Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000
Simulation Timestamp: 2024-07-03 12:21:43
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:43
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 34229.69 | 738.98 | 738.98 |
Net Site Energy | 34229.69 | 738.98 | 738.98 |
Total Source Energy | 108405.42 | 2340.34 | 2340.34 |
Net Source Energy | 108405.42 | 2340.34 | 2340.34 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6993.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3209.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 343.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2566.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2432.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 949.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2647.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19921.36 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 129.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 281.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 34229.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22201.53 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 6993.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3209.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 343.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 55.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2505.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2432.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 949.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 2647.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19921.36 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 129.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 281.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 6993.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3209.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 343.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 2566.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2432.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 949.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 2647.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19921.36 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 129.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 281.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 76.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 287.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
Other | 375.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 738.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 76.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 287.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
Other | 375.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 738.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 34229.687 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 34229.687 | 100.00 |
Total On-Site and Utility Electric Sources | 34229.687 | 100.00 |
Total Electricity End Uses | 34229.687 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 7885.24 | 100.00 |
Air to Air Heat Recovery for Heating | 0.00 | 0.00 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 7885.24 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 22201.53 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 22201.53 | 100.00 |
Total Water End Uses | 22201.53 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 5837.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:43
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Latitude [deg] | 10.82 |
Longitude [deg] | 106.67 |
Elevation [m] | 5.00 |
Time Zone | 7.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 8.6849 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 8.6849 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 8.7339 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 8.7339 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.6849 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 8.6849 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 8.6849 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 8.6849 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 8.6849 | 18.58 | 484.4232 | |
Total | 46320.38 | 8.7339 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 8.7339 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.6845 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:43
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-AUG-15:20 | - | - | - | - | - | - | - | - | - | - | - | 21-FEB-14:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 456205.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 280450.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 233302.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 150799.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 43658.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 97598.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 22653.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2068653.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 456205.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 280450.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3430.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 150799.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 43658.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 97598.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 22653.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:43
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 22149.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 10165.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1086.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8128.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7703.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3006.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 8383.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 411.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 890.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 108405.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 478.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 219.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 23.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 166.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 64.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 180.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 8.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 19.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2340.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 478.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 219.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 23.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 166.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 64.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 180.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 8.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 19.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2340.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:43
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 5.74 | 0.368999 | 0.000000 | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.97 | 0.318681 | 0.324000 | 1.93 | 0.849815 | 0.500000 | 0.001196 |
CORE_MID VAV BOX COMPONENT | 56.31 | 0.337770 | 0.337000 | 18.98 | 0.900719 | 0.500000 | 0.001128 |
CORE_TOP VAV BOX COMPONENT | 5.58 | 0.340702 | 0.346000 | 1.93 | 0.908539 | 0.500000 | 0.001118 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.07 | 0.224093 | 0.228000 | 0.242985 | 0.597581 | 0.500000 | 0.001700 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.02 | 0.150308 | 0.200000 | 0.204786 | 0.400822 | 0.500000 | 0.002535 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.03 | 0.231639 | 0.235000 | 0.242292 | 0.617703 | 0.500000 | 0.001645 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.35 | 0.113726 | 0.200000 | 0.270659 | 0.303269 | 0.500000 | 0.003350 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 10.10 | 0.236487 | 0.236000 | 2.38 | 0.630632 | 0.500000 | 0.001611 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 10.51 | 0.146451 | 0.200000 | 2.10 | 0.390536 | 0.500000 | 0.002602 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 9.72 | 0.245799 | 0.245000 | 2.38 | 0.655465 | 0.500000 | 0.001550 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 11.76 | 0.130890 | 0.200000 | 2.35 | 0.349039 | 0.500000 | 0.002911 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.12 | 0.213837 | 0.217000 | 0.242353 | 0.570233 | 0.500000 | 0.001782 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.06 | 0.145325 | 0.200000 | 0.211808 | 0.387533 | 0.500000 | 0.002622 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.08 | 0.221302 | 0.225000 | 0.242817 | 0.590138 | 0.500000 | 0.001722 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.24 | 0.123745 | 0.200000 | 0.248746 | 0.329986 | 0.500000 | 0.003079 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 64555.98 |
CORE_MID VAV BOX REHEAT COIL | 633514.31 |
CORE_TOP VAV BOX REHEAT COIL | 64483.44 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 8111.58 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 6836.39 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 8088.44 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 9035.45 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 79561.50 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 70164.41 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 79468.17 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 78506.22 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 8090.48 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 7070.81 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 8105.98 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 8303.92 |
VAV_BOT WITH REHEAT HEATING COIL | 44870.97 |
VAV_MID WITH REHEAT HEATING COIL | 419568.15 |
VAV_TOP WITH REHEAT HEATING COIL | 44689.88 |
CAV_BAS HEATING COIL | 248495.45 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 8144.41 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 376.24 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 3762.38 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 376.24 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.471008 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.48 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.456519 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 24.57 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.22 | 2.89 | 10.44 | 2.89 | 9.66 | 9.66 | 0.300000 | 0.299590 | 9.66 |
VAV_MID WITH REHEAT | 49.20 | 28.19 | 98.39 | 28.19 | 90.34 | 90.34 | 0.300000 | 0.312087 | 90.34 |
VAV_TOP WITH REHEAT | 5.04 | 2.88 | 10.08 | 2.88 | 9.62 | 9.62 | 0.300000 | 0.299019 | 9.62 |
CAV_BAS | 0.000000 | 0.000000 | 5.74 | 1.20 | 5.74 | 5.74 | 1.00 | 0.209099 | 5.74 |
AIRLOOP DATACENTER BASEMENT | 24.57 | 24.57 | 24.57 | 24.57 | 24.57 | 24.57 | 1.00 | 0.999990 | 24.57 |
AIRLOOP DATACENTER BOT | 0.471008 | 0.471008 | 0.471008 | 0.471008 | 0.471008 | 0.471008 | 1.00 | 1.00 | 0.471008 |
AIRLOOP DATACENTER MID | 4.48 | 4.48 | 4.48 | 4.48 | 4.48 | 4.48 | 1.00 | 0.999987 | 4.48 |
AIRLOOP DATACENTER TOP | 0.456519 | 0.456519 | 0.456519 | 0.456519 | 0.456519 | 0.456519 | 1.00 | 1.00 | 0.456519 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.66 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 90.34 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 9.62 | |
CAV_BAS_OA_CONTROLLER | 5.74 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 24.57 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.471008 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.48 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.456519 | 0.015632 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT OA HEAT RECOVERY | 2.54 |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 25.38 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.54 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 27.05 | 6.67 | 11.05 | 0.011123 | 0.008500 | 267688.81 | 0.007656 | 9.66 |
VAV_MID WITH REHEAT COOLING COIL | 27.37 | 6.67 | 11.05 | 0.011420 | 0.008500 | 2621465.88 | 0.074974 | 90.34 |
VAV_TOP WITH REHEAT COOLING COIL | 26.96 | 6.67 | 11.05 | 0.011092 | 0.008500 | 264677.85 | 0.007570 | 9.62 |
CAV_BAS COOLING COIL | 25.14 | 6.67 | 11.04 | 0.010663 | 0.008500 | 137527.60 | 0.003933 | 5.74 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.66 |
VAV_MID WITH REHEAT FAN | 90.34 |
VAV_TOP WITH REHEAT FAN | 9.62 |
CAV_BAS FAN | 5.74 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.007656 | 0.000062 |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.074974 | 0.000006 |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.007570 | 0.000063 |
CAV_BAS_COOLC_CONTROLLER | 0.003933 | 0.000121 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 24.57 | 499781.57 | 359778.76 | 0.012240 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.471008 | 9668.23 | 6921.85 | 0.000237 |
AIRLOOP DATACENTER MID COOLING COIL | 4.48 | 92231.89 | 65930.95 | 0.002259 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.456519 | 9387.49 | 6714.58 | 0.000230 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 24.57 | 24.57 | 24.57 | 24.57 | 499781.57 | 499781.57 | 8144.41 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.471008 | 0.471008 | 0.471008 | 0.471008 | 9668.23 | 9668.23 | 376.24 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.48 | 4.48 | 4.48 | 4.48 | 92231.89 | 92231.89 | 3762.38 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.456519 | 0.456519 | 0.456519 | 0.456519 | 9387.49 | 9387.49 | 376.24 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 24.57 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.471008 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.48 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.456519 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 24.57 | 499781.57 | 0.012240 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.471008 | 9668.23 | 0.000237 |
AIRLOOP DATACENTER MID HEATING COIL | 4.48 | 92231.89 | 0.002259 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.456519 | 9387.49 | 0.000230 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000000 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.094132 | 15368.96 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.094132 | 11.30 |
COOLSYS1_SUPPLY | 0.094132 | 11.30 |
SINGLE WATER PLANT LOOP | 0.014965 | 1.80 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.094132 | 0.094132 | 395121.27 | 8.33 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.047066 | 5320.22 |
COOLSYS1 CHILLER2 PUMP | 0.047066 | 5320.22 |
PLANT CIRC PUMP | 0.014965 | 3816.83 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.094132 | 0.047409 | 1657654.21 | 1657655.03 | 0.083270 |
COOLSYS1 CHILLER2 | 0.094132 | 0.047409 | 1657654.21 | 1657655.03 | 0.083270 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | U-factor Times Area Value at High Fan Speed [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/K] | |
CENTRAL TOWER | 0.014965 | 148591.79 | 75221.35 | 74295.90 | 7879.72 | 45132.81 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
CENTRAL BOILER | 616431.55 | 604424.29 | 0.014965 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.166540 | 19.98 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.166540 | 41231.73 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 63.66 | 1984205.13 | 12.73 | 248025.64 |
TOWERWATERSYS COOLTOWER 2 | 63.66 | 1984205.13 | 12.73 | 248025.64 |
Design Water Flow Rate [m3/s] Equipment # 27 | |
WSHPPLANT OPERATION SCHEME | 0.085960 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:43
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:43
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:43
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.90 | 26.70 | 26.00 | 26.40 | 27.50 | 28.30 | 29.20 | 29.00 | 28.90 | 27.20 | 27.50 | 27.60 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 | 10.82 | 106.67 | 7.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.60 | 3.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 8.685 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 13.527 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 8.685 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 493.108 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 24139.153 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 24139.153 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 6806.209 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6806.209 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
47 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
48 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
49 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
50 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
51 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
52 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
53 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
54 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
55 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
56 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
57 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
58 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
59 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
60 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
61 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
62 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
63 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
64 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
65 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
66 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
67 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
68 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
69 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
70 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
71 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
72 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
73 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
74 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
75 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
76 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
77 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
78 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
79 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.498_SHGC_EAST_0.22 | 35 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.221 | ||
2 | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 36 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.221 | ||
3 | WINDOW_U_0.498_SHGC_WEST_0.22 | 37 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.221 | ||
4 | WINDOW_U_0.498_SHGC_NORTH_0.22 | 38 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.221 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00974E-002 | 0.13126 | 0.64120 | 0.64120 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00974E-002 | 0.13126 | 0.64120 | 0.64120 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00974E-002 | 0.13126 | 0.64120 | 0.64120 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00974E-002 | 0.13126 | 0.64120 | 0.64120 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 1.973E-005 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6245E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6257E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6532E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6542E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.2757E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.2763E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5496E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5501E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6526E-003 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7314E-003 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6765E-003 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7433E-003 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.2922E-003 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.3397E-003 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5627E-003 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5954E-003 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.7346E-002 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.2514E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.8954E-002 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.1955E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.9784E-002 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7219E-002 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7830E-002 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.6539E-003 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6520E-003 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7280E-003 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6757E-003 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7392E-003 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.2913E-003 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.3361E-003 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5630E-003 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5964E-003 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6244E-003 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6256E-003 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6531E-003 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6540E-003 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.2755E-003 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.2762E-003 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5495E-003 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5500E-003 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9435E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0220E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.7119E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7841E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.5509E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5975E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6499E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6725E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0344E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.4581E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6696E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.2470E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6168E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.0475E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.8983E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.0820E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.9306E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.9797E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6963E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7326E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.5377E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5517E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6499E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6729E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4586E-003 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4598E-003 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2766E-003 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2775E-003 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1078E-003 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1083E-003 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5496E-003 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5501E-003 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4843E-003 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5497E-003 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2970E-003 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3478E-003 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1205E-003 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1489E-003 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5630E-003 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5964E-003 |
81 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1871E-002 |
82 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0960E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7311E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 8.5492E-003 |
85 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4187E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 5.4968E-003 |
87 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7830E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.6510E-003 |
89 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4843E-003 |
90 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5487E-003 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2972E-003 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3479E-003 |
93 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1213E-003 |
94 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1513E-003 |
95 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5627E-003 |
96 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5955E-003 |
97 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4586E-003 |
98 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4597E-003 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2766E-003 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2775E-003 |
101 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1078E-003 |
102 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1083E-003 |
103 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5495E-003 |
104 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5500E-003 |
105 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0471E-003 |
106 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0958E-003 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8326E-003 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8689E-003 |
109 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6610E-003 |
110 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6755E-003 |
111 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6500E-003 |
112 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6729E-003 |
113 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2293E-002 |
114 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5269E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8940E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.3255E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8310E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.1238E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8983E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.0820E-002 |
121 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0606E-003 |
122 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1425E-003 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8489E-003 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9250E-003 |
125 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6744E-003 |
126 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7225E-003 |
127 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6498E-003 |
128 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6725E-003 |
129 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.3870E-002 |
130 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.4968E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.4635E-002 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.4461E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.6668E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.7845E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.4144E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.6879E-002 |
137 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.6700E-002 |
138 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.1524E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.2613E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.8861E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.1912E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.6480E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.5002E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.7075E-002 |
145 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.7763E-002 |
146 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7954E-002 |
147 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.2560E-002 |
148 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.4624E-002 |
149 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 1.8976E-002 |
150 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.0659E-002 |
151 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.4145E-002 |
152 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6876E-002 |
153 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.8919E-002 |
154 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2494E-002 |
155 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.5174E-002 |
156 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9977E-002 |
157 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.4334E-002 |
158 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7537E-002 |
159 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.5002E-002 |
160 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7075E-002 |
161 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.3968E-002 |
162 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.5036E-002 |
163 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.4750E-002 |
164 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.4532E-002 |
165 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.6790E-002 |
166 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.7910E-002 |
167 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.4218E-002 |
168 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.6916E-002 |
169 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.6732E-002 |
170 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.1555E-002 |
171 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.2648E-002 |
172 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.8889E-002 |
173 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.1970E-002 |
174 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.6512E-002 |
175 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.5076E-002 |
176 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7112E-002 |
177 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.7774E-002 |
178 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7975E-002 |
179 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.2571E-002 |
180 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.4641E-002 |
181 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 1.9007E-002 |
182 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.0677E-002 |
183 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.4218E-002 |
184 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6914E-002 |
185 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.8957E-002 |
186 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2528E-002 |
187 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.5216E-002 |
188 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.0008E-002 |
189 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.4398E-002 |
190 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7572E-002 |
191 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.5076E-002 |
192 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7112E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 79676.24522 | 79676.24522 | 5.73965 | 5.73965 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 28.91000 | 1.71462E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | 00:10:00 | 20.10000 | 1.47983E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 82860.69172 | 82860.69172 | 5.96849 | 5.96849 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 28.91000 | 1.71462E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | 00:10:00 | 20.10000 | 1.47983E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 | |
5 | CORE_MID | Cooling | 781971.22576 | 781971.22576 | 56.31186 | 56.31186 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 28.91000 | 1.71462E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 28181.03955 | 28181.03955 | 1.19887 | 10.77825 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 77524.50395 | 77524.50395 | 5.58272 | 5.58272 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 28.91000 | 1.71462E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 11252.22797 | 11252.22797 | 0.47314 | 1.07782 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 14660.86227 | 14660.86227 | 1.06572 | 1.06572 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 34.94500 | 1.71577E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.13533 | 00:10:00 | 20.10000 | 1.47983E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 | |
11 | PERIMETER_BOT_ZN_2 | Cooling | 14085.99953 | 14085.99953 | 1.02393 | 1.02393 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:10:00 | 30.76583 | 1.71497E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 0.00000 | 0.00000 | 0.00000 | 8.72129E-002 | 00:10:00 | 20.10000 | 1.47983E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 | |
13 | PERIMETER_BOT_ZN_1 | Cooling | 14183.57220 | 14183.57220 | 1.03103 | 1.03103 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 35.20000 | 1.71581E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.13533 | 00:10:00 | 20.10000 | 1.47983E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 | |
15 | PERIMETER_BOT_ZN_4 | Cooling | 18617.13358 | 18617.13358 | 1.35330 | 1.35330 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 34.57667 | 1.71570E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 0.00000 | 0.00000 | 0.00000 | 8.72129E-002 | 00:10:00 | 20.10000 | 1.47983E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 | |
17 | PERIMETER_MID_ZN_3 | Cooling | 138919.21345 | 138919.21345 | 10.09867 | 10.09867 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 | 34.86000 | 1.71575E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 18272.71992 | 18272.71992 | 0.76892 | 1.35332 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 144564.14641 | 144564.14641 | 10.50897 | 10.50897 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:20:00 | 31.00667 | 1.71502E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 12378.86586 | 12378.86586 | 0.52070 | 0.87213 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 133658.96758 | 133658.96758 | 9.71629 | 9.71629 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 35.20000 | 1.71581E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 19500.64280 | 19500.64280 | 0.81987 | 1.35335 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 161751.77580 | 161751.77580 | 11.75838 | 11.75838 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 | 34.46333 | 1.71567E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 4186.00037 | 4186.00037 | 0.17822 | 0.87213 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 15363.14240 | 15363.14240 | 1.11683 | 1.11683 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 34.94500 | 1.71577E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 2670.56843 | 2670.56843 | 0.11464 | 0.13533 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 20.10000 | 1.47983E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 14568.20031 | 14568.20031 | 1.05904 | 1.05904 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:30:00 | 31.24750 | 1.71506E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 1786.70742 | 1786.70742 | 7.66952E-002 | 8.72129E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 20.10000 | 1.47983E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 14845.26223 | 14845.26223 | 1.07919 | 1.07919 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | 35.20000 | 1.71581E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 2804.45084 | 2804.45084 | 0.12038 | 0.13533 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 20.10000 | 1.47983E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 17108.87643 | 17108.87643 | 1.24373 | 1.24373 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 34.57667 | 1.71570E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 1029.20880 | 1029.20880 | 4.35108E-002 | 8.72129E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20.10000 | 1.47983E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8216.17834 | 8216.17834 | 0.47101 | 0.47101 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:20:00 | 26.75667 | 1.71421E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 20.10000 | 1.47983E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 78150.07108 | 78150.07108 | 4.48010 | 4.48010 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:20:00 | 26.75667 | 1.71421E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | 00:10:00 | 20.10000 | 1.47983E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7962.51527 | 7962.51527 | 0.45652 | 0.45652 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | 33.44333 | 1.71548E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 20.10000 | 1.47983E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 372712.79984 | 428619.71982 | 21.36847 | 24.57374 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 07:00:00 | 27.46500 | 1.71434E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | 00:10:00 | 20.10000 | 1.47983E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 160672.30 | 9.66160 | 9.66160 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 0.00 | 0.00000 | 0.00000 | 00:00:00 | |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1485547.23 | 90.34122 | 90.34122 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 0.00 | 0.00000 | 0.00000 | 00:00:00 | |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 164333.81 | 9.62261 | 9.62261 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 0.00 | 0.00000 | 0.00000 | 00:00:00 | |
7 | CAV_BAS | Cooling | Sensible | 85291.10 | 5.73965 | 5.73965 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 28885.26 | 1.20016 | 1.20016 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 424791.18 | 24.57397 | 24.57397 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 8144.41 | 0.33839 | 0.33839 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8198.81 | 0.47101 | 0.47101 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 376.24 | 1.56323E-002 | 1.56323E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 78136.33 | 4.48016 | 4.48016 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 3762.38 | 0.15632 | 0.15632 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7961.24 | 0.45652 | 0.45652 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 376.24 | 1.56323E-002 | 1.56323E-002 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 5.73965 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.36900 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.00000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 0.00000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.96849 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31868 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32400 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.93379 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.84982 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.19555E-003 |
12 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 64555.97503 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 56.31186 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33777 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33700 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 18.97710 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.90072 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.12799E-003 |
20 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 633514.30970 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.58272 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34070 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34600 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.93162 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.90854 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.11828E-003 |
28 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 64483.43864 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.06572 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22409 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22800 |
32 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24298 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59758 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.70019E-003 |
36 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8111.57912 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.02393 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15031 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20479 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40082 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.53479E-003 |
44 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 6836.38994 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.03103 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23164 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23500 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24229 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.61770 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.64480E-003 |
52 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8088.44091 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.35330 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11373 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27066 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30327 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.35016E-003 |
60 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9035.44723 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.09867 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23649 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23600 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.38329 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.63063 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.61108E-003 |
68 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 79561.50170 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.50897 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14645 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.10179 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39054 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.60155E-003 |
76 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 70164.40661 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.71629 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24580 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24500 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.38049 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.65546 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.55004E-003 |
84 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 79468.17266 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.75838 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13089 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.35168 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34904 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.91085E-003 |
92 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 78506.21786 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.11683 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21384 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21700 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24235 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57023 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.78173E-003 |
100 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8090.48394 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.05904 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14533 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.21181 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38753 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.62171E-003 |
108 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7070.81033 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.07919 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22130 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22500 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24282 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59014 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.72163E-003 |
116 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8105.97826 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.24373 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12374 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24875 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32999 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.07892E-003 |
124 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8303.92020 |
125 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.47101 |
126 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.48010 |
127 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.45652 |
128 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 24.57374 |
129 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.22124 |
130 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.89451 |
131 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.44247 |
132 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.89451 |
133 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.66160 |
134 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.66160 |
135 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.29959 |
137 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 49.19709 |
138 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 28.19435 |
139 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 98.39418 |
140 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 28.19435 |
141 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 90.34122 |
142 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 90.34122 |
143 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.31209 |
145 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.04075 |
146 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.87734 |
147 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.08151 |
148 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.87734 |
149 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.62261 |
150 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.62261 |
151 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
152 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.29902 |
153 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.00000 |
154 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.00000 |
155 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.73965 |
156 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 1.20016 |
157 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.73965 |
158 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.73965 |
159 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
160 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.20910 |
161 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 24.57374 |
162 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 24.57374 |
163 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 24.57374 |
164 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 24.57374 |
165 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 24.57397 |
166 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 24.57397 |
167 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
168 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
169 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.47101 |
170 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.47101 |
171 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.47101 |
172 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.47101 |
173 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.47101 |
174 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.47101 |
175 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
176 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
177 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.48010 |
178 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.48010 |
179 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.48010 |
180 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.48010 |
181 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.48016 |
182 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.48016 |
183 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
184 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 0.99999 |
185 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.45652 |
186 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.45652 |
187 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.45652 |
188 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.45652 |
189 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.45652 |
190 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.45652 |
191 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
192 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
193 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.66160 |
194 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 90.34122 |
195 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.62261 |
196 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.73965 |
197 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 24.57397 |
198 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.47101 |
199 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.48016 |
200 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.45652 |
201 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.66160 |
202 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_BOT WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
203 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.04788 |
204 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
205 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04926 |
206 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.11226E-002 |
207 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
208 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 267688.81007 |
209 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.65587E-003 |
210 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.66160 |
211 | Coil:Heating:Electric | VAV_BOT WITH REHEAT HEATING COIL | Design Size Nominal Capacity [W] | 44870.97382 |
212 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.66160 |
213 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.65587E-003 |
214 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.21994E-005 |
215 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 90.34122 |
216 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 25.38195 |
217 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.37132 |
218 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
219 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.05021 |
220 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.14198E-002 |
221 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
222 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2621465.87753 |
223 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.49736E-002 |
224 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 90.34122 |
225 | Coil:Heating:Electric | VAV_MID WITH REHEAT HEATING COIL | Design Size Nominal Capacity [W] | 419568.15326 |
226 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 90.34122 |
227 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.49736E-002 |
228 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.35144E-006 |
229 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.62261 |
230 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
231 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.96171 |
232 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
233 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04916 |
234 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.10919E-002 |
235 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
236 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 264677.84999 |
237 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.56975E-003 |
238 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.62261 |
239 | Coil:Heating:Electric | VAV_TOP WITH REHEAT HEATING COIL | Design Size Nominal Capacity [W] | 44689.88344 |
240 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.62261 |
241 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.56975E-003 |
242 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.29070E-005 |
243 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.73965 |
244 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
245 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.14344 |
246 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
247 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.03650 |
248 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.06626E-002 |
249 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
250 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 137527.60433 |
251 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.93327E-003 |
252 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.73965 |
253 | Coil:Heating:Electric | CAV_BAS HEATING COIL | Design Size Nominal Capacity [W] | 248495.45403 |
254 | Fan:VariableVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.73965 |
255 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.93327E-003 |
256 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.21067E-004 |
257 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 24.57397 |
258 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
259 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.57397 |
260 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 499781.56851 |
261 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 359778.75578 |
262 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.22396E-002 |
263 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 24.57397 |
264 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 24.57397 |
265 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 24.57397 |
266 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 24.57397 |
267 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 499781.56851 |
268 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 499781.56851 |
269 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 8144.40695 |
270 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
271 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 24.57397 |
272 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.57397 |
273 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 499781.56851 |
274 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.22396E-002 |
275 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 8144.40695 |
276 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 0.00000 |
277 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
278 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
279 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
280 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.47101 |
281 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
282 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.47101 |
283 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9668.22504 |
284 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6921.84577 |
285 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.36774E-004 |
286 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.47101 |
287 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.47101 |
288 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.47101 |
289 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.47101 |
290 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9668.22504 |
291 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9668.22504 |
292 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 376.23786 |
293 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
294 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.47101 |
295 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.47101 |
296 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9668.22504 |
297 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.36774E-004 |
298 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 376.23786 |
299 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.48016 |
300 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
301 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.48016 |
302 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 92231.89136 |
303 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 65930.95006 |
304 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.25875E-003 |
305 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.48016 |
306 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.48016 |
307 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.48016 |
308 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.48016 |
309 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 92231.89136 |
310 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 92231.89136 |
311 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 3762.37861 |
312 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
313 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.48016 |
314 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.48016 |
315 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 92231.89136 |
316 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.25875E-003 |
317 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 3762.37861 |
318 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.45652 |
319 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
320 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45652 |
321 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9387.48746 |
322 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6714.57596 |
323 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.29899E-004 |
324 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.45652 |
325 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.45652 |
326 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.45652 |
327 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.45652 |
328 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9387.48746 |
329 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9387.48746 |
330 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 376.23786 |
331 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
332 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.45652 |
333 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.45652 |
334 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9387.48746 |
335 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.29899E-004 |
336 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 376.23786 |
337 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 9.41325E-002 |
338 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 15368.95817 |
339 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 9.41325E-002 |
340 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 11.29590 |
341 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 9.41325E-002 |
342 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 9.41325E-002 |
343 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 395121.26554 |
344 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
345 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 9.41325E-002 |
346 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 11.29590 |
347 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 4.70662E-002 |
348 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 5320.22402 |
349 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 4.70662E-002 |
350 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 5320.22402 |
351 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 9.41325E-002 |
352 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.74087E-002 |
353 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1657654.20727 |
354 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1657655.03000 |
355 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 8.32702E-002 |
356 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 9.41325E-002 |
357 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.74087E-002 |
358 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1657654.20727 |
359 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1657655.03000 |
360 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 8.32702E-002 |
361 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.49650E-002 |
362 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.79581 |
363 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.49650E-002 |
364 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3816.83476 |
365 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.49650E-002 |
366 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 148591.79209 |
367 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at High Fan Speed [W/K] | 75221.35480 |
368 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 74295.89605 |
369 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
370 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/K] | 45132.81288 |
371 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 616431.54566 |
372 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 604424.29000 |
373 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.49650E-002 |
374 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
375 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
376 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
377 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
378 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
379 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.16654 |
380 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 19.98486 |
381 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.16654 |
382 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 41231.73267 |
383 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 63.65688 |
384 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1984205.12889 |
385 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 12.73138 |
386 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 248025.64111 |
387 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 63.65688 |
388 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1984205.12889 |
389 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 12.73138 |
390 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 248025.64111 |
391 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 27 | 8.59600E-002 |
392 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 27 | 8.59600E-002 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 265942.11 | 181748.55 | 84193.56 | 0.68 | 38939.13 | 394.94 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2531276.49 | 1718715.24 | 812561.25 | 0.68 | 367320.79 | 3725.57 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 264164.02 | 180714.15 | 83449.87 | 0.68 | 38757.41 | 393.10 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 149744.87 | 104506.40 | 45238.47 | 0.70 | 23077.92 | 234.07 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 9.21 | 31.42 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 9.21 | 31.42 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.22 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.22 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.22 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.22 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.22 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.22 | N/A | 2.831 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.22 | N/A | 2.831 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.22 | N/A | 2.831 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.22 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.22 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.22 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.22 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.22 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.22 | N/A | 2.831 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.22 | N/A | 2.831 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.22 | N/A | 2.831 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.22 | N/A | 2.831 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.22 | N/A | 2.831 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.22 | N/A | 2.831 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.22 | N/A | 2.831 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.22 | N/A | 2.831 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.22 | N/A | 2.831 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.22 | N/A | 2.831 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.22 | N/A | 2.831 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 6.4047249792E-004 | 1.0951698728E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.4354208001 | 0.2940197830 | Pass | Pass | 0.3527551167 | 0.4776837871 | Pass | Fail |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 0.2046861102 | 0.2587447509 | Pass | Pass | 0.1642376738 | 0.3701014936 | Pass | Fail |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.2219596996 | 0.2548083452 | Pass | Pass | 0.1767875846 | 0.3806509937 | Pass | Fail |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.4281855760 | 0.3218918500 | Pass | Pass | 0.3545509203 | 0.4797604352 | Pass | Fail |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.5124102412 | 0.3676923901 | Pass | Pass | 0.3444741154 | 0.4693429025 | Pass | Fail |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4460693267 | 0.3333202634 | Pass | Pass | 0.3581042120 | 0.4783301993 | Pass | Fail |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.6238848551 | 0.4554755889 | Pass | Pass | 0.3460576955 | 0.4672663354 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1977941629 | 0.2768552165 | Pass | Pass | 0.1635979920 | 0.3685574432 | Pass | Fail |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2549797178 | 0.3624975003 | Pass | Pass | 0.1645426699 | 0.3688438981 | Pass | Fail |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2067267402 | 0.2896106688 | Pass | Pass | 0.1621301402 | 0.3668358040 | Pass | Fail |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2758860619 | 0.3998667954 | Pass | Pass | 0.1651077690 | 0.3684524470 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2160839428 | 0.2699942234 | Pass | Pass | 0.1762325835 | 0.3797719167 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2787341904 | 0.3547115351 | Pass | Pass | 0.1771493035 | 0.3798334146 | Pass | Fail |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2221794901 | 0.2948954636 | Pass | Pass | 0.1808222010 | 0.3860473360 | Pass | Fail |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3101480071 | 0.4042796856 | Pass | Pass | 0.1778227985 | 0.3796046432 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.1605578757E-002 | 5.1852536502E-002 | Pass | Pass | 0.5467404258 | 1.8962692331 | Fail | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.3975225708E-002 | 5.5734413469E-002 | Pass | Pass | 0.1680063053 | 0.3537306885 | Fail | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.5071181722E-002 | 6.4294234372E-002 | Pass | Pass | 0.1842362737 | 0.3784979840 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.0595606355E-006 | 3.0595071292E-006 | Pass | Pass | 2.1341931743E-003 | 1.3876463560E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.3222612013E-006 | 4.7071146623E-006 | Pass | Pass | 1.8458579935E-003 | 1.6807398068E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.0312075168E-006 | 3.0247860061E-006 | Pass | Pass | 1.7594385499E-003 | 1.7016076579E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.5275986734E-004 | 3.5107000752E-004 | Pass | Pass | 4.5617288115E-005 | 1.0841883331E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:43
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5706.90 | -106.5 | 0.00 | -18368.9 | 48058.88 | 35290.38 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:43
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 20.10 | 0.00 | 20.10 | Wetbulb [C] | 1.80 | 0.00 |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 35.20 | 8.50 | 25.80 | Wetbulb [C] | 4.10 | 160.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 57.00 | 12 | |||
Feb | 0.00 | 0 | |||
Mar | 153.60 | 31 | |||
Apr | 87.00 | 59 | |||
May | 227.22 | 128 | |||
Jun | 144.58 | 109 | |||
Jul | 42.40 | 24 | |||
Aug | 164.90 | 163 | |||
Sep | 119.60 | 50 | |||
Oct | 365.70 | 188 | |||
Nov | 70.90 | 67 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:43
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.498_SHGC_NORTH_0.22 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.498_SHGC_NORTH_0.22 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.498_SHGC_NORTH_0.22 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.498_SHGC_NORTH_0.22 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.498_SHGC_NORTH_0.22 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.498_SHGC_EAST_0.22 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.498_SHGC_EAST_0.22 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.498_SHGC_EAST_0.22 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.498_SHGC_WEST_0.22 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.498_SHGC_WEST_0.22 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.498_SHGC_WEST_0.22 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.498_SHGC_NORTH_0.22 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.831 | 0.221 | 0.243 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.498_SHGC_EAST_0.22 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.831 | 0.221 | 0.243 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.831 | 0.221 | 0.243 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.498_SHGC_WEST_0.22 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.831 | 0.221 | 0.243 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.498_SHGC_NORTH_0.22 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.831 | 0.221 | 0.243 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.498_SHGC_EAST_0.22 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.831 | 0.221 | 0.243 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.831 | 0.221 | 0.243 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.498_SHGC_WEST_0.22 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.831 | 0.221 | 0.243 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.831 | 0.221 | 0.243 | |||||||||||||||||
North Total or Average | 1390.74 | 2.831 | 0.221 | 0.243 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.831 | 0.221 | 0.243 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:43
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:43
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.6849 | 2779.43 | 24139.15 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 216.17 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 8.6849 | 2496.12 | 21678.66 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 194.14 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 8.6849 | 24961.20 | 216786.56 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 1941.36 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 8.6849 | 2496.12 | 21678.66 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 194.14 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 8.6849 | 313.41 | 2721.97 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.82 | 0.0000 | Y | 13.71 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.97 | 0.0000 | Y | 8.88 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 8.6849 | 313.42 | 2722.03 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.71 | 0.0000 | Y | 13.65 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.67 | 0.0000 | Y | 8.78 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 8.6849 | 3134.13 | 27219.72 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.78 | 0.0000 | Y | 136.84 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 8.6849 | 2019.75 | 17541.42 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.92 | 0.0000 | Y | 88.65 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 8.6849 | 3134.20 | 27220.31 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.67 | 0.0000 | Y | 136.30 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 8.6849 | 2019.75 | 17541.42 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.63 | 0.0000 | Y | 87.68 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 8.6849 | 313.41 | 2721.97 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.78 | 0.0000 | Y | 13.68 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.92 | 0.0000 | Y | 8.86 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 8.6849 | 313.42 | 2722.03 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.67 | 0.0000 | Y | 13.63 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.63 | 0.0000 | Y | 8.77 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 8.6849 | 783.68 | 6806.21 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 62.65 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 13.9016 | 36.20 | 503.28 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.16 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 13.9016 | 362.03 | 5032.75 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 51.55 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 13.9016 | 36.20 | 503.28 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.16 |
Interior Lighting Total | 8.7339 | 46320.38 | 404555.99 | 1011.61 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13271.55 | AstronomicalClock | - | 41.93 | 41.93 | 104.45 | |
EXTERIOR_LIGHTS_B | 989.48 | AstronomicalClock | - | 83.83 | 62.88 | 11.68 | |
EXTERIOR_LIGHTS_C | 26594.85 | AstronomicalClock | - | 83.83 | 45.49 | 227.08 | |
Exterior Lighting Total | 40855.88 | 343.21 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:43
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 3281222.46 | |||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1657655.03 | 6.01 | 1648417.85 | 5.99 | 9.21 | 31.42 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 1657655.03 | 6.01 | 1648417.85 | 5.99 | 9.21 | 31.42 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 619256.29 | |||||
CENTRAL BOILER | Boiler:HotWater | 604424.29 | 1.00 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1984205.13 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1984205.13 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 267688.81 | 265942.11 | 181748.55 | 84193.56 | 0.68 | - | 38939.13 | 394.94 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2621465.88 | 2531276.49 | 1718715.24 | 812561.25 | 0.68 | - | 367320.79 | 3725.57 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 264677.85 | 264164.02 | 180714.15 | 83449.87 | 0.68 | - | 38757.41 | 393.10 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 137527.60 | 149744.87 | 104506.40 | 45238.47 | 0.70 | - | 23077.92 | 234.07 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 499781.57 | 359778.76 | 140002.81 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9668.23 | 6921.85 | 2746.38 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 92231.89 | 65930.95 | 26300.94 | 0.71 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9387.49 | 6714.58 | 2672.91 | 0.72 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 64555.98 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 633514.31 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 64483.44 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8111.58 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6836.39 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8088.44 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9035.45 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 79561.50 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 70164.41 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 79468.17 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 78506.22 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8090.48 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7070.81 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8105.98 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8303.92 | 1.00 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Electric | 44870.97 | 1.00 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Electric | 419568.15 | 1.00 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Electric | 44689.88 | 1.00 | |
CAV_BAS HEATING COIL | Coil:Heating:Electric | 248495.45 | 1.00 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 499781.57 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9668.23 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 92231.89 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9387.49 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 8144.41 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 376.24 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 3762.38 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 376.24 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.66 | 20878.20 | 2160.95 | 1.00 | 1.12 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 90.34 | 195222.58 | 2160.95 | 1.00 | 1.08 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.62 | 20793.94 | 2160.95 | 1.00 | 1.12 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 |
CAV_BAS FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.74 | 12483.09 | 2174.89 | 1.00 | 1.13 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 24.57 | 40528.55 | 1649.25 | 1.00 | 1.14 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.47 | 527.58 | 1120.11 | 1.00 | 1.63 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.48 | 5018.26 | 1120.11 | 1.00 | 1.16 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:50:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.46 | 511.35 | 1120.11 | 1.00 | 1.65 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.094132 | 15368.96 | 163269.45 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.047066 | 5320.22 | 113036.94 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.047066 | 5320.22 | 113036.94 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.014965 | 3816.83 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.166540 | 41231.73 | 247577.87 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:43
