Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:25
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Simulation Timestamp: 2024-07-03 12:25:28
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:28
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 29067.62 | 627.53 | 627.53 |
Net Site Energy | 29067.62 | 627.53 | 627.53 |
Total Source Energy | 90310.63 | 1949.70 | 1949.70 |
Net Source Energy | 90310.63 | 1949.70 | 1949.70 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 838.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2005.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3223.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 351.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2566.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2470.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 421.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 764.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5124.04 |
Humidification | 1276.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.71 |
Heat Recovery | 46.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 426.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 28229.16 | 838.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7878.92 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 838.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 2005.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3223.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 351.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 55.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2505.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2470.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 421.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 764.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5124.04 |
Humidification | General | 1276.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.71 |
Heat Recovery | General | 46.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 426.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 838.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 2005.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3223.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 351.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 2566.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2470.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 421.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 764.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5124.04 |
Humidification | Unassigned | 1276.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.71 |
Heat Recovery | Unassigned | 46.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 426.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 77.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 159.00 | 18.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Other | 373.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 609.43 | 18.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 77.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 159.00 | 18.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Other | 373.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 609.43 | 18.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 28229.158 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 28229.158 | 100.00 |
Total On-Site and Utility Electric Sources | 28229.158 | 100.00 |
Total Electricity End Uses | 28229.158 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 468.52 | 36.05 |
Air to Air Heat Recovery for Heating | 831.09 | 63.95 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 1299.61 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 7878.92 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 7878.92 | 100.00 |
Total Water End Uses | 7878.92 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 28.83 |
Time Setpoint Not Met During Occupied Cooling | 1711.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5942.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:28
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:25 |
RunPeriod | RUNPERIOD 1 |
Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Latitude [deg] | 40.65 |
Longitude [deg] | -73.8 |
Elevation [m] | 5.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 8.6849 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 8.6849 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 8.7339 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 8.7339 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.6849 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 8.6849 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 8.6849 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 8.6849 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 8.6849 | 18.58 | 484.4232 | |
Total | 46320.38 | 8.7339 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 8.7339 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.6845 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:28
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-AUG-14:09 | 02-JAN-05:10 | - | - | - | - | - | - | - | - | - | - | 30-AUG-15:00 |
Heating | 0.00 | 1710520.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 432665.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 280450.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 233151.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 245878.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 53427.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 91748.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 23299.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2144607.52 | 1710520.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1710520.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 432665.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 280450.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3430.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 112.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 245878.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 53427.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 91748.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 23299.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:28
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 908.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6351.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 10208.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1113.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8128.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7823.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1335.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2422.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 4041.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 146.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1350.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 89401.74 | 908.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 19.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 137.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 220.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 24.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 168.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 28.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 52.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 87.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 3.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 29.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1930.07 | 19.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 19.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 137.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 220.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 24.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 168.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 28.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 52.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 87.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 3.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 29.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1930.07 | 19.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:28
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 5.54 | 0.382100 | 0.000000 | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.85 | 0.325315 | 0.332000 | 1.94 | 0.867508 | 0.500000 | 0.001171 | 0.000171 | 1.94 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 55.05 | 0.345521 | 0.346000 | 19.05 | 0.921389 | 0.500000 | 0.001103 | 0.004014 | 19.05 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.60 | 0.339685 | 0.348000 | 1.95 | 0.905827 | 0.500000 | 0.001122 | 0.000744 | 2.53 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.01 | 0.237448 | 0.242000 | 0.243399 | 0.633194 | 0.500000 | 0.001605 | 0.000119 | 0.405263 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.23 | 0.124819 | 0.200000 | 0.246604 | 0.332852 | 0.500000 | 0.003052 | 0.000082 | 0.278702 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.43 | 0.166698 | 0.200000 | 0.286538 | 0.444527 | 0.500000 | 0.002286 | 0.000135 | 0.460348 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.50 | 0.102407 | 0.200000 | 0.300575 | 0.300000 | 0.500000 | 0.003720 | 0.000070 | 0.300575 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 9.46 | 0.252343 | 0.253000 | 2.39 | 0.672914 | 0.500000 | 0.001510 | 0.002029 | 6.92 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 13.08 | 0.117634 | 0.200000 | 2.62 | 0.313690 | 0.500000 | 0.003239 | 0.001330 | 4.54 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 14.06 | 0.169846 | 0.200000 | 2.81 | 0.452921 | 0.500000 | 0.002243 | 0.002003 | 6.83 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 13.59 | 0.113223 | 0.200000 | 2.72 | 0.301927 | 0.500000 | 0.003365 | 0.001286 | 4.39 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.07 | 0.223039 | 0.228000 | 0.244133 | 0.594770 | 0.500000 | 0.001708 | 0.000257 | 0.875614 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.33 | 0.115655 | 0.200000 | 0.266145 | 0.308413 | 0.500000 | 0.003294 | 0.000168 | 0.571765 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.52 | 0.156878 | 0.200000 | 0.304473 | 0.418342 | 0.500000 | 0.002429 | 0.000254 | 0.866108 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.44 | 0.106773 | 0.200000 | 0.288286 | 0.300000 | 0.500000 | 0.003568 | 0.000165 | 0.561833 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | User-Specified Rated Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 19535.55 | 0.000171 | 393.82 | |
CORE_MID VAV BOX REHEAT COIL | 458792.70 | 0.004014 | 10741.88 | |
CORE_TOP VAV BOX REHEAT COIL | 85045.32 | 0.000744 | 2245.43 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 13595.85 | 0.000119 | 358.74 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 9348.48 | 0.000082 | 246.65 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 15440.41 | 0.000135 | 407.37 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 8018.44 | 0.000070 | 193.65 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 231957.00 | 0.002029 | 6116.92 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 151996.27 | 0.001330 | 4008.22 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 228993.17 | 0.002003 | 6038.83 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 146948.73 | 0.001286 | 3875.20 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 29325.94 | 0.000257 | 773.21 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 19148.99 | 0.000168 | 504.88 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 29008.03 | 0.000254 | 764.83 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 18816.67 | 0.000165 | 496.12 | |
VAV_BOT WITH REHEAT HEATING COIL | 72691.36 | 0.000636 | 1168.21 | |
VAV_MID WITH REHEAT HEATING COIL | 704619.56 | 0.006164 | 11283.58 | |
VAV_TOP WITH REHEAT HEATING COIL | 69646.21 | 0.000609 | 1125.67 | |
CAV_BAS HEATING COIL | 283681.44 | 0.000875 | 2622.73 | 100000.00 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.481492 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.61 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.469171 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 24.55 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.51 | 3.02 | 11.02 | 3.02 | 9.78 | 9.78 | 0.300000 | 0.308509 | 9.78 |
VAV_MID WITH REHEAT | 52.63 | 29.59 | 105.25 | 33.94 | 91.78 | 91.78 | 0.300000 | 0.369775 | 91.78 |
VAV_TOP WITH REHEAT | 5.48 | 3.05 | 10.96 | 5.41 | 9.91 | 9.91 | 0.300000 | 0.545681 | 9.91 |
CAV_BAS | 0.000000 | 0.000000 | 5.54 | 1.20 | 5.54 | 5.54 | 1.00 | 0.216524 | 5.54 |
AIRLOOP DATACENTER BASEMENT | 24.55 | 24.55 | 24.55 | 24.55 | 24.55 | 24.55 | 1.00 | 0.999990 | 24.55 |
AIRLOOP DATACENTER BOT | 0.481492 | 0.481492 | 0.481492 | 0.481492 | 0.481492 | 0.481492 | 1.00 | 1.00 | 0.481492 |
AIRLOOP DATACENTER MID | 4.61 | 4.61 | 4.61 | 4.61 | 4.61 | 4.61 | 1.00 | 1.00 | 4.61 |
AIRLOOP DATACENTER TOP | 0.469171 | 0.469171 | 0.469171 | 0.469171 | 0.469171 | 0.469171 | 1.00 | 1.00 | 0.469171 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.78 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 91.78 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 9.91 | |
CAV_BAS_OA_CONTROLLER | 5.54 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 24.55 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.481492 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.61 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.469171 | 0.015632 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT OA HEAT RECOVERY | 2.54 |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 25.38 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.54 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 26.18 | 6.67 | 10.96 | 0.010275 | 0.008500 | 236261.70 | 0.006757 | 9.78 |
VAV_MID WITH REHEAT COOLING COIL | 26.39 | 6.67 | 10.95 | 0.010465 | 0.008500 | 2295270.17 | 0.065644 | 91.78 |
VAV_TOP WITH REHEAT COOLING COIL | 26.07 | 6.67 | 10.96 | 0.010228 | 0.008500 | 236537.64 | 0.006765 | 9.91 |
CAV_BAS COOLING COIL | 24.67 | 6.67 | 11.03 | 0.010075 | 0.008500 | 119609.82 | 0.003421 | 5.54 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.78 |
VAV_MID WITH REHEAT FAN | 91.78 |
VAV_TOP WITH REHEAT FAN | 9.91 |
CAV_BAS FAN | 5.54 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.006757 | 0.000070 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000636 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.065644 | 0.000007 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.006164 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.006765 | 0.000070 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000609 | |
CAV_BAS_COOLC_CONTROLLER | 0.003421 | 0.000139 |
CAV_BAS_HEATC_CONTROLLER | 0.000875 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 24.55 | 495428.02 | 358142.92 | 0.012133 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.481492 | 9681.44 | 7007.91 | 0.000237 |
AIRLOOP DATACENTER MID COOLING COIL | 4.61 | 92791.35 | 67103.48 | 0.002272 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.469171 | 9446.25 | 6832.79 | 0.000231 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 24.55 | 24.55 | 24.55 | 24.55 | 495428.02 | 495428.02 | 20749.82 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.481492 | 0.481492 | 0.481492 | 0.481492 | 9681.44 | 9681.44 | 958.56 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.61 | 4.61 | 4.61 | 4.61 | 92791.35 | 92791.35 | 9585.56 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.469171 | 0.469171 | 0.469171 | 0.469171 | 9446.25 | 9446.25 | 958.56 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 24.55 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.481492 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.61 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.469171 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 24.55 | 495428.02 | 0.012133 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.481492 | 9681.44 | 0.000237 |
AIRLOOP DATACENTER MID HEATING COIL | 4.61 | 92791.35 | 0.002272 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.469171 | 9446.25 | 0.000231 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 20749.82 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 958.56 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 9585.56 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 958.56 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000199 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.082587 | 13483.98 | |
HEATSYS1 PUMP | 0.021109 | 6357.21 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.082587 | 9.91 |
HEATSYS1 | 0.021109 | 2.53 |
COOLSYS1_SUPPLY | 0.082587 | 9.91 |
SINGLE WATER PLANT LOOP | 0.014874 | 1.78 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.082587 | 0.082587 | 346660.18 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2412928.69 | 2412928.69 | 0.021109 |
CENTRAL BOILER | 612676.76 | 600654.06 | 0.014874 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.041294 | 4667.71 |
COOLSYS1 CHILLER2 PUMP | 0.041294 | 4667.71 |
PLANT CIRC PUMP | 0.014874 | 3793.59 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.082587 | 0.041450 | 1449307.13 | 1449307.95 | 0.072804 |
COOLSYS1 CHILLER2 | 0.082587 | 0.041450 | 1449307.13 | 1449307.95 | 0.072804 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | U-factor Times Area Value at High Fan Speed [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/K] | |
CENTRAL TOWER | 0.014874 | 147686.70 | 74763.17 | 73843.35 | 7879.72 | 44857.90 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.145608 | 17.47 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.145608 | 36049.41 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 55.95 | 1734852.22 | 11.19 | 216856.53 |
TOWERWATERSYS COOLTOWER 2 | 55.95 | 1734852.22 | 11.19 | 216856.53 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.075158 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:28
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:28
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:28
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 14.00 | 7.30 | 3.30 | 1.20 | -0.20 | 5.60 | 10.90 | 16.10 | 21.70 | 25.00 | 24.80 | 19.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 | 40.65 | -73.80 | -5.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 12.47 | 25.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 8.685 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 13.527 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 8.685 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 493.108 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 24139.153 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 24139.153 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 6806.209 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6806.209 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.075 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.028 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.266 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7632 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8055 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6228 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | -0.34463022E-15 | 0.36894385E-16 | -0.14288780E-09 | 0.12757077E-17 |
51 | 8 | 0.20913840E-07 | 0.14359092E-12 | 0.36762620E-03 | -0.23779757E-09 |
52 | 7 | -0.11937955E-01 | 0.75343451E-08 | -0.22648608E-01 | 0.13573889E-03 |
53 | 6 | 0.39710065 | 0.26364580E-05 | 0.46505929 | -0.46505182E-02 |
54 | 5 | -5.1100523 | 0.98937734E-04 | -4.3872286 | 0.62185548E-01 |
55 | 4 | 32.646709 | 0.81302423E-03 | 21.229086 | -0.41739428 |
56 | 3 | -110.46842 | 0.17791168E-02 | -55.206350 | 1.5042464 |
57 | 2 | 196.38009 | 0.10043743E-02 | 77.491871 | -2.8887901 |
58 | 1 | -170.88709 | 0.10757908E-03 | -55.143519 | 2.7407251 |
59 | 0 | 57.057407 | 0.61468164E-06 | 15.577169 | |
60 | 9 | -0.22955380E-15 | 0.37743381E-16 | -0.14509256E-09 | 0.32676096E-18 |
61 | 8 | 0.21224167E-07 | 0.13772622E-12 | 0.37092755E-03 | -0.24132609E-09 |
62 | 7 | -0.12036605E-01 | 0.72012381E-08 | -0.22790691E-01 | 0.13686058E-03 |
63 | 6 | 0.39978134 | 0.25163753E-05 | 0.46734577 | -0.46821170E-02 |
64 | 5 | -5.1362151 | 0.94318005E-04 | -4.4048053 | 0.62509952E-01 |
65 | 4 | 32.762449 | 0.77422319E-03 | 21.297824 | -0.41893096 |
66 | 3 | -110.71472 | 0.16925811E-02 | -55.342260 | 1.5078047 |
67 | 2 | 196.62425 | 0.95470525E-03 | 77.616458 | -2.8926672 |
68 | 1 | -170.97729 | 0.10217823E-03 | -55.179630 | 2.7423060 |
69 | 0 | 57.057407 | 0.58332056E-06 | 15.571109 | |
70 | 9 | 0.11276195E-14 | 0.47405760E-16 | -0.13382366E-09 | -0.64614724E-17 |
71 | 8 | 0.19634610E-07 | 0.16705312E-12 | 0.35383761E-03 | -0.22325229E-09 |
72 | 7 | -0.11525316E-01 | 0.88979655E-08 | -0.22054087E-01 | 0.13104703E-03 |
73 | 6 | 0.38588679 | 0.31323747E-05 | 0.45547913 | -0.45183345E-02 |
74 | 5 | -5.0005974 | 0.11815564E-03 | -4.3135163 | 0.60828376E-01 |
75 | 4 | 32.162433 | 0.97545471E-03 | 20.940665 | -0.41096462 |
76 | 3 | -109.43770 | 0.21433374E-02 | -54.636007 | 1.4893559 |
77 | 2 | 195.35810 | 0.12144036E-02 | 76.969321 | -2.8725616 |
78 | 1 | -170.50942 | 0.13051365E-03 | -54.992579 | 2.7341060 |
79 | 0 | 57.057407 | 0.74839837E-06 | 15.602923 | |
80 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
81 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
82 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
83 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
84 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
85 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
86 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
87 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
88 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
89 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
90 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
91 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
92 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
93 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
94 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
95 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
96 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
97 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
98 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
99 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
100 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
101 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
102 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
103 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
104 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
105 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
106 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
107 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
108 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
109 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
110 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
111 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
112 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
113 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
114 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
115 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
116 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
117 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
118 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
119 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
120 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
121 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
122 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
123 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
124 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
125 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
126 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
127 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.38_SHGC_EAST_0.36 | 35 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.361 | ||
2 | WINDOW_U_0.38_SHGC_SOUTH_0.36 | 36 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.361 | ||
3 | WINDOW_U_0.38_SHGC_WEST_0.36 | 37 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.361 | ||
4 | WINDOW_U_0.38_SHGC_NORTH_0.36 | 38 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.361 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.45900E-002 | 0.27318 | 0.51781 | 0.51781 | 0.39600 | 0.13802 | 0.18068 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.45900E-002 | 0.27318 | 0.51781 | 0.51781 | 0.39600 | 0.13802 | 0.18068 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.45900E-002 | 0.27318 | 0.51781 | 0.51781 | 0.39600 | 0.13802 | 0.18068 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.45900E-002 | 0.27318 | 0.51781 | 0.51781 | 0.39600 | 0.13802 | 0.18068 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 1.973E-005 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.3745E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.3766E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9703E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.9721E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5379E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5393E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4985E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4993E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.4228E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.5664E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.0111E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.1367E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5729E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6767E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5191E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5715E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1583 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.6154E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1788 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.5424E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1118 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4272E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5151E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5705E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.4255E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.5790E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.0138E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.1498E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5752E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6856E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.5196E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.5730E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.3742E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.3764E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.9701E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.9719E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5377E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5392E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.4984E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.4992E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.4675E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.7551E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.1759E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.4894E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.9696E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.0962E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2719E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.3081E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.0194E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.9411E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.5598E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6429E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8978E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.4451E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.7010E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7586E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3802E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.4814E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.0630E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.1362E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.9292E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.9574E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2720E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.3086E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5946E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5966E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2039E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2055E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9517E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9529E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4986E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4993E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6399E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7574E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2406E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3333E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9813E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0471E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5197E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5731E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.1428E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1860E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1712E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6525E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8635E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1156E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.5151E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5700E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6386E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7547E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2393E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3301E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9795E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0416E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5192E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5716E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5945E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5965E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2038E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2053E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9516E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9528E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4985E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4992E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2272E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.3294E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.8719E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.9457E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.8057E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.8333E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2721E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.3087E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7529E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.8360E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2295E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.5124E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6697E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3547E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7010E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.7586E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3093E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.5771E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9784E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.2667E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.8452E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.9684E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2719E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.3080E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1540 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1044 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1680 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1157 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1227 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.5382E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.5293E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.7353E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.1872E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.2492E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.6734E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.8841E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.0064E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.6215E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.6709E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7667E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.1523E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.4348E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.0516E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.7061E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.7145E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.0342E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.5293E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.7348E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.8857E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.1040E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.2994E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.7034E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.7509E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.5012E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.6709E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.7667E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1541 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1046 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1681 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1160 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1229 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.5545E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.5412E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.7413E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.1922E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.2556E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.6790E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.8902E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.0174E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.6292E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.6828E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7727E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.1527E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.4387E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.0524E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.7091E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.7204E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.0379E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.5412E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.7409E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.8902E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.1101E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.3044E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.7091E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.7613E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.5085E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.6828E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.7727E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 76953.58096 | 76953.58096 | 5.54285 | 5.54285 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.41098E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:10:00 | -10.70000 | 1.50390E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 81176.92263 | 81176.92263 | 5.84677 | 5.84677 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.41098E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | -10.70000 | 1.50390E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 764496.37691 | 764496.37691 | 55.04859 | 55.04859 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.41098E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 267105.16573 | 267105.16573 | 11.25946 | 11.25946 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 77754.42811 | 77754.42811 | 5.59943 | 5.59943 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.41098E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 59567.28863 | 59567.28863 | 2.53160 | 2.53160 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 13836.31552 | 13836.31552 | 1.00578 | 1.00578 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 32.10000 | 1.41196E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 9522.45172 | 9522.45172 | 0.40526 | 0.40526 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 16962.57217 | 16962.57217 | 1.23302 | 1.23302 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 27.79567 | 1.41119E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 6546.85218 | 6546.85218 | 0.27870 | 0.27870 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 19709.27710 | 19709.27710 | 1.43269 | 1.43269 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 31.73000 | 1.41190E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 10812.06304 | 10812.06304 | 0.46035 | 0.46035 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 20674.99836 | 20674.99836 | 1.50288 | 1.50288 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 31.36000 | 1.41183E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 4999.45278 | 4999.45278 | 0.21251 | 0.21251 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 130191.40620 | 130191.40620 | 9.46413 | 9.46413 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 32.10000 | 1.41196E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 162362.73058 | 162362.73058 | 6.92298 | 6.92298 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 179981.12412 | 179981.12412 | 13.08340 | 13.08340 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 28.23967 | 1.41127E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 106391.79596 | 106391.79596 | 4.53664 | 4.53664 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 193433.30255 | 193433.30255 | 14.06135 | 14.06135 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 31.79167 | 1.41191E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 160290.69120 | 160290.69120 | 6.83436 | 6.83436 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 186993.00732 | 186993.00732 | 13.59312 | 13.59312 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.41181E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 102862.76083 | 102862.76083 | 4.38575 | 4.38575 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 14729.49342 | 14729.49342 | 1.07076 | 1.07076 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 32.10000 | 1.41196E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 20523.71452 | 20523.71452 | 0.87561 | 0.87561 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 18305.80891 | 18305.80891 | 1.33073 | 1.33073 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 28.23967 | 1.41127E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 13401.37978 | 13401.37978 | 0.57176 | 0.57176 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 20941.94668 | 20941.94668 | 1.52236 | 1.52236 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 31.85333 | 1.41192E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 20301.43698 | 20301.43698 | 0.86611 | 0.86611 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 19828.69265 | 19828.69265 | 1.44143 | 1.44143 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.41181E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 13168.99790 | 13168.99790 | 0.56183 | 0.56183 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8398.15365 | 8398.15365 | 0.48149 | 0.48149 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 29.58400 | 1.41151E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | -10.70000 | 1.50390E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 80348.93163 | 80348.93163 | 4.60668 | 4.60668 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 29.58400 | 1.41151E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -10.70000 | 1.50390E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8183.21358 | 8183.21358 | 0.46917 | 0.46917 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 29.76900 | 1.41154E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -10.70000 | 1.50390E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 372315.69715 | 428163.05172 | 21.34570 | 24.54756 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 25.36600 | 1.41076E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -10.70000 | 1.50390E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 152495.20 | 9.78332 | 9.78332 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 69197.25 | 2.43465 | 2.43465 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1411073.33 | 91.78347 | 91.78347 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 716501.82 | 33.93920 | 33.93920 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 159070.46 | 9.90856 | 9.90856 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 72139.30 | 5.40691 | 5.40691 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 |
7 | CAV_BAS | Cooling | Sensible | 79268.41 | 5.54285 | 5.54285 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 73592.09 | 1.20016 | 1.20016 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 423177.10 | 24.54781 | 24.54781 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 20749.82 | 0.33839 | 0.33839 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8317.17 | 0.48149 | 0.48149 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 958.56 | 1.56323E-002 | 1.56323E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 79595.32 | 4.60668 | 4.60668 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 9585.56 | 0.15632 | 0.15632 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8109.06 | 0.46917 | 0.46917 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 958.56 | 1.56323E-002 | 1.56323E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 5.54285 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.38210 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.00000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 0.00000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.84677 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32532 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33200 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.94113 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.86751 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.17117E-003 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.70905E-004 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.94113 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
16 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19535.54630 |
17 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.70905E-004 |
18 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 393.82128 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 55.04859 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34552 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34600 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 19.04681 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.92139 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.10268E-003 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.01372E-003 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 19.04681 |
28 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
30 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 458792.70172 |
31 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.01372E-003 |
32 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 10741.88112 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.59943 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33969 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34800 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.94860 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.90583 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.12163E-003 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.44014E-004 |
41 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.53160 |
42 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
43 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
44 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 85045.32349 |
45 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.44014E-004 |
46 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2245.42608 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.00578 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23745 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24200 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24340 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.63319 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.60456E-003 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.18942E-004 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.40526 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
58 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13595.84662 |
59 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.18942E-004 |
60 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 358.74457 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.23302 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12482 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24660 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33285 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.05241E-003 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.17846E-005 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.27870 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
72 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9348.47972 |
73 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.17846E-005 |
74 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 246.65436 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.43269 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16670 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28654 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44453 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.28557E-003 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.35079E-004 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.46035 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
86 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15440.41241 |
87 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.35079E-004 |
88 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 407.37466 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.50288 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10241 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.30058 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.72045E-003 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.01488E-005 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.30058 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
100 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8018.43619 |
101 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.01488E-005 |
102 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 193.65420 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.46413 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25234 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25300 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.39443 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.67291 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.50985E-003 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.02926E-003 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.92298 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
114 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 231956.99723 |
115 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.02926E-003 |
116 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6116.91969 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.08340 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11763 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.61668 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31369 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.23886E-003 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.32973E-003 |
125 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.53664 |
126 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
128 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 151996.27422 |
129 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.32973E-003 |
130 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4008.21547 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.06135 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16985 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.81227 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45292 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.24321E-003 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.00333E-003 |
139 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.83436 |
140 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
142 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 228993.17443 |
143 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.00333E-003 |
144 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6038.82619 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.59312 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11322 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.71862 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30193 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.36505E-003 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.28557E-003 |
153 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.38575 |
154 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
156 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 146948.73034 |
157 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.28557E-003 |
158 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3875.20286 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.07076 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22304 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22800 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24413 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59477 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.70822E-003 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.56556E-004 |
167 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.87561 |
168 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
170 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 29325.94361 |
171 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.56556E-004 |
172 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 773.20985 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.33073 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11565 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26615 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30841 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.29428E-003 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.67524E-004 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.57176 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
184 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19148.99276 |
185 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.67524E-004 |
186 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 504.87786 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.52236 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15688 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.30447 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41834 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.42863E-003 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.53775E-004 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.86611 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
198 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 29008.02648 |
199 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.53775E-004 |
200 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 764.83310 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.44143 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10677 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28829 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.56833E-003 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.64616E-004 |
209 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.56183 |
210 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
211 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
212 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18816.67223 |
213 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.64616E-004 |
214 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 496.11975 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.48149 |
216 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.60668 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.46917 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 24.54756 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.51057 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.01824 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.02114 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.01824 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.78332 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.78332 |
225 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
226 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.30851 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 52.62529 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 29.58881 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 105.25058 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 33.93920 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 91.78347 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 91.78347 |
233 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
234 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.36977 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.48235 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.05164 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.96471 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 5.40691 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.90856 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.90856 |
241 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
242 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.54568 |
243 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.00000 |
244 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.00000 |
245 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.54285 |
246 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 1.20016 |
247 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.54285 |
248 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.54285 |
249 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
250 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.21652 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 24.54756 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 24.54756 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 24.54756 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 24.54756 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 24.54781 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 24.54781 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.48149 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.48149 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.48149 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.48149 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.48149 |
264 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.48149 |
265 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
266 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.60668 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.60668 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.60668 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.60668 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.60668 |
272 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.60668 |
273 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
274 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.46917 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.46917 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.46917 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.46917 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.46917 |
280 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.46917 |
281 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
282 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
283 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.78332 |
284 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 91.78347 |
285 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.90856 |
286 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.54285 |
287 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 24.54781 |
288 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.48149 |
289 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.60668 |
290 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.46917 |
291 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.78332 |
292 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_BOT WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.18088 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.95679 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.02752E-002 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
298 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 236261.69512 |
299 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.75705E-003 |
300 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.78332 |
301 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 72691.36046 |
302 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.35936E-004 |
303 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1168.20570 |
304 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.78332 |
305 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.75705E-003 |
306 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.04731E-005 |
307 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.35936E-004 |
308 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 91.78347 |
309 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 25.38195 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.39450 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.94758 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.04653E-002 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
315 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2295270.17217 |
316 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.56444E-002 |
317 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 91.78347 |
318 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 704619.55780 |
319 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.16432E-003 |
320 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 11283.58213 |
321 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 91.78347 |
322 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.56444E-002 |
323 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.25409E-006 |
324 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.16432E-003 |
325 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.90856 |
326 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.07375 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.95663 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.02278E-002 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
332 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 236537.64027 |
333 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.76495E-003 |
334 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.90856 |
335 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 69646.21133 |
336 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.09295E-004 |
337 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1125.67408 |
338 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.90856 |
339 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.76495E-003 |
340 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.03909E-005 |
341 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.09295E-004 |
342 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.54285 |
343 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.67121 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.03461 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.00748E-002 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
349 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 119609.82166 |
350 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.42083E-003 |
351 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.54285 |
352 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 283681.44324 |
353 | Coil:Heating:Water | CAV_BAS HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
354 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
355 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2622.72740 |
356 | Fan:VariableVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.54285 |
357 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.42083E-003 |
358 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.39203E-004 |
359 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.74844E-004 |
360 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 24.54781 |
361 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
362 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.54781 |
363 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 495428.01874 |
364 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 358142.91956 |
365 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.21330E-002 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 24.54781 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 24.54781 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 24.54781 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 24.54781 |
370 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 495428.01874 |
371 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 495428.01874 |
372 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 20749.82071 |
373 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
374 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 24.54781 |
375 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.54781 |
376 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 495428.01874 |
377 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.21330E-002 |
378 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 20749.82071 |
379 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.99035E-004 |
380 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
381 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
382 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
383 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.48149 |
384 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
385 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48149 |
386 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9681.43786 |
387 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 7007.90896 |
388 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.37098E-004 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.48149 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.48149 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.48149 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.48149 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9681.43786 |
394 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9681.43786 |
395 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 958.55576 |
396 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
397 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.48149 |
398 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48149 |
399 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9681.43786 |
400 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.37098E-004 |
401 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 958.55576 |
402 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.60668 |
403 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
404 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.60668 |
405 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 92791.34674 |
406 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 67103.47501 |
407 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.27245E-003 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.60668 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.60668 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.60668 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.60668 |
412 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 92791.34674 |
413 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 92791.34674 |
414 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 9585.55755 |
415 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
416 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.60668 |
417 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.60668 |
418 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 92791.34674 |
419 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.27245E-003 |
420 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 9585.55755 |
421 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.46917 |
422 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
423 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46917 |
424 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9446.24770 |
425 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6832.79196 |
426 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.31338E-004 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.46917 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.46917 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.46917 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.46917 |
431 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9446.24770 |
432 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9446.24770 |
433 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 958.55576 |
434 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
435 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.46917 |
436 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46917 |
437 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9446.24770 |
438 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.31338E-004 |
439 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 958.55576 |
440 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 8.25873E-002 |
441 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 13483.97650 |
442 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 8.25873E-002 |
443 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 9.91047 |
444 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 8.25873E-002 |
445 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 8.25873E-002 |
446 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 346660.18358 |
447 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
448 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.11094E-002 |
449 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 2.53312 |
450 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.11094E-002 |
451 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 6357.21004 |
452 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
453 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2412928.68734 |
454 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 2412928.69000 |
455 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.11094E-002 |
456 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 8.25873E-002 |
457 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 9.91047 |
458 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 4.12936E-002 |
459 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 4667.70583 |
460 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 4.12936E-002 |
461 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 4667.70583 |
462 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 8.25873E-002 |
463 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.14500E-002 |
464 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1449307.12910 |
465 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1449307.95000 |
466 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 7.28042E-002 |
467 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 8.25873E-002 |
468 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.14500E-002 |
469 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1449307.12910 |
470 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1449307.95000 |
471 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 7.28042E-002 |
472 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.48739E-002 |
473 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.78487 |
474 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.48739E-002 |
475 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3793.58580 |
476 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.48739E-002 |
477 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 147686.69541 |
478 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at High Fan Speed [W/K] | 74763.16934 |
479 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 73843.34771 |
480 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
481 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/K] | 44857.90161 |
482 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 612676.76123 |
483 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 600654.06000 |
484 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.48739E-002 |
485 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
486 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
487 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
488 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
489 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
490 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.14561 |
491 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 17.47300 |
492 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.14561 |
493 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 36049.40525 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 55.95450 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1734852.22167 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 11.19090 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 216856.52771 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 55.95450 |
499 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1734852.22167 |
500 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 11.19090 |
501 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 216856.52771 |
502 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 7.51575E-002 |
503 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 7.51575E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 18523.50 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 434664.67 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 80591.48 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 12882.34 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 8857.76 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 14629.83 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 7595.72 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 219760.01 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 144003.41 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 216952.47 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 139221.93 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 27782.94 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 18141.42 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 27481.79 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 17826.61 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 53227.00 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 512063.07 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 51627.12 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 94836.89 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 255255.40 | 178091.43 | 77163.96 | 0.70 | 38932.08 | 394.87 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2429663.24 | 1685600.33 | 744062.91 | 0.69 | 367312.56 | 3725.49 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 257408.07 | 179905.11 | 77502.96 | 0.70 | 39408.04 | 399.70 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 138061.67 | 98159.18 | 39902.49 | 0.71 | 21790.03 | 221.01 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 9.21 | 31.42 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 9.21 | 31.42 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.36 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.36 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.36 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.36 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.36 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.36 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.36 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.36 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.36 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.36 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.36 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.36 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.36 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.36 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.36 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.36 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.36 | N/A | 2.159 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.36 | N/A | 2.159 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.36 | N/A | 2.159 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.36 | N/A | 2.159 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.36 | N/A | 2.159 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.36 | N/A | 2.159 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.36 | N/A | 2.159 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.36 | N/A | 2.159 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.075 | 0.926 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.028 | 0.891 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.266 | 1.064 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 2.0168642634E-003 | 1.7706766921E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 5.5319931239E-003 | 6.9412586629E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 3.3732174187E-002 | 1.8783583120E-002 | Pass | Pass | 0.4861082098 | 0.4904010097 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 6.1676681396E-002 | 7.9210567435E-002 | Pass | Pass | 2.9773109808 | 24.4210502915 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.0196995090E-002 | 2.2651372004E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.4975234824E-002 | 9.2888226334E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1088702544 | 0.1348651159 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.7821646591E-002 | 5.0032228541E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.4579622390 | 0.4410054013 | Pass | Pass | 0.8630914194 | 1.1060731323 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3701364512 | 0.4424881729 | Pass | Pass | 0.9865522346 | 1.6809852252 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3135215472 | 0.3393454348 | Pass | Pass | 0.8547544501 | 1.7761797540 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3578492222 | 0.3956829201 | Pass | Pass | 1.8587804701 | 8.6759132681 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.6303072349 | 0.5847231248 | Pass | Pass | 0.6914170719 | 0.6190233637 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.5274556504 | 0.6061202501 | Pass | Pass | 1.0429686079 | 2.4244621165 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4386725900 | 0.5054476270 | Pass | Pass | 0.9068415156 | 2.1336413194 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.5357066213 | 0.5748134571 | Pass | Pass | 2.5482926455 | 20.9301365571 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.7297088873E-003 | 4.4423390163E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.4432256348E-002 | 3.8518117037E-002 | Pass | Pass | 0.4873869637 | 0.4768295880 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1551929037 | 0.1110477238 | Pass | Pass | 0.4918259929 | 0.4875629021 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.8863832711E-007 | 3.7199025136E-007 | Pass | Pass | 1.6871467925E-002 | 1.1294948057E-002 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.2572631903E-002 | 1.0231018118E-002 | Pass | Pass | 4.7450348588E-003 | 5.5851328450E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.7662355325E-002 | 1.3896612783E-002 | Pass | Pass | 6.4933634935E-003 | 7.4270205968E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.1876317414E-005 | 7.6851418104E-006 | Pass | Pass | 8.8712606598E-005 | 1.1081804881E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:28
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 6783.33 | 103.85 | 0.00 | 23788.95 | 14497.58 | 45173.71 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:28
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70 | 0.00 | -10.70 | Wetbulb [C] | 7.50 | 320.00 |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10 | 7.40 | 23.10 | Wetbulb [C] | 5.60 | 230.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 172.00 | 59 | |||
Feb | 49.00 | 37 | |||
Mar | 40.00 | 38 | |||
Apr | 70.00 | 48 | |||
May | 70.00 | 36 | |||
Jun | 25.00 | 15 | |||
Jul | 64.00 | 20 | |||
Aug | 2.00 | 4 | |||
Sep | 73.00 | 32 | |||
Oct | 7.00 | 8 | |||
Nov | 88.00 | 34 | |||
Dec | 62.00 | 39 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:28
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.926 | 1.075 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.891 | 1.028 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.064 | 1.266 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.38_SHGC_NORTH_0.36 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.38_SHGC_NORTH_0.36 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.38_SHGC_NORTH_0.36 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.38_SHGC_NORTH_0.36 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.38_SHGC_NORTH_0.36 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.38_SHGC_EAST_0.36 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.38_SHGC_EAST_0.36 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.38_SHGC_EAST_0.36 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.38_SHGC_SOUTH_0.36 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.38_SHGC_SOUTH_0.36 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.38_SHGC_SOUTH_0.36 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.38_SHGC_SOUTH_0.36 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.38_SHGC_SOUTH_0.36 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.38_SHGC_WEST_0.36 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.38_SHGC_WEST_0.36 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.38_SHGC_WEST_0.36 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.361 | 0.397 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.38_SHGC_NORTH_0.36 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.159 | 0.361 | 0.397 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.38_SHGC_EAST_0.36 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.159 | 0.361 | 0.397 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.38_SHGC_SOUTH_0.36 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.159 | 0.361 | 0.397 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.38_SHGC_WEST_0.36 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.159 | 0.361 | 0.397 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.38_SHGC_NORTH_0.36 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.159 | 0.361 | 0.397 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.38_SHGC_EAST_0.36 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.159 | 0.361 | 0.397 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.38_SHGC_SOUTH_0.36 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.159 | 0.361 | 0.397 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.38_SHGC_WEST_0.36 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.159 | 0.361 | 0.397 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.159 | 0.361 | 0.397 | |||||||||||||||||
North Total or Average | 1390.74 | 2.159 | 0.361 | 0.397 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.159 | 0.361 | 0.397 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:28
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:28
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.6849 | 2779.43 | 24139.15 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 216.17 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 8.6849 | 2496.12 | 21678.66 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 194.14 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 8.6849 | 24961.20 | 216786.56 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 1941.36 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 8.6849 | 2496.12 | 21678.66 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 194.14 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 8.6849 | 313.41 | 2721.97 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.75 | 0.0000 | Y | 14.18 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.59 | 0.0000 | Y | 9.08 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 8.6849 | 313.42 | 2722.03 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.21 | 0.0000 | Y | 13.90 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.32 | 0.0000 | Y | 9.00 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 8.6849 | 3134.13 | 27219.72 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.69 | 0.0000 | Y | 141.46 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 8.6849 | 2019.75 | 17541.42 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.54 | 0.0000 | Y | 90.68 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 8.6849 | 3134.20 | 27220.31 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.18 | 0.0000 | Y | 138.88 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 8.6849 | 2019.75 | 17541.42 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.27 | 0.0000 | Y | 89.79 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 8.6849 | 313.41 | 2721.97 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.68 | 0.0000 | Y | 14.15 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.54 | 0.0000 | Y | 9.07 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 8.6849 | 313.42 | 2722.03 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.18 | 0.0000 | Y | 13.89 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.27 | 0.0000 | Y | 8.98 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 8.6849 | 783.68 | 6806.21 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 62.65 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 13.9016 | 36.20 | 503.28 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.16 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 13.9016 | 362.03 | 5032.75 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 51.55 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 13.9016 | 36.20 | 503.28 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.16 |
Interior Lighting Total | 8.7339 | 46320.38 | 404555.99 | 1015.02 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13271.55 | AstronomicalClock | - | 42.43 | 42.43 | 105.72 | |
EXTERIOR_LIGHTS_B | 989.48 | AstronomicalClock | - | 83.64 | 63.04 | 11.71 | |
EXTERIOR_LIGHTS_C | 26594.85 | AstronomicalClock | - | 83.64 | 46.90 | 234.14 | |
Exterior Lighting Total | 40855.88 | 351.57 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:28
