Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:26
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Simulation Timestamp: 2024-07-03 12:26:47
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:47
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 27033.10 | 583.61 | 583.61 |
Net Site Energy | 27033.10 | 583.61 | 583.61 |
Total Source Energy | 83374.21 | 1799.95 | 1799.95 |
Net Source Energy | 83374.21 | 1799.95 | 1799.95 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1075.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 699.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3236.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 356.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2566.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2409.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 211.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 200.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 887.05 |
Humidification | 1143.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 425.54 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 457.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 25957.91 | 1075.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3592.76 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1075.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 699.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3236.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 356.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 55.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2505.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2409.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 211.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 200.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 887.05 |
Humidification | General | 1143.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 425.54 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 457.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1075.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 699.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3236.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 356.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 2566.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2409.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 211.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 200.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 887.05 |
Humidification | Unassigned | 1143.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 425.54 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 457.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 77.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 110.56 | 23.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 |
Other | 372.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 560.40 | 23.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 77.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 110.56 | 23.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 |
Other | 372.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 560.40 | 23.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 25957.910 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 25957.910 | 100.00 |
Total On-Site and Utility Electric Sources | 25957.910 | 100.00 |
Total Electricity End Uses | 25957.910 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 3592.76 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 3592.76 | 100.00 |
Total Water End Uses | 3592.76 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 11.83 |
Time Setpoint Not Met During Occupied Cooling | 515.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5937.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:47
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:26 |
RunPeriod | RUNPERIOD 1 |
Weather File | William R Fairchild WA USA TMY3 WMO#=727885 |
Latitude [deg] | 48.12 |
Longitude [deg] | -123.5 |
Elevation [m] | 91.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 8.6849 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 8.6849 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 8.7339 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 8.7339 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.6849 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 8.6849 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 8.6849 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 8.6849 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 8.6849 | 18.58 | 484.4232 | |
Total | 46320.38 | 8.7339 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 8.7339 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.6845 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:47
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 14-AUG-15:39 | 10-JAN-07:00 | - | - | - | - | - | - | - | - | - | - | 21-JUL-16:19 |
Heating | 0.00 | 752112.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 320993.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 280450.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 233302.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 240352.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 37304.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 53309.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 36813.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1980898.52 | 752112.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 752112.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 320993.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 280450.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3430.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 240352.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 37304.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 53309.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 36813.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:47
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1165.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2214.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 10250.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1130.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8128.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7629.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 669.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 633.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 3622.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1448.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 82208.70 | 1165.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 25.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 47.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 221.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 24.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 164.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 14.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 13.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 78.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 31.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1774.78 | 25.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 25.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 47.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 221.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 24.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 164.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 14.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 13.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 78.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 31.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1774.78 | 25.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:47
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 5.57 | 0.380019 | 0.000000 | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.84 | 0.325611 | 0.329000 | 1.92 | 0.868295 | 0.500000 | 0.001170 | 0.000167 | 1.92 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 54.86 | 0.346722 | 0.342000 | 18.76 | 0.924592 | 0.500000 | 0.001099 | 0.003259 | 18.76 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.22 | 0.364392 | 0.370000 | 1.93 | 0.971713 | 0.500000 | 0.001046 | 0.000605 | 2.08 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.845186 | 0.282566 | 0.286000 | 0.241723 | 0.753509 | 0.500000 | 0.001348 | 0.000064 | 0.241723 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.30 | 0.117963 | 0.200000 | 0.260937 | 0.314569 | 0.500000 | 0.003230 | 0.000055 | 0.260937 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.83 | 0.130646 | 0.200000 | 0.365607 | 0.348390 | 0.500000 | 0.002916 | 0.000091 | 0.365607 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.58 | 0.097607 | 0.200000 | 0.315356 | 0.300000 | 0.500000 | 0.003903 | 0.000045 | 0.315356 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 7.62 | 0.313324 | 0.309000 | 2.36 | 0.835529 | 0.500000 | 0.001216 | 0.001408 | 4.85 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 13.65 | 0.112779 | 0.200000 | 2.73 | 0.300744 | 0.500000 | 0.003378 | 0.000944 | 3.25 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 18.88 | 0.126511 | 0.200000 | 3.78 | 0.337362 | 0.500000 | 0.003012 | 0.001418 | 4.88 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 14.46 | 0.106405 | 0.200000 | 2.89 | 0.300000 | 0.500000 | 0.003581 | 0.000855 | 2.94 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.845287 | 0.282532 | 0.287000 | 0.242597 | 0.753418 | 0.500000 | 0.001349 | 0.000187 | 0.643891 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.35 | 0.114202 | 0.200000 | 0.269530 | 0.304540 | 0.500000 | 0.003336 | 0.000124 | 0.427348 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.97 | 0.121223 | 0.200000 | 0.394026 | 0.323263 | 0.500000 | 0.003143 | 0.000188 | 0.647635 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.51 | 0.102249 | 0.200000 | 0.301040 | 0.300000 | 0.500000 | 0.003726 | 0.000117 | 0.404160 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | User-Specified Rated Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 19145.05 | 0.000167 | 385.95 | |
CORE_MID VAV BOX REHEAT COIL | 372546.04 | 0.003259 | 8331.50 | |
CORE_TOP VAV BOX REHEAT COIL | 69115.39 | 0.000605 | 1825.78 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 7337.20 | 0.000064 | 186.32 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 6277.10 | 0.000055 | 147.34 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 10422.17 | 0.000091 | 258.40 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 5154.66 | 0.000045 | 110.93 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 160966.14 | 0.001408 | 4246.93 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 107945.88 | 0.000944 | 2847.90 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 162138.93 | 0.001418 | 4277.84 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 97682.65 | 0.000855 | 2577.43 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 21363.32 | 0.000187 | 563.47 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 14177.87 | 0.000124 | 373.94 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 21487.28 | 0.000188 | 566.74 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 13410.02 | 0.000117 | 353.71 | |
VAV_BOT WITH REHEAT HEATING COIL | 53504.15 | 0.000468 | 882.46 | |
VAV_MID WITH REHEAT HEATING COIL | 511863.19 | 0.004478 | 8412.96 | |
VAV_TOP WITH REHEAT HEATING COIL | 48505.95 | 0.000424 | 808.02 | |
CAV_BAS HEATING COIL | 273059.23 | 0.000875 | 2622.63 | 100000.00 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.512002 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.92 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.498289 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 24.79 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.70 | 3.11 | 11.40 | 3.11 | 9.47 | 9.47 | 0.300000 | 0.327860 | 9.47 |
VAV_MID WITH REHEAT | 54.73 | 30.51 | 109.47 | 30.51 | 87.24 | 87.24 | 0.300000 | 0.349793 | 87.24 |
VAV_TOP WITH REHEAT | 5.44 | 3.14 | 10.89 | 4.20 | 9.63 | 9.63 | 0.300000 | 0.435889 | 9.63 |
CAV_BAS | 0.000000 | 0.000000 | 5.57 | 1.20 | 5.57 | 5.57 | 1.00 | 0.215344 | 5.57 |
AIRLOOP DATACENTER BASEMENT | 24.79 | 24.79 | 24.79 | 24.79 | 24.79 | 24.79 | 1.00 | 0.999998 | 24.79 |
AIRLOOP DATACENTER BOT | 0.512002 | 0.512002 | 0.512002 | 0.512002 | 0.512002 | 0.512002 | 1.00 | 1.00 | 0.512002 |
AIRLOOP DATACENTER MID | 4.92 | 4.92 | 4.92 | 4.92 | 4.92 | 4.92 | 1.00 | 1.00 | 4.92 |
AIRLOOP DATACENTER TOP | 0.498289 | 0.498289 | 0.498289 | 0.498289 | 0.498289 | 0.498289 | 1.00 | 1.00 | 0.498289 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.47 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 87.24 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 9.63 | |
CAV_BAS_OA_CONTROLLER | 5.57 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 24.79 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.512002 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.92 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.498289 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 24.64 | 6.67 | 11.02 | 0.008719 | 0.008500 | 163144.85 | 0.004666 | 9.47 |
VAV_MID WITH REHEAT COOLING COIL | 24.70 | 6.67 | 10.92 | 0.008729 | 0.008500 | 1522477.43 | 0.043543 | 87.24 |
VAV_TOP WITH REHEAT COOLING COIL | 24.63 | 6.67 | 11.02 | 0.008716 | 0.008500 | 165709.34 | 0.004739 | 9.63 |
CAV_BAS COOLING COIL | 24.29 | 6.67 | 11.01 | 0.008853 | 0.008500 | 95931.39 | 0.002744 | 5.57 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.47 |
VAV_MID WITH REHEAT FAN | 87.24 |
VAV_TOP WITH REHEAT FAN | 9.63 |
CAV_BAS FAN | 5.57 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.004666 | 0.000102 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000468 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.043543 | 0.000011 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.004478 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.004739 | 0.000100 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000424 | |
CAV_BAS_COOLC_CONTROLLER | 0.002744 | 0.000174 |
CAV_BAS_HEATC_CONTROLLER | 0.000875 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 24.79 | 489877.65 | 352948.20 | 0.011997 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.512002 | 9859.00 | 7196.91 | 0.000241 |
AIRLOOP DATACENTER MID COOLING COIL | 4.92 | 94725.67 | 69141.59 | 0.002320 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.498289 | 9596.07 | 7004.48 | 0.000235 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 24.79 | 24.79 | 24.79 | 24.79 | 489877.65 | 489877.65 | 17946.39 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.512002 | 0.512002 | 0.512002 | 0.512002 | 9859.00 | 9859.00 | 829.05 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.92 | 4.92 | 4.92 | 4.92 | 94725.67 | 94725.67 | 8290.49 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.498289 | 0.498289 | 0.498289 | 0.498289 | 9596.07 | 9596.07 | 829.05 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 24.79 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.512002 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.92 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.498289 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 24.79 | 489877.65 | 0.011997 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.512002 | 9859.00 | 0.000241 |
AIRLOOP DATACENTER MID HEATING COIL | 4.92 | 94725.67 | 0.002320 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.498289 | 9596.07 | 0.000235 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 17946.39 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 829.05 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 8290.49 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 829.05 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000166 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.055691 | 9092.72 | |
HEATSYS1 PUMP | 0.015774 | 4750.38 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.055691 | 6.68 |
HEATSYS1 | 0.015774 | 1.89 |
COOLSYS1_SUPPLY | 0.055691 | 6.68 |
SINGLE WATER PLANT LOOP | 0.014793 | 1.78 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.055691 | 0.055691 | 233765.07 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1803042.98 | 1803042.98 | 0.015774 |
CENTRAL BOILER | 609359.24 | 597130.53 | 0.014793 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.027846 | 3147.60 |
COOLSYS1 CHILLER2 PUMP | 0.027846 | 3147.60 |
PLANT CIRC PUMP | 0.014793 | 3773.04 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.055691 | 0.028026 | 979950.15 | 979950.00 | 0.050368 |
COOLSYS1 CHILLER2 | 0.055691 | 0.028026 | 979950.15 | 979950.00 | 0.050368 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | U-factor Times Area Value at High Fan Speed [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/K] | |
CENTRAL TOWER | 0.014793 | 146887.00 | 74358.50 | 73443.50 | 7879.72 | 44615.10 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.100735 | 12.09 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.100735 | 24939.77 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 38.47 | 1174483.27 | 7.69 | 146810.41 |
TOWERWATERSYS COOLTOWER 2 | 38.47 | 1174483.27 | 7.69 | 146810.41 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.050818 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:47
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:47
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:47
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.30 | 6.70 | 4.10 | 4.20 | 4.20 | 5.90 | 9.00 | 10.00 | 13.30 | 15.00 | 15.70 | 13.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | William R Fairchild WA USA TMY3 WMO#=727885 | 48.12 | -123.50 | -8.00 | 91.00 | 100237 | 1.1914 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.23 | 11.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 8.685 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 13.527 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 8.685 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 493.108 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 24139.153 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 24139.153 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 6806.209 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6806.209 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 0.9689 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 0.9235 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.155 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8647 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9155 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6987 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | -0.61082983E-15 | 0.35276446E-16 | -0.14787207E-09 | 0.18036823E-17 |
51 | 8 | 0.21615122E-07 | 0.13022774E-12 | 0.37506347E-03 | -0.24577139E-09 |
52 | 7 | -0.12160115E-01 | 0.67804000E-08 | -0.22968555E-01 | 0.13826493E-03 |
53 | 6 | 0.40313748 | 0.23652218E-05 | 0.47020644 | -0.47216777E-02 |
54 | 5 | -5.1689687 | 0.88520675E-04 | -4.4267872 | 0.62916081E-01 |
55 | 4 | 32.907337 | 0.72566064E-03 | 21.383769 | -0.42085466 |
56 | 3 | -111.02301 | 0.15845227E-02 | -55.512186 | 1.5122587 |
57 | 2 | 196.92983 | 0.89280554E-03 | 77.772262 | -2.8975199 |
58 | 1 | -171.09018 | 0.95459611E-04 | -55.224854 | 2.7442846 |
59 | 0 | 57.057407 | 0.54436501E-06 | 15.563573 | |
60 | 9 | -0.28033836E-14 | 0.31423843E-16 | -0.15000593E-09 | 0.49342508E-16 |
61 | 8 | 0.21915022E-07 | 0.12441777E-12 | 0.37821899E-03 | -0.24918134E-09 |
62 | 7 | -0.12254290E-01 | 0.64567074E-08 | -0.23104155E-01 | 0.13933574E-03 |
63 | 6 | 0.40569641 | 0.22493722E-05 | 0.47238617 | -0.47518414E-02 |
64 | 5 | -5.1939411 | 0.84090406E-04 | -4.4435303 | 0.63225727E-01 |
65 | 4 | 33.017798 | 0.68864468E-03 | 21.449218 | -0.42232128 |
66 | 3 | -111.25804 | 0.15023393E-02 | -55.641580 | 1.5156542 |
67 | 2 | 197.16277 | 0.84581883E-03 | 77.890928 | -2.9012190 |
68 | 1 | -171.17623 | 0.90368420E-04 | -55.259345 | 2.7457926 |
69 | 0 | 57.057407 | 0.51494858E-06 | 15.557864 | |
70 | 9 | 0.16475985E-14 | 0.40698495E-16 | -0.13909959E-09 | -0.62647149E-17 |
71 | 8 | 0.20378875E-07 | 0.15355384E-12 | 0.36189576E-03 | -0.23171482E-09 |
72 | 7 | -0.11766586E-01 | 0.81065314E-08 | -0.22401745E-01 | 0.13379037E-03 |
73 | 6 | 0.39244372 | 0.28436739E-05 | 0.46108386 | -0.45956244E-02 |
74 | 5 | -5.0645996 | 0.10693990E-03 | -4.3566540 | 0.61621961E-01 |
75 | 4 | 32.445620 | 0.88045565E-03 | 21.109484 | -0.41472443 |
76 | 3 | -110.04047 | 0.19299305E-02 | -54.969854 | 1.4980638 |
77 | 2 | 195.95581 | 0.10911488E-02 | 77.275137 | -2.8820526 |
78 | 1 | -170.73031 | 0.11703553E-03 | -55.080813 | 2.7379774 |
79 | 0 | 57.057407 | 0.66971377E-06 | 15.587784 | |
80 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
81 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
82 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
83 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
84 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
85 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
86 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
87 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
88 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
89 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
90 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
91 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
92 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
93 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
94 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
95 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
96 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
97 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
98 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
99 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
100 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
101 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
102 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
103 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
104 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
105 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
106 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
107 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
108 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
109 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
110 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
111 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
112 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
113 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
114 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
115 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
116 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
117 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
118 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
119 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
120 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
121 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
122 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
123 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
124 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
125 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
126 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
127 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.38_SHGC_EAST_0.38 | 35 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.381 | ||
2 | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 36 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.381 | ||
3 | WINDOW_U_0.38_SHGC_WEST_0.38 | 37 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.381 | ||
4 | WINDOW_U_0.38_SHGC_NORTH_0.38 | 38 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.381 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.45900E-002 | 0.29373 | 0.49855 | 0.49855 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.45900E-002 | 0.29373 | 0.49855 | 0.49855 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.45900E-002 | 0.29373 | 0.49855 | 0.49855 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.45900E-002 | 0.29373 | 0.49855 | 0.49855 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 1.973E-005 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.3898E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.3921E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2832E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2851E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7314E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7328E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6362E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6370E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.4422E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.5954E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.3276E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.4622E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7686E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.8783E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6580E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7133E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1739 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.5660E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1994 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1111 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1138 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7203E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7658E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6576E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.4505E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.6395E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.3368E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.5110E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7754E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9047E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6585E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7149E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.3896E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.3922E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2829E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.2852E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7312E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7329E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6361E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6369E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.3745E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.8230E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.2094E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.7320E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.5490E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.6955E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.5073E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.5455E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.2602E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5545E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.9850E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3320E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.7803E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.8361E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.9620E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.8561E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.2226E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.3390E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.0081E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.0935E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.5030E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.5364E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.5074E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.5461E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9049E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9072E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4600E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4619E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1482E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1496E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6363E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6371E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9566E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0887E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5031E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6100E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1835E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2626E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6585E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7150E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.8121E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5437E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.6999E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9330E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2914E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2759E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.7658E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6571E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9544E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0883E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5000E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6051E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1781E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2456E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6580E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7133E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9048E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9070E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4599E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.4617E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1480E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1493E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6362E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6370E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.5553E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.6765E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1484E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.2364E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.0389E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.0695E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.5075E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.5462E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.0966E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0724E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.4945E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7124E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9229E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4845E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9620E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.8561E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.6677E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.9813E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2982E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.6447E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.0814E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.2120E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.5072E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.5454E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1746 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1296 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1946 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1487 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1274 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.9449E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.8359E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.8866E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.6143E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 5.0933E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.3110E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.8385E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.0143E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.1509E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.9853E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.9197E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.9302E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.9451E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.6732E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.1125E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.2285E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.2893E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.8359E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.8862E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.2974E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.4271E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.6231E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.9810E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.0543E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.6865E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.9853E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.9197E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1746 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1298 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1946 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1490 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1276 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.9614E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.8484E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.8930E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.6198E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 5.1012E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.3172E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.8463E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.0263E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.1598E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.9978E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.9261E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.9305E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.9497E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.6739E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.1161E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.2352E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.2936E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.8484E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.8925E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.3012E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.4335E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.6272E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.9868E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.0650E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.6942E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.9978E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.9261E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 76587.80201 | 76587.80201 | 5.57321 | 5.57321 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 19.66600 | 8.39663E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -4.30000 | 2.65759E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 80279.54508 | 80279.54508 | 5.84147 | 5.84147 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 19.66600 | 8.39663E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | -4.30000 | 2.65759E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 754117.30589 | 754117.30589 | 54.85792 | 54.85792 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 19.66600 | 8.39663E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 185648.31801 | 185648.31801 | 7.86149 | 10.77825 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 71765.61730 | 71765.61730 | 5.21977 | 5.21977 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 19.66600 | 8.39663E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 48433.03673 | 48433.03673 | 2.07616 | 2.07616 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 11509.23752 | 11509.23752 | 0.84519 | 0.84519 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 26.40000 | 8.40708E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 4930.73036 | 4930.73036 | 0.21101 | 0.21101 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 17766.63449 | 17766.63449 | 1.30469 | 1.30469 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 21.10683 | 8.39884E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 3679.11178 | 3679.11178 | 0.15761 | 0.15761 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 24893.32638 | 24893.32638 | 1.82803 | 1.82803 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 26.09667 | 8.40660E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 6781.56468 | 6781.56468 | 0.29098 | 0.29098 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 21471.91019 | 21471.91019 | 1.57678 | 1.57678 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 25.12600 | 8.40508E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 2016.60849 | 2016.60849 | 8.57622E-002 | 8.72129E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 103794.19858 | 103794.19858 | 7.62217 | 7.62217 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 26.40000 | 8.40708E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 112684.57904 | 112684.57904 | 4.84822 | 4.84822 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 185833.31967 | 185833.31967 | 13.64658 | 13.64658 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 21.39500 | 8.39928E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 75563.51961 | 75563.51961 | 3.25163 | 3.25163 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 257070.73363 | 257070.73363 | 18.87790 | 18.87790 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 26.17250 | 8.40672E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 113504.34475 | 113504.34475 | 4.88364 | 4.88364 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 196965.77805 | 196965.77805 | 14.46408 | 14.46408 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.97433 | 8.40484E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 68388.88758 | 68388.88758 | 2.94172 | 2.94172 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 11510.63497 | 11510.63497 | 0.84529 | 0.84529 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 26.40000 | 8.40708E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 14950.40548 | 14950.40548 | 0.64389 | 0.64389 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 18351.73757 | 18351.73757 | 1.34765 | 1.34765 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 21.65283 | 8.39969E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 9921.63140 | 9921.63140 | 0.42735 | 0.42735 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 26828.35953 | 26828.35953 | 1.97013 | 1.97013 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 26.24833 | 8.40684E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 15037.06350 | 15037.06350 | 0.64764 | 0.64764 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 20497.21111 | 20497.21111 | 1.50520 | 1.50520 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.97433 | 8.40484E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 9384.82853 | 9384.82853 | 0.40416 | 0.40416 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8839.64523 | 8839.64523 | 0.51200 | 0.51200 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 23.07850 | 8.40189E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | -4.30000 | 2.65759E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 84917.87860 | 84917.87860 | 4.91856 | 4.91856 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 23.07850 | 8.40189E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -4.30000 | 2.65759E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8602.86301 | 8602.86301 | 0.49829 | 0.49829 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 23.07850 | 8.40189E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -4.30000 | 2.65759E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 372174.28348 | 428000.42600 | 21.55652 | 24.79000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 18.11900 | 8.39428E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 01:40:00 | -4.30000 | 2.65759E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 134121.01 | 9.47194 | 9.47194 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 37353.02 | 1.82464 | 1.82464 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1232148.51 | 87.23541 | 87.23541 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 517912.96 | 26.70346 | 26.70346 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 136413.78 | 9.63365 | 9.63365 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 51935.44 | 4.19920 | 4.19920 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 16:50:00 |
7 | CAV_BAS | Cooling | Sensible | 69385.73 | 5.57321 | 5.57321 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 63649.34 | 1.20016 | 1.20016 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 420742.53 | 24.79004 | 24.79004 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 17946.39 | 0.33839 | 0.33839 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8629.59 | 0.51200 | 0.51200 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 829.05 | 1.56323E-002 | 1.56323E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 82871.17 | 4.91856 | 4.91856 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 8290.49 | 0.15632 | 0.15632 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8396.47 | 0.49829 | 0.49829 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 829.05 | 1.56323E-002 | 1.56323E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 5.57321 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.38002 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.00000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 0.00000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.84147 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32561 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32900 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.92184 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.86829 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.17011E-003 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.67489E-004 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.92184 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
16 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19145.05125 |
17 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.67489E-004 |
18 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 385.94921 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 54.85792 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34672 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34200 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 18.76141 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.92459 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.09886E-003 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.25920E-003 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 18.76141 |
28 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
30 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 372546.04210 |
31 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.25920E-003 |
32 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 8331.50342 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.21977 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36439 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.37000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.93132 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.97171 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.04558E-003 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.04652E-004 |
41 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.07616 |
42 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
43 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
44 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 69115.38689 |
45 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.04652E-004 |
46 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1825.77966 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.84519 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28257 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28600 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24172 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75351 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.34836E-003 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.41890E-005 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.24172 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
58 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7337.20025 |
59 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.41890E-005 |
60 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 186.31953 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.30469 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11796 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26094 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31457 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.22982E-003 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.49148E-005 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.26094 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
72 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6277.10062 |
73 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.49148E-005 |
74 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 147.34059 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.82803 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13065 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.36561 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34839 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.91627E-003 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.11777E-005 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.36561 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
86 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10422.16807 |
87 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.11777E-005 |
88 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 258.40350 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.57678 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.76073E-002 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.31536 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.90340E-003 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.50952E-005 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.31536 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
100 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5154.66121 |
101 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.50952E-005 |
102 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 110.93284 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.62217 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31332 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30900 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.35525 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83553 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.21600E-003 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.40820E-003 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.84822 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
114 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 160966.13750 |
115 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.40820E-003 |
116 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4246.93190 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.64658 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11278 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.72932 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30074 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.37828E-003 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.44358E-004 |
125 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.25163 |
126 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
128 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 107945.87505 |
129 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.44358E-004 |
130 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2847.90177 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 18.87790 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12651 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.77558 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33736 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.01160E-003 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.41846E-003 |
139 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.88364 |
140 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
142 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 162138.92884 |
143 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.41846E-003 |
144 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4277.83515 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.46408 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10640 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.89282 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.58066E-003 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.54570E-004 |
153 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.94172 |
154 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
156 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 97682.64828 |
157 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.54570E-004 |
158 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2577.43262 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.84529 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28253 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28700 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24260 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75342 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.34852E-003 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.86896E-004 |
167 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.64389 |
168 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
170 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21363.31804 |
171 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.86896E-004 |
172 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 563.47418 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.34765 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11420 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26953 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30454 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.33618E-003 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.24034E-004 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.42735 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
184 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14177.86782 |
185 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.24034E-004 |
186 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 373.94146 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.97013 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12122 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.39403 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32326 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.14296E-003 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.87980E-004 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.64764 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
198 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21487.27869 |
199 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.87980E-004 |
200 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 566.74050 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.50520 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10225 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.30104 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.72620E-003 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.17317E-004 |
209 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.40416 |
210 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
211 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
212 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13410.02408 |
213 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.17317E-004 |
214 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 353.70745 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.51200 |
216 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.91856 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.49829 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 24.79000 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.69808 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.10547 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.39615 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.10547 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.47194 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.47194 |
225 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
226 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.32786 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 54.73433 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 30.51437 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 109.46865 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 30.51437 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 87.23541 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 87.23541 |
233 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
234 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.34979 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.44402 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.13851 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.88804 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 4.19920 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.63365 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.63365 |
241 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