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 79676.25 | 79676.25 | 28.67 | 5.740 | 5.740 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 24.00 | 24.00 | 0.00894 | 28.91 | 0.01715 | 1.200 | 0.00 |
CORE_BOTTOM | 82860.69 | 82860.69 | 33.20 | 5.968 | 5.968 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 24.00 | 24.00 | 0.00888 | 28.91 | 0.01715 | 1.078 | 0.00 |
CORE_MID | 781971.23 | 781971.23 | 313.27 | 56.312 | 56.312 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 24.00 | 24.00 | 0.00890 | 28.91 | 0.01715 | 10.778 | 0.00 |
CORE_TOP | 77524.50 | 77524.50 | 31.06 | 5.583 | 5.583 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 24.00 | 24.00 | 0.00890 | 28.91 | 0.01715 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 14660.86 | 14660.86 | 46.78 | 1.066 | 1.066 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 24.00 | 24.00 | 0.00884 | 34.95 | 0.01716 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 14086.00 | 14086.00 | 69.74 | 1.024 | 1.024 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:10:00 | 24.00 | 24.00 | 0.00873 | 30.77 | 0.01715 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 14183.57 | 14183.57 | 45.25 | 1.031 | 1.031 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:40:00 | 24.00 | 24.00 | 0.00885 | 35.20 | 0.01716 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 18617.13 | 18617.13 | 92.18 | 1.353 | 1.353 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 24.00 | 24.00 | 0.00867 | 34.58 | 0.01716 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 138919.21 | 138919.21 | 443.25 | 10.099 | 10.099 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:40:00 | 24.00 | 24.00 | 0.00897 | 34.86 | 0.01716 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 144564.15 | 144564.15 | 715.75 | 10.509 | 10.509 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:20:00 | 24.00 | 24.00 | 0.00880 | 31.01 | 0.01715 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 133658.97 | 133658.97 | 426.45 | 9.716 | 9.716 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:50:00 | 24.00 | 24.00 | 0.00899 | 35.20 | 0.01716 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 161751.78 | 161751.78 | 800.85 | 11.758 | 11.758 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:20:00 | 24.00 | 24.00 | 0.00876 | 34.46 | 0.01716 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 15363.14 | 15363.14 | 49.02 | 1.117 | 1.117 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 24.00 | 24.00 | 0.00897 | 34.95 | 0.01716 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 14568.20 | 14568.20 | 72.13 | 1.059 | 1.059 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:30:00 | 24.00 | 24.00 | 0.00883 | 31.25 | 0.01715 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 14845.26 | 14845.26 | 47.37 | 1.079 | 1.079 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | 24.00 | 24.00 | 0.00898 | 35.20 | 0.01716 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 17108.88 | 17108.88 | 84.71 | 1.244 | 1.244 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 16:10:00 | 24.00 | 24.00 | 0.00878 | 34.58 | 0.01716 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8216.18 | 8216.18 | 226.95 | 0.471 | 0.471 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:20:00 | 27.00 | 27.00 | 0.00850 | 26.76 | 0.01714 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 78150.07 | 78150.07 | 2158.68 | 4.480 | 4.480 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:20:00 | 27.00 | 27.00 | 0.00850 | 26.76 | 0.01714 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7962.52 | 7962.52 | 219.94 | 0.457 | 0.457 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | 27.00 | 27.00 | 0.00859 | 33.44 | 0.01715 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 372712.80 | 428619.72 | 546.93 | 21.368 | 24.574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 27.47 | 0.01714 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | 00:10:00 | 15.60 | 26.70 | 0.00850 | 20.10 | 0.01480 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | 00:10:00 | 15.60 | 25.28 | 0.01480 | 20.10 | 0.01480 | 1.078 | 0.00 | |
CORE_MID | 28181.04 | 28181.04 | 11.29 | 1.199 | 10.778 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00835 | 20.10 | 0.01480 | 10.778 | 0.00 |
CORE_TOP | 11252.23 | 11252.23 | 4.51 | 0.473 | 1.078 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 20.10 | 0.01480 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.000 | 0.135 | 00:10:00 | 15.60 | 23.72 | 0.01480 | 20.10 | 0.01480 | 0.135 | 0.00 | |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 0.00 | 0.000 | 0.087 | 00:10:00 | 15.60 | 23.49 | 0.01480 | 20.10 | 0.01480 | 0.087 | 0.00 | |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 0.00 | 0.000 | 0.135 | 00:10:00 | 15.60 | 22.61 | 0.01480 | 20.10 | 0.01480 | 0.135 | 0.00 | |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 0.00 | 0.000 | 0.087 | 00:10:00 | 15.60 | 24.29 | 0.01480 | 20.10 | 0.01480 | 0.087 | 0.00 | |
PERIMETER_MID_ZN_3 | 18272.72 | 18272.72 | 58.30 | 0.769 | 1.353 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01059 | 20.10 | 0.01480 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 12378.87 | 12378.87 | 61.29 | 0.521 | 0.872 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01060 | 20.10 | 0.01480 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 19500.64 | 19500.64 | 62.22 | 0.820 | 1.353 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01052 | 20.10 | 0.01480 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 4186.00 | 4186.00 | 20.73 | 0.178 | 0.872 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01198 | 20.10 | 0.01480 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 2670.57 | 2670.57 | 8.52 | 0.115 | 0.135 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 21.00 | 21.00 | 0.01021 | 20.10 | 0.01480 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 1786.71 | 1786.71 | 8.85 | 0.077 | 0.087 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 21.00 | 21.00 | 0.01019 | 20.10 | 0.01480 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 2804.45 | 2804.45 | 8.95 | 0.120 | 0.135 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 21.00 | 21.00 | 0.01011 | 20.10 | 0.01480 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 1029.21 | 1029.21 | 5.10 | 0.044 | 0.087 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.01129 | 20.10 | 0.01480 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 20.10 | 0.01480 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | 00:10:00 | 18.00 | 26.35 | 0.00850 | 20.10 | 0.01480 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 25.99 | 0.00850 | 20.10 | 0.01480 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 20.10 | 0.01480 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 9.66 | 9.66 | 0.00 | 0.00 | 9.6616 | 2.8945 | 9.6616 | 0.2996 | 0.3000 |
VAV_MID WITH REHEAT | 90.34 | 90.34 | 0.00 | 0.00 | 90.3412 | 28.1943 | 90.3412 | 0.3121 | 0.3000 |
VAV_TOP WITH REHEAT | 9.62 | 9.62 | 0.00 | 0.00 | 9.6226 | 2.8773 | 9.6226 | 0.2990 | 0.3000 |
CAV_BAS | 5.74 | 5.74 | 1.20 | 1.20 | 5.7396 | 1.2002 | 5.7396 | 0.2091 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.57 | 24.57 | 0.34 | 0.34 | 24.5740 | 24.5737 | 24.5740 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.47 | 0.47 | 0.02 | 0.02 | 0.4710 | 0.4710 | 0.4710 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.48 | 4.48 | 0.16 | 0.16 | 4.4802 | 4.4801 | 4.4802 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.46 | 0.46 | 0.02 | 0.02 | 0.4565 | 0.4565 | 0.4565 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 64555.975 | 64555.975 | -999.0 | -999.0 | -999.000 | 12/21 00:10:00 | 12/21 00:10:00 | 64555.98 | 35981.13 | 1.077825 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | ||
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 633514.310 | 633514.310 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 633514.31 | 359811.31 | 10.778248 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00834973 | 53.9226 | 28181.04 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 64483.439 | 64483.439 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 64483.44 | 35981.13 | 1.077825 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 11252.23 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 8111.579 | 8111.579 | -999.0 | -999.0 | -999.000 | 12/21 00:10:00 | 12/21 00:10:00 | 8111.58 | 4517.79 | 0.135332 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | ||
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 6836.390 | 6836.390 | -999.0 | -999.0 | -999.000 | 12/21 00:10:00 | 12/21 00:10:00 | 6836.39 | 2911.44 | 0.087213 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | ||
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 8088.441 | 8088.441 | -999.0 | -999.0 | -999.000 | 12/21 00:10:00 | 12/21 00:10:00 | 8088.44 | 4517.89 | 0.135335 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | ||
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 9035.447 | 9035.447 | -999.0 | -999.0 | -999.000 | 12/21 00:10:00 | 12/21 00:10:00 | 9035.45 | 2911.44 | 0.087213 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | ||
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 79561.502 | 79561.502 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 79561.50 | 45177.90 | 1.353317 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01059112 | 68.1495 | 18272.72 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 70164.407 | 70164.407 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 70164.41 | 29114.36 | 0.872129 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01059662 | 68.1840 | 12378.87 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 79468.173 | 79468.173 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 79468.17 | 45178.89 | 1.353346 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01051852 | 67.6899 | 19500.64 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 78506.218 | 78506.218 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 78506.22 | 29114.36 | 0.872129 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01198188 | 76.9323 | 4186.00 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 8090.484 | 8090.484 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 8090.48 | 4517.79 | 0.135332 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01020515 | 65.7036 | 2670.57 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 7070.810 | 7070.810 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 7070.81 | 2911.44 | 0.087213 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01019408 | 65.6332 | 1786.71 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 8105.978 | 8105.978 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 8105.98 | 4517.89 | 0.135335 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01011455 | 65.1296 | 2804.45 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 8303.920 | 8303.920 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8303.92 | 2911.44 | 0.087213 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 0.0000 | 21.00 | 0.01129125 | 72.5731 | 1029.21 | 0.00 | -999.00 | -999.00 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 267688.810 | -999.000 | 9.661598 | 0.00765587 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 267688.81 | 187966.64 | 9.661598 | 27.05 | 19.53 | 0.01112263 | 11.05 | 11.05 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 26.2709 | 24.00 | 0.00886511 | 47.6752 | 128269.97 | 0.00 | 268040.96 | 185964.09 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | VAV_BOT WITH REHEAT | 44870.974 | 44870.974 | -999.0 | -999.0 | -999.000 | unknown | unknown | unknown | 44870.97 | 44870.97 | 2.898479 | 0.00 | -6.26 | 0.00000000 | 12.80 | 11.59 | 0.00800000 | 0.00 | 0.00000000 | -6.26 | 87.5697 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2621465.878 | -999.000 | 90.341225 | 0.07497359 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 2621465.88 | 1792302.56 | 90.341225 | 27.37 | 19.85 | 0.01141984 | 11.05 | 11.05 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 28.0956 | 24.00 | 0.00894757 | 48.1130 | 1159613.01 | 0.00 | 2624894.26 | 1776433.81 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | VAV_MID WITH REHEAT | 419568.153 | 419568.153 | -999.0 | -999.0 | -999.000 | unknown | unknown | unknown | 419568.15 | 419568.15 | 27.102367 | 0.00 | -6.26 | 0.00000000 | 12.80 | 11.59 | 0.00800000 | 0.00 | 0.00000000 | -6.26 | 93.6522 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 264677.850 | -999.000 | 9.622605 | 0.00756975 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | 264677.85 | 186198.64 | 9.622605 | 26.96 | 19.47 | 0.01109189 | 11.05 | 11.05 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 26.3774 | 24.00 | 0.00890985 | 47.9132 | 131988.15 | 0.00 | 265027.24 | 184180.15 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | VAV_TOP WITH REHEAT | 44689.883 | 44689.883 | -999.0 | -999.0 | -999.000 | unknown | unknown | unknown | 44689.88 | 44689.88 | 2.886782 | 0.00 | -6.26 | 0.00000000 | 12.80 | 11.59 | 0.00800000 | 0.00 | 0.00000000 | -6.26 | 87.9246 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 137527.604 | -999.000 | 5.739648 | 0.00393327 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | 137527.60 | 98350.98 | 5.739648 | 25.14 | 18.56 | 0.01066264 | 11.04 | 11.04 | 0.00850000 | 29.45 | 0.01714719 | 24.35 | 20.9099 | 24.00 | 0.00893822 | 48.0627 | 78596.12 | 0.00 | 137689.83 | 96978.88 |
CAV_BAS HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | CAV_BAS | 248495.454 | 248495.454 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 248495.45 | 248495.45 | 5.739648 | 4.20 | 4.20 | 0.00981697 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 20.9099 | 26.70 | 0.00850000 | 38.9515 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 499781.569 | 359778.756 | 24.573970 | 0.01223962 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 07:10:00 | 468208.63 | 457318.12 | -999.0 | 28.50 | 18.07 | 0.00866096 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | -999.0000 | 27.00 | 0.00854217 | 38.4637 | 372220.22 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9668.225 | 6921.846 | 0.471008 | 0.00023677 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:20:00 | 9071.26 | 8587.70 | -999.0 | 28.16 | 18.12 | 0.00887293 | 12.80 | 12.09 | 0.00850000 | 33.44 | 0.01715480 | 25.39 | -999.0000 | 27.00 | 0.00858822 | 38.6660 | 8203.82 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 92231.891 | 65930.950 | 4.480158 | 0.00225875 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:50:00 | 86580.26 | 81751.83 | -999.0 | 28.17 | 18.14 | 0.00889141 | 12.80 | 12.09 | 0.00850000 | 33.44 | 0.01715480 | 25.39 | -999.0000 | 27.00 | 0.00859260 | 38.6857 | 78125.89 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9387.487 | 6714.576 | 0.456519 | 0.00022990 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | 8810.53 | 8327.66 | -999.0 | 28.17 | 18.14 | 0.00888417 | 12.80 | 12.09 | 0.00850000 | 33.44 | 0.01715480 | 25.39 | -999.0000 | 27.00 | 0.00859092 | 38.6781 | 7962.52 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 499781.569 | 499781.569 | 24.573970 | 0.01223962 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 499781.57 | 499781.57 | 24.573970 | 20.10 | 20.10 | 0.01479830 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 1.3770 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9668.225 | 9668.225 | 0.471008 | 0.00023677 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9668.23 | 9668.23 | 0.471008 | 20.10 | 20.10 | 0.01479830 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 3.3189 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 92231.891 | 92231.891 | 4.480158 | 0.00225875 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 92231.89 | 92231.89 | 4.480158 | 20.10 | 20.10 | 0.01479830 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 3.4892 | 26.35 | 0.00850000 | 39.7705 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9387.487 | 9387.487 | 0.456519 | 0.00022990 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9387.49 | 9387.49 | 0.456519 | 20.10 | 20.10 | 0.01479830 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 3.4243 | 25.99 | 0.00850390 | 40.6392 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 8144.407 | 8144.407 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 8144.41 | 8144.41 | 24.573970 | 0.28 | 0.28 | 0.00858673 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 1.3770 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 376.238 | 376.238 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 376.24 | 376.24 | 0.471008 | 0.67 | 0.67 | 0.00870904 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 3.3189 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 3762.379 | 3762.379 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 3762.38 | 3762.38 | 4.480158 | 0.70 | 0.70 | 0.00871976 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 3.4892 | 26.35 | 0.00850000 | 39.7705 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 376.238 | 376.238 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 376.24 | 376.24 | 0.456519 | 0.69 | 0.69 | 0.00871944 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 3.4243 | 25.99 | 0.00850390 | 40.6392 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:43
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 64555.975 | 64555.975 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 64555.98 | 35981.13 | 1.0000 | 1.29726454 | 1.077825 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 64555.98 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 633514.310 | 633514.310 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 633514.31 | 359811.31 | 1.0000 | 12.97264538 | 10.778248 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 633514.31 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.88 | 0.00834973 | 21.00 | 0.00834973 | 53.9226 | 28181.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 64483.439 | 64483.439 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 64483.44 | 35981.13 | 1.0000 | 1.29726454 | 1.077825 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 64483.44 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.71 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 11252.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 8111.579 | 8111.579 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 8111.58 | 4517.79 | 1.0000 | 0.16288451 | 0.135332 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8111.58 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 6836.390 | 6836.390 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 6836.39 | 2911.44 | 1.0000 | 0.10496897 | 0.087213 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6836.39 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 8088.441 | 8088.441 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 8088.44 | 4517.89 | 1.0000 | 0.16288807 | 0.135335 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8088.44 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 9035.447 | 9035.447 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 9035.45 | 2911.44 | 1.0000 | 0.10496897 | 0.087213 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9035.45 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 79561.502 | 79561.502 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 79561.50 | 45177.90 | 1.0000 | 1.62884510 | 1.353317 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 79561.50 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.66 | 0.01059112 | 21.00 | 0.01059112 | 68.1495 | 18272.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 70164.407 | 70164.407 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 70164.41 | 29114.36 | 1.0000 | 1.04968972 | 0.872129 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 70164.41 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.64 | 0.01059662 | 21.00 | 0.01059662 | 68.1840 | 12378.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 79468.173 | 79468.173 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 79468.17 | 45178.89 | 1.0000 | 1.62888071 | 1.353346 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 79468.17 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.64 | 0.01051852 | 21.00 | 0.01051852 | 67.6899 | 19500.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 78506.218 | 78506.218 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 78506.22 | 29114.36 | 1.0000 | 1.04968972 | 0.872129 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 78506.22 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.88 | 0.01198188 | 21.00 | 0.01198188 | 76.9323 | 4186.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 8090.484 | 8090.484 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | Sensible | 8090.48 | 4517.79 | 1.0000 | 0.16288451 | 0.135332 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8090.48 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.02 | 0.01020515 | 21.00 | 0.01020515 | 65.7036 | 2670.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 7070.810 | 7070.810 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | Sensible | 7070.81 | 2911.44 | 1.0000 | 0.10496897 | 0.087213 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7070.81 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.02 | 0.01019408 | 21.00 | 0.01019408 | 65.6332 | 1786.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 8105.978 | 8105.978 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | Sensible | 8105.98 | 4517.89 | 1.0000 | 0.16288807 | 0.135335 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8105.98 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 21.02 | 0.01011455 | 21.00 | 0.01011455 | 65.1296 | 2804.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 8303.920 | 8303.920 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8303.92 | 2911.44 | 1.0000 | 0.10496897 | 0.087213 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8303.92 | 20.10 | 0.01479830 | 20.10 | 0.00000000 | 0.0000 | 20.72 | 0.01129125 | 21.00 | 0.01129125 | 72.5731 | 1029.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 267688.810 | -999.000 | 9.661598 | 0.00765587 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.5164 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.661598 | 11.62865059 | 4197.9300 | 999.8980 | 94.12288093 | 15.00 | 6.67 | 8.33 | 3291360.14 | 8.1331 | 8.133076 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | Sensible | 267688.81 | 187966.64 | 1.0000 | 11.62865059 | 9.661598 | 27.05 | 19.53 | 0.01112263 | 55555.1 | 11.05 | 11.05 | 0.00850000 | 32535.3 | 7.65508510 | 6.67 | 15.00 | 8.33 | 20878.198 | 246810.61 | 35.20 | 0.01715815 | 25.83 | 2.53819000 | 26.2709 | 24.00 | 0.00886511 | 24.00 | 0.00886511 | 47.6752 | 128269.97 | 0.00 | 268040.96 | 185964.09 | 11.62865059 | 27.05 | 19.53 | 0.01112263 | 55555.1 | 11.45 | 11.36 | 0.00832425 | 32505.0 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 44870.974 | 44870.974 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.661598 | 11.62865059 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | Sensible | 44870.97 | 44870.97 | 1.0000 | 3.48859518 | 2.898479 | 0.00 | -6.26 | 0.00000000 | 25.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 44870.97 | 0.00 | 0.00000000 | -6.26 | 2.53819000 | 87.5697 | 0.00 | 0.00000000 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | ||
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2621465.878 | -999.000 | 90.341225 | 0.07497359 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.0689 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 90.341225 | 108.73424485 | 4197.9300 | 999.8980 | 94.12288093 | 15.00 | 6.67 | 8.33 | 3291360.14 | 79.6469 | 79.646887 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | Sensible | 2621465.88 | 1792302.56 | 1.0000 | 108.73424485 | 90.341225 | 27.37 | 19.85 | 0.01141984 | 56645.2 | 11.05 | 11.05 | 0.00850000 | 32536.3 | 74.96594417 | 6.67 | 15.00 | 8.33 | 195222.576 | 2426243.30 | 35.20 | 0.01715815 | 25.83 | 25.38195000 | 28.0956 | 24.00 | 0.00894757 | 24.00 | 0.00894757 | 48.1130 | 1159613.01 | 0.00 | 2624894.26 | 1776433.81 | 108.73424485 | 27.37 | 19.86 | 0.01141984 | 56645.2 | 11.45 | 11.36 | 0.00832612 | 32504.8 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 419568.153 | 419568.153 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 90.341225 | 108.73424485 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | Sensible | 419568.15 | 419568.15 | 1.0000 | 32.62027346 | 27.102367 | 0.00 | -6.26 | 0.00000000 | 25.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 419568.15 | 0.00 | 0.00000000 | -6.26 | 25.38195000 | 93.6522 | 0.00 | 0.00000000 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | ||
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 264677.850 | -999.000 | 9.622605 | 0.00756975 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.4593 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.622605 | 11.58171966 | 4197.9300 | 999.8980 | 94.12288093 | 15.00 | 6.67 | 8.33 | 3291360.14 | 8.0416 | 8.041595 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:30:00 | Sensible | 264677.85 | 186198.64 | 1.0000 | 11.58171966 | 9.622605 | 26.96 | 19.47 | 0.01109189 | 55388.3 | 11.05 | 11.05 | 0.00850000 | 32535.2 | 7.56898081 | 6.67 | 15.00 | 8.33 | 20793.938 | 243883.91 | 35.20 | 0.01715815 | 25.83 | 2.53819000 | 26.3774 | 24.00 | 0.00890985 | 24.00 | 0.00890985 | 47.9132 | 131988.15 | 0.00 | 265027.24 | 184180.15 | 11.58171966 | 26.96 | 19.48 | 0.01109189 | 55388.3 | 11.45 | 11.36 | 0.00832427 | 32505.1 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 44689.883 | 44689.883 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.622605 | 11.58171966 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | unknown | unknown | unknown | unknown | unknown | Sensible | 44689.88 | 44689.88 | 1.0000 | 3.47451590 | 2.886782 | 0.00 | -6.26 | 0.00000000 | 25.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 44689.88 | 0.00 | 0.00000000 | -6.26 | 2.53819000 | 87.9246 | 0.00 | 0.00000000 | -999.00 | -999.0 | -999.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | ||
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 137527.604 | -999.000 | 5.739648 | 0.00393327 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.6613 | 1004.8586 | 1.2036 | CAV_BAS FAN | Fan:VariableVolume | 5.739648 | 6.90821123 | 4197.9300 | 999.8980 | 94.12288093 | 15.00 | 6.67 | 8.33 | 3291360.14 | 4.1784 | 4.178443 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 08:00:00 | Sensible | 137527.60 | 98350.98 | 1.0000 | 6.90821123 | 5.739648 | 25.14 | 18.56 | 0.01066264 | 52430.1 | 11.04 | 11.04 | 0.00850000 | 32522.3 | 3.93287084 | 6.67 | 15.00 | 8.33 | 12483.093 | 125044.51 | 29.45 | 0.01714719 | 24.35 | 1.20015641 | 20.9099 | 24.00 | 0.00893822 | 24.00 | 0.00893822 | 48.0627 | 78596.12 | 0.00 | 137689.83 | 96978.88 | 6.90821123 | 25.14 | 18.56 | 0.01066264 | 52430.1 | 11.44 | 11.36 | 0.00832615 | 32498.8 | |
CAV_BAS HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 248495.454 | 248495.454 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | CAV_BAS FAN | Fan:VariableVolume | 5.739648 | 6.90821123 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 248495.45 | 248495.45 | 1.0000 | 6.90821123 | 5.739648 | 4.20 | 4.20 | 0.00981697 | 28851.6 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 248495.45 | 20.10 | 0.01479830 | 20.10 | 1.20015641 | 20.9099 | 0.00 | 0.00850000 | 26.70 | 0.00850000 | 38.9515 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 499781.569 | 359778.756 | 24.573970 | 0.01223962 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.9403 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 07:10:00 | Sensible | 468208.63 | 457318.12 | 0.9368 | -999.0 | -999.0 | 28.50 | 18.07 | 0.00866096 | 50761.8 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 468208.63 | 35.20 | 0.01715815 | 25.83 | 0.33839277 | -999.0000 | 27.00 | 0.00854217 | 27.00 | 0.00854217 | 38.4637 | 372220.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9668.225 | 6921.846 | 0.471008 | 0.00023677 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.3343 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:20:00 | Sensible | 9071.26 | 8587.70 | 0.9383 | -999.0 | -999.0 | 28.16 | 18.12 | 0.00887293 | 50951.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9071.26 | 33.44 | 0.01715480 | 25.39 | 0.01563234 | -999.0000 | 27.00 | 0.00858822 | 27.00 | 0.00858822 | 38.6660 | 8203.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 92231.891 | 65930.950 | 4.480158 | 0.00225875 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.3687 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:50:00 | Sensible | 86580.26 | 81751.83 | 0.9387 | -999.0 | -999.0 | 28.17 | 18.14 | 0.00889141 | 51009.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 86580.26 | 33.44 | 0.01715480 | 25.39 | 0.15632344 | -999.0000 | 27.00 | 0.00859260 | 27.00 | 0.00859260 | 38.6857 | 78125.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9387.487 | 6714.576 | 0.456519 | 0.00022990 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.3552 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 17:40:00 | Sensible | 8810.53 | 8327.66 | 0.9385 | -999.0 | -999.0 | 28.17 | 18.14 | 0.00888417 | 50986.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8810.53 | 33.44 | 0.01715480 | 25.39 | 0.01563234 | -999.0000 | 27.00 | 0.00859092 | 27.00 | 0.00859092 | 38.6781 | 7962.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 499781.569 | 499781.569 | 24.573970 | 0.01223962 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 499781.57 | 499781.57 | 1.0000 | 29.57710732 | 24.573970 | 20.10 | 20.10 | 0.01479830 | 57759.9 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 499781.57 | 20.10 | 0.01479830 | 20.10 | 0.33839277 | 1.3770 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9668.225 | 9668.225 | 0.471008 | 0.00023677 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9668.23 | 9668.23 | 1.0000 | 0.56690263 | 0.471008 | 20.10 | 20.10 | 0.01479830 | 57759.9 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9668.23 | 20.10 | 0.01479830 | 20.10 | 0.01563234 | 3.3189 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 92231.891 | 92231.891 | 4.480158 | 0.00225875 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 92231.89 | 92231.89 | 1.0000 | 5.39229569 | 4.480158 | 20.10 | 20.10 | 0.01479830 | 57759.9 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 92231.89 | 20.10 | 0.01479830 | 20.10 | 0.15632344 | 3.4892 | 0.00 | 0.00850000 | 26.35 | 0.00850000 | 39.7705 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9387.487 | 9387.487 | 0.456519 | 0.00022990 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9387.49 | 9387.49 | 1.0000 | 0.54946370 | 0.456519 | 20.10 | 20.10 | 0.01479830 | 57759.9 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9387.49 | 20.10 | 0.01479830 | 20.10 | 0.01563234 | 3.4243 | 0.00 | 0.00850390 | 25.99 | 0.00850390 | 40.6392 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8144.407 | 8144.407 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 24.573970 | 29.57710732 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 8144.41 | 8144.41 | 1.0000 | 29.57710732 | 24.573970 | 0.28 | 0.28 | 0.00858673 | 21757.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8144.41 | 20.10 | 0.01479830 | 20.10 | 0.33839277 | 1.3770 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 376.238 | 376.238 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.471008 | 0.56690263 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 376.24 | 376.24 | 1.0000 | 0.56690263 | 0.471008 | 0.67 | 0.67 | 0.00870904 | 22461.9 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 376.24 | 20.10 | 0.01479830 | 20.10 | 0.01563234 | 3.3189 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 3762.379 | 3762.379 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.480158 | 5.39229569 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 3762.38 | 3762.38 | 1.0000 | 5.39229569 | 4.480158 | 0.70 | 0.70 | 0.00871976 | 22523.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 3762.38 | 20.10 | 0.01479830 | 20.10 | 0.15632344 | 3.4892 | 0.00 | 0.00850000 | 26.35 | 0.00850000 | 39.7705 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 376.238 | 376.238 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.456519 | 0.54946370 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 376.24 | 376.24 | 1.0000 | 0.54946370 | 0.456519 | 0.69 | 0.69 | 0.00871944 | 22509.6 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 376.24 | 20.10 | 0.01479830 | 20.10 | 0.01563234 | 3.4243 | 0.00 | 0.00850390 | 25.99 | 0.00850390 | 40.6392 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:43
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 5943.00 | 5769.83 | 5769.83 |
CORE_BOTTOM | 5943.00 | 3.33 | 3.33 |
CORE_MID | 4187.83 | 243.33 | 0.00 |
CORE_TOP | 4695.17 | 47.17 | 0.00 |
PERIMETER_BOT_ZN_3 | 5943.00 | 479.00 | 479.00 |
PERIMETER_BOT_ZN_2 | 5942.00 | 565.83 | 565.83 |
PERIMETER_BOT_ZN_1 | 5943.00 | 526.67 | 526.67 |
PERIMETER_BOT_ZN_4 | 5943.00 | 535.83 | 535.83 |
PERIMETER_MID_ZN_3 | 5877.67 | 167.17 | 165.33 |
PERIMETER_MID_ZN_2 | 4916.17 | 424.50 | 419.67 |
PERIMETER_MID_ZN_1 | 5920.00 | 334.50 | 334.50 |
PERIMETER_MID_ZN_4 | 5816.67 | 319.67 | 311.33 |
PERIMETER_TOP_ZN_3 | 5789.50 | 328.33 | 309.50 |
PERIMETER_TOP_ZN_2 | 5769.17 | 541.83 | 526.33 |
PERIMETER_TOP_ZN_1 | 5875.33 | 447.00 | 444.67 |
PERIMETER_TOP_ZN_4 | 5690.00 | 408.00 | 374.33 |
DATACENTER_BOT_ZN_6 | 5943.00 | 4744.17 | 4744.17 |
DATACENTER_MID_ZN_6 | 5943.00 | 820.17 | 820.17 |
DATACENTER_TOP_ZN_6 | 5943.00 | 1598.17 | 1598.17 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5943.00 | 5943.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 8624.00 | 0.00 | 5830.33 |
CORE_BOTTOM | 0.00 | 104.50 | 0.00 | 2.33 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 269.83 | 0.00 | 126.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 216.17 | 0.00 | 133.83 |
PERIMETER_BOT_ZN_1 | 0.00 | 477.17 | 0.00 | 353.33 |
PERIMETER_BOT_ZN_4 | 0.00 | 289.83 | 0.00 | 106.00 |
PERIMETER_MID_ZN_3 | 0.00 | 26.33 | 0.00 | 21.50 |
PERIMETER_MID_ZN_2 | 0.00 | 74.00 | 0.00 | 73.17 |
PERIMETER_MID_ZN_1 | 0.00 | 149.67 | 0.00 | 143.83 |
PERIMETER_MID_ZN_4 | 0.00 | 74.17 | 0.00 | 51.83 |
PERIMETER_TOP_ZN_3 | 0.00 | 53.00 | 0.00 | 42.17 |
PERIMETER_TOP_ZN_2 | 0.00 | 100.33 | 0.00 | 94.83 |
PERIMETER_TOP_ZN_1 | 0.00 | 129.50 | 0.00 | 117.83 |
PERIMETER_TOP_ZN_4 | 0.00 | 87.17 | 0.00 | 61.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 147.50 | 0.00 | 138.17 |
DATACENTER_MID_ZN_6 | 0.00 | 80.00 | 0.00 | 79.67 |
DATACENTER_TOP_ZN_6 | 0.00 | 51.50 | 0.00 | 49.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 8631.17 | 0.00 | 5837.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:43
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 0.020 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.494 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.456 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.456 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.663 | 0.013 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 0.776 | 0.013 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 0.695 | 0.013 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 0.893 | 0.013 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.712 | 0.030 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 0.864 | 0.033 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 0.800 | 0.030 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 0.959 | 0.031 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.697 | 0.037 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 0.889 | 0.038 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 0.783 | 0.037 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 0.934 | 0.038 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.590 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.590 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.590 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 0.664 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.579 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.579 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.579 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 0.652 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:43
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 60.99 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.86 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.79 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.20 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1010.73 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 879006.49 | 0.00 | 879006.49 | 0.00 | 879006.49 | 37848132.68 | 8556.55 | 203.45 | 0.00 | 23.66 |
CORE_BOTTOM | 26265679.91 | 0.00 | 26265679.91 | 0.00 | 26265679.91 | 33990283.35 | 8560.94 | 55.22 | 143.84 | 1779.98 |
CORE_MID | 0.21E+09 | 0.00 | 0.21E+09 | 0.00 | 0.21E+09 | 0.34E+09 | 8739.41 | 4.85 | 15.74 | 794.40 |
CORE_TOP | 21041833.14 | 0.00 | 21041833.14 | 0.00 | 21041833.14 | 33990283.35 | 8745.80 | 2.50 | 11.70 | 803.86 |
PERIMETER_BOT_ZN_3 | 4168890.59 | 0.00 | 4168890.59 | 115795.02 | 4284685.60 | 4267819.30 | 3846.75 | 54.87 | 4858.38 | 1779.98 |
PERIMETER_BOT_ZN_2 | 3188649.44 | 0.00 | 3188649.44 | 77196.63 | 3265846.06 | 2750345.05 | 1574.35 | 24.69 | 7160.95 | 1779.98 |
PERIMETER_BOT_ZN_1 | 4307892.19 | 0.00 | 4307892.19 | 115795.02 | 4423687.21 | 4267912.63 | 3884.26 | 71.19 | 4804.56 | 1779.98 |
PERIMETER_BOT_ZN_4 | 3809702.12 | 0.00 | 3809702.12 | 77196.63 | 3886898.75 | 2750345.05 | 1507.38 | 6.14 | 7246.47 | 1779.98 |
PERIMETER_MID_ZN_3 | 39101394.28 | 0.00 | 39101394.28 | 271564.58 | 39372958.86 | 42678193.03 | 4382.22 | 36.78 | 4341.00 | 794.40 |
PERIMETER_MID_ZN_2 | 32114543.63 | 0.00 | 32114543.63 | 181042.93 | 32295586.56 | 27503450.52 | 2775.26 | 0.98 | 5983.76 | 1703.40 |
PERIMETER_MID_ZN_1 | 43524672.04 | 0.00 | 43524672.04 | 271564.58 | 43796236.62 | 42679126.28 | 4149.17 | 15.73 | 4595.10 | 794.40 |
PERIMETER_MID_ZN_4 | 34477680.98 | 0.00 | 34477680.98 | 181042.93 | 34658723.91 | 27503450.52 | 2773.08 | 0.99 | 5985.93 | 794.40 |
PERIMETER_TOP_ZN_3 | 3844215.63 | 0.00 | 3844215.63 | 337167.46 | 4181383.09 | 4267819.30 | 4466.87 | 31.78 | 4261.35 | 803.86 |
PERIMETER_TOP_ZN_2 | 3174937.68 | 0.00 | 3174937.68 | 224778.15 | 3399715.84 | 2750345.05 | 2763.71 | 0.59 | 5995.70 | 803.86 |
PERIMETER_TOP_ZN_1 | 4272807.62 | 0.00 | 4272807.62 | 337167.46 | 4609975.08 | 4267912.63 | 4185.53 | 26.20 | 4548.27 | 803.86 |
PERIMETER_TOP_ZN_4 | 3387254.61 | 0.00 | 3387254.61 | 224778.15 | 3612032.76 | 2750345.05 | 2760.21 | 0.27 | 5999.52 | 803.86 |
DATACENTER_BOT_ZN_6 | 492981.60 | 0.00 | 492981.60 | 0.00 | 492981.60 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_MID_ZN_6 | 4929751.20 | 0.00 | 4929751.20 | 0.00 | 4929751.20 | 4929815.99 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_TOP_ZN_6 | 492981.60 | 0.00 | 492981.60 | 0.00 | 492981.60 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_BASEMENT_ZN_6 | 10671554.30 | 0.00 | 10671554.30 | 0.00 | 10671554.30 | 10671554.30 | 0.00 | 8760.00 | 0.00 | 2817.00 |
Total Facility | 0.37E+10 | 0.00 | 0.37E+10 | 10562024.78 | 0.37E+10 | 0.50E+10 | 8760.00 | 8760.00 | 7657.69 | 3726.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 0.0363 | 0.0000 | 0.0363 | 0.0000 | 0.0363 | 1.2002 | 5763.22 | 179.78 | 0.00 |
CORE_BOTTOM | 0.9101 | 0.0000 | 0.9101 | 0.0000 | 0.9101 | 1.0778 | 5833.09 | 42.96 | 66.95 |
CORE_MID | 8.4049 | 0.0000 | 8.4049 | 0.0000 | 8.4049 | 10.7782 | 5926.69 | 4.56 | 11.75 |
CORE_TOP | 0.8409 | 0.0000 | 0.8409 | 0.0000 | 0.8409 | 1.0778 | 5932.63 | 2.11 | 8.27 |
PERIMETER_BOT_ZN_3 | 0.1534 | 0.0000 | 0.1534 | 0.0029 | 0.1564 | 0.1353 | 1260.63 | 45.44 | 4636.92 |
PERIMETER_BOT_ZN_2 | 0.1158 | 0.0000 | 0.1158 | 0.0020 | 0.1178 | 0.0872 | 491.29 | 19.02 | 5432.69 |
PERIMETER_BOT_ZN_1 | 0.1608 | 0.0000 | 0.1608 | 0.0029 | 0.1637 | 0.1353 | 1246.07 | 59.18 | 4637.75 |
PERIMETER_BOT_ZN_4 | 0.1332 | 0.0000 | 0.1332 | 0.0020 | 0.1351 | 0.0872 | 461.83 | 5.55 | 5475.62 |
PERIMETER_MID_ZN_3 | 1.6469 | 0.0000 | 1.6469 | 0.0069 | 1.6538 | 1.3533 | 1591.05 | 36.07 | 4315.88 |
PERIMETER_MID_ZN_2 | 1.2887 | 0.0000 | 1.2887 | 0.0049 | 1.2935 | 0.8721 | 750.85 | 0.28 | 4282.87 |
PERIMETER_MID_ZN_1 | 1.8526 | 0.0000 | 1.8526 | 0.0069 | 1.8595 | 1.3533 | 1366.82 | 15.02 | 4561.17 |
PERIMETER_MID_ZN_4 | 1.4299 | 0.0000 | 1.4299 | 0.0046 | 1.4345 | 0.8721 | 749.98 | 0.95 | 5192.07 |
PERIMETER_TOP_ZN_3 | 0.1613 | 0.0000 | 0.1613 | 0.0085 | 0.1699 | 0.1353 | 1685.19 | 31.12 | 4226.69 |
PERIMETER_TOP_ZN_2 | 0.1327 | 0.0000 | 0.1327 | 0.0057 | 0.1384 | 0.0872 | 748.43 | 0.30 | 5194.27 |
PERIMETER_TOP_ZN_1 | 0.1813 | 0.0000 | 0.1813 | 0.0085 | 0.1898 | 0.1353 | 1409.18 | 25.16 | 4508.66 |
PERIMETER_TOP_ZN_4 | 0.1393 | 0.0000 | 0.1393 | 0.0057 | 0.1450 | 0.0872 | 746.81 | 0.24 | 5195.95 |
DATACENTER_BOT_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1563 | 0.0000 | 0.1563 | 0.0000 | 0.1563 | 0.1563 | 0.00 | 5943.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.3384 | 0.0000 | 0.3384 | 0.0000 | 0.3384 | 0.3384 | 0.00 | 5943.00 | 0.00 |
Total Facility | 151.1278 | 0.0000 | 151.1278 | 0.2704 | 151.3982 | 158.4706 | 5943.00 | 5943.00 | 5642.69 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 60467465.03 | 0.00 | 60467465.03 | 48026705.38 | 1481.94 | 0.00 | 7278.06 | 1779.98 |
VAV_MID WITH REHEAT | 0.52E+09 | 0.00 | 0.52E+09 | 0.48E+09 | 2770.04 | 0.00 | 5989.96 | 794.40 |
VAV_TOP WITH REHEAT | 51746836.89 | 0.00 | 51746836.89 | 48026705.38 | 2759.07 | 0.00 | 6000.93 | 803.86 |
CAV_BAS | 1273364.84 | 0.00 | 1273364.84 | 37848132.68 | 8556.55 | 0.00 | 203.45 | 23.66 |
AIRLOOP DATACENTER BASEMENT | 15459249.82 | 0.00 | 15459249.82 | 10671554.30 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER BOT | 714153.30 | 0.00 | 714153.30 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER MID | 7141532.97 | 0.00 | 7141532.97 | 4929815.99 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER TOP | 714153.30 | 0.00 | 714153.30 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 2.1343 | 0.0000 | 2.1343 | 1.5229 | 444.92 | 0.00 | 5498.08 |
VAV_MID WITH REHEAT | 21.2636 | 0.0000 | 21.2636 | 15.2292 | 747.44 | 0.00 | 5195.56 |
VAV_TOP WITH REHEAT | 2.1085 | 0.0000 | 2.1085 | 1.5229 | 745.93 | 0.00 | 5197.07 |
CAV_BAS | 0.0526 | 0.0000 | 0.0526 | 1.2002 | 5763.22 | 0.00 | 179.78 |
AIRLOOP DATACENTER BASEMENT | 0.4902 | 0.0000 | 0.4902 | 0.3384 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER BOT | 0.0226 | 0.0000 | 0.0226 | 0.0156 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER MID | 0.2265 | 0.0000 | 0.2265 | 0.1563 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER TOP | 0.0226 | 0.0000 | 0.0226 | 0.0156 | 0.00 | 0.00 | 5943.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7278.06 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5989.96 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6000.93 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 203.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.3071 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 24.3252 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.4112 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.7462 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4902 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2265 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:43
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1441 |
Defaulted Fields | 1151 |
Fields with Defaults | 3726 |
Autosized Fields | 291 |
Autosizable Fields | 364 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 472 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:43
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 34229.69 | 394883.03 | 16-JAN-05:20 | 2068653.65 | 22-AUG-15:20 |
Electricity:Building | 17886.15 | 217330.97 | 29-MAY-17:20 | 1092983.62 | 18-DEC-16:50 |
Electricity:Zone:BASEMENT | 640.57 | 14055.89 | 01-JAN-00:10 | 32859.63 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 17886.15 | 217330.97 | 29-MAY-17:20 | 1092983.62 | 18-DEC-16:50 |
InteriorLights:Electricity | 3209.76 | 10074.82 | 29-MAY-17:20 | 314611.94 | 18-DEC-16:50 |
InteriorLights:Electricity:Zone:BASEMENT | 216.17 | 598.35 | 01-JAN-00:10 | 19402.09 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3209.76 | 10074.82 | 29-MAY-17:20 | 314611.94 | 18-DEC-16:50 |
LightsWired:InteriorLights:Electricity | 3209.76 | 10074.82 | 29-MAY-17:20 | 314611.94 | 18-DEC-16:50 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 216.17 | 598.35 | 01-JAN-00:10 | 19402.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3209.76 | 10074.82 | 29-MAY-17:20 | 314611.94 | 18-DEC-16:50 |
Electricity:Zone:CORE_BOTTOM | 483.75 | 4990.59 | 01-JAN-00:10 | 34631.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4837.49 | 49905.77 | 01-JAN-00:10 | 346310.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1941.37 | 5373.60 | 01-JAN-00:10 | 174244.37 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1941.37 | 5373.60 | 01-JAN-00:10 | 174244.37 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 483.75 | 4990.58 | 01-JAN-00:10 | 34631.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 50.07 | 617.00 | 07-MAY-17:10 | 4067.08 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 13.71 | 57.83 | 01-JAN-08:50 | 1906.53 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 13.71 | 57.83 | 01-JAN-08:50 | 1906.53 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 32.32 | 401.23 | 04-JUL-17:10 | 2620.98 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 8.88 | 37.27 | 01-JAN-07:20 | 1228.64 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 8.88 | 37.27 | 01-JAN-07:20 | 1228.64 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 50.02 | 622.62 | 12-MAR-17:10 | 4067.16 | 09-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 13.65 | 57.83 | 01-JAN-08:00 | 1906.57 | 09-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 13.65 | 57.83 | 01-JAN-08:00 | 1906.57 | 09-NOV-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 32.22 | 397.61 | 12-MAR-17:10 | 2620.97 | 18-DEC-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 8.78 | 37.27 | 01-JAN-09:10 | 1228.64 | 18-DEC-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 8.78 | 37.27 | 01-JAN-09:10 | 1228.64 | 18-DEC-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 500.50 | 6169.98 | 07-MAY-17:10 | 40670.84 | 02-JAN-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 136.84 | 578.27 | 01-JAN-08:30 | 19065.32 | 02-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 136.84 | 578.27 | 01-JAN-08:30 | 19065.32 | 02-JAN-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 323.01 | 4012.33 | 11-JUN-17:10 | 26209.84 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 88.65 | 372.66 | 01-JAN-07:20 | 12286.42 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 88.65 | 372.66 | 01-JAN-07:20 | 12286.42 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 499.96 | 6226.18 | 12-MAR-17:10 | 40671.59 | 09-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 136.30 | 578.28 | 01-JAN-07:50 | 19065.74 | 09-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 136.30 | 578.28 | 01-JAN-07:50 | 19065.74 | 09-NOV-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 322.03 | 3976.14 | 12-MAR-17:10 | 26209.75 | 18-DEC-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 87.68 | 372.66 | 01-JAN-09:00 | 12286.42 | 18-DEC-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 87.68 | 372.66 | 01-JAN-09:00 | 12286.42 | 18-DEC-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 50.05 | 617.00 | 07-MAY-17:10 | 4067.08 | 02-JAN-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 13.68 | 57.83 | 01-JAN-08:30 | 1906.53 | 02-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 13.68 | 57.83 | 01-JAN-08:30 | 1906.53 | 02-JAN-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 32.30 | 401.23 | 11-JUN-17:10 | 2620.98 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 8.86 | 37.27 | 01-JAN-07:20 | 1228.64 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 8.86 | 37.27 | 01-JAN-07:20 | 1228.64 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 49.99 | 622.62 | 12-MAR-17:10 | 4067.16 | 09-NOV-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 13.63 | 57.83 | 01-JAN-07:50 | 1906.57 | 09-NOV-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 13.63 | 57.83 | 01-JAN-07:50 | 1906.57 | 09-NOV-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 32.20 | 397.61 | 12-MAR-17:10 | 2620.97 | 18-DEC-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 8.77 | 37.27 | 01-JAN-09:00 | 1228.64 | 18-DEC-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 8.77 | 37.27 | 01-JAN-09:00 | 1228.64 | 18-DEC-16:50 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7557.51 | 95212.03 | 01-JAN-00:10 | 385103.08 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 62.65 | 303.90 | 01-JAN-00:10 | 5470.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 62.65 | 303.90 | 01-JAN-00:10 | 5470.56 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 159.04 | 1973.61 | 01-JAN-00:10 | 8244.54 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1590.36 | 19736.13 | 01-JAN-00:10 | 82445.36 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 51.55 | 250.08 | 01-JAN-00:10 | 4501.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 51.55 | 250.08 | 01-JAN-00:10 | 4501.14 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 159.04 | 1973.61 | 01-JAN-00:10 | 8244.54 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 7320.17 | 53065.11 | 01-JAN-00:10 | 456981.87 | 23-MAY-12:10 |
HeatRejection:Electricity | 2647.08 | 49248.27 | 16-JAN-13:20 | 97598.82 | 01-JAN-18:20 |
General:HeatRejection:Electricity | 2647.08 | 49248.27 | 16-JAN-13:20 | 97598.82 | 01-JAN-18:20 |
Electricity:HVAC | 6168.56 | 88620.22 | 24-JAN-05:00 | 400097.93 | 12-APR-13:30 |
ExteriorEquipment:Electricity | 2566.60 | 20217.42 | 01-JAN-00:10 | 233419.57 | 23-OCT-07:20 |
Transformer:ExteriorEquipment:Electricity | 55.00 | 979.82 | 01-JAN-00:10 | 3448.90 | 18-DEC-17:00 |
ElectricityPurchased:Facility | 34229.69 | 394883.03 | 16-JAN-05:20 | 2068653.65 | 22-AUG-15:20 |
ElectricityPurchased:Plant | 34229.69 | 394883.03 | 16-JAN-05:20 | 2068653.65 | 22-AUG-15:20 |
Cogeneration:ElectricityPurchased | 34229.69 | 394883.03 | 16-JAN-05:20 | 2068653.65 | 22-AUG-15:20 |
General:Cogeneration:ElectricityPurchased | 34229.69 | 394883.03 | 16-JAN-05:20 | 2068653.65 | 22-AUG-15:20 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 34229.69 | 394883.03 | 16-JAN-05:20 | 2068653.65 | 22-AUG-15:20 |
ElectricityNet:Plant | 34229.69 | 394883.03 | 16-JAN-05:20 | 2068653.65 | 22-AUG-15:20 |
Cogeneration:ElectricityNet | 34229.69 | 394883.03 | 16-JAN-05:20 | 2068653.65 | 22-AUG-15:20 |
General:Cogeneration:ElectricityNet | 34229.69 | 394883.03 | 16-JAN-05:20 | 2068653.65 | 22-AUG-15:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Fans:Electricity | 2432.44 | 46585.74 | 01-JAN-01:00 | 195785.44 | 12-APR-13:30 |
General:Fans:Electricity | 2432.44 | 46585.74 | 01-JAN-01:00 | 195785.44 | 12-APR-13:30 |
ExteriorLights:Electricity | 343.21 | 0.00 | 01-JAN-06:20 | 40855.88 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 343.21 | 0.00 | 01-JAN-06:20 | 40855.88 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 2505.76 | 19200.00 | 01-JAN-00:10 | 229608.34 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 129.80 | 0.00 | 01-JAN-00:10 | 5613.48 | 01-JAN-08:10 |
General:HeatRecovery:Electricity | 129.80 | 0.00 | 01-JAN-00:10 | 5613.48 | 01-JAN-08:10 |
Cooling:Electricity | 6993.88 | 40407.13 | 23-JAN-05:50 | 469909.35 | 13-APR-12:50 |
General:Cooling:Electricity | 6993.88 | 40407.13 | 23-JAN-05:50 | 469909.35 | 13-APR-12:50 |
Humidifier:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Humidifier:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 281.34 | 0.00 | 01-JAN-00:10 | 32218.47 | 17-JAN-13:00 |
Water Heater:WaterSystems:Electricity | 281.34 | 0.00 | 01-JAN-00:10 | 32218.47 | 17-JAN-13:00 |
Pumps:Electricity | 949.18 | 3816.83 | 01-JAN-00:10 | 69572.26 | 18-MAY-11:30 |
General:Pumps:Electricity | 949.18 | 3816.83 | 01-JAN-00:10 | 69572.26 | 18-MAY-11:30 |
WIRED_LTG_ELECTRICITY | 90.19 | 0.00 | 01-JAN-00:10 | 8840.60 | 18-DEC-17:00 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 40410.77 | 196577.61 | 23-JAN-05:50 | 2519999.63 | 11-AUG-14:00 |
PlantLoopCoolingDemand:HVAC | 40410.77 | 196577.61 | 23-JAN-05:50 | 2519999.63 | 11-AUG-14:00 |
CoolingCoils:PlantLoopCoolingDemand | 40410.77 | 196577.61 | 23-JAN-05:50 | 2519999.63 | 11-AUG-14:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 22201.53 | 0.00 | 01-JAN-00:10 | 0.00 | 21-FEB-14:10 |
Water:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Humidifier:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
MainsWater:Facility | 22201.53 | 0.00 | 01-JAN-00:10 | 0.00 | 21-FEB-14:10 |
MainsWater:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Humidifier:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water:Plant | 22201.53 | 0.00 | 01-JAN-00:10 | 0.00 | 21-FEB-14:10 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 22201.53 | 0.00 | 01-JAN-00:10 | 0.00 | 21-FEB-14:10 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 19921.36 | 0.00 | 01-JAN-00:10 | 0.00 | 21-FEB-14:10 |
General:HeatRejection:Water | 19921.36 | 0.00 | 01-JAN-00:10 | 0.00 | 21-FEB-14:10 |
HeatRejection:MainsWater | 19921.36 | 0.00 | 01-JAN-00:10 | 0.00 | 21-FEB-14:10 |
General:HeatRejection:MainsWater | 19921.36 | 0.00 | 01-JAN-00:10 | 0.00 | 21-FEB-14:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 154132.60 | 264729.88 | 24-JAN-05:50 | 10809075.64 | 11-AUG-13:10 |
EnergyTransfer:Building | 25688.60 | 106667.48 | 16-SEP-17:20 | 1659724.67 | 27-DEC-15:20 |
EnergyTransfer:Zone:BASEMENT | 52.23 | 0.00 | 01-JAN-00:10 | 92197.27 | 17-JAN-05:30 |
Heating:EnergyTransfer | 2.87 | 0.00 | 01-JAN-00:10 | 15751.36 | 20-AUG-14:00 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 249.54 | 17-JAN-06:30 |
General:Heating:EnergyTransfer | 2.87 | 0.00 | 01-JAN-00:10 | 15751.36 | 20-AUG-14:00 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 249.54 | 17-JAN-06:30 |
Cooling:EnergyTransfer | 25685.74 | 106667.48 | 16-SEP-17:20 | 1659724.67 | 27-DEC-15:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 52.23 | 0.00 | 01-JAN-00:10 | 92197.27 | 17-JAN-05:30 |
General:Cooling:EnergyTransfer | 25685.74 | 106667.48 | 16-SEP-17:20 | 1659724.67 | 27-DEC-15:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 52.23 | 0.00 | 01-JAN-00:10 | 92197.27 | 17-JAN-05:30 |
EnergyTransfer:Zone:CORE_BOTTOM | 1229.76 | 0.00 | 01-JAN-00:10 | 78661.46 | 16-AUG-09:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 1229.76 | 0.00 | 01-JAN-00:10 | 78661.46 | 16-AUG-09:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 1229.76 | 0.00 | 01-JAN-00:10 | 78661.46 | 16-AUG-09:20 |
EnergyTransfer:Zone:CORE_MID | 6781.01 | 0.00 | 01-JAN-00:10 | 496103.65 | 02-JAN-05:20 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 6781.01 | 0.00 | 01-JAN-00:10 | 496103.65 | 02-JAN-05:20 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 6781.01 | 0.00 | 01-JAN-00:10 | 496103.65 | 02-JAN-05:20 |
EnergyTransfer:Zone:CORE_TOP | 724.89 | 0.00 | 01-JAN-00:10 | 51688.06 | 05-MAY-15:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 724.89 | 0.00 | 01-JAN-00:10 | 51688.06 | 05-MAY-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 724.89 | 0.00 | 01-JAN-00:10 | 51688.06 | 05-MAY-15:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 205.30 | 0.00 | 01-JAN-00:10 | 15607.50 | 12-JUN-16:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 205.30 | 0.00 | 01-JAN-00:10 | 15607.50 | 12-JUN-16:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 205.30 | 0.00 | 01-JAN-00:10 | 15607.50 | 12-JUN-16:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 154.13 | 0.00 | 01-JAN-00:10 | 13358.89 | 12-APR-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 154.13 | 0.00 | 01-JAN-00:10 | 13358.89 | 12-APR-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 154.13 | 0.00 | 01-JAN-00:10 | 13358.89 | 12-APR-09:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 213.41 | 0.00 | 01-JAN-00:10 | 16497.52 | 07-DEC-11:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 213.41 | 0.00 | 01-JAN-00:10 | 16497.52 | 07-DEC-11:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 213.41 | 0.00 | 01-JAN-00:10 | 16497.52 | 07-DEC-11:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 179.17 | 0.00 | 01-JAN-00:10 | 16448.37 | 12-APR-15:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 179.17 | 0.00 | 01-JAN-00:10 | 16448.37 | 12-APR-15:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 179.17 | 0.00 | 01-JAN-00:10 | 16448.37 | 12-APR-15:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1348.48 | 0.00 | 01-JAN-00:10 | 140232.12 | 13-JUN-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1348.48 | 0.00 | 01-JAN-00:10 | 140232.12 | 13-JUN-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1348.48 | 0.00 | 01-JAN-00:10 | 140232.12 | 13-JUN-15:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1097.73 | 0.00 | 01-JAN-00:10 | 117074.15 | 05-MAY-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1097.73 | 0.00 | 01-JAN-00:10 | 117074.15 | 05-MAY-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1097.73 | 0.00 | 01-JAN-00:10 | 117074.15 | 05-MAY-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1519.12 | 0.00 | 01-JAN-00:10 | 150731.84 | 04-JAN-14:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1519.12 | 0.00 | 01-JAN-00:10 | 150731.84 | 04-JAN-14:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1519.12 | 0.00 | 01-JAN-00:10 | 150731.84 | 04-JAN-14:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1175.20 | 0.00 | 01-JAN-00:10 | 133306.70 | 12-APR-15:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1175.20 | 0.00 | 01-JAN-00:10 | 133306.70 | 12-APR-15:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1175.20 | 0.00 | 01-JAN-00:10 | 133306.70 | 12-APR-15:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 141.18 | 0.00 | 01-JAN-00:10 | 15314.94 | 13-JUN-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 141.18 | 0.00 | 01-JAN-00:10 | 15314.94 | 13-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 141.18 | 0.00 | 01-JAN-00:10 | 15314.94 | 13-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 115.26 | 0.00 | 01-JAN-00:10 | 11995.47 | 05-MAY-09:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 115.26 | 0.00 | 01-JAN-00:10 | 11995.47 | 05-MAY-09:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 115.26 | 0.00 | 01-JAN-00:10 | 11995.47 | 05-MAY-09:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 158.44 | 0.00 | 01-JAN-00:10 | 16601.77 | 04-JAN-14:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 158.44 | 0.00 | 01-JAN-00:10 | 16601.77 | 04-JAN-14:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 158.44 | 0.00 | 01-JAN-00:10 | 16601.77 | 04-JAN-14:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 122.24 | 0.00 | 01-JAN-00:10 | 14020.31 | 18-APR-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 122.24 | 0.00 | 01-JAN-00:10 | 14020.31 | 18-APR-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 122.24 | 0.00 | 01-JAN-00:10 | 14020.31 | 18-APR-15:30 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 195.82 | 0.00 | 01-JAN-00:10 | 16891.72 | 30-MAY-11:20 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.89 | 0.00 | 01-JAN-00:10 | 1981.33 | 04-AUG-22:40 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.89 | 0.00 | 01-JAN-00:10 | 1981.33 | 04-AUG-22:40 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 194.93 | 0.00 | 01-JAN-00:10 | 16891.72 | 30-MAY-11:20 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 194.93 | 0.00 | 01-JAN-00:10 | 16891.72 | 30-MAY-11:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1174.12 | 0.00 | 01-JAN-00:10 | 98100.19 | 15-FEB-16:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1.78 | 0.00 | 01-JAN-00:10 | 15751.36 | 20-AUG-14:00 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1.78 | 0.00 | 01-JAN-00:10 | 15751.36 | 20-AUG-14:00 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1172.34 | 0.00 | 01-JAN-00:10 | 98100.19 | 15-FEB-16:10 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1172.34 | 0.00 | 01-JAN-00:10 | 98100.19 | 15-FEB-16:10 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 175.70 | 0.00 | 01-JAN-00:10 | 23544.63 | 12-APR-13:30 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 0.20 | 0.00 | 01-JAN-00:10 | 2037.61 | 21-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 0.20 | 0.00 | 01-JAN-00:10 | 2037.61 | 21-DEC-05:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 175.50 | 0.00 | 01-JAN-00:10 | 23544.63 | 12-APR-13:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 175.50 | 0.00 | 01-JAN-00:10 | 23544.63 | 12-APR-13:30 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 148.09 | 1592.30 | 16-SEP-07:00 | 7985.22 | 03-DEC-17:20 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 148.09 | 1592.30 | 16-SEP-07:00 | 7985.22 | 03-DEC-17:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 148.09 | 1592.30 | 16-SEP-07:00 | 7985.22 | 03-DEC-17:20 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1369.82 | 12281.28 | 16-SEP-07:00 | 74867.26 | 15-DEC-17:00 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1369.82 | 12281.28 | 16-SEP-07:00 | 74867.26 | 15-DEC-17:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1369.82 | 12281.28 | 16-SEP-07:00 | 74867.26 | 15-DEC-17:00 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 137.90 | 1116.96 | 16-SEP-07:00 | 7566.79 | 25-DEC-17:00 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 137.90 | 1116.96 | 16-SEP-07:00 | 7566.79 | 25-DEC-17:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 137.90 | 1116.96 | 16-SEP-07:00 | 7566.79 | 25-DEC-17:00 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7269.59 | 90355.95 | 22-JAN-00:30 | 371309.03 | 28-AUG-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7269.59 | 90355.95 | 22-JAN-00:30 | 371309.03 | 28-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7269.59 | 90355.95 | 22-JAN-00:30 | 371309.03 | 28-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 276.97 | 0.00 | 01-JAN-00:10 | 31774.82 | 12-JAN-12:10 |
PlantLoopHeatingDemand:Plant | 276.97 | 0.00 | 01-JAN-00:10 | 31774.82 | 12-JAN-12:10 |
WaterSystems:PlantLoopHeatingDemand | 276.97 | 0.00 | 01-JAN-00:10 | 31774.82 | 12-JAN-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 276.97 | 0.00 | 01-JAN-00:10 | 31774.82 | 12-JAN-12:10 |
EnergyTransfer:HVAC | 44744.70 | 156170.48 | 23-JAN-05:50 | 2953197.84 | 11-AUG-14:00 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
CoolingCoils:EnergyTransfer | 36859.46 | 156170.48 | 23-JAN-05:50 | 2324943.66 | 11-AUG-14:00 |
HeatRecoveryForHeating:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 26-DEC-08:00 |
HeatRecoveryForCooling:EnergyTransfer | 7885.24 | 0.00 | 01-JAN-00:10 | 833588.96 | 30-SEP-11:00 |
PlantLoopHeatingDemand:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatingCoils:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Plant | 83699.29 | 0.00 | 01-JAN-00:10 | 6489231.41 | 22-MAY-15:10 |
LoopToLoop:EnergyTransfer | 26625.27 | 0.00 | 01-JAN-00:10 | 1949991.84 | 11-AUG-13:10 |
WaterSystems:EnergyTransfer | 276.97 | 0.00 | 01-JAN-00:10 | 31774.82 | 12-JAN-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 276.97 | 0.00 | 01-JAN-00:10 | 31774.82 | 12-JAN-12:10 |
Chillers:EnergyTransfer | 26677.24 | 0.00 | 01-JAN-00:10 | 2158065.69 | 22-MAY-15:10 |
HeatRejection:EnergyTransfer | 30119.81 | 0.00 | 01-JAN-00:10 | 2431705.48 | 22-MAY-15:10 |
General:HeatRejection:EnergyTransfer | 30119.81 | 0.00 | 01-JAN-00:10 | 2431705.48 | 22-MAY-15:10 |
Boilers:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:43
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -52.220 | 0.000 | 0.000 | 44.517 | 216.171 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -632.865 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -1229.765 | 0.000 | 0.000 | 83.279 | 194.137 | 289.614 | 0.000 | 0.000 | 0.000 | 662.735 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
CORE_MID | 0.000 | 0.000 | 0.000 | -6781.008 | 0.000 | 0.000 | 837.587 | 1941.366 | 2896.128 | 0.000 | 0.000 | 0.000 | 1105.927 | 0.000 | 0.000 | 0.000 | 0.000 | -0.049 |
CORE_TOP | 0.000 | 0.000 | 0.000 | -724.893 | 0.000 | 0.000 | 83.718 | 194.137 | 289.613 | 0.000 | 0.000 | 0.000 | 157.425 | 0.000 | 0.000 | 0.000 | 0.000 | -0.004 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -205.303 | 0.000 | 0.000 | 10.430 | 13.705 | 36.365 | 64.177 | 0.000 | 0.350 | 89.779 | 0.000 | -9.439 | 0.000 | -0.065 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -154.127 | 0.000 | 0.000 | 6.733 | 8.880 | 23.435 | 65.019 | 0.000 | 0.243 | 55.591 | 0.000 | -5.738 | 0.000 | -0.038 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -213.413 | 0.000 | 0.000 | 10.363 | 13.649 | 36.366 | 83.274 | 0.000 | 0.352 | 78.538 | 0.000 | -9.061 | 0.000 | -0.068 | 0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -179.167 | 0.000 | 0.000 | 6.734 | 8.782 | 23.435 | 64.485 | 0.000 | 0.240 | 82.619 | 0.000 | -7.082 | 0.000 | -0.045 | -0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.000 | -1348.457 | 0.000 | 0.000 | 104.636 | 136.845 | 363.654 | 668.713 | 0.000 | 8.755 | 135.069 | 0.000 | -67.753 | 0.000 | -1.461 | -0.003 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.000 | -1097.711 | 0.000 | 0.000 | 49.475 | 88.653 | 234.352 | 662.435 | 0.000 | 5.846 | 102.597 | 0.000 | -44.603 | 0.000 | -1.045 | -0.005 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.000 | -1519.094 | 0.000 | 0.000 | 104.238 | 136.298 | 363.660 | 855.185 | 0.000 | 8.600 | 124.761 | 0.000 | -71.886 | 0.000 | -1.761 | -0.011 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.000 | -1175.183 | 0.000 | 0.000 | 67.424 | 87.677 | 234.351 | 659.369 | 0.000 | 5.568 | 178.389 | 0.000 | -56.279 | 0.000 | -1.316 | -0.005 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.000 | -141.174 | 0.000 | 0.000 | 10.464 | 13.684 | 36.365 | 65.910 | 0.000 | 1.029 | 20.977 | 0.000 | -7.063 | 0.000 | -0.193 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.000 | -115.261 | 0.000 | 0.000 | 6.741 | 8.865 | 23.435 | 65.562 | 0.000 | 0.691 | 14.735 | 0.000 | -4.631 | 0.000 | -0.137 | -0.001 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.000 | -158.437 | 0.000 | 0.000 | 10.439 | 13.629 | 36.366 | 84.547 | 0.000 | 1.017 | 20.096 | 0.000 | -7.427 | 0.000 | -0.230 | -0.001 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.000 | -122.240 | 0.000 | 0.000 | 6.748 | 8.767 | 23.435 | 65.371 | 0.000 | 0.673 | 23.126 | 0.000 | -5.712 | 0.000 | -0.168 | -0.000 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -148.087 | 0.000 | 0.000 | 0.946 | 5.155 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -11.894 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.000 | -1369.826 | 0.000 | 0.000 | 9.468 | 51.551 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -229.999 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.000 | -137.904 | 0.000 | 0.000 | 0.948 | 5.155 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -22.079 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7269.600 | 0.000 | 0.000 | 20.563 | 62.653 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -308.473 |
GROUNDFLOOR_PLENUM | 0.888 | -194.932 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.572 | 193.641 | 0.000 | 0.000 | 0.000 | -0.170 | 0.000 |
MIDFLOOR_PLENUM | 1.784 | -1172.331 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 12.281 | 1160.521 | 0.000 | 0.000 | 0.000 | -2.255 | 0.000 |
TOPFLOOR_PLENUM | 0.197 | -175.498 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.199 | 174.368 | 0.000 | 0.000 | 0.000 | -0.265 | 0.000 |
Total Facility | 2.869 | -1542.762 | 0.000 | -24142.871 | 0.000 | 0.000 | 1475.450 | 3209.758 | 14676.396 | 3404.048 | 0.000 | 47.416 | 4380.895 | 0.000 | -296.673 | 0.000 | -9.218 | -1205.391 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 17-JAN-06:31 | 0.00 | 0.00 | 0.00 | -103784.70 | 0.00 | 0.00 | 658.87 | 2155.87 | 13457.54 | 0.00 | 0.00 | 0.00 | 87512.42 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 27-DEC-05:13 | 0.00 | 0.00 | 0.00 | -98667.77 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 92192.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 24-JAN-05:12 | 0.00 | 0.00 | 0.00 | -843757.34 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 779007.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 03-FEB-05:13 | 0.00 | 0.00 | 0.00 | -83659.60 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 77184.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 18-JUN-15:41 | 0.00 | 0.00 | 0.00 | -20265.17 | 0.00 | 0.00 | 34.73 | 57.83 | 720.18 | 7114.99 | 0.00 | 72.84 | 12264.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 28-MAY-09:42 | 0.00 | 0.00 | 0.00 | -19246.18 | 0.00 | 0.00 | 21.72 | 37.27 | 464.11 | 8291.57 | 0.00 | 23.84 | 10407.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 08-JAN-14:32 | 0.00 | 0.00 | 0.00 | -19696.20 | 0.00 | 0.00 | 34.40 | 57.83 | 720.19 | 11545.85 | 0.00 | 26.49 | 7311.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 18-JUN-15:41 | 0.00 | 0.00 | 0.00 | -26190.63 | 0.00 | 0.00 | 19.25 | 37.27 | 464.11 | 9939.11 | 0.00 | 45.99 | 15684.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 11-JUN-17:11 | 0.00 | 0.00 | 0.00 | -184819.46 | 0.00 | 0.00 | 0.00 | 578.27 | 5591.71 | 50006.45 | 0.00 | 1369.63 | 127273.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 14-MAY-09:42 | 0.00 | 0.00 | 0.00 | -193440.12 | 0.00 | 0.00 | 231.51 | 372.66 | 4641.14 | 83499.43 | 0.00 | 587.56 | 104107.82 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 08-JAN-14:42 | 0.00 | 0.00 | 0.00 | -185785.07 | 0.00 | 0.00 | 354.15 | 578.28 | 7201.95 | 112061.59 | 0.00 | 646.02 | 64943.08 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 26-FEB-15:51 | 0.00 | 0.00 | 0.00 | -223212.57 | 0.00 | 0.00 | 208.69 | 372.66 | 4641.11 | 94694.98 | 0.00 | 1306.82 | 121988.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 14-MAY-15:01 | 0.00 | 0.00 | 0.00 | -20645.62 | 0.00 | 0.00 | 36.98 | 57.83 | 720.18 | 6607.14 | 0.00 | 117.89 | 13105.61 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 14-MAY-09:42 | 0.00 | 0.00 | 0.00 | -19669.75 | 0.00 | 0.00 | 22.63 | 37.27 | 464.11 | 8277.90 | 0.00 | 68.28 | 10799.56 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 29-OCT-12:42 | 0.00 | 0.00 | 0.00 | -20056.77 | 0.00 | 0.00 | 35.78 | 57.83 | 720.19 | 10163.24 | 0.00 | 240.30 | 8839.42 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 04-SEP-15:51 | 0.00 | 0.00 | 0.00 | -23822.70 | 0.00 | 0.00 | 20.18 | 37.27 | 464.11 | 10784.19 | 0.00 | 97.70 | 12419.24 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 03-DEC-17:20 | 0.00 | 0.00 | 0.00 | -7985.19 | 0.00 | 0.00 | 5.24 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 160.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 15-DEC-17:00 | 0.00 | 0.00 | 0.00 | -74864.56 | 0.00 | 0.00 | 1008.40 | 4501.14 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8589.20 |
DATACENTER_TOP_ZN_6 | 25-DEC-17:00 | 0.00 | 0.00 | 0.00 | -7566.74 | 0.00 | 0.00 | 5.31 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -258.00 |
DATACENTER_BASEMENT_ZN_6 | 28-AUG-16:00 | 0.00 | 0.00 | 0.00 | -371300.53 | 0.00 | 0.00 | 2182.96 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -15985.51 |
GROUNDFLOOR_PLENUM | 01-MAY-05:15 | 0.00 | -20212.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.95 | 20202.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 27-JUN-05:02 | 0.00 | -114313.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114463.00 | 0.00 | -0.00 | 0.00 | -149.53 | 0.00 |
TOPFLOOR_PLENUM | 12-APR-13:30 | 0.00 | -23545.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.22 | 23429.53 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 14-DEC-05:12 | 0.00 | 33232.39 | 0.00 | -2016891.14 | 0.00 | 0.00 | 0.00 | 10917.52 | 587299.42 | 0.00 | 0.00 | 0.00 | 1455245.86 | 0.00 | -65136.43 | 0.00 | -4667.61 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 17-JAN-06:30 | 0.00 | 0.00 | 249.64 | 0.00 | 0.00 | 0.00 | 654.88 | 2155.87 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -16517.93 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 26-OCT-23:42 | 8141.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -9.15 | -8132.16 |
MIDFLOOR_PLENUM | 21-AUG-03:02 | 61654.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -206.69 | -61448.22 |
TOPFLOOR_PLENUM | 23-JAN-05:12 | 9487.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -115.56 | -9372.24 |
Total Facility | 21-AUG-03:02 | -1673750.40 | 1742291.86 | 0.00 | -1742291.86 | 0.00 | 0.00 | 0.00 | 10313.53 | 587299.42 | 0.00 | 0.00 | 0.00 | 1103794.23 | 0.00 | -26915.17 | 0.00 | -741.60 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:43
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 10.4425 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.6616 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 98.3942 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 90.3412 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 10.0815 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.6226 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.7396 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.7396 | 0.2091 | 1.0000 | Not calculated | 1.2002 | 0.2091 | ||
AIRLOOP DATACENTER BASEMENT | 24.5737 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.5740 | 0.0138 | 1.0000 | Not calculated | 0.3384 | 0.0138 | ||
AIRLOOP DATACENTER BOT | 0.4710 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4710 | 0.0332 | 1.0000 | Not calculated | 0.0156 | 0.0332 | ||
AIRLOOP DATACENTER MID | 4.4801 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.4802 | 0.0349 | 1.0000 | Not calculated | 0.1563 | 0.0349 | ||
AIRLOOP DATACENTER TOP | 0.4565 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4565 | 0.0342 | 1.0000 | Not calculated | 0.0156 | 0.0342 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.2212 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.8945 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 49.1971 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 28.1943 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.0408 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.8773 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 0.0000 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 0.0000 | 1.0000 | 1.0000 | Not calculated | 1.2002 | |||
AIRLOOP DATACENTER BASEMENT | 24.5737 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.5737 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0138 | ||
AIRLOOP DATACENTER BOT | 0.4710 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4710 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0332 | ||
AIRLOOP DATACENTER MID | 4.4801 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.4801 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0349 | ||
AIRLOOP DATACENTER TOP | 0.4565 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4565 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0342 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 5.7396 | 5.7396 | 0.0000 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.9685 | 5.9685 | 1.9338 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 56.3119 | 56.3119 | 18.9771 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.5827 | 5.5827 | 1.9316 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0657 | 1.0657 | 0.2430 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0239 | 1.0239 | 0.2048 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0310 | 1.0310 | 0.2423 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3533 | 1.3533 | 0.2707 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.0987 | 10.0987 | 2.3833 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.5090 | 10.5090 | 2.1018 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.7163 | 9.7163 | 2.3805 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.7584 | 11.7584 | 2.3517 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1168 | 1.1168 | 0.2424 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0590 | 1.0590 | 0.2118 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0792 | 1.0792 | 0.2428 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2437 | 1.2437 | 0.2487 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4710 | 0.4710 | 0.4710 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.4801 | 4.4801 | 4.4801 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4565 | 0.4565 | 0.4565 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.5737 | 24.5737 | 24.5737 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 10.4425 | 9.6616 | 10.4425 | 2.8945 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 98.3942 | 90.3412 | 98.3942 | 28.1943 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 10.0815 | 9.6226 | 10.0815 | 2.8773 | 0.0000 | 1.0000 |
CAV_BAS | 5.7396 | 5.7396 | 5.7396 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.5737 | 24.5740 | 24.5737 | 24.5737 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4710 | 0.4710 | 0.4710 | 0.4710 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.4801 | 4.4802 | 4.4801 | 4.4801 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4565 | 0.4565 | 0.4565 | 0.4565 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 0.0000 | 0.0000 | 0.0000 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9842 | 2.9842 | 1.9338 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 28.1559 | 28.1559 | 18.9771 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7914 | 2.7914 | 1.9316 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5329 | 0.5329 | 0.2430 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5120 | 0.5120 | 0.2048 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5155 | 0.5155 | 0.2423 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6766 | 0.6766 | 0.2707 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.0493 | 5.0493 | 2.3833 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2545 | 5.2545 | 2.1018 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.8581 | 4.8581 | 2.3805 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.8792 | 5.8792 | 2.3517 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5584 | 0.5584 | 0.2424 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5295 | 0.5295 | 0.2118 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5396 | 0.5396 | 0.2428 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6219 | 0.6219 | 0.2487 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4710 | 0.4710 | 0.4710 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.4801 | 4.4801 | 4.4801 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4565 | 0.4565 | 0.4565 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.5737 | 24.5737 | 24.5737 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.2212 | 2.8945 | 2.8945 | 2.8945 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 49.1971 | 28.1943 | 28.1943 | 28.1943 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.0408 | 2.8773 | 2.8773 | 2.8773 | 0.0000 | 1.0000 |
