 | 4501.14 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 159.04 | 1973.61 | 01-JAN-00:10 | 8244.54 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 2194.94 | 4102.57 | 09-JAN-06:00 | 415721.62 | 18-AUG-15:50 |
HeatRejection:Electricity | 735.57 | 287.61 | 03-JAN-07:10 | 80352.61 | 22-MAR-12:40 |
General:HeatRejection:Electricity | 735.57 | 287.61 | 03-JAN-07:10 | 80352.61 | 22-MAR-12:40 |
Electricity:HVAC | 3985.68 | 52458.85 | 01-JAN-06:00 | 384319.90 | 05-DEC-16:00 |
ExteriorEquipment:Electricity | 2566.60 | 20217.42 | 01-JAN-00:10 | 233429.20 | 24-OCT-07:20 |
Transformer:ExteriorEquipment:Electricity | 55.01 | 979.82 | 01-JAN-00:10 | 3454.84 | 01-DEC-16:30 |
ElectricityPurchased:Facility | 26936.30 | 295565.99 | 13-MAY-05:00 | 2060483.20 | 18-AUG-15:50 |
ElectricityPurchased:Plant | 26936.30 | 295565.99 | 13-MAY-05:00 | 2060483.20 | 18-AUG-15:50 |
Cogeneration:ElectricityPurchased | 26936.30 | 295565.99 | 13-MAY-05:00 | 2060483.20 | 18-AUG-15:50 |
General:Cogeneration:ElectricityPurchased | 26936.30 | 295565.99 | 13-MAY-05:00 | 2060483.20 | 18-AUG-15:50 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 26936.30 | 295565.99 | 13-MAY-05:00 | 2060483.20 | 18-AUG-15:50 |
ElectricityNet:Plant | 26936.30 | 295565.99 | 13-MAY-05:00 | 2060483.20 | 18-AUG-15:50 |
Cogeneration:ElectricityNet | 26936.30 | 295565.99 | 13-MAY-05:00 | 2060483.20 | 18-AUG-15:50 |
General:Cogeneration:ElectricityNet | 26936.30 | 295565.99 | 13-MAY-05:00 | 2060483.20 | 18-AUG-15:50 |
Fans:Electricity | 2450.80 | 47339.22 | 01-JAN-12:10 | 193755.51 | 18-AUG-14:50 |
General:Fans:Electricity | 2450.80 | 47339.22 | 01-JAN-12:10 | 193755.51 | 18-AUG-14:50 |
ExteriorLights:Electricity | 347.35 | 0.00 | 01-JAN-07:00 | 40855.88 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 347.35 | 0.00 | 01-JAN-07:00 | 40855.88 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 2505.76 | 19200.00 | 01-JAN-00:10 | 229608.34 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 1661.01 | 3539.14 | 03-JAN-07:10 | 430824.11 | 18-AUG-15:50 |
General:Cooling:Electricity | 1661.01 | 3539.14 | 03-JAN-07:10 | 430824.11 | 18-AUG-15:50 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 480.19 | 0.00 | 01-JAN-00:30 | 100000.00 | 08-JAN-11:20 |
General:Humidifier:Electricity | 480.19 | 0.00 | 01-JAN-00:30 | 100000.00 | 08-JAN-11:20 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 392.79 | 0.00 | 01-JAN-00:10 | 45273.71 | 02-FEB-12:40 |
Water Heater:WaterSystems:Electricity | 392.79 | 0.00 | 01-JAN-00:10 | 45273.71 | 02-FEB-12:40 |
Pumps:Electricity | 405.25 | 3743.32 | 01-JAN-00:10 | 46745.99 | 30-OCT-13:40 |
General:Pumps:Electricity | 405.25 | 3743.32 | 01-JAN-00:10 | 46745.99 | 30-OCT-13:40 |
WIRED_LTG_ELECTRICITY | 90.49 | 0.00 | 01-JAN-00:10 | 9152.54 | 02-JAN-17:00 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 30.41 | 0.00 | 01-JAN-00:10 | 282618.82 | 09-JAN-06:10 |
NaturalGas:Plant | 30.41 | 0.00 | 01-JAN-00:10 | 282618.82 | 09-JAN-06:10 |
Heating:NaturalGas | 30.41 | 0.00 | 01-JAN-00:10 | 282618.82 | 09-JAN-06:10 |
Boiler:Heating:NaturalGas | 30.41 | 0.00 | 01-JAN-00:10 | 282618.82 | 09-JAN-06:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 10416.79 | 12569.39 | 03-JAN-07:10 | 2640714.00 | 18-AUG-15:50 |
PlantLoopCoolingDemand:HVAC | 10416.79 | 12569.39 | 03-JAN-07:10 | 2640714.00 | 18-AUG-15:50 |
CoolingCoils:PlantLoopCoolingDemand | 10416.79 | 12569.39 | 03-JAN-07:10 | 2640714.00 | 18-AUG-15:50 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 6530.60 | 0.00 | 01-JAN-00:30 | 0.00 | 16-OCT-11:10 |
Water:HVAC | 178.63 | 0.00 | 01-JAN-00:30 | 0.00 | 01-FEB-07:20 |
Humidifier:Water | 178.63 | 0.00 | 01-JAN-00:30 | 0.00 | 01-FEB-07:20 |
General:Humidifier:Water | 178.63 | 0.00 | 01-JAN-00:30 | 0.00 | 01-FEB-07:20 |
MainsWater:Facility | 6530.60 | 0.00 | 01-JAN-00:30 | 0.00 | 16-OCT-11:10 |
MainsWater:HVAC | 178.63 | 0.00 | 01-JAN-00:30 | 0.00 | 01-FEB-07:20 |
Humidifier:MainsWater | 178.63 | 0.00 | 01-JAN-00:30 | 0.00 | 01-FEB-07:20 |
General:Humidifier:MainsWater | 178.63 | 0.00 | 01-JAN-00:30 | 0.00 | 01-FEB-07:20 |
Water:Plant | 6351.97 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:10 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 6351.97 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:10 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 4071.80 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:00 |
General:HeatRejection:Water | 4071.80 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:00 |
HeatRejection:MainsWater | 4071.80 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:00 |
General:HeatRejection:MainsWater | 4071.80 | 0.00 | 01-JAN-00:10 | 0.00 | 16-OCT-11:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 47268.38 | 107610.85 | 01-JAN-06:00 | 9768010.48 | 18-AUG-15:50 |
EnergyTransfer:Building | 19220.09 | 94268.27 | 08-JAN-07:40 | 1460736.11 | 15-AUG-15:20 |
EnergyTransfer:Zone:BASEMENT | 641.24 | 0.00 | 01-JAN-00:10 | 102066.77 | 26-DEC-07:10 |
Heating:EnergyTransfer | 18.02 | 0.00 | 02-JAN-17:30 | 136425.17 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 18.02 | 0.00 | 02-JAN-17:30 | 136425.17 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 19202.07 | 93733.69 | 08-JAN-07:40 | 1460736.11 | 15-AUG-15:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 641.24 | 0.00 | 01-JAN-00:10 | 102066.77 | 26-DEC-07:10 |
General:Cooling:EnergyTransfer | 19202.07 | 93733.69 | 08-JAN-07:40 | 1460736.11 | 15-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 641.24 | 0.00 | 01-JAN-00:10 | 102066.77 | 26-DEC-07:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 671.61 | 0.00 | 01-JAN-00:10 | 57899.84 | 02-OCT-08:00 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 671.61 | 0.00 | 01-JAN-00:10 | 57899.84 | 02-OCT-08:00 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 671.61 | 0.00 | 01-JAN-00:10 | 57899.84 | 02-OCT-08:00 |
EnergyTransfer:Zone:CORE_MID | 4851.71 | 0.00 | 01-JAN-00:10 | 422104.22 | 17-OCT-14:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4851.71 | 0.00 | 01-JAN-00:10 | 422104.22 | 17-OCT-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4851.71 | 0.00 | 01-JAN-00:10 | 422104.22 | 17-OCT-14:00 |
EnergyTransfer:Zone:CORE_TOP | 435.54 | 0.00 | 01-JAN-00:10 | 48364.23 | 16-OCT-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.08 | 0.00 | 01-JAN-00:10 | 22468.65 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.08 | 0.00 | 01-JAN-00:10 | 22468.65 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 435.46 | 0.00 | 01-JAN-00:10 | 48364.23 | 16-OCT-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 435.46 | 0.00 | 01-JAN-00:10 | 48364.23 | 16-OCT-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 73.12 | 0.00 | 01-JAN-00:10 | 9255.37 | 16-OCT-11:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 73.12 | 0.00 | 01-JAN-00:10 | 9255.37 | 16-OCT-11:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 73.12 | 0.00 | 01-JAN-00:10 | 9255.37 | 16-OCT-11:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 67.23 | 0.00 | 01-JAN-00:10 | 11363.81 | 16-OCT-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 67.23 | 0.00 | 01-JAN-00:10 | 11363.81 | 16-OCT-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 67.23 | 0.00 | 01-JAN-00:10 | 11363.81 | 16-OCT-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 114.61 | 0.00 | 01-JAN-00:10 | 18322.79 | 30-OCT-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 114.61 | 0.00 | 01-JAN-00:10 | 18322.79 | 30-OCT-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 114.61 | 0.00 | 01-JAN-00:10 | 18322.79 | 30-OCT-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 107.17 | 0.00 | 01-JAN-00:10 | 15034.43 | 26-APR-15:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 107.17 | 0.00 | 01-JAN-00:10 | 15034.43 | 26-APR-15:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 107.17 | 0.00 | 01-JAN-00:10 | 15034.43 | 26-APR-15:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 506.20 | 0.00 | 01-JAN-00:10 | 74900.01 | 29-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.47 | 0.00 | 01-JAN-00:10 | 47004.73 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.47 | 0.00 | 01-JAN-00:10 | 47004.73 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 505.73 | 0.00 | 01-JAN-00:10 | 74900.01 | 29-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 505.73 | 0.00 | 01-JAN-00:10 | 74900.01 | 29-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 566.98 | 0.00 | 01-JAN-00:10 | 108148.46 | 19-JUL-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.21 | 0.00 | 01-JAN-00:10 | 27678.16 | 30-MAR-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.21 | 0.00 | 01-JAN-00:10 | 27678.16 | 30-MAR-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 566.76 | 0.00 | 01-JAN-00:10 | 108148.46 | 19-JUL-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 566.76 | 0.00 | 01-JAN-00:10 | 108148.46 | 19-JUL-08:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 982.51 | 0.00 | 01-JAN-00:10 | 180591.57 | 30-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.05 | 0.00 | 01-JAN-00:10 | 27987.40 | 30-MAR-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.05 | 0.00 | 01-JAN-00:10 | 27987.40 | 30-MAR-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 982.46 | 0.00 | 01-JAN-00:10 | 180591.57 | 30-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 982.46 | 0.00 | 01-JAN-00:10 | 180591.57 | 30-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 652.97 | 0.00 | 01-JAN-00:10 | 125246.13 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.03 | 0.00 | 01-JAN-00:10 | 9705.50 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.03 | 0.00 | 01-JAN-00:10 | 9705.50 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 652.94 | 0.00 | 01-JAN-00:10 | 125246.13 | 29-SEP-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 652.94 | 0.00 | 01-JAN-00:10 | 125246.13 | 29-SEP-15:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 47.98 | 0.00 | 01-JAN-00:10 | 10037.02 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 1.47 | 0.00 | 01-JAN-00:10 | 10037.02 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 1.47 | 0.00 | 01-JAN-00:10 | 10037.02 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 46.51 | 0.00 | 01-JAN-00:10 | 8222.97 | 16-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 46.51 | 0.00 | 01-JAN-00:10 | 8222.97 | 16-OCT-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 53.76 | 0.00 | 01-JAN-00:10 | 10737.45 | 19-JUL-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.56 | 0.00 | 01-JAN-00:10 | 6241.44 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.56 | 0.00 | 01-JAN-00:10 | 6241.44 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 53.20 | 0.00 | 01-JAN-00:10 | 10737.45 | 19-JUL-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 53.20 | 0.00 | 01-JAN-00:10 | 10737.45 | 19-JUL-09:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 91.83 | 0.00 | 01-JAN-00:10 | 18836.25 | 16-OCT-12:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.44 | 0.00 | 01-JAN-00:10 | 7043.76 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.44 | 0.00 | 01-JAN-00:10 | 7043.76 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 91.38 | 0.00 | 01-JAN-00:10 | 18836.25 | 16-OCT-12:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 91.38 | 0.00 | 01-JAN-00:10 | 18836.25 | 16-OCT-12:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 62.95 | 0.00 | 01-JAN-00:10 | 13050.97 | 29-SEP-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.31 | 0.00 | 01-JAN-00:10 | 4410.25 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.31 | 0.00 | 01-JAN-00:10 | 4410.25 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 62.64 | 0.00 | 01-JAN-00:10 | 13050.97 | 29-SEP-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 62.64 | 0.00 | 01-JAN-00:10 | 13050.97 | 29-SEP-15:30 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 75.29 | 0.00 | 01-JAN-00:10 | 10647.74 | 02-OCT-05:10 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.98 | 0.00 | 01-JAN-00:10 | 3086.67 | 31-DEC-09:20 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.98 | 0.00 | 01-JAN-00:10 | 3086.67 | 31-DEC-09:20 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 74.32 | 0.00 | 01-JAN-00:10 | 10647.74 | 02-OCT-05:10 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 74.32 | 0.00 | 01-JAN-00:10 | 10647.74 | 02-OCT-05:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 438.73 | 0.00 | 01-JAN-00:10 | 64720.02 | 16-OCT-16:00 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 5.61 | 0.00 | 01-JAN-00:10 | 24613.65 | 14-MAY-14:00 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 5.61 | 0.00 | 01-JAN-00:10 | 24613.65 | 14-MAY-14:00 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 433.12 | 0.00 | 01-JAN-00:10 | 64720.02 | 16-OCT-16:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 433.12 | 0.00 | 01-JAN-00:10 | 64720.02 | 16-OCT-16:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 70.52 | 0.00 | 01-JAN-00:10 | 17107.34 | 16-OCT-13:30 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 7.70 | 0.00 | 01-JAN-00:10 | 9239.72 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 7.70 | 0.00 | 01-JAN-00:10 | 9239.72 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 62.82 | 0.00 | 01-JAN-00:10 | 17107.34 | 16-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 62.82 | 0.00 | 01-JAN-00:10 | 17107.34 | 16-OCT-13:30 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 141.75 | 1125.26 | 07-JAN-08:00 | 8033.26 | 06-AUG-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 141.75 | 1125.26 | 07-JAN-08:00 | 8033.26 | 06-AUG-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 141.75 | 1125.26 | 07-JAN-08:00 | 8033.26 | 06-AUG-18:00 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1280.47 | 4415.61 | 01-JAN-06:50 | 74495.96 | 06-AUG-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1280.47 | 4415.61 | 01-JAN-06:50 | 74495.96 | 06-AUG-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1280.47 | 4415.61 | 01-JAN-06:50 | 74495.96 | 06-AUG-18:00 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 121.01 | 5.44 | 13-JAN-07:10 | 7557.63 | 06-AUG-17:50 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.11 | 0.00 | 02-JAN-09:40 | 541.80 | 08-JAN-07:00 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.11 | 0.00 | 02-JAN-09:40 | 541.80 | 08-JAN-07:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 120.90 | 0.00 | 01-JAN-00:10 | 7557.63 | 06-AUG-17:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 120.90 | 0.00 | 01-JAN-00:10 | 7557.63 | 06-AUG-17:50 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7164.92 | 87404.32 | 14-MAY-05:00 | 369607.28 | 14-AUG-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7164.92 | 87404.32 | 14-MAY-05:00 | 369607.28 | 14-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7164.92 | 87404.32 | 14-MAY-05:00 | 369607.28 | 14-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 407.69 | 0.00 | 01-JAN-00:10 | 224998.87 | 09-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 387.53 | 0.00 | 01-JAN-00:10 | 44746.54 | 02-FEB-13:00 |
WaterSystems:PlantLoopHeatingDemand | 387.53 | 0.00 | 01-JAN-00:10 | 44746.54 | 02-FEB-13:00 |
General:WaterSystems:PlantLoopHeatingDemand | 387.53 | 0.00 | 01-JAN-00:10 | 44746.54 | 02-FEB-13:00 |
EnergyTransfer:HVAC | 9437.26 | 11688.59 | 01-JAN-07:00 | 2473390.62 | 18-AUG-15:50 |
HeatingCoils:EnergyTransfer | 20.16 | 0.00 | 01-JAN-00:10 | 210143.58 | 09-JAN-07:10 |
PlantLoopHeatingDemand:HVAC | 20.16 | 0.00 | 01-JAN-00:10 | 210143.58 | 09-JAN-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 20.16 | 0.00 | 01-JAN-00:10 | 210143.58 | 09-JAN-07:10 |
CoolingCoils:EnergyTransfer | 9417.10 | 9030.25 | 03-JAN-07:10 | 2473390.62 | 18-AUG-15:50 |
EnergyTransfer:Plant | 18611.02 | 0.00 | 01-JAN-00:10 | 5840765.69 | 18-AUG-15:50 |
LoopToLoop:EnergyTransfer | 5835.70 | 0.00 | 01-JAN-00:10 | 1873472.03 | 18-AUG-15:50 |
WaterSystems:EnergyTransfer | 387.53 | 0.00 | 01-JAN-00:10 | 44746.54 | 02-FEB-13:00 |
WaterUse:WaterSystems:EnergyTransfer | 387.53 | 0.00 | 01-JAN-00:10 | 44746.54 | 02-FEB-13:00 |
Boilers:EnergyTransfer | 19.88 | 0.00 | 01-JAN-00:10 | 221872.03 | 09-JAN-06:10 |
Chillers:EnergyTransfer | 5853.29 | 0.00 | 01-JAN-00:10 | 1836233.24 | 18-AUG-15:50 |
HeatRejection:EnergyTransfer | 6514.62 | 0.00 | 01-JAN-00:10 | 2099733.98 | 18-AUG-15:50 |
General:HeatRejection:EnergyTransfer | 6514.62 | 0.00 | 01-JAN-00:10 | 2099733.98 | 18-AUG-15:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -641.235 | 0.000 | 0.000 | 91.742 | 216.171 | 424.397 | 0.000 | 0.000 | 0.000 | 0.005 | 0.000 | 0.000 | 0.000 | 0.000 | -91.075 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -671.616 | 0.000 | 0.000 | 83.403 | 194.137 | 289.614 | 0.000 | 0.000 | 0.000 | 104.463 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
CORE_MID | 0.000 | 0.000 | 0.000 | -4851.731 | 0.000 | 0.000 | 836.837 | 1941.366 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -822.600 |
CORE_TOP | 0.000 | 0.000 | 0.080 | -435.457 | 0.000 | 0.000 | 84.833 | 194.137 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -133.206 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -73.117 | 0.000 | 0.000 | 10.541 | 14.117 | 36.365 | 21.330 | 0.000 | 0.009 | 44.224 | 0.000 | -52.270 | 0.000 | -1.199 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -67.229 | 0.000 | 0.000 | 6.797 | 9.016 | 23.435 | 50.644 | 0.000 | 0.006 | 10.773 | 0.000 | -32.648 | 0.000 | -0.793 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -114.610 | 0.000 | 0.000 | 10.504 | 13.814 | 36.366 | 100.220 | 0.000 | 0.008 | 6.046 | 0.000 | -51.111 | 0.000 | -1.236 | -0.002 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -107.174 | 0.000 | 0.000 | 6.752 | 8.975 | 23.435 | 56.484 | 0.000 | 0.006 | 51.198 | 0.000 | -38.769 | 0.000 | -0.907 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.469 | -505.734 | 0.000 | 0.000 | 108.196 | 140.730 | 363.654 | 229.321 | 0.000 | 0.244 | 160.895 | 0.000 | -472.878 | 0.000 | -24.897 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.214 | -566.768 | 0.000 | 0.000 | 50.749 | 89.991 | 234.352 | 508.354 | 0.000 | 0.133 | 8.793 | 0.000 | -308.394 | 0.000 | -17.425 | -0.001 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.049 | -982.477 | 0.000 | 0.000 | 105.644 | 138.001 | 363.660 | 998.815 | 0.000 | 0.179 | 0.029 | 0.000 | -494.190 | 0.000 | -27.886 | -101.795 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.031 | -652.947 | 0.000 | 0.000 | 69.396 | 89.553 | 234.351 | 577.503 | 0.000 | 0.147 | 37.446 | 0.000 | -337.132 | 0.000 | -18.349 | 0.000 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 1.468 | -46.515 | 0.000 | 0.000 | 11.045 | 14.072 | 36.365 | 23.724 | 0.000 | 0.032 | 6.745 | 0.000 | -44.087 | 0.000 | -2.849 | -0.001 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.561 | -53.203 | 0.000 | 0.000 | 6.962 | 8.998 | 23.435 | 51.315 | 0.000 | 0.016 | 0.002 | 0.000 | -29.171 | 0.000 | -2.027 | -6.886 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.445 | -91.382 | 0.000 | 0.000 | 10.702 | 13.799 | 36.366 | 100.436 | 0.000 | 0.022 | 0.002 | 0.000 | -46.713 | 0.000 | -3.252 | -20.423 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.311 | -62.638 | 0.000 | 0.000 | 7.064 | 8.955 | 23.435 | 57.936 | 0.000 | 0.019 | 0.000 | 0.000 | -31.938 | 0.000 | -2.150 | -0.994 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -141.748 | 0.000 | 0.000 | 0.950 | 5.155 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -18.238 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.000 | -1280.472 | 0.000 | 0.000 | 9.501 | 51.551 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -319.386 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.110 | -120.899 | 0.000 | 0.000 | 0.950 | 5.155 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -39.197 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7164.922 | 0.000 | 0.000 | 20.516 | 62.653 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -413.104 |
GROUNDFLOOR_PLENUM | 0.975 | -74.318 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.014 | 75.949 | 0.000 | 0.000 | 0.000 | -2.621 | 0.000 |
MIDFLOOR_PLENUM | 5.609 | -433.121 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.287 | 471.833 | 0.000 | 0.000 | 0.000 | -44.607 | 0.000 |
TOPFLOOR_PLENUM | 7.700 | -62.821 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.026 | 59.844 | 0.000 | 0.000 | 0.000 | -4.749 | -0.000 |
Total Facility | 14.285 | -570.260 | 3.738 | -18631.871 | 0.000 | 0.000 | 1533.085 | 3220.346 | 14676.396 | 2776.081 | 0.000 | 1.147 | 1038.245 | 0.000 | -1939.302 | 0.000 | -154.948 | -1966.908 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 02-JAN-07:11 | 0.00 | 0.00 | 0.00 | -123754.11 | 0.00 | 0.00 | 1350.18 | 6467.36 | 13457.54 | 0.00 | 0.00 | 0.00 | 102479.03 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 02-JAN-05:11 | 0.00 | 0.00 | 0.00 | -97827.68 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 91352.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 17-OCT-04:12 | 0.00 | 0.00 | 0.00 | -810900.03 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 746150.20 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 10-AUG-05:02 | 0.00 | 0.00 | 0.00 | -76733.39 | 0.00 | 0.00 | 840.65 | 537.36 | 7647.36 | 0.00 | 0.00 | 0.00 | 67708.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 06-OCT-04:12 | 0.00 | 0.00 | 0.00 | -12300.08 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 13190.76 | 0.00 | -1674.47 | 0.00 | -29.25 | 0.00 |
PERIMETER_BOT_ZN_2 | 02-JUL-08:22 | 0.00 | 0.00 | 0.00 | -19179.56 | 0.00 | 0.00 | 23.65 | 37.27 | 464.11 | 12910.55 | 0.00 | 0.00 | 5782.75 | 0.00 | -0.00 | 0.00 | -38.76 | 0.00 |
PERIMETER_BOT_ZN_1 | 19-NOV-12:21 | 0.00 | 0.00 | 0.00 | -24028.52 | 0.00 | 0.00 | 32.64 | 57.83 | 720.19 | 23027.81 | 0.00 | 0.00 | 222.02 | 0.00 | -0.00 | 0.00 | -31.97 | 0.00 |
PERIMETER_BOT_ZN_4 | 28-MAY-16:12 | 0.00 | 0.00 | 0.00 | -24589.56 | 0.00 | 0.00 | 21.63 | 37.27 | 464.11 | 13955.84 | 0.00 | 0.00 | 10202.69 | 0.00 | -0.00 | 0.00 | -91.98 | 0.00 |
PERIMETER_MID_ZN_3 | 30-SEP-05:03 | 0.00 | 0.00 | 0.00 | -95833.94 | 0.00 | 0.00 | 1114.86 | 674.71 | 9602.45 | 0.00 | 0.00 | 0.00 | 94603.42 | 0.00 | -10159.27 | 0.00 | -2.23 | 0.00 |
PERIMETER_MID_ZN_2 | 04-JUL-09:02 | 0.00 | 0.00 | 0.00 | -197608.46 | 0.00 | 0.00 | 231.45 | 372.66 | 4641.14 | 114496.12 | 0.00 | 0.00 | 78680.13 | 0.00 | -0.00 | 0.00 | -813.03 | 0.00 |
PERIMETER_MID_ZN_1 | 15-OCT-12:11 | 0.00 | 0.00 | 0.00 | -236519.74 | 0.00 | 0.00 | 306.61 | 578.28 | 7201.95 | 209870.99 | 0.00 | 906.43 | 17655.48 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 15-OCT-14:51 | 0.00 | 0.00 | 0.00 | -218314.26 | 0.00 | 0.00 | 214.42 | 372.66 | 4641.11 | 140226.12 | 0.00 | 478.99 | 72380.96 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-OCT-13:10 | 0.00 | 0.00 | 0.00 | -8223.60 | 0.00 | 0.00 | 1165.18 | 1040.96 | 2160.55 | 4557.86 | 0.00 | 106.18 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -807.12 |
PERIMETER_TOP_ZN_2 | 06-AUG-08:42 | 0.00 | 0.00 | 0.00 | -19317.73 | 0.00 | 0.00 | 24.23 | 37.27 | 464.11 | 12208.20 | 0.00 | 0.00 | 6641.25 | 0.00 | -0.00 | 0.00 | -57.32 | 0.00 |
PERIMETER_TOP_ZN_1 | 15-OCT-11:01 | 0.00 | 0.00 | 0.00 | -24720.63 | 0.00 | 0.00 | 32.47 | 57.83 | 720.19 | 21188.18 | 0.00 | 51.89 | 2670.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 15-OCT-15:41 | 0.00 | 0.00 | 0.00 | -23636.26 | 0.00 | 0.00 | 19.95 | 37.27 | 464.11 | 12962.69 | 0.00 | 19.87 | 10132.37 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 06-AUG-17:52 | 0.00 | 0.00 | 0.00 | -8033.26 | 0.00 | 0.00 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 213.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 06-AUG-17:52 | 0.00 | 0.00 | 0.00 | -74495.96 | 0.00 | 0.00 | 0.00 | 250.08 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3698.34 |
DATACENTER_TOP_ZN_6 | 06-AUG-17:45 | 0.00 | 0.00 | 0.00 | -7557.63 | 0.00 | 0.00 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -261.80 |
DATACENTER_BASEMENT_ZN_6 | 14-AUG-16:00 | 0.00 | 0.00 | 0.00 | -369555.54 | 0.00 | 0.00 | 2153.56 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -17701.10 |
GROUNDFLOOR_PLENUM | 02-OCT-05:10 | 0.00 | -12435.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12453.99 | 0.00 | -0.00 | 0.00 | -18.42 | 0.00 |
MIDFLOOR_PLENUM | 02-OCT-05:15 | 0.00 | -72040.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72378.86 | 0.00 | -0.00 | 0.00 | -338.12 | 0.00 |
TOPFLOOR_PLENUM | 16-OCT-13:30 | 0.00 | -17108.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.37 | 16998.28 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-AUG-05:02 | 0.00 | 10205.94 | 0.00 | -1622322.10 | 0.00 | 0.00 | 15924.84 | 10917.52 | 616289.16 | 0.00 | 0.00 | 0.00 | 1036511.47 | 0.00 | -66492.11 | 0.00 | -1034.71 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 02-JAN-06:03 | 0.00 | 0.00 | 54363.66 | 0.00 | 0.00 | 0.00 | 1163.43 | 537.36 | 7647.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -63711.81 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 09-JAN-06:02 | 0.00 | 0.00 | 96824.74 | 0.00 | 0.00 | 0.00 | 1485.95 | 674.71 | 9602.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -47495.79 | 0.00 | -1096.85 | -59995.21 |
PERIMETER_MID_ZN_2 | 09-JAN-06:02 | 0.00 | 0.00 | 90197.36 | 0.00 | 0.00 | 0.00 | 944.75 | 434.81 | 6188.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -32971.17 | 0.00 | -753.69 | -64040.25 |
PERIMETER_MID_ZN_1 | 30-MAR-05:03 | 0.00 | 0.00 | 88167.49 | 0.00 | 0.00 | 0.00 | 1439.70 | 674.72 | 9602.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -42890.38 | 0.00 | -1305.93 | -55688.21 |
PERIMETER_MID_ZN_4 | 09-JAN-06:02 | 0.00 | 0.00 | 38713.94 | 0.00 | 0.00 | 0.00 | 916.45 | 434.81 | 6188.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -33338.58 | 0.00 | -762.57 | -12152.19 |
PERIMETER_TOP_ZN_3 | 09-JAN-05:11 | 0.00 | 0.00 | 12317.97 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3584.86 | 0.00 | -355.51 | -9190.63 |
PERIMETER_TOP_ZN_2 | 09-JAN-05:11 | 0.00 | 0.00 | 12784.82 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2503.81 | 0.00 | -250.05 | -10554.91 |
PERIMETER_TOP_ZN_1 | 02-JAN-05:11 | 0.00 | 0.00 | 16412.80 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1951.90 | 0.00 | -427.36 | -14846.58 |
PERIMETER_TOP_ZN_4 | 02-JAN-05:11 | 0.00 | 0.00 | 11997.15 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1412.98 | 0.00 | -304.76 | -10803.36 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 08-JAN-07:00 | 0.00 | 0.00 | 541.80 | 0.00 | 0.00 | 0.00 | 5.41 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2520.82 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 18-DEC-05:12 | 10983.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -362.74 | -10620.35 |
MIDFLOOR_PLENUM | 15-OCT-13:31 | 65759.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3132.58 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -68892.20 |
TOPFLOOR_PLENUM | 05-JUN-05:02 | 14417.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -59.87 | -14357.16 |
Total Facility | 30-MAR-05:03 | -954004.40 | 993675.94 | 330793.32 | -993675.94 | 0.00 | 0.00 | 17798.83 | 10917.52 | 497997.76 | 0.00 | 0.00 | 0.00 | 273481.88 | 0.00 | -169276.57 | 0.00 | -7708.34 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 10.4122 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.3519 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 97.9916 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 86.9928 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 9.9195 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.1142 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.5179 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.5179 | 0.2175 | 1.0000 | Not calculated | 1.2002 | 0.2175 | ||
AIRLOOP DATACENTER BASEMENT | 24.9150 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.9153 | 0.0136 | 1.0000 | Not calculated | 0.3384 | 0.0136 | ||
AIRLOOP DATACENTER BOT | 0.4844 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4844 | 0.0323 | 1.0000 | Not calculated | 0.0156 | 0.0323 | ||
AIRLOOP DATACENTER MID | 4.6238 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.6238 | 0.0338 | 1.0000 | Not calculated | 0.1563 | 0.0338 | ||
AIRLOOP DATACENTER TOP | 0.4697 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4697 | 0.0333 | 1.0000 | Not calculated | 0.0156 | 0.0333 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.2061 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.8885 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 48.9958 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 27.9997 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 4.9597 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.8645 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 0.0000 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 0.0000 | 1.0000 | 1.0000 | Not calculated | 1.2002 | |||
AIRLOOP DATACENTER BASEMENT | 24.9150 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.9150 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0136 | ||
AIRLOOP DATACENTER BOT | 0.4844 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4844 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0323 | ||
AIRLOOP DATACENTER MID | 4.6238 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.6238 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0338 | ||
AIRLOOP DATACENTER TOP | 0.4697 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4697 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0333 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 5.5179 | 5.5179 | 0.0000 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.8566 | 5.8566 | 1.9151 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 55.2232 | 55.2232 | 18.7207 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.3913 | 5.3913 | 1.9031 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8902 | 0.8902 | 0.2403 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0798 | 1.0798 | 0.2160 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2396 | 1.2396 | 0.2479 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3461 | 1.3461 | 0.2692 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.1500 | 8.1500 | 2.3554 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.0632 | 11.0632 | 2.2126 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.8654 | 11.8654 | 2.3731 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.6898 | 11.6898 | 2.3380 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9132 | 0.9132 | 0.2383 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1020 | 1.1020 | 0.2204 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2780 | 1.2780 | 0.2556 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2350 | 1.2350 | 0.2470 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4844 | 0.4844 | 0.4844 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.6238 | 4.6238 | 4.6238 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4697 | 0.4697 | 0.4697 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.9150 | 24.9150 | 24.9150 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 10.4122 | 9.3519 | 10.4122 | 2.8885 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 97.9916 | 86.9928 | 97.9916 | 27.9997 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 9.9195 | 9.1142 | 9.9195 | 2.8645 | 0.0000 | 1.0000 |
CAV_BAS | 5.5179 | 5.5179 | 5.5179 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.9150 | 24.9153 | 24.9150 | 24.9150 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4844 | 0.4844 | 0.4844 | 0.4844 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.6238 | 4.6238 | 4.6238 | 4.6238 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4697 | 0.4697 | 0.4697 | 0.4697 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 0.0000 | 0.0000 | 0.0000 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9283 | 2.9283 | 1.9151 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 27.6116 | 27.6116 | 18.7207 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6956 | 2.6956 | 1.9031 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4451 | 0.4451 | 0.2403 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5399 | 0.5399 | 0.2160 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6198 | 0.6198 | 0.2479 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6731 | 0.6731 | 0.2692 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.0750 | 4.0750 | 2.3554 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.5316 | 5.5316 | 2.2126 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.9327 | 5.9327 | 2.3731 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.8449 | 5.8449 | 2.3380 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4566 | 0.4566 | 0.2383 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5510 | 0.5510 | 0.2204 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6390 | 0.6390 | 0.2556 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6175 | 0.6175 | 0.2470 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4844 | 0.4844 | 0.4844 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.6238 | 4.6238 | 4.6238 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4697 | 0.4697 | 0.4697 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.9150 | 24.9150 | 24.9150 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.2061 | 2.8885 | 2.8885 | 2.8885 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 48.9958 | 27.9997 | 27.9997 | 27.9997 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 4.9597 | 2.8645 | 2.8645 | 2.8645 | 0.0000 | 1.0000 |
CAV_BAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.9150 | 24.9150 | 24.9150 | 24.9150 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4844 | 0.4844 | 0.4844 | 0.4844 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.6238 | 4.6238 | 4.6238 | 4.6238 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4697 | 0.4697 | 0.4697 | 0.4697 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 873.17 |
Number of hours not met | 873.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 30.41 | 282618.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1661.01 | 430824.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3220.35 | 325713.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 347.35 | 40855.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 55.01 | 3454.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 2505.76 | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2450.80 | 193755.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 405.25 | 46745.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 735.57 | 80352.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 480.19 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 392.79 | 45273.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 26936.30 |
Natural Gas | 0.00 | 30.41 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 26966.71 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 69.52 |
Space Heating | 0.00 |
Space Cooling | 35.86 |
Fans (All) | 52.91 |
Service Water Heating | 8.48 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 581.52 |
Subtotal | 581.52 |
Natural Gas [MJ/m2] | |
Space Heating | 0.66 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.66 |
Subtotal | 0.66 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 11.94 |
Space Heating | 0.11 |
Space Cooling | 6.16 |
Fans (All) | 9.09 |
Service Water Heating | 1.46 |
Receptacle Equipment | 54.42 |
Miscellaneous | 16.82 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 7567.00 | 1056.67 | 134.00 | 2.33 | 0.00 |
CORE_BOTTOM | 8665.67 | 94.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8700.50 | 59.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8685.17 | 74.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7992.83 | 767.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8694.83 | 65.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8681.17 | 78.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8644.00 | 116.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8701.17 | 58.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8702.00 | 58.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8654.00 | 106.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 6997.50 | 1762.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 6929.83 | 1830.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 6887.17 | 1872.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 3884.33 | 4875.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8730.83 | 29.17 | 0.00 | 0.00 | 0.00 |
Min | 3884.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 4875.67 | 134.00 | 2.33 | 0.00 |
Average | 8192.96 | 561.12 | 5.83 | 0.10 | 0.00 |
Sum | 188438.00 | 12905.67 | 134.00 | 2.33 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 357374.17 | 7350.67 | 3721.83 | 169.33 | 0.00 |
CORE_BOTTOM | 330746.00 | 67.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1103.50 | 1164.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1065.33 | 1202.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1044.17 | 1223.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 44676.67 | 58718.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 357374.17 | 58718.33 | 3721.83 | 169.33 | 0.00 |
Average | 77134.12 | 3031.61 | 161.82 | 7.36 | 0.00 |
Sum | 1774084.83 | 69727.00 | 3721.83 | 169.33 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 6533.67 | 2091.67 | 100.83 | 33.83 | 0.00 |
CORE_BOTTOM | 7604.17 | 1155.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 7903.17 | 856.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8155.33 | 604.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8354.33 | 405.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8451.00 | 309.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8275.17 | 484.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7303.67 | 1456.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8682.33 | 77.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8483.50 | 276.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8420.33 | 339.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8049.17 | 710.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8700.17 | 59.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8549.67 | 210.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8541.83 | 218.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8173.50 | 586.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7976.50 | 783.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7918.17 | 841.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7892.17 | 867.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 4670.17 | 4089.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 7897.17 | 862.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8145.33 | 614.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7963.00 | 797.00 | 0.00 | 0.00 | 0.00 |
Min | 4670.17 | 59.83 | 0.00 | 0.00 | 0.00 |
Max | 8700.17 | 4089.83 | 100.83 | 33.83 | 0.00 |
Average | 7941.02 | 813.12 | 4.38 | 1.47 | 0.00 |
Sum | 182643.50 | 18701.83 | 100.83 | 33.83 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 352328.67 | 12535.83 | 2886.00 | 865.50 | 0.00 |
CORE_BOTTOM | 329136.00 | 1677.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 329650.17 | 1162.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330061.00 | 752.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1643.00 | 625.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1599.33 | 668.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1582.17 | 685.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 54775.33 | 48619.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 352328.67 | 48619.67 | 2886.00 | 865.50 | 0.00 |
Average | 77270.64 | 2901.17 | 125.48 | 37.63 | 0.00 |
Sum | 1777224.67 | 66726.83 | 2886.00 | 865.50 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:46
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.545048E+11 | 123828.21 | 02-JAN-07:11 | 11.00 | 8.54 | 0.569783E+10 | 7499.58 | 10-JAN-14:09 | 16.83 | 11.85 |
February | 0.467494E+11 | 107238.51 | 27-FEB-07:11 | 10.33 | 8.74 | 0.516034E+10 | 7500.19 | 01-FEB-14:09 | 10.33 | 8.74 |
March | 0.554774E+11 | 109833.09 | 20-MAR-06:11 | 10.67 | 10.09 | 0.615772E+10 | 7499.38 | 09-MAR-14:09 | 10.67 | 10.09 |
April | 0.522750E+11 | 110623.49 | 10-APR-06:11 | 12.00 | 10.34 | 0.547351E+10 | 7499.65 | 13-APR-09:00 | 23.00 | 15.74 |
May | 0.524218E+11 | 107665.68 | 30-MAY-06:11 | 12.67 | 11.58 | 0.592437E+10 | 7499.40 | 04-MAY-09:00 | 12.67 | 11.58 |
June | 0.536206E+11 | 103761.09 | 12-JUN-06:11 | 14.00 | 12.64 | 0.590533E+10 | 7499.25 | 08-JUN-09:00 | 14.00 | 12.64 |
July | 0.529183E+11 | 102403.79 | 17-JUL-06:11 | 15.23 | 14.50 | 0.552852E+10 | 7554.73 | 17-JUL-09:00 | 23.00 | 17.86 |
August | 0.579186E+11 | 100991.80 | 21-AUG-06:11 | 16.67 | 15.12 | 0.629213E+10 | 10986.50 | 14-AUG-13:00 | 16.67 | 15.12 |
September | 0.480453E+11 | 101943.91 | 20-SEP-06:11 | 12.33 | 11.23 | 0.568303E+10 | 10379.41 | 29-SEP-13:00 | 34.00 | 17.85 |
October | 0.548629E+11 | 111330.52 | 30-OCT-06:11 | 11.00 | 7.26 | 0.598345E+10 | 11384.60 | 04-OCT-13:00 | 11.00 | 7.26 |
November | 0.564402E+11 | 107639.43 | 13-NOV-07:05 | 12.33 | 11.14 | 0.564159E+10 | 7500.06 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.560028E+11 | 108807.10 | 26-DEC-07:05 | 7.67 | 1.53 | 0.549794E+10 | 7500.24 | 20-DEC-14:00 | 7.67 | 1.53 |
Annual Sum or Average | 0.641237E+12 | 0.689458E+11 | ||||||||
Minimum of Months | 0.467494E+11 | 100991.80 | 7.67 | 1.53 | 0.516034E+10 | 7499.25 | 7.67 | 1.53 | ||
Maximum of Months | 0.579186E+11 | 123828.21 | 16.67 | 15.12 | 0.629213E+10 | 11384.60 | 34.00 | 17.86 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.486347E+11 | 97828.45 | 02-JAN-05:11 | 11.00 | 9.07 | 0.507729E+10 | 6735.05 | 10-JAN-14:09 | 16.83 | 11.85 |
February | 0.451764E+11 | 91618.88 | 21-FEB-05:12 | 8.00 | 6.97 | 0.460448E+10 | 6735.59 | 01-FEB-14:09 | 8.00 | 6.97 |
March | 0.556491E+11 | 90280.72 | 27-MAR-04:12 | 11.00 | 9.70 | 0.550004E+10 | 6735.04 | 01-MAR-14:09 | 11.00 | 9.70 |
April | 0.579238E+11 | 91227.88 | 10-APR-04:12 | 12.00 | 10.34 | 0.488158E+10 | 6735.18 | 13-APR-09:00 | 23.00 | 15.74 |
May | 0.518477E+11 | 89725.40 | 30-MAY-04:12 | 11.00 | 10.06 | 0.528494E+10 | 6735.23 | 03-MAY-13:00 | 11.00 | 10.06 |
June | 0.556764E+11 | 92165.65 | 12-JUN-04:12 | 13.07 | 11.97 | 0.527122E+10 | 6734.75 | 22-JUN-09:00 | 23.00 | 17.27 |
July | 0.629135E+11 | 90260.19 | 13-JUL-04:13 | 17.00 | 15.07 | 0.489634E+10 | 6734.77 | 11-JUL-09:09 | 17.00 | 15.07 |
August | 0.708498E+11 | 90731.12 | 01-AUG-04:13 | 17.00 | 15.07 | 0.549621E+10 | 6734.74 | 22-AUG-13:09 | 22.67 | 17.06 |
September | 0.524872E+11 | 92842.60 | 11-SEP-04:12 | 15.67 | 14.65 | 0.488270E+10 | 6734.75 | 12-SEP-09:00 | 23.00 | 17.26 |
October | 0.594193E+11 | 96396.12 | 10-OCT-04:11 | 12.67 | 12.11 | 0.507965E+10 | 6960.79 | 30-OCT-13:39 | 26.67 | 16.38 |
November | 0.547990E+11 | 93426.16 | 20-NOV-05:12 | 10.33 | 9.03 | 0.503003E+10 | 6735.49 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.562352E+11 | 93513.12 | 18-DEC-05:12 | 17.67 | 6.58 | 0.490130E+10 | 6735.80 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.671612E+12 | 0.609058E+11 | ||||||||
Minimum of Months | 0.451764E+11 | 89725.40 | 8.00 | 6.58 | 0.460448E+10 | 6734.74 | 8.00 | 6.97 | ||
Maximum of Months | 0.708498E+11 | 97828.45 | 17.67 | 15.07 | 0.550004E+10 | 6960.79 | 26.67 | 17.27 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.359480E+11 | 78445.85 | 18-JAN-06:02 | 15.67 | 11.88 | 0.503759E+10 | 6734.99 | 10-JAN-14:09 | 15.67 | 11.88 |
February | 0.330458E+11 | 78116.51 | 17-FEB-06:02 | 11.98 | 11.37 | 0.457066E+10 | 6735.38 | 01-FEB-14:09 | 11.98 | 11.37 |
March | 0.388084E+11 | 79103.93 | 23-MAR-05:02 | 10.67 | 9.62 | 0.546600E+10 | 6734.99 | 01-MAR-14:09 | 10.67 | 9.62 |
April | 0.392129E+11 | 79288.72 | 07-APR-05:02 | 13.00 | 11.29 | 0.485594E+10 | 6735.08 | 13-APR-13:00 | 20.00 | 15.65 |
May | 0.416405E+11 | 79225.97 | 23-MAY-05:02 | 12.33 | 10.66 | 0.526730E+10 | 6735.18 | 03-MAY-13:00 | 12.33 | 10.66 |
June | 0.437212E+11 | 80044.56 | 30-JUN-04:12 | 17.00 | 16.37 | 0.525947E+10 | 6734.73 | 26-JUN-09:00 | 17.00 | 16.37 |
July | 0.445904E+11 | 80507.44 | 27-JUL-04:12 | 16.00 | 16.00 | 0.488596E+10 | 6734.76 | 07-JUL-13:09 | 16.00 | 16.00 |
August | 0.480553E+11 | 81024.60 | 17-AUG-04:11 | 18.00 | 17.35 | 0.548897E+10 | 6734.76 | 22-AUG-13:09 | 22.67 | 17.06 |
September | 0.418807E+11 | 80226.70 | 25-SEP-04:12 | 17.00 | 16.37 | 0.486897E+10 | 6734.77 | 01-SEP-13:09 | 17.00 | 16.37 |
October | 0.434736E+11 | 81107.84 | 17-OCT-04:12 | 16.33 | 8.45 | 0.506112E+10 | 6735.00 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.379025E+11 | 78870.04 | 14-NOV-06:02 | 10.17 | 9.49 | 0.500208E+10 | 6735.31 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.368920E+11 | 78293.51 | 07-DEC-06:02 | 12.00 | 8.96 | 0.486070E+10 | 6735.62 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.485171E+12 | 0.606248E+11 | ||||||||
Minimum of Months | 0.330458E+11 | 78116.51 | 10.17 | 8.45 | 0.457066E+10 | 6734.73 | 10.67 | 9.62 | ||
Maximum of Months | 0.480553E+11 | 81107.84 | 18.00 | 17.35 | 0.548897E+10 | 6735.62 | 22.67 | 17.06 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.280566E+11 | 36941.80 | 19-JAN-15:00 | 20.00 | 15.12 | 0.479438E+10 | 6734.80 | 27-JAN-14:09 | 16.83 | 12.84 |
February | 0.267161E+11 | 37354.92 | 02-FEB-16:20 | 17.67 | 13.13 | 0.440242E+10 | 6735.59 | 01-FEB-14:09 | 17.67 | 13.13 |
March | 0.321385E+11 | 40739.61 | 24-MAR-15:30 | 18.00 | 15.20 | 0.529487E+10 | 6734.90 | 01-MAR-14:09 | 18.00 | 15.20 |
April | 0.361655E+11 | 74223.12 | 27-APR-05:02 | 15.00 | 14.41 | 0.479592E+10 | 6735.09 | 13-APR-13:00 | 15.00 | 14.41 |
May | 0.386928E+11 | 73988.14 | 03-MAY-05:02 | 14.17 | 14.07 | 0.521168E+10 | 6735.22 | 03-MAY-13:00 | 23.00 | 16.67 |
June | 0.428634E+11 | 75420.66 | 28-JUN-05:03 | 16.17 | 15.98 | 0.523488E+10 | 6734.71 | 26-JUN-09:00 | 16.17 | 15.98 |
July | 0.451581E+11 | 76476.33 | 28-JUL-05:02 | 17.00 | 17.00 | 0.487475E+10 | 6734.72 | 07-JUL-13:09 | 17.00 | 17.00 |
August | 0.480762E+11 | 76749.72 | 10-AUG-05:02 | 18.00 | 16.69 | 0.547548E+10 | 6734.72 | 22-AUG-13:09 | 22.67 | 17.06 |
September | 0.393929E+11 | 75500.01 | 22-SEP-05:02 | 18.00 | 17.35 | 0.483757E+10 | 6734.73 | 01-SEP-13:09 | 18.00 | 17.35 |
October | 0.392264E+11 | 76476.97 | 16-OCT-05:04 | 18.67 | 9.56 | 0.501036E+10 | 6734.86 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.302836E+11 | 70107.40 | 01-NOV-05:02 | 12.83 | 9.89 | 0.487257E+10 | 6735.21 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.286868E+11 | 36740.62 | 19-DEC-15:50 | 21.17 | 8.50 | 0.467058E+10 | 6735.52 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.435457E+12 | 0.594755E+11 | ||||||||
Minimum of Months | 0.267161E+11 | 36740.62 | 12.83 | 8.50 | 0.440242E+10 | 6734.71 | 15.00 | 11.71 | ||
Maximum of Months | 0.480762E+11 | 76749.72 | 21.17 | 17.35 | 0.547548E+10 | 6735.59 | 23.00 | 17.35 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.421510E+10 | 6065.99 | 17-JAN-13:40 | 23.33 | 17.00 | 0.620969E+09 | 845.64 | 27-JAN-14:09 | 16.83 | 12.84 |
February | 0.407337E+10 | 5191.39 | 01-FEB-12:00 | 26.00 | 14.67 | 0.568022E+09 | 845.73 | 01-FEB-14:09 | 19.00 | 15.70 |
March | 0.512631E+10 | 6067.57 | 13-MAR-13:40 | 17.67 | 13.75 | 0.679961E+09 | 845.66 | 01-MAR-14:09 | 17.67 | 13.75 |
April | 0.621513E+10 | 7299.49 | 26-APR-13:40 | 26.33 | 16.87 | 0.609158E+09 | 845.67 | 13-APR-09:00 | 26.33 | 16.87 |
May | 0.604494E+10 | 7071.37 | 04-MAY-13:30 | 23.00 | 16.67 | 0.659939E+09 | 845.69 | 03-MAY-13:00 | 23.00 | 16.67 |
June | 0.727104E+10 | 10631.08 | 26-JUN-04:12 | 17.67 | 15.32 | 0.660807E+09 | 845.63 | 22-JUN-09:00 | 17.67 | 15.32 |
July | 0.850384E+10 | 11289.40 | 03-JUL-05:03 | 17.17 | 15.14 | 0.614653E+09 | 845.63 | 07-JUL-13:09 | 22.83 | 17.20 |
August | 0.900707E+10 | 11768.45 | 21-AUG-05:02 | 16.92 | 15.63 | 0.689581E+09 | 845.63 | 22-AUG-13:09 | 22.67 | 17.06 |
September | 0.613798E+10 | 10437.67 | 22-SEP-05:02 | 18.00 | 17.35 | 0.610470E+09 | 845.63 | 01-SEP-13:09 | 18.00 | 17.35 |
October | 0.669697E+10 | 12303.03 | 06-OCT-04:12 | 19.00 | 17.08 | 0.634518E+09 | 849.05 | 30-OCT-13:39 | 26.67 | 16.38 |
November | 0.497277E+10 | 5852.37 | 13-NOV-11:30 | 18.50 | 14.08 | 0.624680E+09 | 845.70 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.485172E+10 | 6271.76 | 05-DEC-15:00 | 25.00 | 13.22 | 0.606069E+09 | 845.74 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.731162E+11 | 0.757883E+10 | ||||||||
Minimum of Months | 0.407337E+10 | 5191.39 | 16.92 | 13.22 | 0.568022E+09 | 845.63 | 16.83 | 12.37 | ||
Maximum of Months | 0.900707E+10 | 12303.03 | 26.33 | 17.35 | 0.689581E+09 | 849.05 | 26.67 | 17.35 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.410534E+10 | 7182.10 | 20-JAN-09:00 | 17.00 | 13.94 | 0.404058E+09 | 544.98 | 05-JAN-10:00 | 17.00 | 13.94 |
February | 0.376603E+10 | 10528.43 | 20-FEB-09:23 | 14.00 | 8.29 | 0.365196E+09 | 545.02 | 01-FEB-14:09 | 14.00 | 8.29 |
March | 0.472430E+10 | 9538.47 | 23-MAR-08:40 | 18.33 | 14.51 | 0.436507E+09 | 544.98 | 01-MAR-14:09 | 18.33 | 14.51 |
April | 0.606980E+10 | 18248.01 | 30-APR-09:53 | 25.00 | 16.34 | 0.391694E+09 | 545.01 | 13-APR-09:00 | 25.00 | 16.34 |
May | 0.572020E+10 | 18384.70 | 28-MAY-08:13 | 18.33 | 14.01 | 0.424913E+09 | 545.00 | 03-MAY-13:00 | 18.33 | 14.01 |
June | 0.637041E+10 | 18937.72 | 25-JUN-08:42 | 21.50 | 16.24 | 0.424668E+09 | 544.96 | 26-JUN-09:39 | 23.33 | 17.70 |
July | 0.780678E+10 | 19185.35 | 02-JUL-08:22 | 20.50 | 16.74 | 0.395708E+09 | 544.96 | 07-JUL-13:09 | 22.83 | 17.20 |
August | 0.836477E+10 | 19152.49 | 06-AUG-08:12 | 22.67 | 18.51 | 0.443667E+09 | 545.33 | 15-AUG-09:09 | 25.33 | 20.32 |
September | 0.580268E+10 | 18355.17 | 03-SEP-08:43 | 19.67 | 15.00 | 0.392729E+09 | 544.96 | 12-SEP-09:50 | 22.67 | 17.05 |
October | 0.587786E+10 | 18339.98 | 09-OCT-08:13 | 19.33 | 14.92 | 0.408741E+09 | 547.50 | 30-OCT-13:39 | 26.67 | 16.38 |
November | 0.435976E+10 | 7883.61 | 13-NOV-08:40 | 16.00 | 13.11 | 0.402071E+09 | 545.00 | 10-NOV-10:00 | 16.00 | 13.11 |
December | 0.426002E+10 | 7777.37 | 05-DEC-09:00 | 24.00 | 11.80 | 0.389724E+09 | 545.02 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.672279E+11 | 0.487968E+10 | ||||||||
Minimum of Months | 0.376603E+10 | 7182.10 | 14.00 | 8.29 | 0.365196E+09 | 544.96 | 14.00 | 8.29 | ||
Maximum of Months | 0.836477E+10 | 19185.35 | 25.00 | 18.51 | 0.443667E+09 | 547.50 | 26.67 | 20.32 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106760E+11 | 21602.10 | 22-JAN-10:32 | 15.63 | 11.46 | 0.633008E+09 | 873.62 | 18-JAN-14:09 | 15.63 | 11.46 |
February | 0.808431E+10 | 22565.33 | 20-FEB-12:02 | 17.00 | 9.91 | 0.571578E+09 | 846.45 | 16-FEB-14:00 | 17.00 | 9.91 |
March | 0.830045E+10 | 21653.58 | 19-MAR-12:53 | 20.00 | 15.11 | 0.680539E+09 | 846.46 | 10-MAR-14:50 | 20.00 | 15.11 |
April | 0.861615E+10 | 17308.78 | 09-APR-12:32 | 19.67 | 14.47 | 0.609365E+09 | 846.05 | 26-APR-13:20 | 26.67 | 17.00 |
May | 0.647972E+10 | 9153.20 | 04-MAY-12:30 | 23.50 | 16.62 | 0.657303E+09 | 845.72 | 03-MAY-13:00 | 23.50 | 16.62 |
June | 0.709756E+10 | 8236.82 | 30-JUN-12:30 | 23.50 | 17.99 | 0.659250E+09 | 845.64 | 22-JUN-09:00 | 23.50 | 17.99 |
July | 0.879851E+10 | 15408.01 | 30-JUL-13:13 | 24.00 | 19.70 | 0.614384E+09 | 845.65 | 07-JUL-13:09 | 24.00 | 19.70 |
August | 0.112625E+11 | 13913.54 | 13-AUG-12:43 | 24.00 | 19.32 | 0.690050E+09 | 846.50 | 29-AUG-13:00 | 24.00 | 17.64 |
September | 0.999647E+10 | 21315.24 | 10-SEP-13:02 | 22.17 | 18.15 | 0.612491E+09 | 884.54 | 29-SEP-13:20 | 35.33 | 18.10 |
October | 0.121261E+11 | 22210.73 | 15-OCT-12:32 | 32.00 | 16.19 | 0.640679E+09 | 1053.23 | 30-OCT-13:39 | 26.67 | 16.38 |
November | 0.111420E+11 | 24028.52 | 19-NOV-12:21 | 26.50 | 15.22 | 0.630839E+09 | 870.16 | 27-NOV-14:09 | 22.83 | 9.22 |
December | 0.120281E+11 | 23618.13 | 25-DEC-13:11 | 22.00 | 9.35 | 0.616542E+09 | 892.65 | 19-DEC-14:09 | 22.00 | 9.35 |
Annual Sum or Average | 0.114608E+12 | 0.761603E+10 | ||||||||
Minimum of Months | 0.647972E+10 | 8236.82 | 15.63 | 9.35 | 0.571578E+09 | 845.64 | 15.63 | 9.22 | ||
Maximum of Months | 0.121261E+11 | 24028.52 | 32.00 | 19.70 | 0.690050E+09 | 1053.23 | 35.33 | 19.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.551157E+10 | 9738.61 | 26-JAN-15:30 | 16.00 | 12.30 | 0.403111E+09 | 544.99 | 10-JAN-14:09 | 16.00 | 12.30 |
February | 0.586469E+10 | 22139.79 | 20-FEB-14:42 | 17.00 | 11.75 | 0.370850E+09 | 545.04 | 01-FEB-14:09 | 17.00 | 11.75 |
March | 0.810546E+10 | 22106.62 | 19-MAR-15:32 | 18.00 | 14.77 | 0.444629E+09 | 545.00 | 01-MAR-14:09 | 18.00 | 14.77 |
April | 0.108180E+11 | 23826.23 | 30-APR-15:52 | 22.00 | 15.83 | 0.396306E+09 | 545.01 | 13-APR-13:00 | 22.00 | 15.83 |
May | 0.789505E+10 | 24587.42 | 28-MAY-16:12 | 19.67 | 14.47 | 0.427031E+09 | 545.02 | 03-MAY-13:00 | 19.67 | 14.47 |
June | 0.993020E+10 | 22462.69 | 25-JUN-16:12 | 21.00 | 16.52 | 0.427371E+09 | 544.96 | 22-JUN-09:00 | 21.00 | 16.52 |
July | 0.123540E+11 | 23742.33 | 23-JUL-16:02 | 24.00 | 19.22 | 0.397823E+09 | 544.96 | 07-JUL-13:09 | 24.00 | 19.22 |
August | 0.141325E+11 | 24396.10 | 20-AUG-16:01 | 21.80 | 17.34 | 0.446109E+09 | 544.96 | 22-AUG-13:09 | 22.67 | 17.06 |
September | 0.810700E+10 | 24491.67 | 10-SEP-15:42 | 22.00 | 16.93 | 0.395369E+09 | 544.96 | 01-SEP-13:09 | 22.00 | 16.93 |
October | 0.861259E+10 | 23620.09 | 15-OCT-15:12 | 30.67 | 15.29 | 0.411506E+09 | 552.18 | 30-OCT-13:39 | 26.67 | 16.38 |
November | 0.769304E+10 | 23231.26 | 19-NOV-13:42 | 25.33 | 15.09 | 0.407341E+09 | 545.07 | 30-NOV-14:50 | 21.33 | 12.71 |
December | 0.814877E+10 | 23986.41 | 25-DEC-14:32 | 22.00 | 9.59 | 0.397104E+09 | 545.09 | 20-DEC-14:50 | 22.00 | 9.59 |
Annual Sum or Average | 0.107173E+12 | 0.492455E+10 | ||||||||
Minimum of Months | 0.551157E+10 | 9738.61 | 16.00 | 9.59 | 0.370850E+09 | 544.96 | 16.00 | 9.59 | ||
Maximum of Months | 0.141325E+11 | 24587.42 | 30.67 | 19.22 | 0.446109E+09 | 552.18 | 26.67 | 19.22 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.297391E+10 | 4128.60 | 18-JAN-14:20 | 24.07 | 14.82 | 0.570172E+09 | 845.62 | 25-JAN-14:00 | 17.00 | 13.48 |
February | 0.276091E+10 | 3463.26 | 01-FEB-13:20 | 22.33 | 14.89 | 0.531220E+09 | 845.69 | 01-FEB-14:09 | 19.00 | 15.70 |
March | 0.327722E+10 | 4158.41 | 23-MAR-14:40 | 22.33 | 17.37 | 0.636370E+09 | 845.62 | 09-MAR-14:39 | 22.33 | 17.37 |
April | 0.391649E+10 | 5634.52 | 26-APR-14:00 | 26.00 | 16.74 | 0.591052E+09 | 845.66 | 13-APR-13:00 | 26.00 | 16.74 |
May | 0.456351E+10 | 6216.19 | 04-MAY-13:50 | 23.00 | 16.67 | 0.649719E+09 | 845.68 | 03-MAY-13:00 | 23.00 | 16.67 |
June | 0.550979E+10 | 5990.94 | 29-JUN-16:00 | 23.00 | 18.43 | 0.656033E+09 | 845.62 | 26-JUN-09:00 | 23.00 | 18.43 |
July | 0.599065E+10 | 6627.73 | 19-JUL-14:50 | 27.00 | 20.29 | 0.611402E+09 | 845.63 | 07-JUL-13:09 | 27.00 | 20.29 |
August | 0.596530E+10 | 6558.17 | 17-AUG-14:00 | 28.00 | 21.19 | 0.684778E+09 | 845.63 | 22-AUG-13:09 | 22.67 | 17.06 |
September | 0.468418E+10 | 9583.45 | 30-SEP-05:03 | 23.80 | 13.84 | 0.602487E+09 | 845.63 | 01-SEP-13:09 | 23.80 | 13.84 |
October | 0.468414E+10 | 8164.41 | 02-OCT-05:02 | 19.08 | 17.74 | 0.621763E+09 | 845.64 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.319389E+10 | 3707.98 | 01-NOV-13:50 | 17.17 | 13.44 | 0.590237E+09 | 845.64 | 10-NOV-10:00 | 20.00 | 16.17 |
December | 0.305316E+10 | 4025.47 | 05-DEC-15:00 | 25.00 | 13.22 | 0.554496E+09 | 845.64 | 04-DEC-14:09 | 25.00 | 13.22 |
Annual Sum or Average | 0.505731E+11 | 0.729973E+10 | ||||||||
Minimum of Months | 0.276091E+10 | 3463.26 | 17.17 | 13.22 | 0.531220E+09 | 845.62 | 17.00 | 13.22 | ||
Maximum of Months | 0.599065E+10 | 9583.45 | 28.00 | 21.19 | 0.684778E+09 | 845.69 | 27.00 | 20.29 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.320622E+10 | 6246.48 | 20-JAN-09:30 | 18.00 | 14.38 | 0.283100E+09 | 521.21 | 19-JAN-11:20 | 18.00 | 14.38 |
February | 0.299351E+10 | 6307.67 | 21-FEB-09:40 | 16.00 | 10.67 | 0.257279E+09 | 521.27 | 01-FEB-13:50 | 16.00 | 10.67 |
March | 0.375273E+10 | 9169.13 | 19-MAR-10:03 | 18.33 | 14.18 | 0.307707E+09 | 521.24 | 10-MAR-08:09 | 18.33 | 14.18 |
April | 0.507649E+10 | 19515.67 | 30-APR-09:02 | 22.50 | 15.57 | 0.284375E+09 | 521.26 | 13-APR-10:09 | 22.50 | 15.57 |
May | 0.504096E+10 | 18772.00 | 28-MAY-08:43 | 18.83 | 14.19 | 0.308005E+09 | 521.29 | 24-MAY-10:39 | 18.83 | 14.19 |
June | 0.577868E+10 | 19515.42 | 18-JUN-08:32 | 21.00 | 16.35 | 0.308958E+09 | 521.22 | 22-JUN-10:09 | 23.00 | 17.27 |
July | 0.689740E+10 | 19760.49 | 04-JUL-09:02 | 22.00 | 15.93 | 0.290602E+09 | 521.21 | 05-JUL-07:10 | 18.33 | 15.09 |
August | 0.723969E+10 | 19383.41 | 20-AUG-09:22 | 22.00 | 18.63 | 0.324672E+09 | 521.21 | 31-AUG-07:10 | 18.33 | 16.25 |
September | 0.516213E+10 | 19587.68 | 10-SEP-08:52 | 22.00 | 17.40 | 0.284853E+09 | 521.22 | 12-SEP-10:09 | 22.83 | 17.20 |
October | 0.489178E+10 | 19488.29 | 15-OCT-08:12 | 30.33 | 14.69 | 0.296570E+09 | 521.27 | 30-OCT-12:09 | 24.33 | 16.19 |
November | 0.338083E+10 | 6827.20 | 19-NOV-09:13 | 24.67 | 13.00 | 0.286566E+09 | 521.24 | 10-NOV-11:09 | 24.67 | 13.00 |
December | 0.325588E+10 | 6323.39 | 05-DEC-09:20 | 24.67 | 12.23 | 0.274085E+09 | 521.23 | 07-DEC-11:00 | 21.00 | 14.99 |
Annual Sum or Average | 0.566763E+11 | 0.350677E+10 | ||||||||
Minimum of Months | 0.299351E+10 | 6246.48 | 16.00 | 10.67 | 0.257279E+09 | 521.21 | 16.00 | 10.67 | ||
Maximum of Months | 0.723969E+10 | 19760.49 | 30.33 | 18.63 | 0.324672E+09 | 521.29 | 24.67 | 17.27 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.102204E+11 | 21143.91 | 22-JAN-13:12 | 17.33 | 12.40 | 0.630540E+09 | 902.39 | 18-JAN-14:09 | 17.33 | 12.40 |
February | 0.732159E+10 | 20993.93 | 19-FEB-11:53 | 16.00 | 13.58 | 0.563976E+09 | 859.75 | 22-FEB-14:09 | 18.80 | 12.73 |
March | 0.689115E+10 | 20679.66 | 19-MAR-13:23 | 19.50 | 14.94 | 0.666394E+09 | 846.30 | 10-MAR-14:00 | 19.50 | 14.94 |
April | 0.670572E+10 | 11695.01 | 09-APR-13:02 | 19.83 | 14.43 | 0.600853E+09 | 845.71 | 13-APR-13:50 | 20.17 | 15.46 |
May | 0.534301E+10 | 8447.80 | 04-MAY-12:30 | 23.50 | 16.62 | 0.649792E+09 | 845.72 | 03-MAY-13:00 | 23.50 | 16.62 |
June | 0.569356E+10 | 7313.37 | 30-JUN-12:40 | 23.33 | 17.95 | 0.654347E+09 | 845.64 | 26-JUN-09:00 | 23.33 | 17.95 |
July | 0.662511E+10 | 10334.87 | 31-JUL-12:40 | 28.00 | 21.19 | 0.611101E+09 | 845.65 | 07-JUL-13:09 | 28.00 | 21.19 |
August | 0.859411E+10 | 12924.61 | 30-AUG-13:00 | 24.00 | 18.12 | 0.687202E+09 | 846.20 | 30-AUG-13:00 | 23.00 | 18.43 |
September | 0.914685E+10 | 20414.10 | 10-SEP-12:53 | 22.00 | 18.09 | 0.610308E+09 | 912.48 | 29-SEP-13:30 | 35.00 | 18.05 |
October | 0.109357E+11 | 23651.89 | 15-OCT-12:11 | 32.00 | 16.54 | 0.639394E+09 | 1007.33 | 30-OCT-13:30 | 26.50 | 16.48 |
November | 0.100234E+11 | 21779.80 | 26-NOV-12:22 | 16.05 | 11.16 | 0.628002E+09 | 894.55 | 27-NOV-14:09 | 22.83 | 9.22 |
December | 0.107451E+11 | 22335.89 | 24-DEC-13:02 | 17.00 | 11.59 | 0.613466E+09 | 918.00 | 19-DEC-14:09 | 17.00 | 11.59 |
Annual Sum or Average | 0.982457E+11 | 0.755538E+10 | ||||||||
Minimum of Months | 0.534301E+10 | 7313.37 | 16.00 | 11.16 | 0.563976E+09 | 845.64 | 17.00 | 9.22 | ||
Maximum of Months | 0.109357E+11 | 23651.89 | 32.00 | 21.19 | 0.687202E+09 | 1007.33 | 35.00 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.362312E+10 | 7982.05 | 18-JAN-15:00 | 23.00 | 14.79 | 0.374418E+09 | 544.96 | 27-JAN-14:20 | 16.67 | 12.79 |
February | 0.354603E+10 | 9147.36 | 20-FEB-15:32 | 17.00 | 11.06 | 0.345187E+09 | 545.02 | 01-FEB-14:09 | 17.00 | 11.06 |
March | 0.438022E+10 | 18969.18 | 19-MAR-16:01 | 17.83 | 14.89 | 0.412978E+09 | 544.98 | 01-MAR-14:09 | 17.83 | 14.89 |
April | 0.576483E+10 | 20336.14 | 30-APR-16:21 | 22.00 | 15.83 | 0.384601E+09 | 545.00 | 13-APR-13:00 | 22.00 | 15.83 |
May | 0.580763E+10 | 20390.52 | 14-MAY-16:32 | 17.00 | 12.41 | 0.418334E+09 | 545.01 | 03-MAY-13:00 | 17.00 | 12.41 |
June | 0.686393E+10 | 21204.75 | 18-JUN-16:42 | 21.17 | 17.23 | 0.422422E+09 | 544.96 | 26-JUN-09:00 | 24.00 | 18.12 |
July | 0.770947E+10 | 21485.97 | 16-JUL-16:12 | 20.67 | 16.41 | 0.395366E+09 | 544.96 | 07-JUL-13:09 | 20.67 | 16.41 |
August | 0.798462E+10 | 20234.49 | 13-AUG-16:02 | 23.83 | 19.84 | 0.443168E+09 | 544.96 | 22-AUG-13:09 | 22.67 | 17.06 |
September | 0.610501E+10 | 21261.35 | 04-SEP-16:02 | 19.67 | 15.96 | 0.389984E+09 | 544.96 | 01-SEP-13:09 | 19.67 | 15.96 |
October | 0.551175E+10 | 21831.71 | 15-OCT-14:51 | 31.00 | 15.50 | 0.401052E+09 | 544.97 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.415585E+10 | 9416.52 | 23-NOV-15:23 | 20.00 | 7.35 | 0.384095E+09 | 545.05 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.384179E+10 | 8489.51 | 18-DEC-15:30 | 22.00 | 8.99 | 0.365611E+09 | 545.06 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.652942E+11 | 0.473721E+10 | ||||||||
Minimum of Months | 0.354603E+10 | 7982.05 | 17.00 | 7.35 | 0.345187E+09 | 544.96 | 16.67 | 11.06 | ||
Maximum of Months | 0.798462E+10 | 21831.71 | 31.00 | 19.84 | 0.443168E+09 | 545.06 | 26.83 | 18.12 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.231222E+10 | 3772.37 | 18-JAN-15:00 | 23.00 | 14.79 | 0.538029E+09 | 845.62 | 24-JAN-14:00 | 25.00 | 15.45 |
February | 0.221388E+10 | 3172.45 | 16-FEB-14:50 | 17.08 | 13.83 | 0.501307E+09 | 845.71 | 01-FEB-14:09 | 17.08 | 13.83 |
March | 0.277091E+10 | 4271.72 | 23-MAR-15:10 | 21.83 | 17.37 | 0.602775E+09 | 845.62 | 21-MAR-13:09 | 21.83 | 17.37 |
April | 0.363920E+10 | 6142.87 | 26-APR-14:00 | 26.00 | 16.74 | 0.575594E+09 | 845.66 | 13-APR-13:00 | 26.00 | 16.74 |
May | 0.430246E+10 | 6762.08 | 04-MAY-13:50 | 23.00 | 16.67 | 0.635096E+09 | 845.69 | 03-MAY-13:00 | 23.00 | 16.67 |
June | 0.542532E+10 | 6597.05 | 30-JUN-14:00 | 23.00 | 17.85 | 0.650112E+09 | 845.62 | 26-JUN-09:00 | 23.00 | 17.85 |
July | 0.608571E+10 | 7404.45 | 19-JUL-14:50 | 27.00 | 20.29 | 0.608885E+09 | 845.63 | 07-JUL-13:09 | 27.00 | 20.29 |
August | 0.599715E+10 | 7180.94 | 17-AUG-14:00 | 28.00 | 21.19 | 0.680855E+09 | 845.63 | 22-AUG-13:09 | 22.67 | 17.06 |
September | 0.446825E+10 | 8152.48 | 29-SEP-13:50 | 34.33 | 17.92 | 0.592835E+09 | 845.63 | 01-SEP-13:09 | 34.33 | 17.92 |
October | 0.430625E+10 | 8222.97 | 16-OCT-13:10 | 33.75 | 16.65 | 0.608155E+09 | 845.64 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.260083E+10 | 3498.29 | 10-NOV-14:30 | 19.50 | 15.78 | 0.559340E+09 | 845.62 | 10-NOV-14:00 | 19.00 | 15.88 |
December | 0.239231E+10 | 3699.39 | 05-DEC-15:00 | 25.00 | 13.22 | 0.521110E+09 | 845.59 | 05-DEC-14:00 | 25.00 | 13.22 |
Annual Sum or Average | 0.465145E+11 | 0.707409E+10 | ||||||||
Minimum of Months | 0.221388E+10 | 3172.45 | 17.08 | 13.22 | 0.501307E+09 | 845.59 | 17.08 | 13.22 | ||
Maximum of Months | 0.608571E+10 | 8222.97 | 34.33 | 21.19 | 0.680855E+09 | 845.71 | 34.33 | 20.29 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.260263E+10 | 5035.61 | 20-JAN-09:50 | 18.67 | 14.64 | 0.373845E+09 | 544.96 | 05-JAN-10:00 | 18.67 | 14.64 |
February | 0.244767E+10 | 4973.28 | 02-FEB-10:10 | 17.17 | 12.19 | 0.342234E+09 | 545.02 | 01-FEB-14:09 | 17.17 | 12.19 |
March | 0.322996E+10 | 8058.92 | 23-MAR-09:30 | 20.50 | 15.62 | 0.410591E+09 | 544.96 | 09-MAR-14:09 | 20.50 | 15.62 |
April | 0.480985E+10 | 15372.17 | 30-APR-10:13 | 25.33 | 16.65 | 0.385169E+09 | 545.01 | 13-APR-09:00 | 25.33 | 16.65 |
May | 0.484557E+10 | 14636.84 | 28-MAY-08:43 | 18.83 | 14.19 | 0.415998E+09 | 545.00 | 03-MAY-13:00 | 18.83 | 14.19 |
June | 0.579183E+10 | 17429.64 | 18-JUN-09:43 | 22.00 | 16.85 | 0.419585E+09 | 544.97 | 26-JUN-09:00 | 24.00 | 18.12 |
July | 0.704085E+10 | 18849.85 | 23-JUL-07:42 | 22.67 | 18.90 | 0.394363E+09 | 544.97 | 17-JUL-09:00 | 22.67 | 18.90 |
August | 0.733932E+10 | 19328.34 | 06-AUG-08:42 | 23.67 | 19.12 | 0.442097E+09 | 544.96 | 29-AUG-13:09 | 25.67 | 17.79 |
September | 0.503968E+10 | 18728.78 | 10-SEP-08:32 | 21.00 | 17.14 | 0.385578E+09 | 544.96 | 12-SEP-09:00 | 23.00 | 17.26 |
October | 0.460191E+10 | 19105.62 | 15-OCT-10:22 | 31.50 | 16.45 | 0.400802E+09 | 544.99 | 27-OCT-09:00 | 22.00 | 11.71 |
November | 0.280871E+10 | 4504.36 | 01-NOV-09:30 | 15.00 | 12.66 | 0.382419E+09 | 544.98 | 10-NOV-10:00 | 20.00 | 16.17 |
December | 0.264498E+10 | 5075.83 | 05-DEC-09:50 | 25.67 | 12.88 | 0.361652E+09 | 544.96 | 19-DEC-10:09 | 23.33 | 10.05 |
Annual Sum or Average | 0.532030E+11 | 0.471433E+10 | ||||||||
Minimum of Months | 0.244767E+10 | 4504.36 | 15.00 | 12.19 | 0.342234E+09 | 544.96 | 17.17 | 10.05 | ||
Maximum of Months | 0.733932E+10 | 19328.34 | 31.50 | 19.12 | 0.442097E+09 | 545.02 | 25.67 | 18.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.880017E+10 | 22343.22 | 22-JAN-11:32 | 16.67 | 11.79 | 0.616243E+09 | 870.79 | 18-JAN-14:09 | 16.67 | 11.79 |
February | 0.632170E+10 | 22863.89 | 20-FEB-13:52 | 17.00 | 11.02 | 0.548040E+09 | 846.26 | 16-FEB-14:00 | 17.00 | 11.02 |
March | 0.610385E+10 | 18166.16 | 19-MAR-12:23 | 20.50 | 15.55 | 0.642892E+09 | 846.22 | 10-MAR-14:20 | 20.50 | 15.55 |
April | 0.640399E+10 | 12316.13 | 30-APR-13:32 | 24.00 | 16.71 | 0.588910E+09 | 845.71 | 13-APR-13:50 | 24.00 | 16.71 |
May | 0.512207E+10 | 8929.10 | 04-MAY-12:30 | 23.50 | 16.62 | 0.634615E+09 | 845.72 | 03-MAY-13:00 | 23.50 | 16.62 |
June | 0.569338E+10 | 7918.41 | 30-JUN-13:10 | 23.00 | 17.85 | 0.646374E+09 | 845.64 | 26-JUN-09:00 | 23.00 | 17.85 |
July | 0.681411E+10 | 11077.13 | 31-JUL-12:40 | 28.00 | 21.19 | 0.607547E+09 | 845.65 | 07-JUL-13:09 | 28.00 | 21.19 |
August | 0.871666E+10 | 13456.95 | 30-AUG-13:00 | 24.00 | 18.12 | 0.683500E+09 | 846.19 | 30-AUG-13:50 | 23.17 | 18.38 |