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2878785.02 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 2412928.69 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1449307.95 | 6.01 | 1441231.77 | 5.99 | 9.21 | 31.42 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 1449307.95 | 6.01 | 1441231.77 | 5.99 | 9.21 | 31.42 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 615484.30 | |||||
CENTRAL BOILER | Boiler:HotWater | 600654.06 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1734852.22 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1734852.22 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 236261.70 | 255255.40 | 178091.43 | 77163.96 | 0.70 | - | 38932.08 | 394.87 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2295270.17 | 2429663.24 | 1685600.33 | 744062.91 | 0.69 | - | 367312.56 | 3725.49 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 236537.64 | 257408.07 | 179905.11 | 77502.96 | 0.70 | - | 39408.04 | 399.70 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 119609.82 | 138061.67 | 98159.18 | 39902.49 | 0.71 | - | 21790.03 | 221.01 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 495428.02 | 358142.92 | 137285.10 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9681.44 | 7007.91 | 2673.53 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 92791.35 | 67103.48 | 25687.87 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9446.25 | 6832.79 | 2613.46 | 0.72 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 19535.55 | 18523.50 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 458792.70 | 434664.67 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 85045.32 | 80591.48 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 13595.85 | 12882.34 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 9348.48 | 8857.76 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 15440.41 | 14629.83 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 8018.44 | 7595.72 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 231957.00 | 219760.01 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 151996.27 | 144003.41 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 228993.17 | 216952.47 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 146948.73 | 139221.93 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 29325.94 | 27782.94 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 19148.99 | 18141.42 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 29008.03 | 27481.79 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 18816.67 | 17826.61 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 72691.36 | 53227.00 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 704619.56 | 512063.07 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 69646.21 | 51627.12 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 100000.00 | 94836.89 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 495428.02 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9681.44 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 92791.35 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9446.25 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 20749.82 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 958.56 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 9585.56 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 958.56 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 9.78 | 22223.73 | 2271.59 | 1.00 | 1.12 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 91.78 | 209608.47 | 2283.73 | 1.00 | 1.07 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 9.91 | 22508.21 | 2271.59 | 1.00 | 1.12 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
CAV_BAS FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.54 | 12055.07 | 2174.89 | 1.00 | 1.14 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 24.55 | 40485.40 | 1649.25 | 1.00 | 1.14 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.48 | 539.32 | 1120.11 | 1.00 | 1.62 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.61 | 5159.98 | 1120.11 | 1.00 | 1.16 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.47 | 525.52 | 1120.11 | 1.00 | 1.64 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.082587 | 13483.98 | 163269.45 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.021109 | 6357.21 | 301156.09 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.041294 | 4667.71 | 113036.94 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.041294 | 4667.71 | 113036.94 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.014874 | 3793.59 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.145608 | 36049.41 | 247577.87 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:28
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 76953.58 | 76953.58 | 27.69 | 5.543 | 5.543 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00895 | 26.62 | 0.01411 | 1.200 | 0.00 |
CORE_BOTTOM | 81176.92 | 81176.92 | 32.52 | 5.847 | 5.847 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00889 | 26.62 | 0.01411 | 1.078 | 0.00 |
CORE_MID | 764496.38 | 764496.38 | 306.27 | 55.049 | 55.049 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 26.62 | 0.01411 | 10.778 | 0.00 |
CORE_TOP | 77754.43 | 77754.43 | 31.15 | 5.599 | 5.599 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00890 | 26.62 | 0.01411 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 13836.32 | 13836.32 | 44.15 | 1.006 | 1.006 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00885 | 32.10 | 0.01412 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 16962.57 | 16962.57 | 83.98 | 1.233 | 1.233 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 24.00 | 24.00 | 0.00869 | 27.80 | 0.01411 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 19709.28 | 19709.28 | 62.88 | 1.433 | 1.433 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 24.00 | 24.00 | 0.00875 | 31.73 | 0.01412 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 20675.00 | 20675.00 | 102.36 | 1.503 | 1.503 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 24.00 | 24.00 | 0.00865 | 31.36 | 0.01412 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 130191.41 | 130191.41 | 415.40 | 9.464 | 9.464 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00897 | 32.10 | 0.01412 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 179981.12 | 179981.12 | 891.11 | 13.083 | 13.083 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00873 | 28.24 | 0.01411 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 193433.30 | 193433.30 | 617.17 | 14.061 | 14.061 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 24.00 | 24.00 | 0.00882 | 31.79 | 0.01412 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 186993.01 | 186993.01 | 925.82 | 13.593 | 13.593 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00872 | 31.26 | 0.01412 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 14729.49 | 14729.49 | 47.00 | 1.071 | 1.071 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00896 | 32.10 | 0.01412 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 18305.81 | 18305.81 | 90.63 | 1.331 | 1.331 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00875 | 28.24 | 0.01411 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 20941.95 | 20941.95 | 66.82 | 1.522 | 1.522 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00883 | 31.85 | 0.01412 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 19828.69 | 19828.69 | 98.17 | 1.441 | 1.441 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00873 | 31.26 | 0.01412 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8398.15 | 8398.15 | 231.98 | 0.481 | 0.481 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 29.58 | 0.01412 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 80348.93 | 80348.93 | 2219.42 | 4.607 | 4.607 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 29.58 | 0.01412 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8183.21 | 8183.21 | 226.04 | 0.469 | 0.469 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 27.00 | 27.00 | 0.00859 | 29.77 | 0.01412 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 372315.70 | 428163.05 | 546.35 | 21.346 | 24.548 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 25.37 | 0.01411 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:10:00 | 21.00 | 23.68 | 0.00150 | -10.70 | 0.00150 | 1.200 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | 17.60 | 21.24 | 0.00150 | -10.70 | 0.00150 | 1.078 | 0.00 |
CORE_MID | 267105.17 | 267105.17 | 107.01 | 11.259 | 11.259 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 10.778 | 0.00 |
CORE_TOP | 59567.29 | 59567.29 | 23.86 | 2.532 | 2.532 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 9522.45 | 9522.45 | 30.38 | 0.405 | 0.405 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00743 | -10.70 | 0.00150 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 6546.85 | 6546.85 | 32.41 | 0.279 | 0.279 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00748 | -10.70 | 0.00150 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 10812.06 | 10812.06 | 34.50 | 0.460 | 0.460 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00756 | -10.70 | 0.00150 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 4999.45 | 4999.45 | 24.75 | 0.213 | 0.213 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00707 | -10.70 | 0.00150 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 162362.73 | 162362.73 | 518.05 | 6.923 | 6.923 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00752 | -10.70 | 0.00150 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 106391.80 | 106391.80 | 526.76 | 4.537 | 4.537 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00752 | -10.70 | 0.00150 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 160290.69 | 160290.69 | 511.43 | 6.834 | 6.834 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00752 | -10.70 | 0.00150 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 102862.76 | 102862.76 | 509.28 | 4.386 | 4.386 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00750 | -10.70 | 0.00150 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 20523.71 | 20523.71 | 65.48 | 0.876 | 0.876 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00754 | -10.70 | 0.00150 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 13401.38 | 13401.38 | 66.35 | 0.572 | 0.572 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00753 | -10.70 | 0.00150 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 20301.44 | 20301.44 | 64.77 | 0.866 | 0.866 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00754 | -10.70 | 0.00150 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 13169.00 | 13169.00 | 65.20 | 0.562 | 0.562 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00753 | -10.70 | 0.00150 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | 18.00 | 25.54 | 0.00786 | -10.70 | 0.00150 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 22.90 | 0.00220 | -10.70 | 0.00150 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 21.07 | 0.00199 | -10.70 | 0.00150 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 18.00 | 27.00 | 0.00850 | -10.70 | 0.00150 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 9.78 | 9.78 | 2.43 | 2.43 | 9.7833 | 3.0182 | 9.7833 | 0.3085 | 0.3000 |
VAV_MID WITH REHEAT | 91.78 | 91.78 | 33.94 | 33.94 | 91.7835 | 33.9392 | 91.7835 | 0.3698 | 0.3000 |
VAV_TOP WITH REHEAT | 9.91 | 9.91 | 5.41 | 5.41 | 9.9086 | 5.4069 | 9.9086 | 0.5457 | 0.3000 |
CAV_BAS | 5.54 | 5.54 | 1.20 | 1.20 | 5.5428 | 1.2002 | 5.5428 | 0.2165 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.55 | 24.55 | 0.34 | 0.34 | 24.5478 | 24.5476 | 24.5478 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.48 | 0.48 | 0.02 | 0.02 | 0.4815 | 0.4815 | 0.4815 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.61 | 4.61 | 0.16 | 0.16 | 4.6067 | 4.6067 | 4.6067 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.47 | 0.47 | 0.02 | 0.02 | 0.4692 | 0.4692 | 0.4692 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 19535.546 | 19535.546 | 1.941127 | 0.00017091 | 393.821 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | 19535.55 | 19535.55 | 1.941127 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 19607.58 | 19607.58 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 458792.702 | 458792.702 | 19.046811 | 0.00401372 | 10741.881 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 458792.70 | 458792.70 | 19.046811 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 267105.17 | 0.00 | 460299.44 | 460299.44 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 85045.323 | 85045.323 | 2.531596 | 0.00074401 | 2245.426 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 85045.32 | 85045.32 | 2.531596 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 59567.29 | 0.00 | 85342.72 | 85342.72 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 13595.847 | 13595.847 | 0.405263 | 0.00011894 | 358.745 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13595.85 | 13595.85 | 0.405263 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00742718 | 48.0407 | 9522.45 | 0.00 | 13641.79 | 13641.79 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 9348.480 | 9348.480 | 0.278702 | 0.00008178 | 246.654 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9348.48 | 9348.48 | 0.278702 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00748381 | 48.4023 | 6546.85 | 0.00 | 9379.94 | 9379.94 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 15440.412 | 15440.412 | 0.460348 | 0.00013508 | 407.375 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15440.41 | 15440.41 | 0.460348 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00755927 | 48.8839 | 10812.06 | 0.00 | 15492.30 | 15492.30 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 8018.436 | 8018.436 | 0.300575 | 0.00007015 | 193.654 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8018.44 | 8018.44 | 0.300575 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00707419 | 45.7848 | 4999.45 | 0.00 | 8044.37 | 8044.37 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 231956.997 | 231956.997 | 6.922981 | 0.00202926 | 6116.920 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 231957.00 | 231957.00 | 6.922981 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00752243 | 48.6502 | 162362.73 | 0.00 | 232715.15 | 232715.15 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 151996.274 | 151996.274 | 4.536640 | 0.00132973 | 4008.215 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 151996.27 | 151996.27 | 4.536640 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00751624 | 48.6108 | 106391.80 | 0.00 | 152492.60 | 152492.60 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 228993.174 | 228993.174 | 6.834361 | 0.00200333 | 6038.826 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 228993.17 | 228993.17 | 6.834361 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00751561 | 48.6067 | 160290.69 | 0.00 | 229742.11 | 229742.11 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 146948.730 | 146948.730 | 4.385754 | 0.00128557 | 3875.203 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 146948.73 | 146948.73 | 4.385754 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00749750 | 48.4911 | 102862.76 | 0.00 | 147429.24 | 147429.24 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 29325.944 | 29325.944 | 0.875614 | 0.00025656 | 773.210 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 29325.94 | 29325.94 | 0.875614 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00754201 | 48.7762 | 20523.71 | 0.00 | 29420.77 | 29420.77 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 19148.993 | 19148.993 | 0.571765 | 0.00016752 | 504.878 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19148.99 | 19148.99 | 0.571765 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00753331 | 48.7208 | 13401.38 | 0.00 | 19210.87 | 19210.87 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 29008.026 | 29008.026 | 0.866108 | 0.00025377 | 764.833 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 29008.03 | 29008.03 | 0.866108 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00753715 | 48.7452 | 20301.44 | 0.00 | 29101.86 | 29101.86 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 18816.672 | 18816.672 | 0.561833 | 0.00016462 | 496.120 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18816.67 | 18816.67 | 0.561833 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00752526 | 48.6694 | 13169.00 | 0.00 | 18877.50 | 18877.50 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 236261.695 | -999.000 | 9.783321 | 0.00675705 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 236261.70 | 181188.83 | 9.783321 | 26.18 | 18.59 | 0.01027521 | 10.96 | 10.96 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 25.9441 | 24.00 | 0.00885789 | 47.6368 | 129630.35 | 0.00 | 236563.23 | 177889.23 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 72691.360 | 72691.360 | 2.934996 | 0.00063594 | 1168.206 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 72691.36 | 72691.36 | 2.934996 | -7.68 | -7.70 | 0.00195028 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 86.4802 | 21.09 | 0.00560415 | 36.1470 | 31880.82 | 0.00 | 64370.12 | 64370.12 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2295270.172 | -999.000 | 91.783475 | 0.06564444 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 2295270.17 | 1723568.79 | 91.783475 | 26.39 | 18.81 | 0.01046530 | 10.95 | 10.95 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 27.6542 | 24.00 | 0.00893066 | 48.0233 | 1180629.37 | 0.00 | 2298165.05 | 1694476.24 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 704619.558 | 704619.558 | 27.535042 | 0.00616432 | 11283.582 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 704619.56 | 704619.56 | 27.535042 | -8.36 | -8.36 | 0.00197577 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 92.1805 | 19.60 | 0.00733791 | 51.7597 | 467803.76 | 0.00 | 619248.25 | 619248.25 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 236537.640 | -999.000 | 9.908559 | 0.00676495 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 236537.64 | 182232.95 | 9.908559 | 26.07 | 18.52 | 0.01022777 | 10.96 | 10.96 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 25.6161 | 24.00 | 0.00888750 | 47.7945 | 136308.14 | 0.00 | 236841.94 | 178842.93 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 69646.211 | 69646.211 | 2.972568 | 0.00060930 | 1125.674 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 69646.21 | 69646.21 | 2.972568 | -6.57 | -6.57 | 0.00237705 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 85.3871 | 17.60 | 0.00731370 | 58.4782 | 53908.29 | 0.00 | 62445.78 | 62445.78 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 119609.822 | -999.000 | 5.542846 | 0.00342083 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 119609.82 | 91976.52 | 5.542846 | 24.67 | 17.93 | 0.01007485 | 11.03 | 11.03 | 0.00850000 | 27.09 | 0.01411064 | 21.71 | 21.6524 | 24.00 | 0.00895388 | 48.1457 | 75951.83 | 0.00 | 119769.17 | 90247.66 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 100000.000 | 100000.000 | 3.039805 | 0.00087484 | 2622.727 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 100000.00 | 100000.00 | 3.039805 | -2.32 | -5.03 | 0.00150390 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 39.4814 | 23.76 | 0.00150390 | 8.2992 | 0.00 | 0.00 | 100081.81 | 100081.81 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 495428.019 | 358142.920 | 24.547812 | 0.01213300 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 463524.64 | 455474.55 | -999.0 | 28.46 | 18.02 | 0.00861916 | 12.80 | 12.09 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | -999.0000 | 27.00 | 0.00854220 | 38.4639 | 371915.20 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9681.438 | 7007.909 | 0.481492 | 0.00023710 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 9051.65 | 8699.84 | -999.0 | 28.03 | 17.99 | 0.00876574 | 12.80 | 12.09 | 0.00850000 | 29.58 | 0.01411511 | 22.43 | -999.0000 | 27.00 | 0.00858624 | 38.6571 | 8398.15 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 92791.347 | 67103.475 | 4.606682 | 0.00227245 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 86780.76 | 83264.37 | -999.0 | 28.03 | 18.00 | 0.00877758 | 12.80 | 12.09 | 0.00850000 | 29.58 | 0.01411511 | 22.43 | -999.0000 | 27.00 | 0.00859009 | 38.6744 | 80348.93 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9446.248 | 6832.792 | 0.469171 | 0.00023134 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 8833.75 | 8482.14 | -999.0 | 28.04 | 18.00 | 0.00877254 | 12.80 | 12.09 | 0.00850000 | 29.77 | 0.01411544 | 22.48 | -999.0000 | 27.00 | 0.00858839 | 38.6667 | 8183.21 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 495428.019 | 495428.019 | 24.547812 | 0.01213300 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 495428.02 | 495428.02 | 24.547812 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 1.3785 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9681.438 | 9681.438 | 0.481492 | 0.00023710 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9681.44 | 9681.44 | 0.481492 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.2466 | 26.09 | 0.00785818 | 37.3646 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 92791.347 | 92791.347 | 4.606682 | 0.00227245 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 92791.35 | 92791.35 | 4.606682 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.3934 | 24.03 | 0.00219699 | 11.9157 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9446.248 | 9446.248 | 0.469171 | 0.00023134 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9446.25 | 9446.25 | 0.469171 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.3319 | 22.96 | 0.00198800 | 11.5112 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 20749.821 | 20749.821 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 20749.82 | 20749.82 | 24.547812 | -0.15 | -0.15 | 0.00840356 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 1.3785 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 958.556 | 958.556 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 958.56 | 958.56 | 0.481492 | -0.35 | -0.35 | 0.00765188 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.2466 | 26.09 | 0.00785818 | 37.3646 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 9585.558 | 9585.558 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9585.56 | 9585.56 | 4.606682 | -0.36 | -2.71 | 0.00217347 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.3934 | 24.03 | 0.00219699 | 11.9157 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 958.556 | 958.556 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 958.56 | 958.56 | 0.469171 | -0.36 | -3.04 | 0.00197187 | 40.00 | 21.18 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.3319 | 22.96 | 0.00198800 | 11.5112 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:25:28
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 19535.546 | 19535.546 | 1.941127 | 0.00017091 | 393.821 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.10719940 | 54.44 | 82.22 | 27.78 | 2461489.84 | 0.7936 | 0.809620 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | Sensible | 19535.55 | 19535.55 | 1.0000 | 2.33633088 | 1.941127 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.17088805 | 60.00 | 32.22 | 27.78 | 0.000 | 19535.55 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 19607.58 | 19607.58 | 2.33633088 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 458792.702 | 458792.702 | 19.046811 | 0.00401372 | 10741.881 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.10719940 | 54.44 | 82.22 | 27.78 | 2461489.84 | 18.6388 | 19.013935 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 458792.70 | 458792.70 | 1.0000 | 22.92464635 | 19.046811 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 4.01330926 | 60.00 | 32.22 | 27.78 | 0.000 | 458792.70 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.83 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 267105.17 | 0.00 | 460299.44 | 460299.44 | 22.92464635 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.49 | 18.86 | 0.00800000 | 53138.6 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 85045.323 | 85045.323 | 2.531596 | 0.00074401 | 2245.426 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.10719940 | 54.44 | 82.22 | 27.78 | 2461489.84 | 3.4550 | 3.524568 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 85045.32 | 85045.32 | 1.0000 | 3.04701586 | 2.531596 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.74393769 | 60.00 | 32.22 | 27.78 | 0.000 | 85045.32 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 59567.29 | 0.00 | 85342.72 | 85342.72 | 3.04701586 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.27 | 21.26 | 0.00800000 | 61068.5 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13595.847 | 13595.847 | 0.405263 | 0.00011894 | 358.745 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.10719940 | 54.44 | 82.22 | 27.78 | 2461489.84 | 0.5523 | 0.563458 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13595.85 | 13595.85 | 1.0000 | 0.48777292 | 0.405263 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.11893026 | 60.00 | 32.22 | 27.78 | 0.000 | 13595.85 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.91 | 0.00742718 | 21.00 | 0.00742718 | 48.0407 | 9522.45 | 0.00 | 13641.79 | 13641.79 | 0.48777292 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61027.3 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9348.480 | 9348.480 | 0.278702 | 0.00008178 | 246.654 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.10719940 | 54.44 | 82.22 | 27.78 | 2461489.84 | 0.3798 | 0.387433 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9348.48 | 9348.48 | 1.0000 | 0.33544453 | 0.278702 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.08177624 | 60.00 | 32.22 | 27.78 | 0.000 | 9348.48 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.91 | 0.00748381 | 21.00 | 0.00748381 | 48.4023 | 6546.85 | 0.00 | 9379.94 | 9379.94 | 0.33544453 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61022.6 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15440.412 | 15440.412 | 0.460348 | 0.00013508 | 407.375 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.10719940 | 54.44 | 82.22 | 27.78 | 2461489.84 | 0.6273 | 0.639903 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 15440.41 | 15440.41 | 1.0000 | 0.55407216 | 0.460348 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.13506568 | 60.00 | 32.22 | 27.78 | 0.000 | 15440.41 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.91 | 0.00755927 | 21.00 | 0.00755927 | 48.8839 | 10812.06 | 0.00 | 15492.30 | 15492.30 | 0.55407216 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61020.6 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8018.436 | 8018.436 | 0.300575 | 0.00007015 | 193.654 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.10719940 | 54.44 | 82.22 | 27.78 | 2461489.84 | 0.3258 | 0.332311 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8018.44 | 8018.44 | 1.0000 | 0.36177110 | 0.300575 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.07014162 | 60.00 | 32.22 | 27.78 | 0.000 | 8018.44 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.91 | 0.00707419 | 21.00 | 0.00707419 | 45.7848 | 4999.45 | 0.00 | 8044.37 | 8044.37 | 0.36177110 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 34.61 | 19.53 | 0.00800000 | 55295.9 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 231956.997 | 231956.997 | 6.922981 | 0.00202926 | 6116.920 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.10719940 | 54.44 | 82.22 | 27.78 | 2461489.84 | 9.4234 | 9.613090 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 231957.00 | 231957.00 | 1.0000 | 8.33246476 | 6.922981 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 2.02905399 | 60.00 | 32.22 | 27.78 | 0.000 | 231957.00 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00752243 | 21.00 | 0.00752243 | 48.6502 | 162362.73 | 0.00 | 232715.15 | 232715.15 | 8.33246476 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60988.6 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 151996.274 | 151996.274 | 4.536640 | 0.00132973 | 4008.215 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.10719940 | 54.44 | 82.22 | 27.78 | 2461489.84 | 6.1750 | 6.299244 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 151996.27 | 151996.27 | 1.0000 | 5.46027687 | 4.536640 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 1.32959407 | 60.00 | 32.22 | 27.78 | 0.000 | 151996.27 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00751624 | 21.00 | 0.00751624 | 48.6108 | 106391.80 | 0.00 | 152492.60 | 152492.60 | 5.46027687 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60987.5 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 228993.174 | 228993.174 | 6.834361 | 0.00200333 | 6038.826 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.10719940 | 54.44 | 82.22 | 27.78 | 2461489.84 | 9.3030 | 9.490259 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 228993.17 | 228993.17 | 1.0000 | 8.22580260 | 6.834361 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 2.00312782 | 60.00 | 32.22 | 27.78 | 0.000 | 228993.17 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00751561 | 21.00 | 0.00751561 | 48.6067 | 160290.69 | 0.00 | 229742.11 | 229742.11 | 8.22580260 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60989.3 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 146948.730 | 146948.730 | 4.385754 | 0.00128557 | 3875.203 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.10719940 | 54.44 | 82.22 | 27.78 | 2461489.84 | 5.9699 | 6.090057 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 146948.73 | 146948.73 | 1.0000 | 5.27867130 | 4.385754 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 1.28544046 | 60.00 | 32.22 | 27.78 | 0.000 | 146948.73 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00749750 | 21.00 | 0.00749750 | 48.4911 | 102862.76 | 0.00 | 147429.24 | 147429.24 | 5.27867130 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60989.1 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 29325.944 | 29325.944 | 0.875614 | 0.00025656 | 773.210 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.10719940 | 54.44 | 82.22 | 27.78 | 2461489.84 | 1.1914 | 1.215367 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 29325.94 | 29325.94 | 1.0000 | 1.05388417 | 0.875614 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.25652998 | 60.00 | 32.22 | 27.78 | 0.000 | 29325.94 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00754201 | 21.00 | 0.00754201 | 48.7762 | 20523.71 | 0.00 | 29420.77 | 29420.77 | 1.05388417 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60976.3 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19148.993 | 19148.993 | 0.571765 | 0.00016752 | 504.878 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.10719940 | 54.44 | 82.22 | 27.78 | 2461489.84 | 0.7779 | 0.793600 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19148.99 | 19148.99 | 1.0000 | 0.68817317 | 0.571765 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.16750665 | 60.00 | 32.22 | 27.78 | 0.000 | 19148.99 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00753331 | 21.00 | 0.00753331 | 48.7208 | 13401.38 | 0.00 | 19210.87 | 19210.87 | 0.68817317 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60975.6 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 29008.026 | 29008.026 | 0.866108 | 0.00025377 | 764.833 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.10719940 | 54.44 | 82.22 | 27.78 | 2461489.84 | 1.1785 | 1.202192 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 29008.03 | 29008.03 | 1.0000 | 1.04244286 | 0.866108 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.25374898 | 60.00 | 32.22 | 27.78 | 0.000 | 29008.03 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00753715 | 21.00 | 0.00753715 | 48.7452 | 20301.44 | 0.00 | 29101.86 | 29101.86 | 1.04244286 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60976.8 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18816.672 | 18816.672 | 0.561833 | 0.00016462 | 496.120 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 21.10719940 | 54.44 | 82.22 | 27.78 | 2461489.84 | 0.7644 | 0.779827 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18816.67 | 18816.67 | 1.0000 | 0.67621905 | 0.561833 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.16459966 | 60.00 | 32.22 | 27.78 | 0.000 | 18816.67 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00752526 | 21.00 | 0.00752526 | 48.6694 | 13169.00 | 0.00 | 18877.50 | 18877.50 | 0.67621905 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60976.1 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 236261.695 | -999.000 | 9.783321 | 0.00675705 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.9411 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.783321 | 11.77515589 | 4197.9300 | 999.8980 | 82.57883852 | 15.00 | 6.67 | 8.33 | 2887679.33 | 8.1817 | 8.181715 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 236261.70 | 181188.83 | 1.0000 | 11.77515589 | 9.783321 | 26.18 | 18.59 | 0.01027521 | 52505.4 | 10.96 | 10.96 | 0.00850000 | 32440.9 | 6.75636528 | 6.67 | 15.00 | 8.33 | 22223.725 | 214037.97 | 32.10 | 0.01411964 | 23.13 | 2.53819000 | 25.9441 | 24.00 | 0.00885789 | 24.00 | 0.00885789 | 47.6368 | 129630.35 | 0.00 | 236563.23 | 177889.23 | 11.77515589 | 26.18 | 18.60 | 0.01027521 | 52505.4 | 11.43 | 11.32 | 0.00829959 | 32415.3 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 72691.360 | 72691.360 | 2.934996 | 0.00063594 | 1168.206 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.783321 | 11.77515589 | 4197.9300 | 999.8980 | 21.10719940 | 54.44 | 82.22 | 27.78 | 2461489.84 | 2.9531 | 3.012578 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 72691.36 | 72691.36 | 1.0000 | 3.53254677 | 2.934996 | -7.68 | -7.70 | 0.00195028 | -2865.6 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 0.63587086 | 60.00 | 32.22 | 27.78 | 0.000 | 72691.36 | -10.70 | 0.00150390 | -10.70 | 2.53819000 | 86.4802 | 11.65 | 0.00480557 | 21.09 | 0.00560415 | 36.1470 | 31880.82 | 0.00 | 64370.12 | 64370.12 | 3.53254677 | 2.80 | -1.26 | 0.00195028 | 7701.2 | 20.87 | 8.61 | 0.00195028 | 25923.2 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2295270.172 | -999.000 | 91.783475 | 0.06564444 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2945 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 91.783475 | 110.47012989 | 4197.9300 | 999.8980 | 82.57883852 | 15.00 | 6.67 | 8.33 | 2887679.33 | 79.4849 | 79.484940 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 2295270.17 | 1723568.79 | 1.0000 | 110.47012989 | 91.783475 | 26.39 | 18.81 | 0.01046530 | 53208.8 | 10.95 | 10.95 | 0.00850000 | 32431.5 | 65.63773996 | 6.67 | 15.00 | 8.33 | 209608.474 | 2085661.70 | 32.10 | 0.01411964 | 23.13 | 25.38195000 | 27.6542 | 24.00 | 0.00893066 | 24.00 | 0.00893066 | 48.0233 | 1180629.37 | 0.00 | 2298165.05 | 1694476.24 | 110.47012989 | 26.39 | 18.82 | 0.01046530 | 53208.8 | 11.42 | 11.32 | 0.00829862 | 32405.3 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 704619.558 | 704619.558 | 27.535042 | 0.00616432 | 11283.582 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 91.783475 | 110.47012989 | 4197.9300 | 999.8980 | 21.10719940 | 54.44 | 82.22 | 27.78 | 2461489.84 | 28.6257 | 29.201839 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 704619.56 | 704619.56 | 1.0000 | 33.14103897 | 27.535042 | -8.36 | -8.36 | 0.00197577 | -3488.3 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 6.16369045 | 60.00 | 32.22 | 27.78 | 0.000 | 704619.56 | -10.70 | 0.00150390 | -10.70 | 25.38195000 | 92.1805 | 19.25 | 0.00753843 | 19.60 | 0.00733791 | 51.7597 | 467803.76 | 0.00 | 619248.25 | 619248.25 | 33.14103897 | 2.80 | -1.22 | 0.00197577 | 7765.1 | 21.33 | 8.85 | 0.00197577 | 26450.3 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 236537.640 | -999.000 | 9.908559 | 0.00676495 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.8529 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.908559 | 11.92589132 | 4197.9300 | 999.8980 | 82.57883852 | 15.00 | 6.67 | 8.33 | 2887679.33 | 8.1913 | 8.191271 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 236537.64 | 182232.95 | 1.0000 | 11.92589132 | 9.908559 | 26.07 | 18.52 | 0.01022777 | 52274.7 | 10.96 | 10.96 | 0.00850000 | 32440.8 | 6.76425647 | 6.67 | 15.00 | 8.33 | 22508.214 | 214029.43 | 32.10 | 0.01411964 | 23.13 | 2.53819000 | 25.6161 | 24.00 | 0.00888750 | 24.00 | 0.00888750 | 47.7945 | 136308.14 | 0.00 | 236841.94 | 178842.93 | 11.92589132 | 26.07 | 18.52 | 0.01022777 | 52274.7 | 11.43 | 11.32 | 0.00829957 | 32415.3 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 69646.211 | 69646.211 | 2.972568 | 0.00060930 | 1125.674 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.908559 | 11.92589132 | 4197.9300 | 999.8980 | 21.10719940 | 54.44 | 82.22 | 27.78 | 2461489.84 | 2.8294 | 2.886377 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 69646.21 | 69646.21 | 1.0000 | 3.57776740 | 2.972568 | -6.57 | -6.57 | 0.00237705 | -688.3 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 0.60923328 | 60.00 | 32.22 | 27.78 | 0.000 | 69646.21 | -10.70 | 0.00150390 | -10.70 | 2.53819000 | 85.3871 | 17.55 | 0.00747914 | 17.60 | 0.00731370 | 58.4782 | 53908.29 | 0.00 | 62445.78 | 62445.78 | 3.57776740 | 2.80 | -0.60 | 0.00237705 | 8770.8 | 20.09 | 8.74 | 0.00237705 | 26224.6 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 119609.822 | -999.000 | 5.542846 | 0.00342083 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.5686 | 1004.8586 | 1.2036 | CAV_BAS FAN | Fan:VariableVolume | 5.542846 | 6.67134104 | 4197.9300 | 999.8980 | 82.57883852 | 15.00 | 6.67 | 8.33 | 2887679.33 | 4.1421 | 4.142074 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 119609.82 | 91976.52 | 1.0000 | 6.67134104 | 5.542846 | 24.67 | 17.93 | 0.01007485 | 50449.3 | 11.03 | 11.03 | 0.00850000 | 32520.4 | 3.42047680 | 6.67 | 15.00 | 8.33 | 12055.070 | 107554.75 | 27.09 | 0.01411064 | 21.71 | 1.20015641 | 21.6524 | 24.00 | 0.00895388 | 24.00 | 0.00895388 | 48.1457 | 75951.83 | 0.00 | 119769.17 | 90247.66 | 6.67134104 | 24.67 | 17.94 | 0.01007485 | 50449.3 | 11.46 | 11.36 | 0.00832040 | 32496.5 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.039805 | 0.00087484 | 2622.727 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | CAV_BAS FAN | Fan:VariableVolume | 5.542846 | 6.67134104 | 4197.9300 | 999.8980 | 21.10719940 | 54.44 | 82.22 | 27.78 | 2461489.84 | 4.0626 | 4.144341 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.039805 | -2.32 | -5.03 | 0.00150390 | 1426.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | -10.70 | 0.00150390 | -10.70 | 1.20015641 | 39.4814 | 0.00 | 0.00150390 | 23.76 | 0.00150390 | 8.2992 | 0.00 | 0.00 | 100081.81 | 100081.81 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.02 | 14.59 | 0.00000000 | 40241.7 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 495428.019 | 358142.920 | 24.547812 | 0.01213300 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8626 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 463524.64 | 455474.55 | 0.9356 | -999.0 | -999.0 | 28.46 | 18.02 | 0.00861916 | 50611.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 463524.64 | 32.10 | 0.01411964 | 23.13 | 0.33839277 | -999.0000 | 27.00 | 0.00854220 | 27.00 | 0.00854220 | 38.4639 | 371915.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9681.438 | 7007.909 | 0.481492 | 0.00023710 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1351 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 9051.65 | 8699.84 | 0.9349 | -999.0 | -999.0 | 28.03 | 17.99 | 0.00876574 | 50543.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9051.65 | 29.58 | 0.01411511 | 22.43 | 0.01563234 | -999.0000 | 27.00 | 0.00858624 | 27.00 | 0.00858624 | 38.6571 | 8398.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 92791.347 | 67103.475 | 4.606682 | 0.00227245 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1571 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 86780.76 | 83264.37 | 0.9352 | -999.0 | -999.0 | 28.03 | 18.00 | 0.00877758 | 50577.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 86780.76 | 29.58 | 0.01411511 | 22.43 | 0.15632344 | -999.0000 | 27.00 | 0.00859009 | 27.00 | 0.00859009 | 38.6744 | 80348.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9446.248 | 6832.792 | 0.469171 | 0.00023134 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1477 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | Sensible | 8833.75 | 8482.14 | 0.9352 | -999.0 | -999.0 | 28.04 | 18.00 | 0.00877254 | 50569.8 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8833.75 | 29.77 | 0.01411544 | 22.48 | 0.01563234 | -999.0000 | 27.00 | 0.00858839 | 27.00 | 0.00858839 | 38.6667 | 8183.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 495428.019 | 495428.019 | 24.547812 | 0.01213300 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 495428.02 | 495428.02 | 1.0000 | 29.54562331 | 24.547812 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 495428.02 | -10.70 | 0.00150390 | -10.70 | 0.33839277 | 1.3785 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9681.438 | 9681.438 | 0.481492 | 0.00023710 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9681.44 | 9681.44 | 1.0000 | 0.57952194 | 0.481492 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9681.44 | -10.70 | 0.00150390 | -10.70 | 0.01563234 | 3.2466 | 0.00 | 0.00785818 | 26.09 | 0.00785818 | 37.3646 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 92791.347 | 92791.347 | 4.606682 | 0.00227245 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 92791.35 | 92791.35 | 1.0000 | 5.54457973 | 4.606682 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 92791.35 | -10.70 | 0.00150390 | -10.70 | 0.15632344 | 3.3934 | 0.00 | 0.00219699 | 24.03 | 0.00219699 | 11.9157 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9446.248 | 9446.248 | 0.469171 | 0.00023134 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9446.25 | 9446.25 | 1.0000 | 0.56469151 | 0.469171 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9446.25 | -10.70 | 0.00150390 | -10.70 | 0.01563234 | 3.3319 | 0.00 | 0.00198800 | 22.96 | 0.00198800 | 11.5112 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 20749.821 | 20749.821 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 24.547812 | 29.54562331 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 20749.82 | 20749.82 | 1.0000 | 29.54562331 | 24.547812 | -0.15 | -0.15 | 0.00840356 | 20866.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20749.82 | -10.70 | 0.00150390 | -10.70 | 0.33839277 | 1.3785 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2706 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 958.556 | 958.556 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.481492 | 0.57952194 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 958.56 | 958.56 | 1.0000 | 0.57952194 | 0.481492 | -0.35 | -0.35 | 0.00765188 | 18782.9 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 958.56 | -10.70 | 0.00150390 | -10.70 | 0.01563234 | 3.2466 | 0.00 | 0.00785818 | 26.09 | 0.00785818 | 37.3646 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9585.558 | 9585.558 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.606682 | 5.54457973 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9585.56 | 9585.56 | 1.0000 | 5.54457973 | 4.606682 | -0.36 | -2.71 | 0.00217347 | 5069.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9585.56 | -10.70 | 0.00150390 | -10.70 | 0.15632344 | 3.3934 | 0.00 | 0.00219699 | 24.03 | 0.00219699 | 11.9157 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 958.556 | 958.556 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.469171 | 0.56469151 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 958.56 | 958.56 | 1.0000 | 0.56469151 | 0.469171 | -0.36 | -3.04 | 0.00197187 | 4572.0 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 958.56 | -10.70 | 0.00150390 | -10.70 | 0.01563234 | 3.3319 | 0.00 | 0.00198800 | 22.96 | 0.00198800 | 11.5112 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:28
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 9.78 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 91.78 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 9.91 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialEnthalpy | 1.20 | 5.54 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialEnthalpy | 0.34 | 24.55 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 3374.50 | 1926.50 | 1305.00 |
CORE_BOTTOM | 2923.00 | 1018.67 | 14.50 |
CORE_MID | 2269.83 | 2721.33 | 57.50 |
CORE_TOP | 2631.67 | 3274.67 | 589.33 |
PERIMETER_BOT_ZN_3 | 2616.67 | 2943.33 | 332.33 |
PERIMETER_BOT_ZN_2 | 2748.00 | 2950.33 | 385.00 |
PERIMETER_BOT_ZN_1 | 3071.67 | 2434.17 | 390.17 |
PERIMETER_BOT_ZN_4 | 3251.17 | 2007.17 | 340.50 |
PERIMETER_MID_ZN_3 | 3330.17 | 3593.67 | 1463.17 |
PERIMETER_MID_ZN_2 | 2803.83 | 3053.83 | 1197.33 |
PERIMETER_MID_ZN_1 | 3264.33 | 2863.67 | 851.67 |
PERIMETER_MID_ZN_4 | 3254.83 | 3361.00 | 1122.00 |
PERIMETER_TOP_ZN_3 | 3839.50 | 3797.17 | 2094.67 |
PERIMETER_TOP_ZN_2 | 3726.67 | 3646.83 | 1791.33 |
PERIMETER_TOP_ZN_1 | 3552.83 | 3133.00 | 1348.17 |
PERIMETER_TOP_ZN_4 | 3609.50 | 3582.67 | 1645.33 |
DATACENTER_BOT_ZN_6 | 5931.67 | 1271.17 | 1271.17 |
DATACENTER_MID_ZN_6 | 5599.33 | 345.17 | 285.33 |
DATACENTER_TOP_ZN_6 | 5055.67 | 691.67 | 499.17 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5725.67 | 5725.67 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5942.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 2629.50 | 0.00 | 1618.50 |
CORE_BOTTOM | 0.00 | 16.17 | 0.00 | 0.33 |
CORE_MID | 2.33 | 0.00 | 1.33 | 0.00 |
CORE_TOP | 6.50 | 0.00 | 1.33 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.33 | 28.00 | 0.00 | 13.83 |
PERIMETER_BOT_ZN_2 | 0.33 | 38.83 | 0.00 | 36.17 |
PERIMETER_BOT_ZN_1 | 0.33 | 61.00 | 0.00 | 51.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 94.33 | 0.00 | 44.83 |
PERIMETER_MID_ZN_3 | 30.50 | 1.33 | 7.50 | 1.33 |
PERIMETER_MID_ZN_2 | 20.17 | 32.00 | 1.00 | 32.00 |
PERIMETER_MID_ZN_1 | 14.50 | 58.33 | 0.67 | 57.50 |
PERIMETER_MID_ZN_4 | 15.00 | 31.00 | 1.50 | 20.17 |
PERIMETER_TOP_ZN_3 | 107.83 | 8.00 | 28.17 | 6.83 |
PERIMETER_TOP_ZN_2 | 70.33 | 35.50 | 7.83 | 34.83 |
PERIMETER_TOP_ZN_1 | 54.50 | 42.33 | 5.33 | 39.83 |
PERIMETER_TOP_ZN_4 | 46.17 | 34.17 | 5.00 | 22.33 |
DATACENTER_BOT_ZN_6 | 0.00 | 1.17 | 0.00 | 1.17 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 6.67 | 0.00 | 6.67 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 119.33 | 2732.50 | 28.83 | 1711.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:28
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.32 | 149.60 | 6779.02 | 0.905 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.97 | 134.35 | 6849.35 | 0.865 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.97 | 134.35 | 6849.35 | 0.657 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.97 | 134.35 | 6849.35 | 0.637 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.03 | 16.87 | 860.00 | 0.813 | 0.025 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.53 | 10.87 | 554.22 | 1.223 | 0.026 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.03 | 16.87 | 860.02 | 1.280 | 0.025 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.53 | 10.87 | 554.22 | 1.649 | 0.026 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.03 | 16.87 | 860.00 | 0.696 | 0.058 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.96 | 10.87 | 554.22 | 1.131 | 0.064 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.03 | 16.87 | 860.02 | 1.216 | 0.058 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.53 | 10.87 | 554.22 | 1.292 | 0.060 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.03 | 16.87 | 860.00 | 0.702 | 0.072 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.53 | 10.87 | 554.22 | 1.225 | 0.074 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.03 | 16.87 | 860.02 | 1.205 | 0.072 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.53 | 10.87 | 554.22 | 1.320 | 0.074 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.57 | 42.18 | 1911.37 | 21.224 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.32 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.97 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.97 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.97 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.03 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.03 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.03 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.96 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.03 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.03 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.03 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.57 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:25:28
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.32 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.97 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.97 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.97 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.03 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.53 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.03 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.53 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.03 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.96 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.03 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.53 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.03 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.53 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.03 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.53 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.57 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1032.96 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 35744607.90 | 0.00 | 35744607.90 | 0.00 | 35744607.90 | 37848132.68 | 5334.03 | 711.10 | 2714.87 | 0.00 |
CORE_BOTTOM | 36105358.26 | 0.00 | 36105358.26 | 0.00 | 36105358.26 | 33990283.35 | 5330.84 | 65.53 | 3363.64 | 249.40 |
CORE_MID | 0.27E+09 | 0.00 | 0.27E+09 | 0.00 | 0.27E+09 | 0.34E+09 | 6478.26 | 57.10 | 2224.64 | 161.14 |
CORE_TOP | 25918500.38 | 0.00 | 25918500.38 | 0.00 | 25918500.38 | 33990283.35 | 6774.65 | 35.03 | 1950.32 | 257.58 |
PERIMETER_BOT_ZN_3 | 4256255.04 | 0.00 | 4256255.04 | 244309.16 | 4500564.20 | 4267819.30 | 5366.86 | 80.41 | 3312.73 | 249.40 |
PERIMETER_BOT_ZN_2 | 4139977.41 | 0.00 | 4139977.41 | 162872.66 | 4302850.07 | 2750345.05 | 3818.45 | 23.68 | 4917.87 | 249.40 |
PERIMETER_BOT_ZN_1 | 6636382.48 | 0.00 | 6636382.48 | 244309.16 | 6880691.64 | 4267912.63 | 4106.10 | 65.14 | 4588.75 | 249.40 |
PERIMETER_BOT_ZN_4 | 5568785.24 | 0.00 | 5568785.24 | 162872.66 | 5731657.90 | 2750345.05 | 3741.66 | 2.71 | 5015.63 | 249.40 |
PERIMETER_MID_ZN_3 | 35620639.18 | 0.00 | 35620639.18 | 572971.12 | 36193610.30 | 42678193.03 | 5758.17 | 62.71 | 2939.12 | 161.14 |
PERIMETER_MID_ZN_2 | 40307489.42 | 0.00 | 40307489.42 | 381980.48 | 40689469.90 | 27503450.52 | 4038.75 | 10.73 | 4710.52 | 1070.14 |
PERIMETER_MID_ZN_1 | 61778611.64 | 0.00 | 61778611.64 | 572971.12 | 62351582.75 | 42679126.28 | 4112.30 | 16.42 | 4631.28 | 161.14 |
PERIMETER_MID_ZN_4 | 42613035.30 | 0.00 | 42613035.30 | 381980.48 | 42995015.79 | 27503450.52 | 4011.11 | 11.76 | 4737.14 | 161.14 |
PERIMETER_TOP_ZN_3 | 3590074.41 | 0.00 | 3590074.41 | 711401.85 | 4301476.26 | 4267819.30 | 5789.77 | 49.35 | 2920.88 | 257.58 |
PERIMETER_TOP_ZN_2 | 4032209.16 | 0.00 | 4032209.16 | 474267.57 | 4506476.73 | 2750345.05 | 4105.77 | 5.78 | 4648.45 | 257.58 |
PERIMETER_TOP_ZN_1 | 6125951.91 | 0.00 | 6125951.91 | 711401.85 | 6837353.76 | 4267912.63 | 4153.17 | 5.87 | 4600.96 | 257.58 |
PERIMETER_TOP_ZN_4 | 4348021.36 | 0.00 | 4348021.36 | 474267.57 | 4822288.93 | 2750345.05 | 4090.46 | 2.99 | 4666.56 | 257.58 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.33E+09 | 0.00 | 0.33E+09 | 0.00 | 0.33E+09 | 10671554.30 | 882.30 | 971.35 | 6906.35 | 2253.50 |
Total Facility | 0.50E+10 | 0.00 | 0.50E+10 | 22284734.42 | 0.50E+10 | 0.50E+10 | 7231.64 | 4388.54 | 7956.49 | 3215.30 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.6707 | 0.0000 | 1.6707 | 0.0000 | 1.6707 | 1.2002 | 2517.03 | 711.10 | 2714.87 |
CORE_BOTTOM | 1.6122 | 0.0000 | 1.6122 | 0.0000 | 1.6122 | 1.0778 | 2714.14 | 64.05 | 3164.82 |
CORE_MID | 12.2582 | 0.0000 | 12.2582 | 0.0000 | 12.2582 | 10.7782 | 3715.94 | 57.10 | 2169.96 |
CORE_TOP | 1.1886 | 0.0000 | 1.1886 | 0.0000 | 1.1886 | 1.0778 | 3998.41 | 34.95 | 1909.64 |
PERIMETER_BOT_ZN_3 | 0.1903 | 0.0000 | 0.1903 | 0.0058 | 0.1961 | 0.1353 | 2747.07 | 78.58 | 3117.35 |
PERIMETER_BOT_ZN_2 | 0.1849 | 0.0000 | 0.1849 | 0.0039 | 0.1888 | 0.0872 | 1239.91 | 22.59 | 4680.49 |
PERIMETER_BOT_ZN_1 | 0.3001 | 0.0000 | 0.3001 | 0.0058 | 0.3059 | 0.1353 | 1504.43 | 63.52 | 4375.05 |
PERIMETER_BOT_ZN_4 | 0.2489 | 0.0000 | 0.2489 | 0.0039 | 0.2528 | 0.0872 | 1168.20 | 1.81 | 4772.99 |
PERIMETER_MID_ZN_3 | 1.6323 | 0.0000 | 1.6323 | 0.0136 | 1.6459 | 1.3533 | 2999.88 | 62.44 | 2880.68 |
PERIMETER_MID_ZN_2 | 1.7116 | 0.0000 | 1.7116 | 0.0097 | 1.7213 | 0.8721 | 1289.67 | 6.53 | 3737.81 |
PERIMETER_MID_ZN_1 | 2.8499 | 0.0000 | 2.8499 | 0.0136 | 2.8636 | 1.3533 | 1353.26 | 16.31 | 4573.42 |
PERIMETER_MID_ZN_4 | 1.9540 | 0.0000 | 1.9540 | 0.0091 | 1.9631 | 0.8721 | 1277.40 | 6.38 | 4659.22 |
PERIMETER_TOP_ZN_3 | 0.1647 | 0.0000 | 0.1647 | 0.0169 | 0.1817 | 0.1353 | 3016.09 | 49.17 | 2877.73 |
PERIMETER_TOP_ZN_2 | 0.1853 | 0.0000 | 0.1853 | 0.0113 | 0.1966 | 0.0872 | 1346.52 | 4.70 | 4591.78 |
PERIMETER_TOP_ZN_1 | 0.2827 | 0.0000 | 0.2827 | 0.0169 | 0.2996 | 0.1353 | 1381.42 | 5.72 | 4555.86 |
PERIMETER_TOP_ZN_4 | 0.1996 | 0.0000 | 0.1996 | 0.0113 | 0.2109 | 0.0872 | 1333.42 | 2.14 | 4607.44 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 10.9247 | 0.0000 | 10.9247 | 0.0000 | 10.9247 | 0.3384 | 318.80 | 971.35 | 4652.85 |
Total Facility | 222.3764 | 0.0000 | 222.3764 | 0.5367 | 222.9131 | 158.4706 | 4414.64 | 4373.40 | 5650.19 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 82151980.28 | 0.00 | 82151980.28 | 48026705.38 | 3759.64 | 4.46 | 4995.89 | 249.40 |
VAV_MID WITH REHEAT | 0.65E+09 | 0.00 | 0.65E+09 | 0.48E+09 | 4030.40 | 5.31 | 4724.29 | 161.14 |
VAV_TOP WITH REHEAT | 63756778.74 | 0.00 | 63756778.74 | 48026705.38 | 4109.90 | 2.28 | 4647.82 | 257.58 |
CAV_BAS | 51781104.37 | 0.00 | 51781104.37 | 37848132.68 | 5330.36 | 0.36 | 3429.28 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.48E+09 | 0.00 | 0.48E+09 | 10671554.30 | 882.30 | 0.00 | 7877.70 | 2253.50 |
AIRLOOP DATACENTER BOT | 353897.20 | 0.00 | 353897.20 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3538971.99 | 0.00 | 3538971.99 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 353897.20 | 0.00 | 353897.20 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.6745 | 0.0000 | 3.6745 | 1.5229 | 1181.71 | 3.63 | 4757.66 |
VAV_MID WITH REHEAT | 29.7594 | 0.0000 | 29.7594 | 15.2292 | 1285.15 | 4.39 | 4653.46 |
VAV_TOP WITH REHEAT | 2.9274 | 0.0000 | 2.9274 | 1.5229 | 1344.45 | 0.86 | 4597.69 |
CAV_BAS | 2.4203 | 0.0000 | 2.4203 | 1.2002 | 2513.36 | 0.36 | 3429.28 |
AIRLOOP DATACENTER BASEMENT | 15.8260 | 0.0000 | 15.8260 | 0.3384 | 318.80 | 0.00 | 5624.20 |
AIRLOOP DATACENTER BOT | 0.0165 | 0.0000 | 0.0165 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1654 | 0.0000 | 0.1654 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0165 | 0.0000 | 0.0165 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 3.41 | 3190.36 | 0.00 | 0.00 | 0.00 | 1846.07 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.09 | 2623.18 | 0.00 | 0.00 | 0.00 | 2271.11 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.59 | 2486.43 | 0.00 | 0.00 | 0.00 | 2538.15 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 696.62 | 2729.01 | 0.00 | 15.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 971.35 | 6906.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 15.4717 | 5.9103 | 0.0000 | 0.0000 | 0.0000 | 2.3884 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 49.6026 | 0.0000 | 0.0000 | 0.0000 | 24.1014 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 5.0918 | 0.0000 | 0.0000 | 0.0000 | 2.3816 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.7402 | 4.8215 | 0.0000 | 0.9764 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4904 | 20.1156 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0227 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2265 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0227 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:28
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1498 |
Defaulted Fields | 1184 |
Fields with Defaults | 3937 |
Autosized Fields | 337 |
Autosizable Fields | 416 |
Autocalculated Fields | 227 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:25:28
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 28229.16 | 294839.14 | 07-MAY-05:00 | 2144607.52 | 22-AUG-14:10 |
Electricity:Building | 17899.77 | 217189.06 | 14-MAY-17:20 | 1104084.83 | 01-DEC-16:30 |
Electricity:Zone:BASEMENT | 640.57 | 14055.89 | 01-JAN-00:10 | 32859.63 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 17899.77 | 217189.06 | 14-MAY-17:20 | 1104084.83 | 01-DEC-16:30 |
InteriorLights:Electricity | 3223.37 | 9932.90 | 14-MAY-17:20 | 325713.14 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:BASEMENT | 216.17 | 598.35 | 01-JAN-00:10 | 19402.09 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3223.37 | 9932.90 | 14-MAY-17:20 | 325713.14 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity | 3223.37 | 9932.90 | 14-MAY-17:20 | 325713.14 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 216.17 | 598.35 | 01-JAN-00:10 | 19402.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3223.37 | 9932.90 | 14-MAY-17:20 | 325713.14 | 02-JAN-16:30 |
Electricity:Zone:CORE_BOTTOM | 483.75 | 4990.59 | 01-JAN-00:10 | 34631.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4837.49 | 49905.77 | 01-JAN-00:10 | 346310.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1941.37 | 5373.60 | 01-JAN-00:10 | 174244.37 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1941.37 | 5373.60 | 01-JAN-00:10 | 174244.37 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 483.75 | 4990.58 | 01-JAN-00:10 | 34631.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 50.55 | 617.00 | 02-APR-17:10 | 4348.36 | 02-JAN-16:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 14.18 | 57.83 | 01-JAN-09:10 | 2187.81 | 02-JAN-16:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 14.18 | 57.83 | 01-JAN-09:10 | 2187.81 | 02-JAN-16:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 32.52 | 397.62 | 14-MAY-17:10 | 2802.25 | 02-JAN-16:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 9.08 | 37.27 | 01-JAN-07:50 | 1409.91 | 02-JAN-16:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 9.08 | 37.27 | 01-JAN-07:50 | 1409.91 | 02-JAN-16:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 50.27 | 617.01 | 26-MAR-17:10 | 4348.44 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 13.90 | 57.83 | 01-JAN-07:50 | 2187.86 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 13.90 | 57.83 | 01-JAN-07:50 | 2187.86 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 32.43 | 397.61 | 12-MAR-17:10 | 2802.24 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 9.00 | 37.27 | 01-JAN-09:10 | 1409.91 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 9.00 | 37.27 | 01-JAN-09:10 | 1409.91 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 505.12 | 6169.98 | 02-APR-17:10 | 43483.64 | 02-JAN-16:20 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 141.46 | 578.27 | 01-JAN-09:00 | 21878.12 | 02-JAN-16:20 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 141.46 | 578.27 | 01-JAN-09:00 | 21878.12 | 02-JAN-16:20 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 325.03 | 3976.17 | 16-APR-17:10 | 28022.51 | 02-JAN-16:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 90.68 | 372.66 | 01-JAN-07:50 | 14099.09 | 02-JAN-16:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 90.68 | 372.66 | 01-JAN-07:50 | 14099.09 | 02-JAN-16:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 502.54 | 6170.07 | 26-MAR-17:10 | 43484.45 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 138.88 | 578.28 | 01-JAN-07:50 | 21878.60 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 138.88 | 578.28 | 01-JAN-07:50 | 21878.60 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 324.14 | 3976.14 | 12-MAR-17:10 | 28022.42 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 89.79 | 372.66 | 01-JAN-09:00 | 14099.09 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 89.79 | 372.66 | 01-JAN-09:00 | 14099.09 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 50.51 | 617.00 | 02-APR-17:10 | 4348.36 | 02-JAN-16:20 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 14.15 | 57.83 | 01-JAN-09:00 | 2187.81 | 02-JAN-16:20 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 14.15 | 57.83 | 01-JAN-09:00 | 2187.81 | 02-JAN-16:20 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 32.50 | 397.62 | 16-APR-17:10 | 2802.25 | 02-JAN-16:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 9.07 | 37.27 | 01-JAN-07:50 | 1409.91 | 02-JAN-16:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 9.07 | 37.27 | 01-JAN-07:50 | 1409.91 | 02-JAN-16:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 50.25 | 617.01 | 26-MAR-17:10 | 4348.44 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 13.89 | 57.83 | 01-JAN-07:50 | 2187.86 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 13.89 | 57.83 | 01-JAN-07:50 | 2187.86 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 32.41 | 397.61 | 12-MAR-17:10 | 2802.24 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 8.98 | 37.27 | 01-JAN-09:00 | 1409.91 | 02-JAN-16:30 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 8.98 | 37.27 | 01-JAN-09:00 | 1409.91 | 02-JAN-16:30 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7557.51 | 95212.03 | 01-JAN-00:10 | 385103.08 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 62.65 | 303.90 | 01-JAN-00:10 | 5470.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 62.65 | 303.90 | 01-JAN-00:10 | 5470.56 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 159.04 | 1973.61 | 01-JAN-00:10 | 8244.54 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1590.36 | 19736.13 | 01-JAN-00:10 | 82445.36 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 51.55 | 250.08 | 01-JAN-00:10 | 4501.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 51.55 | 250.08 | 01-JAN-00:10 | 4501.14 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 159.04 | 1973.61 | 01-JAN-00:10 | 8244.54 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 2404.28 | 3865.24 | 02-JAN-04:40 | 482613.65 | 01-JUN-15:30 |
HeatRejection:Electricity | 764.95 | 66.31 | 02-JAN-07:20 | 91748.49 | 30-MAY-10:30 |
General:HeatRejection:Electricity | 764.95 | 66.31 | 02-JAN-07:20 | 91748.49 | 30-MAY-10:30 |
Electricity:HVAC | 5061.95 | 49279.14 | 15-JAN-10:30 | 505526.47 | 30-AUG-15:20 |
ExteriorEquipment:Electricity | 2566.61 | 20217.42 | 01-JAN-00:10 | 233436.21 | 03-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 55.01 | 979.82 | 01-JAN-00:10 | 3454.84 | 01-DEC-16:40 |
ElectricityPurchased:Facility | 28229.16 | 294839.14 | 07-MAY-05:00 | 2144607.52 | 22-AUG-14:10 |
ElectricityPurchased:Plant | 28229.16 | 294839.14 | 07-MAY-05:00 | 2144607.52 | 22-AUG-14:10 |
Cogeneration:ElectricityPurchased | 28229.16 | 294839.14 | 07-MAY-05:00 | 2144607.52 | 22-AUG-14:10 |
General:Cogeneration:ElectricityPurchased | 28229.16 | 294839.14 | 07-MAY-05:00 | 2144607.52 | 22-AUG-14:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 28229.16 | 294839.14 | 07-MAY-05:00 | 2144607.52 | 22-AUG-14:10 |
ElectricityNet:Plant | 28229.16 | 294839.14 | 07-MAY-05:00 | 2144607.52 | 22-AUG-14:10 |
Cogeneration:ElectricityNet | 28229.16 | 294839.14 | 07-MAY-05:00 | 2144607.52 | 22-AUG-14:10 |
General:Cogeneration:ElectricityNet | 28229.16 | 294839.14 | 07-MAY-05:00 | 2144607.52 | 22-AUG-14:10 |
Fans:Electricity | 2470.36 | 46710.23 | 01-JAN-15:20 | 306094.32 | 08-AUG-14:30 |
General:Fans:Electricity | 2470.36 | 46710.23 | 01-JAN-15:20 | 306094.32 | 08-AUG-14:30 |
ExteriorLights:Electricity | 351.57 | 0.00 | 01-JAN-07:30 | 40855.88 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 351.57 | 0.00 | 01-JAN-07:30 | 40855.88 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 2505.76 | 19200.00 | 01-JAN-00:10 | 229608.34 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 46.34 | 0.00 | 01-JAN-00:10 | 5613.48 | 02-JAN-07:10 |
General:HeatRecovery:Electricity | 46.34 | 0.00 | 01-JAN-00:10 | 5613.48 | 02-JAN-07:10 |
Cooling:Electricity | 2005.60 | 1399.55 | 03-JAN-08:00 | 463471.92 | 24-AUG-16:50 |
General:Cooling:Electricity | 2005.60 | 1399.55 | 03-JAN-08:00 | 463471.92 | 24-AUG-16:50 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1276.09 | 0.00 | 03-JAN-09:20 | 100000.00 | 02-FEB-06:00 |
General:Humidifier:Electricity | 1276.09 | 0.00 | 03-JAN-09:20 | 100000.00 | 02-FEB-06:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 426.30 | 0.00 | 01-JAN-00:10 | 53261.46 | 06-FEB-12:30 |
Water Heater:WaterSystems:Electricity | 426.30 | 0.00 | 01-JAN-00:10 | 53261.46 | 06-FEB-12:30 |
Pumps:Electricity | 421.59 | 3793.59 | 01-JAN-00:40 | 62600.23 | 03-OCT-13:40 |
General:Pumps:Electricity | 421.59 | 3793.59 | 01-JAN-00:40 | 62600.23 | 03-OCT-13:40 |
WIRED_LTG_ELECTRICITY | 90.58 | 0.00 | 01-JAN-00:10 | 9152.54 | 02-JAN-16:40 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 838.46 | 0.00 | 01-JAN-00:40 | 1710520.23 | 02-JAN-05:10 |
NaturalGas:Plant | 838.46 | 0.00 | 01-JAN-00:40 | 1710520.23 | 02-JAN-05:10 |
Heating:NaturalGas | 838.46 | 0.00 | 01-JAN-00:40 | 1710520.23 | 02-JAN-05:10 |
Boiler:Heating:NaturalGas | 838.46 | 0.00 | 01-JAN-00:40 | 1710520.23 | 02-JAN-05:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 12157.47 | 2528.95 | 03-JAN-09:10 | 2898671.68 | 24-AUG-16:50 |
PlantLoopCoolingDemand:HVAC | 12157.47 | 2528.95 | 03-JAN-09:10 | 2898671.68 | 24-AUG-16:50 |
CoolingCoils:PlantLoopCoolingDemand | 12157.47 | 2528.95 | 03-JAN-09:10 | 2898671.68 | 24-AUG-16:50 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 7878.92 | 0.00 | 24-JAN-00:10 | 0.00 | 30-AUG-16:00 |
Water:HVAC | 474.71 | 0.00 | 03-JAN-09:20 | 0.00 | 22-FEB-05:10 |
Humidifier:Water | 474.71 | 0.00 | 03-JAN-09:20 | 0.00 | 22-FEB-05:10 |
General:Humidifier:Water | 474.71 | 0.00 | 03-JAN-09:20 | 0.00 | 22-FEB-05:10 |
MainsWater:Facility | 7878.92 | 0.00 | 24-JAN-00:10 | 0.00 | 30-AUG-16:00 |
MainsWater:HVAC | 474.71 | 0.00 | 03-JAN-09:20 | 0.00 | 22-FEB-05:10 |
Humidifier:MainsWater | 474.71 | 0.00 | 03-JAN-09:20 | 0.00 | 22-FEB-05:10 |
General:Humidifier:MainsWater | 474.71 | 0.00 | 03-JAN-09:20 | 0.00 | 22-FEB-05:10 |
Water:Plant | 7404.21 | 0.00 | 01-JAN-00:10 | 0.00 | 24-AUG-16:50 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
MainsWater:Plant | 7404.21 | 0.00 | 01-JAN-00:10 | 0.00 | 24-AUG-16:50 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 5124.04 | 0.00 | 01-JAN-00:10 | 0.00 | 24-AUG-16:50 |
General:HeatRejection:Water | 5124.04 | 0.00 | 01-JAN-00:10 | 0.00 | 24-AUG-16:50 |
HeatRejection:MainsWater | 5124.04 | 0.00 | 01-JAN-00:10 | 0.00 | 24-AUG-16:50 |
General:HeatRejection:MainsWater | 5124.04 | 0.00 | 01-JAN-00:10 | 0.00 | 24-AUG-16:50 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 54706.79 | 94369.18 | 02-JAN-04:40 | 11080182.07 | 24-AUG-16:50 |
EnergyTransfer:Building | 19112.79 | 88528.24 | 16-JAN-15:40 | 1693001.47 | 31-AUG-14:50 |
EnergyTransfer:Zone:BASEMENT | 538.59 | 0.00 | 01-JAN-00:10 | 106884.11 | 23-AUG-06:20 |
Heating:EnergyTransfer | 408.17 | 0.00 | 19-JAN-22:10 | 1314713.67 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 408.17 | 0.00 | 19-JAN-22:10 | 1314713.67 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 18704.62 | 85549.64 | 02-JAN-05:00 | 1693001.47 | 31-AUG-14:50 |
Cooling:EnergyTransfer:Zone:BASEMENT | 538.59 | 0.00 | 01-JAN-00:10 | 106884.11 | 23-AUG-06:20 |
General:Cooling:EnergyTransfer | 18704.62 | 85549.64 | 02-JAN-05:00 | 1693001.47 | 31-AUG-14:50 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 538.59 | 0.00 | 01-JAN-00:10 | 106884.11 | 23-AUG-06:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 691.88 | 0.00 | 01-JAN-00:10 | 69208.75 | 14-AUG-07:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 691.88 | 0.00 | 01-JAN-00:10 | 69208.75 | 14-AUG-07:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 691.88 | 0.00 | 01-JAN-00:10 | 69208.75 | 14-AUG-07:20 |
EnergyTransfer:Zone:CORE_MID | 4473.66 | 0.00 | 01-JAN-00:40 | 472525.98 | 11-JUL-15:50 |
Heating:EnergyTransfer:Zone:CORE_MID | 6.90 | 0.00 | 01-JAN-00:10 | 424939.41 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 6.90 | 0.00 | 01-JAN-00:10 | 424939.41 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4466.76 | 0.00 | 01-JAN-00:40 | 472525.98 | 11-JUL-15:50 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4466.76 | 0.00 | 01-JAN-00:40 | 472525.98 | 11-JUL-15:50 |
EnergyTransfer:Zone:CORE_TOP | 421.52 | 0.00 | 01-JAN-00:40 | 72727.06 | 02-JAN-05:30 |
Heating:EnergyTransfer:Zone:CORE_TOP | 9.17 | 0.00 | 01-JAN-00:40 | 72727.06 | 02-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 9.17 | 0.00 | 01-JAN-00:40 | 72727.06 | 02-JAN-05:30 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 412.35 | 0.00 | 01-JAN-00:20 | 53819.00 | 30-MAY-14:30 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 412.35 | 0.00 | 01-JAN-00:20 | 53819.00 | 30-MAY-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 82.95 | 0.00 | 01-JAN-00:10 | 13383.12 | 17-AUG-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.31 | 0.00 | 01-JAN-00:10 | 6250.27 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.31 | 0.00 | 01-JAN-00:10 | 6250.27 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 82.64 | 0.00 | 01-JAN-00:10 | 13383.12 | 17-AUG-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 82.64 | 0.00 | 01-JAN-00:10 | 13383.12 | 17-AUG-13:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 75.56 | 0.00 | 01-JAN-00:10 | 16388.54 | 02-AUG-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.23 | 0.00 | 01-JAN-00:10 | 4128.64 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.23 | 0.00 | 01-JAN-00:10 | 4128.64 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 75.33 | 0.00 | 01-JAN-00:10 | 16388.54 | 02-AUG-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 75.33 | 0.00 | 01-JAN-00:10 | 16388.54 | 02-AUG-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 124.00 | 0.00 | 01-JAN-00:10 | 21344.56 | 04-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.52 | 0.00 | 01-JAN-00:10 | 9695.10 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.52 | 0.00 | 01-JAN-00:10 | 9695.10 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 123.48 | 0.00 | 01-JAN-00:10 | 21344.56 | 04-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 123.48 | 0.00 | 01-JAN-00:10 | 21344.56 | 04-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 105.87 | 0.00 | 01-JAN-00:10 | 19349.85 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.03 | 0.00 | 01-JAN-00:10 | 2926.18 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.03 | 0.00 | 01-JAN-00:10 | 2926.18 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 105.84 | 0.00 | 01-JAN-00:10 | 19349.85 | 15-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 105.84 | 0.00 | 01-JAN-00:10 | 19349.85 | 15-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 608.06 | 0.00 | 01-JAN-00:40 | 130603.42 | 02-JAN-04:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 82.85 | 0.00 | 01-JAN-00:40 | 130603.42 | 02-JAN-04:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 82.85 | 0.00 | 01-JAN-00:40 | 130603.42 | 02-JAN-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 525.21 | 0.00 | 01-JAN-00:10 | 107090.36 | 19-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 525.21 | 0.00 | 01-JAN-00:10 | 107090.36 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 626.34 | 0.00 | 01-JAN-00:40 | 157553.86 | 26-JUN-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 43.28 | 0.00 | 01-JAN-00:40 | 132194.86 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 43.28 | 0.00 | 01-JAN-00:40 | 132194.86 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 583.06 | 0.00 | 01-JAN-00:20 | 157553.86 | 26-JUN-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 583.06 | 0.00 | 01-JAN-00:20 | 157553.86 | 26-JUN-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1049.39 | 0.00 | 01-JAN-00:40 | 214866.92 | 04-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 42.05 | 0.00 | 01-JAN-00:40 | 177235.09 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 42.05 | 0.00 | 01-JAN-00:40 | 177235.09 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1007.34 | 0.00 | 01-JAN-00:20 | 214866.92 | 04-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1007.34 | 0.00 | 01-JAN-00:20 | 214866.92 | 04-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 672.47 | 0.00 | 01-JAN-00:40 | 170697.40 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 33.35 | 0.00 | 01-JAN-00:40 | 126553.01 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 33.35 | 0.00 | 01-JAN-00:40 | 126553.01 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 639.11 | 0.00 | 01-JAN-00:20 | 170697.40 | 15-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 639.11 | 0.00 | 01-JAN-00:20 | 170697.40 | 15-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 71.87 | 0.00 | 01-JAN-00:40 | 15588.46 | 06-FEB-04:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 21.85 | 0.00 | 01-JAN-00:40 | 15588.46 | 06-FEB-04:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 21.85 | 0.00 | 01-JAN-00:40 | 15588.46 | 06-FEB-04:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 50.02 | 0.00 | 01-JAN-00:10 | 12087.50 | 19-JUN-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 50.02 | 0.00 | 01-JAN-00:10 | 12087.50 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 67.35 | 0.00 | 01-JAN-00:40 | 16016.83 | 26-JUN-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 11.34 | 0.00 | 01-JAN-00:40 | 15893.91 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 11.34 | 0.00 | 01-JAN-00:40 | 15893.91 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 56.00 | 0.00 | 01-JAN-00:10 | 16016.83 | 26-JUN-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 56.00 | 0.00 | 01-JAN-00:10 | 16016.83 | 26-JUN-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 107.74 | 0.00 | 01-JAN-00:40 | 22758.44 | 04-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 12.76 | 0.00 | 01-JAN-00:40 | 20241.91 | 06-FEB-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 12.76 | 0.00 | 01-JAN-00:40 | 20241.91 | 06-FEB-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 94.99 | 0.00 | 01-JAN-00:10 | 22758.44 | 04-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 94.99 | 0.00 | 01-JAN-00:10 | 22758.44 | 04-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 70.80 | 0.00 | 01-JAN-00:40 | 17696.70 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 9.02 | 0.00 | 01-JAN-00:40 | 14702.53 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 9.02 | 0.00 | 01-JAN-00:40 | 14702.53 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 61.79 | 0.00 | 01-JAN-00:20 | 17696.70 | 15-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 61.79 | 0.00 | 01-JAN-00:20 | 17696.70 | 15-AUG-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 75.19 | 0.00 | 01-JAN-00:10 | 13346.59 | 14-AUG-05:30 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 2.35 | 0.00 | 01-JAN-00:10 | 4021.92 | 02-JAN-11:30 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 2.35 | 0.00 | 01-JAN-00:10 | 4021.92 | 02-JAN-11:30 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 72.84 | 0.00 | 01-JAN-00:10 | 13346.59 | 14-AUG-05:30 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 72.84 | 0.00 | 01-JAN-00:10 | 13346.59 | 14-AUG-05:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 509.35 | 0.00 | 01-JAN-00:40 | 169267.99 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 93.54 | 0.00 | 01-JAN-00:40 | 169267.99 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 93.54 | 0.00 | 01-JAN-00:40 | 169267.99 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 415.81 | 0.00 | 01-JAN-00:10 | 81980.56 | 11-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 415.81 | 0.00 | 01-JAN-00:10 | 81980.56 | 11-JUL-15:30 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 99.76 | 0.00 | 01-JAN-00:40 | 27764.21 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 34.32 | 0.00 | 01-JAN-00:40 | 27764.21 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 34.32 | 0.00 | 01-JAN-00:40 | 27764.21 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 65.43 | 0.00 | 01-JAN-00:10 | 22158.87 | 19-JUN-13:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 65.43 | 0.00 | 01-JAN-00:10 | 22158.87 | 19-JUN-13:30 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 139.10 | 153.82 | 02-JAN-05:00 | 8310.47 | 23-APR-17:50 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 139.10 | 153.82 | 02-JAN-05:00 | 8310.47 | 23-APR-17:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 139.10 | 153.82 | 02-JAN-05:00 | 8310.47 | 23-APR-17:50 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1202.42 | 7.23 | 31-JAN-00:30 | 78579.13 | 31-AUG-17:30 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 3.55 | 0.00 | 02-JAN-07:10 | 5401.19 | 03-JAN-01:00 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 3.55 | 0.00 | 02-JAN-07:10 | 5401.19 | 03-JAN-01:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1198.86 | 0.00 | 01-JAN-00:10 | 78579.13 | 31-AUG-17:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1198.86 | 0.00 | 01-JAN-00:10 | 78579.13 | 31-AUG-17:30 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 111.68 | 0.55 | 07-JAN-14:10 | 7933.73 | 13-AUG-17:20 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.75 | 0.00 | 02-JAN-07:10 | 582.01 | 16-JAN-18:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.75 | 0.00 | 02-JAN-07:10 | 582.01 | 16-JAN-18:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 110.93 | 0.00 | 01-JAN-00:10 | 7933.73 | 13-AUG-17:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 110.93 | 0.00 | 01-JAN-00:10 | 7933.73 | 13-AUG-17:20 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7187.24 | 85395.82 | 02-JAN-05:00 | 370894.52 | 18-AUG-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7187.24 | 85395.82 | 02-JAN-05:00 | 370894.52 | 18-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7187.24 | 85395.82 | 02-JAN-05:00 | 370894.52 | 18-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 1015.59 | 0.00 | 01-JAN-00:40 | 1396973.63 | 02-JAN-06:20 |
PlantLoopHeatingDemand:Plant | 421.10 | 0.00 | 01-JAN-00:10 | 52999.32 | 09-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 421.10 | 0.00 | 01-JAN-00:10 | 52999.32 | 09-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 421.10 | 0.00 | 01-JAN-00:10 | 52999.32 | 09-FEB-12:10 |
EnergyTransfer:HVAC | 12837.42 | 1103.09 | 15-JAN-10:30 | 2878134.26 | 24-AUG-16:50 |
HeatingCoils:EnergyTransfer | 594.49 | 0.00 | 01-JAN-00:40 | 1390629.98 | 02-JAN-06:20 |
PlantLoopHeatingDemand:HVAC | 594.49 | 0.00 | 01-JAN-00:40 | 1390629.98 | 02-JAN-06:20 |
HeatingCoils:PlantLoopHeatingDemand | 594.49 | 0.00 | 01-JAN-00:40 | 1390629.98 | 02-JAN-06:20 |
CoolingCoils:EnergyTransfer | 10943.32 | 1103.09 | 15-JAN-10:30 | 2708003.67 | 24-AUG-16:50 |
HeatRecoveryForHeating:EnergyTransfer | 831.09 | 0.00 | 01-JAN-00:10 | 613524.69 | 06-FEB-07:10 |
HeatRecoveryForCooling:EnergyTransfer | 468.52 | 0.00 | 01-JAN-00:10 | 520377.81 | 08-JUL-12:00 |
EnergyTransfer:Plant | 22756.57 | 0.00 | 01-JAN-00:40 | 7188524.99 | 01-JUN-15:30 |
LoopToLoop:EnergyTransfer | 7004.93 | 0.00 | 01-JAN-00:10 | 2177491.47 | 24-AUG-16:50 |
WaterSystems:EnergyTransfer | 421.10 | 0.00 | 01-JAN-00:10 | 52999.32 | 09-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 421.10 | 0.00 | 01-JAN-00:10 | 52999.32 | 09-FEB-12:10 |
Boilers:EnergyTransfer | 591.40 | 0.00 | 01-JAN-00:40 | 1420726.80 | 02-JAN-05:10 |
Chillers:EnergyTransfer | 6973.85 | 0.00 | 01-JAN-00:10 | 2356561.85 | 01-JUN-15:30 |
HeatRejection:EnergyTransfer | 7765.30 | 0.00 | 01-JAN-00:10 | 2657072.44 | 01-JUN-15:30 |
General:HeatRejection:EnergyTransfer | 7765.30 | 0.00 | 01-JAN-00:10 | 2657072.44 | 01-JUN-15:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:28
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -538.573 | 0.000 | 0.000 | 84.425 | 216.171 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -186.420 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -691.883 | 0.000 | 0.000 | 83.449 | 194.137 | 289.614 | 0.000 | 0.000 | 0.000 | 124.684 | 0.000 | 0.000 | 0.000 | 0.000 | -0.009 |
CORE_MID | 0.000 | 0.000 | 6.904 | -4466.734 | 0.000 | 0.000 | 849.531 | 1941.366 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1227.195 |
CORE_TOP | 0.000 | 0.000 | 9.170 | -412.350 | 0.000 | 0.000 | 87.670 | 194.137 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -168.241 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.310 | -82.643 | 0.000 | 0.000 | 10.816 | 14.180 | 36.365 | 31.124 | 0.000 | 0.048 | 55.935 | 0.000 | -62.227 | 0.000 | -3.909 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.226 | -75.333 | 0.000 | 0.000 | 7.001 | 9.085 | 23.435 | 57.725 | 0.000 | 0.034 | 18.429 | 0.000 | -38.037 | 0.000 | -2.565 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.518 | -123.481 | 0.000 | 0.000 | 10.716 | 13.905 | 36.366 | 118.295 | 0.000 | 0.048 | 3.909 | 0.000 | -56.355 | 0.000 | -3.922 | -0.001 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.030 | -105.844 | 0.000 | 0.000 | 6.869 | 8.995 | 23.435 | 57.784 | 0.000 | 0.032 | 55.147 | 0.000 | -43.615 | 0.000 | -2.832 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 82.853 | -525.203 | 0.000 | 0.000 | 113.033 | 141.463 | 363.654 | 324.433 | 0.000 | 1.151 | 129.951 | 0.000 | -550.796 | 0.000 | -80.540 | -0.003 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 43.278 | -583.054 | 0.000 | 0.000 | 53.221 | 90.679 | 234.352 | 581.301 | 0.000 | 0.762 | 0.011 | 0.000 | -348.148 | 0.000 | -54.676 | -17.717 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 42.052 | -1007.326 | 0.000 | 0.000 | 108.929 | 138.876 | 363.660 | 1181.774 | 0.000 | 1.094 | 0.024 | 0.000 | -534.500 | 0.000 | -86.551 | -208.008 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 33.352 | -639.113 | 0.000 | 0.000 | 72.530 | 89.786 | 234.351 | 590.844 | 0.000 | 0.744 | 46.249 | 0.000 | -372.112 | 0.000 | -56.629 | -0.004 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 21.848 | -50.021 | 0.000 | 0.000 | 11.444 | 14.145 | 36.365 | 32.777 | 0.000 | 0.134 | 0.000 | 0.000 | -51.711 | 0.000 | -9.419 | -5.563 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 11.341 | -56.004 | 0.000 | 0.000 | 7.298 | 9.067 | 23.435 | 58.412 | 0.000 | 0.089 | 0.000 | 0.000 | -32.837 | 0.000 | -6.411 | -14.390 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 12.755 | -94.984 | 0.000 | 0.000 | 11.055 | 13.886 | 36.366 | 118.647 | 0.000 | 0.130 | 0.000 | 0.000 | -50.235 | 0.000 | -10.095 | -37.525 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 9.017 | -61.787 | 0.000 | 0.000 | 7.339 | 8.978 | 23.435 | 59.215 | 0.000 | 0.089 | 0.000 | 0.000 | -35.288 | 0.000 | -6.670 | -4.327 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -139.102 | 0.000 | 0.000 | 0.950 | 5.155 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -20.884 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 3.551 | -1198.865 | 0.000 | 0.000 | 9.511 | 51.551 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -404.554 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.753 | -110.928 | 0.000 | 0.000 | 0.953 | 5.155 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -49.815 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7187.241 | 0.000 | 0.000 | 20.563 | 62.653 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -390.832 |
GROUNDFLOOR_PLENUM | 2.349 | -72.838 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.078 | 78.819 | 0.000 | 0.000 | 0.000 | -8.408 | 0.000 |
MIDFLOOR_PLENUM | 93.543 | -415.811 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.586 | 460.851 | 0.000 | 0.000 | 0.000 | -140.169 | -0.002 |
TOPFLOOR_PLENUM | 34.324 | -65.430 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.130 | 45.693 | 0.000 | 0.000 | 0.000 | -14.716 | -0.003 |
Total Facility | 130.216 | -554.079 | 277.959 | -18150.466 | 0.000 | 0.000 | 1557.304 | 3223.371 | 14676.396 | 3212.330 | 0.000 | 6.148 | 1019.704 | 0.000 | -2175.862 | 0.000 | -487.514 | -2735.492 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 23-AUG-06:11 | 0.00 | 0.00 | 0.00 | -125872.52 | 0.00 | 0.00 | 1123.78 | 6467.36 | 13457.54 | 0.00 | 0.00 | 0.00 | 104823.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 13-NOV-05:11 | 0.00 | 0.00 | 0.00 | -98792.20 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 92317.19 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 07-AUG-04:14 | 0.00 | 0.00 | 0.00 | -862125.76 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 797375.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 07-AUG-04:12 | 0.00 | 0.00 | 0.00 | -88610.22 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 82135.24 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 09-JUL-14:21 | 0.00 | 0.00 | 0.00 | -18035.97 | 0.00 | 0.00 | 39.51 | 57.83 | 720.18 | 6596.55 | 0.00 | 30.76 | 10591.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-SEP-08:51 | 0.00 | 0.00 | 0.00 | -24972.92 | 0.00 | 0.00 | 18.56 | 37.27 | 464.11 | 17152.57 | 0.00 | 0.00 | 7331.06 | 0.00 | -0.00 | 0.00 | -30.66 | 0.00 |