CAV_BAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.5737 | 24.5737 | 24.5737 | 24.5737 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4710 | 0.4710 | 0.4710 | 0.4710 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.4801 | 4.4801 | 4.4801 | 4.4801 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4565 | 0.4565 | 0.4565 | 0.4565 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:43
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Total gross floor area [m2] | 46320.38 |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 5837.50 |
Number of hours not met | 5837.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 6993.88 | 469909.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3209.76 | 314611.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 343.21 | 40855.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 55.00 | 3448.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 2505.76 | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2432.44 | 195785.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 949.18 | 69572.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 2647.08 | 97598.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 129.80 | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 281.34 | 32218.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 34229.69 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 34229.69 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 69.29 |
Space Heating | 0.00 |
Space Cooling | 150.99 |
Fans (All) | 52.51 |
Service Water Heating | 6.07 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 738.98 |
Subtotal | 738.98 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 9.38 |
Space Heating | 0.00 |
Space Cooling | 20.43 |
Fans (All) | 7.11 |
Service Water Heating | 0.82 |
Receptacle Equipment | 42.88 |
Miscellaneous | 19.39 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:43
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 178.50 | 468.33 | 326.00 | 7766.17 | 21.00 |
CORE_BOTTOM | 8492.17 | 267.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8751.00 | 9.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8749.83 | 10.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8016.83 | 743.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8187.50 | 572.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8003.50 | 756.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7891.67 | 868.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8435.33 | 324.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8312.67 | 447.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8036.17 | 723.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7243.17 | 1516.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8309.17 | 450.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8199.50 | 560.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7963.33 | 796.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7314.83 | 1445.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 14.83 | 8745.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 15.67 | 8744.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 13.50 | 8746.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 1.50 | 8758.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 7867.17 | 892.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8312.83 | 447.17 | 0.00 | 0.00 | 0.00 |
Min | 1.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 8758.50 | 326.00 | 7766.17 | 21.00 |
Average | 6394.38 | 2012.88 | 14.17 | 337.66 | 0.91 |
Sum | 147070.67 | 46296.17 | 326.00 | 7766.17 | 21.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 12534.00 | 7531.67 | 11057.00 | 334518.67 | 2974.67 |
CORE_BOTTOM | 330594.00 | 219.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330803.00 | 10.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330802.00 | 11.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 2268.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 2268.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 2268.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 2.67 | 103392.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 330803.00 | 103392.33 | 11057.00 | 334518.67 | 2974.67 |
Average | 60051.51 | 5129.04 | 480.74 | 14544.29 | 129.33 |
Sum | 1381184.67 | 117968.00 | 11057.00 | 334518.67 | 2974.67 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 161.67 | 540.00 | 219.17 | 2929.00 | 4910.17 |
CORE_BOTTOM | 8404.17 | 355.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8700.17 | 59.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8688.00 | 72.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 7310.67 | 1449.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 7750.33 | 1009.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7280.17 | 1479.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7475.83 | 1284.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 6287.33 | 2472.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 6312.33 | 2447.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 5875.00 | 2885.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 6012.17 | 2747.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 5971.17 | 2788.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 6094.00 | 2666.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 5636.83 | 3123.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 5959.17 | 2800.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 263.17 | 8496.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 257.67 | 8502.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 232.83 | 8527.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 189.00 | 8571.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 6920.17 | 1839.83 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8202.00 | 558.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7280.83 | 1479.17 | 0.00 | 0.00 | 0.00 |
Min | 161.67 | 59.83 | 0.00 | 0.00 | 0.00 |
Max | 8700.17 | 8571.00 | 219.17 | 2929.00 | 4910.17 |
Average | 5533.25 | 2876.39 | 9.53 | 127.35 | 213.49 |
Sum | 127264.67 | 66157.00 | 219.17 | 2929.00 | 4910.17 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 11938.83 | 10439.83 | 8150.50 | 38986.00 | 299100.83 |
CORE_BOTTOM | 330466.00 | 347.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330711.00 | 102.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330719.00 | 94.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38919.67 | 5.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38924.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38924.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 3.67 | 2264.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 3.67 | 2264.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 3.00 | 2265.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 373.33 | 103021.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 330719.00 | 103021.67 | 8150.50 | 38986.00 | 299100.83 |
Average | 60028.76 | 5252.36 | 354.37 | 1695.04 | 13004.38 |
Sum | 1380661.50 | 120804.17 | 8150.50 | 38986.00 | 299100.83 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:43
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:43
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
For: Environment
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
For: Environment
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.180885E+11 | 103797.89 | 17-JAN-06:31 | 20.50 | 19.78 | 0.881929E+10 | 13416.50 | 06-JAN-14:00 | 20.50 | 19.78 |
February | 0.116843E+11 | 89011.77 | 24-FEB-09:00 | 25.00 | 19.01 | 0.820236E+10 | 13477.17 | 17-FEB-14:00 | 25.00 | 19.01 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 | 22.97 | 0.107046E+11 | 13466.42 | 31-MAR-13:00 | 32.00 | 24.80 |
April | 0.137648E+10 | 83648.02 | 14-APR-21:00 | 27.50 | 25.59 | 0.954462E+10 | 13577.11 | 28-APR-13:00 | 34.00 | 26.11 |
May | 0.250147E+09 | 76472.01 | 10-MAY-20:50 | 22.83 | 22.83 | 0.102558E+11 | 13460.68 | 05-MAY-13:00 | 22.83 | 22.83 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 | 23.91 | 0.103479E+11 | 13564.06 | 16-JUN-13:00 | 36.00 | 27.59 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.40 | 24.33 | 0.963535E+10 | 13631.52 | 28-JUL-13:00 | 30.50 | 25.62 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 | 24.75 | 0.108976E+11 | 13674.65 | 11-AUG-13:00 | 33.00 | 28.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 | 25.66 | 0.951405E+10 | 13618.83 | 01-SEP-13:00 | 31.00 | 26.41 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 | 25.35 | 0.986350E+10 | 13469.52 | 06-OCT-13:00 | 29.30 | 26.58 |
November | 0.353832E+10 | 90277.47 | 25-NOV-07:30 | 21.50 | 19.02 | 0.974364E+10 | 13590.66 | 17-NOV-14:00 | 21.50 | 19.02 |
December | 0.172941E+11 | 103452.00 | 21-DEC-00:10 | 21.07 | 18.41 | 0.864197E+10 | 13468.57 | 12-DEC-14:00 | 21.07 | 18.41 |
Annual Sum or Average | 0.522319E+11 | 0.116171E+12 | ||||||||
Minimum of Months | 0.00 | 0.00 | 20.50 | 18.41 | 0.820236E+10 | 13416.50 | 20.50 | 18.41 | ||
Maximum of Months | 0.180885E+11 | 103797.89 | 27.50 | 25.66 | 0.108976E+11 | 13674.65 | 36.00 | 28.40 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.897933E+11 | 97507.56 | 24-JAN-05:13 | 19.20 | 17.44 | 0.508097E+10 | 6758.70 | 04-JAN-14:20 | 19.20 | 17.44 |
February | 0.885593E+11 | 97216.34 | 09-FEB-05:13 | 23.33 | 20.37 | 0.460948E+10 | 6829.77 | 16-FEB-14:39 | 33.00 | 24.27 |
March | 0.111571E+12 | 89585.75 | 27-MAR-05:05 | 26.00 | 24.56 | 0.550663E+10 | 6937.72 | 27-MAR-13:30 | 34.10 | 26.10 |
April | 0.107399E+12 | 95611.90 | 24-APR-04:04 | 25.00 | 24.18 | 0.490724E+10 | 7084.52 | 12-APR-13:39 | 25.00 | 24.18 |
May | 0.103111E+12 | 94479.35 | 01-MAY-04:24 | 28.15 | 26.64 | 0.529628E+10 | 6950.30 | 01-MAY-09:00 | 33.70 | 26.26 |
June | 0.106264E+12 | 89275.80 | 19-JUN-05:03 | 27.00 | 26.21 | 0.527649E+10 | 6840.34 | 12-JUN-09:20 | 27.00 | 26.21 |
July | 0.107232E+12 | 95666.80 | 22-JUL-04:14 | 23.67 | 23.26 | 0.490983E+10 | 7002.71 | 28-JUL-13:30 | 31.75 | 25.96 |
August | 0.114487E+12 | 95358.30 | 28-AUG-04:24 | 25.20 | 24.44 | 0.552604E+10 | 7008.23 | 28-AUG-09:00 | 30.90 | 26.65 |
September | 0.966050E+11 | 93056.17 | 19-SEP-04:13 | 23.27 | 23.19 | 0.489032E+10 | 6849.10 | 07-SEP-13:20 | 23.27 | 23.19 |
October | 0.101447E+12 | 97497.11 | 27-OCT-04:13 | 23.87 | 22.96 | 0.508495E+10 | 6939.38 | 05-OCT-13:50 | 23.87 | 22.96 |
November | 0.102323E+12 | 98627.17 | 25-NOV-05:13 | 20.17 | 18.71 | 0.503547E+10 | 6994.57 | 14-NOV-14:30 | 20.17 | 18.71 |
December | 0.100972E+12 | 98675.82 | 27-DEC-05:13 | 19.00 | 18.34 | 0.490557E+10 | 6942.39 | 11-DEC-14:00 | 19.00 | 18.34 |
Annual Sum or Average | 0.122976E+13 | 0.610293E+11 | ||||||||
Minimum of Months | 0.885593E+11 | 89275.80 | 19.00 | 17.44 | 0.460948E+10 | 6758.70 | 19.00 | 17.44 | ||
Maximum of Months | 0.114487E+12 | 98675.82 | 28.15 | 26.64 | 0.552604E+10 | 7084.52 | 34.10 | 26.65 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.558499E+11 | 84378.88 | 24-JAN-05:12 | 19.20 | 17.44 | 0.505673E+10 | 6734.75 | 04-JAN-10:39 | 19.20 | 17.44 |
February | 0.520614E+11 | 82318.92 | 08-FEB-04:32 | 23.93 | 21.06 | 0.458303E+10 | 6734.81 | 21-FEB-10:09 | 21.92 | 19.78 |
March | 0.609733E+11 | 81929.52 | 03-MAR-04:02 | 23.92 | 21.09 | 0.546464E+10 | 6734.71 | 28-MAR-13:09 | 34.42 | 25.37 |
April | 0.578344E+11 | 71332.40 | 15-APR-05:03 | 25.50 | 24.34 | 0.483851E+10 | 6735.00 | 25-APR-13:50 | 32.65 | 26.63 |
May | 0.594776E+11 | 81536.13 | 26-MAY-04:03 | 24.00 | 23.90 | 0.525211E+10 | 6735.05 | 23-MAY-09:09 | 24.00 | 23.90 |
June | 0.596585E+11 | 78758.82 | 01-JUN-03:22 | 24.00 | 23.88 | 0.524067E+10 | 6734.76 | 27-JUN-09:30 | 30.15 | 27.08 |
July | 0.560991E+11 | 80425.19 | 07-JUL-03:02 | 24.12 | 23.50 | 0.486694E+10 | 6735.04 | 28-JUL-13:30 | 31.75 | 25.96 |
August | 0.583528E+11 | 82685.09 | 21-AUG-03:02 | 24.03 | 23.95 | 0.546897E+10 | 6734.87 | 16-AUG-09:20 | 24.03 | 23.95 |
September | 0.545385E+11 | 82159.08 | 16-SEP-04:12 | 23.67 | 23.18 | 0.484882E+10 | 6734.99 | 07-SEP-13:20 | 23.67 | 23.18 |
October | 0.548472E+11 | 82886.17 | 23-OCT-05:04 | 22.58 | 22.58 | 0.504757E+10 | 6734.98 | 05-OCT-13:50 | 22.58 | 22.58 |
November | 0.541154E+11 | 82180.90 | 27-NOV-05:12 | 22.00 | 20.81 | 0.500561E+10 | 6735.02 | 14-NOV-14:30 | 22.00 | 20.81 |
December | 0.542929E+11 | 83951.60 | 15-DEC-05:12 | 19.67 | 18.54 | 0.487616E+10 | 6734.76 | 28-DEC-14:20 | 31.33 | 22.91 |
Annual Sum or Average | 0.678101E+12 | 0.605498E+11 | ||||||||
Minimum of Months | 0.520614E+11 | 71332.40 | 19.20 | 17.44 | 0.458303E+10 | 6734.71 | 19.20 | 17.44 | ||
Maximum of Months | 0.609733E+11 | 84378.88 | 25.50 | 24.34 | 0.546897E+10 | 6735.05 | 34.42 | 27.08 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.583260E+11 | 82690.84 | 24-JAN-05:12 | 19.20 | 17.44 | 0.505427E+10 | 6734.78 | 27-JAN-14:20 | 31.67 | 23.76 |
February | 0.551036E+11 | 83664.03 | 03-FEB-05:13 | 21.73 | 20.79 | 0.458372E+10 | 6734.80 | 21-FEB-10:09 | 21.92 | 19.78 |
March | 0.656736E+11 | 80063.58 | 02-MAR-05:12 | 23.00 | 22.27 | 0.546949E+10 | 6734.71 | 30-MAR-13:09 | 33.33 | 24.10 |
April | 0.631320E+11 | 78795.47 | 14-APR-03:02 | 26.40 | 24.56 | 0.484764E+10 | 6745.34 | 12-APR-13:39 | 26.40 | 24.56 |
May | 0.647298E+11 | 82613.43 | 17-MAY-03:02 | 24.07 | 24.05 | 0.526240E+10 | 6735.05 | 23-MAY-09:09 | 29.17 | 28.13 |
June | 0.650185E+11 | 80881.47 | 22-JUN-03:02 | 26.03 | 25.97 | 0.524787E+10 | 6734.78 | 27-JUN-09:30 | 30.15 | 27.08 |
July | 0.602384E+11 | 82532.67 | 07-JUL-03:02 | 24.12 | 23.50 | 0.487159E+10 | 6735.13 | 03-JUL-13:09 | 24.12 | 23.50 |
August | 0.623190E+11 | 82992.67 | 21-AUG-03:02 | 24.03 | 23.95 | 0.547149E+10 | 6734.87 | 23-AUG-09:30 | 29.65 | 27.06 |
September | 0.588773E+11 | 81968.88 | 29-SEP-03:02 | 24.00 | 23.30 | 0.485479E+10 | 6735.05 | 07-SEP-13:20 | 24.00 | 23.30 |
October | 0.580925E+11 | 83158.53 | 18-OCT-03:02 | 24.55 | 24.13 | 0.504861E+10 | 6735.09 | 05-OCT-13:50 | 24.55 | 24.13 |
November | 0.569948E+11 | 83442.51 | 27-NOV-05:12 | 22.00 | 20.81 | 0.500589E+10 | 6735.07 | 14-NOV-14:30 | 22.00 | 20.81 |
December | 0.563885E+11 | 82237.63 | 27-DEC-05:12 | 19.00 | 18.34 | 0.487257E+10 | 6734.73 | 28-DEC-14:20 | 31.33 | 22.91 |
Annual Sum or Average | 0.724894E+12 | 0.605903E+11 | ||||||||
Minimum of Months | 0.551036E+11 | 78795.47 | 19.00 | 17.44 | 0.458372E+10 | 6734.71 | 21.92 | 19.78 | ||
Maximum of Months | 0.656736E+11 | 83664.03 | 26.40 | 25.97 | 0.547149E+10 | 6745.34 | 33.33 | 28.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139678E+11 | 18264.80 | 08-JAN-15:12 | 32.30 | 23.02 | 0.638770E+09 | 853.01 | 04-JAN-14:20 | 32.30 | 23.02 |
February | 0.141938E+11 | 18650.84 | 26-FEB-15:01 | 34.85 | 24.53 | 0.579834E+09 | 866.39 | 16-FEB-14:39 | 34.85 | 24.53 |
March | 0.181559E+11 | 18336.93 | 19-MAR-15:01 | 34.95 | 24.52 | 0.692863E+09 | 892.12 | 27-MAR-13:30 | 34.10 | 26.10 |
April | 0.182320E+11 | 18665.94 | 09-APR-10:22 | 33.05 | 26.18 | 0.618914E+09 | 915.47 | 12-APR-13:39 | 33.43 | 25.24 |
May | 0.192131E+11 | 19803.24 | 29-MAY-15:31 | 34.40 | 27.57 | 0.668714E+09 | 911.28 | 01-MAY-09:00 | 34.40 | 27.57 |
June | 0.209888E+11 | 20265.73 | 18-JUN-15:41 | 34.00 | 28.01 | 0.669541E+09 | 903.85 | 12-JUN-09:20 | 34.00 | 28.01 |
July | 0.189518E+11 | 19179.67 | 09-JUL-14:22 | 31.75 | 25.32 | 0.621305E+09 | 927.59 | 28-JUL-13:30 | 31.75 | 25.96 |
August | 0.190984E+11 | 18911.45 | 13-AUG-11:02 | 33.00 | 28.40 | 0.695297E+09 | 894.65 | 28-AUG-13:30 | 32.75 | 27.29 |
September | 0.158544E+11 | 18825.13 | 04-SEP-15:12 | 32.33 | 27.27 | 0.615229E+09 | 883.69 | 07-SEP-13:20 | 31.87 | 26.91 |
October | 0.157197E+11 | 18589.15 | 29-OCT-13:42 | 30.73 | 25.71 | 0.639513E+09 | 879.75 | 05-OCT-13:50 | 30.73 | 25.71 |
November | 0.157336E+11 | 18530.82 | 05-NOV-13:52 | 31.00 | 24.13 | 0.633109E+09 | 886.20 | 14-NOV-14:30 | 31.00 | 26.07 |
December | 0.151942E+11 | 18168.34 | 24-DEC-13:52 | 32.00 | 24.04 | 0.616565E+09 | 866.36 | 11-DEC-14:09 | 32.00 | 24.04 |
Annual Sum or Average | 0.205303E+12 | 0.768966E+10 | ||||||||
Minimum of Months | 0.139678E+11 | 18168.34 | 30.73 | 23.02 | 0.579834E+09 | 853.01 | 30.73 | 23.02 | ||
Maximum of Months | 0.209888E+11 | 20265.73 | 34.95 | 28.40 | 0.695297E+09 | 927.59 | 34.85 | 28.01 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113179E+11 | 17743.42 | 16-JAN-08:43 | 24.25 | 20.54 | 0.411836E+09 | 547.67 | 04-JAN-14:20 | 24.25 | 20.54 |
February | 0.115745E+11 | 17751.08 | 20-FEB-09:22 | 28.70 | 23.27 | 0.373719E+09 | 548.65 | 10-FEB-14:00 | 28.70 | 23.27 |
March | 0.146182E+11 | 18047.25 | 19-MAR-09:02 | 30.78 | 22.93 | 0.446136E+09 | 554.48 | 27-MAR-09:00 | 31.30 | 25.30 |
April | 0.142439E+11 | 19005.32 | 09-APR-10:22 | 33.05 | 26.18 | 0.397276E+09 | 571.91 | 28-APR-09:50 | 31.42 | 25.07 |
May | 0.138090E+11 | 19248.01 | 28-MAY-09:42 | 32.17 | 27.73 | 0.429690E+09 | 580.52 | 01-MAY-09:50 | 32.17 | 27.73 |
June | 0.142615E+11 | 19121.57 | 18-JUN-09:42 | 32.25 | 27.69 | 0.427684E+09 | 561.92 | 12-JUN-09:20 | 32.25 | 27.69 |
July | 0.128554E+11 | 17591.90 | 09-JUL-14:22 | 31.75 | 25.32 | 0.397640E+09 | 558.92 | 27-JUL-13:50 | 31.90 | 25.37 |
August | 0.137716E+11 | 18488.75 | 27-AUG-08:22 | 30.00 | 28.07 | 0.446251E+09 | 575.78 | 28-AUG-09:20 | 30.97 | 27.04 |
September | 0.123904E+11 | 18449.64 | 10-SEP-10:32 | 31.20 | 26.31 | 0.396439E+09 | 557.56 | 05-SEP-09:20 | 31.20 | 26.31 |
October | 0.119390E+11 | 17818.88 | 08-OCT-12:32 | 31.87 | 26.74 | 0.412046E+09 | 557.54 | 05-OCT-13:50 | 31.87 | 26.74 |
November | 0.118408E+11 | 17626.47 | 11-NOV-07:33 | 25.97 | 24.39 | 0.407758E+09 | 555.80 | 14-NOV-14:30 | 31.00 | 26.07 |
December | 0.115048E+11 | 17543.43 | 10-DEC-09:32 | 28.80 | 24.83 | 0.397114E+09 | 546.51 | 08-DEC-14:00 | 28.80 | 24.83 |
Annual Sum or Average | 0.154127E+12 | 0.494359E+10 | ||||||||
Minimum of Months | 0.113179E+11 | 17543.43 | 24.25 | 20.54 | 0.373719E+09 | 546.51 | 24.25 | 20.54 | ||
Maximum of Months | 0.146182E+11 | 19248.01 | 33.05 | 28.07 | 0.446251E+09 | 580.52 | 32.25 | 27.73 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.187874E+11 | 19698.49 | 08-JAN-14:32 | 32.57 | 22.89 | 0.657103E+09 | 1020.42 | 04-JAN-14:20 | 32.57 | 22.89 |
February | 0.176274E+11 | 19461.69 | 26-FEB-15:01 | 34.85 | 24.53 | 0.596583E+09 | 964.29 | 16-FEB-14:39 | 34.85 | 24.53 |
March | 0.195380E+11 | 18158.55 | 05-MAR-11:53 | 31.00 | 23.21 | 0.698893E+09 | 938.41 | 27-MAR-13:30 | 34.10 | 26.10 |
April | 0.172962E+11 | 17848.73 | 09-APR-11:42 | 33.68 | 25.91 | 0.618511E+09 | 916.19 | 12-APR-13:39 | 33.43 | 25.24 |
May | 0.169583E+11 | 18419.11 | 29-MAY-15:31 | 34.40 | 27.57 | 0.666445E+09 | 880.04 | 01-MAY-09:00 | 34.40 | 27.57 |
June | 0.173675E+11 | 18459.19 | 18-JUN-14:21 | 34.50 | 27.04 | 0.663403E+09 | 858.07 | 22-JUN-13:00 | 32.00 | 26.09 |
July | 0.165498E+11 | 18036.15 | 09-JUL-14:22 | 31.75 | 25.32 | 0.617816E+09 | 901.41 | 28-JUL-13:30 | 31.75 | 25.96 |
August | 0.175852E+11 | 17839.59 | 13-AUG-11:02 | 33.00 | 28.40 | 0.693725E+09 | 884.95 | 28-AUG-13:30 | 32.75 | 27.29 |
September | 0.158624E+11 | 18203.18 | 04-SEP-15:12 | 32.33 | 27.27 | 0.615455E+09 | 891.31 | 07-SEP-13:20 | 31.87 | 26.91 |
October | 0.172239E+11 | 19115.19 | 29-OCT-11:42 | 31.50 | 26.00 | 0.641315E+09 | 935.43 | 05-OCT-13:50 | 31.50 | 26.00 |
November | 0.187695E+11 | 19037.84 | 05-NOV-13:52 | 31.00 | 24.13 | 0.648001E+09 | 957.81 | 22-NOV-14:20 | 31.50 | 24.56 |
December | 0.198480E+11 | 19689.35 | 24-DEC-13:52 | 32.00 | 24.04 | 0.639962E+09 | 1006.05 | 08-DEC-14:50 | 32.00 | 24.04 |
Annual Sum or Average | 0.213414E+12 | 0.775721E+10 | ||||||||
Minimum of Months | 0.158624E+11 | 17839.59 | 31.00 | 22.89 | 0.596583E+09 | 858.07 | 31.50 | 22.89 | ||
Maximum of Months | 0.198480E+11 | 19698.49 | 34.85 | 28.40 | 0.698893E+09 | 1020.42 | 34.85 | 27.57 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122807E+11 | 24677.47 | 29-JAN-16:02 | 32.08 | 23.28 | 0.411557E+09 | 548.08 | 04-JAN-14:20 | 32.08 | 23.28 |
February | 0.132862E+11 | 25773.29 | 26-FEB-15:01 | 34.85 | 24.53 | 0.373681E+09 | 549.83 | 16-FEB-14:39 | 34.85 | 24.53 |
March | 0.174617E+11 | 24813.17 | 19-MAR-15:01 | 34.95 | 24.52 | 0.446323E+09 | 553.59 | 09-MAR-14:20 | 34.95 | 24.52 |
April | 0.179175E+11 | 25104.87 | 02-APR-15:41 | 33.75 | 27.23 | 0.397346E+09 | 566.83 | 12-APR-13:39 | 33.43 | 25.24 |
May | 0.141121E+11 | 25327.07 | 29-MAY-15:31 | 34.40 | 27.57 | 0.428834E+09 | 553.13 | 30-MAY-09:50 | 33.00 | 27.79 |
June | 0.155340E+11 | 26192.75 | 18-JUN-15:41 | 34.00 | 28.01 | 0.427477E+09 | 548.66 | 27-JUN-09:30 | 30.15 | 27.08 |
July | 0.153514E+11 | 24699.31 | 04-JUL-16:01 | 31.17 | 25.29 | 0.397744E+09 | 560.35 | 27-JUL-13:50 | 31.90 | 25.37 |
August | 0.172537E+11 | 24950.28 | 27-AUG-15:41 | 32.83 | 25.58 | 0.446486E+09 | 559.04 | 29-AUG-13:39 | 24.97 | 23.78 |
September | 0.126171E+11 | 25377.28 | 04-SEP-15:51 | 33.00 | 26.79 | 0.395836E+09 | 556.36 | 07-SEP-13:20 | 31.87 | 26.91 |
October | 0.133835E+11 | 23591.66 | 29-OCT-15:02 | 29.17 | 25.76 | 0.411887E+09 | 559.85 | 05-OCT-13:50 | 29.17 | 25.76 |
November | 0.143251E+11 | 23555.05 | 05-NOV-13:52 | 31.00 | 24.13 | 0.407962E+09 | 557.97 | 14-NOV-14:30 | 31.00 | 26.07 |
December | 0.156448E+11 | 24568.73 | 24-DEC-13:52 | 32.00 | 24.04 | 0.397739E+09 | 547.15 | 08-DEC-14:00 | 32.00 | 24.04 |
Annual Sum or Average | 0.179168E+12 | 0.494287E+10 | ||||||||
Minimum of Months | 0.122807E+11 | 23555.05 | 29.17 | 23.28 | 0.373681E+09 | 547.15 | 24.97 | 23.28 | ||
Maximum of Months | 0.179175E+11 | 26192.75 | 34.95 | 28.01 | 0.446486E+09 | 566.83 | 34.95 | 27.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.966812E+10 | 13432.98 | 03-JAN-04:02 | 25.75 | 22.56 | 0.637348E+09 | 845.63 | 27-JAN-14:20 | 31.67 | 23.76 |
February | 0.953350E+10 | 17180.65 | 26-FEB-15:11 | 34.70 | 24.67 | 0.578742E+09 | 845.63 | 21-FEB-10:09 | 34.70 | 24.67 |
March | 0.117331E+11 | 13743.57 | 13-MAR-05:03 | 25.00 | 23.59 | 0.690805E+09 | 845.61 | 30-MAR-13:09 | 33.33 | 24.10 |
April | 0.118537E+11 | 16886.69 | 02-APR-15:31 | 34.00 | 27.22 | 0.613667E+09 | 845.70 | 25-APR-13:50 | 32.65 | 26.63 |
May | 0.137414E+11 | 18225.25 | 14-MAY-15:01 | 34.97 | 26.90 | 0.665569E+09 | 845.68 | 23-MAY-09:09 | 29.17 | 28.13 |
June | 0.152682E+11 | 18481.04 | 11-JUN-17:11 | 32.50 | 27.60 | 0.663589E+09 | 846.86 | 16-JUN-13:00 | 36.00 | 27.59 |
July | 0.123314E+11 | 17456.97 | 04-JUL-16:12 | 30.83 | 25.29 | 0.616842E+09 | 850.69 | 28-JUL-13:30 | 31.75 | 25.96 |
August | 0.118667E+11 | 15700.72 | 15-AUG-03:02 | 26.87 | 26.08 | 0.691246E+09 | 845.66 | 16-AUG-09:20 | 29.87 | 27.42 |
September | 0.104852E+11 | 17035.49 | 10-SEP-15:01 | 31.33 | 26.68 | 0.613547E+09 | 845.69 | 07-SEP-13:20 | 31.33 | 26.68 |
October | 0.974223E+10 | 14640.26 | 10-OCT-03:02 | 24.00 | 23.32 | 0.637955E+09 | 845.69 | 05-OCT-13:50 | 24.00 | 23.32 |
November | 0.955577E+10 | 13445.79 | 13-NOV-04:02 | 25.00 | 24.13 | 0.631690E+09 | 845.69 | 14-NOV-14:30 | 31.00 | 26.07 |
December | 0.906842E+10 | 13362.56 | 12-DEC-05:12 | 23.00 | 23.00 | 0.614792E+09 | 845.62 | 28-DEC-14:20 | 31.33 | 22.91 |
Annual Sum or Average | 0.134848E+12 | 0.765579E+10 | ||||||||
Minimum of Months | 0.906842E+10 | 13362.56 | 23.00 | 22.56 | 0.578742E+09 | 845.61 | 24.00 | 22.91 | ||
Maximum of Months | 0.152682E+11 | 18481.04 | 34.97 | 27.60 | 0.691246E+09 | 850.69 | 36.00 | 28.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.847274E+10 | 13360.93 | 02-JAN-05:12 | 23.27 | 23.03 | 0.303247E+09 | 521.22 | 18-JAN-15:09 | 31.97 | 23.69 |
February | 0.864557E+10 | 17914.36 | 26-FEB-15:11 | 34.70 | 24.67 | 0.275158E+09 | 521.24 | 14-FEB-13:00 | 34.70 | 24.67 |
March | 0.106888E+11 | 18404.77 | 05-MAR-11:02 | 31.00 | 23.21 | 0.327477E+09 | 521.21 | 17-MAR-10:09 | 32.17 | 24.73 |
April | 0.105040E+11 | 18777.45 | 16-APR-10:02 | 30.92 | 25.80 | 0.291578E+09 | 521.25 | 10-APR-14:39 | 30.92 | 25.80 |
May | 0.101470E+11 | 19344.00 | 14-MAY-09:42 | 32.00 | 26.15 | 0.315500E+09 | 521.25 | 16-MAY-10:09 | 28.17 | 26.66 |
June | 0.105460E+11 | 18868.73 | 11-JUN-09:12 | 31.70 | 28.10 | 0.314129E+09 | 521.21 | 07-JUN-08:39 | 31.70 | 28.10 |
July | 0.871835E+10 | 13339.77 | 20-JUL-04:12 | 23.87 | 22.70 | 0.292821E+09 | 521.21 | 26-JUL-14:09 | 32.55 | 26.09 |
August | 0.941581E+10 | 18157.16 | 13-AUG-08:32 | 30.33 | 27.76 | 0.327267E+09 | 521.23 | 10-AUG-08:50 | 30.33 | 27.76 |
September | 0.875724E+10 | 18705.21 | 10-SEP-10:22 | 31.30 | 26.26 | 0.291377E+09 | 521.24 | 27-SEP-10:09 | 31.08 | 26.52 |
October | 0.807780E+10 | 18756.36 | 08-OCT-09:22 | 30.00 | 26.31 | 0.302861E+09 | 521.24 | 17-OCT-15:30 | 30.70 | 26.95 |
November | 0.794942E+10 | 17481.26 | 23-NOV-09:13 | 28.63 | 23.89 | 0.300188E+09 | 521.20 | 06-NOV-13:20 | 28.63 | 23.89 |
December | 0.784998E+10 | 17441.16 | 31-DEC-09:53 | 30.80 | 24.86 | 0.292612E+09 | 521.21 | 29-DEC-13:20 | 30.80 | 24.86 |
Annual Sum or Average | 0.109773E+12 | 0.363422E+10 | ||||||||
Minimum of Months | 0.784998E+10 | 13339.77 | 23.27 | 22.70 | 0.275158E+09 | 521.20 | 28.17 | 23.69 | ||
Maximum of Months | 0.106888E+11 | 19344.00 | 34.70 | 28.10 | 0.327477E+09 | 521.25 | 34.70 | 28.10 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.154231E+11 | 18579.70 | 08-JAN-14:42 | 32.58 | 22.90 | 0.651602E+09 | 961.26 | 04-JAN-14:20 | 32.58 | 22.90 |
February | 0.138724E+11 | 18296.37 | 26-FEB-15:11 | 34.70 | 24.67 | 0.586519E+09 | 911.17 | 21-FEB-14:30 | 34.70 | 24.67 |
March | 0.138894E+11 | 16990.38 | 05-MAR-16:21 | 29.10 | 23.70 | 0.691543E+09 | 845.63 | 09-MAR-14:20 | 34.67 | 24.78 |
April | 0.116150E+11 | 16318.39 | 02-APR-15:31 | 34.00 | 27.22 | 0.613548E+09 | 845.71 | 25-APR-13:50 | 32.65 | 26.63 |
May | 0.120917E+11 | 16707.42 | 14-MAY-15:01 | 34.97 | 26.90 | 0.664810E+09 | 845.70 | 23-MAY-09:09 | 29.17 | 28.13 |
June | 0.120908E+11 | 16417.52 | 11-JUN-17:11 | 32.50 | 27.60 | 0.662602E+09 | 845.66 | 30-JUN-09:50 | 30.67 | 27.95 |
July | 0.105649E+11 | 15134.20 | 24-JUL-03:02 | 25.97 | 24.50 | 0.616051E+09 | 845.71 | 28-JUL-13:30 | 31.75 | 25.96 |
August | 0.110307E+11 | 13541.04 | 11-AUG-03:02 | 26.05 | 25.94 | 0.690874E+09 | 845.67 | 22-AUG-09:50 | 30.58 | 27.22 |
September | 0.110658E+11 | 16759.22 | 10-SEP-15:01 | 31.33 | 26.68 | 0.613778E+09 | 845.72 | 07-SEP-13:20 | 31.33 | 26.68 |
October | 0.118718E+11 | 18018.08 | 29-OCT-12:32 | 31.77 | 26.12 | 0.639022E+09 | 859.33 | 05-OCT-13:50 | 31.77 | 26.12 |
November | 0.135840E+11 | 17922.36 | 05-NOV-11:42 | 30.92 | 22.88 | 0.635835E+09 | 889.68 | 29-NOV-14:20 | 30.07 | 24.78 |
December | 0.148122E+11 | 17656.94 | 31-DEC-13:12 | 32.00 | 24.68 | 0.629759E+09 | 957.39 | 07-DEC-14:20 | 32.00 | 24.68 |
Annual Sum or Average | 0.151912E+12 | 0.769594E+10 | ||||||||
Minimum of Months | 0.105649E+11 | 13541.04 | 25.97 | 22.88 | 0.586519E+09 | 845.63 | 29.17 | 22.90 | ||
Maximum of Months | 0.154231E+11 | 18579.70 | 34.97 | 27.60 | 0.691543E+09 | 961.26 | 34.70 | 28.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.906603E+10 | 21272.88 | 08-JAN-15:22 | 32.15 | 23.07 | 0.411032E+09 | 544.96 | 27-JAN-14:20 | 31.67 | 23.76 |
February | 0.921048E+10 | 22322.95 | 26-FEB-15:51 | 34.10 | 25.18 | 0.373318E+09 | 544.96 | 17-FEB-14:39 | 34.10 | 25.18 |
March | 0.116468E+11 | 21988.82 | 05-MAR-16:21 | 29.10 | 23.70 | 0.445798E+09 | 544.95 | 09-MAR-14:20 | 34.67 | 24.78 |
April | 0.113902E+11 | 21613.83 | 02-APR-16:11 | 33.00 | 27.09 | 0.395926E+09 | 545.02 | 25-APR-13:50 | 32.65 | 26.63 |
May | 0.106566E+11 | 22086.11 | 14-MAY-15:01 | 34.97 | 26.90 | 0.428462E+09 | 544.99 | 23-MAY-09:09 | 29.17 | 28.13 |
June | 0.110442E+11 | 22221.54 | 11-JUN-17:11 | 32.50 | 27.60 | 0.427300E+09 | 544.97 | 30-JUN-09:50 | 30.67 | 27.95 |
July | 0.934723E+10 | 20891.98 | 04-JUL-16:12 | 30.83 | 25.29 | 0.397111E+09 | 545.01 | 28-JUL-13:30 | 31.75 | 25.96 |
August | 0.100562E+11 | 20824.94 | 27-AUG-16:02 | 32.83 | 25.70 | 0.445425E+09 | 544.98 | 16-AUG-09:20 | 32.83 | 25.70 |
September | 0.918589E+10 | 22063.17 | 10-SEP-15:01 | 31.33 | 26.68 | 0.395324E+09 | 545.00 | 07-SEP-13:20 | 31.33 | 26.68 |
October | 0.868249E+10 | 20614.23 | 29-OCT-15:52 | 30.00 | 26.14 | 0.410869E+09 | 545.01 | 05-OCT-13:50 | 30.00 | 26.14 |
November | 0.860637E+10 | 20736.31 | 19-NOV-16:52 | 29.50 | 25.36 | 0.407259E+09 | 545.01 | 14-NOV-14:30 | 29.50 | 25.36 |
December | 0.862753E+10 | 20389.10 | 25-DEC-15:52 | 31.00 | 22.24 | 0.396588E+09 | 544.95 | 21-DEC-14:30 | 31.00 | 22.24 |
Annual Sum or Average | 0.117520E+12 | 0.493441E+10 | ||||||||
Minimum of Months | 0.860637E+10 | 20389.10 | 29.10 | 22.24 | 0.373318E+09 | 544.95 | 29.17 | 22.24 | ||
Maximum of Months | 0.116468E+11 | 22322.95 | 34.97 | 27.60 | 0.445798E+09 | 545.02 | 34.67 | 28.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.996316E+10 | 14883.55 | 27-JAN-05:12 | 23.00 | 22.27 | 0.637007E+09 | 845.64 | 27-JAN-14:20 | 31.67 | 23.76 |
February | 0.992733E+10 | 17587.01 | 26-FEB-15:22 | 34.55 | 24.80 | 0.578730E+09 | 845.65 | 17-FEB-14:39 | 34.55 | 24.80 |
March | 0.123779E+11 | 18864.03 | 26-MAR-15:41 | 33.50 | 25.39 | 0.690923E+09 | 845.64 | 08-MAR-14:00 | 33.50 | 25.39 |
April | 0.126098E+11 | 19231.97 | 02-APR-15:31 | 34.00 | 27.22 | 0.613919E+09 | 856.88 | 12-APR-13:39 | 33.43 | 25.24 |
May | 0.145243E+11 | 20645.01 | 14-MAY-15:01 | 34.97 | 26.90 | 0.665597E+09 | 845.68 | 23-MAY-09:09 | 29.17 | 28.13 |
June | 0.160282E+11 | 20091.62 | 04-JUN-14:12 | 33.33 | 27.76 | 0.663531E+09 | 845.66 | 30-JUN-09:50 | 30.67 | 27.95 |
July | 0.128943E+11 | 19306.82 | 04-JUL-16:12 | 30.83 | 25.29 | 0.616924E+09 | 854.46 | 28-JUL-13:30 | 31.75 | 25.96 |
August | 0.123914E+11 | 19884.33 | 27-AUG-15:11 | 32.33 | 25.90 | 0.691158E+09 | 845.66 | 22-AUG-09:50 | 32.33 | 25.90 |
September | 0.110777E+11 | 19558.47 | 04-SEP-15:51 | 33.00 | 26.79 | 0.613632E+09 | 845.71 | 07-SEP-13:20 | 31.87 | 26.91 |
October | 0.101629E+11 | 18728.50 | 08-OCT-14:12 | 32.17 | 26.12 | 0.637718E+09 | 845.70 | 05-OCT-13:50 | 32.17 | 26.12 |
November | 0.989743E+10 | 15099.84 | 05-NOV-13:42 | 30.92 | 23.94 | 0.631635E+09 | 845.70 | 14-NOV-14:30 | 31.00 | 26.07 |
December | 0.932173E+10 | 14722.52 | 26-DEC-05:12 | 22.00 | 21.77 | 0.614277E+09 | 845.63 | 21-DEC-14:30 | 22.00 | 21.77 |
Annual Sum or Average | 0.141176E+12 | 0.765505E+10 | ||||||||
Minimum of Months | 0.932173E+10 | 14722.52 | 22.00 | 21.77 | 0.578730E+09 | 845.63 | 22.00 | 21.77 | ||
Maximum of Months | 0.160282E+11 | 20645.01 | 34.97 | 27.76 | 0.691158E+09 | 856.88 | 34.55 | 28.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.875238E+10 | 13648.97 | 02-JAN-05:12 | 23.27 | 23.03 | 0.411439E+09 | 544.97 | 27-JAN-14:20 | 31.67 | 23.76 |
February | 0.898738E+10 | 15978.21 | 20-FEB-10:02 | 29.58 | 22.93 | 0.373502E+09 | 544.97 | 17-FEB-14:39 | 29.58 | 22.93 |
March | 0.112237E+11 | 18728.33 | 05-MAR-11:02 | 31.00 | 23.21 | 0.445596E+09 | 544.97 | 08-MAR-14:00 | 33.00 | 25.07 |
April | 0.111147E+11 | 19644.62 | 30-APR-10:12 | 32.37 | 27.01 | 0.395922E+09 | 546.38 | 12-APR-13:39 | 32.37 | 27.01 |
May | 0.107829E+11 | 19669.25 | 14-MAY-09:42 | 32.00 | 26.15 | 0.428635E+09 | 545.00 | 23-MAY-09:09 | 29.17 | 28.13 |
June | 0.111558E+11 | 19156.78 | 18-JUN-10:32 | 32.83 | 27.25 | 0.427313E+09 | 544.99 | 30-JUN-09:50 | 30.67 | 27.95 |
July | 0.919870E+10 | 14282.04 | 30-JUL-14:22 | 31.40 | 25.29 | 0.397129E+09 | 545.02 | 28-JUL-13:30 | 31.40 | 25.29 |
August | 0.989775E+10 | 19275.40 | 27-AUG-09:52 | 31.30 | 26.68 | 0.445306E+09 | 545.00 | 22-AUG-09:50 | 31.30 | 26.68 |
September | 0.928612E+10 | 18998.47 | 10-SEP-10:22 | 31.30 | 26.26 | 0.395625E+09 | 545.01 | 07-SEP-13:20 | 31.30 | 26.26 |
October | 0.847350E+10 | 18192.63 | 08-OCT-10:53 | 31.00 | 26.41 | 0.410919E+09 | 545.01 | 05-OCT-13:50 | 31.00 | 26.41 |
November | 0.828399E+10 | 18093.11 | 05-NOV-11:02 | 30.58 | 23.10 | 0.407343E+09 | 545.01 | 14-NOV-14:30 | 31.00 | 26.07 |
December | 0.810564E+10 | 17675.42 | 31-DEC-09:53 | 30.80 | 24.86 | 0.396801E+09 | 544.96 | 21-DEC-14:30 | 30.80 | 24.86 |
Annual Sum or Average | 0.115263E+12 | 0.493553E+10 | ||||||||
Minimum of Months | 0.810564E+10 | 13648.97 | 23.27 | 22.93 | 0.373502E+09 | 544.96 | 29.17 | 22.93 | ||
Maximum of Months | 0.112237E+11 | 19669.25 | 32.83 | 27.25 | 0.445596E+09 | 546.38 | 33.00 | 28.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.158085E+11 | 20007.16 | 22-JAN-16:12 | 29.40 | 21.99 | 0.646271E+09 | 952.76 | 04-JAN-14:20 | 29.40 | 21.99 |
February | 0.143089E+11 | 19438.95 | 26-FEB-12:02 | 32.42 | 24.78 | 0.583822E+09 | 897.68 | 24-FEB-14:00 | 32.42 | 24.78 |
March | 0.145356E+11 | 19041.21 | 05-MAR-16:21 | 29.10 | 23.70 | 0.691596E+09 | 848.13 | 09-MAR-14:20 | 34.67 | 24.78 |
April | 0.123670E+11 | 18618.74 | 02-APR-15:31 | 34.00 | 27.22 | 0.613793E+09 | 860.44 | 12-APR-13:39 | 33.43 | 25.24 |
May | 0.128488E+11 | 19185.01 | 14-MAY-15:01 | 34.97 | 26.90 | 0.664909E+09 | 845.69 | 23-MAY-09:09 | 29.17 | 28.13 |
June | 0.128193E+11 | 18550.12 | 04-JUN-14:12 | 33.33 | 27.76 | 0.662761E+09 | 845.67 | 30-JUN-09:50 | 30.67 | 27.95 |
July | 0.111084E+11 | 15887.70 | 24-JUL-03:02 | 25.97 | 24.50 | 0.616148E+09 | 845.72 | 28-JUL-13:30 | 31.75 | 25.96 |
August | 0.115508E+11 | 18934.18 | 27-AUG-15:11 | 32.33 | 25.90 | 0.690753E+09 | 845.67 | 22-AUG-09:50 | 32.33 | 25.90 |
September | 0.116632E+11 | 19140.73 | 10-SEP-15:01 | 31.33 | 26.68 | 0.613828E+09 | 845.73 | 07-SEP-13:20 | 31.33 | 26.68 |
October | 0.122997E+11 | 20053.35 | 29-OCT-12:42 | 31.83 | 26.15 | 0.638790E+09 | 863.38 | 05-OCT-13:50 | 31.83 | 26.15 |
November | 0.139694E+11 | 19934.90 | 05-NOV-11:42 | 30.92 | 22.88 | 0.634211E+09 | 873.61 | 22-NOV-14:09 | 31.50 | 24.56 |
December | 0.151600E+11 | 19617.63 | 31-DEC-13:12 | 32.00 | 24.68 | 0.624378E+09 | 933.56 | 07-DEC-14:20 | 32.00 | 24.68 |
Annual Sum or Average | 0.158440E+12 | 0.768126E+10 | ||||||||
Minimum of Months | 0.111084E+11 | 15887.70 | 25.97 | 21.99 | 0.583822E+09 | 845.67 | 29.17 | 21.99 | ||
Maximum of Months | 0.158085E+11 | 20053.35 | 34.97 | 27.76 | 0.691596E+09 | 952.76 | 34.67 | 28.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.931029E+10 | 21982.99 | 22-JAN-16:12 | 29.40 | 21.99 | 0.410118E+09 | 544.97 | 27-JAN-14:20 | 31.67 | 23.76 |
February | 0.949944E+10 | 21851.37 | 26-FEB-15:22 | 34.55 | 24.80 | 0.372920E+09 | 544.98 | 17-FEB-14:39 | 34.55 | 24.80 |
March | 0.121078E+11 | 23385.27 | 05-MAR-16:21 | 29.10 | 23.70 | 0.445516E+09 | 544.98 | 08-MAR-14:00 | 33.00 | 25.07 |
April | 0.119432E+11 | 23196.40 | 02-APR-15:31 | 34.00 | 27.22 | 0.395818E+09 | 546.52 | 12-APR-13:39 | 33.43 | 25.24 |
May | 0.112004E+11 | 23815.70 | 14-MAY-15:01 | 34.97 | 26.90 | 0.428107E+09 | 544.99 | 23-MAY-09:09 | 29.17 | 28.13 |
June | 0.115618E+11 | 22076.63 | 11-JUN-16:02 | 34.25 | 28.05 | 0.427079E+09 | 544.97 | 30-JUN-09:50 | 30.67 | 27.95 |
July | 0.976957E+10 | 22094.83 | 04-JUL-16:12 | 30.83 | 25.29 | 0.396630E+09 | 545.01 | 28-JUL-13:30 | 31.75 | 25.96 |
August | 0.104305E+11 | 23795.37 | 27-AUG-15:11 | 32.33 | 25.90 | 0.444943E+09 | 544.98 | 22-AUG-09:50 | 32.33 | 25.90 |
September | 0.964606E+10 | 23821.07 | 04-SEP-15:51 | 33.00 | 26.79 | 0.394880E+09 | 545.01 | 07-SEP-13:20 | 31.87 | 26.91 |
October | 0.903588E+10 | 21890.11 | 08-OCT-14:12 | 32.17 | 26.12 | 0.409932E+09 | 545.02 | 05-OCT-13:50 | 32.17 | 26.12 |
November | 0.888740E+10 | 21983.84 | 19-NOV-16:52 | 29.50 | 25.36 | 0.406760E+09 | 545.02 | 14-NOV-14:30 | 29.50 | 25.36 |
December | 0.885023E+10 | 21598.52 | 25-DEC-15:52 | 31.00 | 22.24 | 0.395656E+09 | 544.96 | 21-DEC-14:30 | 31.00 | 22.24 |
Annual Sum or Average | 0.122243E+12 | 0.492836E+10 | ||||||||
Minimum of Months | 0.885023E+10 | 21598.52 | 29.10 | 21.99 | 0.372920E+09 | 544.96 | 29.17 | 22.24 | ||
Maximum of Months | 0.121078E+11 | 23821.07 | 34.97 | 28.05 | 0.445516E+09 | 546.52 | 34.55 | 28.13 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.145400E+11 | 15202.33 | 18-JAN-06:02 | 19.95 | 19.88 | 0.00 | 0.00 | 01-JAN-00:10 | 19.95 | 19.88 |
February | 0.146337E+11 | 19496.78 | 21-FEB-06:15 | 24.67 | 21.61 | 0.00 | 0.00 | 01-FEB-00:10 | 24.67 | 21.61 |
March | 0.181725E+11 | 19652.36 | 27-MAR-05:13 | 26.00 | 24.56 | 0.00 | 0.00 | 01-MAR-00:10 | 26.00 | 24.56 |
April | 0.175667E+11 | 19646.61 | 03-APR-05:15 | 27.00 | 24.93 | 0.00 | 0.00 | 01-APR-00:10 | 27.00 | 24.93 |
May | 0.171732E+11 | 20213.99 | 01-MAY-05:15 | 28.00 | 26.50 | 0.00 | 0.00 | 01-MAY-00:10 | 28.00 | 26.50 |
June | 0.182456E+11 | 20051.30 | 19-JUN-05:15 | 27.00 | 26.21 | 0.00 | 0.00 | 01-JUN-00:10 | 27.00 | 26.21 |
July | 0.165155E+11 | 18012.78 | 10-JUL-05:15 | 25.10 | 23.55 | 0.00 | 0.00 | 01-JUL-00:10 | 25.10 | 23.55 |
August | 0.174471E+11 | 19165.24 | 14-AUG-05:15 | 26.00 | 26.00 | 0.00 | 0.00 | 01-AUG-00:10 | 26.00 | 26.00 |
September | 0.149917E+11 | 15825.09 | 05-SEP-10:50 | 31.87 | 26.83 | 0.00 | 0.00 | 01-SEP-00:10 | 31.87 | 26.83 |
October | 0.149733E+11 | 17397.59 | 10-OCT-05:05 | 24.00 | 23.57 | 0.00 | 0.00 | 01-OCT-00:10 | 24.00 | 23.57 |
November | 0.155645E+11 | 18260.21 | 13-NOV-06:15 | 25.27 | 24.33 | 0.00 | 0.00 | 01-NOV-00:10 | 25.27 | 24.33 |
December | 0.151090E+11 | 16578.68 | 26-DEC-06:03 | 22.17 | 21.35 | 0.00 | 0.00 | 01-DEC-00:10 | 22.17 | 21.35 |
Annual Sum or Average | 0.194933E+12 | 0.00 | ||||||||
Minimum of Months | 0.145400E+11 | 15202.33 | 19.95 | 19.88 | 0.00 | 0.00 | 19.95 | 19.88 | ||
Maximum of Months | 0.182456E+11 | 20213.99 | 31.87 | 26.83 | 0.00 | 0.00 | 31.87 | 26.83 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.966633E+10 | 11032.04 | 02-JAN-06:03 | 23.28 | 23.00 | 0.00 | 0.00 | 01-JAN-00:10 | 23.28 | 23.00 |
February | 0.947257E+10 | 11250.77 | 28-FEB-06:02 | 24.17 | 21.32 | 0.00 | 0.00 | 01-FEB-00:10 | 24.17 | 21.32 |
March | 0.108628E+11 | 9466.46 | 08-MAR-06:02 | 24.17 | 22.63 | 0.00 | 0.00 | 01-MAR-00:10 | 24.17 | 22.63 |
April | 0.103193E+11 | 9025.95 | 12-APR-13:30 | 33.40 | 25.31 | 0.00 | 0.00 | 01-APR-00:10 | 33.40 | 25.31 |
May | 0.107008E+11 | 9925.19 | 16-MAY-05:02 | 25.00 | 25.00 | 0.00 | 0.00 | 01-MAY-00:10 | 25.00 | 25.00 |
June | 0.113779E+11 | 11431.54 | 27-JUN-05:02 | 23.00 | 23.00 | 0.00 | 0.00 | 01-JUN-00:10 | 23.00 | 23.00 |
July | 0.942258E+10 | 9038.70 | 28-JUL-13:20 | 32.17 | 26.06 | 0.00 | 0.00 | 01-JUL-00:10 | 32.17 | 26.06 |
August | 0.959319E+10 | 9588.72 | 26-AUG-05:03 | 25.17 | 25.17 | 0.00 | 0.00 | 01-AUG-00:10 | 25.17 | 25.17 |
September | 0.904261E+10 | 10944.77 | 09-SEP-05:02 | 24.00 | 23.26 | 0.00 | 0.00 | 01-SEP-00:10 | 24.00 | 23.26 |
October | 0.864616E+10 | 9626.63 | 07-OCT-05:03 | 24.08 | 24.02 | 0.00 | 0.00 | 01-OCT-00:10 | 24.08 | 24.02 |
November | 0.904494E+10 | 11025.07 | 18-NOV-06:02 | 23.13 | 22.28 | 0.00 | 0.00 | 01-NOV-00:10 | 23.13 | 22.28 |
December | 0.908479E+10 | 9825.07 | 06-DEC-06:03 | 22.13 | 22.04 | 0.00 | 0.00 | 01-DEC-00:10 | 22.13 | 22.04 |
Annual Sum or Average | 0.117234E+12 | 0.00 | ||||||||
Minimum of Months | 0.864616E+10 | 9025.95 | 22.13 | 21.32 | 0.00 | 0.00 | 22.13 | 21.32 | ||
Maximum of Months | 0.113779E+11 | 11431.54 | 33.40 | 26.06 | 0.00 | 0.00 | 33.40 | 26.06 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.137042E+11 | 19250.03 | 04-JAN-13:05 | 34.08 | 23.62 | 0.00 | 0.00 | 01-JAN-00:10 | 34.08 | 23.62 |
February | 0.139951E+11 | 19658.05 | 24-FEB-14:50 | 34.00 | 21.29 | 0.00 | 0.00 | 01-FEB-00:10 | 34.00 | 21.29 |
March | 0.170159E+11 | 21414.49 | 29-MAR-14:50 | 34.33 | 24.51 | 0.00 | 0.00 | 01-MAR-00:10 | 34.33 | 24.51 |
April | 0.166689E+11 | 23544.63 | 12-APR-13:30 | 33.40 | 25.31 | 0.00 | 0.00 | 01-APR-00:10 | 33.40 | 25.31 |
May | 0.165078E+11 | 21343.20 | 02-MAY-12:05 | 34.93 | 26.80 | 0.00 | 0.00 | 01-MAY-00:10 | 34.93 | 26.80 |
June | 0.173934E+11 | 20491.36 | 13-JUN-14:30 | 36.00 | 28.43 | 0.00 | 0.00 | 01-JUN-00:10 | 36.00 | 28.43 |
July | 0.140864E+11 | 19419.69 | 14-JUL-15:20 | 32.53 | 24.87 | 0.00 | 0.00 | 01-JUL-00:10 | 32.53 | 24.87 |
August | 0.143644E+11 | 21914.94 | 28-AUG-13:15 | 32.67 | 27.16 | 0.00 | 0.00 | 01-AUG-00:10 | 32.67 | 27.16 |
September | 0.137731E+11 | 18884.23 | 06-SEP-14:00 | 34.00 | 26.51 | 0.00 | 0.00 | 01-SEP-00:10 | 34.00 | 26.51 |
October | 0.123360E+11 | 19690.71 | 04-OCT-12:05 | 32.47 | 26.81 | 0.00 | 0.00 | 01-OCT-00:10 | 32.47 | 26.81 |
November | 0.128564E+11 | 18155.75 | 15-NOV-12:45 | 30.92 | 25.99 | 0.00 | 0.00 | 01-NOV-00:10 | 30.92 | 25.99 |
December | 0.127981E+11 | 17636.58 | 08-DEC-14:40 | 33.00 | 23.51 | 0.00 | 0.00 | 01-DEC-00:10 | 33.00 | 23.51 |
Annual Sum or Average | 0.175500E+12 | 0.00 | ||||||||
Minimum of Months | 0.123360E+11 | 17636.58 | 30.92 | 21.29 | 0.00 | 0.00 | 30.92 | 21.29 | ||
Maximum of Months | 0.173934E+11 | 23544.63 | 36.00 | 28.43 | 0.00 | 0.00 | 36.00 | 28.43 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.492176E+10 | 2400.12 | 16-JAN-17:40 | 28.07 | 21.84 | 95232853.97 | 126.86 | 23-JAN-10:00 | 27.40 | 20.72 |
February | 0.904721E+10 | 4242.32 | 20-FEB-17:40 | 30.00 | 23.63 | 86415270.00 | 126.86 | 15-FEB-10:09 | 30.00 | 23.63 |
March | 0.151525E+11 | 7402.62 | 31-MAR-23:33 | 27.53 | 24.91 | 0.103248E+09 | 126.84 | 15-MAR-09:09 | 27.53 | 24.91 |
April | 0.194829E+11 | 7888.83 | 09-APR-16:12 | 26.33 | 24.38 | 93863420.00 | 136.29 | 18-APR-13:00 | 34.50 | 26.94 |
May | 0.502553E+10 | 3625.52 | 31-MAY-24:00 | 24.10 | 23.98 | 99233185.27 | 126.82 | 23-MAY-09:20 | 24.10 | 23.98 |
June | 0.977270E+10 | 5485.67 | 30-JUN-23:45 | 25.35 | 24.37 | 98989968.49 | 126.88 | 01-JUN-09:09 | 25.35 | 24.37 |
July | 0.151170E+11 | 7403.15 | 31-JUL-24:00 | 25.60 | 24.83 | 91894606.10 | 126.85 | 03-JUL-13:09 | 25.60 | 24.83 |
August | 0.200743E+11 | 7889.54 | 06-AUG-16:38 | 27.13 | 25.79 | 0.105184E+09 | 136.69 | 14-AUG-13:00 | 33.00 | 27.70 |
September | 0.482317E+10 | 3622.51 | 30-SEP-23:45 | 26.28 | 25.37 | 91605159.02 | 126.82 | 27-SEP-09:09 | 26.28 | 25.37 |
October | 0.100039E+11 | 5487.58 | 31-OCT-23:50 | 25.28 | 24.39 | 95260699.08 | 126.87 | 23-OCT-09:09 | 25.28 | 24.39 |
November | 0.145962E+11 | 6107.44 | 19-NOV-16:54 | 29.50 | 25.36 | 94313964.82 | 126.85 | 01-NOV-09:00 | 29.50 | 25.36 |
December | 0.200701E+11 | 7985.22 | 03-DEC-17:20 | 28.00 | 23.05 | 92182702.23 | 130.86 | 08-DEC-14:00 | 33.00 | 23.65 |
Annual Sum or Average | 0.148087E+12 | 0.114742E+10 | ||||||||
Minimum of Months | 0.482317E+10 | 2400.12 | 24.10 | 21.84 | 86415270.00 | 126.82 | 24.10 | 20.72 | ||
Maximum of Months | 0.200743E+11 | 7985.22 | 30.00 | 25.79 | 0.105184E+09 | 136.69 | 34.50 | 27.70 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.437009E+10 | 2032.82 | 16-JAN-17:40 | 28.07 | 21.84 | 95231284.38 | 126.85 | 23-JAN-14:00 | 30.50 | 21.05 |
February | 0.836716E+10 | 3864.17 | 24-FEB-17:00 | 33.00 | 20.57 | 86417160.27 | 126.87 | 15-FEB-10:09 | 33.00 | 20.57 |
March | 0.140939E+11 | 7000.05 | 31-MAR-23:45 | 27.57 | 24.94 | 0.103252E+09 | 126.85 | 15-MAR-09:09 | 27.57 | 24.94 |
April | 0.182070E+11 | 7351.77 | 23-APR-18:00 | 30.50 | 24.94 | 93265332.51 | 135.53 | 18-APR-13:00 | 30.50 | 24.94 |
May | 0.434711E+10 | 3447.64 | 31-MAY-24:00 | 24.10 | 23.98 | 99233470.99 | 126.82 | 03-MAY-13:50 | 24.10 | 23.98 |
June | 0.896472E+10 | 5116.65 | 30-JUN-24:00 | 25.40 | 24.37 | 98993707.63 | 126.88 | 01-JUN-13:20 | 25.40 | 24.37 |
July | 0.140314E+11 | 7002.51 | 31-JUL-24:00 | 25.60 | 24.83 | 91898437.83 | 126.85 | 03-JUL-13:20 | 25.60 | 24.83 |
August | 0.188115E+11 | 7318.47 | 13-AUG-17:22 | 28.00 | 26.50 | 0.104726E+09 | 135.57 | 10-AUG-13:00 | 28.00 | 26.50 |
September | 0.414596E+10 | 3342.97 | 30-SEP-23:45 | 26.28 | 25.37 | 91605416.75 | 126.82 | 29-SEP-13:50 | 26.28 | 25.37 |
October | 0.915742E+10 | 5129.66 | 31-OCT-23:53 | 25.30 | 24.41 | 95262858.79 | 126.88 | 30-OCT-13:20 | 25.30 | 24.41 |
November | 0.136011E+11 | 5663.96 | 20-NOV-17:00 | 30.00 | 25.17 | 94317625.24 | 126.85 | 13-NOV-10:09 | 30.00 | 25.17 |
December | 0.188852E+11 | 7486.73 | 15-DEC-17:00 | 29.00 | 21.53 | 91997685.89 | 129.67 | 08-DEC-14:00 | 29.00 | 21.53 |
Annual Sum or Average | 0.136982E+12 | 0.114620E+10 | ||||||||
Minimum of Months | 0.414596E+10 | 2032.82 | 24.10 | 20.57 | 86417160.27 | 126.82 | 24.10 | 20.57 | ||
Maximum of Months | 0.188852E+11 | 7486.73 | 33.00 | 26.50 | 0.104726E+09 | 135.57 | 33.00 | 26.50 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.439454E+10 | 2204.71 | 16-JAN-17:40 | 28.07 | 21.84 | 95231389.46 | 126.86 | 23-JAN-14:00 | 30.50 | 21.05 |
February | 0.841696E+10 | 3954.03 | 24-FEB-17:00 | 33.00 | 20.57 | 86416473.62 | 126.87 | 15-FEB-10:20 | 33.00 | 20.57 |
March | 0.141952E+11 | 7012.00 | 31-MAR-23:45 | 27.57 | 24.94 | 0.103251E+09 | 126.85 | 14-MAR-09:00 | 27.57 | 24.94 |
April | 0.183433E+11 | 7526.78 | 23-APR-18:00 | 30.50 | 24.94 | 92830462.53 | 134.38 | 18-APR-13:00 | 30.50 | 24.94 |
May | 0.447630E+10 | 3458.26 | 31-MAY-24:00 | 24.10 | 23.98 | 99233191.81 | 126.82 | 23-MAY-09:39 | 24.10 | 23.98 |
June | 0.907621E+10 | 5039.61 | 30-JUN-24:00 | 25.40 | 24.37 | 98993065.30 | 126.88 | 01-JUN-13:09 | 25.40 | 24.37 |
July | 0.141212E+11 | 7003.78 | 31-JUL-24:00 | 25.60 | 24.83 | 91897619.01 | 126.85 | 20-JUL-09:00 | 25.60 | 24.83 |
August | 0.188897E+11 | 7543.92 | 13-AUG-17:40 | 28.00 | 26.50 | 0.104178E+09 | 134.07 | 14-AUG-13:00 | 33.00 | 27.70 |
September | 0.424613E+10 | 3375.47 | 30-SEP-23:20 | 26.23 | 25.32 | 91605164.50 | 126.82 | 25-SEP-09:50 | 26.23 | 25.32 |
October | 0.920529E+10 | 5111.95 | 31-OCT-23:53 | 25.30 | 24.41 | 95262866.41 | 126.88 | 30-OCT-13:39 | 25.30 | 24.41 |
November | 0.136374E+11 | 5741.20 | 20-NOV-17:00 | 30.00 | 25.17 | 94316764.30 | 126.85 | 13-NOV-10:09 | 30.00 | 25.17 |
December | 0.189023E+11 | 7566.79 | 25-DEC-17:00 | 29.00 | 23.94 | 91924986.21 | 128.75 | 08-DEC-14:00 | 29.00 | 23.94 |
Annual Sum or Average | 0.137904E+12 | 0.114514E+10 | ||||||||
Minimum of Months | 0.424613E+10 | 2204.71 | 24.10 | 20.57 | 86416473.62 | 126.82 | 24.10 | 20.57 | ||
Maximum of Months | 0.189023E+11 | 7566.79 | 33.00 | 26.50 | 0.104178E+09 | 134.38 | 33.00 | 27.70 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.247249E+12 | 95553.87 | 05-JAN-17:00 | 31.00 | 23.58 | 0.206237E+10 | 2747.20 | 11-JAN-10:30 | 27.85 | 24.32 |
February | 0.444704E+12 | 187186.25 | 17-FEB-16:43 | 31.35 | 24.62 | 0.187080E+10 | 2746.64 | 15-FEB-10:09 | 31.35 | 24.62 |
March | 0.739067E+12 | 362303.28 | 31-MAR-24:00 | 27.60 | 24.97 | 0.223519E+10 | 2746.04 | 15-MAR-09:09 | 27.60 | 24.97 |
April | 0.952033E+12 | 370958.17 | 03-APR-16:00 | 31.50 | 24.56 | 0.198308E+10 | 2745.55 | 21-APR-09:09 | 27.45 | 25.43 |
May | 0.249445E+12 | 179062.63 | 31-MAY-24:00 | 24.10 | 23.98 | 0.214847E+10 | 2747.27 | 01-MAY-09:09 | 24.10 | 23.98 |
June | 0.478427E+12 | 270689.50 | 30-JUN-24:00 | 25.40 | 24.37 | 0.214322E+10 | 2747.14 | 30-JUN-13:20 | 25.40 | 24.37 |
July | 0.739787E+12 | 362653.18 | 31-JUL-24:00 | 25.60 | 24.83 | 0.198944E+10 | 2746.25 | 03-JUL-13:20 | 25.60 | 24.83 |
August | 0.985023E+12 | 371309.03 | 28-AUG-16:00 | 31.20 | 26.59 | 0.223491E+10 | 2745.62 | 04-AUG-13:30 | 31.20 | 26.59 |
September | 0.241607E+12 | 178462.61 | 30-SEP-23:57 | 26.30 | 25.39 | 0.198351E+10 | 2747.32 | 01-SEP-13:00 | 26.30 | 25.39 |
October | 0.493314E+12 | 270420.85 | 31-OCT-23:53 | 25.30 | 24.41 | 0.206242E+10 | 2746.97 | 11-OCT-13:39 | 25.30 | 24.41 |
November | 0.715083E+12 | 279063.48 | 20-NOV-17:00 | 30.00 | 25.17 | 0.204181E+10 | 2746.22 | 01-NOV-09:00 | 30.00 | 25.17 |
December | 0.983854E+12 | 371023.74 | 07-DEC-17:00 | 29.00 | 23.27 | 0.198905E+10 | 2745.53 | 01-DEC-10:09 | 29.00 | 23.27 |
Annual Sum or Average | 0.726959E+13 | 0.247443E+11 | ||||||||
Minimum of Months | 0.241607E+12 | 95553.87 | 24.10 | 23.27 | 0.187080E+10 | 2745.53 | 24.10 | 23.27 | ||
Maximum of Months | 0.985023E+12 | 371309.03 | 31.50 | 26.59 | 0.223519E+10 | 2747.32 | 31.35 | 26.59 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 149726.66 | 249.54 | 17-JAN-06:30 | 20.50 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:03 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 149726.66 | |||
Minimum of Months | 0.00 | 0.00 | 20.50 | |
Maximum of Months | 149726.66 | 249.54 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:03 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:03 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:03 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:03 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:03 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:03 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:03 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:03 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:03 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:03 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:03 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:03 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:03 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:03 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:03 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 63886181.35 | 6665.83 | 26-JAN-05:12 | 22.00 |
February | 64375720.14 | 5983.79 | 09-FEB-05:11 | 23.33 |
March | 53599772.84 | 5152.50 | 19-MAR-14:22 | 35.50 |
April | 41961785.08 | 6234.28 | 23-APR-15:21 | 33.35 |
May | 61752285.45 | 7886.16 | 18-MAY-01:22 | 26.00 |
June | 56175070.11 | 8105.52 | 30-JUN-22:12 | 25.83 |
July | 79986915.66 | 7863.57 | 01-JUL-01:02 | 25.40 |
August | 89740918.57 | 5109.81 | 20-AUG-06:30 | 23.50 |
September | 85973646.75 | 7530.10 | 17-SEP-05:12 | 24.00 |
October | 0.110626E+09 | 8141.28 | 26-OCT-23:42 | 24.58 |
November | 98951918.41 | 6442.10 | 09-NOV-03:32 | 24.67 |
December | 81394203.15 | 5420.29 | 01-DEC-03:50 | 21.20 |
Annual Sum or Average | 0.888424E+09 | |||
Minimum of Months | 41961785.08 | 5109.81 | 21.20 | |
Maximum of Months | 0.110626E+09 | 8141.28 | 35.50 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16728860.74 | 3764.41 | 02-JAN-05:12 | 23.27 |
February | 13635966.40 | 3814.70 | 26-FEB-14:32 | 35.00 |
March | 15700919.22 | 4553.19 | 19-MAR-14:42 | 35.17 |
April | 9006277.24 | 5504.72 | 02-APR-14:51 | 35.00 |
May | 16169065.39 | 5386.11 | 22-MAY-03:02 | 27.00 |
June | 14183635.19 | 4749.02 | 18-JUN-14:11 | 35.00 |
July | 12081827.66 | 3841.67 | 20-JUL-04:12 | 23.87 |
August | 15374324.27 | 6166.78 | 21-AUG-03:02 | 24.03 |
September | 13203217.58 | 4847.84 | 18-SEP-03:02 | 25.50 |
October | 17322722.35 | 4877.12 | 23-OCT-04:12 | 22.57 |
November | 15715402.81 | 4764.13 | 27-NOV-05:12 | 22.00 |
December | 19299651.62 | 5004.14 | 18-DEC-05:12 | 23.00 |
Annual Sum or Average | 0.178422E+09 | |||
Minimum of Months | 9006277.24 | 3764.41 | 22.00 | |
Maximum of Months | 19299651.62 | 6166.78 | 35.17 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 26944899.19 | 9487.99 | 23-JAN-05:12 | 18.90 |
February | 22013812.00 | 8373.92 | 13-FEB-05:02 | 23.92 |
March | 16132120.58 | 7139.34 | 02-MAR-05:12 | 23.00 |
April | 6582229.21 | 4112.22 | 10-APR-03:02 | 25.03 |
May | 10728438.73 | 5757.85 | 22-MAY-03:02 | 27.00 |
June | 7854242.62 | 6010.34 | 05-JUN-03:02 | 25.85 |
July | 13690489.79 | 6753.57 | 18-JUL-04:12 | 23.93 |
August | 15458225.98 | 6546.45 | 31-AUG-04:02 | 24.33 |
September | 13746781.50 | 6283.13 | 15-SEP-04:02 | 24.83 |
October | 16851627.69 | 6121.25 | 23-OCT-04:12 | 22.57 |
November | 19118655.08 | 8065.30 | 27-NOV-05:12 | 22.00 |
December | 27569882.08 | 8176.84 | 27-DEC-05:12 | 19.00 |
Annual Sum or Average | 0.196691E+09 | |||
Minimum of Months | 6582229.21 | 4112.22 | 18.90 | |
Maximum of Months | 27569882.08 | 9487.99 | 27.00 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:03 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:03 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:03 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 25.03 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 26.43 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 25.93 |
April | 0.00 | 0.00 | 01-APR-00:03 | 27.53 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 28.62 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 24.05 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 25.40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 25.63 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.53 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 26.27 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 25.22 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 23.80 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 23.80 | |
Maximum of Months | 0.00 | 0.00 | 28.62 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180249E+11 | 19402.09 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.163527E+11 | 19402.09 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.194806E+11 | 19402.09 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.173504E+11 | 19402.09 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.187528E+11 | 19402.09 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.186803E+11 | 19402.09 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.174228E+11 | 19402.09 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.194803E+11 | 19402.09 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.173504E+11 | 19402.09 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.180252E+11 | 19402.09 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.178272E+11 | 19402.09 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.174231E+11 | 19402.09 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.216171E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.163527E+11 | 19402.09 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.194806E+11 | 19402.09 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118886E+10 | 1906.53 | 02-JAN-16:49 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.106116E+10 | 1242.97 | 01-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.122680E+10 | 1524.25 | 01-MAR-16:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.106892E+10 | 1141.96 | 14-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.115533E+10 | 1141.96 | 09-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.113762E+10 | 1141.96 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.106995E+10 | 1141.96 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.119970E+10 | 1141.96 | 02-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.109230E+10 | 1141.96 | 07-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.114996E+10 | 1242.97 | 11-OCT-15:50 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.118693E+10 | 1906.53 | 06-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.116787E+10 | 1906.53 | 04-DEC-16:40 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.137054E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.106116E+10 | 1141.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.122680E+10 | 1906.53 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.765665E+09 | 1228.64 | 02-JAN-16:49 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.685467E+09 | 982.28 | 01-FEB-16:49 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.792449E+09 | 982.28 | 01-MAR-16:49 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.693645E+09 | 735.93 | 10-APR-15:30 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.752448E+09 | 735.93 | 02-MAY-15:30 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.742594E+09 | 735.93 | 01-JUN-15:39 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.698559E+09 | 735.93 | 03-JUL-15:50 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.779129E+09 | 735.93 | 02-AUG-15:39 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.706642E+09 | 735.93 | 01-SEP-15:30 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.741255E+09 | 982.28 | 30-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.769512E+09 | 1228.64 | 06-NOV-16:49 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.752635E+09 | 1228.64 | 01-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.888000E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.685467E+09 | 735.93 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.792449E+09 | 1228.64 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.115849E+10 | 1524.28 | 02-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.104577E+10 | 1215.47 | 01-FEB-17:40 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.122242E+10 | 1243.00 | 01-MAR-16:49 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.107641E+10 | 1141.99 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.117137E+10 | 1243.00 | 17-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.115724E+10 | 1243.00 | 20-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.109061E+10 | 1243.00 | 07-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.121137E+10 | 1243.00 | 02-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.109275E+10 | 1141.99 | 07-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.113626E+10 | 1243.00 | 23-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.115527E+10 | 1906.57 | 09-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.113131E+10 | 1906.57 | 04-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.136493E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.104577E+10 | 1141.99 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.122242E+10 | 1906.57 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.747665E+09 | 982.28 | 02-JAN-16:00 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.673312E+09 | 783.28 | 01-FEB-17:40 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.785513E+09 | 801.02 | 13-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.692034E+09 | 801.02 | 05-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.751294E+09 | 982.28 | 17-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.739913E+09 | 801.02 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.699082E+09 | 982.28 | 11-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.779667E+09 | 982.28 | 21-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.705732E+09 | 801.02 | 07-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.736137E+09 | 982.28 | 23-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.742572E+09 | 982.28 | 07-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.729130E+09 | 1228.64 | 18-DEC-16:49 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.878205E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.673312E+09 | 783.28 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.785513E+09 | 1228.64 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118565E+10 | 1906.53 | 02-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.105977E+10 | 1242.97 | 01-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.122533E+10 | 1524.25 | 01-MAR-16:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.106792E+10 | 1141.96 | 14-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.115410E+10 | 1141.96 | 09-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.113665E+10 | 1141.96 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.106922E+10 | 1141.96 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.119859E+10 | 1141.96 | 02-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.109074E+10 | 1141.96 | 07-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.114759E+10 | 1242.97 | 11-OCT-15:00 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.118429E+10 | 1906.53 | 06-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.116459E+10 | 1906.53 | 04-DEC-16:49 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.136845E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.105977E+10 | 1141.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.122533E+10 | 1906.53 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.764070E+09 | 1228.64 | 02-JAN-16:49 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.684392E+09 | 982.28 | 01-FEB-16:49 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.791884E+09 | 982.28 | 01-MAR-16:49 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.693009E+09 | 735.93 | 10-APR-15:30 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.750918E+09 | 735.93 | 02-MAY-15:39 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.741717E+09 | 735.93 | 01-JUN-15:50 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.697692E+09 | 735.93 | 06-JUL-15:50 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.777855E+09 | 735.93 | 02-AUG-15:50 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.705183E+09 | 735.93 | 01-SEP-15:39 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.739709E+09 | 982.28 | 30-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.767604E+09 | 1228.64 | 06-NOV-16:49 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.751288E+09 | 1228.64 | 04-DEC-16:40 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.886532E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.684392E+09 | 735.93 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.791884E+09 | 1228.64 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.115512E+10 | 1524.28 | 02-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.104496E+10 | 1215.47 | 01-FEB-17:40 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.122162E+10 | 1243.00 | 01-MAR-16:49 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.107526E+10 | 1141.99 | 05-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.116987E+10 | 1243.00 | 17-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.115584E+10 | 1243.00 | 20-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.108831E+10 | 1243.00 | 07-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.121001E+10 | 1243.00 | 21-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.109121E+10 | 1141.99 | 07-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.113486E+10 | 1243.00 | 23-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.115387E+10 | 1906.57 | 09-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.112883E+10 | 1906.57 | 18-DEC-16:40 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.136298E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.104496E+10 | 1141.99 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.122162E+10 | 1906.57 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.746623E+09 | 982.28 | 02-JAN-16:00 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.672666E+09 | 783.28 | 01-FEB-17:40 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.784615E+09 | 801.02 | 15-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.691133E+09 | 801.02 | 14-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.749847E+09 | 982.28 | 17-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.738684E+09 | 801.02 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.697468E+09 | 801.02 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.777780E+09 | 801.02 | 02-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.704288E+09 | 801.02 | 07-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.734722E+09 | 982.28 | 23-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.741687E+09 | 982.28 | 07-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.728184E+09 | 1228.64 | 18-DEC-16:49 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.876770E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.672666E+09 | 783.28 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.784615E+09 | 1228.64 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118564E+10 | 1906.53 | 02-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.105977E+10 | 1242.97 | 01-FEB-16:00 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.122525E+10 | 1524.25 | 01-MAR-16:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.106789E+10 | 1141.96 | 14-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.115407E+10 | 1141.96 | 09-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.113665E+10 | 1141.96 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.106917E+10 | 1141.96 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.119857E+10 | 1141.96 | 02-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.109061E+10 | 1141.96 | 07-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.114757E+10 | 1242.97 | 11-OCT-15:00 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.118408E+10 | 1906.53 | 06-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.116448E+10 | 1906.53 | 04-DEC-16:49 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.136838E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.105977E+10 | 1141.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.122525E+10 | 1906.53 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.764066E+09 | 1228.64 | 02-JAN-16:49 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.684244E+09 | 982.28 | 01-FEB-16:49 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.791709E+09 | 982.28 | 01-MAR-16:49 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.692973E+09 | 735.93 | 10-APR-15:30 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.750881E+09 | 735.93 | 02-MAY-15:39 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.741717E+09 | 735.93 | 01-JUN-15:50 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.697692E+09 | 735.93 | 06-JUL-15:50 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.777833E+09 | 735.93 | 02-AUG-15:50 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.705147E+09 | 735.93 | 01-SEP-15:39 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.739672E+09 | 982.28 | 30-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.767526E+09 | 1228.64 | 06-NOV-16:49 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.751249E+09 | 1228.64 | 04-DEC-16:40 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.886471E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.684244E+09 | 735.93 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.791709E+09 | 1228.64 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.115512E+10 | 1524.28 | 02-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.104495E+10 | 1215.47 | 01-FEB-17:40 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.122148E+10 | 1243.00 | 01-MAR-16:00 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.107519E+10 | 1141.99 | 05-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.116972E+10 | 1243.00 | 17-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.115580E+10 | 1243.00 | 20-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.108812E+10 | 1243.00 | 07-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.120988E+10 | 1243.00 | 21-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.109115E+10 | 1141.99 | 07-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.113478E+10 | 1243.00 | 23-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.115387E+10 | 1906.57 | 09-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.112882E+10 | 1906.57 | 18-DEC-16:40 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.136289E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.104495E+10 | 1141.99 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.122148E+10 | 1906.57 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.746571E+09 | 982.28 | 02-JAN-16:00 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.672630E+09 | 783.28 | 01-FEB-17:40 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.784576E+09 | 801.02 | 15-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.691118E+09 | 801.02 | 14-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.749799E+09 | 982.28 | 17-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.738632E+09 | 801.02 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.697432E+09 | 801.02 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.777731E+09 | 801.02 | 02-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.704249E+09 | 801.02 | 07-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.734720E+09 | 982.28 | 23-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.741661E+09 | 982.28 | 07-NOV-16:00 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.728171E+09 | 1228.64 | 18-DEC-16:49 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.876729E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.672630E+09 | 783.28 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.784576E+09 | 1228.64 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.522764E+10 | 5470.56 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.474186E+10 | 5470.56 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.563465E+10 | 5470.56 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.503289E+10 | 5470.56 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.543115E+10 | 5470.56 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.540489E+10 | 5470.56 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.505915E+10 | 5470.56 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.563465E+10 | 5470.56 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.503289E+10 | 5470.56 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.522764E+10 | 5470.56 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.516637E+10 | 5470.56 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.505915E+10 | 5470.56 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.626529E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.474186E+10 | 5470.56 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.563465E+10 | 5470.56 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.180249E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.163527E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.194806E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.173504E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.187528E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.186803E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.174228E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.194803E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.173504E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.180252E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.178272E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.174231E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.216171E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.163527E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.194806E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.118886E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17647390.22 | 13001070.23 |
February | 0.136985E+10 | 0.106116E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25042379.35 | 3394633.29 |
March | 0.163685E+10 | 0.122680E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43910426.80 | 4477391.55 |
April | 0.145243E+10 | 0.106892E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43927529.05 | 719052.19 |
May | 0.157338E+10 | 0.115533E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48302269.38 | 3085249.10 |
June | 0.156900E+10 | 0.113762E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42964434.76 | 3264988.96 |
July | 0.145680E+10 | 0.106995E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25669228.79 | 2758851.34 |
August | 0.163685E+10 | 0.119970E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31470527.44 | 5162536.26 |
September | 0.145243E+10 | 0.109230E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23580443.49 | 3769771.10 |
October | 0.150991E+10 | 0.114996E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18797439.94 | 5658941.87 |
November | 0.149516E+10 | 0.118693E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14589828.24 | 6738034.59 |
December | 0.145680E+10 | 0.116787E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13819361.23 | 13191458.55 |
Annual Sum or Average | 0.181194E+11 | 0.137054E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349721E+09 | 65221979.04 |
Minimum of Months | 0.136985E+10 | 0.106116E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13819361.23 | 719052.19 |
Maximum of Months | 0.163685E+10 | 0.122680E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48302269.38 | 13191458.55 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.765665E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11744476.34 | 8546628.92 |
February | 0.882782E+09 | 0.685467E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16907255.90 | 2102904.66 |
March | 0.105485E+10 | 0.792449E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30229355.03 | 2478286.04 |
April | 0.936002E+09 | 0.693645E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31043102.64 | 314807.89 |
May | 0.101394E+10 | 0.752448E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33446317.78 | 1775523.83 |
June | 0.101113E+10 | 0.742594E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30927894.11 | 1755260.11 |
July | 0.938820E+09 | 0.698559E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18467291.51 | 1279532.19 |
August | 0.105485E+10 | 0.779129E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22625441.96 | 2222303.99 |
September | 0.936002E+09 | 0.706642E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15803815.44 | 2410214.46 |
October | 0.973041E+09 | 0.741255E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12734558.54 | 3237172.74 |
November | 0.963541E+09 | 0.769512E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9992850.35 | 3717179.09 |
December | 0.938820E+09 | 0.752635E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9518696.54 | 7663890.55 |
Annual Sum or Average | 0.116768E+11 | 0.888000E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243441E+09 | 37503704.48 |
Minimum of Months | 0.882782E+09 | 0.685467E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9518696.54 | 314807.89 |
Maximum of Months | 0.105485E+10 | 0.792449E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33446317.78 | 8546628.92 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.115849E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15669526.36 | 15231211.90 |
February | 0.136988E+10 | 0.104577E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23244884.96 | 4178899.45 |
March | 0.163688E+10 | 0.122242E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42773943.27 | 4656374.86 |
April | 0.145246E+10 | 0.107641E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45466671.47 | 556408.02 |
May | 0.157341E+10 | 0.117137E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50492775.90 | 2600737.04 |
June | 0.156904E+10 | 0.115724E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46315207.44 | 2675104.36 |
July | 0.145684E+10 | 0.109061E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27217663.37 | 2101918.12 |
August | 0.163688E+10 | 0.121137E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33043422.72 | 4067366.05 |
September | 0.145246E+10 | 0.109275E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23710202.77 | 3470277.04 |
October | 0.150994E+10 | 0.113626E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18187712.07 | 5800951.93 |
November | 0.149520E+10 | 0.115527E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13518559.30 | 7556353.84 |
December | 0.145684E+10 | 0.113131E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12293977.37 | 15166940.73 |
Annual Sum or Average | 0.181198E+11 | 0.136493E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351935E+09 | 68062543.35 |
Minimum of Months | 0.136988E+10 | 0.104577E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12293977.37 | 556408.02 |
Maximum of Months | 0.163688E+10 | 0.122242E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50492775.90 | 15231211.90 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.747665E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11909193.48 | 8465100.05 |
February | 0.882782E+09 | 0.673312E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16758032.62 | 2471112.70 |
March | 0.105485E+10 | 0.785513E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28773927.07 | 3645460.54 |
April | 0.936002E+09 | 0.692034E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28294443.12 | 752764.45 |
May | 0.101394E+10 | 0.751294E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35090149.29 | 1475965.23 |
June | 0.101113E+10 | 0.739913E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31074551.47 | 1803925.46 |
July | 0.938820E+09 | 0.699082E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18036674.97 | 1649354.49 |
August | 0.105485E+10 | 0.779667E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21182415.98 | 3857729.90 |
September | 0.936002E+09 | 0.705732E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16733938.45 | 1998283.50 |
October | 0.973041E+09 | 0.736137E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13020835.85 | 3351242.44 |
November | 0.963541E+09 | 0.742572E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9799385.80 | 4807716.60 |
December | 0.938820E+09 | 0.729130E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8829108.90 | 10446227.22 |
Annual Sum or Average | 0.116768E+11 | 0.878205E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239503E+09 | 44724882.57 |
Minimum of Months | 0.882782E+09 | 0.673312E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8829108.90 | 752764.45 |
Maximum of Months | 0.105485E+10 | 0.785513E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35090149.29 | 10446227.22 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.118565E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44515341.88 | 28189345.41 |
February | 0.136985E+10 | 0.105977E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62416518.01 | 7801576.54 |
March | 0.163685E+10 | 0.122533E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113803E+09 | 9606122.04 |
April | 0.145243E+10 | 0.106792E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114342E+09 | 1620130.66 |
May | 0.157338E+10 | 0.115410E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115761E+09 | 6818057.58 |
June | 0.156900E+10 | 0.113665E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103006E+09 | 7884036.07 |
July | 0.145680E+10 | 0.106922E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62461035.57 | 6925644.55 |
August | 0.163685E+10 | 0.119859E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77918963.84 | 12349714.21 |
September | 0.145243E+10 | 0.109074E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59861984.08 | 6704064.70 |
October | 0.150991E+10 | 0.114759E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47675030.78 | 11288897.05 |
November | 0.149516E+10 | 0.118429E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37459342.84 | 15397737.31 |
December | 0.145680E+10 | 0.116459E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36294759.38 | 31548116.58 |
Annual Sum or Average | 0.181194E+11 | 0.136845E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.875514E+09 | 0.146133E+09 |
Minimum of Months | 0.136985E+10 | 0.105977E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36294759.38 | 1620130.66 |