September | 0.891379E+10 | 21659.56 | 04-SEP-13:23 | 21.50 | 16.68 | 0.603694E+09 | 900.34 | 29-SEP-13:30 | 35.00 | 18.05 |
October | 0.104038E+11 | 24721.26 | 15-OCT-11:01 | 32.00 | 16.46 | 0.631089E+09 | 962.61 | 16-OCT-13:50 | 32.35 | 16.00 |
November | 0.880810E+10 | 22843.39 | 23-NOV-14:22 | 21.00 | 8.01 | 0.616341E+09 | 852.78 | 30-NOV-14:09 | 22.67 | 10.93 |
December | 0.927904E+10 | 23717.92 | 25-DEC-13:51 | 22.00 | 9.96 | 0.598599E+09 | 885.46 | 19-DEC-14:09 | 22.00 | 9.96 |
Annual Sum or Average | 0.913807E+11 | 0.741784E+10 | ||||||||
Minimum of Months | 0.512207E+10 | 7918.41 | 16.67 | 8.01 | 0.548040E+09 | 845.64 | 16.67 | 9.96 | ||
Maximum of Months | 0.104038E+11 | 24721.26 | 32.00 | 21.19 | 0.683500E+09 | 962.61 | 35.00 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.313091E+10 | 7783.16 | 18-JAN-15:00 | 23.00 | 14.79 | 0.359094E+09 | 544.96 | 24-JAN-14:00 | 25.00 | 15.45 |
February | 0.311952E+10 | 8683.14 | 22-FEB-15:50 | 16.30 | 12.09 | 0.330100E+09 | 545.05 | 01-FEB-14:09 | 16.30 | 12.09 |
March | 0.402655E+10 | 11511.41 | 19-MAR-16:23 | 17.50 | 14.74 | 0.394673E+09 | 544.98 | 01-MAR-14:09 | 17.50 | 14.74 |
April | 0.561920E+10 | 22349.45 | 30-APR-16:12 | 22.00 | 15.83 | 0.375090E+09 | 545.00 | 13-APR-13:00 | 22.00 | 15.83 |
May | 0.568627E+10 | 21530.86 | 29-MAY-16:42 | 18.00 | 13.36 | 0.408228E+09 | 545.02 | 03-MAY-13:00 | 18.00 | 13.36 |
June | 0.687335E+10 | 22283.78 | 18-JUN-16:52 | 21.00 | 17.19 | 0.417418E+09 | 544.95 | 26-JUN-09:00 | 24.00 | 18.12 |
July | 0.783544E+10 | 23139.45 | 04-JUL-16:41 | 19.33 | 15.39 | 0.393361E+09 | 544.96 | 07-JUL-13:09 | 22.83 | 17.20 |
August | 0.805314E+10 | 21770.90 | 06-AUG-16:41 | 23.17 | 19.14 | 0.440470E+09 | 544.96 | 29-AUG-13:09 | 25.67 | 17.79 |
September | 0.600420E+10 | 22374.57 | 04-SEP-16:02 | 19.67 | 15.96 | 0.383501E+09 | 544.96 | 01-SEP-13:09 | 19.67 | 15.96 |
October | 0.530249E+10 | 23636.46 | 15-OCT-15:41 | 30.17 | 14.99 | 0.392374E+09 | 544.97 | 31-OCT-13:09 | 26.83 | 16.92 |
November | 0.369168E+10 | 8338.78 | 10-NOV-14:50 | 19.17 | 15.85 | 0.368825E+09 | 545.04 | 30-NOV-14:00 | 21.00 | 13.08 |
December | 0.329458E+10 | 8205.98 | 19-DEC-15:30 | 21.50 | 8.94 | 0.349561E+09 | 545.05 | 20-DEC-14:00 | 19.00 | 12.37 |
Annual Sum or Average | 0.626373E+11 | 0.461269E+10 | ||||||||
Minimum of Months | 0.311952E+10 | 7783.16 | 16.30 | 8.94 | 0.330100E+09 | 544.95 | 16.30 | 12.09 | ||
Maximum of Months | 0.805314E+10 | 23636.46 | 30.17 | 19.14 | 0.440470E+09 | 545.05 | 26.83 | 18.12 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.453301E+10 | 8675.58 | 02-JAN-06:15 | 11.00 | 8.38 | 0.00 | 0.00 | 01-JAN-00:10 | 11.00 | 8.38 |
February | 0.410547E+10 | 6793.86 | 21-FEB-06:15 | 8.00 | 6.97 | 0.00 | 0.00 | 01-FEB-00:10 | 8.00 | 6.97 |
March | 0.501526E+10 | 6825.91 | 20-MAR-05:15 | 10.67 | 10.47 | 0.00 | 0.00 | 01-MAR-00:10 | 10.67 | 10.47 |
April | 0.635068E+10 | 7137.54 | 10-APR-05:15 | 12.00 | 10.34 | 0.00 | 0.00 | 01-APR-00:10 | 12.00 | 10.34 |
May | 0.539949E+10 | 7445.34 | 01-MAY-05:15 | 13.33 | 12.00 | 0.00 | 0.00 | 01-MAY-00:10 | 13.33 | 12.00 |
June | 0.669446E+10 | 7307.80 | 12-JUN-05:15 | 13.47 | 12.39 | 0.00 | 0.00 | 01-JUN-00:10 | 13.47 | 12.39 |
July | 0.795917E+10 | 8772.37 | 03-JUL-05:15 | 17.33 | 15.20 | 0.00 | 0.00 | 01-JUL-00:10 | 17.33 | 15.20 |
August | 0.881968E+10 | 9688.23 | 21-AUG-05:15 | 16.83 | 15.53 | 0.00 | 0.00 | 01-AUG-00:10 | 16.83 | 15.53 |
September | 0.653304E+10 | 9135.38 | 05-SEP-05:15 | 16.00 | 14.76 | 0.00 | 0.00 | 01-SEP-00:10 | 16.00 | 14.76 |
October | 0.746501E+10 | 12436.52 | 02-OCT-05:10 | 19.08 | 17.74 | 0.00 | 0.00 | 01-OCT-00:10 | 19.08 | 17.74 |
November | 0.574652E+10 | 8824.49 | 13-NOV-06:15 | 11.33 | 10.63 | 0.00 | 0.00 | 01-NOV-00:10 | 11.33 | 10.63 |
December | 0.569554E+10 | 9092.38 | 26-DEC-06:15 | 7.00 | 1.09 | 0.00 | 0.00 | 01-DEC-00:10 | 7.00 | 1.09 |
Annual Sum or Average | 0.743173E+11 | 0.00 | ||||||||
Minimum of Months | 0.410547E+10 | 6793.86 | 7.00 | 1.09 | 0.00 | 0.00 | 7.00 | 1.09 | ||
Maximum of Months | 0.881968E+10 | 12436.52 | 19.08 | 17.74 | 0.00 | 0.00 | 19.08 | 17.74 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.229098E+10 | 4087.88 | 18-JAN-06:10 | 15.67 | 11.88 | 0.00 | 0.00 | 01-JAN-00:10 | 15.67 | 11.88 |
February | 0.216300E+10 | 4297.91 | 03-FEB-06:10 | 12.33 | 3.94 | 0.00 | 0.00 | 01-FEB-00:10 | 12.33 | 3.94 |
March | 0.234810E+10 | 4545.62 | 23-MAR-05:10 | 10.67 | 9.62 | 0.00 | 0.00 | 01-MAR-00:10 | 10.67 | 9.62 |
April | 0.330599E+10 | 4406.83 | 27-APR-15:30 | 18.60 | 14.72 | 0.00 | 0.00 | 01-APR-00:10 | 18.60 | 14.72 |
May | 0.350013E+10 | 4539.27 | 06-MAY-05:10 | 14.17 | 13.59 | 0.00 | 0.00 | 01-MAY-00:10 | 14.17 | 13.59 |
June | 0.437650E+10 | 4843.31 | 30-JUN-16:00 | 22.70 | 17.88 | 0.00 | 0.00 | 01-JUN-00:10 | 22.70 | 17.88 |
July | 0.514907E+10 | 5209.33 | 19-JUL-15:30 | 26.00 | 20.22 | 0.00 | 0.00 | 01-JUL-00:10 | 26.00 | 20.22 |
August | 0.566481E+10 | 5441.77 | 18-AUG-15:20 | 26.00 | 20.57 | 0.00 | 0.00 | 01-AUG-00:10 | 26.00 | 20.57 |
September | 0.449084E+10 | 5757.40 | 30-SEP-05:15 | 23.80 | 13.84 | 0.00 | 0.00 | 01-SEP-00:10 | 23.80 | 13.84 |
October | 0.456566E+10 | 7204.42 | 02-OCT-05:15 | 19.07 | 17.72 | 0.00 | 0.00 | 01-OCT-00:10 | 19.07 | 17.72 |
November | 0.287799E+10 | 4628.73 | 14-NOV-06:10 | 10.17 | 9.49 | 0.00 | 0.00 | 01-NOV-00:10 | 10.17 | 9.49 |
December | 0.257896E+10 | 4453.07 | 20-DEC-06:10 | 8.67 | 1.20 | 0.00 | 0.00 | 01-DEC-00:10 | 8.67 | 1.20 |
Annual Sum or Average | 0.433120E+11 | 0.00 | ||||||||
Minimum of Months | 0.216300E+10 | 4087.88 | 8.67 | 1.20 | 0.00 | 0.00 | 8.67 | 1.20 | ||
Maximum of Months | 0.566481E+10 | 7204.42 | 26.00 | 20.57 | 0.00 | 0.00 | 26.00 | 20.57 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.190722E+10 | 7844.28 | 18-JAN-15:00 | 23.00 | 14.79 | 0.00 | 0.00 | 01-JAN-00:10 | 23.00 | 14.79 |
February | 0.196077E+10 | 7648.64 | 01-FEB-14:10 | 19.00 | 15.70 | 0.00 | 0.00 | 01-FEB-00:10 | 19.00 | 15.70 |
March | 0.294543E+10 | 11297.82 | 23-MAR-15:00 | 22.00 | 17.40 | 0.00 | 0.00 | 01-MAR-00:10 | 22.00 | 17.40 |
April | 0.582877E+10 | 14795.02 | 26-APR-13:50 | 26.17 | 16.81 | 0.00 | 0.00 | 01-APR-00:10 | 26.17 | 16.81 |
May | 0.584402E+10 | 13827.94 | 03-MAY-13:10 | 23.83 | 15.35 | 0.00 | 0.00 | 01-MAY-00:10 | 23.83 | 15.35 |
June | 0.787669E+10 | 13951.69 | 30-JUN-13:10 | 23.00 | 17.85 | 0.00 | 0.00 | 01-JUN-00:10 | 23.00 | 17.85 |
July | 0.975489E+10 | 15609.02 | 19-JUL-13:40 | 27.00 | 20.62 | 0.00 | 0.00 | 01-JUL-00:10 | 27.00 | 20.62 |
August | 0.100566E+11 | 14964.78 | 14-AUG-13:10 | 25.83 | 20.42 | 0.00 | 0.00 | 01-AUG-00:10 | 25.83 | 20.42 |
September | 0.675969E+10 | 15077.39 | 29-SEP-14:00 | 34.00 | 17.85 | 0.00 | 0.00 | 01-SEP-00:10 | 34.00 | 17.85 |
October | 0.561263E+10 | 17107.34 | 16-OCT-13:30 | 33.05 | 16.33 | 0.00 | 0.00 | 01-OCT-00:10 | 33.05 | 16.33 |
November | 0.239120E+10 | 7497.53 | 10-NOV-14:10 | 19.83 | 15.69 | 0.00 | 0.00 | 01-NOV-00:10 | 19.83 | 15.69 |
December | 0.188271E+10 | 7131.07 | 05-DEC-15:00 | 25.00 | 13.22 | 0.00 | 0.00 | 01-DEC-00:10 | 25.00 | 13.22 |
Annual Sum or Average | 0.628206E+11 | 0.00 | ||||||||
Minimum of Months | 0.188271E+10 | 7131.07 | 19.00 | 13.22 | 0.00 | 0.00 | 19.00 | 13.22 | ||
Maximum of Months | 0.100566E+11 | 17107.34 | 34.00 | 20.62 | 0.00 | 0.00 | 34.00 | 20.62 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.405909E+10 | 2134.72 | 30-JAN-16:50 | 14.00 | 11.30 | 95233223.31 | 126.84 | 20-JAN-14:00 | 14.00 | 11.30 |
February | 0.836391E+10 | 4141.14 | 22-FEB-17:00 | 14.00 | 12.23 | 86400611.10 | 126.84 | 13-FEB-14:00 | 14.00 | 12.23 |
March | 0.144319E+11 | 7028.25 | 31-MAR-24:00 | 9.70 | 9.11 | 0.103240E+09 | 126.84 | 24-MAR-09:09 | 9.70 | 9.11 |
April | 0.190177E+11 | 7917.99 | 16-APR-17:40 | 15.00 | 11.13 | 91606646.76 | 126.83 | 05-APR-09:09 | 15.00 | 11.13 |
May | 0.437407E+10 | 3305.68 | 31-MAY-24:00 | 13.10 | 11.97 | 99241059.31 | 126.84 | 05-MAY-13:00 | 13.10 | 11.97 |
June | 0.931974E+10 | 5349.89 | 30-JUN-24:00 | 16.40 | 15.78 | 98968250.46 | 126.85 | 28-JUN-13:09 | 16.40 | 15.78 |
July | 0.147592E+11 | 7222.24 | 31-JUL-23:45 | 18.15 | 17.39 | 91888421.57 | 126.84 | 20-JUL-09:09 | 18.15 | 17.39 |
August | 0.197599E+11 | 8033.26 | 06-AUG-17:52 | 21.00 | 18.98 | 0.103239E+09 | 126.83 | 08-AUG-09:09 | 20.42 | 18.12 |
September | 0.440004E+10 | 3559.66 | 30-SEP-24:00 | 18.40 | 17.30 | 91617145.98 | 126.85 | 25-SEP-13:50 | 18.40 | 17.30 |
October | 0.963939E+10 | 5324.59 | 31-OCT-24:00 | 14.90 | 11.04 | 95236929.04 | 126.86 | 05-OCT-09:09 | 14.90 | 11.04 |
November | 0.140767E+11 | 5997.00 | 07-NOV-16:20 | 18.33 | 14.34 | 94302969.21 | 126.83 | 10-NOV-14:39 | 19.33 | 15.82 |
December | 0.195460E+11 | 7978.95 | 25-DEC-16:13 | 19.33 | 9.96 | 91948319.49 | 130.55 | 19-DEC-10:00 | 19.33 | 9.96 |
Annual Sum or Average | 0.141748E+12 | 0.114292E+10 | ||||||||
Minimum of Months | 0.405909E+10 | 2134.72 | 9.70 | 9.11 | 86400611.10 | 126.83 | 9.70 | 9.11 | ||
Maximum of Months | 0.197599E+11 | 8033.26 | 21.00 | 18.98 | 0.103240E+09 | 130.55 | 20.42 | 18.12 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.288038E+10 | 1947.29 | 30-JAN-16:50 | 14.00 | 11.30 | 95233008.44 | 126.84 | 20-JAN-14:00 | 14.00 | 11.30 |
February | 0.713934E+10 | 3872.53 | 22-FEB-17:00 | 14.00 | 12.23 | 86400336.20 | 126.84 | 13-FEB-14:00 | 14.00 | 12.23 |
March | 0.129335E+11 | 6318.38 | 31-MAR-23:40 | 9.83 | 9.24 | 0.103240E+09 | 126.83 | 22-MAR-13:00 | 9.83 | 9.24 |
April | 0.176423E+11 | 7365.27 | 27-APR-17:30 | 16.50 | 14.05 | 91606888.01 | 126.83 | 05-APR-09:09 | 16.50 | 14.05 |
May | 0.367118E+10 | 2953.90 | 31-MAY-24:00 | 13.10 | 11.97 | 99240628.26 | 126.84 | 05-MAY-13:00 | 13.10 | 11.97 |
June | 0.852731E+10 | 5051.43 | 30-JUN-24:00 | 16.40 | 15.78 | 98967562.87 | 126.85 | 29-JUN-13:00 | 16.40 | 15.78 |
July | 0.138502E+11 | 6893.39 | 31-JUL-23:53 | 18.10 | 17.45 | 91888815.17 | 126.84 | 28-JUL-13:00 | 18.10 | 17.45 |
August | 0.186720E+11 | 7449.60 | 06-AUG-18:00 | 21.00 | 18.98 | 0.103239E+09 | 126.83 | 08-AUG-09:09 | 20.42 | 18.12 |
September | 0.374674E+10 | 3283.00 | 30-SEP-24:00 | 18.40 | 17.30 | 91614014.33 | 126.85 | 05-SEP-13:00 | 18.40 | 17.30 |
October | 0.865216E+10 | 4915.78 | 31-OCT-24:00 | 14.90 | 11.04 | 95236429.35 | 126.85 | 02-OCT-13:00 | 14.90 | 11.04 |
November | 0.126377E+11 | 5633.08 | 07-NOV-16:30 | 18.00 | 14.13 | 94303038.00 | 126.83 | 10-NOV-14:39 | 19.33 | 15.82 |
December | 0.176945E+11 | 7438.90 | 19-DEC-16:20 | 20.33 | 7.94 | 91900948.14 | 127.56 | 19-DEC-14:09 | 20.33 | 7.94 |
Annual Sum or Average | 0.128047E+12 | 0.114287E+10 | ||||||||
Minimum of Months | 0.288038E+10 | 1947.29 | 9.83 | 7.94 | 86400336.20 | 126.83 | 9.83 | 7.94 | ||
Maximum of Months | 0.186720E+11 | 7449.60 | 21.00 | 18.98 | 0.103240E+09 | 127.56 | 20.42 | 18.12 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.177891E+10 | 1879.91 | 30-JAN-16:50 | 14.00 | 11.30 | 95178028.71 | 126.84 | 20-JAN-14:00 | 14.00 | 11.30 |
February | 0.618205E+10 | 3865.81 | 22-FEB-17:00 | 14.00 | 12.23 | 86400300.80 | 126.84 | 13-FEB-14:00 | 14.00 | 12.23 |
March | 0.120583E+11 | 5967.09 | 31-MAR-23:20 | 9.97 | 9.37 | 0.103240E+09 | 126.83 | 22-MAR-13:00 | 9.97 | 9.37 |
April | 0.171763E+11 | 7417.38 | 26-APR-17:00 | 22.00 | 16.84 | 91607069.40 | 126.83 | 05-APR-09:09 | 22.00 | 16.84 |
May | 0.318447E+10 | 2697.37 | 31-MAY-23:40 | 13.20 | 12.26 | 99240713.78 | 126.84 | 05-MAY-13:00 | 13.20 | 12.26 |
June | 0.829999E+10 | 4932.12 | 30-JUN-24:00 | 16.40 | 15.78 | 98967889.93 | 126.85 | 28-JUN-13:50 | 16.40 | 15.78 |
July | 0.137426E+11 | 6802.57 | 31-JUL-23:53 | 18.10 | 17.45 | 91889056.33 | 126.84 | 28-JUL-13:00 | 18.10 | 17.45 |
August | 0.185417E+11 | 7557.63 | 06-AUG-17:45 | 21.33 | 19.00 | 0.103239E+09 | 126.83 | 08-AUG-09:09 | 20.42 | 18.12 |
September | 0.342561E+10 | 3239.79 | 30-SEP-23:50 | 18.37 | 17.42 | 91615008.04 | 126.85 | 28-SEP-13:00 | 18.37 | 17.42 |
October | 0.818834E+10 | 4704.49 | 31-OCT-23:40 | 15.13 | 11.58 | 95236484.81 | 126.85 | 05-OCT-13:00 | 15.13 | 11.58 |
November | 0.117544E+11 | 5614.74 | 07-NOV-16:30 | 18.00 | 14.13 | 94303097.77 | 126.84 | 10-NOV-14:39 | 19.33 | 15.82 |
December | 0.165662E+11 | 7441.98 | 19-DEC-16:20 | 20.33 | 7.94 | 91882428.68 | 126.84 | 19-DEC-14:09 | 20.33 | 7.94 |
Annual Sum or Average | 0.120899E+12 | 0.114280E+10 | ||||||||
Minimum of Months | 0.177891E+10 | 1879.91 | 9.97 | 7.94 | 86400300.80 | 126.83 | 9.97 | 7.94 | ||
Maximum of Months | 0.185417E+11 | 7557.63 | 22.00 | 19.00 | 0.103240E+09 | 126.85 | 22.00 | 18.12 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.240053E+12 | 92725.78 | 02-JAN-16:55 | 11.00 | 7.91 | 0.206142E+10 | 2746.36 | 17-JAN-14:20 | 22.67 | 16.64 |
February | 0.436087E+12 | 183666.00 | 21-FEB-17:00 | 16.00 | 13.03 | 0.187017E+10 | 2746.03 | 09-FEB-14:20 | 16.00 | 13.03 |
March | 0.728708E+12 | 358090.31 | 31-MAR-24:00 | 9.70 | 9.11 | 0.223516E+10 | 2750.91 | 23-MAR-13:39 | 9.70 | 9.11 |
April | 0.942158E+12 | 367065.94 | 26-APR-16:00 | 22.00 | 16.41 | 0.198521E+10 | 2751.70 | 27-APR-09:09 | 19.33 | 16.00 |
May | 0.239970E+12 | 175301.64 | 31-MAY-24:00 | 13.10 | 11.97 | 0.214804E+10 | 2746.15 | 04-MAY-13:09 | 13.10 | 11.97 |
June | 0.468425E+12 | 267087.42 | 30-JUN-24:00 | 16.40 | 15.78 | 0.214266E+10 | 2749.06 | 21-JUN-13:00 | 16.40 | 15.78 |
July | 0.730277E+12 | 359145.32 | 31-JUL-23:53 | 18.10 | 17.45 | 0.199061E+10 | 2751.00 | 25-JUL-13:50 | 18.10 | 17.45 |
August | 0.974769E+12 | 369607.28 | 14-AUG-16:00 | 25.00 | 18.49 | 0.228196E+10 | 3303.58 | 17-AUG-13:00 | 28.00 | 21.19 |
September | 0.234178E+12 | 176337.98 | 30-SEP-24:00 | 18.40 | 17.30 | 0.198296E+10 | 2746.61 | 13-SEP-13:00 | 18.40 | 17.30 |
October | 0.486646E+12 | 267916.53 | 31-OCT-24:00 | 14.90 | 11.04 | 0.206175E+10 | 2748.96 | 06-OCT-13:50 | 14.90 | 11.04 |
November | 0.707535E+12 | 276341.86 | 13-NOV-17:00 | 15.00 | 13.80 | 0.204180E+10 | 2750.31 | 10-NOV-14:00 | 15.00 | 13.80 |
December | 0.976119E+12 | 367982.42 | 26-DEC-17:00 | 16.00 | 8.71 | 0.198949E+10 | 2750.72 | 08-DEC-14:30 | 16.00 | 8.71 |
Annual Sum or Average | 0.716492E+13 | 0.247912E+11 | ||||||||
Minimum of Months | 0.234178E+12 | 92725.78 | 9.70 | 7.91 | 0.187017E+10 | 2746.03 | 9.70 | 8.71 | ||
Maximum of Months | 0.976119E+12 | 369607.28 | 25.00 | 18.49 | 0.228196E+10 | 3303.58 | 28.00 | 21.19 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 75349515.07 | 54373.80 | 02-JAN-06:03 | 11.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 4613887.85 | 30759.25 | 26-DEC-06:03 | 7.00 |
Annual Sum or Average | 79963402.92 | |||
Minimum of Months | 0.00 | 0.00 | 7.00 | |
Maximum of Months | 75349515.07 | 54373.80 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 32412613.41 | 9682.80 | 09-JAN-06:02 | 2.17 |
February | 186546.53 | 1066.86 | 06-FEB-06:03 | 9.00 |
March | 10599198.75 | 9374.85 | 30-MAR-05:03 | 4.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 148728.18 | 991.52 | 27-NOV-06:03 | 10.67 |
December | 3579019.96 | 5088.76 | 13-DEC-06:03 | 6.17 |
Annual Sum or Average | 46926106.83 | |||
Minimum of Months | 0.00 | 0.00 | 2.17 | |
Maximum of Months | 32412613.41 | 9682.80 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11165681.76 | 9020.50 | 09-JAN-06:02 | 2.17 |
February | 124728.33 | 413.33 | 06-FEB-06:05 | 9.00 |
March | 8111081.74 | 8750.12 | 30-MAR-05:03 | 4.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 1954253.41 | 5116.16 | 13-DEC-06:03 | 6.17 |
Annual Sum or Average | 21355745.25 | |||
Minimum of Months | 0.00 | 0.00 | 2.17 | |
Maximum of Months | 11165681.76 | 9020.50 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 4861840.21 | 8816.78 | 30-MAR-05:03 | 4.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 73726.96 | 491.51 | 13-DEC-06:03 | 6.17 |
Annual Sum or Average | 4935567.17 | |||
Minimum of Months | 0.00 | 0.00 | 4.97 | |
Maximum of Months | 4861840.21 | 8816.78 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2779853.81 | 3871.52 | 09-JAN-06:02 | 2.17 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 367091.11 | 1524.04 | 30-MAR-05:03 | 4.97 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 3146944.92 | |||
Minimum of Months | 0.00 | 0.00 | 2.17 | |
Maximum of Months | 2779853.81 | 3871.52 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.530123E+09 | 12318.07 | 09-JAN-05:11 | 4.67 |
February | 0.198899E+09 | 11372.73 | 06-FEB-05:12 | 8.33 |
March | 0.258638E+09 | 11616.23 | 30-MAR-04:12 | 4.57 |
April | 20844436.98 | 10671.45 | 01-APR-05:03 | 7.83 |
May | 2713294.59 | 9808.74 | 15-MAY-05:03 | 8.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 7618567.26 | 10544.82 | 30-OCT-05:03 | 10.83 |
November | 0.131442E+09 | 11351.00 | 27-NOV-05:12 | 8.67 |
December | 0.318094E+09 | 11336.88 | 13-DEC-05:12 | 6.67 |
Annual Sum or Average | 0.146837E+10 | |||
Minimum of Months | 0.00 | 0.00 | 4.57 | |
Maximum of Months | 0.530123E+09 | 12318.07 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.208602E+09 | 12785.04 | 09-JAN-05:11 | 4.67 |
February | 80531962.06 | 11512.51 | 06-FEB-05:12 | 8.33 |
March | 0.103450E+09 | 12252.36 | 30-MAR-04:12 | 4.57 |
April | 7476311.46 | 10302.77 | 01-APR-05:03 | 7.83 |
May | 846738.69 | 2824.29 | 15-MAY-05:03 | 8.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 1546589.95 | 3176.96 | 30-OCT-05:03 | 10.83 |
November | 42311464.81 | 11037.64 | 06-NOV-06:02 | 10.17 |
December | 0.115822E+09 | 11851.14 | 13-DEC-05:12 | 6.67 |
Annual Sum or Average | 0.560588E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.57 | |
Maximum of Months | 0.208602E+09 | 12785.04 | 18.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.156626E+09 | 16412.91 | 02-JAN-05:11 | 11.00 |
February | 55503471.38 | 14934.32 | 13-FEB-06:02 | 14.83 |
March | 0.145806E+09 | 15900.61 | 30-MAR-04:12 | 4.57 |
April | 14148988.72 | 14392.68 | 01-APR-05:03 | 7.83 |
May | 5374164.25 | 9693.06 | 15-MAY-05:03 | 8.50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 12290828.00 | 12104.22 | 27-NOV-06:03 | 10.67 |
December | 54899602.42 | 15393.24 | 13-DEC-05:12 | 6.67 |
Annual Sum or Average | 0.444648E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.57 | |
Maximum of Months | 0.156626E+09 | 16412.91 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.154511E+09 | 11997.25 | 02-JAN-05:11 | 11.00 |
February | 27200876.51 | 8502.07 | 06-FEB-06:03 | 9.00 |
March | 56427820.57 | 10684.41 | 08-MAR-06:02 | 5.17 |
April | 5813557.46 | 8178.30 | 01-APR-05:03 | 7.83 |
May | 281934.14 | 1712.25 | 13-MAY-05:03 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 12139228.29 | 8449.39 | 06-NOV-06:02 | 10.17 |
December | 54590691.91 | 10691.31 | 14-DEC-06:02 | 7.17 |
Annual Sum or Average | 0.310965E+09 | |||
Minimum of Months | 0.00 | 0.00 | 5.17 | |
Maximum of Months | 0.154511E+09 | 11997.25 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 70543849.48 | 8519.65 | 02-JAN-05:11 | 11.00 |
February | 66012215.76 | 8394.83 | 13-FEB-05:12 | 14.33 |
March | 76191998.86 | 8988.69 | 27-MAR-04:12 | 11.00 |
April | 90814044.28 | 10056.72 | 03-APR-04:12 | 11.67 |
May | 69400405.64 | 7416.27 | 01-MAY-04:12 | 13.00 |
June | 55175973.17 | 7831.68 | 19-JUN-04:12 | 16.00 |
July | 99027921.72 | 8735.18 | 13-JUL-04:11 | 17.00 |
August | 0.103873E+09 | 8391.10 | 24-AUG-04:11 | 16.33 |
September | 57985673.64 | 7867.36 | 01-SEP-04:12 | 15.00 |
October | 82664279.00 | 8695.11 | 04-OCT-04:12 | 20.00 |
November | 93701594.49 | 8521.72 | 06-NOV-05:12 | 10.00 |
December | 0.109956E+09 | 10982.43 | 18-DEC-05:12 | 17.67 |
Annual Sum or Average | 0.975347E+09 | |||
Minimum of Months | 55175973.17 | 7416.27 | 10.00 | |
Maximum of Months | 0.109956E+09 | 10982.43 | 20.00 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 83875820.45 | 5434.83 | 17-JAN-06:02 | 15.83 |
February | 55303358.43 | 5604.56 | 14-FEB-06:03 | 13.00 |
March | 40650878.11 | 6384.85 | 19-MAR-15:21 | 18.00 |
April | 39756390.38 | 4932.11 | 02-APR-14:18 | 22.33 |
May | 44951190.71 | 4547.64 | 11-MAY-05:02 | 11.17 |
June | 28491062.83 | 4963.48 | 12-JUN-04:12 | 13.07 |
July | 41917742.22 | 4248.57 | 12-JUL-04:11 | 17.00 |
August | 32606389.27 | 4070.80 | 30-AUG-04:12 | 18.00 |
September | 39683012.12 | 5889.44 | 04-SEP-14:42 | 21.00 |
October | 53836993.65 | 6576.04 | 15-OCT-13:31 | 31.33 |
November | 45559327.71 | 5057.44 | 28-NOV-06:03 | 15.67 |
December | 54286869.89 | 5032.44 | 14-DEC-06:02 | 7.17 |
Annual Sum or Average | 0.560919E+09 | |||
Minimum of Months | 28491062.83 | 4070.80 | 7.17 | |
Maximum of Months | 83875820.45 | 6576.04 | 31.33 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153177E+10 | 10686.89 | 09-JAN-06:02 | 2.17 |
February | 0.101236E+10 | 6690.01 | 09-FEB-06:04 | 6.45 |
March | 0.120792E+10 | 8300.54 | 24-MAR-05:03 | 12.00 |
April | 0.450555E+09 | 12290.08 | 25-APR-05:02 | 11.33 |
May | 0.356893E+09 | 12284.33 | 04-MAY-05:02 | 14.33 |
June | 0.149935E+09 | 14416.60 | 05-JUN-05:02 | 12.17 |
July | 73078535.37 | 12249.81 | 06-JUL-05:03 | 14.33 |
August | 78976166.31 | 12184.08 | 31-AUG-05:03 | 15.17 |
September | 0.183418E+09 | 12859.37 | 12-SEP-05:02 | 15.00 |
October | 0.420297E+09 | 12610.45 | 18-OCT-05:03 | 15.00 |
November | 0.885754E+09 | 12132.91 | 01-NOV-05:02 | 12.83 |
December | 0.134933E+10 | 6673.27 | 21-DEC-06:04 | 6.93 |
Annual Sum or Average | 0.770029E+10 | |||
Minimum of Months | 73078535.37 | 6673.27 | 2.17 | |
Maximum of Months | 0.153177E+10 | 14416.60 | 15.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.109600E+09 | 541.80 | 08-JAN-07:00 | 1.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.109600E+09 | |||
Minimum of Months | 0.00 | 0.00 | 1.00 | |
Maximum of Months | 0.109600E+09 | 541.80 | 18.42 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 8.83 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 13.23 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 7.63 |
April | 0.00 | 0.00 | 01-APR-00:10 | 9.63 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15.20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13.07 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.07 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.07 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 18.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14.77 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 10.63 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 7.63 | |
Maximum of Months | 0.00 | 0.00 | 18.42 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180249E+11 | 19402.09 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.163527E+11 | 19402.09 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.194806E+11 | 19402.09 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.173504E+11 | 19402.09 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.187528E+11 | 19402.09 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.186803E+11 | 19402.09 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.174228E+11 | 19402.09 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.194803E+11 | 19402.09 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.173504E+11 | 19402.09 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.180252E+11 | 19402.09 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.178272E+11 | 19402.09 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.174231E+11 | 19402.09 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.216171E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.163527E+11 | 19402.09 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.194806E+11 | 19402.09 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.130776E+10 | 2187.81 | 02-JAN-16:30 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.110211E+10 | 2187.81 | 27-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.125910E+10 | 1524.25 | 01-MAR-16:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.107266E+10 | 1524.25 | 21-APR-15:00 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.113050E+10 | 1242.97 | 08-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.111866E+10 | 1242.97 | 09-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.104621E+10 | 1141.96 | 11-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.118336E+10 | 1242.97 | 21-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.110444E+10 | 1625.25 | 18-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.122938E+10 | 1906.53 | 20-OCT-15:00 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.127530E+10 | 2187.81 | 06-NOV-16:19 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.128781E+10 | 2187.81 | 01-DEC-16:19 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.141173E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.104621E+10 | 1141.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.130776E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.820470E+09 | 1409.91 | 02-JAN-16:30 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.701256E+09 | 1409.91 | 27-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.804788E+09 | 982.28 | 01-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.691517E+09 | 982.28 | 21-APR-15:39 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.733795E+09 | 735.93 | 08-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.726800E+09 | 735.93 | 08-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.679512E+09 | 735.93 | 28-JUL-15:20 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.765224E+09 | 735.93 | 21-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.707163E+09 | 982.28 | 18-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.773207E+09 | 1228.64 | 20-OCT-15:50 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.808887E+09 | 1409.91 | 06-NOV-16:19 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.803447E+09 | 1409.91 | 01-DEC-16:10 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.901606E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.679512E+09 | 735.93 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.820470E+09 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123174E+10 | 2187.86 | 02-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.106461E+10 | 2187.86 | 27-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.124243E+10 | 1524.28 | 16-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.107345E+10 | 1524.28 | 21-APR-15:00 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.114031E+10 | 1243.00 | 08-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.113075E+10 | 1243.00 | 08-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.105688E+10 | 1141.99 | 11-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.119052E+10 | 1243.00 | 21-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.109701E+10 | 1524.28 | 18-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.116710E+10 | 1524.28 | 04-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.121668E+10 | 2187.86 | 06-NOV-16:40 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.120219E+10 | 2187.86 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.138137E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.105688E+10 | 1141.99 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.124243E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.812829E+09 | 1409.91 | 02-JAN-16:49 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.695793E+09 | 1409.91 | 27-FEB-16:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.804712E+09 | 1047.37 | 16-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.692280E+09 | 982.28 | 05-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.732827E+09 | 982.28 | 09-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.724036E+09 | 801.02 | 08-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.676944E+09 | 801.02 | 11-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.766027E+09 | 982.28 | 21-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.711138E+09 | 1228.64 | 18-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.767206E+09 | 1228.64 | 05-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.793902E+09 | 1409.91 | 06-NOV-16:40 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.797449E+09 | 1409.91 | 01-DEC-16:19 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.897514E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.676944E+09 | 801.02 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.812829E+09 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.130067E+10 | 2187.81 | 02-JAN-16:30 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.109681E+10 | 2187.81 | 27-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.125590E+10 | 1524.25 | 01-MAR-16:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.107115E+10 | 1524.25 | 21-APR-15:00 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.112950E+10 | 1242.97 | 08-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.111779E+10 | 1141.96 | 08-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.104576E+10 | 1141.96 | 11-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.118181E+10 | 1242.97 | 21-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.110203E+10 | 1524.25 | 05-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.122106E+10 | 1906.53 | 23-OCT-15:00 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.126957E+10 | 2187.81 | 06-NOV-16:19 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.128094E+10 | 2187.81 | 01-DEC-16:19 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.140730E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.104576E+10 | 1141.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.130067E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.818056E+09 | 1409.91 | 02-JAN-16:30 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.699624E+09 | 1409.91 | 27-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.803179E+09 | 982.28 | 01-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.690668E+09 | 982.28 | 21-APR-15:50 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.732768E+09 | 735.93 | 08-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.725843E+09 | 735.93 | 09-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.678759E+09 | 735.93 | 28-JUL-15:39 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.764618E+09 | 735.93 | 21-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.706066E+09 | 982.28 | 18-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.770427E+09 | 1228.64 | 20-OCT-15:50 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.807765E+09 | 1409.91 | 06-NOV-16:19 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.801338E+09 | 1409.91 | 01-DEC-16:10 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.899911E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.678759E+09 | 735.93 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.818056E+09 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123111E+10 | 2187.86 | 02-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.106381E+10 | 2187.86 | 27-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.124086E+10 | 1524.28 | 16-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.107186E+10 | 1524.28 | 21-APR-15:00 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.113869E+10 | 1243.00 | 08-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.112947E+10 | 1243.00 | 09-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.105612E+10 | 1141.99 | 11-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.118913E+10 | 1243.00 | 21-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.109567E+10 | 1524.28 | 18-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.116572E+10 | 1524.28 | 04-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.121602E+10 | 2187.86 | 06-NOV-16:40 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.120164E+10 | 2187.86 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.138001E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.105612E+10 | 1141.99 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.124086E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.810665E+09 | 1409.91 | 02-JAN-16:49 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.694329E+09 | 1409.91 | 27-FEB-16:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.803009E+09 | 982.28 | 16-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.691150E+09 | 982.28 | 05-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.731684E+09 | 982.28 | 09-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.723000E+09 | 801.02 | 08-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.676072E+09 | 801.02 | 11-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.764629E+09 | 982.28 | 21-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.709773E+09 | 1228.64 | 18-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.764378E+09 | 1228.64 | 05-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.791968E+09 | 1409.91 | 06-NOV-16:40 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.794683E+09 | 1409.91 | 01-DEC-16:19 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.895534E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.676072E+09 | 801.02 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.810665E+09 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.130053E+10 | 2187.81 | 02-JAN-16:30 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.109672E+10 | 2187.81 | 27-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.125590E+10 | 1524.25 | 01-MAR-16:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.107115E+10 | 1524.25 | 21-APR-15:00 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.112944E+10 | 1242.97 | 08-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.111769E+10 | 1141.96 | 08-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.104576E+10 | 1141.96 | 11-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.118181E+10 | 1242.97 | 21-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.110201E+10 | 1524.25 | 05-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.122099E+10 | 1906.53 | 23-OCT-15:00 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.126940E+10 | 2187.81 | 06-NOV-16:19 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.128070E+10 | 2187.81 | 01-DEC-16:19 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.140721E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.104576E+10 | 1141.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.130053E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.817978E+09 | 1409.91 | 02-JAN-16:30 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.699573E+09 | 1409.91 | 27-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.803023E+09 | 982.28 | 01-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.690586E+09 | 982.28 | 21-APR-15:50 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.732732E+09 | 735.93 | 08-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.725805E+09 | 735.93 | 09-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.678729E+09 | 735.93 | 28-JUL-15:39 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.764599E+09 | 735.93 | 21-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.705971E+09 | 982.28 | 18-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.770316E+09 | 1228.64 | 20-OCT-15:50 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.807719E+09 | 1409.91 | 06-NOV-16:19 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.801272E+09 | 1409.91 | 01-DEC-16:10 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.899830E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.678729E+09 | 735.93 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.817978E+09 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123111E+10 | 2187.86 | 02-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.106381E+10 | 2187.86 | 27-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.124081E+10 | 1524.28 | 16-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.107180E+10 | 1524.28 | 21-APR-15:00 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.113861E+10 | 1243.00 | 08-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.112941E+10 | 1243.00 | 09-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.105600E+10 | 1141.99 | 11-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.118901E+10 | 1243.00 | 21-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.109555E+10 | 1524.28 | 18-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.116570E+10 | 1524.28 | 04-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.121602E+10 | 2187.86 | 06-NOV-16:40 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.120158E+10 | 2187.86 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.137994E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.105600E+10 | 1141.99 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.124081E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.810665E+09 | 1409.91 | 02-JAN-16:49 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.694329E+09 | 1409.91 | 27-FEB-16:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.802931E+09 | 982.28 | 16-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.691137E+09 | 982.28 | 05-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.731579E+09 | 982.28 | 09-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.722916E+09 | 801.02 | 08-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.676063E+09 | 801.02 | 11-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.764604E+09 | 982.28 | 21-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.709754E+09 | 1228.64 | 18-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.764339E+09 | 1228.64 | 05-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.791929E+09 | 1409.91 | 06-NOV-16:40 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.794640E+09 | 1409.91 | 01-DEC-16:19 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.895489E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.676063E+09 | 801.02 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.810665E+09 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.522764E+10 | 5470.56 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.474186E+10 | 5470.56 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.563465E+10 | 5470.56 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.503289E+10 | 5470.56 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.543115E+10 | 5470.56 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.540489E+10 | 5470.56 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.505915E+10 | 5470.56 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.563465E+10 | 5470.56 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.503289E+10 | 5470.56 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.522764E+10 | 5470.56 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.516637E+10 | 5470.56 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.505915E+10 | 5470.56 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.626529E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.474186E+10 | 5470.56 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.563465E+10 | 5470.56 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.180249E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.163527E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.194806E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.173504E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.187528E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.186803E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.174228E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.194803E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.173504E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.180252E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.178272E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.174231E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.216171E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.163527E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.194806E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.130776E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 120485.02 | 0.130219E+09 |
February | 0.136985E+10 | 0.110211E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20387.75 | 0.153237E+09 |
March | 0.163685E+10 | 0.125910E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.18 | 0.162165E+09 |
April | 0.145243E+10 | 0.107266E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 140402.08 | 94368871.81 |
May | 0.157338E+10 | 0.113050E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.13 | 0.110983E+09 |
June | 0.156900E+10 | 0.111866E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12683.58 | 59478107.56 |
July | 0.145680E+10 | 0.104621E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 867299.43 | 42141734.03 |
August | 0.163685E+10 | 0.118336E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 903194.47 | 51680421.88 |
September | 0.145243E+10 | 0.110444E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1439254.58 | 51961556.00 |
October | 0.150991E+10 | 0.122938E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5113020.38 | 83867513.47 |
November | 0.149516E+10 | 0.127530E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 278118.19 | 0.123641E+09 |
December | 0.145680E+10 | 0.128781E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86783.27 | 0.135718E+09 |
Annual Sum or Average | 0.181194E+11 | 0.141173E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8981688.05 | 0.119946E+10 |
Minimum of Months | 0.136985E+10 | 0.104621E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.13 | 42141734.03 |
Maximum of Months | 0.163685E+10 | 0.130776E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5113020.38 | 0.162165E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.820470E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85699.42 | 87323310.93 |
February | 0.882782E+09 | 0.701256E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13591.36 | 0.101329E+09 |
March | 0.105485E+10 | 0.804788E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.05 | 0.106830E+09 |
April | 0.936002E+09 | 0.691517E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62510.49 | 62313183.86 |
May | 0.101394E+10 | 0.733795E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.87 | 74650211.94 |
June | 0.101113E+10 | 0.726800E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8452.25 | 39209873.77 |
July | 0.938820E+09 | 0.679512E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 565993.77 | 27915033.18 |
August | 0.105485E+10 | 0.765224E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 592953.88 | 33454889.65 |
September | 0.936002E+09 | 0.707163E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 959617.66 | 35114901.72 |
October | 0.973041E+09 | 0.773207E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3217103.43 | 55541050.87 |
November | 0.963541E+09 | 0.808887E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 110065.71 | 81330639.05 |
December | 0.938820E+09 | 0.803447E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61563.78 | 88413637.24 |
Annual Sum or Average | 0.116768E+11 | 0.901606E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5677590.66 | 0.793426E+09 |
Minimum of Months | 0.882782E+09 | 0.679512E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.87 | 27915033.18 |
Maximum of Months | 0.105485E+10 | 0.820470E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3217103.43 | 0.106830E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.123174E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97154.80 | 0.135813E+09 |
February | 0.136988E+10 | 0.106461E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20376.79 | 0.157575E+09 |
March | 0.163688E+10 | 0.124243E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.64 | 0.163405E+09 |
April | 0.145246E+10 | 0.107345E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93705.58 | 96831972.67 |
May | 0.157341E+10 | 0.114031E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.58 | 0.109453E+09 |
June | 0.156904E+10 | 0.113075E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12683.97 | 57955121.07 |
July | 0.145684E+10 | 0.105688E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 859675.03 | 42030111.93 |
August | 0.163688E+10 | 0.119052E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 886526.18 | 53512737.46 |
September | 0.145246E+10 | 0.109701E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1421137.10 | 56198419.93 |
October | 0.150994E+10 | 0.116710E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4424720.83 | 89763369.35 |
November | 0.149520E+10 | 0.121668E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40666.45 | 0.130280E+09 |
December | 0.145684E+10 | 0.120219E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63772.86 | 0.142780E+09 |
Annual Sum or Average | 0.181198E+11 | 0.138137E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7920481.81 | 0.123560E+10 |
Minimum of Months | 0.136988E+10 | 0.105688E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.58 | 42030111.93 |
Maximum of Months | 0.163688E+10 | 0.124243E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4424720.83 | 0.163405E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.812829E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71558.79 | 92734239.14 |
February | 0.882782E+09 | 0.695793E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13592.27 | 0.114116E+09 |
March | 0.105485E+10 | 0.804712E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.91 | 0.120698E+09 |
April | 0.936002E+09 | 0.692280E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62548.76 | 73713725.67 |
May | 0.101394E+10 | 0.732827E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.36 | 81867571.29 |
June | 0.101113E+10 | 0.724036E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8454.49 | 44766844.21 |
July | 0.938820E+09 | 0.676944E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 567317.57 | 33762790.71 |
August | 0.105485E+10 | 0.766027E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 590776.51 | 42424581.74 |
September | 0.936002E+09 | 0.711138E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 957073.70 | 39821877.02 |
October | 0.973041E+09 | 0.767206E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3175406.40 | 64413976.02 |
November | 0.963541E+09 | 0.793902E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61348.54 | 93942699.44 |
December | 0.938820E+09 | 0.797449E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55045.70 | 0.104827E+09 |
Annual Sum or Average | 0.116768E+11 | 0.897514E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5563165.00 | 0.907090E+09 |
Minimum of Months | 0.882782E+09 | 0.676944E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.36 | 33762790.71 |
Maximum of Months | 0.105485E+10 | 0.812829E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3175406.40 | 0.120698E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.130067E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 584558.09 | 0.264763E+09 |
February | 0.136985E+10 | 0.109681E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45647.16 | 0.311546E+09 |
March | 0.163685E+10 | 0.125590E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79220.42 | 0.337620E+09 |
April | 0.145243E+10 | 0.107115E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 875920.79 | 0.196686E+09 |
May | 0.157338E+10 | 0.112950E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.242441E+09 |
June | 0.156900E+10 | 0.111779E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23727.76 | 0.130845E+09 |
July | 0.145680E+10 | 0.104576E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2108209.29 | 91785089.30 |
August | 0.163685E+10 | 0.118181E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2296252.45 | 0.113412E+09 |
September | 0.145243E+10 | 0.110203E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3320675.96 | 0.109582E+09 |
October | 0.150991E+10 | 0.122106E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12734581.17 | 0.171799E+09 |
November | 0.149516E+10 | 0.126957E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1510124.29 | 0.251748E+09 |
December | 0.145680E+10 | 0.128094E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 790822.50 | 0.267436E+09 |
Annual Sum or Average | 0.181194E+11 | 0.140730E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24369739.88 | 0.248966E+10 |
Minimum of Months | 0.136985E+10 | 0.104576E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91785089.30 |
Maximum of Months | 0.163685E+10 | 0.130067E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12734581.17 | 0.337620E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.818056E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 286666.17 | 0.184547E+09 |
February | 0.649041E+09 | 0.699624E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28677.32 | 0.215466E+09 |
March | 0.773965E+09 | 0.803179E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233226E+09 |
April | 0.688021E+09 | 0.690668E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 138360.54 | 0.140606E+09 |
May | 0.744847E+09 | 0.732768E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169436E+09 |
June | 0.742030E+09 | 0.725843E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15810.25 | 90162275.85 |
July | 0.690839E+09 | 0.678759E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1253837.98 | 66925577.69 |
August | 0.773965E+09 | 0.764618E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1297490.26 | 82103205.69 |
September | 0.688021E+09 | 0.706066E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2213510.16 | 78001739.18 |
October | 0.715730E+09 | 0.770427E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7499210.05 | 0.120643E+09 |
November | 0.708685E+09 | 0.807765E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 405985.93 | 0.174995E+09 |
December | 0.690839E+09 | 0.801338E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 208766.77 | 0.186361E+09 |
Annual Sum or Average | 0.858171E+10 | 0.899911E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13348315.43 | 0.174247E+10 |
Minimum of Months | 0.649041E+09 | 0.678759E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66925577.69 |
Maximum of Months | 0.773965E+09 | 0.818056E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7499210.05 | 0.233226E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.123111E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 181220.15 | 0.309163E+09 |
February | 0.136988E+10 | 0.106381E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42991.91 | 0.353287E+09 |
March | 0.163688E+10 | 0.124086E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364795E+09 |
April | 0.145246E+10 | 0.107186E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 207656.30 | 0.216754E+09 |
May | 0.157341E+10 | 0.113869E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247755E+09 |
June | 0.156904E+10 | 0.112947E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23728.16 | 0.129952E+09 |
July | 0.145684E+10 | 0.105612E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2027548.29 | 94434676.31 |
August | 0.163688E+10 | 0.118913E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1944136.93 | 0.123738E+09 |
September | 0.145246E+10 | 0.109567E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3231722.68 | 0.129831E+09 |
October | 0.150994E+10 | 0.116572E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9991069.42 | 0.204214E+09 |
November | 0.149520E+10 | 0.121602E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83619.47 | 0.294659E+09 |
December | 0.145684E+10 | 0.120164E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 120250.85 | 0.320039E+09 |
Annual Sum or Average | 0.181198E+11 | 0.138001E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17853944.16 | 0.278862E+10 |
Minimum of Months | 0.136988E+10 | 0.105612E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94434676.31 |
Maximum of Months | 0.163688E+10 | 0.124086E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9991069.42 | 0.364795E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.810665E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 248613.06 | 0.189071E+09 |
February | 0.882782E+09 | 0.694329E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37786.65 | 0.224473E+09 |
March | 0.105485E+10 | 0.803009E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26011.91 | 0.239798E+09 |
April | 0.936002E+09 | 0.691150E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 429532.63 | 0.150209E+09 |
May | 0.101394E+10 | 0.731684E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179158E+09 |
June | 0.101113E+10 | 0.723000E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15817.66 | 96034828.88 |
July | 0.938820E+09 | 0.676072E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1429606.48 | 72803766.39 |
August | 0.105485E+10 | 0.764629E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1453310.72 | 89779705.66 |
September | 0.936002E+09 | 0.709773E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2205493.57 | 85925261.40 |
October | 0.973041E+09 | 0.764378E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7852916.53 | 0.129471E+09 |
November | 0.963541E+09 | 0.791968E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 698349.18 | 0.183123E+09 |
December | 0.938820E+09 | 0.794683E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 331082.90 | 0.195060E+09 |
Annual Sum or Average | 0.116768E+11 | 0.895534E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14728521.30 | 0.183491E+10 |
Minimum of Months | 0.882782E+09 | 0.676072E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72803766.39 |
Maximum of Months | 0.105485E+10 | 0.810665E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7852916.53 | 0.239798E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.130053E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1094295.40 | 0.288262E+09 |
February | 0.136985E+10 | 0.109672E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76107.06 | 0.341164E+09 |
March | 0.163685E+10 | 0.125590E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 147818.37 | 0.383765E+09 |
April | 0.145243E+10 | 0.107115E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1238869.23 | 0.232482E+09 |
May | 0.157338E+10 | 0.112944E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286325E+09 |
June | 0.156900E+10 | 0.111769E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22833.39 | 0.160081E+09 |
July | 0.145680E+10 | 0.104576E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2441068.09 | 0.115592E+09 |
August | 0.163685E+10 | 0.118181E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2623274.08 | 0.139845E+09 |
September | 0.145243E+10 | 0.110201E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4046845.84 | 0.130590E+09 |
October | 0.150991E+10 | 0.122099E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15593530.02 | 0.197438E+09 |
November | 0.149516E+10 | 0.126940E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2417683.49 | 0.280840E+09 |
December | 0.145680E+10 | 0.128070E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2426402.66 | 0.293111E+09 |
Annual Sum or Average | 0.181194E+11 | 0.140721E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32128727.62 | 0.284949E+10 |
Minimum of Months | 0.136985E+10 | 0.104576E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115592E+09 |
Maximum of Months | 0.163685E+10 | 0.130053E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15593530.02 | 0.383765E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.817978E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 428119.67 | 0.204024E+09 |
February | 0.882782E+09 | 0.699573E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31615.05 | 0.240410E+09 |
March | 0.105485E+10 | 0.803023E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268972E+09 |
April | 0.936002E+09 | 0.690586E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 161927.85 | 0.169454E+09 |
May | 0.101394E+10 | 0.732732E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202799E+09 |
June | 0.101113E+10 | 0.725805E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15217.67 | 0.111221E+09 |
July | 0.938820E+09 | 0.678729E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1469327.29 | 84979682.37 |
August | 0.105485E+10 | 0.764599E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1499010.75 | 0.102635E+09 |
September | 0.936002E+09 | 0.705971E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2697155.25 | 94635411.42 |
October | 0.973041E+09 | 0.770316E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8906183.52 | 0.141197E+09 |
November | 0.963541E+09 | 0.807719E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 656508.64 | 0.199088E+09 |
December | 0.938820E+09 | 0.801272E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 439638.34 | 0.207582E+09 |
Annual Sum or Average | 0.116768E+11 | 0.899830E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16304704.03 | 0.202700E+10 |
Minimum of Months | 0.882782E+09 | 0.678729E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84979682.37 |
Maximum of Months | 0.105485E+10 | 0.817978E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8906183.52 | 0.268972E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.123111E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 246882.87 | 0.348848E+09 |
February | 0.136988E+10 | 0.106381E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47408.31 | 0.399007E+09 |
March | 0.163688E+10 | 0.124081E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420258E+09 |
April | 0.145246E+10 | 0.107180E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 291073.79 | 0.258091E+09 |
May | 0.157341E+10 | 0.113861E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292471E+09 |
June | 0.156904E+10 | 0.112941E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22833.88 | 0.158272E+09 |
July | 0.145684E+10 | 0.105600E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2407420.73 | 0.117946E+09 |
August | 0.163688E+10 | 0.118901E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2250667.75 | 0.152157E+09 |
September | 0.145246E+10 | 0.109555E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3970667.87 | 0.156673E+09 |
October | 0.150994E+10 | 0.116570E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12339788.80 | 0.241110E+09 |
November | 0.149520E+10 | 0.121602E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98228.98 | 0.341112E+09 |
December | 0.145684E+10 | 0.120158E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 163513.35 | 0.365706E+09 |
Annual Sum or Average | 0.181198E+11 | 0.137994E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21838486.33 | 0.325165E+10 |
Minimum of Months | 0.136988E+10 | 0.105600E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117946E+09 |
Maximum of Months | 0.163688E+10 | 0.124081E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12339788.80 | 0.420258E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.810665E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 398283.41 | 0.213620E+09 |
February | 0.882782E+09 | 0.694329E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58535.31 | 0.254875E+09 |
March | 0.105485E+10 | 0.802931E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49634.09 | 0.278506E+09 |
April | 0.936002E+09 | 0.691137E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 591816.92 | 0.180660E+09 |
May | 0.101394E+10 | 0.731579E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214718E+09 |
June | 0.101113E+10 | 0.722916E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15221.17 | 0.117528E+09 |
July | 0.938820E+09 | 0.676063E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1672118.14 | 90533767.88 |
August | 0.105485E+10 | 0.764604E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1729698.80 | 0.110498E+09 |
September | 0.936002E+09 | 0.709754E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2694594.48 | 0.103919E+09 |
October | 0.973041E+09 | 0.764339E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9671938.89 | 0.152454E+09 |
November | 0.963541E+09 | 0.791929E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1031667.51 | 0.211101E+09 |
December | 0.938820E+09 | 0.794640E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 753618.98 | 0.221500E+09 |
Annual Sum or Average | 0.116768E+11 | 0.895489E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 18667127.70 | 0.214991E+10 |
Minimum of Months | 0.882782E+09 | 0.676063E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90533767.88 |
Maximum of Months | 0.105485E+10 | 0.810665E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9671938.89 | 0.278506E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.522764E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.474186E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.563465E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.503289E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.543115E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.540489E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.505915E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.563465E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.503289E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.522764E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.516637E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.505915E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.626529E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.474186E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.563465E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121669.27 | 0.287451E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21792.82 | 0.333803E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349533E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156609.76 | 0.205226E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237205E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2819.57 | 0.126949E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1144731.46 | 92731846.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1081177.13 | 0.116703E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2518300.79 | 0.114773E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9064433.72 | 0.185638E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273172.48 | 0.272144E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59307.22 | 0.298990E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14444014.23 | 0.262115E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92731846.06 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9064433.72 | 0.349533E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 375983.70 | 0.484952E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47009.52 | 0.565921E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597260E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 530074.63 | 0.347625E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412552E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5095.10 | 0.219339E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2265313.04 | 0.158339E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2123786.77 | 0.201847E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4560777.02 | 0.196550E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17445148.57 | 0.314480E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1094182.91 | 0.462218E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206729.35 | 0.499650E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28654100.61 | 0.446073E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158339E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17445148.57 | 0.597260E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 679668.66 | 0.473265E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11665.10 | 0.563533E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624471E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162668.50 | 0.394964E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469248E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267380E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1021169.32 | 0.205748E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 760214.65 | 0.240181E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4636831.04 | 0.229679E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17198548.14 | 0.329255E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1272295.69 | 0.465605E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279687.90 | 0.485783E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26022749.00 | 0.474911E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205748E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17198548.14 | 0.624471E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 19402.09 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 19402.09 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 19402.09 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 19402.09 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 19402.09 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 19402.09 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 19402.09 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 19402.09 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 19402.09 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 19402.09 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 19402.09 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 19402.09 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 19402.09 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 19402.09 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2187.81 | 02-JAN-16:30 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 14-JAN-11:00 | 334.76 | 02-JAN-02:53 |
