Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2024-07-03 12:21:49
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 27234.30 | 587.96 | 587.96 |
Net Site Energy | 27234.30 | 587.96 | 587.96 |
Total Source Energy | 84229.62 | 1818.41 | 1818.41 |
Net Source Energy | 84229.62 | 1818.41 | 1818.41 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 970.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 955.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3235.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 356.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2566.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2389.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 272.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 327.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1845.04 |
Humidification | 1045.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388.92 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 438.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 26263.87 | 970.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4514.13 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 970.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 955.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3235.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 356.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 55.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2505.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2389.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 272.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 327.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1845.04 |
Humidification | General | 1045.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388.92 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 438.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 970.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 955.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3235.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 356.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 2566.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2389.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 272.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 327.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1845.04 |
Humidification | Unassigned | 1045.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388.92 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 438.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 77.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 117.19 | 20.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
Other | 372.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 567.00 | 20.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 77.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 117.19 | 20.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
Other | 372.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 567.00 | 20.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 26263.871 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 26263.871 | 100.00 |
Total On-Site and Utility Electric Sources | 26263.871 | 100.00 |
Total Electricity End Uses | 26263.871 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 4514.13 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 4514.13 | 100.00 |
Total Water End Uses | 4514.13 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 12.50 |
Time Setpoint Not Met During Occupied Cooling | 505.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 8.6849 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 8.6849 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 8.7339 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 8.7339 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.6849 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 8.6849 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 8.6849 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 8.6849 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 8.6849 | 18.58 | 484.4232 | |
Total | 46320.38 | 8.7339 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 8.7339 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.6845 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-AUG-15:09 | 02-JAN-06:10 | - | - | - | - | - | - | - | - | - | - | 10-AUG-15:00 |
Heating | 0.00 | 1359749.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 395416.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 280450.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 233302.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 271668.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 40096.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 80769.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 33867.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2113943.05 | 1359749.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1359749.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 395416.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 280450.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3430.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 271668.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 40096.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 80769.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 33867.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1051.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3024.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 10248.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1128.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8128.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7568.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 861.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1037.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 3311.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1388.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 83177.68 | 1051.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 22.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 65.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 221.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 24.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 163.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 18.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 22.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 71.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 29.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1795.70 | 22.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 22.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 65.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 221.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 24.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 163.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 18.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 22.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 71.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 29.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1795.70 | 22.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 5.65 | 0.375174 | 0.000000 | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.90 | 0.322157 | 0.327000 | 1.93 | 0.859084 | 0.500000 | 0.001183 | 0.000168 | 1.93 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 55.45 | 0.343021 | 0.340000 | 18.85 | 0.914723 | 0.500000 | 0.001111 | 0.003418 | 18.85 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.36 | 0.354762 | 0.363000 | 1.95 | 0.946033 | 0.500000 | 0.001074 | 0.000624 | 2.15 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.886474 | 0.269405 | 0.273000 | 0.242007 | 0.718413 | 0.500000 | 0.001414 | 0.000072 | 0.248886 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.32 | 0.116916 | 0.200000 | 0.263274 | 0.311776 | 0.500000 | 0.003259 | 0.000059 | 0.263274 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.83 | 0.130338 | 0.200000 | 0.366470 | 0.347569 | 0.500000 | 0.002923 | 0.000096 | 0.366470 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.58 | 0.097666 | 0.200000 | 0.315165 | 0.300000 | 0.500000 | 0.003901 | 0.000049 | 0.315165 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 8.09 | 0.295093 | 0.293000 | 2.37 | 0.786914 | 0.500000 | 0.001291 | 0.001576 | 5.45 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 13.73 | 0.112120 | 0.200000 | 2.75 | 0.300000 | 0.500000 | 0.003398 | 0.001047 | 3.62 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 18.85 | 0.126673 | 0.200000 | 3.77 | 0.337795 | 0.500000 | 0.003008 | 0.001562 | 5.40 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 14.40 | 0.106880 | 0.200000 | 2.88 | 0.300000 | 0.500000 | 0.003565 | 0.000966 | 3.34 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.903676 | 0.264277 | 0.270000 | 0.243992 | 0.704738 | 0.500000 | 0.001442 | 0.000203 | 0.701488 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.36 | 0.112939 | 0.200000 | 0.272545 | 0.301171 | 0.500000 | 0.003373 | 0.000134 | 0.463016 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.98 | 0.120607 | 0.200000 | 0.396038 | 0.321620 | 0.500000 | 0.003159 | 0.000201 | 0.695901 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.50 | 0.102399 | 0.200000 | 0.300600 | 0.300000 | 0.500000 | 0.003721 | 0.000127 | 0.439368 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | User-Specified Rated Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 19161.95 | 0.000168 | 386.29 | |
CORE_MID VAV BOX REHEAT COIL | 390735.68 | 0.003418 | 8831.99 | |
CORE_TOP VAV BOX REHEAT COIL | 71359.02 | 0.000624 | 1884.84 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 8254.26 | 0.000072 | 218.04 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 6801.06 | 0.000059 | 163.29 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 11025.51 | 0.000096 | 279.40 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 5602.21 | 0.000049 | 122.53 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 180196.63 | 0.001576 | 4753.38 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 119690.45 | 0.001047 | 3157.19 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 178497.16 | 0.001562 | 4708.60 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 110399.48 | 0.000966 | 2912.36 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 23181.97 | 0.000203 | 611.36 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 15300.46 | 0.000134 | 403.50 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 22997.69 | 0.000201 | 606.51 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 14520.33 | 0.000127 | 382.94 | |
VAV_BOT WITH REHEAT HEATING COIL | 52936.07 | 0.000463 | 874.82 | |
VAV_MID WITH REHEAT HEATING COIL | 501396.29 | 0.004386 | 8269.85 | |
VAV_TOP WITH REHEAT HEATING COIL | 48610.38 | 0.000425 | 810.98 | |
CAV_BAS HEATING COIL | 275345.27 | 0.000875 | 2622.59 | 100000.00 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.512790 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.92 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.499398 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 24.90 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.76 | 3.12 | 11.52 | 3.12 | 9.62 | 9.62 | 0.300000 | 0.324223 | 9.62 |
VAV_MID WITH REHEAT | 55.26 | 30.62 | 110.52 | 30.62 | 89.13 | 89.13 | 0.300000 | 0.343547 | 89.13 |
VAV_TOP WITH REHEAT | 5.56 | 3.16 | 11.11 | 4.45 | 9.87 | 9.87 | 0.300000 | 0.451079 | 9.87 |
CAV_BAS | 0.000000 | 0.000000 | 5.65 | 1.20 | 5.65 | 5.65 | 1.00 | 0.212599 | 5.65 |
AIRLOOP DATACENTER BASEMENT | 24.90 | 24.90 | 24.90 | 24.90 | 24.90 | 24.90 | 1.00 | 0.999998 | 24.90 |
AIRLOOP DATACENTER BOT | 0.512790 | 0.512790 | 0.512790 | 0.512790 | 0.512790 | 0.512790 | 1.00 | 1.00 | 0.512790 |
AIRLOOP DATACENTER MID | 4.92 | 4.92 | 4.92 | 4.92 | 4.92 | 4.92 | 1.00 | 1.00 | 4.92 |
AIRLOOP DATACENTER TOP | 0.499398 | 0.499398 | 0.499398 | 0.499398 | 0.499398 | 0.499398 | 1.00 | 1.00 | 0.499398 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.62 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 89.13 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 9.87 | |
CAV_BAS_OA_CONTROLLER | 5.65 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 24.90 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.512790 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.92 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.499398 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 25.43 | 6.67 | 11.02 | 0.008828 | 0.008500 | 177365.51 | 0.005073 | 9.62 |
VAV_MID WITH REHEAT COOLING COIL | 25.56 | 6.67 | 11.02 | 0.008849 | 0.008500 | 1664210.66 | 0.047596 | 89.13 |
VAV_TOP WITH REHEAT COOLING COIL | 25.39 | 6.67 | 11.02 | 0.008822 | 0.008500 | 181431.07 | 0.005189 | 9.87 |
CAV_BAS COOLING COIL | 24.95 | 6.67 | 11.01 | 0.008948 | 0.008500 | 103018.58 | 0.002946 | 5.65 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.62 |
VAV_MID WITH REHEAT FAN | 89.13 |
VAV_TOP WITH REHEAT FAN | 9.87 |
CAV_BAS FAN | 5.65 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.005073 | 0.000094 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000463 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.047596 | 0.000010 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.004386 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.005189 | 0.000092 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000425 | |
CAV_BAS_COOLC_CONTROLLER | 0.002946 | 0.000162 |
CAV_BAS_HEATC_CONTROLLER | 0.000875 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 24.90 | 492249.67 | 352652.76 | 0.012055 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.512790 | 9912.44 | 7181.85 | 0.000243 |
AIRLOOP DATACENTER MID COOLING COIL | 4.92 | 95166.74 | 68949.38 | 0.002331 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.499398 | 9656.19 | 6995.12 | 0.000236 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 24.90 | 24.90 | 24.90 | 24.90 | 492249.67 | 492249.67 | 17840.03 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.512790 | 0.512790 | 0.512790 | 0.512790 | 9912.44 | 9912.44 | 824.14 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.92 | 4.92 | 4.92 | 4.92 | 95166.74 | 95166.74 | 8241.36 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.499398 | 0.499398 | 0.499398 | 0.499398 | 9656.19 | 9656.19 | 824.14 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 24.90 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.512790 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.92 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.499398 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 24.90 | 492249.67 | 0.012055 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.512790 | 9912.44 | 0.000243 |
AIRLOOP DATACENTER MID HEATING COIL | 4.92 | 95166.74 | 0.002331 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.499398 | 9656.19 | 0.000236 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 17840.03 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 824.14 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 8241.36 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 824.14 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000165 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.060804 | 9927.45 | |
HEATSYS1 PUMP | 0.016453 | 4954.89 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.060804 | 7.30 |
HEATSYS1 | 0.016453 | 1.97 |
COOLSYS1_SUPPLY | 0.060804 | 7.30 |
SINGLE WATER PLANT LOOP | 0.014865 | 1.78 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.060804 | 0.060804 | 255225.19 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1880666.60 | 1880666.60 | 0.016453 |
CENTRAL BOILER | 612311.57 | 600028.80 | 0.014865 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.030402 | 3436.55 |
COOLSYS1 CHILLER2 PUMP | 0.030402 | 3436.55 |
PLANT CIRC PUMP | 0.014865 | 3791.32 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.060804 | 0.030743 | 1074926.10 | 1074926.96 | 0.054128 |
COOLSYS1 CHILLER2 | 0.060804 | 0.030743 | 1074926.10 | 1074926.96 | 0.054128 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | U-factor Times Area Value at High Fan Speed [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/K] | |
CENTRAL TOWER | 0.014865 | 147598.67 | 74718.82 | 73799.33 | 7879.72 | 44831.29 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.108256 | 12.99 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.108256 | 26801.77 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 42.08 | 1288308.82 | 8.42 | 161038.60 |
TOWERWATERSYS COOLTOWER 2 | 42.08 | 1288308.82 | 8.42 | 161038.60 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.055743 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 8.685 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 13.527 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 8.685 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 493.108 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 24139.153 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 24139.153 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 6806.209 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6806.209 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.075 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.028 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.266 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7632 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8055 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6228 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | -0.34463022E-15 | 0.36894385E-16 | -0.14288780E-09 | 0.12757077E-17 |
51 | 8 | 0.20913840E-07 | 0.14359092E-12 | 0.36762620E-03 | -0.23779757E-09 |
52 | 7 | -0.11937955E-01 | 0.75343451E-08 | -0.22648608E-01 | 0.13573889E-03 |
53 | 6 | 0.39710065 | 0.26364580E-05 | 0.46505929 | -0.46505182E-02 |
54 | 5 | -5.1100523 | 0.98937734E-04 | -4.3872286 | 0.62185548E-01 |
55 | 4 | 32.646709 | 0.81302423E-03 | 21.229086 | -0.41739428 |
56 | 3 | -110.46842 | 0.17791168E-02 | -55.206350 | 1.5042464 |
57 | 2 | 196.38009 | 0.10043743E-02 | 77.491871 | -2.8887901 |
58 | 1 | -170.88709 | 0.10757908E-03 | -55.143519 | 2.7407251 |
59 | 0 | 57.057407 | 0.61468164E-06 | 15.577169 | |
60 | 9 | -0.22955380E-15 | 0.37743381E-16 | -0.14509256E-09 | 0.32676096E-18 |
61 | 8 | 0.21224167E-07 | 0.13772622E-12 | 0.37092755E-03 | -0.24132609E-09 |
62 | 7 | -0.12036605E-01 | 0.72012381E-08 | -0.22790691E-01 | 0.13686058E-03 |
63 | 6 | 0.39978134 | 0.25163753E-05 | 0.46734577 | -0.46821170E-02 |
64 | 5 | -5.1362151 | 0.94318005E-04 | -4.4048053 | 0.62509952E-01 |
65 | 4 | 32.762449 | 0.77422319E-03 | 21.297824 | -0.41893096 |
66 | 3 | -110.71472 | 0.16925811E-02 | -55.342260 | 1.5078047 |
67 | 2 | 196.62425 | 0.95470525E-03 | 77.616458 | -2.8926672 |
68 | 1 | -170.97729 | 0.10217823E-03 | -55.179630 | 2.7423060 |
69 | 0 | 57.057407 | 0.58332056E-06 | 15.571109 | |
70 | 9 | 0.11276195E-14 | 0.47405760E-16 | -0.13382366E-09 | -0.64614724E-17 |
71 | 8 | 0.19634610E-07 | 0.16705312E-12 | 0.35383761E-03 | -0.22325229E-09 |
72 | 7 | -0.11525316E-01 | 0.88979655E-08 | -0.22054087E-01 | 0.13104703E-03 |
73 | 6 | 0.38588679 | 0.31323747E-05 | 0.45547913 | -0.45183345E-02 |
74 | 5 | -5.0005974 | 0.11815564E-03 | -4.3135163 | 0.60828376E-01 |
75 | 4 | 32.162433 | 0.97545471E-03 | 20.940665 | -0.41096462 |
76 | 3 | -109.43770 | 0.21433374E-02 | -54.636007 | 1.4893559 |
77 | 2 | 195.35810 | 0.12144036E-02 | 76.969321 | -2.8725616 |
78 | 1 | -170.50942 | 0.13051365E-03 | -54.992579 | 2.7341060 |
79 | 0 | 57.057407 | 0.74839837E-06 | 15.602923 | |
80 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
81 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
82 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
83 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
84 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
85 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
86 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
87 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
88 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
89 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
90 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
91 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
92 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
93 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
94 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
95 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
96 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
97 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
98 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
99 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
100 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
101 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
102 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
103 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
104 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
105 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
106 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
107 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
108 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
109 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
110 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
111 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
112 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
113 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
114 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
115 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
116 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
117 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
118 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
119 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
120 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
121 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
122 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
123 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
124 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
125 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
126 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
127 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.38_SHGC_EAST_0.36 | 35 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.361 | ||
2 | WINDOW_U_0.38_SHGC_SOUTH_0.36 | 36 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.361 | ||
3 | WINDOW_U_0.38_SHGC_WEST_0.36 | 37 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.361 | ||
4 | WINDOW_U_0.38_SHGC_NORTH_0.36 | 38 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.361 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.45900E-002 | 0.27318 | 0.51781 | 0.51781 | 0.39600 | 0.13802 | 0.18068 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.45900E-002 | 0.27318 | 0.51781 | 0.51781 | 0.39600 | 0.13802 | 0.18068 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.45900E-002 | 0.27318 | 0.51781 | 0.51781 | 0.39600 | 0.13802 | 0.18068 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.45900E-002 | 0.27318 | 0.51781 | 0.51781 | 0.39600 | 0.13802 | 0.18068 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 1.973E-005 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.1779E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.1801E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.0963E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.0983E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4461E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4475E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4985E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4993E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.2301E-003 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.3870E-003 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.1415E-003 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2823E-003 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4838E-003 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5945E-003 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5191E-003 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5715E-003 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1661 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.4590E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1912 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1108 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1060 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4429E-002 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5151E-002 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5705E-002 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.2330E-003 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.4014E-003 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.1445E-003 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2976E-003 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4861E-003 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6032E-003 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5196E-003 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5730E-003 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.1776E-003 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.1800E-003 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.0960E-003 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.0981E-003 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4459E-003 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4474E-003 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4984E-003 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4992E-003 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8284E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.2308E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6058E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.0726E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.1110E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.2450E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2719E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.3081E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.4706E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.2175E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.0864E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.9583E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.1444E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5799E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.7010E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7586E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.6753E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.7905E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.4014E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.4856E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.0677E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.0990E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2720E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.3086E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7996E-003 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8018E-003 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3666E-003 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3683E-003 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0595E-003 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0608E-003 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4986E-003 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4993E-003 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8485E-003 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9767E-003 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4070E-003 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5099E-003 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0918E-003 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1645E-003 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5197E-003 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5731E-003 |
81 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.6821E-002 |
82 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4768E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.5978E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8817E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1884E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2330E-002 |
87 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.5151E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5700E-002 |
89 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8473E-003 |
90 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9743E-003 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4057E-003 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5068E-003 |
93 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0900E-003 |
94 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1588E-003 |
95 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5192E-003 |
96 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5716E-003 |
97 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7995E-003 |
98 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8016E-003 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3664E-003 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3682E-003 |
101 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0594E-003 |
102 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0606E-003 |
103 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4985E-003 |
104 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4992E-003 |
105 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.5087E-003 |
106 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.6251E-003 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1849E-003 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.2699E-003 |
109 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9562E-003 |
110 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.9868E-003 |
111 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2721E-003 |
112 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.3087E-003 |
113 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.1825E-002 |
114 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0961E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7142E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8009E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9389E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4947E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7010E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7586E-002 |
121 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6480E-003 |
122 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.0108E-003 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3713E-003 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.7859E-003 |
125 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9983E-003 |
126 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.1282E-003 |
127 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2719E-003 |
128 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.3080E-003 |
129 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1628 |
130 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1242 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1811 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1430 |
133 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1187 |
134 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.5082E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.5293E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.7353E-002 |
137 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.7046E-002 |
138 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.6205E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.2783E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.3131E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.2806E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.7901E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.6709E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7667E-002 |
145 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.7555E-002 |
146 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.8276E-002 |
147 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.5310E-002 |
148 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.0170E-002 |
149 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.0869E-002 |
150 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.2050E-002 |
151 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.5293E-002 |
152 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.7348E-002 |
153 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.3777E-002 |
154 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.4518E-002 |
155 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.8558E-002 |
156 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.0940E-002 |
157 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.0504E-002 |
158 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.6777E-002 |
159 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.6709E-002 |
160 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.7667E-002 |
161 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1628 |
162 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1243 |
163 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1811 |
164 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1432 |
165 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1188 |
166 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.5234E-002 |
167 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.5412E-002 |
168 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.7413E-002 |
169 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.7088E-002 |
170 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.6274E-002 |
171 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.2831E-002 |
172 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.3197E-002 |
173 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.2914E-002 |
174 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.7981E-002 |
175 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.6828E-002 |
176 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7727E-002 |
177 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.7558E-002 |
178 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.8321E-002 |
179 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.5316E-002 |
180 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.0205E-002 |
181 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.0934E-002 |
182 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.2092E-002 |
183 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.5412E-002 |
184 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.7409E-002 |
185 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.3816E-002 |
186 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.4584E-002 |
187 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.8601E-002 |
188 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.1002E-002 |
189 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.0609E-002 |
190 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.6854E-002 |
191 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.6828E-002 |
192 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.7727E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 77287.77029 | 77287.77029 | 5.64517 | 5.64517 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:10:00 | -4.20000 | 2.69032E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 80838.95663 | 80838.95663 | 5.90410 | 5.90410 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | -4.20000 | 2.69032E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 759420.64117 | 759420.64117 | 55.44975 | 55.44975 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 203616.92315 | 203616.92315 | 8.68574 | 10.77825 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 73435.08889 | 73435.08889 | 5.36146 | 5.36146 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.80930E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 50000.15215 | 50000.15215 | 2.15199 | 2.15199 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 12027.08223 | 12027.08223 | 0.88647 | 0.88647 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 29.40000 | 8.82150E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 5787.36661 | 5787.36661 | 0.24889 | 0.24889 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 17859.83593 | 17859.83593 | 1.31637 | 1.31637 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 23.02133 | 8.81136E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 4191.08166 | 4191.08166 | 0.18043 | 0.18043 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 24860.31768 | 24860.31768 | 1.83235 | 1.83235 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 28.96667 | 8.82080E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 7391.53121 | 7391.53121 | 0.31853 | 0.31853 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 21379.97058 | 21379.97058 | 1.57582 | 1.57582 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94400 | 8.81916E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 2481.47854 | 2481.47854 | 0.10629 | 0.10629 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 109801.18233 | 109801.18233 | 8.09307 | 8.09307 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40000 | 8.82150E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 126144.34043 | 126144.34043 | 5.44979 | 5.44979 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 186237.49674 | 186237.49674 | 13.72678 | 13.72678 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 23.35067 | 8.81188E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 83784.75610 | 83784.75610 | 3.62014 | 3.62014 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 255796.24482 | 255796.24482 | 18.85368 | 18.85368 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14000 | 8.82108E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 124956.42457 | 124956.42457 | 5.39827 | 5.39827 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 195368.41192 | 195368.41192 | 14.39977 | 14.39977 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 27.77067 | 8.81889E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 77290.23607 | 77290.23607 | 3.33851 | 3.33851 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 12260.46222 | 12260.46222 | 0.90368 | 0.90368 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 29.40000 | 8.82150E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 16223.99524 | 16223.99524 | 0.70149 | 0.70149 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 18488.70044 | 18488.70044 | 1.36272 | 1.36272 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.68000 | 8.81240E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 10707.88901 | 10707.88901 | 0.46302 | 0.46302 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 26866.13911 | 26866.13911 | 1.98019 | 1.98019 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14000 | 8.82108E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 16095.16353 | 16095.16353 | 0.69590 | 0.69590 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 20391.90387 | 20391.90387 | 1.50300 | 1.50300 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 27.77067 | 8.81889E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 10162.46913 | 10162.46913 | 0.43937 | 0.43937 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8820.68056 | 8820.68056 | 0.51279 | 0.51279 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 25.60400 | 8.81543E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | -4.20000 | 2.69032E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 84683.08239 | 84683.08239 | 4.92307 | 4.92307 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 25.60400 | 8.81543E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -4.20000 | 2.69032E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8590.29006 | 8590.29006 | 0.49940 | 0.49940 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 25.86400 | 8.81585E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -4.20000 | 2.69032E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 372404.56980 | 428265.25527 | 21.64947 | 24.89690 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 19.93600 | 8.80655E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 10:40:00 | -4.20000 | 2.69032E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 144730.52 | 9.61546 | 9.61546 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 39174.15 | 1.93196 | 1.93196 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1338311.29 | 89.12956 | 89.12956 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 514640.19 | 28.58496 | 28.58496 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 10:20:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 148170.33 | 9.86914 | 9.86914 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 51330.27 | 4.45176 | 4.45176 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 |
7 | CAV_BAS | Cooling | Sensible | 74021.75 | 5.64517 | 5.64517 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 63272.12 | 1.20016 | 1.20016 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 422205.60 | 24.89696 | 24.89696 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 17840.03 | 0.33839 | 0.33839 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8658.57 | 0.51279 | 0.51279 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 824.14 | 1.56323E-002 | 1.56323E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 83113.60 | 4.92307 | 4.92307 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 8241.36 | 0.15632 | 0.15632 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8436.30 | 0.49940 | 0.49940 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 824.14 | 1.56323E-002 | 1.56323E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 5.64517 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.37517 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.00000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 0.00000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.90410 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32216 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32700 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.93064 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.85908 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.18265E-003 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.67637E-004 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.93064 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
16 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19161.94884 |
17 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.67637E-004 |
18 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 386.28985 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 55.44975 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34302 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 18.85291 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.91472 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.11072E-003 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.41833E-003 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 18.85291 |
28 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
30 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 390735.67513 |
31 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.41833E-003 |
32 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 8831.98743 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.36146 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35476 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.36300 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.94621 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.94603 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.07396E-003 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.24280E-004 |
41 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.15199 |
42 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
43 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
44 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 71359.01735 |
45 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.24280E-004 |
46 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1884.84042 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.88647 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26941 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27300 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24201 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71841 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.41423E-003 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.22119E-005 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.24889 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
58 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8254.25846 |
59 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.22119E-005 |
60 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 218.03939 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.31637 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11692 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26327 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31178 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.25875E-003 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.94986E-005 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.26327 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
72 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6801.05945 |
73 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.94986E-005 |
74 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 163.29003 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.83235 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13034 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.36647 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34757 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.92316E-003 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.64559E-005 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.36647 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
86 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11025.50675 |
87 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.64559E-005 |
88 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 279.40308 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.57582 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.76665E-002 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.31516 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.90103E-003 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.90105E-005 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.31516 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
100 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5602.20594 |
101 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.90105E-005 |
102 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 122.52528 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 8.09307 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29509 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29300 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.37127 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.78691 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.29112E-003 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.57644E-003 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.44979 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
114 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 180196.63120 |
115 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.57644E-003 |
116 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4753.38040 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.72678 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11212 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.74536 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.39814E-003 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.04710E-003 |
125 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.62014 |
126 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
128 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 119690.45012 |
129 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.04710E-003 |
130 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3157.18851 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 18.85368 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12667 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.77074 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33780 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.00774E-003 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.56157E-003 |
139 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.39827 |
140 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
142 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 178497.16318 |
143 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.56157E-003 |
144 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4708.60036 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.39977 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10688 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.87995 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.56474E-003 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.65823E-004 |
153 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.33851 |
154 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
156 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 110399.48341 |
157 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.65823E-004 |
158 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2912.35627 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.90368 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26428 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24399 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70474 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.44167E-003 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.02806E-004 |
167 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.70149 |
168 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
170 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23181.97450 |
171 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.02806E-004 |
172 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 611.36130 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.36272 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11294 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27254 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30117 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.37349E-003 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.33855E-004 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.46302 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
184 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15300.45681 |
185 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.33855E-004 |
186 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 403.49882 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.98019 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12061 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.39604 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32162 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.15901E-003 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.01194E-004 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.69590 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
198 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22997.69131 |
199 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.01194E-004 |
200 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 606.50568 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.50300 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10240 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.30060 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.72075E-003 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.27030E-004 |
209 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.43937 |
210 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
211 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
212 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14520.33176 |
213 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.27030E-004 |
214 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 382.94147 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.51279 |
216 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.92307 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.49940 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 24.89690 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.75756 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.11756 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.51512 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.11756 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.61546 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.61546 |
225 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
226 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.32422 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 55.26152 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 30.62023 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 110.52304 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 30.62023 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 89.12956 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 89.12956 |
233 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
234 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.34355 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.55553 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.15939 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.11105 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 4.45176 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.86914 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.86914 |
241 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
242 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.45108 |
243 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.00000 |
244 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.00000 |
245 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.64517 |
246 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 1.20016 |
247 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.64517 |
248 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.64517 |
249 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
250 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.21260 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 24.89690 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 24.89690 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 24.89690 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 24.89690 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 24.89696 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 24.89696 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 1.00000 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.51279 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.51279 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.51279 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.51279 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.51279 |
264 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.51279 |
265 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
266 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.92307 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.92307 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.92307 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.92307 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.92307 |
272 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.92307 |
273 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
274 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.49940 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.49940 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.49940 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.49940 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.49940 |
280 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.49940 |
281 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
282 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
283 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.61546 |
284 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 89.12956 |
285 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.86914 |
286 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.64517 |
287 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 24.89696 |
288 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.51279 |
289 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.92307 |
290 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.49940 |
291 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.61546 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.42522 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.01736 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.82759E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 177365.50587 |
298 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.07263E-003 |
299 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.61546 |
300 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 52936.07476 |
301 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.63108E-004 |
302 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 874.81599 |
303 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.61546 |
304 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.07263E-003 |
305 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.38745E-005 |
306 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.63108E-004 |
307 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 89.12956 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.55755 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.01743 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.84928E-003 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1664210.66498 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.75962E-002 |
315 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 89.12956 |
316 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 501396.28661 |
317 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.38643E-003 |
318 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 8269.84889 |
319 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 89.12956 |
320 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.75962E-002 |
321 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.00048E-005 |
322 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.38643E-003 |
323 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.86914 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.38800 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.01734 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.82194E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 181431.07442 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.18891E-003 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.86914 |
332 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 48610.38225 |
333 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.25265E-004 |
334 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 810.98157 |
335 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.86914 |
336 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.18891E-003 |
337 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.17709E-005 |
338 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.25265E-004 |
339 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.64517 |
340 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.95015 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.00625 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.94848E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 103018.58355 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.94632E-003 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.64517 |
349 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 275345.26720 |
350 | Coil:Heating:Water | CAV_BAS HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
351 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
352 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2622.58834 |
353 | Fan:VariableVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.64517 |
354 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.94632E-003 |
355 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.61622E-004 |
356 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.74844E-004 |
357 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 24.89696 |
358 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
359 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.89696 |
360 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 492249.67052 |
361 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 352652.75632 |
362 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.20552E-002 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 24.89696 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 24.89696 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 24.89696 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 24.89696 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 492249.67052 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 492249.67052 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 17840.03233 |
370 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
371 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 24.89696 |
372 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.89696 |
373 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 492249.67052 |
374 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.20552E-002 |
375 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 17840.03233 |
376 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.65400E-004 |
377 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
378 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
379 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
380 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.51279 |
381 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
382 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.51279 |
383 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9912.43744 |
384 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 7181.84858 |
385 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.42755E-004 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.51279 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.51279 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.51279 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.51279 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9912.43744 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9912.43744 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 824.13559 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
394 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.51279 |
395 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.51279 |
396 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9912.43744 |
397 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.42755E-004 |
398 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 824.13559 |
399 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.92307 |
400 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
401 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.92307 |
402 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 95166.73734 |
403 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 68949.38008 |
404 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.33063E-003 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.92307 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.92307 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.92307 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.92307 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 95166.73734 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 95166.73734 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 8241.35587 |
412 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
413 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.92307 |
414 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.92307 |
415 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 95166.73734 |
416 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.33063E-003 |
417 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 8241.35587 |
418 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.49940 |
419 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
420 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49940 |
421 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9656.19282 |
422 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6995.11649 |
423 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.36480E-004 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.49940 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.49940 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.49940 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.49940 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9656.19282 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9656.19282 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 824.13559 |
431 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
432 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.49940 |
433 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49940 |
434 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9656.19282 |
435 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.36480E-004 |
436 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 824.13559 |
437 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 6.08041E-002 |
438 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 9927.44659 |
439 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 6.08041E-002 |
440 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 7.29649 |
441 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 6.08041E-002 |
442 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 6.08041E-002 |
443 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 255225.18953 |
444 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
445 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.64529E-002 |
446 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.97435 |
447 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.64529E-002 |
448 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 4954.88849 |
449 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
450 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1880666.59784 |
451 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1880666.60000 |
452 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.64529E-002 |
453 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 6.08041E-002 |
454 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 7.29649 |
455 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 3.04020E-002 |
456 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 3436.55303 |
457 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 3.04020E-002 |
458 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 3436.55303 |
459 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 6.08041E-002 |
460 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.07428E-002 |
461 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1074926.09754 |
462 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1074926.96000 |
463 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 5.41280E-002 |
464 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 6.08041E-002 |
465 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.07428E-002 |
466 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1074926.09754 |
467 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1074926.96000 |
468 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 5.41280E-002 |
469 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.48650E-002 |
470 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.78380 |
471 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.48650E-002 |
472 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3791.32461 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.48650E-002 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 147598.66585 |
475 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at High Fan Speed [W/K] | 74718.82080 |
476 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 73799.33293 |
477 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
478 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/K] | 44831.29248 |
479 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 612311.57151 |
480 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 600028.80000 |
481 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.48650E-002 |
482 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
483 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
484 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
485 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
486 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
487 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.10826 |
488 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 12.99071 |
489 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.10826 |
490 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 26801.76566 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 42.08062 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1288308.82332 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 8.41612 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 161038.60292 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 42.08062 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1288308.82332 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 8.41612 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 161038.60292 |
499 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.57425E-002 |
500 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.57425E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 18169.45 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 370278.78 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 67628.85 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 7822.89 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 6442.87 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 10441.84 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 5309.66 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 170735.44 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 113405.40 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 169125.54 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 104603.95 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 21963.79 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 14496.37 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 21789.22 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 13757.35 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 41086.44 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 387620.78 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 38462.04 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 94837.70 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 221799.02 | 161394.70 | 60404.32 | 0.73 | 36887.38 | 374.13 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2067392.71 | 1500517.50 | 566875.20 | 0.73 | 341376.51 | 3462.43 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 227299.91 | 165515.76 | 61784.15 | 0.73 | 37879.82 | 384.20 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 129909.04 | 94670.61 | 35238.43 | 0.73 | 21952.12 | 222.65 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 8.97 | 30.62 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 8.97 | 30.62 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.36 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.36 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.36 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.36 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.36 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.36 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.36 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.36 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.36 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.36 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.36 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.36 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.36 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.36 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.36 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.36 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.36 | N/A | 2.159 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.36 | N/A | 2.159 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.36 | N/A | 2.159 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.36 | N/A | 2.159 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.36 | N/A | 2.159 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.36 | N/A | 2.159 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.36 | N/A | 2.159 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.36 | N/A | 2.159 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 9.4203371465E-004 | 1.5415148947E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 3.1496273906E-003 | 6.3629988002E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 4.5193755962E-003 | 7.3673665663E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 1.9192640442E-002 | 1.4445302538E-002 | Pass | Pass | 0.4938710598 | 0.7623756483 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.3408804639E-002 | 1.3826601089E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 1.4919884037E-002 | 1.4946614630E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 1.4690434639E-002 | 1.5660793548E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 1.3926929771E-002 | 1.4271143476E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.6345528084E-002 | 1.5356975346E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 1.7732449975E-002 | 1.6687726049E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 1.8151651518E-002 | 1.8168175711E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 1.7134712627E-002 | 1.6532290889E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2517731884 | 0.2299402346 | Pass | Pass | 14.3037822988 | 32.5369604027 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2552155405 | 0.2391838070 | Pass | Pass | 9.9779371236 | 22.0900697446 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2387450560 | 0.2239881612 | Pass | Pass | 10.4503026770 | 23.0149738818 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1191782142 | 0.1396072991 | Pass | Pass | 10.1879644016 | 23.2991356194 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.6380450492E-003 | 2.5654848590E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.2514553342E-003 | 3.2549562005E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.4696178138E-002 | 5.4944703573E-002 | Pass | Pass | 0.4095520335 | 0.4698908004 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.7222785359E-006 | 5.6614202320E-006 | Pass | Pass | 1.6967053109E-003 | 1.3332670110E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 7.1090811176E-003 | 3.7019960850E-003 | Pass | Pass | 1.3389650483E-003 | 9.4651323469E-004 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.7127176205E-003 | 3.9663853537E-003 | Pass | Pass | 1.5869137060E-003 | 1.3081020730E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.6125204001E-006 | 2.9149693964E-006 | Pass | Pass | 2.8862292962E-005 | 1.0842685467E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5753.98 | 89.07 | 0.00 | 32107.66 | 6791.02 | 44741.74 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 22.00 | 23 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 16.00 | 20 | |||
Jul | 0.00 | 0 | |||
Aug | 24.00 | 18 | |||
Sep | 12.00 | 15 | |||
Oct | 61.00 | 41 | |||
Nov | 0.00 | 0 | |||
Dec | 45.00 | 41 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.38_SHGC_NORTH_0.36 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.38_SHGC_NORTH_0.36 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.38_SHGC_NORTH_0.36 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.38_SHGC_NORTH_0.36 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.38_SHGC_NORTH_0.36 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.38_SHGC_EAST_0.36 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.38_SHGC_EAST_0.36 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.38_SHGC_EAST_0.36 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.38_SHGC_SOUTH_0.36 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.38_SHGC_SOUTH_0.36 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.38_SHGC_SOUTH_0.36 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.38_SHGC_SOUTH_0.36 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.38_SHGC_SOUTH_0.36 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.38_SHGC_WEST_0.36 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.38_SHGC_WEST_0.36 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.38_SHGC_WEST_0.36 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.38_SHGC_NORTH_0.36 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.159 | 0.361 | 0.397 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.38_SHGC_EAST_0.36 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.159 | 0.361 | 0.397 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.38_SHGC_SOUTH_0.36 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.159 | 0.361 | 0.397 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.38_SHGC_WEST_0.36 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.159 | 0.361 | 0.397 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.38_SHGC_NORTH_0.36 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.159 | 0.361 | 0.397 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.38_SHGC_EAST_0.36 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.159 | 0.361 | 0.397 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.38_SHGC_SOUTH_0.36 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.159 | 0.361 | 0.397 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.38_SHGC_WEST_0.36 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.159 | 0.361 | 0.397 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.159 | 0.361 | 0.397 | |||||||||||||||||
North Total or Average | 1390.74 | 2.159 | 0.361 | 0.397 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.159 | 0.361 | 0.397 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.6849 | 2779.43 | 24139.15 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 216.17 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 8.6849 | 2496.12 | 21678.66 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 194.14 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 8.6849 | 24961.20 | 216786.56 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 1941.36 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 8.6849 | 2496.12 | 21678.66 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 194.14 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 8.6849 | 313.41 | 2721.97 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.56 | 0.0000 | Y | 14.59 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.11 | 0.0000 | Y | 9.25 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 8.6849 | 313.42 | 2722.03 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.70 | 0.0000 | Y | 14.15 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.06 | 0.0000 | Y | 9.24 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 8.6849 | 3134.13 | 27219.72 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.47 | 0.0000 | Y | 145.47 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 8.6849 | 2019.75 | 17541.42 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.03 | 0.0000 | Y | 92.30 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 8.6849 | 3134.20 | 27220.31 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.66 | 0.0000 | Y | 141.34 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 8.6849 | 2019.75 | 17541.42 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.99 | 0.0000 | Y | 92.16 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 8.6849 | 313.41 | 2721.97 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.47 | 0.0000 | Y | 14.54 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.03 | 0.0000 | Y | 9.23 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 8.6849 | 313.42 | 2722.03 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.66 | 0.0000 | Y | 14.13 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.99 | 0.0000 | Y | 9.22 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 8.6849 | 783.68 | 6806.21 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 62.65 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 13.9016 | 36.20 | 503.28 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.16 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 13.9016 | 362.03 | 5032.75 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 51.55 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 13.9016 | 36.20 | 503.28 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.16 |
Interior Lighting Total | 8.7339 | 46320.38 | 404555.99 | 1018.19 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13271.55 | AstronomicalClock | - | 42.59 | 42.59 | 106.11 | |
EXTERIOR_LIGHTS_B | 989.48 | AstronomicalClock | - | 83.55 | 63.07 | 11.71 | |
EXTERIOR_LIGHTS_C | 26594.85 | AstronomicalClock | - | 83.55 | 47.80 | 238.62 | |
Exterior Lighting Total | 40855.88 | 356.44 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2119477.48 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1880666.60 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1074926.96 | 5.91 | 1068719.79 | 5.88 | 8.97 | 30.62 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 1074926.96 | 5.91 | 1068719.79 | 5.88 | 8.97 | 30.62 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 615117.44 | |||||