Maximum of Months | 0.163685E+10 | 0.122533E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115761E+09 | 31548116.58 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.764070E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28351942.58 | 20697542.29 |
February | 0.649041E+09 | 0.684392E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39888075.00 | 6485260.15 |
March | 0.773965E+09 | 0.791884E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72835795.77 | 7643765.74 |
April | 0.688021E+09 | 0.693009E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75135642.82 | 1307396.63 |
May | 0.744847E+09 | 0.750918E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80678125.41 | 4313065.13 |
June | 0.742030E+09 | 0.741717E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74438495.44 | 4649812.92 |
July | 0.690839E+09 | 0.697692E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44461158.49 | 4067487.56 |
August | 0.773965E+09 | 0.777855E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52590527.52 | 8317046.48 |
September | 0.688021E+09 | 0.705183E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38477099.75 | 5094014.17 |
October | 0.715730E+09 | 0.739709E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31046605.53 | 8181673.22 |
November | 0.708685E+09 | 0.767604E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23951896.84 | 11244640.72 |
December | 0.690839E+09 | 0.751288E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22791267.18 | 22536386.29 |
Annual Sum or Average | 0.858171E+10 | 0.886532E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.584647E+09 | 0.104538E+09 |
Minimum of Months | 0.649041E+09 | 0.684392E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22791267.18 | 1307396.63 |
Maximum of Months | 0.773965E+09 | 0.791884E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80678125.41 | 22536386.29 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.115512E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36291943.06 | 38644947.33 |
February | 0.136988E+10 | 0.104496E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54623896.74 | 12232275.12 |
March | 0.163688E+10 | 0.122162E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105006E+09 | 12311956.65 |
April | 0.145246E+10 | 0.107526E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115715E+09 | 1553263.21 |
May | 0.157341E+10 | 0.116987E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122858E+09 | 5918685.53 |
June | 0.156904E+10 | 0.115584E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113883E+09 | 6297589.26 |
July | 0.145684E+10 | 0.108831E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67903442.58 | 5277399.21 |
August | 0.163688E+10 | 0.121001E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81713356.24 | 11070063.36 |
September | 0.145246E+10 | 0.109121E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58400652.97 | 7142491.74 |
October | 0.150994E+10 | 0.113486E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42870670.10 | 14551013.99 |
November | 0.149520E+10 | 0.115387E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32027449.20 | 20596919.02 |
December | 0.145684E+10 | 0.112883E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28748635.09 | 40524948.53 |
Annual Sum or Average | 0.181198E+11 | 0.136298E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.860043E+09 | 0.176122E+09 |
Minimum of Months | 0.136988E+10 | 0.104496E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28748635.09 | 1553263.21 |
Maximum of Months | 0.163688E+10 | 0.122162E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122858E+09 | 40524948.53 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.746623E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27123974.81 | 23758650.93 |
February | 0.882782E+09 | 0.672666E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38960030.12 | 8658088.09 |
March | 0.105485E+10 | 0.784615E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67665033.31 | 12277034.29 |
April | 0.936002E+09 | 0.691133E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68506845.33 | 2157508.64 |
May | 0.101394E+10 | 0.749847E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77401271.01 | 5421016.69 |
June | 0.101113E+10 | 0.738684E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70583671.67 | 5757543.20 |
July | 0.938820E+09 | 0.697468E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42756964.20 | 5512362.08 |
August | 0.105485E+10 | 0.777780E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50533886.19 | 11759676.21 |
September | 0.936002E+09 | 0.704288E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37727342.77 | 6362463.37 |
October | 0.973041E+09 | 0.734722E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30148752.46 | 10628743.89 |
November | 0.963541E+09 | 0.741687E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23542376.92 | 13521322.37 |
December | 0.938820E+09 | 0.728184E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21827209.86 | 25821109.83 |
Annual Sum or Average | 0.116768E+11 | 0.876770E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556777E+09 | 0.131636E+09 |
Minimum of Months | 0.882782E+09 | 0.672666E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21827209.86 | 2157508.64 |
Maximum of Months | 0.105485E+10 | 0.784615E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77401271.01 | 25821109.83 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.118564E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51940156.11 | 36307910.49 |
February | 0.136985E+10 | 0.105977E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73268618.86 | 10624993.97 |
March | 0.163685E+10 | 0.122525E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132529E+09 | 13255077.68 |
April | 0.145243E+10 | 0.106789E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133565E+09 | 2302011.28 |
May | 0.157338E+10 | 0.115407E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137889E+09 | 9374763.50 |
June | 0.156900E+10 | 0.113665E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122958E+09 | 10595673.13 |
July | 0.145680E+10 | 0.106917E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73785812.68 | 9676844.91 |
August | 0.163685E+10 | 0.119857E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92179740.07 | 16425817.81 |
September | 0.145243E+10 | 0.109061E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69857928.49 | 9524011.73 |
October | 0.150991E+10 | 0.114757E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55577342.23 | 15286735.06 |
November | 0.149516E+10 | 0.118408E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43596542.26 | 20028464.74 |
December | 0.145680E+10 | 0.116448E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42026363.30 | 39353794.34 |
Annual Sum or Average | 0.181194E+11 | 0.136838E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102917E+10 | 0.192756E+09 |
Minimum of Months | 0.136985E+10 | 0.105977E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42026363.30 | 2302011.28 |
Maximum of Months | 0.163685E+10 | 0.122525E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137889E+09 | 39353794.34 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.764066E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33286393.79 | 26598269.08 |
February | 0.882782E+09 | 0.684244E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47246462.47 | 8702806.16 |
March | 0.105485E+10 | 0.791709E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85889708.02 | 10455956.65 |
April | 0.936002E+09 | 0.692973E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88465533.06 | 1825052.55 |
May | 0.101394E+10 | 0.750881E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96131295.30 | 5918781.18 |
June | 0.101113E+10 | 0.741717E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88540223.44 | 6226093.21 |
July | 0.938820E+09 | 0.697692E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52074263.68 | 5704021.58 |
August | 0.105485E+10 | 0.777833E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62437656.94 | 11048733.36 |
September | 0.936002E+09 | 0.705147E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45405141.82 | 7074105.41 |
October | 0.973041E+09 | 0.739672E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36289745.12 | 10830355.02 |
November | 0.963541E+09 | 0.767526E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28121729.60 | 14554152.01 |
December | 0.938820E+09 | 0.751249E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26710662.37 | 28182928.58 |
Annual Sum or Average | 0.116768E+11 | 0.886471E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690599E+09 | 0.137121E+09 |
Minimum of Months | 0.882782E+09 | 0.684244E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26710662.37 | 1825052.55 |
Maximum of Months | 0.105485E+10 | 0.791709E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96131295.30 | 28182928.58 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.115512E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43977345.03 | 49170972.23 |
February | 0.136988E+10 | 0.104495E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65682269.86 | 16160132.84 |
March | 0.163688E+10 | 0.122148E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124099E+09 | 16813157.24 |
April | 0.145246E+10 | 0.107519E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135174E+09 | 2204883.01 |
May | 0.157341E+10 | 0.116972E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145370E+09 | 8177271.96 |
June | 0.156904E+10 | 0.115580E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134726E+09 | 8594414.37 |
July | 0.145684E+10 | 0.108812E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78869692.15 | 7585816.94 |
August | 0.163688E+10 | 0.120988E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96289695.59 | 14705830.06 |
September | 0.145246E+10 | 0.109115E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68545226.47 | 10080204.56 |
October | 0.150994E+10 | 0.113478E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50928731.99 | 19216571.09 |
November | 0.149520E+10 | 0.115387E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38363129.91 | 26406488.99 |
December | 0.145684E+10 | 0.112882E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34743064.71 | 50558533.32 |
Annual Sum or Average | 0.181198E+11 | 0.136289E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101677E+10 | 0.229674E+09 |
Minimum of Months | 0.136988E+10 | 0.104495E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34743064.71 | 2204883.01 |
Maximum of Months | 0.163688E+10 | 0.122148E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145370E+09 | 50558533.32 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.746571E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32691452.50 | 29971336.42 |
February | 0.882782E+09 | 0.672630E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46968773.43 | 11210484.72 |
March | 0.105485E+10 | 0.784576E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81657230.16 | 16143120.61 |
April | 0.936002E+09 | 0.691118E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82567075.78 | 2957284.10 |
May | 0.101394E+10 | 0.749799E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93966138.52 | 7189649.13 |
June | 0.101113E+10 | 0.738632E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85553486.67 | 7435238.58 |
July | 0.938820E+09 | 0.697432E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51402742.38 | 7288622.89 |
August | 0.105485E+10 | 0.777731E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61312601.49 | 15129006.72 |
September | 0.936002E+09 | 0.704249E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45489004.97 | 8441536.13 |
October | 0.973041E+09 | 0.734720E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36379852.05 | 13446377.02 |
November | 0.963541E+09 | 0.741661E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28360822.75 | 17078968.62 |
December | 0.938820E+09 | 0.728171E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26316148.55 | 31861168.76 |
Annual Sum or Average | 0.116768E+11 | 0.876729E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672665E+09 | 0.168153E+09 |
Minimum of Months | 0.882782E+09 | 0.672630E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26316148.55 | 2957284.10 |
Maximum of Months | 0.105485E+10 | 0.784576E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93966138.52 | 31861168.76 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.522764E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.474186E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.563465E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.503289E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.543115E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.540489E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.505915E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.563465E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.503289E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.522764E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.516637E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.505915E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.626529E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.474186E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.563465E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26803790.48 | 32179802.14 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40324096.49 | 9989522.50 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69217740.64 | 14495003.42 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72292901.12 | 2409902.03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82788787.17 | 6887929.45 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73235109.32 | 7453968.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44361328.54 | 7317176.39 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50824574.20 | 13682680.17 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38634366.89 | 8474958.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30317475.79 | 14685060.86 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22423094.36 | 18083511.67 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21153360.18 | 34116373.45 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.572377E+09 | 0.169776E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21153360.18 | 2409902.03 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82788787.17 | 34116373.45 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53768750.46 | 49271106.80 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82884156.66 | 12593232.83 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150573E+09 | 16212771.89 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162578E+09 | 2033109.87 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174667E+09 | 8638822.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154847E+09 | 9627611.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96988977.78 | 7692727.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110344E+09 | 14840697.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83702882.48 | 8433279.20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65753342.11 | 16474133.14 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47678574.68 | 24881871.24 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44333471.70 | 54844374.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122812E+10 | 0.225544E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44333471.70 | 2033109.87 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174667E+09 | 54844374.86 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51616570.03 | 55307347.82 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80730133.66 | 13188506.73 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148550E+09 | 17655631.95 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163795E+09 | 2283988.28 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179266E+09 | 11122886.17 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157248E+09 | 13636802.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87648642.91 | 11330046.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108828E+09 | 17713307.37 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77645282.01 | 12654678.03 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58954200.43 | 21547048.66 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44108260.20 | 29011862.55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40371880.88 | 59508856.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119876E+10 | 0.264961E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40371880.88 | 2283988.28 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179266E+09 | 59508856.38 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 19402.09 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 19402.09 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 19402.09 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 19402.09 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 19402.09 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 19402.09 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 19402.09 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 19402.09 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 19402.09 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 19402.09 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 19402.09 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 19402.09 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 19402.09 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 19402.09 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1906.53 | 02-JAN-16:49 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 60.78 | 15-JAN-13:20 | 250.00 | 07-JAN-05:00 |
February | 2010.79 | 01-FEB-10:09 | 1242.97 | 01-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 132.98 | 19-FEB-14:56 | 23.98 | 11-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 1524.25 | 01-MAR-16:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 221.77 | 19-MAR-15:51 | 47.47 | 14-MAR-22:05 |
April | 2010.79 | 03-APR-09:09 | 1141.96 | 14-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.78 | 30-APR-15:44 | 24.45 | 09-APR-16:20 |
May | 2010.79 | 01-MAY-09:09 | 1141.96 | 09-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.90 | 07-MAY-15:00 | 84.86 | 08-MAY-21:52 |
June | 2010.79 | 01-JUN-09:09 | 1141.96 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.23 | 18-JUN-14:26 | 105.51 | 20-JUN-22:55 |
July | 2010.79 | 03-JUL-09:09 | 1141.96 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.41 | 04-JUL-14:06 | 47.83 | 02-JUL-13:50 |
August | 2010.79 | 01-AUG-09:09 | 1141.96 | 02-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.92 | 06-AUG-12:26 | 79.67 | 20-AUG-11:00 |
September | 2010.79 | 01-SEP-09:09 | 1141.96 | 07-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.66 | 10-SEP-14:51 | 64.34 | 15-SEP-22:00 |
October | 2010.79 | 02-OCT-09:09 | 1242.97 | 11-OCT-15:50 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.06 | 29-OCT-13:06 | 38.60 | 14-OCT-01:00 |
November | 2010.79 | 01-NOV-09:09 | 1906.53 | 06-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.14 | 19-NOV-13:56 | 41.87 | 25-NOV-05:00 |
December | 2010.79 | 01-DEC-10:09 | 1906.53 | 04-DEC-16:40 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 54.67 | 31-DEC-12:58 | 75.35 | 21-DEC-04:40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 54.67 | 23.98 | |||||
Maximum of Months | 2010.79 | 1906.53 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 221.77 | 250.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1228.64 | 02-JAN-16:49 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 41.73 | 15-JAN-13:20 | 168.57 | 07-JAN-05:00 |
February | 1295.83 | 01-FEB-10:09 | 982.28 | 01-FEB-16:49 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 89.82 | 19-FEB-14:56 | 23.84 | 20-FEB-07:20 |
March | 1295.83 | 01-MAR-10:09 | 982.28 | 01-MAR-16:49 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 153.45 | 19-MAR-15:44 | 31.47 | 14-MAR-22:05 |
April | 1295.83 | 03-APR-09:09 | 735.93 | 10-APR-15:30 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.35 | 02-APR-15:44 | 16.90 | 09-APR-16:20 |
May | 1295.83 | 01-MAY-09:09 | 735.93 | 02-MAY-15:30 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.00 | 07-MAY-14:36 | 56.61 | 08-MAY-21:52 |
June | 1295.83 | 01-JUN-09:09 | 735.93 | 01-JUN-15:39 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.47 | 18-JUN-14:26 | 64.99 | 20-JUN-22:55 |
July | 1295.83 | 03-JUL-09:09 | 735.93 | 03-JUL-15:50 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.63 | 04-JUL-14:08 | 29.43 | 02-JUL-13:50 |
August | 1295.83 | 01-AUG-09:09 | 735.93 | 02-AUG-15:39 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.73 | 06-AUG-13:06 | 50.06 | 20-AUG-11:00 |
September | 1295.83 | 01-SEP-09:09 | 735.93 | 01-SEP-15:30 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.11 | 10-SEP-14:51 | 43.79 | 15-SEP-22:00 |
October | 1295.83 | 02-OCT-09:09 | 982.28 | 30-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.19 | 29-OCT-13:06 | 25.12 | 14-OCT-01:00 |
November | 1295.83 | 01-NOV-09:09 | 1228.64 | 06-NOV-16:49 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.40 | 19-NOV-14:00 | 27.14 | 25-NOV-05:00 |
December | 1295.83 | 01-DEC-10:09 | 1228.64 | 01-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.34 | 31-DEC-13:00 | 48.42 | 21-DEC-04:40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 735.93 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 38.34 | 16.90 | |||||
Maximum of Months | 1295.83 | 1228.64 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 153.45 | 168.57 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1524.28 | 02-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 56.45 | 15-JAN-13:00 | 262.81 | 07-JAN-05:00 |
February | 2010.83 | 01-FEB-10:09 | 1215.47 | 01-FEB-17:40 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 122.72 | 19-FEB-14:56 | 27.51 | 09-FEB-23:15 |
March | 2010.83 | 01-MAR-10:09 | 1243.00 | 01-MAR-16:49 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 221.77 | 19-MAR-15:54 | 47.68 | 14-MAR-22:05 |
April | 2010.83 | 03-APR-09:09 | 1141.99 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.91 | 30-APR-15:46 | 19.20 | 22-APR-03:10 |
May | 2010.83 | 01-MAY-09:09 | 1243.00 | 17-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.61 | 07-MAY-14:36 | 82.13 | 08-MAY-21:52 |
June | 2010.83 | 01-JUN-09:09 | 1243.00 | 20-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.83 | 18-JUN-14:26 | 95.27 | 20-JUN-22:55 |
July | 2010.83 | 03-JUL-09:09 | 1243.00 | 07-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.51 | 04-JUL-14:06 | 38.83 | 02-JUL-13:50 |
August | 2010.83 | 01-AUG-09:09 | 1243.00 | 02-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.79 | 06-AUG-12:28 | 74.23 | 20-AUG-11:00 |
September | 2010.83 | 01-SEP-09:09 | 1141.99 | 07-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.66 | 10-SEP-14:51 | 62.20 | 15-SEP-22:00 |
October | 2010.83 | 02-OCT-09:09 | 1243.00 | 23-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.06 | 29-OCT-13:46 | 42.33 | 29-OCT-17:00 |
November | 2010.83 | 01-NOV-09:09 | 1906.57 | 09-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.89 | 19-NOV-13:56 | 42.40 | 25-NOV-05:00 |
December | 2010.83 | 01-DEC-10:09 | 1906.57 | 04-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 50.72 | 31-DEC-12:56 | 77.41 | 21-DEC-04:40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1141.99 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 50.72 | 19.20 | |||||
Maximum of Months | 2010.83 | 1906.57 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 221.77 | 262.81 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 982.28 | 02-JAN-16:00 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 48.92 | 15-JAN-12:40 | 160.07 | 07-JAN-05:00 |
February | 1295.83 | 01-FEB-10:09 | 783.28 | 01-FEB-17:40 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 88.07 | 19-FEB-14:56 | 19.35 | 09-FEB-23:15 |
March | 1295.83 | 01-MAR-10:09 | 801.02 | 13-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 147.85 | 19-MAR-16:00 | 35.91 | 14-MAR-22:05 |
April | 1295.83 | 03-APR-09:09 | 801.02 | 05-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.97 | 02-APR-15:44 | 28.99 | 09-APR-16:20 |
May | 1295.83 | 01-MAY-09:09 | 982.28 | 17-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.96 | 21-MAY-11:50 | 56.66 | 08-MAY-21:52 |
June | 1295.83 | 01-JUN-09:09 | 801.02 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.36 | 18-JUN-14:24 | 69.37 | 20-JUN-22:55 |
July | 1295.83 | 03-JUL-09:09 | 982.28 | 11-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.07 | 04-JUL-14:06 | 36.03 | 02-JUL-13:50 |
August | 1295.83 | 01-AUG-09:09 | 982.28 | 21-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.37 | 06-AUG-12:26 | 56.51 | 20-AUG-11:00 |
September | 1295.83 | 01-SEP-09:09 | 801.02 | 07-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.11 | 10-SEP-14:51 | 43.61 | 15-SEP-22:00 |
October | 1295.83 | 02-OCT-09:09 | 982.28 | 23-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.31 | 29-OCT-13:06 | 31.73 | 29-OCT-17:00 |
November | 1295.83 | 01-NOV-09:09 | 982.28 | 07-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.70 | 11-NOV-15:36 | 32.37 | 26-NOV-06:55 |
December | 1295.83 | 01-DEC-10:09 | 1228.64 | 18-DEC-16:49 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.27 | 31-DEC-12:56 | 57.36 | 21-DEC-04:40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 783.28 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 37.27 | 19.35 | |||||
Maximum of Months | 1295.83 | 1228.64 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 147.85 | 160.07 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1906.53 | 02-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 179.98 | 15-JAN-13:00 | 472.20 | 07-JAN-04:55 |
February | 2010.79 | 01-FEB-10:09 | 1242.97 | 01-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 305.03 | 19-FEB-15:00 | 51.11 | 26-FEB-07:00 |
March | 2010.79 | 01-MAR-10:09 | 1524.25 | 01-MAR-16:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 521.31 | 19-MAR-15:51 | 96.14 | 14-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 1141.96 | 14-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 262.69 | 30-APR-16:00 | 41.42 | 22-APR-02:55 |
May | 2010.79 | 01-MAY-09:09 | 1141.96 | 09-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 370.17 | 07-MAY-14:55 | 171.63 | 08-MAY-22:00 |
June | 2010.79 | 01-JUN-09:09 | 1141.96 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 343.48 | 18-JUN-14:14 | 222.82 | 20-JUN-22:53 |
July | 2010.79 | 03-JUL-09:09 | 1141.96 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 292.80 | 04-JUL-14:18 | 80.10 | 02-JUL-13:30 |
August | 2010.79 | 01-AUG-09:09 | 1141.96 | 02-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 349.20 | 06-AUG-12:52 | 172.17 | 20-AUG-10:53 |
September | 2010.79 | 01-SEP-09:09 | 1141.96 | 07-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 354.82 | 10-SEP-14:51 | 98.67 | 15-SEP-22:00 |
October | 2010.79 | 02-OCT-09:09 | 1242.97 | 11-OCT-15:00 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 338.24 | 29-OCT-12:52 | 79.93 | 22-OCT-17:52 |
November | 2010.79 | 01-NOV-09:09 | 1906.53 | 06-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 178.10 | 11-NOV-16:00 | 83.03 | 26-NOV-10:00 |
December | 2010.79 | 01-DEC-10:09 | 1906.53 | 04-DEC-16:49 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 138.20 | 31-DEC-13:00 | 159.11 | 21-DEC-04:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 138.20 | 41.42 | |||||
Maximum of Months | 2010.79 | 1906.53 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 521.31 | 472.20 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1228.64 | 02-JAN-16:49 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 106.93 | 15-JAN-13:00 | 333.80 | 07-JAN-04:55 |
February | 1239.33 | 01-FEB-08:09 | 982.28 | 01-FEB-16:49 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 212.05 | 19-FEB-15:00 | 45.50 | 26-FEB-07:00 |
March | 1239.33 | 01-MAR-08:09 | 982.28 | 01-MAR-16:49 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 346.36 | 19-MAR-16:05 | 71.03 | 14-MAR-22:00 |
April | 1239.33 | 03-APR-07:10 | 735.93 | 10-APR-15:30 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.34 | 30-APR-16:00 | 32.22 | 23-APR-06:50 |
May | 1239.33 | 01-MAY-07:10 | 735.93 | 02-MAY-15:39 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 266.69 | 07-MAY-14:55 | 116.26 | 08-MAY-22:00 |
June | 1239.33 | 01-JUN-07:10 | 735.93 | 01-JUN-15:50 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 242.78 | 18-JUN-14:14 | 144.41 | 20-JUN-22:53 |
July | 1239.33 | 03-JUL-07:10 | 735.93 | 06-JUL-15:50 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.41 | 04-JUL-14:20 | 47.85 | 02-JUL-13:30 |
August | 1239.33 | 01-AUG-07:10 | 735.93 | 02-AUG-15:50 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 228.76 | 06-AUG-12:54 | 124.15 | 20-AUG-10:50 |
September | 1239.33 | 01-SEP-07:10 | 735.93 | 01-SEP-15:39 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.27 | 10-SEP-14:51 | 65.50 | 15-SEP-22:00 |
October | 1239.33 | 02-OCT-07:10 | 982.28 | 30-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.80 | 29-OCT-14:00 | 53.25 | 22-OCT-17:52 |
November | 1239.33 | 01-NOV-07:10 | 1228.64 | 06-NOV-16:49 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.98 | 11-NOV-16:00 | 63.69 | 26-NOV-10:00 |
December | 1239.33 | 01-DEC-08:09 | 1228.64 | 04-DEC-16:40 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 88.87 | 24-DEC-15:00 | 108.29 | 21-DEC-04:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 735.93 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 88.87 | 32.22 | |||||
Maximum of Months | 1239.33 | 1228.64 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 346.36 | 333.80 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1524.28 | 02-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 128.39 | 15-JAN-13:00 | 548.09 | 07-JAN-04:55 |
February | 2010.83 | 01-FEB-10:09 | 1215.47 | 01-FEB-17:40 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 280.64 | 19-FEB-14:56 | 59.36 | 26-FEB-07:00 |
March | 2010.83 | 01-MAR-10:09 | 1243.00 | 01-MAR-16:49 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 499.63 | 19-MAR-15:51 | 102.67 | 14-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 1141.99 | 05-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 265.33 | 30-APR-16:00 | 39.92 | 22-APR-02:55 |
May | 2010.83 | 01-MAY-09:09 | 1243.00 | 17-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 388.55 | 07-MAY-14:55 | 164.71 | 08-MAY-22:00 |
June | 2010.83 | 01-JUN-09:09 | 1243.00 | 20-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 353.43 | 18-JUN-14:16 | 202.62 | 20-JUN-22:53 |
July | 2010.83 | 03-JUL-09:09 | 1243.00 | 07-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 298.53 | 04-JUL-14:20 | 52.79 | 19-JUL-21:40 |
August | 2010.83 | 01-AUG-09:09 | 1243.00 | 21-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 378.56 | 06-AUG-12:52 | 169.74 | 20-AUG-10:53 |
September | 2010.83 | 01-SEP-09:09 | 1141.99 | 07-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 339.17 | 10-SEP-14:51 | 101.37 | 15-SEP-22:00 |
October | 2010.83 | 02-OCT-09:09 | 1243.00 | 23-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 298.15 | 29-OCT-12:36 | 84.03 | 22-OCT-17:52 |
November | 2010.83 | 01-NOV-09:09 | 1906.57 | 09-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.67 | 11-NOV-15:58 | 99.37 | 26-NOV-10:00 |
December | 2010.83 | 01-DEC-10:09 | 1906.57 | 18-DEC-16:40 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 114.19 | 31-DEC-12:56 | 173.18 | 21-DEC-04:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1141.99 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 114.19 | 39.92 | |||||
Maximum of Months | 2010.83 | 1906.57 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 499.63 | 548.09 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 982.28 | 02-JAN-16:00 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 119.06 | 15-JAN-13:00 | 356.29 | 07-JAN-04:55 |
February | 1295.83 | 01-FEB-10:09 | 783.28 | 01-FEB-17:40 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 203.47 | 19-FEB-14:56 | 40.48 | 09-FEB-24:00 |
March | 1295.83 | 01-MAR-10:09 | 801.02 | 15-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 331.36 | 19-MAR-15:50 | 75.25 | 14-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 801.02 | 14-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.60 | 30-APR-15:54 | 38.12 | 22-APR-02:55 |
May | 1295.83 | 01-MAY-09:09 | 982.28 | 17-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 249.24 | 07-MAY-14:55 | 125.16 | 08-MAY-22:00 |
June | 1295.83 | 01-JUN-09:09 | 801.02 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 231.89 | 18-JUN-14:14 | 159.28 | 20-JUN-22:53 |
July | 1295.83 | 03-JUL-09:09 | 801.02 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 198.03 | 04-JUL-13:40 | 49.98 | 19-JUL-21:40 |
August | 1295.83 | 01-AUG-09:09 | 801.02 | 02-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 257.47 | 06-AUG-12:45 | 121.24 | 20-AUG-10:53 |
September | 1295.83 | 01-SEP-09:09 | 801.02 | 07-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.63 | 10-SEP-14:50 | 73.23 | 15-SEP-22:00 |
October | 1295.83 | 02-OCT-09:09 | 982.28 | 23-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.56 | 29-OCT-13:56 | 58.86 | 22-OCT-17:52 |
November | 1295.83 | 01-NOV-09:09 | 982.28 | 07-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 106.83 | 11-NOV-16:00 | 63.72 | 26-NOV-10:00 |
December | 1295.83 | 01-DEC-10:09 | 1228.64 | 18-DEC-16:49 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 95.28 | 31-DEC-12:40 | 115.30 | 21-DEC-04:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 783.28 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 95.28 | 38.12 | |||||
Maximum of Months | 1295.83 | 1228.64 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 331.36 | 356.29 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1906.53 | 02-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 208.16 | 15-JAN-13:00 | 564.85 | 07-JAN-04:55 |
February | 2010.79 | 01-FEB-10:09 | 1242.97 | 01-FEB-16:00 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 374.71 | 19-FEB-14:58 | 62.64 | 26-FEB-07:00 |
March | 2010.79 | 01-MAR-10:09 | 1524.25 | 01-MAR-16:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 624.84 | 19-MAR-16:05 | 123.02 | 14-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 1141.96 | 14-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 306.73 | 02-APR-15:40 | 53.12 | 22-APR-02:55 |
May | 2010.79 | 01-MAY-09:09 | 1141.96 | 09-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 453.70 | 07-MAY-14:55 | 222.23 | 08-MAY-22:00 |
June | 2010.79 | 01-JUN-09:09 | 1141.96 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 410.63 | 18-JUN-14:14 | 249.41 | 20-JUN-23:00 |
July | 2010.79 | 03-JUL-09:09 | 1141.96 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 361.82 | 04-JUL-14:18 | 121.23 | 02-JUL-14:10 |
August | 2010.79 | 01-AUG-09:09 | 1141.96 | 02-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 414.51 | 06-AUG-12:52 | 209.64 | 20-AUG-10:53 |
September | 2010.79 | 01-SEP-09:09 | 1141.96 | 07-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 400.11 | 10-SEP-14:51 | 121.34 | 15-SEP-22:00 |
October | 2010.79 | 02-OCT-09:09 | 1242.97 | 11-OCT-15:00 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 412.97 | 29-OCT-12:48 | 102.71 | 22-OCT-17:52 |
November | 2010.79 | 01-NOV-09:09 | 1906.53 | 06-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 199.12 | 11-NOV-16:00 | 105.16 | 25-NOV-04:52 |
December | 2010.79 | 01-DEC-10:09 | 1906.53 | 04-DEC-16:49 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 158.40 | 31-DEC-13:00 | 190.24 | 21-DEC-04:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 158.40 | 53.12 | |||||
Maximum of Months | 2010.79 | 1906.53 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 624.84 | 564.85 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1228.64 | 02-JAN-16:49 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 123.28 | 15-JAN-13:00 | 398.60 | 07-JAN-04:55 |
February | 1295.83 | 01-FEB-10:09 | 982.28 | 01-FEB-16:49 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 262.72 | 19-FEB-15:00 | 57.15 | 20-FEB-07:20 |
March | 1295.83 | 01-MAR-10:09 | 982.28 | 01-MAR-16:49 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 430.78 | 19-MAR-16:05 | 90.31 | 14-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 735.93 | 10-APR-15:30 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.02 | 30-APR-15:40 | 41.89 | 23-APR-06:53 |
May | 1295.83 | 01-MAY-09:09 | 735.93 | 02-MAY-15:39 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 331.67 | 07-MAY-14:55 | 150.30 | 08-MAY-22:00 |
June | 1295.83 | 01-JUN-09:09 | 735.93 | 01-JUN-15:50 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 298.46 | 18-JUN-14:36 | 154.52 | 20-JUN-23:00 |
July | 1295.83 | 03-JUL-09:09 | 735.93 | 06-JUL-15:50 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 260.27 | 04-JUL-14:20 | 74.34 | 02-JUL-13:30 |
August | 1295.83 | 01-AUG-09:09 | 735.93 | 02-AUG-15:50 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 272.30 | 06-AUG-12:52 | 151.19 | 20-AUG-10:53 |
September | 1295.83 | 01-SEP-09:09 | 735.93 | 01-SEP-15:39 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 261.83 | 10-SEP-14:51 | 86.73 | 03-SEP-16:00 |
October | 1295.83 | 02-OCT-09:09 | 982.28 | 30-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 293.12 | 29-OCT-12:48 | 68.05 | 22-OCT-17:52 |
November | 1295.83 | 01-NOV-09:09 | 1228.64 | 06-NOV-16:49 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.40 | 11-NOV-16:00 | 79.67 | 26-NOV-10:00 |
December | 1295.83 | 01-DEC-10:09 | 1228.64 | 04-DEC-16:40 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 107.53 | 24-DEC-14:50 | 129.60 | 21-DEC-04:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 735.93 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 107.53 | 41.89 | |||||
Maximum of Months | 1295.83 | 1228.64 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 430.78 | 398.60 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1524.28 | 02-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 154.44 | 15-JAN-13:00 | 651.36 | 07-JAN-04:55 |
February | 2010.83 | 01-FEB-10:09 | 1215.47 | 01-FEB-17:40 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 345.44 | 19-FEB-14:56 | 73.07 | 19-FEB-06:52 |
March | 2010.83 | 01-MAR-10:09 | 1243.00 | 01-MAR-16:00 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 608.64 | 19-MAR-15:50 | 130.90 | 14-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 1141.99 | 05-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.40 | 30-APR-15:40 | 51.22 | 22-APR-02:55 |
May | 2010.83 | 01-MAY-09:09 | 1243.00 | 17-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 470.55 | 07-MAY-14:55 | 214.18 | 08-MAY-22:00 |
June | 2010.83 | 01-JUN-09:09 | 1243.00 | 20-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 435.37 | 18-JUN-14:36 | 223.66 | 20-JUN-23:00 |
July | 2010.83 | 03-JUL-09:09 | 1243.00 | 07-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 368.34 | 04-JUL-14:20 | 91.25 | 02-JUL-13:30 |
August | 2010.83 | 01-AUG-09:09 | 1243.00 | 21-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 451.07 | 06-AUG-12:52 | 206.60 | 20-AUG-10:53 |
September | 2010.83 | 01-SEP-09:09 | 1141.99 | 07-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 397.24 | 10-SEP-14:51 | 124.60 | 15-SEP-22:00 |
October | 2010.83 | 02-OCT-09:09 | 1243.00 | 23-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 379.15 | 29-OCT-12:46 | 119.42 | 29-OCT-17:20 |
November | 2010.83 | 01-NOV-09:09 | 1906.57 | 09-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.32 | 11-NOV-15:58 | 124.26 | 26-NOV-10:00 |
December | 2010.83 | 01-DEC-10:09 | 1906.57 | 18-DEC-16:40 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 138.80 | 31-DEC-12:56 | 207.39 | 21-DEC-04:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1141.99 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 138.80 | 51.22 | |||||
Maximum of Months | 2010.83 | 1906.57 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 608.64 | 651.36 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 982.28 | 02-JAN-16:00 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 144.54 | 15-JAN-12:40 | 426.23 | 07-JAN-04:55 |
February | 1295.83 | 01-FEB-10:09 | 783.28 | 01-FEB-17:40 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 252.78 | 19-FEB-14:56 | 50.33 | 09-FEB-24:00 |
March | 1295.83 | 01-MAR-10:09 | 801.02 | 15-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 405.76 | 19-MAR-15:50 | 95.06 | 14-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 801.02 | 14-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.91 | 30-APR-15:33 | 47.87 | 22-APR-02:55 |
May | 1295.83 | 01-MAY-09:09 | 982.28 | 17-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 303.57 | 07-MAY-14:55 | 160.17 | 08-MAY-22:00 |
June | 1295.83 | 01-JUN-09:09 | 801.02 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 289.41 | 18-JUN-13:56 | 166.97 | 20-JUN-23:00 |
July | 1295.83 | 03-JUL-09:09 | 801.02 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 249.43 | 04-JUL-14:18 | 77.07 | 02-JUL-14:10 |
August | 1295.83 | 01-AUG-09:09 | 801.02 | 02-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 318.96 | 06-AUG-12:45 | 148.25 | 20-AUG-10:53 |
September | 1295.83 | 01-SEP-09:09 | 801.02 | 07-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 256.36 | 10-SEP-14:50 | 89.17 | 15-SEP-22:00 |
October | 1295.83 | 02-OCT-09:09 | 982.28 | 23-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 296.78 | 29-OCT-12:48 | 80.07 | 29-OCT-17:20 |
November | 1295.83 | 01-NOV-09:09 | 982.28 | 07-NOV-16:00 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.55 | 11-NOV-16:00 | 79.67 | 26-NOV-10:00 |
December | 1295.83 | 01-DEC-10:09 | 1228.64 | 18-DEC-16:49 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 113.88 | 31-DEC-12:40 | 138.18 | 21-DEC-04:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 783.28 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 113.88 | 47.87 | |||||
Maximum of Months | 1295.83 | 1228.64 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 405.76 | 426.23 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 5470.56 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 5470.56 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 5470.56 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 5470.56 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 5470.56 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 5470.56 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 5470.56 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 5470.56 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 5470.56 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 5470.56 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 5470.56 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 5470.56 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 5470.56 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.96 | 15-JAN-13:00 | 502.24 | 07-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.05 | 26-FEB-16:00 | 55.77 | 20-FEB-06:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.66 | 19-MAR-16:00 | 88.76 | 03-MAR-04:55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.90 | 02-APR-15:30 | 37.94 | 22-APR-03:10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.01 | 07-MAY-15:00 | 164.69 | 08-MAY-21:56 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.42 | 18-JUN-14:10 | 172.17 | 20-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.82 | 04-JUL-13:52 | 55.93 | 19-JUL-21:20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.41 | 06-AUG-12:52 | 135.61 | 20-AUG-11:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.46 | 10-SEP-15:00 | 104.12 | 15-SEP-22:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.09 | 29-OCT-12:52 | 70.77 | 22-OCT-17:54 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.76 | 19-NOV-14:00 | 83.89 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.02 | 24-DEC-15:00 | 161.72 | 21-DEC-04:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.02 | 37.94 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419.66 | 502.24 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.46 | 15-JAN-13:00 | 826.61 | 07-JAN-04:55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 485.64 | 19-FEB-15:00 | 72.72 | 26-FEB-07:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 866.54 | 19-MAR-15:51 | 139.48 | 03-MAR-05:12 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 434.50 | 30-APR-15:40 | 58.20 | 22-APR-02:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 619.35 | 07-MAY-15:00 | 232.21 | 08-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 571.89 | 18-JUN-14:30 | 257.25 | 20-JUN-22:53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 502.99 | 04-JUL-14:00 | 87.32 | 19-JUL-21:20 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 614.16 | 06-AUG-13:00 | 203.86 | 20-AUG-11:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 611.79 | 10-SEP-14:51 | 152.29 | 15-SEP-22:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 550.14 | 29-OCT-13:00 | 103.96 | 22-OCT-17:52 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.73 | 11-NOV-16:00 | 134.84 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.02 | 31-DEC-13:00 | 272.41 | 21-DEC-04:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.02 | 58.20 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 866.54 | 826.61 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.92 | 15-JAN-13:00 | 847.18 | 07-JAN-04:55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 434.91 | 19-FEB-15:00 | 77.84 | 20-FEB-06:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 769.04 | 19-MAR-15:51 | 157.78 | 14-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 374.29 | 09-APR-15:00 | 67.08 | 22-APR-03:04 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 645.11 | 21-MAY-11:50 | 292.58 | 08-MAY-22:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 517.92 | 18-JUN-14:10 | 348.78 | 20-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 423.17 | 04-JUL-14:00 | 143.36 | 02-JUL-13:30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 674.80 | 06-AUG-12:52 | 260.44 | 20-AUG-10:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.45 | 10-SEP-14:51 | 147.22 | 03-SEP-16:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.12 | 29-OCT-13:00 | 134.14 | 22-OCT-17:52 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.28 | 11-NOV-16:00 | 154.63 | 25-NOV-04:52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.26 | 31-DEC-13:00 | 287.56 | 21-DEC-04:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.26 | 67.08 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 769.04 | 847.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 103797.89 | 17-JAN-06:31 | 14361.80 | 17246.94 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 89011.77 | 24-FEB-09:00 | 17054.64 | 19402.09 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 01-MAR-00:03 | 0.00 | 4311.25 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 83648.02 | 14-APR-21:00 | 1795.23 | 4311.49 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 76472.01 | 10-MAY-20:50 | 3590.45 | 8622.99 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 01-JUN-00:03 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 01-JUL-00:03 | 0.00 | 2393.40 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 01-AUG-00:03 | 0.00 | 2393.40 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 01-SEP-00:05 | 0.00 | 1196.70 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 01-OCT-00:03 | 0.00 | 2393.40 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 90277.47 | 25-NOV-07:30 | 1795.23 | 2155.87 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 103452.00 | 21-DEC-00:10 | 0.00 | 5389.07 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 0.00 | 0.00 | 1196.70 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 103797.89 | 17054.64 | 19402.09 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 97507.56 | 24-JAN-05:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 97216.34 | 09-FEB-05:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 89585.75 | 27-MAR-05:05 | 9673.43 | 3224.16 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 95611.90 | 24-APR-04:04 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 94479.35 | 01-MAY-04:24 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 89275.80 | 19-JUN-05:03 | 9673.43 | 3224.16 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 95666.80 | 22-JUL-04:14 | 0.00 | 2686.80 | 22266.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 95358.30 | 28-AUG-04:24 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 93056.17 | 19-SEP-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 97497.11 | 27-OCT-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 98627.17 | 25-NOV-05:13 | 0.00 | 3224.16 | 26719.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 98675.82 | 27-DEC-05:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 89275.80 | 0.00 | 2686.80 | 22266.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 98675.82 | 9673.43 | 3761.52 | 45884.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 84378.88 | 24-JAN-05:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 82318.92 | 08-FEB-04:32 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 81929.52 | 03-MAR-04:02 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 71332.40 | 15-APR-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 81536.13 | 26-MAY-04:03 | 0.00 | 2149.44 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 78758.82 | 01-JUN-03:22 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 80425.19 | 07-JUL-03:02 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 82685.09 | 21-AUG-03:02 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 82159.08 | 16-SEP-04:12 | 0.00 | 2686.80 | 22266.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 82886.17 | 23-OCT-05:04 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 82180.90 | 27-NOV-05:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 83951.60 | 15-DEC-05:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 71332.40 | 0.00 | 2149.44 | 22266.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 84378.88 | 8061.19 | 3224.16 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 82690.84 | 24-JAN-05:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 83664.03 | 03-FEB-05:13 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 80063.58 | 02-MAR-05:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 78795.47 | 14-APR-03:02 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 82613.43 | 17-MAY-03:02 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 80881.47 | 22-JUN-03:02 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 82532.67 | 07-JUL-03:02 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 82992.67 | 21-AUG-03:02 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 81968.88 | 29-SEP-03:02 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 83158.53 | 18-OCT-03:02 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 83442.51 | 27-NOV-05:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 82237.63 | 27-DEC-05:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 78795.47 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 83664.03 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18264.80 | 08-JAN-15:12 | 607.30 | 346.96 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.05 | 0.00 |
February | 18650.84 | 26-FEB-15:01 | 708.51 | 404.79 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 98.32 | 0.00 |
March | 18336.93 | 19-MAR-15:01 | 708.51 | 404.79 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 177.24 | 0.00 |
April | 18665.94 | 09-APR-10:22 | 607.30 | 346.96 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.04 | 0.00 |
May | 19803.24 | 29-MAY-15:31 | 708.51 | 404.79 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 18.88 | 0.00 |
June | 20265.73 | 18-JUN-15:41 | 809.73 | 462.61 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 72.84 | 0.00 |
July | 19179.67 | 09-JUL-14:22 | 506.08 | 289.13 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 53.62 | 0.00 |
August | 18911.45 | 13-AUG-11:02 | 506.08 | 289.13 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 66.91 | 0.00 |
September | 18825.13 | 04-SEP-15:12 | 607.30 | 346.96 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.47 | 0.00 |
October | 18589.15 | 29-OCT-13:42 | 506.08 | 289.13 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 98.59 | 0.00 |
November | 18530.82 | 05-NOV-13:52 | 506.08 | 289.13 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 17.38 | 0.00 |
December | 18168.34 | 24-DEC-13:52 | 607.30 | 346.96 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.23 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18168.34 | 506.08 | 289.13 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 17.38 | 0.00 | |
Maximum of Months | 20265.73 | 809.73 | 462.61 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 177.24 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17743.42 | 16-JAN-08:43 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.31 |
February | 17751.08 | 20-FEB-09:22 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 9.15 | 0.00 |
March | 18047.25 | 19-MAR-09:02 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 37.46 | 0.00 |
April | 19005.32 | 09-APR-10:22 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 21.47 | 0.00 |
May | 19248.01 | 28-MAY-09:42 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 23.84 | 0.00 |
June | 19121.57 | 18-JUN-09:42 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 41.11 | 0.00 |
July | 17591.90 | 09-JUL-14:22 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 41.74 | 0.00 |
August | 18488.75 | 27-AUG-08:22 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 9.42 | 0.00 |
September | 18449.64 | 10-SEP-10:32 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 17.07 | 0.00 |
October | 17818.88 | 08-OCT-12:32 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 20.65 | 0.00 |
November | 17626.47 | 11-NOV-07:33 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.84 |
December | 17543.43 | 10-DEC-09:32 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 2.58 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17543.43 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19248.01 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 41.74 | 7.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19698.49 | 08-JAN-14:32 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 26.49 | 0.00 |
February | 19461.69 | 26-FEB-15:01 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 83.59 | 0.00 |
March | 18158.55 | 05-MAR-11:53 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 33.83 | 0.00 |
April | 17848.73 | 09-APR-11:42 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 53.38 | 0.00 |
May | 18419.11 | 29-MAY-15:31 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 20.69 | 0.00 |
June | 18459.19 | 18-JUN-14:21 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 124.14 | 0.00 |
July | 18036.15 | 09-JUL-14:22 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 59.19 | 0.00 |
August | 17839.59 | 13-AUG-11:02 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 71.42 | 0.00 |
September | 18203.18 | 04-SEP-15:12 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 59.56 | 0.00 |
October | 19115.19 | 29-OCT-11:42 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 72.48 | 0.00 |
November | 19037.84 | 05-NOV-13:52 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 13.27 | 0.00 |
December | 19689.35 | 24-DEC-13:52 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 20.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17839.59 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 13.27 | 0.00 | |
Maximum of Months | 19698.49 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 124.14 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 24677.47 | 29-JAN-16:02 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 25.86 | 0.00 |
February | 25773.29 | 26-FEB-15:01 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 54.52 | 0.00 |
March | 24813.17 | 19-MAR-15:01 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 104.28 | 0.00 |
April | 25104.87 | 02-APR-15:41 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 55.15 | 0.00 |
May | 25327.07 | 29-MAY-15:31 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 12.37 | 0.00 |
June | 26192.75 | 18-JUN-15:41 | 521.82 | 298.13 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 45.99 | 0.00 |
July | 24699.31 | 04-JUL-16:01 | 521.82 | 298.13 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 41.27 | 0.00 |
August | 24950.28 | 27-AUG-15:41 | 521.82 | 298.13 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 48.78 | 0.00 |
September | 25377.28 | 04-SEP-15:51 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 36.42 | 0.00 |
October | 23591.66 | 29-OCT-15:02 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 33.85 | 0.00 |
November | 23555.05 | 05-NOV-13:52 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 11.54 | 0.00 |
December | 24568.73 | 24-DEC-13:52 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 17.06 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 23555.05 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 11.54 | 0.00 | |
Maximum of Months | 26192.75 | 521.82 | 298.13 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 104.28 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13432.98 | 03-JAN-04:02 | 0.00 | 337.35 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.09 |
February | 17180.65 | 26-FEB-15:11 | 708.51 | 404.79 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 242.92 | 0.00 |
March | 13743.57 | 13-MAR-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 3.80 | 0.00 |
April | 16886.69 | 02-APR-15:31 | 1012.16 | 578.27 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 240.74 | 0.00 |
May | 18225.25 | 14-MAY-15:01 | 708.51 | 404.79 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 101.36 | 0.00 |
June | 18481.04 | 11-JUN-17:11 | 0.00 | 404.79 | 3914.20 | 0.00 | 0.00 | 0.00 | 0.00 | 136.96 | 0.00 |
July | 17456.97 | 04-JUL-16:12 | 607.30 | 346.96 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.79 | 0.00 |
August | 15700.72 | 15-AUG-03:02 | 0.00 | 337.35 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 15.74 | 0.00 |
September | 17035.49 | 10-SEP-15:01 | 708.51 | 404.79 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 254.45 | 0.00 |
October | 14640.26 | 10-OCT-03:02 | 0.00 | 337.35 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.41 |
November | 13445.79 | 13-NOV-04:02 | 0.00 | 337.35 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.49 |
December | 13362.56 | 12-DEC-05:12 | 0.00 | 337.35 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13362.56 | 0.00 | 269.88 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18481.04 | 1012.16 | 578.27 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 254.45 | 14.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13360.93 | 02-JAN-05:12 | 0.00 | 260.89 | 2882.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.99 |
February | 17914.36 | 26-FEB-15:11 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 161.27 | 0.00 |
March | 18404.77 | 05-MAR-11:02 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 70.69 | 0.00 |
April | 18777.45 | 16-APR-10:02 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 50.61 | 0.00 |
May | 19344.00 | 14-MAY-09:42 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 58.76 | 0.00 |
June | 18868.73 | 11-JUN-09:12 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 106.70 | 0.00 |
July | 13339.77 | 20-JUL-04:12 | 0.00 | 260.89 | 2882.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.72 |
August | 18157.16 | 13-AUG-08:32 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 66.23 | 0.00 |
September | 18705.21 | 10-SEP-10:22 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 47.53 | 0.00 |
October | 18756.36 | 08-OCT-09:22 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 21.43 | 0.00 |
November | 17481.26 | 23-NOV-09:13 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 30.61 | 0.00 |
December | 17441.16 | 31-DEC-09:53 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 56.87 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13339.77 | 0.00 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19344.00 | 456.59 | 260.89 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 161.27 | 5.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18579.70 | 08-JAN-14:42 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 64.60 | 0.00 |
February | 18296.37 | 26-FEB-15:11 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 195.54 | 0.00 |
March | 16990.38 | 05-MAR-16:21 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 70.68 | 0.00 |
April | 16318.39 | 02-APR-15:31 | 1012.19 | 578.28 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 238.73 | 0.00 |
May | 16707.42 | 14-MAY-15:01 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 111.44 | 0.00 |
June | 16417.52 | 11-JUN-17:11 | 0.00 | 483.35 | 3914.26 | 0.00 | 0.00 | 0.00 | 0.00 | 173.38 | 0.00 |
July | 15134.20 | 24-JUL-03:02 | 0.00 | 337.36 | 3727.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.93 | 0.00 |
August | 13541.04 | 11-AUG-03:02 | 0.00 | 337.36 | 3727.86 | 0.00 | 0.00 | 0.00 | 0.00 | 6.16 | 0.00 |
September | 16759.22 | 10-SEP-15:01 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 236.26 | 0.00 |
October | 18018.08 | 29-OCT-12:32 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 200.48 | 0.00 |
November | 17922.36 | 05-NOV-11:42 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 76.91 | 0.00 |
December | 17656.94 | 31-DEC-13:12 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 83.98 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13541.04 | 0.00 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.93 | 0.00 | |
Maximum of Months | 18579.70 | 1012.19 | 578.28 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 238.73 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21272.88 | 08-JAN-15:22 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 56.15 | 0.00 |
February | 22322.95 | 26-FEB-15:51 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 130.68 | 0.00 |
March | 21988.82 | 05-MAR-16:21 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 20.10 | 0.00 |
April | 21613.83 | 02-APR-16:11 | 652.28 | 372.66 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 119.13 | 0.00 |
May | 22086.11 | 14-MAY-15:01 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 61.76 | 0.00 |
June | 22221.54 | 11-JUN-17:11 | 0.00 | 260.86 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 80.95 | 0.00 |
July | 20891.98 | 04-JUL-16:12 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 101.68 | 0.00 |
August | 20824.94 | 27-AUG-16:02 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 121.24 | 0.00 |
September | 22063.17 | 10-SEP-15:01 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 108.99 | 0.00 |
October | 20614.23 | 29-OCT-15:52 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 65.05 | 0.00 |
November | 20736.31 | 19-NOV-16:52 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 26.23 | 0.00 |
December | 20389.10 | 25-DEC-15:52 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 38.09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 20389.10 | 0.00 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 20.10 | 0.00 | |
Maximum of Months | 22322.95 | 652.28 | 372.66 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 130.68 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14883.55 | 27-JAN-05:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.19 |
February | 17587.01 | 26-FEB-15:22 | 607.30 | 346.96 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.71 | 0.00 |
March | 18864.03 | 26-MAR-15:41 | 708.51 | 404.79 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 346.99 | 0.00 |
April | 19231.97 | 02-APR-15:31 | 1012.16 | 578.27 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 278.57 | 0.00 |
May | 20645.01 | 14-MAY-15:01 | 708.51 | 404.79 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 117.89 | 0.00 |
June | 20091.62 | 04-JUN-14:12 | 506.08 | 289.13 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 96.15 | 0.00 |
July | 19306.82 | 04-JUL-16:12 | 607.30 | 346.96 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 200.12 | 0.00 |
August | 19884.33 | 27-AUG-15:11 | 708.51 | 404.79 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 203.80 | 0.00 |
September | 19558.47 | 04-SEP-15:51 | 708.51 | 404.79 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 195.39 | 0.00 |
October | 18728.50 | 08-OCT-14:12 | 506.08 | 289.13 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 116.89 | 0.00 |
November | 15099.84 | 05-NOV-13:42 | 506.08 | 289.13 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 51.27 | 0.00 |
December | 14722.52 | 26-DEC-05:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14722.52 | 0.00 | 289.13 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20645.01 | 1012.16 | 578.27 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 346.99 | 62.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13648.97 | 02-JAN-05:12 | 0.00 | 260.89 | 2882.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.35 |
February | 15978.21 | 20-FEB-10:02 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 48.03 | 0.00 |
March | 18728.33 | 05-MAR-11:02 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 81.97 | 0.00 |
April | 19644.62 | 30-APR-10:12 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 62.67 | 0.00 |
May | 19669.25 | 14-MAY-09:42 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 68.28 | 0.00 |
June | 19156.78 | 18-JUN-10:32 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 128.64 | 0.00 |
July | 14282.04 | 30-JUL-14:22 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 150.03 | 0.00 |
August | 19275.40 | 27-AUG-09:52 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 62.49 | 0.00 |
September | 18998.47 | 10-SEP-10:22 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 55.18 | 0.00 |
October | 18192.63 | 08-OCT-10:53 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 59.62 | 0.00 |
November | 18093.11 | 05-NOV-11:02 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 84.62 | 0.00 |
December | 17675.42 | 31-DEC-09:53 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 68.52 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13648.97 | 0.00 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19669.25 | 391.37 | 260.89 | 2882.81 | 0.00 | 0.00 | 0.00 | 0.00 | 150.03 | 7.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20007.16 | 22-JAN-16:12 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 15.01 | 0.00 |
February | 19438.95 | 26-FEB-12:02 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 81.01 | 0.00 |
March | 19041.21 | 05-MAR-16:21 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 68.93 | 0.00 |
April | 18618.74 | 02-APR-15:31 | 1012.19 | 578.28 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 277.44 | 0.00 |
May | 19185.01 | 14-MAY-15:01 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 128.31 | 0.00 |
June | 18550.12 | 04-JUN-14:12 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 108.05 | 0.00 |
July | 15887.70 | 24-JUL-03:02 | 0.00 | 337.36 | 3727.86 | 0.00 | 0.00 | 0.00 | 0.00 | 1.11 | 0.00 |
August | 18934.18 | 27-AUG-15:11 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 213.51 | 0.00 |
September | 19140.73 | 10-SEP-15:01 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 258.55 | 0.00 |
October | 20053.35 | 29-OCT-12:42 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 240.30 | 0.00 |
November | 19934.90 | 05-NOV-11:42 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 89.28 | 0.00 |
December | 19617.63 | 31-DEC-13:12 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 101.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15887.70 | 0.00 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 1.11 | 0.00 | |
Maximum of Months | 20053.35 | 1012.19 | 578.28 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 277.44 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21982.99 | 22-JAN-16:12 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 16.15 | 0.00 |
February | 21851.37 | 26-FEB-15:22 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 190.24 | 0.00 |
March | 23385.27 | 05-MAR-16:21 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 13.96 | 0.00 |
April | 23196.40 | 02-APR-15:31 | 652.28 | 372.66 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 152.90 | 0.00 |
May | 23815.70 | 14-MAY-15:01 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 72.09 | 0.00 |
June | 22076.63 | 11-JUN-16:02 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 155.58 | 0.00 |
July | 22094.83 | 04-JUL-16:12 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 118.42 | 0.00 |
August | 23795.37 | 27-AUG-15:11 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 102.84 | 0.00 |
September | 23821.07 | 04-SEP-15:51 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 97.70 | 0.00 |
October | 21890.11 | 08-OCT-14:12 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 67.56 | 0.00 |
November | 21983.84 | 19-NOV-16:52 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 28.98 | 0.00 |
December | 21598.52 | 25-DEC-15:52 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 45.42 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 21598.52 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 13.96 | 0.00 | |
Maximum of Months | 23821.07 | 652.28 | 372.66 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 190.24 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15202.33 | 18-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.77 |
February | 19496.78 | 21-FEB-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 19652.36 | 27-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.11 |
April | 19646.61 | 03-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.22 | 0.00 |
May | 20213.99 | 01-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.95 | 0.00 |
June | 20051.30 | 19-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.26 | 0.00 |
July | 18012.78 | 10-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.82 |
August | 19165.24 | 14-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
September | 15825.09 | 05-SEP-10:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.98 | 0.00 |
October | 17397.59 | 10-OCT-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.11 |
November | 18260.21 | 13-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.47 |
December | 16578.68 | 26-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 15202.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20213.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.98 | 12.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11032.04 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11250.77 | 28-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
March | 9466.46 | 08-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.93 |
April | 9025.95 | 12-APR-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.48 | 0.00 |
May | 9925.19 | 16-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.87 |
June | 11431.54 | 27-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.95 |
July | 9038.70 | 28-JUL-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.87 | 0.00 |
August | 9588.72 | 26-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.14 |
September | 10944.77 | 09-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.19 |
October | 9626.63 | 07-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.93 |
November | 11025.07 | 18-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.99 |
December | 9825.07 | 06-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9025.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11431.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.48 | 14.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19250.03 | 04-JAN-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.76 | 0.00 |
February | 19658.05 | 24-FEB-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.63 | 0.00 |
March | 21414.49 | 29-MAR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.84 | 0.00 |
April | 23544.63 | 12-APR-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.22 | 0.00 |
May | 21343.20 | 02-MAY-12:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.10 | 0.00 |
June | 20491.36 | 13-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.42 | 0.00 |
July | 19419.69 | 14-JUL-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.64 | 0.00 |
August | 21914.94 | 28-AUG-13:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.92 | 0.00 |
September | 18884.23 | 06-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.91 | 0.00 |
October | 19690.71 | 04-OCT-12:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.89 | 0.00 |
November | 18155.75 | 15-NOV-12:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.62 | 0.00 |
December | 17636.58 | 08-DEC-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 17636.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.64 | 0.00 | |
Maximum of Months | 23544.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.42 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2400.12 | 16-JAN-17:40 | 23.38 | 50.02 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4242.32 | 20-FEB-17:40 | 23.38 | 50.02 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7402.62 | 31-MAR-23:33 | 0.00 | 100.03 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7888.83 | 09-APR-16:12 | 46.77 | 100.03 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3625.52 | 31-MAY-24:00 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5485.67 | 30-JUN-23:45 | 0.00 | 100.03 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7403.15 | 31-JUL-24:00 | 0.00 | 50.02 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7889.54 | 06-AUG-16:38 | 46.77 | 100.03 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3622.51 | 30-SEP-23:45 | 0.00 | 100.03 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5487.58 | 31-OCT-23:50 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6107.44 | 19-NOV-16:54 | 58.46 | 125.04 | 29229.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7985.22 | 03-DEC-17:20 | 11.69 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2400.12 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7985.22 | 58.46 | 125.04 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2032.82 | 16-JAN-17:40 | 23.38 | 50.02 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3864.17 | 24-FEB-17:00 | 222.14 | 450.11 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7000.05 | 31-MAR-23:45 | 0.00 | 100.03 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7351.77 | 23-APR-18:00 | 0.00 | 175.05 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3447.64 | 31-MAY-24:00 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5116.65 | 30-JUN-24:00 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7002.51 | 31-JUL-24:00 | 0.00 | 50.02 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7318.47 | 13-AUG-17:22 | 0.00 | 150.05 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3342.97 | 30-SEP-23:45 | 0.00 | 100.03 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5129.66 | 31-OCT-23:53 | 0.00 | 100.03 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5663.96 | 20-NOV-17:00 | 222.14 | 450.11 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7486.73 | 15-DEC-17:00 | 222.14 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2032.82 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7486.73 | 222.14 | 450.11 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2204.71 | 16-JAN-17:40 | 23.38 | 50.02 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3954.03 | 24-FEB-17:00 | 222.14 | 450.11 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7012.00 | 31-MAR-23:45 | 0.00 | 100.03 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7526.78 | 23-APR-18:00 | 0.00 | 175.05 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3458.26 | 31-MAY-24:00 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5039.61 | 30-JUN-24:00 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7003.78 | 31-JUL-24:00 | 0.00 | 50.02 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7543.92 | 13-AUG-17:40 | 0.00 | 175.05 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3375.47 | 30-SEP-23:20 | 0.00 | 75.02 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5111.95 | 31-OCT-23:53 | 0.00 | 100.03 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5741.20 | 20-NOV-17:00 | 222.14 | 450.11 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7566.79 | 25-DEC-17:00 | 11.69 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2204.71 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7566.79 | 222.14 | 450.11 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 95553.87 | 05-JAN-17:00 | 4808.68 | 5470.56 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 187186.25 | 17-FEB-16:43 | 14426.04 | 16411.67 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 362303.28 | 31-MAR-24:00 | 0.00 | 607.79 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 370958.17 | 03-APR-16:00 | 4808.68 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 179062.63 | 31-MAY-24:00 | 0.00 | 303.90 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 270689.50 | 30-JUN-24:00 | 0.00 | 303.90 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 362653.18 | 31-JUL-24:00 | 0.00 | 607.79 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 371309.03 | 28-AUG-16:00 | 4808.68 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 178462.61 | 30-SEP-23:57 | 0.00 | 911.69 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 270420.85 | 31-OCT-23:53 | 0.00 | 1215.59 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 279063.48 | 20-NOV-17:00 | 4808.68 | 5470.56 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 371023.74 | 07-DEC-17:00 | 4808.68 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 95553.87 | 0.00 | 303.90 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 371309.03 | 14426.04 | 16411.67 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [] | NATURALGAS:FACILITY [] | |
January | 0.219248E+13 | 1575515.90 | 05-JAN-16:00 | 0.00 | 0.00 |
February | 0.239418E+13 | 1755558.54 | 24-FEB-16:19 | 0.00 | 0.00 |
March | 0.315588E+13 | 1911880.35 | 29-MAR-15:30 | 0.00 | 0.00 |
April | 0.345082E+13 | 2056644.88 | 21-APR-15:00 | 0.00 | 0.00 |
May | 0.236229E+13 | 1588672.35 | 30-MAY-10:00 | 0.00 | 0.00 |
June | 0.273597E+13 | 1741942.75 | 13-JUN-15:50 | 0.00 | 0.00 |
July | 0.306542E+13 | 1891055.21 | 14-JUL-15:20 | 0.00 | 0.00 |