February | 2010.79 | 01-FEB-10:09 | 2187.81 | 27-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.42 | 01-FEB-12:00 | 294.10 | 12-FEB-19:00 |
March | 2010.79 | 01-MAR-10:09 | 1524.25 | 01-MAR-16:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 11-MAR-14:00 | 312.91 | 28-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 1524.25 | 21-APR-15:00 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.13 | 30-APR-10:53 | 192.87 | 17-APR-03:00 |
May | 2010.79 | 01-MAY-09:09 | 1242.97 | 08-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 03-MAY-12:00 | 171.34 | 27-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 1242.97 | 09-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.62 | 29-JUN-11:00 | 125.05 | 07-JUN-01:00 |
July | 2010.79 | 03-JUL-09:09 | 1141.96 | 11-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.84 | 31-JUL-13:00 | 106.19 | 16-JUL-18:00 |
August | 2010.79 | 01-AUG-09:09 | 1242.97 | 21-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.76 | 17-AUG-14:00 | 90.23 | 21-AUG-24:00 |
September | 2010.79 | 01-SEP-09:09 | 1625.25 | 18-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.72 | 29-SEP-14:00 | 101.00 | 24-SEP-15:10 |
October | 2010.79 | 02-OCT-09:09 | 1906.53 | 20-OCT-15:00 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.50 | 15-OCT-08:52 | 207.19 | 11-OCT-02:00 |
November | 2010.79 | 01-NOV-09:09 | 2187.81 | 06-NOV-16:19 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.55 | 19-NOV-12:51 | 274.78 | 23-NOV-04:00 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 01-DEC-16:19 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.66 | 05-DEC-10:00 | 250.68 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 90.23 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 107.50 | 334.76 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-16:30 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.81 | 14-JAN-15:00 | 223.27 | 02-JAN-02:53 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 27-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.28 | 01-FEB-12:00 | 187.96 | 12-FEB-19:00 |
March | 1295.83 | 01-MAR-10:09 | 982.28 | 01-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11-MAR-14:00 | 200.63 | 28-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 982.28 | 21-APR-15:39 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.40 | 26-APR-13:00 | 125.26 | 17-APR-03:00 |
May | 1295.83 | 01-MAY-09:09 | 735.93 | 08-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 03-MAY-12:00 | 113.94 | 27-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 735.93 | 08-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.41 | 29-JUN-11:00 | 80.99 | 07-JUN-01:00 |
July | 1295.83 | 03-JUL-09:09 | 735.93 | 28-JUL-15:20 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.56 | 31-JUL-13:00 | 65.94 | 16-JUL-18:00 |
August | 1295.83 | 01-AUG-09:09 | 735.93 | 21-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.51 | 17-AUG-14:00 | 56.84 | 21-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 982.28 | 18-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.82 | 29-SEP-14:00 | 82.21 | 03-SEP-06:40 |
October | 1295.83 | 02-OCT-09:09 | 1228.64 | 20-OCT-15:50 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.98 | 15-OCT-12:40 | 136.65 | 30-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 06-NOV-16:19 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.24 | 19-NOV-12:51 | 183.43 | 23-NOV-07:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-16:10 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.78 | 05-DEC-10:00 | 162.62 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 735.93 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.84 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 67.98 | 223.27 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2187.86 | 02-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.88 | 14-JAN-11:00 | 303.62 | 02-JAN-02:53 |
February | 2010.83 | 01-FEB-10:09 | 2187.86 | 27-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.42 | 01-FEB-12:00 | 283.68 | 25-FEB-03:00 |
March | 2010.83 | 01-MAR-10:09 | 1524.28 | 16-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 11-MAR-14:00 | 307.08 | 28-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 1524.28 | 21-APR-15:00 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.58 | 26-APR-13:00 | 189.71 | 17-APR-03:00 |
May | 2010.83 | 01-MAY-09:09 | 1243.00 | 08-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 03-MAY-12:00 | 167.67 | 07-MAY-18:00 |
June | 2010.83 | 01-JUN-09:09 | 1243.00 | 08-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.62 | 29-JUN-11:00 | 122.94 | 07-JUN-01:00 |
July | 2010.83 | 03-JUL-09:09 | 1141.99 | 11-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.84 | 31-JUL-13:00 | 100.46 | 09-JUL-17:00 |
August | 2010.83 | 01-AUG-09:09 | 1243.00 | 21-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.76 | 17-AUG-14:00 | 89.97 | 21-AUG-24:00 |
September | 2010.83 | 01-SEP-09:09 | 1524.28 | 18-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.61 | 29-SEP-14:00 | 124.39 | 03-SEP-14:00 |
October | 2010.83 | 02-OCT-09:09 | 1524.28 | 04-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.69 | 15-OCT-12:55 | 212.37 | 11-OCT-02:00 |
November | 2010.83 | 01-NOV-09:09 | 2187.86 | 06-NOV-16:40 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.09 | 18-NOV-13:00 | 278.76 | 23-NOV-04:00 |
December | 2010.83 | 01-DEC-10:09 | 2187.86 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.66 | 05-DEC-10:00 | 253.66 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1141.99 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 89.97 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 92.69 | 307.08 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-16:49 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.55 | 14-JAN-11:00 | 220.34 | 02-JAN-02:53 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 27-FEB-16:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.28 | 01-FEB-12:00 | 222.77 | 12-FEB-19:00 |
March | 1295.83 | 01-MAR-10:09 | 1047.37 | 16-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11-MAR-14:00 | 231.02 | 28-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 982.28 | 05-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.40 | 26-APR-13:00 | 164.55 | 16-APR-17:50 |
May | 1295.83 | 01-MAY-09:09 | 982.28 | 09-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 03-MAY-12:00 | 143.84 | 07-MAY-14:50 |
June | 1295.83 | 01-JUN-09:09 | 801.02 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.41 | 29-JUN-11:00 | 108.26 | 04-JUN-16:50 |
July | 1295.83 | 03-JUL-09:09 | 801.02 | 11-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.56 | 31-JUL-13:00 | 107.21 | 09-JUL-17:00 |
August | 1295.83 | 01-AUG-09:09 | 982.28 | 21-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.51 | 17-AUG-14:00 | 81.07 | 27-AUG-18:10 |
September | 1295.83 | 01-SEP-09:09 | 1228.64 | 18-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.81 | 29-SEP-14:00 | 105.76 | 03-SEP-16:40 |
October | 1295.83 | 02-OCT-09:09 | 1228.64 | 05-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.12 | 15-OCT-09:00 | 161.05 | 11-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 06-NOV-16:40 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.13 | 19-NOV-12:26 | 212.43 | 23-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-16:19 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.78 | 05-DEC-10:00 | 188.86 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 801.02 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.07 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 69.12 | 231.02 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2187.81 | 02-JAN-16:30 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.13 | 15-JAN-10:00 | 579.85 | 02-JAN-02:53 |
February | 2010.79 | 01-FEB-10:09 | 2187.81 | 27-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.24 | 01-FEB-12:00 | 600.75 | 25-FEB-03:00 |
March | 2010.79 | 01-MAR-10:09 | 1524.25 | 01-MAR-16:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 11-MAR-14:00 | 650.47 | 28-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 1524.25 | 21-APR-15:00 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.70 | 30-APR-11:10 | 402.72 | 21-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 1242.97 | 08-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 379.06 | 20-MAY-17:55 |
June | 2010.79 | 01-JUN-09:09 | 1141.96 | 08-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.56 | 29-JUN-11:00 | 270.47 | 06-JUN-21:20 |
July | 2010.79 | 03-JUL-09:09 | 1141.96 | 11-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.55 | 23-JUL-10:55 | 216.81 | 09-JUL-17:00 |
August | 2010.79 | 01-AUG-09:09 | 1242.97 | 21-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.12 | 06-AUG-12:50 | 192.76 | 21-AUG-23:53 |
September | 2010.79 | 01-SEP-09:09 | 1524.25 | 05-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.82 | 29-SEP-14:00 | 211.83 | 02-SEP-02:00 |
October | 2010.79 | 02-OCT-09:09 | 1906.53 | 23-OCT-15:00 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 282.18 | 15-OCT-09:00 | 417.06 | 30-OCT-03:00 |
November | 2010.79 | 01-NOV-09:09 | 2187.81 | 06-NOV-16:19 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.45 | 19-NOV-12:51 | 552.66 | 23-NOV-04:00 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 01-DEC-16:19 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 58.29 | 25-DEC-11:52 | 524.09 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.76 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 282.18 | 650.47 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1409.91 | 02-JAN-16:30 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.46 | 15-JAN-14:23 | 402.62 | 02-JAN-02:53 |
February | 1239.33 | 01-FEB-08:09 | 1409.91 | 27-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.49 | 01-FEB-12:00 | 394.32 | 25-FEB-03:00 |
March | 1239.33 | 01-MAR-08:09 | 982.28 | 01-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 426.66 | 28-MAR-22:00 |
April | 1239.33 | 03-APR-07:10 | 982.28 | 21-APR-15:50 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.45 | 26-APR-13:00 | 268.21 | 21-APR-22:00 |
May | 1239.33 | 01-MAY-07:10 | 735.93 | 08-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 261.77 | 29-MAY-12:53 |
June | 1239.33 | 01-JUN-07:10 | 735.93 | 09-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.04 | 29-JUN-11:00 | 185.84 | 04-JUN-14:00 |
July | 1239.33 | 03-JUL-07:10 | 735.93 | 28-JUL-15:39 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.09 | 31-JUL-13:00 | 156.09 | 09-JUL-11:55 |
August | 1239.33 | 01-AUG-07:10 | 735.93 | 21-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.41 | 17-AUG-14:00 | 129.07 | 21-AUG-23:53 |
September | 1239.33 | 01-SEP-07:10 | 982.28 | 18-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.88 | 29-SEP-14:00 | 189.21 | 03-SEP-07:00 |
October | 1239.33 | 02-OCT-07:10 | 1228.64 | 20-OCT-15:50 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.80 | 15-OCT-12:56 | 288.46 | 30-OCT-03:00 |
November | 1239.33 | 01-NOV-07:10 | 1409.91 | 06-NOV-16:19 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.57 | 19-NOV-12:51 | 379.90 | 23-NOV-07:00 |
December | 1239.33 | 01-DEC-08:09 | 1409.91 | 01-DEC-16:10 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.08 | 17-DEC-13:00 | 352.05 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 735.93 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.07 | |||||
Maximum of Months | 1239.33 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 169.80 | 426.66 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2187.86 | 02-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.82 | 14-JAN-11:00 | 625.58 | 02-JAN-02:53 |
February | 2010.83 | 01-FEB-10:09 | 2187.86 | 27-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.24 | 01-FEB-12:00 | 631.78 | 20-FEB-14:50 |
March | 2010.83 | 01-MAR-10:09 | 1524.28 | 16-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 663.32 | 28-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 1524.28 | 21-APR-15:00 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.68 | 26-APR-13:00 | 420.92 | 16-APR-12:00 |
May | 2010.83 | 01-MAY-09:09 | 1243.00 | 08-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 383.59 | 07-MAY-13:00 |
June | 2010.83 | 01-JUN-09:09 | 1243.00 | 09-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.56 | 29-JUN-11:00 | 270.01 | 06-JUN-21:20 |
July | 2010.83 | 03-JUL-09:09 | 1141.99 | 11-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.10 | 23-JUL-10:55 | 219.70 | 09-JUL-17:00 |
August | 2010.83 | 01-AUG-09:09 | 1243.00 | 21-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.11 | 17-AUG-14:00 | 198.38 | 21-AUG-23:53 |
September | 2010.83 | 01-SEP-09:09 | 1524.28 | 18-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.77 | 29-SEP-14:00 | 304.58 | 04-SEP-14:00 |
October | 2010.83 | 02-OCT-09:09 | 1524.28 | 04-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.91 | 15-OCT-13:00 | 476.36 | 30-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 2187.86 | 06-NOV-16:40 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.07 | 18-NOV-13:00 | 605.07 | 23-NOV-04:00 |
December | 2010.83 | 01-DEC-10:09 | 2187.86 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.56 | 05-DEC-10:00 | 562.21 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1141.99 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.38 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 212.91 | 663.32 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-16:49 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.39 | 14-JAN-12:30 | 407.28 | 02-JAN-02:53 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 27-FEB-16:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.90 | 01-FEB-12:00 | 409.97 | 25-FEB-03:00 |
March | 1295.83 | 01-MAR-10:09 | 982.28 | 16-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.53 | 11-MAR-12:20 | 447.80 | 28-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 982.28 | 05-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.75 | 30-APR-11:10 | 345.99 | 16-APR-17:40 |
May | 1295.83 | 01-MAY-09:09 | 982.28 | 09-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 334.46 | 29-MAY-16:10 |
June | 1295.83 | 01-JUN-09:09 | 801.02 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.04 | 29-JUN-11:00 | 242.37 | 04-JUN-17:20 |
July | 1295.83 | 03-JUL-09:09 | 801.02 | 11-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.41 | 23-JUL-10:53 | 240.71 | 09-JUL-17:00 |
August | 1295.83 | 01-AUG-09:09 | 982.28 | 21-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.08 | 06-AUG-12:42 | 168.53 | 27-AUG-17:40 |
September | 1295.83 | 01-SEP-09:09 | 1228.64 | 18-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.88 | 29-SEP-14:00 | 244.48 | 03-SEP-16:30 |
October | 1295.83 | 02-OCT-09:09 | 1228.64 | 05-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.23 | 15-OCT-09:00 | 304.38 | 30-OCT-03:00 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 06-NOV-16:40 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.10 | 19-NOV-12:00 | 391.66 | 23-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-16:19 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.39 | 25-DEC-11:52 | 365.61 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 801.02 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.53 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 194.23 | 447.80 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2187.81 | 02-JAN-16:30 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 81.17 | 15-JAN-10:00 | 641.63 | 27-JAN-05:00 |
February | 2010.79 | 01-FEB-10:09 | 2187.81 | 27-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.89 | 01-FEB-12:00 | 673.50 | 25-FEB-03:00 |
March | 2010.79 | 01-MAR-10:09 | 1524.25 | 01-MAR-16:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.03 | 11-MAR-13:00 | 782.06 | 28-MAR-21:03 |
April | 2010.79 | 03-APR-09:09 | 1524.25 | 21-APR-15:00 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.11 | 30-APR-11:10 | 474.45 | 21-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 1242.97 | 08-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 462.81 | 20-MAY-17:55 |
June | 2010.79 | 01-JUN-09:09 | 1141.96 | 08-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.24 | 29-JUN-11:00 | 328.69 | 06-JUN-21:10 |
July | 2010.79 | 03-JUL-09:09 | 1141.96 | 11-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.52 | 23-JUL-11:10 | 287.44 | 09-JUL-17:00 |
August | 2010.79 | 01-AUG-09:09 | 1242.97 | 21-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.51 | 06-AUG-12:50 | 229.75 | 21-AUG-23:53 |
September | 2010.79 | 01-SEP-09:09 | 1524.25 | 05-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.29 | 29-SEP-14:00 | 256.03 | 04-SEP-18:00 |
October | 2010.79 | 02-OCT-09:09 | 1906.53 | 23-OCT-15:00 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 359.17 | 15-OCT-08:52 | 473.43 | 11-OCT-02:00 |
November | 2010.79 | 01-NOV-09:09 | 2187.81 | 06-NOV-16:19 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.09 | 19-NOV-12:51 | 596.15 | 23-NOV-04:00 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 01-DEC-16:19 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.96 | 25-DEC-12:00 | 597.48 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.75 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 359.17 | 782.06 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-16:30 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.20 | 15-JAN-10:00 | 432.89 | 06-JAN-23:00 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 27-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.10 | 01-FEB-12:00 | 443.24 | 25-FEB-03:00 |
March | 1295.83 | 01-MAR-10:09 | 982.28 | 01-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 520.71 | 28-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 982.28 | 21-APR-15:50 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.27 | 26-APR-13:00 | 317.71 | 21-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 735.93 | 08-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 337.19 | 29-MAY-12:53 |
June | 1295.83 | 01-JUN-09:09 | 735.93 | 09-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.49 | 29-JUN-11:00 | 229.71 | 04-JUN-13:48 |
July | 1295.83 | 03-JUL-09:09 | 735.93 | 28-JUL-15:39 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.08 | 31-JUL-13:00 | 194.85 | 04-JUL-14:00 |
August | 1295.83 | 01-AUG-09:09 | 735.93 | 21-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.42 | 17-AUG-14:00 | 160.52 | 27-AUG-18:20 |
September | 1295.83 | 01-SEP-09:09 | 982.28 | 18-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.53 | 29-SEP-14:00 | 210.37 | 03-SEP-07:00 |
October | 1295.83 | 02-OCT-09:09 | 1228.64 | 20-OCT-15:50 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.44 | 15-OCT-13:10 | 326.08 | 11-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 06-NOV-16:19 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.13 | 19-NOV-12:51 | 407.03 | 23-NOV-07:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-16:10 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.23 | 25-DEC-12:00 | 403.73 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 735.93 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.52 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 190.44 | 520.71 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2187.86 | 02-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.29 | 15-JAN-10:00 | 707.58 | 06-JAN-23:00 |
February | 2010.83 | 01-FEB-10:09 | 2187.86 | 27-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.66 | 01-FEB-12:00 | 738.69 | 20-FEB-15:10 |
March | 2010.83 | 01-MAR-10:09 | 1524.28 | 16-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 784.86 | 28-MAR-21:03 |
April | 2010.83 | 03-APR-09:09 | 1524.28 | 21-APR-15:00 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.90 | 26-APR-13:00 | 492.75 | 16-APR-12:00 |
May | 2010.83 | 01-MAY-09:09 | 1243.00 | 08-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 468.76 | 29-MAY-13:00 |
June | 2010.83 | 01-JUN-09:09 | 1243.00 | 09-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.24 | 29-JUN-11:00 | 327.05 | 06-JUN-21:20 |
July | 2010.83 | 03-JUL-09:09 | 1141.99 | 11-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.62 | 31-JUL-13:00 | 289.25 | 09-JUL-17:00 |
August | 2010.83 | 01-AUG-09:09 | 1243.00 | 21-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.13 | 17-AUG-14:00 | 247.34 | 27-AUG-18:20 |
September | 2010.83 | 01-SEP-09:09 | 1524.28 | 18-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.24 | 29-SEP-14:00 | 382.24 | 04-SEP-14:00 |
October | 2010.83 | 02-OCT-09:09 | 1524.28 | 04-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 254.31 | 15-OCT-12:45 | 541.53 | 30-OCT-03:00 |
November | 2010.83 | 01-NOV-09:09 | 2187.86 | 06-NOV-16:40 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.62 | 18-NOV-13:00 | 669.34 | 23-NOV-04:00 |
December | 2010.83 | 01-DEC-10:09 | 2187.86 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.68 | 05-DEC-10:00 | 650.82 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1141.99 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.34 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 254.31 | 784.86 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-16:49 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.41 | 15-JAN-10:00 | 448.15 | 06-JAN-23:00 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 27-FEB-16:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.13 | 01-FEB-12:00 | 466.27 | 25-FEB-03:00 |
March | 1295.83 | 01-MAR-10:09 | 982.28 | 16-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.98 | 11-MAR-12:20 | 525.52 | 28-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 982.28 | 05-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.11 | 30-APR-11:00 | 446.66 | 16-APR-17:50 |
May | 1295.83 | 01-MAY-09:09 | 982.28 | 09-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 430.83 | 29-MAY-16:00 |
June | 1295.83 | 01-JUN-09:09 | 801.02 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.49 | 29-JUN-11:00 | 311.80 | 04-JUN-17:00 |
July | 1295.83 | 03-JUL-09:09 | 801.02 | 11-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.30 | 23-JUL-11:10 | 305.78 | 09-JUL-17:00 |
August | 1295.83 | 01-AUG-09:09 | 982.28 | 21-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.54 | 06-AUG-12:50 | 213.96 | 27-AUG-17:40 |
September | 1295.83 | 01-SEP-09:09 | 1228.64 | 18-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.53 | 29-SEP-14:00 | 303.27 | 03-SEP-16:40 |
October | 1295.83 | 02-OCT-09:09 | 1228.64 | 05-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 236.22 | 15-OCT-08:52 | 354.05 | 11-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 06-NOV-16:40 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.20 | 19-NOV-12:51 | 435.18 | 23-NOV-04:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-16:19 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 66.89 | 25-DEC-12:00 | 424.35 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 801.02 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.96 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 236.22 | 525.52 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 5470.56 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 5470.56 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 5470.56 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 5470.56 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 5470.56 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 5470.56 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 5470.56 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 5470.56 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 5470.56 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 5470.56 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 5470.56 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 5470.56 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 5470.56 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.79 | 14-JAN-15:00 | 748.32 | 02-JAN-02:57 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.43 | 01-FEB-12:00 | 638.48 | 12-FEB-19:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 673.55 | 28-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.11 | 30-APR-11:00 | 415.08 | 17-APR-03:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 373.28 | 27-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.41 | 29-JUN-11:00 | 263.59 | 07-JUN-01:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.75 | 31-JUL-13:00 | 197.62 | 02-JUL-18:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.97 | 17-AUG-14:00 | 190.30 | 21-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.81 | 29-SEP-13:50 | 221.25 | 04-SEP-17:53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.44 | 15-OCT-13:00 | 447.06 | 30-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.49 | 19-NOV-12:51 | 615.78 | 23-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.31 | 05-DEC-10:00 | 547.72 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.30 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.44 | 748.32 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.55 | 15-JAN-10:00 | 1101.71 | 02-JAN-02:53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.54 | 01-FEB-12:00 | 1097.91 | 25-FEB-03:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1158.40 | 28-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.45 | 30-APR-10:53 | 693.16 | 17-APR-03:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 667.12 | 27-MAY-04:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.35 | 29-JUN-11:00 | 459.10 | 07-JUN-01:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.47 | 23-JUL-11:00 | 338.11 | 13-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.68 | 06-AUG-12:53 | 329.45 | 21-AUG-23:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.99 | 29-SEP-13:50 | 376.91 | 02-SEP-02:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.95 | 15-OCT-13:00 | 757.12 | 30-OCT-03:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.73 | 19-NOV-13:00 | 1058.30 | 23-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.76 | 05-DEC-10:00 | 951.66 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.45 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.95 | 1158.40 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.11 | 15-JAN-10:00 | 1015.20 | 27-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.37 | 01-FEB-12:00 | 1091.72 | 25-FEB-03:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1229.54 | 28-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.95 | 30-APR-10:43 | 768.47 | 16-APR-17:52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 766.68 | 20-MAY-17:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 563.33 | 04-JUN-13:53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.38 | 31-JUL-13:00 | 490.29 | 09-JUL-17:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.60 | 17-AUG-14:00 | 391.92 | 27-AUG-17:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.28 | 29-SEP-13:30 | 456.91 | 04-SEP-17:23 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 483.07 | 15-OCT-08:52 | 764.02 | 11-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.38 | 19-NOV-12:54 | 955.89 | 23-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.30 | 04-DEC-10:00 | 966.30 | 23-DEC-04:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391.92 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 483.07 | 1229.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 123828.21 | 02-JAN-07:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 107238.51 | 27-FEB-07:11 | 28723.60 | 51738.90 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 109833.09 | 20-MAR-06:11 | 32314.05 | 58206.26 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 110623.49 | 10-APR-06:11 | 32314.05 | 58206.26 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 107665.68 | 30-MAY-06:11 | 32314.05 | 58206.26 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 103761.09 | 12-JUN-06:11 | 32314.05 | 58206.26 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 102403.79 | 17-JUL-06:11 | 32314.05 | 58206.26 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 100991.80 | 21-AUG-06:11 | 28723.60 | 51738.90 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 101943.91 | 20-SEP-06:11 | 25133.15 | 45271.53 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 111330.52 | 30-OCT-06:11 | 32314.05 | 58206.26 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 107639.43 | 13-NOV-07:05 | 7180.90 | 12934.72 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 108807.10 | 26-DEC-07:05 | 7180.90 | 12934.72 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 100991.80 | 7180.90 | 12934.72 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 123828.21 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 97828.45 | 02-JAN-05:11 | 0.00 | 4298.88 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 91618.88 | 21-FEB-05:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 90280.72 | 27-MAR-04:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 91227.88 | 10-APR-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 89725.40 | 30-MAY-04:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 92165.65 | 12-JUN-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 90260.19 | 13-JUL-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 90731.12 | 01-AUG-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 92842.60 | 11-SEP-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 96396.12 | 10-OCT-04:11 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 93426.16 | 20-NOV-05:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 93513.12 | 18-DEC-05:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 89725.40 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 97828.45 | 0.00 | 4298.88 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 78445.85 | 18-JAN-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 78116.51 | 17-FEB-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 79103.93 | 23-MAR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 79288.72 | 07-APR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 79225.97 | 23-MAY-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 80044.56 | 30-JUN-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 80507.44 | 27-JUL-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 81024.60 | 17-AUG-04:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 80226.70 | 25-SEP-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 81107.84 | 17-OCT-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 78870.04 | 14-NOV-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 78293.51 | 07-DEC-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 78116.51 | 0.00 | 2686.80 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 81107.84 | 8061.19 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 36941.80 | 19-JAN-15:00 | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 37354.92 | 02-FEB-16:20 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 40739.61 | 24-MAR-15:30 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 74223.12 | 27-APR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 73988.14 | 03-MAY-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 75420.66 | 28-JUN-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 76476.33 | 28-JUL-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 76749.72 | 10-AUG-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 75500.01 | 22-SEP-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 76476.97 | 16-OCT-05:04 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 70107.40 | 01-NOV-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 36740.62 | 19-DEC-15:50 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 36740.62 | 6448.95 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 76749.72 | 16014.58 | 17424.44 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6065.99 | 17-JAN-13:40 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.81 |
February | 5191.39 | 01-FEB-12:00 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 6.42 | 0.00 |
March | 6067.57 | 13-MAR-13:40 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.02 |
April | 7299.49 | 26-APR-13:40 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 6.87 | 0.00 |
May | 7071.37 | 04-MAY-13:30 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.30 |
June | 10631.08 | 26-JUN-04:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 11289.40 | 03-JUL-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 11768.45 | 21-AUG-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.60 |
September | 10437.67 | 22-SEP-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12303.03 | 06-OCT-04:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.25 |
November | 5852.37 | 13-NOV-11:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.54 |
December | 6271.76 | 05-DEC-15:00 | 2010.79 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 3.23 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5191.39 | 0.00 | 269.88 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12303.03 | 2010.79 | 1141.96 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 6.87 | 29.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7182.10 | 20-JAN-09:00 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10528.43 | 20-FEB-09:23 | 195.68 | 111.80 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.09 |
March | 9538.47 | 23-MAR-08:40 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18248.01 | 30-APR-09:53 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.09 |
May | 18384.70 | 28-MAY-08:13 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.24 |
June | 18937.72 | 25-JUN-08:42 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.38 |
July | 19185.35 | 02-JUL-08:22 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.76 |
August | 19152.49 | 06-AUG-08:12 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.00 |
September | 18355.17 | 03-SEP-08:43 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.70 |
October | 18339.98 | 09-OCT-08:13 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.16 |
November | 7883.61 | 13-NOV-08:40 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.47 |
December | 7777.37 | 05-DEC-09:00 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7182.10 | 195.68 | 111.80 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19185.35 | 1239.33 | 670.83 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21602.10 | 22-JAN-10:32 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.14 |
February | 22565.33 | 20-FEB-12:02 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.85 |
March | 21653.58 | 19-MAR-12:53 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.04 |
April | 17308.78 | 09-APR-12:32 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.28 |
May | 9153.20 | 04-MAY-12:30 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.13 |
June | 8236.82 | 30-JUN-12:30 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.91 |
July | 15408.01 | 30-JUL-13:13 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.48 |
August | 13913.54 | 13-AUG-12:43 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.18 |
September | 21315.24 | 10-SEP-13:02 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.95 |
October | 22210.73 | 15-OCT-12:32 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 71.58 | 0.00 |
November | 24028.52 | 19-NOV-12:21 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.97 |
December | 23618.13 | 25-DEC-13:11 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8236.82 | 404.87 | 231.31 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24028.52 | 1923.15 | 1040.98 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 71.58 | 154.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9738.61 | 26-JAN-15:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.43 |
February | 22139.79 | 20-FEB-14:42 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.02 |
March | 22106.62 | 19-MAR-15:32 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.31 |
April | 23826.23 | 30-APR-15:52 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.88 |
May | 24587.42 | 28-MAY-16:12 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.98 |
June | 22462.69 | 25-JUN-16:12 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.67 |
July | 23742.33 | 23-JUL-16:02 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.61 |
August | 24396.10 | 20-AUG-16:01 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.29 |
September | 24491.67 | 10-SEP-15:42 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.29 |
October | 23620.09 | 15-OCT-15:12 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 24.28 | 0.00 |
November | 23231.26 | 19-NOV-13:42 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.06 |
December | 23986.41 | 25-DEC-14:32 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.50 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9738.61 | 326.14 | 186.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24587.42 | 1239.33 | 670.83 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 24.28 | 147.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4128.60 | 18-JAN-14:20 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
February | 3463.26 | 01-FEB-13:20 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.03 |
March | 4158.41 | 23-MAR-14:40 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.52 |
April | 5634.52 | 26-APR-14:00 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 0.00 |
May | 6216.19 | 04-MAY-13:50 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.78 |
June | 5990.94 | 29-JUN-16:00 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.39 |
July | 6627.73 | 19-JUL-14:50 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 0.00 |
August | 6558.17 | 17-AUG-14:00 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 29.11 | 0.00 |
September | 9583.45 | 30-SEP-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
October | 8164.41 | 02-OCT-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.55 |
November | 3707.98 | 01-NOV-13:50 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.53 |
December | 4025.47 | 05-DEC-15:00 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 6.75 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3463.26 | 809.73 | 269.88 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9583.45 | 2010.79 | 1040.96 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 29.11 | 38.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6246.48 | 20-JAN-09:30 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.79 |
February | 6307.67 | 21-FEB-09:40 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.22 |
March | 9169.13 | 19-MAR-10:03 | 195.68 | 111.80 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.05 |
April | 19515.67 | 30-APR-09:02 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.27 |
May | 18772.00 | 28-MAY-08:43 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.35 |
June | 19515.42 | 18-JUN-08:32 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.06 |
July | 19760.49 | 04-JUL-09:02 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.30 |
August | 19383.41 | 20-AUG-09:22 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.97 |
September | 19587.68 | 10-SEP-08:52 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.66 |
October | 19488.29 | 15-OCT-08:12 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 50.04 | 0.00 |
November | 6827.20 | 19-NOV-09:13 | 195.68 | 111.80 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.16 |
December | 6323.39 | 05-DEC-09:20 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 3.44 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6246.48 | 195.68 | 111.80 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19760.49 | 1239.33 | 670.83 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 50.04 | 126.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21143.91 | 22-JAN-13:12 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.00 |
February | 20993.93 | 19-FEB-11:53 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.59 |
March | 20679.66 | 19-MAR-13:23 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.55 |
April | 11695.01 | 09-APR-13:02 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.55 |
May | 8447.80 | 04-MAY-12:30 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.09 |
June | 7313.37 | 30-JUN-12:40 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.84 |
July | 10334.87 | 31-JUL-12:40 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 32.60 | 0.00 |
August | 12924.61 | 30-AUG-13:00 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.93 |
September | 20414.10 | 10-SEP-12:53 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.07 |
October | 23651.89 | 15-OCT-12:11 | 809.75 | 462.62 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 90.64 | 0.00 |
November | 21779.80 | 26-NOV-12:22 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.42 |
December | 22335.89 | 24-DEC-13:02 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7313.37 | 404.87 | 231.31 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23651.89 | 1923.15 | 1040.98 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 90.64 | 319.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7982.05 | 18-JAN-15:00 | 1295.83 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.64 |
February | 9147.36 | 20-FEB-15:32 | 260.91 | 149.06 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.29 |
March | 18969.18 | 19-MAR-16:01 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.78 |
April | 20336.14 | 30-APR-16:21 | 521.82 | 298.13 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.60 |
May | 20390.52 | 14-MAY-16:32 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.20 |
June | 21204.75 | 18-JUN-16:42 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.55 |
July | 21485.97 | 16-JUL-16:12 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.38 |
August | 20234.49 | 13-AUG-16:02 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.95 |
September | 21261.35 | 04-SEP-16:02 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.95 |
October | 21831.71 | 15-OCT-14:51 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 47.90 | 0.00 |
November | 9416.52 | 23-NOV-15:23 | 260.91 | 149.06 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.37 |
December | 8489.51 | 18-DEC-15:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.70 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7982.05 | 260.91 | 149.06 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21831.71 | 1295.83 | 670.83 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 47.90 | 270.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3772.37 | 18-JAN-15:00 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.53 |
February | 3172.45 | 16-FEB-14:50 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.59 |
March | 4271.72 | 23-MAR-15:10 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 |
April | 6142.87 | 26-APR-14:00 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 14.62 | 0.00 |
May | 6762.08 | 04-MAY-13:50 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.80 |
June | 6597.05 | 30-JUN-14:00 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.88 |
July | 7404.45 | 19-JUL-14:50 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 29.07 | 0.00 |
August | 7180.94 | 17-AUG-14:00 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 35.14 | 0.00 |
September | 8152.48 | 29-SEP-13:50 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 110.22 | 0.00 |
October | 8222.97 | 16-OCT-13:10 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 106.18 | 0.00 |
November | 3498.29 | 10-NOV-14:30 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.14 |
December | 3699.39 | 05-DEC-15:00 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 7.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3172.45 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8222.97 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 110.22 | 60.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5035.61 | 20-JAN-09:50 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.87 |
February | 4973.28 | 02-FEB-10:10 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.57 |
March | 8058.92 | 23-MAR-09:30 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.06 |
April | 15372.17 | 30-APR-10:13 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.73 |
May | 14636.84 | 28-MAY-08:43 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.32 |
June | 17429.64 | 18-JUN-09:43 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.85 |
July | 18849.85 | 23-JUL-07:42 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.94 |
August | 19328.34 | 06-AUG-08:42 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.32 |
September | 18728.78 | 10-SEP-08:32 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.02 |
October | 19105.62 | 15-OCT-10:22 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 54.07 | 0.00 |
November | 4504.36 | 01-NOV-09:30 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.10 |
December | 5075.83 | 05-DEC-09:50 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 8.75 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4504.36 | 260.91 | 149.06 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19328.34 | 1295.83 | 670.83 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 54.07 | 154.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22343.22 | 22-JAN-11:32 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.11 |
February | 22863.89 | 20-FEB-13:52 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 586.07 |
March | 18166.16 | 19-MAR-12:23 | 303.66 | 173.48 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.08 |
April | 12316.13 | 30-APR-13:32 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.95 |
May | 8929.10 | 04-MAY-12:30 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.91 |
June | 7918.41 | 30-JUN-13:10 | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.88 |
July | 11077.13 | 31-JUL-12:40 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 39.34 | 0.00 |
August | 13456.95 | 30-AUG-13:00 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.31 |
September | 21659.56 | 04-SEP-13:23 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.06 |
October | 24721.26 | 15-OCT-11:01 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 51.89 | 0.00 |
November | 22843.39 | 23-NOV-14:22 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.48 |
December | 23717.92 | 25-DEC-13:51 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7918.41 | 303.66 | 173.48 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24721.26 | 2010.83 | 1040.98 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 51.89 | 586.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7783.16 | 18-JAN-15:00 | 1295.83 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 |
February | 8683.14 | 22-FEB-15:50 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.98 |
March | 11511.41 | 19-MAR-16:23 | 260.91 | 149.06 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.09 |
April | 22349.45 | 30-APR-16:12 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.95 |
May | 21530.86 | 29-MAY-16:42 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.10 |
June | 22283.78 | 18-JUN-16:52 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.08 |
July | 23139.45 | 04-JUL-16:41 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 21770.90 | 06-AUG-16:41 | 521.82 | 298.13 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.31 |
September | 22374.57 | 04-SEP-16:02 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.15 |
October | 23636.46 | 15-OCT-15:41 | 521.82 | 298.13 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 19.87 | 0.00 |
November | 8338.78 | 10-NOV-14:50 | 1295.83 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.12 |
December | 8205.98 | 19-DEC-15:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7783.16 | 260.91 | 149.06 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23636.46 | 1295.83 | 670.83 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 19.87 | 315.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8675.58 | 02-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.13 |
February | 6793.86 | 21-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.69 |
March | 6825.91 | 20-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.47 |
April | 7137.54 | 10-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.64 |
May | 7445.34 | 01-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7307.80 | 12-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.93 |
July | 8772.37 | 03-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 9688.23 | 21-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.45 |
September | 9135.38 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12436.52 | 02-OCT-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.42 |
November | 8824.49 | 13-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.81 |
December | 9092.38 | 26-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6793.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12436.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4087.88 | 18-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.42 |
February | 4297.91 | 03-FEB-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.64 |
March | 4545.62 | 23-MAR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.82 |
April | 4406.83 | 27-APR-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.37 |
May | 4539.27 | 06-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.96 |
June | 4843.31 | 30-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.63 |
July | 5209.33 | 19-JUL-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.42 | 0.00 |
August | 5441.77 | 18-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.64 | 0.00 |
September | 5757.40 | 30-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.38 |
October | 7204.42 | 02-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.81 |
November | 4628.73 | 14-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.70 |
December | 4453.07 | 20-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.16 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4087.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7204.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.42 | 164.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7844.28 | 18-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.37 |
February | 7648.64 | 01-FEB-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.82 |
March | 11297.82 | 23-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.91 |
April | 14795.02 | 26-APR-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.84 | 0.00 |
May | 13827.94 | 03-MAY-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.38 |
June | 13951.69 | 30-JUN-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.75 |
July | 15609.02 | 19-JUL-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.13 | 0.00 |
August | 14964.78 | 14-AUG-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.02 |
September | 15077.39 | 29-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.84 | 0.00 |
October | 17107.34 | 16-OCT-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.37 | 0.00 |
November | 7497.53 | 10-NOV-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.18 |
December | 7131.07 | 05-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 7131.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17107.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.84 | 99.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2134.72 | 30-JAN-16:50 | 222.14 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4141.14 | 22-FEB-17:00 | 222.14 | 450.11 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7028.25 | 31-MAR-24:00 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7917.99 | 16-APR-17:40 | 0.00 | 100.03 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3305.68 | 31-MAY-24:00 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5349.89 | 30-JUN-24:00 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7222.24 | 31-JUL-23:45 | 0.00 | 50.02 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8033.26 | 06-AUG-17:52 | 0.00 | 125.04 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3559.66 | 30-SEP-24:00 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5324.59 | 31-OCT-24:00 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5997.00 | 07-NOV-16:20 | 222.14 | 450.11 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7978.95 | 25-DEC-16:13 | 35.07 | 75.02 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2134.72 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8033.26 | 222.14 | 450.11 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1947.29 | 30-JAN-16:50 | 222.14 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3872.53 | 22-FEB-17:00 | 222.14 | 450.11 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6318.38 | 31-MAR-23:40 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7365.27 | 27-APR-17:30 | 23.38 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2953.90 | 31-MAY-24:00 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5051.43 | 30-JUN-24:00 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6893.39 | 31-JUL-23:53 | 0.00 | 75.02 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7449.60 | 06-AUG-18:00 | 0.00 | 125.04 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3283.00 | 30-SEP-24:00 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4915.78 | 31-OCT-24:00 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5633.08 | 07-NOV-16:30 | 222.14 | 450.11 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7438.90 | 19-DEC-16:20 | 222.14 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1947.29 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7449.60 | 222.14 | 450.11 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1879.91 | 30-JAN-16:50 | 222.14 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3865.81 | 22-FEB-17:00 | 222.14 | 450.11 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5967.09 | 31-MAR-23:20 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7417.38 | 26-APR-17:00 | 70.15 | 250.06 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2697.37 | 31-MAY-23:40 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4932.12 | 30-JUN-24:00 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6802.57 | 31-JUL-23:53 | 0.00 | 75.02 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7557.63 | 06-AUG-17:45 | 0.00 | 100.03 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3239.79 | 30-SEP-23:50 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4704.49 | 31-OCT-23:40 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5614.74 | 07-NOV-16:30 | 222.14 | 450.11 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7441.98 | 19-DEC-16:20 | 222.14 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1879.91 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7557.63 | 222.14 | 450.11 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 92725.78 | 02-JAN-16:55 | 9617.36 | 10941.12 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 183666.00 | 21-FEB-17:00 | 4808.68 | 5470.56 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358090.31 | 31-MAR-24:00 | 0.00 | 303.90 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 367065.94 | 26-APR-16:00 | 4808.68 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 175301.64 | 31-MAY-24:00 | 0.00 | 303.90 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267087.42 | 30-JUN-24:00 | 0.00 | 303.90 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 359145.32 | 31-JUL-23:53 | 0.00 | 911.69 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 369607.28 | 14-AUG-16:00 | 4808.68 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 176337.98 | 30-SEP-24:00 | 0.00 | 303.90 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 267916.53 | 31-OCT-24:00 | 0.00 | 303.90 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 276341.86 | 13-NOV-17:00 | 4808.68 | 5470.56 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 367982.42 | 26-DEC-17:00 | 4808.68 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 92725.78 | 0.00 | 303.90 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 369607.28 | 9617.36 | 10941.12 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.167150E+13 | 1417697.12 | 18-JAN-11:00 | 0.121773E+11 | 282618.82 | 09-JAN-06:10 |
February | 0.179079E+13 | 1557890.22 | 03-FEB-15:09 | 0.328510E+10 | 85090.19 | 06-FEB-06:10 |
March | 0.235807E+13 | 1712993.32 | 23-MAR-15:50 | 0.680402E+10 | 261120.40 | 30-MAR-05:10 |
April | 0.264694E+13 | 1890057.94 | 26-APR-10:00 | 0.626418E+09 | 95226.51 | 01-APR-05:10 |
May | 0.166104E+13 | 1381138.30 | 04-MAY-14:09 | 0.100019E+09 | 23363.54 | 15-MAY-05:10 |
June | 0.203787E+13 | 1574783.47 | 28-JUN-10:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.257288E+13 | 1888037.16 | 31-JUL-15:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.316977E+13 | 2060483.20 | 18-AUG-15:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.168989E+13 | 1482303.05 | 29-SEP-15:00 | 228579.87 | 350.08 | 20-SEP-05:40 |
October | 0.219484E+13 | 1663866.38 | 13-OCT-15:39 | 0.157926E+09 | 16627.18 | 30-OCT-05:10 |
November | 0.232576E+13 | 1730041.98 | 29-NOV-11:00 | 0.137574E+10 | 78367.48 | 27-NOV-06:10 |
December | 0.281695E+13 | 1910586.80 | 05-DEC-15:50 | 0.588610E+10 | 172485.28 | 13-DEC-06:10 |
Annual Sum or Average | 0.269363E+14 | 0.304129E+11 | ||||
Minimum of Months | 0.166104E+13 | 1381138.30 | 0.00 | 0.00 | ||
Maximum of Months | 0.316977E+13 | 2060483.20 | 0.121773E+11 | 282618.82 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.272603E+12 | 0.377521E+11 | 0.766053E+12 | 0.213344E+12 | 0.190849E+12 | 0.255184E+11 | 0.00 | 0.433197E+11 | 0.227204E+11 | 0.650325E+11 | 0.00 | 0.343123E+11 | 0.00 |
February | 0.244671E+12 | 0.310313E+11 | 0.978954E+12 | 0.195333E+12 | 0.173427E+12 | 0.219380E+11 | 0.00 | 0.422380E+11 | 0.166420E+11 | 0.553416E+11 | 0.00 | 0.312141E+11 | 0.00 |
March | 0.289862E+12 | 0.299078E+11 | 0.141687E+13 | 0.226058E+12 | 0.196718E+12 | 0.231481E+11 | 0.00 | 0.688963E+11 | 0.233140E+11 | 0.469851E+11 | 0.00 | 0.363069E+11 | 0.00 |
April | 0.256638E+12 | 0.247703E+11 | 0.165903E+13 | 0.211502E+12 | 0.203187E+12 | 0.295368E+11 | 0.00 | 0.156302E+12 | 0.582191E+11 | 0.154759E+11 | 0.00 | 0.322833E+11 | 0.00 |
May | 0.276438E+12 | 0.228103E+11 | 0.774844E+12 | 0.219700E+12 | 0.205289E+12 | 0.314155E+11 | 0.00 | 0.521260E+11 | 0.398839E+11 | 0.492322E+10 | 0.00 | 0.336115E+11 | 0.00 |
June | 0.275094E+12 | 0.210075E+11 | 0.106252E+13 | 0.217935E+12 | 0.210477E+12 | 0.375233E+11 | 0.00 | 0.114485E+12 | 0.659322E+11 | 0.324481E+09 | 0.00 | 0.325777E+11 | 0.00 |
July | 0.256723E+12 | 0.220001E+11 | 0.139340E+13 | 0.213266E+12 | 0.224227E+12 | 0.490105E+11 | 0.00 | 0.265692E+12 | 0.117985E+12 | 9462775.40 | 0.00 | 0.305620E+11 | 0.00 |
August | 0.287422E+12 | 0.242313E+11 | 0.173200E+13 | 0.226058E+12 | 0.239018E+12 | 0.538839E+11 | 0.00 | 0.423236E+12 | 0.150544E+12 | 0.00 | 0.00 | 0.333738E+11 | 0.00 |
September | 0.257704E+12 | 0.270872E+11 | 0.740713E+12 | 0.211501E+12 | 0.208583E+12 | 0.385936E+11 | 0.00 | 0.996963E+11 | 0.711035E+11 | 0.425572E+10 | 0.00 | 0.306526E+11 | 0.00 |
October | 0.269743E+12 | 0.325062E+11 | 0.108340E+13 | 0.213343E+12 | 0.210527E+12 | 0.418103E+11 | 0.00 | 0.163752E+12 | 0.890267E+11 | 0.584224E+11 | 0.00 | 0.323116E+11 | 0.00 |
November | 0.269249E+12 | 0.354138E+11 | 0.135889E+13 | 0.205297E+12 | 0.193488E+12 | 0.270495E+11 | 0.00 | 0.885412E+11 | 0.335058E+11 | 0.818134E+11 | 0.00 | 0.325058E+11 | 0.00 |
December | 0.264199E+12 | 0.388307E+11 | 0.170972E+13 | 0.213268E+12 | 0.195007E+12 | 0.258216E+11 | 0.00 | 0.142727E+12 | 0.466981E+11 | 0.147606E+12 | 0.00 | 0.330749E+11 | 0.00 |
Annual Sum or Average | 0.322035E+13 | 0.347348E+12 | 0.146764E+14 | 0.256660E+13 | 0.245080E+13 | 0.405249E+12 | 0.00 | 0.166101E+13 | 0.735574E+12 | 0.480190E+12 | 0.00 | 0.392787E+12 | 0.00 |
Minimum of Months | 0.244671E+12 | 0.210075E+11 | 0.740713E+12 | 0.195333E+12 | 0.173427E+12 | 0.219380E+11 | 0.00 | 0.422380E+11 | 0.166420E+11 | 0.00 | 0.00 | 0.305620E+11 | 0.00 |
Maximum of Months | 0.289862E+12 | 0.388307E+11 | 0.173200E+13 | 0.226058E+12 | 0.239018E+12 | 0.538839E+11 | 0.00 | 0.423236E+12 | 0.150544E+12 | 0.147606E+12 | 0.00 | 0.363069E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.121773E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.328510E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.680402E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.626418E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.100019E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 228579.87 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.157926E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.137574E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.588610E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.304129E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.121773E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 325713.14 | 02-JAN-16:49 | 40855.88 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 233421.82 | 31-JAN-08:20 | 149885.63 | 19-JAN-15:39 | 39851.04 | 18-JAN-13:39 | 0.00 | 01-JAN-00:10 |
February | 325713.14 | 27-FEB-16:00 | 40855.88 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 233419.06 | 08-FEB-08:20 | 154231.87 | 03-FEB-15:50 | 38236.99 | 01-FEB-11:00 | 0.00 | 01-FEB-00:10 |
March | 297414.32 | 16-MAR-07:10 | 40855.88 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 233424.04 | 16-MAR-07:19 | 170602.19 | 23-MAR-15:30 | 39285.39 | 23-MAR-13:30 | 0.00 | 01-MAR-00:10 |
April | 297349.23 | 21-APR-15:00 | 40855.88 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 233419.98 | 05-APR-07:19 | 183272.72 | 26-APR-14:30 | 39579.61 | 12-APR-13:50 | 0.00 | 01-APR-00:10 |
May | 289817.35 | 09-MAY-07:10 | 27558.46 | 01-MAY-18:30 | 423497.50 | 01-MAY-07:10 | 233419.98 | 09-MAY-07:19 | 160254.77 | 04-MAY-13:30 | 38819.03 | 03-MAY-13:39 | 0.00 | 01-MAY-00:10 |
June | 286531.10 | 09-JUN-07:10 | 27558.46 | 01-JUN-18:49 | 541788.89 | 01-JUN-07:10 | 233418.23 | 09-JUN-07:19 | 171488.61 | 21-JUN-15:00 | 38463.06 | 29-JUN-12:00 | 0.00 | 01-JUN-00:10 |
July | 284436.93 | 11-JUL-07:10 | 27558.46 | 01-JUL-18:00 | 660080.29 | 03-JUL-07:10 | 233417.11 | 11-JUL-07:19 | 187850.36 | 31-JUL-14:00 | 40082.01 | 31-JUL-15:50 | 0.00 | 01-JUL-00:10 |
August | 289817.35 | 21-AUG-07:10 | 40855.88 | 08-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 233419.98 | 21-AUG-07:19 | 193755.51 | 18-AUG-14:50 | 40305.41 | 18-AUG-15:50 | 0.00 | 01-AUG-00:10 |
September | 302581.74 | 18-SEP-07:10 | 40855.88 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 233426.80 | 18-SEP-07:19 | 181413.63 | 11-SEP-14:30 | 43388.85 | 29-SEP-10:30 | 0.00 | 01-SEP-00:10 |
October | 307068.14 | 23-OCT-15:00 | 40855.88 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 233429.20 | 24-OCT-07:19 | 193110.52 | 17-OCT-15:00 | 46745.99 | 30-OCT-13:39 | 0.00 | 01-OCT-00:10 |
November | 325713.14 | 06-NOV-16:40 | 40855.88 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 233420.07 | 24-NOV-08:20 | 155334.27 | 13-NOV-15:20 | 38235.25 | 28-NOV-13:50 | 0.00 | 01-NOV-00:10 |
December | 325713.14 | 01-DEC-16:19 | 40855.88 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 233421.14 | 08-DEC-08:20 | 158786.93 | 05-DEC-15:00 | 39232.72 | 05-DEC-14:39 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 284436.93 | 27558.46 | 423497.50 | 233417.11 | 149885.63 | 38235.25 | 0.00 | |||||||
Maximum of Months | 325713.14 | 40855.88 | 778371.69 | 233429.20 | 193755.51 | 46745.99 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 171251.31 | 13-JAN-14:39 | 64800.44 | 13-JAN-13:20 | 100000.00 | 08-JAN-11:20 | 0.00 | 45272.11 | 31-JAN-12:30 | 0.00 |
February | 208698.47 | 01-FEB-11:39 | 64800.44 | 01-FEB-11:39 | 100000.00 | 03-FEB-05:30 | 0.00 | 45273.71 | 02-FEB-12:39 | 0.00 |
March | 239681.28 | 23-MAR-15:39 | 80352.61 | 22-MAR-12:39 | 100000.00 | 07-MAR-11:30 | 0.00 | 45062.60 | 01-MAR-12:30 | 0.00 |
April | 303937.10 | 26-APR-12:20 | 80352.61 | 04-APR-13:00 | 100000.00 | 01-APR-04:19 | 0.00 | 44278.51 | 03-APR-11:30 | 0.00 |
May | 170351.45 | 04-MAY-12:50 | 80352.61 | 03-MAY-13:39 | 100000.00 | 24-MAY-06:40 | 0.00 | 43298.67 | 01-MAY-11:00 | 0.00 |
June | 236347.09 | 29-JUN-11:09 | 80352.61 | 19-JUN-12:20 | 60143.16 | 12-JUN-09:00 | 0.00 | 42135.09 | 01-JUN-11:00 | 0.00 |
July | 384388.66 | 31-JUL-15:50 | 80352.61 | 03-JUL-12:09 | 15771.29 | 31-JUL-23:10 | 0.00 | 41194.49 | 03-JUL-11:00 | 0.00 |
August | 430824.11 | 18-AUG-15:50 | 80352.61 | 02-AUG-09:30 | 0.00 | 01-AUG-00:10 | 0.00 | 41103.73 | 31-AUG-11:50 | 0.00 |
September | 235936.37 | 29-SEP-12:00 | 80352.61 | 05-SEP-12:50 | 100000.00 | 29-SEP-07:40 | 0.00 | 41859.19 | 29-SEP-11:00 | 0.00 |
October | 319853.84 | 03-OCT-13:30 | 80352.61 | 01-OCT-11:39 | 100000.00 | 13-OCT-04:30 | 0.00 | 43051.14 | 31-OCT-11:39 | 0.00 |
November | 250561.20 | 28-NOV-13:09 | 64800.44 | 10-NOV-12:39 | 100000.00 | 09-NOV-05:30 | 0.00 | 44134.80 | 30-NOV-12:30 | 0.00 |