PERIMETER_BOT_ZN_1 | 04-SEP-12:11 | 0.00 | 0.00 | 0.00 | -28849.86 | 0.00 | 0.00 | 29.89 | 57.83 | 720.19 | 23510.14 | 0.00 | 0.00 | 4572.81 | 0.00 | -0.00 | 0.00 | -41.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 04-JUL-16:21 | 0.00 | 0.00 | 0.00 | -30844.57 | 0.00 | 0.00 | 16.02 | 37.27 | 464.11 | 16121.69 | 0.00 | 0.00 | 14255.58 | 0.00 | -0.00 | 0.00 | -50.10 | 0.00 |
PERIMETER_MID_ZN_3 | 09-JUL-14:21 | 0.00 | 0.00 | 0.00 | -163697.24 | 0.00 | 0.00 | 420.53 | 578.27 | 7201.84 | 67056.33 | 0.00 | 897.02 | 87543.25 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 29-MAY-08:31 | 0.00 | 0.00 | 0.00 | -267039.68 | 0.00 | 0.00 | 184.26 | 372.66 | 4641.14 | 183448.13 | 0.00 | 0.00 | 79150.23 | 0.00 | -0.00 | 0.00 | -756.73 | 0.00 |
PERIMETER_MID_ZN_1 | 04-SEP-11:41 | 0.00 | 0.00 | 0.00 | -286100.48 | 0.00 | 0.00 | 300.65 | 578.28 | 7201.95 | 239255.67 | 0.00 | 0.00 | 39733.16 | 0.00 | -0.00 | 0.00 | -969.23 | 0.00 |
PERIMETER_MID_ZN_4 | 02-JUL-16:21 | 0.00 | 0.00 | 0.00 | -282210.84 | 0.00 | 0.00 | 169.74 | 372.66 | 4641.11 | 178759.74 | 0.00 | 0.00 | 100256.51 | 0.00 | -0.00 | 0.00 | -1988.92 | 0.00 |
PERIMETER_TOP_ZN_3 | 13-AUG-15:31 | 0.00 | 0.00 | 0.00 | -19191.10 | 0.00 | 0.00 | 39.95 | 57.83 | 720.18 | 4802.19 | 0.00 | 79.02 | 13491.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 02-JUL-07:41 | 0.00 | 0.00 | 0.00 | -26596.40 | 0.00 | 0.00 | 19.37 | 37.27 | 464.11 | 20173.73 | 0.00 | 0.00 | 5979.38 | 0.00 | -0.00 | 0.00 | -77.46 | 0.00 |
PERIMETER_TOP_ZN_1 | 13-AUG-13:31 | 0.00 | 0.00 | 0.00 | -30087.54 | 0.00 | 0.00 | 30.38 | 57.83 | 720.19 | 16299.23 | 0.00 | 62.14 | 12917.77 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 02-JUL-16:21 | 0.00 | 0.00 | 0.00 | -29919.27 | 0.00 | 0.00 | 15.89 | 37.27 | 464.11 | 17760.49 | 0.00 | 0.00 | 11905.09 | 0.00 | -0.00 | 0.00 | -263.57 | 0.00 |
DATACENTER_BOT_ZN_6 | 23-APR-17:47 | 0.00 | 0.00 | 0.00 | -8310.47 | 0.00 | 0.00 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 491.04 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 31-AUG-17:30 | 0.00 | 0.00 | 0.00 | -78577.09 | 0.00 | 0.00 | 106.03 | 1500.36 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -973.53 |
DATACENTER_TOP_ZN_6 | 13-AUG-17:15 | 0.00 | 0.00 | 0.00 | -7933.72 | 0.00 | 0.00 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 114.29 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 22-AUG-14:43 | 0.00 | 0.00 | 0.00 | -396776.93 | 0.00 | 0.00 | 2183.08 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 9490.77 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 26-JUN-05:15 | 0.00 | -15716.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15750.68 | 0.00 | -0.00 | 0.00 | -34.04 | 0.00 |
MIDFLOOR_PLENUM | 06-FEB-04:11 | 0.00 | -101750.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133796.52 | 0.00 | -0.00 | 0.00 | -32045.64 | 0.00 |
TOPFLOOR_PLENUM | 30-MAY-13:17 | 0.00 | -22745.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.41 | 22681.17 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 19-AUG-05:02 | 0.00 | -50125.87 | 0.00 | -1923439.05 | 0.00 | 0.00 | 15407.24 | 10917.52 | 616289.16 | 0.00 | 0.00 | 0.00 | 1401734.21 | 0.00 | -68227.34 | 0.00 | -2555.86 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-04:01 | 0.00 | 0.00 | 495208.92 | 0.00 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -559958.76 |
CORE_TOP | 02-JAN-04:01 | 0.00 | 0.00 | 82536.54 | 0.00 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -89011.52 |
PERIMETER_BOT_ZN_3 | 02-JAN-05:01 | 0.00 | 0.00 | 12703.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6814.56 | 0.00 | -318.86 | -6382.61 |
PERIMETER_BOT_ZN_2 | 02-JAN-05:01 | 0.00 | 0.00 | 10495.07 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4454.18 | 0.00 | -213.03 | -6351.80 |
PERIMETER_BOT_ZN_1 | 02-JAN-04:01 | 0.00 | 0.00 | 16666.87 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6384.17 | 0.00 | -285.99 | -10809.76 |
PERIMETER_BOT_ZN_4 | 02-JAN-05:01 | 0.00 | 0.00 | 7764.45 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4663.60 | 0.00 | -217.55 | -3407.25 |
PERIMETER_MID_ZN_3 | 01-JAN-22:02 | 0.00 | 0.00 | 147089.88 | 0.00 | 0.00 | 0.00 | 0.00 | 674.71 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -55014.95 | 0.00 | -15593.64 | -82747.70 |
PERIMETER_MID_ZN_2 | 01-JAN-22:02 | 0.00 | 0.00 | 180384.45 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 3603.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -35968.80 | 0.00 | -10759.46 | -137694.50 |
PERIMETER_MID_ZN_1 | 02-JAN-02:42 | 0.00 | 0.00 | 211727.28 | 0.00 | 0.00 | 0.00 | 0.00 | 674.72 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -57417.09 | 0.00 | -7125.31 | -155315.33 |
PERIMETER_MID_ZN_4 | 01-JAN-22:02 | 0.00 | 0.00 | 178706.87 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -37362.28 | 0.00 | -10848.50 | -134534.39 |
PERIMETER_TOP_ZN_3 | 05-FEB-22:42 | 0.00 | 0.00 | 17011.84 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 559.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5927.72 | 0.00 | -2590.57 | -9120.18 |
PERIMETER_TOP_ZN_2 | 01-JAN-22:02 | 0.00 | 0.00 | 20384.63 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 360.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3527.81 | 0.00 | -1317.03 | -15943.62 |
PERIMETER_TOP_ZN_1 | 02-JAN-02:42 | 0.00 | 0.00 | 23477.62 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5619.51 | 0.00 | -869.46 | -17801.70 |
PERIMETER_TOP_ZN_4 | 01-JAN-22:02 | 0.00 | 0.00 | 21259.50 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 360.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3664.92 | 0.00 | -1329.78 | -16668.63 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 03-JAN-01:00 | 0.00 | 0.00 | 5401.19 | 0.00 | 0.00 | 0.00 | 0.00 | 250.08 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25137.32 |
DATACENTER_TOP_ZN_6 | 16-JAN-17:55 | 0.00 | 0.00 | 587.98 | 0.00 | 0.00 | 0.00 | 6.35 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2567.94 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 26-DEC-05:11 | 12565.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -473.68 | -12092.08 |
MIDFLOOR_PLENUM | 02-JAN-06:23 | 179615.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2735.76 | -176879.92 |
TOPFLOOR_PLENUM | 06-FEB-05:10 | 29321.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3633.79 | -25687.69 |
Total Facility | 02-JAN-06:01 | 41060.24 | 101830.63 | 1311885.21 | -101830.63 | 0.00 | 0.00 | 22811.15 | 10917.52 | 261414.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -245910.92 | 0.00 | -11719.94 | -1390458.22 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:28
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 11.0211 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.7833 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 105.2506 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 91.7835 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 10.9647 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.9086 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.5428 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.5428 | 0.2165 | 1.0000 | Not calculated | 1.2002 | 0.2165 | ||
AIRLOOP DATACENTER BASEMENT | 24.5476 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.5478 | 0.0138 | 1.0000 | Not calculated | 0.3384 | 0.0138 | ||
AIRLOOP DATACENTER BOT | 0.4815 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4815 | 0.0325 | 1.0000 | Not calculated | 0.0156 | 0.0325 | ||
AIRLOOP DATACENTER MID | 4.6067 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.6067 | 0.0339 | 1.0000 | Not calculated | 0.1563 | 0.0339 | ||
AIRLOOP DATACENTER TOP | 0.4692 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4692 | 0.0333 | 1.0000 | Not calculated | 0.0156 | 0.0333 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.5106 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.0182 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 52.6253 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 29.5888 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.4824 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.0516 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 0.0000 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 0.0000 | 1.0000 | 1.0000 | Not calculated | 1.2002 | |||
AIRLOOP DATACENTER BASEMENT | 24.5476 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.5476 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0138 | ||
AIRLOOP DATACENTER BOT | 0.4815 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4815 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0325 | ||
AIRLOOP DATACENTER MID | 4.6067 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.6067 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0339 | ||
AIRLOOP DATACENTER TOP | 0.4692 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4692 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0333 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 5.5428 | 5.5428 | 0.0000 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.8468 | 5.8468 | 1.9411 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 55.0486 | 55.0486 | 19.0468 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.5994 | 5.5994 | 1.9486 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0058 | 1.0058 | 0.2434 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2330 | 1.2330 | 0.2466 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4327 | 1.4327 | 0.2865 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5029 | 1.5029 | 0.3006 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.4641 | 9.4641 | 2.3944 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.0834 | 13.0834 | 2.6167 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.0614 | 14.0614 | 2.8123 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.5931 | 13.5931 | 2.7186 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0708 | 1.0708 | 0.2441 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3307 | 1.3307 | 0.2661 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5224 | 1.5224 | 0.3045 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4414 | 1.4414 | 0.2883 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4815 | 0.4815 | 0.4815 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.6067 | 4.6067 | 4.6067 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4692 | 0.4692 | 0.4692 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.5476 | 24.5476 | 24.5476 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 11.0211 | 9.7833 | 11.0211 | 3.0182 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 105.2506 | 91.7835 | 105.2506 | 29.5888 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 10.9647 | 9.9086 | 10.9647 | 3.0516 | 0.0000 | 1.0000 |
CAV_BAS | 5.5428 | 5.5428 | 5.5428 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.5476 | 24.5478 | 24.5476 | 24.5476 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4815 | 0.4815 | 0.4815 | 0.4815 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.6067 | 4.6067 | 4.6067 | 4.6067 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4692 | 0.4692 | 0.4692 | 0.4692 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 0.0000 | 0.0000 | 0.0000 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9234 | 2.9234 | 1.9411 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 27.5243 | 27.5243 | 19.0468 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7997 | 2.7997 | 1.9486 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5029 | 0.5029 | 0.2434 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6165 | 0.6165 | 0.2466 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7163 | 0.7163 | 0.2865 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7514 | 0.7514 | 0.3006 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.7321 | 4.7321 | 2.3944 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.5417 | 6.5417 | 2.6167 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.0307 | 7.0307 | 2.8123 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.7966 | 6.7966 | 2.7186 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5354 | 0.5354 | 0.2441 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6654 | 0.6654 | 0.2661 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7612 | 0.7612 | 0.3045 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7207 | 0.7207 | 0.2883 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4815 | 0.4815 | 0.4815 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.6067 | 4.6067 | 4.6067 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4692 | 0.4692 | 0.4692 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.5476 | 24.5476 | 24.5476 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.5106 | 3.0182 | 3.0182 | 3.0182 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 52.6253 | 29.5888 | 29.5888 | 29.5888 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.4824 | 3.0516 | 3.0516 | 3.0516 | 0.0000 | 1.0000 |
CAV_BAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.5476 | 24.5476 | 24.5476 | 24.5476 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4815 | 0.4815 | 0.4815 | 0.4815 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.6067 | 4.6067 | 4.6067 | 4.6067 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4692 | 0.4692 | 0.4692 | 0.4692 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:28
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 28.83 |
Number of hours cooling loads not met | 1711.50 |
Number of hours not met | 1729.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 838.46 | 1710520.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 2005.60 | 463471.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3223.37 | 325713.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 351.57 | 40855.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 55.01 | 3454.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 2505.76 | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2470.36 | 306094.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 421.59 | 62600.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 764.95 | 91748.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1276.09 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 46.34 | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 426.30 | 53261.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 28229.16 |
Natural Gas | 0.00 | 838.46 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 29067.62 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 69.59 |
Space Heating | 0.00 |
Space Cooling | 43.30 |
Fans (All) | 53.33 |
Service Water Heating | 9.20 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 609.43 |
Subtotal | 609.43 |
Natural Gas [MJ/m2] | |
Space Heating | 18.10 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 18.10 |
Subtotal | 18.10 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 11.09 |
Space Heating | 2.88 |
Space Cooling | 6.90 |
Fans (All) | 8.50 |
Service Water Heating | 1.47 |
Receptacle Equipment | 50.49 |
Miscellaneous | 18.67 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:28
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 6499.67 | 862.50 | 307.17 | 1090.67 | 0.00 |
CORE_BOTTOM | 8628.17 | 131.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8757.83 | 2.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8749.67 | 10.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8691.33 | 68.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8683.67 | 76.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8652.67 | 107.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8253.17 | 506.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8735.67 | 24.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8676.50 | 83.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8652.83 | 107.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8435.00 | 325.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8707.67 | 52.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8652.00 | 108.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8630.00 | 130.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8440.17 | 319.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 6375.50 | 2384.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 6381.50 | 2378.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 6347.83 | 2412.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 5573.33 | 3186.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8728.33 | 31.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8660.33 | 99.67 | 0.00 | 0.00 | 0.00 |
Min | 5573.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 3186.67 | 307.17 | 1090.67 | 0.00 |
Average | 8116.21 | 583.01 | 13.36 | 47.42 | 0.00 |
Sum | 186672.83 | 13409.33 | 307.17 | 1090.67 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 290855.67 | 15572.50 | 14883.67 | 47304.17 | 0.00 |
CORE_BOTTOM | 330698.00 | 115.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330804.00 | 9.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1328.50 | 939.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1321.17 | 946.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1316.00 | 952.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 63691.00 | 39704.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 330813.00 | 39704.00 | 14883.67 | 47304.17 | 0.00 |
Average | 75098.97 | 2532.12 | 647.12 | 2056.70 | 0.00 |
Sum | 1727276.33 | 58238.83 | 14883.67 | 47304.17 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 6259.17 | 1114.67 | 182.00 | 1060.00 | 144.17 |
CORE_BOTTOM | 7627.83 | 1132.17 | 0.00 | 0.00 | 0.00 |
CORE_MID | 7890.50 | 869.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 7961.67 | 798.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 7801.17 | 958.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8004.00 | 756.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7787.00 | 973.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7558.50 | 1201.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 7897.67 | 862.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 7912.67 | 847.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 7798.33 | 961.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7794.17 | 965.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 7895.83 | 864.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 7910.67 | 849.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 7835.33 | 924.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7819.00 | 941.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7458.67 | 1301.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7419.50 | 1340.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7401.83 | 1358.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6477.00 | 2283.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 7614.83 | 1145.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 7687.83 | 1072.17 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7283.50 | 1476.50 | 0.00 | 0.00 | 0.00 |
Min | 6259.17 | 756.00 | 0.00 | 0.00 | 0.00 |
Max | 8004.00 | 2283.00 | 182.00 | 1060.00 | 144.17 |
Average | 7612.90 | 1086.83 | 7.91 | 46.09 | 6.27 |
Sum | 175096.67 | 24997.17 | 182.00 | 1060.00 | 144.17 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 288810.00 | 18916.67 | 10728.00 | 38489.00 | 11672.33 |
CORE_BOTTOM | 328788.00 | 2025.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 329623.00 | 1190.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 329557.50 | 1255.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38921.83 | 3.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18353.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38923.17 | 1.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24908.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38918.50 | 6.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24908.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38922.00 | 3.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24908.83 | 0.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1506.17 | 761.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1486.00 | 782.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1476.67 | 791.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 67257.67 | 36137.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 329623.00 | 36137.33 | 10728.00 | 38489.00 | 11672.33 |
Average | 74997.30 | 2690.25 | 466.43 | 1673.43 | 507.49 |
Sum | 1724937.83 | 61875.83 | 10728.00 | 38489.00 | 11672.33 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:28
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:25:28
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
For: Environment
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
For: Environment
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 1.168 |
February | -0.18 |
March | 5.585 |
April | 10.941 |
May | 16.049 |
June | 21.711 |
July | 25.046 |
August | 24.788 |
September | 19.956 |
October | 14.024 |
November | 7.310 |
December | 3.332 |
Annual Sum or Average | 12.554 |
Minimum of Months | -0.18 |
Maximum of Months | 25.046 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.424222E+11 | 103411.88 | 24-JAN-07:12 | 10.93 | 10.93 | 0.567390E+10 | 7499.40 | 03-JAN-10:00 | 10.93 | 10.93 |
February | 0.408049E+11 | 104700.61 | 21-FEB-07:05 | 2.80 | 1.83 | 0.515076E+10 | 7499.20 | 28-FEB-10:09 | 7.12 | 6.63 |
March | 0.531986E+11 | 106683.22 | 28-MAR-06:11 | 10.00 | 7.50 | 0.615158E+10 | 7499.33 | 27-MAR-09:09 | 10.00 | 7.50 |
April | 0.510505E+11 | 110840.93 | 17-APR-06:11 | 11.70 | 10.63 | 0.547014E+10 | 7499.35 | 26-APR-09:00 | 16.10 | 12.59 |
May | 0.520349E+11 | 112765.94 | 30-MAY-19:51 | 20.00 | 15.55 | 0.604536E+10 | 11298.00 | 30-MAY-13:00 | 20.00 | 15.55 |
June | 0.396995E+11 | 116370.65 | 09-JUN-06:11 | 15.97 | 10.39 | 0.721298E+10 | 12667.89 | 27-JUN-13:00 | 27.20 | 23.26 |
July | 0.172245E+11 | 122082.58 | 11-JUL-06:11 | 21.13 | 15.72 | 0.824631E+10 | 13046.06 | 21-JUL-13:00 | 29.40 | 25.29 |
August | 0.274361E+11 | 125977.30 | 23-AUG-06:11 | 19.47 | 14.69 | 0.903686E+10 | 13457.86 | 18-AUG-13:00 | 19.47 | 14.69 |
September | 0.460211E+11 | 125347.79 | 15-SEP-06:11 | 15.73 | 12.49 | 0.642250E+10 | 12590.60 | 08-SEP-13:00 | 15.73 | 12.49 |
October | 0.607205E+11 | 115522.71 | 02-OCT-06:11 | 10.77 | 10.11 | 0.572317E+10 | 10170.34 | 06-OCT-09:09 | 18.95 | 17.77 |
November | 0.558432E+11 | 112514.93 | 13-NOV-07:05 | 6.10 | 5.08 | 0.563899E+10 | 7499.41 | 09-NOV-14:00 | 6.10 | 5.08 |
December | 0.521354E+11 | 107069.99 | 26-DEC-07:05 | 6.70 | 5.42 | 0.549021E+10 | 7499.20 | 18-DEC-14:39 | 6.70 | 5.42 |
Annual Sum or Average | 0.538591E+12 | 0.762628E+11 | ||||||||
Minimum of Months | 0.172245E+11 | 103411.88 | 2.80 | 1.83 | 0.515076E+10 | 7499.20 | 6.10 | 5.08 | ||
Maximum of Months | 0.607205E+11 | 125977.30 | 21.13 | 15.72 | 0.903686E+10 | 13457.86 | 29.40 | 25.29 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.347236E+11 | 81283.94 | 20-JAN-06:03 | 4.90 | -0.5 | 0.503196E+10 | 6734.94 | 03-JAN-10:00 | 4.90 | -0.5 |
February | 0.350458E+11 | 87978.97 | 21-FEB-05:11 | 2.20 | 1.34 | 0.458531E+10 | 6734.78 | 28-FEB-10:09 | 7.12 | 6.63 |
March | 0.498550E+11 | 89967.67 | 06-MAR-05:11 | 8.70 | 8.70 | 0.549776E+10 | 6739.48 | 22-MAR-09:30 | -0.9 | -4.9 |
April | 0.538714E+11 | 91231.83 | 27-APR-04:13 | 12.43 | 10.86 | 0.488115E+10 | 6734.87 | 26-APR-09:00 | 12.43 | 10.86 |
May | 0.541242E+11 | 98080.34 | 31-MAY-04:13 | 16.10 | 14.49 | 0.528519E+10 | 6770.47 | 30-MAY-13:20 | 16.10 | 14.49 |
June | 0.702437E+11 | 97523.83 | 12-JUN-04:13 | 18.70 | 17.72 | 0.527392E+10 | 6888.46 | 22-JUN-13:09 | 28.58 | 17.26 |
July | 0.876718E+11 | 95460.91 | 01-JUL-04:13 | 20.00 | 19.55 | 0.490464E+10 | 6797.10 | 11-JUL-13:09 | 27.98 | 17.98 |
August | 0.968028E+11 | 93792.88 | 14-AUG-04:24 | 22.20 | 20.13 | 0.550523E+10 | 6771.06 | 11-AUG-09:50 | 22.20 | 20.13 |
September | 0.609891E+11 | 97473.41 | 09-SEP-04:13 | 17.80 | 16.40 | 0.488661E+10 | 6751.52 | 01-SEP-13:39 | 17.80 | 16.40 |
October | 0.553387E+11 | 95848.31 | 10-OCT-04:12 | 10.40 | 8.15 | 0.507850E+10 | 6735.15 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.475076E+11 | 98808.05 | 13-NOV-05:11 | 5.60 | 4.52 | 0.503176E+10 | 6737.50 | 24-NOV-10:39 | -0.2 | -3.0 |
December | 0.457111E+11 | 90513.04 | 26-DEC-05:11 | 5.77 | 4.97 | 0.489787E+10 | 6751.96 | 12-DEC-10:09 | 5.77 | 4.97 |
Annual Sum or Average | 0.691885E+12 | 0.608599E+11 | ||||||||
Minimum of Months | 0.347236E+11 | 81283.94 | 2.20 | -0.5 | 0.458531E+10 | 6734.78 | -0.9 | -4.9 | ||
Maximum of Months | 0.968028E+11 | 98808.05 | 22.20 | 20.13 | 0.550523E+10 | 6888.46 | 28.58 | 20.13 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.229682E+11 | 26583.14 | 25-JAN-14:00 | 2.00 | 1.57 | 0.452903E+10 | 6734.70 | 20-JAN-14:39 | 2.00 | 1.57 |
February | 0.234042E+11 | 33194.02 | 08-FEB-09:40 | -4.1 | -6.9 | 0.426171E+10 | 6734.66 | 17-FEB-14:30 | 6.40 | 1.99 |
March | 0.317837E+11 | 73743.98 | 29-MAR-05:02 | 2.12 | 0.18 | 0.537148E+10 | 6744.41 | 31-MAR-09:30 | 6.70 | 6.70 |
April | 0.341867E+11 | 80490.93 | 28-APR-05:02 | 13.12 | 9.52 | 0.481763E+10 | 6734.80 | 05-APR-09:39 | 13.12 | 9.52 |
May | 0.433875E+11 | 82662.08 | 31-MAY-04:12 | 16.10 | 14.49 | 0.526404E+10 | 6735.01 | 25-MAY-09:09 | 16.10 | 14.49 |
June | 0.484165E+11 | 84151.49 | 12-JUN-04:12 | 18.70 | 17.72 | 0.526453E+10 | 6817.76 | 22-JUN-13:39 | 29.43 | 17.55 |
July | 0.497084E+11 | 82061.43 | 24-JUL-05:04 | 20.78 | 20.27 | 0.489056E+10 | 6750.39 | 12-JUL-09:09 | 20.78 | 20.27 |
August | 0.531394E+11 | 86245.97 | 07-AUG-04:14 | 18.67 | 17.05 | 0.549506E+10 | 6734.82 | 23-AUG-13:20 | 25.60 | 17.10 |
September | 0.441380E+11 | 83933.63 | 18-SEP-04:12 | 17.07 | 16.12 | 0.486993E+10 | 6785.70 | 01-SEP-13:00 | 17.07 | 16.12 |
October | 0.401242E+11 | 81566.22 | 06-OCT-04:12 | 19.40 | 18.28 | 0.504825E+10 | 6735.07 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.292226E+11 | 76155.44 | 04-NOV-05:02 | 10.50 | 9.29 | 0.489418E+10 | 6763.74 | 30-NOV-14:39 | 5.97 | 2.57 |
December | 0.261962E+11 | 28557.26 | 21-DEC-16:30 | 2.25 | -2.5 | 0.464900E+10 | 6734.74 | 22-DEC-10:30 | -1.7 | -4.5 |
Annual Sum or Average | 0.446676E+12 | 0.593554E+11 | ||||||||
Minimum of Months | 0.229682E+11 | 26583.14 | -4.1 | -6.9 | 0.426171E+10 | 6734.66 | -1.7 | -4.5 | ||
Maximum of Months | 0.531394E+11 | 86245.97 | 20.78 | 20.27 | 0.549506E+10 | 6817.76 | 29.43 | 20.27 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.175968E+11 | 19702.47 | 20-JAN-17:00 | 5.60 | 3.19 | 0.411636E+10 | 6464.34 | 20-JAN-14:00 | 5.60 | 3.19 |
February | 0.171734E+11 | 19743.50 | 17-FEB-17:00 | 5.60 | 1.58 | 0.377966E+10 | 6507.70 | 17-FEB-14:00 | 5.60 | 1.58 |
March | 0.258130E+11 | 33743.26 | 29-MAR-16:00 | 7.20 | 4.88 | 0.495222E+10 | 6734.61 | 24-MAR-13:39 | 7.20 | 4.88 |
April | 0.299184E+11 | 76789.87 | 08-APR-05:02 | 14.32 | 11.97 | 0.462992E+10 | 6734.72 | 26-APR-09:00 | 16.10 | 12.59 |
May | 0.414971E+11 | 82757.28 | 30-MAY-04:12 | 17.80 | 14.10 | 0.521128E+10 | 6735.03 | 30-MAY-13:00 | 29.40 | 16.93 |
June | 0.507504E+11 | 84631.02 | 12-JUN-04:12 | 18.70 | 17.72 | 0.526057E+10 | 6800.18 | 22-JUN-13:39 | 29.43 | 17.55 |
July | 0.540432E+11 | 83027.63 | 11-JUL-04:12 | 19.80 | 15.19 | 0.489411E+10 | 6735.39 | 11-JUL-13:50 | 28.72 | 17.86 |
August | 0.568724E+11 | 88629.89 | 07-AUG-04:12 | 18.67 | 17.05 | 0.549470E+10 | 6734.83 | 23-AUG-13:20 | 25.60 | 17.10 |
September | 0.428634E+11 | 82743.84 | 06-SEP-04:12 | 21.30 | 18.82 | 0.484470E+10 | 6772.77 | 01-SEP-13:50 | 21.30 | 18.82 |
October | 0.345921E+11 | 78762.99 | 06-OCT-05:03 | 19.40 | 18.22 | 0.491939E+10 | 6735.01 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.221487E+11 | 33266.61 | 03-NOV-16:00 | 15.00 | 10.26 | 0.446083E+10 | 6734.76 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.190836E+11 | 19386.27 | 20-DEC-17:00 | 6.70 | 3.52 | 0.407422E+10 | 6470.71 | 20-DEC-14:00 | 6.70 | 3.52 |
Annual Sum or Average | 0.412352E+12 | 0.566380E+11 | ||||||||
Minimum of Months | 0.171734E+11 | 19386.27 | 5.60 | 1.58 | 0.377966E+10 | 6464.34 | 5.60 | 1.58 | ||
Maximum of Months | 0.568724E+11 | 88629.89 | 21.30 | 18.82 | 0.549470E+10 | 6800.18 | 29.43 | 18.82 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.218355E+10 | 2730.33 | 24-JAN-06:03 | 11.10 | 11.10 | 0.530234E+09 | 813.77 | 20-JAN-14:00 | 11.10 | 11.10 |
February | 0.216981E+10 | 3175.89 | 20-FEB-12:43 | 9.50 | 4.37 | 0.486701E+09 | 830.79 | 24-FEB-14:20 | 9.03 | 2.95 |
March | 0.389091E+10 | 6440.50 | 27-MAR-13:30 | 20.85 | 16.76 | 0.653315E+09 | 845.63 | 27-MAR-09:20 | 20.85 | 16.76 |
April | 0.545264E+10 | 7775.23 | 26-APR-13:40 | 18.30 | 12.75 | 0.601482E+09 | 845.64 | 26-APR-09:00 | 18.30 | 12.75 |
May | 0.726562E+10 | 13841.22 | 31-MAY-04:12 | 16.10 | 14.49 | 0.661559E+09 | 856.12 | 30-MAY-13:30 | 16.10 | 14.49 |
June | 0.113433E+11 | 17346.39 | 25-JUN-14:31 | 26.70 | 22.80 | 0.662751E+09 | 871.68 | 22-JUN-13:09 | 26.70 | 22.80 |
July | 0.145783E+11 | 18038.26 | 09-JUL-14:21 | 29.45 | 24.51 | 0.617022E+09 | 860.36 | 11-JUL-13:20 | 28.17 | 17.95 |
August | 0.152459E+11 | 17279.48 | 13-AUG-15:01 | 30.50 | 20.85 | 0.691759E+09 | 851.15 | 11-AUG-09:50 | 30.50 | 20.85 |
September | 0.814050E+10 | 17003.94 | 04-SEP-12:11 | 26.10 | 17.96 | 0.612252E+09 | 848.51 | 01-SEP-13:39 | 26.10 | 17.96 |
October | 0.581116E+10 | 7397.97 | 04-OCT-13:04 | 24.90 | 18.61 | 0.630552E+09 | 845.67 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.356185E+10 | 5142.40 | 03-NOV-13:30 | 17.50 | 10.63 | 0.601543E+09 | 845.64 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.299921E+10 | 3373.99 | 26-DEC-13:30 | 9.45 | 5.02 | 0.554044E+09 | 845.61 | 20-DEC-14:30 | 9.45 | 5.02 |
Annual Sum or Average | 0.826428E+11 | 0.730321E+10 | ||||||||
Minimum of Months | 0.216981E+10 | 2730.33 | 9.45 | 4.37 | 0.486701E+09 | 813.77 | 9.03 | 2.95 | ||
Maximum of Months | 0.152459E+11 | 18038.26 | 30.50 | 24.51 | 0.691759E+09 | 871.68 | 30.50 | 22.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.212220E+10 | 4680.21 | 19-JAN-09:40 | 6.67 | 3.82 | 0.342525E+09 | 544.95 | 20-JAN-10:20 | 4.80 | 1.25 |
February | 0.222936E+10 | 6157.52 | 22-FEB-09:05 | 0.10 | -3.4 | 0.319626E+09 | 544.95 | 09-FEB-10:09 | 0.10 | -3.4 |
March | 0.418284E+10 | 9741.73 | 29-MAR-08:35 | 5.20 | 2.69 | 0.415464E+09 | 545.50 | 22-MAR-09:30 | 5.20 | 2.69 |
April | 0.548169E+10 | 22074.57 | 16-APR-08:52 | 15.60 | 11.57 | 0.381133E+09 | 544.98 | 26-APR-09:50 | 16.38 | 12.56 |
May | 0.729849E+10 | 22365.95 | 29-MAY-08:12 | 24.63 | 16.73 | 0.424297E+09 | 549.56 | 30-MAY-13:20 | 29.80 | 17.64 |
June | 0.943129E+10 | 24757.76 | 25-JUN-08:31 | 25.20 | 23.38 | 0.426627E+09 | 556.42 | 22-JUN-13:09 | 25.20 | 23.38 |
July | 0.119123E+11 | 24341.10 | 09-JUL-08:21 | 27.75 | 25.12 | 0.397418E+09 | 557.03 | 12-JUL-09:50 | 27.70 | 18.43 |
August | 0.132448E+11 | 21750.87 | 27-AUG-08:52 | 24.40 | 21.68 | 0.445552E+09 | 550.83 | 11-AUG-09:50 | 24.40 | 21.68 |
September | 0.759328E+10 | 24988.19 | 04-SEP-08:51 | 23.90 | 18.54 | 0.393843E+09 | 547.05 | 01-SEP-13:39 | 23.90 | 18.54 |
October | 0.580404E+10 | 18749.76 | 15-OCT-09:13 | 17.57 | 12.46 | 0.404884E+09 | 545.00 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.332484E+10 | 6905.11 | 02-NOV-08:50 | 10.82 | 5.71 | 0.380170E+09 | 544.99 | 22-NOV-10:09 | 0.10 | -2.5 |
December | 0.270856E+10 | 5125.67 | 20-DEC-09:30 | 7.20 | 4.58 | 0.344529E+09 | 544.95 | 19-DEC-10:20 | 7.20 | 4.58 |
Annual Sum or Average | 0.753336E+11 | 0.467607E+10 | ||||||||
Minimum of Months | 0.212220E+10 | 4680.21 | 0.10 | -3.4 | 0.319626E+09 | 544.95 | 0.10 | -3.4 | ||
Maximum of Months | 0.132448E+11 | 24988.19 | 27.75 | 25.12 | 0.445552E+09 | 557.03 | 29.80 | 23.38 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.449883E+10 | 15641.79 | 17-JAN-13:10 | 10.18 | 5.51 | 0.564613E+09 | 846.03 | 17-JAN-14:09 | 11.02 | 5.14 |
February | 0.510742E+10 | 25011.30 | 20-FEB-12:43 | 9.50 | 4.37 | 0.528344E+09 | 846.17 | 22-FEB-14:20 | 4.80 | -0.9 |
March | 0.817379E+10 | 18845.06 | 01-MAR-13:15 | 13.90 | 6.52 | 0.655759E+09 | 847.71 | 28-MAR-13:09 | 13.80 | 8.65 |
April | 0.824244E+10 | 24681.79 | 16-APR-12:13 | 20.77 | 13.20 | 0.595841E+09 | 867.79 | 07-APR-13:50 | 20.77 | 13.20 |
May | 0.896013E+10 | 19957.42 | 29-MAY-12:13 | 28.33 | 17.95 | 0.658646E+09 | 866.88 | 30-MAY-13:20 | 29.80 | 17.64 |
June | 0.125339E+11 | 25140.58 | 25-JUN-13:52 | 26.70 | 23.10 | 0.662431E+09 | 875.35 | 22-JUN-13:09 | 26.70 | 23.10 |
July | 0.163516E+11 | 26704.38 | 09-JUL-13:41 | 31.70 | 24.87 | 0.616871E+09 | 866.01 | 11-JUL-13:09 | 27.98 | 17.98 |
August | 0.199084E+11 | 26675.40 | 27-AUG-12:12 | 28.13 | 22.58 | 0.692931E+09 | 904.54 | 30-AUG-13:50 | 28.62 | 15.51 |
September | 0.133178E+11 | 28855.59 | 04-SEP-12:11 | 26.10 | 17.96 | 0.614242E+09 | 898.22 | 28-SEP-13:09 | 22.98 | 13.55 |
October | 0.132179E+11 | 28075.11 | 15-OCT-11:51 | 20.00 | 13.65 | 0.635277E+09 | 938.77 | 04-OCT-13:39 | 20.00 | 13.65 |
November | 0.715795E+10 | 20085.68 | 02-NOV-12:40 | 15.40 | 8.14 | 0.609869E+09 | 869.39 | 02-NOV-13:09 | 15.68 | 8.29 |
December | 0.601124E+10 | 27025.08 | 17-DEC-12:52 | 12.20 | 4.95 | 0.568521E+09 | 846.50 | 21-DEC-14:20 | 3.30 | -1.7 |
Annual Sum or Average | 0.123481E+12 | 0.740335E+10 | ||||||||
Minimum of Months | 0.449883E+10 | 15641.79 | 9.50 | 4.37 | 0.528344E+09 | 846.03 | 3.30 | -1.7 | ||
Maximum of Months | 0.199084E+11 | 28855.59 | 31.70 | 24.87 | 0.692931E+09 | 938.77 | 29.80 | 23.10 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.323219E+10 | 6971.71 | 20-JAN-15:30 | 7.50 | 3.89 | 0.351475E+09 | 544.95 | 20-JAN-14:50 | 7.50 | 3.89 |
February | 0.371719E+10 | 15599.21 | 20-FEB-15:23 | 7.75 | 4.55 | 0.334090E+09 | 544.95 | 10-FEB-14:20 | 7.75 | 4.55 |
March | 0.702940E+10 | 18739.66 | 26-MAR-16:32 | 10.97 | 9.75 | 0.437190E+09 | 544.96 | 27-MAR-09:09 | 11.20 | 11.20 |
April | 0.925139E+10 | 27806.51 | 09-APR-16:11 | 16.83 | 14.03 | 0.394888E+09 | 544.97 | 26-APR-09:50 | 16.38 | 12.56 |
May | 0.884627E+10 | 27430.59 | 14-MAY-15:12 | 13.70 | 9.24 | 0.426882E+09 | 550.95 | 30-MAY-13:39 | 29.60 | 17.29 |
June | 0.126791E+11 | 29237.94 | 04-JUN-16:01 | 22.02 | 14.54 | 0.427762E+09 | 559.19 | 22-JUN-13:09 | 28.58 | 17.26 |
July | 0.153687E+11 | 30854.40 | 04-JUL-16:21 | 25.55 | 18.12 | 0.398052E+09 | 552.71 | 11-JUL-13:09 | 27.98 | 17.98 |
August | 0.179649E+11 | 27846.87 | 13-AUG-15:41 | 30.10 | 20.54 | 0.446689E+09 | 559.29 | 22-AUG-15:00 | 29.40 | 17.12 |
September | 0.907083E+10 | 28047.26 | 03-SEP-15:51 | 25.00 | 16.57 | 0.394998E+09 | 548.15 | 01-SEP-13:39 | 25.00 | 16.57 |
October | 0.845618E+10 | 27308.04 | 15-OCT-14:32 | 20.77 | 13.06 | 0.409678E+09 | 545.01 | 03-OCT-13:39 | 20.77 | 13.06 |
November | 0.528309E+10 | 13625.03 | 04-NOV-05:02 | 10.50 | 9.29 | 0.399725E+09 | 544.97 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.494505E+10 | 16723.72 | 17-DEC-14:53 | 12.20 | 5.51 | 0.386445E+09 | 544.95 | 29-DEC-14:00 | 3.90 | 3.16 |
Annual Sum or Average | 0.105844E+12 | 0.480787E+10 | ||||||||
Minimum of Months | 0.323219E+10 | 6971.71 | 7.50 | 3.89 | 0.334090E+09 | 544.95 | 3.90 | 3.16 | ||
Maximum of Months | 0.179649E+11 | 30854.40 | 30.10 | 20.54 | 0.446689E+09 | 559.29 | 29.60 | 17.98 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.542142E+09 | 1913.73 | 20-JAN-17:05 | 5.32 | 3.08 | 0.469905E+09 | 694.38 | 20-JAN-14:00 | 5.32 | 3.08 |
February | 0.583183E+09 | 2194.33 | 23-FEB-16:30 | 5.00 | 3.87 | 0.428938E+09 | 709.79 | 24-FEB-14:00 | 8.30 | 2.27 |
March | 0.210505E+10 | 3285.84 | 28-MAR-14:00 | 13.30 | 8.41 | 0.561770E+09 | 845.60 | 28-MAR-13:20 | 13.30 | 8.41 |
April | 0.320216E+10 | 5876.43 | 07-APR-14:00 | 26.10 | 15.95 | 0.554971E+09 | 845.63 | 07-APR-13:09 | 26.10 | 15.95 |
May | 0.570713E+10 | 11726.74 | 30-MAY-05:02 | 18.17 | 14.31 | 0.651786E+09 | 847.31 | 30-MAY-13:39 | 29.60 | 17.29 |
June | 0.845963E+10 | 12887.77 | 22-JUN-05:03 | 22.88 | 15.44 | 0.661416E+09 | 868.87 | 22-JUN-13:39 | 29.43 | 17.55 |
July | 0.968528E+10 | 16371.91 | 09-JUL-14:21 | 29.45 | 24.51 | 0.616025E+09 | 847.98 | 12-JUL-09:09 | 27.30 | 18.61 |
August | 0.959578E+10 | 12543.21 | 13-AUG-15:41 | 30.10 | 20.54 | 0.690569E+09 | 845.65 | 08-AUG-13:39 | 30.10 | 20.54 |
September | 0.595757E+10 | 12188.63 | 02-SEP-05:03 | 22.12 | 16.30 | 0.605629E+09 | 854.14 | 01-SEP-13:00 | 22.12 | 16.30 |
October | 0.400647E+10 | 6117.05 | 05-OCT-14:00 | 23.30 | 18.86 | 0.603092E+09 | 845.63 | 04-OCT-13:39 | 23.30 | 18.86 |
November | 0.184389E+10 | 3031.66 | 02-NOV-14:20 | 16.30 | 8.82 | 0.515755E+09 | 844.93 | 03-NOV-13:00 | 17.80 | 10.67 |
December | 0.832434E+09 | 1961.03 | 21-DEC-13:30 | 3.05 | -1.7 | 0.456236E+09 | 705.55 | 20-DEC-14:09 | 3.05 | -1.7 |
Annual Sum or Average | 0.525207E+11 | 0.681609E+10 | ||||||||
Minimum of Months | 0.542142E+09 | 1913.73 | 3.05 | -1.7 | 0.428938E+09 | 694.38 | 3.05 | -1.7 | ||
Maximum of Months | 0.968528E+10 | 16371.91 | 30.10 | 24.51 | 0.690569E+09 | 868.87 | 30.10 | 20.54 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.765070E+09 | 2541.93 | 27-JAN-09:55 | 4.40 | 1.46 | 0.225191E+09 | 500.63 | 27-JAN-09:00 | 4.40 | 1.46 |
February | 0.107108E+10 | 4369.62 | 08-FEB-09:40 | -4.1 | -6.9 | 0.208843E+09 | 521.19 | 22-FEB-09:00 | 0.60 | -3.2 |
March | 0.288469E+10 | 8432.56 | 29-MAR-08:55 | 5.60 | 2.98 | 0.279099E+09 | 521.21 | 23-MAR-10:20 | 5.60 | 2.98 |
April | 0.430848E+10 | 19396.92 | 23-APR-08:53 | 11.70 | 7.85 | 0.266932E+09 | 521.23 | 06-APR-12:09 | 11.70 | 7.85 |
May | 0.688808E+10 | 26700.06 | 29-MAY-08:31 | 25.37 | 16.74 | 0.305319E+09 | 528.70 | 30-MAY-10:39 | 28.53 | 17.44 |
June | 0.810030E+10 | 24297.95 | 04-JUN-08:32 | 22.93 | 12.74 | 0.312249E+09 | 545.56 | 22-JUN-15:20 | 30.20 | 17.80 |
July | 0.920735E+10 | 26303.61 | 02-JUL-07:41 | 24.13 | 21.14 | 0.292661E+09 | 535.56 | 11-JUL-14:39 | 28.50 | 17.67 |
August | 0.102818E+11 | 24243.26 | 20-AUG-09:42 | 23.53 | 15.29 | 0.327009E+09 | 535.72 | 22-AUG-10:09 | 28.48 | 18.44 |
September | 0.655555E+10 | 26042.40 | 04-SEP-09:01 | 24.18 | 18.48 | 0.285497E+09 | 523.13 | 01-SEP-15:09 | 24.18 | 18.48 |
October | 0.494756E+10 | 10138.91 | 03-OCT-09:00 | 18.90 | 16.77 | 0.288575E+09 | 521.23 | 16-OCT-08:00 | 16.70 | 14.03 |
November | 0.215625E+10 | 5113.28 | 02-NOV-09:00 | 11.10 | 5.86 | 0.247147E+09 | 521.20 | 03-NOV-10:09 | 13.58 | 8.52 |
December | 0.113979E+10 | 2662.79 | 20-DEC-09:30 | 7.20 | 4.58 | 0.221095E+09 | 517.92 | 20-DEC-09:00 | 8.30 | 5.00 |
Annual Sum or Average | 0.583060E+11 | 0.325962E+10 | ||||||||
Minimum of Months | 0.765070E+09 | 2541.93 | -4.1 | -6.9 | 0.208843E+09 | 500.63 | 0.60 | -3.2 | ||
Maximum of Months | 0.102818E+11 | 26700.06 | 25.37 | 21.14 | 0.327009E+09 | 545.56 | 30.20 | 18.48 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.340775E+10 | 15557.90 | 17-JAN-13:20 | 10.37 | 5.44 | 0.535911E+09 | 860.04 | 05-JAN-10:00 | 10.37 | 5.44 |
February | 0.418129E+10 | 24561.95 | 20-FEB-13:32 | 9.07 | 4.47 | 0.505472E+09 | 864.58 | 09-FEB-10:39 | 9.07 | 4.47 |
March | 0.688534E+10 | 19275.63 | 01-MAR-13:30 | 13.90 | 6.36 | 0.625809E+09 | 851.68 | 22-MAR-13:30 | 1.70 | -3.7 |
April | 0.652711E+10 | 17711.35 | 07-APR-12:30 | 26.15 | 15.90 | 0.573164E+09 | 861.04 | 07-APR-13:50 | 26.20 | 16.03 |
May | 0.799761E+10 | 24790.34 | 29-MAY-13:52 | 26.10 | 17.43 | 0.650270E+09 | 860.39 | 30-MAY-13:39 | 29.60 | 17.29 |
June | 0.100371E+11 | 23511.19 | 25-JUN-12:43 | 26.60 | 23.08 | 0.660861E+09 | 877.16 | 22-JUN-13:39 | 26.60 | 23.08 |
July | 0.118313E+11 | 25667.30 | 09-JUL-13:41 | 31.70 | 24.87 | 0.616342E+09 | 856.52 | 11-JUL-13:09 | 27.98 | 17.98 |
August | 0.150154E+11 | 26560.74 | 27-AUG-12:22 | 28.05 | 22.61 | 0.692339E+09 | 916.45 | 30-AUG-13:50 | 28.62 | 15.51 |
September | 0.121052E+11 | 28609.90 | 04-SEP-11:41 | 26.02 | 17.75 | 0.612073E+09 | 943.42 | 28-SEP-13:20 | 23.17 | 13.55 |
October | 0.125965E+11 | 25463.47 | 15-OCT-12:12 | 20.20 | 13.39 | 0.631012E+09 | 954.94 | 04-OCT-13:39 | 20.20 | 13.39 |
November | 0.590041E+10 | 20336.19 | 02-NOV-13:10 | 15.68 | 8.29 | 0.585509E+09 | 899.77 | 02-NOV-13:20 | 15.77 | 8.37 |
December | 0.424865E+10 | 24710.67 | 17-DEC-13:02 | 12.20 | 5.01 | 0.538075E+09 | 857.01 | 21-DEC-14:39 | 3.30 | -1.8 |
Annual Sum or Average | 0.100734E+12 | 0.722684E+10 | ||||||||
Minimum of Months | 0.340775E+10 | 15557.90 | 9.07 | 4.47 | 0.505472E+09 | 851.68 | 1.70 | -3.7 | ||
Maximum of Months | 0.150154E+11 | 28609.90 | 31.70 | 24.87 | 0.692339E+09 | 954.94 | 29.60 | 23.08 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101379E+10 | 3935.52 | 31-JAN-16:00 | -1.1 | -5.7 | 0.312191E+09 | 542.51 | 19-JAN-14:00 | -1.1 | -5.7 |
February | 0.126719E+10 | 6094.15 | 24-FEB-15:30 | 8.05 | 2.04 | 0.288535E+09 | 544.93 | 17-FEB-14:00 | 8.05 | 2.04 |
March | 0.354943E+10 | 10950.87 | 29-MAR-16:00 | 7.20 | 4.88 | 0.372624E+09 | 544.95 | 01-MAR-14:00 | 7.20 | 4.88 |
April | 0.479773E+10 | 23683.85 | 23-APR-16:31 | 13.30 | 9.12 | 0.356621E+09 | 544.96 | 10-APR-13:09 | 13.30 | 9.12 |
May | 0.691456E+10 | 24680.05 | 21-MAY-15:52 | 18.90 | 12.62 | 0.413972E+09 | 545.34 | 30-MAY-13:00 | 29.40 | 16.93 |
June | 0.915201E+10 | 25421.08 | 18-JUN-16:31 | 25.20 | 22.01 | 0.425846E+09 | 566.18 | 22-JUN-15:20 | 30.20 | 17.80 |
July | 0.993778E+10 | 28230.18 | 02-JUL-16:21 | 24.70 | 20.69 | 0.397228E+09 | 553.15 | 11-JUL-15:50 | 28.30 | 17.25 |
August | 0.111692E+11 | 24739.80 | 13-AUG-15:41 | 30.10 | 20.54 | 0.445588E+09 | 555.38 | 22-AUG-15:09 | 29.90 | 17.46 |
September | 0.689938E+10 | 25751.37 | 03-SEP-16:01 | 24.90 | 16.52 | 0.387438E+09 | 554.03 | 01-SEP-13:00 | 24.90 | 16.52 |
October | 0.557848E+10 | 15324.84 | 15-OCT-14:52 | 20.60 | 12.83 | 0.385904E+09 | 544.97 | 04-OCT-13:39 | 20.60 | 12.83 |
November | 0.228440E+10 | 7087.83 | 03-NOV-15:30 | 16.10 | 10.65 | 0.333481E+09 | 544.96 | 08-NOV-14:50 | 13.68 | 11.16 |
December | 0.134756E+10 | 3808.80 | 08-DEC-15:30 | 6.40 | 2.12 | 0.304382E+09 | 544.34 | 08-DEC-14:00 | 6.40 | 2.12 |
Annual Sum or Average | 0.639115E+11 | 0.442381E+10 | ||||||||
Minimum of Months | 0.101379E+10 | 3808.80 | -1.1 | -5.7 | 0.288535E+09 | 542.51 | -1.1 | -5.7 | ||
Maximum of Months | 0.111692E+11 | 28230.18 | 30.10 | 22.01 | 0.445588E+09 | 566.18 | 30.20 | 17.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.247105E+09 | 1752.63 | 20-JAN-15:00 | 7.80 | 3.97 | 0.464711E+09 | 658.26 | 20-JAN-14:00 | 7.80 | 3.97 |
February | 0.249903E+09 | 1788.52 | 24-FEB-15:40 | 7.97 | 1.96 | 0.422357E+09 | 662.58 | 24-FEB-14:00 | 7.97 | 1.96 |
March | 0.137779E+10 | 3087.63 | 28-MAR-14:00 | 13.30 | 8.41 | 0.538111E+09 | 845.60 | 28-MAR-13:30 | 13.30 | 8.41 |
April | 0.273762E+10 | 6796.65 | 07-APR-13:20 | 26.50 | 16.25 | 0.530989E+09 | 845.63 | 07-APR-13:09 | 26.50 | 16.25 |
May | 0.551999E+10 | 17215.05 | 29-MAY-14:42 | 25.68 | 17.10 | 0.638535E+09 | 846.11 | 30-MAY-13:39 | 29.60 | 17.29 |
June | 0.874688E+10 | 14211.28 | 26-JUN-04:12 | 20.60 | 16.81 | 0.660545E+09 | 858.12 | 22-JUN-13:39 | 20.60 | 16.81 |
July | 0.102752E+11 | 17965.13 | 09-JUL-15:12 | 27.20 | 24.11 | 0.616140E+09 | 846.17 | 10-JUL-13:00 | 32.80 | 20.89 |
August | 0.101388E+11 | 19192.46 | 13-AUG-15:31 | 30.20 | 20.61 | 0.690067E+09 | 845.65 | 08-AUG-13:39 | 30.20 | 20.61 |
September | 0.583130E+10 | 13800.32 | 02-SEP-04:12 | 22.60 | 16.46 | 0.598761E+09 | 851.76 | 01-SEP-13:50 | 22.60 | 16.46 |
October | 0.348889E+10 | 6442.01 | 04-OCT-13:40 | 24.60 | 18.82 | 0.578768E+09 | 845.64 | 04-OCT-13:39 | 24.60 | 18.82 |
November | 0.117287E+10 | 2902.97 | 02-NOV-13:40 | 15.93 | 8.54 | 0.487354E+09 | 823.47 | 03-NOV-13:00 | 17.80 | 10.67 |
December | 0.235073E+09 | 1732.51 | 20-DEC-14:10 | 9.72 | 5.77 | 0.448660E+09 | 653.86 | 20-DEC-14:20 | 9.43 | 5.62 |
Annual Sum or Average | 0.500215E+11 | 0.667500E+10 | ||||||||
Minimum of Months | 0.235073E+09 | 1732.51 | 7.80 | 1.96 | 0.422357E+09 | 653.86 | 7.80 | 1.96 | ||
Maximum of Months | 0.102752E+11 | 19192.46 | 30.20 | 24.11 | 0.690067E+09 | 858.12 | 32.80 | 20.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.470711E+09 | 2329.54 | 19-JAN-09:45 | 7.23 | 3.99 | 0.302633E+09 | 489.97 | 19-JAN-10:30 | 7.80 | 4.48 |
February | 0.661379E+09 | 2483.14 | 22-FEB-09:55 | 0.60 | -3.2 | 0.277626E+09 | 509.56 | 22-FEB-10:20 | 1.13 | -2.8 |
March | 0.219450E+10 | 7221.54 | 29-MAR-09:30 | 6.15 | 3.19 | 0.373106E+09 | 544.95 | 23-MAR-09:00 | 6.15 | 3.19 |
April | 0.381311E+10 | 11403.89 | 28-APR-08:50 | 15.82 | 8.80 | 0.358481E+09 | 544.97 | 26-APR-09:50 | 15.82 | 8.80 |
May | 0.677066E+10 | 26565.37 | 29-MAY-08:61 | 24.27 | 16.71 | 0.411331E+09 | 546.04 | 30-MAY-09:00 | 27.80 | 17.82 |
June | 0.842440E+10 | 23988.72 | 25-JUN-08:42 | 25.40 | 23.51 | 0.424755E+09 | 550.73 | 22-JUN-13:50 | 25.40 | 23.51 |
July | 0.972408E+10 | 26607.92 | 02-JUL-07:41 | 24.13 | 21.14 | 0.396901E+09 | 547.13 | 14-JUL-09:00 | 30.60 | 21.74 |
August | 0.108129E+11 | 26150.47 | 13-AUG-09:31 | 28.53 | 19.31 | 0.445027E+09 | 558.19 | 22-AUG-09:50 | 28.22 | 18.40 |
September | 0.650608E+10 | 23883.92 | 04-SEP-09:12 | 24.47 | 18.42 | 0.386387E+09 | 549.67 | 01-SEP-13:50 | 24.47 | 18.42 |
October | 0.444597E+10 | 9969.18 | 15-OCT-09:23 | 17.75 | 12.58 | 0.387939E+09 | 544.99 | 16-OCT-09:09 | 16.88 | 14.11 |
November | 0.154751E+10 | 3697.99 | 02-NOV-09:40 | 11.83 | 6.09 | 0.322835E+09 | 544.94 | 03-NOV-09:00 | 13.30 | 8.39 |
December | 0.633356E+09 | 2344.86 | 20-DEC-10:10 | 8.40 | 5.03 | 0.291927E+09 | 489.33 | 20-DEC-10:09 | 8.40 | 5.03 |
Annual Sum or Average | 0.560047E+11 | 0.437895E+10 | ||||||||
Minimum of Months | 0.470711E+09 | 2329.54 | 0.60 | -3.2 | 0.277626E+09 | 489.33 | 1.13 | -2.8 | ||
Maximum of Months | 0.108129E+11 | 26607.92 | 28.53 | 23.51 | 0.445027E+09 | 558.19 | 30.60 | 23.51 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.255162E+10 | 14671.93 | 19-JAN-13:30 | 9.40 | 3.94 | 0.523013E+09 | 845.64 | 30-JAN-14:00 | 2.80 | -1.0 |
February | 0.318934E+10 | 15239.45 | 02-FEB-14:00 | 5.60 | -1.0 | 0.486991E+09 | 845.64 | 10-FEB-14:20 | 2.97 | -0.3 |
March | 0.573401E+10 | 19248.64 | 01-MAR-13:30 | 13.90 | 6.36 | 0.602810E+09 | 846.47 | 03-MAR-14:50 | 15.00 | 8.43 |
April | 0.590543E+10 | 20510.26 | 09-APR-13:43 | 19.40 | 15.43 | 0.553312E+09 | 848.14 | 07-APR-13:50 | 19.40 | 15.43 |
May | 0.789277E+10 | 26290.39 | 29-MAY-12:42 | 27.48 | 17.22 | 0.635548E+09 | 858.04 | 30-MAY-13:00 | 29.40 | 16.93 |
June | 0.104104E+11 | 26163.83 | 25-JUN-12:43 | 26.60 | 23.08 | 0.659007E+09 | 863.06 | 22-JUN-13:39 | 26.60 | 23.08 |
July | 0.124864E+11 | 26464.55 | 30-JUL-12:32 | 26.83 | 23.77 | 0.616113E+09 | 869.78 | 11-JUL-13:09 | 26.83 | 23.77 |
August | 0.156713E+11 | 30092.20 | 13-AUG-13:31 | 31.50 | 19.78 | 0.691210E+09 | 885.31 | 30-AUG-13:50 | 28.62 | 15.51 |
September | 0.119946E+11 | 28502.75 | 04-SEP-13:12 | 26.10 | 18.36 | 0.605381E+09 | 919.09 | 28-SEP-13:30 | 23.35 | 13.54 |
October | 0.115780E+11 | 29842.33 | 15-OCT-12:41 | 20.50 | 12.97 | 0.616270E+09 | 934.95 | 04-OCT-13:39 | 20.50 | 12.97 |
November | 0.458912E+10 | 20920.30 | 02-NOV-13:10 | 15.68 | 8.29 | 0.559534E+09 | 852.06 | 02-NOV-13:20 | 15.77 | 8.37 |
December | 0.298198E+10 | 26845.34 | 17-DEC-13:32 | 12.20 | 5.18 | 0.515625E+09 | 845.64 | 14-DEC-14:09 | 12.20 | 5.18 |
Annual Sum or Average | 0.949850E+11 | 0.706481E+10 | ||||||||
Minimum of Months | 0.255162E+10 | 14671.93 | 5.60 | -1.0 | 0.486991E+09 | 845.64 | 2.80 | -1.0 | ||
Maximum of Months | 0.156713E+11 | 30092.20 | 31.50 | 23.77 | 0.691210E+09 | 934.95 | 29.40 | 23.77 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.686846E+09 | 3541.08 | 19-JAN-15:40 | 8.50 | 3.16 | 0.307960E+09 | 531.26 | 19-JAN-14:00 | 8.50 | 3.16 |
February | 0.887549E+09 | 5263.31 | 24-FEB-15:30 | 8.05 | 2.04 | 0.283847E+09 | 544.83 | 17-FEB-14:00 | 8.05 | 2.04 |
March | 0.292476E+10 | 10761.18 | 29-MAR-16:00 | 7.20 | 4.88 | 0.361162E+09 | 544.95 | 01-MAR-14:00 | 7.20 | 4.88 |
April | 0.441570E+10 | 27428.59 | 09-APR-16:21 | 16.65 | 13.97 | 0.343730E+09 | 544.96 | 10-APR-13:09 | 20.10 | 10.10 |
May | 0.689568E+10 | 26440.49 | 28-MAY-15:01 | 26.23 | 15.49 | 0.403926E+09 | 545.10 | 30-MAY-13:50 | 29.50 | 17.11 |
June | 0.941160E+10 | 27050.93 | 18-JUN-16:31 | 25.20 | 22.01 | 0.424266E+09 | 554.55 | 01-JUN-15:20 | 25.20 | 22.01 |
July | 0.103752E+11 | 29929.32 | 02-JUL-16:21 | 24.70 | 20.69 | 0.396918E+09 | 547.04 | 11-JUL-15:20 | 28.30 | 17.46 |
August | 0.115990E+11 | 29667.19 | 13-AUG-15:31 | 30.20 | 20.61 | 0.444945E+09 | 549.56 | 22-AUG-15:39 | 29.60 | 17.26 |
September | 0.688333E+10 | 25987.58 | 10-SEP-15:52 | 23.30 | 12.88 | 0.381717E+09 | 551.05 | 01-SEP-13:50 | 23.30 | 12.88 |
October | 0.518658E+10 | 24678.34 | 15-OCT-16:02 | 19.22 | 12.12 | 0.372394E+09 | 544.98 | 04-OCT-13:39 | 19.22 | 12.12 |
November | 0.171975E+10 | 6734.40 | 03-NOV-15:30 | 16.10 | 10.65 | 0.319411E+09 | 544.96 | 08-NOV-14:50 | 13.68 | 11.16 |
December | 0.801206E+09 | 3106.22 | 17-DEC-14:12 | 12.20 | 5.36 | 0.297147E+09 | 519.97 | 08-DEC-15:50 | 12.20 | 5.36 |
Annual Sum or Average | 0.617871E+11 | 0.433742E+10 | ||||||||
Minimum of Months | 0.686846E+09 | 3106.22 | 7.20 | 2.04 | 0.283847E+09 | 519.97 | 7.20 | 2.04 | ||
Maximum of Months | 0.115990E+11 | 29929.32 | 30.20 | 22.01 | 0.444945E+09 | 554.55 | 29.60 | 22.01 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.770375E+09 | 6445.95 | 14-JAN-06:01 | -7.8 | -8.5 | 0.00 | 0.00 | 01-JAN-00:10 | -7.8 | -8.5 |
February | 0.900771E+09 | 6109.28 | 13-FEB-06:01 | -9.4 | -11.3 | 0.00 | 0.00 | 01-FEB-00:10 | -9.4 | -11.3 |
March | 0.283198E+10 | 5241.14 | 29-MAR-05:10 | 2.12 | 0.18 | 0.00 | 0.00 | 01-MAR-00:10 | 2.12 | 0.18 |
April | 0.472659E+10 | 7307.61 | 10-APR-14:30 | 20.30 | 11.04 | 0.00 | 0.00 | 01-APR-00:10 | 20.30 | 11.04 |
May | 0.613168E+10 | 12137.53 | 30-MAY-05:02 | 18.17 | 14.31 | 0.00 | 0.00 | 01-MAY-00:10 | 18.17 | 14.31 |
June | 0.101964E+11 | 15717.57 | 26-JUN-05:15 | 20.97 | 17.23 | 0.00 | 0.00 | 01-JUN-00:10 | 20.97 | 17.23 |
July | 0.130495E+11 | 14889.01 | 10-JUL-05:15 | 26.10 | 20.74 | 0.00 | 0.00 | 01-JUL-00:10 | 26.10 | 20.74 |
August | 0.144631E+11 | 15674.05 | 07-AUG-05:10 | 19.40 | 16.74 | 0.00 | 0.00 | 01-AUG-00:10 | 19.40 | 16.74 |
September | 0.840779E+10 | 14719.27 | 05-SEP-05:10 | 20.60 | 18.00 | 0.00 | 0.00 | 01-SEP-00:10 | 20.60 | 18.00 |
October | 0.626193E+10 | 8331.66 | 16-OCT-05:15 | 8.90 | 8.42 | 0.00 | 0.00 | 01-OCT-00:10 | 8.90 | 8.42 |
November | 0.313980E+10 | 7442.82 | 13-NOV-06:15 | 5.77 | 4.71 | 0.00 | 0.00 | 01-NOV-00:10 | 5.77 | 4.71 |
December | 0.195809E+10 | 4386.37 | 20-DEC-06:10 | 3.53 | 1.84 | 0.00 | 0.00 | 01-DEC-00:10 | 3.53 | 1.84 |
Annual Sum or Average | 0.728380E+11 | 0.00 | ||||||||
Minimum of Months | 0.770375E+09 | 4386.37 | -9.4 | -11.3 | 0.00 | 0.00 | -9.4 | -11.3 | ||
Maximum of Months | 0.144631E+11 | 15717.57 | 26.10 | 20.74 | 0.00 | 0.00 | 26.10 | 20.74 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.250876E+09 | 7499.14 | 14-JAN-05:01 | -7.3 | -8.0 | 0.00 | 0.00 | 01-JAN-00:10 | -7.3 | -8.0 |
February | 0.350422E+09 | 10175.19 | 06-FEB-04:11 | -13.3 | -14.7 | 0.00 | 0.00 | 01-FEB-00:10 | -13.3 | -14.7 |
March | 0.966020E+09 | 7623.86 | 17-MAR-04:01 | -1.6 | -2.4 | 0.00 | 0.00 | 01-MAR-00:10 | -1.6 | -2.4 |
April | 0.208243E+10 | 5323.49 | 11-APR-05:10 | 6.10 | 1.72 | 0.00 | 0.00 | 01-APR-00:10 | 6.10 | 1.72 |
May | 0.401996E+10 | 7726.30 | 30-MAY-13:47 | 29.50 | 17.11 | 0.00 | 0.00 | 01-MAY-00:10 | 29.50 | 17.11 |
June | 0.672797E+10 | 7756.53 | 20-JUN-14:35 | 27.20 | 17.49 | 0.00 | 0.00 | 01-JUN-00:10 | 27.20 | 17.49 |
July | 0.788148E+10 | 8510.68 | 11-JUL-15:30 | 28.30 | 17.39 | 0.00 | 0.00 | 01-JUL-00:10 | 28.30 | 17.39 |
August | 0.874231E+10 | 9472.38 | 14-AUG-05:02 | 22.38 | 20.81 | 0.00 | 0.00 | 01-AUG-00:10 | 22.38 | 20.81 |
September | 0.551469E+10 | 8877.96 | 01-SEP-14:50 | 30.68 | 17.45 | 0.00 | 0.00 | 01-SEP-00:10 | 30.68 | 17.45 |
October | 0.354943E+10 | 5344.57 | 07-OCT-05:10 | 8.80 | 4.96 | 0.00 | 0.00 | 01-OCT-00:10 | 8.80 | 4.96 |
November | 0.105285E+10 | 7859.57 | 24-NOV-05:01 | -4.0 | -6.0 | 0.00 | 0.00 | 01-NOV-00:10 | -4.0 | -6.0 |
December | 0.442962E+09 | 6880.58 | 02-DEC-05:01 | 1.10 | -2.4 | 0.00 | 0.00 | 01-DEC-00:10 | 1.10 | -2.4 |
Annual Sum or Average | 0.415814E+11 | 0.00 | ||||||||
Minimum of Months | 0.250876E+09 | 5323.49 | -13.3 | -14.7 | 0.00 | 0.00 | -13.3 | -14.7 | ||
Maximum of Months | 0.874231E+10 | 10175.19 | 30.68 | 20.81 | 0.00 | 0.00 | 30.68 | 20.81 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 350130.19 | 188.76 | 19-JAN-13:00 | 9.40 | 4.18 | 0.00 | 0.00 | 01-JAN-00:10 | 9.40 | 4.18 |
February | 26896090.04 | 1789.53 | 20-FEB-14:10 | 8.80 | 4.54 | 0.00 | 0.00 | 01-FEB-00:10 | 8.80 | 4.54 |
March | 0.105748E+10 | 7277.32 | 03-MAR-14:40 | 15.00 | 8.47 | 0.00 | 0.00 | 01-MAR-00:10 | 15.00 | 8.47 |
April | 0.326768E+10 | 14708.94 | 07-APR-13:20 | 26.50 | 16.25 | 0.00 | 0.00 | 01-APR-00:10 | 26.50 | 16.25 |
May | 0.718548E+10 | 22746.85 | 30-MAY-13:17 | 29.80 | 17.64 | 0.00 | 0.00 | 01-MAY-00:10 | 29.80 | 17.64 |
June | 0.119425E+11 | 22158.87 | 19-JUN-13:30 | 34.70 | 23.81 | 0.00 | 0.00 | 01-JUN-00:10 | 34.70 | 23.81 |
July | 0.143300E+11 | 21102.90 | 07-JUL-13:50 | 32.80 | 23.64 | 0.00 | 0.00 | 01-JUL-00:10 | 32.80 | 23.64 |
August | 0.152645E+11 | 21089.85 | 22-AUG-14:40 | 30.37 | 17.86 | 0.00 | 0.00 | 01-AUG-00:10 | 30.37 | 17.86 |
September | 0.776837E+10 | 22078.54 | 01-SEP-14:32 | 30.77 | 17.43 | 0.00 | 0.00 | 01-SEP-00:10 | 30.77 | 17.43 |
October | 0.416816E+10 | 12864.38 | 04-OCT-13:25 | 24.70 | 18.75 | 0.00 | 0.00 | 01-OCT-00:10 | 24.70 | 18.75 |
November | 0.412763E+09 | 4696.92 | 03-NOV-14:20 | 17.60 | 10.78 | 0.00 | 0.00 | 01-NOV-00:10 | 17.60 | 10.78 |
December | 7002709.98 | 1605.96 | 17-DEC-14:18 | 12.20 | 5.36 | 0.00 | 0.00 | 01-DEC-00:10 | 12.20 | 5.36 |
Annual Sum or Average | 0.654312E+11 | 0.00 | ||||||||
Minimum of Months | 350130.19 | 188.76 | 8.80 | 4.18 | 0.00 | 0.00 | 8.80 | 4.18 | ||
Maximum of Months | 0.152645E+11 | 22746.85 | 34.70 | 23.81 | 0.00 | 0.00 | 34.70 | 23.81 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.266160E+10 | 2092.50 | 20-JAN-16:30 | 6.40 | 3.51 | 95230495.91 | 126.83 | 24-JAN-14:00 | 11.00 | 11.00 |
February | 0.744192E+10 | 4214.38 | 14-FEB-17:00 | 0.00 | -4.1 | 86396466.25 | 126.82 | 02-FEB-14:39 | 0.00 | -4.1 |
March | 0.141758E+11 | 6969.47 | 31-MAR-24:00 | 5.40 | 5.40 | 0.103237E+09 | 126.83 | 06-MAR-14:00 | 5.40 | 5.40 |
April | 0.188570E+11 | 8310.47 | 23-APR-17:42 | 12.38 | 8.83 | 91605510.03 | 126.83 | 17-APR-09:00 | 12.38 | 8.83 |
May | 0.448311E+10 | 3554.08 | 31-MAY-24:00 | 18.50 | 16.73 | 99238498.21 | 126.85 | 31-MAY-13:30 | 18.50 | 16.73 |
June | 0.954497E+10 | 5388.68 | 30-JUN-24:00 | 20.00 | 19.21 | 98973645.83 | 126.86 | 15-JUN-13:00 | 20.00 | 19.21 |
July | 0.150566E+11 | 7331.10 | 31-JUL-24:00 | 23.90 | 22.01 | 91891657.45 | 126.85 | 18-JUL-09:09 | 23.90 | 22.01 |
August | 0.201410E+11 | 8216.89 | 31-AUG-17:40 | 25.20 | 22.10 | 0.103489E+09 | 131.00 | 16-AUG-13:00 | 25.20 | 22.10 |
September | 0.455519E+10 | 3405.02 | 30-SEP-24:00 | 12.60 | 11.96 | 91611613.95 | 126.86 | 05-SEP-09:39 | 12.60 | 11.96 |
October | 0.956626E+10 | 5161.65 | 31-OCT-24:00 | 10.60 | 9.48 | 95238053.42 | 126.85 | 24-OCT-09:00 | 10.60 | 9.48 |
November | 0.136614E+11 | 5994.39 | 06-NOV-16:10 | 13.03 | 7.67 | 94301203.74 | 126.84 | 10-NOV-10:39 | 15.77 | 14.99 |
December | 0.189569E+11 | 7886.84 | 08-DEC-16:00 | 6.10 | 1.88 | 91880798.40 | 126.82 | 22-DEC-14:09 | 1.20 | -2.7 |
Annual Sum or Average | 0.139102E+12 | 0.114309E+10 | ||||||||
Minimum of Months | 0.266160E+10 | 2092.50 | 0.00 | -4.1 | 86396466.25 | 126.82 | 0.00 | -4.1 | ||
Maximum of Months | 0.201410E+11 | 8310.47 | 25.20 | 22.10 | 0.103489E+09 | 131.00 | 25.20 | 22.10 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.720121E+09 | 1786.99 | 20-JAN-16:40 | 6.13 | 3.40 | 94178927.81 | 126.83 | 24-JAN-14:50 | 10.93 | 10.93 |
February | 0.515721E+10 | 3779.77 | 22-FEB-17:00 | 3.30 | -0.7 | 86396474.34 | 126.82 | 02-FEB-14:39 | 3.30 | -0.7 |
March | 0.120148E+11 | 6092.37 | 31-MAR-23:40 | 5.67 | 5.67 | 0.103237E+09 | 126.83 | 06-MAR-14:00 | 5.67 | 5.67 |
April | 0.169843E+11 | 7629.76 | 09-APR-17:36 | 15.37 | 13.32 | 91605605.39 | 126.83 | 27-APR-13:00 | 17.20 | 14.14 |
May | 0.374632E+10 | 3348.60 | 31-MAY-24:00 | 18.50 | 16.73 | 99236231.53 | 126.85 | 31-MAY-09:00 | 18.50 | 16.73 |
June | 0.885367E+10 | 5042.59 | 30-JUN-24:00 | 20.00 | 19.21 | 98973701.25 | 126.86 | 15-JUN-13:00 | 20.00 | 19.21 |
July | 0.141255E+11 | 6962.95 | 31-JUL-24:00 | 23.90 | 22.01 | 91893591.57 | 126.85 | 20-JUL-09:39 | 23.90 | 22.01 |
August | 0.190161E+11 | 7857.91 | 31-AUG-17:30 | 25.30 | 22.17 | 0.103335E+09 | 129.18 | 16-AUG-13:00 | 25.30 | 22.17 |
September | 0.384329E+10 | 3074.09 | 30-SEP-23:30 | 13.00 | 12.21 | 91609587.34 | 126.85 | 05-SEP-09:09 | 13.00 | 12.21 |
October | 0.832483E+10 | 4436.91 | 31-OCT-24:00 | 10.60 | 9.48 | 95237621.76 | 126.85 | 06-OCT-09:09 | 10.60 | 9.48 |
November | 0.113173E+11 | 5608.60 | 03-NOV-16:00 | 15.00 | 10.26 | 94301130.94 | 126.84 | 10-NOV-10:39 | 15.77 | 14.99 |
December | 0.157830E+11 | 7266.93 | 08-DEC-16:10 | 5.92 | 1.77 | 91880826.44 | 126.82 | 22-DEC-14:09 | 1.20 | -2.7 |
Annual Sum or Average | 0.119886E+12 | 0.114189E+10 | ||||||||
Minimum of Months | 0.720121E+09 | 1786.99 | 3.30 | -0.7 | 86396474.34 | 126.82 | 1.20 | -2.7 | ||
Maximum of Months | 0.190161E+11 | 7857.91 | 25.30 | 22.17 | 0.103335E+09 | 129.18 | 25.30 | 22.17 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.342414E+09 | 1694.31 | 20-JAN-16:40 | 6.13 | 3.40 | 91923143.19 | 126.85 | 25-JAN-10:09 | 4.40 | 1.15 |
February | 0.354171E+10 | 3672.13 | 22-FEB-17:00 | 3.30 | -0.7 | 86396489.99 | 126.82 | 02-FEB-14:39 | 3.30 | -0.7 |
March | 0.107099E+11 | 5761.74 | 29-MAR-17:20 | 5.73 | 4.14 | 0.103237E+09 | 126.83 | 06-MAR-14:00 | 5.73 | 4.14 |
April | 0.161198E+11 | 7692.37 | 09-APR-17:30 | 15.55 | 13.44 | 91605644.15 | 126.83 | 27-APR-13:00 | 17.20 | 14.14 |
May | 0.339120E+10 | 3306.36 | 31-MAY-24:00 | 18.50 | 16.73 | 99236096.00 | 126.86 | 31-MAY-13:09 | 18.50 | 16.73 |
June | 0.883142E+10 | 4958.67 | 30-JUN-24:00 | 20.00 | 19.21 | 98973894.33 | 126.86 | 15-JUN-13:20 | 20.00 | 19.21 |
July | 0.142112E+11 | 6962.74 | 31-JUL-24:00 | 23.90 | 22.01 | 91893530.99 | 126.85 | 20-JUL-09:30 | 23.90 | 22.01 |
August | 0.190614E+11 | 7933.73 | 13-AUG-17:15 | 29.23 | 20.43 | 0.103300E+09 | 128.44 | 16-AUG-13:00 | 32.20 | 25.36 |
September | 0.359756E+10 | 2766.70 | 30-SEP-23:20 | 13.13 | 12.30 | 91609892.62 | 126.86 | 06-SEP-13:39 | 13.13 | 12.30 |
October | 0.750088E+10 | 4061.61 | 04-OCT-16:30 | 22.25 | 18.94 | 95237659.26 | 126.85 | 06-OCT-09:09 | 18.95 | 17.77 |
November | 0.978253E+10 | 5587.58 | 03-NOV-16:00 | 15.00 | 10.26 | 94301147.60 | 126.84 | 10-NOV-10:39 | 15.77 | 14.99 |
December | 0.138376E+11 | 7086.13 | 08-DEC-16:10 | 5.92 | 1.77 | 91880835.05 | 126.82 | 22-DEC-14:09 | 1.20 | -2.7 |
Annual Sum or Average | 0.110928E+12 | 0.113959E+10 | ||||||||
Minimum of Months | 0.342414E+09 | 1694.31 | 3.30 | -0.7 | 86396489.99 | 126.82 | 1.20 | -2.7 | ||
Maximum of Months | 0.190614E+11 | 7933.73 | 29.23 | 22.01 | 0.103300E+09 | 128.44 | 32.20 | 25.36 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.236554E+12 | 91973.58 | 20-JAN-17:00 | 5.60 | 3.19 | 0.206143E+10 | 2745.29 | 19-JAN-14:00 | 5.60 | 3.19 |
February | 0.434576E+12 | 183410.90 | 22-FEB-17:00 | 3.30 | -0.7 | 0.187023E+10 | 2745.42 | 02-FEB-10:09 | 3.30 | -0.7 |
March | 0.729187E+12 | 358431.15 | 31-MAR-24:00 | 5.40 | 5.40 | 0.223479E+10 | 2745.93 | 02-MAR-10:09 | 5.40 | 5.40 |
April | 0.943135E+12 | 367990.25 | 10-APR-16:00 | 20.00 | 11.13 | 0.198343E+10 | 2751.12 | 06-APR-09:30 | 20.00 | 11.13 |
May | 0.240996E+12 | 176594.23 | 31-MAY-24:00 | 18.50 | 16.73 | 0.214808E+10 | 2746.63 | 31-MAY-13:09 | 18.50 | 16.73 |
June | 0.472361E+12 | 268292.21 | 30-JUN-24:00 | 20.00 | 19.21 | 0.214263E+10 | 2748.90 | 05-JUN-13:09 | 20.00 | 19.21 |
July | 0.735967E+12 | 361181.03 | 31-JUL-23:55 | 23.90 | 22.01 | 0.198935E+10 | 2748.20 | 11-JUL-09:09 | 23.90 | 22.01 |
August | 0.982386E+12 | 396911.11 | 22-AUG-14:43 | 30.18 | 17.70 | 0.223874E+10 | 3065.52 | 30-AUG-15:09 | 29.22 | 15.03 |
September | 0.237824E+12 | 176495.20 | 30-SEP-24:00 | 12.60 | 11.96 | 0.198316E+10 | 2746.95 | 14-SEP-09:00 | 12.60 | 11.96 |
October | 0.489117E+12 | 268282.05 | 31-OCT-24:00 | 10.60 | 9.48 | 0.206159E+10 | 2748.88 | 02-OCT-13:00 | 10.60 | 9.48 |
November | 0.708845E+12 | 277134.97 | 06-NOV-17:00 | 11.70 | 7.36 | 0.204131E+10 | 2747.08 | 09-NOV-10:09 | 14.40 | 10.88 |
December | 0.976291E+12 | 368196.88 | 18-DEC-17:00 | 3.30 | 0.83 | 0.198896E+10 | 2745.38 | 12-DEC-14:30 | 3.30 | 0.83 |
Annual Sum or Average | 0.718724E+13 | 0.247437E+11 | ||||||||
Minimum of Months | 0.236554E+12 | 91973.58 | 3.30 | -0.7 | 0.187023E+10 | 2745.29 | 3.30 | -0.7 | ||
Maximum of Months | 0.982386E+12 | 396911.11 | 30.18 | 22.01 | 0.223874E+10 | 3065.52 | 29.22 | 22.01 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.674305E+09 | 49520.94 | 02-JAN-04:01 | -11.8 |
February | 16068202.22 | 37784.03 | 06-FEB-06:01 | -12.9 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.690373E+09 | |||
Minimum of Months | 0.00 | 0.00 | -12.9 | |
Maximum of Months | 0.674305E+09 | 49520.94 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.386976E+10 | 82536.60 | 02-JAN-04:01 | -11.8 |
February | 0.257163E+10 | 80578.46 | 06-FEB-04:01 | -13.3 |
March | 0.419829E+09 | 72567.18 | 20-MAR-04:01 | -0.8 |
April | 59752566.82 | 67066.32 | 03-APR-05:02 | 2.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.930787E+09 | 74330.13 | 24-NOV-05:01 | -4.0 |
December | 0.131864E+10 | 77208.40 | 26-DEC-05:11 | 5.77 |
Annual Sum or Average | 0.917040E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.386976E+10 | 82536.60 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.173333E+09 | 12701.94 | 02-JAN-05:01 | -12.1 |
February | 0.136466E+09 | 12529.49 | 06-FEB-05:01 | -13.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.309798E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.173333E+09 | 12701.94 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.131971E+09 | 10493.54 | 02-JAN-05:01 | -12.1 |
February | 87914622.34 | 10294.76 | 06-FEB-05:01 | -13.2 |
March | 1275114.20 | 6941.36 | 17-MAR-05:01 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 1924221.19 | 7089.41 | 22-NOV-06:01 | -2.2 |
December | 2929877.64 | 6360.67 | 07-DEC-06:01 | 0.10 |
Annual Sum or Average | 0.226015E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.131971E+09 | 10493.54 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.313783E+09 | 16666.95 | 02-JAN-04:01 | -11.8 |
February | 0.183319E+09 | 16128.91 | 06-FEB-05:01 | -13.2 |
March | 4580634.09 | 12511.34 | 13-MAR-05:01 | -0.6 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 7023511.47 | 12402.22 | 24-NOV-06:02 | -4.4 |
December | 9681442.57 | 12509.56 | 07-DEC-06:01 | 0.10 |
Annual Sum or Average | 0.518388E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.313783E+09 | 16666.95 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 21779639.95 | 7763.13 | 02-JAN-05:01 | -12.1 |
February | 7997211.19 | 7046.91 | 06-FEB-06:01 | -12.9 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 29776851.14 | |||
Minimum of Months | 0.00 | 0.00 | -12.9 | |
Maximum of Months | 21779639.95 | 7763.13 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.336198E+10 | 14709.26 | 01-JAN-22:02 | -9.5 |
February | 0.246315E+10 | 14244.18 | 06-FEB-04:11 | -13.3 |
March | 0.486437E+09 | 12393.81 | 13-MAR-04:01 | -0.1 |
April | 60227391.10 | 11797.32 | 03-APR-04:11 | 2.80 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 1908105.41 | 5366.43 | 28-OCT-05:03 | 3.90 |
November | 0.543710E+09 | 13035.65 | 24-NOV-04:01 | -3.4 |
December | 0.136790E+10 | 12548.22 | 11-DEC-05:01 | 1.70 |
Annual Sum or Average | 0.828531E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.336198E+10 | 14709.26 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.185212E+10 | 18038.50 | 01-JAN-22:02 | -9.5 |
February | 0.114548E+10 | 17618.94 | 06-FEB-04:11 | -13.3 |
March | 0.251259E+09 | 14869.25 | 13-MAR-04:01 | -0.1 |
April | 33631122.58 | 13501.54 | 22-APR-05:02 | 5.50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 352979.49 | 1855.70 | 28-OCT-05:03 | 3.90 |
November | 0.281625E+09 | 15418.21 | 24-NOV-05:01 | -4.0 |
December | 0.763369E+09 | 15284.99 | 11-DEC-05:01 | 1.70 |
Annual Sum or Average | 0.432783E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.185212E+10 | 18038.50 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.191658E+10 | 21172.80 | 02-JAN-02:42 | -11.7 |
February | 0.106841E+10 | 20594.26 | 06-FEB-04:11 | -13.3 |
March | 0.242130E+09 | 17666.82 | 17-MAR-04:01 | -1.6 |
April | 37820975.71 | 16523.87 | 22-APR-05:02 | 5.50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.231485E+09 | 18203.77 | 24-NOV-05:01 | -4.0 |
December | 0.708775E+09 | 18451.01 | 11-DEC-05:01 | 1.70 |
Annual Sum or Average | 0.420520E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.191658E+10 | 21172.80 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.151965E+10 | 17870.74 | 01-JAN-22:02 | -9.5 |
February | 0.974865E+09 | 17438.91 | 06-FEB-04:11 | -13.3 |
March | 0.136348E+09 | 14321.23 | 17-MAR-04:01 | -1.6 |
April | 12365701.12 | 10093.91 | 22-APR-05:02 | 5.50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 2943.93 | 19.63 | 28-OCT-05:05 | 3.90 |
November | 0.202353E+09 | 15300.45 | 24-NOV-05:01 | -4.0 |
December | 0.489561E+09 | 15151.07 | 11-DEC-05:01 | 1.70 |
Annual Sum or Average | 0.333514E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.151965E+10 | 17870.74 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.673579E+10 | 16992.93 | 01-JAN-22:02 | -9.5 |
February | 0.594109E+10 | 17012.47 | 05-FEB-22:42 | -12.0 |
March | 0.189141E+10 | 15858.87 | 13-MAR-03:01 | 0.50 |
April | 0.522493E+09 | 15174.36 | 03-APR-04:11 | 2.80 |
May | 14079563.69 | 12947.96 | 01-MAY-05:02 | 6.28 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.167136E+09 | 13371.81 | 10-OCT-04:12 | 10.40 |
November | 0.213475E+10 | 15885.36 | 23-NOV-23:43 | -3.2 |
December | 0.444063E+10 | 16534.79 | 31-DEC-21:12 | -6.9 |
Annual Sum or Average | 0.218474E+11 | |||
Minimum of Months | 0.00 | 0.00 | -12.0 | |
Maximum of Months | 0.673579E+10 | 17012.47 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.370156E+10 | 20384.76 | 01-JAN-22:02 | -9.5 |
February | 0.289360E+10 | 20367.38 | 06-FEB-04:01 | -13.3 |
March | 0.913397E+09 | 19191.83 | 13-MAR-03:01 | 0.50 |
April | 0.283291E+09 | 18244.61 | 03-APR-04:11 | 2.80 |
May | 7064052.77 | 15389.13 | 01-MAY-05:02 | 6.28 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 76617386.74 | 14078.90 | 31-OCT-05:02 | 4.60 |
November | 0.108847E+10 | 19205.10 | 20-NOV-04:11 | 0.60 |
December | 0.237738E+10 | 19570.59 | 31-DEC-21:12 | -6.9 |
Annual Sum or Average | 0.113414E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.370156E+10 | 20384.76 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.421640E+10 | 23477.77 | 02-JAN-02:42 | -11.7 |
February | 0.319356E+10 | 23302.42 | 06-FEB-04:01 | -13.3 |
March | 0.115021E+10 | 21721.60 | 13-MAR-03:01 | 0.50 |
April | 0.405432E+09 | 20580.59 | 03-APR-04:11 | 2.80 |
May | 15859346.23 | 18144.74 | 01-MAY-05:02 | 6.28 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 40070765.69 | 16235.50 | 27-OCT-05:02 | 6.02 |
November | 0.113056E+10 | 22146.94 | 20-NOV-04:11 | 0.60 |
December | 0.260326E+10 | 22333.62 | 26-DEC-05:11 | 5.77 |
Annual Sum or Average | 0.127553E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.421640E+10 | 23477.77 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.317883E+10 | 21259.54 | 01-JAN-22:02 | -9.5 |
February | 0.246022E+10 | 21158.42 | 06-FEB-04:01 | -13.3 |
March | 0.636670E+09 | 19238.99 | 13-MAR-03:01 | 0.50 |
April | 0.157501E+09 | 17541.85 | 03-APR-04:11 | 2.80 |
May | 2298411.21 | 8015.26 | 01-MAY-05:02 | 6.28 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 34087167.19 | 10634.06 | 27-OCT-05:02 | 6.02 |
November | 0.843848E+09 | 19803.73 | 20-NOV-04:11 | 0.60 |
December | 0.170311E+10 | 19911.12 | 11-DEC-04:51 | 1.70 |
Annual Sum or Average | 0.901657E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.317883E+10 | 21259.54 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.758277E+09 | 9812.10 | 12-JAN-06:02 | 1.78 |
February | 0.480616E+09 | 9823.06 | 16-FEB-06:03 | 1.60 |
March | 86189283.06 | 10277.94 | 13-MAR-04:01 | -0.1 |
April | 0.129717E+09 | 10965.54 | 24-APR-04:12 | 8.13 |
May | 65911711.97 | 8687.96 | 01-MAY-04:12 | 6.50 |
June | 0.109247E+09 | 9496.55 | 15-JUN-04:12 | 20.93 |
July | 0.187521E+09 | 10107.76 | 29-JUL-04:11 | 21.87 |
August | 0.163799E+09 | 9747.81 | 13-AUG-13:42 | 31.60 |
September | 85905989.07 | 10152.82 | 14-SEP-04:12 | 22.20 |
October | 86660681.96 | 9370.79 | 10-OCT-04:12 | 10.40 |
November | 73564140.54 | 11494.80 | 27-NOV-05:11 | 6.30 |
December | 0.121204E+09 | 12565.18 | 26-DEC-05:11 | 5.77 |
Annual Sum or Average | 0.234861E+10 | |||
Minimum of Months | 65911711.97 | 8687.96 | -0.1 | |
Maximum of Months | 0.758277E+09 | 12565.18 | 31.60 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.374960E+10 | 17961.57 | 02-JAN-06:23 | -11.7 |
February | 0.208341E+10 | 8632.13 | 20-FEB-13:32 | 9.07 |
March | 0.946883E+09 | 6068.16 | 28-MAR-05:03 | 9.50 |
April | 0.273389E+09 | 8310.71 | 23-APR-15:51 | 13.30 |
May | 59936561.09 | 8771.42 | 29-MAY-13:52 | 26.10 |
June | 39104419.05 | 6122.05 | 04-JUN-14:31 | 24.07 |
July | 64921427.58 | 9672.58 | 04-JUL-15:01 | 27.02 |
August | 48040333.25 | 8794.89 | 13-AUG-15:01 | 30.50 |
September | 54676051.81 | 8454.04 | 04-SEP-13:41 | 26.10 |
October | 60511517.35 | 7252.45 | 15-OCT-14:52 | 20.60 |
November | 0.632258E+09 | 5526.16 | 14-NOV-06:02 | 10.00 |
December | 0.134133E+10 | 8478.32 | 17-DEC-13:02 | 12.20 |
Annual Sum or Average | 0.935406E+10 | |||
Minimum of Months | 39104419.05 | 5526.16 | -11.7 | |
Maximum of Months | 0.374960E+10 | 17961.57 | 30.50 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.956895E+10 | 28123.50 | 02-JAN-05:08 | -12.1 |
February | 0.793663E+10 | 29321.53 | 06-FEB-05:10 | -13.2 |
March | 0.336006E+10 | 16805.37 | 20-MAR-05:03 | -1.5 |
April | 0.138725E+10 | 13908.08 | 03-APR-05:02 | 2.70 |
May | 0.248289E+09 | 13205.23 | 12-MAY-05:03 | 11.20 |
June | 54642764.05 | 13066.84 | 03-JUN-05:03 | 13.48 |
July | 39013706.09 | 10585.86 | 05-JUL-04:12 | 20.60 |
August | 48538218.23 | 11753.27 | 08-AUG-05:02 | 15.37 |
September | 0.151354E+09 | 13912.50 | 29-SEP-05:02 | 11.78 |
October | 0.799567E+09 | 13252.25 | 12-OCT-05:02 | 12.70 |
November | 0.380471E+10 | 22192.42 | 24-NOV-05:12 | -4.1 |
December | 0.692492E+10 | 19656.49 | 11-DEC-05:13 | 1.70 |
Annual Sum or Average | 0.343239E+11 | |||
Minimum of Months | 39013706.09 | 10585.86 | -13.2 | |
Maximum of Months | 0.956895E+10 | 29321.53 | 20.60 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.355099E+09 | 540.12 | 03-JAN-01:00 | -3.9 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.355099E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.9 | |
Maximum of Months | 0.355099E+09 | 540.12 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.707993E+09 | 587.98 | 16-JAN-17:55 | 3.90 |
February | 44694780.05 | 535.24 | 06-FEB-00:17 | -13.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 530345.37 | 362.91 | 01-MAY-04:35 | 6.30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.753218E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.707993E+09 | 587.98 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180249E+11 | 19402.09 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.163527E+11 | 19402.09 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.194806E+11 | 19402.09 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.173504E+11 | 19402.09 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.187528E+11 | 19402.09 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.186803E+11 | 19402.09 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.174228E+11 | 19402.09 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.194803E+11 | 19402.09 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.173504E+11 | 19402.09 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.180252E+11 | 19402.09 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.178272E+11 | 19402.09 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.174231E+11 | 19402.09 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.216171E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.163527E+11 | 19402.09 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.194806E+11 | 19402.09 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.136862E+10 | 2187.81 | 02-JAN-16:10 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.114245E+10 | 2187.81 | 01-FEB-16:49 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.125891E+10 | 1906.53 | 02-MAR-16:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.106369E+10 | 1242.97 | 18-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.111980E+10 | 1242.97 | 08-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.109764E+10 | 1141.96 | 16-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.103150E+10 | 1141.96 | 05-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.116860E+10 | 1242.97 | 16-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.108819E+10 | 1524.25 | 27-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.118294E+10 | 1906.53 | 06-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.130154E+10 | 2187.81 | 06-NOV-16:19 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.135599E+10 | 2187.81 | 01-DEC-16:10 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.141799E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.103150E+10 | 1141.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.136862E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.865280E+09 | 1409.91 | 02-JAN-16:10 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.725527E+09 | 1409.91 | 01-FEB-16:49 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.807949E+09 | 1228.64 | 02-MAR-16:49 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.686236E+09 | 735.93 | 05-APR-15:39 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.726785E+09 | 801.02 | 19-MAY-15:00 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.714135E+09 | 735.93 | 29-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.669761E+09 | 670.83 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.756142E+09 | 735.93 | 16-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.699614E+09 | 801.02 | 22-SEP-15:50 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.757635E+09 | 1228.64 | 06-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.829012E+09 | 1409.91 | 06-NOV-16:19 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.846656E+09 | 1409.91 | 01-DEC-16:10 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.908473E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.669761E+09 | 670.83 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.865280E+09 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.129900E+10 | 2187.86 | 02-JAN-16:30 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.109633E+10 | 2187.86 | 01-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.124210E+10 | 1524.28 | 02-MAR-16:40 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.106439E+10 | 1243.00 | 21-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.112585E+10 | 1243.00 | 08-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.110663E+10 | 1141.99 | 16-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.103905E+10 | 1141.99 | 05-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.117388E+10 | 1243.00 | 16-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.108193E+10 | 1524.28 | 27-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.115937E+10 | 1906.57 | 06-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.125296E+10 | 2187.86 | 06-NOV-16:40 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.126316E+10 | 2187.86 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.139046E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.103905E+10 | 1141.99 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.129900E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.850579E+09 | 1409.91 | 02-JAN-16:30 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.714168E+09 | 1409.91 | 01-FEB-16:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.800129E+09 | 1047.37 | 16-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.685624E+09 | 982.28 | 14-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.719871E+09 | 801.02 | 04-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.707924E+09 | 801.02 | 16-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.665653E+09 | 801.02 | 24-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.752557E+09 | 801.02 | 16-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.698955E+09 | 982.28 | 21-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.750508E+09 | 1228.64 | 06-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.814425E+09 | 1409.91 | 06-NOV-16:40 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.835078E+09 | 1409.91 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.899547E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.665653E+09 | 801.02 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.850579E+09 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.136320E+10 | 2187.81 | 02-JAN-16:19 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.113681E+10 | 2187.81 | 01-FEB-16:49 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.125578E+10 | 1805.53 | 02-MAR-16:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.106189E+10 | 1141.96 | 13-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.111893E+10 | 1141.96 | 04-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.109705E+10 | 1141.96 | 16-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.103018E+10 | 1141.96 | 24-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.116783E+10 | 1242.97 | 16-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.108657E+10 | 1524.25 | 27-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.118046E+10 | 1906.53 | 06-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.129712E+10 | 2187.81 | 06-NOV-16:19 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.135052E+10 | 2187.81 | 01-DEC-16:10 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.141463E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.103018E+10 | 1141.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.136320E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.862590E+09 | 1409.91 | 02-JAN-16:10 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.723376E+09 | 1409.91 | 01-FEB-16:49 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.806009E+09 | 1228.64 | 02-MAR-16:49 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.685337E+09 | 735.93 | 05-APR-15:50 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.726213E+09 | 735.93 | 04-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.713545E+09 | 735.93 | 29-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.669046E+09 | 670.83 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.755729E+09 | 735.93 | 16-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.698637E+09 | 801.02 | 22-SEP-15:50 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.755980E+09 | 1228.64 | 31-OCT-15:50 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.827161E+09 | 1409.91 | 06-NOV-16:19 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.844313E+09 | 1409.91 | 01-DEC-16:10 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.906794E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.669046E+09 | 670.83 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.862590E+09 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.129730E+10 | 2187.86 | 02-JAN-16:30 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.109493E+10 | 2187.86 | 01-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.123924E+10 | 1524.28 | 02-MAR-16:40 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.106331E+10 | 1141.99 | 14-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.112464E+10 | 1141.99 | 04-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.110588E+10 | 1141.99 | 16-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.103807E+10 | 1141.99 | 05-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.117310E+10 | 1243.00 | 16-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.108061E+10 | 1524.28 | 27-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.115780E+10 | 1906.57 | 06-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.125173E+10 | 2187.86 | 06-NOV-16:40 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.126102E+10 | 2187.86 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.138876E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.103807E+10 | 1141.99 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.129730E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.847647E+09 | 1409.91 | 02-JAN-16:30 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.712369E+09 | 1409.91 | 01-FEB-16:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.798051E+09 | 982.28 | 06-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.684470E+09 | 801.02 | 14-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.719295E+09 | 801.02 | 04-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.707106E+09 | 801.02 | 29-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.664866E+09 | 801.02 | 24-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.752039E+09 | 801.02 | 16-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.697756E+09 | 982.28 | 21-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.749396E+09 | 1228.64 | 06-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.812852E+09 | 1409.91 | 06-NOV-16:40 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.832784E+09 | 1409.91 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.897863E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.664866E+09 | 801.02 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.847647E+09 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.136314E+10 | 2187.81 | 02-JAN-16:19 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.113672E+10 | 2187.81 | 01-FEB-16:49 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.125564E+10 | 1805.53 | 02-MAR-16:00 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.106175E+10 | 1141.96 | 13-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.111891E+10 | 1141.96 | 04-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.109705E+10 | 1141.96 | 16-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.103014E+10 | 1141.96 | 24-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.116783E+10 | 1242.97 | 16-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.108649E+10 | 1524.25 | 27-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.118033E+10 | 1906.53 | 06-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.129704E+10 | 2187.81 | 06-NOV-16:19 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.135046E+10 | 2187.81 | 01-DEC-16:10 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.141455E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.103014E+10 | 1141.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.136314E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.862432E+09 | 1409.91 | 02-JAN-16:10 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.723050E+09 | 1409.91 | 01-FEB-16:49 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.805934E+09 | 1228.64 | 02-MAR-16:49 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.685298E+09 | 735.93 | 05-APR-15:50 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.726179E+09 | 735.93 | 04-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.713490E+09 | 735.93 | 29-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.669011E+09 | 670.83 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.755729E+09 | 735.93 | 16-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.698618E+09 | 801.02 | 22-SEP-15:50 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.755980E+09 | 1228.64 | 31-OCT-15:50 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.827121E+09 | 1409.91 | 06-NOV-16:19 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.844048E+09 | 1409.91 | 01-DEC-16:10 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.906689E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.669011E+09 | 670.83 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.862432E+09 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.129705E+10 | 2187.86 | 02-JAN-16:30 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.109485E+10 | 2187.86 | 01-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.123890E+10 | 1524.28 | 02-MAR-16:40 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.106330E+10 | 1141.99 | 14-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.112456E+10 | 1141.99 | 04-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.110579E+10 | 1141.99 | 16-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.103797E+10 | 1141.99 | 05-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.117307E+10 | 1243.00 | 16-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.108058E+10 | 1524.28 | 27-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.115780E+10 | 1906.57 | 06-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.125155E+10 | 2187.86 | 06-NOV-16:40 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.126102E+10 | 2187.86 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.138865E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.103797E+10 | 1141.99 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.129705E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.847530E+09 | 1409.91 | 02-JAN-16:30 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.712365E+09 | 1409.91 | 01-FEB-16:00 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.798038E+09 | 982.28 | 06-MAR-08:09 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.684506E+09 | 801.02 | 14-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.719241E+09 | 801.02 | 04-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.706992E+09 | 801.02 | 29-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.664886E+09 | 801.02 | 24-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.752039E+09 | 801.02 | 16-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.697715E+09 | 982.28 | 21-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.749396E+09 | 1228.64 | 06-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.812813E+09 | 1409.91 | 06-NOV-16:40 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.832616E+09 | 1409.91 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.897814E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.664886E+09 | 801.02 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.847530E+09 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.522764E+10 | 5470.56 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.474186E+10 | 5470.56 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.563465E+10 | 5470.56 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.503289E+10 | 5470.56 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.543115E+10 | 5470.56 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.540489E+10 | 5470.56 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.505915E+10 | 5470.56 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.563465E+10 | 5470.56 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.503289E+10 | 5470.56 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.522764E+10 | 5470.56 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.516637E+10 | 5470.56 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.505915E+10 | 5470.56 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.626529E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.474186E+10 | 5470.56 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.563465E+10 | 5470.56 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.180249E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.163527E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.194806E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.173504E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.187528E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.186803E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.174228E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.194803E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.173504E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.180252E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.178272E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.174231E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.216171E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.163527E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.194806E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.136862E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.676969E+09 |