August | 0.360423E+13 | 2068653.65 | 22-AUG-15:20 | 0.00 | 0.00 |
September | 0.220264E+13 | 1566771.70 | 01-SEP-15:00 | 0.00 | 0.00 |
October | 0.266224E+13 | 1734629.75 | 17-OCT-15:20 | 0.00 | 0.00 |
November | 0.298218E+13 | 1887507.80 | 03-NOV-15:09 | 0.00 | 0.00 |
December | 0.342136E+13 | 2043569.73 | 08-DEC-16:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.342297E+14 | 0.00 | 0.00 | ||
Minimum of Months | 0.219248E+13 | 1566771.70 | 0.00 | 0.00 | |
Maximum of Months | 0.360423E+13 | 2068653.65 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.268892E+12 | 0.317218E+11 | 0.766053E+12 | 0.213342E+12 | 0.205928E+12 | 0.697921E+11 | 0.00 | 0.401130E+12 | 0.200964E+12 | 0.00 | 0.101767E+11 | 0.244833E+11 | 0.00 |
February | 0.243553E+12 | 0.278446E+11 | 0.978954E+12 | 0.195333E+12 | 0.190996E+12 | 0.685104E+11 | 0.00 | 0.468800E+12 | 0.188382E+12 | 0.00 | 0.970063E+10 | 0.221057E+11 | 0.00 |
March | 0.288903E+12 | 0.290988E+11 | 0.141687E+13 | 0.226058E+12 | 0.213338E+12 | 0.802069E+11 | 0.00 | 0.643343E+12 | 0.220797E+12 | 0.00 | 0.116886E+11 | 0.255782E+11 | 0.00 |
April | 0.256667E+12 | 0.269076E+11 | 0.165903E+13 | 0.211502E+12 | 0.203877E+12 | 0.824087E+11 | 0.00 | 0.746530E+12 | 0.229660E+12 | 0.00 | 0.115051E+11 | 0.227359E+11 | 0.00 |
May | 0.277544E+12 | 0.268926E+11 | 0.774844E+12 | 0.219700E+12 | 0.208547E+12 | 0.867459E+11 | 0.00 | 0.496054E+12 | 0.236848E+12 | 0.00 | 0.113519E+11 | 0.237630E+11 | 0.00 |
June | 0.276016E+12 | 0.256283E+11 | 0.106252E+13 | 0.217935E+12 | 0.209523E+12 | 0.886301E+11 | 0.00 | 0.589687E+12 | 0.231539E+12 | 0.00 | 0.112764E+11 | 0.232140E+11 | 0.00 |
July | 0.257878E+12 | 0.269438E+11 | 0.139340E+13 | 0.213266E+12 | 0.201449E+12 | 0.791280E+11 | 0.00 | 0.633026E+12 | 0.227272E+12 | 0.00 | 0.110636E+11 | 0.219916E+11 | 0.00 |
August | 0.288191E+12 | 0.274541E+11 | 0.173200E+13 | 0.226058E+12 | 0.207673E+12 | 0.866684E+11 | 0.00 | 0.765270E+12 | 0.235419E+12 | 0.00 | 0.112949E+11 | 0.242039E+11 | 0.00 |
September | 0.257438E+12 | 0.277901E+11 | 0.740713E+12 | 0.211501E+12 | 0.192953E+12 | 0.781907E+11 | 0.00 | 0.438682E+12 | 0.222535E+12 | 0.00 | 0.104939E+11 | 0.223405E+11 | 0.00 |
October | 0.267758E+12 | 0.301284E+11 | 0.108340E+13 | 0.213342E+12 | 0.196778E+12 | 0.781483E+11 | 0.00 | 0.531368E+12 | 0.227213E+12 | 0.00 | 0.105575E+11 | 0.235413E+11 | 0.00 |
November | 0.266392E+12 | 0.306961E+11 | 0.135889E+13 | 0.205296E+12 | 0.197604E+12 | 0.754595E+11 | 0.00 | 0.598642E+12 | 0.215395E+12 | 0.00 | 0.102378E+11 | 0.235672E+11 | 0.00 |
December | 0.260526E+12 | 0.321057E+11 | 0.170972E+13 | 0.213266E+12 | 0.203777E+12 | 0.752933E+11 | 0.00 | 0.681347E+12 | 0.211058E+12 | 0.00 | 0.104516E+11 | 0.238120E+11 | 0.00 |
Annual Sum or Average | 0.320976E+13 | 0.343212E+12 | 0.146764E+14 | 0.256660E+13 | 0.243244E+13 | 0.949182E+12 | 0.00 | 0.699388E+13 | 0.264708E+13 | 0.00 | 0.129799E+12 | 0.281337E+12 | 0.00 |
Minimum of Months | 0.243553E+12 | 0.256283E+11 | 0.740713E+12 | 0.195333E+12 | 0.190996E+12 | 0.685104E+11 | 0.00 | 0.401130E+12 | 0.188382E+12 | 0.00 | 0.970063E+10 | 0.219916E+11 | 0.00 |
Maximum of Months | 0.288903E+12 | 0.321057E+11 | 0.173200E+13 | 0.226058E+12 | 0.213338E+12 | 0.886301E+11 | 0.00 | 0.765270E+12 | 0.236848E+12 | 0.00 | 0.116886E+11 | 0.255782E+11 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 307068.14 | 02-JAN-16:00 | 40855.88 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 233416.05 | 02-JAN-08:20 | 156830.23 | 05-JAN-15:20 | 64678.91 | 20-JAN-10:50 | 0.00 | 01-JAN-00:10 |
February | 287824.19 | 01-FEB-16:00 | 40855.88 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 233415.40 | 06-FEB-08:20 | 189055.09 | 15-FEB-16:10 | 69566.52 | 14-FEB-13:50 | 0.00 | 01-FEB-00:10 |
March | 293192.71 | 01-MAR-16:00 | 40855.88 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 233417.11 | 15-MAR-07:19 | 163932.46 | 29-MAR-15:30 | 59876.95 | 28-MAR-10:00 | 0.00 | 01-MAR-00:10 |
April | 284436.93 | 14-APR-07:10 | 40855.88 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 233417.11 | 14-APR-07:19 | 195785.44 | 12-APR-13:30 | 69571.82 | 25-APR-13:39 | 0.00 | 01-APR-00:10 |
May | 287824.21 | 17-MAY-07:10 | 40855.88 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 233418.92 | 17-MAY-07:19 | 192313.80 | 12-MAY-14:39 | 69572.26 | 18-MAY-11:30 | 0.00 | 01-MAY-00:10 |
June | 285649.01 | 20-JUN-07:10 | 40855.88 | 01-JUN-05:10 | 541788.89 | 01-JUN-07:10 | 233417.76 | 20-JUN-07:19 | 151289.49 | 13-JUN-15:50 | 69569.79 | 30-JUN-09:39 | 0.00 | 01-JUN-00:10 |
July | 285830.27 | 11-JUL-07:10 | 40855.88 | 01-JUL-05:10 | 660080.29 | 03-JUL-07:10 | 233417.85 | 11-JUL-07:19 | 193944.81 | 28-JUL-13:20 | 69571.86 | 28-JUL-13:20 | 0.00 | 01-JUL-00:10 |
August | 285830.27 | 21-AUG-07:10 | 40855.88 | 01-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 233417.85 | 21-AUG-07:19 | 155434.77 | 11-AUG-12:00 | 69571.92 | 23-AUG-09:20 | 0.00 | 01-AUG-00:10 |
September | 284436.93 | 07-SEP-07:10 | 40855.88 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 233417.11 | 07-SEP-07:19 | 178707.66 | 07-SEP-13:09 | 69571.77 | 07-SEP-13:09 | 0.00 | 01-SEP-00:10 |
October | 289036.26 | 23-OCT-07:10 | 40855.88 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 233419.57 | 23-OCT-07:19 | 182283.18 | 05-OCT-13:39 | 69571.73 | 17-OCT-15:20 | 0.00 | 01-OCT-00:10 |
November | 311655.64 | 09-NOV-16:00 | 40855.88 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 233416.47 | 01-NOV-07:19 | 181415.58 | 14-NOV-14:20 | 69571.74 | 14-NOV-14:20 | 0.00 | 01-NOV-00:10 |
December | 314611.94 | 18-DEC-16:49 | 40855.88 | 01-DEC-17:30 | 778371.69 | 01-DEC-08:09 | 233416.05 | 11-DEC-08:20 | 151293.02 | 27-DEC-16:10 | 65552.19 | 14-DEC-11:09 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 284436.93 | 40855.88 | 423497.50 | 233415.40 | 151289.49 | 59876.95 | 0.00 | |||||||
Maximum of Months | 314611.94 | 40855.88 | 778371.69 | 233419.57 | 195785.44 | 69572.26 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 333118.45 | 11-JAN-14:00 | 97598.82 | 01-JAN-18:19 | 0.00 | 01-JAN-00:10 | 5613.48 | 01-JAN-08:09 | 32218.47 | 17-JAN-12:00 | 0.00 |
February | 376927.17 | 15-FEB-13:30 | 97598.82 | 01-FEB-09:00 | 0.00 | 01-FEB-00:10 | 5613.48 | 01-FEB-04:19 | 32092.45 | 01-FEB-12:39 | 0.00 |
March | 423284.58 | 28-MAR-11:00 | 97598.82 | 01-MAR-04:19 | 0.00 | 01-MAR-00:10 | 5613.48 | 01-MAR-04:19 | 31554.38 | 02-MAR-12:30 | 0.00 |
April | 469909.35 | 13-APR-12:50 | 97598.82 | 01-APR-01:00 | 0.00 | 01-APR-00:10 | 5613.48 | 01-APR-01:00 | 31202.57 | 03-APR-11:20 | 0.00 |
May | 348677.96 | 05-MAY-12:09 | 97598.82 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 5613.48 | 01-MAY-02:49 | 30831.90 | 04-MAY-11:39 | 0.00 |
June | 388463.09 | 24-JUN-13:00 | 97598.82 | 01-JUN-03:39 | 0.00 | 01-JUN-00:10 | 5613.48 | 01-JUN-03:39 | 30214.93 | 01-JUN-11:30 | 0.00 |
July | 421840.24 | 17-JUL-13:30 | 97598.82 | 01-JUL-03:00 | 0.00 | 01-JUL-00:10 | 5613.48 | 01-JUL-05:19 | 29660.01 | 31-JUL-11:00 | 0.00 |
August | 462721.71 | 15-AUG-11:00 | 97598.82 | 01-AUG-03:20 | 0.00 | 01-AUG-00:10 | 5613.48 | 01-AUG-03:20 | 30332.08 | 31-AUG-11:30 | 0.00 |
September | 341761.24 | 01-SEP-11:20 | 97598.82 | 01-SEP-03:20 | 0.00 | 01-SEP-00:10 | 5613.48 | 01-SEP-03:20 | 30869.35 | 26-SEP-11:39 | 0.00 |
October | 378959.42 | 12-OCT-13:20 | 97598.82 | 01-OCT-06:30 | 0.00 | 01-OCT-00:10 | 5613.48 | 01-OCT-06:30 | 31289.04 | 31-OCT-11:50 | 0.00 |
November | 419396.59 | 10-NOV-11:39 | 97598.82 | 01-NOV-03:20 | 0.00 | 01-NOV-00:10 | 5613.48 | 01-NOV-03:20 | 31601.49 | 30-NOV-12:39 | 0.00 |
December | 455072.53 | 12-DEC-13:30 | 97598.82 | 01-DEC-07:49 | 0.00 | 01-DEC-00:10 | 5613.48 | 01-DEC-05:40 | 32138.67 | 27-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 333118.45 | 97598.82 | 0.00 | 5613.48 | 29660.01 | 0.00 | |||||
Maximum of Months | 469909.35 | 97598.82 | 0.00 | 5613.48 | 32218.47 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1575515.90 | 05-JAN-16:00 | 289987.47 | 423497.50 | 0.00 | 233305.47 | 151343.18 | 43657.51 | 0.00 | 305805.35 | 97598.82 |
February | 1755558.54 | 24-FEB-16:19 | 280515.72 | 541788.89 | 0.00 | 233302.19 | 176230.86 | 45239.90 | 0.00 | 350458.20 | 97598.82 |
March | 1911880.35 | 29-MAR-15:30 | 280450.63 | 660080.29 | 0.00 | 233302.19 | 163932.46 | 43657.59 | 0.00 | 402631.74 | 97598.82 |
April | 2056644.88 | 21-APR-15:00 | 280450.63 | 778371.69 | 0.00 | 233302.19 | 150796.59 | 43658.19 | 0.00 | 443455.64 | 97598.82 |
May | 1588672.35 | 30-MAY-10:00 | 280450.63 | 423497.50 | 0.00 | 233151.79 | 175039.84 | 69567.37 | 0.00 | 278918.54 | 97598.82 |
June | 1741942.75 | 13-JUN-15:50 | 280450.63 | 541788.89 | 0.00 | 233302.19 | 151289.49 | 59321.56 | 0.00 | 349445.33 | 97598.82 |
July | 1891055.21 | 14-JUL-15:20 | 280450.63 | 660080.29 | 0.00 | 233302.19 | 156264.06 | 43657.23 | 0.00 | 391005.65 | 97598.82 |
August | 2068653.65 | 22-AUG-15:20 | 280450.63 | 778371.69 | 0.00 | 233302.19 | 150799.21 | 43658.34 | 0.00 | 456205.55 | 97598.82 |
September | 1566771.70 | 01-SEP-15:00 | 281231.72 | 423497.50 | 0.00 | 233302.60 | 135322.83 | 43657.74 | 0.00 | 323343.80 | 97598.82 |
October | 1734629.75 | 17-OCT-15:20 | 280515.72 | 541788.89 | 0.00 | 233302.60 | 176814.69 | 69571.73 | 0.00 | 305954.82 | 97598.82 |
November | 1887507.80 | 03-NOV-15:09 | 280450.63 | 660080.29 | 0.00 | 233302.19 | 152429.42 | 43657.56 | 0.00 | 391019.83 | 97598.82 |
December | 2043569.73 | 08-DEC-16:00 | 307068.14 | 778371.69 | 0.00 | 233314.82 | 127848.39 | 34752.97 | 0.00 | 435252.00 | 97598.82 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1566771.70 | 280450.63 | 423497.50 | 0.00 | 233151.79 | 127848.39 | 34752.97 | 0.00 | 278918.54 | 97598.82 | |
Maximum of Months | 2068653.65 | 307068.14 | 778371.69 | 0.00 | 233314.82 | 176814.69 | 69571.73 | 0.00 | 456205.55 | 97598.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 670.33 | 29.65 | 442.00 | 29.70 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 656.00 | 29.79 | 438.00 | 29.81 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 30.69 | 514.00 | 30.73 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 720.00 | 30.68 | 485.00 | 30.72 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 30.61 | 508.00 | 30.66 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 720.00 | 30.81 | 496.00 | 30.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 30.83 | 497.00 | 30.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 30.95 | 514.00 | 30.99 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 720.00 | 30.69 | 485.00 | 30.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 30.65 | 502.00 | 30.69 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 714.33 | 30.58 | 483.33 | 30.63 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 703.33 | 29.73 | 466.00 | 29.77 |
Annual Sum or Average | 0.00 | 0.00 | 8624.00 | 30.49 | 5830.33 | 30.53 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 656.00 | 29.65 | 438.00 | 29.70 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 30.95 | 514.00 | 30.99 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 26.36 | 0.00 | 26.36 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 26.08 | 0.00 | 26.08 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 25.95 | 0.17 | 25.92 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 25.99 | 0.00 | 25.99 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 26.25 | 0.50 | 26.30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 26.18 | 0.33 | 26.22 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 26.09 | 0.00 | 26.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 26.03 | 0.00 | 26.03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 26.45 | 0.50 | 26.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 26.37 | 0.83 | 26.43 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 26.08 | 0.00 | 26.08 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 25.90 | 0.00 | 25.90 |
Annual Sum or Average | 0.00 | 0.00 | 104.50 | 26.18 | 2.33 | 26.20 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 25.90 | 0.00 | 25.90 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 26.45 | 0.83 | 26.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 26.50 | 3.00 | 26.75 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 26.91 | 7.83 | 27.15 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 26.76 | 7.67 | 26.99 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 30.33 | 26.76 | 13.67 | 26.83 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 37.50 | 26.78 | 17.33 | 26.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 35.00 | 26.87 | 14.67 | 26.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 38.33 | 26.70 | 20.33 | 26.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 24.50 | 26.72 | 9.00 | 26.84 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 26.75 | 7.50 | 26.98 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 26.78 | 9.17 | 27.04 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 26.86 | 9.17 | 27.10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 26.97 | 6.67 | 27.17 |
Annual Sum or Average | 0.00 | 0.00 | 269.83 | 26.78 | 126.00 | 26.90 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 26.50 | 3.00 | 26.71 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 38.33 | 26.97 | 20.33 | 27.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.10 | 7.50 | 27.29 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 27.38 | 12.17 | 27.57 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 27.36 | 10.50 | 27.63 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | 27.46 | 12.33 | 27.71 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 27.00 | 27.15 | 14.00 | 27.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 27.12 | 10.00 | 27.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 27.20 | 12.83 | 27.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 27.09 | 8.17 | 27.32 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 24.50 | 27.19 | 12.83 | 27.44 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 27.24 | 11.83 | 27.48 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 27.32 | 11.33 | 27.51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.55 | 10.33 | 27.61 |
Annual Sum or Average | 0.00 | 0.00 | 216.17 | 27.25 | 133.83 | 27.48 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.09 | 7.50 | 27.29 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 27.00 | 27.55 | 14.00 | 27.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 75.17 | 25.63 | 66.00 | 25.57 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 73.00 | 25.53 | 63.17 | 25.47 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 38.17 | 25.98 | 24.83 | 25.90 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 26.50 | 12.00 | 26.57 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 26.74 | 6.67 | 26.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 19.00 | 26.76 | 7.33 | 26.99 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 26.83 | 10.00 | 27.05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 26.58 | 4.83 | 26.82 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 26.69 | 7.17 | 26.95 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 23.67 | 26.84 | 14.00 | 27.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 64.67 | 25.75 | 53.67 | 25.68 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 92.17 | 25.64 | 83.67 | 25.58 |
Annual Sum or Average | 0.00 | 0.00 | 477.17 | 25.96 | 353.33 | 25.91 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 25.53 | 4.83 | 25.47 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 92.17 | 26.84 | 83.67 | 27.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.72 | 7.17 | 27.86 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 27.21 | 7.67 | 27.47 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 29.67 | 27.34 | 8.33 | 27.57 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 46.67 | 27.60 | 14.67 | 27.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 27.35 | 5.83 | 27.57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 27.19 | 7.50 | 27.42 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 30.33 | 27.29 | 11.50 | 27.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 31.17 | 27.33 | 8.00 | 27.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 27.24 | 5.83 | 27.45 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 | 27.14 | 8.17 | 27.38 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 23.67 | 27.22 | 9.83 | 27.45 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 24.83 | 27.56 | 11.50 | 27.77 |
Annual Sum or Average | 0.00 | 0.00 | 289.83 | 27.36 | 106.00 | 27.56 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.14 | 5.83 | 27.38 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 46.67 | 27.72 | 14.67 | 27.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.34 | 0.67 | 27.34 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.43 | 6.33 | 27.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.48 | 7.33 | 27.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.46 | 5.17 | 27.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.44 | 2.00 | 27.44 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 26.33 | 27.45 | 21.50 | 27.52 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.48 | 7.33 | 27.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.56 | 0.83 | 27.56 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.58 | 7.33 | 27.58 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 27.82 | 8.67 | 27.83 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.77 | 10.33 | 27.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.89 | 9.50 | 27.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.75 | 6.83 | 27.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.54 | 3.17 | 27.54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.76 | 5.33 | 27.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.69 | 7.50 | 27.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.58 | 5.50 | 27.58 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.51 | 4.67 | 27.51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.48 | 3.50 | 27.48 |
Annual Sum or Average | 0.00 | 0.00 | 74.00 | 27.71 | 73.17 | 27.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.48 | 0.83 | 27.48 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.89 | 10.33 | 27.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 45.83 | 25.60 | 44.17 | 25.57 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 | 26.10 | 21.50 | 26.08 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.62 | 5.50 | 27.63 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.33 | 27.29 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.33 | 1.50 | 27.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.31 | 1.17 | 27.31 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.32 | 0.50 | 27.32 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.62 | 7.33 | 27.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 27.74 | 9.33 | 27.78 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 54.00 | 25.62 | 52.50 | 25.60 |
Annual Sum or Average | 0.00 | 0.00 | 149.67 | 26.05 | 143.83 | 26.03 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 54.00 | 27.74 | 52.50 | 27.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.02 | 5.17 | 28.03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.93 | 5.17 | 27.95 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.96 | 4.50 | 28.12 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.91 | 5.00 | 28.03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.71 | 4.67 | 27.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.86 | 4.33 | 27.99 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.72 | 3.83 | 27.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.80 | 3.17 | 27.91 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.10 | 2.83 | 28.16 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.80 | 3.83 | 27.81 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.81 | 3.67 | 27.81 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.97 | 5.67 | 27.97 |
Annual Sum or Average | 0.00 | 0.00 | 74.17 | 27.88 | 51.83 | 27.96 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.71 | 2.83 | 27.76 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 28.10 | 5.67 | 28.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.43 | 2.83 | 27.43 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.51 | 3.33 | 27.51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.53 | 4.50 | 27.53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.49 | 7.83 | 27.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.56 | 8.00 | 27.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 27.60 | 8.33 | 27.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.64 | 2.83 | 27.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.43 | 3.00 | 27.43 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.28 | 1.50 | 27.28 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 53.00 | 27.53 | 42.17 | 27.58 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.64 | 8.33 | 27.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.44 | 3.00 | 27.44 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.70 | 9.67 | 27.70 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.96 | 9.33 | 27.98 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.90 | 11.33 | 27.93 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 28.01 | 9.67 | 28.05 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.83 | 8.67 | 27.84 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.55 | 8.17 | 27.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.88 | 5.67 | 27.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.82 | 9.17 | 27.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.71 | 7.17 | 27.71 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.60 | 6.33 | 27.60 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.51 | 6.67 | 27.51 |
Annual Sum or Average | 0.00 | 0.00 | 100.33 | 27.78 | 94.83 | 27.79 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.44 | 3.00 | 27.44 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 28.01 | 11.33 | 28.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 26.34 | 23.17 | 26.29 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 27.03 | 14.00 | 27.02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.77 | 6.50 | 27.79 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.50 | 4.00 | 27.50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.47 | 4.17 | 27.54 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.58 | 3.33 | 27.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.43 | 3.00 | 27.43 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.49 | 2.33 | 27.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.49 | 4.83 | 27.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.73 | 8.67 | 27.74 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.86 | 9.83 | 27.90 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 36.33 | 25.97 | 34.00 | 25.93 |
Annual Sum or Average | 0.00 | 0.00 | 129.50 | 26.84 | 117.83 | 26.82 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 25.97 | 2.33 | 25.93 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 36.33 | 27.86 | 34.00 | 27.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.11 | 5.17 | 28.15 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.08 | 5.50 | 28.12 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 28.18 | 5.00 | 28.32 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 28.03 | 5.67 | 28.15 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.84 | 5.33 | 27.99 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 28.06 | 5.00 | 28.15 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.82 | 5.83 | 27.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.96 | 3.67 | 28.05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.04 | 4.33 | 28.07 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.83 | 5.33 | 27.84 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.91 | 4.33 | 27.92 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.10 | 5.83 | 28.11 |
Annual Sum or Average | 0.00 | 0.00 | 87.17 | 28.00 | 61.00 | 28.06 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.82 | 3.67 | 27.82 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 28.18 | 5.83 | 28.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 85.67 | 27.77 | 79.17 | 27.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 61.83 | 27.76 | 59.00 | 27.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 147.50 | 27.77 | 138.17 | 27.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 85.67 | 27.77 | 79.17 | 27.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 44.67 | 27.70 | 44.33 | 27.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 35.33 | 27.73 | 35.33 | 27.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 80.00 | 27.71 | 79.67 | 27.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 44.67 | 27.73 | 44.33 | 27.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 28.83 | 27.69 | 27.17 | 27.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 | 27.68 | 21.83 | 27.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 51.50 | 27.69 | 49.00 | 27.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 28.83 | 27.69 | 27.17 | 27.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 428.83 | 29.94 | 502.00 | 29.51 | 428.83 | 29.64 |
February | 416.17 | 30.08 | 454.00 | 29.85 | 416.17 | 29.92 |
March | 514.00 | 30.80 | 514.00 | 30.80 | 514.00 | 30.80 |
April | 484.83 | 30.79 | 485.00 | 30.79 | 484.83 | 30.79 |
May | 508.00 | 30.73 | 508.00 | 30.73 | 508.00 | 30.73 |
June | 496.00 | 30.92 | 496.00 | 30.92 | 496.00 | 30.92 |
July | 497.00 | 30.94 | 497.00 | 30.94 | 497.00 | 30.94 |
August | 514.00 | 31.06 | 514.00 | 31.06 | 514.00 | 31.06 |
September | 485.00 | 30.80 | 485.00 | 30.80 | 485.00 | 30.80 |
October | 502.00 | 30.76 | 502.00 | 30.76 | 502.00 | 30.76 |
November | 478.50 | 30.76 | 489.00 | 30.69 | 478.50 | 30.72 |
December | 445.50 | 30.06 | 497.00 | 29.77 | 445.50 | 29.86 |
Annual Sum or Average | 5769.83 | 30.66 | 5943.00 | 30.57 | 5769.83 | 30.60 |
Minimum of Months | 416.17 | 29.94 | 454.00 | 29.51 | 416.17 | 29.64 |
Maximum of Months | 514.00 | 31.06 | 514.00 | 31.06 | 514.00 | 31.06 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 27.15 | 502.00 | 24.40 | 0.67 | 24.40 |
February | 0.17 | 27.13 | 454.00 | 24.37 | 0.17 | 24.38 |
March | 0.00 | 0.00 | 514.00 | 24.33 | 0.00 | 24.33 |
April | 0.00 | 0.00 | 485.00 | 24.40 | 0.00 | 24.40 |
May | 0.17 | 27.24 | 508.00 | 24.38 | 0.17 | 24.38 |
June | 0.33 | 27.38 | 496.00 | 24.34 | 0.33 | 24.35 |
July | 0.00 | 0.00 | 497.00 | 24.44 | 0.00 | 24.44 |
August | 0.00 | 0.00 | 514.00 | 24.37 | 0.00 | 24.37 |
September | 1.00 | 27.18 | 485.00 | 24.42 | 1.00 | 24.42 |
October | 0.83 | 27.11 | 502.00 | 24.45 | 0.83 | 24.45 |
November | 0.17 | 26.84 | 489.00 | 24.44 | 0.17 | 24.44 |
December | 0.00 | 0.00 | 497.00 | 24.38 | 0.00 | 24.38 |
Annual Sum or Average | 3.33 | 27.16 | 5943.00 | 24.39 | 3.33 | 24.39 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 24.33 | 0.00 | 24.33 |
Maximum of Months | 1.00 | 27.38 | 514.00 | 24.45 | 1.00 | 24.45 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.17 | 23.18 | 408.33 | 24.21 | 0.00 | 24.21 |
February | 5.50 | 23.18 | 352.67 | 24.15 | 0.00 | 24.15 |
March | 23.83 | 23.17 | 340.50 | 24.08 | 0.00 | 24.08 |
April | 50.33 | 23.16 | 284.83 | 23.98 | 0.00 | 23.98 |
May | 31.00 | 23.17 | 332.83 | 24.08 | 0.00 | 24.08 |
June | 22.67 | 23.20 | 354.00 | 24.08 | 0.00 | 24.08 |
July | 20.50 | 23.18 | 335.67 | 24.16 | 0.00 | 24.16 |
August | 27.33 | 23.16 | 347.83 | 24.15 | 0.00 | 24.15 |
September | 24.67 | 23.16 | 307.17 | 24.12 | 0.00 | 24.12 |
October | 17.17 | 23.17 | 348.33 | 24.18 | 0.00 | 24.18 |
November | 7.50 | 23.18 | 385.67 | 24.21 | 0.00 | 24.21 |
December | 8.67 | 23.17 | 390.00 | 24.18 | 0.00 | 24.18 |
Annual Sum or Average | 243.33 | 23.17 | 4187.83 | 24.13 | 0.00 | 24.13 |
Minimum of Months | 4.17 | 23.16 | 284.83 | 23.98 | 0.00 | 23.98 |
Maximum of Months | 50.33 | 23.20 | 408.33 | 24.21 | 0.00 | 24.21 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 23.25 | 405.83 | 24.25 | 0.00 | 24.25 |
February | 0.33 | 23.28 | 365.33 | 24.21 | 0.00 | 24.21 |
March | 7.17 | 23.25 | 409.17 | 24.14 | 0.00 | 24.14 |
April | 6.17 | 23.22 | 359.67 | 24.12 | 0.00 | 24.12 |
May | 2.83 | 23.25 | 419.50 | 24.16 | 0.00 | 24.16 |
June | 1.17 | 23.27 | 417.67 | 24.15 | 0.00 | 24.15 |
July | 0.33 | 23.28 | 383.00 | 24.26 | 0.00 | 24.26 |
August | 10.17 | 23.19 | 392.33 | 24.19 | 0.00 | 24.19 |
September | 5.83 | 23.03 | 377.00 | 24.18 | 0.00 | 24.18 |
October | 7.00 | 23.25 | 387.17 | 24.24 | 0.00 | 24.24 |
November | 1.50 | 23.13 | 394.00 | 24.27 | 0.00 | 24.27 |
December | 3.67 | 23.20 | 384.50 | 24.23 | 0.00 | 24.23 |
Annual Sum or Average | 47.17 | 23.20 | 4695.17 | 24.20 | 0.00 | 24.20 |
Minimum of Months | 0.33 | 23.03 | 359.67 | 24.12 | 0.00 | 24.12 |
Maximum of Months | 10.17 | 23.28 | 419.50 | 24.27 | 0.00 | 24.27 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 17.50 | 26.76 | 502.00 | 24.57 | 17.50 | 24.64 |
February | 35.33 | 26.79 | 454.00 | 24.68 | 35.33 | 24.82 |
March | 32.00 | 26.83 | 514.00 | 24.58 | 32.00 | 24.71 |
April | 45.83 | 26.87 | 485.00 | 24.77 | 45.83 | 24.94 |
May | 55.83 | 26.91 | 508.00 | 24.82 | 55.83 | 25.01 |
June | 49.83 | 26.96 | 496.00 | 24.79 | 49.83 | 24.97 |
July | 60.50 | 26.89 | 497.00 | 24.89 | 60.50 | 25.09 |
August | 31.00 | 26.89 | 514.00 | 24.61 | 31.00 | 24.74 |
September | 35.67 | 26.82 | 485.00 | 24.70 | 35.67 | 24.83 |
October | 43.50 | 26.80 | 502.00 | 24.75 | 43.50 | 24.90 |
November | 41.17 | 26.78 | 489.00 | 24.72 | 41.17 | 24.87 |
December | 30.83 | 26.77 | 497.00 | 24.62 | 30.83 | 24.74 |
Annual Sum or Average | 479.00 | 26.85 | 5943.00 | 24.71 | 479.00 | 24.86 |
Minimum of Months | 17.50 | 26.76 | 454.00 | 24.57 | 17.50 | 24.64 |
Maximum of Months | 60.50 | 26.96 | 514.00 | 24.89 | 60.50 | 25.09 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 40.00 | 26.73 | 501.50 | 24.70 | 40.00 | 24.84 |
February | 51.83 | 26.82 | 454.00 | 24.76 | 51.83 | 24.95 |
March | 42.00 | 26.96 | 514.00 | 24.63 | 42.00 | 24.79 |
April | 52.00 | 26.96 | 485.00 | 24.77 | 52.00 | 24.96 |
May | 54.00 | 26.93 | 508.00 | 24.78 | 54.00 | 24.97 |
June | 41.67 | 26.92 | 496.00 | 24.66 | 41.67 | 24.83 |
July | 55.17 | 26.79 | 497.00 | 24.78 | 55.17 | 24.96 |
August | 31.50 | 26.91 | 514.00 | 24.55 | 31.50 | 24.68 |
September | 52.50 | 26.89 | 485.00 | 24.79 | 52.50 | 24.97 |
October | 51.67 | 26.84 | 502.00 | 24.77 | 51.67 | 24.95 |
November | 49.67 | 26.80 | 489.00 | 24.73 | 49.67 | 24.90 |
December | 43.83 | 26.77 | 496.50 | 24.65 | 43.83 | 24.81 |
Annual Sum or Average | 565.83 | 26.86 | 5942.00 | 24.71 | 565.83 | 24.89 |
Minimum of Months | 31.50 | 26.73 | 454.00 | 24.55 | 31.50 | 24.68 |
Maximum of Months | 55.17 | 26.96 | 514.00 | 24.79 | 55.17 | 24.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 62.00 | 26.81 | 502.00 | 24.99 | 62.00 | 25.17 |
February | 48.67 | 26.94 | 454.00 | 24.94 | 48.67 | 25.12 |
March | 34.67 | 26.96 | 514.00 | 24.67 | 34.67 | 24.80 |
April | 37.00 | 26.85 | 485.00 | 24.70 | 37.00 | 24.84 |
May | 34.00 | 26.82 | 508.00 | 24.66 | 34.00 | 24.79 |
June | 31.50 | 26.83 | 496.00 | 24.59 | 31.50 | 24.72 |
July | 43.67 | 26.81 | 497.00 | 24.74 | 43.67 | 24.90 |
August | 22.33 | 26.84 | 514.00 | 24.52 | 22.33 | 24.61 |
September | 32.33 | 26.83 | 485.00 | 24.67 | 32.33 | 24.80 |
October | 50.33 | 26.90 | 502.00 | 24.82 | 50.33 | 24.99 |
November | 55.00 | 26.95 | 489.00 | 24.95 | 55.00 | 25.14 |
December | 75.17 | 26.67 | 497.00 | 25.03 | 75.17 | 25.22 |
Annual Sum or Average | 526.67 | 26.84 | 5943.00 | 24.78 | 526.67 | 24.93 |
Minimum of Months | 22.33 | 26.67 | 454.00 | 24.52 | 22.33 | 24.61 |
Maximum of Months | 75.17 | 26.96 | 514.00 | 25.03 | 75.17 | 25.22 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 26.67 | 26.92 | 502.00 | 24.60 | 26.67 | 24.71 |
February | 38.17 | 26.87 | 454.00 | 24.70 | 38.17 | 24.86 |
March | 47.00 | 26.90 | 514.00 | 24.68 | 47.00 | 24.85 |
April | 76.17 | 26.82 | 485.00 | 24.90 | 76.17 | 25.13 |
May | 31.00 | 26.85 | 508.00 | 24.60 | 31.00 | 24.72 |
June | 38.17 | 26.87 | 496.00 | 24.62 | 38.17 | 24.77 |
July | 58.17 | 26.77 | 497.00 | 24.80 | 58.17 | 24.99 |
August | 48.00 | 26.85 | 514.00 | 24.68 | 48.00 | 24.85 |
September | 26.67 | 26.82 | 485.00 | 24.58 | 26.67 | 24.69 |
October | 42.00 | 26.82 | 502.00 | 24.71 | 42.00 | 24.86 |
November | 49.50 | 26.79 | 489.00 | 24.76 | 49.50 | 24.94 |
December | 54.33 | 26.89 | 497.00 | 24.80 | 54.33 | 24.99 |
Annual Sum or Average | 535.83 | 26.84 | 5943.00 | 24.70 | 535.83 | 24.87 |
Minimum of Months | 26.67 | 26.77 | 454.00 | 24.58 | 26.67 | 24.69 |
Maximum of Months | 76.17 | 26.92 | 514.00 | 24.90 | 76.17 | 25.13 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 26.82 | 487.33 | 24.39 | 1.67 | 24.40 |
February | 2.50 | 26.89 | 453.67 | 24.42 | 2.50 | 24.43 |
March | 5.17 | 26.49 | 511.33 | 24.35 | 5.17 | 24.37 |
April | 7.33 | 26.75 | 485.00 | 24.43 | 7.33 | 24.46 |
May | 34.50 | 26.82 | 507.17 | 24.65 | 34.50 | 24.78 |
June | 38.00 | 26.82 | 496.00 | 24.65 | 38.00 | 24.79 |
July | 33.67 | 26.73 | 497.00 | 24.70 | 33.67 | 24.82 |
August | 29.50 | 26.32 | 512.67 | 24.49 | 29.50 | 24.58 |
September | 6.83 | 26.22 | 480.67 | 24.42 | 6.83 | 24.45 |
October | 6.17 | 26.52 | 485.67 | 24.47 | 6.17 | 24.50 |
November | 0.00 | 0.00 | 483.17 | 24.42 | 0.00 | 24.42 |
December | 1.83 | 23.25 | 478.00 | 24.36 | 0.00 | 24.36 |
Annual Sum or Average | 167.17 | 26.63 | 5877.67 | 24.48 | 165.33 | 24.54 |
Minimum of Months | 0.00 | 0.00 | 453.67 | 24.35 | 0.00 | 24.36 |
Maximum of Months | 38.00 | 26.89 | 512.67 | 24.70 | 38.00 | 24.82 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 17.33 | 26.81 | 423.83 | 24.66 | 17.33 | 24.74 |
February | 38.17 | 26.72 | 384.83 | 24.79 | 38.17 | 24.95 |
March | 38.67 | 26.80 | 428.00 | 24.69 | 38.67 | 24.85 |
April | 46.00 | 26.80 | 407.50 | 24.79 | 46.00 | 24.98 |
May | 43.50 | 26.85 | 418.50 | 24.80 | 43.50 | 24.98 |
June | 37.83 | 26.76 | 415.17 | 24.71 | 37.83 | 24.86 |
July | 29.17 | 26.71 | 412.17 | 24.76 | 29.17 | 24.88 |
August | 41.17 | 26.60 | 419.17 | 24.68 | 41.17 | 24.84 |
September | 42.67 | 26.58 | 397.83 | 24.77 | 41.33 | 24.94 |
October | 38.33 | 26.37 | 394.00 | 24.77 | 34.83 | 24.91 |
November | 26.33 | 26.72 | 404.83 | 24.72 | 26.33 | 24.83 |
December | 25.33 | 26.74 | 410.33 | 24.69 | 25.33 | 24.81 |
Annual Sum or Average | 424.50 | 26.70 | 4916.17 | 24.74 | 419.67 | 24.88 |
Minimum of Months | 17.33 | 26.37 | 384.83 | 24.66 | 17.33 | 24.74 |
Maximum of Months | 46.00 | 26.85 | 428.00 | 24.80 | 46.00 | 24.98 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 49.50 | 26.97 | 501.67 | 24.92 | 49.50 | 25.09 |
February | 41.17 | 26.93 | 454.00 | 24.82 | 41.17 | 24.98 |
March | 26.83 | 26.80 | 514.00 | 24.53 | 26.83 | 24.63 |
April | 5.67 | 26.73 | 485.00 | 24.40 | 5.67 | 24.43 |
May | 12.33 | 26.68 | 505.67 | 24.47 | 12.33 | 24.52 |
June | 14.83 | 26.51 | 495.00 | 24.44 | 14.83 | 24.49 |
July | 4.83 | 26.76 | 496.33 | 24.49 | 4.83 | 24.51 |
August | 21.67 | 26.05 | 510.67 | 24.41 | 21.67 | 24.47 |
September | 15.50 | 26.45 | 481.67 | 24.49 | 15.50 | 24.55 |
October | 41.00 | 26.80 | 490.00 | 24.73 | 41.00 | 24.88 |
November | 46.83 | 26.93 | 489.00 | 24.82 | 46.83 | 24.99 |
December | 54.33 | 26.92 | 497.00 | 24.93 | 54.33 | 25.11 |
Annual Sum or Average | 334.50 | 26.80 | 5920.00 | 24.62 | 334.50 | 24.74 |
Minimum of Months | 4.83 | 26.05 | 454.00 | 24.40 | 4.83 | 24.43 |
Maximum of Months | 54.33 | 26.97 | 514.00 | 24.93 | 54.33 | 25.11 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 24.00 | 26.69 | 488.67 | 24.59 | 22.67 | 24.69 |
February | 21.83 | 26.87 | 453.83 | 24.60 | 21.83 | 24.70 |
March | 25.00 | 26.98 | 512.83 | 24.57 | 25.00 | 24.67 |
April | 29.67 | 26.90 | 483.50 | 24.63 | 29.67 | 24.75 |
May | 29.17 | 26.90 | 497.17 | 24.62 | 29.17 | 24.74 |
June | 28.50 | 26.87 | 494.50 | 24.57 | 28.50 | 24.69 |
July | 24.83 | 26.75 | 486.50 | 24.65 | 24.83 | 24.75 |
August | 34.17 | 26.64 | 502.00 | 24.58 | 34.17 | 24.70 |
September | 21.50 | 26.45 | 472.83 | 24.54 | 19.83 | 24.63 |
October | 35.17 | 26.39 | 470.50 | 24.67 | 31.33 | 24.79 |
November | 21.33 | 26.77 | 476.00 | 24.61 | 21.33 | 24.70 |
December | 24.50 | 26.65 | 478.33 | 24.60 | 23.00 | 24.70 |
Annual Sum or Average | 319.67 | 26.73 | 5816.67 | 24.60 | 311.33 | 24.71 |
Minimum of Months | 21.33 | 26.39 | 453.83 | 24.54 | 19.83 | 24.63 |
Maximum of Months | 35.17 | 26.98 | 512.83 | 24.67 | 34.17 | 24.79 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.83 | 24.74 | 474.00 | 24.42 | 4.50 | 24.44 |
February | 19.33 | 26.67 | 438.83 | 24.53 | 19.33 | 24.62 |
March | 24.67 | 26.46 | 509.33 | 24.45 | 24.67 | 24.54 |
April | 24.50 | 26.67 | 484.00 | 24.53 | 24.50 | 24.63 |
May | 45.67 | 26.79 | 504.50 | 24.71 | 45.67 | 24.87 |
June | 42.83 | 26.83 | 495.00 | 24.67 | 42.83 | 24.83 |
July | 42.50 | 26.78 | 495.67 | 24.75 | 42.50 | 24.90 |
August | 37.50 | 26.29 | 505.33 | 24.52 | 37.50 | 24.64 |
September | 25.67 | 26.25 | 477.00 | 24.52 | 24.33 | 24.61 |
October | 30.67 | 26.16 | 474.50 | 24.58 | 26.83 | 24.68 |
November | 12.50 | 26.62 | 473.00 | 24.50 | 12.50 | 24.56 |
December | 12.67 | 24.32 | 458.33 | 24.40 | 4.33 | 24.42 |
Annual Sum or Average | 328.33 | 26.43 | 5789.50 | 24.55 | 309.50 | 24.65 |
Minimum of Months | 9.83 | 24.32 | 438.83 | 24.40 | 4.33 | 24.42 |
Maximum of Months | 45.67 | 26.83 | 509.33 | 24.75 | 45.67 | 24.90 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 30.50 | 26.63 | 495.17 | 24.62 | 30.00 | 24.74 |
February | 47.50 | 26.73 | 449.00 | 24.74 | 47.50 | 24.91 |
March | 45.00 | 26.80 | 506.50 | 24.62 | 45.00 | 24.79 |
April | 50.33 | 26.85 | 479.33 | 24.72 | 50.33 | 24.91 |
May | 48.00 | 26.83 | 494.67 | 24.72 | 47.33 | 24.89 |
June | 43.83 | 26.77 | 492.67 | 24.64 | 43.83 | 24.80 |
July | 44.83 | 26.70 | 481.17 | 24.74 | 44.83 | 24.89 |
August | 45.00 | 26.53 | 493.33 | 24.60 | 44.33 | 24.75 |
September | 50.33 | 26.55 | 466.67 | 24.71 | 48.33 | 24.88 |
October | 57.67 | 26.04 | 462.67 | 24.71 | 47.33 | 24.87 |
November | 39.67 | 26.60 | 470.17 | 24.68 | 38.83 | 24.82 |
December | 39.17 | 26.62 | 477.83 | 24.66 | 38.67 | 24.80 |
Annual Sum or Average | 541.83 | 26.63 | 5769.17 | 24.68 | 526.33 | 24.84 |
Minimum of Months | 30.50 | 26.04 | 449.00 | 24.60 | 30.00 | 24.74 |
Maximum of Months | 57.67 | 26.85 | 506.50 | 24.74 | 50.33 | 24.91 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 52.67 | 26.95 | 500.33 | 24.89 | 52.67 | 25.07 |
February | 42.83 | 26.93 | 454.00 | 24.81 | 42.83 | 24.98 |
March | 35.17 | 26.71 | 511.50 | 24.57 | 35.17 | 24.70 |
April | 23.33 | 26.65 | 482.67 | 24.52 | 23.33 | 24.61 |
May | 24.83 | 26.68 | 502.50 | 24.55 | 24.83 | 24.64 |
June | 27.17 | 26.58 | 494.50 | 24.51 | 27.17 | 24.61 |
July | 27.17 | 26.64 | 485.17 | 24.62 | 27.17 | 24.72 |
August | 31.83 | 26.09 | 501.50 | 24.46 | 31.83 | 24.55 |
September | 29.67 | 26.35 | 477.83 | 24.56 | 28.33 | 24.66 |
October | 48.67 | 26.74 | 482.50 | 24.77 | 47.67 | 24.93 |
November | 50.67 | 26.93 | 488.00 | 24.82 | 50.67 | 25.00 |
December | 53.00 | 27.02 | 494.83 | 24.89 | 53.00 | 25.08 |
Annual Sum or Average | 447.00 | 26.74 | 5875.33 | 24.66 | 444.67 | 24.80 |
Minimum of Months | 23.33 | 26.09 | 454.00 | 24.46 | 23.33 | 24.55 |
Maximum of Months | 53.00 | 27.02 | 511.50 | 24.89 | 53.00 | 25.08 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 30.17 | 26.23 | 467.50 | 24.60 | 25.17 | 24.71 |
February | 26.17 | 26.86 | 440.83 | 24.63 | 26.17 | 24.75 |
March | 30.67 | 26.94 | 509.50 | 24.58 | 30.67 | 24.71 |
April | 37.83 | 26.88 | 479.83 | 24.67 | 37.83 | 24.82 |
May | 36.00 | 26.64 | 492.00 | 24.63 | 33.67 | 24.77 |
June | 32.50 | 26.85 | 493.83 | 24.58 | 32.50 | 24.71 |
July | 32.50 | 26.73 | 476.33 | 24.69 | 32.50 | 24.82 |
August | 38.50 | 26.41 | 492.67 | 24.58 | 36.50 | 24.71 |
September | 31.33 | 26.21 | 462.50 | 24.57 | 27.83 | 24.68 |
October | 51.00 | 25.71 | 452.17 | 24.66 | 37.00 | 24.81 |
November | 28.67 | 26.62 | 462.67 | 24.64 | 28.00 | 24.75 |
December | 32.67 | 26.11 | 460.17 | 24.60 | 26.50 | 24.72 |
Annual Sum or Average | 408.00 | 26.48 | 5690.00 | 24.62 | 374.33 | 24.75 |
Minimum of Months | 26.17 | 25.71 | 440.83 | 24.57 | 25.17 | 24.68 |
Maximum of Months | 51.00 | 26.94 | 509.50 | 24.69 | 37.83 | 24.82 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 198.83 | 27.00 | 502.00 | 27.00 | 198.83 | 27.00 |
February | 278.17 | 27.00 | 454.00 | 27.00 | 278.17 | 27.00 |
March | 486.83 | 27.00 | 514.00 | 27.00 | 486.83 | 27.00 |
April | 485.00 | 27.20 | 485.00 | 27.20 | 485.00 | 27.20 |
May | 348.50 | 27.00 | 508.00 | 27.00 | 348.50 | 27.00 |
June | 416.50 | 27.00 | 496.00 | 27.00 | 416.50 | 27.00 |
July | 466.33 | 27.00 | 497.00 | 27.00 | 466.33 | 27.00 |
August | 514.00 | 27.15 | 514.00 | 27.15 | 514.00 | 27.15 |
September | 287.67 | 27.00 | 485.00 | 27.00 | 287.67 | 27.00 |
October | 340.00 | 27.00 | 502.00 | 27.00 | 340.00 | 27.00 |
November | 433.17 | 27.00 | 489.00 | 27.00 | 433.17 | 27.00 |
December | 489.17 | 27.03 | 497.00 | 27.03 | 489.17 | 27.03 |
Annual Sum or Average | 4744.17 | 27.04 | 5943.00 | 27.04 | 4744.17 | 27.04 |
Minimum of Months | 198.83 | 27.00 | 454.00 | 27.00 | 198.83 | 27.00 |
Maximum of Months | 514.00 | 27.20 | 514.00 | 27.20 | 514.00 | 27.20 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 27.17 | 27.00 | 502.00 | 27.00 | 27.17 | 27.00 |
February | 53.50 | 27.00 | 454.00 | 27.00 | 53.50 | 27.00 |
March | 85.33 | 27.00 | 514.00 | 27.00 | 85.33 | 27.00 |
April | 148.83 | 27.39 | 485.00 | 27.19 | 148.83 | 27.22 |
May | 72.83 | 27.00 | 508.00 | 27.00 | 72.83 | 27.00 |
June | 73.67 | 27.00 | 496.00 | 27.00 | 73.67 | 27.00 |
July | 33.17 | 27.00 | 497.00 | 27.00 | 33.17 | 27.00 |
August | 140.00 | 27.36 | 514.00 | 27.16 | 140.00 | 27.19 |
September | 36.50 | 27.00 | 485.00 | 27.00 | 36.50 | 27.00 |
October | 19.17 | 27.00 | 502.00 | 27.00 | 19.17 | 27.00 |
November | 48.33 | 27.00 | 489.00 | 27.00 | 48.33 | 27.00 |
December | 81.67 | 27.04 | 497.00 | 27.01 | 81.67 | 27.02 |
Annual Sum or Average | 820.17 | 27.14 | 5943.00 | 27.03 | 820.17 | 27.05 |
Minimum of Months | 19.17 | 27.00 | 454.00 | 27.00 | 19.17 | 27.00 |
Maximum of Months | 148.83 | 27.39 | 514.00 | 27.19 | 148.83 | 27.22 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 81.33 | 27.00 | 502.00 | 27.00 | 81.33 | 27.00 |
February | 107.67 | 27.00 | 454.00 | 27.00 | 107.67 | 27.00 |
March | 156.83 | 27.00 | 514.00 | 27.00 | 156.83 | 27.00 |
April | 194.50 | 27.24 | 485.00 | 27.14 | 194.50 | 27.16 |
May | 159.83 | 27.00 | 508.00 | 27.00 | 159.83 | 27.00 |
June | 161.00 | 27.00 | 496.00 | 27.00 | 161.00 | 27.00 |
July | 112.33 | 27.00 | 497.00 | 27.00 | 112.33 | 27.00 |
August | 172.50 | 27.20 | 514.00 | 27.10 | 172.50 | 27.12 |
September | 112.00 | 27.00 | 485.00 | 27.00 | 112.00 | 27.00 |
October | 84.00 | 27.00 | 502.00 | 27.00 | 84.00 | 27.00 |
November | 120.83 | 27.00 | 489.00 | 27.00 | 120.83 | 27.00 |
December | 135.33 | 27.01 | 497.00 | 27.00 | 135.33 | 27.01 |
Annual Sum or Average | 1598.17 | 27.05 | 5943.00 | 27.02 | 1598.17 | 27.03 |
Minimum of Months | 81.33 | 27.00 | 454.00 | 27.00 | 81.33 | 27.00 |
Maximum of Months | 194.50 | 27.24 | 514.00 | 27.14 | 194.50 | 27.16 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.01 | 496.00 | 27.01 | 496.00 | 27.01 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.01 | 502.00 | 27.01 | 502.00 | 27.01 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5943.00 | 27.00 | 5943.00 | 27.00 | 5943.00 | 27.00 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 27.01 | 514.00 | 27.01 | 514.00 | 27.01 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00035 | 43.09216 | 1.05145 | 28.36022 |
February | 454.00000 | 27.00244 | 40.87995 | 1.07231 | 29.28787 |
March | 514.00000 | 27.00135 | 40.18804 | 1.10109 | 30.58454 |
April | 485.00000 | 27.20193 | 39.94973 | 1.16729 | 33.76062 |
May | 508.00000 | 27.00001 | 46.92796 | 0.44646 | 9.20523 |
June | 496.00000 | 27.00369 | 43.13491 | 0.46649 | 9.58972 |
July | 497.00000 | 27.00166 | 40.22881 | 0.47790 | 9.81161 |
August | 514.00000 | 27.15159 | 39.89207 | 0.55169 | 11.59141 |
September | 485.00000 | 27.00001 | 46.23378 | 0.43394 | 8.97476 |
October | 502.00000 | 27.00351 | 42.17356 | 1.07955 | 29.60662 |
November | 489.00000 | 27.00166 | 40.15021 | 1.09593 | 30.34953 |
December | 497.00000 | 27.02819 | 38.96512 | 1.11399 | 31.19224 |
Annual Sum or Average | 5943.00000 | 27.03316 | 41.82235 | 0.83594 | 21.78256 |
Minimum of Months | 454.00000 | 27.00001 | 38.96512 | 0.43394 | 8.97476 |
Maximum of Months | 514.00000 | 27.20193 | 46.92796 | 1.16729 | 33.76062 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00015 | 43.54187 | 0.99961 | 26.13221 |
February | 454.00000 | 27.00255 | 41.04879 | 0.99949 | 26.12903 |
March | 514.00000 | 27.00166 | 40.27477 | 1.00801 | 26.48849 |
April | 485.00000 | 27.12269 | 40.06321 | 1.04095 | 27.96870 |
May | 508.00000 | 27.00004 | 47.78640 | 0.35798 | 7.71485 |
June | 496.00000 | 27.00387 | 43.45950 | 0.35441 | 7.67074 |
July | 497.00000 | 27.00200 | 40.34711 | 0.33977 | 7.45127 |
August | 514.00000 | 27.10086 | 39.99330 | 0.38450 | 8.25972 |
September | 485.00000 | 27.00004 | 47.10938 | 0.34358 | 7.50651 |
October | 502.00000 | 27.00358 | 42.48345 | 0.99964 | 26.12995 |
November | 489.00000 | 27.00197 | 40.26032 | 1.00318 | 26.28146 |
December | 497.00000 | 27.00720 | 38.99647 | 1.00887 | 26.52804 |
Annual Sum or Average | 5943.00000 | 27.02065 | 42.11843 | 0.73416 | 18.61474 |
Minimum of Months | 454.00000 | 27.00004 | 38.99647 | 0.33977 | 7.45127 |
Maximum of Months | 514.00000 | 27.12269 | 47.78640 | 1.04095 | 27.96870 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00016 | 43.54049 | 1.00650 | 26.44170 |
February | 454.00000 | 27.00249 | 41.06099 | 1.00999 | 26.59520 |
March | 514.00000 | 27.00157 | 40.29587 | 1.02229 | 27.12116 |
April | 485.00000 | 27.09671 | 40.10803 | 1.05410 | 28.56173 |
May | 508.00000 | 27.00001 | 47.63456 | 0.37861 | 8.07107 |
June | 496.00000 | 27.00384 | 43.43814 | 0.37571 | 8.03854 |
July | 497.00000 | 27.00193 | 40.37398 | 0.35745 | 7.74808 |
August | 514.00000 | 27.06779 | 40.05527 | 0.39127 | 8.39927 |
September | 485.00000 | 27.00001 | 46.98560 | 0.36072 | 7.79896 |
October | 502.00000 | 27.00358 | 42.49880 | 1.00837 | 26.51771 |
November | 489.00000 | 27.00190 | 40.29510 | 1.01168 | 26.66134 |
December | 497.00000 | 27.00285 | 39.04261 | 1.01375 | 26.75648 |
Annual Sum or Average | 5943.00000 | 27.01528 | 42.11549 | 0.74670 | 18.98463 |
Minimum of Months | 454.00000 | 27.00001 | 39.04261 | 0.35745 | 7.74808 |
Maximum of Months | 514.00000 | 27.09671 | 47.63456 | 1.05410 | 28.56173 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00472 | 40.71620 | 1.24131 | 37.29923 |
February | 454.00000 | 27.00336 | 39.95342 | 1.38167 | 44.54196 |
March | 514.00000 | 27.00215 | 39.86179 | 1.52236 | 52.11681 |
April | 485.00000 | 27.00062 | 39.99844 | 1.65225 | 59.17946 |
May | 508.00000 | 27.00223 | 42.90057 | 0.72002 | 15.94691 |
June | 496.00000 | 27.00547 | 41.25596 | 0.91366 | 22.64475 |
July | 497.00000 | 27.00259 | 39.72422 | 1.09131 | 30.13156 |
August | 514.00000 | 27.00086 | 39.77408 | 1.27751 | 39.12477 |
September | 485.00000 | 27.00379 | 42.31806 | 0.71902 | 15.91513 |
October | 502.00000 | 27.00501 | 40.50697 | 1.39174 | 45.07523 |
November | 489.00000 | 27.00257 | 39.63852 | 1.52249 | 52.12418 |
December | 497.00000 | 27.00067 | 39.12156 | 1.63869 | 58.44549 |
Annual Sum or Average | 5943.00000 | 27.00283 | 40.48381 | 1.25501 | 39.32987 |
Minimum of Months | 454.00000 | 27.00062 | 39.12156 | 0.71902 | 15.91513 |
Maximum of Months | 514.00000 | 27.00547 | 42.90057 | 1.65225 | 59.17946 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 29.14208 | 82.75204 | 1.96818 | 71.47086 |
February | 454.00000 | 29.64034 | 89.07988 | 2.15199 | 79.09857 |
March | 514.00000 | 30.80096 | 99.99895 | 2.54414 | 94.13823 |
April | 485.00000 | 30.78798 | 96.10551 | 2.50771 | 92.22036 |
May | 508.00000 | 30.72848 | 99.19894 | 2.19676 | 84.35162 |
June | 496.00000 | 30.91804 | 99.99918 | 2.27826 | 87.26346 |
July | 497.00000 | 30.93705 | 99.99916 | 2.28747 | 87.53246 |
August | 514.00000 | 31.05729 | 99.99903 | 2.33369 | 88.95740 |
September | 485.00000 | 30.80284 | 99.99889 | 2.23382 | 85.76634 |
October | 502.00000 | 30.76122 | 99.99902 | 2.53291 | 93.92366 |
November | 489.00000 | 30.63034 | 96.23035 | 2.47265 | 90.58081 |
December | 497.00000 | 29.50870 | 84.84741 | 2.07577 | 76.51021 |
Annual Sum or Average | 5943.00000 | 30.48293 | 95.74473 | 2.29968 | 86.03904 |
Minimum of Months | 454.00000 | 29.14208 | 82.75204 | 1.96818 | 71.47086 |
Maximum of Months | 514.00000 | 31.05729 | 99.99918 | 2.54414 | 94.13823 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.39192 | 47.38184 | 0.61327 | 13.20729 |
February | 454.00000 | 24.37333 | 47.25137 | 0.62035 | 13.37012 |
March | 514.00000 | 24.32739 | 46.96212 | 0.62579 | 13.46067 |
April | 485.00000 | 24.39759 | 46.99490 | 0.64423 | 14.00276 |
May | 508.00000 | 24.38010 | 46.94486 | -0.1899 | 6.32216 |
June | 496.00000 | 24.34252 | 46.66057 | -0.1893 | 6.27277 |
July | 497.00000 | 24.43770 | 46.72115 | -0.1609 | 6.20342 |
August | 514.00000 | 24.36720 | 47.14814 | -0.1691 | 6.13091 |
September | 485.00000 | 24.41078 | 47.03174 | -0.1833 | 6.36392 |
October | 502.00000 | 24.44475 | 46.76553 | 0.64028 | 13.98000 |
November | 489.00000 | 24.43814 | 46.78171 | 0.64519 | 14.10366 |
December | 497.00000 | 24.38342 | 47.12212 | 0.62546 | 13.49064 |
Annual Sum or Average | 5943.00000 | 24.39103 | 46.97925 | 0.29030 | 10.54578 |
Minimum of Months | 454.00000 | 24.32739 | 46.66057 | -0.1899 | 6.13091 |
Maximum of Months | 514.00000 | 24.44475 | 47.38184 | 0.64519 | 14.10366 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.10714 | 49.41877 | 0.49275 | 10.28304 |
February | 454.00000 | 24.04501 | 49.56078 | 0.48053 | 9.98618 |
March | 514.00000 | 23.95282 | 49.89631 | 0.45833 | 9.55009 |
April | 485.00000 | 23.85877 | 50.12291 | 0.43472 | 9.12848 |
May | 508.00000 | 23.94819 | 49.84349 | -0.4374 | 9.34365 |
June | 496.00000 | 23.97147 | 49.68563 | -0.4251 | 9.10239 |
July | 497.00000 | 24.00939 | 49.66194 | -0.4219 | 9.11125 |
August | 514.00000 | 24.00955 | 49.87630 | -0.4201 | 9.11614 |
September | 485.00000 | 23.96606 | 49.99033 | -0.4343 | 9.30159 |
October | 502.00000 | 24.03785 | 49.70535 | 0.47245 | 9.86083 |
November | 489.00000 | 24.10401 | 49.46547 | 0.48997 | 10.21125 |
December | 497.00000 | 24.07113 | 49.54679 | 0.48455 | 10.09649 |
Annual Sum or Average | 5943.00000 | 24.00662 | 49.73227 | 0.09427 | 9.58773 |
Minimum of Months | 454.00000 | 23.85877 | 49.41877 | -0.4374 | 9.10239 |
Maximum of Months | 514.00000 | 24.10714 | 50.12291 | 0.49275 | 10.28304 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.13671 | 49.29586 | 0.50731 | 10.58504 |
February | 454.00000 | 24.10063 | 49.31457 | 0.50335 | 10.45415 |
March | 514.00000 | 24.04027 | 49.47766 | 0.49120 | 10.19208 |
April | 485.00000 | 23.98880 | 49.56930 | 0.47927 | 9.94696 |
May | 508.00000 | 24.07099 | 49.31398 | -0.3788 | 8.27413 |
June | 496.00000 | 24.06882 | 49.19820 | -0.3737 | 8.20056 |
July | 497.00000 | 24.10578 | 49.28179 | -0.3756 | 8.32064 |
August | 514.00000 | 24.06693 | 49.62254 | -0.3867 | 8.50008 |
September | 485.00000 | 24.06422 | 49.56596 | -0.3864 | 8.45983 |
October | 502.00000 | 24.09604 | 49.47238 | 0.49419 | 10.30828 |
November | 489.00000 | 24.14819 | 49.28125 | 0.50850 | 10.60465 |
December | 497.00000 | 24.09359 | 49.45923 | 0.49643 | 10.33171 |
Annual Sum or Average | 5943.00000 | 24.08162 | 49.40522 | 0.12805 | 9.50636 |
Minimum of Months | 454.00000 | 23.98880 | 49.19820 | -0.3867 | 8.20056 |
Maximum of Months | 514.00000 | 24.14819 | 49.62254 | 0.50850 | 10.60465 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.49425 | 46.65466 | 0.64684 | 14.31829 |
February | 454.00000 | 24.51072 | 46.41427 | 0.66934 | 15.04721 |
March | 514.00000 | 24.44450 | 46.29461 | 0.67541 | 15.12789 |
April | 485.00000 | 24.57366 | 46.21159 | 0.71908 | 16.55899 |
May | 508.00000 | 24.58832 | 46.01648 | -0.0469 | 6.65103 |
June | 496.00000 | 24.56905 | 45.60975 | -0.0164 | 6.51248 |
July | 497.00000 | 24.65140 | 45.71639 | -0.0297 | 6.66560 |
August | 514.00000 | 24.47774 | 46.60726 | -0.0899 | 6.29946 |
September | 485.00000 | 24.54077 | 46.34438 | -0.1069 | 6.55526 |
October | 502.00000 | 24.57012 | 46.16774 | 0.68106 | 15.48009 |
November | 489.00000 | 24.54243 | 46.16196 | 0.67947 | 15.35396 |
December | 497.00000 | 24.48621 | 46.43737 | 0.65421 | 14.55695 |
Annual Sum or Average | 5943.00000 | 24.53718 | 46.21951 | 0.36665 | 11.55627 |
Minimum of Months | 454.00000 | 24.44450 | 45.60975 | -0.1069 | 6.29946 |
Maximum of Months | 514.00000 | 24.65140 | 46.65466 | 0.71908 | 16.55899 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.53161 | 46.30688 | 0.69779 | 15.86134 |
February | 454.00000 | 24.52890 | 46.13456 | 0.72151 | 16.68244 |
March | 514.00000 | 24.44106 | 46.07049 | 0.72396 | 16.68265 |
April | 485.00000 | 24.53507 | 46.13771 | 0.75396 | 17.73224 |
May | 508.00000 | 24.55224 | 46.00800 | -0.0281 | 6.73130 |
June | 496.00000 | 24.47335 | 45.79822 | -0.0350 | 6.36269 |
July | 497.00000 | 24.55418 | 45.93719 | -0.0526 | 6.48823 |
August | 514.00000 | 24.40318 | 46.68565 | -0.0825 | 6.25904 |
September | 485.00000 | 24.55960 | 46.09418 | -0.0461 | 6.70526 |
October | 502.00000 | 24.56162 | 46.00854 | 0.70914 | 16.36239 |
November | 489.00000 | 24.51580 | 46.07595 | 0.70257 | 16.06748 |
December | 497.00000 | 24.46561 | 46.33674 | 0.67886 | 15.32474 |
Annual Sum or Average | 5943.00000 | 24.50953 | 46.13425 | 0.39208 | 12.22746 |
Minimum of Months | 454.00000 | 24.40318 | 45.79822 | -0.0825 | 6.25904 |
Maximum of Months | 514.00000 | 24.56162 | 46.68565 | 0.75396 | 17.73224 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.76592 | 45.65385 | 0.77233 | 18.50766 |
February | 454.00000 | 24.72759 | 45.62421 | 0.76783 | 18.27337 |
March | 514.00000 | 24.51082 | 46.03410 | 0.70744 | 16.15410 |
April | 485.00000 | 24.53937 | 46.35855 | 0.69842 | 15.86318 |
May | 508.00000 | 24.51372 | 46.36321 | -0.1110 | 6.46609 |
June | 496.00000 | 24.45290 | 46.13074 | -0.1184 | 6.37782 |
July | 497.00000 | 24.56236 | 46.09351 | -0.1031 | 6.55161 |
August | 514.00000 | 24.42040 | 46.86735 | -0.1359 | 6.27868 |
September | 485.00000 | 24.53022 | 46.36821 | -0.1105 | 6.50595 |
October | 502.00000 | 24.60979 | 45.95216 | 0.70920 | 16.41372 |
November | 489.00000 | 24.72783 | 45.49388 | 0.76211 | 18.12154 |
December | 497.00000 | 24.78550 | 45.40630 | 0.78473 | 18.98765 |
Annual Sum or Average | 5943.00000 | 24.59393 | 46.03377 | 0.38155 | 12.82328 |
Minimum of Months | 454.00000 | 24.42040 | 45.40630 | -0.1359 | 6.27868 |
Maximum of Months | 514.00000 | 24.78550 | 46.86735 | 0.78473 | 18.98765 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.47940 | 46.40420 | 0.69807 | 15.89524 |
February | 454.00000 | 24.52204 | 46.08864 | 0.74584 | 17.43235 |
March | 514.00000 | 24.47346 | 45.90411 | 0.76985 | 18.20830 |
April | 485.00000 | 24.59530 | 45.85933 | 0.82036 | 20.04966 |
May | 508.00000 | 24.46026 | 46.26175 | -0.0611 | 6.41992 |
June | 496.00000 | 24.44775 | 45.84565 | -0.0228 | 6.39380 |
July | 497.00000 | 24.57440 | 45.78726 | 0.00371 | 6.59090 |
August | 514.00000 | 24.47182 | 46.33927 | 0.01031 | 6.39376 |
September | 485.00000 | 24.45843 | 46.38204 | -0.0835 | 6.40673 |
October | 502.00000 | 24.53489 | 46.00744 | 0.72190 | 16.68650 |
November | 489.00000 | 24.55895 | 45.82857 | 0.75032 | 17.58636 |
December | 497.00000 | 24.57487 | 45.84125 | 0.76965 | 18.28008 |
Annual Sum or Average | 5943.00000 | 24.51212 | 46.04661 | 0.42382 | 12.98004 |
Minimum of Months | 454.00000 | 24.44775 | 45.78726 | -0.0835 | 6.39376 |
Maximum of Months | 514.00000 | 24.59530 | 46.40420 | 0.82036 | 20.04966 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.35751 | 48.78481 | 0.57474 | 12.27594 |
February | 454.00000 | 24.40270 | 48.44705 | 0.59467 | 12.84079 |
March | 514.00000 | 24.32716 | 48.94529 | 0.58736 | 12.58283 |
April | 485.00000 | 24.39326 | 48.71541 | 0.61177 | 13.26713 |
May | 508.00000 | 24.50241 | 48.48453 | -0.1509 | 6.85498 |
June | 496.00000 | 24.47985 | 48.14064 | -0.1236 | 6.66429 |
July | 497.00000 | 24.55714 | 47.93176 | -0.1552 | 6.89542 |
August | 514.00000 | 24.38057 | 49.69599 | -0.2211 | 6.95970 |
September | 485.00000 | 24.39038 | 49.04222 | -0.2368 | 6.98789 |
October | 502.00000 | 24.42462 | 49.17093 | 0.59299 | 12.92087 |
November | 489.00000 | 24.41143 | 48.79178 | 0.58914 | 12.70025 |
December | 497.00000 | 24.33892 | 48.91182 | 0.56514 | 12.02044 |
Annual Sum or Average | 5943.00000 | 24.41377 | 48.76008 | 0.26589 | 10.22152 |
Minimum of Months | 454.00000 | 24.32716 | 47.93176 | -0.2368 | 6.66429 |
Maximum of Months | 514.00000 | 24.55714 | 49.69599 | 0.61177 | 13.26713 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 24.56457 | 47.71437 | 0.65430 | 14.65420 |
February | 385.00000 | 24.59858 | 47.37412 | 0.68104 | 15.55620 |
March | 433.00000 | 24.48679 | 47.88649 | 0.66700 | 15.14221 |
April | 410.00000 | 24.55948 | 47.70095 | 0.68909 | 15.85344 |
May | 430.00000 | 24.56477 | 48.02267 | -0.1194 | 7.20305 |
June | 418.00000 | 24.51230 | 47.97033 | -0.1191 | 6.78316 |
July | 422.00000 | 24.59449 | 47.62597 | -0.1451 | 6.98480 |
August | 433.00000 | 24.46208 | 49.10472 | -0.1692 | 7.12734 |
September | 410.00000 | 24.54802 | 48.09953 | -0.1479 | 7.23345 |
October | 427.00000 | 24.52591 | 48.37036 | 0.63863 | 14.50392 |
November | 417.00000 | 24.55851 | 47.90186 | 0.64733 | 14.57286 |
December | 422.00000 | 24.54068 | 47.83863 | 0.64098 | 14.37255 |
Annual Sum or Average | 5034.00000 | 24.54231 | 47.97479 | 0.32375 | 11.63495 |
Minimum of Months | 385.00000 | 24.46208 | 47.37412 | -0.1692 | 6.78316 |
Maximum of Months | 433.00000 | 24.59858 | 49.10472 | 0.68909 | 15.85344 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.71697 | 47.14118 | 0.73460 | 17.32629 |
February | 454.00000 | 24.62971 | 47.27137 | 0.71078 | 16.46506 |
March | 514.00000 | 24.40794 | 48.40858 | 0.63393 | 13.98369 |
April | 485.00000 | 24.37673 | 48.80585 | 0.60470 | 13.05919 |
May | 508.00000 | 24.41415 | 48.99252 | -0.2104 | 6.82859 |
June | 496.00000 | 24.37190 | 48.92603 | -0.2183 | 6.80913 |
July | 497.00000 | 24.46331 | 48.44652 | -0.2208 | 7.00390 |
August | 514.00000 | 24.33730 | 49.98968 | -0.2510 | 7.06784 |
September | 485.00000 | 24.41703 | 48.87648 | -0.2166 | 6.91314 |
October | 502.00000 | 24.53897 | 48.46142 | 0.64788 | 14.66366 |
November | 489.00000 | 24.61976 | 47.62535 | 0.69243 | 15.97591 |
December | 497.00000 | 24.71449 | 47.16123 | 0.72986 | 17.25690 |
Annual Sum or Average | 5943.00000 | 24.49936 | 48.35398 | 0.29922 | 11.90598 |
Minimum of Months | 454.00000 | 24.33730 | 47.14118 | -0.2510 | 6.80913 |
Maximum of Months | 514.00000 | 24.71697 | 49.98968 | 0.73460 | 17.32629 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.45997 | 47.89408 | 0.65268 | 14.66988 |
February | 454.00000 | 24.49505 | 47.56943 | 0.67951 | 15.42856 |
March | 514.00000 | 24.44663 | 47.85987 | 0.68625 | 15.63561 |
April | 485.00000 | 24.48803 | 47.75052 | 0.70057 | 16.08687 |
May | 508.00000 | 24.46133 | 48.16180 | -0.1253 | 6.85568 |
June | 496.00000 | 24.43644 | 48.04247 | -0.1148 | 6.67497 |
July | 497.00000 | 24.52517 | 47.70916 | -0.1342 | 6.86178 |
August | 514.00000 | 24.41633 | 48.97843 | -0.1503 | 6.88007 |
September | 485.00000 | 24.42920 | 48.32434 | -0.1598 | 6.90665 |
October | 502.00000 | 24.46608 | 48.35702 | 0.64688 | 14.64726 |
November | 489.00000 | 24.48614 | 47.95142 | 0.65416 | 14.69803 |
December | 497.00000 | 24.45487 | 47.93047 | 0.64726 | 14.52450 |
Annual Sum or Average | 5943.00000 | 24.46335 | 48.05017 | 0.32861 | 11.61980 |
Minimum of Months | 454.00000 | 24.41633 | 47.56943 | -0.1598 | 6.67497 |
Maximum of Months | 514.00000 | 24.52517 | 48.97843 | 0.70057 | 16.08687 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.36276 | 49.04419 | 0.58393 | 12.61068 |
February | 454.00000 | 24.41688 | 48.61431 | 0.60813 | 13.31362 |
March | 514.00000 | 24.34830 | 49.10959 | 0.60572 | 13.17163 |
April | 485.00000 | 24.42476 | 48.87264 | 0.63509 | 14.02526 |
May | 508.00000 | 24.51118 | 48.69947 | -0.1285 | 6.95697 |
June | 496.00000 | 24.48359 | 48.32061 | -0.1033 | 6.74624 |
July | 497.00000 | 24.57130 | 48.05930 | -0.1358 | 7.01802 |
August | 514.00000 | 24.38116 | 50.11706 | -0.2053 | 6.99854 |
September | 485.00000 | 24.41122 | 49.20067 | -0.2136 | 7.04023 |
October | 502.00000 | 24.42834 | 49.39655 | 0.60311 | 13.33113 |
November | 489.00000 | 24.42258 | 49.04706 | 0.60065 | 13.11988 |
December | 497.00000 | 24.33779 | 49.19276 | 0.57205 | 12.32781 |
Annual Sum or Average | 5943.00000 | 24.42483 | 48.97877 | 0.28206 | 10.52703 |
Minimum of Months | 454.00000 | 24.33779 | 48.05930 | -0.2136 | 6.74624 |
Maximum of Months | 514.00000 | 24.57130 | 50.11706 | 0.63509 | 14.02526 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.48665 | 48.07806 | 0.65772 | 14.73292 |
February | 454.00000 | 24.51949 | 47.69415 | 0.68672 | 15.69907 |
March | 514.00000 | 24.41632 | 48.14997 | 0.67939 | 15.46091 |
April | 485.00000 | 24.48739 | 47.99922 | 0.70402 | 16.26731 |
May | 508.00000 | 24.48435 | 48.35362 | -0.1054 | 7.08876 |
June | 496.00000 | 24.44040 | 48.20636 | -0.1017 | 6.66503 |
July | 497.00000 | 24.52343 | 47.92869 | -0.1330 | 6.95146 |
August | 514.00000 | 24.38528 | 49.51190 | -0.1571 | 6.98181 |
September | 485.00000 | 24.47024 | 48.41830 | -0.1364 | 7.13851 |
October | 502.00000 | 24.44832 | 48.69601 | 0.64321 | 14.64636 |
November | 489.00000 | 24.48067 | 48.28142 | 0.65121 | 14.67008 |
December | 497.00000 | 24.45668 | 48.22160 | 0.64119 | 14.36699 |
Annual Sum or Average | 5943.00000 | 24.46581 | 48.30300 | 0.33243 | 11.68417 |
Minimum of Months | 454.00000 | 24.38528 | 47.69415 | -0.1571 | 6.66503 |
Maximum of Months | 514.00000 | 24.52343 | 49.51190 | 0.70402 | 16.26731 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.66721 | 47.51034 | 0.73180 | 17.28940 |
February | 454.00000 | 24.60550 | 47.52237 | 0.71549 | 16.67319 |
March | 514.00000 | 24.41546 | 48.60699 | 0.64873 | 14.47768 |
April | 485.00000 | 24.40880 | 48.96278 | 0.62806 | 13.81320 |
May | 508.00000 | 24.43522 | 49.18655 | -0.1839 | 6.88060 |
June | 496.00000 | 24.39188 | 49.08295 | -0.1925 | 6.81812 |
July | 497.00000 | 24.48977 | 48.55637 | -0.1975 | 7.09908 |
August | 514.00000 | 24.34048 | 50.41366 | -0.2342 | 7.08881 |
September | 485.00000 | 24.43300 | 49.04513 | -0.1950 | 6.98828 |
October | 502.00000 | 24.53067 | 48.71504 | 0.65511 | 14.98294 |
November | 489.00000 | 24.60146 | 47.92033 | 0.69726 | 16.18716 |
December | 497.00000 | 24.66145 | 47.53166 | 0.72552 | 17.17063 |
Annual Sum or Average | 5943.00000 | 24.49719 | 48.60028 | 0.31274 | 12.08126 |
Minimum of Months | 454.00000 | 24.34048 | 47.51034 | -0.2342 | 6.81812 |
Maximum of Months | 514.00000 | 24.66721 | 50.41366 | 0.73180 | 17.28940 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.41859 | 48.22130 | 0.65156 | 14.75553 |
February | 454.00000 | 24.47295 | 47.79073 | 0.68414 | 15.67730 |
March | 514.00000 | 24.43317 | 48.06909 | 0.69549 | 16.00840 |
April | 485.00000 | 24.48237 | 47.95341 | 0.71388 | 16.58259 |
May | 508.00000 | 24.44615 | 48.39014 | -0.1122 | 7.02194 |
June | 496.00000 | 24.42161 | 48.23921 | -0.1018 | 6.79618 |
July | 497.00000 | 24.50814 | 47.89404 | -0.1255 | 7.06605 |
August | 514.00000 | 24.38882 | 49.41146 | -0.1447 | 7.05133 |
September | 485.00000 | 24.40743 | 48.55117 | -0.1510 | 7.09965 |
October | 502.00000 | 24.41924 | 48.65299 | 0.64545 | 14.75490 |
November | 489.00000 | 24.45266 | 48.26019 | 0.65560 | 14.84395 |
December | 497.00000 | 24.40590 | 48.26655 | 0.64380 | 14.55244 |
Annual Sum or Average | 5943.00000 | 24.43762 | 48.31524 | 0.33460 | 11.81414 |
Minimum of Months | 454.00000 | 24.38882 | 47.79073 | -0.1510 | 6.79618 |
Maximum of Months | 514.00000 | 24.50814 | 49.41146 | 0.71388 | 16.58259 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.248790E+12 | 267448.04 | 10-JAN-13:10 | 581.61 | 0.194839E+13 | 0.00 | 0.219719E+13 | 6.74 | 10.60 | 28-JAN-05:43 | 0.00 | 0.00 |
February | 0.233620E+12 | 267789.03 | 15-FEB-11:20 | 565.39 | 0.182786E+13 | 0.00 | 0.206148E+13 | 7.29 | 10.61 | 23-FEB-05:45 | 0.00 | 0.00 |
March | 0.279874E+12 | 267544.84 | 24-MAR-12:30 | 681.75 | 0.218920E+13 | 0.00 | 0.246907E+13 | 7.90 | 10.56 | 03-MAR-00:45 | 0.00 | 0.00 |
April | 0.281581E+12 | 271253.97 | 10-APR-10:40 | 675.57 | 0.216819E+13 | 0.00 | 0.244977E+13 | 7.94 | 10.32 | 22-APR-01:00 | 0.00 | 0.00 |
May | 0.291120E+12 | 273215.82 | 04-MAY-11:40 | 657.24 | 0.220937E+13 | 0.00 | 0.250048E+13 | 7.29 | 10.26 | 08-MAY-22:20 | 0.00 | 0.00 |
June | 0.282112E+12 | 273372.11 | 10-JUN-13:40 | 655.52 | 0.215584E+13 | 0.00 | 0.243796E+13 | 7.57 | 10.33 | 25-JUN-22:02 | 0.00 | 0.00 |
July | 0.280140E+12 | 271545.46 | 17-JUL-13:30 | 671.28 | 0.213841E+13 | 0.00 | 0.241855E+13 | 7.67 | 10.40 | 19-JUL-22:07 | 0.00 | 0.00 |
August | 0.290258E+12 | 273431.62 | 16-AUG-08:20 | 675.68 | 0.218294E+13 | 0.00 | 0.247319E+13 | 7.58 | 10.49 | 20-AUG-01:00 | 0.00 | 0.00 |
September | 0.259842E+12 | 272911.07 | 08-SEP-09:30 | 605.68 | 0.199862E+13 | 0.00 | 0.225846E+13 | 7.03 | 10.32 | 15-SEP-24:00 | 0.00 | 0.00 |
October | 0.263603E+12 | 271757.70 | 13-OCT-14:20 | 628.80 | 0.201861E+13 | 0.00 | 0.228221E+13 | 7.12 | 10.39 | 22-OCT-18:10 | 0.00 | 0.00 |
November | 0.258703E+12 | 271653.13 | 08-NOV-11:00 | 624.07 | 0.197579E+13 | 0.00 | 0.223449E+13 | 7.38 | 10.57 | 25-NOV-04:02 | 0.00 | 0.00 |
December | 0.253913E+12 | 268145.11 | 08-DEC-11:00 | 647.69 | 0.197410E+13 | 0.00 | 0.222801E+13 | 7.60 | 10.61 | 27-DEC-05:43 | 0.00 | 0.00 |
Annual Sum or Average | 0.322356E+13 | 7670.29 | 0.247873E+14 | 0.00 | 0.280109E+14 | 7.43 | 0.00 | 0.00 | ||||
Minimum of Months | 0.233620E+12 | 267448.04 | 565.39 | 0.182786E+13 | 0.00 | 0.206148E+13 | 6.74 | 10.26 | 0.00 | 0.00 | ||
Maximum of Months | 0.291120E+12 | 273431.62 | 681.75 | 0.220937E+13 | 0.00 | 0.250048E+13 | 7.94 | 10.61 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.488296E+10 | 205932.78 | 03-JAN-13:13 | 17.69 | 0.425280E+11 | 0.00 | 0.474110E+11 | 0.22 | 10.77 | 24-JAN-15:00 | 0.00 | 0.00 |
February | 0.902071E+10 | 191658.81 | 13-FEB-11:13 | 28.90 | 0.787724E+11 | 0.00 | 0.877932E+11 | 0.39 | 10.90 | 21-FEB-10:20 | 0.00 | 0.00 |
March | 0.759523E+10 | 172555.86 | 31-MAR-10:13 | 26.75 | 0.661611E+11 | 0.00 | 0.737563E+11 | 0.33 | 10.53 | 15-MAR-08:20 | 0.00 | 0.00 |
April | 0.150812E+11 | 186281.27 | 17-APR-13:23 | 46.81 | 0.129771E+12 | 0.00 | 0.144852E+12 | 0.58 | 10.40 | 04-APR-09:30 | 0.00 | 0.00 |
May | 0.390109E+11 | 179840.49 | 10-MAY-11:43 | 116.25 | 0.336516E+12 | 0.00 | 0.375527E+12 | 1.37 | 10.43 | 30-MAY-15:00 | 0.00 | 0.00 |
June | 0.494449E+11 | 192735.40 | 07-JUN-16:23 | 144.89 | 0.425769E+12 | 0.00 | 0.475214E+12 | 1.76 | 10.46 | 26-JUN-18:00 | 0.00 | 0.00 |
July | 0.668032E+10 | 168265.66 | 26-JUL-14:33 | 24.69 | 0.581994E+11 | 0.00 | 0.648798E+11 | 0.31 | 10.56 | 21-JUL-07:30 | 0.00 | 0.00 |
August | 0.281621E+11 | 198534.50 | 26-AUG-05:03 | 82.33 | 0.242937E+12 | 0.00 | 0.271100E+12 | 0.97 | 10.43 | 21-AUG-11:50 | 0.00 | 0.00 |
September | 0.264300E+11 | 175456.89 | 29-SEP-11:13 | 86.11 | 0.227031E+12 | 0.00 | 0.253461E+12 | 1.07 | 10.47 | 14-SEP-16:20 | 0.00 | 0.00 |
October | 0.185833E+11 | 200363.88 | 23-OCT-05:02 | 62.02 | 0.159712E+12 | 0.00 | 0.178295E+12 | 0.75 | 10.53 | 10-OCT-07:20 | 0.00 | 0.00 |
November | 0.103445E+11 | 177620.33 | 08-NOV-13:13 | 38.34 | 0.892443E+11 | 0.00 | 0.995888E+11 | 0.49 | 10.65 | 27-NOV-08:40 | 0.00 | 0.00 |
December | 0.377608E+10 | 197661.78 | 28-DEC-14:02 | 14.97 | 0.332828E+11 | 0.00 | 0.370588E+11 | 0.19 | 10.72 | 14-DEC-08:20 | 0.00 | 0.00 |
Annual Sum or Average | 0.219012E+12 | 689.76 | 0.188992E+13 | 0.00 | 0.210894E+13 | 0.70 | 0.00 | 0.00 | ||||
Minimum of Months | 0.377608E+10 | 168265.66 | 14.97 | 0.332828E+11 | 0.00 | 0.370588E+11 | 0.19 | 10.40 | 0.00 | 0.00 | ||
Maximum of Months | 0.494449E+11 | 205932.78 | 144.89 | 0.425769E+12 | 0.00 | 0.475214E+12 | 1.76 | 10.90 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.131907E+12 | 744.00 | 49248.27 | 01-JAN-00:03 | 262401.00 | 04-JAN-15:53 | 31.98 | 27.87 | 15.94 |
February | 0.119141E+12 | 672.00 | 49248.27 | 01-FEB-00:03 | 438786.05 | 15-FEB-14:23 | 36.80 | 29.94 | 15.94 |
March | 0.131907E+12 | 744.00 | 49248.27 | 01-MAR-00:03 | 685625.79 | 31-MAR-24:00 | 41.40 | 31.78 | 15.94 |
April | 0.127652E+12 | 720.00 | 49248.27 | 01-APR-00:03 | 747851.68 | 30-APR-19:02 | 46.04 | 33.63 | 15.94 |
May | 0.131907E+12 | 744.00 | 49248.27 | 01-MAY-00:03 | 376970.17 | 31-MAY-23:15 | 34.99 | 30.57 | 15.94 |
June | 0.127652E+12 | 720.00 | 49248.27 | 01-JUN-00:03 | 526055.03 | 30-JUN-23:20 | 38.54 | 31.40 | 15.94 |
July | 0.131907E+12 | 744.00 | 49248.27 | 01-JUL-00:03 | 677219.59 | 31-JUL-24:00 | 40.28 | 30.68 | 15.94 |
August | 0.131907E+12 | 744.00 | 49248.27 | 01-AUG-00:03 | 755634.24 | 22-AUG-15:25 | 44.33 | 31.99 | 15.94 |
September | 0.127652E+12 | 720.00 | 49248.27 | 01-SEP-00:05 | 384460.02 | 30-SEP-23:17 | 33.42 | 29.10 | 15.94 |
October | 0.131907E+12 | 744.00 | 49248.27 | 01-OCT-00:03 | 524943.44 | 31-OCT-23:23 | 36.32 | 29.36 | 15.94 |
November | 0.127652E+12 | 720.00 | 49248.27 | 01-NOV-00:03 | 583717.14 | 08-NOV-14:13 | 39.65 | 30.10 | 15.94 |
December | 0.131907E+12 | 744.00 | 49248.27 | 01-DEC-00:03 | 728206.12 | 08-DEC-15:10 | 42.38 | 30.31 | 15.94 |
Annual Sum or Average | 0.155309E+13 | 8760.00 | 38.85 | 30.56 | 15.94 | ||||
Minimum of Months | 0.119141E+12 | 672.00 | 49248.27 | 262401.00 | 31.98 | 27.87 | 15.94 | ||
Maximum of Months | 0.131907E+12 | 744.00 | 49248.27 | 755634.24 | 46.04 | 33.63 | 15.94 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.479985E+11 | 581.15 | 24175.28 | 01-JAN-00:23 | 1554297.25 | 24-JAN-15:40 | 26.51 | 24.12 | 52.33 |
February | 0.481218E+11 | 565.05 | 24175.28 | 01-FEB-00:30 | 1639248.35 | 21-FEB-14:32 | 26.91 | 24.43 | 56.58 |
March | 0.587429E+11 | 681.75 | 24175.28 | 01-MAR-00:03 | 1546725.28 | 08-MAR-15:43 | 27.78 | 25.09 | 58.17 |
April | 0.587957E+11 | 675.57 | 24175.28 | 01-APR-00:03 | 1609946.56 | 12-APR-14:53 | 29.36 | 26.61 | 51.91 |
May | 0.572006E+11 | 657.24 | 24175.28 | 01-MAY-00:03 | 1561960.10 | 09-MAY-15:43 | 30.15 | 27.46 | 49.18 |
June | 0.570510E+11 | 655.52 | 24175.28 | 01-JUN-00:40 | 1578907.90 | 21-JUN-14:53 | 30.05 | 27.34 | 52.85 |
July | 0.584222E+11 | 671.28 | 24175.28 | 01-JUL-01:02 | 1565634.53 | 26-JUL-14:33 | 28.23 | 25.59 | 52.54 |
August | 0.588047E+11 | 675.68 | 24175.28 | 01-AUG-00:15 | 1467476.26 | 22-AUG-15:25 | 29.50 | 26.82 | 51.28 |
September | 0.527130E+11 | 605.68 | 24175.28 | 01-SEP-00:05 | 1443797.51 | 27-SEP-15:35 | 29.29 | 26.79 | 46.82 |
October | 0.547248E+11 | 628.80 | 24175.28 | 01-OCT-00:30 | 1565404.95 | 06-OCT-14:03 | 28.73 | 26.27 | 47.56 |
November | 0.538096E+11 | 624.07 | 24175.28 | 01-NOV-00:42 | 1545559.36 | 15-NOV-15:23 | 27.90 | 25.40 | 51.63 |
December | 0.524886E+11 | 647.18 | 24175.28 | 01-DEC-00:13 | 1715223.54 | 20-DEC-08:50 | 26.77 | 24.34 | 55.95 |
Annual Sum or Average | 0.658874E+12 | 7668.99 | 28.44 | 25.86 | 52.21 | ||||
Minimum of Months | 0.479985E+11 | 565.05 | 24175.28 | 1443797.51 | 26.51 | 24.12 | 46.82 | ||
Maximum of Months | 0.588047E+11 | 681.75 | 24175.28 | 1715223.54 | 30.15 | 27.46 | 58.17 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.210591E+11 | 241.97 | 24175.28 | 01-JAN-08:10 | 1541655.08 | 12-JAN-14:53 | 26.51 | 25.11 | 14.48 |
February | 0.211192E+11 | 242.66 | 24175.28 | 01-FEB-10:00 | 1639248.35 | 21-FEB-14:32 | 26.91 | 25.41 | 16.76 |
March | 0.301472E+11 | 346.40 | 24175.28 | 01-MAR-04:08 | 1546725.28 | 08-MAR-15:43 | 27.78 | 25.90 | 20.79 |
April | 0.432132E+11 | 496.53 | 24175.28 | 01-APR-00:03 | 1609946.56 | 12-APR-14:53 | 29.36 | 26.88 | 31.30 |
May | 0.477410E+11 | 548.55 | 24175.28 | 01-MAY-00:03 | 1561960.10 | 09-MAY-15:43 | 30.15 | 27.56 | 37.06 |
June | 0.468362E+11 | 538.16 | 24175.28 | 01-JUN-03:28 | 1578907.90 | 21-JUN-14:53 | 30.05 | 27.46 | 39.33 |
July | 0.369432E+11 | 424.48 | 24175.28 | 01-JUL-03:47 | 1565634.53 | 26-JUL-14:33 | 28.23 | 25.99 | 25.04 |
August | 0.447072E+11 | 513.69 | 24175.28 | 01-AUG-03:04 | 1467476.26 | 22-AUG-15:25 | 29.50 | 26.96 | 33.23 |
September | 0.421704E+11 | 484.54 | 24175.28 | 01-SEP-03:06 | 1443797.51 | 27-SEP-15:35 | 29.29 | 26.93 | 32.87 |
October | 0.405821E+11 | 466.29 | 24175.28 | 01-OCT-06:16 | 1565404.95 | 06-OCT-14:03 | 28.73 | 26.46 | 29.45 |
November | 0.339341E+11 | 389.91 | 24175.28 | 01-NOV-03:08 | 1545559.36 | 15-NOV-15:23 | 27.90 | 25.82 | 24.66 |
December | 0.266631E+11 | 306.36 | 24175.28 | 01-DEC-07:50 | 1371863.23 | 27-DEC-16:35 | 26.77 | 25.08 | 17.91 |
Annual Sum or Average | 0.435116E+12 | 4999.55 | 28.44 | 26.30 | 26.93 | ||||
Minimum of Months | 0.210591E+11 | 241.97 | 24175.28 | 1371863.23 | 26.51 | 25.08 | 14.48 | ||
Maximum of Months | 0.477410E+11 | 548.55 | 24175.28 | 1639248.35 | 30.15 | 27.56 | 39.33 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 31.98 | 31.98 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 36.80 | 36.80 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 41.40 | 41.40 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 46.04 | 46.04 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 34.99 | 34.99 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 38.54 | 38.54 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 40.28 | 40.28 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 44.33 | 44.33 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 33.42 | 33.42 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 36.32 | 36.32 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 39.65 | 39.65 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 42.38 | 42.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 38.85 | 38.85 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.98 | 31.98 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.04 | 46.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.221479E+12 | 0.00 | 560.66 | 0.171902E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 228378.83 | 03-JAN-06:02 | 172027.60 | 03-JAN-06:02 | 0.00 | 0.00 | 0.00 |
February | 0.221207E+12 | 0.00 | 543.53 | 0.173476E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 229497.96 | 21-FEB-06:02 | 180125.09 | 21-FEB-06:02 | 0.00 | 0.00 | 0.00 |
March | 0.278285E+12 | 0.00 | 648.03 | 0.219481E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 254266.46 | 27-MAR-05:03 | 182938.49 | 27-MAR-05:03 | 0.00 | 0.00 | 0.00 |
April | 0.275314E+12 | 0.00 | 631.06 | 0.214541E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 242149.85 | 24-APR-05:03 | 185651.16 | 03-APR-05:03 | 0.00 | 0.00 | 0.00 |
May | 0.278418E+12 | 0.00 | 613.49 | 0.203373E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 258339.63 | 13-MAY-05:02 | 185770.47 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.288901E+12 | 0.00 | 613.92 | 0.212463E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 262126.23 | 12-JUN-05:02 | 184878.94 | 19-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.277108E+12 | 0.00 | 632.14 | 0.204068E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 243472.94 | 10-JUL-05:02 | 179241.07 | 10-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.307076E+12 | 0.00 | 648.25 | 0.220248E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 259677.05 | 14-AUG-05:02 | 180918.49 | 14-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.256164E+12 | 0.00 | 573.98 | 0.183453E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 256567.29 | 30-SEP-05:02 | 177264.86 | 08-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.266280E+12 | 0.00 | 596.92 | 0.188969E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 252194.64 | 05-OCT-05:02 | 176615.92 | 05-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.262212E+12 | 0.00 | 593.58 | 0.193339E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 248868.46 | 13-NOV-06:02 | 179528.30 | 13-NOV-06:02 | 0.00 | 0.00 | 0.00 |
December | 0.252968E+12 | 0.00 | 622.50 | 0.189640E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 232212.45 | 11-DEC-06:03 | 171338.30 | 11-DEC-06:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.318541E+13 | 0.00 | 7278.06 | 0.237495E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.221207E+12 | 0.00 | 543.53 | 0.171902E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 228378.83 | 171338.30 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.307076E+12 | 0.00 | 648.25 | 0.220248E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 262126.23 | 185770.47 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.154828E+13 | 0.00 | 476.22 | 0.115836E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2096738.26 | 02-JAN-05:12 | 1529458.46 | 04-JAN-04:02 | 0.00 | 0.00 | 0.00 |
February | 0.147968E+13 | 0.00 | 449.54 | 0.111280E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2085828.29 | 13-FEB-05:02 | 1507707.39 | 25-FEB-04:02 | 0.00 | 0.00 | 0.00 |
March | 0.176258E+13 | 0.00 | 544.89 | 0.131059E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2022368.65 | 15-MAR-04:12 | 1473812.73 | 02-MAR-05:12 | 0.00 | 0.00 | 0.00 |
April | 0.177370E+13 | 0.00 | 538.47 | 0.125185E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1917980.46 | 21-APR-05:02 | 1479186.01 | 21-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.193809E+13 | 0.00 | 534.40 | 0.128786E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2146205.95 | 22-MAY-03:02 | 1542728.77 | 03-MAY-03:02 | 0.00 | 0.00 | 0.00 |
June | 0.197363E+13 | 0.00 | 528.01 | 0.132092E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2209405.10 | 02-JUN-03:02 | 1483322.69 | 22-JUN-03:02 | 0.00 | 0.00 | 0.00 |
July | 0.167992E+13 | 0.00 | 503.08 | 0.115192E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2105310.08 | 27-JUL-03:02 | 1491070.02 | 20-JUL-04:12 | 0.00 | 0.00 | 0.00 |
August | 0.183034E+13 | 0.00 | 514.34 | 0.120162E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2274952.02 | 26-AUG-05:03 | 1484915.05 | 16-AUG-03:02 | 0.00 | 0.00 | 0.00 |
September | 0.169506E+13 | 0.00 | 490.33 | 0.112222E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2098778.08 | 07-SEP-03:02 | 1470697.65 | 27-SEP-03:02 | 0.00 | 0.00 | 0.00 |
October | 0.166758E+13 | 0.00 | 482.42 | 0.110064E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2304010.64 | 23-OCT-05:02 | 1459113.06 | 06-OCT-03:02 | 0.00 | 0.00 | 0.00 |
November | 0.159413E+13 | 0.00 | 463.11 | 0.110856E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2079389.44 | 08-NOV-04:02 | 1538932.26 | 14-NOV-04:02 | 0.00 | 0.00 | 0.00 |