December | 296505.65 | 19-DEC-12:20 | 53895.67 | 05-DEC-14:09 | 100000.00 | 04-DEC-05:19 | 0.00 | 44911.25 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 170351.45 | 53895.67 | 0.00 | 0.00 | 41103.73 | 0.00 | ||||
Maximum of Months | 430824.11 | 80352.61 | 100000.00 | 0.00 | 45273.71 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1417697.12 | 18-JAN-11:00 | 280450.63 | 423497.50 | 0.00 | 233151.79 | 103479.14 | 21234.46 | 0.00 | 167058.46 | 52294.76 |
February | 1557890.22 | 03-FEB-15:09 | 280450.63 | 541788.89 | 0.00 | 233151.79 | 131855.11 | 20931.68 | 0.00 | 173131.52 | 50586.80 |
March | 1712993.32 | 23-MAR-15:50 | 280450.63 | 660080.29 | 0.00 | 233302.19 | 166629.33 | 21589.25 | 0.00 | 236179.88 | 80352.61 |
April | 1890057.94 | 26-APR-10:00 | 280450.63 | 778371.69 | 0.00 | 233151.79 | 156027.17 | 38068.55 | 0.00 | 288299.85 | 80352.61 |
May | 1381138.30 | 04-MAY-14:09 | 280450.63 | 423497.50 | 0.00 | 233151.79 | 158973.77 | 21536.63 | 0.00 | 158166.51 | 80352.61 |
June | 1574783.47 | 28-JUN-10:00 | 280450.63 | 541788.89 | 0.00 | 233151.79 | 142099.88 | 38240.76 | 0.00 | 224691.17 | 80352.61 |
July | 1888037.16 | 31-JUL-15:50 | 280450.63 | 660080.29 | 0.00 | 233302.19 | 177843.62 | 40082.01 | 0.00 | 384388.66 | 80352.61 |
August | 2060483.20 | 18-AUG-15:50 | 280450.63 | 778371.69 | 0.00 | 233302.19 | 185313.71 | 40305.41 | 0.00 | 430824.11 | 80352.61 |
September | 1482303.05 | 29-SEP-15:00 | 281332.72 | 423497.50 | 0.00 | 233302.19 | 172859.95 | 40248.88 | 0.00 | 218273.74 | 80352.61 |
October | 1663866.38 | 13-OCT-15:39 | 282443.77 | 541788.89 | 0.00 | 233303.25 | 175107.04 | 40162.34 | 0.00 | 229783.56 | 80352.61 |
November | 1730041.98 | 29-NOV-11:00 | 280450.63 | 660080.29 | 0.00 | 233151.79 | 105653.57 | 21217.45 | 0.00 | 242757.88 | 50948.71 |
December | 1910586.80 | 05-DEC-15:50 | 286612.11 | 778371.69 | 0.00 | 233152.85 | 150038.29 | 20968.97 | 0.00 | 264069.22 | 51753.88 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1381138.30 | 280450.63 | 423497.50 | 0.00 | 233151.79 | 103479.14 | 20931.68 | 0.00 | 158166.51 | 50586.80 | |
Maximum of Months | 2060483.20 | 286612.11 | 778371.69 | 0.00 | 233303.25 | 185313.71 | 40305.41 | 0.00 | 430824.11 | 80352.61 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 282618.82 | 09-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 85090.19 | 06-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 261120.40 | 30-MAR-05:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 95226.51 | 01-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 23363.54 | 15-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 350.08 | 20-SEP-05:40 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 16627.18 | 30-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 78367.48 | 27-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 172485.28 | 13-DEC-06:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 282618.82 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 95.83 | 27.47 | 46.67 | 27.41 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 58.83 | 26.60 | 28.50 | 26.55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 52.67 | 26.35 | 30.17 | 26.36 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 49.17 | 26.45 | 28.33 | 26.45 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 54.50 | 26.35 | 30.83 | 26.34 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 52.50 | 26.37 | 30.83 | 26.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 117.50 | 26.91 | 68.33 | 26.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 112.83 | 27.03 | 72.00 | 27.01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 158.67 | 27.23 | 98.33 | 27.22 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 205.00 | 27.47 | 122.83 | 27.40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 89.00 | 27.10 | 39.17 | 27.06 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 85.17 | 27.03 | 39.50 | 26.98 |
Annual Sum or Average | 0.00 | 0.00 | 1131.67 | 27.03 | 635.50 | 26.99 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 49.17 | 26.35 | 28.33 | 26.34 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 205.00 | 27.47 | 122.83 | 27.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 26.16 | 0.17 | 26.43 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.58 | 0.00 | 25.58 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.57 | 0.00 | 25.57 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.57 | 0.00 | 25.57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.64 | 0.00 | 25.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.57 | 0.00 | 25.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 26.19 | 0.00 | 26.19 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.63 | 0.00 | 25.63 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.79 | 0.00 | 25.79 |
Annual Sum or Average | 0.00 | 0.00 | 4.83 | 25.81 | 0.17 | 25.86 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 26.19 | 0.17 | 26.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.69 | 0.00 | 25.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 25.69 | 0.00 | 25.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.69 | 0.00 | 25.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.35 | 0.67 | 27.35 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.54 | 1.33 | 27.54 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.68 | 3.00 | 27.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.61 | 2.50 | 27.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.73 | 2.83 | 27.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.86 | 5.17 | 27.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.84 | 3.67 | 27.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.78 | 2.17 | 27.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.92 | 1.83 | 27.92 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.51 | 0.33 | 27.51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 23.50 | 27.75 | 23.50 | 27.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.92 | 5.17 | 27.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.84 | 4.67 | 27.84 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.84 | 4.50 | 27.84 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.65 | 2.50 | 27.65 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.40 | 1.83 | 27.40 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.35 | 0.17 | 27.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.37 | 0.83 | 27.37 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.53 | 4.67 | 27.53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 19.00 | 26.43 | 18.83 | 26.43 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.99 | 6.50 | 27.99 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 26.74 | 13.00 | 26.74 |
Annual Sum or Average | 0.00 | 0.00 | 57.67 | 27.09 | 57.50 | 27.09 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 19.00 | 27.99 | 18.83 | 27.99 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.50 | 0.50 | 27.50 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.81 | 2.67 | 27.81 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.98 | 2.67 | 27.97 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.60 | 6.00 | 27.91 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.90 | 5.17 | 27.94 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.67 | 3.67 | 27.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 19.00 | 27.59 | 8.00 | 27.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 27.36 | 7.00 | 27.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.02 | 3.83 | 28.09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.73 | 5.83 | 27.93 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.86 | 4.00 | 27.86 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.51 | 5.17 | 27.67 |
Annual Sum or Average | 0.00 | 0.00 | 96.33 | 27.62 | 54.50 | 27.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.36 | 0.50 | 27.50 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 28.02 | 8.00 | 28.09 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.38 | 0.50 | 27.38 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.72 | 1.83 | 27.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.63 | 1.83 | 27.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.79 | 2.50 | 27.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.87 | 5.33 | 27.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.84 | 3.83 | 27.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.78 | 1.83 | 27.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.88 | 1.33 | 27.88 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 19.00 | 27.80 | 19.00 | 27.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.88 | 5.33 | 27.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.13 | 6.33 | 27.13 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.87 | 4.83 | 27.87 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.62 | 2.17 | 27.62 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.28 | 0.33 | 27.28 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 26.48 | 6.83 | 26.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 25.17 | 26.18 | 25.00 | 26.18 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 26.67 | 10.17 | 26.67 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 | 25.83 | 22.67 | 25.83 |
Annual Sum or Average | 0.00 | 0.00 | 78.50 | 26.39 | 78.33 | 26.39 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 25.17 | 27.87 | 25.00 | 27.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.34 | 0.33 | 27.34 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.79 | 0.50 | 27.82 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.00 | 3.50 | 28.02 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.82 | 3.83 | 27.84 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.91 | 2.50 | 27.95 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 28.03 | 5.33 | 28.08 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.10 | 3.50 | 28.13 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.94 | 2.67 | 28.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.93 | 3.33 | 27.94 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 33.67 | 27.96 | 25.50 | 27.99 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 28.10 | 5.33 | 28.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.17 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.17 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.17 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.60 | 1.00 | 27.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.45 | 1.00 | 27.45 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.74 | 2.00 | 27.74 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.82 | 5.33 | 27.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.73 | 3.83 | 27.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.66 | 1.17 | 27.66 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.76 | 1.50 | 27.76 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.83 | 19.22 | 0.00 | 19.22 | 15.83 | 27.31 | 15.83 | 27.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 19.28 | 0.00 | 19.28 | 5.33 | 27.82 | 5.33 | 27.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.34 | 0.00 | 19.34 | 3.00 | 27.38 | 3.00 | 27.59 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.66 | 3.67 | 27.66 |
March | 0.17 | 19.42 | 0.00 | 19.42 | 1.83 | 26.80 | 1.83 | 27.12 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 26.47 | 4.67 | 26.47 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 26.40 | 18.17 | 26.40 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.91 | 4.83 | 27.91 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.47 | 6.33 | 27.47 |
Annual Sum or Average | 0.33 | 19.38 | 0.00 | 19.38 | 42.67 | 26.93 | 42.50 | 26.96 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.42 | 0.00 | 19.42 | 18.33 | 27.91 | 18.17 | 27.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.85 | 0.50 | 27.85 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.95 | 3.17 | 28.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.93 | 3.00 | 27.95 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.94 | 3.00 | 27.96 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 28.13 | 5.67 | 28.18 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.21 | 3.50 | 28.24 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.93 | 2.50 | 27.98 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.02 | 2.83 | 28.04 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.38 | 0.00 | 19.38 | 32.00 | 27.99 | 24.17 | 28.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.38 | 0.00 | 19.38 | 8.50 | 28.21 | 5.67 | 28.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.63 | 0.83 | 27.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.83 | 27.63 | 0.83 | 27.63 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.63 | 0.83 | 27.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 54.17 | 28.28 | 54.17 | 28.28 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 54.17 | 28.28 | 54.17 | 28.28 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 54.17 | 28.28 | 54.17 | 28.28 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 32.67 | 26.16 | 304.33 | 25.34 | 14.83 | 25.48 |
February | 22.67 | 24.25 | 286.50 | 24.96 | 1.67 | 24.97 |
March | 0.00 | 0.00 | 347.50 | 24.82 | 0.00 | 24.82 |
April | 1.33 | 24.00 | 426.67 | 24.74 | 0.00 | 24.74 |
May | 0.00 | 0.00 | 405.50 | 24.76 | 0.00 | 24.76 |
June | 0.00 | 0.00 | 482.33 | 24.59 | 0.00 | 24.59 |
July | 139.50 | 25.95 | 497.00 | 25.12 | 139.50 | 25.27 |
August | 126.00 | 26.22 | 514.00 | 25.10 | 126.00 | 25.28 |
September | 76.83 | 27.41 | 483.00 | 25.40 | 76.83 | 25.64 |
October | 71.50 | 28.06 | 387.17 | 25.95 | 71.50 | 26.23 |
November | 21.00 | 26.29 | 319.83 | 25.22 | 13.00 | 25.32 |
December | 26.50 | 25.56 | 244.17 | 25.52 | 11.33 | 25.61 |
Annual Sum or Average | 518.00 | 26.45 | 4698.00 | 25.12 | 454.67 | 25.26 |
Minimum of Months | 0.00 | 0.00 | 244.17 | 24.59 | 0.00 | 24.59 |
Maximum of Months | 139.50 | 28.06 | 514.00 | 25.95 | 139.50 | 26.23 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 30.50 | 23.93 | 242.83 | 24.61 | 0.00 | 24.61 |
February | 18.33 | 23.99 | 255.83 | 24.49 | 0.00 | 24.49 |
March | 0.00 | 0.00 | 340.67 | 24.43 | 0.00 | 24.43 |
April | 2.33 | 23.98 | 437.83 | 24.32 | 0.00 | 24.32 |
May | 0.50 | 23.62 | 380.17 | 24.34 | 0.00 | 24.34 |
June | 0.00 | 0.00 | 485.83 | 24.28 | 0.00 | 24.28 |
July | 0.00 | 0.00 | 497.00 | 24.29 | 0.00 | 24.29 |
August | 0.00 | 0.00 | 514.00 | 24.23 | 0.00 | 24.23 |
September | 0.00 | 0.00 | 458.83 | 24.33 | 0.00 | 24.33 |
October | 1.17 | 24.00 | 347.17 | 24.54 | 0.00 | 24.54 |
November | 14.33 | 24.44 | 288.17 | 24.60 | 2.00 | 24.62 |
December | 18.50 | 24.00 | 220.67 | 24.72 | 0.00 | 24.72 |
Annual Sum or Average | 85.67 | 24.04 | 4469.00 | 24.40 | 2.00 | 24.40 |
Minimum of Months | 0.00 | 0.00 | 220.67 | 24.23 | 0.00 | 24.23 |
Maximum of Months | 30.50 | 24.44 | 514.00 | 24.72 | 2.00 | 24.72 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 177.83 | 23.59 | 106.00 | 23.87 | 13.17 | 23.88 |
February | 134.67 | 23.54 | 109.00 | 23.88 | 0.00 | 23.88 |
March | 109.00 | 23.50 | 173.50 | 23.98 | 0.00 | 23.98 |
April | 56.17 | 23.41 | 236.33 | 24.10 | 0.00 | 24.10 |
May | 40.00 | 23.48 | 264.67 | 24.19 | 0.00 | 24.19 |
June | 4.00 | 23.41 | 397.67 | 24.20 | 0.00 | 24.20 |
July | 0.00 | 0.00 | 479.67 | 24.15 | 0.00 | 24.15 |
August | 0.00 | 0.00 | 508.33 | 24.13 | 0.00 | 24.13 |
September | 7.67 | 23.54 | 401.00 | 24.19 | 0.33 | 24.19 |
October | 54.17 | 23.66 | 259.83 | 24.23 | 0.00 | 24.23 |
November | 133.33 | 23.68 | 166.00 | 24.08 | 0.00 | 24.08 |
December | 217.67 | 23.62 | 71.00 | 23.81 | 0.00 | 23.81 |
Annual Sum or Average | 934.50 | 23.58 | 3173.00 | 24.09 | 13.50 | 24.09 |
Minimum of Months | 0.00 | 0.00 | 71.00 | 23.81 | 0.00 | 23.81 |
Maximum of Months | 217.67 | 23.68 | 508.33 | 24.23 | 13.17 | 24.23 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.50 | 22.73 | 47.33 | 22.77 | 12.67 | 22.70 |
February | 310.33 | 22.81 | 40.50 | 22.95 | 0.00 | 22.95 |
March | 311.50 | 23.00 | 88.50 | 23.23 | 0.00 | 23.23 |
April | 165.00 | 23.05 | 177.83 | 23.60 | 0.00 | 23.60 |
May | 157.83 | 23.12 | 195.17 | 23.68 | 0.00 | 23.68 |
June | 46.00 | 23.24 | 342.17 | 24.04 | 0.00 | 24.04 |
July | 4.00 | 23.29 | 457.83 | 24.12 | 0.00 | 24.12 |
August | 2.50 | 23.41 | 478.00 | 24.09 | 0.00 | 24.09 |
September | 61.00 | 23.27 | 326.00 | 23.97 | 0.17 | 23.97 |
October | 176.00 | 23.32 | 200.33 | 23.77 | 0.00 | 23.77 |
November | 290.67 | 23.07 | 76.33 | 23.29 | 4.33 | 23.30 |
December | 399.00 | 22.88 | 19.50 | 22.92 | 2.00 | 22.91 |
Annual Sum or Average | 2295.33 | 22.97 | 2449.50 | 23.55 | 19.17 | 23.54 |
Minimum of Months | 2.50 | 22.73 | 19.50 | 22.77 | 0.00 | 22.70 |
Maximum of Months | 399.00 | 23.41 | 478.00 | 24.12 | 12.67 | 24.12 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 320.50 | 23.18 | 39.17 | 23.31 | 0.00 | 23.31 |
February | 259.33 | 23.32 | 48.83 | 23.44 | 0.00 | 23.44 |
March | 211.00 | 23.24 | 125.00 | 23.58 | 0.00 | 23.58 |
April | 79.33 | 23.48 | 231.83 | 24.01 | 0.00 | 24.01 |
May | 92.83 | 23.45 | 233.50 | 24.00 | 0.00 | 24.00 |
June | 3.33 | 23.39 | 429.33 | 24.23 | 0.00 | 24.23 |
July | 0.00 | 0.00 | 491.50 | 24.29 | 0.00 | 24.29 |
August | 0.00 | 0.00 | 506.83 | 24.18 | 0.00 | 24.18 |
September | 26.00 | 23.40 | 374.00 | 24.16 | 0.00 | 24.16 |
October | 92.67 | 23.62 | 257.67 | 24.18 | 0.00 | 24.18 |
November | 238.50 | 23.57 | 93.00 | 23.78 | 0.00 | 23.78 |
December | 320.67 | 23.54 | 26.17 | 23.59 | 0.00 | 23.59 |
Annual Sum or Average | 1644.17 | 23.39 | 2856.83 | 23.93 | 0.00 | 23.93 |
Minimum of Months | 0.00 | 0.00 | 26.17 | 23.31 | 0.00 | 23.31 |
Maximum of Months | 320.67 | 23.62 | 506.83 | 24.29 | 0.00 | 24.29 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 250.17 | 23.02 | 91.17 | 23.44 | 0.00 | 23.44 |
February | 239.83 | 23.00 | 92.83 | 23.39 | 0.33 | 23.40 |
March | 226.17 | 22.99 | 178.17 | 23.57 | 3.17 | 23.60 |
April | 125.17 | 23.35 | 281.50 | 24.02 | 8.17 | 24.08 |
May | 114.33 | 23.48 | 284.67 | 24.14 | 9.33 | 24.21 |
June | 54.17 | 23.98 | 378.33 | 24.25 | 11.67 | 24.32 |
July | 33.17 | 26.02 | 453.17 | 24.47 | 25.33 | 24.59 |
August | 27.33 | 25.57 | 455.00 | 24.30 | 17.67 | 24.39 |
September | 61.50 | 23.78 | 365.67 | 24.22 | 10.67 | 24.28 |
October | 92.67 | 23.56 | 291.83 | 24.23 | 6.83 | 24.28 |
November | 217.00 | 23.26 | 133.83 | 23.69 | 0.50 | 23.69 |
December | 267.00 | 23.14 | 49.17 | 23.38 | 0.00 | 23.38 |
Annual Sum or Average | 1708.50 | 23.30 | 3055.33 | 23.97 | 93.67 | 24.03 |
Minimum of Months | 27.33 | 22.99 | 49.17 | 23.38 | 0.00 | 23.38 |
Maximum of Months | 267.00 | 26.02 | 455.00 | 24.47 | 25.33 | 24.59 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 148.33 | 23.56 | 240.33 | 24.17 | 12.83 | 24.26 |
February | 169.83 | 23.49 | 180.33 | 24.02 | 13.33 | 24.13 |
March | 182.33 | 23.34 | 217.17 | 23.87 | 9.50 | 23.94 |
April | 87.50 | 23.55 | 294.33 | 24.18 | 5.67 | 24.22 |
May | 134.50 | 23.27 | 224.50 | 23.88 | 0.00 | 23.88 |
June | 30.67 | 23.35 | 379.50 | 24.13 | 0.00 | 24.13 |
July | 3.83 | 26.52 | 477.17 | 24.30 | 3.67 | 24.32 |
August | 14.83 | 26.67 | 505.00 | 24.32 | 14.83 | 24.38 |
September | 39.83 | 25.38 | 418.17 | 24.48 | 23.17 | 24.59 |
October | 73.50 | 25.34 | 374.00 | 24.73 | 39.17 | 24.92 |
November | 104.17 | 24.29 | 293.67 | 24.50 | 21.00 | 24.63 |
December | 131.33 | 24.19 | 251.67 | 24.51 | 25.17 | 24.68 |
Annual Sum or Average | 1120.67 | 23.85 | 3855.83 | 24.27 | 168.33 | 24.36 |
Minimum of Months | 3.83 | 23.27 | 180.33 | 23.87 | 0.00 | 23.88 |
Maximum of Months | 182.33 | 26.67 | 505.00 | 24.73 | 39.17 | 24.92 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 179.00 | 23.23 | 176.00 | 23.85 | 0.17 | 23.85 |
February | 73.33 | 23.85 | 243.83 | 24.38 | 9.17 | 24.45 |
March | 36.33 | 24.42 | 378.00 | 24.47 | 10.17 | 24.53 |
April | 34.17 | 26.78 | 474.33 | 24.73 | 31.50 | 24.86 |
May | 48.83 | 24.90 | 398.67 | 24.52 | 21.50 | 24.63 |
June | 21.00 | 26.95 | 492.50 | 24.56 | 21.00 | 24.66 |
July | 56.00 | 27.00 | 497.00 | 24.86 | 56.00 | 25.05 |
August | 50.00 | 26.97 | 514.00 | 24.71 | 50.00 | 24.89 |
September | 21.50 | 26.69 | 464.00 | 24.55 | 20.17 | 24.64 |
October | 40.50 | 25.79 | 400.67 | 24.75 | 26.17 | 24.88 |
November | 30.83 | 25.34 | 333.00 | 24.72 | 14.33 | 24.81 |
December | 35.00 | 25.23 | 305.83 | 24.85 | 15.17 | 24.94 |
Annual Sum or Average | 626.50 | 24.95 | 4677.83 | 24.60 | 275.33 | 24.72 |
Minimum of Months | 21.00 | 23.23 | 176.00 | 23.85 | 0.17 | 23.85 |
Maximum of Months | 179.00 | 27.00 | 514.00 | 24.86 | 56.00 | 25.05 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 458.17 | 22.28 | 21.50 | 22.28 | 11.17 | 22.24 |
February | 404.67 | 22.44 | 5.67 | 22.45 | 1.67 | 22.44 |
March | 431.17 | 22.53 | 31.17 | 22.62 | 0.33 | 22.62 |
April | 299.83 | 22.87 | 77.83 | 23.10 | 0.00 | 23.10 |
May | 232.50 | 23.10 | 118.00 | 23.43 | 0.00 | 23.43 |
June | 86.50 | 23.25 | 302.00 | 23.91 | 0.00 | 23.91 |
July | 28.33 | 23.23 | 416.50 | 24.08 | 0.00 | 24.08 |
August | 50.67 | 23.14 | 379.83 | 23.95 | 0.00 | 23.95 |
September | 150.33 | 23.11 | 225.33 | 23.67 | 0.00 | 23.67 |
October | 246.17 | 23.10 | 133.17 | 23.48 | 0.00 | 23.48 |
November | 407.33 | 22.63 | 12.00 | 22.66 | 2.00 | 22.65 |
December | 484.33 | 22.37 | 6.67 | 22.35 | 6.67 | 22.33 |
Annual Sum or Average | 3280.00 | 22.65 | 1729.67 | 23.13 | 21.83 | 23.12 |
Minimum of Months | 28.33 | 22.28 | 5.67 | 22.28 | 0.00 | 22.24 |
Maximum of Months | 484.33 | 23.25 | 416.50 | 24.08 | 11.17 | 24.08 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 344.83 | 22.51 | 32.83 | 22.63 | 4.00 | 22.61 |
February | 298.33 | 22.41 | 33.33 | 22.63 | 0.00 | 22.63 |
March | 279.67 | 22.35 | 86.33 | 22.82 | 2.50 | 22.83 |
April | 183.33 | 22.89 | 172.67 | 23.65 | 5.50 | 23.70 |
May | 183.50 | 23.08 | 179.50 | 23.83 | 6.17 | 23.88 |
June | 114.67 | 23.44 | 250.00 | 24.08 | 12.67 | 24.17 |
July | 61.67 | 24.74 | 342.17 | 24.51 | 27.50 | 24.66 |
August | 62.83 | 24.23 | 337.00 | 24.30 | 20.17 | 24.42 |
September | 130.33 | 23.11 | 225.83 | 23.87 | 7.67 | 23.93 |
October | 162.83 | 23.04 | 165.50 | 23.78 | 4.17 | 23.82 |
November | 292.83 | 22.70 | 42.00 | 22.92 | 0.67 | 22.92 |
December | 363.00 | 22.57 | 10.67 | 22.62 | 1.83 | 22.61 |
Annual Sum or Average | 2477.83 | 22.79 | 1877.83 | 23.49 | 92.83 | 23.55 |
Minimum of Months | 61.67 | 22.35 | 10.67 | 22.62 | 0.00 | 22.61 |
Maximum of Months | 363.00 | 24.74 | 342.17 | 24.51 | 27.50 | 24.66 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 193.00 | 23.28 | 219.50 | 23.97 | 15.00 | 24.08 |
February | 225.33 | 23.04 | 150.67 | 23.67 | 15.00 | 23.80 |
March | 258.33 | 22.83 | 168.33 | 23.42 | 8.67 | 23.49 |
April | 176.67 | 22.99 | 212.00 | 23.73 | 1.17 | 23.74 |
May | 216.17 | 23.04 | 171.17 | 23.57 | 0.00 | 23.57 |
June | 116.00 | 23.20 | 278.67 | 23.85 | 0.00 | 23.85 |
July | 37.50 | 23.42 | 396.17 | 24.14 | 2.00 | 24.15 |
August | 25.67 | 23.81 | 435.50 | 24.18 | 4.50 | 24.20 |
September | 77.83 | 24.21 | 376.33 | 24.34 | 21.83 | 24.45 |
October | 120.17 | 24.50 | 333.67 | 24.59 | 40.33 | 24.78 |
November | 174.17 | 23.70 | 240.00 | 24.24 | 20.50 | 24.37 |
December | 204.50 | 23.58 | 219.67 | 24.20 | 23.67 | 24.36 |
Annual Sum or Average | 1825.33 | 23.33 | 3201.67 | 24.00 | 152.67 | 24.09 |
Minimum of Months | 25.67 | 22.83 | 150.67 | 23.42 | 0.00 | 23.49 |
Maximum of Months | 258.33 | 24.50 | 435.50 | 24.59 | 40.33 | 24.78 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 378.83 | 22.41 | 56.83 | 22.63 | 1.00 | 22.63 |
February | 330.00 | 22.54 | 74.67 | 22.87 | 0.33 | 22.88 |
March | 339.83 | 22.61 | 109.50 | 23.00 | 2.00 | 23.02 |
April | 171.33 | 23.21 | 228.50 | 23.89 | 16.00 | 24.01 |
May | 176.17 | 23.34 | 250.67 | 23.97 | 16.67 | 24.08 |
June | 68.17 | 23.83 | 376.83 | 24.22 | 14.67 | 24.31 |
July | 35.33 | 26.38 | 458.67 | 24.53 | 30.33 | 24.67 |
August | 28.83 | 25.54 | 468.33 | 24.34 | 18.50 | 24.43 |
September | 84.33 | 23.67 | 353.33 | 24.19 | 14.50 | 24.28 |
October | 177.33 | 23.39 | 247.67 | 23.99 | 15.33 | 24.09 |
November | 313.83 | 22.76 | 104.83 | 23.15 | 0.00 | 23.15 |
December | 379.33 | 22.58 | 46.83 | 22.77 | 0.00 | 22.77 |
Annual Sum or Average | 2483.33 | 22.89 | 2776.67 | 23.65 | 129.33 | 23.73 |
Minimum of Months | 28.83 | 22.41 | 46.83 | 22.63 | 0.00 | 22.63 |
Maximum of Months | 379.33 | 26.38 | 468.33 | 24.53 | 30.33 | 24.67 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 480.50 | 21.60 | 96.33 | 21.36 | 96.00 | 21.19 |
February | 430.17 | 21.79 | 41.50 | 21.67 | 39.83 | 21.57 |
March | 461.67 | 21.96 | 57.17 | 21.96 | 33.83 | 21.87 |
April | 334.00 | 22.46 | 81.83 | 22.72 | 5.50 | 22.69 |
May | 288.33 | 22.67 | 109.33 | 23.04 | 0.83 | 23.03 |
June | 141.17 | 23.05 | 261.00 | 23.72 | 0.00 | 23.72 |
July | 57.00 | 23.06 | 372.33 | 24.00 | 0.00 | 24.00 |
August | 110.00 | 23.07 | 340.33 | 23.82 | 0.00 | 23.82 |
September | 218.17 | 22.84 | 197.33 | 23.40 | 0.00 | 23.40 |
October | 292.83 | 22.67 | 122.33 | 23.09 | 2.33 | 23.08 |
November | 467.33 | 22.12 | 40.50 | 22.03 | 34.67 | 21.92 |
December | 492.17 | 21.64 | 94.00 | 21.42 | 94.00 | 21.27 |
Annual Sum or Average | 3773.33 | 22.17 | 1814.00 | 22.58 | 307.00 | 22.46 |
Minimum of Months | 57.00 | 21.60 | 40.50 | 21.36 | 0.00 | 21.19 |
Maximum of Months | 492.17 | 23.07 | 372.33 | 24.00 | 96.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 441.33 | 22.11 | 63.83 | 22.05 | 41.83 | 21.92 |
February | 364.50 | 22.00 | 47.67 | 22.10 | 15.17 | 22.04 |
March | 349.50 | 22.02 | 98.00 | 22.38 | 13.83 | 22.32 |
April | 204.50 | 22.49 | 228.67 | 23.44 | 5.17 | 23.46 |
May | 214.83 | 22.66 | 214.00 | 23.52 | 2.33 | 23.54 |
June | 134.00 | 23.15 | 301.83 | 23.92 | 10.00 | 23.98 |
July | 78.17 | 24.47 | 408.67 | 24.40 | 31.33 | 24.55 |
August | 82.83 | 23.95 | 403.00 | 24.21 | 22.33 | 24.32 |
September | 164.67 | 22.83 | 269.33 | 23.68 | 5.83 | 23.72 |
October | 208.67 | 22.77 | 177.67 | 23.51 | 3.50 | 23.54 |
November | 387.67 | 22.44 | 36.83 | 22.49 | 11.00 | 22.44 |
December | 475.00 | 22.22 | 30.50 | 22.13 | 26.67 | 22.04 |
Annual Sum or Average | 3105.67 | 22.44 | 2280.00 | 23.15 | 189.00 | 23.15 |
Minimum of Months | 78.17 | 22.00 | 30.50 | 22.05 | 2.33 | 21.92 |
Maximum of Months | 475.00 | 24.47 | 408.67 | 24.40 | 41.83 | 24.55 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 251.50 | 22.52 | 193.50 | 23.20 | 26.67 | 23.16 |
February | 265.83 | 22.30 | 132.00 | 22.93 | 19.33 | 22.95 |
March | 323.67 | 22.31 | 147.83 | 22.78 | 25.83 | 22.75 |
April | 222.67 | 22.52 | 199.83 | 23.35 | 4.33 | 23.33 |
May | 266.67 | 22.57 | 146.50 | 23.13 | 1.83 | 23.11 |
June | 168.17 | 22.92 | 248.00 | 23.62 | 0.00 | 23.62 |
July | 83.67 | 23.18 | 356.67 | 24.01 | 3.17 | 24.03 |
August | 80.50 | 23.37 | 392.50 | 24.05 | 8.00 | 24.09 |
September | 122.33 | 23.42 | 325.33 | 24.09 | 16.67 | 24.19 |
October | 161.17 | 23.77 | 296.33 | 24.30 | 35.33 | 24.49 |
November | 227.33 | 22.92 | 207.33 | 23.66 | 18.33 | 23.71 |
December | 250.17 | 22.76 | 192.33 | 23.43 | 27.50 | 23.43 |
Annual Sum or Average | 2423.67 | 22.74 | 2838.17 | 23.55 | 187.00 | 23.58 |
Minimum of Months | 80.50 | 22.30 | 132.00 | 22.78 | 0.00 | 22.75 |
Maximum of Months | 323.67 | 23.77 | 392.50 | 24.30 | 35.33 | 24.49 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 415.00 | 21.88 | 87.33 | 21.93 | 44.83 | 21.81 |
February | 358.17 | 21.96 | 76.17 | 22.23 | 16.00 | 22.17 |
March | 387.50 | 22.12 | 102.50 | 22.47 | 14.33 | 22.45 |
April | 232.00 | 22.81 | 195.33 | 23.54 | 15.67 | 23.66 |
May | 234.17 | 22.89 | 209.67 | 23.61 | 16.00 | 23.73 |
June | 115.00 | 23.38 | 333.67 | 24.04 | 15.50 | 24.14 |
July | 61.83 | 24.91 | 428.33 | 24.45 | 30.50 | 24.59 |
August | 63.33 | 24.16 | 429.50 | 24.24 | 19.67 | 24.34 |
September | 137.33 | 23.18 | 295.00 | 23.94 | 13.50 | 24.03 |
October | 226.17 | 22.94 | 216.67 | 23.65 | 13.50 | 23.75 |
November | 358.17 | 22.24 | 101.17 | 22.56 | 17.17 | 22.50 |
December | 412.83 | 22.02 | 63.67 | 22.04 | 35.50 | 21.94 |
Annual Sum or Average | 3001.50 | 22.44 | 2539.00 | 23.22 | 252.17 | 23.24 |
Minimum of Months | 61.83 | 21.88 | 63.67 | 21.93 | 13.50 | 21.81 |
Maximum of Months | 415.00 | 24.91 | 429.50 | 24.45 | 44.83 | 24.59 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 27.00 | 502.00 | 27.00 | 0.83 | 27.00 |
February | 18.83 | 27.00 | 454.00 | 27.00 | 18.83 | 27.00 |
March | 62.50 | 27.00 | 514.00 | 27.00 | 62.50 | 27.00 |
April | 249.83 | 27.00 | 485.00 | 27.00 | 249.83 | 27.00 |
May | 0.17 | 27.00 | 508.00 | 27.00 | 0.17 | 27.00 |
June | 73.83 | 27.00 | 496.00 | 27.00 | 73.83 | 27.00 |
July | 232.00 | 27.00 | 497.00 | 27.00 | 232.00 | 27.00 |
August | 341.50 | 27.00 | 514.00 | 27.00 | 341.50 | 27.00 |
September | 28.00 | 27.00 | 485.00 | 27.00 | 28.00 | 27.00 |
October | 53.67 | 27.00 | 502.00 | 27.00 | 53.67 | 27.00 |
November | 72.33 | 27.00 | 489.00 | 27.00 | 72.33 | 27.00 |
December | 100.00 | 27.01 | 497.00 | 27.00 | 100.00 | 27.00 |
Annual Sum or Average | 1233.50 | 27.00 | 5943.00 | 27.00 | 1233.50 | 27.00 |
Minimum of Months | 0.17 | 27.00 | 454.00 | 27.00 | 0.17 | 27.00 |
Maximum of Months | 341.50 | 27.01 | 514.00 | 27.00 | 341.50 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.50 | 27.00 | 454.00 | 27.00 | 0.50 | 27.00 |
March | 2.67 | 27.00 | 514.00 | 27.00 | 2.67 | 27.00 |
April | 12.67 | 27.00 | 485.00 | 27.00 | 12.67 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 0.00 | 0.00 | 496.00 | 27.00 | 0.00 | 27.00 |
July | 5.00 | 27.00 | 497.00 | 27.00 | 5.00 | 27.00 |
August | 64.17 | 27.00 | 514.00 | 27.00 | 64.17 | 27.00 |
September | 1.83 | 27.00 | 485.00 | 27.00 | 1.83 | 27.00 |
October | 4.00 | 27.00 | 502.00 | 27.00 | 4.00 | 27.00 |
November | 3.17 | 27.00 | 489.00 | 27.00 | 3.17 | 27.00 |
December | 1.83 | 27.00 | 497.00 | 27.00 | 1.83 | 27.00 |
Annual Sum or Average | 95.83 | 27.00 | 5943.00 | 27.00 | 95.83 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 64.17 | 27.00 | 514.00 | 27.00 | 64.17 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.67 | 25.89 | 486.17 | 26.99 | 0.00 | 26.99 |
February | 0.50 | 27.00 | 448.00 | 27.00 | 0.50 | 27.00 |
March | 4.83 | 27.00 | 514.00 | 27.00 | 4.83 | 27.00 |
April | 36.67 | 27.00 | 485.00 | 27.00 | 36.67 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 3.67 | 27.00 | 496.00 | 27.00 | 3.67 | 27.00 |
July | 64.00 | 27.00 | 497.00 | 27.00 | 64.00 | 27.00 |
August | 107.67 | 27.00 | 514.00 | 27.00 | 107.67 | 27.00 |
September | 5.50 | 27.00 | 485.00 | 27.00 | 5.50 | 27.00 |
October | 8.00 | 27.00 | 502.00 | 27.00 | 8.00 | 27.00 |
November | 1.83 | 27.00 | 489.00 | 27.00 | 1.83 | 27.00 |
December | 1.17 | 27.00 | 497.00 | 27.00 | 1.17 | 27.00 |
Annual Sum or Average | 236.50 | 26.99 | 5921.17 | 27.00 | 233.83 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 448.00 | 26.99 | 0.00 | 26.99 |
Maximum of Months | 107.67 | 27.00 | 514.00 | 27.00 | 107.67 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 474.83 | 27.00 | 502.00 | 27.00 | 474.83 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.01 | 485.00 | 27.01 | 485.00 | 27.01 |
May | 498.33 | 27.00 | 508.00 | 27.00 | 498.33 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
August | 514.00 | 27.17 | 514.00 | 27.17 | 514.00 | 27.17 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5906.17 | 27.02 | 5943.00 | 27.02 | 5906.17 | 27.02 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 27.17 | 514.00 | 27.17 | 514.00 | 27.17 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00029 | 32.15452 | 0.88948 | 21.78999 |
February | 454.00000 | 27.00036 | 32.96235 | 0.93432 | 23.51444 |
March | 514.00000 | 27.00030 | 34.34857 | 0.98319 | 25.46355 |
April | 485.00000 | 27.00015 | 35.15820 | 1.03867 | 27.81720 |
May | 508.00000 | 27.00067 | 36.31591 | 0.27349 | 6.63030 |
June | 496.00000 | 27.00094 | 36.74340 | 0.34417 | 7.52425 |
July | 497.00000 | 27.00073 | 37.16272 | 0.40559 | 8.48557 |
August | 514.00000 | 27.00024 | 37.16742 | 0.44494 | 9.19094 |
September | 485.00000 | 27.00114 | 37.61212 | 0.30278 | 6.98235 |
October | 502.00000 | 27.00061 | 34.09221 | 0.97337 | 25.06844 |
November | 489.00000 | 27.00023 | 31.94797 | 0.97436 | 25.13149 |
December | 497.00000 | 27.00425 | 29.57560 | 0.98123 | 25.41151 |
Annual Sum or Average | 5943.00000 | 27.00083 | 34.61859 | 0.70997 | 17.68889 |
Minimum of Months | 454.00000 | 27.00015 | 29.57560 | 0.27349 | 6.63030 |
Maximum of Months | 514.00000 | 27.00425 | 37.61212 | 1.03867 | 27.81720 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00027 | 32.21722 | 0.81343 | 19.08266 |
February | 454.00000 | 27.00034 | 32.98946 | 0.84140 | 20.04947 |
March | 514.00000 | 27.00029 | 34.34046 | 0.87370 | 21.20013 |
April | 485.00000 | 27.00016 | 35.14398 | 0.92524 | 23.16726 |
May | 508.00000 | 27.00064 | 36.40887 | 0.19838 | 5.93512 |
June | 496.00000 | 27.00090 | 36.78835 | 0.24953 | 6.39076 |
July | 497.00000 | 27.00076 | 37.19074 | 0.29099 | 6.84662 |
August | 514.00000 | 27.00026 | 37.18131 | 0.31334 | 7.13671 |
September | 485.00000 | 27.00090 | 37.78201 | 0.22841 | 6.19701 |
October | 502.00000 | 27.00057 | 34.12607 | 0.89514 | 21.99719 |
November | 489.00000 | 27.00023 | 31.93524 | 0.86316 | 20.84181 |
December | 497.00000 | 27.00132 | 29.55987 | 0.84190 | 20.06241 |
Annual Sum or Average | 5943.00000 | 27.00055 | 34.65370 | 0.60896 | 14.85473 |
Minimum of Months | 454.00000 | 27.00016 | 29.55987 | 0.19838 | 5.93512 |
Maximum of Months | 514.00000 | 27.00132 | 37.78201 | 0.92524 | 23.16726 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.98049 | 32.41755 | 0.75443 | 17.27162 |
February | 454.00000 | 27.00034 | 33.03177 | 0.79131 | 18.40804 |
March | 514.00000 | 27.00030 | 34.36114 | 0.83112 | 19.75130 |
April | 485.00000 | 27.00018 | 35.15362 | 0.90359 | 22.41452 |
May | 508.00000 | 27.00064 | 36.45477 | 0.16955 | 5.86345 |
June | 496.00000 | 27.00092 | 36.79352 | 0.23980 | 6.39679 |
July | 497.00000 | 27.00077 | 37.18983 | 0.29324 | 6.95796 |
August | 514.00000 | 27.00029 | 37.18383 | 0.31161 | 7.20234 |
September | 485.00000 | 27.00096 | 37.82800 | 0.20948 | 6.12906 |
October | 502.00000 | 27.00057 | 34.13968 | 0.87341 | 21.24557 |
November | 489.00000 | 27.00024 | 31.95335 | 0.81742 | 19.29301 |
December | 497.00000 | 27.00011 | 29.56814 | 0.78447 | 18.15836 |
Annual Sum or Average | 5943.00000 | 26.99880 | 34.68801 | 0.57951 | 14.04328 |
Minimum of Months | 454.00000 | 26.98049 | 29.56814 | 0.16955 | 5.86345 |
Maximum of Months | 514.00000 | 27.00096 | 37.82800 | 0.90359 | 22.41452 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99995 | 32.11727 | 1.09165 | 30.17831 |
February | 454.00000 | 26.99988 | 32.65764 | 1.23626 | 37.08582 |
March | 514.00000 | 27.00162 | 34.55037 | 1.39594 | 45.30885 |
April | 485.00000 | 27.01007 | 35.34347 | 1.54112 | 53.14164 |
May | 508.00000 | 26.99983 | 36.76645 | 0.52615 | 10.87124 |
June | 496.00000 | 27.00219 | 41.98095 | 0.79034 | 18.21291 |
July | 497.00000 | 27.00819 | 45.19946 | 1.03321 | 27.57000 |
August | 514.00000 | 27.17190 | 42.39185 | 1.24791 | 37.73963 |
September | 485.00000 | 26.99996 | 44.71295 | 0.62808 | 13.36422 |
October | 502.00000 | 27.00144 | 37.69089 | 1.31037 | 40.88630 |
November | 489.00000 | 27.00164 | 31.34633 | 1.39192 | 45.12660 |
December | 497.00000 | 27.00253 | 27.32487 | 1.48429 | 50.06317 |
Annual Sum or Average | 5943.00000 | 27.01713 | 36.87006 | 1.13902 | 34.10070 |
Minimum of Months | 454.00000 | 26.99983 | 27.32487 | 0.52615 | 10.87124 |
Maximum of Months | 514.00000 | 27.17190 | 45.19946 | 1.54112 | 53.14164 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.76046 | 36.48472 | 0.53319 | 12.39108 |
February | 454.00000 | 24.64450 | 38.02587 | 0.50784 | 11.09763 |
March | 514.00000 | 24.55804 | 40.43818 | 0.50974 | 10.95737 |
April | 485.00000 | 24.65202 | 43.88518 | 0.55660 | 12.04882 |
May | 508.00000 | 24.60670 | 43.47837 | -0.3076 | 7.96554 |
June | 496.00000 | 24.57574 | 49.16723 | -0.2689 | 7.45720 |
July | 497.00000 | 24.89094 | 56.44821 | -0.1129 | 7.24541 |
August | 514.00000 | 24.81953 | 58.06842 | -0.1139 | 7.79185 |
September | 485.00000 | 25.07291 | 54.82309 | -0.0719 | 8.89763 |
October | 502.00000 | 25.20369 | 44.37069 | 0.70200 | 18.15835 |
November | 489.00000 | 24.76784 | 36.17185 | 0.53744 | 12.07814 |
December | 497.00000 | 24.75814 | 31.87060 | 0.50262 | 11.36968 |
Annual Sum or Average | 5943.00000 | 24.77606 | 44.49192 | 0.24500 | 10.61306 |
Minimum of Months | 454.00000 | 24.55804 | 31.87060 | -0.3076 | 7.24541 |
Maximum of Months | 514.00000 | 25.20369 | 58.06842 | 0.70200 | 18.15835 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.34362 | 36.34879 | 0.44076 | 9.45263 |
February | 454.00000 | 24.30716 | 38.90309 | 0.45383 | 9.61981 |
March | 514.00000 | 24.28989 | 41.82606 | 0.47931 | 10.07586 |
April | 485.00000 | 24.29523 | 45.26380 | 0.51670 | 10.81778 |
May | 508.00000 | 24.25380 | 45.10980 | -0.3812 | 8.38906 |
June | 496.00000 | 24.27649 | 51.27136 | -0.3130 | 7.43080 |
July | 497.00000 | 24.29359 | 55.14853 | -0.2651 | 6.78174 |
August | 514.00000 | 24.23036 | 56.05673 | -0.2680 | 6.73893 |
September | 485.00000 | 24.31311 | 52.52858 | -0.2947 | 7.30350 |
October | 502.00000 | 24.37375 | 42.44441 | 0.51861 | 11.13759 |
November | 489.00000 | 24.38610 | 36.93250 | 0.47448 | 10.21477 |
December | 497.00000 | 24.37504 | 31.70715 | 0.43713 | 9.43487 |
Annual Sum or Average | 5943.00000 | 24.31116 | 44.51134 | 0.14682 | 8.94116 |
Minimum of Months | 454.00000 | 24.23036 | 31.70715 | -0.3812 | 6.73893 |
Maximum of Months | 514.00000 | 24.38610 | 56.05673 | 0.51861 | 11.13759 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.96663 | 39.64246 | 0.33849 | 7.78463 |
February | 454.00000 | 23.95145 | 40.73605 | 0.34464 | 7.73029 |
March | 514.00000 | 23.98468 | 43.59860 | 0.37514 | 8.15114 |
April | 485.00000 | 24.01202 | 46.75731 | 0.41372 | 8.83666 |
May | 508.00000 | 24.08086 | 46.04932 | -0.4709 | 9.94826 |
June | 496.00000 | 24.12624 | 52.21773 | -0.4007 | 8.63254 |
July | 497.00000 | 24.13652 | 56.46106 | -0.3622 | 7.97226 |
August | 514.00000 | 24.12419 | 57.41513 | -0.3532 | 7.80490 |
September | 485.00000 | 24.12989 | 53.53557 | -0.3913 | 8.50775 |
October | 502.00000 | 24.12984 | 43.90783 | 0.43081 | 9.21068 |
November | 489.00000 | 24.06695 | 38.78872 | 0.36685 | 8.22625 |
December | 497.00000 | 23.93377 | 33.78745 | 0.29641 | 7.17380 |
Annual Sum or Average | 5943.00000 | 24.05427 | 46.12380 | 0.04603 | 8.33591 |
Minimum of Months | 454.00000 | 23.93377 | 33.78745 | -0.4709 | 7.17380 |
Maximum of Months | 514.00000 | 24.13652 | 57.41513 | 0.43081 | 9.94826 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.05321 | 41.94852 | 0.10066 | 6.52751 |
February | 454.00000 | 23.18475 | 43.36912 | 0.14924 | 6.47171 |
March | 514.00000 | 23.39164 | 45.75904 | 0.22105 | 6.82254 |
April | 485.00000 | 23.69325 | 47.93053 | 0.33400 | 7.94326 |
May | 508.00000 | 23.77341 | 47.16523 | -0.5792 | 12.91001 |
June | 496.00000 | 23.98731 | 52.76857 | -0.4443 | 9.50558 |
July | 497.00000 | 24.08401 | 56.67476 | -0.3710 | 8.08684 |
August | 514.00000 | 24.05318 | 57.74003 | -0.3709 | 8.06876 |
September | 485.00000 | 23.92402 | 54.51448 | -0.4623 | 9.92023 |
October | 502.00000 | 23.83984 | 45.14977 | 0.35642 | 8.23203 |
November | 489.00000 | 23.45931 | 41.04278 | 0.20772 | 6.87981 |
December | 497.00000 | 23.10228 | 36.53573 | 0.08316 | 6.20281 |
Annual Sum or Average | 5943.00000 | 23.63200 | 47.58976 | -0.0670 | 8.14481 |
Minimum of Months | 454.00000 | 23.05321 | 36.53573 | -0.5792 | 6.20281 |
Maximum of Months | 514.00000 | 24.08401 | 57.74003 | 0.35642 | 12.91001 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.52776 | 37.66497 | 0.20364 | 6.56881 |
February | 454.00000 | 23.62286 | 39.98056 | 0.24825 | 6.72829 |
March | 514.00000 | 23.72944 | 42.76298 | 0.30102 | 7.43754 |
April | 485.00000 | 24.00097 | 45.58263 | 0.41003 | 8.75511 |
May | 508.00000 | 24.00114 | 45.11183 | -0.4981 | 10.68142 |
June | 496.00000 | 24.18243 | 50.82831 | -0.3640 | 8.08647 |
July | 497.00000 | 24.28285 | 54.61114 | -0.2825 | 7.02605 |
August | 514.00000 | 24.17407 | 55.74035 | -0.3151 | 7.33981 |
September | 485.00000 | 24.10038 | 52.60151 | -0.4028 | 8.83073 |
October | 502.00000 | 24.12855 | 42.61851 | 0.42787 | 9.38904 |
November | 489.00000 | 23.84440 | 37.82273 | 0.29715 | 7.31067 |
December | 497.00000 | 23.73311 | 32.62043 | 0.23041 | 6.46486 |
Annual Sum or Average | 5943.00000 | 23.94594 | 44.87305 | 0.01881 | 7.89284 |
Minimum of Months | 454.00000 | 23.52776 | 32.62043 | -0.4981 | 6.46486 |
Maximum of Months | 514.00000 | 24.28285 | 55.74035 | 0.42787 | 10.68142 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.62705 | 36.78130 | 0.26001 | 7.36830 |
February | 454.00000 | 23.55040 | 39.69440 | 0.26304 | 7.33071 |
March | 514.00000 | 23.63020 | 42.60640 | 0.31373 | 8.18319 |
April | 485.00000 | 23.94717 | 45.42482 | 0.44836 | 10.10325 |
May | 508.00000 | 24.03757 | 44.69580 | -0.4264 | 10.46932 |
June | 496.00000 | 24.10714 | 50.83935 | -0.3346 | 8.67671 |
July | 497.00000 | 24.27456 | 54.36208 | -0.2145 | 7.49377 |
August | 514.00000 | 24.12835 | 55.57184 | -0.2537 | 7.69656 |
September | 485.00000 | 24.07528 | 52.32989 | -0.3481 | 8.89667 |
October | 502.00000 | 24.11637 | 42.33759 | 0.46103 | 10.31569 |
November | 489.00000 | 23.76384 | 37.60417 | 0.30883 | 7.74283 |
December | 497.00000 | 23.61054 | 32.40926 | 0.23258 | 6.85660 |
Annual Sum or Average | 5943.00000 | 23.90804 | 44.59855 | 0.05691 | 8.43397 |
Minimum of Months | 454.00000 | 23.55040 | 32.40926 | -0.4264 | 6.85660 |
Maximum of Months | 514.00000 | 24.27456 | 55.57184 | 0.46103 | 10.46932 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.06336 | 35.62434 | 0.41991 | 10.06063 |
February | 454.00000 | 23.93129 | 38.78971 | 0.38472 | 9.42819 |
March | 514.00000 | 23.84955 | 41.97054 | 0.37431 | 9.13970 |
April | 485.00000 | 24.10717 | 45.04296 | 0.47047 | 10.39363 |
May | 508.00000 | 23.90896 | 45.30025 | -0.5198 | 11.66037 |
June | 496.00000 | 24.08385 | 51.14560 | -0.4019 | 8.81750 |
July | 497.00000 | 24.26605 | 54.63838 | -0.2842 | 7.25196 |
August | 514.00000 | 24.23836 | 55.32199 | -0.2503 | 7.05094 |
September | 485.00000 | 24.29739 | 51.60093 | -0.2560 | 7.79460 |
October | 502.00000 | 24.43123 | 41.51109 | 0.57540 | 13.26712 |
November | 489.00000 | 24.27950 | 36.24194 | 0.48856 | 11.18004 |
December | 497.00000 | 24.26522 | 30.88756 | 0.45741 | 10.77405 |
Annual Sum or Average | 5943.00000 | 24.14379 | 44.05563 | 0.11840 | 9.73534 |
Minimum of Months | 454.00000 | 23.84955 | 30.88756 | -0.5198 | 7.05094 |
Maximum of Months | 514.00000 | 24.43123 | 55.32199 | 0.57540 | 13.26712 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.89227 | 35.92941 | 0.34935 | 8.41098 |
February | 454.00000 | 24.19842 | 37.73105 | 0.45859 | 10.15076 |
March | 514.00000 | 24.31597 | 40.37023 | 0.53496 | 11.74355 |
April | 485.00000 | 24.56547 | 43.45203 | 0.68249 | 15.79359 |
May | 508.00000 | 24.30298 | 43.73112 | -0.2771 | 8.29124 |
June | 496.00000 | 24.45395 | 49.51883 | -0.1185 | 6.71816 |
July | 497.00000 | 24.61549 | 53.08618 | 0.01632 | 6.96624 |
August | 514.00000 | 24.49090 | 54.12417 | 0.00836 | 6.66777 |
September | 485.00000 | 24.41682 | 51.02940 | -0.1667 | 7.05558 |
October | 502.00000 | 24.50256 | 41.07069 | 0.60446 | 13.73843 |
November | 489.00000 | 24.46729 | 35.49384 | 0.53794 | 11.92780 |
December | 497.00000 | 24.49138 | 30.12990 | 0.51154 | 11.31553 |
Annual Sum or Average | 5943.00000 | 24.39325 | 43.02022 | 0.25952 | 9.88316 |
Minimum of Months | 454.00000 | 23.89227 | 30.12990 | -0.2771 | 6.66777 |
Maximum of Months | 514.00000 | 24.61549 | 54.12417 | 0.68249 | 15.79359 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.42184 | 40.27097 | -0.0696 | 6.46625 |
February | 454.00000 | 22.59941 | 42.98573 | -0.0057 | 6.03237 |
March | 514.00000 | 22.75486 | 45.90614 | 0.05325 | 6.25111 |
April | 485.00000 | 23.28502 | 48.18229 | 0.21606 | 6.77018 |
May | 508.00000 | 23.59431 | 46.63477 | -0.6607 | 15.15391 |
June | 496.00000 | 23.90937 | 52.09952 | -0.4887 | 10.46955 |
July | 497.00000 | 24.03808 | 56.17276 | -0.4029 | 8.71854 |
August | 514.00000 | 23.89978 | 57.76210 | -0.4472 | 9.55365 |
September | 485.00000 | 23.70385 | 54.33107 | -0.5636 | 12.37371 |
October | 502.00000 | 23.58587 | 44.61115 | 0.27653 | 7.45828 |
November | 489.00000 | 22.84918 | 40.79883 | 0.04500 | 6.14198 |
December | 497.00000 | 22.40990 | 35.66098 | -0.0981 | 6.21194 |
Annual Sum or Average | 5943.00000 | 23.25912 | 47.15710 | -0.1809 | 8.48935 |
Minimum of Months | 454.00000 | 22.40990 | 35.66098 | -0.6607 | 6.03237 |
Maximum of Months | 514.00000 | 24.03808 | 57.76210 | 0.27653 | 15.15391 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.82602 | 38.73043 | 0.05212 | 6.45907 |
February | 385.00000 | 22.81253 | 41.67045 | 0.07294 | 6.52171 |
March | 433.00000 | 22.99076 | 43.99611 | 0.14046 | 7.26348 |
April | 410.00000 | 23.63626 | 46.34592 | 0.34804 | 9.05634 |
May | 430.00000 | 23.78128 | 45.42000 | -0.5413 | 13.81132 |
June | 418.00000 | 23.93854 | 51.40598 | -0.4221 | 10.85990 |
July | 422.00000 | 24.24924 | 54.86346 | -0.2566 | 8.66125 |
August | 433.00000 | 24.08635 | 56.41630 | -0.2996 | 8.84688 |
September | 410.00000 | 23.78203 | 53.35157 | -0.4783 | 11.84046 |
October | 427.00000 | 23.76372 | 43.91922 | 0.35521 | 8.81598 |
November | 417.00000 | 23.13185 | 39.39189 | 0.14035 | 6.58028 |
December | 422.00000 | 22.79410 | 34.11965 | 0.01921 | 6.10660 |
Annual Sum or Average | 5034.00000 | 23.48690 | 45.82532 | -0.0737 | 8.74674 |
Minimum of Months | 385.00000 | 22.79410 | 34.11965 | -0.5413 | 6.10660 |
Maximum of Months | 433.00000 | 24.24924 | 56.41630 | 0.35521 | 13.81132 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.88853 | 36.12050 | 0.37476 | 9.93781 |
February | 454.00000 | 23.62274 | 39.81874 | 0.30584 | 9.04012 |
March | 514.00000 | 23.46327 | 43.28491 | 0.27009 | 8.45963 |
April | 485.00000 | 23.76762 | 46.27842 | 0.37039 | 9.09621 |
May | 508.00000 | 23.65631 | 46.24779 | -0.6233 | 14.64511 |
June | 496.00000 | 23.84863 | 52.23595 | -0.5054 | 11.05308 |
July | 497.00000 | 24.06335 | 55.98624 | -0.3822 | 8.72159 |
August | 514.00000 | 24.08835 | 56.70406 | -0.3317 | 8.15409 |
September | 485.00000 | 24.17005 | 52.19867 | -0.3145 | 8.88519 |
October | 502.00000 | 24.29816 | 42.19439 | 0.53115 | 12.58317 |
November | 489.00000 | 24.06518 | 37.00779 | 0.42732 | 10.56050 |
December | 497.00000 | 24.02184 | 31.56160 | 0.38680 | 10.27128 |
Annual Sum or Average | 5943.00000 | 23.91356 | 45.02078 | 0.03920 | 10.12885 |
Minimum of Months | 454.00000 | 23.46327 | 31.56160 | -0.6233 | 8.15409 |
Maximum of Months | 514.00000 | 24.29816 | 56.70406 | 0.53115 | 14.64511 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.82359 | 38.45791 | 0.06491 | 6.74462 |
February | 454.00000 | 22.97868 | 41.12872 | 0.12869 | 6.94390 |
March | 514.00000 | 23.10089 | 43.97981 | 0.18517 | 7.42943 |
April | 485.00000 | 23.79316 | 46.01275 | 0.40864 | 10.11888 |
May | 508.00000 | 23.86541 | 45.25912 | -0.4799 | 12.50890 |
June | 496.00000 | 24.08132 | 51.07455 | -0.3276 | 8.95807 |
July | 497.00000 | 24.31552 | 54.77934 | -0.1935 | 7.58202 |
August | 514.00000 | 24.18164 | 56.17323 | -0.2295 | 7.59526 |
September | 485.00000 | 24.04600 | 52.57389 | -0.3486 | 9.43776 |
October | 502.00000 | 23.88055 | 43.19383 | 0.40181 | 9.87100 |
November | 489.00000 | 23.26276 | 38.76925 | 0.19098 | 7.24692 |
December | 497.00000 | 22.94662 | 33.63577 | 0.07112 | 6.55999 |
Annual Sum or Average | 5943.00000 | 23.61026 | 45.46187 | -0.0126 | 8.42525 |
Minimum of Months | 454.00000 | 22.82359 | 33.63577 | -0.4799 | 6.55999 |
Maximum of Months | 514.00000 | 24.31552 | 56.17323 | 0.40864 | 12.50890 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.69605 | 41.94931 | -0.2627 | 8.74365 |
February | 454.00000 | 21.90079 | 44.83966 | -0.1860 | 7.45271 |
March | 514.00000 | 22.16342 | 47.52538 | -0.0995 | 7.02523 |
April | 485.00000 | 22.92826 | 49.22846 | 0.12811 | 6.84795 |
May | 508.00000 | 23.24330 | 47.67399 | -0.7807 | 19.91308 |
June | 496.00000 | 23.74689 | 52.64425 | -0.5411 | 12.15929 |
July | 497.00000 | 23.95807 | 56.46189 | -0.4227 | 9.42804 |
August | 514.00000 | 23.79614 | 58.18714 | -0.4768 | 10.53100 |
September | 485.00000 | 23.45539 | 55.30717 | -0.6473 | 15.27943 |
October | 502.00000 | 23.25512 | 45.61814 | 0.19388 | 7.38492 |
November | 489.00000 | 22.19986 | 42.39774 | -0.1217 | 7.08955 |
December | 497.00000 | 21.66283 | 37.41773 | -0.2932 | 8.48872 |
Annual Sum or Average | 5943.00000 | 22.84084 | 48.30434 | -0.2940 | 10.05452 |
Minimum of Months | 454.00000 | 21.66283 | 37.41773 | -0.7807 | 6.84795 |
Maximum of Months | 514.00000 | 23.95807 | 58.18714 | 0.19388 | 19.91308 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.33131 | 39.89397 | -0.0822 | 7.20440 |
February | 454.00000 | 22.39871 | 43.08066 | -0.0394 | 7.03905 |
March | 514.00000 | 22.67294 | 45.46135 | 0.05688 | 7.50378 |
April | 485.00000 | 23.47693 | 46.97450 | 0.31500 | 9.05134 |
May | 508.00000 | 23.56475 | 46.14809 | -0.6062 | 15.79097 |
June | 496.00000 | 23.83896 | 51.83213 | -0.4356 | 11.33484 |
July | 497.00000 | 24.18392 | 55.13194 | -0.2494 | 8.59424 |
August | 514.00000 | 24.03319 | 56.60205 | -0.2904 | 8.77938 |
September | 485.00000 | 23.64612 | 53.99958 | -0.5091 | 12.93716 |
October | 502.00000 | 23.57370 | 44.30169 | 0.31143 | 8.48787 |
November | 489.00000 | 22.75759 | 40.49133 | 0.03938 | 6.64330 |
December | 497.00000 | 22.29751 | 35.58905 | -0.1135 | 6.77876 |
Annual Sum or Average | 5943.00000 | 23.23737 | 46.65967 | -0.1350 | 9.19402 |
Minimum of Months | 454.00000 | 22.29751 | 35.58905 | -0.6062 | 6.64330 |
Maximum of Months | 514.00000 | 24.18392 | 56.60205 | 0.31500 | 15.79097 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.37407 | 37.35811 | 0.22787 | 9.35461 |
February | 454.00000 | 23.08892 | 41.35252 | 0.16100 | 8.85253 |
March | 514.00000 | 22.96447 | 44.72659 | 0.13784 | 8.42963 |
April | 485.00000 | 23.44011 | 47.24777 | 0.28983 | 8.85968 |
May | 508.00000 | 23.29078 | 47.28744 | -0.7469 | 19.45195 |
June | 496.00000 | 23.65204 | 52.85790 | -0.5666 | 13.14631 |
July | 497.00000 | 23.95299 | 56.35846 | -0.4094 | 9.67112 |
August | 514.00000 | 23.97150 | 57.16215 | -0.3635 | 9.12187 |
September | 485.00000 | 23.96033 | 53.02752 | -0.3854 | 10.79686 |
October | 502.00000 | 24.05780 | 42.98411 | 0.46812 | 11.90036 |
November | 489.00000 | 23.65451 | 38.13946 | 0.31144 | 9.70072 |
December | 497.00000 | 23.53703 | 32.75930 | 0.24765 | 9.40080 |
Annual Sum or Average | 5943.00000 | 23.58071 | 45.98543 | -0.0553 | 10.74684 |
Minimum of Months | 454.00000 | 22.96447 | 32.75930 | -0.7469 | 8.42963 |
Maximum of Months | 514.00000 | 24.05780 | 57.16215 | 0.46812 | 19.45195 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.25179 | 39.74346 | -0.0885 | 7.69740 |
February | 454.00000 | 22.42307 | 42.59892 | -0.0153 | 7.36757 |
March | 514.00000 | 22.59369 | 45.36298 | 0.05580 | 7.59304 |
April | 485.00000 | 23.48238 | 46.88482 | 0.33329 | 9.79200 |
May | 508.00000 | 23.54756 | 46.13040 | -0.5866 | 16.33725 |
June | 496.00000 | 23.90874 | 51.60609 | -0.3801 | 10.54274 |
July | 497.00000 | 24.21738 | 55.12583 | -0.2162 | 8.26379 |
August | 514.00000 | 24.07108 | 56.60668 | -0.2589 | 8.38828 |
September | 485.00000 | 23.81790 | 53.42347 | -0.4225 | 11.50188 |
October | 502.00000 | 23.58654 | 44.01908 | 0.32975 | 9.46815 |
November | 489.00000 | 22.75265 | 40.02260 | 0.05887 | 7.37957 |
December | 497.00000 | 22.36734 | 34.99592 | -0.0823 | 7.30382 |
Annual Sum or Average | 5943.00000 | 23.25707 | 46.41478 | -0.1076 | 9.31822 |
Minimum of Months | 454.00000 | 22.25179 | 34.99592 | -0.5866 | 7.30382 |
Maximum of Months | 514.00000 | 24.21738 | 56.60668 | 0.33329 | 16.33725 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.251381E+11 | 142600.49 | 18-JAN-12:00 | 254.28 | 0.230241E+12 | 0.00 | 0.255379E+12 | 3.28 | 10.00 | 15-JAN-14:27 | 0.00 | 0.00 |
February | 0.137174E+11 | 139627.84 | 01-FEB-11:40 | 213.39 | 0.127661E+12 | 0.00 | 0.141378E+12 | 3.07 | 10.00 | 22-FEB-15:10 | 0.00 | 0.00 |
March | 0.153911E+11 | 157662.62 | 23-MAR-15:40 | 215.04 | 0.142028E+12 | 0.00 | 0.157419E+12 | 2.79 | 10.00 | 01-MAR-14:50 | 0.00 | 0.00 |
April | 0.335570E+11 | 157901.51 | 25-APR-13:50 | 322.49 | 0.308311E+12 | 0.00 | 0.341868E+12 | 4.30 | 10.00 | 02-APR-14:20 | 0.00 | 0.00 |
May | 0.340312E+11 | 154958.87 | 04-MAY-12:50 | 353.67 | 0.317107E+12 | 0.00 | 0.351138E+12 | 4.58 | 10.00 | 16-MAY-14:20 | 0.00 | 0.00 |
June | 0.572892E+11 | 157537.90 | 21-JUN-12:40 | 431.97 | 0.512135E+12 | 0.00 | 0.569424E+12 | 5.67 | 10.02 | 26-JUN-05:03 | 0.00 | 0.00 |
July | 0.867116E+11 | 158863.14 | 17-JUL-17:30 | 539.01 | 0.755166E+12 | 0.00 | 0.841877E+12 | 6.71 | 10.02 | 31-JUL-04:12 | 0.00 | 0.00 |
August | 0.980331E+11 | 160824.17 | 23-AUG-10:50 | 579.08 | 0.843818E+12 | 0.00 | 0.941851E+12 | 7.15 | 10.02 | 17-AUG-04:11 | 0.00 | 0.00 |
September | 0.623402E+11 | 159314.92 | 13-SEP-09:00 | 421.40 | 0.553107E+12 | 0.00 | 0.615448E+12 | 5.49 | 10.02 | 25-SEP-04:12 | 0.00 | 0.00 |
October | 0.720536E+11 | 159055.36 | 01-OCT-13:52 | 441.71 | 0.629771E+12 | 0.00 | 0.701825E+12 | 5.51 | 10.04 | 16-OCT-04:12 | 0.00 | 0.00 |
November | 0.274932E+11 | 144335.74 | 28-NOV-13:10 | 285.98 | 0.251522E+12 | 0.00 | 0.279015E+12 | 3.81 | 10.00 | 19-NOV-09:38 | 0.00 | 0.00 |
December | 0.321031E+11 | 152723.58 | 19-DEC-14:10 | 256.18 | 0.282846E+12 | 0.00 | 0.314949E+12 | 3.25 | 10.00 | 25-DEC-14:04 | 0.00 | 0.00 |
Annual Sum or Average | 0.557859E+12 | 4314.20 | 0.495371E+13 | 0.00 | 0.551157E+13 | 4.65 | 0.00 | 0.00 | ||||
Minimum of Months | 0.137174E+11 | 139627.84 | 213.39 | 0.127661E+12 | 0.00 | 0.141378E+12 | 2.79 | 10.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.980331E+11 | 160824.17 | 579.08 | 0.843818E+12 | 0.00 | 0.941851E+12 | 7.15 | 10.04 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.195164E+09 | 66959.74 | 18-JAN-14:20 | 1.17 | 0.179963E+10 | 0.00 | 0.199479E+10 | 0.02 | 10.73 | 18-JAN-14:50 | 0.00 | 0.00 |
February | 45444111.11 | 58769.69 | 01-FEB-12:10 | 0.33 | 0.434604E+09 | 0.00 | 0.480048E+09 | 0.00 | 10.65 | 01-FEB-12:00 | 0.00 | 0.00 |
March | 0.455213E+09 | 66360.68 | 23-MAR-14:50 | 2.33 | 0.418195E+10 | 0.00 | 0.463717E+10 | 0.03 | 10.50 | 22-MAR-12:40 | 0.00 | 0.00 |
April | 0.110324E+10 | 67677.14 | 26-APR-12:10 | 5.50 | 0.101900E+11 | 0.00 | 0.112933E+11 | 0.07 | 10.44 | 12-APR-13:20 | 0.00 | 0.00 |
May | 38459863.42 | 58244.95 | 04-MAY-12:20 | 0.50 | 0.360434E+09 | 0.00 | 0.398894E+09 | 0.01 | 10.43 | 03-MAY-13:40 | 0.00 | 0.00 |
June | 0.608499E+10 | 79875.00 | 29-JUN-13:00 | 26.67 | 0.551519E+11 | 0.00 | 0.612369E+11 | 0.34 | 10.37 | 26-JUN-11:40 | 0.00 | 0.00 |
July | 0.263930E+11 | 125820.11 | 31-JUL-16:00 | 99.67 | 0.227123E+12 | 0.00 | 0.253516E+12 | 1.16 | 10.26 | 31-JUL-17:40 | 0.00 | 0.00 |
August | 0.371236E+11 | 131750.37 | 18-AUG-15:50 | 137.83 | 0.317427E+12 | 0.00 | 0.354551E+12 | 1.60 | 10.51 | 30-AUG-10:20 | 0.00 | 0.00 |
September | 0.120234E+11 | 87310.79 | 22-SEP-11:30 | 51.33 | 0.107826E+12 | 0.00 | 0.119849E+12 | 0.64 | 10.62 | 30-SEP-13:00 | 0.00 | 0.00 |
October | 0.189378E+11 | 145310.60 | 30-OCT-13:43 | 73.82 | 0.165213E+12 | 0.00 | 0.184151E+12 | 0.88 | 10.66 | 14-OCT-15:10 | 0.00 | 0.00 |
November | 0.222354E+09 | 64685.51 | 28-NOV-13:30 | 1.00 | 0.204596E+10 | 0.00 | 0.226832E+10 | 0.01 | 9.43 | 28-NOV-14:30 | 0.00 | 0.00 |
December | 0.844635E+09 | 69746.83 | 05-DEC-14:40 | 4.17 | 0.782691E+10 | 0.00 | 0.867154E+10 | 0.05 | 10.69 | 29-DEC-12:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.103467E+12 | 404.32 | 0.899580E+12 | 0.00 | 0.100305E+13 | 0.41 | 0.00 | 0.00 | ||||
Minimum of Months | 38459863.42 | 58244.95 | 0.33 | 0.360434E+09 | 0.00 | 0.398894E+09 | 0.00 | 9.43 | 0.00 | 0.00 | ||
Maximum of Months | 0.371236E+11 | 145310.60 | 137.83 | 0.317427E+12 | 0.00 | 0.354551E+12 | 1.60 | 10.73 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.218320E+11 | 744.00 | 49248.27 | 03-JAN-12:10 | 174128.37 | 14-JAN-12:00 | 19.32 | 18.76 | 15.63 |
February | 0.164140E+11 | 672.00 | 49248.27 | 01-FEB-08:00 | 318603.86 | 01-FEB-12:00 | 19.56 | 18.48 | 15.63 |
March | 0.224581E+11 | 744.00 | 49248.27 | 01-MAR-10:20 | 435265.85 | 23-MAR-14:10 | 20.52 | 18.66 | 15.63 |
April | 0.559959E+11 | 720.00 | 49248.27 | 01-APR-08:30 | 711514.06 | 26-APR-11:00 | 23.96 | 19.69 | 15.63 |
May | 0.383938E+11 | 744.00 | 49248.27 | 01-MAY-09:40 | 98726.51 | 04-MAY-12:10 | 19.39 | 18.81 | 15.63 |
June | 0.586777E+11 | 720.00 | 49248.27 | 01-JUN-08:40 | 386408.83 | 29-JUN-11:00 | 21.41 | 19.69 | 15.63 |
July | 0.986930E+11 | 744.00 | 49248.27 | 01-JUL-05:30 | 709767.33 | 19-JUL-14:00 | 26.59 | 21.60 | 15.63 |
August | 0.126501E+12 | 744.00 | 49248.27 | 01-AUG-00:03 | 786431.31 | 18-AUG-12:10 | 32.74 | 23.16 | 15.63 |
September | 0.605217E+11 | 720.00 | 49248.27 | 01-SEP-08:40 | 284735.47 | 21-SEP-13:30 | 20.69 | 19.90 | 15.63 |
October | 0.791394E+11 | 744.00 | 49248.27 | 01-OCT-00:10 | 474921.30 | 01-OCT-12:00 | 23.14 | 20.93 | 15.63 |
November | 0.329414E+11 | 720.00 | 49248.27 | 01-NOV-11:30 | 519930.94 | 19-NOV-13:01 | 21.06 | 18.93 | 15.63 |
December | 0.462690E+11 | 744.00 | 49248.27 | 03-DEC-13:32 | 645258.45 | 19-DEC-13:00 | 22.97 | 19.37 | 15.63 |
Annual Sum or Average | 0.657837E+12 | 8760.00 | 22.65 | 19.85 | 15.63 | ||||
Minimum of Months | 0.164140E+11 | 672.00 | 49248.27 | 98726.51 | 19.32 | 18.48 | 15.63 | ||
Maximum of Months | 0.126501E+12 | 744.00 | 49248.27 | 786431.31 | 32.74 | 23.16 | 15.63 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.882994E+09 | 168.65 | 15552.17 | 13-JAN-13:20 | 1157151.30 | 18-JAN-12:00 | 21.57 | 21.12 | 14.93 |
February | 0.227948E+09 | 109.25 | 15552.17 | 01-FEB-11:40 | 1119893.79 | 01-FEB-11:40 | 21.33 | 21.05 | 12.95 |
March | 0.743981E+09 | 127.99 | 15552.17 | 22-MAR-12:10 | 1087228.18 | 23-MAR-12:40 | 21.35 | 21.07 | 11.70 |
April | 0.195259E+10 | 238.85 | 15552.17 | 04-APR-12:00 | 1157228.41 | 26-APR-15:40 | 21.70 | 21.07 | 21.17 |
May | 0.143405E+10 | 268.22 | 15552.17 | 02-MAY-12:40 | 1161839.77 | 03-MAY-14:30 | 21.70 | 21.08 | 22.94 |
June | 0.570552E+10 | 370.82 | 15552.17 | 13-JUN-11:00 | 1129240.11 | 21-JUN-14:20 | 22.28 | 21.27 | 30.32 |
July | 0.135064E+11 | 461.09 | 15552.17 | 01-JUL-10:50 | 1075498.46 | 07-JUL-13:20 | 23.08 | 21.63 | 36.56 |
August | 0.161395E+11 | 481.45 | 15552.17 | 01-AUG-09:50 | 1104721.57 | 21-AUG-12:30 | 23.36 | 21.74 | 39.32 |
September | 0.775296E+10 | 372.47 | 15552.17 | 01-SEP-10:40 | 1103719.51 | 06-SEP-15:20 | 22.58 | 21.48 | 29.91 |
October | 0.702109E+10 | 377.38 | 15552.17 | 01-OCT-10:37 | 1174181.37 | 30-OCT-11:00 | 22.72 | 21.48 | 29.78 |
November | 0.562975E+09 | 181.08 | 15552.17 | 10-NOV-12:40 | 1150828.42 | 28-NOV-13:10 | 21.55 | 21.05 | 17.66 |
December | 0.421389E+09 | 172.55 | 3336.67 | 07-DEC-13:30 | 1220972.04 | 19-DEC-14:10 | 21.59 | 21.04 | 15.64 |
Annual Sum or Average | 0.563515E+11 | 3329.77 | 22.07 | 21.26 | 23.65 | ||||
Minimum of Months | 0.227948E+09 | 109.25 | 3336.67 | 1075498.46 | 21.33 | 21.04 | 11.70 | ||
Maximum of Months | 0.161395E+11 | 481.45 | 15552.17 | 1220972.04 | 23.36 | 21.74 | 39.32 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 5442678.86 | 0.67 | 2887.12 | 18-JAN-15:00 | 999651.05 | 18-JAN-14:30 | 21.57 | 21.57 | 0.05 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.33 | 21.33 | 0.00 |
March | 0.111976E+09 | 2.00 | 15552.17 | 22-MAR-12:40 | 840059.24 | 22-MAR-13:20 | 21.35 | 21.34 | 0.13 |
April | 0.270608E+09 | 4.83 | 15552.17 | 04-APR-14:00 | 860234.07 | 26-APR-14:20 | 21.70 | 21.67 | 0.31 |
May | 55987810.52 | 1.00 | 15552.17 | 03-MAY-13:40 | 817992.43 | 03-MAY-13:40 | 21.70 | 21.69 | 0.05 |
June | 0.154900E+10 | 27.67 | 15552.17 | 19-JUN-12:20 | 816434.28 | 21-JUN-13:00 | 22.28 | 22.16 | 1.99 |
July | 0.578541E+10 | 103.33 | 15552.17 | 03-JUL-12:10 | 1030575.41 | 31-JUL-16:00 | 23.08 | 22.61 | 7.26 |
August | 0.790361E+10 | 141.17 | 15552.17 | 02-AUG-09:30 | 1054783.71 | 18-AUG-16:00 | 23.36 | 22.71 | 9.93 |
September | 0.282878E+10 | 50.67 | 15552.17 | 05-SEP-12:50 | 981739.26 | 29-SEP-08:20 | 22.58 | 22.35 | 3.67 |
October | 0.286613E+10 | 63.86 | 15552.17 | 01-OCT-11:15 | 1033289.05 | 16-OCT-08:40 | 22.72 | 22.40 | 4.50 |
November | 1395007.89 | 0.33 | 1164.56 | 28-NOV-14:30 | 936257.23 | 28-NOV-14:00 | 21.55 | 21.55 | 0.02 |
December | 7660499.12 | 1.67 | 2323.70 | 05-DEC-14:10 | 1007110.14 | 05-DEC-14:10 | 21.59 | 21.58 | 0.12 |
Annual Sum or Average | 0.213860E+11 | 397.19 | 22.07 | 21.92 | 2.36 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 21.33 | 0.00 | ||
Maximum of Months | 0.790361E+10 | 141.17 | 15552.17 | 1054783.71 | 23.36 | 22.71 | 9.93 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.813005E+10 | 0.00 | 113.70 | 583876.19 | 09-JAN-06:02 | 0.00 | 27.00 | 35.51 | 0.01 | 0.00 | 0.00 | 0.42 | 09-JAN-06:02 |
February | 0.208582E+10 | 0.00 | 88.77 | 127761.52 | 06-FEB-06:03 | 0.00 | 23.79 | 31.44 | 0.00 | 0.00 | 0.00 | 0.09 | 06-FEB-06:03 |
March | 0.446333E+10 | 0.00 | 89.39 | 620035.71 | 30-MAR-05:03 | 0.00 | 24.35 | 31.20 | 0.01 | 0.00 | 0.00 | 0.45 | 30-MAR-05:03 |
April | 0.398788E+09 | 0.00 | 20.13 | 132535.16 | 01-APR-05:03 | 0.00 | 22.20 | 23.86 | 0.00 | 0.00 | 0.00 | 0.10 | 01-APR-05:03 |
May | 63239942.65 | 0.00 | 9.54 | 51188.23 | 15-MAY-05:03 | 0.00 | 22.53 | 23.30 | 0.00 | 0.00 | 0.00 | 0.04 | 15-MAY-05:03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 22.89 | 22.89 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 22.89 | 22.89 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 22.89 | 22.89 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 144525.94 | 0.00 | 0.33 | 221.35 | 20-SEP-05:40 | 0.00 | 22.89 | 22.92 | 0.00 | 0.00 | 0.00 | 0.00 | 20-SEP-05:40 |
October | 99852921.42 | 0.00 | 17.08 | 31519.72 | 30-OCT-05:03 | 0.00 | 22.51 | 23.88 | 0.00 | 0.00 | 0.00 | 0.02 | 30-OCT-05:03 |
November | 0.874794E+09 | 0.00 | 55.92 | 120714.23 | 27-NOV-06:03 | 0.00 | 24.80 | 29.20 | 0.00 | 0.00 | 0.00 | 0.09 | 27-NOV-06:03 |
December | 0.376400E+10 | 0.00 | 99.77 | 362472.00 | 13-DEC-06:03 | 0.00 | 24.93 | 32.55 | 0.01 | 0.00 | 0.00 | 0.26 | 13-DEC-06:03 |
Annual Sum or Average | 0.198800E+11 | 0.00 | 494.63 | 0.00 | 23.64 | 26.86 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.20 | 22.89 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.813005E+10 | 0.00 | 113.70 | 620035.71 | 0.00 | 27.00 | 35.51 | 0.01 | 0.00 | 0.00 | 0.45 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 19.32 | 19.32 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 19.56 | 19.56 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 20.52 | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 23.96 | 23.96 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 19.39 | 19.39 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 21.41 | 21.41 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 26.59 | 26.59 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 32.74 | 32.74 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 20.69 | 20.69 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 23.14 | 23.14 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 21.06 | 21.06 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 22.97 | 22.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 22.65 | 22.65 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.32 | 19.32 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.74 | 32.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.213981E+11 | 0.00 | 219.78 | 0.213530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 90474.67 | 18-JAN-13:50 | 90474.67 | 18-JAN-13:50 | 0.00 | 0.00 | 0.00 |
February | 0.123034E+11 | 0.00 | 169.54 | 0.122294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 84776.59 | 01-FEB-12:00 | 84776.59 | 01-FEB-12:00 | 0.00 | 0.00 | 0.00 |
March | 0.147013E+11 | 0.00 | 172.91 | 0.143527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 95121.48 | 23-MAR-14:00 | 82743.92 | 23-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.331267E+11 | 0.00 | 291.32 | 0.331052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 111768.25 | 26-APR-13:40 | 109623.22 | 26-APR-13:50 | 0.00 | 0.00 | 0.00 |
May | 0.294531E+11 | 0.00 | 327.26 | 0.293668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 80790.61 | 03-MAY-13:00 | 80790.61 | 03-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.534074E+11 | 0.00 | 416.15 | 0.489101E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 124632.39 | 29-JUN-13:00 | 88528.88 | 26-JUN-10:00 | 0.00 | 0.00 | 0.00 |
July | 0.981487E+11 | 0.00 | 520.61 | 0.732660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 177961.07 | 31-JUL-15:40 | 112051.57 | 31-JUL-13:10 | 0.00 | 0.00 | 0.00 |
August | 0.120847E+12 | 0.00 | 564.01 | 0.848957E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 181825.86 | 15-AUG-08:50 | 120767.20 | 14-AUG-14:50 | 0.00 | 0.00 | 0.00 |
September | 0.613979E+11 | 0.00 | 401.21 | 0.518148E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 149807.55 | 22-SEP-12:30 | 124823.03 | 29-SEP-13:10 | 0.00 | 0.00 | 0.00 |
October | 0.799617E+11 | 0.00 | 415.71 | 0.664858E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 182796.65 | 05-OCT-04:23 | 137573.87 | 16-OCT-11:00 | 0.00 | 0.00 | 0.00 |