February | 0.136985E+10 | 0.114245E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.590281E+09 |
March | 0.163685E+10 | 0.125891E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.494188E+09 |
April | 0.145243E+10 | 0.106369E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 226639.79 | 0.330736E+09 |
May | 0.157338E+10 | 0.111980E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 982300.90 | 0.186344E+09 |
June | 0.156900E+10 | 0.109764E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7063974.59 | 96781838.76 |
July | 0.145680E+10 | 0.103150E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16765351.45 | 34056973.81 |
August | 0.163685E+10 | 0.116860E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20783227.78 | 40837939.86 |
September | 0.145243E+10 | 0.108819E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2584561.92 | 0.105047E+09 |
October | 0.150991E+10 | 0.118294E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42923.93 | 0.259401E+09 |
November | 0.149516E+10 | 0.130154E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498812E+09 |
December | 0.145680E+10 | 0.135599E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.595429E+09 |
Annual Sum or Average | 0.181194E+11 | 0.141799E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48448980.35 | 0.390888E+10 |
Minimum of Months | 0.136985E+10 | 0.103150E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34056973.81 |
Maximum of Months | 0.163685E+10 | 0.136862E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20783227.78 | 0.676969E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.865280E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449061E+09 |
February | 0.882782E+09 | 0.725527E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395067E+09 |
March | 0.105485E+10 | 0.807949E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323738E+09 |
April | 0.936002E+09 | 0.686236E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 151080.57 | 0.215496E+09 |
May | 0.101394E+10 | 0.726785E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 577680.73 | 0.123571E+09 |
June | 0.101113E+10 | 0.714135E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4946636.54 | 61166283.00 |
July | 0.938820E+09 | 0.669761E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12037276.92 | 18302000.62 |
August | 0.105485E+10 | 0.756142E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14745868.43 | 23105787.96 |
September | 0.936002E+09 | 0.699614E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1737444.81 | 69984081.27 |
October | 0.973041E+09 | 0.757635E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28610.46 | 0.171625E+09 |
November | 0.963541E+09 | 0.829012E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326568E+09 |
December | 0.938820E+09 | 0.846656E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387344E+09 |
Annual Sum or Average | 0.116768E+11 | 0.908473E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34224598.46 | 0.256503E+10 |
Minimum of Months | 0.882782E+09 | 0.669761E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18302000.62 |
Maximum of Months | 0.105485E+10 | 0.865280E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14745868.43 | 0.449061E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.129900E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672059E+09 |
February | 0.136988E+10 | 0.109633E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.603374E+09 |
March | 0.163688E+10 | 0.124210E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.493949E+09 |
April | 0.145246E+10 | 0.106439E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 223304.26 | 0.328484E+09 |
May | 0.157341E+10 | 0.112585E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 833161.12 | 0.184906E+09 |
June | 0.156904E+10 | 0.110663E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7065168.23 | 94734182.34 |
July | 0.145684E+10 | 0.103905E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16967757.11 | 31871438.76 |
August | 0.163688E+10 | 0.117388E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20598273.30 | 40609355.57 |
September | 0.145246E+10 | 0.108193E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2528234.56 | 0.109160E+09 |
October | 0.150994E+10 | 0.115937E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24749.60 | 0.272010E+09 |
November | 0.149520E+10 | 0.125296E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498413E+09 |
December | 0.145684E+10 | 0.126316E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.592732E+09 |
Annual Sum or Average | 0.181198E+11 | 0.139046E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48240648.18 | 0.392230E+10 |
Minimum of Months | 0.136988E+10 | 0.103905E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31871438.76 |
Maximum of Months | 0.163688E+10 | 0.129900E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20598273.30 | 0.672059E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.850579E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469745E+09 |
February | 0.882782E+09 | 0.714168E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418218E+09 |
March | 0.105485E+10 | 0.800129E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360458E+09 |
April | 0.936002E+09 | 0.685624E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 147118.29 | 0.248690E+09 |
May | 0.101394E+10 | 0.719871E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 695403.88 | 0.134846E+09 |
June | 0.101113E+10 | 0.707924E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4703052.04 | 72982798.84 |
July | 0.938820E+09 | 0.665653E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11061835.01 | 26102100.12 |
August | 0.105485E+10 | 0.752557E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13401767.48 | 32101909.11 |
September | 0.936002E+09 | 0.698955E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1739463.98 | 76801168.95 |
October | 0.973041E+09 | 0.750508E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28624.07 | 0.191811E+09 |
November | 0.963541E+09 | 0.814425E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362597E+09 |
December | 0.938820E+09 | 0.835078E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438055E+09 |
Annual Sum or Average | 0.116768E+11 | 0.899547E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31777264.75 | 0.283241E+10 |
Minimum of Months | 0.882782E+09 | 0.665653E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26102100.12 |
Maximum of Months | 0.105485E+10 | 0.850579E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13401767.48 | 0.469745E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.136320E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139116E+10 |
February | 0.136985E+10 | 0.113681E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123572E+10 |
March | 0.163685E+10 | 0.125578E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101805E+10 |
April | 0.145243E+10 | 0.106189E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 496257.10 | 0.677217E+09 |
May | 0.157338E+10 | 0.111893E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2606660.19 | 0.407107E+09 |
June | 0.156900E+10 | 0.109705E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17132481.02 | 0.211956E+09 |
July | 0.145680E+10 | 0.103018E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39929312.59 | 74459678.20 |
August | 0.163685E+10 | 0.116783E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48898630.24 | 94733087.00 |
September | 0.145243E+10 | 0.108657E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5950000.53 | 0.217828E+09 |
October | 0.150991E+10 | 0.118046E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77876.19 | 0.538109E+09 |
November | 0.149516E+10 | 0.129712E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.998394E+09 |
December | 0.145680E+10 | 0.135052E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118923E+10 |
Annual Sum or Average | 0.181194E+11 | 0.141463E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115091E+09 | 0.805397E+10 |
Minimum of Months | 0.136985E+10 | 0.103018E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74459678.20 |
Maximum of Months | 0.163685E+10 | 0.136320E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48898630.24 | 0.139116E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.862590E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.931310E+09 |
February | 0.649041E+09 | 0.723376E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.842320E+09 |
March | 0.773965E+09 | 0.806009E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.691877E+09 |
April | 0.688021E+09 | 0.685337E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 331489.54 | 0.467358E+09 |
May | 0.744847E+09 | 0.726213E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1258933.79 | 0.274856E+09 |
June | 0.742030E+09 | 0.713545E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11515759.02 | 0.141591E+09 |
July | 0.690839E+09 | 0.669046E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27051081.15 | 49450661.37 |
August | 0.773965E+09 | 0.755729E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32066215.20 | 65630218.88 |
September | 0.688021E+09 | 0.698637E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3906150.21 | 0.151772E+09 |
October | 0.715730E+09 | 0.755980E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51866.78 | 0.371116E+09 |
November | 0.708685E+09 | 0.827161E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678357E+09 |
December | 0.690839E+09 | 0.844313E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.801951E+09 |
Annual Sum or Average | 0.858171E+10 | 0.906794E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 76181495.69 | 0.546759E+10 |
Minimum of Months | 0.649041E+09 | 0.669046E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49450661.37 |
Maximum of Months | 0.773965E+09 | 0.862590E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32066215.20 | 0.931310E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.129730E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145765E+10 |
February | 0.136988E+10 | 0.109493E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134422E+10 |
March | 0.163688E+10 | 0.123924E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108931E+10 |
April | 0.145246E+10 | 0.106331E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 489923.89 | 0.720049E+09 |
May | 0.157341E+10 | 0.112464E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1883821.00 | 0.416376E+09 |
June | 0.156904E+10 | 0.110588E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16406485.46 | 0.214463E+09 |
July | 0.145684E+10 | 0.103807E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38665299.81 | 78084128.56 |
August | 0.163688E+10 | 0.117310E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46284906.26 | 0.104118E+09 |
September | 0.145246E+10 | 0.108061E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5605253.76 | 0.245908E+09 |
October | 0.150994E+10 | 0.115780E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36101.74 | 0.616161E+09 |
November | 0.149520E+10 | 0.125173E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108475E+10 |
December | 0.145684E+10 | 0.126102E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128399E+10 |
Annual Sum or Average | 0.181198E+11 | 0.138876E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109372E+09 | 0.865509E+10 |
Minimum of Months | 0.136988E+10 | 0.103807E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78084128.56 |
Maximum of Months | 0.163688E+10 | 0.129730E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46284906.26 | 0.145765E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.847647E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.954622E+09 |
February | 0.882782E+09 | 0.712369E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.856448E+09 |
March | 0.105485E+10 | 0.798051E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.721219E+09 |
April | 0.936002E+09 | 0.684470E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 334072.99 | 0.485179E+09 |
May | 0.101394E+10 | 0.719295E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1815082.33 | 0.288023E+09 |
June | 0.101113E+10 | 0.707106E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11054893.67 | 0.157607E+09 |
July | 0.938820E+09 | 0.664866E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26123647.99 | 63141079.03 |
August | 0.105485E+10 | 0.752039E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31046303.15 | 76851184.06 |
September | 0.936002E+09 | 0.697756E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3954706.67 | 0.159261E+09 |
October | 0.973041E+09 | 0.749396E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51936.70 | 0.388735E+09 |
November | 0.963541E+09 | 0.812852E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.686462E+09 |
December | 0.938820E+09 | 0.832784E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.825385E+09 |
Annual Sum or Average | 0.116768E+11 | 0.897863E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74380643.49 | 0.566293E+10 |
Minimum of Months | 0.882782E+09 | 0.664866E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63141079.03 |
Maximum of Months | 0.105485E+10 | 0.847647E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31046303.15 | 0.954622E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.136314E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165702E+10 |
February | 0.136985E+10 | 0.113672E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146728E+10 |
March | 0.163685E+10 | 0.125564E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118022E+10 |
April | 0.145243E+10 | 0.106175E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 578734.60 | 0.778225E+09 |
May | 0.157338E+10 | 0.111891E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2769124.75 | 0.485176E+09 |
June | 0.156900E+10 | 0.109705E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19661509.73 | 0.264964E+09 |
July | 0.145680E+10 | 0.103014E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46030153.93 | 98848829.59 |
August | 0.163685E+10 | 0.116783E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57587017.24 | 0.119596E+09 |
September | 0.145243E+10 | 0.108649E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6967984.61 | 0.259580E+09 |
October | 0.150991E+10 | 0.118033E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72382.68 | 0.612983E+09 |
November | 0.149516E+10 | 0.129704E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112627E+10 |
December | 0.145680E+10 | 0.135046E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136875E+10 |
Annual Sum or Average | 0.181194E+11 | 0.141455E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133667E+09 | 0.941891E+10 |
Minimum of Months | 0.136985E+10 | 0.103014E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98848829.59 |
Maximum of Months | 0.163685E+10 | 0.136314E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57587017.24 | 0.165702E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.862432E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110873E+10 |
February | 0.882782E+09 | 0.723050E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.992770E+09 |
March | 0.105485E+10 | 0.805934E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.805668E+09 |
April | 0.936002E+09 | 0.685298E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 383297.28 | 0.545091E+09 |
May | 0.101394E+10 | 0.726179E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1467704.77 | 0.330148E+09 |
June | 0.101113E+10 | 0.713490E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13301569.48 | 0.177307E+09 |
July | 0.938820E+09 | 0.669011E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31344395.53 | 65141167.19 |
August | 0.105485E+10 | 0.755729E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37948500.59 | 82888971.57 |
September | 0.936002E+09 | 0.698618E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4602488.54 | 0.183062E+09 |
October | 0.973041E+09 | 0.755980E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48230.68 | 0.430145E+09 |
November | 0.963541E+09 | 0.827121E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.768811E+09 |
December | 0.938820E+09 | 0.844048E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.921540E+09 |
Annual Sum or Average | 0.116768E+11 | 0.906689E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 89096186.88 | 0.641130E+10 |
Minimum of Months | 0.882782E+09 | 0.669011E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65141167.19 |
Maximum of Months | 0.105485E+10 | 0.862432E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37948500.59 | 0.110873E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.129705E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171896E+10 |
February | 0.136988E+10 | 0.109485E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156872E+10 |
March | 0.163688E+10 | 0.123890E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126730E+10 |
April | 0.145246E+10 | 0.106330E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 572577.74 | 0.832707E+09 |
May | 0.157341E+10 | 0.112456E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2224071.09 | 0.495109E+09 |
June | 0.156904E+10 | 0.110579E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19439470.75 | 0.265937E+09 |
July | 0.145684E+10 | 0.103797E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45626737.46 | 0.101231E+09 |
August | 0.163688E+10 | 0.117307E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55232552.02 | 0.130524E+09 |
September | 0.145246E+10 | 0.108058E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6717183.35 | 0.294582E+09 |
October | 0.150994E+10 | 0.115780E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31995.38 | 0.722647E+09 |
November | 0.149520E+10 | 0.125155E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122898E+10 |
December | 0.145684E+10 | 0.126102E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146876E+10 |
Annual Sum or Average | 0.181198E+11 | 0.138865E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129845E+09 | 0.100955E+11 |
Minimum of Months | 0.136988E+10 | 0.103797E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101231E+09 |
Maximum of Months | 0.163688E+10 | 0.129705E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55232552.02 | 0.171896E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.847530E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113219E+10 |
February | 0.882782E+09 | 0.712365E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101554E+10 |
March | 0.105485E+10 | 0.798038E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.848259E+09 |
April | 0.936002E+09 | 0.684506E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 395905.39 | 0.568880E+09 |
May | 0.101394E+10 | 0.719241E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2110213.47 | 0.345018E+09 |
June | 0.101113E+10 | 0.706992E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13131903.07 | 0.195199E+09 |
July | 0.938820E+09 | 0.664886E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31027258.87 | 80266693.18 |
August | 0.105485E+10 | 0.752039E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37159361.44 | 95752078.31 |
September | 0.936002E+09 | 0.697715E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4714678.70 | 0.191149E+09 |
October | 0.973041E+09 | 0.749396E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48302.45 | 0.453857E+09 |
November | 0.963541E+09 | 0.812813E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.788096E+09 |
December | 0.938820E+09 | 0.832616E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.956109E+09 |
Annual Sum or Average | 0.116768E+11 | 0.897814E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88587623.39 | 0.667032E+10 |
Minimum of Months | 0.882782E+09 | 0.664886E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80266693.18 |
Maximum of Months | 0.105485E+10 | 0.847530E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37159361.44 | 0.113219E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.522764E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.474186E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.563465E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.503289E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.543115E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.540489E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.505915E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.563465E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.503289E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.522764E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.516637E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.505915E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.626529E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.474186E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.563465E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146771E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128267E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105476E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289704.65 | 0.703218E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1921422.90 | 0.392611E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11332764.60 | 0.202647E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27592077.30 | 71908178.12 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33686743.65 | 92477726.01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3457497.81 | 0.223618E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4687.26 | 0.559604E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106933E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128784E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78284898.17 | 0.840839E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71908178.12 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33686743.65 | 0.146771E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237788E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215704E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178005E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 580084.73 | 0.118121E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4316614.03 | 0.681437E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23490072.54 | 0.344353E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58158171.78 | 0.109731E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65703246.05 | 0.152689E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6340569.12 | 0.375903E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11472.18 | 0.959069E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177971E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211780E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158600E+09 | 0.140169E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109731E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65703246.05 | 0.237788E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248499E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223991E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188051E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137385.92 | 0.125413E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1557658.18 | 0.771739E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18178773.56 | 0.412930E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45331212.57 | 0.146579E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59379693.74 | 0.180524E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5190705.94 | 0.419044E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101105E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179228E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212252E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129775E+09 | 0.147162E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146579E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59379693.74 | 0.248499E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 19402.09 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 19402.09 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 19402.09 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 19402.09 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 19402.09 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 19402.09 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 19402.09 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 19402.09 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 19402.09 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 19402.09 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 19402.09 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 19402.09 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 19402.09 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 19402.09 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2187.81 | 02-JAN-16:10 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1140.31 | 31-JAN-01:00 |
February | 2010.79 | 01-FEB-10:09 | 2187.81 | 01-FEB-16:49 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1145.36 | 05-FEB-07:53 |
March | 2010.79 | 01-MAR-10:09 | 1906.53 | 02-MAR-16:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 922.78 | 12-MAR-10:00 |
April | 2010.79 | 03-APR-09:09 | 1242.97 | 18-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.29 | 07-APR-13:00 | 713.01 | 11-APR-04:00 |
May | 2010.79 | 01-MAY-09:09 | 1242.97 | 08-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.35 | 29-MAY-12:00 | 422.17 | 03-MAY-04:00 |
June | 2010.79 | 01-JUN-09:09 | 1141.96 | 16-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.16 | 19-JUN-21:02 | 238.43 | 02-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 1141.96 | 05-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.02 | 09-JUL-13:46 | 115.11 | 11-JUL-05:00 |
August | 2010.79 | 01-AUG-09:09 | 1242.97 | 16-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.66 | 04-AUG-21:02 | 152.40 | 20-AUG-06:10 |
September | 2010.79 | 01-SEP-09:09 | 1524.25 | 27-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.65 | 14-SEP-14:00 | 225.08 | 17-SEP-10:00 |
October | 2010.79 | 02-OCT-09:09 | 1906.53 | 06-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.09 | 25-OCT-11:00 | 617.68 | 08-OCT-08:00 |
November | 2010.79 | 01-NOV-09:09 | 2187.81 | 06-NOV-16:19 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 949.16 | 23-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 01-DEC-16:10 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1235.00 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.11 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 122.66 | 1235.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-16:10 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 758.69 | 31-JAN-01:00 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 01-FEB-16:49 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 828.39 | 05-FEB-09:10 |
March | 1295.83 | 01-MAR-10:09 | 1228.64 | 02-MAR-16:49 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 690.63 | 12-MAR-10:00 |
April | 1295.83 | 03-APR-09:09 | 735.93 | 05-APR-15:39 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.86 | 07-APR-13:00 | 463.54 | 11-APR-04:00 |
May | 1295.83 | 01-MAY-09:09 | 801.02 | 19-MAY-15:00 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.16 | 29-MAY-12:20 | 278.78 | 03-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 735.93 | 29-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.68 | 19-JUN-21:02 | 155.66 | 02-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 670.83 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.89 | 09-JUL-13:44 | 74.65 | 11-JUL-05:00 |
August | 1295.83 | 01-AUG-09:09 | 735.93 | 16-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.71 | 04-AUG-21:02 | 102.47 | 20-AUG-06:10 |
September | 1295.83 | 01-SEP-09:09 | 801.02 | 22-SEP-15:50 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.10 | 14-SEP-14:00 | 147.49 | 17-SEP-10:00 |
October | 1295.83 | 02-OCT-09:09 | 1228.64 | 06-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 | 25-OCT-11:00 | 465.29 | 08-OCT-08:20 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 06-NOV-16:19 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 624.45 | 23-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-16:10 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 812.70 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.65 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 81.71 | 828.39 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2187.86 | 02-JAN-16:30 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1152.22 | 31-JAN-01:00 |
February | 2010.83 | 01-FEB-10:09 | 2187.86 | 01-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1176.92 | 05-FEB-10:00 |
March | 2010.83 | 01-MAR-10:09 | 1524.28 | 02-MAR-16:40 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1009.24 | 12-MAR-10:00 |
April | 2010.83 | 03-APR-09:09 | 1243.00 | 21-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.24 | 07-APR-13:00 | 709.99 | 11-APR-04:00 |
May | 2010.83 | 01-MAY-09:09 | 1243.00 | 08-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.82 | 29-MAY-11:52 | 418.96 | 03-MAY-04:00 |
June | 2010.83 | 01-JUN-09:09 | 1141.99 | 16-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.07 | 19-JUN-21:02 | 238.86 | 02-JUN-22:00 |
July | 2010.83 | 03-JUL-09:09 | 1141.99 | 05-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.91 | 09-JUL-13:44 | 111.73 | 02-JUL-18:30 |
August | 2010.83 | 01-AUG-09:09 | 1243.00 | 16-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.36 | 04-AUG-21:02 | 148.20 | 20-AUG-06:10 |
September | 2010.83 | 01-SEP-09:09 | 1524.28 | 27-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.60 | 14-SEP-14:00 | 218.64 | 17-SEP-10:00 |
October | 2010.83 | 02-OCT-09:09 | 1906.57 | 06-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.87 | 25-OCT-11:00 | 647.29 | 08-OCT-08:00 |
November | 2010.83 | 01-NOV-09:09 | 2187.86 | 06-NOV-16:40 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 945.45 | 23-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 2187.86 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1220.11 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1141.99 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.73 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 122.36 | 1220.11 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-16:30 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 790.64 | 31-JAN-01:00 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 01-FEB-16:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 803.19 | 05-FEB-07:53 |
March | 1295.83 | 01-MAR-10:09 | 1047.37 | 16-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 687.19 | 12-MAR-10:00 |
April | 1295.83 | 03-APR-09:09 | 982.28 | 14-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.86 | 07-APR-13:00 | 538.66 | 11-APR-04:00 |
May | 1295.83 | 01-MAY-09:09 | 801.02 | 04-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.71 | 29-MAY-12:00 | 311.36 | 03-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 801.02 | 16-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.79 | 19-JUN-21:02 | 186.27 | 02-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 801.02 | 24-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.34 | 09-JUL-13:44 | 110.58 | 02-JUL-17:50 |
August | 1295.83 | 01-AUG-09:09 | 801.02 | 16-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.10 | 04-AUG-21:02 | 115.59 | 20-AUG-06:10 |
September | 1295.83 | 01-SEP-09:09 | 982.28 | 21-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.10 | 14-SEP-14:00 | 164.13 | 17-SEP-10:00 |
October | 1295.83 | 02-OCT-09:09 | 1228.64 | 06-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 | 25-OCT-11:00 | 445.51 | 08-OCT-08:00 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 06-NOV-16:40 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 682.65 | 23-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 901.76 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 801.02 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.58 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 80.10 | 901.76 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2187.81 | 02-JAN-16:19 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2366.67 | 31-JAN-01:00 |
February | 2010.79 | 01-FEB-10:09 | 2187.81 | 01-FEB-16:49 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2421.10 | 06-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 1805.53 | 02-MAR-16:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1846.41 | 21-MAR-21:03 |
April | 2010.79 | 03-APR-09:09 | 1141.96 | 13-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.91 | 07-APR-13:00 | 1485.29 | 11-APR-04:00 |
May | 2010.79 | 01-MAY-09:09 | 1141.96 | 04-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.51 | 29-MAY-12:00 | 882.00 | 03-MAY-04:00 |
June | 2010.79 | 01-JUN-09:09 | 1141.96 | 16-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.02 | 19-JUN-21:02 | 526.59 | 02-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 1141.96 | 24-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.97 | 09-JUL-13:50 | 235.07 | 11-JUL-05:00 |
August | 2010.79 | 01-AUG-09:09 | 1242.97 | 16-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 300.72 | 12-AUG-19:00 | 343.16 | 20-AUG-06:00 |
September | 2010.79 | 01-SEP-09:09 | 1524.25 | 27-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.93 | 14-SEP-14:00 | 451.59 | 17-SEP-10:00 |
October | 2010.79 | 02-OCT-09:09 | 1906.53 | 06-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.73 | 25-OCT-11:00 | 1235.66 | 08-OCT-08:00 |
November | 2010.79 | 01-NOV-09:09 | 2187.81 | 06-NOV-16:19 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1934.75 | 23-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 01-DEC-16:10 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2408.39 | 31-DEC-21:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.07 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 300.72 | 2421.10 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1409.91 | 02-JAN-16:10 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1589.61 | 31-JAN-01:00 |
February | 1239.33 | 01-FEB-08:09 | 1409.91 | 01-FEB-16:49 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1671.91 | 05-FEB-09:10 |
March | 1239.33 | 01-MAR-08:09 | 1228.64 | 02-MAR-16:49 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1394.83 | 12-MAR-10:00 |
April | 1239.33 | 03-APR-07:10 | 735.93 | 05-APR-15:50 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.94 | 07-APR-13:00 | 992.19 | 11-APR-04:00 |
May | 1239.33 | 01-MAY-07:10 | 735.93 | 04-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.68 | 29-MAY-11:55 | 592.26 | 03-MAY-04:00 |
June | 1239.33 | 01-JUN-07:10 | 735.93 | 29-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.69 | 19-JUN-21:02 | 349.47 | 02-JUN-22:00 |
July | 1239.33 | 03-JUL-07:10 | 670.83 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.42 | 09-JUL-13:44 | 161.88 | 02-JUL-19:00 |
August | 1239.33 | 01-AUG-07:10 | 735.93 | 16-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.05 | 12-AUG-18:55 | 242.66 | 20-AUG-06:00 |
September | 1239.33 | 01-SEP-07:10 | 801.02 | 22-SEP-15:50 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.28 | 14-SEP-14:00 | 331.50 | 10-SEP-07:50 |
October | 1239.33 | 02-OCT-07:10 | 1228.64 | 31-OCT-15:50 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.48 | 25-OCT-11:00 | 970.91 | 08-OCT-08:30 |
November | 1239.33 | 01-NOV-07:10 | 1409.91 | 06-NOV-16:19 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1301.76 | 23-NOV-02:00 |
December | 1239.33 | 01-DEC-08:09 | 1409.91 | 01-DEC-16:10 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1604.15 | 31-DEC-21:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.88 | |||||
Maximum of Months | 1239.33 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 219.05 | 1671.91 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2187.86 | 02-JAN-16:30 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2518.04 | 31-JAN-01:00 |
February | 2010.83 | 01-FEB-10:09 | 2187.86 | 01-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2588.19 | 05-FEB-12:10 |
March | 2010.83 | 01-MAR-10:09 | 1524.28 | 02-MAR-16:40 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2122.39 | 12-MAR-10:00 |
April | 2010.83 | 03-APR-09:09 | 1141.99 | 14-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.85 | 07-APR-13:00 | 1529.98 | 11-APR-04:00 |
May | 2010.83 | 01-MAY-09:09 | 1141.99 | 04-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.58 | 29-MAY-11:53 | 905.70 | 03-MAY-04:00 |
June | 2010.83 | 01-JUN-09:09 | 1141.99 | 16-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.54 | 19-JUN-21:02 | 529.58 | 02-JUN-22:00 |
July | 2010.83 | 03-JUL-09:09 | 1141.99 | 05-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.71 | 09-JUL-13:44 | 243.81 | 02-JUL-19:00 |
August | 2010.83 | 01-AUG-09:09 | 1243.00 | 16-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 298.48 | 12-AUG-19:00 | 356.21 | 20-AUG-06:00 |
September | 2010.83 | 01-SEP-09:09 | 1524.28 | 27-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.83 | 14-SEP-14:00 | 493.40 | 30-SEP-24:00 |
October | 2010.83 | 02-OCT-09:09 | 1906.57 | 06-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.44 | 25-OCT-11:00 | 1410.74 | 08-OCT-09:50 |
November | 2010.83 | 01-NOV-09:09 | 2187.86 | 06-NOV-16:40 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2030.56 | 23-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 2187.86 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2563.51 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1141.99 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.81 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 298.48 | 2588.19 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-16:30 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1621.12 | 31-JAN-01:00 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 01-FEB-16:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1614.09 | 06-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 982.28 | 06-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1263.78 | 21-MAR-21:10 |
April | 1295.83 | 03-APR-09:09 | 801.02 | 14-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.94 | 07-APR-13:00 | 1043.69 | 11-APR-04:00 |
May | 1295.83 | 01-MAY-09:09 | 801.02 | 04-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.23 | 29-MAY-12:00 | 629.13 | 03-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 801.02 | 29-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.67 | 19-JUN-21:02 | 416.69 | 03-JUN-17:40 |
July | 1295.83 | 03-JUL-09:09 | 801.02 | 24-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.68 | 09-JUL-14:00 | 249.90 | 02-JUL-17:40 |
August | 1295.83 | 01-AUG-09:09 | 801.02 | 16-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 192.13 | 12-AUG-19:00 | 256.31 | 20-AUG-06:00 |
September | 1295.83 | 01-SEP-09:09 | 982.28 | 21-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.29 | 14-SEP-14:00 | 326.06 | 30-SEP-24:00 |
October | 1295.83 | 02-OCT-09:09 | 1228.64 | 06-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.49 | 25-OCT-11:00 | 857.84 | 17-OCT-24:00 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 06-NOV-16:40 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1320.07 | 23-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1644.15 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 801.02 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.90 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 192.13 | 1644.15 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2187.81 | 02-JAN-16:19 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2923.24 | 14-JAN-06:00 |
February | 2010.79 | 01-FEB-10:09 | 2187.81 | 01-FEB-16:49 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3017.44 | 06-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 1805.53 | 02-MAR-16:00 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2286.77 | 21-MAR-21:03 |
April | 2010.79 | 03-APR-09:09 | 1141.96 | 13-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.57 | 07-APR-13:00 | 1720.06 | 11-APR-04:00 |
May | 2010.79 | 01-MAY-09:09 | 1141.96 | 04-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.05 | 29-MAY-12:10 | 1016.71 | 03-MAY-04:00 |
June | 2010.79 | 01-JUN-09:09 | 1141.96 | 16-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 248.05 | 19-JUN-21:02 | 638.64 | 02-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 1141.96 | 24-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 273.73 | 09-JUL-13:56 | 329.42 | 02-JUL-19:00 |
August | 2010.79 | 01-AUG-09:09 | 1242.97 | 16-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 352.19 | 04-AUG-21:02 | 403.23 | 20-AUG-06:00 |
September | 2010.79 | 01-SEP-09:09 | 1524.25 | 27-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.57 | 14-SEP-14:00 | 522.21 | 23-SEP-04:00 |
October | 2010.79 | 02-OCT-09:09 | 1906.53 | 06-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.87 | 25-OCT-11:00 | 1414.35 | 17-OCT-24:00 |
November | 2010.79 | 01-NOV-09:09 | 2187.81 | 06-NOV-16:19 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2231.29 | 22-NOV-22:03 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 01-DEC-16:10 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3001.91 | 31-DEC-21:57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.42 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 352.19 | 3017.44 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-16:10 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1948.91 | 14-JAN-06:00 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 01-FEB-16:49 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2011.63 | 06-FEB-00:57 |
March | 1295.83 | 01-MAR-10:09 | 1228.64 | 02-MAR-16:49 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1529.20 | 21-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 735.93 | 05-APR-15:50 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.90 | 07-APR-13:20 | 1151.28 | 11-APR-04:00 |
May | 1295.83 | 01-MAY-09:09 | 735.93 | 04-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.31 | 29-MAY-12:06 | 685.60 | 03-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 735.93 | 29-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.47 | 19-JUN-21:02 | 425.60 | 02-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 670.83 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.85 | 09-JUL-13:56 | 231.06 | 02-JUL-19:00 |
August | 1295.83 | 01-AUG-09:09 | 735.93 | 16-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 249.57 | 12-AUG-18:53 | 286.02 | 20-AUG-06:00 |
September | 1295.83 | 01-SEP-09:09 | 801.02 | 22-SEP-15:50 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.05 | 14-SEP-14:00 | 406.00 | 10-SEP-07:50 |
October | 1295.83 | 02-OCT-09:09 | 1228.64 | 31-OCT-15:50 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.24 | 25-OCT-11:00 | 1053.22 | 08-OCT-08:30 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 06-NOV-16:19 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1489.39 | 22-NOV-22:03 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-16:10 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2001.24 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.06 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 249.57 | 2011.63 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2187.86 | 02-JAN-16:30 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2923.32 | 14-JAN-05:58 |
February | 2010.83 | 01-FEB-10:09 | 2187.86 | 01-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3017.49 | 06-FEB-01:00 |
March | 2010.83 | 01-MAR-10:09 | 1524.28 | 02-MAR-16:40 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2323.86 | 12-MAR-10:00 |
April | 2010.83 | 03-APR-09:09 | 1141.99 | 14-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.47 | 07-APR-13:00 | 1777.51 | 11-APR-04:00 |
May | 2010.83 | 01-MAY-09:09 | 1141.99 | 04-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.22 | 29-MAY-12:04 | 1047.72 | 03-MAY-04:00 |
June | 2010.83 | 01-JUN-09:09 | 1141.99 | 16-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 247.42 | 19-JUN-21:02 | 642.13 | 02-JUN-22:00 |
July | 2010.83 | 03-JUL-09:09 | 1141.99 | 05-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 276.29 | 09-JUL-13:56 | 341.27 | 02-JUL-19:00 |
August | 2010.83 | 01-AUG-09:09 | 1243.00 | 16-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 350.63 | 04-AUG-21:02 | 419.68 | 20-AUG-06:00 |
September | 2010.83 | 01-SEP-09:09 | 1524.28 | 27-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.43 | 14-SEP-14:00 | 585.14 | 10-SEP-19:53 |
October | 2010.83 | 02-OCT-09:09 | 1906.57 | 06-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.45 | 25-OCT-11:00 | 1545.89 | 08-OCT-09:50 |
November | 2010.83 | 01-NOV-09:09 | 2187.86 | 06-NOV-16:40 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2293.99 | 23-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 2187.86 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3005.59 | 31-DEC-21:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1141.99 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.27 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 350.63 | 3017.49 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-16:30 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1948.85 | 14-JAN-05:54 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 01-FEB-16:00 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2011.71 | 06-FEB-00:53 |
March | 1295.83 | 01-MAR-10:09 | 982.28 | 06-MAR-08:09 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1543.44 | 21-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 801.02 | 14-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.04 | 07-APR-13:20 | 1219.30 | 11-APR-04:00 |
May | 1295.83 | 01-MAY-09:09 | 801.02 | 04-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.12 | 29-MAY-12:10 | 735.10 | 03-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 801.02 | 29-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.75 | 19-JUN-21:02 | 523.16 | 03-JUN-17:40 |
July | 1295.83 | 03-JUL-09:09 | 801.02 | 24-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.50 | 09-JUL-13:54 | 329.11 | 02-JUL-17:40 |
August | 1295.83 | 01-AUG-09:09 | 801.02 | 16-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 231.86 | 04-AUG-21:02 | 303.05 | 20-AUG-06:00 |
September | 1295.83 | 01-SEP-09:09 | 982.28 | 21-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.05 | 14-SEP-14:00 | 415.52 | 10-SEP-19:53 |
October | 1295.83 | 02-OCT-09:09 | 1228.64 | 06-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.25 | 25-OCT-11:00 | 1001.65 | 17-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 06-NOV-16:40 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1509.25 | 23-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2003.22 | 31-DEC-21:55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 801.02 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.05 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 231.86 | 2011.71 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 5470.56 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 5470.56 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 5470.56 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 5470.56 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 5470.56 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 5470.56 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 5470.56 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 5470.56 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 5470.56 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 5470.56 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 5470.56 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 5470.56 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 5470.56 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2516.03 | 31-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2526.70 | 06-FEB-00:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1889.43 | 12-MAR-10:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.39 | 07-APR-13:00 | 1534.25 | 11-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.37 | 29-MAY-12:00 | 906.92 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.11 | 19-JUN-21:02 | 492.56 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.30 | 09-JUL-14:00 | 227.14 | 11-JUL-05:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.98 | 12-AUG-18:53 | 334.33 | 20-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.48 | 14-SEP-14:00 | 448.69 | 23-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.91 | 25-OCT-11:00 | 1320.59 | 08-OCT-08:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2095.17 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2706.40 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.14 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.98 | 2706.40 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4265.09 | 31-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4240.35 | 05-FEB-07:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3100.47 | 21-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.41 | 07-APR-13:00 | 2649.99 | 11-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.51 | 29-MAY-12:00 | 1557.90 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.25 | 19-JUN-21:02 | 870.64 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.10 | 09-JUL-14:00 | 376.36 | 11-JUL-05:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 449.64 | 12-AUG-19:00 | 578.08 | 20-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.08 | 14-SEP-14:00 | 773.28 | 23-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.57 | 25-OCT-11:00 | 2263.76 | 08-OCT-07:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3558.72 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4387.90 | 31-DEC-21:53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 376.36 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 449.64 | 4387.90 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 4322.40 | 31-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4202.86 | 06-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3485.15 | 21-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.72 | 08-APR-10:00 | 2741.93 | 11-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.30 | 29-MAY-11:52 | 1631.03 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.42 | 19-JUN-21:02 | 918.03 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.59 | 07-JUL-21:53 | 500.87 | 02-JUL-18:22 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.73 | 12-AUG-18:53 | 584.99 | 20-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.17 | 14-SEP-14:00 | 811.61 | 23-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2267.50 | 17-OCT-24:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3512.33 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4283.65 | 31-DEC-22:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 500.87 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.73 | 4322.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 103411.88 | 24-JAN-07:12 | 21542.70 | 38804.17 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 104700.61 | 21-FEB-07:05 | 7180.90 | 12934.72 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 106683.22 | 28-MAR-06:11 | 25133.15 | 45271.53 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 110840.93 | 17-APR-06:11 | 28723.60 | 51738.90 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 112765.94 | 30-MAY-19:51 | 16157.03 | 38803.45 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 116370.65 | 09-JUN-06:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 122082.58 | 11-JUL-06:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 125977.30 | 23-AUG-06:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 125347.79 | 15-SEP-06:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 115522.71 | 02-OCT-06:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 112514.93 | 13-NOV-07:05 | 7180.90 | 12934.72 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 107069.99 | 26-DEC-07:05 | 7180.90 | 12934.72 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 103411.88 | 7180.90 | 12934.72 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 125977.30 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 81283.94 | 20-JAN-06:03 | 6448.95 | 2149.44 | 30589.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 87978.97 | 21-FEB-05:11 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 89967.67 | 06-MAR-05:11 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 91231.83 | 27-APR-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 98080.34 | 31-MAY-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 97523.83 | 12-JUN-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 95460.91 | 01-JUL-04:13 | 0.00 | 3224.16 | 26719.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 93792.88 | 14-AUG-04:24 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 97473.41 | 09-SEP-04:13 | 0.00 | 3224.16 | 26719.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 95848.31 | 10-OCT-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 98808.05 | 13-NOV-05:11 | 0.00 | 4298.88 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 90513.04 | 26-DEC-05:11 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 81283.94 | 0.00 | 2149.44 | 26719.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 98808.05 | 6448.95 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 26583.14 | 25-JAN-14:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 33194.02 | 08-FEB-09:40 | 30632.53 | 34848.87 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 73743.98 | 29-MAR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 80490.93 | 28-APR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 82662.08 | 31-MAY-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 84151.49 | 12-JUN-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 82061.43 | 24-JUL-05:04 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 86245.97 | 07-AUG-04:14 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 83933.63 | 18-SEP-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 81566.22 | 06-OCT-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 76155.44 | 04-NOV-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 28557.26 | 21-DEC-16:30 | 30632.53 | 34848.87 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 26583.14 | 0.00 | 2686.80 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 86245.97 | 30632.53 | 34848.87 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 19702.47 | 20-JAN-17:00 | 30632.53 | 34848.87 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 19743.50 | 17-FEB-17:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 33743.26 | 29-MAR-16:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 76789.87 | 08-APR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 82757.28 | 30-MAY-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 84631.02 | 12-JUN-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 83027.63 | 11-JUL-04:12 | 0.00 | 2149.44 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 88629.89 | 07-AUG-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 82743.84 | 06-SEP-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 78762.99 | 06-OCT-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 33266.61 | 03-NOV-16:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19386.27 | 20-DEC-17:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 19386.27 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 88629.89 | 30632.53 | 34848.87 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2730.33 | 24-JAN-06:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.25 |
February | 3175.89 | 20-FEB-12:43 | 404.87 | 231.31 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.65 |
March | 6440.50 | 27-MAR-13:30 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.22 |
April | 7775.23 | 26-APR-13:40 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.45 |
May | 13841.22 | 31-MAY-04:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17346.39 | 25-JUN-14:31 | 708.51 | 404.79 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.16 |
July | 18038.26 | 09-JUL-14:21 | 809.73 | 462.61 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 30.76 | 0.00 |
August | 17279.48 | 13-AUG-15:01 | 708.51 | 404.79 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 39.53 | 0.00 |
September | 17003.94 | 04-SEP-12:11 | 809.73 | 462.61 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.09 |
October | 7397.97 | 04-OCT-13:04 | 10053.95 | 5204.80 | 10802.76 | 0.00 | 0.00 | 0.00 | 0.00 | 3.62 | 0.00 |
November | 5142.40 | 03-NOV-13:30 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.57 |
December | 3373.99 | 26-DEC-13:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2730.33 | 0.00 | 231.31 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18038.26 | 10053.95 | 5204.80 | 10802.76 | 0.00 | 0.00 | 0.00 | 0.00 | 39.53 | 181.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4680.21 | 19-JAN-09:40 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.60 |
February | 6157.52 | 22-FEB-09:05 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.81 |
March | 9741.73 | 29-MAR-08:35 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.75 |
April | 22074.57 | 16-APR-08:52 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.67 |
May | 22365.95 | 29-MAY-08:12 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.61 |
June | 24757.76 | 25-JUN-08:31 | 521.82 | 298.13 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.80 |
July | 24341.10 | 09-JUL-08:21 | 521.82 | 298.13 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.86 |
August | 21750.87 | 27-AUG-08:52 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.01 |
September | 24988.19 | 04-SEP-08:51 | 521.82 | 298.13 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.66 |
October | 18749.76 | 15-OCT-09:13 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.99 |
November | 6905.11 | 02-NOV-08:50 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.74 |
December | 5125.67 | 20-DEC-09:30 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4680.21 | 260.91 | 149.06 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.86 | |
Maximum of Months | 24988.19 | 2478.65 | 1341.67 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15641.79 | 17-JAN-13:10 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.42 |
February | 25011.30 | 20-FEB-12:43 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.44 |
March | 18845.06 | 01-MAR-13:15 | 3846.30 | 2081.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.95 |
April | 24681.79 | 16-APR-12:13 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.29 |
May | 19957.42 | 29-MAY-12:13 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 28.81 | 0.00 |
June | 25140.58 | 25-JUN-13:52 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.05 |
July | 26704.38 | 09-JUL-13:41 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 57.46 | 0.00 |
August | 26675.40 | 27-AUG-12:12 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
September | 28855.59 | 04-SEP-12:11 | 809.75 | 462.62 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.00 |
October | 28075.11 | 15-OCT-11:51 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.42 |
November | 20085.68 | 02-NOV-12:40 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.24 |
December | 27025.08 | 17-DEC-12:52 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15641.79 | 404.87 | 231.31 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28855.59 | 3846.30 | 2081.97 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 57.46 | 228.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6971.71 | 20-JAN-15:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.08 |
February | 15599.21 | 20-FEB-15:23 | 260.91 | 149.06 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.12 |
March | 18739.66 | 26-MAR-16:32 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.30 |
April | 27806.51 | 09-APR-16:11 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.50 |
May | 27430.59 | 14-MAY-15:12 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.12 |
June | 29237.94 | 04-JUN-16:01 | 521.82 | 298.13 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.47 |
July | 30854.40 | 04-JUL-16:21 | 652.28 | 372.66 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.10 |
August | 27846.87 | 13-AUG-15:41 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 16.11 | 0.00 |
September | 28047.26 | 03-SEP-15:51 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.47 |
October | 27308.04 | 15-OCT-14:32 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.19 |
November | 13625.03 | 04-NOV-05:02 | 652.28 | 217.40 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.54 |
December | 16723.72 | 17-DEC-14:53 | 260.91 | 149.06 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6971.71 | 260.91 | 149.06 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30854.40 | 1239.33 | 670.83 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 16.11 | 186.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1913.73 | 20-JAN-17:05 | 1214.60 | 2430.88 | 2400.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.26 |
February | 2194.33 | 23-FEB-16:30 | 1923.11 | 1524.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.43 |
March | 3285.84 | 28-MAR-14:00 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.04 |
April | 5876.43 | 07-APR-14:00 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 26.72 | 0.00 |
May | 11726.74 | 30-MAY-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.60 |
June | 12887.77 | 22-JUN-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.78 |
July | 16371.91 | 09-JUL-14:21 | 809.73 | 462.61 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 89.70 | 0.00 |
August | 12543.21 | 13-AUG-15:41 | 708.51 | 404.79 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 96.72 | 0.00 |
September | 12188.63 | 02-SEP-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.46 |
October | 6117.05 | 05-OCT-14:00 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.92 |
November | 3031.66 | 02-NOV-14:20 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.91 |
December | 1961.03 | 21-DEC-13:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1913.73 | 708.51 | 269.88 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16371.91 | 2010.79 | 2430.88 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 96.72 | 190.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2541.93 | 27-JAN-09:55 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.96 |
February | 4369.62 | 08-FEB-09:40 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.23 |
March | 8432.56 | 29-MAR-08:55 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.18 |
April | 19396.92 | 23-APR-08:53 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.19 |
May | 26700.06 | 29-MAY-08:31 | 587.05 | 335.39 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.67 |
June | 24297.95 | 04-JUN-08:32 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.80 |
July | 26303.61 | 02-JUL-07:41 | 521.82 | 298.13 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.21 |
August | 24243.26 | 20-AUG-09:42 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.27 |
September | 26042.40 | 04-SEP-09:01 | 521.82 | 298.13 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.73 |
October | 10138.91 | 03-OCT-09:00 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.73 |
November | 5113.28 | 02-NOV-09:00 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.71 |
December | 2662.79 | 20-DEC-09:30 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2541.93 | 260.91 | 149.06 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.73 | |
Maximum of Months | 26700.06 | 2478.65 | 1341.67 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 366.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15557.90 | 17-JAN-13:20 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.81 |
February | 24561.95 | 20-FEB-13:32 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 636.93 |
March | 19275.63 | 01-MAR-13:30 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.92 |
April | 17711.35 | 07-APR-12:30 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 23.59 | 0.00 |
May | 24790.34 | 29-MAY-13:52 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.90 |
June | 23511.19 | 25-JUN-12:43 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.53 |
July | 25667.30 | 09-JUL-13:41 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 139.18 | 0.00 |
August | 26560.74 | 27-AUG-12:22 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.95 |
September | 28609.90 | 04-SEP-11:41 | 809.75 | 462.62 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.92 |
October | 25463.47 | 15-OCT-12:12 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 433.09 |
November | 20336.19 | 02-NOV-13:10 | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.94 |
December | 24710.67 | 17-DEC-13:02 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 457.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15557.90 | 404.87 | 231.31 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28609.90 | 2010.83 | 1040.98 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 139.18 | 636.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3935.52 | 31-JAN-16:00 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6094.15 | 24-FEB-15:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.63 |
March | 10950.87 | 29-MAR-16:00 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.34 |
April | 23683.85 | 23-APR-16:31 | 587.05 | 335.39 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 643.36 |
May | 24680.05 | 21-MAY-15:52 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.03 |
June | 25421.08 | 18-JUN-16:31 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.62 |
July | 28230.18 | 02-JUL-16:21 | 652.28 | 372.66 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.89 |
August | 24739.80 | 13-AUG-15:41 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 41.67 | 0.00 |
September | 25751.37 | 03-SEP-16:01 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.02 |
October | 15324.84 | 15-OCT-14:52 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.29 |
November | 7087.83 | 03-NOV-15:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.06 |
December | 3808.80 | 08-DEC-15:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3808.80 | 326.14 | 186.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28230.18 | 1239.33 | 670.83 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 41.67 | 643.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1752.63 | 20-JAN-15:00 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.50 |
February | 1788.52 | 24-FEB-15:40 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.14 |
March | 3087.63 | 28-MAR-14:00 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.18 |
April | 6796.65 | 07-APR-13:20 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 35.50 | 0.00 |
May | 17215.05 | 29-MAY-14:42 | 506.08 | 289.13 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.26 |
June | 14211.28 | 26-JUN-04:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.54 |
July | 17965.13 | 09-JUL-15:12 | 607.30 | 346.96 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.72 | 0.00 |
August | 19192.46 | 13-AUG-15:31 | 1012.16 | 578.27 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 79.02 | 0.00 |
September | 13800.32 | 02-SEP-04:12 | 0.00 | 404.83 | 3355.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.50 |
October | 6442.01 | 04-OCT-13:40 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 0.00 |
November | 2902.97 | 02-NOV-13:40 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.82 |
December | 1732.51 | 20-DEC-14:10 | 2010.79 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1732.51 | 0.00 | 289.13 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19192.46 | 2010.79 | 1141.96 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 79.02 | 316.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2329.54 | 19-JAN-09:45 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.41 |
February | 2483.14 | 22-FEB-09:55 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.21 |
March | 7221.54 | 29-MAR-09:30 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.81 |
April | 11403.89 | 28-APR-08:50 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.80 |
May | 26565.37 | 29-MAY-08:61 | 521.82 | 298.13 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.55 |
June | 23988.72 | 25-JUN-08:42 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.46 |
July | 26607.92 | 02-JUL-07:41 | 521.82 | 298.13 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.46 |
August | 26150.47 | 13-AUG-09:31 | 521.82 | 298.13 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.43 |
September | 23883.92 | 04-SEP-09:12 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.39 |
October | 9969.18 | 15-OCT-09:23 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.38 |
November | 3697.99 | 02-NOV-09:40 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.68 |
December | 2344.86 | 20-DEC-10:10 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2329.54 | 260.91 | 149.06 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.43 | |
Maximum of Months | 26607.92 | 2478.65 | 1341.67 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.38 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14671.93 | 19-JAN-13:30 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.56 |
February | 15239.45 | 02-FEB-14:00 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.54 |
March | 19248.64 | 01-MAR-13:30 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.83 |
April | 20510.26 | 09-APR-13:43 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.45 |
May | 26290.39 | 29-MAY-12:42 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 20.64 | 0.00 |
June | 26163.83 | 25-JUN-12:43 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.79 |
July | 26464.55 | 30-JUL-12:32 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 |
August | 30092.20 | 13-AUG-13:31 | 809.75 | 462.62 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 62.14 | 0.00 |
September | 28502.75 | 04-SEP-13:12 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.55 |
October | 29842.33 | 15-OCT-12:41 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 717.99 |
November | 20920.30 | 02-NOV-13:10 | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.38 |
December | 26845.34 | 17-DEC-13:32 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 694.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14671.93 | 404.87 | 231.31 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30092.20 | 2010.83 | 1040.98 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 62.14 | 717.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3541.08 | 19-JAN-15:40 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.30 |
February | 5263.31 | 24-FEB-15:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.79 |
March | 10761.18 | 29-MAR-16:00 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.62 |
April | 27428.59 | 09-APR-16:21 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.25 |
May | 26440.49 | 28-MAY-15:01 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.33 |
June | 27050.93 | 18-JUN-16:31 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.03 |
July | 29929.32 | 02-JUL-16:21 | 652.28 | 372.66 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.57 |
August | 29667.19 | 13-AUG-15:31 | 652.28 | 372.66 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.97 | 0.00 |
September | 25987.58 | 10-SEP-15:52 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.48 |
October | 24678.34 | 15-OCT-16:02 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 340.17 |
November | 6734.40 | 03-NOV-15:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.34 |
December | 3106.22 | 17-DEC-14:12 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3106.22 | 326.14 | 186.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29929.32 | 1239.33 | 670.83 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.97 | 340.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6445.95 | 14-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 527.63 |
February | 6109.28 | 13-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.25 |
March | 5241.14 | 29-MAR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.24 |
April | 7307.61 | 10-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.81 |
May | 12137.53 | 30-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.84 |
June | 15717.57 | 26-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.04 |
July | 14889.01 | 10-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.51 | 0.00 |
August | 15674.05 | 07-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.50 |
September | 14719.27 | 05-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.02 |
October | 8331.66 | 16-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.43 |
November | 7442.82 | 13-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.12 |
December | 4386.37 | 20-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4386.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15717.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.51 | 527.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7499.14 | 14-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3150.38 |
February | 10175.19 | 06-FEB-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3204.56 |
March | 7623.86 | 17-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1849.84 |
April | 5323.49 | 11-APR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 511.51 |
May | 7726.30 | 30-MAY-13:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.64 | 0.00 |
June | 7756.53 | 20-JUN-14:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.64 | 0.00 |
July | 8510.68 | 11-JUL-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.55 | 0.00 |
August | 9472.38 | 14-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.31 |
September | 8877.96 | 01-SEP-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.76 | 0.00 |
October | 5344.57 | 07-OCT-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.20 |
November | 7859.57 | 24-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1190.73 |
December | 6880.58 | 02-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2512.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5323.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10175.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.76 | 3204.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 188.76 | 19-JAN-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 471.32 |
February | 1789.53 | 20-FEB-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 818.93 |
March | 7277.32 | 03-MAR-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.20 |
April | 14708.94 | 07-APR-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.61 | 0.00 |
May | 22746.85 | 30-MAY-13:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.41 | 0.00 |
June | 22158.87 | 19-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.21 | 0.00 |
July | 21102.90 | 07-JUL-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.44 | 0.00 |
August | 21089.85 | 22-AUG-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.35 | 0.00 |
September | 22078.54 | 01-SEP-14:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.99 | 0.00 |
October | 12864.38 | 04-OCT-13:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.63 |
November | 4696.92 | 03-NOV-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.18 |
December | 1605.96 | 17-DEC-14:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 698.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 188.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22746.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.21 | 818.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2092.50 | 20-JAN-16:30 | 222.14 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4214.38 | 14-FEB-17:00 | 222.14 | 450.11 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6969.47 | 31-MAR-24:00 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8310.47 | 23-APR-17:42 | 0.00 | 100.03 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3554.08 | 31-MAY-24:00 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5388.68 | 30-JUN-24:00 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7331.10 | 31-JUL-24:00 | 0.00 | 50.02 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8216.89 | 31-AUG-17:40 | 23.38 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3405.02 | 30-SEP-24:00 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5161.65 | 31-OCT-24:00 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5994.39 | 06-NOV-16:10 | 222.14 | 450.11 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7886.84 | 08-DEC-16:00 | 222.14 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2092.50 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8310.47 | 222.14 | 450.11 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1786.99 | 20-JAN-16:40 | 222.14 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3779.77 | 22-FEB-17:00 | 222.14 | 450.11 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6092.37 | 31-MAR-23:40 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7629.76 | 09-APR-17:36 | 0.00 | 125.04 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3348.60 | 31-MAY-24:00 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5042.59 | 30-JUN-24:00 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6962.95 | 31-JUL-24:00 | 0.00 | 50.02 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7857.91 | 31-AUG-17:30 | 23.38 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3074.09 | 30-SEP-23:30 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4436.91 | 31-OCT-24:00 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5608.60 | 03-NOV-16:00 | 222.14 | 450.11 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7266.93 | 08-DEC-16:10 | 222.14 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1786.99 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7857.91 | 222.14 | 450.11 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1694.31 | 20-JAN-16:40 | 222.14 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3672.13 | 22-FEB-17:00 | 222.14 | 450.11 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5761.74 | 29-MAR-17:20 | 23.38 | 150.04 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7692.37 | 09-APR-17:30 | 0.00 | 175.05 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3306.36 | 31-MAY-24:00 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4958.67 | 30-JUN-24:00 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6962.74 | 31-JUL-24:00 | 0.00 | 50.02 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7933.73 | 13-AUG-17:15 | 0.00 | 50.02 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2766.70 | 30-SEP-23:20 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4061.61 | 04-OCT-16:30 | 70.15 | 250.06 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5587.58 | 03-NOV-16:00 | 222.14 | 450.11 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7086.13 | 08-DEC-16:10 | 222.14 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1694.31 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7933.73 | 222.14 | 450.11 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 91973.58 | 20-JAN-17:00 | 9617.36 | 10941.12 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 183410.90 | 22-FEB-17:00 | 4808.68 | 5470.56 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358431.15 | 31-MAR-24:00 | 0.00 | 303.90 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 367990.25 | 10-APR-16:00 | 4808.68 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176594.23 | 31-MAY-24:00 | 0.00 | 303.90 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 268292.21 | 30-JUN-24:00 | 0.00 | 303.90 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 361181.03 | 31-JUL-23:55 | 0.00 | 607.79 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 396911.11 | 22-AUG-14:43 | 28852.07 | 32823.35 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 176495.20 | 30-SEP-24:00 | 0.00 | 303.90 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 268282.05 | 31-OCT-24:00 | 0.00 | 303.90 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 277134.97 | 06-NOV-17:00 | 4808.68 | 5470.56 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 368196.88 | 18-DEC-17:00 | 4808.68 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 91973.58 | 0.00 | 303.90 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 396911.11 | 28852.07 | 32823.35 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.165092E+13 | 1233783.43 | 19-JAN-16:00 | 0.294382E+12 | 1710520.23 | 02-JAN-05:10 |
February | 0.189674E+13 | 1336821.52 | 01-FEB-16:00 | 0.207076E+12 | 1182729.76 | 06-FEB-06:10 |
March | 0.245444E+13 | 1563668.62 | 27-MAR-15:00 | 0.702735E+11 | 546895.18 | 13-MAR-04:10 |
April | 0.265496E+13 | 1973168.07 | 07-APR-14:00 | 0.195850E+11 | 444700.47 | 03-APR-05:10 |
May | 0.174671E+13 | 1668565.03 | 30-MAY-10:00 | 0.170492E+10 | 229736.11 | 30-MAY-10:00 |
June | 0.238289E+13 | 1938722.47 | 01-JUN-15:30 | 0.269422E+10 | 181318.68 | 22-JUN-13:30 |
July | 0.297477E+13 | 1985843.27 | 11-JUL-15:20 | 0.733399E+09 | 90274.05 | 11-JUL-13:00 |
August | 0.344450E+13 | 2144607.52 | 22-AUG-14:09 | 0.293857E+10 | 276869.85 | 24-AUG-18:40 |
September | 0.181771E+13 | 1654365.83 | 01-SEP-15:20 | 51639446.97 | 24348.36 | 14-SEP-19:49 |
October | 0.210192E+13 | 1668131.85 | 25-OCT-10:00 | 0.300971E+10 | 142904.66 | 28-OCT-05:10 |
November | 0.233055E+13 | 1567251.64 | 03-NOV-14:09 | 0.720973E+11 | 630968.29 | 24-NOV-05:10 |
December | 0.277303E+13 | 1647351.14 | 15-DEC-16:30 | 0.163914E+12 | 666124.62 | 11-DEC-05:10 |
Annual Sum or Average | 0.282292E+14 | 0.838460E+12 | ||||
Minimum of Months | 0.165092E+13 | 1233783.43 | 51639446.97 | 24348.36 | ||