242 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.43589 |
243 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.00000 |
244 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.00000 |
245 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.57321 |
246 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 1.20016 |
247 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.57321 |
248 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.57321 |
249 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
250 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.21534 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 24.79000 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 24.79000 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 24.79000 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 24.79000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 24.79004 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 24.79004 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 1.00000 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.51200 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.51200 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.51200 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.51200 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.51200 |
264 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.51200 |
265 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
266 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.91856 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.91856 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.91856 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.91856 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.91856 |
272 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.91856 |
273 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
274 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.49829 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.49829 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.49829 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.49829 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.49829 |
280 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.49829 |
281 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
282 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
283 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.47194 |
284 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 87.23541 |
285 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.63365 |
286 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.57321 |
287 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 24.79004 |
288 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.51200 |
289 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.91856 |
290 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.49829 |
291 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.47194 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.64309 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.02356 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.71857E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 163144.85007 |
298 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.66592E-003 |
299 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.47194 |
300 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 53504.14622 |
301 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.68078E-004 |
302 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 882.46214 |
303 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.47194 |
304 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.66592E-003 |
305 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.02057E-004 |
306 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.68078E-004 |
307 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 87.23541 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.70370 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.92266 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.72914E-003 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1522477.42555 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.35427E-002 |
315 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 87.23541 |
316 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 511863.18965 |
317 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.47800E-003 |
318 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 8412.96096 |
319 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 87.23541 |
320 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.35427E-002 |
321 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.09362E-005 |
322 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.47800E-003 |
323 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.63365 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.63165 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.02355 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.71560E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 165709.34199 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.73927E-003 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.63365 |
332 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 48505.95433 |
333 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.24351E-004 |
334 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 808.02416 |
335 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.63365 |
336 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.73927E-003 |
337 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.00478E-004 |
338 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.24351E-004 |
339 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.57321 |
340 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.28851 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.01253 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.85270E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 95931.38672 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 2.74363E-003 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.57321 |
349 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 273059.22573 |
350 | Coil:Heating:Water | CAV_BAS HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
351 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
352 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2622.62541 |
353 | Fan:VariableVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.57321 |
354 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.74363E-003 |
355 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.73562E-004 |
356 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.74844E-004 |
357 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 24.79004 |
358 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
359 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.79004 |
360 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 489877.64658 |
361 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 352948.20153 |
362 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.19971E-002 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 24.79004 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 24.79004 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 24.79004 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 24.79004 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 489877.64658 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 489877.64658 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 17946.39161 |
370 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
371 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 24.79004 |
372 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.79004 |
373 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 489877.64658 |
374 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.19971E-002 |
375 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 17946.39161 |
376 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.66253E-004 |
377 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
378 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
379 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
380 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.51200 |
381 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
382 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.51200 |
383 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9859.00010 |
384 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 7196.90884 |
385 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.41446E-004 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.51200 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.51200 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.51200 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.51200 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9859.00010 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9859.00010 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 829.04894 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
394 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.51200 |
395 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.51200 |
396 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9859.00010 |
397 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.41446E-004 |
398 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 829.04894 |
399 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.91856 |
400 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
401 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.91856 |
402 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 94725.66938 |
403 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 69141.58928 |
404 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.31983E-003 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.91856 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.91856 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.91856 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.91856 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 94725.66938 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 94725.66938 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 8290.48945 |
412 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
413 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.91856 |
414 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.91856 |
415 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 94725.66938 |
416 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.31983E-003 |
417 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 8290.48945 |
418 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.49829 |
419 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
420 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49829 |
421 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9596.07153 |
422 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 7004.47816 |
423 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.35007E-004 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.49829 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.49829 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.49829 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.49829 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9596.07153 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9596.07153 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 829.04894 |
431 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
432 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.49829 |
433 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49829 |
434 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9596.07153 |
435 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.35007E-004 |
436 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 829.04894 |
437 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 5.56915E-002 |
438 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 9092.71619 |
439 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 5.56915E-002 |
440 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 6.68298 |
441 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 5.56915E-002 |
442 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 5.56915E-002 |
443 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 233765.06655 |
444 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
445 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.57738E-002 |
446 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 1.89286 |
447 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.57738E-002 |
448 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 4750.37782 |
449 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
450 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1803042.97889 |
451 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1803042.98000 |
452 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.57738E-002 |
453 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 5.56915E-002 |
454 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 6.68298 |
455 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 2.78457E-002 |
456 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 3147.59703 |
457 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 2.78457E-002 |
458 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 3147.59703 |
459 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 5.56915E-002 |
460 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 2.80265E-002 |
461 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 979950.15171 |
462 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 979950.00000 |
463 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 5.03675E-002 |
464 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 5.56915E-002 |
465 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 2.80265E-002 |
466 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 979950.15171 |
467 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 979950.00000 |
468 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 5.03675E-002 |
469 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.47934E-002 |
470 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.77520 |
471 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.47934E-002 |
472 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3773.04429 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.47934E-002 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 146887.00134 |
475 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at High Fan Speed [W/K] | 74358.49822 |
476 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 73443.50067 |
477 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
478 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/K] | 44615.09893 |
479 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 609359.23848 |
480 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 597130.53000 |
481 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.47934E-002 |
482 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
483 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
484 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
485 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
486 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
487 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.10074 |
488 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 12.08821 |
489 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.10074 |
490 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 24939.76873 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 38.46820 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1174483.26912 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 7.69364 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 146810.40864 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 38.46820 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1174483.26912 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 7.69364 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 146810.40864 |
499 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.08175E-002 |
500 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.08175E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 18153.37 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 353055.03 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 65503.38 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 6948.66 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 5947.04 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 9871.27 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4885.84 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 152519.13 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 102280.25 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 153630.11 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 92557.72 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 20241.06 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 13433.00 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 20358.49 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 12705.62 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 41360.24 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 392872.95 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 38262.70 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 94837.48 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 211173.35 | 156547.66 | 54625.69 | 0.74 | 36423.10 | 369.42 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 1964681.71 | 1450336.00 | 514345.71 | 0.74 | 340812.33 | 3456.71 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 214639.09 | 159166.49 | 55472.60 | 0.74 | 37054.06 | 375.82 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 124540.30 | 92263.12 | 32277.19 | 0.74 | 21713.12 | 220.23 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 7.93 | 27.04 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 7.93 | 27.04 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.38 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.38 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.38 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.38 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.38 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.38 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.38 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.38 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.38 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.38 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.38 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.38 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.38 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.38 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.38 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.38 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.38 | N/A | 2.159 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.38 | N/A | 2.159 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.38 | N/A | 2.159 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.38 | N/A | 2.159 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.38 | N/A | 2.159 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.38 | N/A | 2.159 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.38 | N/A | 2.159 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.38 | N/A | 2.159 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.3558466875E-003 | 1.3642856150E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.1028578050 | 0.2071284781 | Pass | Pass | 6.3631072547E-002 | 0.2468874520 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 7.1804659059E-003 | 7.7035681103E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 4.2747212847E-002 | 3.0767490943E-002 | Pass | Pass | 0.4275031424 | 0.5311351470 | Pass | Fail |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 6.6090479615E-002 | 0.1195426251 | Pass | Pass | 5.6191439680E-002 | 0.2290998423 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1277812517 | 0.2358217832 | Pass | Pass | 5.9189927736E-002 | 0.2359999486 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1483783550 | 0.2495358019 | Pass | Pass | 6.1525479957E-002 | 0.2433602727 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1316643109 | 0.2460388331 | Pass | Pass | 5.8199023384E-002 | 0.2321898713 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.8603831960E-002 | 1.5729685308E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 5.4507377747E-002 | 8.6033580214E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 9.5007558523E-002 | 0.1194810351 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 4.6492324815E-002 | 5.8228210595E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1869636747 | 0.1948154440 | Pass | Fail | 14.1608375399 | 34.3373514442 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1400665176 | 0.1447026954 | Pass | Fail | 8.5509692544 | 20.3480596497 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1305570658 | 0.1509435297 | Pass | Pass | 6.3370115403 | 35.5411973058 | Fail | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 7.5572468836E-002 | 7.8050135668E-002 | Fail | Pass | 6.4004663350 | 16.3197308648 | Fail | Fail |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.6605516772E-002 | 3.0711190342E-002 | Pass | Pass | 0.2942961270 | 1.4494083885 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.9334269970E-003 | 6.1544072019E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.9009691691E-002 | 6.3400812633E-002 | Pass | Pass | 0.4023681274 | 0.4687188769 | Fail | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.2730115996E-006 | 6.7252022438E-006 | Pass | Pass | 3.5520562870E-003 | 4.3237527583E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.2959357224E-006 | 7.6931473060E-006 | Pass | Pass | 0.1665427326 | 0.4701175730 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.7806393795E-002 | 2.4831536641E-002 | Pass | Pass | 5.7252943174E-003 | 9.3823907742E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.3905829449E-006 | 1.8714672260E-006 | Pass | Pass | 4.8118717277E-005 | 1.0712525435E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:47
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5848.13 | 60.84 | 0.00 | 34309.26 | 4733.49 | 44951.73 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:47
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00 | -4.30 | Wetbulb [C] | 1.20 | 110.00 |
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 9.10 | 17.00 | Wetbulb [C] | 2.10 | 90.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 42.00 | 35 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 40.00 | 22 | |||
Jun | 4.00 | 8 | |||
Jul | 5.00 | 4 | |||
Aug | 7.00 | 8 | |||
Sep | 17.00 | 10 | |||
Oct | 50.00 | 49 | |||
Nov | 69.00 | 59 | |||
Dec | 95.00 | 53 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:47
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.38_SHGC_NORTH_0.38 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.38_SHGC_NORTH_0.38 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.38_SHGC_NORTH_0.38 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.38_SHGC_NORTH_0.38 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.38_SHGC_NORTH_0.38 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.38_SHGC_EAST_0.38 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.38_SHGC_EAST_0.38 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.38_SHGC_EAST_0.38 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.38_SHGC_WEST_0.38 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.38_SHGC_WEST_0.38 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.38_SHGC_WEST_0.38 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.38_SHGC_NORTH_0.38 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.159 | 0.381 | 0.420 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.38_SHGC_EAST_0.38 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.159 | 0.381 | 0.420 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.159 | 0.381 | 0.420 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.38_SHGC_WEST_0.38 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.159 | 0.381 | 0.420 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.38_SHGC_NORTH_0.38 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.159 | 0.381 | 0.420 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.38_SHGC_EAST_0.38 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.159 | 0.381 | 0.420 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.159 | 0.381 | 0.420 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.38_SHGC_WEST_0.38 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.159 | 0.381 | 0.420 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.159 | 0.381 | 0.420 | |||||||||||||||||
North Total or Average | 1390.74 | 2.159 | 0.381 | 0.420 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.159 | 0.381 | 0.420 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:47
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:47
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.6849 | 2779.43 | 24139.15 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 216.17 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 8.6849 | 2496.12 | 21678.66 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 194.14 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 8.6849 | 24961.20 | 216786.56 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 1941.36 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 8.6849 | 2496.12 | 21678.66 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 194.14 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 8.6849 | 313.41 | 2721.97 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.52 | 0.0000 | Y | 14.57 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.02 | 0.0000 | Y | 9.23 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 8.6849 | 313.42 | 2722.03 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.77 | 0.0000 | Y | 14.19 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.19 | 0.0000 | Y | 9.28 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 8.6849 | 3134.13 | 27219.72 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.45 | 0.0000 | Y | 145.37 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 8.6849 | 2019.75 | 17541.42 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.97 | 0.0000 | Y | 92.10 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 8.6849 | 3134.20 | 27220.31 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.74 | 0.0000 | Y | 141.73 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 8.6849 | 2019.75 | 17541.42 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.12 | 0.0000 | Y | 92.60 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 8.6849 | 313.41 | 2721.97 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.45 | 0.0000 | Y | 14.53 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.97 | 0.0000 | Y | 9.21 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 8.6849 | 313.42 | 2722.03 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.74 | 0.0000 | Y | 14.17 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 28.12 | 0.0000 | Y | 9.26 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 8.6849 | 783.68 | 6806.21 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 62.65 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 13.9016 | 36.20 | 503.28 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.16 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 13.9016 | 362.03 | 5032.75 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 51.55 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 13.9016 | 36.20 | 503.28 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.16 |
Interior Lighting Total | 8.7339 | 46320.38 | 404555.99 | 1018.32 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13271.55 | AstronomicalClock | - | 42.50 | 42.50 | 105.87 | |
EXTERIOR_LIGHTS_B | 989.48 | AstronomicalClock | - | 83.54 | 63.02 | 11.70 | |
EXTERIOR_LIGHTS_C | 26594.85 | AstronomicalClock | - | 83.54 | 47.95 | 239.37 | |
Exterior Lighting Total | 40855.88 | 356.94 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:47
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 1941265.26 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1803042.98 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 979950.00 | 5.17 | 976631.56 | 5.11 | 7.93 | 27.04 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 979950.00 | 5.17 | 976631.56 | 5.11 | 7.93 | 27.04 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 612151.58 | |||||
CENTRAL BOILER | Boiler:HotWater | 597130.53 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1174483.27 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1174483.27 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 163144.85 | 211173.35 | 156547.66 | 54625.69 | 0.74 | - | 36423.10 | 369.42 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1522477.43 | 1964681.71 | 1450336.00 | 514345.71 | 0.74 | - | 340812.33 | 3456.71 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 165709.34 | 214639.09 | 159166.49 | 55472.60 | 0.74 | - | 37054.06 | 375.82 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 95931.39 | 124540.30 | 92263.12 | 32277.19 | 0.74 | - | 21713.12 | 220.23 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 489877.65 | 352948.20 | 136929.45 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9859.00 | 7196.91 | 2662.09 | 0.73 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 94725.67 | 69141.59 | 25584.08 | 0.73 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9596.07 | 7004.48 | 2591.59 | 0.73 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 19145.05 | 18153.37 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 372546.04 | 353055.03 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 69115.39 | 65503.38 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 7337.20 | 6948.66 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 6277.10 | 5947.04 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10422.17 | 9871.27 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 5154.66 | 4885.84 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 160966.14 | 152519.13 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 107945.88 | 102280.25 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 162138.93 | 153630.11 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 97682.65 | 92557.72 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 21363.32 | 20241.06 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 14177.87 | 13433.00 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 21487.28 | 20358.49 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 13410.02 | 12705.62 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 53504.15 | 41360.24 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 511863.19 | 392872.95 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 48505.95 | 38262.70 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 100000.00 | 94837.48 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 489877.65 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9859.00 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 94725.67 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9596.07 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 17946.39 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 829.05 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 8290.49 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 829.05 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.47 | 20468.35 | 2160.95 | 1.00 | 1.12 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 87.24 | 199221.94 | 2283.73 | 1.00 | 1.07 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 9.63 | 20817.80 | 2160.95 | 1.00 | 1.12 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
CAV_BAS FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.57 | 12121.11 | 2174.89 | 1.00 | 1.13 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 24.79 | 40884.90 | 1649.25 | 1.00 | 1.14 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.51 | 573.50 | 1120.11 | 1.00 | 1.60 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.92 | 5509.32 | 1120.11 | 1.00 | 1.16 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.50 | 558.14 | 1120.11 | 1.00 | 1.61 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.055691 | 9092.72 | 163269.45 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.015774 | 4750.38 | 301156.09 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.027846 | 3147.60 | 113036.94 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.027846 | 3147.60 | 113036.94 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.014793 | 3773.04 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.100735 | 24939.77 | 247577.87 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:47
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 76587.80 | 76587.80 | 27.56 | 5.573 | 5.573 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00896 | 19.67 | 0.00840 | 1.200 | 0.00 |
CORE_BOTTOM | 80279.55 | 80279.55 | 32.16 | 5.841 | 5.841 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00889 | 19.67 | 0.00840 | 1.078 | 0.00 |
CORE_MID | 754117.31 | 754117.31 | 302.12 | 54.858 | 54.858 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 19.67 | 0.00840 | 10.778 | 0.00 |
CORE_TOP | 71765.62 | 71765.62 | 28.75 | 5.220 | 5.220 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00894 | 19.67 | 0.00840 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 11509.24 | 11509.24 | 36.72 | 0.845 | 0.845 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00883 | 26.40 | 0.00841 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 17766.63 | 17766.63 | 87.96 | 1.305 | 1.305 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 24.00 | 24.00 | 0.00864 | 21.11 | 0.00840 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 24893.33 | 24893.33 | 79.42 | 1.828 | 1.828 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00865 | 26.10 | 0.00841 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 21471.91 | 21471.91 | 106.31 | 1.577 | 1.577 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00861 | 25.13 | 0.00841 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 103794.20 | 103794.20 | 331.17 | 7.622 | 7.622 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 24.00 | 0.00886 | 26.40 | 0.00841 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 185833.32 | 185833.32 | 920.08 | 13.647 | 13.647 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 24.00 | 24.00 | 0.00863 | 21.39 | 0.00840 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 257070.73 | 257070.73 | 820.21 | 18.878 | 18.878 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00865 | 26.17 | 0.00841 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 196965.78 | 196965.78 | 975.20 | 14.464 | 14.464 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00862 | 24.97 | 0.00840 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 11510.63 | 11510.63 | 36.73 | 0.845 | 0.845 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00882 | 26.40 | 0.00841 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 18351.74 | 18351.74 | 90.86 | 1.348 | 1.348 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 24.00 | 24.00 | 0.00863 | 21.65 | 0.00840 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 26828.36 | 26828.36 | 85.60 | 1.970 | 1.970 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 24.00 | 0.00864 | 26.25 | 0.00841 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 20497.21 | 20497.21 | 101.48 | 1.505 | 1.505 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00862 | 24.97 | 0.00840 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8839.65 | 8839.65 | 244.17 | 0.512 | 0.512 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 27.00 | 27.00 | 0.00858 | 23.08 | 0.00840 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 84917.88 | 84917.88 | 2345.62 | 4.919 | 4.919 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 27.00 | 27.00 | 0.00859 | 23.08 | 0.00840 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8602.86 | 8602.86 | 237.63 | 0.498 | 0.498 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 27.00 | 27.00 | 0.00858 | 23.08 | 0.00840 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 372174.28 | 428000.43 | 546.14 | 21.557 | 24.790 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 18.12 | 0.00839 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 21.00 | 24.39 | 0.00266 | -4.30 | 0.00266 | 1.200 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | 19.60 | 22.25 | 0.00266 | -4.30 | 0.00266 | 1.078 | 0.00 |
CORE_MID | 185648.32 | 185648.32 | 74.37 | 7.861 | 10.778 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.30 | 0.00266 | 10.778 | 0.00 |
CORE_TOP | 48433.04 | 48433.04 | 19.40 | 2.076 | 2.076 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.30 | 0.00266 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 4930.73 | 4930.73 | 15.73 | 0.211 | 0.211 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00769 | -4.30 | 0.00266 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 3679.11 | 3679.11 | 18.22 | 0.158 | 0.158 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -4.30 | 0.00266 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 6781.56 | 6781.56 | 21.64 | 0.291 | 0.291 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00780 | -4.30 | 0.00266 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 2016.61 | 2016.61 | 9.98 | 0.086 | 0.087 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00743 | -4.30 | 0.00266 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 112684.58 | 112684.58 | 359.54 | 4.848 | 4.848 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00786 | -4.30 | 0.00266 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 75563.52 | 75563.52 | 374.12 | 3.252 | 3.252 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00787 | -4.30 | 0.00266 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 113504.34 | 113504.34 | 362.15 | 4.884 | 4.884 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00786 | -4.30 | 0.00266 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 68388.89 | 68388.89 | 338.60 | 2.942 | 2.942 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -4.30 | 0.00266 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 14950.41 | 14950.41 | 47.70 | 0.644 | 0.644 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00791 | -4.30 | 0.00266 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 9921.63 | 9921.63 | 49.12 | 0.427 | 0.427 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00791 | -4.30 | 0.00266 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 15037.06 | 15037.06 | 47.98 | 0.648 | 0.648 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00791 | -4.30 | 0.00266 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 9384.83 | 9384.83 | 46.47 | 0.404 | 0.404 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00790 | -4.30 | 0.00266 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | 18.00 | 26.81 | 0.00850 | -4.30 | 0.00266 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 23.66 | 0.00651 | -4.30 | 0.00266 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 21.84 | 0.00298 | -4.30 | 0.00266 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 01:40:00 | 18.00 | 27.00 | 0.00850 | -4.30 | 0.00266 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 9.47 | 9.47 | 1.82 | 1.82 | 9.4719 | 3.1055 | 9.4719 | 0.3279 | 0.3000 |
VAV_MID WITH REHEAT | 87.24 | 87.24 | 26.70 | 26.70 | 87.2354 | 30.5144 | 87.2354 | 0.3498 | 0.3000 |
VAV_TOP WITH REHEAT | 9.63 | 9.63 | 4.20 | 4.20 | 9.6336 | 4.1992 | 9.6336 | 0.4359 | 0.3000 |
CAV_BAS | 5.57 | 5.57 | 1.20 | 1.20 | 5.5732 | 1.2002 | 5.5732 | 0.2153 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.79 | 24.79 | 0.34 | 0.34 | 24.7900 | 24.7900 | 24.7900 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.51 | 0.51 | 0.02 | 0.02 | 0.5120 | 0.5120 | 0.5120 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.92 | 4.92 | 0.16 | 0.16 | 4.9186 | 4.9186 | 4.9186 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.50 | 0.50 | 0.02 | 0.02 | 0.4983 | 0.4983 | 0.4983 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 19145.051 | 19145.051 | 1.921843 | 0.00016749 | 385.949 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | 19145.05 | 19145.05 | 1.921843 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00800000 | 51.1678 | 0.00 | 0.00 | 19215.64 | 19215.64 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 372546.042 | 372546.042 | 18.761407 | 0.00325920 | 8331.503 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 372546.04 | 372546.04 | 18.761407 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00800000 | 51.1678 | 185648.32 | 0.00 | 373822.88 | 373822.88 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 69115.387 | 69115.387 | 2.076162 | 0.00060465 | 1825.780 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 69115.39 | 69115.39 | 2.076162 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00800000 | 51.1678 | 48433.04 | 0.00 | 69363.86 | 69363.86 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 7337.200 | 7337.200 | 0.241723 | 0.00006419 | 186.320 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7337.20 | 7337.20 | 0.241723 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00768737 | 49.1944 | 4930.73 | 0.00 | 7359.89 | 7359.89 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 6277.101 | 6277.101 | 0.260937 | 0.00005491 | 147.341 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6277.10 | 6277.10 | 0.260937 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00773563 | 49.4993 | 3679.11 | 0.00 | 6297.69 | 6297.69 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 10422.168 | 10422.168 | 0.365607 | 0.00009118 | 258.404 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10422.17 | 10422.17 | 0.365607 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00780328 | 49.9266 | 6781.56 | 0.00 | 10454.81 | 10454.81 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 5154.661 | 5154.661 | 0.315356 | 0.00004510 | 110.933 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5154.66 | 5154.66 | 0.315356 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00743449 | 47.5953 | 2016.61 | 0.00 | 5172.69 | 5172.69 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 160966.137 | 160966.137 | 4.848219 | 0.00140820 | 4246.932 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 160966.14 | 160966.14 | 4.848219 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00785726 | 50.2678 | 112684.58 | 0.00 | 161507.42 | 161507.42 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 107945.875 | 107945.875 | 3.251632 | 0.00094436 | 2847.902 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 107945.88 | 107945.88 | 3.251632 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00786600 | 50.3230 | 75563.52 | 0.00 | 108307.84 | 108307.84 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 162138.929 | 162138.929 | 4.883641 | 0.00141846 | 4277.835 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 162138.93 | 162138.93 | 4.883641 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00785981 | 50.2839 | 113504.34 | 0.00 | 162683.87 | 162683.87 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 97682.648 | 97682.648 | 2.941721 | 0.00085457 | 2577.433 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 97682.65 | 97682.65 | 2.941721 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00782985 | 50.0949 | 68388.89 | 0.00 | 98012.37 | 98012.37 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 21363.318 | 21363.318 | 0.643891 | 0.00018690 | 563.474 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21363.32 | 21363.32 | 0.643891 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00790538 | 50.5715 | 14950.41 | 0.00 | 21433.89 | 21433.89 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 14177.868 | 14177.868 | 0.427348 | 0.00012403 | 373.941 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14177.87 | 14177.87 | 0.427348 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00790631 | 50.5774 | 9921.63 | 0.00 | 14224.63 | 14224.63 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 21487.279 | 21487.279 | 0.647635 | 0.00018798 | 566.741 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21487.28 | 21487.28 | 0.647635 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00790621 | 50.5767 | 15037.06 | 0.00 | 21558.24 | 21558.24 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 13410.024 | 13410.024 | 0.404160 | 0.00011732 | 353.707 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13410.02 | 13410.02 | 0.404160 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00789641 | 50.5149 | 9384.83 | 0.00 | 13454.38 | 13454.38 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 163144.850 | -999.000 | 9.471936 | 0.00466592 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | 163144.85 | 156674.40 | 9.471936 | 24.64 | 16.69 | 0.00871857 | 11.02 | 11.02 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 26.7970 | 24.00 | 0.00883280 | 47.0210 | 128816.66 | 0.00 | 164702.43 | 152244.28 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 53504.146 | 53504.146 | 2.841581 | 0.00046808 | 882.462 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 53504.15 | 53504.15 | 2.841581 | -2.93 | -3.11 | 0.00287852 | 12.80 | 11.50 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 89.3232 | 21.58 | 0.00541557 | 33.5643 | 17408.02 | 0.00 | 50040.36 | 50040.36 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1522477.426 | -999.000 | 87.235413 | 0.04354266 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 1522477.43 | 1459570.06 | 87.235413 | 24.70 | 16.72 | 0.00872914 | 10.92 | 10.92 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 29.0959 | 24.00 | 0.00886297 | 47.1794 | 1177391.72 | 0.00 | 1536972.25 | 1413950.82 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 511863.190 | 511863.190 | 26.170624 | 0.00447800 | 8412.961 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 511863.19 | 511863.19 | 26.170624 | -3.54 | -3.57 | 0.00281658 | 12.80 | 11.50 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 96.9864 | 21.00 | 0.00792335 | 50.6845 | 511638.34 | 0.00 | 475305.64 | 475305.64 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 165709.342 | -999.000 | 9.633647 | 0.00473927 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 165709.34 | 159217.74 | 9.633647 | 24.63 | 16.68 | 0.00871560 | 11.02 | 11.02 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 26.3471 | 24.00 | 0.00882601 | 46.9853 | 131145.46 | 0.00 | 167293.74 | 154710.87 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 48505.954 | 48505.954 | 2.890094 | 0.00042435 | 808.024 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 16:50:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 48505.95 | 48505.95 | 2.890094 | -1.22 | -1.45 | 0.00329964 | 12.80 | 11.50 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 87.8238 | 21.00 | 0.00793057 | 50.7300 | 58559.64 | 0.00 | 46299.73 | 46299.73 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 95931.387 | -999.000 | 5.573210 | 0.00274363 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 95931.39 | 89784.55 | 5.573210 | 24.29 | 16.68 | 0.00885270 | 11.01 | 11.01 | 0.00850000 | 25.22 | 0.00840522 | 16.63 | 21.5344 | 24.00 | 0.00899238 | 47.8588 | 70019.52 | 0.00 | 96834.82 | 87300.65 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 100000.000 | 100000.000 | 3.070992 | 0.00087484 | 2622.625 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 100000.00 | 100000.00 | 3.070992 | -0.93 | -2.30 | 0.00265759 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 39.0804 | 24.44 | 0.00265759 | 13.9177 | 0.00 | 0.00 | 100079.59 | 100079.59 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 489877.647 | 352948.202 | 24.790042 | 0.01199707 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | 455920.28 | 453221.47 | -999.0 | 28.40 | 17.83 | 0.00854036 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | -999.0000 | 27.00 | 0.00854221 | 38.0734 | 371823.13 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9859.000 | 7196.909 | 0.512002 | 0.00024145 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 9135.73 | 9030.65 | -999.0 | 27.83 | 17.67 | 0.00857629 | 12.80 | 12.00 | 0.00850000 | 23.08 | 0.00840189 | 15.87 | -999.0000 | 27.00 | 0.00858178 | 38.2448 | 8839.65 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 94725.669 | 69141.589 | 4.918563 | 0.00231983 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 87778.34 | 86729.02 | -999.0 | 27.83 | 17.67 | 0.00857930 | 12.80 | 12.00 | 0.00850000 | 23.08 | 0.00840189 | 15.87 | -999.0000 | 27.00 | 0.00858512 | 38.2596 | 84917.88 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9596.072 | 7004.478 | 0.498289 | 0.00023501 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | 8892.24 | 8787.14 | -999.0 | 27.83 | 17.67 | 0.00857839 | 12.80 | 12.00 | 0.00850000 | 23.08 | 0.00840189 | 15.87 | -999.0000 | 27.00 | 0.00858411 | 38.2551 | 8602.86 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 489877.647 | 489877.647 | 24.790042 | 0.01199707 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 489877.65 | 489877.65 | 24.790042 | -4.30 | -4.30 | 0.00265759 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 1.3650 | 27.00 | 0.00850000 | 37.8820 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9859.000 | 9859.000 | 0.512002 | 0.00024145 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9859.00 | 9859.00 | 0.512002 | -4.30 | -4.30 | 0.00265759 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 3.0532 | 27.00 | 0.00850000 | 37.8820 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 94725.669 | 94725.669 | 4.918563 | 0.00231983 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 94725.67 | 94725.67 | 4.918563 | -4.30 | -4.30 | 0.00265759 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 3.1782 | 24.79 | 0.00650701 | 33.1680 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9596.072 | 9596.072 | 0.498289 | 0.00023501 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9596.07 | 9596.07 | 0.498289 | -4.30 | -4.30 | 0.00265759 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 3.1372 | 23.68 | 0.00298298 | 16.3422 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 17946.392 | 17946.392 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 17946.39 | 17946.39 | 24.790042 | -0.06 | -0.06 | 0.00842025 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 1.3650 | 27.00 | 0.00850000 | 37.8820 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 829.049 | 829.049 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 829.05 | 829.05 | 0.512002 | -0.13 | -0.13 | 0.00832162 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 3.0532 | 27.00 | 0.00850000 | 37.8820 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 8290.489 | 8290.489 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 8290.49 | 8290.49 | 4.918563 | -0.14 | -0.14 | 0.00638467 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 3.1782 | 24.79 | 0.00650701 | 33.1680 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 829.049 | 829.049 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 829.05 | 829.05 | 0.498289 | -0.13 | -1.35 | 0.00297277 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 3.1372 | 23.68 | 0.00298298 | 16.3422 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:26:47