CENTRAL BOILER | Boiler:HotWater | 600028.80 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1288308.82 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1288308.82 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 177365.51 | 221799.02 | 161394.70 | 60404.32 | 0.73 | - | 36887.38 | 374.13 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1664210.66 | 2067392.71 | 1500517.50 | 566875.20 | 0.73 | - | 341376.51 | 3462.43 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 181431.07 | 227299.91 | 165515.76 | 61784.15 | 0.73 | - | 37879.82 | 384.20 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 103018.58 | 129909.04 | 94670.61 | 35238.43 | 0.73 | - | 21952.12 | 222.65 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 492249.67 | 352652.76 | 139596.91 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9912.44 | 7181.85 | 2730.59 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 95166.74 | 68949.38 | 26217.36 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9656.19 | 6995.12 | 2661.08 | 0.72 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 19161.95 | 18169.45 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 390735.68 | 370278.78 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 71359.02 | 67628.85 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 8254.26 | 7822.89 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 6801.06 | 6442.87 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11025.51 | 10441.84 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 5602.21 | 5309.66 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 180196.63 | 170735.44 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 119690.45 | 113405.40 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 178497.16 | 169125.54 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 110399.48 | 104603.95 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 23181.97 | 21963.79 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 15300.46 | 14496.37 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 22997.69 | 21789.22 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 14520.33 | 13757.35 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 52936.07 | 41086.44 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 501396.29 | 387620.78 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 48610.38 | 38462.04 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 100000.00 | 94837.70 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 492249.67 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9912.44 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 95166.74 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9656.19 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 17840.03 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 824.14 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 8241.36 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 824.14 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.62 | 20778.51 | 2160.95 | 1.00 | 1.12 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 89.13 | 192604.23 | 2160.95 | 1.00 | 1.08 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.87 | 21326.70 | 2160.95 | 1.00 | 1.12 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
CAV_BAS FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.65 | 12277.62 | 2174.89 | 1.00 | 1.13 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 24.90 | 41061.23 | 1649.25 | 1.00 | 1.14 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.51 | 574.38 | 1120.11 | 1.00 | 1.59 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.92 | 5514.37 | 1120.11 | 1.00 | 1.16 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.50 | 559.38 | 1120.11 | 1.00 | 1.61 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.060804 | 9927.45 | 163269.45 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.016453 | 4954.89 | 301156.09 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.030402 | 3436.55 | 113036.94 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.030402 | 3436.55 | 113036.94 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.014865 | 3791.32 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.108256 | 26801.77 | 247577.87 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 77287.77 | 77287.77 | 27.81 | 5.645 | 5.645 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00895 | 21.70 | 0.00881 | 1.200 | 0.00 |
CORE_BOTTOM | 80838.96 | 80838.96 | 32.39 | 5.904 | 5.904 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00889 | 21.70 | 0.00881 | 1.078 | 0.00 |
CORE_MID | 759420.64 | 759420.64 | 304.24 | 55.450 | 55.450 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 21.70 | 0.00881 | 10.778 | 0.00 |
CORE_TOP | 73435.09 | 73435.09 | 29.42 | 5.361 | 5.361 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 21.70 | 0.00881 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 12027.08 | 12027.08 | 38.37 | 0.886 | 0.886 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00882 | 29.40 | 0.00882 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 17859.84 | 17859.84 | 88.43 | 1.316 | 1.316 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 24.00 | 24.00 | 0.00864 | 23.02 | 0.00881 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 24860.32 | 24860.32 | 79.32 | 1.832 | 1.832 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 24.00 | 24.00 | 0.00865 | 28.97 | 0.00882 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 21379.97 | 21379.97 | 105.85 | 1.576 | 1.576 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00862 | 27.94 | 0.00882 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 109801.18 | 109801.18 | 350.34 | 8.093 | 8.093 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 24.00 | 0.00885 | 29.40 | 0.00882 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 186237.50 | 186237.50 | 922.08 | 13.727 | 13.727 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 24.00 | 24.00 | 0.00863 | 23.35 | 0.00881 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 255796.24 | 255796.24 | 816.15 | 18.854 | 18.854 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00865 | 29.14 | 0.00882 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 195368.41 | 195368.41 | 967.29 | 14.400 | 14.400 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00863 | 27.77 | 0.00882 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 12260.46 | 12260.46 | 39.12 | 0.904 | 0.904 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00881 | 29.40 | 0.00882 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 18488.70 | 18488.70 | 91.54 | 1.363 | 1.363 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 24.00 | 24.00 | 0.00864 | 23.68 | 0.00881 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 26866.14 | 26866.14 | 85.72 | 1.980 | 1.980 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00864 | 29.14 | 0.00882 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 20391.90 | 20391.90 | 100.96 | 1.503 | 1.503 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00862 | 27.77 | 0.00882 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8820.68 | 8820.68 | 243.65 | 0.513 | 0.513 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 27.00 | 27.00 | 0.00858 | 25.60 | 0.00882 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 84683.08 | 84683.08 | 2339.13 | 4.923 | 4.923 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 27.00 | 27.00 | 0.00859 | 25.60 | 0.00882 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8590.29 | 8590.29 | 237.28 | 0.499 | 0.499 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00858 | 25.86 | 0.00882 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 372404.57 | 428265.26 | 546.48 | 21.649 | 24.897 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 19.94 | 0.00881 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:10:00 | 21.00 | 24.45 | 0.00269 | -4.20 | 0.00269 | 1.200 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | 19.60 | 22.14 | 0.00269 | -4.20 | 0.00269 | 1.078 | 0.00 |
CORE_MID | 203616.92 | 203616.92 | 81.57 | 8.686 | 10.778 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 10.778 | 0.00 |
CORE_TOP | 50000.15 | 50000.15 | 20.03 | 2.152 | 2.152 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 5787.37 | 5787.37 | 18.47 | 0.249 | 0.249 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00735 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 4191.08 | 4191.08 | 20.75 | 0.180 | 0.180 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00744 | -4.20 | 0.00269 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 7391.53 | 7391.53 | 23.58 | 0.319 | 0.319 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00757 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 2481.48 | 2481.48 | 12.29 | 0.106 | 0.106 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00682 | -4.20 | 0.00269 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 126144.34 | 126144.34 | 402.49 | 5.450 | 5.450 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00769 | -4.20 | 0.00269 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 83784.76 | 83784.76 | 414.83 | 3.620 | 3.620 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00770 | -4.20 | 0.00269 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 124956.42 | 124956.42 | 398.69 | 5.398 | 5.398 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00769 | -4.20 | 0.00269 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 77290.24 | 77290.24 | 382.67 | 3.339 | 3.339 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -4.20 | 0.00269 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 16224.00 | 16224.00 | 51.77 | 0.701 | 0.701 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 10707.89 | 10707.89 | 53.02 | 0.463 | 0.463 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -4.20 | 0.00269 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 16095.16 | 16095.16 | 51.35 | 0.696 | 0.696 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 10162.47 | 10162.47 | 50.32 | 0.439 | 0.439 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00771 | -4.20 | 0.00269 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | 18.00 | 26.66 | 0.00850 | -4.20 | 0.00269 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 23.41 | 0.00553 | -4.20 | 0.00269 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 21.77 | 0.00302 | -4.20 | 0.00269 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 10:40:00 | 18.00 | 27.00 | 0.00850 | -4.20 | 0.00269 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 9.62 | 9.62 | 1.93 | 1.93 | 9.6155 | 3.1176 | 9.6155 | 0.3242 | 0.3000 |
VAV_MID WITH REHEAT | 89.13 | 89.13 | 28.58 | 28.58 | 89.1296 | 30.6202 | 89.1296 | 0.3435 | 0.3000 |
VAV_TOP WITH REHEAT | 9.87 | 9.87 | 4.45 | 4.45 | 9.8691 | 4.4518 | 9.8691 | 0.4511 | 0.3000 |
CAV_BAS | 5.65 | 5.65 | 1.20 | 1.20 | 5.6452 | 1.2002 | 5.6452 | 0.2126 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.90 | 24.90 | 0.34 | 0.34 | 24.8970 | 24.8969 | 24.8970 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.51 | 0.51 | 0.02 | 0.02 | 0.5128 | 0.5128 | 0.5128 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.92 | 4.92 | 0.16 | 0.16 | 4.9231 | 4.9231 | 4.9231 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.50 | 0.50 | 0.02 | 0.02 | 0.4994 | 0.4994 | 0.4994 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 19161.949 | 19161.949 | 1.930639 | 0.00016764 | 386.290 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | 19161.95 | 19161.95 | 1.930639 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 19232.60 | 19232.60 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 390735.675 | 390735.675 | 18.852914 | 0.00341833 | 8831.987 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 390735.68 | 390735.68 | 18.852914 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 203616.92 | 0.00 | 392068.73 | 392068.73 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 71359.017 | 71359.017 | 2.151987 | 0.00062428 | 1884.840 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 71359.02 | 71359.02 | 2.151987 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 50000.15 | 0.00 | 71614.07 | 71614.07 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 8254.258 | 8254.258 | 0.248886 | 0.00007221 | 218.039 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8254.26 | 8254.26 | 0.248886 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00734520 | 46.8595 | 5787.37 | 0.00 | 8283.87 | 8283.87 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 6801.059 | 6801.059 | 0.263274 | 0.00005950 | 163.290 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 6801.06 | 6801.06 | 0.263274 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00744104 | 47.4635 | 4191.08 | 0.00 | 6823.11 | 6823.11 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 11025.507 | 11025.507 | 0.366470 | 0.00009646 | 279.403 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11025.51 | 11025.51 | 0.366470 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00757275 | 48.2930 | 7391.53 | 0.00 | 11059.63 | 11059.63 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 5602.206 | 5602.206 | 0.315165 | 0.00004901 | 122.525 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5602.21 | 5602.21 | 0.315165 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00681507 | 43.5147 | 2481.48 | 0.00 | 5621.62 | 5621.62 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 180196.631 | 180196.631 | 5.449790 | 0.00157644 | 4753.380 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 180196.63 | 180196.63 | 5.449790 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00769206 | 49.0448 | 126144.34 | 0.00 | 180795.90 | 180795.90 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 119690.450 | 119690.450 | 3.620138 | 0.00104710 | 3157.189 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 119690.45 | 119690.45 | 3.620138 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00769680 | 49.0746 | 83784.76 | 0.00 | 120087.72 | 120087.72 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 178497.163 | 178497.163 | 5.398267 | 0.00156157 | 4708.600 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 178497.16 | 178497.16 | 5.398267 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00768729 | 49.0148 | 124956.42 | 0.00 | 179091.14 | 179091.14 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 110399.483 | 110399.483 | 3.338513 | 0.00096582 | 2912.356 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 110399.48 | 110399.48 | 3.338513 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00765165 | 48.7906 | 77290.24 | 0.00 | 110767.67 | 110767.67 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 23181.975 | 23181.975 | 0.701488 | 0.00020281 | 611.361 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 23181.97 | 23181.97 | 0.701488 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00773008 | 49.2843 | 16224.00 | 0.00 | 23257.97 | 23257.97 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 15300.457 | 15300.457 | 0.463016 | 0.00013386 | 403.499 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15300.46 | 15300.46 | 0.463016 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00772834 | 49.2734 | 10707.89 | 0.00 | 15350.55 | 15350.55 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 22997.691 | 22997.691 | 0.695901 | 0.00020119 | 606.506 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 22997.69 | 22997.69 | 0.695901 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00772774 | 49.2696 | 16095.16 | 0.00 | 23073.11 | 23073.11 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 14520.332 | 14520.332 | 0.439368 | 0.00012703 | 382.941 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 14520.33 | 14520.33 | 0.439368 | 12.80 | 11.47 | 0.00800000 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00771170 | 49.1687 | 10162.47 | 0.00 | 14567.99 | 14567.99 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 177365.506 | -999.000 | 9.615465 | 0.00507263 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | 177365.51 | 167604.60 | 9.615465 | 25.43 | 17.02 | 0.00882759 | 11.02 | 11.02 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 26.3970 | 24.00 | 0.00882977 | 46.8323 | 130395.05 | 0.00 | 179489.37 | 163334.43 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 52936.075 | 52936.075 | 2.884639 | 0.00046311 | 874.816 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 52936.07 | 52936.07 | 2.884639 | -2.59 | -2.82 | 0.00293956 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 87.9899 | 21.50 | 0.00540364 | 33.5359 | 19851.46 | 0.00 | 49710.18 | 49710.18 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1664210.665 | -999.000 | 89.129560 | 0.04759621 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 1664210.66 | 1567760.45 | 89.129560 | 25.56 | 17.08 | 0.00884928 | 11.02 | 11.02 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 28.4776 | 24.00 | 0.00886055 | 46.9933 | 1193244.02 | 0.00 | 1683905.65 | 1528184.65 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 501396.287 | 501396.287 | 26.738868 | 0.00438643 | 8269.849 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 10:20:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 501396.29 | 501396.29 | 26.738868 | -2.92 | -3.00 | 0.00295014 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 94.9253 | 21.00 | 0.00777611 | 49.5726 | 494764.71 | 0.00 | 468974.50 | 468974.50 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 181431.074 | -999.000 | 9.869145 | 0.00518891 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 181431.07 | 171584.88 | 9.869145 | 25.39 | 17.00 | 0.00882194 | 11.02 | 11.02 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 25.7184 | 24.00 | 0.00882209 | 46.7921 | 133888.88 | 0.00 | 183610.86 | 167202.75 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 48610.382 | 48610.382 | 2.960743 | 0.00042526 | 810.982 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 48610.38 | 48610.38 | 2.960743 | -0.96 | -1.16 | 0.00340689 | 12.80 | 11.47 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 85.7281 | 19.68 | 0.00767211 | 53.0754 | 58329.12 | 0.00 | 46542.11 | 46542.11 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 103018.584 | -999.000 | 5.645173 | 0.00294632 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 103018.58 | 95167.87 | 5.645173 | 24.95 | 16.95 | 0.00894848 | 11.01 | 11.01 | 0.00850000 | 28.05 | 0.00881933 | 17.90 | 21.2599 | 24.00 | 0.00898815 | 47.6607 | 69296.72 | 0.00 | 104249.92 | 92775.11 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 100000.000 | 100000.000 | 3.082328 | 0.00087484 | 2622.588 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 100000.00 | 100000.00 | 3.082328 | -0.89 | -2.25 | 0.00269032 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 38.9367 | 24.50 | 0.00269032 | 13.9790 | 0.00 | 0.00 | 100078.78 | 100078.78 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 492249.671 | 352652.756 | 24.896957 | 0.01205516 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | 457888.62 | 454821.42 | -999.0 | 28.44 | 17.81 | 0.00854598 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | -999.0000 | 27.00 | 0.00854218 | 37.9332 | 372045.10 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9912.437 | 7181.849 | 0.512790 | 0.00024275 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 9185.55 | 9063.62 | -999.0 | 27.92 | 17.67 | 0.00858897 | 12.80 | 11.97 | 0.00850000 | 25.86 | 0.00881585 | 17.16 | -999.0000 | 27.00 | 0.00858183 | 38.1044 | 8820.68 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 95166.737 | 68949.380 | 4.923067 | 0.00233063 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 88187.66 | 86966.69 | -999.0 | 27.91 | 17.67 | 0.00859280 | 12.80 | 11.97 | 0.00850000 | 25.60 | 0.00881543 | 17.07 | -999.0000 | 27.00 | 0.00858549 | 38.1206 | 84683.08 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9656.193 | 6995.116 | 0.499398 | 0.00023648 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 8948.48 | 8826.64 | -999.0 | 27.92 | 17.67 | 0.00859128 | 12.80 | 11.97 | 0.00850000 | 25.86 | 0.00881585 | 17.16 | -999.0000 | 27.00 | 0.00858403 | 38.1141 | 8590.29 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 492249.671 | 492249.671 | 24.896957 | 0.01205516 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 492249.67 | 492249.67 | 24.896957 | -4.20 | -4.20 | 0.00269032 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 1.3592 | 27.00 | 0.00850000 | 37.7427 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9912.437 | 9912.437 | 0.512790 | 0.00024275 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9912.44 | 9912.44 | 0.512790 | -4.20 | -4.20 | 0.00269032 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.0485 | 26.93 | 0.00850000 | 37.8921 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 95166.737 | 95166.737 | 4.923067 | 0.00233063 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 95166.74 | 95166.74 | 4.923067 | -4.20 | -4.20 | 0.00269032 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.1753 | 24.60 | 0.00552641 | 28.4195 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9656.193 | 9656.193 | 0.499398 | 0.00023648 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9656.19 | 9656.19 | 0.499398 | -4.20 | -4.20 | 0.00269032 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.1302 | 23.56 | 0.00301667 | 16.5813 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 17840.032 | 17840.032 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 17840.03 | 17840.03 | 24.896957 | -0.06 | -0.06 | 0.00842104 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 1.3592 | 27.00 | 0.00850000 | 37.7427 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 824.136 | 824.136 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 824.14 | 824.14 | 0.512790 | -0.13 | -0.13 | 0.00832289 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.0485 | 26.93 | 0.00850000 | 37.8921 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 8241.356 | 8241.356 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 8241.36 | 8241.36 | 4.923067 | -0.13 | -0.13 | 0.00543635 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.1753 | 24.60 | 0.00552641 | 28.4195 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 824.136 | 824.136 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 824.14 | 824.14 | 0.499398 | -0.13 | -1.32 | 0.00300645 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.1302 | 23.56 | 0.00301667 | 16.5813 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 19161.949 | 19161.949 | 1.930639 | 0.00016764 | 386.290 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.45121345 | 54.44 | 82.22 | 27.78 | 1918515.76 | 0.9988 | 1.018891 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:40:00 | Sensible | 19161.95 | 19161.95 | 1.0000 | 2.29165092 | 1.930639 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.16761999 | 60.00 | 32.22 | 27.78 | 0.000 | 19161.95 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 19232.60 | 19232.60 | 2.29165092 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 390735.675 | 390735.675 | 18.852914 | 0.00341833 | 8831.987 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.45121345 | 54.44 | 82.22 | 27.78 | 1918515.76 | 20.3666 | 20.776446 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 390735.68 | 390735.68 | 1.0000 | 22.37823462 | 18.852914 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 3.41797744 | 60.00 | 32.22 | 27.78 | 0.000 | 390735.68 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 203616.92 | 0.00 | 392068.73 | 392068.73 | 22.37823462 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 29.98 | 18.03 | 0.00800000 | 50579.9 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 71359.017 | 71359.017 | 2.151987 | 0.00062428 | 1884.840 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.45121345 | 54.44 | 82.22 | 27.78 | 1918515.76 | 3.7195 | 3.794347 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 71359.02 | 71359.02 | 1.0000 | 2.55438857 | 2.151987 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.62421613 | 60.00 | 32.22 | 27.78 | 0.000 | 71359.02 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 50000.15 | 0.00 | 71614.07 | 71614.07 | 2.55438857 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.29 | 21.27 | 0.00800000 | 61095.5 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8254.258 | 8254.258 | 0.248886 | 0.00007221 | 218.039 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.45121345 | 54.44 | 82.22 | 27.78 | 1918515.76 | 0.4302 | 0.438901 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8254.26 | 8254.26 | 1.0000 | 0.29542578 | 0.248886 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.07220449 | 60.00 | 32.22 | 27.78 | 0.000 | 8254.26 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.92 | 0.00734520 | 21.00 | 0.00734520 | 46.8595 | 5787.37 | 0.00 | 8283.87 | 8283.87 | 0.29542578 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.30 | 21.27 | 0.00800000 | 61100.3 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6801.059 | 6801.059 | 0.263274 | 0.00005950 | 163.290 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.45121345 | 54.44 | 82.22 | 27.78 | 1918515.76 | 0.3545 | 0.361630 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 6801.06 | 6801.06 | 1.0000 | 0.31250426 | 0.263274 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.05949257 | 60.00 | 32.22 | 27.78 | 0.000 | 6801.06 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00744104 | 21.00 | 0.00744104 | 47.4635 | 4191.08 | 0.00 | 6823.11 | 6823.11 | 0.31250426 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 34.21 | 19.41 | 0.00800000 | 54893.5 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11025.507 | 11025.507 | 0.366470 | 0.00009646 | 279.403 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.45121345 | 54.44 | 82.22 | 27.78 | 1918515.76 | 0.5747 | 0.586255 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 11025.51 | 11025.51 | 1.0000 | 0.43499680 | 0.366470 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.09644610 | 60.00 | 32.22 | 27.78 | 0.000 | 11025.51 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00757275 | 21.00 | 0.00757275 | 48.2930 | 7391.53 | 0.00 | 11059.63 | 11059.63 | 0.43499680 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 37.73 | 20.50 | 0.00800000 | 58484.5 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5602.206 | 5602.206 | 0.315165 | 0.00004901 | 122.525 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.45121345 | 54.44 | 82.22 | 27.78 | 1918515.76 | 0.2920 | 0.297884 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 5602.21 | 5602.21 | 1.0000 | 0.37409744 | 0.315165 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.04900554 | 60.00 | 32.22 | 27.78 | 0.000 | 5602.21 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.87 | 0.00681507 | 21.00 | 0.00681507 | 43.5147 | 2481.48 | 0.00 | 5621.62 | 5621.62 | 0.37409744 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 27.54 | 17.20 | 0.00800000 | 48087.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 180196.631 | 180196.631 | 5.449790 | 0.00157644 | 4753.380 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.45121345 | 54.44 | 82.22 | 27.78 | 1918515.76 | 9.3925 | 9.581530 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 180196.63 | 180196.63 | 1.0000 | 6.46885074 | 5.449790 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 1.57627793 | 60.00 | 32.22 | 27.78 | 0.000 | 180196.63 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00769206 | 21.00 | 0.00769206 | 49.0448 | 126144.34 | 0.00 | 180795.90 | 180795.90 | 6.46885074 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61008.5 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 119690.450 | 119690.450 | 3.620138 | 0.00104710 | 3157.189 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.45121345 | 54.44 | 82.22 | 27.78 | 1918515.76 | 6.2387 | 6.364257 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 119690.45 | 119690.45 | 1.0000 | 4.29707075 | 3.620138 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 1.04699746 | 60.00 | 32.22 | 27.78 | 0.000 | 119690.45 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00769680 | 21.00 | 0.00769680 | 49.0746 | 83784.76 | 0.00 | 120087.72 | 120087.72 | 4.29707075 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61006.2 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 178497.163 | 178497.163 | 5.398267 | 0.00156157 | 4708.600 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.45121345 | 54.44 | 82.22 | 27.78 | 1918515.76 | 9.3039 | 9.491165 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 178497.16 | 178497.16 | 1.0000 | 6.40769318 | 5.398267 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 1.56141175 | 60.00 | 32.22 | 27.78 | 0.000 | 178497.16 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00768729 | 21.00 | 0.00768729 | 49.0148 | 124956.42 | 0.00 | 179091.14 | 179091.14 | 6.40769318 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61009.2 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 110399.483 | 110399.483 | 3.338513 | 0.00096582 | 2912.356 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.45121345 | 54.44 | 82.22 | 27.78 | 1918515.76 | 5.7544 | 5.870232 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 110399.48 | 110399.48 | 1.0000 | 3.96278402 | 3.338513 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.96572432 | 60.00 | 32.22 | 27.78 | 0.000 | 110399.48 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00765165 | 21.00 | 0.00765165 | 48.7906 | 77290.24 | 0.00 | 110767.67 | 110767.67 | 3.96278402 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61011.8 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23181.975 | 23181.975 | 0.701488 | 0.00020281 | 611.361 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.45121345 | 54.44 | 82.22 | 27.78 | 1918515.76 | 1.2083 | 1.232647 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 23181.97 | 23181.97 | 1.0000 | 0.83266025 | 0.701488 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.20278534 | 60.00 | 32.22 | 27.78 | 0.000 | 23181.97 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00773008 | 21.00 | 0.00773008 | 49.2843 | 16224.00 | 0.00 | 23257.97 | 23257.97 | 0.83266025 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60992.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15300.457 | 15300.457 | 0.463016 | 0.00013386 | 403.499 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.45121345 | 54.44 | 82.22 | 27.78 | 1918515.76 | 0.7975 | 0.813566 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 15300.46 | 15300.46 | 1.0000 | 0.54959517 | 0.463016 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.13384142 | 60.00 | 32.22 | 27.78 | 0.000 | 15300.46 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00772834 | 21.00 | 0.00772834 | 49.2734 | 10707.89 | 0.00 | 15350.55 | 15350.55 | 0.54959517 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60990.5 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22997.691 | 22997.691 | 0.695901 | 0.00020119 | 606.506 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.45121345 | 54.44 | 82.22 | 27.78 | 1918515.76 | 1.1987 | 1.222848 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 22997.69 | 22997.69 | 1.0000 | 0.82602813 | 0.695901 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.20117331 | 60.00 | 32.22 | 27.78 | 0.000 | 22997.69 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00772774 | 21.00 | 0.00772774 | 49.2696 | 16095.16 | 0.00 | 23073.11 | 23073.11 | 0.82602813 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60992.4 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14520.332 | 14520.332 | 0.439368 | 0.00012703 | 382.941 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 16.45121345 | 54.44 | 82.22 | 27.78 | 1918515.76 | 0.7569 | 0.772084 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 14520.33 | 14520.33 | 1.0000 | 0.52152568 | 0.439368 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.12701724 | 60.00 | 32.22 | 27.78 | 0.000 | 14520.33 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00771170 | 21.00 | 0.00771170 | 49.1687 | 10162.47 | 0.00 | 14567.99 | 14567.99 | 0.52152568 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60993.2 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 177365.506 | -999.000 | 9.615465 | 0.00507263 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2500 | 1004.8586 | 1.1870 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.615465 | 11.41346784 | 4197.9300 | 999.8980 | 60.79786693 | 15.00 | 6.67 | 8.33 | 2126025.83 | 8.3426 | 8.342585 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | Sensible | 177365.51 | 167604.60 | 1.0000 | 11.41346784 | 9.615465 | 25.43 | 17.02 | 0.00882759 | 48042.8 | 11.02 | 11.02 | 0.00850000 | 32502.8 | 5.07211355 | 6.67 | 15.00 | 8.33 | 20778.507 | 156587.00 | 29.40 | 0.00882150 | 18.34 | 2.53819000 | 26.3970 | 24.00 | 0.00882977 | 24.00 | 0.00882977 | 46.8323 | 130395.05 | 0.00 | 179489.37 | 163334.43 | 11.41346784 | 25.43 | 17.17 | 0.00882759 | 48042.8 | 11.41 | 11.28 | 0.00826639 | 32316.7 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 52936.075 | 52936.075 | 2.884639 | 0.00046311 | 874.816 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.615465 | 11.41346784 | 4197.9300 | 999.8980 | 16.45121345 | 54.44 | 82.22 | 27.78 | 1918515.76 | 2.7592 | 2.814751 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 52936.07 | 52936.07 | 1.0000 | 3.42404035 | 2.884639 | -2.59 | -2.82 | 0.00293956 | 4739.7 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 0.46306063 | 60.00 | 32.22 | 27.78 | 0.000 | 52936.07 | -4.20 | 0.00269032 | -4.20 | 2.53819000 | 87.9899 | 9.24 | 0.00476558 | 21.50 | 0.00540364 | 33.5359 | 19851.46 | 0.00 | 49710.18 | 49710.18 | 3.42404035 | 2.80 | 0.44 | 0.00293956 | 10180.5 | 17.17 | 8.02 | 0.00293956 | 24698.5 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1664210.665 | -999.000 | 89.129560 | 0.04759621 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2904 | 1004.8586 | 1.1870 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 89.129560 | 105.79596611 | 4197.9300 | 999.8980 | 60.79786693 | 15.00 | 6.67 | 8.33 | 2126025.83 | 78.2780 | 78.278008 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 1664210.66 | 1567760.45 | 1.0000 | 105.79596611 | 89.129560 | 25.56 | 17.08 | 0.00884928 | 48233.2 | 11.02 | 11.02 | 0.00850000 | 32502.8 | 47.59135904 | 6.67 | 15.00 | 8.33 | 192604.232 | 1471606.43 | 29.40 | 0.00882150 | 18.34 | 25.38195000 | 28.4776 | 24.00 | 0.00886055 | 24.00 | 0.00886055 | 46.9933 | 1193244.02 | 0.00 | 1683905.65 | 1528184.65 | 105.79596611 | 25.56 | 17.23 | 0.00884928 | 48233.2 | 11.41 | 11.28 | 0.00826569 | 32316.7 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 501396.287 | 501396.287 | 26.738868 | 0.00438643 | 8269.849 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 89.129560 | 105.79596611 | 4197.9300 | 999.8980 | 16.45121345 | 54.44 | 82.22 | 27.78 | 1918515.76 | 26.1346 | 26.660562 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 10:20:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 501396.29 | 501396.29 | 1.0000 | 31.73878983 | 26.738868 | -2.92 | -3.00 | 0.00295014 | 4426.8 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 4.38598598 | 60.00 | 32.22 | 27.78 | 0.000 | 501396.29 | -4.20 | 0.00269032 | -4.20 | 25.38195000 | 94.9253 | 21.00 | 0.00781026 | 21.00 | 0.00777611 | 49.5726 | 494764.71 | 0.00 | 468974.50 | 468974.50 | 31.73878983 | 2.80 | 0.45 | 0.00295014 | 10207.0 | 17.43 | 8.16 | 0.00295014 | 24983.1 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 181431.074 | -999.000 | 9.869145 | 0.00518891 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2395 | 1004.8586 | 1.1870 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.869145 | 11.71458371 | 4197.9300 | 999.8980 | 60.79786693 | 15.00 | 6.67 | 8.33 | 2126025.83 | 8.5338 | 8.533813 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 181431.07 | 171584.88 | 1.0000 | 11.71458371 | 9.869145 | 25.39 | 17.00 | 0.00882194 | 47990.4 | 11.02 | 11.02 | 0.00850000 | 32502.7 | 5.18837644 | 6.67 | 15.00 | 8.33 | 21326.696 | 160104.38 | 29.40 | 0.00882150 | 18.34 | 2.53819000 | 25.7184 | 24.00 | 0.00882209 | 24.00 | 0.00882209 | 46.7921 | 133888.88 | 0.00 | 183610.86 | 167202.75 | 11.71458371 | 25.39 | 17.15 | 0.00882194 | 47990.4 | 11.41 | 11.28 | 0.00826660 | 32316.7 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 48610.382 | 48610.382 | 2.960743 | 0.00042526 | 810.982 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.869145 | 11.71458371 | 4197.9300 | 999.8980 | 16.45121345 | 54.44 | 82.22 | 27.78 | 1918515.76 | 2.5337 | 2.584742 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 48610.38 | 48610.38 | 1.0000 | 3.51437511 | 2.960743 | -0.96 | -1.16 | 0.00340689 | 7544.6 | 12.80 | 11.47 | 0.00800000 | 33059.8 | 0.42522145 | 60.00 | 32.22 | 27.78 | 0.000 | 48610.38 | -4.20 | 0.00269032 | -4.20 | 2.53819000 | 85.7281 | 18.47 | 0.00771116 | 19.68 | 0.00767211 | 53.0754 | 58329.12 | 0.00 | 46542.11 | 46542.11 | 3.51437511 | 2.80 | 1.11 | 0.00340689 | 11351.7 | 15.90 | 7.97 | 0.00340689 | 24595.1 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 103018.584 | -999.000 | 5.645173 | 0.00294632 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4748 | 1004.8586 | 1.1870 | CAV_BAS FAN | Fan:VariableVolume | 5.645173 | 6.70076831 | 4197.9300 | 999.8980 | 60.79786693 | 15.00 | 6.67 | 8.33 | 2126025.83 | 4.8456 | 4.845594 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 103018.58 | 95167.87 | 1.0000 | 6.70076831 | 5.645173 | 24.95 | 16.95 | 0.00894848 | 47865.6 | 11.01 | 11.01 | 0.00850000 | 32491.4 | 2.94601789 | 6.67 | 15.00 | 8.33 | 12277.621 | 90740.96 | 28.05 | 0.00881933 | 17.90 | 1.20015641 | 21.2599 | 24.00 | 0.00898815 | 24.00 | 0.00898815 | 47.6607 | 69296.72 | 0.00 | 104249.92 | 92775.11 | 6.70076831 | 24.95 | 17.10 | 0.00894848 | 47865.6 | 11.40 | 11.28 | 0.00826951 | 32307.7 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.082328 | 0.00087484 | 2622.588 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | CAV_BAS FAN | Fan:VariableVolume | 5.645173 | 6.70076831 | 4197.9300 | 999.8980 | 16.45121345 | 54.44 | 82.22 | 27.78 | 1918515.76 | 5.2124 | 5.317264 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.082328 | -0.89 | -2.25 | 0.00269032 | 5826.6 | 40.00 | 21.01 | 0.00800000 | 60796.0 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | -4.20 | 0.00269032 | -4.20 | 1.20015641 | 38.9367 | 0.00 | 0.00269032 | 24.50 | 0.00269032 | 13.9790 | 0.00 | 0.00 | 100078.78 | 100078.78 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.02 | 14.59 | 0.00000000 | 40240.9 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 492249.671 | 352652.756 | 24.896957 | 0.01205516 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7266 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | Sensible | 457888.62 | 454821.42 | 0.9302 | -999.0 | -999.0 | 28.44 | 17.81 | 0.00854598 | 50405.6 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 457888.62 | 29.40 | 0.00882150 | 18.34 | 0.33839277 | -999.0000 | 27.00 | 0.00854218 | 27.00 | 0.00854218 | 37.9332 | 372045.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9912.437 | 7181.849 | 0.512790 | 0.00024275 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8065 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | Sensible | 9185.55 | 9063.62 | 0.9267 | -999.0 | -999.0 | 27.92 | 17.67 | 0.00858897 | 49984.8 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9185.55 | 25.86 | 0.00881585 | 17.16 | 0.01563234 | -999.0000 | 27.00 | 0.00858183 | 27.00 | 0.00858183 | 38.1044 | 8820.68 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 95166.737 | 68949.380 | 4.923067 | 0.00233063 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8136 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | Sensible | 88187.66 | 86966.69 | 0.9267 | -999.0 | -999.0 | 27.91 | 17.67 | 0.00859280 | 49984.6 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 88187.66 | 25.60 | 0.00881543 | 17.07 | 0.15632344 | -999.0000 | 27.00 | 0.00858549 | 27.00 | 0.00858549 | 38.1206 | 84683.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9656.193 | 6995.116 | 0.499398 | 0.00023648 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8108 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | Sensible | 8948.48 | 8826.64 | 0.9267 | -999.0 | -999.0 | 27.92 | 17.67 | 0.00859128 | 49989.7 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8948.48 | 25.86 | 0.00881585 | 17.16 | 0.01563234 | -999.0000 | 27.00 | 0.00858403 | 27.00 | 0.00858403 | 38.1141 | 8590.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 492249.671 | 492249.671 | 24.896957 | 0.01205516 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 492249.67 | 492249.67 | 1.0000 | 29.55245881 | 24.896957 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 492249.67 | -4.20 | 0.00269032 | -4.20 | 0.33839277 | 1.3592 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.7427 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9912.437 | 9912.437 | 0.512790 | 0.00024275 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9912.44 | 9912.44 | 1.0000 | 0.60867673 | 0.512790 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9912.44 | -4.20 | 0.00269032 | -4.20 | 0.01563234 | 3.0485 | 0.00 | 0.00850000 | 26.93 | 0.00850000 | 37.8921 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 95166.737 | 95166.737 | 4.923067 | 0.00233063 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 95166.74 | 95166.74 | 1.0000 | 5.84363568 | 4.923067 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 95166.74 | -4.20 | 0.00269032 | -4.20 | 0.15632344 | 3.1753 | 0.00 | 0.00552641 | 24.60 | 0.00552641 | 28.4195 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9656.193 | 9656.193 | 0.499398 | 0.00023648 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9656.19 | 9656.19 | 1.0000 | 0.59278036 | 0.499398 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9656.19 | -4.20 | 0.00269032 | -4.20 | 0.01563234 | 3.1302 | 0.00 | 0.00301667 | 23.56 | 0.00301667 | 16.5813 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17840.032 | 17840.032 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 24.896957 | 29.55245881 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 17840.03 | 17840.03 | 1.0000 | 29.55245881 | 24.896957 | -0.06 | -0.06 | 0.00842104 | 21002.3 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17840.03 | -4.20 | 0.00269032 | -4.20 | 0.33839277 | 1.3592 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.7427 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 824.136 | 824.136 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.512790 | 0.60867673 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 824.14 | 824.14 | 1.0000 | 0.60867673 | 0.512790 | -0.13 | -0.13 | 0.00832289 | 20684.4 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 824.14 | -4.20 | 0.00269032 | -4.20 | 0.01563234 | 3.0485 | 0.00 | 0.00850000 | 26.93 | 0.00850000 | 37.8921 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8241.356 | 8241.356 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.923067 | 5.84363568 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 8241.36 | 8241.36 | 1.0000 | 5.84363568 | 4.923067 | -0.13 | -0.13 | 0.00543635 | 13460.6 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8241.36 | -4.20 | 0.00269032 | -4.20 | 0.15632344 | 3.1753 | 0.00 | 0.00552641 | 24.60 | 0.00552641 | 28.4195 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 824.136 | 824.136 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.499398 | 0.59278036 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 824.14 | 824.14 | 1.0000 | 0.59278036 | 0.499398 | -0.13 | -1.32 | 0.00300645 | 7386.1 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 824.14 | -4.20 | 0.00269032 | -4.20 | 0.01563234 | 3.1302 | 0.00 | 0.00301667 | 23.56 | 0.00301667 | 16.5813 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 9.62 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 89.13 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 9.87 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 5.65 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 24.90 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 3136.67 | 206.00 | 74.83 |
CORE_BOTTOM | 2646.50 | 414.83 | 12.83 |
CORE_MID | 1318.17 | 2581.33 | 12.00 |
CORE_TOP | 1361.50 | 3713.33 | 360.33 |
PERIMETER_BOT_ZN_3 | 1483.33 | 2978.00 | 24.83 |
PERIMETER_BOT_ZN_2 | 1678.67 | 3384.33 | 79.33 |
PERIMETER_BOT_ZN_1 | 2105.00 | 2994.67 | 136.67 |
PERIMETER_BOT_ZN_4 | 2927.67 | 1816.33 | 154.00 |
PERIMETER_MID_ZN_3 | 1649.83 | 4195.00 | 819.50 |
PERIMETER_MID_ZN_2 | 1746.00 | 3546.83 | 779.17 |
PERIMETER_MID_ZN_1 | 2165.33 | 3592.17 | 559.50 |
PERIMETER_MID_ZN_4 | 1984.17 | 3978.67 | 626.17 |
PERIMETER_TOP_ZN_3 | 2259.50 | 4512.83 | 1520.00 |
PERIMETER_TOP_ZN_2 | 2607.17 | 4183.17 | 1421.00 |
PERIMETER_TOP_ZN_1 | 2530.17 | 3926.83 | 1106.33 |
PERIMETER_TOP_ZN_4 | 2405.17 | 4284.00 | 1202.83 |
DATACENTER_BOT_ZN_6 | 5943.00 | 829.17 | 829.17 |
DATACENTER_MID_ZN_6 | 5851.00 | 166.00 | 151.67 |
DATACENTER_TOP_ZN_6 | 5542.83 | 355.00 | 233.67 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5766.17 | 5766.17 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 834.00 | 0.00 | 408.33 |
CORE_BOTTOM | 0.00 | 1.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 3.67 | 0.00 | 0.50 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 12.00 | 0.00 | 12.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 24.33 | 0.00 | 24.33 |
PERIMETER_BOT_ZN_4 | 0.00 | 57.67 | 0.00 | 27.67 |
PERIMETER_MID_ZN_3 | 3.00 | 0.00 | 0.33 | 0.00 |
PERIMETER_MID_ZN_2 | 2.67 | 12.33 | 0.00 | 12.33 |
PERIMETER_MID_ZN_1 | 1.17 | 21.00 | 0.00 | 20.83 |
PERIMETER_MID_ZN_4 | 0.83 | 22.17 | 0.00 | 12.33 |
PERIMETER_TOP_ZN_3 | 50.33 | 0.00 | 12.33 | 0.00 |
PERIMETER_TOP_ZN_2 | 31.83 | 12.17 | 2.67 | 12.17 |
PERIMETER_TOP_ZN_1 | 19.17 | 15.83 | 1.00 | 15.50 |
PERIMETER_TOP_ZN_4 | 13.00 | 21.67 | 0.67 | 12.33 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 53.83 | 959.67 | 12.50 | 505.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.22 | 149.60 | 6779.02 | 1.322 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.88 | 134.35 | 6849.35 | 1.090 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.88 | 134.35 | 6849.35 | 0.796 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.88 | 134.35 | 6849.35 | 0.747 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.02 | 16.87 | 860.00 | 0.973 | 0.018 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.52 | 10.87 | 554.22 | 1.521 | 0.019 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.02 | 16.87 | 860.02 | 1.631 | 0.018 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.52 | 10.87 | 554.22 | 2.123 | 0.019 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.02 | 16.87 | 860.00 | 0.757 | 0.043 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.95 | 10.87 | 554.22 | 1.326 | 0.047 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.02 | 16.87 | 860.02 | 1.520 | 0.043 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.52 | 10.87 | 554.22 | 1.528 | 0.044 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.02 | 16.87 | 860.00 | 0.749 | 0.053 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.52 | 10.87 | 554.22 | 1.411 | 0.055 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.02 | 16.87 | 860.02 | 1.496 | 0.053 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.52 | 10.87 | 554.22 | 1.542 | 0.055 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.54 | 42.18 | 1911.37 | 28.970 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.22 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.88 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.95 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.02 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.02 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.52 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.54 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.22 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.88 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.88 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.88 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.02 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.02 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.02 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.95 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.02 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.02 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.02 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.52 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.54 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1031.21 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 52082628.80 | 0.00 | 52082628.80 | 0.00 | 52082628.80 | 37848132.68 | 4500.28 | 302.28 | 3957.44 | 0.00 |
CORE_BOTTOM | 45479438.46 | 0.00 | 45479438.46 | 0.00 | 45479438.46 | 33990283.35 | 4100.37 | 40.74 | 4618.89 | 324.89 |
CORE_MID | 0.32E+09 | 0.00 | 0.32E+09 | 0.00 | 0.32E+09 | 0.34E+09 | 5237.83 | 59.72 | 3462.45 | 131.91 |
CORE_TOP | 30359182.41 | 0.00 | 30359182.41 | 0.00 | 30359182.41 | 33990283.35 | 5667.67 | 46.27 | 3046.06 | 197.04 |
PERIMETER_BOT_ZN_3 | 5103816.05 | 0.00 | 5103816.05 | 189059.25 | 5292875.30 | 4267819.30 | 4779.41 | 75.14 | 3905.45 | 324.89 |
PERIMETER_BOT_ZN_2 | 5167416.59 | 0.00 | 5167416.59 | 126039.41 | 5293456.00 | 2750345.05 | 3537.87 | 2.54 | 5219.60 | 324.89 |
PERIMETER_BOT_ZN_1 | 8525769.88 | 0.00 | 8525769.88 | 189059.25 | 8714829.13 | 4267912.63 | 3545.68 | 3.23 | 5211.08 | 324.89 |
PERIMETER_BOT_ZN_4 | 7192315.58 | 0.00 | 7192315.58 | 126039.41 | 7318354.99 | 2750345.05 | 3533.30 | 0.00 | 5226.70 | 324.89 |
PERIMETER_MID_ZN_3 | 38776836.24 | 0.00 | 38776836.24 | 443394.83 | 39220231.08 | 42678193.03 | 5363.79 | 65.02 | 3331.19 | 131.91 |
PERIMETER_MID_ZN_2 | 47712549.66 | 0.00 | 47712549.66 | 295596.35 | 48008146.02 | 27503450.52 | 3854.97 | 1.47 | 4903.56 | 1040.91 |
PERIMETER_MID_ZN_1 | 77516721.81 | 0.00 | 77516721.81 | 443394.83 | 77960116.65 | 42679126.28 | 3884.31 | 6.27 | 4869.42 | 131.91 |
PERIMETER_MID_ZN_4 | 50605671.98 | 0.00 | 50605671.98 | 295596.35 | 50901268.33 | 27503450.52 | 3851.29 | 2.57 | 4906.14 | 131.91 |
PERIMETER_TOP_ZN_3 | 3834429.84 | 0.00 | 3834429.84 | 550519.38 | 4384949.22 | 4267819.30 | 5541.65 | 65.44 | 3152.91 | 197.04 |
PERIMETER_TOP_ZN_2 | 4643581.11 | 0.00 | 4643581.11 | 367012.67 | 5010593.78 | 2750345.05 | 3975.71 | 7.23 | 4777.05 | 197.04 |
PERIMETER_TOP_ZN_1 | 7620252.02 | 0.00 | 7620252.02 | 550519.38 | 8170771.40 | 4267912.63 | 3999.35 | 3.66 | 4756.99 | 197.04 |
PERIMETER_TOP_ZN_4 | 5100852.09 | 0.00 | 5100852.09 | 367012.67 | 5467864.76 | 2750345.05 | 3953.51 | 6.19 | 4800.31 | 197.04 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.45E+09 | 0.00 | 0.45E+09 | 0.00 | 0.45E+09 | 10671554.30 | 9.00 | 60.17 | 8690.83 | 2816.67 |
Total Facility | 0.60E+10 | 0.00 | 0.60E+10 | 17245085.19 | 0.61E+10 | 0.50E+10 | 6069.12 | 4394.52 | 8751.44 | 3725.67 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.4344 | 0.0000 | 2.4344 | 0.0000 | 2.4344 | 1.2002 | 1683.28 | 302.28 | 3957.44 |
CORE_BOTTOM | 2.0286 | 0.0000 | 2.0286 | 0.0000 | 2.0286 | 1.0778 | 1567.13 | 38.17 | 4337.70 |
CORE_MID | 14.8238 | 0.0000 | 14.8238 | 0.0000 | 14.8238 | 10.7782 | 2513.26 | 59.72 | 3370.02 |
CORE_TOP | 1.3922 | 0.0000 | 1.3922 | 0.0000 | 1.3922 | 1.0778 | 2907.11 | 46.27 | 2989.62 |
PERIMETER_BOT_ZN_3 | 0.2275 | 0.0000 | 0.2275 | 0.0043 | 0.2317 | 0.1353 | 2243.16 | 72.04 | 3627.80 |
PERIMETER_BOT_ZN_2 | 0.2295 | 0.0000 | 0.2295 | 0.0029 | 0.2323 | 0.0872 | 1045.76 | 2.54 | 4894.71 |
PERIMETER_BOT_ZN_1 | 0.3817 | 0.0000 | 0.3817 | 0.0043 | 0.3860 | 0.1353 | 1052.48 | 2.84 | 4887.68 |
PERIMETER_BOT_ZN_4 | 0.3198 | 0.0000 | 0.3198 | 0.0029 | 0.3227 | 0.0872 | 1041.19 | 0.00 | 4901.81 |
PERIMETER_MID_ZN_3 | 1.7727 | 0.0000 | 1.7727 | 0.0101 | 1.7828 | 1.3533 | 2640.76 | 64.90 | 3237.34 |
PERIMETER_MID_ZN_2 | 2.0037 | 0.0000 | 2.0037 | 0.0071 | 2.0108 | 0.8721 | 1159.54 | 1.03 | 3873.44 |
PERIMETER_MID_ZN_1 | 3.5602 | 0.0000 | 3.5602 | 0.0101 | 3.5703 | 1.3533 | 1177.57 | 4.26 | 4761.18 |
PERIMETER_MID_ZN_4 | 2.3073 | 0.0000 | 2.3073 | 0.0067 | 2.3140 | 0.8721 | 1157.63 | 1.04 | 4784.32 |
PERIMETER_TOP_ZN_3 | 0.1757 | 0.0000 | 0.1757 | 0.0125 | 0.1882 | 0.1353 | 2784.41 | 65.07 | 3093.51 |
PERIMETER_TOP_ZN_2 | 0.2132 | 0.0000 | 0.2132 | 0.0083 | 0.2216 | 0.0872 | 1242.92 | 4.58 | 4695.50 |
PERIMETER_TOP_ZN_1 | 0.3506 | 0.0000 | 0.3506 | 0.0125 | 0.3631 | 0.1353 | 1257.61 | 2.68 | 4682.71 |
PERIMETER_TOP_ZN_4 | 0.2331 | 0.0000 | 0.2331 | 0.0083 | 0.2414 | 0.0872 | 1228.19 | 4.06 | 4710.76 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 14.8993 | 0.0000 | 14.8993 | 0.0000 | 14.8993 | 0.3384 | 8.67 | 60.17 | 5874.17 |
Total Facility | 268.7272 | 0.0000 | 268.7272 | 0.3961 | 269.1233 | 158.4706 | 3252.12 | 4380.77 | 5934.77 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 0.10E+09 | 0.00 | 0.10E+09 | 48026705.38 | 3537.69 | 0.58 | 5221.73 | 324.89 |
VAV_MID WITH REHEAT | 0.76E+09 | 0.00 | 0.76E+09 | 0.48E+09 | 3879.51 | 5.47 | 4875.01 | 131.91 |
VAV_TOP WITH REHEAT | 72642914.34 | 0.00 | 72642914.34 | 48026705.38 | 4002.43 | 4.38 | 4753.20 | 197.04 |
CAV_BAS | 73381671.24 | 0.00 | 73381671.24 | 37848132.68 | 4498.14 | 0.75 | 4261.11 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.64E+09 | 0.00 | 0.64E+09 | 10671554.30 | 9.00 | 0.00 | 8751.00 | 2816.67 |
AIRLOOP DATACENTER BOT | 344200.17 | 0.00 | 344200.17 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3442001.72 | 0.00 | 3442001.72 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 344200.17 | 0.00 | 344200.17 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 4.4904 | 0.0000 | 4.4904 | 1.5229 | 1045.58 | 0.58 | 4896.84 |
VAV_MID WITH REHEAT | 34.7281 | 0.0000 | 34.7281 | 15.2292 | 1174.93 | 3.45 | 4764.61 |
VAV_TOP WITH REHEAT | 3.3320 | 0.0000 | 3.3320 | 1.5229 | 1258.45 | 2.98 | 4681.57 |
CAV_BAS | 3.4299 | 0.0000 | 3.4299 | 1.2002 | 1681.14 | 0.75 | 4261.11 |
AIRLOOP DATACENTER BASEMENT | 20.9924 | 0.0000 | 20.9924 | 0.3384 | 8.67 | 0.00 | 5934.33 |
AIRLOOP DATACENTER BOT | 0.0161 | 0.0000 | 0.0161 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1609 | 0.0000 | 0.1609 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0161 | 0.0000 | 0.0161 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.28 | 4670.56 | 0.00 | 0.00 | 0.00 | 555.86 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.22 | 3995.44 | 0.00 | 0.00 | 0.00 | 931.76 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.17 | 3571.56 | 0.00 | 0.00 | 0.00 | 1430.05 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 297.50 | 3962.22 | 0.00 | 12.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 60.17 | 8690.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 5.8354 | 0.0000 | 0.0000 | 0.0000 | 2.3923 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 47.7246 | 0.0000 | 0.0000 | 0.0000 | 23.6317 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 4.8811 | 0.0000 | 0.0000 | 0.0000 | 2.3291 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.6938 | 5.0149 | 0.0000 | 0.9635 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4781 | 21.2341 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0220 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2203 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0220 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1492 |
Defaulted Fields | 1184 |
Fields with Defaults | 3877 |
Autosized Fields | 334 |
Autosizable Fields | 413 |
Autocalculated Fields | 227 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 26263.87 | 295321.99 | 29-MAY-04:40 | 2113943.05 | 29-AUG-15:10 |
Electricity:Building | 17912.36 | 217189.06 | 07-MAY-17:20 | 1104084.83 | 01-DEC-16:20 |
Electricity:Zone:BASEMENT | 640.57 | 14055.89 | 01-JAN-00:10 | 32859.63 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 17912.36 | 217189.06 | 07-MAY-17:20 | 1104084.83 | 01-DEC-16:20 |
InteriorLights:Electricity | 3235.96 | 9932.90 | 23-APR-17:20 | 325713.14 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 216.17 | 598.35 | 01-JAN-00:10 | 19402.09 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3235.96 | 9932.90 | 23-APR-17:20 | 325713.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 3235.96 | 9932.90 | 23-APR-17:20 | 325713.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 216.17 | 598.35 | 01-JAN-00:10 | 19402.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3235.96 | 9932.90 | 23-APR-17:20 | 325713.14 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 483.75 | 4990.59 | 01-JAN-00:10 | 34631.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4837.49 | 49905.77 | 01-JAN-00:10 | 346310.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1941.37 | 5373.60 | 01-JAN-00:10 | 174244.37 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1941.37 | 5373.60 | 01-JAN-00:10 | 174244.37 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 483.75 | 4990.58 | 01-JAN-00:10 | 34631.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 50.96 | 617.00 | 09-APR-17:10 | 4348.36 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 14.60 | 57.83 | 08-JAN-11:10 | 2187.81 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 14.60 | 57.83 | 08-JAN-11:10 | 2187.81 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 32.69 | 397.62 | 23-APR-17:10 | 2802.25 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 9.25 | 37.27 | 01-JAN-10:10 | 1409.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 9.25 | 37.27 | 01-JAN-10:10 | 1409.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 50.52 | 617.01 | 19-MAR-17:10 | 4348.44 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 14.15 | 57.83 | 01-JAN-10:00 | 2187.86 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 14.15 | 57.83 | 01-JAN-10:00 | 2187.86 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 32.67 | 397.61 | 19-MAR-17:10 | 2802.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 9.24 | 37.27 | 01-JAN-13:20 | 1409.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 9.24 | 37.27 | 01-JAN-13:20 | 1409.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 509.12 | 6169.98 | 02-APR-17:10 | 43483.64 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 145.47 | 578.27 | 08-JAN-10:40 | 21878.12 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 145.47 | 578.27 | 08-JAN-10:40 | 21878.12 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 326.65 | 3976.17 | 23-APR-17:10 | 28022.51 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 92.30 | 372.66 | 01-JAN-10:10 | 14099.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 92.30 | 372.66 | 01-JAN-10:10 | 14099.09 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 505.00 | 6170.07 | 19-MAR-17:10 | 43484.45 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 141.34 | 578.28 | 01-JAN-10:00 | 21878.60 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 141.34 | 578.28 | 01-JAN-10:00 | 21878.60 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 326.51 | 3976.14 | 19-MAR-17:10 | 28022.42 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 92.16 | 372.66 | 01-JAN-13:20 | 14099.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 92.16 | 372.66 | 01-JAN-13:20 | 14099.09 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 50.91 | 617.00 | 02-APR-17:10 | 4348.36 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 14.54 | 57.83 | 08-JAN-10:40 | 2187.81 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 14.54 | 57.83 | 08-JAN-10:40 | 2187.81 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 32.66 | 397.62 | 23-APR-17:10 | 2802.25 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 9.23 | 37.27 | 01-JAN-10:10 | 1409.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 9.23 | 37.27 | 01-JAN-10:10 | 1409.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 50.50 | 617.01 | 19-MAR-17:10 | 4348.44 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 14.13 | 57.83 | 01-JAN-10:00 | 2187.86 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 14.13 | 57.83 | 01-JAN-10:00 | 2187.86 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 32.65 | 397.61 | 19-MAR-17:10 | 2802.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 9.22 | 37.27 | 01-JAN-13:20 | 1409.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 9.22 | 37.27 | 01-JAN-13:20 | 1409.91 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7557.51 | 95212.03 | 01-JAN-00:10 | 385103.08 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 62.65 | 303.90 | 01-JAN-00:10 | 5470.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 62.65 | 303.90 | 01-JAN-00:10 | 5470.56 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 159.04 | 1973.61 | 01-JAN-00:10 | 8244.54 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1590.36 | 19736.13 | 01-JAN-00:10 | 82445.36 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 51.55 | 250.08 | 01-JAN-00:10 | 4501.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 51.55 | 250.08 | 01-JAN-00:10 | 4501.14 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 159.04 | 1973.61 | 01-JAN-00:10 | 8244.54 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 1316.90 | 3903.50 | 16-JAN-05:30 | 384040.99 | 29-AUG-12:30 |
HeatRejection:Electricity | 327.66 | 97.69 | 07-JAN-08:00 | 80769.65 | 27-APR-12:40 |
General:HeatRejection:Electricity | 327.66 | 97.69 | 07-JAN-08:00 | 80769.65 | 27-APR-12:40 |
Electricity:HVAC | 4166.58 | 53101.20 | 12-JAN-02:20 | 455894.93 | 29-AUG-15:10 |
ExteriorEquipment:Electricity | 2566.61 | 20217.42 | 01-JAN-00:10 | 233439.18 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 55.02 | 979.82 | 01-JAN-00:10 | 3454.84 | 01-DEC-16:30 |
ElectricityPurchased:Facility | 26263.87 | 295321.99 | 29-MAY-04:40 | 2113943.05 | 29-AUG-15:10 |
ElectricityPurchased:Plant | 26263.87 | 295321.99 | 29-MAY-04:40 | 2113943.05 | 29-AUG-15:10 |
Cogeneration:ElectricityPurchased | 26263.87 | 295321.99 | 29-MAY-04:40 | 2113943.05 | 29-AUG-15:10 |
General:Cogeneration:ElectricityPurchased | 26263.87 | 295321.99 | 29-MAY-04:40 | 2113943.05 | 29-AUG-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 26263.87 | 295321.99 | 29-MAY-04:40 | 2113943.05 | 29-AUG-15:10 |
ElectricityNet:Plant | 26263.87 | 295321.99 | 29-MAY-04:40 | 2113943.05 | 29-AUG-15:10 |
Cogeneration:ElectricityNet | 26263.87 | 295321.99 | 29-MAY-04:40 | 2113943.05 | 29-AUG-15:10 |
General:Cogeneration:ElectricityNet | 26263.87 | 295321.99 | 29-MAY-04:40 | 2113943.05 | 29-AUG-15:10 |
Fans:Electricity | 2389.88 | 47709.36 | 03-JAN-02:10 | 294597.62 | 11-SEP-14:40 |
General:Fans:Electricity | 2389.88 | 47709.36 | 03-JAN-02:10 | 294597.62 | 11-SEP-14:40 |
ExteriorLights:Electricity | 356.44 | 0.00 | 01-JAN-08:10 | 40855.88 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 356.44 | 0.00 | 01-JAN-08:10 | 40855.88 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 2505.76 | 19200.00 | 01-JAN-00:10 | 229608.34 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 955.00 | 1618.47 | 03-JAN-08:00 | 408812.15 | 29-AUG-14:30 |
General:Cooling:Electricity | 955.00 | 1618.47 | 03-JAN-08:00 | 408812.15 | 29-AUG-14:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1045.49 | 0.00 | 11-JAN-20:10 | 100000.00 | 11-FEB-17:20 |
General:Humidifier:Electricity | 1045.49 | 0.00 | 11-JAN-20:10 | 100000.00 | 11-FEB-17:20 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 438.43 | 0.00 | 01-JAN-00:10 | 52005.61 | 10-FEB-12:40 |
Water Heater:WaterSystems:Electricity | 438.43 | 0.00 | 01-JAN-00:10 | 52005.61 | 10-FEB-12:40 |
Pumps:Electricity | 272.00 | 3791.32 | 02-JAN-05:50 | 44611.57 | 12-SEP-13:30 |
General:Pumps:Electricity | 272.00 | 3791.32 | 02-JAN-05:50 | 44611.57 | 12-SEP-13:30 |
WIRED_LTG_ELECTRICITY | 90.93 | 0.00 | 01-JAN-00:10 | 9152.54 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 970.43 | 0.00 | 01-JAN-00:10 | 1359749.70 | 02-JAN-06:10 |
NaturalGas:Plant | 970.43 | 0.00 | 01-JAN-00:10 | 1359749.70 | 02-JAN-06:10 |
Heating:NaturalGas | 970.43 | 0.00 | 01-JAN-00:10 | 1359749.70 | 02-JAN-06:10 |
Boiler:Heating:NaturalGas | 970.43 | 0.00 | 01-JAN-00:10 | 1359749.70 | 02-JAN-06:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 5620.32 | 3744.26 | 03-JAN-08:00 | 2405975.13 | 29-AUG-14:30 |
PlantLoopCoolingDemand:HVAC | 5620.32 | 3744.26 | 03-JAN-08:00 | 2405975.13 | 29-AUG-14:30 |
CoolingCoils:PlantLoopCoolingDemand | 5620.32 | 3744.26 | 03-JAN-08:00 | 2405975.13 | 29-AUG-14:30 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 4514.13 | 0.00 | 12-JAN-01:20 | 0.00 | 10-AUG-16:00 |
Water:HVAC | 388.92 | 0.00 | 11-JAN-20:10 | 0.00 | 13-FEB-05:10 |
Humidifier:Water | 388.92 | 0.00 | 11-JAN-20:10 | 0.00 | 13-FEB-05:10 |
General:Humidifier:Water | 388.92 | 0.00 | 11-JAN-20:10 | 0.00 | 13-FEB-05:10 |
MainsWater:Facility | 4514.13 | 0.00 | 12-JAN-01:20 | 0.00 | 10-AUG-16:00 |
MainsWater:HVAC | 388.92 | 0.00 | 11-JAN-20:10 | 0.00 | 13-FEB-05:10 |
Humidifier:MainsWater | 388.92 | 0.00 | 11-JAN-20:10 | 0.00 | 13-FEB-05:10 |
General:Humidifier:MainsWater | 388.92 | 0.00 | 11-JAN-20:10 | 0.00 | 13-FEB-05:10 |
Water:Plant | 4125.21 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 4125.21 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 1845.04 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
General:HeatRejection:Water | 1845.04 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
HeatRejection:MainsWater | 1845.04 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
General:HeatRejection:MainsWater | 1845.04 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 32449.40 | 96708.23 | 22-JAN-02:00 | 9284611.66 | 29-AUG-14:30 |
EnergyTransfer:Building | 17900.80 | 88454.47 | 21-JAN-18:20 | 1676321.44 | 10-AUG-15:20 |
EnergyTransfer:Zone:BASEMENT | 639.92 | 0.00 | 01-JAN-00:10 | 94641.16 | 10-OCT-06:30 |
Heating:EnergyTransfer | 197.66 | 0.00 | 11-JAN-18:00 | 888301.56 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 197.66 | 0.00 | 11-JAN-18:00 | 888301.56 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 17703.14 | 87240.35 | 16-JAN-05:30 | 1676321.44 | 10-AUG-15:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 639.92 | 0.00 | 01-JAN-00:10 | 94641.16 | 10-OCT-06:30 |
General:Cooling:EnergyTransfer | 17703.14 | 87240.35 | 16-JAN-05:30 | 1676321.44 | 10-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 639.92 | 0.00 | 01-JAN-00:10 | 94641.16 | 10-OCT-06:30 |
EnergyTransfer:Zone:CORE_BOTTOM | 612.35 | 0.00 | 01-JAN-00:10 | 54525.75 | 28-AUG-10:00 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 612.35 | 0.00 | 01-JAN-00:10 | 54525.75 | 28-AUG-10:00 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 612.35 | 0.00 | 01-JAN-00:10 | 54525.75 | 28-AUG-10:00 |
EnergyTransfer:Zone:CORE_MID | 4196.05 | 0.00 | 01-JAN-00:10 | 424340.07 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 1.44 | 0.00 | 01-JAN-00:10 | 283652.75 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 1.44 | 0.00 | 01-JAN-00:10 | 283652.75 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4194.61 | 0.00 | 01-JAN-00:10 | 424340.07 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4194.61 | 0.00 | 01-JAN-00:10 | 424340.07 | 10-AUG-16:00 |
EnergyTransfer:Zone:CORE_TOP | 371.11 | 0.00 | 01-JAN-00:10 | 69385.64 | 02-JAN-05:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 5.20 | 0.00 | 01-JAN-00:10 | 69385.64 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 5.20 | 0.00 | 01-JAN-00:10 | 69385.64 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 365.91 | 0.00 | 01-JAN-00:10 | 48825.20 | 10-AUG-15:50 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 365.91 | 0.00 | 01-JAN-00:10 | 48825.20 | 10-AUG-15:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 63.49 | 0.00 | 01-JAN-00:10 | 9843.60 | 24-JUL-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 526.27 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 526.27 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 63.49 | 0.00 | 01-JAN-00:10 | 9843.60 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 63.49 | 0.00 | 01-JAN-00:10 | 9843.60 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 61.44 | 0.00 | 01-JAN-00:10 | 15084.18 | 31-JUL-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 1106.54 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 1106.54 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 61.43 | 0.00 | 01-JAN-00:10 | 15084.18 | 31-JUL-08:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 61.43 | 0.00 | 01-JAN-00:10 | 15084.18 | 31-JUL-08:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 105.05 | 0.00 | 01-JAN-00:10 | 23868.65 | 04-OCT-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.06 | 0.00 | 01-JAN-00:10 | 5250.29 | 17-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.06 | 0.00 | 01-JAN-00:10 | 5250.29 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 104.99 | 0.00 | 01-JAN-00:10 | 23868.65 | 04-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 104.99 | 0.00 | 01-JAN-00:10 | 23868.65 | 04-OCT-12:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 92.90 | 0.00 | 01-JAN-00:10 | 19193.68 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 92.90 | 0.00 | 01-JAN-00:10 | 19193.68 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 92.90 | 0.00 | 01-JAN-00:10 | 19193.68 | 10-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 436.83 | 0.00 | 01-JAN-00:10 | 106067.35 | 02-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 28.89 | 0.00 | 01-JAN-00:10 | 106067.35 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 28.89 | 0.00 | 01-JAN-00:10 | 106067.35 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 407.94 | 0.00 | 01-JAN-00:10 | 84976.39 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 407.94 | 0.00 | 01-JAN-00:10 | 84976.39 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 504.40 | 0.00 | 01-JAN-00:10 | 155984.95 | 10-AUG-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 19.74 | 0.00 | 01-JAN-00:10 | 85292.52 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 19.74 | 0.00 | 01-JAN-00:10 | 85292.52 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 484.66 | 0.00 | 01-JAN-00:10 | 155984.95 | 10-AUG-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 484.66 | 0.00 | 01-JAN-00:10 | 155984.95 | 10-AUG-08:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 906.96 | 0.00 | 01-JAN-00:10 | 255441.71 | 04-OCT-13:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 18.57 | 0.00 | 01-JAN-00:10 | 128605.48 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 18.57 | 0.00 | 01-JAN-00:10 | 128605.48 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 888.39 | 0.00 | 01-JAN-00:10 | 255441.71 | 04-OCT-13:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 888.39 | 0.00 | 01-JAN-00:10 | 255441.71 | 04-OCT-13:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 557.93 | 0.00 | 01-JAN-00:10 | 170854.79 | 10-AUG-16:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 10.07 | 0.00 | 01-JAN-00:10 | 68671.66 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 10.07 | 0.00 | 01-JAN-00:10 | 68671.66 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 547.86 | 0.00 | 01-JAN-00:10 | 170854.79 | 10-AUG-16:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 547.86 | 0.00 | 01-JAN-00:10 | 170854.79 | 10-AUG-16:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 47.84 | 0.00 | 01-JAN-00:10 | 12183.75 | 02-JAN-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 12.52 | 0.00 | 01-JAN-00:10 | 12183.75 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 12.52 | 0.00 | 01-JAN-00:10 | 12183.75 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 35.32 | 0.00 | 01-JAN-00:10 | 9496.67 | 24-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 35.32 | 0.00 | 01-JAN-00:10 | 9496.67 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 51.22 | 0.00 | 01-JAN-00:10 | 15490.35 | 10-AUG-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 7.62 | 0.00 | 01-JAN-00:10 | 13367.62 | 17-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 7.62 | 0.00 | 01-JAN-00:10 | 13367.62 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 43.60 | 0.00 | 01-JAN-00:10 | 15490.35 | 10-AUG-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 43.60 | 0.00 | 01-JAN-00:10 | 15490.35 | 10-AUG-08:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 88.56 | 0.00 | 01-JAN-00:10 | 25606.16 | 04-OCT-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 8.73 | 0.00 | 01-JAN-00:10 | 19892.89 | 17-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 8.73 | 0.00 | 01-JAN-00:10 | 19892.89 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 79.84 | 0.00 | 01-JAN-00:10 | 25606.16 | 04-OCT-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 79.84 | 0.00 | 01-JAN-00:10 | 25606.16 | 04-OCT-13:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 54.80 | 0.00 | 01-JAN-00:10 | 17666.90 | 10-AUG-16:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 4.75 | 0.00 | 01-JAN-00:10 | 12153.77 | 17-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 4.75 | 0.00 | 01-JAN-00:10 | 12153.77 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 50.05 | 0.00 | 01-JAN-00:10 | 17666.90 | 10-AUG-16:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 50.05 | 0.00 | 01-JAN-00:10 | 17666.90 | 10-AUG-16:30 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 58.10 | 0.00 | 01-JAN-00:10 | 8890.93 | 14-AUG-13:50 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.05 | 0.00 | 01-JAN-00:10 | 4114.89 | 10-DEC-13:30 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.05 | 0.00 | 01-JAN-00:10 | 4114.89 | 10-DEC-13:30 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 57.05 | 0.00 | 01-JAN-00:10 | 8890.93 | 14-AUG-13:50 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 57.05 | 0.00 | 01-JAN-00:10 | 8890.93 | 14-AUG-13:50 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 369.03 | 0.00 | 01-JAN-00:10 | 89364.84 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 49.35 | 0.00 | 01-JAN-00:10 | 89364.84 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 49.35 | 0.00 | 01-JAN-00:10 | 89364.84 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 319.68 | 0.00 | 01-JAN-00:10 | 70133.76 | 10-AUG-15:10 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 319.68 | 0.00 | 01-JAN-00:10 | 70133.76 | 10-AUG-15:10 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 69.08 | 0.00 | 01-JAN-00:10 | 20637.12 | 17-JAN-05:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 26.69 | 0.00 | 01-JAN-00:10 | 20637.12 | 17-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 26.69 | 0.00 | 01-JAN-00:10 | 20637.12 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 42.39 | 0.00 | 01-JAN-00:10 | 19081.06 | 10-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 42.39 | 0.00 | 01-JAN-00:10 | 19081.06 | 10-AUG-14:30 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 138.52 | 698.68 | 17-JAN-07:00 | 8675.41 | 06-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 138.52 | 698.68 | 17-JAN-07:00 | 8675.41 | 06-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 138.52 | 698.68 | 17-JAN-07:00 | 8675.41 | 06-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1190.02 | 6.15 | 07-JAN-05:00 | 81133.65 | 06-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 2.24 | 0.00 | 02-JAN-12:50 | 5573.83 | 01-JAN-19:40 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 2.24 | 0.00 | 02-JAN-12:50 | 5573.83 | 01-JAN-19:40 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1187.77 | 0.00 | 01-JAN-00:10 | 81133.65 | 06-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1187.77 | 0.00 | 01-JAN-00:10 | 81133.65 | 06-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 109.31 | 0.27 | 07-JAN-08:40 | 8196.84 | 06-AUG-18:30 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.74 | 0.00 | 02-JAN-14:30 | 618.49 | 08-JAN-17:30 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.74 | 0.00 | 02-JAN-14:30 | 618.49 | 08-JAN-17:30 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 108.57 | 0.00 | 01-JAN-00:10 | 8196.84 | 06-AUG-18:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 108.57 | 0.00 | 01-JAN-00:10 | 8196.84 | 06-AUG-18:30 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7175.91 | 86465.63 | 17-JAN-05:00 | 369018.89 | 25-AUG-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7175.91 | 86465.63 | 17-JAN-05:00 | 369018.89 | 25-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7175.91 | 86465.63 | 17-JAN-05:00 | 369018.89 | 25-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 1150.02 | 0.00 | 01-JAN-00:10 | 1085822.68 | 02-JAN-06:10 |
PlantLoopHeatingDemand:Plant | 433.10 | 0.00 | 01-JAN-00:10 | 51259.06 | 10-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 433.10 | 0.00 | 01-JAN-00:10 | 51259.06 | 10-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 433.10 | 0.00 | 01-JAN-00:10 | 51259.06 | 10-FEB-12:10 |
EnergyTransfer:HVAC | 5661.04 | 2495.52 | 01-JAN-07:30 | 2228730.77 | 29-AUG-14:30 |
HeatingCoils:EnergyTransfer | 716.92 | 0.00 | 01-JAN-00:10 | 1079627.76 | 02-JAN-06:10 |
PlantLoopHeatingDemand:HVAC | 716.92 | 0.00 | 01-JAN-00:10 | 1079627.76 | 02-JAN-06:10 |
HeatingCoils:PlantLoopHeatingDemand | 716.92 | 0.00 | 01-JAN-00:10 | 1079627.76 | 02-JAN-06:10 |
CoolingCoils:EnergyTransfer | 4944.13 | 2125.79 | 03-JAN-08:00 | 2228730.77 | 29-AUG-14:30 |
EnergyTransfer:Plant | 8887.55 | 0.00 | 01-JAN-00:10 | 5407477.37 | 29-AUG-14:30 |
LoopToLoop:EnergyTransfer | 2480.93 | 0.00 | 01-JAN-00:10 | 1716442.93 | 29-AUG-14:30 |
WaterSystems:EnergyTransfer | 433.10 | 0.00 | 01-JAN-00:10 | 51259.06 | 10-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 433.10 | 0.00 | 01-JAN-00:10 | 51259.06 | 10-FEB-12:10 |
Boilers:EnergyTransfer | 710.63 | 0.00 | 01-JAN-00:10 | 1127734.10 | 02-JAN-06:10 |
Chillers:EnergyTransfer | 2492.04 | 0.00 | 01-JAN-00:10 | 1716943.78 | 29-AUG-14:30 |
HeatRejection:EnergyTransfer | 2770.84 | 0.00 | 01-JAN-00:10 | 1948511.57 | 29-AUG-14:30 |
General:HeatRejection:EnergyTransfer | 2770.84 | 0.00 | 01-JAN-00:10 | 1948511.57 | 29-AUG-14:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -639.912 | 0.000 | 0.000 | 92.326 | 216.171 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -92.982 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -612.347 | 0.000 | 0.000 | 83.431 | 194.137 | 289.614 | 0.000 | 0.000 | 0.000 | 45.166 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
CORE_MID | 0.000 | 0.000 | 1.443 | -4194.585 | 0.000 | 0.000 | 845.829 | 1941.366 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1490.180 |
CORE_TOP | 0.000 | 0.000 | 5.200 | -365.905 | 0.000 | 0.000 | 87.586 | 194.137 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -210.631 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -63.485 | 0.000 | 0.000 | 10.733 | 14.595 | 36.365 | 22.293 | 0.000 | 0.007 | 46.088 | 0.000 | -63.632 | 0.000 | -2.964 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.004 | -61.431 | 0.000 | 0.000 | 7.058 | 9.254 | 23.435 | 45.245 | 0.000 | 0.004 | 17.595 | 0.000 | -39.250 | 0.000 | -1.914 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.063 | -104.989 | 0.000 | 0.000 | 10.867 | 14.155 | 36.366 | 98.693 | 0.000 | 0.006 | 6.833 | 0.000 | -59.079 | 0.000 | -2.915 | 0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -92.901 | 0.000 | 0.000 | 6.854 | 9.239 | 23.435 | 47.870 | 0.000 | 0.004 | 53.325 | 0.000 | -45.666 | 0.000 | -2.161 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 28.887 | -407.937 | 0.000 | 0.000 | 113.226 | 145.466 | 363.654 | 234.387 | 0.000 | 0.177 | 145.011 | 0.000 | -561.653 | 0.000 | -61.218 | -0.001 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 19.744 | -484.661 | 0.000 | 0.000 | 54.022 | 92.302 | 234.352 | 455.985 | 0.000 | 0.098 | 28.782 | 0.000 | -359.634 | 0.000 | -40.992 | -0.003 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 18.567 | -888.382 | 0.000 | 0.000 | 111.615 | 141.343 | 363.660 | 986.924 | 0.000 | 0.128 | 0.001 | 0.000 | -561.088 | 0.000 | -64.331 | -108.436 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 10.068 | -547.853 | 0.000 | 0.000 | 73.503 | 92.161 | 234.351 | 491.848 | 0.000 | 0.089 | 74.248 | 0.000 | -385.495 | 0.000 | -42.919 | 0.000 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 12.520 | -35.323 | 0.000 | 0.000 | 11.564 | 14.544 | 36.365 | 24.107 | 0.000 | 0.020 | 0.000 | 0.000 | -52.049 | 0.000 | -7.075 | -4.672 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 7.621 | -43.597 | 0.000 | 0.000 | 7.415 | 9.229 | 23.435 | 46.033 | 0.000 | 0.011 | 0.000 | 0.000 | -33.658 | 0.000 | -4.779 | -11.711 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 8.726 | -79.838 | 0.000 | 0.000 | 11.373 | 14.132 | 36.366 | 99.471 | 0.000 | 0.015 | 0.000 | 0.000 | -52.446 | 0.000 | -7.475 | -30.324 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 4.748 | -50.054 | 0.000 | 0.000 | 7.471 | 9.215 | 23.435 | 49.463 | 0.000 | 0.010 | 0.001 | 0.000 | -36.339 | 0.000 | -5.038 | -2.913 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -138.517 | 0.000 | 0.000 | 0.950 | 5.155 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -21.469 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 2.242 | -1187.774 | 0.000 | 0.000 | 9.503 | 51.551 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -414.328 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.737 | -108.572 | 0.000 | 0.000 | 0.952 | 5.155 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -52.153 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7175.909 | 0.000 | 0.000 | 20.565 | 62.653 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -402.165 |
GROUNDFLOOR_PLENUM | 1.051 | -57.053 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.010 | 62.294 | 0.000 | 0.000 | 0.000 | -6.302 | 0.000 |
MIDFLOOR_PLENUM | 49.348 | -319.677 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.214 | 376.035 | 0.000 | 0.000 | 0.000 | -105.920 | -0.005 |
TOPFLOOR_PLENUM | 26.691 | -42.389 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.012 | 26.814 | 0.000 | 0.000 | 0.000 | -11.129 | -0.001 |
Total Facility | 77.090 | -419.119 | 120.572 | -17283.971 | 0.000 | 0.000 | 1566.844 | 3235.960 | 14676.396 | 2602.318 | 0.000 | 0.805 | 882.193 | 0.000 | -2249.989 | 0.000 | -367.132 | -2841.975 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 05-SEP-06:11 | 0.00 | 0.00 | 0.00 | -119504.31 | 0.00 | 0.00 | 1488.32 | 6467.36 | 13457.54 | 0.00 | 0.00 | 0.00 | 98091.08 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 05-SEP-04:12 | 0.00 | 0.00 | 0.00 | -96205.36 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 89730.35 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 11-AUG-04:12 | 0.00 | 0.00 | 0.00 | -826675.67 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 761925.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 11-AUG-04:12 | 0.00 | 0.00 | 0.00 | -78104.72 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 71629.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 14-AUG-05:02 | 0.00 | 0.00 | 0.00 | -11890.72 | 0.00 | 0.00 | 108.57 | 67.47 | 960.25 | 0.00 | 0.00 | 0.00 | 11518.85 | 0.00 | -752.30 | 0.00 | -12.11 | 0.00 |
PERIMETER_BOT_ZN_2 | 30-JUL-08:31 | 0.00 | 0.00 | 0.00 | -25673.79 | 0.00 | 0.00 | 19.78 | 37.27 | 464.11 | 19340.57 | 0.00 | 0.00 | 5859.73 | 0.00 | -0.00 | 0.00 | -47.67 | 0.00 |