November | 0.257540E+11 | 0.00 | 255.01 | 0.254026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96833.13 | 28-NOV-14:00 | 96833.13 | 28-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.299395E+11 | 0.00 | 232.32 | 0.298697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 103013.28 | 05-DEC-15:00 | 103013.28 | 05-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.580439E+12 | 0.00 | 3985.83 | 0.491052E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.123034E+11 | 0.00 | 169.54 | 0.122294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 80790.61 | 80790.61 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.120847E+12 | 0.00 | 564.01 | 0.848957E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 182796.65 | 137573.87 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.176099E+12 | 0.00 | 235.79 | 0.175652E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 746007.77 | 18-JAN-14:00 | 746007.77 | 18-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.943601E+11 | 0.00 | 179.21 | 0.936309E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 692732.04 | 01-FEB-12:00 | 692732.04 | 01-FEB-12:00 | 0.00 | 0.00 | 0.00 |
March | 0.107077E+12 | 0.00 | 177.04 | 0.104285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 787243.17 | 23-MAR-14:10 | 669147.11 | 23-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.233542E+12 | 0.00 | 282.35 | 0.233481E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 856517.40 | 26-APR-14:00 | 856517.40 | 26-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.237872E+12 | 0.00 | 329.70 | 0.237234E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 701866.95 | 03-MAY-13:00 | 701866.95 | 03-MAY-13:00 | 0.00 | 0.00 | 0.00 |
June | 0.420069E+12 | 0.00 | 408.13 | 0.387005E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1040815.75 | 29-JUN-13:00 | 729022.77 | 29-JUN-11:00 | 0.00 | 0.00 | 0.00 |
July | 0.730200E+12 | 0.00 | 450.97 | 0.555316E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1406165.63 | 31-JUL-15:50 | 902707.75 | 19-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.860043E+12 | 0.00 | 465.14 | 0.624142E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1468297.09 | 18-AUG-15:50 | 934062.16 | 17-AUG-14:10 | 0.00 | 0.00 | 0.00 |
September | 0.502277E+12 | 0.00 | 399.28 | 0.427033E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1265341.66 | 30-SEP-05:03 | 1265341.66 | 30-SEP-05:03 | 0.00 | 0.00 | 0.00 |
October | 0.594924E+12 | 0.00 | 405.76 | 0.509294E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1397193.30 | 03-OCT-13:30 | 1142251.20 | 16-OCT-11:00 | 0.00 | 0.00 | 0.00 |
November | 0.185118E+12 | 0.00 | 256.76 | 0.182768E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 724517.90 | 28-NOV-14:00 | 724517.90 | 28-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.208837E+12 | 0.00 | 232.23 | 0.208305E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 762543.81 | 05-DEC-15:00 | 762543.81 | 05-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.435042E+13 | 0.00 | 3822.36 | 0.373815E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.943601E+11 | 0.00 | 177.04 | 0.936309E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 692732.04 | 669147.11 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.860043E+12 | 0.00 | 465.14 | 0.624142E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1468297.09 | 1265341.66 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.138405E+11 | 0.00 | 204.75 | 0.138104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 72993.99 | 18-JAN-13:30 | 72993.99 | 18-JAN-13:30 | 0.00 | 0.00 | 0.00 |
February | 0.763960E+10 | 0.00 | 158.64 | 0.758010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63597.30 | 01-FEB-12:00 | 63597.30 | 01-FEB-12:00 | 0.00 | 0.00 | 0.00 |
March | 0.942434E+10 | 0.00 | 153.94 | 0.928800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77078.08 | 23-MAR-14:30 | 69904.14 | 23-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.230100E+11 | 0.00 | 263.59 | 0.230066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 103633.54 | 26-APR-14:00 | 103633.54 | 26-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.235276E+11 | 0.00 | 314.36 | 0.234708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79113.28 | 03-MAY-13:10 | 79113.28 | 03-MAY-13:10 | 0.00 | 0.00 | 0.00 |
June | 0.435599E+11 | 0.00 | 396.30 | 0.399556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 116630.87 | 29-JUN-13:00 | 79139.39 | 21-JUN-13:00 | 0.00 | 0.00 | 0.00 |
July | 0.776991E+11 | 0.00 | 439.15 | 0.589154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 172725.02 | 31-JUL-15:20 | 110265.23 | 31-JUL-14:00 | 0.00 | 0.00 | 0.00 |
August | 0.908970E+11 | 0.00 | 450.70 | 0.654469E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 172127.72 | 17-AUG-15:50 | 111496.52 | 17-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.497141E+11 | 0.00 | 381.75 | 0.425237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 129358.40 | 29-SEP-13:40 | 129358.40 | 29-SEP-13:40 | 0.00 | 0.00 | 0.00 |
October | 0.576048E+11 | 0.00 | 385.97 | 0.492840E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 149038.59 | 03-OCT-13:10 | 132882.74 | 16-OCT-13:30 | 0.00 | 0.00 | 0.00 |
November | 0.147777E+11 | 0.00 | 230.37 | 0.147112E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 70594.33 | 28-NOV-14:00 | 70594.33 | 28-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.170681E+11 | 0.00 | 207.20 | 0.170386E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 77901.76 | 05-DEC-15:00 | 77901.76 | 05-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.428763E+12 | 0.00 | 3586.73 | 0.365031E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.763960E+10 | 0.00 | 153.94 | 0.758010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63597.30 | 63597.30 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.908970E+11 | 0.00 | 450.70 | 0.654469E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 172725.02 | 132882.74 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.158652E+11 | 0.00 | 189.07 | 0.156654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82782.98 | 17-JAN-12:00 | 76783.00 | 17-JAN-12:00 | 0.00 | 0.00 | 0.00 |
February | 0.945653E+10 | 0.00 | 161.26 | 0.910983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68437.91 | 13-FEB-07:23 | 58806.81 | 01-FEB-12:00 | 0.00 | 0.00 | 0.00 |
March | 0.987206E+10 | 0.00 | 154.20 | 0.919962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61958.24 | 23-MAR-15:00 | 46595.11 | 10-MAR-11:00 | 0.00 | 0.00 | 0.00 |
April | 0.209885E+11 | 0.00 | 227.77 | 0.196457E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 72159.56 | 27-APR-06:25 | 61745.15 | 03-APR-10:00 | 0.00 | 0.00 | 0.00 |
May | 0.209524E+11 | 0.00 | 251.05 | 0.198094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75344.83 | 05-MAY-06:14 | 55028.15 | 24-MAY-06:42 | 0.00 | 0.00 | 0.00 |
June | 0.368951E+11 | 0.00 | 309.07 | 0.318642E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91736.83 | 30-JUN-06:25 | 67678.25 | 26-JUN-10:00 | 0.00 | 0.00 | 0.00 |
July | 0.549885E+11 | 0.00 | 309.89 | 0.436120E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 116619.16 | 31-JUL-09:10 | 74007.99 | 31-JUL-10:00 | 0.00 | 0.00 | 0.00 |
August | 0.604998E+11 | 0.00 | 337.66 | 0.465892E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 129727.63 | 15-AUG-08:45 | 86208.60 | 15-AUG-10:00 | 0.00 | 0.00 | 0.00 |
September | 0.360201E+11 | 0.00 | 260.41 | 0.276986E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102697.18 | 22-SEP-17:31 | 69316.92 | 11-SEP-11:00 | 0.00 | 0.00 | 0.00 |
October | 0.466468E+11 | 0.00 | 280.67 | 0.389110E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 128793.90 | 05-OCT-13:00 | 100392.33 | 16-OCT-11:00 | 0.00 | 0.00 | 0.00 |
November | 0.180016E+11 | 0.00 | 209.15 | 0.176609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74137.33 | 10-NOV-07:11 | 64541.89 | 27-NOV-12:00 | 0.00 | 0.00 | 0.00 |
December | 0.195428E+11 | 0.00 | 175.56 | 0.195109E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75954.19 | 04-DEC-10:00 | 75954.19 | 04-DEC-10:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.349729E+12 | 0.00 | 2865.75 | 0.299277E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.945653E+10 | 0.00 | 154.20 | 0.910983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61958.24 | 46595.11 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.604998E+11 | 0.00 | 337.66 | 0.465892E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 129727.63 | 100392.33 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.804747E+10 | 0.559005E+10 | 464.92 | 0.798288E+10 | 64587806.59 | 0.00 | 0.31 | 14-JAN-11:10 | 0.01 | 30-JAN-08:25 | 105167.69 | 14-JAN-11:00 | 105167.69 | 14-JAN-11:00 | 9064.18 | 17-JAN-14:00 | 39682.59 | 14-JAN-11:10 | 0.00 |
February | 0.745058E+10 | 0.524560E+10 | 366.53 | 0.739092E+10 | 59656016.98 | 0.00 | 0.50 | 01-FEB-12:00 | 0.00 | 05-FEB-18:50 | 194709.22 | 01-FEB-12:00 | 194709.22 | 01-FEB-12:00 | 11690.24 | 01-FEB-13:30 | 66129.09 | 01-FEB-12:00 | 0.00 |
March | 0.397036E+11 | 0.148033E+11 | 421.57 | 0.318552E+11 | 0.784837E+10 | 0.00 | 0.60 | 23-MAR-14:00 | 0.01 | 05-MAR-18:10 | 261162.47 | 23-MAR-14:00 | 226976.22 | 11-MAR-14:00 | 80321.12 | 23-MAR-15:20 | 76120.38 | 11-MAR-14:00 | 0.00 |
April | 0.244216E+12 | 0.707746E+11 | 489.75 | 0.186577E+12 | 0.576387E+11 | 0.00 | 0.96 | 26-APR-11:00 | 0.01 | 17-APR-05:03 | 448321.12 | 26-APR-11:00 | 407565.04 | 26-APR-13:00 | 103948.33 | 25-APR-09:30 | 136208.82 | 26-APR-11:00 | 0.00 |
May | 0.914900E+09 | 0.336393E+10 | 240.21 | 0.843756E+09 | 71143552.62 | 0.00 | 0.13 | 04-MAY-12:00 | 0.01 | 14-MAY-07:05 | 47967.85 | 04-MAY-12:00 | 43363.31 | 03-MAY-12:10 | 6238.88 | 04-MAY-12:00 | 15924.77 | 04-MAY-12:00 | 0.00 |
June | 0.659977E+11 | 0.225991E+11 | 329.48 | 0.473950E+11 | 0.186026E+11 | 0.00 | 0.54 | 29-JUN-11:00 | 0.01 | 02-JUN-04:53 | 245134.09 | 29-JUN-11:00 | 164078.84 | 29-JUN-11:00 | 81055.26 | 29-JUN-11:00 | 71834.82 | 29-JUN-11:00 | 0.00 |
July | 0.379876E+12 | 0.107356E+12 | 671.05 | 0.238645E+12 | 0.141231E+12 | 0.00 | 0.95 | 31-JUL-14:00 | 0.01 | 05-JUL-21:12 | 464778.80 | 31-JUL-14:00 | 318454.27 | 31-JUL-14:00 | 166925.60 | 31-JUL-23:53 | 136826.53 | 19-JUL-14:00 | 0.00 |
August | 0.855067E+12 | 0.227880E+12 | 743.33 | 0.485688E+12 | 0.369378E+12 | 0.00 | 1.00 | 05-AUG-12:50 | 0.01 | 31-AUG-23:10 | 494843.25 | 14-AUG-10:00 | 378146.85 | 29-AUG-13:00 | 241997.85 | 18-AUG-08:20 | 149104.64 | 14-AUG-11:00 | 0.00 |
September | 0.178629E+11 | 0.956569E+10 | 265.38 | 0.163410E+11 | 0.152191E+10 | 0.00 | 0.42 | 21-SEP-13:30 | 0.01 | 20-SEP-03:00 | 188304.60 | 21-SEP-13:30 | 137409.72 | 29-SEP-07:40 | 84553.66 | 22-SEP-12:00 | 60994.71 | 29-SEP-12:10 | 0.00 |
October | 0.120671E+12 | 0.420600E+11 | 526.71 | 0.100961E+12 | 0.197103E+11 | 0.00 | 0.66 | 01-OCT-12:00 | 0.01 | 30-OCT-00:40 | 314846.29 | 01-OCT-11:52 | 229447.78 | 17-OCT-08:20 | 123742.12 | 01-OCT-11:52 | 102411.32 | 16-OCT-11:00 | 0.00 |
November | 0.634804E+11 | 0.226907E+11 | 488.03 | 0.573454E+11 | 0.613500E+10 | 0.00 | 0.77 | 19-NOV-12:57 | 0.01 | 15-NOV-07:10 | 316273.51 | 19-NOV-12:53 | 316273.51 | 19-NOV-12:53 | 61296.87 | 10-NOV-13:00 | 107908.51 | 19-NOV-12:57 | 0.00 |
December | 0.177211E+12 | 0.581959E+11 | 620.46 | 0.167221E+12 | 0.998985E+10 | 0.00 | 0.99 | 19-DEC-13:00 | 0.01 | 03-DEC-18:20 | 382684.12 | 05-DEC-10:00 | 382684.12 | 05-DEC-10:00 | 82422.67 | 07-DEC-13:00 | 137293.74 | 19-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.198050E+13 | 0.590126E+12 | 5627.42 | 0.134825E+13 | 0.632252E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.914900E+09 | 0.336393E+10 | 240.21 | 0.843756E+09 | 59656016.98 | 0.00 | 0.13 | 0.00 | 47967.85 | 43363.31 | 6238.88 | 15924.77 | 0.00 | ||||||
Maximum of Months | 0.855067E+12 | 0.227880E+12 | 743.33 | 0.485688E+12 | 0.369378E+12 | 0.00 | 1.00 | 0.01 | 494843.25 | 407565.04 | 241997.85 | 149104.64 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.527390E+10 | 0.132671E+10 | 744.00 | 0.523187E+10 | 42025655.48 | 0.00 | 0.33 | 15-JAN-16:03 | 0.17 | 28-JAN-07:10 | 2542.05 | 18-JAN-16:10 | 2451.66 | 18-JAN-16:00 | 173.89 | 17-JAN-15:00 | 739.59 | 13-JAN-14:00 | 0.00 |
February | 0.946524E+10 | 0.221075E+10 | 672.00 | 0.940490E+10 | 60340332.28 | 0.00 | 0.56 | 03-FEB-15:00 | 0.40 | 25-FEB-18:00 | 4665.70 | 20-FEB-17:00 | 4648.09 | 20-FEB-16:55 | 207.59 | 13-FEB-17:00 | 1295.26 | 01-FEB-12:00 | 0.00 |
March | 0.156439E+11 | 0.350157E+10 | 744.00 | 0.155503E+11 | 93627936.91 | 0.00 | 0.84 | 31-MAR-24:00 | 0.61 | 01-MAR-07:05 | 7570.85 | 31-MAR-24:00 | 7570.85 | 31-MAR-24:00 | 269.18 | 23-MAR-16:10 | 1717.59 | 23-MAR-14:00 | 0.00 |
April | 0.203161E+11 | 0.452328E+10 | 720.00 | 0.201849E+11 | 0.131210E+09 | 0.00 | 0.97 | 02-APR-13:53 | 0.30 | 30-APR-24:00 | 8476.43 | 16-APR-17:25 | 8460.60 | 16-APR-17:35 | 256.76 | 13-APR-16:00 | 2503.48 | 26-APR-13:00 | 0.00 |
May | 0.568289E+10 | 0.139771E+10 | 744.00 | 0.558382E+10 | 99065921.43 | 0.00 | 0.46 | 31-MAY-24:00 | 0.19 | 13-MAY-06:20 | 3866.01 | 31-MAY-24:00 | 3848.42 | 31-MAY-24:00 | 211.26 | 05-MAY-15:30 | 886.67 | 31-MAY-24:00 | 0.00 |
June | 0.107242E+11 | 0.255779E+10 | 720.00 | 0.105312E+11 | 0.193000E+09 | 0.00 | 0.67 | 30-JUN-24:00 | 0.43 | 01-JUN-06:10 | 5897.13 | 30-JUN-24:00 | 5892.52 | 30-JUN-24:00 | 298.88 | 28-JUN-13:10 | 1321.44 | 29-JUN-11:00 | 0.00 |
July | 0.163605E+11 | 0.398007E+10 | 744.00 | 0.160743E+11 | 0.286169E+09 | 0.00 | 0.86 | 31-JUL-23:45 | 0.65 | 08-JUL-06:55 | 7764.83 | 31-JUL-23:45 | 7764.83 | 31-JUL-23:45 | 367.65 | 28-JUL-14:00 | 2073.07 | 19-JUL-14:30 | 0.00 |
August | 0.213891E+11 | 0.527153E+10 | 744.00 | 0.210622E+11 | 0.326901E+09 | 0.00 | 0.99 | 17-AUG-14:40 | 0.30 | 31-AUG-24:00 | 8602.95 | 17-AUG-16:00 | 8575.86 | 06-AUG-17:52 | 367.73 | 18-AUG-16:00 | 2687.97 | 17-AUG-14:00 | 0.00 |
September | 0.582026E+10 | 0.147746E+10 | 720.00 | 0.563937E+10 | 0.180886E+09 | 0.00 | 0.49 | 30-SEP-24:00 | 0.22 | 20-SEP-06:10 | 4102.25 | 30-SEP-24:00 | 4102.25 | 30-SEP-24:00 | 331.26 | 22-SEP-10:50 | 1100.46 | 29-SEP-13:00 | 0.00 |
October | 0.110662E+11 | 0.279416E+10 | 744.00 | 0.109405E+11 | 0.125676E+09 | 0.00 | 0.66 | 31-OCT-24:00 | 0.42 | 28-OCT-06:35 | 5871.04 | 31-OCT-24:00 | 5867.21 | 31-OCT-24:00 | 349.30 | 03-OCT-15:00 | 1960.38 | 16-OCT-11:00 | 0.00 |
November | 0.153008E+11 | 0.348561E+10 | 720.00 | 0.152278E+11 | 73004733.41 | 0.00 | 0.81 | 28-NOV-14:00 | 0.62 | 18-NOV-07:30 | 6575.81 | 07-NOV-16:20 | 6516.80 | 12-NOV-16:13 | 274.36 | 10-NOV-16:50 | 1970.73 | 28-NOV-14:00 | 0.00 |
December | 0.207642E+11 | 0.468186E+10 | 744.00 | 0.207317E+11 | 32419873.44 | 0.00 | 1.00 | 19-DEC-10:00 | 0.80 | 23-DEC-07:05 | 8521.51 | 25-DEC-16:20 | 8521.51 | 25-DEC-16:20 | 252.37 | 07-DEC-16:50 | 2546.15 | 19-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.157807E+12 | 0.372085E+11 | 8760.00 | 0.156163E+12 | 0.164433E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.527390E+10 | 0.132671E+10 | 672.00 | 0.523187E+10 | 32419873.44 | 0.00 | 0.33 | 0.17 | 2542.05 | 2451.66 | 173.89 | 739.59 | 0.00 | ||||||
Maximum of Months | 0.213891E+11 | 0.527153E+10 | 744.00 | 0.210622E+11 | 0.326901E+09 | 0.00 | 1.00 | 0.80 | 8602.95 | 8575.86 | 367.73 | 2687.97 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.402796E+11 | 0.103229E+11 | 744.00 | 0.398706E+11 | 0.409005E+09 | 0.00 | 0.31 | 18-JAN-16:10 | 0.09 | 03-JAN-07:05 | 23643.17 | 18-JAN-16:10 | 22761.81 | 18-JAN-16:10 | 1666.29 | 17-JAN-15:00 | 6679.66 | 24-JAN-15:50 | 0.00 |
February | 0.818042E+11 | 0.192909E+11 | 672.00 | 0.812063E+11 | 0.597925E+09 | 0.00 | 0.55 | 03-FEB-15:00 | 0.33 | 25-FEB-18:00 | 42734.12 | 01-FEB-16:50 | 41460.91 | 22-FEB-17:00 | 2077.56 | 13-FEB-17:00 | 12024.04 | 01-FEB-12:00 | 0.00 |
March | 0.140790E+12 | 0.317379E+11 | 744.00 | 0.139859E+12 | 0.931368E+09 | 0.00 | 0.80 | 31-MAR-23:40 | 0.55 | 30-MAR-06:05 | 68362.91 | 31-MAR-23:40 | 68362.91 | 31-MAR-23:40 | 2664.05 | 23-MAR-16:10 | 16297.35 | 23-MAR-14:00 | 0.00 |
April | 0.188759E+12 | 0.421989E+11 | 720.00 | 0.187455E+12 | 0.130405E+10 | 0.00 | 0.95 | 26-APR-13:30 | 0.26 | 30-APR-23:53 | 79517.00 | 26-APR-16:00 | 78596.64 | 30-APR-17:30 | 2539.85 | 13-APR-16:00 | 23815.08 | 26-APR-13:00 | 0.00 |
May | 0.491199E+11 | 0.121814E+11 | 744.00 | 0.481481E+11 | 0.971796E+09 | 0.00 | 0.43 | 31-MAY-24:00 | 0.15 | 13-MAY-06:40 | 34947.09 | 31-MAY-23:40 | 34719.98 | 31-MAY-24:00 | 2086.34 | 05-MAY-15:30 | 8053.63 | 31-MAY-24:00 | 0.00 |
June | 0.986595E+11 | 0.236293E+11 | 720.00 | 0.967479E+11 | 0.191157E+10 | 0.00 | 0.66 | 30-JUN-24:00 | 0.40 | 01-JUN-06:10 | 55744.43 | 30-JUN-24:00 | 55693.76 | 30-JUN-24:00 | 2963.75 | 28-JUN-13:10 | 12512.25 | 29-JUN-11:00 | 0.00 |
July | 0.153833E+12 | 0.375072E+11 | 744.00 | 0.150992E+12 | 0.284165E+10 | 0.00 | 0.86 | 31-JUL-23:53 | 0.63 | 08-JUL-06:55 | 74113.04 | 31-JUL-23:53 | 74113.04 | 31-JUL-23:53 | 3645.58 | 28-JUL-14:00 | 19735.01 | 19-JUL-14:20 | 0.00 |
August | 0.202338E+12 | 0.499410E+11 | 744.00 | 0.199081E+12 | 0.325670E+10 | 0.00 | 0.99 | 17-AUG-14:30 | 0.26 | 31-AUG-24:00 | 81732.33 | 17-AUG-16:00 | 79675.08 | 06-AUG-18:00 | 3657.49 | 18-AUG-16:00 | 25561.60 | 17-AUG-14:00 | 0.00 |
September | 0.509982E+11 | 0.130507E+11 | 720.00 | 0.492207E+11 | 0.177750E+10 | 0.00 | 0.47 | 30-SEP-24:00 | 0.18 | 20-SEP-06:10 | 38009.10 | 30-SEP-24:00 | 38009.10 | 30-SEP-24:00 | 3271.89 | 22-SEP-10:50 | 10369.05 | 29-SEP-13:00 | 0.00 |
October | 0.100117E+12 | 0.254528E+11 | 744.00 | 0.988719E+11 | 0.124503E+10 | 0.00 | 0.65 | 31-OCT-24:00 | 0.38 | 28-OCT-06:55 | 54382.51 | 31-OCT-24:00 | 54337.23 | 31-OCT-24:00 | 3454.53 | 03-OCT-15:00 | 18536.60 | 16-OCT-11:00 | 0.00 |
November | 0.137972E+12 | 0.316544E+11 | 720.00 | 0.137248E+12 | 0.724554E+09 | 0.00 | 0.80 | 28-NOV-14:00 | 0.57 | 18-NOV-07:30 | 61973.85 | 10-NOV-16:20 | 59867.21 | 07-NOV-16:20 | 2714.58 | 10-NOV-16:50 | 18550.46 | 28-NOV-14:00 | 0.00 |
December | 0.188468E+12 | 0.428260E+11 | 744.00 | 0.188143E+12 | 0.325012E+09 | 0.00 | 1.00 | 19-DEC-10:40 | 0.75 | 23-DEC-07:05 | 80002.05 | 07-DEC-16:20 | 78326.95 | 19-DEC-16:10 | 2493.60 | 07-DEC-16:50 | 24309.25 | 19-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.143314E+13 | 0.339793E+12 | 8760.00 | 0.141684E+13 | 0.162962E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.402796E+11 | 0.103229E+11 | 672.00 | 0.398706E+11 | 0.325012E+09 | 0.00 | 0.31 | 0.09 | 23643.17 | 22761.81 | 1666.29 | 6679.66 | 0.00 | ||||||
Maximum of Months | 0.202338E+12 | 0.499410E+11 | 744.00 | 0.199081E+12 | 0.325670E+10 | 0.00 | 1.00 | 0.75 | 81732.33 | 79675.08 | 3657.49 | 25561.60 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.283815E+10 | 0.746708E+09 | 704.17 | 0.279826E+10 | 39882083.41 | 0.00 | 0.31 | 18-JAN-16:10 | 0.00 | 01-JAN-00:10 | 2386.70 | 18-JAN-16:10 | 2298.04 | 18-JAN-16:10 | 163.99 | 20-JAN-16:30 | 669.55 | 24-JAN-15:50 | 0.00 |
February | 0.724222E+10 | 0.172787E+10 | 672.00 | 0.718309E+10 | 59134752.56 | 0.00 | 0.54 | 03-FEB-15:00 | 0.24 | 26-FEB-06:50 | 4292.68 | 01-FEB-16:50 | 4147.53 | 22-FEB-17:00 | 210.88 | 13-FEB-17:00 | 1186.91 | 03-FEB-15:00 | 0.00 |
March | 0.132252E+11 | 0.300720E+10 | 744.00 | 0.131325E+11 | 92745046.61 | 0.00 | 0.75 | 31-MAR-23:20 | 0.46 | 30-MAR-06:05 | 6493.16 | 31-MAR-23:20 | 6493.16 | 31-MAR-23:20 | 267.00 | 23-MAR-16:10 | 1642.85 | 23-MAR-14:00 | 0.00 |
April | 0.184310E+11 | 0.414483E+10 | 720.00 | 0.183007E+11 | 0.130235E+09 | 0.00 | 0.95 | 26-APR-14:00 | 0.23 | 30-APR-24:00 | 8044.78 | 26-APR-16:00 | 7909.42 | 30-APR-17:14 | 254.46 | 13-APR-16:00 | 2402.17 | 26-APR-13:00 | 0.00 |
May | 0.444643E+10 | 0.111330E+10 | 744.00 | 0.434994E+10 | 96489433.50 | 0.00 | 0.40 | 31-MAY-23:20 | 0.08 | 15-MAY-06:10 | 3263.98 | 31-MAY-23:20 | 3223.72 | 31-MAY-23:40 | 206.99 | 05-MAY-15:30 | 756.87 | 31-MAY-23:20 | 0.00 |
June | 0.965986E+10 | 0.232413E+10 | 720.00 | 0.946861E+10 | 0.191248E+09 | 0.00 | 0.64 | 30-JUN-23:50 | 0.35 | 01-JUN-06:10 | 5464.84 | 30-JUN-23:40 | 5458.22 | 30-JUN-24:00 | 298.03 | 28-JUN-13:10 | 1266.85 | 29-JUN-11:00 | 0.00 |
July | 0.152977E+11 | 0.374356E+10 | 744.00 | 0.150135E+11 | 0.284208E+09 | 0.00 | 0.84 | 31-JUL-23:33 | 0.59 | 06-JUL-06:12 | 7328.64 | 31-JUL-23:53 | 7328.64 | 31-JUL-23:53 | 365.48 | 28-JUL-14:00 | 2002.72 | 19-JUL-14:40 | 0.00 |
August | 0.201252E+11 | 0.498610E+10 | 744.00 | 0.197997E+11 | 0.325548E+09 | 0.00 | 0.98 | 17-AUG-14:40 | 0.23 | 31-AUG-24:00 | 8269.57 | 17-AUG-16:00 | 8083.69 | 06-AUG-17:45 | 366.26 | 18-AUG-16:00 | 2585.02 | 17-AUG-14:00 | 0.00 |
September | 0.479929E+10 | 0.123889E+10 | 720.00 | 0.462210E+10 | 0.177191E+09 | 0.00 | 0.46 | 30-SEP-24:00 | 0.12 | 20-SEP-06:40 | 3765.86 | 30-SEP-23:50 | 3765.86 | 30-SEP-23:50 | 328.84 | 22-SEP-11:00 | 1069.80 | 29-SEP-13:00 | 0.00 |
October | 0.956942E+10 | 0.245388E+10 | 744.00 | 0.944522E+10 | 0.124204E+09 | 0.00 | 0.63 | 15-OCT-16:32 | 0.30 | 30-OCT-06:13 | 5240.28 | 31-OCT-23:30 | 5230.61 | 31-OCT-23:40 | 346.08 | 03-OCT-15:00 | 1875.50 | 16-OCT-11:00 | 0.00 |
November | 0.129348E+11 | 0.299495E+10 | 720.00 | 0.128627E+11 | 72122816.73 | 0.00 | 0.79 | 28-NOV-14:00 | 0.47 | 27-NOV-07:05 | 6215.36 | 10-NOV-16:20 | 5977.22 | 07-NOV-16:20 | 271.25 | 10-NOV-16:50 | 1857.14 | 28-NOV-14:00 | 0.00 |
December | 0.177401E+11 | 0.407519E+10 | 744.00 | 0.177079E+11 | 32261142.87 | 0.00 | 1.00 | 19-DEC-13:00 | 0.64 | 26-DEC-07:05 | 7997.84 | 07-DEC-16:20 | 7845.20 | 19-DEC-16:10 | 249.37 | 07-DEC-16:50 | 2468.88 | 19-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.136309E+12 | 0.325566E+11 | 8720.17 | 0.134684E+12 | 0.162527E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.283815E+10 | 0.746708E+09 | 672.00 | 0.279826E+10 | 32261142.87 | 0.00 | 0.31 | 0.00 | 2386.70 | 2298.04 | 163.99 | 669.55 | 0.00 | ||||||
Maximum of Months | 0.201252E+11 | 0.498610E+10 | 744.00 | 0.197997E+11 | 0.325548E+09 | 0.00 | 1.00 | 0.64 | 8269.57 | 8083.69 | 366.26 | 2585.02 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.22 | 0.00 | 104.22 | 49.08 | 458.98 | 0.00 | 0.00 | 0.00 |
February | 130.83 | 0.00 | 130.83 | 60.57 | 419.78 | 0.00 | 0.00 | 0.00 |
March | 160.32 | 0.00 | 160.32 | 93.95 | 425.92 | 0.00 | 0.00 | 0.00 |
April | 184.70 | 0.71 | 183.99 | 139.43 | 334.04 | 0.00 | 0.00 | 0.00 |
May | 221.95 | 10.34 | 211.62 | 184.52 | 280.74 | 0.00 | 0.00 | 0.00 |
June | 236.50 | 23.12 | 213.38 | 242.68 | 221.90 | 0.00 | 0.00 | 0.00 |
July | 223.93 | 18.77 | 205.16 | 255.90 | 196.75 | 0.00 | 0.00 | 0.00 |
August | 185.97 | 3.72 | 182.24 | 203.52 | 207.06 | 0.00 | 0.00 | 0.00 |
September | 157.40 | 0.02 | 157.38 | 157.08 | 253.41 | 0.00 | 0.00 | 0.00 |
October | 124.86 | 0.00 | 124.86 | 132.70 | 289.96 | 0.00 | 0.00 | 0.00 |
November | 113.05 | 0.00 | 113.05 | 58.35 | 421.98 | 0.00 | 0.00 | 0.00 |
December | 97.02 | 0.00 | 97.02 | 40.13 | 472.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 161.86 | 4.75 | 157.11 | 135.28 | 331.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 97.02 | 0.00 | 97.02 | 40.13 | 196.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 236.50 | 23.12 | 213.38 | 255.90 | 472.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.22 | 0.00 | 104.22 | 49.08 | 458.98 | 0.00 | 0.00 | 0.00 |
February | 130.83 | 0.00 | 130.83 | 60.57 | 419.78 | 0.00 | 0.00 | 0.00 |
March | 160.32 | 0.00 | 160.32 | 93.95 | 425.92 | 0.00 | 0.00 | 0.00 |
April | 184.70 | 0.71 | 183.99 | 139.43 | 334.04 | 0.00 | 0.00 | 0.00 |
May | 221.95 | 10.34 | 211.62 | 184.52 | 280.74 | 0.00 | 0.00 | 0.00 |
June | 236.50 | 23.12 | 213.38 | 242.68 | 221.90 | 0.00 | 0.00 | 0.00 |
July | 223.93 | 18.77 | 205.16 | 255.90 | 196.75 | 0.00 | 0.00 | 0.00 |
August | 185.97 | 3.72 | 182.24 | 203.52 | 207.06 | 0.00 | 0.00 | 0.00 |
September | 157.40 | 0.02 | 157.38 | 157.08 | 253.41 | 0.00 | 0.00 | 0.00 |
October | 124.86 | 0.00 | 124.86 | 132.70 | 289.96 | 0.00 | 0.00 | 0.00 |
November | 113.05 | 0.00 | 113.05 | 58.35 | 421.98 | 0.00 | 0.00 | 0.00 |
December | 97.02 | 0.00 | 97.02 | 40.13 | 472.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 161.86 | 4.75 | 157.11 | 135.28 | 331.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 97.02 | 0.00 | 97.02 | 40.13 | 196.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 236.50 | 23.12 | 213.38 | 255.90 | 472.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.22 | 0.00 | 104.22 | 49.08 | 458.98 | 0.00 | 0.00 | 0.00 |
February | 130.83 | 0.00 | 130.83 | 60.57 | 419.78 | 0.00 | 0.00 | 0.00 |
March | 160.32 | 0.00 | 160.32 | 93.95 | 425.92 | 0.00 | 0.00 | 0.00 |
April | 184.70 | 0.71 | 183.99 | 139.43 | 334.04 | 0.00 | 0.00 | 0.00 |
May | 221.95 | 10.34 | 211.62 | 184.52 | 280.74 | 0.00 | 0.00 | 0.00 |
June | 236.50 | 23.12 | 213.38 | 242.68 | 221.90 | 0.00 | 0.00 | 0.00 |
July | 223.93 | 18.77 | 205.16 | 255.90 | 196.75 | 0.00 | 0.00 | 0.00 |
August | 185.97 | 3.72 | 182.24 | 203.52 | 207.06 | 0.00 | 0.00 | 0.00 |
September | 157.40 | 0.02 | 157.38 | 157.08 | 253.41 | 0.00 | 0.00 | 0.00 |
October | 124.86 | 0.00 | 124.86 | 132.70 | 289.96 | 0.00 | 0.00 | 0.00 |
November | 113.05 | 0.00 | 113.05 | 58.35 | 421.98 | 0.00 | 0.00 | 0.00 |
December | 97.02 | 0.00 | 97.02 | 40.13 | 472.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 161.86 | 4.75 | 157.11 | 135.28 | 331.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 97.02 | 0.00 | 97.02 | 40.13 | 196.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 236.50 | 23.12 | 213.38 | 255.90 | 472.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.22 | 0.00 | 104.22 | 49.08 | 458.98 | 0.00 | 0.00 | 0.00 |
February | 130.83 | 0.00 | 130.83 | 60.57 | 419.78 | 0.00 | 0.00 | 0.00 |
March | 160.32 | 0.00 | 160.32 | 93.95 | 425.92 | 0.00 | 0.00 | 0.00 |
April | 184.70 | 0.71 | 183.99 | 139.43 | 334.04 | 0.00 | 0.00 | 0.00 |
May | 221.95 | 10.34 | 211.62 | 184.52 | 280.74 | 0.00 | 0.00 | 0.00 |
June | 236.50 | 23.12 | 213.38 | 242.68 | 221.90 | 0.00 | 0.00 | 0.00 |
July | 223.93 | 18.77 | 205.16 | 255.90 | 196.75 | 0.00 | 0.00 | 0.00 |
August | 185.97 | 3.72 | 182.24 | 203.52 | 207.06 | 0.00 | 0.00 | 0.00 |
September | 157.40 | 0.02 | 157.38 | 157.08 | 253.41 | 0.00 | 0.00 | 0.00 |
October | 124.86 | 0.00 | 124.86 | 132.70 | 289.96 | 0.00 | 0.00 | 0.00 |
November | 113.05 | 0.00 | 113.05 | 58.35 | 421.98 | 0.00 | 0.00 | 0.00 |
December | 97.02 | 0.00 | 97.02 | 40.13 | 472.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 161.86 | 4.75 | 157.11 | 135.28 | 331.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 97.02 | 0.00 | 97.02 | 40.13 | 196.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 236.50 | 23.12 | 213.38 | 255.90 | 472.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 104.22 | 0.00 | 104.22 | 49.08 | 458.96 | 0.00 | 0.00 | 0.00 |
February | 130.82 | 0.00 | 130.82 | 60.56 | 419.76 | 0.00 | 0.00 | 0.00 |
March | 160.31 | 0.00 | 160.31 | 93.94 | 425.91 | 0.00 | 0.00 | 0.00 |
April | 184.70 | 0.71 | 183.98 | 139.43 | 334.03 | 0.00 | 0.00 | 0.00 |
May | 221.95 | 10.33 | 211.61 | 184.51 | 280.73 | 0.00 | 0.00 | 0.00 |
June | 236.49 | 23.12 | 213.37 | 242.67 | 221.89 | 0.00 | 0.00 | 0.00 |
July | 223.92 | 18.77 | 205.15 | 255.89 | 196.74 | 0.00 | 0.00 | 0.00 |
August | 185.96 | 3.72 | 182.24 | 203.51 | 207.05 | 0.00 | 0.00 | 0.00 |
September | 157.40 | 0.02 | 157.37 | 157.07 | 253.40 | 0.00 | 0.00 | 0.00 |
October | 124.85 | 0.00 | 124.85 | 132.70 | 289.95 | 0.00 | 0.00 | 0.00 |
November | 113.04 | 0.00 | 113.04 | 58.34 | 421.96 | 0.00 | 0.00 | 0.00 |
December | 97.02 | 0.00 | 97.02 | 40.13 | 472.91 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 161.85 | 4.75 | 157.11 | 135.27 | 331.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 97.02 | 0.00 | 97.02 | 40.13 | 196.74 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 236.49 | 23.12 | 213.37 | 255.89 | 472.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 312.36 | 167.06 | 145.30 | 354.08 | 468.92 | 0.00 | 0.00 | 0.00 |
February | 329.51 | 150.95 | 178.56 | 350.86 | 428.44 | 0.00 | 0.00 | 0.00 |
March | 400.26 | 178.33 | 221.92 | 449.99 | 431.65 | 0.00 | 0.00 | 0.00 |
April | 511.72 | 256.64 | 255.08 | 668.97 | 345.75 | 0.00 | 0.00 | 0.00 |
May | 482.92 | 201.53 | 281.39 | 605.18 | 313.69 | 0.00 | 0.00 | 0.00 |
June | 479.91 | 208.23 | 271.69 | 649.31 | 249.77 | 0.00 | 0.00 | 0.00 |
July | 543.78 | 270.22 | 273.56 | 797.22 | 220.09 | 0.00 | 0.00 | 0.00 |
August | 537.03 | 285.25 | 251.78 | 798.86 | 221.49 | 0.00 | 0.00 | 0.00 |
September | 391.00 | 179.17 | 211.83 | 544.54 | 269.96 | 0.00 | 0.00 | 0.00 |
October | 346.11 | 177.89 | 168.22 | 489.45 | 300.50 | 0.00 | 0.00 | 0.00 |
November | 315.52 | 160.29 | 155.22 | 360.11 | 426.62 | 0.00 | 0.00 | 0.00 |
December | 301.00 | 167.24 | 133.76 | 339.85 | 469.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 413.14 | 200.63 | 212.52 | 535.30 | 345.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 301.00 | 150.95 | 133.76 | 339.85 | 220.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 543.78 | 285.25 | 281.39 | 798.86 | 469.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 312.36 | 167.06 | 145.30 | 354.08 | 468.92 | 0.00 | 0.00 | 0.00 |
February | 329.51 | 150.95 | 178.56 | 350.86 | 428.44 | 0.00 | 0.00 | 0.00 |
March | 400.26 | 178.33 | 221.92 | 449.99 | 431.65 | 0.00 | 0.00 | 0.00 |
April | 511.72 | 256.64 | 255.08 | 668.97 | 345.75 | 0.00 | 0.00 | 0.00 |
May | 482.92 | 201.53 | 281.39 | 605.18 | 313.69 | 0.00 | 0.00 | 0.00 |
June | 479.91 | 208.23 | 271.69 | 649.31 | 249.77 | 0.00 | 0.00 | 0.00 |
July | 543.78 | 270.22 | 273.56 | 797.22 | 220.09 | 0.00 | 0.00 | 0.00 |
August | 537.03 | 285.25 | 251.78 | 798.86 | 221.49 | 0.00 | 0.00 | 0.00 |
September | 391.00 | 179.17 | 211.83 | 544.54 | 269.96 | 0.00 | 0.00 | 0.00 |
October | 346.11 | 177.89 | 168.22 | 489.45 | 300.50 | 0.00 | 0.00 | 0.00 |
November | 315.52 | 160.29 | 155.22 | 360.11 | 426.62 | 0.00 | 0.00 | 0.00 |
December | 301.00 | 167.24 | 133.76 | 339.85 | 469.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 413.14 | 200.63 | 212.52 | 535.30 | 345.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 301.00 | 150.95 | 133.76 | 339.85 | 220.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 543.78 | 285.25 | 281.39 | 798.86 | 469.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 312.36 | 167.06 | 145.30 | 354.07 | 468.92 | 0.00 | 0.00 | 0.00 |
February | 329.50 | 150.95 | 178.56 | 350.85 | 428.44 | 0.00 | 0.00 | 0.00 |
March | 400.25 | 178.33 | 221.92 | 449.98 | 431.65 | 0.00 | 0.00 | 0.00 |
April | 511.72 | 256.64 | 255.08 | 668.96 | 345.74 | 0.00 | 0.00 | 0.00 |
May | 482.91 | 201.53 | 281.38 | 605.17 | 313.68 | 0.00 | 0.00 | 0.00 |
June | 479.91 | 208.22 | 271.68 | 649.30 | 249.77 | 0.00 | 0.00 | 0.00 |
July | 543.77 | 270.21 | 273.56 | 797.21 | 220.09 | 0.00 | 0.00 | 0.00 |
August | 537.02 | 285.25 | 251.77 | 798.84 | 221.49 | 0.00 | 0.00 | 0.00 |
September | 390.99 | 179.17 | 211.82 | 544.53 | 269.96 | 0.00 | 0.00 | 0.00 |
October | 346.10 | 177.89 | 168.21 | 489.44 | 300.49 | 0.00 | 0.00 | 0.00 |
November | 315.51 | 160.29 | 155.22 | 360.10 | 426.61 | 0.00 | 0.00 | 0.00 |
December | 300.99 | 167.23 | 133.76 | 339.84 | 469.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 413.14 | 200.63 | 212.51 | 535.29 | 345.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 300.99 | 150.95 | 133.76 | 339.84 | 220.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 543.77 | 285.25 | 281.38 | 798.84 | 469.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 687.79 | 504.52 | 183.26 | 985.87 | 423.70 | 0.00 | 0.00 | 0.00 |
February | 540.56 | 332.96 | 207.61 | 725.10 | 391.52 | 0.00 | 0.00 | 0.00 |
March | 430.96 | 208.17 | 222.78 | 565.92 | 409.36 | 0.00 | 0.00 | 0.00 |
April | 360.07 | 137.30 | 222.77 | 506.42 | 340.07 | 0.00 | 0.00 | 0.00 |
May | 256.40 | 31.55 | 224.85 | 289.05 | 300.50 | 0.00 | 0.00 | 0.00 |
June | 224.93 | 13.58 | 211.35 | 253.60 | 237.06 | 0.00 | 0.00 | 0.00 |
July | 238.26 | 26.82 | 211.44 | 316.55 | 209.00 | 0.00 | 0.00 | 0.00 |
August | 306.10 | 96.55 | 209.54 | 474.95 | 218.43 | 0.00 | 0.00 | 0.00 |
September | 425.94 | 215.84 | 210.10 | 666.48 | 257.21 | 0.00 | 0.00 | 0.00 |
October | 541.69 | 362.13 | 179.56 | 848.83 | 282.77 | 0.00 | 0.00 | 0.00 |
November | 658.37 | 464.80 | 193.57 | 940.27 | 392.95 | 0.00 | 0.00 | 0.00 |
December | 734.78 | 559.26 | 175.52 | 1057.10 | 431.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 450.11 | 245.83 | 204.28 | 635.59 | 324.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 224.93 | 13.58 | 175.52 | 253.60 | 209.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 734.78 | 559.26 | 224.85 | 1057.10 | 431.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 687.79 | 504.52 | 183.26 | 985.87 | 423.70 | 0.00 | 0.00 | 0.00 |
February | 540.56 | 332.96 | 207.60 | 725.10 | 391.52 | 0.00 | 0.00 | 0.00 |
March | 430.96 | 208.17 | 222.78 | 565.92 | 409.36 | 0.00 | 0.00 | 0.00 |
April | 360.07 | 137.30 | 222.77 | 506.42 | 340.07 | 0.00 | 0.00 | 0.00 |
May | 256.40 | 31.55 | 224.85 | 289.05 | 300.50 | 0.00 | 0.00 | 0.00 |
June | 224.93 | 13.58 | 211.35 | 253.60 | 237.06 | 0.00 | 0.00 | 0.00 |
July | 238.26 | 26.82 | 211.44 | 316.55 | 209.00 | 0.00 | 0.00 | 0.00 |
August | 306.10 | 96.55 | 209.54 | 474.95 | 218.43 | 0.00 | 0.00 | 0.00 |
September | 425.93 | 215.84 | 210.10 | 666.48 | 257.21 | 0.00 | 0.00 | 0.00 |
October | 541.69 | 362.13 | 179.55 | 848.83 | 282.77 | 0.00 | 0.00 | 0.00 |
November | 658.37 | 464.80 | 193.57 | 940.27 | 392.95 | 0.00 | 0.00 | 0.00 |
December | 734.78 | 559.26 | 175.52 | 1057.10 | 431.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 450.11 | 245.83 | 204.28 | 635.59 | 324.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 224.93 | 13.58 | 175.52 | 253.60 | 209.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 734.78 | 559.26 | 224.85 | 1057.10 | 431.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 687.79 | 504.52 | 183.26 | 985.87 | 423.70 | 0.00 | 0.00 | 0.00 |
February | 540.56 | 332.96 | 207.61 | 725.10 | 391.52 | 0.00 | 0.00 | 0.00 |
March | 430.96 | 208.17 | 222.78 | 565.92 | 409.36 | 0.00 | 0.00 | 0.00 |
April | 360.07 | 137.30 | 222.77 | 506.42 | 340.07 | 0.00 | 0.00 | 0.00 |
May | 256.40 | 31.55 | 224.85 | 289.05 | 300.50 | 0.00 | 0.00 | 0.00 |
June | 224.93 | 13.58 | 211.35 | 253.60 | 237.06 | 0.00 | 0.00 | 0.00 |
July | 238.26 | 26.82 | 211.44 | 316.55 | 209.00 | 0.00 | 0.00 | 0.00 |
August | 306.10 | 96.55 | 209.54 | 474.95 | 218.43 | 0.00 | 0.00 | 0.00 |
September | 425.94 | 215.84 | 210.10 | 666.48 | 257.21 | 0.00 | 0.00 | 0.00 |
October | 541.69 | 362.13 | 179.56 | 848.83 | 282.77 | 0.00 | 0.00 | 0.00 |
November | 658.37 | 464.80 | 193.57 | 940.27 | 392.95 | 0.00 | 0.00 | 0.00 |
December | 734.78 | 559.26 | 175.52 | 1057.10 | 431.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 450.11 | 245.83 | 204.28 | 635.59 | 324.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 224.93 | 13.58 | 175.52 | 253.60 | 209.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 734.78 | 559.26 | 224.85 | 1057.10 | 431.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 687.79 | 504.52 | 183.26 | 985.87 | 423.70 | 0.00 | 0.00 | 0.00 |
February | 540.56 | 332.96 | 207.60 | 725.10 | 391.52 | 0.00 | 0.00 | 0.00 |
March | 430.96 | 208.17 | 222.78 | 565.92 | 409.36 | 0.00 | 0.00 | 0.00 |
April | 360.07 | 137.30 | 222.77 | 506.42 | 340.07 | 0.00 | 0.00 | 0.00 |
May | 256.40 | 31.55 | 224.85 | 289.05 | 300.50 | 0.00 | 0.00 | 0.00 |
June | 224.93 | 13.58 | 211.35 | 253.60 | 237.06 | 0.00 | 0.00 | 0.00 |
July | 238.26 | 26.82 | 211.44 | 316.55 | 209.00 | 0.00 | 0.00 | 0.00 |
August | 306.10 | 96.55 | 209.54 | 474.95 | 218.43 | 0.00 | 0.00 | 0.00 |
September | 425.93 | 215.84 | 210.10 | 666.48 | 257.21 | 0.00 | 0.00 | 0.00 |
October | 541.69 | 362.13 | 179.55 | 848.83 | 282.77 | 0.00 | 0.00 | 0.00 |
November | 658.37 | 464.80 | 193.57 | 940.27 | 392.95 | 0.00 | 0.00 | 0.00 |
December | 734.78 | 559.26 | 175.52 | 1057.10 | 431.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 450.11 | 245.83 | 204.28 | 635.59 | 324.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 224.93 | 13.58 | 175.52 | 253.60 | 209.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 734.78 | 559.26 | 224.85 | 1057.10 | 431.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 687.76 | 504.50 | 183.26 | 985.83 | 423.68 | 0.00 | 0.00 | 0.00 |
February | 540.54 | 332.95 | 207.60 | 725.07 | 391.51 | 0.00 | 0.00 | 0.00 |
March | 430.94 | 208.16 | 222.77 | 565.89 | 409.35 | 0.00 | 0.00 | 0.00 |
April | 360.06 | 137.29 | 222.77 | 506.40 | 340.06 | 0.00 | 0.00 | 0.00 |
May | 256.39 | 31.55 | 224.84 | 289.03 | 300.49 | 0.00 | 0.00 | 0.00 |
June | 224.92 | 13.58 | 211.34 | 253.59 | 237.05 | 0.00 | 0.00 | 0.00 |
July | 238.25 | 26.82 | 211.43 | 316.54 | 209.00 | 0.00 | 0.00 | 0.00 |
August | 306.09 | 96.55 | 209.54 | 474.93 | 218.42 | 0.00 | 0.00 | 0.00 |
September | 425.92 | 215.83 | 210.09 | 666.45 | 257.20 | 0.00 | 0.00 | 0.00 |
October | 541.67 | 362.12 | 179.55 | 848.80 | 282.76 | 0.00 | 0.00 | 0.00 |
November | 658.34 | 464.78 | 193.56 | 940.23 | 392.94 | 0.00 | 0.00 | 0.00 |
December | 734.75 | 559.24 | 175.51 | 1057.05 | 431.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 450.09 | 245.82 | 204.27 | 635.57 | 324.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 224.92 | 13.58 | 175.51 | 253.59 | 209.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 734.75 | 559.24 | 224.84 | 1057.05 | 431.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 297.31 | 149.95 | 147.36 | 348.14 | 526.24 | 0.00 | 0.00 | 0.00 |
February | 354.70 | 163.74 | 190.95 | 392.84 | 501.25 | 0.00 | 0.00 | 0.00 |
March | 406.58 | 179.88 | 226.70 | 455.77 | 515.64 | 0.00 | 0.00 | 0.00 |
April | 560.49 | 291.85 | 268.64 | 727.90 | 428.58 | 0.00 | 0.00 | 0.00 |
May | 550.58 | 254.31 | 296.27 | 705.71 | 356.19 | 0.00 | 0.00 | 0.00 |
June | 583.28 | 291.63 | 291.65 | 792.39 | 293.32 | 0.00 | 0.00 | 0.00 |
July | 617.44 | 330.39 | 287.05 | 885.86 | 267.00 | 0.00 | 0.00 | 0.00 |
August | 579.28 | 313.95 | 265.34 | 840.30 | 282.48 | 0.00 | 0.00 | 0.00 |
September | 495.97 | 265.39 | 230.59 | 702.73 | 306.48 | 0.00 | 0.00 | 0.00 |
October | 379.15 | 207.00 | 172.15 | 541.22 | 354.93 | 0.00 | 0.00 | 0.00 |
November | 342.48 | 179.14 | 163.34 | 408.29 | 511.24 | 0.00 | 0.00 | 0.00 |
December | 302.47 | 162.23 | 140.24 | 351.35 | 579.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 456.21 | 232.75 | 223.46 | 597.03 | 409.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 297.31 | 149.95 | 140.24 | 348.14 | 267.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 617.44 | 330.39 | 296.27 | 885.86 | 579.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 297.31 | 149.95 | 147.36 | 348.14 | 526.24 | 0.00 | 0.00 | 0.00 |
February | 354.70 | 163.74 | 190.95 | 392.84 | 501.25 | 0.00 | 0.00 | 0.00 |
March | 406.58 | 179.88 | 226.70 | 455.77 | 515.64 | 0.00 | 0.00 | 0.00 |
April | 560.49 | 291.85 | 268.64 | 727.90 | 428.58 | 0.00 | 0.00 | 0.00 |
May | 550.58 | 254.31 | 296.27 | 705.71 | 356.19 | 0.00 | 0.00 | 0.00 |
June | 583.28 | 291.63 | 291.65 | 792.39 | 293.32 | 0.00 | 0.00 | 0.00 |
July | 617.44 | 330.39 | 287.05 | 885.86 | 267.00 | 0.00 | 0.00 | 0.00 |
August | 579.28 | 313.95 | 265.34 | 840.30 | 282.48 | 0.00 | 0.00 | 0.00 |
September | 495.97 | 265.39 | 230.59 | 702.73 | 306.48 | 0.00 | 0.00 | 0.00 |
October | 379.15 | 207.00 | 172.15 | 541.22 | 354.93 | 0.00 | 0.00 | 0.00 |
November | 342.48 | 179.14 | 163.34 | 408.29 | 511.24 | 0.00 | 0.00 | 0.00 |
December | 302.47 | 162.23 | 140.24 | 351.35 | 579.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 456.21 | 232.75 | 223.46 | 597.03 | 409.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 297.31 | 149.95 | 140.24 | 348.14 | 267.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 617.44 | 330.39 | 296.27 | 885.86 | 579.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 297.31 | 149.95 | 147.36 | 348.13 | 526.23 | 0.00 | 0.00 | 0.00 |
February | 354.69 | 163.74 | 190.95 | 392.83 | 501.24 | 0.00 | 0.00 | 0.00 |
March | 406.57 | 179.87 | 226.70 | 455.76 | 515.63 | 0.00 | 0.00 | 0.00 |
April | 560.48 | 291.84 | 268.64 | 727.88 | 428.57 | 0.00 | 0.00 | 0.00 |
May | 550.57 | 254.31 | 296.26 | 705.69 | 356.19 | 0.00 | 0.00 | 0.00 |
June | 583.26 | 291.62 | 291.64 | 792.37 | 293.32 | 0.00 | 0.00 | 0.00 |
July | 617.43 | 330.38 | 287.05 | 885.84 | 266.99 | 0.00 | 0.00 | 0.00 |
August | 579.27 | 313.94 | 265.33 | 840.28 | 282.48 | 0.00 | 0.00 | 0.00 |
September | 495.96 | 265.38 | 230.58 | 702.72 | 306.48 | 0.00 | 0.00 | 0.00 |
October | 379.14 | 207.00 | 172.15 | 541.21 | 354.93 | 0.00 | 0.00 | 0.00 |
November | 342.48 | 179.14 | 163.34 | 408.28 | 511.23 | 0.00 | 0.00 | 0.00 |
December | 302.47 | 162.23 | 140.24 | 351.34 | 579.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 456.20 | 232.75 | 223.45 | 597.02 | 409.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 297.31 | 149.95 | 140.24 | 348.13 | 266.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 617.43 | 330.38 | 296.26 | 885.84 | 579.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 521.10 | 0.00 | 521.10 | 305.52 | 2053.09 | 0.00 | 0.00 | 0.00 |
February | 654.12 | 0.00 | 654.12 | 361.49 | 1872.26 | 0.00 | 0.00 | 0.00 |
March | 801.57 | 0.00 | 801.57 | 531.72 | 1916.10 | 0.00 | 0.00 | 0.00 |
April | 923.50 | 3.55 | 919.95 | 760.74 | 1505.85 | 0.00 | 0.00 | 0.00 |
May | 1109.76 | 51.68 | 1058.08 | 960.58 | 1323.17 | 0.00 | 0.00 | 0.00 |
June | 1182.50 | 115.61 | 1066.89 | 1238.47 | 1041.01 | 0.00 | 0.00 | 0.00 |
July | 1119.64 | 93.84 | 1025.80 | 1317.23 | 923.53 | 0.00 | 0.00 | 0.00 |
August | 929.83 | 18.62 | 911.21 | 1058.59 | 969.09 | 0.00 | 0.00 | 0.00 |
September | 787.00 | 0.12 | 786.88 | 818.18 | 1165.93 | 0.00 | 0.00 | 0.00 |
October | 624.28 | 0.00 | 624.28 | 713.17 | 1307.59 | 0.00 | 0.00 | 0.00 |
November | 565.24 | 0.00 | 565.24 | 355.49 | 1876.41 | 0.00 | 0.00 | 0.00 |
December | 485.10 | 0.00 | 485.10 | 278.01 | 2062.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 809.29 | 23.75 | 785.55 | 727.17 | 1499.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 485.10 | 0.00 | 485.10 | 278.01 | 923.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1182.50 | 115.61 | 1066.89 | 1317.23 | 2062.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 937.08 | 501.17 | 435.91 | 1086.97 | 1301.84 | 0.00 | 0.00 | 0.00 |
February | 988.52 | 452.85 | 535.67 | 1071.35 | 1191.95 | 0.00 | 0.00 | 0.00 |
March | 1200.76 | 534.99 | 665.77 | 1364.16 | 1218.48 | 0.00 | 0.00 | 0.00 |
April | 1535.16 | 769.91 | 765.25 | 2005.95 | 990.82 | 0.00 | 0.00 | 0.00 |
May | 1448.75 | 604.60 | 844.15 | 1810.16 | 906.15 | 0.00 | 0.00 | 0.00 |
June | 1439.73 | 624.67 | 815.06 | 1939.84 | 721.80 | 0.00 | 0.00 | 0.00 |
July | 1631.32 | 810.65 | 820.68 | 2378.59 | 649.05 | 0.00 | 0.00 | 0.00 |
August | 1611.06 | 855.74 | 755.32 | 2381.66 | 663.90 | 0.00 | 0.00 | 0.00 |
September | 1172.98 | 537.51 | 635.48 | 1636.14 | 765.41 | 0.00 | 0.00 | 0.00 |
October | 1038.30 | 533.66 | 504.64 | 1476.37 | 844.90 | 0.00 | 0.00 | 0.00 |
November | 946.54 | 480.88 | 465.66 | 1099.30 | 1193.88 | 0.00 | 0.00 | 0.00 |
December | 902.98 | 501.70 | 401.27 | 1048.48 | 1299.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1239.42 | 601.88 | 637.54 | 1611.98 | 977.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 902.98 | 452.85 | 401.27 | 1048.48 | 649.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1631.32 | 855.74 | 844.15 | 2381.66 | 1301.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3438.90 | 2522.59 | 916.31 | 4899.33 | 2084.80 | 0.00 | 0.00 | 0.00 |
February | 2702.79 | 1664.78 | 1038.01 | 3596.69 | 1897.27 | 0.00 | 0.00 | 0.00 |
March | 2154.75 | 1040.85 | 1113.91 | 2821.10 | 1966.63 | 0.00 | 0.00 | 0.00 |
April | 1800.35 | 686.49 | 1113.86 | 2534.21 | 1618.06 | 0.00 | 0.00 | 0.00 |
May | 1281.99 | 157.77 | 1124.22 | 1443.88 | 1455.85 | 0.00 | 0.00 | 0.00 |
June | 1124.64 | 67.90 | 1056.74 | 1279.72 | 1129.13 | 0.00 | 0.00 | 0.00 |
July | 1191.31 | 134.11 | 1057.20 | 1601.76 | 995.85 | 0.00 | 0.00 | 0.00 |
August | 1530.47 | 482.76 | 1047.71 | 2379.93 | 1056.51 | 0.00 | 0.00 | 0.00 |
September | 2129.65 | 1079.17 | 1050.48 | 3311.20 | 1251.30 | 0.00 | 0.00 | 0.00 |
October | 2708.42 | 1810.65 | 897.76 | 4220.04 | 1373.65 | 0.00 | 0.00 | 0.00 |
November | 3291.81 | 2323.96 | 967.84 | 4671.68 | 1908.55 | 0.00 | 0.00 | 0.00 |
December | 3673.84 | 2796.27 | 877.57 | 5260.57 | 2087.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2250.52 | 1229.13 | 1021.39 | 3167.22 | 1567.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1124.64 | 67.90 | 877.57 | 1279.72 | 995.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3673.84 | 2796.27 | 1124.22 | 5260.57 | 2087.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 891.93 | 449.85 | 442.08 | 1085.51 | 1406.51 | 0.00 | 0.00 | 0.00 |
February | 1064.08 | 491.23 | 572.85 | 1226.60 | 1291.13 | 0.00 | 0.00 | 0.00 |
March | 1219.72 | 539.62 | 680.10 | 1425.50 | 1316.62 | 0.00 | 0.00 | 0.00 |
April | 1681.45 | 875.53 | 805.92 | 2239.08 | 1101.04 | 0.00 | 0.00 | 0.00 |
May | 1651.71 | 762.92 | 888.79 | 2127.79 | 991.93 | 0.00 | 0.00 | 0.00 |
June | 1749.81 | 874.87 | 874.94 | 2396.78 | 785.74 | 0.00 | 0.00 | 0.00 |
July | 1852.31 | 991.16 | 861.16 | 2690.07 | 714.66 | 0.00 | 0.00 | 0.00 |
August | 1737.83 | 941.83 | 796.00 | 2561.47 | 742.52 | 0.00 | 0.00 | 0.00 |
September | 1487.90 | 796.16 | 691.75 | 2118.50 | 839.18 | 0.00 | 0.00 | 0.00 |
October | 1137.43 | 620.99 | 516.44 | 1660.27 | 930.89 | 0.00 | 0.00 | 0.00 |
November | 1027.44 | 537.42 | 490.02 | 1282.09 | 1294.47 | 0.00 | 0.00 | 0.00 |
December | 907.41 | 486.69 | 420.72 | 1125.76 | 1427.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1368.61 | 698.24 | 670.36 | 1831.25 | 1069.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 891.93 | 449.85 | 420.72 | 1085.51 | 714.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1852.31 | 991.16 | 888.79 | 2690.07 | 1427.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 521.10 | 0.00 | 521.10 | 359.36 | 1854.63 | 0.00 | 0.00 | 0.00 |
February | 654.12 | 0.00 | 654.12 | 413.50 | 1694.56 | 0.00 | 0.00 | 0.00 |
March | 801.57 | 0.00 | 801.57 | 577.49 | 1775.10 | 0.00 | 0.00 | 0.00 |
April | 923.50 | 3.55 | 919.95 | 781.89 | 1426.75 | 0.00 | 0.00 | 0.00 |
May | 1109.76 | 51.68 | 1058.08 | 988.77 | 1257.65 | 0.00 | 0.00 | 0.00 |
June | 1182.50 | 115.61 | 1066.89 | 1236.46 | 1008.49 | 0.00 | 0.00 | 0.00 |
July | 1119.64 | 93.84 | 1025.80 | 1301.68 | 905.45 | 0.00 | 0.00 | 0.00 |
August | 929.83 | 18.62 | 911.21 | 1049.32 | 946.25 | 0.00 | 0.00 | 0.00 |
September | 787.00 | 0.12 | 786.88 | 826.67 | 1112.37 | 0.00 | 0.00 | 0.00 |
October | 624.28 | 0.00 | 624.28 | 732.76 | 1230.99 | 0.00 | 0.00 | 0.00 |
November | 565.24 | 0.00 | 565.24 | 402.40 | 1716.19 | 0.00 | 0.00 | 0.00 |
December | 485.10 | 0.00 | 485.10 | 331.86 | 1865.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 809.29 | 23.75 | 785.55 | 752.27 | 1398.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 485.10 | 0.00 | 485.10 | 331.86 | 905.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1182.50 | 115.61 | 1066.89 | 1301.68 | 1865.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 937.08 | 501.17 | 435.91 | 1130.47 | 1193.57 | 0.00 | 0.00 | 0.00 |
February | 988.52 | 452.85 | 535.67 | 1105.67 | 1095.85 | 0.00 | 0.00 | 0.00 |
March | 1200.76 | 534.99 | 665.77 | 1392.68 | 1144.83 | 0.00 | 0.00 | 0.00 |
April | 1535.16 | 769.91 | 765.25 | 2013.67 | 952.28 | 0.00 | 0.00 | 0.00 |
May | 1448.75 | 604.60 | 844.15 | 1821.87 | 870.55 | 0.00 | 0.00 | 0.00 |
June | 1439.73 | 624.67 | 815.06 | 1935.69 | 705.56 | 0.00 | 0.00 | 0.00 |
July | 1631.32 | 810.65 | 820.68 | 2365.11 | 642.22 | 0.00 | 0.00 | 0.00 |
August | 1611.06 | 855.74 | 755.32 | 2370.16 | 654.80 | 0.00 | 0.00 | 0.00 |
September | 1172.98 | 537.51 | 635.48 | 1637.23 | 737.89 | 0.00 | 0.00 | 0.00 |
October | 1038.30 | 533.66 | 504.64 | 1485.77 | 806.18 | 0.00 | 0.00 | 0.00 |
November | 946.54 | 480.88 | 465.66 | 1131.94 | 1110.91 | 0.00 | 0.00 | 0.00 |
December | 902.98 | 501.70 | 401.27 | 1092.20 | 1195.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1239.42 | 601.88 | 637.54 | 1627.18 | 925.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 902.98 | 452.85 | 401.27 | 1092.20 | 642.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1631.32 | 855.74 | 844.15 | 2370.16 | 1195.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3438.90 | 2522.59 | 916.31 | 4948.18 | 1929.90 | 0.00 | 0.00 | 0.00 |
February | 2702.79 | 1664.78 | 1038.01 | 3637.58 | 1748.14 | 0.00 | 0.00 | 0.00 |
March | 2154.75 | 1040.85 | 1113.91 | 2856.58 | 1838.43 | 0.00 | 0.00 | 0.00 |
April | 1800.35 | 686.49 | 1113.86 | 2545.63 | 1542.18 | 0.00 | 0.00 | 0.00 |
May | 1281.99 | 157.77 | 1124.22 | 1462.75 | 1381.90 | 0.00 | 0.00 | 0.00 |
June | 1124.64 | 67.90 | 1056.74 | 1279.28 | 1092.10 | 0.00 | 0.00 | 0.00 |
July | 1191.31 | 134.11 | 1057.20 | 1589.28 | 976.35 | 0.00 | 0.00 | 0.00 |
August | 1530.47 | 482.76 | 1047.71 | 2366.71 | 1033.05 | 0.00 | 0.00 | 0.00 |
September | 2129.65 | 1079.17 | 1050.48 | 3308.29 | 1202.33 | 0.00 | 0.00 | 0.00 |
October | 2708.42 | 1810.65 | 897.76 | 4226.98 | 1312.75 | 0.00 | 0.00 | 0.00 |
November | 3291.81 | 2323.96 | 967.84 | 4704.25 | 1789.47 | 0.00 | 0.00 | 0.00 |
December | 3673.84 | 2796.27 | 877.57 | 5307.02 | 1944.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2250.52 | 1229.13 | 1021.39 | 3184.82 | 1481.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1124.64 | 67.90 | 877.57 | 1279.28 | 976.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3673.84 | 2796.27 | 1124.22 | 5307.02 | 1944.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 891.93 | 449.85 | 442.08 | 1109.96 | 1301.26 | 0.00 | 0.00 | 0.00 |
February | 1064.08 | 491.23 | 572.85 | 1249.30 | 1196.69 | 0.00 | 0.00 | 0.00 |
March | 1219.72 | 539.62 | 680.10 | 1444.11 | 1237.33 | 0.00 | 0.00 | 0.00 |
April | 1681.45 | 875.53 | 805.92 | 2240.23 | 1055.22 | 0.00 | 0.00 | 0.00 |
May | 1651.71 | 762.92 | 888.79 | 2130.75 | 950.13 | 0.00 | 0.00 | 0.00 |
June | 1749.81 | 874.87 | 874.94 | 2386.47 | 764.17 | 0.00 | 0.00 | 0.00 |
July | 1852.31 | 991.16 | 861.16 | 2672.95 | 702.06 | 0.00 | 0.00 | 0.00 |
August | 1737.83 | 941.83 | 796.00 | 2546.70 | 727.89 | 0.00 | 0.00 | 0.00 |
September | 1487.90 | 796.16 | 691.75 | 2114.75 | 809.14 | 0.00 | 0.00 | 0.00 |
October | 1137.43 | 620.99 | 516.44 | 1664.84 | 888.10 | 0.00 | 0.00 | 0.00 |
November | 1027.44 | 537.42 | 490.02 | 1301.15 | 1209.21 | 0.00 | 0.00 | 0.00 |
December | 907.41 | 486.69 | 420.72 | 1150.05 | 1322.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1368.61 | 698.24 | 670.36 | 1837.15 | 1012.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 891.93 | 449.85 | 420.72 | 1109.96 | 702.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1852.31 | 991.16 | 888.79 | 2672.95 | 1322.81 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.279146E+09 | 0.00 | 0.279146E+09 | 0.131464E+09 | 0.122932E+10 |
February | 0.316493E+09 | 0.00 | 0.316493E+09 | 0.146521E+09 | 0.101552E+10 |
March | 0.429391E+09 | 0.00 | 0.429391E+09 | 0.251630E+09 | 0.114079E+10 |
April | 0.478751E+09 | 1842638.00 | 0.476908E+09 | 0.361411E+09 | 0.865829E+09 |
May | 0.594482E+09 | 27682335.67 | 0.566800E+09 | 0.494216E+09 | 0.751934E+09 |
June | 0.613017E+09 | 59932695.13 | 0.553085E+09 | 0.629024E+09 | 0.575161E+09 |
July | 0.599778E+09 | 50271329.26 | 0.549507E+09 | 0.685408E+09 | 0.526971E+09 |
August | 0.498096E+09 | 9973877.46 | 0.488122E+09 | 0.545108E+09 | 0.554591E+09 |
September | 0.407987E+09 | 63947.56 | 0.407923E+09 | 0.407153E+09 | 0.656837E+09 |
October | 0.334417E+09 | 0.00 | 0.334417E+09 | 0.355430E+09 | 0.776624E+09 |
November | 0.293023E+09 | 0.00 | 0.293023E+09 | 0.151232E+09 | 0.109376E+10 |
December | 0.259861E+09 | 0.00 | 0.259861E+09 | 0.107495E+09 | 0.126670E+10 |
Annual Sum or Average | 0.510444E+10 | 0.149767E+09 | 0.495467E+10 | 0.426609E+10 | 0.104541E+11 |
Minimum of Months | 0.259861E+09 | 0.00 | 0.259861E+09 | 0.107495E+09 | 0.526971E+09 |
Maximum of Months | 0.613017E+09 | 59932695.13 | 0.566800E+09 | 0.685408E+09 | 0.126670E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.279146E+09 | 0.00 | 0.279146E+09 | 0.131464E+09 | 0.122932E+10 |
February | 0.316493E+09 | 0.00 | 0.316493E+09 | 0.146521E+09 | 0.101552E+10 |
March | 0.429391E+09 | 0.00 | 0.429391E+09 | 0.251630E+09 | 0.114079E+10 |
April | 0.478750E+09 | 1842635.79 | 0.476908E+09 | 0.361411E+09 | 0.865829E+09 |
May | 0.594482E+09 | 27682302.45 | 0.566799E+09 | 0.494216E+09 | 0.751934E+09 |
June | 0.613017E+09 | 59932623.22 | 0.553084E+09 | 0.629023E+09 | 0.575161E+09 |
July | 0.599778E+09 | 50271268.94 | 0.549507E+09 | 0.685407E+09 | 0.526971E+09 |
August | 0.498095E+09 | 9973865.49 | 0.488122E+09 | 0.545108E+09 | 0.554591E+09 |
September | 0.407987E+09 | 63947.48 | 0.407923E+09 | 0.407153E+09 | 0.656837E+09 |
October | 0.334416E+09 | 0.00 | 0.334416E+09 | 0.355429E+09 | 0.776624E+09 |
November | 0.293023E+09 | 0.00 | 0.293023E+09 | 0.151232E+09 | 0.109376E+10 |
December | 0.259861E+09 | 0.00 | 0.259861E+09 | 0.107495E+09 | 0.126670E+10 |
Annual Sum or Average | 0.510444E+10 | 0.149767E+09 | 0.495467E+10 | 0.426609E+10 | 0.104541E+11 |
Minimum of Months | 0.259861E+09 | 0.00 | 0.259861E+09 | 0.107495E+09 | 0.526971E+09 |
Maximum of Months | 0.613017E+09 | 59932623.22 | 0.566799E+09 | 0.685407E+09 | 0.126670E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.279146E+09 | 0.00 | 0.279146E+09 | 0.131464E+09 | 0.122932E+10 |
February | 0.316493E+09 | 0.00 | 0.316493E+09 | 0.146521E+09 | 0.101552E+10 |
March | 0.429391E+09 | 0.00 | 0.429391E+09 | 0.251630E+09 | 0.114079E+10 |
April | 0.478751E+09 | 1842638.00 | 0.476908E+09 | 0.361411E+09 | 0.865829E+09 |
May | 0.594482E+09 | 27682335.67 | 0.566800E+09 | 0.494216E+09 | 0.751934E+09 |
June | 0.613017E+09 | 59932695.13 | 0.553085E+09 | 0.629024E+09 | 0.575161E+09 |
July | 0.599778E+09 | 50271329.26 | 0.549507E+09 | 0.685408E+09 | 0.526971E+09 |
August | 0.498096E+09 | 9973877.46 | 0.488122E+09 | 0.545108E+09 | 0.554591E+09 |
September | 0.407987E+09 | 63947.56 | 0.407923E+09 | 0.407153E+09 | 0.656837E+09 |
October | 0.334417E+09 | 0.00 | 0.334417E+09 | 0.355430E+09 | 0.776624E+09 |
November | 0.293023E+09 | 0.00 | 0.293023E+09 | 0.151232E+09 | 0.109376E+10 |
December | 0.259861E+09 | 0.00 | 0.259861E+09 | 0.107495E+09 | 0.126670E+10 |
Annual Sum or Average | 0.510444E+10 | 0.149767E+09 | 0.495467E+10 | 0.426609E+10 | 0.104541E+11 |
Minimum of Months | 0.259861E+09 | 0.00 | 0.259861E+09 | 0.107495E+09 | 0.526971E+09 |
Maximum of Months | 0.613017E+09 | 59932695.13 | 0.566800E+09 | 0.685408E+09 | 0.126670E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.279146E+09 | 0.00 | 0.279146E+09 | 0.131464E+09 | 0.122932E+10 |
February | 0.316493E+09 | 0.00 | 0.316493E+09 | 0.146521E+09 | 0.101552E+10 |
March | 0.429391E+09 | 0.00 | 0.429391E+09 | 0.251630E+09 | 0.114079E+10 |
April | 0.478750E+09 | 1842635.79 | 0.476908E+09 | 0.361411E+09 | 0.865829E+09 |
May | 0.594482E+09 | 27682302.45 | 0.566799E+09 | 0.494216E+09 | 0.751934E+09 |
June | 0.613017E+09 | 59932623.22 | 0.553084E+09 | 0.629023E+09 | 0.575161E+09 |
July | 0.599778E+09 | 50271268.94 | 0.549507E+09 | 0.685407E+09 | 0.526971E+09 |
August | 0.498095E+09 | 9973865.49 | 0.488122E+09 | 0.545108E+09 | 0.554591E+09 |
September | 0.407987E+09 | 63947.48 | 0.407923E+09 | 0.407153E+09 | 0.656837E+09 |
October | 0.334416E+09 | 0.00 | 0.334416E+09 | 0.355429E+09 | 0.776624E+09 |
November | 0.293023E+09 | 0.00 | 0.293023E+09 | 0.151232E+09 | 0.109376E+10 |
December | 0.259861E+09 | 0.00 | 0.259861E+09 | 0.107495E+09 | 0.126670E+10 |
Annual Sum or Average | 0.510444E+10 | 0.149767E+09 | 0.495467E+10 | 0.426609E+10 | 0.104541E+11 |
Minimum of Months | 0.259861E+09 | 0.00 | 0.259861E+09 | 0.107495E+09 | 0.526971E+09 |
Maximum of Months | 0.613017E+09 | 59932623.22 | 0.566799E+09 | 0.685407E+09 | 0.126670E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.279135E+09 | 0.00 | 0.279135E+09 | 0.131459E+09 | 0.122927E+10 |
February | 0.316480E+09 | 0.00 | 0.316480E+09 | 0.146515E+09 | 0.101548E+10 |
March | 0.429374E+09 | 0.00 | 0.429374E+09 | 0.251620E+09 | 0.114074E+10 |
April | 0.478731E+09 | 1842563.74 | 0.476889E+09 | 0.361396E+09 | 0.865794E+09 |
May | 0.594458E+09 | 27681219.95 | 0.566777E+09 | 0.494197E+09 | 0.751904E+09 |
June | 0.612993E+09 | 59930279.58 | 0.553062E+09 | 0.628998E+09 | 0.575138E+09 |
July | 0.599754E+09 | 50269303.10 | 0.549485E+09 | 0.685380E+09 | 0.526950E+09 |
August | 0.498076E+09 | 9973475.47 | 0.488102E+09 | 0.545086E+09 | 0.554568E+09 |
September | 0.407971E+09 | 63944.98 | 0.407907E+09 | 0.407137E+09 | 0.656811E+09 |
October | 0.334403E+09 | 0.00 | 0.334403E+09 | 0.355415E+09 | 0.776593E+09 |
November | 0.293011E+09 | 0.00 | 0.293011E+09 | 0.151226E+09 | 0.109372E+10 |
December | 0.259850E+09 | 0.00 | 0.259850E+09 | 0.107491E+09 | 0.126665E+10 |
Annual Sum or Average | 0.510424E+10 | 0.149761E+09 | 0.495448E+10 | 0.426592E+10 | 0.104536E+11 |
Minimum of Months | 0.259850E+09 | 0.00 | 0.259850E+09 | 0.107491E+09 | 0.526950E+09 |
Maximum of Months | 0.612993E+09 | 59930279.58 | 0.566777E+09 | 0.685380E+09 | 0.126665E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.836630E+09 | 0.447450E+09 | 0.389181E+09 | 0.948360E+09 | 0.125597E+10 |
February | 0.797150E+09 | 0.365181E+09 | 0.431969E+09 | 0.848799E+09 | 0.103649E+10 |
March | 0.107205E+10 | 0.477647E+09 | 0.594403E+09 | 0.120525E+10 | 0.115614E+10 |
April | 0.132639E+10 | 0.665212E+09 | 0.661179E+09 | 0.173397E+10 | 0.896171E+09 |
May | 0.129346E+10 | 0.539791E+09 | 0.753668E+09 | 0.162092E+10 | 0.840184E+09 |
June | 0.124394E+10 | 0.539723E+09 | 0.704216E+09 | 0.168301E+10 | 0.647404E+09 |
July | 0.145646E+10 | 0.723754E+09 | 0.732707E+09 | 0.213528E+10 | 0.589496E+09 |
August | 0.143837E+10 | 0.764016E+09 | 0.674358E+09 | 0.213966E+10 | 0.593249E+09 |
September | 0.101347E+10 | 0.464409E+09 | 0.549058E+09 | 0.141145E+10 | 0.699748E+09 |
October | 0.927008E+09 | 0.476458E+09 | 0.450550E+09 | 0.131093E+10 | 0.804853E+09 |
November | 0.817816E+09 | 0.415484E+09 | 0.402332E+09 | 0.933398E+09 | 0.110580E+10 |
December | 0.806187E+09 | 0.447926E+09 | 0.358261E+09 | 0.910246E+09 | 0.125731E+10 |
Annual Sum or Average | 0.130289E+11 | 0.632705E+10 | 0.670188E+10 | 0.168813E+11 | 0.108828E+11 |
Minimum of Months | 0.797150E+09 | 0.365181E+09 | 0.358261E+09 | 0.848799E+09 | 0.589496E+09 |
Maximum of Months | 0.145646E+10 | 0.764016E+09 | 0.753668E+09 | 0.213966E+10 | 0.125731E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.836630E+09 | 0.447450E+09 | 0.389181E+09 | 0.948360E+09 | 0.125597E+10 |
February | 0.797150E+09 | 0.365181E+09 | 0.431969E+09 | 0.848799E+09 | 0.103649E+10 |
March | 0.107205E+10 | 0.477647E+09 | 0.594403E+09 | 0.120525E+10 | 0.115614E+10 |
April | 0.132639E+10 | 0.665212E+09 | 0.661179E+09 | 0.173397E+10 | 0.896171E+09 |
May | 0.129346E+10 | 0.539791E+09 | 0.753668E+09 | 0.162092E+10 | 0.840184E+09 |
June | 0.124394E+10 | 0.539723E+09 | 0.704216E+09 | 0.168301E+10 | 0.647404E+09 |
July | 0.145646E+10 | 0.723754E+09 | 0.732707E+09 | 0.213528E+10 | 0.589496E+09 |
August | 0.143837E+10 | 0.764016E+09 | 0.674358E+09 | 0.213966E+10 | 0.593249E+09 |
September | 0.101347E+10 | 0.464409E+09 | 0.549058E+09 | 0.141145E+10 | 0.699748E+09 |
October | 0.927008E+09 | 0.476458E+09 | 0.450550E+09 | 0.131093E+10 | 0.804853E+09 |
November | 0.817816E+09 | 0.415484E+09 | 0.402332E+09 | 0.933398E+09 | 0.110580E+10 |
December | 0.806187E+09 | 0.447926E+09 | 0.358261E+09 | 0.910246E+09 | 0.125731E+10 |
Annual Sum or Average | 0.130289E+11 | 0.632705E+10 | 0.670188E+10 | 0.168813E+11 | 0.108828E+11 |
Minimum of Months | 0.797150E+09 | 0.365181E+09 | 0.358261E+09 | 0.848799E+09 | 0.589496E+09 |
Maximum of Months | 0.145646E+10 | 0.764016E+09 | 0.753668E+09 | 0.213966E+10 | 0.125731E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.836615E+09 | 0.447442E+09 | 0.389174E+09 | 0.948343E+09 | 0.125594E+10 |
February | 0.797135E+09 | 0.365174E+09 | 0.431961E+09 | 0.848783E+09 | 0.103647E+10 |
March | 0.107203E+10 | 0.477639E+09 | 0.594392E+09 | 0.120523E+10 | 0.115612E+10 |
April | 0.132637E+10 | 0.665199E+09 | 0.661167E+09 | 0.173393E+10 | 0.896155E+09 |
May | 0.129344E+10 | 0.539781E+09 | 0.753655E+09 | 0.162089E+10 | 0.840169E+09 |
June | 0.124392E+10 | 0.539714E+09 | 0.704203E+09 | 0.168298E+10 | 0.647392E+09 |
July | 0.145643E+10 | 0.723741E+09 | 0.732693E+09 | 0.213524E+10 | 0.589485E+09 |
August | 0.143835E+10 | 0.764002E+09 | 0.674345E+09 | 0.213962E+10 | 0.593238E+09 |
September | 0.101345E+10 | 0.464401E+09 | 0.549048E+09 | 0.141143E+10 | 0.699735E+09 |
October | 0.926991E+09 | 0.476449E+09 | 0.450541E+09 | 0.131091E+10 | 0.804838E+09 |
November | 0.817801E+09 | 0.415477E+09 | 0.402324E+09 | 0.933381E+09 | 0.110578E+10 |
December | 0.806173E+09 | 0.447918E+09 | 0.358255E+09 | 0.910229E+09 | 0.125728E+10 |
Annual Sum or Average | 0.130287E+11 | 0.632694E+10 | 0.670176E+10 | 0.168810E+11 | 0.108826E+11 |
Minimum of Months | 0.797135E+09 | 0.365174E+09 | 0.358255E+09 | 0.848783E+09 | 0.589485E+09 |
Maximum of Months | 0.145643E+10 | 0.764002E+09 | 0.753655E+09 | 0.213962E+10 | 0.125728E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184217E+10 | 0.135132E+10 | 0.490854E+09 | 0.264057E+10 | 0.113483E+10 |
February | 0.130773E+10 | 0.805495E+09 | 0.502238E+09 | 0.175416E+10 | 0.947168E+09 |
March | 0.115427E+10 | 0.557568E+09 | 0.596704E+09 | 0.151575E+10 | 0.109644E+10 |
April | 0.933312E+09 | 0.355881E+09 | 0.577431E+09 | 0.131263E+10 | 0.881460E+09 |
May | 0.686743E+09 | 84513120.71 | 0.602230E+09 | 0.774181E+09 | 0.804862E+09 |
June | 0.583022E+09 | 35200758.67 | 0.547821E+09 | 0.657333E+09 | 0.614461E+09 |
July | 0.638166E+09 | 71839307.42 | 0.566327E+09 | 0.847860E+09 | 0.559796E+09 |
August | 0.819852E+09 | 0.258607E+09 | 0.561245E+09 | 0.127211E+10 | 0.585031E+09 |
September | 0.110402E+10 | 0.559447E+09 | 0.544577E+09 | 0.172751E+10 | 0.666689E+09 |
October | 0.145086E+10 | 0.969942E+09 | 0.480920E+09 | 0.227351E+10 | 0.757363E+09 |
November | 0.170649E+10 | 0.120476E+10 | 0.501735E+09 | 0.243718E+10 | 0.101854E+10 |
December | 0.196803E+10 | 0.149793E+10 | 0.470102E+09 | 0.283133E+10 | 0.115572E+10 |
Annual Sum or Average | 0.141947E+11 | 0.775249E+10 | 0.644218E+10 | 0.200441E+11 | 0.102224E+11 |
Minimum of Months | 0.583022E+09 | 35200758.67 | 0.470102E+09 | 0.657333E+09 | 0.559796E+09 |
Maximum of Months | 0.196803E+10 | 0.149793E+10 | 0.602230E+09 | 0.283133E+10 | 0.115572E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184217E+10 | 0.135131E+10 | 0.490853E+09 | 0.264056E+10 | 0.113483E+10 |
February | 0.130773E+10 | 0.805494E+09 | 0.502238E+09 | 0.175415E+10 | 0.947168E+09 |
March | 0.115427E+10 | 0.557567E+09 | 0.596703E+09 | 0.151575E+10 | 0.109644E+10 |
April | 0.933311E+09 | 0.355880E+09 | 0.577431E+09 | 0.131263E+10 | 0.881459E+09 |
May | 0.686742E+09 | 84513019.30 | 0.602229E+09 | 0.774180E+09 | 0.804862E+09 |
June | 0.583021E+09 | 35200716.44 | 0.547821E+09 | 0.657332E+09 | 0.614461E+09 |
July | 0.638166E+09 | 71839221.22 | 0.566327E+09 | 0.847859E+09 | 0.559795E+09 |
August | 0.819852E+09 | 0.258607E+09 | 0.561245E+09 | 0.127210E+10 | 0.585031E+09 |
September | 0.110402E+10 | 0.559446E+09 | 0.544576E+09 | 0.172750E+10 | 0.666689E+09 |
October | 0.145086E+10 | 0.969941E+09 | 0.480920E+09 | 0.227351E+10 | 0.757363E+09 |
November | 0.170649E+10 | 0.120476E+10 | 0.501735E+09 | 0.243717E+10 | 0.101854E+10 |
December | 0.196803E+10 | 0.149792E+10 | 0.470102E+09 | 0.283133E+10 | 0.115572E+10 |
Annual Sum or Average | 0.141947E+11 | 0.775248E+10 | 0.644218E+10 | 0.200441E+11 | 0.102223E+11 |
Minimum of Months | 0.583021E+09 | 35200716.44 | 0.470102E+09 | 0.657332E+09 | 0.559795E+09 |
Maximum of Months | 0.196803E+10 | 0.149792E+10 | 0.602229E+09 | 0.283133E+10 | 0.115572E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184217E+10 | 0.135132E+10 | 0.490854E+09 | 0.264057E+10 | 0.113483E+10 |
February | 0.130773E+10 | 0.805495E+09 | 0.502238E+09 | 0.175416E+10 | 0.947168E+09 |
March | 0.115427E+10 | 0.557568E+09 | 0.596704E+09 | 0.151575E+10 | 0.109644E+10 |
April | 0.933312E+09 | 0.355881E+09 | 0.577431E+09 | 0.131263E+10 | 0.881460E+09 |
May | 0.686743E+09 | 84513120.71 | 0.602230E+09 | 0.774181E+09 | 0.804862E+09 |
June | 0.583022E+09 | 35200758.67 | 0.547821E+09 | 0.657333E+09 | 0.614461E+09 |
July | 0.638166E+09 | 71839307.42 | 0.566327E+09 | 0.847860E+09 | 0.559796E+09 |
August | 0.819852E+09 | 0.258607E+09 | 0.561245E+09 | 0.127211E+10 | 0.585031E+09 |
September | 0.110402E+10 | 0.559447E+09 | 0.544577E+09 | 0.172751E+10 | 0.666689E+09 |
October | 0.145086E+10 | 0.969942E+09 | 0.480920E+09 | 0.227351E+10 | 0.757363E+09 |
November | 0.170649E+10 | 0.120476E+10 | 0.501735E+09 | 0.243718E+10 | 0.101854E+10 |
December | 0.196803E+10 | 0.149793E+10 | 0.470102E+09 | 0.283133E+10 | 0.115572E+10 |
Annual Sum or Average | 0.141947E+11 | 0.775249E+10 | 0.644218E+10 | 0.200441E+11 | 0.102224E+11 |
Minimum of Months | 0.583022E+09 | 35200758.67 | 0.470102E+09 | 0.657333E+09 | 0.559796E+09 |
Maximum of Months | 0.196803E+10 | 0.149793E+10 | 0.602230E+09 | 0.283133E+10 | 0.115572E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184217E+10 | 0.135131E+10 | 0.490853E+09 | 0.264056E+10 | 0.113483E+10 |
February | 0.130773E+10 | 0.805494E+09 | 0.502238E+09 | 0.175415E+10 | 0.947168E+09 |
March | 0.115427E+10 | 0.557567E+09 | 0.596703E+09 | 0.151575E+10 | 0.109644E+10 |
April | 0.933311E+09 | 0.355880E+09 | 0.577431E+09 | 0.131263E+10 | 0.881459E+09 |
May | 0.686742E+09 | 84513019.30 | 0.602229E+09 | 0.774180E+09 | 0.804862E+09 |
June | 0.583021E+09 | 35200716.44 | 0.547821E+09 | 0.657332E+09 | 0.614461E+09 |
July | 0.638166E+09 | 71839221.22 | 0.566327E+09 | 0.847859E+09 | 0.559795E+09 |
August | 0.819852E+09 | 0.258607E+09 | 0.561245E+09 | 0.127210E+10 | 0.585031E+09 |
September | 0.110402E+10 | 0.559446E+09 | 0.544576E+09 | 0.172750E+10 | 0.666689E+09 |
October | 0.145086E+10 | 0.969941E+09 | 0.480920E+09 | 0.227351E+10 | 0.757363E+09 |