December | 0.152234E+13 | 0.00 | 465.13 | 0.110880E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2080579.11 | 11-DEC-05:12 | 1464905.89 | 07-DEC-05:12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204653E+14 | 0.00 | 5989.96 | 0.142361E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.147968E+13 | 0.00 | 449.54 | 0.110064E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1917980.46 | 1459113.06 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.197363E+13 | 0.00 | 544.89 | 0.132092E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2304010.64 | 1542728.77 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.162432E+12 | 0.00 | 473.88 | 0.123749E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 217674.90 | 02-JAN-05:12 | 153548.73 | 05-JAN-04:02 | 0.00 | 0.00 | 0.00 |
February | 0.156623E+12 | 0.00 | 447.01 | 0.120586E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 218891.57 | 13-FEB-05:02 | 153925.31 | 17-FEB-05:12 | 0.00 | 0.00 | 0.00 |
March | 0.189574E+12 | 0.00 | 542.28 | 0.144386E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 214702.27 | 01-MAR-04:02 | 150240.56 | 07-MAR-06:02 | 0.00 | 0.00 | 0.00 |
April | 0.192250E+12 | 0.00 | 538.42 | 0.139652E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 215864.86 | 14-APR-03:02 | 164697.58 | 14-APR-03:02 | 0.00 | 0.00 | 0.00 |
May | 0.208681E+12 | 0.00 | 537.33 | 0.142707E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 232161.77 | 19-MAY-03:02 | 165735.94 | 03-MAY-03:02 | 0.00 | 0.00 | 0.00 |
June | 0.212414E+12 | 0.00 | 532.08 | 0.146200E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 233572.78 | 02-JUN-03:02 | 159833.25 | 27-JUN-04:12 | 0.00 | 0.00 | 0.00 |
July | 0.179358E+12 | 0.00 | 507.20 | 0.126024E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 230679.88 | 27-JUL-03:02 | 162439.95 | 06-JUL-03:02 | 0.00 | 0.00 | 0.00 |
August | 0.194129E+12 | 0.00 | 514.16 | 0.130892E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 247004.50 | 26-AUG-05:03 | 160645.65 | 08-AUG-03:02 | 0.00 | 0.00 | 0.00 |
September | 0.181639E+12 | 0.00 | 493.54 | 0.123511E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 242521.90 | 18-SEP-03:02 | 163519.46 | 26-SEP-03:02 | 0.00 | 0.00 | 0.00 |
October | 0.175362E+12 | 0.00 | 487.95 | 0.118615E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 236739.11 | 23-OCT-05:02 | 159103.79 | 10-OCT-03:02 | 0.00 | 0.00 | 0.00 |
November | 0.167222E+12 | 0.00 | 463.13 | 0.118974E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 215075.47 | 08-NOV-04:02 | 153513.78 | 14-NOV-04:02 | 0.00 | 0.00 | 0.00 |
December | 0.159173E+12 | 0.00 | 463.93 | 0.117945E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 213882.73 | 11-DEC-05:12 | 153747.07 | 04-DEC-05:12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.217886E+13 | 0.00 | 6000.93 | 0.155324E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.156623E+12 | 0.00 | 447.01 | 0.117945E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 213882.73 | 150240.56 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.212414E+12 | 0.00 | 542.28 | 0.146200E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 247004.50 | 165735.94 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.288210E+11 | 0.00 | 74.27 | 0.222745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 276547.64 | 07-JAN-04:03 | 108460.74 | 17-JAN-05:23 | 0.00 | 0.00 | 0.00 |
February | 0.197648E+11 | 0.00 | 43.00 | 0.146699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 273259.19 | 12-FEB-06:43 | 112985.64 | 21-FEB-14:45 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 |
April | 0.297165E+10 | 0.00 | 5.00 | 0.165935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 286037.81 | 14-APR-16:02 | 100171.65 | 14-APR-21:00 | 0.00 | 0.00 | 0.00 |
May | 0.771089E+09 | 0.00 | 1.00 | 0.274114E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 280557.99 | 10-MAY-20:02 | 84026.70 | 10-MAY-20:50 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 |
November | 0.563726E+10 | 0.00 | 12.00 | 0.405685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 275505.70 | 25-NOV-04:43 | 99645.81 | 25-NOV-12:00 | 0.00 | 0.00 | 0.00 |
December | 0.304535E+11 | 0.00 | 65.34 | 0.203721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 281861.64 | 07-DEC-02:42 | 109932.84 | 21-DEC-01:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.884194E+11 | 0.00 | 200.61 | 0.633068E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.304535E+11 | 0.00 | 74.27 | 0.222745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 286037.81 | 112985.64 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.376601E+12 | 0.122632E+12 | 744.00 | 0.355324E+12 | 0.212776E+11 | 0.00 | 0.37 | 11-JAN-15:00 | 0.30 | 23-JAN-06:00 | 149624.57 | 11-JAN-17:00 | 138866.68 | 05-JAN-15:00 | 12431.10 | 11-JAN-17:10 | 57993.91 | 04-JAN-13:20 | 0.00 |
February | 0.564031E+12 | 0.186028E+12 | 672.00 | 0.543436E+12 | 0.205953E+11 | 0.00 | 0.58 | 28-FEB-15:00 | 0.50 | 01-FEB-07:00 | 243121.41 | 13-FEB-16:43 | 230545.44 | 28-FEB-15:00 | 14711.33 | 15-FEB-15:00 | 96022.84 | 28-FEB-15:00 | 0.00 |
March | 0.874285E+12 | 0.291700E+12 | 744.00 | 0.849334E+12 | 0.249505E+11 | 0.00 | 0.91 | 31-MAR-24:00 | 0.70 | 03-MAR-06:00 | 415646.59 | 31-MAR-23:03 | 403188.79 | 31-MAR-24:00 | 15062.02 | 14-MAR-11:00 | 134623.81 | 21-MAR-13:10 | 0.00 |
April | 0.108915E+13 | 0.368219E+12 | 720.00 | 0.105971E+13 | 0.294404E+11 | 0.00 | 0.98 | 11-APR-14:00 | 0.37 | 30-APR-23:12 | 429667.92 | 10-APR-16:00 | 414602.31 | 11-APR-16:00 | 16544.91 | 10-APR-16:10 | 166495.36 | 26-APR-14:00 | 0.00 |
May | 0.396025E+12 | 0.137051E+12 | 744.00 | 0.360601E+12 | 0.354238E+11 | 0.00 | 0.53 | 31-MAY-23:03 | 0.33 | 10-MAY-21:10 | 234692.31 | 31-MAY-23:03 | 218442.63 | 31-MAY-24:00 | 17913.40 | 03-MAY-14:00 | 68848.94 | 31-MAY-23:12 | 0.00 |
June | 0.621679E+12 | 0.211524E+12 | 720.00 | 0.585837E+12 | 0.358416E+11 | 0.00 | 0.72 | 30-JUN-23:05 | 0.52 | 01-JUN-02:00 | 325592.09 | 30-JUN-23:05 | 310628.60 | 30-JUN-24:00 | 18465.98 | 15-JUN-10:20 | 100731.86 | 13-JUN-15:00 | 0.00 |
July | 0.877711E+12 | 0.283867E+12 | 744.00 | 0.848878E+12 | 0.288332E+11 | 0.00 | 0.90 | 31-JUL-24:00 | 0.71 | 13-JUL-05:00 | 415906.30 | 31-JUL-23:03 | 402700.09 | 31-JUL-24:00 | 17132.82 | 17-JUL-15:50 | 127095.32 | 31-JUL-24:00 | 0.00 |
August | 0.112969E+13 | 0.365677E+12 | 744.00 | 0.109452E+13 | 0.351713E+11 | 0.00 | 0.98 | 22-AUG-15:00 | 0.37 | 31-AUG-23:15 | 431931.77 | 07-AUG-14:30 | 414553.39 | 10-AUG-14:00 | 19935.00 | 07-AUG-14:40 | 163324.05 | 10-AUG-14:00 | 0.00 |
September | 0.379226E+12 | 0.126360E+12 | 720.00 | 0.347577E+12 | 0.316487E+11 | 0.00 | 0.54 | 30-SEP-23:02 | 0.33 | 16-SEP-20:00 | 236529.38 | 30-SEP-23:02 | 218806.68 | 30-SEP-23:57 | 18373.98 | 30-SEP-23:02 | 73743.13 | 30-SEP-23:13 | 0.00 |
October | 0.634845E+12 | 0.204841E+12 | 744.00 | 0.602035E+12 | 0.328100E+11 | 0.00 | 0.72 | 31-OCT-23:20 | 0.52 | 23-OCT-05:00 | 323922.03 | 31-OCT-23:10 | 310347.09 | 31-OCT-23:53 | 16695.14 | 06-OCT-10:00 | 98517.54 | 31-OCT-23:20 | 0.00 |
November | 0.848201E+12 | 0.270180E+12 | 720.00 | 0.820039E+12 | 0.281619E+11 | 0.00 | 0.77 | 10-NOV-14:00 | 0.69 | 25-NOV-05:30 | 337108.66 | 14-NOV-16:20 | 321393.74 | 13-NOV-14:00 | 16422.38 | 14-NOV-16:50 | 126352.08 | 18-NOV-13:00 | 0.00 |
December | 0.111529E+13 | 0.347043E+12 | 744.00 | 0.109146E+13 | 0.238252E+11 | 0.00 | 0.96 | 08-DEC-15:00 | 0.85 | 21-DEC-06:00 | 426501.26 | 12-DEC-16:50 | 413928.19 | 08-DEC-15:00 | 15657.42 | 18-DEC-17:10 | 157525.54 | 08-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.890674E+13 | 0.291512E+13 | 8760.00 | 0.855876E+13 | 0.347980E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.376601E+12 | 0.122632E+12 | 672.00 | 0.347577E+12 | 0.205953E+11 | 0.00 | 0.37 | 0.30 | 149624.57 | 138866.68 | 12431.10 | 57993.91 | 0.00 | ||||||
Maximum of Months | 0.112969E+13 | 0.368219E+12 | 744.00 | 0.109452E+13 | 0.358416E+11 | 0.00 | 0.98 | 0.85 | 431931.77 | 414602.31 | 19935.00 | 166495.36 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.718984E+10 | 0.224404E+10 | 744.00 | 0.631271E+10 | 0.877135E+09 | 0.00 | 0.40 | 16-JAN-17:35 | 0.26 | 24-JAN-07:00 | 3211.45 | 16-JAN-17:40 | 2950.68 | 16-JAN-17:40 | 518.38 | 10-JAN-10:10 | 1150.64 | 05-JAN-15:00 | 0.00 |
February | 0.112465E+11 | 0.355423E+10 | 672.00 | 0.103550E+11 | 0.891503E+09 | 0.00 | 0.63 | 13-FEB-15:40 | 0.49 | 01-FEB-07:00 | 5231.53 | 13-FEB-16:43 | 4831.41 | 20-FEB-17:40 | 589.46 | 15-FEB-15:00 | 1926.87 | 28-FEB-15:00 | 0.00 |
March | 0.177538E+11 | 0.566590E+10 | 744.00 | 0.166448E+11 | 0.110901E+10 | 0.00 | 0.95 | 31-MAR-23:25 | 0.71 | 03-MAR-07:00 | 8522.97 | 31-MAR-23:03 | 7945.59 | 31-MAR-23:33 | 615.39 | 14-MAR-11:00 | 2664.93 | 21-MAR-14:00 | 0.00 |
April | 0.223121E+11 | 0.717572E+10 | 720.00 | 0.209653E+11 | 0.134680E+10 | 0.00 | 1.00 | 01-APR-12:50 | 0.40 | 30-APR-23:12 | 9058.43 | 09-APR-16:00 | 8446.30 | 09-APR-16:00 | 744.19 | 10-APR-16:20 | 3191.54 | 01-APR-14:00 | 0.00 |
May | 0.804418E+10 | 0.263049E+10 | 744.00 | 0.655714E+10 | 0.148704E+10 | 0.00 | 0.55 | 31-MAY-23:03 | 0.30 | 25-MAY-21:20 | 4819.48 | 31-MAY-23:03 | 4100.53 | 31-MAY-24:00 | 764.89 | 31-MAY-23:03 | 1328.58 | 31-MAY-23:07 | 0.00 |
June | 0.128112E+11 | 0.413789E+10 | 720.00 | 0.112485E+11 | 0.156264E+10 | 0.00 | 0.74 | 30-JUN-23:05 | 0.52 | 27-JUN-06:00 | 6622.68 | 30-JUN-23:05 | 5985.99 | 30-JUN-23:45 | 826.17 | 15-JUN-10:20 | 2073.33 | 13-JUN-15:00 | 0.00 |
July | 0.178395E+11 | 0.551106E+10 | 744.00 | 0.165549E+11 | 0.128458E+10 | 0.00 | 0.94 | 31-JUL-24:00 | 0.71 | 19-JUL-21:20 | 8502.86 | 31-JUL-23:03 | 7908.59 | 31-JUL-24:00 | 717.98 | 10-JUL-15:00 | 2510.59 | 21-JUL-15:00 | 0.00 |
August | 0.231321E+11 | 0.712391E+10 | 744.00 | 0.215260E+11 | 0.160610E+10 | 0.00 | 1.00 | 01-AUG-08:50 | 0.36 | 31-AUG-23:15 | 9208.15 | 07-AUG-15:00 | 8431.72 | 06-AUG-15:58 | 890.35 | 15-AUG-14:00 | 3116.76 | 13-AUG-15:00 | 0.00 |
September | 0.755744E+10 | 0.238579E+10 | 720.00 | 0.623203E+10 | 0.132541E+10 | 0.00 | 0.56 | 30-SEP-23:02 | 0.30 | 15-SEP-21:20 | 4914.00 | 30-SEP-23:02 | 4141.38 | 30-SEP-23:45 | 810.42 | 30-SEP-23:02 | 1438.89 | 30-SEP-23:13 | 0.00 |
October | 0.128488E+11 | 0.394814E+10 | 744.00 | 0.114243E+11 | 0.142448E+10 | 0.00 | 0.74 | 31-OCT-23:20 | 0.52 | 23-OCT-06:00 | 6586.41 | 31-OCT-23:10 | 5986.06 | 31-OCT-23:50 | 701.47 | 16-OCT-10:20 | 1905.89 | 31-OCT-23:20 | 0.00 |
November | 0.172136E+11 | 0.523991E+10 | 720.00 | 0.159592E+11 | 0.125438E+10 | 0.00 | 0.84 | 11-NOV-15:02 | 0.69 | 25-NOV-07:20 | 7218.15 | 20-NOV-17:00 | 6688.59 | 19-NOV-16:54 | 721.53 | 14-NOV-16:50 | 2445.46 | 11-NOV-14:22 | 0.00 |
December | 0.225319E+11 | 0.671650E+10 | 744.00 | 0.214393E+11 | 0.109260E+10 | 0.00 | 1.00 | 01-DEC-14:20 | 0.85 | 21-DEC-07:00 | 9016.49 | 25-DEC-18:05 | 8539.64 | 03-DEC-17:20 | 706.55 | 18-DEC-17:00 | 3054.36 | 08-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.180481E+12 | 0.563336E+11 | 8760.00 | 0.165219E+12 | 0.152617E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.718984E+10 | 0.224404E+10 | 672.00 | 0.623203E+10 | 0.877135E+09 | 0.00 | 0.40 | 0.26 | 3211.45 | 2950.68 | 518.38 | 1150.64 | 0.00 | ||||||
Maximum of Months | 0.231321E+11 | 0.717572E+10 | 744.00 | 0.215260E+11 | 0.160610E+10 | 0.00 | 1.00 | 0.85 | 9208.15 | 8539.64 | 890.35 | 3191.54 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.655332E+11 | 0.205094E+11 | 744.00 | 0.569184E+11 | 0.861476E+10 | 0.00 | 0.39 | 31-JAN-17:00 | 0.24 | 24-JAN-07:00 | 29962.02 | 30-JAN-17:00 | 26131.01 | 31-JAN-17:00 | 5179.85 | 10-JAN-10:10 | 10742.14 | 05-JAN-15:00 | 0.00 |
February | 0.104981E+12 | 0.332263E+11 | 672.00 | 0.961274E+11 | 0.885309E+10 | 0.00 | 0.62 | 13-FEB-15:50 | 0.48 | 01-FEB-07:00 | 49127.26 | 13-FEB-16:43 | 44827.27 | 24-FEB-17:00 | 5827.56 | 15-FEB-15:00 | 18163.54 | 28-FEB-15:00 | 0.00 |
March | 0.166221E+12 | 0.531441E+11 | 744.00 | 0.155174E+12 | 0.110469E+11 | 0.00 | 0.95 | 31-MAR-23:15 | 0.69 | 04-MAR-07:00 | 80907.14 | 31-MAR-23:03 | 75179.41 | 31-MAR-23:45 | 6205.71 | 31-MAR-23:03 | 25081.44 | 21-MAR-14:00 | 0.00 |
April | 0.209723E+12 | 0.676423E+11 | 720.00 | 0.196255E+12 | 0.134675E+11 | 0.00 | 1.00 | 01-APR-13:30 | 0.32 | 30-APR-23:12 | 85850.26 | 20-APR-15:50 | 79278.17 | 23-APR-17:53 | 7395.86 | 20-APR-16:00 | 30443.41 | 01-APR-14:00 | 0.00 |
May | 0.726833E+11 | 0.238054E+11 | 744.00 | 0.580938E+11 | 0.145895E+11 | 0.00 | 0.55 | 31-MAY-23:03 | 0.27 | 25-MAY-21:12 | 46406.69 | 31-MAY-23:03 | 38969.11 | 31-MAY-24:00 | 7987.72 | 31-MAY-23:03 | 12763.38 | 31-MAY-23:12 | 0.00 |
June | 0.119249E+12 | 0.385623E+11 | 720.00 | 0.103738E+12 | 0.155113E+11 | 0.00 | 0.74 | 30-JUN-23:05 | 0.50 | 26-JUN-06:00 | 62654.52 | 30-JUN-23:05 | 55916.33 | 30-JUN-24:00 | 8222.26 | 15-JUN-10:10 | 19467.76 | 13-JUN-15:00 | 0.00 |
July | 0.166798E+12 | 0.516216E+11 | 744.00 | 0.154004E+12 | 0.127938E+11 | 0.00 | 0.93 | 31-JUL-23:15 | 0.70 | 22-JUL-07:00 | 80926.47 | 31-JUL-23:03 | 74822.76 | 31-JUL-24:00 | 7143.94 | 10-JUL-15:00 | 23702.62 | 21-JUL-15:00 | 0.00 |
August | 0.218008E+12 | 0.672733E+11 | 744.00 | 0.201959E+12 | 0.160490E+11 | 0.00 | 1.00 | 01-AUG-09:40 | 0.32 | 31-AUG-23:15 | 87000.73 | 15-AUG-14:00 | 78875.07 | 22-AUG-16:00 | 8946.35 | 15-AUG-14:00 | 29720.00 | 10-AUG-14:00 | 0.00 |
September | 0.678573E+11 | 0.214734E+11 | 720.00 | 0.548773E+11 | 0.129801E+11 | 0.00 | 0.55 | 30-SEP-23:02 | 0.26 | 16-SEP-07:00 | 46313.65 | 30-SEP-23:02 | 38360.69 | 30-SEP-23:45 | 8495.67 | 30-SEP-23:02 | 13537.04 | 30-SEP-23:13 | 0.00 |
October | 0.119219E+12 | 0.366946E+11 | 744.00 | 0.105088E+12 | 0.141310E+11 | 0.00 | 0.74 | 31-OCT-23:10 | 0.49 | 30-OCT-21:20 | 62260.81 | 31-OCT-23:10 | 56035.81 | 31-OCT-23:53 | 6984.65 | 16-OCT-10:20 | 17980.61 | 31-OCT-23:20 | 0.00 |
November | 0.161473E+12 | 0.492237E+11 | 720.00 | 0.148975E+12 | 0.124973E+11 | 0.00 | 0.82 | 20-NOV-17:00 | 0.67 | 25-NOV-07:30 | 67871.22 | 20-NOV-17:00 | 62289.30 | 20-NOV-17:00 | 7191.52 | 14-NOV-16:50 | 22960.54 | 13-NOV-14:00 | 0.00 |
December | 0.212780E+12 | 0.635166E+11 | 744.00 | 0.201859E+12 | 0.109207E+11 | 0.00 | 1.00 | 01-DEC-14:50 | 0.84 | 21-DEC-07:00 | 85224.64 | 29-DEC-17:00 | 80296.95 | 15-DEC-17:00 | 7053.43 | 18-DEC-17:00 | 29134.09 | 08-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.168452E+13 | 0.526693E+12 | 8760.00 | 0.153307E+13 | 0.151455E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.655332E+11 | 0.205094E+11 | 672.00 | 0.548773E+11 | 0.861476E+10 | 0.00 | 0.39 | 0.24 | 29962.02 | 26131.01 | 5179.85 | 10742.14 | 0.00 | ||||||
Maximum of Months | 0.218008E+12 | 0.676423E+11 | 744.00 | 0.201959E+12 | 0.160490E+11 | 0.00 | 1.00 | 0.84 | 87000.73 | 80296.95 | 8946.35 | 30443.41 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.660352E+10 | 0.207149E+10 | 744.00 | 0.574182E+10 | 0.861700E+09 | 0.00 | 0.39 | 31-JAN-17:00 | 0.21 | 24-JAN-08:00 | 3082.04 | 30-JAN-17:00 | 2738.99 | 16-JAN-17:40 | 523.70 | 10-JAN-10:10 | 1105.48 | 05-JAN-15:00 | 0.00 |
February | 0.105704E+11 | 0.335185E+10 | 672.00 | 0.968546E+10 | 0.884985E+09 | 0.00 | 0.63 | 13-FEB-15:50 | 0.46 | 24-FEB-07:00 | 5008.50 | 13-FEB-16:43 | 4582.06 | 24-FEB-17:00 | 585.35 | 15-FEB-15:00 | 1855.29 | 28-FEB-15:00 | 0.00 |
March | 0.167481E+11 | 0.536393E+10 | 744.00 | 0.156440E+11 | 0.110415E+10 | 0.00 | 0.93 | 31-MAR-23:15 | 0.67 | 04-MAR-07:20 | 8111.08 | 31-MAR-23:03 | 7539.31 | 31-MAR-23:45 | 619.25 | 31-MAR-23:03 | 2557.15 | 21-MAR-14:00 | 0.00 |
April | 0.211333E+11 | 0.682995E+10 | 720.00 | 0.197870E+11 | 0.134630E+10 | 0.00 | 1.00 | 01-APR-13:40 | 0.33 | 30-APR-23:12 | 8709.75 | 13-APR-15:10 | 8107.65 | 23-APR-17:53 | 743.95 | 10-APR-16:20 | 3098.51 | 01-APR-14:00 | 0.00 |
May | 0.742831E+10 | 0.243645E+10 | 744.00 | 0.596409E+10 | 0.146421E+10 | 0.00 | 0.54 | 31-MAY-23:03 | 0.26 | 25-MAY-21:12 | 4655.18 | 31-MAY-23:03 | 3917.00 | 31-MAY-24:00 | 794.76 | 31-MAY-23:03 | 1282.87 | 31-MAY-23:12 | 0.00 |
June | 0.120619E+11 | 0.390572E+10 | 720.00 | 0.105099E+11 | 0.155207E+10 | 0.00 | 0.72 | 30-JUN-23:05 | 0.49 | 30-JUN-21:12 | 6195.13 | 30-JUN-23:05 | 5524.04 | 30-JUN-24:00 | 823.68 | 15-JUN-10:20 | 1993.42 | 13-JUN-15:10 | 0.00 |
July | 0.167943E+11 | 0.520629E+10 | 744.00 | 0.155155E+11 | 0.127874E+10 | 0.00 | 0.92 | 31-JUL-23:15 | 0.68 | 22-JUL-07:00 | 8099.83 | 31-JUL-23:03 | 7492.96 | 31-JUL-24:00 | 714.40 | 10-JUL-15:00 | 2407.20 | 21-JUL-15:00 | 0.00 |
August | 0.219047E+11 | 0.677623E+10 | 744.00 | 0.203005E+11 | 0.160422E+10 | 0.00 | 1.00 | 01-AUG-10:40 | 0.32 | 31-AUG-23:15 | 8822.90 | 15-AUG-14:00 | 8083.33 | 13-AUG-17:50 | 890.75 | 15-AUG-14:00 | 3024.51 | 13-AUG-15:00 | 0.00 |
September | 0.691469E+10 | 0.219084E+10 | 720.00 | 0.561258E+10 | 0.130211E+10 | 0.00 | 0.55 | 30-SEP-23:02 | 0.24 | 16-SEP-07:00 | 4706.37 | 30-SEP-23:02 | 3877.65 | 30-SEP-23:13 | 840.20 | 30-SEP-23:02 | 1375.13 | 30-SEP-23:13 | 0.00 |
October | 0.119948E+11 | 0.369806E+10 | 744.00 | 0.105821E+11 | 0.141272E+10 | 0.00 | 0.72 | 31-OCT-23:10 | 0.47 | 30-OCT-21:12 | 6213.90 | 31-OCT-23:10 | 5595.32 | 31-OCT-23:53 | 700.46 | 16-OCT-10:20 | 1798.95 | 31-OCT-23:20 | 0.00 |
November | 0.162070E+11 | 0.495065E+10 | 720.00 | 0.149583E+11 | 0.124866E+10 | 0.00 | 0.82 | 20-NOV-17:00 | 0.65 | 25-NOV-07:40 | 6873.54 | 20-NOV-17:00 | 6315.62 | 20-NOV-17:00 | 718.57 | 14-NOV-16:50 | 2326.46 | 13-NOV-14:00 | 0.00 |
December | 0.213192E+11 | 0.638074E+10 | 744.00 | 0.202284E+11 | 0.109076E+10 | 0.00 | 1.00 | 05-DEC-15:00 | 0.81 | 21-DEC-07:00 | 8611.21 | 10-DEC-17:05 | 8120.92 | 25-DEC-17:00 | 704.20 | 18-DEC-17:00 | 2964.97 | 08-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.169680E+12 | 0.531622E+11 | 8760.00 | 0.154530E+12 | 0.151506E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.660352E+10 | 0.207149E+10 | 672.00 | 0.561258E+10 | 0.861700E+09 | 0.00 | 0.39 | 0.21 | 3082.04 | 2738.99 | 523.70 | 1105.48 | 0.00 | ||||||
Maximum of Months | 0.219047E+11 | 0.682995E+10 | 744.00 | 0.203005E+11 | 0.160422E+10 | 0.00 | 1.00 | 0.81 | 8822.90 | 8120.92 | 890.75 | 3098.51 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.82 | 0.00 | 142.82 | 311.23 | 90.25 | 0.00 | 0.00 | 0.00 |
February | 152.35 | 0.00 | 152.35 | 347.96 | 74.11 | 0.00 | 0.00 | 0.00 |
March | 156.36 | 0.00 | 156.36 | 376.72 | 56.75 | 0.00 | 0.00 | 0.00 |
April | 170.16 | 2.41 | 167.75 | 418.68 | 31.40 | 0.00 | 0.00 | 0.00 |
May | 218.12 | 23.24 | 194.89 | 544.03 | 33.39 | 0.00 | 0.00 | 0.00 |
June | 266.44 | 53.85 | 212.60 | 650.17 | 38.83 | 0.00 | 0.00 | 0.00 |
July | 229.12 | 24.02 | 205.10 | 507.54 | 59.77 | 0.00 | 0.00 | 0.00 |
August | 188.64 | 8.04 | 180.59 | 419.60 | 51.53 | 0.00 | 0.00 | 0.00 |
September | 160.60 | 0.08 | 160.53 | 370.02 | 48.91 | 0.00 | 0.00 | 0.00 |
October | 154.75 | 0.00 | 154.75 | 328.34 | 60.76 | 0.00 | 0.00 | 0.00 |
November | 146.43 | 0.00 | 146.43 | 312.28 | 70.75 | 0.00 | 0.00 | 0.00 |
December | 138.75 | 0.00 | 138.75 | 295.82 | 101.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 177.15 | 9.33 | 167.82 | 407.01 | 59.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 138.75 | 0.00 | 138.75 | 295.82 | 31.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 266.44 | 53.85 | 212.60 | 650.17 | 101.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.82 | 0.00 | 142.82 | 311.23 | 90.25 | 0.00 | 0.00 | 0.00 |
February | 152.35 | 0.00 | 152.35 | 347.96 | 74.11 | 0.00 | 0.00 | 0.00 |
March | 156.36 | 0.00 | 156.36 | 376.72 | 56.75 | 0.00 | 0.00 | 0.00 |
April | 170.16 | 2.41 | 167.75 | 418.68 | 31.40 | 0.00 | 0.00 | 0.00 |
May | 218.12 | 23.24 | 194.89 | 544.03 | 33.39 | 0.00 | 0.00 | 0.00 |
June | 266.44 | 53.85 | 212.60 | 650.17 | 38.83 | 0.00 | 0.00 | 0.00 |
July | 229.12 | 24.02 | 205.10 | 507.53 | 59.77 | 0.00 | 0.00 | 0.00 |
August | 188.64 | 8.04 | 180.59 | 419.60 | 51.53 | 0.00 | 0.00 | 0.00 |
September | 160.60 | 0.08 | 160.53 | 370.02 | 48.91 | 0.00 | 0.00 | 0.00 |
October | 154.75 | 0.00 | 154.75 | 328.34 | 60.76 | 0.00 | 0.00 | 0.00 |
November | 146.43 | 0.00 | 146.43 | 312.28 | 70.75 | 0.00 | 0.00 | 0.00 |
December | 138.75 | 0.00 | 138.75 | 295.82 | 101.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 177.15 | 9.33 | 167.82 | 407.01 | 59.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 138.75 | 0.00 | 138.75 | 295.82 | 31.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 266.44 | 53.85 | 212.60 | 650.17 | 101.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.82 | 0.00 | 142.82 | 311.23 | 90.25 | 0.00 | 0.00 | 0.00 |
February | 152.35 | 0.00 | 152.35 | 347.96 | 74.11 | 0.00 | 0.00 | 0.00 |
March | 156.36 | 0.00 | 156.36 | 376.72 | 56.75 | 0.00 | 0.00 | 0.00 |
April | 170.16 | 2.41 | 167.75 | 418.68 | 31.40 | 0.00 | 0.00 | 0.00 |
May | 218.12 | 23.24 | 194.89 | 544.03 | 33.39 | 0.00 | 0.00 | 0.00 |
June | 266.44 | 53.85 | 212.60 | 650.17 | 38.83 | 0.00 | 0.00 | 0.00 |
July | 229.12 | 24.02 | 205.10 | 507.54 | 59.77 | 0.00 | 0.00 | 0.00 |
August | 188.64 | 8.04 | 180.59 | 419.60 | 51.53 | 0.00 | 0.00 | 0.00 |
September | 160.60 | 0.08 | 160.53 | 370.02 | 48.91 | 0.00 | 0.00 | 0.00 |
October | 154.75 | 0.00 | 154.75 | 328.34 | 60.76 | 0.00 | 0.00 | 0.00 |
November | 146.43 | 0.00 | 146.43 | 312.28 | 70.75 | 0.00 | 0.00 | 0.00 |
December | 138.75 | 0.00 | 138.75 | 295.82 | 101.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 177.15 | 9.33 | 167.82 | 407.01 | 59.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 138.75 | 0.00 | 138.75 | 295.82 | 31.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 266.44 | 53.85 | 212.60 | 650.17 | 101.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.82 | 0.00 | 142.82 | 311.23 | 90.25 | 0.00 | 0.00 | 0.00 |
February | 152.35 | 0.00 | 152.35 | 347.96 | 74.11 | 0.00 | 0.00 | 0.00 |
March | 156.36 | 0.00 | 156.36 | 376.72 | 56.75 | 0.00 | 0.00 | 0.00 |
April | 170.16 | 2.41 | 167.75 | 418.68 | 31.40 | 0.00 | 0.00 | 0.00 |
May | 218.12 | 23.24 | 194.89 | 544.03 | 33.39 | 0.00 | 0.00 | 0.00 |
June | 266.44 | 53.85 | 212.60 | 650.17 | 38.83 | 0.00 | 0.00 | 0.00 |
July | 229.12 | 24.02 | 205.10 | 507.53 | 59.77 | 0.00 | 0.00 | 0.00 |
August | 188.64 | 8.04 | 180.59 | 419.60 | 51.53 | 0.00 | 0.00 | 0.00 |
September | 160.60 | 0.08 | 160.53 | 370.02 | 48.91 | 0.00 | 0.00 | 0.00 |
October | 154.75 | 0.00 | 154.75 | 328.34 | 60.76 | 0.00 | 0.00 | 0.00 |
November | 146.43 | 0.00 | 146.43 | 312.28 | 70.75 | 0.00 | 0.00 | 0.00 |
December | 138.75 | 0.00 | 138.75 | 295.82 | 101.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 177.15 | 9.33 | 167.82 | 407.01 | 59.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 138.75 | 0.00 | 138.75 | 295.82 | 31.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 266.44 | 53.85 | 212.60 | 650.17 | 101.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 142.81 | 0.00 | 142.81 | 311.21 | 90.25 | 0.00 | 0.00 | 0.00 |
February | 152.34 | 0.00 | 152.34 | 347.94 | 74.11 | 0.00 | 0.00 | 0.00 |
March | 156.35 | 0.00 | 156.35 | 376.71 | 56.74 | 0.00 | 0.00 | 0.00 |
April | 170.15 | 2.41 | 167.74 | 418.66 | 31.40 | 0.00 | 0.00 | 0.00 |
May | 218.11 | 23.24 | 194.88 | 544.01 | 33.39 | 0.00 | 0.00 | 0.00 |
June | 266.43 | 53.84 | 212.59 | 650.14 | 38.82 | 0.00 | 0.00 | 0.00 |
July | 229.11 | 24.01 | 205.09 | 507.51 | 59.77 | 0.00 | 0.00 | 0.00 |
August | 188.63 | 8.04 | 180.59 | 419.59 | 51.52 | 0.00 | 0.00 | 0.00 |
September | 160.60 | 0.08 | 160.52 | 370.01 | 48.91 | 0.00 | 0.00 | 0.00 |
October | 154.74 | 0.00 | 154.74 | 328.32 | 60.76 | 0.00 | 0.00 | 0.00 |
November | 146.42 | 0.00 | 146.42 | 312.26 | 70.75 | 0.00 | 0.00 | 0.00 |
December | 138.74 | 0.00 | 138.74 | 295.81 | 101.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 177.14 | 9.33 | 167.82 | 406.99 | 59.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 138.74 | 0.00 | 138.74 | 295.81 | 31.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 266.43 | 53.84 | 212.59 | 650.14 | 101.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 305.99 | 103.13 | 202.86 | 624.58 | 94.91 | 0.00 | 0.00 | 0.00 |
February | 346.99 | 127.23 | 219.77 | 725.66 | 75.50 | 0.00 | 0.00 | 0.00 |
March | 378.29 | 148.14 | 230.15 | 810.01 | 56.21 | 0.00 | 0.00 | 0.00 |
April | 382.32 | 146.06 | 236.26 | 836.37 | 27.85 | 0.00 | 0.00 | 0.00 |
May | 328.64 | 99.48 | 229.16 | 746.81 | 34.31 | 0.00 | 0.00 | 0.00 |
June | 350.03 | 115.28 | 234.75 | 788.17 | 37.13 | 0.00 | 0.00 | 0.00 |
July | 298.97 | 66.98 | 231.99 | 631.76 | 58.99 | 0.00 | 0.00 | 0.00 |
August | 329.02 | 96.72 | 232.30 | 685.42 | 49.94 | 0.00 | 0.00 | 0.00 |
September | 308.99 | 84.20 | 224.79 | 660.77 | 54.07 | 0.00 | 0.00 | 0.00 |
October | 289.60 | 74.09 | 215.51 | 588.96 | 64.38 | 0.00 | 0.00 | 0.00 |
November | 280.27 | 77.45 | 202.82 | 573.41 | 72.79 | 0.00 | 0.00 | 0.00 |
December | 286.81 | 92.04 | 194.77 | 582.40 | 101.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 323.56 | 102.33 | 221.24 | 687.25 | 60.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 280.27 | 66.98 | 194.77 | 573.41 | 27.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 382.32 | 148.14 | 236.26 | 836.37 | 101.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 305.99 | 103.13 | 202.86 | 624.58 | 94.91 | 0.00 | 0.00 | 0.00 |
February | 346.99 | 127.23 | 219.77 | 725.66 | 75.50 | 0.00 | 0.00 | 0.00 |
March | 378.29 | 148.14 | 230.15 | 810.01 | 56.21 | 0.00 | 0.00 | 0.00 |
April | 382.32 | 146.06 | 236.26 | 836.37 | 27.85 | 0.00 | 0.00 | 0.00 |
May | 328.64 | 99.48 | 229.16 | 746.81 | 34.31 | 0.00 | 0.00 | 0.00 |
June | 350.03 | 115.28 | 234.75 | 788.17 | 37.13 | 0.00 | 0.00 | 0.00 |
July | 298.97 | 66.98 | 231.99 | 631.76 | 58.99 | 0.00 | 0.00 | 0.00 |
August | 329.02 | 96.72 | 232.30 | 685.42 | 49.94 | 0.00 | 0.00 | 0.00 |
September | 308.99 | 84.20 | 224.79 | 660.77 | 54.07 | 0.00 | 0.00 | 0.00 |
October | 289.60 | 74.09 | 215.51 | 588.96 | 64.38 | 0.00 | 0.00 | 0.00 |
November | 280.27 | 77.45 | 202.82 | 573.41 | 72.79 | 0.00 | 0.00 | 0.00 |
December | 286.81 | 92.04 | 194.77 | 582.40 | 101.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 323.56 | 102.33 | 221.24 | 687.25 | 60.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 280.27 | 66.98 | 194.77 | 573.41 | 27.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 382.32 | 148.14 | 236.26 | 836.37 | 101.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 305.99 | 103.13 | 202.86 | 624.56 | 94.91 | 0.00 | 0.00 | 0.00 |
February | 346.99 | 127.22 | 219.76 | 725.65 | 75.50 | 0.00 | 0.00 | 0.00 |
March | 378.28 | 148.13 | 230.15 | 810.00 | 56.21 | 0.00 | 0.00 | 0.00 |
April | 382.31 | 146.06 | 236.25 | 836.35 | 27.85 | 0.00 | 0.00 | 0.00 |
May | 328.63 | 99.48 | 229.16 | 746.79 | 34.31 | 0.00 | 0.00 | 0.00 |
June | 350.02 | 115.28 | 234.74 | 788.15 | 37.13 | 0.00 | 0.00 | 0.00 |
July | 298.97 | 66.98 | 231.99 | 631.74 | 58.99 | 0.00 | 0.00 | 0.00 |
August | 329.02 | 96.72 | 232.30 | 685.41 | 49.94 | 0.00 | 0.00 | 0.00 |
September | 308.99 | 84.20 | 224.79 | 660.76 | 54.07 | 0.00 | 0.00 | 0.00 |
October | 289.59 | 74.09 | 215.50 | 588.95 | 64.38 | 0.00 | 0.00 | 0.00 |
November | 280.26 | 77.45 | 202.81 | 573.40 | 72.79 | 0.00 | 0.00 | 0.00 |
December | 286.81 | 92.04 | 194.77 | 582.39 | 101.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 323.56 | 102.33 | 221.23 | 687.24 | 60.64 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 280.26 | 66.98 | 194.77 | 573.40 | 27.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 382.31 | 148.13 | 236.25 | 836.35 | 101.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 378.13 | 157.76 | 220.37 | 781.59 | 93.54 | 0.00 | 0.00 | 0.00 |
February | 321.09 | 104.69 | 216.40 | 711.52 | 74.82 | 0.00 | 0.00 | 0.00 |
March | 219.13 | 29.43 | 189.70 | 532.77 | 54.04 | 0.00 | 0.00 | 0.00 |
April | 163.37 | 0.07 | 163.30 | 407.87 | 25.45 | 0.00 | 0.00 | 0.00 |
May | 163.48 | 0.00 | 163.48 | 423.34 | 27.93 | 0.00 | 0.00 | 0.00 |
June | 162.89 | 0.00 | 162.89 | 420.02 | 30.61 | 0.00 | 0.00 | 0.00 |
July | 167.80 | 0.00 | 167.80 | 374.83 | 53.17 | 0.00 | 0.00 | 0.00 |
August | 163.36 | 0.25 | 163.11 | 364.99 | 44.98 | 0.00 | 0.00 | 0.00 |
September | 180.85 | 5.91 | 174.94 | 418.46 | 46.00 | 0.00 | 0.00 | 0.00 |
October | 236.60 | 37.72 | 198.88 | 505.89 | 60.34 | 0.00 | 0.00 | 0.00 |
November | 307.66 | 93.86 | 213.80 | 640.57 | 72.98 | 0.00 | 0.00 | 0.00 |
December | 377.94 | 160.80 | 217.14 | 766.11 | 105.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 236.53 | 49.02 | 187.51 | 528.12 | 57.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 162.89 | 0.00 | 162.89 | 364.99 | 25.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 378.13 | 160.80 | 220.37 | 781.59 | 105.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 378.13 | 157.76 | 220.37 | 781.59 | 93.54 | 0.00 | 0.00 | 0.00 |
February | 321.09 | 104.69 | 216.40 | 711.52 | 74.82 | 0.00 | 0.00 | 0.00 |
March | 219.13 | 29.43 | 189.70 | 532.77 | 54.04 | 0.00 | 0.00 | 0.00 |
April | 163.37 | 0.07 | 163.30 | 407.87 | 25.45 | 0.00 | 0.00 | 0.00 |
May | 163.48 | 0.00 | 163.48 | 423.34 | 27.93 | 0.00 | 0.00 | 0.00 |
June | 162.89 | 0.00 | 162.89 | 420.02 | 30.61 | 0.00 | 0.00 | 0.00 |
July | 167.80 | 0.00 | 167.80 | 374.83 | 53.17 | 0.00 | 0.00 | 0.00 |
August | 163.36 | 0.25 | 163.11 | 364.99 | 44.98 | 0.00 | 0.00 | 0.00 |
September | 180.85 | 5.91 | 174.94 | 418.46 | 46.00 | 0.00 | 0.00 | 0.00 |
October | 236.60 | 37.72 | 198.88 | 505.89 | 60.34 | 0.00 | 0.00 | 0.00 |
November | 307.66 | 93.86 | 213.80 | 640.57 | 72.98 | 0.00 | 0.00 | 0.00 |
December | 377.94 | 160.80 | 217.14 | 766.11 | 105.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 236.53 | 49.02 | 187.51 | 528.12 | 57.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 162.89 | 0.00 | 162.89 | 364.99 | 25.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 378.13 | 160.80 | 220.37 | 781.59 | 105.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 378.13 | 157.76 | 220.37 | 781.59 | 93.54 | 0.00 | 0.00 | 0.00 |
February | 321.09 | 104.69 | 216.40 | 711.52 | 74.82 | 0.00 | 0.00 | 0.00 |
March | 219.13 | 29.43 | 189.70 | 532.77 | 54.04 | 0.00 | 0.00 | 0.00 |
April | 163.37 | 0.07 | 163.30 | 407.87 | 25.45 | 0.00 | 0.00 | 0.00 |
May | 163.48 | 0.00 | 163.48 | 423.34 | 27.93 | 0.00 | 0.00 | 0.00 |
June | 162.89 | 0.00 | 162.89 | 420.02 | 30.61 | 0.00 | 0.00 | 0.00 |
July | 167.80 | 0.00 | 167.80 | 374.83 | 53.17 | 0.00 | 0.00 | 0.00 |
August | 163.36 | 0.25 | 163.11 | 364.99 | 44.98 | 0.00 | 0.00 | 0.00 |
September | 180.85 | 5.91 | 174.94 | 418.46 | 46.00 | 0.00 | 0.00 | 0.00 |
October | 236.60 | 37.72 | 198.88 | 505.89 | 60.34 | 0.00 | 0.00 | 0.00 |
November | 307.66 | 93.86 | 213.80 | 640.57 | 72.98 | 0.00 | 0.00 | 0.00 |
December | 377.94 | 160.80 | 217.14 | 766.11 | 105.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 236.53 | 49.02 | 187.51 | 528.12 | 57.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 162.89 | 0.00 | 162.89 | 364.99 | 25.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 378.13 | 160.80 | 220.37 | 781.59 | 105.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 378.13 | 157.76 | 220.37 | 781.59 | 93.54 | 0.00 | 0.00 | 0.00 |
February | 321.09 | 104.69 | 216.40 | 711.52 | 74.82 | 0.00 | 0.00 | 0.00 |
March | 219.13 | 29.43 | 189.70 | 532.77 | 54.04 | 0.00 | 0.00 | 0.00 |
April | 163.37 | 0.07 | 163.30 | 407.87 | 25.45 | 0.00 | 0.00 | 0.00 |
May | 163.48 | 0.00 | 163.48 | 423.34 | 27.93 | 0.00 | 0.00 | 0.00 |
June | 162.89 | 0.00 | 162.89 | 420.02 | 30.61 | 0.00 | 0.00 | 0.00 |
July | 167.80 | 0.00 | 167.80 | 374.83 | 53.17 | 0.00 | 0.00 | 0.00 |
August | 163.36 | 0.25 | 163.11 | 364.99 | 44.98 | 0.00 | 0.00 | 0.00 |
September | 180.85 | 5.91 | 174.94 | 418.46 | 46.00 | 0.00 | 0.00 | 0.00 |
October | 236.60 | 37.72 | 198.88 | 505.89 | 60.34 | 0.00 | 0.00 | 0.00 |
November | 307.66 | 93.86 | 213.80 | 640.57 | 72.98 | 0.00 | 0.00 | 0.00 |
December | 377.94 | 160.80 | 217.14 | 766.11 | 105.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 236.53 | 49.02 | 187.51 | 528.12 | 57.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 162.89 | 0.00 | 162.89 | 364.99 | 25.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 378.13 | 160.80 | 220.37 | 781.59 | 105.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 378.12 | 157.76 | 220.36 | 781.56 | 93.54 | 0.00 | 0.00 | 0.00 |
February | 321.08 | 104.68 | 216.40 | 711.49 | 74.81 | 0.00 | 0.00 | 0.00 |
March | 219.12 | 29.43 | 189.69 | 532.75 | 54.04 | 0.00 | 0.00 | 0.00 |
April | 163.36 | 0.07 | 163.29 | 407.85 | 25.44 | 0.00 | 0.00 | 0.00 |
May | 163.47 | 0.00 | 163.47 | 423.32 | 27.93 | 0.00 | 0.00 | 0.00 |
June | 162.89 | 0.00 | 162.89 | 420.00 | 30.61 | 0.00 | 0.00 | 0.00 |
July | 167.80 | 0.00 | 167.80 | 374.81 | 53.16 | 0.00 | 0.00 | 0.00 |
August | 163.35 | 0.25 | 163.10 | 364.98 | 44.98 | 0.00 | 0.00 | 0.00 |
September | 180.84 | 5.91 | 174.94 | 418.44 | 46.00 | 0.00 | 0.00 | 0.00 |
October | 236.59 | 37.72 | 198.87 | 505.87 | 60.33 | 0.00 | 0.00 | 0.00 |
November | 307.65 | 93.86 | 213.79 | 640.55 | 72.98 | 0.00 | 0.00 | 0.00 |
December | 377.92 | 160.79 | 217.13 | 766.08 | 105.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 236.52 | 49.02 | 187.51 | 528.10 | 57.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 162.89 | 0.00 | 162.89 | 364.98 | 25.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 378.12 | 160.79 | 220.36 | 781.56 | 105.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 310.04 | 109.02 | 201.02 | 640.42 | 107.51 | 0.00 | 0.00 | 0.00 |
February | 340.51 | 120.50 | 220.01 | 715.11 | 93.54 | 0.00 | 0.00 | 0.00 |
March | 381.68 | 150.76 | 230.93 | 813.53 | 78.07 | 0.00 | 0.00 | 0.00 |
April | 383.57 | 146.91 | 236.66 | 818.42 | 50.43 | 0.00 | 0.00 | 0.00 |
May | 326.38 | 96.69 | 229.69 | 740.01 | 32.37 | 0.00 | 0.00 | 0.00 |
June | 353.67 | 121.90 | 231.77 | 785.01 | 41.20 | 0.00 | 0.00 | 0.00 |
July | 301.52 | 71.11 | 230.42 | 626.45 | 71.81 | 0.00 | 0.00 | 0.00 |
August | 327.82 | 97.08 | 230.73 | 663.92 | 70.17 | 0.00 | 0.00 | 0.00 |
September | 307.05 | 85.16 | 221.89 | 655.57 | 52.13 | 0.00 | 0.00 | 0.00 |
October | 288.38 | 74.34 | 214.04 | 581.83 | 72.15 | 0.00 | 0.00 | 0.00 |
November | 281.23 | 76.70 | 204.53 | 567.18 | 90.70 | 0.00 | 0.00 | 0.00 |
December | 287.81 | 94.15 | 193.66 | 578.25 | 137.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 323.92 | 103.51 | 220.41 | 681.60 | 74.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 281.23 | 71.11 | 193.66 | 567.18 | 32.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 383.57 | 150.76 | 236.66 | 818.42 | 137.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 310.04 | 109.02 | 201.02 | 640.42 | 107.51 | 0.00 | 0.00 | 0.00 |
February | 340.51 | 120.50 | 220.01 | 715.11 | 93.54 | 0.00 | 0.00 | 0.00 |
March | 381.68 | 150.76 | 230.93 | 813.53 | 78.07 | 0.00 | 0.00 | 0.00 |
April | 383.57 | 146.91 | 236.66 | 818.42 | 50.43 | 0.00 | 0.00 | 0.00 |
May | 326.38 | 96.69 | 229.69 | 740.01 | 32.37 | 0.00 | 0.00 | 0.00 |
June | 353.67 | 121.90 | 231.77 | 785.01 | 41.20 | 0.00 | 0.00 | 0.00 |
July | 301.52 | 71.11 | 230.42 | 626.45 | 71.81 | 0.00 | 0.00 | 0.00 |
August | 327.82 | 97.08 | 230.73 | 663.92 | 70.17 | 0.00 | 0.00 | 0.00 |
September | 307.05 | 85.16 | 221.89 | 655.57 | 52.13 | 0.00 | 0.00 | 0.00 |
October | 288.38 | 74.34 | 214.04 | 581.83 | 72.15 | 0.00 | 0.00 | 0.00 |
November | 281.23 | 76.70 | 204.53 | 567.18 | 90.70 | 0.00 | 0.00 | 0.00 |
December | 287.81 | 94.15 | 193.66 | 578.25 | 137.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 323.92 | 103.51 | 220.41 | 681.60 | 74.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 281.23 | 71.11 | 193.66 | 567.18 | 32.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 383.57 | 150.76 | 236.66 | 818.42 | 137.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 310.03 | 109.02 | 201.01 | 640.41 | 107.51 | 0.00 | 0.00 | 0.00 |
February | 340.50 | 120.50 | 220.01 | 715.10 | 93.54 | 0.00 | 0.00 | 0.00 |
March | 381.68 | 150.76 | 230.92 | 813.52 | 78.06 | 0.00 | 0.00 | 0.00 |
April | 383.56 | 146.91 | 236.65 | 818.41 | 50.43 | 0.00 | 0.00 | 0.00 |
May | 326.37 | 96.69 | 229.68 | 739.99 | 32.37 | 0.00 | 0.00 | 0.00 |
June | 353.66 | 121.90 | 231.76 | 784.99 | 41.20 | 0.00 | 0.00 | 0.00 |
July | 301.52 | 71.10 | 230.41 | 626.44 | 71.80 | 0.00 | 0.00 | 0.00 |
August | 327.81 | 97.08 | 230.73 | 663.91 | 70.17 | 0.00 | 0.00 | 0.00 |
September | 307.04 | 85.16 | 221.88 | 655.56 | 52.13 | 0.00 | 0.00 | 0.00 |
October | 288.37 | 74.34 | 214.04 | 581.82 | 72.14 | 0.00 | 0.00 | 0.00 |
November | 281.22 | 76.70 | 204.52 | 567.17 | 90.70 | 0.00 | 0.00 | 0.00 |
December | 287.81 | 94.15 | 193.66 | 578.24 | 137.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 323.92 | 103.51 | 220.41 | 681.59 | 74.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 281.22 | 71.10 | 193.66 | 567.17 | 32.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 383.56 | 150.76 | 236.65 | 818.41 | 137.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 714.09 | 0.00 | 714.09 | 1618.33 | 376.62 | 0.00 | 0.00 | 0.00 |
February | 761.74 | 0.00 | 761.74 | 1812.09 | 293.73 | 0.00 | 0.00 | 0.00 |
March | 781.77 | 0.00 | 781.77 | 1978.45 | 179.63 | 0.00 | 0.00 | 0.00 |
April | 850.78 | 12.06 | 838.72 | 2225.68 | 67.18 | 0.00 | 0.00 | 0.00 |
May | 1090.60 | 116.18 | 974.41 | 2809.82 | 110.54 | 0.00 | 0.00 | 0.00 |
June | 1332.20 | 269.23 | 1062.97 | 3326.23 | 130.34 | 0.00 | 0.00 | 0.00 |
July | 1145.57 | 120.08 | 1025.49 | 2614.80 | 221.71 | 0.00 | 0.00 | 0.00 |
August | 943.17 | 40.22 | 902.96 | 2191.32 | 161.78 | 0.00 | 0.00 | 0.00 |
September | 803.01 | 0.38 | 802.63 | 1936.99 | 154.12 | 0.00 | 0.00 | 0.00 |
October | 773.73 | 0.00 | 773.73 | 1723.88 | 202.90 | 0.00 | 0.00 | 0.00 |
November | 732.12 | 0.00 | 732.12 | 1645.09 | 257.98 | 0.00 | 0.00 | 0.00 |
December | 693.73 | 0.00 | 693.73 | 1554.23 | 421.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 885.74 | 46.63 | 839.11 | 2120.48 | 214.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 693.73 | 0.00 | 693.73 | 1554.23 | 67.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1332.20 | 269.23 | 1062.97 | 3326.23 | 421.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 917.97 | 309.38 | 608.59 | 1897.54 | 249.17 | 0.00 | 0.00 | 0.00 |
February | 1040.97 | 381.67 | 659.30 | 2203.56 | 193.15 | 0.00 | 0.00 | 0.00 |
March | 1134.86 | 444.40 | 690.45 | 2464.45 | 115.98 | 0.00 | 0.00 | 0.00 |
April | 1146.95 | 438.18 | 708.76 | 2565.46 | 42.50 | 0.00 | 0.00 | 0.00 |
May | 985.90 | 298.43 | 687.47 | 2299.21 | 68.96 | 0.00 | 0.00 | 0.00 |
June | 1050.07 | 345.84 | 704.23 | 2411.47 | 74.60 | 0.00 | 0.00 | 0.00 |
July | 896.90 | 200.93 | 695.98 | 1938.45 | 136.95 | 0.00 | 0.00 | 0.00 |
August | 987.06 | 290.15 | 696.91 | 2096.12 | 106.14 | 0.00 | 0.00 | 0.00 |
September | 926.97 | 252.60 | 674.37 | 2023.89 | 109.16 | 0.00 | 0.00 | 0.00 |
October | 868.78 | 222.26 | 646.51 | 1805.07 | 140.12 | 0.00 | 0.00 | 0.00 |
November | 840.80 | 232.35 | 608.45 | 1754.43 | 178.98 | 0.00 | 0.00 | 0.00 |
December | 860.43 | 276.12 | 584.31 | 1768.53 | 281.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 970.68 | 306.98 | 663.70 | 2100.57 | 141.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 840.80 | 200.93 | 584.31 | 1754.43 | 42.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1146.95 | 444.40 | 708.76 | 2565.46 | 281.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1890.65 | 788.80 | 1101.85 | 3923.06 | 436.09 | 0.00 | 0.00 | 0.00 |
February | 1605.44 | 523.43 | 1082.01 | 3596.27 | 329.83 | 0.00 | 0.00 | 0.00 |
March | 1095.62 | 147.14 | 948.48 | 2738.17 | 188.82 | 0.00 | 0.00 | 0.00 |
April | 816.84 | 0.37 | 816.47 | 2174.15 | 57.55 | 0.00 | 0.00 | 0.00 |
May | 817.40 | 0.00 | 817.40 | 2224.83 | 93.95 | 0.00 | 0.00 | 0.00 |
June | 814.46 | 0.00 | 814.46 | 2206.16 | 98.50 | 0.00 | 0.00 | 0.00 |
July | 839.01 | 0.00 | 839.01 | 1958.49 | 194.17 | 0.00 | 0.00 | 0.00 |
August | 816.78 | 1.26 | 815.52 | 1917.86 | 141.57 | 0.00 | 0.00 | 0.00 |
September | 904.24 | 29.53 | 874.71 | 2162.36 | 159.39 | 0.00 | 0.00 | 0.00 |
October | 1183.01 | 188.62 | 994.39 | 2578.92 | 235.11 | 0.00 | 0.00 | 0.00 |
November | 1538.30 | 469.31 | 1068.98 | 3253.35 | 310.68 | 0.00 | 0.00 | 0.00 |
December | 1889.68 | 803.98 | 1085.70 | 3859.36 | 490.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1182.64 | 245.09 | 937.55 | 2711.77 | 227.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 814.46 | 0.00 | 814.46 | 1917.86 | 57.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1890.65 | 803.98 | 1101.85 | 3923.06 | 490.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 930.10 | 327.05 | 603.05 | 1941.20 | 302.19 | 0.00 | 0.00 | 0.00 |
February | 1021.52 | 361.49 | 660.02 | 2178.50 | 244.86 | 0.00 | 0.00 | 0.00 |
March | 1145.04 | 452.27 | 692.77 | 2488.22 | 178.11 | 0.00 | 0.00 | 0.00 |
April | 1150.70 | 440.74 | 709.97 | 2533.46 | 81.93 | 0.00 | 0.00 | 0.00 |
May | 979.12 | 290.07 | 689.05 | 2252.56 | 82.10 | 0.00 | 0.00 | 0.00 |
June | 1061.00 | 365.70 | 695.30 | 2400.04 | 92.99 | 0.00 | 0.00 | 0.00 |
July | 904.56 | 213.32 | 691.24 | 1934.01 | 165.13 | 0.00 | 0.00 | 0.00 |
August | 983.44 | 291.24 | 692.20 | 2058.81 | 135.40 | 0.00 | 0.00 | 0.00 |
September | 921.13 | 255.48 | 665.65 | 1992.28 | 132.56 | 0.00 | 0.00 | 0.00 |
October | 865.12 | 223.01 | 642.11 | 1784.15 | 173.47 | 0.00 | 0.00 | 0.00 |
November | 843.67 | 230.09 | 613.58 | 1752.95 | 213.85 | 0.00 | 0.00 | 0.00 |
December | 863.43 | 282.44 | 580.99 | 1792.63 | 339.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 971.76 | 310.53 | 661.23 | 2090.85 | 178.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 843.67 | 213.32 | 580.99 | 1752.95 | 81.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1150.70 | 452.27 | 709.97 | 2533.46 | 339.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 714.09 | 0.00 | 714.09 | 1596.64 | 383.14 | 0.00 | 0.00 | 0.00 |
February | 761.74 | 0.00 | 761.74 | 1786.18 | 301.36 | 0.00 | 0.00 | 0.00 |
March | 781.77 | 0.00 | 781.77 | 1947.79 | 192.15 | 0.00 | 0.00 | 0.00 |
April | 850.78 | 12.06 | 838.72 | 2182.45 | 76.53 | 0.00 | 0.00 | 0.00 |
May | 1090.60 | 116.18 | 974.41 | 2768.85 | 119.10 | 0.00 | 0.00 | 0.00 |
June | 1332.20 | 269.23 | 1062.97 | 3289.87 | 141.75 | 0.00 | 0.00 | 0.00 |
July | 1145.57 | 120.08 | 1025.49 | 2580.57 | 233.16 | 0.00 | 0.00 | 0.00 |
August | 943.17 | 40.22 | 902.96 | 2163.08 | 170.75 | 0.00 | 0.00 | 0.00 |
September | 803.01 | 0.38 | 802.63 | 1903.53 | 167.42 | 0.00 | 0.00 | 0.00 |
October | 773.73 | 0.00 | 773.73 | 1697.36 | 212.41 | 0.00 | 0.00 | 0.00 |
November | 732.12 | 0.00 | 732.12 | 1619.68 | 264.83 | 0.00 | 0.00 | 0.00 |
December | 693.73 | 0.00 | 693.73 | 1534.84 | 424.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 885.74 | 46.63 | 839.11 | 2089.98 | 223.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 693.73 | 0.00 | 693.73 | 1534.84 | 76.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1332.20 | 269.23 | 1062.97 | 3289.87 | 424.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 917.97 | 309.38 | 608.59 | 1881.24 | 253.38 | 0.00 | 0.00 | 0.00 |
February | 1040.97 | 381.67 | 659.30 | 2184.21 | 197.23 | 0.00 | 0.00 | 0.00 |
March | 1134.86 | 444.40 | 690.45 | 2440.97 | 122.63 | 0.00 | 0.00 | 0.00 |
April | 1146.95 | 438.18 | 708.76 | 2534.87 | 47.28 | 0.00 | 0.00 | 0.00 |
May | 985.90 | 298.43 | 687.47 | 2270.86 | 73.95 | 0.00 | 0.00 | 0.00 |
June | 1050.07 | 345.84 | 704.23 | 2385.52 | 81.21 | 0.00 | 0.00 | 0.00 |
July | 896.90 | 200.93 | 695.98 | 1915.71 | 144.72 | 0.00 | 0.00 | 0.00 |
August | 987.06 | 290.15 | 696.91 | 2076.70 | 112.06 | 0.00 | 0.00 | 0.00 |
September | 926.97 | 252.60 | 674.37 | 2002.25 | 117.53 | 0.00 | 0.00 | 0.00 |
October | 868.78 | 222.26 | 646.51 | 1786.20 | 145.62 | 0.00 | 0.00 | 0.00 |
November | 840.80 | 232.35 | 608.45 | 1736.31 | 183.06 | 0.00 | 0.00 | 0.00 |
December | 860.43 | 276.12 | 584.31 | 1753.99 | 283.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 970.68 | 306.98 | 663.70 | 2078.96 | 146.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 840.80 | 200.93 | 584.31 | 1736.31 | 47.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1146.95 | 444.40 | 708.76 | 2534.87 | 283.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1890.65 | 788.80 | 1101.85 | 3903.82 | 439.66 | 0.00 | 0.00 | 0.00 |
February | 1605.44 | 523.43 | 1082.01 | 3571.38 | 334.75 | 0.00 | 0.00 | 0.00 |
March | 1095.62 | 147.14 | 948.48 | 2706.29 | 198.50 | 0.00 | 0.00 | 0.00 |
April | 816.84 | 0.37 | 816.47 | 2129.42 | 64.81 | 0.00 | 0.00 | 0.00 |
May | 817.40 | 0.00 | 817.40 | 2181.47 | 101.35 | 0.00 | 0.00 | 0.00 |
June | 814.46 | 0.00 | 814.46 | 2166.60 | 107.74 | 0.00 | 0.00 | 0.00 |
July | 839.01 | 0.00 | 839.01 | 1924.02 | 206.49 | 0.00 | 0.00 | 0.00 |
August | 816.78 | 1.26 | 815.52 | 1888.84 | 150.07 | 0.00 | 0.00 | 0.00 |
September | 904.24 | 29.53 | 874.71 | 2128.63 | 172.22 | 0.00 | 0.00 | 0.00 |
October | 1183.01 | 188.62 | 994.39 | 2551.68 | 243.69 | 0.00 | 0.00 | 0.00 |
November | 1538.30 | 469.31 | 1068.98 | 3229.04 | 316.01 | 0.00 | 0.00 | 0.00 |
December | 1889.68 | 803.98 | 1085.70 | 3841.97 | 491.20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1182.64 | 245.09 | 937.55 | 2680.96 | 235.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 814.46 | 0.00 | 814.46 | 1888.84 | 64.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1890.65 | 803.98 | 1101.85 | 3903.82 | 491.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 930.10 | 327.05 | 603.05 | 1928.64 | 303.43 | 0.00 | 0.00 | 0.00 |
February | 1021.52 | 361.49 | 660.02 | 2162.46 | 246.85 | 0.00 | 0.00 | 0.00 |
March | 1145.04 | 452.27 | 692.77 | 2469.16 | 182.30 | 0.00 | 0.00 | 0.00 |
April | 1150.70 | 440.74 | 709.97 | 2510.28 | 85.94 | 0.00 | 0.00 | 0.00 |
May | 979.12 | 290.07 | 689.05 | 2229.23 | 85.15 | 0.00 | 0.00 | 0.00 |
June | 1061.00 | 365.70 | 695.30 | 2377.25 | 96.98 | 0.00 | 0.00 | 0.00 |
July | 904.56 | 213.32 | 691.24 | 1913.91 | 168.93 | 0.00 | 0.00 | 0.00 |
August | 983.44 | 291.24 | 692.20 | 2040.62 | 138.24 | 0.00 | 0.00 | 0.00 |
September | 921.13 | 255.48 | 665.65 | 1972.92 | 137.41 | 0.00 | 0.00 | 0.00 |
October | 865.12 | 223.01 | 642.11 | 1769.34 | 175.28 | 0.00 | 0.00 | 0.00 |
November | 843.67 | 230.09 | 613.58 | 1738.40 | 215.12 | 0.00 | 0.00 | 0.00 |
December | 863.43 | 282.44 | 580.99 | 1781.23 | 338.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 971.76 | 310.53 | 661.23 | 2072.91 | 181.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 843.67 | 213.32 | 580.99 | 1738.40 | 85.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1150.70 | 452.27 | 709.97 | 2510.28 | 338.03 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.382527E+09 | 0.00 | 0.382527E+09 | 0.833590E+09 | 0.241739E+09 |
February | 0.368563E+09 | 0.00 | 0.368563E+09 | 0.841781E+09 | 0.179288E+09 |
March | 0.418786E+09 | 0.00 | 0.418786E+09 | 0.100902E+10 | 0.151987E+09 |
April | 0.441049E+09 | 6250485.00 | 0.434798E+09 | 0.108521E+10 | 81394086.76 |
May | 0.584217E+09 | 62236681.22 | 0.521981E+09 | 0.145713E+10 | 89422521.92 |
June | 0.690621E+09 | 0.139569E+09 | 0.551052E+09 | 0.168524E+10 | 0.100638E+09 |
July | 0.613664E+09 | 64323000.09 | 0.549341E+09 | 0.135938E+10 | 0.160088E+09 |
August | 0.505246E+09 | 21544075.95 | 0.483702E+09 | 0.112386E+10 | 0.138009E+09 |
September | 0.416285E+09 | 199339.91 | 0.416086E+09 | 0.959092E+09 | 0.126785E+09 |
October | 0.414478E+09 | 0.00 | 0.414478E+09 | 0.879418E+09 | 0.162738E+09 |
November | 0.379536E+09 | 0.00 | 0.379536E+09 | 0.809423E+09 | 0.183391E+09 |
December | 0.371620E+09 | 0.00 | 0.371620E+09 | 0.792333E+09 | 0.272241E+09 |
Annual Sum or Average | 0.558659E+10 | 0.294123E+09 | 0.529247E+10 | 0.128355E+11 | 0.188772E+10 |
Minimum of Months | 0.368563E+09 | 0.00 | 0.368563E+09 | 0.792333E+09 | 81394086.76 |
Maximum of Months | 0.690621E+09 | 0.139569E+09 | 0.551052E+09 | 0.168524E+10 | 0.272241E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.382527E+09 | 0.00 | 0.382527E+09 | 0.833590E+09 | 0.241739E+09 |
February | 0.368562E+09 | 0.00 | 0.368562E+09 | 0.841781E+09 | 0.179288E+09 |
March | 0.418785E+09 | 0.00 | 0.418785E+09 | 0.100902E+10 | 0.151987E+09 |
April | 0.441048E+09 | 6250477.50 | 0.434798E+09 | 0.108521E+10 | 81393987.83 |
May | 0.584217E+09 | 62236606.54 | 0.521980E+09 | 0.145712E+10 | 89422447.54 |
June | 0.690620E+09 | 0.139569E+09 | 0.551052E+09 | 0.168524E+10 | 0.100638E+09 |
July | 0.613664E+09 | 64322922.91 | 0.549341E+09 | 0.135938E+10 | 0.160088E+09 |
August | 0.505245E+09 | 21544050.10 | 0.483701E+09 | 0.112386E+10 | 0.138009E+09 |
September | 0.416285E+09 | 199339.67 | 0.416086E+09 | 0.959092E+09 | 0.126785E+09 |
October | 0.414477E+09 | 0.00 | 0.414477E+09 | 0.879417E+09 | 0.162738E+09 |
November | 0.379536E+09 | 0.00 | 0.379536E+09 | 0.809422E+09 | 0.183391E+09 |
December | 0.371620E+09 | 0.00 | 0.371620E+09 | 0.792333E+09 | 0.272240E+09 |
Annual Sum or Average | 0.558659E+10 | 0.294122E+09 | 0.529246E+10 | 0.128355E+11 | 0.188772E+10 |
Minimum of Months | 0.368562E+09 | 0.00 | 0.368562E+09 | 0.792333E+09 | 81393987.83 |
Maximum of Months | 0.690620E+09 | 0.139569E+09 | 0.551052E+09 | 0.168524E+10 | 0.272240E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.382527E+09 | 0.00 | 0.382527E+09 | 0.833590E+09 | 0.241739E+09 |
February | 0.368563E+09 | 0.00 | 0.368563E+09 | 0.841781E+09 | 0.179288E+09 |
March | 0.418786E+09 | 0.00 | 0.418786E+09 | 0.100902E+10 | 0.151987E+09 |
April | 0.441049E+09 | 6250485.00 | 0.434798E+09 | 0.108521E+10 | 81394086.76 |
May | 0.584217E+09 | 62236681.22 | 0.521981E+09 | 0.145713E+10 | 89422521.92 |
June | 0.690621E+09 | 0.139569E+09 | 0.551052E+09 | 0.168524E+10 | 0.100638E+09 |
July | 0.613664E+09 | 64323000.09 | 0.549341E+09 | 0.135938E+10 | 0.160088E+09 |
August | 0.505246E+09 | 21544075.95 | 0.483702E+09 | 0.112386E+10 | 0.138009E+09 |
September | 0.416285E+09 | 199339.91 | 0.416086E+09 | 0.959092E+09 | 0.126785E+09 |
October | 0.414478E+09 | 0.00 | 0.414478E+09 | 0.879418E+09 | 0.162738E+09 |
November | 0.379536E+09 | 0.00 | 0.379536E+09 | 0.809423E+09 | 0.183391E+09 |
December | 0.371620E+09 | 0.00 | 0.371620E+09 | 0.792333E+09 | 0.272241E+09 |
Annual Sum or Average | 0.558659E+10 | 0.294123E+09 | 0.529247E+10 | 0.128355E+11 | 0.188772E+10 |
Minimum of Months | 0.368563E+09 | 0.00 | 0.368563E+09 | 0.792333E+09 | 81394086.76 |
Maximum of Months | 0.690621E+09 | 0.139569E+09 | 0.551052E+09 | 0.168524E+10 | 0.272241E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.382527E+09 | 0.00 | 0.382527E+09 | 0.833590E+09 | 0.241739E+09 |
February | 0.368562E+09 | 0.00 | 0.368562E+09 | 0.841781E+09 | 0.179288E+09 |
March | 0.418785E+09 | 0.00 | 0.418785E+09 | 0.100902E+10 | 0.151987E+09 |
April | 0.441048E+09 | 6250477.50 | 0.434798E+09 | 0.108521E+10 | 81393987.83 |
May | 0.584217E+09 | 62236606.54 | 0.521980E+09 | 0.145712E+10 | 89422447.54 |
June | 0.690620E+09 | 0.139569E+09 | 0.551052E+09 | 0.168524E+10 | 0.100638E+09 |
July | 0.613664E+09 | 64322922.91 | 0.549341E+09 | 0.135938E+10 | 0.160088E+09 |
August | 0.505245E+09 | 21544050.10 | 0.483701E+09 | 0.112386E+10 | 0.138009E+09 |
September | 0.416285E+09 | 199339.67 | 0.416086E+09 | 0.959092E+09 | 0.126785E+09 |
October | 0.414477E+09 | 0.00 | 0.414477E+09 | 0.879417E+09 | 0.162738E+09 |
November | 0.379536E+09 | 0.00 | 0.379536E+09 | 0.809422E+09 | 0.183391E+09 |
December | 0.371620E+09 | 0.00 | 0.371620E+09 | 0.792333E+09 | 0.272240E+09 |
Annual Sum or Average | 0.558659E+10 | 0.294122E+09 | 0.529246E+10 | 0.128355E+11 | 0.188772E+10 |
Minimum of Months | 0.368562E+09 | 0.00 | 0.368562E+09 | 0.792333E+09 | 81393987.83 |
Maximum of Months | 0.690620E+09 | 0.139569E+09 | 0.551052E+09 | 0.168524E+10 | 0.272240E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.382512E+09 | 0.00 | 0.382512E+09 | 0.833556E+09 | 0.241729E+09 |
February | 0.368548E+09 | 0.00 | 0.368548E+09 | 0.841748E+09 | 0.179281E+09 |
March | 0.418769E+09 | 0.00 | 0.418769E+09 | 0.100898E+10 | 0.151981E+09 |
April | 0.441031E+09 | 6250233.07 | 0.434781E+09 | 0.108517E+10 | 81390806.22 |
May | 0.584194E+09 | 62234172.81 | 0.521960E+09 | 0.145707E+10 | 89418917.80 |
June | 0.690593E+09 | 0.139563E+09 | 0.551030E+09 | 0.168517E+10 | 0.100634E+09 |
July | 0.613640E+09 | 64320407.59 | 0.549319E+09 | 0.135933E+10 | 0.160082E+09 |
August | 0.505225E+09 | 21543207.63 | 0.483682E+09 | 0.112382E+10 | 0.138004E+09 |
September | 0.416269E+09 | 199331.87 | 0.416069E+09 | 0.959053E+09 | 0.126780E+09 |
October | 0.414461E+09 | 0.00 | 0.414461E+09 | 0.879382E+09 | 0.162732E+09 |
November | 0.379521E+09 | 0.00 | 0.379521E+09 | 0.809390E+09 | 0.183383E+09 |
December | 0.371605E+09 | 0.00 | 0.371605E+09 | 0.792301E+09 | 0.272230E+09 |
Annual Sum or Average | 0.558637E+10 | 0.294111E+09 | 0.529226E+10 | 0.128350E+11 | 0.188764E+10 |
Minimum of Months | 0.368548E+09 | 0.00 | 0.368548E+09 | 0.792301E+09 | 81390806.22 |
Maximum of Months | 0.690593E+09 | 0.139563E+09 | 0.551030E+09 | 0.168517E+10 | 0.272230E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.819570E+09 | 0.276219E+09 | 0.543352E+09 | 0.167286E+10 | 0.254210E+09 |
February | 0.839448E+09 | 0.307783E+09 | 0.531665E+09 | 0.175551E+10 | 0.182643E+09 |
March | 0.101321E+10 | 0.396768E+09 | 0.616442E+09 | 0.216954E+10 | 0.150558E+09 |
April | 0.990971E+09 | 0.378593E+09 | 0.612378E+09 | 0.216787E+10 | 72194096.04 |
May | 0.880222E+09 | 0.266442E+09 | 0.613780E+09 | 0.200024E+10 | 91893936.55 |
June | 0.907269E+09 | 0.298806E+09 | 0.608462E+09 | 0.204292E+10 | 96241077.55 |
July | 0.800764E+09 | 0.179391E+09 | 0.621373E+09 | 0.169209E+10 | 0.158012E+09 |
August | 0.881255E+09 | 0.259052E+09 | 0.622204E+09 | 0.183584E+10 | 0.133752E+09 |
September | 0.800910E+09 | 0.218251E+09 | 0.582659E+09 | 0.171271E+10 | 0.140162E+09 |
October | 0.775652E+09 | 0.198439E+09 | 0.577213E+09 | 0.157746E+10 | 0.172442E+09 |
November | 0.726460E+09 | 0.200754E+09 | 0.525706E+09 | 0.148629E+10 | 0.188684E+09 |
December | 0.768195E+09 | 0.246521E+09 | 0.521674E+09 | 0.155989E+10 | 0.271729E+09 |
Annual Sum or Average | 0.102039E+11 | 0.322702E+10 | 0.697691E+10 | 0.216732E+11 | 0.191252E+10 |
Minimum of Months | 0.726460E+09 | 0.179391E+09 | 0.521674E+09 | 0.148629E+10 | 72194096.04 |
Maximum of Months | 0.101321E+10 | 0.396768E+09 | 0.622204E+09 | 0.216954E+10 | 0.271729E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.819570E+09 | 0.276219E+09 | 0.543352E+09 | 0.167286E+10 | 0.254210E+09 |
February | 0.839448E+09 | 0.307783E+09 | 0.531665E+09 | 0.175551E+10 | 0.182643E+09 |
March | 0.101321E+10 | 0.396768E+09 | 0.616442E+09 | 0.216954E+10 | 0.150558E+09 |
April | 0.990971E+09 | 0.378593E+09 | 0.612378E+09 | 0.216787E+10 | 72194096.04 |
May | 0.880222E+09 | 0.266442E+09 | 0.613780E+09 | 0.200024E+10 | 91893936.55 |
June | 0.907269E+09 | 0.298806E+09 | 0.608462E+09 | 0.204292E+10 | 96241077.55 |
July | 0.800764E+09 | 0.179391E+09 | 0.621373E+09 | 0.169209E+10 | 0.158012E+09 |
August | 0.881255E+09 | 0.259052E+09 | 0.622204E+09 | 0.183584E+10 | 0.133752E+09 |
September | 0.800910E+09 | 0.218251E+09 | 0.582659E+09 | 0.171271E+10 | 0.140162E+09 |
October | 0.775652E+09 | 0.198439E+09 | 0.577213E+09 | 0.157746E+10 | 0.172442E+09 |
November | 0.726460E+09 | 0.200754E+09 | 0.525706E+09 | 0.148629E+10 | 0.188684E+09 |
December | 0.768195E+09 | 0.246521E+09 | 0.521674E+09 | 0.155989E+10 | 0.271729E+09 |
Annual Sum or Average | 0.102039E+11 | 0.322702E+10 | 0.697691E+10 | 0.216732E+11 | 0.191252E+10 |
Minimum of Months | 0.726460E+09 | 0.179391E+09 | 0.521674E+09 | 0.148629E+10 | 72194096.04 |
Maximum of Months | 0.101321E+10 | 0.396768E+09 | 0.622204E+09 | 0.216954E+10 | 0.271729E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.819555E+09 | 0.276214E+09 | 0.543342E+09 | 0.167283E+10 | 0.254205E+09 |
February | 0.839433E+09 | 0.307777E+09 | 0.531655E+09 | 0.175548E+10 | 0.182640E+09 |
March | 0.101319E+10 | 0.396761E+09 | 0.616431E+09 | 0.216950E+10 | 0.150555E+09 |
April | 0.990953E+09 | 0.378586E+09 | 0.612367E+09 | 0.216783E+10 | 72192776.89 |
May | 0.880206E+09 | 0.266437E+09 | 0.613769E+09 | 0.200021E+10 | 91892257.44 |
June | 0.907252E+09 | 0.298801E+09 | 0.608451E+09 | 0.204289E+10 | 96239319.02 |
July | 0.800749E+09 | 0.179388E+09 | 0.621362E+09 | 0.169206E+10 | 0.158009E+09 |
August | 0.881239E+09 | 0.259047E+09 | 0.622192E+09 | 0.183581E+10 | 0.133749E+09 |
September | 0.800896E+09 | 0.218247E+09 | 0.582648E+09 | 0.171268E+10 | 0.140160E+09 |
October | 0.775638E+09 | 0.198436E+09 | 0.577202E+09 | 0.157743E+10 | 0.172439E+09 |
November | 0.726447E+09 | 0.200751E+09 | 0.525696E+09 | 0.148626E+10 | 0.188681E+09 |
December | 0.768181E+09 | 0.246517E+09 | 0.521665E+09 | 0.155987E+10 | 0.271724E+09 |
Annual Sum or Average | 0.102037E+11 | 0.322696E+10 | 0.697678E+10 | 0.216728E+11 | 0.191249E+10 |
Minimum of Months | 0.726447E+09 | 0.179388E+09 | 0.521665E+09 | 0.148626E+10 | 72192776.89 |
Maximum of Months | 0.101319E+10 | 0.396761E+09 | 0.622192E+09 | 0.216950E+10 | 0.271724E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101279E+10 | 0.422549E+09 | 0.590244E+09 | 0.209342E+10 | 0.250545E+09 |
February | 0.776787E+09 | 0.253262E+09 | 0.523525E+09 | 0.172132E+10 | 0.180999E+09 |
March | 0.586911E+09 | 78822514.38 | 0.508088E+09 | 0.142696E+10 | 0.144745E+09 |
April | 0.423455E+09 | 190092.13 | 0.423265E+09 | 0.105720E+10 | 65953956.48 |
May | 0.437869E+09 | 0.00 | 0.437869E+09 | 0.113388E+10 | 74798615.80 |
June | 0.422219E+09 | 0.00 | 0.422219E+09 | 0.108868E+10 | 79353272.90 |
July | 0.449447E+09 | 0.00 | 0.449447E+09 | 0.100394E+10 | 0.142400E+09 |
August | 0.437540E+09 | 676227.59 | 0.436864E+09 | 0.977589E+09 | 0.120472E+09 |
September | 0.468763E+09 | 15310139.07 | 0.453453E+09 | 0.108465E+10 | 0.119243E+09 |
October | 0.633721E+09 | 0.101042E+09 | 0.532679E+09 | 0.135497E+10 | 0.161608E+09 |
November | 0.797464E+09 | 0.243296E+09 | 0.554168E+09 | 0.166036E+10 | 0.189163E+09 |
December | 0.101227E+10 | 0.430682E+09 | 0.581593E+09 | 0.205194E+10 | 0.282926E+09 |
Annual Sum or Average | 0.745924E+10 | 0.154583E+10 | 0.591341E+10 | 0.166549E+11 | 0.181221E+10 |
Minimum of Months | 0.422219E+09 | 0.00 | 0.422219E+09 | 0.977589E+09 | 65953956.48 |
Maximum of Months | 0.101279E+10 | 0.430682E+09 | 0.590244E+09 | 0.209342E+10 | 0.282926E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101279E+10 | 0.422548E+09 | 0.590244E+09 | 0.209342E+10 | 0.250545E+09 |
February | 0.776786E+09 | 0.253261E+09 | 0.523525E+09 | 0.172132E+10 | 0.180999E+09 |
March | 0.586910E+09 | 78822419.80 | 0.508088E+09 | 0.142696E+10 | 0.144745E+09 |
April | 0.423455E+09 | 190091.90 | 0.423265E+09 | 0.105720E+10 | 65953867.72 |
May | 0.437869E+09 | 0.00 | 0.437869E+09 | 0.113388E+10 | 74798552.86 |
June | 0.422218E+09 | 0.00 | 0.422218E+09 | 0.108868E+10 | 79353211.38 |
July | 0.449447E+09 | 0.00 | 0.449447E+09 | 0.100394E+10 | 0.142400E+09 |
August | 0.437540E+09 | 676226.78 | 0.436864E+09 | 0.977588E+09 | 0.120472E+09 |
September | 0.468762E+09 | 15310120.70 | 0.453452E+09 | 0.108465E+10 | 0.119243E+09 |
October | 0.633721E+09 | 0.101042E+09 | 0.532679E+09 | 0.135497E+10 | 0.161608E+09 |
November | 0.797463E+09 | 0.243295E+09 | 0.554168E+09 | 0.166036E+10 | 0.189162E+09 |
December | 0.101227E+10 | 0.430681E+09 | 0.581593E+09 | 0.205194E+10 | 0.282926E+09 |
Annual Sum or Average | 0.745924E+10 | 0.154583E+10 | 0.591341E+10 | 0.166549E+11 | 0.181221E+10 |
Minimum of Months | 0.422218E+09 | 0.00 | 0.422218E+09 | 0.977588E+09 | 65953867.72 |
Maximum of Months | 0.101279E+10 | 0.430681E+09 | 0.590244E+09 | 0.209342E+10 | 0.282926E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101279E+10 | 0.422549E+09 | 0.590244E+09 | 0.209342E+10 | 0.250545E+09 |
February | 0.776787E+09 | 0.253262E+09 | 0.523525E+09 | 0.172132E+10 | 0.180999E+09 |
March | 0.586911E+09 | 78822514.38 | 0.508088E+09 | 0.142696E+10 | 0.144745E+09 |
April | 0.423455E+09 | 190092.13 | 0.423265E+09 | 0.105720E+10 | 65953956.48 |
May | 0.437869E+09 | 0.00 | 0.437869E+09 | 0.113388E+10 | 74798615.80 |
June | 0.422219E+09 | 0.00 | 0.422219E+09 | 0.108868E+10 | 79353272.90 |
July | 0.449447E+09 | 0.00 | 0.449447E+09 | 0.100394E+10 | 0.142400E+09 |
August | 0.437540E+09 | 676227.59 | 0.436864E+09 | 0.977589E+09 | 0.120472E+09 |
September | 0.468763E+09 | 15310139.07 | 0.453453E+09 | 0.108465E+10 | 0.119243E+09 |
October | 0.633721E+09 | 0.101042E+09 | 0.532679E+09 | 0.135497E+10 | 0.161608E+09 |
November | 0.797464E+09 | 0.243296E+09 | 0.554168E+09 | 0.166036E+10 | 0.189163E+09 |
December | 0.101227E+10 | 0.430682E+09 | 0.581593E+09 | 0.205194E+10 | 0.282926E+09 |
Annual Sum or Average | 0.745924E+10 | 0.154583E+10 | 0.591341E+10 | 0.166549E+11 | 0.181221E+10 |
Minimum of Months | 0.422219E+09 | 0.00 | 0.422219E+09 | 0.977589E+09 | 65953956.48 |
Maximum of Months | 0.101279E+10 | 0.430682E+09 | 0.590244E+09 | 0.209342E+10 | 0.282926E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101279E+10 | 0.422548E+09 | 0.590244E+09 | 0.209342E+10 | 0.250545E+09 |
February | 0.776786E+09 | 0.253261E+09 | 0.523525E+09 | 0.172132E+10 | 0.180999E+09 |
March | 0.586910E+09 | 78822419.80 | 0.508088E+09 | 0.142696E+10 | 0.144745E+09 |
April | 0.423455E+09 | 190091.90 | 0.423265E+09 | 0.105720E+10 | 65953867.72 |
May | 0.437869E+09 | 0.00 | 0.437869E+09 | 0.113388E+10 | 74798552.86 |
June | 0.422218E+09 | 0.00 | 0.422218E+09 | 0.108868E+10 | 79353211.38 |
July | 0.449447E+09 | 0.00 | 0.449447E+09 | 0.100394E+10 | 0.142400E+09 |
August | 0.437540E+09 | 676226.78 | 0.436864E+09 | 0.977588E+09 | 0.120472E+09 |
September | 0.468762E+09 | 15310120.70 | 0.453452E+09 | 0.108465E+10 | 0.119243E+09 |
October | 0.633721E+09 | 0.101042E+09 | 0.532679E+09 | 0.135497E+10 | 0.161608E+09 |
November | 0.797463E+09 | 0.243295E+09 | 0.554168E+09 | 0.166036E+10 | 0.189162E+09 |
December | 0.101227E+10 | 0.430681E+09 | 0.581593E+09 | 0.205194E+10 | 0.282926E+09 |
Annual Sum or Average | 0.745924E+10 | 0.154583E+10 | 0.591341E+10 | 0.166549E+11 | 0.181221E+10 |
Minimum of Months | 0.422218E+09 | 0.00 | 0.422218E+09 | 0.977588E+09 | 65953867.72 |
Maximum of Months | 0.101279E+10 | 0.430681E+09 | 0.590244E+09 | 0.209342E+10 | 0.282926E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101275E+10 | 0.422532E+09 | 0.590221E+09 | 0.209333E+10 | 0.250535E+09 |
February | 0.776756E+09 | 0.253252E+09 | 0.523504E+09 | 0.172125E+10 | 0.180991E+09 |
March | 0.586887E+09 | 78819337.48 | 0.508068E+09 | 0.142691E+10 | 0.144739E+09 |
April | 0.423438E+09 | 190084.46 | 0.423248E+09 | 0.105716E+10 | 65951298.24 |
May | 0.437851E+09 | 0.00 | 0.437851E+09 | 0.113383E+10 | 74795601.09 |
June | 0.422202E+09 | 0.00 | 0.422202E+09 | 0.108864E+10 | 79350074.62 |
July | 0.449429E+09 | 0.00 | 0.449429E+09 | 0.100390E+10 | 0.142395E+09 |
August | 0.437523E+09 | 676200.33 | 0.436846E+09 | 0.977549E+09 | 0.120467E+09 |
September | 0.468744E+09 | 15309522.01 | 0.453434E+09 | 0.108461E+10 | 0.119239E+09 |
October | 0.633696E+09 | 0.101038E+09 | 0.532658E+09 | 0.135492E+10 | 0.161601E+09 |
November | 0.797432E+09 | 0.243286E+09 | 0.554146E+09 | 0.166029E+10 | 0.189155E+09 |
December | 0.101223E+10 | 0.430664E+09 | 0.581570E+09 | 0.205186E+10 | 0.282915E+09 |
Annual Sum or Average | 0.745894E+10 | 0.154577E+10 | 0.591318E+10 | 0.166542E+11 | 0.181213E+10 |
Minimum of Months | 0.422202E+09 | 0.00 | 0.422202E+09 | 0.977549E+09 | 65951298.24 |
Maximum of Months | 0.101275E+10 | 0.430664E+09 | 0.590221E+09 | 0.209333E+10 | 0.282915E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.830400E+09 | 0.291995E+09 | 0.538404E+09 | 0.171530E+10 | 0.287959E+09 |
February | 0.823758E+09 | 0.291509E+09 | 0.532249E+09 | 0.173000E+10 | 0.226300E+09 |
March | 0.102230E+10 | 0.403790E+09 | 0.618513E+09 | 0.217896E+10 | 0.209090E+09 |
April | 0.994219E+09 | 0.380800E+09 | 0.613418E+09 | 0.212135E+10 | 0.130709E+09 |
May | 0.874169E+09 | 0.258976E+09 | 0.615193E+09 | 0.198204E+10 | 86707263.49 |
June | 0.916715E+09 | 0.315970E+09 | 0.600745E+09 | 0.203474E+10 | 0.106795E+09 |
July | 0.807598E+09 | 0.190450E+09 | 0.617148E+09 | 0.167788E+10 | 0.192324E+09 |
August | 0.878020E+09 | 0.260020E+09 | 0.618000E+09 | 0.177824E+10 | 0.187942E+09 |
September | 0.795866E+09 | 0.220738E+09 | 0.575128E+09 | 0.169924E+10 | 0.135126E+09 |
October | 0.772391E+09 | 0.199106E+09 | 0.573285E+09 | 0.155837E+10 | 0.193235E+09 |
November | 0.728939E+09 | 0.198804E+09 | 0.530135E+09 | 0.147013E+10 | 0.235096E+09 |
December | 0.770880E+09 | 0.252169E+09 | 0.518711E+09 | 0.154879E+10 | 0.369453E+09 |
Annual Sum or Average | 0.102153E+11 | 0.326433E+10 | 0.695093E+10 | 0.214950E+11 | 0.236074E+10 |
Minimum of Months | 0.728939E+09 | 0.190450E+09 | 0.518711E+09 | 0.147013E+10 | 86707263.49 |
Maximum of Months | 0.102230E+10 | 0.403790E+09 | 0.618513E+09 | 0.217896E+10 | 0.369453E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.830400E+09 | 0.291995E+09 | 0.538404E+09 | 0.171530E+10 | 0.287959E+09 |
February | 0.823758E+09 | 0.291509E+09 | 0.532249E+09 | 0.173000E+10 | 0.226300E+09 |
March | 0.102230E+10 | 0.403790E+09 | 0.618513E+09 | 0.217896E+10 | 0.209090E+09 |
April | 0.994219E+09 | 0.380800E+09 | 0.613418E+09 | 0.212135E+10 | 0.130709E+09 |
May | 0.874169E+09 | 0.258976E+09 | 0.615193E+09 | 0.198204E+10 | 86707263.49 |
June | 0.916715E+09 | 0.315970E+09 | 0.600745E+09 | 0.203474E+10 | 0.106795E+09 |
July | 0.807598E+09 | 0.190450E+09 | 0.617148E+09 | 0.167788E+10 | 0.192324E+09 |
August | 0.878020E+09 | 0.260020E+09 | 0.618000E+09 | 0.177824E+10 | 0.187942E+09 |
September | 0.795866E+09 | 0.220738E+09 | 0.575128E+09 | 0.169924E+10 | 0.135126E+09 |
October | 0.772391E+09 | 0.199106E+09 | 0.573285E+09 | 0.155837E+10 | 0.193235E+09 |
November | 0.728939E+09 | 0.198804E+09 | 0.530135E+09 | 0.147013E+10 | 0.235096E+09 |
December | 0.770880E+09 | 0.252169E+09 | 0.518711E+09 | 0.154879E+10 | 0.369453E+09 |
Annual Sum or Average | 0.102153E+11 | 0.326433E+10 | 0.695093E+10 | 0.214950E+11 | 0.236074E+10 |
Minimum of Months | 0.728939E+09 | 0.190450E+09 | 0.518711E+09 | 0.147013E+10 | 86707263.49 |
Maximum of Months | 0.102230E+10 | 0.403790E+09 | 0.618513E+09 | 0.217896E+10 | 0.369453E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.830385E+09 | 0.291990E+09 | 0.538395E+09 | 0.171527E+10 | 0.287953E+09 |
February | 0.823743E+09 | 0.291504E+09 | 0.532240E+09 | 0.172997E+10 | 0.226296E+09 |
March | 0.102229E+10 | 0.403783E+09 | 0.618502E+09 | 0.217892E+10 | 0.209086E+09 |
April | 0.994200E+09 | 0.380794E+09 | 0.613407E+09 | 0.212131E+10 | 0.130707E+09 |
May | 0.874154E+09 | 0.258971E+09 | 0.615182E+09 | 0.198200E+10 | 86705679.16 |
June | 0.916698E+09 | 0.315964E+09 | 0.600734E+09 | 0.203471E+10 | 0.106793E+09 |
July | 0.807583E+09 | 0.190447E+09 | 0.617136E+09 | 0.167785E+10 | 0.192320E+09 |
August | 0.878004E+09 | 0.260015E+09 | 0.617989E+09 | 0.177821E+10 | 0.187939E+09 |
September | 0.795852E+09 | 0.220734E+09 | 0.575118E+09 | 0.169921E+10 | 0.135123E+09 |
October | 0.772377E+09 | 0.199102E+09 | 0.573275E+09 | 0.155834E+10 | 0.193231E+09 |
November | 0.728926E+09 | 0.198800E+09 | 0.530125E+09 | 0.147011E+10 | 0.235092E+09 |
December | 0.770865E+09 | 0.252164E+09 | 0.518701E+09 | 0.154876E+10 | 0.369446E+09 |
Annual Sum or Average | 0.102151E+11 | 0.326427E+10 | 0.695080E+10 | 0.214947E+11 | 0.236069E+10 |
Minimum of Months | 0.728926E+09 | 0.190447E+09 | 0.518701E+09 | 0.147011E+10 | 86705679.16 |
Maximum of Months | 0.102229E+10 | 0.403783E+09 | 0.618502E+09 | 0.217892E+10 | 0.369446E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.191261E+10 | 0.00 | 0.191261E+10 | 0.433454E+10 | 0.100874E+10 |
February | 0.184279E+10 | 0.00 | 0.184279E+10 | 0.438381E+10 | 0.710585E+09 |
March | 0.209390E+10 | 0.00 | 0.209390E+10 | 0.529908E+10 | 0.481119E+09 |
April | 0.220522E+10 | 31252047.08 | 0.217396E+10 | 0.576897E+10 | 0.174119E+09 |
May | 0.292105E+10 | 0.311180E+09 | 0.260987E+10 | 0.752582E+10 | 0.296083E+09 |
June | 0.345306E+10 | 0.697837E+09 | 0.275523E+10 | 0.862158E+10 | 0.337854E+09 |
July | 0.306829E+10 | 0.321611E+09 | 0.274667E+10 | 0.700349E+10 | 0.593823E+09 |
August | 0.252620E+10 | 0.107719E+09 | 0.241848E+10 | 0.586922E+10 | 0.433305E+09 |
September | 0.208140E+10 | 996687.49 | 0.208040E+10 | 0.502067E+10 | 0.399490E+09 |
October | 0.207236E+10 | 0.00 | 0.207236E+10 | 0.461723E+10 | 0.543445E+09 |
November | 0.189766E+10 | 0.00 | 0.189766E+10 | 0.426407E+10 | 0.668696E+09 |
December | 0.185808E+10 | 0.00 | 0.185808E+10 | 0.416285E+10 | 0.112805E+10 |
Annual Sum or Average | 0.279326E+11 | 0.147060E+10 | 0.264620E+11 | 0.668713E+11 | 0.677532E+10 |
Minimum of Months | 0.184279E+10 | 0.00 | 0.184279E+10 | 0.416285E+10 | 0.174119E+09 |
Maximum of Months | 0.345306E+10 | 0.697837E+09 | 0.275523E+10 | 0.862158E+10 | 0.112805E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.245869E+10 | 0.828648E+09 | 0.163004E+10 | 0.508238E+10 | 0.667372E+09 |
February | 0.251832E+10 | 0.923340E+09 | 0.159498E+10 | 0.533085E+10 | 0.467261E+09 |
March | 0.303960E+10 | 0.119029E+10 | 0.184931E+10 | 0.660079E+10 | 0.310654E+09 |
April | 0.297288E+10 | 0.113577E+10 | 0.183712E+10 | 0.664967E+10 | 0.110155E+09 |
May | 0.264064E+10 | 0.799317E+09 | 0.184132E+10 | 0.615820E+10 | 0.184710E+09 |
June | 0.272178E+10 | 0.896410E+09 | 0.182537E+10 | 0.625054E+10 | 0.193366E+09 |
July | 0.240227E+10 | 0.538167E+09 | 0.186410E+10 | 0.519194E+10 | 0.366820E+09 |
August | 0.264374E+10 | 0.777147E+09 | 0.186659E+10 | 0.561426E+10 | 0.284277E+09 |
September | 0.240271E+10 | 0.654748E+09 | 0.174796E+10 | 0.524592E+10 | 0.282944E+09 |
October | 0.232693E+10 | 0.595312E+09 | 0.173162E+10 | 0.483470E+10 | 0.375309E+09 |
November | 0.217936E+10 | 0.602257E+09 | 0.157710E+10 | 0.454748E+10 | 0.463916E+09 |
December | 0.230456E+10 | 0.739556E+09 | 0.156501E+10 | 0.473682E+10 | 0.753495E+09 |
Annual Sum or Average | 0.306115E+11 | 0.968096E+10 | 0.209305E+11 | 0.662435E+11 | 0.446028E+10 |
Minimum of Months | 0.217936E+10 | 0.538167E+09 | 0.156501E+10 | 0.454748E+10 | 0.110155E+09 |
Maximum of Months | 0.303960E+10 | 0.119029E+10 | 0.186659E+10 | 0.664967E+10 | 0.753495E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.506390E+10 | 0.211272E+10 | 0.295119E+10 | 0.105075E+11 | 0.116802E+10 |
February | 0.388389E+10 | 0.126629E+10 | 0.261759E+10 | 0.870009E+10 | 0.797936E+09 |
March | 0.293452E+10 | 0.394108E+09 | 0.254041E+10 | 0.733393E+10 | 0.505727E+09 |
April | 0.211725E+10 | 950449.13 | 0.211630E+10 | 0.563541E+10 | 0.149169E+09 |
May | 0.218932E+10 | 0.00 | 0.218932E+10 | 0.595899E+10 | 0.251639E+09 |
June | 0.211107E+10 | 0.00 | 0.211107E+10 | 0.571836E+10 | 0.255305E+09 |
July | 0.224721E+10 | 0.00 | 0.224721E+10 | 0.524561E+10 | 0.520052E+09 |
August | 0.218767E+10 | 3381097.06 | 0.218429E+10 | 0.513679E+10 | 0.379188E+09 |
September | 0.234379E+10 | 76549769.73 | 0.226724E+10 | 0.560485E+10 | 0.413127E+09 |
October | 0.316857E+10 | 0.505203E+09 | 0.266336E+10 | 0.690737E+10 | 0.629707E+09 |
November | 0.398727E+10 | 0.121646E+10 | 0.277081E+10 | 0.843269E+10 | 0.805292E+09 |
December | 0.506131E+10 | 0.215338E+10 | 0.290793E+10 | 0.103369E+11 | 0.131347E+10 |
Annual Sum or Average | 0.372958E+11 | 0.772905E+10 | 0.295667E+11 | 0.855185E+11 | 0.718863E+10 |
Minimum of Months | 0.211107E+10 | 0.00 | 0.211107E+10 | 0.513679E+10 | 0.149169E+09 |
Maximum of Months | 0.506390E+10 | 0.215338E+10 | 0.295119E+10 | 0.105075E+11 | 0.131347E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.249117E+10 | 0.875977E+09 | 0.161520E+10 | 0.519930E+10 | 0.809393E+09 |
February | 0.247125E+10 | 0.874518E+09 | 0.159673E+10 | 0.527024E+10 | 0.592363E+09 |
March | 0.306688E+10 | 0.121136E+10 | 0.185552E+10 | 0.666445E+10 | 0.477062E+09 |
April | 0.298263E+10 | 0.114239E+10 | 0.184024E+10 | 0.656673E+10 | 0.212361E+09 |
May | 0.262248E+10 | 0.776921E+09 | 0.184556E+10 | 0.603325E+10 | 0.219908E+09 |
June | 0.275012E+10 | 0.947901E+09 | 0.180222E+10 | 0.622089E+10 | 0.241031E+09 |
July | 0.242277E+10 | 0.571345E+09 | 0.185142E+10 | 0.518006E+10 | 0.442291E+09 |
August | 0.263403E+10 | 0.780052E+09 | 0.185398E+10 | 0.551433E+10 | 0.362654E+09 |
September | 0.238757E+10 | 0.662208E+09 | 0.172537E+10 | 0.516398E+10 | 0.343595E+09 |
October | 0.231715E+10 | 0.597311E+09 | 0.171984E+10 | 0.477867E+10 | 0.464629E+09 |
November | 0.218679E+10 | 0.596405E+09 | 0.159039E+10 | 0.454365E+10 | 0.554301E+09 |
December | 0.231261E+10 | 0.756498E+09 | 0.155612E+10 | 0.480137E+10 | 0.908323E+09 |
Annual Sum or Average | 0.306455E+11 | 0.979288E+10 | 0.208526E+11 | 0.659369E+11 | 0.562791E+10 |
Minimum of Months | 0.218679E+10 | 0.571345E+09 | 0.155612E+10 | 0.454365E+10 | 0.212361E+09 |
Maximum of Months | 0.306688E+10 | 0.121136E+10 | 0.185552E+10 | 0.666445E+10 | 0.908323E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.191261E+10 | 0.00 | 0.191261E+10 | 0.427644E+10 | 0.102621E+10 |
February | 0.184279E+10 | 0.00 | 0.184279E+10 | 0.432112E+10 | 0.729039E+09 |
March | 0.209390E+10 | 0.00 | 0.209390E+10 | 0.521695E+10 | 0.514651E+09 |
April | 0.220522E+10 | 31252047.08 | 0.217396E+10 | 0.565691E+10 | 0.198362E+09 |
May | 0.292105E+10 | 0.311180E+09 | 0.260987E+10 | 0.741609E+10 | 0.319006E+09 |
June | 0.345306E+10 | 0.697837E+09 | 0.275523E+10 | 0.852735E+10 | 0.367408E+09 |
July | 0.306829E+10 | 0.321611E+09 | 0.274667E+10 | 0.691181E+10 | 0.624501E+09 |
August | 0.252620E+10 | 0.107719E+09 | 0.241848E+10 | 0.579359E+10 | 0.457331E+09 |
September | 0.208140E+10 | 996687.49 | 0.208040E+10 | 0.493396E+10 | 0.433955E+09 |
October | 0.207236E+10 | 0.00 | 0.207236E+10 | 0.454621E+10 | 0.568929E+09 |
November | 0.189766E+10 | 0.00 | 0.189766E+10 | 0.419821E+10 | 0.686436E+09 |
December | 0.185808E+10 | 0.00 | 0.185808E+10 | 0.411091E+10 | 0.113679E+10 |
Annual Sum or Average | 0.279326E+11 | 0.147060E+10 | 0.264620E+11 | 0.659095E+11 | 0.706262E+10 |
Minimum of Months | 0.184279E+10 | 0.00 | 0.184279E+10 | 0.411091E+10 | 0.198362E+09 |
Maximum of Months | 0.345306E+10 | 0.697837E+09 | 0.275523E+10 | 0.852735E+10 | 0.113679E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.245869E+10 | 0.828648E+09 | 0.163004E+10 | 0.503872E+10 | 0.678649E+09 |
February | 0.251832E+10 | 0.923340E+09 | 0.159498E+10 | 0.528404E+10 | 0.477135E+09 |
March | 0.303960E+10 | 0.119029E+10 | 0.184931E+10 | 0.653788E+10 | 0.328452E+09 |
April | 0.297288E+10 | 0.113577E+10 | 0.183712E+10 | 0.657039E+10 | 0.122548E+09 |
May | 0.264064E+10 | 0.799317E+09 | 0.184132E+10 | 0.608226E+10 | 0.198064E+09 |
June | 0.272178E+10 | 0.896410E+09 | 0.182537E+10 | 0.618327E+10 | 0.210506E+09 |
July | 0.240227E+10 | 0.538167E+09 | 0.186410E+10 | 0.513105E+10 | 0.387609E+09 |
August | 0.264374E+10 | 0.777147E+09 | 0.186659E+10 | 0.556223E+10 | 0.300148E+09 |
September | 0.240271E+10 | 0.654748E+09 | 0.174796E+10 | 0.518982E+10 | 0.304643E+09 |
October | 0.232693E+10 | 0.595312E+09 | 0.173162E+10 | 0.478416E+10 | 0.390025E+09 |
November | 0.217936E+10 | 0.602257E+09 | 0.157710E+10 | 0.450052E+10 | 0.474482E+09 |
December | 0.230456E+10 | 0.739556E+09 | 0.156501E+10 | 0.469789E+10 | 0.759173E+09 |
Annual Sum or Average | 0.306115E+11 | 0.968096E+10 | 0.209305E+11 | 0.655622E+11 | 0.463143E+10 |
Minimum of Months | 0.217936E+10 | 0.538167E+09 | 0.156501E+10 | 0.450052E+10 | 0.122548E+09 |
Maximum of Months | 0.303960E+10 | 0.119029E+10 | 0.186659E+10 | 0.657039E+10 | 0.759173E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.506390E+10 | 0.211272E+10 | 0.295119E+10 | 0.104560E+11 | 0.117759E+10 |
February | 0.388389E+10 | 0.126629E+10 | 0.261759E+10 | 0.863989E+10 | 0.809823E+09 |
March | 0.293452E+10 | 0.394108E+09 | 0.254041E+10 | 0.724854E+10 | 0.531659E+09 |
April | 0.211725E+10 | 950449.13 | 0.211630E+10 | 0.551945E+10 | 0.168000E+09 |
May | 0.218932E+10 | 0.00 | 0.218932E+10 | 0.584284E+10 | 0.271453E+09 |
June | 0.211107E+10 | 0.00 | 0.211107E+10 | 0.561583E+10 | 0.279255E+09 |
July | 0.224721E+10 | 0.00 | 0.224721E+10 | 0.515330E+10 | 0.553057E+09 |
August | 0.218767E+10 | 3381097.06 | 0.218429E+10 | 0.505906E+10 | 0.401954E+09 |
September | 0.234379E+10 | 76549769.73 | 0.226724E+10 | 0.551740E+10 | 0.446390E+09 |
October | 0.316857E+10 | 0.505203E+09 | 0.266336E+10 | 0.683442E+10 | 0.652698E+09 |
November | 0.398727E+10 | 0.121646E+10 | 0.277081E+10 | 0.836967E+10 | 0.819107E+09 |
December | 0.506131E+10 | 0.215338E+10 | 0.290793E+10 | 0.102903E+11 | 0.131564E+10 |
Annual Sum or Average | 0.372958E+11 | 0.772905E+10 | 0.295667E+11 | 0.845467E+11 | 0.742663E+10 |
Minimum of Months | 0.211107E+10 | 0.00 | 0.211107E+10 | 0.505906E+10 | 0.168000E+09 |
Maximum of Months | 0.506390E+10 | 0.215338E+10 | 0.295119E+10 | 0.104560E+11 | 0.131564E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.249117E+10 | 0.875977E+09 | 0.161520E+10 | 0.516568E+10 | 0.812701E+09 |
February | 0.247125E+10 | 0.874518E+09 | 0.159673E+10 | 0.523142E+10 | 0.597186E+09 |
March | 0.306688E+10 | 0.121136E+10 | 0.185552E+10 | 0.661341E+10 | 0.488262E+09 |
April | 0.298263E+10 | 0.114239E+10 | 0.184024E+10 | 0.650664E+10 | 0.222765E+09 |
May | 0.262248E+10 | 0.776921E+09 | 0.184556E+10 | 0.597076E+10 | 0.228075E+09 |
June | 0.275012E+10 | 0.947901E+09 | 0.180222E+10 | 0.616184E+10 | 0.251384E+09 |
July | 0.242277E+10 | 0.571345E+09 | 0.185142E+10 | 0.512621E+10 | 0.452451E+09 |
August | 0.263403E+10 | 0.780052E+09 | 0.185398E+10 | 0.546560E+10 | 0.370267E+09 |
September | 0.238757E+10 | 0.662208E+09 | 0.172537E+10 | 0.511380E+10 | 0.356160E+09 |
October | 0.231715E+10 | 0.597311E+09 | 0.171984E+10 | 0.473901E+10 | 0.469469E+09 |
November | 0.218679E+10 | 0.596405E+09 | 0.159039E+10 | 0.450593E+10 | 0.557588E+09 |
December | 0.231261E+10 | 0.756498E+09 | 0.155612E+10 | 0.477084E+10 | 0.905392E+09 |
Annual Sum or Average | 0.306455E+11 | 0.979288E+10 | 0.208526E+11 | 0.653711E+11 | 0.571170E+10 |
Minimum of Months | 0.218679E+10 | 0.571345E+09 | 0.155612E+10 | 0.450593E+10 | 0.222765E+09 |
Maximum of Months | 0.306688E+10 | 0.121136E+10 | 0.185552E+10 | 0.661341E+10 | 0.905392E+09 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1556.12 | 451.27 | 714.09 | 0.00 | 714.09 | 0.00 | 0.00 |
February | 1739.78 | 370.55 | 761.74 | 0.00 | 761.74 | 0.00 | 0.00 |
March | 1883.60 | 283.72 | 781.78 | 0.00 | 781.78 | 0.00 | 0.00 |
April | 2093.37 | 157.01 | 850.78 | 12.06 | 838.72 | 0.00 | 0.00 |
May | 2720.12 | 166.93 | 1090.60 | 116.18 | 974.42 | 0.00 | 0.00 |
June | 3250.82 | 194.13 | 1332.21 | 269.23 | 1062.98 | 0.00 | 0.00 |
July | 2537.65 | 298.85 | 1145.57 | 120.08 | 1025.49 | 0.00 | 0.00 |
August | 2097.99 | 257.63 | 943.18 | 40.22 | 902.96 | 0.00 | 0.00 |
September | 1850.09 | 244.57 | 803.01 | 0.38 | 802.63 | 0.00 | 0.00 |
October | 1641.67 | 303.80 | 773.73 | 0.00 | 773.73 | 0.00 | 0.00 |
November | 1561.37 | 353.76 | 732.12 | 0.00 | 732.12 | 0.00 | 0.00 |
December | 1479.10 | 508.21 | 693.73 | 0.00 | 693.73 | 0.00 | 0.00 |
Annual Sum or Average | 2035.03 | 299.29 | 885.74 | 46.63 | 839.11 | 0.00 | 0.00 |
Minimum of Months | 1479.10 | 157.01 | 693.73 | 0.00 | 693.73 | 0.00 | 0.00 |
Maximum of Months | 3250.82 | 508.21 | 1332.21 | 269.23 | 1062.98 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1873.72 | 284.73 | 917.97 | 309.38 | 608.59 | 0.00 | 0.00 |
February | 2176.96 | 226.49 | 1040.98 | 381.67 | 659.30 | 0.00 | 0.00 |
March | 2430.03 | 168.63 | 1134.86 | 444.41 | 690.45 | 0.00 | 0.00 |
April | 2509.09 | 83.56 | 1146.95 | 438.18 | 708.77 | 0.00 | 0.00 |
May | 2240.40 | 102.93 | 985.91 | 298.43 | 687.47 | 0.00 | 0.00 |
June | 2364.48 | 111.39 | 1050.07 | 345.84 | 704.23 | 0.00 | 0.00 |
July | 1895.25 | 176.98 | 896.91 | 200.93 | 695.98 | 0.00 | 0.00 |
August | 2056.26 | 149.81 | 987.06 | 290.15 | 696.91 | 0.00 | 0.00 |
September | 1982.29 | 162.22 | 926.97 | 252.60 | 674.37 | 0.00 | 0.00 |
October | 1766.86 | 193.15 | 868.78 | 222.27 | 646.52 | 0.00 | 0.00 |
November | 1720.23 | 218.38 | 840.81 | 232.35 | 608.45 | 0.00 | 0.00 |