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 19145.051 | 19145.051 | 1.921843 | 0.00016749 | 385.949 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 15.77219744 | 54.44 | 82.22 | 27.78 | 1839329.94 | 1.0409 | 1.061819 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | Sensible | 19145.05 | 19145.05 | 1.0000 | 2.28963008 | 1.921843 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.16747217 | 60.00 | 32.22 | 27.78 | 0.000 | 19145.05 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.1678 | 0.00 | 0.00 | 19215.64 | 19215.64 | 2.28963008 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 372546.042 | 372546.042 | 18.761407 | 0.00325920 | 8331.503 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 15.77219744 | 54.44 | 82.22 | 27.78 | 1839329.94 | 20.2544 | 20.662072 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 372546.04 | 372546.04 | 1.0000 | 22.35181527 | 18.761407 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 3.25886282 | 60.00 | 32.22 | 27.78 | 0.000 | 372546.04 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.57 | 0.00800000 | 21.00 | 0.00800000 | 51.1678 | 185648.32 | 0.00 | 373822.88 | 373822.88 | 22.35181527 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 29.20 | 17.77 | 0.00800000 | 49784.3 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 69115.387 | 69115.387 | 2.076162 | 0.00060465 | 1825.780 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 15.77219744 | 54.44 | 82.22 | 27.78 | 1839329.94 | 3.7576 | 3.833263 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 69115.39 | 69115.39 | 1.0000 | 2.47348154 | 2.076162 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.60458987 | 60.00 | 32.22 | 27.78 | 0.000 | 69115.39 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 51.1678 | 48433.04 | 0.00 | 69363.86 | 69363.86 | 2.47348154 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.30 | 21.27 | 0.00800000 | 61102.8 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7337.200 | 7337.200 | 0.241723 | 0.00006419 | 186.320 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 15.77219744 | 54.44 | 82.22 | 27.78 | 1839329.94 | 0.3989 | 0.406934 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7337.20 | 7337.20 | 1.0000 | 0.28798215 | 0.241723 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.06418248 | 60.00 | 32.22 | 27.78 | 0.000 | 7337.20 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.86 | 0.00768737 | 21.00 | 0.00768737 | 49.1944 | 4930.73 | 0.00 | 7359.89 | 7359.89 | 0.28798215 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 37.86 | 20.54 | 0.00800000 | 58616.6 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6277.101 | 6277.101 | 0.260937 | 0.00005491 | 147.341 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 15.77219744 | 54.44 | 82.22 | 27.78 | 1839329.94 | 0.3413 | 0.348139 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 6277.10 | 6277.10 | 1.0000 | 0.31087320 | 0.260937 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.05490921 | 60.00 | 32.22 | 27.78 | 0.000 | 6277.10 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.92 | 0.00773563 | 21.00 | 0.00773563 | 49.4993 | 3679.11 | 0.00 | 6297.69 | 6297.69 | 0.31087320 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.67 | 18.91 | 0.00800000 | 53317.9 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10422.168 | 10422.168 | 0.365607 | 0.00009118 | 258.404 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 15.77219744 | 54.44 | 82.22 | 27.78 | 1839329.94 | 0.5666 | 0.578032 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10422.17 | 10422.17 | 1.0000 | 0.43557376 | 0.365607 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.09116837 | 60.00 | 32.22 | 27.78 | 0.000 | 10422.17 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.91 | 0.00780328 | 21.00 | 0.00780328 | 49.9266 | 6781.56 | 0.00 | 10454.81 | 10454.81 | 0.43557376 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 36.34 | 20.07 | 0.00800000 | 57062.2 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5154.661 | 5154.661 | 0.315356 | 0.00004510 | 110.933 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 15.77219744 | 54.44 | 82.22 | 27.78 | 1839329.94 | 0.2802 | 0.285887 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5154.66 | 5154.66 | 1.0000 | 0.37570576 | 0.315356 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.04509062 | 60.00 | 32.22 | 27.78 | 0.000 | 5154.66 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.81 | 0.00743449 | 21.00 | 0.00743449 | 47.5953 | 2016.61 | 0.00 | 5172.69 | 5172.69 | 0.37570576 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 26.30 | 16.77 | 0.00800000 | 46827.8 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 160966.137 | 160966.137 | 4.848219 | 0.00140820 | 4246.932 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 15.77219744 | 54.44 | 82.22 | 27.78 | 1839329.94 | 8.7513 | 8.927471 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 160966.14 | 160966.14 | 1.0000 | 5.77603197 | 4.848219 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 1.40805834 | 60.00 | 32.22 | 27.78 | 0.000 | 160966.14 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00785726 | 21.00 | 0.00785726 | 50.2678 | 112684.58 | 0.00 | 161507.42 | 161507.42 | 5.77603197 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61021.5 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 107945.875 | 107945.875 | 3.251632 | 0.00094436 | 2847.902 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 15.77219744 | 54.44 | 82.22 | 27.78 | 1839329.94 | 5.8688 | 5.986872 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 107945.88 | 107945.88 | 1.0000 | 3.87390324 | 3.251632 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.94426127 | 60.00 | 32.22 | 27.78 | 0.000 | 107945.88 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00786600 | 21.00 | 0.00786600 | 50.3230 | 75563.52 | 0.00 | 108307.84 | 108307.84 | 3.87390324 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61018.2 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 162138.929 | 162138.929 | 4.883641 | 0.00141846 | 4277.835 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 15.77219744 | 54.44 | 82.22 | 27.78 | 1839329.94 | 8.8151 | 8.992516 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 162138.93 | 162138.93 | 1.0000 | 5.81823373 | 4.883641 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 1.41831738 | 60.00 | 32.22 | 27.78 | 0.000 | 162138.93 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00785981 | 21.00 | 0.00785981 | 50.2839 | 113504.34 | 0.00 | 162683.87 | 162683.87 | 5.81823373 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61020.9 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 97682.648 | 97682.648 | 2.941721 | 0.00085457 | 2577.433 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 15.77219744 | 54.44 | 82.22 | 27.78 | 1839329.94 | 5.3108 | 5.417655 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 97682.65 | 97682.65 | 1.0000 | 3.50468432 | 2.941721 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.85448325 | 60.00 | 32.22 | 27.78 | 0.000 | 97682.65 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.91 | 0.00782985 | 21.00 | 0.00782985 | 50.0949 | 68388.89 | 0.00 | 98012.37 | 98012.37 | 3.50468432 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61025.9 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21363.318 | 21363.318 | 0.643891 | 0.00018690 | 563.474 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 15.77219744 | 54.44 | 82.22 | 27.78 | 1839329.94 | 1.1615 | 1.184848 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21363.32 | 21363.32 | 1.0000 | 0.76711370 | 0.643891 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.18687656 | 60.00 | 32.22 | 27.78 | 0.000 | 21363.32 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00790538 | 21.00 | 0.00790538 | 50.5715 | 14950.41 | 0.00 | 21433.89 | 21433.89 | 0.76711370 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61000.8 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14177.868 | 14177.868 | 0.427348 | 0.00012403 | 373.941 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 15.77219744 | 54.44 | 82.22 | 27.78 | 1839329.94 | 0.7708 | 0.786330 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14177.87 | 14177.87 | 1.0000 | 0.50913101 | 0.427348 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.12402152 | 60.00 | 32.22 | 27.78 | 0.000 | 14177.87 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00790631 | 21.00 | 0.00790631 | 50.5774 | 9921.63 | 0.00 | 14224.63 | 14224.63 | 0.50913101 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60998.9 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21487.279 | 21487.279 | 0.647635 | 0.00018798 | 566.741 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 15.77219744 | 54.44 | 82.22 | 27.78 | 1839329.94 | 1.1682 | 1.191723 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21487.28 | 21487.28 | 1.0000 | 0.77157451 | 0.647635 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.18796091 | 60.00 | 32.22 | 27.78 | 0.000 | 21487.28 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00790621 | 21.00 | 0.00790621 | 50.5767 | 15037.06 | 0.00 | 21558.24 | 21558.24 | 0.77157451 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61000.4 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13410.024 | 13410.024 | 0.404160 | 0.00011732 | 353.707 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 15.77219744 | 54.44 | 82.22 | 27.78 | 1839329.94 | 0.7291 | 0.743744 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13410.02 | 13410.02 | 1.0000 | 0.48150433 | 0.404160 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.11730477 | 60.00 | 32.22 | 27.78 | 0.000 | 13410.02 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00789641 | 21.00 | 0.00789641 | 50.5149 | 9384.83 | 0.00 | 13454.38 | 13454.38 | 0.48150433 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61002.2 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 163144.850 | -999.000 | 9.471936 | 0.00466592 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0474 | 1004.8586 | 1.1914 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.471936 | 11.28459931 | 4197.9300 | 999.8980 | 55.68579432 | 15.00 | 6.67 | 8.33 | 1947263.00 | 8.3782 | 8.378162 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:40:00 | Sensible | 163144.85 | 156674.40 | 1.0000 | 11.28459931 | 9.471936 | 24.64 | 16.69 | 0.00871857 | 46966.4 | 11.02 | 11.02 | 0.00850000 | 32509.1 | 4.66544609 | 6.67 | 15.00 | 8.33 | 20468.349 | 142676.50 | 26.40 | 0.00840708 | 17.04 | 2.53819000 | 26.7970 | 24.00 | 0.00883280 | 24.00 | 0.00883280 | 47.0210 | 128816.66 | 0.00 | 164702.43 | 152244.28 | 11.28459931 | 24.64 | 16.80 | 0.00871857 | 46966.4 | 11.43 | 11.30 | 0.00828086 | 32371.1 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 53504.146 | 53504.146 | 2.841581 | 0.00046808 | 882.462 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.471936 | 11.28459931 | 4197.9300 | 999.8980 | 15.77219744 | 54.44 | 82.22 | 27.78 | 1839329.94 | 2.9089 | 2.967436 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 53504.15 | 53504.15 | 1.0000 | 3.38537979 | 2.841581 | -2.93 | -3.11 | 0.00287852 | 4241.1 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 0.46802986 | 60.00 | 32.22 | 27.78 | 0.000 | 53504.15 | -4.30 | 0.00265759 | -4.30 | 2.53819000 | 89.3232 | 8.55 | 0.00472682 | 21.58 | 0.00541557 | 33.5643 | 17408.02 | 0.00 | 50040.36 | 50040.36 | 3.38537979 | 2.80 | 0.35 | 0.00287852 | 10027.5 | 17.43 | 8.08 | 0.00287852 | 24808.8 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1522477.426 | -999.000 | 87.235413 | 0.04354266 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0670 | 1004.8586 | 1.1914 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 87.235413 | 103.92982905 | 4197.9300 | 999.8980 | 55.68579432 | 15.00 | 6.67 | 8.33 | 1947263.00 | 78.1855 | 78.185506 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 1522477.43 | 1459570.06 | 1.0000 | 103.92982905 | 87.235413 | 24.70 | 16.72 | 0.00872914 | 47055.2 | 10.92 | 10.92 | 0.00850000 | 32406.1 | 43.53821984 | 6.67 | 15.00 | 8.33 | 199221.938 | 1323255.49 | 26.40 | 0.00840708 | 17.04 | 25.38195000 | 29.0959 | 24.00 | 0.00886297 | 24.00 | 0.00886297 | 47.1794 | 1177391.72 | 0.00 | 1536972.25 | 1413950.82 | 103.92982905 | 24.70 | 16.83 | 0.00872914 | 47055.2 | 11.38 | 11.26 | 0.00825981 | 32266.6 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 511863.190 | 511863.190 | 26.170624 | 0.00447800 | 8412.961 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 87.235413 | 103.92982905 | 4197.9300 | 999.8980 | 15.77219744 | 54.44 | 82.22 | 27.78 | 1839329.94 | 27.8288 | 28.388851 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 511863.19 | 511863.19 | 1.0000 | 31.17894871 | 26.170624 | -3.54 | -3.57 | 0.00281658 | 3470.9 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 4.47754567 | 60.00 | 32.22 | 27.78 | 0.000 | 511863.19 | -4.30 | 0.00265759 | -4.30 | 25.38195000 | 96.9864 | 21.00 | 0.00793351 | 21.00 | 0.00792335 | 50.6845 | 511638.34 | 0.00 | 475305.64 | 475305.64 | 31.17894871 | 2.80 | 0.26 | 0.00281658 | 9872.3 | 17.89 | 8.22 | 0.00281658 | 25116.8 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 165709.342 | -999.000 | 9.633647 | 0.00473927 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0419 | 1004.8586 | 1.1914 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.633647 | 11.47725783 | 4197.9300 | 999.8980 | 55.68579432 | 15.00 | 6.67 | 8.33 | 1947263.00 | 8.5099 | 8.509859 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 165709.34 | 159217.74 | 1.0000 | 11.47725783 | 9.633647 | 24.63 | 16.68 | 0.00871560 | 46947.1 | 11.02 | 11.02 | 0.00850000 | 32509.1 | 4.73878275 | 6.67 | 15.00 | 8.33 | 20817.799 | 144891.54 | 26.40 | 0.00840708 | 17.04 | 2.53819000 | 26.3471 | 24.00 | 0.00882601 | 24.00 | 0.00882601 | 46.9853 | 131145.46 | 0.00 | 167293.74 | 154710.87 | 11.47725783 | 24.63 | 16.80 | 0.00871560 | 46947.1 | 11.43 | 11.30 | 0.00828092 | 32371.0 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 48505.954 | 48505.954 | 2.890094 | 0.00042435 | 808.024 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.633647 | 11.47725783 | 4197.9300 | 999.8980 | 15.77219744 | 54.44 | 82.22 | 27.78 | 1839329.94 | 2.6372 | 2.690227 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 16:50:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 48505.95 | 48505.95 | 1.0000 | 3.44317735 | 2.890094 | -1.22 | -1.45 | 0.00329964 | 7019.4 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 0.42430796 | 60.00 | 32.22 | 27.78 | 0.000 | 48505.95 | -4.30 | 0.00265759 | -4.30 | 2.53819000 | 87.8238 | 21.00 | 0.00793057 | 21.00 | 0.00793057 | 50.7300 | 58559.64 | 0.00 | 46299.73 | 46299.73 | 3.44317735 | 2.80 | 0.96 | 0.00329964 | 11082.9 | 16.10 | 7.94 | 0.00329964 | 24529.7 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 95931.387 | -999.000 | 5.573210 | 0.00274363 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2967 | 1004.8586 | 1.1914 | CAV_BAS FAN | Fan:VariableVolume | 5.573210 | 6.63976692 | 4197.9300 | 999.8980 | 55.68579432 | 15.00 | 6.67 | 8.33 | 1947263.00 | 4.9265 | 4.926473 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 95931.39 | 89784.55 | 1.0000 | 6.63976692 | 5.573210 | 24.29 | 16.68 | 0.00885270 | 46945.8 | 11.01 | 11.01 | 0.00850000 | 32497.8 | 2.74334564 | 6.67 | 15.00 | 8.33 | 12121.110 | 83810.28 | 25.22 | 0.00840522 | 16.63 | 1.20015641 | 21.5344 | 24.00 | 0.00899238 | 24.00 | 0.00899238 | 47.8588 | 70019.52 | 0.00 | 96834.82 | 87300.65 | 6.63976692 | 24.29 | 16.79 | 0.00885270 | 46945.8 | 11.41 | 11.30 | 0.00828337 | 32361.8 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.070992 | 0.00087484 | 2622.625 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | CAV_BAS FAN | Fan:VariableVolume | 5.573210 | 6.63976692 | 4197.9300 | 999.8980 | 15.77219744 | 54.44 | 82.22 | 27.78 | 1839329.94 | 5.4368 | 5.546179 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.070992 | -0.93 | -2.30 | 0.00265759 | 5711.4 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | -4.30 | 0.00265759 | -4.30 | 1.20015641 | 39.0804 | 0.00 | 0.00265759 | 24.44 | 0.00265759 | 13.9177 | 0.00 | 0.00 | 100079.59 | 100079.59 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.02 | 14.59 | 0.00000000 | 40241.1 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 489877.647 | 352948.202 | 24.790042 | 0.01199707 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7161 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | Sensible | 455920.28 | 453221.47 | 0.9307 | -999.0 | -999.0 | 28.40 | 17.83 | 0.00854036 | 50344.1 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 455920.28 | 26.40 | 0.00840708 | 17.04 | 0.33839277 | -999.0000 | 27.00 | 0.00854221 | 27.00 | 0.00854221 | 38.0734 | 371823.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9859.000 | 7196.909 | 0.512002 | 0.00024145 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7829 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | Sensible | 9135.73 | 9030.65 | 0.9266 | -999.0 | -999.0 | 27.83 | 17.67 | 0.00857629 | 49861.7 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9135.73 | 23.08 | 0.00840189 | 15.87 | 0.01563234 | -999.0000 | 27.00 | 0.00858178 | 27.00 | 0.00858178 | 38.2448 | 8839.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 94725.669 | 69141.589 | 4.918563 | 0.00231983 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7885 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | Sensible | 87778.34 | 86729.02 | 0.9267 | -999.0 | -999.0 | 27.83 | 17.67 | 0.00857930 | 49864.3 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 87778.34 | 23.08 | 0.00840189 | 15.87 | 0.15632344 | -999.0000 | 27.00 | 0.00858512 | 27.00 | 0.00858512 | 38.2596 | 84917.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9596.072 | 7004.478 | 0.498289 | 0.00023501 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7868 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:50:00 | Sensible | 8892.24 | 8787.14 | 0.9267 | -999.0 | -999.0 | 27.83 | 17.67 | 0.00857839 | 49863.7 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8892.24 | 23.08 | 0.00840189 | 15.87 | 0.01563234 | -999.0000 | 27.00 | 0.00858411 | 27.00 | 0.00858411 | 38.2551 | 8602.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 489877.647 | 489877.647 | 24.790042 | 0.01199707 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 489877.65 | 489877.65 | 1.0000 | 29.53416179 | 24.790042 | -4.30 | -4.30 | 0.00265759 | 2304.4 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 489877.65 | -4.30 | 0.00265759 | -4.30 | 0.33839277 | 1.3650 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.8820 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9859.000 | 9859.000 | 0.512002 | 0.00024145 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9859.00 | 9859.00 | 1.0000 | 0.60998540 | 0.512002 | -4.30 | -4.30 | 0.00265759 | 2304.4 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9859.00 | -4.30 | 0.00265759 | -4.30 | 0.01563234 | 3.0532 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.8820 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 94725.669 | 94725.669 | 4.918563 | 0.00231983 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 94725.67 | 94725.67 | 1.0000 | 5.85983796 | 4.918563 | -4.30 | -4.30 | 0.00265759 | 2304.4 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 94725.67 | -4.30 | 0.00265759 | -4.30 | 0.15632344 | 3.1782 | 0.00 | 0.00650701 | 24.79 | 0.00650701 | 33.1680 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9596.072 | 9596.072 | 0.498289 | 0.00023501 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9596.07 | 9596.07 | 1.0000 | 0.59364751 | 0.498289 | -4.30 | -4.30 | 0.00265759 | 2304.4 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9596.07 | -4.30 | 0.00265759 | -4.30 | 0.01563234 | 3.1372 | 0.00 | 0.00298298 | 23.68 | 0.00298298 | 16.3422 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17946.392 | 17946.392 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 24.790042 | 29.53416179 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 17946.39 | 17946.39 | 1.0000 | 29.53416179 | 24.790042 | -0.06 | -0.06 | 0.00842025 | 20998.6 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17946.39 | -4.30 | 0.00265759 | -4.30 | 0.33839277 | 1.3650 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.8820 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 829.049 | 829.049 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.512002 | 0.60998540 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 829.05 | 829.05 | 1.0000 | 0.60998540 | 0.512002 | -0.13 | -0.13 | 0.00832162 | 20677.9 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 829.05 | -4.30 | 0.00265759 | -4.30 | 0.01563234 | 3.0532 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.8820 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8290.489 | 8290.489 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.918563 | 5.85983796 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 8290.49 | 8290.49 | 1.0000 | 5.85983796 | 4.918563 | -0.14 | -0.14 | 0.00638467 | 15828.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8290.49 | -4.30 | 0.00265759 | -4.30 | 0.15632344 | 3.1782 | 0.00 | 0.00650701 | 24.79 | 0.00650701 | 33.1680 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 829.049 | 829.049 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.498289 | 0.59364751 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 829.05 | 829.05 | 1.0000 | 0.59364751 | 0.498289 | -0.13 | -1.35 | 0.00297277 | 7298.4 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 829.05 | -4.30 | 0.00265759 | -4.30 | 0.01563234 | 3.1372 | 0.00 | 0.00298298 | 23.68 | 0.00298298 | 16.3422 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:47
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 9.47 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 87.24 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 9.63 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 5.57 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 24.79 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2950.33 | 148.17 | 48.83 |
CORE_BOTTOM | 2469.67 | 389.50 | 0.00 |
CORE_MID | 1058.50 | 2688.33 | 12.50 |
CORE_TOP | 1164.67 | 4138.00 | 372.33 |
PERIMETER_BOT_ZN_3 | 1239.67 | 3286.83 | 16.83 |
PERIMETER_BOT_ZN_2 | 1629.67 | 3529.00 | 109.00 |
PERIMETER_BOT_ZN_1 | 1937.17 | 3183.83 | 135.00 |
PERIMETER_BOT_ZN_4 | 2643.17 | 1988.50 | 112.33 |
PERIMETER_MID_ZN_3 | 1392.50 | 4484.50 | 765.00 |
PERIMETER_MID_ZN_2 | 1637.00 | 3583.50 | 707.67 |
PERIMETER_MID_ZN_1 | 1954.33 | 3758.83 | 474.83 |
PERIMETER_MID_ZN_4 | 1723.50 | 4188.50 | 552.67 |
PERIMETER_TOP_ZN_3 | 2271.50 | 4812.17 | 1707.33 |
PERIMETER_TOP_ZN_2 | 2749.50 | 4238.67 | 1573.00 |
PERIMETER_TOP_ZN_1 | 2500.50 | 4139.00 | 1232.00 |
PERIMETER_TOP_ZN_4 | 2346.17 | 4498.83 | 1308.83 |
DATACENTER_BOT_ZN_6 | 5943.00 | 759.50 | 759.50 |
DATACENTER_MID_ZN_6 | 5922.50 | 113.00 | 113.00 |
DATACENTER_TOP_ZN_6 | 5529.00 | 281.00 | 190.33 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5809.33 | 5809.33 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5937.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 804.67 | 0.00 | 394.00 |
CORE_BOTTOM | 0.00 | 1.33 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 2.83 | 0.00 | 0.17 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 20.50 | 0.00 | 20.50 |
PERIMETER_BOT_ZN_1 | 0.00 | 31.00 | 0.00 | 30.83 |
PERIMETER_BOT_ZN_4 | 0.00 | 48.00 | 0.00 | 24.67 |
PERIMETER_MID_ZN_3 | 1.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 1.67 | 19.50 | 0.00 | 19.50 |
PERIMETER_MID_ZN_1 | 0.00 | 27.00 | 0.00 | 26.67 |
PERIMETER_MID_ZN_4 | 0.00 | 23.83 | 0.00 | 12.83 |
PERIMETER_TOP_ZN_3 | 45.00 | 0.00 | 11.67 | 0.00 |
PERIMETER_TOP_ZN_2 | 22.33 | 16.00 | 0.17 | 16.00 |
PERIMETER_TOP_ZN_1 | 16.00 | 21.50 | 0.00 | 21.17 |
PERIMETER_TOP_ZN_4 | 12.67 | 23.00 | 0.00 | 12.67 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 47.17 | 954.00 | 11.83 | 515.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:47
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 1.255 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 1.044 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.768 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.703 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.917 | 0.011 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 1.518 | 0.012 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 1.617 | 0.011 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 2.090 | 0.012 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.718 | 0.026 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 1.326 | 0.029 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 1.538 | 0.027 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 1.533 | 0.027 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.697 | 0.033 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 1.385 | 0.034 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 1.479 | 0.033 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 1.520 | 0.034 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 26.631 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:26:47
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 60.99 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.86 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.79 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.20 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1010.73 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 49556647.48 | 0.00 | 49556647.48 | 0.00 | 49556647.48 | 37848132.68 | 4496.90 | 188.39 | 4074.71 | 0.00 |
CORE_BOTTOM | 43215856.52 | 0.00 | 43215856.52 | 0.00 | 43215856.52 | 33990283.35 | 4188.75 | 74.32 | 4496.93 | 279.72 |
CORE_MID | 0.31E+09 | 0.00 | 0.31E+09 | 0.00 | 0.31E+09 | 0.34E+09 | 5396.93 | 75.89 | 3287.18 | 110.93 |
CORE_TOP | 28603503.69 | 0.00 | 28603503.69 | 0.00 | 28603503.69 | 33990283.35 | 6051.61 | 59.55 | 2648.84 | 196.35 |
PERIMETER_BOT_ZN_3 | 4775429.32 | 0.00 | 4775429.32 | 114807.37 | 4890236.69 | 4267819.30 | 5170.52 | 98.42 | 3491.06 | 279.72 |
PERIMETER_BOT_ZN_2 | 5100289.26 | 0.00 | 5100289.26 | 76538.19 | 5176827.45 | 2750345.05 | 3583.75 | 0.76 | 5175.49 | 279.72 |
PERIMETER_BOT_ZN_1 | 8379670.06 | 0.00 | 8379670.06 | 114807.37 | 8494477.43 | 4267912.63 | 3592.50 | 1.91 | 5165.59 | 279.72 |
PERIMETER_BOT_ZN_4 | 7022488.22 | 0.00 | 7022488.22 | 76538.19 | 7099026.41 | 2750345.05 | 3578.97 | 0.00 | 5181.03 | 279.72 |
PERIMETER_MID_ZN_3 | 36742764.22 | 0.00 | 36742764.22 | 269254.52 | 37012018.74 | 42678193.03 | 5780.12 | 88.47 | 2891.41 | 110.93 |
PERIMETER_MID_ZN_2 | 47973245.04 | 0.00 | 47973245.04 | 179502.89 | 48152747.93 | 27503450.52 | 3840.88 | 4.82 | 4914.30 | 1019.93 |
PERIMETER_MID_ZN_1 | 78329469.90 | 0.00 | 78329469.90 | 269254.52 | 78598724.42 | 42679126.28 | 3868.89 | 5.62 | 4885.50 | 110.93 |
PERIMETER_MID_ZN_4 | 50692348.22 | 0.00 | 50692348.22 | 179502.89 | 50871851.11 | 27503450.52 | 3830.66 | 4.07 | 4925.27 | 110.93 |
PERIMETER_TOP_ZN_3 | 3573952.71 | 0.00 | 3573952.71 | 334307.04 | 3908259.75 | 4267819.30 | 5996.54 | 64.41 | 2699.05 | 196.35 |
PERIMETER_TOP_ZN_2 | 4558819.09 | 0.00 | 4558819.09 | 222871.21 | 4781690.30 | 2750345.05 | 3988.19 | 2.91 | 4768.90 | 196.35 |
PERIMETER_TOP_ZN_1 | 7533327.39 | 0.00 | 7533327.39 | 334307.04 | 7867634.43 | 4267912.63 | 4005.79 | 8.34 | 4745.87 | 196.35 |
PERIMETER_TOP_ZN_4 | 5028802.48 | 0.00 | 5028802.48 | 222871.21 | 5251673.69 | 2750345.05 | 3963.14 | 6.09 | 4790.78 | 196.35 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.41E+09 | 0.00 | 0.41E+09 | 0.00 | 0.41E+09 | 10671554.30 | 2.50 | 7.17 | 8750.33 | 2815.50 |
Total Facility | 0.59E+10 | 0.00 | 0.59E+10 | 10472195.81 | 0.59E+10 | 0.50E+10 | 6386.18 | 4401.20 | 8757.50 | 3724.50 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.3163 | 0.0000 | 2.3163 | 0.0000 | 2.3163 | 1.2002 | 1679.90 | 188.39 | 4074.71 |
CORE_BOTTOM | 1.9466 | 0.0000 | 1.9466 | 0.0000 | 1.9466 | 1.0778 | 1584.04 | 71.47 | 4287.49 |
CORE_MID | 14.3277 | 0.0000 | 14.3277 | 0.0000 | 14.3277 | 10.7782 | 2659.97 | 75.45 | 3207.58 |
CORE_TOP | 1.3133 | 0.0000 | 1.3133 | 0.0000 | 1.3133 | 1.0778 | 3283.68 | 59.13 | 2600.18 |
PERIMETER_BOT_ZN_3 | 0.2149 | 0.0000 | 0.2149 | 0.0027 | 0.2176 | 0.1353 | 2560.42 | 95.17 | 3287.41 |
PERIMETER_BOT_ZN_2 | 0.2295 | 0.0000 | 0.2295 | 0.0018 | 0.2312 | 0.0872 | 1046.47 | 0.76 | 4895.77 |
PERIMETER_BOT_ZN_1 | 0.3792 | 0.0000 | 0.3792 | 0.0027 | 0.3818 | 0.1353 | 1053.44 | 1.50 | 4888.06 |
PERIMETER_BOT_ZN_4 | 0.3156 | 0.0000 | 0.3156 | 0.0018 | 0.3173 | 0.0872 | 1041.69 | 0.00 | 4901.31 |
PERIMETER_MID_ZN_3 | 1.6856 | 0.0000 | 1.6856 | 0.0062 | 1.6918 | 1.3533 | 3043.45 | 87.76 | 2811.79 |
PERIMETER_MID_ZN_2 | 2.0077 | 0.0000 | 2.0077 | 0.0044 | 2.0121 | 0.8721 | 1123.87 | 3.83 | 3906.30 |
PERIMETER_MID_ZN_1 | 3.6103 | 0.0000 | 3.6103 | 0.0062 | 3.6166 | 1.3533 | 1142.94 | 5.08 | 4794.99 |
PERIMETER_MID_ZN_4 | 2.3203 | 0.0000 | 2.3203 | 0.0042 | 2.3245 | 0.8721 | 1118.67 | 1.52 | 4822.81 |
PERIMETER_TOP_ZN_3 | 0.1639 | 0.0000 | 0.1639 | 0.0077 | 0.1716 | 0.1353 | 3230.20 | 63.96 | 2648.83 |
PERIMETER_TOP_ZN_2 | 0.2097 | 0.0000 | 0.2097 | 0.0052 | 0.2148 | 0.0872 | 1248.78 | 1.97 | 4692.24 |
PERIMETER_TOP_ZN_1 | 0.3472 | 0.0000 | 0.3472 | 0.0077 | 0.3549 | 0.1353 | 1260.59 | 5.07 | 4677.34 |
PERIMETER_TOP_ZN_4 | 0.2303 | 0.0000 | 0.2303 | 0.0052 | 0.2354 | 0.0872 | 1227.79 | 4.93 | 4710.28 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 13.7222 | 0.0000 | 13.7222 | 0.0000 | 13.7222 | 0.3384 | 1.00 | 7.17 | 5934.83 |
Total Facility | 262.0696 | 0.0000 | 262.0696 | 0.2447 | 262.3143 | 158.4706 | 3569.18 | 4386.66 | 5942.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 97217765.50 | 0.00 | 97217765.50 | 48026705.38 | 3584.40 | 1.79 | 5173.81 | 279.72 |
VAV_MID WITH REHEAT | 0.75E+09 | 0.00 | 0.75E+09 | 0.48E+09 | 3861.70 | 6.98 | 4891.32 | 110.93 |
VAV_TOP WITH REHEAT | 69972543.03 | 0.00 | 69972543.03 | 48026705.38 | 4007.66 | 8.71 | 4743.63 | 196.27 |
CAV_BAS | 70339086.97 | 0.00 | 70339086.97 | 37848132.68 | 4494.13 | 0.17 | 4265.70 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.59E+09 | 0.00 | 0.59E+09 | 10671554.30 | 2.50 | 0.00 | 8757.50 | 2815.50 |
AIRLOOP DATACENTER BOT | 346745.77 | 0.00 | 346745.77 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3467457.73 | 0.00 | 3467457.73 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 346745.77 | 0.00 | 346745.77 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 4.3798 | 0.0000 | 4.3798 | 1.5229 | 1047.12 | 1.71 | 4894.17 |
VAV_MID WITH REHEAT | 34.2769 | 0.0000 | 34.2769 | 15.2292 | 1137.61 | 5.51 | 4799.88 |
VAV_TOP WITH REHEAT | 3.2138 | 0.0000 | 3.2138 | 1.5229 | 1260.52 | 5.46 | 4677.02 |
CAV_BAS | 3.2877 | 0.0000 | 3.2877 | 1.2002 | 1677.13 | 0.17 | 4265.70 |
AIRLOOP DATACENTER BASEMENT | 19.4768 | 0.0000 | 19.4768 | 0.3384 | 1.00 | 0.00 | 5942.00 |
AIRLOOP DATACENTER BOT | 0.0162 | 0.0000 | 0.0162 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1621 | 0.0000 | 0.1621 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0162 | 0.0000 | 0.0162 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.17 | 4599.28 | 0.00 | 0.00 | 0.00 | 581.58 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.00 | 3895.32 | 0.00 | 0.00 | 0.00 | 1047.18 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.00 | 3270.19 | 0.00 | 0.00 | 0.00 | 1733.64 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 177.72 | 4084.88 | 0.00 | 16.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 7.17 | 8750.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 5.6985 | 0.0000 | 0.0000 | 0.0000 | 2.4351 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 47.2612 | 0.0000 | 0.0000 | 0.0000 | 23.7551 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 4.8882 | 0.0000 | 0.0000 | 0.0000 | 2.3534 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.7104 | 4.7062 | 0.0000 | 0.9800 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4917 | 19.5058 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0222 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2219 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0222 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:47
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1492 |
Defaulted Fields | 1184 |
Fields with Defaults | 3877 |
Autosized Fields | 334 |
Autosizable Fields | 413 |
Autocalculated Fields | 227 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:26:47
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 25957.91 | 294917.39 | 14-MAY-04:50 | 1980898.52 | 14-AUG-15:40 |
Electricity:Building | 17912.96 | 217189.06 | 07-MAY-17:20 | 1104084.83 | 01-DEC-08:10 |
Electricity:Zone:BASEMENT | 640.57 | 14055.89 | 01-JAN-00:10 | 32859.63 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 17912.96 | 217189.06 | 07-MAY-17:20 | 1104084.83 | 01-DEC-08:10 |
InteriorLights:Electricity | 3236.57 | 9932.90 | 16-APR-17:20 | 325713.14 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 216.17 | 598.35 | 01-JAN-00:10 | 19402.09 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3236.57 | 9932.90 | 16-APR-17:20 | 325713.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 3236.57 | 9932.90 | 16-APR-17:20 | 325713.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 216.17 | 598.35 | 01-JAN-00:10 | 19402.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3236.57 | 9932.90 | 16-APR-17:20 | 325713.14 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 483.75 | 4990.59 | 01-JAN-00:10 | 34631.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4837.49 | 49905.77 | 01-JAN-00:10 | 346310.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1941.37 | 5373.60 | 01-JAN-00:10 | 174244.37 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1941.37 | 5373.60 | 01-JAN-00:10 | 174244.37 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 483.75 | 4990.58 | 01-JAN-00:10 | 34631.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 50.94 | 617.00 | 02-APR-17:10 | 4348.36 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 14.57 | 57.83 | 01-JAN-10:30 | 2187.81 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 14.57 | 57.83 | 01-JAN-10:30 | 2187.81 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 32.66 | 397.62 | 16-APR-17:10 | 2802.25 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 9.23 | 37.27 | 01-JAN-08:40 | 1409.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 9.23 | 37.27 | 01-JAN-08:40 | 1409.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 50.56 | 617.01 | 02-APR-17:10 | 4348.44 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 14.19 | 57.83 | 01-JAN-08:40 | 2187.86 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 14.19 | 57.83 | 01-JAN-08:40 | 2187.86 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 32.72 | 397.61 | 12-MAR-17:10 | 2802.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 9.28 | 37.27 | 01-JAN-10:20 | 1409.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 9.28 | 37.27 | 01-JAN-10:20 | 1409.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 509.02 | 6169.98 | 02-APR-17:10 | 43483.64 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 145.37 | 578.27 | 01-JAN-10:20 | 21878.12 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 145.37 | 578.27 | 01-JAN-10:20 | 21878.12 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 326.45 | 3976.17 | 02-APR-17:10 | 28022.51 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 92.10 | 372.66 | 01-JAN-08:40 | 14099.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 92.10 | 372.66 | 01-JAN-08:40 | 14099.09 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 505.39 | 6170.07 | 02-APR-17:10 | 43484.45 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 141.73 | 578.28 | 01-JAN-08:40 | 21878.60 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 141.73 | 578.28 | 01-JAN-08:40 | 21878.60 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 326.95 | 3976.14 | 12-MAR-17:10 | 28022.42 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 92.60 | 372.66 | 01-JAN-10:10 | 14099.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 92.60 | 372.66 | 01-JAN-10:10 | 14099.09 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 50.90 | 617.00 | 02-APR-17:10 | 4348.36 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 14.53 | 57.83 | 01-JAN-10:20 | 2187.81 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 14.53 | 57.83 | 01-JAN-10:20 | 2187.81 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 32.64 | 397.62 | 02-APR-17:10 | 2802.25 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 9.21 | 37.27 | 01-JAN-08:40 | 1409.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 9.21 | 37.27 | 01-JAN-08:40 | 1409.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 50.54 | 617.01 | 02-APR-17:10 | 4348.44 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 14.17 | 57.83 | 01-JAN-08:40 | 2187.86 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 14.17 | 57.83 | 01-JAN-08:40 | 2187.86 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 32.69 | 397.61 | 12-MAR-17:10 | 2802.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 9.26 | 37.27 | 01-JAN-10:10 | 1409.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 9.26 | 37.27 | 01-JAN-10:10 | 1409.91 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7557.51 | 95212.03 | 01-JAN-00:10 | 385103.08 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 62.65 | 303.90 | 01-JAN-00:10 | 5470.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 62.65 | 303.90 | 01-JAN-00:10 | 5470.56 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 159.04 | 1973.61 | 01-JAN-00:10 | 8244.54 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1590.36 | 19736.13 | 01-JAN-00:10 | 82445.36 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 51.55 | 250.08 | 01-JAN-00:10 | 4501.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 51.55 | 250.08 | 01-JAN-00:10 | 4501.14 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 159.04 | 1973.61 | 01-JAN-00:10 | 8244.54 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 1031.20 | 3952.98 | 10-JAN-05:00 | 357986.75 | 13-JUN-16:00 |
HeatRejection:Electricity | 200.04 | 90.68 | 10-JAN-08:00 | 78170.05 | 22-MAY-14:10 |
General:HeatRejection:Electricity | 200.04 | 90.68 | 10-JAN-08:00 | 78170.05 | 22-MAY-14:10 |
Electricity:HVAC | 4145.21 | 52065.73 | 29-JAN-01:30 | 411650.10 | 14-AUG-16:50 |
ExteriorEquipment:Electricity | 2566.61 | 20217.42 | 01-JAN-00:10 | 233439.18 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 55.02 | 979.82 | 01-JAN-00:10 | 3454.84 | 01-DEC-08:20 |
ElectricityPurchased:Facility | 25957.91 | 294917.39 | 14-MAY-04:50 | 1980898.52 | 14-AUG-15:40 |
ElectricityPurchased:Plant | 25957.91 | 294917.39 | 14-MAY-04:50 | 1980898.52 | 14-AUG-15:40 |
Cogeneration:ElectricityPurchased | 25957.91 | 294917.39 | 14-MAY-04:50 | 1980898.52 | 14-AUG-15:40 |
General:Cogeneration:ElectricityPurchased | 25957.91 | 294917.39 | 14-MAY-04:50 | 1980898.52 | 14-AUG-15:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 25957.91 | 294917.39 | 14-MAY-04:50 | 1980898.52 | 14-AUG-15:40 |
ElectricityNet:Plant | 25957.91 | 294917.39 | 14-MAY-04:50 | 1980898.52 | 14-AUG-15:40 |
Cogeneration:ElectricityNet | 25957.91 | 294917.39 | 14-MAY-04:50 | 1980898.52 | 14-AUG-15:40 |
General:Cogeneration:ElectricityNet | 25957.91 | 294917.39 | 14-MAY-04:50 | 1980898.52 | 14-AUG-15:40 |
Fans:Electricity | 2409.22 | 47525.86 | 09-JAN-04:30 | 247462.67 | 28-APR-14:50 |
General:Fans:Electricity | 2409.22 | 47525.86 | 09-JAN-04:30 | 247462.67 | 28-APR-14:50 |
ExteriorLights:Electricity | 356.94 | 0.00 | 01-JAN-08:20 | 40855.88 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 356.94 | 0.00 | 01-JAN-08:20 | 40855.88 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 2505.76 | 19200.00 | 01-JAN-00:10 | 229608.34 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 699.34 | 1861.28 | 02-JAN-07:10 | 323082.37 | 14-AUG-16:00 |
General:Cooling:Electricity | 699.34 | 1861.28 | 02-JAN-07:10 | 323082.37 | 14-AUG-16:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1143.93 | 0.00 | 17-JAN-11:30 | 100000.00 | 20-FEB-15:40 |
General:Humidifier:Electricity | 1143.93 | 0.00 | 17-JAN-11:30 | 100000.00 | 20-FEB-15:40 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 457.39 | 0.00 | 01-JAN-00:10 | 52812.29 | 15-FEB-13:00 |
Water Heater:WaterSystems:Electricity | 457.39 | 0.00 | 01-JAN-00:10 | 52812.29 | 15-FEB-13:00 |
Pumps:Electricity | 211.47 | 3773.04 | 01-JAN-00:40 | 41298.31 | 21-JUL-17:30 |
General:Pumps:Electricity | 211.47 | 3773.04 | 01-JAN-00:40 | 41298.31 | 21-JUL-17:30 |
WIRED_LTG_ELECTRICITY | 90.95 | 0.00 | 01-JAN-00:10 | 9152.54 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1075.19 | 0.00 | 01-JAN-00:40 | 752112.66 | 10-JAN-08:00 |
NaturalGas:Plant | 1075.19 | 0.00 | 01-JAN-00:40 | 752112.66 | 10-JAN-08:00 |
Heating:NaturalGas | 1075.19 | 0.00 | 01-JAN-00:40 | 752112.66 | 10-JAN-08:00 |
Boiler:Heating:NaturalGas | 1075.19 | 0.00 | 01-JAN-00:40 | 752112.66 | 10-JAN-08:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 3887.73 | 4880.05 | 09-JAN-08:00 | 1949490.90 | 14-AUG-15:50 |
PlantLoopCoolingDemand:HVAC | 3887.73 | 4880.05 | 09-JAN-08:00 | 1949490.90 | 14-AUG-15:50 |
CoolingCoils:PlantLoopCoolingDemand | 3887.73 | 4880.05 | 09-JAN-08:00 | 1949490.90 | 14-AUG-15:50 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 3592.76 | 0.00 | 29-JAN-01:30 | 0.00 | 21-JUL-16:20 |
Water:HVAC | 425.54 | 0.00 | 17-JAN-11:30 | 0.00 | 04-MAR-05:20 |
Humidifier:Water | 425.54 | 0.00 | 17-JAN-11:30 | 0.00 | 04-MAR-05:20 |
General:Humidifier:Water | 425.54 | 0.00 | 17-JAN-11:30 | 0.00 | 04-MAR-05:20 |
MainsWater:Facility | 3592.76 | 0.00 | 29-JAN-01:30 | 0.00 | 21-JUL-16:20 |
MainsWater:HVAC | 425.54 | 0.00 | 17-JAN-11:30 | 0.00 | 04-MAR-05:20 |
Humidifier:MainsWater | 425.54 | 0.00 | 17-JAN-11:30 | 0.00 | 04-MAR-05:20 |
General:Humidifier:MainsWater | 425.54 | 0.00 | 17-JAN-11:30 | 0.00 | 04-MAR-05:20 |
Water:Plant | 3167.22 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-16:20 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 3167.22 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-16:20 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 887.05 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-16:20 |
General:HeatRejection:Water | 887.05 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-16:20 |
HeatRejection:MainsWater | 887.05 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-16:20 |
General:HeatRejection:MainsWater | 887.05 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-16:20 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 27226.32 | 96591.52 | 15-JAN-06:00 | 7725280.94 | 13-JUN-16:00 |
EnergyTransfer:Building | 17769.46 | 88268.22 | 15-JAN-06:00 | 1573951.41 | 14-AUG-15:30 |
EnergyTransfer:Zone:BASEMENT | 634.10 | 0.00 | 01-JAN-00:10 | 110626.48 | 02-JAN-07:10 |
Heating:EnergyTransfer | 167.82 | 0.00 | 06-JAN-22:10 | 348457.33 | 26-DEC-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 167.82 | 0.00 | 06-JAN-22:10 | 348457.33 | 26-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 17601.64 | 87697.29 | 15-JAN-06:00 | 1573951.41 | 14-AUG-15:30 |
Cooling:EnergyTransfer:Zone:BASEMENT | 634.10 | 0.00 | 01-JAN-00:10 | 110626.48 | 02-JAN-07:10 |
General:Cooling:EnergyTransfer | 17601.64 | 87697.29 | 15-JAN-06:00 | 1573951.41 | 14-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 634.10 | 0.00 | 01-JAN-00:10 | 110626.48 | 02-JAN-07:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 604.48 | 0.00 | 01-JAN-00:10 | 54451.36 | 24-JUL-09:30 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 604.48 | 0.00 | 01-JAN-00:10 | 54451.36 | 24-JUL-09:30 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 604.48 | 0.00 | 01-JAN-00:10 | 54451.36 | 24-JUL-09:30 |
EnergyTransfer:Zone:CORE_MID | 4166.98 | 0.00 | 01-JAN-00:10 | 420478.96 | 02-SEP-05:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4166.98 | 0.00 | 01-JAN-00:10 | 420478.96 | 02-SEP-05:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4166.98 | 0.00 | 01-JAN-00:10 | 420478.96 | 02-SEP-05:10 |
EnergyTransfer:Zone:CORE_TOP | 355.01 | 0.00 | 01-JAN-00:40 | 63543.50 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 4.85 | 0.00 | 01-JAN-00:10 | 63543.50 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 4.85 | 0.00 | 01-JAN-00:10 | 63543.50 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 350.16 | 0.00 | 01-JAN-00:40 | 47231.72 | 13-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 350.16 | 0.00 | 01-JAN-00:40 | 47231.72 | 13-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 60.37 | 0.00 | 01-JAN-00:10 | 9876.16 | 10-JUL-14:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 763.85 | 10-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 763.85 | 10-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 60.37 | 0.00 | 01-JAN-00:10 | 9876.16 | 10-JUL-14:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 60.37 | 0.00 | 01-JAN-00:10 | 9876.16 | 10-JUL-14:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 62.40 | 0.00 | 01-JAN-00:10 | 14115.13 | 13-JUN-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 1119.16 | 10-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 1119.16 | 10-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 62.39 | 0.00 | 01-JAN-00:10 | 14115.13 | 13-JUN-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 62.39 | 0.00 | 01-JAN-00:10 | 14115.13 | 13-JUN-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 103.69 | 0.00 | 01-JAN-00:10 | 21967.04 | 11-SEP-12:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.03 | 0.00 | 01-JAN-00:10 | 3180.71 | 10-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.03 | 0.00 | 01-JAN-00:10 | 3180.71 | 10-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 103.66 | 0.00 | 01-JAN-00:10 | 21967.04 | 11-SEP-12:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 103.66 | 0.00 | 01-JAN-00:10 | 21967.04 | 11-SEP-12:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 91.14 | 0.00 | 01-JAN-00:10 | 17919.48 | 28-APR-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 91.14 | 0.00 | 01-JAN-00:10 | 17919.48 | 28-APR-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 91.14 | 0.00 | 01-JAN-00:10 | 17919.48 | 28-APR-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 410.15 | 0.00 | 01-JAN-00:10 | 76875.13 | 13-JUN-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 23.69 | 0.00 | 01-JAN-00:10 | 75948.32 | 26-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 23.69 | 0.00 | 01-JAN-00:10 | 75948.32 | 26-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 386.46 | 0.00 | 01-JAN-00:10 | 76875.13 | 13-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 386.46 | 0.00 | 01-JAN-00:10 | 76875.13 | 13-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 518.32 | 0.00 | 01-JAN-00:10 | 146755.13 | 13-JUN-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 15.57 | 0.00 | 01-JAN-00:10 | 53967.44 | 26-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 15.57 | 0.00 | 01-JAN-00:10 | 53967.44 | 26-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 502.74 | 0.00 | 01-JAN-00:10 | 146755.13 | 13-JUN-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 502.74 | 0.00 | 01-JAN-00:10 | 146755.13 | 13-JUN-08:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 910.38 | 0.00 | 01-JAN-00:10 | 235668.10 | 11-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 13.06 | 0.00 | 01-JAN-00:10 | 63036.48 | 11-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 13.06 | 0.00 | 01-JAN-00:10 | 63036.48 | 11-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 897.32 | 0.00 | 01-JAN-00:10 | 235668.10 | 11-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 897.32 | 0.00 | 01-JAN-00:10 | 235668.10 | 11-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 551.42 | 0.00 | 01-JAN-00:10 | 168799.84 | 13-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 8.09 | 0.00 | 01-JAN-00:10 | 38929.89 | 26-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 8.09 | 0.00 | 01-JAN-00:10 | 38929.89 | 26-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 543.33 | 0.00 | 01-JAN-00:10 | 168799.84 | 13-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 543.33 | 0.00 | 01-JAN-00:10 | 168799.84 | 13-JUN-17:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 44.62 | 0.00 | 01-JAN-00:40 | 11533.96 | 26-DEC-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 13.06 | 0.00 | 01-JAN-00:40 | 11533.96 | 26-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 13.06 | 0.00 | 01-JAN-00:40 | 11533.96 | 26-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 31.56 | 0.00 | 01-JAN-00:20 | 8557.74 | 13-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 31.56 | 0.00 | 01-JAN-00:20 | 8557.74 | 13-JUN-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 51.15 | 0.00 | 01-JAN-00:40 | 14643.63 | 13-JUN-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 7.61 | 0.00 | 01-JAN-00:40 | 11513.29 | 26-DEC-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 7.61 | 0.00 | 01-JAN-00:40 | 11513.29 | 26-DEC-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 43.55 | 0.00 | 01-JAN-00:20 | 14643.63 | 13-JUN-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 43.55 | 0.00 | 01-JAN-00:20 | 14643.63 | 13-JUN-08:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 86.84 | 0.00 | 01-JAN-00:40 | 23744.43 | 11-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 8.71 | 0.00 | 01-JAN-00:10 | 16016.39 | 26-DEC-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 8.71 | 0.00 | 01-JAN-00:10 | 16016.39 | 26-DEC-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 78.13 | 0.00 | 01-JAN-00:40 | 23744.43 | 11-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 78.13 | 0.00 | 01-JAN-00:40 | 23744.43 | 11-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 53.24 | 0.00 | 01-JAN-00:40 | 17510.82 | 13-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 4.91 | 0.00 | 01-JAN-00:40 | 9627.92 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 4.91 | 0.00 | 01-JAN-00:40 | 9627.92 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 48.33 | 0.00 | 01-JAN-00:20 | 17510.82 | 13-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 48.33 | 0.00 | 01-JAN-00:20 | 17510.82 | 13-JUN-17:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 56.79 | 0.00 | 01-JAN-00:10 | 8902.13 | 24-JUL-12:10 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.98 | 0.00 | 01-JAN-00:10 | 4180.04 | 17-DEC-12:50 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.98 | 0.00 | 01-JAN-00:10 | 4180.04 | 17-DEC-12:50 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 55.81 | 0.00 | 01-JAN-00:10 | 8902.13 | 24-JUL-12:10 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 55.81 | 0.00 | 01-JAN-00:10 | 8902.13 | 24-JUL-12:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 342.38 | 0.00 | 01-JAN-00:10 | 55067.77 | 24-JUL-15:50 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 37.53 | 0.00 | 01-JAN-00:10 | 42011.15 | 18-DEC-13:40 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 37.53 | 0.00 | 01-JAN-00:10 | 42011.15 | 18-DEC-13:40 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 304.85 | 0.00 | 01-JAN-00:10 | 55067.77 | 24-JUL-15:50 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 304.85 | 0.00 | 01-JAN-00:10 | 55067.77 | 24-JUL-15:50 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 66.47 | 0.00 | 01-JAN-00:40 | 18057.66 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 28.88 | 0.00 | 01-JAN-00:40 | 18057.66 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 28.88 | 0.00 | 01-JAN-00:40 | 18057.66 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 37.59 | 0.00 | 01-JAN-00:10 | 17109.69 | 13-JUN-14:20 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 37.59 | 0.00 | 01-JAN-00:10 | 17109.69 | 13-JUN-14:20 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 138.28 | 800.98 | 14-JAN-18:30 | 8470.29 | 30-APR-18:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 138.28 | 800.98 | 14-JAN-18:30 | 8470.29 | 30-APR-18:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 138.28 | 800.98 | 14-JAN-18:30 | 8470.29 | 30-APR-18:10 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1183.74 | 0.76 | 15-JAN-07:10 | 79622.21 | 30-APR-18:10 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.19 | 0.00 | 01-JAN-12:40 | 2301.84 | 02-JAN-05:00 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.19 | 0.00 | 01-JAN-12:40 | 2301.84 | 02-JAN-05:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1183.55 | 0.00 | 01-JAN-00:10 | 79622.21 | 30-APR-18:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1183.55 | 0.00 | 01-JAN-00:10 | 79622.21 | 30-APR-18:10 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 106.45 | 0.01 | 11-JAN-20:30 | 8071.70 | 30-APR-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.65 | 0.00 | 02-JAN-13:40 | 597.72 | 08-JAN-17:40 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.65 | 0.00 | 02-JAN-13:40 | 597.72 | 08-JAN-17:40 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 105.80 | 0.00 | 01-JAN-00:10 | 8071.70 | 30-APR-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 105.80 | 0.00 | 01-JAN-00:10 | 8071.70 | 30-APR-18:00 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7171.06 | 86755.38 | 15-JAN-06:00 | 368643.11 | 28-AUG-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7171.06 | 86755.38 | 15-JAN-06:00 | 368643.11 | 28-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7171.06 | 86755.38 | 15-JAN-06:00 | 368643.11 | 28-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 1247.47 | 0.00 | 01-JAN-00:40 | 647478.82 | 10-JAN-08:00 |
PlantLoopHeatingDemand:Plant | 452.04 | 0.00 | 01-JAN-00:10 | 52439.48 | 14-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 452.04 | 0.00 | 01-JAN-00:10 | 52439.48 | 14-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 452.04 | 0.00 | 01-JAN-00:10 | 52439.48 | 14-FEB-12:10 |
EnergyTransfer:HVAC | 4146.13 | 6393.07 | 01-JAN-06:00 | 1801059.97 | 14-AUG-15:40 |
HeatingCoils:EnergyTransfer | 795.43 | 0.00 | 01-JAN-00:40 | 630161.49 | 10-JAN-08:00 |
PlantLoopHeatingDemand:HVAC | 795.43 | 0.00 | 01-JAN-00:40 | 630161.49 | 10-JAN-08:00 |
HeatingCoils:PlantLoopHeatingDemand | 795.43 | 0.00 | 01-JAN-00:40 | 630161.49 | 10-JAN-08:00 |
CoolingCoils:EnergyTransfer | 3350.70 | 3005.96 | 09-JAN-08:00 | 1801059.97 | 14-AUG-15:40 |
EnergyTransfer:Plant | 5310.73 | 0.00 | 01-JAN-00:40 | 4633321.92 | 13-JUN-16:00 |
LoopToLoop:EnergyTransfer | 1294.74 | 0.00 | 01-JAN-00:10 | 1462775.86 | 13-JUN-16:00 |
WaterSystems:EnergyTransfer | 452.04 | 0.00 | 01-JAN-00:10 | 52439.48 | 14-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 452.04 | 0.00 | 01-JAN-00:10 | 52439.48 | 14-FEB-12:10 |
Boilers:EnergyTransfer | 791.32 | 0.00 | 01-JAN-00:40 | 628093.41 | 10-JAN-08:00 |
Chillers:EnergyTransfer | 1305.16 | 0.00 | 01-JAN-00:10 | 1464382.51 | 13-JUN-16:00 |
HeatRejection:EnergyTransfer | 1467.47 | 0.00 | 01-JAN-00:10 | 1668727.68 | 13-JUN-16:00 |
General:HeatRejection:EnergyTransfer | 1467.47 | 0.00 | 01-JAN-00:10 | 1668727.68 | 13-JUN-16:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:47
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -634.092 | 0.000 | 0.000 | 92.424 | 216.171 | 424.397 | 0.000 | 0.000 | 0.000 | 0.007 | 0.000 | 0.000 | 0.000 | 0.000 | -98.901 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -604.482 | 0.000 | 0.000 | 83.422 | 194.137 | 289.614 | 0.000 | 0.000 | 0.000 | 37.309 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
CORE_MID | 0.000 | 0.000 | 0.000 | -4166.968 | 0.000 | 0.000 | 843.485 | 1941.366 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1514.011 |
CORE_TOP | 0.000 | 0.000 | 4.847 | -350.156 | 0.000 | 0.000 | 88.089 | 194.137 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -226.530 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.002 | -60.368 | 0.000 | 0.000 | 10.745 | 14.573 | 36.365 | 22.378 | 0.000 | 0.001 | 48.856 | 0.000 | -70.607 | 0.000 | -1.945 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.006 | -62.394 | 0.000 | 0.000 | 7.058 | 9.227 | 23.435 | 52.469 | 0.000 | 0.001 | 15.285 | 0.000 | -43.813 | 0.000 | -1.274 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.033 | -103.660 | 0.000 | 0.000 | 10.878 | 14.192 | 36.366 | 105.907 | 0.000 | 0.001 | 4.743 | 0.000 | -66.528 | 0.000 | -1.931 | -0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -91.142 | 0.000 | 0.000 | 6.858 | 9.281 | 23.435 | 50.070 | 0.000 | 0.000 | 53.572 | 0.000 | -50.662 | 0.000 | -1.412 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 23.689 | -386.456 | 0.000 | 0.000 | 113.472 | 145.369 | 363.654 | 235.855 | 0.000 | 0.016 | 176.952 | 0.000 | -631.490 | 0.000 | -41.060 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 15.575 | -502.745 | 0.000 | 0.000 | 53.950 | 92.100 | 234.352 | 528.160 | 0.000 | 0.012 | 12.304 | 0.000 | -405.825 | 0.000 | -27.882 | -0.006 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 13.058 | -897.316 | 0.000 | 0.000 | 111.528 | 141.729 | 363.660 | 1060.321 | 0.000 | 0.017 | 0.010 | 0.000 | -637.285 | 0.000 | -43.268 | -112.442 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 8.089 | -543.323 | 0.000 | 0.000 | 73.700 | 92.600 | 234.351 | 515.432 | 0.000 | 0.009 | 83.332 | 0.000 | -435.378 | 0.000 | -28.813 | 0.000 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 13.061 | -31.559 | 0.000 | 0.000 | 11.636 | 14.534 | 36.365 | 24.559 | 0.000 | 0.002 | 0.001 | 0.000 | -58.244 | 0.000 | -4.745 | -5.610 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 7.608 | -43.545 | 0.000 | 0.000 | 7.416 | 9.209 | 23.435 | 53.425 | 0.000 | 0.001 | 0.001 | 0.000 | -37.828 | 0.000 | -3.259 | -16.462 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 8.709 | -78.131 | 0.000 | 0.000 | 11.401 | 14.172 | 36.366 | 107.098 | 0.000 | 0.002 | 0.000 | 0.000 | -59.318 | 0.000 | -5.040 | -35.260 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 4.909 | -48.333 | 0.000 | 0.000 | 7.510 | 9.259 | 23.435 | 51.982 | 0.000 | 0.001 | 0.001 | 0.000 | -40.932 | 0.000 | -3.389 | -4.442 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -138.277 | 0.000 | 0.000 | 0.950 | 5.155 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -21.709 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.188 | -1183.553 | 0.000 | 0.000 | 9.502 | 51.551 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -416.494 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.649 | -105.802 | 0.000 | 0.000 | 0.952 | 5.155 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -54.835 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7171.057 | 0.000 | 0.000 | 20.565 | 62.653 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -407.018 |