November | 0.170649E+10 | 0.120476E+10 | 0.501735E+09 | 0.243717E+10 | 0.101854E+10 |
December | 0.196803E+10 | 0.149792E+10 | 0.470102E+09 | 0.283133E+10 | 0.115572E+10 |
Annual Sum or Average | 0.141947E+11 | 0.775248E+10 | 0.644218E+10 | 0.200441E+11 | 0.102223E+11 |
Minimum of Months | 0.583021E+09 | 35200716.44 | 0.470102E+09 | 0.657332E+09 | 0.559795E+09 |
Maximum of Months | 0.196803E+10 | 0.149792E+10 | 0.602229E+09 | 0.283133E+10 | 0.115572E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184210E+10 | 0.135126E+10 | 0.490834E+09 | 0.264046E+10 | 0.113478E+10 |
February | 0.130768E+10 | 0.805462E+09 | 0.502218E+09 | 0.175408E+10 | 0.947130E+09 |
March | 0.115422E+10 | 0.557545E+09 | 0.596680E+09 | 0.151569E+10 | 0.109639E+10 |
April | 0.933274E+09 | 0.355867E+09 | 0.577408E+09 | 0.131258E+10 | 0.881424E+09 |
May | 0.686715E+09 | 84509714.46 | 0.602205E+09 | 0.774149E+09 | 0.804830E+09 |
June | 0.582998E+09 | 35199339.93 | 0.547799E+09 | 0.657306E+09 | 0.614437E+09 |
July | 0.638141E+09 | 71836411.98 | 0.566304E+09 | 0.847826E+09 | 0.559773E+09 |
August | 0.819819E+09 | 0.258597E+09 | 0.561223E+09 | 0.127205E+10 | 0.585008E+09 |
September | 0.110398E+10 | 0.559425E+09 | 0.544555E+09 | 0.172744E+10 | 0.666663E+09 |
October | 0.145080E+10 | 0.969903E+09 | 0.480901E+09 | 0.227342E+10 | 0.757333E+09 |
November | 0.170642E+10 | 0.120471E+10 | 0.501715E+09 | 0.243708E+10 | 0.101850E+10 |
December | 0.196795E+10 | 0.149787E+10 | 0.470083E+09 | 0.283122E+10 | 0.115567E+10 |
Annual Sum or Average | 0.141941E+11 | 0.775218E+10 | 0.644192E+10 | 0.200433E+11 | 0.102219E+11 |
Minimum of Months | 0.582998E+09 | 35199339.93 | 0.470083E+09 | 0.657306E+09 | 0.559773E+09 |
Maximum of Months | 0.196795E+10 | 0.149787E+10 | 0.602205E+09 | 0.283122E+10 | 0.115567E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.796326E+09 | 0.401631E+09 | 0.394695E+09 | 0.932450E+09 | 0.140949E+10 |
February | 0.858082E+09 | 0.396131E+09 | 0.461951E+09 | 0.950348E+09 | 0.121262E+10 |
March | 0.108898E+10 | 0.481781E+09 | 0.607196E+09 | 0.122072E+10 | 0.138109E+10 |
April | 0.145279E+10 | 0.756465E+09 | 0.696324E+09 | 0.188671E+10 | 0.111087E+10 |
May | 0.147466E+10 | 0.681145E+09 | 0.793519E+09 | 0.189016E+10 | 0.954027E+09 |
June | 0.151185E+10 | 0.755896E+09 | 0.755954E+09 | 0.205387E+10 | 0.760290E+09 |
July | 0.165376E+10 | 0.884913E+09 | 0.768848E+09 | 0.237268E+10 | 0.715130E+09 |
August | 0.155155E+10 | 0.840876E+09 | 0.710675E+09 | 0.225065E+10 | 0.756597E+09 |
September | 0.128556E+10 | 0.687885E+09 | 0.597676E+09 | 0.182149E+10 | 0.794398E+09 |
October | 0.101551E+10 | 0.554426E+09 | 0.461085E+09 | 0.144961E+10 | 0.950653E+09 |
November | 0.887720E+09 | 0.464340E+09 | 0.423380E+09 | 0.105829E+10 | 0.132513E+10 |
December | 0.810143E+09 | 0.434523E+09 | 0.375620E+09 | 0.941050E+09 | 0.155278E+10 |
Annual Sum or Average | 0.143869E+11 | 0.734001E+10 | 0.704692E+10 | 0.188280E+11 | 0.129231E+11 |
Minimum of Months | 0.796326E+09 | 0.396131E+09 | 0.375620E+09 | 0.932450E+09 | 0.715130E+09 |
Maximum of Months | 0.165376E+10 | 0.884913E+09 | 0.793519E+09 | 0.237268E+10 | 0.155278E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.796326E+09 | 0.401631E+09 | 0.394695E+09 | 0.932450E+09 | 0.140949E+10 |
February | 0.858082E+09 | 0.396131E+09 | 0.461951E+09 | 0.950348E+09 | 0.121262E+10 |
March | 0.108898E+10 | 0.481781E+09 | 0.607196E+09 | 0.122072E+10 | 0.138109E+10 |
April | 0.145279E+10 | 0.756465E+09 | 0.696324E+09 | 0.188671E+10 | 0.111087E+10 |
May | 0.147466E+10 | 0.681145E+09 | 0.793519E+09 | 0.189016E+10 | 0.954027E+09 |
June | 0.151185E+10 | 0.755896E+09 | 0.755954E+09 | 0.205387E+10 | 0.760290E+09 |
July | 0.165376E+10 | 0.884913E+09 | 0.768848E+09 | 0.237268E+10 | 0.715130E+09 |
August | 0.155155E+10 | 0.840876E+09 | 0.710675E+09 | 0.225065E+10 | 0.756597E+09 |
September | 0.128556E+10 | 0.687885E+09 | 0.597676E+09 | 0.182149E+10 | 0.794398E+09 |
October | 0.101551E+10 | 0.554426E+09 | 0.461085E+09 | 0.144961E+10 | 0.950653E+09 |
November | 0.887720E+09 | 0.464340E+09 | 0.423380E+09 | 0.105829E+10 | 0.132513E+10 |
December | 0.810143E+09 | 0.434523E+09 | 0.375620E+09 | 0.941050E+09 | 0.155278E+10 |
Annual Sum or Average | 0.143869E+11 | 0.734001E+10 | 0.704692E+10 | 0.188280E+11 | 0.129231E+11 |
Minimum of Months | 0.796326E+09 | 0.396131E+09 | 0.375620E+09 | 0.932450E+09 | 0.715130E+09 |
Maximum of Months | 0.165376E+10 | 0.884913E+09 | 0.793519E+09 | 0.237268E+10 | 0.155278E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.796311E+09 | 0.401623E+09 | 0.394688E+09 | 0.932433E+09 | 0.140946E+10 |
February | 0.858067E+09 | 0.396124E+09 | 0.461943E+09 | 0.950330E+09 | 0.121260E+10 |
March | 0.108896E+10 | 0.481772E+09 | 0.607185E+09 | 0.122070E+10 | 0.138107E+10 |
April | 0.145276E+10 | 0.756451E+09 | 0.696311E+09 | 0.188667E+10 | 0.111085E+10 |
May | 0.147464E+10 | 0.681132E+09 | 0.793505E+09 | 0.189013E+10 | 0.954010E+09 |
June | 0.151182E+10 | 0.755882E+09 | 0.755940E+09 | 0.205383E+10 | 0.760276E+09 |
July | 0.165373E+10 | 0.884897E+09 | 0.768834E+09 | 0.237264E+10 | 0.715117E+09 |
August | 0.155152E+10 | 0.840861E+09 | 0.710662E+09 | 0.225061E+10 | 0.756583E+09 |
September | 0.128554E+10 | 0.687873E+09 | 0.597666E+09 | 0.182145E+10 | 0.794384E+09 |
October | 0.101549E+10 | 0.554416E+09 | 0.461077E+09 | 0.144958E+10 | 0.950635E+09 |
November | 0.887704E+09 | 0.464331E+09 | 0.423372E+09 | 0.105827E+10 | 0.132510E+10 |
December | 0.810129E+09 | 0.434515E+09 | 0.375614E+09 | 0.941033E+09 | 0.155275E+10 |
Annual Sum or Average | 0.143867E+11 | 0.733988E+10 | 0.704680E+10 | 0.188277E+11 | 0.129228E+11 |
Minimum of Months | 0.796311E+09 | 0.396124E+09 | 0.375614E+09 | 0.932433E+09 | 0.715117E+09 |
Maximum of Months | 0.165373E+10 | 0.884897E+09 | 0.793505E+09 | 0.237264E+10 | 0.155275E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139571E+10 | 0.00 | 0.139571E+10 | 0.818315E+09 | 0.549900E+10 |
February | 0.158244E+10 | 0.00 | 0.158244E+10 | 0.874510E+09 | 0.452937E+10 |
March | 0.214693E+10 | 0.00 | 0.214693E+10 | 0.142415E+10 | 0.513207E+10 |
April | 0.239372E+10 | 9213078.61 | 0.238451E+10 | 0.197184E+10 | 0.390316E+10 |
May | 0.297238E+10 | 0.138410E+09 | 0.283397E+10 | 0.257281E+10 | 0.354397E+10 |
June | 0.306505E+10 | 0.299660E+09 | 0.276539E+10 | 0.321010E+10 | 0.269830E+10 |
July | 0.299885E+10 | 0.251354E+09 | 0.274750E+10 | 0.352807E+10 | 0.247358E+10 |
August | 0.249045E+10 | 49868784.28 | 0.244058E+10 | 0.283534E+10 | 0.259561E+10 |
September | 0.203991E+10 | 319733.91 | 0.203959E+10 | 0.212072E+10 | 0.302210E+10 |
October | 0.167206E+10 | 0.00 | 0.167206E+10 | 0.191016E+10 | 0.350224E+10 |
November | 0.146510E+10 | 0.00 | 0.146510E+10 | 0.921419E+09 | 0.486366E+10 |
December | 0.129929E+10 | 0.00 | 0.129929E+10 | 0.744621E+09 | 0.552478E+10 |
Annual Sum or Average | 0.255219E+11 | 0.748825E+09 | 0.247731E+11 | 0.229321E+11 | 0.472878E+11 |
Minimum of Months | 0.129929E+10 | 0.00 | 0.129929E+10 | 0.744621E+09 | 0.247358E+10 |
Maximum of Months | 0.306505E+10 | 0.299660E+09 | 0.283397E+10 | 0.352807E+10 | 0.552478E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.250987E+10 | 0.134234E+10 | 0.116753E+10 | 0.291133E+10 | 0.348686E+10 |
February | 0.239143E+10 | 0.109553E+10 | 0.129589E+10 | 0.259180E+10 | 0.288356E+10 |
March | 0.321612E+10 | 0.143293E+10 | 0.178319E+10 | 0.365378E+10 | 0.326357E+10 |
April | 0.397913E+10 | 0.199561E+10 | 0.198352E+10 | 0.519943E+10 | 0.256820E+10 |
May | 0.388034E+10 | 0.161936E+10 | 0.226098E+10 | 0.484834E+10 | 0.242703E+10 |
June | 0.373178E+10 | 0.161915E+10 | 0.211263E+10 | 0.502805E+10 | 0.187092E+10 |
July | 0.436934E+10 | 0.217124E+10 | 0.219810E+10 | 0.637081E+10 | 0.173843E+10 |
August | 0.431508E+10 | 0.229202E+10 | 0.202305E+10 | 0.637902E+10 | 0.177819E+10 |
September | 0.304037E+10 | 0.139321E+10 | 0.164716E+10 | 0.424087E+10 | 0.198393E+10 |
October | 0.278099E+10 | 0.142936E+10 | 0.135164E+10 | 0.395430E+10 | 0.226298E+10 |
November | 0.245342E+10 | 0.124644E+10 | 0.120698E+10 | 0.284938E+10 | 0.309454E+10 |
December | 0.241854E+10 | 0.134376E+10 | 0.107477E+10 | 0.280824E+10 | 0.348116E+10 |
Annual Sum or Average | 0.390864E+11 | 0.189810E+11 | 0.201054E+11 | 0.508354E+11 | 0.308394E+11 |
Minimum of Months | 0.239143E+10 | 0.109553E+10 | 0.107477E+10 | 0.259180E+10 | 0.173843E+10 |
Maximum of Months | 0.436934E+10 | 0.229202E+10 | 0.226098E+10 | 0.637902E+10 | 0.348686E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.921074E+10 | 0.675650E+10 | 0.245424E+10 | 0.131224E+11 | 0.558392E+10 |
February | 0.653858E+10 | 0.402742E+10 | 0.251116E+10 | 0.870111E+10 | 0.458988E+10 |
March | 0.577129E+10 | 0.278780E+10 | 0.298348E+10 | 0.755604E+10 | 0.526743E+10 |
April | 0.466650E+10 | 0.177938E+10 | 0.288712E+10 | 0.656866E+10 | 0.419401E+10 |
May | 0.343367E+10 | 0.422560E+09 | 0.301111E+10 | 0.386728E+10 | 0.389935E+10 |
June | 0.291507E+10 | 0.176002E+09 | 0.273907E+10 | 0.331704E+10 | 0.292670E+10 |
July | 0.319079E+10 | 0.359192E+09 | 0.283160E+10 | 0.429016E+10 | 0.266729E+10 |
August | 0.409921E+10 | 0.129302E+10 | 0.280619E+10 | 0.637439E+10 | 0.282977E+10 |
September | 0.552005E+10 | 0.279720E+10 | 0.272285E+10 | 0.858263E+10 | 0.324337E+10 |
October | 0.725422E+10 | 0.484965E+10 | 0.240457E+10 | 0.113029E+11 | 0.367920E+10 |
November | 0.853236E+10 | 0.602372E+10 | 0.250865E+10 | 0.121090E+11 | 0.494696E+10 |
December | 0.984002E+10 | 0.748954E+10 | 0.235048E+10 | 0.140899E+11 | 0.559111E+10 |
Annual Sum or Average | 0.709725E+11 | 0.387620E+11 | 0.322105E+11 | 0.998815E+11 | 0.494190E+11 |
Minimum of Months | 0.291507E+10 | 0.176002E+09 | 0.235048E+10 | 0.331704E+10 | 0.266729E+10 |
Maximum of Months | 0.984002E+10 | 0.748954E+10 | 0.301111E+10 | 0.140899E+11 | 0.559111E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238895E+10 | 0.120488E+10 | 0.118407E+10 | 0.290744E+10 | 0.376718E+10 |
February | 0.257422E+10 | 0.118838E+10 | 0.138584E+10 | 0.296740E+10 | 0.312350E+10 |
March | 0.326690E+10 | 0.144533E+10 | 0.182157E+10 | 0.381805E+10 | 0.352644E+10 |
April | 0.435832E+10 | 0.226937E+10 | 0.208895E+10 | 0.580369E+10 | 0.285390E+10 |
May | 0.442395E+10 | 0.204341E+10 | 0.238053E+10 | 0.569908E+10 | 0.265679E+10 |
June | 0.453550E+10 | 0.226766E+10 | 0.226784E+10 | 0.621246E+10 | 0.203664E+10 |
July | 0.496123E+10 | 0.265471E+10 | 0.230652E+10 | 0.720507E+10 | 0.191416E+10 |
August | 0.465460E+10 | 0.252260E+10 | 0.213200E+10 | 0.686063E+10 | 0.198878E+10 |
September | 0.385665E+10 | 0.206364E+10 | 0.179301E+10 | 0.549116E+10 | 0.217514E+10 |
October | 0.304650E+10 | 0.166326E+10 | 0.138324E+10 | 0.444685E+10 | 0.249330E+10 |
November | 0.266313E+10 | 0.139301E+10 | 0.127013E+10 | 0.332319E+10 | 0.335527E+10 |
December | 0.243041E+10 | 0.130356E+10 | 0.112685E+10 | 0.301525E+10 | 0.382212E+10 |
Annual Sum or Average | 0.431604E+11 | 0.220198E+11 | 0.211406E+11 | 0.577503E+11 | 0.337132E+11 |
Minimum of Months | 0.238895E+10 | 0.118838E+10 | 0.112685E+10 | 0.290744E+10 | 0.191416E+10 |
Maximum of Months | 0.496123E+10 | 0.265471E+10 | 0.238053E+10 | 0.720507E+10 | 0.382212E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139571E+10 | 0.00 | 0.139571E+10 | 0.962514E+09 | 0.496745E+10 |
February | 0.158244E+10 | 0.00 | 0.158244E+10 | 0.100033E+10 | 0.409949E+10 |
March | 0.214693E+10 | 0.00 | 0.214693E+10 | 0.154674E+10 | 0.475443E+10 |
April | 0.239372E+10 | 9213078.61 | 0.238451E+10 | 0.202667E+10 | 0.369814E+10 |
May | 0.297238E+10 | 0.138410E+09 | 0.283397E+10 | 0.264831E+10 | 0.336850E+10 |
June | 0.306505E+10 | 0.299660E+09 | 0.276539E+10 | 0.320491E+10 | 0.261400E+10 |
July | 0.299885E+10 | 0.251354E+09 | 0.274750E+10 | 0.348642E+10 | 0.242517E+10 |
August | 0.249045E+10 | 49868784.28 | 0.244058E+10 | 0.281049E+10 | 0.253444E+10 |
September | 0.203991E+10 | 319733.91 | 0.203959E+10 | 0.214274E+10 | 0.288327E+10 |
October | 0.167206E+10 | 0.00 | 0.167206E+10 | 0.196263E+10 | 0.329708E+10 |
November | 0.146510E+10 | 0.00 | 0.146510E+10 | 0.104302E+10 | 0.444837E+10 |
December | 0.129929E+10 | 0.00 | 0.129929E+10 | 0.888848E+09 | 0.499692E+10 |
Annual Sum or Average | 0.255219E+11 | 0.748825E+09 | 0.247731E+11 | 0.237236E+11 | 0.440873E+11 |
Minimum of Months | 0.129929E+10 | 0.00 | 0.129929E+10 | 0.888848E+09 | 0.242517E+10 |
Maximum of Months | 0.306505E+10 | 0.299660E+09 | 0.283397E+10 | 0.348642E+10 | 0.499692E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.250987E+10 | 0.134234E+10 | 0.116753E+10 | 0.302784E+10 | 0.319684E+10 |
February | 0.239143E+10 | 0.109553E+10 | 0.129589E+10 | 0.267483E+10 | 0.265109E+10 |
March | 0.321612E+10 | 0.143293E+10 | 0.178319E+10 | 0.373016E+10 | 0.306632E+10 |
April | 0.397913E+10 | 0.199561E+10 | 0.198352E+10 | 0.521942E+10 | 0.246831E+10 |
May | 0.388034E+10 | 0.161936E+10 | 0.226098E+10 | 0.487970E+10 | 0.233169E+10 |
June | 0.373178E+10 | 0.161915E+10 | 0.211263E+10 | 0.501731E+10 | 0.182880E+10 |
July | 0.436934E+10 | 0.217124E+10 | 0.219810E+10 | 0.633470E+10 | 0.172013E+10 |
August | 0.431508E+10 | 0.229202E+10 | 0.202305E+10 | 0.634824E+10 | 0.175381E+10 |
September | 0.304037E+10 | 0.139321E+10 | 0.164716E+10 | 0.424370E+10 | 0.191262E+10 |
October | 0.278099E+10 | 0.142936E+10 | 0.135164E+10 | 0.397948E+10 | 0.215929E+10 |
November | 0.245342E+10 | 0.124644E+10 | 0.120698E+10 | 0.293399E+10 | 0.287949E+10 |
December | 0.241854E+10 | 0.134376E+10 | 0.107477E+10 | 0.292534E+10 | 0.320244E+10 |
Annual Sum or Average | 0.390864E+11 | 0.189810E+11 | 0.201054E+11 | 0.513147E+11 | 0.291708E+11 |
Minimum of Months | 0.239143E+10 | 0.109553E+10 | 0.107477E+10 | 0.267483E+10 | 0.172013E+10 |
Maximum of Months | 0.436934E+10 | 0.229202E+10 | 0.226098E+10 | 0.634824E+10 | 0.320244E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.921074E+10 | 0.675650E+10 | 0.245424E+10 | 0.132532E+11 | 0.516903E+10 |
February | 0.653858E+10 | 0.402742E+10 | 0.251116E+10 | 0.880004E+10 | 0.422910E+10 |
March | 0.577129E+10 | 0.278780E+10 | 0.298348E+10 | 0.765106E+10 | 0.492405E+10 |
April | 0.466650E+10 | 0.177938E+10 | 0.288712E+10 | 0.659828E+10 | 0.399734E+10 |
May | 0.343367E+10 | 0.422560E+09 | 0.301111E+10 | 0.391782E+10 | 0.370127E+10 |
June | 0.291507E+10 | 0.176002E+09 | 0.273907E+10 | 0.331588E+10 | 0.283072E+10 |
July | 0.319079E+10 | 0.359192E+09 | 0.283160E+10 | 0.425673E+10 | 0.261506E+10 |
August | 0.409921E+10 | 0.129302E+10 | 0.280619E+10 | 0.633900E+10 | 0.276692E+10 |
September | 0.552005E+10 | 0.279720E+10 | 0.272285E+10 | 0.857510E+10 | 0.311644E+10 |
October | 0.725422E+10 | 0.484965E+10 | 0.240457E+10 | 0.113216E+11 | 0.351606E+10 |
November | 0.853236E+10 | 0.602372E+10 | 0.250865E+10 | 0.121934E+11 | 0.463830E+10 |
December | 0.984002E+10 | 0.748954E+10 | 0.235048E+10 | 0.142143E+11 | 0.520851E+10 |
Annual Sum or Average | 0.709725E+11 | 0.387620E+11 | 0.322105E+11 | 0.100436E+12 | 0.467128E+11 |
Minimum of Months | 0.291507E+10 | 0.176002E+09 | 0.235048E+10 | 0.331588E+10 | 0.261506E+10 |
Maximum of Months | 0.984002E+10 | 0.748954E+10 | 0.301111E+10 | 0.142143E+11 | 0.520851E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.238895E+10 | 0.120488E+10 | 0.118407E+10 | 0.297292E+10 | 0.348531E+10 |
February | 0.257422E+10 | 0.118838E+10 | 0.138584E+10 | 0.302230E+10 | 0.289503E+10 |
March | 0.326690E+10 | 0.144533E+10 | 0.182157E+10 | 0.386790E+10 | 0.331406E+10 |
April | 0.435832E+10 | 0.226937E+10 | 0.208895E+10 | 0.580667E+10 | 0.273513E+10 |
May | 0.442395E+10 | 0.204341E+10 | 0.238053E+10 | 0.570701E+10 | 0.254482E+10 |
June | 0.453550E+10 | 0.226766E+10 | 0.226784E+10 | 0.618573E+10 | 0.198072E+10 |
July | 0.496123E+10 | 0.265471E+10 | 0.230652E+10 | 0.715923E+10 | 0.188039E+10 |
August | 0.465460E+10 | 0.252260E+10 | 0.213200E+10 | 0.682108E+10 | 0.194958E+10 |
September | 0.385665E+10 | 0.206364E+10 | 0.179301E+10 | 0.548142E+10 | 0.209730E+10 |
October | 0.304650E+10 | 0.166326E+10 | 0.138324E+10 | 0.445910E+10 | 0.237868E+10 |
November | 0.266313E+10 | 0.139301E+10 | 0.127013E+10 | 0.337258E+10 | 0.313428E+10 |
December | 0.243041E+10 | 0.130356E+10 | 0.112685E+10 | 0.308030E+10 | 0.354301E+10 |
Annual Sum or Average | 0.431604E+11 | 0.220198E+11 | 0.211406E+11 | 0.579362E+11 | 0.319383E+11 |
Minimum of Months | 0.238895E+10 | 0.118838E+10 | 0.112685E+10 | 0.297292E+10 | 0.188039E+10 |
Maximum of Months | 0.496123E+10 | 0.265471E+10 | 0.238053E+10 | 0.715923E+10 | 0.354301E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 245.41 | 2294.86 | 521.10 | 0.00 | 521.10 | 0.00 | 0.00 |
February | 302.83 | 2098.87 | 654.12 | 0.00 | 654.12 | 0.00 | 0.00 |
March | 469.74 | 2129.59 | 801.57 | 0.00 | 801.57 | 0.00 | 0.00 |
April | 697.16 | 1670.18 | 923.51 | 3.55 | 919.95 | 0.00 | 0.00 |
May | 922.59 | 1403.69 | 1109.76 | 51.68 | 1058.09 | 0.00 | 0.00 |
June | 1213.38 | 1109.48 | 1182.51 | 115.61 | 1066.90 | 0.00 | 0.00 |
July | 1279.50 | 983.73 | 1119.65 | 93.85 | 1025.80 | 0.00 | 0.00 |
August | 1017.59 | 1035.29 | 929.83 | 18.62 | 911.21 | 0.00 | 0.00 |
September | 785.40 | 1267.04 | 787.01 | 0.12 | 786.88 | 0.00 | 0.00 |
October | 663.51 | 1449.78 | 624.28 | 0.00 | 624.28 | 0.00 | 0.00 |
November | 291.73 | 2109.87 | 565.24 | 0.00 | 565.24 | 0.00 | 0.00 |
December | 200.67 | 2364.65 | 485.10 | 0.00 | 485.10 | 0.00 | 0.00 |
Annual Sum or Average | 676.38 | 1657.47 | 809.30 | 23.75 | 785.55 | 0.00 | 0.00 |
Minimum of Months | 200.67 | 983.73 | 485.10 | 0.00 | 485.10 | 0.00 | 0.00 |
Maximum of Months | 1279.50 | 2364.65 | 1182.51 | 115.61 | 1066.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1062.22 | 1406.76 | 937.08 | 501.17 | 435.91 | 0.00 | 0.00 |
February | 1052.57 | 1285.33 | 988.52 | 452.85 | 535.67 | 0.00 | 0.00 |
March | 1349.96 | 1294.95 | 1200.77 | 535.00 | 665.77 | 0.00 | 0.00 |
April | 2006.89 | 1037.23 | 1535.16 | 769.92 | 765.25 | 0.00 | 0.00 |
May | 1815.54 | 941.06 | 1448.76 | 604.60 | 844.16 | 0.00 | 0.00 |
June | 1947.92 | 749.31 | 1439.74 | 624.68 | 815.06 | 0.00 | 0.00 |
July | 2391.65 | 660.27 | 1631.33 | 810.65 | 820.68 | 0.00 | 0.00 |
August | 2396.56 | 664.48 | 1611.07 | 855.75 | 755.32 | 0.00 | 0.00 |
September | 1633.62 | 809.89 | 1172.99 | 537.51 | 635.48 | 0.00 | 0.00 |
October | 1468.33 | 901.49 | 1038.31 | 533.66 | 504.64 | 0.00 | 0.00 |
November | 1080.32 | 1279.85 | 946.54 | 480.88 | 465.66 | 0.00 | 0.00 |
December | 1019.53 | 1408.27 | 902.98 | 501.71 | 401.28 | 0.00 | 0.00 |
Annual Sum or Average | 1605.90 | 1035.27 | 1239.43 | 601.88 | 637.54 | 0.00 | 0.00 |
Minimum of Months | 1019.53 | 660.27 | 902.98 | 452.85 | 401.28 | 0.00 | 0.00 |
Maximum of Months | 2396.56 | 1408.27 | 1631.33 | 855.75 | 844.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4929.33 | 2118.46 | 3438.91 | 2522.60 | 916.31 | 0.00 | 0.00 |
February | 3625.46 | 1957.59 | 2702.80 | 1664.78 | 1038.02 | 0.00 | 0.00 |
March | 2829.56 | 2046.80 | 2154.76 | 1040.85 | 1113.91 | 0.00 | 0.00 |
April | 2532.07 | 1700.33 | 1800.36 | 686.49 | 1113.86 | 0.00 | 0.00 |
May | 1445.22 | 1502.49 | 1281.99 | 157.77 | 1124.22 | 0.00 | 0.00 |
June | 1267.99 | 1185.29 | 1124.65 | 67.90 | 1056.74 | 0.00 | 0.00 |
July | 1582.76 | 1045.01 | 1191.31 | 134.11 | 1057.20 | 0.00 | 0.00 |
August | 2374.73 | 1092.12 | 1530.48 | 482.76 | 1047.72 | 0.00 | 0.00 |
September | 3332.35 | 1286.04 | 2129.66 | 1079.17 | 1050.49 | 0.00 | 0.00 |
October | 4244.12 | 1413.82 | 2708.43 | 1810.66 | 897.77 | 0.00 | 0.00 |
November | 4701.30 | 1964.75 | 3291.82 | 2323.97 | 967.85 | 0.00 | 0.00 |
December | 5285.44 | 2157.46 | 3673.86 | 2796.28 | 877.57 | 0.00 | 0.00 |
Annual Sum or Average | 3177.95 | 1620.73 | 2250.53 | 1229.14 | 1021.39 | 0.00 | 0.00 |
Minimum of Months | 1267.99 | 1045.01 | 1124.65 | 67.90 | 877.57 | 0.00 | 0.00 |
Maximum of Months | 5285.44 | 2157.46 | 3673.86 | 2796.28 | 1124.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1044.41 | 1578.72 | 891.94 | 449.85 | 442.08 | 0.00 | 0.00 |
February | 1178.50 | 1503.73 | 1064.08 | 491.23 | 572.85 | 0.00 | 0.00 |
March | 1367.29 | 1546.91 | 1219.72 | 539.63 | 680.10 | 0.00 | 0.00 |
April | 2183.67 | 1285.72 | 1681.46 | 875.53 | 805.93 | 0.00 | 0.00 |
May | 2117.11 | 1068.57 | 1651.72 | 762.93 | 888.79 | 0.00 | 0.00 |
June | 2377.14 | 879.96 | 1749.82 | 874.87 | 874.94 | 0.00 | 0.00 |
July | 2657.56 | 800.99 | 1852.32 | 991.16 | 861.16 | 0.00 | 0.00 |
August | 2520.87 | 847.44 | 1737.84 | 941.84 | 796.00 | 0.00 | 0.00 |
September | 2108.19 | 919.44 | 1487.91 | 796.16 | 691.75 | 0.00 | 0.00 |
October | 1623.65 | 1064.79 | 1137.44 | 620.99 | 516.45 | 0.00 | 0.00 |
November | 1224.86 | 1533.70 | 1027.45 | 537.43 | 490.02 | 0.00 | 0.00 |
December | 1054.04 | 1739.21 | 907.41 | 486.69 | 420.72 | 0.00 | 0.00 |
Annual Sum or Average | 1791.09 | 1229.36 | 1368.61 | 698.25 | 670.37 | 0.00 | 0.00 |
Minimum of Months | 1044.41 | 800.99 | 891.94 | 449.85 | 420.72 | 0.00 | 0.00 |
Maximum of Months | 2657.56 | 1739.21 | 1852.32 | 991.16 | 888.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 305.52 | 2053.09 | 521.10 | 0.00 | 521.10 | 0.00 | 0.00 |
February | 361.49 | 1872.26 | 654.12 | 0.00 | 654.12 | 0.00 | 0.00 |
March | 531.72 | 1916.10 | 801.57 | 0.00 | 801.57 | 0.00 | 0.00 |
April | 760.74 | 1505.85 | 923.50 | 3.55 | 919.95 | 0.00 | 0.00 |
May | 960.58 | 1323.17 | 1109.76 | 51.68 | 1058.08 | 0.00 | 0.00 |
June | 1238.47 | 1041.01 | 1182.50 | 115.61 | 1066.89 | 0.00 | 0.00 |
July | 1317.23 | 923.53 | 1119.64 | 93.84 | 1025.80 | 0.00 | 0.00 |
August | 1058.59 | 969.09 | 929.83 | 18.62 | 911.21 | 0.00 | 0.00 |
September | 818.18 | 1165.93 | 787.00 | 0.12 | 786.88 | 0.00 | 0.00 |
October | 713.17 | 1307.59 | 624.28 | 0.00 | 624.28 | 0.00 | 0.00 |
November | 355.49 | 1876.41 | 565.24 | 0.00 | 565.24 | 0.00 | 0.00 |
December | 278.01 | 2062.72 | 485.10 | 0.00 | 485.10 | 0.00 | 0.00 |
Annual Sum or Average | 727.17 | 1499.49 | 809.29 | 23.75 | 785.55 | 0.00 | 0.00 |
Minimum of Months | 278.01 | 923.53 | 485.10 | 0.00 | 485.10 | 0.00 | 0.00 |
Maximum of Months | 1317.23 | 2062.72 | 1182.50 | 115.61 | 1066.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1086.97 | 1301.84 | 937.08 | 501.17 | 435.91 | 0.00 | 0.00 |
February | 1071.35 | 1191.95 | 988.52 | 452.85 | 535.67 | 0.00 | 0.00 |
March | 1364.16 | 1218.48 | 1200.76 | 534.99 | 665.77 | 0.00 | 0.00 |
April | 2005.95 | 990.82 | 1535.16 | 769.91 | 765.25 | 0.00 | 0.00 |
May | 1810.16 | 906.15 | 1448.75 | 604.60 | 844.15 | 0.00 | 0.00 |
June | 1939.84 | 721.80 | 1439.73 | 624.67 | 815.06 | 0.00 | 0.00 |
July | 2378.59 | 649.05 | 1631.32 | 810.65 | 820.68 | 0.00 | 0.00 |
August | 2381.66 | 663.90 | 1611.06 | 855.74 | 755.32 | 0.00 | 0.00 |
September | 1636.14 | 765.41 | 1172.98 | 537.51 | 635.48 | 0.00 | 0.00 |
October | 1476.37 | 844.90 | 1038.30 | 533.66 | 504.64 | 0.00 | 0.00 |
November | 1099.30 | 1193.88 | 946.54 | 480.88 | 465.66 | 0.00 | 0.00 |
December | 1048.48 | 1299.72 | 902.98 | 501.70 | 401.27 | 0.00 | 0.00 |
Annual Sum or Average | 1611.98 | 977.91 | 1239.42 | 601.88 | 637.54 | 0.00 | 0.00 |
Minimum of Months | 1048.48 | 649.05 | 902.98 | 452.85 | 401.27 | 0.00 | 0.00 |
Maximum of Months | 2381.66 | 1301.84 | 1631.32 | 855.74 | 844.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4899.33 | 2084.80 | 3438.90 | 2522.59 | 916.31 | 0.00 | 0.00 |
February | 3596.69 | 1897.27 | 2702.79 | 1664.78 | 1038.01 | 0.00 | 0.00 |
March | 2821.10 | 1966.63 | 2154.75 | 1040.85 | 1113.91 | 0.00 | 0.00 |
April | 2534.21 | 1618.06 | 1800.35 | 686.49 | 1113.86 | 0.00 | 0.00 |
May | 1443.88 | 1455.85 | 1281.99 | 157.77 | 1124.22 | 0.00 | 0.00 |
June | 1279.72 | 1129.13 | 1124.64 | 67.90 | 1056.74 | 0.00 | 0.00 |
July | 1601.76 | 995.85 | 1191.31 | 134.11 | 1057.20 | 0.00 | 0.00 |
August | 2379.93 | 1056.51 | 1530.47 | 482.76 | 1047.71 | 0.00 | 0.00 |
September | 3311.20 | 1251.30 | 2129.65 | 1079.17 | 1050.48 | 0.00 | 0.00 |
October | 4220.04 | 1373.65 | 2708.42 | 1810.65 | 897.76 | 0.00 | 0.00 |
November | 4671.68 | 1908.55 | 3291.81 | 2323.96 | 967.84 | 0.00 | 0.00 |
December | 5260.57 | 2087.48 | 3673.84 | 2796.27 | 877.57 | 0.00 | 0.00 |
Annual Sum or Average | 3167.22 | 1567.07 | 2250.52 | 1229.13 | 1021.39 | 0.00 | 0.00 |
Minimum of Months | 1279.72 | 995.85 | 1124.64 | 67.90 | 877.57 | 0.00 | 0.00 |
Maximum of Months | 5260.57 | 2087.48 | 3673.84 | 2796.27 | 1124.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1085.51 | 1406.51 | 891.93 | 449.85 | 442.08 | 0.00 | 0.00 |
February | 1226.60 | 1291.13 | 1064.08 | 491.23 | 572.85 | 0.00 | 0.00 |
March | 1425.50 | 1316.62 | 1219.72 | 539.62 | 680.10 | 0.00 | 0.00 |
April | 2239.08 | 1101.04 | 1681.45 | 875.53 | 805.92 | 0.00 | 0.00 |
May | 2127.79 | 991.93 | 1651.71 | 762.92 | 888.79 | 0.00 | 0.00 |
June | 2396.78 | 785.74 | 1749.81 | 874.87 | 874.94 | 0.00 | 0.00 |
July | 2690.07 | 714.66 | 1852.31 | 991.16 | 861.16 | 0.00 | 0.00 |
August | 2561.47 | 742.52 | 1737.83 | 941.83 | 796.00 | 0.00 | 0.00 |
September | 2118.50 | 839.18 | 1487.90 | 796.16 | 691.75 | 0.00 | 0.00 |
October | 1660.27 | 930.89 | 1137.43 | 620.99 | 516.44 | 0.00 | 0.00 |
November | 1282.09 | 1294.47 | 1027.44 | 537.42 | 490.02 | 0.00 | 0.00 |
December | 1125.76 | 1427.02 | 907.41 | 486.69 | 420.72 | 0.00 | 0.00 |
Annual Sum or Average | 1831.25 | 1069.04 | 1368.61 | 698.24 | 670.36 | 0.00 | 0.00 |
Minimum of Months | 1085.51 | 714.66 | 891.93 | 449.85 | 420.72 | 0.00 | 0.00 |
Maximum of Months | 2690.07 | 1427.02 | 1852.31 | 991.16 | 888.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 359.36 | 1854.63 | 521.10 | 0.00 | 521.10 | 0.00 | 0.00 |
February | 413.50 | 1694.56 | 654.12 | 0.00 | 654.12 | 0.00 | 0.00 |
March | 577.49 | 1775.10 | 801.57 | 0.00 | 801.57 | 0.00 | 0.00 |
April | 781.89 | 1426.75 | 923.50 | 3.55 | 919.95 | 0.00 | 0.00 |
May | 988.77 | 1257.65 | 1109.76 | 51.68 | 1058.08 | 0.00 | 0.00 |
June | 1236.46 | 1008.49 | 1182.50 | 115.61 | 1066.89 | 0.00 | 0.00 |
July | 1301.68 | 905.45 | 1119.64 | 93.84 | 1025.80 | 0.00 | 0.00 |
August | 1049.32 | 946.25 | 929.83 | 18.62 | 911.21 | 0.00 | 0.00 |
September | 826.67 | 1112.37 | 787.00 | 0.12 | 786.88 | 0.00 | 0.00 |
October | 732.76 | 1230.99 | 624.28 | 0.00 | 624.28 | 0.00 | 0.00 |
November | 402.40 | 1716.19 | 565.24 | 0.00 | 565.24 | 0.00 | 0.00 |
December | 331.86 | 1865.64 | 485.10 | 0.00 | 485.10 | 0.00 | 0.00 |
Annual Sum or Average | 752.27 | 1398.00 | 809.29 | 23.75 | 785.55 | 0.00 | 0.00 |
Minimum of Months | 331.86 | 905.45 | 485.10 | 0.00 | 485.10 | 0.00 | 0.00 |
Maximum of Months | 1301.68 | 1865.64 | 1182.50 | 115.61 | 1066.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1130.47 | 1193.57 | 937.08 | 501.17 | 435.91 | 0.00 | 0.00 |
February | 1105.67 | 1095.85 | 988.52 | 452.85 | 535.67 | 0.00 | 0.00 |
March | 1392.68 | 1144.83 | 1200.76 | 534.99 | 665.77 | 0.00 | 0.00 |
April | 2013.67 | 952.28 | 1535.16 | 769.91 | 765.25 | 0.00 | 0.00 |
May | 1821.87 | 870.55 | 1448.75 | 604.60 | 844.15 | 0.00 | 0.00 |
June | 1935.69 | 705.56 | 1439.73 | 624.67 | 815.06 | 0.00 | 0.00 |
July | 2365.11 | 642.22 | 1631.32 | 810.65 | 820.68 | 0.00 | 0.00 |
August | 2370.16 | 654.80 | 1611.06 | 855.74 | 755.32 | 0.00 | 0.00 |
September | 1637.23 | 737.89 | 1172.98 | 537.51 | 635.48 | 0.00 | 0.00 |
October | 1485.77 | 806.18 | 1038.30 | 533.66 | 504.64 | 0.00 | 0.00 |
November | 1131.94 | 1110.91 | 946.54 | 480.88 | 465.66 | 0.00 | 0.00 |
December | 1092.20 | 1195.65 | 902.98 | 501.70 | 401.27 | 0.00 | 0.00 |
Annual Sum or Average | 1627.18 | 925.00 | 1239.42 | 601.88 | 637.54 | 0.00 | 0.00 |
Minimum of Months | 1092.20 | 642.22 | 902.98 | 452.85 | 401.27 | 0.00 | 0.00 |
Maximum of Months | 2370.16 | 1195.65 | 1631.32 | 855.74 | 844.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4948.18 | 1929.90 | 3438.90 | 2522.59 | 916.31 | 0.00 | 0.00 |
February | 3637.58 | 1748.14 | 2702.79 | 1664.78 | 1038.01 | 0.00 | 0.00 |
March | 2856.58 | 1838.43 | 2154.75 | 1040.85 | 1113.91 | 0.00 | 0.00 |
April | 2545.63 | 1542.18 | 1800.35 | 686.49 | 1113.86 | 0.00 | 0.00 |
May | 1462.75 | 1381.90 | 1281.99 | 157.77 | 1124.22 | 0.00 | 0.00 |
June | 1279.28 | 1092.10 | 1124.64 | 67.90 | 1056.74 | 0.00 | 0.00 |
July | 1589.28 | 976.35 | 1191.31 | 134.11 | 1057.20 | 0.00 | 0.00 |
August | 2366.71 | 1033.05 | 1530.47 | 482.76 | 1047.71 | 0.00 | 0.00 |
September | 3308.29 | 1202.33 | 2129.65 | 1079.17 | 1050.48 | 0.00 | 0.00 |
October | 4226.98 | 1312.75 | 2708.42 | 1810.65 | 897.76 | 0.00 | 0.00 |
November | 4704.25 | 1789.47 | 3291.81 | 2323.96 | 967.84 | 0.00 | 0.00 |
December | 5307.02 | 1944.64 | 3673.84 | 2796.27 | 877.57 | 0.00 | 0.00 |
Annual Sum or Average | 3184.82 | 1481.25 | 2250.52 | 1229.13 | 1021.39 | 0.00 | 0.00 |
Minimum of Months | 1279.28 | 976.35 | 1124.64 | 67.90 | 877.57 | 0.00 | 0.00 |
Maximum of Months | 5307.02 | 1944.64 | 3673.84 | 2796.27 | 1124.22 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1109.96 | 1301.26 | 891.93 | 449.85 | 442.08 | 0.00 | 0.00 |
February | 1249.30 | 1196.69 | 1064.08 | 491.23 | 572.85 | 0.00 | 0.00 |
March | 1444.11 | 1237.33 | 1219.72 | 539.62 | 680.10 | 0.00 | 0.00 |
April | 2240.23 | 1055.22 | 1681.45 | 875.53 | 805.92 | 0.00 | 0.00 |
May | 2130.75 | 950.13 | 1651.71 | 762.92 | 888.79 | 0.00 | 0.00 |
June | 2386.47 | 764.17 | 1749.81 | 874.87 | 874.94 | 0.00 | 0.00 |
July | 2672.95 | 702.06 | 1852.31 | 991.16 | 861.16 | 0.00 | 0.00 |
August | 2546.70 | 727.89 | 1737.83 | 941.83 | 796.00 | 0.00 | 0.00 |
September | 2114.75 | 809.14 | 1487.90 | 796.16 | 691.75 | 0.00 | 0.00 |
October | 1664.84 | 888.10 | 1137.43 | 620.99 | 516.44 | 0.00 | 0.00 |
November | 1301.15 | 1209.21 | 1027.44 | 537.42 | 490.02 | 0.00 | 0.00 |
December | 1150.05 | 1322.81 | 907.41 | 486.69 | 420.72 | 0.00 | 0.00 |
Annual Sum or Average | 1837.15 | 1012.76 | 1368.61 | 698.24 | 670.36 | 0.00 | 0.00 |
Minimum of Months | 1109.96 | 702.06 | 891.93 | 449.85 | 420.72 | 0.00 | 0.00 |
Maximum of Months | 2672.95 | 1322.81 | 1852.31 | 991.16 | 888.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.657315E+09 | 0.614656E+10 | 0.139572E+10 | 0.00 | 0.139572E+10 | 0.00 | 0.00 |
February | 0.732598E+09 | 0.507758E+10 | 0.158245E+10 | 0.00 | 0.158245E+10 | 0.00 | 0.00 |
March | 0.125814E+10 | 0.570391E+10 | 0.214694E+10 | 0.00 | 0.214694E+10 | 0.00 | 0.00 |
April | 0.180704E+10 | 0.432911E+10 | 0.239373E+10 | 9213111.32 | 0.238452E+10 | 0.00 | 0.00 |
May | 0.247106E+10 | 0.375964E+10 | 0.297239E+10 | 0.138410E+09 | 0.283398E+10 | 0.00 | 0.00 |
June | 0.314509E+10 | 0.287578E+10 | 0.306506E+10 | 0.299661E+09 | 0.276540E+10 | 0.00 | 0.00 |
July | 0.342701E+10 | 0.263483E+10 | 0.299887E+10 | 0.251354E+09 | 0.274751E+10 | 0.00 | 0.00 |
August | 0.272552E+10 | 0.277293E+10 | 0.249046E+10 | 49868961.37 | 0.244059E+10 | 0.00 | 0.00 |
September | 0.203575E+10 | 0.328416E+10 | 0.203992E+10 | 319735.05 | 0.203960E+10 | 0.00 | 0.00 |
October | 0.177713E+10 | 0.388309E+10 | 0.167207E+10 | 0.00 | 0.167207E+10 | 0.00 | 0.00 |
November | 0.756152E+09 | 0.546878E+10 | 0.146510E+10 | 0.00 | 0.146510E+10 | 0.00 | 0.00 |
December | 0.537471E+09 | 0.633347E+10 | 0.129929E+10 | 0.00 | 0.129929E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.213303E+11 | 0.522698E+11 | 0.255220E+11 | 0.748828E+09 | 0.247732E+11 | 0.00 | 0.00 |
Minimum of Months | 0.537471E+09 | 0.263483E+10 | 0.129929E+10 | 0.00 | 0.129929E+10 | 0.00 | 0.00 |
Maximum of Months | 0.342701E+10 | 0.633347E+10 | 0.306506E+10 | 0.299661E+09 | 0.283398E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.284506E+10 | 0.376787E+10 | 0.250988E+10 | 0.134234E+10 | 0.116754E+10 | 0.00 | 0.00 |
February | 0.254638E+10 | 0.310946E+10 | 0.239144E+10 | 0.109554E+10 | 0.129590E+10 | 0.00 | 0.00 |
March | 0.361574E+10 | 0.346840E+10 | 0.321613E+10 | 0.143293E+10 | 0.178320E+10 | 0.00 | 0.00 |
April | 0.520186E+10 | 0.268850E+10 | 0.397915E+10 | 0.199562E+10 | 0.198352E+10 | 0.00 | 0.00 |
May | 0.486274E+10 | 0.252054E+10 | 0.388035E+10 | 0.161936E+10 | 0.226099E+10 | 0.00 | 0.00 |
June | 0.504900E+10 | 0.194220E+10 | 0.373180E+10 | 0.161916E+10 | 0.211264E+10 | 0.00 | 0.00 |
July | 0.640580E+10 | 0.176848E+10 | 0.436936E+10 | 0.217125E+10 | 0.219811E+10 | 0.00 | 0.00 |
August | 0.641894E+10 | 0.177974E+10 | 0.431509E+10 | 0.229203E+10 | 0.202306E+10 | 0.00 | 0.00 |
September | 0.423433E+10 | 0.209923E+10 | 0.304038E+10 | 0.139322E+10 | 0.164717E+10 | 0.00 | 0.00 |
October | 0.393278E+10 | 0.241454E+10 | 0.278101E+10 | 0.142937E+10 | 0.135164E+10 | 0.00 | 0.00 |
November | 0.280018E+10 | 0.331738E+10 | 0.245343E+10 | 0.124645E+10 | 0.120699E+10 | 0.00 | 0.00 |
December | 0.273072E+10 | 0.377190E+10 | 0.241855E+10 | 0.134377E+10 | 0.107478E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.506435E+11 | 0.326482E+11 | 0.390866E+11 | 0.189810E+11 | 0.201055E+11 | 0.00 | 0.00 |
Minimum of Months | 0.254638E+10 | 0.176848E+10 | 0.239144E+10 | 0.109554E+10 | 0.107478E+10 | 0.00 | 0.00 |
Maximum of Months | 0.641894E+10 | 0.377190E+10 | 0.436936E+10 | 0.229203E+10 | 0.226099E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.132027E+11 | 0.567409E+10 | 0.921077E+10 | 0.675652E+10 | 0.245425E+10 | 0.00 | 0.00 |
February | 0.877070E+10 | 0.473580E+10 | 0.653861E+10 | 0.402744E+10 | 0.251117E+10 | 0.00 | 0.00 |
March | 0.757869E+10 | 0.548215E+10 | 0.577131E+10 | 0.278781E+10 | 0.298349E+10 | 0.00 | 0.00 |
April | 0.656311E+10 | 0.440726E+10 | 0.466652E+10 | 0.177939E+10 | 0.288713E+10 | 0.00 | 0.00 |
May | 0.387087E+10 | 0.402428E+10 | 0.343369E+10 | 0.422562E+09 | 0.301112E+10 | 0.00 | 0.00 |
June | 0.328664E+10 | 0.307228E+10 | 0.291508E+10 | 0.176002E+09 | 0.273908E+10 | 0.00 | 0.00 |
July | 0.423926E+10 | 0.279895E+10 | 0.319081E+10 | 0.359193E+09 | 0.283161E+10 | 0.00 | 0.00 |
August | 0.636047E+10 | 0.292513E+10 | 0.409923E+10 | 0.129302E+10 | 0.280620E+10 | 0.00 | 0.00 |
September | 0.863745E+10 | 0.333342E+10 | 0.552007E+10 | 0.279721E+10 | 0.272286E+10 | 0.00 | 0.00 |
October | 0.113675E+11 | 0.378679E+10 | 0.725425E+10 | 0.484967E+10 | 0.240458E+10 | 0.00 | 0.00 |
November | 0.121858E+11 | 0.509264E+10 | 0.853239E+10 | 0.602374E+10 | 0.250865E+10 | 0.00 | 0.00 |
December | 0.141565E+11 | 0.577854E+10 | 0.984005E+10 | 0.748956E+10 | 0.235049E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.100220E+12 | 0.511113E+11 | 0.709728E+11 | 0.387621E+11 | 0.322106E+11 | 0.00 | 0.00 |
Minimum of Months | 0.328664E+10 | 0.279895E+10 | 0.291508E+10 | 0.176002E+09 | 0.235049E+10 | 0.00 | 0.00 |
Maximum of Months | 0.141565E+11 | 0.577854E+10 | 0.984005E+10 | 0.748956E+10 | 0.301112E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.279733E+10 | 0.422845E+10 | 0.238896E+10 | 0.120488E+10 | 0.118408E+10 | 0.00 | 0.00 |
February | 0.285103E+10 | 0.363783E+10 | 0.257423E+10 | 0.118839E+10 | 0.138585E+10 | 0.00 | 0.00 |
March | 0.366215E+10 | 0.414325E+10 | 0.326691E+10 | 0.144533E+10 | 0.182158E+10 | 0.00 | 0.00 |
April | 0.566008E+10 | 0.333259E+10 | 0.435834E+10 | 0.226938E+10 | 0.208896E+10 | 0.00 | 0.00 |
May | 0.567046E+10 | 0.286206E+10 | 0.442397E+10 | 0.204342E+10 | 0.238054E+10 | 0.00 | 0.00 |
June | 0.616156E+10 | 0.228086E+10 | 0.453552E+10 | 0.226767E+10 | 0.226785E+10 | 0.00 | 0.00 |
July | 0.711801E+10 | 0.214538E+10 | 0.496125E+10 | 0.265472E+10 | 0.230653E+10 | 0.00 | 0.00 |
August | 0.675190E+10 | 0.226978E+10 | 0.465462E+10 | 0.252261E+10 | 0.213201E+10 | 0.00 | 0.00 |
September | 0.546443E+10 | 0.238318E+10 | 0.385666E+10 | 0.206364E+10 | 0.179302E+10 | 0.00 | 0.00 |
October | 0.434879E+10 | 0.285194E+10 | 0.304652E+10 | 0.166327E+10 | 0.138325E+10 | 0.00 | 0.00 |
November | 0.317484E+10 | 0.397536E+10 | 0.266314E+10 | 0.139301E+10 | 0.127013E+10 | 0.00 | 0.00 |
December | 0.282313E+10 | 0.465831E+10 | 0.243042E+10 | 0.130356E+10 | 0.112685E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.564837E+11 | 0.387690E+11 | 0.431605E+11 | 0.220199E+11 | 0.211406E+11 | 0.00 | 0.00 |
Minimum of Months | 0.279733E+10 | 0.214538E+10 | 0.238896E+10 | 0.118839E+10 | 0.112685E+10 | 0.00 | 0.00 |
Maximum of Months | 0.711801E+10 | 0.465831E+10 | 0.496125E+10 | 0.265472E+10 | 0.238054E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.818315E+09 | 0.549900E+10 | 0.139571E+10 | 0.00 | 0.139571E+10 | 0.00 | 0.00 |
February | 0.874510E+09 | 0.452937E+10 | 0.158244E+10 | 0.00 | 0.158244E+10 | 0.00 | 0.00 |
March | 0.142415E+10 | 0.513207E+10 | 0.214693E+10 | 0.00 | 0.214693E+10 | 0.00 | 0.00 |
April | 0.197184E+10 | 0.390316E+10 | 0.239372E+10 | 9213078.61 | 0.238451E+10 | 0.00 | 0.00 |
May | 0.257281E+10 | 0.354397E+10 | 0.297238E+10 | 0.138410E+09 | 0.283397E+10 | 0.00 | 0.00 |
June | 0.321010E+10 | 0.269830E+10 | 0.306505E+10 | 0.299660E+09 | 0.276539E+10 | 0.00 | 0.00 |
July | 0.352807E+10 | 0.247358E+10 | 0.299885E+10 | 0.251354E+09 | 0.274750E+10 | 0.00 | 0.00 |
August | 0.283534E+10 | 0.259561E+10 | 0.249045E+10 | 49868784.28 | 0.244058E+10 | 0.00 | 0.00 |
September | 0.212072E+10 | 0.302210E+10 | 0.203991E+10 | 319733.91 | 0.203959E+10 | 0.00 | 0.00 |
October | 0.191016E+10 | 0.350224E+10 | 0.167206E+10 | 0.00 | 0.167206E+10 | 0.00 | 0.00 |
November | 0.921419E+09 | 0.486366E+10 | 0.146510E+10 | 0.00 | 0.146510E+10 | 0.00 | 0.00 |
December | 0.744621E+09 | 0.552478E+10 | 0.129929E+10 | 0.00 | 0.129929E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.229321E+11 | 0.472878E+11 | 0.255219E+11 | 0.748825E+09 | 0.247731E+11 | 0.00 | 0.00 |
Minimum of Months | 0.744621E+09 | 0.247358E+10 | 0.129929E+10 | 0.00 | 0.129929E+10 | 0.00 | 0.00 |
Maximum of Months | 0.352807E+10 | 0.552478E+10 | 0.306505E+10 | 0.299660E+09 | 0.283397E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.291133E+10 | 0.348686E+10 | 0.250987E+10 | 0.134234E+10 | 0.116753E+10 | 0.00 | 0.00 |
February | 0.259180E+10 | 0.288356E+10 | 0.239143E+10 | 0.109553E+10 | 0.129589E+10 | 0.00 | 0.00 |
March | 0.365378E+10 | 0.326357E+10 | 0.321612E+10 | 0.143293E+10 | 0.178319E+10 | 0.00 | 0.00 |
April | 0.519943E+10 | 0.256820E+10 | 0.397913E+10 | 0.199561E+10 | 0.198352E+10 | 0.00 | 0.00 |
May | 0.484834E+10 | 0.242703E+10 | 0.388034E+10 | 0.161936E+10 | 0.226098E+10 | 0.00 | 0.00 |
June | 0.502805E+10 | 0.187092E+10 | 0.373178E+10 | 0.161915E+10 | 0.211263E+10 | 0.00 | 0.00 |
July | 0.637081E+10 | 0.173843E+10 | 0.436934E+10 | 0.217124E+10 | 0.219810E+10 | 0.00 | 0.00 |
August | 0.637902E+10 | 0.177819E+10 | 0.431508E+10 | 0.229202E+10 | 0.202305E+10 | 0.00 | 0.00 |
September | 0.424087E+10 | 0.198393E+10 | 0.304037E+10 | 0.139321E+10 | 0.164716E+10 | 0.00 | 0.00 |
October | 0.395430E+10 | 0.226298E+10 | 0.278099E+10 | 0.142936E+10 | 0.135164E+10 | 0.00 | 0.00 |
November | 0.284938E+10 | 0.309454E+10 | 0.245342E+10 | 0.124644E+10 | 0.120698E+10 | 0.00 | 0.00 |
December | 0.280824E+10 | 0.348116E+10 | 0.241854E+10 | 0.134376E+10 | 0.107477E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.508354E+11 | 0.308394E+11 | 0.390864E+11 | 0.189810E+11 | 0.201054E+11 | 0.00 | 0.00 |
Minimum of Months | 0.259180E+10 | 0.173843E+10 | 0.239143E+10 | 0.109553E+10 | 0.107477E+10 | 0.00 | 0.00 |
Maximum of Months | 0.637902E+10 | 0.348686E+10 | 0.436934E+10 | 0.229202E+10 | 0.226098E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.131224E+11 | 0.558392E+10 | 0.921074E+10 | 0.675650E+10 | 0.245424E+10 | 0.00 | 0.00 |
February | 0.870111E+10 | 0.458988E+10 | 0.653858E+10 | 0.402742E+10 | 0.251116E+10 | 0.00 | 0.00 |
March | 0.755604E+10 | 0.526743E+10 | 0.577129E+10 | 0.278780E+10 | 0.298348E+10 | 0.00 | 0.00 |
April | 0.656866E+10 | 0.419401E+10 | 0.466650E+10 | 0.177938E+10 | 0.288712E+10 | 0.00 | 0.00 |
May | 0.386728E+10 | 0.389935E+10 | 0.343367E+10 | 0.422560E+09 | 0.301111E+10 | 0.00 | 0.00 |
June | 0.331704E+10 | 0.292670E+10 | 0.291507E+10 | 0.176002E+09 | 0.273907E+10 | 0.00 | 0.00 |
July | 0.429016E+10 | 0.266729E+10 | 0.319079E+10 | 0.359192E+09 | 0.283160E+10 | 0.00 | 0.00 |
August | 0.637439E+10 | 0.282977E+10 | 0.409921E+10 | 0.129302E+10 | 0.280619E+10 | 0.00 | 0.00 |
September | 0.858263E+10 | 0.324337E+10 | 0.552005E+10 | 0.279720E+10 | 0.272285E+10 | 0.00 | 0.00 |
October | 0.113029E+11 | 0.367920E+10 | 0.725422E+10 | 0.484965E+10 | 0.240457E+10 | 0.00 | 0.00 |
November | 0.121090E+11 | 0.494696E+10 | 0.853236E+10 | 0.602372E+10 | 0.250865E+10 | 0.00 | 0.00 |
December | 0.140899E+11 | 0.559111E+10 | 0.984002E+10 | 0.748954E+10 | 0.235048E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.998815E+11 | 0.494190E+11 | 0.709725E+11 | 0.387620E+11 | 0.322105E+11 | 0.00 | 0.00 |
Minimum of Months | 0.331704E+10 | 0.266729E+10 | 0.291507E+10 | 0.176002E+09 | 0.235048E+10 | 0.00 | 0.00 |
Maximum of Months | 0.140899E+11 | 0.559111E+10 | 0.984002E+10 | 0.748954E+10 | 0.301111E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.290744E+10 | 0.376718E+10 | 0.238895E+10 | 0.120488E+10 | 0.118407E+10 | 0.00 | 0.00 |
February | 0.296740E+10 | 0.312350E+10 | 0.257422E+10 | 0.118838E+10 | 0.138584E+10 | 0.00 | 0.00 |
March | 0.381805E+10 | 0.352644E+10 | 0.326690E+10 | 0.144533E+10 | 0.182157E+10 | 0.00 | 0.00 |
April | 0.580369E+10 | 0.285390E+10 | 0.435832E+10 | 0.226937E+10 | 0.208895E+10 | 0.00 | 0.00 |
May | 0.569908E+10 | 0.265679E+10 | 0.442395E+10 | 0.204341E+10 | 0.238053E+10 | 0.00 | 0.00 |
June | 0.621246E+10 | 0.203664E+10 | 0.453550E+10 | 0.226766E+10 | 0.226784E+10 | 0.00 | 0.00 |
July | 0.720507E+10 | 0.191416E+10 | 0.496123E+10 | 0.265471E+10 | 0.230652E+10 | 0.00 | 0.00 |
August | 0.686063E+10 | 0.198878E+10 | 0.465460E+10 | 0.252260E+10 | 0.213200E+10 | 0.00 | 0.00 |
September | 0.549116E+10 | 0.217514E+10 | 0.385665E+10 | 0.206364E+10 | 0.179301E+10 | 0.00 | 0.00 |
October | 0.444685E+10 | 0.249330E+10 | 0.304650E+10 | 0.166326E+10 | 0.138324E+10 | 0.00 | 0.00 |
November | 0.332319E+10 | 0.335527E+10 | 0.266313E+10 | 0.139301E+10 | 0.127013E+10 | 0.00 | 0.00 |
December | 0.301525E+10 | 0.382212E+10 | 0.243041E+10 | 0.130356E+10 | 0.112685E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.577503E+11 | 0.337132E+11 | 0.431604E+11 | 0.220198E+11 | 0.211406E+11 | 0.00 | 0.00 |
Minimum of Months | 0.290744E+10 | 0.191416E+10 | 0.238895E+10 | 0.118838E+10 | 0.112685E+10 | 0.00 | 0.00 |
Maximum of Months | 0.720507E+10 | 0.382212E+10 | 0.496123E+10 | 0.265471E+10 | 0.238053E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.962514E+09 | 0.496745E+10 | 0.139571E+10 | 0.00 | 0.139571E+10 | 0.00 | 0.00 |
February | 0.100033E+10 | 0.409949E+10 | 0.158244E+10 | 0.00 | 0.158244E+10 | 0.00 | 0.00 |
March | 0.154674E+10 | 0.475443E+10 | 0.214693E+10 | 0.00 | 0.214693E+10 | 0.00 | 0.00 |
April | 0.202667E+10 | 0.369814E+10 | 0.239372E+10 | 9213078.61 | 0.238451E+10 | 0.00 | 0.00 |
May | 0.264831E+10 | 0.336850E+10 | 0.297238E+10 | 0.138410E+09 | 0.283397E+10 | 0.00 | 0.00 |
June | 0.320491E+10 | 0.261400E+10 | 0.306505E+10 | 0.299660E+09 | 0.276539E+10 | 0.00 | 0.00 |
July | 0.348642E+10 | 0.242517E+10 | 0.299885E+10 | 0.251354E+09 | 0.274750E+10 | 0.00 | 0.00 |
August | 0.281049E+10 | 0.253444E+10 | 0.249045E+10 | 49868784.28 | 0.244058E+10 | 0.00 | 0.00 |
September | 0.214274E+10 | 0.288327E+10 | 0.203991E+10 | 319733.91 | 0.203959E+10 | 0.00 | 0.00 |
October | 0.196263E+10 | 0.329708E+10 | 0.167206E+10 | 0.00 | 0.167206E+10 | 0.00 | 0.00 |
November | 0.104302E+10 | 0.444837E+10 | 0.146510E+10 | 0.00 | 0.146510E+10 | 0.00 | 0.00 |
December | 0.888848E+09 | 0.499692E+10 | 0.129929E+10 | 0.00 | 0.129929E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.237236E+11 | 0.440873E+11 | 0.255219E+11 | 0.748825E+09 | 0.247731E+11 | 0.00 | 0.00 |
Minimum of Months | 0.888848E+09 | 0.242517E+10 | 0.129929E+10 | 0.00 | 0.129929E+10 | 0.00 | 0.00 |
Maximum of Months | 0.348642E+10 | 0.499692E+10 | 0.306505E+10 | 0.299660E+09 | 0.283397E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.302784E+10 | 0.319684E+10 | 0.250987E+10 | 0.134234E+10 | 0.116753E+10 | 0.00 | 0.00 |
February | 0.267483E+10 | 0.265109E+10 | 0.239143E+10 | 0.109553E+10 | 0.129589E+10 | 0.00 | 0.00 |
March | 0.373016E+10 | 0.306632E+10 | 0.321612E+10 | 0.143293E+10 | 0.178319E+10 | 0.00 | 0.00 |
April | 0.521942E+10 | 0.246831E+10 | 0.397913E+10 | 0.199561E+10 | 0.198352E+10 | 0.00 | 0.00 |
May | 0.487970E+10 | 0.233169E+10 | 0.388034E+10 | 0.161936E+10 | 0.226098E+10 | 0.00 | 0.00 |
June | 0.501731E+10 | 0.182880E+10 | 0.373178E+10 | 0.161915E+10 | 0.211263E+10 | 0.00 | 0.00 |
July | 0.633470E+10 | 0.172013E+10 | 0.436934E+10 | 0.217124E+10 | 0.219810E+10 | 0.00 | 0.00 |
August | 0.634824E+10 | 0.175381E+10 | 0.431508E+10 | 0.229202E+10 | 0.202305E+10 | 0.00 | 0.00 |
September | 0.424370E+10 | 0.191262E+10 | 0.304037E+10 | 0.139321E+10 | 0.164716E+10 | 0.00 | 0.00 |
October | 0.397948E+10 | 0.215929E+10 | 0.278099E+10 | 0.142936E+10 | 0.135164E+10 | 0.00 | 0.00 |
November | 0.293399E+10 | 0.287949E+10 | 0.245342E+10 | 0.124644E+10 | 0.120698E+10 | 0.00 | 0.00 |
December | 0.292534E+10 | 0.320244E+10 | 0.241854E+10 | 0.134376E+10 | 0.107477E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.513147E+11 | 0.291708E+11 | 0.390864E+11 | 0.189810E+11 | 0.201054E+11 | 0.00 | 0.00 |
Minimum of Months | 0.267483E+10 | 0.172013E+10 | 0.239143E+10 | 0.109553E+10 | 0.107477E+10 | 0.00 | 0.00 |
Maximum of Months | 0.634824E+10 | 0.320244E+10 | 0.436934E+10 | 0.229202E+10 | 0.226098E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.132532E+11 | 0.516903E+10 | 0.921074E+10 | 0.675650E+10 | 0.245424E+10 | 0.00 | 0.00 |
February | 0.880004E+10 | 0.422910E+10 | 0.653858E+10 | 0.402742E+10 | 0.251116E+10 | 0.00 | 0.00 |
March | 0.765106E+10 | 0.492405E+10 | 0.577129E+10 | 0.278780E+10 | 0.298348E+10 | 0.00 | 0.00 |
April | 0.659828E+10 | 0.399734E+10 | 0.466650E+10 | 0.177938E+10 | 0.288712E+10 | 0.00 | 0.00 |
May | 0.391782E+10 | 0.370127E+10 | 0.343367E+10 | 0.422560E+09 | 0.301111E+10 | 0.00 | 0.00 |
June | 0.331588E+10 | 0.283072E+10 | 0.291507E+10 | 0.176002E+09 | 0.273907E+10 | 0.00 | 0.00 |
July | 0.425673E+10 | 0.261506E+10 | 0.319079E+10 | 0.359192E+09 | 0.283160E+10 | 0.00 | 0.00 |
August | 0.633900E+10 | 0.276692E+10 | 0.409921E+10 | 0.129302E+10 | 0.280619E+10 | 0.00 | 0.00 |
September | 0.857510E+10 | 0.311644E+10 | 0.552005E+10 | 0.279720E+10 | 0.272285E+10 | 0.00 | 0.00 |
October | 0.113216E+11 | 0.351606E+10 | 0.725422E+10 | 0.484965E+10 | 0.240457E+10 | 0.00 | 0.00 |
November | 0.121934E+11 | 0.463830E+10 | 0.853236E+10 | 0.602372E+10 | 0.250865E+10 | 0.00 | 0.00 |
December | 0.142143E+11 | 0.520851E+10 | 0.984002E+10 | 0.748954E+10 | 0.235048E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.100436E+12 | 0.467128E+11 | 0.709725E+11 | 0.387620E+11 | 0.322105E+11 | 0.00 | 0.00 |
Minimum of Months | 0.331588E+10 | 0.261506E+10 | 0.291507E+10 | 0.176002E+09 | 0.235048E+10 | 0.00 | 0.00 |
Maximum of Months | 0.142143E+11 | 0.520851E+10 | 0.984002E+10 | 0.748954E+10 | 0.301111E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.297292E+10 | 0.348531E+10 | 0.238895E+10 | 0.120488E+10 | 0.118407E+10 | 0.00 | 0.00 |
February | 0.302230E+10 | 0.289503E+10 | 0.257422E+10 | 0.118838E+10 | 0.138584E+10 | 0.00 | 0.00 |
March | 0.386790E+10 | 0.331406E+10 | 0.326690E+10 | 0.144533E+10 | 0.182157E+10 | 0.00 | 0.00 |
April | 0.580667E+10 | 0.273513E+10 | 0.435832E+10 | 0.226937E+10 | 0.208895E+10 | 0.00 | 0.00 |
May | 0.570701E+10 | 0.254482E+10 | 0.442395E+10 | 0.204341E+10 | 0.238053E+10 | 0.00 | 0.00 |
June | 0.618573E+10 | 0.198072E+10 | 0.453550E+10 | 0.226766E+10 | 0.226784E+10 | 0.00 | 0.00 |
July | 0.715923E+10 | 0.188039E+10 | 0.496123E+10 | 0.265471E+10 | 0.230652E+10 | 0.00 | 0.00 |
August | 0.682108E+10 | 0.194958E+10 | 0.465460E+10 | 0.252260E+10 | 0.213200E+10 | 0.00 | 0.00 |
September | 0.548142E+10 | 0.209730E+10 | 0.385665E+10 | 0.206364E+10 | 0.179301E+10 | 0.00 | 0.00 |
October | 0.445910E+10 | 0.237868E+10 | 0.304650E+10 | 0.166326E+10 | 0.138324E+10 | 0.00 | 0.00 |
November | 0.337258E+10 | 0.313428E+10 | 0.266313E+10 | 0.139301E+10 | 0.127013E+10 | 0.00 | 0.00 |
December | 0.308030E+10 | 0.354301E+10 | 0.243041E+10 | 0.130356E+10 | 0.112685E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.579362E+11 | 0.319383E+11 | 0.431604E+11 | 0.220198E+11 | 0.211406E+11 | 0.00 | 0.00 |
Minimum of Months | 0.297292E+10 | 0.188039E+10 | 0.238895E+10 | 0.118838E+10 | 0.112685E+10 | 0.00 | 0.00 |
Maximum of Months | 0.715923E+10 | 0.354301E+10 | 0.496123E+10 | 0.265471E+10 | 0.238053E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.22 | 9.61 | 5.99 | 2.23 | 0.81 | 45.19 | 208.20 | 0.00 |
February | 13.28 | 10.20 | 7.03 | 3.12 | 2.96 | 66.07 | 175.60 | 0.04 |
March | 12.64 | 10.61 | 8.97 | 2.93 | 3.55 | 84.90 | 179.28 | 0.03 |
April | 15.30 | 12.62 | 10.61 | 2.62 | 4.76 | 81.20 | 282.81 | 0.02 |
May | 15.56 | 12.65 | 10.56 | 2.92 | 6.17 | 105.80 | 234.18 | 0.01 |
June | 17.67 | 14.80 | 13.02 | 2.53 | 9.03 | 98.05 | 261.27 | 0.00 |
July | 19.43 | 16.76 | 15.28 | 2.35 | 9.62 | 86.54 | 312.15 | 0.00 |
August | 19.66 | 17.23 | 15.95 | 2.55 | 9.62 | 74.58 | 307.55 | 0.00 |
September | 18.47 | 15.50 | 13.65 | 2.19 | 8.99 | 70.75 | 240.05 | 0.00 |
October | 18.77 | 13.72 | 9.60 | 2.71 | 7.74 | 53.88 | 216.36 | 0.00 |
November | 14.32 | 10.43 | 6.22 | 2.47 | 2.41 | 50.75 | 207.87 | 0.01 |
December | 13.59 | 8.82 | 3.19 | 2.50 | 0.05 | 39.49 | 221.83 | 0.00 |
Annual Sum or Average | 16.01 | 12.76 | 10.02 | 2.59 | 5.49 | 71.44 | 237.65 | 0.01 |
Minimum of Months | 12.64 | 8.82 | 3.19 | 2.19 | 0.05 | 39.49 | 175.60 | 0.00 |
Maximum of Months | 19.66 | 17.23 | 15.95 | 3.12 | 9.62 | 105.80 | 312.15 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 26.00 | 13-JAN-13:00 | 15.46 | 8.00 | 3.10 | 11.84 | 120.00 | 725.00 |
February | 26.00 | 01-FEB-11:00 | 14.67 | 6.00 | 4.10 | 10.11 | 166.00 | 715.50 |
March | 24.00 | 11-MAR-10:00 | 13.82 | 6.00 | 2.60 | 8.15 | 120.00 | 907.00 |
April | 27.00 | 26-APR-12:00 | 17.13 | 11.00 | 4.10 | 12.22 | 159.00 | 884.00 |
May | 24.00 | 03-MAY-11:00 | 15.05 | 9.00 | 4.10 | 12.98 | 187.00 | 842.50 |
June | 25.00 | 29-JUN-10:00 | 19.59 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 28.00 | 19-JUL-10:00 | 20.49 | 17.00 | 3.60 | 14.65 | 173.00 | 813.00 |
August | 28.00 | 14-AUG-10:00 | 21.19 | 18.00 | 3.60 | 14.84 | 148.00 | 840.00 |
September | 36.00 | 29-SEP-10:00 | 17.91 | 5.00 | 3.60 | 19.35 | 159.50 | 790.00 |
October | 37.00 | 16-OCT-10:00 | 17.87 | 4.00 | 5.70 | 20.05 | 122.00 | 871.50 |
November | 27.00 | 19-NOV-12:00 | 14.96 | 6.00 | 4.10 | 11.07 | 128.50 | 796.00 |
December | 26.00 | 05-DEC-09:00 | 13.09 | 1.00 | 3.60 | 8.94 | 75.50 | 857.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.00 | 13.09 | 1.00 | 2.60 | 8.15 | 75.50 | 715.50 | |
Maximum of Months | 37.00 | 21.19 | 18.00 | 5.70 | 20.05 | 187.00 | 907.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.00 | 08-JAN-06:00 | -0.3 | -2.0 | 3.10 | -15.5 | 11.50 | 193.50 |
February | 5.00 | 04-FEB-05:00 | 0.22 | -8.0 | 4.10 | -10.9 | 0.00 | 0.00 |
March | 4.00 | 07-MAR-04:00 | 3.53 | 3.00 | 0.00 | -11.4 | 0.00 | 0.00 |
April | 7.00 | 01-APR-05:00 | 4.33 | 1.00 | 4.10 | -9.0 | 23.50 | 211.00 |
May | 8.00 | 14-MAY-03:00 | 7.45 | 7.00 | 1.50 | -6.6 | 0.00 | 0.00 |
June | 11.00 | 13-JUN-03:00 | 9.85 | 9.00 | 2.10 | -3.4 | 0.00 | 0.00 |
July | 13.00 | 06-JUL-00:00 | 13.00 | 13.00 | 0.00 | -0.6 | 0.00 | 0.00 |
August | 14.00 | 24-AUG-01:00 | 14.00 | 14.00 | 0.00 | 0.51 | 0.00 | 0.00 |
September | 11.00 | 20-SEP-02:00 | 9.85 | 9.00 | 1.50 | -3.4 | 0.00 | 0.00 |
October | 9.00 | 12-OCT-04:00 | 6.56 | 4.00 | 3.10 | -6.4 | 0.00 | 0.00 |
November | 7.00 | 05-NOV-01:00 | 5.54 | 4.00 | 3.10 | -8.3 | 0.00 | 0.00 |
December | 5.00 | 03-DEC-00:00 | 5.00 | 5.00 | 2.10 | -0.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | -0.3 | -8.0 | 0.00 | -15.5 | 0.00 | 0.00 | |
Maximum of Months | 14.00 | 14.00 | 14.00 | 4.10 | 0.51 | 23.50 | 211.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.04 | 17-JAN-11:00 | 24.00 | 13.00 | 3.10 | 12.79 | 223.50 | 9.00 |
February | 16.80 | 11-FEB-13:00 | 18.00 | 16.20 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 17.41 | 22-MAR-12:00 | 22.00 | 15.00 | 3.10 | 8.35 | 145.50 | 876.00 |
April | 18.33 | 26-APR-10:00 | 26.00 | 14.00 | 4.10 | 12.03 | 141.50 | 915.50 |
May | 16.69 | 05-MAY-14:00 | 18.00 | 16.00 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 19.59 | 29-JUN-10:00 | 25.00 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 21.19 | 19-JUL-11:00 | 28.00 | 18.00 | 4.60 | 14.84 | 182.50 | 808.00 |
August | 21.20 | 18-AUG-11:00 | 28.00 | 18.00 | 3.60 | 17.21 | 244.00 | 667.50 |
September | 21.85 | 22-SEP-11:00 | 26.00 | 20.00 | 2.60 | 20.05 | 284.00 | 21.00 |
October | 21.09 | 01-OCT-11:00 | 26.00 | 19.00 | 3.60 | 13.16 | 102.00 | 899.50 |
November | 16.52 | 10-NOV-12:00 | 21.00 | 14.00 | 5.10 | 7.15 | 131.00 | 808.50 |
December | 15.64 | 07-DEC-12:00 | 20.00 | 13.00 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.64 | 18.00 | 13.00 | 1.10 | 5.94 | 89.00 | 9.00 | |
Maximum of Months | 21.85 | 28.00 | 20.00 | 5.10 | 20.05 | 303.50 | 915.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 17-JAN-12:00 | 22.00 | 16.85 | 2.10 | 11.65 | 241.50 | 67.50 |
February | 16.20 | 11-FEB-13:00 | 18.00 | 16.80 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 15.00 | 23-MAR-15:20 | 21.67 | 17.34 | 3.77 | 8.02 | 112.00 | 809.83 |
April | 15.00 | 26-APR-21:19 | 16.00 | 15.39 | 2.23 | 6.15 | 0.00 | 0.00 |
May | 16.00 | 05-MAY-14:00 | 18.00 | 16.69 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 17.00 | 28-JUN-08:00 | 19.00 | 17.66 | 1.50 | 16.12 | 285.00 | 428.50 |
July | 18.00 | 18-JUL-10:00 | 26.00 | 20.47 | 4.60 | 12.79 | 169.00 | 819.00 |
August | 18.10 | 14-AUG-09:00 | 26.90 | 20.93 | 3.40 | 13.73 | 139.00 | 817.00 |
September | 20.00 | 22-SEP-09:00 | 22.00 | 20.55 | 1.50 | 16.30 | 296.00 | 18.00 |
October | 19.00 | 01-OCT-07:10 | 19.17 | 19.06 | 0.25 | 16.82 | 53.33 | 0.00 |
November | 15.00 | 10-NOV-17:19 | 16.67 | 15.62 | 2.77 | 3.34 | 0.00 | 0.00 |
December | 13.00 | 07-DEC-12:00 | 20.00 | 15.64 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.00 | 16.00 | 15.39 | 0.25 | 3.34 | 0.00 | 0.00 | |
Maximum of Months | 20.00 | 26.90 | 20.93 | 5.10 | 16.82 | 303.50 | 868.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 17.43 | 27.46 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 17.38 | 30.87 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 17.83 | 38.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 18.69 | 55.75 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 19.73 | 55.13 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.65 | 58.21 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.22 | 63.49 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 21.28 | 59.02 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.81 | 46.26 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.94 | 34.64 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.91 | 29.25 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 17.99 | 26.27 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.33 | 43.77 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 17.38 | 26.27 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 21.28 | 63.49 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.343123E+11 | -0.338717E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -440596753.8 | 60.05 | 0.00 | 0.00 |
February | 0.312141E+11 | -0.308141E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -399989647.6 | 60.05 | 0.00 | 0.00 |
March | 0.363071E+11 | -0.358631E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -444012416.0 | 60.05 | 0.00 | 0.00 |
April | 0.322834E+11 | -0.318553E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -428161779.0 | 60.05 | 0.00 | 0.00 |
May | 0.336116E+11 | -0.331681E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -443515248.3 | 60.05 | 0.00 | 0.00 |
June | 0.325775E+11 | -0.321480E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -429464305.1 | 60.05 | 0.00 | 0.00 |
July | 0.305619E+11 | -0.301227E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -439180923.7 | 60.05 | 0.00 | 0.00 |
August | 0.333736E+11 | -0.329331E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -440437625.4 | 60.05 | 0.00 | 0.00 |
September | 0.306530E+11 | -0.302295E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -423481833.6 | 60.05 | 0.00 | 0.00 |
October | 0.323116E+11 | -0.318763E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -435298504.7 | 60.05 | 0.00 | 0.00 |
November | 0.325056E+11 | -0.320795E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -426146949.4 | 60.05 | 0.00 | 0.00 |
December | 0.330750E+11 | -0.326345E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -440462919.5 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.392787E+12 | -0.387596E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.519075E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.305619E+11 | -0.358631E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -444012416.0 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.363071E+11 | -0.301227E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -399989647.6 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.50 | 0.48 | 01-JAN-07:30 | 7865.64 | 37.55 | 285.17 | 281.00 | 1699.37 | 26.83 | 209.17 | 265.33 |
February | 279.67 | 0.50 | 0.48 | 01-FEB-07:30 | 6982.62 | 35.77 | 275.67 | 274.67 | 1253.95 | 24.80 | 216.83 | 253.00 |
March | 338.17 | 0.53 | 0.48 | 01-MAR-06:49 | 2072.88 | 20.45 | 99.50 | 315.50 | 1001.94 | 21.28 | 199.33 | 286.83 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:10 | 1365.16 | 19.64 | 38.33 | 332.67 | 826.77 | 21.00 | 159.83 | 297.50 |
May | 393.83 | 0.52 | 0.48 | 01-MAY-06:49 | 1175.10 | 19.43 | 1.17 | 365.83 | 674.43 | 20.79 | 162.00 | 323.17 |
June | 381.00 | 0.52 | 0.48 | 01-JUN-06:49 | 1045.35 | 19.07 | 0.00 | 358.00 | 619.36 | 20.45 | 115.00 | 311.17 |
July | 408.67 | 0.52 | 0.48 | 01-JUL-06:30 | 1054.92 | 19.10 | 1.17 | 368.17 | 644.93 | 20.50 | 145.83 | 332.33 |
August | 390.67 | 0.52 | 0.48 | 01-AUG-07:19 | 1178.22 | 19.25 | 9.50 | 354.83 | 728.98 | 20.61 | 154.67 | 317.33 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:00 | 1711.05 | 20.27 | 54.33 | 309.83 | 951.00 | 21.04 | 153.33 | 278.00 |
October | 296.17 | 0.51 | 0.48 | 01-OCT-09:39 | 3871.48 | 27.18 | 157.50 | 304.67 | 1169.84 | 21.77 | 139.67 | 276.50 |
November | 300.00 | 0.51 | 0.48 | 01-NOV-06:49 | 7613.02 | 37.32 | 294.83 | 279.50 | 1527.62 | 26.39 | 220.33 | 270.17 |
December | 297.00 | 0.50 | 0.48 | 01-DEC-07:19 | 7739.72 | 38.43 | 293.33 | 283.17 | 2166.54 | 29.57 | 209.67 | 271.50 |
Annual Sum or Average | 4065.67 | 0.51 | 3319.15 | 25.22 | 1510.50 | 3827.83 | 1056.44 | 22.63 | 2085.67 | 3482.83 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 1045.35 | 19.07 | 0.00 | 274.67 | 619.36 | 20.45 | 115.00 | 253.00 | |
Maximum of Months | 408.67 | 0.53 | 0.48 | 7865.64 | 38.43 | 294.83 | 368.17 | 2166.54 | 29.57 | 220.33 | 332.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.52 | 0.48 | 01-JAN-07:19 | 1747.24 | 23.81 | 90.33 | 266.50 | 886.13 | 23.59 | 112.00 | 229.33 |
February | 279.67 | 0.51 | 0.48 | 01-FEB-07:10 | 1910.04 | 23.88 | 87.33 | 268.50 | 996.99 | 23.94 | 119.67 | 224.50 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-06:40 | 2328.06 | 23.80 | 107.17 | 317.67 | 1268.40 | 24.00 | 142.17 | 279.83 |
April | 358.33 | 0.51 | 0.48 | 01-APR-05:00 | 2359.88 | 23.19 | 93.83 | 339.17 | 1247.02 | 23.54 | 104.33 | 308.83 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-06:19 | 2275.14 | 22.55 | 99.67 | 378.00 | 1238.19 | 23.14 | 126.33 | 333.50 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-06:19 | 2267.93 | 21.76 | 89.33 | 369.33 | 1202.16 | 22.42 | 90.17 | 327.33 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-05:30 | 2497.18 | 22.19 | 99.67 | 378.33 | 1314.75 | 22.71 | 95.67 | 343.33 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-06:49 | 2510.58 | 23.00 | 103.33 | 363.17 | 1278.70 | 23.25 | 92.33 | 329.83 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:40 | 2621.24 | 23.30 | 98.83 | 313.00 | 993.85 | 22.26 | 86.83 | 277.50 |
October | 296.17 | 0.53 | 0.48 | 01-OCT-09:39 | 2370.37 | 23.20 | 89.33 | 286.50 | 975.16 | 22.14 | 90.33 | 241.33 |
November | 300.00 | 0.53 | 0.48 | 01-NOV-06:40 | 1991.58 | 24.05 | 98.67 | 265.00 | 1075.33 | 24.00 | 126.00 | 233.67 |
December | 297.00 | 0.53 | 0.48 | 01-DEC-07:10 | 1746.44 | 24.26 | 97.83 | 267.50 | 907.80 | 23.94 | 108.83 | 227.00 |
Annual Sum or Average | 4065.67 | 0.52 | 2243.46 | 23.17 | 1155.33 | 3812.67 | 1132.63 | 23.21 | 1294.67 | 3356.00 | ||
Minimum of Months | 279.67 | 0.51 | 0.48 | 1746.44 | 21.76 | 87.33 | 265.00 | 886.13 | 22.14 | 86.83 | 224.50 | |
Maximum of Months | 408.67 | 0.53 | 0.48 | 2621.24 | 24.26 | 107.17 | 378.33 | 1314.75 | 24.00 | 142.17 | 343.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.56 | 0.48 | 01-JAN-09:09 | 555.66 | 16.94 | 0.00 | 237.67 | 358.51 | 18.70 | 0.00 | 164.83 |
February | 279.67 | 0.54 | 0.48 | 01-FEB-08:00 | 661.96 | 17.69 | 0.00 | 249.00 | 404.89 | 19.18 | 0.00 | 179.83 |
March | 338.17 | 0.54 | 0.48 | 01-MAR-08:30 | 774.06 | 18.00 | 0.00 | 306.50 | 461.37 | 19.33 | 6.67 | 252.33 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:19 | 864.01 | 19.16 | 0.00 | 336.33 | 547.26 | 20.54 | 65.17 | 297.83 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:40 | 1072.06 | 19.86 | 27.83 | 382.67 | 621.84 | 21.17 | 158.00 | 352.83 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:40 | 1132.81 | 21.53 | 84.00 | 375.50 | 671.49 | 22.72 | 182.83 | 342.17 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-05:49 | 1064.60 | 21.42 | 86.17 | 385.00 | 624.87 | 21.21 | 176.50 | 360.83 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:19 | 876.47 | 19.24 | 7.67 | 364.33 | 563.76 | 20.59 | 86.00 | 338.17 |
September | 328.83 | 0.52 | 0.48 | 01-SEP-07:10 | 772.40 | 18.49 | 0.00 | 305.50 | 492.50 | 19.93 | 9.17 | 259.67 |
October | 296.17 | 0.55 | 0.48 | 01-OCT-09:39 | 591.52 | 17.12 | 0.00 | 263.67 | 385.70 | 18.70 | 0.50 | 185.17 |
November | 300.00 | 0.57 | 0.48 | 01-NOV-08:09 | 564.22 | 16.52 | 0.00 | 241.33 | 361.01 | 18.17 | 0.00 | 172.17 |
December | 297.00 | 0.58 | 0.48 | 01-DEC-08:50 | 506.22 | 16.21 | 0.00 | 230.50 | 332.35 | 18.04 | 0.00 | 145.50 |
Annual Sum or Average | 4065.67 | 0.53 | 811.57 | 18.71 | 205.67 | 3678.00 | 499.32 | 20.01 | 684.83 | 3051.33 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 506.22 | 16.21 | 0.00 | 230.50 | 332.35 | 18.04 | 0.00 | 145.50 | |
Maximum of Months | 408.67 | 0.58 | 0.48 | 1132.81 | 21.53 | 86.17 | 385.00 | 671.49 | 22.72 | 182.83 | 360.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.53 | 0.48 | 01-JAN-08:00 | 2264.55 | 24.59 | 107.00 | 254.17 | 851.09 | 22.83 | 119.17 | 216.17 |
February | 279.67 | 0.53 | 0.48 | 01-FEB-08:00 | 2084.86 | 23.94 | 90.17 | 257.17 | 1111.42 | 24.10 | 134.33 | 217.67 |
March | 338.17 | 0.53 | 0.48 | 01-MAR-08:30 | 2324.33 | 23.34 | 101.17 | 311.17 | 1248.48 | 23.56 | 143.67 | 270.67 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:49 | 3199.49 | 22.09 | 82.33 | 333.00 | 1205.05 | 20.09 | 78.33 | 300.50 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-07:30 | 3003.12 | 20.11 | 52.83 | 368.83 | 1214.86 | 20.26 | 98.00 | 331.17 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-07:10 | 2546.84 | 17.91 | 0.00 | 362.33 | 1375.80 | 20.27 | 91.83 | 327.33 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-06:00 | 2686.63 | 17.96 | 5.67 | 372.17 | 1421.48 | 20.19 | 90.50 | 345.50 |
August | 390.67 | 0.52 | 0.48 | 01-AUG-07:49 | 3318.21 | 21.78 | 88.33 | 356.50 | 1343.83 | 20.27 | 82.83 | 327.33 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-07:40 | 2957.88 | 24.53 | 106.67 | 306.67 | 1518.01 | 24.35 | 115.33 | 273.67 |
October | 296.17 | 0.52 | 0.48 | 01-OCT-09:39 | 2832.50 | 25.27 | 114.33 | 288.17 | 1122.03 | 23.55 | 105.50 | 244.83 |
November | 300.00 | 0.54 | 0.48 | 01-NOV-08:09 | 2212.42 | 24.42 | 106.67 | 257.67 | 1204.27 | 24.36 | 136.17 | 219.50 |
December | 297.00 | 0.55 | 0.48 | 01-DEC-08:50 | 2010.06 | 24.41 | 110.50 | 249.33 | 1105.75 | 24.31 | 122.67 | 205.00 |
Annual Sum or Average | 4065.67 | 0.52 | 2656.25 | 22.24 | 965.67 | 3717.17 | 1240.68 | 22.13 | 1318.33 | 3279.33 | ||
Minimum of Months | 279.67 | 0.51 | 0.48 | 2010.06 | 17.91 | 0.00 | 249.33 | 851.09 | 20.09 | 78.33 | 205.00 | |
Maximum of Months | 408.67 | 0.55 | 0.48 | 3318.21 | 25.27 | 114.33 | 372.17 | 1518.01 | 24.36 | 143.67 | 345.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.50 | 0.48 | 01-JAN-07:30 | 7934.84 | 37.02 | 284.83 | 281.17 | 1811.36 | 22.58 | 97.17 | 266.33 |
February | 279.67 | 0.50 | 0.48 | 01-FEB-07:19 | 7024.78 | 35.34 | 275.17 | 274.67 | 1343.94 | 20.77 | 61.00 | 255.17 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-06:49 | 2108.14 | 14.22 | 11.17 | 316.00 | 1073.39 | 17.05 | 3.50 | 290.50 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:10 | 1400.91 | 13.63 | 0.00 | 333.33 | 887.32 | 17.16 | 0.00 | 305.00 |
May | 393.83 | 0.52 | 0.48 | 01-MAY-06:49 | 1196.30 | 13.62 | 0.00 | 366.33 | 719.45 | 17.06 | 0.00 | 330.17 |
June | 381.00 | 0.52 | 0.48 | 01-JUN-06:49 | 1065.51 | 13.39 | 0.00 | 358.17 | 660.88 | 16.86 | 0.00 | 316.17 |
July | 408.67 | 0.52 | 0.48 | 01-JUL-06:30 | 1078.05 | 13.55 | 0.00 | 368.83 | 689.17 | 17.04 | 0.00 | 335.83 |
August | 390.67 | 0.52 | 0.48 | 01-AUG-07:19 | 1209.19 | 13.53 | 0.00 | 355.17 | 781.87 | 17.03 | 0.00 | 324.17 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:00 | 1754.14 | 14.16 | 14.00 | 310.00 | 1022.99 | 16.91 | 0.17 | 283.00 |
October | 296.17 | 0.50 | 0.48 | 01-OCT-09:39 | 3932.02 | 23.19 | 141.67 | 304.67 | 1261.30 | 17.16 | 14.00 | 279.50 |
November | 300.00 | 0.51 | 0.48 | 01-NOV-06:49 | 7672.95 | 36.92 | 294.67 | 279.67 | 1631.17 | 22.19 | 92.67 | 270.83 |
December | 297.00 | 0.50 | 0.48 | 01-DEC-07:19 | 7810.76 | 38.01 | 293.00 | 283.17 | 2281.85 | 26.00 | 143.00 | 272.83 |