Maximum of Months | 0.344450E+13 | 2144607.52 | 0.294382E+12 | 1710520.23 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.275126E+12 | 0.408408E+11 | 0.766053E+12 | 0.213345E+12 | 0.168855E+12 | 0.132610E+11 | 0.00 | 0.886516E+10 | 0.669009E+09 | 0.117845E+12 | 0.585149E+10 | 0.402103E+11 | 0.00 |
February | 0.246028E+12 | 0.326002E+11 | 0.978954E+12 | 0.195334E+12 | 0.152639E+12 | 0.118556E+11 | 0.00 | 0.239906E+11 | 0.166277E+10 | 0.210997E+12 | 0.578820E+10 | 0.368913E+11 | 0.00 |
March | 0.289817E+12 | 0.302259E+11 | 0.141687E+13 | 0.226058E+12 | 0.181128E+12 | 0.164317E+11 | 0.00 | 0.450878E+11 | 0.572359E+10 | 0.196732E+12 | 0.394740E+10 | 0.424154E+11 | 0.00 |
April | 0.256280E+12 | 0.239031E+11 | 0.165903E+13 | 0.211501E+12 | 0.191741E+12 | 0.212400E+11 | 0.00 | 0.929742E+11 | 0.263247E+11 | 0.134058E+12 | 0.134031E+10 | 0.365703E+11 | 0.00 |
May | 0.275914E+12 | 0.212805E+11 | 0.774844E+12 | 0.219699E+12 | 0.217510E+12 | 0.383913E+11 | 0.00 | 0.695277E+11 | 0.443786E+11 | 0.483605E+11 | 0.382278E+09 | 0.364265E+11 | 0.00 |
June | 0.274222E+12 | 0.191138E+11 | 0.106252E+13 | 0.217935E+12 | 0.244812E+12 | 0.595074E+11 | 0.00 | 0.302116E+12 | 0.147722E+12 | 0.166971E+11 | 0.470035E+10 | 0.335506E+11 | 0.00 |
July | 0.256070E+12 | 0.202223E+11 | 0.139340E+13 | 0.213265E+12 | 0.260546E+12 | 0.738969E+11 | 0.00 | 0.525588E+12 | 0.194531E+12 | 1344725.55 | 0.695977E+10 | 0.302834E+11 | 0.00 |
August | 0.286802E+12 | 0.228706E+11 | 0.173200E+13 | 0.226058E+12 | 0.276640E+12 | 0.771369E+11 | 0.00 | 0.596522E+12 | 0.181742E+12 | 0.641536E+10 | 0.563432E+10 | 0.326811E+11 | 0.00 |
September | 0.257103E+12 | 0.267496E+11 | 0.740713E+12 | 0.211501E+12 | 0.218698E+12 | 0.496652E+11 | 0.00 | 0.155820E+12 | 0.108216E+12 | 0.158892E+11 | 0.276071E+10 | 0.305966E+11 | 0.00 |
October | 0.268799E+12 | 0.336583E+11 | 0.108340E+13 | 0.213342E+12 | 0.207963E+12 | 0.343178E+11 | 0.00 | 0.892514E+11 | 0.433608E+11 | 0.933315E+11 | 0.907138E+09 | 0.335899E+11 | 0.00 |
November | 0.270491E+12 | 0.379632E+11 | 0.135889E+13 | 0.205298E+12 | 0.177010E+12 | 0.142066E+11 | 0.00 | 0.416852E+11 | 0.616996E+10 | 0.180728E+12 | 0.266387E+10 | 0.354442E+11 | 0.00 |
December | 0.266719E+12 | 0.421400E+11 | 0.170972E+13 | 0.213269E+12 | 0.172815E+12 | 0.116778E+11 | 0.00 | 0.541688E+11 | 0.444861E+10 | 0.255036E+12 | 0.540484E+10 | 0.376357E+11 | 0.00 |
Annual Sum or Average | 0.322337E+13 | 0.351568E+12 | 0.146764E+14 | 0.256661E+13 | 0.247036E+13 | 0.421588E+12 | 0.00 | 0.200560E+13 | 0.764949E+12 | 0.127609E+13 | 0.463407E+11 | 0.426295E+12 | 0.00 |
Minimum of Months | 0.246028E+12 | 0.191138E+11 | 0.740713E+12 | 0.195334E+12 | 0.152639E+12 | 0.116778E+11 | 0.00 | 0.886516E+10 | 0.669009E+09 | 1344725.55 | 0.382278E+09 | 0.302834E+11 | 0.00 |
Maximum of Months | 0.289817E+12 | 0.421400E+11 | 0.173200E+13 | 0.226058E+12 | 0.276640E+12 | 0.771369E+11 | 0.00 | 0.596522E+12 | 0.194531E+12 | 0.255036E+12 | 0.695977E+10 | 0.424154E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.294382E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.207076E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.702735E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.195850E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.170492E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.269422E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.733399E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.293857E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 51639446.97 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.300971E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.720973E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.163914E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.838460E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 51639446.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.294382E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 325713.14 | 02-JAN-16:30 | 40855.88 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 233436.21 | 03-JAN-08:20 | 102407.65 | 02-JAN-06:19 | 26452.28 | 04-JAN-21:00 | 0.00 | 01-JAN-00:10 |
February | 325713.14 | 01-FEB-16:00 | 40855.88 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 233425.17 | 28-FEB-08:20 | 100503.57 | 02-FEB-15:09 | 26491.64 | 16-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 303000.80 | 02-MAR-16:00 | 40855.88 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 233424.13 | 16-MAR-07:19 | 149714.51 | 29-MAR-15:20 | 26750.15 | 27-MAR-15:00 | 0.00 | 01-MAR-00:10 |
April | 285420.03 | 21-APR-07:10 | 40855.88 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 233417.64 | 21-APR-07:19 | 211462.21 | 07-APR-14:00 | 32282.67 | 07-APR-14:20 | 0.00 | 01-APR-00:10 |
May | 285420.03 | 08-MAY-07:10 | 27558.46 | 01-MAY-18:49 | 423497.50 | 01-MAY-07:10 | 233417.64 | 08-MAY-07:19 | 288250.16 | 30-MAY-10:00 | 56315.62 | 30-MAY-11:50 | 0.00 | 01-MAY-00:10 |
June | 285218.02 | 29-JUN-07:10 | 27558.46 | 01-JUN-19:19 | 541788.89 | 01-JUN-07:10 | 233417.53 | 29-JUN-07:19 | 301533.08 | 01-JUN-15:09 | 60003.73 | 22-JUN-12:50 | 0.00 | 01-JUN-00:10 |
July | 284436.93 | 24-JUL-07:10 | 27558.46 | 01-JUL-19:30 | 660080.29 | 03-JUL-07:10 | 233417.11 | 24-JUL-07:19 | 291242.54 | 11-JUL-15:20 | 53634.12 | 11-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 287642.14 | 16-AUG-07:10 | 40855.88 | 16-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 233418.82 | 16-AUG-07:19 | 306094.32 | 08-AUG-14:30 | 61216.28 | 30-AUG-14:20 | 0.00 | 01-AUG-00:10 |
September | 297349.23 | 27-SEP-07:10 | 40855.88 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 233424.00 | 27-SEP-07:19 | 300948.91 | 01-SEP-15:20 | 56522.88 | 01-SEP-13:00 | 0.00 | 01-SEP-00:10 |
October | 314611.94 | 31-OCT-15:00 | 40855.88 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 233431.78 | 06-OCT-07:19 | 200495.97 | 05-OCT-15:50 | 62600.23 | 03-OCT-13:39 | 0.00 | 01-OCT-00:10 |
November | 325713.14 | 06-NOV-16:40 | 40855.88 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 233433.23 | 30-NOV-08:20 | 143581.18 | 03-NOV-14:39 | 26530.58 | 04-NOV-12:30 | 0.00 | 01-NOV-00:10 |
December | 325713.14 | 01-DEC-16:30 | 40855.88 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 233433.23 | 11-DEC-08:20 | 104412.99 | 21-DEC-14:39 | 26473.48 | 30-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 284436.93 | 27558.46 | 423497.50 | 233417.11 | 100503.57 | 26452.28 | 0.00 | |||||||
Maximum of Months | 325713.14 | 40855.88 | 778371.69 | 233436.21 | 306094.32 | 62600.23 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 9207.84 | 20-JAN-16:00 | 2012.78 | 25-JAN-11:20 | 77388.61 | 19-JAN-13:00 | 5613.48 | 02-JAN-07:10 | 53135.26 | 31-JAN-12:20 | 0.00 |
February | 15866.62 | 02-FEB-16:30 | 3808.58 | 22-FEB-15:00 | 100000.00 | 02-FEB-05:00 | 5613.48 | 01-FEB-07:10 | 53261.46 | 06-FEB-12:30 | 0.00 |
March | 145168.37 | 27-MAR-15:00 | 51960.93 | 27-MAR-15:00 | 100000.00 | 01-MAR-05:00 | 5613.48 | 01-MAR-07:10 | 52914.01 | 01-MAR-12:50 | 0.00 |
April | 340092.48 | 07-APR-14:00 | 70498.38 | 07-APR-12:39 | 100000.00 | 01-APR-04:19 | 5613.48 | 01-APR-06:10 | 51210.13 | 04-APR-11:20 | 0.00 |
May | 320346.46 | 30-MAY-13:20 | 91748.49 | 30-MAY-10:30 | 100000.00 | 20-MAY-16:19 | 5613.48 | 30-MAY-08:50 | 47702.88 | 01-MAY-11:00 | 0.00 |
June | 398185.99 | 01-JUN-15:30 | 91748.49 | 01-JUN-09:00 | 100000.00 | 04-JUN-06:30 | 5613.48 | 01-JUN-10:09 | 44517.00 | 01-JUN-11:00 | 0.00 |
July | 378434.24 | 07-JUL-12:20 | 91748.49 | 03-JUL-07:19 | 2241.21 | 11-JUL-17:30 | 5613.48 | 01-JUL-06:10 | 41426.89 | 03-JUL-11:00 | 0.00 |
August | 463471.92 | 24-AUG-16:49 | 91748.49 | 01-AUG-07:19 | 100000.00 | 20-AUG-13:39 | 5613.48 | 01-AUG-06:10 | 40260.81 | 31-AUG-11:00 | 0.00 |
September | 338179.97 | 01-SEP-13:00 | 91748.49 | 01-SEP-07:19 | 100000.00 | 10-SEP-15:39 | 5613.48 | 01-SEP-06:10 | 42475.49 | 29-SEP-11:30 | 0.00 |
October | 296689.50 | 25-OCT-10:00 | 91748.49 | 03-OCT-10:30 | 100000.00 | 07-OCT-16:10 | 5613.48 | 03-OCT-11:50 | 45760.08 | 31-OCT-11:39 | 0.00 |
November | 61491.28 | 03-NOV-13:00 | 49554.40 | 04-NOV-12:30 | 100000.00 | 01-NOV-04:30 | 5613.48 | 01-NOV-06:10 | 49085.03 | 30-NOV-12:20 | 0.00 |
December | 23492.50 | 21-DEC-15:20 | 3768.30 | 15-DEC-15:20 | 100000.00 | 01-DEC-05:30 | 5613.48 | 01-DEC-07:10 | 52074.98 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 9207.84 | 2012.78 | 2241.21 | 5613.48 | 40260.81 | 0.00 | |||||
Maximum of Months | 463471.92 | 91748.49 | 100000.00 | 5613.48 | 53261.46 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1233783.43 | 19-JAN-16:00 | 325713.14 | 423497.50 | 40855.88 | 233326.38 | 76181.71 | 3849.87 | 0.00 | 7742.73 | 850.47 |
February | 1336821.52 | 01-FEB-16:00 | 325713.14 | 541788.89 | 0.00 | 233323.41 | 75454.14 | 3850.05 | 0.00 | 11853.34 | 1221.86 |
March | 1563668.62 | 27-MAR-15:00 | 280450.63 | 660080.29 | 0.00 | 233302.19 | 126452.66 | 26750.15 | 0.00 | 145168.37 | 51960.93 |
April | 1973168.07 | 07-APR-14:00 | 280450.63 | 778371.69 | 0.00 | 233151.79 | 211462.21 | 29968.29 | 0.00 | 340092.48 | 70498.38 |
May | 1668565.03 | 30-MAY-10:00 | 280450.63 | 423497.50 | 0.00 | 233151.79 | 288250.16 | 52691.20 | 0.00 | 260583.09 | 91748.49 |
June | 1938722.47 | 01-JUN-15:30 | 280450.63 | 541788.89 | 0.00 | 233302.19 | 299149.40 | 55985.29 | 0.00 | 398185.99 | 91748.49 |
July | 1985843.27 | 11-JUL-15:20 | 280450.63 | 660080.29 | 0.00 | 233302.19 | 291242.54 | 52739.90 | 0.00 | 341148.14 | 91748.49 |
August | 2144607.52 | 22-AUG-14:09 | 280450.63 | 778371.69 | 0.00 | 233151.79 | 245878.82 | 53427.83 | 0.00 | 432665.13 | 91748.49 |
September | 1654365.83 | 01-SEP-15:20 | 280450.63 | 423497.50 | 0.00 | 233302.19 | 300948.91 | 38685.40 | 0.00 | 262924.73 | 77581.75 |
October | 1668131.85 | 25-OCT-10:00 | 280450.63 | 541788.89 | 0.00 | 233151.79 | 153383.33 | 27851.18 | 0.00 | 296689.50 | 91748.49 |
November | 1567251.64 | 03-NOV-14:09 | 280450.63 | 660080.29 | 0.00 | 233151.79 | 133438.02 | 26486.28 | 0.00 | 59346.38 | 49477.31 |
December | 1647351.14 | 15-DEC-16:30 | 325713.14 | 778371.69 | 40855.88 | 233323.41 | 86553.98 | 15125.81 | 0.00 | 23118.19 | 1875.02 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1233783.43 | 280450.63 | 423497.50 | 0.00 | 233151.79 | 75454.14 | 3849.87 | 0.00 | 7742.73 | 850.47 | |
Maximum of Months | 2144607.52 | 325713.14 | 778371.69 | 40855.88 | 233326.38 | 300948.91 | 55985.29 | 0.00 | 432665.13 | 91748.49 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 1710520.23 | 02-JAN-05:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 1182729.76 | 06-FEB-06:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 546895.18 | 13-MAR-04:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 444700.47 | 03-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 229736.11 | 30-MAY-10:00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 181318.68 | 22-JUN-13:30 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 90274.05 | 11-JUL-13:00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 276869.85 | 24-AUG-18:40 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 24348.36 | 14-SEP-19:49 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 142904.66 | 28-OCT-05:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 630968.29 | 24-NOV-05:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 666124.62 | 11-DEC-05:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 24348.36 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 1710520.23 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 49.50 | 25.89 | 25.33 | 25.90 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 48.17 | 26.02 | 23.17 | 26.02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 54.67 | 26.23 | 27.67 | 26.23 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 47.83 | 26.39 | 27.00 | 26.39 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 89.67 | 27.10 | 51.67 | 27.13 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 374.00 | 28.24 | 254.83 | 28.23 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 711.67 | 29.03 | 464.67 | 29.04 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 618.50 | 29.44 | 416.00 | 29.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 349.33 | 28.18 | 216.00 | 28.17 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 122.83 | 27.23 | 47.83 | 27.18 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 94.67 | 27.10 | 38.33 | 27.06 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 68.67 | 26.50 | 26.00 | 26.48 |
Annual Sum or Average | 0.00 | 0.00 | 2629.50 | 28.39 | 1618.50 | 28.44 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 47.83 | 25.89 | 23.17 | 25.90 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 711.67 | 29.44 | 464.67 | 29.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 25.81 | 0.00 | 25.81 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 25.77 | 0.17 | 25.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 25.94 | 0.17 | 25.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 26.02 | 0.00 | 26.02 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.59 | 0.00 | 25.59 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 16.17 | 25.86 | 0.33 | 25.84 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 26.02 | 0.17 | 26.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 19.40 | 1.33 | 19.57 | 0.00 | 19.57 | 0.00 | 19.57 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.33 | 19.40 | 1.33 | 19.57 | 0.00 | 19.57 | 0.00 | 19.57 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 19.40 | 1.33 | 19.57 | 0.00 | 19.57 | 0.00 | 19.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 18.71 | 0.83 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 |
February | 2.50 | 19.25 | 0.50 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
December | 0.50 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
Annual Sum or Average | 6.50 | 18.99 | 1.33 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 19.38 | 0.83 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
February | 0.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 26.62 | 1.33 | 26.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.17 | 26.90 | 8.83 | 27.12 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 26.67 | 3.67 | 26.92 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.61 | 0.00 | 25.61 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 19.41 | 0.00 | 19.41 | 28.00 | 26.70 | 13.83 | 26.96 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.43 | 0.00 | 19.43 | 15.17 | 26.90 | 8.83 | 27.12 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
February | 0.17 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.97 | 2.00 | 27.97 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.08 | 6.33 | 28.08 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.76 | 4.67 | 27.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.92 | 9.83 | 28.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.70 | 5.17 | 27.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 28.05 | 6.83 | 28.08 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.53 | 1.33 | 27.53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 19.37 | 0.00 | 19.37 | 38.83 | 27.83 | 36.17 | 27.93 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.38 | 0.00 | 19.38 | 10.83 | 28.08 | 9.83 | 28.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 18.97 | 0.00 | 18.97 | 0.33 | 24.60 | 0.33 | 25.73 |
February | 0.17 | 19.11 | 0.00 | 19.11 | 1.67 | 26.84 | 1.67 | 27.21 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.44 | 0.50 | 27.44 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.54 | 2.50 | 27.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.74 | 3.50 | 27.74 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.35 | 3.67 | 27.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 27.29 | 10.00 | 27.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 27.18 | 6.17 | 27.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.39 | 9.33 | 27.41 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.32 | 9.67 | 27.32 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.50 | 0.83 | 27.50 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.02 | 2.83 | 28.02 |
Annual Sum or Average | 0.33 | 19.04 | 0.00 | 19.04 | 61.00 | 27.33 | 51.00 | 27.47 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.60 | 0.33 | 25.73 |
Maximum of Months | 0.17 | 19.11 | 0.00 | 19.11 | 14.33 | 28.02 | 10.00 | 28.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.48 | 0.33 | 27.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.03 | 1.17 | 28.04 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.90 | 4.50 | 28.08 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.03 | 4.50 | 28.10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.43 | 5.00 | 27.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 27.52 | 12.67 | 27.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 27.35 | 8.50 | 27.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.86 | 3.83 | 28.09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.97 | 3.17 | 27.99 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.29 | 0.50 | 27.29 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.54 | 0.67 | 27.54 |
Annual Sum or Average | 0.00 | 0.00 | 94.33 | 27.58 | 44.83 | 27.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 28.03 | 12.67 | 28.10 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 16.50 | 17.00 | 5.67 | 17.07 | 0.00 | 17.07 | 0.00 | 17.07 |
February | 10.00 | 18.23 | 1.83 | 18.52 | 0.00 | 18.52 | 0.00 | 18.52 |
March | 0.67 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.36 | 1.17 | 27.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.00 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
December | 2.33 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
Annual Sum or Average | 30.50 | 17.70 | 7.50 | 17.75 | 1.33 | 18.08 | 1.33 | 18.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 16.50 | 19.35 | 5.67 | 19.35 | 1.17 | 27.36 | 1.17 | 27.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.50 | 16.69 | 1.00 | 16.60 | 0.00 | 16.60 | 0.00 | 16.60 |
February | 5.83 | 17.76 | 0.00 | 17.76 | 0.00 | 17.76 | 0.00 | 17.76 |
March | 0.67 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.78 | 1.50 | 27.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.14 | 6.50 | 28.14 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.94 | 3.83 | 27.94 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 28.09 | 9.17 | 28.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.03 | 5.33 | 28.03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.18 | 5.17 | 28.18 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.47 | 0.50 | 27.47 |
November | 1.00 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
December | 2.17 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
Annual Sum or Average | 20.17 | 17.49 | 1.00 | 17.40 | 32.00 | 23.82 | 32.00 | 25.41 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.60 | 0.00 | 16.60 |
Maximum of Months | 10.50 | 19.35 | 1.00 | 19.35 | 9.17 | 28.18 | 9.17 | 28.18 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.33 | 16.85 | 0.67 | 16.88 | 0.50 | 17.38 | 0.50 | 17.84 |
February | 3.50 | 18.51 | 0.00 | 18.51 | 1.67 | 21.46 | 1.67 | 22.97 |
March | 0.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.56 | 0.83 | 27.56 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.73 | 3.33 | 27.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.53 | 2.83 | 27.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.74 | 7.83 | 27.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.40 | 6.83 | 27.40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 26.73 | 13.17 | 26.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 26.31 | 16.67 | 26.31 |
November | 0.33 | 19.23 | 0.00 | 19.23 | 1.50 | 23.65 | 1.50 | 24.10 |
December | 1.17 | 19.35 | 0.00 | 19.35 | 2.33 | 25.18 | 2.33 | 26.35 |
Annual Sum or Average | 14.50 | 17.54 | 0.67 | 17.53 | 58.33 | 25.02 | 57.50 | 25.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.38 | 0.00 | 17.84 |
Maximum of Months | 9.33 | 19.42 | 0.67 | 19.42 | 16.67 | 27.74 | 16.67 | 27.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.83 | 16.55 | 1.50 | 16.40 | 0.00 | 16.40 | 0.00 | 16.40 |
February | 3.83 | 18.40 | 0.00 | 18.40 | 0.00 | 18.40 | 0.00 | 18.40 |
March | 0.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.08 | 1.33 | 28.10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.99 | 3.50 | 28.05 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.01 | 3.67 | 28.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 28.28 | 5.50 | 28.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.17 | 2.83 | 28.33 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.47 | 2.67 | 28.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 28.06 | 0.67 | 28.06 |
November | 0.50 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
December | 0.67 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
Annual Sum or Average | 15.00 | 17.26 | 1.50 | 17.10 | 31.00 | 24.32 | 20.17 | 25.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.40 | 0.00 | 16.40 |
Maximum of Months | 9.83 | 19.43 | 1.50 | 19.43 | 9.00 | 28.47 | 5.50 | 28.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 43.50 | 16.47 | 12.67 | 16.53 | 0.00 | 16.53 | 0.00 | 16.53 |
February | 36.00 | 16.92 | 11.83 | 17.08 | 0.00 | 17.08 | 0.00 | 17.08 |
March | 5.33 | 18.58 | 0.17 | 18.63 | 0.00 | 18.63 | 0.00 | 18.63 |
April | 1.00 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.33 | 27.29 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.39 | 4.67 | 27.42 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.57 | 1.67 | 27.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8.33 | 17.78 | 1.00 | 18.04 | 0.00 | 18.04 | 0.00 | 18.04 |
December | 13.67 | 17.66 | 2.50 | 17.57 | 0.00 | 17.57 | 0.00 | 17.57 |
Annual Sum or Average | 107.83 | 17.00 | 28.17 | 17.06 | 8.00 | 17.63 | 6.83 | 18.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 43.50 | 19.14 | 12.67 | 19.14 | 5.50 | 27.57 | 4.67 | 27.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 30.00 | 15.67 | 5.67 | 15.56 | 0.00 | 15.56 | 0.00 | 15.56 |
February | 19.33 | 16.12 | 1.33 | 16.08 | 0.00 | 16.08 | 0.00 | 16.08 |
March | 4.33 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 |
April | 0.67 | 19.15 | 0.00 | 19.15 | 0.17 | 20.77 | 0.17 | 21.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.12 | 6.83 | 28.12 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.91 | 4.67 | 27.91 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 28.06 | 11.67 | 28.07 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.07 | 6.00 | 28.08 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.10 | 5.50 | 28.10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5.50 | 17.33 | 0.00 | 17.33 | 0.00 | 17.33 | 0.00 | 17.33 |
December | 10.50 | 17.27 | 0.83 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 |
Annual Sum or Average | 70.33 | 16.36 | 7.83 | 16.23 | 35.50 | 19.92 | 34.83 | 21.83 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 30.00 | 19.15 | 5.67 | 19.15 | 12.00 | 28.12 | 11.67 | 28.12 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 24.00 | 16.13 | 3.17 | 16.06 | 0.00 | 16.06 | 0.00 | 16.06 |
February | 14.67 | 16.85 | 1.67 | 16.91 | 0.00 | 16.91 | 0.00 | 16.91 |
March | 3.67 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 |
April | 0.67 | 19.24 | 0.00 | 19.24 | 0.17 | 20.92 | 0.17 | 22.03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.81 | 3.83 | 27.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.63 | 3.67 | 27.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 27.86 | 8.83 | 27.88 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.16 | 5.33 | 28.20 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.35 | 8.83 | 27.35 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.01 | 7.83 | 27.01 |
November | 3.67 | 18.29 | 0.00 | 18.29 | 0.00 | 18.29 | 0.00 | 18.29 |
December | 7.83 | 17.88 | 0.50 | 17.70 | 1.33 | 19.06 | 1.33 | 20.09 |
Annual Sum or Average | 54.50 | 16.92 | 5.33 | 16.85 | 42.33 | 21.30 | 39.83 | 23.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.06 | 0.00 | 16.06 |
Maximum of Months | 24.00 | 19.24 | 3.17 | 19.24 | 9.83 | 28.16 | 8.83 | 28.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 19.50 | 16.04 | 3.50 | 15.87 | 0.00 | 15.87 | 0.00 | 15.87 |
February | 13.00 | 16.60 | 1.50 | 16.49 | 0.00 | 16.49 | 0.00 | 16.49 |
March | 3.17 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
April | 0.33 | 19.40 | 0.00 | 19.40 | 2.00 | 26.79 | 1.50 | 27.30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.00 | 4.00 | 28.08 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.25 | 3.50 | 28.34 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 28.37 | 6.17 | 28.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.20 | 3.67 | 28.22 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.47 | 2.83 | 28.53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.99 | 0.67 | 27.99 |
November | 3.17 | 18.19 | 0.00 | 18.19 | 0.00 | 18.19 | 0.00 | 18.19 |
December | 7.00 | 18.19 | 0.00 | 18.19 | 0.00 | 18.19 | 0.00 | 18.19 |
Annual Sum or Average | 46.17 | 16.89 | 5.00 | 16.72 | 34.17 | 21.33 | 22.33 | 22.79 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.87 | 0.00 | 15.87 |
Maximum of Months | 19.50 | 19.40 | 3.50 | 19.40 | 10.17 | 28.47 | 6.17 | 28.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.60 | 1.17 | 27.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.17 | 27.60 | 1.17 | 27.60 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.60 | 1.17 | 27.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.17 | 6.67 | 28.17 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 6.67 | 28.17 | 6.67 | 28.17 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.17 | 6.67 | 28.17 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 177.33 | 24.01 | 84.50 | 24.49 | 0.00 | 24.49 |
February | 215.50 | 24.01 | 71.50 | 24.54 | 0.00 | 24.54 |
March | 82.33 | 24.00 | 132.83 | 25.04 | 0.00 | 25.04 |
April | 22.50 | 24.00 | 194.33 | 25.33 | 0.00 | 25.33 |
May | 22.50 | 27.50 | 306.67 | 25.41 | 19.67 | 25.55 |
June | 238.50 | 28.30 | 462.17 | 27.19 | 238.50 | 27.47 |
July | 434.17 | 29.35 | 497.00 | 29.04 | 434.17 | 29.14 |
August | 390.00 | 29.75 | 512.00 | 29.07 | 390.00 | 29.28 |
September | 185.00 | 28.48 | 433.50 | 27.01 | 185.00 | 27.35 |
October | 35.67 | 25.69 | 364.00 | 25.17 | 23.67 | 25.24 |
November | 35.67 | 25.48 | 192.33 | 25.78 | 14.00 | 25.89 |
December | 87.33 | 24.00 | 123.67 | 25.38 | 0.00 | 25.38 |
Annual Sum or Average | 1926.50 | 27.43 | 3374.50 | 26.98 | 1305.00 | 27.39 |
Minimum of Months | 22.50 | 24.00 | 71.50 | 24.49 | 0.00 | 24.49 |
Maximum of Months | 434.17 | 29.75 | 512.00 | 29.07 | 434.17 | 29.28 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 349.00 | 23.80 | 32.33 | 23.84 | 12.00 | 23.84 |
February | 286.33 | 23.87 | 7.00 | 23.91 | 0.00 | 23.91 |
March | 106.17 | 23.95 | 88.67 | 24.50 | 0.00 | 24.50 |
April | 26.83 | 23.93 | 168.00 | 24.65 | 0.00 | 24.65 |
May | 7.83 | 23.92 | 265.50 | 24.43 | 0.00 | 24.43 |
June | 0.17 | 26.91 | 445.83 | 24.34 | 0.17 | 24.34 |
July | 0.00 | 0.00 | 497.00 | 24.40 | 0.00 | 24.40 |
August | 1.50 | 26.61 | 504.00 | 24.33 | 1.50 | 24.34 |
September | 0.83 | 27.16 | 408.83 | 24.45 | 0.83 | 24.46 |
October | 32.50 | 23.99 | 319.33 | 24.45 | 0.00 | 24.45 |
November | 54.67 | 23.95 | 127.00 | 24.91 | 0.00 | 24.91 |
December | 152.83 | 23.96 | 59.50 | 24.47 | 0.00 | 24.47 |
Annual Sum or Average | 1018.67 | 23.89 | 2923.00 | 24.35 | 14.50 | 24.35 |
Minimum of Months | 0.00 | 0.00 | 7.00 | 23.84 | 0.00 | 23.84 |
Maximum of Months | 349.00 | 27.16 | 504.00 | 24.91 | 12.00 | 24.91 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.17 | 22.31 | 51.17 | 22.08 | 51.17 | 21.89 |
February | 453.83 | 22.86 | 6.33 | 22.83 | 6.33 | 22.81 |
March | 427.33 | 23.46 | 7.67 | 23.47 | 0.00 | 23.47 |
April | 253.00 | 23.41 | 41.17 | 23.57 | 0.00 | 23.57 |
May | 93.33 | 23.66 | 184.83 | 24.07 | 0.00 | 24.07 |
June | 14.33 | 23.69 | 421.33 | 24.19 | 0.00 | 24.19 |
July | 0.00 | 0.00 | 492.83 | 24.20 | 0.00 | 24.20 |
August | 0.00 | 0.00 | 458.33 | 24.24 | 0.00 | 24.24 |
September | 33.50 | 23.57 | 337.17 | 24.20 | 0.00 | 24.20 |
October | 123.33 | 23.67 | 224.33 | 24.03 | 0.00 | 24.03 |
November | 329.50 | 23.29 | 44.67 | 23.45 | 0.00 | 23.45 |
December | 494.00 | 23.05 | 0.00 | 23.05 | 0.00 | 23.05 |
Annual Sum or Average | 2721.33 | 23.07 | 2269.83 | 23.55 | 57.50 | 23.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 22.08 | 0.00 | 21.89 |
Maximum of Months | 499.17 | 23.69 | 492.83 | 24.24 | 51.17 | 24.24 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.08 | 177.83 | 20.71 | 177.83 | 20.49 |
February | 454.00 | 21.38 | 160.83 | 21.08 | 160.83 | 20.91 |
March | 488.00 | 22.41 | 31.67 | 22.31 | 29.33 | 22.22 |
April | 346.33 | 22.68 | 43.00 | 22.74 | 11.33 | 22.67 |
May | 173.00 | 23.36 | 157.17 | 23.76 | 0.00 | 23.76 |
June | 14.00 | 23.58 | 414.33 | 24.19 | 0.00 | 24.19 |
July | 0.00 | 0.00 | 497.00 | 24.25 | 0.00 | 24.25 |
August | 0.00 | 0.00 | 458.00 | 24.26 | 0.00 | 24.26 |
September | 73.83 | 23.20 | 320.50 | 24.00 | 0.00 | 24.00 |
October | 264.33 | 22.92 | 161.17 | 23.33 | 4.50 | 23.31 |
November | 462.17 | 22.24 | 71.50 | 22.02 | 66.83 | 21.84 |
December | 497.00 | 21.41 | 138.67 | 21.09 | 138.67 | 20.88 |
Annual Sum or Average | 3274.67 | 22.03 | 2631.67 | 22.59 | 589.33 | 22.36 |
Minimum of Months | 0.00 | 0.00 | 31.67 | 20.71 | 0.00 | 20.49 |
Maximum of Months | 502.00 | 23.58 | 497.00 | 24.26 | 177.83 | 24.26 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.64 | 133.83 | 21.44 | 133.83 | 21.30 |
February | 454.00 | 21.84 | 100.33 | 21.66 | 100.33 | 21.54 |
March | 456.50 | 22.94 | 10.83 | 22.95 | 2.00 | 22.95 |
April | 270.83 | 23.35 | 74.67 | 23.56 | 0.00 | 23.56 |
May | 69.50 | 23.66 | 223.67 | 24.20 | 0.50 | 24.20 |
June | 12.17 | 26.49 | 455.17 | 24.44 | 11.17 | 24.49 |
July | 49.83 | 26.77 | 497.00 | 24.75 | 49.83 | 24.92 |
August | 21.17 | 26.78 | 501.33 | 24.49 | 21.17 | 24.57 |
September | 35.00 | 23.89 | 361.83 | 24.35 | 2.67 | 24.37 |
October | 184.50 | 23.45 | 230.83 | 23.86 | 0.00 | 23.86 |
November | 391.33 | 22.95 | 20.00 | 22.99 | 3.67 | 22.97 |
December | 496.50 | 22.47 | 7.17 | 22.45 | 7.17 | 22.43 |
Annual Sum or Average | 2943.33 | 22.68 | 2616.67 | 23.32 | 332.33 | 23.27 |
Minimum of Months | 12.17 | 21.64 | 7.17 | 21.44 | 0.00 | 21.30 |
Maximum of Months | 502.00 | 26.78 | 501.33 | 24.75 | 133.83 | 24.92 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 494.83 | 21.54 | 124.33 | 21.37 | 124.33 | 21.25 |
February | 438.83 | 21.88 | 77.67 | 21.76 | 74.17 | 21.64 |
March | 407.50 | 22.46 | 30.50 | 22.55 | 5.83 | 22.54 |
April | 272.33 | 22.84 | 119.50 | 23.35 | 7.50 | 23.42 |
May | 126.33 | 23.88 | 282.33 | 24.30 | 22.83 | 24.44 |
June | 22.83 | 26.54 | 465.17 | 24.44 | 20.67 | 24.54 |
July | 52.33 | 26.84 | 497.00 | 24.72 | 52.33 | 24.90 |
August | 22.00 | 26.87 | 499.83 | 24.44 | 21.50 | 24.54 |
September | 79.50 | 24.49 | 380.67 | 24.46 | 26.17 | 24.60 |
October | 174.50 | 23.17 | 227.67 | 23.81 | 5.17 | 23.84 |
November | 376.67 | 22.50 | 24.17 | 22.57 | 7.33 | 22.54 |
December | 482.67 | 22.00 | 19.17 | 21.98 | 17.17 | 21.94 |
Annual Sum or Average | 2950.33 | 22.48 | 2748.00 | 23.27 | 385.00 | 23.27 |
Minimum of Months | 22.00 | 21.54 | 19.17 | 21.37 | 5.17 | 21.25 |
Maximum of Months | 494.83 | 26.87 | 499.83 | 24.72 | 124.33 | 24.90 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.33 | 21.63 | 129.00 | 21.51 | 109.50 | 21.33 |
February | 349.17 | 22.06 | 100.00 | 22.10 | 71.17 | 21.94 |
March | 346.33 | 22.68 | 85.17 | 22.89 | 12.67 | 22.85 |
April | 242.67 | 23.02 | 126.33 | 23.54 | 6.83 | 23.60 |
May | 117.00 | 23.69 | 259.83 | 24.18 | 11.83 | 24.26 |
June | 20.00 | 26.18 | 464.83 | 24.43 | 15.83 | 24.51 |
July | 46.50 | 26.90 | 497.00 | 24.72 | 46.50 | 24.89 |
August | 30.17 | 26.95 | 501.67 | 24.56 | 30.17 | 24.69 |
September | 54.83 | 25.24 | 410.67 | 24.59 | 26.67 | 24.73 |
October | 120.50 | 24.06 | 331.00 | 24.39 | 23.00 | 24.52 |
November | 293.17 | 22.71 | 105.67 | 23.11 | 8.33 | 23.07 |
December | 386.50 | 22.30 | 60.50 | 22.48 | 27.67 | 22.47 |
Annual Sum or Average | 2434.17 | 22.72 | 3071.67 | 23.54 | 390.17 | 23.53 |
Minimum of Months | 20.00 | 21.63 | 60.50 | 21.51 | 6.83 | 21.33 |
Maximum of Months | 427.33 | 26.95 | 501.67 | 24.72 | 109.50 | 24.89 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 476.33 | 21.95 | 54.33 | 21.87 | 51.17 | 21.78 |
February | 397.33 | 22.48 | 25.17 | 22.52 | 14.17 | 22.48 |
March | 209.50 | 23.42 | 129.50 | 23.89 | 4.67 | 23.93 |
April | 62.33 | 24.54 | 273.33 | 24.72 | 18.17 | 24.84 |
May | 49.50 | 24.94 | 368.33 | 24.55 | 22.17 | 24.67 |
June | 36.33 | 26.98 | 482.17 | 24.67 | 36.33 | 24.83 |
July | 82.67 | 26.68 | 497.00 | 24.91 | 82.67 | 25.13 |
August | 79.00 | 26.15 | 514.00 | 24.71 | 79.00 | 24.88 |
September | 32.50 | 25.67 | 415.17 | 24.57 | 20.00 | 24.68 |
October | 69.83 | 24.09 | 333.67 | 24.46 | 11.33 | 24.53 |
November | 193.00 | 23.22 | 122.50 | 23.87 | 0.50 | 23.88 |
December | 318.83 | 23.37 | 36.00 | 23.62 | 0.33 | 23.62 |
Annual Sum or Average | 2007.17 | 23.30 | 3251.17 | 24.05 | 340.50 | 24.14 |
Minimum of Months | 32.50 | 21.95 | 25.17 | 21.87 | 0.33 | 21.78 |
Maximum of Months | 476.33 | 26.98 | 514.00 | 24.91 | 82.67 | 25.13 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.28 | 369.00 | 20.15 | 369.00 | 20.10 |
February | 454.00 | 20.48 | 357.33 | 20.38 | 357.33 | 20.35 |
March | 509.83 | 21.43 | 136.83 | 21.26 | 134.33 | 21.13 |
April | 404.33 | 22.22 | 42.17 | 22.24 | 19.17 | 22.16 |
May | 201.83 | 23.25 | 139.33 | 23.66 | 0.00 | 23.66 |
June | 24.17 | 24.79 | 431.00 | 24.30 | 13.67 | 24.34 |
July | 45.50 | 26.17 | 497.00 | 24.59 | 45.50 | 24.71 |
August | 25.33 | 25.85 | 470.00 | 24.42 | 22.17 | 24.49 |
September | 117.50 | 23.24 | 286.00 | 23.93 | 5.83 | 23.95 |
October | 325.67 | 22.54 | 119.33 | 22.83 | 14.00 | 22.76 |
November | 486.50 | 21.46 | 133.83 | 21.19 | 133.83 | 21.02 |
December | 497.00 | 20.56 | 348.33 | 20.46 | 348.33 | 20.41 |
Annual Sum or Average | 3593.67 | 21.50 | 3330.17 | 22.04 | 1463.17 | 21.78 |
Minimum of Months | 24.17 | 20.28 | 42.17 | 20.15 | 0.00 | 20.10 |
Maximum of Months | 509.83 | 26.17 | 497.00 | 24.59 | 369.00 | 24.71 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.25 | 298.50 | 20.08 | 298.50 | 20.00 |
February | 385.00 | 20.76 | 249.83 | 20.58 | 249.83 | 20.50 |
March | 402.00 | 21.51 | 91.67 | 21.35 | 87.00 | 21.22 |
April | 299.67 | 22.17 | 77.83 | 22.59 | 12.83 | 22.60 |
May | 197.17 | 23.30 | 170.00 | 23.94 | 22.17 | 24.12 |
June | 45.50 | 25.28 | 350.67 | 24.50 | 27.83 | 24.64 |
July | 62.17 | 26.63 | 418.33 | 24.83 | 62.17 | 25.04 |
August | 40.17 | 26.38 | 403.50 | 24.63 | 37.17 | 24.78 |
September | 125.67 | 23.57 | 256.33 | 24.20 | 24.83 | 24.35 |
October | 253.50 | 22.53 | 121.17 | 23.03 | 11.17 | 23.02 |
November | 394.00 | 21.40 | 104.00 | 21.18 | 101.83 | 21.03 |
December | 422.00 | 20.70 | 262.00 | 20.53 | 262.00 | 20.46 |
Annual Sum or Average | 3053.83 | 21.69 | 2803.83 | 22.28 | 1197.33 | 22.09 |
Minimum of Months | 40.17 | 20.25 | 77.83 | 20.08 | 11.17 | 20.00 |
Maximum of Months | 427.00 | 26.63 | 418.33 | 24.83 | 298.50 | 25.04 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 440.50 | 20.87 | 230.83 | 20.64 | 214.50 | 20.45 |
February | 366.33 | 21.48 | 184.83 | 21.39 | 157.83 | 21.19 |
March | 379.50 | 21.92 | 116.00 | 22.09 | 50.83 | 21.95 |
April | 313.67 | 22.34 | 107.17 | 22.80 | 13.83 | 22.78 |
May | 192.33 | 23.26 | 205.83 | 23.85 | 10.00 | 23.92 |
June | 41.00 | 24.93 | 437.67 | 24.36 | 21.83 | 24.44 |
July | 59.67 | 26.45 | 496.83 | 24.69 | 59.67 | 24.86 |
August | 40.33 | 26.48 | 486.33 | 24.59 | 37.83 | 24.73 |
September | 89.17 | 24.43 | 374.17 | 24.46 | 32.50 | 24.61 |
October | 177.50 | 23.62 | 300.83 | 24.18 | 30.33 | 24.34 |
November | 346.83 | 22.01 | 131.17 | 22.20 | 55.00 | 22.00 |
December | 416.83 | 21.52 | 192.67 | 21.42 | 167.50 | 21.26 |
Annual Sum or Average | 2863.67 | 22.17 | 3264.33 | 22.94 | 851.67 | 22.80 |
Minimum of Months | 40.33 | 20.87 | 107.17 | 20.64 | 10.00 | 20.45 |
Maximum of Months | 440.50 | 26.48 | 496.83 | 24.69 | 214.50 | 24.86 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.00 | 20.58 | 292.50 | 20.38 | 292.50 | 20.28 |
February | 441.83 | 20.90 | 253.83 | 20.72 | 253.83 | 20.63 |
March | 438.50 | 21.63 | 87.50 | 21.71 | 56.83 | 21.62 |
April | 343.00 | 22.22 | 94.50 | 22.63 | 12.50 | 22.65 |
May | 190.00 | 23.28 | 221.50 | 23.87 | 18.50 | 24.00 |
June | 39.83 | 25.57 | 450.67 | 24.47 | 27.83 | 24.59 |
July | 54.67 | 26.68 | 495.67 | 24.73 | 54.67 | 24.91 |
August | 34.50 | 26.69 | 496.00 | 24.59 | 34.17 | 24.72 |
September | 115.67 | 23.43 | 321.67 | 24.10 | 19.50 | 24.22 |
October | 245.17 | 22.54 | 188.67 | 23.24 | 4.67 | 23.25 |
November | 463.33 | 21.50 | 103.67 | 21.33 | 98.33 | 21.20 |
December | 495.50 | 20.95 | 248.67 | 20.79 | 248.67 | 20.71 |
Annual Sum or Average | 3361.00 | 21.72 | 3254.83 | 22.45 | 1122.00 | 22.28 |
Minimum of Months | 34.50 | 20.58 | 87.50 | 20.38 | 4.67 | 20.28 |
Maximum of Months | 499.00 | 26.69 | 496.00 | 24.73 | 292.50 | 24.91 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.97 | 430.00 | 19.89 | 430.00 | 19.86 |
February | 454.00 | 20.09 | 415.33 | 20.04 | 415.33 | 20.02 |
March | 512.67 | 20.94 | 251.67 | 20.70 | 251.67 | 20.58 |
April | 413.83 | 21.65 | 121.33 | 21.51 | 95.33 | 21.32 |
May | 251.83 | 22.86 | 131.83 | 23.35 | 2.33 | 23.36 |
June | 43.33 | 24.65 | 416.33 | 24.31 | 22.17 | 24.38 |
July | 63.00 | 26.23 | 497.00 | 24.66 | 63.00 | 24.82 |
August | 42.17 | 25.36 | 459.50 | 24.43 | 28.33 | 24.53 |
September | 153.00 | 22.87 | 257.17 | 23.71 | 7.33 | 23.72 |
October | 375.33 | 21.95 | 147.83 | 22.02 | 67.67 | 21.80 |
November | 489.00 | 20.77 | 249.33 | 20.50 | 249.33 | 20.36 |
December | 497.00 | 20.06 | 462.17 | 20.02 | 462.17 | 20.01 |
Annual Sum or Average | 3797.17 | 21.13 | 3839.50 | 21.62 | 2094.67 | 21.34 |
Minimum of Months | 42.17 | 19.97 | 121.33 | 19.89 | 2.33 | 19.86 |
Maximum of Months | 512.67 | 26.23 | 497.00 | 24.66 | 462.17 | 24.82 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.05 | 395.50 | 19.91 | 395.50 | 19.86 |
February | 454.00 | 20.34 | 356.33 | 20.22 | 356.33 | 20.17 |
March | 484.50 | 21.23 | 168.17 | 20.92 | 167.50 | 20.74 |
April | 343.17 | 21.73 | 153.33 | 22.01 | 70.83 | 21.84 |
May | 240.83 | 22.94 | 219.00 | 23.70 | 23.83 | 23.86 |
June | 61.33 | 24.81 | 424.00 | 24.39 | 30.83 | 24.52 |
July | 69.67 | 26.62 | 488.83 | 24.76 | 69.67 | 24.97 |
August | 46.67 | 26.10 | 479.17 | 24.54 | 39.00 | 24.69 |
September | 158.50 | 23.29 | 304.67 | 24.01 | 29.50 | 24.15 |
October | 308.17 | 22.11 | 156.50 | 22.57 | 27.17 | 22.45 |
November | 481.00 | 20.97 | 190.00 | 20.66 | 190.00 | 20.49 |
December | 497.00 | 20.21 | 391.17 | 20.09 | 391.17 | 20.05 |
Annual Sum or Average | 3646.83 | 21.33 | 3726.67 | 21.92 | 1791.33 | 21.68 |
Minimum of Months | 46.67 | 20.05 | 153.33 | 19.91 | 23.83 | 19.86 |
Maximum of Months | 502.00 | 26.62 | 488.83 | 24.76 | 395.50 | 24.97 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 456.33 | 20.47 | 293.83 | 20.19 | 285.50 | 20.03 |
February | 392.50 | 20.95 | 254.00 | 20.74 | 237.83 | 20.56 |
March | 397.67 | 21.32 | 192.00 | 21.30 | 140.83 | 21.08 |
April | 334.33 | 21.76 | 154.67 | 22.06 | 68.67 | 21.87 |
May | 237.17 | 22.83 | 184.67 | 23.52 | 14.83 | 23.61 |
June | 57.33 | 24.44 | 410.83 | 24.32 | 24.83 | 24.42 |
July | 65.33 | 26.40 | 493.83 | 24.70 | 65.33 | 24.87 |
August | 49.00 | 25.99 | 474.17 | 24.57 | 39.33 | 24.72 |
September | 116.17 | 23.72 | 345.50 | 24.24 | 31.17 | 24.40 |
October | 205.67 | 22.70 | 284.83 | 23.55 | 37.67 | 23.53 |
November | 385.67 | 21.38 | 181.00 | 21.30 | 132.17 | 21.05 |
December | 435.83 | 20.81 | 283.50 | 20.59 | 270.00 | 20.42 |
Annual Sum or Average | 3133.00 | 21.66 | 3552.83 | 22.36 | 1348.17 | 22.12 |
Minimum of Months | 49.00 | 20.47 | 154.67 | 20.19 | 14.83 | 20.03 |
Maximum of Months | 456.33 | 26.40 | 493.83 | 24.70 | 285.50 | 24.87 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.33 | 20.24 | 354.83 | 20.05 | 354.83 | 19.98 |
February | 445.00 | 20.51 | 323.00 | 20.33 | 323.00 | 20.26 |
March | 445.83 | 21.19 | 181.50 | 21.11 | 156.67 | 20.97 |
April | 365.50 | 21.79 | 133.50 | 22.06 | 57.17 | 21.94 |
May | 242.33 | 22.88 | 196.17 | 23.58 | 19.17 | 23.72 |
June | 55.50 | 24.88 | 428.50 | 24.42 | 29.67 | 24.55 |
July | 62.33 | 26.56 | 490.00 | 24.74 | 62.33 | 24.93 |
August | 50.00 | 25.93 | 484.33 | 24.58 | 41.50 | 24.72 |
September | 146.00 | 23.00 | 288.50 | 23.87 | 20.17 | 23.99 |
October | 299.17 | 22.05 | 182.67 | 22.58 | 36.17 | 22.45 |
November | 473.67 | 20.97 | 182.67 | 20.73 | 180.83 | 20.59 |
December | 497.00 | 20.47 | 363.83 | 20.33 | 363.83 | 20.27 |
Annual Sum or Average | 3582.67 | 21.38 | 3609.50 | 22.01 | 1645.33 | 21.79 |
Minimum of Months | 50.00 | 20.24 | 133.50 | 20.05 | 19.17 | 19.98 |
Maximum of Months | 500.33 | 26.56 | 490.00 | 24.74 | 363.83 | 24.93 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 490.67 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 14.67 | 27.00 | 514.00 | 27.00 | 14.67 | 27.00 |
April | 106.67 | 27.00 | 485.00 | 27.00 | 106.67 | 27.00 |
May | 11.67 | 27.00 | 508.00 | 27.00 | 11.67 | 27.00 |
June | 167.17 | 27.00 | 496.00 | 27.00 | 167.17 | 27.00 |
July | 363.83 | 27.00 | 497.00 | 27.00 | 363.83 | 27.00 |
August | 479.00 | 27.02 | 514.00 | 27.02 | 479.00 | 27.02 |
September | 57.83 | 27.00 | 485.00 | 27.00 | 57.83 | 27.00 |
October | 56.17 | 27.00 | 502.00 | 27.00 | 56.17 | 27.00 |
November | 12.33 | 27.00 | 489.00 | 27.00 | 12.33 | 27.00 |
December | 1.83 | 27.00 | 497.00 | 27.00 | 1.83 | 27.00 |
Annual Sum or Average | 1271.17 | 27.01 | 5931.67 | 27.00 | 1271.17 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 479.00 | 27.02 | 514.00 | 27.02 | 479.00 | 27.02 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 66.67 | 25.32 | 332.33 | 26.64 | 6.83 | 26.58 |
February | 0.00 | 0.00 | 325.00 | 27.00 | 0.00 | 27.00 |
March | 1.33 | 27.00 | 511.83 | 27.00 | 1.33 | 27.00 |
April | 8.17 | 27.00 | 485.00 | 27.00 | 8.17 | 27.00 |
May | 2.83 | 27.00 | 508.00 | 27.00 | 2.83 | 27.00 |
June | 28.67 | 27.00 | 496.00 | 27.00 | 28.67 | 27.00 |
July | 73.17 | 27.00 | 497.00 | 27.00 | 73.17 | 27.00 |
August | 133.33 | 27.03 | 514.00 | 27.01 | 133.33 | 27.01 |
September | 16.00 | 27.00 | 485.00 | 27.00 | 16.00 | 27.00 |
October | 15.00 | 27.00 | 502.00 | 27.00 | 15.00 | 27.00 |
November | 0.00 | 0.00 | 468.83 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 474.33 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 345.17 | 26.69 | 5599.33 | 26.98 | 285.33 | 26.97 |
Minimum of Months | 0.00 | 0.00 | 325.00 | 26.64 | 0.00 | 26.58 |
Maximum of Months | 133.33 | 27.03 | 514.00 | 27.01 | 133.33 | 27.01 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 157.00 | 24.60 | 230.33 | 25.70 | 26.17 | 25.49 |
February | 42.67 | 27.00 | 195.17 | 27.00 | 0.00 | 27.00 |
March | 1.17 | 27.00 | 451.83 | 27.00 | 1.17 | 27.00 |
April | 16.33 | 27.00 | 478.00 | 27.00 | 16.33 | 27.00 |
May | 9.83 | 27.00 | 508.00 | 27.00 | 9.83 | 27.00 |
June | 70.00 | 27.00 | 496.00 | 27.00 | 70.00 | 27.00 |
July | 133.50 | 27.00 | 497.00 | 27.00 | 133.50 | 27.00 |
August | 194.33 | 27.01 | 514.00 | 27.01 | 194.33 | 27.01 |
September | 29.50 | 27.00 | 485.00 | 27.00 | 29.50 | 27.00 |
October | 18.33 | 27.00 | 481.00 | 27.00 | 18.33 | 27.00 |
November | 4.67 | 27.00 | 407.50 | 27.00 | 0.00 | 27.00 |
December | 14.33 | 27.00 | 311.83 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 691.67 | 26.46 | 5055.67 | 26.91 | 499.17 | 26.90 |
Minimum of Months | 1.17 | 24.60 | 195.17 | 25.70 | 0.00 | 25.49 |
Maximum of Months | 194.33 | 27.01 | 514.00 | 27.01 | 194.33 | 27.01 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 284.67 | 27.00 | 502.00 | 27.00 | 284.67 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 27.02 | 514.00 | 27.02 | 514.00 | 27.02 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5725.67 | 27.00 | 5943.00 | 27.00 | 5725.67 | 27.00 |
Minimum of Months | 284.67 | 27.00 | 454.00 | 27.00 | 284.67 | 27.00 |
Maximum of Months | 514.00 | 27.02 | 514.00 | 27.02 | 514.00 | 27.02 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00004 | 20.66393 | 0.71004 | 15.79164 |
February | 454.00000 | 27.00000 | 17.40427 | 0.73918 | 16.61788 |
March | 514.00000 | 27.00004 | 24.54601 | 0.88213 | 21.55348 |
April | 485.00000 | 27.00003 | 29.69382 | 0.97728 | 25.27341 |
May | 508.00000 | 27.00047 | 34.14993 | 0.26975 | 6.62072 |
June | 496.00000 | 27.00144 | 37.85983 | 0.38807 | 8.21986 |
July | 497.00000 | 27.00109 | 38.98733 | 0.46127 | 9.50530 |
August | 514.00000 | 27.01810 | 38.22366 | 0.50576 | 10.44705 |
September | 485.00000 | 27.00064 | 37.41135 | 0.32113 | 7.28973 |
October | 502.00000 | 27.00072 | 31.53779 | 0.94810 | 24.14325 |
November | 489.00000 | 27.00007 | 27.02664 | 0.89720 | 22.14307 |
December | 497.00000 | 26.99999 | 20.15593 | 0.84994 | 20.32284 |
Annual Sum or Average | 5943.00000 | 27.00194 | 29.89286 | 0.66145 | 15.63624 |
Minimum of Months | 454.00000 | 26.99999 | 17.40427 | 0.26975 | 6.62072 |
Maximum of Months | 514.00000 | 27.01810 | 38.98733 | 0.97728 | 25.27341 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.74925 | 20.74417 | 0.52945 | 12.01425 |
February | 454.00000 | 27.00000 | 17.40408 | 0.59567 | 12.60532 |
March | 514.00000 | 27.00004 | 24.53052 | 0.74064 | 16.74987 |
April | 485.00000 | 27.00004 | 29.65986 | 0.83599 | 19.93826 |
May | 508.00000 | 27.00030 | 34.22578 | 0.19035 | 5.92702 |
June | 496.00000 | 27.00144 | 37.91528 | 0.29670 | 6.93904 |
July | 497.00000 | 27.00121 | 39.02842 | 0.34285 | 7.53123 |
August | 514.00000 | 27.00683 | 38.22842 | 0.37337 | 8.01830 |
September | 485.00000 | 27.00046 | 37.56350 | 0.23758 | 6.37789 |
October | 502.00000 | 27.00069 | 31.54917 | 0.85760 | 20.76452 |
November | 489.00000 | 27.00006 | 27.00713 | 0.74135 | 16.81282 |
December | 497.00000 | 27.00000 | 20.14396 | 0.65321 | 14.08286 |
Annual Sum or Average | 5943.00000 | 26.97977 | 29.92125 | 0.53196 | 12.29822 |
Minimum of Months | 454.00000 | 26.74925 | 17.40408 | 0.19035 | 5.92702 |
Maximum of Months | 514.00000 | 27.00683 | 39.02842 | 0.85760 | 20.76452 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.18693 | 21.09699 | 0.36491 | 10.54152 |
February | 454.00000 | 27.00018 | 17.40193 | 0.52382 | 11.00889 |
March | 514.00000 | 27.00004 | 24.54294 | 0.68284 | 15.13452 |
April | 485.00000 | 27.00004 | 29.67520 | 0.79478 | 18.67361 |
May | 508.00000 | 27.00032 | 34.29644 | 0.17155 | 5.94282 |
June | 496.00000 | 27.00146 | 37.92134 | 0.30450 | 7.11479 |
July | 497.00000 | 27.00122 | 39.03462 | 0.36112 | 7.85575 |
August | 514.00000 | 27.00422 | 38.24283 | 0.38490 | 8.26634 |
September | 485.00000 | 27.00047 | 37.60044 | 0.22370 | 6.37995 |
October | 502.00000 | 27.00069 | 31.59559 | 0.81879 | 19.56085 |
November | 489.00000 | 27.00006 | 27.02599 | 0.67103 | 14.82010 |
December | 497.00000 | 27.00000 | 20.14891 | 0.57104 | 12.04701 |
Annual Sum or Average | 5943.00000 | 26.93206 | 29.97042 | 0.48871 | 11.43783 |
Minimum of Months | 454.00000 | 26.18693 | 17.40193 | 0.17155 | 5.94282 |
Maximum of Months | 514.00000 | 27.00422 | 39.03462 | 0.81879 | 19.56085 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99995 | 30.41368 | 1.03138 | 27.48503 |
February | 454.00000 | 27.00009 | 29.12197 | 1.18735 | 34.63875 |
March | 514.00000 | 27.00047 | 27.81204 | 1.34248 | 42.48992 |
April | 485.00000 | 27.00256 | 29.01061 | 1.49359 | 50.56123 |
May | 508.00000 | 27.00000 | 36.41646 | 0.54170 | 11.26674 |
June | 496.00000 | 27.00231 | 40.22016 | 0.82880 | 19.59102 |
July | 497.00000 | 27.00182 | 38.77962 | 1.04269 | 27.97372 |
August | 514.00000 | 27.02082 | 37.70902 | 1.24078 | 37.28994 |
September | 485.00000 | 27.00088 | 40.68233 | 0.65032 | 14.07074 |
October | 502.00000 | 27.00052 | 38.09548 | 1.33374 | 42.10734 |
November | 489.00000 | 27.00010 | 29.35160 | 1.38282 | 44.61203 |
December | 497.00000 | 27.00013 | 23.68902 | 1.45131 | 48.27069 |
Annual Sum or Average | 5943.00000 | 27.00253 | 33.47476 | 1.12669 | 33.34412 |
Minimum of Months | 454.00000 | 26.99995 | 23.68902 | 0.54170 | 11.26674 |
Maximum of Months | 514.00000 | 27.02082 | 40.68233 | 1.49359 | 50.56123 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.50285 | 21.95591 | 0.33696 | 7.77403 |
February | 454.00000 | 24.54697 | 17.91991 | 0.32493 | 7.64131 |
March | 514.00000 | 24.51085 | 25.20586 | 0.38461 | 8.55659 |
April | 485.00000 | 24.62178 | 31.13214 | 0.45577 | 10.00858 |
May | 508.00000 | 24.76332 | 39.42736 | -0.2850 | 9.02091 |
June | 496.00000 | 26.43796 | 65.60721 | 0.46697 | 22.35799 |
July | 497.00000 | 28.77657 | 82.71903 | 1.37255 | 49.42629 |
August | 514.00000 | 28.53929 | 80.65386 | 1.31271 | 50.32044 |
September | 485.00000 | 26.12686 | 59.72106 | 0.33753 | 19.81679 |
October | 502.00000 | 24.82561 | 39.59243 | 0.58089 | 13.19835 |
November | 489.00000 | 24.74641 | 27.47948 | 0.46787 | 10.53637 |
December | 497.00000 | 24.67682 | 19.73547 | 0.38498 | 8.71089 |
Annual Sum or Average | 5943.00000 | 25.60128 | 42.81276 | 0.51397 | 18.24736 |
Minimum of Months | 454.00000 | 24.50285 | 17.91991 | -0.2850 | 7.64131 |
Maximum of Months | 514.00000 | 28.77657 | 82.71903 | 1.37255 | 50.32044 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.94213 | 25.99277 | 0.22965 | 6.41532 |
February | 454.00000 | 24.12345 | 20.02794 | 0.24311 | 6.43561 |
March | 514.00000 | 24.26716 | 26.55599 | 0.34887 | 7.82951 |
April | 485.00000 | 24.28905 | 32.48008 | 0.41410 | 8.92493 |
May | 508.00000 | 24.25463 | 41.48642 | -0.3981 | 8.82167 |
June | 496.00000 | 24.30596 | 51.36672 | -0.2603 | 6.98311 |
July | 497.00000 | 24.40296 | 53.93467 | -0.1667 | 6.21155 |
August | 514.00000 | 24.31761 | 50.11838 | -0.2070 | 6.47227 |
September | 485.00000 | 24.37804 | 47.61126 | -0.2808 | 7.43178 |
October | 502.00000 | 24.36078 | 40.12870 | 0.48883 | 10.51569 |
November | 489.00000 | 24.41794 | 29.12615 | 0.40348 | 8.92153 |
December | 497.00000 | 24.32952 | 21.82855 | 0.32320 | 7.44944 |
Annual Sum or Average | 5943.00000 | 24.28298 | 36.84849 | 0.09294 | 7.70695 |
Minimum of Months | 454.00000 | 23.94213 | 20.02794 | -0.3981 | 6.21155 |
Maximum of Months | 514.00000 | 24.41794 | 53.93467 | 0.48883 | 10.51569 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.31691 | 27.66754 | -0.1933 | 8.12914 |
February | 454.00000 | 22.85992 | 23.31572 | -0.0810 | 5.87020 |
March | 514.00000 | 23.56411 | 29.43289 | 0.15005 | 5.93941 |
April | 485.00000 | 23.77113 | 34.73414 | 0.25469 | 6.84901 |
May | 508.00000 | 24.04261 | 42.44611 | -0.5020 | 10.73624 |
June | 496.00000 | 24.16659 | 52.83542 | -0.3641 | 8.11878 |
July | 497.00000 | 24.19513 | 56.97660 | -0.3211 | 7.41302 |
August | 514.00000 | 24.21249 | 52.84649 | -0.3380 | 7.73423 |
September | 485.00000 | 24.14919 | 48.82307 | -0.4083 | 8.97223 |
October | 502.00000 | 24.02878 | 41.48249 | 0.37999 | 8.57050 |
November | 489.00000 | 23.60504 | 32.44173 | 0.17836 | 6.55847 |
December | 497.00000 | 23.05969 | 26.03094 | -0.0096 | 5.61996 |
Annual Sum or Average | 5943.00000 | 23.67008 | 39.20634 | -0.1055 | 7.55767 |
Minimum of Months | 454.00000 | 22.31691 | 23.31572 | -0.5020 | 5.61996 |
Maximum of Months | 514.00000 | 24.21249 | 56.97660 | 0.37999 | 10.73624 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.08356 | 29.98718 | -0.5029 | 13.70431 |
February | 454.00000 | 21.37541 | 24.93761 | -0.4571 | 11.45126 |
March | 514.00000 | 22.48613 | 31.89499 | -0.1183 | 6.81807 |
April | 485.00000 | 23.07349 | 36.58350 | 0.08126 | 6.87661 |
May | 508.00000 | 23.84150 | 43.19454 | -0.5716 | 12.75496 |
June | 496.00000 | 24.16063 | 52.87277 | -0.3537 | 7.99393 |
July | 497.00000 | 24.25477 | 56.69202 | -0.2826 | 6.96350 |
August | 514.00000 | 24.23053 | 52.71829 | -0.3167 | 7.50932 |
September | 485.00000 | 23.99260 | 49.55654 | -0.4597 | 10.24258 |
October | 502.00000 | 23.44073 | 43.21584 | 0.23165 | 7.84013 |
November | 489.00000 | 22.33155 | 35.55791 | -0.1416 | 7.67681 |
December | 497.00000 | 21.40933 | 28.62577 | -0.4226 | 10.76196 |
Annual Sum or Average | 5943.00000 | 22.98593 | 40.60192 | -0.2754 | 9.20230 |
Minimum of Months | 454.00000 | 21.08356 | 24.93761 | -0.5716 | 6.81807 |
Maximum of Months | 514.00000 | 24.25477 | 56.69202 | 0.23165 | 13.70431 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.63885 | 26.18424 | -0.3546 | 8.99731 |
February | 454.00000 | 21.84390 | 21.13747 | -0.3319 | 8.37517 |
March | 514.00000 | 23.06250 | 27.92174 | 0.02234 | 6.04745 |
April | 485.00000 | 23.70368 | 32.97216 | 0.23909 | 7.00578 |
May | 508.00000 | 24.13141 | 41.00547 | -0.4529 | 10.08351 |
June | 496.00000 | 24.35247 | 50.68790 | -0.2207 | 6.82486 |
July | 497.00000 | 24.54416 | 53.11785 | -0.0827 | 6.48233 |
August | 514.00000 | 24.37881 | 49.40594 | -0.1659 | 6.53702 |
September | 485.00000 | 24.27231 | 47.44800 | -0.3336 | 8.34873 |
October | 502.00000 | 23.88592 | 40.31868 | 0.34100 | 8.37769 |
November | 489.00000 | 23.19154 | 30.47643 | 0.06807 | 6.39596 |
December | 497.00000 | 22.47315 | 23.43680 | -0.1599 | 6.29819 |
Annual Sum or Average | 5943.00000 | 23.46788 | 37.12833 | -0.1184 | 7.47552 |
Minimum of Months | 454.00000 | 21.63885 | 21.13747 | -0.4529 | 6.04745 |
Maximum of Months | 514.00000 | 24.54416 | 53.11785 | 0.34100 | 10.08351 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.57838 | 25.65653 | -0.3534 | 8.96651 |
February | 454.00000 | 21.97394 | 20.34404 | -0.2814 | 8.16307 |
March | 514.00000 | 22.79986 | 27.60034 | 0.00111 | 6.61109 |
April | 485.00000 | 23.43093 | 33.04803 | 0.22432 | 8.07641 |
May | 508.00000 | 24.08523 | 40.88288 | -0.3856 | 10.58760 |
June | 496.00000 | 24.30332 | 50.67682 | -0.1788 | 6.96482 |
July | 497.00000 | 24.49188 | 53.07951 | -0.0375 | 6.80165 |
August | 514.00000 | 24.31769 | 49.30689 | -0.1007 | 6.45111 |
September | 485.00000 | 24.26306 | 47.13866 | -0.2629 | 8.76025 |
October | 502.00000 | 23.79100 | 40.13550 | 0.36752 | 9.29841 |
November | 489.00000 | 22.88365 | 30.36240 | 0.02321 | 6.72913 |
December | 497.00000 | 22.07032 | 23.19393 | -0.2340 | 7.26087 |
Annual Sum or Average | 5943.00000 | 23.34223 | 36.90795 | -0.1007 | 7.88616 |
Minimum of Months | 454.00000 | 21.57838 | 20.34404 | -0.3856 | 6.45111 |
Maximum of Months | 514.00000 | 24.49188 | 53.07951 | 0.36752 | 10.58760 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.02227 | 25.25394 | -0.2384 | 9.44546 |
February | 454.00000 | 22.62174 | 19.71771 | -0.1113 | 8.60448 |
March | 514.00000 | 23.14462 | 27.01743 | 0.09874 | 7.19824 |
April | 485.00000 | 23.61923 | 32.75900 | 0.25980 | 8.33127 |
May | 508.00000 | 24.06685 | 41.07267 | -0.4395 | 10.77714 |
June | 496.00000 | 24.33472 | 50.66747 | -0.2054 | 6.90632 |
July | 497.00000 | 24.51818 | 53.09285 | -0.0607 | 6.62376 |
August | 514.00000 | 24.40592 | 49.09532 | -0.0762 | 6.43807 |
September | 485.00000 | 24.38643 | 46.79611 | -0.1923 | 8.02792 |
October | 502.00000 | 24.21743 | 39.01073 | 0.52089 | 12.49081 |
November | 489.00000 | 23.35137 | 29.54150 | 0.15566 | 7.77254 |
December | 497.00000 | 22.73857 | 22.48362 | -0.0575 | 7.85864 |
Annual Sum or Average | 5943.00000 | 23.62573 | 36.50045 | -0.0290 | 8.37297 |
Minimum of Months | 454.00000 | 22.02227 | 19.71771 | -0.4395 | 6.43807 |
Maximum of Months | 514.00000 | 24.51818 | 53.09285 | 0.52089 | 12.49081 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.07797 | 24.60943 | -0.2131 | 7.50283 |
February | 454.00000 | 22.73165 | 19.13271 | -0.0730 | 6.72504 |
March | 514.00000 | 23.95283 | 25.39137 | 0.31734 | 8.16236 |
April | 485.00000 | 24.39408 | 30.88977 | 0.51552 | 11.77013 |
May | 508.00000 | 24.30647 | 40.19237 | -0.2716 | 8.25001 |
June | 496.00000 | 24.48688 | 49.96919 | -0.0331 | 6.66187 |
July | 497.00000 | 24.61470 | 52.60196 | 0.08091 | 7.25413 |
August | 514.00000 | 24.49311 | 48.75062 | 0.06282 | 6.67685 |
September | 485.00000 | 24.38647 | 46.70938 | -0.1823 | 7.47290 |
October | 502.00000 | 24.33156 | 38.72767 | 0.54296 | 12.38885 |
November | 489.00000 | 23.94776 | 28.15581 | 0.30326 | 8.08692 |
December | 497.00000 | 23.77997 | 20.68657 | 0.19802 | 6.64713 |
Annual Sum or Average | 5943.00000 | 23.96657 | 35.60846 | 0.10466 | 8.13692 |
Minimum of Months | 454.00000 | 22.07797 | 19.13271 | -0.2716 | 6.64713 |
Maximum of Months | 514.00000 | 24.61470 | 52.60196 | 0.54296 | 12.38885 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.28287 | 28.51189 | -0.7462 | 19.12365 |
February | 454.00000 | 20.47796 | 23.07438 | -0.7166 | 17.46470 |
March | 514.00000 | 21.45300 | 31.08376 | -0.3775 | 9.39571 |
April | 485.00000 | 22.51904 | 35.93770 | -0.0614 | 7.13611 |
May | 508.00000 | 23.77078 | 42.30042 | -0.5996 | 13.90835 |
June | 496.00000 | 24.23034 | 52.42090 | -0.3045 | 7.54104 |
July | 497.00000 | 24.44330 | 56.53873 | -0.1771 | 6.64805 |
August | 514.00000 | 24.30488 | 52.30852 | -0.2640 | 7.23285 |
September | 485.00000 | 23.91769 | 49.19174 | -0.4901 | 11.31411 |
October | 502.00000 | 23.02548 | 42.61742 | 0.12152 | 7.42013 |
November | 489.00000 | 21.46739 | 34.20395 | -0.3604 | 9.86176 |
December | 497.00000 | 20.56268 | 27.03931 | -0.6547 | 15.09564 |
Annual Sum or Average | 5943.00000 | 22.55401 | 39.72530 | -0.3839 | 10.96823 |
Minimum of Months | 454.00000 | 20.28287 | 23.07438 | -0.7462 | 6.64805 |
Maximum of Months | 514.00000 | 24.44330 | 56.53873 | 0.12152 | 19.12365 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.25436 | 27.13765 | -0.7365 | 19.06846 |
February | 385.00000 | 20.75662 | 21.46158 | -0.6252 | 15.00669 |
March | 433.00000 | 21.69498 | 29.54955 | -0.2905 | 8.96487 |
April | 410.00000 | 22.73180 | 34.49928 | 0.03314 | 8.19874 |
May | 430.00000 | 23.76759 | 41.72955 | -0.5116 | 14.66564 |
June | 418.00000 | 24.25615 | 51.96185 | -0.2360 | 8.00215 |
July | 422.00000 | 24.55496 | 55.83442 | -0.0774 | 7.50118 |
August | 433.00000 | 24.40463 | 51.72002 | -0.1408 | 7.16046 |
September | 410.00000 | 23.98488 | 48.57937 | -0.3937 | 11.68331 |
October | 427.00000 | 23.15486 | 41.28030 | 0.19490 | 8.17623 |
November | 417.00000 | 21.55203 | 32.92111 | -0.3190 | 9.43794 |
December | 422.00000 | 20.69712 | 25.61730 | -0.6085 | 14.04150 |
Annual Sum or Average | 5034.00000 | 22.66284 | 38.63600 | -0.3074 | 10.96995 |
Minimum of Months | 385.00000 | 20.25436 | 21.46158 | -0.7365 | 7.16046 |
Maximum of Months | 433.00000 | 24.55496 | 55.83442 | 0.19490 | 19.06846 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.27804 | 26.78096 | -0.4438 | 14.31290 |
February | 454.00000 | 22.06214 | 20.93938 | -0.2639 | 11.25197 |
March | 514.00000 | 22.48954 | 28.69495 | -0.0651 | 8.32114 |
April | 485.00000 | 23.01316 | 34.28984 | 0.10303 | 8.32800 |
May | 508.00000 | 23.81873 | 41.92877 | -0.5355 | 13.48564 |
June | 496.00000 | 24.23661 | 52.23212 | -0.2714 | 7.66584 |
July | 497.00000 | 24.47545 | 56.13136 | -0.1256 | 6.85701 |
August | 514.00000 | 24.39923 | 51.58216 | -0.1317 | 6.80216 |
September | 485.00000 | 24.24381 | 47.75422 | -0.2573 | 9.27564 |
October | 502.00000 | 24.00264 | 39.58989 | 0.46725 | 12.19748 |
November | 489.00000 | 22.65917 | 31.49218 | -0.0158 | 8.66517 |
December | 497.00000 | 21.96201 | 24.79773 | -0.2630 | 10.76152 |
Annual Sum or Average | 5943.00000 | 23.22877 | 38.14687 | -0.1500 | 9.82238 |
Minimum of Months | 454.00000 | 21.27804 | 20.93938 | -0.5355 | 6.80216 |
Maximum of Months | 514.00000 | 24.47545 | 56.13136 | 0.46725 | 14.31290 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.60277 | 27.30459 | -0.6377 | 16.19414 |
February | 454.00000 | 20.98724 | 21.73976 | -0.5566 | 13.76034 |
March | 514.00000 | 22.00589 | 29.24831 | -0.1945 | 8.25497 |
April | 485.00000 | 22.78759 | 34.55742 | 0.06522 | 8.11751 |
May | 508.00000 | 23.78102 | 41.87543 | -0.4950 | 13.18714 |
June | 496.00000 | 24.29985 | 51.78357 | -0.1737 | 7.42425 |
July | 497.00000 | 24.51512 | 55.74408 | -0.0521 | 7.08420 |
August | 514.00000 | 24.41877 | 51.52788 | -0.0880 | 6.74339 |
September | 485.00000 | 23.95663 | 48.53825 | -0.3791 | 10.80475 |
October | 502.00000 | 23.30309 | 41.25167 | 0.25430 | 8.84025 |
November | 489.00000 | 21.62809 | 33.04922 | -0.2914 | 8.86622 |
December | 497.00000 | 20.96391 | 25.68719 | -0.5304 | 12.13549 |
Annual Sum or Average | 5943.00000 | 22.78561 | 38.64971 | -0.2545 | 10.09089 |
Minimum of Months | 454.00000 | 20.60277 | 21.73976 | -0.6377 | 6.74339 |
Maximum of Months | 514.00000 | 24.51512 | 55.74408 | 0.25430 | 16.19414 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.96878 | 29.53642 | -0.8658 | 23.80359 |
February | 454.00000 | 20.08620 | 24.24250 | -0.8618 | 23.09780 |
March | 514.00000 | 20.94322 | 32.38597 | -0.5309 | 13.12702 |
April | 485.00000 | 21.99952 | 37.10917 | -0.1999 | 9.09054 |
May | 508.00000 | 23.50536 | 43.09228 | -0.6888 | 17.63727 |
June | 496.00000 | 24.19732 | 52.67444 | -0.3049 | 7.86488 |
July | 497.00000 | 24.46155 | 56.62428 | -0.1531 | 6.74489 |
August | 514.00000 | 24.29123 | 52.42596 | -0.2544 | 7.41041 |
September | 485.00000 | 23.72404 | 50.02488 | -0.5526 | 13.64576 |
October | 502.00000 | 22.44213 | 44.08220 | -0.0250 | 8.81492 |
November | 489.00000 | 20.76685 | 36.05823 | -0.5607 | 14.52875 |
December | 497.00000 | 20.05550 | 28.67207 | -0.8297 | 21.93248 |
Annual Sum or Average | 5943.00000 | 22.22083 | 40.69631 | -0.4830 | 13.90916 |
Minimum of Months | 454.00000 | 19.96878 | 24.24250 | -0.8658 | 6.74489 |
Maximum of Months | 514.00000 | 24.46155 | 56.62428 | -0.0250 | 23.80359 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.04656 | 28.72537 | -0.8207 | 22.42868 |
February | 454.00000 | 20.34477 | 23.29866 | -0.7575 | 19.56934 |
March | 514.00000 | 21.38885 | 31.00785 | -0.3853 | 11.36708 |
April | 485.00000 | 22.46095 | 35.38196 | -0.0424 | 9.10532 |
May | 508.00000 | 23.57712 | 42.44619 | -0.5616 | 16.64130 |
June | 496.00000 | 24.18891 | 52.30621 | -0.2253 | 7.93196 |
July | 497.00000 | 24.47973 | 55.95039 | -0.0603 | 7.36492 |
August | 514.00000 | 24.33272 | 51.74332 | -0.1209 | 7.02899 |
September | 485.00000 | 23.83497 | 49.15763 | -0.4248 | 12.69868 |
October | 502.00000 | 22.84480 | 42.51345 | 0.12158 | 8.79242 |
November | 489.00000 | 21.01999 | 34.88072 | -0.4715 | 12.86235 |
December | 497.00000 | 20.20517 | 27.76812 | -0.7667 | 19.74778 |
Annual Sum or Average | 5943.00000 | 22.41031 | 39.71843 | -0.3736 | 12.91279 |
Minimum of Months | 454.00000 | 20.04656 | 23.29866 | -0.8207 | 7.02899 |
Maximum of Months | 514.00000 | 24.47973 | 55.95039 | 0.12158 | 22.42868 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.79691 | 27.95324 | -0.5952 | 18.56038 |
February | 454.00000 | 21.41153 | 22.25140 | -0.4575 | 15.23772 |
March | 514.00000 | 21.94548 | 30.05798 | -0.2225 | 10.72228 |
April | 485.00000 | 22.52274 | 35.44006 | -0.0287 | 9.51352 |
May | 508.00000 | 23.51928 | 42.77819 | -0.6333 | 17.43895 |
June | 496.00000 | 24.16814 | 52.56924 | -0.2817 | 8.21058 |
July | 497.00000 | 24.46532 | 56.29890 | -0.1100 | 7.02600 |
August | 514.00000 | 24.36862 | 51.77171 | -0.1266 | 7.06747 |
September | 485.00000 | 24.05484 | 48.54687 | -0.3174 | 11.04618 |
October | 502.00000 | 23.60003 | 40.66835 | 0.35782 | 11.70625 |
November | 489.00000 | 21.95678 | 33.34123 | -0.2133 | 10.93221 |
December | 497.00000 | 21.25332 | 26.60627 | -0.4745 | 15.42250 |
Annual Sum or Average | 5943.00000 | 22.85006 | 39.14819 | -0.2575 | 11.88984 |
Minimum of Months | 454.00000 | 20.79691 | 22.25140 | -0.6333 | 7.02600 |
Maximum of Months | 514.00000 | 24.46532 | 56.29890 | 0.35782 | 18.56038 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.25590 | 28.30379 | -0.7582 | 20.47024 |
February | 454.00000 | 20.58269 | 22.93335 | -0.6912 | 18.25152 |
March | 514.00000 | 21.57708 | 30.37152 | -0.3222 | 10.43563 |
April | 485.00000 | 22.36142 | 35.54581 | -0.0486 | 9.19761 |
May | 508.00000 | 23.50073 | 42.63712 | -0.5845 | 16.74869 |
June | 496.00000 | 24.23109 | 52.11952 | -0.1841 | 7.93517 |
July | 497.00000 | 24.49577 | 55.92739 | -0.0401 | 7.33405 |
August | 514.00000 | 24.38663 | 51.70174 | -0.0841 | 7.01699 |
September | 485.00000 | 23.74739 | 49.37031 | -0.4432 | 13.02356 |
October | 502.00000 | 22.83438 | 42.44678 | 0.13576 | 9.17160 |
November | 489.00000 | 21.06748 | 34.62001 | -0.4531 | 12.04536 |
December | 497.00000 | 20.47184 | 27.21373 | -0.6888 | 17.12126 |
Annual Sum or Average | 5943.00000 | 22.47550 | 39.55238 | -0.3442 | 12.35116 |
Minimum of Months | 454.00000 | 20.25590 | 22.93335 | -0.7582 | 7.01699 |
Maximum of Months | 514.00000 | 24.49577 | 55.92739 | 0.13576 | 20.47024 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 72818693.24 | 2562.67 | 24-JAN-07:13 | 36.58 | 0.771329E+09 | 0.00 | 0.844148E+09 | 0.52 | 10.69 | 07-JAN-13:30 | 0.00 | 0.00 |
February | 46386186.93 | 528.94 | 28-FEB-15:00 | 31.56 | 0.491537E+09 | 0.00 | 0.537923E+09 | 0.50 | 10.68 | 09-FEB-06:50 | 0.00 | 0.00 |
March | 0.140018E+10 | 63261.52 | 27-MAR-16:00 | 75.77 | 0.147940E+11 | 0.00 | 0.161942E+11 | 1.08 | 10.68 | 17-MAR-08:70 | 0.00 | 0.00 |
April | 0.129449E+11 | 194872.24 | 07-APR-15:00 | 138.03 | 0.127120E+12 | 0.00 | 0.140065E+12 | 2.00 | 10.67 | 11-APR-13:50 | 0.00 | 0.00 |
May | 0.410594E+11 | 218990.10 | 31-MAY-07:50 | 331.74 | 0.404384E+12 | 0.00 | 0.445444E+12 | 4.61 | 10.66 | 01-MAY-13:40 | 0.00 | 0.00 |
June | 0.134606E+12 | 225854.02 | 19-JUN-17:00 | 516.29 | 0.117394E+13 | 0.00 | 0.130854E+13 | 6.80 | 10.65 | 02-JUN-08:00 | 0.00 | 0.00 |
July | 0.167106E+12 | 223936.83 | 20-JUL-16:50 | 628.22 | 0.141762E+13 | 0.00 | 0.158473E+13 | 7.80 | 10.63 | 11-JUL-04:12 | 0.00 | 0.00 |
August | 0.161992E+12 | 227973.94 | 02-AUG-16:20 | 655.35 | 0.138809E+13 | 0.00 | 0.155008E+13 | 8.30 | 10.62 | 26-AUG-04:33 | 0.00 | 0.00 |
September | 0.954917E+11 | 219236.69 | 07-SEP-16:10 | 437.89 | 0.856097E+12 | 0.00 | 0.951588E+12 | 5.95 | 10.65 | 23-SEP-14:20 | 0.00 | 0.00 |
October | 0.448998E+11 | 214345.69 | 24-OCT-10:40 | 273.43 | 0.409225E+12 | 0.00 | 0.454125E+12 | 3.70 | 10.67 | 26-OCT-11:50 | 0.00 | 0.00 |
November | 0.136243E+10 | 31458.90 | 03-NOV-14:00 | 52.44 | 0.144098E+11 | 0.00 | 0.157723E+11 | 0.77 | 10.67 | 15-NOV-08:20 | 0.00 | 0.00 |
December | 25691212.78 | 518.34 | 15-DEC-13:20 | 17.21 | 0.272280E+09 | 0.00 | 0.297971E+09 | 0.25 | 10.68 | 06-DEC-07:50 | 0.00 | 0.00 |
Annual Sum or Average | 0.661007E+12 | 3194.52 | 0.580721E+13 | 0.00 | 0.646822E+13 | 3.54 | 0.00 | 0.00 | ||||
Minimum of Months | 25691212.78 | 518.34 | 17.21 | 0.272280E+09 | 0.00 | 0.297971E+09 | 0.25 | 10.62 | 0.00 | 0.00 | ||
Maximum of Months | 0.167106E+12 | 227973.94 | 655.35 | 0.141762E+13 | 0.00 | 0.158473E+13 | 8.30 | 10.69 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.320709E+10 | 192497.83 | 30-MAY-13:30 | 10.53 | 0.294449E+11 | 0.00 | 0.326520E+11 | 0.13 | 11.10 | 30-MAY-13:27 | 0.00 | 0.00 |
June | 0.231254E+11 | 181972.04 | 27-JUN-15:01 | 76.75 | 0.210708E+12 | 0.00 | 0.233833E+12 | 0.98 | 11.19 | 01-JUN-15:20 | 0.00 | 0.00 |
July | 0.419551E+11 | 214975.88 | 24-JUL-05:04 | 131.50 | 0.371915E+12 | 0.00 | 0.413870E+12 | 1.57 | 11.05 | 11-JUL-09:30 | 0.00 | 0.00 |
August | 0.458355E+11 | 154527.79 | 25-AUG-14:43 | 142.65 | 0.405896E+12 | 0.00 | 0.451732E+12 | 1.71 | 11.22 | 25-AUG-14:40 | 0.00 | 0.00 |
September | 0.119626E+11 | 182698.68 | 06-SEP-11:22 | 38.42 | 0.108206E+12 | 0.00 | 0.120169E+12 | 0.48 | 10.98 | 01-SEP-15:50 | 0.00 | 0.00 |
October | 0.435735E+10 | 187697.24 | 04-OCT-13:02 | 15.59 | 0.404642E+11 | 0.00 | 0.448215E+11 | 0.20 | 11.07 | 11-OCT-14:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.130443E+12 | 415.44 | 0.116663E+13 | 0.00 | 0.129708E+13 | 0.43 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.458355E+11 | 214975.88 | 142.65 | 0.405896E+12 | 0.00 | 0.451732E+12 | 1.71 | 11.22 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.669009E+09 | 744.00 | 2056.26 | 20-JAN-17:00 | 87408.82 | 20-JAN-17:05 | 18.60 | 18.33 | 15.78 |
February | 0.166277E+10 | 672.00 | 3808.58 | 22-FEB-16:00 | 131116.03 | 22-FEB-16:10 | 19.21 | 18.33 | 15.77 |
March | 0.568699E+10 | 744.00 | 49248.27 | 27-MAR-12:20 | 368253.36 | 27-MAR-16:00 | 19.91 | 18.36 | 15.76 |
April | 0.258111E+11 | 720.00 | 49248.27 | 06-APR-09:00 | 657508.35 | 07-APR-13:10 | 21.71 | 18.85 | 15.81 |
May | 0.407288E+11 | 744.00 | 49248.27 | 05-MAY-11:30 | 369454.63 | 30-MAY-13:55 | 20.07 | 19.29 | 15.83 |
June | 0.113296E+12 | 720.00 | 49248.27 | 01-JUN-00:10 | 487702.79 | 21-JUN-16:40 | 28.05 | 23.52 | 15.84 |
July | 0.131907E+12 | 744.00 | 49248.27 | 01-JUL-00:10 | 646270.60 | 31-JUL-24:00 | 37.56 | 28.33 | 15.84 |
August | 0.131163E+12 | 744.00 | 49248.27 | 01-AUG-00:05 | 736536.39 | 22-AUG-14:43 | 40.12 | 28.84 | 15.84 |
September | 0.902699E+11 | 720.00 | 49248.27 | 01-SEP-00:03 | 384681.79 | 01-SEP-14:00 | 22.87 | 21.38 | 15.84 |
October | 0.367618E+11 | 744.00 | 49248.27 | 02-OCT-09:10 | 428461.81 | 25-OCT-10:50 | 20.24 | 18.92 | 15.84 |
November | 0.615983E+10 | 720.00 | 49248.27 | 03-NOV-13:30 | 157696.90 | 21-NOV-08:55 | 19.80 | 18.33 | 15.81 |
December | 0.444861E+10 | 744.00 | 3768.30 | 15-DEC-15:20 | 223753.27 | 22-DEC-17:05 | 20.30 | 18.33 | 15.70 |
Annual Sum or Average | 0.588564E+12 | 8760.00 | 24.09 | 20.93 | 15.81 | ||||
Minimum of Months | 0.669009E+09 | 672.00 | 2056.26 | 87408.82 | 18.60 | 18.33 | 15.70 | ||
Maximum of Months | 0.131907E+12 | 744.00 | 49248.27 | 736536.39 | 40.12 | 28.84 | 15.84 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 279808.40 | 11-JAN-21:50 | 21.01 | 21.00 | 0.31 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 279809.39 | 06-FEB-20:00 | 20.89 | 20.89 | 0.28 |
March | 36601185.65 | 7.50 | 2712.66 | 27-MAR-16:00 | 709887.90 | 27-MAR-16:00 | 20.94 | 20.91 | 2.25 |
April | 0.513599E+09 | 81.72 | 21250.11 | 07-APR-12:40 | 1560254.69 | 07-APR-15:00 | 21.19 | 21.00 | 10.52 |
May | 0.284873E+10 | 245.18 | 21250.11 | 18-MAY-10:00 | 1446713.70 | 30-MAY-10:20 | 21.75 | 21.18 | 29.28 |
June | 0.254693E+11 | 487.17 | 21250.11 | 01-JUN-09:30 | 1501465.32 | 22-JUN-12:40 | 24.00 | 22.31 | 48.92 |
July | 0.444761E+11 | 624.39 | 21250.11 | 01-JUL-04:12 | 1494154.67 | 11-JUL-17:00 | 25.78 | 23.79 | 55.97 |
August | 0.345260E+11 | 601.55 | 21250.11 | 01-AUG-00:10 | 1623090.84 | 23-AUG-10:40 | 24.95 | 22.99 | 58.54 |
September | 0.130756E+11 | 381.85 | 21250.11 | 01-SEP-04:12 | 1519545.80 | 01-SEP-14:45 | 23.16 | 21.92 | 41.39 |
October | 0.527909E+10 | 208.68 | 21250.11 | 02-OCT-12:50 | 1521377.34 | 13-OCT-14:10 | 21.76 | 21.18 | 23.85 |
November | 10127447.26 | 12.49 | 767.72 | 10-NOV-10:00 | 378484.31 | 03-NOV-14:00 | 21.01 | 20.99 | 2.63 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 279634.93 | 15-DEC-11:40 | 20.90 | 20.90 | 0.13 |
Annual Sum or Average | 0.126235E+12 | 2650.52 | 22.29 | 21.59 | 22.99 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 279634.93 | 20.89 | 20.89 | 0.13 | ||
Maximum of Months | 0.444761E+11 | 624.39 | 21250.11 | 1623090.84 | 25.78 | 23.79 | 58.54 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 21.01 | 21.01 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 20.89 | 20.89 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 20.94 | 20.94 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 21.19 | 21.19 | 0.00 |
May | 0.801129E+09 | 10.47 | 21250.11 | 30-MAY-10:25 | 1315429.09 | 30-MAY-13:33 | 21.75 | 21.71 | 0.99 |
June | 0.895692E+10 | 117.08 | 21250.11 | 01-JUN-10:00 | 1245217.40 | 22-JUN-15:25 | 24.00 | 23.41 | 9.66 |
July | 0.181487E+11 | 237.24 | 21250.11 | 03-JUL-07:20 | 1192695.55 | 11-JUL-09:40 | 25.78 | 24.66 | 17.94 |
August | 0.160532E+11 | 212.32 | 21250.11 | 01-AUG-07:20 | 1395515.34 | 25-AUG-12:55 | 24.95 | 23.97 | 17.03 |
September | 0.487010E+10 | 63.66 | 21250.11 | 01-SEP-05:05 | 1424515.05 | 01-SEP-13:23 | 23.16 | 22.83 | 5.13 |
October | 0.131984E+10 | 17.25 | 21250.11 | 03-OCT-10:30 | 1208611.41 | 04-OCT-13:04 | 21.76 | 21.68 | 1.57 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.01 | 21.01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 20.90 | 20.90 | 0.00 |
Annual Sum or Average | 0.501500E+11 | 658.02 | 22.29 | 22.02 | 4.40 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.89 | 20.89 | 0.00 | ||
Maximum of Months | 0.181487E+11 | 237.24 | 21250.11 | 1424515.05 | 25.78 | 24.66 | 17.94 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.215236E+12 | 0.00 | 502.96 | 1907487.36 | 02-JAN-04:01 | 0.00 | 28.74 | 64.39 | 0.42 | 0.00 | 0.03 | 0.79 | 02-JAN-04:01 |
February | 0.147026E+12 | 0.00 | 435.17 | 1587094.76 | 13-FEB-06:01 | 0.00 | 28.49 | 62.45 | 0.32 | 0.00 | 0.03 | 0.66 | 13-FEB-06:01 |
March | 0.477080E+11 | 0.00 | 321.84 | 1350871.20 | 13-MAR-04:01 | 0.00 | 23.27 | 47.98 | 0.08 | 0.00 | 0.01 | 0.56 | 13-MAR-04:01 |
April | 0.128490E+11 | 0.00 | 140.56 | 1180071.39 | 22-APR-05:02 | 0.00 | 24.12 | 35.50 | 0.02 | 0.00 | 0.00 | 0.49 | 22-APR-05:02 |
May | 0.111536E+10 | 0.00 | 19.69 | 161230.61 | 30-MAY-11:40 | 0.00 | 23.54 | 25.07 | 0.00 | 0.00 | 0.00 | 0.07 | 30-MAY-11:40 |
June | 0.175444E+10 | 0.00 | 11.54 | 149877.11 | 22-JUN-13:30 | 0.00 | 46.24 | 46.82 | 0.00 | 0.00 | 0.00 | 0.06 | 22-JUN-13:30 |
July | 0.479488E+09 | 0.00 | 7.14 | 75442.28 | 11-JUL-15:25 | 0.00 | 57.42 | 57.63 | 0.00 | 0.00 | 0.00 | 0.03 | 11-JUL-15:25 |
August | 0.193476E+10 | 0.00 | 21.89 | 200089.05 | 24-AUG-18:40 | 0.00 | 50.08 | 51.05 | 0.01 | 0.00 | 0.00 | 0.08 | 24-AUG-18:40 |
September | 34832296.55 | 0.00 | 4.47 | 15600.05 | 14-SEP-19:50 | 0.00 | 47.49 | 47.70 | 0.00 | 0.00 | 0.00 | 0.01 | 14-SEP-19:50 |
October | 0.193473E+10 | 0.00 | 60.49 | 270036.43 | 28-OCT-05:03 | 0.00 | 32.02 | 36.46 | 0.00 | 0.00 | 0.00 | 0.11 | 28-OCT-05:03 |
November | 0.491667E+11 | 0.00 | 288.24 | 1452403.24 | 27-NOV-05:11 | 0.00 | 23.85 | 46.48 | 0.09 | 0.00 | 0.01 | 0.60 | 27-NOV-05:11 |
December | 0.112161E+12 | 0.00 | 437.86 | 1410344.10 | 26-DEC-05:11 | 0.00 | 25.30 | 58.31 | 0.19 | 0.00 | 0.02 | 0.58 | 26-DEC-05:11 |
Annual Sum or Average | 0.591401E+12 | 0.00 | 2251.84 | 0.00 | 34.25 | 48.25 | 0.09 | 0.00 | 0.01 | ||||
Minimum of Months | 34832296.55 | 0.00 | 4.47 | 15600.05 | 0.00 | 23.27 | 25.07 | 0.00 | 0.00 | 0.00 | 0.01 | ||
Maximum of Months | 0.215236E+12 | 0.00 | 502.96 | 1907487.36 | 0.00 | 57.42 | 64.39 | 0.42 | 0.00 | 0.03 | 0.79 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 18.60 | 18.60 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 19.21 | 19.21 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 19.91 | 19.91 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 21.71 | 21.71 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 20.07 | 20.07 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 28.05 | 28.05 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 37.56 | 37.56 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 40.12 | 40.12 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 22.87 | 22.87 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 20.24 | 20.24 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 19.80 | 19.80 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 20.30 | 20.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 24.09 | 24.09 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.60 | 18.60 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.12 | 40.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 7766105.30 | 0.00 | 11.85 | 7766105.30 | 0.00 | 0.00 | 0.00 | 0.00 | 8445.29 | 19-JAN-08:20 | 8445.29 | 19-JAN-08:20 | 0.00 | 0.00 | 0.00 |
February | 8016590.26 | 0.00 | 16.13 | 8016590.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2433.81 | 27-FEB-13:10 | 2433.81 | 27-FEB-13:10 | 0.00 | 0.00 | 0.00 |
March | 0.148115E+10 | 0.00 | 32.28 | 0.144025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73905.68 | 27-MAR-16:00 | 73905.68 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.135049E+11 | 0.00 | 116.35 | 0.135006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 131969.26 | 07-APR-14:40 | 131969.26 | 07-APR-14:40 | 0.00 | 0.00 | 0.00 |
May | 0.398011E+11 | 0.00 | 312.73 | 0.357248E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 191830.31 | 30-MAY-14:10 | 191830.31 | 30-MAY-14:10 | 0.00 | 0.00 | 0.00 |
June | 0.141707E+12 | 0.00 | 502.15 | 0.120108E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 240733.56 | 19-JUN-05:02 | 197348.94 | 22-JUN-15:10 | 0.00 | 0.00 | 0.00 |
July | 0.205624E+12 | 0.00 | 601.76 | 0.178447E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 244769.73 | 10-JUL-04:23 | 212351.72 | 11-JUL-14:03 | 0.00 | 0.00 | 0.00 |
August | 0.210695E+12 | 0.00 | 636.96 | 0.190548E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 235899.75 | 16-AUG-04:33 | 231380.00 | 24-AUG-16:40 | 0.00 | 0.00 | 0.00 |
September | 0.945966E+11 | 0.00 | 421.97 | 0.829802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 229688.31 | 22-SEP-04:12 | 178390.76 | 01-SEP-13:50 | 0.00 | 0.00 | 0.00 |
October | 0.424268E+11 | 0.00 | 245.82 | 0.324564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 187067.26 | 06-OCT-04:12 | 108232.08 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.144595E+10 | 0.00 | 35.48 | 0.133672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64637.48 | 10-NOV-06:02 | 34142.77 | 03-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 1674477.14 | 0.00 | 4.14 | 1674477.14 | 0.00 | 0.00 | 0.00 | 0.00 | 754.09 | 22-DEC-09:50 | 754.09 | 22-DEC-09:50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.751300E+12 | 0.00 | 2937.62 | 0.656560E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1674477.14 | 0.00 | 4.14 | 1674477.14 | 0.00 | 0.00 | 0.00 | 0.00 | 754.09 | 754.09 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.210695E+12 | 0.00 | 636.96 | 0.190548E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 244769.73 | 231380.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 8522055.50 | 0.00 | 12.89 | 8522055.50 | 0.00 | 0.00 | 0.00 | 0.00 | 890.45 | 12-JAN-14:30 | 890.45 | 12-JAN-14:30 | 0.00 | 0.00 | 0.00 |
February | 7011180.15 | 0.00 | 15.68 | 7011180.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1716.00 | 28-FEB-15:00 | 1716.00 | 28-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.938278E+10 | 0.00 | 32.23 | 0.935866E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 486271.98 | 27-MAR-16:00 | 486271.98 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.949777E+11 | 0.00 | 103.67 | 0.949643E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1031171.87 | 07-APR-13:40 | 1031171.87 | 07-APR-13:40 | 0.00 | 0.00 | 0.00 |
May | 0.329684E+12 | 0.00 | 308.01 | 0.296686E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1891420.12 | 30-MAY-14:07 | 1891420.12 | 30-MAY-14:07 | 0.00 | 0.00 | 0.00 |
June | 0.104514E+13 | 0.00 | 447.82 | 0.849947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1991518.90 | 19-JUN-04:12 | 1697263.30 | 01-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.135575E+13 | 0.00 | 471.52 | 0.109472E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2462515.81 | 24-JUL-05:02 | 1819932.76 | 11-JUL-14:07 | 0.00 | 0.00 | 0.00 |
August | 0.134904E+13 | 0.00 | 477.02 | 0.117116E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1926269.70 | 14-AUG-04:12 | 1824774.92 | 24-AUG-16:50 | 0.00 | 0.00 | 0.00 |
September | 0.731540E+12 | 0.00 | 397.89 | 0.627714E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1923893.67 | 07-SEP-04:12 | 1621221.77 | 01-SEP-14:00 | 0.00 | 0.00 | 0.00 |
October | 0.334980E+12 | 0.00 | 240.17 | 0.255271E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1403816.05 | 06-OCT-05:03 | 943681.48 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.105748E+11 | 0.00 | 37.75 | 0.100482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 505463.35 | 10-NOV-06:02 | 260272.81 | 03-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 5796710.99 | 0.00 | 5.55 | 5796710.99 | 0.00 | 0.00 | 0.00 | 0.00 | 1806.04 | 15-DEC-13:20 | 1806.04 | 15-DEC-13:20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.526110E+13 | 0.00 | 2550.19 | 0.440989E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5796710.99 | 0.00 | 5.55 | 5796710.99 | 0.00 | 0.00 | 0.00 | 0.00 | 890.45 | 890.45 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.135575E+13 | 0.00 | 477.02 | 0.117116E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2462515.81 | 1891420.12 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 13104266.75 | 0.00 | 15.83 | 13104266.75 | 0.00 | 0.00 | 0.00 | 0.00 | 2581.37 | 15-JAN-11:00 | 2581.37 | 15-JAN-11:00 | 0.00 | 0.00 | 0.00 |
February | 9473899.31 | 0.00 | 18.12 | 9473899.31 | 0.00 | 0.00 | 0.00 | 0.00 | 704.07 | 09-FEB-11:30 | 704.07 | 09-FEB-11:30 | 0.00 | 0.00 | 0.00 |
March | 0.743436E+09 | 0.00 | 32.06 | 0.743301E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 41780.88 | 27-MAR-16:00 | 41780.88 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.958783E+10 | 0.00 | 106.68 | 0.958783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 114835.87 | 07-APR-14:50 | 114835.87 | 07-APR-14:50 | 0.00 | 0.00 | 0.00 |
May | 0.343775E+11 | 0.00 | 301.02 | 0.312590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 196954.24 | 30-MAY-13:37 | 196954.24 | 30-MAY-13:37 | 0.00 | 0.00 | 0.00 |
June | 0.112788E+12 | 0.00 | 445.97 | 0.929521E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 214437.41 | 19-JUN-04:12 | 193462.67 | 22-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.150235E+12 | 0.00 | 473.13 | 0.122836E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 255018.49 | 24-JUL-05:02 | 180187.25 | 11-JUL-15:45 | 0.00 | 0.00 | 0.00 |
August | 0.148347E+12 | 0.00 | 479.31 | 0.130125E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 231460.53 | 17-AUG-03:02 | 228299.56 | 24-AUG-16:35 | 0.00 | 0.00 | 0.00 |
September | 0.748297E+11 | 0.00 | 392.78 | 0.642595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 196382.23 | 01-SEP-04:12 | 173981.38 | 01-SEP-14:10 | 0.00 | 0.00 | 0.00 |
October | 0.314840E+11 | 0.00 | 231.21 | 0.239865E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 140775.17 | 06-OCT-05:03 | 106980.84 | 04-OCT-14:50 | 0.00 | 0.00 | 0.00 |
November | 0.804963E+09 | 0.00 | 36.90 | 0.764048E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20096.55 | 03-NOV-14:00 | 20096.55 | 03-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 9382863.50 | 0.00 | 13.86 | 9382863.50 | 0.00 | 0.00 | 0.00 | 0.00 | 634.79 | 14-DEC-10:10 | 634.79 | 14-DEC-10:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.563229E+12 | 0.00 | 2546.86 | 0.476545E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9382863.50 | 0.00 | 13.86 | 9382863.50 | 0.00 | 0.00 | 0.00 | 0.00 | 634.79 | 634.79 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.150235E+12 | 0.00 | 479.31 | 0.130125E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 255018.49 | 228299.56 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.270904E+09 | 0.00 | 12.64 | 0.146497E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40491.33 | 24-JAN-07:12 | 17866.40 | 24-JAN-07:12 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 0.211246E+10 | 0.00 | 52.10 | 0.209198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47632.77 | 27-MAR-16:00 | 47632.77 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.730891E+10 | 0.00 | 87.14 | 0.724891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74161.58 | 10-APR-06:23 | 72004.56 | 07-APR-13:50 | 0.00 | 0.00 | 0.00 |
May | 0.233540E+11 | 0.00 | 215.11 | 0.192753E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 112318.80 | 31-MAY-10:30 | 91541.61 | 31-MAY-10:00 | 0.00 | 0.00 | 0.00 |
June | 0.467177E+11 | 0.00 | 202.85 | 0.373683E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 167129.99 | 27-JUN-16:00 | 104548.75 | 21-JUN-06:11 | 0.00 | 0.00 | 0.00 |
July | 0.253463E+11 | 0.00 | 64.00 | 0.196246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 159622.75 | 24-JUL-08:20 | 100288.18 | 11-JUL-13:53 | 0.00 | 0.00 | 0.00 |
August | 0.339721E+11 | 0.00 | 109.33 | 0.300868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 138447.35 | 31-AUG-07:20 | 112230.47 | 25-AUG-14:47 | 0.00 | 0.00 | 0.00 |
September | 0.371656E+11 | 0.00 | 208.23 | 0.326743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 141366.46 | 22-SEP-11:20 | 94923.39 | 05-SEP-12:00 | 0.00 | 0.00 | 0.00 |
October | 0.298458E+11 | 0.00 | 226.91 | 0.229451E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 114354.95 | 06-OCT-09:01 | 65151.88 | 04-OCT-13:04 | 0.00 | 0.00 | 0.00 |
November | 0.750686E+09 | 0.00 | 24.55 | 0.580024E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 92407.12 | 10-NOV-07:25 | 35972.21 | 10-NOV-07:25 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.206844E+12 | 0.00 | 1202.85 | 0.172042E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.467177E+11 | 0.00 | 226.91 | 0.373683E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 167129.99 | 112230.47 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.571647E+10 | 0.440394E+10 | 703.08 | 0.571638E+10 | 86245.99 | 0.00 | 0.02 | 19-JAN-14:00 | 0.01 | 18-JAN-08:65 | 3756.02 | 19-JAN-14:00 | 3756.02 | 19-JAN-14:00 | 25.09 | 18-JAN-18:40 | 2453.77 | 30-JAN-13:00 | 0.00 |
February | 0.106820E+11 | 0.560937E+10 | 672.00 | 0.106765E+11 | 5545692.69 | 0.00 | 0.03 | 02-FEB-16:30 | 0.01 | 28-FEB-16:00 | 5097.29 | 14-FEB-17:35 | 5097.29 | 14-FEB-17:35 | 59.38 | 28-FEB-17:30 | 3312.53 | 02-FEB-16:30 | 0.00 |
March | 0.144030E+11 | 0.709160E+10 | 696.73 | 0.131296E+11 | 0.127342E+10 | 0.00 | 0.51 | 27-MAR-16:00 | 0.01 | 26-MAR-16:07 | 216277.59 | 27-MAR-16:00 | 170667.88 | 27-MAR-16:00 | 71117.73 | 27-MAR-13:00 | 63014.36 | 27-MAR-16:00 | 0.00 |
April | 0.994331E+11 | 0.314273E+11 | 609.51 | 0.845951E+11 | 0.148380E+11 | 0.00 | 0.91 | 07-APR-13:00 | 0.01 | 16-APR-01:10 | 398806.65 | 07-APR-13:00 | 398806.65 | 07-APR-13:00 | 137578.35 | 09-APR-10:53 | 129746.19 | 07-APR-13:00 | 0.00 |