December | 1747.18 | 304.35 | 860.43 | 276.12 | 584.31 | 0.00 | 0.00 |
Annual Sum or Average | 2061.75 | 181.94 | 970.69 | 306.98 | 663.70 | 0.00 | 0.00 |
Minimum of Months | 1720.23 | 83.56 | 840.81 | 200.93 | 584.31 | 0.00 | 0.00 |
Maximum of Months | 2509.09 | 304.35 | 1146.95 | 444.41 | 708.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3907.93 | 467.71 | 1890.65 | 788.80 | 1101.85 | 0.00 | 0.00 |
February | 3557.59 | 374.08 | 1605.45 | 523.44 | 1082.01 | 0.00 | 0.00 |
March | 2663.81 | 270.21 | 1095.63 | 147.14 | 948.48 | 0.00 | 0.00 |
April | 2039.34 | 127.22 | 816.84 | 0.37 | 816.48 | 0.00 | 0.00 |
May | 2116.69 | 139.63 | 817.40 | 0.00 | 817.40 | 0.00 | 0.00 |
June | 2100.06 | 153.07 | 814.46 | 0.00 | 814.46 | 0.00 | 0.00 |
July | 1874.12 | 265.83 | 839.01 | 0.00 | 839.01 | 0.00 | 0.00 |
August | 1824.93 | 224.89 | 816.79 | 1.26 | 815.52 | 0.00 | 0.00 |
September | 2092.28 | 230.02 | 904.24 | 29.53 | 874.71 | 0.00 | 0.00 |
October | 2529.42 | 301.68 | 1183.01 | 188.62 | 994.39 | 0.00 | 0.00 |
November | 3202.83 | 364.89 | 1538.30 | 469.32 | 1068.99 | 0.00 | 0.00 |
December | 3830.51 | 528.16 | 1889.68 | 803.98 | 1085.70 | 0.00 | 0.00 |
Annual Sum or Average | 2640.60 | 287.32 | 1182.65 | 245.09 | 937.56 | 0.00 | 0.00 |
Minimum of Months | 1824.93 | 127.22 | 814.46 | 0.00 | 814.46 | 0.00 | 0.00 |
Maximum of Months | 3907.93 | 528.16 | 1890.65 | 803.98 | 1101.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1921.24 | 322.53 | 930.10 | 327.05 | 603.05 | 0.00 | 0.00 |
February | 2145.32 | 280.63 | 1021.52 | 361.49 | 660.03 | 0.00 | 0.00 |
March | 2440.58 | 234.19 | 1145.05 | 452.27 | 692.78 | 0.00 | 0.00 |
April | 2455.25 | 151.28 | 1150.71 | 440.74 | 709.97 | 0.00 | 0.00 |
May | 2220.01 | 97.12 | 979.13 | 290.07 | 689.06 | 0.00 | 0.00 |
June | 2355.01 | 123.60 | 1061.01 | 365.70 | 695.30 | 0.00 | 0.00 |
July | 1879.33 | 215.42 | 904.56 | 213.32 | 691.25 | 0.00 | 0.00 |
August | 1991.75 | 210.51 | 983.44 | 291.24 | 692.20 | 0.00 | 0.00 |
September | 1966.71 | 156.39 | 921.14 | 255.48 | 665.65 | 0.00 | 0.00 |
October | 1745.48 | 216.44 | 865.13 | 223.01 | 642.12 | 0.00 | 0.00 |
November | 1701.53 | 272.10 | 843.67 | 230.10 | 613.58 | 0.00 | 0.00 |
December | 1734.75 | 413.81 | 863.44 | 282.45 | 580.99 | 0.00 | 0.00 |
Annual Sum or Average | 2044.80 | 224.57 | 971.77 | 310.53 | 661.23 | 0.00 | 0.00 |
Minimum of Months | 1701.53 | 97.12 | 843.67 | 213.32 | 580.99 | 0.00 | 0.00 |
Maximum of Months | 2455.25 | 413.81 | 1150.71 | 452.27 | 709.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1618.33 | 376.62 | 714.09 | 0.00 | 714.09 | 0.00 | 0.00 |
February | 1812.09 | 293.73 | 761.74 | 0.00 | 761.74 | 0.00 | 0.00 |
March | 1978.45 | 179.63 | 781.77 | 0.00 | 781.77 | 0.00 | 0.00 |
April | 2225.68 | 67.18 | 850.78 | 12.06 | 838.72 | 0.00 | 0.00 |
May | 2809.82 | 110.54 | 1090.60 | 116.18 | 974.41 | 0.00 | 0.00 |
June | 3326.23 | 130.34 | 1332.20 | 269.23 | 1062.97 | 0.00 | 0.00 |
July | 2614.80 | 221.71 | 1145.57 | 120.08 | 1025.49 | 0.00 | 0.00 |
August | 2191.32 | 161.78 | 943.17 | 40.22 | 902.96 | 0.00 | 0.00 |
September | 1936.99 | 154.12 | 803.01 | 0.38 | 802.63 | 0.00 | 0.00 |
October | 1723.88 | 202.90 | 773.73 | 0.00 | 773.73 | 0.00 | 0.00 |
November | 1645.09 | 257.98 | 732.12 | 0.00 | 732.12 | 0.00 | 0.00 |
December | 1554.23 | 421.17 | 693.73 | 0.00 | 693.73 | 0.00 | 0.00 |
Annual Sum or Average | 2120.48 | 214.84 | 885.74 | 46.63 | 839.11 | 0.00 | 0.00 |
Minimum of Months | 1554.23 | 67.18 | 693.73 | 0.00 | 693.73 | 0.00 | 0.00 |
Maximum of Months | 3326.23 | 421.17 | 1332.20 | 269.23 | 1062.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1897.54 | 249.17 | 917.97 | 309.38 | 608.59 | 0.00 | 0.00 |
February | 2203.56 | 193.15 | 1040.97 | 381.67 | 659.30 | 0.00 | 0.00 |
March | 2464.45 | 115.98 | 1134.86 | 444.40 | 690.45 | 0.00 | 0.00 |
April | 2565.46 | 42.50 | 1146.95 | 438.18 | 708.76 | 0.00 | 0.00 |
May | 2299.21 | 68.96 | 985.90 | 298.43 | 687.47 | 0.00 | 0.00 |
June | 2411.47 | 74.60 | 1050.07 | 345.84 | 704.23 | 0.00 | 0.00 |
July | 1938.45 | 136.95 | 896.90 | 200.93 | 695.98 | 0.00 | 0.00 |
August | 2096.12 | 106.14 | 987.06 | 290.15 | 696.91 | 0.00 | 0.00 |
September | 2023.89 | 109.16 | 926.97 | 252.60 | 674.37 | 0.00 | 0.00 |
October | 1805.07 | 140.12 | 868.78 | 222.26 | 646.51 | 0.00 | 0.00 |
November | 1754.43 | 178.98 | 840.80 | 232.35 | 608.45 | 0.00 | 0.00 |
December | 1768.53 | 281.32 | 860.43 | 276.12 | 584.31 | 0.00 | 0.00 |
Annual Sum or Average | 2100.57 | 141.43 | 970.68 | 306.98 | 663.70 | 0.00 | 0.00 |
Minimum of Months | 1754.43 | 42.50 | 840.80 | 200.93 | 584.31 | 0.00 | 0.00 |
Maximum of Months | 2565.46 | 281.32 | 1146.95 | 444.40 | 708.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3923.06 | 436.09 | 1890.65 | 788.80 | 1101.85 | 0.00 | 0.00 |
February | 3596.27 | 329.83 | 1605.44 | 523.43 | 1082.01 | 0.00 | 0.00 |
March | 2738.17 | 188.82 | 1095.62 | 147.14 | 948.48 | 0.00 | 0.00 |
April | 2174.15 | 57.55 | 816.84 | 0.37 | 816.47 | 0.00 | 0.00 |
May | 2224.83 | 93.95 | 817.40 | 0.00 | 817.40 | 0.00 | 0.00 |
June | 2206.16 | 98.50 | 814.46 | 0.00 | 814.46 | 0.00 | 0.00 |
July | 1958.49 | 194.17 | 839.01 | 0.00 | 839.01 | 0.00 | 0.00 |
August | 1917.86 | 141.57 | 816.78 | 1.26 | 815.52 | 0.00 | 0.00 |
September | 2162.36 | 159.39 | 904.24 | 29.53 | 874.71 | 0.00 | 0.00 |
October | 2578.92 | 235.11 | 1183.01 | 188.62 | 994.39 | 0.00 | 0.00 |
November | 3253.35 | 310.68 | 1538.30 | 469.31 | 1068.98 | 0.00 | 0.00 |
December | 3859.36 | 490.39 | 1889.68 | 803.98 | 1085.70 | 0.00 | 0.00 |
Annual Sum or Average | 2711.77 | 227.95 | 1182.64 | 245.09 | 937.55 | 0.00 | 0.00 |
Minimum of Months | 1917.86 | 57.55 | 814.46 | 0.00 | 814.46 | 0.00 | 0.00 |
Maximum of Months | 3923.06 | 490.39 | 1890.65 | 803.98 | 1101.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1941.20 | 302.19 | 930.10 | 327.05 | 603.05 | 0.00 | 0.00 |
February | 2178.50 | 244.86 | 1021.52 | 361.49 | 660.02 | 0.00 | 0.00 |
March | 2488.22 | 178.11 | 1145.04 | 452.27 | 692.77 | 0.00 | 0.00 |
April | 2533.46 | 81.93 | 1150.70 | 440.74 | 709.97 | 0.00 | 0.00 |
May | 2252.56 | 82.10 | 979.12 | 290.07 | 689.05 | 0.00 | 0.00 |
June | 2400.04 | 92.99 | 1061.00 | 365.70 | 695.30 | 0.00 | 0.00 |
July | 1934.01 | 165.13 | 904.56 | 213.32 | 691.24 | 0.00 | 0.00 |
August | 2058.81 | 135.40 | 983.44 | 291.24 | 692.20 | 0.00 | 0.00 |
September | 1992.28 | 132.56 | 921.13 | 255.48 | 665.65 | 0.00 | 0.00 |
October | 1784.15 | 173.47 | 865.12 | 223.01 | 642.11 | 0.00 | 0.00 |
November | 1752.95 | 213.85 | 843.67 | 230.09 | 613.58 | 0.00 | 0.00 |
December | 1792.63 | 339.13 | 863.43 | 282.44 | 580.99 | 0.00 | 0.00 |
Annual Sum or Average | 2090.85 | 178.46 | 971.76 | 310.53 | 661.23 | 0.00 | 0.00 |
Minimum of Months | 1752.95 | 81.93 | 843.67 | 213.32 | 580.99 | 0.00 | 0.00 |
Maximum of Months | 2533.46 | 339.13 | 1150.70 | 452.27 | 709.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1596.64 | 383.14 | 714.09 | 0.00 | 714.09 | 0.00 | 0.00 |
February | 1786.18 | 301.36 | 761.74 | 0.00 | 761.74 | 0.00 | 0.00 |
March | 1947.79 | 192.15 | 781.77 | 0.00 | 781.77 | 0.00 | 0.00 |
April | 2182.45 | 76.53 | 850.78 | 12.06 | 838.72 | 0.00 | 0.00 |
May | 2768.85 | 119.10 | 1090.60 | 116.18 | 974.41 | 0.00 | 0.00 |
June | 3289.87 | 141.75 | 1332.20 | 269.23 | 1062.97 | 0.00 | 0.00 |
July | 2580.57 | 233.16 | 1145.57 | 120.08 | 1025.49 | 0.00 | 0.00 |
August | 2163.08 | 170.75 | 943.17 | 40.22 | 902.96 | 0.00 | 0.00 |
September | 1903.53 | 167.42 | 803.01 | 0.38 | 802.63 | 0.00 | 0.00 |
October | 1697.36 | 212.41 | 773.73 | 0.00 | 773.73 | 0.00 | 0.00 |
November | 1619.68 | 264.83 | 732.12 | 0.00 | 732.12 | 0.00 | 0.00 |
December | 1534.84 | 424.43 | 693.73 | 0.00 | 693.73 | 0.00 | 0.00 |
Annual Sum or Average | 2089.98 | 223.95 | 885.74 | 46.63 | 839.11 | 0.00 | 0.00 |
Minimum of Months | 1534.84 | 76.53 | 693.73 | 0.00 | 693.73 | 0.00 | 0.00 |
Maximum of Months | 3289.87 | 424.43 | 1332.20 | 269.23 | 1062.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1881.24 | 253.38 | 917.97 | 309.38 | 608.59 | 0.00 | 0.00 |
February | 2184.21 | 197.23 | 1040.97 | 381.67 | 659.30 | 0.00 | 0.00 |
March | 2440.97 | 122.63 | 1134.86 | 444.40 | 690.45 | 0.00 | 0.00 |
April | 2534.87 | 47.28 | 1146.95 | 438.18 | 708.76 | 0.00 | 0.00 |
May | 2270.86 | 73.95 | 985.90 | 298.43 | 687.47 | 0.00 | 0.00 |
June | 2385.52 | 81.21 | 1050.07 | 345.84 | 704.23 | 0.00 | 0.00 |
July | 1915.71 | 144.72 | 896.90 | 200.93 | 695.98 | 0.00 | 0.00 |
August | 2076.70 | 112.06 | 987.06 | 290.15 | 696.91 | 0.00 | 0.00 |
September | 2002.25 | 117.53 | 926.97 | 252.60 | 674.37 | 0.00 | 0.00 |
October | 1786.20 | 145.62 | 868.78 | 222.26 | 646.51 | 0.00 | 0.00 |
November | 1736.31 | 183.06 | 840.80 | 232.35 | 608.45 | 0.00 | 0.00 |
December | 1753.99 | 283.44 | 860.43 | 276.12 | 584.31 | 0.00 | 0.00 |
Annual Sum or Average | 2078.96 | 146.86 | 970.68 | 306.98 | 663.70 | 0.00 | 0.00 |
Minimum of Months | 1736.31 | 47.28 | 840.80 | 200.93 | 584.31 | 0.00 | 0.00 |
Maximum of Months | 2534.87 | 283.44 | 1146.95 | 444.40 | 708.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3903.82 | 439.66 | 1890.65 | 788.80 | 1101.85 | 0.00 | 0.00 |
February | 3571.38 | 334.75 | 1605.44 | 523.43 | 1082.01 | 0.00 | 0.00 |
March | 2706.29 | 198.50 | 1095.62 | 147.14 | 948.48 | 0.00 | 0.00 |
April | 2129.42 | 64.81 | 816.84 | 0.37 | 816.47 | 0.00 | 0.00 |
May | 2181.47 | 101.35 | 817.40 | 0.00 | 817.40 | 0.00 | 0.00 |
June | 2166.60 | 107.74 | 814.46 | 0.00 | 814.46 | 0.00 | 0.00 |
July | 1924.02 | 206.49 | 839.01 | 0.00 | 839.01 | 0.00 | 0.00 |
August | 1888.84 | 150.07 | 816.78 | 1.26 | 815.52 | 0.00 | 0.00 |
September | 2128.63 | 172.22 | 904.24 | 29.53 | 874.71 | 0.00 | 0.00 |
October | 2551.68 | 243.69 | 1183.01 | 188.62 | 994.39 | 0.00 | 0.00 |
November | 3229.04 | 316.01 | 1538.30 | 469.31 | 1068.98 | 0.00 | 0.00 |
December | 3841.97 | 491.20 | 1889.68 | 803.98 | 1085.70 | 0.00 | 0.00 |
Annual Sum or Average | 2680.96 | 235.50 | 1182.64 | 245.09 | 937.55 | 0.00 | 0.00 |
Minimum of Months | 1888.84 | 64.81 | 814.46 | 0.00 | 814.46 | 0.00 | 0.00 |
Maximum of Months | 3903.82 | 491.20 | 1890.65 | 803.98 | 1101.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1928.64 | 303.43 | 930.10 | 327.05 | 603.05 | 0.00 | 0.00 |
February | 2162.46 | 246.85 | 1021.52 | 361.49 | 660.02 | 0.00 | 0.00 |
March | 2469.16 | 182.30 | 1145.04 | 452.27 | 692.77 | 0.00 | 0.00 |
April | 2510.28 | 85.94 | 1150.70 | 440.74 | 709.97 | 0.00 | 0.00 |
May | 2229.23 | 85.15 | 979.12 | 290.07 | 689.05 | 0.00 | 0.00 |
June | 2377.25 | 96.98 | 1061.00 | 365.70 | 695.30 | 0.00 | 0.00 |
July | 1913.91 | 168.93 | 904.56 | 213.32 | 691.24 | 0.00 | 0.00 |
August | 2040.62 | 138.24 | 983.44 | 291.24 | 692.20 | 0.00 | 0.00 |
September | 1972.92 | 137.41 | 921.13 | 255.48 | 665.65 | 0.00 | 0.00 |
October | 1769.34 | 175.28 | 865.12 | 223.01 | 642.11 | 0.00 | 0.00 |
November | 1738.40 | 215.12 | 843.67 | 230.09 | 613.58 | 0.00 | 0.00 |
December | 1781.23 | 338.03 | 863.43 | 282.44 | 580.99 | 0.00 | 0.00 |
Annual Sum or Average | 2072.91 | 181.12 | 971.76 | 310.53 | 661.23 | 0.00 | 0.00 |
Minimum of Months | 1738.40 | 85.15 | 843.67 | 213.32 | 580.99 | 0.00 | 0.00 |
Maximum of Months | 2510.28 | 338.03 | 1150.70 | 452.27 | 709.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.416792E+10 | 0.120868E+10 | 0.191262E+10 | 0.00 | 0.191262E+10 | 0.00 | 0.00 |
February | 0.420887E+10 | 0.896434E+09 | 0.184280E+10 | 0.00 | 0.184280E+10 | 0.00 | 0.00 |
March | 0.504505E+10 | 0.759927E+09 | 0.209391E+10 | 0.00 | 0.209391E+10 | 0.00 | 0.00 |
April | 0.542601E+10 | 0.406967E+09 | 0.220522E+10 | 31252158.06 | 0.217397E+10 | 0.00 | 0.00 |
May | 0.728556E+10 | 0.447109E+09 | 0.292106E+10 | 0.311181E+09 | 0.260988E+10 | 0.00 | 0.00 |
June | 0.842613E+10 | 0.503185E+09 | 0.345308E+10 | 0.697839E+09 | 0.275524E+10 | 0.00 | 0.00 |
July | 0.679685E+10 | 0.800435E+09 | 0.306830E+10 | 0.321612E+09 | 0.274668E+10 | 0.00 | 0.00 |
August | 0.561927E+10 | 0.690040E+09 | 0.252621E+10 | 0.107719E+09 | 0.241849E+10 | 0.00 | 0.00 |
September | 0.479542E+10 | 0.633918E+09 | 0.208141E+10 | 996691.03 | 0.208041E+10 | 0.00 | 0.00 |
October | 0.439705E+10 | 0.813685E+09 | 0.207237E+10 | 0.00 | 0.207237E+10 | 0.00 | 0.00 |
November | 0.404708E+10 | 0.916946E+09 | 0.189766E+10 | 0.00 | 0.189766E+10 | 0.00 | 0.00 |
December | 0.396163E+10 | 0.136119E+10 | 0.185808E+10 | 0.00 | 0.185808E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.641768E+11 | 0.943852E+10 | 0.279327E+11 | 0.147060E+10 | 0.264621E+11 | 0.00 | 0.00 |
Minimum of Months | 0.396163E+10 | 0.406967E+09 | 0.184280E+10 | 0.00 | 0.184280E+10 | 0.00 | 0.00 |
Maximum of Months | 0.842613E+10 | 0.136119E+10 | 0.345308E+10 | 0.697839E+09 | 0.275524E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.501856E+10 | 0.762625E+09 | 0.245870E+10 | 0.828651E+09 | 0.163004E+10 | 0.00 | 0.00 |
February | 0.526651E+10 | 0.547926E+09 | 0.251833E+10 | 0.923344E+09 | 0.159499E+10 | 0.00 | 0.00 |
March | 0.650858E+10 | 0.451671E+09 | 0.303961E+10 | 0.119030E+10 | 0.184931E+10 | 0.00 | 0.00 |
April | 0.650356E+10 | 0.216581E+09 | 0.297290E+10 | 0.113577E+10 | 0.183712E+10 | 0.00 | 0.00 |
May | 0.600070E+10 | 0.275680E+09 | 0.264065E+10 | 0.799320E+09 | 0.184133E+10 | 0.00 | 0.00 |
June | 0.612874E+10 | 0.288721E+09 | 0.272179E+10 | 0.896413E+09 | 0.182538E+10 | 0.00 | 0.00 |
July | 0.507625E+10 | 0.474034E+09 | 0.240228E+10 | 0.538169E+09 | 0.186411E+10 | 0.00 | 0.00 |
August | 0.550749E+10 | 0.401253E+09 | 0.264375E+10 | 0.777151E+09 | 0.186660E+10 | 0.00 | 0.00 |
September | 0.513809E+10 | 0.420484E+09 | 0.240272E+10 | 0.654750E+09 | 0.174797E+10 | 0.00 | 0.00 |
October | 0.473236E+10 | 0.517322E+09 | 0.232694E+10 | 0.595315E+09 | 0.173163E+10 | 0.00 | 0.00 |
November | 0.445884E+10 | 0.566050E+09 | 0.217937E+10 | 0.602259E+09 | 0.157711E+10 | 0.00 | 0.00 |
December | 0.467965E+10 | 0.815181E+09 | 0.230457E+10 | 0.739559E+09 | 0.156501E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.650193E+11 | 0.573753E+10 | 0.306116E+11 | 0.968100E+10 | 0.209306E+11 | 0.00 | 0.00 |
Minimum of Months | 0.445884E+10 | 0.216581E+09 | 0.217937E+10 | 0.538169E+09 | 0.156501E+10 | 0.00 | 0.00 |
Maximum of Months | 0.650858E+10 | 0.815181E+09 | 0.303961E+10 | 0.119030E+10 | 0.186660E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.104670E+11 | 0.125271E+10 | 0.506392E+10 | 0.211273E+10 | 0.295120E+10 | 0.00 | 0.00 |
February | 0.860651E+10 | 0.904986E+09 | 0.388390E+10 | 0.126630E+10 | 0.261760E+10 | 0.00 | 0.00 |
March | 0.713476E+10 | 0.723720E+09 | 0.293453E+10 | 0.394109E+09 | 0.254042E+10 | 0.00 | 0.00 |
April | 0.528597E+10 | 0.329767E+09 | 0.211726E+10 | 950452.51 | 0.211631E+10 | 0.00 | 0.00 |
May | 0.566934E+10 | 0.373990E+09 | 0.218933E+10 | 0.00 | 0.218933E+10 | 0.00 | 0.00 |
June | 0.544335E+10 | 0.396763E+09 | 0.211108E+10 | 0.00 | 0.211108E+10 | 0.00 | 0.00 |
July | 0.501964E+10 | 0.711996E+09 | 0.224722E+10 | 0.00 | 0.224722E+10 | 0.00 | 0.00 |
August | 0.488790E+10 | 0.602354E+09 | 0.218768E+10 | 3381109.07 | 0.218430E+10 | 0.00 | 0.00 |
September | 0.542320E+10 | 0.596212E+09 | 0.234379E+10 | 76550041.56 | 0.226724E+10 | 0.00 | 0.00 |
October | 0.677480E+10 | 0.808032E+09 | 0.316858E+10 | 0.505205E+09 | 0.266337E+10 | 0.00 | 0.00 |
November | 0.830173E+10 | 0.945805E+09 | 0.398729E+10 | 0.121647E+10 | 0.277082E+10 | 0.00 | 0.00 |
December | 0.102596E+11 | 0.141462E+10 | 0.506133E+10 | 0.215339E+10 | 0.290794E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.832738E+11 | 0.906096E+10 | 0.372959E+11 | 0.772908E+10 | 0.295668E+11 | 0.00 | 0.00 |
Minimum of Months | 0.488790E+10 | 0.329767E+09 | 0.211108E+10 | 0.00 | 0.211108E+10 | 0.00 | 0.00 |
Maximum of Months | 0.104670E+11 | 0.141462E+10 | 0.506392E+10 | 0.215339E+10 | 0.295120E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.514586E+10 | 0.863871E+09 | 0.249118E+10 | 0.875981E+09 | 0.161520E+10 | 0.00 | 0.00 |
February | 0.518996E+10 | 0.678896E+09 | 0.247126E+10 | 0.874521E+09 | 0.159674E+10 | 0.00 | 0.00 |
March | 0.653684E+10 | 0.627266E+09 | 0.306689E+10 | 0.121136E+10 | 0.185553E+10 | 0.00 | 0.00 |
April | 0.636400E+10 | 0.392125E+09 | 0.298264E+10 | 0.114239E+10 | 0.184024E+10 | 0.00 | 0.00 |
May | 0.594608E+10 | 0.260120E+09 | 0.262249E+10 | 0.776924E+09 | 0.184557E+10 | 0.00 | 0.00 |
June | 0.610419E+10 | 0.320382E+09 | 0.275013E+10 | 0.947905E+09 | 0.180222E+10 | 0.00 | 0.00 |
July | 0.503361E+10 | 0.576968E+09 | 0.242278E+10 | 0.571347E+09 | 0.185143E+10 | 0.00 | 0.00 |
August | 0.533469E+10 | 0.563823E+09 | 0.263405E+10 | 0.780055E+09 | 0.185399E+10 | 0.00 | 0.00 |
September | 0.509770E+10 | 0.405375E+09 | 0.238758E+10 | 0.662211E+09 | 0.172537E+10 | 0.00 | 0.00 |
October | 0.467508E+10 | 0.579700E+09 | 0.231716E+10 | 0.597313E+09 | 0.171984E+10 | 0.00 | 0.00 |
November | 0.441037E+10 | 0.705285E+09 | 0.218680E+10 | 0.596408E+09 | 0.159040E+10 | 0.00 | 0.00 |
December | 0.464634E+10 | 0.110835E+10 | 0.231262E+10 | 0.756501E+09 | 0.155612E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.644847E+11 | 0.708216E+10 | 0.306456E+11 | 0.979292E+10 | 0.208527E+11 | 0.00 | 0.00 |
Minimum of Months | 0.441037E+10 | 0.260120E+09 | 0.218680E+10 | 0.571347E+09 | 0.155612E+10 | 0.00 | 0.00 |
Maximum of Months | 0.653684E+10 | 0.110835E+10 | 0.306689E+10 | 0.121136E+10 | 0.185553E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.433454E+10 | 0.100874E+10 | 0.191261E+10 | 0.00 | 0.191261E+10 | 0.00 | 0.00 |
February | 0.438381E+10 | 0.710585E+09 | 0.184279E+10 | 0.00 | 0.184279E+10 | 0.00 | 0.00 |
March | 0.529908E+10 | 0.481119E+09 | 0.209390E+10 | 0.00 | 0.209390E+10 | 0.00 | 0.00 |
April | 0.576897E+10 | 0.174119E+09 | 0.220522E+10 | 31252047.08 | 0.217396E+10 | 0.00 | 0.00 |
May | 0.752582E+10 | 0.296083E+09 | 0.292105E+10 | 0.311180E+09 | 0.260987E+10 | 0.00 | 0.00 |
June | 0.862158E+10 | 0.337854E+09 | 0.345306E+10 | 0.697837E+09 | 0.275523E+10 | 0.00 | 0.00 |
July | 0.700349E+10 | 0.593823E+09 | 0.306829E+10 | 0.321611E+09 | 0.274667E+10 | 0.00 | 0.00 |
August | 0.586922E+10 | 0.433305E+09 | 0.252620E+10 | 0.107719E+09 | 0.241848E+10 | 0.00 | 0.00 |
September | 0.502067E+10 | 0.399490E+09 | 0.208140E+10 | 996687.49 | 0.208040E+10 | 0.00 | 0.00 |
October | 0.461723E+10 | 0.543445E+09 | 0.207236E+10 | 0.00 | 0.207236E+10 | 0.00 | 0.00 |
November | 0.426407E+10 | 0.668696E+09 | 0.189766E+10 | 0.00 | 0.189766E+10 | 0.00 | 0.00 |
December | 0.416285E+10 | 0.112805E+10 | 0.185808E+10 | 0.00 | 0.185808E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.668713E+11 | 0.677532E+10 | 0.279326E+11 | 0.147060E+10 | 0.264620E+11 | 0.00 | 0.00 |
Minimum of Months | 0.416285E+10 | 0.174119E+09 | 0.184279E+10 | 0.00 | 0.184279E+10 | 0.00 | 0.00 |
Maximum of Months | 0.862158E+10 | 0.112805E+10 | 0.345306E+10 | 0.697837E+09 | 0.275523E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.508238E+10 | 0.667372E+09 | 0.245869E+10 | 0.828648E+09 | 0.163004E+10 | 0.00 | 0.00 |
February | 0.533085E+10 | 0.467261E+09 | 0.251832E+10 | 0.923340E+09 | 0.159498E+10 | 0.00 | 0.00 |
March | 0.660079E+10 | 0.310654E+09 | 0.303960E+10 | 0.119029E+10 | 0.184931E+10 | 0.00 | 0.00 |
April | 0.664967E+10 | 0.110155E+09 | 0.297288E+10 | 0.113577E+10 | 0.183712E+10 | 0.00 | 0.00 |
May | 0.615820E+10 | 0.184710E+09 | 0.264064E+10 | 0.799317E+09 | 0.184132E+10 | 0.00 | 0.00 |
June | 0.625054E+10 | 0.193366E+09 | 0.272178E+10 | 0.896410E+09 | 0.182537E+10 | 0.00 | 0.00 |
July | 0.519194E+10 | 0.366820E+09 | 0.240227E+10 | 0.538167E+09 | 0.186410E+10 | 0.00 | 0.00 |
August | 0.561426E+10 | 0.284277E+09 | 0.264374E+10 | 0.777147E+09 | 0.186659E+10 | 0.00 | 0.00 |
September | 0.524592E+10 | 0.282944E+09 | 0.240271E+10 | 0.654748E+09 | 0.174796E+10 | 0.00 | 0.00 |
October | 0.483470E+10 | 0.375309E+09 | 0.232693E+10 | 0.595312E+09 | 0.173162E+10 | 0.00 | 0.00 |
November | 0.454748E+10 | 0.463916E+09 | 0.217936E+10 | 0.602257E+09 | 0.157710E+10 | 0.00 | 0.00 |
December | 0.473682E+10 | 0.753495E+09 | 0.230456E+10 | 0.739556E+09 | 0.156501E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.662435E+11 | 0.446028E+10 | 0.306115E+11 | 0.968096E+10 | 0.209305E+11 | 0.00 | 0.00 |
Minimum of Months | 0.454748E+10 | 0.110155E+09 | 0.217936E+10 | 0.538167E+09 | 0.156501E+10 | 0.00 | 0.00 |
Maximum of Months | 0.664967E+10 | 0.753495E+09 | 0.303960E+10 | 0.119029E+10 | 0.186659E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.105075E+11 | 0.116802E+10 | 0.506390E+10 | 0.211272E+10 | 0.295119E+10 | 0.00 | 0.00 |
February | 0.870009E+10 | 0.797936E+09 | 0.388389E+10 | 0.126629E+10 | 0.261759E+10 | 0.00 | 0.00 |
March | 0.733393E+10 | 0.505727E+09 | 0.293452E+10 | 0.394108E+09 | 0.254041E+10 | 0.00 | 0.00 |
April | 0.563541E+10 | 0.149169E+09 | 0.211725E+10 | 950449.13 | 0.211630E+10 | 0.00 | 0.00 |
May | 0.595899E+10 | 0.251639E+09 | 0.218932E+10 | 0.00 | 0.218932E+10 | 0.00 | 0.00 |
June | 0.571836E+10 | 0.255305E+09 | 0.211107E+10 | 0.00 | 0.211107E+10 | 0.00 | 0.00 |
July | 0.524561E+10 | 0.520052E+09 | 0.224721E+10 | 0.00 | 0.224721E+10 | 0.00 | 0.00 |
August | 0.513679E+10 | 0.379188E+09 | 0.218767E+10 | 3381097.06 | 0.218429E+10 | 0.00 | 0.00 |
September | 0.560485E+10 | 0.413127E+09 | 0.234379E+10 | 76549769.73 | 0.226724E+10 | 0.00 | 0.00 |
October | 0.690737E+10 | 0.629707E+09 | 0.316857E+10 | 0.505203E+09 | 0.266336E+10 | 0.00 | 0.00 |
November | 0.843269E+10 | 0.805292E+09 | 0.398727E+10 | 0.121646E+10 | 0.277081E+10 | 0.00 | 0.00 |
December | 0.103369E+11 | 0.131347E+10 | 0.506131E+10 | 0.215338E+10 | 0.290793E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.855185E+11 | 0.718863E+10 | 0.372958E+11 | 0.772905E+10 | 0.295667E+11 | 0.00 | 0.00 |
Minimum of Months | 0.513679E+10 | 0.149169E+09 | 0.211107E+10 | 0.00 | 0.211107E+10 | 0.00 | 0.00 |
Maximum of Months | 0.105075E+11 | 0.131347E+10 | 0.506390E+10 | 0.215338E+10 | 0.295119E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.519930E+10 | 0.809393E+09 | 0.249117E+10 | 0.875977E+09 | 0.161520E+10 | 0.00 | 0.00 |
February | 0.527024E+10 | 0.592363E+09 | 0.247125E+10 | 0.874518E+09 | 0.159673E+10 | 0.00 | 0.00 |
March | 0.666445E+10 | 0.477062E+09 | 0.306688E+10 | 0.121136E+10 | 0.185552E+10 | 0.00 | 0.00 |
April | 0.656673E+10 | 0.212361E+09 | 0.298263E+10 | 0.114239E+10 | 0.184024E+10 | 0.00 | 0.00 |
May | 0.603325E+10 | 0.219908E+09 | 0.262248E+10 | 0.776921E+09 | 0.184556E+10 | 0.00 | 0.00 |
June | 0.622089E+10 | 0.241031E+09 | 0.275012E+10 | 0.947901E+09 | 0.180222E+10 | 0.00 | 0.00 |
July | 0.518006E+10 | 0.442291E+09 | 0.242277E+10 | 0.571345E+09 | 0.185142E+10 | 0.00 | 0.00 |
August | 0.551433E+10 | 0.362654E+09 | 0.263403E+10 | 0.780052E+09 | 0.185398E+10 | 0.00 | 0.00 |
September | 0.516398E+10 | 0.343595E+09 | 0.238757E+10 | 0.662208E+09 | 0.172537E+10 | 0.00 | 0.00 |
October | 0.477867E+10 | 0.464629E+09 | 0.231715E+10 | 0.597311E+09 | 0.171984E+10 | 0.00 | 0.00 |
November | 0.454365E+10 | 0.554301E+09 | 0.218679E+10 | 0.596405E+09 | 0.159039E+10 | 0.00 | 0.00 |
December | 0.480137E+10 | 0.908323E+09 | 0.231261E+10 | 0.756498E+09 | 0.155612E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.659369E+11 | 0.562791E+10 | 0.306455E+11 | 0.979288E+10 | 0.208526E+11 | 0.00 | 0.00 |
Minimum of Months | 0.454365E+10 | 0.212361E+09 | 0.218679E+10 | 0.571345E+09 | 0.155612E+10 | 0.00 | 0.00 |
Maximum of Months | 0.666445E+10 | 0.908323E+09 | 0.306688E+10 | 0.121136E+10 | 0.185552E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.427644E+10 | 0.102621E+10 | 0.191261E+10 | 0.00 | 0.191261E+10 | 0.00 | 0.00 |
February | 0.432112E+10 | 0.729039E+09 | 0.184279E+10 | 0.00 | 0.184279E+10 | 0.00 | 0.00 |
March | 0.521695E+10 | 0.514651E+09 | 0.209390E+10 | 0.00 | 0.209390E+10 | 0.00 | 0.00 |
April | 0.565691E+10 | 0.198362E+09 | 0.220522E+10 | 31252047.08 | 0.217396E+10 | 0.00 | 0.00 |
May | 0.741609E+10 | 0.319006E+09 | 0.292105E+10 | 0.311180E+09 | 0.260987E+10 | 0.00 | 0.00 |
June | 0.852735E+10 | 0.367408E+09 | 0.345306E+10 | 0.697837E+09 | 0.275523E+10 | 0.00 | 0.00 |
July | 0.691181E+10 | 0.624501E+09 | 0.306829E+10 | 0.321611E+09 | 0.274667E+10 | 0.00 | 0.00 |
August | 0.579359E+10 | 0.457331E+09 | 0.252620E+10 | 0.107719E+09 | 0.241848E+10 | 0.00 | 0.00 |
September | 0.493396E+10 | 0.433955E+09 | 0.208140E+10 | 996687.49 | 0.208040E+10 | 0.00 | 0.00 |
October | 0.454621E+10 | 0.568929E+09 | 0.207236E+10 | 0.00 | 0.207236E+10 | 0.00 | 0.00 |
November | 0.419821E+10 | 0.686436E+09 | 0.189766E+10 | 0.00 | 0.189766E+10 | 0.00 | 0.00 |
December | 0.411091E+10 | 0.113679E+10 | 0.185808E+10 | 0.00 | 0.185808E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.659095E+11 | 0.706262E+10 | 0.279326E+11 | 0.147060E+10 | 0.264620E+11 | 0.00 | 0.00 |
Minimum of Months | 0.411091E+10 | 0.198362E+09 | 0.184279E+10 | 0.00 | 0.184279E+10 | 0.00 | 0.00 |
Maximum of Months | 0.852735E+10 | 0.113679E+10 | 0.345306E+10 | 0.697837E+09 | 0.275523E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.503872E+10 | 0.678649E+09 | 0.245869E+10 | 0.828648E+09 | 0.163004E+10 | 0.00 | 0.00 |
February | 0.528404E+10 | 0.477135E+09 | 0.251832E+10 | 0.923340E+09 | 0.159498E+10 | 0.00 | 0.00 |
March | 0.653788E+10 | 0.328452E+09 | 0.303960E+10 | 0.119029E+10 | 0.184931E+10 | 0.00 | 0.00 |
April | 0.657039E+10 | 0.122548E+09 | 0.297288E+10 | 0.113577E+10 | 0.183712E+10 | 0.00 | 0.00 |
May | 0.608226E+10 | 0.198064E+09 | 0.264064E+10 | 0.799317E+09 | 0.184132E+10 | 0.00 | 0.00 |
June | 0.618327E+10 | 0.210506E+09 | 0.272178E+10 | 0.896410E+09 | 0.182537E+10 | 0.00 | 0.00 |
July | 0.513105E+10 | 0.387609E+09 | 0.240227E+10 | 0.538167E+09 | 0.186410E+10 | 0.00 | 0.00 |
August | 0.556223E+10 | 0.300148E+09 | 0.264374E+10 | 0.777147E+09 | 0.186659E+10 | 0.00 | 0.00 |
September | 0.518982E+10 | 0.304643E+09 | 0.240271E+10 | 0.654748E+09 | 0.174796E+10 | 0.00 | 0.00 |
October | 0.478416E+10 | 0.390025E+09 | 0.232693E+10 | 0.595312E+09 | 0.173162E+10 | 0.00 | 0.00 |
November | 0.450052E+10 | 0.474482E+09 | 0.217936E+10 | 0.602257E+09 | 0.157710E+10 | 0.00 | 0.00 |
December | 0.469789E+10 | 0.759173E+09 | 0.230456E+10 | 0.739556E+09 | 0.156501E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.655622E+11 | 0.463143E+10 | 0.306115E+11 | 0.968096E+10 | 0.209305E+11 | 0.00 | 0.00 |
Minimum of Months | 0.450052E+10 | 0.122548E+09 | 0.217936E+10 | 0.538167E+09 | 0.156501E+10 | 0.00 | 0.00 |
Maximum of Months | 0.657039E+10 | 0.759173E+09 | 0.303960E+10 | 0.119029E+10 | 0.186659E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.104560E+11 | 0.117759E+10 | 0.506390E+10 | 0.211272E+10 | 0.295119E+10 | 0.00 | 0.00 |
February | 0.863989E+10 | 0.809823E+09 | 0.388389E+10 | 0.126629E+10 | 0.261759E+10 | 0.00 | 0.00 |
March | 0.724854E+10 | 0.531659E+09 | 0.293452E+10 | 0.394108E+09 | 0.254041E+10 | 0.00 | 0.00 |
April | 0.551945E+10 | 0.168000E+09 | 0.211725E+10 | 950449.13 | 0.211630E+10 | 0.00 | 0.00 |
May | 0.584284E+10 | 0.271453E+09 | 0.218932E+10 | 0.00 | 0.218932E+10 | 0.00 | 0.00 |
June | 0.561583E+10 | 0.279255E+09 | 0.211107E+10 | 0.00 | 0.211107E+10 | 0.00 | 0.00 |
July | 0.515330E+10 | 0.553057E+09 | 0.224721E+10 | 0.00 | 0.224721E+10 | 0.00 | 0.00 |
August | 0.505906E+10 | 0.401954E+09 | 0.218767E+10 | 3381097.06 | 0.218429E+10 | 0.00 | 0.00 |
September | 0.551740E+10 | 0.446390E+09 | 0.234379E+10 | 76549769.73 | 0.226724E+10 | 0.00 | 0.00 |
October | 0.683442E+10 | 0.652698E+09 | 0.316857E+10 | 0.505203E+09 | 0.266336E+10 | 0.00 | 0.00 |
November | 0.836967E+10 | 0.819107E+09 | 0.398727E+10 | 0.121646E+10 | 0.277081E+10 | 0.00 | 0.00 |
December | 0.102903E+11 | 0.131564E+10 | 0.506131E+10 | 0.215338E+10 | 0.290793E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.845467E+11 | 0.742663E+10 | 0.372958E+11 | 0.772905E+10 | 0.295667E+11 | 0.00 | 0.00 |
Minimum of Months | 0.505906E+10 | 0.168000E+09 | 0.211107E+10 | 0.00 | 0.211107E+10 | 0.00 | 0.00 |
Maximum of Months | 0.104560E+11 | 0.131564E+10 | 0.506390E+10 | 0.215338E+10 | 0.295119E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.516568E+10 | 0.812701E+09 | 0.249117E+10 | 0.875977E+09 | 0.161520E+10 | 0.00 | 0.00 |
February | 0.523142E+10 | 0.597186E+09 | 0.247125E+10 | 0.874518E+09 | 0.159673E+10 | 0.00 | 0.00 |
March | 0.661341E+10 | 0.488262E+09 | 0.306688E+10 | 0.121136E+10 | 0.185552E+10 | 0.00 | 0.00 |
April | 0.650664E+10 | 0.222765E+09 | 0.298263E+10 | 0.114239E+10 | 0.184024E+10 | 0.00 | 0.00 |
May | 0.597076E+10 | 0.228075E+09 | 0.262248E+10 | 0.776921E+09 | 0.184556E+10 | 0.00 | 0.00 |
June | 0.616184E+10 | 0.251384E+09 | 0.275012E+10 | 0.947901E+09 | 0.180222E+10 | 0.00 | 0.00 |
July | 0.512621E+10 | 0.452451E+09 | 0.242277E+10 | 0.571345E+09 | 0.185142E+10 | 0.00 | 0.00 |
August | 0.546560E+10 | 0.370267E+09 | 0.263403E+10 | 0.780052E+09 | 0.185398E+10 | 0.00 | 0.00 |
September | 0.511380E+10 | 0.356160E+09 | 0.238757E+10 | 0.662208E+09 | 0.172537E+10 | 0.00 | 0.00 |
October | 0.473901E+10 | 0.469469E+09 | 0.231715E+10 | 0.597311E+09 | 0.171984E+10 | 0.00 | 0.00 |
November | 0.450593E+10 | 0.557588E+09 | 0.218679E+10 | 0.596405E+09 | 0.159039E+10 | 0.00 | 0.00 |
December | 0.477084E+10 | 0.905392E+09 | 0.231261E+10 | 0.756498E+09 | 0.155612E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.653711E+11 | 0.571170E+10 | 0.306455E+11 | 0.979288E+10 | 0.208526E+11 | 0.00 | 0.00 |
Minimum of Months | 0.450593E+10 | 0.222765E+09 | 0.218679E+10 | 0.571345E+09 | 0.155612E+10 | 0.00 | 0.00 |
Maximum of Months | 0.661341E+10 | 0.905392E+09 | 0.306688E+10 | 0.121136E+10 | 0.185552E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 26.42 | 22.38 | 20.70 | 2.25 | 18.66 | 103.85 | 146.57 | 0.01 |
February | 27.50 | 22.91 | 21.01 | 2.37 | 18.54 | 110.59 | 164.59 | 0.00 |
March | 28.33 | 23.63 | 21.77 | 3.67 | 19.85 | 110.33 | 194.39 | 0.01 |
April | 29.15 | 25.37 | 24.04 | 2.98 | 21.51 | 118.69 | 185.56 | 0.03 |
May | 29.01 | 26.53 | 25.72 | 3.19 | 23.00 | 127.71 | 124.87 | 0.08 |
June | 28.86 | 26.50 | 25.74 | 3.10 | 22.78 | 123.38 | 156.09 | 0.05 |
July | 27.25 | 24.29 | 23.20 | 2.32 | 21.53 | 137.39 | 88.28 | 0.02 |
August | 27.54 | 25.86 | 25.31 | 3.22 | 21.55 | 129.55 | 122.00 | 0.07 |
September | 27.58 | 25.59 | 24.93 | 2.22 | 22.01 | 128.30 | 103.37 | 0.04 |
October | 26.89 | 25.07 | 24.46 | 2.18 | 21.39 | 123.79 | 92.41 | 0.11 |
November | 26.68 | 24.14 | 23.20 | 1.94 | 20.29 | 113.70 | 103.30 | 0.02 |
December | 25.97 | 22.85 | 21.57 | 2.00 | 18.63 | 101.83 | 131.96 | 0.00 |
Annual Sum or Average | 27.59 | 24.60 | 23.48 | 2.62 | 20.82 | 119.14 | 134.17 | 0.04 |
Minimum of Months | 25.97 | 22.38 | 20.70 | 1.94 | 18.54 | 101.83 | 88.28 | 0.00 |
Maximum of Months | 29.15 | 26.53 | 25.74 | 3.67 | 23.00 | 137.39 | 194.39 | 0.11 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 34.10 | 04-JAN-12:00 | 23.67 | 19.40 | 5.00 | 24.66 | 266.50 | 576.50 |
February | 35.00 | 21-FEB-13:00 | 22.02 | 16.00 | 2.10 | 24.16 | 230.00 | 672.50 |
March | 36.40 | 21-MAR-12:00 | 23.01 | 17.00 | 5.00 | 26.97 | 269.50 | 658.50 |
April | 35.50 | 01-APR-13:00 | 26.96 | 24.00 | 2.50 | 27.14 | 295.50 | 519.50 |
May | 37.60 | 06-MAY-12:00 | 26.43 | 22.60 | 4.00 | 29.39 | 317.00 | 525.50 |
June | 36.00 | 12-JUN-14:00 | 27.60 | 25.00 | 4.00 | 28.43 | 235.00 | 472.00 |
July | 33.20 | 15-JUL-15:00 | 25.63 | 23.00 | 2.00 | 27.95 | 219.00 | 181.00 |
August | 34.00 | 10-AUG-13:00 | 27.86 | 26.00 | 5.00 | 26.65 | 344.50 | 278.50 |
September | 34.00 | 06-SEP-13:00 | 26.51 | 24.00 | 4.00 | 25.00 | 258.00 | 581.50 |
October | 33.00 | 04-OCT-13:00 | 26.23 | 24.00 | 4.00 | 25.16 | 303.00 | 428.50 |
November | 34.30 | 18-NOV-12:00 | 25.34 | 22.20 | 3.00 | 25.49 | 289.50 | 511.50 |
December | 33.00 | 07-DEC-13:00 | 23.23 | 19.00 | 3.00 | 22.98 | 215.00 | 596.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 33.00 | 22.02 | 16.00 | 2.00 | 22.98 | 215.00 | 181.00 | |
Maximum of Months | 37.60 | 27.86 | 26.00 | 5.00 | 29.39 | 344.50 | 672.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 18.70 | 23-JAN-05:00 | 16.92 | 16.00 | 2.00 | 7.75 | 0.00 | 0.00 |
February | 20.30 | 21-FEB-09:00 | 19.04 | 18.40 | 2.00 | 10.50 | 258.50 | 564.00 |
March | 22.00 | 03-MAR-05:00 | 19.94 | 19.00 | 3.00 | 13.35 | 0.00 | 0.00 |
April | 22.90 | 14-APR-15:00 | 22.90 | 22.90 | 3.00 | 14.65 | 199.50 | 264.50 |
May | 22.00 | 10-MAY-19:00 | 22.00 | 22.00 | 2.00 | 18.28 | 0.00 | 0.00 |
June | 23.00 | 20-JUN-23:00 | 23.00 | 23.00 | 2.00 | 19.35 | 0.00 | 0.00 |
July | 23.00 | 13-JUL-04:00 | 22.27 | 22.00 | 0.00 | 13.91 | 0.00 | 0.00 |
August | 22.00 | 20-AUG-10:00 | 22.00 | 22.00 | 5.00 | 18.28 | 430.50 | 41.50 |
September | 22.90 | 19-SEP-03:00 | 22.78 | 22.78 | 0.00 | 21.27 | 0.00 | 0.00 |
October | 22.50 | 23-OCT-04:00 | 22.50 | 22.50 | 2.80 | 18.82 | 0.00 | 0.00 |
November | 20.00 | 25-NOV-04:00 | 18.63 | 18.00 | 2.00 | 10.69 | 0.00 | 0.00 |
December | 18.00 | 21-DEC-04:00 | 17.36 | 17.00 | 3.00 | 9.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.00 | 16.92 | 16.00 | 0.00 | 7.75 | 0.00 | 0.00 | |
Maximum of Months | 23.00 | 23.00 | 23.00 | 5.00 | 21.27 | 430.50 | 564.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 25.53 | 12-JAN-12:00 | 32.40 | 23.10 | 2.00 | 25.00 | 353.00 | 347.00 |
February | 26.17 | 14-FEB-15:00 | 32.30 | 24.20 | 2.00 | 25.16 | 200.00 | 199.00 |
March | 26.28 | 27-MAR-12:00 | 34.20 | 23.60 | 4.00 | 26.32 | 326.00 | 535.00 |
April | 27.93 | 10-APR-16:49 | 31.52 | 26.85 | 4.08 | 27.70 | 110.67 | 57.00 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 30.11 | 15-JUN-09:00 | 33.20 | 29.20 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.43 | 20-JUL-14:00 | 32.80 | 24.20 | 1.00 | 26.65 | 305.00 | 253.00 |
August | 28.81 | 14-AUG-16:00 | 32.00 | 28.00 | 1.00 | 25.16 | 107.50 | 223.00 |
September | 30.06 | 30-SEP-10:00 | 32.80 | 29.40 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 27.36 | 16-OCT-14:00 | 31.50 | 26.00 | 3.00 | 24.16 | 239.00 | 346.50 |
November | 27.56 | 10-NOV-12:00 | 31.00 | 26.40 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.86 | 03-DEC-12:00 | 31.50 | 25.30 | 1.00 | 23.49 | 301.00 | 468.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 25.53 | 29.00 | 23.10 | 1.00 | 22.47 | 0.00 | 0.00 | |
Maximum of Months | 30.11 | 34.20 | 29.40 | 6.00 | 28.11 | 398.00 | 535.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.20 | 09-JAN-21:00 | 26.50 | 24.77 | 4.00 | 25.16 | 0.00 | 0.00 |
February | 24.40 | 15-FEB-18:00 | 28.30 | 25.33 | 4.00 | 20.75 | 0.00 | 0.00 |
March | 25.30 | 28-MAR-06:00 | 27.20 | 25.72 | 3.00 | 19.87 | 103.00 | 28.00 |
April | 27.00 | 10-APR-17:00 | 30.50 | 27.87 | 4.50 | 25.00 | 20.00 | 20.50 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 29.20 | 15-JUN-09:00 | 33.20 | 30.11 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.00 | 10-JUL-14:00 | 26.50 | 26.11 | 2.30 | 23.49 | 286.00 | 36.50 |
August | 28.00 | 02-AUG-10:00 | 31.00 | 28.65 | 4.00 | 24.16 | 419.00 | 195.50 |
September | 29.40 | 30-SEP-10:00 | 32.80 | 30.06 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 26.50 | 16-OCT-08:00 | 29.00 | 27.04 | 2.50 | 21.78 | 300.00 | 326.00 |
November | 26.40 | 10-NOV-12:00 | 31.00 | 27.56 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.00 | 10-DEC-17:00 | 29.00 | 26.74 | 3.00 | 21.78 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.20 | 26.50 | 24.77 | 2.30 | 19.87 | 0.00 | 0.00 | |
Maximum of Months | 29.40 | 33.20 | 30.11 | 6.00 | 28.11 | 419.00 | 421.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 29.71 | 38.82 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 29.90 | 44.34 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 30.35 | 50.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 30.97 | 51.18 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.58 | 43.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 32.02 | 46.77 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 32.16 | 39.95 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 31.97 | 43.65 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 31.50 | 40.53 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.87 | 37.35 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 30.27 | 35.77 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 29.84 | 36.19 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 30.93 | 42.35 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 29.71 | 35.77 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 32.16 | 51.18 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.244835E+11 | -0.240913E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -392123286.9 | 60.05 | 0.00 | 0.00 |
February | 0.221056E+11 | -0.217571E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -348458439.2 | 60.05 | 0.00 | 0.00 |
March | 0.255783E+11 | -0.252054E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -372881991.6 | 60.05 | 0.00 | 0.00 |
April | 0.227358E+11 | -0.223749E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -360911388.4 | 60.05 | 0.00 | 0.00 |
May | 0.237634E+11 | -0.233896E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -373789582.3 | 60.05 | 0.00 | 0.00 |
June | 0.232138E+11 | -0.228544E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -359391420.2 | 60.05 | 0.00 | 0.00 |
July | 0.219914E+11 | -0.216203E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -371117929.5 | 60.05 | 0.00 | 0.00 |
August | 0.242042E+11 | -0.238346E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -369590116.5 | 60.05 | 0.00 | 0.00 |
September | 0.223406E+11 | -0.219798E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -360803002.4 | 60.05 | 0.00 | 0.00 |
October | 0.235413E+11 | -0.231679E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -373383672.5 | 60.05 | 0.00 | 0.00 |
November | 0.235671E+11 | -0.232043E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -362777517.7 | 60.05 | 0.00 | 0.00 |
December | 0.238119E+11 | -0.234237E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -388162126.5 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.281337E+12 | -0.276903E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.443339E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.219914E+11 | -0.252054E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -392123286.9 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.255783E+11 | -0.216203E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -348458439.2 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.51 | 0.48 | 01-JAN-07:00 | 2249.34 | 26.27 | 215.50 | 323.50 | 1036.19 | 22.28 | 285.17 | 299.83 |
February | 321.17 | 0.51 | 0.48 | 01-FEB-07:10 | 1785.27 | 20.66 | 105.67 | 294.50 | 927.84 | 21.98 | 255.00 | 272.83 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-07:49 | 1363.35 | 20.37 | 60.50 | 327.33 | 749.68 | 21.66 | 268.33 | 300.33 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:10 | 1125.35 | 20.01 | 0.00 | 325.17 | 632.64 | 21.35 | 227.00 | 287.50 |
May | 376.33 | 0.52 | 0.48 | 01-MAY-06:00 | 961.82 | 18.99 | 0.00 | 331.67 | 530.99 | 20.28 | 106.33 | 284.50 |
June | 370.50 | 0.52 | 0.48 | 01-JUN-07:49 | 942.31 | 19.14 | 0.00 | 324.50 | 536.82 | 20.50 | 126.50 | 279.17 |
July | 383.17 | 0.53 | 0.48 | 01-JUL-07:19 | 908.01 | 18.59 | 0.00 | 328.17 | 490.13 | 19.83 | 38.83 | 277.00 |
August | 369.33 | 0.52 | 0.48 | 01-AUG-07:10 | 1073.73 | 19.48 | 1.67 | 330.50 | 582.46 | 20.77 | 158.00 | 287.67 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-06:00 | 1207.63 | 19.34 | 10.83 | 314.67 | 628.90 | 20.59 | 182.33 | 276.17 |
October | 356.83 | 0.51 | 0.48 | 01-OCT-06:00 | 1554.27 | 20.77 | 85.00 | 324.83 | 780.56 | 21.74 | 249.67 | 286.50 |
November | 337.67 | 0.51 | 0.48 | 01-NOV-07:10 | 1954.56 | 24.77 | 198.83 | 313.33 | 947.39 | 23.39 | 285.00 | 285.00 |
December | 349.33 | 0.51 | 0.48 | 01-DEC-06:49 | 2257.33 | 26.30 | 208.33 | 320.83 | 1072.83 | 24.04 | 305.83 | 300.33 |
Annual Sum or Average | 4292.33 | 0.52 | 1432.47 | 21.16 | 886.33 | 3859.00 | 735.89 | 21.49 | 2488.00 | 3436.83 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 908.01 | 18.59 | 0.00 | 294.50 | 490.13 | 19.83 | 38.83 | 272.83 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 2257.33 | 26.30 | 215.50 | 331.67 | 1072.83 | 24.04 | 305.83 | 300.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.52 | 0.48 | 01-JAN-07:19 | 1902.36 | 23.73 | 108.50 | 311.17 | 988.77 | 24.00 | 194.33 | 275.83 |
February | 321.17 | 0.52 | 0.48 | 01-FEB-06:40 | 2113.95 | 23.89 | 99.17 | 288.50 | 1100.65 | 24.15 | 162.67 | 261.33 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-07:10 | 2390.29 | 23.99 | 112.33 | 325.17 | 987.76 | 23.09 | 155.67 | 298.00 |
April | 358.33 | 0.51 | 0.48 | 01-APR-06:10 | 1991.26 | 23.26 | 90.50 | 330.00 | 1038.02 | 23.73 | 156.67 | 300.33 |
May | 376.33 | 0.52 | 0.48 | 01-MAY-05:00 | 1715.39 | 22.71 | 98.00 | 339.83 | 880.21 | 23.17 | 153.00 | 301.50 |
June | 370.50 | 0.51 | 0.48 | 01-JUN-06:49 | 1836.72 | 22.95 | 93.17 | 336.17 | 950.56 | 23.44 | 173.17 | 303.50 |
July | 383.17 | 0.52 | 0.48 | 01-JUL-06:19 | 1524.71 | 22.33 | 95.67 | 338.67 | 771.96 | 22.75 | 157.50 | 296.67 |
August | 369.33 | 0.51 | 0.48 | 01-AUG-05:00 | 1740.69 | 22.77 | 91.00 | 338.00 | 892.90 | 23.24 | 161.67 | 303.00 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-06:10 | 1634.95 | 22.23 | 90.67 | 315.83 | 833.40 | 22.64 | 151.67 | 278.17 |
October | 356.83 | 0.52 | 0.48 | 01-OCT-05:00 | 1638.48 | 22.63 | 91.50 | 318.33 | 828.53 | 22.98 | 165.00 | 280.83 |
November | 337.67 | 0.52 | 0.48 | 01-NOV-06:40 | 1643.50 | 22.58 | 84.83 | 299.33 | 816.58 | 22.72 | 173.83 | 263.17 |
December | 349.33 | 0.53 | 0.48 | 01-DEC-06:40 | 1848.87 | 23.79 | 112.50 | 303.67 | 841.00 | 23.02 | 192.33 | 270.50 |
Annual Sum or Average | 4292.33 | 0.52 | 1828.04 | 23.06 | 1167.83 | 3844.67 | 908.90 | 23.24 | 1997.50 | 3432.83 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 1524.71 | 22.23 | 84.83 | 288.50 | 771.96 | 22.64 | 151.67 | 261.33 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 2390.29 | 23.99 | 112.50 | 339.83 | 1100.65 | 24.15 | 194.33 | 303.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.54 | 0.48 | 01-JAN-08:50 | 772.33 | 18.13 | 0.00 | 300.50 | 452.13 | 19.50 | 0.00 | 244.33 |
February | 321.17 | 0.53 | 0.48 | 01-FEB-07:00 | 850.58 | 18.62 | 0.00 | 281.00 | 499.83 | 19.97 | 9.50 | 242.83 |
March | 361.17 | 0.52 | 0.48 | 01-MAR-08:09 | 971.12 | 19.49 | 0.00 | 324.67 | 569.22 | 20.81 | 147.33 | 290.50 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:49 | 1180.11 | 20.46 | 17.33 | 333.67 | 660.73 | 21.76 | 245.00 | 303.17 |
May | 376.33 | 0.51 | 0.48 | 01-MAY-06:19 | 1358.81 | 20.36 | 79.67 | 349.83 | 704.42 | 21.59 | 240.00 | 317.50 |
June | 370.50 | 0.50 | 0.48 | 01-JUN-07:30 | 1623.24 | 24.34 | 190.33 | 348.67 | 816.59 | 23.31 | 319.83 | 323.33 |
July | 383.17 | 0.51 | 0.48 | 01-JUL-06:49 | 1403.68 | 23.86 | 138.33 | 352.17 | 695.93 | 23.38 | 281.67 | 320.00 |
August | 369.33 | 0.50 | 0.48 | 01-AUG-06:30 | 1264.76 | 20.25 | 51.00 | 343.83 | 670.23 | 21.52 | 225.67 | 308.17 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-06:00 | 1029.41 | 19.04 | 0.00 | 315.50 | 552.02 | 20.27 | 117.83 | 274.17 |
October | 356.83 | 0.53 | 0.48 | 01-OCT-07:49 | 911.41 | 18.86 | 0.00 | 312.00 | 496.70 | 20.09 | 63.33 | 261.83 |
November | 337.67 | 0.53 | 0.48 | 01-NOV-07:49 | 817.91 | 18.50 | 0.00 | 289.67 | 457.32 | 19.77 | 1.17 | 237.83 |
December | 349.33 | 0.55 | 0.48 | 01-DEC-07:40 | 750.99 | 17.91 | 0.00 | 293.50 | 434.38 | 19.26 | 0.00 | 236.67 |
Annual Sum or Average | 4292.33 | 0.52 | 1087.40 | 20.05 | 476.67 | 3845.00 | 588.07 | 20.98 | 1651.33 | 3360.33 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 750.99 | 17.91 | 0.00 | 281.00 | 434.38 | 19.26 | 0.00 | 236.67 | |
Maximum of Months | 383.17 | 0.55 | 0.48 | 1623.24 | 24.34 | 190.33 | 352.17 | 816.59 | 23.38 | 319.83 | 323.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.52 | 0.48 | 01-JAN-09:09 | 1962.78 | 23.94 | 109.33 | 310.33 | 1017.55 | 24.15 | 196.17 | 277.83 |
February | 321.17 | 0.52 | 0.48 | 01-FEB-08:09 | 2198.44 | 23.86 | 102.33 | 284.83 | 919.28 | 22.85 | 157.17 | 257.67 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-08:39 | 2444.65 | 23.71 | 112.67 | 333.17 | 1005.70 | 22.79 | 159.17 | 302.50 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:30 | 2370.06 | 18.70 | 0.00 | 329.17 | 994.61 | 20.85 | 129.33 | 299.50 |
May | 376.33 | 0.52 | 0.48 | 01-MAY-07:19 | 1897.69 | 18.42 | 0.00 | 338.17 | 837.69 | 20.32 | 125.00 | 300.33 |
June | 370.50 | 0.51 | 0.48 | 01-JUN-08:20 | 2101.66 | 18.82 | 0.00 | 335.00 | 919.29 | 20.83 | 143.00 | 302.33 |
July | 383.17 | 0.52 | 0.48 | 01-JUL-07:00 | 1536.71 | 18.23 | 0.00 | 337.83 | 771.39 | 20.00 | 112.50 | 296.00 |
August | 369.33 | 0.51 | 0.48 | 01-AUG-07:30 | 1982.71 | 18.93 | 8.50 | 335.50 | 869.70 | 20.51 | 122.00 | 299.50 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-07:40 | 1784.34 | 21.35 | 87.00 | 311.67 | 804.54 | 20.24 | 113.83 | 277.50 |
October | 356.83 | 0.52 | 0.48 | 01-OCT-08:20 | 1703.61 | 23.20 | 103.67 | 316.17 | 866.71 | 23.55 | 169.50 | 281.83 |
November | 337.67 | 0.52 | 0.48 | 01-NOV-08:20 | 1690.71 | 23.40 | 96.00 | 302.00 | 860.30 | 23.67 | 183.67 | 267.33 |
December | 349.33 | 0.53 | 0.48 | 01-DEC-07:49 | 1760.81 | 23.41 | 102.83 | 308.00 | 912.63 | 23.66 | 197.67 | 273.00 |
Annual Sum or Average | 4292.33 | 0.52 | 1950.66 | 21.25 | 722.33 | 3841.83 | 897.13 | 21.90 | 1809.00 | 3435.33 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 1536.71 | 18.23 | 0.00 | 284.83 | 771.39 | 20.00 | 112.50 | 257.67 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 2444.65 | 23.94 | 112.67 | 338.17 | 1017.55 | 24.15 | 197.67 | 302.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.51 | 0.48 | 01-JAN-07:49 | 2275.54 | 22.11 | 147.33 | 323.83 | 1158.08 | 21.86 | 88.50 | 312.83 |
February | 321.17 | 0.51 | 0.48 | 01-FEB-07:10 | 1811.57 | 14.31 | 0.00 | 294.50 | 988.93 | 17.86 | 0.00 | 276.00 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-07:49 | 1385.04 | 14.65 | 0.00 | 327.50 | 798.25 | 18.08 | 0.00 | 303.50 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:10 | 1142.66 | 14.47 | 0.00 | 325.50 | 673.09 | 17.89 | 0.00 | 292.50 |
May | 376.33 | 0.52 | 0.48 | 01-MAY-06:00 | 975.49 | 13.15 | 0.00 | 332.17 | 564.68 | 16.50 | 0.00 | 287.83 |
June | 370.50 | 0.52 | 0.48 | 01-JUN-07:49 | 956.67 | 13.49 | 0.00 | 325.17 | 571.09 | 16.92 | 0.00 | 284.00 |
July | 383.17 | 0.53 | 0.48 | 01-JUL-07:19 | 920.83 | 12.55 | 0.00 | 328.67 | 521.03 | 15.90 | 0.00 | 283.50 |
August | 369.33 | 0.52 | 0.48 | 01-AUG-07:10 | 1088.10 | 13.67 | 0.00 | 331.67 | 619.10 | 17.02 | 0.00 | 290.17 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-06:00 | 1221.04 | 13.34 | 0.00 | 315.00 | 667.81 | 16.63 | 0.00 | 280.50 |
October | 356.83 | 0.51 | 0.48 | 01-OCT-06:40 | 1568.10 | 14.66 | 15.00 | 325.00 | 828.33 | 17.54 | 4.50 | 290.17 |
November | 337.67 | 0.50 | 0.48 | 01-NOV-07:10 | 1970.68 | 20.21 | 114.17 | 313.67 | 1006.55 | 19.55 | 39.83 | 288.67 |
December | 349.33 | 0.51 | 0.48 | 01-DEC-06:40 | 2281.42 | 22.16 | 148.50 | 320.83 | 1156.17 | 21.74 | 87.50 | 305.67 |
Annual Sum or Average | 4292.33 | 0.52 | 1450.17 | 15.66 | 425.00 | 3863.50 | 788.36 | 18.08 | 220.33 | 3495.33 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 920.83 | 12.55 | 0.00 | 294.50 | 521.03 | 15.90 | 0.00 | 276.00 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 2281.42 | 22.16 | 148.50 | 332.17 | 1158.08 | 21.86 | 88.50 | 312.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.52 | 0.48 | 01-JAN-07:19 | 1938.85 | 21.00 | 108.50 | 312.67 | 1033.21 | 21.86 | 77.50 | 279.67 |
February | 321.17 | 0.52 | 0.48 | 01-FEB-06:40 | 2165.89 | 21.10 | 99.00 | 289.17 | 1149.45 | 21.95 | 71.17 | 264.50 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-07:10 | 2416.52 | 21.12 | 112.17 | 325.33 | 1041.04 | 20.48 | 52.17 | 301.17 |
April | 358.33 | 0.51 | 0.48 | 01-APR-06:10 | 1998.58 | 19.25 | 84.17 | 330.00 | 1091.83 | 21.20 | 60.50 | 303.33 |
May | 376.33 | 0.51 | 0.48 | 01-MAY-05:00 | 1755.40 | 19.51 | 98.00 | 340.83 | 924.29 | 20.68 | 67.33 | 307.00 |
June | 370.50 | 0.51 | 0.48 | 01-JUN-06:49 | 1890.18 | 19.75 | 92.67 | 336.33 | 997.33 | 20.98 | 63.17 | 307.17 |
July | 383.17 | 0.52 | 0.48 | 01-JUL-06:19 | 1557.22 | 18.17 | 86.67 | 338.33 | 812.05 | 20.25 | 64.67 | 301.17 |
August | 369.33 | 0.51 | 0.48 | 01-AUG-05:00 | 1761.51 | 18.83 | 86.00 | 338.50 | 939.20 | 20.70 | 60.33 | 307.50 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-06:10 | 1644.81 | 18.25 | 83.67 | 316.67 | 875.74 | 20.17 | 60.67 | 282.33 |
October | 356.83 | 0.52 | 0.48 | 01-OCT-05:00 | 1667.55 | 18.79 | 86.17 | 319.50 | 871.18 | 20.52 | 60.50 | 285.17 |
November | 337.67 | 0.52 | 0.48 | 01-NOV-06:40 | 1679.93 | 19.47 | 84.50 | 300.17 | 857.76 | 20.28 | 51.33 | 267.33 |
December | 349.33 | 0.53 | 0.48 | 01-DEC-06:40 | 1880.23 | 21.08 | 112.50 | 304.50 | 882.97 | 20.69 | 56.00 | 273.83 |
Annual Sum or Average | 4292.33 | 0.52 | 1859.20 | 19.67 | 1134.00 | 3852.00 | 954.36 | 20.80 | 745.33 | 3480.17 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 1557.22 | 18.17 | 83.67 | 289.17 | 812.05 | 20.17 | 51.33 | 264.50 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 2416.52 | 21.12 | 112.50 | 340.83 | 1149.45 | 21.95 | 77.50 | 307.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.54 | 0.48 | 01-JAN-08:30 | 784.84 | 12.61 | 0.00 | 300.83 | 481.08 | 16.03 | 0.00 | 253.17 |
February | 321.17 | 0.53 | 0.48 | 01-FEB-07:49 | 865.19 | 13.21 | 0.00 | 281.17 | 532.09 | 16.61 | 0.00 | 248.17 |
March | 361.17 | 0.52 | 0.48 | 01-MAR-08:09 | 988.17 | 14.16 | 0.00 | 325.17 | 606.18 | 17.57 | 0.00 | 295.50 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:49 | 1199.01 | 14.90 | 0.00 | 334.50 | 702.91 | 18.37 | 0.00 | 307.17 |
May | 376.33 | 0.50 | 0.48 | 01-MAY-06:19 | 1376.19 | 14.19 | 3.83 | 350.33 | 748.46 | 17.52 | 1.17 | 321.00 |
June | 370.50 | 0.50 | 0.48 | 01-JUN-07:19 | 1644.95 | 19.87 | 112.17 | 349.00 | 868.23 | 19.59 | 33.17 | 328.50 |
July | 383.17 | 0.51 | 0.48 | 01-JUL-06:40 | 1418.50 | 19.30 | 115.50 | 352.50 | 738.52 | 19.83 | 59.17 | 323.33 |
August | 369.33 | 0.50 | 0.48 | 01-AUG-06:19 | 1281.18 | 14.27 | 0.00 | 344.17 | 711.99 | 17.68 | 0.00 | 313.00 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-06:49 | 1043.17 | 13.20 | 0.00 | 315.67 | 586.59 | 16.49 | 0.00 | 280.67 |
October | 356.83 | 0.53 | 0.48 | 01-OCT-07:40 | 924.57 | 12.99 | 0.00 | 312.17 | 527.92 | 16.33 | 0.00 | 268.33 |
November | 337.67 | 0.53 | 0.48 | 01-NOV-07:40 | 830.54 | 12.72 | 0.00 | 290.50 | 486.22 | 16.09 | 0.00 | 244.33 |
December | 349.33 | 0.54 | 0.48 | 01-DEC-07:30 | 762.63 | 12.29 | 0.00 | 294.50 | 462.03 | 15.68 | 0.00 | 244.17 |
Annual Sum or Average | 4292.33 | 0.52 | 1102.84 | 14.55 | 231.50 | 3850.50 | 625.19 | 17.36 | 93.50 | 3427.33 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 762.63 | 12.29 | 0.00 | 281.17 | 462.03 | 15.68 | 0.00 | 244.17 | |
Maximum of Months | 383.17 | 0.54 | 0.48 | 1644.95 | 19.87 | 115.50 | 352.50 | 868.23 | 19.83 | 59.17 | 328.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.52 | 0.48 | 01-JAN-08:00 | 2000.00 | 21.21 | 109.33 | 311.50 | 1062.40 | 22.02 | 77.50 | 281.33 |
February | 321.17 | 0.52 | 0.48 | 01-FEB-08:09 | 2248.65 | 21.12 | 102.33 | 285.67 | 967.67 | 20.36 | 46.67 | 260.67 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-08:30 | 2470.45 | 20.89 | 112.67 | 333.33 | 1058.99 | 20.19 | 50.67 | 306.00 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:30 | 2386.25 | 14.20 | 0.00 | 329.83 | 1047.62 | 17.65 | 0.00 | 302.33 |
May | 376.33 | 0.52 | 0.48 | 01-MAY-07:19 | 1937.40 | 13.97 | 0.00 | 339.50 | 881.73 | 17.16 | 0.00 | 305.00 |
June | 370.50 | 0.51 | 0.48 | 01-JUN-08:09 | 2154.11 | 14.42 | 0.00 | 335.33 | 965.97 | 17.71 | 0.00 | 306.33 |
July | 383.17 | 0.52 | 0.48 | 01-JUL-07:49 | 1570.25 | 13.76 | 0.00 | 338.50 | 811.70 | 16.86 | 0.00 | 301.83 |
August | 369.33 | 0.51 | 0.48 | 01-AUG-07:30 | 2008.81 | 14.59 | 8.50 | 336.17 | 915.44 | 17.35 | 0.00 | 305.17 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-07:30 | 1802.13 | 18.06 | 87.00 | 312.33 | 846.76 | 17.13 | 7.67 | 283.00 |
October | 356.83 | 0.52 | 0.48 | 01-OCT-08:09 | 1738.69 | 20.18 | 103.33 | 317.17 | 909.38 | 21.21 | 72.67 | 285.50 |
November | 337.67 | 0.52 | 0.48 | 01-NOV-08:09 | 1727.76 | 20.42 | 95.83 | 303.00 | 901.88 | 21.38 | 66.00 | 270.83 |
December | 349.33 | 0.53 | 0.48 | 01-DEC-07:49 | 1792.63 | 20.62 | 102.83 | 309.00 | 955.92 | 21.49 | 71.83 | 277.83 |
Annual Sum or Average | 4292.33 | 0.52 | 1984.13 | 17.68 | 721.83 | 3851.33 | 942.61 | 19.15 | 393.00 | 3485.83 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 1570.25 | 13.76 | 0.00 | 285.67 | 811.70 | 16.86 | 0.00 | 260.67 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 2470.45 | 21.21 | 112.67 | 339.50 | 1062.40 | 22.02 | 77.50 | 306.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.51 | 0.48 | 01-JAN-07:49 | 2278.63 | 22.09 | 147.33 | 323.83 | 1159.99 | 21.85 | 88.50 | 312.83 |
February | 321.17 | 0.51 | 0.48 | 01-FEB-07:10 | 1814.31 | 14.28 | 0.00 | 294.50 | 990.58 | 17.85 | 0.00 | 276.17 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-07:49 | 1386.99 | 14.62 | 0.00 | 327.50 | 799.49 | 18.06 | 0.00 | 303.50 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:10 | 1144.13 | 14.44 | 0.00 | 325.50 | 674.08 | 17.88 | 0.00 | 292.50 |
May | 376.33 | 0.52 | 0.48 | 01-MAY-06:00 | 976.87 | 13.12 | 0.00 | 332.17 | 565.55 | 16.48 | 0.00 | 288.00 |
June | 370.50 | 0.52 | 0.48 | 01-JUN-07:49 | 957.85 | 13.46 | 0.00 | 325.17 | 571.92 | 16.90 | 0.00 | 284.17 |
July | 383.17 | 0.53 | 0.48 | 01-JUL-07:19 | 922.26 | 12.52 | 0.00 | 328.67 | 521.88 | 15.88 | 0.00 | 283.83 |
August | 369.33 | 0.52 | 0.48 | 01-AUG-07:10 | 1089.72 | 13.64 | 0.00 | 331.83 | 620.09 | 17.00 | 0.00 | 290.17 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-06:00 | 1223.07 | 13.31 | 0.00 | 315.00 | 668.97 | 16.61 | 0.00 | 280.67 |
October | 356.83 | 0.51 | 0.48 | 01-OCT-06:40 | 1570.84 | 14.64 | 15.00 | 325.17 | 829.87 | 17.52 | 4.50 | 290.33 |
November | 337.67 | 0.50 | 0.48 | 01-NOV-07:10 | 1973.87 | 20.19 | 114.17 | 313.67 | 1008.43 | 19.54 | 39.83 | 288.67 |
December | 349.33 | 0.51 | 0.48 | 01-DEC-06:40 | 2284.55 | 22.14 | 148.50 | 320.83 | 1158.13 | 21.73 | 87.50 | 305.83 |
Annual Sum or Average | 4292.33 | 0.52 | 1452.30 | 15.63 | 425.00 | 3863.83 | 789.67 | 18.06 | 220.33 | 3496.67 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 922.26 | 12.52 | 0.00 | 294.50 | 521.88 | 15.88 | 0.00 | 276.17 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 2284.55 | 22.14 | 148.50 | 332.17 | 1159.99 | 21.85 | 88.50 | 312.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.52 | 0.48 | 01-JAN-07:19 | 1940.50 | 20.97 | 108.50 | 312.67 | 1034.55 | 21.85 | 77.50 | 280.00 |
February | 321.17 | 0.52 | 0.48 | 01-FEB-06:40 | 2167.75 | 21.07 | 99.00 | 289.33 | 1150.84 | 21.94 | 71.17 | 264.67 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-07:10 | 2418.30 | 21.09 | 112.17 | 325.33 | 1042.46 | 20.47 | 52.17 | 301.83 |
April | 358.33 | 0.51 | 0.48 | 01-APR-06:10 | 2000.41 | 19.22 | 84.17 | 330.00 | 1093.25 | 21.18 | 60.50 | 303.33 |
May | 376.33 | 0.51 | 0.48 | 01-MAY-05:00 | 1757.39 | 19.49 | 98.00 | 341.00 | 925.63 | 20.67 | 67.33 | 307.00 |
June | 370.50 | 0.51 | 0.48 | 01-JUN-06:49 | 1892.18 | 19.73 | 92.67 | 336.33 | 998.75 | 20.97 | 63.17 | 307.17 |
July | 383.17 | 0.52 | 0.48 | 01-JUL-06:19 | 1559.33 | 18.15 | 86.67 | 338.33 | 813.35 | 20.23 | 64.67 | 301.17 |
August | 369.33 | 0.51 | 0.48 | 01-AUG-05:00 | 1763.64 | 18.81 | 86.00 | 338.50 | 940.62 | 20.69 | 60.33 | 307.67 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-06:10 | 1646.90 | 18.22 | 83.67 | 316.67 | 877.10 | 20.16 | 60.67 | 282.33 |
October | 356.83 | 0.52 | 0.48 | 01-OCT-05:00 | 1669.71 | 18.77 | 86.17 | 319.33 | 872.56 | 20.51 | 60.50 | 285.33 |
November | 337.67 | 0.52 | 0.48 | 01-NOV-06:40 | 1681.88 | 19.44 | 84.50 | 300.17 | 859.14 | 20.27 | 51.33 | 267.67 |
December | 349.33 | 0.53 | 0.48 | 01-DEC-06:40 | 1881.90 | 21.06 | 112.50 | 304.50 | 884.27 | 20.68 | 56.00 | 274.00 |
Annual Sum or Average | 4292.33 | 0.52 | 1861.14 | 19.64 | 1134.00 | 3852.17 | 955.73 | 20.79 | 745.33 | 3482.17 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 1559.33 | 18.15 | 83.67 | 289.33 | 813.35 | 20.16 | 51.33 | 264.67 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 2418.30 | 21.09 | 112.50 | 341.00 | 1150.84 | 21.94 | 77.50 | 307.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.54 | 0.48 | 01-JAN-08:30 | 785.68 | 12.58 | 0.00 | 300.83 | 481.74 | 16.01 | 0.00 | 253.33 |
February | 321.17 | 0.53 | 0.48 | 01-FEB-07:49 | 866.11 | 13.17 | 0.00 | 281.17 | 532.81 | 16.60 | 0.00 | 248.33 |
March | 361.17 | 0.52 | 0.48 | 01-MAR-08:09 | 989.23 | 14.13 | 0.00 | 325.17 | 607.00 | 17.55 | 0.00 | 295.67 |
April | 358.33 | 0.50 | 0.48 | 01-APR-06:49 | 1200.55 | 14.87 | 0.00 | 334.50 | 703.97 | 18.35 | 0.00 | 307.17 |
May | 376.33 | 0.50 | 0.48 | 01-MAY-06:19 | 1378.34 | 14.16 | 3.83 | 350.33 | 749.73 | 17.51 | 1.17 | 321.17 |
June | 370.50 | 0.50 | 0.48 | 01-JUN-07:19 | 1647.32 | 19.85 | 112.17 | 349.00 | 869.68 | 19.57 | 33.17 | 328.50 |
July | 383.17 | 0.51 | 0.48 | 01-JUL-06:40 | 1420.86 | 19.28 | 115.50 | 352.67 | 739.85 | 19.82 | 59.17 | 323.33 |
August | 369.33 | 0.50 | 0.48 | 01-AUG-06:19 | 1283.18 | 14.24 | 0.00 | 344.17 | 713.19 | 17.67 | 0.00 | 313.00 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-06:49 | 1044.76 | 13.18 | 0.00 | 315.67 | 587.56 | 16.48 | 0.00 | 281.00 |
October | 356.83 | 0.53 | 0.48 | 01-OCT-07:40 | 925.91 | 12.96 | 0.00 | 312.33 | 528.77 | 16.31 | 0.00 | 268.67 |
November | 337.67 | 0.53 | 0.48 | 01-NOV-07:40 | 831.63 | 12.69 | 0.00 | 290.50 | 486.98 | 16.07 | 0.00 | 245.00 |
December | 349.33 | 0.54 | 0.48 | 01-DEC-07:30 | 763.49 | 12.26 | 0.00 | 294.50 | 462.69 | 15.67 | 0.00 | 244.33 |
Annual Sum or Average | 4292.33 | 0.52 | 1104.37 | 14.52 | 231.50 | 3850.83 | 626.18 | 17.34 | 93.50 | 3429.50 | ||
Minimum of Months | 321.17 | 0.50 | 0.48 | 763.49 | 12.26 | 0.00 | 281.17 | 462.69 | 15.67 | 0.00 | 244.33 | |
Maximum of Months | 383.17 | 0.54 | 0.48 | 1647.32 | 19.85 | 115.50 | 352.67 | 869.68 | 19.82 | 59.17 | 328.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 350.67 | 0.52 | 0.48 | 01-JAN-08:00 | 2001.64 | 21.18 | 109.33 | 311.50 | 1063.72 | 22.01 | 77.50 | 281.50 |
February | 321.17 | 0.52 | 0.48 | 01-FEB-08:09 | 2250.49 | 21.09 | 102.33 | 285.67 | 969.05 | 20.35 | 46.67 | 260.67 |
March | 361.17 | 0.51 | 0.48 | 01-MAR-08:30 | 2472.21 | 20.87 | 112.67 | 333.33 | 1060.40 | 20.18 | 50.67 | 306.17 |
April | 358.33 | 0.51 | 0.48 | 01-APR-07:30 | 2388.08 | 14.17 | 0.00 | 329.83 | 1049.05 | 17.63 | 0.00 | 302.33 |
May | 376.33 | 0.52 | 0.48 | 01-MAY-07:19 | 1939.47 | 13.94 | 0.00 | 339.50 | 883.08 | 17.14 | 0.00 | 305.00 |
June | 370.50 | 0.51 | 0.48 | 01-JUN-08:09 | 2156.06 | 14.39 | 0.00 | 335.33 | 967.36 | 17.69 | 0.00 | 306.67 |
July | 383.17 | 0.52 | 0.48 | 01-JUL-07:49 | 1572.33 | 13.73 | 0.00 | 338.50 | 812.99 | 16.84 | 0.00 | 301.83 |
August | 369.33 | 0.51 | 0.48 | 01-AUG-07:30 | 2010.91 | 14.56 | 8.50 | 336.17 | 916.85 | 17.33 | 0.00 | 305.33 |
September | 357.83 | 0.53 | 0.48 | 01-SEP-07:30 | 1804.20 | 18.03 | 87.00 | 312.33 | 848.09 | 17.12 | 7.67 | 283.17 |
October | 356.83 | 0.52 | 0.48 | 01-OCT-08:09 | 1740.82 | 20.15 | 103.33 | 317.17 | 910.77 | 21.20 | 72.67 | 285.50 |
November | 337.67 | 0.52 | 0.48 | 01-NOV-08:09 | 1729.68 | 20.40 | 95.83 | 303.00 | 903.26 | 21.37 | 66.00 | 271.00 |
December | 349.33 | 0.53 | 0.48 | 01-DEC-07:49 | 1794.25 | 20.60 | 102.83 | 309.00 | 957.21 | 21.48 | 71.83 | 277.83 |
Annual Sum or Average | 4292.33 | 0.52 | 1986.05 | 17.65 | 721.83 | 3851.33 | 943.97 | 19.13 | 393.00 | 3487.00 | ||
Minimum of Months | 321.17 | 0.51 | 0.48 | 1572.33 | 13.73 | 0.00 | 285.67 | 812.99 | 16.84 | 0.00 | 260.67 | |
Maximum of Months | 383.17 | 0.53 | 0.48 | 2472.21 | 21.18 | 112.67 | 339.50 | 1063.72 | 22.01 | 77.50 | 306.67 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.221479E+12 | 0.171902E+12 | 228378.83 | 03-JAN-06:02 | 172027.60 | 0.75 |
February | 0.00 | 0.00 | 0.221207E+12 | 0.173476E+12 | 229497.96 | 21-FEB-06:02 | 180125.09 | 0.81 |
March | 0.00 | 0.00 | 0.278285E+12 | 0.219481E+12 | 254266.46 | 27-MAR-05:03 | 182938.49 | 0.87 |
April | 0.00 | 0.00 | 0.275314E+12 | 0.214541E+12 | 242149.85 | 24-APR-05:03 | 176906.44 | 0.88 |
May | 0.00 | 0.00 | 0.278418E+12 | 0.203373E+12 | 258339.63 | 13-MAY-05:02 | 174976.29 | 0.82 |
June | 0.00 | 0.00 | 0.288901E+12 | 0.212463E+12 | 262126.23 | 12-JUN-05:02 | 181561.30 | 0.85 |
July | 0.00 | 0.00 | 0.277108E+12 | 0.204068E+12 | 243472.94 | 10-JUL-05:02 | 179241.07 | 0.85 |
August | 0.00 | 0.00 | 0.307076E+12 | 0.220248E+12 | 259677.05 | 14-AUG-05:02 | 180918.49 | 0.87 |
September | 0.00 | 0.00 | 0.256164E+12 | 0.183453E+12 | 256567.29 | 30-SEP-05:02 | 176517.22 | 0.80 |
October | 0.00 | 0.00 | 0.266280E+12 | 0.188969E+12 | 252194.64 | 05-OCT-05:02 | 176615.92 | 0.80 |
November | 0.00 | 0.00 | 0.262212E+12 | 0.193339E+12 | 248868.46 | 13-NOV-06:02 | 179528.30 | 0.82 |
December | 0.00 | 0.00 | 0.252968E+12 | 0.189640E+12 | 232212.45 | 11-DEC-06:03 | 171338.30 | 0.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.318541E+13 | 0.237495E+13 | 0.83 | |||
Minimum of Months | 0.00 | 0.00 | 0.221207E+12 | 0.171902E+12 | 228378.83 | 171338.30 | 0.75 | |
Maximum of Months | 0.00 | 0.00 | 0.307076E+12 | 0.220248E+12 | 262126.23 | 182938.49 | 0.88 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.154828E+13 | 0.115836E+13 | 2096738.26 | 02-JAN-05:12 | 1470916.50 | 0.64 |
February | 0.00 | 0.00 | 0.147968E+13 | 0.111280E+13 | 2085828.29 | 13-FEB-05:02 | 1488488.21 | 0.67 |
March | 0.00 | 0.00 | 0.176258E+13 | 0.131059E+13 | 2022368.65 | 15-MAR-04:12 | 1403750.05 | 0.73 |
April | 0.00 | 0.00 | 0.177370E+13 | 0.125185E+13 | 1917980.46 | 21-APR-05:02 | 1479186.01 | 0.75 |
May | 0.00 | 0.00 | 0.193809E+13 | 0.128786E+13 | 2146205.95 | 22-MAY-03:02 | 1405718.49 | 0.72 |
June | 0.00 | 0.00 | 0.197363E+13 | 0.132092E+13 | 2209405.10 | 02-JUN-03:02 | 1455103.67 | 0.73 |
July | 0.00 | 0.00 | 0.167992E+13 | 0.115192E+13 | 2105310.08 | 27-JUL-03:02 | 1435891.10 | 0.68 |
August | 0.00 | 0.00 | 0.183034E+13 | 0.120162E+13 | 2274952.02 | 26-AUG-05:03 | 1434862.74 | 0.69 |
September | 0.00 | 0.00 | 0.169506E+13 | 0.112222E+13 | 2098778.08 | 07-SEP-03:02 | 1455786.87 | 0.68 |
October | 0.00 | 0.00 | 0.166758E+13 | 0.110064E+13 | 2304010.64 | 23-OCT-05:02 | 1447360.07 | 0.65 |
November | 0.00 | 0.00 | 0.159413E+13 | 0.110856E+13 | 2079389.44 | 08-NOV-04:02 | 1480510.46 | 0.64 |
December | 0.00 | 0.00 | 0.152234E+13 | 0.110880E+13 | 2080579.11 | 11-DEC-05:12 | 1459293.20 | 0.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.204653E+14 | 0.142361E+14 | 0.68 | |||
Minimum of Months | 0.00 | 0.00 | 0.147968E+13 | 0.110064E+13 | 1917980.46 | 1403750.05 | 0.63 | |
Maximum of Months | 0.00 | 0.00 | 0.197363E+13 | 0.132092E+13 | 2304010.64 | 1488488.21 | 0.75 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.162432E+12 | 0.123749E+12 | 217674.90 | 02-JAN-05:12 | 152281.99 | 0.64 |
February | 0.00 | 0.00 | 0.156623E+12 | 0.120586E+12 | 218891.57 | 13-FEB-05:02 | 153544.29 | 0.67 |
March | 0.00 | 0.00 | 0.189574E+12 | 0.144386E+12 | 214702.27 | 01-MAR-04:02 | 148277.52 | 0.73 |
April | 0.00 | 0.00 | 0.192250E+12 | 0.139652E+12 | 215864.86 | 14-APR-03:02 | 164697.58 | 0.75 |
May | 0.00 | 0.00 | 0.208681E+12 | 0.142707E+12 | 232161.77 | 19-MAY-03:02 | 163049.04 | 0.72 |
June | 0.00 | 0.00 | 0.212414E+12 | 0.146200E+12 | 233572.78 | 02-JUN-03:02 | 155394.23 | 0.74 |
July | 0.00 | 0.00 | 0.179358E+12 | 0.126024E+12 | 230679.88 | 27-JUL-03:02 | 162114.92 | 0.68 |
August | 0.00 | 0.00 | 0.194129E+12 | 0.130892E+12 | 247004.50 | 26-AUG-05:03 | 152288.39 | 0.69 |
September | 0.00 | 0.00 | 0.181639E+12 | 0.123511E+12 | 242521.90 | 18-SEP-03:02 | 160762.51 | 0.69 |
October | 0.00 | 0.00 | 0.175362E+12 | 0.118615E+12 | 236739.11 | 23-OCT-05:02 | 148521.98 | 0.66 |
November | 0.00 | 0.00 | 0.167222E+12 | 0.118974E+12 | 215075.47 | 08-NOV-04:02 | 152496.27 | 0.64 |
December | 0.00 | 0.00 | 0.159173E+12 | 0.117945E+12 | 213882.73 | 11-DEC-05:12 | 149991.99 | 0.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.217886E+13 | 0.155324E+13 | 0.69 | |||
Minimum of Months | 0.00 | 0.00 | 0.156623E+12 | 0.117945E+12 | 213882.73 | 148277.52 | 0.62 | |
Maximum of Months | 0.00 | 0.00 | 0.212414E+12 | 0.146200E+12 | 247004.50 | 164697.58 | 0.75 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.288210E+11 | 0.222745E+11 | 276547.64 | 07-JAN-04:03 | 73250.34 | 0.10 |
February | 0.00 | 0.00 | 0.197648E+11 | 0.146699E+11 | 273259.19 | 12-FEB-06:43 | 71368.54 | 0.06 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.297165E+10 | 0.165935E+10 | 286037.81 | 14-APR-16:02 | 71102.69 | 0.01 |
May | 0.00 | 0.00 | 0.771089E+09 | 0.274114E+09 | 280557.99 | 10-MAY-20:02 | 72013.26 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.563726E+10 | 0.405685E+10 | 275505.70 | 25-NOV-04:43 | 71976.42 | 0.02 |
December | 0.00 | 0.00 | 0.304535E+11 | 0.203721E+11 | 281861.64 | 07-DEC-02:42 | 71035.63 | 0.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.884194E+11 | 0.633068E+11 | 0.02 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.304535E+11 | 0.222745E+11 | 286037.81 | 73250.34 | 0.10 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.376601E+12 | 0.355324E+12 | 149624.57 | 11-JAN-17:00 | 137262.97 | 0.00 |
February | 0.00 | 0.00 | 0.564031E+12 | 0.543436E+12 | 243121.41 | 13-FEB-16:43 | 229900.04 | 0.00 |
March | 0.00 | 0.00 | 0.874285E+12 | 0.849334E+12 | 415646.59 | 31-MAR-23:03 | 402410.47 | 0.00 |
April | 0.00 | 0.00 | 0.108915E+13 | 0.105971E+13 | 429667.92 | 10-APR-16:00 | 413409.91 | 0.00 |
May | 0.00 | 0.00 | 0.396025E+12 | 0.360601E+12 | 234692.31 | 31-MAY-23:03 | 217790.99 | 0.00 |
June | 0.00 | 0.00 | 0.621679E+12 | 0.585837E+12 | 325592.09 | 30-JUN-23:05 | 309828.26 | 0.00 |
July | 0.00 | 0.00 | 0.877711E+12 | 0.848878E+12 | 415906.30 | 31-JUL-23:03 | 401895.36 | 0.00 |
August | 0.00 | 0.00 | 0.112969E+13 | 0.109452E+13 | 431931.77 | 07-AUG-14:30 | 412085.89 | 0.00 |
September | 0.00 | 0.00 | 0.379226E+12 | 0.347577E+12 | 236529.38 | 30-SEP-23:02 | 218155.40 | 0.00 |
October | 0.00 | 0.00 | 0.634845E+12 | 0.602035E+12 | 323922.03 | 31-OCT-23:10 | 309552.04 | 0.00 |
November | 0.00 | 0.00 | 0.848201E+12 | 0.820039E+12 | 337108.66 | 14-NOV-16:20 | 320690.41 | 0.00 |
December | 0.00 | 0.00 | 0.111529E+13 | 0.109146E+13 | 426501.26 | 12-DEC-16:50 | 412514.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.890674E+13 | 0.855876E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.376601E+12 | 0.347577E+12 | 149624.57 | 137262.97 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.112969E+13 | 0.109452E+13 | 431931.77 | 413409.91 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.718984E+10 | 0.631271E+10 | 3211.45 | 16-JAN-17:40 | 2950.68 | 0.00 |
February | 0.00 | 0.00 | 0.112465E+11 | 0.103550E+11 | 5231.53 | 13-FEB-16:43 | 4675.97 | 0.00 |
March | 0.00 | 0.00 | 0.177538E+11 | 0.166448E+11 | 8522.97 | 31-MAR-23:03 | 7909.41 | 0.00 |
April | 0.00 | 0.00 | 0.223121E+11 | 0.209653E+11 | 9058.43 | 09-APR-16:00 | 8446.30 | 0.00 |
May | 0.00 | 0.00 | 0.804418E+10 | 0.655714E+10 | 4819.48 | 31-MAY-23:03 | 4054.59 | 0.00 |
June | 0.00 | 0.00 | 0.128112E+11 | 0.112485E+11 | 6622.68 | 30-JUN-23:05 | 5909.91 | 0.00 |
July | 0.00 | 0.00 | 0.178395E+11 | 0.165549E+11 | 8502.86 | 31-JUL-23:03 | 7849.55 | 0.00 |
August | 0.00 | 0.00 | 0.231321E+11 | 0.215260E+11 | 9208.15 | 07-AUG-15:00 | 8331.31 | 0.00 |
September | 0.00 | 0.00 | 0.755744E+10 | 0.623203E+10 | 4914.00 | 30-SEP-23:02 | 4103.57 | 0.00 |
October | 0.00 | 0.00 | 0.128488E+11 | 0.114243E+11 | 6586.41 | 31-OCT-23:10 | 5918.15 | 0.00 |
November | 0.00 | 0.00 | 0.172136E+11 | 0.159592E+11 | 7218.15 | 20-NOV-17:00 | 6657.85 | 0.00 |
December | 0.00 | 0.00 | 0.225319E+11 | 0.214393E+11 | 9016.49 | 25-DEC-18:05 | 8472.99 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.180481E+12 | 0.165219E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.718984E+10 | 0.623203E+10 | 3211.45 | 2950.68 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.231321E+11 | 0.215260E+11 | 9208.15 | 8472.99 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.655332E+11 | 0.569184E+11 | 29962.02 | 30-JAN-17:00 | 25414.63 | 0.00 |
February | 0.00 | 0.00 | 0.104981E+12 | 0.961274E+11 | 49127.26 | 13-FEB-16:43 | 43613.88 | 0.00 |
March | 0.00 | 0.00 | 0.166221E+12 | 0.155174E+12 | 80907.14 | 31-MAR-23:03 | 74701.42 | 0.00 |
April | 0.00 | 0.00 | 0.209723E+12 | 0.196255E+12 | 85850.26 | 20-APR-15:50 | 78465.94 | 0.00 |
May | 0.00 | 0.00 | 0.726833E+11 | 0.580938E+11 | 46406.69 | 31-MAY-23:03 | 38418.97 | 0.00 |
June | 0.00 | 0.00 | 0.119249E+12 | 0.103738E+12 | 62654.52 | 30-JUN-23:05 | 55333.93 | 0.00 |
July | 0.00 | 0.00 | 0.166798E+12 | 0.154004E+12 | 80926.47 | 31-JUL-23:03 | 74302.22 | 0.00 |
August | 0.00 | 0.00 | 0.218008E+12 | 0.201959E+12 | 87000.73 | 15-AUG-14:00 | 78054.38 | 0.00 |
September | 0.00 | 0.00 | 0.678573E+11 | 0.548773E+11 | 46313.65 | 30-SEP-23:02 | 37817.98 | 0.00 |
October | 0.00 | 0.00 | 0.119219E+12 | 0.105088E+12 | 62260.81 | 31-OCT-23:10 | 55400.69 | 0.00 |
November | 0.00 | 0.00 | 0.161473E+12 | 0.148975E+12 | 67871.22 | 20-NOV-17:00 | 62289.30 | 0.00 |
December | 0.00 | 0.00 | 0.212780E+12 | 0.201859E+12 | 85224.64 | 29-DEC-17:00 | 78969.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.168452E+13 | 0.153307E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.655332E+11 | 0.548773E+11 | 29962.02 | 25414.63 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.218008E+12 | 0.201959E+12 | 87000.73 | 78969.81 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.660352E+10 | 0.574182E+10 | 3082.04 | 30-JAN-17:00 | 2624.82 | 0.00 |
February | 0.00 | 0.00 | 0.105704E+11 | 0.968546E+10 | 5008.50 | 13-FEB-16:43 | 4456.24 | 0.00 |
March | 0.00 | 0.00 | 0.167481E+11 | 0.156440E+11 | 8111.08 | 31-MAR-23:03 | 7491.83 | 0.00 |
April | 0.00 | 0.00 | 0.211333E+11 | 0.197870E+11 | 8709.75 | 13-APR-15:10 | 7982.48 | 0.00 |
May | 0.00 | 0.00 | 0.742831E+10 | 0.596409E+10 | 4655.18 | 31-MAY-23:03 | 3860.42 | 0.00 |
June | 0.00 | 0.00 | 0.120619E+11 | 0.105099E+11 | 6195.13 | 30-JUN-23:05 | 5460.20 | 0.00 |
July | 0.00 | 0.00 | 0.167943E+11 | 0.155155E+11 | 8099.83 | 31-JUL-23:03 | 7438.49 | 0.00 |
August | 0.00 | 0.00 | 0.219047E+11 | 0.203005E+11 | 8822.90 | 15-AUG-14:00 | 7932.15 | 0.00 |
September | 0.00 | 0.00 | 0.691469E+10 | 0.561258E+10 | 4706.37 | 30-SEP-23:02 | 3866.16 | 0.00 |
October | 0.00 | 0.00 | 0.119948E+11 | 0.105821E+11 | 6213.90 | 31-OCT-23:10 | 5528.28 | 0.00 |
November | 0.00 | 0.00 | 0.162070E+11 | 0.149583E+11 | 6873.54 | 20-NOV-17:00 | 6315.62 | 0.00 |
December | 0.00 | 0.00 | 0.213192E+11 | 0.202284E+11 | 8611.21 | 10-DEC-17:05 | 8046.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.169680E+12 | 0.154530E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.660352E+10 | 0.561258E+10 | 3082.04 | 2624.82 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.219047E+11 | 0.203005E+11 | 8822.90 | 8046.62 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 757366.95 | 2862072.54 | 03-JAN-13:13 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 801676.69 | 2723043.30 | 13-FEB-11:13 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 853474.67 | 2534442.73 | 31-MAR-10:13 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 900034.59 | 2639548.34 | 17-APR-13:23 | 0.00 | 0.00 | 01-APR-00:03 |
May | 969436.96 | 2592652.25 | 01-MAY-12:33 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1014647.39 | 2689286.03 | 07-JUN-16:23 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 833399.53 | 2471434.48 | 26-JUL-14:33 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 920815.75 | 2776512.86 | 26-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 883782.44 | 2533838.86 | 29-SEP-11:13 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 834706.23 | 2881427.21 | 23-OCT-05:02 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 813994.77 | 2585614.75 | 29-NOV-13:13 | 0.00 | 0.00 | 01-NOV-00:03 |
December | 759194.85 | 2809968.18 | 28-DEC-14:02 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 861920.45 | 0.00 | ||||
Minimum of Months | 757366.95 | 2471434.48 | 0.00 | 0.00 | ||
Maximum of Months | 1014647.39 | 2881427.21 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 825253.87 | 3605649.70 | 02-JAN-05:12 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 888317.07 | 3570917.83 | 16-FEB-04:02 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 923800.41 | 3578866.10 | 15-MAR-04:12 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 1019900.37 | 3406976.34 | 25-APR-13:40 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1021860.02 | 3698812.11 | 22-MAY-03:02 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1049162.65 | 3695702.31 | 28-JUN-03:02 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 905312.09 | 3615707.43 | 28-JUL-03:02 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1045462.04 | 3665700.46 | 01-AUG-03:02 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 931411.57 | 3640199.03 | 07-SEP-03:02 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 875080.96 | 3637651.20 | 06-OCT-03:02 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 883002.34 | 3628520.01 | 13-NOV-04:02 | 0.00 | 0.00 | 01-NOV-00:03 |
December | 812737.21 | 3924407.62 | 08-DEC-05:12 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 931703.81 | 0.00 | ||||
Minimum of Months | 812737.21 | 3406976.34 | 0.00 | 0.00 | ||
Maximum of Months | 1049162.65 | 3924407.62 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 764037.37 | 1233222.75 | 04-JAN-13:10 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 1038380.89 | 1520129.37 | 28-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 1302621.04 | 1816191.93 | 21-MAR-13:10 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 1571006.23 | 1977863.16 | 01-APR-14:00 | 0.00 | 0.00 | 01-APR-00:03 |
May | 934758.94 | 1437836.07 | 06-MAY-13:00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1137975.29 | 1602220.89 | 13-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1237619.53 | 1619698.62 | 21-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1471898.03 | 1900458.01 | 10-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 845493.20 | 1244005.32 | 06-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 1010322.72 | 1401821.55 | 04-OCT-14:00 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 1201675.19 | 1664486.85 | 18-NOV-13:00 | 0.00 | 0.00 | 01-NOV-00:03 |
December | 1358853.59 | 1824976.71 | 08-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 1156829.07 | 0.00 | ||||
Minimum of Months | 764037.37 | 1233222.75 | 0.00 | 0.00 | ||
Maximum of Months | 1571006.23 | 1977863.16 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 8918.11 | 31666.38 | 12-JAN-12:55 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 8916.97 | 31592.27 | 01-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 9333.59 | 31251.63 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:03 | 8556.25 | 30599.98 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 8656.53 | 29979.62 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 8741.08 | 29399.46 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 7996.78 | 29116.65 | 31-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 8822.49 | 29482.57 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 8404.01 | 30049.67 | 29-SEP-11:13 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 8573.79 | 30757.38 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 8875.77 | 31318.75 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 8669.19 | 31626.07 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 8704.31 | ||||
Minimum of Months | 0.00 | 0.00 | 7996.78 | 29116.65 | ||
Maximum of Months | 0.00 | 0.00 | 9333.59 | 31666.38 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1770983.60 | 7360502.99 | 12-JAN-14:53 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 1987750.08 | 8110467.41 | 14-FEB-15:53 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 2321977.26 | 7789676.71 | 23-MAR-14:23 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 2959013.64 | 8449004.36 | 17-APR-14:43 | 0.00 | 0.00 | 01-APR-00:03 |
May | 3416039.77 | 8487884.61 | 09-MAY-15:43 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 3607102.32 | 8316566.72 | 09-JUN-12:03 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 2437641.55 | 8011687.34 | 26-JUL-14:33 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 3129790.44 | 8181602.55 | 02-AUG-13:35 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 2946943.06 | 7960281.65 | 05-SEP-10:35 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 2679210.75 | 8369240.35 | 06-OCT-14:03 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 2375538.21 | 7877080.54 | 15-NOV-15:23 | 0.00 | 0.00 | 01-NOV-00:03 |
December | 1904023.64 | 7108393.72 | 12-DEC-13:03 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 2629492.05 | 0.00 | ||||
Minimum of Months | 1770983.60 | 7108393.72 | 0.00 | 0.00 | ||
Maximum of Months | 3607102.32 | 8487884.61 | 0.00 | 0.00 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.112091E+11 | 0.59 | 20869.85 | 04-JAN-06:02 | 1.76 |
February | 0.119798E+11 | 0.66 | 20869.85 | 02-FEB-06:03 | 1.76 |
March | 0.162638E+11 | 0.76 | 20869.85 | 01-MAR-06:02 | 1.76 |
April | 0.167704E+11 | 0.78 | 20869.85 | 03-APR-03:02 | 1.76 |
May | 0.139603E+11 | 0.68 | 20869.85 | 01-MAY-04:22 | 1.76 |
June | 0.151606E+11 | 0.74 | 20869.85 | 01-JUN-04:12 | 1.76 |
July | 0.147566E+11 | 0.71 | 20869.85 | 01-JUL-05:02 | 1.76 |
August | 0.176234E+11 | 0.79 | 20869.85 | 01-AUG-04:12 | 1.76 |
September | 0.122839E+11 | 0.64 | 20869.85 | 01-SEP-09:30 | 1.76 |
October | 0.127071E+11 | 0.64 | 20869.85 | 04-OCT-12:05 | 1.76 |
November | 0.140691E+11 | 0.70 | 20869.85 | 01-NOV-03:02 | 1.76 |
December | 0.131614E+11 | 0.67 | 20869.85 | 01-DEC-05:52 | 1.76 |
Annual Sum or Average | 0.169946E+12 | 0.70 | |||
Minimum of Months | 0.112091E+11 | 0.59 | 20869.85 | 1.76 | |
Maximum of Months | 0.176234E+11 | 0.79 | 20869.85 | 1.76 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.603009E+11 | 0.41 | 195144.49 | 04-JAN-04:02 | 1.76 |
February | 0.581051E+11 | 0.44 | 195144.49 | 04-FEB-06:02 | 1.76 |
March | 0.650907E+11 | 0.46 | 195144.49 | 02-MAR-05:12 | 1.76 |
April | 0.594003E+11 | 0.45 | 195144.49 | 21-APR-05:02 | 1.76 |
May | 0.628163E+11 | 0.45 | 195144.49 | 09-MAY-05:02 | 1.76 |
June | 0.663210E+11 | 0.47 | 195144.49 | 02-JUN-03:02 | 1.76 |
July | 0.558821E+11 | 0.41 | 195144.49 | 08-JUL-05:03 | 1.76 |
August | 0.588798E+11 | 0.43 | 195144.49 | 05-AUG-05:02 | 1.76 |
September | 0.540190E+11 | 0.41 | 195144.49 | 15-SEP-05:02 | 1.76 |
October | 0.536527E+11 | 0.40 | 195144.49 | 06-OCT-03:02 | 1.76 |
November | 0.563220E+11 | 0.41 | 195144.49 | 02-NOV-05:03 | 1.76 |
December | 0.570016E+11 | 0.40 | 195144.49 | 01-DEC-06:02 | 1.76 |
Annual Sum or Average | 0.707792E+12 | 0.43 | |||
Minimum of Months | 0.536527E+11 | 0.40 | 195144.49 | 1.76 | |
Maximum of Months | 0.663210E+11 | 0.47 | 195144.49 | 1.76 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.631241E+10 | 0.41 | 20785.62 | 02-JAN-05:12 | 1.76 |