GROUNDFLOOR_PLENUM | 0.980 | -55.808 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.001 | 58.961 | 0.000 | 0.000 | 0.000 | -4.134 | 0.000 |
MIDFLOOR_PLENUM | 37.536 | -304.848 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.021 | 337.848 | 0.000 | 0.000 | 0.000 | -70.557 | -0.007 |
TOPFLOOR_PLENUM | 28.884 | -37.589 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.001 | 16.170 | 0.000 | 0.000 | 0.000 | -7.466 | -0.006 |
Total Facility | 67.399 | -398.245 | 100.422 | -17203.359 | 0.000 | 0.000 | 1565.542 | 3236.569 | 14676.396 | 2807.656 | 0.000 | 0.087 | 845.350 | 0.000 | -2537.909 | 0.000 | -246.176 | -2913.734 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 02-JAN-07:05 | 0.00 | 0.00 | 0.00 | -117907.04 | 0.00 | 0.00 | 1314.58 | 6467.36 | 13457.54 | 0.00 | 0.00 | 0.00 | 96667.55 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 10-OCT-04:12 | 0.00 | 0.00 | 0.00 | -95644.72 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 89169.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 27-JUN-04:12 | 0.00 | 0.00 | 0.00 | -796618.83 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 731869.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 27-JUN-05:03 | 0.00 | 0.00 | 0.00 | -74417.77 | 0.00 | 0.00 | 846.51 | 537.36 | 7647.36 | 0.00 | 0.00 | 0.00 | 65386.55 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 23-JUL-17:11 | 0.00 | 0.00 | 0.00 | -11232.30 | 0.00 | 0.00 | 0.00 | 57.83 | 559.17 | 2595.78 | 0.00 | 0.00 | 8082.37 | 0.00 | -0.00 | 0.00 | -62.85 | 0.00 |
PERIMETER_BOT_ZN_2 | 23-JUL-08:31 | 0.00 | 0.00 | 0.00 | -25768.68 | 0.00 | 0.00 | 19.21 | 37.27 | 464.11 | 19281.59 | 0.00 | 0.00 | 6025.90 | 0.00 | -0.00 | 0.00 | -59.39 | 0.00 |
PERIMETER_BOT_ZN_1 | 06-AUG-13:02 | 0.00 | 0.00 | 0.00 | -33592.73 | 0.00 | 0.00 | 34.10 | 57.83 | 720.19 | 22385.35 | 0.00 | 0.00 | 10490.85 | 0.00 | -0.00 | 0.00 | -95.59 | 0.00 |
PERIMETER_BOT_ZN_4 | 09-JUL-17:01 | 0.00 | 0.00 | 0.00 | -33511.59 | 0.00 | 0.00 | 0.00 | 37.27 | 360.35 | 20942.14 | 0.00 | 0.00 | 12240.85 | 0.00 | -0.00 | 0.00 | -69.01 | 0.00 |
PERIMETER_MID_ZN_3 | 13-JUN-15:00 | 0.00 | 0.00 | 0.00 | -76876.18 | 0.00 | 0.00 | 11143.73 | 10409.61 | 21605.52 | 54441.19 | 0.00 | 178.50 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -20902.37 |
PERIMETER_MID_ZN_2 | 16-JUL-08:21 | 0.00 | 0.00 | 0.00 | -260210.14 | 0.00 | 0.00 | 204.34 | 372.66 | 4641.14 | 185486.52 | 0.00 | 0.00 | 70862.74 | 0.00 | -0.00 | 0.00 | -1357.26 | 0.00 |
PERIMETER_MID_ZN_1 | 24-SEP-13:01 | 0.00 | 0.00 | 0.00 | -365376.19 | 0.00 | 0.00 | 312.73 | 578.28 | 7201.95 | 256272.36 | 0.00 | 0.00 | 103263.67 | 0.00 | -0.00 | 0.00 | -2252.79 | 0.00 |
PERIMETER_MID_ZN_4 | 25-JUN-17:21 | 0.00 | 0.00 | 0.00 | -291338.90 | 0.00 | 0.00 | 0.00 | 372.66 | 3603.49 | 182978.06 | 0.00 | 0.00 | 104809.97 | 0.00 | -0.00 | 0.00 | -425.28 | 0.00 |
PERIMETER_TOP_ZN_3 | 13-JUN-15:00 | 0.00 | 0.00 | 0.00 | -8558.98 | 0.00 | 0.00 | 1114.35 | 1040.96 | 2160.55 | 5383.52 | 0.00 | 20.88 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1161.29 |
PERIMETER_TOP_ZN_2 | 25-JUN-09:32 | 0.00 | 0.00 | 0.00 | -24580.74 | 0.00 | 0.00 | 22.06 | 37.27 | 464.11 | 14985.20 | 0.00 | 0.00 | 9119.85 | 0.00 | -0.00 | 0.00 | -47.74 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-SEP-13:41 | 0.00 | 0.00 | 0.00 | -38725.98 | 0.00 | 0.00 | 30.41 | 57.83 | 720.19 | 24113.93 | 0.00 | 0.00 | 14146.33 | 0.00 | -0.00 | 0.00 | -342.71 | 0.00 |
PERIMETER_TOP_ZN_4 | 09-JUL-17:11 | 0.00 | 0.00 | 0.00 | -31207.90 | 0.00 | 0.00 | 0.00 | 37.27 | 360.35 | 20618.78 | 0.00 | 0.00 | 10378.31 | 0.00 | -0.00 | 0.00 | -186.81 | 0.00 |
DATACENTER_BOT_ZN_6 | 30-APR-18:02 | 0.00 | 0.00 | 0.00 | -8472.02 | 0.00 | 0.00 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 652.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 30-APR-18:02 | 0.00 | 0.00 | 0.00 | -79622.21 | 0.00 | 0.00 | 0.00 | 250.08 | 77944.22 | 0.00 | 0.00 | 0.00 | 1427.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 30-APR-17:51 | 0.00 | 0.00 | 0.00 | -8071.70 | 0.00 | 0.00 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 252.27 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 28-AUG-16:00 | 0.00 | 0.00 | 0.00 | -368643.12 | 0.00 | 0.00 | 2182.66 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -18642.62 |
GROUNDFLOOR_PLENUM | 24-JUL-05:15 | 0.00 | -10366.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10428.81 | 0.00 | -0.00 | 0.00 | -62.59 | 0.00 |
MIDFLOOR_PLENUM | 30-DEC-05:01 | 0.00 | -74520.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83506.76 | 0.00 | -0.00 | 0.00 | -8986.04 | 0.00 |
TOPFLOOR_PLENUM | 13-JUN-14:20 | 0.00 | -17109.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17116.23 | 0.00 | -0.00 | 0.00 | -6.47 | 0.00 |
Total Facility | 21-AUG-05:02 | 0.00 | 33138.30 | 0.00 | -1584988.82 | 0.00 | 0.00 | 15998.13 | 10917.52 | 616289.16 | 0.00 | 0.00 | 0.00 | 1036504.36 | 0.00 | -127233.16 | 0.00 | -625.48 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 02-JAN-04:01 | 0.00 | 0.00 | 72033.77 | 0.00 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -78508.75 |
PERIMETER_BOT_ZN_3 | 10-JAN-06:01 | 0.00 | 0.00 | 4426.46 | 0.00 | 0.00 | 0.00 | 140.90 | 67.47 | 960.25 | 0.00 | 0.00 | 0.00 | 59.79 | 0.00 | -5591.00 | 0.00 | -63.86 | 0.00 |
PERIMETER_BOT_ZN_2 | 10-JAN-06:01 | 0.00 | 0.00 | 3365.55 | 0.00 | 0.00 | 0.00 | 92.08 | 43.48 | 618.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3688.35 | 0.00 | -42.12 | -389.47 |
PERIMETER_BOT_ZN_1 | 10-JAN-06:03 | 0.00 | 0.00 | 8425.82 | 0.00 | 0.00 | 0.00 | 145.37 | 67.47 | 960.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5338.44 | 0.00 | -63.83 | -4196.66 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 26-DEC-05:11 | 0.00 | 0.00 | 101500.56 | 0.00 | 0.00 | 0.00 | 0.00 | 674.71 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -36070.97 | 0.00 | -5291.63 | -68268.28 |
PERIMETER_MID_ZN_2 | 26-DEC-05:11 | 0.00 | 0.00 | 125865.06 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -24175.39 | 0.00 | -3603.74 | -103325.42 |
PERIMETER_MID_ZN_1 | 11-DEC-05:11 | 0.00 | 0.00 | 176057.16 | 0.00 | 0.00 | 0.00 | 0.00 | 674.72 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -32316.46 | 0.00 | 0.00 | -151871.15 |
PERIMETER_MID_ZN_4 | 26-DEC-05:11 | 0.00 | 0.00 | 111914.42 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -25906.60 | 0.00 | -3765.04 | -87482.23 |
PERIMETER_TOP_ZN_3 | 02-JAN-04:01 | 0.00 | 0.00 | 12487.43 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2891.98 | 0.00 | -36.93 | -10371.55 |
PERIMETER_TOP_ZN_2 | 02-JAN-04:01 | 0.00 | 0.00 | 16855.98 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1922.83 | 0.00 | -25.56 | -15431.54 |
PERIMETER_TOP_ZN_1 | 11-DEC-05:11 | 0.00 | 0.00 | 25095.67 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2532.42 | 0.00 | 0.00 | -23376.30 |
PERIMETER_TOP_ZN_4 | 02-JAN-04:01 | 0.00 | 0.00 | 16867.66 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2004.26 | 0.00 | -25.94 | -15361.40 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 15-JAN-06:25 | 0.00 | 0.00 | 3754.76 | 0.00 | 0.00 | 0.00 | 53.08 | 250.08 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -23543.98 |
DATACENTER_TOP_ZN_6 | 08-JAN-17:40 | 0.00 | 0.00 | 597.72 | 0.00 | 0.00 | 0.00 | 5.77 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2577.10 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 30-APR-14:32 | 11539.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -27.37 | -11512.47 |
MIDFLOOR_PLENUM | 10-SEP-15:51 | 123800.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1614.39 | -122185.69 |
TOPFLOOR_PLENUM | 09-JAN-05:23 | 21661.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -21661.96 |
Total Facility | 26-DEC-05:11 | -724566.21 | 682625.79 | 654638.47 | -682625.79 | 0.00 | 0.00 | 0.00 | 10917.52 | 587299.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -151127.41 | 0.00 | -32448.99 | -344712.81 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:47
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 11.3962 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.4719 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 109.4687 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 87.2354 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 10.8880 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.6336 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.5732 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.5732 | 0.2153 | 1.0000 | Not calculated | 1.2002 | 0.2153 | ||
AIRLOOP DATACENTER BASEMENT | 24.7900 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.7900 | 0.0137 | 1.0000 | Not calculated | 0.3384 | 0.0137 | ||
AIRLOOP DATACENTER BOT | 0.5120 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5120 | 0.0305 | 1.0000 | Not calculated | 0.0156 | 0.0305 | ||
AIRLOOP DATACENTER MID | 4.9186 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.9186 | 0.0318 | 1.0000 | Not calculated | 0.1563 | 0.0318 | ||
AIRLOOP DATACENTER TOP | 0.4983 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4983 | 0.0314 | 1.0000 | Not calculated | 0.0156 | 0.0314 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.6981 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.1055 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 54.7343 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 30.5144 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.4440 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.1385 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 0.0000 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 0.0000 | 1.0000 | 1.0000 | Not calculated | 1.2002 | |||
AIRLOOP DATACENTER BASEMENT | 24.7900 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.7900 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0137 | ||
AIRLOOP DATACENTER BOT | 0.5120 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5120 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0305 | ||
AIRLOOP DATACENTER MID | 4.9186 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.9186 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0318 | ||
AIRLOOP DATACENTER TOP | 0.4983 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4983 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0314 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 5.5732 | 5.5732 | 0.0000 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.8415 | 5.8415 | 1.9218 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 54.8579 | 54.8579 | 18.7614 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2198 | 5.2198 | 1.9313 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8452 | 0.8452 | 0.2417 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3047 | 1.3047 | 0.2609 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8280 | 1.8280 | 0.3656 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5768 | 1.5768 | 0.3154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.6222 | 7.6222 | 2.3553 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.6466 | 13.6466 | 2.7293 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 18.8779 | 18.8779 | 3.7756 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.4641 | 14.4641 | 2.8928 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8453 | 0.8453 | 0.2426 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3477 | 1.3477 | 0.2695 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9701 | 1.9701 | 0.3940 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5052 | 1.5052 | 0.3010 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5120 | 0.5120 | 0.5120 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.9186 | 4.9186 | 4.9186 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4983 | 0.4983 | 0.4983 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.7900 | 24.7900 | 24.7900 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 11.3962 | 9.4719 | 11.3962 | 3.1055 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 109.4687 | 87.2354 | 109.4687 | 30.5144 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 10.8880 | 9.6336 | 10.8880 | 3.1385 | 0.0000 | 1.0000 |
CAV_BAS | 5.5732 | 5.5732 | 5.5732 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.7900 | 24.7900 | 24.7900 | 24.7900 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5120 | 0.5120 | 0.5120 | 0.5120 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.9186 | 4.9186 | 4.9186 | 4.9186 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4983 | 0.4983 | 0.4983 | 0.4983 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 0.0000 | 0.0000 | 0.0000 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9207 | 2.9207 | 1.9218 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 27.4290 | 27.4290 | 18.7614 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6099 | 2.6099 | 1.9313 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4226 | 0.4226 | 0.2417 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6523 | 0.6523 | 0.2609 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9140 | 0.9140 | 0.3656 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7884 | 0.7884 | 0.3154 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.8111 | 3.8111 | 2.3553 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.8233 | 6.8233 | 2.7293 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.4389 | 9.4389 | 3.7756 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.2320 | 7.2320 | 2.8928 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4226 | 0.4226 | 0.2426 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6738 | 0.6738 | 0.2695 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9851 | 0.9851 | 0.3940 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7526 | 0.7526 | 0.3010 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5120 | 0.5120 | 0.5120 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.9186 | 4.9186 | 4.9186 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4983 | 0.4983 | 0.4983 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.7900 | 24.7900 | 24.7900 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.6981 | 3.1055 | 3.1055 | 3.1055 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 54.7343 | 30.5144 | 30.5144 | 30.5144 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.4440 | 3.1385 | 3.1385 | 3.1385 | 0.0000 | 1.0000 |
CAV_BAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.7900 | 24.7900 | 24.7900 | 24.7900 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5120 | 0.5120 | 0.5120 | 0.5120 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.9186 | 4.9186 | 4.9186 | 4.9186 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4983 | 0.4983 | 0.4983 | 0.4983 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:47
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 11.83 |
Number of hours cooling loads not met | 515.17 |
Number of hours not met | 516.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1075.19 | 752112.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 699.34 | 323082.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3236.57 | 325713.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 356.94 | 40855.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 55.02 | 3454.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 2505.76 | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2409.22 | 247462.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 211.47 | 41298.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 200.04 | 78170.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1143.93 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 457.39 | 52812.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 25957.91 |
Natural Gas | 0.00 | 1075.19 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 27033.10 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 69.87 |
Space Heating | 0.00 |
Space Cooling | 15.10 |
Fans (All) | 52.01 |
Service Water Heating | 9.87 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 560.40 |
Subtotal | 560.40 |
Natural Gas [MJ/m2] | |
Space Heating | 23.21 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 23.21 |
Subtotal | 23.21 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 11.97 |
Space Heating | 3.98 |
Space Cooling | 2.59 |
Fans (All) | 8.91 |
Service Water Heating | 1.69 |
Receptacle Equipment | 54.29 |
Miscellaneous | 16.57 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:47
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8291.67 | 437.33 | 0.00 | 31.00 | 0.00 |
CORE_BOTTOM | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8758.33 | 1.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8731.33 | 28.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8725.33 | 34.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8516.83 | 243.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8733.00 | 27.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8726.17 | 33.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8719.83 | 40.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8738.17 | 21.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8730.00 | 30.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8721.33 | 38.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8022.33 | 737.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7972.33 | 787.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7943.50 | 816.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7491.17 | 1268.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8753.67 | 6.33 | 0.00 | 0.00 | 0.00 |
Min | 7491.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1268.83 | 0.00 | 31.00 | 0.00 |
Average | 8560.46 | 198.20 | 0.00 | 1.35 | 0.00 |
Sum | 196890.50 | 4558.50 | 0.00 | 31.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 367020.00 | 1498.00 | 0.00 | 98.00 | 0.00 |
CORE_BOTTOM | 330811.00 | 2.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1709.50 | 558.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1671.00 | 597.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1652.67 | 615.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 85451.33 | 17943.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367020.00 | 17943.67 | 0.00 | 98.00 | 0.00 |
Average | 79408.28 | 922.37 | 0.00 | 4.26 | 0.00 |
Sum | 1826390.50 | 21214.50 | 0.00 | 98.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8249.83 | 479.17 | 0.00 | 31.00 | 0.00 |
CORE_BOTTOM | 8649.17 | 110.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8709.50 | 50.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8752.00 | 8.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8752.67 | 7.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8732.83 | 27.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8719.00 | 41.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8562.50 | 197.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8734.50 | 25.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8721.50 | 38.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8710.67 | 49.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8758.17 | 1.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8735.33 | 24.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8724.83 | 35.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8716.67 | 43.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8630.17 | 129.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8615.67 | 144.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8611.50 | 148.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8021.00 | 739.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8748.50 | 11.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8727.67 | 32.33 | 0.00 | 0.00 | 0.00 |
Min | 8021.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 739.00 | 0.00 | 31.00 | 0.00 |
Average | 8656.67 | 101.98 | 0.00 | 1.35 | 0.00 |
Sum | 199103.50 | 2345.50 | 0.00 | 31.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 366692.67 | 1825.33 | 0.00 | 98.00 | 0.00 |
CORE_BOTTOM | 330706.00 | 107.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330715.00 | 98.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330802.00 | 11.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2162.67 | 105.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2152.83 | 115.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2150.50 | 117.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 92544.50 | 10850.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 366692.67 | 10850.50 | 0.00 | 98.00 | 0.00 |
Average | 79755.44 | 575.21 | 0.00 | 4.26 | 0.00 |
Sum | 1834375.17 | 13229.83 | 0.00 | 98.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:47
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:26:47
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
For: Environment
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
For: Environment
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.472942E+11 | 118486.11 | 02-JAN-07:05 | 1.83 | 1.41 | 0.568501E+10 | 7499.25 | 18-JAN-10:00 | 10.00 | 9.41 |
February | 0.429901E+11 | 104034.98 | 21-FEB-07:05 | 4.00 | 4.00 | 0.515305E+10 | 7499.23 | 22-FEB-10:09 | 8.33 | 8.16 |
March | 0.526607E+11 | 103595.29 | 27-MAR-06:05 | 0.33 | -0.3 | 0.615142E+10 | 7499.32 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.534984E+11 | 106007.30 | 24-APR-06:05 | 7.50 | 4.86 | 0.547238E+10 | 7499.52 | 14-APR-13:00 | 7.50 | 4.86 |
May | 0.537852E+11 | 107048.27 | 30-MAY-06:05 | 8.83 | 7.86 | 0.592324E+10 | 7499.28 | 16-MAY-13:09 | 8.83 | 7.86 |
June | 0.561479E+11 | 112221.32 | 19-JUN-06:11 | 11.33 | 10.03 | 0.590677E+10 | 7499.52 | 08-JUN-13:09 | 11.33 | 10.03 |
July | 0.559654E+11 | 114173.27 | 05-JUL-06:11 | 10.00 | 8.44 | 0.551607E+10 | 7551.60 | 10-JUL-13:00 | 21.00 | 15.44 |
August | 0.628725E+11 | 112791.19 | 07-AUG-06:11 | 12.33 | 10.83 | 0.616579E+10 | 7505.58 | 28-AUG-13:50 | 22.83 | 15.32 |
September | 0.538730E+11 | 113129.77 | 25-SEP-06:11 | 11.33 | 9.54 | 0.547521E+10 | 7499.41 | 19-SEP-13:00 | 11.33 | 9.54 |
October | 0.538951E+11 | 115993.49 | 10-OCT-06:11 | 10.67 | 10.67 | 0.569250E+10 | 7499.44 | 17-OCT-09:09 | 12.33 | 11.88 |
November | 0.517509E+11 | 110038.53 | 24-NOV-07:11 | 11.00 | 10.48 | 0.563450E+10 | 7499.32 | 07-NOV-14:09 | 11.00 | 10.48 |
December | 0.493632E+11 | 106640.78 | 26-DEC-07:05 | 1.83 | 0.22 | 0.548685E+10 | 7499.37 | 04-DEC-14:00 | 1.83 | 0.22 |
Annual Sum or Average | 0.634097E+12 | 0.682628E+11 | ||||||||
Minimum of Months | 0.429901E+11 | 103595.29 | 0.33 | -0.3 | 0.515305E+10 | 7499.23 | 1.83 | 0.22 | ||
Maximum of Months | 0.628725E+11 | 118486.11 | 12.33 | 10.83 | 0.616579E+10 | 7551.60 | 22.83 | 15.44 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.393224E+11 | 95206.69 | 02-JAN-04:01 | 1.17 | 0.70 | 0.506184E+10 | 6734.77 | 10-JAN-10:00 | -2.0 | -2.0 |
February | 0.379972E+11 | 86794.93 | 21-FEB-05:11 | 5.37 | 4.72 | 0.459862E+10 | 6734.81 | 21-FEB-10:09 | 8.17 | 7.45 |
March | 0.488840E+11 | 88737.39 | 20-MAR-04:12 | 5.33 | 4.89 | 0.550019E+10 | 6734.78 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.556869E+11 | 94102.18 | 24-APR-04:12 | 7.00 | 5.73 | 0.488424E+10 | 6735.06 | 14-APR-13:00 | 7.00 | 5.73 |
May | 0.512052E+11 | 92000.91 | 01-MAY-04:12 | 4.67 | 3.91 | 0.528486E+10 | 6734.75 | 04-MAY-09:09 | 9.00 | 8.02 |
June | 0.564172E+11 | 91099.60 | 05-JUN-04:12 | 12.00 | 11.82 | 0.527037E+10 | 6734.99 | 08-JUN-13:09 | 13.50 | 10.04 |
July | 0.607413E+11 | 93761.04 | 05-JUL-04:12 | 7.67 | 6.81 | 0.489789E+10 | 6749.69 | 10-JUL-13:00 | 21.00 | 15.44 |
August | 0.674275E+11 | 93143.03 | 28-AUG-04:12 | 9.00 | 8.43 | 0.549919E+10 | 6734.93 | 08-AUG-09:00 | 9.00 | 8.43 |
September | 0.504053E+11 | 91946.27 | 05-SEP-04:12 | 6.67 | 6.14 | 0.487894E+10 | 6734.92 | 06-SEP-09:09 | 13.33 | 11.45 |
October | 0.472106E+11 | 95648.75 | 10-OCT-04:12 | 10.33 | 10.33 | 0.508025E+10 | 6734.95 | 17-OCT-09:09 | 12.33 | 11.88 |
November | 0.453682E+11 | 94501.13 | 13-NOV-05:11 | 3.33 | 3.18 | 0.503051E+10 | 6734.76 | 10-NOV-10:09 | 3.33 | 3.18 |
December | 0.438157E+11 | 90818.57 | 26-DEC-05:11 | 1.97 | 0.30 | 0.489947E+10 | 6734.82 | 20-DEC-10:20 | 1.97 | 0.30 |
Annual Sum or Average | 0.604482E+12 | 0.608864E+11 | ||||||||
Minimum of Months | 0.379972E+11 | 86794.93 | 1.17 | 0.30 | 0.459862E+10 | 6734.75 | -2.0 | -2.0 | ||
Maximum of Months | 0.674275E+11 | 95648.75 | 12.00 | 11.82 | 0.550019E+10 | 6749.69 | 21.00 | 15.44 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.264816E+11 | 50380.81 | 26-JAN-06:02 | 5.00 | 4.51 | 0.489103E+10 | 6734.77 | 20-JAN-10:09 | 5.00 | 4.51 |
February | 0.252401E+11 | 40708.22 | 10-FEB-06:03 | 5.00 | 4.51 | 0.448145E+10 | 6734.77 | 17-FEB-10:20 | 4.00 | 2.99 |
March | 0.311292E+11 | 71242.08 | 24-MAR-05:02 | 4.00 | 3.12 | 0.540207E+10 | 6734.72 | 29-MAR-09:09 | 7.17 | 6.35 |
April | 0.364199E+11 | 79069.93 | 29-APR-05:02 | 6.17 | 5.65 | 0.485155E+10 | 6734.97 | 14-APR-13:00 | 6.17 | 5.65 |
May | 0.399811E+11 | 79097.65 | 23-MAY-05:02 | 9.67 | 9.01 | 0.525613E+10 | 6734.74 | 04-MAY-09:09 | 9.67 | 9.01 |
June | 0.431547E+11 | 79672.57 | 27-JUN-04:12 | 14.00 | 14.00 | 0.525591E+10 | 6734.94 | 08-JUN-13:09 | 14.00 | 14.00 |
July | 0.430180E+11 | 79514.89 | 15-JUL-05:02 | 8.50 | 7.86 | 0.488099E+10 | 6734.79 | 18-JUL-13:09 | 19.00 | 15.79 |
August | 0.465494E+11 | 79138.43 | 17-AUG-04:12 | 13.07 | 12.82 | 0.548395E+10 | 6734.87 | 08-AUG-09:00 | 13.07 | 12.82 |
September | 0.397623E+11 | 79568.39 | 02-SEP-05:02 | 13.00 | 11.97 | 0.485668E+10 | 6734.88 | 06-SEP-09:09 | 13.33 | 11.45 |
October | 0.324710E+11 | 76186.25 | 05-OCT-05:02 | 4.00 | 4.00 | 0.501800E+10 | 6734.86 | 17-OCT-09:09 | 12.33 | 11.88 |
November | 0.275793E+11 | 65878.82 | 01-NOV-05:02 | 5.00 | 4.51 | 0.491577E+10 | 6734.74 | 10-NOV-10:09 | 11.00 | 9.41 |
December | 0.249115E+11 | 27384.41 | 22-DEC-17:00 | 5.00 | 4.08 | 0.466649E+10 | 6734.72 | 08-DEC-10:30 | 5.00 | 4.08 |
Annual Sum or Average | 0.416698E+12 | 0.599600E+11 | ||||||||
Minimum of Months | 0.249115E+11 | 27384.41 | 4.00 | 3.12 | 0.448145E+10 | 6734.72 | 4.00 | 2.99 | ||
Maximum of Months | 0.465494E+11 | 79672.57 | 14.00 | 14.00 | 0.548395E+10 | 6734.97 | 19.00 | 15.79 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.190684E+11 | 21044.54 | 19-JAN-17:00 | 6.00 | 6.00 | 0.423851E+10 | 6639.24 | 20-JAN-14:00 | 8.00 | 6.49 |
February | 0.186977E+11 | 20871.96 | 09-FEB-17:00 | 6.00 | 4.60 | 0.394585E+10 | 6582.53 | 24-FEB-14:00 | 6.00 | 4.60 |
March | 0.239650E+11 | 26289.47 | 31-MAR-16:00 | 9.00 | 4.96 | 0.487388E+10 | 6734.52 | 31-MAR-13:00 | 9.00 | 4.96 |
April | 0.306862E+11 | 50575.21 | 21-APR-05:02 | 8.00 | 6.97 | 0.469856E+10 | 6734.94 | 14-APR-13:00 | 8.00 | 6.97 |
May | 0.349181E+11 | 69396.50 | 23-MAY-05:02 | 9.67 | 9.01 | 0.514326E+10 | 6734.70 | 22-MAY-13:00 | 9.67 | 9.01 |
June | 0.407023E+11 | 74431.95 | 27-JUN-05:03 | 14.17 | 14.17 | 0.521381E+10 | 6734.89 | 09-JUN-13:00 | 14.17 | 14.17 |
July | 0.414246E+11 | 73969.06 | 24-JUL-05:03 | 13.00 | 13.00 | 0.484789E+10 | 6734.74 | 18-JUL-13:09 | 13.00 | 13.00 |
August | 0.435447E+11 | 71580.05 | 15-AUG-05:03 | 14.50 | 11.07 | 0.544717E+10 | 6734.80 | 08-AUG-09:00 | 14.50 | 11.07 |
September | 0.343889E+11 | 69377.67 | 13-SEP-05:03 | 9.33 | 9.25 | 0.476978E+10 | 6734.84 | 19-SEP-13:00 | 14.00 | 14.00 |
October | 0.245072E+11 | 33658.36 | 05-OCT-16:00 | 16.00 | 9.13 | 0.464167E+10 | 6734.56 | 11-OCT-13:09 | 16.00 | 10.53 |
November | 0.204268E+11 | 25114.94 | 10-NOV-16:40 | 8.33 | 7.19 | 0.434713E+10 | 6734.35 | 10-NOV-14:09 | 8.33 | 7.19 |
December | 0.178286E+11 | 18942.90 | 21-DEC-17:00 | 6.00 | 5.49 | 0.405158E+10 | 6440.02 | 21-DEC-14:00 | 6.00 | 5.49 |
Annual Sum or Average | 0.350159E+12 | 0.562191E+11 | ||||||||
Minimum of Months | 0.178286E+11 | 18942.90 | 6.00 | 4.60 | 0.394585E+10 | 6440.02 | 6.00 | 4.60 | ||
Maximum of Months | 0.435447E+11 | 74431.95 | 16.00 | 14.17 | 0.544717E+10 | 6734.94 | 16.00 | 14.17 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.276821E+10 | 3059.34 | 02-JAN-04:02 | 1.17 | 0.70 | 0.567932E+09 | 845.60 | 17-JAN-14:00 | 10.40 | 7.95 |
February | 0.277247E+10 | 3228.31 | 21-FEB-14:10 | 9.00 | 7.84 | 0.533326E+09 | 845.62 | 07-FEB-14:39 | 9.00 | 7.84 |
March | 0.383365E+10 | 5088.71 | 20-MAR-12:30 | 10.10 | 6.57 | 0.663287E+09 | 845.63 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.565607E+10 | 7319.83 | 28-APR-14:00 | 20.00 | 12.76 | 0.606167E+09 | 845.66 | 14-APR-13:00 | 20.00 | 12.76 |
May | 0.570149E+10 | 7342.81 | 22-MAY-15:00 | 24.00 | 16.08 | 0.656953E+09 | 845.63 | 22-MAY-13:00 | 24.00 | 16.08 |
June | 0.750259E+10 | 11116.41 | 26-JUN-05:02 | 14.33 | 11.96 | 0.660341E+09 | 845.66 | 08-JUN-13:09 | 14.33 | 11.96 |
July | 0.829038E+10 | 11233.30 | 23-JUL-17:11 | 21.00 | 16.54 | 0.614451E+09 | 853.93 | 10-JUL-13:00 | 21.00 | 16.54 |
August | 0.844141E+10 | 8379.65 | 14-AUG-15:20 | 25.33 | 15.98 | 0.689130E+09 | 846.13 | 28-AUG-13:50 | 22.83 | 15.32 |
September | 0.537700E+10 | 6703.78 | 13-SEP-14:20 | 23.00 | 16.22 | 0.605528E+09 | 845.64 | 19-SEP-13:00 | 14.00 | 14.00 |
October | 0.389215E+10 | 5784.05 | 10-OCT-13:10 | 13.00 | 11.87 | 0.618341E+09 | 845.63 | 11-OCT-13:09 | 16.00 | 10.53 |
November | 0.320566E+10 | 3668.48 | 08-NOV-14:30 | 12.00 | 11.73 | 0.597804E+09 | 845.62 | 24-NOV-14:09 | 12.83 | 11.81 |
December | 0.292674E+10 | 2826.96 | 26-DEC-05:12 | 1.97 | 0.30 | 0.560640E+09 | 840.09 | 21-DEC-14:50 | 1.97 | 0.30 |
Annual Sum or Average | 0.603678E+11 | 0.737390E+10 | ||||||||
Minimum of Months | 0.276821E+10 | 2826.96 | 1.17 | 0.30 | 0.533326E+09 | 840.09 | 1.97 | 0.30 | ||
Maximum of Months | 0.844141E+10 | 11233.30 | 25.33 | 16.54 | 0.689130E+09 | 853.93 | 24.00 | 16.54 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.268895E+10 | 4408.28 | 20-JAN-10:05 | 4.33 | 3.91 | 0.350984E+09 | 544.95 | 20-JAN-10:20 | 4.67 | 4.23 |
February | 0.276285E+10 | 5810.65 | 17-FEB-09:45 | 2.67 | 1.90 | 0.327691E+09 | 544.96 | 21-FEB-10:09 | 8.17 | 7.45 |
March | 0.344000E+10 | 5150.80 | 25-MAR-09:30 | 10.00 | 7.02 | 0.403494E+09 | 544.95 | 08-MAR-10:00 | 10.00 | 7.02 |
April | 0.653777E+10 | 22474.04 | 30-APR-08:32 | 17.80 | 12.19 | 0.388694E+09 | 544.98 | 14-APR-13:00 | 17.80 | 12.19 |
May | 0.671227E+10 | 23948.08 | 21-MAY-08:52 | 13.00 | 9.30 | 0.421650E+09 | 545.86 | 23-MAY-09:20 | 19.33 | 14.73 |
June | 0.746527E+10 | 23852.29 | 18-JUN-08:32 | 13.67 | 11.08 | 0.423950E+09 | 545.86 | 13-JUN-09:30 | 13.67 | 11.08 |
July | 0.813142E+10 | 25773.44 | 23-JUL-08:31 | 19.67 | 15.53 | 0.395034E+09 | 546.57 | 10-JUL-13:00 | 19.67 | 15.53 |
August | 0.851835E+10 | 24021.86 | 20-AUG-09:32 | 16.33 | 13.20 | 0.442260E+09 | 545.15 | 14-AUG-09:09 | 16.33 | 13.20 |
September | 0.657549E+10 | 19471.44 | 04-SEP-08:52 | 14.00 | 10.69 | 0.390491E+09 | 544.97 | 07-SEP-09:39 | 13.33 | 10.64 |
October | 0.399567E+10 | 8705.20 | 03-OCT-09:00 | 12.00 | 9.31 | 0.383069E+09 | 544.96 | 11-OCT-13:09 | 16.00 | 10.53 |
November | 0.298152E+10 | 5174.08 | 13-NOV-09:25 | 8.00 | 7.22 | 0.358059E+09 | 544.95 | 13-NOV-10:09 | 8.17 | 7.54 |
December | 0.258443E+10 | 3236.12 | 26-DEC-10:10 | 3.17 | 1.00 | 0.333447E+09 | 544.95 | 08-DEC-10:09 | 3.17 | 1.00 |
Annual Sum or Average | 0.623940E+11 | 0.461882E+10 | ||||||||
Minimum of Months | 0.258443E+10 | 3236.12 | 2.67 | 1.00 | 0.327691E+09 | 544.95 | 3.17 | 1.00 | ||
Maximum of Months | 0.851835E+10 | 25773.44 | 19.67 | 15.53 | 0.442260E+09 | 546.57 | 19.67 | 15.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.517336E+10 | 30885.78 | 15-JAN-12:23 | 9.50 | 6.65 | 0.564978E+09 | 845.65 | 20-JAN-10:00 | 6.00 | 5.49 |
February | 0.578162E+10 | 31143.82 | 19-FEB-14:52 | 6.00 | 4.14 | 0.526289E+09 | 845.64 | 17-FEB-10:00 | 6.00 | 4.14 |
March | 0.557216E+10 | 12610.01 | 28-MAR-12:10 | 11.67 | 7.18 | 0.634120E+09 | 845.66 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.109797E+11 | 32730.11 | 30-APR-12:32 | 22.00 | 13.38 | 0.599362E+09 | 847.06 | 28-APR-13:39 | 22.00 | 13.38 |
May | 0.913385E+10 | 29232.00 | 21-MAY-14:12 | 17.67 | 10.37 | 0.646314E+09 | 845.66 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.100428E+11 | 25806.73 | 11-JUN-12:53 | 18.00 | 14.39 | 0.654959E+09 | 845.70 | 08-JUN-13:09 | 18.00 | 14.39 |
July | 0.117875E+11 | 32581.17 | 23-JUL-12:32 | 21.67 | 16.29 | 0.611585E+09 | 849.05 | 10-JUL-13:00 | 21.67 | 16.29 |
August | 0.142074E+11 | 33591.45 | 06-AUG-13:02 | 17.17 | 13.56 | 0.687169E+09 | 852.58 | 28-AUG-13:50 | 22.83 | 15.32 |
September | 0.124883E+11 | 33083.03 | 17-SEP-13:32 | 15.33 | 11.58 | 0.604437E+09 | 847.19 | 29-SEP-13:00 | 16.00 | 9.47 |
October | 0.831016E+10 | 21598.05 | 01-OCT-13:13 | 12.33 | 9.63 | 0.599663E+09 | 846.83 | 04-OCT-13:50 | 14.00 | 10.28 |
November | 0.560460E+10 | 22820.35 | 11-NOV-13:13 | 9.00 | 7.29 | 0.573138E+09 | 845.64 | 08-NOV-14:00 | 9.00 | 7.29 |
December | 0.457889E+10 | 16194.75 | 18-DEC-13:30 | 8.00 | 5.46 | 0.539491E+09 | 845.65 | 20-DEC-10:20 | 8.33 | 7.62 |
Annual Sum or Average | 0.103660E+12 | 0.724151E+10 | ||||||||
Minimum of Months | 0.457889E+10 | 12610.01 | 6.00 | 4.14 | 0.526289E+09 | 845.64 | 6.00 | 4.14 | ||
Maximum of Months | 0.142074E+11 | 33591.45 | 22.00 | 16.29 | 0.687169E+09 | 852.58 | 23.00 | 16.29 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.378135E+10 | 7822.14 | 30-JAN-16:38 | 7.37 | 6.68 | 0.364767E+09 | 544.95 | 17-JAN-14:00 | 7.37 | 6.68 |
February | 0.444059E+10 | 15210.31 | 19-FEB-16:12 | 5.33 | 4.26 | 0.352167E+09 | 544.95 | 21-FEB-14:09 | 9.00 | 7.84 |
March | 0.579003E+10 | 11274.12 | 23-MAR-16:00 | 10.00 | 6.65 | 0.437621E+09 | 544.96 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.100077E+11 | 29054.84 | 30-APR-15:51 | 24.00 | 13.13 | 0.395631E+09 | 544.99 | 14-APR-13:00 | 24.00 | 13.13 |
May | 0.821952E+10 | 31393.10 | 21-MAY-16:51 | 20.00 | 12.79 | 0.422938E+09 | 544.96 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.106055E+11 | 32087.79 | 11-JUN-16:51 | 14.00 | 12.24 | 0.426825E+09 | 544.99 | 08-JUN-13:09 | 14.00 | 12.24 |
July | 0.124545E+11 | 33510.88 | 09-JUL-17:01 | 21.00 | 15.03 | 0.397521E+09 | 547.28 | 10-JUL-13:00 | 21.00 | 15.44 |
August | 0.133306E+11 | 29597.97 | 20-AUG-16:11 | 23.33 | 14.80 | 0.446094E+09 | 544.97 | 08-AUG-09:00 | 23.33 | 14.80 |
September | 0.753644E+10 | 25558.32 | 17-SEP-15:32 | 16.00 | 11.40 | 0.390602E+09 | 544.97 | 28-SEP-13:00 | 16.00 | 13.03 |
October | 0.563429E+10 | 12328.64 | 03-OCT-15:30 | 14.00 | 8.96 | 0.401862E+09 | 544.96 | 11-OCT-13:09 | 16.00 | 10.53 |
November | 0.480228E+10 | 11127.06 | 06-NOV-05:11 | 8.00 | 7.45 | 0.396900E+09 | 544.96 | 07-NOV-14:09 | 11.00 | 10.91 |
December | 0.454000E+10 | 7688.91 | 18-DEC-14:30 | 8.00 | 5.66 | 0.385735E+09 | 544.96 | 04-DEC-14:00 | 8.00 | 5.66 |
Annual Sum or Average | 0.911427E+11 | 0.481866E+10 | ||||||||
Minimum of Months | 0.378135E+10 | 7688.91 | 5.33 | 4.26 | 0.352167E+09 | 544.95 | 7.37 | 5.66 | ||
Maximum of Months | 0.133306E+11 | 33510.88 | 24.00 | 15.03 | 0.446094E+09 | 547.28 | 24.00 | 15.76 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124273E+10 | 2041.90 | 15-JAN-12:52 | 10.00 | 6.68 | 0.490354E+09 | 747.00 | 19-JAN-14:00 | 9.00 | 7.43 |
February | 0.139749E+10 | 1995.34 | 22-FEB-15:00 | 9.00 | 6.99 | 0.454191E+09 | 737.34 | 22-FEB-14:00 | 9.00 | 6.99 |
March | 0.225174E+10 | 2311.94 | 30-MAR-14:00 | 13.00 | 7.37 | 0.574203E+09 | 822.16 | 30-MAR-13:00 | 13.00 | 7.37 |
April | 0.339476E+10 | 5572.36 | 28-APR-14:00 | 20.00 | 12.76 | 0.573051E+09 | 845.65 | 14-APR-13:00 | 20.00 | 12.76 |
May | 0.414676E+10 | 6015.10 | 22-MAY-15:00 | 24.00 | 16.08 | 0.635799E+09 | 845.62 | 22-MAY-13:00 | 24.00 | 16.08 |
June | 0.556701E+10 | 7687.51 | 13-JUN-15:00 | 26.00 | 17.83 | 0.654001E+09 | 845.65 | 08-JUN-13:09 | 26.00 | 17.83 |
July | 0.585264E+10 | 7518.98 | 10-JUL-15:00 | 23.00 | 16.69 | 0.608525E+09 | 845.63 | 18-JUL-13:09 | 19.00 | 15.79 |
August | 0.564456E+10 | 6560.32 | 10-AUG-15:00 | 21.00 | 15.45 | 0.679787E+09 | 845.63 | 15-AUG-09:09 | 16.00 | 13.59 |
September | 0.397686E+10 | 5789.14 | 13-SEP-15:30 | 23.00 | 16.22 | 0.587025E+09 | 845.63 | 19-SEP-13:00 | 14.00 | 14.00 |
October | 0.251064E+10 | 3136.87 | 06-OCT-15:30 | 17.00 | 9.21 | 0.553509E+09 | 845.60 | 02-OCT-13:30 | 17.00 | 9.21 |
November | 0.170859E+10 | 2347.47 | 11-NOV-13:02 | 9.00 | 7.36 | 0.502107E+09 | 776.81 | 10-NOV-14:00 | 9.00 | 7.36 |
December | 0.951888E+09 | 1832.76 | 21-DEC-14:50 | 8.00 | 6.98 | 0.459617E+09 | 695.90 | 21-DEC-14:50 | 8.00 | 6.98 |
Annual Sum or Average | 0.386457E+11 | 0.677217E+10 | ||||||||
Minimum of Months | 0.951888E+09 | 1832.76 | 8.00 | 6.68 | 0.454191E+09 | 695.90 | 8.00 | 6.98 | ||
Maximum of Months | 0.585264E+10 | 7687.51 | 26.00 | 17.83 | 0.679787E+09 | 845.65 | 26.00 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.130415E+10 | 2716.49 | 15-JAN-12:52 | 10.00 | 6.68 | 0.228500E+09 | 499.67 | 20-JAN-09:00 | 4.00 | 3.60 |
February | 0.153438E+10 | 3902.17 | 17-FEB-09:55 | 3.00 | 2.16 | 0.214680E+09 | 521.20 | 24-FEB-11:30 | 6.00 | 4.60 |
March | 0.226255E+10 | 3264.41 | 25-MAR-09:30 | 10.00 | 7.02 | 0.261491E+09 | 517.84 | 30-MAR-10:39 | 9.67 | 6.89 |
April | 0.557454E+10 | 23513.61 | 30-APR-09:12 | 18.67 | 12.24 | 0.279116E+09 | 521.33 | 28-APR-07:00 | 18.67 | 12.24 |
May | 0.611617E+10 | 23720.52 | 07-MAY-08:32 | 10.67 | 8.56 | 0.301416E+09 | 521.54 | 23-MAY-08:00 | 19.00 | 14.78 |
June | 0.693863E+10 | 25062.57 | 25-JUN-09:22 | 17.00 | 12.48 | 0.307051E+09 | 521.51 | 13-JUN-08:00 | 17.00 | 12.48 |
July | 0.733356E+10 | 26021.55 | 16-JUL-08:21 | 16.00 | 13.59 | 0.288793E+09 | 521.41 | 10-JUL-08:00 | 16.00 | 13.59 |
August | 0.768055E+10 | 25838.09 | 20-AUG-08:41 | 16.83 | 13.42 | 0.320414E+09 | 521.25 | 14-AUG-07:10 | 16.83 | 13.42 |
September | 0.601351E+10 | 23761.36 | 10-SEP-09:12 | 17.33 | 14.10 | 0.282169E+09 | 521.24 | 21-SEP-08:09 | 13.00 | 11.30 |
October | 0.298269E+10 | 9556.52 | 01-OCT-09:43 | 12.83 | 9.13 | 0.257420E+09 | 521.20 | 02-OCT-10:30 | 12.50 | 9.91 |
November | 0.165097E+10 | 3172.52 | 11-NOV-12:22 | 9.00 | 7.22 | 0.229869E+09 | 499.97 | 03-NOV-10:30 | 9.00 | 7.22 |
December | 0.882391E+09 | 2323.63 | 06-DEC-10:00 | 4.00 | 3.12 | 0.215809E+09 | 454.19 | 06-DEC-09:00 | 4.00 | 3.12 |
Annual Sum or Average | 0.502741E+11 | 0.318673E+10 | ||||||||
Minimum of Months | 0.882391E+09 | 2323.63 | 3.00 | 2.16 | 0.214680E+09 | 454.19 | 4.00 | 3.12 | ||
Maximum of Months | 0.768055E+10 | 26021.55 | 18.67 | 14.10 | 0.320414E+09 | 521.54 | 19.00 | 14.78 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.408857E+10 | 32762.30 | 15-JAN-12:52 | 10.00 | 6.68 | 0.538356E+09 | 845.65 | 17-JAN-14:39 | 10.67 | 7.88 |
February | 0.483960E+10 | 23753.68 | 19-FEB-14:23 | 6.00 | 4.14 | 0.502221E+09 | 845.85 | 17-FEB-14:20 | 6.00 | 4.14 |
March | 0.418401E+10 | 11290.13 | 28-MAR-12:10 | 11.67 | 7.18 | 0.592680E+09 | 845.66 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.959022E+10 | 34277.93 | 30-APR-13:12 | 22.33 | 12.98 | 0.582767E+09 | 846.71 | 28-APR-13:39 | 22.33 | 12.98 |
May | 0.845770E+10 | 21227.86 | 28-MAY-14:32 | 12.67 | 8.15 | 0.628377E+09 | 845.66 | 22-MAY-13:00 | 12.67 | 8.15 |
June | 0.894831E+10 | 21754.48 | 25-JUN-13:23 | 24.00 | 14.74 | 0.642791E+09 | 845.69 | 08-JUN-13:09 | 24.00 | 14.74 |
July | 0.101694E+11 | 33408.07 | 30-JUL-13:22 | 17.00 | 12.42 | 0.602902E+09 | 845.66 | 18-JUL-13:09 | 17.00 | 12.42 |
August | 0.124992E+11 | 34820.85 | 20-AUG-13:22 | 23.00 | 14.82 | 0.677092E+09 | 846.62 | 29-AUG-13:00 | 18.00 | 13.90 |
September | 0.124780E+11 | 36537.19 | 24-SEP-13:01 | 19.33 | 14.90 | 0.596454E+09 | 846.83 | 29-SEP-13:00 | 16.00 | 9.47 |
October | 0.762450E+10 | 34979.50 | 01-OCT-13:02 | 12.17 | 9.71 | 0.571913E+09 | 846.55 | 04-OCT-13:00 | 14.00 | 10.28 |
November | 0.423933E+10 | 34304.28 | 11-NOV-13:02 | 9.00 | 7.36 | 0.533661E+09 | 845.64 | 17-NOV-10:09 | 6.17 | 3.87 |
December | 0.261311E+10 | 14864.36 | 18-DEC-13:30 | 8.00 | 5.46 | 0.497791E+09 | 845.64 | 26-DEC-14:00 | 6.00 | 3.37 |
Annual Sum or Average | 0.897320E+11 | 0.696701E+10 | ||||||||
Minimum of Months | 0.261311E+10 | 11290.13 | 6.00 | 4.14 | 0.497791E+09 | 845.64 | 6.00 | 3.37 | ||
Maximum of Months | 0.124992E+11 | 36537.19 | 24.00 | 14.90 | 0.677092E+09 | 846.83 | 24.00 | 14.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.164189E+10 | 4133.51 | 19-JAN-15:40 | 8.33 | 7.46 | 0.317005E+09 | 540.39 | 19-JAN-14:00 | 8.33 | 7.46 |
February | 0.214505E+10 | 7376.09 | 27-FEB-16:30 | 8.00 | 6.72 | 0.298286E+09 | 544.94 | 27-FEB-14:00 | 8.00 | 6.72 |
March | 0.279181E+10 | 7620.64 | 23-MAR-16:40 | 10.00 | 6.65 | 0.361248E+09 | 544.87 | 10-MAR-14:00 | 10.00 | 6.65 |
April | 0.549153E+10 | 25979.20 | 30-APR-17:11 | 24.00 | 12.77 | 0.362605E+09 | 544.98 | 14-APR-13:00 | 24.00 | 12.77 |
May | 0.633811E+10 | 25733.84 | 21-MAY-16:32 | 19.33 | 11.98 | 0.397983E+09 | 544.96 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.766355E+10 | 29184.66 | 25-JUN-17:21 | 21.50 | 17.05 | 0.414617E+09 | 544.97 | 08-JUN-13:09 | 21.50 | 17.05 |
July | 0.823579E+10 | 26353.34 | 09-JUL-17:22 | 21.00 | 15.03 | 0.389167E+09 | 544.96 | 18-JUL-13:09 | 19.00 | 15.79 |
August | 0.777367E+10 | 26483.21 | 20-AUG-16:41 | 22.33 | 14.82 | 0.434322E+09 | 544.96 | 21-AUG-13:00 | 21.00 | 15.01 |
September | 0.570794E+10 | 25868.31 | 10-SEP-16:32 | 19.67 | 16.13 | 0.370485E+09 | 544.96 | 28-SEP-13:00 | 16.00 | 13.03 |
October | 0.333129E+10 | 10951.44 | 01-OCT-15:42 | 12.17 | 9.38 | 0.345896E+09 | 544.93 | 06-OCT-13:00 | 16.00 | 9.11 |
November | 0.207422E+10 | 4345.57 | 10-NOV-15:30 | 11.50 | 8.42 | 0.319110E+09 | 544.93 | 15-NOV-14:00 | 12.00 | 8.90 |
December | 0.113792E+10 | 2654.01 | 21-DEC-14:40 | 8.00 | 6.98 | 0.296054E+09 | 503.14 | 21-DEC-14:50 | 8.00 | 6.98 |
Annual Sum or Average | 0.543328E+11 | 0.430678E+10 | ||||||||
Minimum of Months | 0.113792E+10 | 2654.01 | 8.00 | 6.65 | 0.296054E+09 | 503.14 | 8.00 | 6.65 | ||
Maximum of Months | 0.823579E+10 | 29184.66 | 24.00 | 17.05 | 0.434322E+09 | 544.98 | 24.00 | 17.05 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.500960E+09 | 1901.90 | 19-JAN-15:50 | 8.17 | 7.46 | 0.469720E+09 | 694.61 | 19-JAN-14:00 | 8.17 | 7.46 |
February | 0.677413E+09 | 1832.66 | 03-FEB-15:10 | 8.83 | 5.32 | 0.428683E+09 | 681.56 | 03-FEB-14:00 | 8.83 | 5.32 |
March | 0.139258E+10 | 2202.72 | 30-MAR-15:50 | 12.00 | 5.94 | 0.532983E+09 | 765.75 | 30-MAR-13:00 | 12.00 | 5.94 |
April | 0.284985E+10 | 5808.27 | 28-APR-15:30 | 20.05 | 13.01 | 0.543711E+09 | 845.64 | 14-APR-13:00 | 20.05 | 13.01 |
May | 0.367317E+10 | 6641.47 | 22-MAY-15:10 | 23.83 | 15.94 | 0.606314E+09 | 845.63 | 22-MAY-13:00 | 23.83 | 15.94 |
June | 0.526517E+10 | 8557.74 | 13-JUN-15:00 | 26.00 | 17.83 | 0.641588E+09 | 845.65 | 09-JUN-13:00 | 26.00 | 17.83 |
July | 0.563919E+10 | 8235.85 | 10-JUL-15:00 | 23.00 | 16.69 | 0.600766E+09 | 845.63 | 18-JUL-13:09 | 19.00 | 15.79 |
August | 0.531427E+10 | 7044.34 | 14-AUG-16:00 | 26.00 | 15.86 | 0.667335E+09 | 845.63 | 15-AUG-13:00 | 19.00 | 15.28 |
September | 0.344843E+10 | 6005.55 | 13-SEP-15:30 | 23.00 | 16.22 | 0.564456E+09 | 845.63 | 19-SEP-13:00 | 14.00 | 14.00 |
October | 0.172117E+10 | 2493.53 | 01-OCT-13:31 | 12.67 | 9.47 | 0.508344E+09 | 812.76 | 06-OCT-13:00 | 16.00 | 9.11 |
November | 0.791332E+09 | 2045.06 | 10-NOV-15:40 | 11.33 | 8.41 | 0.471097E+09 | 732.49 | 10-NOV-14:00 | 11.33 | 8.41 |
December | 0.285566E+09 | 1671.71 | 21-DEC-14:50 | 8.00 | 6.98 | 0.448582E+09 | 644.78 | 21-DEC-14:00 | 8.00 | 6.98 |
Annual Sum or Average | 0.315591E+11 | 0.648358E+10 | ||||||||
Minimum of Months | 0.285566E+09 | 1671.71 | 8.00 | 5.32 | 0.428683E+09 | 644.78 | 8.00 | 5.32 | ||
Maximum of Months | 0.563919E+10 | 8557.74 | 26.00 | 17.83 | 0.667335E+09 | 845.65 | 26.00 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.656098E+09 | 2366.84 | 20-JAN-10:40 | 5.33 | 4.86 | 0.302864E+09 | 488.96 | 20-JAN-10:50 | 5.67 | 5.18 |
February | 0.894704E+09 | 2581.46 | 24-FEB-10:40 | 5.67 | 4.28 | 0.281797E+09 | 521.27 | 24-FEB-10:50 | 5.83 | 4.44 |
March | 0.150449E+10 | 2495.13 | 25-MAR-10:00 | 11.00 | 7.91 | 0.342151E+09 | 500.38 | 31-MAR-09:00 | 9.00 | 5.32 |
April | 0.490328E+10 | 22106.36 | 30-APR-09:32 | 19.33 | 12.50 | 0.376067E+09 | 544.98 | 14-APR-13:00 | 19.33 | 12.50 |
May | 0.555683E+10 | 24137.81 | 21-MAY-09:42 | 13.00 | 10.15 | 0.404444E+09 | 545.55 | 23-MAY-09:30 | 19.50 | 14.70 |
June | 0.670780E+10 | 24579.59 | 25-JUN-09:32 | 17.33 | 12.62 | 0.415727E+09 | 545.80 | 13-JUN-09:00 | 17.33 | 12.62 |
July | 0.712351E+10 | 24264.93 | 23-JUL-09:22 | 20.50 | 15.83 | 0.391114E+09 | 545.56 | 10-JUL-09:50 | 20.50 | 15.83 |
August | 0.740377E+10 | 20328.61 | 20-AUG-09:02 | 16.83 | 13.42 | 0.434911E+09 | 544.98 | 23-AUG-09:09 | 16.17 | 12.09 |
September | 0.540936E+10 | 18235.21 | 10-SEP-09:02 | 17.17 | 14.03 | 0.381040E+09 | 544.97 | 07-SEP-09:50 | 17.17 | 14.03 |
October | 0.215524E+10 | 6127.15 | 04-OCT-10:00 | 13.00 | 9.81 | 0.337949E+09 | 544.95 | 03-OCT-09:09 | 13.00 | 9.81 |
November | 0.851203E+09 | 2311.22 | 03-NOV-10:00 | 7.00 | 5.17 | 0.302761E+09 | 480.41 | 03-NOV-09:00 | 7.00 | 5.17 |
December | 0.378980E+09 | 2015.60 | 06-DEC-10:10 | 4.50 | 3.47 | 0.289674E+09 | 438.31 | 06-DEC-10:20 | 5.00 | 3.82 |
Annual Sum or Average | 0.435453E+11 | 0.426050E+10 | ||||||||
Minimum of Months | 0.378980E+09 | 2015.60 | 4.50 | 3.47 | 0.281797E+09 | 438.31 | 5.00 | 3.82 | ||
Maximum of Months | 0.740377E+10 | 24579.59 | 20.50 | 15.83 | 0.434911E+09 | 545.80 | 20.50 | 15.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.268487E+10 | 13806.34 | 11-JAN-13:40 | -1.3 | -2.8 | 0.511802E+09 | 845.64 | 17-JAN-14:39 | 10.67 | 7.88 |
February | 0.343285E+10 | 17811.29 | 17-FEB-13:40 | 6.00 | 3.25 | 0.478672E+09 | 845.64 | 17-FEB-10:00 | 6.00 | 3.25 |
March | 0.295672E+10 | 9092.12 | 28-MAR-12:20 | 11.33 | 7.17 | 0.558036E+09 | 845.65 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.858840E+10 | 35615.36 | 30-APR-13:32 | 22.67 | 12.88 | 0.565301E+09 | 846.77 | 28-APR-13:39 | 22.67 | 12.88 |
May | 0.774644E+10 | 31224.26 | 21-MAY-14:22 | 18.00 | 10.40 | 0.605920E+09 | 845.66 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.866651E+10 | 27243.81 | 11-JUN-14:22 | 17.50 | 14.17 | 0.628509E+09 | 845.69 | 08-JUN-13:09 | 17.50 | 14.17 |
July | 0.994260E+10 | 28996.39 | 09-JUL-14:32 | 20.67 | 15.36 | 0.593815E+09 | 845.67 | 21-JUL-13:09 | 26.17 | 16.40 |
August | 0.121225E+11 | 36026.10 | 13-AUG-13:32 | 21.00 | 15.45 | 0.665716E+09 | 846.21 | 30-AUG-13:20 | 20.00 | 14.96 |
September | 0.115819E+11 | 38734.61 | 10-SEP-13:41 | 21.00 | 15.91 | 0.583395E+09 | 846.71 | 29-SEP-13:00 | 16.00 | 9.47 |
October | 0.610431E+10 | 33615.14 | 01-OCT-13:31 | 12.67 | 9.47 | 0.544321E+09 | 846.14 | 05-OCT-13:00 | 16.00 | 8.75 |
November | 0.273870E+10 | 25051.21 | 11-NOV-13:32 | 9.00 | 7.15 | 0.505715E+09 | 845.63 | 03-NOV-13:00 | 9.00 | 7.15 |
December | 0.156577E+10 | 11858.73 | 18-DEC-13:30 | 8.00 | 5.46 | 0.477600E+09 | 845.64 | 26-DEC-14:00 | 6.00 | 3.37 |
Annual Sum or Average | 0.781316E+11 | 0.671880E+10 | ||||||||
Minimum of Months | 0.156577E+10 | 9092.12 | -1.3 | -2.8 | 0.477600E+09 | 845.63 | 6.00 | 3.25 | ||
Maximum of Months | 0.121225E+11 | 38734.61 | 22.67 | 15.91 | 0.665716E+09 | 846.77 | 26.17 | 16.40 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.927642E+09 | 3436.41 | 19-JAN-15:40 | 8.33 | 7.46 | 0.307822E+09 | 521.18 | 19-JAN-16:10 | 7.67 | 7.22 |
February | 0.140649E+10 | 6436.46 | 27-FEB-16:30 | 8.00 | 6.72 | 0.288760E+09 | 544.56 | 09-FEB-14:00 | 8.00 | 6.72 |
March | 0.203307E+10 | 6923.09 | 23-MAR-16:50 | 10.00 | 6.65 | 0.344707E+09 | 533.59 | 10-MAR-14:00 | 10.00 | 6.65 |
April | 0.504366E+10 | 26801.51 | 30-APR-16:52 | 24.00 | 12.58 | 0.347286E+09 | 544.98 | 14-APR-13:00 | 24.00 | 12.58 |
May | 0.597008E+10 | 29393.49 | 21-MAY-16:21 | 19.00 | 11.58 | 0.382306E+09 | 544.96 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.751990E+10 | 30576.05 | 25-JUN-17:31 | 21.67 | 18.03 | 0.404788E+09 | 544.97 | 09-JUN-13:00 | 21.67 | 18.03 |
July | 0.811275E+10 | 31207.34 | 09-JUL-17:11 | 21.00 | 15.03 | 0.382911E+09 | 544.96 | 18-JUL-13:09 | 19.00 | 15.79 |
August | 0.759245E+10 | 29297.57 | 13-AUG-17:31 | 18.33 | 14.20 | 0.424875E+09 | 544.96 | 21-AUG-13:00 | 21.00 | 15.01 |
September | 0.534336E+10 | 26873.81 | 10-SEP-16:22 | 20.00 | 16.24 | 0.357063E+09 | 544.96 | 28-SEP-13:00 | 16.00 | 13.03 |
October | 0.257306E+10 | 9613.76 | 03-OCT-15:40 | 14.00 | 8.96 | 0.328000E+09 | 544.92 | 04-OCT-13:00 | 14.00 | 10.28 |
November | 0.125149E+10 | 3694.62 | 10-NOV-15:40 | 11.33 | 8.41 | 0.307300E+09 | 542.07 | 15-NOV-14:00 | 12.00 | 8.90 |
December | 0.559791E+09 | 2560.36 | 21-DEC-14:40 | 8.00 | 6.98 | 0.291255E+09 | 476.87 | 21-DEC-14:50 | 8.00 | 6.98 |
Annual Sum or Average | 0.483337E+11 | 0.416707E+10 | ||||||||
Minimum of Months | 0.559791E+09 | 2560.36 | 8.00 | 6.65 | 0.288760E+09 | 476.87 | 7.67 | 6.65 | ||
Maximum of Months | 0.811275E+10 | 31207.34 | 24.00 | 18.03 | 0.424875E+09 | 544.98 | 24.00 | 18.03 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.220664E+10 | 7819.33 | 02-JAN-06:13 | 1.33 | 0.92 | 0.00 | 0.00 | 01-JAN-00:10 | 1.33 | 0.92 |
February | 0.203055E+10 | 4730.95 | 25-FEB-06:10 | 1.00 | 1.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1.00 | 1.00 |
March | 0.312746E+10 | 4917.60 | 15-MAR-05:10 | 1.75 | 1.33 | 0.00 | 0.00 | 01-MAR-00:10 | 1.75 | 1.33 |
April | 0.573176E+10 | 7729.63 | 24-APR-05:15 | 7.00 | 5.00 | 0.00 | 0.00 | 01-APR-00:10 | 7.00 | 5.00 |
May | 0.503606E+10 | 8538.66 | 01-MAY-05:15 | 4.67 | 3.91 | 0.00 | 0.00 | 01-MAY-00:10 | 4.67 | 3.91 |
June | 0.667755E+10 | 8661.14 | 26-JUN-05:15 | 14.67 | 12.18 | 0.00 | 0.00 | 01-JUN-00:10 | 14.67 | 12.18 |
July | 0.771432E+10 | 10366.47 | 24-JUL-05:15 | 13.00 | 13.00 | 0.00 | 0.00 | 01-JUL-00:10 | 13.00 | 13.00 |
August | 0.853510E+10 | 10134.29 | 14-AUG-05:13 | 11.33 | 10.21 | 0.00 | 0.00 | 01-AUG-00:10 | 11.33 | 10.21 |
September | 0.571711E+10 | 7539.53 | 05-SEP-05:15 | 6.67 | 5.99 | 0.00 | 0.00 | 01-SEP-00:10 | 6.67 | 5.99 |
October | 0.394568E+10 | 8159.55 | 10-OCT-05:15 | 11.00 | 11.00 | 0.00 | 0.00 | 01-OCT-00:10 | 11.00 | 11.00 |
November | 0.289794E+10 | 5916.96 | 13-NOV-06:15 | 4.33 | 3.86 | 0.00 | 0.00 | 01-NOV-00:10 | 4.33 | 3.86 |
December | 0.218778E+10 | 4141.62 | 21-DEC-06:10 | 3.00 | 2.55 | 0.00 | 0.00 | 01-DEC-00:10 | 3.00 | 2.55 |
Annual Sum or Average | 0.558079E+11 | 0.00 | ||||||||
Minimum of Months | 0.203055E+10 | 4141.62 | 1.00 | 0.92 | 0.00 | 0.00 | 1.00 | 0.92 | ||
Maximum of Months | 0.853510E+10 | 10366.47 | 14.67 | 13.00 | 0.00 | 0.00 | 14.67 | 13.00 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.773786E+09 | 7106.83 | 09-JAN-05:01 | -2.1 | -2.8 | 0.00 | 0.00 | 01-JAN-00:10 | -2.1 | -2.8 |
February | 0.869051E+09 | 6947.43 | 18-FEB-06:02 | -1.2 | -1.5 | 0.00 | 0.00 | 01-FEB-00:10 | -1.2 | -1.5 |
March | 0.129453E+10 | 4965.49 | 06-MAR-06:02 | 4.00 | 3.61 | 0.00 | 0.00 | 01-MAR-00:10 | 4.00 | 3.61 |
April | 0.275701E+10 | 5756.36 | 29-APR-05:10 | 6.17 | 5.65 | 0.00 | 0.00 | 01-APR-00:10 | 6.17 | 5.65 |
May | 0.308892E+10 | 5604.92 | 02-MAY-05:10 | 4.17 | 3.22 | 0.00 | 0.00 | 01-MAY-00:10 | 4.17 | 3.22 |
June | 0.431656E+10 | 5447.48 | 24-JUN-05:10 | 12.00 | 10.35 | 0.00 | 0.00 | 01-JUN-00:10 | 12.00 | 10.35 |
July | 0.478717E+10 | 5506.78 | 24-JUL-15:50 | 19.83 | 16.14 | 0.00 | 0.00 | 01-JUL-00:10 | 19.83 | 16.14 |
August | 0.511718E+10 | 5556.53 | 21-AUG-05:13 | 11.00 | 9.86 | 0.00 | 0.00 | 01-AUG-00:10 | 11.00 | 9.86 |
September | 0.385288E+10 | 5368.97 | 16-SEP-05:10 | 14.00 | 13.42 | 0.00 | 0.00 | 01-SEP-00:10 | 14.00 | 13.42 |
October | 0.200728E+10 | 4796.25 | 06-OCT-05:10 | 3.00 | 3.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3.00 | 3.00 |
November | 0.103556E+10 | 5863.49 | 27-NOV-05:11 | 4.00 | 3.53 | 0.00 | 0.00 | 01-NOV-00:10 | 4.00 | 3.53 |
December | 0.585077E+09 | 7452.12 | 30-DEC-05:01 | -1.8 | -3.4 | 0.00 | 0.00 | 01-DEC-00:10 | -1.8 | -3.4 |
Annual Sum or Average | 0.304850E+11 | 0.00 | ||||||||
Minimum of Months | 0.585077E+09 | 4796.25 | -2.1 | -3.4 | 0.00 | 0.00 | -2.1 | -3.4 | ||
Maximum of Months | 0.511718E+10 | 7452.12 | 19.83 | 16.14 | 0.00 | 0.00 | 19.83 | 16.14 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9115050.32 | 730.57 | 21-JAN-12:50 | 7.83 | 5.99 | 0.00 | 0.00 | 01-JAN-00:10 | 7.83 | 5.99 |
February | 33304955.92 | 1236.32 | 22-FEB-12:40 | 9.33 | 7.76 | 0.00 | 0.00 | 01-FEB-00:10 | 9.33 | 7.76 |
March | 0.283880E+09 | 3198.04 | 25-MAR-12:30 | 13.00 | 10.05 | 0.00 | 0.00 | 01-MAR-00:10 | 13.00 | 10.05 |
April | 0.398110E+10 | 14290.45 | 28-APR-14:40 | 20.07 | 13.39 | 0.00 | 0.00 | 01-APR-00:10 | 20.07 | 13.39 |
May | 0.474803E+10 | 14933.03 | 22-MAY-14:40 | 23.67 | 15.97 | 0.00 | 0.00 | 01-MAY-00:10 | 23.67 | 15.97 |
June | 0.709041E+10 | 17109.69 | 13-JUN-14:20 | 25.40 | 17.58 | 0.00 | 0.00 | 01-JUN-00:10 | 25.40 | 17.58 |
July | 0.813926E+10 | 16736.90 | 21-JUL-14:40 | 27.00 | 15.95 | 0.00 | 0.00 | 01-JUL-00:10 | 27.00 | 15.95 |
August | 0.770138E+10 | 14795.29 | 14-AUG-14:50 | 24.83 | 16.12 | 0.00 | 0.00 | 01-AUG-00:10 | 24.83 | 16.12 |
September | 0.465699E+10 | 12684.12 | 12-SEP-15:00 | 22.00 | 15.41 | 0.00 | 0.00 | 01-SEP-00:10 | 22.00 | 15.41 |
October | 0.917276E+09 | 5873.92 | 03-OCT-14:40 | 14.00 | 9.11 | 0.00 | 0.00 | 01-OCT-00:10 | 14.00 | 9.11 |
November | 28825284.36 | 1365.70 | 11-NOV-13:38 | 9.00 | 7.15 | 0.00 | 0.00 | 01-NOV-00:10 | 9.00 | 7.15 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 | 3.53 | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 | 3.53 |
Annual Sum or Average | 0.375896E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.00 | 3.53 | 0.00 | 0.00 | 4.00 | 3.53 | ||
Maximum of Months | 0.813926E+10 | 17109.69 | 27.00 | 17.58 | 0.00 | 0.00 | 27.00 | 17.58 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.326058E+10 | 2055.14 | 19-JAN-16:20 | 7.33 | 6.98 | 95230130.50 | 126.83 | 18-JAN-14:00 | 7.33 | 6.98 |
February | 0.783902E+10 | 4279.25 | 27-FEB-17:00 | 8.00 | 6.97 | 86396549.20 | 126.83 | 08-FEB-14:00 | 8.00 | 6.97 |
March | 0.140780E+11 | 7032.97 | 31-MAR-24:00 | 4.30 | 1.71 | 0.103236E+09 | 126.82 | 23-MAR-13:09 | 4.30 | 1.71 |
April | 0.189890E+11 | 8472.02 | 30-APR-18:02 | 24.00 | 13.14 | 91605087.97 | 126.82 | 28-APR-09:30 | 24.00 | 13.14 |
May | 0.432281E+10 | 3383.32 | 31-MAY-24:00 | 9.40 | 7.45 | 99235081.54 | 126.84 | 23-MAY-13:30 | 9.40 | 7.45 |
June | 0.934951E+10 | 5219.52 | 30-JUN-24:00 | 11.00 | 9.86 | 98963647.48 | 126.84 | 27-JUN-09:09 | 11.00 | 9.86 |
July | 0.148144E+11 | 7273.70 | 31-JUL-24:00 | 11.40 | 9.79 | 91885428.83 | 126.83 | 25-JUL-09:09 | 11.40 | 9.79 |
August | 0.198131E+11 | 8243.28 | 13-AUG-18:10 | 17.83 | 13.92 | 0.103238E+09 | 126.83 | 08-AUG-13:00 | 17.83 | 13.92 |
September | 0.420937E+10 | 3247.98 | 30-SEP-24:00 | 7.60 | 5.71 | 91610265.01 | 126.84 | 12-SEP-13:00 | 7.60 | 5.71 |