PERIMETER_BOT_ZN_1 | 13-AUG-12:41 | 0.00 | 0.00 | 0.00 | -34252.39 | 0.00 | 0.00 | 32.68 | 57.83 | 720.19 | 22738.61 | 0.00 | 0.00 | 10733.70 | 0.00 | -0.00 | 0.00 | -30.62 | 0.00 |
PERIMETER_BOT_ZN_4 | 30-JUL-16:31 | 0.00 | 0.00 | 0.00 | -33401.08 | 0.00 | 0.00 | 14.23 | 37.27 | 464.11 | 21776.71 | 0.00 | 0.00 | 11148.77 | 0.00 | -0.00 | 0.00 | -40.01 | 0.00 |
PERIMETER_MID_ZN_3 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 | -84973.86 | 0.00 | 0.00 | 11143.84 | 10409.61 | 21605.52 | 64201.53 | 0.00 | 364.75 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -22751.38 |
PERIMETER_MID_ZN_2 | 06-AUG-09:41 | 0.00 | 0.00 | 0.00 | -261165.07 | 0.00 | 0.00 | 202.60 | 372.66 | 4641.14 | 144635.46 | 0.00 | 0.00 | 113140.70 | 0.00 | -0.00 | 0.00 | -1827.50 | 0.00 |
PERIMETER_MID_ZN_1 | 10-SEP-12:21 | 0.00 | 0.00 | 0.00 | -375632.41 | 0.00 | 0.00 | 289.16 | 578.28 | 7201.95 | 281679.68 | 0.00 | 0.00 | 87740.98 | 0.00 | -0.00 | 0.00 | -1857.64 | 0.00 |
PERIMETER_MID_ZN_4 | 06-AUG-17:01 | 0.00 | 0.00 | 0.00 | -294053.54 | 0.00 | 0.00 | 0.00 | 372.66 | 3603.49 | 204151.46 | 0.00 | 0.00 | 87427.53 | 0.00 | -0.00 | 0.00 | -1501.60 | 0.00 |
PERIMETER_TOP_ZN_3 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 | -9496.50 | 0.00 | 0.00 | 1114.38 | 1040.96 | 2160.55 | 6358.73 | 0.00 | 44.53 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1222.65 |
PERIMETER_TOP_ZN_2 | 14-MAY-09:32 | 0.00 | 0.00 | 0.00 | -24519.67 | 0.00 | 0.00 | 22.40 | 37.27 | 464.11 | 14043.72 | 0.00 | 0.00 | 10224.46 | 0.00 | -0.00 | 0.00 | -272.28 | 0.00 |
PERIMETER_TOP_ZN_1 | 30-JUL-14:21 | 0.00 | 0.00 | 0.00 | -36716.84 | 0.00 | 0.00 | 32.66 | 57.83 | 720.19 | 15501.16 | 0.00 | 0.00 | 20477.47 | 0.00 | -0.00 | 0.00 | -72.48 | 0.00 |
PERIMETER_TOP_ZN_4 | 30-JUL-17:01 | 0.00 | 0.00 | 0.00 | -31420.61 | 0.00 | 0.00 | 0.00 | 37.27 | 360.35 | 21174.91 | 0.00 | 0.00 | 9970.83 | 0.00 | -0.00 | 0.00 | -122.75 | 0.00 |
DATACENTER_BOT_ZN_6 | 06-AUG-18:33 | 0.00 | 0.00 | 0.00 | -8675.41 | 0.00 | 0.00 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 855.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 06-AUG-18:35 | 0.00 | 0.00 | 0.00 | -81133.65 | 0.00 | 0.00 | 0.00 | 250.08 | 77944.22 | 0.00 | 0.00 | 0.00 | 2939.35 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 06-AUG-18:21 | 0.00 | 0.00 | 0.00 | -8196.84 | 0.00 | 0.00 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 377.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 25-AUG-16:00 | 0.00 | 0.00 | 0.00 | -369003.15 | 0.00 | 0.00 | 2180.72 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -18280.65 |
GROUNDFLOOR_PLENUM | 14-AUG-05:15 | 0.00 | -10397.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10427.60 | 0.00 | -0.00 | 0.00 | -29.99 | 0.00 |
MIDFLOOR_PLENUM | 14-JAN-05:11 | 0.00 | -71761.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84506.49 | 0.00 | -0.00 | 0.00 | -12745.37 | 0.00 |
TOPFLOOR_PLENUM | 10-AUG-14:30 | 0.00 | -19081.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.53 | 19051.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-AUG-05:03 | 0.00 | 1987.82 | 0.00 | -1708742.08 | 0.00 | 0.00 | 15746.25 | 10917.52 | 616289.16 | 67287.90 | 0.00 | 0.00 | 1035129.33 | 0.00 | -36611.32 | 0.00 | -2004.57 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-05:11 | 0.00 | 0.00 | 335249.84 | 0.00 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -399999.67 |
CORE_TOP | 17-JAN-04:51 | 0.00 | 0.00 | 75773.94 | 0.00 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -82248.93 |
PERIMETER_BOT_ZN_3 | 09-JAN-06:03 | 0.00 | 0.00 | 1833.51 | 0.00 | 0.00 | 0.00 | 140.58 | 67.47 | 960.25 | 0.00 | 0.00 | 0.00 | 2138.34 | 0.00 | -5080.73 | 0.00 | -59.42 | 0.00 |
PERIMETER_BOT_ZN_2 | 17-JAN-06:02 | 0.00 | 0.00 | 4734.17 | 0.00 | 0.00 | 0.00 | 91.67 | 43.48 | 618.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2836.81 | 0.00 | -27.70 | -2623.62 |
PERIMETER_BOT_ZN_1 | 17-JAN-05:01 | 0.00 | 0.00 | 11257.06 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3788.66 | 0.00 | -137.24 | -8144.21 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 02-JAN-05:11 | 0.00 | 0.00 | 115923.41 | 0.00 | 0.00 | 0.00 | 0.00 | 674.71 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -22043.52 | 0.00 | -4592.72 | -97417.48 |
PERIMETER_MID_ZN_2 | 02-JAN-05:11 | 0.00 | 0.00 | 151120.50 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -14523.31 | 0.00 | -3126.88 | -138709.80 |
PERIMETER_MID_ZN_1 | 02-JAN-05:11 | 0.00 | 0.00 | 217432.88 | 0.00 | 0.00 | 0.00 | 0.00 | 674.72 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -22664.94 | 0.00 | -4725.92 | -198172.47 |
PERIMETER_MID_ZN_4 | 02-JAN-05:11 | 0.00 | 0.00 | 138133.39 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -16323.69 | 0.00 | -3397.72 | -123651.43 |
PERIMETER_TOP_ZN_3 | 26-DEC-04:11 | 0.00 | 0.00 | 13409.02 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3366.62 | 0.00 | -347.07 | -10508.37 |
PERIMETER_TOP_ZN_2 | 26-DEC-04:11 | 0.00 | 0.00 | 17912.11 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2240.92 | 0.00 | -237.83 | -15957.31 |
PERIMETER_TOP_ZN_1 | 26-DEC-04:11 | 0.00 | 0.00 | 26448.88 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3308.65 | 0.00 | -357.73 | -23595.55 |
PERIMETER_TOP_ZN_4 | 17-JAN-04:51 | 0.00 | 0.00 | 17939.63 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1896.90 | 0.00 | -205.39 | -16361.28 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 01-JAN-19:15 | 0.00 | 0.00 | 5574.09 | 0.00 | 0.00 | 0.00 | 0.00 | 250.08 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25310.22 |
DATACENTER_TOP_ZN_6 | 08-JAN-17:30 | 0.00 | 0.00 | 618.50 | 0.00 | 0.00 | 0.00 | 5.60 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2597.71 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 27-NOV-05:11 | 11485.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -573.64 | -10911.51 |
MIDFLOOR_PLENUM | 14-MAY-15:01 | 118519.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1310.63 | -117209.12 |
TOPFLOOR_PLENUM | 17-JAN-05:13 | 23612.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -486.00 | -23126.53 |
Total Facility | 02-JAN-05:11 | -188945.46 | 188293.81 | 1114490.10 | -188293.81 | 0.00 | 0.00 | 0.00 | 10917.52 | 232425.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -93818.35 | 0.00 | -28331.67 | -1046737.38 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 11.5151 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.6155 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 110.5230 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 89.1296 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 11.1111 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.8691 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.6452 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.6452 | 0.2126 | 1.0000 | Not calculated | 1.2002 | 0.2126 | ||
AIRLOOP DATACENTER BASEMENT | 24.8969 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.8970 | 0.0136 | 1.0000 | Not calculated | 0.3384 | 0.0136 | ||
AIRLOOP DATACENTER BOT | 0.5128 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5128 | 0.0305 | 1.0000 | Not calculated | 0.0156 | 0.0305 | ||
AIRLOOP DATACENTER MID | 4.9231 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.9231 | 0.0318 | 1.0000 | Not calculated | 0.1563 | 0.0318 | ||
AIRLOOP DATACENTER TOP | 0.4994 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4994 | 0.0313 | 1.0000 | Not calculated | 0.0156 | 0.0313 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.7576 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.1176 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 55.2615 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 30.6202 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.5555 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.1594 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 0.0000 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 0.0000 | 1.0000 | 1.0000 | Not calculated | 1.2002 | |||
AIRLOOP DATACENTER BASEMENT | 24.8969 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.8969 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0136 | ||
AIRLOOP DATACENTER BOT | 0.5128 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5128 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0305 | ||
AIRLOOP DATACENTER MID | 4.9231 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.9231 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0318 | ||
AIRLOOP DATACENTER TOP | 0.4994 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4994 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0313 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 5.6452 | 5.6452 | 0.0000 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.9041 | 5.9041 | 1.9306 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 55.4497 | 55.4497 | 18.8529 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.3615 | 5.3615 | 1.9462 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8865 | 0.8865 | 0.2420 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3164 | 1.3164 | 0.2633 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8324 | 1.8324 | 0.3665 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5758 | 1.5758 | 0.3152 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.0931 | 8.0931 | 2.3713 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.7268 | 13.7268 | 2.7454 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 18.8537 | 18.8537 | 3.7707 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.3998 | 14.3998 | 2.8800 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9037 | 0.9037 | 0.2440 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3627 | 1.3627 | 0.2725 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9802 | 1.9802 | 0.3960 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5030 | 1.5030 | 0.3006 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5128 | 0.5128 | 0.5128 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.9231 | 4.9231 | 4.9231 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4994 | 0.4994 | 0.4994 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.8969 | 24.8969 | 24.8969 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 11.5151 | 9.6155 | 11.5151 | 3.1176 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 110.5230 | 89.1296 | 110.5230 | 30.6202 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 11.1111 | 9.8691 | 11.1111 | 3.1594 | 0.0000 | 1.0000 |
CAV_BAS | 5.6452 | 5.6452 | 5.6452 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.8969 | 24.8970 | 24.8969 | 24.8969 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5128 | 0.5128 | 0.5128 | 0.5128 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.9231 | 4.9231 | 4.9231 | 4.9231 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4994 | 0.4994 | 0.4994 | 0.4994 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 0.0000 | 0.0000 | 0.0000 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9520 | 2.9520 | 1.9306 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 27.7249 | 27.7249 | 18.8529 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6807 | 2.6807 | 1.9462 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4432 | 0.4432 | 0.2420 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6582 | 0.6582 | 0.2633 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9162 | 0.9162 | 0.3665 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7879 | 0.7879 | 0.3152 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.0465 | 4.0465 | 2.3713 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.8634 | 6.8634 | 2.7454 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.4268 | 9.4268 | 3.7707 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.1999 | 7.1999 | 2.8800 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4518 | 0.4518 | 0.2440 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6814 | 0.6814 | 0.2725 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9901 | 0.9901 | 0.3960 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7515 | 0.7515 | 0.3006 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5128 | 0.5128 | 0.5128 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.9231 | 4.9231 | 4.9231 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4994 | 0.4994 | 0.4994 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.8969 | 24.8969 | 24.8969 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.7576 | 3.1176 | 3.1176 | 3.1176 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 55.2615 | 30.6202 | 30.6202 | 30.6202 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.5555 | 3.1594 | 3.1594 | 3.1594 | 0.0000 | 1.0000 |
CAV_BAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.8969 | 24.8969 | 24.8969 | 24.8969 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5128 | 0.5128 | 0.5128 | 0.5128 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.9231 | 4.9231 | 4.9231 | 4.9231 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4994 | 0.4994 | 0.4994 | 0.4994 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 12.50 |
Number of hours cooling loads not met | 505.50 |
Number of hours not met | 509.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 970.43 | 1359749.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 955.00 | 408812.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3235.96 | 325713.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 356.44 | 40855.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 55.02 | 3454.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 2505.76 | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2389.88 | 294597.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 272.00 | 44611.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 327.66 | 80769.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1045.49 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 438.43 | 52005.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 26263.87 |
Natural Gas | 0.00 | 970.43 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 27234.30 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 69.86 |
Space Heating | 0.00 |
Space Cooling | 20.62 |
Fans (All) | 51.59 |
Service Water Heating | 9.47 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 567.00 |
Subtotal | 567.00 |
Natural Gas [MJ/m2] | |
Space Heating | 20.95 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 20.95 |
Subtotal | 20.95 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 11.88 |
Space Heating | 3.56 |
Space Cooling | 3.51 |
Fans (All) | 8.78 |
Service Water Heating | 1.61 |
Receptacle Equipment | 53.89 |
Miscellaneous | 16.77 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8234.00 | 508.33 | 17.67 | 0.00 | 0.00 |
CORE_BOTTOM | 8713.67 | 46.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8740.00 | 20.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8733.33 | 26.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8498.00 | 262.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8741.33 | 18.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8731.67 | 28.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8711.00 | 49.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8742.33 | 17.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8734.33 | 25.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8714.00 | 46.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7898.17 | 861.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7850.67 | 909.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7828.17 | 931.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7352.67 | 1407.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8746.33 | 13.67 | 0.00 | 0.00 | 0.00 |
Min | 7352.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1407.33 | 17.67 | 0.00 | 0.00 |
Average | 8534.31 | 224.92 | 0.77 | 0.00 | 0.00 |
Sum | 196289.17 | 5173.17 | 17.67 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 365619.67 | 2363.00 | 633.33 | 0.00 | 0.00 |
CORE_BOTTOM | 330739.00 | 74.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1736.67 | 531.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1700.67 | 567.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1688.17 | 579.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 86088.83 | 17306.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 365619.67 | 17306.17 | 633.33 | 0.00 | 0.00 |
Average | 79376.00 | 931.38 | 27.54 | 0.00 | 0.00 |
Sum | 1825648.00 | 21421.67 | 633.33 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8059.00 | 683.50 | 17.50 | 0.00 | 0.00 |
CORE_BOTTOM | 8515.33 | 244.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8615.33 | 144.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8672.83 | 87.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8739.83 | 20.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8737.83 | 22.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8718.00 | 42.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8471.83 | 288.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8753.67 | 6.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8730.67 | 29.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8702.67 | 57.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8654.67 | 105.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8756.50 | 3.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8734.33 | 25.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8712.83 | 47.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8669.00 | 91.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8498.17 | 261.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8472.00 | 288.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8462.33 | 297.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7764.33 | 995.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8723.67 | 36.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8758.33 | 1.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8637.67 | 122.33 | 0.00 | 0.00 | 0.00 |
Min | 7764.33 | 1.67 | 0.00 | 0.00 | 0.00 |
Max | 8758.33 | 995.67 | 17.50 | 0.00 | 0.00 |
Average | 8589.60 | 169.64 | 0.76 | 0.00 | 0.00 |
Sum | 197560.83 | 3901.67 | 17.50 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 365063.83 | 2942.50 | 609.67 | 0.00 | 0.00 |
CORE_BOTTOM | 330429.17 | 383.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330558.00 | 255.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330657.00 | 156.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2085.00 | 183.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2063.50 | 204.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2057.17 | 210.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 90957.33 | 12437.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 365063.83 | 12437.67 | 609.67 | 0.00 | 0.00 |
Average | 79579.13 | 729.28 | 26.51 | 0.00 | 0.00 |
Sum | 1830320.00 | 16773.33 | 609.67 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:49
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Environment
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Environment
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.443517E+11 | 108578.04 | 02-JAN-07:05 | 6.20 | 5.35 | 0.567861E+10 | 7499.24 | 11-JAN-14:09 | 14.40 | 10.49 |
February | 0.430293E+11 | 107355.74 | 28-FEB-07:11 | 10.60 | 9.82 | 0.515336E+10 | 7499.18 | 13-FEB-10:39 | 10.60 | 9.82 |
March | 0.551611E+11 | 105402.89 | 11-MAR-07:12 | 10.00 | 9.66 | 0.615460E+10 | 7499.28 | 09-MAR-14:09 | 10.00 | 9.66 |
April | 0.528774E+11 | 112769.64 | 03-APR-06:11 | 10.40 | 9.80 | 0.547284E+10 | 7499.28 | 27-APR-13:09 | 26.10 | 16.37 |
May | 0.546338E+11 | 115227.37 | 30-MAY-06:11 | 10.77 | 9.90 | 0.592691E+10 | 7499.33 | 05-MAY-09:09 | 10.77 | 9.90 |
June | 0.571519E+11 | 114221.35 | 05-JUN-06:11 | 11.30 | 9.68 | 0.590999E+10 | 7499.36 | 05-JUN-09:00 | 14.40 | 11.89 |
July | 0.573643E+11 | 115154.00 | 03-JUL-06:11 | 12.07 | 8.59 | 0.550216E+10 | 7505.77 | 24-JUL-09:30 | 24.15 | 16.83 |
August | 0.621045E+11 | 108003.01 | 26-AUG-06:11 | 15.40 | 14.63 | 0.626165E+10 | 10539.32 | 25-AUG-13:00 | 15.40 | 14.63 |
September | 0.546409E+11 | 119521.22 | 05-SEP-06:11 | 10.93 | 9.52 | 0.547968E+10 | 7639.65 | 12-SEP-13:30 | 23.60 | 16.15 |
October | 0.555276E+11 | 118657.19 | 10-OCT-06:11 | 12.03 | 10.85 | 0.569650E+10 | 7499.26 | 05-OCT-09:00 | 12.03 | 10.85 |
November | 0.527899E+11 | 116474.28 | 06-NOV-07:11 | 12.20 | 8.87 | 0.563645E+10 | 7499.22 | 02-NOV-09:09 | 12.20 | 8.87 |
December | 0.502846E+11 | 109440.09 | 26-DEC-07:03 | -1.6 | -1.6 | 0.548890E+10 | 7499.47 | 13-DEC-14:09 | -1.6 | -1.6 |
Annual Sum or Average | 0.639917E+12 | 0.683616E+11 | ||||||||
Minimum of Months | 0.430293E+11 | 105402.89 | -1.6 | -1.6 | 0.515336E+10 | 7499.18 | -1.6 | -1.6 | ||
Maximum of Months | 0.621045E+11 | 119521.22 | 15.40 | 14.63 | 0.626165E+10 | 10539.32 | 26.10 | 16.83 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.362158E+11 | 87535.36 | 02-JAN-05:11 | 6.10 | 5.29 | 0.504932E+10 | 6734.78 | 20-JAN-10:09 | 4.18 | 2.79 |
February | 0.377503E+11 | 87463.64 | 27-FEB-05:12 | 6.50 | 5.53 | 0.459598E+10 | 6734.78 | 08-FEB-10:09 | 6.50 | 5.53 |
March | 0.517182E+11 | 90272.55 | 27-MAR-04:11 | 4.80 | 3.63 | 0.550110E+10 | 6734.75 | 09-MAR-14:09 | 4.80 | 3.63 |
April | 0.548247E+11 | 91594.49 | 17-APR-04:12 | 6.10 | 5.14 | 0.488365E+10 | 6734.77 | 20-APR-09:39 | 9.80 | 7.10 |
May | 0.521810E+11 | 93396.55 | 01-MAY-04:12 | 12.20 | 10.35 | 0.528685E+10 | 6734.84 | 05-MAY-09:09 | 15.97 | 13.48 |
June | 0.569405E+11 | 94907.92 | 12-JUN-04:13 | 14.80 | 13.61 | 0.527097E+10 | 6734.86 | 05-JUN-09:00 | 14.80 | 13.61 |
July | 0.621244E+11 | 93761.17 | 05-JUL-04:12 | 11.30 | 8.18 | 0.489753E+10 | 6734.79 | 28-JUL-13:00 | 20.00 | 15.26 |
August | 0.706206E+11 | 91976.68 | 26-AUG-04:13 | 15.03 | 14.27 | 0.549727E+10 | 6755.43 | 15-AUG-13:09 | 15.03 | 14.27 |
September | 0.499718E+11 | 96215.65 | 05-SEP-04:12 | 11.33 | 9.63 | 0.488521E+10 | 6806.32 | 12-SEP-13:30 | 23.60 | 16.15 |
October | 0.493759E+11 | 95360.48 | 10-OCT-04:12 | 12.20 | 11.04 | 0.507920E+10 | 6734.77 | 12-OCT-09:09 | 9.18 | 7.86 |
November | 0.459770E+11 | 94016.84 | 06-NOV-05:12 | 10.77 | 8.10 | 0.503003E+10 | 6734.73 | 13-NOV-10:00 | 2.80 | 2.80 |
December | 0.446487E+11 | 90864.21 | 04-DEC-05:12 | 3.70 | 1.47 | 0.490025E+10 | 6734.86 | 13-DEC-14:09 | 7.10 | 5.11 |
Annual Sum or Average | 0.612349E+12 | 0.608773E+11 | ||||||||
Minimum of Months | 0.362158E+11 | 87463.64 | 3.70 | 1.47 | 0.459598E+10 | 6734.73 | 2.80 | 2.79 | ||
Maximum of Months | 0.706206E+11 | 96215.65 | 15.03 | 14.27 | 0.550110E+10 | 6806.32 | 23.60 | 16.15 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.236755E+11 | 25664.46 | 12-JAN-17:00 | 7.20 | 5.41 | 0.467616E+10 | 6734.60 | 27-JAN-14:09 | 9.72 | 8.09 |
February | 0.245926E+11 | 55478.43 | 28-FEB-06:03 | 10.60 | 9.74 | 0.442594E+10 | 6734.78 | 08-FEB-10:09 | 10.60 | 9.74 |
March | 0.335833E+11 | 73731.58 | 03-MAR-06:02 | 6.60 | 6.18 | 0.542496E+10 | 6734.73 | 14-MAR-09:39 | 9.27 | 7.14 |
April | 0.344527E+11 | 79371.24 | 29-APR-05:02 | 8.40 | 8.40 | 0.484125E+10 | 6734.77 | 20-APR-09:39 | 8.40 | 8.40 |
May | 0.412537E+11 | 79647.91 | 08-MAY-05:02 | 9.50 | 9.45 | 0.526290E+10 | 6734.82 | 05-MAY-09:09 | 9.50 | 9.45 |
June | 0.435636E+11 | 80908.84 | 12-JUN-04:12 | 14.80 | 13.61 | 0.525717E+10 | 6734.83 | 09-JUN-13:09 | 14.80 | 13.61 |
July | 0.439963E+11 | 82063.17 | 17-JUL-04:12 | 14.23 | 12.63 | 0.488802E+10 | 6734.78 | 28-JUL-13:00 | 20.00 | 15.26 |
August | 0.478673E+11 | 82678.09 | 11-AUG-04:12 | 12.73 | 11.87 | 0.549016E+10 | 6735.22 | 09-AUG-09:00 | 12.73 | 11.87 |
September | 0.395548E+11 | 79981.31 | 07-SEP-05:02 | 12.20 | 11.57 | 0.486592E+10 | 6748.70 | 12-SEP-13:30 | 23.60 | 16.15 |
October | 0.339694E+11 | 79989.95 | 10-OCT-05:02 | 12.20 | 11.22 | 0.502375E+10 | 6734.78 | 12-OCT-09:09 | 9.18 | 7.86 |
November | 0.275777E+11 | 72477.46 | 06-NOV-06:03 | 11.28 | 8.36 | 0.490676E+10 | 6734.74 | 10-NOV-10:09 | 6.88 | 5.74 |
December | 0.253739E+11 | 28729.57 | 06-DEC-16:20 | 2.57 | 2.27 | 0.466259E+10 | 6734.70 | 13-DEC-14:09 | 7.10 | 5.11 |
Annual Sum or Average | 0.419461E+12 | 0.597256E+11 | ||||||||
Minimum of Months | 0.236755E+11 | 25664.46 | 2.57 | 2.27 | 0.442594E+10 | 6734.60 | 6.88 | 5.11 | ||
Maximum of Months | 0.478673E+11 | 82678.09 | 14.80 | 13.61 | 0.549016E+10 | 6748.70 | 23.60 | 16.15 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.183313E+11 | 18990.41 | 11-JAN-17:00 | 12.20 | 9.27 | 0.418634E+10 | 6406.56 | 12-JAN-14:00 | 7.20 | 5.88 |
February | 0.193184E+11 | 28572.84 | 28-FEB-17:00 | 14.40 | 10.82 | 0.397126E+10 | 6734.34 | 28-FEB-14:09 | 14.40 | 10.82 |
March | 0.267022E+11 | 32091.81 | 15-MAR-16:00 | 11.10 | 7.72 | 0.506294E+10 | 6734.65 | 09-MAR-14:09 | 11.10 | 7.72 |
April | 0.297355E+11 | 73476.27 | 28-APR-05:03 | 11.10 | 9.92 | 0.467227E+10 | 6734.74 | 14-APR-09:09 | 11.10 | 9.92 |
May | 0.376138E+11 | 73316.43 | 05-MAY-05:03 | 12.98 | 10.75 | 0.519204E+10 | 6734.79 | 05-MAY-09:09 | 15.97 | 13.48 |
June | 0.419957E+11 | 77260.53 | 12-JUN-04:12 | 14.80 | 13.61 | 0.522683E+10 | 6734.82 | 09-JUN-13:09 | 14.80 | 13.61 |
July | 0.438920E+11 | 77403.98 | 25-JUL-04:12 | 13.90 | 13.04 | 0.486987E+10 | 6734.81 | 11-JUL-09:09 | 13.90 | 13.04 |
August | 0.469852E+11 | 78114.31 | 11-AUG-04:12 | 12.73 | 11.87 | 0.546899E+10 | 6735.20 | 09-AUG-09:00 | 12.73 | 11.87 |
September | 0.348967E+11 | 73608.23 | 14-SEP-05:03 | 12.62 | 12.25 | 0.479226E+10 | 6734.85 | 12-SEP-13:39 | 12.62 | 12.25 |
October | 0.268606E+11 | 39066.87 | 04-OCT-15:50 | 21.20 | 11.42 | 0.476853E+10 | 6734.67 | 06-OCT-09:30 | 12.75 | 11.01 |
November | 0.209150E+11 | 25870.59 | 02-NOV-16:00 | 13.30 | 10.88 | 0.441681E+10 | 6734.56 | 03-NOV-13:00 | 13.30 | 12.64 |
December | 0.186612E+11 | 19016.71 | 06-DEC-16:50 | 1.47 | 1.30 | 0.409399E+10 | 6456.60 | 06-DEC-14:00 | 1.47 | 1.30 |
Annual Sum or Average | 0.365908E+12 | 0.567221E+11 | ||||||||
Minimum of Months | 0.183313E+11 | 18990.41 | 1.47 | 1.30 | 0.397126E+10 | 6406.56 | 1.47 | 1.30 | ||
Maximum of Months | 0.469852E+11 | 78114.31 | 21.20 | 13.61 | 0.546899E+10 | 6735.20 | 15.97 | 13.61 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.264779E+10 | 2746.15 | 12-JAN-06:03 | 6.70 | 6.36 | 0.557431E+09 | 834.76 | 11-JAN-14:50 | 6.70 | 6.36 |
February | 0.286311E+10 | 4726.70 | 27-FEB-15:30 | 19.70 | 12.30 | 0.530275E+09 | 845.61 | 24-FEB-10:09 | 19.70 | 12.30 |
March | 0.420596E+10 | 5264.29 | 10-MAR-14:20 | 16.50 | 11.85 | 0.669586E+09 | 845.63 | 09-MAR-14:09 | 16.50 | 11.85 |
April | 0.546658E+10 | 7711.47 | 27-APR-15:20 | 27.20 | 17.16 | 0.605705E+09 | 845.63 | 27-APR-13:20 | 27.20 | 17.16 |
May | 0.631281E+10 | 7682.27 | 15-MAY-13:50 | 23.22 | 13.56 | 0.658702E+09 | 845.63 | 15-MAY-13:09 | 23.22 | 13.56 |
June | 0.757924E+10 | 11454.42 | 12-JUN-05:03 | 14.40 | 13.42 | 0.660597E+09 | 845.64 | 09-JUN-13:09 | 14.40 | 13.42 |
July | 0.882034E+10 | 11886.78 | 31-JUL-05:02 | 17.30 | 14.53 | 0.614601E+09 | 845.75 | 24-JUL-13:20 | 17.30 | 14.53 |
August | 0.953691E+10 | 11891.44 | 14-AUG-05:02 | 15.37 | 13.48 | 0.689689E+09 | 852.08 | 15-AUG-13:09 | 24.25 | 15.86 |
September | 0.546523E+10 | 8713.55 | 12-SEP-13:27 | 23.60 | 16.15 | 0.607960E+09 | 852.29 | 12-SEP-13:30 | 23.60 | 16.15 |
October | 0.423157E+10 | 5659.26 | 10-OCT-12:10 | 13.30 | 8.88 | 0.623285E+09 | 845.62 | 12-OCT-09:30 | 9.75 | 8.05 |
November | 0.335017E+10 | 4720.10 | 06-NOV-11:40 | 13.70 | 9.94 | 0.602564E+09 | 845.62 | 03-NOV-09:30 | 13.70 | 9.94 |
December | 0.300568E+10 | 3010.13 | 04-DEC-05:12 | 3.70 | 1.47 | 0.566469E+09 | 845.61 | 04-DEC-14:09 | 8.90 | 5.70 |
Annual Sum or Average | 0.634854E+11 | 0.738686E+10 | ||||||||
Minimum of Months | 0.264779E+10 | 2746.15 | 3.70 | 1.47 | 0.530275E+09 | 834.76 | 6.70 | 5.70 | ||
Maximum of Months | 0.953691E+10 | 11891.44 | 27.20 | 17.16 | 0.689689E+09 | 852.29 | 27.20 | 17.16 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.242153E+10 | 2828.99 | 11-JAN-06:03 | 9.90 | 7.47 | 0.338272E+09 | 531.62 | 05-JAN-10:09 | 9.90 | 7.47 |
February | 0.273543E+10 | 4718.61 | 08-FEB-09:45 | 1.93 | 0.91 | 0.327089E+09 | 544.95 | 08-FEB-10:09 | 2.48 | 1.47 |
March | 0.411769E+10 | 9264.20 | 14-MAR-08:55 | 7.80 | 5.89 | 0.417883E+09 | 544.96 | 02-MAR-10:09 | 7.80 | 5.89 |
April | 0.554091E+10 | 12563.97 | 27-APR-08:30 | 16.95 | 12.18 | 0.385574E+09 | 544.96 | 20-APR-09:00 | 16.95 | 12.18 |
May | 0.622424E+10 | 19549.20 | 14-MAY-08:32 | 15.93 | 11.13 | 0.420613E+09 | 544.97 | 15-MAY-09:00 | 18.90 | 13.25 |
June | 0.751968E+10 | 24081.07 | 25-JUN-07:52 | 15.60 | 11.55 | 0.423936E+09 | 544.97 | 09-JUN-13:09 | 15.60 | 11.55 |
July | 0.814161E+10 | 25677.56 | 30-JUL-08:31 | 19.83 | 15.43 | 0.394304E+09 | 546.18 | 24-JUL-09:39 | 19.83 | 15.43 |
August | 0.895090E+10 | 25016.13 | 06-AUG-08:11 | 14.57 | 12.64 | 0.442238E+09 | 546.61 | 15-AUG-13:09 | 24.25 | 15.86 |
September | 0.574747E+10 | 20931.76 | 10-SEP-08:32 | 15.53 | 13.26 | 0.387534E+09 | 549.49 | 12-SEP-13:30 | 23.60 | 16.15 |
October | 0.424397E+10 | 10302.63 | 04-OCT-08:50 | 15.32 | 10.37 | 0.388592E+09 | 544.96 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.306475E+10 | 4168.08 | 15-NOV-09:10 | 6.78 | 5.27 | 0.360109E+09 | 544.95 | 15-NOV-10:09 | 7.30 | 5.72 |
December | 0.272294E+10 | 3640.56 | 05-DEC-09:55 | 6.70 | 5.10 | 0.333144E+09 | 544.95 | 05-DEC-10:09 | 6.97 | 5.16 |
Annual Sum or Average | 0.614311E+11 | 0.461929E+10 | ||||||||
Minimum of Months | 0.242153E+10 | 2828.99 | 1.93 | 0.91 | 0.327089E+09 | 531.62 | 2.48 | 1.47 | ||
Maximum of Months | 0.895090E+10 | 25677.56 | 19.83 | 15.43 | 0.442238E+09 | 549.49 | 24.25 | 16.15 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.403021E+10 | 16629.43 | 20-JAN-13:10 | 6.70 | 4.72 | 0.542431E+09 | 845.64 | 11-JAN-14:09 | 6.70 | 4.72 |
February | 0.556813E+10 | 21754.76 | 12-FEB-13:13 | 6.30 | 1.05 | 0.523554E+09 | 846.57 | 27-FEB-14:50 | 19.72 | 12.05 |
March | 0.845403E+10 | 20298.49 | 01-MAR-13:30 | 11.15 | 5.98 | 0.652733E+09 | 846.71 | 01-MAR-14:50 | 13.03 | 7.20 |
April | 0.959265E+10 | 21574.97 | 02-APR-15:22 | 20.60 | 11.92 | 0.596891E+09 | 846.69 | 26-APR-13:00 | 23.90 | 13.95 |
May | 0.947178E+10 | 20701.52 | 14-MAY-13:13 | 22.40 | 12.22 | 0.650261E+09 | 845.67 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.100047E+11 | 27589.03 | 11-JUN-12:43 | 21.70 | 15.34 | 0.655948E+09 | 845.68 | 28-JUN-13:39 | 24.80 | 15.68 |
July | 0.124154E+11 | 33323.92 | 30-JUL-11:52 | 26.10 | 17.22 | 0.612486E+09 | 846.78 | 31-JUL-13:00 | 28.30 | 18.92 |
August | 0.146498E+11 | 34254.61 | 13-AUG-12:41 | 26.43 | 18.35 | 0.687681E+09 | 860.44 | 15-AUG-13:09 | 24.25 | 15.86 |
September | 0.111255E+11 | 32472.68 | 10-SEP-12:32 | 20.20 | 13.87 | 0.603037E+09 | 949.96 | 12-SEP-13:30 | 23.60 | 16.15 |
October | 0.899516E+10 | 33445.21 | 08-OCT-13:42 | 19.63 | 14.09 | 0.609208E+09 | 846.79 | 02-OCT-13:39 | 19.63 | 14.09 |
November | 0.544581E+10 | 21326.87 | 11-NOV-12:53 | 6.70 | 5.18 | 0.576179E+09 | 845.64 | 13-NOV-14:30 | 6.70 | 4.24 |
December | 0.523618E+10 | 29033.69 | 03-DEC-13:32 | 12.20 | 6.14 | 0.542136E+09 | 845.66 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.104989E+12 | 0.725254E+10 | ||||||||
Minimum of Months | 0.403021E+10 | 16629.43 | 6.30 | 1.05 | 0.523554E+09 | 845.64 | 6.70 | 4.24 | ||
Maximum of Months | 0.146498E+11 | 34254.61 | 26.43 | 18.35 | 0.687681E+09 | 949.96 | 28.30 | 18.92 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.350600E+10 | 5352.40 | 05-JAN-15:30 | 6.40 | 4.89 | 0.356494E+09 | 544.94 | 11-JAN-14:30 | 14.40 | 10.49 |
February | 0.419873E+10 | 13268.29 | 26-FEB-15:13 | 14.40 | 10.43 | 0.350772E+09 | 544.95 | 22-FEB-14:09 | 14.40 | 10.43 |
March | 0.667249E+10 | 15144.13 | 18-MAR-17:06 | 19.22 | 9.55 | 0.440405E+09 | 544.96 | 09-MAR-14:09 | 19.22 | 9.55 |
April | 0.920067E+10 | 26895.53 | 02-APR-15:22 | 20.60 | 11.92 | 0.395481E+09 | 544.96 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.835820E+10 | 28007.25 | 14-MAY-16:32 | 22.97 | 11.85 | 0.424471E+09 | 544.96 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.988421E+10 | 28672.48 | 18-JUN-16:51 | 17.20 | 12.22 | 0.426828E+09 | 544.98 | 28-JUN-13:39 | 24.80 | 15.68 |
July | 0.132382E+11 | 33401.22 | 30-JUL-16:31 | 27.07 | 18.02 | 0.397685E+09 | 544.97 | 28-JUL-13:39 | 27.07 | 18.02 |
August | 0.144267E+11 | 33262.75 | 06-AUG-16:51 | 23.40 | 15.11 | 0.446004E+09 | 548.00 | 15-AUG-13:09 | 24.25 | 15.86 |
September | 0.766675E+10 | 27529.45 | 10-SEP-16:32 | 22.20 | 14.28 | 0.392313E+09 | 559.17 | 11-SEP-15:09 | 23.30 | 15.89 |
October | 0.603223E+10 | 17501.92 | 08-OCT-13:42 | 19.63 | 14.09 | 0.404934E+09 | 544.96 | 05-OCT-09:00 | 19.63 | 14.09 |
November | 0.486909E+10 | 13548.02 | 06-NOV-05:12 | 10.77 | 8.10 | 0.398983E+09 | 544.95 | 03-NOV-09:09 | 10.77 | 8.10 |
December | 0.484794E+10 | 12820.48 | 04-DEC-05:11 | 3.70 | 1.47 | 0.388342E+09 | 544.97 | 13-DEC-14:09 | 7.10 | 5.11 |
Annual Sum or Average | 0.929012E+11 | 0.482271E+10 | ||||||||
Minimum of Months | 0.350600E+10 | 5352.40 | 3.70 | 1.47 | 0.350772E+09 | 544.94 | 7.10 | 5.11 | ||
Maximum of Months | 0.144267E+11 | 33401.22 | 27.07 | 18.02 | 0.446004E+09 | 559.17 | 27.07 | 18.02 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.882813E+09 | 1958.37 | 11-JAN-16:20 | 13.67 | 10.10 | 0.475061E+09 | 719.70 | 11-JAN-14:00 | 13.67 | 10.10 |
February | 0.138442E+10 | 2346.58 | 28-FEB-15:00 | 13.90 | 10.81 | 0.451903E+09 | 826.76 | 28-FEB-14:00 | 13.90 | 10.81 |
March | 0.254562E+10 | 2832.35 | 10-MAR-14:30 | 16.40 | 11.76 | 0.589860E+09 | 845.59 | 10-MAR-14:09 | 16.40 | 11.76 |
April | 0.316899E+10 | 6187.69 | 27-APR-15:20 | 27.20 | 17.16 | 0.563506E+09 | 845.62 | 27-APR-13:30 | 27.20 | 17.16 |
May | 0.474540E+10 | 6834.73 | 05-MAY-13:30 | 23.85 | 16.52 | 0.643218E+09 | 845.63 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.563832E+10 | 7418.77 | 21-JUN-15:30 | 24.70 | 15.68 | 0.653949E+09 | 845.64 | 09-JUN-13:09 | 24.70 | 15.68 |
July | 0.629850E+10 | 8497.64 | 24-JUL-15:00 | 30.60 | 18.78 | 0.610639E+09 | 845.63 | 28-JUL-13:50 | 20.55 | 15.38 |
August | 0.643484E+10 | 8195.60 | 25-AUG-14:00 | 27.40 | 18.74 | 0.684348E+09 | 845.69 | 09-AUG-09:00 | 27.40 | 18.74 |
September | 0.410324E+10 | 6769.15 | 12-SEP-13:27 | 23.60 | 16.15 | 0.591310E+09 | 847.48 | 12-SEP-13:30 | 23.60 | 16.15 |
October | 0.276132E+10 | 3755.75 | 04-OCT-15:10 | 21.60 | 11.48 | 0.564899E+09 | 845.60 | 10-OCT-13:09 | 13.48 | 9.32 |
November | 0.179325E+10 | 2371.51 | 07-NOV-06:03 | 12.12 | 9.85 | 0.505475E+09 | 798.76 | 02-NOV-13:00 | 12.12 | 9.85 |
December | 0.103715E+10 | 1871.81 | 29-DEC-16:10 | 10.40 | 8.63 | 0.462554E+09 | 700.19 | 29-DEC-14:00 | 10.40 | 8.63 |
Annual Sum or Average | 0.407939E+11 | 0.679672E+10 | ||||||||
Minimum of Months | 0.882813E+09 | 1871.81 | 10.40 | 8.63 | 0.451903E+09 | 700.19 | 10.40 | 8.63 | ||
Maximum of Months | 0.643484E+10 | 8497.64 | 30.60 | 18.78 | 0.684348E+09 | 847.48 | 27.40 | 18.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.750199E+09 | 2149.98 | 05-JAN-09:40 | 1.67 | 1.50 | 0.221783E+09 | 433.35 | 05-JAN-09:50 | 2.23 | 2.03 |
February | 0.145296E+10 | 2887.47 | 12-FEB-12:22 | 5.85 | 0.79 | 0.213021E+09 | 509.51 | 08-FEB-09:00 | 5.85 | 0.79 |
March | 0.301772E+10 | 7328.27 | 14-MAR-10:10 | 10.28 | 7.92 | 0.276808E+09 | 521.21 | 14-MAR-10:09 | 10.28 | 7.92 |
April | 0.440067E+10 | 12616.90 | 27-APR-09:00 | 17.80 | 12.21 | 0.270016E+09 | 521.22 | 20-APR-10:09 | 17.80 | 12.21 |
May | 0.561173E+10 | 24941.12 | 14-MAY-08:22 | 15.55 | 10.92 | 0.299179E+09 | 521.23 | 15-MAY-10:09 | 19.18 | 13.24 |
June | 0.699018E+10 | 25734.65 | 25-JUN-08:21 | 16.15 | 11.79 | 0.306619E+09 | 521.22 | 07-JUN-10:09 | 16.15 | 11.79 |
July | 0.729460E+10 | 24448.58 | 30-JUL-08:42 | 20.22 | 15.61 | 0.287394E+09 | 521.65 | 31-JUL-07:49 | 20.82 | 16.47 |
August | 0.780704E+10 | 26116.34 | 06-AUG-09:41 | 16.80 | 13.46 | 0.321799E+09 | 521.49 | 10-AUG-08:00 | 22.50 | 17.13 |
September | 0.525146E+10 | 24862.67 | 10-SEP-09:42 | 17.02 | 13.53 | 0.274262E+09 | 528.09 | 11-SEP-15:09 | 23.30 | 15.89 |
October | 0.325646E+10 | 9383.69 | 04-OCT-09:00 | 15.60 | 10.49 | 0.262333E+09 | 521.22 | 05-OCT-10:09 | 14.08 | 9.36 |
November | 0.166175E+10 | 2675.17 | 02-NOV-10:40 | 12.43 | 10.47 | 0.230263E+09 | 505.13 | 02-NOV-10:50 | 12.62 | 10.55 |
December | 0.971099E+09 | 2384.37 | 05-DEC-10:00 | 6.70 | 5.10 | 0.216044E+09 | 461.05 | 05-DEC-09:00 | 6.70 | 5.10 |
Annual Sum or Average | 0.484659E+11 | 0.317952E+10 | ||||||||
Minimum of Months | 0.750199E+09 | 2149.98 | 1.67 | 0.79 | 0.213021E+09 | 433.35 | 2.23 | 0.79 | ||
Maximum of Months | 0.780704E+10 | 26116.34 | 20.22 | 15.61 | 0.321799E+09 | 528.09 | 23.30 | 17.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.254769E+10 | 16730.89 | 20-JAN-13:20 | 6.70 | 4.72 | 0.506175E+09 | 845.64 | 20-JAN-14:20 | 6.87 | 4.79 |
February | 0.451463E+10 | 32771.96 | 12-FEB-12:22 | 5.85 | 0.79 | 0.492470E+09 | 846.19 | 27-FEB-14:50 | 19.72 | 12.05 |
March | 0.723157E+10 | 21647.77 | 01-MAR-13:40 | 11.33 | 6.09 | 0.617883E+09 | 846.50 | 01-MAR-14:00 | 13.30 | 7.37 |
April | 0.786066E+10 | 22082.26 | 02-APR-15:22 | 20.60 | 11.92 | 0.573672E+09 | 846.44 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.869640E+10 | 33132.53 | 14-MAY-13:02 | 22.30 | 12.21 | 0.635220E+09 | 845.67 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.881981E+10 | 27186.25 | 11-JUN-13:02 | 21.78 | 15.29 | 0.644117E+09 | 845.68 | 28-JUN-13:30 | 24.70 | 15.69 |
July | 0.105905E+11 | 32470.66 | 30-JUL-13:22 | 26.40 | 17.72 | 0.604537E+09 | 846.50 | 31-JUL-13:00 | 28.30 | 18.92 |
August | 0.122768E+11 | 34728.46 | 06-AUG-13:42 | 22.45 | 15.67 | 0.680118E+09 | 847.67 | 29-AUG-13:39 | 29.43 | 20.04 |
September | 0.109251E+11 | 37559.74 | 10-SEP-12:21 | 20.00 | 13.75 | 0.590855E+09 | 944.08 | 12-SEP-13:30 | 23.60 | 16.15 |
October | 0.815911E+10 | 33070.50 | 08-OCT-13:12 | 18.53 | 13.81 | 0.583133E+09 | 850.88 | 04-OCT-13:20 | 18.53 | 13.81 |
November | 0.396063E+10 | 22151.97 | 11-NOV-12:53 | 6.70 | 5.18 | 0.529865E+09 | 845.64 | 15-NOV-10:09 | 7.30 | 5.72 |
December | 0.325600E+10 | 16981.11 | 05-DEC-12:30 | 10.30 | 6.13 | 0.500229E+09 | 845.65 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.888390E+11 | 0.695828E+10 | ||||||||
Minimum of Months | 0.254769E+10 | 16730.89 | 5.85 | 0.79 | 0.492470E+09 | 845.64 | 6.87 | 4.79 | ||
Maximum of Months | 0.122768E+11 | 37559.74 | 26.40 | 17.72 | 0.680118E+09 | 944.08 | 29.43 | 20.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113352E+10 | 2743.34 | 05-JAN-15:50 | 6.20 | 4.71 | 0.306728E+09 | 496.88 | 05-JAN-15:00 | 6.10 | 4.61 |
February | 0.189732E+10 | 8113.93 | 27-FEB-15:30 | 19.70 | 12.30 | 0.294342E+09 | 544.93 | 27-FEB-14:00 | 19.70 | 12.30 |
March | 0.343118E+10 | 10775.62 | 14-MAR-16:00 | 17.20 | 10.94 | 0.374034E+09 | 544.94 | 02-MAR-14:00 | 17.20 | 10.94 |
April | 0.467797E+10 | 15205.28 | 02-APR-15:22 | 20.60 | 11.92 | 0.356795E+09 | 544.96 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.641354E+10 | 29143.61 | 07-MAY-16:41 | 21.78 | 16.19 | 0.405138E+09 | 544.96 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.688306E+10 | 25809.99 | 18-JUN-17:31 | 16.87 | 12.26 | 0.414275E+09 | 544.96 | 28-JUN-13:30 | 24.70 | 15.69 |
July | 0.882843E+10 | 27012.78 | 23-JUL-17:11 | 26.50 | 15.70 | 0.391289E+09 | 544.96 | 28-JUL-13:50 | 20.55 | 15.38 |
August | 0.848721E+10 | 29401.88 | 06-AUG-17:01 | 23.47 | 15.14 | 0.437826E+09 | 545.01 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.590011E+10 | 27580.10 | 10-SEP-17:01 | 21.93 | 14.12 | 0.372723E+09 | 553.80 | 11-SEP-15:09 | 23.30 | 15.89 |
October | 0.363456E+10 | 12100.36 | 04-OCT-16:00 | 21.10 | 11.40 | 0.353921E+09 | 544.93 | 12-OCT-13:00 | 15.00 | 11.02 |
November | 0.208703E+10 | 5638.61 | 04-NOV-15:30 | 20.55 | 15.94 | 0.318888E+09 | 544.93 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.141193E+10 | 3009.93 | 05-DEC-15:30 | 8.05 | 5.82 | 0.300521E+09 | 527.14 | 05-DEC-14:00 | 8.05 | 5.82 |
Annual Sum or Average | 0.547859E+11 | 0.432648E+10 | ||||||||
Minimum of Months | 0.113352E+10 | 2743.34 | 6.20 | 4.71 | 0.294342E+09 | 496.88 | 6.10 | 4.61 | ||
Maximum of Months | 0.882843E+10 | 29401.88 | 26.50 | 16.19 | 0.437826E+09 | 553.80 | 26.10 | 16.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.369589E+09 | 1853.64 | 11-JAN-16:20 | 13.67 | 10.10 | 0.465823E+09 | 677.48 | 11-JAN-14:00 | 13.67 | 10.10 |
February | 0.788674E+09 | 2298.54 | 28-FEB-15:10 | 13.90 | 10.77 | 0.434631E+09 | 795.64 | 28-FEB-14:00 | 13.90 | 10.77 |
March | 0.182752E+10 | 2456.24 | 10-MAR-14:50 | 16.20 | 11.59 | 0.550701E+09 | 839.03 | 10-MAR-14:00 | 16.10 | 11.51 |
April | 0.271504E+10 | 6787.00 | 27-APR-15:20 | 27.20 | 17.16 | 0.535132E+09 | 845.63 | 27-APR-13:30 | 27.20 | 17.16 |
May | 0.437884E+10 | 7146.59 | 05-MAY-13:30 | 23.85 | 16.52 | 0.622966E+09 | 845.63 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.545721E+10 | 8049.15 | 21-JUN-15:30 | 24.70 | 15.68 | 0.643889E+09 | 845.64 | 09-JUN-13:09 | 24.70 | 15.68 |
July | 0.627588E+10 | 9496.67 | 24-JUL-15:00 | 30.60 | 18.78 | 0.605583E+09 | 845.64 | 28-JUL-13:50 | 20.55 | 15.38 |
August | 0.634232E+10 | 8729.82 | 09-AUG-14:40 | 28.17 | 18.42 | 0.677492E+09 | 845.69 | 09-AUG-09:00 | 28.17 | 18.42 |
September | 0.372834E+10 | 6446.94 | 12-SEP-13:27 | 23.60 | 16.15 | 0.568364E+09 | 845.63 | 12-SEP-13:39 | 23.87 | 16.28 |
October | 0.207981E+10 | 3575.70 | 04-OCT-15:30 | 21.40 | 11.45 | 0.525538E+09 | 845.60 | 05-OCT-13:50 | 16.10 | 10.63 |
November | 0.990136E+09 | 2160.88 | 02-NOV-14:40 | 13.67 | 11.26 | 0.476103E+09 | 756.55 | 02-NOV-13:00 | 13.67 | 11.26 |
December | 0.370334E+09 | 1763.32 | 29-DEC-16:10 | 10.40 | 8.63 | 0.449493E+09 | 660.23 | 29-DEC-14:00 | 10.40 | 8.63 |
Annual Sum or Average | 0.353237E+11 | 0.655572E+10 | ||||||||
Minimum of Months | 0.369589E+09 | 1763.32 | 10.40 | 8.63 | 0.434631E+09 | 660.23 | 10.40 | 8.63 | ||
Maximum of Months | 0.634232E+10 | 9496.67 | 30.60 | 18.78 | 0.677492E+09 | 845.69 | 28.17 | 18.42 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.377692E+09 | 1914.62 | 05-JAN-09:40 | 1.67 | 1.50 | 0.299856E+09 | 422.42 | 20-JAN-10:50 | 5.32 | 3.17 |
February | 0.973727E+09 | 2414.55 | 27-FEB-15:50 | 19.50 | 12.39 | 0.282077E+09 | 488.06 | 03-FEB-10:50 | 19.50 | 12.39 |
March | 0.229546E+10 | 5998.91 | 14-MAR-09:50 | 9.63 | 7.44 | 0.365960E+09 | 544.95 | 02-MAR-10:09 | 9.63 | 7.44 |
April | 0.388628E+10 | 12188.88 | 27-APR-09:20 | 18.17 | 12.47 | 0.362053E+09 | 544.96 | 20-APR-09:00 | 18.17 | 12.47 |
May | 0.527276E+10 | 24519.22 | 14-MAY-09:32 | 18.17 | 11.98 | 0.402997E+09 | 544.98 | 15-MAY-09:00 | 18.90 | 13.25 |
June | 0.685211E+10 | 20499.78 | 25-JUN-08:42 | 16.52 | 11.95 | 0.415650E+09 | 544.97 | 09-JUN-13:09 | 16.52 | 11.95 |
July | 0.730532E+10 | 24498.69 | 30-JUL-08:21 | 19.45 | 15.24 | 0.389133E+09 | 545.90 | 31-JUL-09:00 | 23.30 | 17.69 |
August | 0.778499E+10 | 24168.61 | 13-AUG-09:32 | 22.10 | 16.37 | 0.436905E+09 | 545.93 | 10-AUG-09:00 | 22.10 | 16.37 |
September | 0.486501E+10 | 18396.02 | 10-SEP-09:12 | 16.47 | 13.50 | 0.366727E+09 | 544.97 | 14-SEP-09:09 | 17.38 | 15.51 |
October | 0.254802E+10 | 8265.38 | 04-OCT-09:30 | 16.40 | 10.73 | 0.346432E+09 | 544.96 | 05-OCT-09:00 | 13.90 | 9.28 |
November | 0.987966E+09 | 2431.82 | 02-NOV-10:40 | 12.43 | 10.47 | 0.303910E+09 | 481.54 | 02-NOV-13:00 | 14.40 | 11.37 |
December | 0.447455E+09 | 2030.56 | 05-DEC-10:30 | 7.50 | 5.28 | 0.289809E+09 | 438.36 | 05-DEC-10:39 | 7.77 | 5.32 |
Annual Sum or Average | 0.435968E+11 | 0.426151E+10 | ||||||||
Minimum of Months | 0.377692E+09 | 1914.62 | 1.67 | 1.50 | 0.282077E+09 | 422.42 | 5.32 | 3.17 | ||
Maximum of Months | 0.778499E+10 | 24519.22 | 22.10 | 16.37 | 0.436905E+09 | 545.93 | 23.30 | 17.69 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.168836E+10 | 15039.88 | 20-JAN-13:30 | 6.70 | 4.72 | 0.489879E+09 | 845.64 | 20-JAN-14:20 | 6.87 | 4.79 |
February | 0.339180E+10 | 18415.52 | 27-FEB-14:30 | 19.15 | 11.80 | 0.475561E+09 | 845.63 | 07-FEB-14:09 | 19.15 | 11.80 |
March | 0.593130E+10 | 20686.40 | 14-MAR-13:30 | 15.00 | 10.00 | 0.591842E+09 | 845.93 | 14-MAR-13:30 | 15.00 | 10.00 |
April | 0.705536E+10 | 28452.99 | 02-APR-12:23 | 18.05 | 10.93 | 0.555190E+09 | 846.54 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.818872E+10 | 35287.84 | 14-MAY-13:32 | 22.60 | 12.25 | 0.617987E+09 | 845.67 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.865109E+10 | 26744.75 | 11-JUN-12:32 | 21.70 | 15.39 | 0.632247E+09 | 845.67 | 09-JUN-13:09 | 21.70 | 15.39 |
July | 0.106239E+11 | 36720.75 | 30-JUL-14:21 | 26.95 | 17.87 | 0.596991E+09 | 846.58 | 31-JUL-13:00 | 28.30 | 18.92 |
August | 0.122327E+11 | 34186.38 | 13-AUG-12:52 | 26.50 | 18.40 | 0.671888E+09 | 847.81 | 29-AUG-13:39 | 29.43 | 20.04 |
September | 0.103707E+11 | 35595.19 | 10-SEP-13:12 | 21.13 | 14.29 | 0.572555E+09 | 897.91 | 12-SEP-13:30 | 23.60 | 16.15 |
October | 0.688539E+10 | 31156.97 | 08-OCT-13:22 | 18.90 | 13.91 | 0.558509E+09 | 846.13 | 03-OCT-13:00 | 18.90 | 13.91 |
November | 0.269720E+10 | 17562.55 | 04-NOV-13:30 | 20.85 | 16.00 | 0.501501E+09 | 845.64 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.212207E+10 | 14530.82 | 05-DEC-12:30 | 10.30 | 6.13 | 0.482289E+09 | 845.65 | 05-DEC-14:00 | 10.00 | 7.01 |
Annual Sum or Average | 0.798385E+11 | 0.674644E+10 | ||||||||
Minimum of Months | 0.168836E+10 | 14530.82 | 6.70 | 4.72 | 0.475561E+09 | 845.63 | 6.87 | 4.79 | ||
Maximum of Months | 0.122327E+11 | 36720.75 | 26.95 | 18.40 | 0.671888E+09 | 897.91 | 29.43 | 20.04 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.656865E+09 | 2719.82 | 05-JAN-15:50 | 6.20 | 4.71 | 0.302574E+09 | 478.42 | 05-JAN-15:00 | 6.10 | 4.61 |
February | 0.130475E+10 | 7577.11 | 27-FEB-15:30 | 19.70 | 12.30 | 0.287367E+09 | 544.93 | 27-FEB-14:00 | 19.70 | 12.30 |
March | 0.276068E+10 | 10663.80 | 14-MAR-16:00 | 17.20 | 10.94 | 0.357983E+09 | 544.94 | 02-MAR-14:00 | 17.20 | 10.94 |
April | 0.427157E+10 | 15250.18 | 26-APR-16:00 | 24.40 | 14.49 | 0.342972E+09 | 544.96 | 27-APR-13:00 | 26.10 | 16.83 |
May | 0.616983E+10 | 30508.01 | 07-MAY-16:41 | 21.78 | 16.19 | 0.392895E+09 | 544.96 | 15-MAY-13:09 | 22.88 | 13.76 |
June | 0.681283E+10 | 26214.84 | 18-JUN-17:02 | 17.12 | 12.23 | 0.405807E+09 | 544.96 | 09-JUN-13:09 | 17.12 | 12.23 |
July | 0.885930E+10 | 31423.99 | 30-JUL-17:01 | 26.70 | 17.83 | 0.386540E+09 | 544.96 | 28-JUL-13:50 | 26.70 | 17.83 |
August | 0.847534E+10 | 27644.61 | 06-AUG-17:11 | 23.53 | 15.16 | 0.431966E+09 | 545.01 | 09-AUG-09:00 | 23.80 | 15.92 |
September | 0.562811E+10 | 26355.61 | 10-SEP-16:32 | 22.20 | 14.28 | 0.359417E+09 | 544.97 | 12-SEP-13:39 | 23.87 | 16.28 |
October | 0.300995E+10 | 12029.32 | 04-OCT-16:00 | 21.10 | 11.40 | 0.336604E+09 | 544.93 | 03-OCT-13:00 | 21.10 | 11.40 |
November | 0.134000E+10 | 5213.20 | 04-NOV-15:30 | 20.55 | 15.94 | 0.306883E+09 | 529.76 | 15-NOV-14:00 | 8.90 | 6.49 |
December | 0.764842E+09 | 2852.64 | 05-DEC-15:40 | 7.40 | 5.40 | 0.294401E+09 | 499.70 | 05-DEC-14:00 | 7.40 | 5.40 |
Annual Sum or Average | 0.500541E+11 | 0.420541E+10 | ||||||||
Minimum of Months | 0.656865E+09 | 2719.82 | 6.20 | 4.71 | 0.287367E+09 | 478.42 | 6.10 | 4.61 | ||
Maximum of Months | 0.885930E+10 | 31423.99 | 26.70 | 17.83 | 0.431966E+09 | 545.01 | 26.70 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.132213E+10 | 3538.42 | 06-JAN-06:07 | -1.8 | -1.8 | 0.00 | 0.00 | 01-JAN-00:10 | -1.8 | -1.8 |
February | 0.185547E+10 | 4488.30 | 28-FEB-06:15 | 10.60 | 9.74 | 0.00 | 0.00 | 01-FEB-00:10 | 10.60 | 9.74 |
March | 0.378338E+10 | 5833.25 | 20-MAR-05:15 | 5.97 | 4.27 | 0.00 | 0.00 | 01-MAR-00:10 | 5.97 | 4.27 |
April | 0.511618E+10 | 6907.63 | 03-APR-05:15 | 10.60 | 9.99 | 0.00 | 0.00 | 01-APR-00:10 | 10.60 | 9.99 |
May | 0.548475E+10 | 7243.71 | 01-MAY-05:15 | 12.20 | 10.44 | 0.00 | 0.00 | 01-MAY-00:10 | 12.20 | 10.44 |
June | 0.684053E+10 | 9062.97 | 12-JUN-05:15 | 14.40 | 13.42 | 0.00 | 0.00 | 01-JUN-00:10 | 14.40 | 13.42 |
July | 0.815971E+10 | 9432.96 | 10-JUL-05:13 | 13.13 | 11.62 | 0.00 | 0.00 | 01-JUL-00:10 | 13.13 | 11.62 |
August | 0.917840E+10 | 10397.80 | 14-AUG-05:15 | 15.33 | 13.50 | 0.00 | 0.00 | 01-AUG-00:10 | 15.33 | 13.50 |
September | 0.585468E+10 | 9694.87 | 11-SEP-15:10 | 23.30 | 15.89 | 0.00 | 0.00 | 01-SEP-00:10 | 23.30 | 15.89 |
October | 0.433278E+10 | 9055.93 | 10-OCT-05:15 | 12.20 | 11.16 | 0.00 | 0.00 | 01-OCT-00:10 | 12.20 | 11.16 |
November | 0.293418E+10 | 6838.16 | 06-NOV-06:15 | 11.47 | 8.44 | 0.00 | 0.00 | 01-NOV-00:10 | 11.47 | 8.44 |
December | 0.219143E+10 | 4591.03 | 05-DEC-06:08 | 2.30 | 1.82 | 0.00 | 0.00 | 01-DEC-00:10 | 2.30 | 1.82 |
Annual Sum or Average | 0.570536E+11 | 0.00 | ||||||||
Minimum of Months | 0.132213E+10 | 3538.42 | -1.8 | -1.8 | 0.00 | 0.00 | -1.8 | -1.8 | ||
Maximum of Months | 0.917840E+10 | 10397.80 | 23.30 | 15.89 | 0.00 | 0.00 | 23.30 | 15.89 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.309572E+09 | 7176.12 | 14-JAN-05:11 | 2.20 | 1.37 | 0.00 | 0.00 | 01-JAN-00:10 | 2.20 | 1.37 |
February | 0.718726E+09 | 6950.05 | 18-FEB-05:01 | -1.2 | -2.4 | 0.00 | 0.00 | 01-FEB-00:10 | -1.2 | -2.4 |
March | 0.150210E+10 | 4209.73 | 06-MAR-05:11 | 6.70 | 6.18 | 0.00 | 0.00 | 01-MAR-00:10 | 6.70 | 6.18 |
April | 0.217312E+10 | 5480.06 | 29-APR-05:10 | 8.40 | 8.40 | 0.00 | 0.00 | 01-APR-00:10 | 8.40 | 8.40 |
May | 0.350949E+10 | 5375.50 | 08-MAY-05:10 | 9.50 | 9.45 | 0.00 | 0.00 | 01-MAY-00:10 | 9.50 | 9.45 |
June | 0.441230E+10 | 5292.05 | 28-JUN-15:40 | 26.10 | 16.04 | 0.00 | 0.00 | 01-JUN-00:10 | 26.10 | 16.04 |
July | 0.531711E+10 | 5762.26 | 31-JUL-15:20 | 28.50 | 19.00 | 0.00 | 0.00 | 01-JUL-00:10 | 28.50 | 19.00 |
August | 0.603896E+10 | 7013.38 | 10-AUG-15:10 | 30.37 | 18.88 | 0.00 | 0.00 | 01-AUG-00:10 | 30.37 | 18.88 |
September | 0.409080E+10 | 6590.77 | 11-SEP-15:10 | 23.30 | 15.89 | 0.00 | 0.00 | 01-SEP-00:10 | 23.30 | 15.89 |
October | 0.224837E+10 | 4884.55 | 05-OCT-05:10 | 8.30 | 5.23 | 0.00 | 0.00 | 01-OCT-00:10 | 8.30 | 5.23 |
November | 0.104548E+10 | 5779.50 | 13-NOV-06:01 | 1.70 | 1.50 | 0.00 | 0.00 | 01-NOV-00:10 | 1.70 | 1.50 |
December | 0.601824E+09 | 6401.76 | 26-DEC-05:01 | -0.6 | -0.6 | 0.00 | 0.00 | 01-DEC-00:10 | -0.6 | -0.6 |
Annual Sum or Average | 0.319679E+11 | 0.00 | ||||||||
Minimum of Months | 0.309572E+09 | 4209.73 | -1.2 | -2.4 | 0.00 | 0.00 | -1.2 | -2.4 | ||
Maximum of Months | 0.603896E+10 | 7176.12 | 30.37 | 19.00 | 0.00 | 0.00 | 30.37 | 19.00 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 206767.31 | 195.20 | 11-JAN-17:30 | 12.50 | 9.44 | 0.00 | 0.00 | 01-JAN-00:10 | 12.50 | 9.44 |
February | 0.149784E+09 | 3106.44 | 27-FEB-15:30 | 19.70 | 12.30 | 0.00 | 0.00 | 01-FEB-00:10 | 19.70 | 12.30 |
March | 0.962342E+09 | 5995.58 | 14-MAR-15:00 | 16.10 | 10.31 | 0.00 | 0.00 | 01-MAR-00:10 | 16.10 | 10.31 |
April | 0.315961E+10 | 15843.29 | 27-APR-14:30 | 26.65 | 17.06 | 0.00 | 0.00 | 01-APR-00:10 | 26.65 | 17.06 |
May | 0.568083E+10 | 16251.60 | 15-MAY-14:20 | 23.30 | 13.21 | 0.00 | 0.00 | 01-MAY-00:10 | 23.30 | 13.21 |
June | 0.740856E+10 | 16652.57 | 28-JUN-14:30 | 25.55 | 15.61 | 0.00 | 0.00 | 01-JUN-00:10 | 25.55 | 15.61 |
July | 0.951821E+10 | 18157.09 | 24-JUL-13:50 | 29.22 | 18.16 | 0.00 | 0.00 | 01-JUL-00:10 | 29.22 | 18.16 |
August | 0.923979E+10 | 19081.06 | 10-AUG-14:30 | 29.80 | 19.03 | 0.00 | 0.00 | 01-AUG-00:10 | 29.80 | 19.03 |
September | 0.481805E+10 | 15340.92 | 11-SEP-14:27 | 23.05 | 15.79 | 0.00 | 0.00 | 01-SEP-00:10 | 23.05 | 15.79 |
October | 0.134047E+10 | 9264.93 | 04-OCT-14:50 | 21.60 | 11.48 | 0.00 | 0.00 | 01-OCT-00:10 | 21.60 | 11.48 |
November | 0.111778E+09 | 3526.20 | 04-NOV-14:00 | 21.10 | 15.94 | 0.00 | 0.00 | 01-NOV-00:10 | 21.10 | 15.94 |
December | 12189.07 | 40.63 | 30-DEC-12:40 | 8.70 | 7.56 | 0.00 | 0.00 | 01-DEC-00:10 | 8.70 | 7.56 |
Annual Sum or Average | 0.423896E+11 | 0.00 | ||||||||
Minimum of Months | 12189.07 | 40.63 | 8.70 | 7.56 | 0.00 | 0.00 | 8.70 | 7.56 | ||
Maximum of Months | 0.951821E+10 | 19081.06 | 29.80 | 19.03 | 0.00 | 0.00 | 29.80 | 19.03 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.295370E+10 | 1993.43 | 05-JAN-16:10 | 5.73 | 4.38 | 95230012.24 | 126.82 | 19-JAN-14:09 | 5.40 | 2.91 |
February | 0.778113E+10 | 4099.86 | 07-FEB-16:50 | 7.30 | 3.84 | 86397249.47 | 126.83 | 24-FEB-10:00 | 13.30 | 12.07 |
March | 0.142392E+11 | 6998.41 | 31-MAR-24:00 | 8.00 | 7.45 | 0.103237E+09 | 126.83 | 10-MAR-10:00 | 8.00 | 7.45 |
April | 0.189139E+11 | 8205.19 | 26-APR-18:00 | 22.80 | 13.49 | 91605347.99 | 126.83 | 28-APR-09:00 | 11.70 | 11.07 |
May | 0.440359E+10 | 3460.90 | 31-MAY-24:00 | 13.00 | 10.11 | 99236364.84 | 126.84 | 31-MAY-13:00 | 13.00 | 10.11 |
June | 0.933334E+10 | 5337.88 | 30-JUN-24:00 | 15.50 | 12.58 | 98961310.15 | 126.84 | 12-JUN-13:00 | 15.50 | 12.58 |
July | 0.148612E+11 | 7260.73 | 31-JUL-23:50 | 17.63 | 14.21 | 91884608.26 | 126.84 | 11-JUL-09:39 | 17.63 | 14.21 |
August | 0.198387E+11 | 8675.41 | 06-AUG-18:33 | 22.47 | 15.07 | 0.103239E+09 | 126.83 | 02-AUG-09:00 | 22.47 | 15.07 |
September | 0.432817E+10 | 3313.27 | 30-SEP-24:00 | 14.30 | 12.32 | 91612444.78 | 126.84 | 13-SEP-13:30 | 14.30 | 12.32 |
October | 0.924301E+10 | 5019.02 | 31-OCT-24:00 | 9.10 | 7.85 | 95231868.08 | 126.83 | 26-OCT-13:00 | 9.10 | 7.85 |
November | 0.136306E+11 | 5792.60 | 10-NOV-16:00 | 8.90 | 6.48 | 94301522.22 | 126.83 | 03-NOV-13:00 | 8.90 | 6.48 |
December | 0.189904E+11 | 7833.47 | 05-DEC-15:50 | 6.75 | 4.97 | 91880901.97 | 126.82 | 28-DEC-14:00 | 11.10 | 9.78 |
Annual Sum or Average | 0.138517E+12 | 0.114282E+10 | ||||||||
Minimum of Months | 0.295370E+10 | 1993.43 | 5.73 | 3.84 | 86397249.47 | 126.82 | 5.40 | 2.91 | ||
Maximum of Months | 0.198387E+11 | 8675.41 | 22.80 | 15.07 | 0.103239E+09 | 126.84 | 22.47 | 15.07 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.824817E+09 | 1586.50 | 05-JAN-16:20 | 5.37 | 4.14 | 95085129.21 | 126.82 | 19-JAN-14:09 | 5.40 | 2.91 |
February | 0.572173E+10 | 3747.15 | 08-FEB-17:00 | 6.70 | 3.26 | 86397178.85 | 126.83 | 24-FEB-10:00 | 13.30 | 12.07 |
March | 0.122146E+11 | 6149.45 | 31-MAR-23:50 | 8.05 | 7.50 | 0.103237E+09 | 126.83 | 09-MAR-14:00 | 8.05 | 7.50 |
April | 0.171677E+11 | 7819.97 | 26-APR-18:00 | 22.80 | 13.49 | 91605415.02 | 126.83 | 28-APR-13:39 | 17.77 | 13.44 |
May | 0.357619E+10 | 3210.11 | 31-MAY-23:50 | 13.17 | 10.29 | 99236115.31 | 126.84 | 31-MAY-13:00 | 13.17 | 10.29 |
June | 0.844612E+10 | 4996.08 | 30-JUN-24:00 | 15.50 | 12.58 | 98960987.88 | 126.84 | 12-JUN-13:00 | 15.50 | 12.58 |
July | 0.138847E+11 | 6987.53 | 31-JUL-24:00 | 17.40 | 14.08 | 91884846.10 | 126.84 | 11-JUL-09:39 | 17.40 | 14.08 |
August | 0.186974E+11 | 8113.36 | 06-AUG-18:35 | 22.47 | 15.07 | 0.103239E+09 | 126.83 | 02-AUG-09:00 | 22.47 | 15.07 |
September | 0.354459E+10 | 2905.99 | 30-SEP-23:50 | 14.25 | 12.27 | 91611900.37 | 126.84 | 13-SEP-13:00 | 14.25 | 12.27 |
October | 0.761509E+10 | 4189.01 | 04-OCT-16:50 | 20.68 | 11.37 | 95231707.10 | 126.83 | 26-OCT-13:00 | 13.30 | 12.35 |
November | 0.112313E+11 | 5357.14 | 10-NOV-16:10 | 8.53 | 6.27 | 94301353.20 | 126.83 | 01-NOV-13:00 | 8.53 | 6.27 |
December | 0.158531E+11 | 7189.70 | 05-DEC-16:00 | 6.10 | 4.53 | 91880925.21 | 126.82 | 28-DEC-14:00 | 11.10 | 9.78 |
Annual Sum or Average | 0.118777E+12 | 0.114267E+10 | ||||||||
Minimum of Months | 0.824817E+09 | 1586.50 | 5.37 | 3.26 | 86397178.85 | 126.82 | 5.40 | 2.91 | ||
Maximum of Months | 0.186974E+11 | 8113.36 | 22.80 | 15.07 | 0.103239E+09 | 126.84 | 22.47 | 15.07 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.325894E+09 | 1440.48 | 05-JAN-16:20 | 5.37 | 4.14 | 93456855.34 | 128.20 | 02-JAN-14:30 | 5.37 | 4.14 |
February | 0.422511E+10 | 3638.57 | 08-FEB-17:00 | 6.70 | 3.26 | 86397245.67 | 126.83 | 24-FEB-10:00 | 13.30 | 12.07 |
March | 0.109658E+11 | 5706.55 | 01-MAR-17:00 | 12.20 | 6.61 | 0.103237E+09 | 126.83 | 09-MAR-14:00 | 14.40 | 11.89 |
April | 0.163937E+11 | 7889.89 | 26-APR-18:00 | 22.80 | 13.49 | 91605434.69 | 126.83 | 28-APR-13:39 | 17.77 | 13.44 |
May | 0.305408E+10 | 3126.33 | 31-MAY-23:30 | 13.50 | 10.66 | 99236411.73 | 126.84 | 31-MAY-13:00 | 13.50 | 10.66 |
June | 0.818597E+10 | 4895.30 | 30-JUN-23:40 | 15.63 | 12.81 | 98961001.88 | 126.84 | 12-JUN-13:00 | 15.63 | 12.81 |
July | 0.137313E+11 | 6962.70 | 31-JUL-24:00 | 17.40 | 14.08 | 91884893.69 | 126.84 | 11-JUL-09:39 | 17.40 | 14.08 |
August | 0.185108E+11 | 8196.84 | 06-AUG-18:21 | 22.80 | 15.13 | 0.103239E+09 | 126.83 | 02-AUG-09:00 | 22.80 | 15.13 |
September | 0.298981E+10 | 2477.39 | 30-SEP-23:20 | 14.10 | 12.13 | 91611273.75 | 126.84 | 13-SEP-13:00 | 14.10 | 12.13 |
October | 0.647648E+10 | 4211.42 | 04-OCT-16:50 | 20.68 | 11.37 | 95231663.73 | 126.83 | 26-OCT-13:00 | 13.30 | 12.35 |
November | 0.968782E+10 | 5205.85 | 10-NOV-16:10 | 8.53 | 6.27 | 94301363.70 | 126.83 | 01-NOV-13:00 | 8.53 | 6.27 |
December | 0.140251E+11 | 6995.45 | 05-DEC-16:00 | 6.10 | 4.53 | 91880937.81 | 126.82 | 28-DEC-14:00 | 11.10 | 9.78 |
Annual Sum or Average | 0.108572E+12 | 0.114104E+10 | ||||||||
Minimum of Months | 0.325894E+09 | 1440.48 | 5.37 | 3.26 | 86397245.67 | 126.82 | 5.37 | 4.14 | ||
Maximum of Months | 0.185108E+11 | 8196.84 | 22.80 | 15.13 | 0.103239E+09 | 128.20 | 22.80 | 15.13 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.237024E+12 | 91559.73 | 12-JAN-17:00 | 7.20 | 5.41 | 0.206144E+10 | 2745.30 | 09-JAN-14:00 | 7.20 | 5.41 |
February | 0.435600E+12 | 183885.11 | 27-FEB-17:00 | 18.90 | 12.17 | 0.187023E+10 | 2745.79 | 22-FEB-14:39 | 18.90 | 12.17 |
March | 0.729965E+12 | 358642.48 | 31-MAR-24:00 | 8.00 | 7.45 | 0.223481E+10 | 2747.26 | 10-MAR-14:00 | 8.00 | 7.45 |
April | 0.944072E+12 | 368241.54 | 27-APR-16:00 | 27.20 | 16.90 | 0.198323E+10 | 2751.37 | 28-APR-13:39 | 17.77 | 13.44 |
May | 0.241581E+12 | 176425.42 | 31-MAY-24:00 | 13.00 | 10.11 | 0.214809E+10 | 2746.26 | 05-MAY-13:00 | 13.00 | 10.11 |
June | 0.471086E+12 | 268006.88 | 30-JUN-24:00 | 15.50 | 12.58 | 0.214221E+10 | 2747.26 | 27-JUN-13:20 | 15.50 | 12.58 |
July | 0.733108E+12 | 360531.89 | 31-JUL-23:53 | 17.40 | 14.08 | 0.199006E+10 | 2750.65 | 11-JUL-13:09 | 17.40 | 14.08 |
August | 0.978630E+12 | 369018.89 | 25-AUG-16:00 | 26.80 | 18.62 | 0.223727E+10 | 2751.94 | 30-AUG-09:09 | 19.33 | 17.24 |
September | 0.235425E+12 | 175700.32 | 30-SEP-24:00 | 14.30 | 12.32 | 0.198297E+10 | 2746.42 | 14-SEP-13:00 | 14.30 | 12.32 |
October | 0.486502E+12 | 267383.89 | 31-OCT-24:00 | 9.10 | 7.85 | 0.206145E+10 | 2746.65 | 06-OCT-13:00 | 9.10 | 7.85 |
November | 0.707482E+12 | 276467.12 | 06-NOV-17:00 | 11.70 | 10.80 | 0.204135E+10 | 2747.85 | 17-NOV-14:30 | 10.30 | 8.83 |
December | 0.975436E+12 | 367853.30 | 05-DEC-17:00 | 6.10 | 4.53 | 0.198901E+10 | 2747.15 | 28-DEC-10:09 | 10.10 | 8.95 |
Annual Sum or Average | 0.717591E+13 | 0.247421E+11 | ||||||||
Minimum of Months | 0.235425E+12 | 91559.73 | 6.10 | 4.53 | 0.187023E+10 | 2745.30 | 7.20 | 5.41 | ||
Maximum of Months | 0.978630E+12 | 369018.89 | 27.20 | 18.62 | 0.223727E+10 | 2751.94 | 19.33 | 17.24 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.144343E+09 | 33532.14 | 02-JAN-05:11 | 6.10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.144343E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.144343E+09 | 33532.14 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.227358E+10 | 75773.95 | 17-JAN-04:51 | 1.70 |
February | 0.898952E+09 | 72575.89 | 21-FEB-04:51 | 1.70 |
March | 0.187905E+09 | 66031.03 | 06-MAR-05:11 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 37154087.28 | 60458.77 | 16-OCT-05:03 | 7.12 |
November | 0.571334E+09 | 68166.28 | 13-NOV-05:01 | 1.20 |
December | 0.123127E+10 | 74013.19 | 26-DEC-04:11 | -0.9 |
Annual Sum or Average | 0.520019E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.9 | |
Maximum of Months | 0.227358E+10 | 75773.95 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 444764.61 | 1833.52 | 09-JAN-06:03 | -1.5 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 444764.61 | |||
Minimum of Months | 0.00 | 0.00 | -1.5 | |
Maximum of Months | 444764.61 | 1833.52 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3374847.07 | 4734.08 | 17-JAN-06:02 | 1.20 |
February | 638436.25 | 2928.53 | 18-FEB-06:01 | -1.8 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 187522.93 | 575.85 | 26-DEC-06:05 | -0.8 |
Annual Sum or Average | 4200806.25 | |||
Minimum of Months | 0.00 | 0.00 | -1.8 | |
Maximum of Months | 3374847.07 | 4734.08 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 47345558.41 | 11257.18 | 17-JAN-05:01 | 1.60 |
February | 8804506.87 | 8035.40 | 18-FEB-06:01 | -1.8 |
March | 2640.27 | 22.00 | 06-MAR-06:04 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 595341.94 | 3965.60 | 13-NOV-06:01 | 1.70 |
December | 6504219.04 | 7878.41 | 26-DEC-06:02 | -0.8 |
Annual Sum or Average | 63252266.53 | |||
Minimum of Months | 0.00 | 0.00 | -1.8 | |
Maximum of Months | 47345558.41 | 11257.18 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.127382E+10 | 11592.35 | 02-JAN-05:11 | 6.10 |
February | 0.525022E+09 | 10797.52 | 21-FEB-05:01 | 1.70 |
March | 87814626.13 | 9962.37 | 06-MAR-05:11 | 6.70 |
April | 7928412.75 | 9284.78 | 19-APR-05:02 | 1.78 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 15766020.71 | 9404.28 | 30-OCT-05:03 | 7.20 |
November | 0.216011E+09 | 10065.61 | 13-NOV-05:01 | 1.20 |
December | 0.762327E+09 | 10902.11 | 26-DEC-04:03 | -1.0 |
Annual Sum or Average | 0.288869E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.127382E+10 | 11592.35 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.844840E+09 | 15112.07 | 02-JAN-05:11 | 6.10 |
February | 0.321289E+09 | 13551.81 | 21-FEB-05:01 | 1.70 |
March | 56993815.71 | 12330.97 | 06-MAR-05:11 | 6.70 |
April | 9077558.71 | 8278.32 | 19-APR-05:02 | 1.78 |
May | 10372.05 | 86.43 | 18-MAY-05:02 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 21107.07 | 140.71 | 27-SEP-05:08 | 7.38 |
October | 13149464.74 | 7604.88 | 31-OCT-05:03 | 8.58 |
November | 0.162613E+09 | 12515.27 | 24-NOV-05:11 | 2.60 |
December | 0.566418E+09 | 13300.81 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.197441E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.844840E+09 | 15112.07 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.832592E+09 | 21743.32 | 02-JAN-05:11 | 6.10 |
February | 0.273546E+09 | 18672.22 | 21-FEB-05:01 | 1.70 |
March | 37125650.68 | 17802.93 | 06-MAR-05:11 | 6.70 |
April | 5048058.00 | 7409.78 | 18-APR-05:03 | 3.30 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 3484046.71 | 6549.77 | 28-OCT-05:03 | 8.22 |
November | 0.149115E+09 | 17930.63 | 24-NOV-05:11 | 2.60 |
December | 0.555788E+09 | 19370.32 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.185670E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.832592E+09 | 21743.32 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.491458E+09 | 13813.36 | 02-JAN-05:11 | 6.10 |
February | 0.174798E+09 | 12065.63 | 21-FEB-05:01 | 1.70 |
March | 16541729.40 | 9436.73 | 06-MAR-06:02 | 6.70 |
April | 1136176.08 | 3101.77 | 19-APR-05:02 | 1.78 |
May | 21021.47 | 175.18 | 18-MAY-05:04 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 1149868.42 | 2601.64 | 28-OCT-05:03 | 8.22 |
November | 68513561.46 | 10884.83 | 13-NOV-06:01 | 1.70 |
December | 0.253142E+09 | 12686.07 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.100676E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.491458E+09 | 13813.36 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.395224E+10 | 13386.67 | 17-JAN-04:51 | 1.70 |
February | 0.234548E+10 | 13313.89 | 20-FEB-05:33 | -0.6 |
March | 0.881236E+09 | 13023.90 | 06-MAR-05:11 | 6.70 |
April | 0.267816E+09 | 11287.82 | 18-APR-04:12 | 2.97 |
May | 18560112.35 | 10696.58 | 18-MAY-05:02 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 10301654.49 | 9484.32 | 27-SEP-05:03 | 7.38 |
October | 0.373887E+09 | 11961.77 | 30-OCT-04:11 | 7.20 |
November | 0.149776E+10 | 13223.56 | 13-NOV-04:01 | 1.60 |
December | 0.317260E+10 | 13408.98 | 26-DEC-04:11 | -0.9 |
Annual Sum or Average | 0.125199E+11 | |||
Minimum of Months | 0.00 | 0.00 | -0.9 | |
Maximum of Months | 0.395224E+10 | 13408.98 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.245378E+10 | 17889.08 | 17-JAN-04:51 | 1.70 |
February | 0.131917E+10 | 17415.50 | 13-FEB-04:11 | 0.77 |
March | 0.495916E+09 | 17424.81 | 06-MAR-05:11 | 6.70 |
April | 0.143437E+09 | 14572.08 | 18-APR-04:12 | 2.97 |
May | 16393334.54 | 13743.37 | 18-MAY-05:02 | 5.60 |
June | 177797.45 | 1463.01 | 14-JUN-05:02 | 10.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 7647853.84 | 8345.84 | 27-SEP-05:03 | 7.38 |
October | 0.240663E+09 | 15366.31 | 30-OCT-04:11 | 7.20 |
November | 0.947479E+09 | 17534.31 | 13-NOV-04:01 | 1.60 |
December | 0.199662E+10 | 17912.03 | 26-DEC-04:11 | -0.9 |
Annual Sum or Average | 0.762128E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.9 | |
Maximum of Months | 0.245378E+10 | 17912.03 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.278943E+10 | 26431.40 | 17-JAN-04:51 | 1.70 |
February | 0.138633E+10 | 25521.18 | 21-FEB-04:51 | 1.70 |
March | 0.598160E+09 | 25563.45 | 06-MAR-05:11 | 6.70 |
April | 0.214265E+09 | 21601.32 | 18-APR-04:12 | 2.97 |
May | 23630190.14 | 20496.21 | 18-MAY-05:02 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 7714682.57 | 9265.38 | 27-SEP-05:03 | 7.38 |
October | 0.244605E+09 | 22343.74 | 16-OCT-04:11 | 7.20 |
November | 0.110112E+10 | 25476.13 | 24-NOV-05:11 | 2.60 |
December | 0.236043E+10 | 26448.76 | 26-DEC-04:11 | -0.9 |
Annual Sum or Average | 0.872568E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.9 | |
Maximum of Months | 0.278943E+10 | 26448.76 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.170449E+10 | 17939.62 | 17-JAN-04:51 | 1.70 |
February | 0.798770E+09 | 17323.64 | 21-FEB-04:51 | 1.70 |
March | 0.303132E+09 | 16404.84 | 06-MAR-05:11 | 6.70 |
April | 79183223.84 | 11721.99 | 19-APR-05:02 | 1.78 |
May | 8475221.74 | 12916.67 | 18-MAY-05:02 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 77273.57 | 509.06 | 18-SEP-05:08 | 12.20 |
October | 0.112793E+09 | 13619.66 | 16-OCT-04:11 | 7.20 |
November | 0.547012E+09 | 16465.82 | 24-NOV-05:11 | 2.60 |
December | 0.119426E+10 | 17787.11 | 26-DEC-04:11 | -0.9 |
Annual Sum or Average | 0.474819E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.9 | |
Maximum of Months | 0.170449E+10 | 17939.62 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.158379E+09 | 10289.72 | 02-JAN-05:11 | 6.10 |
February | 77582766.78 | 9424.82 | 22-FEB-06:03 | 7.62 |
March | 63546077.94 | 10430.94 | 06-MAR-05:11 | 6.70 |
April | 0.109498E+09 | 11354.33 | 10-APR-04:12 | 9.63 |
May | 78993783.12 | 9683.04 | 01-MAY-04:12 | 12.20 |
June | 70757706.16 | 7945.66 | 12-JUN-04:12 | 14.80 |
July | 0.113787E+09 | 10546.50 | 30-JUL-15:51 | 27.80 |
August | 0.111142E+09 | 11144.95 | 06-AUG-15:31 | 23.77 |
September | 53495271.14 | 10170.08 | 10-SEP-15:12 | 22.60 |
October | 78952280.05 | 9317.10 | 23-OCT-04:12 | 10.60 |
November | 65051898.14 | 11483.28 | 27-NOV-05:11 | 12.03 |
December | 69647067.21 | 11378.27 | 27-DEC-05:11 | 4.60 |
Annual Sum or Average | 0.105083E+10 | |||
Minimum of Months | 53495271.14 | 7945.66 | 4.60 | |
Maximum of Months | 0.158379E+09 | 11483.28 | 27.80 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.189436E+10 | 9754.76 | 02-JAN-06:10 | 6.10 |
February | 0.888453E+09 | 11607.23 | 12-FEB-13:42 | 6.60 |
March | 0.256463E+09 | 5767.96 | 15-MAR-05:03 | 8.03 |
April | 59913181.06 | 10693.98 | 02-APR-15:22 | 20.60 |
May | 68011843.20 | 11852.25 | 14-MAY-15:01 | 23.30 |
June | 47009270.86 | 6280.79 | 18-JUN-16:51 | 17.20 |
July | 61152041.81 | 9303.86 | 30-JUL-15:22 | 27.50 |
August | 52587567.08 | 11369.14 | 06-AUG-15:41 | 23.78 |
September | 43213908.20 | 11701.39 | 10-SEP-15:01 | 22.70 |
October | 0.126292E+09 | 8981.64 | 29-OCT-13:53 | 11.70 |
November | 0.446953E+09 | 7659.31 | 11-NOV-12:53 | 6.70 |
December | 0.990253E+09 | 4704.01 | 03-DEC-11:50 | 11.52 |
Annual Sum or Average | 0.493466E+10 | |||
Minimum of Months | 43213908.20 | 4704.01 | 6.10 | |
Maximum of Months | 0.189436E+10 | 11852.25 | 27.50 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.706073E+10 | 23612.53 | 17-JAN-05:13 | 1.50 |
February | 0.425016E+10 | 21935.49 | 21-FEB-05:23 | 1.70 |
March | 0.230688E+10 | 13208.56 | 06-MAR-06:02 | 6.70 |
April | 0.106116E+10 | 12663.46 | 27-APR-05:03 | 9.37 |
May | 0.448876E+09 | 13662.67 | 04-MAY-05:03 | 10.78 |
June | 0.188649E+09 | 14141.46 | 02-JUN-05:03 | 10.18 |
July | 0.103105E+09 | 12779.85 | 18-JUL-05:03 | 12.80 |
August | 0.136255E+09 | 12230.18 | 22-AUG-05:03 | 13.02 |
September | 0.410995E+09 | 13287.63 | 08-SEP-05:03 | 10.18 |
October | 0.146258E+10 | 8815.13 | 05-OCT-05:03 | 8.30 |
November | 0.336094E+10 | 17160.64 | 13-NOV-06:13 | 1.70 |
December | 0.590028E+10 | 21183.59 | 26-DEC-05:13 | -0.6 |
Annual Sum or Average | 0.266906E+11 | |||
Minimum of Months | 0.103105E+09 | 8815.13 | -0.6 | |
Maximum of Months | 0.706073E+10 | 23612.53 | 13.02 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.224242E+09 | 557.41 | 01-JAN-19:15 | 6.10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.224242E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.224242E+09 | 557.41 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.721612E+09 | 618.49 | 08-JAN-17:30 | 2.75 |
February | 15084895.27 | 392.09 | 20-FEB-22:25 | 4.15 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 422666.69 | 379.67 | 29-MAY-06:00 | 10.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.737120E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.75 | |
Maximum of Months | 0.721612E+09 | 618.49 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180249E+11 | 19402.09 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.163527E+11 | 19402.09 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.194806E+11 | 19402.09 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.173504E+11 | 19402.09 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.187528E+11 | 19402.09 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.186803E+11 | 19402.09 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.174228E+11 | 19402.09 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.194803E+11 | 19402.09 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.173504E+11 | 19402.09 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.180252E+11 | 19402.09 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.178272E+11 | 19402.09 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.174231E+11 | 19402.09 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.216171E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.163527E+11 | 19402.09 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.194806E+11 | 19402.09 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.146182E+10 | 2187.81 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.117928E+10 | 2187.81 | 01-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.127464E+10 | 1906.53 | 07-MAR-16:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.106298E+10 | 1524.25 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.111509E+10 | 1141.96 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.108890E+10 | 1141.96 | 16-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.102185E+10 | 1524.25 | 12-JUL-07:40 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.115953E+10 | 1242.97 | 02-AUG-07:19 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.110391E+10 | 1906.53 | 21-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.125766E+10 | 2187.81 | 20-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.140440E+10 | 2187.81 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.146495E+10 | 2187.81 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.145950E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.102185E+10 | 1141.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.146495E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.902045E+09 | 1409.91 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.742169E+09 | 1409.91 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.812092E+09 | 1228.64 | 03-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.684194E+09 | 801.02 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.722642E+09 | 735.93 | 05-MAY-14:30 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.707192E+09 | 735.93 | 08-JUN-15:30 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.662148E+09 | 735.93 | 12-JUL-07:49 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.751594E+09 | 801.02 | 02-AUG-07:30 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.702896E+09 | 1228.64 | 21-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.790701E+09 | 1409.91 | 26-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.876419E+09 | 1409.91 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.900299E+09 | 1409.91 | 01-DEC-16:10 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.925439E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.662148E+09 | 735.93 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.902045E+09 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135269E+10 | 2187.86 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.111619E+10 | 2187.86 | 02-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.124827E+10 | 1906.57 | 13-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.106210E+10 | 1524.28 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.112134E+10 | 1141.99 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.109679E+10 | 1141.99 | 16-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.103310E+10 | 1524.28 | 12-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.116872E+10 | 1243.00 | 02-AUG-07:19 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.109151E+10 | 1906.57 | 21-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.120536E+10 | 2187.86 | 26-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.131740E+10 | 2187.86 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.134130E+10 | 2187.86 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.141548E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.103310E+10 | 1141.99 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.135269E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.900768E+09 | 1409.91 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.733122E+09 | 1409.91 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.812147E+09 | 1228.64 | 13-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.685010E+09 | 982.28 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.719977E+09 | 801.02 | 02-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.702897E+09 | 735.93 | 05-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.662684E+09 | 982.28 | 12-JUL-07:19 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.749108E+09 | 982.28 | 02-AUG-07:30 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.710485E+09 | 1228.64 | 21-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.792032E+09 | 1409.91 | 20-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.871574E+09 | 1409.91 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.899298E+09 | 1409.91 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.923910E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.662684E+09 | 735.93 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.900768E+09 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.145393E+10 | 2187.81 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.117369E+10 | 2187.81 | 01-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.127026E+10 | 1906.53 | 07-MAR-16:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.106105E+10 | 1524.25 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.111407E+10 | 1141.96 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.108765E+10 | 1141.96 | 16-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.102000E+10 | 1524.25 | 12-JUL-07:49 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.115752E+10 | 1242.97 | 02-AUG-07:19 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.110126E+10 | 1906.53 | 21-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.125129E+10 | 2187.81 | 20-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.139777E+10 | 2187.81 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.145809E+10 | 2187.81 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.145466E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.102000E+10 | 1141.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.145809E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.898240E+09 | 1409.91 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.739129E+09 | 1409.91 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.810487E+09 | 1228.64 | 03-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.682843E+09 | 801.02 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.721761E+09 | 735.93 | 05-MAY-14:30 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.706480E+09 | 670.83 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.661473E+09 | 735.93 | 12-JUL-07:49 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.750582E+09 | 801.02 | 02-AUG-07:30 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.701731E+09 | 1228.64 | 21-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.788375E+09 | 1409.91 | 27-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.872048E+09 | 1409.91 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.897076E+09 | 1409.91 | 01-DEC-16:10 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.923022E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.661473E+09 | 670.83 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.898240E+09 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135058E+10 | 2187.86 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.111391E+10 | 2187.86 | 02-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.124648E+10 | 1906.57 | 13-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.106089E+10 | 1524.28 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.112012E+10 | 1141.99 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.109574E+10 | 1141.99 | 16-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.103152E+10 | 1524.28 | 12-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.116715E+10 | 1243.00 | 02-AUG-07:19 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.109010E+10 | 1906.57 | 21-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.120357E+10 | 2187.86 | 26-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.131535E+10 | 2187.86 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.133891E+10 | 2187.86 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.141343E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.103152E+10 | 1141.99 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.135058E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.897039E+09 | 1409.91 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.731157E+09 | 1409.91 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.810092E+09 | 1228.64 | 13-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.683680E+09 | 982.28 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.719003E+09 | 801.02 | 02-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.702338E+09 | 735.93 | 05-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.661878E+09 | 982.28 | 12-JUL-07:19 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.748359E+09 | 982.28 | 02-AUG-07:30 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.708593E+09 | 1228.64 | 21-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.790009E+09 | 1409.91 | 20-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.868315E+09 | 1409.91 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.895659E+09 | 1409.91 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.921612E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.661878E+09 | 735.93 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.897039E+09 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.145362E+10 | 2187.81 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.117342E+10 | 2187.81 | 01-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.127017E+10 | 1906.53 | 07-MAR-16:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.106097E+10 | 1524.25 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.111390E+10 | 1141.96 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.108759E+10 | 1141.96 | 16-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.101995E+10 | 1524.25 | 12-JUL-07:49 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.115749E+10 | 1242.97 | 02-AUG-07:19 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.110079E+10 | 1906.53 | 21-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.125104E+10 | 2187.81 | 20-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.139753E+10 | 2187.81 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.145786E+10 | 2187.81 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.145443E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.101995E+10 | 1141.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.145786E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.898116E+09 | 1409.91 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.739041E+09 | 1409.91 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.810359E+09 | 1228.64 | 03-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.682695E+09 | 801.02 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.721744E+09 | 735.93 | 05-MAY-14:30 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.706429E+09 | 670.83 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.661408E+09 | 735.93 | 12-JUL-07:00 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.750542E+09 | 801.02 | 02-AUG-07:30 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.701791E+09 | 1228.64 | 21-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.788347E+09 | 1409.91 | 27-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.871419E+09 | 1409.91 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.896730E+09 | 1409.91 | 01-DEC-16:10 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.922862E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.661408E+09 | 670.83 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.898116E+09 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135035E+10 | 2187.86 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.111380E+10 | 2187.86 | 02-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.124640E+10 | 1906.57 | 13-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.106079E+10 | 1524.28 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.112010E+10 | 1141.99 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.109571E+10 | 1141.99 | 16-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.103120E+10 | 1243.00 | 12-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.116714E+10 | 1243.00 | 02-AUG-07:19 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.109002E+10 | 1906.57 | 21-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.120324E+10 | 2187.86 | 26-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.131512E+10 | 2187.86 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.133851E+10 | 2187.86 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.141324E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.103120E+10 | 1141.99 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.135035E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.896959E+09 | 1409.91 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.731118E+09 | 1409.91 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.809936E+09 | 1228.64 | 13-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.683574E+09 | 982.28 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.718965E+09 | 801.02 | 02-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.702237E+09 | 735.93 | 05-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.661821E+09 | 982.28 | 12-JUL-07:19 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.748325E+09 | 982.28 | 02-AUG-07:30 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.708550E+09 | 1228.64 | 21-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.789979E+09 | 1409.91 | 20-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.868202E+09 | 1409.91 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.895560E+09 | 1409.91 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.921523E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.661821E+09 | 735.93 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.896959E+09 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.522764E+10 | 5470.56 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.474186E+10 | 5470.56 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.563465E+10 | 5470.56 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.503289E+10 | 5470.56 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.543115E+10 | 5470.56 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.540489E+10 | 5470.56 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.505915E+10 | 5470.56 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.563465E+10 | 5470.56 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.503289E+10 | 5470.56 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.522764E+10 | 5470.56 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.516637E+10 | 5470.56 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.505915E+10 | 5470.56 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.626529E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.474186E+10 | 5470.56 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.563465E+10 | 5470.56 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.180249E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.163527E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.194806E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.173504E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.187528E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.186803E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.174228E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.194803E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.173504E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.180252E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.178272E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.174231E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.216171E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.163527E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.194806E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.146182E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364893E+09 |