May | 0.223153E+11 | 0.986831E+10 | 456.88 | 0.216897E+11 | 0.625590E+09 | 0.00 | 0.52 | 30-MAY-13:23 | 0.01 | 17-MAY-06:15 | 218637.10 | 31-MAY-23:20 | 216843.95 | 31-MAY-23:20 | 35140.97 | 31-MAY-10:10 | 74695.71 | 30-MAY-13:23 | 0.00 |
June | 0.368175E+12 | 0.110456E+12 | 632.39 | 0.350388E+12 | 0.177867E+11 | 0.00 | 0.71 | 01-JUN-14:55 | 0.01 | 01-JUN-22:43 | 349662.23 | 21-JUN-16:40 | 308778.18 | 30-JUN-24:00 | 130156.78 | 21-JUN-16:30 | 103559.02 | 01-JUN-14:55 | 0.00 |
July | 0.848894E+12 | 0.259661E+12 | 744.00 | 0.832319E+12 | 0.165750E+11 | 0.00 | 0.88 | 31-JUL-24:00 | 0.29 | 11-JUL-04:54 | 401666.44 | 31-JUL-23:55 | 401666.44 | 31-JUL-23:55 | 141703.85 | 12-JUL-02:55 | 125486.45 | 07-JUL-12:00 | 0.00 |
August | 0.102620E+13 | 0.316006E+12 | 744.00 | 0.985235E+12 | 0.409648E+11 | 0.00 | 1.00 | 19-AUG-13:40 | 0.18 | 08-AUG-04:53 | 453810.05 | 31-AUG-06:11 | 447545.89 | 22-AUG-14:42 | 186024.35 | 31-AUG-06:10 | 159024.74 | 24-AUG-15:30 | 0.00 |
September | 0.939076E+11 | 0.312670E+11 | 460.19 | 0.894328E+11 | 0.447482E+10 | 0.00 | 0.64 | 01-SEP-14:00 | 0.01 | 25-SEP-04:55 | 266411.91 | 01-SEP-14:00 | 266411.91 | 01-SEP-14:00 | 88960.04 | 13-SEP-11:00 | 95888.14 | 01-SEP-14:00 | 0.00 |
October | 0.318958E+11 | 0.122205E+11 | 505.75 | 0.231142E+11 | 0.878162E+10 | 0.00 | 0.62 | 25-OCT-10:50 | 0.01 | 16-OCT-06:25 | 286823.85 | 25-OCT-10:50 | 224811.53 | 25-OCT-11:00 | 85118.17 | 25-OCT-10:40 | 82317.95 | 25-OCT-10:50 | 0.00 |
November | 0.107007E+11 | 0.593510E+10 | 623.91 | 0.104571E+11 | 0.243646E+09 | 0.00 | 0.14 | 03-NOV-14:00 | 0.01 | 03-NOV-23:10 | 46168.87 | 03-NOV-14:00 | 46168.87 | 03-NOV-14:00 | 7110.84 | 04-NOV-13:00 | 14537.96 | 03-NOV-14:00 | 0.00 |
December | 0.141978E+11 | 0.737782E+10 | 737.58 | 0.139864E+11 | 0.211327E+09 | 0.00 | 0.03 | 21-DEC-15:20 | 0.01 | 25-DEC-12:10 | 5969.57 | 26-DEC-00:50 | 5635.48 | 19-DEC-22:25 | 558.64 | 04-DEC-05:11 | 3719.70 | 21-DEC-15:20 | 0.00 |
Annual Sum or Average | 0.254652E+13 | 0.801323E+12 | 7586.04 | 0.244074E+13 | 0.105781E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.571647E+10 | 0.440394E+10 | 456.88 | 0.571638E+10 | 86245.99 | 0.00 | 0.02 | 0.01 | 3756.02 | 3756.02 | 25.09 | 2453.77 | 0.00 | ||||||
Maximum of Months | 0.102620E+13 | 0.316006E+12 | 744.00 | 0.985235E+12 | 0.409648E+11 | 0.00 | 1.00 | 0.29 | 453810.05 | 447545.89 | 186024.35 | 159024.74 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.350401E+10 | 0.944903E+09 | 744.00 | 0.349878E+10 | 5227406.44 | 0.00 | 0.30 | 16-JAN-16:25 | 0.02 | 02-JAN-07:03 | 2263.67 | 29-JAN-16:40 | 2263.67 | 29-JAN-16:40 | 100.78 | 24-JAN-15:20 | 588.02 | 16-JAN-16:25 | 0.00 |
February | 0.816188E+10 | 0.206964E+10 | 672.00 | 0.816188E+10 | -0.0 | 0.00 | 0.54 | 14-FEB-17:00 | 0.29 | 06-FEB-07:03 | 4327.55 | 20-FEB-16:30 | 4327.55 | 20-FEB-16:30 | 0.00 | 24-FEB-16:40 | 1064.71 | 14-FEB-17:00 | 0.00 |
March | 0.150846E+11 | 0.350860E+10 | 744.00 | 0.150735E+11 | 11161967.03 | 0.00 | 0.81 | 31-MAR-24:00 | 0.57 | 01-MAR-07:05 | 7508.80 | 31-MAR-24:00 | 7508.80 | 31-MAR-24:00 | 236.44 | 27-MAR-15:00 | 1677.76 | 27-MAR-16:00 | 0.00 |
April | 0.199108E+11 | 0.442574E+10 | 720.00 | 0.198851E+11 | 25704819.08 | 0.00 | 0.95 | 12-APR-17:40 | 0.30 | 30-APR-24:00 | 8849.80 | 23-APR-17:47 | 8849.80 | 23-APR-17:47 | 257.55 | 27-APR-16:00 | 2478.69 | 07-APR-17:00 | 0.00 |
May | 0.577464E+10 | 0.146319E+10 | 744.00 | 0.567947E+10 | 95172550.85 | 0.00 | 0.48 | 31-MAY-23:20 | 0.19 | 04-MAY-07:00 | 4165.86 | 31-MAY-23:40 | 4093.86 | 31-MAY-24:00 | 281.19 | 18-MAY-15:30 | 1033.24 | 31-MAY-23:20 | 0.00 |
June | 0.111651E+11 | 0.300398E+10 | 720.00 | 0.108439E+11 | 0.321133E+09 | 0.00 | 0.67 | 30-JUN-24:00 | 0.44 | 02-JUN-06:12 | 5949.19 | 30-JUN-24:00 | 5928.03 | 30-JUN-24:00 | 524.36 | 15-JUN-14:00 | 1918.95 | 19-JUN-12:10 | 0.00 |
July | 0.169732E+11 | 0.499465E+10 | 744.00 | 0.164896E+11 | 0.483666E+09 | 0.00 | 0.88 | 31-JUL-24:00 | 0.67 | 01-JUL-06:10 | 7872.87 | 31-JUL-23:55 | 7870.43 | 31-JUL-24:00 | 619.71 | 20-JUL-15:00 | 2469.85 | 10-JUL-15:00 | 0.00 |
August | 0.219600E+11 | 0.635830E+10 | 744.00 | 0.215746E+11 | 0.385378E+09 | 0.00 | 1.00 | 01-AUG-13:20 | 0.31 | 31-AUG-24:00 | 9092.38 | 31-AUG-17:40 | 8757.30 | 13-AUG-18:02 | 619.24 | 03-AUG-15:00 | 3105.84 | 24-AUG-15:40 | 0.00 |
September | 0.601598E+10 | 0.160580E+10 | 720.00 | 0.581345E+10 | 0.202539E+09 | 0.00 | 0.45 | 30-SEP-24:00 | 0.20 | 30-SEP-06:55 | 3944.34 | 30-SEP-24:00 | 3944.34 | 30-SEP-24:00 | 452.95 | 07-SEP-15:00 | 1016.13 | 14-SEP-14:00 | 0.00 |
October | 0.108835E+11 | 0.259710E+10 | 744.00 | 0.107371E+11 | 0.146378E+09 | 0.00 | 0.63 | 31-OCT-24:00 | 0.40 | 28-OCT-06:55 | 5701.41 | 31-OCT-24:00 | 5700.97 | 31-OCT-24:00 | 355.19 | 24-OCT-16:00 | 1351.17 | 04-OCT-16:00 | 0.00 |
November | 0.146333E+11 | 0.336076E+10 | 720.00 | 0.146161E+11 | 17205523.96 | 0.00 | 0.72 | 23-NOV-15:55 | 0.58 | 01-NOV-06:15 | 6301.10 | 03-NOV-16:00 | 6301.10 | 03-NOV-16:00 | 248.84 | 10-NOV-10:20 | 1435.71 | 23-NOV-15:55 | 0.00 |
December | 0.198374E+11 | 0.454555E+10 | 744.00 | 0.198374E+11 | 0.00 | 0.00 | 0.95 | 03-DEC-15:53 | 0.78 | 30-DEC-08:00 | 8255.71 | 17-DEC-15:55 | 8255.71 | 17-DEC-15:55 | 0.00 | 04-DEC-18:40 | 1886.19 | 03-DEC-15:53 | 0.00 |
Annual Sum or Average | 0.153904E+12 | 0.388782E+11 | 8760.00 | 0.152211E+12 | 0.169357E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.350401E+10 | 0.944903E+09 | 672.00 | 0.349878E+10 | -0.0 | 0.00 | 0.30 | 0.02 | 2263.67 | 2263.67 | 0.00 | 588.02 | 0.00 | ||||||
Maximum of Months | 0.219600E+11 | 0.635830E+10 | 744.00 | 0.215746E+11 | 0.483666E+09 | 0.00 | 1.00 | 0.78 | 9092.38 | 8849.80 | 619.71 | 3105.84 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.114559E+11 | 0.330989E+10 | 548.83 | 0.114141E+11 | 41841375.90 | 0.00 | 0.27 | 20-JAN-16:55 | 0.00 | 01-JAN-00:02 | 19097.15 | 20-JAN-16:30 | 19097.15 | 20-JAN-16:30 | 876.13 | 24-JAN-15:20 | 5935.57 | 20-JAN-16:55 | 0.00 |
February | 0.582081E+11 | 0.151522E+11 | 672.00 | 0.582081E+11 | 0.00 | 0.00 | 0.51 | 02-FEB-16:30 | 0.13 | 06-FEB-07:03 | 38454.48 | 22-FEB-17:00 | 38454.48 | 22-FEB-17:00 | 0.00 | 06-FEB-03:12 | 10609.55 | 02-FEB-16:30 | 0.00 |
March | 0.128614E+12 | 0.303258E+11 | 744.00 | 0.128501E+12 | 0.112884E+09 | 0.00 | 0.75 | 31-MAR-23:40 | 0.47 | 01-MAR-07:05 | 66083.64 | 31-MAR-23:40 | 66083.64 | 31-MAR-23:40 | 2336.50 | 27-MAR-15:00 | 15682.56 | 27-MAR-17:00 | 0.00 |
April | 0.179779E+12 | 0.403022E+11 | 720.00 | 0.179520E+12 | 0.258535E+09 | 0.00 | 0.95 | 12-APR-17:40 | 0.21 | 30-APR-24:00 | 81522.46 | 09-APR-17:32 | 81457.70 | 09-APR-17:34 | 2540.98 | 27-APR-16:00 | 23583.20 | 07-APR-17:00 | 0.00 |
May | 0.497376E+11 | 0.127304E+11 | 744.00 | 0.488021E+11 | 0.935494E+09 | 0.00 | 0.47 | 31-MAY-23:20 | 0.13 | 01-MAY-06:05 | 39417.34 | 31-MAY-23:30 | 38650.71 | 31-MAY-24:00 | 2780.66 | 18-MAY-15:30 | 9788.85 | 31-MAY-23:20 | 0.00 |
June | 0.104110E+12 | 0.281048E+11 | 720.00 | 0.100922E+12 | 0.318862E+10 | 0.00 | 0.66 | 30-JUN-24:00 | 0.41 | 07-JUN-06:10 | 55799.77 | 30-JUN-24:00 | 55586.20 | 30-JUN-24:00 | 5201.77 | 15-JUN-14:00 | 18219.70 | 19-JUN-12:10 | 0.00 |
July | 0.159775E+12 | 0.471184E+11 | 744.00 | 0.154959E+12 | 0.481593E+10 | 0.00 | 0.88 | 31-JUL-24:00 | 0.65 | 01-JUL-06:10 | 74822.06 | 31-JUL-23:55 | 74789.48 | 31-JUL-24:00 | 6166.06 | 20-JUL-15:00 | 23340.64 | 07-JUL-12:10 | 0.00 |
August | 0.207723E+12 | 0.602672E+11 | 744.00 | 0.203874E+12 | 0.384975E+10 | 0.00 | 1.00 | 01-AUG-15:10 | 0.29 | 31-AUG-24:00 | 87095.58 | 31-AUG-17:30 | 83424.02 | 31-AUG-17:30 | 6244.40 | 03-AUG-15:00 | 29763.20 | 24-AUG-15:40 | 0.00 |
September | 0.524012E+11 | 0.141284E+11 | 720.00 | 0.504105E+11 | 0.199069E+10 | 0.00 | 0.43 | 30-SEP-23:40 | 0.16 | 30-SEP-06:55 | 35900.83 | 30-SEP-23:30 | 35900.83 | 30-SEP-23:30 | 4476.94 | 07-SEP-15:00 | 9519.48 | 14-SEP-14:00 | 0.00 |
October | 0.957852E+11 | 0.230466E+11 | 744.00 | 0.943321E+11 | 0.145315E+10 | 0.00 | 0.58 | 31-OCT-24:00 | 0.34 | 28-OCT-06:55 | 49549.90 | 31-OCT-24:00 | 49529.18 | 31-OCT-24:00 | 3520.87 | 24-OCT-16:00 | 12819.43 | 04-OCT-16:00 | 0.00 |
November | 0.122289E+12 | 0.284968E+11 | 720.00 | 0.122117E+12 | 0.172328E+09 | 0.00 | 0.68 | 03-NOV-16:00 | 0.46 | 24-NOV-07:03 | 58948.96 | 03-NOV-16:00 | 58948.96 | 03-NOV-16:00 | 2494.17 | 10-NOV-10:20 | 13147.70 | 03-NOV-16:00 | 0.00 |
December | 0.166011E+12 | 0.387379E+11 | 744.00 | 0.166011E+12 | -0.0 | 0.00 | 0.88 | 15-DEC-16:10 | 0.63 | 31-DEC-23:53 | 73813.74 | 08-DEC-16:10 | 73813.74 | 08-DEC-16:10 | 0.00 | 12-DEC-21:00 | 16737.31 | 15-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.133589E+13 | 0.341721E+12 | 8564.83 | 0.131907E+13 | 0.168192E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.114559E+11 | 0.330989E+10 | 548.83 | 0.114141E+11 | -0.0 | 0.00 | 0.27 | 0.00 | 19097.15 | 19097.15 | 0.00 | 5935.57 | 0.00 | ||||||
Maximum of Months | 0.207723E+12 | 0.602672E+11 | 744.00 | 0.203874E+12 | 0.481593E+10 | 0.00 | 1.00 | 0.65 | 87095.58 | 83424.02 | 6244.40 | 29763.20 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.448234E+09 | 0.133606E+09 | 277.08 | 0.444989E+09 | 3245202.85 | 0.00 | 0.24 | 19-JAN-16:30 | 0.00 | 01-JAN-00:02 | 1858.53 | 19-JAN-16:30 | 1858.53 | 19-JAN-16:30 | 79.29 | 24-JAN-15:20 | 474.86 | 19-JAN-16:30 | 0.00 |
February | 0.418377E+10 | 0.111308E+10 | 662.22 | 0.418377E+10 | 0.00 | 0.00 | 0.48 | 02-FEB-16:50 | 0.00 | 05-FEB-17:53 | 3747.35 | 22-FEB-17:00 | 3747.35 | 22-FEB-17:00 | 0.00 | 12-FEB-21:27 | 936.44 | 02-FEB-16:50 | 0.00 |
March | 0.115818E+11 | 0.276163E+10 | 744.00 | 0.115708E+11 | 11075574.56 | 0.00 | 0.71 | 27-MAR-17:00 | 0.37 | 20-MAR-06:05 | 6206.97 | 27-MAR-17:20 | 6116.60 | 31-MAR-23:20 | 234.51 | 27-MAR-15:00 | 1571.66 | 27-MAR-17:00 | 0.00 |
April | 0.171380E+11 | 0.387412E+10 | 720.00 | 0.171123E+11 | 25678752.49 | 0.00 | 0.93 | 12-APR-17:40 | 0.13 | 30-APR-24:00 | 8228.34 | 09-APR-17:21 | 8217.91 | 09-APR-17:23 | 254.69 | 27-APR-16:00 | 2390.58 | 07-APR-17:00 | 0.00 |
May | 0.464268E+10 | 0.119926E+10 | 743.83 | 0.455010E+10 | 92579765.35 | 0.00 | 0.46 | 31-MAY-23:20 | 0.00 | 01-MAY-04:35 | 3912.03 | 31-MAY-23:30 | 3832.36 | 31-MAY-24:00 | 278.63 | 18-MAY-15:30 | 973.92 | 31-MAY-23:20 | 0.00 |
June | 0.104135E+11 | 0.281973E+10 | 720.00 | 0.100946E+11 | 0.318874E+09 | 0.00 | 0.64 | 30-JUN-24:00 | 0.37 | 03-JUN-06:50 | 5506.02 | 30-JUN-24:00 | 5484.23 | 30-JUN-24:00 | 522.15 | 15-JUN-14:00 | 1864.23 | 19-JUN-12:10 | 0.00 |
July | 0.160887E+11 | 0.475271E+10 | 744.00 | 0.156071E+11 | 0.481549E+09 | 0.00 | 0.86 | 31-JUL-24:00 | 0.63 | 01-JUL-06:10 | 7491.63 | 31-JUL-23:55 | 7488.26 | 31-JUL-24:00 | 617.82 | 20-JUL-15:00 | 2374.76 | 10-JUL-15:00 | 0.00 |
August | 0.208430E+11 | 0.606323E+10 | 744.00 | 0.204583E+11 | 0.384768E+09 | 0.00 | 1.00 | 01-AUG-15:30 | 0.28 | 31-AUG-24:00 | 8798.99 | 31-AUG-17:20 | 8459.26 | 13-AUG-17:15 | 628.49 | 03-AUG-15:00 | 3029.70 | 24-AUG-15:40 | 0.00 |
September | 0.501868E+10 | 0.136437E+10 | 720.00 | 0.482002E+10 | 0.198660E+09 | 0.00 | 0.39 | 30-SEP-23:20 | 0.10 | 30-SEP-06:55 | 3292.22 | 30-SEP-23:20 | 3292.22 | 30-SEP-23:20 | 450.76 | 07-SEP-15:00 | 983.09 | 14-SEP-14:00 | 0.00 |
October | 0.877952E+10 | 0.213003E+10 | 744.00 | 0.863478E+10 | 0.144734E+09 | 0.00 | 0.57 | 04-OCT-16:00 | 0.24 | 29-OCT-07:20 | 4814.74 | 04-OCT-16:00 | 4502.19 | 31-OCT-23:30 | 352.63 | 24-OCT-16:00 | 1303.79 | 04-OCT-16:00 | 0.00 |
November | 0.107186E+11 | 0.253018E+10 | 720.00 | 0.107016E+11 | 17045972.15 | 0.00 | 0.67 | 03-NOV-16:00 | 0.30 | 24-NOV-04:01 | 5883.41 | 03-NOV-16:00 | 5883.41 | 03-NOV-16:00 | 250.31 | 10-NOV-10:20 | 1315.49 | 03-NOV-16:00 | 0.00 |
December | 0.146813E+11 | 0.348178E+10 | 744.00 | 0.146813E+11 | -0.0 | 0.00 | 0.84 | 21-DEC-16:10 | 0.47 | 31-DEC-23:55 | 7210.15 | 08-DEC-16:10 | 7210.15 | 08-DEC-16:10 | 0.00 | 31-DEC-19:55 | 1641.10 | 21-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.124538E+12 | 0.322238E+11 | 8283.14 | 0.122860E+12 | 0.167821E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.448234E+09 | 0.133606E+09 | 277.08 | 0.444989E+09 | -0.0 | 0.00 | 0.24 | 0.00 | 1858.53 | 1858.53 | 0.00 | 474.86 | 0.00 | ||||||
Maximum of Months | 0.208430E+11 | 0.606323E+10 | 744.00 | 0.204583E+11 | 0.481549E+09 | 0.00 | 1.00 | 0.63 | 8798.99 | 8459.26 | 628.49 | 3029.70 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 116.83 | 0.00 | 116.83 | 2.01 | 751.56 | 0.00 | 0.00 | 0.00 |
February | 159.88 | 0.00 | 159.88 | 8.05 | 773.52 | 0.00 | 0.00 | 0.00 |
March | 221.71 | 0.00 | 221.71 | 59.76 | 532.72 | 0.00 | 0.00 | 0.00 |
April | 266.31 | 0.76 | 265.55 | 146.60 | 379.39 | 0.00 | 0.00 | 0.00 |
May | 353.31 | 11.77 | 341.53 | 318.35 | 217.67 | 0.00 | 0.00 | 0.00 |
June | 374.68 | 20.13 | 354.54 | 455.17 | 120.64 | 0.00 | 0.00 | 0.00 |
July | 362.09 | 13.09 | 349.00 | 504.84 | 72.32 | 0.00 | 0.00 | 0.00 |
August | 320.79 | 3.82 | 316.98 | 440.01 | 95.32 | 0.00 | 0.00 | 0.00 |
September | 241.83 | 0.05 | 241.78 | 249.46 | 186.72 | 0.00 | 0.00 | 0.00 |
October | 209.28 | 0.00 | 209.28 | 140.40 | 342.76 | 0.00 | 0.00 | 0.00 |
November | 146.79 | 0.00 | 146.79 | 27.54 | 557.45 | 0.00 | 0.00 | 0.00 |
December | 101.91 | 0.00 | 101.91 | 1.05 | 731.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 240.08 | 4.16 | 235.92 | 197.39 | 394.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.91 | 0.00 | 101.91 | 1.05 | 72.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 374.68 | 20.13 | 354.54 | 504.84 | 773.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 116.83 | 0.00 | 116.83 | 2.01 | 751.56 | 0.00 | 0.00 | 0.00 |
February | 159.88 | 0.00 | 159.88 | 8.05 | 773.52 | 0.00 | 0.00 | 0.00 |
March | 221.71 | 0.00 | 221.71 | 59.76 | 532.72 | 0.00 | 0.00 | 0.00 |
April | 266.31 | 0.76 | 265.55 | 146.60 | 379.39 | 0.00 | 0.00 | 0.00 |
May | 353.31 | 11.77 | 341.53 | 318.35 | 217.67 | 0.00 | 0.00 | 0.00 |
June | 374.68 | 20.13 | 354.54 | 455.17 | 120.63 | 0.00 | 0.00 | 0.00 |
July | 362.09 | 13.09 | 348.99 | 504.84 | 72.32 | 0.00 | 0.00 | 0.00 |
August | 320.79 | 3.82 | 316.98 | 440.01 | 95.32 | 0.00 | 0.00 | 0.00 |
September | 241.83 | 0.05 | 241.78 | 249.46 | 186.72 | 0.00 | 0.00 | 0.00 |
October | 209.28 | 0.00 | 209.28 | 140.40 | 342.76 | 0.00 | 0.00 | 0.00 |
November | 146.79 | 0.00 | 146.79 | 27.54 | 557.45 | 0.00 | 0.00 | 0.00 |
December | 101.91 | 0.00 | 101.91 | 1.05 | 731.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 240.08 | 4.16 | 235.92 | 197.39 | 394.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.91 | 0.00 | 101.91 | 1.05 | 72.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 374.68 | 20.13 | 354.54 | 504.84 | 773.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 116.83 | 0.00 | 116.83 | 2.01 | 751.56 | 0.00 | 0.00 | 0.00 |
February | 159.88 | 0.00 | 159.88 | 8.05 | 773.52 | 0.00 | 0.00 | 0.00 |
March | 221.71 | 0.00 | 221.71 | 59.76 | 532.72 | 0.00 | 0.00 | 0.00 |
April | 266.31 | 0.76 | 265.55 | 146.60 | 379.39 | 0.00 | 0.00 | 0.00 |
May | 353.31 | 11.77 | 341.53 | 318.35 | 217.67 | 0.00 | 0.00 | 0.00 |
June | 374.68 | 20.13 | 354.54 | 455.17 | 120.64 | 0.00 | 0.00 | 0.00 |
July | 362.09 | 13.09 | 349.00 | 504.84 | 72.32 | 0.00 | 0.00 | 0.00 |
August | 320.79 | 3.82 | 316.98 | 440.01 | 95.32 | 0.00 | 0.00 | 0.00 |
September | 241.83 | 0.05 | 241.78 | 249.46 | 186.72 | 0.00 | 0.00 | 0.00 |
October | 209.28 | 0.00 | 209.28 | 140.40 | 342.76 | 0.00 | 0.00 | 0.00 |
November | 146.79 | 0.00 | 146.79 | 27.54 | 557.45 | 0.00 | 0.00 | 0.00 |
December | 101.91 | 0.00 | 101.91 | 1.05 | 731.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 240.08 | 4.16 | 235.92 | 197.39 | 394.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.91 | 0.00 | 101.91 | 1.05 | 72.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 374.68 | 20.13 | 354.54 | 504.84 | 773.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 116.83 | 0.00 | 116.83 | 2.01 | 751.56 | 0.00 | 0.00 | 0.00 |
February | 159.88 | 0.00 | 159.88 | 8.05 | 773.52 | 0.00 | 0.00 | 0.00 |
March | 221.71 | 0.00 | 221.71 | 59.76 | 532.72 | 0.00 | 0.00 | 0.00 |
April | 266.31 | 0.76 | 265.55 | 146.60 | 379.39 | 0.00 | 0.00 | 0.00 |
May | 353.31 | 11.77 | 341.53 | 318.35 | 217.67 | 0.00 | 0.00 | 0.00 |
June | 374.68 | 20.13 | 354.54 | 455.17 | 120.63 | 0.00 | 0.00 | 0.00 |
July | 362.09 | 13.09 | 348.99 | 504.84 | 72.32 | 0.00 | 0.00 | 0.00 |
August | 320.79 | 3.82 | 316.98 | 440.01 | 95.32 | 0.00 | 0.00 | 0.00 |
September | 241.83 | 0.05 | 241.78 | 249.46 | 186.72 | 0.00 | 0.00 | 0.00 |
October | 209.28 | 0.00 | 209.28 | 140.40 | 342.76 | 0.00 | 0.00 | 0.00 |
November | 146.79 | 0.00 | 146.79 | 27.54 | 557.45 | 0.00 | 0.00 | 0.00 |
December | 101.91 | 0.00 | 101.91 | 1.05 | 731.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 240.08 | 4.16 | 235.92 | 197.39 | 394.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.91 | 0.00 | 101.91 | 1.05 | 72.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 374.68 | 20.13 | 354.54 | 504.84 | 773.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 116.83 | 0.00 | 116.83 | 2.01 | 751.52 | 0.00 | 0.00 | 0.00 |
February | 159.87 | 0.00 | 159.87 | 8.05 | 773.49 | 0.00 | 0.00 | 0.00 |
March | 221.70 | 0.00 | 221.70 | 59.76 | 532.70 | 0.00 | 0.00 | 0.00 |
April | 266.30 | 0.76 | 265.54 | 146.60 | 379.37 | 0.00 | 0.00 | 0.00 |
May | 353.29 | 11.77 | 341.52 | 318.34 | 217.67 | 0.00 | 0.00 | 0.00 |
June | 374.66 | 20.13 | 354.53 | 455.15 | 120.63 | 0.00 | 0.00 | 0.00 |
July | 362.07 | 13.09 | 348.98 | 504.82 | 72.32 | 0.00 | 0.00 | 0.00 |
August | 320.78 | 3.82 | 316.96 | 439.99 | 95.32 | 0.00 | 0.00 | 0.00 |
September | 241.82 | 0.05 | 241.77 | 249.45 | 186.72 | 0.00 | 0.00 | 0.00 |
October | 209.27 | 0.00 | 209.27 | 140.40 | 342.75 | 0.00 | 0.00 | 0.00 |
November | 146.79 | 0.00 | 146.79 | 27.54 | 557.43 | 0.00 | 0.00 | 0.00 |
December | 101.90 | 0.00 | 101.90 | 1.05 | 731.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 240.07 | 4.16 | 235.91 | 197.38 | 394.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.90 | 0.00 | 101.90 | 1.05 | 72.32 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 374.66 | 20.13 | 354.53 | 504.82 | 773.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 271.17 | 108.72 | 162.45 | 151.95 | 767.05 | 0.00 | 0.00 | 0.00 |
February | 420.52 | 196.17 | 224.35 | 274.35 | 762.75 | 0.00 | 0.00 | 0.00 |
March | 536.45 | 228.16 | 308.29 | 449.01 | 549.70 | 0.00 | 0.00 | 0.00 |
April | 643.78 | 281.99 | 361.78 | 635.14 | 387.67 | 0.00 | 0.00 | 0.00 |
May | 780.77 | 312.04 | 468.73 | 895.62 | 241.53 | 0.00 | 0.00 | 0.00 |
June | 723.61 | 261.94 | 461.67 | 940.59 | 132.00 | 0.00 | 0.00 | 0.00 |
July | 726.77 | 262.27 | 464.50 | 1023.57 | 74.79 | 0.00 | 0.00 | 0.00 |
August | 818.37 | 369.00 | 449.36 | 1147.55 | 97.90 | 0.00 | 0.00 | 0.00 |
September | 610.34 | 273.84 | 336.51 | 754.12 | 196.74 | 0.00 | 0.00 | 0.00 |
October | 553.32 | 250.78 | 302.54 | 602.26 | 358.02 | 0.00 | 0.00 | 0.00 |
November | 342.19 | 131.40 | 210.78 | 254.74 | 559.20 | 0.00 | 0.00 | 0.00 |
December | 266.58 | 125.17 | 141.41 | 165.09 | 721.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 558.71 | 233.72 | 324.99 | 610.15 | 402.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 266.58 | 108.72 | 141.41 | 151.95 | 74.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 818.37 | 369.00 | 468.73 | 1147.55 | 767.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 271.17 | 108.72 | 162.45 | 151.95 | 767.05 | 0.00 | 0.00 | 0.00 |
February | 420.52 | 196.17 | 224.35 | 274.35 | 762.75 | 0.00 | 0.00 | 0.00 |
March | 536.45 | 228.16 | 308.29 | 449.01 | 549.70 | 0.00 | 0.00 | 0.00 |
April | 643.78 | 281.99 | 361.78 | 635.14 | 387.67 | 0.00 | 0.00 | 0.00 |
May | 780.77 | 312.04 | 468.73 | 895.62 | 241.53 | 0.00 | 0.00 | 0.00 |
June | 723.61 | 261.94 | 461.67 | 940.59 | 132.00 | 0.00 | 0.00 | 0.00 |
July | 726.77 | 262.27 | 464.50 | 1023.57 | 74.79 | 0.00 | 0.00 | 0.00 |
August | 818.37 | 369.00 | 449.36 | 1147.55 | 97.90 | 0.00 | 0.00 | 0.00 |
September | 610.34 | 273.84 | 336.51 | 754.12 | 196.74 | 0.00 | 0.00 | 0.00 |
October | 553.32 | 250.78 | 302.54 | 602.26 | 358.02 | 0.00 | 0.00 | 0.00 |
November | 342.19 | 131.40 | 210.78 | 254.74 | 559.20 | 0.00 | 0.00 | 0.00 |
December | 266.58 | 125.17 | 141.41 | 165.09 | 721.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 558.71 | 233.72 | 324.99 | 610.15 | 402.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 266.58 | 108.72 | 141.41 | 151.95 | 74.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 818.37 | 369.00 | 468.73 | 1147.55 | 767.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 271.16 | 108.71 | 162.45 | 151.95 | 767.04 | 0.00 | 0.00 | 0.00 |
February | 420.51 | 196.17 | 224.34 | 274.35 | 762.73 | 0.00 | 0.00 | 0.00 |
March | 536.44 | 228.15 | 308.29 | 449.01 | 549.69 | 0.00 | 0.00 | 0.00 |
April | 643.77 | 281.99 | 361.78 | 635.13 | 387.67 | 0.00 | 0.00 | 0.00 |
May | 780.75 | 312.04 | 468.72 | 895.60 | 241.52 | 0.00 | 0.00 | 0.00 |
June | 723.59 | 261.94 | 461.66 | 940.57 | 132.00 | 0.00 | 0.00 | 0.00 |
July | 726.76 | 262.27 | 464.49 | 1023.55 | 74.79 | 0.00 | 0.00 | 0.00 |
August | 818.35 | 368.99 | 449.36 | 1147.53 | 97.90 | 0.00 | 0.00 | 0.00 |
September | 610.33 | 273.83 | 336.50 | 754.11 | 196.74 | 0.00 | 0.00 | 0.00 |
October | 553.31 | 250.78 | 302.53 | 602.25 | 358.02 | 0.00 | 0.00 | 0.00 |
November | 342.18 | 131.40 | 210.78 | 254.74 | 559.19 | 0.00 | 0.00 | 0.00 |
December | 266.58 | 125.17 | 141.41 | 165.08 | 721.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 558.70 | 233.72 | 324.98 | 610.14 | 402.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 266.58 | 108.71 | 141.41 | 151.95 | 74.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 818.35 | 368.99 | 468.72 | 1147.53 | 767.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 604.40 | 395.77 | 208.63 | 579.48 | 644.43 | 0.00 | 0.00 | 0.00 |
February | 797.18 | 527.67 | 269.51 | 778.96 | 650.80 | 0.00 | 0.00 | 0.00 |
March | 719.21 | 399.17 | 320.04 | 748.31 | 493.48 | 0.00 | 0.00 | 0.00 |
April | 558.08 | 220.68 | 337.40 | 597.73 | 372.71 | 0.00 | 0.00 | 0.00 |
May | 489.08 | 102.01 | 387.06 | 561.94 | 229.78 | 0.00 | 0.00 | 0.00 |
June | 458.98 | 70.16 | 388.82 | 612.50 | 127.16 | 0.00 | 0.00 | 0.00 |
July | 481.11 | 83.57 | 397.54 | 711.93 | 72.11 | 0.00 | 0.00 | 0.00 |
August | 642.46 | 238.30 | 404.16 | 960.82 | 98.61 | 0.00 | 0.00 | 0.00 |
September | 697.09 | 360.56 | 336.52 | 925.19 | 187.30 | 0.00 | 0.00 | 0.00 |
October | 954.95 | 598.82 | 356.13 | 1180.01 | 332.36 | 0.00 | 0.00 | 0.00 |
November | 662.18 | 397.67 | 264.51 | 688.60 | 491.27 | 0.00 | 0.00 | 0.00 |
December | 655.08 | 465.06 | 190.02 | 654.34 | 609.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 642.59 | 320.58 | 322.01 | 750.23 | 357.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 458.98 | 70.16 | 190.02 | 561.94 | 72.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 954.95 | 598.82 | 404.16 | 1180.01 | 650.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 604.40 | 395.76 | 208.63 | 579.48 | 644.43 | 0.00 | 0.00 | 0.00 |
February | 797.18 | 527.67 | 269.51 | 778.95 | 650.80 | 0.00 | 0.00 | 0.00 |
March | 719.21 | 399.17 | 320.04 | 748.31 | 493.48 | 0.00 | 0.00 | 0.00 |
April | 558.08 | 220.68 | 337.40 | 597.73 | 372.71 | 0.00 | 0.00 | 0.00 |
May | 489.08 | 102.01 | 387.06 | 561.94 | 229.78 | 0.00 | 0.00 | 0.00 |
June | 458.98 | 70.16 | 388.82 | 612.50 | 127.16 | 0.00 | 0.00 | 0.00 |
July | 481.11 | 83.57 | 397.54 | 711.93 | 72.11 | 0.00 | 0.00 | 0.00 |
August | 642.46 | 238.30 | 404.16 | 960.82 | 98.61 | 0.00 | 0.00 | 0.00 |
September | 697.09 | 360.56 | 336.52 | 925.19 | 187.30 | 0.00 | 0.00 | 0.00 |
October | 954.95 | 598.82 | 356.13 | 1180.01 | 332.36 | 0.00 | 0.00 | 0.00 |
November | 662.17 | 397.67 | 264.51 | 688.60 | 491.27 | 0.00 | 0.00 | 0.00 |
December | 655.08 | 465.06 | 190.02 | 654.34 | 609.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 642.59 | 320.58 | 322.01 | 750.23 | 357.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 458.98 | 70.16 | 190.02 | 561.94 | 72.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 954.95 | 598.82 | 404.16 | 1180.01 | 650.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 604.40 | 395.77 | 208.63 | 579.48 | 644.43 | 0.00 | 0.00 | 0.00 |
February | 797.18 | 527.67 | 269.51 | 778.96 | 650.80 | 0.00 | 0.00 | 0.00 |
March | 719.21 | 399.17 | 320.04 | 748.31 | 493.48 | 0.00 | 0.00 | 0.00 |
April | 558.08 | 220.68 | 337.40 | 597.73 | 372.71 | 0.00 | 0.00 | 0.00 |
May | 489.08 | 102.01 | 387.06 | 561.94 | 229.78 | 0.00 | 0.00 | 0.00 |
June | 458.98 | 70.16 | 388.82 | 612.50 | 127.16 | 0.00 | 0.00 | 0.00 |
July | 481.11 | 83.57 | 397.54 | 711.93 | 72.11 | 0.00 | 0.00 | 0.00 |
August | 642.46 | 238.30 | 404.16 | 960.82 | 98.61 | 0.00 | 0.00 | 0.00 |
September | 697.09 | 360.56 | 336.52 | 925.19 | 187.30 | 0.00 | 0.00 | 0.00 |
October | 954.95 | 598.82 | 356.13 | 1180.01 | 332.36 | 0.00 | 0.00 | 0.00 |
November | 662.18 | 397.67 | 264.51 | 688.60 | 491.27 | 0.00 | 0.00 | 0.00 |
December | 655.08 | 465.06 | 190.02 | 654.34 | 609.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 642.59 | 320.58 | 322.01 | 750.23 | 357.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 458.98 | 70.16 | 190.02 | 561.94 | 72.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 954.95 | 598.82 | 404.16 | 1180.01 | 650.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 604.40 | 395.76 | 208.63 | 579.48 | 644.43 | 0.00 | 0.00 | 0.00 |
February | 797.18 | 527.67 | 269.51 | 778.95 | 650.80 | 0.00 | 0.00 | 0.00 |
March | 719.21 | 399.17 | 320.04 | 748.31 | 493.48 | 0.00 | 0.00 | 0.00 |
April | 558.08 | 220.68 | 337.40 | 597.73 | 372.71 | 0.00 | 0.00 | 0.00 |
May | 489.08 | 102.01 | 387.06 | 561.94 | 229.78 | 0.00 | 0.00 | 0.00 |
June | 458.98 | 70.16 | 388.82 | 612.50 | 127.16 | 0.00 | 0.00 | 0.00 |
July | 481.11 | 83.57 | 397.54 | 711.93 | 72.11 | 0.00 | 0.00 | 0.00 |
August | 642.46 | 238.30 | 404.16 | 960.82 | 98.61 | 0.00 | 0.00 | 0.00 |
September | 697.09 | 360.56 | 336.52 | 925.19 | 187.30 | 0.00 | 0.00 | 0.00 |
October | 954.95 | 598.82 | 356.13 | 1180.01 | 332.36 | 0.00 | 0.00 | 0.00 |
November | 662.17 | 397.67 | 264.51 | 688.60 | 491.27 | 0.00 | 0.00 | 0.00 |
December | 655.08 | 465.06 | 190.02 | 654.34 | 609.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 642.59 | 320.58 | 322.01 | 750.23 | 357.40 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 458.98 | 70.16 | 190.02 | 561.94 | 72.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 954.95 | 598.82 | 404.16 | 1180.01 | 650.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 604.38 | 395.75 | 208.63 | 579.46 | 644.41 | 0.00 | 0.00 | 0.00 |
February | 797.15 | 527.65 | 269.50 | 778.92 | 650.77 | 0.00 | 0.00 | 0.00 |
March | 719.18 | 399.16 | 320.02 | 748.28 | 493.46 | 0.00 | 0.00 | 0.00 |
April | 558.06 | 220.67 | 337.39 | 597.70 | 372.69 | 0.00 | 0.00 | 0.00 |
May | 489.06 | 102.01 | 387.05 | 561.92 | 229.77 | 0.00 | 0.00 | 0.00 |
June | 458.96 | 70.16 | 388.81 | 612.47 | 127.15 | 0.00 | 0.00 | 0.00 |
July | 481.09 | 83.56 | 397.52 | 711.91 | 72.11 | 0.00 | 0.00 | 0.00 |
August | 642.44 | 238.29 | 404.15 | 960.78 | 98.61 | 0.00 | 0.00 | 0.00 |
September | 697.06 | 360.55 | 336.51 | 925.15 | 187.29 | 0.00 | 0.00 | 0.00 |
October | 954.91 | 598.80 | 356.11 | 1179.97 | 332.35 | 0.00 | 0.00 | 0.00 |
November | 662.15 | 397.65 | 264.50 | 688.57 | 491.25 | 0.00 | 0.00 | 0.00 |
December | 655.05 | 465.04 | 190.01 | 654.31 | 609.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 642.56 | 320.56 | 322.00 | 750.20 | 357.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 458.96 | 70.16 | 190.01 | 561.92 | 72.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 954.91 | 598.80 | 404.15 | 1179.97 | 650.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 267.70 | 109.65 | 158.05 | 150.12 | 822.61 | 0.00 | 0.00 | 0.00 |
February | 394.76 | 173.38 | 221.38 | 248.62 | 852.30 | 0.00 | 0.00 | 0.00 |
March | 582.92 | 269.12 | 313.80 | 489.81 | 617.08 | 0.00 | 0.00 | 0.00 |
April | 637.10 | 272.60 | 364.50 | 611.94 | 471.74 | 0.00 | 0.00 | 0.00 |
May | 742.16 | 281.84 | 460.31 | 842.06 | 273.69 | 0.00 | 0.00 | 0.00 |
June | 812.27 | 327.61 | 484.66 | 1051.15 | 160.81 | 0.00 | 0.00 | 0.00 |
July | 760.73 | 286.47 | 474.26 | 1055.99 | 97.20 | 0.00 | 0.00 | 0.00 |
August | 841.58 | 389.59 | 451.98 | 1169.24 | 130.50 | 0.00 | 0.00 | 0.00 |
September | 597.45 | 261.09 | 336.37 | 739.47 | 224.15 | 0.00 | 0.00 | 0.00 |
October | 592.33 | 288.04 | 304.29 | 645.37 | 411.30 | 0.00 | 0.00 | 0.00 |
November | 278.16 | 80.39 | 197.77 | 160.62 | 651.68 | 0.00 | 0.00 | 0.00 |
December | 247.41 | 107.06 | 140.36 | 133.74 | 846.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 564.06 | 237.78 | 326.28 | 610.77 | 461.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 247.41 | 80.39 | 140.36 | 133.74 | 97.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 841.58 | 389.59 | 484.66 | 1169.24 | 852.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 267.70 | 109.65 | 158.05 | 150.12 | 822.61 | 0.00 | 0.00 | 0.00 |
February | 394.76 | 173.38 | 221.38 | 248.62 | 852.30 | 0.00 | 0.00 | 0.00 |
March | 582.92 | 269.12 | 313.80 | 489.81 | 617.08 | 0.00 | 0.00 | 0.00 |
April | 637.10 | 272.60 | 364.50 | 611.94 | 471.74 | 0.00 | 0.00 | 0.00 |
May | 742.16 | 281.84 | 460.31 | 842.06 | 273.69 | 0.00 | 0.00 | 0.00 |
June | 812.27 | 327.61 | 484.66 | 1051.15 | 160.81 | 0.00 | 0.00 | 0.00 |
July | 760.73 | 286.47 | 474.26 | 1055.99 | 97.20 | 0.00 | 0.00 | 0.00 |
August | 841.58 | 389.59 | 451.98 | 1169.24 | 130.50 | 0.00 | 0.00 | 0.00 |
September | 597.45 | 261.09 | 336.37 | 739.47 | 224.15 | 0.00 | 0.00 | 0.00 |
October | 592.33 | 288.04 | 304.29 | 645.37 | 411.30 | 0.00 | 0.00 | 0.00 |
November | 278.16 | 80.39 | 197.77 | 160.62 | 651.68 | 0.00 | 0.00 | 0.00 |
December | 247.41 | 107.06 | 140.36 | 133.74 | 846.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 564.06 | 237.78 | 326.28 | 610.77 | 461.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 247.41 | 80.39 | 140.36 | 133.74 | 97.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 841.58 | 389.59 | 484.66 | 1169.24 | 852.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 267.70 | 109.65 | 158.05 | 150.11 | 822.60 | 0.00 | 0.00 | 0.00 |
February | 394.76 | 173.38 | 221.38 | 248.62 | 852.28 | 0.00 | 0.00 | 0.00 |
March | 582.90 | 269.11 | 313.79 | 489.80 | 617.07 | 0.00 | 0.00 | 0.00 |
April | 637.09 | 272.59 | 364.49 | 611.93 | 471.74 | 0.00 | 0.00 | 0.00 |
May | 742.14 | 281.84 | 460.31 | 842.04 | 273.68 | 0.00 | 0.00 | 0.00 |
June | 812.25 | 327.60 | 484.65 | 1051.13 | 160.80 | 0.00 | 0.00 | 0.00 |
July | 760.72 | 286.46 | 474.26 | 1055.97 | 97.20 | 0.00 | 0.00 | 0.00 |
August | 841.56 | 389.59 | 451.97 | 1169.21 | 130.50 | 0.00 | 0.00 | 0.00 |
September | 597.44 | 261.08 | 336.36 | 739.46 | 224.15 | 0.00 | 0.00 | 0.00 |
October | 592.32 | 288.03 | 304.29 | 645.36 | 411.29 | 0.00 | 0.00 | 0.00 |
November | 278.15 | 80.39 | 197.76 | 160.62 | 651.67 | 0.00 | 0.00 | 0.00 |
December | 247.41 | 107.05 | 140.35 | 133.74 | 846.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 564.05 | 237.78 | 326.27 | 610.76 | 461.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 247.41 | 80.39 | 140.35 | 133.74 | 97.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 841.56 | 389.59 | 484.65 | 1169.21 | 852.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 584.16 | 0.00 | 584.16 | 29.58 | 3338.44 | 0.00 | 0.00 | 0.00 |
February | 799.39 | 0.00 | 799.39 | 65.24 | 3484.65 | 0.00 | 0.00 | 0.00 |
March | 1108.56 | 0.00 | 1108.56 | 365.84 | 2349.08 | 0.00 | 0.00 | 0.00 |
April | 1331.53 | 3.79 | 1327.74 | 807.35 | 1670.36 | 0.00 | 0.00 | 0.00 |
May | 1766.51 | 58.86 | 1707.65 | 1619.21 | 1023.44 | 0.00 | 0.00 | 0.00 |
June | 1873.36 | 100.66 | 1772.70 | 2304.49 | 555.36 | 0.00 | 0.00 | 0.00 |
July | 1810.43 | 65.47 | 1744.95 | 2576.31 | 307.79 | 0.00 | 0.00 | 0.00 |
August | 1603.95 | 19.09 | 1584.86 | 2257.74 | 416.62 | 0.00 | 0.00 | 0.00 |
September | 1209.11 | 0.23 | 1208.89 | 1284.82 | 840.11 | 0.00 | 0.00 | 0.00 |
October | 1046.40 | 0.00 | 1046.40 | 753.95 | 1542.45 | 0.00 | 0.00 | 0.00 |
November | 733.95 | 0.00 | 733.95 | 184.15 | 2403.13 | 0.00 | 0.00 | 0.00 |
December | 509.54 | 0.00 | 509.54 | 18.36 | 3146.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1200.38 | 20.78 | 1179.59 | 1028.77 | 1746.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 509.54 | 0.00 | 509.54 | 18.36 | 307.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1873.36 | 100.66 | 1772.70 | 2576.31 | 3484.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 813.49 | 326.14 | 487.34 | 484.46 | 2073.63 | 0.00 | 0.00 | 0.00 |
February | 1261.54 | 588.51 | 673.03 | 853.51 | 2104.50 | 0.00 | 0.00 | 0.00 |
March | 1609.34 | 684.46 | 924.87 | 1365.50 | 1515.25 | 0.00 | 0.00 | 0.00 |
April | 1931.32 | 845.98 | 1085.34 | 1917.86 | 1079.24 | 0.00 | 0.00 | 0.00 |
May | 2342.28 | 936.12 | 1406.16 | 2677.79 | 690.77 | 0.00 | 0.00 | 0.00 |
June | 2170.80 | 785.81 | 1384.98 | 2816.78 | 376.24 | 0.00 | 0.00 | 0.00 |
July | 2180.30 | 786.82 | 1393.48 | 3078.36 | 206.91 | 0.00 | 0.00 | 0.00 |
August | 2455.07 | 1106.99 | 1348.08 | 3444.93 | 281.72 | 0.00 | 0.00 | 0.00 |
September | 1831.01 | 821.50 | 1009.51 | 2265.41 | 543.34 | 0.00 | 0.00 | 0.00 |
October | 1659.94 | 752.34 | 907.60 | 1816.11 | 1000.32 | 0.00 | 0.00 | 0.00 |
November | 1026.55 | 394.20 | 632.34 | 796.03 | 1503.75 | 0.00 | 0.00 | 0.00 |
December | 799.74 | 375.51 | 424.23 | 520.64 | 1939.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1676.10 | 701.16 | 974.95 | 1843.29 | 1103.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 799.74 | 326.14 | 424.23 | 484.46 | 206.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2455.07 | 1106.99 | 1406.16 | 3444.93 | 2104.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3021.96 | 1978.80 | 1043.16 | 2904.21 | 3042.70 | 0.00 | 0.00 | 0.00 |
February | 3985.87 | 2638.32 | 1347.55 | 3881.32 | 3130.33 | 0.00 | 0.00 | 0.00 |
March | 3596.00 | 1995.84 | 1600.16 | 3727.96 | 2343.86 | 0.00 | 0.00 | 0.00 |
April | 2790.37 | 1103.40 | 1686.98 | 2992.06 | 1751.57 | 0.00 | 0.00 | 0.00 |
May | 2445.35 | 510.06 | 1935.29 | 2798.47 | 1108.93 | 0.00 | 0.00 | 0.00 |
June | 2294.89 | 350.80 | 1944.09 | 3066.08 | 598.56 | 0.00 | 0.00 | 0.00 |
July | 2405.50 | 417.83 | 1987.67 | 3582.59 | 320.94 | 0.00 | 0.00 | 0.00 |
August | 3212.28 | 1191.49 | 2020.79 | 4816.44 | 456.99 | 0.00 | 0.00 | 0.00 |
September | 3485.39 | 1802.79 | 1682.60 | 4607.51 | 892.99 | 0.00 | 0.00 | 0.00 |
October | 4774.69 | 2994.07 | 1780.62 | 5856.76 | 1617.54 | 0.00 | 0.00 | 0.00 |
November | 3310.84 | 1988.32 | 1322.52 | 3443.76 | 2315.74 | 0.00 | 0.00 | 0.00 |
December | 3275.36 | 2325.28 | 950.07 | 3275.97 | 2858.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3212.92 | 1602.87 | 1610.05 | 3747.38 | 1694.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2294.89 | 350.80 | 950.07 | 2798.47 | 320.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4774.69 | 2994.07 | 2020.79 | 5856.76 | 3130.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 803.09 | 328.95 | 474.14 | 477.31 | 2172.69 | 0.00 | 0.00 | 0.00 |
February | 1184.28 | 520.14 | 664.14 | 784.23 | 2248.70 | 0.00 | 0.00 | 0.00 |
March | 1748.73 | 807.34 | 941.39 | 1531.38 | 1563.87 | 0.00 | 0.00 | 0.00 |
April | 1911.28 | 817.79 | 1093.49 | 1911.15 | 1165.18 | 0.00 | 0.00 | 0.00 |
May | 2226.45 | 845.52 | 1380.93 | 2549.74 | 749.82 | 0.00 | 0.00 | 0.00 |
June | 2436.78 | 982.82 | 1453.96 | 3172.45 | 429.28 | 0.00 | 0.00 | 0.00 |
July | 2282.17 | 859.40 | 1422.78 | 3202.45 | 248.27 | 0.00 | 0.00 | 0.00 |
August | 2524.70 | 1168.77 | 1355.93 | 3549.09 | 334.16 | 0.00 | 0.00 | 0.00 |
September | 1792.34 | 783.25 | 1009.09 | 2241.54 | 597.72 | 0.00 | 0.00 | 0.00 |
October | 1776.97 | 864.10 | 912.87 | 1979.78 | 1077.69 | 0.00 | 0.00 | 0.00 |
November | 834.46 | 241.16 | 593.29 | 540.97 | 1590.64 | 0.00 | 0.00 | 0.00 |
December | 742.23 | 321.17 | 421.07 | 449.13 | 2054.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1692.16 | 713.33 | 978.83 | 1873.55 | 1179.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 742.23 | 241.16 | 421.07 | 449.13 | 248.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2524.70 | 1168.77 | 1453.96 | 3549.09 | 2248.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 584.16 | 0.00 | 584.16 | 37.95 | 3176.18 | 0.00 | 0.00 | 0.00 |
February | 799.39 | 0.00 | 799.39 | 79.52 | 3289.08 | 0.00 | 0.00 | 0.00 |
March | 1108.56 | 0.00 | 1108.56 | 396.69 | 2184.72 | 0.00 | 0.00 | 0.00 |
April | 1331.53 | 3.79 | 1327.74 | 844.91 | 1551.12 | 0.00 | 0.00 | 0.00 |
May | 1766.51 | 58.86 | 1707.65 | 1632.03 | 981.95 | 0.00 | 0.00 | 0.00 |
June | 1873.36 | 100.66 | 1772.70 | 2285.81 | 552.10 | 0.00 | 0.00 | 0.00 |
July | 1810.43 | 65.47 | 1744.95 | 2547.74 | 316.57 | 0.00 | 0.00 | 0.00 |
August | 1603.95 | 19.09 | 1584.86 | 2237.77 | 418.02 | 0.00 | 0.00 | 0.00 |
September | 1209.11 | 0.23 | 1208.89 | 1288.45 | 804.83 | 0.00 | 0.00 | 0.00 |
October | 1046.40 | 0.00 | 1046.40 | 793.81 | 1424.36 | 0.00 | 0.00 | 0.00 |
November | 733.95 | 0.00 | 733.95 | 220.01 | 2188.15 | 0.00 | 0.00 | 0.00 |
December | 509.54 | 0.00 | 509.54 | 30.16 | 2902.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1200.38 | 20.78 | 1179.59 | 1039.35 | 1639.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 509.54 | 0.00 | 509.54 | 30.16 | 316.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1873.36 | 100.66 | 1772.70 | 2547.74 | 3289.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 813.49 | 326.14 | 487.34 | 498.33 | 1971.19 | 0.00 | 0.00 | 0.00 |
February | 1261.54 | 588.51 | 673.03 | 879.78 | 1983.13 | 0.00 | 0.00 | 0.00 |
March | 1609.34 | 684.46 | 924.87 | 1387.64 | 1417.69 | 0.00 | 0.00 | 0.00 |
April | 1931.32 | 845.98 | 1085.34 | 1937.65 | 1015.59 | 0.00 | 0.00 | 0.00 |
May | 2342.28 | 936.12 | 1406.16 | 2679.17 | 667.64 | 0.00 | 0.00 | 0.00 |
June | 2170.80 | 785.81 | 1384.98 | 2802.25 | 375.50 | 0.00 | 0.00 | 0.00 |
July | 2180.30 | 786.82 | 1393.48 | 3058.53 | 213.08 | 0.00 | 0.00 | 0.00 |
August | 2455.07 | 1106.99 | 1348.08 | 3428.04 | 283.37 | 0.00 | 0.00 | 0.00 |
September | 1831.01 | 821.50 | 1009.51 | 2263.75 | 525.38 | 0.00 | 0.00 | 0.00 |
October | 1659.94 | 752.34 | 907.60 | 1836.58 | 936.04 | 0.00 | 0.00 | 0.00 |
November | 1026.55 | 394.20 | 632.34 | 830.11 | 1380.41 | 0.00 | 0.00 | 0.00 |
December | 799.74 | 375.51 | 424.23 | 544.39 | 1789.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1676.10 | 701.16 | 974.95 | 1852.22 | 1041.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 799.74 | 326.14 | 424.23 | 498.33 | 213.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2455.07 | 1106.99 | 1406.16 | 3428.04 | 1983.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 3021.96 | 1978.80 | 1043.16 | 2931.38 | 2874.35 | 0.00 | 0.00 | 0.00 |
February | 3985.87 | 2638.32 | 1347.55 | 3927.68 | 2934.20 | 0.00 | 0.00 | 0.00 |
March | 3596.00 | 1995.84 | 1600.16 | 3757.23 | 2185.03 | 0.00 | 0.00 | 0.00 |
April | 2790.37 | 1103.40 | 1686.98 | 3021.14 | 1636.22 | 0.00 | 0.00 | 0.00 |
May | 2445.35 | 510.06 | 1935.29 | 2805.65 | 1062.47 | 0.00 | 0.00 | 0.00 |
June | 2294.89 | 350.80 | 1944.09 | 3046.74 | 593.62 | 0.00 | 0.00 | 0.00 |
July | 2405.50 | 417.83 | 1987.67 | 3553.82 | 328.38 | 0.00 | 0.00 | 0.00 |
August | 3212.28 | 1191.49 | 2020.79 | 4791.81 | 457.53 | 0.00 | 0.00 | 0.00 |
September | 3485.39 | 1802.79 | 1682.60 | 4603.95 | 861.06 | 0.00 | 0.00 | 0.00 |
October | 4774.69 | 2994.07 | 1780.62 | 5875.24 | 1520.36 | 0.00 | 0.00 | 0.00 |
November | 3310.84 | 1988.32 | 1322.52 | 3494.09 | 2122.84 | 0.00 | 0.00 | 0.00 |
December | 3275.36 | 2325.28 | 950.07 | 3325.94 | 2631.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3212.92 | 1602.87 | 1610.05 | 3762.26 | 1592.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2294.89 | 350.80 | 950.07 | 2805.65 | 328.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4774.69 | 2994.07 | 2020.79 | 5875.24 | 2934.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 803.09 | 328.95 | 474.14 | 485.53 | 2068.34 | 0.00 | 0.00 | 0.00 |
February | 1184.28 | 520.14 | 664.14 | 794.43 | 2136.55 | 0.00 | 0.00 | 0.00 |
March | 1748.73 | 807.34 | 941.39 | 1545.57 | 1474.64 | 0.00 | 0.00 | 0.00 |
April | 1911.28 | 817.79 | 1093.49 | 1926.18 | 1099.18 | 0.00 | 0.00 | 0.00 |
May | 2226.45 | 845.52 | 1380.93 | 2552.41 | 722.53 | 0.00 | 0.00 | 0.00 |
June | 2436.78 | 982.82 | 1453.96 | 3157.51 | 425.62 | 0.00 | 0.00 | 0.00 |
July | 2282.17 | 859.40 | 1422.78 | 3183.14 | 251.34 | 0.00 | 0.00 | 0.00 |
August | 2524.70 | 1168.77 | 1355.93 | 3533.31 | 333.61 | 0.00 | 0.00 | 0.00 |
September | 1792.34 | 783.25 | 1009.09 | 2240.95 | 577.11 | 0.00 | 0.00 | 0.00 |
October | 1776.97 | 864.10 | 912.87 | 1996.30 | 1014.06 | 0.00 | 0.00 | 0.00 |
November | 834.46 | 241.16 | 593.29 | 561.71 | 1475.41 | 0.00 | 0.00 | 0.00 |
December | 742.23 | 321.17 | 421.07 | 462.50 | 1918.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1692.16 | 713.33 | 978.83 | 1877.69 | 1118.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 742.23 | 241.16 | 421.07 | 462.50 | 251.34 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2524.70 | 1168.77 | 1453.96 | 3533.31 | 2136.55 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.312924E+09 | 0.00 | 0.312924E+09 | 5376729.81 | 0.201297E+10 |
February | 0.386783E+09 | 0.00 | 0.386783E+09 | 19470540.51 | 0.187130E+10 |
March | 0.593839E+09 | 0.00 | 0.593839E+09 | 0.160060E+09 | 0.142683E+10 |
April | 0.690272E+09 | 1963346.87 | 0.688309E+09 | 0.379993E+09 | 0.983373E+09 |
May | 0.946297E+09 | 31531151.65 | 0.914766E+09 | 0.852672E+09 | 0.583021E+09 |
June | 0.971164E+09 | 52184715.67 | 0.918979E+09 | 0.117981E+10 | 0.312686E+09 |
July | 0.969821E+09 | 35071959.59 | 0.934749E+09 | 0.135218E+10 | 0.193700E+09 |
August | 0.859215E+09 | 10225867.42 | 0.848989E+09 | 0.117852E+10 | 0.255310E+09 |
September | 0.626812E+09 | 117376.35 | 0.626694E+09 | 0.646603E+09 | 0.483991E+09 |
October | 0.560542E+09 | 0.00 | 0.560542E+09 | 0.376055E+09 | 0.918046E+09 |
November | 0.380484E+09 | 0.00 | 0.380484E+09 | 71384707.59 | 0.144492E+10 |
December | 0.272953E+09 | 0.00 | 0.272953E+09 | 2805609.51 | 0.195941E+10 |
Annual Sum or Average | 0.757111E+10 | 0.131094E+09 | 0.744001E+10 | 0.622492E+10 | 0.124456E+11 |
Minimum of Months | 0.272953E+09 | 0.00 | 0.272953E+09 | 2805609.51 | 0.193700E+09 |
Maximum of Months | 0.971164E+09 | 52184715.67 | 0.934749E+09 | 0.135218E+10 | 0.201297E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.312924E+09 | 0.00 | 0.312924E+09 | 5376681.24 | 0.201297E+10 |
February | 0.386782E+09 | 0.00 | 0.386782E+09 | 19470464.74 | 0.187130E+10 |
March | 0.593838E+09 | 0.00 | 0.593838E+09 | 0.160059E+09 | 0.142683E+10 |
April | 0.690272E+09 | 1963344.51 | 0.688308E+09 | 0.379992E+09 | 0.983373E+09 |
May | 0.946296E+09 | 31531113.82 | 0.914765E+09 | 0.852671E+09 | 0.583021E+09 |
June | 0.971163E+09 | 52184653.05 | 0.918979E+09 | 0.117981E+10 | 0.312686E+09 |
July | 0.969820E+09 | 35071917.51 | 0.934748E+09 | 0.135217E+10 | 0.193700E+09 |
August | 0.859214E+09 | 10225855.15 | 0.848988E+09 | 0.117851E+10 | 0.255310E+09 |
September | 0.626811E+09 | 117376.21 | 0.626694E+09 | 0.646603E+09 | 0.483991E+09 |
October | 0.560542E+09 | 0.00 | 0.560542E+09 | 0.376055E+09 | 0.918046E+09 |
November | 0.380484E+09 | 0.00 | 0.380484E+09 | 71384530.04 | 0.144492E+10 |
December | 0.272953E+09 | 0.00 | 0.272953E+09 | 2805588.57 | 0.195941E+10 |
Annual Sum or Average | 0.757110E+10 | 0.131094E+09 | 0.744001E+10 | 0.622491E+10 | 0.124456E+11 |
Minimum of Months | 0.272953E+09 | 0.00 | 0.272953E+09 | 2805588.57 | 0.193700E+09 |
Maximum of Months | 0.971163E+09 | 52184653.05 | 0.934748E+09 | 0.135217E+10 | 0.201297E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.312924E+09 | 0.00 | 0.312924E+09 | 5376729.81 | 0.201297E+10 |
February | 0.386783E+09 | 0.00 | 0.386783E+09 | 19470540.51 | 0.187130E+10 |
March | 0.593839E+09 | 0.00 | 0.593839E+09 | 0.160060E+09 | 0.142683E+10 |
April | 0.690272E+09 | 1963346.87 | 0.688309E+09 | 0.379993E+09 | 0.983373E+09 |
May | 0.946297E+09 | 31531151.65 | 0.914766E+09 | 0.852672E+09 | 0.583021E+09 |
June | 0.971164E+09 | 52184715.67 | 0.918979E+09 | 0.117981E+10 | 0.312686E+09 |
July | 0.969821E+09 | 35071959.59 | 0.934749E+09 | 0.135218E+10 | 0.193700E+09 |
August | 0.859215E+09 | 10225867.42 | 0.848989E+09 | 0.117852E+10 | 0.255310E+09 |
September | 0.626812E+09 | 117376.35 | 0.626694E+09 | 0.646603E+09 | 0.483991E+09 |
October | 0.560542E+09 | 0.00 | 0.560542E+09 | 0.376055E+09 | 0.918046E+09 |
November | 0.380484E+09 | 0.00 | 0.380484E+09 | 71384707.59 | 0.144492E+10 |
December | 0.272953E+09 | 0.00 | 0.272953E+09 | 2805609.51 | 0.195941E+10 |
Annual Sum or Average | 0.757111E+10 | 0.131094E+09 | 0.744001E+10 | 0.622492E+10 | 0.124456E+11 |
Minimum of Months | 0.272953E+09 | 0.00 | 0.272953E+09 | 2805609.51 | 0.193700E+09 |
Maximum of Months | 0.971164E+09 | 52184715.67 | 0.934749E+09 | 0.135218E+10 | 0.201297E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.312924E+09 | 0.00 | 0.312924E+09 | 5376681.24 | 0.201297E+10 |
February | 0.386782E+09 | 0.00 | 0.386782E+09 | 19470464.74 | 0.187130E+10 |
March | 0.593838E+09 | 0.00 | 0.593838E+09 | 0.160059E+09 | 0.142683E+10 |
April | 0.690272E+09 | 1963344.51 | 0.688308E+09 | 0.379992E+09 | 0.983373E+09 |
May | 0.946296E+09 | 31531113.82 | 0.914765E+09 | 0.852671E+09 | 0.583021E+09 |
June | 0.971163E+09 | 52184653.05 | 0.918979E+09 | 0.117981E+10 | 0.312686E+09 |
July | 0.969820E+09 | 35071917.51 | 0.934748E+09 | 0.135217E+10 | 0.193700E+09 |
August | 0.859214E+09 | 10225855.15 | 0.848988E+09 | 0.117851E+10 | 0.255310E+09 |
September | 0.626811E+09 | 117376.21 | 0.626694E+09 | 0.646603E+09 | 0.483991E+09 |
October | 0.560542E+09 | 0.00 | 0.560542E+09 | 0.376055E+09 | 0.918046E+09 |
November | 0.380484E+09 | 0.00 | 0.380484E+09 | 71384530.04 | 0.144492E+10 |
December | 0.272953E+09 | 0.00 | 0.272953E+09 | 2805588.57 | 0.195941E+10 |
Annual Sum or Average | 0.757110E+10 | 0.131094E+09 | 0.744001E+10 | 0.622491E+10 | 0.124456E+11 |
Minimum of Months | 0.272953E+09 | 0.00 | 0.272953E+09 | 2805588.57 | 0.193700E+09 |
Maximum of Months | 0.971163E+09 | 52184653.05 | 0.934748E+09 | 0.135217E+10 | 0.201297E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.312912E+09 | 0.00 | 0.312912E+09 | 5376513.11 | 0.201288E+10 |
February | 0.386767E+09 | 0.00 | 0.386767E+09 | 19469755.76 | 0.187123E+10 |
March | 0.593815E+09 | 0.00 | 0.593815E+09 | 0.160053E+09 | 0.142677E+10 |
April | 0.690244E+09 | 1963267.74 | 0.688281E+09 | 0.379977E+09 | 0.983333E+09 |
May | 0.946259E+09 | 31529880.81 | 0.914729E+09 | 0.852638E+09 | 0.582997E+09 |
June | 0.971125E+09 | 52182612.39 | 0.918942E+09 | 0.117976E+10 | 0.312673E+09 |
July | 0.969782E+09 | 35070546.04 | 0.934711E+09 | 0.135212E+10 | 0.193692E+09 |
August | 0.859180E+09 | 10225455.27 | 0.848955E+09 | 0.117847E+10 | 0.255300E+09 |
September | 0.626786E+09 | 117371.62 | 0.626669E+09 | 0.646577E+09 | 0.483972E+09 |
October | 0.560520E+09 | 0.00 | 0.560520E+09 | 0.376040E+09 | 0.918009E+09 |
November | 0.380469E+09 | 0.00 | 0.380469E+09 | 71381830.47 | 0.144486E+10 |
December | 0.272942E+09 | 0.00 | 0.272942E+09 | 2805496.43 | 0.195933E+10 |
Annual Sum or Average | 0.757080E+10 | 0.131089E+09 | 0.743971E+10 | 0.622467E+10 | 0.124451E+11 |
Minimum of Months | 0.272942E+09 | 0.00 | 0.272942E+09 | 2805496.43 | 0.193692E+09 |
Maximum of Months | 0.971125E+09 | 52182612.39 | 0.934711E+09 | 0.135212E+10 | 0.201288E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.726289E+09 | 0.291183E+09 | 0.435106E+09 | 0.406984E+09 | 0.205448E+10 |
February | 0.101732E+10 | 0.474580E+09 | 0.542739E+09 | 0.663712E+09 | 0.184524E+10 |
March | 0.143683E+10 | 0.611094E+09 | 0.825736E+09 | 0.120264E+10 | 0.147232E+10 |
April | 0.166867E+10 | 0.730931E+09 | 0.937743E+09 | 0.164629E+10 | 0.100485E+10 |
May | 0.209121E+10 | 0.835773E+09 | 0.125544E+10 | 0.239883E+10 | 0.646905E+09 |
June | 0.187559E+10 | 0.678950E+09 | 0.119664E+10 | 0.243801E+10 | 0.342149E+09 |
July | 0.194659E+10 | 0.702477E+09 | 0.124412E+10 | 0.274152E+10 | 0.200309E+09 |
August | 0.219191E+10 | 0.988333E+09 | 0.120358E+10 | 0.307361E+10 | 0.262216E+09 |
September | 0.158201E+10 | 0.709784E+09 | 0.872221E+09 | 0.195469E+10 | 0.509957E+09 |
October | 0.148201E+10 | 0.671698E+09 | 0.810314E+09 | 0.161309E+10 | 0.958932E+09 |
November | 0.886945E+09 | 0.340596E+09 | 0.546349E+09 | 0.660290E+09 | 0.144944E+10 |
December | 0.714013E+09 | 0.335257E+09 | 0.378756E+09 | 0.442164E+09 | 0.193229E+10 |
Annual Sum or Average | 0.176194E+11 | 0.737065E+10 | 0.102487E+11 | 0.192418E+11 | 0.126791E+11 |
Minimum of Months | 0.714013E+09 | 0.291183E+09 | 0.378756E+09 | 0.406984E+09 | 0.200309E+09 |
Maximum of Months | 0.219191E+10 | 0.988333E+09 | 0.125544E+10 | 0.307361E+10 | 0.205448E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.726289E+09 | 0.291183E+09 | 0.435106E+09 | 0.406984E+09 | 0.205448E+10 |
February | 0.101732E+10 | 0.474580E+09 | 0.542739E+09 | 0.663712E+09 | 0.184524E+10 |
March | 0.143683E+10 | 0.611094E+09 | 0.825736E+09 | 0.120264E+10 | 0.147232E+10 |
April | 0.166867E+10 | 0.730931E+09 | 0.937743E+09 | 0.164629E+10 | 0.100485E+10 |
May | 0.209121E+10 | 0.835773E+09 | 0.125544E+10 | 0.239883E+10 | 0.646905E+09 |
June | 0.187559E+10 | 0.678950E+09 | 0.119664E+10 | 0.243801E+10 | 0.342149E+09 |
July | 0.194659E+10 | 0.702477E+09 | 0.124412E+10 | 0.274152E+10 | 0.200309E+09 |
August | 0.219191E+10 | 0.988333E+09 | 0.120358E+10 | 0.307361E+10 | 0.262216E+09 |
September | 0.158201E+10 | 0.709784E+09 | 0.872221E+09 | 0.195469E+10 | 0.509957E+09 |
October | 0.148201E+10 | 0.671698E+09 | 0.810314E+09 | 0.161309E+10 | 0.958932E+09 |
November | 0.886945E+09 | 0.340596E+09 | 0.546349E+09 | 0.660290E+09 | 0.144944E+10 |
December | 0.714013E+09 | 0.335257E+09 | 0.378756E+09 | 0.442164E+09 | 0.193229E+10 |
Annual Sum or Average | 0.176194E+11 | 0.737065E+10 | 0.102487E+11 | 0.192418E+11 | 0.126791E+11 |
Minimum of Months | 0.714013E+09 | 0.291183E+09 | 0.378756E+09 | 0.406984E+09 | 0.200309E+09 |
Maximum of Months | 0.219191E+10 | 0.988333E+09 | 0.125544E+10 | 0.307361E+10 | 0.205448E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.726275E+09 | 0.291178E+09 | 0.435098E+09 | 0.406977E+09 | 0.205444E+10 |
February | 0.101730E+10 | 0.474571E+09 | 0.542729E+09 | 0.663700E+09 | 0.184520E+10 |
March | 0.143680E+10 | 0.611083E+09 | 0.825721E+09 | 0.120262E+10 | 0.147230E+10 |
April | 0.166864E+10 | 0.730917E+09 | 0.937726E+09 | 0.164626E+10 | 0.100484E+10 |
May | 0.209117E+10 | 0.835758E+09 | 0.125541E+10 | 0.239878E+10 | 0.646893E+09 |
June | 0.187555E+10 | 0.678937E+09 | 0.119662E+10 | 0.243797E+10 | 0.342142E+09 |
July | 0.194656E+10 | 0.702464E+09 | 0.124409E+10 | 0.274147E+10 | 0.200305E+09 |
August | 0.219187E+10 | 0.988315E+09 | 0.120356E+10 | 0.307355E+10 | 0.262211E+09 |
September | 0.158198E+10 | 0.709771E+09 | 0.872205E+09 | 0.195465E+10 | 0.509948E+09 |
October | 0.148198E+10 | 0.671686E+09 | 0.810299E+09 | 0.161306E+10 | 0.958915E+09 |
November | 0.886928E+09 | 0.340590E+09 | 0.546339E+09 | 0.660278E+09 | 0.144941E+10 |
December | 0.714000E+09 | 0.335251E+09 | 0.378749E+09 | 0.442156E+09 | 0.193226E+10 |
Annual Sum or Average | 0.176191E+11 | 0.737052E+10 | 0.102485E+11 | 0.192415E+11 | 0.126789E+11 |
Minimum of Months | 0.714000E+09 | 0.291178E+09 | 0.378749E+09 | 0.406977E+09 | 0.200305E+09 |
Maximum of Months | 0.219187E+10 | 0.988315E+09 | 0.125541E+10 | 0.307355E+10 | 0.205444E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161883E+10 | 0.106002E+10 | 0.558808E+09 | 0.155209E+10 | 0.172605E+10 |
February | 0.192855E+10 | 0.127654E+10 | 0.652005E+09 | 0.188445E+10 | 0.157441E+10 |
March | 0.192633E+10 | 0.106915E+10 | 0.857184E+09 | 0.200428E+10 | 0.132175E+10 |
April | 0.144655E+10 | 0.572008E+09 | 0.874539E+09 | 0.154931E+10 | 0.966063E+09 |
May | 0.130994E+10 | 0.273233E+09 | 0.103671E+10 | 0.150511E+10 | 0.615445E+09 |
June | 0.118968E+10 | 0.181855E+09 | 0.100783E+10 | 0.158759E+10 | 0.329597E+09 |
July | 0.128859E+10 | 0.223828E+09 | 0.106477E+10 | 0.190685E+10 | 0.193151E+09 |
August | 0.172077E+10 | 0.638264E+09 | 0.108251E+10 | 0.257347E+10 | 0.264128E+09 |
September | 0.180685E+10 | 0.934575E+09 | 0.872272E+09 | 0.239809E+10 | 0.485473E+09 |
October | 0.255774E+10 | 0.160388E+10 | 0.953851E+09 | 0.316055E+10 | 0.890198E+09 |
November | 0.171636E+10 | 0.103076E+10 | 0.685603E+09 | 0.178484E+10 | 0.127336E+10 |
December | 0.175456E+10 | 0.124562E+10 | 0.508941E+09 | 0.175258E+10 | 0.163151E+10 |
Annual Sum or Average | 0.202647E+11 | 0.101097E+11 | 0.101550E+11 | 0.236592E+11 | 0.112711E+11 |
Minimum of Months | 0.118968E+10 | 0.181855E+09 | 0.508941E+09 | 0.150511E+10 | 0.193151E+09 |
Maximum of Months | 0.255774E+10 | 0.160388E+10 | 0.108251E+10 | 0.316055E+10 | 0.172605E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161882E+10 | 0.106002E+10 | 0.558807E+09 | 0.155209E+10 | 0.172605E+10 |
February | 0.192854E+10 | 0.127654E+10 | 0.652004E+09 | 0.188445E+10 | 0.157441E+10 |
March | 0.192633E+10 | 0.106915E+10 | 0.857183E+09 | 0.200428E+10 | 0.132175E+10 |
April | 0.144654E+10 | 0.572007E+09 | 0.874538E+09 | 0.154930E+10 | 0.966063E+09 |
May | 0.130994E+10 | 0.273232E+09 | 0.103671E+10 | 0.150511E+10 | 0.615445E+09 |
June | 0.118968E+10 | 0.181855E+09 | 0.100783E+10 | 0.158759E+10 | 0.329597E+09 |
July | 0.128859E+10 | 0.223828E+09 | 0.106476E+10 | 0.190684E+10 | 0.193151E+09 |
August | 0.172077E+10 | 0.638263E+09 | 0.108251E+10 | 0.257346E+10 | 0.264128E+09 |
September | 0.180685E+10 | 0.934574E+09 | 0.872271E+09 | 0.239809E+10 | 0.485472E+09 |
October | 0.255773E+10 | 0.160388E+10 | 0.953851E+09 | 0.316055E+10 | 0.890198E+09 |
November | 0.171636E+10 | 0.103075E+10 | 0.685603E+09 | 0.178484E+10 | 0.127336E+10 |
December | 0.175456E+10 | 0.124562E+10 | 0.508940E+09 | 0.175257E+10 | 0.163151E+10 |
Annual Sum or Average | 0.202647E+11 | 0.101097E+11 | 0.101550E+11 | 0.236592E+11 | 0.112711E+11 |
Minimum of Months | 0.118968E+10 | 0.181855E+09 | 0.508940E+09 | 0.150511E+10 | 0.193151E+09 |
Maximum of Months | 0.255773E+10 | 0.160388E+10 | 0.108251E+10 | 0.316055E+10 | 0.172605E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161883E+10 | 0.106002E+10 | 0.558808E+09 | 0.155209E+10 | 0.172605E+10 |
February | 0.192855E+10 | 0.127654E+10 | 0.652005E+09 | 0.188445E+10 | 0.157441E+10 |
March | 0.192633E+10 | 0.106915E+10 | 0.857184E+09 | 0.200428E+10 | 0.132175E+10 |
April | 0.144655E+10 | 0.572008E+09 | 0.874539E+09 | 0.154931E+10 | 0.966063E+09 |
May | 0.130994E+10 | 0.273233E+09 | 0.103671E+10 | 0.150511E+10 | 0.615445E+09 |
June | 0.118968E+10 | 0.181855E+09 | 0.100783E+10 | 0.158759E+10 | 0.329597E+09 |
July | 0.128859E+10 | 0.223828E+09 | 0.106477E+10 | 0.190685E+10 | 0.193151E+09 |
August | 0.172077E+10 | 0.638264E+09 | 0.108251E+10 | 0.257347E+10 | 0.264128E+09 |
September | 0.180685E+10 | 0.934575E+09 | 0.872272E+09 | 0.239809E+10 | 0.485473E+09 |
October | 0.255774E+10 | 0.160388E+10 | 0.953851E+09 | 0.316055E+10 | 0.890198E+09 |
November | 0.171636E+10 | 0.103076E+10 | 0.685603E+09 | 0.178484E+10 | 0.127336E+10 |
December | 0.175456E+10 | 0.124562E+10 | 0.508941E+09 | 0.175258E+10 | 0.163151E+10 |
Annual Sum or Average | 0.202647E+11 | 0.101097E+11 | 0.101550E+11 | 0.236592E+11 | 0.112711E+11 |
Minimum of Months | 0.118968E+10 | 0.181855E+09 | 0.508941E+09 | 0.150511E+10 | 0.193151E+09 |
Maximum of Months | 0.255774E+10 | 0.160388E+10 | 0.108251E+10 | 0.316055E+10 | 0.172605E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161882E+10 | 0.106002E+10 | 0.558807E+09 | 0.155209E+10 | 0.172605E+10 |
February | 0.192854E+10 | 0.127654E+10 | 0.652004E+09 | 0.188445E+10 | 0.157441E+10 |
March | 0.192633E+10 | 0.106915E+10 | 0.857183E+09 | 0.200428E+10 | 0.132175E+10 |
April | 0.144654E+10 | 0.572007E+09 | 0.874538E+09 | 0.154930E+10 | 0.966063E+09 |
May | 0.130994E+10 | 0.273232E+09 | 0.103671E+10 | 0.150511E+10 | 0.615445E+09 |
June | 0.118968E+10 | 0.181855E+09 | 0.100783E+10 | 0.158759E+10 | 0.329597E+09 |
July | 0.128859E+10 | 0.223828E+09 | 0.106476E+10 | 0.190684E+10 | 0.193151E+09 |
August | 0.172077E+10 | 0.638263E+09 | 0.108251E+10 | 0.257346E+10 | 0.264128E+09 |
September | 0.180685E+10 | 0.934574E+09 | 0.872271E+09 | 0.239809E+10 | 0.485472E+09 |
October | 0.255773E+10 | 0.160388E+10 | 0.953851E+09 | 0.316055E+10 | 0.890198E+09 |
November | 0.171636E+10 | 0.103075E+10 | 0.685603E+09 | 0.178484E+10 | 0.127336E+10 |
December | 0.175456E+10 | 0.124562E+10 | 0.508940E+09 | 0.175257E+10 | 0.163151E+10 |
Annual Sum or Average | 0.202647E+11 | 0.101097E+11 | 0.101550E+11 | 0.236592E+11 | 0.112711E+11 |
Minimum of Months | 0.118968E+10 | 0.181855E+09 | 0.508940E+09 | 0.150511E+10 | 0.193151E+09 |
Maximum of Months | 0.255773E+10 | 0.160388E+10 | 0.108251E+10 | 0.316055E+10 | 0.172605E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161876E+10 | 0.105997E+10 | 0.558785E+09 | 0.155203E+10 | 0.172598E+10 |
February | 0.192847E+10 | 0.127649E+10 | 0.651979E+09 | 0.188437E+10 | 0.157434E+10 |
March | 0.192625E+10 | 0.106910E+10 | 0.857149E+09 | 0.200420E+10 | 0.132169E+10 |
April | 0.144649E+10 | 0.571985E+09 | 0.874503E+09 | 0.154924E+10 | 0.966024E+09 |
May | 0.130989E+10 | 0.273222E+09 | 0.103667E+10 | 0.150505E+10 | 0.615421E+09 |
June | 0.118964E+10 | 0.181848E+09 | 0.100779E+10 | 0.158753E+10 | 0.329584E+09 |
July | 0.128854E+10 | 0.223819E+09 | 0.106472E+10 | 0.190677E+10 | 0.193143E+09 |
August | 0.172071E+10 | 0.638238E+09 | 0.108247E+10 | 0.257336E+10 | 0.264117E+09 |
September | 0.180677E+10 | 0.934538E+09 | 0.872237E+09 | 0.239800E+10 | 0.485453E+09 |
October | 0.255763E+10 | 0.160382E+10 | 0.953813E+09 | 0.316042E+10 | 0.890162E+09 |
November | 0.171629E+10 | 0.103071E+10 | 0.685576E+09 | 0.178477E+10 | 0.127331E+10 |
December | 0.175449E+10 | 0.124557E+10 | 0.508920E+09 | 0.175251E+10 | 0.163144E+10 |
Annual Sum or Average | 0.202639E+11 | 0.101093E+11 | 0.101546E+11 | 0.236583E+11 | 0.112707E+11 |
Minimum of Months | 0.118964E+10 | 0.181848E+09 | 0.508920E+09 | 0.150505E+10 | 0.193143E+09 |
Maximum of Months | 0.255763E+10 | 0.160382E+10 | 0.108247E+10 | 0.316042E+10 | 0.172598E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.717009E+09 | 0.293689E+09 | 0.423320E+09 | 0.402072E+09 | 0.220328E+10 |
February | 0.955010E+09 | 0.419444E+09 | 0.535566E+09 | 0.601464E+09 | 0.206188E+10 |
March | 0.156128E+10 | 0.720800E+09 | 0.840480E+09 | 0.131190E+10 | 0.165279E+10 |
April | 0.165136E+10 | 0.706575E+09 | 0.944786E+09 | 0.158615E+10 | 0.122276E+10 |
May | 0.198779E+10 | 0.754886E+09 | 0.123290E+10 | 0.225537E+10 | 0.733038E+09 |
June | 0.210540E+10 | 0.849167E+09 | 0.125623E+10 | 0.272458E+10 | 0.416809E+09 |
July | 0.203754E+10 | 0.767277E+09 | 0.127027E+10 | 0.282835E+10 | 0.260346E+09 |
August | 0.225408E+10 | 0.104349E+10 | 0.121059E+10 | 0.313168E+10 | 0.349543E+09 |
September | 0.154860E+10 | 0.676733E+09 | 0.871864E+09 | 0.191671E+10 | 0.580996E+09 |
October | 0.158650E+10 | 0.771474E+09 | 0.815021E+09 | 0.172855E+10 | 0.110162E+10 |
November | 0.720980E+09 | 0.208368E+09 | 0.512611E+09 | 0.416331E+09 | 0.168916E+10 |
December | 0.662673E+09 | 0.286741E+09 | 0.375933E+09 | 0.358212E+09 | 0.226624E+10 |
Annual Sum or Average | 0.177882E+11 | 0.749865E+10 | 0.102896E+11 | 0.192614E+11 | 0.145385E+11 |
Minimum of Months | 0.662673E+09 | 0.208368E+09 | 0.375933E+09 | 0.358212E+09 | 0.260346E+09 |
Maximum of Months | 0.225408E+10 | 0.104349E+10 | 0.127027E+10 | 0.313168E+10 | 0.226624E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.717009E+09 | 0.293689E+09 | 0.423320E+09 | 0.402072E+09 | 0.220328E+10 |
February | 0.955010E+09 | 0.419444E+09 | 0.535566E+09 | 0.601464E+09 | 0.206188E+10 |
March | 0.156128E+10 | 0.720800E+09 | 0.840480E+09 | 0.131190E+10 | 0.165279E+10 |
April | 0.165136E+10 | 0.706575E+09 | 0.944786E+09 | 0.158615E+10 | 0.122276E+10 |
May | 0.198779E+10 | 0.754886E+09 | 0.123290E+10 | 0.225537E+10 | 0.733038E+09 |
June | 0.210540E+10 | 0.849167E+09 | 0.125623E+10 | 0.272458E+10 | 0.416809E+09 |
July | 0.203754E+10 | 0.767277E+09 | 0.127027E+10 | 0.282835E+10 | 0.260346E+09 |
August | 0.225408E+10 | 0.104349E+10 | 0.121059E+10 | 0.313168E+10 | 0.349543E+09 |
September | 0.154860E+10 | 0.676733E+09 | 0.871864E+09 | 0.191671E+10 | 0.580996E+09 |
October | 0.158650E+10 | 0.771474E+09 | 0.815021E+09 | 0.172855E+10 | 0.110162E+10 |
November | 0.720980E+09 | 0.208368E+09 | 0.512611E+09 | 0.416331E+09 | 0.168916E+10 |
December | 0.662673E+09 | 0.286741E+09 | 0.375933E+09 | 0.358212E+09 | 0.226624E+10 |
Annual Sum or Average | 0.177882E+11 | 0.749865E+10 | 0.102896E+11 | 0.192614E+11 | 0.145385E+11 |
Minimum of Months | 0.662673E+09 | 0.208368E+09 | 0.375933E+09 | 0.358212E+09 | 0.260346E+09 |
Maximum of Months | 0.225408E+10 | 0.104349E+10 | 0.127027E+10 | 0.313168E+10 | 0.226624E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.716996E+09 | 0.293684E+09 | 0.423312E+09 | 0.402065E+09 | 0.220324E+10 |
February | 0.954992E+09 | 0.419436E+09 | 0.535556E+09 | 0.601453E+09 | 0.206184E+10 |
March | 0.156125E+10 | 0.720787E+09 | 0.840465E+09 | 0.131187E+10 | 0.165275E+10 |
April | 0.165133E+10 | 0.706562E+09 | 0.944769E+09 | 0.158612E+10 | 0.122274E+10 |
May | 0.198775E+10 | 0.754872E+09 | 0.123288E+10 | 0.225533E+10 | 0.733025E+09 |
June | 0.210536E+10 | 0.849152E+09 | 0.125621E+10 | 0.272453E+10 | 0.416801E+09 |
July | 0.203751E+10 | 0.767263E+09 | 0.127024E+10 | 0.282830E+10 | 0.260341E+09 |
August | 0.225404E+10 | 0.104347E+10 | 0.121057E+10 | 0.313163E+10 | 0.349536E+09 |
September | 0.154857E+10 | 0.676721E+09 | 0.871848E+09 | 0.191668E+10 | 0.580985E+09 |
October | 0.158647E+10 | 0.771460E+09 | 0.815006E+09 | 0.172852E+10 | 0.110160E+10 |
November | 0.720967E+09 | 0.208364E+09 | 0.512602E+09 | 0.416324E+09 | 0.168913E+10 |
December | 0.662661E+09 | 0.286736E+09 | 0.375926E+09 | 0.358205E+09 | 0.226620E+10 |
Annual Sum or Average | 0.177879E+11 | 0.749851E+10 | 0.102894E+11 | 0.192610E+11 | 0.145382E+11 |
Minimum of Months | 0.662661E+09 | 0.208364E+09 | 0.375926E+09 | 0.358205E+09 | 0.260341E+09 |
Maximum of Months | 0.225404E+10 | 0.104347E+10 | 0.127024E+10 | 0.313163E+10 | 0.226620E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.156460E+10 | 0.00 | 0.156460E+10 | 79229839.06 | 0.894169E+10 |
February | 0.193389E+10 | 0.00 | 0.193389E+10 | 0.157837E+09 | 0.843005E+10 |
March | 0.296916E+10 | 0.00 | 0.296916E+10 | 0.979875E+09 | 0.629178E+10 |
April | 0.345132E+10 | 9816615.63 | 0.344150E+10 | 0.209265E+10 | 0.432958E+10 |
May | 0.473143E+10 | 0.157654E+09 | 0.457377E+10 | 0.433688E+10 | 0.274118E+10 |
June | 0.485576E+10 | 0.260920E+09 | 0.459484E+10 | 0.597323E+10 | 0.143950E+10 |
July | 0.484904E+10 | 0.175358E+09 | 0.467369E+10 | 0.690038E+10 | 0.824378E+09 |
August | 0.429602E+10 | 51128718.85 | 0.424489E+10 | 0.604713E+10 | 0.111587E+10 |
September | 0.313402E+10 | 586874.67 | 0.313343E+10 | 0.333024E+10 | 0.217756E+10 |
October | 0.280268E+10 | 0.00 | 0.280268E+10 | 0.201938E+10 | 0.413131E+10 |
November | 0.190240E+10 | 0.00 | 0.190240E+10 | 0.477314E+09 | 0.622891E+10 |
December | 0.136475E+10 | 0.00 | 0.136475E+10 | 49180091.39 | 0.842780E+10 |
Annual Sum or Average | 0.378551E+11 | 0.655464E+09 | 0.371996E+11 | 0.324433E+11 | 0.550796E+11 |
Minimum of Months | 0.136475E+10 | 0.00 | 0.136475E+10 | 49180091.39 | 0.824378E+09 |
Maximum of Months | 0.485576E+10 | 0.260920E+09 | 0.467369E+10 | 0.690038E+10 | 0.894169E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.217884E+10 | 0.873541E+09 | 0.130530E+10 | 0.129757E+10 | 0.555401E+10 |
February | 0.305193E+10 | 0.142373E+10 | 0.162820E+10 | 0.206482E+10 | 0.509120E+10 |
March | 0.431045E+10 | 0.183326E+10 | 0.247718E+10 | 0.365734E+10 | 0.405845E+10 |
April | 0.500597E+10 | 0.219277E+10 | 0.281320E+10 | 0.497110E+10 | 0.279740E+10 |
May | 0.627356E+10 | 0.250729E+10 | 0.376627E+10 | 0.717220E+10 | 0.185016E+10 |
June | 0.562671E+10 | 0.203683E+10 | 0.358988E+10 | 0.730109E+10 | 0.975204E+09 |
July | 0.583972E+10 | 0.210741E+10 | 0.373231E+10 | 0.824507E+10 | 0.554183E+09 |
August | 0.657567E+10 | 0.296497E+10 | 0.361070E+10 | 0.922690E+10 | 0.754554E+09 |
September | 0.474597E+10 | 0.212933E+10 | 0.261664E+10 | 0.587194E+10 | 0.140834E+10 |
October | 0.444599E+10 | 0.201507E+10 | 0.243092E+10 | 0.486428E+10 | 0.267927E+10 |
November | 0.266081E+10 | 0.102178E+10 | 0.163903E+10 | 0.206331E+10 | 0.389772E+10 |
December | 0.214202E+10 | 0.100576E+10 | 0.113626E+10 | 0.139448E+10 | 0.519428E+10 |
Annual Sum or Average | 0.528576E+11 | 0.221117E+11 | 0.307459E+11 | 0.581301E+11 | 0.348148E+11 |
Minimum of Months | 0.214202E+10 | 0.873541E+09 | 0.113626E+10 | 0.129757E+10 | 0.554183E+09 |
Maximum of Months | 0.657567E+10 | 0.296497E+10 | 0.376627E+10 | 0.922690E+10 | 0.555401E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.809403E+10 | 0.530002E+10 | 0.279400E+10 | 0.777864E+10 | 0.814957E+10 |
February | 0.964261E+10 | 0.638262E+10 | 0.325999E+10 | 0.938968E+10 | 0.757290E+10 |
March | 0.963154E+10 | 0.534567E+10 | 0.428587E+10 | 0.998497E+10 | 0.627779E+10 |
April | 0.723264E+10 | 0.286000E+10 | 0.437264E+10 | 0.775541E+10 | 0.454007E+10 |
May | 0.654962E+10 | 0.136615E+10 | 0.518347E+10 | 0.749542E+10 | 0.297017E+10 |
June | 0.594834E+10 | 0.909266E+09 | 0.503908E+10 | 0.794729E+10 | 0.155147E+10 |
July | 0.644289E+10 | 0.111913E+10 | 0.532376E+10 | 0.959562E+10 | 0.859604E+09 |
August | 0.860377E+10 | 0.319128E+10 | 0.541249E+10 | 0.129003E+11 | 0.122399E+10 |
September | 0.903413E+10 | 0.467282E+10 | 0.436131E+10 | 0.119427E+11 | 0.231463E+10 |
October | 0.127885E+11 | 0.801932E+10 | 0.476920E+10 | 0.156868E+11 | 0.433241E+10 |
November | 0.858169E+10 | 0.515371E+10 | 0.342797E+10 | 0.892623E+10 | 0.600241E+10 |
December | 0.877271E+10 | 0.622804E+10 | 0.254467E+10 | 0.877435E+10 | 0.765497E+10 |
Annual Sum or Average | 0.101322E+12 | 0.505480E+11 | 0.507745E+11 | 0.118177E+12 | 0.534500E+11 |
Minimum of Months | 0.594834E+10 | 0.909266E+09 | 0.254467E+10 | 0.749542E+10 | 0.859604E+09 |
Maximum of Months | 0.127885E+11 | 0.801932E+10 | 0.541249E+10 | 0.156868E+11 | 0.814957E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.215100E+10 | 0.881058E+09 | 0.126995E+10 | 0.127843E+10 | 0.581932E+10 |
February | 0.286500E+10 | 0.125832E+10 | 0.160668E+10 | 0.189720E+10 | 0.544006E+10 |
March | 0.468379E+10 | 0.216238E+10 | 0.252141E+10 | 0.410166E+10 | 0.418868E+10 |
April | 0.495403E+10 | 0.211970E+10 | 0.283433E+10 | 0.495371E+10 | 0.302015E+10 |
May | 0.596331E+10 | 0.226463E+10 | 0.369868E+10 | 0.682921E+10 | 0.200831E+10 |
June | 0.631613E+10 | 0.254748E+10 | 0.376865E+10 | 0.822298E+10 | 0.111268E+10 |
July | 0.611257E+10 | 0.230181E+10 | 0.381077E+10 | 0.857744E+10 | 0.664967E+09 |
August | 0.676217E+10 | 0.313044E+10 | 0.363173E+10 | 0.950588E+10 | 0.895006E+09 |
September | 0.464574E+10 | 0.203018E+10 | 0.261556E+10 | 0.581008E+10 | 0.154929E+10 |
October | 0.475944E+10 | 0.231440E+10 | 0.244504E+10 | 0.530264E+10 | 0.288648E+10 |
November | 0.216292E+10 | 0.625098E+09 | 0.153782E+10 | 0.140218E+10 | 0.412294E+10 |
December | 0.198800E+10 | 0.860214E+09 | 0.112779E+10 | 0.120296E+10 | 0.550337E+10 |
Annual Sum or Average | 0.533641E+11 | 0.224957E+11 | 0.308684E+11 | 0.590844E+11 | 0.372112E+11 |
Minimum of Months | 0.198800E+10 | 0.625098E+09 | 0.112779E+10 | 0.120296E+10 | 0.664967E+09 |
Maximum of Months | 0.676217E+10 | 0.313044E+10 | 0.381077E+10 | 0.950588E+10 | 0.581932E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.156460E+10 | 0.00 | 0.156460E+10 | 0.101654E+09 | 0.850709E+10 |
February | 0.193389E+10 | 0.00 | 0.193389E+10 | 0.192384E+09 | 0.795695E+10 |
March | 0.296916E+10 | 0.00 | 0.296916E+10 | 0.106248E+10 | 0.585155E+10 |
April | 0.345132E+10 | 9816615.63 | 0.344150E+10 | 0.219000E+10 | 0.402051E+10 |
May | 0.473143E+10 | 0.157654E+09 | 0.457377E+10 | 0.437122E+10 | 0.263004E+10 |
June | 0.485576E+10 | 0.260920E+09 | 0.459484E+10 | 0.592483E+10 | 0.143104E+10 |
July | 0.484904E+10 | 0.175358E+09 | 0.467369E+10 | 0.682388E+10 | 0.847899E+09 |
August | 0.429602E+10 | 51128718.85 | 0.424489E+10 | 0.599365E+10 | 0.111962E+10 |
September | 0.313402E+10 | 586874.67 | 0.313343E+10 | 0.333966E+10 | 0.208612E+10 |
October | 0.280268E+10 | 0.00 | 0.280268E+10 | 0.212615E+10 | 0.381501E+10 |
November | 0.190240E+10 | 0.00 | 0.190240E+10 | 0.570274E+09 | 0.567168E+10 |
December | 0.136475E+10 | 0.00 | 0.136475E+10 | 80770393.80 | 0.777330E+10 |
Annual Sum or Average | 0.378551E+11 | 0.655464E+09 | 0.371996E+11 | 0.327770E+11 | 0.517108E+11 |
Minimum of Months | 0.136475E+10 | 0.00 | 0.136475E+10 | 80770393.80 | 0.847899E+09 |
Maximum of Months | 0.485576E+10 | 0.260920E+09 | 0.467369E+10 | 0.682388E+10 | 0.850709E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.217884E+10 | 0.873541E+09 | 0.130530E+10 | 0.133474E+10 | 0.527964E+10 |
February | 0.305193E+10 | 0.142373E+10 | 0.162820E+10 | 0.212836E+10 | 0.479760E+10 |
March | 0.431045E+10 | 0.183326E+10 | 0.247718E+10 | 0.371665E+10 | 0.379715E+10 |
April | 0.500597E+10 | 0.219277E+10 | 0.281320E+10 | 0.502238E+10 | 0.263241E+10 |
May | 0.627356E+10 | 0.250729E+10 | 0.376627E+10 | 0.717588E+10 | 0.178820E+10 |
June | 0.562671E+10 | 0.203683E+10 | 0.358988E+10 | 0.726344E+10 | 0.973290E+09 |
July | 0.583972E+10 | 0.210741E+10 | 0.373231E+10 | 0.819198E+10 | 0.570710E+09 |
August | 0.657567E+10 | 0.296497E+10 | 0.361070E+10 | 0.918165E+10 | 0.758973E+09 |
September | 0.474597E+10 | 0.212933E+10 | 0.261664E+10 | 0.586765E+10 | 0.136179E+10 |
October | 0.444599E+10 | 0.201507E+10 | 0.243092E+10 | 0.491908E+10 | 0.250708E+10 |
November | 0.266081E+10 | 0.102178E+10 | 0.163903E+10 | 0.215164E+10 | 0.357802E+10 |
December | 0.214202E+10 | 0.100576E+10 | 0.113626E+10 | 0.145810E+10 | 0.479237E+10 |
Annual Sum or Average | 0.528576E+11 | 0.221117E+11 | 0.307459E+11 | 0.584116E+11 | 0.328372E+11 |
Minimum of Months | 0.214202E+10 | 0.873541E+09 | 0.113626E+10 | 0.133474E+10 | 0.570710E+09 |
Maximum of Months | 0.657567E+10 | 0.296497E+10 | 0.376627E+10 | 0.918165E+10 | 0.527964E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.809403E+10 | 0.530002E+10 | 0.279400E+10 | 0.785142E+10 | 0.769867E+10 |
February | 0.964261E+10 | 0.638262E+10 | 0.325999E+10 | 0.950184E+10 | 0.709842E+10 |
March | 0.963154E+10 | 0.534567E+10 | 0.428587E+10 | 0.100634E+11 | 0.585238E+10 |
April | 0.723264E+10 | 0.286000E+10 | 0.437264E+10 | 0.783079E+10 | 0.424109E+10 |
May | 0.654962E+10 | 0.136615E+10 | 0.518347E+10 | 0.751466E+10 | 0.284571E+10 |
June | 0.594834E+10 | 0.909266E+09 | 0.503908E+10 | 0.789714E+10 | 0.153865E+10 |
July | 0.644289E+10 | 0.111913E+10 | 0.532376E+10 | 0.951856E+10 | 0.879526E+09 |
August | 0.860377E+10 | 0.319128E+10 | 0.541249E+10 | 0.128344E+11 | 0.122544E+10 |
September | 0.903413E+10 | 0.467282E+10 | 0.436131E+10 | 0.119334E+11 | 0.223187E+10 |
October | 0.127885E+11 | 0.801932E+10 | 0.476920E+10 | 0.157362E+11 | 0.407212E+10 |
November | 0.858169E+10 | 0.515371E+10 | 0.342797E+10 | 0.905667E+10 | 0.550241E+10 |
December | 0.877271E+10 | 0.622804E+10 | 0.254467E+10 | 0.890821E+10 | 0.704851E+10 |
Annual Sum or Average | 0.101322E+12 | 0.505480E+11 | 0.507745E+11 | 0.118647E+12 | 0.502348E+11 |
Minimum of Months | 0.594834E+10 | 0.909266E+09 | 0.254467E+10 | 0.751466E+10 | 0.879526E+09 |
Maximum of Months | 0.127885E+11 | 0.801932E+10 | 0.541249E+10 | 0.157362E+11 | 0.769867E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.215100E+10 | 0.881058E+09 | 0.126995E+10 | 0.130043E+10 | 0.553984E+10 |
February | 0.286500E+10 | 0.125832E+10 | 0.160668E+10 | 0.192188E+10 | 0.516875E+10 |
March | 0.468379E+10 | 0.216238E+10 | 0.252141E+10 | 0.413966E+10 | 0.394969E+10 |
April | 0.495403E+10 | 0.211970E+10 | 0.283433E+10 | 0.499265E+10 | 0.284908E+10 |
May | 0.596331E+10 | 0.226463E+10 | 0.369868E+10 | 0.683637E+10 | 0.193523E+10 |
June | 0.631613E+10 | 0.254748E+10 | 0.376865E+10 | 0.818427E+10 | 0.110320E+10 |
July | 0.611257E+10 | 0.230181E+10 | 0.381077E+10 | 0.852571E+10 | 0.673198E+09 |
August | 0.676217E+10 | 0.313044E+10 | 0.363173E+10 | 0.946363E+10 | 0.893542E+09 |
September | 0.464574E+10 | 0.203018E+10 | 0.261556E+10 | 0.580855E+10 | 0.149588E+10 |
October | 0.475944E+10 | 0.231440E+10 | 0.244504E+10 | 0.534688E+10 | 0.271607E+10 |
November | 0.216292E+10 | 0.625098E+09 | 0.153782E+10 | 0.145595E+10 | 0.382427E+10 |
December | 0.198800E+10 | 0.860214E+09 | 0.112779E+10 | 0.123875E+10 | 0.513973E+10 |
Annual Sum or Average | 0.533641E+11 | 0.224957E+11 | 0.308684E+11 | 0.592147E+11 | 0.352885E+11 |
Minimum of Months | 0.198800E+10 | 0.625098E+09 | 0.112779E+10 | 0.123875E+10 | 0.673198E+09 |
Maximum of Months | 0.676217E+10 | 0.313044E+10 | 0.381077E+10 | 0.946363E+10 | 0.553984E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 10.04 | 3757.75 | 584.16 | 0.00 | 584.16 | 0.00 | 0.00 |
February | 40.24 | 3867.58 | 799.40 | 0.00 | 799.40 | 0.00 | 0.00 |
March | 298.79 | 2663.57 | 1108.56 | 0.00 | 1108.56 | 0.00 | 0.00 |
April | 733.00 | 1896.92 | 1331.53 | 3.79 | 1327.74 | 0.00 | 0.00 |
May | 1591.74 | 1088.37 | 1766.52 | 58.86 | 1707.66 | 0.00 | 0.00 |
June | 2275.85 | 603.17 | 1873.37 | 100.66 | 1772.71 | 0.00 | 0.00 |
July | 2524.20 | 361.59 | 1810.43 | 65.47 | 1744.96 | 0.00 | 0.00 |
August | 2200.02 | 476.61 | 1603.96 | 19.09 | 1584.87 | 0.00 | 0.00 |
September | 1247.30 | 933.62 | 1209.12 | 0.23 | 1208.89 | 0.00 | 0.00 |
October | 702.01 | 1713.78 | 1046.40 | 0.00 | 1046.40 | 0.00 | 0.00 |
November | 137.70 | 2787.25 | 733.95 | 0.00 | 733.95 | 0.00 | 0.00 |
December | 5.24 | 3657.77 | 509.54 | 0.00 | 509.54 | 0.00 | 0.00 |
Annual Sum or Average | 986.95 | 1973.21 | 1200.38 | 20.78 | 1179.60 | 0.00 | 0.00 |
Minimum of Months | 5.24 | 361.59 | 509.54 | 0.00 | 509.54 | 0.00 | 0.00 |
Maximum of Months | 2524.20 | 3867.58 | 1873.37 | 100.66 | 1772.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 455.85 | 2301.15 | 813.49 | 326.14 | 487.35 | 0.00 | 0.00 |
February | 823.05 | 2288.23 | 1261.55 | 588.51 | 673.04 | 0.00 | 0.00 |
March | 1347.04 | 1649.10 | 1609.34 | 684.46 | 924.88 | 0.00 | 0.00 |
April | 1905.42 | 1163.02 | 1931.32 | 845.98 | 1085.34 | 0.00 | 0.00 |
May | 2686.84 | 724.58 | 2342.29 | 936.12 | 1406.17 | 0.00 | 0.00 |
June | 2821.75 | 396.00 | 2170.81 | 785.82 | 1384.99 | 0.00 | 0.00 |
July | 3070.68 | 224.36 | 2180.31 | 786.82 | 1393.49 | 0.00 | 0.00 |
August | 3442.64 | 293.70 | 2455.08 | 1107.00 | 1348.09 | 0.00 | 0.00 |
September | 2262.35 | 590.22 | 1831.01 | 821.50 | 1009.51 | 0.00 | 0.00 |
October | 1806.76 | 1074.07 | 1659.95 | 752.35 | 907.60 | 0.00 | 0.00 |
November | 764.22 | 1677.58 | 1026.55 | 394.21 | 632.34 | 0.00 | 0.00 |
December | 495.25 | 2164.30 | 799.74 | 375.51 | 424.23 | 0.00 | 0.00 |
Annual Sum or Average | 1830.45 | 1206.15 | 1676.11 | 701.16 | 974.95 | 0.00 | 0.00 |
Minimum of Months | 455.85 | 224.36 | 799.74 | 326.14 | 424.23 | 0.00 | 0.00 |
Maximum of Months | 3442.64 | 2301.15 | 2455.08 | 1107.00 | 1406.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2897.40 | 3222.13 | 3021.97 | 1978.81 | 1043.17 | 0.00 | 0.00 |
February | 3894.75 | 3253.96 | 3985.88 | 2638.33 | 1347.55 | 0.00 | 0.00 |
March | 3741.54 | 2467.40 | 3596.02 | 1995.85 | 1600.17 | 0.00 | 0.00 |
April | 2988.60 | 1863.53 | 2790.38 | 1103.40 | 1686.98 | 0.00 | 0.00 |
May | 2809.70 | 1148.90 | 2445.36 | 510.06 | 1935.29 | 0.00 | 0.00 |
June | 3062.46 | 635.79 | 2294.89 | 350.80 | 1944.10 | 0.00 | 0.00 |
July | 3559.64 | 360.57 | 2405.51 | 417.84 | 1987.67 | 0.00 | 0.00 |
August | 4804.07 | 493.07 | 3212.29 | 1191.49 | 2020.80 | 0.00 | 0.00 |
September | 4625.91 | 936.47 | 3485.40 | 1802.79 | 1682.61 | 0.00 | 0.00 |
October | 5900.02 | 1661.80 | 4774.70 | 2994.08 | 1780.62 | 0.00 | 0.00 |
November | 3442.96 | 2456.31 | 3310.85 | 1988.32 | 1322.53 | 0.00 | 0.00 |
December | 3271.66 | 3045.66 | 3275.37 | 2325.29 | 950.08 | 0.00 | 0.00 |
Annual Sum or Average | 3751.11 | 1787.01 | 3212.93 | 1602.87 | 1610.05 | 0.00 | 0.00 |
Minimum of Months | 2809.70 | 360.57 | 2294.89 | 350.80 | 950.08 | 0.00 | 0.00 |
Maximum of Months | 5900.02 | 3253.96 | 4774.70 | 2994.08 | 2020.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 450.35 | 2467.82 | 803.10 | 328.95 | 474.15 | 0.00 | 0.00 |
February | 745.86 | 2556.88 | 1184.28 | 520.14 | 664.14 | 0.00 | 0.00 |
March | 1469.41 | 1851.23 | 1748.74 | 807.34 | 941.39 | 0.00 | 0.00 |
April | 1835.80 | 1415.22 | 1911.29 | 817.79 | 1093.50 | 0.00 | 0.00 |
May | 2526.16 | 821.05 | 2226.45 | 845.52 | 1380.93 | 0.00 | 0.00 |
June | 3153.43 | 482.41 | 2436.79 | 982.83 | 1453.96 | 0.00 | 0.00 |
July | 3167.94 | 291.60 | 2282.18 | 859.40 | 1422.78 | 0.00 | 0.00 |
August | 3507.69 | 391.51 | 2524.71 | 1168.78 | 1355.94 | 0.00 | 0.00 |
September | 2218.40 | 672.44 | 1792.35 | 783.25 | 1009.10 | 0.00 | 0.00 |
October | 1936.09 | 1233.88 | 1776.98 | 864.10 | 912.88 | 0.00 | 0.00 |
November | 481.86 | 1955.04 | 834.46 | 241.17 | 593.30 | 0.00 | 0.00 |
December | 401.22 | 2538.34 | 742.24 | 321.17 | 421.07 | 0.00 | 0.00 |
Annual Sum or Average | 1832.31 | 1383.03 | 1692.17 | 713.34 | 978.83 | 0.00 | 0.00 |
Minimum of Months | 401.22 | 291.60 | 742.24 | 241.17 | 421.07 | 0.00 | 0.00 |
Maximum of Months | 3507.69 | 2556.88 | 2524.71 | 1168.78 | 1453.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 29.58 | 3338.44 | 584.16 | 0.00 | 584.16 | 0.00 | 0.00 |
February | 65.24 | 3484.65 | 799.39 | 0.00 | 799.39 | 0.00 | 0.00 |
March | 365.84 | 2349.08 | 1108.56 | 0.00 | 1108.56 | 0.00 | 0.00 |
April | 807.35 | 1670.36 | 1331.53 | 3.79 | 1327.74 | 0.00 | 0.00 |
May | 1619.21 | 1023.44 | 1766.51 | 58.86 | 1707.65 | 0.00 | 0.00 |
June | 2304.49 | 555.36 | 1873.36 | 100.66 | 1772.70 | 0.00 | 0.00 |
July | 2576.31 | 307.79 | 1810.43 | 65.47 | 1744.95 | 0.00 | 0.00 |
August | 2257.74 | 416.62 | 1603.95 | 19.09 | 1584.86 | 0.00 | 0.00 |
September | 1284.82 | 840.11 | 1209.11 | 0.23 | 1208.89 | 0.00 | 0.00 |
October | 753.95 | 1542.45 | 1046.40 | 0.00 | 1046.40 | 0.00 | 0.00 |
November | 184.15 | 2403.13 | 733.95 | 0.00 | 733.95 | 0.00 | 0.00 |
December | 18.36 | 3146.58 | 509.54 | 0.00 | 509.54 | 0.00 | 0.00 |
Annual Sum or Average | 1028.77 | 1746.56 | 1200.38 | 20.78 | 1179.59 | 0.00 | 0.00 |
Minimum of Months | 18.36 | 307.79 | 509.54 | 0.00 | 509.54 | 0.00 | 0.00 |
Maximum of Months | 2576.31 | 3484.65 | 1873.36 | 100.66 | 1772.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 484.46 | 2073.63 | 813.49 | 326.14 | 487.34 | 0.00 | 0.00 |
February | 853.51 | 2104.50 | 1261.54 | 588.51 | 673.03 | 0.00 | 0.00 |
March | 1365.50 | 1515.25 | 1609.34 | 684.46 | 924.87 | 0.00 | 0.00 |
April | 1917.86 | 1079.24 | 1931.32 | 845.98 | 1085.34 | 0.00 | 0.00 |
May | 2677.79 | 690.77 | 2342.28 | 936.12 | 1406.16 | 0.00 | 0.00 |
June | 2816.78 | 376.24 | 2170.80 | 785.81 | 1384.98 | 0.00 | 0.00 |
July | 3078.36 | 206.91 | 2180.30 | 786.82 | 1393.48 | 0.00 | 0.00 |
August | 3444.93 | 281.72 | 2455.07 | 1106.99 | 1348.08 | 0.00 | 0.00 |
September | 2265.41 | 543.34 | 1831.01 | 821.50 | 1009.51 | 0.00 | 0.00 |
October | 1816.11 | 1000.32 | 1659.94 | 752.34 | 907.60 | 0.00 | 0.00 |
November | 796.03 | 1503.75 | 1026.55 | 394.20 | 632.34 | 0.00 | 0.00 |
December | 520.64 | 1939.32 | 799.74 | 375.51 | 424.23 | 0.00 | 0.00 |
Annual Sum or Average | 1843.29 | 1103.97 | 1676.10 | 701.16 | 974.95 | 0.00 | 0.00 |
Minimum of Months | 484.46 | 206.91 | 799.74 | 326.14 | 424.23 | 0.00 | 0.00 |
Maximum of Months | 3444.93 | 2104.50 | 2455.07 | 1106.99 | 1406.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2904.21 | 3042.70 | 3021.96 | 1978.80 | 1043.16 | 0.00 | 0.00 |
February | 3881.32 | 3130.33 | 3985.87 | 2638.32 | 1347.55 | 0.00 | 0.00 |
March | 3727.96 | 2343.86 | 3596.00 | 1995.84 | 1600.16 | 0.00 | 0.00 |
April | 2992.06 | 1751.57 | 2790.37 | 1103.40 | 1686.98 | 0.00 | 0.00 |
May | 2798.47 | 1108.93 | 2445.35 | 510.06 | 1935.29 | 0.00 | 0.00 |
June | 3066.08 | 598.56 | 2294.89 | 350.80 | 1944.09 | 0.00 | 0.00 |
July | 3582.59 | 320.94 | 2405.50 | 417.83 | 1987.67 | 0.00 | 0.00 |
August | 4816.44 | 456.99 | 3212.28 | 1191.49 | 2020.79 | 0.00 | 0.00 |
September | 4607.51 | 892.99 | 3485.39 | 1802.79 | 1682.60 | 0.00 | 0.00 |
October | 5856.76 | 1617.54 | 4774.69 | 2994.07 | 1780.62 | 0.00 | 0.00 |
November | 3443.76 | 2315.74 | 3310.84 | 1988.32 | 1322.52 | 0.00 | 0.00 |
December | 3275.97 | 2858.04 | 3275.36 | 2325.28 | 950.07 | 0.00 | 0.00 |
Annual Sum or Average | 3747.38 | 1694.89 | 3212.92 | 1602.87 | 1610.05 | 0.00 | 0.00 |
Minimum of Months | 2798.47 | 320.94 | 2294.89 | 350.80 | 950.07 | 0.00 | 0.00 |
Maximum of Months | 5856.76 | 3130.33 | 4774.69 | 2994.07 | 2020.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 477.31 | 2172.69 | 803.09 | 328.95 | 474.14 | 0.00 | 0.00 |
February | 784.23 | 2248.70 | 1184.28 | 520.14 | 664.14 | 0.00 | 0.00 |
March | 1531.38 | 1563.87 | 1748.73 | 807.34 | 941.39 | 0.00 | 0.00 |
April | 1911.15 | 1165.18 | 1911.28 | 817.79 | 1093.49 | 0.00 | 0.00 |
May | 2549.74 | 749.82 | 2226.45 | 845.52 | 1380.93 | 0.00 | 0.00 |
June | 3172.45 | 429.28 | 2436.78 | 982.82 | 1453.96 | 0.00 | 0.00 |
July | 3202.45 | 248.27 | 2282.17 | 859.40 | 1422.78 | 0.00 | 0.00 |
August | 3549.09 | 334.16 | 2524.70 | 1168.77 | 1355.93 | 0.00 | 0.00 |
September | 2241.54 | 597.72 | 1792.34 | 783.25 | 1009.09 | 0.00 | 0.00 |
October | 1979.78 | 1077.69 | 1776.97 | 864.10 | 912.87 | 0.00 | 0.00 |
November | 540.97 | 1590.64 | 834.46 | 241.16 | 593.29 | 0.00 | 0.00 |
December | 449.13 | 2054.72 | 742.23 | 321.17 | 421.07 | 0.00 | 0.00 |
Annual Sum or Average | 1873.55 | 1179.96 | 1692.16 | 713.33 | 978.83 | 0.00 | 0.00 |
Minimum of Months | 449.13 | 248.27 | 742.23 | 241.16 | 421.07 | 0.00 | 0.00 |
Maximum of Months | 3549.09 | 2248.70 | 2524.70 | 1168.77 | 1453.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 37.95 | 3176.18 | 584.16 | 0.00 | 584.16 | 0.00 | 0.00 |
February | 79.52 | 3289.08 | 799.39 | 0.00 | 799.39 | 0.00 | 0.00 |
March | 396.69 | 2184.72 | 1108.56 | 0.00 | 1108.56 | 0.00 | 0.00 |
April | 844.91 | 1551.12 | 1331.53 | 3.79 | 1327.74 | 0.00 | 0.00 |
May | 1632.03 | 981.95 | 1766.51 | 58.86 | 1707.65 | 0.00 | 0.00 |
June | 2285.81 | 552.10 | 1873.36 | 100.66 | 1772.70 | 0.00 | 0.00 |
July | 2547.74 | 316.57 | 1810.43 | 65.47 | 1744.95 | 0.00 | 0.00 |
August | 2237.77 | 418.02 | 1603.95 | 19.09 | 1584.86 | 0.00 | 0.00 |
September | 1288.45 | 804.83 | 1209.11 | 0.23 | 1208.89 | 0.00 | 0.00 |
October | 793.81 | 1424.36 | 1046.40 | 0.00 | 1046.40 | 0.00 | 0.00 |
November | 220.01 | 2188.15 | 733.95 | 0.00 | 733.95 | 0.00 | 0.00 |
December | 30.16 | 2902.22 | 509.54 | 0.00 | 509.54 | 0.00 | 0.00 |
Annual Sum or Average | 1039.35 | 1639.74 | 1200.38 | 20.78 | 1179.59 | 0.00 | 0.00 |
Minimum of Months | 30.16 | 316.57 | 509.54 | 0.00 | 509.54 | 0.00 | 0.00 |
Maximum of Months | 2547.74 | 3289.08 | 1873.36 | 100.66 | 1772.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 498.33 | 1971.19 | 813.49 | 326.14 | 487.34 | 0.00 | 0.00 |
February | 879.78 | 1983.13 | 1261.54 | 588.51 | 673.03 | 0.00 | 0.00 |
March | 1387.64 | 1417.69 | 1609.34 | 684.46 | 924.87 | 0.00 | 0.00 |
April | 1937.65 | 1015.59 | 1931.32 | 845.98 | 1085.34 | 0.00 | 0.00 |
May | 2679.17 | 667.64 | 2342.28 | 936.12 | 1406.16 | 0.00 | 0.00 |
June | 2802.25 | 375.50 | 2170.80 | 785.81 | 1384.98 | 0.00 | 0.00 |
July | 3058.53 | 213.08 | 2180.30 | 786.82 | 1393.48 | 0.00 | 0.00 |
August | 3428.04 | 283.37 | 2455.07 | 1106.99 | 1348.08 | 0.00 | 0.00 |
September | 2263.75 | 525.38 | 1831.01 | 821.50 | 1009.51 | 0.00 | 0.00 |
October | 1836.58 | 936.04 | 1659.94 | 752.34 | 907.60 | 0.00 | 0.00 |
November | 830.11 | 1380.41 | 1026.55 | 394.20 | 632.34 | 0.00 | 0.00 |
December | 544.39 | 1789.27 | 799.74 | 375.51 | 424.23 | 0.00 | 0.00 |
Annual Sum or Average | 1852.22 | 1041.26 | 1676.10 | 701.16 | 974.95 | 0.00 | 0.00 |
Minimum of Months | 498.33 | 213.08 | 799.74 | 326.14 | 424.23 | 0.00 | 0.00 |
Maximum of Months | 3428.04 | 1983.13 | 2455.07 | 1106.99 | 1406.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2931.38 | 2874.35 | 3021.96 | 1978.80 | 1043.16 | 0.00 | 0.00 |
February | 3927.68 | 2934.20 | 3985.87 | 2638.32 | 1347.55 | 0.00 | 0.00 |
March | 3757.23 | 2185.03 | 3596.00 | 1995.84 | 1600.16 | 0.00 | 0.00 |
April | 3021.14 | 1636.22 | 2790.37 | 1103.40 | 1686.98 | 0.00 | 0.00 |
May | 2805.65 | 1062.47 | 2445.35 | 510.06 | 1935.29 | 0.00 | 0.00 |
June | 3046.74 | 593.62 | 2294.89 | 350.80 | 1944.09 | 0.00 | 0.00 |
July | 3553.82 | 328.38 | 2405.50 | 417.83 | 1987.67 | 0.00 | 0.00 |
August | 4791.81 | 457.53 | 3212.28 | 1191.49 | 2020.79 | 0.00 | 0.00 |
September | 4603.95 | 861.06 | 3485.39 | 1802.79 | 1682.60 | 0.00 | 0.00 |
October | 5875.24 | 1520.36 | 4774.69 | 2994.07 | 1780.62 | 0.00 | 0.00 |
November | 3494.09 | 2122.84 | 3310.84 | 1988.32 | 1322.52 | 0.00 | 0.00 |
December | 3325.94 | 2631.61 | 3275.36 | 2325.28 | 950.07 | 0.00 | 0.00 |
Annual Sum or Average | 3762.26 | 1592.94 | 3212.92 | 1602.87 | 1610.05 | 0.00 | 0.00 |
Minimum of Months | 2805.65 | 328.38 | 2294.89 | 350.80 | 950.07 | 0.00 | 0.00 |
Maximum of Months | 5875.24 | 2934.20 | 4774.69 | 2994.07 | 2020.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 485.53 | 2068.34 | 803.09 | 328.95 | 474.14 | 0.00 | 0.00 |
February | 794.43 | 2136.55 | 1184.28 | 520.14 | 664.14 | 0.00 | 0.00 |
March | 1545.57 | 1474.64 | 1748.73 | 807.34 | 941.39 | 0.00 | 0.00 |
April | 1926.18 | 1099.18 | 1911.28 | 817.79 | 1093.49 | 0.00 | 0.00 |
May | 2552.41 | 722.53 | 2226.45 | 845.52 | 1380.93 | 0.00 | 0.00 |
June | 3157.51 | 425.62 | 2436.78 | 982.82 | 1453.96 | 0.00 | 0.00 |
July | 3183.14 | 251.34 | 2282.17 | 859.40 | 1422.78 | 0.00 | 0.00 |
August | 3533.31 | 333.61 | 2524.70 | 1168.77 | 1355.93 | 0.00 | 0.00 |
September | 2240.95 | 577.11 | 1792.34 | 783.25 | 1009.09 | 0.00 | 0.00 |
October | 1996.30 | 1014.06 | 1776.97 | 864.10 | 912.87 | 0.00 | 0.00 |
November | 561.71 | 1475.41 | 834.46 | 241.16 | 593.29 | 0.00 | 0.00 |