October | 0.912483E+10 | 5093.90 | 31-OCT-24:00 | 6.60 | 4.32 | 95232117.96 | 126.83 | 10-OCT-13:00 | 6.60 | 4.32 |
November | 0.135870E+11 | 5846.31 | 03-NOV-16:00 | 8.00 | 4.84 | 94301231.99 | 126.83 | 08-NOV-14:00 | 12.00 | 12.00 |
December | 0.188893E+11 | 7550.50 | 26-DEC-15:20 | 5.00 | 2.88 | 91880828.75 | 126.82 | 26-DEC-10:09 | 5.00 | 2.88 |
Annual Sum or Average | 0.138277E+12 | 0.114282E+10 | ||||||||
Minimum of Months | 0.326058E+10 | 2055.14 | 4.30 | 1.71 | 86396549.20 | 126.82 | 4.30 | 1.71 | ||
Maximum of Months | 0.198131E+11 | 8472.02 | 24.00 | 13.92 | 0.103238E+09 | 126.84 | 24.00 | 13.92 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134400E+10 | 1805.95 | 19-JAN-16:30 | 7.00 | 6.74 | 95228987.13 | 126.82 | 18-JAN-14:00 | 7.00 | 6.74 |
February | 0.596517E+10 | 3883.70 | 27-FEB-17:00 | 8.00 | 6.97 | 86396560.51 | 126.82 | 08-FEB-14:00 | 8.00 | 6.97 |
March | 0.118561E+11 | 6286.10 | 31-MAR-23:40 | 4.43 | 1.73 | 0.103236E+09 | 126.82 | 23-MAR-13:09 | 4.43 | 1.73 |
April | 0.173766E+11 | 7962.22 | 30-APR-18:10 | 24.00 | 13.14 | 91605099.03 | 126.82 | 28-APR-09:30 | 24.00 | 13.14 |
May | 0.343478E+10 | 3080.39 | 31-MAY-23:40 | 9.70 | 8.23 | 99234978.12 | 126.84 | 23-MAY-13:00 | 9.70 | 8.23 |
June | 0.847535E+10 | 4727.80 | 30-JUN-24:00 | 11.00 | 9.86 | 98963263.64 | 126.84 | 27-JUN-09:09 | 11.00 | 9.86 |
July | 0.137064E+11 | 6818.37 | 31-JUL-23:50 | 11.38 | 9.85 | 91885758.09 | 126.84 | 24-JUL-13:30 | 11.38 | 9.85 |
August | 0.185222E+11 | 7681.34 | 13-AUG-18:10 | 17.83 | 13.92 | 0.103239E+09 | 126.83 | 08-AUG-13:00 | 17.83 | 13.92 |
September | 0.335771E+10 | 2860.83 | 30-SEP-23:30 | 7.65 | 5.76 | 91609888.70 | 126.84 | 12-SEP-13:00 | 7.65 | 5.76 |
October | 0.741136E+10 | 4355.78 | 31-OCT-24:00 | 6.60 | 4.32 | 95231948.80 | 126.83 | 10-OCT-13:00 | 6.60 | 4.32 |
November | 0.112008E+11 | 5415.95 | 03-NOV-16:00 | 8.00 | 4.84 | 94301129.27 | 126.83 | 08-NOV-14:00 | 12.00 | 12.00 |
December | 0.157048E+11 | 6890.41 | 21-DEC-15:20 | 7.67 | 6.81 | 91880847.32 | 126.82 | 26-DEC-10:09 | 3.17 | 1.00 |
Annual Sum or Average | 0.118355E+12 | 0.114281E+10 | ||||||||
Minimum of Months | 0.134400E+10 | 1805.95 | 4.43 | 1.73 | 86396560.51 | 126.82 | 3.17 | 1.00 | ||
Maximum of Months | 0.185222E+11 | 7962.22 | 24.00 | 13.92 | 0.103239E+09 | 126.84 | 24.00 | 13.92 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.412348E+09 | 1702.76 | 19-JAN-16:40 | 6.67 | 6.49 | 93803491.20 | 127.37 | 04-JAN-10:30 | 6.67 | 6.49 |
February | 0.426131E+10 | 3692.93 | 17-FEB-17:00 | 5.00 | 2.86 | 86396561.60 | 126.82 | 08-FEB-14:00 | 5.00 | 2.86 |
March | 0.103163E+11 | 5832.19 | 31-MAR-23:20 | 4.57 | 1.75 | 0.103236E+09 | 126.82 | 23-MAR-13:09 | 4.57 | 1.75 |
April | 0.165665E+11 | 8071.70 | 30-APR-18:00 | 24.00 | 13.13 | 91605101.44 | 126.82 | 28-APR-09:30 | 24.00 | 13.13 |
May | 0.270939E+10 | 2933.81 | 31-MAY-23:20 | 10.00 | 9.01 | 99235134.66 | 126.84 | 23-MAY-13:00 | 10.00 | 9.01 |
June | 0.810579E+10 | 4486.35 | 30-JUN-23:30 | 11.00 | 10.17 | 98963293.58 | 126.84 | 27-JUN-09:09 | 11.00 | 10.17 |
July | 0.134055E+11 | 6663.57 | 31-JUL-23:20 | 11.33 | 10.03 | 91885816.41 | 126.84 | 24-JUL-13:30 | 11.33 | 10.03 |
August | 0.181958E+11 | 7763.81 | 13-AUG-18:00 | 18.00 | 13.90 | 0.103239E+09 | 126.83 | 08-AUG-13:00 | 18.00 | 13.90 |
September | 0.268567E+10 | 2330.95 | 30-SEP-23:20 | 7.67 | 5.77 | 91609794.13 | 126.84 | 12-SEP-13:00 | 7.67 | 5.77 |
October | 0.596539E+10 | 3912.45 | 03-OCT-16:50 | 13.17 | 8.54 | 95231878.04 | 126.83 | 13-OCT-13:00 | 11.00 | 11.00 |
November | 0.946487E+10 | 5318.00 | 10-NOV-16:20 | 9.67 | 7.83 | 94301138.55 | 126.83 | 08-NOV-14:00 | 9.67 | 7.83 |
December | 0.137129E+11 | 6663.62 | 21-DEC-15:20 | 7.67 | 6.81 | 91880852.76 | 126.82 | 26-DEC-10:09 | 3.17 | 1.00 |
Annual Sum or Average | 0.105802E+12 | 0.114139E+10 | ||||||||
Minimum of Months | 0.412348E+09 | 1702.76 | 4.57 | 1.75 | 86396561.60 | 126.82 | 3.17 | 1.00 | ||
Maximum of Months | 0.181958E+11 | 8071.70 | 24.00 | 13.90 | 0.103239E+09 | 127.37 | 24.00 | 13.90 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.237737E+12 | 92269.19 | 02-JAN-17:00 | 3.00 | 1.77 | 0.206144E+10 | 2745.71 | 25-JAN-14:39 | 11.00 | 9.22 |
February | 0.435547E+12 | 183385.76 | 09-FEB-17:00 | 6.00 | 4.60 | 0.187024E+10 | 2746.01 | 08-FEB-14:30 | 6.00 | 4.60 |
March | 0.728920E+12 | 358819.58 | 31-MAR-24:00 | 4.30 | 1.71 | 0.223479E+10 | 2745.39 | 31-MAR-09:39 | 4.30 | 1.71 |
April | 0.944309E+12 | 368239.87 | 28-APR-16:00 | 20.00 | 12.32 | 0.198310E+10 | 2749.21 | 28-APR-09:09 | 20.00 | 12.32 |
May | 0.241087E+12 | 176117.08 | 31-MAY-24:00 | 9.40 | 7.45 | 0.214808E+10 | 2745.89 | 04-MAY-09:39 | 9.40 | 7.45 |
June | 0.470715E+12 | 267449.38 | 30-JUN-24:00 | 11.00 | 9.86 | 0.214224E+10 | 2749.03 | 26-JUN-13:00 | 11.00 | 9.86 |
July | 0.732668E+12 | 360254.61 | 31-JUL-24:00 | 11.40 | 9.79 | 0.198971E+10 | 2750.34 | 24-JUL-13:00 | 11.40 | 9.79 |
August | 0.978102E+12 | 368643.11 | 28-AUG-16:00 | 24.00 | 15.59 | 0.223763E+10 | 2752.23 | 08-AUG-13:30 | 24.00 | 15.59 |
September | 0.234787E+12 | 175631.97 | 30-SEP-24:00 | 7.60 | 5.71 | 0.198292E+10 | 2745.68 | 25-SEP-09:50 | 7.60 | 5.71 |
October | 0.485614E+12 | 267581.10 | 31-OCT-24:00 | 6.60 | 4.32 | 0.206141E+10 | 2746.11 | 20-OCT-13:30 | 6.60 | 4.32 |
November | 0.706816E+12 | 276045.03 | 15-NOV-17:00 | 8.00 | 6.97 | 0.204132E+10 | 2746.52 | 06-NOV-10:50 | 8.00 | 6.97 |
December | 0.974759E+12 | 367578.20 | 26-DEC-17:00 | 1.00 | 0.17 | 0.198900E+10 | 2745.44 | 08-DEC-10:39 | 1.00 | 0.17 |
Annual Sum or Average | 0.717106E+13 | 0.247419E+11 | ||||||||
Minimum of Months | 0.234787E+12 | 92269.19 | 1.00 | 0.17 | 0.187024E+10 | 2745.39 | 1.00 | 0.17 | ||
Maximum of Months | 0.978102E+12 | 368643.11 | 24.00 | 15.59 | 0.223763E+10 | 2752.23 | 24.00 | 15.59 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.162117E+10 | 72033.79 | 02-JAN-04:01 | 1.17 |
February | 0.714848E+09 | 65373.71 | 13-FEB-05:01 | -1.0 |
March | 0.296736E+09 | 64579.07 | 06-MAR-05:11 | 3.87 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 67528967.16 | 59803.98 | 23-OCT-05:03 | 3.17 |
November | 0.641431E+09 | 66583.51 | 27-NOV-05:11 | 4.00 |
December | 0.150581E+10 | 70076.55 | 26-DEC-05:11 | 1.97 |
Annual Sum or Average | 0.484753E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.162117E+10 | 72033.79 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1531331.15 | 4426.47 | 10-JAN-06:01 | -4.0 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 1531331.15 | |||
Minimum of Months | 0.00 | 0.00 | -4.0 | |
Maximum of Months | 1531331.15 | 4426.47 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5902228.59 | 3365.57 | 10-JAN-06:01 | -4.0 |
February | 112421.18 | 891.04 | 17-FEB-06:01 | -3.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 277740.95 | 2336.56 | 30-DEC-06:01 | -1.0 |
Annual Sum or Average | 6292390.72 | |||
Minimum of Months | 0.00 | 0.00 | -4.0 | |
Maximum of Months | 5902228.59 | 3365.57 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 24728228.79 | 8425.84 | 10-JAN-06:03 | -4.0 |
February | 1547159.79 | 4002.19 | 17-FEB-06:01 | -3.1 |
March | 107952.51 | 462.88 | 06-MAR-06:04 | 4.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 453138.40 | 2453.56 | 27-NOV-06:03 | 4.00 |
December | 5958016.34 | 6913.25 | 26-DEC-06:03 | 1.92 |
Annual Sum or Average | 32794495.82 | |||
Minimum of Months | 0.00 | 0.00 | -4.0 | |
Maximum of Months | 24728228.79 | 8425.84 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.668859E+09 | 9918.75 | 09-JAN-05:01 | -2.1 |
February | 0.348341E+09 | 9643.37 | 13-FEB-05:01 | -1.0 |
March | 0.133618E+09 | 9322.92 | 06-MAR-05:11 | 3.87 |
April | 1022115.51 | 3696.23 | 01-APR-05:02 | 2.17 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 21656111.11 | 8876.73 | 23-OCT-05:03 | 3.17 |
November | 0.265677E+09 | 9638.97 | 27-NOV-05:11 | 4.00 |
December | 0.929690E+09 | 10149.98 | 26-DEC-05:11 | 1.97 |
Annual Sum or Average | 0.236886E+10 | |||
Minimum of Months | 0.00 | 0.00 | -2.1 | |
Maximum of Months | 0.929690E+09 | 10149.98 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.415733E+09 | 12192.48 | 09-JAN-05:01 | -2.1 |
February | 0.210745E+09 | 11442.37 | 17-FEB-05:01 | -2.1 |
March | 94587781.08 | 11149.34 | 06-MAR-05:11 | 3.87 |
April | 1081044.36 | 3182.64 | 01-APR-05:02 | 2.17 |
May | 71182.83 | 474.55 | 05-MAY-05:03 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 17127473.69 | 6405.92 | 21-OCT-05:03 | 7.00 |
November | 0.177958E+09 | 11733.82 | 27-NOV-05:11 | 4.00 |
December | 0.640159E+09 | 12586.24 | 26-DEC-05:11 | 1.97 |
Annual Sum or Average | 0.155746E+10 | |||
Minimum of Months | 0.00 | 0.00 | -2.1 | |
Maximum of Months | 0.640159E+09 | 12586.24 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.313349E+09 | 16982.02 | 09-JAN-05:01 | -2.1 |
February | 0.150015E+09 | 15756.31 | 17-FEB-06:01 | -3.1 |
March | 82332657.48 | 15850.18 | 06-MAR-06:02 | 4.00 |
April | 186937.46 | 728.63 | 11-APR-05:05 | 5.83 |
May | 480908.00 | 2733.00 | 05-MAY-05:03 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 5807383.58 | 6583.44 | 28-OCT-05:03 | 7.00 |
November | 0.139295E+09 | 16978.75 | 27-NOV-05:11 | 4.00 |
December | 0.614296E+09 | 17606.01 | 11-DEC-05:11 | 3.00 |
Annual Sum or Average | 0.130576E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.1 | |
Maximum of Months | 0.614296E+09 | 17606.01 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.235849E+09 | 10811.56 | 10-JAN-05:01 | -4.0 |
February | 0.100202E+09 | 10324.90 | 13-FEB-05:01 | -1.0 |
March | 30941432.33 | 9497.81 | 06-MAR-06:02 | 4.00 |
April | 61654.02 | 298.91 | 11-APR-05:08 | 5.83 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 1471339.93 | 2476.41 | 28-OCT-05:03 | 7.00 |
November | 94288277.30 | 10528.77 | 27-NOV-05:11 | 4.00 |
December | 0.346050E+09 | 11191.19 | 26-DEC-05:11 | 1.97 |
Annual Sum or Average | 0.808863E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.0 | |
Maximum of Months | 0.346050E+09 | 11191.19 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.319298E+10 | 12487.42 | 02-JAN-04:01 | 1.17 |
February | 0.212372E+10 | 12367.17 | 13-FEB-04:01 | -1.8 |
March | 0.134312E+10 | 12092.27 | 06-MAR-05:11 | 3.87 |
April | 0.215616E+09 | 10292.50 | 03-APR-04:12 | 4.33 |
May | 50984426.79 | 10285.04 | 05-MAY-04:12 | 5.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 30358.88 | 202.39 | 31-JUL-05:03 | 7.50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 21444898.98 | 9938.54 | 18-SEP-05:02 | 12.00 |
October | 0.682570E+09 | 11418.35 | 23-OCT-04:11 | 3.00 |
November | 0.180372E+10 | 12338.48 | 20-NOV-04:31 | 1.33 |
December | 0.362695E+10 | 12467.67 | 18-DEC-04:01 | -0.7 |
Annual Sum or Average | 0.130611E+11 | |||
Minimum of Months | 0.00 | 0.00 | -1.8 | |
Maximum of Months | 0.362695E+10 | 12487.42 | 12.00 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.181427E+10 | 16855.96 | 02-JAN-04:01 | 1.17 |
February | 0.117864E+10 | 16430.90 | 27-FEB-05:11 | 6.00 |
March | 0.815304E+09 | 16433.59 | 06-MAR-05:11 | 3.87 |
April | 75781632.36 | 13033.22 | 24-APR-05:02 | 7.00 |
May | 22944488.88 | 9708.63 | 05-MAY-04:12 | 5.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 9600.26 | 64.00 | 31-JUL-05:08 | 7.50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 4252977.93 | 4189.69 | 18-SEP-05:02 | 12.00 |
October | 0.399986E+09 | 15037.54 | 23-OCT-04:11 | 3.00 |
November | 0.106074E+10 | 16639.97 | 20-NOV-04:31 | 1.33 |
December | 0.223577E+10 | 16836.67 | 11-DEC-05:11 | 3.00 |
Annual Sum or Average | 0.760770E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.17 | |
Maximum of Months | 0.223577E+10 | 16855.96 | 12.00 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.191635E+10 | 24923.62 | 02-JAN-04:01 | 1.17 |
February | 0.126014E+10 | 24362.19 | 27-FEB-05:11 | 6.00 |
March | 0.105322E+10 | 24351.69 | 06-MAR-05:11 | 3.87 |
April | 0.116552E+09 | 19448.55 | 24-APR-05:02 | 7.00 |
May | 75889754.30 | 19421.28 | 15-MAY-05:02 | 7.12 |
June | 1497264.27 | 6320.61 | 08-JUN-05:03 | 6.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 323816.08 | 655.48 | 20-SEP-05:03 | 6.00 |
October | 0.434624E+09 | 21390.32 | 23-OCT-04:11 | 3.00 |
November | 0.117211E+10 | 24804.52 | 27-NOV-05:11 | 4.00 |
December | 0.267865E+10 | 25095.68 | 11-DEC-05:11 | 3.00 |
Annual Sum or Average | 0.870935E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.17 | |
Maximum of Months | 0.267865E+10 | 25095.68 | 11.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.127928E+10 | 16867.64 | 02-JAN-04:01 | 1.17 |
February | 0.721888E+09 | 15672.44 | 13-FEB-04:01 | -1.8 |
March | 0.476527E+09 | 15301.46 | 06-MAR-05:11 | 3.87 |
April | 30935156.91 | 11197.79 | 01-APR-05:02 | 2.17 |
May | 20651618.86 | 9175.84 | 05-MAY-05:03 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 584314.84 | 2040.92 | 07-SEP-05:03 | 8.83 |
October | 0.214482E+09 | 13915.27 | 23-OCT-04:11 | 3.00 |
November | 0.674641E+09 | 16223.75 | 27-NOV-05:11 | 4.00 |
December | 0.149018E+10 | 16762.07 | 26-DEC-05:11 | 1.97 |
Annual Sum or Average | 0.490917E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.8 | |
Maximum of Months | 0.149018E+10 | 16867.64 | 11.43 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 72319914.72 | 9401.92 | 01-JAN-16:02 | 3.83 |
February | 68963400.81 | 9647.60 | 27-FEB-05:11 | 6.00 |
March | 53023997.40 | 9523.54 | 06-MAR-05:11 | 3.87 |
April | 0.108579E+09 | 11540.44 | 30-APR-14:32 | 23.67 |
May | 84136142.74 | 9249.49 | 21-MAY-15:31 | 18.33 |
June | 79807753.68 | 7769.75 | 19-JUN-04:12 | 11.00 |
July | 0.123512E+09 | 9341.44 | 30-JUL-14:52 | 17.00 |
August | 0.112691E+09 | 10634.82 | 13-AUG-15:21 | 21.00 |
September | 83547495.99 | 10291.17 | 10-SEP-15:22 | 21.50 |
October | 62132935.77 | 9003.22 | 30-OCT-04:11 | 7.00 |
November | 68193659.86 | 10134.66 | 06-NOV-05:11 | 8.00 |
December | 62744985.79 | 11190.30 | 26-DEC-05:11 | 1.97 |
Annual Sum or Average | 0.979652E+09 | |||
Minimum of Months | 53023997.40 | 7769.75 | 1.97 | |
Maximum of Months | 0.123512E+09 | 11540.44 | 23.67 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.853951E+09 | 11571.75 | 15-JAN-12:52 | 10.00 |
February | 0.657810E+09 | 10032.26 | 19-FEB-13:43 | 6.00 |
March | 0.385062E+09 | 5030.33 | 23-MAR-05:02 | 6.67 |
April | 47537488.35 | 11978.61 | 30-APR-15:12 | 24.00 |
May | 57714312.29 | 7466.28 | 21-MAY-16:32 | 19.33 |
June | 48893081.15 | 7215.37 | 25-JUN-15:22 | 24.50 |
July | 71910362.48 | 11811.19 | 30-JUL-15:21 | 16.50 |
August | 58256975.81 | 11130.68 | 20-AUG-15:21 | 23.50 |
September | 70962403.73 | 12379.74 | 10-SEP-15:51 | 21.00 |
October | 0.137741E+09 | 7884.76 | 01-OCT-15:42 | 12.17 |
November | 0.404639E+09 | 9075.06 | 11-NOV-13:02 | 9.00 |
December | 0.958995E+09 | 4201.12 | 18-DEC-13:40 | 8.00 |
Annual Sum or Average | 0.375347E+10 | |||
Minimum of Months | 47537488.35 | 4201.12 | 6.00 | |
Maximum of Months | 0.958995E+09 | 12379.74 | 24.50 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.578641E+10 | 21662.01 | 09-JAN-05:23 | -2.0 |
February | 0.395950E+10 | 16186.15 | 13-FEB-06:03 | -1.0 |
March | 0.316693E+10 | 13773.77 | 06-MAR-05:22 | 3.90 |
April | 0.107414E+10 | 12335.99 | 21-APR-05:02 | 8.00 |
May | 0.729533E+09 | 14272.63 | 24-MAY-05:03 | 8.42 |
June | 0.252994E+09 | 14154.22 | 21-JUN-05:03 | 11.17 |
July | 0.203777E+09 | 14866.61 | 05-JUL-05:03 | 7.33 |
August | 0.314572E+09 | 12633.30 | 02-AUG-05:03 | 11.17 |
September | 0.669705E+09 | 13180.59 | 12-SEP-05:03 | 11.83 |
October | 0.216332E+10 | 10006.73 | 23-OCT-05:03 | 3.17 |
November | 0.391126E+10 | 17171.24 | 20-NOV-06:03 | -0.7 |
December | 0.665118E+10 | 20674.69 | 26-DEC-05:23 | 1.95 |
Annual Sum or Average | 0.288833E+11 | |||
Minimum of Months | 0.203777E+09 | 10006.73 | -2.0 | |
Maximum of Months | 0.665118E+10 | 21662.01 | 11.83 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 18800073.39 | 375.48 | 15-JAN-06:25 | 5.05 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 18800073.39 | |||
Minimum of Months | 0.00 | 0.00 | 3.80 | |
Maximum of Months | 18800073.39 | 375.48 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.646832E+09 | 597.72 | 08-JAN-17:40 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 643468.69 | 442.27 | 15-MAY-05:10 | 7.12 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 2009763.85 | 376.54 | 17-SEP-03:05 | 8.67 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 0.649486E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.646832E+09 | 597.72 | 11.43 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180249E+11 | 19402.09 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.163527E+11 | 19402.09 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.194806E+11 | 19402.09 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.173504E+11 | 19402.09 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.187528E+11 | 19402.09 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.186803E+11 | 19402.09 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.174228E+11 | 19402.09 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.194803E+11 | 19402.09 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.173504E+11 | 19402.09 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.180252E+11 | 19402.09 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.178272E+11 | 19402.09 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.174231E+11 | 19402.09 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.216171E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.163527E+11 | 19402.09 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.194806E+11 | 19402.09 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.144953E+10 | 2187.81 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.116782E+10 | 2187.81 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.126764E+10 | 1906.53 | 15-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.105057E+10 | 1906.53 | 10-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.109596E+10 | 1141.96 | 03-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.107745E+10 | 1040.96 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.100996E+10 | 1141.96 | 07-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.115954E+10 | 1524.25 | 22-AUG-07:30 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.108377E+10 | 1524.25 | 08-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.126678E+10 | 2187.81 | 16-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.142946E+10 | 2187.81 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.151446E+10 | 2187.81 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.145729E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.100996E+10 | 1040.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.151446E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.894154E+09 | 1409.91 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.731184E+09 | 1409.91 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.807826E+09 | 1228.64 | 15-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.675897E+09 | 982.28 | 10-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.709636E+09 | 735.93 | 15-MAY-15:20 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.698313E+09 | 670.83 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.654416E+09 | 735.93 | 07-JUL-15:30 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.747294E+09 | 801.02 | 22-AUG-07:30 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.691184E+09 | 982.28 | 08-SEP-07:30 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.798250E+09 | 1409.91 | 16-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.889475E+09 | 1409.91 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.929324E+09 | 1409.91 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.922695E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.654416E+09 | 670.83 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.929324E+09 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135364E+10 | 2187.86 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.111581E+10 | 2187.86 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.124560E+10 | 1906.57 | 15-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.105195E+10 | 1625.29 | 10-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.110129E+10 | 1141.99 | 03-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.108278E+10 | 1040.98 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.101639E+10 | 1141.99 | 07-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.116427E+10 | 1524.28 | 22-AUG-07:30 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.107634E+10 | 1524.28 | 08-SEP-07:19 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.122594E+10 | 2187.86 | 16-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.134902E+10 | 2187.86 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.140872E+10 | 2187.86 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.141917E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.101639E+10 | 1040.98 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.140872E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.903657E+09 | 1409.91 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.736325E+09 | 1409.91 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.812405E+09 | 1228.64 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.677932E+09 | 1228.64 | 10-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.707523E+09 | 801.02 | 04-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.695067E+09 | 735.93 | 14-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.652291E+09 | 735.93 | 07-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.750537E+09 | 982.28 | 22-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.698137E+09 | 1228.64 | 08-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.806158E+09 | 1409.91 | 16-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.894933E+09 | 1409.91 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.945893E+09 | 1409.91 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.928086E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.652291E+09 | 735.93 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.945893E+09 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.144343E+10 | 2187.81 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.116358E+10 | 2187.81 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.126264E+10 | 1906.53 | 15-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.104932E+10 | 1805.53 | 10-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.109506E+10 | 1141.96 | 03-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.107699E+10 | 1040.96 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.100942E+10 | 1141.96 | 07-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.115834E+10 | 1524.25 | 22-AUG-07:30 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.108223E+10 | 1524.25 | 08-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.126254E+10 | 2187.81 | 16-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.142419E+10 | 2187.81 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.150915E+10 | 2187.81 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.145369E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.100942E+10 | 1040.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.150915E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.892090E+09 | 1409.91 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.729096E+09 | 1409.91 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.806389E+09 | 1228.64 | 15-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.675339E+09 | 982.28 | 10-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.708947E+09 | 735.93 | 15-MAY-15:30 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.697880E+09 | 670.83 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.653904E+09 | 735.93 | 07-JUL-15:39 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.746618E+09 | 801.02 | 22-AUG-07:30 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.690518E+09 | 801.02 | 08-SEP-07:30 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.796496E+09 | 1409.91 | 16-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.886488E+09 | 1409.91 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.926203E+09 | 1409.91 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.920997E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.653904E+09 | 670.83 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.926203E+09 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135214E+10 | 2187.86 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.111275E+10 | 2187.86 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.124336E+10 | 1906.57 | 15-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.105098E+10 | 1524.28 | 10-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.110039E+10 | 1141.99 | 03-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.108208E+10 | 1040.98 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.101565E+10 | 1141.99 | 07-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.116323E+10 | 1524.28 | 22-AUG-07:30 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.107544E+10 | 1524.28 | 08-SEP-07:19 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.122336E+10 | 2187.86 | 16-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.134714E+10 | 2187.86 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.140634E+10 | 2187.86 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.141729E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.101565E+10 | 1040.98 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.140634E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.900918E+09 | 1409.91 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.734384E+09 | 1409.91 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.810824E+09 | 1228.64 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.677109E+09 | 1228.64 | 10-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.706974E+09 | 735.93 | 03-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.694493E+09 | 735.93 | 14-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.651886E+09 | 735.93 | 07-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.749839E+09 | 982.28 | 22-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.697334E+09 | 1228.64 | 08-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.803323E+09 | 1409.91 | 16-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.890505E+09 | 1409.91 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.942450E+09 | 1409.91 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.926004E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.651886E+09 | 735.93 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.942450E+09 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.144302E+10 | 2187.81 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.116357E+10 | 2187.81 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.126236E+10 | 1906.53 | 15-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.104911E+10 | 1524.25 | 10-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.109504E+10 | 1141.96 | 03-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.107697E+10 | 1040.96 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.100938E+10 | 1141.96 | 07-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.115830E+10 | 1524.25 | 22-AUG-07:30 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.108211E+10 | 1524.25 | 08-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.126224E+10 | 2187.81 | 16-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.142367E+10 | 2187.81 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.150869E+10 | 2187.81 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.145345E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.100938E+10 | 1040.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.150869E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.892090E+09 | 1409.91 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.729018E+09 | 1409.91 | 01-FEB-08:09 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.806335E+09 | 1228.64 | 15-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.675324E+09 | 982.28 | 10-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.708938E+09 | 735.93 | 15-MAY-15:30 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.697838E+09 | 670.83 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.653858E+09 | 735.93 | 07-JUL-15:39 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.746562E+09 | 801.02 | 22-AUG-07:30 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.690476E+09 | 801.02 | 08-SEP-07:30 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.796329E+09 | 1409.91 | 16-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.886404E+09 | 1409.91 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.925889E+09 | 1409.91 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.920906E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.653858E+09 | 670.83 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.925889E+09 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.135214E+10 | 2187.86 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.111275E+10 | 2187.86 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.124326E+10 | 1906.57 | 15-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.105096E+10 | 1524.28 | 10-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.110038E+10 | 1141.99 | 03-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.108201E+10 | 1040.98 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.101563E+10 | 1141.99 | 07-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.116315E+10 | 1524.28 | 22-AUG-07:30 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.107542E+10 | 1524.28 | 08-SEP-07:19 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.122329E+10 | 2187.86 | 16-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.134696E+10 | 2187.86 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.140627E+10 | 2187.86 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.141722E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.101563E+10 | 1040.98 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.140627E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.900625E+09 | 1409.91 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.734159E+09 | 1409.91 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.810647E+09 | 1228.64 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.677109E+09 | 1228.64 | 10-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.706961E+09 | 735.93 | 03-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.694493E+09 | 735.93 | 14-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.651838E+09 | 735.93 | 07-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.749761E+09 | 982.28 | 22-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.697278E+09 | 1163.55 | 08-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.803276E+09 | 1409.91 | 16-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.890318E+09 | 1409.91 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.942324E+09 | 1409.91 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.925879E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.651838E+09 | 735.93 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.942324E+09 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.522764E+10 | 5470.56 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.474186E+10 | 5470.56 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.563465E+10 | 5470.56 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.503289E+10 | 5470.56 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.543115E+10 | 5470.56 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.540489E+10 | 5470.56 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.505915E+10 | 5470.56 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.563465E+10 | 5470.56 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.503289E+10 | 5470.56 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.522764E+10 | 5470.56 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.516637E+10 | 5470.56 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.505915E+10 | 5470.56 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.626529E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.474186E+10 | 5470.56 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.563465E+10 | 5470.56 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.180249E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.163527E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.194806E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.173504E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.187528E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.186803E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.174228E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.194803E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.173504E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.180252E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.178272E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.174231E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.216171E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.163527E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.194806E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.144953E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101247E+09 |
February | 0.136985E+10 | 0.116782E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141809E+09 |
March | 0.163685E+10 | 0.126764E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84426264.22 |
April | 0.145243E+10 | 0.105057E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105437E+09 |
May | 0.157338E+10 | 0.109596E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.58 | 0.251022E+09 |
June | 0.156900E+10 | 0.107745E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 112376.16 | 0.193706E+09 |
July | 0.145680E+10 | 0.100996E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 514236.63 | 0.187899E+09 |
August | 0.163685E+10 | 0.115954E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72694.33 | 0.135187E+09 |
September | 0.145243E+10 | 0.108377E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140887E+09 |
October | 0.150991E+10 | 0.126678E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153397E+09 |
November | 0.149516E+10 | 0.142946E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189921E+09 |
December | 0.145680E+10 | 0.151446E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260068E+09 |
Annual Sum or Average | 0.181194E+11 | 0.145729E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 699308.70 | 0.194501E+10 |
Minimum of Months | 0.136985E+10 | 0.100996E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84426264.22 |
Maximum of Months | 0.163685E+10 | 0.151446E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 514236.63 | 0.260068E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.894154E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67077475.11 |
February | 0.882782E+09 | 0.731184E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92956168.99 |
March | 0.105485E+10 | 0.807826E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54798145.58 |
April | 0.936002E+09 | 0.675897E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69292123.30 |
May | 0.101394E+10 | 0.709636E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.05 | 0.167068E+09 |
June | 0.101113E+10 | 0.698313E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74916.40 | 0.127186E+09 |
July | 0.938820E+09 | 0.654416E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 386404.89 | 0.122583E+09 |
August | 0.105485E+10 | 0.747294E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48449.70 | 87512318.29 |
September | 0.936002E+09 | 0.691184E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95199798.05 |
October | 0.973041E+09 | 0.798250E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100324E+09 |
November | 0.963541E+09 | 0.889475E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122748E+09 |
December | 0.938820E+09 | 0.929324E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166957E+09 |
Annual Sum or Average | 0.116768E+11 | 0.922695E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 509772.04 | 0.127370E+10 |
Minimum of Months | 0.882782E+09 | 0.654416E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54798145.58 |
Maximum of Months | 0.105485E+10 | 0.929324E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 386404.89 | 0.167068E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.135364E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100984E+09 |
February | 0.136988E+10 | 0.111581E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141085E+09 |
March | 0.163688E+10 | 0.124560E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82097554.93 |
April | 0.145246E+10 | 0.105195E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106003E+09 |
May | 0.157341E+10 | 0.110129E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.54 | 0.249807E+09 |
June | 0.156904E+10 | 0.108278E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 112372.90 | 0.191837E+09 |
July | 0.145684E+10 | 0.101639E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 542147.22 | 0.186595E+09 |
August | 0.163688E+10 | 0.116427E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72534.93 | 0.136756E+09 |
September | 0.145246E+10 | 0.107634E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145440E+09 |
October | 0.150994E+10 | 0.122594E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153475E+09 |
November | 0.149520E+10 | 0.134902E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186392E+09 |
December | 0.145684E+10 | 0.140872E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250634E+09 |
Annual Sum or Average | 0.181198E+11 | 0.141917E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 727056.59 | 0.193111E+10 |
Minimum of Months | 0.136988E+10 | 0.101639E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82097554.93 |
Maximum of Months | 0.163688E+10 | 0.140872E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 542147.22 | 0.250634E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.903657E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69914948.66 |
February | 0.882782E+09 | 0.736325E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100998E+09 |
March | 0.105485E+10 | 0.812405E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60198508.71 |
April | 0.936002E+09 | 0.677932E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77588171.34 |
May | 0.101394E+10 | 0.707523E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.05 | 0.178263E+09 |
June | 0.101113E+10 | 0.695067E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74895.44 | 0.141134E+09 |
July | 0.938820E+09 | 0.652291E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 297958.12 | 0.140430E+09 |
August | 0.105485E+10 | 0.750537E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48266.52 | 0.103222E+09 |
September | 0.936002E+09 | 0.698137E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101231E+09 |
October | 0.973041E+09 | 0.806158E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110538E+09 |
November | 0.963541E+09 | 0.894933E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137880E+09 |
December | 0.938820E+09 | 0.945893E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190897E+09 |
Annual Sum or Average | 0.116768E+11 | 0.928086E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 421121.14 | 0.141229E+10 |
Minimum of Months | 0.882782E+09 | 0.652291E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60198508.71 |
Maximum of Months | 0.105485E+10 | 0.945893E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 297958.12 | 0.190897E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.144343E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207091E+09 |
February | 0.136985E+10 | 0.116358E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293490E+09 |
March | 0.163685E+10 | 0.126264E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175994E+09 |
April | 0.145243E+10 | 0.104932E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226307E+09 |
May | 0.157338E+10 | 0.109506E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551613E+09 |
June | 0.156900E+10 | 0.107699E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 245801.90 | 0.430388E+09 |
July | 0.145680E+10 | 0.100942E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1231349.50 | 0.409008E+09 |
August | 0.163685E+10 | 0.115834E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 160640.74 | 0.292744E+09 |
September | 0.145243E+10 | 0.108223E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303018E+09 |
October | 0.150991E+10 | 0.126254E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317612E+09 |
November | 0.149516E+10 | 0.142419E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382289E+09 |
December | 0.145680E+10 | 0.150915E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516457E+09 |
Annual Sum or Average | 0.181194E+11 | 0.145369E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1637792.14 | 0.410601E+10 |
Minimum of Months | 0.136985E+10 | 0.100942E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175994E+09 |
Maximum of Months | 0.163685E+10 | 0.150915E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1231349.50 | 0.551613E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.892090E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140061E+09 |
February | 0.649041E+09 | 0.729096E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198285E+09 |
March | 0.773965E+09 | 0.806389E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117707E+09 |
April | 0.688021E+09 | 0.675339E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156852E+09 |
May | 0.744847E+09 | 0.708947E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375431E+09 |
June | 0.742030E+09 | 0.697880E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 163857.46 | 0.289439E+09 |
July | 0.690839E+09 | 0.653904E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 900060.76 | 0.280059E+09 |
August | 0.773965E+09 | 0.746618E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 107126.36 | 0.201403E+09 |
September | 0.688021E+09 | 0.690518E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212814E+09 |
October | 0.715730E+09 | 0.796496E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215080E+09 |
November | 0.708685E+09 | 0.886488E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256089E+09 |
December | 0.690839E+09 | 0.926203E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345009E+09 |
Annual Sum or Average | 0.858171E+10 | 0.920997E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1171044.58 | 0.278823E+10 |
Minimum of Months | 0.649041E+09 | 0.653904E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117707E+09 |
Maximum of Months | 0.773965E+09 | 0.926203E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 900060.76 | 0.375431E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.135214E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226053E+09 |
February | 0.136988E+10 | 0.111275E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316600E+09 |
March | 0.163688E+10 | 0.124336E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182322E+09 |
April | 0.145246E+10 | 0.105098E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241819E+09 |
May | 0.157341E+10 | 0.110039E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.567975E+09 |
June | 0.156904E+10 | 0.108208E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 245793.36 | 0.434651E+09 |
July | 0.145684E+10 | 0.101565E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1276681.17 | 0.421840E+09 |
August | 0.163688E+10 | 0.116323E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 160639.62 | 0.311837E+09 |
September | 0.145246E+10 | 0.107544E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332996E+09 |
October | 0.150994E+10 | 0.122336E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343990E+09 |
November | 0.149520E+10 | 0.134714E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407496E+09 |
December | 0.145684E+10 | 0.140634E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539243E+09 |
Annual Sum or Average | 0.181198E+11 | 0.141729E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1683114.14 | 0.432682E+10 |
Minimum of Months | 0.136988E+10 | 0.101565E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182322E+09 |
Maximum of Months | 0.163688E+10 | 0.140634E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1276681.17 | 0.567975E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.900918E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142924E+09 |
February | 0.882782E+09 | 0.734384E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204210E+09 |
March | 0.105485E+10 | 0.810824E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119343E+09 |
April | 0.936002E+09 | 0.677109E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159470E+09 |
May | 0.101394E+10 | 0.706974E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388801E+09 |
June | 0.101113E+10 | 0.694493E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 163839.53 | 0.304387E+09 |
July | 0.938820E+09 | 0.651886E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 668952.07 | 0.295859E+09 |
August | 0.105485E+10 | 0.749839E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 107101.97 | 0.213376E+09 |
September | 0.936002E+09 | 0.697334E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215189E+09 |
October | 0.973041E+09 | 0.803323E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221226E+09 |
November | 0.963541E+09 | 0.890505E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262496E+09 |
December | 0.938820E+09 | 0.942450E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354039E+09 |
Annual Sum or Average | 0.116768E+11 | 0.926004E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 939893.56 | 0.288132E+10 |
Minimum of Months | 0.882782E+09 | 0.651886E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119343E+09 |
Maximum of Months | 0.105485E+10 | 0.942450E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 668952.07 | 0.388801E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.144302E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231158E+09 |
February | 0.136985E+10 | 0.116357E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329474E+09 |
March | 0.163685E+10 | 0.126236E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201161E+09 |
April | 0.145243E+10 | 0.104911E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263246E+09 |
May | 0.157338E+10 | 0.109504E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.647907E+09 |
June | 0.156900E+10 | 0.107697E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 283529.90 | 0.517301E+09 |
July | 0.145680E+10 | 0.100938E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1388615.83 | 0.492666E+09 |
August | 0.163685E+10 | 0.115830E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 186982.31 | 0.351349E+09 |
September | 0.145243E+10 | 0.108211E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349271E+09 |
October | 0.150991E+10 | 0.126224E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354150E+09 |
November | 0.149516E+10 | 0.142367E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426026E+09 |
December | 0.145680E+10 | 0.150869E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.581247E+09 |
Annual Sum or Average | 0.181194E+11 | 0.145345E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1859128.04 | 0.474496E+10 |
Minimum of Months | 0.136985E+10 | 0.100938E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201161E+09 |
Maximum of Months | 0.163685E+10 | 0.150869E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1388615.83 | 0.647907E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.892090E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156178E+09 |
February | 0.882782E+09 | 0.729018E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223992E+09 |
March | 0.105485E+10 | 0.806335E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135946E+09 |
April | 0.936002E+09 | 0.675324E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185754E+09 |
May | 0.101394E+10 | 0.708938E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447468E+09 |
June | 0.101113E+10 | 0.697838E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 189016.27 | 0.351329E+09 |
July | 0.938820E+09 | 0.653858E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1012473.59 | 0.341880E+09 |
August | 0.105485E+10 | 0.746562E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 124654.60 | 0.245295E+09 |
September | 0.936002E+09 | 0.690476E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251351E+09 |
October | 0.973041E+09 | 0.796329E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243613E+09 |
November | 0.963541E+09 | 0.886404E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287332E+09 |
December | 0.938820E+09 | 0.925889E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388950E+09 |
Annual Sum or Average | 0.116768E+11 | 0.920906E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1326144.47 | 0.325909E+10 |
Minimum of Months | 0.882782E+09 | 0.653858E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135946E+09 |
Maximum of Months | 0.105485E+10 | 0.925889E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1012473.59 | 0.447468E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.135214E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251163E+09 |
February | 0.136988E+10 | 0.111275E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359200E+09 |
March | 0.163688E+10 | 0.124326E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209981E+09 |
April | 0.145246E+10 | 0.105096E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286154E+09 |
May | 0.157341E+10 | 0.110038E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.673265E+09 |
June | 0.156904E+10 | 0.108201E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 283520.62 | 0.523593E+09 |
July | 0.145684E+10 | 0.101563E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1462117.84 | 0.510417E+09 |
August | 0.163688E+10 | 0.116315E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 186983.70 | 0.377190E+09 |
September | 0.145246E+10 | 0.107542E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392822E+09 |
October | 0.150994E+10 | 0.122329E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392922E+09 |
November | 0.149520E+10 | 0.134696E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458127E+09 |
December | 0.145684E+10 | 0.140627E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.604720E+09 |
Annual Sum or Average | 0.181198E+11 | 0.141722E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1932622.17 | 0.503955E+10 |
Minimum of Months | 0.136988E+10 | 0.101563E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209981E+09 |
Maximum of Months | 0.163688E+10 | 0.140627E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1462117.84 | 0.673265E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.900625E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161597E+09 |
February | 0.882782E+09 | 0.734159E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235358E+09 |
March | 0.105485E+10 | 0.810647E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139431E+09 |
April | 0.936002E+09 | 0.677109E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188993E+09 |
May | 0.101394E+10 | 0.706961E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463917E+09 |
June | 0.101113E+10 | 0.694493E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 188979.45 | 0.368567E+09 |
July | 0.938820E+09 | 0.651838E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 794660.29 | 0.359597E+09 |
August | 0.105485E+10 | 0.749761E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 124664.00 | 0.258250E+09 |
September | 0.936002E+09 | 0.697278E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253528E+09 |
October | 0.973041E+09 | 0.803276E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254466E+09 |
November | 0.963541E+09 | 0.890318E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300426E+09 |
December | 0.938820E+09 | 0.942324E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404881E+09 |
Annual Sum or Average | 0.116768E+11 | 0.925879E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1108303.74 | 0.338901E+10 |
Minimum of Months | 0.882782E+09 | 0.651838E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139431E+09 |