February | 0.136985E+10 | 0.117928E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325247E+09 |
March | 0.163685E+10 | 0.127464E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313228E+09 |
April | 0.145243E+10 | 0.106298E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 425847.78 | 0.296611E+09 |
May | 0.157338E+10 | 0.111509E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17302.60 | 0.226175E+09 |
June | 0.156900E+10 | 0.108890E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 173868.07 | 0.188068E+09 |
July | 0.145680E+10 | 0.102185E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2205902.67 | 0.156085E+09 |
August | 0.163685E+10 | 0.115953E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3702601.40 | 0.126097E+09 |
September | 0.145243E+10 | 0.110391E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17242.18 | 0.105548E+09 |
October | 0.150991E+10 | 0.125766E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251037E+09 |
November | 0.149516E+10 | 0.140440E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292093E+09 |
December | 0.145680E+10 | 0.146495E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318658E+09 |
Annual Sum or Average | 0.181194E+11 | 0.145950E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 6542764.69 | 0.296374E+10 |
Minimum of Months | 0.136985E+10 | 0.102185E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105548E+09 |
Maximum of Months | 0.163685E+10 | 0.146495E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3702601.40 | 0.364893E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.902045E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237904E+09 |
February | 0.882782E+09 | 0.742169E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212995E+09 |
March | 0.105485E+10 | 0.812092E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202609E+09 |
April | 0.936002E+09 | 0.684194E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 345765.38 | 0.191099E+09 |
May | 0.101394E+10 | 0.722642E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11534.68 | 0.148722E+09 |
June | 0.101113E+10 | 0.707192E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 115909.67 | 0.123190E+09 |
July | 0.938820E+09 | 0.662148E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1437150.61 | 98998109.40 |
August | 0.105485E+10 | 0.751594E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2487861.66 | 78724661.55 |
September | 0.936002E+09 | 0.702896E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11494.20 | 69136333.83 |
October | 0.973041E+09 | 0.790701E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162150E+09 |
November | 0.963541E+09 | 0.876419E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185834E+09 |
December | 0.938820E+09 | 0.900299E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202717E+09 |
Annual Sum or Average | 0.116768E+11 | 0.925439E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4409716.20 | 0.191408E+10 |
Minimum of Months | 0.882782E+09 | 0.662148E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69136333.83 |
Maximum of Months | 0.105485E+10 | 0.902045E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2487861.66 | 0.237904E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.135269E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351786E+09 |
February | 0.136988E+10 | 0.111619E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325512E+09 |
March | 0.163688E+10 | 0.124827E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309182E+09 |
April | 0.145246E+10 | 0.106210E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 379753.90 | 0.292646E+09 |
May | 0.157341E+10 | 0.112134E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17300.45 | 0.224839E+09 |
June | 0.156904E+10 | 0.109679E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 173859.74 | 0.186425E+09 |
July | 0.145684E+10 | 0.103310E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1658141.19 | 0.154324E+09 |
August | 0.163688E+10 | 0.116872E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3556129.39 | 0.124997E+09 |
September | 0.145246E+10 | 0.109151E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17107.02 | 0.107447E+09 |
October | 0.150994E+10 | 0.120536E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249935E+09 |
November | 0.149520E+10 | 0.131740E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281110E+09 |
December | 0.145684E+10 | 0.134130E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306970E+09 |
Annual Sum or Average | 0.181198E+11 | 0.141548E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5802291.69 | 0.291518E+10 |
Minimum of Months | 0.136988E+10 | 0.103310E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107447E+09 |
Maximum of Months | 0.163688E+10 | 0.135269E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3556129.39 | 0.351786E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.900768E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251833E+09 |
February | 0.882782E+09 | 0.733122E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233301E+09 |
March | 0.105485E+10 | 0.812147E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228929E+09 |
April | 0.936002E+09 | 0.685010E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 156327.32 | 0.220971E+09 |
May | 0.101394E+10 | 0.719977E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11534.48 | 0.162276E+09 |
June | 0.101113E+10 | 0.702897E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 115904.69 | 0.137963E+09 |
July | 0.938820E+09 | 0.662684E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 982889.32 | 0.119735E+09 |
August | 0.105485E+10 | 0.749108E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2348207.91 | 98171514.00 |
September | 0.936002E+09 | 0.710485E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11493.10 | 77297739.84 |
October | 0.973041E+09 | 0.792032E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182062E+09 |
November | 0.963541E+09 | 0.871574E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212780E+09 |
December | 0.938820E+09 | 0.899298E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236101E+09 |
Annual Sum or Average | 0.116768E+11 | 0.923910E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3626356.82 | 0.216142E+10 |
Minimum of Months | 0.882782E+09 | 0.662684E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77297739.84 |
Maximum of Months | 0.105485E+10 | 0.900768E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2348207.91 | 0.251833E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.145393E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.726054E+09 |
February | 0.136985E+10 | 0.117369E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655622E+09 |
March | 0.163685E+10 | 0.127026E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.643080E+09 |
April | 0.145243E+10 | 0.106105E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1432329.44 | 0.619971E+09 |
May | 0.157338E+10 | 0.111407E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28809.16 | 0.495365E+09 |
June | 0.156900E+10 | 0.108765E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 358111.30 | 0.412375E+09 |
July | 0.145680E+10 | 0.102000E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6653891.87 | 0.345347E+09 |
August | 0.163685E+10 | 0.115752E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9176431.85 | 0.281362E+09 |
September | 0.145243E+10 | 0.110126E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30209.68 | 0.227213E+09 |
October | 0.150991E+10 | 0.125129E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512560E+09 |
November | 0.149516E+10 | 0.139777E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.578494E+09 |
December | 0.145680E+10 | 0.145809E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624335E+09 |
Annual Sum or Average | 0.181194E+11 | 0.145466E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 17679783.29 | 0.612178E+10 |
Minimum of Months | 0.136985E+10 | 0.102000E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227213E+09 |
Maximum of Months | 0.163685E+10 | 0.145809E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9176431.85 | 0.726054E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.898240E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482711E+09 |
February | 0.649041E+09 | 0.739129E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443944E+09 |
March | 0.773965E+09 | 0.810487E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430977E+09 |
April | 0.688021E+09 | 0.682843E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 890819.56 | 0.419036E+09 |
May | 0.744847E+09 | 0.721761E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19198.56 | 0.331239E+09 |
June | 0.742030E+09 | 0.706480E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 238722.16 | 0.278548E+09 |
July | 0.690839E+09 | 0.661473E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3116952.76 | 0.230835E+09 |
August | 0.773965E+09 | 0.750582E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5556928.74 | 0.190418E+09 |
September | 0.688021E+09 | 0.701731E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20167.11 | 0.152003E+09 |
October | 0.715730E+09 | 0.788375E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342018E+09 |
November | 0.708685E+09 | 0.872048E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381994E+09 |
December | 0.690839E+09 | 0.897076E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415427E+09 |
Annual Sum or Average | 0.858171E+10 | 0.923022E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9842788.89 | 0.409915E+10 |
Minimum of Months | 0.649041E+09 | 0.661473E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152003E+09 |
Maximum of Months | 0.773965E+09 | 0.898240E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5556928.74 | 0.482711E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.135058E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.756807E+09 |
February | 0.136988E+10 | 0.111391E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717245E+09 |
March | 0.163688E+10 | 0.124648E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681420E+09 |
April | 0.145246E+10 | 0.106089E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 852196.73 | 0.648570E+09 |
May | 0.157341E+10 | 0.112012E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28803.43 | 0.507760E+09 |
June | 0.156904E+10 | 0.109574E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 358085.47 | 0.418390E+09 |
July | 0.145684E+10 | 0.103152E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3567192.18 | 0.354162E+09 |
August | 0.163688E+10 | 0.116715E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7995372.70 | 0.294338E+09 |
September | 0.145246E+10 | 0.109010E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29735.22 | 0.243868E+09 |
October | 0.150994E+10 | 0.120357E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554125E+09 |
November | 0.149520E+10 | 0.131535E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.601820E+09 |
December | 0.145684E+10 | 0.133891E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.654577E+09 |
Annual Sum or Average | 0.181198E+11 | 0.141343E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12831385.73 | 0.643308E+10 |
Minimum of Months | 0.136988E+10 | 0.103152E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243868E+09 |
Maximum of Months | 0.163688E+10 | 0.135058E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7995372.70 | 0.756807E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.897039E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498654E+09 |
February | 0.882782E+09 | 0.731157E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458410E+09 |
March | 0.105485E+10 | 0.810092E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447648E+09 |
April | 0.936002E+09 | 0.683680E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 354228.44 | 0.435698E+09 |
May | 0.101394E+10 | 0.719003E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19180.93 | 0.350715E+09 |
June | 0.101113E+10 | 0.702338E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 238697.66 | 0.289864E+09 |
July | 0.938820E+09 | 0.661878E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2648018.89 | 0.255165E+09 |
August | 0.105485E+10 | 0.748359E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5584635.31 | 0.207561E+09 |
September | 0.936002E+09 | 0.708593E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20135.62 | 0.164312E+09 |
October | 0.973041E+09 | 0.790009E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357182E+09 |
November | 0.963541E+09 | 0.868315E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395643E+09 |
December | 0.938820E+09 | 0.895659E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431053E+09 |
Annual Sum or Average | 0.116768E+11 | 0.921612E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8864896.85 | 0.429191E+10 |
Minimum of Months | 0.882782E+09 | 0.661878E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164312E+09 |
Maximum of Months | 0.105485E+10 | 0.897039E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5584635.31 | 0.498654E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.145362E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.838690E+09 |
February | 0.136985E+10 | 0.117342E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.746679E+09 |
March | 0.163685E+10 | 0.127017E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.732866E+09 |
April | 0.145243E+10 | 0.106097E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1841850.80 | 0.717877E+09 |
May | 0.157338E+10 | 0.111390E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23380.91 | 0.587634E+09 |
June | 0.156900E+10 | 0.108759E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 387706.21 | 0.497767E+09 |
July | 0.145680E+10 | 0.101995E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6881138.53 | 0.420895E+09 |
August | 0.163685E+10 | 0.115749E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10621896.27 | 0.340153E+09 |
September | 0.145243E+10 | 0.110079E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26052.87 | 0.265204E+09 |
October | 0.150991E+10 | 0.125104E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.574853E+09 |
November | 0.149516E+10 | 0.139753E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648821E+09 |
December | 0.145680E+10 | 0.145786E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703852E+09 |
Annual Sum or Average | 0.181194E+11 | 0.145443E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 19782025.59 | 0.707529E+10 |
Minimum of Months | 0.136985E+10 | 0.101995E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265204E+09 |
Maximum of Months | 0.163685E+10 | 0.145786E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10621896.27 | 0.838690E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.898116E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559055E+09 |
February | 0.882782E+09 | 0.739041E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.505633E+09 |
March | 0.105485E+10 | 0.810359E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496396E+09 |
April | 0.936002E+09 | 0.682695E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1085854.25 | 0.491332E+09 |
May | 0.101394E+10 | 0.721744E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15585.90 | 0.397335E+09 |
June | 0.101113E+10 | 0.706429E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 258460.58 | 0.339465E+09 |
July | 0.938820E+09 | 0.661408E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3147166.88 | 0.283874E+09 |
August | 0.105485E+10 | 0.750542E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6478900.47 | 0.232662E+09 |
September | 0.936002E+09 | 0.701791E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17366.43 | 0.180297E+09 |
October | 0.973041E+09 | 0.788347E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390138E+09 |
November | 0.963541E+09 | 0.871419E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432517E+09 |
December | 0.938820E+09 | 0.896730E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470338E+09 |
Annual Sum or Average | 0.116768E+11 | 0.922862E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 11003334.51 | 0.477904E+10 |
Minimum of Months | 0.882782E+09 | 0.661408E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180297E+09 |
Maximum of Months | 0.105485E+10 | 0.898116E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6478900.47 | 0.559055E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.135035E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.867366E+09 |
February | 0.136988E+10 | 0.111380E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.815767E+09 |
March | 0.163688E+10 | 0.124640E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.785906E+09 |
April | 0.145246E+10 | 0.106079E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1021566.54 | 0.759189E+09 |
May | 0.157341E+10 | 0.112010E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23375.21 | 0.605905E+09 |
June | 0.156904E+10 | 0.109571E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 387680.86 | 0.505467E+09 |
July | 0.145684E+10 | 0.103120E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4037048.20 | 0.432498E+09 |
August | 0.163688E+10 | 0.116714E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9512499.34 | 0.356907E+09 |
September | 0.145246E+10 | 0.109002E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25808.07 | 0.288652E+09 |
October | 0.150994E+10 | 0.120324E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.635325E+09 |
November | 0.149520E+10 | 0.131512E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681145E+09 |
December | 0.145684E+10 | 0.133851E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.740877E+09 |
Annual Sum or Average | 0.181198E+11 | 0.141324E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 15007978.22 | 0.747501E+10 |
Minimum of Months | 0.136988E+10 | 0.103120E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288652E+09 |
Maximum of Months | 0.163688E+10 | 0.135035E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9512499.34 | 0.867366E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.896959E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576062E+09 |
February | 0.882782E+09 | 0.731118E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529331E+09 |
March | 0.105485E+10 | 0.809936E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521881E+09 |
April | 0.936002E+09 | 0.683574E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 418411.46 | 0.513641E+09 |
May | 0.101394E+10 | 0.718965E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15585.95 | 0.420848E+09 |
June | 0.101113E+10 | 0.702237E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 258413.49 | 0.351210E+09 |
July | 0.938820E+09 | 0.661821E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3015767.44 | 0.312442E+09 |
August | 0.105485E+10 | 0.748325E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6634572.00 | 0.252194E+09 |
September | 0.936002E+09 | 0.708550E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17365.91 | 0.195536E+09 |
October | 0.973041E+09 | 0.789979E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413057E+09 |
November | 0.963541E+09 | 0.868202E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456035E+09 |
December | 0.938820E+09 | 0.895560E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.495957E+09 |
Annual Sum or Average | 0.116768E+11 | 0.921523E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10360116.25 | 0.503819E+10 |
Minimum of Months | 0.882782E+09 | 0.661821E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195536E+09 |
Maximum of Months | 0.105485E+10 | 0.896959E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6634572.00 | 0.576062E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.522764E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.474186E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.563465E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.503289E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.543115E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.540489E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.505915E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.563465E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.503289E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.522764E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.516637E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.505915E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.626529E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.474186E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.563465E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.784987E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.697732E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.665384E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 631341.16 | 0.623908E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2248.48 | 0.476363E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135594.36 | 0.393486E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3585323.02 | 0.328452E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5934119.37 | 0.271476E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1275.42 | 0.224869E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534729E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.620047E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.680496E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10289901.81 | 0.630193E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224869E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5934119.37 | 0.784987E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126885E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115819E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112510E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1647841.05 | 0.105905E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3828.85 | 0.830782E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251394.77 | 0.683545E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8133304.94 | 0.570315E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11320744.38 | 0.474481E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1916.50 | 0.390497E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.902510E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102176E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110689E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21359030.48 | 0.105920E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390497E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11320744.38 | 0.126885E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127696E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117236E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116642E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1315417.36 | 0.114036E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.928355E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71826.17 | 0.780275E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2659733.37 | 0.659631E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8030891.66 | 0.535536E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423320E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.926063E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102269E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109674E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12077868.56 | 0.111287E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423320E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8030891.66 | 0.127696E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 19402.09 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 19402.09 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 19402.09 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 19402.09 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 19402.09 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 19402.09 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 19402.09 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 19402.09 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 19402.09 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 19402.09 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 19402.09 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 19402.09 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 19402.09 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 19402.09 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2187.81 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 598.75 | 28-JAN-04:00 |
February | 2010.79 | 01-FEB-10:09 | 2187.81 | 01-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 561.37 | 16-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 1906.53 | 07-MAR-16:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 527.40 | 28-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 1524.25 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.91 | 01-APR-17:10 | 541.74 | 07-APR-24:00 |
May | 2010.79 | 01-MAY-09:09 | 1141.96 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.05 | 05-MAY-16:00 | 384.81 | 18-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 1141.96 | 16-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.61 | 28-JUN-16:00 | 532.06 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 1524.25 | 12-JUL-07:40 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.07 | 23-JUL-16:00 | 270.97 | 02-JUL-04:00 |
August | 2010.79 | 01-AUG-09:09 | 1242.97 | 02-AUG-07:19 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.26 | 08-AUG-17:00 | 351.39 | 11-AUG-04:00 |
September | 2010.79 | 01-SEP-09:09 | 1906.53 | 21-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.45 | 14-SEP-17:00 | 256.38 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 2187.81 | 20-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 471.20 | 31-OCT-21:10 |
November | 2010.79 | 01-NOV-09:09 | 2187.81 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 573.83 | 29-NOV-23:00 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 472.80 | 17-DEC-20:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.38 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 58.07 | 598.75 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 388.27 | 28-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 362.81 | 16-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 1228.64 | 03-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 345.24 | 28-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 801.02 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.38 | 01-APR-17:10 | 353.94 | 07-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 735.93 | 05-MAY-14:30 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.37 | 05-MAY-16:00 | 251.88 | 22-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 735.93 | 08-JUN-15:30 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.07 | 28-JUN-16:00 | 346.03 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 735.93 | 12-JUL-07:49 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.00 | 23-JUL-16:00 | 173.41 | 02-JUL-04:00 |
August | 1295.83 | 01-AUG-09:09 | 801.02 | 02-AUG-07:30 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.73 | 13-AUG-15:30 | 224.93 | 11-AUG-04:00 |
September | 1295.83 | 01-SEP-09:09 | 1228.64 | 21-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.64 | 14-SEP-17:00 | 165.99 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 26-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 297.43 | 31-OCT-21:10 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 365.44 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-16:10 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 302.67 | 17-DEC-20:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 735.93 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.99 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 42.38 | 388.27 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2187.86 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 571.92 | 12-JAN-24:00 |
February | 2010.83 | 01-FEB-10:09 | 2187.86 | 02-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 577.55 | 19-FEB-12:00 |
March | 2010.83 | 01-MAR-10:09 | 1906.57 | 13-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 530.97 | 28-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 1524.28 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.49 | 01-APR-17:10 | 538.78 | 07-APR-24:00 |
May | 2010.83 | 01-MAY-09:09 | 1141.99 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.05 | 05-MAY-16:00 | 378.89 | 22-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 1141.99 | 16-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.61 | 28-JUN-16:00 | 517.52 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 1524.28 | 12-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.51 | 23-JUL-16:00 | 265.40 | 02-JUL-04:00 |
August | 2010.83 | 01-AUG-09:09 | 1243.00 | 02-AUG-07:19 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.26 | 08-AUG-17:00 | 355.64 | 11-AUG-04:00 |
September | 2010.83 | 01-SEP-09:09 | 1906.57 | 21-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.45 | 14-SEP-17:00 | 247.60 | 18-SEP-23:00 |
October | 2010.83 | 02-OCT-09:09 | 2187.86 | 26-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 445.58 | 31-OCT-21:10 |
November | 2010.83 | 01-NOV-09:09 | 2187.86 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 547.96 | 29-NOV-23:00 |
December | 2010.83 | 01-DEC-10:09 | 2187.86 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 435.33 | 02-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1141.99 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.60 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 48.51 | 577.55 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 417.35 | 28-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 399.29 | 16-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 1228.64 | 13-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 390.75 | 28-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 982.28 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.98 | 01-APR-16:00 | 405.53 | 07-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 801.02 | 02-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.37 | 05-MAY-16:00 | 271.55 | 22-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 735.93 | 05-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.07 | 28-JUN-16:00 | 386.39 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 982.28 | 12-JUL-07:19 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.86 | 23-JUL-13:55 | 209.50 | 02-JUL-04:00 |
August | 1295.83 | 01-AUG-09:09 | 982.28 | 02-AUG-07:30 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 08-AUG-17:00 | 276.65 | 11-AUG-04:00 |
September | 1295.83 | 01-SEP-09:09 | 1228.64 | 21-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.63 | 14-SEP-17:00 | 181.54 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 20-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 327.82 | 31-OCT-21:20 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 414.66 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 352.75 | 17-DEC-20:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 735.93 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.54 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 21.86 | 417.35 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2187.81 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1226.99 | 12-JAN-24:00 |
February | 2010.79 | 01-FEB-10:09 | 2187.81 | 01-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1124.11 | 16-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 1906.53 | 07-MAR-16:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1081.22 | 28-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 1524.25 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 176.76 | 01-APR-17:02 | 1135.14 | 07-APR-24:00 |
May | 2010.79 | 01-MAY-09:09 | 1141.96 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.29 | 05-MAY-16:00 | 835.02 | 18-MAY-04:55 |
June | 2010.79 | 01-JUN-09:09 | 1141.96 | 16-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.92 | 28-JUN-16:00 | 1118.49 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 1524.25 | 12-JUL-07:49 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.30 | 23-JUL-16:00 | 563.69 | 02-JUL-04:00 |
August | 2010.79 | 01-AUG-09:09 | 1242.97 | 02-AUG-07:19 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.37 | 13-AUG-15:00 | 792.86 | 11-AUG-04:00 |
September | 2010.79 | 01-SEP-09:09 | 1906.53 | 21-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.13 | 14-SEP-17:00 | 543.40 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 2187.81 | 20-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 982.94 | 31-OCT-21:03 |
November | 2010.79 | 01-NOV-09:09 | 2187.81 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1161.56 | 29-NOV-23:00 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 922.85 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 543.40 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 176.76 | 1226.99 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1409.91 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 807.96 | 12-JAN-24:00 |
February | 1239.33 | 01-FEB-08:09 | 1409.91 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 754.19 | 19-FEB-10:00 |
March | 1239.33 | 01-MAR-08:09 | 1228.64 | 03-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 733.53 | 28-MAR-24:00 |
April | 1239.33 | 03-APR-07:10 | 801.02 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.05 | 01-APR-17:02 | 769.59 | 07-APR-24:00 |
May | 1239.33 | 01-MAY-07:10 | 735.93 | 05-MAY-14:30 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.86 | 05-MAY-16:00 | 549.18 | 22-MAY-24:00 |
June | 1239.33 | 01-JUN-07:10 | 670.83 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.28 | 28-JUN-16:00 | 740.13 | 13-JUN-03:00 |
July | 1239.33 | 03-JUL-07:10 | 735.93 | 12-JUL-07:49 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.64 | 23-JUL-16:00 | 371.67 | 02-JUL-09:58 |
August | 1239.33 | 01-AUG-07:10 | 801.02 | 02-AUG-07:30 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.42 | 08-AUG-17:00 | 539.04 | 11-AUG-04:00 |
September | 1239.33 | 01-SEP-07:10 | 1228.64 | 21-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.42 | 14-SEP-17:00 | 350.44 | 18-SEP-23:00 |
October | 1239.33 | 02-OCT-07:10 | 1409.91 | 27-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 653.28 | 31-OCT-21:03 |
November | 1239.33 | 01-NOV-07:10 | 1409.91 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 767.36 | 29-NOV-23:00 |
December | 1239.33 | 01-DEC-08:09 | 1409.91 | 01-DEC-16:10 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 612.10 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.44 | |||||
Maximum of Months | 1239.33 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 113.05 | 807.96 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2187.86 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1227.51 | 12-JAN-24:00 |
February | 2010.83 | 01-FEB-10:09 | 2187.86 | 02-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1317.90 | 19-FEB-12:10 |
March | 2010.83 | 01-MAR-10:09 | 1906.57 | 13-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1148.54 | 28-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 1524.28 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.98 | 01-APR-17:10 | 1162.85 | 07-APR-24:00 |
May | 2010.83 | 01-MAY-09:09 | 1141.99 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.29 | 05-MAY-16:00 | 833.31 | 22-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 1141.99 | 16-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.92 | 28-JUN-16:00 | 1106.76 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 1524.28 | 12-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.65 | 23-JUL-16:00 | 572.59 | 02-JUL-04:00 |
August | 2010.83 | 01-AUG-09:09 | 1243.00 | 02-AUG-07:19 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.63 | 08-AUG-17:00 | 824.12 | 11-AUG-04:00 |
September | 2010.83 | 01-SEP-09:09 | 1906.57 | 21-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.13 | 14-SEP-17:00 | 539.46 | 18-SEP-23:00 |
October | 2010.83 | 02-OCT-09:09 | 2187.86 | 26-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 982.04 | 31-OCT-21:03 |
November | 2010.83 | 01-NOV-09:09 | 2187.86 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1160.03 | 29-NOV-23:00 |
December | 2010.83 | 01-DEC-10:09 | 2187.86 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 934.97 | 02-DEC-21:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1141.99 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 539.46 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 103.65 | 1317.90 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 822.35 | 12-JAN-24:00 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 757.67 | 16-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 1228.64 | 13-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 747.86 | 28-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 982.28 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.15 | 01-APR-16:00 | 768.87 | 07-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 801.02 | 02-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.86 | 05-MAY-16:00 | 566.78 | 22-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 735.93 | 05-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.28 | 28-JUN-16:00 | 747.19 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 982.28 | 12-JUL-07:19 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.40 | 23-JUL-13:32 | 401.19 | 02-JUL-04:00 |
August | 1295.83 | 01-AUG-09:09 | 982.28 | 02-AUG-07:30 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.42 | 08-AUG-17:00 | 579.06 | 11-AUG-04:00 |
September | 1295.83 | 01-SEP-09:09 | 1228.64 | 21-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.42 | 14-SEP-17:00 | 360.11 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 20-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 655.65 | 31-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 782.45 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 626.49 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 735.93 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.11 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 68.40 | 822.35 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2187.81 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1415.87 | 12-JAN-24:00 |
February | 2010.79 | 01-FEB-10:09 | 2187.81 | 01-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1309.68 | 16-FEB-22:03 |
March | 2010.79 | 01-MAR-10:09 | 1906.53 | 07-MAR-16:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1269.99 | 29-MAR-05:00 |
April | 2010.79 | 03-APR-09:09 | 1524.25 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 227.84 | 01-APR-17:02 | 1334.62 | 07-APR-24:00 |
May | 2010.79 | 01-MAY-09:09 | 1141.96 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.68 | 05-MAY-16:00 | 993.77 | 22-MAY-24:00 |
June | 2010.79 | 01-JUN-09:09 | 1141.96 | 16-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.86 | 28-JUN-16:00 | 1296.19 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 1524.25 | 12-JUL-07:49 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.84 | 23-JUL-13:53 | 650.20 | 02-JUL-04:00 |
August | 2010.79 | 01-AUG-09:09 | 1242.97 | 02-AUG-07:19 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.87 | 13-AUG-15:00 | 960.89 | 11-AUG-04:00 |
September | 2010.79 | 01-SEP-09:09 | 1906.53 | 21-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.59 | 14-SEP-17:00 | 612.38 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 2187.81 | 20-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1215.82 | 31-OCT-21:03 |
November | 2010.79 | 01-NOV-09:09 | 2187.81 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1348.99 | 29-NOV-23:00 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1083.23 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 612.38 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 227.84 | 1415.87 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 936.78 | 12-JAN-24:00 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 872.65 | 16-FEB-22:03 |
March | 1295.83 | 01-MAR-10:09 | 1228.64 | 03-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 847.21 | 28-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 801.02 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.27 | 01-APR-17:02 | 912.26 | 07-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 735.93 | 05-MAY-14:30 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.12 | 05-MAY-16:00 | 658.52 | 22-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 670.83 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.24 | 28-JUN-16:00 | 858.78 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 735.93 | 12-JUL-07:00 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.88 | 23-JUL-15:40 | 459.63 | 02-JUL-09:47 |
August | 1295.83 | 01-AUG-09:09 | 801.02 | 02-AUG-07:30 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.53 | 08-AUG-17:00 | 655.22 | 11-AUG-04:00 |
September | 1295.83 | 01-SEP-09:09 | 1228.64 | 21-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.73 | 14-SEP-17:00 | 395.93 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 27-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 809.39 | 31-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 894.05 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-16:10 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 719.92 | 22-DEC-22:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 395.93 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 139.27 | 936.78 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2187.86 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1419.06 | 12-JAN-24:00 |
February | 2010.83 | 01-FEB-10:09 | 2187.86 | 02-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1434.53 | 19-FEB-12:10 |
March | 2010.83 | 01-MAR-10:09 | 1906.57 | 13-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1329.91 | 28-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 1524.28 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.26 | 01-APR-17:10 | 1373.94 | 07-APR-24:00 |
May | 2010.83 | 01-MAY-09:09 | 1141.99 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.68 | 05-MAY-16:00 | 996.92 | 22-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 1141.99 | 16-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.86 | 28-JUN-16:00 | 1279.87 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 1243.00 | 12-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.28 | 23-JUL-15:37 | 662.35 | 02-JUL-04:00 |
August | 2010.83 | 01-AUG-09:09 | 1243.00 | 02-AUG-07:19 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.80 | 08-AUG-17:00 | 1001.56 | 11-AUG-04:00 |
September | 2010.83 | 01-SEP-09:09 | 1906.57 | 21-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.59 | 14-SEP-17:00 | 610.56 | 30-SEP-04:55 |
October | 2010.83 | 02-OCT-09:09 | 2187.86 | 26-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1215.54 | 31-OCT-21:03 |
November | 2010.83 | 01-NOV-09:09 | 2187.86 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1350.12 | 29-NOV-23:00 |
December | 2010.83 | 01-DEC-10:09 | 2187.86 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1095.29 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1141.99 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 610.56 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 109.28 | 1434.53 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 962.32 | 12-JAN-24:00 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 875.32 | 16-FEB-22:03 |
March | 1295.83 | 01-MAR-10:09 | 1228.64 | 13-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 868.28 | 28-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 982.28 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.52 | 01-APR-16:00 | 909.27 | 07-APR-24:00 |
May | 1295.83 | 01-MAY-09:09 | 801.02 | 02-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.12 | 05-MAY-16:00 | 680.22 | 22-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 735.93 | 05-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.24 | 28-JUN-16:00 | 868.91 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 982.28 | 12-JUL-07:19 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.50 | 23-JUL-13:53 | 477.80 | 22-JUL-22:55 |
August | 1295.83 | 01-AUG-09:09 | 982.28 | 02-AUG-07:30 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.53 | 08-AUG-17:00 | 704.80 | 11-AUG-04:00 |
September | 1295.83 | 01-SEP-09:09 | 1228.64 | 21-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.73 | 14-SEP-17:00 | 413.53 | 30-SEP-04:55 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 20-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 812.35 | 31-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 921.55 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 742.91 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 735.93 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 413.53 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 70.50 | 962.32 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 5470.56 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 5470.56 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 5470.56 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 5470.56 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 5470.56 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 5470.56 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 5470.56 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 5470.56 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 5470.56 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 5470.56 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 5470.56 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 5470.56 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 5470.56 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1292.75 | 28-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1203.63 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1127.64 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.48 | 01-APR-17:02 | 1145.72 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 05-MAY-16:00 | 837.90 | 18-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.19 | 28-JUN-15:00 | 1132.57 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.05 | 23-JUL-16:00 | 569.84 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.81 | 13-AUG-15:00 | 743.59 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.11 | 14-SEP-17:00 | 532.44 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1005.37 | 31-OCT-21:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1225.38 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1008.94 | 17-DEC-20:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 532.44 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.05 | 1292.75 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2179.23 | 28-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2014.93 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1917.07 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.95 | 01-APR-17:02 | 1973.59 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.62 | 05-MAY-16:00 | 1483.75 | 18-MAY-04:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.51 | 28-JUN-15:00 | 1959.19 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.89 | 23-JUL-16:00 | 979.70 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.90 | 13-AUG-15:20 | 1338.19 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.78 | 14-SEP-17:00 | 914.49 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1700.38 | 31-OCT-21:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2037.47 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1621.88 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 914.49 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.89 | 2179.23 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2237.01 | 12-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2025.81 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1970.53 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.92 | 01-APR-17:02 | 2124.72 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1518.35 | 22-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.69 | 28-JUN-17:00 | 2017.36 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.31 | 23-JUL-14:00 | 1006.61 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.33 | 08-AUG-17:00 | 1493.77 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 939.38 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1840.23 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2113.59 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1716.56 | 22-DEC-23:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 939.38 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.92 | 2237.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 108578.04 | 02-JAN-07:05 | 7180.90 | 12934.72 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 107355.74 | 28-FEB-07:11 | 25133.15 | 45271.53 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 105402.89 | 11-MAR-07:12 | 10771.35 | 12935.21 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 112769.64 | 03-APR-06:11 | 32314.05 | 58206.26 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 115227.37 | 30-MAY-06:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 114221.35 | 05-JUN-06:11 | 32314.05 | 58206.26 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 115154.00 | 03-JUL-06:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 108003.01 | 26-AUG-06:11 | 16157.03 | 19402.81 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 119521.22 | 05-SEP-06:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 118657.19 | 10-OCT-06:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 116474.28 | 06-NOV-07:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 109440.09 | 26-DEC-07:03 | 10771.35 | 19402.09 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 105402.89 | 7180.90 | 12934.72 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 119521.22 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 87535.36 | 02-JAN-05:11 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 87463.64 | 27-FEB-05:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 90272.55 | 27-MAR-04:11 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 91594.49 | 17-APR-04:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 93396.55 | 01-MAY-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 94907.92 | 12-JUN-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 93761.17 | 05-JUL-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 91976.68 | 26-AUG-04:13 | 0.00 | 3224.16 | 26719.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 96215.65 | 05-SEP-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 95360.48 | 10-OCT-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 94016.84 | 06-NOV-05:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 90864.21 | 04-DEC-05:12 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 87463.64 | 0.00 | 2686.80 | 26719.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 96215.65 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 25664.46 | 12-JAN-17:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 55478.43 | 28-FEB-06:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 73731.58 | 03-MAR-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 79371.24 | 29-APR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 79647.91 | 08-MAY-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 80908.84 | 12-JUN-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 82063.17 | 17-JUL-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 82678.09 | 11-AUG-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 79981.31 | 07-SEP-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 79989.95 | 10-OCT-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 72477.46 | 06-NOV-06:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 28729.57 | 06-DEC-16:20 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 25664.46 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 82678.09 | 15316.26 | 17424.44 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 18990.41 | 11-JAN-17:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 28572.84 | 28-FEB-17:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 32091.81 | 15-MAR-16:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 73476.27 | 28-APR-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 73316.43 | 05-MAY-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 77260.53 | 12-JUN-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 77403.98 | 25-JUL-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 78114.31 | 11-AUG-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 73608.23 | 14-SEP-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 39066.87 | 04-OCT-15:50 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 25870.59 | 02-NOV-16:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19016.71 | 06-DEC-16:50 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 18990.41 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 78114.31 | 15316.26 | 17424.44 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2746.15 | 12-JAN-06:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.49 |
February | 4726.70 | 27-FEB-15:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.98 |
March | 5264.29 | 10-MAR-14:20 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.36 |
April | 7711.47 | 27-APR-15:20 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 10.25 | 0.00 |
May | 7682.27 | 15-MAY-13:50 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.54 |
June | 11454.42 | 12-JUN-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.91 |
July | 11886.78 | 31-JUL-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.94 |
August | 11891.44 | 14-AUG-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.11 |
September | 8713.55 | 12-SEP-13:27 | 6032.37 | 3122.88 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.25 |
October | 5659.26 | 10-OCT-12:10 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.08 |
November | 4720.10 | 06-NOV-11:40 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.52 |
December | 3010.13 | 04-DEC-05:12 | 0.00 | 674.71 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2746.15 | 0.00 | 269.88 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11891.44 | 6032.37 | 3122.88 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 10.25 | 67.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2828.99 | 11-JAN-06:03 | 521.82 | 173.92 | 2475.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.43 |
February | 4718.61 | 08-FEB-09:45 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.30 |
March | 9264.20 | 14-MAR-08:55 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.67 |
April | 12563.97 | 27-APR-08:30 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.96 |
May | 19549.20 | 14-MAY-08:32 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.79 |
June | 24081.07 | 25-JUN-07:52 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.09 |
July | 25677.56 | 30-JUL-08:31 | 521.82 | 298.13 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.67 |
August | 25016.13 | 06-AUG-08:11 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.60 |
September | 20931.76 | 10-SEP-08:32 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.74 |
October | 10302.63 | 04-OCT-08:50 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.58 |
November | 4168.08 | 15-NOV-09:10 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.03 |
December | 3640.56 | 05-DEC-09:55 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2828.99 | 326.14 | 173.92 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.96 | |
Maximum of Months | 25677.56 | 2478.65 | 1341.67 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16629.43 | 20-JAN-13:10 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 |
February | 21754.76 | 12-FEB-13:13 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 413.36 |
March | 20298.49 | 01-MAR-13:30 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.25 |
April | 21574.97 | 02-APR-15:22 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.38 |
May | 20701.52 | 14-MAY-13:13 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.09 |
June | 27589.03 | 11-JUN-12:43 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.13 |
July | 33323.92 | 30-JUL-11:52 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.58 |
August | 34254.61 | 13-AUG-12:41 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.62 |
September | 32472.68 | 10-SEP-12:32 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.87 |
October | 33445.21 | 08-OCT-13:42 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.25 |
November | 21326.87 | 11-NOV-12:53 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.86 |
December | 29033.69 | 03-DEC-13:32 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16629.43 | 404.87 | 231.31 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | |
Maximum of Months | 34254.61 | 1923.15 | 1040.98 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 413.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5352.40 | 05-JAN-15:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.08 |
February | 13268.29 | 26-FEB-15:13 | 260.91 | 149.06 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.93 |
March | 15144.13 | 18-MAR-17:06 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.38 |
April | 26895.53 | 02-APR-15:22 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.90 |
May | 28007.25 | 14-MAY-16:32 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.64 |
June | 28672.48 | 18-JUN-16:51 | 521.82 | 298.13 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.99 |
July | 33401.22 | 30-JUL-16:31 | 652.28 | 372.66 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.01 |
August | 33262.75 | 06-AUG-16:51 | 652.28 | 372.66 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.14 |
September | 27529.45 | 10-SEP-16:32 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.73 |
October | 17501.92 | 08-OCT-13:42 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.59 |
November | 13548.02 | 06-NOV-05:12 | 0.00 | 260.89 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.83 |
December | 12820.48 | 04-DEC-05:11 | 0.00 | 434.81 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5352.40 | 0.00 | 149.06 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33401.22 | 1239.33 | 670.83 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1958.37 | 11-JAN-16:20 | 1923.11 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.87 |
February | 2346.58 | 28-FEB-15:00 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2832.35 | 10-MAR-14:30 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.11 |
April | 6187.69 | 27-APR-15:20 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 23.21 | 0.00 |
May | 6834.73 | 05-MAY-13:30 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.48 |
June | 7418.77 | 21-JUN-15:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 3.68 | 0.00 |
July | 8497.64 | 24-JUL-15:00 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 36.47 | 0.00 |
August | 8195.60 | 25-AUG-14:00 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 15.62 | 0.00 |
September | 6769.15 | 12-SEP-13:27 | 6032.37 | 3122.88 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.66 |
October | 3755.75 | 04-OCT-15:10 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.25 |
November | 2371.51 | 07-NOV-06:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.35 |
December | 1871.81 | 29-DEC-16:10 | 1923.11 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1871.81 | 809.73 | 269.88 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8497.64 | 6032.37 | 3122.88 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 36.47 | 114.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2149.98 | 05-JAN-09:40 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.74 |
February | 2887.47 | 12-FEB-12:22 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 428.44 |
March | 7328.27 | 14-MAR-10:10 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.59 |
April | 12616.90 | 27-APR-09:00 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.74 |
May | 24941.12 | 14-MAY-08:22 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.70 |
June | 25734.65 | 25-JUN-08:21 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.55 |
July | 24448.58 | 30-JUL-08:42 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.31 |
August | 26116.34 | 06-AUG-09:41 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.75 |
September | 24862.67 | 10-SEP-09:42 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.64 |
October | 9383.69 | 04-OCT-09:00 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.98 |
November | 2675.17 | 02-NOV-10:40 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.47 |
December | 2384.37 | 05-DEC-10:00 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2149.98 | 326.14 | 186.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.74 | |
Maximum of Months | 26116.34 | 2478.65 | 1341.67 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 428.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16730.89 | 20-JAN-13:20 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.34 |
February | 32771.96 | 12-FEB-12:22 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 873.57 |
March | 21647.77 | 01-MAR-13:40 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.75 |
April | 22082.26 | 02-APR-15:22 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.93 |
May | 33132.53 | 14-MAY-13:02 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.43 |
June | 27186.25 | 11-JUN-13:02 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.14 |
July | 32470.66 | 30-JUL-13:22 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.02 |
August | 34728.46 | 06-AUG-13:42 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.84 |
September | 37559.74 | 10-SEP-12:21 | 809.75 | 462.62 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.76 |
October | 33070.50 | 08-OCT-13:12 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.23 |
November | 22151.97 | 11-NOV-12:53 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 417.24 |
December | 16981.11 | 05-DEC-12:30 | 1058.33 | 1040.98 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 16730.89 | 404.87 | 231.31 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.34 | |
Maximum of Months | 37559.74 | 1923.15 | 1040.98 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 873.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2743.34 | 05-JAN-15:50 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.97 |
February | 8113.93 | 27-FEB-15:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.40 |
March | 10775.62 | 14-MAR-16:00 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.41 |
April | 15205.28 | 02-APR-15:22 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.04 |
May | 29143.61 | 07-MAY-16:41 | 587.05 | 335.39 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.20 |
June | 25809.99 | 18-JUN-17:31 | 0.00 | 298.13 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.01 |
July | 27012.78 | 23-JUL-17:11 | 0.00 | 260.86 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.07 |
August | 29401.88 | 06-AUG-17:01 | 0.00 | 372.66 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.16 |
September | 27580.10 | 10-SEP-17:01 | 0.00 | 298.13 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.32 |
October | 12100.36 | 04-OCT-16:00 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.41 |
November | 5638.61 | 04-NOV-15:30 | 130.46 | 111.81 | 541.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.69 |
December | 3009.93 | 05-DEC-15:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2743.34 | 0.00 | 111.81 | 541.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.69 | |
Maximum of Months | 29401.88 | 1239.33 | 670.83 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1853.64 | 11-JAN-16:20 | 1923.11 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.86 |
February | 2298.54 | 28-FEB-15:10 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.03 |
March | 2456.24 | 10-MAR-14:50 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.23 |
April | 6787.00 | 27-APR-15:20 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 27.80 | 0.00 |
May | 7146.59 | 05-MAY-13:30 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.62 |
June | 8049.15 | 21-JUN-15:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 3.72 | 0.00 |
July | 9496.67 | 24-JUL-15:00 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 44.53 | 0.00 |
August | 8729.82 | 09-AUG-14:40 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 44.95 | 0.00 |
September | 6446.94 | 12-SEP-13:27 | 6032.37 | 3122.88 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.49 |
October | 3575.70 | 04-OCT-15:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.83 |
November | 2160.88 | 02-NOV-14:40 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.90 |
December | 1763.32 | 29-DEC-16:10 | 1923.11 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.91 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1763.32 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9496.67 | 6032.37 | 3122.88 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 44.95 | 117.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1914.62 | 05-JAN-09:40 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.61 |
February | 2414.55 | 27-FEB-15:50 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.78 |
March | 5998.91 | 14-MAR-09:50 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.74 |
April | 12188.88 | 27-APR-09:20 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.66 |
May | 24519.22 | 14-MAY-09:32 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.28 |
June | 20499.78 | 25-JUN-08:42 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.59 |
July | 24498.69 | 30-JUL-08:21 | 521.82 | 298.13 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.52 |
August | 24168.61 | 13-AUG-09:32 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.76 |
September | 18396.02 | 10-SEP-09:12 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.75 |
October | 8265.38 | 04-OCT-09:30 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.34 |
November | 2431.82 | 02-NOV-10:40 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.44 |
December | 2030.56 | 05-DEC-10:30 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1914.62 | 326.14 | 186.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.78 | |
Maximum of Months | 24519.22 | 2478.65 | 1341.67 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 272.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15039.88 | 20-JAN-13:30 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.49 |
February | 18415.52 | 27-FEB-14:30 | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.87 |
March | 20686.40 | 14-MAR-13:30 | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.12 |
April | 28452.99 | 02-APR-12:23 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 394.15 |
May | 35287.84 | 14-MAY-13:32 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.91 |
June | 26744.75 | 11-JUN-12:32 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.74 |
July | 36720.75 | 30-JUL-14:21 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.48 |
August | 34186.38 | 13-AUG-12:52 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.14 |
September | 35595.19 | 10-SEP-13:12 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.74 |
October | 31156.97 | 08-OCT-13:22 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.24 |
November | 17562.55 | 04-NOV-13:30 | 211.67 | 173.50 | 840.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14530.82 | 05-DEC-12:30 | 1058.33 | 1040.98 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14530.82 | 211.67 | 173.50 | 840.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36720.75 | 2010.83 | 1040.98 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 394.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2719.82 | 05-JAN-15:50 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.23 |
February | 7577.11 | 27-FEB-15:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.32 |
March | 10663.80 | 14-MAR-16:00 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.22 |
April | 15250.18 | 26-APR-16:00 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 | 0.00 |
May | 30508.01 | 07-MAY-16:41 | 587.05 | 335.39 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.06 |
June | 26214.84 | 18-JUN-17:02 | 0.00 | 223.59 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.56 |
July | 31423.99 | 30-JUL-17:01 | 0.00 | 372.66 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.75 |
August | 27644.61 | 06-AUG-17:11 | 0.00 | 260.86 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.47 |
September | 26355.61 | 10-SEP-16:32 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.32 |
October | 12029.32 | 04-OCT-16:00 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.97 |
November | 5213.20 | 04-NOV-15:30 | 130.46 | 111.81 | 541.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 |
December | 2852.64 | 05-DEC-15:40 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2719.82 | 0.00 | 111.81 | 541.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31423.99 | 1239.33 | 670.83 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.87 | 329.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3538.42 | 06-JAN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.33 |
February | 4488.30 | 28-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.16 |
March | 5833.25 | 20-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.41 |
April | 6907.63 | 03-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.26 |
May | 7243.71 | 01-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.77 |
June | 9062.97 | 12-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.90 |
July | 9432.96 | 10-JUL-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.26 |
August | 10397.80 | 14-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.99 |
September | 9694.87 | 11-SEP-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.41 |
October | 9055.93 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.27 |
November | 6838.16 | 06-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.96 |
December | 4591.03 | 05-DEC-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3538.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.41 | |
Maximum of Months | 10397.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7176.12 | 14-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1274.54 |
February | 6950.05 | 18-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 428.01 |
March | 4209.73 | 06-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 901.21 |
April | 5480.06 | 29-APR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.74 |
May | 5375.50 | 08-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.36 |
June | 5292.05 | 28-JUN-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.42 | 0.00 |
July | 5762.26 | 31-JUL-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.14 | 0.00 |
August | 7013.38 | 10-AUG-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.74 | 0.00 |
September | 6590.77 | 11-SEP-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.97 |
October | 4884.55 | 05-OCT-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.11 |
November | 5779.50 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.81 |
December | 6401.76 | 26-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4209.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7176.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.14 | 1274.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 195.20 | 11-JAN-17:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.22 |
February | 3106.44 | 27-FEB-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.06 |
March | 5995.58 | 14-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.42 |
April | 15843.29 | 27-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.59 | 0.00 |
May | 16251.60 | 15-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.50 |
June | 16652.57 | 28-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 |
July | 18157.09 | 24-JUL-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.09 | 0.00 |
August | 19081.06 | 10-AUG-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.53 | 0.00 |
September | 15340.92 | 11-SEP-14:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 |
October | 9264.93 | 04-OCT-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.19 |
November | 3526.20 | 04-NOV-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 40.63 | 30-DEC-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 40.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19081.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.09 | 200.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1993.43 | 05-JAN-16:10 | 222.14 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4099.86 | 07-FEB-16:50 | 222.14 | 450.11 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6998.41 | 31-MAR-24:00 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8205.19 | 26-APR-18:00 | 23.38 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3460.90 | 31-MAY-24:00 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5337.88 | 30-JUN-24:00 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7260.73 | 31-JUL-23:50 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8675.41 | 06-AUG-18:33 | 0.00 | 150.05 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3313.27 | 30-SEP-24:00 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5019.02 | 31-OCT-24:00 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5792.60 | 10-NOV-16:00 | 222.14 | 450.11 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7833.47 | 05-DEC-15:50 | 222.14 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1993.43 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8675.41 | 222.14 | 450.11 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1586.50 | 05-JAN-16:20 | 222.14 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3747.15 | 08-FEB-17:00 | 222.14 | 450.11 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6149.45 | 31-MAR-23:50 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7819.97 | 26-APR-18:00 | 23.38 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3210.11 | 31-MAY-23:50 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4996.08 | 30-JUN-24:00 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6987.53 | 31-JUL-24:00 | 0.00 | 75.02 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8113.36 | 06-AUG-18:35 | 0.00 | 150.05 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2905.99 | 30-SEP-23:50 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4189.01 | 04-OCT-16:50 | 70.15 | 250.06 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5357.14 | 10-NOV-16:10 | 222.14 | 450.11 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7189.70 | 05-DEC-16:00 | 222.14 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1586.50 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8113.36 | 222.14 | 450.11 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1440.48 | 05-JAN-16:20 | 222.14 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3638.57 | 08-FEB-17:00 | 222.14 | 450.11 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5706.55 | 01-MAR-17:00 | 222.14 | 450.11 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7889.89 | 26-APR-18:00 | 23.38 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3126.33 | 31-MAY-23:30 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4895.30 | 30-JUN-23:40 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6962.70 | 31-JUL-24:00 | 0.00 | 75.02 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8196.84 | 06-AUG-18:21 | 0.00 | 200.06 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2477.39 | 30-SEP-23:20 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4211.42 | 04-OCT-16:50 | 70.15 | 250.06 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5205.85 | 10-NOV-16:10 | 222.14 | 450.11 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6995.45 | 05-DEC-16:00 | 222.14 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1440.48 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8196.84 | 222.14 | 450.11 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 91559.73 | 12-JAN-17:00 | 4808.68 | 5470.56 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 183885.11 | 27-FEB-17:00 | 4808.68 | 5470.56 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358642.48 | 31-MAR-24:00 | 0.00 | 303.90 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 368241.54 | 27-APR-16:00 | 4808.68 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176425.42 | 31-MAY-24:00 | 0.00 | 303.90 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 268006.88 | 30-JUN-24:00 | 0.00 | 303.90 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 360531.89 | 31-JUL-23:53 | 0.00 | 911.69 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 369018.89 | 25-AUG-16:00 | 4808.68 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 175700.32 | 30-SEP-24:00 | 0.00 | 303.90 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 267383.89 | 31-OCT-24:00 | 0.00 | 303.90 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 276467.12 | 06-NOV-17:00 | 4808.68 | 5470.56 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 367853.30 | 05-DEC-17:00 | 4808.68 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 91559.73 | 0.00 | 303.90 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 369018.89 | 4808.68 | 5470.56 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.162367E+13 | 1218095.10 | 10-JAN-16:00 | 0.329797E+12 | 1359749.70 | 02-JAN-06:10 |
February | 0.182436E+13 | 1427801.15 | 27-FEB-15:09 | 0.180100E+12 | 609630.80 | 18-FEB-07:10 |
March | 0.244104E+13 | 1547353.91 | 14-MAR-15:00 | 0.551730E+11 | 408069.34 | 01-MAR-07:10 |
April | 0.266523E+13 | 1988483.30 | 27-APR-14:39 | 0.176345E+11 | 274922.88 | 19-APR-06:10 |
May | 0.166202E+13 | 1519132.80 | 15-MAY-15:20 | 0.207672E+10 | 155435.81 | 18-MAY-06:10 |
June | 0.200373E+13 | 1658975.30 | 28-JUN-15:30 | 91117976.07 | 7515.93 | 14-JUN-05:49 |
July | 0.246660E+13 | 1897583.30 | 31-JUL-15:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.301923E+13 | 2113943.05 | 29-AUG-15:09 | 23590.43 | 39.32 | 03-AUG-06:30 |
September | 0.159572E+13 | 1523441.75 | 11-SEP-14:00 | 0.638592E+09 | 49442.26 | 27-SEP-05:10 |
October | 0.194958E+13 | 1623198.44 | 04-OCT-15:09 | 0.185624E+11 | 259804.53 | 30-OCT-05:10 |
November | 0.226997E+13 | 1510979.59 | 15-NOV-16:00 | 0.118627E+12 | 489875.64 | 24-NOV-07:10 |
December | 0.274271E+13 | 1651400.55 | 04-DEC-16:40 | 0.247729E+12 | 785105.35 | 26-DEC-07:10 |
Annual Sum or Average | 0.262639E+14 | 0.970429E+12 | ||||
Minimum of Months | 0.159572E+13 | 1218095.10 | 0.00 | 0.00 | ||
Maximum of Months | 0.301923E+13 | 2113943.05 | 0.329797E+12 | 1359749.70 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.277880E+12 | 0.441256E+11 | 0.766053E+12 | 0.213346E+12 | 0.167395E+12 | 0.119358E+11 | 0.00 | 0.963712E+10 | 0.858894E+09 | 0.933828E+11 | 0.00 | 0.390567E+11 | 0.00 |
February | 0.247115E+12 | 0.343652E+11 | 0.978954E+12 | 0.195334E+12 | 0.157725E+12 | 0.133870E+11 | 0.00 | 0.250948E+11 | 0.344215E+10 | 0.133219E+12 | 0.00 | 0.357277E+11 | 0.00 |
March | 0.290276E+12 | 0.307121E+11 | 0.141687E+13 | 0.226059E+12 | 0.188097E+12 | 0.148900E+11 | 0.00 | 0.448081E+11 | 0.651962E+10 | 0.181267E+12 | 0.00 | 0.415405E+11 | 0.00 |
April | 0.256202E+12 | 0.231133E+11 | 0.165903E+13 | 0.211502E+12 | 0.197268E+12 | 0.173140E+11 | 0.00 | 0.862705E+11 | 0.210881E+11 | 0.156767E+12 | 0.00 | 0.366855E+11 | 0.00 |