Annual Sum or Average | 4065.67 | 0.51 | 3359.88 | 21.06 | 1314.50 | 3831.17 | 1128.32 | 18.72 | 411.50 | 3529.50 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 1065.51 | 13.39 | 0.00 | 274.67 | 660.88 | 16.86 | 0.00 | 255.17 | |
Maximum of Months | 408.67 | 0.52 | 0.48 | 7934.84 | 38.01 | 294.67 | 368.83 | 2281.85 | 26.00 | 143.00 | 335.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.52 | 0.48 | 01-JAN-07:19 | 1780.64 | 21.08 | 85.00 | 266.50 | 930.56 | 21.56 | 55.00 | 235.17 |
February | 279.67 | 0.51 | 0.48 | 01-FEB-07:10 | 1915.68 | 19.71 | 70.83 | 268.83 | 1044.62 | 21.80 | 54.50 | 230.33 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-06:49 | 2371.55 | 21.01 | 106.50 | 318.33 | 1320.65 | 21.85 | 77.67 | 284.17 |
April | 358.33 | 0.51 | 0.48 | 01-APR-05:00 | 2401.87 | 20.00 | 93.67 | 340.00 | 1309.63 | 21.00 | 65.17 | 311.17 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-06:10 | 2305.77 | 19.35 | 99.33 | 378.83 | 1295.11 | 20.63 | 70.17 | 338.83 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-06:10 | 2304.42 | 18.51 | 88.83 | 370.00 | 1259.24 | 19.84 | 60.67 | 334.17 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-05:30 | 2533.37 | 19.01 | 99.67 | 379.00 | 1378.40 | 20.14 | 68.67 | 348.83 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-06:49 | 2544.94 | 19.86 | 103.33 | 363.50 | 1342.60 | 20.69 | 69.67 | 334.00 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:40 | 2667.76 | 20.48 | 98.83 | 313.83 | 1048.43 | 19.71 | 43.67 | 282.17 |
October | 296.17 | 0.53 | 0.48 | 01-OCT-09:39 | 2413.53 | 20.36 | 88.83 | 287.33 | 1024.38 | 19.69 | 42.50 | 247.33 |
November | 300.00 | 0.53 | 0.48 | 01-NOV-06:40 | 2019.70 | 21.38 | 95.17 | 265.67 | 1119.77 | 22.14 | 68.33 | 238.50 |
December | 297.00 | 0.53 | 0.48 | 01-DEC-07:10 | 1754.67 | 20.74 | 86.17 | 267.50 | 951.45 | 22.13 | 64.33 | 232.83 |
Annual Sum or Average | 4065.67 | 0.52 | 2276.48 | 20.05 | 1116.17 | 3819.33 | 1186.84 | 20.87 | 740.33 | 3417.50 | ||
Minimum of Months | 279.67 | 0.51 | 0.48 | 1754.67 | 18.51 | 70.83 | 265.67 | 930.56 | 19.69 | 42.50 | 230.33 | |
Maximum of Months | 408.67 | 0.53 | 0.48 | 2667.76 | 21.38 | 106.50 | 379.00 | 1378.40 | 22.14 | 77.67 | 348.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.56 | 0.48 | 01-JAN-08:00 | 564.86 | 11.20 | 0.00 | 239.00 | 381.89 | 15.01 | 0.00 | 179.67 |
February | 279.67 | 0.54 | 0.48 | 01-FEB-08:50 | 673.17 | 12.16 | 0.00 | 250.33 | 431.18 | 15.71 | 0.00 | 191.67 |
March | 338.17 | 0.54 | 0.48 | 01-MAR-08:20 | 788.09 | 12.62 | 0.00 | 306.83 | 491.48 | 15.99 | 0.00 | 260.50 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:10 | 883.63 | 13.81 | 0.00 | 336.50 | 584.50 | 17.35 | 0.00 | 304.50 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:40 | 1092.67 | 14.13 | 0.00 | 383.00 | 662.35 | 17.69 | 0.00 | 356.00 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:40 | 1155.98 | 16.33 | 42.50 | 375.83 | 714.76 | 19.55 | 40.83 | 347.50 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-05:49 | 1089.62 | 16.42 | 45.17 | 385.50 | 667.94 | 17.88 | 0.00 | 363.33 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:19 | 906.91 | 13.93 | 0.00 | 366.33 | 601.94 | 17.50 | 0.00 | 342.33 |
September | 328.83 | 0.52 | 0.48 | 01-SEP-06:00 | 788.94 | 13.13 | 0.00 | 305.67 | 525.70 | 16.66 | 0.00 | 266.17 |
October | 296.17 | 0.55 | 0.48 | 01-OCT-09:39 | 604.32 | 11.60 | 0.00 | 266.17 | 411.75 | 15.28 | 0.00 | 201.00 |
November | 300.00 | 0.56 | 0.48 | 01-NOV-07:49 | 574.00 | 11.07 | 0.00 | 243.00 | 384.63 | 14.66 | 0.00 | 186.00 |
December | 297.00 | 0.57 | 0.48 | 01-DEC-08:39 | 514.32 | 10.54 | 0.00 | 231.50 | 354.01 | 14.33 | 0.00 | 160.67 |
Annual Sum or Average | 4065.67 | 0.53 | 829.09 | 13.29 | 87.67 | 3689.67 | 532.48 | 16.64 | 40.83 | 3159.33 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 514.32 | 10.54 | 0.00 | 231.50 | 354.01 | 14.33 | 0.00 | 160.67 | |
Maximum of Months | 408.67 | 0.57 | 0.48 | 1155.98 | 16.42 | 45.17 | 385.50 | 714.76 | 19.55 | 40.83 | 363.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.53 | 0.48 | 01-JAN-08:00 | 2296.82 | 22.17 | 105.33 | 255.17 | 895.58 | 20.71 | 45.33 | 221.83 |
February | 279.67 | 0.52 | 0.48 | 01-FEB-08:50 | 2124.38 | 21.19 | 85.17 | 258.00 | 1161.57 | 21.98 | 60.00 | 223.17 |
March | 338.17 | 0.53 | 0.48 | 01-MAR-08:20 | 2373.22 | 20.52 | 100.83 | 311.50 | 1301.97 | 21.33 | 71.50 | 275.50 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:40 | 3239.97 | 18.75 | 82.33 | 333.50 | 1271.90 | 16.75 | 0.00 | 304.50 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-07:19 | 3033.97 | 16.18 | 52.50 | 370.00 | 1278.37 | 16.89 | 0.00 | 336.83 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-07:10 | 2590.16 | 13.22 | 0.00 | 364.83 | 1440.78 | 16.80 | 0.00 | 330.83 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-06:49 | 2726.35 | 13.36 | 5.67 | 373.33 | 1490.52 | 16.72 | 0.00 | 348.83 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:49 | 3349.44 | 18.41 | 88.17 | 357.83 | 1411.57 | 16.96 | 7.00 | 331.17 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-07:30 | 3006.72 | 21.45 | 104.83 | 307.67 | 1584.20 | 22.00 | 73.67 | 277.83 |
October | 296.17 | 0.52 | 0.48 | 01-OCT-09:39 | 2862.54 | 21.91 | 107.83 | 289.00 | 1176.89 | 21.23 | 58.50 | 251.67 |
November | 300.00 | 0.54 | 0.48 | 01-NOV-07:00 | 2247.30 | 22.00 | 104.33 | 258.50 | 1250.89 | 22.51 | 75.00 | 225.50 |
December | 297.00 | 0.55 | 0.48 | 01-DEC-08:39 | 2040.94 | 22.02 | 104.67 | 251.00 | 1149.62 | 22.56 | 74.67 | 211.83 |
Annual Sum or Average | 4065.67 | 0.52 | 2693.94 | 18.90 | 941.67 | 3730.33 | 1299.36 | 19.41 | 465.67 | 3339.50 | ||
Minimum of Months | 279.67 | 0.51 | 0.48 | 2040.94 | 13.22 | 0.00 | 251.00 | 895.58 | 16.72 | 0.00 | 211.83 | |
Maximum of Months | 408.67 | 0.55 | 0.48 | 3349.44 | 22.17 | 107.83 | 373.33 | 1584.20 | 22.56 | 75.00 | 348.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.50 | 0.48 | 01-JAN-07:30 | 7936.18 | 37.01 | 284.83 | 281.17 | 1813.21 | 22.57 | 97.17 | 266.33 |
February | 279.67 | 0.50 | 0.48 | 01-FEB-07:19 | 7027.13 | 35.33 | 275.00 | 274.67 | 1345.81 | 20.76 | 61.00 | 255.17 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-06:49 | 2110.68 | 14.19 | 11.17 | 316.00 | 1074.99 | 17.03 | 3.33 | 290.50 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:10 | 1402.52 | 13.60 | 0.00 | 333.33 | 888.42 | 17.15 | 0.00 | 305.50 |
May | 393.83 | 0.52 | 0.48 | 01-MAY-06:49 | 1197.86 | 13.59 | 0.00 | 366.50 | 720.47 | 17.05 | 0.00 | 330.33 |
June | 381.00 | 0.52 | 0.48 | 01-JUN-06:49 | 1066.75 | 13.36 | 0.00 | 358.17 | 661.74 | 16.84 | 0.00 | 316.17 |
July | 408.67 | 0.52 | 0.48 | 01-JUL-06:30 | 1079.14 | 13.52 | 0.00 | 369.00 | 689.99 | 17.03 | 0.00 | 336.33 |
August | 390.67 | 0.52 | 0.48 | 01-AUG-07:19 | 1210.43 | 13.50 | 0.00 | 355.33 | 782.78 | 17.01 | 0.00 | 324.50 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:00 | 1756.07 | 14.13 | 14.00 | 310.17 | 1024.25 | 16.90 | 0.17 | 283.00 |
October | 296.17 | 0.50 | 0.48 | 01-OCT-09:39 | 3933.92 | 23.17 | 141.67 | 304.67 | 1262.66 | 17.15 | 14.00 | 279.50 |
November | 300.00 | 0.51 | 0.48 | 01-NOV-06:49 | 7674.62 | 36.91 | 294.67 | 279.67 | 1632.98 | 22.18 | 92.67 | 270.83 |
December | 297.00 | 0.50 | 0.48 | 01-DEC-07:19 | 7811.72 | 38.00 | 293.00 | 283.17 | 2283.59 | 25.99 | 143.00 | 273.00 |
Annual Sum or Average | 4065.67 | 0.51 | 3361.47 | 21.03 | 1314.33 | 3831.83 | 1129.62 | 18.71 | 411.33 | 3531.17 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 1066.75 | 13.36 | 0.00 | 274.67 | 661.74 | 16.84 | 0.00 | 255.17 | |
Maximum of Months | 408.67 | 0.52 | 0.48 | 7936.18 | 38.00 | 294.67 | 369.00 | 2283.59 | 25.99 | 143.00 | 336.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.52 | 0.48 | 01-JAN-07:19 | 1781.32 | 21.05 | 85.00 | 266.50 | 931.40 | 21.55 | 55.00 | 235.17 |
February | 279.67 | 0.51 | 0.48 | 01-FEB-07:10 | 1916.75 | 19.68 | 70.83 | 269.00 | 1045.65 | 21.79 | 54.50 | 230.33 |
March | 338.17 | 0.52 | 0.48 | 01-MAR-06:49 | 2373.04 | 20.99 | 106.50 | 318.67 | 1321.86 | 21.84 | 77.67 | 284.50 |
April | 358.33 | 0.51 | 0.48 | 01-APR-05:00 | 2403.11 | 19.97 | 93.67 | 340.00 | 1310.78 | 20.99 | 65.17 | 311.33 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-06:10 | 2307.29 | 19.32 | 99.33 | 378.83 | 1296.36 | 20.62 | 70.17 | 338.83 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-06:10 | 2305.76 | 18.48 | 88.83 | 370.17 | 1260.38 | 19.82 | 60.67 | 334.17 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-05:30 | 2534.54 | 18.99 | 99.67 | 379.17 | 1379.56 | 20.12 | 68.67 | 349.00 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-06:49 | 2545.96 | 19.83 | 103.33 | 363.50 | 1343.67 | 20.68 | 69.67 | 334.17 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-06:40 | 2668.84 | 20.45 | 98.83 | 313.83 | 1049.44 | 19.69 | 43.67 | 282.50 |
October | 296.17 | 0.53 | 0.48 | 01-OCT-09:39 | 2414.35 | 20.33 | 88.83 | 287.33 | 1025.23 | 19.67 | 42.50 | 247.50 |
November | 300.00 | 0.53 | 0.48 | 01-NOV-06:40 | 2020.44 | 21.35 | 95.17 | 265.67 | 1120.63 | 22.13 | 68.33 | 238.67 |
December | 297.00 | 0.53 | 0.48 | 01-DEC-07:10 | 1755.18 | 20.71 | 86.17 | 267.33 | 952.16 | 22.12 | 64.33 | 233.17 |
Annual Sum or Average | 4065.67 | 0.52 | 2277.57 | 20.02 | 1116.17 | 3820.00 | 1187.88 | 20.86 | 740.33 | 3419.33 | ||
Minimum of Months | 279.67 | 0.51 | 0.48 | 1755.18 | 18.48 | 70.83 | 265.67 | 931.40 | 19.67 | 42.50 | 230.33 | |
Maximum of Months | 408.67 | 0.53 | 0.48 | 2668.84 | 21.35 | 106.50 | 379.17 | 1379.56 | 22.13 | 77.67 | 349.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.56 | 0.48 | 01-JAN-08:00 | 565.18 | 11.17 | 0.00 | 239.00 | 382.30 | 14.99 | 0.00 | 180.33 |
February | 279.67 | 0.54 | 0.48 | 01-FEB-08:50 | 673.75 | 12.13 | 0.00 | 250.33 | 431.72 | 15.69 | 0.00 | 191.83 |
March | 338.17 | 0.54 | 0.48 | 01-MAR-08:20 | 788.90 | 12.59 | 0.00 | 306.83 | 492.13 | 15.98 | 0.00 | 260.50 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:10 | 884.31 | 13.78 | 0.00 | 336.50 | 585.15 | 17.34 | 0.00 | 304.50 |
May | 393.83 | 0.50 | 0.48 | 01-MAY-06:40 | 1093.80 | 14.10 | 0.00 | 383.17 | 663.22 | 17.67 | 0.00 | 356.00 |
June | 381.00 | 0.50 | 0.48 | 01-JUN-06:40 | 1157.09 | 16.30 | 42.50 | 376.00 | 715.64 | 19.54 | 40.83 | 347.67 |
July | 408.67 | 0.50 | 0.48 | 01-JUL-05:49 | 1090.47 | 16.39 | 45.17 | 385.50 | 668.72 | 17.86 | 0.00 | 363.33 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:19 | 907.52 | 13.90 | 0.00 | 366.33 | 602.58 | 17.49 | 0.00 | 342.33 |
September | 328.83 | 0.52 | 0.48 | 01-SEP-06:00 | 789.51 | 13.10 | 0.00 | 305.67 | 526.28 | 16.65 | 0.00 | 266.17 |
October | 296.17 | 0.55 | 0.48 | 01-OCT-09:39 | 604.71 | 11.57 | 0.00 | 266.17 | 412.17 | 15.27 | 0.00 | 201.17 |
November | 300.00 | 0.56 | 0.48 | 01-NOV-07:49 | 574.36 | 11.04 | 0.00 | 243.17 | 385.05 | 14.65 | 0.00 | 186.17 |
December | 297.00 | 0.57 | 0.48 | 01-DEC-08:39 | 514.55 | 10.51 | 0.00 | 231.50 | 354.37 | 14.31 | 0.00 | 161.00 |
Annual Sum or Average | 4065.67 | 0.53 | 829.76 | 13.26 | 87.67 | 3690.17 | 533.11 | 16.62 | 40.83 | 3161.00 | ||
Minimum of Months | 279.67 | 0.50 | 0.48 | 514.55 | 10.51 | 0.00 | 231.50 | 354.37 | 14.31 | 0.00 | 161.00 | |
Maximum of Months | 408.67 | 0.57 | 0.48 | 1157.09 | 16.39 | 45.17 | 385.50 | 715.64 | 19.54 | 40.83 | 363.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 293.33 | 0.53 | 0.48 | 01-JAN-08:00 | 2297.54 | 22.14 | 105.33 | 255.17 | 896.49 | 20.70 | 45.33 | 221.83 |
February | 279.67 | 0.52 | 0.48 | 01-FEB-08:50 | 2125.45 | 21.16 | 85.17 | 258.00 | 1162.69 | 21.97 | 60.00 | 223.17 |
March | 338.17 | 0.53 | 0.48 | 01-MAR-08:20 | 2374.67 | 20.50 | 100.83 | 311.50 | 1303.25 | 21.32 | 71.50 | 275.83 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:40 | 3241.17 | 18.72 | 82.33 | 333.50 | 1273.16 | 16.74 | 0.00 | 304.50 |
May | 393.83 | 0.51 | 0.48 | 01-MAY-07:19 | 3035.44 | 16.15 | 52.50 | 370.00 | 1279.67 | 16.87 | 0.00 | 337.17 |
June | 381.00 | 0.51 | 0.48 | 01-JUN-07:10 | 2591.47 | 13.18 | 0.00 | 365.00 | 1442.09 | 16.78 | 0.00 | 331.00 |
July | 408.67 | 0.51 | 0.48 | 01-JUL-06:49 | 2727.38 | 13.33 | 5.67 | 373.17 | 1491.78 | 16.70 | 0.00 | 348.83 |
August | 390.67 | 0.51 | 0.48 | 01-AUG-07:49 | 3350.45 | 18.38 | 88.17 | 357.83 | 1412.74 | 16.94 | 7.00 | 331.17 |
September | 328.83 | 0.51 | 0.48 | 01-SEP-07:30 | 3007.92 | 21.42 | 104.83 | 307.67 | 1585.46 | 21.99 | 73.67 | 277.83 |
October | 296.17 | 0.52 | 0.48 | 01-OCT-09:39 | 2863.39 | 21.88 | 107.83 | 289.00 | 1177.79 | 21.22 | 58.50 | 251.67 |
November | 300.00 | 0.54 | 0.48 | 01-NOV-07:00 | 2248.07 | 21.97 | 104.33 | 258.50 | 1251.86 | 22.50 | 75.00 | 225.67 |
December | 297.00 | 0.55 | 0.48 | 01-DEC-08:39 | 2041.50 | 21.99 | 104.67 | 251.00 | 1150.45 | 22.54 | 74.67 | 212.17 |
Annual Sum or Average | 4065.67 | 0.52 | 2695.01 | 18.87 | 941.67 | 3730.33 | 1300.51 | 19.40 | 465.67 | 3340.83 | ||
Minimum of Months | 279.67 | 0.51 | 0.48 | 2041.50 | 13.18 | 0.00 | 251.00 | 896.49 | 16.70 | 0.00 | 212.17 | |
Maximum of Months | 408.67 | 0.55 | 0.48 | 3350.45 | 22.14 | 107.83 | 373.17 | 1585.46 | 22.54 | 75.00 | 348.83 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 60338414.04 | 7368.09 | 28-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 14430755.77 | 3291.59 | 30-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 363449.24 | 605.75 | 12-DEC-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75132619.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 60338414.04 | 7368.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 44282.43 | 42.12 | 30-MAR-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 44282.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44282.43 | 42.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.206107E+10 | 103736.92 | 03-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 74116681.78 | 27645.45 | 09-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.981003E+09 | 64173.62 | 30-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17305729.53 | 20682.77 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.734628E+09 | 55323.78 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.386812E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.206107E+10 | 103736.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.158603E+10 | 118663.58 | 03-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.310425E+09 | 32219.76 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.703943E+09 | 119440.46 | 30-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 66761857.85 | 13881.96 | 01-APR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110578E+09 | 31054.10 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.671684E+09 | 72594.68 | 13-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.344942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.158603E+10 | 119440.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.738286E+09 | 122460.04 | 03-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.286317E+09 | 19912.41 | 06-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.427404E+09 | 122764.71 | 30-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 33091695.83 | 16550.15 | 01-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 44557395.84 | 14184.39 | 27-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.372960E+09 | 71774.57 | 13-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.190262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.738286E+09 | 122764.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.100413E+09 | 14160.25 | 03-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.270424E+09 | 113407.43 | 30-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 35369720.76 | 10717.79 | 01-APR-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 36430661.88 | 26836.87 | 13-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.442638E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.270424E+09 | 113407.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.715870E+09 | 52784.82 | 09-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 41843895.29 | 8788.29 | 28-FEB-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.271159E+09 | 30563.17 | 30-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 46011395.70 | 14681.59 | 01-APR-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.170991E+09 | 18571.93 | 13-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.124588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.715870E+09 | 52784.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.561506E+09 | 15626.62 | 09-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.102525E+09 | 6889.68 | 09-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.355276E+09 | 11153.12 | 30-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10247565.88 | 5985.40 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 371243.11 | 649.62 | 12-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17664676.49 | 4584.08 | 24-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.304945E+09 | 9672.66 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.561506E+09 | 15626.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.313668E+09 | 69172.18 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 34368801.41 | 8337.90 | 27-FEB-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12332468.37 | 4653.14 | 27-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 55825838.73 | 42836.51 | 26-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.416195E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.313668E+09 | 69172.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.980801E+09 | 13504.90 | 02-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.502876E+09 | 13438.83 | 13-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.566475E+09 | 13397.92 | 30-MAR-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 79528366.65 | 13344.02 | 01-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14079454.61 | 12568.76 | 15-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 53281415.16 | 13426.11 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.349637E+09 | 13430.60 | 08-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.679434E+09 | 13434.04 | 11-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.322611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.980801E+09 | 13504.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.453560E+09 | 14474.20 | 03-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.304470E+09 | 14475.43 | 13-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.297269E+09 | 14462.55 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 33268785.23 | 13177.99 | 01-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3271457.03 | 4249.91 | 13-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 160689.19 | 245.80 | 20-SEP-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 25527623.80 | 4594.80 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132379E+09 | 14466.61 | 18-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.299979E+09 | 14462.32 | 21-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.453560E+09 | 14475.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.318238E+09 | 18748.26 | 02-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.212147E+09 | 18815.11 | 13-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.341584E+09 | 18735.32 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 52497869.61 | 18365.55 | 01-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32681571.81 | 12419.99 | 15-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4849477.49 | 1039.02 | 12-OCT-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 58818657.32 | 15449.31 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167080E+09 | 18733.78 | 11-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.118790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.341584E+09 | 18815.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.454036E+09 | 14573.10 | 02-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.232436E+09 | 10870.35 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.254515E+09 | 14564.94 | 08-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 31604361.42 | 10446.53 | 01-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10594324.72 | 3315.77 | 13-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17823509.13 | 1219.28 | 30-OCT-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142123E+09 | 10805.97 | 06-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.294323E+09 | 14570.03 | 14-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.454036E+09 | 14573.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 1791346.03 | 4347.32 | 28-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 899145.68 | 1198.68 | 09-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2574209.55 | 2100.22 | 31-MAR-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 119777.86 | 393.11 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1517.25 | 0.91 | 09-MAY-06:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1263.27 | 0.67 | 01-JUN-06:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 34.84 | 0.41 | 02-AUG-06:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 310.82 | 0.83 | 16-SEP-06:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1220.30 | 0.99 | 31-OCT-06:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 402.64 | 0.72 | 08-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 693.89 | 1.30 | 11-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 5389922.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2574209.55 | 4347.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.213981E+11 | 0.213530E+11 | 90474.67 | 18-JAN-13:50 | 90474.67 | 0.19 |
February | 0.00 | 0.00 | 0.123034E+11 | 0.122294E+11 | 84776.59 | 01-FEB-12:00 | 84776.59 | 0.16 |
March | 0.00 | 0.00 | 0.147013E+11 | 0.143527E+11 | 95121.48 | 23-MAR-14:00 | 82743.92 | 0.19 |
April | 0.00 | 0.00 | 0.331267E+11 | 0.331052E+11 | 111768.25 | 26-APR-13:40 | 109542.10 | 0.38 |
May | 0.00 | 0.00 | 0.294531E+11 | 0.293668E+11 | 80790.61 | 03-MAY-13:00 | 80790.61 | 0.42 |
June | 0.00 | 0.00 | 0.534074E+11 | 0.489101E+11 | 124632.39 | 29-JUN-13:00 | 82795.56 | 0.58 |
July | 0.00 | 0.00 | 0.981487E+11 | 0.732660E+11 | 177961.07 | 31-JUL-15:40 | 103950.89 | 0.70 |
August | 0.00 | 0.00 | 0.120847E+12 | 0.848957E+11 | 181825.86 | 15-AUG-08:50 | 108211.02 | 0.76 |
September | 0.00 | 0.00 | 0.613979E+11 | 0.518148E+11 | 149807.55 | 22-SEP-12:30 | 79746.69 | 0.54 |
October | 0.00 | 0.00 | 0.799617E+11 | 0.664858E+11 | 182796.65 | 05-OCT-04:23 | 81595.62 | 0.40 |
November | 0.00 | 0.00 | 0.257540E+11 | 0.254026E+11 | 96833.13 | 28-NOV-14:00 | 96833.13 | 0.22 |
December | 0.00 | 0.00 | 0.299395E+11 | 0.298697E+11 | 103013.28 | 05-DEC-15:00 | 103013.28 | 0.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.580439E+12 | 0.491052E+12 | 0.39 | |||
Minimum of Months | 0.00 | 0.00 | 0.123034E+11 | 0.122294E+11 | 80790.61 | 79746.69 | 0.10 | |
Maximum of Months | 0.00 | 0.00 | 0.120847E+12 | 0.848957E+11 | 182796.65 | 109542.10 | 0.76 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.176099E+12 | 0.175652E+12 | 746007.77 | 18-JAN-14:00 | 746007.77 | 0.20 |
February | 0.00 | 0.00 | 0.943601E+11 | 0.936309E+11 | 692732.04 | 01-FEB-12:00 | 692732.04 | 0.17 |
March | 0.00 | 0.00 | 0.107077E+12 | 0.104285E+12 | 787243.17 | 23-MAR-14:10 | 664154.29 | 0.19 |
April | 0.00 | 0.00 | 0.233542E+12 | 0.233481E+12 | 856517.40 | 26-APR-14:00 | 856517.40 | 0.37 |
May | 0.00 | 0.00 | 0.237872E+12 | 0.237234E+12 | 701866.95 | 03-MAY-13:00 | 701866.95 | 0.43 |
June | 0.00 | 0.00 | 0.420069E+12 | 0.387005E+12 | 1040815.75 | 29-JUN-13:00 | 699654.56 | 0.57 |
July | 0.00 | 0.00 | 0.730200E+12 | 0.555316E+12 | 1406165.63 | 31-JUL-15:50 | 825292.16 | 0.61 |
August | 0.00 | 0.00 | 0.860043E+12 | 0.624142E+12 | 1468297.09 | 18-AUG-15:50 | 865622.92 | 0.63 |
September | 0.00 | 0.00 | 0.502277E+12 | 0.427033E+12 | 1265341.66 | 30-SEP-05:03 | 1265341.66 | 0.54 |
October | 0.00 | 0.00 | 0.594924E+12 | 0.509294E+12 | 1397193.30 | 03-OCT-13:30 | 825142.03 | 0.39 |
November | 0.00 | 0.00 | 0.185118E+12 | 0.182768E+12 | 724517.90 | 28-NOV-14:00 | 724517.90 | 0.23 |
December | 0.00 | 0.00 | 0.208837E+12 | 0.208305E+12 | 762543.81 | 05-DEC-15:00 | 762543.81 | 0.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.435042E+13 | 0.373815E+13 | 0.37 | |||
Minimum of Months | 0.00 | 0.00 | 0.943601E+11 | 0.936309E+11 | 692732.04 | 664154.29 | 0.09 | |
Maximum of Months | 0.00 | 0.00 | 0.860043E+12 | 0.624142E+12 | 1468297.09 | 1265341.66 | 0.63 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.138405E+11 | 0.138104E+11 | 72993.99 | 18-JAN-13:30 | 72993.99 | 0.18 |
February | 0.00 | 0.00 | 0.763960E+10 | 0.758010E+10 | 63597.30 | 01-FEB-12:00 | 63597.30 | 0.15 |
March | 0.00 | 0.00 | 0.942434E+10 | 0.928800E+10 | 77078.08 | 23-MAR-14:30 | 67746.13 | 0.17 |
April | 0.00 | 0.00 | 0.230100E+11 | 0.230066E+11 | 103633.54 | 26-APR-14:00 | 103633.54 | 0.35 |
May | 0.00 | 0.00 | 0.235276E+11 | 0.234708E+11 | 79113.28 | 03-MAY-13:10 | 79113.28 | 0.41 |
June | 0.00 | 0.00 | 0.435599E+11 | 0.399556E+11 | 116630.87 | 29-JUN-13:00 | 77864.73 | 0.55 |
July | 0.00 | 0.00 | 0.776991E+11 | 0.589154E+11 | 172725.02 | 31-JUL-15:20 | 105249.01 | 0.59 |
August | 0.00 | 0.00 | 0.908970E+11 | 0.654469E+11 | 172127.72 | 17-AUG-15:50 | 104370.69 | 0.61 |
September | 0.00 | 0.00 | 0.497141E+11 | 0.425237E+11 | 129358.40 | 29-SEP-13:40 | 129358.40 | 0.52 |
October | 0.00 | 0.00 | 0.576048E+11 | 0.492840E+11 | 149038.59 | 03-OCT-13:10 | 89738.50 | 0.38 |
November | 0.00 | 0.00 | 0.147777E+11 | 0.147112E+11 | 70594.33 | 28-NOV-14:00 | 70594.33 | 0.20 |
December | 0.00 | 0.00 | 0.170681E+11 | 0.170386E+11 | 77901.76 | 05-DEC-15:00 | 77901.76 | 0.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.428763E+12 | 0.365031E+12 | 0.35 | |||
Minimum of Months | 0.00 | 0.00 | 0.763960E+10 | 0.758010E+10 | 63597.30 | 63597.30 | 0.08 | |
Maximum of Months | 0.00 | 0.00 | 0.908970E+11 | 0.654469E+11 | 172725.02 | 129358.40 | 0.61 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.158652E+11 | 0.156654E+11 | 82782.98 | 17-JAN-12:00 | 76783.00 | 0.15 |
February | 0.00 | 0.00 | 0.945653E+10 | 0.910983E+10 | 68437.91 | 13-FEB-07:23 | 29486.50 | 0.16 |
March | 0.00 | 0.00 | 0.987206E+10 | 0.919962E+10 | 61958.24 | 23-MAR-15:00 | 40130.77 | 0.17 |
April | 0.00 | 0.00 | 0.209885E+11 | 0.196457E+11 | 72159.56 | 27-APR-06:25 | 34855.26 | 0.30 |
May | 0.00 | 0.00 | 0.209524E+11 | 0.198094E+11 | 75344.83 | 05-MAY-06:14 | 39563.26 | 0.32 |
June | 0.00 | 0.00 | 0.368951E+11 | 0.318642E+11 | 91736.83 | 30-JUN-06:25 | 41112.81 | 0.43 |
July | 0.00 | 0.00 | 0.549885E+11 | 0.436120E+11 | 116619.16 | 31-JUL-09:10 | 69303.63 | 0.42 |
August | 0.00 | 0.00 | 0.604998E+11 | 0.465892E+11 | 129727.63 | 15-AUG-08:45 | 74703.39 | 0.45 |
September | 0.00 | 0.00 | 0.360201E+11 | 0.276986E+11 | 102697.18 | 22-SEP-17:31 | 44733.93 | 0.36 |
October | 0.00 | 0.00 | 0.466468E+11 | 0.389110E+11 | 128793.90 | 05-OCT-13:00 | 71466.75 | 0.27 |
November | 0.00 | 0.00 | 0.180016E+11 | 0.176609E+11 | 74137.33 | 10-NOV-07:11 | 37724.40 | 0.18 |
December | 0.00 | 0.00 | 0.195428E+11 | 0.195109E+11 | 75954.19 | 04-DEC-10:00 | 75954.19 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.349729E+12 | 0.299277E+12 | 0.27 | |||
Minimum of Months | 0.00 | 0.00 | 0.945653E+10 | 0.910983E+10 | 61958.24 | 29486.50 | 0.06 | |
Maximum of Months | 0.00 | 0.00 | 0.604998E+11 | 0.465892E+11 | 129727.63 | 76783.00 | 0.45 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.804747E+10 | 0.798288E+10 | 105167.69 | 14-JAN-11:00 | 105167.69 | 0.00 |
February | 0.00 | 0.00 | 0.745058E+10 | 0.739092E+10 | 194709.22 | 01-FEB-12:00 | 194709.22 | 0.00 |
March | 0.00 | 0.00 | 0.397036E+11 | 0.318552E+11 | 261162.47 | 23-MAR-14:00 | 195246.14 | 0.00 |
April | 0.00 | 0.00 | 0.244216E+12 | 0.186577E+12 | 448321.12 | 26-APR-11:00 | 377827.07 | 0.00 |
May | 0.00 | 0.00 | 0.914900E+09 | 0.843756E+09 | 47967.85 | 04-MAY-12:00 | 41728.97 | 0.00 |
June | 0.00 | 0.00 | 0.659977E+11 | 0.473950E+11 | 245134.09 | 29-JUN-11:00 | 164078.84 | 0.00 |
July | 0.00 | 0.00 | 0.379876E+12 | 0.238645E+12 | 464778.80 | 31-JUL-14:00 | 318454.27 | 0.00 |
August | 0.00 | 0.00 | 0.855067E+12 | 0.485688E+12 | 494843.25 | 14-AUG-10:00 | 333030.17 | 0.00 |
September | 0.00 | 0.00 | 0.178629E+11 | 0.163410E+11 | 188304.60 | 21-SEP-13:30 | 133596.50 | 0.00 |
October | 0.00 | 0.00 | 0.120671E+12 | 0.100961E+12 | 314846.29 | 01-OCT-11:52 | 191104.17 | 0.00 |
November | 0.00 | 0.00 | 0.634804E+11 | 0.573454E+11 | 316273.51 | 19-NOV-12:53 | 316273.51 | 0.00 |
December | 0.00 | 0.00 | 0.177211E+12 | 0.167221E+12 | 382684.12 | 05-DEC-10:00 | 382684.12 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.198050E+13 | 0.134825E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.914900E+09 | 0.843756E+09 | 47967.85 | 41728.97 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.855067E+12 | 0.485688E+12 | 494843.25 | 382684.12 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.527390E+10 | 0.523187E+10 | 2542.05 | 18-JAN-16:10 | 2451.56 | 0.00 |
February | 0.00 | 0.00 | 0.946524E+10 | 0.940490E+10 | 4665.70 | 20-FEB-17:00 | 4648.06 | 0.00 |
March | 0.00 | 0.00 | 0.156439E+11 | 0.155503E+11 | 7570.85 | 31-MAR-24:00 | 7570.85 | 0.00 |
April | 0.00 | 0.00 | 0.203161E+11 | 0.201849E+11 | 8476.43 | 16-APR-17:25 | 8459.36 | 0.00 |
May | 0.00 | 0.00 | 0.568289E+10 | 0.558382E+10 | 3866.01 | 31-MAY-24:00 | 3848.42 | 0.00 |
June | 0.00 | 0.00 | 0.107242E+11 | 0.105312E+11 | 5897.13 | 30-JUN-24:00 | 5892.52 | 0.00 |
July | 0.00 | 0.00 | 0.163605E+11 | 0.160743E+11 | 7764.83 | 31-JUL-23:45 | 7764.83 | 0.00 |
August | 0.00 | 0.00 | 0.213891E+11 | 0.210622E+11 | 8602.95 | 17-AUG-16:00 | 8252.51 | 0.00 |
September | 0.00 | 0.00 | 0.582026E+10 | 0.563937E+10 | 4102.25 | 30-SEP-24:00 | 4102.25 | 0.00 |
October | 0.00 | 0.00 | 0.110662E+11 | 0.109405E+11 | 5871.04 | 31-OCT-24:00 | 5867.21 | 0.00 |
November | 0.00 | 0.00 | 0.153008E+11 | 0.152278E+11 | 6575.81 | 07-NOV-16:20 | 6376.78 | 0.00 |
December | 0.00 | 0.00 | 0.207642E+11 | 0.207317E+11 | 8521.51 | 25-DEC-16:20 | 8521.51 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.157807E+12 | 0.156163E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.527390E+10 | 0.523187E+10 | 2542.05 | 2451.56 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.213891E+11 | 0.210622E+11 | 8602.95 | 8521.51 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.402796E+11 | 0.398706E+11 | 23643.17 | 18-JAN-16:10 | 22761.81 | 0.00 |
February | 0.00 | 0.00 | 0.818042E+11 | 0.812063E+11 | 42734.12 | 01-FEB-16:50 | 40742.08 | 0.00 |
March | 0.00 | 0.00 | 0.140790E+12 | 0.139859E+12 | 68362.91 | 31-MAR-23:40 | 68362.91 | 0.00 |
April | 0.00 | 0.00 | 0.188759E+12 | 0.187455E+12 | 79517.00 | 26-APR-16:00 | 77556.86 | 0.00 |
May | 0.00 | 0.00 | 0.491199E+11 | 0.481481E+11 | 34947.09 | 31-MAY-23:40 | 34642.22 | 0.00 |
June | 0.00 | 0.00 | 0.986595E+11 | 0.967479E+11 | 55744.43 | 30-JUN-24:00 | 55693.76 | 0.00 |
July | 0.00 | 0.00 | 0.153833E+12 | 0.150992E+12 | 74113.04 | 31-JUL-23:53 | 74113.04 | 0.00 |
August | 0.00 | 0.00 | 0.202338E+12 | 0.199081E+12 | 81732.33 | 17-AUG-16:00 | 78241.64 | 0.00 |
September | 0.00 | 0.00 | 0.509982E+11 | 0.492207E+11 | 38009.10 | 30-SEP-24:00 | 38009.10 | 0.00 |
October | 0.00 | 0.00 | 0.100117E+12 | 0.988719E+11 | 54382.51 | 31-OCT-24:00 | 54337.23 | 0.00 |
November | 0.00 | 0.00 | 0.137972E+12 | 0.137248E+12 | 61973.85 | 10-NOV-16:20 | 59354.36 | 0.00 |
December | 0.00 | 0.00 | 0.188468E+12 | 0.188143E+12 | 80002.05 | 07-DEC-16:20 | 77594.88 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.143314E+13 | 0.141684E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.402796E+11 | 0.398706E+11 | 23643.17 | 22761.81 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.202338E+12 | 0.199081E+12 | 81732.33 | 78241.64 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.283815E+10 | 0.279826E+10 | 2386.70 | 18-JAN-16:10 | 2298.04 | 0.00 |
February | 0.00 | 0.00 | 0.724222E+10 | 0.718309E+10 | 4292.68 | 01-FEB-16:50 | 4093.79 | 0.00 |
March | 0.00 | 0.00 | 0.132252E+11 | 0.131325E+11 | 6493.16 | 31-MAR-23:20 | 6493.16 | 0.00 |
April | 0.00 | 0.00 | 0.184310E+11 | 0.183007E+11 | 8044.78 | 26-APR-16:00 | 7848.35 | 0.00 |
May | 0.00 | 0.00 | 0.444643E+10 | 0.434994E+10 | 3263.98 | 31-MAY-23:20 | 3217.77 | 0.00 |
June | 0.00 | 0.00 | 0.965986E+10 | 0.946861E+10 | 5464.84 | 30-JUN-23:40 | 5455.51 | 0.00 |
July | 0.00 | 0.00 | 0.152977E+11 | 0.150135E+11 | 7328.64 | 31-JUL-23:53 | 7328.64 | 0.00 |
August | 0.00 | 0.00 | 0.201252E+11 | 0.197997E+11 | 8269.57 | 17-AUG-16:00 | 7920.11 | 0.00 |
September | 0.00 | 0.00 | 0.479929E+10 | 0.462210E+10 | 3765.86 | 30-SEP-23:50 | 3765.86 | 0.00 |
October | 0.00 | 0.00 | 0.956942E+10 | 0.944522E+10 | 5240.28 | 31-OCT-23:30 | 5229.07 | 0.00 |
November | 0.00 | 0.00 | 0.129348E+11 | 0.128627E+11 | 6215.36 | 10-NOV-16:20 | 5953.33 | 0.00 |
December | 0.00 | 0.00 | 0.177401E+11 | 0.177079E+11 | 7997.84 | 07-DEC-16:20 | 7757.08 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.136309E+12 | 0.134684E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.283815E+10 | 0.279826E+10 | 2386.70 | 2298.04 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.201252E+11 | 0.197997E+11 | 8269.57 | 7920.11 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 3035.41 | 583876.19 | 09-JAN-06:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 862.19 | 127761.52 | 06-FEB-06:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 1666.42 | 620035.71 | 30-MAR-05:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 153.85 | 132535.16 | 01-APR-05:03 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 23.61 | 51188.23 | 15-MAY-05:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.55 | 01-JUN-06:25 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.33 | 02-AUG-06:19 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.06 | 221.35 | 20-SEP-05:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 37.28 | 31519.72 | 30-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 337.50 | 120714.23 | 27-NOV-06:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 1405.32 | 362472.00 | 13-DEC-06:03 |
Annual Sum or Average | 0.00 | 630.39 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 3035.41 | 620035.71 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 86953.82 | 1216101.83 | 18-JAN-14:30 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 53133.74 | 1241474.91 | 01-FEB-12:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 54864.13 | 1207843.42 | 23-MAR-14:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 123324.87 | 1226635.24 | 26-APR-12:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 118781.74 | 1097583.19 | 04-MAY-12:10 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 220462.56 | 1347769.33 | 29-JUN-13:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 369272.49 | 1785003.35 | 31-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 435811.56 | 1836233.24 | 18-AUG-15:50 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 258052.43 | 1409584.49 | 22-SEP-11:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 301956.74 | 2034694.66 | 30-OCT-13:43 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 97827.19 | 1170342.64 | 28-NOV-13:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 109920.86 | 1280295.63 | 05-DEC-10:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 187074.40 | 0.00 | ||||
Minimum of Months | 53133.74 | 1097583.19 | 0.00 | 0.00 | ||
Maximum of Months | 435811.56 | 2034694.66 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 86645.57 | 1780309.10 | 18-JAN-14:10 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 52194.32 | 1246258.37 | 01-FEB-12:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 54051.66 | 1311609.88 | 23-MAR-14:40 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 122120.50 | 1287813.72 | 12-APR-13:50 | 0.00 | 0.00 | 01-APR-00:10 |
May | 117543.87 | 1121760.91 | 03-MAY-13:30 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 218705.98 | 1345085.23 | 29-JUN-13:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 367297.33 | 2127098.91 | 29-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 433965.24 | 2311883.14 | 07-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 256798.56 | 2182400.46 | 30-SEP-05:03 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 304607.05 | 2489808.86 | 30-OCT-13:40 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 96850.87 | 1212886.29 | 28-NOV-13:50 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 108957.33 | 1449585.13 | 05-DEC-14:40 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 186194.05 | 0.00 | ||||
Minimum of Months | 52194.32 | 1121760.91 | 0.00 | 0.00 | ||
Maximum of Months | 433965.24 | 2489808.86 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 53859.69 | 655367.32 | 14-JAN-12:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 66601.86 | 852645.58 | 01-FEB-12:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 118957.42 | 844196.28 | 11-MAR-14:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 307922.61 | 1392569.65 | 26-APR-11:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 57767.48 | 439760.53 | 03-MAY-13:00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 167849.01 | 889854.22 | 29-JUN-11:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 453329.92 | 1446500.53 | 19-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 793436.95 | 1601847.66 | 14-AUG-11:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 128639.43 | 1312214.04 | 29-SEP-13:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 263210.89 | 1595423.89 | 16-OCT-11:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 148417.52 | 1179468.93 | 19-NOV-12:57 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 253422.65 | 1301191.89 | 19-DEC-13:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 236337.66 | 0.00 | ||||
Minimum of Months | 53859.69 | 439760.53 | 0.00 | 0.00 | ||
Maximum of Months | 793436.95 | 1601847.66 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 12564.79 | 44636.64 | 31-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 12655.77 | 44638.09 | 02-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 13307.34 | 44417.28 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 12208.91 | 43614.22 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 12302.43 | 42650.70 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12321.69 | 41560.08 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11166.96 | 40718.11 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 12214.87 | 40638.23 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 11582.52 | 41325.55 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11820.77 | 42413.94 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 12295.21 | 43470.43 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 12103.52 | 44259.66 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 12209.62 | ||||
Minimum of Months | 0.00 | 0.00 | 11166.96 | 40638.23 | ||
Maximum of Months | 0.00 | 0.00 | 13307.34 | 44638.09 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 97898.25 | 1999302.10 | 18-JAN-14:30 | 1441.86 | 111494.17 | 04-JAN-06:40 |
February | 56994.33 | 1501208.00 | 01-FEB-12:00 | 1708.13 | 103184.30 | 06-FEB-06:50 |
March | 63426.55 | 2132311.74 | 23-MAR-14:10 | 1535.01 | 88555.37 | 29-MAR-15:30 |
April | 146498.85 | 2061736.13 | 26-APR-12:40 | 816.32 | 63229.29 | 21-APR-15:10 |
May | 135973.73 | 1679469.11 | 04-MAY-12:10 | 790.88 | 78625.52 | 19-MAY-05:05 |
June | 286989.52 | 2539921.61 | 29-JUN-13:00 | 353.65 | 46584.40 | 02-JUN-06:10 |
July | 583812.42 | 3788341.18 | 31-JUL-16:00 | 265.42 | 35120.12 | 17-JUL-05:50 |
August | 712132.53 | 3882060.23 | 18-AUG-16:00 | 270.98 | 52384.84 | 22-AUG-05:40 |
September | 352627.06 | 3179993.69 | 22-SEP-11:30 | 301.82 | 48359.56 | 18-SEP-06:10 |
October | 418183.31 | 3499440.65 | 03-OCT-13:30 | 520.01 | 59219.91 | 28-OCT-07:50 |
November | 107914.71 | 1872514.46 | 28-NOV-14:00 | 1237.93 | 98870.55 | 22-NOV-20:10 |
December | 122499.63 | 2014220.28 | 05-DEC-14:10 | 1173.92 | 118211.58 | 26-DEC-07:12 |
Annual Sum or Average | 259091.68 | 863.18 | ||||
Minimum of Months | 56994.33 | 1501208.00 | 265.42 | 35120.12 | ||
Maximum of Months | 712132.53 | 3882060.23 | 1708.13 | 118211.58 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.633385E+10 | 0.40 | 12615.94 | 02-JAN-10:40 | 1.34 |
February | 0.614009E+10 | 0.41 | 12913.75 | 21-FEB-15:50 | 1.35 |
March | 0.798583E+10 | 0.46 | 13600.38 | 23-MAR-15:10 | 1.39 |
April | 0.982455E+10 | 0.53 | 15077.10 | 26-APR-14:00 | 1.48 |
May | 0.740035E+10 | 0.44 | 12964.98 | 03-MAY-05:02 | 1.35 |
June | 0.896527E+10 | 0.50 | 16218.44 | 26-JUN-04:12 | 1.56 |
July | 0.108892E+11 | 0.57 | 15426.12 | 03-JUL-05:03 | 1.51 |
August | 0.130899E+11 | 0.66 | 19103.13 | 21-AUG-05:02 | 1.73 |
September | 0.855615E+10 | 0.48 | 19571.83 | 22-SEP-05:02 | 1.75 |
October | 0.943361E+10 | 0.50 | 20200.92 | 02-OCT-04:12 | 1.79 |
November | 0.804062E+10 | 0.46 | 15172.55 | 13-NOV-09:10 | 1.49 |
December | 0.796971E+10 | 0.45 | 15267.48 | 18-DEC-16:00 | 1.52 |
Annual Sum or Average | 0.104629E+12 | 0.49 | |||
Minimum of Months | 0.614009E+10 | 0.40 | 12615.94 | 1.34 | |
Maximum of Months | 0.130899E+11 | 0.66 | 20200.92 | 1.79 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.420082E+11 | 0.33 | 102758.35 | 03-JAN-06:02 | 1.23 |
February | 0.390439E+11 | 0.34 | 84717.90 | 01-FEB-06:03 | 1.10 |
March | 0.458478E+11 | 0.36 | 108616.71 | 30-MAR-05:03 | 1.28 |
April | 0.537618E+11 | 0.39 | 98560.72 | 26-APR-14:40 | 1.19 |
May | 0.533052E+11 | 0.39 | 91224.78 | 01-MAY-05:03 | 1.14 |
June | 0.610063E+11 | 0.42 | 103114.19 | 19-JUN-05:03 | 1.23 |
July | 0.675805E+11 | 0.44 | 110171.82 | 28-JUL-05:02 | 1.28 |
August | 0.775924E+11 | 0.48 | 116220.93 | 16-AUG-05:02 | 1.32 |
September | 0.617039E+11 | 0.42 | 187911.56 | 30-SEP-05:03 | 1.80 |
October | 0.575615E+11 | 0.40 | 187911.56 | 02-OCT-05:02 | 1.79 |
November | 0.461000E+11 | 0.36 | 84717.90 | 01-NOV-04:12 | 1.09 |
December | 0.429134E+11 | 0.34 | 84806.14 | 13-DEC-06:03 | 1.10 |
Annual Sum or Average | 0.648425E+12 | 0.39 | |||
Minimum of Months | 0.390439E+11 | 0.33 | 84717.90 | 1.09 | |
Maximum of Months | 0.775924E+11 | 0.48 | 187911.56 | 1.80 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.343863E+10 | 0.31 | 7089.14 | 18-JAN-15:40 | 0.95 |
February | 0.320769E+10 | 0.31 | 7351.78 | 03-FEB-15:30 | 0.98 |
March | 0.382294E+10 | 0.33 | 10228.46 | 23-MAR-15:10 | 1.18 |
April | 0.498240E+10 | 0.37 | 11796.77 | 26-APR-14:30 | 1.30 |
May | 0.496011E+10 | 0.36 | 10643.77 | 03-MAY-15:20 | 1.22 |
June | 0.609810E+10 | 0.41 | 11268.33 | 30-JUN-16:00 | 1.26 |
July | 0.708987E+10 | 0.43 | 12972.98 | 31-JUL-14:50 | 1.37 |
August | 0.799986E+10 | 0.46 | 13110.41 | 17-AUG-15:20 | 1.38 |
September | 0.582805E+10 | 0.39 | 14704.36 | 30-SEP-05:03 | 1.49 |
October | 0.519665E+10 | 0.37 | 17509.34 | 02-OCT-05:02 | 1.66 |
November | 0.366269E+10 | 0.32 | 7647.97 | 10-NOV-15:10 | 0.99 |
December | 0.344454E+10 | 0.31 | 7459.01 | 05-DEC-15:50 | 0.99 |
Annual Sum or Average | 0.597315E+11 | 0.36 | |||
Minimum of Months | 0.320769E+10 | 0.31 | 7089.14 | 0.95 | |
Maximum of Months | 0.799986E+10 | 0.46 | 17509.34 | 1.66 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.122753E+11 | 0.74 | 11996.08 | 02-JAN-07:10 | 1.77 |
February | 0.105120E+11 | 0.71 | 11996.08 | 01-FEB-07:10 | 1.81 |
March | 0.122685E+11 | 0.75 | 11996.08 | 01-MAR-07:05 | 1.81 |
April | 0.119145E+11 | 0.74 | 11996.08 | 01-APR-06:05 | 1.82 |
May | 0.128304E+11 | 0.77 | 11996.08 | 01-MAY-06:10 | 1.80 |
June | 0.117036E+11 | 0.74 | 11996.08 | 01-JUN-06:10 | 1.80 |
July | 0.118739E+11 | 0.70 | 11996.08 | 03-JUL-06:10 | 1.78 |
August | 0.135425E+11 | 0.80 | 11996.08 | 01-AUG-06:10 | 1.79 |
September | 0.979129E+10 | 0.62 | 11996.08 | 01-SEP-06:10 | 1.79 |
October | 0.115421E+11 | 0.68 | 11996.08 | 02-OCT-06:10 | 1.76 |
November | 0.129817E+11 | 0.79 | 11996.08 | 01-NOV-06:10 | 1.80 |
December | 0.138863E+11 | 0.81 | 11996.08 | 01-DEC-07:10 | 1.81 |
Annual Sum or Average | 0.145122E+12 | 0.74 | |||
Minimum of Months | 0.979129E+10 | 0.62 | 11996.08 | 1.76 | |
Maximum of Months | 0.138863E+11 | 0.81 | 11996.08 | 1.82 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.110059E+12 | 1.37 | 41091.44 | 01-JAN-00:10 | 1.37 |
February | 0.994084E+11 | 1.37 | 41091.44 | 01-FEB-00:10 | 1.37 |
March | 0.110059E+12 | 1.37 | 41091.44 | 01-MAR-00:10 | 1.37 |
April | 0.106509E+12 | 1.37 | 41091.44 | 01-APR-00:10 | 1.37 |
May | 0.110059E+12 | 1.37 | 41091.44 | 01-MAY-00:05 | 1.36 |
June | 0.106509E+12 | 1.36 | 41091.44 | 01-JUN-00:10 | 1.37 |
July | 0.110059E+12 | 1.36 | 41091.44 | 01-JUL-00:10 | 1.36 |
August | 0.110059E+12 | 1.36 | 41091.44 | 01-AUG-00:07 | 1.36 |
September | 0.106509E+12 | 1.36 | 41091.44 | 01-SEP-00:10 | 1.36 |
October | 0.110059E+12 | 1.37 | 41091.44 | 01-OCT-00:10 | 1.36 |
November | 0.106509E+12 | 1.37 | 41091.44 | 01-NOV-00:10 | 1.37 |
December | 0.110059E+12 | 1.38 | 41091.44 | 01-DEC-00:10 | 1.38 |
Annual Sum or Average | 0.129586E+13 | 1.37 | |||
Minimum of Months | 0.994084E+11 | 1.36 | 41091.44 | 1.36 | |
Maximum of Months | 0.110059E+12 | 1.38 | 41091.44 | 1.38 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.145329E+10 | 0.93 | 542.60 | 01-JAN-00:10 | 0.93 |
February | 0.131265E+10 | 0.93 | 542.60 | 01-FEB-00:10 | 0.93 |
March | 0.145329E+10 | 0.93 | 542.60 | 01-MAR-00:10 | 0.93 |
April | 0.140641E+10 | 0.93 | 542.60 | 01-APR-00:10 | 0.93 |
May | 0.145329E+10 | 0.93 | 542.60 | 01-MAY-00:05 | 0.93 |
June | 0.140641E+10 | 0.93 | 542.60 | 01-JUN-00:10 | 0.93 |
July | 0.145329E+10 | 0.93 | 542.60 | 01-JUL-00:10 | 0.93 |
August | 0.145329E+10 | 0.93 | 542.60 | 01-AUG-00:03 | 0.93 |
September | 0.140641E+10 | 0.93 | 542.60 | 01-SEP-00:10 | 0.93 |
October | 0.145329E+10 | 0.93 | 542.60 | 01-OCT-00:10 | 0.93 |
November | 0.140641E+10 | 0.93 | 542.60 | 01-NOV-00:10 | 0.93 |
December | 0.145329E+10 | 0.93 | 542.60 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.171113E+11 | 0.93 | |||
Minimum of Months | 0.131265E+10 | 0.93 | 542.60 | 0.93 | |
Maximum of Months | 0.145329E+10 | 0.93 | 542.60 | 0.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.138718E+11 | 0.93 | 5179.12 | 01-JAN-00:10 | 0.93 |
February | 0.125293E+11 | 0.93 | 5179.12 | 01-FEB-00:20 | 0.93 |
March | 0.138718E+11 | 0.93 | 5179.12 | 01-MAR-00:10 | 0.93 |
April | 0.134243E+11 | 0.93 | 5179.12 | 01-APR-00:20 | 0.93 |
May | 0.138718E+11 | 0.93 | 5179.12 | 01-MAY-00:05 | 0.93 |
June | 0.134243E+11 | 0.93 | 5179.12 | 01-JUN-00:10 | 0.93 |
July | 0.138718E+11 | 0.93 | 5179.12 | 01-JUL-00:10 | 0.93 |
August | 0.138718E+11 | 0.93 | 5179.12 | 01-AUG-00:03 | 0.93 |
September | 0.134243E+11 | 0.93 | 5179.12 | 01-SEP-00:10 | 0.93 |
October | 0.138718E+11 | 0.93 | 5179.12 | 01-OCT-00:20 | 0.93 |
November | 0.134243E+11 | 0.93 | 5179.12 | 01-NOV-00:10 | 0.93 |
December | 0.138718E+11 | 0.93 | 5179.12 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.163329E+12 | 0.93 | |||
Minimum of Months | 0.125293E+11 | 0.93 | 5179.12 | 0.93 | |
Maximum of Months | 0.138718E+11 | 0.93 | 5179.12 | 0.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.140901E+10 | 0.93 | 526.06 | 01-JAN-00:10 | 0.93 |
February | 0.127266E+10 | 0.93 | 526.06 | 01-FEB-00:10 | 0.93 |
March | 0.140901E+10 | 0.93 | 526.06 | 01-MAR-00:10 | 0.93 |
April | 0.136356E+10 | 0.93 | 526.06 | 01-APR-00:10 | 0.93 |
May | 0.140901E+10 | 0.93 | 526.06 | 01-MAY-00:05 | 0.93 |
June | 0.136356E+10 | 0.93 | 526.06 | 01-JUN-00:10 | 0.93 |
July | 0.140901E+10 | 0.93 | 526.06 | 01-JUL-00:10 | 0.93 |
August | 0.140901E+10 | 0.93 | 526.06 | 01-AUG-00:03 | 0.93 |
September | 0.136356E+10 | 0.93 | 526.06 | 01-SEP-00:10 | 0.93 |
October | 0.140901E+10 | 0.93 | 526.06 | 01-OCT-00:20 | 0.93 |
November | 0.136356E+10 | 0.93 | 526.06 | 01-NOV-00:10 | 0.93 |
December | 0.140901E+10 | 0.93 | 526.06 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.165900E+11 | 0.93 | |||
Minimum of Months | 0.127266E+10 | 0.93 | 526.06 | 0.93 | |
Maximum of Months | 0.140901E+10 | 0.93 | 526.06 | 0.93 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 413394.30 | 372054.87 | 146.90 | 09-JAN-06:02 | 132.21 | 132.21 | 35.83 | 3.03 |
February | 63090.48 | 56781.43 | 6.97 | 06-FEB-06:03 | 6.27 | 6.27 | 27.71 | 0.56 |
March | 204724.07 | 184251.66 | 168.43 | 30-MAR-05:03 | 151.59 | 151.59 | 36.05 | 3.23 |
April | 12786.23 | 11507.61 | 6.85 | 01-APR-05:03 | 6.16 | 6.16 | 25.08 | 0.56 |
May | 1707.51 | 1536.76 | 1.73 | 15-MAY-05:03 | 1.56 | 1.56 | 22.78 | 0.21 |
June | 0.03 | 0.02 | 0.00 | 01-JUN-06:25 | 0.00 | 0.00 | 22.89 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 22.89 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 02-AUG-06:19 | 0.00 | 0.00 | 22.89 | 0.00 |
September | 3.63 | 3.27 | 0.01 | 20-SEP-05:40 | 0.00 | 0.00 | 22.89 | 0.00 |
October | 2549.06 | 2294.15 | 0.94 | 30-OCT-05:03 | 0.85 | 0.85 | 22.08 | 0.13 |
November | 26599.28 | 23939.35 | 6.56 | 27-NOV-06:03 | 5.90 | 5.90 | 28.62 | 0.54 |
December | 134277.11 | 120849.40 | 47.14 | 13-DEC-06:03 | 42.42 | 42.42 | 31.49 | 1.72 |
Annual Sum or Average | 859131.69 | 773218.52 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.08 | 0.00 | |
Maximum of Months | 413394.30 | 372054.87 | 168.43 | 151.59 | 151.59 | 36.05 | 3.23 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.180904E+09 | 0.162814E+09 | 6545.72 | 18-JAN-14:10 | 5891.15 | 5891.15 | 11.31 | 51.02 |
February | 69158957.95 | 62243062.16 | 1647.10 | 01-FEB-12:30 | 1482.39 | 1482.39 | 6.72 | 28.81 |
March | 79323156.21 | 71390840.59 | 2391.94 | 23-MAR-13:30 | 2152.75 | 2152.75 | 9.51 | 33.77 |
April | 0.209292E+09 | 0.188363E+09 | 2697.18 | 12-APR-13:50 | 2427.47 | 2427.47 | 9.79 | 35.52 |
May | 0.207650E+09 | 0.186885E+09 | 2752.33 | 03-MAY-13:00 | 2477.09 | 2477.09 | 7.83 | 35.82 |
June | 0.380683E+09 | 0.342615E+09 | 2633.16 | 30-JUN-05:03 | 2369.85 | 2369.85 | 7.32 | 35.17 |
July | 0.772235E+09 | 0.695012E+09 | 8634.45 | 28-JUL-05:02 | 7771.01 | 7771.01 | 9.08 | 56.95 |
August | 0.100028E+10 | 0.900249E+09 | 8707.94 | 07-AUG-05:03 | 7837.15 | 7837.15 | 9.58 | 57.14 |
September | 0.593126E+09 | 0.533814E+09 | 6844.80 | 22-SEP-05:02 | 6160.32 | 6160.32 | 8.77 | 51.95 |
October | 0.860580E+09 | 0.774522E+09 | 9855.49 | 18-OCT-11:50 | 8869.94 | 8869.94 | 11.11 | 60.00 |
November | 0.168261E+09 | 0.151435E+09 | 3088.06 | 08-NOV-13:20 | 2779.26 | 2779.26 | 7.75 | 37.58 |
December | 0.167746E+09 | 0.150972E+09 | 2352.43 | 05-DEC-14:40 | 2117.19 | 2117.19 | 8.45 | 33.54 |
Annual Sum or Average | 0.468924E+10 | 0.422031E+10 | ||||||
Minimum of Months | 69158957.95 | 62243062.16 | 1647.10 | 1482.39 | 1482.39 | 6.72 | 28.81 | |
Maximum of Months | 0.100028E+10 | 0.900249E+09 | 9855.49 | 8869.94 | 8869.94 | 11.31 | 60.00 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.310468E+10 | 0.279421E+10 | 3391.63 | 02-JAN-07:11 | 3052.47 | 3052.47 | 6.71 | 30.00 |
February | 0.260546E+10 | 0.234492E+10 | 3391.63 | 01-FEB-05:12 | 3052.47 | 3052.47 | 6.78 | 30.00 |
March | 0.262566E+10 | 0.236310E+10 | 3391.63 | 01-MAR-06:03 | 3052.47 | 3052.47 | 6.75 | 30.00 |
April | 0.393761E+10 | 0.354385E+10 | 3391.63 | 01-APR-05:03 | 3052.47 | 3052.47 | 6.72 | 30.00 |
May | 0.431832E+10 | 0.388649E+10 | 3391.63 | 01-MAY-04:12 | 3052.47 | 3052.47 | 6.77 | 30.00 |
June | 0.527427E+10 | 0.474684E+10 | 3391.63 | 01-JUN-05:02 | 3052.47 | 3052.47 | 6.94 | 30.00 |
July | 0.658129E+10 | 0.592316E+10 | 3391.63 | 01-JUL-04:12 | 3052.47 | 3052.47 | 9.08 | 30.00 |
August | 0.707049E+10 | 0.636344E+10 | 3391.63 | 01-AUG-01:03 | 3052.47 | 3052.47 | 6.87 | 30.00 |
September | 0.514521E+10 | 0.463069E+10 | 3391.63 | 01-SEP-00:33 | 3052.47 | 3052.47 | 6.76 | 30.00 |
October | 0.539322E+10 | 0.485390E+10 | 3391.63 | 01-OCT-05:53 | 3052.47 | 3052.47 | 8.24 | 30.00 |
November | 0.349177E+10 | 0.314260E+10 | 3391.63 | 01-NOV-04:12 | 3052.47 | 3052.47 | 7.15 | 30.00 |
December | 0.312790E+10 | 0.281511E+10 | 3391.63 | 01-DEC-07:11 | 3052.47 | 3052.47 | 6.84 | 30.00 |
Annual Sum or Average | 0.526759E+11 | 0.474083E+11 | ||||||
Minimum of Months | 0.260546E+10 | 0.234492E+10 | 3391.63 | 3052.47 | 3052.47 | 6.71 | 30.00 | |
Maximum of Months | 0.707049E+10 | 0.636344E+10 | 3391.63 | 3052.47 | 3052.47 | 9.08 | 30.00 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 18314817.91 | 16483336.12 | 3391.63 | 18-JAN-13:10 | 3052.47 | 3052.47 | 13.36 | 15.00 |
February | 6104939.30 | 5494445.37 | 3391.63 | 01-FEB-11:50 | 3052.47 | 3052.47 | 14.93 | 15.00 |
March | 30524696.52 | 27472226.87 | 3391.63 | 22-MAR-12:40 | 3052.47 | 3052.47 | 15.43 | 15.00 |
April | 71224291.88 | 64101862.69 | 3391.63 | 12-APR-13:20 | 3052.47 | 3052.47 | 15.50 | 15.00 |
May | 8139919.07 | 7325927.16 | 3391.63 | 03-MAY-13:40 | 3052.47 | 3052.47 | 15.34 | 15.00 |
June | 0.356121E+09 | 0.320509E+09 | 3391.63 | 21-JUN-12:50 | 3052.47 | 3052.47 | 15.64 | 15.00 |
July | 0.126983E+10 | 0.114284E+10 | 3391.63 | 12-JUL-12:10 | 3052.47 | 3052.47 | 14.66 | 15.00 |
August | 0.172363E+10 | 0.155127E+10 | 3391.63 | 02-AUG-09:30 | 3052.47 | 3052.47 | 15.67 | 15.00 |
September | 0.677648E+09 | 0.609883E+09 | 3391.63 | 05-SEP-12:40 | 3052.47 | 3052.47 | 15.61 | 15.00 |
October | 0.997954E+09 | 0.898159E+09 | 3391.63 | 01-OCT-13:12 | 3052.47 | 3052.47 | 15.33 | 15.00 |
November | 12209878.61 | 10988890.75 | 3391.63 | 28-NOV-13:20 | 3052.47 | 3052.47 | 15.30 | 15.00 |
December | 77329231.18 | 69596308.06 | 3391.63 | 05-DEC-09:40 | 3052.47 | 3052.47 | 14.80 | 15.00 |
Annual Sum or Average | 0.524903E+10 | 0.472412E+10 | ||||||
Minimum of Months | 6104939.30 | 5494445.37 | 3391.63 | 3052.47 | 3052.47 | 13.36 | 15.00 | |
Maximum of Months | 0.172363E+10 | 0.155127E+10 | 3391.63 | 3052.47 | 3052.47 | 15.67 | 15.00 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.100261E+11 | 0.902351E+10 | 3743.32 | 01-JAN-00:10 | 3368.99 | 3368.99 | 18.69 | 15.63 |
February | 0.905585E+10 | 0.815026E+10 | 3743.32 | 01-FEB-00:10 | 3368.99 | 3368.99 | 19.27 | 15.63 |
March | 0.100261E+11 | 0.902351E+10 | 3743.32 | 01-MAR-00:10 | 3368.99 | 3368.99 | 19.77 | 15.63 |
April | 0.970269E+10 | 0.873243E+10 | 3743.32 | 01-APR-00:10 | 3368.99 | 3368.99 | 20.29 | 15.63 |
May | 0.100261E+11 | 0.902351E+10 | 3743.32 | 01-MAY-00:05 | 3368.99 | 3368.99 | 18.94 | 15.63 |
June | 0.970269E+10 | 0.873243E+10 | 3743.32 | 01-JUN-00:10 | 3368.99 | 3368.99 | 19.35 | 15.63 |
July | 0.100261E+11 | 0.902351E+10 | 3743.32 | 01-JUL-00:10 | 3368.99 | 3368.99 | 19.90 | 15.63 |
August | 0.100261E+11 | 0.902351E+10 | 3743.32 | 01-AUG-00:03 | 3368.99 | 3368.99 | 29.96 | 15.63 |
September | 0.970269E+10 | 0.873243E+10 | 3743.32 | 01-SEP-00:10 | 3368.99 | 3368.99 | 18.94 | 15.63 |
October | 0.100261E+11 | 0.902351E+10 | 3743.32 | 01-OCT-00:10 | 3368.99 | 3368.99 | 19.91 | 15.63 |
November | 0.970269E+10 | 0.873243E+10 | 3743.32 | 01-NOV-00:10 | 3368.99 | 3368.99 | 19.91 | 15.63 |
December | 0.100261E+11 | 0.902351E+10 | 3743.32 | 01-DEC-00:10 | 3368.99 | 3368.99 | 20.41 | 15.63 |
Annual Sum or Average | 0.118049E+12 | 0.106245E+12 | ||||||
Minimum of Months | 0.905585E+10 | 0.815026E+10 | 3743.32 | 3368.99 | 3368.99 | 18.69 | 15.63 | |
Maximum of Months | 0.100261E+11 | 0.902351E+10 | 3743.32 | 3368.99 | 3368.99 | 29.96 | 15.63 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:10 | 16.86 | 16.86 | 57.22 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:03 | 16.86 | 16.86 | 57.38 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:03 | 16.86 | 16.86 | 57.39 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:03 | 16.86 | 16.86 | 57.44 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 57.65 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:02 | 16.86 | 16.86 | 57.62 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 57.62 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:02 | 16.86 | 16.86 | 57.69 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 57.56 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 57.37 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:02 | 16.86 | 16.86 | 57.57 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:03 | 16.86 | 16.86 | 57.46 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 57.22 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.69 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.120751E+11 | 0.108676E+11 | 26324.72 | 18-JAN-14:30 | 23692.24 | 23692.24 | 25.60 | 106.37 |
February | 0.100994E+11 | 0.908946E+10 | 26301.67 | 01-FEB-12:00 | 23671.50 | 23671.50 | 24.48 | 106.37 |
March | 0.102734E+11 | 0.924603E+10 | 26331.32 | 23-MAR-14:10 | 23698.18 | 23698.18 | 25.90 | 106.37 |
April | 0.155067E+11 | 0.139560E+11 | 26327.81 | 26-APR-12:40 | 23695.03 | 23695.03 | 25.74 | 106.37 |
May | 0.167424E+11 | 0.150681E+11 | 26309.24 | 04-MAY-12:10 | 23678.32 | 23678.32 | 24.88 | 106.37 |
June | 0.217003E+11 | 0.195303E+11 | 26351.56 | 29-JUN-13:00 | 23716.40 | 23716.40 | 26.81 | 106.37 |
July | 0.302481E+11 | 0.272233E+11 | 26409.84 | 31-JUL-16:00 | 23768.85 | 23768.85 | 29.62 | 106.37 |
August | 0.339504E+11 | 0.305554E+11 | 26409.84 | 18-AUG-15:50 | 23768.85 | 23768.85 | 29.67 | 106.37 |
September | 0.223657E+11 | 0.201291E+11 | 26383.41 | 22-SEP-11:30 | 23745.07 | 23745.07 | 28.25 | 106.37 |
October | 0.244196E+11 | 0.219776E+11 | 26399.33 | 03-OCT-13:30 | 23759.40 | 23759.40 | 28.97 | 106.37 |
November | 0.135652E+11 | 0.122087E+11 | 26318.43 | 28-NOV-14:00 | 23686.59 | 23686.59 | 25.31 | 106.37 |
December | 0.123095E+11 | 0.110785E+11 | 26325.46 | 05-DEC-14:10 | 23692.91 | 23692.91 | 25.63 | 106.37 |
Annual Sum or Average | 0.223256E+12 | 0.200930E+12 | ||||||
Minimum of Months | 0.100994E+11 | 0.908946E+10 | 26301.67 | 23671.50 | 23671.50 | 24.48 | 106.37 | |
Maximum of Months | 0.339504E+11 | 0.305554E+11 | 26409.84 | 23768.85 | 23768.85 | 29.67 | 106.37 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 82.00 | 82.00 | 3035.41 | 583876.19 | 09-JAN-06:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 25.19 | 25.19 | 862.19 | 127761.52 | 06-FEB-06:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 23.34 | 23.34 | 1666.42 | 620035.71 | 30-MAR-05:03 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.55 | 23.55 | 153.85 | 132535.16 | 01-APR-05:03 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 21.93 | 21.93 | 23.61 | 51188.23 | 15-MAY-05:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.89 | 22.89 | 0.00 | 0.55 | 01-JUN-06:25 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.89 | 22.89 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 22.89 | 22.89 | 0.00 | 0.33 | 02-AUG-06:19 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.89 | 22.89 | 0.06 | 221.35 | 20-SEP-05:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.89 | 22.89 | 37.28 | 31519.72 | 30-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.40 | 22.40 | 337.50 | 120714.23 | 27-NOV-06:03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 26.10 | 26.10 | 1405.32 | 362472.00 | 13-DEC-06:03 |
Annual Sum or Average | 0.00 | 630.39 | ||||||
Minimum of Months | 0.00 | 0.00 | 21.93 | 21.93 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 82.00 | 82.00 | 3035.41 | 620035.71 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 86953.82 | 1216101.83 | 18-JAN-14:30 | 11.54 | 6.70 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 53133.74 | 1241474.91 | 01-FEB-12:00 | 16.59 | 9.36 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 54864.13 | 1207843.42 | 23-MAR-14:50 | 11.51 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 123324.87 | 1226635.24 | 26-APR-12:10 | 11.58 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 118781.74 | 1097583.19 | 04-MAY-12:10 | 15.44 | 9.93 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 220462.56 | 1347769.33 | 29-JUN-13:00 | 12.06 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 369272.49 | 1785003.35 | 31-JUL-16:00 | 13.81 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 435811.56 | 1836233.24 | 18-AUG-15:50 | 14.01 | 6.70 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 258052.43 | 1409584.49 | 22-SEP-11:30 | 12.31 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 301956.74 | 2034694.66 | 30-OCT-13:43 | 14.80 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 97827.19 | 1170342.64 | 28-NOV-13:30 | 11.36 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 109920.86 | 1280295.63 | 05-DEC-10:00 | 16.90 | 9.20 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 187074.40 | 0.00 | ||||||
Minimum of Months | 53133.74 | 1097583.19 | 11.36 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 435811.56 | 2034694.66 | 16.90 | 9.93 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 86645.57 | 1780309.10 | 18-JAN-14:10 | 15.04 | 11.45 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 52194.32 | 1246258.37 | 01-FEB-12:00 | 17.96 | 9.95 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 54051.66 | 1311609.88 | 23-MAR-14:40 | 16.38 | 10.18 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 122120.50 | 1287813.72 | 12-APR-13:50 | 15.36 | 10.22 | 0.00 | 0.00 | 01-APR-00:10 |
May | 117543.87 | 1121760.91 | 03-MAY-13:30 | 15.10 | 7.18 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 218705.98 | 1345085.23 | 29-JUN-13:00 | 18.23 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 367297.33 | 2127098.91 | 29-JUL-05:03 | 15.65 | 10.91 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 433965.24 | 2311883.14 | 07-AUG-05:03 | 16.37 | 11.28 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 256798.56 | 2182400.46 | 30-SEP-05:03 | 18.85 | 10.34 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 304607.05 | 2489808.86 | 30-OCT-13:40 | 16.62 | 11.64 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 96850.87 | 1212886.29 | 28-NOV-13:50 | 17.65 | 9.14 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 108957.33 | 1449585.13 | 05-DEC-14:40 | 17.03 | 8.31 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 186194.05 | 0.00 | ||||||
Minimum of Months | 52194.32 | 1121760.91 | 15.04 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 433965.24 | 2489808.86 | 18.85 | 11.64 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 53859.69 | 655367.32 | 14-JAN-12:00 | 30.30 | 27.12 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 66601.86 | 852645.58 | 01-FEB-12:00 | 33.85 | 28.05 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 118957.42 | 844196.28 | 11-MAR-14:00 | 33.70 | 26.53 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 307922.61 | 1392569.65 | 26-APR-11:00 | 43.44 | 30.61 | 0.00 | 0.00 | 01-APR-00:10 |
May | 57767.48 | 439760.53 | 03-MAY-13:00 | 26.39 | 24.62 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 167849.01 | 889854.22 | 29-JUN-11:00 | 34.52 | 27.49 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 453329.92 | 1446500.53 | 19-JUL-14:00 | 44.39 | 31.60 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 793436.95 | 1601847.66 | 14-AUG-11:00 | 47.12 | 33.08 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 128639.43 | 1312214.04 | 29-SEP-13:00 | 42.03 | 37.59 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 263210.89 | 1595423.89 | 16-OCT-11:00 | 47.01 | 39.66 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 148417.52 | 1179468.93 | 19-NOV-12:57 | 39.68 | 30.34 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 253422.65 | 1301191.89 | 19-DEC-13:00 | 41.83 | 30.18 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 236337.66 | 0.00 | ||||||
Minimum of Months | 53859.69 | 439760.53 | 26.39 | 24.62 | 0.00 | 0.00 | ||
Maximum of Months | 793436.95 | 1601847.66 | 47.12 | 39.66 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 58.36 | 58.36 | 12564.79 | 44636.64 | 31-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.92 | 57.92 | 12655.77 | 44638.09 | 02-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.93 | 57.93 | 13307.34 | 44417.28 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.97 | 57.97 | 12208.91 | 43614.22 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 58.43 | 58.43 | 12302.43 | 42650.70 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 58.07 | 58.07 | 12321.69 | 41560.08 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.11 | 58.11 | 11166.96 | 40718.11 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 58.13 | 58.13 | 12214.87 | 40638.23 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 58.11 | 58.11 | 11582.52 | 41325.55 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 58.08 | 58.08 | 11820.77 | 42413.94 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 58.03 | 58.03 | 12295.21 | 43470.43 | 30-NOV-12:20 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.98 | 57.98 | 12103.52 | 44259.66 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 12209.62 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.92 | 57.92 | 11166.96 | 40638.23 | ||
Maximum of Months | 0.00 | 0.00 | 58.43 | 58.43 | 13307.34 | 44638.09 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 97898.25 | 1999302.10 | 18-JAN-14:30 | 25.60 | 21.10 | 1441.86 | 111494.17 | 04-JAN-06:40 |
February | 56994.33 | 1501208.00 | 01-FEB-12:00 | 24.48 | 22.73 | 1708.13 | 103184.30 | 06-FEB-06:50 |
March | 63426.55 | 2132311.74 | 23-MAR-14:10 | 25.90 | 22.13 | 1535.01 | 88555.37 | 29-MAR-15:30 |
April | 146498.85 | 2061736.13 | 26-APR-12:40 | 25.74 | 22.01 | 816.32 | 63229.29 | 21-APR-15:10 |
May | 135973.73 | 1679469.11 | 04-MAY-12:10 | 24.88 | 21.33 | 790.88 | 78625.52 | 19-MAY-05:05 |
June | 286989.52 | 2539921.61 | 29-JUN-13:00 | 26.81 | 23.37 | 353.65 | 46584.40 | 02-JUN-06:10 |