Maximum of Months | 0.105485E+10 | 0.942324E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 794660.29 | 0.463917E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.522764E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.474186E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.563465E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.503289E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.543115E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.540489E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.505915E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.563465E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.503289E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.522764E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.516637E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.505915E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.626529E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.474186E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.563465E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217774E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304178E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176854E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221802E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529782E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130390.91 | 0.405159E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 892906.42 | 0.393044E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88291.51 | 0.288242E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303550E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327820E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408375E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557035E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1111588.84 | 0.413362E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176854E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 892906.42 | 0.557035E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362268E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515715E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299466E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382506E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.926808E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246029.47 | 0.709766E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1713919.50 | 0.678507E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174367.58 | 0.498808E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.527828E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559267E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681911E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.912852E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2134316.55 | 0.705570E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299466E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1713919.50 | 0.926808E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357474E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.517263E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314953E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423506E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101975E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80313.96 | 0.804236E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1151142.07 | 0.772532E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95995.87 | 0.559684E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.563828E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566091E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.669569E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.897440E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1327451.89 | 0.746633E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314953E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1151142.07 | 0.101975E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 19402.09 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 19402.09 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 19402.09 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 19402.09 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 19402.09 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 19402.09 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 19402.09 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 19402.09 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 19402.09 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 19402.09 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 19402.09 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 19402.09 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 19402.09 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 19402.09 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2187.81 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 334.94 | 08-JAN-08:00 |
February | 2010.79 | 01-FEB-10:09 | 2187.81 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 301.73 | 08-FEB-22:10 |
March | 2010.79 | 01-MAR-10:09 | 1906.53 | 15-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 314.57 | 27-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 1906.53 | 10-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 343.23 | 23-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 1141.96 | 03-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22-MAY-15:00 | 497.63 | 04-MAY-23:00 |
June | 2010.79 | 01-JUN-09:09 | 1040.96 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.16 | 13-JUN-15:30 | 343.88 | 05-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 1141.96 | 07-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 | 22-JUL-17:10 | 334.02 | 30-JUL-18:50 |
August | 2010.79 | 01-AUG-09:09 | 1524.25 | 22-AUG-07:30 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.18 | 14-AUG-16:50 | 234.22 | 22-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 1524.25 | 08-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 309.76 | 06-SEP-04:00 |
October | 2010.79 | 02-OCT-09:09 | 2187.81 | 16-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 389.57 | 20-OCT-22:00 |
November | 2010.79 | 01-NOV-09:09 | 2187.81 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 412.37 | 25-NOV-05:00 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 600.58 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.22 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 | 600.58 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 221.22 | 08-JAN-08:00 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 192.35 | 08-FEB-22:10 |
March | 1295.83 | 01-MAR-10:09 | 1228.64 | 15-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 201.86 | 27-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 982.28 | 10-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 220.72 | 23-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 735.93 | 15-MAY-15:20 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22-MAY-15:00 | 323.72 | 04-MAY-23:00 |
June | 1295.83 | 01-JUN-09:09 | 670.83 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.44 | 13-JUN-15:30 | 255.57 | 18-JUN-09:50 |
July | 1295.83 | 03-JUL-09:09 | 735.93 | 07-JUL-15:30 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.60 | 22-JUL-19:10 | 213.78 | 30-JUL-18:50 |
August | 1295.83 | 01-AUG-09:09 | 801.02 | 22-AUG-07:30 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.12 | 14-AUG-16:50 | 145.53 | 22-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 982.28 | 08-SEP-07:30 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 206.11 | 06-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 16-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 247.83 | 20-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 263.09 | 25-NOV-05:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 379.29 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.53 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 22.60 | 379.29 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2187.86 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 331.05 | 01-JAN-15:00 |
February | 2010.83 | 01-FEB-10:09 | 2187.86 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 320.88 | 05-FEB-14:00 |
March | 2010.83 | 01-MAR-10:09 | 1906.57 | 15-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 299.91 | 27-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 1625.29 | 10-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 329.20 | 23-APR-22:00 |
May | 2010.83 | 01-MAY-09:09 | 1141.99 | 03-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22-MAY-15:00 | 484.93 | 04-MAY-23:00 |
June | 2010.83 | 01-JUN-09:09 | 1040.98 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.16 | 13-JUN-15:30 | 364.11 | 18-JUN-12:10 |
July | 2010.83 | 03-JUL-09:09 | 1141.99 | 07-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.74 | 22-JUL-19:10 | 339.13 | 30-JUL-18:50 |
August | 2010.83 | 01-AUG-09:09 | 1524.28 | 22-AUG-07:30 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.18 | 14-AUG-16:50 | 235.38 | 22-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 1524.28 | 08-SEP-07:19 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 305.02 | 06-SEP-04:00 |
October | 2010.83 | 02-OCT-09:09 | 2187.86 | 16-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 381.40 | 20-OCT-22:00 |
November | 2010.83 | 01-NOV-09:09 | 2187.86 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 385.48 | 25-NOV-05:00 |
December | 2010.83 | 01-DEC-10:09 | 2187.86 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 579.49 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.38 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 28.74 | 579.49 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 233.88 | 08-JAN-08:00 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 213.65 | 14-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 1228.64 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 226.49 | 27-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 1228.64 | 10-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 257.49 | 23-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 801.02 | 04-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22-MAY-15:00 | 348.84 | 04-MAY-23:00 |
June | 1295.83 | 01-JUN-09:09 | 735.93 | 14-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.44 | 13-JUN-15:30 | 289.60 | 18-JUN-16:10 |
July | 1295.83 | 03-JUL-09:09 | 735.93 | 07-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.04 | 22-JUL-19:06 | 289.68 | 30-JUL-18:50 |
August | 1295.83 | 01-AUG-09:09 | 982.28 | 22-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.11 | 14-AUG-16:50 | 179.52 | 18-AUG-03:00 |
September | 1295.83 | 01-SEP-09:09 | 1228.64 | 08-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 219.13 | 06-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 16-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 283.32 | 20-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 304.90 | 25-NOV-05:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 436.90 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 735.93 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.52 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 14.04 | 436.90 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2187.81 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 673.03 | 08-JAN-08:00 |
February | 2010.79 | 01-FEB-10:09 | 2187.81 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 653.60 | 08-FEB-22:03 |
March | 2010.79 | 01-MAR-10:09 | 1906.53 | 15-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 652.09 | 27-MAR-21:10 |
April | 2010.79 | 03-APR-09:09 | 1805.53 | 10-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 699.33 | 23-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 1141.96 | 03-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 1078.96 | 04-MAY-23:00 |
June | 2010.79 | 01-JUN-09:09 | 1040.96 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.23 | 13-JUN-15:40 | 762.53 | 05-JUN-21:20 |
July | 2010.79 | 03-JUL-09:09 | 1141.96 | 07-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.20 | 22-JUL-17:01 | 677.78 | 30-JUL-18:40 |
August | 2010.79 | 01-AUG-09:09 | 1524.25 | 22-AUG-07:30 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.94 | 14-AUG-16:50 | 505.77 | 22-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 1524.25 | 08-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 646.69 | 06-SEP-04:00 |
October | 2010.79 | 02-OCT-09:09 | 2187.81 | 16-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 800.72 | 20-OCT-22:00 |
November | 2010.79 | 01-NOV-09:09 | 2187.81 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 786.64 | 25-NOV-05:00 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1225.28 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505.77 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 61.20 | 1225.28 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1409.91 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 451.07 | 08-JAN-08:00 |
February | 1239.33 | 01-FEB-08:09 | 1409.91 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 434.98 | 08-FEB-22:03 |
March | 1239.33 | 01-MAR-08:09 | 1228.64 | 15-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 433.72 | 27-MAR-21:03 |
April | 1239.33 | 03-APR-07:10 | 982.28 | 10-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 468.31 | 23-APR-22:00 |
May | 1239.33 | 01-MAY-07:10 | 735.93 | 15-MAY-15:30 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 700.46 | 04-MAY-23:00 |
June | 1239.33 | 01-JUN-07:10 | 670.83 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.15 | 13-JUN-15:40 | 619.19 | 18-JUN-10:00 |
July | 1239.33 | 03-JUL-07:10 | 735.93 | 07-JUL-15:39 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.60 | 22-JUL-19:10 | 464.68 | 30-JUL-18:40 |
August | 1239.33 | 01-AUG-07:10 | 801.02 | 22-AUG-07:30 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.29 | 14-AUG-16:50 | 322.72 | 22-AUG-21:10 |
September | 1239.33 | 01-SEP-07:10 | 801.02 | 08-SEP-07:30 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 438.73 | 06-SEP-04:00 |
October | 1239.33 | 02-OCT-07:10 | 1409.91 | 16-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 521.17 | 20-OCT-22:00 |
November | 1239.33 | 01-NOV-07:10 | 1409.91 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 516.27 | 25-NOV-05:00 |
December | 1239.33 | 01-DEC-08:09 | 1409.91 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 804.98 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.72 | |||||
Maximum of Months | 1239.33 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 54.60 | 804.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2187.86 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 764.41 | 01-JAN-14:53 |
February | 2010.83 | 01-FEB-10:09 | 2187.86 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 720.57 | 05-FEB-13:53 |
March | 2010.83 | 01-MAR-10:09 | 1906.57 | 15-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 651.54 | 27-MAR-21:03 |
April | 2010.83 | 03-APR-09:09 | 1524.28 | 10-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 754.10 | 16-APR-12:10 |
May | 2010.83 | 01-MAY-09:09 | 1141.99 | 03-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 1065.15 | 04-MAY-23:00 |
June | 2010.83 | 01-JUN-09:09 | 1040.98 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.23 | 13-JUN-15:40 | 816.84 | 18-JUN-15:32 |
July | 2010.83 | 03-JUL-09:09 | 1141.99 | 07-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 71.73 | 22-JUL-19:10 | 767.45 | 30-JUL-18:40 |
August | 2010.83 | 01-AUG-09:09 | 1524.28 | 22-AUG-07:30 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.94 | 14-AUG-16:50 | 519.95 | 22-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 1524.28 | 08-SEP-07:19 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 664.69 | 06-SEP-04:00 |
October | 2010.83 | 02-OCT-09:09 | 2187.86 | 16-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 850.76 | 01-OCT-24:00 |
November | 2010.83 | 01-NOV-09:09 | 2187.86 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 793.84 | 26-NOV-04:00 |
December | 2010.83 | 01-DEC-10:09 | 2187.86 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1245.67 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 519.95 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 71.73 | 1245.67 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 462.84 | 08-JAN-08:00 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 439.53 | 08-FEB-22:10 |
March | 1295.83 | 01-MAR-10:09 | 1228.64 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 438.44 | 27-MAR-21:20 |
April | 1295.83 | 03-APR-09:09 | 1228.64 | 10-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 478.47 | 23-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 735.93 | 03-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 723.50 | 04-MAY-23:00 |
June | 1295.83 | 01-JUN-09:09 | 735.93 | 14-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.15 | 13-JUN-15:40 | 632.97 | 18-JUN-16:10 |
July | 1295.83 | 03-JUL-09:09 | 735.93 | 07-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.70 | 22-JUL-19:06 | 648.57 | 30-JUL-18:40 |
August | 1295.83 | 01-AUG-09:09 | 982.28 | 22-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.30 | 14-AUG-16:50 | 370.20 | 22-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 1228.64 | 08-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 443.16 | 06-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 16-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 548.86 | 20-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 534.62 | 25-NOV-05:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 827.17 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 735.93 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.20 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 32.70 | 827.17 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2187.81 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 747.56 | 10-JAN-05:52 |
February | 2010.79 | 01-FEB-10:09 | 2187.81 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 809.15 | 08-FEB-22:03 |
March | 2010.79 | 01-MAR-10:09 | 1906.53 | 15-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 804.81 | 27-MAR-21:03 |
April | 2010.79 | 03-APR-09:09 | 1524.25 | 10-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 767.52 | 23-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 1141.96 | 03-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 1241.17 | 04-MAY-23:00 |
June | 2010.79 | 01-JUN-09:09 | 1040.96 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.53 | 13-JUN-15:50 | 922.18 | 05-JUN-21:17 |
July | 2010.79 | 03-JUL-09:09 | 1141.96 | 07-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.73 | 22-JUL-17:01 | 851.78 | 30-JUL-19:00 |
August | 2010.79 | 01-AUG-09:09 | 1524.25 | 22-AUG-07:30 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.62 | 14-AUG-16:50 | 609.53 | 22-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 1524.25 | 08-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 726.33 | 06-SEP-04:00 |
October | 2010.79 | 02-OCT-09:09 | 2187.81 | 16-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 919.94 | 20-OCT-22:00 |
November | 2010.79 | 01-NOV-09:09 | 2187.81 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 942.85 | 25-NOV-05:17 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1434.35 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 609.53 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 67.73 | 1434.35 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 498.74 | 10-JAN-05:52 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 01-FEB-08:09 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 539.02 | 08-FEB-22:03 |
March | 1295.83 | 01-MAR-10:09 | 1228.64 | 15-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 536.28 | 27-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 982.28 | 10-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 515.40 | 23-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 735.93 | 15-MAY-15:30 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 814.92 | 04-MAY-23:00 |
June | 1295.83 | 01-JUN-09:09 | 670.83 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.35 | 13-JUN-15:50 | 743.66 | 18-JUN-10:20 |
July | 1295.83 | 03-JUL-09:09 | 735.93 | 07-JUL-15:39 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.08 | 22-JUL-19:10 | 587.17 | 30-JUL-19:00 |
August | 1295.83 | 01-AUG-09:09 | 801.02 | 22-AUG-07:30 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.08 | 14-AUG-16:50 | 391.43 | 22-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 801.02 | 08-SEP-07:30 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 497.53 | 06-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 16-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 606.38 | 20-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 628.57 | 25-NOV-05:18 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 942.98 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391.43 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 59.08 | 942.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2187.86 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 768.30 | 01-JAN-14:53 |
February | 2010.83 | 01-FEB-10:09 | 2187.86 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 822.48 | 05-FEB-14:00 |
March | 2010.83 | 01-MAR-10:09 | 1906.57 | 15-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 805.03 | 27-MAR-21:03 |
April | 2010.83 | 03-APR-09:09 | 1524.28 | 10-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 867.09 | 16-APR-11:45 |
May | 2010.83 | 01-MAY-09:09 | 1141.99 | 03-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 1233.65 | 04-MAY-23:00 |
June | 2010.83 | 01-JUN-09:09 | 1040.98 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.53 | 13-JUN-15:50 | 996.39 | 18-JUN-14:00 |
July | 2010.83 | 03-JUL-09:09 | 1141.99 | 07-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.62 | 22-JUL-19:10 | 959.69 | 30-JUL-19:00 |
August | 2010.83 | 01-AUG-09:09 | 1524.28 | 22-AUG-07:30 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.62 | 14-AUG-16:50 | 628.87 | 22-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 1524.28 | 08-SEP-07:19 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 752.82 | 06-SEP-04:00 |
October | 2010.83 | 02-OCT-09:09 | 2187.86 | 16-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 951.90 | 01-OCT-24:00 |
November | 2010.83 | 01-NOV-09:09 | 2187.86 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 942.84 | 25-NOV-05:18 |
December | 2010.83 | 01-DEC-10:09 | 2187.86 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1453.16 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 628.87 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 80.62 | 1453.16 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 500.43 | 10-JAN-05:52 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 542.76 | 08-FEB-22:03 |
March | 1295.83 | 01-MAR-10:09 | 1228.64 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 538.71 | 27-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 1228.64 | 10-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 557.68 | 15-APR-17:40 |
May | 1295.83 | 01-MAY-09:09 | 735.93 | 03-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 842.98 | 04-MAY-23:00 |
June | 1295.83 | 01-JUN-09:09 | 735.93 | 14-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.35 | 13-JUN-15:50 | 788.13 | 18-JUN-16:20 |
July | 1295.83 | 03-JUL-09:09 | 735.93 | 07-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.28 | 22-JUL-19:06 | 814.81 | 30-JUL-19:00 |
August | 1295.83 | 01-AUG-09:09 | 982.28 | 22-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.08 | 14-AUG-16:50 | 449.17 | 22-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 1163.55 | 08-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 506.09 | 06-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 16-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 643.78 | 20-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 641.50 | 25-NOV-05:13 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 976.32 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 735.93 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 449.17 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 38.28 | 976.32 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 5470.56 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 5470.56 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 5470.56 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 5470.56 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 5470.56 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 5470.56 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 5470.56 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 5470.56 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 5470.56 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 5470.56 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 5470.56 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 5470.56 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 5470.56 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 736.75 | 08-JAN-08:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 656.27 | 08-FEB-22:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 663.12 | 27-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 724.17 | 23-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 1074.99 | 04-MAY-23:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.37 | 13-JUN-16:00 | 719.23 | 05-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.60 | 22-JUL-18:51 | 674.72 | 30-JUL-18:54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.07 | 14-AUG-17:00 | 491.37 | 22-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 671.77 | 06-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 825.10 | 20-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 890.34 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1311.48 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 491.37 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.60 | 1311.48 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1245.11 | 08-JAN-08:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1125.08 | 08-FEB-22:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1116.08 | 27-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1230.36 | 23-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 1887.07 | 04-MAY-23:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.92 | 13-JUN-16:00 | 1261.43 | 05-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.28 | 22-JUL-18:51 | 1120.43 | 30-JUL-18:52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.20 | 14-AUG-17:00 | 862.53 | 22-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1151.50 | 06-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1405.44 | 20-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1448.01 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2171.49 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 862.53 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.28 | 2171.49 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1104.48 | 08-JAN-08:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1210.36 | 08-FEB-22:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1188.33 | 27-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1217.73 | 23-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 1973.06 | 04-MAY-23:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.32 | 13-JUN-17:00 | 1444.44 | 18-JUN-15:55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.14 | 22-JUL-18:51 | 1369.01 | 30-JUL-18:52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.08 | 14-AUG-18:00 | 938.77 | 22-AUG-21:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1136.30 | 06-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1434.75 | 20-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1372.61 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2315.91 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 938.77 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.14 | 2315.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 118486.11 | 02-JAN-07:05 | 7180.90 | 12934.72 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 104034.98 | 21-FEB-07:05 | 7180.90 | 12934.72 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 103595.29 | 27-MAR-06:05 | 7180.90 | 12934.72 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 106007.30 | 24-APR-06:05 | 7180.90 | 12934.72 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 107048.27 | 30-MAY-06:05 | 7180.90 | 12934.72 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 112221.32 | 19-JUN-06:11 | 32314.05 | 58206.26 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 114173.27 | 05-JUL-06:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 112791.19 | 07-AUG-06:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 113129.77 | 25-SEP-06:11 | 32314.05 | 58206.26 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 115993.49 | 10-OCT-06:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 110038.53 | 24-NOV-07:11 | 28723.60 | 51738.90 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 106640.78 | 26-DEC-07:05 | 7180.90 | 12934.72 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 103595.29 | 7180.90 | 12934.72 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 118486.11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 95206.69 | 02-JAN-04:01 | 0.00 | 4298.88 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 86794.93 | 21-FEB-05:11 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 88737.39 | 20-MAR-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 94102.18 | 24-APR-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 92000.91 | 01-MAY-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 91099.60 | 05-JUN-04:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 93761.04 | 05-JUL-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 93143.03 | 28-AUG-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 91946.27 | 05-SEP-04:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 95648.75 | 10-OCT-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 94501.13 | 13-NOV-05:11 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 90818.57 | 26-DEC-05:11 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 86794.93 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 95648.75 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 50380.81 | 26-JAN-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 40708.22 | 10-FEB-06:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 71242.08 | 24-MAR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 79069.93 | 29-APR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 79097.65 | 23-MAY-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 79672.57 | 27-JUN-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 79514.89 | 15-JUL-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 79138.43 | 17-AUG-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 79568.39 | 02-SEP-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 76186.25 | 05-OCT-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 65878.82 | 01-NOV-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 27384.41 | 22-DEC-17:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 27384.41 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 79672.57 | 15316.26 | 17424.44 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 21044.54 | 19-JAN-17:00 | 30632.53 | 34848.87 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 20871.96 | 09-FEB-17:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 26289.47 | 31-MAR-16:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 50575.21 | 21-APR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 69396.50 | 23-MAY-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 74431.95 | 27-JUN-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 73969.06 | 24-JUL-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 71580.05 | 15-AUG-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 69377.67 | 13-SEP-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 33658.36 | 05-OCT-16:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 25114.94 | 10-NOV-16:40 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18942.90 | 21-DEC-17:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 18942.90 | 6448.95 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 74431.95 | 30632.53 | 34848.87 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3059.34 | 02-JAN-04:02 | 0.00 | 539.77 | 5964.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.20 |
February | 3228.31 | 21-FEB-14:10 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.65 |
March | 5088.71 | 20-MAR-12:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.24 |
April | 7319.83 | 28-APR-14:00 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.35 |
May | 7342.81 | 22-MAY-15:00 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11116.41 | 26-JUN-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.67 |
July | 11233.30 | 23-JUL-17:11 | 0.00 | 520.44 | 5032.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.85 |
August | 8379.65 | 14-AUG-15:20 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 3.45 | 0.00 |
September | 6703.78 | 13-SEP-14:20 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.87 |
October | 5784.05 | 10-OCT-13:10 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.73 |
November | 3668.48 | 08-NOV-14:30 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.44 |
December | 2826.96 | 26-DEC-05:12 | 0.00 | 674.71 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.85 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2826.96 | 0.00 | 337.35 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11233.30 | 2010.79 | 1040.96 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 3.45 | 288.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4408.28 | 20-JAN-10:05 | 2591.66 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5810.65 | 17-FEB-09:45 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5150.80 | 25-MAR-09:30 | 818.42 | 447.22 | 1547.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 22474.04 | 30-APR-08:32 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.01 |
May | 23948.08 | 21-MAY-08:52 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.15 |
June | 23852.29 | 18-JUN-08:32 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.27 |
July | 25773.44 | 23-JUL-08:31 | 521.82 | 298.13 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.39 |
August | 24021.86 | 20-AUG-09:32 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.95 |
September | 19471.44 | 04-SEP-08:52 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.63 |
October | 8705.20 | 03-OCT-09:00 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.38 |
November | 5174.08 | 13-NOV-09:25 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.55 |
December | 3236.12 | 26-DEC-10:10 | 2591.66 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3236.12 | 326.14 | 186.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25773.44 | 2591.66 | 1341.67 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 30885.78 | 15-JAN-12:23 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 31143.82 | 19-FEB-14:52 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.56 |
March | 12610.01 | 28-MAR-12:10 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.81 |
April | 32730.11 | 30-APR-12:32 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.79 |
May | 29232.00 | 21-MAY-14:12 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.37 |
June | 25806.73 | 11-JUN-12:53 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.94 |
July | 32581.17 | 23-JUL-12:32 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.05 |
August | 33591.45 | 06-AUG-13:02 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.59 |
September | 33083.03 | 17-SEP-13:32 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.53 |
October | 21598.05 | 01-OCT-13:13 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.57 |
November | 22820.35 | 11-NOV-13:13 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.80 |
December | 16194.75 | 18-DEC-13:30 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12610.01 | 404.87 | 231.31 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33591.45 | 1923.15 | 1040.98 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7822.14 | 30-JAN-16:38 | 4957.30 | 3929.14 | 5569.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 15210.31 | 19-FEB-16:12 | 260.91 | 149.06 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.50 |
March | 11274.12 | 23-MAR-16:00 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.94 |
April | 29054.84 | 30-APR-15:51 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31393.10 | 21-MAY-16:51 | 587.05 | 335.39 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.49 |
June | 32087.79 | 11-JUN-16:51 | 587.05 | 335.39 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.28 |
July | 33510.88 | 09-JUL-17:01 | 0.00 | 372.66 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.01 |
August | 29597.97 | 20-AUG-16:11 | 587.05 | 335.39 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.98 |
September | 25558.32 | 17-SEP-15:32 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.05 |
October | 12328.64 | 03-OCT-15:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.14 |
November | 11127.06 | 06-NOV-05:11 | 0.00 | 347.85 | 3843.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7688.91 | 18-DEC-14:30 | 1295.83 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7688.91 | 0.00 | 149.06 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33510.88 | 4957.30 | 3929.14 | 5569.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2041.90 | 15-JAN-12:52 | 506.08 | 289.13 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1995.34 | 22-FEB-15:00 | 2010.79 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.84 |
March | 2311.94 | 30-MAR-14:00 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.90 |
April | 5572.36 | 28-APR-14:00 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.12 |
May | 6015.10 | 22-MAY-15:00 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
June | 7687.51 | 13-JUN-15:00 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 17.85 | 0.00 |
July | 7518.98 | 10-JUL-15:00 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.52 |
August | 6560.32 | 10-AUG-15:00 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.13 |
September | 5789.14 | 13-SEP-15:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.94 |
October | 3136.87 | 06-OCT-15:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.44 |
November | 2347.47 | 11-NOV-13:02 | 607.30 | 346.96 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.77 |
December | 1832.76 | 21-DEC-14:50 | 2010.79 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1832.76 | 506.08 | 289.13 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7687.51 | 2010.79 | 1141.96 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.85 | 251.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2716.49 | 15-JAN-12:52 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3902.17 | 17-FEB-09:55 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3264.41 | 25-MAR-09:30 | 0.00 | 447.22 | 1547.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 23513.61 | 30-APR-09:12 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.96 |
May | 23720.52 | 07-MAY-08:32 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.93 |
June | 25062.57 | 25-JUN-09:22 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.61 |
July | 26021.55 | 16-JUL-08:21 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.73 |
August | 25838.09 | 20-AUG-08:41 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.14 |
September | 23761.36 | 10-SEP-09:12 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.63 |
October | 9556.52 | 01-OCT-09:43 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.02 |
November | 3172.52 | 11-NOV-12:22 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.86 |
December | 2323.63 | 06-DEC-10:00 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2323.63 | 0.00 | 149.06 | 1547.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26021.55 | 2478.65 | 1341.67 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 32762.30 | 15-JAN-12:52 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 23753.68 | 19-FEB-14:23 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.16 |
March | 11290.13 | 28-MAR-12:10 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.64 |
April | 34277.93 | 30-APR-13:12 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.24 |
May | 21227.86 | 28-MAY-14:32 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 523.84 |
June | 21754.48 | 25-JUN-13:23 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.62 |
July | 33408.07 | 30-JUL-13:22 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 439.81 |
August | 34820.85 | 20-AUG-13:22 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.50 |
September | 36537.19 | 24-SEP-13:01 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.28 |
October | 34979.50 | 01-OCT-13:02 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 326.62 |
November | 34304.28 | 11-NOV-13:02 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391.06 |
December | 14864.36 | 18-DEC-13:30 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11290.13 | 404.87 | 231.31 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36537.19 | 1923.15 | 1040.98 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 523.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4133.51 | 19-JAN-15:40 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7376.09 | 27-FEB-16:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7620.64 | 23-MAR-16:40 | 391.37 | 372.68 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.05 |
April | 25979.20 | 30-APR-17:11 | 0.00 | 260.86 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.65 |
May | 25733.84 | 21-MAY-16:32 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.84 |
June | 29184.66 | 25-JUN-17:21 | 0.00 | 335.39 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.53 |
July | 26353.34 | 09-JUL-17:22 | 0.00 | 223.59 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.81 |
August | 26483.21 | 20-AUG-16:41 | 652.28 | 372.66 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.00 |
September | 25868.31 | 10-SEP-16:32 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.36 |
October | 10951.44 | 01-OCT-15:42 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.79 |
November | 4345.57 | 10-NOV-15:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.67 |
December | 2654.01 | 21-DEC-14:40 | 1295.83 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2654.01 | 0.00 | 186.33 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29184.66 | 1295.83 | 670.83 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1901.90 | 19-JAN-15:50 | 1923.11 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1832.66 | 03-FEB-15:10 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.58 |
March | 2202.72 | 30-MAR-15:50 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.36 |
April | 5808.27 | 28-APR-15:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.47 |
May | 6641.47 | 22-MAY-15:10 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.38 |
June | 8557.74 | 13-JUN-15:00 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 20.88 | 0.00 |
July | 8235.85 | 10-JUL-15:00 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.62 |
August | 7044.34 | 14-AUG-16:00 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 14.79 | 0.00 |
September | 6005.55 | 13-SEP-15:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.46 |
October | 2493.53 | 01-OCT-13:31 | 708.51 | 404.79 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.06 |
November | 2045.06 | 10-NOV-15:40 | 1923.11 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.66 |
December | 1671.71 | 21-DEC-14:50 | 2010.79 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1671.71 | 708.51 | 404.79 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8557.74 | 2010.79 | 1141.96 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 20.88 | 224.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2366.84 | 20-JAN-10:40 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2581.46 | 24-FEB-10:40 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.69 |
March | 2495.13 | 25-MAR-10:00 | 409.21 | 223.61 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 22106.36 | 30-APR-09:32 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.76 |
May | 24137.81 | 21-MAY-09:42 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.22 |
June | 24579.59 | 25-JUN-09:32 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.74 |
July | 24264.93 | 23-JUL-09:22 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.11 |
August | 20328.61 | 20-AUG-09:02 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.24 |
September | 18235.21 | 10-SEP-09:02 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.85 |
October | 6127.15 | 04-OCT-10:00 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2311.22 | 03-NOV-10:00 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.83 |
December | 2015.60 | 06-DEC-10:10 | 2591.66 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2015.60 | 326.14 | 186.33 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24579.59 | 2591.66 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13806.34 | 11-JAN-13:40 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.87 |
February | 17811.29 | 17-FEB-13:40 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.64 |
March | 9092.12 | 28-MAR-12:20 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.65 |
April | 35615.36 | 30-APR-13:32 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.67 |
May | 31224.26 | 21-MAY-14:22 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 397.47 |
June | 27243.81 | 11-JUN-14:22 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.73 |
July | 28996.39 | 09-JUL-14:32 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.96 |
August | 36026.10 | 13-AUG-13:32 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.18 |
September | 38734.61 | 10-SEP-13:41 | 809.75 | 462.62 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 342.71 |
October | 33615.14 | 01-OCT-13:31 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 364.44 |
November | 25051.21 | 11-NOV-13:32 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 460.04 |
December | 11858.73 | 18-DEC-13:30 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9092.12 | 506.09 | 289.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.67 | |
Maximum of Months | 38734.61 | 1923.15 | 1040.98 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 460.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3436.41 | 19-JAN-15:40 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6436.46 | 27-FEB-16:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6923.09 | 23-MAR-16:50 | 391.37 | 372.68 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.61 |
April | 26801.51 | 30-APR-16:52 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.25 |
May | 29393.49 | 21-MAY-16:21 | 521.82 | 298.13 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.20 |
June | 30576.05 | 25-JUN-17:31 | 0.00 | 335.39 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.53 |
July | 31207.34 | 09-JUL-17:11 | 0.00 | 372.66 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.81 |
August | 29297.57 | 13-AUG-17:31 | 0.00 | 298.13 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.68 |
September | 26873.81 | 10-SEP-16:22 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.81 |
October | 9613.76 | 03-OCT-15:40 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.24 |
November | 3694.62 | 10-NOV-15:40 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.83 |
December | 2560.36 | 21-DEC-14:40 | 1295.83 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2560.36 | 0.00 | 223.59 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31207.34 | 1295.83 | 670.83 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 245.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7819.33 | 02-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4730.95 | 25-FEB-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.85 |
March | 4917.60 | 15-MAR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7729.63 | 24-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.27 |
May | 8538.66 | 01-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.85 |
June | 8661.14 | 26-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.85 |
July | 10366.47 | 24-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.59 |
August | 10134.29 | 14-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7539.53 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.96 |
October | 8159.55 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5916.96 | 13-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.03 |
December | 4141.62 | 21-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4141.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10366.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7106.83 | 09-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6947.43 | 18-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.20 |
March | 4965.49 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5756.36 | 29-APR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5604.92 | 02-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.19 |
June | 5447.48 | 24-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.55 |
July | 5506.78 | 24-JUL-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.32 |
August | 5556.53 | 21-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.76 |
September | 5368.97 | 16-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4796.25 | 06-OCT-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.25 |
November | 5863.49 | 27-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 533.22 |
December | 7452.12 | 30-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 898.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4796.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7452.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 898.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 730.57 | 21-JAN-12:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.35 |
February | 1236.32 | 22-FEB-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.72 |
March | 3198.04 | 25-MAR-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.70 |
April | 14290.45 | 28-APR-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.53 |
May | 14933.03 | 22-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.04 |
June | 17109.69 | 13-JUN-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.47 |
July | 16736.90 | 21-JUL-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.24 | 0.00 |
August | 14795.29 | 14-AUG-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.09 |
September | 12684.12 | 12-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.66 |
October | 5873.92 | 03-OCT-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.26 |
November | 1365.70 | 11-NOV-13:38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 513.53 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17109.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.24 | 513.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2055.14 | 19-JAN-16:20 | 222.14 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4279.25 | 27-FEB-17:00 | 222.14 | 450.11 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7032.97 | 31-MAR-24:00 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8472.02 | 30-APR-18:02 | 0.00 | 200.06 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3383.32 | 31-MAY-24:00 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5219.52 | 30-JUN-24:00 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7273.70 | 31-JUL-24:00 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8243.28 | 13-AUG-18:10 | 0.00 | 150.05 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3247.98 | 30-SEP-24:00 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5093.90 | 31-OCT-24:00 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5846.31 | 03-NOV-16:00 | 222.14 | 450.11 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7550.50 | 26-DEC-15:20 | 222.14 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2055.14 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8472.02 | 222.14 | 450.11 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1805.95 | 19-JAN-16:30 | 222.14 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3883.70 | 27-FEB-17:00 | 222.14 | 450.11 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6286.10 | 31-MAR-23:40 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7962.22 | 30-APR-18:10 | 0.00 | 200.06 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3080.39 | 31-MAY-23:40 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4727.80 | 30-JUN-24:00 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6818.37 | 31-JUL-23:50 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7681.34 | 13-AUG-18:10 | 0.00 | 150.05 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2860.83 | 30-SEP-23:30 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4355.78 | 31-OCT-24:00 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5415.95 | 03-NOV-16:00 | 222.14 | 450.11 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6890.41 | 21-DEC-15:20 | 222.14 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1805.95 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7962.22 | 222.14 | 450.11 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1702.76 | 19-JAN-16:40 | 222.14 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3692.93 | 17-FEB-17:00 | 222.14 | 450.11 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5832.19 | 31-MAR-23:20 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8071.70 | 30-APR-18:00 | 0.00 | 175.05 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2933.81 | 31-MAY-23:20 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4486.35 | 30-JUN-23:30 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6663.57 | 31-JUL-23:20 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7763.81 | 13-AUG-18:00 | 0.00 | 200.06 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2330.95 | 30-SEP-23:20 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3912.45 | 03-OCT-16:50 | 70.15 | 250.06 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5318.00 | 10-NOV-16:20 | 222.14 | 450.11 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6663.62 | 21-DEC-15:20 | 222.14 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1702.76 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8071.70 | 222.14 | 450.11 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 92269.19 | 02-JAN-17:00 | 4808.68 | 5470.56 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 183385.76 | 09-FEB-17:00 | 4808.68 | 5470.56 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358819.58 | 31-MAR-24:00 | 0.00 | 303.90 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 368239.87 | 28-APR-16:00 | 4808.68 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176117.08 | 31-MAY-24:00 | 0.00 | 303.90 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267449.38 | 30-JUN-24:00 | 0.00 | 303.90 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 360254.61 | 31-JUL-24:00 | 0.00 | 303.90 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 368643.11 | 28-AUG-16:00 | 4808.68 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 175631.97 | 30-SEP-24:00 | 0.00 | 303.90 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 267581.10 | 31-OCT-24:00 | 0.00 | 303.90 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 276045.03 | 15-NOV-17:00 | 4808.68 | 5470.56 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 367578.20 | 26-DEC-17:00 | 4808.68 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 92269.19 | 0.00 | 303.90 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 368643.11 | 4808.68 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.161621E+13 | 1215963.20 | 10-JAN-16:00 | 0.272898E+12 | 752112.66 | 10-JAN-07:00 |
February | 0.180689E+13 | 1302226.68 | 17-FEB-16:10 | 0.180515E+12 | 632024.19 | 17-FEB-07:10 |
March | 0.244216E+13 | 1458776.51 | 23-MAR-15:00 | 0.129762E+12 | 444305.27 | 06-MAR-06:10 |
April | 0.271515E+13 | 1864701.64 | 28-APR-15:00 | 0.163058E+11 | 307190.60 | 08-APR-06:10 |
May | 0.163240E+13 | 1459962.62 | 22-MAY-15:09 | 0.532171E+10 | 199552.03 | 06-MAY-06:10 |
June | 0.195734E+13 | 1737623.04 | 13-JUN-15:30 | 98593696.51 | 18105.89 | 07-JUN-20:00 |
July | 0.234804E+13 | 1861223.31 | 21-JUL-15:20 | 18642950.70 | 3105.74 | 31-JUL-05:10 |
August | 0.285889E+13 | 1980898.52 | 14-AUG-15:39 | 6796727.90 | 1087.20 | 24-AUG-05:00 |
September | 0.159718E+13 | 1474500.20 | 27-SEP-15:39 | 0.129334E+10 | 111342.78 | 21-SEP-06:10 |
October | 0.194169E+13 | 1436790.66 | 06-OCT-15:20 | 0.372665E+11 | 294833.33 | 23-OCT-06:10 |
November | 0.228076E+13 | 1501228.39 | 16-NOV-16:00 | 0.133165E+12 | 546999.32 | 29-NOV-07:10 |