December | 462.50 | 1918.96 | 742.23 | 321.17 | 421.07 | 0.00 | 0.00 |
Annual Sum or Average | 1877.69 | 1118.99 | 1692.16 | 713.33 | 978.83 | 0.00 | 0.00 |
Minimum of Months | 462.50 | 251.34 | 742.23 | 241.16 | 421.07 | 0.00 | 0.00 |
Maximum of Months | 3533.31 | 2136.55 | 2524.70 | 1168.77 | 1453.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 26883335.21 | 0.100647E+11 | 0.156461E+10 | 0.00 | 0.156461E+10 | 0.00 | 0.00 |
February | 97351766.25 | 0.935644E+10 | 0.193390E+10 | 0.00 | 0.193390E+10 | 0.00 | 0.00 |
March | 0.800291E+09 | 0.713410E+10 | 0.296917E+10 | 0.00 | 0.296917E+10 | 0.00 | 0.00 |
April | 0.189995E+10 | 0.491683E+10 | 0.345133E+10 | 9816650.49 | 0.344151E+10 | 0.00 | 0.00 |
May | 0.426333E+10 | 0.291508E+10 | 0.473145E+10 | 0.157654E+09 | 0.457379E+10 | 0.00 | 0.00 |
June | 0.589899E+10 | 0.156342E+10 | 0.485578E+10 | 0.260921E+09 | 0.459486E+10 | 0.00 | 0.00 |
July | 0.676082E+10 | 0.968491E+09 | 0.484906E+10 | 0.175358E+09 | 0.467370E+10 | 0.00 | 0.00 |
August | 0.589253E+10 | 0.127654E+10 | 0.429604E+10 | 51128900.42 | 0.424491E+10 | 0.00 | 0.00 |
September | 0.323299E+10 | 0.241994E+10 | 0.313403E+10 | 586876.76 | 0.313344E+10 | 0.00 | 0.00 |
October | 0.188026E+10 | 0.459019E+10 | 0.280269E+10 | 0.00 | 0.280269E+10 | 0.00 | 0.00 |
November | 0.356920E+09 | 0.722454E+10 | 0.190240E+10 | 0.00 | 0.190240E+10 | 0.00 | 0.00 |
December | 14027892.59 | 0.979698E+10 | 0.136475E+10 | 0.00 | 0.136475E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.311243E+11 | 0.622273E+11 | 0.378552E+11 | 0.655466E+09 | 0.371997E+11 | 0.00 | 0.00 |
Minimum of Months | 14027892.59 | 0.968491E+09 | 0.136475E+10 | 0.00 | 0.136475E+10 | 0.00 | 0.00 |
Maximum of Months | 0.676082E+10 | 0.100647E+11 | 0.485578E+10 | 0.260921E+09 | 0.467370E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.122095E+10 | 0.616340E+10 | 0.217885E+10 | 0.873544E+09 | 0.130531E+10 | 0.00 | 0.00 |
February | 0.199112E+10 | 0.553567E+10 | 0.305194E+10 | 0.142373E+10 | 0.162821E+10 | 0.00 | 0.00 |
March | 0.360790E+10 | 0.441695E+10 | 0.431046E+10 | 0.183327E+10 | 0.247719E+10 | 0.00 | 0.00 |
April | 0.493884E+10 | 0.301454E+10 | 0.500599E+10 | 0.219278E+10 | 0.281321E+10 | 0.00 | 0.00 |
May | 0.719644E+10 | 0.194070E+10 | 0.627359E+10 | 0.250730E+10 | 0.376629E+10 | 0.00 | 0.00 |
June | 0.731399E+10 | 0.102644E+10 | 0.562673E+10 | 0.203684E+10 | 0.358989E+10 | 0.00 | 0.00 |
July | 0.822452E+10 | 0.600922E+09 | 0.583974E+10 | 0.210742E+10 | 0.373232E+10 | 0.00 | 0.00 |
August | 0.922077E+10 | 0.786643E+09 | 0.657569E+10 | 0.296498E+10 | 0.361071E+10 | 0.00 | 0.00 |
September | 0.586402E+10 | 0.152986E+10 | 0.474599E+10 | 0.212934E+10 | 0.261665E+10 | 0.00 | 0.00 |
October | 0.483923E+10 | 0.287678E+10 | 0.444601E+10 | 0.201508E+10 | 0.243093E+10 | 0.00 | 0.00 |
November | 0.198086E+10 | 0.434829E+10 | 0.266082E+10 | 0.102178E+10 | 0.163904E+10 | 0.00 | 0.00 |
December | 0.132648E+10 | 0.579685E+10 | 0.214203E+10 | 0.100576E+10 | 0.113626E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.577251E+11 | 0.380370E+11 | 0.528578E+11 | 0.221118E+11 | 0.307460E+11 | 0.00 | 0.00 |
Minimum of Months | 0.122095E+10 | 0.600922E+09 | 0.214203E+10 | 0.873544E+09 | 0.113626E+10 | 0.00 | 0.00 |
Maximum of Months | 0.922077E+10 | 0.616340E+10 | 0.657569E+10 | 0.296498E+10 | 0.376629E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.776040E+10 | 0.863016E+10 | 0.809406E+10 | 0.530004E+10 | 0.279402E+10 | 0.00 | 0.00 |
February | 0.942217E+10 | 0.787197E+10 | 0.964264E+10 | 0.638265E+10 | 0.326000E+10 | 0.00 | 0.00 |
March | 0.100213E+11 | 0.660867E+10 | 0.963157E+10 | 0.534569E+10 | 0.428588E+10 | 0.00 | 0.00 |
April | 0.774646E+10 | 0.483027E+10 | 0.723267E+10 | 0.286001E+10 | 0.437266E+10 | 0.00 | 0.00 |
May | 0.752550E+10 | 0.307720E+10 | 0.654964E+10 | 0.136615E+10 | 0.518349E+10 | 0.00 | 0.00 |
June | 0.793788E+10 | 0.164797E+10 | 0.594837E+10 | 0.909269E+09 | 0.503910E+10 | 0.00 | 0.00 |
July | 0.953415E+10 | 0.965747E+09 | 0.644292E+10 | 0.111913E+10 | 0.532378E+10 | 0.00 | 0.00 |
August | 0.128672E+11 | 0.132063E+10 | 0.860380E+10 | 0.319129E+10 | 0.541251E+10 | 0.00 | 0.00 |
September | 0.119904E+11 | 0.242734E+10 | 0.903416E+10 | 0.467284E+10 | 0.436132E+10 | 0.00 | 0.00 |
October | 0.158026E+11 | 0.445096E+10 | 0.127886E+11 | 0.801935E+10 | 0.476922E+10 | 0.00 | 0.00 |
November | 0.892415E+10 | 0.636675E+10 | 0.858172E+10 | 0.515373E+10 | 0.342799E+10 | 0.00 | 0.00 |
December | 0.876281E+10 | 0.815749E+10 | 0.877274E+10 | 0.622806E+10 | 0.254468E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.118295E+12 | 0.563552E+11 | 0.101323E+12 | 0.505482E+11 | 0.507746E+11 | 0.00 | 0.00 |
Minimum of Months | 0.752550E+10 | 0.965747E+09 | 0.594837E+10 | 0.909269E+09 | 0.254468E+10 | 0.00 | 0.00 |
Maximum of Months | 0.158026E+11 | 0.863016E+10 | 0.127886E+11 | 0.801935E+10 | 0.541251E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.120621E+10 | 0.660981E+10 | 0.215101E+10 | 0.881062E+09 | 0.126995E+10 | 0.00 | 0.00 |
February | 0.180438E+10 | 0.618559E+10 | 0.286501E+10 | 0.125832E+10 | 0.160669E+10 | 0.00 | 0.00 |
March | 0.393567E+10 | 0.495833E+10 | 0.468381E+10 | 0.216239E+10 | 0.252142E+10 | 0.00 | 0.00 |
April | 0.475841E+10 | 0.366826E+10 | 0.495405E+10 | 0.211971E+10 | 0.283434E+10 | 0.00 | 0.00 |
May | 0.676607E+10 | 0.219910E+10 | 0.596334E+10 | 0.226464E+10 | 0.369869E+10 | 0.00 | 0.00 |
June | 0.817370E+10 | 0.125042E+10 | 0.631615E+10 | 0.254749E+10 | 0.376867E+10 | 0.00 | 0.00 |
July | 0.848500E+10 | 0.781032E+09 | 0.611260E+10 | 0.230182E+10 | 0.381078E+10 | 0.00 | 0.00 |
August | 0.939499E+10 | 0.104862E+10 | 0.676220E+10 | 0.313045E+10 | 0.363174E+10 | 0.00 | 0.00 |
September | 0.575010E+10 | 0.174298E+10 | 0.464576E+10 | 0.203019E+10 | 0.261558E+10 | 0.00 | 0.00 |
October | 0.518563E+10 | 0.330483E+10 | 0.475946E+10 | 0.231441E+10 | 0.244505E+10 | 0.00 | 0.00 |
November | 0.124899E+10 | 0.506746E+10 | 0.216293E+10 | 0.625101E+09 | 0.153782E+10 | 0.00 | 0.00 |
December | 0.107463E+10 | 0.679869E+10 | 0.198801E+10 | 0.860217E+09 | 0.112779E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.577838E+11 | 0.436151E+11 | 0.533643E+11 | 0.224958E+11 | 0.308685E+11 | 0.00 | 0.00 |
Minimum of Months | 0.107463E+10 | 0.781032E+09 | 0.198801E+10 | 0.625101E+09 | 0.112779E+10 | 0.00 | 0.00 |
Maximum of Months | 0.939499E+10 | 0.679869E+10 | 0.676220E+10 | 0.313045E+10 | 0.381078E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 79229839.06 | 0.894169E+10 | 0.156460E+10 | 0.00 | 0.156460E+10 | 0.00 | 0.00 |
February | 0.157837E+09 | 0.843005E+10 | 0.193389E+10 | 0.00 | 0.193389E+10 | 0.00 | 0.00 |
March | 0.979875E+09 | 0.629178E+10 | 0.296916E+10 | 0.00 | 0.296916E+10 | 0.00 | 0.00 |
April | 0.209265E+10 | 0.432958E+10 | 0.345132E+10 | 9816615.63 | 0.344150E+10 | 0.00 | 0.00 |
May | 0.433688E+10 | 0.274118E+10 | 0.473143E+10 | 0.157654E+09 | 0.457377E+10 | 0.00 | 0.00 |
June | 0.597323E+10 | 0.143950E+10 | 0.485576E+10 | 0.260920E+09 | 0.459484E+10 | 0.00 | 0.00 |
July | 0.690038E+10 | 0.824378E+09 | 0.484904E+10 | 0.175358E+09 | 0.467369E+10 | 0.00 | 0.00 |
August | 0.604713E+10 | 0.111587E+10 | 0.429602E+10 | 51128718.85 | 0.424489E+10 | 0.00 | 0.00 |
September | 0.333024E+10 | 0.217756E+10 | 0.313402E+10 | 586874.67 | 0.313343E+10 | 0.00 | 0.00 |
October | 0.201938E+10 | 0.413131E+10 | 0.280268E+10 | 0.00 | 0.280268E+10 | 0.00 | 0.00 |
November | 0.477314E+09 | 0.622891E+10 | 0.190240E+10 | 0.00 | 0.190240E+10 | 0.00 | 0.00 |
December | 49180091.39 | 0.842780E+10 | 0.136475E+10 | 0.00 | 0.136475E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.324433E+11 | 0.550796E+11 | 0.378551E+11 | 0.655464E+09 | 0.371996E+11 | 0.00 | 0.00 |
Minimum of Months | 49180091.39 | 0.824378E+09 | 0.136475E+10 | 0.00 | 0.136475E+10 | 0.00 | 0.00 |
Maximum of Months | 0.690038E+10 | 0.894169E+10 | 0.485576E+10 | 0.260920E+09 | 0.467369E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.129757E+10 | 0.555401E+10 | 0.217884E+10 | 0.873541E+09 | 0.130530E+10 | 0.00 | 0.00 |
February | 0.206482E+10 | 0.509120E+10 | 0.305193E+10 | 0.142373E+10 | 0.162820E+10 | 0.00 | 0.00 |
March | 0.365734E+10 | 0.405845E+10 | 0.431045E+10 | 0.183326E+10 | 0.247718E+10 | 0.00 | 0.00 |
April | 0.497110E+10 | 0.279740E+10 | 0.500597E+10 | 0.219277E+10 | 0.281320E+10 | 0.00 | 0.00 |
May | 0.717220E+10 | 0.185016E+10 | 0.627356E+10 | 0.250729E+10 | 0.376627E+10 | 0.00 | 0.00 |
June | 0.730109E+10 | 0.975204E+09 | 0.562671E+10 | 0.203683E+10 | 0.358988E+10 | 0.00 | 0.00 |
July | 0.824507E+10 | 0.554183E+09 | 0.583972E+10 | 0.210741E+10 | 0.373231E+10 | 0.00 | 0.00 |
August | 0.922690E+10 | 0.754554E+09 | 0.657567E+10 | 0.296497E+10 | 0.361070E+10 | 0.00 | 0.00 |
September | 0.587194E+10 | 0.140834E+10 | 0.474597E+10 | 0.212933E+10 | 0.261664E+10 | 0.00 | 0.00 |
October | 0.486428E+10 | 0.267927E+10 | 0.444599E+10 | 0.201507E+10 | 0.243092E+10 | 0.00 | 0.00 |
November | 0.206331E+10 | 0.389772E+10 | 0.266081E+10 | 0.102178E+10 | 0.163903E+10 | 0.00 | 0.00 |
December | 0.139448E+10 | 0.519428E+10 | 0.214202E+10 | 0.100576E+10 | 0.113626E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.581301E+11 | 0.348148E+11 | 0.528576E+11 | 0.221117E+11 | 0.307459E+11 | 0.00 | 0.00 |
Minimum of Months | 0.129757E+10 | 0.554183E+09 | 0.214202E+10 | 0.873541E+09 | 0.113626E+10 | 0.00 | 0.00 |
Maximum of Months | 0.922690E+10 | 0.555401E+10 | 0.657567E+10 | 0.296497E+10 | 0.376627E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.777864E+10 | 0.814957E+10 | 0.809403E+10 | 0.530002E+10 | 0.279400E+10 | 0.00 | 0.00 |
February | 0.938968E+10 | 0.757290E+10 | 0.964261E+10 | 0.638262E+10 | 0.325999E+10 | 0.00 | 0.00 |
March | 0.998497E+10 | 0.627779E+10 | 0.963154E+10 | 0.534567E+10 | 0.428587E+10 | 0.00 | 0.00 |
April | 0.775541E+10 | 0.454007E+10 | 0.723264E+10 | 0.286000E+10 | 0.437264E+10 | 0.00 | 0.00 |
May | 0.749542E+10 | 0.297017E+10 | 0.654962E+10 | 0.136615E+10 | 0.518347E+10 | 0.00 | 0.00 |
June | 0.794729E+10 | 0.155147E+10 | 0.594834E+10 | 0.909266E+09 | 0.503908E+10 | 0.00 | 0.00 |
July | 0.959562E+10 | 0.859604E+09 | 0.644289E+10 | 0.111913E+10 | 0.532376E+10 | 0.00 | 0.00 |
August | 0.129003E+11 | 0.122399E+10 | 0.860377E+10 | 0.319128E+10 | 0.541249E+10 | 0.00 | 0.00 |
September | 0.119427E+11 | 0.231463E+10 | 0.903413E+10 | 0.467282E+10 | 0.436131E+10 | 0.00 | 0.00 |
October | 0.156868E+11 | 0.433241E+10 | 0.127885E+11 | 0.801932E+10 | 0.476920E+10 | 0.00 | 0.00 |
November | 0.892623E+10 | 0.600241E+10 | 0.858169E+10 | 0.515371E+10 | 0.342797E+10 | 0.00 | 0.00 |
December | 0.877435E+10 | 0.765497E+10 | 0.877271E+10 | 0.622804E+10 | 0.254467E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.118177E+12 | 0.534500E+11 | 0.101322E+12 | 0.505480E+11 | 0.507745E+11 | 0.00 | 0.00 |
Minimum of Months | 0.749542E+10 | 0.859604E+09 | 0.594834E+10 | 0.909266E+09 | 0.254467E+10 | 0.00 | 0.00 |
Maximum of Months | 0.156868E+11 | 0.814957E+10 | 0.127885E+11 | 0.801932E+10 | 0.541249E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.127843E+10 | 0.581932E+10 | 0.215100E+10 | 0.881058E+09 | 0.126995E+10 | 0.00 | 0.00 |
February | 0.189720E+10 | 0.544006E+10 | 0.286500E+10 | 0.125832E+10 | 0.160668E+10 | 0.00 | 0.00 |
March | 0.410166E+10 | 0.418868E+10 | 0.468379E+10 | 0.216238E+10 | 0.252141E+10 | 0.00 | 0.00 |
April | 0.495371E+10 | 0.302015E+10 | 0.495403E+10 | 0.211970E+10 | 0.283433E+10 | 0.00 | 0.00 |
May | 0.682921E+10 | 0.200831E+10 | 0.596331E+10 | 0.226463E+10 | 0.369868E+10 | 0.00 | 0.00 |
June | 0.822298E+10 | 0.111268E+10 | 0.631613E+10 | 0.254748E+10 | 0.376865E+10 | 0.00 | 0.00 |
July | 0.857744E+10 | 0.664967E+09 | 0.611257E+10 | 0.230181E+10 | 0.381077E+10 | 0.00 | 0.00 |
August | 0.950588E+10 | 0.895006E+09 | 0.676217E+10 | 0.313044E+10 | 0.363173E+10 | 0.00 | 0.00 |
September | 0.581008E+10 | 0.154929E+10 | 0.464574E+10 | 0.203018E+10 | 0.261556E+10 | 0.00 | 0.00 |
October | 0.530264E+10 | 0.288648E+10 | 0.475944E+10 | 0.231440E+10 | 0.244504E+10 | 0.00 | 0.00 |
November | 0.140218E+10 | 0.412294E+10 | 0.216292E+10 | 0.625098E+09 | 0.153782E+10 | 0.00 | 0.00 |
December | 0.120296E+10 | 0.550337E+10 | 0.198800E+10 | 0.860214E+09 | 0.112779E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.590844E+11 | 0.372112E+11 | 0.533641E+11 | 0.224957E+11 | 0.308684E+11 | 0.00 | 0.00 |
Minimum of Months | 0.120296E+10 | 0.664967E+09 | 0.198800E+10 | 0.625098E+09 | 0.112779E+10 | 0.00 | 0.00 |
Maximum of Months | 0.950588E+10 | 0.581932E+10 | 0.676217E+10 | 0.313044E+10 | 0.381077E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.101654E+09 | 0.850709E+10 | 0.156460E+10 | 0.00 | 0.156460E+10 | 0.00 | 0.00 |
February | 0.192384E+09 | 0.795695E+10 | 0.193389E+10 | 0.00 | 0.193389E+10 | 0.00 | 0.00 |
March | 0.106248E+10 | 0.585155E+10 | 0.296916E+10 | 0.00 | 0.296916E+10 | 0.00 | 0.00 |
April | 0.219000E+10 | 0.402051E+10 | 0.345132E+10 | 9816615.63 | 0.344150E+10 | 0.00 | 0.00 |
May | 0.437122E+10 | 0.263004E+10 | 0.473143E+10 | 0.157654E+09 | 0.457377E+10 | 0.00 | 0.00 |
June | 0.592483E+10 | 0.143104E+10 | 0.485576E+10 | 0.260920E+09 | 0.459484E+10 | 0.00 | 0.00 |
July | 0.682388E+10 | 0.847899E+09 | 0.484904E+10 | 0.175358E+09 | 0.467369E+10 | 0.00 | 0.00 |
August | 0.599365E+10 | 0.111962E+10 | 0.429602E+10 | 51128718.85 | 0.424489E+10 | 0.00 | 0.00 |
September | 0.333966E+10 | 0.208612E+10 | 0.313402E+10 | 586874.67 | 0.313343E+10 | 0.00 | 0.00 |
October | 0.212615E+10 | 0.381501E+10 | 0.280268E+10 | 0.00 | 0.280268E+10 | 0.00 | 0.00 |
November | 0.570274E+09 | 0.567168E+10 | 0.190240E+10 | 0.00 | 0.190240E+10 | 0.00 | 0.00 |
December | 80770393.80 | 0.777330E+10 | 0.136475E+10 | 0.00 | 0.136475E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.327770E+11 | 0.517108E+11 | 0.378551E+11 | 0.655464E+09 | 0.371996E+11 | 0.00 | 0.00 |
Minimum of Months | 80770393.80 | 0.847899E+09 | 0.136475E+10 | 0.00 | 0.136475E+10 | 0.00 | 0.00 |
Maximum of Months | 0.682388E+10 | 0.850709E+10 | 0.485576E+10 | 0.260920E+09 | 0.467369E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.133474E+10 | 0.527964E+10 | 0.217884E+10 | 0.873541E+09 | 0.130530E+10 | 0.00 | 0.00 |
February | 0.212836E+10 | 0.479760E+10 | 0.305193E+10 | 0.142373E+10 | 0.162820E+10 | 0.00 | 0.00 |
March | 0.371665E+10 | 0.379715E+10 | 0.431045E+10 | 0.183326E+10 | 0.247718E+10 | 0.00 | 0.00 |
April | 0.502238E+10 | 0.263241E+10 | 0.500597E+10 | 0.219277E+10 | 0.281320E+10 | 0.00 | 0.00 |
May | 0.717588E+10 | 0.178820E+10 | 0.627356E+10 | 0.250729E+10 | 0.376627E+10 | 0.00 | 0.00 |
June | 0.726344E+10 | 0.973290E+09 | 0.562671E+10 | 0.203683E+10 | 0.358988E+10 | 0.00 | 0.00 |
July | 0.819198E+10 | 0.570710E+09 | 0.583972E+10 | 0.210741E+10 | 0.373231E+10 | 0.00 | 0.00 |
August | 0.918165E+10 | 0.758973E+09 | 0.657567E+10 | 0.296497E+10 | 0.361070E+10 | 0.00 | 0.00 |
September | 0.586765E+10 | 0.136179E+10 | 0.474597E+10 | 0.212933E+10 | 0.261664E+10 | 0.00 | 0.00 |
October | 0.491908E+10 | 0.250708E+10 | 0.444599E+10 | 0.201507E+10 | 0.243092E+10 | 0.00 | 0.00 |
November | 0.215164E+10 | 0.357802E+10 | 0.266081E+10 | 0.102178E+10 | 0.163903E+10 | 0.00 | 0.00 |
December | 0.145810E+10 | 0.479237E+10 | 0.214202E+10 | 0.100576E+10 | 0.113626E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.584116E+11 | 0.328372E+11 | 0.528576E+11 | 0.221117E+11 | 0.307459E+11 | 0.00 | 0.00 |
Minimum of Months | 0.133474E+10 | 0.570710E+09 | 0.214202E+10 | 0.873541E+09 | 0.113626E+10 | 0.00 | 0.00 |
Maximum of Months | 0.918165E+10 | 0.527964E+10 | 0.657567E+10 | 0.296497E+10 | 0.376627E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.785142E+10 | 0.769867E+10 | 0.809403E+10 | 0.530002E+10 | 0.279400E+10 | 0.00 | 0.00 |
February | 0.950184E+10 | 0.709842E+10 | 0.964261E+10 | 0.638262E+10 | 0.325999E+10 | 0.00 | 0.00 |
March | 0.100634E+11 | 0.585238E+10 | 0.963154E+10 | 0.534567E+10 | 0.428587E+10 | 0.00 | 0.00 |
April | 0.783079E+10 | 0.424109E+10 | 0.723264E+10 | 0.286000E+10 | 0.437264E+10 | 0.00 | 0.00 |
May | 0.751466E+10 | 0.284571E+10 | 0.654962E+10 | 0.136615E+10 | 0.518347E+10 | 0.00 | 0.00 |
June | 0.789714E+10 | 0.153865E+10 | 0.594834E+10 | 0.909266E+09 | 0.503908E+10 | 0.00 | 0.00 |
July | 0.951856E+10 | 0.879526E+09 | 0.644289E+10 | 0.111913E+10 | 0.532376E+10 | 0.00 | 0.00 |
August | 0.128344E+11 | 0.122544E+10 | 0.860377E+10 | 0.319128E+10 | 0.541249E+10 | 0.00 | 0.00 |
September | 0.119334E+11 | 0.223187E+10 | 0.903413E+10 | 0.467282E+10 | 0.436131E+10 | 0.00 | 0.00 |
October | 0.157362E+11 | 0.407212E+10 | 0.127885E+11 | 0.801932E+10 | 0.476920E+10 | 0.00 | 0.00 |
November | 0.905667E+10 | 0.550241E+10 | 0.858169E+10 | 0.515371E+10 | 0.342797E+10 | 0.00 | 0.00 |
December | 0.890821E+10 | 0.704851E+10 | 0.877271E+10 | 0.622804E+10 | 0.254467E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.118647E+12 | 0.502348E+11 | 0.101322E+12 | 0.505480E+11 | 0.507745E+11 | 0.00 | 0.00 |
Minimum of Months | 0.751466E+10 | 0.879526E+09 | 0.594834E+10 | 0.909266E+09 | 0.254467E+10 | 0.00 | 0.00 |
Maximum of Months | 0.157362E+11 | 0.769867E+10 | 0.127885E+11 | 0.801932E+10 | 0.541249E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.130043E+10 | 0.553984E+10 | 0.215100E+10 | 0.881058E+09 | 0.126995E+10 | 0.00 | 0.00 |
February | 0.192188E+10 | 0.516875E+10 | 0.286500E+10 | 0.125832E+10 | 0.160668E+10 | 0.00 | 0.00 |
March | 0.413966E+10 | 0.394969E+10 | 0.468379E+10 | 0.216238E+10 | 0.252141E+10 | 0.00 | 0.00 |
April | 0.499265E+10 | 0.284908E+10 | 0.495403E+10 | 0.211970E+10 | 0.283433E+10 | 0.00 | 0.00 |
May | 0.683637E+10 | 0.193523E+10 | 0.596331E+10 | 0.226463E+10 | 0.369868E+10 | 0.00 | 0.00 |
June | 0.818427E+10 | 0.110320E+10 | 0.631613E+10 | 0.254748E+10 | 0.376865E+10 | 0.00 | 0.00 |
July | 0.852571E+10 | 0.673198E+09 | 0.611257E+10 | 0.230181E+10 | 0.381077E+10 | 0.00 | 0.00 |
August | 0.946363E+10 | 0.893542E+09 | 0.676217E+10 | 0.313044E+10 | 0.363173E+10 | 0.00 | 0.00 |
September | 0.580855E+10 | 0.149588E+10 | 0.464574E+10 | 0.203018E+10 | 0.261556E+10 | 0.00 | 0.00 |
October | 0.534688E+10 | 0.271607E+10 | 0.475944E+10 | 0.231440E+10 | 0.244504E+10 | 0.00 | 0.00 |
November | 0.145595E+10 | 0.382427E+10 | 0.216292E+10 | 0.625098E+09 | 0.153782E+10 | 0.00 | 0.00 |
December | 0.123875E+10 | 0.513973E+10 | 0.198800E+10 | 0.860214E+09 | 0.112779E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.592147E+11 | 0.352885E+11 | 0.533641E+11 | 0.224957E+11 | 0.308684E+11 | 0.00 | 0.00 |
Minimum of Months | 0.123875E+10 | 0.673198E+09 | 0.198800E+10 | 0.625098E+09 | 0.112779E+10 | 0.00 | 0.00 |
Maximum of Months | 0.946363E+10 | 0.553984E+10 | 0.676217E+10 | 0.313044E+10 | 0.381077E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 1.17 | -0.7 | -4.4 | 5.65 | -10.4 | 36.91 | 88.07 | 0.05 |
February | -0.2 | -2.6 | -7.5 | 5.07 | -13.4 | 46.98 | 136.68 | 0.04 |
March | 5.59 | 3.43 | 0.29 | 5.58 | -4.1 | 68.24 | 153.73 | 0.03 |
April | 10.94 | 8.00 | 4.75 | 4.99 | 0.53 | 82.64 | 161.98 | 0.05 |
May | 16.05 | 12.31 | 9.14 | 4.42 | 7.77 | 109.28 | 173.60 | 0.03 |
June | 21.71 | 18.08 | 15.84 | 4.92 | 13.23 | 112.36 | 186.51 | 0.01 |
July | 25.05 | 21.76 | 20.26 | 4.06 | 17.39 | 114.46 | 172.96 | 0.02 |
August | 24.79 | 19.84 | 17.14 | 4.19 | 14.42 | 95.56 | 226.16 | 0.00 |
September | 19.96 | 15.96 | 13.24 | 3.91 | 10.59 | 73.65 | 166.08 | 0.03 |
October | 14.02 | 11.03 | 7.95 | 4.86 | 2.64 | 61.34 | 179.75 | 0.00 |
November | 7.31 | 4.98 | 2.14 | 5.60 | -4.0 | 48.23 | 90.71 | 0.03 |
December | 3.33 | 0.91 | -2.8 | 5.64 | -8.5 | 30.23 | 98.59 | 0.04 |
Annual Sum or Average | 12.55 | 9.49 | 6.43 | 4.91 | 2.28 | 73.48 | 153.05 | 0.03 |
Minimum of Months | -0.2 | -2.6 | -7.5 | 3.91 | -13.4 | 30.23 | 88.07 | 0.00 |
Maximum of Months | 25.05 | 21.76 | 20.26 | 5.65 | 17.39 | 114.46 | 226.16 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.20 | 24-JAN-12:20 | 11.81 | 11.50 | 1.00 | 8.15 | 93.67 | 0.00 |
February | 10.00 | 20-FEB-11:00 | 4.36 | -3.3 | 2.60 | -3.9 | 151.50 | 540.00 |
March | 22.20 | 27-MAR-15:00 | 16.34 | 12.80 | 6.70 | 11.65 | 136.50 | 590.00 |
April | 26.70 | 07-APR-12:00 | 16.40 | 9.40 | 6.20 | 11.65 | 179.00 | 713.50 |
May | 30.00 | 30-MAY-12:00 | 18.00 | 10.60 | 5.20 | 17.39 | 233.50 | 730.00 |
June | 36.70 | 19-JUN-11:00 | 24.28 | 19.40 | 5.20 | 24.83 | 185.00 | 771.50 |
July | 33.90 | 07-JUL-11:00 | 23.31 | 18.90 | 3.60 | 23.82 | 331.00 | 570.00 |
August | 33.90 | 24-AUG-14:00 | 20.23 | 12.80 | 8.80 | 21.61 | 240.00 | 432.00 |
September | 31.10 | 01-SEP-13:00 | 17.34 | 8.30 | 4.60 | 18.46 | 182.00 | 662.00 |
October | 25.00 | 04-OCT-12:00 | 18.54 | 15.00 | 5.20 | 11.27 | 171.50 | 695.00 |
November | 17.80 | 04-NOV-12:20 | 12.57 | 8.50 | 3.60 | 6.15 | 182.50 | 595.67 |
December | 12.20 | 17-DEC-12:20 | 4.65 | -6.1 | 4.27 | -4.7 | 53.17 | 801.67 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 4.36 | -6.1 | 1.00 | -4.7 | 53.17 | 0.00 | |
Maximum of Months | 36.70 | 24.28 | 19.40 | 8.80 | 24.83 | 331.00 | 801.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -12.2 | 02-JAN-04:00 | -13.6 | -19.4 | 2.60 | -30.7 | 0.00 | 0.00 |
February | -13.9 | 06-FEB-02:00 | -15.3 | -22.8 | 7.20 | -34.1 | 0.00 | 0.00 |
March | -5.0 | 23-MAR-03:00 | -7.6 | -14.4 | 1.50 | -23.9 | 0.00 | 0.00 |
April | 2.20 | 01-APR-03:00 | 0.57 | -1.7 | 3.10 | -6.6 | 0.00 | 0.00 |
May | 6.10 | 01-MAY-04:00 | 4.33 | 2.20 | 3.60 | -9.7 | 25.50 | 0.00 |
June | 13.30 | 03-JUN-02:00 | 9.35 | 5.60 | 4.60 | -2.1 | 0.00 | 0.00 |
July | 18.30 | 02-JUL-02:00 | 17.54 | 17.20 | 0.00 | 5.33 | 0.00 | 0.00 |
August | 15.00 | 08-AUG-04:00 | 12.47 | 10.60 | 3.10 | 3.06 | 0.00 | 0.00 |
September | 10.00 | 24-SEP-05:00 | 8.56 | 7.20 | 2.60 | -3.4 | 18.50 | 158.50 |
October | 2.20 | 09-OCT-03:00 | 1.71 | 1.10 | 0.00 | -13.7 | 0.00 | 0.00 |
November | -4.4 | 24-NOV-05:00 | -6.2 | -10.0 | 1.50 | -19.7 | 0.00 | 0.00 |
December | -8.3 | 31-DEC-23:00 | -10.6 | -18.9 | 9.30 | -26.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -13.9 | -15.3 | -22.8 | 0.00 | -34.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.54 | 17.20 | 9.30 | 5.33 | 25.50 | 158.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.93 | 24-JAN-11:00 | 12.20 | 11.70 | 1.50 | 8.15 | 103.00 | 0.00 |
February | 6.67 | 28-FEB-09:00 | 7.20 | 6.10 | 4.10 | 2.01 | 101.50 | 0.00 |
March | 16.99 | 27-MAR-12:00 | 20.60 | 15.00 | 3.60 | 10.50 | 295.50 | 565.50 |
April | 17.70 | 09-APR-10:00 | 21.70 | 15.60 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 20.43 | 31-MAY-12:00 | 26.10 | 17.80 | 4.10 | 17.03 | 214.00 | 772.00 |
June | 24.96 | 15-JUN-11:00 | 31.10 | 22.80 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 26.10 | 08-JUL-11:00 | 32.20 | 23.90 | 5.20 | 22.47 | 354.00 | 501.50 |
August | 25.84 | 03-AUG-13:00 | 30.00 | 24.40 | 6.20 | 20.57 | 298.00 | 500.00 |
September | 23.57 | 07-SEP-13:00 | 27.20 | 22.20 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 19.76 | 25-OCT-10:00 | 25.00 | 17.20 | 7.70 | 14.84 | 189.00 | 308.50 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.26 | 25-DEC-08:00 | 10.60 | 10.00 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.67 | 7.20 | 6.10 | 1.50 | 2.01 | 43.00 | 0.00 | |
Maximum of Months | 26.10 | 32.20 | 24.40 | 8.20 | 22.47 | 380.00 | 772.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 18-JAN-15:00 | 12.20 | 11.93 | 14.90 | 8.15 | 22.00 | 2.00 |
February | 6.10 | 28-FEB-10:20 | 7.03 | 6.58 | 3.43 | 1.87 | 109.83 | 0.00 |
March | 15.00 | 27-MAR-12:20 | 18.00 | 16.18 | 3.93 | 10.11 | 271.83 | 611.17 |
April | 15.60 | 09-APR-10:00 | 21.70 | 17.70 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 18.00 | 18-MAY-09:00 | 18.00 | 18.00 | 4.60 | 15.39 | 265.50 | 12.00 |
June | 22.80 | 15-JUN-11:00 | 31.10 | 24.96 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 24.40 | 09-JUL-07:00 | 27.20 | 25.17 | 2.10 | 15.39 | 195.00 | 504.00 |
August | 25.00 | 03-AUG-19:00 | 26.10 | 25.32 | 5.70 | 19.35 | 0.00 | 0.00 |
September | 22.20 | 07-SEP-13:00 | 27.20 | 23.57 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 18.30 | 05-OCT-18:00 | 19.40 | 18.62 | 7.70 | 6.55 | 0.00 | 0.00 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.00 | 25-DEC-08:00 | 10.60 | 10.26 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 7.03 | 6.58 | 2.10 | 1.87 | 0.00 | 0.00 | |
Maximum of Months | 25.00 | 31.10 | 25.32 | 14.90 | 22.47 | 380.00 | 730.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.03 | 13.58 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 9.54 | 21.42 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.65 | 30.29 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 13.15 | 37.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 16.36 | 45.86 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 19.42 | 49.74 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.50 | 48.12 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 22.05 | 49.54 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.89 | 34.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 18.36 | 29.93 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 15.14 | 17.00 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.10 | 12.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 15.80 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 9.54 | 12.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 22.05 | 49.74 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.402106E+11 | -0.397645E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -446107104.3 | 60.05 | 0.00 | 0.00 |
February | 0.368915E+11 | -0.364896E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -401920206.5 | 60.05 | 0.00 | 0.00 |
March | 0.424153E+11 | -0.419703E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -444977059.1 | 60.05 | 0.00 | 0.00 |
April | 0.365700E+11 | -0.361413E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -428739183.1 | 60.05 | 0.00 | 0.00 |
May | 0.364269E+11 | -0.359852E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -441668879.2 | 60.05 | 0.00 | 0.00 |
June | 0.335505E+11 | -0.331414E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -409078035.0 | 60.05 | 0.00 | 0.00 |
July | 0.302835E+11 | -0.298871E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -396460417.1 | 60.05 | 0.00 | 0.00 |
August | 0.326808E+11 | -0.322827E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -398050007.4 | 60.05 | 0.00 | 0.00 |
September | 0.305966E+11 | -0.301854E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -411268773.3 | 60.05 | 0.00 | 0.00 |
October | 0.335900E+11 | -0.331507E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -439254423.2 | 60.05 | 0.00 | 0.00 |
November | 0.354440E+11 | -0.350175E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -426529875.9 | 60.05 | 0.00 | 0.00 |
December | 0.376361E+11 | -0.371940E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -442150100.1 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.426296E+12 | -0.421210E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.508620E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.302835E+11 | -0.419703E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -446107104.3 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.424153E+11 | -0.298871E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -396460417.1 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.51 | 0.48 | 01-JAN-07:49 | 6534.60 | 36.95 | 196.67 | 243.50 | 3360.95 | 33.74 | 200.33 | 197.17 |
February | 216.00 | 0.50 | 0.48 | 01-FEB-07:49 | 9293.45 | 37.82 | 211.33 | 259.67 | 2112.56 | 28.01 | 210.00 | 235.50 |
March | 275.00 | 0.52 | 0.48 | 01-MAR-07:10 | 3559.96 | 24.99 | 164.67 | 318.17 | 1577.34 | 22.62 | 217.83 | 286.33 |
April | 261.17 | 0.51 | 0.48 | 01-APR-14:39 | 2120.62 | 20.63 | 98.17 | 341.17 | 1232.95 | 22.02 | 227.33 | 299.67 |
May | 372.00 | 0.51 | 0.48 | 01-MAY-06:10 | 1859.72 | 20.47 | 145.67 | 391.50 | 1031.60 | 21.85 | 278.67 | 348.50 |
June | 351.83 | 0.51 | 0.48 | 01-JUN-05:00 | 1778.63 | 20.46 | 130.33 | 384.33 | 1001.42 | 21.88 | 268.67 | 341.67 |
July | 365.17 | 0.51 | 0.48 | 01-JUL-05:00 | 1957.40 | 20.73 | 164.33 | 391.67 | 1077.69 | 22.15 | 288.33 | 346.33 |
August | 389.17 | 0.52 | 0.48 | 01-AUG-06:10 | 2162.41 | 20.70 | 181.17 | 371.67 | 1234.33 | 22.10 | 298.17 | 341.00 |
September | 285.33 | 0.51 | 0.48 | 01-SEP-06:30 | 3843.61 | 22.86 | 156.83 | 325.17 | 1458.35 | 22.37 | 230.33 | 290.00 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 10172.40 | 36.47 | 284.33 | 306.67 | 2019.89 | 24.31 | 271.67 | 288.67 |
November | 240.83 | 0.50 | 0.48 | 01-NOV-06:00 | 6485.15 | 36.73 | 236.67 | 258.17 | 2238.43 | 29.50 | 233.33 | 235.00 |
December | 211.17 | 0.51 | 0.48 | 01-DEC-07:40 | 6111.49 | 37.97 | 207.83 | 245.33 | 5383.17 | 39.15 | 213.00 | 214.67 |
Annual Sum or Average | 3472.67 | 0.51 | 4254.52 | 26.71 | 2178.00 | 3837.00 | 1785.84 | 24.89 | 2937.67 | 3424.50 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1778.63 | 20.46 | 98.17 | 243.50 | 1001.42 | 21.85 | 200.33 | 197.17 | |
Maximum of Months | 389.17 | 0.52 | 0.48 | 10172.40 | 37.97 | 284.33 | 391.67 | 5383.17 | 39.15 | 298.17 | 348.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.53 | 0.48 | 01-JAN-07:49 | 2077.39 | 24.91 | 90.83 | 224.83 | 1133.81 | 24.89 | 121.33 | 160.83 |
February | 216.00 | 0.51 | 0.48 | 01-FEB-07:40 | 2863.61 | 25.88 | 96.00 | 247.50 | 1637.74 | 25.87 | 138.33 | 209.50 |
March | 275.00 | 0.52 | 0.48 | 01-MAR-06:00 | 2977.94 | 23.65 | 94.17 | 314.67 | 1650.41 | 24.10 | 160.83 | 263.50 |
April | 261.17 | 0.51 | 0.48 | 01-APR-06:19 | 3933.28 | 25.78 | 97.17 | 343.50 | 1571.88 | 24.61 | 172.00 | 306.00 |
May | 372.00 | 0.51 | 0.48 | 01-MAY-05:40 | 3241.21 | 23.58 | 103.33 | 397.83 | 1743.59 | 24.15 | 225.83 | 357.67 |
June | 351.83 | 0.51 | 0.48 | 01-JUN-04:00 | 2913.69 | 23.60 | 95.00 | 389.50 | 1611.55 | 24.40 | 221.17 | 355.50 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-04:00 | 3002.09 | 23.99 | 116.67 | 397.83 | 1616.51 | 24.63 | 259.00 | 360.33 |
August | 389.17 | 0.51 | 0.48 | 01-AUG-05:40 | 3985.10 | 25.42 | 143.17 | 375.00 | 1652.17 | 24.55 | 242.00 | 348.67 |
September | 285.33 | 0.51 | 0.48 | 01-SEP-05:49 | 3479.29 | 25.27 | 105.67 | 323.67 | 1506.37 | 24.41 | 180.00 | 288.00 |
October | 305.50 | 0.51 | 0.48 | 01-OCT-14:39 | 3083.32 | 25.38 | 142.67 | 295.67 | 1618.56 | 25.50 | 208.67 | 268.00 |
November | 240.83 | 0.52 | 0.48 | 01-NOV-06:49 | 2103.22 | 24.98 | 117.50 | 246.67 | 1076.17 | 24.75 | 153.00 | 203.33 |
December | 211.17 | 0.54 | 0.48 | 01-DEC-07:40 | 1934.83 | 25.25 | 94.33 | 225.33 | 1109.71 | 25.19 | 113.17 | 161.17 |
Annual Sum or Average | 3472.67 | 0.51 | 3054.41 | 24.72 | 1296.50 | 3782.00 | 1529.37 | 24.70 | 2195.33 | 3282.50 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1934.83 | 23.58 | 90.83 | 224.83 | 1076.17 | 24.10 | 113.17 | 160.83 | |
Maximum of Months | 389.17 | 0.54 | 0.48 | 3985.10 | 25.88 | 143.17 | 397.83 | 1743.59 | 25.87 | 259.00 | 360.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.56 | 0.48 | 01-JAN-09:09 | 665.34 | 17.28 | 0.00 | 209.83 | 399.84 | 18.89 | 3.33 | 122.17 |
February | 216.00 | 0.54 | 0.48 | 01-FEB-08:00 | 727.16 | 18.21 | 0.00 | 232.83 | 462.77 | 19.90 | 7.33 | 167.67 |
March | 275.00 | 0.53 | 0.48 | 01-MAR-07:40 | 958.44 | 18.95 | 0.33 | 308.83 | 588.97 | 20.40 | 91.67 | 241.00 |
April | 261.17 | 0.51 | 0.48 | 01-APR-14:39 | 1079.63 | 19.88 | 10.33 | 344.83 | 666.28 | 21.29 | 127.50 | 296.67 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:49 | 1378.67 | 20.68 | 101.83 | 404.50 | 784.60 | 21.94 | 267.33 | 363.50 |
June | 351.83 | 0.49 | 0.48 | 01-JUN-05:19 | 1552.71 | 23.70 | 167.00 | 402.67 | 856.29 | 23.42 | 295.33 | 370.67 |
July | 365.17 | 0.49 | 0.48 | 01-JUL-05:10 | 1532.55 | 22.47 | 155.17 | 408.67 | 847.93 | 22.28 | 290.33 | 368.33 |
August | 389.17 | 0.51 | 0.48 | 01-AUG-05:00 | 1267.68 | 20.27 | 67.17 | 378.50 | 755.86 | 21.66 | 272.33 | 350.83 |
September | 285.33 | 0.51 | 0.48 | 01-SEP-06:30 | 990.75 | 19.49 | 0.83 | 321.50 | 616.71 | 20.96 | 118.33 | 271.83 |
October | 305.50 | 0.52 | 0.48 | 01-OCT-14:39 | 901.59 | 19.18 | 0.00 | 290.83 | 571.09 | 20.80 | 137.67 | 247.00 |
November | 240.83 | 0.54 | 0.48 | 01-NOV-07:40 | 740.18 | 17.97 | 0.00 | 235.33 | 436.38 | 19.48 | 15.67 | 158.50 |
December | 211.17 | 0.59 | 0.48 | 01-DEC-09:09 | 538.99 | 16.37 | 0.00 | 201.17 | 333.22 | 18.11 | 0.17 | 94.83 |
Annual Sum or Average | 3472.67 | 0.52 | 1093.59 | 19.90 | 502.67 | 3739.50 | 644.62 | 21.04 | 1627.00 | 3053.00 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 538.99 | 16.37 | 0.00 | 201.17 | 333.22 | 18.11 | 0.17 | 94.83 | |
Maximum of Months | 389.17 | 0.59 | 0.48 | 1552.71 | 23.70 | 167.00 | 408.67 | 856.29 | 23.42 | 295.33 | 370.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.53 | 0.48 | 01-JAN-09:09 | 2011.88 | 25.14 | 90.17 | 231.50 | 1122.39 | 25.11 | 119.50 | 165.17 |
February | 216.00 | 0.52 | 0.48 | 01-FEB-08:00 | 2274.75 | 24.82 | 93.17 | 247.33 | 1196.34 | 24.84 | 130.83 | 208.17 |
March | 275.00 | 0.51 | 0.48 | 01-MAR-07:40 | 3237.47 | 25.78 | 117.17 | 319.50 | 1810.65 | 26.00 | 183.17 | 275.67 |
April | 261.17 | 0.51 | 0.48 | 01-APR-14:39 | 3708.62 | 24.32 | 83.00 | 342.33 | 1519.21 | 23.41 | 164.50 | 302.33 |
May | 372.00 | 0.51 | 0.48 | 01-MAY-06:30 | 3479.99 | 22.00 | 75.00 | 396.67 | 1536.12 | 21.32 | 210.17 | 360.33 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-06:10 | 3375.03 | 19.40 | 20.00 | 393.67 | 1814.66 | 21.53 | 210.00 | 355.17 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-06:10 | 3180.94 | 21.52 | 64.17 | 399.33 | 1692.13 | 21.61 | 236.83 | 359.50 |
August | 389.17 | 0.51 | 0.48 | 01-AUG-06:30 | 4058.81 | 22.92 | 106.33 | 374.33 | 1758.59 | 21.69 | 221.17 | 347.83 |
September | 285.33 | 0.51 | 0.48 | 01-SEP-06:00 | 3294.56 | 24.89 | 107.33 | 324.33 | 1711.70 | 24.97 | 179.50 | 287.00 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 3546.82 | 27.19 | 160.50 | 305.17 | 1500.67 | 25.81 | 224.67 | 278.50 |
November | 240.83 | 0.52 | 0.48 | 01-NOV-07:49 | 1742.97 | 24.70 | 110.83 | 247.50 | 925.61 | 24.78 | 156.83 | 206.17 |
December | 211.17 | 0.54 | 0.48 | 01-DEC-09:09 | 1633.20 | 24.75 | 90.83 | 224.17 | 897.04 | 24.53 | 117.00 | 165.83 |
Annual Sum or Average | 3472.67 | 0.51 | 3099.34 | 23.67 | 1118.50 | 3805.83 | 1511.35 | 23.51 | 2154.17 | 3311.67 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1633.20 | 19.40 | 20.00 | 224.17 | 897.04 | 21.32 | 117.00 | 165.17 | |
Maximum of Months | 389.17 | 0.54 | 0.48 | 4058.81 | 27.19 | 160.50 | 399.33 | 1814.66 | 26.00 | 236.83 | 360.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.51 | 0.48 | 01-JAN-07:49 | 6583.38 | 36.53 | 196.17 | 243.50 | 3479.79 | 31.83 | 144.00 | 199.67 |
February | 216.00 | 0.50 | 0.48 | 01-FEB-07:49 | 9357.98 | 37.33 | 210.00 | 260.00 | 2245.71 | 24.10 | 80.00 | 238.00 |
March | 275.00 | 0.51 | 0.48 | 01-MAR-07:10 | 3663.97 | 20.20 | 90.67 | 320.50 | 1692.81 | 18.23 | 22.83 | 289.33 |
April | 261.17 | 0.51 | 0.48 | 01-APR-14:39 | 2167.67 | 14.44 | 0.00 | 341.17 | 1322.04 | 17.97 | 1.17 | 304.17 |
May | 372.00 | 0.51 | 0.48 | 01-MAY-06:10 | 1888.34 | 14.51 | 0.00 | 391.67 | 1100.10 | 17.90 | 0.00 | 354.33 |
June | 351.83 | 0.51 | 0.48 | 01-JUN-05:49 | 1806.20 | 14.50 | 0.00 | 384.67 | 1067.57 | 17.96 | 0.00 | 345.00 |
July | 365.17 | 0.51 | 0.48 | 01-JUL-05:00 | 1984.44 | 14.67 | 0.00 | 391.83 | 1148.01 | 18.12 | 0.00 | 351.00 |
August | 389.17 | 0.51 | 0.48 | 01-AUG-06:10 | 2204.01 | 14.75 | 0.00 | 372.00 | 1320.49 | 18.20 | 4.00 | 343.67 |
September | 285.33 | 0.51 | 0.48 | 01-SEP-06:19 | 3904.05 | 17.11 | 29.50 | 326.00 | 1565.80 | 18.05 | 4.83 | 293.50 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 10248.41 | 35.69 | 283.50 | 307.67 | 2245.48 | 20.16 | 27.17 | 291.83 |
November | 240.83 | 0.50 | 0.48 | 01-NOV-06:00 | 6519.46 | 36.31 | 236.33 | 258.33 | 2786.39 | 29.03 | 144.17 | 238.67 |
December | 211.17 | 0.51 | 0.48 | 01-DEC-07:40 | 6170.61 | 37.57 | 207.67 | 245.83 | 5500.53 | 38.84 | 207.83 | 218.33 |
Annual Sum or Average | 3472.67 | 0.51 | 4304.10 | 22.67 | 1253.83 | 3843.17 | 1921.69 | 21.44 | 636.00 | 3467.50 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1806.20 | 14.44 | 0.00 | 243.50 | 1067.57 | 17.90 | 0.00 | 199.67 | |
Maximum of Months | 389.17 | 0.51 | 0.48 | 10248.41 | 37.57 | 283.50 | 391.83 | 5500.53 | 38.84 | 207.83 | 354.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.53 | 0.48 | 01-JAN-07:49 | 2109.46 | 22.62 | 72.83 | 226.33 | 1179.15 | 23.16 | 68.50 | 165.33 |
February | 216.00 | 0.51 | 0.48 | 01-FEB-07:40 | 2906.23 | 23.52 | 80.67 | 249.17 | 1695.43 | 24.08 | 60.33 | 213.67 |
March | 275.00 | 0.52 | 0.48 | 01-MAR-06:00 | 3039.73 | 20.76 | 71.50 | 315.17 | 1720.88 | 21.87 | 51.67 | 271.83 |
April | 261.17 | 0.50 | 0.48 | 01-APR-06:19 | 3993.65 | 23.08 | 92.67 | 344.83 | 1651.28 | 22.13 | 50.17 | 309.00 |
May | 372.00 | 0.51 | 0.48 | 01-MAY-05:40 | 3281.86 | 20.47 | 99.50 | 398.17 | 1820.60 | 21.70 | 72.83 | 361.17 |
June | 351.83 | 0.51 | 0.48 | 01-JUN-04:00 | 2958.03 | 20.41 | 88.50 | 390.50 | 1685.92 | 21.98 | 68.83 | 358.33 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-04:00 | 3039.25 | 20.34 | 89.67 | 399.17 | 1693.23 | 22.18 | 70.00 | 364.00 |
August | 389.17 | 0.51 | 0.48 | 01-AUG-05:40 | 4033.84 | 22.55 | 128.17 | 375.17 | 1732.41 | 22.09 | 70.50 | 351.50 |
September | 285.33 | 0.51 | 0.48 | 01-SEP-05:49 | 3519.25 | 21.51 | 82.67 | 324.17 | 1581.64 | 21.99 | 48.50 | 292.33 |
October | 305.50 | 0.51 | 0.48 | 01-OCT-14:39 | 3129.57 | 22.49 | 91.17 | 296.50 | 1688.35 | 23.51 | 74.33 | 272.83 |
November | 240.83 | 0.52 | 0.48 | 01-NOV-06:49 | 2122.20 | 21.46 | 73.33 | 247.33 | 1126.31 | 22.82 | 75.17 | 206.50 |
December | 211.17 | 0.54 | 0.48 | 01-DEC-07:30 | 1964.18 | 23.03 | 83.00 | 226.00 | 1150.00 | 23.60 | 79.17 | 166.83 |
Annual Sum or Average | 3472.67 | 0.51 | 3097.01 | 21.70 | 1053.67 | 3792.50 | 1598.22 | 22.48 | 790.00 | 3333.33 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1964.18 | 20.34 | 71.50 | 226.00 | 1126.31 | 21.70 | 48.50 | 165.33 | |
Maximum of Months | 389.17 | 0.54 | 0.48 | 4033.84 | 23.52 | 128.17 | 399.17 | 1820.60 | 24.08 | 79.17 | 364.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.55 | 0.48 | 01-JAN-08:00 | 673.51 | 11.61 | 0.00 | 210.33 | 424.89 | 15.14 | 0.00 | 132.33 |
February | 216.00 | 0.54 | 0.48 | 01-FEB-08:50 | 738.61 | 12.69 | 0.00 | 234.00 | 492.69 | 16.38 | 0.00 | 177.50 |
March | 275.00 | 0.53 | 0.48 | 01-MAR-07:30 | 974.99 | 13.64 | 0.00 | 309.00 | 627.39 | 17.08 | 0.00 | 251.17 |
April | 261.17 | 0.51 | 0.48 | 01-APR-14:39 | 1101.13 | 14.58 | 0.00 | 345.33 | 710.60 | 18.09 | 0.00 | 303.50 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:49 | 1402.28 | 15.05 | 3.17 | 404.50 | 836.28 | 18.47 | 11.33 | 369.33 |
June | 351.83 | 0.49 | 0.48 | 01-JUN-05:10 | 1580.28 | 19.18 | 73.00 | 403.00 | 920.96 | 21.17 | 52.00 | 376.00 |
July | 365.17 | 0.49 | 0.48 | 01-JUL-04:00 | 1558.61 | 17.45 | 41.50 | 409.17 | 911.29 | 20.66 | 46.50 | 376.50 |
August | 389.17 | 0.51 | 0.48 | 01-AUG-05:00 | 1291.57 | 14.99 | 0.00 | 378.67 | 805.79 | 18.45 | 3.67 | 354.33 |
September | 285.33 | 0.51 | 0.48 | 01-SEP-06:30 | 1009.38 | 14.23 | 0.00 | 321.83 | 657.36 | 17.74 | 0.00 | 277.17 |
October | 305.50 | 0.52 | 0.48 | 01-OCT-14:39 | 915.61 | 13.94 | 0.00 | 291.50 | 608.00 | 17.50 | 0.00 | 252.17 |
November | 240.83 | 0.54 | 0.48 | 01-NOV-07:30 | 749.66 | 12.17 | 0.00 | 235.83 | 463.67 | 15.69 | 0.00 | 166.83 |
December | 211.17 | 0.58 | 0.48 | 01-DEC-08:00 | 545.46 | 10.50 | 0.00 | 201.67 | 354.13 | 14.20 | 0.00 | 103.67 |
Annual Sum or Average | 3472.67 | 0.52 | 1112.26 | 14.58 | 117.67 | 3744.83 | 688.39 | 17.91 | 113.50 | 3140.50 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 545.46 | 10.50 | 0.00 | 201.67 | 354.13 | 14.20 | 0.00 | 103.67 | |
Maximum of Months | 389.17 | 0.58 | 0.48 | 1580.28 | 19.18 | 73.00 | 409.17 | 920.96 | 21.17 | 52.00 | 376.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.52 | 0.48 | 01-JAN-08:00 | 2042.79 | 22.88 | 73.33 | 232.50 | 1166.21 | 23.44 | 65.83 | 170.33 |
February | 216.00 | 0.52 | 0.48 | 01-FEB-08:00 | 2285.39 | 20.91 | 57.00 | 247.83 | 1253.74 | 22.85 | 45.50 | 213.17 |
March | 275.00 | 0.51 | 0.48 | 01-MAR-07:40 | 3301.46 | 23.15 | 95.83 | 320.83 | 1883.96 | 24.01 | 75.00 | 283.83 |
April | 261.17 | 0.51 | 0.48 | 01-APR-14:39 | 3767.41 | 21.32 | 76.83 | 343.33 | 1597.99 | 20.74 | 37.00 | 306.83 |
May | 372.00 | 0.51 | 0.48 | 01-MAY-06:19 | 3520.58 | 18.44 | 69.17 | 397.50 | 1610.75 | 18.04 | 0.00 | 364.33 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-05:00 | 3411.97 | 14.81 | 1.83 | 394.17 | 1898.77 | 18.19 | 0.00 | 360.00 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-06:10 | 3218.57 | 17.67 | 49.00 | 400.17 | 1771.78 | 18.34 | 0.00 | 362.83 |
August | 389.17 | 0.51 | 0.48 | 01-AUG-06:19 | 4113.72 | 19.59 | 86.33 | 374.50 | 1840.59 | 18.52 | 8.50 | 352.00 |
September | 285.33 | 0.51 | 0.48 | 01-SEP-06:49 | 3342.82 | 21.80 | 85.33 | 325.00 | 1785.61 | 22.71 | 61.67 | 291.33 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 3584.61 | 23.94 | 111.83 | 305.33 | 1572.98 | 23.76 | 70.67 | 282.00 |
November | 240.83 | 0.52 | 0.48 | 01-NOV-07:40 | 1769.58 | 22.05 | 79.67 | 248.50 | 967.98 | 22.96 | 70.83 | 212.50 |
December | 211.17 | 0.54 | 0.48 | 01-DEC-08:00 | 1627.41 | 20.95 | 68.50 | 224.50 | 935.93 | 22.89 | 67.00 | 171.50 |
Annual Sum or Average | 3472.67 | 0.51 | 3138.25 | 20.28 | 854.67 | 3814.17 | 1580.99 | 20.95 | 502.00 | 3370.67 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1627.41 | 14.81 | 1.83 | 224.50 | 935.93 | 18.04 | 0.00 | 170.33 | |
Maximum of Months | 389.17 | 0.54 | 0.48 | 4113.72 | 23.94 | 111.83 | 400.17 | 1898.77 | 24.01 | 75.00 | 364.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.51 | 0.48 | 01-JAN-07:49 | 6585.05 | 36.52 | 196.17 | 243.50 | 3482.30 | 31.82 | 144.00 | 199.83 |
February | 216.00 | 0.50 | 0.48 | 01-FEB-07:49 | 9360.01 | 37.32 | 210.00 | 260.17 | 2248.27 | 24.09 | 80.00 | 238.00 |
March | 275.00 | 0.51 | 0.48 | 01-MAR-07:10 | 3667.25 | 20.17 | 90.67 | 320.67 | 1695.18 | 18.22 | 22.17 | 289.67 |
April | 261.17 | 0.51 | 0.48 | 01-APR-14:39 | 2170.51 | 14.41 | 0.00 | 341.17 | 1323.85 | 17.96 | 1.17 | 304.17 |
May | 372.00 | 0.51 | 0.48 | 01-MAY-06:10 | 1891.06 | 14.48 | 0.00 | 391.83 | 1101.78 | 17.89 | 0.00 | 354.50 |
June | 351.83 | 0.51 | 0.48 | 01-JUN-05:49 | 1808.68 | 14.47 | 0.00 | 384.83 | 1069.14 | 17.95 | 0.00 | 345.17 |
July | 365.17 | 0.51 | 0.48 | 01-JUL-05:00 | 1987.33 | 14.64 | 0.00 | 392.00 | 1149.78 | 18.11 | 0.00 | 351.00 |
August | 389.17 | 0.51 | 0.48 | 01-AUG-06:10 | 2206.98 | 14.72 | 0.00 | 372.00 | 1322.38 | 18.18 | 3.83 | 343.67 |
September | 285.33 | 0.51 | 0.48 | 01-SEP-06:19 | 3907.29 | 17.08 | 29.50 | 326.00 | 1567.97 | 18.03 | 4.67 | 293.67 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 10251.51 | 35.68 | 283.50 | 307.67 | 2248.47 | 20.14 | 26.83 | 291.83 |
November | 240.83 | 0.50 | 0.48 | 01-NOV-06:00 | 6521.48 | 36.30 | 236.33 | 258.67 | 2789.17 | 29.02 | 144.17 | 238.67 |
December | 211.17 | 0.51 | 0.48 | 01-DEC-07:40 | 6171.41 | 37.56 | 207.67 | 245.83 | 5502.58 | 38.83 | 207.83 | 218.33 |
Annual Sum or Average | 3472.67 | 0.51 | 4306.71 | 22.65 | 1253.83 | 3844.33 | 1923.81 | 21.42 | 634.67 | 3468.50 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1808.68 | 14.41 | 0.00 | 243.50 | 1069.14 | 17.89 | 0.00 | 199.83 | |
Maximum of Months | 389.17 | 0.51 | 0.48 | 10251.51 | 37.56 | 283.50 | 392.00 | 5502.58 | 38.83 | 207.83 | 354.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.53 | 0.48 | 01-JAN-07:49 | 2110.45 | 22.60 | 72.83 | 226.67 | 1180.28 | 23.14 | 68.17 | 165.67 |
February | 216.00 | 0.51 | 0.48 | 01-FEB-07:40 | 2907.17 | 23.50 | 80.67 | 249.33 | 1696.66 | 24.07 | 60.00 | 213.67 |
March | 275.00 | 0.52 | 0.48 | 01-MAR-06:00 | 3041.09 | 20.73 | 71.50 | 315.17 | 1722.47 | 21.86 | 51.67 | 272.00 |
April | 261.17 | 0.50 | 0.48 | 01-APR-06:19 | 3995.36 | 23.06 | 92.67 | 344.83 | 1652.90 | 22.12 | 50.17 | 309.17 |
May | 372.00 | 0.51 | 0.48 | 01-MAY-05:40 | 3284.15 | 20.44 | 99.50 | 398.33 | 1822.51 | 21.69 | 72.83 | 361.33 |
June | 351.83 | 0.51 | 0.48 | 01-JUN-04:00 | 2960.17 | 20.38 | 88.50 | 390.83 | 1687.67 | 21.97 | 68.83 | 358.50 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-04:00 | 3041.76 | 20.31 | 89.67 | 399.17 | 1695.18 | 22.17 | 70.00 | 364.17 |
August | 389.17 | 0.51 | 0.48 | 01-AUG-05:40 | 4035.95 | 22.52 | 128.17 | 375.17 | 1734.27 | 22.08 | 70.50 | 351.50 |
September | 285.33 | 0.51 | 0.48 | 01-SEP-05:49 | 3520.83 | 21.48 | 82.67 | 324.17 | 1583.21 | 21.98 | 48.50 | 292.50 |
October | 305.50 | 0.51 | 0.48 | 01-OCT-14:39 | 3130.81 | 22.47 | 91.17 | 296.50 | 1689.95 | 23.50 | 74.00 | 272.83 |
November | 240.83 | 0.52 | 0.48 | 01-NOV-06:49 | 2123.49 | 21.43 | 73.33 | 247.33 | 1127.64 | 22.80 | 74.67 | 206.50 |
December | 211.17 | 0.54 | 0.48 | 01-DEC-07:30 | 1964.85 | 23.01 | 82.83 | 226.17 | 1150.88 | 23.59 | 78.83 | 167.17 |
Annual Sum or Average | 3472.67 | 0.51 | 3098.69 | 21.68 | 1053.50 | 3793.67 | 1599.81 | 22.46 | 788.17 | 3335.00 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1964.85 | 20.31 | 71.50 | 226.17 | 1127.64 | 21.69 | 48.50 | 165.67 | |
Maximum of Months | 389.17 | 0.54 | 0.48 | 4035.95 | 23.50 | 128.17 | 399.17 | 1822.51 | 24.07 | 78.83 | 364.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.55 | 0.48 | 01-JAN-08:00 | 674.08 | 11.58 | 0.00 | 210.33 | 425.45 | 15.13 | 0.00 | 132.50 |
February | 216.00 | 0.54 | 0.48 | 01-FEB-08:50 | 739.06 | 12.65 | 0.00 | 234.00 | 493.25 | 16.36 | 0.00 | 177.67 |
March | 275.00 | 0.53 | 0.48 | 01-MAR-07:30 | 975.80 | 13.60 | 0.00 | 309.17 | 628.16 | 17.06 | 0.00 | 251.33 |
April | 261.17 | 0.51 | 0.48 | 01-APR-14:39 | 1102.02 | 14.55 | 0.00 | 345.50 | 711.45 | 18.07 | 0.00 | 304.00 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-05:49 | 1403.78 | 15.02 | 3.17 | 404.50 | 837.45 | 18.45 | 10.50 | 369.33 |
June | 351.83 | 0.49 | 0.48 | 01-JUN-05:10 | 1581.82 | 19.15 | 73.00 | 403.17 | 922.20 | 21.16 | 51.83 | 376.00 |
July | 365.17 | 0.49 | 0.48 | 01-JUL-04:00 | 1560.23 | 17.43 | 41.33 | 409.17 | 912.56 | 20.65 | 46.17 | 376.50 |
August | 389.17 | 0.51 | 0.48 | 01-AUG-05:00 | 1292.67 | 14.96 | 0.00 | 378.67 | 806.80 | 18.43 | 3.50 | 354.33 |
September | 285.33 | 0.51 | 0.48 | 01-SEP-06:30 | 1010.17 | 14.20 | 0.00 | 321.83 | 658.14 | 17.72 | 0.00 | 277.50 |
October | 305.50 | 0.52 | 0.48 | 01-OCT-14:39 | 916.16 | 13.91 | 0.00 | 291.50 | 608.69 | 17.48 | 0.00 | 252.33 |
November | 240.83 | 0.54 | 0.48 | 01-NOV-07:30 | 750.38 | 12.14 | 0.00 | 236.17 | 464.31 | 15.67 | 0.00 | 167.17 |
December | 211.17 | 0.58 | 0.48 | 01-DEC-08:00 | 545.83 | 10.47 | 0.00 | 201.67 | 354.56 | 14.19 | 0.00 | 103.83 |
Annual Sum or Average | 3472.67 | 0.52 | 1113.24 | 14.55 | 117.50 | 3745.67 | 689.27 | 17.90 | 112.00 | 3142.50 | ||
Minimum of Months | 199.50 | 0.49 | 0.48 | 545.83 | 10.47 | 0.00 | 201.67 | 354.56 | 14.19 | 0.00 | 103.83 | |
Maximum of Months | 389.17 | 0.58 | 0.48 | 1581.82 | 19.15 | 73.00 | 409.17 | 922.20 | 21.16 | 51.83 | 376.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.52 | 0.48 | 01-JAN-08:00 | 2043.72 | 22.85 | 73.33 | 232.50 | 1167.29 | 23.43 | 65.67 | 170.33 |
February | 216.00 | 0.52 | 0.48 | 01-FEB-08:00 | 2286.34 | 20.88 | 57.00 | 247.83 | 1254.92 | 22.84 | 45.17 | 213.33 |
March | 275.00 | 0.51 | 0.48 | 01-MAR-07:40 | 3302.88 | 23.12 | 95.83 | 320.83 | 1885.59 | 23.99 | 74.83 | 283.83 |
April | 261.17 | 0.51 | 0.48 | 01-APR-14:39 | 3739.07 | 21.30 | 76.83 | 343.33 | 1599.64 | 20.72 | 37.00 | 306.83 |
May | 372.00 | 0.50 | 0.48 | 01-MAY-06:19 | 3522.87 | 18.41 | 69.17 | 397.67 | 1612.60 | 18.03 | 0.00 | 364.67 |
June | 351.83 | 0.50 | 0.48 | 01-JUN-05:00 | 3414.46 | 14.77 | 1.83 | 394.17 | 1900.82 | 18.17 | 0.00 | 360.33 |
July | 365.17 | 0.50 | 0.48 | 01-JUL-06:10 | 3221.17 | 17.64 | 49.00 | 400.17 | 1773.81 | 18.33 | 0.00 | 362.83 |
August | 389.17 | 0.51 | 0.48 | 01-AUG-06:19 | 4115.85 | 19.56 | 86.33 | 374.50 | 1842.46 | 18.51 | 8.50 | 352.00 |
September | 285.33 | 0.51 | 0.48 | 01-SEP-06:49 | 3344.45 | 21.77 | 85.33 | 325.00 | 1787.23 | 22.70 | 61.50 | 291.50 |
October | 305.50 | 0.50 | 0.48 | 01-OCT-14:39 | 3585.99 | 23.91 | 111.83 | 305.33 | 1574.56 | 23.74 | 70.33 | 282.00 |
November | 240.83 | 0.52 | 0.48 | 01-NOV-07:40 | 1770.85 | 22.03 | 79.67 | 248.50 | 969.19 | 22.95 | 70.33 | 212.50 |
December | 211.17 | 0.54 | 0.48 | 01-DEC-08:00 | 1628.11 | 20.92 | 68.50 | 224.67 | 936.79 | 22.88 | 67.00 | 171.83 |
Annual Sum or Average | 3472.67 | 0.51 | 3137.74 | 20.25 | 854.67 | 3814.50 | 1582.61 | 20.94 | 500.33 | 3372.00 | ||
Minimum of Months | 199.50 | 0.50 | 0.48 | 1628.11 | 14.77 | 1.83 | 224.67 | 936.79 | 18.03 | 0.00 | 170.33 | |
Maximum of Months | 389.17 | 0.54 | 0.48 | 4115.85 | 23.91 | 111.83 | 400.17 | 1900.82 | 23.99 | 74.83 | 364.67 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.134990E+09 | 6276.78 | 31-JAN-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148684E+09 | 12477.23 | 22-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.126791E+09 | 15475.13 | 23-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 32518151.77 | 4614.58 | 07-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1941692.10 | 9700.87 | 30-MAY-13:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 79672312.64 | 14985.25 | 22-JUN-11:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 48729850.54 | 11145.37 | 11-JUL-15:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.197366E+09 | 20687.06 | 24-AUG-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 25645800.79 | 9633.97 | 01-SEP-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1012571.15 | 1355.92 | 28-OCT-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 49473977.45 | 15775.15 | 24-NOV-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160558E+09 | 15953.84 | 22-DEC-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1012571.15 | 1355.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.197366E+09 | 20687.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.586645E+09 | 15074.08 | 31-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.435361E+09 | 15100.13 | 03-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4419442.91 | 901.40 | 23-MAR-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9169403.85 | 1729.43 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4170735.09 | 1596.92 | 15-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.103976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.586645E+09 | 15100.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.642177E+09 | 13310.18 | 30-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.458526E+09 | 13328.81 | 04-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 69110888.79 | 9849.56 | 17-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 773139.53 | 629.70 | 01-APR-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 45124652.80 | 10255.62 | 22-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.189798E+09 | 8949.54 | 07-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.140551E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.642177E+09 | 13328.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.795076E+09 | 19111.63 | 26-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.518751E+09 | 19113.48 | 28-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 69233354.98 | 19129.84 | 17-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 53404813.65 | 19152.34 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156751E+09 | 19138.46 | 07-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159322E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.795076E+09 | 19152.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.264851E+09 | 11317.20 | 02-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 81044595.02 | 11312.70 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.345896E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.264851E+09 | 11317.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.502254E+10 | 242311.23 | 30-JAN-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.417423E+10 | 279813.47 | 06-FEB-19:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.400369E+10 | 164481.54 | 22-MAR-07:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.339744E+09 | 37813.81 | 12-APR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.780604E+09 | 170110.26 | 30-MAY-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152023E+10 | 175029.33 | 22-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.348267E+09 | 128286.07 | 11-JUL-15:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.168620E+10 | 161203.36 | 22-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 13435462.21 | 22307.62 | 14-SEP-19:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14654776.60 | 9805.29 | 31-OCT-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.231896E+10 | 147041.61 | 22-NOV-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.382612E+10 | 143139.33 | 21-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.240487E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 13435462.21 | 9805.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.502254E+10 | 279813.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.171018E+11 | 526833.71 | 17-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144268E+10 | 526142.22 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.171018E+11 | 526833.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.519123E+11 | 141864.62 | 04-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.406799E+11 | 141685.93 | 28-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.113506E+11 | 153669.90 | 30-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.229828E+10 | 140424.89 | 04-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.371739E+09 | 76224.42 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.117666E+11 | 141694.84 | 27-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.282856E+11 | 141688.09 | 30-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146665E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.519123E+11 | 153669.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.365634E+11 | 176694.98 | 23-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.250314E+11 | 176665.29 | 13-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.868047E+10 | 176332.79 | 11-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.285386E+10 | 176362.10 | 22-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6609658.36 | 5113.40 | 01-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.391940E+09 | 43211.92 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.911619E+10 | 176378.05 | 30-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.219421E+11 | 176659.28 | 26-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.104586E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.365634E+11 | 176694.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.311749E+11 | 210945.19 | 04-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.195003E+11 | 209777.19 | 28-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.618578E+10 | 208628.43 | 01-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.195737E+10 | 208641.73 | 22-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 23001617.40 | 6772.47 | 28-OCT-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.545151E+10 | 209502.37 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159269E+11 | 208838.83 | 07-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.802198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.311749E+11 | 210945.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.322360E+11 | 176318.11 | 04-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.236161E+11 | 176503.45 | 13-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.623349E+10 | 176002.60 | 17-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.162279E+10 | 128876.96 | 22-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.234565E+09 | 19836.37 | 28-OCT-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.839393E+10 | 176199.53 | 24-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.184909E+11 | 176312.97 | 11-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.908277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.322360E+11 | 176503.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.965216E+09 | 16593.64 | 02-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.509774E+09 | 15215.82 | 06-FEB-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 64033157.80 | 4024.68 | 22-MAR-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18601160.87 | 3115.99 | 24-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 40662113.16 | 18538.96 | 30-MAY-14:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 82468620.34 | 16314.94 | 22-JUN-15:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 83658326.09 | 10626.41 | 11-JUL-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.100651E+09 | 20280.67 | 24-AUG-16:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 8808233.67 | 7726.60 | 01-SEP-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2883012.25 | 781.48 | 18-OCT-19:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 33764356.93 | 2685.10 | 03-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 79567995.96 | 5494.66 | 31-DEC-23:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199009E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2883012.25 | 781.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.965216E+09 | 20280.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.838217E+10 | 83810.14 | 23-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.617103E+10 | 83702.56 | 28-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139934E+10 | 83710.82 | 20-MAR-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.278879E+09 | 82816.57 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 49875562.97 | 11151.84 | 30-OCT-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.243838E+10 | 84109.80 | 27-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.449332E+10 | 83779.14 | 26-DEC-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.232130E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.838217E+10 | 84109.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.903543E+10 | 16115.22 | 23-JAN-05:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.803523E+10 | 16068.14 | 21-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.326820E+10 | 16032.48 | 20-MAR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104867E+10 | 16024.94 | 01-APR-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 44241956.16 | 15962.57 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 638455.79 | 276.72 | 30-SEP-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.370721E+09 | 15968.16 | 10-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.341209E+10 | 16145.97 | 27-NOV-05:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.663860E+10 | 16072.03 | 26-DEC-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.318538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.903543E+10 | 16145.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.584083E+10 | 19846.02 | 07-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.466213E+10 | 19925.74 | 21-FEB-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.203254E+10 | 19913.36 | 06-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.828500E+09 | 19765.35 | 03-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 38815648.70 | 19594.15 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1816491.06 | 1280.97 | 30-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.246454E+09 | 17988.26 | 31-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.222202E+10 | 19920.97 | 27-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.430732E+10 | 19933.88 | 04-DEC-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.201804E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.584083E+10 | 19933.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.606649E+10 | 22866.41 | 23-JAN-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.464614E+10 | 22792.29 | 28-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.215669E+10 | 22790.59 | 18-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.964283E+09 | 22626.22 | 01-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 61831611.51 | 22684.93 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.163614E+09 | 20754.11 | 27-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.199767E+10 | 22851.43 | 27-NOV-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.414903E+10 | 22790.59 | 12-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.202057E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.606649E+10 | 22866.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.535143E+10 | 20672.14 | 31-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.431238E+10 | 20669.01 | 09-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173109E+10 | 20649.18 | 06-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.648499E+09 | 20639.97 | 22-APR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 37730303.35 | 10238.84 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.207932E+09 | 13590.22 | 27-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.206213E+10 | 20674.59 | 27-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.373544E+10 | 20666.24 | 26-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.535143E+10 | 20674.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.433865E+10 | 28835.39 | 02-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.337598E+10 | 33262.72 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.596557E+09 | 10992.94 | 17-MAR-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18340286.55 | 5193.94 | 01-APR-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 384.10 | 0.55 | 05-MAY-06:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30.04 | 0.40 | 02-JUN-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 181.32 | 0.91 | 23-SEP-06:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 333.21 | 0.89 | 10-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 46336059.30 | 6156.95 | 22-NOV-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.297390E+09 | 11481.66 | 06-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.867325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.433865E+10 | 33262.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 7766105.30 | 7766105.30 | 8445.29 | 19-JAN-08:20 | 8445.29 | 0.00 |
February | 0.00 | 0.00 | 8016590.26 | 8016590.26 | 2433.81 | 27-FEB-13:10 | 2433.81 | 0.00 |
March | 0.00 | 0.00 | 0.148115E+10 | 0.144025E+10 | 73905.68 | 27-MAR-16:00 | 73905.68 | 0.02 |
April | 0.00 | 0.00 | 0.135049E+11 | 0.135006E+11 | 131969.26 | 07-APR-14:40 | 131969.26 | 0.12 |
May | 0.00 | 0.00 | 0.398011E+11 | 0.357248E+11 | 191830.31 | 30-MAY-14:10 | 191830.31 | 0.29 |
June | 0.00 | 0.00 | 0.141707E+12 | 0.120108E+12 | 240733.56 | 19-JUN-05:02 | 169557.20 | 0.66 |
July | 0.00 | 0.00 | 0.205624E+12 | 0.178447E+12 | 244769.73 | 10-JUL-04:23 | 177545.39 | 0.81 |
August | 0.00 | 0.00 | 0.210695E+12 | 0.190548E+12 | 235899.75 | 16-AUG-04:33 | 173108.13 | 0.83 |
September | 0.00 | 0.00 | 0.945966E+11 | 0.829802E+11 | 229688.31 | 22-SEP-04:12 | 160555.17 | 0.53 |
October | 0.00 | 0.00 | 0.424268E+11 | 0.324564E+11 | 187067.26 | 06-OCT-04:12 | 79430.25 | 0.29 |
November | 0.00 | 0.00 | 0.144595E+10 | 0.133672E+10 | 64637.48 | 10-NOV-06:02 | 25153.19 | 0.02 |
December | 0.00 | 0.00 | 1674477.14 | 1674477.14 | 754.09 | 22-DEC-09:50 | 754.09 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.751300E+12 | 0.656560E+12 | 0.30 | |||
Minimum of Months | 0.00 | 0.00 | 1674477.14 | 1674477.14 | 754.09 | 754.09 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.210695E+12 | 0.190548E+12 | 244769.73 | 191830.31 | 0.83 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 8522055.50 | 8522055.50 | 890.45 | 12-JAN-14:30 | 890.45 | 0.00 |
February | 0.00 | 0.00 | 7011180.15 | 7011180.15 | 1716.00 | 28-FEB-15:00 | 1716.00 | 0.00 |
March | 0.00 | 0.00 | 0.938278E+10 | 0.935866E+10 | 486271.98 | 27-MAR-16:00 | 486271.98 | 0.02 |
April | 0.00 | 0.00 | 0.949777E+11 | 0.949643E+11 | 1031171.87 | 07-APR-13:40 | 1031171.87 | 0.11 |
May | 0.00 | 0.00 | 0.329684E+12 | 0.296686E+12 | 1891420.12 | 30-MAY-14:07 | 1891420.12 | 0.29 |
June | 0.00 | 0.00 | 0.104514E+13 | 0.849947E+12 | 1991518.90 | 19-JUN-04:12 | 1391715.66 | 0.58 |
July | 0.00 | 0.00 | 0.135575E+13 | 0.109472E+13 | 2462515.81 | 24-JUL-05:02 | 1527466.67 | 0.63 |
August | 0.00 | 0.00 | 0.134904E+13 | 0.117116E+13 | 1926269.70 | 14-AUG-04:12 | 1468296.97 | 0.62 |
September | 0.00 | 0.00 | 0.731540E+12 | 0.627714E+12 | 1923893.67 | 07-SEP-04:12 | 1395640.37 | 0.50 |
October | 0.00 | 0.00 | 0.334980E+12 | 0.255271E+12 | 1403816.05 | 06-OCT-05:03 | 602077.38 | 0.28 |
November | 0.00 | 0.00 | 0.105748E+11 | 0.100482E+11 | 505463.35 | 10-NOV-06:02 | 195587.13 | 0.02 |
December | 0.00 | 0.00 | 5796710.99 | 5796710.99 | 1806.04 | 15-DEC-13:20 | 1806.04 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.526110E+13 | 0.440989E+13 | 0.26 | |||
Minimum of Months | 0.00 | 0.00 | 5796710.99 | 5796710.99 | 890.45 | 890.45 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.135575E+13 | 0.117116E+13 | 2462515.81 | 1891420.12 | 0.63 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 13104266.75 | 13104266.75 | 2581.37 | 15-JAN-11:00 | 2581.37 | 0.00 |
February | 0.00 | 0.00 | 9473899.31 | 9473899.31 | 704.07 | 09-FEB-11:30 | 704.07 | 0.00 |
March | 0.00 | 0.00 | 0.743436E+09 | 0.743301E+09 | 41780.88 | 27-MAR-16:00 | 41780.88 | 0.02 |
April | 0.00 | 0.00 | 0.958783E+10 | 0.958783E+10 | 114835.87 | 07-APR-14:50 | 114835.87 | 0.11 |
May | 0.00 | 0.00 | 0.343775E+11 | 0.312590E+11 | 196954.24 | 30-MAY-13:37 | 196954.24 | 0.28 |
June | 0.00 | 0.00 | 0.112788E+12 | 0.929521E+11 | 214437.41 | 19-JUN-04:12 | 148014.32 | 0.58 |
July | 0.00 | 0.00 | 0.150235E+12 | 0.122836E+12 | 255018.49 | 24-JUL-05:02 | 154717.44 | 0.64 |
August | 0.00 | 0.00 | 0.148347E+12 | 0.130125E+12 | 231460.53 | 17-AUG-03:02 | 154285.96 | 0.62 |
September | 0.00 | 0.00 | 0.748297E+11 | 0.642595E+11 | 196382.23 | 01-SEP-04:12 | 141680.03 | 0.50 |
October | 0.00 | 0.00 | 0.314840E+11 | 0.239865E+11 | 140775.17 | 06-OCT-05:03 | 60391.73 | 0.28 |
November | 0.00 | 0.00 | 0.804963E+09 | 0.764048E+09 | 20096.55 | 03-NOV-14:00 | 20096.55 | 0.02 |
December | 0.00 | 0.00 | 9382863.50 | 9382863.50 | 634.79 | 14-DEC-10:10 | 634.79 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.563229E+12 | 0.476545E+12 | 0.26 | |||
Minimum of Months | 0.00 | 0.00 | 9382863.50 | 9382863.50 | 634.79 | 634.79 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.150235E+12 | 0.130125E+12 | 255018.49 | 196954.24 | 0.64 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.270904E+09 | 0.146497E+09 | 40491.33 | 24-JAN-07:12 | 17866.40 | 0.01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.211246E+10 | 0.209198E+10 | 47632.77 | 27-MAR-16:00 | 47632.77 | 0.02 |
April | 0.00 | 0.00 | 0.730891E+10 | 0.724891E+10 | 74161.58 | 10-APR-06:23 | 43619.06 | 0.08 |
May | 0.00 | 0.00 | 0.233540E+11 | 0.192753E+11 | 112318.80 | 31-MAY-10:30 | 91150.44 | 0.20 |
June | 0.00 | 0.00 | 0.467177E+11 | 0.373683E+11 | 167129.99 | 27-JUN-16:00 | 81358.95 | 0.26 |
July | 0.00 | 0.00 | 0.253463E+11 | 0.196246E+11 | 159622.75 | 24-JUL-08:20 | 58371.05 | 0.09 |
August | 0.00 | 0.00 | 0.339721E+11 | 0.300868E+11 | 138447.35 | 31-AUG-07:20 | 80752.90 | 0.14 |
September | 0.00 | 0.00 | 0.371656E+11 | 0.326743E+11 | 141366.46 | 22-SEP-11:20 | 52369.43 | 0.26 |
October | 0.00 | 0.00 | 0.298458E+11 | 0.229451E+11 | 114354.95 | 06-OCT-09:01 | 49945.50 | 0.26 |
November | 0.00 | 0.00 | 0.750686E+09 | 0.580024E+09 | 92407.12 | 10-NOV-07:25 | 35972.21 | 0.02 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.206844E+12 | 0.172042E+12 | 0.11 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.467177E+11 | 0.373683E+11 | 167129.99 | 91150.44 | 0.26 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.571647E+10 | 0.571638E+10 | 3756.02 | 19-JAN-14:00 | 3756.02 | 0.00 |
February | 0.00 | 0.00 | 0.106820E+11 | 0.106765E+11 | 5097.29 | 14-FEB-17:35 | 5097.29 | 0.00 |
March | 0.00 | 0.00 | 0.144030E+11 | 0.131296E+11 | 216277.59 | 27-MAR-16:00 | 170667.88 | 0.00 |
April | 0.00 | 0.00 | 0.994331E+11 | 0.845951E+11 | 398806.65 | 07-APR-13:00 | 398806.65 | 0.00 |
May | 0.00 | 0.00 | 0.223153E+11 | 0.216897E+11 | 218637.10 | 31-MAY-23:20 | 216843.95 | 0.00 |
June | 0.00 | 0.00 | 0.368175E+12 | 0.350388E+12 | 349662.23 | 21-JUN-16:40 | 222195.69 | 0.00 |
July | 0.00 | 0.00 | 0.848894E+12 | 0.832319E+12 | 401666.44 | 31-JUL-23:55 | 401666.44 | 0.00 |
August | 0.00 | 0.00 | 0.102620E+13 | 0.985235E+12 | 453810.05 | 31-AUG-06:11 | 405689.36 | 0.00 |
September | 0.00 | 0.00 | 0.939076E+11 | 0.894328E+11 | 266411.91 | 01-SEP-14:00 | 266411.91 | 0.00 |
October | 0.00 | 0.00 | 0.318958E+11 | 0.231142E+11 | 286823.85 | 25-OCT-10:50 | 224706.29 | 0.00 |
November | 0.00 | 0.00 | 0.107007E+11 | 0.104571E+11 | 46168.87 | 03-NOV-14:00 | 46168.87 | 0.00 |
December | 0.00 | 0.00 | 0.141978E+11 | 0.139864E+11 | 5969.57 | 26-DEC-00:50 | 5489.63 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.254652E+13 | 0.244074E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.571647E+10 | 0.571638E+10 | 3756.02 | 3756.02 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.102620E+13 | 0.985235E+12 | 453810.05 | 405689.36 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.350401E+10 | 0.349878E+10 | 2263.67 | 29-JAN-16:40 | 2263.67 | 0.00 |
February | 0.00 | 0.00 | 0.816188E+10 | 0.816188E+10 | 4327.55 | 20-FEB-16:30 | 4327.55 | 0.00 |
March | 0.00 | 0.00 | 0.150846E+11 | 0.150735E+11 | 7508.80 | 31-MAR-24:00 | 7508.80 | 0.00 |
April | 0.00 | 0.00 | 0.199108E+11 | 0.198851E+11 | 8849.80 | 23-APR-17:47 | 8849.80 | 0.00 |
May | 0.00 | 0.00 | 0.577464E+10 | 0.567947E+10 | 4165.86 | 31-MAY-23:40 | 4081.62 | 0.00 |
June | 0.00 | 0.00 | 0.111651E+11 | 0.108439E+11 | 5949.19 | 30-JUN-24:00 | 5928.03 | 0.00 |
July | 0.00 | 0.00 | 0.169732E+11 | 0.164896E+11 | 7872.87 | 31-JUL-23:55 | 7870.43 | 0.00 |
August | 0.00 | 0.00 | 0.219600E+11 | 0.215746E+11 | 9092.38 | 31-AUG-17:40 | 8734.37 | 0.00 |
September | 0.00 | 0.00 | 0.601598E+10 | 0.581345E+10 | 3944.34 | 30-SEP-24:00 | 3944.34 | 0.00 |
October | 0.00 | 0.00 | 0.108835E+11 | 0.107371E+11 | 5701.41 | 31-OCT-24:00 | 5700.97 | 0.00 |
November | 0.00 | 0.00 | 0.146333E+11 | 0.146161E+11 | 6301.10 | 03-NOV-16:00 | 6301.10 | 0.00 |
December | 0.00 | 0.00 | 0.198374E+11 | 0.198374E+11 | 8255.71 | 17-DEC-15:55 | 8255.71 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.153904E+12 | 0.152211E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.350401E+10 | 0.349878E+10 | 2263.67 | 2263.67 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.219600E+11 | 0.215746E+11 | 9092.38 | 8849.80 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.114559E+11 | 0.114141E+11 | 19097.15 | 20-JAN-16:30 | 19097.15 | 0.00 |
February | 0.00 | 0.00 | 0.582081E+11 | 0.582081E+11 | 38454.48 | 22-FEB-17:00 | 38454.48 | 0.00 |
March | 0.00 | 0.00 | 0.128614E+12 | 0.128501E+12 | 66083.64 | 31-MAR-23:40 | 66083.64 | 0.00 |
April | 0.00 | 0.00 | 0.179779E+12 | 0.179520E+12 | 81522.46 | 09-APR-17:32 | 81457.70 | 0.00 |
May | 0.00 | 0.00 | 0.497376E+11 | 0.488021E+11 | 39417.34 | 31-MAY-23:30 | 38480.44 | 0.00 |
June | 0.00 | 0.00 | 0.104110E+12 | 0.100922E+12 | 55799.77 | 30-JUN-24:00 | 55586.20 | 0.00 |
July | 0.00 | 0.00 | 0.159775E+12 | 0.154959E+12 | 74822.06 | 31-JUL-23:55 | 74789.48 | 0.00 |
August | 0.00 | 0.00 | 0.207723E+12 | 0.203874E+12 | 87095.58 | 31-AUG-17:30 | 83424.02 | 0.00 |
September | 0.00 | 0.00 | 0.524012E+11 | 0.504105E+11 | 35900.83 | 30-SEP-23:30 | 35900.83 | 0.00 |
October | 0.00 | 0.00 | 0.957852E+11 | 0.943321E+11 | 49549.90 | 31-OCT-24:00 | 49529.18 | 0.00 |
November | 0.00 | 0.00 | 0.122289E+12 | 0.122117E+12 | 58948.96 | 03-NOV-16:00 | 58948.96 | 0.00 |
December | 0.00 | 0.00 | 0.166011E+12 | 0.166011E+12 | 73813.74 | 08-DEC-16:10 | 73813.74 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.133589E+13 | 0.131907E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.114559E+11 | 0.114141E+11 | 19097.15 | 19097.15 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.207723E+12 | 0.203874E+12 | 87095.58 | 83424.02 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.448234E+09 | 0.444989E+09 | 1858.53 | 19-JAN-16:30 | 1858.53 | 0.00 |
February | 0.00 | 0.00 | 0.418377E+10 | 0.418377E+10 | 3747.35 | 22-FEB-17:00 | 3747.35 | 0.00 |
March | 0.00 | 0.00 | 0.115818E+11 | 0.115708E+11 | 6206.97 | 27-MAR-17:20 | 6081.23 | 0.00 |
April | 0.00 | 0.00 | 0.171380E+11 | 0.171123E+11 | 8228.34 | 09-APR-17:21 | 8217.91 | 0.00 |
May | 0.00 | 0.00 | 0.464268E+10 | 0.455010E+10 | 3912.03 | 31-MAY-23:30 | 3817.80 | 0.00 |
June | 0.00 | 0.00 | 0.104135E+11 | 0.100946E+11 | 5506.02 | 30-JUN-24:00 | 5484.23 | 0.00 |
July | 0.00 | 0.00 | 0.160887E+11 | 0.156071E+11 | 7491.63 | 31-JUL-23:55 | 7488.26 | 0.00 |
August | 0.00 | 0.00 | 0.208430E+11 | 0.204583E+11 | 8798.99 | 31-AUG-17:20 | 8417.32 | 0.00 |
September | 0.00 | 0.00 | 0.501868E+10 | 0.482002E+10 | 3292.22 | 30-SEP-23:20 | 3292.22 | 0.00 |
October | 0.00 | 0.00 | 0.877952E+10 | 0.863478E+10 | 4814.74 | 04-OCT-16:00 | 4494.69 | 0.00 |
November | 0.00 | 0.00 | 0.107186E+11 | 0.107016E+11 | 5883.41 | 03-NOV-16:00 | 5883.41 | 0.00 |
December | 0.00 | 0.00 | 0.146813E+11 | 0.146813E+11 | 7210.15 | 08-DEC-16:10 | 7210.15 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.124538E+12 | 0.122860E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.448234E+09 | 0.444989E+09 | 1858.53 | 1858.53 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.208430E+11 | 0.204583E+11 | 8798.99 | 8417.32 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 80359.88 | 1907487.36 | 02-JAN-04:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 60774.76 | 1587094.76 | 13-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17812.14 | 1350871.20 | 13-MAR-04:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4957.18 | 1180071.39 | 22-APR-05:02 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 416.43 | 161230.61 | 30-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 676.87 | 149877.11 | 22-JUN-13:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 179.02 | 75442.28 | 11-JUL-15:25 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 722.36 | 200089.05 | 24-AUG-18:40 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 13.44 | 15600.05 | 14-SEP-19:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 722.34 | 270036.43 | 28-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 18968.63 | 1452403.24 | 27-NOV-05:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 41876.16 | 1410344.10 | 26-DEC-05:11 |
Annual Sum or Average | 0.00 | 18753.19 | ||||
Minimum of Months | 0.00 | 0.00 | 13.44 | 15600.05 | ||
Maximum of Months | 0.00 | 0.00 | 80359.88 | 1907487.36 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 287.98 | 27077.09 | 24-JAN-07:13 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 203.18 | 5608.54 | 28-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 5523.45 | 640737.12 | 27-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 49043.19 | 1367798.20 | 07-APR-15:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 162729.25 | 2716581.60 | 30-MAY-13:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 545969.79 | 2564492.83 | 27-JUN-15:01 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 682505.38 | 2857672.58 | 24-JUL-05:04 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 678025.11 | 2400701.54 | 25-AUG-14:43 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 377620.29 | 2575692.96 | 06-SEP-11:22 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 171592.17 | 2653534.03 | 04-OCT-13:02 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 5559.35 | 332251.13 | 03-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 101.66 | 5513.99 | 15-DEC-13:20 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 224863.51 | 0.00 | ||||
Minimum of Months | 101.66 | 5513.99 | 0.00 | 0.00 | ||
Maximum of Months | 682505.38 | 2857672.58 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 81.65 | 32739.91 | 24-JAN-07:13 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 5.89 | 1733.78 | 28-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 5098.60 | 646252.95 | 27-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 48883.99 | 1790120.09 | 07-APR-14:20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 162355.49 | 2782899.63 | 30-MAY-13:07 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 545002.65 | 3623983.21 | 27-JUN-04:12 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 681708.80 | 3622937.81 | 28-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 679248.15 | 3598209.43 | 16-AUG-04:12 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 380916.03 | 3628804.43 | 14-SEP-04:12 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 176209.64 | 2898464.22 | 03-OCT-13:40 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 5254.99 | 411950.40 | 10-NOV-06:02 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 4.46 | 1574.80 | 15-DEC-13:20 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 225336.45 | 0.00 | ||||
Minimum of Months | 4.46 | 1574.80 | 0.00 | 0.00 | ||
Maximum of Months | 681708.80 | 3628804.43 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 14507.74 | 87408.82 | 20-JAN-17:05 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 46914.89 | 131116.03 | 22-FEB-16:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 84990.80 | 712819.14 | 27-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 185516.00 | 1362116.94 | 07-APR-13:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 95803.09 | 1120113.74 | 30-MAY-13:55 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 540271.01 | 1602509.92 | 19-JUN-12:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1074927.40 | 1647041.41 | 07-JUL-12:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1222213.41 | 1864908.61 | 24-AUG-15:30 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 251285.22 | 1237739.28 | 01-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 105379.89 | 947216.60 | 25-OCT-11:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 80052.79 | 167805.21 | 03-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 103966.93 | 223753.27 | 22-DEC-17:05 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 319952.97 | 0.00 | ||||
Minimum of Months | 14507.74 | 87408.82 | 0.00 | 0.00 | ||
Maximum of Months | 1222213.41 | 1864908.61 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 14762.12 | 52818.51 | 31-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 14998.81 | 52890.49 | 09-FEB-12:20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15584.59 | 52482.84 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 13860.34 | 50266.73 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 13352.85 | 47350.68 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12704.42 | 43855.23 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11079.10 | 40948.28 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 11972.37 | 39991.05 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 11565.51 | 41873.59 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12295.95 | 45155.97 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 13427.21 | 48541.79 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 13803.68 | 51250.17 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 13274.14 | ||||
Minimum of Months | 0.00 | 0.00 | 11079.10 | 39991.05 | ||
Maximum of Months | 0.00 | 0.00 | 15584.59 | 52890.49 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 27.19 | 14967.00 | 24-JAN-09:40 | 2347.52 | 177174.03 | 06-JAN-07:03 |
February | 22.57 | 10425.75 | 02-FEB-08:50 | 2640.18 | 175788.65 | 18-FEB-05:43 |
March | 4513.45 | 709887.90 | 27-MAR-16:00 | 3083.38 | 164827.99 | 23-MAR-11:10 |
April | 55169.39 | 1917342.53 | 07-APR-15:00 | 1558.43 | 128995.09 | 05-APR-05:40 |
May | 199473.12 | 3490723.48 | 30-MAY-13:13 | 1035.91 | 108174.65 | 01-MAY-09:10 |
June | 998097.58 | 5800833.39 | 15-JUN-12:20 | 254.13 | 90437.85 | 09-JUN-05:40 |
July | 1721816.91 | 6097396.50 | 20-JUL-14:30 | 3.34 | 17050.93 | 11-JUL-02:23 |
August | 1529238.01 | 6407944.07 | 03-AUG-13:40 | 316.25 | 59369.79 | 08-AUG-04:40 |
September | 622221.45 | 4946806.26 | 07-SEP-14:00 | 372.17 | 98652.56 | 23-SEP-11:20 |
October | 223731.26 | 3848660.69 | 03-OCT-13:02 | 1175.99 | 124136.07 | 18-OCT-14:20 |
November | 5027.28 | 378484.31 | 03-NOV-14:00 | 1387.05 | 129073.84 | 16-NOV-11:50 |
December | 8.51 | 9981.37 | 08-DEC-11:40 | 1299.81 | 166182.16 | 15-DEC-12:20 |
Annual Sum or Average | 450573.05 | 1282.76 | ||||
Minimum of Months | 8.51 | 9981.37 | 3.34 | 17050.93 | ||
Maximum of Months | 1721816.91 | 6407944.07 | 3083.38 | 177174.03 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.376455E+10 | 0.31 | 12818.57 | 06-JAN-06:01 | 1.32 |
February | 0.396607E+10 | 0.33 | 12818.57 | 03-FEB-06:01 | 1.32 |
March | 0.657356E+10 | 0.41 | 11712.44 | 29-MAR-14:50 | 1.24 |
April | 0.841301E+10 | 0.48 | 18980.65 | 07-APR-14:40 | 1.68 |
May | 0.880539E+10 | 0.48 | 22214.84 | 30-MAY-04:12 | 1.85 |
June | 0.147576E+11 | 0.68 | 22214.84 | 01-JUN-14:10 | 1.85 |
July | 0.197344E+11 | 0.83 | 22214.84 | 03-JUL-04:12 | 1.85 |
August | 0.219523E+11 | 0.90 | 22214.84 | 01-AUG-10:10 | 1.85 |
September | 0.108760E+11 | 0.54 | 22214.84 | 01-SEP-14:40 | 1.85 |
October | 0.879062E+10 | 0.47 | 16312.32 | 06-OCT-04:12 | 1.52 |
November | 0.602617E+10 | 0.38 | 13201.69 | 06-NOV-14:30 | 1.34 |
December | 0.537105E+10 | 0.36 | 10470.88 | 07-DEC-06:01 | 1.17 |
Annual Sum or Average | 0.119031E+12 | 0.51 | |||
Minimum of Months | 0.376455E+10 | 0.31 | 10470.88 | 1.17 | |
Maximum of Months | 0.219523E+11 | 0.90 | 22214.84 | 1.85 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.327093E+11 | 0.32 | 51389.53 | 02-JAN-04:01 | 0.81 |
February | 0.299996E+11 | 0.32 | 51389.53 | 06-FEB-06:01 | 0.80 |
March | 0.387032E+11 | 0.33 | 99601.13 | 31-MAR-05:03 | 1.17 |
April | 0.460289E+11 | 0.36 | 122865.62 | 07-APR-15:00 | 1.33 |
May | 0.652157E+11 | 0.42 | 209524.63 | 30-MAY-05:02 | 1.86 |
June | 0.909084E+11 | 0.51 | 209524.63 | 01-JUN-14:15 | 1.86 |
July | 0.101806E+12 | 0.54 | 209524.63 | 03-JUL-04:12 | 1.86 |
August | 0.112696E+12 | 0.57 | 209524.63 | 01-AUG-05:02 | 1.86 |
September | 0.705614E+11 | 0.44 | 209524.63 | 01-SEP-04:12 | 1.86 |
October | 0.563739E+11 | 0.38 | 117349.78 | 05-OCT-15:50 | 1.29 |
November | 0.343744E+11 | 0.31 | 116565.69 | 15-NOV-06:02 | 1.29 |
December | 0.313925E+11 | 0.30 | 43669.37 | 21-DEC-14:40 | 0.74 |
Annual Sum or Average | 0.710769E+12 | 0.40 | |||
Minimum of Months | 0.299996E+11 | 0.30 | 43669.37 | 0.74 | |
Maximum of Months | 0.112696E+12 | 0.57 | 209524.63 | 1.86 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.386403E+10 | 0.37 | 5109.80 | 02-JAN-04:01 | 0.77 |
February | 0.339454E+10 | 0.36 | 5109.80 | 03-FEB-06:01 | 0.77 |
March | 0.359571E+10 | 0.33 | 6399.14 | 29-MAR-15:20 | 0.86 |
April | 0.418911E+10 | 0.33 | 13559.05 | 07-APR-14:50 | 1.35 |
May | 0.618310E+10 | 0.40 | 22499.21 | 30-MAY-11:10 | 1.85 |
June | 0.945433E+10 | 0.50 | 22499.21 | 01-JUN-14:30 | 1.85 |
July | 0.110778E+11 | 0.54 | 22499.21 | 10-JUL-05:02 | 1.85 |
August | 0.121174E+11 | 0.57 | 22499.21 | 01-AUG-05:02 | 1.85 |
September | 0.674629E+10 | 0.41 | 22499.21 | 01-SEP-14:32 | 1.85 |
October | 0.486698E+10 | 0.34 | 12956.62 | 04-OCT-16:00 | 1.30 |
November | 0.316432E+10 | 0.31 | 5310.55 | 03-NOV-14:40 | 0.78 |
December | 0.339875E+10 | 0.33 | 5109.80 | 02-DEC-06:01 | 0.77 |
Annual Sum or Average | 0.720523E+11 | 0.40 | |||
Minimum of Months | 0.316432E+10 | 0.31 | 5109.80 | 0.77 | |
Maximum of Months | 0.121174E+11 | 0.57 | 22499.21 | 1.85 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.340884E+10 | 0.34 | 12050.25 | 02-JAN-07:03 | 1.78 |
February | 0.227737E+10 | 0.30 | 12050.25 | 01-FEB-07:05 | 1.79 |
March | 0.714696E+10 | 0.52 | 12050.25 | 01-MAR-07:05 | 1.78 |
April | 0.120375E+11 | 0.73 | 12050.25 | 01-APR-06:05 | 1.78 |
May | 0.121969E+11 | 0.72 | 12050.25 | 01-MAY-06:05 | 1.78 |
June | 0.861890E+10 | 0.50 | 12050.25 | 01-JUN-06:10 | 1.76 |
July | 0.281886E+10 | 0.15 | 12050.25 | 05-JUL-06:10 | 1.72 |
August | 0.476607E+10 | 0.26 | 12050.25 | 07-AUG-06:10 | 1.72 |
September | 0.944161E+10 | 0.55 | 12050.25 | 05-SEP-06:10 | 1.72 |
October | 0.128225E+11 | 0.74 | 12050.25 | 02-OCT-06:10 | 1.77 |
November | 0.123726E+11 | 0.75 | 12050.25 | 01-NOV-06:05 | 1.78 |
December | 0.754410E+10 | 0.52 | 12050.25 | 01-DEC-07:05 | 1.79 |
Annual Sum or Average | 0.954522E+11 | 0.51 | |||
Minimum of Months | 0.227737E+10 | 0.15 | 12050.25 | 1.72 | |
Maximum of Months | 0.128225E+11 | 0.75 | 12050.25 | 1.79 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.108436E+12 | 1.35 | 40485.40 | 01-JAN-00:02 | 1.35 |
February | 0.979423E+11 | 1.35 | 40485.40 | 01-FEB-00:10 | 1.35 |
March | 0.108436E+12 | 1.35 | 40485.40 | 01-MAR-00:10 | 1.35 |
April | 0.104938E+12 | 1.35 | 40485.40 | 01-APR-00:10 | 1.35 |
May | 0.108436E+12 | 1.34 | 40485.40 | 01-MAY-00:10 | 1.34 |
June | 0.104938E+12 | 1.34 | 40485.40 | 01-JUN-00:10 | 1.34 |
July | 0.108436E+12 | 1.34 | 40485.40 | 01-JUL-00:10 | 1.34 |
August | 0.108436E+12 | 1.34 | 40485.40 | 01-AUG-00:05 | 1.34 |
September | 0.104938E+12 | 1.34 | 40485.40 | 01-SEP-00:03 | 1.34 |
October | 0.108436E+12 | 1.34 | 40485.40 | 01-OCT-00:10 | 1.34 |
November | 0.104938E+12 | 1.35 | 40485.40 | 01-NOV-00:10 | 1.35 |
December | 0.108436E+12 | 1.35 | 40485.40 | 01-DEC-00:10 | 1.35 |
Annual Sum or Average | 0.127675E+13 | 1.35 | |||
Minimum of Months | 0.979423E+11 | 1.34 | 40485.40 | 1.34 | |