May | 0.275745E+12 | 0.194367E+11 | 0.774844E+12 | 0.219699E+12 | 0.211863E+12 | 0.256498E+11 | 0.00 | 0.395405E+11 | 0.211078E+11 | 0.363836E+11 | 0.00 | 0.377489E+11 | 0.00 |
June | 0.273847E+12 | 0.168813E+11 | 0.106252E+13 | 0.217935E+12 | 0.219745E+12 | 0.314496E+11 | 0.00 | 0.802531E+11 | 0.418947E+11 | 0.231620E+11 | 0.00 | 0.360470E+11 | 0.00 |
July | 0.255743E+12 | 0.181386E+11 | 0.139340E+13 | 0.213265E+12 | 0.237258E+12 | 0.399408E+11 | 0.00 | 0.178926E+12 | 0.743863E+11 | 0.221544E+11 | 0.00 | 0.333859E+11 | 0.00 |
August | 0.286504E+12 | 0.215466E+11 | 0.173200E+13 | 0.226058E+12 | 0.252291E+12 | 0.460677E+11 | 0.00 | 0.310446E+12 | 0.107313E+12 | 0.793380E+09 | 0.00 | 0.362128E+11 | 0.00 |
September | 0.257562E+12 | 0.266127E+11 | 0.740713E+12 | 0.211501E+12 | 0.213037E+12 | 0.284722E+11 | 0.00 | 0.519973E+11 | 0.307544E+11 | 0.176036E+10 | 0.00 | 0.333046E+11 | 0.00 |
October | 0.271079E+12 | 0.349330E+11 | 0.108340E+13 | 0.213343E+12 | 0.195548E+12 | 0.164710E+11 | 0.00 | 0.345996E+11 | 0.916844E+10 | 0.556167E+11 | 0.00 | 0.354159E+11 | 0.00 |
November | 0.273673E+12 | 0.406597E+11 | 0.135889E+13 | 0.205299E+12 | 0.175420E+12 | 0.135566E+11 | 0.00 | 0.405325E+11 | 0.609514E+10 | 0.119759E+12 | 0.00 | 0.360876E+11 | 0.00 |
December | 0.270336E+12 | 0.459151E+11 | 0.170972E+13 | 0.213271E+12 | 0.174232E+12 | 0.128678E+11 | 0.00 | 0.528903E+11 | 0.503654E+10 | 0.221221E+12 | 0.00 | 0.372211E+11 | 0.00 |
Annual Sum or Average | 0.323596E+13 | 0.356440E+12 | 0.146764E+14 | 0.256661E+13 | 0.238988E+13 | 0.272002E+12 | 0.00 | 0.954996E+12 | 0.327665E+12 | 0.104549E+13 | 0.00 | 0.438434E+12 | 0.00 |
Minimum of Months | 0.247115E+12 | 0.168813E+11 | 0.740713E+12 | 0.195334E+12 | 0.157725E+12 | 0.119358E+11 | 0.00 | 0.963712E+10 | 0.858894E+09 | 0.793380E+09 | 0.00 | 0.333046E+11 | 0.00 |
Maximum of Months | 0.290276E+12 | 0.459151E+11 | 0.173200E+13 | 0.226059E+12 | 0.252291E+12 | 0.460677E+11 | 0.00 | 0.310446E+12 | 0.107313E+12 | 0.221221E+12 | 0.00 | 0.415405E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.329797E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.180100E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.551730E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.176345E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.207672E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 91117976.07 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 23590.43 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.638592E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.185624E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.118627E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.247729E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.970429E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.329797E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 325713.14 | 02-JAN-08:09 | 40855.88 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 233439.18 | 02-JAN-08:20 | 94655.58 | 02-JAN-06:10 | 21297.18 | 13-JAN-06:40 | 0.00 | 01-JAN-00:10 |
February | 325713.14 | 02-FEB-16:00 | 40855.88 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 233438.02 | 02-FEB-08:20 | 137084.09 | 27-FEB-14:00 | 21781.65 | 16-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 314611.94 | 22-MAR-07:10 | 40855.88 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 233433.23 | 22-MAR-07:19 | 153101.83 | 14-MAR-15:30 | 21410.15 | 24-MAR-05:10 | 0.00 | 01-MAR-00:10 |
April | 297349.23 | 03-APR-07:10 | 40855.88 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 233424.00 | 03-APR-07:19 | 234317.94 | 27-APR-14:39 | 41075.65 | 27-APR-12:20 | 0.00 | 01-APR-00:10 |
May | 284436.93 | 02-MAY-07:10 | 27558.46 | 01-MAY-19:19 | 423497.50 | 01-MAY-07:10 | 233417.11 | 02-MAY-07:19 | 217168.44 | 15-MAY-14:50 | 40647.53 | 04-MAY-14:09 | 0.00 | 01-MAY-00:10 |
June | 283655.84 | 16-JUN-07:10 | 27558.46 | 01-JUN-19:00 | 541788.89 | 01-JUN-07:10 | 233416.70 | 16-JUN-07:19 | 221153.51 | 28-JUN-15:20 | 40934.32 | 27-JUN-14:00 | 0.00 | 01-JUN-00:10 |
July | 293192.71 | 12-JUL-07:00 | 27558.46 | 01-JUL-20:10 | 660080.29 | 03-JUL-07:10 | 233421.75 | 12-JUL-07:00 | 245852.73 | 31-JUL-14:50 | 41097.12 | 20-JUL-12:20 | 0.00 | 01-JUL-00:10 |
August | 290598.44 | 02-AUG-07:30 | 40855.88 | 16-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 233420.40 | 02-AUG-07:40 | 273187.64 | 10-AUG-14:50 | 40707.89 | 29-AUG-12:30 | 0.00 | 01-AUG-00:10 |
September | 314611.94 | 21-SEP-07:10 | 40855.88 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 233433.23 | 21-SEP-07:19 | 294597.62 | 11-SEP-14:39 | 44611.57 | 12-SEP-13:30 | 0.00 | 01-SEP-00:10 |
October | 325713.14 | 27-OCT-07:10 | 40855.88 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 233439.18 | 27-OCT-07:19 | 206775.58 | 04-OCT-15:30 | 21508.51 | 04-OCT-13:39 | 0.00 | 01-OCT-00:10 |
November | 325713.14 | 01-NOV-07:10 | 40855.88 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 233439.18 | 01-NOV-07:19 | 117662.10 | 15-NOV-13:09 | 22129.52 | 24-NOV-06:10 | 0.00 | 01-NOV-00:10 |
December | 325713.14 | 01-DEC-16:19 | 40855.88 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 233439.18 | 08-DEC-08:20 | 112154.26 | 05-DEC-11:00 | 23016.53 | 26-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 283655.84 | 27558.46 | 423497.50 | 233416.70 | 94655.58 | 21297.18 | 0.00 | |||||||
Maximum of Months | 325713.14 | 40855.88 | 778371.69 | 233439.18 | 294597.62 | 44611.57 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 6781.91 | 05-JAN-16:19 | 1586.25 | 11-JAN-15:20 | 64566.56 | 09-JAN-11:00 | 0.00 | 51962.27 | 31-JAN-12:00 | 0.00 |
February | 66795.45 | 27-FEB-15:00 | 49869.58 | 27-FEB-15:09 | 100000.00 | 11-FEB-17:19 | 0.00 | 52005.61 | 10-FEB-12:39 | 0.00 |
March | 92703.23 | 18-MAR-15:00 | 49472.08 | 18-MAR-15:00 | 100000.00 | 01-MAR-05:19 | 0.00 | 51882.88 | 01-MAR-12:39 | 0.00 |
April | 320228.71 | 27-APR-12:30 | 80769.65 | 27-APR-12:39 | 100000.00 | 01-APR-06:19 | 0.00 | 50641.37 | 05-APR-11:39 | 0.00 |
May | 208069.10 | 04-MAY-14:09 | 80769.65 | 05-MAY-12:00 | 100000.00 | 14-MAY-12:50 | 0.00 | 48587.55 | 03-MAY-11:00 | 0.00 |
June | 238472.07 | 28-JUN-12:00 | 80769.65 | 20-JUN-14:20 | 100000.00 | 01-JUN-13:00 | 0.00 | 46732.05 | 02-JUN-11:20 | 0.00 |
July | 342816.22 | 31-JUL-15:00 | 80769.65 | 07-JUL-12:00 | 100000.00 | 18-JUL-14:20 | 0.00 | 45392.64 | 03-JUL-11:00 | 0.00 |
August | 408812.15 | 29-AUG-14:30 | 80769.65 | 07-AUG-10:30 | 100000.00 | 09-AUG-08:00 | 0.00 | 44766.80 | 31-AUG-11:30 | 0.00 |
September | 186624.90 | 14-SEP-16:49 | 80769.65 | 11-SEP-15:30 | 38970.82 | 08-SEP-14:00 | 0.00 | 45683.82 | 29-SEP-11:30 | 0.00 |
October | 178153.57 | 04-OCT-14:00 | 51087.86 | 04-OCT-14:00 | 100000.00 | 03-OCT-11:20 | 0.00 | 47250.70 | 31-OCT-11:00 | 0.00 |
November | 110787.19 | 04-NOV-14:09 | 50794.91 | 04-NOV-14:09 | 100000.00 | 13-NOV-22:10 | 0.00 | 49235.58 | 30-NOV-12:39 | 0.00 |
December | 22405.12 | 05-DEC-15:50 | 4071.52 | 14-DEC-11:00 | 100000.00 | 02-DEC-05:30 | 0.00 | 51130.63 | 28-DEC-12:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 6781.91 | 1586.25 | 38970.82 | 0.00 | 44766.80 | 0.00 | ||||
Maximum of Months | 408812.15 | 80769.65 | 100000.00 | 0.00 | 52005.61 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1218095.10 | 10-JAN-16:00 | 325713.14 | 423497.50 | 40855.88 | 233326.38 | 75010.26 | 20582.30 | 0.00 | 5838.54 | 750.39 |
February | 1427801.15 | 27-FEB-15:09 | 280450.63 | 541788.89 | 0.00 | 233151.79 | 135984.63 | 20748.32 | 0.00 | 65735.28 | 49869.58 |
March | 1547353.91 | 14-MAR-15:00 | 280450.63 | 660080.29 | 0.00 | 233302.19 | 149726.86 | 20651.56 | 0.00 | 49488.91 | 32323.01 |
April | 1988483.30 | 27-APR-14:39 | 280450.63 | 778371.69 | 0.00 | 233151.79 | 234317.94 | 39687.81 | 0.00 | 313689.92 | 80769.65 |
May | 1519132.80 | 15-MAY-15:20 | 280450.63 | 423497.50 | 0.00 | 233302.19 | 216164.68 | 38042.27 | 0.00 | 140703.71 | 49947.64 |
June | 1658975.30 | 28-JUN-15:30 | 280450.63 | 541788.89 | 0.00 | 233302.19 | 220803.05 | 39672.74 | 0.00 | 227094.26 | 80769.65 |
July | 1897583.30 | 31-JUL-15:20 | 280450.63 | 660080.29 | 0.00 | 233302.19 | 243315.72 | 39716.51 | 0.00 | 326004.28 | 80769.65 |
August | 2113943.05 | 29-AUG-15:09 | 280450.63 | 778371.69 | 0.00 | 233302.19 | 271668.21 | 40096.76 | 0.00 | 395416.08 | 80769.65 |
September | 1523441.75 | 11-SEP-14:00 | 280450.63 | 423497.50 | 0.00 | 233151.79 | 294597.62 | 30630.57 | 0.00 | 169590.05 | 65008.96 |
October | 1623198.44 | 04-OCT-15:09 | 280450.63 | 541788.89 | 0.00 | 233302.19 | 187459.18 | 21331.40 | 0.00 | 173665.74 | 51053.97 |
November | 1510979.59 | 15-NOV-16:00 | 325713.14 | 660080.29 | 40855.88 | 233326.38 | 94662.10 | 20593.91 | 0.00 | 17238.47 | 1657.09 |
December | 1651400.55 | 04-DEC-16:40 | 325713.14 | 778371.69 | 40855.88 | 233326.38 | 90412.36 | 20594.75 | 0.00 | 21592.48 | 2208.22 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1218095.10 | 280450.63 | 423497.50 | 0.00 | 233151.79 | 75010.26 | 20582.30 | 0.00 | 5838.54 | 750.39 | |
Maximum of Months | 2113943.05 | 325713.14 | 778371.69 | 40855.88 | 233326.38 | 294597.62 | 40096.76 | 0.00 | 395416.08 | 80769.65 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 1359749.70 | 02-JAN-06:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 609630.80 | 18-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 408069.34 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 274922.88 | 19-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 155435.81 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 7515.93 | 14-JUN-05:49 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 39.32 | 03-AUG-06:30 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 49442.26 | 27-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 259804.53 | 30-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 489875.64 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 785105.35 | 26-DEC-07:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 1359749.70 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 76.83 | 26.52 | 37.33 | 26.50 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 45.83 | 26.15 | 24.33 | 26.15 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 52.50 | 26.32 | 28.33 | 26.33 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 48.00 | 26.47 | 27.17 | 26.48 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 63.50 | 26.61 | 30.67 | 26.56 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 58.50 | 26.62 | 30.83 | 26.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 85.67 | 26.96 | 30.50 | 26.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 120.00 | 27.18 | 58.83 | 27.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 83.83 | 27.01 | 40.83 | 26.97 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 78.67 | 27.00 | 41.00 | 26.96 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 70.67 | 26.82 | 32.33 | 26.77 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 50.00 | 26.36 | 26.17 | 26.36 |
Annual Sum or Average | 0.00 | 0.00 | 834.00 | 26.75 | 408.33 | 26.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 45.83 | 26.15 | 24.33 | 26.15 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 120.00 | 27.18 | 58.83 | 27.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.64 | 0.00 | 25.64 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.67 | 0.00 | 25.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.60 | 0.00 | 25.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.00 | 25.62 | 0.00 | 25.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.67 | 0.00 | 25.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 19.15 | 0.50 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
February | 0.50 | 18.57 | 0.00 | 18.57 | 0.00 | 18.57 | 0.00 | 18.57 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
December | 0.67 | 18.43 | 0.00 | 18.43 | 0.00 | 18.43 | 0.00 | 18.43 |
Annual Sum or Average | 3.67 | 18.94 | 0.50 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 19.19 | 0.50 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.22 | 1.17 | 28.22 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.91 | 3.00 | 27.91 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.34 | 3.17 | 28.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.34 | 2.83 | 28.34 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.00 | 1.83 | 28.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.00 | 28.17 | 12.00 | 28.17 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.34 | 3.17 | 28.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.93 | 1.17 | 27.93 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.35 | 0.17 | 27.35 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.93 | 1.50 | 27.93 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.75 | 3.17 | 27.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.58 | 2.67 | 27.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.96 | 4.00 | 27.96 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.20 | 3.33 | 28.20 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 26.88 | 3.83 | 26.88 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.88 | 2.33 | 27.88 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.87 | 1.17 | 27.87 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.65 | 1.00 | 27.65 |
Annual Sum or Average | 0.00 | 0.00 | 24.33 | 27.72 | 24.33 | 27.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.20 | 4.00 | 28.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.32 | 0.33 | 27.32 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.33 | 0.33 | 27.34 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.74 | 3.50 | 27.87 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.53 | 3.67 | 28.57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.27 | 3.33 | 28.26 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 27.84 | 7.33 | 27.96 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 27.44 | 5.00 | 27.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.89 | 3.17 | 27.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.60 | 0.67 | 27.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.34 | 0.17 | 27.34 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
Annual Sum or Average | 0.00 | 0.00 | 57.67 | 27.82 | 27.67 | 27.94 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 28.53 | 7.33 | 28.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 19.22 | 0.33 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
February | 0.50 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
Annual Sum or Average | 3.00 | 19.18 | 0.33 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 19.22 | 0.33 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
February | 0.50 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.18 | 1.33 | 28.18 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.94 | 2.83 | 27.94 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.43 | 3.33 | 28.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.40 | 3.17 | 28.40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.98 | 1.67 | 27.98 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
Annual Sum or Average | 2.67 | 19.16 | 0.00 | 19.16 | 12.33 | 26.61 | 12.33 | 27.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 19.32 | 0.00 | 19.32 | 3.33 | 28.43 | 3.33 | 28.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 19.02 | 0.00 | 19.02 | 0.17 | 20.68 | 0.17 | 21.78 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.13 | 1.17 | 28.13 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.91 | 1.33 | 27.91 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.86 | 2.50 | 27.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.57 | 1.50 | 27.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.00 | 3.50 | 28.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.26 | 3.17 | 28.26 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 26.99 | 3.83 | 26.98 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.97 | 2.17 | 27.97 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.98 | 1.00 | 27.98 |
December | 0.50 | 19.12 | 0.00 | 19.12 | 0.50 | 23.36 | 0.50 | 24.77 |
Annual Sum or Average | 1.17 | 19.07 | 0.00 | 19.07 | 21.00 | 27.32 | 20.83 | 27.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 19.12 | 0.00 | 19.12 | 4.00 | 28.26 | 3.83 | 28.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.63 | 0.67 | 27.65 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.45 | 3.00 | 28.50 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.22 | 1.67 | 28.19 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.69 | 2.50 | 28.70 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.56 | 2.00 | 28.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.89 | 2.50 | 27.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
Annual Sum or Average | 0.83 | 19.09 | 0.00 | 19.09 | 22.17 | 28.06 | 12.33 | 28.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 19.13 | 0.00 | 19.13 | 6.00 | 28.69 | 3.00 | 28.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 20.17 | 17.61 | 5.83 | 17.81 | 0.00 | 17.81 | 0.00 | 17.81 |
February | 11.17 | 17.65 | 3.00 | 17.68 | 0.00 | 17.68 | 0.00 | 17.68 |
March | 1.83 | 19.20 | 0.17 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.33 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
November | 4.33 | 19.08 | 0.83 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
December | 12.50 | 18.32 | 2.50 | 18.48 | 0.00 | 18.48 | 0.00 | 18.48 |
Annual Sum or Average | 50.33 | 17.99 | 12.33 | 18.11 | 0.00 | 18.11 | 0.00 | 18.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 20.17 | 19.22 | 5.83 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.00 | 16.45 | 1.83 | 16.26 | 0.00 | 16.26 | 0.00 | 16.26 |
February | 6.33 | 17.44 | 0.83 | 17.15 | 0.00 | 17.15 | 0.00 | 17.15 |
March | 1.33 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
April | 0.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.08 | 1.17 | 28.08 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.81 | 2.33 | 27.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.24 | 3.83 | 28.24 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.16 | 3.83 | 28.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.07 | 1.00 | 28.07 |
October | 0.50 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
November | 3.00 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
December | 7.50 | 17.28 | 0.00 | 17.28 | 0.00 | 17.28 | 0.00 | 17.28 |
Annual Sum or Average | 31.83 | 17.25 | 2.67 | 17.07 | 12.17 | 19.94 | 12.17 | 21.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.26 | 0.00 | 16.26 |
Maximum of Months | 13.00 | 19.42 | 1.83 | 19.42 | 3.83 | 28.24 | 3.83 | 28.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.33 | 17.24 | 0.83 | 17.05 | 0.00 | 17.05 | 0.00 | 17.05 |
February | 2.50 | 18.24 | 0.17 | 18.04 | 0.33 | 19.08 | 0.33 | 19.92 |
March | 0.50 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.92 | 1.17 | 27.92 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.82 | 2.67 | 27.82 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.63 | 1.50 | 27.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.09 | 3.33 | 28.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.31 | 3.00 | 28.33 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.89 | 2.17 | 27.90 |
October | 0.17 | 19.39 | 0.00 | 19.39 | 1.00 | 26.62 | 1.00 | 27.17 |
November | 2.33 | 18.92 | 0.00 | 18.92 | 0.33 | 19.99 | 0.33 | 20.83 |
December | 4.33 | 18.62 | 0.00 | 18.62 | 0.00 | 18.62 | 0.00 | 18.62 |
Annual Sum or Average | 19.17 | 17.95 | 1.00 | 17.80 | 15.83 | 22.27 | 15.50 | 23.99 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.05 | 0.00 | 17.05 |
Maximum of Months | 9.33 | 19.39 | 0.83 | 19.39 | 3.33 | 28.31 | 3.33 | 28.33 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.50 | 18.07 | 0.67 | 17.74 | 0.00 | 17.74 | 0.00 | 17.74 |
February | 2.50 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 |
March | 0.33 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.65 | 0.67 | 27.65 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.43 | 3.17 | 28.45 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.19 | 1.67 | 28.17 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.79 | 3.00 | 28.77 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.71 | 1.83 | 28.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.04 | 2.00 | 28.03 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.17 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
December | 3.50 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 |
Annual Sum or Average | 13.00 | 18.50 | 0.67 | 18.33 | 21.67 | 24.55 | 12.33 | 25.55 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.50 | 19.12 | 0.67 | 19.12 | 6.00 | 28.79 | 3.17 | 28.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 68.83 | 24.63 | 118.50 | 25.49 | 13.50 | 25.61 |
February | 35.67 | 24.00 | 137.33 | 25.32 | 0.00 | 25.32 |
March | 22.50 | 24.00 | 145.00 | 25.57 | 0.00 | 25.57 |
April | 3.00 | 24.00 | 197.67 | 25.56 | 0.00 | 25.56 |
May | 0.00 | 0.00 | 273.67 | 25.17 | 0.00 | 25.17 |
June | 0.00 | 0.00 | 327.00 | 24.94 | 0.00 | 24.94 |
July | 4.33 | 27.46 | 440.83 | 24.90 | 4.33 | 24.92 |
August | 31.00 | 27.58 | 481.83 | 25.00 | 31.00 | 25.14 |
September | 14.50 | 27.62 | 404.83 | 24.95 | 14.50 | 25.04 |
October | 10.17 | 27.78 | 239.83 | 25.62 | 10.17 | 25.71 |
November | 2.83 | 25.68 | 231.17 | 25.49 | 1.33 | 25.50 |
December | 13.17 | 24.00 | 139.00 | 26.07 | 0.00 | 26.07 |
Annual Sum or Average | 206.00 | 25.29 | 3136.67 | 25.22 | 74.83 | 25.27 |
Minimum of Months | 0.00 | 0.00 | 118.50 | 24.90 | 0.00 | 24.92 |
Maximum of Months | 68.83 | 27.78 | 481.83 | 26.07 | 31.00 | 26.07 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 201.33 | 23.84 | 23.33 | 23.99 | 12.83 | 24.07 |
February | 104.00 | 23.85 | 68.00 | 24.27 | 0.00 | 24.27 |
March | 32.83 | 23.97 | 107.17 | 24.98 | 0.00 | 24.98 |
April | 2.17 | 23.99 | 165.83 | 24.90 | 0.00 | 24.90 |
May | 6.33 | 23.81 | 223.33 | 24.60 | 0.00 | 24.60 |
June | 0.00 | 0.00 | 302.00 | 24.45 | 0.00 | 24.45 |
July | 0.00 | 0.00 | 426.83 | 24.36 | 0.00 | 24.36 |
August | 0.00 | 0.00 | 484.33 | 24.26 | 0.00 | 24.26 |
September | 0.00 | 0.00 | 366.83 | 24.46 | 0.00 | 24.46 |
October | 6.50 | 23.74 | 192.33 | 24.92 | 0.00 | 24.92 |
November | 13.83 | 23.87 | 190.17 | 24.88 | 0.00 | 24.88 |
December | 47.83 | 23.90 | 96.33 | 25.11 | 0.00 | 25.11 |
Annual Sum or Average | 414.83 | 23.86 | 2646.50 | 24.52 | 12.83 | 24.52 |
Minimum of Months | 0.00 | 0.00 | 23.33 | 23.99 | 0.00 | 24.07 |
Maximum of Months | 201.33 | 23.99 | 484.33 | 25.11 | 12.83 | 25.11 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 484.17 | 22.69 | 12.00 | 22.61 | 12.00 | 22.53 |
February | 390.50 | 23.15 | 0.00 | 23.15 | 0.00 | 23.15 |
March | 328.17 | 23.57 | 3.00 | 23.58 | 0.00 | 23.58 |
April | 193.83 | 23.55 | 41.50 | 23.75 | 0.00 | 23.75 |
May | 100.33 | 23.59 | 116.33 | 24.05 | 0.00 | 24.05 |
June | 39.67 | 23.60 | 153.33 | 24.30 | 0.00 | 24.30 |
July | 10.67 | 23.60 | 286.67 | 24.34 | 0.00 | 24.34 |
August | 10.83 | 23.49 | 393.83 | 24.23 | 0.00 | 24.23 |
September | 28.67 | 23.46 | 244.83 | 24.31 | 0.00 | 24.31 |
October | 191.83 | 23.44 | 45.17 | 23.71 | 0.00 | 23.71 |
November | 342.33 | 23.36 | 21.50 | 23.42 | 0.00 | 23.42 |
December | 460.33 | 23.07 | 0.00 | 23.07 | 0.00 | 23.07 |
Annual Sum or Average | 2581.33 | 23.21 | 1318.17 | 23.59 | 12.00 | 23.58 |
Minimum of Months | 10.67 | 22.69 | 0.00 | 22.61 | 0.00 | 22.53 |
Maximum of Months | 484.17 | 23.60 | 393.83 | 24.34 | 12.00 | 24.34 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.26 | 131.67 | 20.86 | 131.67 | 20.60 |
February | 442.83 | 21.79 | 76.33 | 21.49 | 76.33 | 21.26 |
March | 472.17 | 22.64 | 17.17 | 22.57 | 17.17 | 22.50 |
April | 333.00 | 22.97 | 30.67 | 23.09 | 0.00 | 23.09 |
May | 215.17 | 23.23 | 72.83 | 23.48 | 0.00 | 23.48 |
June | 112.83 | 23.39 | 127.67 | 23.87 | 0.00 | 23.87 |
July | 48.17 | 23.45 | 273.67 | 24.14 | 0.00 | 24.14 |
August | 55.83 | 23.33 | 341.50 | 24.07 | 0.00 | 24.07 |
September | 172.17 | 23.17 | 151.33 | 23.65 | 0.00 | 23.65 |
October | 395.50 | 22.73 | 1.83 | 22.74 | 0.00 | 22.74 |
November | 466.67 | 22.10 | 35.83 | 21.97 | 34.17 | 21.85 |
December | 497.00 | 21.53 | 101.00 | 21.27 | 101.00 | 21.08 |
Annual Sum or Average | 3713.33 | 22.28 | 1361.50 | 22.48 | 360.33 | 22.30 |
Minimum of Months | 48.17 | 21.26 | 1.83 | 20.86 | 0.00 | 20.60 |
Maximum of Months | 502.00 | 23.45 | 341.50 | 24.14 | 131.67 | 24.14 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.16 | 18.83 | 22.11 | 18.83 | 22.06 |
February | 417.50 | 22.58 | 6.83 | 22.56 | 5.83 | 22.53 |
March | 405.50 | 23.28 | 0.00 | 23.28 | 0.00 | 23.28 |
April | 209.83 | 23.52 | 59.33 | 23.73 | 0.00 | 23.73 |
May | 140.67 | 23.49 | 128.50 | 23.94 | 0.00 | 23.94 |
June | 26.83 | 23.59 | 216.83 | 24.30 | 0.00 | 24.30 |
July | 0.00 | 0.00 | 384.83 | 24.35 | 0.00 | 24.35 |
August | 3.50 | 23.79 | 424.00 | 24.24 | 0.17 | 24.24 |
September | 101.50 | 23.37 | 209.00 | 24.02 | 0.00 | 24.02 |
October | 289.83 | 23.27 | 22.17 | 23.40 | 0.00 | 23.40 |
November | 390.50 | 23.03 | 13.00 | 23.08 | 0.00 | 23.08 |
December | 490.33 | 22.77 | 0.00 | 22.77 | 0.00 | 22.77 |
Annual Sum or Average | 2978.00 | 22.91 | 1483.33 | 23.37 | 24.83 | 23.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 22.11 | 0.00 | 22.06 |
Maximum of Months | 502.00 | 23.79 | 424.00 | 24.35 | 18.83 | 24.35 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.68 | 23.33 | 21.63 | 23.33 | 21.59 |
February | 417.83 | 22.10 | 13.17 | 22.10 | 8.67 | 22.07 |
March | 405.00 | 22.67 | 7.33 | 22.70 | 0.00 | 22.70 |
April | 230.50 | 22.97 | 110.67 | 23.39 | 0.00 | 23.39 |
May | 179.33 | 23.16 | 190.67 | 23.81 | 5.33 | 23.85 |
June | 89.33 | 23.61 | 281.33 | 24.19 | 10.67 | 24.26 |
July | 58.17 | 24.08 | 359.83 | 24.29 | 12.67 | 24.37 |
August | 63.67 | 23.85 | 383.33 | 24.15 | 12.50 | 24.23 |
September | 160.33 | 23.07 | 239.17 | 23.84 | 6.17 | 23.89 |
October | 336.50 | 22.74 | 60.33 | 23.01 | 0.00 | 23.01 |
November | 448.67 | 22.31 | 9.50 | 22.36 | 0.00 | 22.36 |
December | 493.00 | 21.91 | 0.00 | 21.91 | 0.00 | 21.91 |
Annual Sum or Average | 3384.33 | 22.44 | 1678.67 | 23.04 | 79.33 | 23.06 |
Minimum of Months | 58.17 | 21.68 | 0.00 | 21.63 | 0.00 | 21.59 |
Maximum of Months | 502.00 | 24.08 | 383.33 | 24.29 | 23.33 | 24.37 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 459.33 | 21.67 | 56.50 | 21.65 | 43.67 | 21.55 |
February | 348.83 | 22.16 | 78.83 | 22.50 | 16.17 | 22.45 |
March | 339.33 | 22.70 | 79.00 | 23.00 | 0.17 | 23.00 |
April | 216.83 | 23.13 | 148.67 | 23.64 | 4.50 | 23.68 |
May | 193.83 | 23.27 | 194.33 | 23.84 | 9.83 | 23.92 |
June | 108.33 | 23.51 | 265.50 | 24.13 | 8.33 | 24.19 |
July | 59.67 | 24.29 | 362.83 | 24.38 | 15.67 | 24.47 |
August | 45.33 | 24.42 | 409.50 | 24.29 | 14.50 | 24.37 |
September | 135.00 | 23.29 | 281.17 | 24.05 | 9.67 | 24.12 |
October | 274.17 | 22.92 | 137.17 | 23.46 | 7.17 | 23.52 |
November | 386.50 | 22.40 | 51.33 | 22.68 | 3.67 | 22.72 |
December | 427.50 | 22.02 | 40.17 | 22.21 | 3.33 | 22.21 |
Annual Sum or Average | 2994.67 | 22.54 | 2105.00 | 23.27 | 136.67 | 23.29 |
Minimum of Months | 45.33 | 21.67 | 40.17 | 21.65 | 0.17 | 21.55 |
Maximum of Months | 459.33 | 24.42 | 409.50 | 24.38 | 43.67 | 24.47 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 489.33 | 22.29 | 0.00 | 22.29 | 0.00 | 22.29 |
February | 322.83 | 22.88 | 56.67 | 23.18 | 0.33 | 23.18 |
March | 142.33 | 23.38 | 126.50 | 24.08 | 1.00 | 24.09 |
April | 33.67 | 24.96 | 306.83 | 24.80 | 14.00 | 24.88 |
May | 93.17 | 23.89 | 295.33 | 24.41 | 18.17 | 24.53 |
June | 16.33 | 26.32 | 432.67 | 24.54 | 13.17 | 24.61 |
July | 39.33 | 26.67 | 488.50 | 24.76 | 39.33 | 24.89 |
August | 47.17 | 25.89 | 514.00 | 24.59 | 47.17 | 24.69 |
September | 63.00 | 24.11 | 351.00 | 24.49 | 16.83 | 24.58 |
October | 139.83 | 23.28 | 179.50 | 24.17 | 3.33 | 24.20 |
November | 195.67 | 23.28 | 120.50 | 23.89 | 0.33 | 23.89 |
December | 233.67 | 23.28 | 56.17 | 23.67 | 0.33 | 23.67 |
Annual Sum or Average | 1816.33 | 23.21 | 2927.67 | 24.08 | 154.00 | 24.16 |
Minimum of Months | 16.33 | 22.29 | 0.00 | 22.29 | 0.00 | 22.29 |
Maximum of Months | 489.33 | 26.67 | 514.00 | 24.80 | 47.17 | 24.89 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.54 | 281.00 | 20.36 | 281.00 | 20.27 |
February | 454.00 | 21.02 | 161.67 | 20.78 | 161.67 | 20.65 |
March | 511.00 | 21.92 | 40.00 | 21.82 | 40.00 | 21.73 |
April | 414.50 | 22.60 | 18.33 | 22.66 | 1.17 | 22.66 |
May | 281.50 | 23.04 | 59.83 | 23.23 | 0.00 | 23.23 |
June | 141.50 | 23.33 | 102.67 | 23.70 | 0.00 | 23.70 |
July | 75.83 | 23.42 | 256.50 | 24.02 | 0.00 | 24.02 |
August | 96.00 | 23.31 | 303.67 | 23.96 | 0.00 | 23.96 |
September | 253.17 | 22.98 | 90.50 | 23.28 | 0.00 | 23.28 |
October | 479.50 | 22.28 | 4.67 | 22.26 | 4.67 | 22.24 |
November | 489.00 | 21.36 | 98.83 | 21.18 | 98.83 | 21.05 |
December | 497.00 | 20.76 | 232.17 | 20.61 | 232.17 | 20.52 |
Annual Sum or Average | 4195.00 | 21.81 | 1649.83 | 21.92 | 819.50 | 21.70 |
Minimum of Months | 75.83 | 20.54 | 4.67 | 20.36 | 0.00 | 20.27 |
Maximum of Months | 511.00 | 23.42 | 303.67 | 24.02 | 281.00 | 24.02 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.41 | 257.00 | 20.26 | 257.00 | 20.19 |
February | 385.00 | 21.06 | 131.17 | 20.87 | 131.17 | 20.76 |
March | 414.83 | 21.73 | 30.67 | 21.65 | 29.00 | 21.58 |
April | 281.67 | 22.30 | 56.67 | 22.66 | 0.50 | 22.66 |
May | 238.17 | 22.69 | 104.83 | 23.26 | 5.67 | 23.32 |
June | 144.00 | 23.17 | 171.67 | 23.89 | 9.50 | 23.99 |
July | 112.17 | 23.55 | 248.33 | 24.19 | 13.33 | 24.29 |
August | 106.67 | 23.47 | 277.67 | 24.12 | 14.17 | 24.22 |
September | 227.00 | 22.63 | 132.50 | 23.30 | 5.67 | 23.36 |
October | 372.67 | 21.91 | 27.50 | 22.04 | 5.17 | 22.02 |
November | 415.67 | 21.14 | 96.83 | 20.99 | 96.83 | 20.89 |
December | 422.00 | 20.67 | 211.17 | 20.53 | 211.17 | 20.46 |
Annual Sum or Average | 3546.83 | 21.66 | 1746.00 | 21.99 | 779.17 | 21.82 |
Minimum of Months | 106.67 | 20.41 | 27.50 | 20.26 | 0.50 | 20.19 |
Maximum of Months | 427.00 | 23.55 | 277.67 | 24.19 | 257.00 | 24.29 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 470.17 | 20.94 | 197.50 | 20.77 | 188.67 | 20.64 |
February | 371.50 | 21.48 | 135.50 | 21.68 | 82.17 | 21.54 |
March | 378.83 | 21.92 | 87.50 | 22.24 | 16.00 | 22.18 |
April | 288.83 | 22.45 | 120.67 | 23.05 | 4.50 | 23.10 |
May | 256.17 | 22.83 | 161.67 | 23.44 | 9.33 | 23.52 |
June | 181.17 | 23.02 | 195.83 | 23.72 | 5.00 | 23.76 |
July | 125.17 | 23.44 | 299.33 | 24.12 | 12.67 | 24.20 |
August | 119.17 | 23.46 | 343.83 | 24.10 | 13.83 | 24.19 |
September | 195.67 | 22.98 | 234.00 | 23.76 | 10.33 | 23.84 |
October | 329.33 | 22.32 | 120.67 | 22.94 | 8.00 | 23.01 |
November | 431.17 | 21.58 | 86.17 | 21.71 | 53.17 | 21.63 |
December | 445.00 | 21.12 | 182.67 | 21.09 | 155.83 | 20.96 |
Annual Sum or Average | 3592.17 | 21.97 | 2165.33 | 22.55 | 559.50 | 22.42 |
Minimum of Months | 119.17 | 20.94 | 86.17 | 20.77 | 4.50 | 20.64 |
Maximum of Months | 470.17 | 23.46 | 343.83 | 24.12 | 188.67 | 24.20 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.70 | 220.17 | 20.53 | 220.17 | 20.44 |
February | 435.00 | 21.18 | 109.00 | 21.03 | 105.17 | 20.90 |
March | 460.67 | 21.82 | 33.00 | 21.86 | 16.00 | 21.82 |
April | 344.67 | 22.41 | 81.50 | 22.83 | 3.33 | 22.86 |
May | 262.83 | 22.95 | 160.00 | 23.52 | 14.67 | 23.64 |
June | 167.50 | 23.12 | 213.50 | 23.81 | 7.00 | 23.87 |
July | 95.50 | 23.79 | 346.83 | 24.34 | 18.17 | 24.43 |
August | 91.67 | 23.37 | 362.33 | 24.15 | 11.67 | 24.21 |
September | 225.17 | 22.90 | 190.50 | 23.61 | 12.17 | 23.70 |
October | 423.33 | 22.06 | 43.33 | 22.29 | 0.50 | 22.29 |
November | 474.67 | 21.33 | 61.67 | 21.28 | 55.00 | 21.21 |
December | 495.67 | 20.96 | 162.33 | 20.83 | 162.33 | 20.75 |
Annual Sum or Average | 3978.67 | 21.79 | 1984.17 | 22.28 | 626.17 | 22.16 |
Minimum of Months | 91.67 | 20.70 | 33.00 | 20.53 | 0.50 | 20.44 |
Maximum of Months | 502.00 | 23.79 | 362.33 | 24.34 | 220.17 | 24.43 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.08 | 378.17 | 19.95 | 378.17 | 19.89 |
February | 454.00 | 20.45 | 261.33 | 20.23 | 261.33 | 20.12 |
March | 514.00 | 21.23 | 161.17 | 21.00 | 161.17 | 20.86 |
April | 436.17 | 22.04 | 59.50 | 21.92 | 49.00 | 21.79 |
May | 327.33 | 22.54 | 56.17 | 22.72 | 6.33 | 22.68 |
June | 196.83 | 23.01 | 96.50 | 23.40 | 0.00 | 23.40 |
July | 129.67 | 23.19 | 243.67 | 23.84 | 0.00 | 23.84 |
August | 147.33 | 23.02 | 273.50 | 23.75 | 0.00 | 23.75 |
September | 322.17 | 22.49 | 65.50 | 22.75 | 0.00 | 22.75 |
October | 497.33 | 21.55 | 71.00 | 21.36 | 71.00 | 21.21 |
November | 489.00 | 20.64 | 222.50 | 20.40 | 222.50 | 20.27 |
December | 497.00 | 20.20 | 370.50 | 20.08 | 370.50 | 20.03 |
Annual Sum or Average | 4512.83 | 21.34 | 2259.50 | 21.33 | 1520.00 | 21.07 |
Minimum of Months | 129.67 | 20.08 | 56.17 | 19.95 | 0.00 | 19.89 |
Maximum of Months | 514.00 | 23.19 | 378.17 | 23.84 | 378.17 | 23.84 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.10 | 365.00 | 19.96 | 365.00 | 19.90 |
February | 454.00 | 20.60 | 235.67 | 20.39 | 235.67 | 20.28 |
March | 494.83 | 21.35 | 116.17 | 21.12 | 115.00 | 20.96 |
April | 325.00 | 21.91 | 90.00 | 22.12 | 31.67 | 22.00 |
May | 275.50 | 22.34 | 140.67 | 22.97 | 11.33 | 22.98 |
June | 167.50 | 22.93 | 230.50 | 23.76 | 8.00 | 23.82 |
July | 135.50 | 23.38 | 311.33 | 24.06 | 16.50 | 24.16 |
August | 132.67 | 23.25 | 332.00 | 23.99 | 15.50 | 24.08 |
September | 267.17 | 22.18 | 154.83 | 22.96 | 3.83 | 22.99 |
October | 443.00 | 21.49 | 69.67 | 21.40 | 57.17 | 21.27 |
November | 489.00 | 20.65 | 209.83 | 20.43 | 209.83 | 20.31 |
December | 497.00 | 20.24 | 351.50 | 20.10 | 351.50 | 20.05 |
Annual Sum or Average | 4183.17 | 21.27 | 2607.17 | 21.55 | 1421.00 | 21.31 |
Minimum of Months | 132.67 | 20.10 | 69.67 | 19.96 | 3.83 | 19.90 |
Maximum of Months | 502.00 | 23.38 | 365.00 | 24.06 | 365.00 | 24.16 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 487.67 | 20.46 | 290.83 | 20.21 | 287.67 | 20.09 |
February | 391.00 | 20.95 | 204.50 | 20.92 | 169.50 | 20.75 |
March | 402.00 | 21.37 | 146.50 | 21.42 | 97.17 | 21.23 |
April | 314.67 | 21.95 | 138.50 | 22.39 | 39.67 | 22.30 |
May | 284.67 | 22.36 | 151.50 | 23.03 | 13.83 | 23.09 |
June | 213.67 | 22.70 | 182.33 | 23.46 | 6.17 | 23.51 |
July | 161.67 | 23.13 | 287.50 | 23.93 | 12.83 | 24.02 |
August | 160.83 | 23.10 | 319.67 | 23.91 | 13.50 | 23.99 |
September | 242.00 | 22.42 | 211.00 | 23.33 | 7.83 | 23.39 |
October | 357.17 | 21.67 | 133.17 | 22.16 | 35.50 | 22.06 |
November | 449.50 | 20.96 | 182.83 | 20.91 | 153.50 | 20.73 |
December | 462.00 | 20.55 | 281.83 | 20.39 | 269.17 | 20.26 |
Annual Sum or Average | 3926.83 | 21.50 | 2530.17 | 21.91 | 1106.33 | 21.68 |
Minimum of Months | 160.83 | 20.46 | 133.17 | 20.21 | 6.17 | 20.09 |
Maximum of Months | 487.67 | 23.13 | 319.67 | 23.93 | 287.67 | 24.02 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.25 | 317.83 | 20.06 | 317.83 | 19.98 |
February | 442.67 | 20.77 | 209.50 | 20.56 | 206.83 | 20.44 |
March | 474.17 | 21.35 | 111.50 | 21.27 | 97.67 | 21.14 |
April | 366.17 | 21.96 | 98.17 | 22.28 | 29.00 | 22.23 |
May | 302.83 | 22.55 | 145.33 | 23.17 | 16.00 | 23.29 |
June | 210.17 | 22.81 | 196.17 | 23.55 | 7.17 | 23.61 |
July | 130.83 | 23.38 | 320.00 | 24.15 | 18.00 | 24.25 |
August | 146.33 | 23.12 | 323.83 | 23.95 | 17.67 | 24.02 |
September | 285.17 | 22.48 | 165.33 | 23.19 | 10.33 | 23.27 |
October | 445.33 | 21.57 | 63.00 | 21.65 | 32.33 | 21.57 |
November | 481.33 | 20.86 | 162.67 | 20.69 | 158.17 | 20.57 |
December | 497.00 | 20.52 | 291.83 | 20.35 | 291.83 | 20.27 |
Annual Sum or Average | 4284.00 | 21.44 | 2405.17 | 21.77 | 1202.83 | 21.56 |
Minimum of Months | 130.83 | 20.25 | 63.00 | 20.06 | 7.17 | 19.98 |
Maximum of Months | 502.00 | 23.38 | 323.83 | 24.15 | 317.83 | 24.25 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 2.67 | 27.00 | 454.00 | 27.00 | 2.67 | 27.00 |
March | 11.33 | 27.00 | 514.00 | 27.00 | 11.33 | 27.00 |
April | 124.83 | 27.00 | 485.00 | 27.00 | 124.83 | 27.00 |
May | 9.67 | 27.00 | 508.00 | 27.00 | 9.67 | 27.00 |
June | 46.33 | 27.00 | 496.00 | 27.00 | 46.33 | 27.00 |
July | 220.50 | 27.00 | 497.00 | 27.00 | 220.50 | 27.00 |
August | 352.50 | 27.00 | 514.00 | 27.00 | 352.50 | 27.00 |
September | 34.50 | 27.00 | 485.00 | 27.00 | 34.50 | 27.00 |
October | 13.83 | 27.00 | 502.00 | 27.00 | 13.83 | 27.00 |
November | 5.00 | 27.00 | 489.00 | 27.00 | 5.00 | 27.00 |
December | 8.00 | 27.00 | 497.00 | 27.00 | 8.00 | 27.00 |
Annual Sum or Average | 829.17 | 27.00 | 5943.00 | 27.00 | 829.17 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 352.50 | 27.00 | 514.00 | 27.00 | 352.50 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.33 | 25.34 | 436.67 | 26.95 | 0.00 | 26.95 |
February | 0.00 | 0.00 | 427.33 | 27.00 | 0.00 | 27.00 |
March | 0.83 | 27.00 | 514.00 | 27.00 | 0.83 | 27.00 |
April | 8.50 | 27.00 | 485.00 | 27.00 | 8.50 | 27.00 |
May | 0.33 | 27.00 | 508.00 | 27.00 | 0.33 | 27.00 |
June | 8.83 | 27.00 | 496.00 | 27.00 | 8.83 | 27.00 |
July | 45.33 | 27.00 | 497.00 | 27.00 | 45.33 | 27.00 |
August | 71.33 | 27.00 | 514.00 | 27.00 | 71.33 | 27.00 |
September | 12.33 | 27.00 | 485.00 | 27.00 | 12.33 | 27.00 |
October | 4.17 | 27.00 | 502.00 | 27.00 | 4.17 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 166.00 | 26.86 | 5851.00 | 27.00 | 151.67 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 427.33 | 26.95 | 0.00 | 26.95 |
Maximum of Months | 71.33 | 27.00 | 514.00 | 27.00 | 71.33 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 104.50 | 24.50 | 325.83 | 26.29 | 10.00 | 26.21 |
February | 21.50 | 27.00 | 357.50 | 27.00 | 0.00 | 27.00 |
March | 0.83 | 27.00 | 483.17 | 27.00 | 0.83 | 27.00 |
April | 11.00 | 27.00 | 485.00 | 27.00 | 11.00 | 27.00 |
May | 4.00 | 27.00 | 508.00 | 27.00 | 4.00 | 27.00 |
June | 22.50 | 27.00 | 496.00 | 27.00 | 22.50 | 27.00 |
July | 72.83 | 27.00 | 497.00 | 27.00 | 72.83 | 27.00 |
August | 91.17 | 27.00 | 514.00 | 27.00 | 91.17 | 27.00 |
September | 17.17 | 27.00 | 485.00 | 27.00 | 17.17 | 27.00 |
October | 4.17 | 27.00 | 502.00 | 27.00 | 4.17 | 27.00 |
November | 0.00 | 0.00 | 464.83 | 27.00 | 0.00 | 27.00 |
December | 5.33 | 27.00 | 424.50 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 355.00 | 26.26 | 5542.83 | 26.95 | 233.67 | 26.94 |
Minimum of Months | 0.00 | 0.00 | 325.83 | 26.29 | 0.00 | 26.21 |
Maximum of Months | 104.50 | 27.00 | 514.00 | 27.00 | 91.17 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 325.17 | 27.00 | 502.00 | 27.00 | 325.17 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
August | 514.00 | 27.01 | 514.00 | 27.01 | 514.00 | 27.01 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5766.17 | 27.00 | 5943.00 | 27.00 | 5766.17 | 27.00 |
Minimum of Months | 325.17 | 27.00 | 454.00 | 27.00 | 325.17 | 27.00 |
Maximum of Months | 514.00 | 27.01 | 514.00 | 27.01 | 514.00 | 27.01 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 26.83775 | 0.77275 | 17.68151 |
February | 454.00000 | 27.00006 | 27.11692 | 0.84071 | 20.05053 |
March | 514.00000 | 27.00003 | 28.02046 | 0.91292 | 22.68074 |
April | 485.00000 | 27.00002 | 30.78371 | 0.99240 | 25.85876 |
May | 508.00000 | 27.00025 | 33.75812 | 0.25483 | 6.46122 |
June | 496.00000 | 27.00029 | 35.04869 | 0.33182 | 7.36624 |
July | 497.00000 | 27.00030 | 36.25112 | 0.41058 | 8.59479 |
August | 514.00000 | 27.00039 | 36.85951 | 0.45028 | 9.31998 |
September | 485.00000 | 27.00063 | 36.57578 | 0.28700 | 6.82307 |
October | 502.00000 | 27.00012 | 33.30031 | 0.93321 | 23.44502 |
November | 489.00000 | 27.00010 | 31.32998 | 0.92538 | 23.14960 |
December | 497.00000 | 27.00000 | 27.22311 | 0.90826 | 22.47320 |
Annual Sum or Average | 5943.00000 | 27.00018 | 31.95665 | 0.66654 | 16.11045 |
Minimum of Months | 454.00000 | 27.00000 | 26.83775 | 0.25483 | 6.46122 |
Maximum of Months | 514.00000 | 27.00063 | 36.85951 | 0.99240 | 25.85876 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.94664 | 26.99261 | 0.63462 | 13.69262 |
February | 454.00000 | 27.00006 | 27.12034 | 0.70416 | 15.63925 |
March | 514.00000 | 27.00003 | 28.00291 | 0.77599 | 17.82005 |
April | 485.00000 | 27.00002 | 30.76693 | 0.85492 | 20.55235 |
May | 508.00000 | 27.00024 | 33.78706 | 0.16667 | 5.75423 |
June | 496.00000 | 27.00027 | 35.05563 | 0.22569 | 6.19092 |
July | 497.00000 | 27.00032 | 36.26273 | 0.28995 | 6.89371 |
August | 514.00000 | 27.00045 | 36.87338 | 0.31328 | 7.20923 |
September | 485.00000 | 27.00059 | 36.70623 | 0.19983 | 5.99973 |
October | 502.00000 | 27.00011 | 33.30431 | 0.82267 | 19.36947 |
November | 489.00000 | 27.00009 | 31.32216 | 0.76537 | 17.44437 |
December | 497.00000 | 27.00000 | 27.21212 | 0.71152 | 15.74694 |
Annual Sum or Average | 5943.00000 | 26.99567 | 31.98175 | 0.53698 | 12.65636 |
Minimum of Months | 454.00000 | 26.94664 | 26.99261 | 0.16667 | 5.75423 |
Maximum of Months | 514.00000 | 27.00059 | 36.87338 | 0.85492 | 20.55235 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.41969 | 27.48829 | 0.46675 | 11.58933 |
February | 454.00000 | 27.00022 | 27.13164 | 0.63454 | 13.81342 |
March | 514.00000 | 27.00003 | 28.01217 | 0.71685 | 16.04967 |
April | 485.00000 | 27.00003 | 30.77353 | 0.81500 | 19.24877 |
May | 508.00000 | 27.00052 | 33.80829 | 0.13349 | 5.72168 |
June | 496.00000 | 27.00027 | 35.06314 | 0.21069 | 6.16903 |
July | 497.00000 | 27.00032 | 36.26238 | 0.28394 | 6.93664 |
August | 514.00000 | 27.00038 | 36.87337 | 0.30129 | 7.17558 |
September | 485.00000 | 27.00055 | 36.79410 | 0.15969 | 5.85320 |
October | 502.00000 | 27.00011 | 33.32878 | 0.76713 | 17.57453 |
November | 489.00000 | 27.00009 | 31.33765 | 0.69245 | 15.26741 |
December | 497.00000 | 27.00000 | 27.21688 | 0.63238 | 13.57446 |
Annual Sum or Average | 5943.00000 | 26.95119 | 32.03914 | 0.48290 | 11.55141 |
Minimum of Months | 454.00000 | 26.41969 | 27.13164 | 0.13349 | 5.72168 |
Maximum of Months | 514.00000 | 27.00055 | 36.87337 | 0.81500 | 19.24877 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 30.01427 | 1.03422 | 27.59498 |
February | 454.00000 | 27.00020 | 30.49185 | 1.21096 | 35.79961 |
March | 514.00000 | 27.00034 | 28.84484 | 1.35720 | 43.25768 |
April | 485.00000 | 27.00173 | 29.79882 | 1.50683 | 51.27388 |
May | 508.00000 | 27.00012 | 32.17947 | 0.51549 | 10.62495 |
June | 496.00000 | 27.00065 | 32.84059 | 0.74881 | 16.84231 |
July | 497.00000 | 27.00569 | 35.88272 | 0.98658 | 25.59870 |
August | 514.00000 | 27.01173 | 36.84256 | 1.19021 | 34.79011 |
September | 485.00000 | 27.00007 | 36.87037 | 0.58145 | 12.16447 |
October | 502.00000 | 27.00024 | 31.22720 | 1.25310 | 37.88982 |
November | 489.00000 | 27.00055 | 31.23141 | 1.38709 | 44.83237 |
December | 497.00000 | 27.00049 | 28.52009 | 1.48536 | 50.10852 |
Annual Sum or Average | 5943.00000 | 27.00185 | 32.07149 | 1.10387 | 32.52757 |
Minimum of Months | 454.00000 | 27.00000 | 28.52009 | 0.51549 | 10.62495 |
Maximum of Months | 514.00000 | 27.01173 | 36.87037 | 1.50683 | 51.27388 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.56125 | 28.66350 | 0.40433 | 9.12594 |
February | 454.00000 | 24.56713 | 28.42709 | 0.41049 | 8.95808 |
March | 514.00000 | 24.53890 | 28.22375 | 0.41680 | 9.06155 |
April | 485.00000 | 24.65577 | 31.54827 | 0.47095 | 10.28489 |
May | 508.00000 | 24.63613 | 36.34400 | -0.3417 | 8.56832 |
June | 496.00000 | 24.62153 | 38.20023 | -0.3208 | 8.21379 |
July | 497.00000 | 24.77408 | 43.20899 | -0.2340 | 7.56107 |
August | 514.00000 | 24.77703 | 47.98063 | -0.1886 | 8.02480 |
September | 485.00000 | 24.71175 | 43.89026 | -0.2530 | 7.82639 |
October | 502.00000 | 24.73541 | 34.76343 | 0.51413 | 11.32393 |
November | 489.00000 | 24.70992 | 32.95203 | 0.49119 | 10.79582 |
December | 497.00000 | 24.65976 | 27.75854 | 0.43441 | 9.51648 |
Annual Sum or Average | 5943.00000 | 24.66284 | 35.21747 | 0.14765 | 9.10190 |
Minimum of Months | 454.00000 | 24.53890 | 27.75854 | -0.3417 | 7.56107 |
Maximum of Months | 514.00000 | 24.77703 | 47.98063 | 0.51413 | 11.32393 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.08408 | 31.62779 | 0.30961 | 7.51392 |
February | 454.00000 | 24.20837 | 29.98455 | 0.34228 | 7.70043 |
March | 514.00000 | 24.30725 | 29.46288 | 0.38402 | 8.33692 |
April | 485.00000 | 24.33302 | 32.52930 | 0.42785 | 9.11000 |
May | 508.00000 | 24.28447 | 37.66584 | -0.4243 | 9.22929 |
June | 496.00000 | 24.27391 | 39.74199 | -0.3908 | 8.58072 |
July | 497.00000 | 24.31407 | 44.63709 | -0.3322 | 7.68328 |
August | 514.00000 | 24.24345 | 48.40879 | -0.3149 | 7.36152 |
September | 485.00000 | 24.34745 | 45.32119 | -0.3459 | 8.10571 |
October | 502.00000 | 24.37388 | 36.42718 | 0.44856 | 9.54742 |
November | 489.00000 | 24.38700 | 34.85586 | 0.43220 | 9.25110 |
December | 497.00000 | 24.36261 | 29.79288 | 0.38432 | 8.38752 |
Annual Sum or Average | 5943.00000 | 24.29337 | 36.75628 | 0.07389 | 8.40231 |
Minimum of Months | 454.00000 | 24.08408 | 29.46288 | -0.4243 | 7.36152 |
Maximum of Months | 514.00000 | 24.38700 | 48.40879 | 0.44856 | 9.54742 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.73181 | 34.58226 | -0.0471 | 6.01608 |
February | 454.00000 | 23.26874 | 32.83382 | 0.08954 | 5.94756 |
March | 514.00000 | 23.76297 | 31.77447 | 0.22129 | 6.30661 |
April | 485.00000 | 23.94873 | 34.55440 | 0.29728 | 7.14732 |
May | 508.00000 | 24.05194 | 38.66403 | -0.5356 | 11.37413 |
June | 496.00000 | 24.10332 | 40.58897 | -0.4894 | 10.28569 |
July | 497.00000 | 24.17929 | 45.79529 | -0.4269 | 9.18147 |
August | 514.00000 | 24.15783 | 49.34986 | -0.4003 | 8.66918 |
September | 485.00000 | 24.13558 | 46.33030 | -0.4508 | 9.63783 |
October | 502.00000 | 23.89458 | 38.44124 | 0.30494 | 7.24787 |
November | 489.00000 | 23.57414 | 38.28590 | 0.20417 | 6.34859 |
December | 497.00000 | 23.13427 | 33.61762 | 0.05551 | 5.64365 |
Annual Sum or Average | 5943.00000 | 23.74876 | 38.77752 | -0.1003 | 7.83264 |
Minimum of Months | 454.00000 | 22.73181 | 31.77447 | -0.5356 | 5.64365 |
Maximum of Months | 514.00000 | 24.17929 | 49.34986 | 0.30494 | 11.37413 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.25548 | 35.01935 | -0.4261 | 12.03869 |
February | 454.00000 | 21.84495 | 35.30158 | -0.2654 | 9.28722 |
March | 514.00000 | 22.75289 | 34.25160 | -0.0335 | 6.35810 |
April | 485.00000 | 23.32754 | 36.29541 | 0.14128 | 6.39396 |
May | 508.00000 | 23.72221 | 39.69231 | -0.6547 | 15.03486 |
June | 496.00000 | 23.95303 | 41.04269 | -0.5404 | 11.56922 |
July | 497.00000 | 24.07712 | 46.09080 | -0.4557 | 9.76204 |
August | 514.00000 | 24.03428 | 49.78913 | -0.4406 | 9.51937 |
September | 485.00000 | 23.75709 | 47.79181 | -0.5900 | 13.13984 |
October | 502.00000 | 23.00583 | 41.24028 | 0.07971 | 6.23384 |
November | 489.00000 | 22.18429 | 41.83769 | -0.1422 | 7.13205 |
December | 497.00000 | 21.53310 | 36.48129 | -0.3462 | 9.22464 |
Annual Sum or Average | 5943.00000 | 22.96305 | 40.43519 | -0.3070 | 9.64565 |
Minimum of Months | 454.00000 | 21.25548 | 34.25160 | -0.6547 | 6.23384 |
Maximum of Months | 514.00000 | 24.07712 | 49.78913 | 0.14128 | 15.03486 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.15863 | 31.83785 | -0.1906 | 6.69693 |
February | 454.00000 | 22.69681 | 31.64200 | -0.0527 | 6.30745 |
March | 514.00000 | 23.43993 | 30.62658 | 0.13183 | 5.92955 |
April | 485.00000 | 23.88569 | 32.84436 | 0.28182 | 7.10315 |
May | 508.00000 | 23.99018 | 37.45170 | -0.5489 | 12.11017 |
June | 496.00000 | 24.17131 | 39.22986 | -0.4408 | 9.45686 |
July | 497.00000 | 24.27873 | 43.97154 | -0.3485 | 7.92742 |
August | 514.00000 | 24.19450 | 47.85208 | -0.3483 | 7.89598 |
September | 485.00000 | 24.00963 | 45.53176 | -0.5020 | 10.98401 |
October | 502.00000 | 23.64511 | 37.59362 | 0.23117 | 6.60757 |
November | 489.00000 | 23.24343 | 36.72250 | 0.11307 | 6.02906 |
December | 497.00000 | 22.78735 | 31.88581 | -0.0360 | 5.53508 |
Annual Sum or Average | 5943.00000 | 23.54787 | 37.30648 | -0.1439 | 7.72382 |
Minimum of Months | 454.00000 | 22.15863 | 30.62658 | -0.5489 | 5.53508 |
Maximum of Months | 514.00000 | 24.27873 | 47.85208 | 0.28182 | 12.11017 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.67943 | 31.77591 | -0.2858 | 7.36929 |
February | 454.00000 | 22.26886 | 31.63491 | -0.1282 | 6.72739 |
March | 514.00000 | 22.96181 | 30.82890 | 0.05589 | 6.07924 |
April | 485.00000 | 23.57106 | 33.06388 | 0.26019 | 7.48154 |
May | 508.00000 | 23.83229 | 37.43926 | -0.5304 | 13.11744 |
June | 496.00000 | 24.06967 | 39.19294 | -0.3894 | 9.89403 |
July | 497.00000 | 24.14311 | 44.12071 | -0.3192 | 8.77104 |
August | 514.00000 | 24.03054 | 48.15295 | -0.3203 | 8.82447 |
September | 485.00000 | 23.81250 | 45.64018 | -0.4893 | 12.25658 |
October | 502.00000 | 23.21971 | 37.89218 | 0.17033 | 6.72977 |
November | 489.00000 | 22.46021 | 37.44508 | -0.0450 | 6.10073 |
December | 497.00000 | 21.92377 | 32.47283 | -0.2154 | 6.57944 |
Annual Sum or Average | 5943.00000 | 23.17149 | 37.51308 | -0.1874 | 8.33737 |
Minimum of Months | 454.00000 | 21.67943 | 30.82890 | -0.5304 | 6.07924 |
Maximum of Months | 514.00000 | 24.14311 | 48.15295 | 0.26019 | 13.11744 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.89259 | 31.57312 | -0.2351 | 8.02497 |
February | 454.00000 | 22.69305 | 30.89304 | -0.0132 | 7.80270 |
March | 514.00000 | 23.19181 | 30.24477 | 0.13374 | 6.98526 |
April | 485.00000 | 23.70705 | 32.67986 | 0.30194 | 8.30704 |
May | 508.00000 | 23.82998 | 37.39932 | -0.5358 | 13.53498 |
June | 496.00000 | 24.05225 | 39.29695 | -0.4296 | 10.38020 |
July | 497.00000 | 24.22058 | 43.88433 | -0.2996 | 8.42824 |
August | 514.00000 | 24.13979 | 47.73817 | -0.2739 | 8.14835 |
September | 485.00000 | 23.98574 | 45.03536 | -0.3907 | 10.93883 |
October | 502.00000 | 23.53617 | 37.06131 | 0.27411 | 8.42971 |
November | 489.00000 | 22.79932 | 36.80498 | 0.04063 | 7.10737 |
December | 497.00000 | 22.33700 | 31.80349 | -0.1090 | 7.19612 |
Annual Sum or Average | 5943.00000 | 23.37050 | 37.07886 | -0.1296 | 8.78020 |
Minimum of Months | 454.00000 | 21.89259 | 30.24477 | -0.5358 | 6.98526 |
Maximum of Months | 514.00000 | 24.22058 | 47.73817 | 0.30194 | 13.53498 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.33175 | 30.40352 | -0.1135 | 6.00495 |
February | 454.00000 | 23.32016 | 29.47624 | 0.14430 | 6.75215 |
March | 514.00000 | 24.07713 | 28.44743 | 0.35835 | 8.31261 |
April | 485.00000 | 24.47055 | 31.00687 | 0.53477 | 11.88791 |
May | 508.00000 | 24.19684 | 36.47644 | -0.3560 | 9.92867 |
June | 496.00000 | 24.38730 | 38.31528 | -0.2237 | 7.42408 |
July | 497.00000 | 24.59544 | 42.73319 | -0.0422 | 7.01665 |
August | 514.00000 | 24.46985 | 46.66390 | -0.0458 | 6.71184 |
September | 485.00000 | 24.26665 | 44.22405 | -0.2861 | 8.78531 |
October | 502.00000 | 24.08867 | 35.71530 | 0.40351 | 9.25398 |
November | 489.00000 | 23.95222 | 34.09773 | 0.33100 | 8.17411 |
December | 497.00000 | 23.90039 | 28.72354 | 0.27572 | 7.17289 |
Annual Sum or Average | 5943.00000 | 24.00879 | 35.56962 | 0.08051 | 8.11879 |
Minimum of Months | 454.00000 | 22.33175 | 28.44743 | -0.3560 | 6.00495 |
Maximum of Months | 514.00000 | 24.59544 | 46.66390 | 0.53477 | 11.88791 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.53743 | 34.47615 | -0.6252 | 14.92370 |
February | 454.00000 | 21.02054 | 34.63672 | -0.4773 | 11.73085 |
March | 514.00000 | 21.93279 | 34.06466 | -0.2355 | 7.29190 |
April | 485.00000 | 22.81182 | 35.79728 | 0.00758 | 6.32355 |
May | 508.00000 | 23.49113 | 38.96332 | -0.7403 | 18.09181 |
June | 496.00000 | 23.86849 | 40.33320 | -0.5772 | 12.66877 |
July | 497.00000 | 24.03258 | 44.94505 | -0.4742 | 10.25825 |
August | 514.00000 | 23.95611 | 48.99298 | -0.4764 | 10.43258 |
September | 485.00000 | 23.47924 | 47.39416 | -0.7029 | 16.69805 |
October | 502.00000 | 22.35631 | 41.11902 | -0.0831 | 6.23498 |
November | 489.00000 | 21.36458 | 41.05094 | -0.3472 | 8.78840 |
December | 497.00000 | 20.76112 | 35.70838 | -0.5519 | 12.15851 |
Annual Sum or Average | 5943.00000 | 22.47957 | 39.82343 | -0.4404 | 11.29671 |
Minimum of Months | 454.00000 | 20.53743 | 34.06466 | -0.7403 | 6.23498 |
Maximum of Months | 514.00000 | 24.03258 | 48.99298 | 0.00758 | 18.09181 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.41369 | 33.16223 | -0.6556 | 15.59802 |
February | 385.00000 | 21.05574 | 33.11577 | -0.4614 | 10.90553 |
March | 433.00000 | 21.82135 | 32.84785 | -0.2362 | 7.51539 |
April | 410.00000 | 22.89423 | 34.22932 | 0.07318 | 7.16156 |
May | 430.00000 | 23.35729 | 38.22448 | -0.7150 | 19.44393 |
June | 418.00000 | 23.84296 | 39.66515 | -0.4930 | 12.94102 |
July | 422.00000 | 24.03996 | 44.19681 | -0.3897 | 10.87643 |
August | 433.00000 | 23.96967 | 48.12228 | -0.3787 | 10.69390 |
September | 410.00000 | 23.32434 | 46.71282 | -0.6773 | 18.37310 |
October | 427.00000 | 22.20904 | 40.11385 | -0.0887 | 6.85840 |
November | 417.00000 | 21.14632 | 40.03014 | -0.3930 | 9.29109 |
December | 422.00000 | 20.66612 | 34.43743 | -0.5748 | 12.64036 |
Annual Sum or Average | 5034.00000 | 22.40315 | 38.77187 | -0.4159 | 11.86135 |
Minimum of Months | 385.00000 | 20.41369 | 32.84785 | -0.7150 | 6.85840 |
Maximum of Months | 433.00000 | 24.03996 | 48.12228 | 0.07318 | 19.44393 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.15476 | 32.73445 | -0.4462 | 12.02738 |
February | 454.00000 | 22.02338 | 32.18006 | -0.1884 | 9.56188 |
March | 514.00000 | 22.52384 | 31.94364 | -0.0306 | 7.76263 |
April | 485.00000 | 23.17393 | 34.03948 | 0.16290 | 8.09558 |
May | 508.00000 | 23.48618 | 38.29233 | -0.6578 | 17.80346 |
June | 496.00000 | 23.75027 | 40.15604 | -0.5461 | 13.60165 |
July | 497.00000 | 24.01639 | 44.58759 | -0.3915 | 10.61524 |
August | 514.00000 | 23.98412 | 48.40534 | -0.3526 | 10.16154 |
September | 485.00000 | 23.70906 | 45.84883 | -0.4835 | 13.99173 |
October | 502.00000 | 23.00101 | 38.51443 | 0.14409 | 8.47241 |
November | 489.00000 | 21.92489 | 39.04434 | -0.1815 | 8.57148 |
December | 497.00000 | 21.45910 | 33.62423 | -0.3507 | 10.39547 |
Annual Sum or Average | 5943.00000 | 22.85746 | 38.32336 | -0.2780 | 10.93416 |
Minimum of Months | 454.00000 | 21.15476 | 31.94364 | -0.6578 | 7.76263 |
Maximum of Months | 514.00000 | 24.01639 | 48.40534 | 0.16290 | 17.80346 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.70306 | 33.20310 | -0.5643 | 12.94184 |
February | 454.00000 | 21.29861 | 33.24443 | -0.3809 | 10.00131 |
March | 514.00000 | 22.06124 | 32.75574 | -0.1631 | 7.19622 |
April | 485.00000 | 22.95303 | 34.54305 | 0.10254 | 7.47710 |
May | 508.00000 | 23.51136 | 38.27878 | -0.6312 | 17.39397 |
June | 496.00000 | 23.79752 | 40.06006 | -0.4977 | 12.53702 |
July | 497.00000 | 24.17253 | 44.12834 | -0.2895 | 9.42068 |
August | 514.00000 | 24.02880 | 48.33621 | -0.3259 | 9.68710 |
September | 485.00000 | 23.56249 | 46.34249 | -0.5662 | 15.28703 |
October | 502.00000 | 22.40449 | 39.91838 | -0.0276 | 6.68061 |
November | 489.00000 | 21.41405 | 39.93785 | -0.3110 | 8.22276 |
December | 497.00000 | 20.97304 | 34.30434 | -0.4781 | 10.54785 |
Annual Sum or Average | 5943.00000 | 22.58388 | 38.79131 | -0.3445 | 10.61913 |
Minimum of Months | 454.00000 | 20.70306 | 32.75574 | -0.6312 | 6.68061 |
Maximum of Months | 514.00000 | 24.17253 | 48.33621 | 0.10254 | 17.39397 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.07988 | 35.46238 | -0.7834 | 20.84121 |
February | 454.00000 | 20.45454 | 35.79861 | -0.6556 | 17.10056 |
March | 514.00000 | 21.22536 | 35.50157 | -0.4287 | 10.60749 |
April | 485.00000 | 22.23414 | 37.03404 | -0.1403 | 7.50234 |
May | 508.00000 | 23.07811 | 39.99984 | -0.8830 | 24.26929 |
June | 496.00000 | 23.65200 | 40.89507 | -0.6495 | 15.33448 |
July | 497.00000 | 23.88663 | 45.28222 | -0.5191 | 11.78085 |
August | 514.00000 | 23.78733 | 49.51398 | -0.5315 | 12.27531 |
September | 485.00000 | 22.99187 | 48.86204 | -0.8714 | 23.44172 |
October | 502.00000 | 21.57689 | 43.12264 | -0.2853 | 8.30253 |
November | 489.00000 | 20.64309 | 42.80562 | -0.5585 | 13.80564 |
December | 497.00000 | 20.20237 | 37.00447 | -0.7386 | 18.58808 |
Annual Sum or Average | 5943.00000 | 21.99747 | 40.97125 | -0.5868 | 15.30245 |
Minimum of Months | 454.00000 | 20.07988 | 35.46238 | -0.8830 | 7.50234 |
Maximum of Months | 514.00000 | 23.88663 | 49.51398 | -0.1403 | 24.26929 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.10163 | 34.61514 | -0.7728 | 20.36612 |
February | 454.00000 | 20.60411 | 34.79369 | -0.6022 | 15.09802 |
March | 514.00000 | 21.44869 | 34.30993 | -0.3465 | 9.73236 |
April | 485.00000 | 22.62317 | 35.38177 | 0.00453 | 7.73687 |
May | 508.00000 | 23.16587 | 39.14581 | -0.7731 | 22.26581 |
June | 496.00000 | 23.74435 | 40.02883 | -0.5099 | 13.66695 |
July | 497.00000 | 23.94021 | 44.71546 | -0.3981 | 11.29048 |
August | 514.00000 | 23.86997 | 48.77430 | -0.3894 | 11.20052 |
September | 485.00000 | 23.05285 | 47.91153 | -0.7639 | 22.09025 |
October | 502.00000 | 21.78592 | 41.72262 | -0.2068 | 8.16437 |
November | 489.00000 | 20.65424 | 41.91386 | -0.5473 | 13.35892 |
December | 497.00000 | 20.23629 | 36.10358 | -0.7238 | 18.06127 |
Annual Sum or Average | 5943.00000 | 22.11502 | 39.98380 | -0.5019 | 14.40563 |
Minimum of Months | 454.00000 | 20.10163 | 34.30993 | -0.7731 | 7.73687 |
Maximum of Months | 514.00000 | 23.94021 | 48.77430 | 0.00453 | 22.26581 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.56308 | 33.89571 | -0.6293 | 17.23497 |
February | 454.00000 | 21.41473 | 33.34927 | -0.3738 | 12.61926 |
March | 514.00000 | 21.97024 | 33.19943 | -0.1910 | 9.74628 |
April | 485.00000 | 22.73561 | 35.05648 | 0.04373 | 8.61692 |
May | 508.00000 | 23.13758 | 39.16371 | -0.7820 | 23.13174 |
June | 496.00000 | 23.52359 | 40.70075 | -0.6205 | 16.55998 |
July | 497.00000 | 23.84884 | 44.97435 | -0.4413 | 12.45389 |
August | 514.00000 | 23.80671 | 48.94378 | -0.4088 | 12.09556 |
September | 485.00000 | 23.31308 | 47.03186 | -0.6240 | 19.22159 |
October | 502.00000 | 22.43285 | 40.07852 | -0.0146 | 9.00157 |
November | 489.00000 | 21.25774 | 40.62797 | -0.3806 | 11.68805 |
December | 497.00000 | 20.81477 | 35.07048 | -0.5512 | 15.39109 |
Annual Sum or Average | 5943.00000 | 22.41017 | 39.38115 | -0.4151 | 13.99081 |
Minimum of Months | 454.00000 | 20.56308 | 33.19943 | -0.7820 | 8.61692 |
Maximum of Months | 514.00000 | 23.84884 | 48.94378 | 0.04373 | 23.13174 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.25139 | 34.19730 | -0.7129 | 18.40782 |
February | 454.00000 | 20.85308 | 34.16990 | -0.5238 | 13.65681 |
March | 514.00000 | 21.57168 | 33.84782 | -0.3043 | 9.24062 |
April | 485.00000 | 22.51298 | 35.53129 | -0.0125 | 8.06917 |
May | 508.00000 | 23.16964 | 39.09787 | -0.7499 | 22.33783 |
June | 496.00000 | 23.56683 | 40.58195 | -0.5717 | 15.29933 |
July | 497.00000 | 24.01773 | 44.47975 | -0.3350 | 10.89364 |
August | 514.00000 | 23.85135 | 48.86608 | -0.3816 | 11.43757 |
September | 485.00000 | 23.16366 | 47.50459 | -0.7041 | 20.46489 |
October | 502.00000 | 21.86307 | 41.37791 | -0.1752 | 7.72510 |
November | 489.00000 | 20.91289 | 41.17353 | -0.4673 | 11.32034 |
December | 497.00000 | 20.51870 | 35.35500 | -0.6313 | 15.05142 |
Annual Sum or Average | 5943.00000 | 22.19918 | 39.71754 | -0.4639 | 13.65522 |
Minimum of Months | 454.00000 | 20.25139 | 33.84782 | -0.7499 | 7.72510 |
Maximum of Months | 514.00000 | 24.01773 | 48.86608 | -0.0125 | 22.33783 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 14139418.80 | 542.04 | 27-JAN-13:20 | 11.07 | 0.137870E+09 | 0.00 | 0.152010E+09 | 0.15 | 9.83 | 13-JAN-06:50 | 0.00 | 0.00 |
February | 0.868794E+09 | 53441.87 | 27-FEB-16:00 | 59.27 | 0.852811E+10 | 0.00 | 0.939691E+10 | 0.86 | 10.00 | 27-FEB-14:20 | 0.00 | 0.00 |
March | 0.125704E+10 | 34360.95 | 18-MAR-16:00 | 74.18 | 0.122868E+11 | 0.00 | 0.135438E+11 | 0.97 | 9.96 | 18-MAR-16:00 | 0.00 | 0.00 |
April | 0.958176E+10 | 142600.73 | 27-APR-16:10 | 113.06 | 0.877564E+11 | 0.00 | 0.973381E+11 | 1.51 | 10.00 | 01-APR-12:20 | 0.00 | 0.00 |
May | 0.193077E+11 | 157137.41 | 05-MAY-12:40 | 245.47 | 0.177721E+12 | 0.00 | 0.197028E+12 | 3.18 | 10.00 | 14-MAY-12:24 | 0.00 | 0.00 |
June | 0.361956E+11 | 153825.25 | 20-JUN-13:20 | 338.30 | 0.329753E+12 | 0.00 | 0.365949E+12 | 4.50 | 10.00 | 01-JUN-15:00 | 0.00 | 0.00 |
July | 0.616146E+11 | 154433.33 | 20-JUL-12:10 | 446.23 | 0.550198E+12 | 0.00 | 0.611813E+12 | 5.67 | 10.00 | 11-JUL-17:30 | 0.00 | 0.00 |
August | 0.735334E+11 | 154927.13 | 21-AUG-15:00 | 497.63 | 0.644211E+12 | 0.00 | 0.717745E+12 | 6.26 | 10.01 | 30-AUG-04:13 | 0.00 | 0.00 |
September | 0.295864E+11 | 161008.48 | 14-SEP-12:00 | 285.90 | 0.267152E+12 | 0.00 | 0.296738E+12 | 3.80 | 10.00 | 15-SEP-18:00 | 0.00 | 0.00 |
October | 0.556098E+10 | 140491.16 | 04-OCT-15:00 | 101.76 | 0.506645E+11 | 0.00 | 0.562255E+11 | 1.32 | 10.00 | 04-OCT-17:10 | 0.00 | 0.00 |
November | 0.905083E+09 | 42930.23 | 04-NOV-14:10 | 54.57 | 0.892453E+10 | 0.00 | 0.982962E+10 | 0.74 | 10.00 | 04-NOV-15:20 | 0.00 | 0.00 |
December | 53859570.08 | 3546.14 | 16-DEC-07:13 | 31.08 | 0.525228E+09 | 0.00 | 0.579087E+09 | 0.41 | 9.84 | 26-DEC-06:50 | 0.00 | 0.00 |
Annual Sum or Average | 0.238479E+12 | 2258.51 | 0.213786E+13 | 0.00 | 0.237634E+13 | 2.46 | 0.00 | 0.00 | ||||
Minimum of Months | 14139418.80 | 542.04 | 11.07 | 0.137870E+09 | 0.00 | 0.152010E+09 | 0.15 | 9.83 | 0.00 | 0.00 | ||
Maximum of Months | 0.735334E+11 | 161008.48 | 497.63 | 0.644211E+12 | 0.00 | 0.717745E+12 | 6.26 | 10.01 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.163061E+10 | 88089.27 | 27-APR-12:30 | 6.67 | 0.146518E+11 | 0.00 | 0.162824E+11 | 0.08 | 10.49 | 27-APR-17:00 | 0.00 | 0.00 |
May | 0.152433E+10 | 92489.13 | 04-MAY-14:10 | 7.00 | 0.140514E+11 | 0.00 | 0.155758E+11 | 0.09 | 10.59 | 04-MAY-14:00 | 0.00 | 0.00 |
June | 0.279070E+10 | 88077.47 | 28-JUN-13:00 | 12.33 | 0.255448E+11 | 0.00 | 0.283355E+11 | 0.16 | 10.68 | 21-JUN-14:00 | 0.00 | 0.00 |
July | 0.877765E+10 | 104154.94 | 31-JUL-16:00 | 35.17 | 0.777135E+11 | 0.00 | 0.864911E+11 | 0.42 | 10.60 | 19-JUL-13:30 | 0.00 | 0.00 |
August | 0.218752E+11 | 115783.90 | 29-AUG-14:30 | 80.50 | 0.188612E+12 | 0.00 | 0.210487E+12 | 0.95 | 10.71 | 21-AUG-15:40 | 0.00 | 0.00 |
September | 0.372397E+10 | 140037.78 | 12-SEP-13:27 | 15.83 | 0.336092E+11 | 0.00 | 0.373332E+11 | 0.20 | 10.53 | 15-SEP-12:30 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.403224E+11 | 157.50 | 0.354183E+12 | 0.00 | 0.394505E+12 | 0.16 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.218752E+11 | 140037.78 | 80.50 | 0.188612E+12 | 0.00 | 0.210487E+12 | 0.95 | 10.71 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.858894E+09 | 744.00 | 1586.25 | 11-JAN-15:20 | 32766.25 | 05-JAN-16:20 | 18.63 | 18.33 | 15.83 |
February | 0.343684E+10 | 672.00 | 49248.27 | 27-FEB-13:20 | 82865.57 | 27-FEB-15:10 | 19.23 | 18.34 | 15.83 |
March | 0.651531E+10 | 744.00 | 49248.27 | 18-MAR-13:10 | 256422.61 | 18-MAR-16:02 | 19.87 | 18.35 | 15.83 |
April | 0.204734E+11 | 720.00 | 49248.27 | 01-APR-10:30 | 679736.30 | 27-APR-16:00 | 21.46 | 18.79 | 15.83 |
May | 0.203447E+11 | 744.00 | 49248.27 | 02-MAY-15:40 | 152916.88 | 05-MAY-16:00 | 19.31 | 18.71 | 15.83 |
June | 0.404387E+11 | 720.00 | 49248.27 | 01-JUN-14:20 | 358853.73 | 28-JUN-17:00 | 20.56 | 19.17 | 15.83 |
July | 0.683003E+11 | 744.00 | 49248.27 | 01-JUL-12:25 | 574690.51 | 31-JUL-18:00 | 24.06 | 20.60 | 15.83 |
August | 0.956547E+11 | 744.00 | 49248.27 | 01-AUG-00:03 | 756631.59 | 25-AUG-15:00 | 29.03 | 22.26 | 15.83 |
September | 0.280189E+11 | 720.00 | 49248.27 | 01-SEP-14:20 | 154373.39 | 22-SEP-16:00 | 19.43 | 18.82 | 15.83 |
October | 0.912148E+10 | 744.00 | 49248.27 | 03-OCT-12:40 | 161264.73 | 04-OCT-15:00 | 19.37 | 18.37 | 15.83 |
November | 0.607106E+10 | 720.00 | 49248.27 | 04-NOV-10:50 | 320355.09 | 04-NOV-15:00 | 19.80 | 18.36 | 15.83 |
December | 0.503654E+10 | 744.00 | 4071.52 | 14-DEC-12:00 | 120622.18 | 05-DEC-16:00 | 20.22 | 18.33 | 15.83 |
Annual Sum or Average | 0.304271E+12 | 8760.00 | 20.94 | 19.04 | 15.83 | ||||
Minimum of Months | 0.858894E+09 | 672.00 | 1586.25 | 32766.25 | 18.63 | 18.33 | 15.83 | ||
Maximum of Months | 0.956547E+11 | 744.00 | 49248.27 | 756631.59 | 29.03 | 22.26 | 15.83 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 158456.99 | 10-JAN-16:50 | 21.01 | 21.01 | 0.05 |
February | 5310305.43 | 4.83 | 621.31 | 27-FEB-15:10 | 560273.67 | 27-FEB-16:00 | 20.95 | 20.93 | 1.31 |
March | 4305534.98 | 11.46 | 223.81 | 18-MAR-16:00 | 387361.18 | 18-MAR-16:00 | 21.02 | 20.99 | 1.93 |
April | 0.440725E+09 | 57.95 | 15760.69 | 27-APR-11:50 | 1119203.97 | 27-APR-12:00 | 21.24 | 21.06 | 6.13 |
May | 0.686501E+09 | 129.97 | 15760.69 | 04-MAY-13:20 | 1181885.63 | 04-MAY-13:40 | 21.42 | 21.07 | 12.92 |
June | 0.126083E+10 | 232.16 | 15760.69 | 20-JUN-12:30 | 1215830.54 | 20-JUN-13:30 | 21.83 | 21.17 | 21.48 |
July | 0.450722E+10 | 328.57 | 15760.69 | 07-JUL-11:00 | 1172773.41 | 21-JUL-16:00 | 22.24 | 21.17 | 28.48 |
August | 0.782287E+10 | 362.42 | 15760.69 | 07-AUG-09:50 | 1197774.91 | 21-AUG-13:30 | 22.48 | 21.23 | 31.44 |
September | 0.205031E+10 | 186.24 | 15760.69 | 11-SEP-13:20 | 1204592.09 | 11-SEP-15:00 | 21.74 | 21.20 | 18.15 |
October | 46964483.12 | 40.79 | 1839.58 | 04-OCT-15:00 | 1157947.31 | 04-OCT-15:00 | 21.11 | 21.01 | 4.68 |
November | 24084346.18 | 6.72 | 1546.64 | 04-NOV-14:10 | 481536.92 | 04-NOV-14:10 | 21.02 | 21.00 | 1.12 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 211824.07 | 26-DEC-04:05 | 21.02 | 21.02 | 0.27 |
Annual Sum or Average | 0.168491E+11 | 1361.11 | 21.43 | 21.07 | 10.73 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 158456.99 | 20.95 | 20.93 | 0.05 | ||
Maximum of Months | 0.782287E+10 | 362.42 | 15760.69 | 1215830.54 | 22.48 | 21.23 | 31.44 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 21.01 | 21.01 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 20.95 | 20.95 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 21.02 | 21.02 | 0.00 |
April | 0.174043E+09 | 5.00 | 15760.69 | 27-APR-12:40 | 1038407.47 | 26-APR-14:30 | 21.24 | 21.22 | 0.37 |
May | 76634513.90 | 3.50 | 15760.69 | 05-MAY-13:00 | 988576.80 | 04-MAY-15:00 | 21.42 | 21.40 | 0.25 |
June | 0.195228E+09 | 7.67 | 15760.69 | 20-JUN-14:20 | 1105099.13 | 22-JUN-15:10 | 21.83 | 21.79 | 0.57 |
July | 0.157873E+10 | 30.00 | 15760.69 | 07-JUL-13:00 | 1117747.42 | 19-JUL-13:40 | 22.24 | 22.09 | 2.16 |
August | 0.383523E+10 | 70.33 | 15760.69 | 07-AUG-10:30 | 1095349.60 | 09-AUG-09:40 | 22.48 | 22.13 | 5.07 |
September | 0.685255E+09 | 13.39 | 15760.69 | 11-SEP-15:03 | 1124886.68 | 11-SEP-15:03 | 21.74 | 21.67 | 1.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 21.11 | 21.11 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.02 | 21.02 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 21.02 | 21.02 | 0.00 |
Annual Sum or Average | 0.654512E+10 | 129.89 | 21.43 | 21.37 | 0.80 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.95 | 20.95 | 0.00 | ||
Maximum of Months | 0.383523E+10 | 70.33 | 15760.69 | 1124886.68 | 22.48 | 22.13 | 5.07 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.248891E+12 | 0.00 | 471.95 | 1540253.77 | 02-JAN-05:11 | 0.00 | 28.07 | 62.15 | 0.43 | 0.00 | 0.05 | 0.82 | 02-JAN-05:11 |
February | 0.133120E+12 | 0.00 | 348.03 | 1104534.91 | 14-FEB-05:01 | 0.00 | 25.41 | 54.17 | 0.25 | 0.00 | 0.03 | 0.59 | 14-FEB-05:01 |
March | 0.378081E+11 | 0.00 | 254.00 | 1198589.93 | 06-MAR-05:11 | 0.00 | 23.09 | 42.96 | 0.06 | 0.00 | 0.01 | 0.64 | 06-MAR-05:11 |
April | 0.116967E+11 | 0.00 | 108.69 | 701621.65 | 19-APR-05:02 | 0.00 | 23.09 | 31.91 | 0.02 | 0.00 | 0.00 | 0.37 | 19-APR-05:02 |
May | 0.133583E+10 | 0.00 | 45.46 | 192335.96 | 18-MAY-05:02 | 0.00 | 22.15 | 25.80 | 0.00 | 0.00 | 0.00 | 0.10 | 18-MAY-05:02 |
June | 58379498.28 | 0.00 | 7.78 | 5360.30 | 14-JUN-05:02 | 0.00 | 20.68 | 21.34 | 0.00 | 0.00 | 0.00 | 0.00 | 14-JUN-05:02 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 20.53 | 20.53 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 15114.44 | 0.00 | 0.08 | 50.38 | 03-AUG-06:30 | 0.00 | 20.53 | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 | 03-AUG-06:30 |
September | 0.409148E+09 | 0.00 | 35.56 | 65911.87 | 27-SEP-05:03 | 0.00 | 20.49 | 23.53 | 0.00 | 0.00 | 0.00 | 0.04 | 27-SEP-05:03 |
October | 0.121320E+11 | 0.00 | 174.39 | 581332.12 | 30-OCT-05:03 | 0.00 | 20.98 | 35.11 | 0.02 | 0.00 | 0.00 | 0.31 | 30-OCT-05:03 |
November | 0.833368E+11 | 0.00 | 324.25 | 1281665.02 | 24-NOV-05:11 | 0.00 | 22.88 | 49.12 | 0.14 | 0.00 | 0.02 | 0.68 | 24-NOV-05:11 |
December | 0.181845E+12 | 0.00 | 419.48 | 1272344.29 | 18-DEC-05:11 | 0.00 | 25.68 | 57.28 | 0.30 | 0.00 | 0.04 | 0.68 | 18-DEC-05:11 |
Annual Sum or Average | 0.710634E+12 | 0.00 | 2189.68 | 0.00 | 22.79 | 36.96 | 0.10 | 0.00 | 0.01 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.49 | 20.53 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.248891E+12 | 0.00 | 471.95 | 1540253.77 | 0.00 | 28.07 | 62.15 | 0.43 | 0.00 | 0.05 | 0.82 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 18.63 | 18.63 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 19.23 | 19.23 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 19.87 | 19.87 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 21.46 | 21.46 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 19.31 | 19.31 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 20.56 | 20.56 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 24.06 | 24.06 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 29.03 | 29.03 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 19.43 | 19.43 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 19.37 | 19.37 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 19.80 | 19.80 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 20.22 | 20.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 20.94 | 20.94 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.63 | 18.63 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.03 | 29.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 21.23 | 0.00 | 0.02 | 21.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 | 02-JAN-05:20 | 0.35 | 02-JAN-05:20 | 0.00 | 0.00 | 0.00 |
February | 0.807767E+09 | 0.00 | 8.21 | 0.807767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55219.18 | 27-FEB-15:00 | 55219.18 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.107148E+10 | 0.00 | 27.43 | 0.107148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29096.43 | 18-MAR-16:00 | 29096.43 | 18-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.103402E+11 | 0.00 | 93.01 | 0.103402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 125450.24 | 27-APR-14:30 | 125450.24 | 27-APR-14:30 | 0.00 | 0.00 | 0.00 |
May | 0.167513E+11 | 0.00 | 177.29 | 0.167488E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 101267.30 | 04-MAY-15:00 | 101267.30 | 04-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.328265E+11 | 0.00 | 291.19 | 0.328208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 113232.58 | 28-JUN-15:20 | 113232.58 | 28-JUN-15:20 | 0.00 | 0.00 | 0.00 |
July | 0.597965E+11 | 0.00 | 411.82 | 0.591635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 144180.94 | 31-JUL-15:50 | 133654.45 | 31-JUL-14:30 | 0.00 | 0.00 | 0.00 |
August | 0.817936E+11 | 0.00 | 472.25 | 0.796977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 154907.46 | 29-AUG-14:30 | 141764.17 | 29-AUG-15:10 | 0.00 | 0.00 | 0.00 |
September | 0.259091E+11 | 0.00 | 247.64 | 0.256042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 133961.79 | 11-SEP-15:03 | 133961.79 | 11-SEP-15:03 | 0.00 | 0.00 | 0.00 |
October | 0.478266E+10 | 0.00 | 73.99 | 0.478266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78848.81 | 04-OCT-15:00 | 78848.81 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.690295E+09 | 0.00 | 9.81 | 0.690295E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38032.51 | 04-NOV-14:00 | 38032.51 | 04-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 525.30 | 0.00 | 0.25 | 525.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.71 | 26-DEC-06:15 | 0.71 | 26-DEC-06:15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.234769E+12 | 0.00 | 1812.90 | 0.231728E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 21.23 | 0.00 | 0.02 | 21.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 | 0.35 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.817936E+11 | 0.00 | 472.25 | 0.796977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 154907.46 | 141764.17 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 47618.03 | 0.00 | 16.30 | 47618.03 | 0.00 | 0.00 | 0.00 | 0.00 | 2.75 | 02-JAN-06:50 | 2.75 | 02-JAN-06:50 | 0.00 | 0.00 | 0.00 |
February | 0.513887E+10 | 0.00 | 21.56 | 0.513887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 366538.01 | 27-FEB-15:00 | 366538.01 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.776076E+10 | 0.00 | 35.00 | 0.776076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 269642.98 | 18-MAR-16:00 | 269642.98 | 18-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.772722E+11 | 0.00 | 94.94 | 0.772722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1041239.68 | 27-APR-14:40 | 1041239.68 | 27-APR-14:40 | 0.00 | 0.00 | 0.00 |
May | 0.143975E+12 | 0.00 | 181.79 | 0.143943E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 937290.77 | 04-MAY-15:00 | 937290.77 | 04-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.266206E+12 | 0.00 | 285.94 | 0.266182E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1003139.12 | 28-JUN-15:30 | 1003139.12 | 28-JUN-15:30 | 0.00 | 0.00 | 0.00 |
July | 0.468342E+12 | 0.00 | 375.29 | 0.465015E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1244905.61 | 31-JUL-16:00 | 1115127.24 | 31-JUL-15:20 | 0.00 | 0.00 | 0.00 |
August | 0.620347E+12 | 0.00 | 395.08 | 0.606423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1333875.81 | 29-AUG-14:30 | 1237566.50 | 29-AUG-15:10 | 0.00 | 0.00 | 0.00 |
September | 0.228585E+12 | 0.00 | 246.37 | 0.224979E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1061541.21 | 11-SEP-15:03 | 1061541.21 | 11-SEP-15:03 | 0.00 | 0.00 | 0.00 |
October | 0.375576E+11 | 0.00 | 76.86 | 0.375576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 684119.76 | 04-OCT-15:00 | 684119.76 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.601908E+10 | 0.00 | 33.50 | 0.601908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 333008.51 | 04-NOV-14:10 | 333008.51 | 04-NOV-14:10 | 0.00 | 0.00 | 0.00 |
December | 50521.68 | 0.00 | 16.92 | 50521.68 | 0.00 | 0.00 | 0.00 | 0.00 | 2.96 | 26-DEC-06:02 | 2.96 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186120E+13 | 0.00 | 1779.55 | 0.184029E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 47618.03 | 0.00 | 16.30 | 47618.03 | 0.00 | 0.00 | 0.00 | 0.00 | 2.75 | 2.75 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.620347E+12 | 0.00 | 395.08 | 0.606423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1333875.81 | 1237566.50 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 53792.68 | 0.00 | 0.14 | 53792.68 | 0.00 | 0.00 | 0.00 | 0.00 | 446.77 | 09-JAN-04:22 | 446.77 | 09-JAN-04:22 | 0.00 | 0.00 | 0.00 |
February | 0.430738E+09 | 0.00 | 8.50 | 0.430738E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 29511.97 | 27-FEB-15:00 | 29511.97 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.664518E+09 | 0.00 | 23.53 | 0.664518E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26393.94 | 18-MAR-16:00 | 26393.94 | 18-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.801913E+10 | 0.00 | 78.58 | 0.801913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 122332.90 | 27-APR-14:40 | 122332.90 | 27-APR-14:40 | 0.00 | 0.00 | 0.00 |
May | 0.148504E+11 | 0.00 | 167.40 | 0.148471E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 103669.18 | 04-MAY-15:00 | 103669.18 | 04-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.280522E+11 | 0.00 | 276.62 | 0.280503E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 120439.27 | 28-JUN-15:20 | 120439.27 | 28-JUN-15:20 | 0.00 | 0.00 | 0.00 |
July | 0.502032E+11 | 0.00 | 363.06 | 0.498710E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 145155.25 | 31-JUL-16:00 | 133667.21 | 31-JUL-15:20 | 0.00 | 0.00 | 0.00 |
August | 0.655530E+11 | 0.00 | 384.21 | 0.642504E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 151354.07 | 10-AUG-15:40 | 144815.50 | 10-AUG-15:10 | 0.00 | 0.00 | 0.00 |
September | 0.224069E+11 | 0.00 | 233.21 | 0.221718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110282.69 | 12-SEP-13:27 | 105446.61 | 12-SEP-15:20 | 0.00 | 0.00 | 0.00 |
October | 0.323837E+10 | 0.00 | 59.58 | 0.323837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67765.10 | 04-OCT-15:00 | 67765.10 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.576840E+09 | 0.00 | 7.83 | 0.576840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32724.13 | 04-NOV-14:00 | 32724.13 | 04-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 19369.25 | 0.00 | 0.11 | 19369.25 | 0.00 | 0.00 | 0.00 | 0.00 | 62.86 | 26-DEC-04:30 | 62.86 | 26-DEC-04:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.193995E+12 | 0.00 | 1602.78 | 0.192120E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 19369.25 | 0.00 | 0.11 | 19369.25 | 0.00 | 0.00 | 0.00 | 0.00 | 62.86 | 62.86 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.655530E+11 | 0.00 | 384.21 | 0.642504E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 151354.07 | 144815.50 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 48045070.28 | 0.00 | 5.07 | 48045070.28 | 0.00 | 0.00 | 0.00 | 0.00 | 8179.44 | 11-JAN-07:12 | 8179.44 | 11-JAN-07:12 | 0.00 | 0.00 | 0.00 |
February | 0.156443E+10 | 0.00 | 45.17 | 0.131604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49421.53 | 24-FEB-07:12 | 35418.86 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.199320E+10 | 0.00 | 57.89 | 0.193854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37961.91 | 10-MAR-07:12 | 22666.46 | 10-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.497688E+10 | 0.00 | 62.48 | 0.496149E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63126.32 | 27-APR-15:00 | 63126.32 | 27-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.120008E+11 | 0.00 | 179.85 | 0.119672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61981.54 | 15-MAY-16:00 | 61981.54 | 15-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.221279E+11 | 0.00 | 252.39 | 0.217454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 65037.04 | 12-JUN-06:25 | 61878.67 | 28-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.373870E+11 | 0.00 | 308.99 | 0.358228E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 95098.58 | 31-JUL-10:10 | 78123.59 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.480967E+11 | 0.00 | 323.73 | 0.455383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85608.78 | 30-AUG-06:23 | 78649.66 | 21-AUG-14:40 | 0.00 | 0.00 | 0.00 |
September | 0.170712E+11 | 0.00 | 208.13 | 0.165169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78943.23 | 11-SEP-15:03 | 78943.23 | 11-SEP-15:03 | 0.00 | 0.00 | 0.00 |
October | 0.265960E+10 | 0.00 | 58.76 | 0.263208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44749.57 | 04-OCT-15:00 | 44749.57 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.105540E+10 | 0.00 | 25.59 | 0.805155E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42059.84 | 04-NOV-06:11 | 27245.28 | 06-NOV-07:16 | 0.00 | 0.00 | 0.00 |
December | 0.155311E+09 | 0.00 | 14.17 | 0.153337E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 24903.39 | 16-DEC-07:13 | 15016.28 | 16-DEC-07:13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.149136E+12 | 0.00 | 1542.20 | 0.143445E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 48045070.28 | 0.00 | 5.07 | 48045070.28 | 0.00 | 0.00 | 0.00 | 0.00 | 8179.44 | 8179.44 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.480967E+11 | 0.00 | 323.73 | 0.455383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 95098.58 | 78943.23 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.452884E+10 | 0.405178E+10 | 740.61 | 0.452882E+10 | 22862.18 | 0.00 | 0.02 | 09-JAN-12:00 | 0.01 | 11-JAN-22:40 | 3131.09 | 09-JAN-12:00 | 3131.09 | 09-JAN-12:00 | 8.25 | 11-JAN-23:00 | 1909.67 | 09-JAN-12:00 | 0.00 |
February | 0.680323E+10 | 0.450098E+10 | 596.00 | 0.676628E+10 | 36950290.14 | 0.00 | 0.06 | 27-FEB-15:00 | 0.01 | 28-FEB-08:65 | 18117.71 | 27-FEB-15:00 | 18117.71 | 27-FEB-15:00 | 68.65 | 26-FEB-16:40 | 6599.46 | 27-FEB-15:00 | 0.00 |
March | 0.118029E+11 | 0.642545E+10 | 688.90 | 0.114231E+11 | 0.379884E+09 | 0.00 | 0.36 | 18-MAR-16:00 | 0.01 | 10-MAR-05:50 | 125841.07 | 18-MAR-16:00 | 125841.07 | 18-MAR-16:00 | 4599.13 | 09-MAR-12:00 | 41233.31 | 18-MAR-16:00 | 0.00 |
April | 0.763553E+11 | 0.258680E+11 | 627.31 | 0.720775E+11 | 0.427779E+10 | 0.00 | 1.00 | 01-APR-16:25 | 0.01 | 29-APR-06:14 | 409379.61 | 27-APR-16:00 | 409379.61 | 27-APR-16:00 | 61171.98 | 28-APR-13:00 | 142140.33 | 01-APR-16:25 | 0.00 |
May | 0.432714E+10 | 0.418764E+10 | 482.42 | 0.409976E+10 | 0.227373E+09 | 0.00 | 0.21 | 05-MAY-16:00 | 0.01 | 26-MAY-23:50 | 84814.98 | 05-MAY-16:00 | 73222.97 | 05-MAY-16:00 | 11592.02 | 05-MAY-16:00 | 27424.19 | 05-MAY-16:00 | 0.00 |
June | 0.331919E+11 | 0.133666E+11 | 369.35 | 0.316849E+11 | 0.150695E+10 | 0.00 | 0.52 | 28-JUN-17:00 | 0.00 | 07-JUN-01:50 | 215179.78 | 28-JUN-17:00 | 215179.78 | 28-JUN-17:00 | 16964.25 | 21-JUN-17:00 | 70971.02 | 28-JUN-17:00 | 0.00 |
July | 0.208127E+12 | 0.644925E+11 | 559.40 | 0.177035E+12 | 0.310925E+11 | 0.00 | 0.78 | 27-JUL-16:00 | 0.01 | 08-JUL-06:10 | 358106.07 | 27-JUL-16:00 | 319071.53 | 24-JUL-15:00 | 84945.15 | 27-JUL-18:50 | 114122.42 | 24-JUL-15:00 | 0.00 |
August | 0.532851E+12 | 0.155955E+12 | 682.24 | 0.426196E+12 | 0.106656E+12 | 0.00 | 1.00 | 24-AUG-12:10 | 0.01 | 05-AUG-05:04 | 474911.20 | 29-AUG-11:00 | 411853.57 | 29-AUG-16:00 | 158297.55 | 30-AUG-09:00 | 149330.54 | 29-AUG-16:00 | 0.00 |
September | 0.343313E+10 | 0.424353E+10 | 243.37 | 0.289425E+10 | 0.538871E+09 | 0.00 | 0.22 | 22-SEP-16:00 | 0.01 | 04-SEP-13:25 | 86937.91 | 22-SEP-16:00 | 73808.63 | 22-SEP-16:00 | 13129.28 | 22-SEP-16:00 | 27943.94 | 22-SEP-16:00 | 0.00 |
October | 0.380397E+10 | 0.406756E+10 | 494.64 | 0.372888E+10 | 75090925.49 | 0.00 | 0.21 | 04-OCT-15:00 | 0.01 | 01-OCT-00:10 | 71973.06 | 04-OCT-15:00 | 71973.06 | 04-OCT-15:00 | 2125.74 | 08-OCT-13:52 | 24470.04 | 04-OCT-15:00 | 0.00 |
November | 0.994902E+10 | 0.565228E+10 | 554.48 | 0.865023E+10 | 0.129879E+10 | 0.00 | 0.43 | 04-NOV-15:00 | 0.01 | 02-NOV-21:30 | 180067.31 | 04-NOV-15:00 | 134974.22 | 04-NOV-15:00 | 49349.52 | 04-NOV-13:00 | 51651.62 | 04-NOV-15:00 | 0.00 |
December | 0.130115E+11 | 0.682766E+10 | 721.09 | 0.121172E+11 | 0.894319E+09 | 0.00 | 0.03 | 13-DEC-24:00 | 0.01 | 16-DEC-05:14 | 6019.55 | 18-DEC-19:40 | 5613.62 | 04-DEC-05:42 | 604.00 | 10-DEC-21:30 | 2882.24 | 18-DEC-19:40 | 0.00 |
Annual Sum or Average | 0.908186E+12 | 0.299639E+12 | 6759.80 | 0.761201E+12 | 0.146984E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.343313E+10 | 0.405178E+10 | 243.37 | 0.289425E+10 | 22862.18 | 0.00 | 0.02 | 0.00 | 3131.09 | 3131.09 | 8.25 | 1909.67 | 0.00 | ||||||