December | 0.276120E+13 | 1644267.96 | 22-DEC-16:19 | 0.298539E+12 | 611484.72 | 26-DEC-05:19 |
Annual Sum or Average | 0.259579E+14 | 0.107519E+13 | ||||
Minimum of Months | 0.159718E+13 | 1215963.20 | 6796727.90 | 1087.20 | ||
Maximum of Months | 0.285889E+13 | 1980898.52 | 0.298539E+12 | 752112.66 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.277740E+12 | 0.444933E+11 | 0.766053E+12 | 0.213346E+12 | 0.172213E+12 | 0.109623E+11 | 0.00 | 0.112940E+11 | 0.100480E+10 | 0.791349E+11 | 0.00 | 0.399682E+11 | 0.00 |
February | 0.246896E+12 | 0.345613E+11 | 0.978954E+12 | 0.195334E+12 | 0.158211E+12 | 0.105084E+11 | 0.00 | 0.243730E+11 | 0.216144E+10 | 0.119335E+12 | 0.00 | 0.365524E+11 | 0.00 |
March | 0.290107E+12 | 0.308164E+11 | 0.141687E+13 | 0.226059E+12 | 0.178362E+12 | 0.127123E+11 | 0.00 | 0.419597E+11 | 0.420186E+10 | 0.198377E+12 | 0.00 | 0.426937E+11 | 0.00 |
April | 0.255772E+12 | 0.230363E+11 | 0.165903E+13 | 0.211501E+12 | 0.210302E+12 | 0.139495E+11 | 0.00 | 0.713873E+11 | 0.148107E+11 | 0.217339E+12 | 0.00 | 0.380231E+11 | 0.00 |
May | 0.274981E+12 | 0.191640E+11 | 0.774844E+12 | 0.219699E+12 | 0.212923E+12 | 0.168182E+11 | 0.00 | 0.251234E+11 | 0.788960E+10 | 0.414181E+11 | 0.00 | 0.395395E+11 | 0.00 |
June | 0.273356E+12 | 0.165920E+11 | 0.106252E+13 | 0.217934E+12 | 0.228148E+12 | 0.225666E+11 | 0.00 | 0.622773E+11 | 0.222916E+11 | 0.134986E+11 | 0.00 | 0.381599E+11 | 0.00 |
July | 0.255213E+12 | 0.178410E+11 | 0.139340E+13 | 0.213265E+12 | 0.237641E+12 | 0.307880E+11 | 0.00 | 0.111618E+12 | 0.422692E+11 | 0.104280E+11 | 0.00 | 0.355764E+11 | 0.00 |
August | 0.286435E+12 | 0.214285E+11 | 0.173200E+13 | 0.226058E+12 | 0.249342E+12 | 0.339477E+11 | 0.00 | 0.185745E+12 | 0.712796E+11 | 0.140361E+11 | 0.00 | 0.386186E+11 | 0.00 |
September | 0.256885E+12 | 0.266429E+11 | 0.740713E+12 | 0.211501E+12 | 0.220956E+12 | 0.244394E+11 | 0.00 | 0.444731E+11 | 0.209109E+11 | 0.153492E+11 | 0.00 | 0.353126E+11 | 0.00 |
October | 0.271708E+12 | 0.350556E+11 | 0.108340E+13 | 0.213344E+12 | 0.193557E+12 | 0.131576E+11 | 0.00 | 0.295448E+11 | 0.446234E+10 | 0.602759E+11 | 0.00 | 0.371808E+11 | 0.00 |
November | 0.274809E+12 | 0.409293E+11 | 0.135889E+13 | 0.205300E+12 | 0.175467E+12 | 0.104727E+11 | 0.00 | 0.387869E+11 | 0.418721E+10 | 0.134443E+12 | 0.00 | 0.374728E+11 | 0.00 |
December | 0.272667E+12 | 0.463809E+11 | 0.170972E+13 | 0.213272E+12 | 0.172096E+12 | 0.111437E+11 | 0.00 | 0.527593E+11 | 0.456768E+10 | 0.240297E+12 | 0.00 | 0.382971E+11 | 0.00 |
Annual Sum or Average | 0.323657E+13 | 0.356942E+12 | 0.146764E+14 | 0.256661E+13 | 0.240922E+13 | 0.211466E+12 | 0.00 | 0.699342E+12 | 0.200037E+12 | 0.114393E+13 | 0.00 | 0.457395E+12 | 0.00 |
Minimum of Months | 0.246896E+12 | 0.165920E+11 | 0.740713E+12 | 0.195334E+12 | 0.158211E+12 | 0.104727E+11 | 0.00 | 0.112940E+11 | 0.100480E+10 | 0.104280E+11 | 0.00 | 0.353126E+11 | 0.00 |
Maximum of Months | 0.290107E+12 | 0.463809E+11 | 0.173200E+13 | 0.226059E+12 | 0.249342E+12 | 0.339477E+11 | 0.00 | 0.185745E+12 | 0.712796E+11 | 0.240297E+12 | 0.00 | 0.426937E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.272898E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.180515E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.129762E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.163058E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.532171E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 98593696.51 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 18642950.70 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 6796727.90 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.129334E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.372665E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.133165E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.298539E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.107519E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 6796727.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.298539E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 325713.14 | 02-JAN-08:09 | 40855.88 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 233439.18 | 02-JAN-08:20 | 109514.95 | 20-JAN-11:00 | 19440.69 | 31-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 325713.14 | 01-FEB-08:09 | 40855.88 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 233439.18 | 01-FEB-08:20 | 118270.26 | 17-FEB-14:00 | 19420.22 | 13-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 314611.94 | 15-MAR-07:10 | 40855.88 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 233433.23 | 15-MAR-07:19 | 112523.82 | 23-MAR-15:00 | 19408.32 | 07-MAR-06:10 | 0.00 | 01-MAR-00:10 |
April | 305776.82 | 10-APR-07:10 | 40855.88 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 233428.51 | 10-APR-07:19 | 247462.67 | 28-APR-14:50 | 22601.06 | 28-APR-14:30 | 0.00 | 01-APR-00:10 |
May | 283720.93 | 04-MAY-07:10 | 27558.46 | 01-MAY-19:19 | 423497.50 | 01-MAY-07:10 | 233416.73 | 04-MAY-07:19 | 214535.54 | 23-MAY-15:20 | 37682.58 | 22-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 281231.72 | 14-JUN-07:10 | 27558.46 | 01-JUN-19:00 | 541788.89 | 01-JUN-07:10 | 233415.40 | 14-JUN-07:19 | 246933.31 | 13-JUN-15:20 | 37719.42 | 21-JUN-14:30 | 0.00 | 01-JUN-00:10 |
July | 283655.84 | 07-JUL-07:10 | 27558.46 | 01-JUL-20:19 | 660080.29 | 03-JUL-07:10 | 233416.70 | 07-JUL-07:19 | 245870.71 | 21-JUL-15:20 | 41298.31 | 21-JUL-17:30 | 0.00 | 01-JUL-00:10 |
August | 297349.23 | 22-AUG-07:30 | 40855.88 | 14-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 233424.00 | 22-AUG-07:40 | 243467.95 | 14-AUG-15:20 | 37807.66 | 28-AUG-13:39 | 0.00 | 01-AUG-00:10 |
September | 297530.49 | 08-SEP-07:30 | 40855.88 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 233424.10 | 08-SEP-07:40 | 244064.03 | 12-SEP-15:20 | 38058.51 | 12-SEP-15:30 | 0.00 | 01-SEP-00:10 |
October | 325713.14 | 16-OCT-07:10 | 40855.88 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 233439.18 | 16-OCT-07:19 | 186255.91 | 03-OCT-14:00 | 19434.14 | 06-OCT-15:20 | 0.00 | 01-OCT-00:10 |
November | 325713.14 | 01-NOV-07:10 | 40855.88 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 233439.18 | 01-NOV-07:19 | 123656.23 | 10-NOV-13:30 | 19453.52 | 20-NOV-06:10 | 0.00 | 01-NOV-00:10 |
December | 325713.14 | 01-DEC-08:09 | 40855.88 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 233439.18 | 01-DEC-08:20 | 103932.81 | 18-DEC-13:30 | 19483.60 | 26-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 281231.72 | 27558.46 | 423497.50 | 233415.40 | 103932.81 | 19408.32 | 0.00 | |||||||
Maximum of Months | 325713.14 | 40855.88 | 778371.69 | 233439.18 | 247462.67 | 41298.31 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 7018.91 | 19-JAN-16:30 | 1059.36 | 29-JAN-05:00 | 62951.93 | 10-JAN-17:00 | 0.00 | 52757.38 | 31-JAN-12:30 | 0.00 |
February | 13497.89 | 16-FEB-16:00 | 1658.19 | 07-FEB-14:00 | 100000.00 | 20-FEB-15:39 | 0.00 | 52812.29 | 15-FEB-12:00 | 0.00 |
March | 21417.35 | 31-MAR-23:40 | 3373.53 | 25-MAR-12:00 | 100000.00 | 03-MAR-22:10 | 0.00 | 52754.88 | 01-MAR-12:20 | 0.00 |
April | 197638.14 | 28-APR-14:00 | 51391.46 | 28-APR-14:00 | 100000.00 | 01-APR-04:30 | 0.00 | 52227.40 | 03-APR-11:50 | 0.00 |
May | 165502.95 | 22-MAY-13:50 | 78170.05 | 22-MAY-14:09 | 98029.91 | 21-MAY-14:00 | 0.00 | 51276.40 | 01-MAY-11:50 | 0.00 |
June | 292970.76 | 13-JUN-15:00 | 78170.05 | 12-JUN-12:50 | 100000.00 | 08-JUN-11:50 | 0.00 | 49552.87 | 01-JUN-11:50 | 0.00 |
July | 314732.96 | 21-JUL-15:39 | 78170.05 | 10-JUL-08:00 | 100000.00 | 05-JUL-15:50 | 0.00 | 47950.86 | 03-JUL-11:30 | 0.00 |
August | 323082.37 | 14-AUG-15:00 | 78170.05 | 14-AUG-10:09 | 100000.00 | 14-AUG-16:49 | 0.00 | 47401.09 | 31-AUG-11:00 | 0.00 |
September | 164203.39 | 13-SEP-12:39 | 78170.05 | 11-SEP-13:00 | 71496.68 | 29-SEP-16:00 | 0.00 | 47953.64 | 29-SEP-11:20 | 0.00 |
October | 45548.16 | 07-OCT-14:00 | 49417.68 | 07-OCT-14:00 | 100000.00 | 07-OCT-16:19 | 0.00 | 49560.32 | 31-OCT-11:00 | 0.00 |
November | 21268.13 | 24-NOV-11:00 | 5381.84 | 24-NOV-11:00 | 100000.00 | 19-NOV-12:20 | 0.00 | 51347.93 | 30-NOV-12:30 | 0.00 |
December | 21830.13 | 29-DEC-15:50 | 3725.07 | 23-DEC-10:00 | 100000.00 | 03-DEC-11:50 | 0.00 | 52230.92 | 29-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 7018.91 | 1059.36 | 62951.93 | 0.00 | 47401.09 | 0.00 | ||||
Maximum of Months | 323082.37 | 78170.05 | 100000.00 | 0.00 | 52812.29 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1215963.20 | 10-JAN-16:00 | 325713.14 | 423497.50 | 40855.88 | 233326.38 | 79859.06 | 3854.77 | 0.00 | 6480.89 | 354.19 |
February | 1302226.68 | 17-FEB-16:10 | 280450.63 | 541788.89 | 0.00 | 233302.19 | 110885.01 | 3829.25 | 0.00 | 13004.90 | 1236.97 |
March | 1458776.51 | 23-MAR-15:00 | 280450.63 | 660080.29 | 0.00 | 233302.19 | 112523.82 | 19347.98 | 0.00 | 18055.44 | 2380.03 |
April | 1864701.64 | 28-APR-15:00 | 280450.63 | 778371.69 | 0.00 | 233302.19 | 216311.15 | 19787.99 | 0.00 | 175821.80 | 50669.19 |
May | 1459962.62 | 22-MAY-15:09 | 280450.63 | 423497.50 | 0.00 | 233302.19 | 209642.05 | 36847.17 | 0.00 | 160076.64 | 78170.05 |
June | 1737623.04 | 13-JUN-15:30 | 280450.63 | 541788.89 | 0.00 | 233302.19 | 246512.21 | 37081.63 | 0.00 | 282191.74 | 78170.05 |
July | 1861223.31 | 21-JUL-15:20 | 280450.63 | 660080.29 | 0.00 | 233302.19 | 245870.71 | 37656.73 | 0.00 | 313067.38 | 53741.35 |
August | 1980898.52 | 14-AUG-15:39 | 280450.63 | 778371.69 | 0.00 | 233302.19 | 240352.86 | 37304.10 | 0.00 | 320993.71 | 53309.71 |
September | 1474500.20 | 27-SEP-15:39 | 280450.63 | 423497.50 | 0.00 | 233302.19 | 203284.16 | 35515.59 | 0.00 | 141765.68 | 50442.23 |
October | 1436790.66 | 06-OCT-15:20 | 280450.63 | 541788.89 | 0.00 | 233302.19 | 172831.55 | 19434.14 | 0.00 | 45146.37 | 7054.54 |
November | 1501228.39 | 16-NOV-16:00 | 325713.14 | 660080.29 | 40855.88 | 233326.38 | 98995.79 | 19347.38 | 0.00 | 16719.97 | 1745.76 |
December | 1644267.96 | 22-DEC-16:19 | 325713.14 | 778371.69 | 40855.88 | 233326.38 | 85458.28 | 19347.96 | 0.00 | 21168.85 | 2058.49 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1215963.20 | 280450.63 | 423497.50 | 0.00 | 233302.19 | 79859.06 | 3829.25 | 0.00 | 6480.89 | 354.19 | |
Maximum of Months | 1980898.52 | 325713.14 | 778371.69 | 40855.88 | 233326.38 | 246512.21 | 37656.73 | 0.00 | 320993.71 | 78170.05 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 752112.66 | 10-JAN-07:00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 632024.19 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 444305.27 | 06-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 307190.60 | 08-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 199552.03 | 06-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 18105.89 | 07-JUN-20:00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 3105.74 | 31-JUL-05:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 1087.20 | 24-AUG-05:00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 111342.78 | 21-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 294833.33 | 23-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 546999.32 | 29-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 611484.72 | 26-DEC-05:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 1087.20 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 752112.66 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 79.17 | 27.20 | 37.83 | 27.15 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 44.67 | 26.15 | 23.33 | 26.16 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 53.00 | 26.23 | 27.83 | 26.23 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 52.67 | 26.53 | 26.17 | 26.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 66.33 | 26.61 | 29.33 | 26.54 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 51.50 | 26.48 | 29.83 | 26.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 100.00 | 27.05 | 51.67 | 27.01 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 88.67 | 26.90 | 32.17 | 26.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 69.00 | 26.84 | 37.00 | 26.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 74.50 | 26.90 | 39.33 | 26.87 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 67.50 | 26.74 | 33.83 | 26.72 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 57.67 | 26.46 | 25.67 | 26.41 |
Annual Sum or Average | 0.00 | 0.00 | 804.67 | 26.74 | 394.00 | 26.70 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 44.67 | 26.15 | 23.33 | 26.16 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 100.00 | 27.20 | 51.67 | 27.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.57 | 0.00 | 25.57 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.58 | 0.00 | 25.58 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.75 | 0.00 | 25.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.33 | 25.59 | 0.00 | 25.59 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.75 | 0.00 | 25.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 19.03 | 0.17 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
February | 0.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 18.75 | 0.00 | 18.75 | 0.00 | 18.75 | 0.00 | 18.75 |
December | 1.17 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
Annual Sum or Average | 2.83 | 19.07 | 0.17 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 19.42 | 0.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.23 | 1.50 | 28.23 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.09 | 2.00 | 28.09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.08 | 3.17 | 28.08 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.07 | 5.67 | 28.07 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.05 | 3.83 | 28.05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.92 | 4.00 | 27.92 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.50 | 0.33 | 27.50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 20.50 | 28.04 | 20.50 | 28.04 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.23 | 5.67 | 28.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.78 | 0.83 | 27.78 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.69 | 1.33 | 27.69 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.22 | 2.67 | 28.24 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.57 | 1.83 | 27.57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.59 | 2.50 | 27.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.87 | 5.33 | 27.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.08 | 6.33 | 28.08 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.09 | 6.50 | 28.09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.01 | 1.67 | 28.01 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.84 | 1.50 | 27.84 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.30 | 0.33 | 27.30 |
Annual Sum or Average | 0.00 | 0.00 | 31.00 | 27.94 | 30.83 | 27.94 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.22 | 6.50 | 28.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.48 | 0.50 | 27.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.29 | 2.67 | 28.30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.25 | 3.00 | 28.29 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.49 | 3.17 | 28.51 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 28.18 | 5.17 | 28.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.66 | 5.33 | 27.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.09 | 3.50 | 28.12 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.67 | 0.83 | 27.70 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.33 | 0.17 | 27.33 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.32 | 0.17 | 27.32 |
Annual Sum or Average | 0.00 | 0.00 | 48.00 | 28.05 | 24.67 | 28.18 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 28.49 | 5.33 | 28.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
Annual Sum or Average | 1.67 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.32 | 1.50 | 28.32 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.15 | 1.83 | 28.15 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.07 | 3.33 | 28.07 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.18 | 5.17 | 28.18 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.10 | 3.83 | 28.10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.79 | 3.83 | 27.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.00 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
Annual Sum or Average | 1.67 | 19.33 | 0.00 | 19.33 | 19.50 | 27.39 | 19.50 | 27.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 19.33 | 0.00 | 19.33 | 5.17 | 28.32 | 5.17 | 28.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.85 | 0.83 | 27.85 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 28.07 | 0.83 | 28.07 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.38 | 2.17 | 28.44 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.64 | 1.67 | 27.64 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.55 | 1.83 | 27.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.90 | 4.33 | 27.90 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.16 | 5.67 | 28.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.29 | 6.50 | 28.29 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.24 | 1.67 | 28.24 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.97 | 1.17 | 27.97 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 27.00 | 28.08 | 26.67 | 28.08 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.38 | 6.50 | 28.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.59 | 1.00 | 28.64 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.25 | 2.00 | 28.26 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.50 | 1.67 | 28.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.55 | 3.00 | 28.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.41 | 2.83 | 28.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.94 | 2.33 | 27.95 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 23.83 | 28.40 | 12.83 | 28.41 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.59 | 3.00 | 28.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.67 | 18.95 | 4.17 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
February | 7.50 | 19.01 | 1.33 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
March | 3.00 | 19.21 | 0.33 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.67 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
November | 6.33 | 18.89 | 1.17 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
December | 14.83 | 18.90 | 4.67 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
Annual Sum or Average | 45.00 | 18.95 | 11.67 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 14.83 | 19.21 | 4.67 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.17 | 18.21 | 0.00 | 18.21 | 0.00 | 18.21 | 0.00 | 18.21 |
February | 4.33 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
March | 2.17 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.25 | 1.33 | 28.25 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.88 | 1.50 | 27.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.82 | 3.67 | 27.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.18 | 4.50 | 28.18 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.92 | 3.33 | 27.92 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.63 | 1.67 | 27.63 |
October | 0.50 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
November | 3.33 | 18.69 | 0.00 | 18.69 | 0.00 | 18.69 | 0.00 | 18.69 |
December | 6.83 | 17.96 | 0.17 | 17.89 | 0.00 | 17.89 | 0.00 | 17.89 |
Annual Sum or Average | 22.33 | 18.46 | 0.17 | 18.43 | 16.00 | 22.39 | 16.00 | 24.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.89 | 0.00 | 17.89 |
Maximum of Months | 6.83 | 19.21 | 0.17 | 19.21 | 4.50 | 28.25 | 4.50 | 28.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.83 | 18.53 | 0.00 | 18.53 | 0.00 | 18.53 | 0.00 | 18.53 |
February | 2.83 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
March | 1.50 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.58 | 1.67 | 28.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.69 | 0.83 | 27.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.59 | 1.67 | 27.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.92 | 4.00 | 27.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.09 | 5.67 | 28.09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.16 | 5.67 | 28.16 |
October | 0.17 | 19.42 | 0.00 | 19.42 | 1.17 | 26.99 | 1.17 | 27.49 |
November | 2.50 | 18.66 | 0.00 | 18.66 | 0.50 | 20.19 | 0.50 | 21.28 |
December | 5.17 | 18.86 | 0.00 | 18.86 | 0.00 | 18.86 | 0.00 | 18.86 |
Annual Sum or Average | 16.00 | 18.82 | 0.00 | 18.82 | 21.50 | 24.12 | 21.17 | 25.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.53 | 0.00 | 18.53 |
Maximum of Months | 5.17 | 19.42 | 0.00 | 19.42 | 5.67 | 28.58 | 5.67 | 28.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.67 | 18.53 | 0.00 | 18.53 | 0.00 | 18.53 | 0.00 | 18.53 |
February | 2.00 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
March | 0.67 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.64 | 1.17 | 28.67 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.21 | 2.00 | 28.25 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.48 | 1.83 | 28.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 28.56 | 3.17 | 28.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.42 | 2.83 | 28.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.01 | 1.67 | 28.01 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.83 | 18.59 | 0.00 | 18.59 | 0.00 | 18.59 | 0.00 | 18.59 |
December | 4.50 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
Annual Sum or Average | 12.67 | 18.80 | 0.00 | 18.80 | 23.00 | 25.01 | 12.67 | 25.92 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.50 | 19.11 | 0.00 | 19.11 | 7.00 | 28.64 | 3.17 | 28.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 57.50 | 25.13 | 135.50 | 25.82 | 13.67 | 26.02 |
February | 16.17 | 24.00 | 117.50 | 25.81 | 0.00 | 25.81 |
March | 19.17 | 24.00 | 118.83 | 25.78 | 0.00 | 25.78 |
April | 0.00 | 0.00 | 135.00 | 26.31 | 0.00 | 26.31 |
May | 0.50 | 26.33 | 224.50 | 25.37 | 0.33 | 25.38 |
June | 0.00 | 0.00 | 355.67 | 24.83 | 0.00 | 24.83 |
July | 17.50 | 27.51 | 451.33 | 25.02 | 17.50 | 25.11 |
August | 4.17 | 27.54 | 455.50 | 24.74 | 4.17 | 24.77 |
September | 11.00 | 27.46 | 357.50 | 25.00 | 11.00 | 25.07 |
October | 1.17 | 28.02 | 251.67 | 25.41 | 1.17 | 25.43 |
November | 2.50 | 25.51 | 210.17 | 25.59 | 1.00 | 25.60 |
December | 18.50 | 24.00 | 137.17 | 25.94 | 0.00 | 25.94 |
Annual Sum or Average | 148.17 | 25.27 | 2950.33 | 25.27 | 48.83 | 25.31 |
Minimum of Months | 0.00 | 0.00 | 117.50 | 24.74 | 0.00 | 24.77 |
Maximum of Months | 57.50 | 28.02 | 455.50 | 26.31 | 17.50 | 26.31 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 153.17 | 23.76 | 55.50 | 24.25 | 0.00 | 24.25 |
February | 89.00 | 23.84 | 56.83 | 24.49 | 0.00 | 24.49 |
March | 34.67 | 23.91 | 79.50 | 25.20 | 0.00 | 25.20 |
April | 2.83 | 23.95 | 100.33 | 25.52 | 0.00 | 25.52 |
May | 12.50 | 23.82 | 162.67 | 24.68 | 0.00 | 24.68 |
June | 0.00 | 0.00 | 350.67 | 24.37 | 0.00 | 24.37 |
July | 0.00 | 0.00 | 436.67 | 24.36 | 0.00 | 24.36 |
August | 0.00 | 0.00 | 461.83 | 24.31 | 0.00 | 24.31 |
September | 0.33 | 23.79 | 311.50 | 24.38 | 0.00 | 24.38 |
October | 9.83 | 23.76 | 205.33 | 24.89 | 0.00 | 24.89 |
November | 26.33 | 23.91 | 157.67 | 24.98 | 0.00 | 24.98 |
December | 60.83 | 23.87 | 91.17 | 24.99 | 0.00 | 24.99 |
Annual Sum or Average | 389.50 | 23.82 | 2469.67 | 24.56 | 0.00 | 24.56 |
Minimum of Months | 0.00 | 0.00 | 55.50 | 24.25 | 0.00 | 24.25 |
Maximum of Months | 153.17 | 23.95 | 461.83 | 25.52 | 0.00 | 25.52 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 429.33 | 23.21 | 12.50 | 23.19 | 12.50 | 23.18 |
February | 366.00 | 23.33 | 0.00 | 23.33 | 0.00 | 23.33 |
March | 380.17 | 23.50 | 0.00 | 23.50 | 0.00 | 23.50 |
April | 181.33 | 23.66 | 21.67 | 23.84 | 0.00 | 23.84 |
May | 149.50 | 23.53 | 69.67 | 23.86 | 0.00 | 23.86 |
June | 37.83 | 23.55 | 217.83 | 24.23 | 0.00 | 24.23 |
July | 34.17 | 23.46 | 263.50 | 24.19 | 0.00 | 24.19 |
August | 8.67 | 23.46 | 277.67 | 24.23 | 0.00 | 24.23 |
September | 74.83 | 23.52 | 159.00 | 24.09 | 0.00 | 24.09 |
October | 216.67 | 23.45 | 34.17 | 23.60 | 0.00 | 23.60 |
November | 343.50 | 23.41 | 2.50 | 23.41 | 0.00 | 23.41 |
December | 466.33 | 23.06 | 0.00 | 23.06 | 0.00 | 23.06 |
Annual Sum or Average | 2688.33 | 23.35 | 1058.50 | 23.63 | 12.50 | 23.62 |
Minimum of Months | 8.67 | 23.06 | 0.00 | 23.06 | 0.00 | 23.06 |
Maximum of Months | 466.33 | 23.66 | 277.67 | 24.23 | 12.50 | 24.23 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.50 | 21.53 | 108.67 | 21.25 | 108.67 | 21.06 |
February | 454.00 | 21.81 | 72.33 | 21.56 | 72.33 | 21.38 |
March | 510.83 | 22.30 | 24.33 | 22.21 | 24.33 | 22.13 |
April | 343.83 | 23.13 | 1.33 | 23.14 | 0.00 | 23.14 |
May | 288.17 | 23.11 | 49.50 | 23.26 | 0.00 | 23.26 |
June | 140.67 | 23.28 | 182.50 | 23.78 | 0.00 | 23.78 |
July | 127.83 | 23.24 | 238.00 | 23.87 | 0.00 | 23.87 |
August | 118.00 | 23.31 | 226.83 | 23.86 | 0.00 | 23.86 |
September | 233.17 | 23.02 | 94.17 | 23.33 | 0.00 | 23.33 |
October | 444.67 | 22.50 | 0.00 | 22.50 | 0.00 | 22.50 |
November | 479.33 | 21.97 | 48.00 | 21.83 | 48.00 | 21.71 |
December | 497.00 | 21.40 | 119.00 | 21.10 | 119.00 | 20.91 |
Annual Sum or Average | 4138.00 | 22.29 | 1164.67 | 22.41 | 372.33 | 22.25 |
Minimum of Months | 118.00 | 21.40 | 0.00 | 21.10 | 0.00 | 20.91 |
Maximum of Months | 510.83 | 23.31 | 238.00 | 23.87 | 119.00 | 23.87 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.67 | 22.44 | 16.83 | 22.39 | 16.83 | 22.35 |
February | 437.83 | 22.66 | 0.00 | 22.66 | 0.00 | 22.66 |
March | 446.83 | 23.16 | 5.33 | 23.18 | 0.00 | 23.18 |
April | 220.17 | 23.53 | 18.67 | 23.65 | 0.00 | 23.65 |
May | 196.17 | 23.46 | 65.83 | 23.68 | 0.00 | 23.68 |
June | 39.00 | 23.65 | 269.67 | 24.19 | 0.00 | 24.19 |
July | 5.33 | 23.70 | 368.33 | 24.33 | 0.00 | 24.33 |
August | 20.17 | 23.63 | 349.83 | 24.21 | 0.00 | 24.21 |
September | 165.00 | 23.37 | 125.67 | 23.73 | 0.00 | 23.73 |
October | 334.17 | 23.15 | 19.50 | 23.24 | 0.00 | 23.24 |
November | 428.50 | 23.00 | 0.00 | 23.00 | 0.00 | 23.00 |
December | 497.00 | 22.64 | 0.00 | 22.64 | 0.00 | 22.64 |
Annual Sum or Average | 3286.83 | 22.95 | 1239.67 | 23.31 | 16.83 | 23.30 |
Minimum of Months | 5.33 | 22.44 | 0.00 | 22.39 | 0.00 | 22.35 |
Maximum of Months | 497.00 | 23.70 | 368.33 | 24.33 | 16.83 | 24.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 481.00 | 22.00 | 22.00 | 22.00 | 17.50 | 21.97 |
February | 425.83 | 22.15 | 5.00 | 22.18 | 0.00 | 22.18 |
March | 467.00 | 22.47 | 2.67 | 22.49 | 0.00 | 22.49 |
April | 203.50 | 23.12 | 109.00 | 23.60 | 4.67 | 23.65 |
May | 181.00 | 23.17 | 180.00 | 23.85 | 6.33 | 23.91 |
June | 105.83 | 23.68 | 305.83 | 24.14 | 12.67 | 24.23 |
July | 75.17 | 24.38 | 351.33 | 24.43 | 23.83 | 24.56 |
August | 97.17 | 23.75 | 339.67 | 24.18 | 16.00 | 24.27 |
September | 170.33 | 23.37 | 244.67 | 24.00 | 15.83 | 24.10 |
October | 359.67 | 22.61 | 55.33 | 22.87 | 0.50 | 22.87 |
November | 470.50 | 22.35 | 2.50 | 22.36 | 0.00 | 22.36 |
December | 492.00 | 21.84 | 11.67 | 21.82 | 11.67 | 21.80 |
Annual Sum or Average | 3529.00 | 22.51 | 1629.67 | 23.09 | 109.00 | 23.14 |
Minimum of Months | 75.17 | 21.84 | 2.50 | 21.82 | 0.00 | 21.80 |
Maximum of Months | 492.00 | 24.38 | 351.33 | 24.43 | 23.83 | 24.56 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 409.17 | 21.97 | 66.00 | 22.27 | 14.83 | 22.26 |
February | 344.17 | 22.18 | 64.83 | 22.53 | 5.33 | 22.54 |
March | 418.00 | 22.46 | 11.67 | 22.51 | 0.00 | 22.51 |
April | 201.00 | 23.25 | 158.00 | 23.76 | 7.83 | 23.84 |
May | 221.67 | 22.99 | 156.67 | 23.59 | 3.00 | 23.62 |
June | 113.83 | 23.42 | 275.83 | 24.02 | 8.17 | 24.08 |
July | 83.50 | 24.17 | 340.50 | 24.36 | 21.50 | 24.48 |
August | 88.00 | 24.28 | 371.67 | 24.34 | 25.00 | 24.48 |
September | 157.00 | 23.63 | 270.17 | 24.16 | 24.50 | 24.32 |
October | 315.67 | 22.75 | 126.67 | 23.23 | 5.83 | 23.28 |
November | 393.50 | 22.42 | 50.17 | 22.70 | 3.83 | 22.73 |
December | 438.33 | 21.88 | 45.00 | 22.03 | 15.17 | 21.99 |
Annual Sum or Average | 3183.83 | 22.58 | 1937.17 | 23.26 | 135.00 | 23.32 |
Minimum of Months | 83.50 | 21.88 | 11.67 | 22.03 | 0.00 | 21.99 |
Maximum of Months | 438.33 | 24.28 | 371.67 | 24.36 | 25.00 | 24.48 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 448.33 | 22.47 | 14.33 | 22.53 | 0.83 | 22.53 |
February | 322.67 | 22.99 | 47.50 | 23.19 | 0.50 | 23.20 |
March | 205.67 | 23.29 | 65.83 | 23.79 | 0.00 | 23.79 |
April | 25.00 | 24.87 | 289.50 | 24.84 | 9.33 | 24.91 |
May | 115.67 | 23.54 | 225.17 | 24.21 | 12.17 | 24.31 |
June | 24.67 | 26.04 | 434.33 | 24.55 | 19.67 | 24.64 |
July | 28.50 | 26.88 | 481.67 | 24.71 | 28.50 | 24.83 |
August | 24.00 | 27.10 | 506.33 | 24.62 | 24.00 | 24.72 |
September | 96.17 | 23.71 | 289.83 | 24.25 | 15.00 | 24.35 |
October | 180.00 | 23.16 | 155.50 | 23.92 | 2.33 | 23.94 |
November | 222.67 | 23.22 | 100.33 | 23.75 | 0.00 | 23.75 |
December | 295.17 | 23.27 | 32.83 | 23.49 | 0.00 | 23.49 |
Annual Sum or Average | 1988.50 | 23.22 | 2643.17 | 24.01 | 112.33 | 24.08 |
Minimum of Months | 24.00 | 22.47 | 14.33 | 22.53 | 0.00 | 22.53 |
Maximum of Months | 448.33 | 27.10 | 506.33 | 24.84 | 28.50 | 24.91 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.96 | 214.17 | 20.80 | 214.17 | 20.71 |
February | 454.00 | 21.10 | 139.50 | 20.93 | 139.50 | 20.82 |
March | 514.00 | 21.71 | 50.00 | 21.61 | 50.00 | 21.54 |
April | 411.00 | 22.76 | 5.00 | 22.75 | 3.67 | 22.73 |
May | 357.83 | 22.95 | 28.33 | 23.02 | 0.00 | 23.02 |
June | 154.50 | 23.29 | 150.17 | 23.72 | 0.00 | 23.72 |
July | 124.83 | 23.30 | 215.83 | 23.84 | 0.00 | 23.84 |
August | 167.67 | 23.20 | 178.83 | 23.63 | 0.00 | 23.63 |
September | 321.50 | 22.85 | 53.00 | 23.01 | 0.00 | 23.01 |
October | 491.17 | 22.06 | 11.50 | 22.02 | 11.50 | 21.99 |
November | 489.00 | 21.27 | 93.83 | 21.14 | 93.83 | 21.04 |
December | 497.00 | 20.69 | 252.33 | 20.54 | 252.33 | 20.47 |
Annual Sum or Average | 4484.50 | 21.87 | 1392.50 | 21.92 | 765.00 | 21.74 |
Minimum of Months | 124.83 | 20.69 | 5.00 | 20.54 | 0.00 | 20.47 |
Maximum of Months | 514.00 | 23.30 | 252.33 | 23.84 | 252.33 | 23.84 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.95 | 165.17 | 20.83 | 165.17 | 20.76 |
February | 382.67 | 21.17 | 100.67 | 21.03 | 100.67 | 20.94 |
March | 430.33 | 21.46 | 49.83 | 21.38 | 49.83 | 21.32 |
April | 237.50 | 22.59 | 65.33 | 23.01 | 6.67 | 23.07 |
May | 232.83 | 22.69 | 117.50 | 23.35 | 6.33 | 23.41 |
June | 159.33 | 23.21 | 194.00 | 23.90 | 12.50 | 24.01 |
July | 133.17 | 23.65 | 243.17 | 24.29 | 21.83 | 24.44 |
August | 156.67 | 23.37 | 220.17 | 23.98 | 16.50 | 24.11 |
September | 208.67 | 22.84 | 151.17 | 23.58 | 12.83 | 23.70 |
October | 377.33 | 21.77 | 20.67 | 21.86 | 6.00 | 21.83 |
November | 416.00 | 21.14 | 76.00 | 21.04 | 76.00 | 20.97 |
December | 422.00 | 20.65 | 233.33 | 20.52 | 233.33 | 20.46 |
Annual Sum or Average | 3583.50 | 21.75 | 1637.00 | 22.13 | 707.67 | 22.01 |
Minimum of Months | 133.17 | 20.65 | 20.67 | 20.52 | 6.00 | 20.46 |
Maximum of Months | 430.33 | 23.65 | 243.17 | 24.29 | 233.33 | 24.44 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 430.17 | 21.51 | 143.83 | 21.64 | 98.50 | 21.52 |
February | 362.50 | 21.64 | 98.00 | 21.91 | 46.17 | 21.81 |
March | 463.00 | 21.80 | 35.33 | 21.76 | 29.83 | 21.70 |
April | 255.33 | 22.68 | 142.50 | 23.34 | 7.33 | 23.41 |
May | 291.33 | 22.64 | 137.17 | 23.22 | 3.83 | 23.25 |
June | 198.83 | 23.00 | 223.00 | 23.68 | 5.50 | 23.72 |
July | 165.83 | 23.33 | 262.50 | 23.99 | 18.83 | 24.12 |
August | 156.00 | 23.53 | 293.83 | 24.05 | 23.67 | 24.20 |
September | 201.67 | 23.24 | 246.00 | 23.92 | 25.00 | 24.09 |
October | 352.00 | 22.12 | 109.83 | 22.64 | 8.67 | 22.69 |
November | 418.83 | 21.61 | 75.67 | 21.82 | 38.83 | 21.77 |
December | 463.33 | 21.14 | 186.67 | 21.04 | 168.67 | 20.90 |
Annual Sum or Average | 3758.83 | 22.08 | 1954.33 | 22.63 | 474.83 | 22.57 |
Minimum of Months | 156.00 | 21.14 | 35.33 | 21.04 | 3.83 | 20.90 |
Maximum of Months | 463.33 | 23.53 | 293.83 | 24.05 | 168.67 | 24.20 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 498.50 | 21.14 | 141.50 | 21.02 | 141.50 | 20.94 |
February | 423.83 | 21.30 | 69.67 | 21.23 | 63.83 | 21.15 |
March | 498.83 | 21.63 | 26.17 | 21.60 | 22.83 | 21.57 |
April | 329.67 | 22.73 | 78.17 | 23.04 | 6.50 | 23.11 |
May | 315.33 | 22.77 | 131.00 | 23.25 | 8.50 | 23.32 |
June | 154.00 | 23.15 | 248.67 | 23.89 | 10.50 | 23.96 |
July | 133.33 | 23.36 | 310.50 | 24.09 | 15.67 | 24.19 |
August | 136.00 | 23.29 | 286.83 | 23.96 | 14.17 | 24.06 |
September | 275.67 | 22.73 | 144.83 | 23.30 | 10.00 | 23.39 |
October | 444.50 | 21.89 | 27.00 | 22.03 | 0.00 | 22.03 |
November | 481.83 | 21.32 | 56.00 | 21.24 | 56.00 | 21.18 |
December | 497.00 | 20.84 | 203.17 | 20.72 | 203.17 | 20.66 |
Annual Sum or Average | 4188.50 | 21.85 | 1723.50 | 22.26 | 552.67 | 22.18 |
Minimum of Months | 133.33 | 20.84 | 26.17 | 20.72 | 0.00 | 20.66 |
Maximum of Months | 498.83 | 23.36 | 310.50 | 24.09 | 203.17 | 24.19 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.27 | 358.67 | 20.13 | 358.67 | 20.07 |
February | 454.00 | 20.38 | 277.83 | 20.19 | 277.83 | 20.11 |
March | 514.00 | 20.97 | 220.33 | 20.79 | 220.33 | 20.69 |
April | 434.67 | 22.16 | 56.17 | 22.00 | 53.67 | 21.85 |
May | 411.83 | 22.38 | 41.50 | 22.44 | 10.67 | 22.40 |
June | 216.83 | 22.86 | 132.33 | 23.35 | 0.00 | 23.35 |
July | 189.67 | 22.92 | 199.33 | 23.56 | 0.00 | 23.56 |
August | 233.50 | 22.87 | 158.50 | 23.34 | 0.00 | 23.34 |
September | 367.67 | 22.30 | 48.17 | 22.43 | 7.50 | 22.38 |
October | 502.00 | 21.22 | 120.33 | 21.00 | 120.33 | 20.85 |
November | 489.00 | 20.52 | 259.50 | 20.32 | 259.50 | 20.23 |
December | 497.00 | 20.09 | 398.83 | 19.99 | 398.83 | 19.95 |
Annual Sum or Average | 4812.17 | 21.32 | 2271.50 | 21.22 | 1707.33 | 20.98 |
Minimum of Months | 189.67 | 20.09 | 41.50 | 19.99 | 0.00 | 19.95 |
Maximum of Months | 514.00 | 22.92 | 398.83 | 23.56 | 398.83 | 23.56 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.39 | 335.17 | 20.24 | 335.17 | 20.18 |
February | 454.00 | 20.62 | 245.67 | 20.42 | 245.67 | 20.33 |
March | 514.00 | 21.01 | 198.50 | 20.85 | 198.50 | 20.76 |
April | 290.00 | 22.31 | 90.83 | 22.61 | 25.17 | 22.56 |
May | 287.83 | 22.39 | 135.00 | 22.99 | 7.50 | 23.00 |
June | 190.33 | 22.89 | 239.83 | 23.70 | 11.33 | 23.78 |
July | 155.00 | 23.31 | 306.17 | 24.10 | 20.33 | 24.22 |
August | 177.50 | 23.06 | 287.33 | 23.82 | 13.33 | 23.91 |
September | 232.67 | 22.34 | 195.50 | 23.25 | 8.17 | 23.28 |
October | 449.33 | 21.24 | 104.67 | 21.11 | 97.00 | 20.98 |
November | 489.00 | 20.61 | 228.67 | 20.42 | 228.67 | 20.33 |
December | 497.00 | 20.16 | 382.17 | 20.05 | 382.17 | 20.01 |
Annual Sum or Average | 4238.67 | 21.28 | 2749.50 | 21.57 | 1573.00 | 21.34 |
Minimum of Months | 155.00 | 20.16 | 90.83 | 20.05 | 7.50 | 20.01 |
Maximum of Months | 514.00 | 23.31 | 382.17 | 24.10 | 382.17 | 24.22 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 456.50 | 20.85 | 259.17 | 20.72 | 242.00 | 20.59 |
February | 390.83 | 21.04 | 197.50 | 20.99 | 163.67 | 20.82 |
March | 491.33 | 21.24 | 167.50 | 21.04 | 167.50 | 20.92 |
April | 285.83 | 22.20 | 147.17 | 22.72 | 33.17 | 22.66 |
May | 326.17 | 22.13 | 132.67 | 22.69 | 13.50 | 22.65 |
June | 234.17 | 22.56 | 204.17 | 23.35 | 6.00 | 23.40 |
July | 198.67 | 22.89 | 248.00 | 23.73 | 17.67 | 23.85 |
August | 198.83 | 23.10 | 267.67 | 23.79 | 22.50 | 23.94 |
September | 234.17 | 22.64 | 231.67 | 23.50 | 26.00 | 23.62 |
October | 394.00 | 21.54 | 136.67 | 21.84 | 58.17 | 21.74 |
November | 447.67 | 21.02 | 192.00 | 20.93 | 170.33 | 20.79 |
December | 480.83 | 20.56 | 316.33 | 20.38 | 311.50 | 20.28 |
Annual Sum or Average | 4139.00 | 21.56 | 2500.50 | 21.90 | 1232.00 | 21.71 |
Minimum of Months | 198.67 | 20.56 | 132.67 | 20.38 | 6.00 | 20.28 |
Maximum of Months | 491.33 | 23.10 | 316.33 | 23.79 | 311.50 | 23.94 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.50 | 20.59 | 291.50 | 20.42 | 291.50 | 20.34 |
February | 436.83 | 20.84 | 192.50 | 20.64 | 190.50 | 20.53 |
March | 503.33 | 21.12 | 151.67 | 21.00 | 149.33 | 20.92 |
April | 362.33 | 22.25 | 92.67 | 22.51 | 26.50 | 22.49 |
May | 349.50 | 22.29 | 121.33 | 22.82 | 9.67 | 22.88 |
June | 216.00 | 22.79 | 227.33 | 23.58 | 10.83 | 23.65 |
July | 171.83 | 22.94 | 284.50 | 23.84 | 15.17 | 23.95 |
August | 199.50 | 22.95 | 246.17 | 23.68 | 14.83 | 23.79 |
September | 316.00 | 22.25 | 127.00 | 22.83 | 10.50 | 22.89 |
October | 461.67 | 21.34 | 74.50 | 21.34 | 53.00 | 21.25 |
November | 484.33 | 20.81 | 185.83 | 20.64 | 185.83 | 20.54 |
December | 497.00 | 20.37 | 351.17 | 20.25 | 351.17 | 20.20 |
Annual Sum or Average | 4498.83 | 21.43 | 2346.17 | 21.67 | 1308.83 | 21.49 |
Minimum of Months | 171.83 | 20.37 | 74.50 | 20.25 | 9.67 | 20.20 |
Maximum of Months | 503.33 | 22.95 | 351.17 | 23.84 | 351.17 | 23.95 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 7.83 | 27.00 | 454.00 | 27.00 | 7.83 | 27.00 |
March | 3.83 | 27.00 | 514.00 | 27.00 | 3.83 | 27.00 |
April | 88.33 | 27.00 | 485.00 | 27.00 | 88.33 | 27.00 |
May | 14.83 | 27.00 | 508.00 | 27.00 | 14.83 | 27.00 |
June | 74.83 | 27.00 | 496.00 | 27.00 | 74.83 | 27.00 |
July | 195.67 | 27.00 | 497.00 | 27.00 | 195.67 | 27.00 |
August | 328.17 | 27.00 | 514.00 | 27.00 | 328.17 | 27.00 |
September | 25.17 | 27.00 | 485.00 | 27.00 | 25.17 | 27.00 |
October | 14.17 | 27.00 | 502.00 | 27.00 | 14.17 | 27.00 |
November | 5.67 | 27.00 | 489.00 | 27.00 | 5.67 | 27.00 |
December | 1.00 | 27.00 | 497.00 | 27.00 | 1.00 | 27.00 |
Annual Sum or Average | 759.50 | 27.00 | 5943.00 | 27.00 | 759.50 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 328.17 | 27.00 | 514.00 | 27.00 | 328.17 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 490.33 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
April | 13.33 | 27.00 | 485.00 | 27.00 | 13.33 | 27.00 |
May | 5.67 | 27.00 | 508.00 | 27.00 | 5.67 | 27.00 |
June | 14.67 | 27.00 | 496.00 | 27.00 | 14.67 | 27.00 |
July | 28.50 | 27.00 | 497.00 | 27.00 | 28.50 | 27.00 |
August | 43.50 | 27.00 | 514.00 | 27.00 | 43.50 | 27.00 |
September | 6.33 | 27.00 | 485.00 | 27.00 | 6.33 | 27.00 |
October | 1.00 | 27.00 | 502.00 | 27.00 | 1.00 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 488.17 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 113.00 | 27.00 | 5922.50 | 27.00 | 113.00 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 43.50 | 27.00 | 514.00 | 27.00 | 43.50 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 83.17 | 25.25 | 333.67 | 26.65 | 0.00 | 26.65 |
February | 1.83 | 27.00 | 382.83 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 484.33 | 27.00 | 0.00 | 27.00 |
April | 17.83 | 27.00 | 485.00 | 27.00 | 17.83 | 27.00 |
May | 10.33 | 27.00 | 508.00 | 27.00 | 10.33 | 27.00 |
June | 31.83 | 27.00 | 496.00 | 27.00 | 31.83 | 27.00 |
July | 58.50 | 27.00 | 497.00 | 27.00 | 58.50 | 27.00 |
August | 62.33 | 27.00 | 514.00 | 27.00 | 62.33 | 27.00 |
September | 8.67 | 27.00 | 485.00 | 27.00 | 8.67 | 27.00 |
October | 0.83 | 27.00 | 500.33 | 27.00 | 0.83 | 27.00 |
November | 0.00 | 0.00 | 448.83 | 27.00 | 0.00 | 27.00 |
December | 5.67 | 27.00 | 394.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 281.00 | 26.48 | 5529.00 | 26.97 | 190.33 | 26.98 |
Minimum of Months | 0.00 | 0.00 | 333.67 | 26.65 | 0.00 | 26.65 |
Maximum of Months | 83.17 | 27.00 | 514.00 | 27.00 | 62.33 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 368.33 | 27.00 | 502.00 | 27.00 | 368.33 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 27.01 | 514.00 | 27.01 | 514.00 | 27.01 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5809.33 | 27.00 | 5943.00 | 27.00 | 5809.33 | 27.00 |
Minimum of Months | 368.33 | 27.00 | 454.00 | 27.00 | 368.33 | 27.00 |
Maximum of Months | 514.00 | 27.01 | 514.00 | 27.01 | 514.00 | 27.01 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00001 | 27.62950 | 0.79741 | 18.52730 |
February | 454.00000 | 27.00000 | 27.91910 | 0.85287 | 20.44336 |
March | 514.00000 | 27.00000 | 27.80104 | 0.89767 | 22.07817 |
April | 485.00000 | 27.00000 | 28.42671 | 0.98062 | 25.37670 |
May | 508.00000 | 27.00015 | 32.78652 | 0.24191 | 6.35371 |
June | 496.00000 | 27.00047 | 35.84389 | 0.34328 | 7.53913 |
July | 497.00000 | 27.00035 | 36.05964 | 0.40181 | 8.44187 |
August | 514.00000 | 27.00017 | 36.18658 | 0.43999 | 9.10789 |
September | 485.00000 | 27.00046 | 36.09695 | 0.27084 | 6.64305 |
October | 502.00000 | 27.00015 | 32.70474 | 0.91956 | 22.91471 |
November | 489.00000 | 27.00007 | 30.55058 | 0.91600 | 22.78994 |
December | 497.00000 | 27.00000 | 26.72963 | 0.89527 | 21.98863 |
Annual Sum or Average | 5943.00000 | 27.00015 | 31.58780 | 0.66118 | 15.96495 |
Minimum of Months | 454.00000 | 27.00000 | 26.72963 | 0.24191 | 6.35371 |
Maximum of Months | 514.00000 | 27.00047 | 36.18658 | 0.98062 | 25.37670 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00003 | 27.62956 | 0.68839 | 15.10030 |
February | 454.00000 | 27.00001 | 27.90470 | 0.72574 | 16.23455 |
March | 514.00000 | 27.00000 | 27.79101 | 0.75273 | 17.03212 |
April | 485.00000 | 27.00000 | 28.41816 | 0.85206 | 20.46484 |
May | 508.00000 | 27.00014 | 32.78893 | 0.14960 | 5.68453 |
June | 496.00000 | 27.00045 | 35.86537 | 0.23993 | 6.34599 |
July | 497.00000 | 27.00038 | 36.06869 | 0.27012 | 6.67387 |
August | 514.00000 | 27.00020 | 36.18917 | 0.28860 | 6.86988 |
September | 485.00000 | 27.00043 | 36.18495 | 0.17962 | 5.85343 |
October | 502.00000 | 27.00014 | 32.71044 | 0.80577 | 18.79032 |
November | 489.00000 | 27.00006 | 30.53314 | 0.75819 | 17.21708 |
December | 497.00000 | 27.00000 | 26.71368 | 0.69878 | 15.37435 |
Annual Sum or Average | 5943.00000 | 27.00015 | 31.59301 | 0.53213 | 12.59398 |
Minimum of Months | 454.00000 | 27.00000 | 26.71368 | 0.14960 | 5.68453 |
Maximum of Months | 514.00000 | 27.00045 | 36.18917 | 0.85206 | 20.46484 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.65792 | 28.43956 | 0.53980 | 12.02939 |
February | 454.00000 | 27.00001 | 27.91278 | 0.64364 | 13.96429 |
March | 514.00000 | 27.00000 | 27.79509 | 0.68039 | 14.90529 |
April | 485.00000 | 27.00000 | 28.42102 | 0.81035 | 19.12944 |
May | 508.00000 | 27.00016 | 32.80203 | 0.10220 | 5.64342 |
June | 496.00000 | 27.00045 | 35.88007 | 0.21634 | 6.27288 |
July | 497.00000 | 27.00038 | 36.07987 | 0.25310 | 6.64361 |
August | 514.00000 | 27.00021 | 36.19981 | 0.26630 | 6.74171 |
September | 485.00000 | 27.00041 | 36.25504 | 0.13298 | 5.72375 |
October | 502.00000 | 27.00013 | 32.74803 | 0.73663 | 16.61634 |
November | 489.00000 | 27.00006 | 30.55384 | 0.67637 | 14.80244 |
December | 497.00000 | 27.00000 | 26.71903 | 0.61436 | 13.11580 |
Annual Sum or Average | 5943.00000 | 26.97126 | 31.67788 | 0.47084 | 11.26322 |
Minimum of Months | 454.00000 | 26.65792 | 26.71903 | 0.10220 | 5.64342 |
Maximum of Months | 514.00000 | 27.00045 | 36.25504 | 0.81035 | 19.12944 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00001 | 30.07502 | 1.04373 | 28.00866 |
February | 454.00000 | 27.00023 | 30.01294 | 1.20644 | 35.57033 |
March | 514.00000 | 27.00020 | 29.82371 | 1.35631 | 43.20191 |
April | 485.00000 | 27.00069 | 28.44954 | 1.49742 | 50.76227 |
May | 508.00000 | 26.99999 | 30.97797 | 0.49720 | 10.23398 |
June | 496.00000 | 27.00056 | 35.15975 | 0.76338 | 17.32519 |
July | 497.00000 | 27.00335 | 36.43876 | 0.98551 | 25.56232 |
August | 514.00000 | 27.01321 | 35.06122 | 1.17021 | 33.82062 |
September | 485.00000 | 26.99986 | 34.71095 | 0.55384 | 11.51704 |
October | 502.00000 | 27.00006 | 31.38251 | 1.24610 | 37.54461 |
November | 489.00000 | 27.00020 | 30.47277 | 1.37537 | 44.20910 |
December | 497.00000 | 27.00034 | 28.62131 | 1.48112 | 49.87867 |
Annual Sum or Average | 5943.00000 | 27.00160 | 31.78081 | 1.09716 | 32.26591 |
Minimum of Months | 454.00000 | 26.99986 | 28.44954 | 0.49720 | 10.23398 |
Maximum of Months | 514.00000 | 27.01321 | 36.43876 | 1.49742 | 50.76227 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.63454 | 30.30140 | 0.44323 | 10.55017 |
February | 454.00000 | 24.57168 | 28.94030 | 0.41501 | 8.99972 |
March | 514.00000 | 24.50876 | 28.21835 | 0.40459 | 8.84543 |
April | 485.00000 | 24.65787 | 27.92373 | 0.44682 | 9.77384 |
May | 508.00000 | 24.61311 | 34.29318 | -0.3668 | 8.84680 |
June | 496.00000 | 24.59797 | 41.75251 | -0.3060 | 7.99991 |
July | 497.00000 | 24.83977 | 43.85600 | -0.2121 | 7.68377 |
August | 514.00000 | 24.63677 | 44.22010 | -0.2609 | 7.66561 |
September | 485.00000 | 24.68016 | 41.49986 | -0.2827 | 8.09828 |
October | 502.00000 | 24.70701 | 34.56727 | 0.50137 | 10.90465 |
November | 489.00000 | 24.69376 | 31.57314 | 0.47450 | 10.34961 |
December | 497.00000 | 24.63867 | 27.36556 | 0.42459 | 9.32324 |
Annual Sum or Average | 5943.00000 | 24.64830 | 34.59084 | 0.13723 | 9.08403 |
Minimum of Months | 454.00000 | 24.50876 | 27.36556 | -0.3668 | 7.66561 |
Maximum of Months | 514.00000 | 24.83977 | 44.22010 | 0.50137 | 10.90465 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.20716 | 30.22082 | 0.33715 | 7.72852 |
February | 454.00000 | 24.23901 | 30.60127 | 0.35427 | 7.79266 |
March | 514.00000 | 24.30020 | 29.67421 | 0.37574 | 8.22602 |
April | 485.00000 | 24.34332 | 29.06943 | 0.40879 | 8.76490 |
May | 508.00000 | 24.25424 | 35.42187 | -0.4536 | 9.68381 |
June | 496.00000 | 24.26208 | 43.08702 | -0.3738 | 8.28295 |
July | 497.00000 | 24.31880 | 44.92323 | -0.3303 | 7.67493 |
August | 514.00000 | 24.27937 | 45.31923 | -0.3298 | 7.64269 |
September | 485.00000 | 24.24711 | 42.46553 | -0.3958 | 8.62107 |
October | 502.00000 | 24.39262 | 36.45865 | 0.44637 | 9.51866 |
November | 489.00000 | 24.39447 | 33.46997 | 0.42221 | 9.06475 |
December | 497.00000 | 24.35377 | 29.00476 | 0.37392 | 8.22043 |
Annual Sum or Average | 5943.00000 | 24.29954 | 35.85422 | 0.06669 | 8.43767 |
Minimum of Months | 454.00000 | 24.20716 | 29.00476 | -0.4536 | 7.64269 |
Maximum of Months | 514.00000 | 24.39447 | 45.31923 | 0.44637 | 9.68381 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.32394 | 34.65459 | 0.11126 | 5.80915 |
February | 454.00000 | 23.45553 | 33.28359 | 0.14107 | 5.86458 |
March | 514.00000 | 23.64204 | 32.56778 | 0.18895 | 6.06151 |
April | 485.00000 | 24.01672 | 30.81415 | 0.29412 | 6.99634 |
May | 508.00000 | 23.99119 | 36.60189 | -0.5740 | 12.34633 |
June | 496.00000 | 24.09267 | 44.07796 | -0.4707 | 9.93095 |
July | 497.00000 | 24.09201 | 46.11327 | -0.4565 | 9.66283 |
August | 514.00000 | 24.08464 | 46.53448 | -0.4493 | 9.46566 |
September | 485.00000 | 24.00994 | 43.60374 | -0.5091 | 10.74612 |
October | 502.00000 | 23.86797 | 38.62890 | 0.29420 | 7.09269 |
November | 489.00000 | 23.59540 | 36.62400 | 0.19852 | 6.25817 |
December | 497.00000 | 23.12123 | 32.87606 | 0.04582 | 5.64813 |
Annual Sum or Average | 5943.00000 | 23.77658 | 38.07396 | -0.1014 | 8.00821 |
Minimum of Months | 454.00000 | 23.12123 | 30.81415 | -0.5740 | 5.64813 |
Maximum of Months | 514.00000 | 24.09267 | 46.53448 | 0.29420 | 12.34633 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.53773 | 36.32919 | -0.3463 | 9.57231 |
February | 454.00000 | 21.80804 | 36.77766 | -0.2688 | 8.30166 |
March | 514.00000 | 22.30773 | 35.65353 | -0.1452 | 6.67466 |
April | 485.00000 | 23.40120 | 32.54092 | 0.13793 | 6.24905 |
May | 508.00000 | 23.52057 | 38.13265 | -0.7452 | 18.03408 |
June | 496.00000 | 23.87017 | 44.88850 | -0.5495 | 11.97569 |
July | 497.00000 | 23.90038 | 46.82463 | -0.5207 | 11.40986 |
August | 514.00000 | 23.89075 | 47.23142 | -0.5196 | 11.14043 |
September | 485.00000 | 23.55387 | 45.39513 | -0.6758 | 15.75184 |
October | 502.00000 | 22.67121 | 42.21290 | -0.0058 | 6.16221 |
November | 489.00000 | 22.00939 | 40.49522 | -0.1963 | 7.26392 |
December | 497.00000 | 21.39895 | 35.79836 | -0.3875 | 9.97053 |
Annual Sum or Average | 5943.00000 | 22.82978 | 40.22024 | -0.3533 | 10.22622 |
Minimum of Months | 454.00000 | 21.39895 | 32.54092 | -0.7452 | 6.16221 |
Maximum of Months | 514.00000 | 23.90038 | 47.23142 | 0.13793 | 18.03408 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.45436 | 32.51608 | -0.1146 | 6.27761 |
February | 454.00000 | 22.70450 | 32.83017 | -0.0478 | 5.83112 |
March | 514.00000 | 23.29359 | 31.15501 | 0.09169 | 5.84103 |
April | 485.00000 | 23.87734 | 29.39737 | 0.25897 | 6.80786 |
May | 508.00000 | 23.86592 | 35.54167 | -0.6192 | 13.77144 |
June | 496.00000 | 24.13294 | 42.62594 | -0.4321 | 9.36526 |
July | 497.00000 | 24.26049 | 44.33870 | -0.3619 | 8.22051 |
August | 514.00000 | 24.15618 | 45.00630 | -0.4013 | 8.74165 |
September | 485.00000 | 23.83398 | 42.82829 | -0.5800 | 12.80196 |
October | 502.00000 | 23.48140 | 37.93060 | 0.18677 | 6.29866 |
November | 489.00000 | 23.12253 | 35.48951 | 0.07221 | 5.81583 |
December | 497.00000 | 22.64491 | 31.23268 | -0.0760 | 5.71000 |
Annual Sum or Average | 5943.00000 | 23.49142 | 36.77545 | -0.1702 | 7.97162 |
Minimum of Months | 454.00000 | 22.45436 | 29.39737 | -0.6192 | 5.71000 |
Maximum of Months | 514.00000 | 24.26049 | 45.00630 | 0.25897 | 13.77144 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.10958 | 32.17144 | -0.1748 | 6.87082 |
February | 454.00000 | 22.28195 | 32.62705 | -0.1204 | 6.50907 |
March | 514.00000 | 22.63651 | 31.51083 | -0.0364 | 6.12729 |
April | 485.00000 | 23.72622 | 29.10165 | 0.29438 | 8.09241 |
May | 508.00000 | 23.85118 | 35.04645 | -0.5254 | 13.35550 |
June | 496.00000 | 24.02279 | 42.59578 | -0.3840 | 10.03337 |
July | 497.00000 | 24.20456 | 44.28151 | -0.2923 | 8.95557 |
August | 514.00000 | 24.04546 | 45.01577 | -0.3426 | 9.47493 |
September | 485.00000 | 23.88020 | 42.10389 | -0.4573 | 12.20658 |
October | 502.00000 | 23.07213 | 38.13891 | 0.12856 | 6.58715 |
November | 489.00000 | 22.42108 | 36.01321 | -0.0673 | 5.99499 |
December | 497.00000 | 21.86458 | 31.60733 | -0.2389 | 6.96285 |
Annual Sum or Average | 5943.00000 | 23.18237 | 36.72155 | -0.1861 | 8.44350 |
Minimum of Months | 454.00000 | 21.86458 | 29.10165 | -0.5254 | 5.99499 |
Maximum of Months | 514.00000 | 24.20456 | 45.01577 | 0.29438 | 13.35550 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.42854 | 31.64217 | -0.0878 | 7.76905 |
February | 454.00000 | 22.69872 | 31.77908 | -0.0033 | 7.50336 |
March | 514.00000 | 22.76327 | 31.29821 | -0.0068 | 6.35088 |
April | 485.00000 | 23.80252 | 28.92338 | 0.32042 | 8.70168 |
May | 508.00000 | 23.68384 | 35.43697 | -0.6066 | 15.52301 |
June | 496.00000 | 23.96682 | 42.78213 | -0.4342 | 10.60795 |
July | 497.00000 | 24.15646 | 44.36152 | -0.3271 | 9.18124 |
August | 514.00000 | 24.15531 | 44.61710 | -0.2918 | 8.92595 |
September | 485.00000 | 23.98500 | 41.72982 | -0.3800 | 11.57499 |
October | 502.00000 | 23.29496 | 37.53729 | 0.20616 | 7.82477 |
November | 489.00000 | 22.79579 | 35.30176 | 0.03128 | 6.95808 |
December | 497.00000 | 22.19655 | 31.08102 | -0.1582 | 7.59435 |
Annual Sum or Average | 5943.00000 | 23.33082 | 36.41637 | -0.1470 | 9.05406 |
Minimum of Months | 454.00000 | 22.19655 | 28.92338 | -0.6066 | 6.35088 |
Maximum of Months | 514.00000 | 24.15646 | 44.61710 | 0.32042 | 15.52301 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.66434 | 30.82923 | -0.0251 | 6.16629 |
February | 454.00000 | 23.36513 | 30.31277 | 0.16441 | 6.56867 |
March | 514.00000 | 23.93886 | 28.75349 | 0.30513 | 7.65082 |
April | 485.00000 | 24.48299 | 27.58216 | 0.53022 | 11.77964 |
May | 508.00000 | 24.07872 | 34.42839 | -0.4144 | 10.78226 |
June | 496.00000 | 24.38660 | 41.47488 | -0.1826 | 7.36606 |
July | 497.00000 | 24.56379 | 43.14444 | -0.0679 | 7.06958 |
August | 514.00000 | 24.49026 | 43.58178 | -0.0801 | 6.98383 |
September | 485.00000 | 24.06947 | 41.50737 | -0.3719 | 9.97860 |
October | 502.00000 | 23.94694 | 35.96243 | 0.35943 | 8.57001 |
November | 489.00000 | 23.87283 | 32.80284 | 0.30005 | 7.65107 |
December | 497.00000 | 23.75305 | 28.13272 | 0.22790 | 6.69792 |
Annual Sum or Average | 5943.00000 | 23.97142 | 34.91615 | 0.06059 | 8.10526 |
Minimum of Months | 454.00000 | 22.66434 | 27.58216 | -0.4144 | 6.16629 |
Maximum of Months | 514.00000 | 24.56379 | 43.58178 | 0.53022 | 11.77964 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.95999 | 35.42250 | -0.5024 | 11.31638 |
February | 454.00000 | 21.10016 | 36.02655 | -0.4509 | 10.15345 |
March | 514.00000 | 21.70607 | 34.84387 | -0.2967 | 7.73419 |
April | 485.00000 | 22.95401 | 31.97755 | 0.01909 | 6.21606 |
May | 508.00000 | 23.25981 | 37.31948 | -0.8431 | 21.59424 |
June | 496.00000 | 23.82288 | 43.78671 | -0.5704 | 12.67640 |
July | 497.00000 | 23.88763 | 45.62180 | -0.5282 | 11.60490 |
August | 514.00000 | 23.73685 | 46.61149 | -0.5859 | 13.01070 |
September | 485.00000 | 23.22857 | 44.68208 | -0.8061 | 20.25687 |
October | 502.00000 | 22.10614 | 41.68698 | -0.1470 | 6.51166 |
November | 489.00000 | 21.27484 | 39.61241 | -0.3822 | 8.97517 |
December | 497.00000 | 20.69206 | 34.82545 | -0.5802 | 12.90665 |
Annual Sum or Average | 5943.00000 | 22.40392 | 39.39799 | -0.4737 | 11.92833 |
Minimum of Months | 454.00000 | 20.69206 | 31.97755 | -0.8431 | 6.21606 |
Maximum of Months | 514.00000 | 23.88763 | 46.61149 | 0.01909 | 21.59424 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.95365 | 33.83595 | -0.4999 | 10.99725 |
February | 385.00000 | 21.18488 | 34.16744 | -0.4236 | 9.65887 |
March | 433.00000 | 21.47581 | 33.66369 | -0.3394 | 8.25224 |
April | 410.00000 | 23.27117 | 30.15820 | 0.15987 | 7.77675 |
May | 430.00000 | 23.41801 | 35.76053 | -0.6952 | 19.26800 |
June | 418.00000 | 23.78860 | 42.97758 | -0.4883 | 13.19862 |
July | 422.00000 | 24.07365 | 44.45764 | -0.3726 | 11.34730 |
August | 433.00000 | 23.84224 | 45.33900 | -0.4458 | 12.30542 |
September | 410.00000 | 23.52006 | 42.77266 | -0.6083 | 17.08700 |
October | 427.00000 | 22.04998 | 40.30109 | -0.1367 | 7.02079 |
November | 417.00000 | 21.14543 | 38.36652 | -0.4068 | 9.10733 |
December | 422.00000 | 20.64533 | 33.44026 | -0.5918 | 13.07476 |
Annual Sum or Average | 5034.00000 | 22.45298 | 37.96865 | -0.4049 | 11.60391 |
Minimum of Months | 385.00000 | 20.64533 | 30.15820 | -0.6952 | 7.02079 |
Maximum of Months | 433.00000 | 24.07365 | 45.33900 | 0.15987 | 19.26800 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.93286 | 32.69885 | -0.2255 | 9.21525 |
February | 454.00000 | 22.19483 | 32.96554 | -0.1363 | 8.83555 |
March | 514.00000 | 22.02614 | 33.24202 | -0.1920 | 7.53727 |
April | 485.00000 | 23.41701 | 29.99733 | 0.21888 | 8.63278 |
May | 508.00000 | 23.31831 | 36.36068 | -0.7319 | 20.32694 |
June | 496.00000 | 23.66718 | 43.65362 | -0.5476 | 13.91580 |
July | 497.00000 | 23.86864 | 45.24830 | -0.4435 | 12.17646 |
August | 514.00000 | 23.89121 | 45.47144 | -0.3976 | 11.54197 |
September | 485.00000 | 23.76156 | 42.26904 | -0.4512 | 14.34849 |
October | 502.00000 | 22.74989 | 39.15883 | 0.07593 | 8.06221 |
November | 489.00000 | 22.02300 | 37.27871 | -0.1659 | 8.27325 |
December | 497.00000 | 21.35826 | 32.76787 | -0.3934 | 10.70755 |
Annual Sum or Average | 5943.00000 | 22.85411 | 37.63647 | -0.2849 | 11.15338 |