February | 0.625871E+10 | 0.44 | 20785.62 | 04-FEB-06:02 | 1.76 |
March | 0.720842E+10 | 0.47 | 20785.62 | 07-MAR-06:02 | 1.76 |
April | 0.672424E+10 | 0.47 | 20785.62 | 12-APR-13:30 | 1.75 |
May | 0.694231E+10 | 0.46 | 20785.62 | 03-MAY-03:02 | 1.76 |
June | 0.729166E+10 | 0.48 | 20785.62 | 10-JUN-05:03 | 1.76 |
July | 0.603508E+10 | 0.42 | 20785.62 | 18-JUL-05:02 | 1.76 |
August | 0.639441E+10 | 0.43 | 20785.62 | 03-AUG-03:02 | 1.76 |
September | 0.589992E+10 | 0.42 | 20785.62 | 02-SEP-03:02 | 1.76 |
October | 0.564293E+10 | 0.40 | 20785.62 | 06-OCT-03:02 | 1.76 |
November | 0.592361E+10 | 0.41 | 20785.62 | 13-NOV-04:02 | 1.76 |
December | 0.588777E+10 | 0.39 | 20785.62 | 04-DEC-05:12 | 1.76 |
Annual Sum or Average | 0.765215E+11 | 0.43 | |||
Minimum of Months | 0.564293E+10 | 0.39 | 20785.62 | 1.75 | |
Maximum of Months | 0.729166E+10 | 0.48 | 20785.62 | 1.76 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.333020E+10 | 0.18 | 12478.10 | 07-JAN-03:50 | 1.72 |
February | 0.195259E+10 | 0.11 | 12478.10 | 01-FEB-06:50 | 1.72 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 |
April | 0.232093E+09 | 0.01 | 12478.10 | 14-APR-16:00 | 1.71 |
May | 52408018.82 | 0.00 | 12478.10 | 10-MAY-20:00 | 1.71 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 |
November | 0.538945E+09 | 0.03 | 12478.10 | 25-NOV-04:43 | 1.75 |
December | 0.295102E+10 | 0.16 | 12478.10 | 01-DEC-02:53 | 1.75 |
Annual Sum or Average | 0.905725E+10 | 0.04 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.333020E+10 | 0.18 | 12478.10 | 1.75 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.108552E+12 | 1.34 | 40528.55 | 01-JAN-00:03 | 1.34 |
February | 0.980467E+11 | 1.34 | 40528.55 | 01-FEB-00:03 | 1.34 |
March | 0.108552E+12 | 1.34 | 40528.55 | 01-MAR-00:03 | 1.34 |
April | 0.105050E+12 | 1.34 | 40528.55 | 01-APR-00:03 | 1.34 |
May | 0.108552E+12 | 1.34 | 40528.55 | 01-MAY-00:03 | 1.34 |
June | 0.105050E+12 | 1.34 | 40528.55 | 01-JUN-00:03 | 1.34 |
July | 0.108552E+12 | 1.34 | 40528.55 | 01-JUL-00:03 | 1.34 |
August | 0.108552E+12 | 1.34 | 40528.55 | 01-AUG-00:03 | 1.34 |
September | 0.105050E+12 | 1.34 | 40528.55 | 01-SEP-00:05 | 1.34 |
October | 0.108552E+12 | 1.34 | 40528.55 | 01-OCT-00:03 | 1.34 |
November | 0.105050E+12 | 1.34 | 40528.55 | 01-NOV-00:03 | 1.34 |
December | 0.108552E+12 | 1.34 | 40528.55 | 01-DEC-00:03 | 1.34 |
Annual Sum or Average | 0.127811E+13 | 1.34 | |||
Minimum of Months | 0.980467E+11 | 1.34 | 40528.55 | 1.34 | |
Maximum of Months | 0.108552E+12 | 1.34 | 40528.55 | 1.34 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.141307E+10 | 0.91 | 527.58 | 01-JAN-00:03 | 0.91 |
February | 0.127632E+10 | 0.91 | 527.58 | 01-FEB-00:03 | 0.91 |
March | 0.141307E+10 | 0.91 | 527.58 | 01-MAR-00:03 | 0.91 |
April | 0.136749E+10 | 0.91 | 527.58 | 01-APR-00:03 | 0.91 |
May | 0.141307E+10 | 0.91 | 527.58 | 01-MAY-00:03 | 0.91 |
June | 0.136749E+10 | 0.91 | 527.58 | 01-JUN-00:03 | 0.91 |
July | 0.141307E+10 | 0.91 | 527.58 | 01-JUL-00:03 | 0.91 |
August | 0.141307E+10 | 0.91 | 527.58 | 01-AUG-00:03 | 0.91 |
September | 0.136749E+10 | 0.91 | 527.58 | 01-SEP-00:05 | 0.91 |
October | 0.141307E+10 | 0.91 | 527.58 | 01-OCT-00:03 | 0.91 |
November | 0.136749E+10 | 0.91 | 527.58 | 01-NOV-00:03 | 0.91 |
December | 0.141307E+10 | 0.91 | 527.58 | 01-DEC-00:03 | 0.91 |
Annual Sum or Average | 0.166377E+11 | 0.91 | |||
Minimum of Months | 0.127632E+10 | 0.91 | 527.58 | 0.91 | |
Maximum of Months | 0.141307E+10 | 0.91 | 527.58 | 0.91 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.134409E+11 | 0.91 | 5018.26 | 01-JAN-00:03 | 0.91 |
February | 0.121402E+11 | 0.91 | 5018.26 | 01-FEB-00:03 | 0.91 |
March | 0.134409E+11 | 0.91 | 5018.26 | 01-MAR-00:03 | 0.91 |
April | 0.130073E+11 | 0.91 | 5018.26 | 01-APR-00:03 | 0.91 |
May | 0.134409E+11 | 0.91 | 5018.26 | 01-MAY-00:03 | 0.91 |
June | 0.130073E+11 | 0.91 | 5018.26 | 01-JUN-00:03 | 0.91 |
July | 0.134409E+11 | 0.91 | 5018.26 | 01-JUL-00:03 | 0.91 |
August | 0.134409E+11 | 0.91 | 5018.26 | 01-AUG-00:03 | 0.91 |
September | 0.130073E+11 | 0.91 | 5018.26 | 01-SEP-00:05 | 0.91 |
October | 0.134409E+11 | 0.91 | 5018.26 | 01-OCT-00:03 | 0.91 |
November | 0.130073E+11 | 0.91 | 5018.26 | 01-NOV-00:03 | 0.91 |
December | 0.134409E+11 | 0.91 | 5018.26 | 01-DEC-00:03 | 0.91 |
Annual Sum or Average | 0.158256E+12 | 0.91 | |||
Minimum of Months | 0.121402E+11 | 0.91 | 5018.26 | 0.91 | |
Maximum of Months | 0.134409E+11 | 0.91 | 5018.26 | 0.91 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.136960E+10 | 0.91 | 511.35 | 01-JAN-00:03 | 0.91 |
February | 0.123706E+10 | 0.91 | 511.35 | 01-FEB-00:03 | 0.91 |
March | 0.136960E+10 | 0.91 | 511.35 | 01-MAR-00:03 | 0.91 |
April | 0.132542E+10 | 0.91 | 511.35 | 01-APR-00:03 | 0.91 |
May | 0.136960E+10 | 0.91 | 511.35 | 01-MAY-00:03 | 0.91 |
June | 0.132542E+10 | 0.91 | 511.35 | 01-JUN-00:03 | 0.91 |
July | 0.136960E+10 | 0.91 | 511.35 | 01-JUL-00:03 | 0.91 |
August | 0.136960E+10 | 0.91 | 511.35 | 01-AUG-00:03 | 0.91 |
September | 0.132542E+10 | 0.91 | 511.35 | 01-SEP-00:05 | 0.91 |
October | 0.136960E+10 | 0.91 | 511.35 | 01-OCT-00:03 | 0.91 |
November | 0.132542E+10 | 0.91 | 511.35 | 01-NOV-00:03 | 0.91 |
December | 0.136960E+10 | 0.91 | 511.35 | 01-DEC-00:03 | 0.91 |
Annual Sum or Average | 0.161259E+11 | 0.91 | |||
Minimum of Months | 0.123706E+10 | 0.91 | 511.35 | 0.91 | |
Maximum of Months | 0.136960E+10 | 0.91 | 511.35 | 0.91 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.341850E+10 | 0.307665E+10 | 15459.64 | 17-JAN-10:15 | 13913.67 | 13913.67 | 11.05 | 94.12 |
February | 0.363338E+10 | 0.327004E+10 | 15459.64 | 01-FEB-12:00 | 13913.67 | 13913.67 | 10.95 | 94.12 |
March | 0.373340E+10 | 0.336006E+10 | 13880.78 | 31-MAR-10:50 | 12492.70 | 12492.70 | 11.35 | 90.19 |
April | 0.488956E+10 | 0.440060E+10 | 13884.32 | 25-APR-13:40 | 12495.89 | 12495.89 | 12.19 | 90.19 |
May | 0.403924E+10 | 0.363532E+10 | 13884.93 | 08-MAY-10:10 | 12496.44 | 12496.44 | 12.33 | 90.19 |
June | 0.381738E+10 | 0.343564E+10 | 13884.51 | 09-JUN-08:40 | 12496.06 | 12496.06 | 12.23 | 90.19 |
July | 0.376412E+10 | 0.338771E+10 | 13884.37 | 28-JUL-13:20 | 12495.93 | 12495.93 | 12.20 | 90.19 |
August | 0.543278E+10 | 0.488950E+10 | 13885.00 | 15-AUG-11:30 | 12496.50 | 12496.50 | 12.35 | 90.19 |
September | 0.345241E+10 | 0.310717E+10 | 13884.28 | 07-SEP-13:10 | 12495.85 | 12495.85 | 12.18 | 90.19 |
October | 0.318151E+10 | 0.286336E+10 | 13884.26 | 05-OCT-12:30 | 12495.83 | 12495.83 | 12.17 | 90.19 |
November | 0.358255E+10 | 0.322429E+10 | 14946.71 | 25-NOV-06:04 | 13452.04 | 13452.04 | 10.32 | 92.86 |
December | 0.312818E+10 | 0.281536E+10 | 15459.64 | 14-DEC-10:00 | 13913.67 | 13913.67 | 10.93 | 94.12 |
Annual Sum or Average | 0.460730E+11 | 0.414657E+11 | ||||||
Minimum of Months | 0.312818E+10 | 0.281536E+10 | 13880.78 | 12492.70 | 12492.70 | 10.32 | 90.19 | |
Maximum of Months | 0.543278E+10 | 0.488950E+10 | 15459.64 | 13913.67 | 13913.67 | 12.35 | 94.12 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.111395E+11 | 0.100255E+11 | 5320.22 | 01-JAN-00:23 | 4788.20 | 4788.20 | 7.20 | 47.06 |
February | 0.108287E+11 | 0.974586E+10 | 5320.22 | 01-FEB-00:30 | 4788.20 | 4788.20 | 8.34 | 47.06 |
March | 0.130574E+11 | 0.117517E+11 | 5320.22 | 01-MAR-00:03 | 4788.20 | 4788.20 | 7.27 | 47.06 |
April | 0.129391E+11 | 0.116452E+11 | 5320.22 | 01-APR-00:03 | 4788.20 | 4788.20 | 9.35 | 47.06 |
May | 0.125881E+11 | 0.113293E+11 | 5320.22 | 01-MAY-00:03 | 4788.20 | 4788.20 | 11.12 | 47.06 |
June | 0.125551E+11 | 0.112996E+11 | 5320.22 | 01-JUN-00:40 | 4788.20 | 4788.20 | 7.18 | 47.06 |
July | 0.128569E+11 | 0.115712E+11 | 5320.22 | 01-JUL-01:02 | 4788.20 | 4788.20 | 7.38 | 47.06 |
August | 0.129411E+11 | 0.116470E+11 | 5320.22 | 01-AUG-00:15 | 4788.20 | 4788.20 | 7.23 | 47.06 |
September | 0.116005E+11 | 0.104404E+11 | 5320.22 | 01-SEP-00:05 | 4788.20 | 4788.20 | 7.10 | 47.06 |
October | 0.120432E+11 | 0.108389E+11 | 5320.22 | 01-OCT-00:30 | 4788.20 | 4788.20 | 8.56 | 47.06 |
November | 0.119528E+11 | 0.107575E+11 | 5320.22 | 01-NOV-00:42 | 4788.20 | 4788.20 | 7.29 | 47.06 |
December | 0.124051E+11 | 0.111646E+11 | 5320.22 | 01-DEC-00:13 | 4788.20 | 4788.20 | 7.18 | 47.06 |
Annual Sum or Average | 0.146908E+12 | 0.132217E+12 | ||||||
Minimum of Months | 0.108287E+11 | 0.974586E+10 | 5320.22 | 4788.20 | 4788.20 | 7.10 | 47.06 | |
Maximum of Months | 0.130574E+11 | 0.117517E+11 | 5320.22 | 4788.20 | 4788.20 | 11.12 | 47.06 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.555963E+09 | 0.500367E+09 | 5320.22 | 02-JAN-05:17 | 4788.20 | 4788.20 | 15.33 | 23.53 |
February | 0.738660E+09 | 0.664794E+09 | 5320.22 | 01-FEB-11:50 | 4788.20 | 4788.20 | 14.92 | 23.53 |
March | 0.650663E+09 | 0.585597E+09 | 5320.22 | 02-MAR-11:40 | 4788.20 | 4788.20 | 14.99 | 23.53 |
April | 0.106883E+10 | 0.961950E+09 | 5320.22 | 03-APR-08:50 | 4788.20 | 4788.20 | 15.33 | 23.53 |
May | 0.245316E+10 | 0.220784E+10 | 5320.22 | 01-MAY-07:50 | 4788.20 | 4788.20 | 14.80 | 23.53 |
June | 0.295858E+10 | 0.266272E+10 | 5320.22 | 01-JUN-08:30 | 4788.20 | 4788.20 | 15.35 | 23.53 |
July | 0.643747E+09 | 0.579372E+09 | 5320.22 | 03-JUL-09:20 | 4788.20 | 4788.20 | 15.33 | 23.53 |
August | 0.179717E+10 | 0.161745E+10 | 5320.22 | 01-AUG-08:70 | 4788.20 | 4788.20 | 15.15 | 23.53 |
September | 0.188230E+10 | 0.169407E+10 | 5320.22 | 01-SEP-08:00 | 4788.20 | 4788.20 | 15.38 | 23.53 |
October | 0.142082E+10 | 0.127874E+10 | 5320.22 | 02-OCT-08:50 | 4788.20 | 4788.20 | 15.31 | 23.53 |
November | 0.894010E+09 | 0.804609E+09 | 5320.22 | 01-NOV-11:20 | 4788.20 | 4788.20 | 15.32 | 23.53 |
December | 0.414445E+09 | 0.373001E+09 | 5320.22 | 01-DEC-09:10 | 4788.20 | 4788.20 | 15.23 | 23.53 |
Annual Sum or Average | 0.154783E+11 | 0.139305E+11 | ||||||
Minimum of Months | 0.414445E+09 | 0.373001E+09 | 5320.22 | 4788.20 | 4788.20 | 14.80 | 23.53 | |
Maximum of Months | 0.295858E+10 | 0.266272E+10 | 5320.22 | 4788.20 | 4788.20 | 15.38 | 23.53 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.102230E+11 | 0.920071E+10 | 3816.83 | 01-JAN-00:03 | 3435.15 | 3435.15 | 30.56 | 15.94 |
February | 0.923369E+10 | 0.831032E+10 | 3816.83 | 01-FEB-00:03 | 3435.15 | 3435.15 | 33.63 | 15.94 |
March | 0.102230E+11 | 0.920071E+10 | 3816.83 | 01-MAR-00:03 | 3435.15 | 3435.15 | 36.92 | 15.94 |
April | 0.989324E+10 | 0.890391E+10 | 3816.83 | 01-APR-00:03 | 3435.15 | 3435.15 | 44.06 | 15.94 |
May | 0.102230E+11 | 0.920071E+10 | 3816.83 | 01-MAY-00:03 | 3435.15 | 3435.15 | 34.82 | 15.94 |
June | 0.989324E+10 | 0.890391E+10 | 3816.83 | 01-JUN-00:03 | 3435.15 | 3435.15 | 33.11 | 15.94 |
July | 0.102230E+11 | 0.920071E+10 | 3816.83 | 01-JUL-00:03 | 3435.15 | 3435.15 | 38.03 | 15.94 |
August | 0.102230E+11 | 0.920071E+10 | 3816.83 | 01-AUG-00:03 | 3435.15 | 3435.15 | 41.91 | 15.94 |
September | 0.989324E+10 | 0.890391E+10 | 3816.83 | 01-SEP-00:05 | 3435.15 | 3435.15 | 32.66 | 15.94 |
October | 0.102230E+11 | 0.920071E+10 | 3816.83 | 01-OCT-00:03 | 3435.15 | 3435.15 | 35.46 | 15.94 |
November | 0.989324E+10 | 0.890391E+10 | 3816.83 | 01-NOV-00:03 | 3435.15 | 3435.15 | 37.89 | 15.94 |
December | 0.102230E+11 | 0.920071E+10 | 3816.83 | 01-DEC-00:03 | 3435.15 | 3435.15 | 38.11 | 15.94 |
Annual Sum or Average | 0.120368E+12 | 0.108331E+12 | ||||||
Minimum of Months | 0.923369E+10 | 0.831032E+10 | 3816.83 | 3435.15 | 3435.15 | 30.56 | 15.94 | |
Maximum of Months | 0.102230E+11 | 0.920071E+10 | 3816.83 | 3435.15 | 3435.15 | 44.06 | 15.94 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:03 | 16.86 | 16.86 | 58.27 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:02 | 16.86 | 16.86 | 58.21 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:02 | 16.86 | 16.86 | 58.25 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:03 | 16.86 | 16.86 | 58.17 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:02 | 16.86 | 16.86 | 58.46 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 58.25 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:02 | 16.86 | 16.86 | 58.35 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 58.26 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 58.25 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:03 | 16.86 | 16.86 | 58.21 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:02 | 16.86 | 16.86 | 58.25 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:02 | 16.86 | 16.86 | 58.22 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 58.17 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 58.46 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.443422E+11 | 0.399080E+11 | 41174.01 | 02-JAN-16:35 | 37056.61 | 37056.61 | 29.91 | 165.83 |
February | 0.439740E+11 | 0.395766E+11 | 41174.01 | 01-FEB-13:03 | 37056.61 | 37056.61 | 30.62 | 165.83 |
March | 0.524295E+11 | 0.471866E+11 | 41174.01 | 06-MAR-14:15 | 37056.61 | 37056.61 | 29.78 | 165.83 |
April | 0.535088E+11 | 0.481579E+11 | 41174.01 | 03-APR-08:50 | 37056.61 | 37056.61 | 29.57 | 165.83 |
May | 0.573296E+11 | 0.515966E+11 | 41174.01 | 01-MAY-10:55 | 37056.61 | 37056.61 | 32.57 | 165.83 |
June | 0.592965E+11 | 0.533669E+11 | 41174.01 | 01-JUN-08:30 | 37056.61 | 37056.61 | 30.67 | 165.83 |
July | 0.515273E+11 | 0.463746E+11 | 41174.01 | 03-JUL-09:30 | 37056.61 | 37056.61 | 29.49 | 165.83 |
August | 0.561614E+11 | 0.505453E+11 | 41174.01 | 01-AUG-08:70 | 37056.61 | 37056.61 | 30.28 | 165.83 |
September | 0.512530E+11 | 0.461277E+11 | 41174.01 | 01-SEP-08:00 | 37056.61 | 37056.61 | 31.27 | 165.83 |
October | 0.511669E+11 | 0.460502E+11 | 41174.01 | 02-OCT-10:00 | 37056.61 | 37056.61 | 29.98 | 165.83 |
November | 0.490277E+11 | 0.441249E+11 | 41174.01 | 01-NOV-13:30 | 37056.61 | 37056.61 | 29.59 | 165.83 |
December | 0.490096E+11 | 0.441087E+11 | 41174.01 | 11-DEC-10:10 | 37056.61 | 37056.61 | 29.58 | 165.83 |
Annual Sum or Average | 0.619026E+12 | 0.557124E+12 | ||||||
Minimum of Months | 0.439740E+11 | 0.395766E+11 | 41174.01 | 37056.61 | 37056.61 | 29.49 | 165.83 | |
Maximum of Months | 0.592965E+11 | 0.533669E+11 | 41174.01 | 37056.61 | 37056.61 | 32.57 | 165.83 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 757366.95 | 2862072.54 | 03-JAN-13:13 | 13.96 | 6.70 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 801676.69 | 2723043.30 | 13-FEB-11:13 | 13.61 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 853474.67 | 2534442.73 | 31-MAR-10:13 | 13.13 | 6.70 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 900034.59 | 2639548.34 | 17-APR-13:23 | 13.40 | 6.70 | 0.00 | 0.00 | 01-APR-00:03 |
May | 969436.96 | 2592652.25 | 01-MAY-12:33 | 13.28 | 6.70 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1014647.39 | 2689286.03 | 07-JUN-16:23 | 13.52 | 6.70 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 833399.53 | 2471434.48 | 26-JUL-14:33 | 12.97 | 6.70 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 920815.75 | 2776512.86 | 26-AUG-05:03 | 13.75 | 6.70 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 883782.44 | 2533838.86 | 29-SEP-11:13 | 13.13 | 6.70 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 834706.23 | 2881427.21 | 23-OCT-05:02 | 14.01 | 6.70 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 813994.77 | 2585614.75 | 29-NOV-13:13 | 13.26 | 6.70 | 0.00 | 0.00 | 01-NOV-00:03 |
December | 759194.85 | 2809968.18 | 28-DEC-14:02 | 13.83 | 6.70 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 861920.45 | 0.00 | ||||||
Minimum of Months | 757366.95 | 2471434.48 | 12.97 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 1014647.39 | 2881427.21 | 14.01 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 825253.87 | 3605649.70 | 02-JAN-05:12 | 16.26 | 11.26 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 888317.07 | 3570917.83 | 16-FEB-04:02 | 16.16 | 11.21 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 923800.41 | 3578866.10 | 15-MAR-04:12 | 16.18 | 11.22 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 1019900.37 | 3406976.34 | 25-APR-13:40 | 15.73 | 12.35 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1021860.02 | 3698812.11 | 22-MAY-03:02 | 16.50 | 11.37 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1049162.65 | 3695702.31 | 28-JUN-03:02 | 16.51 | 11.37 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 905312.09 | 3615707.43 | 28-JUL-03:02 | 16.28 | 11.27 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1045462.04 | 3665700.46 | 01-AUG-03:02 | 16.41 | 11.33 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 931411.57 | 3640199.03 | 07-SEP-03:02 | 16.42 | 11.30 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 875080.96 | 3637651.20 | 06-OCT-03:02 | 16.43 | 11.29 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 883002.34 | 3628520.01 | 13-NOV-04:02 | 16.32 | 11.28 | 0.00 | 0.00 | 01-NOV-00:03 |
December | 812737.21 | 3924407.62 | 08-DEC-05:12 | 17.10 | 11.66 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 931703.81 | 0.00 | ||||||
Minimum of Months | 812737.21 | 3406976.34 | 15.73 | 11.21 | 0.00 | 0.00 | ||
Maximum of Months | 1049162.65 | 3924407.62 | 17.10 | 12.35 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 764037.37 | 1233222.75 | 04-JAN-13:10 | 40.21 | 35.70 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 1038380.89 | 1520129.37 | 28-FEB-15:00 | 45.17 | 37.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 1302621.04 | 1816191.93 | 21-MAR-13:10 | 50.25 | 40.04 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 1571006.23 | 1977863.16 | 01-APR-14:00 | 53.00 | 40.18 | 0.00 | 0.00 | 01-APR-00:03 |
May | 934758.94 | 1437836.07 | 06-MAY-13:00 | 43.75 | 39.23 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1137975.29 | 1602220.89 | 13-JUN-15:00 | 46.58 | 38.81 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1237619.53 | 1619698.62 | 21-JUL-15:00 | 46.88 | 36.69 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1471898.03 | 1900458.01 | 10-AUG-14:00 | 51.68 | 38.72 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 845493.20 | 1244005.32 | 06-SEP-14:00 | 40.40 | 35.69 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 1010322.72 | 1401821.55 | 04-OCT-14:00 | 43.13 | 35.68 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 1201675.19 | 1664486.85 | 18-NOV-13:00 | 47.65 | 37.85 | 0.00 | 0.00 | 01-NOV-00:03 |
December | 1358853.59 | 1824976.71 | 08-DEC-15:00 | 50.40 | 37.64 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 1156829.07 | 0.00 | ||||||
Minimum of Months | 764037.37 | 1233222.75 | 40.21 | 35.68 | 0.00 | 0.00 | ||
Maximum of Months | 1571006.23 | 1977863.16 | 53.00 | 40.18 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 58.85 | 58.85 | 8918.11 | 31666.38 | 12-JAN-12:55 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 58.55 | 58.55 | 8916.97 | 31592.27 | 01-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 58.56 | 58.56 | 9333.59 | 31251.63 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:03 | 58.59 | 58.59 | 8556.25 | 30599.98 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 58.90 | 58.90 | 8656.53 | 29979.62 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 58.65 | 58.65 | 8741.08 | 29399.46 | 01-JUN-11:20 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 58.67 | 58.67 | 7996.78 | 29116.65 | 31-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 58.66 | 58.66 | 8822.49 | 29482.57 | 31-AUG-11:20 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 58.65 | 58.65 | 8404.01 | 30049.67 | 29-SEP-11:13 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 58.62 | 58.62 | 8573.79 | 30757.38 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 58.59 | 58.59 | 8875.77 | 31318.75 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:03 | 58.56 | 58.56 | 8669.19 | 31626.07 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 8704.31 | ||||||
Minimum of Months | 0.00 | 0.00 | 58.55 | 58.55 | 7996.78 | 29116.65 | ||
Maximum of Months | 0.00 | 0.00 | 58.90 | 58.90 | 9333.59 | 31666.38 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1770983.60 | 7360502.99 | 12-JAN-14:53 | 31.72 | 27.27 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 1987750.08 | 8110467.41 | 14-FEB-15:53 | 32.80 | 28.38 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 2321977.26 | 7789676.71 | 23-MAR-14:23 | 32.34 | 27.92 | 0.00 | 0.00 | 01-MAR-00:03 |
April | 2959013.64 | 8449004.36 | 17-APR-14:43 | 33.29 | 28.80 | 0.00 | 0.00 | 01-APR-00:03 |
May | 3416039.77 | 8487884.61 | 09-MAY-15:43 | 33.34 | 28.84 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 3607102.32 | 8316566.72 | 09-JUN-12:03 | 33.10 | 28.76 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 2437641.55 | 8011687.34 | 26-JUL-14:33 | 32.66 | 28.14 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 3129790.44 | 8181602.55 | 02-AUG-13:35 | 32.90 | 28.69 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 2946943.06 | 7960281.65 | 05-SEP-10:35 | 32.58 | 28.59 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 2679210.75 | 8369240.35 | 06-OCT-14:03 | 33.17 | 28.66 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 2375538.21 | 7877080.54 | 15-NOV-15:23 | 32.46 | 28.00 | 0.00 | 0.00 | 01-NOV-00:03 |
December | 1904023.64 | 7108393.72 | 12-DEC-13:03 | 31.35 | 27.51 | 0.00 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 2629492.05 | 0.00 | ||||||
Minimum of Months | 1770983.60 | 7108393.72 | 31.35 | 27.27 | 0.00 | 0.00 | ||
Maximum of Months | 3607102.32 | 8487884.61 | 33.34 | 28.84 | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.221479E+12 | 0.112091E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.221207E+12 | 0.119798E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.278285E+12 | 0.162638E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.275314E+12 | 0.167704E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.278418E+12 | 0.139603E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.288901E+12 | 0.151606E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.277108E+12 | 0.147566E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.307076E+12 | 0.176234E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.256164E+12 | 0.122839E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.266280E+12 | 0.127071E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.262212E+12 | 0.140691E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.252968E+12 | 0.131614E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.318541E+13 | 0.169946E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.221207E+12 | 0.112091E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.307076E+12 | 0.176234E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.154828E+13 | 0.603009E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.147968E+13 | 0.581051E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.176258E+13 | 0.650907E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.177370E+13 | 0.594003E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.193809E+13 | 0.628163E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.197363E+13 | 0.663210E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.167992E+13 | 0.558821E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.183034E+13 | 0.588798E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.169506E+13 | 0.540190E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.166758E+13 | 0.536527E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.159413E+13 | 0.563220E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.152234E+13 | 0.570016E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.204653E+14 | 0.707792E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.147968E+13 | 0.536527E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.197363E+13 | 0.663210E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.162432E+12 | 0.631241E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.156623E+12 | 0.625871E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.189574E+12 | 0.720842E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.192250E+12 | 0.672424E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.208681E+12 | 0.694231E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.212414E+12 | 0.729166E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.179358E+12 | 0.603508E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.194129E+12 | 0.639441E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.181639E+12 | 0.589992E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.175362E+12 | 0.564293E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.167222E+12 | 0.592361E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.159173E+12 | 0.588777E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.217886E+13 | 0.765215E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.156623E+12 | 0.564293E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.212414E+12 | 0.729166E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.288210E+11 | 0.333020E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.197648E+11 | 0.195259E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.297165E+10 | 0.232093E+09 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.771089E+09 | 52408018.82 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.563726E+10 | 0.538945E+09 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.304535E+11 | 0.295102E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.884194E+11 | 0.905725E+10 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.304535E+11 | 0.333020E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.499233E+12 | 0.231183E+12 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.750059E+12 | 0.284074E+12 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.116598E+13 | 0.400252E+12 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.145737E+13 | 0.473269E+12 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.533076E+12 | 0.245602E+12 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.833203E+12 | 0.316574E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.116158E+13 | 0.392419E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.149537E+13 | 0.474229E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.505586E+12 | 0.231410E+12 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.839686E+12 | 0.313393E+12 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.111838E+13 | 0.375230E+12 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.146233E+13 | 0.455595E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.118219E+14 | 0.419323E+13 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.499233E+12 | 0.231183E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.149537E+13 | 0.474229E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.943389E+10 | 0.365711E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.148008E+11 | 0.483055E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.234197E+11 | 0.707896E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.294878E+11 | 0.854321E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.106747E+11 | 0.404356E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.169491E+11 | 0.550537E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.233505E+11 | 0.692413E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.302560E+11 | 0.853698E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.994323E+10 | 0.375328E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.167969E+11 | 0.536121E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.224535E+11 | 0.660740E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.292484E+11 | 0.812957E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.236814E+12 | 0.729713E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.943389E+10 | 0.365711E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.302560E+11 | 0.854321E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.860426E+11 | 0.339503E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.138207E+12 | 0.453665E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.219365E+12 | 0.665850E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.277365E+12 | 0.806496E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.964888E+11 | 0.372463E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.157811E+12 | 0.515696E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.218420E+12 | 0.650625E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.285282E+12 | 0.807142E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.893307E+11 | 0.344807E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.155914E+12 | 0.501355E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.210696E+12 | 0.622310E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.276296E+12 | 0.769575E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.221122E+13 | 0.684949E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.860426E+11 | 0.339503E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.285282E+12 | 0.807142E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.867501E+10 | 0.344109E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.139223E+11 | 0.458891E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.221121E+11 | 0.673353E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.279633E+11 | 0.815537E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.986476E+10 | 0.380605E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.159677E+11 | 0.523114E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.220006E+11 | 0.657589E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.286809E+11 | 0.814583E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.910553E+10 | 0.351626E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.156929E+11 | 0.506766E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.211576E+11 | 0.627607E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.276999E+11 | 0.775034E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.222843E+12 | 0.692881E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.867501E+10 | 0.344109E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.286809E+11 | 0.815537E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.112091E+11 | 0.221479E+12 | 0.00 | 0.00 | 0.317092E+11 | 0.00 | 0.00 | 0.00 |
February | 0.119798E+11 | 0.221207E+12 | 0.00 | 0.00 | 0.342777E+11 | 0.00 | 0.00 | 0.00 |
March | 0.162638E+11 | 0.278285E+12 | 0.00 | 0.00 | 0.496854E+11 | 0.00 | 0.00 | 0.00 |
April | 0.167704E+11 | 0.275314E+12 | 0.00 | 0.00 | 0.729377E+11 | 0.00 | 0.00 | 0.00 |
May | 0.139603E+11 | 0.278418E+12 | 0.00 | 0.00 | 0.801806E+11 | 0.00 | 0.00 | 0.00 |
June | 0.151606E+11 | 0.288901E+12 | 0.00 | 0.00 | 0.798270E+11 | 0.00 | 0.00 | 0.00 |
July | 0.147566E+11 | 0.277108E+12 | 0.00 | 0.00 | 0.445760E+11 | 0.00 | 0.00 | 0.00 |
August | 0.176234E+11 | 0.307076E+12 | 0.00 | 0.00 | 0.650675E+11 | 0.00 | 0.00 | 0.00 |
September | 0.122839E+11 | 0.256164E+12 | 0.00 | 0.00 | 0.575090E+11 | 0.00 | 0.00 | 0.00 |
October | 0.127071E+11 | 0.266280E+12 | 0.00 | 0.00 | 0.499406E+11 | 0.00 | 0.00 | 0.00 |
November | 0.140691E+11 | 0.262212E+12 | 0.00 | 0.00 | 0.424038E+11 | 0.00 | 0.00 | 0.00 |
December | 0.131614E+11 | 0.252968E+12 | 0.00 | 0.00 | 0.335720E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169946E+12 | 0.318541E+13 | 0.00 | 0.00 | 0.641686E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.112091E+11 | 0.221207E+12 | 0.00 | 0.00 | 0.317092E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.176234E+11 | 0.307076E+12 | 0.00 | 0.00 | 0.801806E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.603009E+11 | 0.154828E+13 | 0.00 | 0.00 | 0.335470E+12 | 0.00 | 0.00 | 0.00 |
February | 0.581051E+11 | 0.147968E+13 | 0.00 | 0.00 | 0.356455E+12 | 0.00 | 0.00 | 0.00 |
March | 0.650907E+11 | 0.176258E+13 | 0.00 | 0.00 | 0.524660E+12 | 0.00 | 0.00 | 0.00 |
April | 0.594003E+11 | 0.177370E+13 | 0.00 | 0.00 | 0.703072E+12 | 0.00 | 0.00 | 0.00 |
May | 0.628163E+11 | 0.193809E+13 | 0.00 | 0.00 | 0.788428E+12 | 0.00 | 0.00 | 0.00 |
June | 0.663210E+11 | 0.197363E+13 | 0.00 | 0.00 | 0.795334E+12 | 0.00 | 0.00 | 0.00 |
July | 0.558821E+11 | 0.167992E+13 | 0.00 | 0.00 | 0.468762E+12 | 0.00 | 0.00 | 0.00 |
August | 0.588798E+11 | 0.183034E+13 | 0.00 | 0.00 | 0.684768E+12 | 0.00 | 0.00 | 0.00 |
September | 0.540190E+11 | 0.169506E+13 | 0.00 | 0.00 | 0.609991E+12 | 0.00 | 0.00 | 0.00 |
October | 0.536527E+11 | 0.166758E+13 | 0.00 | 0.00 | 0.526410E+12 | 0.00 | 0.00 | 0.00 |
November | 0.563220E+11 | 0.159413E+13 | 0.00 | 0.00 | 0.446916E+12 | 0.00 | 0.00 | 0.00 |
December | 0.570016E+11 | 0.152234E+13 | 0.00 | 0.00 | 0.356984E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.707792E+12 | 0.204653E+14 | 0.00 | 0.00 | 0.659725E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.536527E+11 | 0.147968E+13 | 0.00 | 0.00 | 0.335470E+12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.663210E+11 | 0.197363E+13 | 0.00 | 0.00 | 0.795334E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.631241E+10 | 0.162432E+12 | 0.00 | 0.00 | 0.327154E+11 | 0.00 | 0.00 | 0.00 |
February | 0.625871E+10 | 0.156623E+12 | 0.00 | 0.00 | 0.349397E+11 | 0.00 | 0.00 | 0.00 |
March | 0.720842E+10 | 0.189574E+12 | 0.00 | 0.00 | 0.507199E+11 | 0.00 | 0.00 | 0.00 |
April | 0.672424E+10 | 0.192250E+12 | 0.00 | 0.00 | 0.682423E+11 | 0.00 | 0.00 | 0.00 |
May | 0.694231E+10 | 0.208681E+12 | 0.00 | 0.00 | 0.771702E+11 | 0.00 | 0.00 | 0.00 |
June | 0.729166E+10 | 0.212414E+12 | 0.00 | 0.00 | 0.778491E+11 | 0.00 | 0.00 | 0.00 |
July | 0.603508E+10 | 0.179358E+12 | 0.00 | 0.00 | 0.458952E+11 | 0.00 | 0.00 | 0.00 |
August | 0.639441E+10 | 0.194129E+12 | 0.00 | 0.00 | 0.670333E+11 | 0.00 | 0.00 | 0.00 |
September | 0.589992E+10 | 0.181639E+12 | 0.00 | 0.00 | 0.597952E+11 | 0.00 | 0.00 | 0.00 |
October | 0.564293E+10 | 0.175362E+12 | 0.00 | 0.00 | 0.528416E+11 | 0.00 | 0.00 | 0.00 |
November | 0.592361E+10 | 0.167222E+12 | 0.00 | 0.00 | 0.442518E+11 | 0.00 | 0.00 | 0.00 |
December | 0.588777E+10 | 0.159173E+12 | 0.00 | 0.00 | 0.348507E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.765215E+11 | 0.217886E+13 | 0.00 | 0.00 | 0.646304E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.564293E+10 | 0.156623E+12 | 0.00 | 0.00 | 0.327154E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.729166E+10 | 0.212414E+12 | 0.00 | 0.00 | 0.778491E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.333020E+10 | 0.288210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.195259E+10 | 0.197648E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.232093E+09 | 0.297165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 52408018.82 | 0.771089E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.538945E+09 | 0.563726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.295102E+10 | 0.304535E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.905725E+10 | 0.884194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.333020E+10 | 0.304535E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.108552E+12 | 0.376601E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.980467E+11 | 0.564031E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.108552E+12 | 0.874285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.105050E+12 | 0.108915E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108552E+12 | 0.396025E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.105050E+12 | 0.621679E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.108552E+12 | 0.877711E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.108552E+12 | 0.112969E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.105050E+12 | 0.379226E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108552E+12 | 0.634845E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.105050E+12 | 0.848201E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108552E+12 | 0.111529E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127811E+13 | 0.890674E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.980467E+11 | 0.376601E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.108552E+12 | 0.112969E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.141307E+10 | 0.718984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127632E+10 | 0.112465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141307E+10 | 0.177538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136749E+10 | 0.223121E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141307E+10 | 0.804418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136749E+10 | 0.128112E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141307E+10 | 0.178395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.141307E+10 | 0.231321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136749E+10 | 0.755744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141307E+10 | 0.128488E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136749E+10 | 0.172136E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141307E+10 | 0.225319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166377E+11 | 0.180481E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127632E+10 | 0.718984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141307E+10 | 0.231321E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.134409E+11 | 0.655332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121402E+11 | 0.104981E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134409E+11 | 0.166221E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130073E+11 | 0.209723E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134409E+11 | 0.726833E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130073E+11 | 0.119249E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134409E+11 | 0.166798E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.134409E+11 | 0.218008E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130073E+11 | 0.678573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134409E+11 | 0.119219E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130073E+11 | 0.161473E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134409E+11 | 0.212780E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158256E+12 | 0.168452E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121402E+11 | 0.655332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134409E+11 | 0.218008E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.136960E+10 | 0.660352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123706E+10 | 0.105704E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136960E+10 | 0.167481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132542E+10 | 0.211333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136960E+10 | 0.742831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132542E+10 | 0.120619E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136960E+10 | 0.167943E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.136960E+10 | 0.219047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132542E+10 | 0.691469E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136960E+10 | 0.119948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132542E+10 | 0.162070E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136960E+10 | 0.213192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161259E+11 | 0.169680E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123706E+10 | 0.660352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136960E+10 | 0.219047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.112091E+11 | 0.00 | 0.221479E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119798E+11 | 0.00 | 0.221207E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.162638E+11 | 0.00 | 0.278285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167704E+11 | 0.00 | 0.275314E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139603E+11 | 0.00 | 0.278418E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.151606E+11 | 0.00 | 0.288901E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147566E+11 | 0.00 | 0.277108E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.176234E+11 | 0.00 | 0.307076E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.122839E+11 | 0.00 | 0.256164E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.127071E+11 | 0.00 | 0.266280E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140691E+11 | 0.00 | 0.262212E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131614E+11 | 0.00 | 0.252968E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169946E+12 | 0.00 | 0.318541E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.112091E+11 | 0.00 | 0.221207E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.176234E+11 | 0.00 | 0.307076E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.603009E+11 | 0.00 | 0.154828E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.581051E+11 | 0.00 | 0.147968E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.650907E+11 | 0.00 | 0.176258E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.594003E+11 | 0.00 | 0.177370E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.628163E+11 | 0.00 | 0.193809E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.663210E+11 | 0.00 | 0.197363E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.558821E+11 | 0.00 | 0.167992E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.588798E+11 | 0.00 | 0.183034E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.540190E+11 | 0.00 | 0.169506E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.536527E+11 | 0.00 | 0.166758E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.563220E+11 | 0.00 | 0.159413E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.570016E+11 | 0.00 | 0.152234E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.707792E+12 | 0.00 | 0.204653E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.536527E+11 | 0.00 | 0.147968E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.663210E+11 | 0.00 | 0.197363E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.631241E+10 | 0.00 | 0.162432E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.625871E+10 | 0.00 | 0.156623E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.720842E+10 | 0.00 | 0.189574E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.672424E+10 | 0.00 | 0.192250E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.694231E+10 | 0.00 | 0.208681E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.729166E+10 | 0.00 | 0.212414E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.603508E+10 | 0.00 | 0.179358E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.639441E+10 | 0.00 | 0.194129E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.589992E+10 | 0.00 | 0.181639E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.564293E+10 | 0.00 | 0.175362E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.592361E+10 | 0.00 | 0.167222E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.588777E+10 | 0.00 | 0.159173E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.765215E+11 | 0.00 | 0.217886E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.564293E+10 | 0.00 | 0.156623E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.729166E+10 | 0.00 | 0.212414E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.333020E+10 | 0.00 | 0.288210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.195259E+10 | 0.00 | 0.197648E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.232093E+09 | 0.00 | 0.297165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 52408018.82 | 0.00 | 0.771089E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.538945E+09 | 0.00 | 0.563726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.295102E+10 | 0.00 | 0.304535E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.905725E+10 | 0.00 | 0.884194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.333020E+10 | 0.00 | 0.304535E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.108552E+12 | 0.00 | 0.499233E+12 | 0.00 | 0.122632E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.980467E+11 | 0.00 | 0.750059E+12 | 0.00 | 0.186028E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.108552E+12 | 0.00 | 0.116598E+13 | 0.00 | 0.291700E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.105050E+12 | 0.00 | 0.145737E+13 | 0.00 | 0.368219E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108552E+12 | 0.00 | 0.533076E+12 | 0.00 | 0.137051E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.105050E+12 | 0.00 | 0.833203E+12 | 0.00 | 0.211524E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.108552E+12 | 0.00 | 0.116158E+13 | 0.00 | 0.283867E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.108552E+12 | 0.00 | 0.149537E+13 | 0.00 | 0.365677E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.105050E+12 | 0.00 | 0.505586E+12 | 0.00 | 0.126360E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108552E+12 | 0.00 | 0.839686E+12 | 0.00 | 0.204841E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.105050E+12 | 0.00 | 0.111838E+13 | 0.00 | 0.270180E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108552E+12 | 0.00 | 0.146233E+13 | 0.00 | 0.347043E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127811E+13 | 0.00 | 0.118219E+14 | 0.00 | 0.291512E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.980467E+11 | 0.00 | 0.499233E+12 | 0.00 | 0.122632E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.108552E+12 | 0.00 | 0.149537E+13 | 0.00 | 0.368219E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.141307E+10 | 0.00 | 0.943389E+10 | 0.00 | 0.224404E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127632E+10 | 0.00 | 0.148008E+11 | 0.00 | 0.355423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141307E+10 | 0.00 | 0.234197E+11 | 0.00 | 0.566590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136749E+10 | 0.00 | 0.294878E+11 | 0.00 | 0.717572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141307E+10 | 0.00 | 0.106747E+11 | 0.00 | 0.263049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136749E+10 | 0.00 | 0.169491E+11 | 0.00 | 0.413789E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141307E+10 | 0.00 | 0.233505E+11 | 0.00 | 0.551106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.141307E+10 | 0.00 | 0.302560E+11 | 0.00 | 0.712391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136749E+10 | 0.00 | 0.994323E+10 | 0.00 | 0.238579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141307E+10 | 0.00 | 0.167969E+11 | 0.00 | 0.394814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136749E+10 | 0.00 | 0.224535E+11 | 0.00 | 0.523991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141307E+10 | 0.00 | 0.292484E+11 | 0.00 | 0.671650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166377E+11 | 0.00 | 0.236814E+12 | 0.00 | 0.563336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127632E+10 | 0.00 | 0.943389E+10 | 0.00 | 0.224404E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141307E+10 | 0.00 | 0.302560E+11 | 0.00 | 0.717572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.134409E+11 | 0.00 | 0.860426E+11 | 0.00 | 0.205094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121402E+11 | 0.00 | 0.138207E+12 | 0.00 | 0.332263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.134409E+11 | 0.00 | 0.219365E+12 | 0.00 | 0.531441E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130073E+11 | 0.00 | 0.277365E+12 | 0.00 | 0.676423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134409E+11 | 0.00 | 0.964888E+11 | 0.00 | 0.238054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130073E+11 | 0.00 | 0.157811E+12 | 0.00 | 0.385623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.134409E+11 | 0.00 | 0.218420E+12 | 0.00 | 0.516216E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.134409E+11 | 0.00 | 0.285282E+12 | 0.00 | 0.672733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130073E+11 | 0.00 | 0.893307E+11 | 0.00 | 0.214734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134409E+11 | 0.00 | 0.155914E+12 | 0.00 | 0.366946E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130073E+11 | 0.00 | 0.210696E+12 | 0.00 | 0.492237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.134409E+11 | 0.00 | 0.276296E+12 | 0.00 | 0.635166E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.158256E+12 | 0.00 | 0.221122E+13 | 0.00 | 0.526693E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121402E+11 | 0.00 | 0.860426E+11 | 0.00 | 0.205094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.134409E+11 | 0.00 | 0.285282E+12 | 0.00 | 0.676423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.136960E+10 | 0.00 | 0.867501E+10 | 0.00 | 0.207149E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123706E+10 | 0.00 | 0.139223E+11 | 0.00 | 0.335185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.136960E+10 | 0.00 | 0.221121E+11 | 0.00 | 0.536393E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132542E+10 | 0.00 | 0.279633E+11 | 0.00 | 0.682995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.136960E+10 | 0.00 | 0.986476E+10 | 0.00 | 0.243645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132542E+10 | 0.00 | 0.159677E+11 | 0.00 | 0.390572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136960E+10 | 0.00 | 0.220006E+11 | 0.00 | 0.520629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.136960E+10 | 0.00 | 0.286809E+11 | 0.00 | 0.677623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132542E+10 | 0.00 | 0.910553E+10 | 0.00 | 0.219084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136960E+10 | 0.00 | 0.156929E+11 | 0.00 | 0.369806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132542E+10 | 0.00 | 0.211576E+11 | 0.00 | 0.495065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136960E+10 | 0.00 | 0.276999E+11 | 0.00 | 0.638074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161259E+11 | 0.00 | 0.222843E+12 | 0.00 | 0.531622E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123706E+10 | 0.00 | 0.867501E+10 | 0.00 | 0.207149E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136960E+10 | 0.00 | 0.286809E+11 | 0.00 | 0.682995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.433899E+10 | 0.00 | 39050170.67 | 0.00 | 0.00 | 0.554506E+09 | 0.00 | 0.07 |
February | 0.00 | 0.341321E+10 | 0.00 | 32254345.94 | 0.00 | 0.00 | 0.525627E+09 | 0.00 | 0.04 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.624876E+09 | 0.00 | 11906899.43 | 0.00 | 0.00 | 74472756.02 | 0.00 | 0.00 |
May | 0.00 | 6717235.81 | 0.00 | 10157054.62 | 0.00 | 0.00 | 93865948.73 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.830477E+09 | 0.00 | 10852249.09 | 0.00 | 0.00 | 0.160047E+09 | 0.00 | 0.01 |
December | 0.00 | 0.412842E+10 | 0.00 | 79009403.76 | 0.00 | 0.00 | 0.124993E+10 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.133427E+11 | 0.00 | 0.183230E+09 | 0.00 | 0.00 | 0.265845E+10 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.433899E+10 | 0.00 | 79009403.76 | 0.00 | 0.00 | 0.124993E+10 | 0.00 | 0.07 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 4996506.48 | 0.158448E+11 | 0.00 | 1356351.51 | 0.884749E+10 | 0.00 | 5496398.78 | 0.00 | 0.41 |
February | 468765.64 | 0.150648E+11 | 0.00 | 38581.21 | 0.994468E+10 | 0.00 | 199903.54 | 0.00 | 0.43 |
March | 0.00 | 0.196708E+11 | 0.00 | 0.00 | 0.123960E+11 | 0.00 | 0.00 | 0.00 | 0.47 |
April | 0.00 | 0.212653E+11 | 0.00 | 0.00 | 0.131502E+11 | 0.00 | 0.00 | 0.00 | 0.47 |
May | 0.00 | 0.287944E+11 | 0.00 | 0.00 | 0.139366E+11 | 0.00 | 0.00 | 0.00 | 0.45 |
June | 0.00 | 0.286185E+11 | 0.00 | 0.00 | 0.144194E+11 | 0.00 | 0.00 | 0.00 | 0.46 |
July | 0.00 | 0.249687E+11 | 0.00 | 0.00 | 0.165081E+11 | 0.00 | 0.00 | 0.00 | 0.47 |
August | 0.00 | 0.313458E+11 | 0.00 | 0.00 | 0.184713E+11 | 0.00 | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.279885E+11 | 0.00 | 0.00 | 0.137448E+11 | 0.00 | 0.00 | 0.00 | 0.44 |
October | 0.00 | 0.287703E+11 | 0.00 | 0.00 | 0.153370E+11 | 0.00 | 0.00 | 0.00 | 0.44 |
November | 0.00 | 0.227601E+11 | 0.00 | 0.00 | 0.152543E+11 | 0.00 | 0.00 | 0.00 | 0.45 |
December | 1015548.73 | 0.170620E+11 | 0.00 | 193919.69 | 0.155509E+11 | 0.00 | 51920.30 | 0.00 | 0.46 |
Annual Sum or Average | 6480820.84 | 0.282154E+12 | 0.00 | 1588852.41 | 0.167561E+12 | 0.00 | 5748222.62 | 0.00 | 0.45 |
Minimum of Months | 0.00 | 0.150648E+11 | 0.00 | 0.00 | 0.884749E+10 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 4996506.48 | 0.313458E+11 | 0.00 | 1356351.51 | 0.184713E+11 | 0.00 | 5496398.78 | 0.00 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 44597937.64 | 0.131666E+12 | 0.00 | 7551799.40 | 0.434770E+11 | 0.00 | 18325886.67 | 0.00 | 0.34 |
February | 0.00 | 0.120501E+12 | 0.00 | 0.00 | 0.499704E+11 | 0.00 | 0.00 | 0.00 | 0.35 |
March | 0.00 | 0.145207E+12 | 0.00 | 0.00 | 0.678618E+11 | 0.00 | 0.00 | 0.00 | 0.38 |
April | 0.00 | 0.159645E+12 | 0.00 | 0.00 | 0.103343E+12 | 0.00 | 0.00 | 0.00 | 0.39 |
May | 0.00 | 0.223474E+12 | 0.00 | 0.00 | 0.105572E+12 | 0.00 | 0.00 | 0.00 | 0.38 |
June | 0.00 | 0.222938E+12 | 0.00 | 0.00 | 0.996099E+11 | 0.00 | 0.00 | 0.00 | 0.38 |
July | 0.00 | 0.180913E+12 | 0.00 | 0.00 | 0.877320E+11 | 0.00 | 0.00 | 0.00 | 0.36 |
August | 0.00 | 0.231166E+12 | 0.00 | 0.00 | 0.831562E+11 | 0.00 | 0.00 | 0.00 | 0.37 |
September | 0.00 | 0.203895E+12 | 0.00 | 0.00 | 0.916988E+11 | 0.00 | 0.00 | 0.00 | 0.36 |
October | 0.00 | 0.209083E+12 | 0.00 | 0.00 | 0.806992E+11 | 0.00 | 0.00 | 0.00 | 0.35 |
November | 0.00 | 0.177072E+12 | 0.00 | 0.00 | 0.613517E+11 | 0.00 | 0.00 | 0.00 | 0.34 |
December | 9726056.97 | 0.142300E+12 | 0.00 | 2146124.87 | 0.496983E+11 | 0.00 | 1359226.22 | 0.00 | 0.33 |
Annual Sum or Average | 54323994.61 | 0.214786E+13 | 0.00 | 9697924.27 | 0.924170E+12 | 0.00 | 19685112.90 | 0.00 | 0.36 |
Minimum of Months | 0.00 | 0.120501E+12 | 0.00 | 0.00 | 0.434770E+11 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 44597937.64 | 0.231166E+12 | 0.00 | 7551799.40 | 0.105572E+12 | 0.00 | 18325886.67 | 0.00 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1866611.59 | 0.128343E+11 | 0.00 | 342493.11 | 0.415539E+10 | 0.00 | 549437.30 | 0.00 | 0.33 |
February | 0.00 | 0.119137E+11 | 0.00 | 0.00 | 0.438932E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
March | 0.00 | 0.144693E+11 | 0.00 | 0.00 | 0.609250E+10 | 0.00 | 0.00 | 0.00 | 0.38 |
April | 0.00 | 0.166584E+11 | 0.00 | 0.00 | 0.905733E+10 | 0.00 | 0.00 | 0.00 | 0.39 |
May | 0.00 | 0.229525E+11 | 0.00 | 0.00 | 0.960158E+10 | 0.00 | 0.00 | 0.00 | 0.38 |
June | 0.00 | 0.228331E+11 | 0.00 | 0.00 | 0.924560E+10 | 0.00 | 0.00 | 0.00 | 0.38 |
July | 0.00 | 0.184824E+11 | 0.00 | 0.00 | 0.803452E+10 | 0.00 | 0.00 | 0.00 | 0.36 |
August | 0.00 | 0.231981E+11 | 0.00 | 0.00 | 0.764125E+10 | 0.00 | 0.00 | 0.00 | 0.37 |
September | 0.00 | 0.208678E+11 | 0.00 | 0.00 | 0.845125E+10 | 0.00 | 0.00 | 0.00 | 0.37 |
October | 0.00 | 0.200617E+11 | 0.00 | 0.00 | 0.833729E+10 | 0.00 | 0.00 | 0.00 | 0.35 |
November | 0.00 | 0.172856E+11 | 0.00 | 0.00 | 0.589211E+10 | 0.00 | 0.00 | 0.00 | 0.34 |
December | 0.00 | 0.141148E+11 | 0.00 | 0.00 | 0.471282E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 1866611.59 | 0.215672E+12 | 0.00 | 342493.11 | 0.856110E+11 | 0.00 | 549437.30 | 0.00 | 0.36 |
Minimum of Months | 0.00 | 0.119137E+11 | 0.00 | 0.00 | 0.415539E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 1866611.59 | 0.231981E+11 | 0.00 | 342493.11 | 0.960158E+10 | 0.00 | 549437.30 | 0.00 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 994401.01 | 0.250809E+10 | 0.00 | 71736.19 | 0.107440E+10 | 0.00 | 249704.94 | 0.00 | 0.49 |
February | 58901.28 | 0.257315E+10 | 0.00 | 2345.54 | 0.112651E+10 | 0.00 | 23654.78 | 0.00 | 0.53 |
March | 0.00 | 0.342068E+10 | 0.00 | 0.00 | 0.139165E+10 | 0.00 | 0.00 | 0.00 | 0.58 |
April | 0.00 | 0.416642E+10 | 0.00 | 0.00 | 0.129818E+10 | 0.00 | 0.00 | 0.00 | 0.60 |
May | 0.00 | 0.616850E+10 | 0.00 | 0.00 | 0.118121E+10 | 0.00 | 0.00 | 0.00 | 0.63 |
June | 0.00 | 0.667162E+10 | 0.00 | 0.00 | 0.114840E+10 | 0.00 | 0.00 | 0.00 | 0.68 |
July | 0.00 | 0.512164E+10 | 0.00 | 0.00 | 0.148844E+10 | 0.00 | 0.00 | 0.00 | 0.62 |
August | 0.00 | 0.565350E+10 | 0.00 | 0.00 | 0.200011E+10 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.494733E+10 | 0.00 | 0.00 | 0.144502E+10 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 0.00 | 0.465675E+10 | 0.00 | 0.00 | 0.170112E+10 | 0.00 | 0.00 | 0.00 | 0.53 |
November | 0.00 | 0.368770E+10 | 0.00 | 0.00 | 0.173988E+10 | 0.00 | 0.00 | 0.00 | 0.53 |
December | 137921.39 | 0.270972E+10 | 0.00 | 10861.42 | 0.186460E+10 | 0.00 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 1191223.68 | 0.522851E+11 | 0.00 | 84943.16 | 0.174595E+11 | 0.00 | 273359.72 | 0.00 | 0.57 |
Minimum of Months | 0.00 | 0.250809E+10 | 0.00 | 0.00 | 0.107440E+10 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 994401.01 | 0.667162E+10 | 0.00 | 71736.19 | 0.200011E+10 | 0.00 | 249704.94 | 0.00 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 935530.30 | 0.205155E+10 | 0.00 | 43333.93 | 0.885601E+09 | 0.00 | 98963.53 | 0.00 | 0.62 |
February | 49641.64 | 0.210863E+10 | 0.00 | 1692.01 | 0.941005E+09 | 0.00 | 20220.90 | 0.00 | 0.68 |
March | 0.00 | 0.267004E+10 | 0.00 | 0.00 | 0.121485E+10 | 0.00 | 0.00 | 0.00 | 0.73 |
April | 0.00 | 0.312142E+10 | 0.00 | 0.00 | 0.120356E+10 | 0.00 | 0.00 | 0.00 | 0.74 |
May | 0.00 | 0.422078E+10 | 0.00 | 0.00 | 0.116158E+10 | 0.00 | 0.00 | 0.00 | 0.71 |
June | 0.00 | 0.414675E+10 | 0.00 | 0.00 | 0.129926E+10 | 0.00 | 0.00 | 0.00 | 0.73 |
July | 0.00 | 0.302624E+10 | 0.00 | 0.00 | 0.163824E+10 | 0.00 | 0.00 | 0.00 | 0.67 |
August | 0.00 | 0.372213E+10 | 0.00 | 0.00 | 0.197393E+10 | 0.00 | 0.00 | 0.00 | 0.69 |
September | 0.00 | 0.382213E+10 | 0.00 | 0.00 | 0.121775E+10 | 0.00 | 0.00 | 0.00 | 0.67 |
October | 0.00 | 0.338315E+10 | 0.00 | 0.00 | 0.152079E+10 | 0.00 | 0.00 | 0.00 | 0.63 |
November | 0.00 | 0.264033E+10 | 0.00 | 0.00 | 0.157182E+10 | 0.00 | 0.00 | 0.00 | 0.63 |
December | 116239.32 | 0.199842E+10 | 0.00 | 4065.91 | 0.160018E+10 | 0.00 | 107.85 | 0.00 | 0.63 |
Annual Sum or Average | 1101411.26 | 0.369116E+11 | 0.00 | 49091.85 | 0.162286E+11 | 0.00 | 119292.28 | 0.00 | 0.68 |
Minimum of Months | 0.00 | 0.199842E+10 | 0.00 | 0.00 | 0.885601E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
Maximum of Months | 935530.30 | 0.422078E+10 | 0.00 | 43333.93 | 0.197393E+10 | 0.00 | 98963.53 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 686707.52 | 0.360417E+10 | 0.00 | 125029.74 | 0.851278E+09 | 0.00 | 571214.48 | 0.00 | 0.64 |
February | 58733.26 | 0.337598E+10 | 0.00 | 5973.74 | 0.954865E+09 | 0.00 | 30507.69 | 0.00 | 0.64 |
March | 0.00 | 0.371671E+10 | 0.00 | 0.00 | 0.132635E+10 | 0.00 | 0.00 | 0.00 | 0.62 |
April | 0.00 | 0.376798E+10 | 0.00 | 0.00 | 0.143891E+10 | 0.00 | 0.00 | 0.00 | 0.58 |
May | 0.00 | 0.506249E+10 | 0.00 | 0.00 | 0.148880E+10 | 0.00 | 0.00 | 0.00 | 0.56 |
June | 0.00 | 0.501235E+10 | 0.00 | 0.00 | 0.157862E+10 | 0.00 | 0.00 | 0.00 | 0.57 |
July | 0.00 | 0.401547E+10 | 0.00 | 0.00 | 0.188567E+10 | 0.00 | 0.00 | 0.00 | 0.55 |
August | 0.00 | 0.487410E+10 | 0.00 | 0.00 | 0.226848E+10 | 0.00 | 0.00 | 0.00 | 0.56 |
September | 0.00 | 0.483757E+10 | 0.00 | 0.00 | 0.150582E+10 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 0.00 | 0.517856E+10 | 0.00 | 0.00 | 0.159319E+10 | 0.00 | 0.00 | 0.00 | 0.57 |
November | 0.00 | 0.470423E+10 | 0.00 | 0.00 | 0.145421E+10 | 0.00 | 0.00 | 0.00 | 0.62 |
December | 137527.97 | 0.402752E+10 | 0.00 | 12996.37 | 0.147524E+10 | 0.00 | 0.00 | 0.00 | 0.66 |
Annual Sum or Average | 882968.76 | 0.521771E+11 | 0.00 | 143999.86 | 0.178214E+11 | 0.00 | 601722.18 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.337598E+10 | 0.00 | 0.00 | 0.851278E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 686707.52 | 0.517856E+10 | 0.00 | 125029.74 | 0.226848E+10 | 0.00 | 571214.48 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 1077543.14 | 0.206726E+10 | 0.00 | 76241.73 | 0.123524E+10 | 0.00 | 282765.75 | 0.00 | 0.70 |
February | 65609.84 | 0.241990E+10 | 0.00 | 4997.14 | 0.119661E+10 | 0.00 | 25311.64 | 0.00 | 0.80 |
March | 0.00 | 0.354980E+10 | 0.00 | 0.00 | 0.129238E+10 | 0.00 | 0.00 | 0.00 | 0.90 |
April | 0.00 | 0.457297E+10 | 0.00 | 0.00 | 0.998229E+09 | 0.00 | 0.00 | 0.00 | 0.95 |
May | 0.00 | 0.396701E+10 | 0.00 | 0.00 | 0.183026E+10 | 0.00 | 0.00 | 0.00 | 0.76 |
June | 0.00 | 0.448718E+10 | 0.00 | 0.00 | 0.171673E+10 | 0.00 | 0.00 | 0.00 | 0.82 |
July | 0.00 | 0.392761E+10 | 0.00 | 0.00 | 0.187791E+10 | 0.00 | 0.00 | 0.00 | 0.82 |
August | 0.00 | 0.551948E+10 | 0.00 | 0.00 | 0.182678E+10 | 0.00 | 0.00 | 0.00 | 0.88 |
September | 0.00 | 0.353175E+10 | 0.00 | 0.00 | 0.192779E+10 | 0.00 | 0.00 | 0.00 | 0.72 |
October | 0.00 | 0.374081E+10 | 0.00 | 0.00 | 0.204716E+10 | 0.00 | 0.00 | 0.00 | 0.73 |
November | 0.00 | 0.342366E+10 | 0.00 | 0.00 | 0.184242E+10 | 0.00 | 0.00 | 0.00 | 0.78 |
December | 150274.02 | 0.333135E+10 | 0.00 | 17840.80 | 0.154334E+10 | 0.00 | 0.00 | 0.00 | 0.86 |
Annual Sum or Average | 1293427.00 | 0.445388E+11 | 0.00 | 99079.67 | 0.193348E+11 | 0.00 | 308077.39 | 0.00 | 0.81 |
Minimum of Months | 0.00 | 0.206726E+10 | 0.00 | 0.00 | 0.998229E+09 | 0.00 | 0.00 | 0.00 | 0.70 |
Maximum of Months | 1077543.14 | 0.551948E+10 | 0.00 | 76241.73 | 0.204716E+10 | 0.00 | 282765.75 | 0.00 | 0.95 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 7078475.26 | 0.230726E+11 | 0.00 | 374074.50 | 0.525712E+10 | 0.00 | 760807.48 | 0.00 | 0.44 |
February | 0.00 | 0.231953E+11 | 0.00 | 0.00 | 0.557385E+10 | 0.00 | 0.00 | 0.00 | 0.48 |
March | 0.00 | 0.307799E+11 | 0.00 | 0.00 | 0.710881E+10 | 0.00 | 0.00 | 0.00 | 0.55 |
April | 0.00 | 0.394416E+11 | 0.00 | 0.00 | 0.102583E+11 | 0.00 | 0.00 | 0.00 | 0.59 |
May | 0.00 | 0.608904E+11 | 0.00 | 0.00 | 0.830525E+10 | 0.00 | 0.00 | 0.00 | 0.64 |
June | 0.00 | 0.689699E+11 | 0.00 | 0.00 | 0.716631E+10 | 0.00 | 0.00 | 0.00 | 0.72 |
July | 0.00 | 0.456948E+11 | 0.00 | 0.00 | 0.705127E+10 | 0.00 | 0.00 | 0.00 | 0.59 |
August | 0.00 | 0.518880E+11 | 0.00 | 0.00 | 0.787387E+10 | 0.00 | 0.00 | 0.00 | 0.56 |
September | 0.00 | 0.432585E+11 | 0.00 | 0.00 | 0.926439E+10 | 0.00 | 0.00 | 0.00 | 0.52 |
October | 0.00 | 0.387579E+11 | 0.00 | 0.00 | 0.864472E+10 | 0.00 | 0.00 | 0.00 | 0.46 |
November | 0.00 | 0.318444E+11 | 0.00 | 0.00 | 0.711439E+10 | 0.00 | 0.00 | 0.00 | 0.45 |
December | 1363015.34 | 0.241262E+11 | 0.00 | 4851.78 | 0.581016E+10 | 0.00 | 23500.84 | 0.00 | 0.42 |
Annual Sum or Average | 8441490.60 | 0.481920E+12 | 0.00 | 378926.29 | 0.894285E+11 | 0.00 | 784308.32 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 0.230726E+11 | 0.00 | 0.00 | 0.525712E+10 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 7078475.26 | 0.689699E+11 | 0.00 | 374074.50 | 0.102583E+11 | 0.00 | 760807.48 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 6179525.23 | 0.208177E+11 | 0.00 | 567621.59 | 0.429542E+10 | 0.00 | 752343.28 | 0.00 | 0.61 |
February | 0.00 | 0.218289E+11 | 0.00 | 0.00 | 0.431509E+10 | 0.00 | 0.00 | 0.00 | 0.68 |
March | 0.00 | 0.287512E+11 | 0.00 | 0.00 | 0.555206E+10 | 0.00 | 0.00 | 0.00 | 0.78 |
April | 0.00 | 0.361214E+11 | 0.00 | 0.00 | 0.798903E+10 | 0.00 | 0.00 | 0.00 | 0.82 |
May | 0.00 | 0.438649E+11 | 0.00 | 0.00 | 0.802907E+10 | 0.00 | 0.00 | 0.00 | 0.75 |
June | 0.00 | 0.453023E+11 | 0.00 | 0.00 | 0.817694E+10 | 0.00 | 0.00 | 0.00 | 0.78 |
July | 0.00 | 0.305430E+11 | 0.00 | 0.00 | 0.749656E+10 | 0.00 | 0.00 | 0.00 | 0.65 |
August | 0.00 | 0.410941E+11 | 0.00 | 0.00 | 0.662318E+10 | 0.00 | 0.00 | 0.00 | 0.69 |
September | 0.00 | 0.369258E+11 | 0.00 | 0.00 | 0.713852E+10 | 0.00 | 0.00 | 0.00 | 0.68 |
October | 0.00 | 0.322066E+11 | 0.00 | 0.00 | 0.743252E+10 | 0.00 | 0.00 | 0.00 | 0.60 |
November | 0.00 | 0.270597E+11 | 0.00 | 0.00 | 0.581816E+10 | 0.00 | 0.00 | 0.00 | 0.59 |
December | 1202028.12 | 0.219500E+11 | 0.00 | 5404.59 | 0.437880E+10 | 0.00 | 19599.28 | 0.00 | 0.57 |
Annual Sum or Average | 7381553.35 | 0.386466E+12 | 0.00 | 573026.18 | 0.772454E+11 | 0.00 | 771942.56 | 0.00 | 0.68 |
Minimum of Months | 0.00 | 0.208177E+11 | 0.00 | 0.00 | 0.429542E+10 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 6179525.23 | 0.453023E+11 | 0.00 | 567621.59 | 0.817694E+10 | 0.00 | 752343.28 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 3928527.90 | 0.395439E+11 | 0.00 | 1427766.74 | 0.285128E+10 | 0.00 | 4383965.17 | 0.00 | 0.69 |
February | 0.00 | 0.366447E+11 | 0.00 | 0.00 | 0.342247E+10 | 0.00 | 0.00 | 0.00 | 0.68 |
March | 0.00 | 0.379708E+11 | 0.00 | 0.00 | 0.604089E+10 | 0.00 | 0.00 | 0.00 | 0.64 |
April | 0.00 | 0.383376E+11 | 0.00 | 0.00 | 0.103937E+11 | 0.00 | 0.00 | 0.00 | 0.58 |
May | 0.00 | 0.511354E+11 | 0.00 | 0.00 | 0.103027E+11 | 0.00 | 0.00 | 0.00 | 0.57 |
June | 0.00 | 0.506766E+11 | 0.00 | 0.00 | 0.102958E+11 | 0.00 | 0.00 | 0.00 | 0.57 |
July | 0.00 | 0.367642E+11 | 0.00 | 0.00 | 0.911980E+10 | 0.00 | 0.00 | 0.00 | 0.51 |
August | 0.00 | 0.472101E+11 | 0.00 | 0.00 | 0.850341E+10 | 0.00 | 0.00 | 0.00 | 0.52 |
September | 0.00 | 0.462688E+11 | 0.00 | 0.00 | 0.886892E+10 | 0.00 | 0.00 | 0.00 | 0.55 |
October | 0.00 | 0.498239E+11 | 0.00 | 0.00 | 0.660921E+10 | 0.00 | 0.00 | 0.00 | 0.56 |
November | 0.00 | 0.487535E+11 | 0.00 | 0.00 | 0.450872E+10 | 0.00 | 0.00 | 0.00 | 0.63 |
December | 1252488.45 | 0.431304E+11 | 0.00 | 138041.43 | 0.291418E+10 | 0.00 | 101292.68 | 0.00 | 0.66 |
Annual Sum or Average | 5181016.35 | 0.526260E+12 | 0.00 | 1565808.17 | 0.838310E+11 | 0.00 | 4485257.85 | 0.00 | 0.60 |
Minimum of Months | 0.00 | 0.366447E+11 | 0.00 | 0.00 | 0.285128E+10 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 3928527.90 | 0.511354E+11 | 0.00 | 1427766.74 | 0.103937E+11 | 0.00 | 4383965.17 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 6919258.42 | 0.218563E+11 | 0.00 | 475889.20 | 0.450083E+10 | 0.00 | 1252693.45 | 0.00 | 0.65 |
February | 0.00 | 0.231246E+11 | 0.00 | 0.00 | 0.465362E+10 | 0.00 | 0.00 | 0.00 | 0.72 |
March | 0.00 | 0.324495E+11 | 0.00 | 0.00 | 0.534136E+10 | 0.00 | 0.00 | 0.00 | 0.85 |
April | 0.00 | 0.401882E+11 | 0.00 | 0.00 | 0.772071E+10 | 0.00 | 0.00 | 0.00 | 0.89 |
May | 0.00 | 0.462209E+11 | 0.00 | 0.00 | 0.850463E+10 | 0.00 | 0.00 | 0.00 | 0.79 |
June | 0.00 | 0.479102E+11 | 0.00 | 0.00 | 0.821228E+10 | 0.00 | 0.00 | 0.00 | 0.82 |
July | 0.00 | 0.337300E+11 | 0.00 | 0.00 | 0.750791E+10 | 0.00 | 0.00 | 0.00 | 0.70 |
August | 0.00 | 0.449102E+11 | 0.00 | 0.00 | 0.658441E+10 | 0.00 | 0.00 | 0.00 | 0.75 |
September | 0.00 | 0.385769E+11 | 0.00 | 0.00 | 0.798775E+10 | 0.00 | 0.00 | 0.00 | 0.72 |
October | 0.00 | 0.350556E+11 | 0.00 | 0.00 | 0.803315E+10 | 0.00 | 0.00 | 0.00 | 0.65 |
November | 0.00 | 0.294198E+11 | 0.00 | 0.00 | 0.620315E+10 | 0.00 | 0.00 | 0.00 | 0.64 |
December | 1237327.19 | 0.236746E+11 | 0.00 | 67849.42 | 0.482867E+10 | 0.00 | 77030.72 | 0.00 | 0.62 |
Annual Sum or Average | 8156585.62 | 0.417117E+12 | 0.00 | 543738.62 | 0.800785E+11 | 0.00 | 1329724.17 | 0.00 | 0.73 |
Minimum of Months | 0.00 | 0.218563E+11 | 0.00 | 0.00 | 0.450083E+10 | 0.00 | 0.00 | 0.00 | 0.62 |
Maximum of Months | 6919258.42 | 0.479102E+11 | 0.00 | 475889.20 | 0.850463E+10 | 0.00 | 1252693.45 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 240901.93 | 0.217599E+10 | 0.00 | 19658.42 | 0.529183E+09 | 0.00 | 53763.45 | 0.00 | 0.43 |
February | 0.00 | 0.223262E+10 | 0.00 | 0.00 | 0.486658E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
March | 0.00 | 0.296630E+10 | 0.00 | 0.00 | 0.638396E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
April | 0.00 | 0.385984E+10 | 0.00 | 0.00 | 0.926308E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
May | 0.00 | 0.594214E+10 | 0.00 | 0.00 | 0.763850E+09 | 0.00 | 0.00 | 0.00 | 0.63 |
June | 0.00 | 0.665127E+10 | 0.00 | 0.00 | 0.690531E+09 | 0.00 | 0.00 | 0.00 | 0.70 |
July | 0.00 | 0.442717E+10 | 0.00 | 0.00 | 0.693942E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.501601E+10 | 0.00 | 0.00 | 0.744988E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
September | 0.00 | 0.425219E+10 | 0.00 | 0.00 | 0.890120E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
October | 0.00 | 0.368198E+10 | 0.00 | 0.00 | 0.915219E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
November | 0.00 | 0.304387E+10 | 0.00 | 0.00 | 0.694666E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
December | 0.00 | 0.227941E+10 | 0.00 | 0.00 | 0.621011E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 240901.93 | 0.465288E+11 | 0.00 | 19658.42 | 0.859487E+10 | 0.00 | 53763.45 | 0.00 | 0.53 |
Minimum of Months | 0.00 | 0.217599E+10 | 0.00 | 0.00 | 0.486658E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 240901.93 | 0.665127E+10 | 0.00 | 19658.42 | 0.926308E+09 | 0.00 | 53763.45 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 204679.79 | 0.199160E+10 | 0.00 | 31079.79 | 0.410407E+09 | 0.00 | 81574.38 | 0.00 | 0.60 |
February | 0.00 | 0.209497E+10 | 0.00 | 0.00 | 0.372310E+09 | 0.00 | 0.00 | 0.00 | 0.67 |
March | 0.00 | 0.275658E+10 | 0.00 | 0.00 | 0.506085E+09 | 0.00 | 0.00 | 0.00 | 0.76 |
April | 0.00 | 0.351107E+10 | 0.00 | 0.00 | 0.732832E+09 | 0.00 | 0.00 | 0.00 | 0.80 |
May | 0.00 | 0.429922E+10 | 0.00 | 0.00 | 0.764288E+09 | 0.00 | 0.00 | 0.00 | 0.74 |
June | 0.00 | 0.443159E+10 | 0.00 | 0.00 | 0.776901E+09 | 0.00 | 0.00 | 0.00 | 0.77 |
July | 0.00 | 0.301245E+10 | 0.00 | 0.00 | 0.712866E+09 | 0.00 | 0.00 | 0.00 | 0.65 |
August | 0.00 | 0.398574E+10 | 0.00 | 0.00 | 0.651607E+09 | 0.00 | 0.00 | 0.00 | 0.68 |
September | 0.00 | 0.364515E+10 | 0.00 | 0.00 | 0.684408E+09 | 0.00 | 0.00 | 0.00 | 0.68 |
October | 0.00 | 0.307838E+10 | 0.00 | 0.00 | 0.785003E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
November | 0.00 | 0.260077E+10 | 0.00 | 0.00 | 0.562759E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
December | 0.00 | 0.212367E+10 | 0.00 | 0.00 | 0.425038E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
Annual Sum or Average | 204679.79 | 0.375312E+11 | 0.00 | 31079.79 | 0.738450E+10 | 0.00 | 81574.38 | 0.00 | 0.67 |
Minimum of Months | 0.00 | 0.199160E+10 | 0.00 | 0.00 | 0.372310E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
Maximum of Months | 204679.79 | 0.443159E+10 | 0.00 | 31079.79 | 0.785003E+09 | 0.00 | 81574.38 | 0.00 | 0.80 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 234644.95 | 0.373806E+10 | 0.00 | 69126.84 | 0.275452E+09 | 0.00 | 131910.17 | 0.00 | 0.67 |
February | 0.00 | 0.342356E+10 | 0.00 | 0.00 | 0.333228E+09 | 0.00 | 0.00 | 0.00 | 0.66 |
March | 0.00 | 0.359279E+10 | 0.00 | 0.00 | 0.561317E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
April | 0.00 | 0.374606E+10 | 0.00 | 0.00 | 0.949860E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
May | 0.00 | 0.500890E+10 | 0.00 | 0.00 | 0.974187E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
June | 0.00 | 0.495302E+10 | 0.00 | 0.00 | 0.983553E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
July | 0.00 | 0.360943E+10 | 0.00 | 0.00 | 0.876415E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
August | 0.00 | 0.457321E+10 | 0.00 | 0.00 | 0.816332E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
September | 0.00 | 0.452553E+10 | 0.00 | 0.00 | 0.859342E+09 | 0.00 | 0.00 | 0.00 | 0.54 |
October | 0.00 | 0.473250E+10 | 0.00 | 0.00 | 0.702164E+09 | 0.00 | 0.00 | 0.00 | 0.55 |
November | 0.00 | 0.462568E+10 | 0.00 | 0.00 | 0.446090E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
December | 0.00 | 0.410759E+10 | 0.00 | 0.00 | 0.297672E+09 | 0.00 | 0.00 | 0.00 | 0.65 |
Annual Sum or Average | 234644.95 | 0.506363E+11 | 0.00 | 69126.84 | 0.807561E+10 | 0.00 | 131910.17 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.342356E+10 | 0.00 | 0.00 | 0.275452E+09 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 234644.95 | 0.500890E+10 | 0.00 | 69126.84 | 0.983553E+09 | 0.00 | 131910.17 | 0.00 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 240826.54 | 0.206523E+10 | 0.00 | 24167.96 | 0.473344E+09 | 0.00 | 60815.07 | 0.00 | 0.64 |
February | 0.00 | 0.218542E+10 | 0.00 | 0.00 | 0.441510E+09 | 0.00 | 0.00 | 0.00 | 0.70 |
March | 0.00 | 0.303567E+10 | 0.00 | 0.00 | 0.524182E+09 | 0.00 | 0.00 | 0.00 | 0.82 |
April | 0.00 | 0.379307E+10 | 0.00 | 0.00 | 0.772923E+09 | 0.00 | 0.00 | 0.00 | 0.86 |
May | 0.00 | 0.440568E+10 | 0.00 | 0.00 | 0.899477E+09 | 0.00 | 0.00 | 0.00 | 0.77 |
June | 0.00 | 0.456019E+10 | 0.00 | 0.00 | 0.858934E+09 | 0.00 | 0.00 | 0.00 | 0.80 |
July | 0.00 | 0.323335E+10 | 0.00 | 0.00 | 0.809551E+09 | 0.00 | 0.00 | 0.00 | 0.70 |
August | 0.00 | 0.424243E+10 | 0.00 | 0.00 | 0.709085E+09 | 0.00 | 0.00 | 0.00 | 0.73 |
September | 0.00 | 0.372811E+10 | 0.00 | 0.00 | 0.838711E+09 | 0.00 | 0.00 | 0.00 | 0.71 |
October | 0.00 | 0.327272E+10 | 0.00 | 0.00 | 0.933732E+09 | 0.00 | 0.00 | 0.00 | 0.65 |
November | 0.00 | 0.279768E+10 | 0.00 | 0.00 | 0.643766E+09 | 0.00 | 0.00 | 0.00 | 0.63 |
December | 0.00 | 0.223207E+10 | 0.00 | 0.00 | 0.558881E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
Annual Sum or Average | 240826.54 | 0.395516E+11 | 0.00 | 24167.96 | 0.846410E+10 | 0.00 | 60815.07 | 0.00 | 0.72 |
Minimum of Months | 0.00 | 0.206523E+10 | 0.00 | 0.00 | 0.441510E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
Maximum of Months | 240826.54 | 0.456019E+10 | 0.00 | 24167.96 | 0.933732E+09 | 0.00 | 60815.07 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.735683E+09 | 0.00 | 146776.48 | 0.00 | 0.00 | 115043.81 | 0.00 | 0.59 |
February | 0.00 | 0.810123E+09 | 0.00 | 11107.25 | 0.00 | 0.00 | 11893.50 | 0.00 | 0.59 |
March | 0.00 | 0.105855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
April | 0.00 | 0.136137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
May | 0.00 | 0.148625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.154266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.119194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
August | 0.00 | 0.153158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.125710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.130529E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
November | 0.00 | 0.113137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
December | 0.00 | 0.946127E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Annual Sum or Average | 0.00 | 0.143581E+11 | 0.00 | 157883.74 | 0.00 | 0.00 | 126937.31 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.735683E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Maximum of Months | 0.00 | 0.154266E+10 | 0.00 | 146776.48 | 0.00 | 0.00 | 115043.81 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.722409E+10 | 0.00 | 1376743.24 | 0.00 | 0.00 | 2081452.50 | 0.00 | 0.59 |
February | 0.00 | 0.805755E+10 | 0.00 | 102884.02 | 0.00 | 0.00 | 133424.39 | 0.00 | 0.59 |
March | 0.00 | 0.105586E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
April | 0.00 | 0.136571E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
May | 0.00 | 0.145985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.153325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.118840E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
August | 0.00 | 0.153359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.123160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.129631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
November | 0.00 | 0.112827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
December | 0.00 | 0.947123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Annual Sum or Average | 0.00 | 0.142681E+12 | 0.00 | 1479627.27 | 0.00 | 0.00 | 2214876.89 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.722409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Maximum of Months | 0.00 | 0.153359E+11 | 0.00 | 1376743.24 | 0.00 | 0.00 | 2081452.50 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.722368E+09 | 0.00 | 134865.14 | 0.00 | 0.00 | 265761.85 | 0.00 | 0.59 |
February | 0.00 | 0.805273E+09 | 0.00 | 10214.55 | 0.00 | 0.00 | 13828.25 | 0.00 | 0.59 |
March | 0.00 | 0.105515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
April | 0.00 | 0.136638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
May | 0.00 | 0.146452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
June | 0.00 | 0.153379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
July | 0.00 | 0.118758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
August | 0.00 | 0.153461E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.123514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.129575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
November | 0.00 | 0.112716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
December | 0.00 | 0.946028E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Annual Sum or Average | 0.00 | 0.142737E+11 | 0.00 | 145079.69 | 0.00 | 0.00 | 279590.09 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.722368E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Maximum of Months | 0.00 | 0.153461E+10 | 0.00 | 134865.14 | 0.00 | 0.00 | 265761.85 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.173844E+11 | 0.00 | 1787832.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
February | 0.00 | 0.180260E+11 | 0.00 | 483709.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
March | 0.00 | 0.230845E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
April | 0.00 | 0.298031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
May | 0.00 | 0.346861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
June | 0.00 | 0.344838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
July | 0.00 | 0.260688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
August | 0.00 | 0.334837E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
September | 0.00 | 0.295085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
October | 0.00 | 0.292351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
November | 0.00 | 0.247529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
December | 0.00 | 0.204007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
Annual Sum or Average | 0.00 | 0.320918E+12 | 0.00 | 2271541.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
Minimum of Months | 0.00 | 0.173844E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
Maximum of Months | 0.00 | 0.346861E+11 | 0.00 | 1787832.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:43
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.410198E+12 | -0.501488E+10 | 0.00 | -0.100962E+13 | 0.310604E+13 |
February | 0.400790E+12 | -0.546479E+10 | 0.00 | -0.101001E+13 | 0.331287E+13 |
March | 0.533351E+12 | -0.105820E+11 | 0.00 | -0.127136E+13 | 0.427136E+13 |
April | 0.534884E+12 | -0.113811E+11 | 0.00 | -0.172051E+13 | 0.469547E+13 |
May | 0.530229E+12 | -0.139390E+11 | 0.00 | -0.210480E+13 | 0.381809E+13 |
June | 0.545376E+12 | -0.132798E+11 | 0.00 | -0.204706E+13 | 0.423037E+13 |
July | 0.449523E+12 | -0.748996E+10 | 0.00 | -0.143968E+13 | 0.420965E+13 |
August | 0.572991E+12 | -0.121799E+11 | 0.00 | -0.187778E+13 | 0.489291E+13 |
September | 0.450131E+12 | -0.836362E+10 | 0.00 | -0.174747E+13 | 0.339821E+13 |
October | 0.496506E+12 | -0.807180E+10 | 0.00 | -0.164814E+13 | 0.377963E+13 |
November | 0.398189E+12 | -0.587488E+10 | 0.00 | -0.136779E+13 | 0.399253E+13 |
December | 0.384734E+12 | -0.489182E+10 | 0.00 | -0.112456E+13 | 0.435168E+13 |
Annual Sum or Average | 0.570690E+13 | -0.106534E+12 | 0.00 | -0.183688E+14 | 0.480588E+14 |
Minimum of Months | 0.384734E+12 | -0.139390E+11 | 0.00 | -0.210480E+13 | 0.310604E+13 |