Maximum of Months | 0.532851E+12 | 0.155955E+12 | 740.61 | 0.426196E+12 | 0.106656E+12 | 0.00 | 1.00 | 0.01 | 474911.20 | 411853.57 | 158297.55 | 149330.54 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.396576E+10 | 0.103373E+10 | 744.00 | 0.396544E+10 | 326978.24 | 0.00 | 0.27 | 08-JAN-16:15 | 0.11 | 07-JAN-08:00 | 2167.61 | 05-JAN-16:10 | 2167.61 | 05-JAN-16:10 | 15.59 | 02-JAN-07:05 | 545.11 | 08-JAN-16:15 | 0.00 |
February | 0.873578E+10 | 0.211261E+10 | 672.00 | 0.872536E+10 | 10416674.95 | 0.00 | 0.53 | 12-FEB-16:55 | 0.36 | 18-FEB-08:00 | 4452.33 | 27-FEB-16:20 | 4435.03 | 27-FEB-16:20 | 128.70 | 24-FEB-11:10 | 1072.07 | 12-FEB-16:55 | 0.00 |
March | 0.153258E+11 | 0.352078E+10 | 744.00 | 0.153177E+11 | 8013316.55 | 0.00 | 0.80 | 31-MAR-24:00 | 0.56 | 01-MAR-07:05 | 7572.79 | 31-MAR-24:00 | 7572.79 | 31-MAR-24:00 | 136.91 | 09-MAR-17:00 | 1646.74 | 31-MAR-24:00 | 0.00 |
April | 0.200563E+11 | 0.445004E+10 | 720.00 | 0.200430E+11 | 13320750.86 | 0.00 | 0.97 | 01-APR-17:32 | 0.29 | 30-APR-24:00 | 8699.67 | 26-APR-18:00 | 8699.67 | 26-APR-18:00 | 165.89 | 28-APR-13:00 | 2652.58 | 01-APR-17:02 | 0.00 |
May | 0.566063E+10 | 0.141073E+10 | 744.00 | 0.562422E+10 | 36402738.80 | 0.00 | 0.45 | 31-MAY-24:00 | 0.17 | 18-MAY-06:05 | 4043.12 | 31-MAY-24:00 | 4035.34 | 31-MAY-24:00 | 134.38 | 05-MAY-17:00 | 927.56 | 31-MAY-24:00 | 0.00 |
June | 0.106230E+11 | 0.252304E+10 | 720.00 | 0.105707E+11 | 52317550.37 | 0.00 | 0.63 | 30-JUN-24:00 | 0.41 | 07-JUN-06:10 | 5914.12 | 30-JUN-24:00 | 5912.27 | 30-JUN-24:00 | 194.27 | 12-JUN-15:00 | 1411.50 | 28-JUN-16:00 | 0.00 |
July | 0.163361E+11 | 0.388666E+10 | 744.00 | 0.162221E+11 | 0.113954E+09 | 0.00 | 0.83 | 30-JUL-18:21 | 0.61 | 01-JUL-07:00 | 7865.23 | 31-JUL-23:33 | 7835.15 | 31-JUL-23:50 | 246.49 | 11-JUL-10:00 | 2242.49 | 24-JUL-15:00 | 0.00 |
August | 0.213738E+11 | 0.517934E+10 | 744.00 | 0.212136E+11 | 0.160227E+09 | 0.00 | 1.00 | 10-AUG-18:00 | 0.29 | 31-AUG-24:00 | 9249.79 | 06-AUG-18:38 | 9249.79 | 06-AUG-18:38 | 277.77 | 30-AUG-08:00 | 2997.21 | 10-AUG-18:00 | 0.00 |
September | 0.565297E+10 | 0.139318E+10 | 720.00 | 0.556174E+10 | 91230617.70 | 0.00 | 0.44 | 30-SEP-24:00 | 0.18 | 28-SEP-06:35 | 3888.76 | 30-SEP-24:00 | 3887.66 | 30-SEP-24:00 | 174.61 | 14-SEP-11:00 | 895.80 | 30-SEP-24:00 | 0.00 |
October | 0.104455E+11 | 0.243952E+10 | 744.00 | 0.104230E+11 | 22575598.74 | 0.00 | 0.61 | 31-OCT-24:00 | 0.38 | 28-OCT-07:00 | 5593.40 | 31-OCT-24:00 | 5593.40 | 31-OCT-24:00 | 136.42 | 26-OCT-14:10 | 1261.92 | 31-OCT-24:00 | 0.00 |
November | 0.147086E+11 | 0.332806E+10 | 720.00 | 0.146850E+11 | 23569063.31 | 0.00 | 0.69 | 11-NOV-15:55 | 0.58 | 24-NOV-07:05 | 6322.37 | 12-NOV-16:00 | 6322.37 | 12-NOV-16:00 | 165.52 | 03-NOV-16:00 | 1550.14 | 04-NOV-15:40 | 0.00 |
December | 0.200272E+11 | 0.445684E+10 | 744.00 | 0.200248E+11 | 2425504.65 | 0.00 | 0.89 | 03-DEC-15:23 | 0.75 | 16-DEC-18:00 | 8142.66 | 10-DEC-15:50 | 8142.66 | 10-DEC-15:50 | 85.65 | 28-DEC-15:00 | 1813.37 | 03-DEC-15:23 | 0.00 |
Annual Sum or Average | 0.152911E+12 | 0.357345E+11 | 8760.00 | 0.152377E+12 | 0.534780E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.396576E+10 | 0.103373E+10 | 672.00 | 0.396544E+10 | 326978.24 | 0.00 | 0.27 | 0.11 | 2167.61 | 2167.61 | 15.59 | 545.11 | 0.00 | ||||||
Maximum of Months | 0.213738E+11 | 0.517934E+10 | 744.00 | 0.212136E+11 | 0.160227E+09 | 0.00 | 1.00 | 0.75 | 9249.79 | 9249.79 | 277.77 | 2997.21 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.155073E+11 | 0.436626E+10 | 683.71 | 0.155073E+11 | 5277.54 | 0.00 | 0.22 | 05-JAN-16:20 | 0.00 | 01-JAN-00:05 | 17308.96 | 05-JAN-16:20 | 17308.96 | 05-JAN-16:20 | 2.96 | 02-JAN-11:10 | 4378.57 | 05-JAN-16:20 | 0.00 |
February | 0.662069E+11 | 0.163280E+11 | 672.00 | 0.661051E+11 | 0.101742E+09 | 0.00 | 0.48 | 08-FEB-16:50 | 0.23 | 21-FEB-07:10 | 40764.67 | 27-FEB-16:20 | 40586.75 | 27-FEB-16:20 | 1243.26 | 24-FEB-11:10 | 9761.77 | 27-FEB-16:20 | 0.00 |
March | 0.132398E+12 | 0.307816E+11 | 744.00 | 0.132318E+12 | 80259437.17 | 0.00 | 0.75 | 31-MAR-23:50 | 0.48 | 06-MAR-07:10 | 67008.82 | 31-MAR-23:50 | 67008.82 | 31-MAR-23:50 | 1353.92 | 09-MAR-17:00 | 14721.46 | 31-MAR-23:50 | 0.00 |
April | 0.182508E+12 | 0.407992E+11 | 720.00 | 0.182374E+12 | 0.134306E+09 | 0.00 | 0.95 | 01-APR-17:42 | 0.23 | 30-APR-24:00 | 82915.02 | 26-APR-18:00 | 82915.02 | 26-APR-18:00 | 1647.00 | 28-APR-13:00 | 24854.03 | 27-APR-16:00 | 0.00 |
May | 0.477097E+11 | 0.120229E+11 | 744.00 | 0.473539E+11 | 0.355787E+09 | 0.00 | 0.44 | 31-MAY-23:40 | 0.12 | 18-MAY-06:05 | 37722.33 | 31-MAY-23:40 | 37616.25 | 31-MAY-23:50 | 1321.53 | 05-MAY-16:10 | 8675.64 | 31-MAY-23:40 | 0.00 |
June | 0.967580E+11 | 0.231130E+11 | 720.00 | 0.962401E+11 | 0.517894E+09 | 0.00 | 0.62 | 30-JUN-24:00 | 0.36 | 14-JUN-06:50 | 55495.64 | 30-JUN-24:00 | 55475.27 | 30-JUN-24:00 | 1930.99 | 12-JUN-15:00 | 13412.83 | 28-JUN-17:00 | 0.00 |
July | 0.152970E+12 | 0.365199E+11 | 744.00 | 0.151842E+12 | 0.112720E+10 | 0.00 | 0.83 | 31-JUL-23:20 | 0.58 | 18-JUL-06:05 | 75668.75 | 31-JUL-23:57 | 75390.27 | 31-JUL-23:53 | 2449.95 | 11-JUL-10:00 | 21276.77 | 24-JUL-15:00 | 0.00 |
August | 0.201698E+12 | 0.490200E+11 | 744.00 | 0.200108E+12 | 0.158920E+10 | 0.00 | 1.00 | 10-AUG-18:00 | 0.25 | 31-AUG-24:00 | 86648.01 | 06-AUG-18:35 | 86648.01 | 06-AUG-18:35 | 2762.55 | 30-AUG-08:00 | 28775.67 | 10-AUG-18:00 | 0.00 |
September | 0.480755E+11 | 0.119737E+11 | 720.00 | 0.471869E+11 | 0.888573E+09 | 0.00 | 0.41 | 30-SEP-23:50 | 0.13 | 28-SEP-06:55 | 34592.72 | 30-SEP-23:50 | 34574.44 | 30-SEP-23:50 | 1728.99 | 14-SEP-11:00 | 8025.12 | 30-SEP-23:50 | 0.00 |
October | 0.875591E+11 | 0.207033E+11 | 744.00 | 0.873364E+11 | 0.222670E+09 | 0.00 | 0.55 | 04-OCT-16:50 | 0.31 | 28-OCT-07:00 | 47191.37 | 31-OCT-24:00 | 47191.37 | 31-OCT-24:00 | 1325.75 | 26-OCT-14:10 | 11845.73 | 04-OCT-16:50 | 0.00 |
November | 0.122497E+12 | 0.281479E+11 | 720.00 | 0.122263E+12 | 0.233879E+09 | 0.00 | 0.66 | 04-NOV-16:00 | 0.47 | 24-NOV-07:05 | 57717.75 | 04-NOV-16:00 | 56524.91 | 04-NOV-16:00 | 1639.89 | 03-NOV-16:00 | 14223.88 | 04-NOV-15:50 | 0.00 |
December | 0.168286E+12 | 0.381009E+11 | 744.00 | 0.168262E+12 | 24463401.03 | 0.00 | 0.82 | 05-DEC-16:00 | 0.61 | 26-DEC-07:03 | 73472.90 | 05-DEC-16:00 | 73472.90 | 05-DEC-16:00 | 844.28 | 28-DEC-15:00 | 16202.33 | 05-DEC-16:00 | 0.00 |
Annual Sum or Average | 0.132217E+13 | 0.311877E+12 | 8699.71 | 0.131690E+13 | 0.527598E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.155073E+11 | 0.436626E+10 | 672.00 | 0.155073E+11 | 5277.54 | 0.00 | 0.22 | 0.00 | 17308.96 | 17308.96 | 2.96 | 4378.57 | 0.00 | ||||||
Maximum of Months | 0.201698E+12 | 0.490200E+11 | 744.00 | 0.200108E+12 | 0.158920E+10 | 0.00 | 1.00 | 0.61 | 86648.01 | 86648.01 | 2762.55 | 28775.67 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.579462E+09 | 0.171201E+09 | 376.03 | 0.579462E+09 | -0.0 | 0.00 | 0.20 | 05-JAN-16:20 | 0.00 | 01-JAN-00:05 | 1592.85 | 05-JAN-16:20 | 1592.85 | 05-JAN-16:20 | 0.00 | 11-JAN-17:20 | 406.27 | 05-JAN-16:20 | 0.00 |
February | 0.512817E+10 | 0.128450E+10 | 671.67 | 0.511812E+10 | 10050898.75 | 0.00 | 0.47 | 27-FEB-16:20 | 0.00 | 19-FEB-09:45 | 4041.87 | 27-FEB-16:30 | 4021.06 | 27-FEB-16:20 | 122.91 | 24-FEB-11:20 | 969.44 | 27-FEB-16:20 | 0.00 |
March | 0.120123E+11 | 0.282331E+10 | 744.00 | 0.120043E+11 | 7959508.48 | 0.00 | 0.69 | 31-MAR-23:20 | 0.35 | 06-MAR-05:16 | 6255.69 | 31-MAR-23:20 | 6255.69 | 31-MAR-23:20 | 134.94 | 09-MAR-17:00 | 1431.85 | 18-MAR-17:02 | 0.00 |
April | 0.174973E+11 | 0.394082E+10 | 720.00 | 0.174840E+11 | 13370090.98 | 0.00 | 0.94 | 26-APR-17:50 | 0.18 | 30-APR-24:00 | 8369.37 | 26-APR-18:00 | 8369.37 | 26-APR-18:00 | 164.79 | 28-APR-13:00 | 2518.17 | 27-APR-16:00 | 0.00 |
May | 0.426955E+10 | 0.108711E+10 | 743.75 | 0.423422E+10 | 35320790.97 | 0.00 | 0.43 | 31-MAY-23:20 | 0.00 | 18-MAY-05:15 | 3701.34 | 31-MAY-23:20 | 3685.81 | 31-MAY-23:30 | 133.28 | 05-MAY-16:10 | 853.73 | 31-MAY-23:20 | 0.00 |
June | 0.943625E+10 | 0.226428E+10 | 720.00 | 0.938445E+10 | 51793524.17 | 0.00 | 0.60 | 30-JUN-23:40 | 0.31 | 14-JUN-06:25 | 5458.22 | 30-JUN-23:40 | 5454.70 | 30-JUN-23:40 | 193.16 | 12-JUN-15:00 | 1370.03 | 28-JUN-16:00 | 0.00 |
July | 0.151649E+11 | 0.363465E+10 | 744.00 | 0.150521E+11 | 0.112810E+09 | 0.00 | 0.83 | 30-JUL-18:31 | 0.55 | 18-JUL-06:05 | 7551.20 | 31-JUL-23:33 | 7522.15 | 31-JUL-23:53 | 244.90 | 11-JUL-10:00 | 2167.43 | 24-JUL-15:00 | 0.00 |
August | 0.200043E+11 | 0.488311E+10 | 744.00 | 0.198455E+11 | 0.158844E+09 | 0.00 | 1.00 | 10-AUG-18:00 | 0.23 | 31-AUG-24:00 | 8756.22 | 06-AUG-18:21 | 8756.22 | 06-AUG-18:21 | 275.16 | 30-AUG-08:00 | 2919.74 | 10-AUG-18:00 | 0.00 |
September | 0.427203E+10 | 0.107649E+10 | 720.00 | 0.418450E+10 | 87529879.79 | 0.00 | 0.36 | 10-SEP-17:31 | 0.06 | 27-SEP-06:10 | 3040.66 | 30-SEP-23:20 | 3036.80 | 30-SEP-23:20 | 176.45 | 14-SEP-11:00 | 810.47 | 14-SEP-17:00 | 0.00 |
October | 0.763822E+10 | 0.182817E+10 | 744.00 | 0.761633E+10 | 21886379.33 | 0.00 | 0.55 | 04-OCT-16:50 | 0.20 | 16-OCT-06:05 | 4651.45 | 04-OCT-16:50 | 4651.45 | 04-OCT-16:50 | 130.61 | 26-OCT-14:10 | 1193.31 | 04-OCT-16:50 | 0.00 |
November | 0.107267E+11 | 0.249919E+10 | 720.00 | 0.107035E+11 | 23181866.27 | 0.00 | 0.64 | 04-NOV-16:00 | 0.34 | 13-NOV-05:00 | 5685.87 | 04-NOV-16:00 | 5567.33 | 04-NOV-16:00 | 163.57 | 03-NOV-16:00 | 1405.77 | 04-NOV-15:50 | 0.00 |
December | 0.150219E+11 | 0.345095E+10 | 744.00 | 0.150195E+11 | 2422443.72 | 0.00 | 0.80 | 05-DEC-16:00 | 0.45 | 26-DEC-04:11 | 7161.01 | 05-DEC-16:00 | 7161.01 | 05-DEC-16:00 | 83.99 | 28-DEC-15:10 | 1587.65 | 05-DEC-16:00 | 0.00 |
Annual Sum or Average | 0.121751E+12 | 0.289438E+11 | 8391.44 | 0.121226E+12 | 0.525169E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.579462E+09 | 0.171201E+09 | 376.03 | 0.579462E+09 | -0.0 | 0.00 | 0.20 | 0.00 | 1592.85 | 1592.85 | 0.00 | 406.27 | 0.00 | ||||||
Maximum of Months | 0.200043E+11 | 0.488311E+10 | 744.00 | 0.198455E+11 | 0.158844E+09 | 0.00 | 1.00 | 0.55 | 8756.22 | 8756.22 | 275.16 | 2919.74 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.64 | 0.00 | 85.64 | 0.62 | 650.16 | 0.00 | 0.00 | 0.00 |
February | 133.26 | 0.00 | 133.26 | 14.43 | 575.07 | 0.00 | 0.00 | 0.00 |
March | 196.34 | 0.00 | 196.34 | 60.94 | 468.30 | 0.00 | 0.00 | 0.00 |
April | 277.84 | 0.99 | 276.85 | 157.10 | 367.11 | 0.00 | 0.00 | 0.00 |
May | 357.51 | 10.62 | 346.89 | 273.38 | 280.90 | 0.00 | 0.00 | 0.00 |
June | 375.91 | 24.82 | 351.09 | 322.42 | 216.33 | 0.00 | 0.00 | 0.00 |
July | 357.28 | 28.01 | 329.27 | 350.31 | 193.66 | 0.00 | 0.00 | 0.00 |
August | 289.22 | 7.82 | 281.41 | 287.35 | 190.78 | 0.00 | 0.00 | 0.00 |
September | 224.66 | 0.07 | 224.59 | 160.63 | 287.34 | 0.00 | 0.00 | 0.00 |
October | 153.93 | 0.00 | 153.93 | 53.22 | 409.99 | 0.00 | 0.00 | 0.00 |
November | 96.96 | 0.00 | 96.96 | 6.39 | 542.39 | 0.00 | 0.00 | 0.00 |
December | 72.77 | 0.00 | 72.77 | 0.11 | 670.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 218.87 | 6.07 | 212.79 | 141.38 | 403.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.77 | 0.00 | 72.77 | 0.11 | 190.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 375.91 | 28.01 | 351.09 | 350.31 | 670.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.64 | 0.00 | 85.64 | 0.62 | 650.16 | 0.00 | 0.00 | 0.00 |
February | 133.26 | 0.00 | 133.26 | 14.43 | 575.07 | 0.00 | 0.00 | 0.00 |
March | 196.34 | 0.00 | 196.34 | 60.94 | 468.30 | 0.00 | 0.00 | 0.00 |
April | 277.84 | 0.99 | 276.85 | 157.10 | 367.11 | 0.00 | 0.00 | 0.00 |
May | 357.51 | 10.62 | 346.89 | 273.38 | 280.90 | 0.00 | 0.00 | 0.00 |
June | 375.91 | 24.82 | 351.09 | 322.42 | 216.33 | 0.00 | 0.00 | 0.00 |
July | 357.28 | 28.01 | 329.27 | 350.31 | 193.66 | 0.00 | 0.00 | 0.00 |
August | 289.22 | 7.82 | 281.41 | 287.35 | 190.78 | 0.00 | 0.00 | 0.00 |
September | 224.66 | 0.07 | 224.59 | 160.63 | 287.34 | 0.00 | 0.00 | 0.00 |
October | 153.93 | 0.00 | 153.93 | 53.22 | 409.99 | 0.00 | 0.00 | 0.00 |
November | 96.96 | 0.00 | 96.96 | 6.39 | 542.39 | 0.00 | 0.00 | 0.00 |
December | 72.77 | 0.00 | 72.77 | 0.11 | 670.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 218.87 | 6.07 | 212.79 | 141.38 | 403.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.77 | 0.00 | 72.77 | 0.11 | 190.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 375.91 | 28.01 | 351.09 | 350.31 | 670.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.64 | 0.00 | 85.64 | 0.62 | 650.16 | 0.00 | 0.00 | 0.00 |
February | 133.26 | 0.00 | 133.26 | 14.43 | 575.07 | 0.00 | 0.00 | 0.00 |
March | 196.34 | 0.00 | 196.34 | 60.94 | 468.30 | 0.00 | 0.00 | 0.00 |
April | 277.84 | 0.99 | 276.85 | 157.10 | 367.11 | 0.00 | 0.00 | 0.00 |
May | 357.51 | 10.62 | 346.89 | 273.38 | 280.90 | 0.00 | 0.00 | 0.00 |
June | 375.91 | 24.82 | 351.09 | 322.42 | 216.33 | 0.00 | 0.00 | 0.00 |
July | 357.28 | 28.01 | 329.27 | 350.31 | 193.66 | 0.00 | 0.00 | 0.00 |
August | 289.22 | 7.82 | 281.41 | 287.35 | 190.78 | 0.00 | 0.00 | 0.00 |
September | 224.66 | 0.07 | 224.59 | 160.63 | 287.34 | 0.00 | 0.00 | 0.00 |
October | 153.93 | 0.00 | 153.93 | 53.22 | 409.99 | 0.00 | 0.00 | 0.00 |
November | 96.96 | 0.00 | 96.96 | 6.39 | 542.39 | 0.00 | 0.00 | 0.00 |
December | 72.77 | 0.00 | 72.77 | 0.11 | 670.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 218.87 | 6.07 | 212.79 | 141.38 | 403.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.77 | 0.00 | 72.77 | 0.11 | 190.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 375.91 | 28.01 | 351.09 | 350.31 | 670.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.64 | 0.00 | 85.64 | 0.62 | 650.16 | 0.00 | 0.00 | 0.00 |
February | 133.26 | 0.00 | 133.26 | 14.43 | 575.07 | 0.00 | 0.00 | 0.00 |
March | 196.34 | 0.00 | 196.34 | 60.94 | 468.30 | 0.00 | 0.00 | 0.00 |
April | 277.84 | 0.99 | 276.85 | 157.10 | 367.11 | 0.00 | 0.00 | 0.00 |
May | 357.51 | 10.62 | 346.89 | 273.38 | 280.90 | 0.00 | 0.00 | 0.00 |
June | 375.91 | 24.82 | 351.09 | 322.42 | 216.33 | 0.00 | 0.00 | 0.00 |
July | 357.28 | 28.01 | 329.27 | 350.31 | 193.66 | 0.00 | 0.00 | 0.00 |
August | 289.22 | 7.82 | 281.41 | 287.35 | 190.78 | 0.00 | 0.00 | 0.00 |
September | 224.66 | 0.07 | 224.59 | 160.63 | 287.34 | 0.00 | 0.00 | 0.00 |
October | 153.93 | 0.00 | 153.93 | 53.22 | 409.99 | 0.00 | 0.00 | 0.00 |
November | 96.96 | 0.00 | 96.96 | 6.39 | 542.39 | 0.00 | 0.00 | 0.00 |
December | 72.77 | 0.00 | 72.77 | 0.11 | 670.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 218.87 | 6.07 | 212.79 | 141.38 | 403.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.77 | 0.00 | 72.77 | 0.11 | 190.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 375.91 | 28.01 | 351.09 | 350.31 | 670.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 85.64 | 0.00 | 85.64 | 0.62 | 650.14 | 0.00 | 0.00 | 0.00 |
February | 133.26 | 0.00 | 133.26 | 14.43 | 575.05 | 0.00 | 0.00 | 0.00 |
March | 196.33 | 0.00 | 196.33 | 60.94 | 468.28 | 0.00 | 0.00 | 0.00 |
April | 277.83 | 0.99 | 276.84 | 157.10 | 367.09 | 0.00 | 0.00 | 0.00 |
May | 357.50 | 10.62 | 346.87 | 273.37 | 280.89 | 0.00 | 0.00 | 0.00 |
June | 375.90 | 24.82 | 351.08 | 322.41 | 216.32 | 0.00 | 0.00 | 0.00 |
July | 357.27 | 28.01 | 329.26 | 350.30 | 193.65 | 0.00 | 0.00 | 0.00 |
August | 289.21 | 7.82 | 281.39 | 287.33 | 190.77 | 0.00 | 0.00 | 0.00 |
September | 224.65 | 0.07 | 224.58 | 160.62 | 287.33 | 0.00 | 0.00 | 0.00 |
October | 153.92 | 0.00 | 153.92 | 53.22 | 409.97 | 0.00 | 0.00 | 0.00 |
November | 96.96 | 0.00 | 96.96 | 6.39 | 542.37 | 0.00 | 0.00 | 0.00 |
December | 72.77 | 0.00 | 72.77 | 0.11 | 670.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 218.86 | 6.07 | 212.79 | 141.38 | 403.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.77 | 0.00 | 72.77 | 0.11 | 190.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 375.90 | 28.01 | 351.08 | 350.30 | 670.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.90 | 38.77 | 114.14 | 44.74 | 668.77 | 0.00 | 0.00 | 0.00 |
February | 280.56 | 99.58 | 180.99 | 160.64 | 577.77 | 0.00 | 0.00 | 0.00 |
March | 418.90 | 151.65 | 267.26 | 325.22 | 474.79 | 0.00 | 0.00 | 0.00 |
April | 649.37 | 269.82 | 379.55 | 635.86 | 372.40 | 0.00 | 0.00 | 0.00 |
May | 690.99 | 240.24 | 450.75 | 719.02 | 306.71 | 0.00 | 0.00 | 0.00 |
June | 827.54 | 360.07 | 467.47 | 934.43 | 238.78 | 0.00 | 0.00 | 0.00 |
July | 770.63 | 345.90 | 424.73 | 912.42 | 205.95 | 0.00 | 0.00 | 0.00 |
August | 757.42 | 378.91 | 378.52 | 929.10 | 198.72 | 0.00 | 0.00 | 0.00 |
September | 560.00 | 258.28 | 301.72 | 603.64 | 299.03 | 0.00 | 0.00 | 0.00 |
October | 365.01 | 155.09 | 209.91 | 314.07 | 419.56 | 0.00 | 0.00 | 0.00 |
November | 178.91 | 50.51 | 128.40 | 81.53 | 548.84 | 0.00 | 0.00 | 0.00 |
December | 146.74 | 47.24 | 99.50 | 58.50 | 676.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 484.14 | 200.11 | 284.03 | 478.24 | 414.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 146.74 | 38.77 | 99.50 | 44.74 | 198.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 827.54 | 378.91 | 467.47 | 934.43 | 676.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.90 | 38.77 | 114.14 | 44.74 | 668.77 | 0.00 | 0.00 | 0.00 |
February | 280.56 | 99.58 | 180.99 | 160.64 | 577.77 | 0.00 | 0.00 | 0.00 |
March | 418.90 | 151.65 | 267.26 | 325.22 | 474.79 | 0.00 | 0.00 | 0.00 |
April | 649.37 | 269.82 | 379.55 | 635.86 | 372.40 | 0.00 | 0.00 | 0.00 |
May | 690.99 | 240.24 | 450.75 | 719.02 | 306.71 | 0.00 | 0.00 | 0.00 |
June | 827.54 | 360.07 | 467.47 | 934.43 | 238.78 | 0.00 | 0.00 | 0.00 |
July | 770.63 | 345.90 | 424.73 | 912.42 | 205.95 | 0.00 | 0.00 | 0.00 |
August | 757.42 | 378.91 | 378.52 | 929.10 | 198.72 | 0.00 | 0.00 | 0.00 |
September | 560.00 | 258.28 | 301.72 | 603.64 | 299.03 | 0.00 | 0.00 | 0.00 |
October | 365.01 | 155.09 | 209.91 | 314.07 | 419.56 | 0.00 | 0.00 | 0.00 |
November | 178.91 | 50.51 | 128.40 | 81.53 | 548.84 | 0.00 | 0.00 | 0.00 |
December | 146.74 | 47.24 | 99.50 | 58.50 | 676.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 484.14 | 200.11 | 284.03 | 478.24 | 414.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 146.74 | 38.77 | 99.50 | 44.74 | 198.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 827.54 | 378.91 | 467.47 | 934.43 | 676.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.90 | 38.77 | 114.14 | 44.74 | 668.76 | 0.00 | 0.00 | 0.00 |
February | 280.56 | 99.58 | 180.98 | 160.64 | 577.76 | 0.00 | 0.00 | 0.00 |
March | 418.90 | 151.64 | 267.25 | 325.22 | 474.78 | 0.00 | 0.00 | 0.00 |
April | 649.36 | 269.82 | 379.54 | 635.84 | 372.39 | 0.00 | 0.00 | 0.00 |
May | 690.98 | 240.24 | 450.74 | 719.01 | 306.71 | 0.00 | 0.00 | 0.00 |
June | 827.52 | 360.06 | 467.46 | 934.41 | 238.77 | 0.00 | 0.00 | 0.00 |
July | 770.61 | 345.90 | 424.72 | 912.41 | 205.95 | 0.00 | 0.00 | 0.00 |
August | 757.41 | 378.90 | 378.51 | 929.08 | 198.72 | 0.00 | 0.00 | 0.00 |
September | 559.99 | 258.27 | 301.72 | 603.62 | 299.02 | 0.00 | 0.00 | 0.00 |
October | 365.00 | 155.09 | 209.91 | 314.06 | 419.56 | 0.00 | 0.00 | 0.00 |
November | 178.90 | 50.51 | 128.40 | 81.53 | 548.83 | 0.00 | 0.00 | 0.00 |
December | 146.74 | 47.24 | 99.50 | 58.50 | 676.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 484.13 | 200.11 | 284.02 | 478.23 | 414.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 146.74 | 38.77 | 99.50 | 44.74 | 198.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 827.52 | 378.90 | 467.46 | 934.41 | 676.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 378.39 | 224.69 | 153.70 | 318.90 | 549.32 | 0.00 | 0.00 | 0.00 |
February | 581.91 | 360.21 | 221.70 | 567.77 | 495.95 | 0.00 | 0.00 | 0.00 |
March | 625.97 | 333.82 | 292.15 | 646.40 | 435.76 | 0.00 | 0.00 | 0.00 |
April | 660.90 | 286.96 | 373.94 | 725.86 | 365.62 | 0.00 | 0.00 | 0.00 |
May | 604.31 | 180.03 | 424.28 | 674.69 | 295.55 | 0.00 | 0.00 | 0.00 |
June | 552.88 | 148.44 | 404.44 | 631.00 | 235.19 | 0.00 | 0.00 | 0.00 |
July | 602.94 | 220.83 | 382.11 | 763.78 | 211.26 | 0.00 | 0.00 | 0.00 |
August | 647.79 | 302.07 | 345.71 | 849.62 | 204.00 | 0.00 | 0.00 | 0.00 |
September | 717.72 | 396.35 | 321.37 | 881.51 | 284.81 | 0.00 | 0.00 | 0.00 |
October | 650.14 | 401.41 | 248.72 | 722.91 | 381.59 | 0.00 | 0.00 | 0.00 |
November | 384.38 | 220.28 | 164.10 | 348.94 | 470.39 | 0.00 | 0.00 | 0.00 |
December | 402.17 | 260.26 | 141.91 | 376.65 | 573.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 567.21 | 277.43 | 289.78 | 625.91 | 374.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 378.39 | 148.44 | 141.91 | 318.90 | 204.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 717.72 | 401.41 | 424.28 | 881.51 | 573.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 378.39 | 224.69 | 153.70 | 318.90 | 549.32 | 0.00 | 0.00 | 0.00 |
February | 581.91 | 360.21 | 221.70 | 567.77 | 495.95 | 0.00 | 0.00 | 0.00 |
March | 625.97 | 333.82 | 292.15 | 646.40 | 435.76 | 0.00 | 0.00 | 0.00 |
April | 660.90 | 286.96 | 373.94 | 725.86 | 365.62 | 0.00 | 0.00 | 0.00 |
May | 604.31 | 180.03 | 424.28 | 674.69 | 295.55 | 0.00 | 0.00 | 0.00 |
June | 552.88 | 148.44 | 404.44 | 631.00 | 235.19 | 0.00 | 0.00 | 0.00 |
July | 602.94 | 220.83 | 382.11 | 763.78 | 211.26 | 0.00 | 0.00 | 0.00 |
August | 647.79 | 302.07 | 345.71 | 849.61 | 204.00 | 0.00 | 0.00 | 0.00 |
September | 717.72 | 396.35 | 321.37 | 881.50 | 284.81 | 0.00 | 0.00 | 0.00 |
October | 650.13 | 401.41 | 248.72 | 722.91 | 381.59 | 0.00 | 0.00 | 0.00 |
November | 384.38 | 220.28 | 164.10 | 348.94 | 470.39 | 0.00 | 0.00 | 0.00 |
December | 402.17 | 260.26 | 141.91 | 376.65 | 573.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 567.21 | 277.43 | 289.78 | 625.91 | 374.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 378.39 | 148.44 | 141.91 | 318.90 | 204.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 717.72 | 401.41 | 424.28 | 881.50 | 573.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 378.39 | 224.69 | 153.70 | 318.90 | 549.32 | 0.00 | 0.00 | 0.00 |
February | 581.91 | 360.21 | 221.70 | 567.77 | 495.95 | 0.00 | 0.00 | 0.00 |
March | 625.97 | 333.82 | 292.15 | 646.40 | 435.76 | 0.00 | 0.00 | 0.00 |
April | 660.90 | 286.96 | 373.94 | 725.86 | 365.62 | 0.00 | 0.00 | 0.00 |
May | 604.31 | 180.03 | 424.28 | 674.69 | 295.55 | 0.00 | 0.00 | 0.00 |
June | 552.88 | 148.44 | 404.44 | 631.00 | 235.19 | 0.00 | 0.00 | 0.00 |
July | 602.94 | 220.83 | 382.11 | 763.78 | 211.26 | 0.00 | 0.00 | 0.00 |
August | 647.79 | 302.07 | 345.71 | 849.62 | 204.00 | 0.00 | 0.00 | 0.00 |
September | 717.72 | 396.35 | 321.37 | 881.51 | 284.81 | 0.00 | 0.00 | 0.00 |
October | 650.14 | 401.41 | 248.72 | 722.91 | 381.59 | 0.00 | 0.00 | 0.00 |
November | 384.38 | 220.28 | 164.10 | 348.94 | 470.39 | 0.00 | 0.00 | 0.00 |
December | 402.17 | 260.26 | 141.91 | 376.65 | 573.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 567.21 | 277.43 | 289.78 | 625.91 | 374.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 378.39 | 148.44 | 141.91 | 318.90 | 204.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 717.72 | 401.41 | 424.28 | 881.51 | 573.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 378.39 | 224.69 | 153.70 | 318.90 | 549.32 | 0.00 | 0.00 | 0.00 |
February | 581.91 | 360.21 | 221.70 | 567.77 | 495.95 | 0.00 | 0.00 | 0.00 |
March | 625.97 | 333.82 | 292.15 | 646.40 | 435.76 | 0.00 | 0.00 | 0.00 |
April | 660.90 | 286.96 | 373.94 | 725.86 | 365.62 | 0.00 | 0.00 | 0.00 |
May | 604.31 | 180.03 | 424.28 | 674.69 | 295.55 | 0.00 | 0.00 | 0.00 |
June | 552.88 | 148.44 | 404.44 | 631.00 | 235.19 | 0.00 | 0.00 | 0.00 |
July | 602.94 | 220.83 | 382.11 | 763.78 | 211.26 | 0.00 | 0.00 | 0.00 |
August | 647.79 | 302.07 | 345.71 | 849.61 | 204.00 | 0.00 | 0.00 | 0.00 |
September | 717.72 | 396.35 | 321.37 | 881.50 | 284.81 | 0.00 | 0.00 | 0.00 |
October | 650.13 | 401.41 | 248.72 | 722.91 | 381.59 | 0.00 | 0.00 | 0.00 |
November | 384.38 | 220.28 | 164.10 | 348.94 | 470.39 | 0.00 | 0.00 | 0.00 |
December | 402.17 | 260.26 | 141.91 | 376.65 | 573.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 567.21 | 277.43 | 289.78 | 625.91 | 374.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 378.39 | 148.44 | 141.91 | 318.90 | 204.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 717.72 | 401.41 | 424.28 | 881.50 | 573.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 378.38 | 224.68 | 153.70 | 318.88 | 549.29 | 0.00 | 0.00 | 0.00 |
February | 581.89 | 360.20 | 221.69 | 567.75 | 495.93 | 0.00 | 0.00 | 0.00 |
March | 625.94 | 333.81 | 292.13 | 646.38 | 435.74 | 0.00 | 0.00 | 0.00 |
April | 660.88 | 286.95 | 373.93 | 725.83 | 365.60 | 0.00 | 0.00 | 0.00 |
May | 604.29 | 180.02 | 424.26 | 674.66 | 295.54 | 0.00 | 0.00 | 0.00 |
June | 552.86 | 148.44 | 404.43 | 630.97 | 235.18 | 0.00 | 0.00 | 0.00 |
July | 602.92 | 220.82 | 382.10 | 763.75 | 211.26 | 0.00 | 0.00 | 0.00 |
August | 647.76 | 302.06 | 345.70 | 849.58 | 203.99 | 0.00 | 0.00 | 0.00 |
September | 717.69 | 396.33 | 321.36 | 881.47 | 284.80 | 0.00 | 0.00 | 0.00 |
October | 650.11 | 401.39 | 248.71 | 722.89 | 381.58 | 0.00 | 0.00 | 0.00 |
November | 384.37 | 220.27 | 164.09 | 348.92 | 470.37 | 0.00 | 0.00 | 0.00 |
December | 402.16 | 260.25 | 141.91 | 376.64 | 573.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 567.19 | 277.42 | 289.77 | 625.89 | 374.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 378.38 | 148.44 | 141.91 | 318.88 | 203.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 717.69 | 401.39 | 424.26 | 881.47 | 573.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 161.28 | 47.56 | 113.72 | 57.11 | 714.69 | 0.00 | 0.00 | 0.00 |
February | 289.16 | 108.67 | 180.48 | 175.08 | 648.26 | 0.00 | 0.00 | 0.00 |
March | 405.18 | 136.76 | 268.42 | 302.69 | 555.47 | 0.00 | 0.00 | 0.00 |
April | 616.44 | 235.69 | 380.75 | 576.43 | 458.73 | 0.00 | 0.00 | 0.00 |
May | 793.22 | 322.24 | 470.98 | 849.25 | 348.18 | 0.00 | 0.00 | 0.00 |
June | 762.86 | 296.19 | 466.66 | 832.77 | 284.98 | 0.00 | 0.00 | 0.00 |
July | 942.41 | 495.38 | 447.03 | 1137.60 | 265.90 | 0.00 | 0.00 | 0.00 |
August | 779.60 | 398.08 | 381.51 | 949.39 | 264.47 | 0.00 | 0.00 | 0.00 |
September | 634.86 | 304.62 | 330.24 | 712.74 | 344.15 | 0.00 | 0.00 | 0.00 |
October | 361.43 | 147.26 | 214.16 | 306.17 | 485.42 | 0.00 | 0.00 | 0.00 |
November | 179.99 | 50.76 | 129.22 | 79.06 | 635.51 | 0.00 | 0.00 | 0.00 |
December | 151.32 | 51.85 | 99.46 | 67.24 | 795.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 507.80 | 217.08 | 290.72 | 505.99 | 482.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 151.32 | 47.56 | 99.46 | 57.11 | 264.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 942.41 | 495.38 | 470.98 | 1137.60 | 795.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 161.28 | 47.56 | 113.72 | 57.11 | 714.69 | 0.00 | 0.00 | 0.00 |
February | 289.16 | 108.67 | 180.48 | 175.08 | 648.26 | 0.00 | 0.00 | 0.00 |
March | 405.18 | 136.76 | 268.42 | 302.69 | 555.47 | 0.00 | 0.00 | 0.00 |
April | 616.44 | 235.69 | 380.75 | 576.43 | 458.73 | 0.00 | 0.00 | 0.00 |
May | 793.22 | 322.24 | 470.98 | 849.25 | 348.18 | 0.00 | 0.00 | 0.00 |
June | 762.86 | 296.19 | 466.66 | 832.77 | 284.98 | 0.00 | 0.00 | 0.00 |
July | 942.41 | 495.38 | 447.03 | 1137.60 | 265.90 | 0.00 | 0.00 | 0.00 |
August | 779.60 | 398.08 | 381.51 | 949.39 | 264.47 | 0.00 | 0.00 | 0.00 |
September | 634.86 | 304.62 | 330.24 | 712.74 | 344.15 | 0.00 | 0.00 | 0.00 |
October | 361.43 | 147.26 | 214.16 | 306.17 | 485.42 | 0.00 | 0.00 | 0.00 |
November | 179.99 | 50.76 | 129.22 | 79.06 | 635.51 | 0.00 | 0.00 | 0.00 |
December | 151.32 | 51.85 | 99.46 | 67.24 | 795.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 507.80 | 217.08 | 290.72 | 505.99 | 482.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 151.32 | 47.56 | 99.46 | 57.11 | 264.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 942.41 | 495.38 | 470.98 | 1137.60 | 795.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 161.27 | 47.56 | 113.72 | 57.11 | 714.68 | 0.00 | 0.00 | 0.00 |
February | 289.15 | 108.67 | 180.48 | 175.08 | 648.25 | 0.00 | 0.00 | 0.00 |
March | 405.18 | 136.76 | 268.42 | 302.69 | 555.46 | 0.00 | 0.00 | 0.00 |
April | 616.43 | 235.69 | 380.75 | 576.42 | 458.73 | 0.00 | 0.00 | 0.00 |
May | 793.20 | 322.24 | 470.97 | 849.24 | 348.18 | 0.00 | 0.00 | 0.00 |
June | 762.84 | 296.19 | 466.66 | 832.75 | 284.98 | 0.00 | 0.00 | 0.00 |
July | 942.39 | 495.37 | 447.02 | 1137.58 | 265.89 | 0.00 | 0.00 | 0.00 |
August | 779.58 | 398.08 | 381.50 | 949.37 | 264.47 | 0.00 | 0.00 | 0.00 |
September | 634.85 | 304.61 | 330.24 | 712.73 | 344.14 | 0.00 | 0.00 | 0.00 |
October | 361.42 | 147.26 | 214.16 | 306.16 | 485.41 | 0.00 | 0.00 | 0.00 |
November | 179.99 | 50.76 | 129.22 | 79.06 | 635.49 | 0.00 | 0.00 | 0.00 |
December | 151.31 | 51.85 | 99.46 | 67.24 | 795.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 507.79 | 217.08 | 290.72 | 505.98 | 482.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 151.31 | 47.56 | 99.46 | 57.11 | 264.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 942.39 | 495.37 | 470.97 | 1137.58 | 795.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 428.20 | 0.00 | 428.20 | 10.11 | 2805.18 | 0.00 | 0.00 | 0.00 |
February | 666.30 | 0.00 | 666.30 | 110.82 | 2499.39 | 0.00 | 0.00 | 0.00 |
March | 981.68 | 0.00 | 981.68 | 371.71 | 2060.66 | 0.00 | 0.00 | 0.00 |
April | 1389.18 | 4.93 | 1384.25 | 856.97 | 1641.33 | 0.00 | 0.00 | 0.00 |
May | 1787.53 | 53.10 | 1734.42 | 1403.23 | 1322.06 | 0.00 | 0.00 | 0.00 |
June | 1879.54 | 124.12 | 1755.42 | 1641.88 | 1018.64 | 0.00 | 0.00 | 0.00 |
July | 1786.40 | 140.06 | 1646.34 | 1786.09 | 911.71 | 0.00 | 0.00 | 0.00 |
August | 1446.10 | 39.09 | 1407.01 | 1474.08 | 894.00 | 0.00 | 0.00 | 0.00 |
September | 1123.28 | 0.33 | 1122.95 | 835.20 | 1332.11 | 0.00 | 0.00 | 0.00 |
October | 769.64 | 0.00 | 769.64 | 321.55 | 1803.05 | 0.00 | 0.00 | 0.00 |
November | 484.79 | 0.00 | 484.79 | 55.06 | 2295.26 | 0.00 | 0.00 | 0.00 |
December | 363.86 | 0.00 | 363.86 | 4.32 | 2831.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1094.32 | 30.36 | 1063.96 | 743.24 | 1780.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 363.86 | 0.00 | 363.86 | 4.32 | 894.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1879.54 | 140.06 | 1755.42 | 1786.09 | 2831.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 458.71 | 116.30 | 342.41 | 150.65 | 1772.77 | 0.00 | 0.00 | 0.00 |
February | 841.69 | 298.73 | 542.95 | 517.72 | 1568.85 | 0.00 | 0.00 | 0.00 |
March | 1256.70 | 454.93 | 801.76 | 1004.80 | 1303.02 | 0.00 | 0.00 | 0.00 |
April | 1948.09 | 809.46 | 1138.63 | 1920.65 | 1047.43 | 0.00 | 0.00 | 0.00 |
May | 2072.94 | 720.72 | 1352.23 | 2160.75 | 876.93 | 0.00 | 0.00 | 0.00 |
June | 2482.59 | 1080.19 | 1402.39 | 2791.50 | 690.99 | 0.00 | 0.00 | 0.00 |
July | 2311.86 | 1037.70 | 1274.17 | 2727.34 | 603.76 | 0.00 | 0.00 | 0.00 |
August | 2272.24 | 1136.70 | 1135.53 | 2773.80 | 592.71 | 0.00 | 0.00 | 0.00 |
September | 1679.99 | 774.82 | 905.16 | 1817.94 | 846.18 | 0.00 | 0.00 | 0.00 |
October | 1095.01 | 465.28 | 629.74 | 967.49 | 1144.69 | 0.00 | 0.00 | 0.00 |
November | 536.71 | 151.52 | 385.19 | 268.35 | 1458.49 | 0.00 | 0.00 | 0.00 |
December | 440.23 | 141.72 | 298.50 | 192.95 | 1803.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1452.40 | 600.32 | 852.08 | 1445.92 | 1140.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 440.23 | 116.30 | 298.50 | 150.65 | 592.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2482.59 | 1136.70 | 1402.39 | 2791.50 | 1803.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1891.94 | 1123.44 | 768.50 | 1611.17 | 2575.77 | 0.00 | 0.00 | 0.00 |
February | 2909.51 | 1801.03 | 1108.48 | 2850.79 | 2361.91 | 0.00 | 0.00 | 0.00 |
March | 3129.79 | 1669.09 | 1460.71 | 3232.30 | 2065.95 | 0.00 | 0.00 | 0.00 |
April | 3304.47 | 1434.78 | 1869.69 | 3626.14 | 1739.96 | 0.00 | 0.00 | 0.00 |
May | 3021.51 | 900.14 | 2121.37 | 3357.91 | 1434.36 | 0.00 | 0.00 | 0.00 |
June | 2764.39 | 742.20 | 2022.19 | 3146.91 | 1131.02 | 0.00 | 0.00 | 0.00 |
July | 3014.69 | 1104.14 | 1910.55 | 3808.82 | 1021.23 | 0.00 | 0.00 | 0.00 |
August | 3238.90 | 1510.35 | 1728.55 | 4236.73 | 994.86 | 0.00 | 0.00 | 0.00 |
September | 3588.57 | 1981.73 | 1606.84 | 4392.95 | 1386.16 | 0.00 | 0.00 | 0.00 |
October | 3250.64 | 2007.03 | 1243.61 | 3604.88 | 1821.02 | 0.00 | 0.00 | 0.00 |
November | 1921.88 | 1101.40 | 820.48 | 1766.53 | 2190.77 | 0.00 | 0.00 | 0.00 |
December | 2010.84 | 1301.30 | 709.55 | 1905.45 | 2662.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2836.04 | 1387.16 | 1448.88 | 3129.52 | 1779.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1891.94 | 742.20 | 709.55 | 1611.17 | 994.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3588.57 | 2007.03 | 2121.37 | 4392.95 | 2662.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 483.83 | 142.67 | 341.15 | 190.52 | 1839.19 | 0.00 | 0.00 | 0.00 |
February | 867.46 | 326.02 | 541.45 | 575.44 | 1638.27 | 0.00 | 0.00 | 0.00 |
March | 1215.54 | 410.28 | 805.26 | 975.92 | 1379.29 | 0.00 | 0.00 | 0.00 |
April | 1849.31 | 707.06 | 1142.25 | 1808.94 | 1151.29 | 0.00 | 0.00 | 0.00 |
May | 2379.63 | 966.71 | 1412.91 | 2569.36 | 964.37 | 0.00 | 0.00 | 0.00 |
June | 2288.55 | 888.57 | 1399.98 | 2533.02 | 762.30 | 0.00 | 0.00 | 0.00 |
July | 2827.19 | 1486.12 | 1341.07 | 3445.18 | 710.99 | 0.00 | 0.00 | 0.00 |
August | 2338.76 | 1194.24 | 1144.52 | 2893.88 | 690.36 | 0.00 | 0.00 | 0.00 |
September | 1904.57 | 913.85 | 990.71 | 2164.00 | 938.23 | 0.00 | 0.00 | 0.00 |
October | 1084.28 | 441.79 | 642.48 | 971.50 | 1223.86 | 0.00 | 0.00 | 0.00 |
November | 539.96 | 152.29 | 387.67 | 278.91 | 1513.85 | 0.00 | 0.00 | 0.00 |
December | 453.94 | 155.55 | 298.39 | 231.39 | 1880.09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1523.39 | 651.23 | 872.16 | 1559.64 | 1222.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 453.94 | 142.67 | 298.39 | 190.52 | 690.36 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2827.19 | 1486.12 | 1412.91 | 3445.18 | 1880.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 428.20 | 0.00 | 428.20 | 17.37 | 2597.42 | 0.00 | 0.00 | 0.00 |
February | 666.30 | 0.00 | 666.30 | 135.95 | 2293.43 | 0.00 | 0.00 | 0.00 |
March | 981.68 | 0.00 | 981.68 | 416.70 | 1888.36 | 0.00 | 0.00 | 0.00 |
April | 1389.18 | 4.93 | 1384.25 | 899.47 | 1533.44 | 0.00 | 0.00 | 0.00 |
May | 1787.53 | 53.10 | 1734.42 | 1431.65 | 1257.48 | 0.00 | 0.00 | 0.00 |
June | 1879.54 | 124.12 | 1755.42 | 1649.31 | 987.37 | 0.00 | 0.00 | 0.00 |
July | 1786.40 | 140.06 | 1646.34 | 1782.66 | 891.87 | 0.00 | 0.00 | 0.00 |
August | 1446.10 | 39.09 | 1407.01 | 1476.98 | 867.97 | 0.00 | 0.00 | 0.00 |
September | 1123.28 | 0.33 | 1122.95 | 863.04 | 1248.04 | 0.00 | 0.00 | 0.00 |
October | 769.64 | 0.00 | 769.64 | 367.49 | 1632.40 | 0.00 | 0.00 | 0.00 |
November | 484.79 | 0.00 | 484.79 | 74.72 | 2060.73 | 0.00 | 0.00 | 0.00 |
December | 363.86 | 0.00 | 363.86 | 10.70 | 2584.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1094.32 | 30.36 | 1063.96 | 764.42 | 1650.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 363.86 | 0.00 | 363.86 | 10.70 | 867.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1879.54 | 140.06 | 1755.42 | 1782.66 | 2597.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 458.71 | 116.30 | 342.41 | 163.29 | 1646.49 | 0.00 | 0.00 | 0.00 |
February | 841.69 | 298.73 | 542.95 | 547.46 | 1448.01 | 0.00 | 0.00 | 0.00 |
March | 1256.70 | 454.93 | 801.76 | 1034.33 | 1209.11 | 0.00 | 0.00 | 0.00 |
April | 1948.09 | 809.46 | 1138.63 | 1942.03 | 991.47 | 0.00 | 0.00 | 0.00 |
May | 2072.94 | 720.72 | 1352.23 | 2171.19 | 842.62 | 0.00 | 0.00 | 0.00 |
June | 2482.59 | 1080.19 | 1402.39 | 2787.96 | 675.22 | 0.00 | 0.00 | 0.00 |
July | 2311.86 | 1037.70 | 1274.17 | 2720.69 | 595.96 | 0.00 | 0.00 | 0.00 |
August | 2272.24 | 1136.70 | 1135.53 | 2770.03 | 580.94 | 0.00 | 0.00 | 0.00 |
September | 1679.99 | 774.82 | 905.16 | 1830.61 | 803.91 | 0.00 | 0.00 | 0.00 |
October | 1095.01 | 465.28 | 629.74 | 996.10 | 1054.32 | 0.00 | 0.00 | 0.00 |
November | 536.71 | 151.52 | 385.19 | 288.92 | 1325.07 | 0.00 | 0.00 | 0.00 |
December | 440.23 | 141.72 | 298.50 | 208.12 | 1655.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1452.40 | 600.32 | 852.08 | 1459.70 | 1067.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 440.23 | 116.30 | 298.50 | 163.29 | 580.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2482.59 | 1136.70 | 1402.39 | 2787.96 | 1655.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1891.94 | 1123.44 | 768.50 | 1652.09 | 2379.42 | 0.00 | 0.00 | 0.00 |
February | 2909.51 | 1801.03 | 1108.48 | 2905.57 | 2179.32 | 0.00 | 0.00 | 0.00 |
March | 3129.79 | 1669.09 | 1460.71 | 3268.45 | 1914.60 | 0.00 | 0.00 | 0.00 |
April | 3304.47 | 1434.78 | 1869.69 | 3652.83 | 1643.75 | 0.00 | 0.00 | 0.00 |
May | 3021.51 | 900.14 | 2121.37 | 3371.61 | 1370.99 | 0.00 | 0.00 | 0.00 |
June | 2764.39 | 742.20 | 2022.19 | 3145.82 | 1096.84 | 0.00 | 0.00 | 0.00 |
July | 3014.69 | 1104.14 | 1910.55 | 3800.19 | 1001.28 | 0.00 | 0.00 | 0.00 |
August | 3238.90 | 1510.35 | 1728.55 | 4231.55 | 968.80 | 0.00 | 0.00 | 0.00 |
September | 3588.57 | 1981.73 | 1606.84 | 4410.90 | 1314.47 | 0.00 | 0.00 | 0.00 |
October | 3250.64 | 2007.03 | 1243.61 | 3642.74 | 1680.20 | 0.00 | 0.00 | 0.00 |
November | 1921.88 | 1101.40 | 820.48 | 1812.37 | 1994.32 | 0.00 | 0.00 | 0.00 |
December | 2010.84 | 1301.30 | 709.55 | 1945.29 | 2443.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2836.04 | 1387.16 | 1448.88 | 3154.20 | 1663.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1891.94 | 742.20 | 709.55 | 1652.09 | 968.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3588.57 | 2007.03 | 2121.37 | 4410.90 | 2443.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 483.83 | 142.67 | 341.15 | 199.35 | 1712.89 | 0.00 | 0.00 | 0.00 |
February | 867.46 | 326.02 | 541.45 | 593.22 | 1530.53 | 0.00 | 0.00 | 0.00 |
March | 1215.54 | 410.28 | 805.26 | 995.31 | 1290.82 | 0.00 | 0.00 | 0.00 |
April | 1849.31 | 707.06 | 1142.25 | 1825.30 | 1093.54 | 0.00 | 0.00 | 0.00 |
May | 2379.63 | 966.71 | 1412.91 | 2575.85 | 926.60 | 0.00 | 0.00 | 0.00 |
June | 2288.55 | 888.57 | 1399.98 | 2530.74 | 741.14 | 0.00 | 0.00 | 0.00 |
July | 2827.19 | 1486.12 | 1341.07 | 3435.93 | 698.21 | 0.00 | 0.00 | 0.00 |
August | 2338.76 | 1194.24 | 1144.52 | 2889.72 | 673.92 | 0.00 | 0.00 | 0.00 |
September | 1904.57 | 913.85 | 990.71 | 2174.61 | 894.12 | 0.00 | 0.00 | 0.00 |
October | 1084.28 | 441.79 | 642.48 | 992.32 | 1138.10 | 0.00 | 0.00 | 0.00 |
November | 539.96 | 152.29 | 387.67 | 292.81 | 1398.84 | 0.00 | 0.00 | 0.00 |
December | 453.94 | 155.55 | 298.39 | 239.87 | 1750.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1523.39 | 651.23 | 872.16 | 1568.47 | 1152.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 453.94 | 142.67 | 298.39 | 199.35 | 673.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2827.19 | 1486.12 | 1412.91 | 3435.93 | 1750.06 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229383E+09 | 0.00 | 0.229383E+09 | 1653535.25 | 0.174140E+10 |
February | 0.322385E+09 | 0.00 | 0.322385E+09 | 34900084.22 | 0.139122E+10 |
March | 0.525875E+09 | 0.00 | 0.525875E+09 | 0.163226E+09 | 0.125428E+10 |
April | 0.720161E+09 | 2554629.96 | 0.717606E+09 | 0.407210E+09 | 0.951542E+09 |
May | 0.957555E+09 | 28447560.61 | 0.929107E+09 | 0.732232E+09 | 0.752374E+09 |
June | 0.974366E+09 | 64343079.21 | 0.910023E+09 | 0.835711E+09 | 0.560727E+09 |
July | 0.956951E+09 | 75029504.75 | 0.881922E+09 | 0.938279E+09 | 0.518694E+09 |
August | 0.774659E+09 | 20941355.22 | 0.753717E+09 | 0.769626E+09 | 0.510981E+09 |
September | 0.582317E+09 | 171716.39 | 0.582145E+09 | 0.416343E+09 | 0.744789E+09 |
October | 0.412283E+09 | 0.00 | 0.412283E+09 | 0.142538E+09 | 0.109812E+10 |
November | 0.251321E+09 | 0.00 | 0.251321E+09 | 16574075.94 | 0.140589E+10 |
December | 0.194917E+09 | 0.00 | 0.194917E+09 | 299868.02 | 0.179649E+10 |
Annual Sum or Average | 0.690217E+10 | 0.191488E+09 | 0.671068E+10 | 0.445859E+10 | 0.127265E+11 |
Minimum of Months | 0.194917E+09 | 0.00 | 0.194917E+09 | 299868.02 | 0.510981E+09 |
Maximum of Months | 0.974366E+09 | 75029504.75 | 0.929107E+09 | 0.938279E+09 | 0.179649E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229383E+09 | 0.00 | 0.229383E+09 | 1653519.25 | 0.174140E+10 |
February | 0.322385E+09 | 0.00 | 0.322385E+09 | 34899976.00 | 0.139122E+10 |
March | 0.525875E+09 | 0.00 | 0.525875E+09 | 0.163226E+09 | 0.125428E+10 |
April | 0.720160E+09 | 2554626.89 | 0.717606E+09 | 0.407209E+09 | 0.951542E+09 |
May | 0.957554E+09 | 28447526.48 | 0.929107E+09 | 0.732231E+09 | 0.752374E+09 |
June | 0.974366E+09 | 64343002.00 | 0.910023E+09 | 0.835710E+09 | 0.560727E+09 |
July | 0.956950E+09 | 75029414.72 | 0.881921E+09 | 0.938278E+09 | 0.518694E+09 |
August | 0.774658E+09 | 20941330.09 | 0.753717E+09 | 0.769625E+09 | 0.510981E+09 |
September | 0.582316E+09 | 171716.19 | 0.582145E+09 | 0.416342E+09 | 0.744789E+09 |
October | 0.412283E+09 | 0.00 | 0.412283E+09 | 0.142538E+09 | 0.109812E+10 |
November | 0.251320E+09 | 0.00 | 0.251320E+09 | 16574017.95 | 0.140589E+10 |
December | 0.194916E+09 | 0.00 | 0.194916E+09 | 299864.11 | 0.179649E+10 |
Annual Sum or Average | 0.690217E+10 | 0.191488E+09 | 0.671068E+10 | 0.445859E+10 | 0.127265E+11 |
Minimum of Months | 0.194916E+09 | 0.00 | 0.194916E+09 | 299864.11 | 0.510981E+09 |
Maximum of Months | 0.974366E+09 | 75029414.72 | 0.929107E+09 | 0.938278E+09 | 0.179649E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229383E+09 | 0.00 | 0.229383E+09 | 1653535.25 | 0.174140E+10 |
February | 0.322385E+09 | 0.00 | 0.322385E+09 | 34900084.22 | 0.139122E+10 |
March | 0.525875E+09 | 0.00 | 0.525875E+09 | 0.163226E+09 | 0.125428E+10 |
April | 0.720161E+09 | 2554629.96 | 0.717606E+09 | 0.407210E+09 | 0.951542E+09 |
May | 0.957555E+09 | 28447560.61 | 0.929107E+09 | 0.732232E+09 | 0.752374E+09 |
June | 0.974366E+09 | 64343079.21 | 0.910023E+09 | 0.835711E+09 | 0.560727E+09 |
July | 0.956951E+09 | 75029504.75 | 0.881922E+09 | 0.938279E+09 | 0.518694E+09 |
August | 0.774659E+09 | 20941355.22 | 0.753717E+09 | 0.769626E+09 | 0.510981E+09 |
September | 0.582317E+09 | 171716.39 | 0.582145E+09 | 0.416343E+09 | 0.744789E+09 |
October | 0.412283E+09 | 0.00 | 0.412283E+09 | 0.142538E+09 | 0.109812E+10 |
November | 0.251321E+09 | 0.00 | 0.251321E+09 | 16574075.94 | 0.140589E+10 |
December | 0.194917E+09 | 0.00 | 0.194917E+09 | 299868.02 | 0.179649E+10 |
Annual Sum or Average | 0.690217E+10 | 0.191488E+09 | 0.671068E+10 | 0.445859E+10 | 0.127265E+11 |
Minimum of Months | 0.194917E+09 | 0.00 | 0.194917E+09 | 299868.02 | 0.510981E+09 |
Maximum of Months | 0.974366E+09 | 75029504.75 | 0.929107E+09 | 0.938279E+09 | 0.179649E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229383E+09 | 0.00 | 0.229383E+09 | 1653519.25 | 0.174140E+10 |
February | 0.322385E+09 | 0.00 | 0.322385E+09 | 34899976.00 | 0.139122E+10 |
March | 0.525875E+09 | 0.00 | 0.525875E+09 | 0.163226E+09 | 0.125428E+10 |
April | 0.720160E+09 | 2554626.89 | 0.717606E+09 | 0.407209E+09 | 0.951542E+09 |
May | 0.957554E+09 | 28447526.48 | 0.929107E+09 | 0.732231E+09 | 0.752374E+09 |
June | 0.974366E+09 | 64343002.00 | 0.910023E+09 | 0.835710E+09 | 0.560727E+09 |
July | 0.956950E+09 | 75029414.72 | 0.881921E+09 | 0.938278E+09 | 0.518694E+09 |
August | 0.774658E+09 | 20941330.09 | 0.753717E+09 | 0.769625E+09 | 0.510981E+09 |
September | 0.582316E+09 | 171716.19 | 0.582145E+09 | 0.416342E+09 | 0.744789E+09 |
October | 0.412283E+09 | 0.00 | 0.412283E+09 | 0.142538E+09 | 0.109812E+10 |
November | 0.251320E+09 | 0.00 | 0.251320E+09 | 16574017.95 | 0.140589E+10 |
December | 0.194916E+09 | 0.00 | 0.194916E+09 | 299864.11 | 0.179649E+10 |
Annual Sum or Average | 0.690217E+10 | 0.191488E+09 | 0.671068E+10 | 0.445859E+10 | 0.127265E+11 |
Minimum of Months | 0.194916E+09 | 0.00 | 0.194916E+09 | 299864.11 | 0.510981E+09 |
Maximum of Months | 0.974366E+09 | 75029414.72 | 0.929107E+09 | 0.938278E+09 | 0.179649E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.229374E+09 | 0.00 | 0.229374E+09 | 1653468.61 | 0.174133E+10 |
February | 0.322372E+09 | 0.00 | 0.322372E+09 | 34898677.59 | 0.139116E+10 |
March | 0.525854E+09 | 0.00 | 0.525854E+09 | 0.163220E+09 | 0.125423E+10 |
April | 0.720132E+09 | 2554526.99 | 0.717577E+09 | 0.407194E+09 | 0.951503E+09 |
May | 0.957516E+09 | 28446414.05 | 0.929070E+09 | 0.732202E+09 | 0.752343E+09 |
June | 0.974327E+09 | 64340485.90 | 0.909987E+09 | 0.835677E+09 | 0.560704E+09 |
July | 0.956913E+09 | 75026480.73 | 0.881886E+09 | 0.938241E+09 | 0.518674E+09 |
August | 0.774628E+09 | 20940511.19 | 0.753687E+09 | 0.769595E+09 | 0.510960E+09 |
September | 0.582293E+09 | 171709.47 | 0.582122E+09 | 0.416326E+09 | 0.744759E+09 |
October | 0.412267E+09 | 0.00 | 0.412267E+09 | 0.142532E+09 | 0.109807E+10 |
November | 0.251311E+09 | 0.00 | 0.251311E+09 | 16573407.93 | 0.140583E+10 |
December | 0.194909E+09 | 0.00 | 0.194909E+09 | 299855.93 | 0.179642E+10 |
Annual Sum or Average | 0.690189E+10 | 0.191480E+09 | 0.671041E+10 | 0.445841E+10 | 0.127260E+11 |
Minimum of Months | 0.194909E+09 | 0.00 | 0.194909E+09 | 299855.93 | 0.510960E+09 |
Maximum of Months | 0.974327E+09 | 75026480.73 | 0.929070E+09 | 0.938241E+09 | 0.179642E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.409539E+09 | 0.103832E+09 | 0.305707E+09 | 0.119843E+09 | 0.179124E+10 |
February | 0.678742E+09 | 0.240900E+09 | 0.437842E+09 | 0.388632E+09 | 0.139774E+10 |
March | 0.112199E+10 | 0.406170E+09 | 0.715819E+09 | 0.871072E+09 | 0.127167E+10 |
April | 0.168317E+10 | 0.699382E+09 | 0.983788E+09 | 0.164814E+10 | 0.965251E+09 |
May | 0.185074E+10 | 0.643461E+09 | 0.120728E+10 | 0.192584E+10 | 0.821500E+09 |
June | 0.214498E+10 | 0.933294E+09 | 0.121168E+10 | 0.242204E+10 | 0.618913E+09 |
July | 0.206405E+10 | 0.926466E+09 | 0.113759E+10 | 0.244383E+10 | 0.551626E+09 |
August | 0.202868E+10 | 0.101486E+10 | 0.101382E+10 | 0.248849E+10 | 0.532250E+09 |
September | 0.145152E+10 | 0.669455E+09 | 0.782068E+09 | 0.156462E+10 | 0.775077E+09 |
October | 0.977638E+09 | 0.415404E+09 | 0.562234E+09 | 0.841192E+09 | 0.112376E+10 |
November | 0.463726E+09 | 0.130915E+09 | 0.332812E+09 | 0.211337E+09 | 0.142259E+10 |
December | 0.393039E+09 | 0.126531E+09 | 0.266508E+09 | 0.156687E+09 | 0.181183E+10 |
Annual Sum or Average | 0.152678E+11 | 0.631067E+10 | 0.895714E+10 | 0.150817E+11 | 0.130834E+11 |
Minimum of Months | 0.393039E+09 | 0.103832E+09 | 0.266508E+09 | 0.119843E+09 | 0.532250E+09 |
Maximum of Months | 0.214498E+10 | 0.101486E+10 | 0.121168E+10 | 0.248849E+10 | 0.181183E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.409539E+09 | 0.103832E+09 | 0.305707E+09 | 0.119843E+09 | 0.179124E+10 |
February | 0.678742E+09 | 0.240900E+09 | 0.437842E+09 | 0.388632E+09 | 0.139774E+10 |
March | 0.112199E+10 | 0.406170E+09 | 0.715819E+09 | 0.871072E+09 | 0.127167E+10 |
April | 0.168317E+10 | 0.699382E+09 | 0.983788E+09 | 0.164814E+10 | 0.965251E+09 |
May | 0.185074E+10 | 0.643461E+09 | 0.120728E+10 | 0.192584E+10 | 0.821500E+09 |
June | 0.214498E+10 | 0.933294E+09 | 0.121168E+10 | 0.242204E+10 | 0.618913E+09 |
July | 0.206405E+10 | 0.926466E+09 | 0.113759E+10 | 0.244383E+10 | 0.551626E+09 |
August | 0.202868E+10 | 0.101486E+10 | 0.101382E+10 | 0.248849E+10 | 0.532250E+09 |
September | 0.145152E+10 | 0.669455E+09 | 0.782068E+09 | 0.156462E+10 | 0.775077E+09 |
October | 0.977638E+09 | 0.415404E+09 | 0.562234E+09 | 0.841192E+09 | 0.112376E+10 |
November | 0.463726E+09 | 0.130915E+09 | 0.332812E+09 | 0.211337E+09 | 0.142259E+10 |
December | 0.393039E+09 | 0.126531E+09 | 0.266508E+09 | 0.156687E+09 | 0.181183E+10 |
Annual Sum or Average | 0.152678E+11 | 0.631067E+10 | 0.895714E+10 | 0.150817E+11 | 0.130834E+11 |
Minimum of Months | 0.393039E+09 | 0.103832E+09 | 0.266508E+09 | 0.119843E+09 | 0.532250E+09 |
Maximum of Months | 0.214498E+10 | 0.101486E+10 | 0.121168E+10 | 0.248849E+10 | 0.181183E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.409532E+09 | 0.103830E+09 | 0.305702E+09 | 0.119841E+09 | 0.179121E+10 |
February | 0.678730E+09 | 0.240895E+09 | 0.437834E+09 | 0.388625E+09 | 0.139771E+10 |
March | 0.112197E+10 | 0.406162E+09 | 0.715806E+09 | 0.871056E+09 | 0.127164E+10 |
April | 0.168314E+10 | 0.699369E+09 | 0.983770E+09 | 0.164811E+10 | 0.965233E+09 |
May | 0.185071E+10 | 0.643450E+09 | 0.120726E+10 | 0.192580E+10 | 0.821485E+09 |
June | 0.214494E+10 | 0.933277E+09 | 0.121166E+10 | 0.242199E+10 | 0.618902E+09 |
July | 0.206401E+10 | 0.926449E+09 | 0.113757E+10 | 0.244379E+10 | 0.551616E+09 |
August | 0.202864E+10 | 0.101484E+10 | 0.101380E+10 | 0.248845E+10 | 0.532240E+09 |
September | 0.145150E+10 | 0.669443E+09 | 0.782054E+09 | 0.156459E+10 | 0.775063E+09 |
October | 0.977620E+09 | 0.415397E+09 | 0.562223E+09 | 0.841177E+09 | 0.112374E+10 |
November | 0.463718E+09 | 0.130912E+09 | 0.332806E+09 | 0.211333E+09 | 0.142257E+10 |
December | 0.393031E+09 | 0.126528E+09 | 0.266503E+09 | 0.156684E+09 | 0.181179E+10 |
Annual Sum or Average | 0.152675E+11 | 0.631055E+10 | 0.895698E+10 | 0.150814E+11 | 0.130832E+11 |
Minimum of Months | 0.393031E+09 | 0.103830E+09 | 0.266503E+09 | 0.119841E+09 | 0.532240E+09 |
Maximum of Months | 0.214494E+10 | 0.101484E+10 | 0.121166E+10 | 0.248845E+10 | 0.181179E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101349E+10 | 0.601813E+09 | 0.411674E+09 | 0.854136E+09 | 0.147129E+10 |
February | 0.140776E+10 | 0.871420E+09 | 0.536336E+09 | 0.137355E+10 | 0.119980E+10 |
March | 0.167659E+10 | 0.894106E+09 | 0.782482E+09 | 0.173132E+10 | 0.116714E+10 |
April | 0.171306E+10 | 0.743800E+09 | 0.969257E+09 | 0.188144E+10 | 0.947683E+09 |
May | 0.161858E+10 | 0.482192E+09 | 0.113639E+10 | 0.180709E+10 | 0.791602E+09 |
June | 0.143308E+10 | 0.384763E+09 | 0.104831E+10 | 0.163555E+10 | 0.609615E+09 |
July | 0.161493E+10 | 0.591472E+09 | 0.102345E+10 | 0.204571E+10 | 0.565850E+09 |
August | 0.173504E+10 | 0.809076E+09 | 0.925960E+09 | 0.227561E+10 | 0.546389E+09 |
September | 0.186034E+10 | 0.102734E+10 | 0.832997E+09 | 0.228486E+10 | 0.738236E+09 |
October | 0.174132E+10 | 0.107514E+10 | 0.666184E+09 | 0.193625E+10 | 0.102206E+10 |
November | 0.996317E+09 | 0.570974E+09 | 0.425343E+09 | 0.904442E+09 | 0.121926E+10 |
December | 0.107718E+10 | 0.697086E+09 | 0.380094E+09 | 0.100883E+10 | 0.153702E+10 |
Annual Sum or Average | 0.178877E+11 | 0.874918E+10 | 0.913849E+10 | 0.197388E+11 | 0.118159E+11 |
Minimum of Months | 0.996317E+09 | 0.384763E+09 | 0.380094E+09 | 0.854136E+09 | 0.546389E+09 |
Maximum of Months | 0.186034E+10 | 0.107514E+10 | 0.113639E+10 | 0.228486E+10 | 0.153702E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101349E+10 | 0.601812E+09 | 0.411673E+09 | 0.854134E+09 | 0.147129E+10 |
February | 0.140775E+10 | 0.871419E+09 | 0.536335E+09 | 0.137355E+10 | 0.119980E+10 |
March | 0.167659E+10 | 0.894105E+09 | 0.782481E+09 | 0.173132E+10 | 0.116714E+10 |
April | 0.171306E+10 | 0.743799E+09 | 0.969256E+09 | 0.188144E+10 | 0.947683E+09 |
May | 0.161858E+10 | 0.482192E+09 | 0.113639E+10 | 0.180709E+10 | 0.791602E+09 |
June | 0.143308E+10 | 0.384763E+09 | 0.104831E+10 | 0.163554E+10 | 0.609615E+09 |
July | 0.161493E+10 | 0.591472E+09 | 0.102345E+10 | 0.204570E+10 | 0.565850E+09 |
August | 0.173503E+10 | 0.809075E+09 | 0.925959E+09 | 0.227561E+10 | 0.546389E+09 |
September | 0.186034E+10 | 0.102734E+10 | 0.832997E+09 | 0.228486E+10 | 0.738236E+09 |
October | 0.174132E+10 | 0.107514E+10 | 0.666184E+09 | 0.193625E+10 | 0.102206E+10 |
November | 0.996316E+09 | 0.570973E+09 | 0.425343E+09 | 0.904441E+09 | 0.121926E+10 |
December | 0.107718E+10 | 0.697085E+09 | 0.380094E+09 | 0.100883E+10 | 0.153702E+10 |
Annual Sum or Average | 0.178876E+11 | 0.874917E+10 | 0.913848E+10 | 0.197388E+11 | 0.118159E+11 |
Minimum of Months | 0.996316E+09 | 0.384763E+09 | 0.380094E+09 | 0.854134E+09 | 0.546389E+09 |
Maximum of Months | 0.186034E+10 | 0.107514E+10 | 0.113639E+10 | 0.228486E+10 | 0.153702E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101349E+10 | 0.601813E+09 | 0.411674E+09 | 0.854136E+09 | 0.147129E+10 |
February | 0.140776E+10 | 0.871420E+09 | 0.536336E+09 | 0.137355E+10 | 0.119980E+10 |
March | 0.167659E+10 | 0.894106E+09 | 0.782482E+09 | 0.173132E+10 | 0.116714E+10 |
April | 0.171306E+10 | 0.743800E+09 | 0.969257E+09 | 0.188144E+10 | 0.947683E+09 |
May | 0.161858E+10 | 0.482192E+09 | 0.113639E+10 | 0.180709E+10 | 0.791602E+09 |
June | 0.143308E+10 | 0.384763E+09 | 0.104831E+10 | 0.163555E+10 | 0.609615E+09 |
July | 0.161493E+10 | 0.591472E+09 | 0.102345E+10 | 0.204571E+10 | 0.565850E+09 |
August | 0.173504E+10 | 0.809076E+09 | 0.925960E+09 | 0.227561E+10 | 0.546389E+09 |
September | 0.186034E+10 | 0.102734E+10 | 0.832997E+09 | 0.228486E+10 | 0.738236E+09 |
October | 0.174132E+10 | 0.107514E+10 | 0.666184E+09 | 0.193625E+10 | 0.102206E+10 |
November | 0.996317E+09 | 0.570974E+09 | 0.425343E+09 | 0.904442E+09 | 0.121926E+10 |
December | 0.107718E+10 | 0.697086E+09 | 0.380094E+09 | 0.100883E+10 | 0.153702E+10 |
Annual Sum or Average | 0.178877E+11 | 0.874918E+10 | 0.913849E+10 | 0.197388E+11 | 0.118159E+11 |
Minimum of Months | 0.996317E+09 | 0.384763E+09 | 0.380094E+09 | 0.854136E+09 | 0.546389E+09 |
Maximum of Months | 0.186034E+10 | 0.107514E+10 | 0.113639E+10 | 0.228486E+10 | 0.153702E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101349E+10 | 0.601812E+09 | 0.411673E+09 | 0.854134E+09 | 0.147129E+10 |
February | 0.140775E+10 | 0.871419E+09 | 0.536335E+09 | 0.137355E+10 | 0.119980E+10 |
March | 0.167659E+10 | 0.894105E+09 | 0.782481E+09 | 0.173132E+10 | 0.116714E+10 |
April | 0.171306E+10 | 0.743799E+09 | 0.969256E+09 | 0.188144E+10 | 0.947683E+09 |
May | 0.161858E+10 | 0.482192E+09 | 0.113639E+10 | 0.180709E+10 | 0.791602E+09 |
June | 0.143308E+10 | 0.384763E+09 | 0.104831E+10 | 0.163554E+10 | 0.609615E+09 |
July | 0.161493E+10 | 0.591472E+09 | 0.102345E+10 | 0.204570E+10 | 0.565850E+09 |
August | 0.173503E+10 | 0.809075E+09 | 0.925959E+09 | 0.227561E+10 | 0.546389E+09 |
September | 0.186034E+10 | 0.102734E+10 | 0.832997E+09 | 0.228486E+10 | 0.738236E+09 |
October | 0.174132E+10 | 0.107514E+10 | 0.666184E+09 | 0.193625E+10 | 0.102206E+10 |
November | 0.996316E+09 | 0.570973E+09 | 0.425343E+09 | 0.904441E+09 | 0.121926E+10 |
December | 0.107718E+10 | 0.697085E+09 | 0.380094E+09 | 0.100883E+10 | 0.153702E+10 |
Annual Sum or Average | 0.178876E+11 | 0.874917E+10 | 0.913848E+10 | 0.197388E+11 | 0.118159E+11 |
Minimum of Months | 0.996316E+09 | 0.384763E+09 | 0.380094E+09 | 0.854134E+09 | 0.546389E+09 |
Maximum of Months | 0.186034E+10 | 0.107514E+10 | 0.113639E+10 | 0.228486E+10 | 0.153702E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101345E+10 | 0.601789E+09 | 0.411657E+09 | 0.854101E+09 | 0.147123E+10 |
February | 0.140770E+10 | 0.871385E+09 | 0.536314E+09 | 0.137350E+10 | 0.119975E+10 |
March | 0.167652E+10 | 0.894070E+09 | 0.782451E+09 | 0.173125E+10 | 0.116709E+10 |
April | 0.171299E+10 | 0.743770E+09 | 0.969218E+09 | 0.188136E+10 | 0.947645E+09 |
May | 0.161852E+10 | 0.482173E+09 | 0.113635E+10 | 0.180702E+10 | 0.791570E+09 |
June | 0.143302E+10 | 0.384748E+09 | 0.104827E+10 | 0.163548E+10 | 0.609590E+09 |
July | 0.161486E+10 | 0.591449E+09 | 0.102341E+10 | 0.204562E+10 | 0.565827E+09 |
August | 0.173497E+10 | 0.809043E+09 | 0.925922E+09 | 0.227552E+10 | 0.546367E+09 |
September | 0.186026E+10 | 0.102730E+10 | 0.832964E+09 | 0.228477E+10 | 0.738206E+09 |
October | 0.174125E+10 | 0.107509E+10 | 0.666157E+09 | 0.193618E+10 | 0.102202E+10 |
November | 0.996277E+09 | 0.570951E+09 | 0.425326E+09 | 0.904406E+09 | 0.121921E+10 |
December | 0.107714E+10 | 0.697058E+09 | 0.380079E+09 | 0.100879E+10 | 0.153695E+10 |
Annual Sum or Average | 0.178869E+11 | 0.874883E+10 | 0.913812E+10 | 0.197380E+11 | 0.118155E+11 |
Minimum of Months | 0.996277E+09 | 0.384748E+09 | 0.380079E+09 | 0.854101E+09 | 0.546367E+09 |
Maximum of Months | 0.186026E+10 | 0.107509E+10 | 0.113635E+10 | 0.228477E+10 | 0.153695E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.431964E+09 | 0.127378E+09 | 0.304586E+09 | 0.152972E+09 | 0.191423E+10 |
February | 0.699528E+09 | 0.262902E+09 | 0.436626E+09 | 0.423550E+09 | 0.156827E+10 |
March | 0.108524E+10 | 0.366298E+09 | 0.718943E+09 | 0.810729E+09 | 0.148777E+10 |
April | 0.159782E+10 | 0.610907E+09 | 0.986910E+09 | 0.149410E+10 | 0.118904E+10 |
May | 0.212455E+10 | 0.863091E+09 | 0.126146E+10 | 0.227463E+10 | 0.932578E+09 |
June | 0.197733E+10 | 0.767730E+09 | 0.120960E+10 | 0.215854E+10 | 0.738675E+09 |
July | 0.252414E+10 | 0.132682E+10 | 0.119732E+10 | 0.304694E+10 | 0.712179E+09 |
August | 0.208807E+10 | 0.106623E+10 | 0.102184E+10 | 0.254284E+10 | 0.708360E+09 |
September | 0.164556E+10 | 0.789576E+09 | 0.855985E+09 | 0.184743E+10 | 0.892035E+09 |
October | 0.968051E+09 | 0.394434E+09 | 0.573616E+09 | 0.820040E+09 | 0.130015E+10 |
November | 0.466532E+09 | 0.131581E+09 | 0.334951E+09 | 0.204932E+09 | 0.164723E+10 |
December | 0.405284E+09 | 0.138881E+09 | 0.266404E+09 | 0.180101E+09 | 0.213144E+10 |
Annual Sum or Average | 0.160141E+11 | 0.684582E+10 | 0.916824E+10 | 0.159568E+11 | 0.152219E+11 |
Minimum of Months | 0.405284E+09 | 0.127378E+09 | 0.266404E+09 | 0.152972E+09 | 0.708360E+09 |
Maximum of Months | 0.252414E+10 | 0.132682E+10 | 0.126146E+10 | 0.304694E+10 | 0.213144E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.431964E+09 | 0.127378E+09 | 0.304586E+09 | 0.152972E+09 | 0.191423E+10 |
February | 0.699528E+09 | 0.262902E+09 | 0.436626E+09 | 0.423550E+09 | 0.156827E+10 |
March | 0.108524E+10 | 0.366298E+09 | 0.718943E+09 | 0.810729E+09 | 0.148777E+10 |
April | 0.159782E+10 | 0.610907E+09 | 0.986910E+09 | 0.149410E+10 | 0.118904E+10 |
May | 0.212455E+10 | 0.863091E+09 | 0.126146E+10 | 0.227463E+10 | 0.932578E+09 |
June | 0.197733E+10 | 0.767730E+09 | 0.120960E+10 | 0.215854E+10 | 0.738675E+09 |
July | 0.252414E+10 | 0.132682E+10 | 0.119732E+10 | 0.304694E+10 | 0.712179E+09 |
August | 0.208807E+10 | 0.106623E+10 | 0.102184E+10 | 0.254284E+10 | 0.708360E+09 |
September | 0.164556E+10 | 0.789576E+09 | 0.855985E+09 | 0.184743E+10 | 0.892035E+09 |
October | 0.968051E+09 | 0.394434E+09 | 0.573616E+09 | 0.820040E+09 | 0.130015E+10 |
November | 0.466532E+09 | 0.131581E+09 | 0.334951E+09 | 0.204932E+09 | 0.164723E+10 |
December | 0.405284E+09 | 0.138881E+09 | 0.266404E+09 | 0.180101E+09 | 0.213144E+10 |
Annual Sum or Average | 0.160141E+11 | 0.684582E+10 | 0.916824E+10 | 0.159568E+11 | 0.152219E+11 |
Minimum of Months | 0.405284E+09 | 0.127378E+09 | 0.266404E+09 | 0.152972E+09 | 0.708360E+09 |
Maximum of Months | 0.252414E+10 | 0.132682E+10 | 0.126146E+10 | 0.304694E+10 | 0.213144E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.431956E+09 | 0.127376E+09 | 0.304580E+09 | 0.152969E+09 | 0.191419E+10 |
February | 0.699515E+09 | 0.262898E+09 | 0.436618E+09 | 0.423543E+09 | 0.156824E+10 |
March | 0.108522E+10 | 0.366291E+09 | 0.718930E+09 | 0.810714E+09 | 0.148774E+10 |
April | 0.159779E+10 | 0.610896E+09 | 0.986892E+09 | 0.149408E+10 | 0.118902E+10 |
May | 0.212451E+10 | 0.863075E+09 | 0.126144E+10 | 0.227459E+10 | 0.932561E+09 |
June | 0.197729E+10 | 0.767716E+09 | 0.120957E+10 | 0.215850E+10 | 0.738661E+09 |
July | 0.252409E+10 | 0.132679E+10 | 0.119730E+10 | 0.304688E+10 | 0.712166E+09 |
August | 0.208803E+10 | 0.106621E+10 | 0.102182E+10 | 0.254279E+10 | 0.708347E+09 |
September | 0.164553E+10 | 0.789562E+09 | 0.855969E+09 | 0.184740E+10 | 0.892019E+09 |
October | 0.968033E+09 | 0.394427E+09 | 0.573606E+09 | 0.820025E+09 | 0.130012E+10 |
November | 0.466524E+09 | 0.131579E+09 | 0.334945E+09 | 0.204929E+09 | 0.164720E+10 |
December | 0.405277E+09 | 0.138878E+09 | 0.266399E+09 | 0.180098E+09 | 0.213140E+10 |
Annual Sum or Average | 0.160138E+11 | 0.684570E+10 | 0.916807E+10 | 0.159565E+11 | 0.152217E+11 |
Minimum of Months | 0.405277E+09 | 0.127376E+09 | 0.266399E+09 | 0.152969E+09 | 0.708347E+09 |
Maximum of Months | 0.252409E+10 | 0.132679E+10 | 0.126144E+10 | 0.304688E+10 | 0.213140E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.114690E+10 | 0.00 | 0.114690E+10 | 27079009.30 | 0.751340E+10 |
February | 0.161191E+10 | 0.00 | 0.161191E+10 | 0.268107E+09 | 0.604652E+10 |
March | 0.262934E+10 | 0.00 | 0.262934E+10 | 0.995576E+09 | 0.551928E+10 |
April | 0.360076E+10 | 12772995.34 | 0.358799E+10 | 0.222126E+10 | 0.425433E+10 |
May | 0.478772E+10 | 0.142236E+09 | 0.464548E+10 | 0.375842E+10 | 0.354100E+10 |
June | 0.487177E+10 | 0.321712E+09 | 0.455006E+10 | 0.425577E+10 | 0.264032E+10 |
July | 0.478470E+10 | 0.375143E+09 | 0.440955E+10 | 0.478387E+10 | 0.244192E+10 |
August | 0.387325E+10 | 0.104706E+09 | 0.376854E+10 | 0.394818E+10 | 0.239449E+10 |
September | 0.291155E+10 | 858571.59 | 0.291069E+10 | 0.216485E+10 | 0.345283E+10 |
October | 0.206139E+10 | 0.00 | 0.206139E+10 | 0.861246E+09 | 0.482928E+10 |
November | 0.125659E+10 | 0.00 | 0.125659E+10 | 0.142725E+09 | 0.594932E+10 |
December | 0.974571E+09 | 0.00 | 0.974571E+09 | 11581046.21 | 0.758261E+10 |
Annual Sum or Average | 0.345104E+11 | 0.957428E+09 | 0.335530E+11 | 0.234387E+11 | 0.561653E+11 |
Minimum of Months | 0.974571E+09 | 0.00 | 0.974571E+09 | 11581046.21 | 0.239449E+10 |
Maximum of Months | 0.487177E+10 | 0.375143E+09 | 0.464548E+10 | 0.478387E+10 | 0.758261E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122860E+10 | 0.311492E+09 | 0.917113E+09 | 0.403505E+09 | 0.474818E+10 |
February | 0.203621E+10 | 0.722692E+09 | 0.131351E+10 | 0.125246E+10 | 0.379536E+10 |
March | 0.336593E+10 | 0.121850E+10 | 0.214744E+10 | 0.269126E+10 | 0.349000E+10 |
April | 0.504946E+10 | 0.209812E+10 | 0.295133E+10 | 0.497832E+10 | 0.271493E+10 |
May | 0.555217E+10 | 0.193036E+10 | 0.362181E+10 | 0.578737E+10 | 0.234876E+10 |
June | 0.643486E+10 | 0.279985E+10 | 0.363501E+10 | 0.723556E+10 | 0.179104E+10 |
July | 0.619209E+10 | 0.277937E+10 | 0.341273E+10 | 0.730490E+10 | 0.161712E+10 |
August | 0.608596E+10 | 0.304455E+10 | 0.304142E+10 | 0.742934E+10 | 0.158753E+10 |
September | 0.435453E+10 | 0.200835E+10 | 0.234618E+10 | 0.471210E+10 | 0.219329E+10 |
October | 0.293288E+10 | 0.124620E+10 | 0.168668E+10 | 0.259132E+10 | 0.306594E+10 |
November | 0.139117E+10 | 0.392740E+09 | 0.998425E+09 | 0.695553E+09 | 0.378041E+10 |
December | 0.117910E+10 | 0.379588E+09 | 0.799515E+09 | 0.516785E+09 | 0.483084E+10 |
Annual Sum or Average | 0.458030E+11 | 0.189318E+11 | 0.268712E+11 | 0.455985E+11 | 0.359634E+11 |
Minimum of Months | 0.117910E+10 | 0.311492E+09 | 0.799515E+09 | 0.403505E+09 | 0.158753E+10 |
Maximum of Months | 0.643486E+10 | 0.304455E+10 | 0.363501E+10 | 0.742934E+10 | 0.483084E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.506737E+10 | 0.300903E+10 | 0.205834E+10 | 0.431535E+10 | 0.689895E+10 |
February | 0.703869E+10 | 0.435705E+10 | 0.268165E+10 | 0.689662E+10 | 0.571393E+10 |
March | 0.838284E+10 | 0.447048E+10 | 0.391236E+10 | 0.865739E+10 | 0.553345E+10 |
April | 0.856518E+10 | 0.371896E+10 | 0.484623E+10 | 0.939895E+10 | 0.450998E+10 |
May | 0.809282E+10 | 0.241093E+10 | 0.568189E+10 | 0.899382E+10 | 0.384180E+10 |
June | 0.716530E+10 | 0.192379E+10 | 0.524151E+10 | 0.815680E+10 | 0.293159E+10 |
July | 0.807454E+10 | 0.295733E+10 | 0.511721E+10 | 0.102016E+11 | 0.273528E+10 |
August | 0.867507E+10 | 0.404533E+10 | 0.462974E+10 | 0.113477E+11 | 0.266462E+10 |
September | 0.930157E+10 | 0.513664E+10 | 0.416494E+10 | 0.113865E+11 | 0.359293E+10 |
October | 0.870651E+10 | 0.537562E+10 | 0.333088E+10 | 0.965530E+10 | 0.487742E+10 |
November | 0.498153E+10 | 0.285483E+10 | 0.212669E+10 | 0.457885E+10 | 0.567848E+10 |
December | 0.538584E+10 | 0.348539E+10 | 0.190045E+10 | 0.510357E+10 | 0.713042E+10 |
Annual Sum or Average | 0.894373E+11 | 0.437454E+11 | 0.456919E+11 | 0.986924E+11 | 0.561088E+11 |
Minimum of Months | 0.498153E+10 | 0.192379E+10 | 0.190045E+10 | 0.431535E+10 | 0.266462E+10 |
Maximum of Months | 0.930157E+10 | 0.537562E+10 | 0.568189E+10 | 0.113865E+11 | 0.713042E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129588E+10 | 0.382131E+09 | 0.913748E+09 | 0.510277E+09 | 0.492609E+10 |
February | 0.209856E+10 | 0.788699E+09 | 0.130986E+10 | 0.139210E+10 | 0.396329E+10 |
March | 0.325569E+10 | 0.109888E+10 | 0.215681E+10 | 0.261389E+10 | 0.369428E+10 |
April | 0.479340E+10 | 0.183270E+10 | 0.296070E+10 | 0.468878E+10 | 0.298416E+10 |
May | 0.637359E+10 | 0.258925E+10 | 0.378435E+10 | 0.688178E+10 | 0.258297E+10 |
June | 0.593192E+10 | 0.230317E+10 | 0.362875E+10 | 0.656558E+10 | 0.197589E+10 |
July | 0.757234E+10 | 0.398041E+10 | 0.359193E+10 | 0.922756E+10 | 0.190432E+10 |
August | 0.626414E+10 | 0.319865E+10 | 0.306549E+10 | 0.775098E+10 | 0.184906E+10 |
September | 0.493663E+10 | 0.236870E+10 | 0.256793E+10 | 0.560908E+10 | 0.243189E+10 |
October | 0.290412E+10 | 0.118329E+10 | 0.172083E+10 | 0.260205E+10 | 0.327799E+10 |
November | 0.139958E+10 | 0.394740E+09 | 0.100484E+10 | 0.722924E+09 | 0.392391E+10 |
December | 0.121584E+10 | 0.416638E+09 | 0.799203E+09 | 0.619752E+09 | 0.503564E+10 |
Annual Sum or Average | 0.480417E+11 | 0.205373E+11 | 0.275044E+11 | 0.491848E+11 | 0.385495E+11 |
Minimum of Months | 0.121584E+10 | 0.382131E+09 | 0.799203E+09 | 0.510277E+09 | 0.184906E+10 |
Maximum of Months | 0.757234E+10 | 0.398041E+10 | 0.378435E+10 | 0.922756E+10 | 0.503564E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.114690E+10 | 0.00 | 0.114690E+10 | 46515425.98 | 0.695693E+10 |
February | 0.161191E+10 | 0.00 | 0.161191E+10 | 0.328899E+09 | 0.554826E+10 |
March | 0.262934E+10 | 0.00 | 0.262934E+10 | 0.111610E+10 | 0.505779E+10 |
April | 0.360076E+10 | 12772995.34 | 0.358799E+10 | 0.233143E+10 | 0.397467E+10 |
May | 0.478772E+10 | 0.142236E+09 | 0.464548E+10 | 0.383454E+10 | 0.336803E+10 |
June | 0.487177E+10 | 0.321712E+09 | 0.455006E+10 | 0.427500E+10 | 0.255927E+10 |
July | 0.478470E+10 | 0.375143E+09 | 0.440955E+10 | 0.477466E+10 | 0.238880E+10 |
August | 0.387325E+10 | 0.104706E+09 | 0.376854E+10 | 0.395594E+10 | 0.232476E+10 |
September | 0.291155E+10 | 858571.59 | 0.291069E+10 | 0.223700E+10 | 0.323491E+10 |
October | 0.206139E+10 | 0.00 | 0.206139E+10 | 0.984284E+09 | 0.437222E+10 |
November | 0.125659E+10 | 0.00 | 0.125659E+10 | 0.193670E+09 | 0.534142E+10 |
December | 0.974571E+09 | 0.00 | 0.974571E+09 | 28659935.24 | 0.692168E+10 |
Annual Sum or Average | 0.345104E+11 | 0.957428E+09 | 0.335530E+11 | 0.241067E+11 | 0.520487E+11 |
Minimum of Months | 0.974571E+09 | 0.00 | 0.974571E+09 | 28659935.24 | 0.232476E+10 |
Maximum of Months | 0.487177E+10 | 0.375143E+09 | 0.464548E+10 | 0.477466E+10 | 0.695693E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122860E+10 | 0.311492E+09 | 0.917113E+09 | 0.437353E+09 | 0.440996E+10 |
February | 0.203621E+10 | 0.722692E+09 | 0.131351E+10 | 0.132443E+10 | 0.350303E+10 |
March | 0.336593E+10 | 0.121850E+10 | 0.214744E+10 | 0.277034E+10 | 0.323848E+10 |
April | 0.504946E+10 | 0.209812E+10 | 0.295133E+10 | 0.503374E+10 | 0.256990E+10 |
May | 0.555217E+10 | 0.193036E+10 | 0.362181E+10 | 0.581531E+10 | 0.225687E+10 |
June | 0.643486E+10 | 0.279985E+10 | 0.363501E+10 | 0.722640E+10 | 0.175017E+10 |
July | 0.619209E+10 | 0.277937E+10 | 0.341273E+10 | 0.728710E+10 | 0.159621E+10 |
August | 0.608596E+10 | 0.304455E+10 | 0.304142E+10 | 0.741925E+10 | 0.155598E+10 |
September | 0.435453E+10 | 0.200835E+10 | 0.234618E+10 | 0.474494E+10 | 0.208374E+10 |
October | 0.293288E+10 | 0.124620E+10 | 0.168668E+10 | 0.266796E+10 | 0.282389E+10 |
November | 0.139117E+10 | 0.392740E+09 | 0.998425E+09 | 0.748893E+09 | 0.343458E+10 |
December | 0.117910E+10 | 0.379588E+09 | 0.799515E+09 | 0.557427E+09 | 0.443526E+10 |
Annual Sum or Average | 0.458030E+11 | 0.189318E+11 | 0.268712E+11 | 0.460331E+11 | 0.336581E+11 |
Minimum of Months | 0.117910E+10 | 0.311492E+09 | 0.799515E+09 | 0.437353E+09 | 0.155598E+10 |
Maximum of Months | 0.643486E+10 | 0.304455E+10 | 0.363501E+10 | 0.741925E+10 | 0.443526E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.506737E+10 | 0.300903E+10 | 0.205834E+10 | 0.442495E+10 | 0.637304E+10 |
February | 0.703869E+10 | 0.435705E+10 | 0.268165E+10 | 0.702916E+10 | 0.527222E+10 |
March | 0.838284E+10 | 0.447048E+10 | 0.391236E+10 | 0.875422E+10 | 0.512805E+10 |
April | 0.856518E+10 | 0.371896E+10 | 0.484623E+10 | 0.946815E+10 | 0.426061E+10 |
May | 0.809282E+10 | 0.241093E+10 | 0.568189E+10 | 0.903051E+10 | 0.367205E+10 |
June | 0.716530E+10 | 0.192379E+10 | 0.524151E+10 | 0.815397E+10 | 0.284300E+10 |
July | 0.807454E+10 | 0.295733E+10 | 0.511721E+10 | 0.101784E+11 | 0.268183E+10 |
August | 0.867507E+10 | 0.404533E+10 | 0.462974E+10 | 0.113338E+11 | 0.259484E+10 |
September | 0.930157E+10 | 0.513664E+10 | 0.416494E+10 | 0.114331E+11 | 0.340712E+10 |
October | 0.870651E+10 | 0.537562E+10 | 0.333088E+10 | 0.975671E+10 | 0.450024E+10 |
November | 0.498153E+10 | 0.285483E+10 | 0.212669E+10 | 0.469766E+10 | 0.516928E+10 |
December | 0.538584E+10 | 0.348539E+10 | 0.190045E+10 | 0.521026E+10 | 0.654394E+10 |
Annual Sum or Average | 0.894373E+11 | 0.437454E+11 | 0.456919E+11 | 0.994709E+11 | 0.524462E+11 |
Minimum of Months | 0.498153E+10 | 0.192379E+10 | 0.190045E+10 | 0.442495E+10 | 0.259484E+10 |
Maximum of Months | 0.930157E+10 | 0.537562E+10 | 0.568189E+10 | 0.114331E+11 | 0.654394E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129588E+10 | 0.382131E+09 | 0.913748E+09 | 0.533932E+09 | 0.458782E+10 |
February | 0.209856E+10 | 0.788699E+09 | 0.130986E+10 | 0.143511E+10 | 0.370265E+10 |
March | 0.325569E+10 | 0.109888E+10 | 0.215681E+10 | 0.266583E+10 | 0.345733E+10 |
April | 0.479340E+10 | 0.183270E+10 | 0.296070E+10 | 0.473118E+10 | 0.283447E+10 |
May | 0.637359E+10 | 0.258925E+10 | 0.378435E+10 | 0.689916E+10 | 0.248180E+10 |
June | 0.593192E+10 | 0.230317E+10 | 0.362875E+10 | 0.655968E+10 | 0.192102E+10 |
July | 0.757234E+10 | 0.398041E+10 | 0.359193E+10 | 0.920278E+10 | 0.187008E+10 |
August | 0.626414E+10 | 0.319865E+10 | 0.306549E+10 | 0.773982E+10 | 0.180504E+10 |
September | 0.493663E+10 | 0.236870E+10 | 0.256793E+10 | 0.563659E+10 | 0.231756E+10 |
October | 0.290412E+10 | 0.118329E+10 | 0.172083E+10 | 0.265784E+10 | 0.304828E+10 |
November | 0.139958E+10 | 0.394740E+09 | 0.100484E+10 | 0.758972E+09 | 0.362580E+10 |
December | 0.121584E+10 | 0.416638E+09 | 0.799203E+09 | 0.642463E+09 | 0.468736E+10 |
Annual Sum or Average | 0.480417E+11 | 0.205373E+11 | 0.275044E+11 | 0.494634E+11 | 0.363392E+11 |
Minimum of Months | 0.121584E+10 | 0.382131E+09 | 0.799203E+09 | 0.533932E+09 | 0.180504E+10 |
Maximum of Months | 0.757234E+10 | 0.398041E+10 | 0.378435E+10 | 0.920278E+10 | 0.468736E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3.09 | 3250.80 | 428.21 | 0.00 | 428.21 | 0.00 | 0.00 |
February | 72.13 | 2875.35 | 666.30 | 0.00 | 666.30 | 0.00 | 0.00 |
March | 304.71 | 2341.46 | 981.69 | 0.00 | 981.69 | 0.00 | 0.00 |
April | 785.51 | 1835.52 | 1389.19 | 4.93 | 1384.26 | 0.00 | 0.00 |
May | 1366.91 | 1404.51 | 1787.54 | 53.11 | 1734.43 | 0.00 | 0.00 |
June | 1612.08 | 1081.64 | 1879.55 | 124.12 | 1755.43 | 0.00 | 0.00 |
July | 1751.55 | 968.28 | 1786.41 | 140.06 | 1646.35 | 0.00 | 0.00 |
August | 1436.71 | 953.88 | 1446.11 | 39.09 | 1407.02 | 0.00 | 0.00 |
September | 803.12 | 1436.70 | 1123.29 | 0.33 | 1122.96 | 0.00 | 0.00 |
October | 266.09 | 2049.94 | 769.64 | 0.00 | 769.64 | 0.00 | 0.00 |
November | 31.97 | 2711.95 | 484.80 | 0.00 | 484.80 | 0.00 | 0.00 |
December | 0.56 | 3353.64 | 363.86 | 0.00 | 363.86 | 0.00 | 0.00 |
Annual Sum or Average | 706.90 | 2017.76 | 1094.32 | 30.36 | 1063.96 | 0.00 | 0.00 |
Minimum of Months | 0.56 | 953.88 | 363.86 | 0.00 | 363.86 | 0.00 | 0.00 |
Maximum of Months | 1751.55 | 3353.64 | 1879.55 | 140.06 | 1755.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 134.23 | 2006.31 | 458.71 | 116.30 | 342.41 | 0.00 | 0.00 |
February | 481.93 | 1733.29 | 841.69 | 298.73 | 542.96 | 0.00 | 0.00 |
March | 975.66 | 1424.35 | 1256.70 | 454.94 | 801.76 | 0.00 | 0.00 |
April | 1907.56 | 1117.18 | 1948.10 | 809.46 | 1138.64 | 0.00 | 0.00 |
May | 2157.06 | 920.13 | 2072.95 | 720.72 | 1352.23 | 0.00 | 0.00 |
June | 2803.27 | 716.33 | 2482.60 | 1080.19 | 1402.40 | 0.00 | 0.00 |
July | 2737.25 | 617.86 | 2311.87 | 1037.70 | 1274.17 | 0.00 | 0.00 |
August | 2787.27 | 596.15 | 2272.25 | 1136.71 | 1135.54 | 0.00 | 0.00 |
September | 1810.90 | 897.07 | 1679.99 | 774.83 | 905.17 | 0.00 | 0.00 |
October | 942.19 | 1258.68 | 1095.02 | 465.28 | 629.74 | 0.00 | 0.00 |
November | 244.60 | 1646.51 | 536.72 | 151.52 | 385.20 | 0.00 | 0.00 |
December | 175.50 | 2029.36 | 440.23 | 141.72 | 298.51 | 0.00 | 0.00 |
Annual Sum or Average | 1434.71 | 1244.61 | 1452.41 | 600.33 | 852.08 | 0.00 | 0.00 |
Minimum of Months | 134.23 | 596.15 | 440.23 | 116.30 | 298.51 | 0.00 | 0.00 |
Maximum of Months | 2803.27 | 2029.36 | 2482.60 | 1136.71 | 1402.40 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1594.48 | 2746.56 | 1891.95 | 1123.45 | 768.50 | 0.00 | 0.00 |
February | 2838.84 | 2479.72 | 2909.52 | 1801.03 | 1108.49 | 0.00 | 0.00 |
March | 3231.98 | 2178.78 | 3129.81 | 1669.09 | 1460.71 | 0.00 | 0.00 |
April | 3629.29 | 1828.08 | 3304.48 | 1434.79 | 1869.69 | 0.00 | 0.00 |
May | 3373.42 | 1477.74 | 3021.52 | 900.14 | 2121.38 | 0.00 | 0.00 |
June | 3154.96 | 1175.94 | 2764.40 | 742.21 | 2022.19 | 0.00 | 0.00 |
July | 3818.86 | 1056.31 | 3014.70 | 1104.14 | 1910.56 | 0.00 | 0.00 |
August | 4248.04 | 1019.98 | 3238.91 | 1510.36 | 1728.55 | 0.00 | 0.00 |
September | 4407.49 | 1424.05 | 3588.58 | 1981.73 | 1606.85 | 0.00 | 0.00 |
October | 3614.54 | 1907.96 | 3250.65 | 2007.04 | 1243.61 | 0.00 | 0.00 |
November | 1744.67 | 2351.94 | 1921.89 | 1101.41 | 820.49 | 0.00 | 0.00 |
December | 1883.25 | 2869.26 | 2010.85 | 1301.30 | 709.55 | 0.00 | 0.00 |
Annual Sum or Average | 3129.54 | 1873.39 | 2836.05 | 1387.16 | 1448.89 | 0.00 | 0.00 |
Minimum of Months | 1594.48 | 1019.98 | 1891.95 | 742.21 | 709.55 | 0.00 | 0.00 |
Maximum of Months | 4407.49 | 2869.26 | 3588.58 | 2007.04 | 2121.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 171.34 | 2144.06 | 483.83 | 142.67 | 341.16 | 0.00 | 0.00 |
February | 525.23 | 1944.76 | 867.47 | 326.02 | 541.45 | 0.00 | 0.00 |
March | 908.07 | 1666.40 | 1215.54 | 410.28 | 805.26 | 0.00 | 0.00 |
April | 1729.28 | 1376.19 | 1849.31 | 707.06 | 1142.25 | 0.00 | 0.00 |
May | 2547.74 | 1044.55 | 2379.64 | 966.72 | 1412.92 | 0.00 | 0.00 |
June | 2498.29 | 854.94 | 2288.56 | 888.57 | 1399.99 | 0.00 | 0.00 |
July | 3412.77 | 797.69 | 2827.20 | 1486.12 | 1341.08 | 0.00 | 0.00 |
August | 2848.15 | 793.41 | 2338.77 | 1194.24 | 1144.53 | 0.00 | 0.00 |
September | 2138.22 | 1032.44 | 1904.57 | 913.86 | 990.72 | 0.00 | 0.00 |
October | 918.50 | 1456.25 | 1084.28 | 441.79 | 642.49 | 0.00 | 0.00 |
November | 237.19 | 1906.51 | 539.96 | 152.29 | 387.67 | 0.00 | 0.00 |
December | 201.72 | 2387.35 | 453.94 | 155.56 | 298.39 | 0.00 | 0.00 |
Annual Sum or Average | 1517.95 | 1448.05 | 1523.40 | 651.23 | 872.16 | 0.00 | 0.00 |
Minimum of Months | 171.34 | 793.41 | 453.94 | 142.67 | 298.39 | 0.00 | 0.00 |
Maximum of Months | 3412.77 | 2387.35 | 2827.20 | 1486.12 | 1412.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 10.11 | 2805.18 | 428.20 | 0.00 | 428.20 | 0.00 | 0.00 |
February | 110.82 | 2499.39 | 666.30 | 0.00 | 666.30 | 0.00 | 0.00 |
March | 371.71 | 2060.66 | 981.68 | 0.00 | 981.68 | 0.00 | 0.00 |
April | 856.97 | 1641.33 | 1389.18 | 4.93 | 1384.25 | 0.00 | 0.00 |
May | 1403.23 | 1322.06 | 1787.53 | 53.10 | 1734.42 | 0.00 | 0.00 |
June | 1641.88 | 1018.64 | 1879.54 | 124.12 | 1755.42 | 0.00 | 0.00 |
July | 1786.09 | 911.71 | 1786.40 | 140.06 | 1646.34 | 0.00 | 0.00 |
August | 1474.08 | 894.00 | 1446.10 | 39.09 | 1407.01 | 0.00 | 0.00 |
September | 835.20 | 1332.11 | 1123.28 | 0.33 | 1122.95 | 0.00 | 0.00 |
October | 321.55 | 1803.05 | 769.64 | 0.00 | 769.64 | 0.00 | 0.00 |
November | 55.06 | 2295.26 | 484.79 | 0.00 | 484.79 | 0.00 | 0.00 |
December | 4.32 | 2831.02 | 363.86 | 0.00 | 363.86 | 0.00 | 0.00 |
Annual Sum or Average | 743.24 | 1780.99 | 1094.32 | 30.36 | 1063.96 | 0.00 | 0.00 |
Minimum of Months | 4.32 | 894.00 | 363.86 | 0.00 | 363.86 | 0.00 | 0.00 |
Maximum of Months | 1786.09 | 2831.02 | 1879.54 | 140.06 | 1755.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 150.65 | 1772.77 | 458.71 | 116.30 | 342.41 | 0.00 | 0.00 |
February | 517.72 | 1568.85 | 841.69 | 298.73 | 542.95 | 0.00 | 0.00 |
March | 1004.80 | 1303.02 | 1256.70 | 454.93 | 801.76 | 0.00 | 0.00 |
April | 1920.65 | 1047.43 | 1948.09 | 809.46 | 1138.63 | 0.00 | 0.00 |
May | 2160.75 | 876.93 | 2072.94 | 720.72 | 1352.23 | 0.00 | 0.00 |
June | 2791.50 | 690.99 | 2482.59 | 1080.19 | 1402.39 | 0.00 | 0.00 |
July | 2727.34 | 603.76 | 2311.86 | 1037.70 | 1274.17 | 0.00 | 0.00 |
August | 2773.80 | 592.71 | 2272.24 | 1136.70 | 1135.53 | 0.00 | 0.00 |
September | 1817.94 | 846.18 | 1679.99 | 774.82 | 905.16 | 0.00 | 0.00 |
October | 967.49 | 1144.69 | 1095.01 | 465.28 | 629.74 | 0.00 | 0.00 |
November | 268.35 | 1458.49 | 536.71 | 151.52 | 385.19 | 0.00 | 0.00 |
December | 192.95 | 1803.63 | 440.23 | 141.72 | 298.50 | 0.00 | 0.00 |
Annual Sum or Average | 1445.92 | 1140.39 | 1452.40 | 600.32 | 852.08 | 0.00 | 0.00 |
Minimum of Months | 150.65 | 592.71 | 440.23 | 116.30 | 298.50 | 0.00 | 0.00 |
Maximum of Months | 2791.50 | 1803.63 | 2482.59 | 1136.70 | 1402.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1611.17 | 2575.77 | 1891.94 | 1123.44 | 768.50 | 0.00 | 0.00 |
February | 2850.79 | 2361.91 | 2909.51 | 1801.03 | 1108.48 | 0.00 | 0.00 |
March | 3232.30 | 2065.95 | 3129.79 | 1669.09 | 1460.71 | 0.00 | 0.00 |
April | 3626.14 | 1739.96 | 3304.47 | 1434.78 | 1869.69 | 0.00 | 0.00 |
May | 3357.91 | 1434.36 | 3021.51 | 900.14 | 2121.37 | 0.00 | 0.00 |
June | 3146.91 | 1131.02 | 2764.39 | 742.20 | 2022.19 | 0.00 | 0.00 |
July | 3808.82 | 1021.23 | 3014.69 | 1104.14 | 1910.55 | 0.00 | 0.00 |
August | 4236.73 | 994.86 | 3238.90 | 1510.35 | 1728.55 | 0.00 | 0.00 |
September | 4392.95 | 1386.16 | 3588.57 | 1981.73 | 1606.84 | 0.00 | 0.00 |
October | 3604.88 | 1821.02 | 3250.64 | 2007.03 | 1243.61 | 0.00 | 0.00 |
November | 1766.53 | 2190.77 | 1921.88 | 1101.40 | 820.48 | 0.00 | 0.00 |
December | 1905.45 | 2662.19 | 2010.84 | 1301.30 | 709.55 | 0.00 | 0.00 |
Annual Sum or Average | 3129.52 | 1779.20 | 2836.04 | 1387.16 | 1448.88 | 0.00 | 0.00 |
Minimum of Months | 1611.17 | 994.86 | 1891.94 | 742.20 | 709.55 | 0.00 | 0.00 |
Maximum of Months | 4392.95 | 2662.19 | 3588.57 | 2007.03 | 2121.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 190.52 | 1839.19 | 483.83 | 142.67 | 341.15 | 0.00 | 0.00 |
February | 575.44 | 1638.27 | 867.46 | 326.02 | 541.45 | 0.00 | 0.00 |
March | 975.92 | 1379.29 | 1215.54 | 410.28 | 805.26 | 0.00 | 0.00 |
April | 1808.94 | 1151.29 | 1849.31 | 707.06 | 1142.25 | 0.00 | 0.00 |
May | 2569.36 | 964.37 | 2379.63 | 966.71 | 1412.91 | 0.00 | 0.00 |
June | 2533.02 | 762.30 | 2288.55 | 888.57 | 1399.98 | 0.00 | 0.00 |
July | 3445.18 | 710.99 | 2827.19 | 1486.12 | 1341.07 | 0.00 | 0.00 |
August | 2893.88 | 690.36 | 2338.76 | 1194.24 | 1144.52 | 0.00 | 0.00 |
September | 2164.00 | 938.23 | 1904.57 | 913.85 | 990.71 | 0.00 | 0.00 |
October | 971.50 | 1223.86 | 1084.28 | 441.79 | 642.48 | 0.00 | 0.00 |
November | 278.91 | 1513.85 | 539.96 | 152.29 | 387.67 | 0.00 | 0.00 |
December | 231.39 | 1880.09 | 453.94 | 155.55 | 298.39 | 0.00 | 0.00 |
Annual Sum or Average | 1559.64 | 1222.40 | 1523.39 | 651.23 | 872.16 | 0.00 | 0.00 |
Minimum of Months | 190.52 | 690.36 | 453.94 | 142.67 | 298.39 | 0.00 | 0.00 |
Maximum of Months | 3445.18 | 1880.09 | 2827.19 | 1486.12 | 1412.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 17.37 | 2597.42 | 428.20 | 0.00 | 428.20 | 0.00 | 0.00 |
February | 135.95 | 2293.43 | 666.30 | 0.00 | 666.30 | 0.00 | 0.00 |
March | 416.70 | 1888.36 | 981.68 | 0.00 | 981.68 | 0.00 | 0.00 |
April | 899.47 | 1533.44 | 1389.18 | 4.93 | 1384.25 | 0.00 | 0.00 |
May | 1431.65 | 1257.48 | 1787.53 | 53.10 | 1734.42 | 0.00 | 0.00 |
June | 1649.31 | 987.37 | 1879.54 | 124.12 | 1755.42 | 0.00 | 0.00 |
July | 1782.66 | 891.87 | 1786.40 | 140.06 | 1646.34 | 0.00 | 0.00 |
August | 1476.98 | 867.97 | 1446.10 | 39.09 | 1407.01 | 0.00 | 0.00 |
September | 863.04 | 1248.04 | 1123.28 | 0.33 | 1122.95 | 0.00 | 0.00 |
October | 367.49 | 1632.40 | 769.64 | 0.00 | 769.64 | 0.00 | 0.00 |
November | 74.72 | 2060.73 | 484.79 | 0.00 | 484.79 | 0.00 | 0.00 |
December | 10.70 | 2584.26 | 363.86 | 0.00 | 363.86 | 0.00 | 0.00 |
Annual Sum or Average | 764.42 | 1650.45 | 1094.32 | 30.36 | 1063.96 | 0.00 | 0.00 |
Minimum of Months | 10.70 | 867.97 | 363.86 | 0.00 | 363.86 | 0.00 | 0.00 |
Maximum of Months | 1782.66 | 2597.42 | 1879.54 | 140.06 | 1755.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 163.29 | 1646.49 | 458.71 | 116.30 | 342.41 | 0.00 | 0.00 |
February | 547.46 | 1448.01 | 841.69 | 298.73 | 542.95 | 0.00 | 0.00 |
March | 1034.33 | 1209.11 | 1256.70 | 454.93 | 801.76 | 0.00 | 0.00 |
April | 1942.03 | 991.47 | 1948.09 | 809.46 | 1138.63 | 0.00 | 0.00 |
May | 2171.19 | 842.62 | 2072.94 | 720.72 | 1352.23 | 0.00 | 0.00 |
June | 2787.96 | 675.22 | 2482.59 | 1080.19 | 1402.39 | 0.00 | 0.00 |
July | 2720.69 | 595.96 | 2311.86 | 1037.70 | 1274.17 | 0.00 | 0.00 |
August | 2770.03 | 580.94 | 2272.24 | 1136.70 | 1135.53 | 0.00 | 0.00 |
September | 1830.61 | 803.91 | 1679.99 | 774.82 | 905.16 | 0.00 | 0.00 |
October | 996.10 | 1054.32 | 1095.01 | 465.28 | 629.74 | 0.00 | 0.00 |
November | 288.92 | 1325.07 | 536.71 | 151.52 | 385.19 | 0.00 | 0.00 |
December | 208.12 | 1655.94 | 440.23 | 141.72 | 298.50 | 0.00 | 0.00 |
Annual Sum or Average | 1459.70 | 1067.29 | 1452.40 | 600.32 | 852.08 | 0.00 | 0.00 |
Minimum of Months | 163.29 | 580.94 | 440.23 | 116.30 | 298.50 | 0.00 | 0.00 |
Maximum of Months | 2787.96 | 1655.94 | 2482.59 | 1136.70 | 1402.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1652.09 | 2379.42 | 1891.94 | 1123.44 | 768.50 | 0.00 | 0.00 |
February | 2905.57 | 2179.32 | 2909.51 | 1801.03 | 1108.48 | 0.00 | 0.00 |
March | 3268.45 | 1914.60 | 3129.79 | 1669.09 | 1460.71 | 0.00 | 0.00 |
April | 3652.83 | 1643.75 | 3304.47 | 1434.78 | 1869.69 | 0.00 | 0.00 |
May | 3371.61 | 1370.99 | 3021.51 | 900.14 | 2121.37 | 0.00 | 0.00 |
June | 3145.82 | 1096.84 | 2764.39 | 742.20 | 2022.19 | 0.00 | 0.00 |
July | 3800.19 | 1001.28 | 3014.69 | 1104.14 | 1910.55 | 0.00 | 0.00 |
August | 4231.55 | 968.80 | 3238.90 | 1510.35 | 1728.55 | 0.00 | 0.00 |
September | 4410.90 | 1314.47 | 3588.57 | 1981.73 | 1606.84 | 0.00 | 0.00 |
October | 3642.74 | 1680.20 | 3250.64 | 2007.03 | 1243.61 | 0.00 | 0.00 |
November | 1812.37 | 1994.32 | 1921.88 | 1101.40 | 820.48 | 0.00 | 0.00 |
December | 1945.29 | 2443.23 | 2010.84 | 1301.30 | 709.55 | 0.00 | 0.00 |
Annual Sum or Average | 3154.20 | 1663.06 | 2836.04 | 1387.16 | 1448.88 | 0.00 | 0.00 |
Minimum of Months | 1652.09 | 968.80 | 1891.94 | 742.20 | 709.55 | 0.00 | 0.00 |
Maximum of Months | 4410.90 | 2443.23 | 3588.57 | 2007.03 | 2121.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 199.35 | 1712.89 | 483.83 | 142.67 | 341.15 | 0.00 | 0.00 |
February | 593.22 | 1530.53 | 867.46 | 326.02 | 541.45 | 0.00 | 0.00 |
March | 995.31 | 1290.82 | 1215.54 | 410.28 | 805.26 | 0.00 | 0.00 |
April | 1825.30 | 1093.54 | 1849.31 | 707.06 | 1142.25 | 0.00 | 0.00 |
May | 2575.85 | 926.60 | 2379.63 | 966.71 | 1412.91 | 0.00 | 0.00 |
June | 2530.74 | 741.14 | 2288.55 | 888.57 | 1399.98 | 0.00 | 0.00 |
July | 3435.93 | 698.21 | 2827.19 | 1486.12 | 1341.07 | 0.00 | 0.00 |
August | 2889.72 | 673.92 | 2338.76 | 1194.24 | 1144.52 | 0.00 | 0.00 |
September | 2174.61 | 894.12 | 1904.57 | 913.85 | 990.71 | 0.00 | 0.00 |
October | 992.32 | 1138.10 | 1084.28 | 441.79 | 642.48 | 0.00 | 0.00 |