July | 583812.42 | 3788341.18 | 31-JUL-16:00 | 29.62 | 24.98 | 265.42 | 35120.12 | 17-JUL-05:50 |
August | 712132.53 | 3882060.23 | 18-AUG-16:00 | 29.83 | 25.09 | 270.98 | 52384.84 | 22-AUG-05:40 |
September | 352627.06 | 3179993.69 | 22-SEP-11:30 | 28.25 | 24.74 | 301.82 | 48359.56 | 18-SEP-06:10 |
October | 418183.31 | 3499440.65 | 03-OCT-13:30 | 28.97 | 24.50 | 520.01 | 59219.91 | 28-OCT-07:50 |
November | 107914.71 | 1872514.46 | 28-NOV-14:00 | 25.31 | 21.10 | 1237.93 | 98870.55 | 22-NOV-20:10 |
December | 122499.63 | 2014220.28 | 05-DEC-14:10 | 25.63 | 21.10 | 1173.92 | 118211.58 | 26-DEC-07:12 |
Annual Sum or Average | 259091.68 | 863.18 | ||||||
Minimum of Months | 56994.33 | 1501208.00 | 24.48 | 21.10 | 265.42 | 35120.12 | ||
Maximum of Months | 712132.53 | 3882060.23 | 29.83 | 25.09 | 1708.13 | 118211.58 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 60338414.04 | 0.00 | 0.213981E+11 | 0.633385E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.123034E+11 | 0.614009E+10 | 0.00 | 0.00 |
March | 14475038.19 | 0.00 | 0.147013E+11 | 0.798583E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.331267E+11 | 0.982455E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.294531E+11 | 0.740035E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.534074E+11 | 0.896527E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.981487E+11 | 0.108892E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.120847E+12 | 0.130899E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.613979E+11 | 0.855615E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.799617E+11 | 0.943361E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.257540E+11 | 0.804062E+10 | 0.00 | 0.00 |
December | 363449.24 | 0.00 | 0.299395E+11 | 0.796971E+10 | 0.00 | 0.00 |
Annual Sum or Average | 75176901.47 | 0.00 | 0.580439E+12 | 0.104629E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.123034E+11 | 0.614009E+10 | 0.00 | 0.00 |
Maximum of Months | 60338414.04 | 0.00 | 0.120847E+12 | 0.130899E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.520167E+10 | 0.00 | 0.176099E+12 | 0.420082E+11 | 0.00 | 0.00 |
February | 0.712702E+09 | 0.00 | 0.943601E+11 | 0.390439E+11 | 0.00 | 0.00 |
March | 0.265393E+10 | 0.00 | 0.107077E+12 | 0.458478E+11 | 0.00 | 0.00 |
April | 0.198540E+09 | 0.00 | 0.233542E+12 | 0.537618E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.237872E+12 | 0.533052E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.420069E+12 | 0.610063E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.730200E+12 | 0.675805E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.860043E+12 | 0.775924E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.502277E+12 | 0.617039E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.594924E+12 | 0.575615E+11 | 0.00 | 0.00 |
November | 0.155135E+09 | 0.00 | 0.185118E+12 | 0.461000E+11 | 0.00 | 0.00 |
December | 0.198669E+10 | 0.00 | 0.208837E+12 | 0.429134E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.109087E+11 | 0.00 | 0.435042E+13 | 0.648425E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.943601E+11 | 0.390439E+11 | 0.00 | 0.00 |
Maximum of Months | 0.520167E+10 | 0.00 | 0.860043E+12 | 0.775924E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.308181E+10 | 0.00 | 0.138405E+11 | 0.343863E+10 | 0.00 | 0.00 |
February | 0.138882E+10 | 0.00 | 0.763960E+10 | 0.320769E+10 | 0.00 | 0.00 |
March | 0.181512E+10 | 0.00 | 0.942434E+10 | 0.382294E+10 | 0.00 | 0.00 |
April | 0.207147E+09 | 0.00 | 0.230100E+11 | 0.498240E+10 | 0.00 | 0.00 |
May | 60626808.17 | 0.00 | 0.235276E+11 | 0.496011E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.435599E+11 | 0.609810E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.776991E+11 | 0.708987E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.908970E+11 | 0.799986E+10 | 0.00 | 0.00 |
September | 160689.19 | 0.00 | 0.497141E+11 | 0.582805E+10 | 0.00 | 0.00 |
October | 0.101853E+09 | 0.00 | 0.576048E+11 | 0.519665E+10 | 0.00 | 0.00 |
November | 0.712954E+09 | 0.00 | 0.147777E+11 | 0.366269E+10 | 0.00 | 0.00 |
December | 0.180159E+10 | 0.00 | 0.170681E+11 | 0.344454E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.917008E+10 | 0.00 | 0.428763E+12 | 0.597315E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.763960E+10 | 0.320769E+10 | 0.00 | 0.00 |
Maximum of Months | 0.308181E+10 | 0.00 | 0.908970E+11 | 0.799986E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 1791346.03 | 0.00 | 0.158652E+11 | 0.122753E+11 | 0.00 | 0.00 |
February | 899145.68 | 0.00 | 0.945653E+10 | 0.105120E+11 | 0.00 | 0.00 |
March | 2574209.55 | 0.00 | 0.987206E+10 | 0.122685E+11 | 0.00 | 0.00 |
April | 119777.86 | 0.00 | 0.209885E+11 | 0.119145E+11 | 0.00 | 0.00 |
May | 1517.25 | 0.00 | 0.209524E+11 | 0.128304E+11 | 0.00 | 0.00 |
June | 1263.27 | 0.00 | 0.368951E+11 | 0.117036E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.549885E+11 | 0.118739E+11 | 0.00 | 0.00 |
August | 34.84 | 0.00 | 0.604998E+11 | 0.135425E+11 | 0.00 | 0.00 |
September | 310.82 | 0.00 | 0.360201E+11 | 0.979129E+10 | 0.00 | 0.00 |
October | 1220.30 | 0.00 | 0.466468E+11 | 0.115421E+11 | 0.00 | 0.00 |
November | 402.64 | 0.00 | 0.180016E+11 | 0.129817E+11 | 0.00 | 0.00 |
December | 693.89 | 0.00 | 0.195428E+11 | 0.138863E+11 | 0.00 | 0.00 |
Annual Sum or Average | 5389922.11 | 0.00 | 0.349729E+12 | 0.145122E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.945653E+10 | 0.979129E+10 | 0.00 | 0.00 |
Maximum of Months | 2574209.55 | 0.00 | 0.604998E+11 | 0.138863E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.136375E+11 | 0.180682E+12 | 0.00 | 24.19 |
February | 0.00 | 0.00 | 0.126962E+11 | 0.159996E+12 | 0.00 | 20.59 |
March | 0.00 | 0.00 | 0.545069E+11 | 0.171848E+12 | 0.00 | 17.48 |
April | 0.00 | 0.00 | 0.314990E+12 | 0.192760E+12 | 0.00 | 5.76 |
May | 0.00 | 0.00 | 0.427883E+10 | 0.118346E+12 | 0.00 | 1.83 |
June | 0.00 | 0.00 | 0.885968E+11 | 0.129433E+12 | 0.00 | 0.12 |
July | 0.00 | 0.00 | 0.487232E+12 | 0.217425E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.108295E+13 | 0.337939E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.274286E+11 | 0.120330E+12 | 0.00 | 1.58 |
October | 0.00 | 0.00 | 0.162731E+12 | 0.210542E+12 | 0.00 | 21.73 |
November | 0.00 | 0.00 | 0.861711E+11 | 0.211013E+12 | 0.00 | 30.43 |
December | 0.00 | 0.00 | 0.235407E+12 | 0.315861E+12 | 0.00 | 54.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.257062E+13 | 0.236617E+13 | 0.00 | 178.63 |
Minimum of Months | 0.00 | 0.00 | 0.427883E+10 | 0.118346E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.108295E+13 | 0.337939E+12 | 0.00 | 54.91 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.660061E+10 | 0.278000E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.116760E+11 | 0.352340E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.191455E+11 | 0.495486E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.248394E+11 | 0.592969E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.708060E+10 | 0.285100E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.132820E+11 | 0.396420E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.203406E+11 | 0.543337E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.266606E+11 | 0.672482E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.729772E+10 | 0.288387E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.138604E+11 | 0.424745E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.187864E+11 | 0.489202E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.254460E+11 | 0.613515E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.195016E+12 | 0.543198E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.660061E+10 | 0.278000E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.266606E+11 | 0.672482E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.506025E+11 | 0.241947E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.101095E+12 | 0.318202E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.172528E+12 | 0.456097E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.230958E+12 | 0.556231E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.613013E+11 | 0.260531E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.122289E+12 | 0.370535E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.191341E+12 | 0.513790E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.252279E+12 | 0.638128E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.640489E+11 | 0.264749E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.125570E+12 | 0.393245E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.169627E+12 | 0.450787E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.231294E+12 | 0.566978E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.177293E+13 | 0.503122E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.506025E+11 | 0.241947E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.252279E+12 | 0.638128E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.358485E+10 | 0.215572E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.897009E+10 | 0.300053E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.162324E+11 | 0.441621E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.225758E+11 | 0.550839E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.555973E+10 | 0.252231E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.119840E+11 | 0.368769E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.190412E+11 | 0.515257E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.251113E+11 | 0.639511E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.603818E+10 | 0.260245E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.120233E+11 | 0.386289E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.159298E+11 | 0.435851E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.218153E+11 | 0.548420E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.168866E+12 | 0.491466E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.358485E+10 | 0.215572E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.251113E+11 | 0.639511E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.633385E+10 | 0.213981E+11 | 60338414.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.614009E+10 | 0.123034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.798583E+10 | 0.147013E+11 | 14475038.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.982455E+10 | 0.331267E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.740035E+10 | 0.294531E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.896527E+10 | 0.534074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.108892E+11 | 0.981487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130899E+11 | 0.120847E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.855615E+10 | 0.613979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.943361E+10 | 0.799617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.804062E+10 | 0.257540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.796971E+10 | 0.299395E+11 | 363449.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104629E+12 | 0.580439E+12 | 75176901.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.614009E+10 | 0.123034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130899E+11 | 0.120847E+12 | 60338414.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.420082E+11 | 0.176099E+12 | 0.520167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.390439E+11 | 0.943601E+11 | 0.712702E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.458478E+11 | 0.107077E+12 | 0.265393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.537618E+11 | 0.233542E+12 | 0.198540E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.533052E+11 | 0.237872E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.610063E+11 | 0.420069E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.675805E+11 | 0.730200E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.775924E+11 | 0.860043E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.617039E+11 | 0.502277E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.575615E+11 | 0.594924E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.461000E+11 | 0.185118E+12 | 0.155135E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.429134E+11 | 0.208837E+12 | 0.198669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.648425E+12 | 0.435042E+13 | 0.109087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.390439E+11 | 0.943601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.775924E+11 | 0.860043E+12 | 0.520167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.343863E+10 | 0.138405E+11 | 0.308181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.320769E+10 | 0.763960E+10 | 0.138882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.382294E+10 | 0.942434E+10 | 0.181512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.498240E+10 | 0.230100E+11 | 0.207147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.496011E+10 | 0.235276E+11 | 60626808.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.609810E+10 | 0.435599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.708987E+10 | 0.776991E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.799986E+10 | 0.908970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.582805E+10 | 0.497141E+11 | 160689.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.519665E+10 | 0.576048E+11 | 0.101853E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.366269E+10 | 0.147777E+11 | 0.712954E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.344454E+10 | 0.170681E+11 | 0.180159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.597315E+11 | 0.428763E+12 | 0.917008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.320769E+10 | 0.763960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.799986E+10 | 0.908970E+11 | 0.308181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.122753E+11 | 0.158652E+11 | 1791346.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105120E+11 | 0.945653E+10 | 899145.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122685E+11 | 0.987206E+10 | 2574209.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.119145E+11 | 0.209885E+11 | 119777.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.128304E+11 | 0.209524E+11 | 1517.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.117036E+11 | 0.368951E+11 | 1263.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.118739E+11 | 0.549885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135425E+11 | 0.604998E+11 | 34.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.979129E+10 | 0.360201E+11 | 310.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115421E+11 | 0.466468E+11 | 1220.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129817E+11 | 0.180016E+11 | 402.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138863E+11 | 0.195428E+11 | 693.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145122E+12 | 0.349729E+12 | 5389922.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.979129E+10 | 0.945653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138863E+11 | 0.604998E+11 | 2574209.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.110059E+12 | 0.804747E+10 | 0.00 | 0.00 | 0.00 | 0.647410E+11 | 0.00 | 0.00 |
February | 0.994084E+11 | 0.745058E+10 | 0.00 | 0.00 | 0.00 | 0.550936E+11 | 0.00 | 0.00 |
March | 0.110059E+12 | 0.397036E+11 | 0.00 | 0.00 | 0.00 | 0.467746E+11 | 0.00 | 0.00 |
April | 0.106509E+12 | 0.244216E+12 | 0.00 | 0.00 | 0.00 | 0.154066E+11 | 0.00 | 0.00 |
May | 0.110059E+12 | 0.914900E+09 | 0.00 | 0.00 | 0.00 | 0.490116E+10 | 0.00 | 0.00 |
June | 0.106509E+12 | 0.659977E+11 | 0.00 | 0.00 | 0.00 | 0.323027E+09 | 0.00 | 0.00 |
July | 0.110059E+12 | 0.379876E+12 | 0.00 | 0.00 | 0.00 | 9420370.49 | 0.00 | 0.00 |
August | 0.110059E+12 | 0.855067E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.106509E+12 | 0.178629E+11 | 0.00 | 0.00 | 0.00 | 0.423664E+10 | 0.00 | 0.00 |
October | 0.110059E+12 | 0.120671E+12 | 0.00 | 0.00 | 0.00 | 0.581606E+11 | 0.00 | 0.00 |
November | 0.106509E+12 | 0.634804E+11 | 0.00 | 0.00 | 0.00 | 0.814468E+11 | 0.00 | 0.00 |
December | 0.110059E+12 | 0.177211E+12 | 0.00 | 0.00 | 0.00 | 0.146945E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.129586E+13 | 0.198050E+13 | 0.00 | 0.00 | 0.00 | 0.478038E+12 | 0.00 | 0.00 |
Minimum of Months | 0.994084E+11 | 0.914900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.110059E+12 | 0.855067E+12 | 0.00 | 0.00 | 0.00 | 0.146945E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.145329E+10 | 0.527390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131265E+10 | 0.946524E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145329E+10 | 0.156439E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140641E+10 | 0.203161E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145329E+10 | 0.568289E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140641E+10 | 0.107242E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.145329E+10 | 0.163605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145329E+10 | 0.213891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140641E+10 | 0.582026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.145329E+10 | 0.110662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140641E+10 | 0.153008E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145329E+10 | 0.207642E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171113E+11 | 0.157807E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.131265E+10 | 0.527390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145329E+10 | 0.213891E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.138718E+11 | 0.402796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125293E+11 | 0.818042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138718E+11 | 0.140790E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134243E+11 | 0.188759E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138718E+11 | 0.491199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134243E+11 | 0.986595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138718E+11 | 0.153833E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138718E+11 | 0.202338E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.134243E+11 | 0.509982E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138718E+11 | 0.100117E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134243E+11 | 0.137972E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138718E+11 | 0.188468E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163329E+12 | 0.143314E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125293E+11 | 0.402796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138718E+11 | 0.202338E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.140901E+10 | 0.283815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127266E+10 | 0.724222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140901E+10 | 0.132252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136356E+10 | 0.184310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140901E+10 | 0.444643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136356E+10 | 0.965986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140901E+10 | 0.152977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140901E+10 | 0.201252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136356E+10 | 0.479929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140901E+10 | 0.956942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136356E+10 | 0.129348E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140901E+10 | 0.177401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165900E+11 | 0.136309E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127266E+10 | 0.283815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140901E+10 | 0.201252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.633385E+10 | 60338414.04 | 0.213981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.614009E+10 | 0.00 | 0.123034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.798583E+10 | 14475038.19 | 0.147013E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.982455E+10 | 0.00 | 0.331267E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.740035E+10 | 0.00 | 0.294531E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.896527E+10 | 0.00 | 0.534074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.108892E+11 | 0.00 | 0.981487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130899E+11 | 0.00 | 0.120847E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.855615E+10 | 0.00 | 0.613979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.943361E+10 | 0.00 | 0.799617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.804062E+10 | 0.00 | 0.257540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.796971E+10 | 363449.24 | 0.299395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104629E+12 | 75176901.47 | 0.580439E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.614009E+10 | 0.00 | 0.123034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130899E+11 | 60338414.04 | 0.120847E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.420082E+11 | 0.520167E+10 | 0.176099E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.390439E+11 | 0.712702E+09 | 0.943601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.458478E+11 | 0.265393E+10 | 0.107077E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.537618E+11 | 0.198540E+09 | 0.233542E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.533052E+11 | 0.00 | 0.237872E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.610063E+11 | 0.00 | 0.420069E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.675805E+11 | 0.00 | 0.730200E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.775924E+11 | 0.00 | 0.860043E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.617039E+11 | 0.00 | 0.502277E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.575615E+11 | 0.00 | 0.594924E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.461000E+11 | 0.155135E+09 | 0.185118E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.429134E+11 | 0.198669E+10 | 0.208837E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.648425E+12 | 0.109087E+11 | 0.435042E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.390439E+11 | 0.00 | 0.943601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.775924E+11 | 0.520167E+10 | 0.860043E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.343863E+10 | 0.308181E+10 | 0.138405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.320769E+10 | 0.138882E+10 | 0.763960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.382294E+10 | 0.181512E+10 | 0.942434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.498240E+10 | 0.207147E+09 | 0.230100E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.496011E+10 | 60626808.17 | 0.235276E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.609810E+10 | 0.00 | 0.435599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.708987E+10 | 0.00 | 0.776991E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.799986E+10 | 0.00 | 0.908970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.582805E+10 | 160689.19 | 0.497141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.519665E+10 | 0.101853E+09 | 0.576048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.366269E+10 | 0.712954E+09 | 0.147777E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.344454E+10 | 0.180159E+10 | 0.170681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.597315E+11 | 0.917008E+10 | 0.428763E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.320769E+10 | 0.00 | 0.763960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.799986E+10 | 0.308181E+10 | 0.908970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.122753E+11 | 1791346.03 | 0.158652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.105120E+11 | 899145.68 | 0.945653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.122685E+11 | 2574209.55 | 0.987206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.119145E+11 | 119777.86 | 0.209885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.128304E+11 | 1517.25 | 0.209524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.117036E+11 | 1263.27 | 0.368951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.118739E+11 | 0.00 | 0.549885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135425E+11 | 34.84 | 0.604998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.979129E+10 | 310.82 | 0.360201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.115421E+11 | 1220.30 | 0.466468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129817E+11 | 402.64 | 0.180016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138863E+11 | 693.89 | 0.195428E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145122E+12 | 5389922.11 | 0.349729E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.979129E+10 | 0.00 | 0.945653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138863E+11 | 2574209.55 | 0.604998E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.110059E+12 | 0.00 | 0.136375E+11 | 0.00 | 0.559005E+10 | 0.00 | 0.00 | 0.00 | 0.650325E+11 | 0.00 | 0.00 | 0.00 |
February | 0.994084E+11 | 0.00 | 0.126962E+11 | 0.00 | 0.524560E+10 | 0.00 | 0.00 | 0.00 | 0.553416E+11 | 0.00 | 0.00 | 0.00 |
March | 0.110059E+12 | 0.00 | 0.545069E+11 | 0.00 | 0.148033E+11 | 0.00 | 0.00 | 0.00 | 0.469851E+11 | 0.00 | 0.00 | 0.00 |
April | 0.106509E+12 | 0.00 | 0.314990E+12 | 0.00 | 0.707746E+11 | 0.00 | 0.00 | 0.00 | 0.154759E+11 | 0.00 | 0.00 | 0.00 |
May | 0.110059E+12 | 0.00 | 0.427883E+10 | 0.00 | 0.336393E+10 | 0.00 | 0.00 | 0.00 | 0.492322E+10 | 0.00 | 0.00 | 0.00 |
June | 0.106509E+12 | 0.00 | 0.885968E+11 | 0.00 | 0.225991E+11 | 0.00 | 0.00 | 0.00 | 0.324481E+09 | 0.00 | 0.00 | 0.00 |
July | 0.110059E+12 | 0.00 | 0.487232E+12 | 0.00 | 0.107356E+12 | 0.00 | 0.00 | 0.00 | 9462775.40 | 0.00 | 0.00 | 0.00 |
August | 0.110059E+12 | 0.00 | 0.108295E+13 | 0.00 | 0.227880E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.106509E+12 | 0.00 | 0.274286E+11 | 0.00 | 0.956569E+10 | 0.00 | 0.00 | 0.00 | 0.425572E+10 | 0.00 | 0.00 | 0.00 |
October | 0.110059E+12 | 0.00 | 0.162731E+12 | 0.00 | 0.420600E+11 | 0.00 | 0.00 | 0.00 | 0.584224E+11 | 0.00 | 0.00 | 0.00 |
November | 0.106509E+12 | 0.00 | 0.861711E+11 | 0.00 | 0.226907E+11 | 0.00 | 0.00 | 0.00 | 0.818134E+11 | 0.00 | 0.00 | 0.00 |
December | 0.110059E+12 | 0.00 | 0.235407E+12 | 0.00 | 0.581959E+11 | 0.00 | 0.00 | 0.00 | 0.147606E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129586E+13 | 0.00 | 0.257062E+13 | 0.00 | 0.590126E+12 | 0.00 | 0.00 | 0.00 | 0.480190E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.994084E+11 | 0.00 | 0.427883E+10 | 0.00 | 0.336393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.110059E+12 | 0.00 | 0.108295E+13 | 0.00 | 0.227880E+12 | 0.00 | 0.00 | 0.00 | 0.147606E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.145329E+10 | 0.00 | 0.660061E+10 | 0.00 | 0.132671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.131265E+10 | 0.00 | 0.116760E+11 | 0.00 | 0.221075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145329E+10 | 0.00 | 0.191455E+11 | 0.00 | 0.350157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140641E+10 | 0.00 | 0.248394E+11 | 0.00 | 0.452328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145329E+10 | 0.00 | 0.708060E+10 | 0.00 | 0.139771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140641E+10 | 0.00 | 0.132820E+11 | 0.00 | 0.255779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.145329E+10 | 0.00 | 0.203406E+11 | 0.00 | 0.398007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145329E+10 | 0.00 | 0.266606E+11 | 0.00 | 0.527153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140641E+10 | 0.00 | 0.729772E+10 | 0.00 | 0.147746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.145329E+10 | 0.00 | 0.138604E+11 | 0.00 | 0.279416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140641E+10 | 0.00 | 0.187864E+11 | 0.00 | 0.348561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145329E+10 | 0.00 | 0.254460E+11 | 0.00 | 0.468186E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171113E+11 | 0.00 | 0.195016E+12 | 0.00 | 0.372085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.131265E+10 | 0.00 | 0.660061E+10 | 0.00 | 0.132671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145329E+10 | 0.00 | 0.266606E+11 | 0.00 | 0.527153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.138718E+11 | 0.00 | 0.506025E+11 | 0.00 | 0.103229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125293E+11 | 0.00 | 0.101095E+12 | 0.00 | 0.192909E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138718E+11 | 0.00 | 0.172528E+12 | 0.00 | 0.317379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134243E+11 | 0.00 | 0.230958E+12 | 0.00 | 0.421989E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138718E+11 | 0.00 | 0.613013E+11 | 0.00 | 0.121814E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134243E+11 | 0.00 | 0.122289E+12 | 0.00 | 0.236293E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138718E+11 | 0.00 | 0.191341E+12 | 0.00 | 0.375072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138718E+11 | 0.00 | 0.252279E+12 | 0.00 | 0.499410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.134243E+11 | 0.00 | 0.640489E+11 | 0.00 | 0.130507E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138718E+11 | 0.00 | 0.125570E+12 | 0.00 | 0.254528E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134243E+11 | 0.00 | 0.169627E+12 | 0.00 | 0.316544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138718E+11 | 0.00 | 0.231294E+12 | 0.00 | 0.428260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163329E+12 | 0.00 | 0.177293E+13 | 0.00 | 0.339793E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125293E+11 | 0.00 | 0.506025E+11 | 0.00 | 0.103229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138718E+11 | 0.00 | 0.252279E+12 | 0.00 | 0.499410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.140901E+10 | 0.00 | 0.358485E+10 | 0.00 | 0.746708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127266E+10 | 0.00 | 0.897009E+10 | 0.00 | 0.172787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140901E+10 | 0.00 | 0.162324E+11 | 0.00 | 0.300720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136356E+10 | 0.00 | 0.225758E+11 | 0.00 | 0.414483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140901E+10 | 0.00 | 0.555973E+10 | 0.00 | 0.111330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136356E+10 | 0.00 | 0.119840E+11 | 0.00 | 0.232413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140901E+10 | 0.00 | 0.190412E+11 | 0.00 | 0.374356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140901E+10 | 0.00 | 0.251113E+11 | 0.00 | 0.498610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136356E+10 | 0.00 | 0.603818E+10 | 0.00 | 0.123889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140901E+10 | 0.00 | 0.120233E+11 | 0.00 | 0.245388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136356E+10 | 0.00 | 0.159298E+11 | 0.00 | 0.299495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140901E+10 | 0.00 | 0.218153E+11 | 0.00 | 0.407519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165900E+11 | 0.00 | 0.168866E+12 | 0.00 | 0.325566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127266E+10 | 0.00 | 0.358485E+10 | 0.00 | 0.746708E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140901E+10 | 0.00 | 0.251113E+11 | 0.00 | 0.498610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 70300558.94 | 0.00 | 0.119762E+09 | 0.00 | 0.00 | 0.571176E+11 | 0.00 | 1.06 |
February | 0.00 | 5527092.00 | 0.00 | 97583577.61 | 0.00 | 0.00 | 0.530677E+11 | 0.00 | 1.03 |
March | 0.00 | 77344709.48 | 0.00 | 0.116015E+09 | 0.00 | 0.00 | 0.641425E+11 | 0.00 | 1.08 |
April | 0.00 | 95268579.75 | 0.00 | 0.109317E+09 | 0.00 | 0.00 | 0.487002E+11 | 0.00 | 1.14 |
May | 0.00 | 26526645.96 | 0.00 | 0.113818E+09 | 0.00 | 0.00 | 0.502461E+11 | 0.00 | 1.20 |
June | 0.00 | 0.103506E+10 | 0.00 | 0.110810E+09 | 0.00 | 0.00 | 0.353249E+11 | 0.00 | 1.24 |
July | 0.00 | 0.383243E+10 | 0.00 | 94847280.38 | 0.00 | 0.00 | 0.192768E+11 | 0.00 | 1.04 |
August | 0.00 | 0.454787E+10 | 0.00 | 0.103911E+09 | 0.00 | 0.00 | 0.219786E+11 | 0.00 | 1.21 |
September | 0.00 | 0.167869E+10 | 0.00 | 0.105274E+09 | 0.00 | 0.00 | 0.290602E+11 | 0.00 | 1.07 |
October | 0.00 | 0.322671E+10 | 0.00 | 0.118120E+09 | 0.00 | 0.00 | 0.301307E+11 | 0.00 | 1.01 |
November | 0.00 | 11035633.10 | 0.00 | 0.116912E+09 | 0.00 | 0.00 | 0.573885E+11 | 0.00 | 1.18 |
December | 0.00 | 798062.63 | 0.00 | 0.113983E+09 | 0.00 | 0.00 | 0.558504E+11 | 0.00 | 1.11 |
Annual Sum or Average | 0.00 | 0.146076E+11 | 0.00 | 0.132035E+10 | 0.00 | 0.00 | 0.522284E+12 | 0.00 | 1.11 |
Minimum of Months | 0.00 | 798062.63 | 0.00 | 94847280.38 | 0.00 | 0.00 | 0.192768E+11 | 0.00 | 1.01 |
Maximum of Months | 0.00 | 0.454787E+10 | 0.00 | 0.119762E+09 | 0.00 | 0.00 | 0.641425E+11 | 0.00 | 1.24 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.315582E+10 | 62624623.61 | 0.00 | 92186291.27 | 38510532.66 | 0.00 | 0.449118E+11 | 0.00 | 0.81 |
February | 0.307455E+10 | 17796415.98 | 0.00 | 84572015.80 | 0.00 | 0.00 | 0.465956E+11 | 0.00 | 0.87 |
March | 0.258886E+10 | 0.00 | 0.00 | 0.106727E+09 | 6804163.69 | 0.00 | 0.591321E+11 | 0.00 | 0.95 |
April | 0.538256E+10 | 11351517.38 | 0.00 | 0.105813E+09 | 43325240.69 | 0.00 | 0.481937E+11 | 0.00 | 1.10 |
May | 0.363726E+10 | 34042696.04 | 0.00 | 93208201.84 | 0.00 | 0.00 | 0.439791E+11 | 0.00 | 0.99 |
June | 0.261821E+10 | 0.425417E+09 | 0.00 | 98700015.38 | 0.00 | 0.00 | 0.361442E+11 | 0.00 | 1.12 |
July | 0.627646E+10 | 0.414664E+10 | 0.00 | 74365376.94 | 0.343846E+09 | 0.00 | 0.183977E+11 | 0.00 | 1.15 |
August | 0.626000E+10 | 0.580008E+10 | 0.00 | 75487090.23 | 0.383408E+09 | 0.00 | 0.171319E+11 | 0.00 | 1.28 |
September | 0.234524E+10 | 0.114490E+10 | 0.00 | 86593311.39 | 46005349.73 | 0.00 | 0.291365E+11 | 0.00 | 1.00 |
October | 0.216417E+10 | 0.344170E+10 | 0.00 | 87485128.57 | 0.298718E+09 | 0.00 | 0.284716E+11 | 0.00 | 0.99 |
November | 0.310087E+10 | 6295669.19 | 0.00 | 0.105100E+09 | 25870300.10 | 0.00 | 0.511721E+11 | 0.00 | 0.99 |
December | 0.396888E+10 | 3014361.90 | 0.00 | 0.109053E+09 | 0.00 | 0.00 | 0.487391E+11 | 0.00 | 0.92 |
Annual Sum or Average | 0.445729E+11 | 0.150939E+11 | 0.00 | 0.111929E+10 | 0.118649E+10 | 0.00 | 0.472005E+12 | 0.00 | 1.02 |
Minimum of Months | 0.216417E+10 | 0.00 | 0.00 | 74365376.94 | 0.00 | 0.00 | 0.171319E+11 | 0.00 | 0.81 |
Maximum of Months | 0.627646E+10 | 0.580008E+10 | 0.00 | 0.109053E+09 | 0.383408E+09 | 0.00 | 0.591321E+11 | 0.00 | 1.28 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.653630E+11 | 0.157464E+09 | 0.00 | 0.504096E+09 | 0.514597E+09 | 0.00 | 0.280298E+12 | 0.00 | 0.60 |
February | 0.537527E+11 | 0.168358E+09 | 0.00 | 0.464863E+09 | 0.00 | 0.00 | 0.303151E+12 | 0.00 | 0.65 |
March | 0.515523E+11 | 0.00 | 0.00 | 0.551952E+09 | 0.245313E+09 | 0.00 | 0.371402E+12 | 0.00 | 0.67 |
April | 0.424553E+11 | 54101587.61 | 0.00 | 0.580015E+09 | 0.728953E+09 | 0.00 | 0.311919E+12 | 0.00 | 0.76 |
May | 0.379320E+11 | 0.356330E+09 | 0.00 | 0.635217E+09 | 0.00 | 0.00 | 0.340564E+12 | 0.00 | 0.81 |
June | 0.254051E+11 | 0.269313E+10 | 0.00 | 0.680584E+09 | 380159.77 | 0.00 | 0.273675E+12 | 0.00 | 0.89 |
July | 0.262961E+11 | 0.282004E+11 | 0.00 | 0.517560E+09 | 0.303983E+10 | 0.00 | 0.132226E+12 | 0.00 | 0.82 |
August | 0.129081E+11 | 0.360537E+11 | 0.00 | 0.559996E+09 | 0.329876E+10 | 0.00 | 0.128523E+12 | 0.00 | 0.87 |
September | 0.261077E+11 | 0.968993E+10 | 0.00 | 0.588436E+09 | 0.852608E+09 | 0.00 | 0.220161E+12 | 0.00 | 0.81 |
October | 0.227253E+11 | 0.214997E+11 | 0.00 | 0.537574E+09 | 0.408764E+10 | 0.00 | 0.198630E+12 | 0.00 | 0.73 |
November | 0.371177E+11 | 33515006.11 | 0.00 | 0.571083E+09 | 0.182133E+09 | 0.00 | 0.331944E+12 | 0.00 | 0.69 |
December | 0.582605E+11 | 41011654.67 | 0.00 | 0.514533E+09 | 10228536.86 | 0.00 | 0.278944E+12 | 0.00 | 0.62 |
Annual Sum or Average | 0.459876E+12 | 0.989476E+11 | 0.00 | 0.670591E+10 | 0.129604E+11 | 0.00 | 0.317144E+13 | 0.00 | 0.74 |
Minimum of Months | 0.129081E+11 | 0.00 | 0.00 | 0.464863E+09 | 0.00 | 0.00 | 0.128523E+12 | 0.00 | 0.60 |
Maximum of Months | 0.653630E+11 | 0.360537E+11 | 0.00 | 0.680584E+09 | 0.408764E+10 | 0.00 | 0.371402E+12 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.147675E+11 | 3720043.67 | 0.00 | 20872524.65 | 55858809.11 | 0.194346E+09 | 0.128670E+11 | 0.00 | 0.51 |
February | 0.124758E+11 | 7087586.85 | 0.00 | 22811827.67 | 0.00 | 0.00 | 0.166973E+11 | 0.00 | 0.55 |
March | 0.130602E+11 | 0.00 | 0.00 | 28856083.68 | 29479866.44 | 0.00 | 0.222738E+11 | 0.00 | 0.57 |
April | 0.854321E+10 | 364193.91 | 0.00 | 42991203.41 | 41993537.27 | 0.00 | 0.249654E+11 | 0.00 | 0.72 |
May | 0.843793E+10 | 13791582.51 | 0.00 | 48408404.62 | 0.00 | 0.00 | 0.275490E+11 | 0.00 | 0.76 |
June | 0.460529E+10 | 0.139418E+09 | 0.00 | 58679835.55 | 0.00 | 0.00 | 0.254963E+11 | 0.00 | 0.88 |
July | 0.320277E+10 | 0.242828E+10 | 0.00 | 46282755.37 | 0.252572E+09 | 0.00 | 0.130268E+11 | 0.00 | 0.85 |
August | 0.177440E+10 | 0.330197E+10 | 0.00 | 48872705.05 | 0.309196E+09 | 0.00 | 0.120341E+11 | 0.00 | 0.91 |
September | 0.492024E+10 | 0.763939E+09 | 0.00 | 46875286.42 | 41795464.24 | 0.00 | 0.183967E+11 | 0.00 | 0.77 |
October | 0.603588E+10 | 0.183414E+10 | 0.00 | 35841047.56 | 0.396515E+09 | 0.00 | 0.127059E+11 | 0.00 | 0.68 |
November | 0.109363E+11 | 219289.48 | 0.00 | 29582400.53 | 7752368.04 | 0.00 | 0.190359E+11 | 0.00 | 0.58 |
December | 0.133407E+11 | 498557.61 | 0.00 | 22465693.08 | 3702693.33 | 1859044.96 | 0.130330E+11 | 0.00 | 0.52 |
Annual Sum or Average | 0.102100E+12 | 0.849343E+10 | 0.00 | 0.452540E+09 | 0.113887E+10 | 0.196205E+09 | 0.218081E+12 | 0.00 | 0.69 |
Minimum of Months | 0.177440E+10 | 0.00 | 0.00 | 20872524.65 | 0.00 | 0.00 | 0.120341E+11 | 0.00 | 0.51 |
Maximum of Months | 0.147675E+11 | 0.330197E+10 | 0.00 | 58679835.55 | 0.396515E+09 | 0.194346E+09 | 0.275490E+11 | 0.00 | 0.91 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.229156E+10 | 7530763.99 | 0.00 | 3810561.76 | 4833003.93 | 0.00 | 0.204670E+10 | 0.00 | 0.59 |
February | 0.201826E+10 | 2048766.42 | 0.00 | 4134683.21 | 0.00 | 0.00 | 0.262033E+10 | 0.00 | 0.65 |
March | 0.190630E+10 | 0.00 | 0.00 | 5834100.89 | 853910.54 | 0.00 | 0.386042E+10 | 0.00 | 0.73 |
April | 0.150600E+10 | 1399463.73 | 0.00 | 7818189.55 | 5437241.29 | 0.00 | 0.408659E+10 | 0.00 | 0.96 |
May | 0.127353E+10 | 4802794.60 | 0.00 | 7998747.90 | 0.00 | 0.00 | 0.416694E+10 | 0.00 | 0.94 |
June | 0.521666E+09 | 62821760.36 | 0.00 | 10701241.32 | 0.00 | 0.00 | 0.426499E+10 | 0.00 | 1.17 |
July | 0.878372E+09 | 0.654914E+09 | 0.00 | 8100728.80 | 43152097.60 | 0.00 | 0.213119E+10 | 0.00 | 1.23 |
August | 0.860747E+09 | 0.854299E+09 | 0.00 | 7279481.02 | 48117011.93 | 0.00 | 0.175163E+10 | 0.00 | 1.29 |
September | 0.778183E+09 | 0.173932E+09 | 0.00 | 6903010.20 | 5773590.25 | 0.00 | 0.256528E+10 | 0.00 | 0.92 |
October | 0.854268E+09 | 0.487418E+09 | 0.00 | 6159280.68 | 38174395.97 | 0.00 | 0.215156E+10 | 0.00 | 0.87 |
November | 0.178147E+10 | 691463.76 | 0.00 | 5636099.53 | 3246677.03 | 0.00 | 0.313933E+10 | 0.00 | 0.74 |
December | 0.203047E+10 | 340898.97 | 0.00 | 5196061.09 | 0.00 | 0.00 | 0.249511E+10 | 0.00 | 0.66 |
Annual Sum or Average | 0.167008E+11 | 0.225020E+10 | 0.00 | 79572185.94 | 0.149588E+09 | 0.00 | 0.352801E+11 | 0.00 | 0.90 |
Minimum of Months | 0.521666E+09 | 0.00 | 0.00 | 3810561.76 | 0.00 | 0.00 | 0.175163E+10 | 0.00 | 0.59 |
Maximum of Months | 0.229156E+10 | 0.854299E+09 | 0.00 | 10701241.32 | 48117011.93 | 0.00 | 0.426499E+10 | 0.00 | 1.29 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.179961E+10 | 6762865.81 | 0.00 | 4909507.98 | 4342620.94 | 0.00 | 0.253404E+10 | 0.00 | 0.89 |
February | 0.175932E+10 | 1506117.02 | 0.00 | 4369661.45 | 0.00 | 0.00 | 0.260087E+10 | 0.00 | 0.95 |
March | 0.186997E+10 | 49379.64 | 0.00 | 5933990.04 | 717888.47 | 0.00 | 0.343707E+10 | 0.00 | 1.06 |
April | 0.157325E+10 | 2534362.49 | 0.00 | 8467963.19 | 4475388.12 | 0.00 | 0.400726E+10 | 0.00 | 1.47 |
May | 0.115859E+10 | 4581658.32 | 0.00 | 8329259.60 | 0.00 | 0.00 | 0.404650E+10 | 0.00 | 1.37 |
June | 0.829476E+09 | 50764586.02 | 0.00 | 9313623.88 | 0.00 | 0.00 | 0.335578E+10 | 0.00 | 1.60 |
July | 0.895519E+09 | 0.552667E+09 | 0.00 | 8025585.29 | 26541898.48 | 0.00 | 0.199518E+10 | 0.00 | 1.78 |
August | 0.980587E+09 | 0.813374E+09 | 0.00 | 6545606.44 | 32851828.93 | 0.00 | 0.155337E+10 | 0.00 | 1.89 |
September | 0.889975E+09 | 0.131597E+09 | 0.00 | 6929367.18 | 7112817.61 | 0.00 | 0.237335E+10 | 0.00 | 1.36 |
October | 0.958934E+09 | 0.361551E+09 | 0.00 | 5545565.26 | 34310792.01 | 0.00 | 0.192646E+10 | 0.00 | 1.17 |
November | 0.167554E+10 | 518953.40 | 0.00 | 5471896.66 | 2917251.44 | 0.00 | 0.282137E+10 | 0.00 | 1.01 |
December | 0.190153E+10 | 296846.36 | 0.00 | 4929753.65 | 0.00 | 0.00 | 0.223549E+10 | 0.00 | 0.91 |
Annual Sum or Average | 0.162923E+11 | 0.192620E+10 | 0.00 | 78771780.62 | 0.113270E+09 | 0.00 | 0.328867E+11 | 0.00 | 1.29 |
Minimum of Months | 0.829476E+09 | 49379.64 | 0.00 | 4369661.45 | 0.00 | 0.00 | 0.155337E+10 | 0.00 | 0.89 |
Maximum of Months | 0.190153E+10 | 0.813374E+09 | 0.00 | 9313623.88 | 34310792.01 | 0.00 | 0.404650E+10 | 0.00 | 1.89 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.122707E+10 | 37566206.89 | 0.00 | 17997775.76 | 4646563.94 | 0.00 | 0.823921E+10 | 0.00 | 1.43 |
February | 0.134993E+10 | 6127618.42 | 0.00 | 13438392.42 | 0.00 | 0.00 | 0.675906E+10 | 0.00 | 1.28 |
March | 0.166031E+10 | 1473466.18 | 0.00 | 12078682.27 | 94933.28 | 0.00 | 0.678152E+10 | 0.00 | 1.21 |
April | 0.151211E+10 | 5457897.46 | 0.00 | 12094317.74 | 3419031.53 | 0.00 | 0.570313E+10 | 0.00 | 1.33 |
May | 0.156988E+10 | 6091369.00 | 0.00 | 8288220.97 | 0.00 | 0.00 | 0.411655E+10 | 0.00 | 1.01 |
June | 0.849324E+09 | 72001961.43 | 0.00 | 9259139.95 | 0.00 | 0.00 | 0.369940E+10 | 0.00 | 1.15 |
July | 0.942877E+09 | 0.743392E+09 | 0.00 | 7168205.50 | 35556916.08 | 0.00 | 0.197698E+10 | 0.00 | 1.27 |
August | 0.896915E+09 | 0.118556E+10 | 0.00 | 8477116.55 | 35010179.54 | 0.00 | 0.200649E+10 | 0.00 | 1.59 |
September | 0.585495E+09 | 0.275767E+09 | 0.00 | 13214740.03 | 5705122.23 | 0.00 | 0.416664E+10 | 0.00 | 1.47 |
October | 0.653279E+09 | 0.886060E+09 | 0.00 | 14852196.51 | 17686003.54 | 0.00 | 0.385075E+10 | 0.00 | 1.43 |
November | 0.882535E+09 | 8625133.38 | 0.00 | 19796487.04 | 632092.98 | 0.00 | 0.862318E+10 | 0.00 | 1.58 |
December | 0.975837E+09 | 761296.08 | 0.00 | 23953402.44 | 0.00 | 0.00 | 0.844381E+10 | 0.00 | 1.56 |
Annual Sum or Average | 0.131055E+11 | 0.322888E+10 | 0.00 | 0.160619E+09 | 0.102751E+09 | 0.00 | 0.643667E+11 | 0.00 | 1.36 |
Minimum of Months | 0.585495E+09 | 761296.08 | 0.00 | 7168205.50 | 0.00 | 0.00 | 0.197698E+10 | 0.00 | 1.01 |
Maximum of Months | 0.166031E+10 | 0.118556E+10 | 0.00 | 23953402.44 | 35556916.08 | 0.00 | 0.862318E+10 | 0.00 | 1.59 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.177039E+10 | 15078226.75 | 0.00 | 6296423.62 | 4877433.66 | 0.00 | 0.371552E+10 | 0.00 | 1.17 |
February | 0.825060E+09 | 3008957.88 | 0.00 | 8916209.58 | 0.00 | 0.00 | 0.548979E+10 | 0.00 | 1.43 |
March | 0.500995E+09 | 86904.83 | 0.00 | 14047756.94 | 893342.04 | 0.00 | 0.818123E+10 | 0.00 | 1.76 |
April | 0.512748E+09 | 7624368.54 | 0.00 | 22196423.69 | 2592783.65 | 0.00 | 0.890102E+10 | 0.00 | 2.52 |
May | 0.657864E+09 | 5111150.90 | 0.00 | 13522241.68 | 0.00 | 0.00 | 0.626698E+10 | 0.00 | 1.87 |
June | 0.288207E+09 | 67749541.97 | 0.00 | 18026169.58 | 0.00 | 0.00 | 0.616093E+10 | 0.00 | 2.46 |
July | 0.639774E+09 | 0.974596E+09 | 0.00 | 17667522.48 | 21637841.86 | 0.00 | 0.366954E+10 | 0.00 | 2.73 |
August | 0.672901E+09 | 0.128523E+10 | 0.00 | 16928694.66 | 19345595.77 | 0.00 | 0.333423E+10 | 0.00 | 3.09 |
September | 0.330152E+09 | 0.182904E+09 | 0.00 | 12562007.22 | 3245728.26 | 0.00 | 0.413742E+10 | 0.00 | 1.88 |
October | 0.382118E+09 | 0.531277E+09 | 0.00 | 11146320.17 | 27257185.11 | 0.00 | 0.350772E+10 | 0.00 | 1.69 |
November | 0.478474E+09 | 5991451.49 | 0.00 | 13522198.70 | 1015651.49 | 0.00 | 0.672398E+10 | 0.00 | 1.72 |
December | 0.524709E+09 | 441965.10 | 0.00 | 15247785.89 | 0.00 | 0.00 | 0.663198E+10 | 0.00 | 1.66 |
Annual Sum or Average | 0.758339E+10 | 0.307910E+10 | 0.00 | 0.170080E+09 | 80865561.85 | 0.00 | 0.667203E+11 | 0.00 | 2.00 |
Minimum of Months | 0.288207E+09 | 86904.83 | 0.00 | 6296423.62 | 0.00 | 0.00 | 0.333423E+10 | 0.00 | 1.17 |
Maximum of Months | 0.177039E+10 | 0.128523E+10 | 0.00 | 22196423.69 | 27257185.11 | 0.00 | 0.890102E+10 | 0.00 | 3.09 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.295637E+11 | 6077292.54 | 0.00 | 8863712.15 | 75006405.88 | 0.115549E+10 | 0.477667E+10 | 0.00 | 0.48 |
February | 0.270002E+11 | 15687255.76 | 0.00 | 9767717.46 | 0.00 | 21126934.37 | 0.801048E+10 | 0.00 | 0.49 |
March | 0.301484E+11 | 0.00 | 0.00 | 14644751.80 | 30864216.59 | 0.389798E+09 | 0.107568E+11 | 0.00 | 0.52 |
April | 0.204930E+11 | 5915962.64 | 0.00 | 33564946.19 | 91713735.72 | 0.00 | 0.167733E+11 | 0.00 | 0.64 |
May | 0.169932E+11 | 47068403.40 | 0.00 | 48272052.43 | 0.00 | 0.00 | 0.250711E+11 | 0.00 | 0.73 |
June | 0.103827E+11 | 0.382474E+09 | 0.00 | 67747086.37 | 47830.04 | 0.00 | 0.261330E+11 | 0.00 | 0.91 |
July | 0.707845E+10 | 0.444280E+10 | 0.00 | 46691839.37 | 0.382458E+09 | 0.00 | 0.124091E+11 | 0.00 | 0.87 |
August | 0.735001E+10 | 0.509265E+10 | 0.00 | 37745496.92 | 0.416647E+09 | 0.00 | 0.861203E+10 | 0.00 | 0.86 |
September | 0.135956E+11 | 0.146001E+10 | 0.00 | 37517903.78 | 82845877.54 | 0.00 | 0.130779E+11 | 0.00 | 0.73 |
October | 0.151334E+11 | 0.315268E+10 | 0.00 | 25974034.89 | 0.350469E+09 | 0.00 | 0.820745E+10 | 0.00 | 0.63 |
November | 0.255271E+11 | 2197752.65 | 0.00 | 14315108.22 | 23535192.53 | 7873793.48 | 0.992186E+10 | 0.00 | 0.52 |
December | 0.297228E+11 | 3227388.99 | 0.00 | 7127613.03 | 1457005.53 | 0.256258E+09 | 0.390238E+10 | 0.00 | 0.48 |
Annual Sum or Average | 0.232989E+12 | 0.146108E+11 | 0.00 | 0.352232E+09 | 0.145504E+10 | 0.183055E+10 | 0.147652E+12 | 0.00 | 0.66 |
Minimum of Months | 0.707845E+10 | 0.00 | 0.00 | 7127613.03 | 0.00 | 0.00 | 0.390238E+10 | 0.00 | 0.48 |
Maximum of Months | 0.301484E+11 | 0.509265E+10 | 0.00 | 67747086.37 | 0.416647E+09 | 0.115549E+10 | 0.261330E+11 | 0.00 | 0.91 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.219283E+11 | 23198516.94 | 0.00 | 22313866.75 | 52957635.41 | 0.397808E+09 | 0.131917E+11 | 0.00 | 0.74 |
February | 0.208238E+11 | 15700240.69 | 0.00 | 24776133.65 | 0.00 | 20427553.61 | 0.154744E+11 | 0.00 | 0.80 |
March | 0.219755E+11 | 2006128.56 | 0.00 | 36911122.40 | 27827769.51 | 0.226670E+09 | 0.212865E+11 | 0.00 | 0.88 |
April | 0.146278E+11 | 26054198.78 | 0.00 | 67349114.36 | 76520436.56 | 0.00 | 0.310370E+11 | 0.00 | 1.25 |
May | 0.145746E+11 | 54524357.40 | 0.00 | 65412790.69 | 0.00 | 0.00 | 0.312230E+11 | 0.00 | 1.24 |
June | 0.103628E+11 | 0.358119E+09 | 0.00 | 81973010.29 | 2430.40 | 0.00 | 0.271294E+11 | 0.00 | 1.47 |
July | 0.635940E+10 | 0.452170E+10 | 0.00 | 76183448.79 | 0.237110E+09 | 0.00 | 0.169679E+11 | 0.00 | 1.56 |
August | 0.597851E+10 | 0.653799E+10 | 0.00 | 61614732.49 | 0.227435E+09 | 0.00 | 0.134282E+11 | 0.00 | 1.62 |
September | 0.121013E+11 | 0.128103E+10 | 0.00 | 55399427.02 | 77539828.35 | 0.00 | 0.173918E+11 | 0.00 | 1.24 |
October | 0.122200E+11 | 0.285854E+10 | 0.00 | 36089783.73 | 0.335685E+09 | 0.00 | 0.125675E+11 | 0.00 | 0.99 |
November | 0.188015E+11 | 2682657.39 | 0.00 | 28413860.52 | 21526813.00 | 0.00 | 0.173409E+11 | 0.00 | 0.82 |
December | 0.222929E+11 | 4188202.34 | 0.00 | 21528095.22 | 1208936.78 | 78915302.06 | 0.109144E+11 | 0.00 | 0.75 |
Annual Sum or Average | 0.182046E+12 | 0.156857E+11 | 0.00 | 0.577965E+09 | 0.105781E+10 | 0.723821E+09 | 0.227953E+12 | 0.00 | 1.11 |
Minimum of Months | 0.597851E+10 | 2006128.56 | 0.00 | 21528095.22 | 0.00 | 0.00 | 0.109144E+11 | 0.00 | 0.74 |
Maximum of Months | 0.222929E+11 | 0.653799E+10 | 0.00 | 81973010.29 | 0.335685E+09 | 0.397808E+09 | 0.312230E+11 | 0.00 | 1.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.116495E+11 | 0.403201E+09 | 0.00 | 0.176407E+09 | 474686.69 | 0.00 | 0.739470E+11 | 0.00 | 1.33 |
February | 0.142126E+11 | 72391171.29 | 0.00 | 0.120545E+09 | 0.00 | 0.00 | 0.562641E+11 | 0.00 | 1.15 |
March | 0.179950E+11 | 37764732.84 | 0.00 | 95367983.02 | 7757725.65 | 0.176865E+09 | 0.502796E+11 | 0.00 | 1.02 |
April | 0.150244E+11 | 36785795.99 | 0.00 | 87198141.86 | 74924685.86 | 0.00 | 0.400879E+11 | 0.00 | 1.05 |
May | 0.168147E+11 | 64412854.47 | 0.00 | 61923942.81 | 0.00 | 0.00 | 0.301876E+11 | 0.00 | 0.85 |
June | 0.119549E+11 | 0.465616E+09 | 0.00 | 67159414.58 | 48189.84 | 0.00 | 0.247493E+11 | 0.00 | 0.94 |
July | 0.789041E+10 | 0.535434E+10 | 0.00 | 48913245.40 | 0.354094E+09 | 0.00 | 0.121679E+11 | 0.00 | 0.96 |
August | 0.538622E+10 | 0.813251E+10 | 0.00 | 63251515.14 | 0.407948E+09 | 0.00 | 0.139863E+11 | 0.00 | 1.21 |
September | 0.806402E+10 | 0.297850E+10 | 0.00 | 0.114556E+09 | 58252403.80 | 0.00 | 0.341458E+11 | 0.00 | 1.35 |
October | 0.752026E+10 | 0.812312E+10 | 0.00 | 0.130124E+09 | 51568412.13 | 0.00 | 0.308919E+11 | 0.00 | 1.27 |
November | 0.102822E+11 | 75226567.31 | 0.00 | 0.174096E+09 | 0.00 | 0.00 | 0.717383E+11 | 0.00 | 1.41 |
December | 0.109709E+11 | 22582609.67 | 0.00 | 0.210740E+09 | 0.00 | 5658702.42 | 0.674157E+11 | 0.00 | 1.38 |
Annual Sum or Average | 0.137765E+12 | 0.257664E+11 | 0.00 | 0.135028E+10 | 0.955068E+09 | 0.182524E+09 | 0.505861E+12 | 0.00 | 1.16 |
Minimum of Months | 0.538622E+10 | 22582609.67 | 0.00 | 48913245.40 | 0.00 | 0.00 | 0.121679E+11 | 0.00 | 0.85 |
Maximum of Months | 0.179950E+11 | 0.813251E+10 | 0.00 | 0.210740E+09 | 0.407948E+09 | 0.176865E+09 | 0.739470E+11 | 0.00 | 1.41 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.256669E+11 | 82221425.39 | 0.00 | 24639014.09 | 25388470.56 | 0.252035E+09 | 0.136283E+11 | 0.00 | 0.84 |
February | 0.229913E+11 | 22094351.48 | 0.00 | 27803197.31 | 0.00 | 0.00 | 0.182520E+11 | 0.00 | 0.93 |
March | 0.238619E+11 | 0.00 | 0.00 | 40937494.41 | 30636247.04 | 25542712.39 | 0.264748E+11 | 0.00 | 1.03 |
April | 0.127256E+11 | 49932475.12 | 0.00 | 88634156.65 | 60258676.06 | 0.00 | 0.377801E+11 | 0.00 | 1.41 |
May | 0.122888E+11 | 45188824.92 | 0.00 | 85966327.95 | 0.00 | 0.00 | 0.390553E+11 | 0.00 | 1.41 |
June | 0.729645E+10 | 0.344273E+09 | 0.00 | 0.106585E+09 | 2568.04 | 0.00 | 0.366454E+11 | 0.00 | 1.73 |
July | 0.415909E+10 | 0.603084E+10 | 0.00 | 92489734.20 | 0.244719E+09 | 0.00 | 0.200720E+11 | 0.00 | 1.72 |
August | 0.355403E+10 | 0.655266E+10 | 0.00 | 76464947.24 | 0.244283E+09 | 0.00 | 0.161728E+11 | 0.00 | 1.77 |
September | 0.822643E+10 | 0.157200E+10 | 0.00 | 76848737.58 | 58740482.81 | 0.00 | 0.254828E+11 | 0.00 | 1.45 |
October | 0.116243E+11 | 0.347349E+10 | 0.00 | 43591362.50 | 0.219474E+09 | 0.00 | 0.136378E+11 | 0.00 | 1.10 |
November | 0.217440E+11 | 10495446.28 | 0.00 | 35827100.82 | 19081335.82 | 0.00 | 0.202320E+11 | 0.00 | 0.99 |
December | 0.243680E+11 | 5216669.08 | 0.00 | 27377034.79 | 1446243.78 | 0.00 | 0.130236E+11 | 0.00 | 0.87 |
Annual Sum or Average | 0.178507E+12 | 0.181884E+11 | 0.00 | 0.727164E+09 | 0.904031E+09 | 0.277578E+09 | 0.280457E+12 | 0.00 | 1.27 |
Minimum of Months | 0.355403E+10 | 0.00 | 0.00 | 24639014.09 | 0.00 | 0.00 | 0.130236E+11 | 0.00 | 0.84 |
Maximum of Months | 0.256669E+11 | 0.655266E+10 | 0.00 | 0.106585E+09 | 0.244719E+09 | 0.252035E+09 | 0.390553E+11 | 0.00 | 1.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.251523E+10 | 0.00 | 62137.82 | 419311.05 | 7380451.26 | 0.469213E+09 | 0.248057E+09 | 95.56 | 0.46 |
February | 0.253419E+10 | 604911.18 | 0.00 | 446972.95 | 0.00 | 0.246696E+09 | 0.427344E+09 | 0.00 | 0.48 |
March | 0.299095E+10 | 0.00 | 0.00 | 871000.36 | 3691964.62 | 0.263972E+09 | 0.664401E+09 | 0.00 | 0.50 |
April | 0.198598E+10 | 43861.98 | 0.00 | 2949405.82 | 5259136.91 | 33403998.59 | 0.163399E+10 | 0.00 | 0.62 |
May | 0.182837E+10 | 1728254.95 | 0.00 | 4208689.06 | 0.00 | 2450603.02 | 0.231145E+10 | 0.00 | 0.71 |
June | 0.106370E+10 | 19301237.21 | 0.00 | 6643993.61 | 0.00 | 0.00 | 0.269320E+10 | 0.00 | 0.90 |
July | 0.728812E+09 | 0.382053E+09 | 0.00 | 4955275.92 | 31631332.87 | 0.00 | 0.131971E+10 | 0.00 | 0.90 |
August | 0.664257E+09 | 0.464243E+09 | 0.00 | 4196886.63 | 43056173.78 | 0.00 | 0.939939E+09 | 0.00 | 0.90 |
September | 0.134831E+10 | 0.110928E+09 | 0.00 | 3694701.50 | 8768910.19 | 0.00 | 0.126781E+10 | 0.00 | 0.71 |
October | 0.139666E+10 | 0.260480E+09 | 0.00 | 2200667.90 | 43530560.07 | 22434019.18 | 0.684935E+09 | 0.00 | 0.61 |
November | 0.251000E+10 | 17743.44 | 0.00 | 584074.89 | 970881.89 | 0.185434E+09 | 0.527533E+09 | 0.00 | 0.49 |
December | 0.250320E+10 | 0.00 | 0.00 | 258087.35 | 513880.96 | 0.368836E+09 | 0.152852E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.220697E+11 | 0.123940E+10 | 62137.82 | 31429067.03 | 0.144803E+09 | 0.159244E+10 | 0.128712E+11 | 95.56 | 0.65 |
Minimum of Months | 0.664257E+09 | 0.00 | 0.00 | 258087.35 | 0.00 | 0.00 | 0.152852E+09 | 0.00 | 0.46 |
Maximum of Months | 0.299095E+10 | 0.464243E+09 | 62137.82 | 6643993.61 | 43530560.07 | 0.469213E+09 | 0.269320E+10 | 95.56 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.205748E+10 | 1087095.47 | 0.00 | 1168962.46 | 5795260.01 | 0.233853E+09 | 0.757356E+09 | 0.00 | 0.69 |
February | 0.178996E+10 | 664033.87 | 0.00 | 1833300.66 | 0.00 | 0.136778E+09 | 0.122751E+10 | 0.00 | 0.74 |
March | 0.205955E+10 | 292280.43 | 0.00 | 2787962.04 | 3133687.06 | 0.126569E+09 | 0.174069E+10 | 0.00 | 0.81 |
April | 0.130701E+10 | 725647.06 | 0.00 | 6163884.99 | 4339600.17 | 12050800.72 | 0.308321E+10 | 0.00 | 1.20 |
May | 0.141902E+10 | 2325387.99 | 0.00 | 5946469.19 | 0.00 | 524952.64 | 0.306293E+10 | 0.00 | 1.20 |
June | 0.953391E+09 | 19035825.04 | 0.00 | 8187187.99 | 0.00 | 0.00 | 0.291935E+10 | 0.00 | 1.48 |
July | 0.554631E+09 | 0.399824E+09 | 0.00 | 8025572.34 | 9589821.20 | 0.00 | 0.186368E+10 | 0.00 | 1.62 |
August | 0.500456E+09 | 0.604129E+09 | 0.00 | 6605543.39 | 19672605.52 | 0.00 | 0.143257E+10 | 0.00 | 1.70 |
September | 0.107908E+10 | 0.103842E+09 | 0.00 | 5553580.08 | 7625544.29 | 0.00 | 0.181012E+10 | 0.00 | 1.21 |
October | 0.108046E+10 | 0.254167E+09 | 0.00 | 3227977.53 | 35467975.50 | 11216868.26 | 0.107316E+10 | 0.00 | 0.96 |
November | 0.172594E+10 | 16407.61 | 0.00 | 1841000.29 | 897788.18 | 60764306.15 | 0.129474E+10 | 0.00 | 0.74 |
December | 0.209449E+10 | 81309.35 | 0.00 | 1071739.26 | 428802.44 | 0.166438E+09 | 0.558309E+09 | 0.00 | 0.68 |
Annual Sum or Average | 0.166215E+11 | 0.138619E+10 | 0.00 | 52413180.23 | 86951084.37 | 0.748195E+09 | 0.208236E+11 | 0.00 | 1.09 |
Minimum of Months | 0.500456E+09 | 16407.61 | 0.00 | 1071739.26 | 0.00 | 0.00 | 0.558309E+09 | 0.00 | 0.68 |
Maximum of Months | 0.209449E+10 | 0.604129E+09 | 0.00 | 8187187.99 | 35467975.50 | 0.233853E+09 | 0.308321E+10 | 0.00 | 1.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.123510E+10 | 36011372.74 | 0.00 | 13682585.47 | 594084.69 | 0.158169E+09 | 0.624397E+10 | 0.00 | 1.24 |
February | 0.145273E+10 | 3185356.48 | 0.00 | 9691978.10 | 0.00 | 0.116371E+09 | 0.489460E+10 | 0.00 | 1.07 |
March | 0.196583E+10 | 3305097.01 | 0.00 | 7726858.08 | 1304342.53 | 0.168943E+09 | 0.446512E+10 | 0.00 | 0.95 |
April | 0.158882E+10 | 1119011.32 | 0.00 | 8141613.16 | 4993786.14 | 24419022.41 | 0.409428E+10 | 0.00 | 1.03 |
May | 0.191459E+10 | 2324648.66 | 0.00 | 5449043.14 | 0.00 | 11268290.68 | 0.289455E+10 | 0.00 | 0.84 |
June | 0.130293E+10 | 23398710.38 | 0.00 | 6639923.14 | 0.00 | 0.00 | 0.261141E+10 | 0.00 | 0.95 |
July | 0.843492E+09 | 0.449902E+09 | 0.00 | 5327292.13 | 31603432.28 | 0.00 | 0.136895E+10 | 0.00 | 1.01 |
August | 0.547280E+09 | 0.715987E+09 | 0.00 | 7022885.03 | 42042485.53 | 0.00 | 0.155461E+10 | 0.00 | 1.29 |
September | 0.861839E+09 | 0.215743E+09 | 0.00 | 11413418.06 | 9035220.01 | 0.00 | 0.360523E+10 | 0.00 | 1.32 |
October | 0.816275E+09 | 0.710240E+09 | 0.00 | 12075881.32 | 8235494.10 | 0.00 | 0.283258E+10 | 0.00 | 1.26 |
November | 0.121914E+10 | 2560117.23 | 0.00 | 14087171.81 | 73766.16 | 20394347.20 | 0.628718E+10 | 0.00 | 1.31 |
December | 0.120768E+10 | 2754020.22 | 0.00 | 16048984.85 | 0.00 | 80577490.00 | 0.550410E+10 | 0.00 | 1.27 |
Annual Sum or Average | 0.149557E+11 | 0.216653E+10 | 0.00 | 0.117308E+09 | 97882611.45 | 0.580142E+09 | 0.463566E+11 | 0.00 | 1.13 |
Minimum of Months | 0.547280E+09 | 1119011.32 | 0.00 | 5327292.13 | 0.00 | 0.00 | 0.136895E+10 | 0.00 | 0.84 |
Maximum of Months | 0.196583E+10 | 0.715987E+09 | 0.00 | 16048984.85 | 42042485.53 | 0.168943E+09 | 0.628718E+10 | 0.00 | 1.32 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.224089E+10 | 6442721.14 | 0.00 | 1920576.29 | 3156376.18 | 0.297674E+09 | 0.117157E+10 | 0.00 | 0.84 |
February | 0.225634E+10 | 988621.72 | 0.00 | 2224187.29 | 0.00 | 0.106296E+09 | 0.154968E+10 | 0.00 | 0.92 |
March | 0.258351E+10 | 0.00 | 0.00 | 3391922.21 | 3825968.32 | 0.118353E+09 | 0.228861E+10 | 0.00 | 1.02 |
April | 0.141094E+10 | 2564581.60 | 0.00 | 8243388.33 | 3490749.66 | 17803508.22 | 0.379271E+10 | 0.00 | 1.40 |
May | 0.143860E+10 | 1399680.45 | 0.00 | 7880717.50 | 0.00 | 1291377.07 | 0.387621E+10 | 0.00 | 1.41 |
June | 0.802729E+09 | 16226744.94 | 0.00 | 10534716.80 | 0.00 | 0.00 | 0.390295E+10 | 0.00 | 1.75 |
July | 0.464561E+09 | 0.515697E+09 | 0.00 | 10328673.07 | 27424149.30 | 0.00 | 0.217716E+10 | 0.00 | 1.79 |
August | 0.377939E+09 | 0.577677E+09 | 0.00 | 8198560.19 | 31855830.52 | 0.00 | 0.170257E+10 | 0.00 | 1.86 |
September | 0.903355E+09 | 0.114653E+09 | 0.00 | 7564617.54 | 6386798.81 | 0.00 | 0.258701E+10 | 0.00 | 1.44 |
October | 0.121249E+10 | 0.280815E+09 | 0.00 | 3980666.09 | 36375459.93 | 0.00 | 0.121315E+10 | 0.00 | 1.11 |
November | 0.222270E+10 | 290679.25 | 0.00 | 2871759.47 | 807656.37 | 49318619.70 | 0.171660E+10 | 0.00 | 0.97 |
December | 0.221755E+10 | 41218.83 | 0.00 | 2080199.04 | 514082.16 | 0.185465E+09 | 0.104059E+10 | 0.00 | 0.85 |
Annual Sum or Average | 0.181316E+11 | 0.151680E+10 | 0.00 | 69219983.82 | 0.113837E+09 | 0.776201E+09 | 0.270188E+11 | 0.00 | 1.28 |
Minimum of Months | 0.377939E+09 | 0.00 | 0.00 | 1920576.29 | 0.00 | 0.00 | 0.104059E+10 | 0.00 | 0.84 |
Maximum of Months | 0.258351E+10 | 0.577677E+09 | 0.00 | 10534716.80 | 36375459.93 | 0.297674E+09 | 0.390295E+10 | 0.00 | 1.86 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 3925582.83 | 0.00 | 0.00 | 0.330997E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7836770.69 | 0.00 | 0.00 | 0.290995E+09 | 0.00 | 0.29 |
March | 0.00 | 20521.02 | 0.00 | 14157462.99 | 0.00 | 0.00 | 0.338267E+09 | 0.00 | 0.31 |
April | 0.00 | 180431.93 | 0.00 | 17640796.76 | 0.00 | 0.00 | 0.198220E+09 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 4199781.37 | 0.00 | 0.00 | 0.242844E+09 | 0.00 | 0.29 |
June | 0.00 | 7738262.34 | 0.00 | 8046001.10 | 0.00 | 0.00 | 0.117156E+09 | 0.00 | 0.30 |
July | 0.00 | 60239813.75 | 0.00 | 5531884.73 | 0.00 | 0.00 | 25432930.81 | 0.00 | 0.28 |
August | 0.00 | 77640617.16 | 0.00 | 5873410.67 | 0.00 | 0.00 | 18015845.23 | 0.00 | 0.31 |
September | 0.00 | 14138977.28 | 0.00 | 3257605.79 | 0.00 | 0.00 | 93103808.55 | 0.00 | 0.29 |
October | 0.00 | 23141641.34 | 0.00 | 6757201.64 | 0.00 | 0.00 | 0.146608E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 12804056.65 | 0.00 | 0.00 | 0.275347E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 17730738.33 | 0.00 | 0.00 | 0.310153E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.183100E+09 | 0.00 | 0.107761E+09 | 0.00 | 0.00 | 0.238714E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3257605.79 | 0.00 | 0.00 | 18015845.23 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 77640617.16 | 0.00 | 17730738.33 | 0.00 | 0.00 | 0.338267E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 30405571.44 | 0.00 | 0.00 | 0.332907E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 68969280.73 | 0.00 | 0.00 | 0.292414E+10 | 0.00 | 0.29 |
March | 0.00 | 169987.98 | 0.00 | 0.128950E+09 | 0.00 | 0.00 | 0.339544E+10 | 0.00 | 0.31 |
April | 0.00 | 1780863.82 | 0.00 | 0.165211E+09 | 0.00 | 0.00 | 0.199241E+10 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 36405082.53 | 0.00 | 0.00 | 0.245096E+10 | 0.00 | 0.29 |
June | 0.00 | 75428068.09 | 0.00 | 74594207.85 | 0.00 | 0.00 | 0.118420E+10 | 0.00 | 0.30 |
July | 0.00 | 0.597966E+09 | 0.00 | 52287831.80 | 0.00 | 0.00 | 0.258664E+09 | 0.00 | 0.28 |
August | 0.00 | 0.773320E+09 | 0.00 | 56013872.59 | 0.00 | 0.00 | 0.183072E+09 | 0.00 | 0.31 |
September | 0.00 | 0.132963E+09 | 0.00 | 28781192.99 | 0.00 | 0.00 | 0.955042E+09 | 0.00 | 0.29 |
October | 0.00 | 0.227513E+09 | 0.00 | 61423125.51 | 0.00 | 0.00 | 0.147446E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.117035E+09 | 0.00 | 0.00 | 0.276404E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.163186E+09 | 0.00 | 0.00 | 0.311152E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.180914E+10 | 0.00 | 0.983262E+09 | 0.00 | 0.00 | 0.240230E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 28781192.99 | 0.00 | 0.00 | 0.183072E+09 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.773320E+09 | 0.00 | 0.165211E+09 | 0.00 | 0.00 | 0.339544E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 21085159.20 | 0.00 | 0.00 | 2257343.50 | 0.00 | 0.00 | 0.313920E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 6268131.66 | 0.00 | 0.00 | 0.293694E+09 | 0.00 | 0.29 |
March | 0.00 | 17464.92 | 0.00 | 12255260.10 | 0.00 | 0.00 | 0.340525E+09 | 0.00 | 0.31 |
April | 0.00 | 178129.81 | 0.00 | 16219777.30 | 0.00 | 0.00 | 0.199679E+09 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 3345014.95 | 0.00 | 0.00 | 0.246173E+09 | 0.00 | 0.29 |
June | 0.00 | 7586555.28 | 0.00 | 7332115.04 | 0.00 | 0.00 | 0.118685E+09 | 0.00 | 0.30 |
July | 0.00 | 59829733.96 | 0.00 | 5187143.77 | 0.00 | 0.00 | 25942527.23 | 0.00 | 0.28 |
August | 0.00 | 77312841.68 | 0.00 | 5557561.94 | 0.00 | 0.00 | 18400642.90 | 0.00 | 0.31 |
September | 0.00 | 13157729.76 | 0.00 | 2695257.37 | 0.00 | 0.00 | 96231220.39 | 0.00 | 0.29 |
October | 0.00 | 22715421.22 | 0.00 | 5839212.79 | 0.00 | 0.00 | 0.147945E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 11120897.26 | 0.00 | 0.00 | 0.277243E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 15605564.16 | 0.00 | 0.00 | 0.311954E+09 | 0.00 | 0.28 |
Annual Sum or Average | 21085159.20 | 0.180798E+09 | 0.00 | 93683279.83 | 0.00 | 0.00 | 0.239039E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2257343.50 | 0.00 | 0.00 | 18400642.90 | 0.00 | 0.28 |
Maximum of Months | 21085159.20 | 77312841.68 | 0.00 | 16219777.30 | 0.00 | 0.00 | 0.340525E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.522717E+09 | 0.00 | 0.00 | 0.408316E+12 | 0.00 | 17.79 |
February | 0.00 | 0.00 | 0.00 | 0.930418E+09 | 0.00 | 0.00 | 0.584100E+12 | 0.00 | 27.52 |
March | 0.00 | 0.00 | 0.00 | 0.154699E+10 | 0.00 | 0.00 | 0.846644E+12 | 0.00 | 35.97 |
April | 0.00 | 0.101478E+09 | 0.00 | 0.239816E+10 | 0.00 | 0.00 | 0.819733E+12 | 0.00 | 46.55 |
May | 0.00 | 0.00 | 0.00 | 0.535910E+09 | 0.00 | 0.00 | 0.355857E+12 | 0.00 | 20.52 |
June | 0.00 | 46737412.25 | 0.00 | 0.107156E+10 | 0.00 | 0.00 | 0.510606E+12 | 0.00 | 37.80 |
July | 0.00 | 0.183064E+11 | 0.00 | 0.191160E+10 | 0.00 | 0.00 | 0.478950E+12 | 0.00 | 47.85 |
August | 0.00 | 0.451029E+11 | 0.00 | 0.221060E+10 | 0.00 | 0.00 | 0.274677E+12 | 0.00 | 48.66 |
September | 0.00 | 0.475296E+09 | 0.00 | 0.513215E+09 | 0.00 | 0.00 | 0.329020E+12 | 0.00 | 25.69 |
October | 0.00 | 0.101297E+10 | 0.00 | 0.109232E+10 | 0.00 | 0.00 | 0.536456E+12 | 0.00 | 37.03 |
November | 0.00 | 0.00 | 0.00 | 0.159045E+10 | 0.00 | 0.00 | 0.832661E+12 | 0.00 | 39.37 |
December | 0.00 | 0.00 | 0.00 | 0.222238E+10 | 0.00 | 0.00 | 0.105565E+13 | 0.00 | 43.32 |
Annual Sum or Average | 0.00 | 0.650458E+11 | 0.00 | 0.165463E+11 | 0.00 | 0.00 | 0.703267E+13 | 0.00 | 35.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.513215E+09 | 0.00 | 0.00 | 0.274677E+12 | 0.00 | 17.79 |
Maximum of Months | 0.00 | 0.451029E+11 | 0.00 | 0.239816E+10 | 0.00 | 0.00 | 0.105565E+13 | 0.00 | 48.66 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:46
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.316255E+12 | 0.420410E+10 | 0.00 | 0.247493E+13 | 0.377869E+12 |
February | 0.389834E+12 | 0.504678E+10 | 0.00 | 0.260489E+13 | 0.310387E+12 |
March | 0.543266E+12 | 0.516062E+10 | 0.00 | 0.300654E+13 | 0.466856E+12 |
April | 0.689182E+12 | 0.306630E+10 | 0.00 | 0.278898E+13 | 0.103214E+13 |
May | 0.726087E+12 | 0.367021E+10 | 0.00 | 0.240174E+13 | 0.492451E+12 |
June | 0.711141E+12 | 0.191991E+10 | 0.00 | 0.223916E+13 | 0.958560E+12 |
July | 0.761042E+12 | 0.944659E+09 | 0.00 | 0.163354E+13 | 0.197113E+13 |
August | 0.708199E+12 | 0.989001E+09 | 0.00 | 0.117689E+13 | 0.288807E+13 |
September | 0.550578E+12 | 0.159255E+10 | 0.00 | 0.188978E+13 | 0.939246E+12 |
October | 0.388115E+12 | 0.270150E+10 | 0.00 | 0.208261E+13 | 0.133355E+13 |
November | 0.345859E+12 | 0.421996E+10 | 0.00 | 0.303448E+13 | 0.626643E+12 |
December | 0.285394E+12 | 0.474049E+10 | 0.00 | 0.327407E+13 | 0.908566E+12 |
Annual Sum or Average | 0.641495E+13 | 0.382561E+11 | 0.00 | 0.286076E+14 | 0.123055E+14 |
Minimum of Months | 0.285394E+12 | 0.944659E+09 | 0.00 | 0.117689E+13 | 0.310387E+12 |
Maximum of Months | 0.761042E+12 | 0.516062E+10 | 0.00 | 0.327407E+13 | 0.288807E+13 |