Maximum of Months | 0.108436E+12 | 1.35 | 40485.40 | 1.35 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.144452E+10 | 0.92 | 539.32 | 01-JAN-00:02 | 0.92 |
February | 0.130473E+10 | 0.92 | 539.32 | 01-FEB-00:10 | 0.92 |
March | 0.144452E+10 | 0.92 | 539.32 | 01-MAR-00:10 | 0.92 |
April | 0.139793E+10 | 0.92 | 539.32 | 01-APR-00:10 | 0.91 |
May | 0.144452E+10 | 0.91 | 539.32 | 01-MAY-00:10 | 0.91 |
June | 0.139793E+10 | 0.91 | 539.32 | 01-JUN-00:10 | 0.91 |
July | 0.144452E+10 | 0.91 | 539.32 | 01-JUL-00:10 | 0.91 |
August | 0.144452E+10 | 0.91 | 539.32 | 01-AUG-00:05 | 0.91 |
September | 0.139793E+10 | 0.91 | 539.32 | 01-SEP-00:03 | 0.91 |
October | 0.144452E+10 | 0.91 | 539.32 | 01-OCT-00:10 | 0.91 |
November | 0.139793E+10 | 0.92 | 539.32 | 01-NOV-00:10 | 0.91 |
December | 0.144452E+10 | 0.92 | 539.32 | 01-DEC-00:10 | 0.92 |
Annual Sum or Average | 0.170081E+11 | 0.92 | |||
Minimum of Months | 0.130473E+10 | 0.91 | 539.32 | 0.91 | |
Maximum of Months | 0.144452E+10 | 0.92 | 539.32 | 0.92 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.138205E+11 | 0.92 | 5159.98 | 01-JAN-00:02 | 0.92 |
February | 0.124830E+11 | 0.92 | 5159.98 | 01-FEB-00:10 | 0.92 |
March | 0.138205E+11 | 0.92 | 5159.98 | 01-MAR-00:10 | 0.92 |
April | 0.133747E+11 | 0.92 | 5159.98 | 01-APR-00:10 | 0.91 |
May | 0.138205E+11 | 0.91 | 5159.98 | 01-MAY-00:10 | 0.91 |
June | 0.133747E+11 | 0.91 | 5159.98 | 01-JUN-00:10 | 0.91 |
July | 0.138205E+11 | 0.91 | 5159.98 | 01-JUL-00:10 | 0.91 |
August | 0.138205E+11 | 0.91 | 5159.98 | 01-AUG-00:05 | 0.91 |
September | 0.133747E+11 | 0.91 | 5159.98 | 01-SEP-00:03 | 0.91 |
October | 0.138205E+11 | 0.91 | 5159.98 | 01-OCT-00:10 | 0.91 |
November | 0.133747E+11 | 0.92 | 5159.98 | 01-NOV-00:10 | 0.91 |
December | 0.138205E+11 | 0.92 | 5159.98 | 01-DEC-00:10 | 0.92 |
Annual Sum or Average | 0.162725E+12 | 0.92 | |||
Minimum of Months | 0.124830E+11 | 0.91 | 5159.98 | 0.91 | |
Maximum of Months | 0.138205E+11 | 0.92 | 5159.98 | 0.92 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.140756E+10 | 0.92 | 525.52 | 01-JAN-00:02 | 0.92 |
February | 0.127134E+10 | 0.92 | 525.52 | 01-FEB-00:10 | 0.92 |
March | 0.140756E+10 | 0.92 | 525.52 | 01-MAR-00:10 | 0.92 |
April | 0.136215E+10 | 0.92 | 525.52 | 01-APR-00:10 | 0.91 |
May | 0.140756E+10 | 0.91 | 525.52 | 01-MAY-00:10 | 0.91 |
June | 0.136215E+10 | 0.91 | 525.52 | 01-JUN-00:10 | 0.91 |
July | 0.140756E+10 | 0.91 | 525.52 | 01-JUL-00:10 | 0.91 |
August | 0.140756E+10 | 0.91 | 525.52 | 01-AUG-00:05 | 0.91 |
September | 0.136215E+10 | 0.91 | 525.52 | 01-SEP-00:03 | 0.91 |
October | 0.140756E+10 | 0.91 | 525.52 | 01-OCT-00:10 | 0.91 |
November | 0.136215E+10 | 0.92 | 525.52 | 01-NOV-00:10 | 0.91 |
December | 0.140756E+10 | 0.92 | 525.52 | 01-DEC-00:10 | 0.92 |
Annual Sum or Average | 0.165729E+11 | 0.92 | |||
Minimum of Months | 0.127134E+10 | 0.91 | 525.52 | 0.91 | |
Maximum of Months | 0.140756E+10 | 0.92 | 525.52 | 0.92 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 30976015.41 | 27878413.87 | 1322.78 | 02-JAN-06:02 | 1190.51 | 1190.51 | 50.42 | 10.97 |
February | 14439737.70 | 12995763.93 | 1323.32 | 06-FEB-06:02 | 1190.98 | 1190.98 | 49.49 | 10.98 |
March | 2796889.42 | 2517200.48 | 434.39 | 17-MAR-05:01 | 390.95 | 390.95 | 37.56 | 6.75 |
April | 574314.61 | 516883.14 | 319.29 | 03-APR-05:02 | 287.36 | 287.36 | 35.05 | 5.86 |
May | 49789.56 | 44810.61 | 9.37 | 30-MAY-13:23 | 8.44 | 8.44 | 36.20 | 0.82 |
June | 111563.38 | 100407.04 | 9.89 | 01-JUN-14:55 | 8.90 | 8.90 | 46.95 | 0.85 |
July | 46115.87 | 41504.28 | 6.30 | 11-JUL-14:20 | 5.67 | 5.67 | 60.25 | 0.62 |
August | 140824.87 | 126742.38 | 30.00 | 24-AUG-18:40 | 27.00 | 27.00 | 53.85 | 1.70 |
September | 1617.48 | 1455.73 | 0.74 | 14-SEP-19:50 | 0.67 | 0.67 | 47.39 | 0.11 |
October | 59830.06 | 53847.06 | 15.22 | 28-OCT-05:03 | 13.69 | 13.69 | 25.14 | 1.14 |
November | 3176062.32 | 2858456.09 | 435.77 | 22-NOV-06:01 | 392.19 | 392.19 | 40.26 | 6.75 |
December | 6916561.11 | 6224905.00 | 434.83 | 07-DEC-06:01 | 391.34 | 391.34 | 41.48 | 6.74 |
Annual Sum or Average | 59289321.79 | 53360389.61 | ||||||
Minimum of Months | 1617.48 | 1455.73 | 0.74 | 0.67 | 0.67 | 25.14 | 0.11 | |
Maximum of Months | 30976015.41 | 27878413.87 | 1323.32 | 1190.98 | 1190.98 | 60.25 | 10.98 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 67403.92 | 60663.53 | 21.49 | 24-JAN-07:13 | 19.34 | 19.34 | 6.70 | 3.42 |
February | 2717.88 | 2446.09 | 0.32 | 28-FEB-15:00 | 0.29 | 0.29 | 6.70 | 0.09 |
March | 3991616.41 | 3592454.77 | 320.33 | 27-MAR-16:00 | 288.30 | 288.30 | 6.70 | 16.07 |
April | 86060489.37 | 77454440.44 | 5806.04 | 07-APR-14:20 | 5225.44 | 5225.44 | 8.83 | 58.81 |
May | 0.296583E+09 | 0.266925E+09 | 12185.47 | 30-MAY-13:50 | 10966.92 | 10966.92 | 10.12 | 79.16 |
June | 0.106726E+10 | 0.960536E+09 | 12184.89 | 16-JUN-05:03 | 10966.40 | 10966.40 | 9.89 | 79.16 |
July | 0.141107E+10 | 0.126996E+10 | 12189.96 | 28-JUL-05:04 | 10970.96 | 10970.96 | 11.33 | 79.16 |
August | 0.174127E+10 | 0.156714E+10 | 13563.53 | 08-AUG-12:05 | 12207.18 | 12207.18 | 12.06 | 82.58 |
September | 0.866877E+09 | 0.780189E+09 | 12192.73 | 06-SEP-11:50 | 10973.46 | 10973.46 | 12.07 | 79.16 |
October | 0.491444E+09 | 0.442299E+09 | 13541.66 | 03-OCT-13:40 | 12187.50 | 12187.50 | 11.24 | 82.50 |
November | 3355675.74 | 3020108.17 | 431.16 | 10-NOV-06:02 | 388.04 | 388.04 | 6.70 | 18.59 |
December | 1719.32 | 1547.39 | 0.23 | 15-DEC-13:20 | 0.21 | 0.21 | 6.70 | 0.07 |
Annual Sum or Average | 0.596799E+10 | 0.537119E+10 | ||||||
Minimum of Months | 1719.32 | 1547.39 | 0.23 | 0.21 | 0.21 | 6.70 | 0.07 | |
Maximum of Months | 0.174127E+10 | 0.156714E+10 | 13563.53 | 12207.18 | 12207.18 | 12.07 | 82.58 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.614597E+09 | 0.553137E+09 | 4667.71 | 02-JAN-07:03 | 4200.94 | 4200.94 | 6.71 | 41.29 |
February | 0.530311E+09 | 0.477280E+09 | 4667.71 | 01-FEB-13:50 | 4200.94 | 4200.94 | 6.72 | 41.29 |
March | 0.127325E+10 | 0.114593E+10 | 4667.71 | 01-MAR-07:15 | 4200.94 | 4200.94 | 6.72 | 41.29 |
April | 0.231941E+10 | 0.208747E+10 | 4667.71 | 01-APR-08:40 | 4200.94 | 4200.94 | 6.72 | 41.29 |
May | 0.557447E+10 | 0.501702E+10 | 4667.71 | 01-MAY-08:40 | 4200.94 | 4200.94 | 6.73 | 41.29 |
June | 0.867561E+10 | 0.780805E+10 | 4667.71 | 01-JUN-04:12 | 4200.94 | 4200.94 | 9.77 | 41.29 |
July | 0.105564E+11 | 0.950080E+10 | 4667.71 | 01-JUL-04:12 | 4200.94 | 4200.94 | 12.30 | 41.29 |
August | 0.110123E+11 | 0.991109E+10 | 4667.71 | 01-AUG-00:10 | 4200.94 | 4200.94 | 6.95 | 41.29 |
September | 0.735821E+10 | 0.662239E+10 | 4667.71 | 01-SEP-00:17 | 4200.94 | 4200.94 | 6.95 | 41.29 |
October | 0.459468E+10 | 0.413522E+10 | 4667.71 | 02-OCT-06:11 | 4200.94 | 4200.94 | 7.29 | 41.29 |
November | 0.881270E+09 | 0.793143E+09 | 4667.71 | 01-NOV-12:40 | 4200.94 | 4200.94 | 6.74 | 41.29 |
December | 0.289258E+09 | 0.260332E+09 | 4667.71 | 01-DEC-09:05 | 4200.94 | 4200.94 | 6.73 | 41.29 |
Annual Sum or Average | 0.536798E+11 | 0.483119E+11 | ||||||
Minimum of Months | 0.289258E+09 | 0.260332E+09 | 4667.71 | 4200.94 | 4200.94 | 6.71 | 41.29 | |
Maximum of Months | 0.110123E+11 | 0.991109E+10 | 4667.71 | 4200.94 | 4200.94 | 12.30 | 41.29 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 | 6.70 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
May | 0.189976E+09 | 0.170978E+09 | 4667.71 | 30-MAY-10:25 | 4200.94 | 4200.94 | 11.20 | 41.29 |
June | 0.151934E+10 | 0.136740E+10 | 4667.71 | 01-JUN-10:00 | 4200.94 | 4200.94 | 15.82 | 20.64 |
July | 0.252266E+10 | 0.227040E+10 | 4667.71 | 03-JUL-08:50 | 4200.94 | 4200.94 | 15.09 | 20.64 |
August | 0.254969E+10 | 0.229472E+10 | 4667.71 | 01-AUG-07:30 | 4200.94 | 4200.94 | 15.36 | 20.64 |
September | 0.763310E+09 | 0.686979E+09 | 4667.71 | 01-SEP-05:05 | 4200.94 | 4200.94 | 15.52 | 20.64 |
October | 0.326319E+09 | 0.293687E+09 | 4667.71 | 03-OCT-10:20 | 4200.94 | 4200.94 | 15.29 | 20.64 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 6.75 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
Annual Sum or Average | 0.787129E+10 | 0.708416E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 | |
Maximum of Months | 0.254969E+10 | 0.229472E+10 | 4667.71 | 4200.94 | 4200.94 | 15.82 | 41.29 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.101607E+11 | 0.914467E+10 | 3793.59 | 01-JAN-00:02 | 3414.23 | 3414.23 | 18.49 | 15.84 |
February | 0.917744E+10 | 0.825970E+10 | 3793.59 | 01-FEB-00:10 | 3414.23 | 3414.23 | 19.17 | 15.84 |
March | 0.101607E+11 | 0.914467E+10 | 3793.59 | 01-MAR-00:10 | 3414.23 | 3414.23 | 19.62 | 15.84 |
April | 0.983297E+10 | 0.884968E+10 | 3793.59 | 01-APR-00:10 | 3414.23 | 3414.23 | 20.28 | 15.84 |
May | 0.101607E+11 | 0.914467E+10 | 3793.59 | 01-MAY-00:10 | 3414.23 | 3414.23 | 18.86 | 15.84 |
June | 0.983297E+10 | 0.884968E+10 | 3793.59 | 01-JUN-00:10 | 3414.23 | 3414.23 | 19.94 | 15.84 |
July | 0.101607E+11 | 0.914467E+10 | 3793.59 | 01-JUL-00:10 | 3414.23 | 3414.23 | 31.78 | 15.84 |
August | 0.101607E+11 | 0.914467E+10 | 3793.59 | 01-AUG-00:05 | 3414.23 | 3414.23 | 39.57 | 15.84 |
September | 0.983297E+10 | 0.884968E+10 | 3793.59 | 01-SEP-00:03 | 3414.23 | 3414.23 | 29.01 | 15.84 |
October | 0.101607E+11 | 0.914467E+10 | 3793.59 | 01-OCT-00:10 | 3414.23 | 3414.23 | 19.36 | 15.84 |
November | 0.983297E+10 | 0.884968E+10 | 3793.59 | 01-NOV-00:10 | 3414.23 | 3414.23 | 19.76 | 15.84 |
December | 0.101607E+11 | 0.914467E+10 | 3793.59 | 01-DEC-00:10 | 3414.23 | 3414.23 | 20.23 | 15.84 |
Annual Sum or Average | 0.119635E+12 | 0.107671E+12 | ||||||
Minimum of Months | 0.917744E+10 | 0.825970E+10 | 3793.59 | 3414.23 | 3414.23 | 18.49 | 15.84 | |
Maximum of Months | 0.101607E+11 | 0.914467E+10 | 3793.59 | 3414.23 | 3414.23 | 39.57 | 15.84 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:03 | 16.86 | 16.86 | 57.15 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:02 | 16.86 | 16.86 | 56.96 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:03 | 16.86 | 16.86 | 56.91 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:03 | 16.86 | 16.86 | 57.04 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:02 | 16.86 | 16.86 | 57.47 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 57.43 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 57.59 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:02 | 16.86 | 16.86 | 57.73 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 57.66 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 57.32 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:03 | 16.86 | 16.86 | 57.35 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:03 | 16.86 | 16.86 | 57.14 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 56.91 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.73 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.234176E+10 | 0.210759E+10 | 17882.80 | 24-JAN-09:40 | 16094.52 | 16094.52 | 21.15 | 72.50 |
February | 0.203138E+10 | 0.182824E+10 | 17882.61 | 02-FEB-08:50 | 16094.35 | 16094.35 | 21.13 | 72.50 |
March | 0.487803E+10 | 0.439023E+10 | 17912.32 | 27-MAR-16:00 | 16121.08 | 16121.08 | 23.44 | 72.50 |
April | 0.889169E+10 | 0.800252E+10 | 17969.00 | 07-APR-15:00 | 16172.10 | 16172.10 | 27.43 | 72.50 |
May | 0.220566E+11 | 0.198509E+11 | 35920.92 | 30-MAY-13:13 | 32328.83 | 32328.83 | 26.86 | 144.99 |
June | 0.383028E+11 | 0.344726E+11 | 35998.94 | 15-JUN-11:40 | 32399.04 | 32399.04 | 29.83 | 144.99 |
July | 0.491330E+11 | 0.442197E+11 | 35998.94 | 06-JUL-09:30 | 32399.04 | 32399.04 | 29.59 | 144.99 |
August | 0.515598E+11 | 0.464038E+11 | 35998.94 | 02-AUG-07:40 | 32399.04 | 32399.04 | 29.90 | 144.99 |
September | 0.307346E+11 | 0.276611E+11 | 35993.43 | 07-SEP-14:00 | 32394.09 | 32394.09 | 29.26 | 144.99 |
October | 0.186316E+11 | 0.167685E+11 | 35938.72 | 03-OCT-13:02 | 32344.85 | 32344.85 | 27.45 | 144.99 |
November | 0.337658E+10 | 0.303892E+10 | 17898.23 | 03-NOV-14:00 | 16108.41 | 16108.41 | 22.35 | 72.50 |
December | 0.110801E+10 | 0.997210E+09 | 17882.59 | 08-DEC-11:40 | 16094.33 | 16094.33 | 21.13 | 72.50 |
Annual Sum or Average | 0.233046E+12 | 0.209741E+12 | ||||||
Minimum of Months | 0.110801E+10 | 0.997210E+09 | 17882.59 | 16094.33 | 16094.33 | 21.13 | 72.50 | |
Maximum of Months | 0.515598E+11 | 0.464038E+11 | 35998.94 | 32399.04 | 32399.04 | 29.90 | 144.99 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 38.06 | 38.06 | 80359.88 | 1907487.36 | 02-JAN-04:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 26.61 | 26.61 | 60774.76 | 1587094.76 | 13-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 24.11 | 24.11 | 17812.14 | 1350871.20 | 13-MAR-04:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.81 | 20.81 | 4957.18 | 1180071.39 | 22-APR-05:02 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 21.50 | 21.50 | 416.43 | 161230.61 | 30-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 41.93 | 41.93 | 676.87 | 149877.11 | 22-JUN-13:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.12 | 57.12 | 179.02 | 75442.28 | 11-JUL-15:25 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 57.26 | 57.26 | 722.36 | 200089.05 | 24-AUG-18:40 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 49.69 | 49.69 | 13.44 | 15600.05 | 14-SEP-19:50 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 46.81 | 46.81 | 722.34 | 270036.43 | 28-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.70 | 21.70 | 18968.63 | 1452403.24 | 27-NOV-05:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 22.48 | 22.48 | 41876.16 | 1410344.10 | 26-DEC-05:11 |
Annual Sum or Average | 0.00 | 18753.19 | ||||||
Minimum of Months | 0.00 | 0.00 | 20.81 | 20.81 | 13.44 | 15600.05 | ||
Maximum of Months | 0.00 | 0.00 | 57.26 | 57.26 | 80359.88 | 1907487.36 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 287.98 | 27077.09 | 24-JAN-07:13 | 6.86 | 6.70 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 203.18 | 5608.54 | 28-FEB-15:00 | 6.73 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 5523.45 | 640737.12 | 27-MAR-16:00 | 10.40 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 49043.19 | 1367798.20 | 07-APR-15:00 | 14.61 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 162729.25 | 2716581.60 | 30-MAY-13:30 | 14.56 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 545969.79 | 2564492.83 | 27-JUN-15:01 | 14.12 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 682505.38 | 2857672.58 | 24-JUL-05:04 | 14.97 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 678025.11 | 2400701.54 | 25-AUG-14:43 | 13.64 | 6.70 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 377620.29 | 2575692.96 | 06-SEP-11:22 | 14.15 | 6.70 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 171592.17 | 2653534.03 | 04-OCT-13:02 | 14.38 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 5559.35 | 332251.13 | 03-NOV-14:00 | 8.62 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 101.66 | 5513.99 | 15-DEC-13:20 | 6.73 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 224863.51 | 0.00 | ||||||
Minimum of Months | 101.66 | 5513.99 | 6.73 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 682505.38 | 2857672.58 | 14.97 | 6.70 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 81.65 | 32739.91 | 24-JAN-07:13 | 8.98 | 6.70 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 5.89 | 1733.78 | 28-FEB-15:00 | 11.11 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 5098.60 | 646252.95 | 27-MAR-16:00 | 16.31 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 48883.99 | 1790120.09 | 07-APR-14:20 | 13.97 | 8.85 | 0.00 | 0.00 | 01-APR-00:10 |
May | 162355.49 | 2782899.63 | 30-MAY-13:07 | 15.26 | 10.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 545002.65 | 3623983.21 | 27-JUN-04:12 | 17.64 | 11.92 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 681708.80 | 3622937.81 | 28-JUL-05:02 | 17.64 | 11.92 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 679248.15 | 3598209.43 | 16-AUG-04:12 | 17.57 | 11.88 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 380916.03 | 3628804.43 | 14-SEP-04:12 | 17.66 | 11.93 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 176209.64 | 2898464.22 | 03-OCT-13:40 | 15.10 | 11.21 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 5254.99 | 411950.40 | 10-NOV-06:02 | 11.99 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 4.46 | 1574.80 | 15-DEC-13:20 | 12.29 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 225336.45 | 0.00 | ||||||
Minimum of Months | 4.46 | 1574.80 | 8.98 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 681708.80 | 3628804.43 | 17.66 | 11.93 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 14507.74 | 87408.82 | 20-JAN-17:05 | 19.92 | 18.33 | 0.00 | 0.00 | 01-JAN-00:02 |
February | 46914.89 | 131116.03 | 22-FEB-16:10 | 20.71 | 18.33 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 84990.80 | 712819.14 | 27-MAR-16:00 | 31.16 | 24.53 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 185516.00 | 1362116.94 | 07-APR-13:00 | 42.59 | 30.90 | 0.00 | 0.00 | 01-APR-00:10 |
May | 95803.09 | 1120113.74 | 30-MAY-13:55 | 38.36 | 31.75 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 540271.01 | 1602509.92 | 19-JUN-12:00 | 46.76 | 39.37 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1074927.40 | 1647041.41 | 07-JUL-12:00 | 47.53 | 37.52 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1222213.41 | 1864908.61 | 24-AUG-15:30 | 51.27 | 38.54 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 251285.22 | 1237739.28 | 01-SEP-14:00 | 40.42 | 33.56 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 105379.89 | 947216.60 | 25-OCT-11:00 | 35.32 | 27.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 80052.79 | 167805.21 | 03-NOV-14:00 | 21.38 | 18.72 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 103966.93 | 223753.27 | 22-DEC-17:05 | 22.39 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 319952.97 | 0.00 | ||||||
Minimum of Months | 14507.74 | 87408.82 | 19.92 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 1222213.41 | 1864908.61 | 51.27 | 39.37 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:02 | 58.09 | 58.09 | 14762.12 | 52818.51 | 31-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.53 | 57.53 | 14998.81 | 52890.49 | 09-FEB-12:20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.55 | 57.55 | 15584.59 | 52482.84 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.64 | 57.64 | 13860.34 | 50266.73 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.24 | 58.24 | 13352.85 | 47350.68 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.96 | 57.96 | 12704.42 | 43855.23 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 58.09 | 58.09 | 11079.10 | 40948.28 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 58.16 | 58.16 | 11972.37 | 39991.05 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 58.14 | 58.14 | 11565.51 | 41873.59 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 58.05 | 58.05 | 12295.95 | 45155.97 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.90 | 57.90 | 13427.21 | 48541.79 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.74 | 57.74 | 13803.68 | 51250.17 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 13274.14 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.53 | 57.53 | 11079.10 | 39991.05 | ||
Maximum of Months | 0.00 | 0.00 | 58.24 | 58.24 | 15584.59 | 52890.49 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 27.19 | 14967.00 | 24-JAN-09:40 | 21.15 | 20.63 | 2347.52 | 177174.03 | 06-JAN-07:03 |
February | 22.57 | 10425.75 | 02-FEB-08:50 | 21.13 | 20.26 | 2640.18 | 175788.65 | 18-FEB-05:43 |
March | 4513.45 | 709887.90 | 27-MAR-16:00 | 23.44 | 21.10 | 3083.38 | 164827.99 | 23-MAR-11:10 |
April | 55169.39 | 1917342.53 | 07-APR-15:00 | 27.43 | 22.28 | 1558.43 | 128995.09 | 05-APR-05:40 |
May | 199473.12 | 3490723.48 | 30-MAY-13:13 | 26.86 | 22.62 | 1035.91 | 108174.65 | 01-MAY-09:10 |
June | 998097.58 | 5800833.39 | 15-JUN-12:20 | 30.67 | 27.36 | 254.13 | 90437.85 | 09-JUN-05:40 |
July | 1721816.91 | 6097396.50 | 20-JUL-14:30 | 31.16 | 27.91 | 3.34 | 17050.93 | 11-JUL-02:23 |
August | 1529238.01 | 6407944.07 | 03-AUG-13:40 | 31.67 | 28.34 | 316.25 | 59369.79 | 08-AUG-04:40 |
September | 622221.45 | 4946806.26 | 07-SEP-14:00 | 29.26 | 26.24 | 372.17 | 98652.56 | 23-SEP-11:20 |
October | 223731.26 | 3848660.69 | 03-OCT-13:02 | 27.45 | 23.50 | 1175.99 | 124136.07 | 18-OCT-14:20 |
November | 5027.28 | 378484.31 | 03-NOV-14:00 | 22.35 | 21.10 | 1387.05 | 129073.84 | 16-NOV-11:50 |
December | 8.51 | 9981.37 | 08-DEC-11:40 | 21.13 | 20.34 | 1299.81 | 166182.16 | 15-DEC-12:20 |
Annual Sum or Average | 450573.05 | 1282.76 | ||||||
Minimum of Months | 8.51 | 9981.37 | 21.13 | 20.26 | 3.34 | 17050.93 | ||
Maximum of Months | 1721816.91 | 6407944.07 | 31.67 | 28.34 | 3083.38 | 177174.03 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.242374E+10 | 0.00 | 7766105.30 | 0.376455E+10 | 0.00 | 0.00 |
February | 0.164237E+10 | 0.00 | 8016590.26 | 0.396607E+10 | 0.00 | 0.00 |
March | 0.269555E+09 | 0.00 | 0.148115E+10 | 0.657356E+10 | 0.00 | 0.00 |
April | 33291291.30 | 0.00 | 0.135049E+11 | 0.841301E+10 | 0.00 | 0.00 |
May | 1941692.10 | 0.00 | 0.398011E+11 | 0.880539E+10 | 0.00 | 0.00 |
June | 79672312.64 | 0.00 | 0.141707E+12 | 0.147576E+11 | 0.00 | 0.00 |
July | 48729850.54 | 0.00 | 0.205624E+12 | 0.197344E+11 | 0.00 | 0.00 |
August | 0.197366E+09 | 0.00 | 0.210695E+12 | 0.219523E+11 | 0.00 | 0.00 |
September | 25645800.79 | 0.00 | 0.945966E+11 | 0.108760E+11 | 0.00 | 0.00 |
October | 1012571.15 | 0.00 | 0.424268E+11 | 0.879062E+10 | 0.00 | 0.00 |
November | 0.157173E+09 | 0.00 | 0.144595E+10 | 0.602617E+10 | 0.00 | 0.00 |
December | 0.511278E+09 | 0.00 | 1674477.14 | 0.537105E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.539177E+10 | 0.00 | 0.751300E+12 | 0.119031E+12 | 0.00 | 0.00 |
Minimum of Months | 1012571.15 | 0.00 | 1674477.14 | 0.376455E+10 | 0.00 | 0.00 |
Maximum of Months | 0.242374E+10 | 0.00 | 0.210695E+12 | 0.219523E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.174011E+12 | 0.00 | 8522055.50 | 0.327093E+11 | 0.00 | 0.00 |
February | 0.114445E+12 | 0.00 | 7011180.15 | 0.299996E+11 | 0.00 | 0.00 |
March | 0.364540E+11 | 0.00 | 0.938278E+10 | 0.387032E+11 | 0.00 | 0.00 |
April | 0.907205E+10 | 0.00 | 0.949777E+11 | 0.460289E+11 | 0.00 | 0.00 |
May | 0.787213E+09 | 0.00 | 0.329684E+12 | 0.652157E+11 | 0.00 | 0.00 |
June | 0.152023E+10 | 0.00 | 0.104514E+13 | 0.909084E+11 | 0.00 | 0.00 |
July | 0.348267E+09 | 0.00 | 0.135575E+13 | 0.101806E+12 | 0.00 | 0.00 |
August | 0.168620E+10 | 0.00 | 0.134904E+13 | 0.112696E+12 | 0.00 | 0.00 |
September | 13435462.21 | 0.00 | 0.731540E+12 | 0.705614E+11 | 0.00 | 0.00 |
October | 0.103590E+10 | 0.00 | 0.334980E+12 | 0.563739E+11 | 0.00 | 0.00 |
November | 0.370472E+11 | 0.00 | 0.105748E+11 | 0.343744E+11 | 0.00 | 0.00 |
December | 0.884716E+11 | 0.00 | 5796710.99 | 0.313925E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.464892E+12 | 0.00 | 0.526110E+13 | 0.710769E+12 | 0.00 | 0.00 |
Minimum of Months | 13435462.21 | 0.00 | 5796710.99 | 0.299996E+11 | 0.00 | 0.00 |
Maximum of Months | 0.174011E+12 | 0.00 | 0.135575E+13 | 0.112696E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.356416E+11 | 0.00 | 13104266.75 | 0.386403E+10 | 0.00 | 0.00 |
February | 0.283367E+11 | 0.00 | 9473899.31 | 0.339454E+10 | 0.00 | 0.00 |
March | 0.106519E+11 | 0.00 | 0.743436E+09 | 0.359571E+10 | 0.00 | 0.00 |
April | 0.378743E+10 | 0.00 | 0.958783E+10 | 0.418911E+10 | 0.00 | 0.00 |
May | 0.223282E+09 | 0.00 | 0.343775E+11 | 0.618310E+10 | 0.00 | 0.00 |
June | 82468620.34 | 0.00 | 0.112788E+12 | 0.945433E+10 | 0.00 | 0.00 |
July | 83658326.09 | 0.00 | 0.150235E+12 | 0.110778E+11 | 0.00 | 0.00 |
August | 0.100651E+09 | 0.00 | 0.148347E+12 | 0.121174E+11 | 0.00 | 0.00 |
September | 11263180.52 | 0.00 | 0.748297E+11 | 0.674629E+10 | 0.00 | 0.00 |
October | 0.104148E+10 | 0.00 | 0.314840E+11 | 0.486698E+10 | 0.00 | 0.00 |
November | 0.121661E+11 | 0.00 | 0.804963E+09 | 0.316432E+10 | 0.00 | 0.00 |
December | 0.234033E+11 | 0.00 | 9382863.50 | 0.339875E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.115530E+12 | 0.00 | 0.563229E+12 | 0.720523E+11 | 0.00 | 0.00 |
Minimum of Months | 11263180.52 | 0.00 | 9382863.50 | 0.316432E+10 | 0.00 | 0.00 |
Maximum of Months | 0.356416E+11 | 0.00 | 0.150235E+12 | 0.121174E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.433865E+10 | 0.00 | 0.270904E+09 | 0.340884E+10 | 0.00 | 0.00 |
February | 0.337598E+10 | 0.00 | 0.00 | 0.227737E+10 | 0.00 | 0.00 |
March | 0.596557E+09 | 0.00 | 0.211246E+10 | 0.714696E+10 | 0.00 | 0.00 |
April | 18340286.55 | 0.00 | 0.730891E+10 | 0.120375E+11 | 0.00 | 0.00 |
May | 384.10 | 0.00 | 0.233540E+11 | 0.121969E+11 | 0.00 | 0.00 |
June | 30.04 | 0.00 | 0.467177E+11 | 0.861890E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.253463E+11 | 0.281886E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.339721E+11 | 0.476607E+10 | 0.00 | 0.00 |
September | 181.32 | 0.00 | 0.371656E+11 | 0.944161E+10 | 0.00 | 0.00 |
October | 333.21 | 0.00 | 0.298458E+11 | 0.128225E+11 | 0.00 | 0.00 |
November | 46336059.30 | 0.00 | 0.750686E+09 | 0.123726E+11 | 0.00 | 0.00 |
December | 0.297390E+09 | 0.00 | 0.00 | 0.754410E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.867325E+10 | 0.00 | 0.206844E+12 | 0.954522E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.227737E+10 | 0.00 | 0.00 |
Maximum of Months | 0.433865E+10 | 0.00 | 0.467177E+11 | 0.128225E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.101204E+11 | 0.230685E+12 | 0.00 | 43.84 |
February | 0.00 | 0.00 | 0.162914E+11 | 0.314548E+12 | 0.00 | 78.49 |
March | 0.00 | 0.00 | 0.214946E+11 | 0.312260E+12 | 0.00 | 73.18 |
April | 0.00 | 0.00 | 0.130860E+12 | 0.270423E+12 | 0.00 | 49.87 |
May | 0.00 | 0.00 | 0.321836E+11 | 0.166665E+12 | 0.00 | 17.99 |
June | 0.00 | 0.00 | 0.478631E+12 | 0.232091E+12 | 0.00 | 6.21 |
July | 0.00 | 0.00 | 0.110856E+13 | 0.368098E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.134221E+13 | 0.430857E+12 | 0.00 | 2.39 |
September | 0.00 | 0.00 | 0.125175E+12 | 0.152094E+12 | 0.00 | 5.91 |
October | 0.00 | 0.00 | 0.441163E+11 | 0.213988E+12 | 0.00 | 34.72 |
November | 0.00 | 0.00 | 0.166358E+11 | 0.291601E+12 | 0.00 | 67.23 |
December | 0.00 | 0.00 | 0.215756E+11 | 0.370850E+12 | 0.00 | 94.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.334784E+13 | 0.335416E+13 | 0.00 | 474.71 |
Minimum of Months | 0.00 | 0.00 | 0.101204E+11 | 0.152094E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.134221E+13 | 0.430857E+12 | 0.00 | 94.87 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.444891E+10 | 0.238943E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.102315E+11 | 0.337437E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.185932E+11 | 0.495312E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.243366E+11 | 0.582367E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.723784E+10 | 0.290772E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.141691E+11 | 0.440191E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.219679E+11 | 0.643917E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.283182E+11 | 0.780282E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.762179E+10 | 0.300373E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.134806E+11 | 0.404162E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.179941E+11 | 0.475869E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.243829E+11 | 0.599007E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.192783E+12 | 0.558863E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.444891E+10 | 0.238943E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.283182E+11 | 0.780282E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.147658E+11 | 0.171304E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.733603E+11 | 0.276352E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.158940E+12 | 0.441463E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.220081E+12 | 0.536768E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.624680E+11 | 0.265509E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.132215E+12 | 0.414795E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.206894E+12 | 0.609389E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.267990E+12 | 0.740877E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.665296E+11 | 0.275031E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.118832E+12 | 0.368671E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.150786E+12 | 0.418714E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.204749E+12 | 0.525584E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.167761E+13 | 0.504446E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.147658E+11 | 0.171304E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.267990E+12 | 0.740877E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.581841E+09 | 0.154116E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.529685E+10 | 0.238442E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.143435E+11 | 0.416919E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.210121E+11 | 0.523627E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.584194E+10 | 0.260682E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.132332E+11 | 0.418189E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.208414E+11 | 0.616027E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.269063E+11 | 0.747079E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.638305E+10 | 0.272653E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.109095E+11 | 0.353759E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.132488E+11 | 0.389233E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.181631E+11 | 0.488934E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.156762E+12 | 0.487966E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.581841E+09 | 0.154116E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.269063E+11 | 0.747079E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.376455E+10 | 7766105.30 | 0.242374E+10 | 0.155714E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.396607E+10 | 8016590.26 | 0.164237E+10 | 0.138601E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.657356E+10 | 0.148115E+10 | 0.269555E+09 | 0.354120E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.841301E+10 | 0.135049E+11 | 33291291.30 | 0.289596E+09 | 12515945.29 | 0.00 | 0.00 | 0.00 |
May | 0.880539E+10 | 0.398011E+11 | 1941692.10 | 0.00 | 0.265754E+09 | 0.00 | 0.00 | 0.00 |
June | 0.147576E+11 | 0.141707E+12 | 79672312.64 | 0.00 | 0.403922E+10 | 0.00 | 0.00 | 0.00 |
July | 0.197344E+11 | 0.205624E+12 | 48729850.54 | 0.00 | 0.165072E+11 | 0.00 | 0.00 | 0.00 |
August | 0.219523E+11 | 0.210695E+12 | 0.197366E+09 | 0.00 | 0.165821E+11 | 0.00 | 0.00 | 0.00 |
September | 0.108760E+11 | 0.945966E+11 | 25645800.79 | 0.00 | 0.229276E+10 | 0.00 | 0.00 | 0.00 |
October | 0.879062E+10 | 0.424268E+11 | 1012571.15 | 30996842.45 | 23136713.74 | 0.00 | 0.00 | 0.00 |
November | 0.602617E+10 | 0.144595E+10 | 0.157173E+09 | 0.206185E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.537105E+10 | 1674477.14 | 0.511278E+09 | 0.511217E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119031E+12 | 0.751300E+12 | 0.539177E+10 | 0.404673E+11 | 0.397227E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.376455E+10 | 1674477.14 | 1012571.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.219523E+11 | 0.210695E+12 | 0.242374E+10 | 0.155714E+11 | 0.165821E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.327093E+11 | 8522055.50 | 0.174011E+12 | 0.214680E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.299996E+11 | 7011180.15 | 0.114445E+12 | 0.206606E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.387032E+11 | 0.938278E+10 | 0.364540E+11 | 0.821017E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.460289E+11 | 0.949777E+11 | 0.907205E+10 | 0.111694E+11 | 0.160168E+09 | 0.00 | 0.00 | 0.00 |
May | 0.652157E+11 | 0.329684E+12 | 0.787213E+09 | 9302359.68 | 0.246999E+10 | 0.00 | 0.00 | 0.00 |
June | 0.909084E+11 | 0.104514E+13 | 0.152023E+10 | 0.00 | 0.405332E+11 | 0.00 | 0.00 | 0.00 |
July | 0.101806E+12 | 0.135575E+13 | 0.348267E+09 | 0.00 | 0.163562E+12 | 0.00 | 0.00 | 0.00 |
August | 0.112696E+12 | 0.134904E+13 | 0.168620E+10 | 0.00 | 0.163478E+12 | 0.00 | 0.00 | 0.00 |
September | 0.705614E+11 | 0.731540E+12 | 13435462.21 | 0.00 | 0.233708E+11 | 0.00 | 0.00 | 0.00 |
October | 0.563739E+11 | 0.334980E+12 | 0.103590E+10 | 0.127729E+10 | 0.318162E+09 | 0.00 | 0.00 | 0.00 |
November | 0.343744E+11 | 0.105748E+11 | 0.370472E+11 | 0.522268E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.313925E+11 | 5796710.99 | 0.884716E+11 | 0.135325E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.710769E+12 | 0.526110E+13 | 0.464892E+12 | 0.703396E+12 | 0.393892E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.299996E+11 | 5796710.99 | 13435462.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.112696E+12 | 0.135575E+13 | 0.174011E+12 | 0.214680E+12 | 0.163562E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.386403E+10 | 13104266.75 | 0.356416E+11 | 0.240875E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.339454E+10 | 9473899.31 | 0.283367E+11 | 0.237042E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.359571E+10 | 0.743436E+09 | 0.106519E+11 | 0.112605E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.418911E+10 | 0.958783E+10 | 0.378743E+10 | 0.227546E+10 | 3433820.47 | 0.00 | 0.00 | 0.00 |
May | 0.618310E+10 | 0.343775E+11 | 0.223282E+09 | 18004513.53 | 0.172141E+09 | 0.00 | 0.00 | 0.00 |
June | 0.945433E+10 | 0.112788E+12 | 82468620.34 | 0.00 | 0.335590E+10 | 0.00 | 0.00 | 0.00 |
July | 0.110778E+11 | 0.150235E+12 | 83658326.09 | 0.00 | 0.146068E+11 | 0.00 | 0.00 | 0.00 |
August | 0.121174E+11 | 0.148347E+12 | 0.100651E+09 | 0.00 | 0.149261E+11 | 0.00 | 0.00 | 0.00 |
September | 0.674629E+10 | 0.748297E+11 | 11263180.52 | 0.00 | 0.184575E+10 | 0.00 | 0.00 | 0.00 |
October | 0.486698E+10 | 0.314840E+11 | 0.104148E+10 | 0.392334E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.316432E+10 | 0.804963E+09 | 0.121661E+11 | 0.753252E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.339875E+10 | 9382863.50 | 0.234033E+11 | 0.179544E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.720523E+11 | 0.563229E+12 | 0.115530E+12 | 0.872250E+11 | 0.349101E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.316432E+10 | 9382863.50 | 11263180.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.121174E+11 | 0.150235E+12 | 0.356416E+11 | 0.240875E+11 | 0.149261E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.340884E+10 | 0.270904E+09 | 0.433865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.227737E+10 | 0.00 | 0.337598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.714696E+10 | 0.211246E+10 | 0.596557E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.120375E+11 | 0.730891E+10 | 18340286.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.121969E+11 | 0.233540E+11 | 384.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.861890E+10 | 0.467177E+11 | 30.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.281886E+10 | 0.253463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.476607E+10 | 0.339721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.944161E+10 | 0.371656E+11 | 181.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.128225E+11 | 0.298458E+11 | 333.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123726E+11 | 0.750686E+09 | 46336059.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.754410E+10 | 0.00 | 0.297390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.954522E+11 | 0.206844E+12 | 0.867325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.227737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.128225E+11 | 0.467177E+11 | 0.433865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.108436E+12 | 0.571647E+10 | 0.00 | 0.00 | 0.00 | 0.117317E+12 | 0.00 | 0.00 |
February | 0.979423E+11 | 0.106820E+11 | 0.00 | 0.00 | 0.00 | 0.210051E+12 | 0.00 | 0.00 |
March | 0.108436E+12 | 0.144030E+11 | 0.00 | 0.00 | 0.00 | 0.195851E+12 | 0.00 | 0.00 |
April | 0.104938E+12 | 0.994331E+11 | 0.00 | 0.00 | 0.00 | 0.133457E+12 | 0.00 | 0.00 |
May | 0.108436E+12 | 0.223153E+11 | 0.00 | 0.00 | 0.00 | 0.481437E+11 | 0.00 | 0.00 |
June | 0.104938E+12 | 0.368175E+12 | 0.00 | 0.00 | 0.00 | 0.166223E+11 | 0.00 | 0.00 |
July | 0.108436E+12 | 0.848894E+12 | 0.00 | 0.00 | 0.00 | 1338699.52 | 0.00 | 0.00 |
August | 0.108436E+12 | 0.102620E+13 | 0.00 | 0.00 | 0.00 | 0.638661E+10 | 0.00 | 0.00 |
September | 0.104938E+12 | 0.939076E+11 | 0.00 | 0.00 | 0.00 | 0.158180E+11 | 0.00 | 0.00 |
October | 0.108436E+12 | 0.318958E+11 | 0.00 | 0.00 | 0.00 | 0.929132E+11 | 0.00 | 0.00 |
November | 0.104938E+12 | 0.107007E+11 | 0.00 | 0.00 | 0.00 | 0.179918E+12 | 0.00 | 0.00 |
December | 0.108436E+12 | 0.141978E+11 | 0.00 | 0.00 | 0.00 | 0.253893E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.127675E+13 | 0.254652E+13 | 0.00 | 0.00 | 0.00 | 0.127037E+13 | 0.00 | 0.00 |
Minimum of Months | 0.979423E+11 | 0.571647E+10 | 0.00 | 0.00 | 0.00 | 1338699.52 | 0.00 | 0.00 |
Maximum of Months | 0.108436E+12 | 0.102620E+13 | 0.00 | 0.00 | 0.00 | 0.253893E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.144452E+10 | 0.350401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130473E+10 | 0.816188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144452E+10 | 0.150846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139793E+10 | 0.199108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144452E+10 | 0.577464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139793E+10 | 0.111651E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144452E+10 | 0.169732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144452E+10 | 0.219600E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139793E+10 | 0.601598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144452E+10 | 0.108835E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139793E+10 | 0.146333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144452E+10 | 0.198374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170081E+11 | 0.153904E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130473E+10 | 0.350401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144452E+10 | 0.219600E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.138205E+11 | 0.114559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124830E+11 | 0.582081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138205E+11 | 0.128614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133747E+11 | 0.179779E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138205E+11 | 0.497376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133747E+11 | 0.104110E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138205E+11 | 0.159775E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138205E+11 | 0.207723E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133747E+11 | 0.524012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138205E+11 | 0.957852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133747E+11 | 0.122289E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138205E+11 | 0.166011E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162725E+12 | 0.133589E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124830E+11 | 0.114559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138205E+11 | 0.207723E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.140756E+10 | 0.448234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127134E+10 | 0.418377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140756E+10 | 0.115818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136215E+10 | 0.171380E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140756E+10 | 0.464268E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136215E+10 | 0.104135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140756E+10 | 0.160887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140756E+10 | 0.208430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136215E+10 | 0.501868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140756E+10 | 0.877952E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136215E+10 | 0.107186E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140756E+10 | 0.146813E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165729E+11 | 0.124538E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127134E+10 | 0.448234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140756E+10 | 0.208430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.376455E+10 | 0.242374E+10 | 7766105.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.396607E+10 | 0.164237E+10 | 8016590.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.657356E+10 | 0.269555E+09 | 0.148115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.841301E+10 | 33291291.30 | 0.135049E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.880539E+10 | 1941692.10 | 0.398011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147576E+11 | 79672312.64 | 0.141707E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.197344E+11 | 48729850.54 | 0.205624E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.219523E+11 | 0.197366E+09 | 0.210695E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.108760E+11 | 25645800.79 | 0.945966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.879062E+10 | 1012571.15 | 0.424268E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.602617E+10 | 0.157173E+09 | 0.144595E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.537105E+10 | 0.511278E+09 | 1674477.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119031E+12 | 0.539177E+10 | 0.751300E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.376455E+10 | 1012571.15 | 1674477.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.219523E+11 | 0.242374E+10 | 0.210695E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.327093E+11 | 0.174011E+12 | 8522055.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.299996E+11 | 0.114445E+12 | 7011180.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.387032E+11 | 0.364540E+11 | 0.938278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.460289E+11 | 0.907205E+10 | 0.949777E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.652157E+11 | 0.787213E+09 | 0.329684E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.909084E+11 | 0.152023E+10 | 0.104514E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.101806E+12 | 0.348267E+09 | 0.135575E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.112696E+12 | 0.168620E+10 | 0.134904E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.705614E+11 | 13435462.21 | 0.731540E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.563739E+11 | 0.103590E+10 | 0.334980E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.343744E+11 | 0.370472E+11 | 0.105748E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.313925E+11 | 0.884716E+11 | 5796710.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.710769E+12 | 0.464892E+12 | 0.526110E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.299996E+11 | 13435462.21 | 5796710.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.112696E+12 | 0.174011E+12 | 0.135575E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.386403E+10 | 0.356416E+11 | 13104266.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.339454E+10 | 0.283367E+11 | 9473899.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.359571E+10 | 0.106519E+11 | 0.743436E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.418911E+10 | 0.378743E+10 | 0.958783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.618310E+10 | 0.223282E+09 | 0.343775E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.945433E+10 | 82468620.34 | 0.112788E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.110778E+11 | 83658326.09 | 0.150235E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.121174E+11 | 0.100651E+09 | 0.148347E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.674629E+10 | 11263180.52 | 0.748297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.486698E+10 | 0.104148E+10 | 0.314840E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.316432E+10 | 0.121661E+11 | 0.804963E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.339875E+10 | 0.234033E+11 | 9382863.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.720523E+11 | 0.115530E+12 | 0.563229E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.316432E+10 | 11263180.52 | 9382863.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.121174E+11 | 0.356416E+11 | 0.150235E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.340884E+10 | 0.433865E+10 | 0.270904E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.227737E+10 | 0.337598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.714696E+10 | 0.596557E+09 | 0.211246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.120375E+11 | 18340286.55 | 0.730891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.121969E+11 | 384.10 | 0.233540E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.861890E+10 | 30.04 | 0.467177E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.281886E+10 | 0.00 | 0.253463E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.476607E+10 | 0.00 | 0.339721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.944161E+10 | 181.32 | 0.371656E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.128225E+11 | 333.21 | 0.298458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123726E+11 | 46336059.30 | 0.750686E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.754410E+10 | 0.297390E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.954522E+11 | 0.867325E+10 | 0.206844E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.227737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.128225E+11 | 0.433865E+10 | 0.467177E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.108436E+12 | 0.00 | 0.101204E+11 | 0.00 | 0.440394E+10 | 0.00 | 0.00 | 0.00 | 0.117845E+12 | 0.00 | 0.00 | 0.00 |
February | 0.979423E+11 | 0.00 | 0.162914E+11 | 0.00 | 0.560937E+10 | 0.00 | 0.00 | 0.00 | 0.210997E+12 | 0.00 | 0.00 | 0.00 |
March | 0.108436E+12 | 0.00 | 0.214946E+11 | 0.00 | 0.709160E+10 | 0.00 | 0.00 | 0.00 | 0.196732E+12 | 0.00 | 0.00 | 0.00 |
April | 0.104938E+12 | 0.00 | 0.130860E+12 | 0.00 | 0.314273E+11 | 0.00 | 0.00 | 0.00 | 0.134058E+12 | 0.00 | 0.00 | 0.00 |
May | 0.108436E+12 | 0.00 | 0.321836E+11 | 0.00 | 0.986831E+10 | 0.00 | 0.00 | 0.00 | 0.483605E+11 | 0.00 | 0.00 | 0.00 |
June | 0.104938E+12 | 0.00 | 0.478631E+12 | 0.00 | 0.110456E+12 | 0.00 | 0.00 | 0.00 | 0.166971E+11 | 0.00 | 0.00 | 0.00 |
July | 0.108436E+12 | 0.00 | 0.110856E+13 | 0.00 | 0.259661E+12 | 0.00 | 0.00 | 0.00 | 1344725.55 | 0.00 | 0.00 | 0.00 |
August | 0.108436E+12 | 0.00 | 0.134221E+13 | 0.00 | 0.316006E+12 | 0.00 | 0.00 | 0.00 | 0.641536E+10 | 0.00 | 0.00 | 0.00 |
September | 0.104938E+12 | 0.00 | 0.125175E+12 | 0.00 | 0.312670E+11 | 0.00 | 0.00 | 0.00 | 0.158892E+11 | 0.00 | 0.00 | 0.00 |
October | 0.108436E+12 | 0.00 | 0.441163E+11 | 0.00 | 0.122205E+11 | 0.00 | 0.00 | 0.00 | 0.933315E+11 | 0.00 | 0.00 | 0.00 |
November | 0.104938E+12 | 0.00 | 0.166358E+11 | 0.00 | 0.593510E+10 | 0.00 | 0.00 | 0.00 | 0.180728E+12 | 0.00 | 0.00 | 0.00 |
December | 0.108436E+12 | 0.00 | 0.215756E+11 | 0.00 | 0.737782E+10 | 0.00 | 0.00 | 0.00 | 0.255036E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127675E+13 | 0.00 | 0.334784E+13 | 0.00 | 0.801323E+12 | 0.00 | 0.00 | 0.00 | 0.127609E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.979423E+11 | 0.00 | 0.101204E+11 | 0.00 | 0.440394E+10 | 0.00 | 0.00 | 0.00 | 1344725.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.108436E+12 | 0.00 | 0.134221E+13 | 0.00 | 0.316006E+12 | 0.00 | 0.00 | 0.00 | 0.255036E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.144452E+10 | 0.00 | 0.444891E+10 | 0.00 | 0.944903E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130473E+10 | 0.00 | 0.102315E+11 | 0.00 | 0.206964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144452E+10 | 0.00 | 0.185932E+11 | 0.00 | 0.350860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139793E+10 | 0.00 | 0.243366E+11 | 0.00 | 0.442574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144452E+10 | 0.00 | 0.723784E+10 | 0.00 | 0.146319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139793E+10 | 0.00 | 0.141691E+11 | 0.00 | 0.300398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144452E+10 | 0.00 | 0.219679E+11 | 0.00 | 0.499465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144452E+10 | 0.00 | 0.283182E+11 | 0.00 | 0.635830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139793E+10 | 0.00 | 0.762179E+10 | 0.00 | 0.160580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144452E+10 | 0.00 | 0.134806E+11 | 0.00 | 0.259710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139793E+10 | 0.00 | 0.179941E+11 | 0.00 | 0.336076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144452E+10 | 0.00 | 0.243829E+11 | 0.00 | 0.454555E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170081E+11 | 0.00 | 0.192783E+12 | 0.00 | 0.388782E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130473E+10 | 0.00 | 0.444891E+10 | 0.00 | 0.944903E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144452E+10 | 0.00 | 0.283182E+11 | 0.00 | 0.635830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.138205E+11 | 0.00 | 0.147658E+11 | 0.00 | 0.330989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124830E+11 | 0.00 | 0.733603E+11 | 0.00 | 0.151522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138205E+11 | 0.00 | 0.158940E+12 | 0.00 | 0.303258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133747E+11 | 0.00 | 0.220081E+12 | 0.00 | 0.403022E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138205E+11 | 0.00 | 0.624680E+11 | 0.00 | 0.127304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133747E+11 | 0.00 | 0.132215E+12 | 0.00 | 0.281048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138205E+11 | 0.00 | 0.206894E+12 | 0.00 | 0.471184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138205E+11 | 0.00 | 0.267990E+12 | 0.00 | 0.602672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133747E+11 | 0.00 | 0.665296E+11 | 0.00 | 0.141284E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138205E+11 | 0.00 | 0.118832E+12 | 0.00 | 0.230466E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133747E+11 | 0.00 | 0.150786E+12 | 0.00 | 0.284968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138205E+11 | 0.00 | 0.204749E+12 | 0.00 | 0.387379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162725E+12 | 0.00 | 0.167761E+13 | 0.00 | 0.341721E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124830E+11 | 0.00 | 0.147658E+11 | 0.00 | 0.330989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138205E+11 | 0.00 | 0.267990E+12 | 0.00 | 0.602672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.140756E+10 | 0.00 | 0.581841E+09 | 0.00 | 0.133606E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127134E+10 | 0.00 | 0.529685E+10 | 0.00 | 0.111308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140756E+10 | 0.00 | 0.143435E+11 | 0.00 | 0.276163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136215E+10 | 0.00 | 0.210121E+11 | 0.00 | 0.387412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140756E+10 | 0.00 | 0.584194E+10 | 0.00 | 0.119926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136215E+10 | 0.00 | 0.132332E+11 | 0.00 | 0.281973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140756E+10 | 0.00 | 0.208414E+11 | 0.00 | 0.475271E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140756E+10 | 0.00 | 0.269063E+11 | 0.00 | 0.606323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136215E+10 | 0.00 | 0.638305E+10 | 0.00 | 0.136437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140756E+10 | 0.00 | 0.109095E+11 | 0.00 | 0.213003E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136215E+10 | 0.00 | 0.132488E+11 | 0.00 | 0.253018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140756E+10 | 0.00 | 0.181631E+11 | 0.00 | 0.348178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165729E+11 | 0.00 | 0.156762E+12 | 0.00 | 0.322238E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127134E+10 | 0.00 | 0.581841E+09 | 0.00 | 0.133606E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140756E+10 | 0.00 | 0.269063E+11 | 0.00 | 0.606323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 84145007.85 | 0.00 | 0.00 | 0.556373E+11 | 0.00 | 0.41 |
February | 0.00 | 0.00 | 0.00 | 82138292.51 | 0.00 | 0.00 | 0.514583E+11 | 0.00 | 0.38 |
March | 0.00 | 0.00 | 0.00 | 0.111061E+09 | 0.00 | 0.00 | 0.649562E+11 | 0.00 | 0.61 |
April | 0.00 | 16755887.13 | 0.00 | 0.102970E+09 | 0.00 | 0.00 | 0.612324E+11 | 0.00 | 0.90 |
May | 0.00 | 0.705154E+09 | 0.00 | 0.108503E+09 | 0.00 | 0.00 | 0.476757E+11 | 0.00 | 1.08 |
June | 0.00 | 0.397809E+10 | 0.00 | 83276174.99 | 0.00 | 0.00 | 0.115210E+11 | 0.00 | 0.51 |
July | 0.00 | 0.351313E+10 | 0.00 | 56963811.29 | 0.00 | 0.00 | 0.222664E+10 | 0.00 | 0.08 |
August | 0.00 | 0.193732E+10 | 0.00 | 93153966.35 | 0.00 | 0.00 | 0.542229E+10 | 0.00 | 0.21 |
September | 0.00 | 0.176717E+10 | 0.00 | 0.130866E+09 | 0.00 | 0.00 | 0.259356E+11 | 0.00 | 0.80 |
October | 0.00 | 0.379512E+09 | 0.00 | 0.138380E+09 | 0.00 | 0.00 | 0.499296E+11 | 0.00 | 1.06 |
November | 0.00 | 0.00 | 0.00 | 0.116855E+09 | 0.00 | 0.00 | 0.734243E+11 | 0.00 | 0.82 |
December | 0.00 | 0.00 | 0.00 | 0.104629E+09 | 0.00 | 0.00 | 0.654272E+11 | 0.00 | 0.51 |
Annual Sum or Average | 0.00 | 0.122971E+11 | 0.00 | 0.121294E+10 | 0.00 | 0.00 | 0.514846E+12 | 0.00 | 0.61 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 56963811.29 | 0.00 | 0.00 | 0.222664E+10 | 0.00 | 0.08 |
Maximum of Months | 0.00 | 0.397809E+10 | 0.00 | 0.138380E+09 | 0.00 | 0.00 | 0.734243E+11 | 0.00 | 1.08 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.698144E+10 | 0.00 | 0.00 | 49877957.77 | 0.00 | 0.00 | 0.339781E+11 | 0.00 | 0.35 |
February | 0.338376E+10 | 0.00 | 0.00 | 59330650.10 | 0.00 | 0.00 | 0.379030E+11 | 0.00 | 0.37 |
March | 0.225091E+10 | 0.00 | 0.00 | 0.102480E+09 | 0.00 | 0.00 | 0.580050E+11 | 0.00 | 0.56 |
April | 0.474773E+10 | 17659446.10 | 0.00 | 97970834.25 | 0.00 | 0.00 | 0.548029E+11 | 0.00 | 0.82 |
May | 0.281331E+10 | 0.138959E+09 | 0.00 | 90903510.45 | 0.00 | 0.00 | 0.429525E+11 | 0.00 | 0.94 |
June | 0.152513E+10 | 0.509038E+10 | 0.00 | 48431838.30 | 99592103.07 | 0.00 | 0.100692E+11 | 0.00 | 0.66 |
July | 0.275523E+09 | 0.104450E+11 | 0.00 | 4739419.18 | 0.170894E+09 | 0.00 | 0.427864E+09 | 0.00 | 0.30 |
August | 0.242036E+10 | 0.722042E+10 | 0.00 | 44940809.20 | 0.143955E+09 | 0.00 | 0.560838E+10 | 0.00 | 0.66 |
September | 0.231665E+10 | 0.328274E+10 | 0.00 | 71535461.96 | 32643818.93 | 0.00 | 0.225100E+11 | 0.00 | 0.79 |
October | 0.353862E+10 | 0.448966E+09 | 0.00 | 0.101367E+09 | 0.00 | 0.00 | 0.422110E+11 | 0.00 | 0.85 |
November | 0.180403E+10 | 0.00 | 0.00 | 97841349.81 | 0.00 | 0.00 | 0.564902E+11 | 0.00 | 0.62 |
December | 0.242343E+10 | 0.00 | 0.00 | 93614381.42 | 0.00 | 0.00 | 0.527053E+11 | 0.00 | 0.44 |
Annual Sum or Average | 0.344809E+11 | 0.266441E+11 | 0.00 | 0.863033E+09 | 0.447085E+09 | 0.00 | 0.417663E+12 | 0.00 | 0.61 |
Minimum of Months | 0.275523E+09 | 0.00 | 0.00 | 4739419.18 | 0.00 | 0.00 | 0.427864E+09 | 0.00 | 0.30 |
Maximum of Months | 0.698144E+10 | 0.104450E+11 | 0.00 | 0.102480E+09 | 0.170894E+09 | 0.00 | 0.580050E+11 | 0.00 | 0.94 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.212889E+12 | 0.00 | 0.00 | 52076687.98 | 0.00 | 0.504048E+10 | 0.537928E+11 | 0.00 | 0.29 |
February | 0.192379E+12 | 0.00 | 0.00 | 81407160.28 | 0.00 | 0.132666E+09 | 0.780634E+11 | 0.00 | 0.30 |
March | 0.143047E+12 | 0.00 | 0.00 | 0.327969E+09 | 0.00 | 0.00 | 0.231411E+12 | 0.00 | 0.38 |
April | 0.894367E+11 | 54850873.97 | 0.00 | 0.422435E+09 | 0.00 | 0.00 | 0.279939E+12 | 0.00 | 0.53 |
May | 0.383059E+11 | 0.115693E+10 | 0.00 | 0.600314E+09 | 0.00 | 0.00 | 0.323596E+12 | 0.00 | 0.76 |
June | 0.907291E+10 | 0.448739E+11 | 0.00 | 0.326666E+09 | 0.988672E+09 | 0.00 | 0.758628E+11 | 0.00 | 0.53 |
July | 0.547764E+09 | 0.912184E+11 | 0.00 | 25775875.61 | 0.163341E+10 | 0.00 | 0.274837E+10 | 0.00 | 0.27 |
August | 0.461236E+10 | 0.605896E+11 | 0.00 | 0.300713E+09 | 0.129691E+10 | 0.00 | 0.397152E+11 | 0.00 | 0.47 |
September | 0.247784E+11 | 0.298626E+11 | 0.00 | 0.426961E+09 | 0.319976E+09 | 0.00 | 0.155745E+12 | 0.00 | 0.60 |
October | 0.507641E+11 | 0.429818E+10 | 0.00 | 0.542814E+09 | 0.00 | 0.00 | 0.269080E+12 | 0.00 | 0.62 |
November | 0.117929E+12 | 0.00 | 0.00 | 0.308207E+09 | 0.00 | 0.00 | 0.230664E+12 | 0.00 | 0.40 |
December | 0.179485E+12 | 0.00 | 0.00 | 0.145091E+09 | 0.00 | 0.00 | 0.127291E+12 | 0.00 | 0.30 |
Annual Sum or Average | 0.106325E+13 | 0.232054E+12 | 0.00 | 0.356043E+10 | 0.423897E+10 | 0.517315E+10 | 0.186791E+13 | 0.00 | 0.46 |
Minimum of Months | 0.547764E+09 | 0.00 | 0.00 | 25775875.61 | 0.00 | 0.00 | 0.274837E+10 | 0.00 | 0.27 |
Maximum of Months | 0.212889E+12 | 0.912184E+11 | 0.00 | 0.600314E+09 | 0.163341E+10 | 0.504048E+10 | 0.323596E+12 | 0.00 | 0.76 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.200796E+11 | 0.00 | 0.00 | 303305.58 | 0.00 | 0.172602E+10 | 0.532598E+09 | 0.00 | 0.28 |
February | 0.189111E+11 | 0.00 | 0.00 | 542559.55 | 0.00 | 0.112838E+10 | 0.981833E+09 | 0.00 | 0.28 |
March | 0.210953E+11 | 0.00 | 0.00 | 9235153.44 | 0.00 | 0.287111E+09 | 0.945085E+10 | 0.00 | 0.35 |
April | 0.133002E+11 | 499931.12 | 0.00 | 25448960.28 | 0.00 | 91281232.47 | 0.189462E+11 | 0.00 | 0.49 |
May | 0.864311E+10 | 0.102598E+09 | 0.00 | 47007650.27 | 0.00 | 0.00 | 0.260701E+11 | 0.00 | 0.74 |
June | 0.121018E+10 | 0.438016E+10 | 0.00 | 30411423.30 | 98894198.87 | 0.00 | 0.776869E+10 | 0.00 | 0.55 |
July | 0.130528E+09 | 0.928896E+10 | 0.00 | 3242582.26 | 0.168780E+09 | 0.00 | 0.280506E+09 | 0.00 | 0.28 |
August | 0.486350E+09 | 0.606046E+10 | 0.00 | 28622608.79 | 0.149175E+09 | 0.00 | 0.396113E+10 | 0.00 | 0.50 |
September | 0.468447E+10 | 0.299219E+10 | 0.00 | 31857342.99 | 27789161.77 | 0.00 | 0.121447E+11 | 0.00 | 0.59 |
October | 0.108223E+11 | 0.300651E+09 | 0.00 | 31326859.53 | 0.00 | 0.00 | 0.160555E+11 | 0.00 | 0.57 |
November | 0.184980E+11 | 0.00 | 0.00 | 7301415.98 | 0.00 | 0.446791E+09 | 0.778263E+10 | 0.00 | 0.35 |
December | 0.216369E+11 | 0.00 | 0.00 | 315460.92 | 0.00 | 0.732418E+09 | 0.107012E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.139498E+12 | 0.231255E+11 | 0.00 | 0.215615E+09 | 0.444638E+09 | 0.441200E+10 | 0.105045E+12 | 0.00 | 0.44 |
Minimum of Months | 0.130528E+09 | 0.00 | 0.00 | 303305.58 | 0.00 | 0.00 | 0.280506E+09 | 0.00 | 0.28 |
Maximum of Months | 0.216369E+11 | 0.928896E+10 | 0.00 | 47007650.27 | 0.168780E+09 | 0.172602E+10 | 0.260701E+11 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.359298E+10 | 0.00 | 0.00 | 797.75 | 0.00 | 0.408138E+09 | 9367962.53 | 0.00 | 0.28 |
February | 0.342960E+10 | 0.00 | 0.00 | 30399.30 | 0.00 | 0.262395E+09 | 76730838.53 | 0.00 | 0.27 |
March | 0.303750E+10 | 0.00 | 0.00 | 2715724.46 | 0.00 | 0.00 | 0.216497E+10 | 0.00 | 0.40 |
April | 0.202717E+10 | 2764747.26 | 0.00 | 5945331.31 | 0.00 | 0.00 | 0.397673E+10 | 0.00 | 0.71 |
May | 0.832150E+09 | 25459600.36 | 0.00 | 9682903.79 | 0.00 | 0.00 | 0.487755E+10 | 0.00 | 1.00 |
June | 0.231567E+09 | 0.877289E+09 | 0.00 | 6350706.12 | 12487911.66 | 0.00 | 0.142173E+10 | 0.00 | 0.83 |
July | 34016563.49 | 0.179729E+10 | 0.00 | 1127100.60 | 20806265.84 | 0.00 | 65496055.15 | 0.00 | 0.41 |
August | 0.337739E+09 | 0.122886E+10 | 0.00 | 5870567.59 | 18050595.42 | 0.00 | 0.698501E+09 | 0.00 | 0.79 |
September | 0.552139E+09 | 0.475583E+09 | 0.00 | 6914423.92 | 4093227.42 | 0.00 | 0.230018E+10 | 0.00 | 0.80 |
October | 0.143981E+10 | 64200195.70 | 0.00 | 6458572.16 | 0.00 | 0.00 | 0.308085E+10 | 0.00 | 0.72 |
November | 0.252986E+10 | 0.00 | 0.00 | 2652042.08 | 0.00 | 0.00 | 0.225746E+10 | 0.00 | 0.42 |
December | 0.385766E+10 | 0.00 | 0.00 | 410102.34 | 0.00 | 0.00 | 0.506393E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.219022E+11 | 0.447145E+10 | 0.00 | 48158671.42 | 55438000.34 | 0.670533E+09 | 0.214360E+11 | 0.00 | 0.58 |
Minimum of Months | 34016563.49 | 0.00 | 0.00 | 797.75 | 0.00 | 0.00 | 9367962.53 | 0.00 | 0.27 |
Maximum of Months | 0.385766E+10 | 0.179729E+10 | 0.00 | 9682903.79 | 20806265.84 | 0.408138E+09 | 0.487755E+10 | 0.00 | 1.00 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.340159E+10 | 0.00 | 0.00 | 509166.32 | 0.00 | 0.422036E+09 | 0.289029E+09 | 0.00 | 0.44 |
February | 0.318273E+10 | 0.00 | 0.00 | 773545.65 | 0.00 | 0.241914E+09 | 0.492125E+09 | 0.00 | 0.44 |
March | 0.300327E+10 | 0.00 | 0.00 | 4615831.49 | 0.00 | 12016286.92 | 0.284233E+10 | 0.00 | 0.67 |
April | 0.242796E+10 | 2001304.36 | 0.00 | 6696985.51 | 0.00 | 0.00 | 0.389833E+10 | 0.00 | 1.13 |
May | 0.105877E+10 | 23399662.99 | 0.00 | 11682771.53 | 0.00 | 0.00 | 0.492776E+10 | 0.00 | 1.56 |
June | 0.222181E+09 | 0.652072E+09 | 0.00 | 6125343.77 | 13247443.59 | 0.00 | 0.150071E+10 | 0.00 | 1.13 |
July | 39354854.15 | 0.135686E+10 | 0.00 | 875043.97 | 21710671.37 | 0.00 | 69146906.65 | 0.00 | 0.52 |
August | 0.347286E+09 | 0.994703E+09 | 0.00 | 5474270.29 | 18288312.39 | 0.00 | 0.759990E+09 | 0.00 | 1.12 |
September | 0.612367E+09 | 0.369206E+09 | 0.00 | 9635427.35 | 4147133.10 | 0.00 | 0.242187E+10 | 0.00 | 1.20 |
October | 0.161169E+10 | 51109480.57 | 0.00 | 6849627.99 | 0.00 | 0.00 | 0.324050E+10 | 0.00 | 1.13 |
November | 0.281492E+10 | 0.00 | 0.00 | 2522564.20 | 0.00 | 11855658.48 | 0.191733E+10 | 0.00 | 0.62 |
December | 0.383419E+10 | 0.00 | 0.00 | 791669.17 | 0.00 | 23763184.73 | 0.624268E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.225563E+11 | 0.344935E+10 | 0.00 | 56552247.24 | 57393560.45 | 0.711586E+09 | 0.229834E+11 | 0.00 | 0.87 |
Minimum of Months | 39354854.15 | 0.00 | 0.00 | 509166.32 | 0.00 | 0.00 | 69146906.65 | 0.00 | 0.44 |
Maximum of Months | 0.383419E+10 | 0.135686E+10 | 0.00 | 11682771.53 | 21710671.37 | 0.422036E+09 | 0.492776E+10 | 0.00 | 1.56 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.288750E+10 | 0.00 | 0.00 | 5255775.05 | 0.00 | 0.519486E+09 | 0.343823E+10 | 0.00 | 0.45 |
February | 0.243892E+10 | 0.00 | 0.00 | 7115353.04 | 0.00 | 0.284720E+09 | 0.445407E+10 | 0.00 | 0.50 |
March | 0.287641E+10 | 0.00 | 0.00 | 11705623.31 | 0.00 | 23905102.28 | 0.773066E+10 | 0.00 | 0.83 |
April | 0.247598E+10 | 4958434.46 | 0.00 | 10492300.10 | 0.00 | 0.00 | 0.635744E+10 | 0.00 | 1.10 |
May | 0.137143E+10 | 31695472.21 | 0.00 | 11760515.75 | 0.00 | 0.00 | 0.551830E+10 | 0.00 | 1.23 |
June | 0.296131E+09 | 0.959658E+09 | 0.00 | 6602563.53 | 14701194.73 | 0.00 | 0.147092E+10 | 0.00 | 0.91 |
July | 44909206.41 | 0.194802E+10 | 0.00 | 1248550.05 | 25226323.84 | 0.00 | 57217649.82 | 0.00 | 0.45 |
August | 0.393783E+09 | 0.154876E+10 | 0.00 | 8031041.25 | 20291026.23 | 0.00 | 0.835214E+09 | 0.00 | 1.03 |
September | 0.605045E+09 | 0.635998E+09 | 0.00 | 18853114.53 | 4818686.66 | 0.00 | 0.406629E+10 | 0.00 | 1.34 |
October | 0.102397E+10 | 0.163978E+09 | 0.00 | 21808964.17 | 0.00 | 0.00 | 0.874860E+10 | 0.00 | 1.55 |
November | 0.229752E+10 | 0.00 | 0.00 | 10009101.70 | 0.00 | 21935501.97 | 0.689672E+10 | 0.00 | 0.83 |
December | 0.314311E+10 | 0.00 | 0.00 | 8819344.77 | 0.00 | 36027142.31 | 0.504294E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.198547E+11 | 0.529306E+10 | 0.00 | 0.121702E+09 | 65037231.46 | 0.886074E+09 | 0.546166E+11 | 0.00 | 0.90 |
Minimum of Months | 44909206.41 | 0.00 | 0.00 | 1248550.05 | 0.00 | 0.00 | 57217649.82 | 0.00 | 0.45 |
Maximum of Months | 0.314311E+10 | 0.194802E+10 | 0.00 | 21808964.17 | 25226323.84 | 0.519486E+09 | 0.874860E+10 | 0.00 | 1.55 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.426505E+10 | 0.00 | 0.00 | 932899.76 | 0.00 | 54936739.08 | 0.821575E+09 | 0.00 | 0.55 |
February | 0.325839E+10 | 0.00 | 0.00 | 2208259.85 | 0.00 | 42037089.69 | 0.189232E+10 | 0.00 | 0.57 |
March | 0.138589E+10 | 0.00 | 0.00 | 10332586.80 | 0.00 | 0.00 | 0.727687E+10 | 0.00 | 1.05 |
April | 0.695005E+09 | 5556189.61 | 0.00 | 17240816.57 | 0.00 | 0.00 | 0.903835E+10 | 0.00 | 1.81 |
May | 0.621822E+09 | 29715487.73 | 0.00 | 13685050.25 | 0.00 | 0.00 | 0.630314E+10 | 0.00 | 1.87 |
June | 0.206934E+09 | 0.929198E+09 | 0.00 | 8491935.55 | 11342573.79 | 0.00 | 0.170720E+10 | 0.00 | 1.47 |
July | 36348765.09 | 0.178548E+10 | 0.00 | 1984971.00 | 12982078.23 | 0.00 | 62470909.08 | 0.00 | 0.65 |
August | 0.316907E+09 | 0.137463E+10 | 0.00 | 8011274.92 | 9516629.06 | 0.00 | 0.906729E+09 | 0.00 | 1.47 |
September | 0.494000E+09 | 0.475075E+09 | 0.00 | 9842796.88 | 3647852.54 | 0.00 | 0.282580E+10 | 0.00 | 1.43 |
October | 0.766018E+09 | 98139933.44 | 0.00 | 12521426.79 | 0.00 | 0.00 | 0.563217E+10 | 0.00 | 1.59 |
November | 0.154514E+10 | 0.00 | 0.00 | 6668319.18 | 0.00 | 0.00 | 0.513397E+10 | 0.00 | 0.92 |
December | 0.205737E+10 | 0.00 | 0.00 | 5067531.03 | 0.00 | 0.00 | 0.420398E+10 | 0.00 | 0.63 |
Annual Sum or Average | 0.156489E+11 | 0.469780E+10 | 0.00 | 96987868.59 | 37489133.61 | 96973828.77 | 0.458046E+11 | 0.00 | 1.17 |
Minimum of Months | 36348765.09 | 0.00 | 0.00 | 932899.76 | 0.00 | 0.00 | 62470909.08 | 0.00 | 0.55 |
Maximum of Months | 0.426505E+10 | 0.178548E+10 | 0.00 | 17240816.57 | 12982078.23 | 54936739.08 | 0.903835E+10 | 0.00 | 1.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.124699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223925E+11 | 0.00 | 0.00 | 0.29 |
February | 0.135082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208048E+11 | 0.00 | 0.00 | 0.30 |
March | 0.337264E+11 | 0.00 | 0.00 | 1472124.45 | 0.00 | 0.707689E+10 | 0.135137E+10 | 0.00 | 0.34 |
April | 0.271817E+11 | 8472587.97 | 0.00 | 18135375.23 | 0.00 | 0.128187E+10 | 0.114935E+11 | 0.00 | 0.47 |
May | 0.138750E+11 | 0.236180E+09 | 0.00 | 63033515.31 | 0.00 | 0.00 | 0.301688E+11 | 0.00 | 0.80 |
June | 0.164558E+10 | 0.859272E+10 | 0.00 | 43723278.43 | 0.127980E+09 | 0.00 | 0.107790E+11 | 0.00 | 0.72 |
July | 66295848.82 | 0.182453E+11 | 0.00 | 4886853.06 | 0.205340E+09 | 0.00 | 0.458111E+09 | 0.00 | 0.43 |
August | 0.952400E+09 | 0.122250E+11 | 0.00 | 37554967.07 | 0.175407E+09 | 0.00 | 0.488446E+10 | 0.00 | 0.64 |
September | 0.928441E+10 | 0.442670E+10 | 0.00 | 35983106.71 | 49627098.13 | 0.00 | 0.118996E+11 | 0.00 | 0.62 |
October | 0.222879E+11 | 0.590229E+09 | 0.00 | 22598538.99 | 0.00 | 0.159144E+09 | 0.105812E+11 | 0.00 | 0.53 |
November | 0.293759E+11 | 0.00 | 0.00 | 1102495.98 | 0.00 | 0.685037E+10 | 0.161650E+10 | 0.00 | 0.34 |
December | 0.192010E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182296E+11 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.183575E+12 | 0.443246E+11 | 0.00 | 0.228490E+09 | 0.558355E+09 | 0.767952E+11 | 0.832326E+11 | 0.00 | 0.48 |
Minimum of Months | 66295848.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.337264E+11 | 0.182453E+11 | 0.00 | 63033515.31 | 0.205340E+09 | 0.223925E+11 | 0.301688E+11 | 0.00 | 0.80 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.186549E+11 | 0.00 | 0.00 | 31941.79 | 0.00 | 0.185308E+11 | 0.126375E+09 | 0.00 | 0.49 |
February | 0.208041E+11 | 0.00 | 0.00 | 1016880.29 | 0.00 | 0.153556E+11 | 0.654145E+09 | 0.00 | 0.49 |
March | 0.308793E+11 | 0.00 | 0.00 | 21556692.99 | 0.00 | 0.510154E+10 | 0.139614E+11 | 0.00 | 0.63 |
April | 0.241525E+11 | 8726590.92 | 0.00 | 47769437.70 | 0.00 | 0.111168E+10 | 0.272056E+11 | 0.00 | 0.97 |
May | 0.168665E+11 | 0.232430E+09 | 0.00 | 99640266.05 | 0.00 | 0.00 | 0.391542E+11 | 0.00 | 1.48 |
June | 0.194215E+10 | 0.697531E+10 | 0.00 | 55401985.45 | 0.320251E+09 | 0.00 | 0.139074E+11 | 0.00 | 1.13 |
July | 77162205.31 | 0.158321E+11 | 0.00 | 6590947.39 | 0.312084E+09 | 0.00 | 0.688064E+09 | 0.00 | 0.62 |
August | 0.919299E+09 | 0.118156E+11 | 0.00 | 51485921.61 | 0.178171E+09 | 0.00 | 0.749045E+10 | 0.00 | 1.12 |
September | 0.925225E+10 | 0.364638E+10 | 0.00 | 60392224.69 | 0.420433E+09 | 0.00 | 0.175334E+11 | 0.00 | 1.09 |
October | 0.191015E+11 | 0.547603E+09 | 0.00 | 44919921.28 | 912810.28 | 22610584.84 | 0.221866E+11 | 0.00 | 1.02 |
November | 0.305891E+11 | 0.00 | 0.00 | 6047942.58 | 0.00 | 0.590108E+10 | 0.544502E+10 | 0.00 | 0.59 |
December | 0.247948E+11 | 0.00 | 0.00 | 147452.15 | 0.00 | 0.158272E+11 | 0.165405E+09 | 0.00 | 0.49 |
Annual Sum or Average | 0.198034E+12 | 0.390582E+11 | 0.00 | 0.395002E+09 | 0.123185E+10 | 0.618505E+11 | 0.148518E+12 | 0.00 | 0.84 |
Minimum of Months | 77162205.31 | 0.00 | 0.00 | 31941.79 | 0.00 | 0.00 | 0.126375E+09 | 0.00 | 0.49 |
Maximum of Months | 0.308793E+11 | 0.158321E+11 | 0.00 | 99640266.05 | 0.420433E+09 | 0.185308E+11 | 0.391542E+11 | 0.00 | 1.48 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.179209E+11 | 0.00 | 0.00 | 42266270.07 | 0.00 | 0.129548E+11 | 0.249262E+11 | 0.00 | 0.45 |
February | 0.170093E+11 | 0.00 | 0.00 | 60305861.44 | 0.00 | 0.997856E+10 | 0.346812E+11 | 0.00 | 0.51 |
March | 0.255152E+11 | 0.00 | 0.00 | 96554586.06 | 0.00 | 0.402698E+10 | 0.613655E+11 | 0.00 | 0.76 |
April | 0.238899E+11 | 23636884.41 | 0.00 | 78599384.43 | 0.00 | 0.120876E+10 | 0.453998E+11 | 0.00 | 0.90 |
May | 0.164759E+11 | 0.321666E+09 | 0.00 | 96051001.81 | 0.00 | 0.00 | 0.438939E+11 | 0.00 | 1.11 |
June | 0.302844E+10 | 0.995705E+10 | 0.00 | 48523955.55 | 0.161585E+09 | 0.00 | 0.116393E+11 | 0.00 | 0.85 |
July | 78534962.45 | 0.212578E+11 | 0.00 | 7363667.80 | 0.255938E+09 | 0.00 | 0.438651E+09 | 0.00 | 0.51 |
August | 0.106431E+10 | 0.175698E+11 | 0.00 | 67518470.04 | 0.191489E+09 | 0.00 | 0.709996E+10 | 0.00 | 0.99 |
September | 0.740267E+10 | 0.694772E+10 | 0.00 | 0.147756E+09 | 70467679.39 | 0.00 | 0.340155E+11 | 0.00 | 1.24 |
October | 0.108755E+11 | 0.195327E+10 | 0.00 | 0.201061E+09 | 0.00 | 0.00 | 0.776177E+11 | 0.00 | 1.47 |
November | 0.217461E+11 | 0.00 | 0.00 | 77592678.89 | 0.00 | 0.294130E+10 | 0.519606E+11 | 0.00 | 0.74 |
December | 0.199775E+11 | 0.00 | 0.00 | 62275699.18 | 0.00 | 0.104624E+11 | 0.337994E+11 | 0.00 | 0.48 |
Annual Sum or Average | 0.164984E+12 | 0.580309E+11 | 0.00 | 0.985868E+09 | 0.679480E+09 | 0.415727E+11 | 0.426838E+12 | 0.00 | 0.84 |
Minimum of Months | 78534962.45 | 0.00 | 0.00 | 7363667.80 | 0.00 | 0.00 | 0.438651E+09 | 0.00 | 0.45 |
Maximum of Months | 0.255152E+11 | 0.212578E+11 | 0.00 | 0.201061E+09 | 0.255938E+09 | 0.129548E+11 | 0.776177E+11 | 0.00 | 1.47 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.209356E+11 | 0.00 | 0.00 | 1703277.79 | 0.00 | 0.164889E+11 | 0.142795E+10 | 0.00 | 0.51 |
February | 0.215858E+11 | 0.00 | 0.00 | 4399046.43 | 0.00 | 0.141340E+11 | 0.345562E+10 | 0.00 | 0.52 |
March | 0.339660E+11 | 0.00 | 0.00 | 25700027.98 | 0.00 | 0.386326E+10 | 0.181856E+11 | 0.00 | 0.72 |
April | 0.264580E+11 | 12308345.95 | 0.00 | 53840195.89 | 0.00 | 0.761657E+09 | 0.284302E+11 | 0.00 | 1.06 |
May | 0.152885E+11 | 0.299739E+09 | 0.00 | 86282683.74 | 0.00 | 0.00 | 0.381333E+11 | 0.00 | 1.49 |
June | 0.248389E+10 | 0.911934E+10 | 0.00 | 48403032.52 | 0.133748E+09 | 0.00 | 0.107464E+11 | 0.00 | 1.20 |
July | 73411502.74 | 0.180139E+11 | 0.00 | 9460945.48 | 0.178931E+09 | 0.00 | 0.340220E+09 | 0.00 | 0.66 |
August | 0.975538E+09 | 0.141088E+11 | 0.00 | 42539863.67 | 0.142257E+09 | 0.00 | 0.496916E+10 | 0.00 | 1.16 |
September | 0.100540E+11 | 0.482026E+10 | 0.00 | 56435750.86 | 0.121082E+09 | 0.00 | 0.151148E+11 | 0.00 | 1.14 |
October | 0.215502E+11 | 0.937150E+09 | 0.00 | 45446159.00 | 0.00 | 4896306.67 | 0.219647E+11 | 0.00 | 1.11 |
November | 0.339797E+11 | 0.00 | 0.00 | 6222574.53 | 0.00 | 0.465234E+10 | 0.545052E+10 | 0.00 | 0.63 |
December | 0.289308E+11 | 0.00 | 0.00 | 1381944.85 | 0.00 | 0.121337E+11 | 0.133465E+10 | 0.00 | 0.51 |
Annual Sum or Average | 0.216281E+12 | 0.473116E+11 | 0.00 | 0.381816E+09 | 0.576019E+09 | 0.520387E+11 | 0.149553E+12 | 0.00 | 0.89 |
Minimum of Months | 73411502.74 | 0.00 | 0.00 | 1381944.85 | 0.00 | 0.00 | 0.340220E+09 | 0.00 | 0.51 |
Maximum of Months | 0.339797E+11 | 0.180139E+11 | 0.00 | 86282683.74 | 0.178931E+09 | 0.164889E+11 | 0.381333E+11 | 0.00 | 1.49 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.646128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232423E+10 | 0.00 | 0.00 | 0.30 |
February | 0.636418E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216771E+10 | 0.00 | 0.00 | 0.30 |
March | 0.241788E+10 | 0.00 | 0.00 | 92847.02 | 0.00 | 0.127028E+10 | 0.110759E+09 | 0.00 | 0.34 |
April | 0.240672E+10 | 73630.84 | 0.00 | 1641291.83 | 0.00 | 0.452100E+09 | 0.965338E+09 | 0.00 | 0.47 |
May | 0.161221E+10 | 20030988.89 | 0.00 | 5615857.00 | 0.00 | 22671739.26 | 0.277250E+10 | 0.00 | 0.79 |
June | 0.224205E+09 | 0.810154E+09 | 0.00 | 4446134.42 | 14094501.44 | 0.00 | 0.111847E+10 | 0.00 | 0.73 |
July | 10998260.79 | 0.179583E+10 | 0.00 | 806747.70 | 21803310.54 | 0.00 | 53577027.82 | 0.00 | 0.43 |
August | 0.119983E+09 | 0.118123E+10 | 0.00 | 4050771.18 | 21096133.80 | 0.00 | 0.507024E+09 | 0.00 | 0.68 |
September | 0.932050E+09 | 0.427715E+09 | 0.00 | 3236157.87 | 14741431.59 | 0.00 | 0.112016E+10 | 0.00 | 0.62 |
October | 0.213019E+10 | 40576256.20 | 0.00 | 1740613.99 | 106925.50 | 0.122528E+09 | 0.781707E+09 | 0.00 | 0.52 |
November | 0.208469E+10 | 0.00 | 0.00 | 18037.47 | 0.00 | 0.119367E+10 | 28487731.16 | 0.00 | 0.34 |
December | 0.809330E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222973E+10 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.140308E+11 | 0.427561E+10 | 0.00 | 21648458.48 | 71842302.87 | 0.978292E+10 | 0.745802E+10 | 0.00 | 0.49 |
Minimum of Months | 10998260.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.241788E+10 | 0.179583E+10 | 0.00 | 5615857.00 | 21803310.54 | 0.232423E+10 | 0.277250E+10 | 0.00 | 0.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.118992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189055E+10 | 0.00 | 0.00 | 0.47 |
February | 0.136502E+10 | 0.00 | 0.00 | 378.12 | 0.00 | 0.152836E+10 | 4608311.18 | 0.00 | 0.47 |
March | 0.250302E+10 | 0.00 | 0.00 | 1377452.93 | 0.00 | 0.824086E+09 | 0.944960E+09 | 0.00 | 0.60 |
April | 0.201044E+10 | 75659.82 | 0.00 | 3968766.68 | 0.00 | 0.407639E+09 | 0.245040E+10 | 0.00 | 0.94 |
May | 0.172996E+10 | 19673118.08 | 0.00 | 10285582.90 | 0.00 | 11223314.53 | 0.385718E+10 | 0.00 | 1.49 |
June | 0.186120E+09 | 0.664765E+09 | 0.00 | 5754471.12 | 40731773.75 | 0.00 | 0.148462E+10 | 0.00 | 1.17 |
July | 13391681.27 | 0.155996E+10 | 0.00 | 911746.96 | 39576780.61 | 0.00 | 79154120.36 | 0.00 | 0.64 |
August | 98092691.66 | 0.115730E+10 | 0.00 | 5832879.91 | 18932705.40 | 0.00 | 0.784064E+09 | 0.00 | 1.19 |
September | 0.850911E+09 | 0.365818E+09 | 0.00 | 6247921.57 | 49241303.30 | 0.00 | 0.172887E+10 | 0.00 | 1.11 |
October | 0.175990E+10 | 38567083.97 | 0.00 | 3808052.42 | 281124.72 | 95352737.90 | 0.181420E+10 | 0.00 | 0.99 |
November | 0.246937E+10 | 0.00 | 0.00 | 202616.21 | 0.00 | 0.880685E+09 | 0.218026E+09 | 0.00 | 0.57 |
December | 0.143535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178579E+10 | 0.00 | 0.00 | 0.48 |
Annual Sum or Average | 0.156115E+11 | 0.380616E+10 | 0.00 | 38389868.82 | 0.148764E+09 | 0.742368E+10 | 0.133661E+11 | 0.00 | 0.85 |
Minimum of Months | 13391681.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.250302E+10 | 0.155996E+10 | 0.00 | 10285582.90 | 49241303.30 | 0.189055E+10 | 0.385718E+10 | 0.00 | 1.49 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.127225E+10 | 0.00 | 0.00 | 2987884.04 | 0.00 | 0.148605E+10 | 0.184614E+10 | 0.00 | 0.43 |
February | 0.127841E+10 | 0.00 | 0.00 | 3952850.91 | 0.00 | 0.111298E+10 | 0.244855E+10 | 0.00 | 0.47 |
March | 0.209587E+10 | 0.00 | 0.00 | 7889230.67 | 0.00 | 0.691270E+09 | 0.547933E+10 | 0.00 | 0.73 |
April | 0.219326E+10 | 215956.02 | 0.00 | 7068822.05 | 0.00 | 0.442944E+09 | 0.434774E+10 | 0.00 | 0.90 |
May | 0.201108E+10 | 26072959.21 | 0.00 | 9683408.12 | 0.00 | 29652867.96 | 0.430792E+10 | 0.00 | 1.13 |
June | 0.344773E+09 | 0.918677E+09 | 0.00 | 5370507.93 | 27303231.97 | 0.00 | 0.131207E+10 | 0.00 | 0.88 |
July | 13143680.86 | 0.206713E+10 | 0.00 | 1234915.09 | 32044742.41 | 0.00 | 58857393.32 | 0.00 | 0.51 |
August | 0.130610E+09 | 0.166225E+10 | 0.00 | 7678954.43 | 24038315.30 | 0.00 | 0.815416E+09 | 0.00 | 1.06 |
September | 0.816753E+09 | 0.667447E+09 | 0.00 | 15981384.37 | 18882368.76 | 0.00 | 0.351102E+10 | 0.00 | 1.27 |
October | 0.113555E+10 | 0.133444E+09 | 0.00 | 18072516.78 | 0.00 | 88388290.22 | 0.719111E+10 | 0.00 | 1.45 |
November | 0.181112E+10 | 0.00 | 0.00 | 5464120.04 | 0.00 | 0.672389E+09 | 0.382277E+10 | 0.00 | 0.67 |
December | 0.146374E+10 | 0.00 | 0.00 | 3569069.20 | 0.00 | 0.133896E+10 | 0.200735E+10 | 0.00 | 0.44 |
Annual Sum or Average | 0.145666E+11 | 0.547525E+10 | 0.00 | 88953663.63 | 0.102269E+09 | 0.586264E+10 | 0.371483E+11 | 0.00 | 0.83 |
Minimum of Months | 13143680.86 | 0.00 | 0.00 | 1234915.09 | 0.00 | 0.00 | 58857393.32 | 0.00 | 0.43 |
Maximum of Months | 0.219326E+10 | 0.206713E+10 | 0.00 | 18072516.78 | 32044742.41 | 0.148605E+10 | 0.719111E+10 | 0.00 | 1.45 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.136254E+10 | 0.00 | 0.00 | 111861.25 | 0.00 | 0.185368E+10 | 0.105408E+09 | 0.00 | 0.51 |
February | 0.140797E+10 | 0.00 | 0.00 | 323483.73 | 0.00 | 0.151047E+10 | 0.276629E+09 | 0.00 | 0.52 |
March | 0.283096E+10 | 0.00 | 0.00 | 2246046.35 | 0.00 | 0.622474E+09 | 0.172801E+10 | 0.00 | 0.73 |
April | 0.253548E+10 | 74035.45 | 0.00 | 5095960.80 | 0.00 | 0.270077E+09 | 0.272500E+10 | 0.00 | 1.08 |
May | 0.190129E+10 | 25108213.73 | 0.00 | 8895675.46 | 0.00 | 8380874.30 | 0.373103E+10 | 0.00 | 1.54 |
June | 0.271088E+09 | 0.833165E+09 | 0.00 | 5634614.60 | 18358876.85 | 0.00 | 0.120183E+10 | 0.00 | 1.23 |
July | 10518425.16 | 0.173905E+10 | 0.00 | 1734415.43 | 24563059.13 | 0.00 | 51817035.65 | 0.00 | 0.66 |
August | 0.130365E+09 | 0.133127E+10 | 0.00 | 4654545.84 | 16634955.83 | 0.00 | 0.521080E+09 | 0.00 | 1.22 |
September | 0.104473E+10 | 0.462450E+09 | 0.00 | 6100894.75 | 23912276.19 | 0.00 | 0.153724E+10 | 0.00 | 1.17 |
October | 0.211870E+10 | 64937612.61 | 0.00 | 4128747.16 | 0.00 | 94917720.31 | 0.199380E+10 | 0.00 | 1.13 |
November | 0.268344E+10 | 0.00 | 0.00 | 425957.83 | 0.00 | 0.860854E+09 | 0.385342E+09 | 0.00 | 0.63 |
December | 0.176465E+10 | 0.00 | 0.00 | 42457.88 | 0.00 | 0.163635E+10 | 75983317.95 | 0.00 | 0.52 |
Annual Sum or Average | 0.180617E+11 | 0.445606E+10 | 0.00 | 39394661.08 | 83469168.01 | 0.685720E+10 | 0.143332E+11 | 0.00 | 0.91 |
Minimum of Months | 10518425.16 | 0.00 | 0.00 | 42457.88 | 0.00 | 0.00 | 51817035.65 | 0.00 | 0.51 |
Maximum of Months | 0.283096E+10 | 0.173905E+10 | 0.00 | 8895675.46 | 24563059.13 | 0.185368E+10 | 0.373103E+10 | 0.00 | 1.54 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 2945967.51 | 0.00 | 0.00 | 0.697500E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7458389.29 | 0.00 | 0.00 | 0.659397E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 15216826.45 | 0.00 | 0.00 | 0.623552E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 17435283.99 | 0.00 | 0.00 | 0.422533E+09 | 0.00 | 0.29 |
May | 0.00 | 4685071.51 | 0.00 | 3983856.49 | 0.00 | 0.00 | 0.255054E+09 | 0.00 | 0.29 |
June | 0.00 | 0.149889E+09 | 0.00 | 2878603.33 | 0.00 | 0.00 | 43034398.09 | 0.00 | 0.31 |
July | 0.00 | 0.362651E+09 | 0.00 | 399756.74 | 0.00 | 0.00 | 777699.28 | 0.00 | 0.28 |
August | 0.00 | 0.287321E+09 | 0.00 | 4892713.32 | 0.00 | 0.00 | 19557219.64 | 0.00 | 0.31 |
September | 0.00 | 77269771.16 | 0.00 | 2584678.33 | 0.00 | 0.00 | 0.113639E+09 | 0.00 | 0.29 |
October | 0.00 | 12872560.58 | 0.00 | 7461271.53 | 0.00 | 0.00 | 0.236658E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 12941112.00 | 0.00 | 0.00 | 0.511759E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 17851797.96 | 0.00 | 0.00 | 0.638123E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.894688E+09 | 0.00 | 96050256.93 | 0.00 | 0.00 | 0.422158E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 399756.74 | 0.00 | 0.00 | 777699.28 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.362651E+09 | 0.00 | 17851797.96 | 0.00 | 0.00 | 0.697500E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.137922E+10 | 0.00 | 0.00 | 11682176.43 | 0.00 | 0.00 | 0.557433E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 56703232.90 | 0.00 | 0.00 | 0.661318E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.132532E+09 | 0.00 | 0.00 | 0.625381E+10 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 0.159464E+09 | 0.00 | 0.00 | 0.423619E+10 | 0.00 | 0.29 |
May | 0.00 | 44930102.53 | 0.00 | 34568782.88 | 0.00 | 0.00 | 0.256981E+10 | 0.00 | 0.29 |
June | 0.00 | 0.148750E+10 | 0.00 | 26989261.81 | 0.00 | 0.00 | 0.431739E+09 | 0.00 | 0.31 |
July | 0.00 | 0.361685E+10 | 0.00 | 3823687.26 | 0.00 | 0.00 | 7887920.22 | 0.00 | 0.28 |
August | 0.00 | 0.287811E+10 | 0.00 | 46548357.67 | 0.00 | 0.00 | 0.196552E+09 | 0.00 | 0.31 |
September | 0.00 | 0.754766E+09 | 0.00 | 22106393.00 | 0.00 | 0.00 | 0.114798E+10 | 0.00 | 0.29 |
October | 0.00 | 0.125139E+09 | 0.00 | 66331829.36 | 0.00 | 0.00 | 0.237706E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.111019E+09 | 0.00 | 0.00 | 0.513471E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.153958E+09 | 0.00 | 0.00 | 0.640542E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.137922E+10 | 0.890729E+10 | 0.00 | 0.825728E+09 | 0.00 | 0.00 | 0.409487E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3823687.26 | 0.00 | 0.00 | 7887920.22 | 0.00 | 0.28 |
Maximum of Months | 0.137922E+10 | 0.361685E+10 | 0.00 | 0.159464E+09 | 0.00 | 0.00 | 0.661318E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.334298E+09 | 0.00 | 0.00 | 596196.33 | 0.00 | 0.00 | 0.352783E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 4675264.80 | 0.00 | 0.00 | 0.662226E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 12282232.03 | 0.00 | 0.00 | 0.626524E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 15404215.09 | 0.00 | 0.00 | 0.424358E+09 | 0.00 | 0.29 |
May | 885985.45 | 4516539.44 | 0.00 | 3233134.25 | 0.00 | 0.00 | 0.257381E+09 | 0.00 | 0.29 |
June | 0.00 | 0.148743E+09 | 0.00 | 2698352.62 | 0.00 | 0.00 | 43223706.75 | 0.00 | 0.31 |
July | 0.00 | 0.361636E+09 | 0.00 | 382682.28 | 0.00 | 0.00 | 791977.77 | 0.00 | 0.28 |
August | 0.00 | 0.287862E+09 | 0.00 | 4664038.50 | 0.00 | 0.00 | 19699225.94 | 0.00 | 0.31 |
September | 0.00 | 75503319.67 | 0.00 | 2054202.96 | 0.00 | 0.00 | 0.115426E+09 | 0.00 | 0.29 |
October | 0.00 | 12393688.36 | 0.00 | 6122174.62 | 0.00 | 0.00 | 0.238752E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 10095169.78 | 0.00 | 0.00 | 0.514716E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 14216225.41 | 0.00 | 0.00 | 0.641737E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.335184E+09 | 0.890654E+09 | 0.00 | 76423888.67 | 0.00 | 0.00 | 0.389762E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 382682.28 | 0.00 | 0.00 | 791977.77 | 0.00 | 0.28 |
Maximum of Months | 0.334298E+09 | 0.361636E+09 | 0.00 | 15404215.09 | 0.00 | 0.00 | 0.662226E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.594970E+09 | 0.00 | 0.00 | 0.458053E+12 | 0.00 | 8.27 |
February | 0.00 | 0.00 | 0.00 | 0.111006E+10 | 0.00 | 0.00 | 0.732636E+12 | 0.00 | 13.38 |
March | 0.00 | 0.00 | 0.00 | 0.159748E+10 | 0.00 | 0.00 | 0.101962E+13 | 0.00 | 24.21 |
April | 0.00 | 0.00 | 0.00 | 0.227025E+10 | 0.00 | 0.00 | 0.108175E+13 | 0.00 | 38.89 |
May | 0.00 | 93487328.25 | 0.00 | 0.539013E+09 | 0.00 | 0.00 | 0.377021E+12 | 0.00 | 19.67 |
June | 0.00 | 0.304157E+10 | 0.00 | 0.598899E+09 | 0.00 | 0.00 | 0.231483E+12 | 0.00 | 20.02 |
July | 0.00 | 0.799707E+10 | 0.00 | 90837444.81 | 0.00 | 0.00 | 0.637102E+10 | 0.00 | 1.83 |
August | 0.00 | 0.627211E+10 | 0.00 | 0.850396E+09 | 0.00 | 0.00 | 0.789178E+11 | 0.00 | 12.52 |
September | 0.00 | 0.134712E+10 | 0.00 | 0.488132E+09 | 0.00 | 0.00 | 0.267813E+12 | 0.00 | 22.10 |
October | 0.00 | 3124309.86 | 0.00 | 0.113110E+10 | 0.00 | 0.00 | 0.659721E+12 | 0.00 | 29.88 |
November | 0.00 | 0.00 | 0.00 | 0.152162E+10 | 0.00 | 0.00 | 0.983535E+12 | 0.00 | 26.94 |
December | 0.00 | 0.00 | 0.00 | 0.225989E+10 | 0.00 | 0.00 | 0.132416E+13 | 0.00 | 27.83 |
Annual Sum or Average | 0.00 | 0.187545E+11 | 0.00 | 0.130527E+11 | 0.00 | 0.00 | 0.722108E+13 | 0.00 | 20.45 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 90837444.81 | 0.00 | 0.00 | 0.637102E+10 | 0.00 | 1.83 |
Maximum of Months | 0.00 | 0.799707E+10 | 0.00 | 0.227025E+10 | 0.00 | 0.00 | 0.132416E+13 | 0.00 | 38.89 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:25:28
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.234752E+12 | 0.206709E+11 | 0.00 | 0.213010E+13 | 0.121082E+12 |
February | 0.377528E+12 | 0.187433E+11 | 0.00 | 0.244658E+13 | 0.177625E+12 |
March | 0.634292E+12 | 0.152776E+11 | 0.00 | 0.309077E+13 | 0.271894E+12 |
April | 0.678351E+12 | 0.996064E+10 | 0.00 | 0.308416E+13 | 0.587707E+12 |
May | 0.863982E+12 | 0.563368E+10 | 0.00 | 0.227808E+13 | 0.659711E+12 |
June | 0.844481E+12 | -224241807.2 | 0.00 | 0.697135E+12 | 0.237098E+13 |
July | 0.825728E+12 | -0.568869E+10 | 0.00 | -0.311289E+12 | 0.361596E+13 |
August | 0.790046E+12 | -0.283814E+10 | 0.00 | 0.148100E+12 | 0.392716E+13 |
September | 0.555570E+12 | 0.197175E+10 | 0.00 | 0.130630E+13 | 0.141923E+13 |
October | 0.526396E+12 | 0.775461E+10 | 0.00 | 0.268277E+13 | 0.755478E+12 |
November | 0.261962E+12 | 0.149025E+11 | 0.00 | 0.304770E+13 | 0.254844E+12 |
December | 0.190240E+12 | 0.176883E+11 | 0.00 | 0.318852E+13 | 0.335905E+12 |
Annual Sum or Average | 0.678333E+13 | 0.103852E+12 | 0.00 | 0.237889E+14 | 0.144976E+14 |
Minimum of Months | 0.190240E+12 | -0.568869E+10 | 0.00 | -0.311289E+12 | 0.121082E+12 |