November | 292.81 | 1398.84 | 539.96 | 152.29 | 387.67 | 0.00 | 0.00 |
December | 239.87 | 1750.06 | 453.94 | 155.55 | 298.39 | 0.00 | 0.00 |
Annual Sum or Average | 1568.47 | 1152.31 | 1523.39 | 651.23 | 872.16 | 0.00 | 0.00 |
Minimum of Months | 199.35 | 673.92 | 453.94 | 142.67 | 298.39 | 0.00 | 0.00 |
Maximum of Months | 3435.93 | 1750.06 | 2827.19 | 1486.12 | 1412.91 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 8267577.61 | 0.870694E+10 | 0.114691E+10 | 0.00 | 0.114691E+10 | 0.00 | 0.00 |
February | 0.174499E+09 | 0.695605E+10 | 0.161191E+10 | 0.00 | 0.161191E+10 | 0.00 | 0.00 |
March | 0.816124E+09 | 0.627137E+10 | 0.262935E+10 | 0.00 | 0.262935E+10 | 0.00 | 0.00 |
April | 0.203603E+10 | 0.475767E+10 | 0.360077E+10 | 12773040.70 | 0.358800E+10 | 0.00 | 0.00 |
May | 0.366113E+10 | 0.376184E+10 | 0.478773E+10 | 0.142237E+09 | 0.464550E+10 | 0.00 | 0.00 |
June | 0.417852E+10 | 0.280361E+10 | 0.487179E+10 | 0.321713E+09 | 0.455008E+10 | 0.00 | 0.00 |
July | 0.469136E+10 | 0.259345E+10 | 0.478472E+10 | 0.375144E+09 | 0.440957E+10 | 0.00 | 0.00 |
August | 0.384810E+10 | 0.255488E+10 | 0.387326E+10 | 0.104706E+09 | 0.376856E+10 | 0.00 | 0.00 |
September | 0.208170E+10 | 0.372391E+10 | 0.291156E+10 | 858574.63 | 0.291070E+10 | 0.00 | 0.00 |
October | 0.712683E+09 | 0.549055E+10 | 0.206140E+10 | 0.00 | 0.206140E+10 | 0.00 | 0.00 |
November | 82869595.70 | 0.702937E+10 | 0.125659E+10 | 0.00 | 0.125659E+10 | 0.00 | 0.00 |
December | 1499320.18 | 0.898238E+10 | 0.974575E+09 | 0.00 | 0.974575E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.222928E+11 | 0.636320E+11 | 0.345106E+11 | 0.957431E+09 | 0.335531E+11 | 0.00 | 0.00 |
Minimum of Months | 1499320.18 | 0.255488E+10 | 0.974575E+09 | 0.00 | 0.974575E+09 | 0.00 | 0.00 |
Maximum of Months | 0.469136E+10 | 0.898238E+10 | 0.487179E+10 | 0.375144E+09 | 0.464550E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.359526E+09 | 0.537370E+10 | 0.122861E+10 | 0.311493E+09 | 0.917117E+09 | 0.00 | 0.00 |
February | 0.116589E+10 | 0.419319E+10 | 0.203621E+10 | 0.722695E+09 | 0.131352E+10 | 0.00 | 0.00 |
March | 0.261320E+10 | 0.381498E+10 | 0.336595E+10 | 0.121850E+10 | 0.214744E+10 | 0.00 | 0.00 |
April | 0.494438E+10 | 0.289573E+10 | 0.504948E+10 | 0.209813E+10 | 0.295135E+10 | 0.00 | 0.00 |
May | 0.577747E+10 | 0.246448E+10 | 0.555220E+10 | 0.193037E+10 | 0.362182E+10 | 0.00 | 0.00 |
June | 0.726607E+10 | 0.185673E+10 | 0.643489E+10 | 0.279987E+10 | 0.363502E+10 | 0.00 | 0.00 |
July | 0.733145E+10 | 0.165487E+10 | 0.619212E+10 | 0.277938E+10 | 0.341274E+10 | 0.00 | 0.00 |
August | 0.746543E+10 | 0.159674E+10 | 0.608599E+10 | 0.304456E+10 | 0.304143E+10 | 0.00 | 0.00 |
September | 0.469384E+10 | 0.232522E+10 | 0.435455E+10 | 0.200835E+10 | 0.234619E+10 | 0.00 | 0.00 |
October | 0.252356E+10 | 0.337125E+10 | 0.293290E+10 | 0.124621E+10 | 0.168669E+10 | 0.00 | 0.00 |
November | 0.634006E+09 | 0.426775E+10 | 0.139117E+10 | 0.392741E+09 | 0.998430E+09 | 0.00 | 0.00 |
December | 0.470057E+09 | 0.543545E+10 | 0.117911E+10 | 0.379590E+09 | 0.799519E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.452449E+11 | 0.392501E+11 | 0.458032E+11 | 0.189319E+11 | 0.268713E+11 | 0.00 | 0.00 |
Minimum of Months | 0.359526E+09 | 0.159674E+10 | 0.117911E+10 | 0.311493E+09 | 0.799519E+09 | 0.00 | 0.00 |
Maximum of Months | 0.746543E+10 | 0.543545E+10 | 0.643489E+10 | 0.304456E+10 | 0.363502E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.427064E+10 | 0.735640E+10 | 0.506739E+10 | 0.300904E+10 | 0.205835E+10 | 0.00 | 0.00 |
February | 0.686771E+10 | 0.599894E+10 | 0.703872E+10 | 0.435706E+10 | 0.268166E+10 | 0.00 | 0.00 |
March | 0.865654E+10 | 0.583565E+10 | 0.838287E+10 | 0.447049E+10 | 0.391238E+10 | 0.00 | 0.00 |
April | 0.940711E+10 | 0.473838E+10 | 0.856521E+10 | 0.371897E+10 | 0.484625E+10 | 0.00 | 0.00 |
May | 0.903537E+10 | 0.395798E+10 | 0.809285E+10 | 0.241094E+10 | 0.568191E+10 | 0.00 | 0.00 |
June | 0.817766E+10 | 0.304805E+10 | 0.716532E+10 | 0.192380E+10 | 0.524153E+10 | 0.00 | 0.00 |
July | 0.102284E+11 | 0.282923E+10 | 0.807457E+10 | 0.295734E+10 | 0.511723E+10 | 0.00 | 0.00 |
August | 0.113779E+11 | 0.273192E+10 | 0.867511E+10 | 0.404535E+10 | 0.462976E+10 | 0.00 | 0.00 |
September | 0.114242E+11 | 0.369115E+10 | 0.930161E+10 | 0.513665E+10 | 0.416495E+10 | 0.00 | 0.00 |
October | 0.968119E+10 | 0.511027E+10 | 0.870654E+10 | 0.537564E+10 | 0.333089E+10 | 0.00 | 0.00 |
November | 0.452217E+10 | 0.609623E+10 | 0.498154E+10 | 0.285484E+10 | 0.212670E+10 | 0.00 | 0.00 |
December | 0.504411E+10 | 0.768501E+10 | 0.538586E+10 | 0.348540E+10 | 0.190046E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.986931E+11 | 0.590792E+11 | 0.894376E+11 | 0.437455E+11 | 0.456921E+11 | 0.00 | 0.00 |
Minimum of Months | 0.427064E+10 | 0.273192E+10 | 0.498154E+10 | 0.192380E+10 | 0.190046E+10 | 0.00 | 0.00 |
Maximum of Months | 0.114242E+11 | 0.768501E+10 | 0.930161E+10 | 0.537564E+10 | 0.568191E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.458913E+09 | 0.574265E+10 | 0.129588E+10 | 0.382133E+09 | 0.913751E+09 | 0.00 | 0.00 |
February | 0.127064E+10 | 0.470478E+10 | 0.209857E+10 | 0.788702E+09 | 0.130987E+10 | 0.00 | 0.00 |
March | 0.243217E+10 | 0.446327E+10 | 0.325570E+10 | 0.109889E+10 | 0.215682E+10 | 0.00 | 0.00 |
April | 0.448228E+10 | 0.356709E+10 | 0.479342E+10 | 0.183271E+10 | 0.296071E+10 | 0.00 | 0.00 |
May | 0.682386E+10 | 0.279772E+10 | 0.637362E+10 | 0.258926E+10 | 0.378436E+10 | 0.00 | 0.00 |
June | 0.647558E+10 | 0.221601E+10 | 0.593194E+10 | 0.230318E+10 | 0.362876E+10 | 0.00 | 0.00 |
July | 0.914075E+10 | 0.213652E+10 | 0.757238E+10 | 0.398043E+10 | 0.359195E+10 | 0.00 | 0.00 |
August | 0.762847E+10 | 0.212507E+10 | 0.626417E+10 | 0.319866E+10 | 0.306550E+10 | 0.00 | 0.00 |
September | 0.554226E+10 | 0.267609E+10 | 0.493665E+10 | 0.236871E+10 | 0.256794E+10 | 0.00 | 0.00 |
October | 0.246011E+10 | 0.390042E+10 | 0.290413E+10 | 0.118330E+10 | 0.172084E+10 | 0.00 | 0.00 |
November | 0.614794E+09 | 0.494166E+10 | 0.139959E+10 | 0.394742E+09 | 0.100485E+10 | 0.00 | 0.00 |
December | 0.540300E+09 | 0.639428E+10 | 0.121585E+10 | 0.416639E+09 | 0.799206E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.478701E+11 | 0.456656E+11 | 0.480419E+11 | 0.205373E+11 | 0.275046E+11 | 0.00 | 0.00 |
Minimum of Months | 0.458913E+09 | 0.212507E+10 | 0.121585E+10 | 0.382133E+09 | 0.799206E+09 | 0.00 | 0.00 |
Maximum of Months | 0.914075E+10 | 0.639428E+10 | 0.757238E+10 | 0.398043E+10 | 0.378436E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 27079009.30 | 0.751340E+10 | 0.114690E+10 | 0.00 | 0.114690E+10 | 0.00 | 0.00 |
February | 0.268107E+09 | 0.604652E+10 | 0.161191E+10 | 0.00 | 0.161191E+10 | 0.00 | 0.00 |
March | 0.995576E+09 | 0.551928E+10 | 0.262934E+10 | 0.00 | 0.262934E+10 | 0.00 | 0.00 |
April | 0.222126E+10 | 0.425433E+10 | 0.360076E+10 | 12772995.34 | 0.358799E+10 | 0.00 | 0.00 |
May | 0.375842E+10 | 0.354100E+10 | 0.478772E+10 | 0.142236E+09 | 0.464548E+10 | 0.00 | 0.00 |
June | 0.425577E+10 | 0.264032E+10 | 0.487177E+10 | 0.321712E+09 | 0.455006E+10 | 0.00 | 0.00 |
July | 0.478387E+10 | 0.244192E+10 | 0.478470E+10 | 0.375143E+09 | 0.440955E+10 | 0.00 | 0.00 |
August | 0.394818E+10 | 0.239449E+10 | 0.387325E+10 | 0.104706E+09 | 0.376854E+10 | 0.00 | 0.00 |
September | 0.216485E+10 | 0.345283E+10 | 0.291155E+10 | 858571.59 | 0.291069E+10 | 0.00 | 0.00 |
October | 0.861246E+09 | 0.482928E+10 | 0.206139E+10 | 0.00 | 0.206139E+10 | 0.00 | 0.00 |
November | 0.142725E+09 | 0.594932E+10 | 0.125659E+10 | 0.00 | 0.125659E+10 | 0.00 | 0.00 |
December | 11581046.21 | 0.758261E+10 | 0.974571E+09 | 0.00 | 0.974571E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.234387E+11 | 0.561653E+11 | 0.345104E+11 | 0.957428E+09 | 0.335530E+11 | 0.00 | 0.00 |
Minimum of Months | 11581046.21 | 0.239449E+10 | 0.974571E+09 | 0.00 | 0.974571E+09 | 0.00 | 0.00 |
Maximum of Months | 0.478387E+10 | 0.758261E+10 | 0.487177E+10 | 0.375143E+09 | 0.464548E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.403505E+09 | 0.474818E+10 | 0.122860E+10 | 0.311492E+09 | 0.917113E+09 | 0.00 | 0.00 |
February | 0.125246E+10 | 0.379536E+10 | 0.203621E+10 | 0.722692E+09 | 0.131351E+10 | 0.00 | 0.00 |
March | 0.269126E+10 | 0.349000E+10 | 0.336593E+10 | 0.121850E+10 | 0.214744E+10 | 0.00 | 0.00 |
April | 0.497832E+10 | 0.271493E+10 | 0.504946E+10 | 0.209812E+10 | 0.295133E+10 | 0.00 | 0.00 |
May | 0.578737E+10 | 0.234876E+10 | 0.555217E+10 | 0.193036E+10 | 0.362181E+10 | 0.00 | 0.00 |
June | 0.723556E+10 | 0.179104E+10 | 0.643486E+10 | 0.279985E+10 | 0.363501E+10 | 0.00 | 0.00 |
July | 0.730490E+10 | 0.161712E+10 | 0.619209E+10 | 0.277937E+10 | 0.341273E+10 | 0.00 | 0.00 |
August | 0.742934E+10 | 0.158753E+10 | 0.608596E+10 | 0.304455E+10 | 0.304142E+10 | 0.00 | 0.00 |
September | 0.471210E+10 | 0.219329E+10 | 0.435453E+10 | 0.200835E+10 | 0.234618E+10 | 0.00 | 0.00 |
October | 0.259132E+10 | 0.306594E+10 | 0.293288E+10 | 0.124620E+10 | 0.168668E+10 | 0.00 | 0.00 |
November | 0.695553E+09 | 0.378041E+10 | 0.139117E+10 | 0.392740E+09 | 0.998425E+09 | 0.00 | 0.00 |
December | 0.516785E+09 | 0.483084E+10 | 0.117910E+10 | 0.379588E+09 | 0.799515E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.455985E+11 | 0.359634E+11 | 0.458030E+11 | 0.189318E+11 | 0.268712E+11 | 0.00 | 0.00 |
Minimum of Months | 0.403505E+09 | 0.158753E+10 | 0.117910E+10 | 0.311492E+09 | 0.799515E+09 | 0.00 | 0.00 |
Maximum of Months | 0.742934E+10 | 0.483084E+10 | 0.643486E+10 | 0.304455E+10 | 0.363501E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.431535E+10 | 0.689895E+10 | 0.506737E+10 | 0.300903E+10 | 0.205834E+10 | 0.00 | 0.00 |
February | 0.689662E+10 | 0.571393E+10 | 0.703869E+10 | 0.435705E+10 | 0.268165E+10 | 0.00 | 0.00 |
March | 0.865739E+10 | 0.553345E+10 | 0.838284E+10 | 0.447048E+10 | 0.391236E+10 | 0.00 | 0.00 |
April | 0.939895E+10 | 0.450998E+10 | 0.856518E+10 | 0.371896E+10 | 0.484623E+10 | 0.00 | 0.00 |
May | 0.899382E+10 | 0.384180E+10 | 0.809282E+10 | 0.241093E+10 | 0.568189E+10 | 0.00 | 0.00 |
June | 0.815680E+10 | 0.293159E+10 | 0.716530E+10 | 0.192379E+10 | 0.524151E+10 | 0.00 | 0.00 |
July | 0.102016E+11 | 0.273528E+10 | 0.807454E+10 | 0.295733E+10 | 0.511721E+10 | 0.00 | 0.00 |
August | 0.113477E+11 | 0.266462E+10 | 0.867507E+10 | 0.404533E+10 | 0.462974E+10 | 0.00 | 0.00 |
September | 0.113865E+11 | 0.359293E+10 | 0.930157E+10 | 0.513664E+10 | 0.416494E+10 | 0.00 | 0.00 |
October | 0.965530E+10 | 0.487742E+10 | 0.870651E+10 | 0.537562E+10 | 0.333088E+10 | 0.00 | 0.00 |
November | 0.457885E+10 | 0.567848E+10 | 0.498153E+10 | 0.285483E+10 | 0.212669E+10 | 0.00 | 0.00 |
December | 0.510357E+10 | 0.713042E+10 | 0.538584E+10 | 0.348539E+10 | 0.190045E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.986924E+11 | 0.561088E+11 | 0.894373E+11 | 0.437454E+11 | 0.456919E+11 | 0.00 | 0.00 |
Minimum of Months | 0.431535E+10 | 0.266462E+10 | 0.498153E+10 | 0.192379E+10 | 0.190045E+10 | 0.00 | 0.00 |
Maximum of Months | 0.113865E+11 | 0.713042E+10 | 0.930157E+10 | 0.537562E+10 | 0.568189E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.510277E+09 | 0.492609E+10 | 0.129588E+10 | 0.382131E+09 | 0.913748E+09 | 0.00 | 0.00 |
February | 0.139210E+10 | 0.396329E+10 | 0.209856E+10 | 0.788699E+09 | 0.130986E+10 | 0.00 | 0.00 |
March | 0.261389E+10 | 0.369428E+10 | 0.325569E+10 | 0.109888E+10 | 0.215681E+10 | 0.00 | 0.00 |
April | 0.468878E+10 | 0.298416E+10 | 0.479340E+10 | 0.183270E+10 | 0.296070E+10 | 0.00 | 0.00 |
May | 0.688178E+10 | 0.258297E+10 | 0.637359E+10 | 0.258925E+10 | 0.378435E+10 | 0.00 | 0.00 |
June | 0.656558E+10 | 0.197589E+10 | 0.593192E+10 | 0.230317E+10 | 0.362875E+10 | 0.00 | 0.00 |
July | 0.922756E+10 | 0.190432E+10 | 0.757234E+10 | 0.398041E+10 | 0.359193E+10 | 0.00 | 0.00 |
August | 0.775098E+10 | 0.184906E+10 | 0.626414E+10 | 0.319865E+10 | 0.306549E+10 | 0.00 | 0.00 |
September | 0.560908E+10 | 0.243189E+10 | 0.493663E+10 | 0.236870E+10 | 0.256793E+10 | 0.00 | 0.00 |
October | 0.260205E+10 | 0.327799E+10 | 0.290412E+10 | 0.118329E+10 | 0.172083E+10 | 0.00 | 0.00 |
November | 0.722924E+09 | 0.392391E+10 | 0.139958E+10 | 0.394740E+09 | 0.100484E+10 | 0.00 | 0.00 |
December | 0.619752E+09 | 0.503564E+10 | 0.121584E+10 | 0.416638E+09 | 0.799203E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.491848E+11 | 0.385495E+11 | 0.480417E+11 | 0.205373E+11 | 0.275044E+11 | 0.00 | 0.00 |
Minimum of Months | 0.510277E+09 | 0.184906E+10 | 0.121584E+10 | 0.382131E+09 | 0.799203E+09 | 0.00 | 0.00 |
Maximum of Months | 0.922756E+10 | 0.503564E+10 | 0.757234E+10 | 0.398041E+10 | 0.378435E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 46515425.98 | 0.695693E+10 | 0.114690E+10 | 0.00 | 0.114690E+10 | 0.00 | 0.00 |
February | 0.328899E+09 | 0.554826E+10 | 0.161191E+10 | 0.00 | 0.161191E+10 | 0.00 | 0.00 |
March | 0.111610E+10 | 0.505779E+10 | 0.262934E+10 | 0.00 | 0.262934E+10 | 0.00 | 0.00 |
April | 0.233143E+10 | 0.397467E+10 | 0.360076E+10 | 12772995.34 | 0.358799E+10 | 0.00 | 0.00 |
May | 0.383454E+10 | 0.336803E+10 | 0.478772E+10 | 0.142236E+09 | 0.464548E+10 | 0.00 | 0.00 |
June | 0.427500E+10 | 0.255927E+10 | 0.487177E+10 | 0.321712E+09 | 0.455006E+10 | 0.00 | 0.00 |
July | 0.477466E+10 | 0.238880E+10 | 0.478470E+10 | 0.375143E+09 | 0.440955E+10 | 0.00 | 0.00 |
August | 0.395594E+10 | 0.232476E+10 | 0.387325E+10 | 0.104706E+09 | 0.376854E+10 | 0.00 | 0.00 |
September | 0.223700E+10 | 0.323491E+10 | 0.291155E+10 | 858571.59 | 0.291069E+10 | 0.00 | 0.00 |
October | 0.984284E+09 | 0.437222E+10 | 0.206139E+10 | 0.00 | 0.206139E+10 | 0.00 | 0.00 |
November | 0.193670E+09 | 0.534142E+10 | 0.125659E+10 | 0.00 | 0.125659E+10 | 0.00 | 0.00 |
December | 28659935.24 | 0.692168E+10 | 0.974571E+09 | 0.00 | 0.974571E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.241067E+11 | 0.520487E+11 | 0.345104E+11 | 0.957428E+09 | 0.335530E+11 | 0.00 | 0.00 |
Minimum of Months | 28659935.24 | 0.232476E+10 | 0.974571E+09 | 0.00 | 0.974571E+09 | 0.00 | 0.00 |
Maximum of Months | 0.477466E+10 | 0.695693E+10 | 0.487177E+10 | 0.375143E+09 | 0.464548E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.437353E+09 | 0.440996E+10 | 0.122860E+10 | 0.311492E+09 | 0.917113E+09 | 0.00 | 0.00 |
February | 0.132443E+10 | 0.350303E+10 | 0.203621E+10 | 0.722692E+09 | 0.131351E+10 | 0.00 | 0.00 |
March | 0.277034E+10 | 0.323848E+10 | 0.336593E+10 | 0.121850E+10 | 0.214744E+10 | 0.00 | 0.00 |
April | 0.503374E+10 | 0.256990E+10 | 0.504946E+10 | 0.209812E+10 | 0.295133E+10 | 0.00 | 0.00 |
May | 0.581531E+10 | 0.225687E+10 | 0.555217E+10 | 0.193036E+10 | 0.362181E+10 | 0.00 | 0.00 |
June | 0.722640E+10 | 0.175017E+10 | 0.643486E+10 | 0.279985E+10 | 0.363501E+10 | 0.00 | 0.00 |
July | 0.728710E+10 | 0.159621E+10 | 0.619209E+10 | 0.277937E+10 | 0.341273E+10 | 0.00 | 0.00 |
August | 0.741925E+10 | 0.155598E+10 | 0.608596E+10 | 0.304455E+10 | 0.304142E+10 | 0.00 | 0.00 |
September | 0.474494E+10 | 0.208374E+10 | 0.435453E+10 | 0.200835E+10 | 0.234618E+10 | 0.00 | 0.00 |
October | 0.266796E+10 | 0.282389E+10 | 0.293288E+10 | 0.124620E+10 | 0.168668E+10 | 0.00 | 0.00 |
November | 0.748893E+09 | 0.343458E+10 | 0.139117E+10 | 0.392740E+09 | 0.998425E+09 | 0.00 | 0.00 |
December | 0.557427E+09 | 0.443526E+10 | 0.117910E+10 | 0.379588E+09 | 0.799515E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.460331E+11 | 0.336581E+11 | 0.458030E+11 | 0.189318E+11 | 0.268712E+11 | 0.00 | 0.00 |
Minimum of Months | 0.437353E+09 | 0.155598E+10 | 0.117910E+10 | 0.311492E+09 | 0.799515E+09 | 0.00 | 0.00 |
Maximum of Months | 0.741925E+10 | 0.443526E+10 | 0.643486E+10 | 0.304455E+10 | 0.363501E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.442495E+10 | 0.637304E+10 | 0.506737E+10 | 0.300903E+10 | 0.205834E+10 | 0.00 | 0.00 |
February | 0.702916E+10 | 0.527222E+10 | 0.703869E+10 | 0.435705E+10 | 0.268165E+10 | 0.00 | 0.00 |
March | 0.875422E+10 | 0.512805E+10 | 0.838284E+10 | 0.447048E+10 | 0.391236E+10 | 0.00 | 0.00 |
April | 0.946815E+10 | 0.426061E+10 | 0.856518E+10 | 0.371896E+10 | 0.484623E+10 | 0.00 | 0.00 |
May | 0.903051E+10 | 0.367205E+10 | 0.809282E+10 | 0.241093E+10 | 0.568189E+10 | 0.00 | 0.00 |
June | 0.815397E+10 | 0.284300E+10 | 0.716530E+10 | 0.192379E+10 | 0.524151E+10 | 0.00 | 0.00 |
July | 0.101784E+11 | 0.268183E+10 | 0.807454E+10 | 0.295733E+10 | 0.511721E+10 | 0.00 | 0.00 |
August | 0.113338E+11 | 0.259484E+10 | 0.867507E+10 | 0.404533E+10 | 0.462974E+10 | 0.00 | 0.00 |
September | 0.114331E+11 | 0.340712E+10 | 0.930157E+10 | 0.513664E+10 | 0.416494E+10 | 0.00 | 0.00 |
October | 0.975671E+10 | 0.450024E+10 | 0.870651E+10 | 0.537562E+10 | 0.333088E+10 | 0.00 | 0.00 |
November | 0.469766E+10 | 0.516928E+10 | 0.498153E+10 | 0.285483E+10 | 0.212669E+10 | 0.00 | 0.00 |
December | 0.521026E+10 | 0.654394E+10 | 0.538584E+10 | 0.348539E+10 | 0.190045E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.994709E+11 | 0.524462E+11 | 0.894373E+11 | 0.437454E+11 | 0.456919E+11 | 0.00 | 0.00 |
Minimum of Months | 0.442495E+10 | 0.259484E+10 | 0.498153E+10 | 0.192379E+10 | 0.190045E+10 | 0.00 | 0.00 |
Maximum of Months | 0.114331E+11 | 0.654394E+10 | 0.930157E+10 | 0.537562E+10 | 0.568189E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.533932E+09 | 0.458782E+10 | 0.129588E+10 | 0.382131E+09 | 0.913748E+09 | 0.00 | 0.00 |
February | 0.143511E+10 | 0.370265E+10 | 0.209856E+10 | 0.788699E+09 | 0.130986E+10 | 0.00 | 0.00 |
March | 0.266583E+10 | 0.345733E+10 | 0.325569E+10 | 0.109888E+10 | 0.215681E+10 | 0.00 | 0.00 |
April | 0.473118E+10 | 0.283447E+10 | 0.479340E+10 | 0.183270E+10 | 0.296070E+10 | 0.00 | 0.00 |
May | 0.689916E+10 | 0.248180E+10 | 0.637359E+10 | 0.258925E+10 | 0.378435E+10 | 0.00 | 0.00 |
June | 0.655968E+10 | 0.192102E+10 | 0.593192E+10 | 0.230317E+10 | 0.362875E+10 | 0.00 | 0.00 |
July | 0.920278E+10 | 0.187008E+10 | 0.757234E+10 | 0.398041E+10 | 0.359193E+10 | 0.00 | 0.00 |
August | 0.773982E+10 | 0.180504E+10 | 0.626414E+10 | 0.319865E+10 | 0.306549E+10 | 0.00 | 0.00 |
September | 0.563659E+10 | 0.231756E+10 | 0.493663E+10 | 0.236870E+10 | 0.256793E+10 | 0.00 | 0.00 |
October | 0.265784E+10 | 0.304828E+10 | 0.290412E+10 | 0.118329E+10 | 0.172083E+10 | 0.00 | 0.00 |
November | 0.758972E+09 | 0.362580E+10 | 0.139958E+10 | 0.394740E+09 | 0.100484E+10 | 0.00 | 0.00 |
December | 0.642463E+09 | 0.468736E+10 | 0.121584E+10 | 0.416638E+09 | 0.799203E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.494634E+11 | 0.363392E+11 | 0.480417E+11 | 0.205373E+11 | 0.275044E+11 | 0.00 | 0.00 |
Minimum of Months | 0.533932E+09 | 0.180504E+10 | 0.121584E+10 | 0.382131E+09 | 0.799203E+09 | 0.00 | 0.00 |
Maximum of Months | 0.920278E+10 | 0.468736E+10 | 0.757234E+10 | 0.398041E+10 | 0.378435E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.10 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.07 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.04 | 5.25 | 4.23 | 1.22 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.02 | 7.49 | 3.85 | 3.75 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.80 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.41 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.57 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.55 | 10.74 | 2.23 | 5.47 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.19 | 7.19 | 4.02 | 2.10 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.13 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.10 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.57 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.49 | 7.20 | 8.40 | 3.89 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.17 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.43 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.22 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.36 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.74 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.78 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.70 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.69 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.49 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.94 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.44 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.44 | 0.00 | 0.00 | 3.89 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.78 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -2.0 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.19 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.57 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.57 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.49 | 11-JAN-13:00 | 14.40 | 7.20 | 8.20 | 2.85 | 105.50 | 249.00 |
February | 12.42 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.45 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.29 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.58 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.74 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.18 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.13 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.97 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.05 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.71 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.49 | 11.70 | 6.70 | 0.00 | 2.85 | 45.00 | 0.00 | |
Maximum of Months | 20.13 | 28.90 | 15.70 | 8.20 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.49 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.35 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.10 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.77 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.93 | 2.10 | 6.89 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.01 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.10 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.390570E+11 | -0.386122E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -444874439.3 | 60.05 | 0.00 | 0.00 |
February | 0.357276E+11 | -0.353262E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -401451652.1 | 60.05 | 0.00 | 0.00 |
March | 0.415406E+11 | -0.410963E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -444292676.9 | 60.05 | 0.00 | 0.00 |
April | 0.366855E+11 | -0.362576E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -427965563.5 | 60.05 | 0.00 | 0.00 |
May | 0.377488E+11 | -0.373060E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -442763968.9 | 60.05 | 0.00 | 0.00 |
June | 0.360470E+11 | -0.356186E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -428378181.4 | 60.05 | 0.00 | 0.00 |
July | 0.333857E+11 | -0.329455E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -440146259.5 | 60.05 | 0.00 | 0.00 |
August | 0.362127E+11 | -0.357723E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -440368817.3 | 60.05 | 0.00 | 0.00 |
September | 0.333049E+11 | -0.328780E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -426921492.8 | 60.05 | 0.00 | 0.00 |
October | 0.354156E+11 | -0.349745E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -441064355.6 | 60.05 | 0.00 | 0.00 |
November | 0.360880E+11 | -0.356606E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -427391341.5 | 60.05 | 0.00 | 0.00 |
December | 0.372210E+11 | -0.367784E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -442617467.8 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.438434E+12 | -0.433226E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.520824E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.333049E+11 | -0.410963E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -444874439.3 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.415406E+11 | -0.328780E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -401451652.1 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.52 | 0.48 | 01-JAN-09:00 | 2764.29 | 32.58 | 224.33 | 219.67 | 2179.77 | 33.69 | 226.67 | 187.33 |
February | 259.50 | 0.51 | 0.48 | 01-FEB-08:39 | 4701.18 | 33.55 | 246.00 | 244.33 | 2039.82 | 29.27 | 224.33 | 219.00 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-07:40 | 7785.46 | 33.52 | 209.67 | 313.00 | 1665.08 | 22.72 | 204.17 | 267.83 |
April | 379.50 | 0.52 | 0.48 | 01-APR-07:10 | 2224.33 | 20.36 | 171.00 | 345.50 | 1215.99 | 21.78 | 250.50 | 308.33 |
May | 427.83 | 0.52 | 0.48 | 01-MAY-07:19 | 2044.61 | 20.21 | 161.33 | 386.00 | 1103.62 | 21.59 | 278.83 | 344.67 |
June | 375.17 | 0.53 | 0.48 | 01-JUN-06:10 | 1794.58 | 19.75 | 113.67 | 396.33 | 1019.83 | 21.16 | 267.00 | 346.17 |
July | 471.00 | 0.55 | 0.48 | 01-JUL-05:49 | 1595.41 | 18.59 | 118.00 | 395.67 | 925.90 | 19.98 | 193.00 | 341.00 |
August | 366.67 | 0.53 | 0.48 | 01-AUG-06:10 | 1884.96 | 19.64 | 117.83 | 374.67 | 1114.43 | 21.05 | 210.00 | 328.50 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:40 | 3019.21 | 22.38 | 144.17 | 320.33 | 1465.92 | 22.55 | 226.33 | 288.17 |
October | 245.33 | 0.52 | 0.48 | 01-OCT-07:00 | 7226.87 | 34.96 | 224.67 | 285.00 | 1943.36 | 23.90 | 188.33 | 256.17 |
November | 242.67 | 0.51 | 0.48 | 01-NOV-08:20 | 3080.82 | 32.13 | 226.83 | 225.50 | 2447.31 | 33.31 | 230.50 | 194.00 |
December | 160.33 | 0.51 | 0.48 | 01-DEC-09:39 | 3710.65 | 35.80 | 149.50 | 207.67 | 3119.16 | 37.06 | 149.67 | 167.00 |
Annual Sum or Average | 3714.00 | 0.52 | 3139.47 | 25.13 | 2107.00 | 3713.67 | 1516.49 | 24.36 | 2649.33 | 3248.17 | ||
Minimum of Months | 160.33 | 0.51 | 0.48 | 1595.41 | 18.59 | 113.67 | 207.67 | 925.90 | 19.98 | 149.67 | 167.00 | |
Maximum of Months | 471.00 | 0.55 | 0.48 | 7785.46 | 35.80 | 246.00 | 396.33 | 3119.16 | 37.06 | 278.83 | 346.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.55 | 0.48 | 01-JAN-10:09 | 936.03 | 21.21 | 70.50 | 200.67 | 574.26 | 22.54 | 94.00 | 132.17 |
February | 259.50 | 0.53 | 0.48 | 01-FEB-08:39 | 1528.42 | 23.20 | 98.67 | 228.67 | 795.76 | 23.34 | 136.33 | 182.17 |
March | 247.00 | 0.52 | 0.48 | 01-MAR-07:30 | 2751.02 | 25.63 | 117.50 | 304.33 | 1201.86 | 24.51 | 158.83 | 256.00 |
April | 379.50 | 0.51 | 0.48 | 01-APR-06:19 | 2871.38 | 24.34 | 148.67 | 348.17 | 1597.08 | 24.71 | 229.50 | 308.83 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-06:00 | 2951.89 | 23.65 | 160.83 | 391.83 | 1287.14 | 23.41 | 248.83 | 352.17 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-05:10 | 3103.90 | 23.54 | 107.33 | 404.33 | 1698.99 | 24.00 | 208.67 | 359.33 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-04:00 | 2917.06 | 23.77 | 170.50 | 411.17 | 1318.87 | 23.35 | 221.67 | 373.83 |
August | 366.67 | 0.52 | 0.48 | 01-AUG-05:30 | 3394.92 | 24.43 | 127.67 | 379.50 | 1476.80 | 23.73 | 177.83 | 340.33 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2786.33 | 24.19 | 99.83 | 323.83 | 1545.32 | 24.54 | 164.33 | 286.33 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-07:49 | 2523.40 | 25.24 | 109.17 | 272.17 | 1103.64 | 24.05 | 140.00 | 227.67 |
November | 242.67 | 0.54 | 0.48 | 01-NOV-08:09 | 1161.91 | 22.46 | 87.83 | 208.33 | 602.68 | 22.60 | 93.83 | 147.33 |
December | 160.33 | 0.55 | 0.48 | 01-DEC-09:39 | 1097.01 | 23.42 | 64.83 | 185.83 | 588.15 | 23.35 | 71.67 | 107.67 |
Annual Sum or Average | 3714.00 | 0.52 | 2517.67 | 23.81 | 1363.33 | 3658.83 | 1231.42 | 23.72 | 1945.50 | 3073.83 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 936.03 | 21.21 | 64.83 | 185.83 | 574.26 | 22.54 | 71.67 | 107.67 | |
Maximum of Months | 471.00 | 0.55 | 0.48 | 3394.92 | 25.63 | 170.50 | 411.17 | 1698.99 | 24.71 | 248.83 | 373.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.59 | 0.48 | 03-JAN-10:30 | 507.95 | 16.04 | 0.00 | 179.67 | 276.08 | 17.37 | 0.00 | 54.33 |
February | 259.50 | 0.55 | 0.48 | 01-FEB-11:09 | 646.14 | 17.22 | 0.00 | 216.17 | 364.52 | 18.64 | 1.83 | 132.33 |
March | 247.00 | 0.53 | 0.48 | 01-MAR-08:39 | 873.39 | 18.64 | 0.00 | 298.67 | 516.20 | 20.10 | 68.67 | 218.50 |
April | 379.50 | 0.52 | 0.48 | 01-APR-07:19 | 1023.75 | 19.32 | 0.50 | 349.00 | 591.78 | 20.66 | 163.00 | 302.50 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-07:19 | 1256.76 | 21.41 | 94.17 | 399.67 | 719.48 | 22.14 | 274.50 | 365.50 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:40 | 1335.90 | 22.48 | 126.00 | 414.00 | 758.14 | 22.47 | 263.17 | 381.00 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-05:10 | 1127.37 | 21.63 | 127.50 | 423.50 | 647.45 | 21.56 | 231.83 | 378.50 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:00 | 978.76 | 19.36 | 15.83 | 389.00 | 609.83 | 20.71 | 131.83 | 345.67 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:49 | 951.48 | 19.42 | 0.00 | 314.67 | 575.86 | 20.85 | 102.83 | 257.83 |
October | 245.33 | 0.55 | 0.48 | 01-OCT-08:39 | 708.98 | 17.71 | 0.00 | 261.17 | 428.17 | 19.22 | 13.50 | 171.50 |
November | 242.67 | 0.58 | 0.48 | 01-NOV-11:39 | 547.34 | 16.35 | 0.00 | 193.33 | 297.55 | 17.64 | 0.17 | 70.33 |
December | 160.33 | 0.61 | 0.48 | 01-DEC-10:20 | 476.37 | 16.05 | 0.00 | 155.67 | 277.13 | 17.64 | 0.00 | 41.50 |
Annual Sum or Average | 3714.00 | 0.53 | 940.00 | 19.34 | 364.00 | 3594.50 | 546.11 | 20.34 | 1251.33 | 2719.50 | ||
Minimum of Months | 160.33 | 0.51 | 0.48 | 476.37 | 16.04 | 0.00 | 155.67 | 276.08 | 17.37 | 0.00 | 41.50 | |
Maximum of Months | 471.00 | 0.61 | 0.48 | 1335.90 | 22.48 | 127.50 | 423.50 | 758.14 | 22.47 | 274.50 | 381.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.55 | 0.48 | 01-JAN-13:20 | 1065.66 | 22.56 | 87.33 | 202.17 | 566.35 | 22.67 | 94.67 | 139.00 |
February | 259.50 | 0.53 | 0.48 | 01-FEB-09:30 | 1513.23 | 23.17 | 95.17 | 232.17 | 775.78 | 23.24 | 126.50 | 184.33 |
March | 247.00 | 0.52 | 0.48 | 01-MAR-08:39 | 2405.55 | 24.41 | 112.33 | 306.67 | 1283.19 | 24.60 | 152.33 | 254.00 |
April | 379.50 | 0.52 | 0.48 | 01-APR-07:49 | 2875.26 | 23.21 | 134.17 | 345.83 | 1253.55 | 22.65 | 208.67 | 308.83 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-08:09 | 2981.80 | 20.76 | 88.50 | 392.67 | 1594.19 | 20.97 | 223.67 | 357.33 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-06:19 | 3042.30 | 20.35 | 52.00 | 403.67 | 1371.60 | 20.72 | 189.67 | 363.17 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-09:00 | 3336.15 | 19.60 | 75.83 | 405.33 | 1461.79 | 19.66 | 157.50 | 364.00 |
August | 366.67 | 0.52 | 0.48 | 01-AUG-06:49 | 3183.48 | 22.01 | 93.33 | 384.00 | 1828.10 | 22.70 | 161.17 | 346.00 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-08:09 | 3520.24 | 25.45 | 125.00 | 316.50 | 1954.79 | 25.51 | 180.67 | 274.33 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-08:00 | 2427.62 | 25.92 | 116.33 | 274.50 | 1078.27 | 24.70 | 153.17 | 228.00 |
November | 242.67 | 0.54 | 0.48 | 01-NOV-10:20 | 1132.10 | 22.04 | 79.33 | 210.33 | 590.00 | 22.12 | 91.83 | 143.00 |
December | 160.33 | 0.55 | 0.48 | 01-DEC-10:09 | 1118.40 | 22.56 | 56.00 | 186.17 | 591.65 | 22.56 | 66.17 | 103.67 |
Annual Sum or Average | 3714.00 | 0.52 | 2583.99 | 22.36 | 1115.33 | 3660.00 | 1285.79 | 22.39 | 1806.00 | 3065.67 | ||
Minimum of Months | 160.33 | 0.51 | 0.48 | 1065.66 | 19.60 | 52.00 | 186.17 | 566.35 | 19.66 | 66.17 | 103.67 | |
Maximum of Months | 471.00 | 0.55 | 0.48 | 3520.24 | 25.92 | 134.17 | 405.33 | 1954.79 | 25.51 | 223.67 | 364.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.52 | 0.48 | 01-JAN-09:00 | 2768.53 | 32.00 | 220.33 | 219.67 | 2241.42 | 33.13 | 221.33 | 190.33 |
February | 259.50 | 0.51 | 0.48 | 01-FEB-08:39 | 4724.26 | 32.97 | 239.00 | 244.50 | 2132.71 | 27.47 | 156.50 | 223.17 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-07:40 | 7825.28 | 32.31 | 208.50 | 313.33 | 1776.48 | 18.00 | 8.50 | 272.17 |
April | 379.50 | 0.52 | 0.48 | 01-APR-07:10 | 2254.49 | 13.84 | 0.00 | 345.83 | 1299.10 | 17.30 | 0.67 | 312.50 |
May | 427.83 | 0.52 | 0.48 | 01-MAY-07:19 | 2069.49 | 13.84 | 0.00 | 386.83 | 1176.69 | 17.25 | 0.00 | 349.67 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-06:10 | 1826.03 | 13.71 | 0.00 | 396.67 | 1089.65 | 17.12 | 0.00 | 351.83 |
July | 471.00 | 0.54 | 0.48 | 01-JUL-05:40 | 1627.93 | 12.33 | 0.00 | 396.33 | 991.65 | 15.78 | 0.00 | 348.33 |
August | 366.67 | 0.53 | 0.48 | 01-AUG-06:10 | 1928.11 | 13.43 | 0.00 | 375.33 | 1196.78 | 16.95 | 1.33 | 333.00 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:40 | 3066.04 | 16.45 | 27.00 | 320.50 | 1571.82 | 18.16 | 11.67 | 292.00 |
October | 245.33 | 0.51 | 0.48 | 01-OCT-07:00 | 7268.91 | 34.06 | 220.33 | 285.00 | 2054.23 | 19.38 | 26.17 | 258.83 |
November | 242.67 | 0.51 | 0.48 | 01-NOV-08:20 | 3093.27 | 31.50 | 221.67 | 225.50 | 2510.94 | 32.77 | 226.17 | 197.50 |
December | 160.33 | 0.51 | 0.48 | 01-DEC-09:39 | 3727.58 | 34.97 | 149.17 | 208.00 | 3206.96 | 36.43 | 149.67 | 171.17 |
Annual Sum or Average | 3714.00 | 0.52 | 3169.63 | 20.94 | 1286.00 | 3717.50 | 1598.63 | 20.86 | 802.00 | 3300.50 | ||
Minimum of Months | 160.33 | 0.51 | 0.48 | 1627.93 | 12.33 | 0.00 | 208.00 | 991.65 | 15.78 | 0.00 | 171.17 | |
Maximum of Months | 471.00 | 0.54 | 0.48 | 7825.28 | 34.97 | 239.00 | 396.67 | 3206.96 | 36.43 | 226.17 | 351.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.55 | 0.48 | 01-JAN-10:09 | 952.21 | 18.36 | 61.33 | 202.50 | 598.14 | 20.66 | 71.50 | 138.67 |
February | 259.50 | 0.53 | 0.48 | 01-FEB-08:30 | 1554.69 | 20.51 | 81.17 | 230.50 | 832.11 | 21.29 | 62.00 | 188.17 |
March | 247.00 | 0.52 | 0.48 | 01-MAR-07:30 | 2799.49 | 23.14 | 91.50 | 304.83 | 1260.55 | 22.34 | 51.50 | 260.83 |
April | 379.50 | 0.51 | 0.48 | 01-APR-06:19 | 2921.38 | 21.52 | 118.33 | 349.00 | 1661.69 | 22.53 | 91.67 | 313.67 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-06:00 | 2994.48 | 20.41 | 132.67 | 393.33 | 1351.85 | 20.94 | 79.50 | 357.00 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-05:10 | 3154.37 | 20.41 | 98.83 | 405.33 | 1777.20 | 21.57 | 73.67 | 364.33 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-04:00 | 2958.33 | 20.06 | 148.50 | 411.17 | 1383.86 | 20.91 | 99.33 | 379.50 |
August | 366.67 | 0.52 | 0.48 | 01-AUG-05:30 | 3449.91 | 21.55 | 116.33 | 380.67 | 1549.63 | 21.20 | 66.50 | 345.33 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2840.11 | 21.35 | 84.33 | 324.17 | 1609.41 | 22.32 | 61.50 | 290.50 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-07:49 | 2563.36 | 22.89 | 93.33 | 273.67 | 1155.25 | 22.01 | 58.00 | 232.33 |
November | 242.67 | 0.54 | 0.48 | 01-NOV-08:09 | 1181.14 | 19.80 | 78.83 | 210.33 | 629.49 | 20.55 | 62.83 | 155.17 |
December | 160.33 | 0.54 | 0.48 | 01-DEC-09:39 | 1115.52 | 21.02 | 56.33 | 186.83 | 615.19 | 21.61 | 52.67 | 114.33 |
Annual Sum or Average | 3714.00 | 0.52 | 2558.60 | 20.87 | 1161.50 | 3672.33 | 1288.31 | 21.47 | 830.67 | 3139.83 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 952.21 | 18.36 | 56.33 | 186.83 | 598.14 | 20.55 | 51.50 | 114.33 | |
Maximum of Months | 471.00 | 0.55 | 0.48 | 3449.91 | 23.14 | 148.50 | 411.17 | 1777.20 | 22.53 | 99.33 | 379.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.59 | 0.48 | 02-JAN-11:30 | 512.91 | 9.51 | 0.00 | 180.33 | 292.82 | 13.00 | 0.00 | 68.33 |
February | 259.50 | 0.55 | 0.48 | 01-FEB-09:30 | 653.92 | 11.08 | 0.00 | 216.33 | 387.11 | 14.57 | 0.00 | 143.17 |
March | 247.00 | 0.53 | 0.48 | 01-MAR-08:30 | 887.03 | 12.97 | 0.00 | 298.83 | 549.07 | 16.44 | 0.00 | 229.50 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:19 | 1040.20 | 13.68 | 0.00 | 349.00 | 629.80 | 17.07 | 0.00 | 310.00 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:19 | 1293.30 | 16.18 | 39.17 | 400.17 | 770.07 | 19.33 | 44.67 | 371.00 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:40 | 1361.03 | 17.81 | 60.17 | 414.33 | 832.82 | 20.88 | 62.00 | 388.33 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-05:10 | 1154.32 | 16.76 | 78.00 | 424.00 | 719.62 | 19.89 | 80.17 | 389.50 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:00 | 1020.56 | 13.89 | 0.00 | 392.00 | 650.40 | 17.45 | 0.50 | 354.17 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:49 | 967.37 | 14.16 | 0.00 | 314.83 | 613.21 | 17.61 | 0.00 | 265.33 |
October | 245.33 | 0.55 | 0.48 | 01-OCT-08:30 | 719.50 | 12.08 | 0.00 | 262.00 | 455.43 | 15.62 | 0.00 | 186.83 |
November | 242.67 | 0.57 | 0.48 | 01-NOV-10:50 | 552.99 | 9.88 | 0.00 | 193.50 | 315.68 | 13.31 | 0.00 | 83.67 |
December | 160.33 | 0.60 | 0.48 | 01-DEC-10:09 | 480.89 | 9.80 | 0.00 | 156.33 | 294.00 | 13.50 | 0.00 | 51.33 |
Annual Sum or Average | 3714.00 | 0.53 | 960.29 | 13.82 | 177.33 | 3601.67 | 588.10 | 17.18 | 187.33 | 2841.17 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 480.89 | 9.51 | 0.00 | 156.33 | 292.82 | 13.00 | 0.00 | 51.33 | |
Maximum of Months | 471.00 | 0.60 | 0.48 | 1361.03 | 17.81 | 78.00 | 424.00 | 832.82 | 20.88 | 80.17 | 389.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.54 | 0.48 | 01-JAN-13:20 | 1083.08 | 20.00 | 79.17 | 203.83 | 591.37 | 20.72 | 64.33 | 145.50 |
February | 259.50 | 0.53 | 0.48 | 01-FEB-09:30 | 1528.36 | 19.35 | 66.50 | 232.33 | 813.21 | 21.16 | 59.83 | 190.33 |
March | 247.00 | 0.52 | 0.48 | 01-MAR-08:30 | 2443.29 | 21.62 | 78.17 | 307.67 | 1339.06 | 22.55 | 59.83 | 258.67 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:40 | 2923.24 | 20.20 | 105.33 | 346.50 | 1315.63 | 20.02 | 51.00 | 313.50 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-07:49 | 3018.00 | 16.84 | 52.17 | 393.00 | 1665.55 | 17.68 | 0.00 | 361.17 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-06:19 | 3089.44 | 16.46 | 42.83 | 404.00 | 1443.80 | 17.46 | 0.00 | 367.50 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-09:50 | 3385.22 | 15.58 | 58.83 | 406.50 | 1537.53 | 16.26 | 3.67 | 367.83 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-06:30 | 3217.16 | 18.53 | 75.83 | 384.00 | 1905.28 | 19.94 | 50.17 | 350.83 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:00 | 3555.86 | 22.42 | 100.50 | 316.83 | 2030.35 | 23.31 | 76.83 | 280.00 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-08:50 | 2438.38 | 22.22 | 89.83 | 275.17 | 1130.22 | 22.71 | 64.67 | 232.33 |
November | 242.67 | 0.54 | 0.48 | 01-NOV-10:09 | 1151.27 | 19.31 | 70.50 | 211.50 | 617.10 | 20.01 | 52.33 | 150.17 |
December | 160.33 | 0.55 | 0.48 | 01-DEC-09:00 | 1136.73 | 19.91 | 48.67 | 186.83 | 618.54 | 20.66 | 45.83 | 111.67 |
Annual Sum or Average | 3714.00 | 0.52 | 2617.70 | 18.95 | 868.33 | 3668.17 | 1345.29 | 19.77 | 528.50 | 3129.50 | ||
Minimum of Months | 160.33 | 0.51 | 0.48 | 1083.08 | 15.58 | 42.83 | 186.83 | 591.37 | 16.26 | 0.00 | 111.67 | |
Maximum of Months | 471.00 | 0.55 | 0.48 | 3555.86 | 22.42 | 105.33 | 406.50 | 2030.35 | 23.31 | 76.83 | 367.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.52 | 0.48 | 01-JAN-09:00 | 2769.69 | 31.99 | 220.33 | 219.83 | 2242.89 | 33.13 | 221.33 | 190.33 |
February | 259.50 | 0.51 | 0.48 | 01-FEB-08:39 | 4726.05 | 32.96 | 239.00 | 244.50 | 2134.77 | 27.47 | 156.50 | 223.17 |
March | 247.00 | 0.51 | 0.48 | 01-MAR-07:40 | 7828.32 | 32.30 | 208.50 | 313.33 | 1779.05 | 17.98 | 8.50 | 272.50 |
April | 379.50 | 0.52 | 0.48 | 01-APR-07:10 | 2257.87 | 13.81 | 0.00 | 346.00 | 1301.20 | 17.29 | 0.67 | 312.67 |
May | 427.83 | 0.52 | 0.48 | 01-MAY-07:19 | 2072.76 | 13.81 | 0.00 | 386.83 | 1178.61 | 17.24 | 0.00 | 349.67 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-06:10 | 1828.55 | 13.68 | 0.00 | 396.67 | 1091.22 | 17.11 | 0.00 | 352.00 |
July | 471.00 | 0.54 | 0.48 | 01-JUL-05:40 | 1630.15 | 12.30 | 0.00 | 396.83 | 993.02 | 15.76 | 0.00 | 348.67 |
August | 366.67 | 0.53 | 0.48 | 01-AUG-06:10 | 1930.57 | 13.40 | 0.00 | 375.50 | 1198.37 | 16.94 | 1.33 | 333.00 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:40 | 3069.14 | 16.43 | 27.00 | 320.67 | 1574.11 | 18.14 | 11.00 | 292.00 |
October | 245.33 | 0.51 | 0.48 | 01-OCT-07:00 | 7270.87 | 34.05 | 220.33 | 285.00 | 2056.58 | 19.37 | 26.17 | 259.00 |
November | 242.67 | 0.51 | 0.48 | 01-NOV-08:20 | 3094.55 | 31.49 | 221.67 | 225.50 | 2512.60 | 32.77 | 226.17 | 197.50 |
December | 160.33 | 0.51 | 0.48 | 01-DEC-09:39 | 3728.33 | 34.96 | 149.17 | 208.17 | 3208.42 | 36.43 | 149.67 | 171.50 |
Annual Sum or Average | 3714.00 | 0.52 | 3172.03 | 20.91 | 1286.00 | 3718.83 | 1600.47 | 20.85 | 801.33 | 3302.00 | ||
Minimum of Months | 160.33 | 0.51 | 0.48 | 1630.15 | 12.30 | 0.00 | 208.17 | 993.02 | 15.76 | 0.00 | 171.50 | |
Maximum of Months | 471.00 | 0.54 | 0.48 | 7828.32 | 34.96 | 239.00 | 396.83 | 3208.42 | 36.43 | 226.17 | 352.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.55 | 0.48 | 01-JAN-10:09 | 953.19 | 18.34 | 61.33 | 202.50 | 598.96 | 20.65 | 71.33 | 138.83 |
February | 259.50 | 0.53 | 0.48 | 01-FEB-08:30 | 1555.90 | 20.48 | 81.00 | 230.67 | 833.16 | 21.27 | 61.50 | 188.33 |
March | 247.00 | 0.52 | 0.48 | 01-MAR-07:30 | 2801.15 | 23.11 | 91.50 | 304.83 | 1262.01 | 22.33 | 51.50 | 261.17 |
April | 379.50 | 0.51 | 0.48 | 01-APR-06:19 | 2898.31 | 20.41 | 105.17 | 349.00 | 1663.29 | 22.51 | 91.67 | 314.17 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-06:00 | 2996.88 | 20.38 | 132.50 | 393.50 | 1353.55 | 20.93 | 79.50 | 357.00 |
June | 375.17 | 0.52 | 0.48 | 01-JUN-05:10 | 3156.41 | 20.38 | 98.83 | 405.50 | 1778.89 | 21.55 | 73.67 | 364.67 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-04:00 | 2960.00 | 20.04 | 148.50 | 411.17 | 1385.18 | 20.90 | 99.33 | 380.00 |
August | 366.67 | 0.52 | 0.48 | 01-AUG-05:30 | 3451.33 | 21.52 | 116.33 | 380.67 | 1551.03 | 21.18 | 66.50 | 345.33 |
September | 301.17 | 0.50 | 0.48 | 01-SEP-07:40 | 2837.06 | 21.12 | 82.67 | 324.00 | 1610.82 | 22.31 | 61.33 | 290.50 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-07:49 | 2524.98 | 21.43 | 83.00 | 273.50 | 1156.40 | 22.00 | 57.83 | 232.83 |
November | 242.67 | 0.54 | 0.48 | 01-NOV-08:09 | 1182.21 | 19.77 | 78.83 | 210.67 | 630.37 | 20.54 | 62.83 | 155.50 |
December | 160.33 | 0.54 | 0.48 | 01-DEC-09:39 | 1116.25 | 21.00 | 56.33 | 186.83 | 615.97 | 21.60 | 52.50 | 114.83 |
Annual Sum or Average | 3714.00 | 0.52 | 2554.65 | 20.63 | 1136.00 | 3672.83 | 1289.65 | 21.46 | 829.50 | 3143.17 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 953.19 | 18.34 | 56.33 | 186.83 | 598.96 | 20.54 | 51.50 | 114.83 | |
Maximum of Months | 471.00 | 0.55 | 0.48 | 3451.33 | 23.11 | 148.50 | 411.17 | 1778.89 | 22.51 | 99.33 | 380.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.59 | 0.48 | 02-JAN-11:30 | 513.61 | 9.48 | 0.00 | 180.50 | 293.31 | 12.98 | 0.00 | 68.50 |
February | 259.50 | 0.55 | 0.48 | 01-FEB-09:30 | 654.70 | 11.05 | 0.00 | 216.50 | 387.71 | 14.56 | 0.00 | 143.33 |
March | 247.00 | 0.53 | 0.48 | 01-MAR-08:30 | 887.93 | 12.94 | 0.00 | 298.83 | 549.83 | 16.43 | 0.00 | 229.83 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:19 | 1041.35 | 13.65 | 0.00 | 349.00 | 630.70 | 17.06 | 0.00 | 310.17 |
May | 427.83 | 0.50 | 0.48 | 01-MAY-07:19 | 1294.83 | 16.15 | 39.17 | 400.33 | 771.18 | 19.31 | 44.67 | 371.33 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-05:40 | 1362.28 | 17.78 | 60.17 | 414.33 | 833.87 | 20.87 | 62.00 | 388.50 |
July | 471.00 | 0.52 | 0.48 | 01-JUL-05:10 | 1155.42 | 16.74 | 78.00 | 424.00 | 720.50 | 19.87 | 80.00 | 390.00 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-05:00 | 1021.41 | 13.86 | 0.00 | 392.00 | 651.17 | 17.43 | 0.50 | 354.33 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:49 | 968.23 | 14.13 | 0.00 | 315.00 | 614.00 | 17.60 | 0.00 | 266.50 |
October | 245.33 | 0.55 | 0.48 | 01-OCT-08:30 | 720.13 | 12.05 | 0.00 | 262.00 | 456.02 | 15.60 | 0.00 | 187.50 |
November | 242.67 | 0.57 | 0.48 | 01-NOV-10:39 | 553.75 | 9.85 | 0.00 | 193.50 | 316.21 | 13.30 | 0.00 | 84.00 |
December | 160.33 | 0.60 | 0.48 | 01-DEC-10:09 | 481.35 | 9.77 | 0.00 | 156.50 | 294.42 | 13.49 | 0.00 | 51.33 |
Annual Sum or Average | 3714.00 | 0.53 | 961.27 | 13.79 | 177.33 | 3602.50 | 588.90 | 17.17 | 187.17 | 2845.33 | ||
Minimum of Months | 160.33 | 0.50 | 0.48 | 481.35 | 9.48 | 0.00 | 156.50 | 293.31 | 12.98 | 0.00 | 51.33 | |
Maximum of Months | 471.00 | 0.60 | 0.48 | 1362.28 | 17.78 | 78.00 | 424.00 | 833.87 | 20.87 | 80.00 | 390.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.54 | 0.48 | 01-JAN-13:20 | 1084.05 | 19.98 | 79.17 | 203.83 | 592.17 | 20.71 | 64.00 | 145.67 |
February | 259.50 | 0.53 | 0.48 | 01-FEB-09:30 | 1529.56 | 19.32 | 66.50 | 232.33 | 814.26 | 21.15 | 59.50 | 190.50 |
March | 247.00 | 0.52 | 0.48 | 01-MAR-08:30 | 2444.91 | 21.59 | 78.17 | 307.83 | 1340.55 | 22.54 | 59.67 | 258.67 |
April | 379.50 | 0.51 | 0.48 | 01-APR-07:40 | 2925.20 | 20.17 | 105.33 | 346.50 | 1317.25 | 20.00 | 51.00 | 314.00 |
May | 427.83 | 0.51 | 0.48 | 01-MAY-07:49 | 3020.43 | 16.81 | 52.17 | 393.00 | 1667.40 | 17.66 | 0.00 | 361.50 |
June | 375.17 | 0.51 | 0.48 | 01-JUN-06:19 | 3091.48 | 16.43 | 42.83 | 404.17 | 1445.48 | 17.45 | 0.00 | 367.67 |
July | 471.00 | 0.53 | 0.48 | 01-JUL-09:50 | 3386.98 | 15.55 | 58.83 | 406.50 | 1538.98 | 16.24 | 3.67 | 368.17 |
August | 366.67 | 0.51 | 0.48 | 01-AUG-06:30 | 3218.60 | 18.50 | 75.83 | 384.00 | 1906.71 | 19.93 | 50.17 | 351.00 |
September | 301.17 | 0.51 | 0.48 | 01-SEP-07:00 | 3557.60 | 22.39 | 100.50 | 316.67 | 2032.08 | 23.29 | 76.83 | 280.17 |
October | 245.33 | 0.53 | 0.48 | 01-OCT-08:50 | 2439.49 | 22.19 | 89.83 | 275.33 | 1131.42 | 22.70 | 64.50 | 232.50 |
November | 242.67 | 0.54 | 0.48 | 01-NOV-10:09 | 1152.34 | 19.28 | 70.50 | 211.67 | 617.97 | 20.00 | 52.17 | 150.50 |
December | 160.33 | 0.55 | 0.48 | 01-DEC-09:00 | 1137.42 | 19.88 | 48.67 | 186.83 | 619.30 | 20.65 | 45.17 | 111.83 |
Annual Sum or Average | 3714.00 | 0.52 | 2619.32 | 18.92 | 868.33 | 3668.67 | 1346.69 | 19.76 | 526.67 | 3132.17 | ||
Minimum of Months | 160.33 | 0.51 | 0.48 | 1084.05 | 15.55 | 42.83 | 186.83 | 592.17 | 16.24 | 0.00 | 111.83 | |
Maximum of Months | 471.00 | 0.55 | 0.48 | 3557.60 | 22.39 | 105.33 | 406.50 | 2032.08 | 23.29 | 76.83 | 368.17 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.496706E+10 | 23784.45 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.276487E+10 | 19296.50 | 18-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.322297E+09 | 13911.81 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 37928533.56 | 6808.49 | 19-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8347774.33 | 2855.07 | 18-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.661675E+09 | 10663.86 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.205415E+10 | 16600.45 | 26-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.496706E+10 | 23784.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 51479814.73 | 4028.42 | 09-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3671389.89 | 790.21 | 18-FEB-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 55151204.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 51479814.73 | 4028.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.266919E+09 | 6404.98 | 17-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 93520162.96 | 5338.69 | 18-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2560103.47 | 334.06 | 01-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11983175.71 | 734.03 | 30-NOV-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119918E+09 | 2886.16 | 22-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.494901E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.266919E+09 | 6404.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.465566E+09 | 16256.20 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154377E+09 | 16271.19 | 21-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5766565.14 | 2500.10 | 06-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 39776035.19 | 7368.79 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.173442E+09 | 16306.71 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.838927E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.465566E+09 | 16306.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 16022003.66 | 1223.67 | 09-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 16022003.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16022003.66 | 1223.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.103102E+12 | 267921.16 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.606634E+11 | 221825.41 | 18-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137503E+11 | 170963.12 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.476822E+10 | 119811.71 | 19-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.300098E+09 | 44746.05 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.126221E+10 | 49837.23 | 16-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.317026E+11 | 171910.58 | 13-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.733083E+11 | 239360.04 | 26-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.288857E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.103102E+12 | 267921.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.420427E+10 | 450438.98 | 02-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 76761543.21 | 26990.15 | 21-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.219136E+09 | 97287.74 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.450017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.420427E+10 | 450438.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.265024E+11 | 120748.36 | 02-JAN-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130232E+11 | 119524.26 | 10-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.339294E+10 | 129523.26 | 02-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.697785E+09 | 129171.24 | 19-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2891893.33 | 3688.30 | 18-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.109317E+10 | 118756.56 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.753261E+10 | 119706.37 | 13-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195566E+11 | 119711.24 | 26-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.718016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.265024E+11 | 129523.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.266338E+11 | 156559.71 | 23-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135722E+11 | 156507.76 | 21-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.440223E+10 | 156134.68 | 06-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.102467E+10 | 115489.55 | 19-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139380E+09 | 26565.76 | 18-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 62665074.10 | 19314.07 | 27-SEP-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.248475E+10 | 97379.05 | 31-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107817E+11 | 156283.86 | 27-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.214417E+11 | 156480.54 | 18-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.805430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.266338E+11 | 156559.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.248034E+11 | 226244.91 | 02-JAN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.111546E+11 | 225269.59 | 23-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.368846E+10 | 225237.58 | 06-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.120178E+10 | 98524.63 | 18-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.100869E+09 | 24837.01 | 18-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 22703787.78 | 5506.47 | 27-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166158E+10 | 88854.90 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.893907E+10 | 225192.37 | 15-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.197619E+11 | 225734.15 | 18-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.713343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.248034E+11 | 226244.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.209143E+11 | 151436.75 | 02-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100835E+11 | 151055.95 | 15-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.307948E+10 | 122335.67 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.766169E+09 | 57137.01 | 19-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 75176201.19 | 22435.20 | 18-MAY-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5543149.96 | 1946.09 | 28-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.156121E+10 | 43870.46 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.755974E+10 | 151075.48 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156479E+11 | 151416.81 | 26-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.596929E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.209143E+11 | 151436.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.124397E+11 | 30419.55 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.793926E+10 | 26842.63 | 18-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.300462E+10 | 21722.21 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.109458E+10 | 16447.81 | 19-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.168992E+09 | 8454.03 | 18-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 19557124.10 | 2698.13 | 27-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.507415E+09 | 9360.29 | 16-OCT-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.496616E+10 | 21181.26 | 13-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.101419E+11 | 27117.01 | 26-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.402822E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.124397E+11 | 30419.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.575464E+10 | 77391.97 | 23-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.259214E+10 | 77357.63 | 21-FEB-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.510914E+09 | 77429.80 | 06-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10620083.65 | 3459.72 | 17-APR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.238601E+09 | 77160.16 | 23-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.171273E+10 | 77419.25 | 13-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.386121E+10 | 77416.20 | 26-DEC-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146809E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.575464E+10 | 77429.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.595079E+10 | 13419.96 | 30-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.375427E+10 | 13369.14 | 06-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174835E+10 | 13392.33 | 13-MAR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.600803E+09 | 13285.64 | 04-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 87333169.24 | 13214.75 | 18-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4563933.85 | 986.14 | 14-JUN-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 56319694.82 | 12148.30 | 27-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.916744E+09 | 13352.63 | 16-OCT-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.280555E+10 | 13420.23 | 27-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.512098E+10 | 13419.75 | 18-DEC-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210457E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.595079E+10 | 13420.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.465512E+10 | 17964.92 | 30-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.277602E+10 | 17976.05 | 06-FEB-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137333E+10 | 17965.98 | 06-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.441569E+09 | 17924.41 | 24-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134347E+09 | 17916.22 | 18-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 15794632.84 | 3239.45 | 14-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16348.38 | 54.49 | 03-AUG-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 99782221.86 | 10683.17 | 27-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.875774E+09 | 17935.31 | 31-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.247588E+10 | 17966.24 | 27-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.408774E+10 | 17976.65 | 11-DEC-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169354E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.465512E+10 | 17976.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.526177E+10 | 26583.54 | 30-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.296875E+10 | 26599.94 | 06-FEB-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.165266E+10 | 26585.08 | 06-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.712734E+09 | 26513.45 | 18-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.220196E+09 | 26511.78 | 18-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 31161459.84 | 2581.56 | 15-JUN-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 92024788.16 | 11870.33 | 27-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.922946E+09 | 26532.45 | 23-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.283916E+10 | 26585.92 | 27-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.464428E+10 | 26600.85 | 11-DEC-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.193457E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.526177E+10 | 26600.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.390263E+10 | 18214.29 | 30-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.227647E+10 | 18187.51 | 06-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.119494E+10 | 18188.08 | 06-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.425230E+09 | 14965.09 | 19-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.118378E+09 | 16951.15 | 18-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9095604.42 | 1345.37 | 14-JUN-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 53169631.50 | 2475.24 | 18-SEP-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.709478E+09 | 16867.25 | 16-OCT-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.201519E+10 | 18211.52 | 24-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.326101E+10 | 18193.39 | 18-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139656E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.390263E+10 | 18214.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.123912E+10 | 12109.21 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.408474E+09 | 11427.51 | 18-FEB-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16072024.71 | 9729.54 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 861731.23 | 1251.63 | 05-APR-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3150634.85 | 2157.10 | 11-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1560.72 | 0.94 | 10-JUN-06:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 374.86 | 0.87 | 05-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 68.11 | 0.56 | 08-AUG-06:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 169.35 | 1.37 | 28-SEP-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 217464.17 | 1093.81 | 25-OCT-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 745818.97 | 2485.95 | 30-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 42737582.33 | 11296.96 | 26-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171138E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 68.11 | 0.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.123912E+10 | 12109.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 21.23 | 21.23 | 0.35 | 02-JAN-05:20 | 0.35 | 0.00 |
February | 0.00 | 0.00 | 0.807767E+09 | 0.807767E+09 | 55219.18 | 27-FEB-15:00 | 55219.18 | 0.01 |
March | 0.00 | 0.00 | 0.107148E+10 | 0.107148E+10 | 29096.43 | 18-MAR-16:00 | 29096.43 | 0.02 |
April | 0.00 | 0.00 | 0.103402E+11 | 0.103402E+11 | 125450.24 | 27-APR-14:30 | 125450.24 | 0.05 |
May | 0.00 | 0.00 | 0.167513E+11 | 0.167488E+11 | 101267.30 | 04-MAY-15:00 | 101267.30 | 0.16 |
June | 0.00 | 0.00 | 0.328265E+11 | 0.328208E+11 | 113232.58 | 28-JUN-15:20 | 113232.58 | 0.33 |
July | 0.00 | 0.00 | 0.597965E+11 | 0.591635E+11 | 144180.94 | 31-JUL-15:50 | 127014.30 | 0.52 |
August | 0.00 | 0.00 | 0.817936E+11 | 0.796977E+11 | 154907.46 | 29-AUG-14:30 | 136684.67 | 0.63 |
September | 0.00 | 0.00 | 0.259091E+11 | 0.256042E+11 | 133961.79 | 11-SEP-15:03 | 133961.79 | 0.34 |
October | 0.00 | 0.00 | 0.478266E+10 | 0.478266E+10 | 78848.81 | 04-OCT-15:00 | 78848.81 | 0.05 |
November | 0.00 | 0.00 | 0.690295E+09 | 0.690295E+09 | 38032.51 | 04-NOV-14:00 | 38032.51 | 0.01 |
December | 0.00 | 0.00 | 525.30 | 525.30 | 0.71 | 26-DEC-06:15 | 0.71 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.234769E+12 | 0.231728E+12 | 0.18 | |||
Minimum of Months | 0.00 | 0.00 | 21.23 | 21.23 | 0.35 | 0.35 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.817936E+11 | 0.796977E+11 | 154907.46 | 136684.67 | 0.63 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 47618.03 | 47618.03 | 2.75 | 02-JAN-06:50 | 2.75 | 0.00 |
February | 0.00 | 0.00 | 0.513887E+10 | 0.513887E+10 | 366538.01 | 27-FEB-15:00 | 366538.01 | 0.01 |
March | 0.00 | 0.00 | 0.776076E+10 | 0.776076E+10 | 269642.98 | 18-MAR-16:00 | 269642.98 | 0.02 |
April | 0.00 | 0.00 | 0.772722E+11 | 0.772722E+11 | 1041239.68 | 27-APR-14:40 | 1041239.68 | 0.05 |
May | 0.00 | 0.00 | 0.143975E+12 | 0.143943E+12 | 937290.77 | 04-MAY-15:00 | 937290.77 | 0.16 |
June | 0.00 | 0.00 | 0.266206E+12 | 0.266182E+12 | 1003139.12 | 28-JUN-15:30 | 1003139.12 | 0.32 |
July | 0.00 | 0.00 | 0.468342E+12 | 0.465015E+12 | 1244905.61 | 31-JUL-16:00 | 1073107.72 | 0.48 |
August | 0.00 | 0.00 | 0.620347E+12 | 0.606423E+12 | 1333875.81 | 29-AUG-14:30 | 1173837.19 | 0.53 |
September | 0.00 | 0.00 | 0.228585E+12 | 0.224979E+12 | 1061541.21 | 11-SEP-15:03 | 1061541.21 | 0.34 |
October | 0.00 | 0.00 | 0.375576E+11 | 0.375576E+11 | 684119.76 | 04-OCT-15:00 | 684119.76 | 0.05 |
November | 0.00 | 0.00 | 0.601908E+10 | 0.601908E+10 | 333008.51 | 04-NOV-14:10 | 333008.51 | 0.03 |
December | 0.00 | 0.00 | 50521.68 | 50521.68 | 2.96 | 26-DEC-06:02 | 2.96 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.186120E+13 | 0.184029E+13 | 0.17 | |||
Minimum of Months | 0.00 | 0.00 | 47618.03 | 47618.03 | 2.75 | 2.75 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.620347E+12 | 0.606423E+12 | 1333875.81 | 1173837.19 | 0.53 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 53792.68 | 53792.68 | 446.77 | 09-JAN-04:22 | 446.77 | 0.00 |
February | 0.00 | 0.00 | 0.430738E+09 | 0.430738E+09 | 29511.97 | 27-FEB-15:00 | 29511.97 | 0.01 |
March | 0.00 | 0.00 | 0.664518E+09 | 0.664518E+09 | 26393.94 | 18-MAR-16:00 | 26393.94 | 0.02 |
April | 0.00 | 0.00 | 0.801913E+10 | 0.801913E+10 | 122332.90 | 27-APR-14:40 | 122332.90 | 0.05 |
May | 0.00 | 0.00 | 0.148504E+11 | 0.148471E+11 | 103669.18 | 04-MAY-15:00 | 103669.18 | 0.15 |
June | 0.00 | 0.00 | 0.280522E+11 | 0.280503E+11 | 120439.27 | 28-JUN-15:20 | 120439.27 | 0.31 |
July | 0.00 | 0.00 | 0.502032E+11 | 0.498710E+11 | 145155.25 | 31-JUL-16:00 | 126928.13 | 0.46 |
August | 0.00 | 0.00 | 0.655530E+11 | 0.642504E+11 | 151354.07 | 10-AUG-15:40 | 139833.77 | 0.51 |
September | 0.00 | 0.00 | 0.224069E+11 | 0.221718E+11 | 110282.69 | 12-SEP-13:27 | 103331.63 | 0.32 |
October | 0.00 | 0.00 | 0.323837E+10 | 0.323837E+10 | 67765.10 | 04-OCT-15:00 | 67765.10 | 0.04 |
November | 0.00 | 0.00 | 0.576840E+09 | 0.576840E+09 | 32724.13 | 04-NOV-14:00 | 32724.13 | 0.01 |
December | 0.00 | 0.00 | 19369.25 | 19369.25 | 62.86 | 26-DEC-04:30 | 62.86 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.193995E+12 | 0.192120E+12 | 0.16 | |||
Minimum of Months | 0.00 | 0.00 | 19369.25 | 19369.25 | 62.86 | 62.86 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.655530E+11 | 0.642504E+11 | 151354.07 | 139833.77 | 0.51 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 48045070.28 | 48045070.28 | 8179.44 | 11-JAN-07:12 | 8179.44 | 0.00 |
February | 0.00 | 0.00 | 0.156443E+10 | 0.131604E+10 | 49421.53 | 24-FEB-07:12 | 33729.21 | 0.05 |
March | 0.00 | 0.00 | 0.199320E+10 | 0.193854E+10 | 37961.91 | 10-MAR-07:12 | 20935.22 | 0.03 |
April | 0.00 | 0.00 | 0.497688E+10 | 0.496149E+10 | 63126.32 | 27-APR-15:00 | 63126.32 | 0.05 |
May | 0.00 | 0.00 | 0.120008E+11 | 0.119672E+11 | 61981.54 | 15-MAY-16:00 | 61981.54 | 0.15 |
June | 0.00 | 0.00 | 0.221279E+11 | 0.217454E+11 | 65037.04 | 12-JUN-06:25 | 35848.92 | 0.28 |
July | 0.00 | 0.00 | 0.373870E+11 | 0.358228E+11 | 95098.58 | 31-JUL-10:10 | 73712.29 | 0.39 |
August | 0.00 | 0.00 | 0.480967E+11 | 0.455383E+11 | 85608.78 | 30-AUG-06:23 | 40395.45 | 0.43 |
September | 0.00 | 0.00 | 0.170712E+11 | 0.165169E+11 | 78943.23 | 11-SEP-15:03 | 78943.23 | 0.28 |
October | 0.00 | 0.00 | 0.265960E+10 | 0.263208E+10 | 44749.57 | 04-OCT-15:00 | 44749.57 | 0.03 |
November | 0.00 | 0.00 | 0.105540E+10 | 0.805155E+09 | 42059.84 | 04-NOV-06:11 | 26752.38 | 0.03 |
December | 0.00 | 0.00 | 0.155311E+09 | 0.153337E+09 | 24903.39 | 16-DEC-07:13 | 15016.28 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.149136E+12 | 0.143445E+12 | 0.15 | |||
Minimum of Months | 0.00 | 0.00 | 48045070.28 | 48045070.28 | 8179.44 | 8179.44 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.480967E+11 | 0.455383E+11 | 95098.58 | 78943.23 | 0.43 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.452884E+10 | 0.452882E+10 | 3131.09 | 09-JAN-12:00 | 3131.09 | 0.00 |
February | 0.00 | 0.00 | 0.680323E+10 | 0.676628E+10 | 18117.71 | 27-FEB-15:00 | 18117.71 | 0.00 |
March | 0.00 | 0.00 | 0.118029E+11 | 0.114231E+11 | 125841.07 | 18-MAR-16:00 | 125841.07 | 0.00 |
April | 0.00 | 0.00 | 0.763553E+11 | 0.720775E+11 | 409379.61 | 27-APR-16:00 | 409379.61 | 0.00 |
May | 0.00 | 0.00 | 0.432714E+10 | 0.409976E+10 | 84814.98 | 05-MAY-16:00 | 73222.97 | 0.00 |
June | 0.00 | 0.00 | 0.331919E+11 | 0.316849E+11 | 215179.78 | 28-JUN-17:00 | 215179.78 | 0.00 |
July | 0.00 | 0.00 | 0.208127E+12 | 0.177035E+12 | 358106.07 | 27-JUL-16:00 | 290586.36 | 0.00 |
August | 0.00 | 0.00 | 0.532851E+12 | 0.426196E+12 | 474911.20 | 29-AUG-11:00 | 390184.15 | 0.00 |
September | 0.00 | 0.00 | 0.343313E+10 | 0.289425E+10 | 86937.91 | 22-SEP-16:00 | 73808.63 | 0.00 |
October | 0.00 | 0.00 | 0.380397E+10 | 0.372888E+10 | 71973.06 | 04-OCT-15:00 | 71973.06 | 0.00 |
November | 0.00 | 0.00 | 0.994902E+10 | 0.865023E+10 | 180067.31 | 04-NOV-15:00 | 134974.22 | 0.00 |
December | 0.00 | 0.00 | 0.130115E+11 | 0.121172E+11 | 6019.55 | 18-DEC-19:40 | 5486.60 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.908186E+12 | 0.761201E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.343313E+10 | 0.289425E+10 | 3131.09 | 3131.09 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.532851E+12 | 0.426196E+12 | 474911.20 | 409379.61 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.396576E+10 | 0.396544E+10 | 2167.61 | 05-JAN-16:10 | 2167.61 | 0.00 |
February | 0.00 | 0.00 | 0.873578E+10 | 0.872536E+10 | 4452.33 | 27-FEB-16:20 | 4435.03 | 0.00 |
March | 0.00 | 0.00 | 0.153258E+11 | 0.153177E+11 | 7572.79 | 31-MAR-24:00 | 7572.79 | 0.00 |
April | 0.00 | 0.00 | 0.200563E+11 | 0.200430E+11 | 8699.67 | 26-APR-18:00 | 8699.67 | 0.00 |
May | 0.00 | 0.00 | 0.566063E+10 | 0.562422E+10 | 4043.12 | 31-MAY-24:00 | 4035.34 | 0.00 |
June | 0.00 | 0.00 | 0.106230E+11 | 0.105707E+11 | 5914.12 | 30-JUN-24:00 | 5912.27 | 0.00 |
July | 0.00 | 0.00 | 0.163361E+11 | 0.162221E+11 | 7865.23 | 31-JUL-23:33 | 7834.80 | 0.00 |
August | 0.00 | 0.00 | 0.213738E+11 | 0.212136E+11 | 9249.79 | 06-AUG-18:38 | 9249.79 | 0.00 |
September | 0.00 | 0.00 | 0.565297E+10 | 0.556174E+10 | 3888.76 | 30-SEP-24:00 | 3887.66 | 0.00 |
October | 0.00 | 0.00 | 0.104455E+11 | 0.104230E+11 | 5593.40 | 31-OCT-24:00 | 5593.40 | 0.00 |
November | 0.00 | 0.00 | 0.147086E+11 | 0.146850E+11 | 6322.37 | 12-NOV-16:00 | 6322.37 | 0.00 |
December | 0.00 | 0.00 | 0.200272E+11 | 0.200248E+11 | 8142.66 | 10-DEC-15:50 | 8142.66 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.152911E+12 | 0.152377E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.396576E+10 | 0.396544E+10 | 2167.61 | 2167.61 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.213738E+11 | 0.212136E+11 | 9249.79 | 9249.79 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.155073E+11 | 0.155073E+11 | 17308.96 | 05-JAN-16:20 | 17308.96 | 0.00 |
February | 0.00 | 0.00 | 0.662069E+11 | 0.661051E+11 | 40764.67 | 27-FEB-16:20 | 40586.75 | 0.00 |
March | 0.00 | 0.00 | 0.132398E+12 | 0.132318E+12 | 67008.82 | 31-MAR-23:50 | 67008.82 | 0.00 |
April | 0.00 | 0.00 | 0.182508E+12 | 0.182374E+12 | 82915.02 | 26-APR-18:00 | 82915.02 | 0.00 |
May | 0.00 | 0.00 | 0.477097E+11 | 0.473539E+11 | 37722.33 | 31-MAY-23:40 | 37605.36 | 0.00 |
June | 0.00 | 0.00 | 0.967580E+11 | 0.962401E+11 | 55495.64 | 30-JUN-24:00 | 55475.27 | 0.00 |
July | 0.00 | 0.00 | 0.152970E+12 | 0.151842E+12 | 75668.75 | 31-JUL-23:57 | 75390.17 | 0.00 |
August | 0.00 | 0.00 | 0.201698E+12 | 0.200108E+12 | 86648.01 | 06-AUG-18:35 | 86648.01 | 0.00 |
September | 0.00 | 0.00 | 0.480755E+11 | 0.471869E+11 | 34592.72 | 30-SEP-23:50 | 34574.44 | 0.00 |
October | 0.00 | 0.00 | 0.875591E+11 | 0.873364E+11 | 47191.37 | 31-OCT-24:00 | 47191.37 | 0.00 |
November | 0.00 | 0.00 | 0.122497E+12 | 0.122263E+12 | 57717.75 | 04-NOV-16:00 | 56524.91 | 0.00 |
December | 0.00 | 0.00 | 0.168286E+12 | 0.168262E+12 | 73472.90 | 05-DEC-16:00 | 73472.90 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.132217E+13 | 0.131690E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.155073E+11 | 0.155073E+11 | 17308.96 | 17308.96 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.201698E+12 | 0.200108E+12 | 86648.01 | 86648.01 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.579462E+09 | 0.579462E+09 | 1592.85 | 05-JAN-16:20 | 1592.85 | 0.00 |
February | 0.00 | 0.00 | 0.512817E+10 | 0.511812E+10 | 4041.87 | 27-FEB-16:30 | 4017.56 | 0.00 |
March | 0.00 | 0.00 | 0.120123E+11 | 0.120043E+11 | 6255.69 | 31-MAR-23:20 | 6255.69 | 0.00 |
April | 0.00 | 0.00 | 0.174973E+11 | 0.174840E+11 | 8369.37 | 26-APR-18:00 | 8369.37 | 0.00 |
May | 0.00 | 0.00 | 0.426955E+10 | 0.423422E+10 | 3701.34 | 31-MAY-23:20 | 3685.08 | 0.00 |
June | 0.00 | 0.00 | 0.943625E+10 | 0.938445E+10 | 5458.22 | 30-JUN-23:40 | 5454.70 | 0.00 |
July | 0.00 | 0.00 | 0.151649E+11 | 0.150521E+11 | 7551.20 | 31-JUL-23:33 | 7521.15 | 0.00 |
August | 0.00 | 0.00 | 0.200043E+11 | 0.198455E+11 | 8756.22 | 06-AUG-18:21 | 8756.22 | 0.00 |
September | 0.00 | 0.00 | 0.427203E+10 | 0.418450E+10 | 3040.66 | 30-SEP-23:20 | 3036.80 | 0.00 |
October | 0.00 | 0.00 | 0.763822E+10 | 0.761633E+10 | 4651.45 | 04-OCT-16:50 | 4651.45 | 0.00 |
November | 0.00 | 0.00 | 0.107267E+11 | 0.107035E+11 | 5685.87 | 04-NOV-16:00 | 5567.33 | 0.00 |
December | 0.00 | 0.00 | 0.150219E+11 | 0.150195E+11 | 7161.01 | 05-DEC-16:00 | 7161.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.121751E+12 | 0.121226E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.579462E+09 | 0.579462E+09 | 1592.85 | 1592.85 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.200043E+11 | 0.198455E+11 | 8756.22 | 8756.22 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 92925.32 | 1540253.77 | 02-JAN-05:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 55026.50 | 1104534.91 | 14-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 14115.94 | 1198589.93 | 06-MAR-05:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4512.60 | 701621.65 | 19-APR-05:02 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 498.75 | 192335.96 | 18-MAY-05:02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.52 | 5360.30 | 14-JUN-05:02 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.72 | 05-JUL-06:05 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.01 | 50.38 | 03-AUG-06:30 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 157.85 | 65911.87 | 27-SEP-05:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 4529.57 | 581332.12 | 30-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 32151.55 | 1281665.02 | 24-NOV-05:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 67893.25 | 1272344.29 | 18-DEC-05:11 |
Annual Sum or Average | 0.00 | 22534.04 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.72 | ||
Maximum of Months | 0.00 | 0.00 | 92925.32 | 1540253.77 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 51.48 | 5291.11 | 27-JAN-13:20 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 3525.18 | 515910.52 | 27-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 4587.35 | 342150.22 | 18-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 39948.70 | 1488738.80 | 27-APR-12:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 72218.80 | 1542051.00 | 04-MAY-14:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 137964.60 | 1491991.90 | 28-JUN-13:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 237317.83 | 1617625.85 | 31-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 314575.79 | 1716943.78 | 29-AUG-14:30 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 116930.00 | 1992781.51 | 12-SEP-13:27 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 18915.97 | 1007879.22 | 04-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 3443.11 | 427114.11 | 04-NOV-14:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 196.10 | 34585.55 | 16-DEC-07:13 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 79811.12 | 0.00 | ||||
Minimum of Months | 51.48 | 5291.11 | 0.00 | 0.00 | ||
Maximum of Months | 314575.79 | 1992781.51 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 5.61 | 2294.19 | 27-JAN-13:10 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 3257.14 | 537958.43 | 27-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 4278.82 | 340332.46 | 18-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 39842.55 | 1858455.04 | 27-APR-12:20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 71525.92 | 1680831.55 | 04-MAY-14:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 137849.89 | 1770279.40 | 28-JUN-12:40 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 236883.41 | 1921975.82 | 20-JUL-12:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 314178.97 | 1895822.70 | 15-AUG-12:50 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 119046.58 | 2168792.83 | 12-SEP-13:23 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 18512.33 | 1008866.83 | 04-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 3211.18 | 424752.08 | 04-NOV-14:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 66.88 | 45148.85 | 16-DEC-07:12 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 79722.51 | 0.00 | ||||
Minimum of Months | 5.61 | 2294.19 | 0.00 | 0.00 | ||
Maximum of Months | 314178.97 | 2168792.83 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 16180.23 | 32766.25 | 05-JAN-16:20 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 49600.14 | 200654.95 | 27-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 84676.73 | 465811.64 | 18-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 173050.27 | 1422401.38 | 27-APR-16:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 53848.40 | 575916.72 | 05-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 123114.67 | 952495.54 | 28-JUN-17:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 317812.17 | 1427811.41 | 24-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 596093.37 | 1717368.57 | 10-AUG-17:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 60370.90 | 577899.92 | 22-SEP-16:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 56859.93 | 403557.87 | 04-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 80972.12 | 586112.76 | 04-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 104045.07 | 120622.18 | 05-DEC-16:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 144189.14 | 0.00 | ||||
Minimum of Months | 16180.23 | 32766.25 | 0.00 | 0.00 | ||
Maximum of Months | 596093.37 | 1717368.57 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 14332.44 | 51088.77 | 31-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 14518.51 | 51150.74 | 10-FEB-13:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15258.69 | 50975.41 | 01-MAR-12:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 13905.14 | 49837.63 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 13845.35 | 48284.47 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 13658.88 | 46383.77 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 12219.48 | 44763.67 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 13273.49 | 44110.83 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 12602.96 | 45073.87 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12975.99 | 46819.59 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 13675.01 | 48660.90 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 13648.71 | 50167.43 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 13654.68 | ||||
Minimum of Months | 0.00 | 0.00 | 12219.48 | 44110.83 | ||
Maximum of Months | 0.00 | 0.00 | 15258.69 | 51150.74 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 3.51 | 5997.05 | 10-JAN-15:50 | 469.55 | 96798.36 | 10-JAN-16:10 |
February | 3274.62 | 560273.67 | 27-FEB-16:00 | 1786.75 | 126261.74 | 08-FEB-07:00 |
March | 3929.57 | 387361.18 | 18-MAR-16:00 | 1924.95 | 113831.32 | 28-MAR-06:00 |
April | 46735.11 | 2163959.63 | 27-APR-15:50 | 998.56 | 94565.60 | 17-APR-12:40 |
May | 81757.12 | 2094970.90 | 05-MAY-16:00 | 2302.88 | 93063.17 | 11-MAY-08:40 |
June | 160744.27 | 2220909.48 | 22-JUN-15:10 | 1531.72 | 74495.51 | 01-JUN-05:40 |
July | 293397.56 | 2919963.70 | 31-JUL-16:00 | 1075.04 | 79314.53 | 03-JUL-08:00 |
August | 420529.19 | 3387181.60 | 29-AUG-14:30 | 1161.05 | 59576.66 | 03-AUG-19:40 |
September | 140917.85 | 2593344.69 | 11-SEP-15:03 | 1171.81 | 77837.76 | 29-SEP-06:50 |
October | 20058.37 | 1157947.31 | 04-OCT-15:00 | 1161.50 | 89695.20 | 11-OCT-05:40 |
November | 3314.77 | 481536.92 | 04-NOV-14:10 | 1536.53 | 110191.54 | 18-NOV-07:12 |
December | 27.56 | 16276.72 | 14-DEC-11:40 | 1161.90 | 113146.44 | 21-DEC-05:53 |
Annual Sum or Average | 98777.64 | 1353.84 | ||||
Minimum of Months | 3.51 | 5997.05 | 469.55 | 59576.66 | ||
Maximum of Months | 420529.19 | 3387181.60 | 2302.88 | 126261.74 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.376328E+10 | 0.30 | 11183.03 | 02-JAN-06:03 | 1.21 |
February | 0.438998E+10 | 0.34 | 12704.32 | 27-FEB-15:00 | 1.31 |
March | 0.687505E+10 | 0.42 | 12931.71 | 14-MAR-15:00 | 1.33 |
April | 0.878479E+10 | 0.48 | 19489.57 | 27-APR-14:30 | 1.71 |
May | 0.801342E+10 | 0.45 | 15898.73 | 15-MAY-14:30 | 1.51 |
June | 0.979799E+10 | 0.52 | 19451.14 | 12-JUN-04:12 | 1.71 |
July | 0.119463E+11 | 0.58 | 20500.16 | 31-JUL-14:30 | 1.76 |
August | 0.139786E+11 | 0.66 | 20770.20 | 07-AUG-14:10 | 1.78 |
September | 0.819419E+10 | 0.45 | 20770.20 | 11-SEP-14:23 | 1.78 |
October | 0.678546E+10 | 0.40 | 15351.92 | 04-OCT-15:10 | 1.48 |
November | 0.525942E+10 | 0.36 | 11459.42 | 06-NOV-05:12 | 1.23 |
December | 0.509191E+10 | 0.34 | 11366.70 | 04-DEC-05:11 | 1.23 |
Annual Sum or Average | 0.928803E+11 | 0.44 | |||
Minimum of Months | 0.376328E+10 | 0.30 | 11183.03 | 1.21 | |
Maximum of Months | 0.139786E+11 | 0.66 | 20770.20 | 1.78 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.288239E+11 | 0.29 | 56290.89 | 02-JAN-05:11 | 0.85 |
February | 0.293867E+11 | 0.30 | 90615.07 | 28-FEB-06:03 | 1.12 |
March | 0.405570E+11 | 0.33 | 103529.34 | 01-MAR-06:02 | 1.22 |
April | 0.469069E+11 | 0.35 | 141285.92 | 27-APR-14:40 | 1.46 |
May | 0.592142E+11 | 0.40 | 127869.25 | 15-MAY-14:50 | 1.38 |
June | 0.674453E+11 | 0.44 | 131628.62 | 28-JUN-15:20 | 1.40 |
July | 0.776738E+11 | 0.46 | 149092.50 | 31-JUL-15:20 | 1.51 |
August | 0.887115E+11 | 0.49 | 174696.38 | 10-AUG-15:10 | 1.67 |
September | 0.625507E+11 | 0.41 | 192527.19 | 11-SEP-14:23 | 1.78 |
October | 0.433422E+11 | 0.33 | 122056.35 | 04-OCT-15:30 | 1.35 |
November | 0.305232E+11 | 0.29 | 90615.07 | 03-NOV-05:02 | 1.12 |
December | 0.295540E+11 | 0.28 | 40706.55 | 06-DEC-14:10 | 0.71 |
Annual Sum or Average | 0.604689E+12 | 0.36 | |||
Minimum of Months | 0.288239E+11 | 0.28 | 40706.55 | 0.71 | |
Maximum of Months | 0.887115E+11 | 0.49 | 192527.19 | 1.78 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.347070E+10 | 0.34 | 5023.93 | 02-JAN-05:11 | 0.75 |
February | 0.299157E+10 | 0.31 | 5023.93 | 06-FEB-05:11 | 0.75 |
March | 0.339656E+10 | 0.31 | 5644.53 | 14-MAR-15:40 | 0.80 |
April | 0.396931E+10 | 0.32 | 15281.26 | 27-APR-14:30 | 1.44 |
May | 0.513472E+10 | 0.36 | 14427.06 | 15-MAY-15:10 | 1.40 |
June | 0.616010E+10 | 0.40 | 14961.22 | 28-JUN-15:20 | 1.43 |
July | 0.741834E+10 | 0.42 | 17282.12 | 31-JUL-14:50 | 1.56 |
August | 0.825048E+10 | 0.45 | 19368.48 | 10-AUG-15:10 | 1.67 |
September | 0.525179E+10 | 0.35 | 21318.17 | 11-SEP-14:27 | 1.78 |
October | 0.344996E+10 | 0.29 | 10817.60 | 04-OCT-15:20 | 1.17 |
November | 0.282113E+10 | 0.28 | 5023.93 | 13-NOV-05:01 | 0.75 |
December | 0.308503E+10 | 0.30 | 5023.93 | 01-DEC-06:02 | 0.75 |
Annual Sum or Average | 0.553997E+11 | 0.34 | |||
Minimum of Months | 0.282113E+10 | 0.28 | 5023.93 | 0.75 | |
Maximum of Months | 0.825048E+10 | 0.45 | 21318.17 | 1.78 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.355281E+10 | 0.35 | 12272.71 | 02-JAN-07:05 | 1.80 |
February | 0.553808E+10 | 0.46 | 12272.71 | 01-FEB-07:10 | 1.80 |
March | 0.948356E+10 | 0.62 | 12272.71 | 01-MAR-07:05 | 1.81 |
April | 0.139440E+11 | 0.82 | 12272.71 | 01-APR-06:10 | 1.80 |
May | 0.117156E+11 | 0.70 | 12272.71 | 01-MAY-06:10 | 1.79 |
June | 0.126788E+11 | 0.77 | 12272.71 | 01-JUN-06:05 | 1.80 |
July | 0.124346E+11 | 0.72 | 12272.71 | 01-JUL-06:10 | 1.79 |
August | 0.135662E+11 | 0.79 | 12272.71 | 01-AUG-06:10 | 1.79 |
September | 0.133781E+11 | 0.79 | 12272.71 | 01-SEP-06:10 | 1.79 |
October | 0.141861E+11 | 0.80 | 12272.71 | 02-OCT-06:10 | 1.79 |
November | 0.131535E+11 | 0.78 | 12272.71 | 01-NOV-06:10 | 1.80 |
December | 0.871581E+10 | 0.57 | 12272.71 | 01-DEC-07:05 | 1.81 |
Annual Sum or Average | 0.132347E+12 | 0.68 | |||
Minimum of Months | 0.355281E+10 | 0.35 | 12272.71 | 1.79 | |
Maximum of Months | 0.141861E+11 | 0.82 | 12272.71 | 1.81 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.109978E+12 | 1.37 | 41061.23 | 01-JAN-00:05 | 1.37 |
February | 0.993353E+11 | 1.37 | 41061.23 | 01-FEB-00:10 | 1.37 |
March | 0.109978E+12 | 1.37 | 41061.23 | 01-MAR-00:10 | 1.37 |
April | 0.106431E+12 | 1.37 | 41061.23 | 01-APR-00:10 | 1.37 |
May | 0.109978E+12 | 1.37 | 41061.23 | 01-MAY-00:10 | 1.37 |
June | 0.106431E+12 | 1.36 | 41061.23 | 01-JUN-00:10 | 1.37 |
July | 0.109978E+12 | 1.36 | 41061.23 | 01-JUL-00:10 | 1.36 |
August | 0.109978E+12 | 1.36 | 41061.23 | 01-AUG-00:03 | 1.36 |
September | 0.106431E+12 | 1.36 | 41061.23 | 01-SEP-00:05 | 1.36 |
October | 0.109978E+12 | 1.37 | 41061.23 | 01-OCT-00:10 | 1.36 |
November | 0.106431E+12 | 1.37 | 41061.23 | 01-NOV-00:10 | 1.37 |
December | 0.109978E+12 | 1.37 | 41061.23 | 01-DEC-00:20 | 1.37 |
Annual Sum or Average | 0.129491E+13 | 1.37 | |||
Minimum of Months | 0.993353E+11 | 1.36 | 41061.23 | 1.36 | |
Maximum of Months | 0.109978E+12 | 1.37 | 41061.23 | 1.37 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.153842E+10 | 0.93 | 574.38 | 01-JAN-00:05 | 0.93 |
February | 0.138954E+10 | 0.93 | 574.38 | 01-FEB-00:10 | 0.93 |
March | 0.153842E+10 | 0.93 | 574.38 | 01-MAR-00:10 | 0.93 |
April | 0.148879E+10 | 0.93 | 574.38 | 01-APR-00:10 | 0.93 |
May | 0.153842E+10 | 0.93 | 574.38 | 01-MAY-00:10 | 0.93 |
June | 0.148879E+10 | 0.93 | 574.38 | 01-JUN-00:20 | 0.93 |
July | 0.153842E+10 | 0.93 | 574.38 | 01-JUL-00:10 | 0.93 |
August | 0.153842E+10 | 0.93 | 574.38 | 01-AUG-00:03 | 0.93 |
September | 0.148879E+10 | 0.93 | 574.38 | 01-SEP-00:05 | 0.93 |
October | 0.153842E+10 | 0.93 | 574.38 | 01-OCT-00:10 | 0.93 |
November | 0.148879E+10 | 0.93 | 574.38 | 01-NOV-00:10 | 0.93 |
December | 0.153842E+10 | 0.93 | 574.38 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.181136E+11 | 0.93 | |||
Minimum of Months | 0.138954E+10 | 0.93 | 574.38 | 0.93 | |
Maximum of Months | 0.153842E+10 | 0.93 | 574.38 | 0.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.147697E+11 | 0.93 | 5514.37 | 01-JAN-00:05 | 0.92 |
February | 0.133404E+11 | 0.93 | 5514.37 | 01-FEB-00:10 | 0.93 |
March | 0.147697E+11 | 0.93 | 5514.37 | 01-MAR-00:10 | 0.93 |
April | 0.142932E+11 | 0.93 | 5514.37 | 01-APR-00:10 | 0.93 |
May | 0.147697E+11 | 0.93 | 5514.37 | 01-MAY-00:10 | 0.93 |
June | 0.142932E+11 | 0.93 | 5514.37 | 01-JUN-00:10 | 0.93 |
July | 0.147697E+11 | 0.93 | 5514.37 | 01-JUL-00:10 | 0.93 |
August | 0.147697E+11 | 0.93 | 5514.37 | 01-AUG-00:03 | 0.93 |
September | 0.142932E+11 | 0.93 | 5514.37 | 01-SEP-00:05 | 0.93 |
October | 0.147697E+11 | 0.93 | 5514.37 | 01-OCT-00:10 | 0.93 |
November | 0.142932E+11 | 0.93 | 5514.37 | 01-NOV-00:10 | 0.93 |
December | 0.147697E+11 | 0.93 | 5514.37 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.173901E+12 | 0.93 | |||
Minimum of Months | 0.133404E+11 | 0.93 | 5514.37 | 0.92 | |
Maximum of Months | 0.147697E+11 | 0.93 | 5514.37 | 0.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.149824E+10 | 0.93 | 559.38 | 01-JAN-00:05 | 0.93 |
February | 0.135325E+10 | 0.93 | 559.38 | 01-FEB-00:10 | 0.93 |
March | 0.149824E+10 | 0.93 | 559.38 | 01-MAR-00:10 | 0.93 |
April | 0.144991E+10 | 0.93 | 559.38 | 01-APR-00:10 | 0.93 |
May | 0.149824E+10 | 0.93 | 559.38 | 01-MAY-00:10 | 0.93 |
June | 0.144991E+10 | 0.93 | 559.38 | 01-JUN-00:10 | 0.93 |
July | 0.149824E+10 | 0.93 | 559.38 | 01-JUL-00:10 | 0.93 |
August | 0.149824E+10 | 0.93 | 559.38 | 01-AUG-00:03 | 0.93 |
September | 0.144991E+10 | 0.93 | 559.38 | 01-SEP-00:05 | 0.93 |
October | 0.149824E+10 | 0.93 | 559.38 | 01-OCT-00:10 | 0.93 |
November | 0.144991E+10 | 0.93 | 559.38 | 01-NOV-00:10 | 0.93 |
December | 0.149824E+10 | 0.93 | 559.38 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.176406E+11 | 0.93 | |||
Minimum of Months | 0.135325E+10 | 0.93 | 559.38 | 0.93 | |
Maximum of Months | 0.149824E+10 | 0.93 | 559.38 | 0.93 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.100168E+10 | 0.901510E+09 | 3849.67 | 17-JAN-06:02 | 3464.70 | 3464.70 | 46.35 | 9.19 |
February | 0.539597E+09 | 0.485638E+09 | 3318.70 | 21-FEB-06:02 | 2986.83 | 2986.83 | 42.08 | 5.82 |
March | 0.151037E+09 | 0.135934E+09 | 3128.58 | 06-MAR-05:11 | 2815.72 | 2815.72 | 26.44 | 5.16 |
April | 46325508.27 | 41692957.44 | 2326.09 | 19-APR-05:02 | 2093.48 | 2093.48 | 29.08 | 3.17 |
May | 5191747.63 | 4672572.87 | 710.27 | 18-MAY-05:02 | 639.24 | 639.24 | 22.74 | 0.78 |
June | 223142.84 | 200828.55 | 20.49 | 14-JUN-05:02 | 18.44 | 18.44 | 20.78 | 0.02 |
July | 1.19 | 1.07 | 0.00 | 05-JUL-06:05 | 0.00 | 0.00 | 20.53 | 0.00 |
August | 57.87 | 52.08 | 0.19 | 03-AUG-06:30 | 0.17 | 0.17 | 20.53 | 0.00 |
September | 1562981.15 | 1406683.03 | 245.82 | 27-SEP-05:03 | 221.24 | 221.24 | 20.56 | 0.26 |
October | 47249447.63 | 42524502.87 | 2044.75 | 30-OCT-05:03 | 1840.27 | 1840.27 | 29.62 | 2.66 |
November | 0.330055E+09 | 0.297050E+09 | 3276.00 | 13-NOV-06:01 | 2948.40 | 2948.40 | 35.65 | 5.66 |
December | 0.728029E+09 | 0.655226E+09 | 3397.97 | 26-DEC-06:02 | 3058.18 | 3058.18 | 44.65 | 6.14 |
Annual Sum or Average | 0.285095E+10 | 0.256585E+10 | ||||||
Minimum of Months | 1.19 | 1.07 | 0.00 | 0.00 | 0.00 | 20.53 | 0.00 | |
Maximum of Months | 0.100168E+10 | 0.901510E+09 | 3849.67 | 3464.70 | 3464.70 | 46.35 | 9.19 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 10601.93 | 9541.74 | 3.49 | 11-JAN-07:12 | 3.14 | 3.14 | 6.70 | 0.82 |
February | 3229964.10 | 2906967.69 | 443.55 | 27-FEB-16:00 | 399.20 | 399.20 | 6.70 | 16.07 |
March | 2877493.24 | 2589743.91 | 79.60 | 10-MAR-14:00 | 71.64 | 71.64 | 6.70 | 6.70 |
April | 0.106392E+09 | 95752974.73 | 4806.63 | 27-APR-12:00 | 4325.97 | 4325.97 | 9.26 | 45.42 |
May | 0.150515E+09 | 0.135463E+09 | 6513.67 | 04-MAY-13:50 | 5862.30 | 5862.30 | 9.58 | 51.33 |
June | 0.363344E+09 | 0.327010E+09 | 7937.40 | 28-JUN-12:40 | 7143.66 | 7143.66 | 10.11 | 55.53 |
July | 0.592166E+09 | 0.532949E+09 | 5768.11 | 06-JUL-16:00 | 5191.30 | 5191.30 | 9.19 | 48.89 |
August | 0.866564E+09 | 0.779907E+09 | 9245.51 | 15-AUG-12:50 | 8320.96 | 8320.96 | 10.37 | 58.97 |
September | 0.332124E+09 | 0.298912E+09 | 9986.02 | 11-SEP-14:23 | 8987.42 | 8987.42 | 10.56 | 60.80 |
October | 24916185.01 | 22424566.51 | 883.57 | 04-OCT-13:40 | 795.21 | 795.21 | 6.71 | 22.07 |
November | 2996687.21 | 2697018.49 | 193.22 | 04-NOV-14:10 | 173.89 | 173.89 | 6.70 | 10.70 |
December | 49202.04 | 44281.83 | 14.40 | 16-DEC-07:13 | 12.96 | 12.96 | 6.70 | 2.36 |
Annual Sum or Average | 0.244518E+10 | 0.220067E+10 | ||||||
Minimum of Months | 10601.93 | 9541.74 | 3.49 | 3.14 | 3.14 | 6.70 | 0.82 | |
Maximum of Months | 0.866564E+09 | 0.779907E+09 | 9986.02 | 8987.42 | 8987.42 | 10.56 | 60.80 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.136912E+09 | 0.123221E+09 | 3436.55 | 10-JAN-15:40 | 3092.90 | 3092.90 | 6.72 | 30.40 |
February | 0.733265E+09 | 0.659938E+09 | 3436.55 | 01-FEB-07:12 | 3092.90 | 3092.90 | 6.75 | 30.40 |
March | 0.917766E+09 | 0.825989E+09 | 3436.55 | 01-MAR-05:03 | 3092.90 | 3092.90 | 6.93 | 30.40 |
April | 0.139874E+10 | 0.125887E+10 | 3436.55 | 01-APR-05:03 | 3092.90 | 3092.90 | 6.73 | 30.40 |
May | 0.303686E+10 | 0.273317E+10 | 3436.55 | 01-MAY-04:12 | 3092.90 | 3092.90 | 6.75 | 30.40 |
June | 0.418528E+10 | 0.376675E+10 | 3436.55 | 01-JUN-04:12 | 3092.90 | 3092.90 | 6.94 | 30.40 |
July | 0.552052E+10 | 0.496847E+10 | 3436.55 | 01-JUL-04:12 | 3092.90 | 3092.90 | 7.15 | 30.40 |
August | 0.615653E+10 | 0.554087E+10 | 3436.55 | 01-AUG-00:42 | 3092.90 | 3092.90 | 6.80 | 30.40 |
September | 0.353700E+10 | 0.318330E+10 | 3436.55 | 01-SEP-00:53 | 3092.90 | 3092.90 | 6.76 | 30.40 |
October | 0.125887E+10 | 0.113299E+10 | 3436.55 | 01-OCT-12:23 | 3092.90 | 3092.90 | 6.84 | 30.40 |
November | 0.675123E+09 | 0.607611E+09 | 3436.55 | 01-NOV-06:11 | 3092.90 | 3092.90 | 6.83 | 30.40 |
December | 0.384550E+09 | 0.346095E+09 | 3436.55 | 01-DEC-11:55 | 3092.90 | 3092.90 | 6.72 | 30.40 |
Annual Sum or Average | 0.279414E+11 | 0.251473E+11 | ||||||
Minimum of Months | 0.136912E+09 | 0.123221E+09 | 3436.55 | 3092.90 | 3092.90 | 6.72 | 30.40 | |
Maximum of Months | 0.615653E+10 | 0.554087E+10 | 3436.55 | 3092.90 | 3092.90 | 7.15 | 30.40 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 6.70 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 7.08 | 0.00 |
April | 90725000.10 | 81652500.09 | 3436.55 | 26-APR-13:40 | 3092.90 | 3092.90 | 14.50 | 15.20 |
May | 96910795.56 | 87219716.00 | 3436.55 | 04-MAY-14:00 | 3092.90 | 3092.90 | 17.16 | 15.20 |
June | 0.164955E+09 | 0.148459E+09 | 3436.55 | 09-JUN-14:40 | 3092.90 | 3092.90 | 14.83 | 15.20 |
July | 0.486616E+09 | 0.437954E+09 | 3436.55 | 07-JUL-11:40 | 3092.90 | 3092.90 | 15.36 | 15.20 |
August | 0.105777E+10 | 0.951994E+09 | 3436.55 | 07-AUG-10:20 | 3092.90 | 3092.90 | 15.62 | 15.20 |
September | 0.208255E+09 | 0.187430E+09 | 3436.55 | 08-SEP-14:50 | 3092.90 | 3092.90 | 14.83 | 15.20 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 6.89 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
Annual Sum or Average | 0.210523E+10 | 0.189471E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 | |
Maximum of Months | 0.105777E+10 | 0.951994E+09 | 3436.55 | 3092.90 | 3092.90 | 17.16 | 15.20 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.101547E+11 | 0.913922E+10 | 3791.32 | 01-JAN-00:05 | 3412.19 | 3412.19 | 18.48 | 15.83 |
February | 0.917197E+10 | 0.825478E+10 | 3791.32 | 01-FEB-00:10 | 3412.19 | 3412.19 | 19.11 | 15.83 |
March | 0.101547E+11 | 0.913922E+10 | 3791.32 | 01-MAR-00:10 | 3412.19 | 3412.19 | 19.79 | 15.83 |
April | 0.982711E+10 | 0.884440E+10 | 3791.32 | 01-APR-00:10 | 3412.19 | 3412.19 | 20.27 | 15.83 |
May | 0.101547E+11 | 0.913922E+10 | 3791.32 | 01-MAY-00:10 | 3412.19 | 3412.19 | 18.89 | 15.83 |
June | 0.982711E+10 | 0.884440E+10 | 3791.32 | 01-JUN-00:10 | 3412.19 | 3412.19 | 19.41 | 15.83 |
July | 0.101547E+11 | 0.913922E+10 | 3791.32 | 01-JUL-00:10 | 3412.19 | 3412.19 | 19.90 | 15.83 |
August | 0.101547E+11 | 0.913922E+10 | 3791.32 | 01-AUG-00:03 | 3412.19 | 3412.19 | 24.99 | 15.83 |
September | 0.982711E+10 | 0.884440E+10 | 3791.32 | 01-SEP-00:05 | 3412.19 | 3412.19 | 18.96 | 15.83 |
October | 0.101547E+11 | 0.913922E+10 | 3791.32 | 01-OCT-00:10 | 3412.19 | 3412.19 | 19.32 | 15.83 |
November | 0.982711E+10 | 0.884440E+10 | 3791.32 | 01-NOV-00:10 | 3412.19 | 3412.19 | 19.72 | 15.83 |
December | 0.101547E+11 | 0.913922E+10 | 3791.32 | 01-DEC-00:10 | 3412.19 | 3412.19 | 20.21 | 15.83 |
Annual Sum or Average | 0.119563E+12 | 0.107607E+12 | ||||||
Minimum of Months | 0.917197E+10 | 0.825478E+10 | 3791.32 | 3412.19 | 3412.19 | 18.48 | 15.83 | |
Maximum of Months | 0.101547E+11 | 0.913922E+10 | 3791.32 | 3412.19 | 3412.19 | 24.99 | 15.83 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 56.98 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:03 | 16.86 | 16.86 | 57.00 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:02 | 16.86 | 16.86 | 57.07 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:03 | 16.86 | 16.86 | 57.07 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 57.23 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:02 | 16.86 | 16.86 | 57.34 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 57.31 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 57.42 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 57.42 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 57.12 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:02 | 16.86 | 16.86 | 57.31 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:02 | 16.86 | 16.86 | 57.20 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 56.98 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.42 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.529616E+09 | 0.476655E+09 | 13295.16 | 10-JAN-15:50 | 11965.65 | 11965.65 | 21.13 | 53.90 |
February | 0.283692E+10 | 0.255322E+10 | 13318.71 | 27-FEB-16:00 | 11986.84 | 11986.84 | 23.59 | 53.90 |
March | 0.355077E+10 | 0.319569E+10 | 13311.36 | 18-MAR-16:00 | 11980.22 | 11980.22 | 22.82 | 53.90 |
April | 0.573543E+10 | 0.516189E+10 | 26684.82 | 27-APR-15:50 | 24016.34 | 24016.34 | 25.90 | 107.80 |
May | 0.120927E+11 | 0.108835E+11 | 26681.40 | 05-MAY-16:00 | 24013.26 | 24013.26 | 25.75 | 107.80 |
June | 0.167995E+11 | 0.151195E+11 | 26687.65 | 22-JUN-15:10 | 24018.88 | 24018.88 | 26.03 | 107.80 |
July | 0.230740E+11 | 0.207666E+11 | 26722.39 | 31-JUL-16:00 | 24050.15 | 24050.15 | 27.58 | 107.80 |
August | 0.277193E+11 | 0.249473E+11 | 26745.66 | 29-AUG-14:30 | 24071.09 | 24071.09 | 28.62 | 107.80 |
September | 0.144569E+11 | 0.130112E+11 | 26706.15 | 11-SEP-15:03 | 24035.53 | 24035.53 | 26.86 | 107.80 |
October | 0.487234E+10 | 0.438510E+10 | 13346.15 | 04-OCT-15:00 | 12011.53 | 12011.53 | 26.24 | 53.90 |
November | 0.261203E+10 | 0.235083E+10 | 13315.36 | 04-NOV-14:10 | 11983.82 | 11983.82 | 23.24 | 53.90 |
December | 0.148757E+10 | 0.133881E+10 | 13295.60 | 14-DEC-11:40 | 11966.04 | 11966.04 | 21.17 | 53.90 |
Annual Sum or Average | 0.115767E+12 | 0.104190E+12 | ||||||
Minimum of Months | 0.529616E+09 | 0.476655E+09 | 13295.16 | 11965.65 | 11965.65 | 21.13 | 53.90 | |
Maximum of Months | 0.277193E+11 | 0.249473E+11 | 26745.66 | 24071.09 | 24071.09 | 28.62 | 107.80 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 38.27 | 38.27 | 92925.32 | 1540253.77 | 02-JAN-05:11 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 24.70 | 24.70 | 55026.50 | 1104534.91 | 14-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 21.14 | 21.14 | 14115.94 | 1198589.93 | 06-MAR-05:11 |
April | 0.00 | 0.00 | 01-APR-00:10 | 19.90 | 19.90 | 4512.60 | 701621.65 | 19-APR-05:02 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 23.81 | 23.81 | 498.75 | 192335.96 | 18-MAY-05:02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 20.96 | 20.96 | 22.52 | 5360.30 | 14-JUN-05:02 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.53 | 20.53 | 0.00 | 0.72 | 05-JUL-06:05 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 20.53 | 20.53 | 0.01 | 50.38 | 03-AUG-06:30 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 20.53 | 20.53 | 157.85 | 65911.87 | 27-SEP-05:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 20.73 | 20.73 | 4529.57 | 581332.12 | 30-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.25 | 21.25 | 32151.55 | 1281665.02 | 24-NOV-05:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 26.10 | 26.10 | 67893.25 | 1272344.29 | 18-DEC-05:11 |
Annual Sum or Average | 0.00 | 22534.04 | ||||||
Minimum of Months | 0.00 | 0.00 | 19.90 | 19.90 | 0.00 | 0.72 | ||
Maximum of Months | 0.00 | 0.00 | 38.27 | 38.27 | 92925.32 | 1540253.77 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 51.48 | 5291.11 | 27-JAN-13:20 | 6.74 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 3525.18 | 515910.52 | 27-FEB-16:00 | 10.75 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 4587.35 | 342150.22 | 18-MAR-16:00 | 9.39 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 39948.70 | 1488738.80 | 27-APR-12:30 | 12.55 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 72218.80 | 1542051.00 | 04-MAY-14:10 | 12.76 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 137964.60 | 1491991.90 | 28-JUN-13:00 | 12.56 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 237317.83 | 1617625.85 | 31-JUL-16:00 | 13.05 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 314575.79 | 1716943.78 | 29-AUG-14:30 | 13.44 | 6.70 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 116930.00 | 1992781.51 | 12-SEP-13:27 | 14.53 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 18915.97 | 1007879.22 | 04-OCT-15:00 | 14.62 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 3443.11 | 427114.11 | 04-NOV-14:10 | 10.05 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 196.10 | 34585.55 | 16-DEC-07:13 | 6.97 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 79811.12 | 0.00 | ||||||
Minimum of Months | 51.48 | 5291.11 | 6.74 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 314575.79 | 1992781.51 | 14.62 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 5.61 | 2294.19 | 27-JAN-13:10 | 8.56 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 3257.14 | 537958.43 | 27-FEB-16:00 | 14.70 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 4278.82 | 340332.46 | 18-MAR-16:00 | 19.56 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 39842.55 | 1858455.04 | 27-APR-12:20 | 17.59 | 9.92 | 0.00 | 0.00 | 01-APR-00:10 |
May | 71525.92 | 1680831.55 | 04-MAY-14:00 | 17.83 | 10.35 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 137849.89 | 1770279.40 | 28-JUN-12:40 | 14.32 | 10.14 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 236883.41 | 1921975.82 | 20-JUL-12:20 | 17.94 | 9.56 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 314178.97 | 1895822.70 | 15-AUG-12:50 | 14.38 | 10.41 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 119046.58 | 2168792.83 | 12-SEP-13:23 | 15.22 | 10.95 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 18512.33 | 1008866.83 | 04-OCT-15:00 | 18.34 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 3211.18 | 424752.08 | 04-NOV-14:10 | 16.18 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 66.88 | 45148.85 | 16-DEC-07:12 | 11.28 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 79722.51 | 0.00 | ||||||
Minimum of Months | 5.61 | 2294.19 | 8.56 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 314178.97 | 2168792.83 | 19.56 | 10.95 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 16180.23 | 32766.25 | 05-JAN-16:20 | 18.93 | 18.33 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 49600.14 | 200654.95 | 27-FEB-15:00 | 21.98 | 20.51 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 84676.73 | 465811.64 | 18-MAR-16:00 | 26.76 | 22.19 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 173050.27 | 1422401.38 | 27-APR-16:00 | 43.65 | 31.55 | 0.00 | 0.00 | 01-APR-00:10 |
May | 53848.40 | 575916.72 | 05-MAY-16:00 | 28.73 | 25.97 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 123114.67 | 952495.54 | 28-JUN-17:00 | 35.42 | 28.98 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 317812.17 | 1427811.41 | 24-JUL-15:00 | 43.75 | 34.08 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 596093.37 | 1717368.57 | 10-AUG-17:00 | 48.76 | 36.31 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 60370.90 | 577899.92 | 22-SEP-16:00 | 28.76 | 25.98 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 56859.93 | 403557.87 | 04-OCT-15:00 | 25.64 | 22.72 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 80972.12 | 586112.76 | 04-NOV-15:00 | 28.91 | 23.13 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 104045.07 | 120622.18 | 05-DEC-16:00 | 20.53 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 144189.14 | 0.00 | ||||||
Minimum of Months | 16180.23 | 32766.25 | 18.93 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 596093.37 | 1717368.57 | 48.76 | 36.31 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 58.14 | 58.14 | 14332.44 | 51088.77 | 31-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.62 | 57.62 | 14518.51 | 51150.74 | 10-FEB-13:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.62 | 57.62 | 15258.69 | 50975.41 | 01-MAR-12:30 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.67 | 57.67 | 13905.14 | 49837.63 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.21 | 58.21 | 13845.35 | 48284.47 | 01-MAY-11:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.84 | 57.84 | 13658.88 | 46383.77 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.91 | 57.91 | 12219.48 | 44763.67 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 57.95 | 57.95 | 13273.49 | 44110.83 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 57.95 | 57.95 | 12602.96 | 45073.87 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.90 | 57.90 | 12975.99 | 46819.59 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.82 | 57.82 | 13675.01 | 48660.90 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.73 | 57.73 | 13648.71 | 50167.43 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 13654.68 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.62 | 57.62 | 12219.48 | 44110.83 | ||
Maximum of Months | 0.00 | 0.00 | 58.21 | 58.21 | 15258.69 | 51150.74 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 3.51 | 5997.05 | 10-JAN-15:50 | 21.13 | 20.45 | 469.55 | 96798.36 | 10-JAN-16:10 |
February | 3274.62 | 560273.67 | 27-FEB-16:00 | 23.59 | 21.10 | 1786.75 | 126261.74 | 08-FEB-07:00 |
March | 3929.57 | 387361.18 | 18-MAR-16:00 | 22.82 | 21.10 | 1924.95 | 113831.32 | 28-MAR-06:00 |
April | 46735.11 | 2163959.63 | 27-APR-15:50 | 25.90 | 21.79 | 998.56 | 94565.60 | 17-APR-12:40 |
May | 81757.12 | 2094970.90 | 05-MAY-16:00 | 25.75 | 21.87 | 2302.88 | 93063.17 | 11-MAY-08:40 |
June | 160744.27 | 2220909.48 | 22-JUN-15:10 | 26.03 | 21.12 | 1531.72 | 74495.51 | 01-JUN-05:40 |
July | 293397.56 | 2919963.70 | 31-JUL-16:00 | 27.58 | 23.49 | 1075.04 | 79314.53 | 03-JUL-08:00 |
August | 420529.19 | 3387181.60 | 29-AUG-14:30 | 28.62 | 24.25 | 1161.05 | 59576.66 | 03-AUG-19:40 |
September | 140917.85 | 2593344.69 | 11-SEP-15:03 | 26.86 | 21.86 | 1171.81 | 77837.76 | 29-SEP-06:50 |
October | 20058.37 | 1157947.31 | 04-OCT-15:00 | 26.24 | 21.10 | 1161.50 | 89695.20 | 11-OCT-05:40 |
November | 3314.77 | 481536.92 | 04-NOV-14:10 | 23.24 | 21.10 | 1536.53 | 110191.54 | 18-NOV-07:12 |
December | 27.56 | 16276.72 | 14-DEC-11:40 | 21.17 | 20.56 | 1161.90 | 113146.44 | 21-DEC-05:53 |
Annual Sum or Average | 98777.64 | 1353.84 | ||||||
Minimum of Months | 3.51 | 5997.05 | 21.13 | 20.45 | 469.55 | 59576.66 | ||
Maximum of Months | 420529.19 | 3387181.60 | 28.62 | 24.25 | 2302.88 | 126261.74 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.576705E+10 | 0.00 | 21.23 | 0.376328E+10 | 0.00 | 0.00 |
February | 0.301644E+10 | 0.00 | 0.807767E+09 | 0.438998E+10 | 0.00 | 0.00 |
March | 0.330624E+09 | 0.00 | 0.107148E+10 | 0.687505E+10 | 0.00 | 0.00 |
April | 37928533.56 | 0.00 | 0.103402E+11 | 0.878479E+10 | 0.00 | 0.00 |
May | 8347774.33 | 0.00 | 0.167513E+11 | 0.801342E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.328265E+11 | 0.979799E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.597965E+11 | 0.119463E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.817936E+11 | 0.139786E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.259091E+11 | 0.819419E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.478266E+10 | 0.678546E+10 | 0.00 | 0.00 |
November | 0.713434E+09 | 0.00 | 0.690295E+09 | 0.525942E+10 | 0.00 | 0.00 |
December | 0.234751E+10 | 0.00 | 525.30 | 0.509191E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.122213E+11 | 0.00 | 0.234769E+12 | 0.928803E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 21.23 | 0.376328E+10 | 0.00 | 0.00 |
Maximum of Months | 0.576705E+10 | 0.00 | 0.817936E+11 | 0.139786E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.206160E+12 | 0.00 | 47618.03 | 0.288239E+11 | 0.00 | 0.00 |
February | 0.108574E+12 | 0.00 | 0.513887E+10 | 0.293867E+11 | 0.00 | 0.00 |
March | 0.283134E+11 | 0.00 | 0.776076E+10 | 0.405570E+11 | 0.00 | 0.00 |
April | 0.845862E+10 | 0.00 | 0.772722E+11 | 0.469069E+11 | 0.00 | 0.00 |
May | 0.618415E+09 | 0.00 | 0.143975E+12 | 0.592142E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.266206E+12 | 0.674453E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.468342E+12 | 0.776738E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.620347E+12 | 0.887115E+11 | 0.00 | 0.00 |
September | 90912011.84 | 0.00 | 0.228585E+12 | 0.625507E+11 | 0.00 | 0.00 |
October | 0.806293E+10 | 0.00 | 0.375576E+11 | 0.433422E+11 | 0.00 | 0.00 |
November | 0.665157E+11 | 0.00 | 0.601908E+10 | 0.305232E+11 | 0.00 | 0.00 |
December | 0.149935E+12 | 0.00 | 50521.68 | 0.295540E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.576729E+12 | 0.00 | 0.186120E+13 | 0.604689E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 47618.03 | 0.288239E+11 | 0.00 | 0.00 |
Maximum of Months | 0.206160E+12 | 0.00 | 0.620347E+12 | 0.887115E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.379646E+11 | 0.00 | 53792.68 | 0.347070E+10 | 0.00 | 0.00 |
February | 0.223069E+11 | 0.00 | 0.430738E+09 | 0.299157E+10 | 0.00 | 0.00 |
March | 0.948481E+10 | 0.00 | 0.664518E+09 | 0.339656E+10 | 0.00 | 0.00 |
April | 0.328553E+10 | 0.00 | 0.801913E+10 | 0.396931E+10 | 0.00 | 0.00 |
May | 0.729247E+09 | 0.00 | 0.148504E+11 | 0.513472E+10 | 0.00 | 0.00 |
June | 60615630.96 | 0.00 | 0.280522E+11 | 0.616010E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.502032E+11 | 0.741834E+10 | 0.00 | 0.00 |
August | 16348.38 | 0.00 | 0.655530E+11 | 0.825048E+10 | 0.00 | 0.00 |
September | 0.320853E+09 | 0.00 | 0.224069E+11 | 0.525179E+10 | 0.00 | 0.00 |
October | 0.417096E+10 | 0.00 | 0.323837E+10 | 0.344996E+10 | 0.00 | 0.00 |
November | 0.168147E+11 | 0.00 | 0.576840E+09 | 0.282113E+10 | 0.00 | 0.00 |
December | 0.311171E+11 | 0.00 | 19369.25 | 0.308503E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.126255E+12 | 0.00 | 0.193995E+12 | 0.553997E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 19369.25 | 0.282113E+10 | 0.00 | 0.00 |
Maximum of Months | 0.379646E+11 | 0.00 | 0.655530E+11 | 0.825048E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.123912E+10 | 0.00 | 48045070.28 | 0.355281E+10 | 0.00 | 0.00 |
February | 0.408474E+09 | 0.00 | 0.156443E+10 | 0.553808E+10 | 0.00 | 0.00 |
March | 16072024.71 | 0.00 | 0.199320E+10 | 0.948356E+10 | 0.00 | 0.00 |
April | 861731.23 | 0.00 | 0.497688E+10 | 0.139440E+11 | 0.00 | 0.00 |
May | 3150634.85 | 0.00 | 0.120008E+11 | 0.117156E+11 | 0.00 | 0.00 |
June | 1560.72 | 0.00 | 0.221279E+11 | 0.126788E+11 | 0.00 | 0.00 |
July | 374.86 | 0.00 | 0.373870E+11 | 0.124346E+11 | 0.00 | 0.00 |
August | 68.11 | 0.00 | 0.480967E+11 | 0.135662E+11 | 0.00 | 0.00 |
September | 169.35 | 0.00 | 0.170712E+11 | 0.133781E+11 | 0.00 | 0.00 |
October | 217464.17 | 0.00 | 0.265960E+10 | 0.141861E+11 | 0.00 | 0.00 |
November | 745818.97 | 0.00 | 0.105540E+10 | 0.131535E+11 | 0.00 | 0.00 |
December | 42737582.33 | 0.00 | 0.155311E+09 | 0.871581E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.171138E+10 | 0.00 | 0.149136E+12 | 0.132347E+12 | 0.00 | 0.00 |
Minimum of Months | 68.11 | 0.00 | 48045070.28 | 0.355281E+10 | 0.00 | 0.00 |
Maximum of Months | 0.123912E+10 | 0.00 | 0.480967E+11 | 0.141861E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.858063E+10 | 0.207413E+12 | 0.00 | 34.74 |
February | 0.00 | 0.00 | 0.113042E+11 | 0.237056E+12 | 0.00 | 49.56 |
March | 0.00 | 0.00 | 0.182284E+11 | 0.297671E+12 | 0.00 | 67.43 |
April | 0.00 | 0.00 | 0.102223E+12 | 0.289066E+12 | 0.00 | 58.32 |
May | 0.00 | 0.00 | 0.851478E+10 | 0.150550E+12 | 0.00 | 13.53 |
June | 0.00 | 0.00 | 0.465585E+11 | 0.142959E+12 | 0.00 | 8.62 |
July | 0.00 | 0.00 | 0.272620E+12 | 0.196625E+12 | 0.00 | 8.24 |
August | 0.00 | 0.00 | 0.688806E+12 | 0.266727E+12 | 0.00 | 0.30 |
September | 0.00 | 0.00 | 0.767666E+10 | 0.112435E+12 | 0.00 | 0.65 |
October | 0.00 | 0.00 | 0.787152E+10 | 0.169663E+12 | 0.00 | 20.69 |
November | 0.00 | 0.00 | 0.156013E+11 | 0.231842E+12 | 0.00 | 44.55 |
December | 0.00 | 0.00 | 0.198391E+11 | 0.338027E+12 | 0.00 | 82.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.120782E+13 | 0.264003E+13 | 0.00 | 388.92 |
Minimum of Months | 0.00 | 0.00 | 0.767666E+10 | 0.112435E+12 | 0.00 | 0.30 |
Maximum of Months | 0.00 | 0.00 | 0.688806E+12 | 0.338027E+12 | 0.00 | 82.29 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.499950E+10 | 0.257215E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.108484E+11 | 0.350215E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.188465E+11 | 0.505920E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.245063E+11 | 0.593883E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.707135E+10 | 0.294914E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.131460E+11 | 0.401184E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.202227E+11 | 0.542508E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.265531E+11 | 0.671776E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.704616E+10 | 0.288198E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.128851E+11 | 0.397794E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.180366E+11 | 0.481685E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.244841E+11 | 0.599526E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.188646E+12 | 0.538482E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.499950E+10 | 0.257215E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.265531E+11 | 0.671776E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.198736E+11 | 0.191359E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.825348E+11 | 0.296683E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.163180E+12 | 0.455512E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.223308E+12 | 0.550925E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.597326E+11 | 0.267926E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.119871E+12 | 0.374062E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.189490E+12 | 0.512896E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.250718E+12 | 0.637897E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.600492E+11 | 0.262670E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.108262E+12 | 0.354730E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.150645E+12 | 0.424411E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.206387E+12 | 0.528706E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.163405E+13 | 0.485778E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.198736E+11 | 0.191359E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.250718E+12 | 0.637897E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.750662E+09 | 0.166944E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.641267E+10 | 0.263775E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.148356E+11 | 0.432155E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.214382E+11 | 0.539073E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.535665E+10 | 0.258535E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.117005E+11 | 0.371419E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.187995E+11 | 0.513289E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.248875E+11 | 0.638135E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.534852E+10 | 0.252640E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.946638E+10 | 0.332641E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.132259E+11 | 0.394910E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.184729E+11 | 0.494919E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.150695E+12 | 0.465844E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.750662E+09 | 0.166944E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.248875E+11 | 0.638135E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.376328E+10 | 21.23 | 0.576705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.438998E+10 | 0.807767E+09 | 0.301644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.687505E+10 | 0.107148E+10 | 0.330624E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.878479E+10 | 0.103402E+11 | 37928533.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.801342E+10 | 0.167513E+11 | 8347774.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.979799E+10 | 0.328265E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.119463E+11 | 0.597965E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139786E+11 | 0.817936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.819419E+10 | 0.259091E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.678546E+10 | 0.478266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.525942E+10 | 0.690295E+09 | 0.713434E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.509191E+10 | 525.30 | 0.234751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.928803E+11 | 0.234769E+12 | 0.122213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.376328E+10 | 21.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.139786E+11 | 0.817936E+11 | 0.576705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.288239E+11 | 47618.03 | 0.206160E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.293867E+11 | 0.513887E+10 | 0.108574E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.405570E+11 | 0.776076E+10 | 0.283134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.469069E+11 | 0.772722E+11 | 0.845862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.592142E+11 | 0.143975E+12 | 0.618415E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.674453E+11 | 0.266206E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.776738E+11 | 0.468342E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.887115E+11 | 0.620347E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.625507E+11 | 0.228585E+12 | 90912011.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.433422E+11 | 0.375576E+11 | 0.806293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.305232E+11 | 0.601908E+10 | 0.665157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.295540E+11 | 50521.68 | 0.149935E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.604689E+12 | 0.186120E+13 | 0.576729E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.288239E+11 | 47618.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.887115E+11 | 0.620347E+12 | 0.206160E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.347070E+10 | 53792.68 | 0.379646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.299157E+10 | 0.430738E+09 | 0.223069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.339656E+10 | 0.664518E+09 | 0.948481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.396931E+10 | 0.801913E+10 | 0.328553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.513472E+10 | 0.148504E+11 | 0.729247E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.616010E+10 | 0.280522E+11 | 60615630.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.741834E+10 | 0.502032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.825048E+10 | 0.655530E+11 | 16348.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.525179E+10 | 0.224069E+11 | 0.320853E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.344996E+10 | 0.323837E+10 | 0.417096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.282113E+10 | 0.576840E+09 | 0.168147E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.308503E+10 | 19369.25 | 0.311171E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.553997E+11 | 0.193995E+12 | 0.126255E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.282113E+10 | 19369.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.825048E+10 | 0.655530E+11 | 0.379646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.355281E+10 | 48045070.28 | 0.123912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.553808E+10 | 0.156443E+10 | 0.408474E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.948356E+10 | 0.199320E+10 | 16072024.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139440E+11 | 0.497688E+10 | 861731.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.117156E+11 | 0.120008E+11 | 3150634.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.126788E+11 | 0.221279E+11 | 1560.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.124346E+11 | 0.373870E+11 | 374.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135662E+11 | 0.480967E+11 | 68.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133781E+11 | 0.170712E+11 | 169.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141861E+11 | 0.265960E+10 | 217464.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131535E+11 | 0.105540E+10 | 745818.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.871581E+10 | 0.155311E+09 | 42737582.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132347E+12 | 0.149136E+12 | 0.171138E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.355281E+10 | 48045070.28 | 68.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141861E+11 | 0.480967E+11 | 0.123912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.109978E+12 | 0.452884E+10 | 0.00 | 0.00 | 0.00 | 0.929643E+11 | 0.00 | 0.00 |
February | 0.993353E+11 | 0.680323E+10 | 0.00 | 0.00 | 0.00 | 0.132622E+12 | 0.00 | 0.00 |
March | 0.109978E+12 | 0.118029E+11 | 0.00 | 0.00 | 0.00 | 0.180455E+12 | 0.00 | 0.00 |
April | 0.106431E+12 | 0.763553E+11 | 0.00 | 0.00 | 0.00 | 0.156065E+12 | 0.00 | 0.00 |
May | 0.109978E+12 | 0.432714E+10 | 0.00 | 0.00 | 0.00 | 0.362205E+11 | 0.00 | 0.00 |
June | 0.106431E+12 | 0.331919E+11 | 0.00 | 0.00 | 0.00 | 0.230582E+11 | 0.00 | 0.00 |
July | 0.109978E+12 | 0.208127E+12 | 0.00 | 0.00 | 0.00 | 0.220551E+11 | 0.00 | 0.00 |
August | 0.109978E+12 | 0.532851E+12 | 0.00 | 0.00 | 0.00 | 0.789824E+09 | 0.00 | 0.00 |
September | 0.106431E+12 | 0.343313E+10 | 0.00 | 0.00 | 0.00 | 0.175248E+10 | 0.00 | 0.00 |
October | 0.109978E+12 | 0.380397E+10 | 0.00 | 0.00 | 0.00 | 0.553675E+11 | 0.00 | 0.00 |
November | 0.106431E+12 | 0.994902E+10 | 0.00 | 0.00 | 0.00 | 0.119222E+12 | 0.00 | 0.00 |
December | 0.109978E+12 | 0.130115E+11 | 0.00 | 0.00 | 0.00 | 0.220230E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.129491E+13 | 0.908186E+12 | 0.00 | 0.00 | 0.00 | 0.104080E+13 | 0.00 | 0.00 |
Minimum of Months | 0.993353E+11 | 0.343313E+10 | 0.00 | 0.00 | 0.00 | 0.789824E+09 | 0.00 | 0.00 |
Maximum of Months | 0.109978E+12 | 0.532851E+12 | 0.00 | 0.00 | 0.00 | 0.220230E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.153842E+10 | 0.396576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138954E+10 | 0.873578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153842E+10 | 0.153258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148879E+10 | 0.200563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153842E+10 | 0.566063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.148879E+10 | 0.106230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153842E+10 | 0.163361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153842E+10 | 0.213738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.148879E+10 | 0.565297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153842E+10 | 0.104455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148879E+10 | 0.147086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153842E+10 | 0.200272E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181136E+11 | 0.152911E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.138954E+10 | 0.396576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153842E+10 | 0.213738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.147697E+11 | 0.155073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133404E+11 | 0.662069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147697E+11 | 0.132398E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142932E+11 | 0.182508E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147697E+11 | 0.477097E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142932E+11 | 0.967580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147697E+11 | 0.152970E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147697E+11 | 0.201698E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142932E+11 | 0.480755E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147697E+11 | 0.875591E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142932E+11 | 0.122497E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147697E+11 | 0.168286E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173901E+12 | 0.132217E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133404E+11 | 0.155073E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147697E+11 | 0.201698E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.149824E+10 | 0.579462E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135325E+10 | 0.512817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149824E+10 | 0.120123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144991E+10 | 0.174973E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149824E+10 | 0.426955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144991E+10 | 0.943625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149824E+10 | 0.151649E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149824E+10 | 0.200043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144991E+10 | 0.427203E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149824E+10 | 0.763822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144991E+10 | 0.107267E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149824E+10 | 0.150219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176406E+11 | 0.121751E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135325E+10 | 0.579462E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149824E+10 | 0.200043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.376328E+10 | 0.576705E+10 | 21.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.438998E+10 | 0.301644E+10 | 0.807767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.687505E+10 | 0.330624E+09 | 0.107148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.878479E+10 | 37928533.56 | 0.103402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.801342E+10 | 8347774.33 | 0.167513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.979799E+10 | 0.00 | 0.328265E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.119463E+11 | 0.00 | 0.597965E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139786E+11 | 0.00 | 0.817936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.819419E+10 | 0.00 | 0.259091E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.678546E+10 | 0.00 | 0.478266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.525942E+10 | 0.713434E+09 | 0.690295E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.509191E+10 | 0.234751E+10 | 525.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.928803E+11 | 0.122213E+11 | 0.234769E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.376328E+10 | 0.00 | 21.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.139786E+11 | 0.576705E+10 | 0.817936E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.288239E+11 | 0.206160E+12 | 47618.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.293867E+11 | 0.108574E+12 | 0.513887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.405570E+11 | 0.283134E+11 | 0.776076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.469069E+11 | 0.845862E+10 | 0.772722E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.592142E+11 | 0.618415E+09 | 0.143975E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.674453E+11 | 0.00 | 0.266206E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.776738E+11 | 0.00 | 0.468342E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.887115E+11 | 0.00 | 0.620347E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.625507E+11 | 90912011.84 | 0.228585E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.433422E+11 | 0.806293E+10 | 0.375576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.305232E+11 | 0.665157E+11 | 0.601908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.295540E+11 | 0.149935E+12 | 50521.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.604689E+12 | 0.576729E+12 | 0.186120E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.288239E+11 | 0.00 | 47618.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.887115E+11 | 0.206160E+12 | 0.620347E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.347070E+10 | 0.379646E+11 | 53792.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.299157E+10 | 0.223069E+11 | 0.430738E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.339656E+10 | 0.948481E+10 | 0.664518E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.396931E+10 | 0.328553E+10 | 0.801913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.513472E+10 | 0.729247E+09 | 0.148504E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.616010E+10 | 60615630.96 | 0.280522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.741834E+10 | 0.00 | 0.502032E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.825048E+10 | 16348.38 | 0.655530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.525179E+10 | 0.320853E+09 | 0.224069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.344996E+10 | 0.417096E+10 | 0.323837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.282113E+10 | 0.168147E+11 | 0.576840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.308503E+10 | 0.311171E+11 | 19369.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.553997E+11 | 0.126255E+12 | 0.193995E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.282113E+10 | 0.00 | 19369.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.825048E+10 | 0.379646E+11 | 0.655530E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.355281E+10 | 0.123912E+10 | 48045070.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.553808E+10 | 0.408474E+09 | 0.156443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.948356E+10 | 16072024.71 | 0.199320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139440E+11 | 861731.23 | 0.497688E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.117156E+11 | 3150634.85 | 0.120008E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.126788E+11 | 1560.72 | 0.221279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.124346E+11 | 374.86 | 0.373870E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135662E+11 | 68.11 | 0.480967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133781E+11 | 169.35 | 0.170712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141861E+11 | 217464.17 | 0.265960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.131535E+11 | 745818.97 | 0.105540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.871581E+10 | 42737582.33 | 0.155311E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132347E+12 | 0.171138E+10 | 0.149136E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.355281E+10 | 68.11 | 48045070.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141861E+11 | 0.123912E+10 | 0.480967E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.109978E+12 | 0.00 | 0.858063E+10 | 0.00 | 0.405178E+10 | 0.00 | 0.00 | 0.00 | 0.933828E+11 | 0.00 | 0.00 | 0.00 |
February | 0.993353E+11 | 0.00 | 0.113042E+11 | 0.00 | 0.450098E+10 | 0.00 | 0.00 | 0.00 | 0.133219E+12 | 0.00 | 0.00 | 0.00 |
March | 0.109978E+12 | 0.00 | 0.182284E+11 | 0.00 | 0.642545E+10 | 0.00 | 0.00 | 0.00 | 0.181267E+12 | 0.00 | 0.00 | 0.00 |
April | 0.106431E+12 | 0.00 | 0.102223E+12 | 0.00 | 0.258680E+11 | 0.00 | 0.00 | 0.00 | 0.156767E+12 | 0.00 | 0.00 | 0.00 |
May | 0.109978E+12 | 0.00 | 0.851478E+10 | 0.00 | 0.418764E+10 | 0.00 | 0.00 | 0.00 | 0.363836E+11 | 0.00 | 0.00 | 0.00 |
June | 0.106431E+12 | 0.00 | 0.465585E+11 | 0.00 | 0.133666E+11 | 0.00 | 0.00 | 0.00 | 0.231620E+11 | 0.00 | 0.00 | 0.00 |
July | 0.109978E+12 | 0.00 | 0.272620E+12 | 0.00 | 0.644925E+11 | 0.00 | 0.00 | 0.00 | 0.221544E+11 | 0.00 | 0.00 | 0.00 |
August | 0.109978E+12 | 0.00 | 0.688806E+12 | 0.00 | 0.155955E+12 | 0.00 | 0.00 | 0.00 | 0.793380E+09 | 0.00 | 0.00 | 0.00 |
September | 0.106431E+12 | 0.00 | 0.767666E+10 | 0.00 | 0.424353E+10 | 0.00 | 0.00 | 0.00 | 0.176036E+10 | 0.00 | 0.00 | 0.00 |
October | 0.109978E+12 | 0.00 | 0.787152E+10 | 0.00 | 0.406756E+10 | 0.00 | 0.00 | 0.00 | 0.556167E+11 | 0.00 | 0.00 | 0.00 |
November | 0.106431E+12 | 0.00 | 0.156013E+11 | 0.00 | 0.565228E+10 | 0.00 | 0.00 | 0.00 | 0.119759E+12 | 0.00 | 0.00 | 0.00 |
December | 0.109978E+12 | 0.00 | 0.198391E+11 | 0.00 | 0.682766E+10 | 0.00 | 0.00 | 0.00 | 0.221221E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.129491E+13 | 0.00 | 0.120782E+13 | 0.00 | 0.299639E+12 | 0.00 | 0.00 | 0.00 | 0.104549E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.993353E+11 | 0.00 | 0.767666E+10 | 0.00 | 0.405178E+10 | 0.00 | 0.00 | 0.00 | 0.793380E+09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.109978E+12 | 0.00 | 0.688806E+12 | 0.00 | 0.155955E+12 | 0.00 | 0.00 | 0.00 | 0.221221E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.153842E+10 | 0.00 | 0.499950E+10 | 0.00 | 0.103373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138954E+10 | 0.00 | 0.108484E+11 | 0.00 | 0.211261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153842E+10 | 0.00 | 0.188465E+11 | 0.00 | 0.352078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148879E+10 | 0.00 | 0.245063E+11 | 0.00 | 0.445004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153842E+10 | 0.00 | 0.707135E+10 | 0.00 | 0.141073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.148879E+10 | 0.00 | 0.131460E+11 | 0.00 | 0.252304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153842E+10 | 0.00 | 0.202227E+11 | 0.00 | 0.388666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153842E+10 | 0.00 | 0.265531E+11 | 0.00 | 0.517934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.148879E+10 | 0.00 | 0.704616E+10 | 0.00 | 0.139318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153842E+10 | 0.00 | 0.128851E+11 | 0.00 | 0.243952E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148879E+10 | 0.00 | 0.180366E+11 | 0.00 | 0.332806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153842E+10 | 0.00 | 0.244841E+11 | 0.00 | 0.445684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181136E+11 | 0.00 | 0.188646E+12 | 0.00 | 0.357345E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.138954E+10 | 0.00 | 0.499950E+10 | 0.00 | 0.103373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153842E+10 | 0.00 | 0.265531E+11 | 0.00 | 0.517934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.147697E+11 | 0.00 | 0.198736E+11 | 0.00 | 0.436626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133404E+11 | 0.00 | 0.825348E+11 | 0.00 | 0.163280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147697E+11 | 0.00 | 0.163180E+12 | 0.00 | 0.307816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142932E+11 | 0.00 | 0.223308E+12 | 0.00 | 0.407992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147697E+11 | 0.00 | 0.597326E+11 | 0.00 | 0.120229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142932E+11 | 0.00 | 0.119871E+12 | 0.00 | 0.231130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147697E+11 | 0.00 | 0.189490E+12 | 0.00 | 0.365199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147697E+11 | 0.00 | 0.250718E+12 | 0.00 | 0.490200E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142932E+11 | 0.00 | 0.600492E+11 | 0.00 | 0.119737E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147697E+11 | 0.00 | 0.108262E+12 | 0.00 | 0.207033E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142932E+11 | 0.00 | 0.150645E+12 | 0.00 | 0.281479E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147697E+11 | 0.00 | 0.206387E+12 | 0.00 | 0.381009E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173901E+12 | 0.00 | 0.163405E+13 | 0.00 | 0.311877E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133404E+11 | 0.00 | 0.198736E+11 | 0.00 | 0.436626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147697E+11 | 0.00 | 0.250718E+12 | 0.00 | 0.490200E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.149824E+10 | 0.00 | 0.750662E+09 | 0.00 | 0.171201E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135325E+10 | 0.00 | 0.641267E+10 | 0.00 | 0.128450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149824E+10 | 0.00 | 0.148356E+11 | 0.00 | 0.282331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144991E+10 | 0.00 | 0.214382E+11 | 0.00 | 0.394082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149824E+10 | 0.00 | 0.535665E+10 | 0.00 | 0.108711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144991E+10 | 0.00 | 0.117005E+11 | 0.00 | 0.226428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149824E+10 | 0.00 | 0.187995E+11 | 0.00 | 0.363465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149824E+10 | 0.00 | 0.248875E+11 | 0.00 | 0.488311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144991E+10 | 0.00 | 0.534852E+10 | 0.00 | 0.107649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149824E+10 | 0.00 | 0.946638E+10 | 0.00 | 0.182817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144991E+10 | 0.00 | 0.132259E+11 | 0.00 | 0.249919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149824E+10 | 0.00 | 0.184729E+11 | 0.00 | 0.345095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176406E+11 | 0.00 | 0.150695E+12 | 0.00 | 0.289438E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135325E+10 | 0.00 | 0.750662E+09 | 0.00 | 0.171201E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149824E+10 | 0.00 | 0.248875E+11 | 0.00 | 0.488311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 82476731.38 | 0.00 | 0.00 | 0.550784E+11 | 0.00 | 0.46 |
February | 0.00 | 0.00 | 0.00 | 83071386.11 | 0.00 | 0.00 | 0.525667E+11 | 0.00 | 0.57 |
March | 0.00 | 0.00 | 0.00 | 0.108472E+09 | 0.00 | 0.00 | 0.688237E+11 | 0.00 | 0.75 |
April | 0.00 | 20782872.18 | 0.00 | 0.105670E+09 | 0.00 | 0.00 | 0.673465E+11 | 0.00 | 0.92 |
May | 0.00 | 13687415.21 | 0.00 | 0.119728E+09 | 0.00 | 0.00 | 0.602956E+11 | 0.00 | 1.05 |
June | 0.00 | 15436791.76 | 0.00 | 0.130233E+09 | 0.00 | 0.00 | 0.535499E+11 | 0.00 | 1.22 |
July | 0.00 | 0.323069E+09 | 0.00 | 0.126618E+09 | 0.00 | 0.00 | 0.381301E+11 | 0.00 | 1.12 |
August | 0.00 | 0.675884E+09 | 0.00 | 0.127645E+09 | 0.00 | 0.00 | 0.346767E+11 | 0.00 | 1.09 |
September | 0.00 | 0.00 | 0.00 | 0.123212E+09 | 0.00 | 0.00 | 0.564498E+11 | 0.00 | 1.22 |
October | 0.00 | 0.00 | 0.00 | 0.124470E+09 | 0.00 | 0.00 | 0.729197E+11 | 0.00 | 1.01 |
November | 0.00 | 0.00 | 0.00 | 0.109052E+09 | 0.00 | 0.00 | 0.706999E+11 | 0.00 | 0.77 |
December | 0.00 | 0.00 | 0.00 | 96973168.28 | 0.00 | 0.00 | 0.644013E+11 | 0.00 | 0.56 |
Annual Sum or Average | 0.00 | 0.104886E+10 | 0.00 | 0.133762E+10 | 0.00 | 0.00 | 0.694938E+12 | 0.00 | 0.90 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 82476731.38 | 0.00 | 0.00 | 0.346767E+11 | 0.00 | 0.46 |
Maximum of Months | 0.00 | 0.675884E+09 | 0.00 | 0.130233E+09 | 0.00 | 0.00 | 0.729197E+11 | 0.00 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.448046E+10 | 0.00 | 0.00 | 54556030.60 | 0.00 | 0.00 | 0.419366E+11 | 0.00 | 0.38 |
February | 0.226315E+10 | 0.00 | 0.00 | 67172158.06 | 0.00 | 0.00 | 0.447394E+11 | 0.00 | 0.49 |
March | 0.184205E+10 | 0.00 | 0.00 | 0.101775E+09 | 0.00 | 0.00 | 0.619856E+11 | 0.00 | 0.67 |
April | 0.433898E+10 | 16125243.98 | 0.00 | 0.101680E+09 | 0.00 | 0.00 | 0.587993E+11 | 0.00 | 0.82 |
May | 0.361115E+10 | 618009.72 | 0.00 | 94738821.26 | 0.00 | 0.00 | 0.532074E+11 | 0.00 | 0.88 |
June | 0.324725E+10 | 19043974.21 | 0.00 | 0.106759E+09 | 5979566.76 | 0.00 | 0.509475E+11 | 0.00 | 1.07 |
July | 0.706315E+10 | 0.131565E+09 | 0.00 | 0.103167E+09 | 3329002.45 | 0.00 | 0.390190E+11 | 0.00 | 1.09 |
August | 0.783749E+10 | 0.524362E+09 | 0.00 | 0.104866E+09 | 5837955.55 | 0.00 | 0.367636E+11 | 0.00 | 1.13 |
September | 0.283386E+10 | 0.00 | 0.00 | 95022007.62 | 0.00 | 0.00 | 0.466933E+11 | 0.00 | 0.94 |
October | 0.250325E+10 | 0.00 | 0.00 | 95468068.48 | 0.00 | 0.00 | 0.567990E+11 | 0.00 | 0.76 |
November | 0.197047E+10 | 0.00 | 0.00 | 88753971.59 | 0.00 | 0.00 | 0.547661E+11 | 0.00 | 0.58 |
December | 0.181085E+10 | 0.00 | 0.00 | 87375626.99 | 0.00 | 0.00 | 0.532318E+11 | 0.00 | 0.47 |
Annual Sum or Average | 0.438021E+11 | 0.691714E+09 | 0.00 | 0.110133E+10 | 15146524.77 | 0.00 | 0.598889E+12 | 0.00 | 0.78 |
Minimum of Months | 0.181085E+10 | 0.00 | 0.00 | 54556030.60 | 0.00 | 0.00 | 0.367636E+11 | 0.00 | 0.38 |
Maximum of Months | 0.783749E+10 | 0.524362E+09 | 0.00 | 0.106759E+09 | 5979566.76 | 0.00 | 0.619856E+11 | 0.00 | 1.13 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.242660E+12 | 0.00 | 0.00 | 86896099.39 | 0.00 | 0.176914E+10 | 0.947503E+11 | 0.00 | 0.29 |
February | 0.164623E+12 | 0.00 | 0.00 | 0.185887E+09 | 0.00 | 0.00 | 0.158311E+12 | 0.00 | 0.34 |
March | 0.113946E+12 | 0.00 | 0.00 | 0.407929E+09 | 0.00 | 0.00 | 0.296481E+12 | 0.00 | 0.44 |
April | 0.694532E+11 | 0.156121E+09 | 0.00 | 0.450065E+09 | 58126444.08 | 0.00 | 0.319566E+12 | 0.00 | 0.52 |
May | 0.446553E+11 | 10419257.62 | 0.00 | 0.610582E+09 | 0.00 | 0.00 | 0.397455E+12 | 0.00 | 0.71 |
June | 0.303583E+11 | 0.159179E+09 | 0.00 | 0.700528E+09 | 47902327.02 | 0.00 | 0.377317E+12 | 0.00 | 0.82 |
July | 0.331023E+11 | 0.100237E+10 | 0.00 | 0.674477E+09 | 44505693.01 | 0.00 | 0.279441E+12 | 0.00 | 0.78 |
August | 0.216762E+11 | 0.441478E+10 | 0.00 | 0.718223E+09 | 38907352.80 | 0.00 | 0.264496E+12 | 0.00 | 0.77 |
September | 0.359320E+11 | 0.00 | 0.00 | 0.618830E+09 | 0.00 | 0.00 | 0.344632E+12 | 0.00 | 0.75 |
October | 0.836513E+11 | 0.00 | 0.00 | 0.449165E+09 | 0.00 | 0.00 | 0.315348E+12 | 0.00 | 0.53 |
November | 0.132292E+12 | 0.00 | 0.00 | 0.264209E+09 | 0.00 | 0.00 | 0.211783E+12 | 0.00 | 0.37 |
December | 0.196695E+12 | 0.00 | 0.00 | 0.156743E+09 | 0.00 | 0.00 | 0.142669E+12 | 0.00 | 0.30 |
Annual Sum or Average | 0.116904E+13 | 0.574287E+10 | 0.00 | 0.532353E+10 | 0.189442E+09 | 0.176914E+10 | 0.320225E+13 | 0.00 | 0.55 |
Minimum of Months | 0.216762E+11 | 0.00 | 0.00 | 86896099.39 | 0.00 | 0.00 | 0.947503E+11 | 0.00 | 0.29 |
Maximum of Months | 0.242660E+12 | 0.441478E+10 | 0.00 | 0.718223E+09 | 58126444.08 | 0.176914E+10 | 0.397455E+12 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.286533E+11 | 0.00 | 0.00 | 125004.03 | 0.00 | 0.123087E+10 | 0.563173E+09 | 0.00 | 0.28 |
February | 0.235153E+11 | 0.00 | 0.00 | 2974736.18 | 0.00 | 0.734107E+09 | 0.370284E+10 | 0.00 | 0.32 |
March | 0.209511E+11 | 0.00 | 0.00 | 12346157.97 | 0.00 | 0.161180E+09 | 0.123557E+11 | 0.00 | 0.38 |
April | 0.127748E+11 | 3749070.65 | 0.00 | 25745868.13 | 1786571.18 | 0.00 | 0.207922E+11 | 0.00 | 0.47 |
May | 0.963189E+10 | 0.00 | 0.00 | 43981465.99 | 0.00 | 0.00 | 0.309070E+11 | 0.00 | 0.66 |
June | 0.645384E+10 | 6550158.66 | 0.00 | 56470880.71 | 3052167.56 | 0.00 | 0.328589E+11 | 0.00 | 0.81 |
July | 0.494188E+10 | 51008242.26 | 0.00 | 59244608.16 | 3420892.52 | 0.00 | 0.259846E+11 | 0.00 | 0.79 |
August | 0.415877E+10 | 0.290400E+09 | 0.00 | 59759021.82 | 10685816.51 | 0.00 | 0.225251E+11 | 0.00 | 0.76 |
September | 0.941535E+10 | 0.00 | 0.00 | 41050847.82 | 0.00 | 0.00 | 0.232891E+11 | 0.00 | 0.68 |
October | 0.156955E+11 | 0.00 | 0.00 | 17869983.71 | 0.00 | 38686811.57 | 0.155500E+11 | 0.00 | 0.44 |
November | 0.225332E+11 | 0.00 | 0.00 | 3955602.97 | 0.00 | 0.435589E+09 | 0.493213E+10 | 0.00 | 0.32 |
December | 0.273050E+11 | 0.00 | 0.00 | 245146.55 | 0.00 | 0.935583E+09 | 0.823466E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.186030E+12 | 0.351707E+09 | 0.00 | 0.323769E+09 | 18945447.78 | 0.353602E+10 | 0.194284E+12 | 0.00 | 0.52 |
Minimum of Months | 0.415877E+10 | 0.00 | 0.00 | 125004.03 | 0.00 | 0.00 | 0.563173E+09 | 0.00 | 0.28 |
Maximum of Months | 0.286533E+11 | 0.290400E+09 | 0.00 | 59759021.82 | 10685816.51 | 0.123087E+10 | 0.328589E+11 | 0.00 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.427285E+10 | 0.00 | 0.00 | 38227.68 | 0.00 | 2325428.74 | 76052883.74 | 0.00 | 0.28 |
February | 0.333862E+10 | 0.00 | 0.00 | 858555.27 | 0.00 | 0.00 | 0.826532E+09 | 0.00 | 0.35 |
March | 0.244537E+10 | 0.00 | 0.00 | 3771382.26 | 0.00 | 0.00 | 0.308693E+10 | 0.00 | 0.47 |
April | 0.166545E+10 | 2535376.98 | 0.00 | 6465534.89 | 0.00 | 0.00 | 0.463188E+10 | 0.00 | 0.69 |
May | 0.126114E+10 | 159382.92 | 0.00 | 8559335.63 | 0.00 | 0.00 | 0.546237E+10 | 0.00 | 0.89 |
June | 0.669234E+09 | 3336275.32 | 0.00 | 11934452.23 | 749544.36 | 0.00 | 0.613255E+10 | 0.00 | 1.15 |
July | 0.101246E+10 | 23695433.45 | 0.00 | 12596699.94 | 417293.61 | 0.00 | 0.500792E+10 | 0.00 | 1.22 |
August | 0.112692E+10 | 90808091.99 | 0.00 | 11822602.81 | 731793.26 | 0.00 | 0.430296E+10 | 0.00 | 1.18 |
September | 0.123582E+10 | 0.00 | 0.00 | 7193356.29 | 0.00 | 0.00 | 0.400920E+10 | 0.00 | 0.84 |
October | 0.211627E+10 | 0.00 | 0.00 | 4033922.33 | 0.00 | 0.00 | 0.317767E+10 | 0.00 | 0.55 |
November | 0.265255E+10 | 0.00 | 0.00 | 1876493.62 | 0.00 | 0.00 | 0.186975E+10 | 0.00 | 0.38 |
December | 0.367887E+10 | 0.00 | 0.00 | 406965.03 | 0.00 | 0.00 | 0.666478E+09 | 0.00 | 0.29 |
Annual Sum or Average | 0.254755E+11 | 0.120535E+09 | 0.00 | 69557527.99 | 1898631.22 | 2325428.74 | 0.392503E+11 | 0.00 | 0.69 |
Minimum of Months | 0.669234E+09 | 0.00 | 0.00 | 38227.68 | 0.00 | 0.00 | 76052883.74 | 0.00 | 0.28 |
Maximum of Months | 0.427285E+10 | 90808091.99 | 0.00 | 12596699.94 | 749544.36 | 2325428.74 | 0.613255E+10 | 0.00 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.465583E+10 | 0.00 | 0.00 | 26373.33 | 0.00 | 42309478.02 | 35474926.58 | 0.00 | 0.47 |
February | 0.383396E+10 | 0.00 | 0.00 | 768051.23 | 0.00 | 15474713.21 | 0.616973E+09 | 0.00 | 0.56 |
March | 0.313163E+10 | 0.00 | 0.00 | 3514593.98 | 0.00 | 0.00 | 0.262136E+10 | 0.00 | 0.74 |
April | 0.213422E+10 | 1941951.19 | 0.00 | 6543154.10 | 0.00 | 0.00 | 0.451226E+10 | 0.00 | 1.10 |
May | 0.170867E+10 | 126195.61 | 0.00 | 8613196.82 | 0.00 | 0.00 | 0.511452E+10 | 0.00 | 1.36 |
June | 0.108503E+10 | 2123192.87 | 0.00 | 12198457.68 | 815412.17 | 0.00 | 0.610189E+10 | 0.00 | 1.78 |
July | 0.141979E+10 | 18029593.64 | 0.00 | 12590102.35 | 453964.18 | 0.00 | 0.450937E+10 | 0.00 | 1.79 |
August | 0.161900E+10 | 70076691.76 | 0.00 | 11930062.00 | 248662.03 | 0.00 | 0.392663E+10 | 0.00 | 1.83 |
September | 0.176442E+10 | 0.00 | 0.00 | 7696817.97 | 0.00 | 0.00 | 0.399844E+10 | 0.00 | 1.39 |
October | 0.294434E+10 | 0.00 | 0.00 | 3710036.32 | 0.00 | 0.00 | 0.267761E+10 | 0.00 | 0.90 |
November | 0.406262E+10 | 0.00 | 0.00 | 540270.02 | 0.00 | 0.00 | 0.630718E+09 | 0.00 | 0.60 |
December | 0.457661E+10 | 0.00 | 0.00 | 164469.31 | 0.00 | 2140329.62 | 0.149028E+09 | 0.00 | 0.49 |
Annual Sum or Average | 0.329361E+11 | 92297625.06 | 0.00 | 68295585.12 | 1518038.39 | 59924520.85 | 0.348943E+11 | 0.00 | 1.09 |
Minimum of Months | 0.108503E+10 | 0.00 | 0.00 | 26373.33 | 0.00 | 0.00 | 35474926.58 | 0.00 | 0.47 |
Maximum of Months | 0.465583E+10 | 70076691.76 | 0.00 | 12590102.35 | 815412.17 | 42309478.02 | 0.610189E+10 | 0.00 | 1.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.536741E+10 | 0.00 | 0.00 | 2139816.35 | 0.00 | 0.283185E+09 | 0.156581E+10 | 0.00 | 0.46 |
February | 0.434979E+10 | 0.00 | 0.00 | 5475171.31 | 0.00 | 68565057.41 | 0.366720E+10 | 0.00 | 0.68 |
March | 0.386240E+10 | 0.00 | 0.00 | 10074002.65 | 0.00 | 513211.65 | 0.738430E+10 | 0.00 | 0.98 |
April | 0.277783E+10 | 6501599.69 | 0.00 | 12118429.63 | 0.00 | 0.00 | 0.805590E+10 | 0.00 | 1.25 |
May | 0.245138E+10 | 293179.76 | 0.00 | 12910602.57 | 0.00 | 0.00 | 0.755549E+10 | 0.00 | 1.36 |
June | 0.179343E+10 | 3911785.91 | 0.00 | 13899375.34 | 1135029.93 | 0.00 | 0.699910E+10 | 0.00 | 1.53 |
July | 0.200524E+10 | 40762432.06 | 0.00 | 15658873.66 | 631904.88 | 0.00 | 0.594202E+10 | 0.00 | 1.70 |
August | 0.210736E+10 | 0.169850E+09 | 0.00 | 16314325.79 | 32198.81 | 0.00 | 0.528748E+10 | 0.00 | 1.72 |
September | 0.210236E+10 | 0.00 | 0.00 | 17354173.40 | 0.00 | 0.00 | 0.756385E+10 | 0.00 | 1.73 |
October | 0.323899E+10 | 0.00 | 0.00 | 11996914.31 | 0.00 | 0.00 | 0.775016E+10 | 0.00 | 1.22 |
November | 0.464787E+10 | 0.00 | 0.00 | 4158632.02 | 0.00 | 1398812.90 | 0.297066E+10 | 0.00 | 0.65 |
December | 0.514362E+10 | 0.00 | 0.00 | 4052885.90 | 0.00 | 52271620.08 | 0.281645E+10 | 0.00 | 0.55 |
Annual Sum or Average | 0.398477E+11 | 0.221319E+09 | 0.00 | 0.126153E+09 | 1799133.62 | 0.405934E+09 | 0.675584E+11 | 0.00 | 1.16 |
Minimum of Months | 0.179343E+10 | 0.00 | 0.00 | 2139816.35 | 0.00 | 0.00 | 0.156581E+10 | 0.00 | 0.46 |
Maximum of Months | 0.536741E+10 | 0.169850E+09 | 0.00 | 17354173.40 | 1135029.93 | 0.283185E+09 | 0.805590E+10 | 0.00 | 1.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.523583E+10 | 0.00 | 0.00 | 342850.74 | 0.00 | 0.00 | 0.461162E+09 | 0.00 | 0.56 |
February | 0.295716E+10 | 0.00 | 0.00 | 2774834.01 | 0.00 | 0.00 | 0.281102E+10 | 0.00 | 0.75 |
March | 0.112777E+10 | 0.00 | 0.00 | 9332336.75 | 0.00 | 0.00 | 0.723667E+10 | 0.00 | 1.14 |
April | 0.656704E+09 | 4600829.47 | 0.00 | 16232127.55 | 0.00 | 0.00 | 0.927545E+10 | 0.00 | 1.75 |
May | 0.107253E+10 | 166356.12 | 0.00 | 15731035.43 | 0.00 | 0.00 | 0.727884E+10 | 0.00 | 1.81 |
June | 0.505490E+09 | 9298325.11 | 0.00 | 18016697.97 | 905614.90 | 0.00 | 0.769682E+10 | 0.00 | 2.28 |
July | 0.864004E+09 | 49747234.43 | 0.00 | 22998318.25 | 78155.67 | 0.00 | 0.726270E+10 | 0.00 | 2.72 |
August | 0.983242E+09 | 0.159436E+09 | 0.00 | 23588811.32 | 665860.52 | 0.00 | 0.657917E+10 | 0.00 | 2.60 |
September | 0.974172E+09 | 0.00 | 0.00 | 12496747.37 | 0.00 | 0.00 | 0.578470E+10 | 0.00 | 1.81 |
October | 0.150172E+10 | 0.00 | 0.00 | 7520349.79 | 0.00 | 0.00 | 0.574135E+10 | 0.00 | 1.22 |
November | 0.167939E+10 | 0.00 | 0.00 | 5145851.59 | 0.00 | 0.00 | 0.452201E+10 | 0.00 | 0.81 |
December | 0.191817E+10 | 0.00 | 0.00 | 4912694.05 | 0.00 | 0.00 | 0.436192E+10 | 0.00 | 0.66 |
Annual Sum or Average | 0.194762E+11 | 0.223248E+09 | 0.00 | 0.139093E+09 | 1649631.10 | 0.00 | 0.690118E+11 | 0.00 | 1.51 |
Minimum of Months | 0.505490E+09 | 0.00 | 0.00 | 342850.74 | 0.00 | 0.00 | 0.461162E+09 | 0.00 | 0.56 |
Maximum of Months | 0.523583E+10 | 0.159436E+09 | 0.00 | 23588811.32 | 905614.90 | 0.00 | 0.927545E+10 | 0.00 | 2.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.216414E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207338E+11 | 0.00 | 0.00 | 0.29 |
February | 0.272901E+11 | 0.00 | 0.00 | 224609.19 | 0.00 | 0.102738E+11 | 0.550897E+09 | 0.00 | 0.32 |
March | 0.371109E+11 | 0.00 | 0.00 | 1364994.38 | 0.00 | 0.280178E+10 | 0.252569E+10 | 0.00 | 0.36 |
April | 0.260974E+11 | 23780343.83 | 0.00 | 16635857.68 | 7310989.05 | 0.266158E+09 | 0.132719E+11 | 0.00 | 0.43 |
May | 0.183549E+11 | 2338146.30 | 0.00 | 49990869.24 | 0.00 | 0.00 | 0.320851E+11 | 0.00 | 0.68 |
June | 0.108966E+11 | 29158468.36 | 0.00 | 73569842.71 | 6025026.89 | 0.00 | 0.385285E+11 | 0.00 | 0.86 |
July | 0.920126E+10 | 0.188755E+09 | 0.00 | 79715537.73 | 5597807.32 | 0.00 | 0.313341E+11 | 0.00 | 0.88 |
August | 0.900384E+10 | 0.794615E+09 | 0.00 | 69468768.60 | 4893663.03 | 0.00 | 0.248587E+11 | 0.00 | 0.79 |
September | 0.195388E+11 | 0.00 | 0.00 | 38939768.14 | 0.00 | 0.00 | 0.201077E+11 | 0.00 | 0.65 |
October | 0.328879E+11 | 0.00 | 0.00 | 6535848.87 | 0.00 | 0.610575E+09 | 0.610654E+10 | 0.00 | 0.42 |
November | 0.329932E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557574E+10 | 0.00 | 0.00 | 0.32 |
December | 0.249023E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161382E+11 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.269919E+12 | 0.103865E+10 | 0.00 | 0.336446E+09 | 23827486.29 | 0.564001E+11 | 0.169369E+12 | 0.00 | 0.52 |
Minimum of Months | 0.900384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.371109E+11 | 0.794615E+09 | 0.00 | 79715537.73 | 7310989.05 | 0.207338E+11 | 0.385285E+11 | 0.00 | 0.88 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.253257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235422E+11 | 0.00 | 0.00 | 0.51 |
February | 0.338537E+11 | 0.00 | 0.00 | 212333.51 | 0.00 | 0.965485E+10 | 0.595487E+09 | 0.00 | 0.57 |
March | 0.390214E+11 | 0.00 | 0.00 | 13432795.41 | 0.00 | 0.231082E+10 | 0.100702E+11 | 0.00 | 0.67 |
April | 0.243156E+11 | 31002411.92 | 0.00 | 44117280.79 | 438453.60 | 0.480590E+09 | 0.294151E+11 | 0.00 | 0.91 |
May | 0.219820E+11 | 2278473.58 | 0.00 | 69699048.02 | 0.00 | 5017717.07 | 0.393495E+11 | 0.00 | 1.26 |
June | 0.129649E+11 | 21058573.45 | 0.00 | 0.106114E+09 | 6975521.69 | 0.00 | 0.527389E+11 | 0.00 | 1.67 |
July | 0.120097E+11 | 0.171391E+09 | 0.00 | 0.114393E+09 | 6480904.92 | 0.00 | 0.382333E+11 | 0.00 | 1.61 |
August | 0.102620E+11 | 0.737467E+09 | 0.00 | 0.109150E+09 | 899378.55 | 0.00 | 0.341358E+11 | 0.00 | 1.57 |
September | 0.235407E+11 | 0.00 | 0.00 | 61749613.92 | 0.00 | 5529635.84 | 0.292817E+11 | 0.00 | 1.32 |
October | 0.334923E+11 | 0.00 | 0.00 | 19968945.51 | 0.00 | 0.761378E+09 | 0.148686E+11 | 0.00 | 0.80 |
November | 0.375310E+11 | 0.00 | 0.00 | 142873.89 | 0.00 | 0.687010E+10 | 0.256716E+09 | 0.00 | 0.58 |
December | 0.287914E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186750E+11 | 0.00 | 0.00 | 0.51 |
Annual Sum or Average | 0.303090E+12 | 0.963198E+09 | 0.00 | 0.538980E+09 | 14794258.76 | 0.623055E+11 | 0.248945E+12 | 0.00 | 1.00 |
Minimum of Months | 0.102620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.390214E+11 | 0.737467E+09 | 0.00 | 0.114393E+09 | 6975521.69 | 0.235422E+11 | 0.527389E+11 | 0.00 | 1.67 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.416797E+11 | 0.00 | 0.00 | 14178328.29 | 0.00 | 0.187289E+11 | 0.105456E+11 | 0.00 | 0.48 |
February | 0.396029E+11 | 0.00 | 0.00 | 48477200.92 | 0.00 | 0.877026E+10 | 0.295024E+11 | 0.00 | 0.67 |
March | 0.414054E+11 | 0.00 | 0.00 | 81792318.44 | 0.00 | 0.177634E+10 | 0.580268E+11 | 0.00 | 0.90 |
April | 0.307924E+11 | 0.114591E+09 | 0.00 | 91258738.29 | 0.00 | 0.385076E+09 | 0.578935E+11 | 0.00 | 1.04 |
May | 0.292870E+11 | 4915719.45 | 0.00 | 0.112457E+09 | 0.00 | 0.00 | 0.615054E+11 | 0.00 | 1.27 |
June | 0.230440E+11 | 38071127.87 | 0.00 | 0.110580E+09 | 9580856.75 | 0.00 | 0.536500E+11 | 0.00 | 1.37 |
July | 0.182598E+11 | 0.398720E+09 | 0.00 | 0.125387E+09 | 8901502.20 | 0.00 | 0.457241E+11 | 0.00 | 1.45 |
August | 0.162948E+11 | 0.180245E+10 | 0.00 | 0.138598E+09 | 0.00 | 0.00 | 0.392779E+11 | 0.00 | 1.40 |
September | 0.253601E+11 | 0.00 | 0.00 | 0.172811E+09 | 0.00 | 0.00 | 0.656388E+11 | 0.00 | 1.71 |
October | 0.354967E+11 | 0.00 | 0.00 | 0.106489E+09 | 0.00 | 0.337479E+09 | 0.644433E+11 | 0.00 | 1.15 |
November | 0.469859E+11 | 0.00 | 0.00 | 27644597.88 | 0.00 | 0.566672E+10 | 0.162117E+11 | 0.00 | 0.61 |
December | 0.396955E+11 | 0.00 | 0.00 | 26416171.64 | 0.00 | 0.167799E+11 | 0.176605E+11 | 0.00 | 0.52 |
Annual Sum or Average | 0.387904E+12 | 0.235875E+10 | 0.00 | 0.105609E+10 | 18482358.95 | 0.524447E+11 | 0.520080E+12 | 0.00 | 1.05 |
Minimum of Months | 0.162948E+11 | 0.00 | 0.00 | 14178328.29 | 0.00 | 0.00 | 0.105456E+11 | 0.00 | 0.48 |
Maximum of Months | 0.469859E+11 | 0.180245E+10 | 0.00 | 0.172811E+09 | 9580856.75 | 0.187289E+11 | 0.656388E+11 | 0.00 | 1.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.343285E+11 | 0.00 | 0.00 | 49052.48 | 0.00 | 0.166854E+11 | 0.196209E+09 | 0.00 | 0.54 |
February | 0.360060E+11 | 0.00 | 0.00 | 4336370.76 | 0.00 | 0.730570E+10 | 0.364155E+10 | 0.00 | 0.61 |
March | 0.412166E+11 | 0.00 | 0.00 | 15576449.24 | 0.00 | 0.126453E+10 | 0.130580E+11 | 0.00 | 0.75 |
April | 0.296641E+11 | 55690873.05 | 0.00 | 38682183.30 | 685884.92 | 92227150.34 | 0.251933E+11 | 0.00 | 0.97 |
May | 0.218863E+11 | 2158593.87 | 0.00 | 0.112794E+09 | 0.00 | 4238344.20 | 0.417547E+11 | 0.00 | 1.44 |
June | 0.157469E+11 | 91715478.66 | 0.00 | 96241992.92 | 7317516.17 | 0.00 | 0.397114E+11 | 0.00 | 1.62 |
July | 0.112730E+11 | 0.454702E+09 | 0.00 | 0.122587E+09 | 1086150.45 | 0.00 | 0.378795E+11 | 0.00 | 1.82 |
August | 0.108682E+11 | 0.135381E+10 | 0.00 | 0.109962E+09 | 5943452.04 | 0.00 | 0.280696E+11 | 0.00 | 1.49 |
September | 0.220548E+11 | 0.00 | 0.00 | 75070586.85 | 0.00 | 0.00 | 0.300728E+11 | 0.00 | 1.45 |
October | 0.384521E+11 | 0.00 | 0.00 | 18021625.93 | 0.00 | 80750992.53 | 0.132743E+11 | 0.00 | 0.88 |
November | 0.416836E+11 | 0.00 | 0.00 | 1575788.11 | 0.00 | 0.386962E+10 | 0.133600E+10 | 0.00 | 0.61 |
December | 0.380319E+11 | 0.00 | 0.00 | 366278.68 | 0.00 | 0.111022E+11 | 0.584120E+09 | 0.00 | 0.53 |
Annual Sum or Average | 0.341212E+12 | 0.195808E+10 | 0.00 | 0.595263E+09 | 15033003.59 | 0.404046E+11 | 0.234771E+12 | 0.00 | 1.06 |
Minimum of Months | 0.108682E+11 | 0.00 | 0.00 | 49052.48 | 0.00 | 0.00 | 0.196209E+09 | 0.00 | 0.53 |
Maximum of Months | 0.416836E+11 | 0.135381E+10 | 0.00 | 0.122587E+09 | 7317516.17 | 0.166854E+11 | 0.417547E+11 | 0.00 | 1.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.109751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281806E+10 | 0.00 | 0.00 | 0.29 |
February | 0.163143E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191172E+10 | 0.00 | 0.00 | 0.32 |
March | 0.320009E+10 | 0.00 | 0.00 | 30738.83 | 0.00 | 0.789392E+09 | 59336238.89 | 0.00 | 0.36 |
April | 0.255555E+10 | 554705.86 | 0.00 | 1206460.01 | 223978.81 | 0.300189E+09 | 0.937358E+09 | 0.00 | 0.42 |
May | 0.207478E+10 | 0.00 | 0.00 | 4137907.16 | 0.00 | 30725937.81 | 0.276019E+10 | 0.00 | 0.66 |
June | 0.131629E+10 | 1101546.41 | 0.00 | 6640089.94 | 382644.07 | 0.00 | 0.356444E+10 | 0.00 | 0.86 |
July | 0.976232E+09 | 9233395.70 | 0.00 | 7920810.98 | 428870.38 | 0.00 | 0.313451E+10 | 0.00 | 0.89 |
August | 0.103212E+10 | 50631742.47 | 0.00 | 6755932.94 | 1339659.20 | 0.00 | 0.222810E+10 | 0.00 | 0.78 |
September | 0.216290E+10 | 0.00 | 0.00 | 2963757.00 | 0.00 | 29917516.87 | 0.151704E+10 | 0.00 | 0.62 |
October | 0.302101E+10 | 0.00 | 0.00 | 262126.99 | 0.00 | 0.410930E+09 | 0.199923E+09 | 0.00 | 0.40 |
November | 0.194518E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156669E+10 | 0.00 | 0.00 | 0.32 |
December | 0.115169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256935E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.221648E+11 | 61521390.44 | 0.00 | 29917823.85 | 2375152.46 | 0.104270E+11 | 0.144009E+11 | 0.00 | 0.52 |
Minimum of Months | 0.976232E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.320009E+10 | 50631742.47 | 0.00 | 7920810.98 | 1339659.20 | 0.281806E+10 | 0.356444E+10 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.154919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273310E+10 | 0.00 | 0.00 | 0.49 |
February | 0.215429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174964E+10 | 0.00 | 0.00 | 0.55 |
March | 0.329868E+10 | 0.00 | 0.00 | 779491.19 | 0.00 | 0.640750E+09 | 0.654688E+09 | 0.00 | 0.63 |
April | 0.209544E+10 | 544652.91 | 0.00 | 3794645.53 | 250189.21 | 0.207787E+09 | 0.263145E+10 | 0.00 | 0.86 |
May | 0.207077E+10 | 0.00 | 0.00 | 6467702.03 | 0.00 | 48106600.63 | 0.379629E+10 | 0.00 | 1.22 |
June | 0.127684E+10 | 826537.88 | 0.00 | 10038274.55 | 427421.75 | 518306.46 | 0.522293E+10 | 0.00 | 1.66 |
July | 0.110463E+10 | 8205999.26 | 0.00 | 11828000.98 | 463192.13 | 0.00 | 0.394834E+10 | 0.00 | 1.63 |
August | 0.958189E+09 | 47582239.71 | 0.00 | 10917846.38 | 357371.36 | 0.00 | 0.332073E+10 | 0.00 | 1.59 |
September | 0.218719E+10 | 0.00 | 0.00 | 5606622.09 | 0.00 | 25939121.54 | 0.267166E+10 | 0.00 | 1.26 |
October | 0.276462E+10 | 0.00 | 0.00 | 1373859.50 | 0.00 | 0.412968E+09 | 0.109092E+10 | 0.00 | 0.74 |
November | 0.234428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154792E+10 | 0.00 | 0.00 | 0.55 |
December | 0.158845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250076E+10 | 0.00 | 0.00 | 0.48 |
Annual Sum or Average | 0.233926E+11 | 57159429.76 | 0.00 | 50806442.26 | 1498174.45 | 0.986748E+10 | 0.233370E+11 | 0.00 | 0.97 |
Minimum of Months | 0.958189E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 0.329868E+10 | 47582239.71 | 0.00 | 11828000.98 | 463192.13 | 0.273310E+10 | 0.522293E+10 | 0.00 | 1.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.283269E+10 | 0.00 | 0.00 | 733631.69 | 0.00 | 0.296655E+10 | 0.593974E+09 | 0.00 | 0.47 |
February | 0.295429E+10 | 0.00 | 0.00 | 3242760.34 | 0.00 | 0.166769E+10 | 0.222373E+10 | 0.00 | 0.63 |
March | 0.360172E+10 | 0.00 | 0.00 | 6513306.63 | 0.00 | 0.849589E+09 | 0.481158E+10 | 0.00 | 0.84 |
April | 0.285382E+10 | 2747480.45 | 0.00 | 8221206.42 | 0.00 | 0.387325E+09 | 0.536206E+10 | 0.00 | 1.02 |
May | 0.305673E+10 | 0.00 | 0.00 | 10378175.33 | 0.00 | 61579313.59 | 0.600472E+10 | 0.00 | 1.24 |
June | 0.250386E+10 | 1462202.03 | 0.00 | 10463803.63 | 621091.95 | 492375.49 | 0.539255E+10 | 0.00 | 1.39 |
July | 0.196950E+10 | 19974498.73 | 0.00 | 13604737.50 | 122618.21 | 0.00 | 0.480552E+10 | 0.00 | 1.50 |
August | 0.173421E+10 | 0.113319E+09 | 0.00 | 14147906.91 | 0.00 | 0.00 | 0.392543E+10 | 0.00 | 1.45 |
September | 0.277653E+10 | 0.00 | 0.00 | 15469363.97 | 0.00 | 38938268.73 | 0.625318E+10 | 0.00 | 1.68 |
October | 0.317049E+10 | 0.00 | 0.00 | 8362810.19 | 0.00 | 0.419951E+09 | 0.547858E+10 | 0.00 | 1.06 |
November | 0.344351E+10 | 0.00 | 0.00 | 1644740.11 | 0.00 | 0.166706E+10 | 0.976894E+09 | 0.00 | 0.58 |
December | 0.267847E+10 | 0.00 | 0.00 | 1581256.19 | 0.00 | 0.263910E+10 | 0.108533E+10 | 0.00 | 0.49 |
Annual Sum or Average | 0.335758E+11 | 0.137503E+09 | 0.00 | 94363698.92 | 743710.16 | 0.106983E+11 | 0.469136E+11 | 0.00 | 1.03 |
Minimum of Months | 0.173421E+10 | 0.00 | 0.00 | 733631.69 | 0.00 | 0.00 | 0.593974E+09 | 0.00 | 0.47 |
Maximum of Months | 0.360172E+10 | 0.113319E+09 | 0.00 | 15469363.97 | 621091.95 | 0.296655E+10 | 0.625318E+10 | 0.00 | 1.68 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.215902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255116E+10 | 0.00 | 0.00 | 0.54 |
February | 0.264714E+10 | 0.00 | 0.00 | 295690.38 | 0.00 | 0.141419E+10 | 0.278556E+09 | 0.00 | 0.61 |
March | 0.364804E+10 | 0.00 | 0.00 | 1214160.01 | 0.00 | 0.547580E+09 | 0.110327E+10 | 0.00 | 0.74 |
April | 0.289484E+10 | 1471186.98 | 0.00 | 3616565.40 | 0.00 | 0.210158E+09 | 0.230052E+10 | 0.00 | 0.98 |
May | 0.240602E+10 | 0.00 | 0.00 | 10642302.38 | 0.00 | 26365848.80 | 0.405616E+10 | 0.00 | 1.43 |
June | 0.180017E+10 | 3277878.40 | 0.00 | 9087614.18 | 471419.39 | 0.00 | 0.393885E+10 | 0.00 | 1.67 |
July | 0.120570E+10 | 21222019.95 | 0.00 | 14050083.62 | 358137.03 | 0.00 | 0.398400E+10 | 0.00 | 1.89 |
August | 0.124370E+10 | 82286596.73 | 0.00 | 10958141.78 | 1484988.04 | 0.00 | 0.266973E+10 | 0.00 | 1.52 |
September | 0.249962E+10 | 0.00 | 0.00 | 6677804.18 | 0.00 | 731680.63 | 0.265434E+10 | 0.00 | 1.44 |
October | 0.346481E+10 | 0.00 | 0.00 | 1459707.50 | 0.00 | 0.289398E+09 | 0.106494E+10 | 0.00 | 0.85 |
November | 0.305442E+10 | 0.00 | 0.00 | 84867.14 | 0.00 | 0.116231E+10 | 72304483.18 | 0.00 | 0.61 |
December | 0.229198E+10 | 0.00 | 0.00 | 4612.00 | 0.00 | 0.219051E+10 | 14270408.93 | 0.00 | 0.53 |
Annual Sum or Average | 0.293155E+11 | 0.108258E+09 | 0.00 | 58091548.55 | 2314544.45 | 0.839240E+10 | 0.221369E+11 | 0.00 | 1.07 |
Minimum of Months | 0.120570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.364804E+10 | 82286596.73 | 0.00 | 14050083.62 | 1484988.04 | 0.255116E+10 | 0.405616E+10 | 0.00 | 1.89 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 2929495.30 | 0.00 | 0.00 | 0.621016E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7279200.67 | 0.00 | 0.00 | 0.514090E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 14274707.39 | 0.00 | 0.00 | 0.541008E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 17765980.77 | 0.00 | 0.00 | 0.420321E+09 | 0.00 | 0.29 |
May | 0.00 | 16442.90 | 0.00 | 4250601.52 | 0.00 | 0.00 | 0.379242E+09 | 0.00 | 0.29 |
June | 0.00 | 0.00 | 0.00 | 9169027.67 | 0.00 | 0.00 | 0.294960E+09 | 0.00 | 0.30 |
July | 0.00 | 4142764.48 | 0.00 | 12076988.02 | 0.00 | 0.00 | 0.167351E+09 | 0.00 | 0.28 |
August | 0.00 | 13439635.44 | 0.00 | 15689288.83 | 0.00 | 0.00 | 0.125443E+09 | 0.00 | 0.31 |
September | 0.00 | 93951.72 | 0.00 | 4140661.45 | 0.00 | 0.00 | 0.255238E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 8691549.78 | 0.00 | 0.00 | 0.424976E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 12366029.41 | 0.00 | 0.00 | 0.494921E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 17072683.83 | 0.00 | 0.00 | 0.575757E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 17692794.54 | 0.00 | 0.125706E+09 | 0.00 | 0.00 | 0.481432E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2929495.30 | 0.00 | 0.00 | 0.125443E+09 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 13439635.44 | 0.00 | 17765980.77 | 0.00 | 0.00 | 0.621016E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.336394E+09 | 0.00 | 0.00 | 12669182.61 | 0.00 | 0.00 | 0.589151E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 57422500.03 | 0.00 | 0.00 | 0.515887E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.125447E+09 | 0.00 | 0.00 | 0.542692E+10 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 0.163044E+09 | 0.00 | 0.00 | 0.421689E+10 | 0.00 | 0.29 |
May | 0.00 | 134316.93 | 0.00 | 35758169.93 | 0.00 | 0.00 | 0.380637E+10 | 0.00 | 0.29 |
June | 0.00 | 0.00 | 0.00 | 84047515.41 | 0.00 | 0.00 | 0.295984E+10 | 0.00 | 0.30 |
July | 0.00 | 40889404.90 | 0.00 | 0.113457E+09 | 0.00 | 0.00 | 0.168298E+10 | 0.00 | 0.28 |
August | 0.00 | 0.133375E+09 | 0.00 | 0.148445E+09 | 0.00 | 0.00 | 0.126483E+10 | 0.00 | 0.31 |
September | 0.00 | 745185.75 | 0.00 | 34892246.92 | 0.00 | 0.00 | 0.258115E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 73711285.89 | 0.00 | 0.00 | 0.426546E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.104983E+09 | 0.00 | 0.00 | 0.496853E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.147241E+09 | 0.00 | 0.00 | 0.578100E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.336394E+09 | 0.175144E+09 | 0.00 | 0.110112E+10 | 0.00 | 0.00 | 0.480043E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 12669182.61 | 0.00 | 0.00 | 0.126483E+10 | 0.00 | 0.28 |
Maximum of Months | 0.336394E+09 | 0.133375E+09 | 0.00 | 0.163044E+09 | 0.00 | 0.00 | 0.589151E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.231075E+09 | 0.00 | 0.00 | 571165.87 | 0.00 | 0.00 | 0.385406E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 4865821.39 | 0.00 | 0.00 | 0.516874E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 11635647.14 | 0.00 | 0.00 | 0.543671E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 15771215.79 | 0.00 | 0.00 | 0.422271E+09 | 0.00 | 0.29 |
May | 0.00 | 13114.09 | 0.00 | 3229932.38 | 0.00 | 0.00 | 0.381299E+09 | 0.00 | 0.29 |
June | 0.00 | 0.00 | 0.00 | 8222911.14 | 0.00 | 0.00 | 0.296261E+09 | 0.00 | 0.30 |
July | 0.00 | 4109659.18 | 0.00 | 11253158.64 | 0.00 | 0.00 | 0.168410E+09 | 0.00 | 0.28 |
August | 0.00 | 13372807.04 | 0.00 | 14704337.70 | 0.00 | 0.00 | 0.126666E+09 | 0.00 | 0.31 |
September | 0.00 | 69544.59 | 0.00 | 3085069.26 | 0.00 | 0.00 | 0.259976E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 6566164.79 | 0.00 | 0.00 | 0.427730E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 9499154.78 | 0.00 | 0.00 | 0.498057E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 13633815.79 | 0.00 | 0.00 | 0.579208E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.231075E+09 | 17565124.90 | 0.00 | 0.103038E+09 | 0.00 | 0.00 | 0.460583E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 571165.87 | 0.00 | 0.00 | 0.126666E+09 | 0.00 | 0.28 |
Maximum of Months | 0.231075E+09 | 13372807.04 | 0.00 | 15771215.79 | 0.00 | 0.00 | 0.579208E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.509285E+09 | 0.00 | 0.00 | 0.436969E+12 | 0.00 | 9.52 |
February | 0.00 | 0.00 | 0.00 | 0.946415E+09 | 0.00 | 0.00 | 0.661674E+12 | 0.00 | 17.82 |
March | 0.00 | 0.00 | 0.00 | 0.148497E+10 | 0.00 | 0.00 | 0.100923E+13 | 0.00 | 27.96 |
April | 0.00 | 31962.02 | 0.00 | 0.220595E+10 | 0.00 | 0.00 | 0.113003E+13 | 0.00 | 39.38 |
May | 0.00 | 0.00 | 0.00 | 0.569359E+09 | 0.00 | 0.00 | 0.385064E+12 | 0.00 | 17.24 |
June | 0.00 | 0.00 | 0.00 | 0.111564E+10 | 0.00 | 0.00 | 0.568406E+12 | 0.00 | 32.71 |
July | 0.00 | 0.825120E+09 | 0.00 | 0.203222E+10 | 0.00 | 0.00 | 0.658261E+12 | 0.00 | 43.10 |
August | 0.00 | 0.324170E+10 | 0.00 | 0.272915E+10 | 0.00 | 0.00 | 0.559892E+12 | 0.00 | 45.06 |
September | 0.00 | 0.00 | 0.00 | 0.526609E+09 | 0.00 | 0.00 | 0.341695E+12 | 0.00 | 19.94 |
October | 0.00 | 0.00 | 0.00 | 0.103192E+10 | 0.00 | 0.00 | 0.649078E+12 | 0.00 | 24.05 |
November | 0.00 | 0.00 | 0.00 | 0.144742E+10 | 0.00 | 0.00 | 0.923757E+12 | 0.00 | 27.71 |
December | 0.00 | 0.00 | 0.00 | 0.203879E+10 | 0.00 | 0.00 | 0.129260E+13 | 0.00 | 30.73 |
Annual Sum or Average | 0.00 | 0.406686E+10 | 0.00 | 0.166377E+11 | 0.00 | 0.00 | 0.861666E+13 | 0.00 | 28.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.509285E+09 | 0.00 | 0.00 | 0.341695E+12 | 0.00 | 9.52 |
Maximum of Months | 0.00 | 0.324170E+10 | 0.00 | 0.272915E+10 | 0.00 | 0.00 | 0.129260E+13 | 0.00 | 45.06 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:49
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.116671E+12 | 0.107302E+11 | 0.00 | 0.211981E+13 | 0.125473E+12 |
February | 0.227478E+12 | 0.973646E+10 | 0.00 | 0.236751E+13 | 0.181250E+12 |
March | 0.416171E+12 | 0.919389E+10 | 0.00 | 0.305852E+13 | 0.263790E+12 |
April | 0.643894E+12 | 0.889504E+10 | 0.00 | 0.323801E+13 | 0.531017E+12 |
May | 0.847576E+12 | 0.703421E+10 | 0.00 | 0.255519E+13 | 0.334168E+12 |
June | 0.861061E+12 | 0.579536E+10 | 0.00 | 0.255232E+13 | 0.656654E+12 |
July | 0.905133E+12 | 0.510115E+10 | 0.00 | 0.264507E+13 | 0.131652E+13 |
August | 0.709865E+12 | 0.401200E+10 | 0.00 | 0.222494E+13 | 0.207447E+13 |
September | 0.492502E+12 | 0.333615E+10 | 0.00 | 0.248798E+13 | 0.474110E+12 |
October | 0.313203E+12 | 0.741484E+10 | 0.00 | 0.283042E+13 | 0.223125E+12 |
November | 0.133777E+12 | 0.861149E+10 | 0.00 | 0.290180E+13 | 0.258858E+12 |
December | 0.866473E+11 | 0.920821E+10 | 0.00 | 0.312595E+13 | 0.351584E+12 |
Annual Sum or Average | 0.575398E+13 | 0.890690E+11 | 0.00 | 0.321075E+14 | 0.679102E+13 |
Minimum of Months | 0.866473E+11 | 0.333615E+10 | 0.00 | 0.211981E+13 | 0.125473E+12 |
Maximum of Months | 0.905133E+12 | 0.107302E+11 | 0.00 | 0.323801E+13 | 0.207447E+13 |