Minimum of Months | 454.00000 | 21.35826 | 29.99733 | -0.7319 | 7.53727 |
Maximum of Months | 514.00000 | 23.89121 | 45.47144 | 0.21888 | 20.32694 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.15900 | 33.90298 | -0.4312 | 9.84664 |
February | 454.00000 | 21.48566 | 34.15728 | -0.3249 | 8.77325 |
March | 514.00000 | 21.69844 | 33.58530 | -0.2662 | 7.49353 |
April | 485.00000 | 23.17326 | 30.53187 | 0.14570 | 7.55133 |
May | 508.00000 | 23.29099 | 36.36776 | -0.7184 | 19.99420 |
June | 496.00000 | 23.82172 | 43.21818 | -0.4454 | 12.09454 |
July | 497.00000 | 23.95543 | 45.01041 | -0.3724 | 11.00310 |
August | 514.00000 | 23.84822 | 45.70427 | -0.4234 | 11.37899 |
September | 485.00000 | 23.30651 | 43.60879 | -0.6724 | 18.36301 |
October | 502.00000 | 22.15303 | 40.50285 | -0.0955 | 6.71630 |
November | 489.00000 | 21.36225 | 38.36734 | -0.3359 | 8.25007 |
December | 497.00000 | 20.83641 | 33.50442 | -0.5280 | 11.40353 |
Annual Sum or Average | 5943.00000 | 22.51487 | 38.24108 | -0.3735 | 11.08748 |
Minimum of Months | 454.00000 | 20.83641 | 30.53187 | -0.7184 | 6.71630 |
Maximum of Months | 514.00000 | 23.95543 | 45.70427 | 0.14570 | 19.99420 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.27085 | 36.87010 | -0.7226 | 18.30923 |
February | 454.00000 | 20.37845 | 37.61038 | -0.6719 | 16.63628 |
March | 514.00000 | 20.96737 | 36.40136 | -0.5097 | 11.68860 |
April | 485.00000 | 22.35944 | 33.26320 | -0.1339 | 7.49752 |
May | 508.00000 | 22.68651 | 38.71632 | -1.0426 | 30.48260 |
June | 496.00000 | 23.53133 | 44.64447 | -0.6708 | 16.33631 |
July | 497.00000 | 23.64763 | 46.30711 | -0.6091 | 14.59032 |
August | 514.00000 | 23.47595 | 47.38669 | -0.6769 | 16.36069 |
September | 485.00000 | 22.70432 | 46.19940 | -0.9916 | 28.35820 |
October | 502.00000 | 21.21670 | 44.04695 | -0.3846 | 9.59420 |
November | 489.00000 | 20.52226 | 41.41631 | -0.6085 | 14.60411 |
December | 497.00000 | 20.09111 | 36.09865 | -0.7807 | 20.30964 |
Annual Sum or Average | 5943.00000 | 21.83210 | 40.77430 | -0.6507 | 17.06923 |
Minimum of Months | 454.00000 | 20.09111 | 33.26320 | -1.0426 | 7.49752 |
Maximum of Months | 514.00000 | 23.64763 | 47.38669 | -0.1339 | 30.48260 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.38706 | 35.63240 | -0.6820 | 16.70317 |
February | 454.00000 | 20.62266 | 36.19026 | -0.5973 | 14.28098 |
March | 514.00000 | 21.00635 | 35.30678 | -0.4850 | 11.06310 |
April | 485.00000 | 23.02561 | 30.95725 | 0.09707 | 8.09605 |
May | 508.00000 | 23.15667 | 36.84357 | -0.7839 | 22.55288 |
June | 496.00000 | 23.63927 | 43.71318 | -0.5268 | 14.52877 |
July | 497.00000 | 23.94495 | 45.06220 | -0.3988 | 12.06311 |
August | 514.00000 | 23.74086 | 45.90680 | -0.4630 | 12.91997 |
September | 485.00000 | 23.30386 | 43.69964 | -0.6821 | 19.54680 |
October | 502.00000 | 21.53238 | 42.45002 | -0.2841 | 8.93964 |
November | 489.00000 | 20.60868 | 40.32370 | -0.5780 | 13.46726 |
December | 497.00000 | 20.16361 | 35.06306 | -0.7572 | 19.35171 |
Annual Sum or Average | 5943.00000 | 22.10405 | 39.29311 | -0.5122 | 14.46275 |
Minimum of Months | 454.00000 | 20.16361 | 30.95725 | -0.7839 | 8.09605 |
Maximum of Months | 514.00000 | 23.94495 | 45.90680 | 0.09707 | 22.55288 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.16024 | 34.15473 | -0.4608 | 13.24339 |
February | 454.00000 | 21.48036 | 34.48749 | -0.3532 | 11.87753 |
March | 514.00000 | 21.35846 | 34.70271 | -0.3895 | 10.31783 |
April | 485.00000 | 23.00935 | 30.93981 | 0.10501 | 8.98897 |
May | 508.00000 | 22.88181 | 37.46133 | -0.8926 | 27.16058 |
June | 496.00000 | 23.37419 | 44.46230 | -0.6469 | 17.77007 |
July | 497.00000 | 23.64047 | 45.88931 | -0.5196 | 15.14904 |
August | 514.00000 | 23.66631 | 46.09790 | -0.4760 | 14.27683 |
September | 485.00000 | 23.40920 | 43.29449 | -0.5860 | 19.23322 |
October | 502.00000 | 22.08663 | 41.03470 | -0.1141 | 9.16094 |
November | 489.00000 | 21.30431 | 38.96292 | -0.3832 | 11.38946 |
December | 497.00000 | 20.67226 | 34.12878 | -0.6099 | 16.01143 |
Annual Sum or Average | 5943.00000 | 22.34167 | 38.84285 | -0.4459 | 14.57791 |
Minimum of Months | 454.00000 | 20.67226 | 30.93981 | -0.8926 | 8.98897 |
Maximum of Months | 514.00000 | 23.66631 | 46.09790 | 0.10501 | 27.16058 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.59754 | 35.02574 | -0.6145 | 14.89014 |
February | 454.00000 | 20.95791 | 35.34079 | -0.4932 | 12.50814 |
March | 514.00000 | 21.18392 | 34.75514 | -0.4232 | 10.01849 |
April | 485.00000 | 22.70827 | 31.51711 | 0.02497 | 8.10243 |
May | 508.00000 | 22.86205 | 37.43393 | -0.8717 | 26.63440 |
June | 496.00000 | 23.54316 | 43.96346 | -0.5391 | 15.48837 |
July | 497.00000 | 23.74241 | 45.59191 | -0.4428 | 13.56411 |
August | 514.00000 | 23.59951 | 46.37514 | -0.5074 | 14.19664 |
September | 485.00000 | 22.88454 | 44.78826 | -0.8226 | 24.51263 |
October | 502.00000 | 21.55568 | 42.19358 | -0.2645 | 8.33152 |
November | 489.00000 | 20.83770 | 39.64970 | -0.5038 | 11.74511 |
December | 497.00000 | 20.36806 | 34.46838 | -0.6896 | 16.70034 |
Annual Sum or Average | 5943.00000 | 22.07822 | 39.29309 | -0.5132 | 14.73972 |
Minimum of Months | 454.00000 | 20.36806 | 31.51711 | -0.8717 | 8.10243 |
Maximum of Months | 514.00000 | 23.74241 | 46.37514 | 0.02497 | 26.63440 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 17534206.22 | 601.82 | 25-JAN-15:00 | 13.00 | 0.145754E+09 | 0.00 | 0.163288E+09 | 0.15 | 8.40 | 31-JAN-06:30 | 0.00 | 0.00 |
February | 28682358.28 | 622.27 | 07-FEB-15:00 | 22.74 | 0.238279E+09 | 0.00 | 0.266961E+09 | 0.28 | 8.40 | 17-FEB-06:50 | 0.00 | 0.00 |
March | 79733073.36 | 1789.07 | 18-MAR-06:13 | 44.55 | 0.662786E+09 | 0.00 | 0.742519E+09 | 0.50 | 8.40 | 08-MAR-06:40 | 0.00 | 0.00 |
April | 0.586764E+10 | 109776.58 | 28-APR-15:00 | 71.99 | 0.486856E+11 | 0.00 | 0.545532E+11 | 0.83 | 8.68 | 30-APR-14:32 | 0.00 | 0.00 |
May | 0.741440E+10 | 154046.53 | 22-MAY-13:50 | 114.89 | 0.605811E+11 | 0.00 | 0.679955E+11 | 1.28 | 8.68 | 22-MAY-09:40 | 0.00 | 0.00 |
June | 0.223476E+11 | 155877.83 | 12-JUN-17:30 | 208.01 | 0.176282E+12 | 0.00 | 0.198629E+12 | 2.37 | 8.68 | 25-JUN-14:14 | 0.00 | 0.00 |
July | 0.377910E+11 | 159328.31 | 22-JUL-10:40 | 346.71 | 0.303215E+12 | 0.00 | 0.341006E+12 | 3.84 | 8.68 | 31-JUL-16:40 | 0.00 | 0.00 |
August | 0.490941E+11 | 153982.08 | 28-AUG-13:30 | 407.25 | 0.397503E+12 | 0.00 | 0.446597E+12 | 4.53 | 8.68 | 11-AUG-12:10 | 0.00 | 0.00 |
September | 0.257116E+11 | 155786.95 | 13-SEP-12:40 | 246.58 | 0.205782E+12 | 0.00 | 0.231493E+12 | 2.82 | 8.68 | 26-SEP-14:30 | 0.00 | 0.00 |
October | 0.142549E+10 | 32313.44 | 07-OCT-15:00 | 52.54 | 0.118189E+11 | 0.00 | 0.132443E+11 | 0.59 | 8.40 | 07-OCT-15:00 | 0.00 | 0.00 |
November | 26834248.24 | 6560.76 | 24-NOV-12:00 | 10.34 | 0.223061E+09 | 0.00 | 0.249895E+09 | 0.12 | 8.38 | 03-NOV-05:50 | 0.00 | 0.00 |
December | 19974045.42 | 376.12 | 26-DEC-05:11 | 16.25 | 0.165978E+09 | 0.00 | 0.185952E+09 | 0.18 | 8.39 | 26-DEC-06:50 | 0.00 | 0.00 |
Annual Sum or Average | 0.149825E+12 | 1554.85 | 0.120530E+13 | 0.00 | 0.135513E+13 | 1.47 | 0.00 | 0.00 | ||||
Minimum of Months | 17534206.22 | 376.12 | 10.34 | 0.145754E+09 | 0.00 | 0.163288E+09 | 0.12 | 8.38 | 0.00 | 0.00 | ||
Maximum of Months | 0.490941E+11 | 159328.31 | 407.25 | 0.397503E+12 | 0.00 | 0.446597E+12 | 4.53 | 8.68 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.510491E+09 | 69822.58 | 22-MAY-14:10 | 2.17 | 0.416179E+10 | 0.00 | 0.467228E+10 | 0.02 | 8.33 | 22-MAY-14:20 | 0.00 | 0.00 |
June | 0.363820E+10 | 102172.59 | 13-JUN-16:00 | 14.67 | 0.289190E+11 | 0.00 | 0.325572E+11 | 0.16 | 8.52 | 13-JUN-09:40 | 0.00 | 0.00 |
July | 0.366716E+10 | 91897.04 | 21-JUL-15:30 | 15.17 | 0.292508E+11 | 0.00 | 0.329180E+11 | 0.16 | 8.51 | 12-JUL-15:50 | 0.00 | 0.00 |
August | 0.264987E+10 | 87208.23 | 14-AUG-15:40 | 10.83 | 0.211560E+11 | 0.00 | 0.238059E+11 | 0.12 | 8.64 | 25-AUG-14:30 | 0.00 | 0.00 |
September | 0.201567E+10 | 71958.20 | 13-SEP-13:30 | 9.00 | 0.163737E+11 | 0.00 | 0.183894E+11 | 0.10 | 8.51 | 12-SEP-12:30 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.124814E+11 | 51.83 | 0.998612E+11 | 0.00 | 0.112343E+12 | 0.05 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.366716E+10 | 102172.59 | 15.17 | 0.292508E+11 | 0.00 | 0.329180E+11 | 0.16 | 8.64 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.100480E+10 | 744.00 | 1059.36 | 29-JAN-06:00 | 34754.56 | 19-JAN-16:30 | 18.68 | 18.33 | 15.76 |
February | 0.216144E+10 | 672.00 | 1658.19 | 07-FEB-15:00 | 68375.96 | 17-FEB-17:00 | 19.24 | 18.33 | 15.76 |
March | 0.420186E+10 | 744.00 | 3373.53 | 25-MAR-13:00 | 112859.00 | 31-MAR-23:40 | 19.81 | 18.33 | 15.76 |
April | 0.147541E+11 | 720.00 | 49248.27 | 22-APR-12:20 | 575528.25 | 30-APR-19:02 | 20.92 | 18.51 | 15.76 |
May | 0.761639E+10 | 744.00 | 49248.27 | 21-MAY-14:32 | 100522.95 | 22-MAY-15:00 | 18.95 | 18.39 | 15.76 |
June | 0.203979E+11 | 720.00 | 49248.27 | 09-JUN-11:00 | 376566.54 | 13-JUN-17:00 | 19.98 | 18.72 | 15.76 |
July | 0.404129E+11 | 744.00 | 49248.27 | 05-JUL-14:30 | 548356.78 | 22-JUL-19:02 | 21.54 | 19.19 | 15.76 |
August | 0.694254E+11 | 744.00 | 49248.27 | 01-AUG-07:40 | 690681.03 | 14-AUG-17:20 | 24.12 | 19.56 | 15.76 |
September | 0.199394E+11 | 720.00 | 49248.27 | 09-SEP-12:40 | 64630.84 | 13-SEP-16:00 | 19.16 | 18.59 | 15.76 |
October | 0.445818E+10 | 744.00 | 49248.27 | 07-OCT-14:30 | 84125.07 | 31-OCT-23:30 | 19.30 | 18.33 | 15.76 |
November | 0.418721E+10 | 720.00 | 5381.84 | 24-NOV-12:00 | 94368.30 | 03-NOV-16:00 | 19.75 | 18.33 | 15.76 |
December | 0.456768E+10 | 744.00 | 3725.07 | 23-DEC-11:00 | 114830.98 | 18-DEC-15:20 | 20.22 | 18.33 | 15.76 |
Annual Sum or Average | 0.193127E+12 | 8760.00 | 20.15 | 18.58 | 15.76 | ||||
Minimum of Months | 0.100480E+10 | 672.00 | 1059.36 | 34754.56 | 18.68 | 18.33 | 15.76 | ||
Maximum of Months | 0.694254E+11 | 744.00 | 49248.27 | 690681.03 | 24.12 | 19.56 | 15.76 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 171795.39 | 30-JAN-06:06 | 21.03 | 21.03 | 0.06 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 194933.68 | 24-FEB-06:30 | 21.01 | 21.01 | 0.14 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 175735.64 | 10-MAR-07:00 | 20.89 | 20.88 | 0.21 |
April | 56598730.81 | 36.39 | 2143.19 | 28-APR-15:00 | 898259.78 | 28-APR-15:00 | 21.09 | 20.98 | 3.86 |
May | 0.211683E+09 | 46.39 | 14460.89 | 22-MAY-13:20 | 1101526.25 | 22-MAY-13:50 | 21.11 | 20.98 | 4.41 |
June | 0.142001E+10 | 125.03 | 14460.89 | 12-JUN-12:20 | 1070565.50 | 21-JUN-15:30 | 21.44 | 21.05 | 11.50 |
July | 0.149924E+10 | 246.37 | 14460.89 | 10-JUL-08:20 | 1078491.69 | 10-JUL-14:10 | 21.71 | 21.07 | 20.27 |
August | 0.158747E+10 | 326.56 | 14460.89 | 14-AUG-09:40 | 1121704.87 | 28-AUG-13:30 | 21.93 | 21.10 | 25.47 |
September | 0.836603E+09 | 163.86 | 14460.89 | 11-SEP-13:20 | 1061320.49 | 11-SEP-13:40 | 21.50 | 21.05 | 14.51 |
October | 4154970.86 | 14.61 | 190.06 | 11-OCT-15:00 | 311525.09 | 07-OCT-15:10 | 21.04 | 21.02 | 1.70 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 193064.47 | 20-NOV-06:15 | 21.02 | 21.02 | 0.13 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 191178.24 | 15-DEC-05:40 | 20.96 | 20.96 | 0.09 |
Annual Sum or Average | 0.561576E+10 | 959.20 | 21.23 | 21.01 | 6.91 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 171795.39 | 20.89 | 20.88 | 0.06 | ||
Maximum of Months | 0.158747E+10 | 326.56 | 14460.89 | 1121704.87 | 21.93 | 21.10 | 25.47 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 21.03 | 21.03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.01 | 21.01 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 20.89 | 20.89 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 21.09 | 21.09 | 0.00 |
May | 61535369.96 | 1.33 | 14460.89 | 22-MAY-14:10 | 913062.93 | 22-MAY-14:10 | 21.11 | 21.10 | 0.09 |
June | 0.473758E+09 | 9.67 | 14460.89 | 12-JUN-12:50 | 884596.32 | 21-JUN-13:40 | 21.44 | 21.39 | 0.67 |
July | 0.357023E+09 | 10.67 | 14460.89 | 10-JUL-09:00 | 927985.72 | 21-JUL-10:40 | 21.71 | 21.65 | 0.71 |
August | 0.266807E+09 | 9.33 | 14460.89 | 14-AUG-10:10 | 948086.37 | 25-AUG-14:40 | 21.93 | 21.88 | 0.63 |
September | 0.134883E+09 | 3.67 | 14460.89 | 11-SEP-14:00 | 921375.17 | 25-SEP-14:10 | 21.50 | 21.48 | 0.26 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 21.04 | 21.04 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.02 | 21.02 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 20.96 | 20.96 | 0.00 |
Annual Sum or Average | 0.129401E+10 | 34.67 | 21.23 | 21.21 | 0.20 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.89 | 20.89 | 0.00 | ||
Maximum of Months | 0.473758E+09 | 10.67 | 14460.89 | 948086.37 | 21.93 | 21.88 | 0.71 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.207225E+12 | 0.00 | 413.25 | 1020629.72 | 03-JAN-06:02 | 0.00 | 26.97 | 57.30 | 0.36 | 0.00 | 0.04 | 0.57 | 03-JAN-06:02 |
February | 0.131962E+12 | 0.00 | 352.97 | 1020227.09 | 17-FEB-06:01 | 0.00 | 26.12 | 55.52 | 0.24 | 0.00 | 0.03 | 0.57 | 17-FEB-06:01 |
March | 0.914010E+11 | 0.00 | 354.54 | 1014600.53 | 27-MAR-05:02 | 0.00 | 24.38 | 51.64 | 0.15 | 0.00 | 0.02 | 0.56 | 27-MAR-05:02 |
April | 0.108235E+11 | 0.00 | 109.28 | 256250.92 | 01-APR-05:02 | 0.00 | 24.03 | 32.80 | 0.02 | 0.00 | 0.00 | 0.14 | 01-APR-05:02 |
May | 0.343460E+10 | 0.00 | 75.88 | 235608.74 | 05-MAY-05:03 | 0.00 | 22.09 | 28.15 | 0.01 | 0.00 | 0.00 | 0.13 | 05-MAY-05:03 |
June | 63169449.43 | 0.00 | 13.65 | 12552.97 | 08-JUN-05:03 | 0.00 | 21.01 | 22.16 | 0.00 | 0.00 | 0.00 | 0.01 | 08-JUN-05:03 |
July | 11944581.69 | 0.00 | 4.62 | 3129.14 | 31-JUL-05:08 | 0.00 | 20.78 | 21.16 | 0.00 | 0.00 | 0.00 | 0.00 | 31-JUL-05:08 |
August | 4354908.90 | 0.00 | 4.38 | 1613.22 | 23-AUG-05:10 | 0.00 | 20.72 | 21.09 | 0.00 | 0.00 | 0.00 | 0.00 | 23-AUG-05:10 |
September | 0.828645E+09 | 0.00 | 39.10 | 71358.10 | 21-SEP-06:05 | 0.00 | 20.94 | 24.24 | 0.00 | 0.00 | 0.00 | 0.04 | 21-SEP-06:05 |
October | 0.249257E+11 | 0.00 | 236.03 | 564680.93 | 23-OCT-05:03 | 0.00 | 22.73 | 41.50 | 0.04 | 0.00 | 0.01 | 0.31 | 23-OCT-05:03 |
November | 0.956190E+11 | 0.00 | 355.79 | 1213381.79 | 27-NOV-05:11 | 0.00 | 23.47 | 52.07 | 0.16 | 0.00 | 0.02 | 0.67 | 27-NOV-05:11 |
December | 0.225018E+12 | 0.00 | 425.36 | 1126112.50 | 26-DEC-05:11 | 0.00 | 26.83 | 58.42 | 0.38 | 0.00 | 0.05 | 0.62 | 26-DEC-05:11 |
Annual Sum or Average | 0.791318E+12 | 0.00 | 2384.86 | 0.00 | 23.33 | 38.76 | 0.11 | 0.00 | 0.01 | ||||
Minimum of Months | 4354908.90 | 0.00 | 4.38 | 1613.22 | 0.00 | 20.72 | 21.09 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.225018E+12 | 0.00 | 425.36 | 1213381.79 | 0.00 | 26.97 | 58.42 | 0.38 | 0.00 | 0.05 | 0.67 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 18.68 | 18.68 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 19.24 | 19.24 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 19.81 | 19.81 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 20.92 | 20.92 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 18.95 | 18.95 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 19.98 | 19.98 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 21.54 | 21.54 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 24.12 | 24.12 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 19.16 | 19.16 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 19.30 | 19.30 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 19.75 | 19.75 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 20.22 | 20.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 20.15 | 20.15 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.68 | 18.68 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.12 | 24.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.469895E+10 | 0.00 | 54.29 | 0.469350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83403.40 | 30-APR-15:12 | 83403.40 | 30-APR-15:12 | 0.00 | 0.00 | 0.00 |
May | 0.577104E+10 | 0.00 | 66.47 | 0.577104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 101062.63 | 22-MAY-15:00 | 101062.63 | 22-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.186705E+11 | 0.00 | 171.06 | 0.183866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 126264.58 | 13-JUN-16:00 | 118378.08 | 13-JUN-15:20 | 0.00 | 0.00 | 0.00 |
July | 0.320333E+11 | 0.00 | 304.35 | 0.319156E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 121442.92 | 21-JUL-15:20 | 121442.92 | 21-JUL-15:20 | 0.00 | 0.00 | 0.00 |
August | 0.420379E+11 | 0.00 | 376.22 | 0.418832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 127047.73 | 14-AUG-15:10 | 127047.73 | 14-AUG-15:10 | 0.00 | 0.00 | 0.00 |
September | 0.197180E+11 | 0.00 | 212.09 | 0.196649E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91042.88 | 13-SEP-14:20 | 91042.88 | 13-SEP-14:20 | 0.00 | 0.00 | 0.00 |
October | 0.107330E+10 | 0.00 | 24.67 | 0.107330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25714.58 | 11-OCT-15:00 | 25714.58 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 13567362.30 | 0.00 | 0.83 | 13567362.30 | 0.00 | 0.00 | 0.00 | 0.00 | 8282.98 | 24-NOV-12:00 | 8282.98 | 24-NOV-12:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.124017E+12 | 0.00 | 1209.98 | 0.123402E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.420379E+11 | 0.00 | 376.22 | 0.418832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 127047.73 | 127047.73 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 50013.79 | 0.00 | 14.29 | 50013.79 | 0.00 | 0.00 | 0.00 | 0.00 | 3.62 | 02-JAN-05:20 | 3.62 | 02-JAN-05:20 | 0.00 | 0.00 | 0.00 |
February | 53685.99 | 0.00 | 21.24 | 53685.99 | 0.00 | 0.00 | 0.00 | 0.00 | 2.66 | 22-FEB-06:03 | 2.66 | 22-FEB-06:03 | 0.00 | 0.00 | 0.00 |
March | 83825.41 | 0.00 | 25.61 | 83825.41 | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27-MAR-05:02 | 4.17 | 27-MAR-05:02 | 0.00 | 0.00 | 0.00 |
April | 0.386430E+11 | 0.00 | 67.51 | 0.386237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 823661.06 | 30-APR-15:12 | 823661.06 | 30-APR-15:12 | 0.00 | 0.00 | 0.00 |
May | 0.490828E+11 | 0.00 | 75.57 | 0.490828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 867273.71 | 22-MAY-15:00 | 867273.71 | 22-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.154291E+12 | 0.00 | 173.89 | 0.152079E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1140253.53 | 13-JUN-16:00 | 1056462.79 | 13-JUN-15:30 | 0.00 | 0.00 | 0.00 |
July | 0.250011E+12 | 0.00 | 298.35 | 0.249749E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1078193.67 | 21-JUL-15:30 | 1078193.67 | 21-JUL-15:30 | 0.00 | 0.00 | 0.00 |
August | 0.314850E+12 | 0.00 | 374.25 | 0.314159E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1024779.59 | 14-AUG-15:40 | 1024779.59 | 14-AUG-15:40 | 0.00 | 0.00 | 0.00 |
September | 0.172191E+12 | 0.00 | 227.57 | 0.171167E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 851809.15 | 13-SEP-14:40 | 851809.15 | 13-SEP-14:40 | 0.00 | 0.00 | 0.00 |
October | 0.900400E+10 | 0.00 | 36.09 | 0.900400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 228092.02 | 07-OCT-15:00 | 228092.02 | 07-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 51926402.11 | 0.00 | 9.36 | 51926402.11 | 0.00 | 0.00 | 0.00 | 0.00 | 38544.45 | 24-NOV-12:00 | 38544.45 | 24-NOV-12:00 | 0.00 | 0.00 | 0.00 |
December | 56088.88 | 0.00 | 16.08 | 56088.88 | 0.00 | 0.00 | 0.00 | 0.00 | 3.76 | 11-DEC-05:52 | 3.76 | 11-DEC-05:52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.988125E+12 | 0.00 | 1339.80 | 0.983918E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 50013.79 | 0.00 | 9.36 | 50013.79 | 0.00 | 0.00 | 0.00 | 0.00 | 2.66 | 2.66 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.314850E+12 | 0.00 | 374.25 | 0.314159E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1140253.53 | 1078193.67 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.372357E+10 | 0.00 | 51.95 | 0.372357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84581.73 | 30-APR-15:32 | 84581.73 | 30-APR-15:32 | 0.00 | 0.00 | 0.00 |
May | 0.498357E+10 | 0.00 | 64.61 | 0.498357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95263.14 | 22-MAY-15:00 | 95263.14 | 22-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.159832E+11 | 0.00 | 158.40 | 0.157662E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 132655.03 | 13-JUN-16:00 | 126404.09 | 13-JUN-15:30 | 0.00 | 0.00 | 0.00 |
July | 0.254910E+11 | 0.00 | 279.82 | 0.254727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 125461.13 | 21-JUL-15:30 | 125461.13 | 21-JUL-15:30 | 0.00 | 0.00 | 0.00 |
August | 0.302570E+11 | 0.00 | 361.94 | 0.302215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 116844.80 | 14-AUG-15:40 | 116844.80 | 14-AUG-15:40 | 0.00 | 0.00 | 0.00 |
September | 0.155879E+11 | 0.00 | 200.64 | 0.155431E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86922.98 | 13-SEP-14:50 | 86922.98 | 13-SEP-14:50 | 0.00 | 0.00 | 0.00 |
October | 0.635572E+09 | 0.00 | 22.19 | 0.635572E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 21679.94 | 07-OCT-15:00 | 21679.94 | 07-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 4561892.58 | 0.00 | 0.67 | 4561892.58 | 0.00 | 0.00 | 0.00 | 0.00 | 3487.25 | 24-NOV-12:00 | 3487.25 | 24-NOV-12:00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.966663E+11 | 0.00 | 1140.22 | 0.963509E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.302570E+11 | 0.00 | 361.94 | 0.302215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 132655.03 | 126404.09 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 36600270.12 | 0.00 | 6.17 | 36600270.12 | 0.00 | 0.00 | 0.00 | 0.00 | 4589.48 | 25-JAN-15:00 | 4589.48 | 25-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 10231437.37 | 0.00 | 1.50 | 10231437.37 | 0.00 | 0.00 | 0.00 | 0.00 | 4322.83 | 07-FEB-15:00 | 4322.83 | 07-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.244250E+09 | 0.00 | 18.94 | 0.242978E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11734.98 | 18-MAR-06:13 | 10956.29 | 30-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.114216E+10 | 0.00 | 26.43 | 0.114216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32589.85 | 28-APR-15:00 | 32589.85 | 28-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.375880E+10 | 0.00 | 82.75 | 0.373947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61700.94 | 22-MAY-15:00 | 61700.94 | 22-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.109175E+11 | 0.00 | 132.22 | 0.104489E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 74791.42 | 27-JUN-06:23 | 64517.54 | 12-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.189652E+11 | 0.00 | 220.40 | 0.175440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82529.13 | 10-JUL-06:35 | 72621.79 | 10-JUL-10:00 | 0.00 | 0.00 | 0.00 |
August | 0.266857E+11 | 0.00 | 308.33 | 0.255918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75324.19 | 14-AUG-13:10 | 70606.73 | 14-AUG-13:10 | 0.00 | 0.00 | 0.00 |
September | 0.118183E+11 | 0.00 | 160.35 | 0.116714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61816.41 | 16-SEP-06:14 | 54353.56 | 25-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.552948E+09 | 0.00 | 32.50 | 0.522043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37519.60 | 20-OCT-06:12 | 18740.57 | 20-OCT-06:12 | 0.00 | 0.00 | 0.00 |
November | 49763889.70 | 0.00 | 1.82 | 41700750.73 | 0.00 | 0.00 | 0.00 | 0.00 | 32887.21 | 24-NOV-07:11 | 18150.21 | 24-NOV-07:11 | 0.00 | 0.00 | 0.00 |
December | 276615.73 | 0.00 | 0.17 | 276615.73 | 0.00 | 0.00 | 0.00 | 0.00 | 461.03 | 23-DEC-11:00 | 461.03 | 23-DEC-11:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.741817E+11 | 0.00 | 991.58 | 0.709915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 276615.73 | 0.00 | 0.17 | 276615.73 | 0.00 | 0.00 | 0.00 | 0.00 | 461.03 | 461.03 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.266857E+11 | 0.00 | 308.33 | 0.255918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 82529.13 | 72621.79 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.383784E+10 | 0.385206E+10 | 718.67 | 0.383774E+10 | 101730.70 | 0.00 | 0.02 | 10-JAN-17:05 | 0.01 | 29-JAN-05:10 | 3053.55 | 10-JAN-17:05 | 3053.55 | 10-JAN-17:05 | 55.68 | 29-JAN-05:50 | 1883.48 | 10-JAN-17:05 | 0.00 |
February | 0.609449E+10 | 0.424297E+10 | 661.67 | 0.603894E+10 | 55543986.09 | 0.00 | 0.02 | 20-FEB-16:03 | 0.01 | 07-FEB-14:15 | 5067.51 | 20-FEB-16:03 | 5067.51 | 20-FEB-16:03 | 65.64 | 06-FEB-18:50 | 2490.23 | 20-FEB-16:03 | 0.00 |
March | 0.108219E+11 | 0.597060E+10 | 706.66 | 0.104530E+11 | 0.368875E+09 | 0.00 | 0.03 | 31-MAR-23:30 | 0.01 | 18-MAR-04:27 | 5492.72 | 31-MAR-23:10 | 5492.72 | 31-MAR-23:10 | 255.70 | 01-MAR-18:30 | 2782.23 | 31-MAR-23:30 | 0.00 |
April | 0.448575E+11 | 0.160757E+11 | 715.95 | 0.427937E+11 | 0.206381E+10 | 0.00 | 0.82 | 30-APR-16:58 | 0.01 | 26-APR-17:10 | 320463.21 | 30-APR-17:41 | 320463.21 | 30-APR-17:41 | 79326.49 | 28-APR-08:00 | 106667.39 | 30-APR-17:00 | 0.00 |
May | 0.223940E+10 | 0.351465E+10 | 567.01 | 0.221967E+10 | 19732629.00 | 0.00 | 0.13 | 22-MAY-15:00 | 0.00 | 21-MAY-17:45 | 46321.86 | 22-MAY-15:00 | 42761.66 | 22-MAY-15:00 | 3560.20 | 22-MAY-15:00 | 15610.11 | 22-MAY-15:00 | 0.00 |
June | 0.184084E+11 | 0.899869E+10 | 298.74 | 0.157597E+11 | 0.264867E+10 | 0.00 | 0.54 | 13-JUN-17:00 | 0.01 | 18-JUN-10:02 | 227269.40 | 13-JUN-17:00 | 223825.62 | 13-JUN-17:00 | 76960.90 | 25-JUN-17:51 | 74081.23 | 13-JUN-17:00 | 0.00 |
July | 0.866000E+11 | 0.288726E+11 | 410.31 | 0.717615E+11 | 0.148385E+11 | 0.00 | 0.77 | 21-JUL-17:00 | 0.01 | 02-JUL-16:15 | 317886.71 | 21-JUL-16:00 | 317886.71 | 21-JUL-16:00 | 60983.10 | 23-JUL-15:51 | 111613.48 | 22-JUL-18:00 | 0.00 |
August | 0.285665E+12 | 0.806993E+11 | 603.39 | 0.212277E+12 | 0.733879E+11 | 0.00 | 1.00 | 14-AUG-17:20 | 0.01 | 07-AUG-04:53 | 412254.14 | 14-AUG-17:00 | 412254.14 | 14-AUG-17:00 | 136610.44 | 08-AUG-13:00 | 142261.41 | 14-AUG-17:20 | 0.00 |
September | 0.960196E+09 | 0.309744E+10 | 347.88 | 0.929773E+09 | 30423302.76 | 0.00 | 0.06 | 27-SEP-16:00 | 0.01 | 27-SEP-07:03 | 17219.81 | 27-SEP-16:00 | 17219.81 | 27-SEP-16:00 | 2480.37 | 13-SEP-16:00 | 6752.87 | 27-SEP-16:00 | 0.00 |
October | 0.311770E+10 | 0.378622E+10 | 537.92 | 0.304440E+10 | 73299756.76 | 0.00 | 0.03 | 31-OCT-23:10 | 0.00 | 16-OCT-06:40 | 5330.38 | 31-OCT-23:10 | 5290.45 | 31-OCT-23:10 | 89.28 | 31-OCT-24:00 | 2622.30 | 07-OCT-15:00 | 0.00 |
November | 0.742988E+10 | 0.491671E+10 | 603.18 | 0.707765E+10 | 0.352224E+09 | 0.00 | 0.03 | 25-NOV-14:00 | 0.01 | 24-NOV-07:11 | 5376.21 | 16-NOV-22:50 | 5301.36 | 19-NOV-12:23 | 257.85 | 20-NOV-23:00 | 2628.97 | 25-NOV-14:00 | 0.00 |
December | 0.140647E+11 | 0.711172E+10 | 744.00 | 0.131705E+11 | 0.894129E+09 | 0.00 | 0.03 | 04-DEC-11:00 | 0.01 | 02-DEC-17:00 | 5983.72 | 22-DEC-00:50 | 5540.29 | 03-DEC-13:23 | 575.47 | 21-DEC-20:00 | 2903.82 | 04-DEC-11:00 | 0.00 |
Annual Sum or Average | 0.484096E+12 | 0.171139E+12 | 6915.35 | 0.389363E+12 | 0.947331E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.960196E+09 | 0.309744E+10 | 298.74 | 0.929773E+09 | 101730.70 | 0.00 | 0.02 | 0.00 | 3053.55 | 3053.55 | 55.68 | 1883.48 | 0.00 | ||||||
Maximum of Months | 0.285665E+12 | 0.806993E+11 | 744.00 | 0.212277E+12 | 0.733879E+11 | 0.00 | 1.00 | 0.01 | 412254.14 | 412254.14 | 136610.44 | 142261.41 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.425415E+10 | 0.109501E+10 | 744.00 | 0.425267E+10 | 1474486.81 | 0.00 | 0.28 | 01-JAN-16:02 | 0.11 | 10-JAN-08:00 | 2401.57 | 01-JAN-16:10 | 2396.04 | 01-JAN-16:02 | 52.67 | 18-JAN-16:20 | 575.63 | 01-JAN-16:02 | 0.00 |
February | 0.874401E+10 | 0.210507E+10 | 672.00 | 0.874274E+10 | 1266950.06 | 0.00 | 0.54 | 19-FEB-16:53 | 0.36 | 17-FEB-07:40 | 4559.60 | 19-FEB-17:10 | 4559.60 | 19-FEB-17:10 | 56.32 | 07-FEB-16:00 | 1095.06 | 19-FEB-16:53 | 0.00 |
March | 0.150820E+11 | 0.346179E+10 | 744.00 | 0.150817E+11 | 296715.39 | 0.00 | 0.84 | 31-MAR-24:00 | 0.58 | 01-MAR-07:05 | 7606.47 | 31-MAR-24:00 | 7606.47 | 31-MAR-24:00 | 65.15 | 20-MAR-06:05 | 1705.51 | 31-MAR-24:00 | 0.00 |
April | 0.200811E+11 | 0.444818E+10 | 720.00 | 0.200805E+11 | 655232.92 | 0.00 | 1.00 | 30-APR-17:51 | 0.30 | 30-APR-23:55 | 9041.68 | 30-APR-18:10 | 9041.68 | 30-APR-18:10 | 57.60 | 28-APR-10:40 | 2553.49 | 30-APR-18:10 | 0.00 |
May | 0.548176E+10 | 0.135715E+10 | 744.00 | 0.546199E+10 | 19765702.23 | 0.00 | 0.44 | 31-MAY-24:00 | 0.17 | 06-MAY-06:05 | 3956.82 | 31-MAY-24:00 | 3956.82 | 31-MAY-24:00 | 137.59 | 23-MAY-16:00 | 909.11 | 31-MAY-24:00 | 0.00 |
June | 0.106079E+11 | 0.246864E+10 | 720.00 | 0.105232E+11 | 84693175.75 | 0.00 | 0.63 | 30-JUN-24:00 | 0.40 | 01-JUN-06:20 | 5793.01 | 30-JUN-24:00 | 5793.01 | 30-JUN-24:00 | 218.20 | 26-JUN-17:50 | 1457.33 | 13-JUN-16:00 | 0.00 |
July | 0.162150E+11 | 0.367403E+10 | 744.00 | 0.161034E+11 | 0.111637E+09 | 0.00 | 0.82 | 31-JUL-24:00 | 0.59 | 01-JUL-06:30 | 7847.20 | 31-JUL-24:00 | 7847.20 | 31-JUL-24:00 | 251.29 | 18-JUL-15:40 | 2269.40 | 22-JUL-18:35 | 0.00 |
August | 0.212362E+11 | 0.470570E+10 | 744.00 | 0.210980E+11 | 0.138256E+09 | 0.00 | 0.95 | 14-AUG-18:00 | 0.30 | 31-AUG-24:00 | 8841.59 | 13-AUG-18:14 | 8816.80 | 13-AUG-18:05 | 281.70 | 08-AUG-13:30 | 2613.15 | 14-AUG-18:00 | 0.00 |
September | 0.547658E+10 | 0.134273E+10 | 720.00 | 0.541217E+10 | 64411667.39 | 0.00 | 0.45 | 30-SEP-24:00 | 0.18 | 20-SEP-06:05 | 3821.48 | 30-SEP-24:00 | 3821.48 | 30-SEP-24:00 | 155.23 | 19-SEP-16:00 | 910.81 | 30-SEP-24:00 | 0.00 |
October | 0.102865E+11 | 0.240989E+10 | 744.00 | 0.102603E+11 | 26212848.20 | 0.00 | 0.64 | 31-OCT-24:00 | 0.37 | 28-OCT-07:00 | 5667.40 | 31-OCT-24:00 | 5667.40 | 31-OCT-24:00 | 128.31 | 17-OCT-15:30 | 1294.74 | 31-OCT-24:00 | 0.00 |
November | 0.146259E+11 | 0.331879E+10 | 720.00 | 0.146103E+11 | 15651120.12 | 0.00 | 0.69 | 19-NOV-15:55 | 0.57 | 25-NOV-08:00 | 6227.30 | 19-NOV-16:00 | 6227.30 | 19-NOV-16:00 | 143.02 | 08-NOV-15:10 | 1414.70 | 19-NOV-15:55 | 0.00 |
December | 0.198916E+11 | 0.443791E+10 | 744.00 | 0.198915E+11 | 104636.74 | 0.00 | 0.89 | 31-DEC-15:15 | 0.76 | 02-DEC-18:00 | 7984.32 | 25-DEC-15:10 | 7984.32 | 25-DEC-15:10 | 37.73 | 20-DEC-17:10 | 1810.11 | 31-DEC-15:15 | 0.00 |
Annual Sum or Average | 0.151983E+12 | 0.348249E+11 | 8760.00 | 0.151518E+12 | 0.464425E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.425415E+10 | 0.109501E+10 | 672.00 | 0.425267E+10 | 104636.74 | 0.00 | 0.28 | 0.11 | 2401.57 | 2396.04 | 37.73 | 575.63 | 0.00 | ||||||
Maximum of Months | 0.212362E+11 | 0.470570E+10 | 744.00 | 0.210980E+11 | 0.138256E+09 | 0.00 | 1.00 | 0.76 | 9041.68 | 9041.68 | 281.70 | 2613.15 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.225841E+11 | 0.612113E+10 | 740.67 | 0.225698E+11 | 14340551.87 | 0.00 | 0.25 | 19-JAN-16:20 | 0.00 | 02-JAN-07:05 | 19795.60 | 19-JAN-16:20 | 19795.60 | 19-JAN-16:20 | 500.79 | 18-JAN-16:30 | 4853.53 | 19-JAN-16:20 | 0.00 |
February | 0.681566E+11 | 0.167117E+11 | 672.00 | 0.681436E+11 | 13045411.32 | 0.00 | 0.48 | 17-FEB-17:00 | 0.26 | 13-FEB-07:05 | 40747.89 | 27-FEB-17:00 | 40747.89 | 27-FEB-17:00 | 552.36 | 07-FEB-16:10 | 9423.55 | 17-FEB-17:00 | 0.00 |
March | 0.127996E+12 | 0.297868E+11 | 744.00 | 0.127993E+12 | 3024543.40 | 0.00 | 0.79 | 31-MAR-23:40 | 0.49 | 27-MAR-06:05 | 68370.37 | 31-MAR-23:40 | 68370.37 | 31-MAR-23:40 | 543.78 | 20-MAR-06:05 | 15473.35 | 31-MAR-23:40 | 0.00 |
April | 0.184102E+12 | 0.410400E+11 | 720.00 | 0.184095E+12 | 6815927.80 | 0.00 | 0.98 | 30-APR-18:10 | 0.27 | 30-APR-23:53 | 85131.53 | 30-APR-18:10 | 85131.53 | 30-APR-18:10 | 563.07 | 28-APR-10:40 | 24133.70 | 30-APR-18:10 | 0.00 |
May | 0.453305E+11 | 0.113557E+11 | 744.00 | 0.451354E+11 | 0.195031E+09 | 0.00 | 0.43 | 31-MAY-23:40 | 0.11 | 05-MAY-06:05 | 36313.26 | 31-MAY-23:40 | 36313.26 | 31-MAY-23:40 | 1369.11 | 23-MAY-16:00 | 8379.09 | 31-MAY-23:40 | 0.00 |
June | 0.967459E+11 | 0.226324E+11 | 720.00 | 0.959053E+11 | 0.840620E+09 | 0.00 | 0.60 | 30-JUN-24:00 | 0.37 | 08-JUN-06:05 | 52787.29 | 30-JUN-24:00 | 52787.29 | 30-JUN-24:00 | 2154.89 | 26-JUN-17:50 | 13829.74 | 13-JUN-16:00 | 0.00 |
July | 0.150458E+12 | 0.342396E+11 | 744.00 | 0.149350E+12 | 0.110770E+10 | 0.00 | 0.80 | 31-JUL-23:50 | 0.56 | 01-JUL-06:40 | 73693.06 | 31-JUL-23:50 | 73693.06 | 31-JUL-23:50 | 2480.50 | 18-JUL-15:40 | 21498.47 | 22-JUL-18:35 | 0.00 |
August | 0.198835E+12 | 0.442242E+11 | 744.00 | 0.197467E+12 | 0.136855E+10 | 0.00 | 0.94 | 14-AUG-18:00 | 0.24 | 31-AUG-24:00 | 82550.22 | 13-AUG-18:03 | 82322.89 | 13-AUG-18:05 | 2790.36 | 08-AUG-13:30 | 24940.11 | 14-AUG-18:00 | 0.00 |
September | 0.456480E+11 | 0.113231E+11 | 720.00 | 0.450202E+11 | 0.627709E+09 | 0.00 | 0.42 | 30-SEP-23:30 | 0.13 | 20-SEP-06:55 | 34117.59 | 30-SEP-23:30 | 34117.59 | 30-SEP-23:30 | 1558.93 | 19-SEP-16:00 | 8190.00 | 30-SEP-23:30 | 0.00 |
October | 0.851235E+11 | 0.202144E+11 | 744.00 | 0.848642E+11 | 0.259267E+09 | 0.00 | 0.58 | 31-OCT-24:00 | 0.30 | 28-OCT-07:00 | 49067.13 | 31-OCT-24:00 | 49067.13 | 31-OCT-24:00 | 1269.26 | 17-OCT-15:30 | 11348.04 | 31-OCT-24:00 | 0.00 |
November | 0.121813E+12 | 0.280751E+11 | 720.00 | 0.121656E+12 | 0.156343E+09 | 0.00 | 0.65 | 03-NOV-16:00 | 0.47 | 27-NOV-07:05 | 56449.69 | 10-NOV-16:10 | 56242.94 | 10-NOV-16:00 | 1422.12 | 08-NOV-15:10 | 12710.57 | 03-NOV-16:00 | 0.00 |
December | 0.166467E+12 | 0.378047E+11 | 744.00 | 0.166466E+12 | 1331278.32 | 0.00 | 0.81 | 29-DEC-15:50 | 0.64 | 26-DEC-07:05 | 70750.42 | 21-DEC-15:20 | 70750.42 | 21-DEC-15:20 | 386.26 | 20-DEC-17:10 | 15783.97 | 29-DEC-15:50 | 0.00 |
Annual Sum or Average | 0.131326E+13 | 0.303529E+12 | 8756.67 | 0.130867E+13 | 0.459378E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.225841E+11 | 0.612113E+10 | 672.00 | 0.225698E+11 | 1331278.32 | 0.00 | 0.25 | 0.00 | 19795.60 | 19795.60 | 386.26 | 4853.53 | 0.00 | ||||||
Maximum of Months | 0.198835E+12 | 0.442242E+11 | 744.00 | 0.197467E+12 | 0.136855E+10 | 0.00 | 0.98 | 0.64 | 85131.53 | 85131.53 | 2790.36 | 24940.11 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.721067E+09 | 0.208270E+09 | 421.35 | 0.720154E+09 | 912189.37 | 0.00 | 0.23 | 19-JAN-16:30 | 0.00 | 01-JAN-00:05 | 1881.85 | 19-JAN-16:30 | 1881.85 | 19-JAN-16:30 | 45.96 | 18-JAN-16:40 | 463.63 | 19-JAN-16:30 | 0.00 |
February | 0.512921E+10 | 0.128460E+10 | 672.00 | 0.512798E+10 | 1232383.67 | 0.00 | 0.46 | 17-FEB-17:00 | 0.11 | 20-FEB-08:20 | 3858.27 | 27-FEB-17:00 | 3858.27 | 27-FEB-17:00 | 52.61 | 07-FEB-16:30 | 918.60 | 17-FEB-17:00 | 0.00 |
March | 0.112792E+11 | 0.266078E+10 | 744.00 | 0.112789E+11 | 289479.40 | 0.00 | 0.74 | 31-MAR-23:20 | 0.36 | 06-MAR-05:13 | 6390.32 | 31-MAR-23:20 | 6390.32 | 31-MAR-23:20 | 43.50 | 20-MAR-06:05 | 1461.06 | 31-MAR-23:20 | 0.00 |
April | 0.176189E+11 | 0.395580E+10 | 720.00 | 0.176182E+11 | 671506.46 | 0.00 | 0.98 | 30-APR-18:00 | 0.25 | 30-APR-23:57 | 8629.84 | 30-APR-18:00 | 8629.84 | 30-APR-18:00 | 56.08 | 28-APR-10:50 | 2445.99 | 30-APR-18:00 | 0.00 |
May | 0.382618E+10 | 0.970990E+09 | 743.91 | 0.380683E+10 | 19345576.69 | 0.00 | 0.41 | 31-MAY-23:20 | 0.00 | 15-MAY-04:53 | 3491.95 | 31-MAY-23:20 | 3491.95 | 31-MAY-23:20 | 137.72 | 23-MAY-16:00 | 809.66 | 31-MAY-23:20 | 0.00 |
June | 0.932354E+10 | 0.219182E+10 | 720.00 | 0.923966E+10 | 83884452.16 | 0.00 | 0.57 | 30-JUN-23:30 | 0.30 | 08-JUN-06:05 | 5044.49 | 30-JUN-23:30 | 5044.49 | 30-JUN-23:30 | 216.29 | 26-JUN-17:50 | 1416.60 | 13-JUN-16:00 | 0.00 |
July | 0.147640E+11 | 0.337370E+10 | 744.00 | 0.146534E+11 | 0.110665E+09 | 0.00 | 0.80 | 22-JUL-18:50 | 0.51 | 01-JUL-06:30 | 7221.71 | 31-JUL-23:20 | 7221.71 | 31-JUL-23:20 | 248.37 | 18-JUL-15:40 | 2205.12 | 22-JUL-18:35 | 0.00 |
August | 0.195761E+11 | 0.437238E+10 | 744.00 | 0.194395E+11 | 0.136582E+09 | 0.00 | 0.94 | 14-AUG-18:00 | 0.21 | 31-AUG-24:00 | 8344.49 | 13-AUG-17:52 | 8321.97 | 13-AUG-17:54 | 278.48 | 08-AUG-13:30 | 2519.26 | 14-AUG-18:00 | 0.00 |
September | 0.390848E+10 | 0.982494E+09 | 719.92 | 0.384667E+10 | 61813413.20 | 0.00 | 0.36 | 30-SEP-23:20 | 0.00 | 17-SEP-03:05 | 2889.09 | 30-SEP-23:20 | 2889.09 | 30-SEP-23:20 | 157.09 | 19-SEP-16:00 | 736.96 | 13-SEP-17:00 | 0.00 |
October | 0.708509E+10 | 0.170876E+10 | 744.00 | 0.705978E+10 | 25309653.39 | 0.00 | 0.52 | 31-OCT-23:20 | 0.18 | 23-OCT-06:05 | 4398.28 | 31-OCT-23:20 | 4398.28 | 31-OCT-23:20 | 126.85 | 17-OCT-15:40 | 1030.40 | 31-OCT-23:20 | 0.00 |
November | 0.104638E+11 | 0.244945E+10 | 720.00 | 0.104484E+11 | 15393064.48 | 0.00 | 0.63 | 03-NOV-16:00 | 0.33 | 27-NOV-04:55 | 5578.91 | 10-NOV-16:10 | 5557.34 | 10-NOV-16:10 | 141.45 | 08-NOV-15:10 | 1251.84 | 03-NOV-16:00 | 0.00 |
December | 0.146742E+11 | 0.338497E+10 | 744.00 | 0.146740E+11 | 120148.65 | 0.00 | 0.77 | 29-DEC-15:50 | 0.48 | 26-DEC-05:19 | 6855.48 | 21-DEC-15:20 | 6855.48 | 21-DEC-15:20 | 37.11 | 20-DEC-17:10 | 1516.94 | 29-DEC-15:50 | 0.00 |
Annual Sum or Average | 0.118370E+12 | 0.275440E+11 | 8437.17 | 0.117914E+12 | 0.456220E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.721067E+09 | 0.208270E+09 | 421.35 | 0.720154E+09 | 120148.65 | 0.00 | 0.23 | 0.00 | 1881.85 | 1881.85 | 37.11 | 463.63 | 0.00 | ||||||
Maximum of Months | 0.195761E+11 | 0.437238E+10 | 744.00 | 0.194395E+11 | 0.136582E+09 | 0.00 | 0.98 | 0.51 | 8629.84 | 8629.84 | 278.48 | 2519.26 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.96 | 0.00 | 91.96 | 2.32 | 657.35 | 0.00 | 0.00 | 0.00 |
February | 143.59 | 0.00 | 143.59 | 9.30 | 614.00 | 0.00 | 0.00 | 0.00 |
March | 198.71 | 0.00 | 198.71 | 45.31 | 514.19 | 0.00 | 0.00 | 0.00 |
April | 323.53 | 1.45 | 322.08 | 183.18 | 404.84 | 0.00 | 0.00 | 0.00 |
May | 404.49 | 19.51 | 384.98 | 238.59 | 314.71 | 0.00 | 0.00 | 0.00 |
June | 447.14 | 28.04 | 419.10 | 354.42 | 246.92 | 0.00 | 0.00 | 0.00 |
July | 424.14 | 24.18 | 399.96 | 357.69 | 229.60 | 0.00 | 0.00 | 0.00 |
August | 333.39 | 5.22 | 328.17 | 273.57 | 258.72 | 0.00 | 0.00 | 0.00 |
September | 253.76 | 0.06 | 253.70 | 175.56 | 341.96 | 0.00 | 0.00 | 0.00 |
October | 162.61 | 0.00 | 162.61 | 51.22 | 476.47 | 0.00 | 0.00 | 0.00 |
November | 97.70 | 0.00 | 97.70 | 3.86 | 600.06 | 0.00 | 0.00 | 0.00 |
December | 66.54 | 0.00 | 66.54 | 0.00 | 724.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 246.09 | 6.58 | 239.50 | 141.92 | 447.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 66.54 | 0.00 | 66.54 | 0.00 | 229.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 447.14 | 28.04 | 419.10 | 357.69 | 724.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.96 | 0.00 | 91.96 | 2.32 | 657.35 | 0.00 | 0.00 | 0.00 |
February | 143.59 | 0.00 | 143.59 | 9.30 | 614.00 | 0.00 | 0.00 | 0.00 |
March | 198.71 | 0.00 | 198.71 | 45.31 | 514.19 | 0.00 | 0.00 | 0.00 |
April | 323.53 | 1.45 | 322.08 | 183.18 | 404.84 | 0.00 | 0.00 | 0.00 |
May | 404.49 | 19.51 | 384.98 | 238.59 | 314.71 | 0.00 | 0.00 | 0.00 |
June | 447.14 | 28.04 | 419.10 | 354.42 | 246.92 | 0.00 | 0.00 | 0.00 |
July | 424.14 | 24.18 | 399.96 | 357.69 | 229.60 | 0.00 | 0.00 | 0.00 |
August | 333.39 | 5.22 | 328.17 | 273.57 | 258.72 | 0.00 | 0.00 | 0.00 |
September | 253.76 | 0.06 | 253.70 | 175.56 | 341.96 | 0.00 | 0.00 | 0.00 |
October | 162.61 | 0.00 | 162.61 | 51.22 | 476.47 | 0.00 | 0.00 | 0.00 |
November | 97.70 | 0.00 | 97.70 | 3.86 | 600.06 | 0.00 | 0.00 | 0.00 |
December | 66.54 | 0.00 | 66.54 | 0.00 | 724.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 246.09 | 6.58 | 239.50 | 141.92 | 447.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 66.54 | 0.00 | 66.54 | 0.00 | 229.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 447.14 | 28.04 | 419.10 | 357.69 | 724.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.96 | 0.00 | 91.96 | 2.32 | 657.35 | 0.00 | 0.00 | 0.00 |
February | 143.59 | 0.00 | 143.59 | 9.30 | 614.00 | 0.00 | 0.00 | 0.00 |
March | 198.71 | 0.00 | 198.71 | 45.31 | 514.19 | 0.00 | 0.00 | 0.00 |
April | 323.53 | 1.45 | 322.08 | 183.18 | 404.84 | 0.00 | 0.00 | 0.00 |
May | 404.49 | 19.51 | 384.98 | 238.59 | 314.71 | 0.00 | 0.00 | 0.00 |
June | 447.14 | 28.04 | 419.10 | 354.42 | 246.92 | 0.00 | 0.00 | 0.00 |
July | 424.14 | 24.18 | 399.96 | 357.69 | 229.60 | 0.00 | 0.00 | 0.00 |
August | 333.39 | 5.22 | 328.17 | 273.57 | 258.72 | 0.00 | 0.00 | 0.00 |
September | 253.76 | 0.06 | 253.70 | 175.56 | 341.96 | 0.00 | 0.00 | 0.00 |
October | 162.61 | 0.00 | 162.61 | 51.22 | 476.47 | 0.00 | 0.00 | 0.00 |
November | 97.70 | 0.00 | 97.70 | 3.86 | 600.06 | 0.00 | 0.00 | 0.00 |
December | 66.54 | 0.00 | 66.54 | 0.00 | 724.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 246.09 | 6.58 | 239.50 | 141.92 | 447.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 66.54 | 0.00 | 66.54 | 0.00 | 229.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 447.14 | 28.04 | 419.10 | 357.69 | 724.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.96 | 0.00 | 91.96 | 2.32 | 657.35 | 0.00 | 0.00 | 0.00 |
February | 143.59 | 0.00 | 143.59 | 9.30 | 614.00 | 0.00 | 0.00 | 0.00 |
March | 198.71 | 0.00 | 198.71 | 45.31 | 514.19 | 0.00 | 0.00 | 0.00 |
April | 323.53 | 1.45 | 322.08 | 183.18 | 404.84 | 0.00 | 0.00 | 0.00 |
May | 404.49 | 19.51 | 384.98 | 238.59 | 314.71 | 0.00 | 0.00 | 0.00 |
June | 447.14 | 28.04 | 419.10 | 354.42 | 246.92 | 0.00 | 0.00 | 0.00 |
July | 424.14 | 24.18 | 399.96 | 357.69 | 229.60 | 0.00 | 0.00 | 0.00 |
August | 333.39 | 5.22 | 328.17 | 273.57 | 258.72 | 0.00 | 0.00 | 0.00 |
September | 253.76 | 0.06 | 253.70 | 175.56 | 341.96 | 0.00 | 0.00 | 0.00 |
October | 162.61 | 0.00 | 162.61 | 51.22 | 476.47 | 0.00 | 0.00 | 0.00 |
November | 97.70 | 0.00 | 97.70 | 3.86 | 600.06 | 0.00 | 0.00 | 0.00 |
December | 66.54 | 0.00 | 66.54 | 0.00 | 724.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 246.09 | 6.58 | 239.50 | 141.92 | 447.79 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 66.54 | 0.00 | 66.54 | 0.00 | 229.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 447.14 | 28.04 | 419.10 | 357.69 | 724.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.95 | 0.00 | 91.95 | 2.32 | 657.32 | 0.00 | 0.00 | 0.00 |
February | 143.59 | 0.00 | 143.59 | 9.30 | 613.97 | 0.00 | 0.00 | 0.00 |
March | 198.70 | 0.00 | 198.70 | 45.30 | 514.17 | 0.00 | 0.00 | 0.00 |
April | 323.52 | 1.45 | 322.07 | 183.17 | 404.83 | 0.00 | 0.00 | 0.00 |
May | 404.48 | 19.51 | 384.96 | 238.58 | 314.69 | 0.00 | 0.00 | 0.00 |
June | 447.12 | 28.04 | 419.09 | 354.41 | 246.91 | 0.00 | 0.00 | 0.00 |
July | 424.12 | 24.18 | 399.94 | 357.68 | 229.59 | 0.00 | 0.00 | 0.00 |
August | 333.38 | 5.22 | 328.16 | 273.56 | 258.71 | 0.00 | 0.00 | 0.00 |
September | 253.75 | 0.06 | 253.69 | 175.55 | 341.95 | 0.00 | 0.00 | 0.00 |
October | 162.60 | 0.00 | 162.60 | 51.22 | 476.45 | 0.00 | 0.00 | 0.00 |
November | 97.70 | 0.00 | 97.70 | 3.86 | 600.03 | 0.00 | 0.00 | 0.00 |
December | 66.53 | 0.00 | 66.53 | 0.00 | 724.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 246.08 | 6.58 | 239.49 | 141.91 | 447.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 66.53 | 0.00 | 66.53 | 0.00 | 229.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 447.12 | 28.04 | 419.09 | 357.68 | 724.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 208.84 | 83.89 | 124.95 | 108.66 | 669.77 | 0.00 | 0.00 | 0.00 |
February | 311.41 | 115.04 | 196.38 | 184.09 | 626.02 | 0.00 | 0.00 | 0.00 |
March | 325.43 | 64.13 | 261.30 | 174.33 | 520.02 | 0.00 | 0.00 | 0.00 |
April | 873.82 | 410.61 | 463.21 | 889.17 | 412.02 | 0.00 | 0.00 | 0.00 |
May | 918.79 | 400.67 | 518.12 | 911.71 | 352.56 | 0.00 | 0.00 | 0.00 |
June | 909.44 | 363.22 | 546.22 | 967.56 | 274.40 | 0.00 | 0.00 | 0.00 |
July | 928.36 | 394.55 | 533.80 | 1032.64 | 253.48 | 0.00 | 0.00 | 0.00 |
August | 879.41 | 420.18 | 459.24 | 1008.74 | 273.74 | 0.00 | 0.00 | 0.00 |
September | 791.94 | 421.12 | 370.82 | 874.71 | 354.15 | 0.00 | 0.00 | 0.00 |
October | 382.28 | 158.43 | 223.85 | 319.69 | 492.82 | 0.00 | 0.00 | 0.00 |
November | 199.29 | 67.92 | 131.37 | 102.53 | 607.18 | 0.00 | 0.00 | 0.00 |
December | 147.70 | 54.91 | 92.79 | 65.35 | 730.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 573.89 | 246.54 | 327.35 | 554.60 | 463.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 147.70 | 54.91 | 92.79 | 65.35 | 253.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 928.36 | 421.12 | 546.22 | 1032.64 | 730.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 208.84 | 83.89 | 124.95 | 108.66 | 669.77 | 0.00 | 0.00 | 0.00 |
February | 311.41 | 115.04 | 196.38 | 184.09 | 626.02 | 0.00 | 0.00 | 0.00 |
March | 325.43 | 64.13 | 261.30 | 174.33 | 520.02 | 0.00 | 0.00 | 0.00 |
April | 873.82 | 410.61 | 463.21 | 889.17 | 412.02 | 0.00 | 0.00 | 0.00 |
May | 918.79 | 400.67 | 518.12 | 911.71 | 352.56 | 0.00 | 0.00 | 0.00 |
June | 909.44 | 363.22 | 546.22 | 967.56 | 274.40 | 0.00 | 0.00 | 0.00 |
July | 928.36 | 394.55 | 533.80 | 1032.64 | 253.48 | 0.00 | 0.00 | 0.00 |
August | 879.41 | 420.18 | 459.24 | 1008.74 | 273.74 | 0.00 | 0.00 | 0.00 |
September | 791.94 | 421.12 | 370.82 | 874.71 | 354.15 | 0.00 | 0.00 | 0.00 |
October | 382.28 | 158.43 | 223.85 | 319.69 | 492.82 | 0.00 | 0.00 | 0.00 |
November | 199.29 | 67.92 | 131.37 | 102.53 | 607.18 | 0.00 | 0.00 | 0.00 |
December | 147.70 | 54.91 | 92.79 | 65.35 | 730.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 573.89 | 246.54 | 327.35 | 554.60 | 463.10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 147.70 | 54.91 | 92.79 | 65.35 | 253.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 928.36 | 421.12 | 546.22 | 1032.64 | 730.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 208.83 | 83.89 | 124.95 | 108.66 | 669.75 | 0.00 | 0.00 | 0.00 |
February | 311.41 | 115.04 | 196.37 | 184.09 | 626.01 | 0.00 | 0.00 | 0.00 |
March | 325.43 | 64.13 | 261.30 | 174.32 | 520.01 | 0.00 | 0.00 | 0.00 |
April | 873.80 | 410.61 | 463.20 | 889.15 | 412.01 | 0.00 | 0.00 | 0.00 |
May | 918.78 | 400.66 | 518.11 | 911.69 | 352.56 | 0.00 | 0.00 | 0.00 |
June | 909.42 | 363.21 | 546.21 | 967.54 | 274.39 | 0.00 | 0.00 | 0.00 |
July | 928.34 | 394.54 | 533.79 | 1032.62 | 253.48 | 0.00 | 0.00 | 0.00 |
August | 879.40 | 420.17 | 459.23 | 1008.72 | 273.73 | 0.00 | 0.00 | 0.00 |
September | 791.93 | 421.11 | 370.82 | 874.69 | 354.14 | 0.00 | 0.00 | 0.00 |
October | 382.27 | 158.42 | 223.85 | 319.69 | 492.81 | 0.00 | 0.00 | 0.00 |
November | 199.29 | 67.92 | 131.37 | 102.53 | 607.17 | 0.00 | 0.00 | 0.00 |
December | 147.70 | 54.91 | 92.79 | 65.35 | 730.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 573.88 | 246.53 | 327.34 | 554.59 | 463.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 147.70 | 54.91 | 92.79 | 65.35 | 253.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 928.34 | 421.11 | 546.21 | 1032.62 | 730.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 522.07 | 337.96 | 184.11 | 499.64 | 558.80 | 0.00 | 0.00 | 0.00 |
February | 637.61 | 389.08 | 248.53 | 629.14 | 547.89 | 0.00 | 0.00 | 0.00 |
March | 394.21 | 114.78 | 279.44 | 299.88 | 468.45 | 0.00 | 0.00 | 0.00 |
April | 818.61 | 370.00 | 448.61 | 912.29 | 405.36 | 0.00 | 0.00 | 0.00 |
May | 677.07 | 220.43 | 456.64 | 696.45 | 344.93 | 0.00 | 0.00 | 0.00 |
June | 623.73 | 150.98 | 472.75 | 668.58 | 268.03 | 0.00 | 0.00 | 0.00 |
July | 675.79 | 211.63 | 464.16 | 781.89 | 250.64 | 0.00 | 0.00 | 0.00 |
August | 791.88 | 356.22 | 435.66 | 974.10 | 273.09 | 0.00 | 0.00 | 0.00 |
September | 935.80 | 548.21 | 387.59 | 1143.35 | 341.45 | 0.00 | 0.00 | 0.00 |
October | 642.93 | 375.77 | 267.17 | 693.85 | 444.63 | 0.00 | 0.00 | 0.00 |
November | 455.84 | 277.30 | 178.54 | 438.74 | 531.35 | 0.00 | 0.00 | 0.00 |
December | 361.29 | 231.48 | 129.81 | 333.31 | 636.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 627.11 | 297.49 | 329.62 | 671.66 | 421.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 361.29 | 114.78 | 129.81 | 299.88 | 250.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 935.80 | 548.21 | 472.75 | 1143.35 | 636.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 522.07 | 337.96 | 184.11 | 499.64 | 558.80 | 0.00 | 0.00 | 0.00 |
February | 637.61 | 389.08 | 248.53 | 629.14 | 547.89 | 0.00 | 0.00 | 0.00 |
March | 394.21 | 114.78 | 279.43 | 299.88 | 468.45 | 0.00 | 0.00 | 0.00 |
April | 818.61 | 370.00 | 448.61 | 912.29 | 405.36 | 0.00 | 0.00 | 0.00 |
May | 677.07 | 220.43 | 456.64 | 696.45 | 344.93 | 0.00 | 0.00 | 0.00 |
June | 623.72 | 150.98 | 472.75 | 668.58 | 268.03 | 0.00 | 0.00 | 0.00 |
July | 675.79 | 211.63 | 464.16 | 781.89 | 250.64 | 0.00 | 0.00 | 0.00 |
August | 791.88 | 356.22 | 435.66 | 974.10 | 273.09 | 0.00 | 0.00 | 0.00 |
September | 935.80 | 548.21 | 387.59 | 1143.35 | 341.45 | 0.00 | 0.00 | 0.00 |
October | 642.93 | 375.76 | 267.17 | 693.85 | 444.63 | 0.00 | 0.00 | 0.00 |
November | 455.84 | 277.30 | 178.54 | 438.74 | 531.35 | 0.00 | 0.00 | 0.00 |
December | 361.29 | 231.48 | 129.81 | 333.31 | 636.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 627.11 | 297.49 | 329.62 | 671.66 | 421.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 361.29 | 114.78 | 129.81 | 299.88 | 250.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 935.80 | 548.21 | 472.75 | 1143.35 | 636.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 522.07 | 337.96 | 184.11 | 499.64 | 558.80 | 0.00 | 0.00 | 0.00 |
February | 637.61 | 389.08 | 248.53 | 629.14 | 547.89 | 0.00 | 0.00 | 0.00 |
March | 394.21 | 114.78 | 279.44 | 299.88 | 468.45 | 0.00 | 0.00 | 0.00 |
April | 818.61 | 370.00 | 448.61 | 912.29 | 405.36 | 0.00 | 0.00 | 0.00 |
May | 677.07 | 220.43 | 456.64 | 696.45 | 344.93 | 0.00 | 0.00 | 0.00 |
June | 623.73 | 150.98 | 472.75 | 668.58 | 268.03 | 0.00 | 0.00 | 0.00 |
July | 675.79 | 211.63 | 464.16 | 781.89 | 250.64 | 0.00 | 0.00 | 0.00 |
August | 791.88 | 356.22 | 435.66 | 974.10 | 273.09 | 0.00 | 0.00 | 0.00 |
September | 935.80 | 548.21 | 387.59 | 1143.35 | 341.45 | 0.00 | 0.00 | 0.00 |
October | 642.93 | 375.77 | 267.17 | 693.85 | 444.63 | 0.00 | 0.00 | 0.00 |
November | 455.84 | 277.30 | 178.54 | 438.74 | 531.35 | 0.00 | 0.00 | 0.00 |
December | 361.29 | 231.48 | 129.81 | 333.31 | 636.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 627.11 | 297.49 | 329.62 | 671.66 | 421.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 361.29 | 114.78 | 129.81 | 299.88 | 250.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 935.80 | 548.21 | 472.75 | 1143.35 | 636.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 522.07 | 337.96 | 184.11 | 499.64 | 558.80 | 0.00 | 0.00 | 0.00 |
February | 637.61 | 389.08 | 248.53 | 629.14 | 547.89 | 0.00 | 0.00 | 0.00 |
March | 394.21 | 114.78 | 279.43 | 299.88 | 468.45 | 0.00 | 0.00 | 0.00 |
April | 818.61 | 370.00 | 448.61 | 912.29 | 405.36 | 0.00 | 0.00 | 0.00 |
May | 677.07 | 220.43 | 456.64 | 696.45 | 344.93 | 0.00 | 0.00 | 0.00 |
June | 623.72 | 150.98 | 472.75 | 668.58 | 268.03 | 0.00 | 0.00 | 0.00 |
July | 675.79 | 211.63 | 464.16 | 781.89 | 250.64 | 0.00 | 0.00 | 0.00 |
August | 791.88 | 356.22 | 435.66 | 974.10 | 273.09 | 0.00 | 0.00 | 0.00 |
September | 935.80 | 548.21 | 387.59 | 1143.35 | 341.45 | 0.00 | 0.00 | 0.00 |
October | 642.93 | 375.76 | 267.17 | 693.85 | 444.63 | 0.00 | 0.00 | 0.00 |
November | 455.84 | 277.30 | 178.54 | 438.74 | 531.35 | 0.00 | 0.00 | 0.00 |
December | 361.29 | 231.48 | 129.81 | 333.31 | 636.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 627.11 | 297.49 | 329.62 | 671.66 | 421.92 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 361.29 | 114.78 | 129.81 | 299.88 | 250.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 935.80 | 548.21 | 472.75 | 1143.35 | 636.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 522.05 | 337.94 | 184.10 | 499.62 | 558.77 | 0.00 | 0.00 | 0.00 |
February | 637.58 | 389.06 | 248.52 | 629.11 | 547.86 | 0.00 | 0.00 | 0.00 |
March | 394.20 | 114.77 | 279.42 | 299.87 | 468.43 | 0.00 | 0.00 | 0.00 |
April | 818.58 | 369.99 | 448.59 | 912.25 | 405.34 | 0.00 | 0.00 | 0.00 |
May | 677.04 | 220.42 | 456.62 | 696.42 | 344.92 | 0.00 | 0.00 | 0.00 |
June | 623.70 | 150.97 | 472.73 | 668.55 | 268.02 | 0.00 | 0.00 | 0.00 |
July | 675.77 | 211.62 | 464.14 | 781.86 | 250.63 | 0.00 | 0.00 | 0.00 |
August | 791.85 | 356.20 | 435.65 | 974.06 | 273.08 | 0.00 | 0.00 | 0.00 |
September | 935.76 | 548.18 | 387.58 | 1143.30 | 341.44 | 0.00 | 0.00 | 0.00 |
October | 642.91 | 375.75 | 267.16 | 693.82 | 444.61 | 0.00 | 0.00 | 0.00 |
November | 455.82 | 277.29 | 178.53 | 438.72 | 531.32 | 0.00 | 0.00 | 0.00 |
December | 361.28 | 231.47 | 129.81 | 333.29 | 636.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 627.08 | 297.48 | 329.60 | 671.64 | 421.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 361.28 | 114.77 | 129.81 | 299.87 | 250.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 935.76 | 548.18 | 472.73 | 1143.30 | 636.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 203.09 | 67.10 | 135.99 | 105.81 | 716.96 | 0.00 | 0.00 | 0.00 |
February | 359.57 | 151.82 | 207.75 | 257.27 | 702.84 | 0.00 | 0.00 | 0.00 |
March | 325.13 | 62.20 | 262.93 | 159.22 | 599.84 | 0.00 | 0.00 | 0.00 |
April | 767.16 | 304.72 | 462.44 | 739.52 | 498.27 | 0.00 | 0.00 | 0.00 |
May | 900.05 | 365.99 | 534.06 | 883.46 | 397.24 | 0.00 | 0.00 | 0.00 |
June | 971.96 | 400.12 | 571.84 | 1036.43 | 323.16 | 0.00 | 0.00 | 0.00 |
July | 989.90 | 436.45 | 553.45 | 1099.37 | 309.22 | 0.00 | 0.00 | 0.00 |
August | 831.45 | 359.99 | 471.45 | 928.54 | 342.78 | 0.00 | 0.00 | 0.00 |
September | 667.04 | 299.12 | 367.93 | 719.10 | 404.47 | 0.00 | 0.00 | 0.00 |
October | 355.84 | 127.96 | 227.88 | 283.32 | 560.89 | 0.00 | 0.00 | 0.00 |
November | 192.57 | 56.21 | 136.36 | 98.23 | 708.24 | 0.00 | 0.00 | 0.00 |
December | 109.00 | 23.00 | 86.00 | 29.62 | 871.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 556.65 | 221.31 | 335.34 | 529.24 | 535.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 109.00 | 23.00 | 86.00 | 29.62 | 309.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 989.90 | 436.45 | 571.84 | 1099.37 | 871.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 203.09 | 67.10 | 135.99 | 105.81 | 716.96 | 0.00 | 0.00 | 0.00 |
February | 359.57 | 151.82 | 207.75 | 257.27 | 702.84 | 0.00 | 0.00 | 0.00 |
March | 325.13 | 62.20 | 262.93 | 159.22 | 599.84 | 0.00 | 0.00 | 0.00 |
April | 767.16 | 304.72 | 462.44 | 739.52 | 498.27 | 0.00 | 0.00 | 0.00 |
May | 900.05 | 365.99 | 534.06 | 883.46 | 397.24 | 0.00 | 0.00 | 0.00 |
June | 971.96 | 400.12 | 571.84 | 1036.43 | 323.16 | 0.00 | 0.00 | 0.00 |
July | 989.90 | 436.45 | 553.45 | 1099.37 | 309.22 | 0.00 | 0.00 | 0.00 |
August | 831.45 | 359.99 | 471.45 | 928.54 | 342.78 | 0.00 | 0.00 | 0.00 |
September | 667.04 | 299.12 | 367.93 | 719.10 | 404.47 | 0.00 | 0.00 | 0.00 |
October | 355.84 | 127.96 | 227.88 | 283.32 | 560.89 | 0.00 | 0.00 | 0.00 |
November | 192.57 | 56.21 | 136.36 | 98.23 | 708.24 | 0.00 | 0.00 | 0.00 |
December | 109.00 | 23.00 | 86.00 | 29.62 | 871.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 556.65 | 221.31 | 335.34 | 529.24 | 535.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 109.00 | 23.00 | 86.00 | 29.62 | 309.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 989.90 | 436.45 | 571.84 | 1099.37 | 871.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 203.08 | 67.10 | 135.98 | 105.80 | 716.95 | 0.00 | 0.00 | 0.00 |
February | 359.57 | 151.82 | 207.75 | 257.26 | 702.83 | 0.00 | 0.00 | 0.00 |
March | 325.12 | 62.20 | 262.93 | 159.22 | 599.83 | 0.00 | 0.00 | 0.00 |
April | 767.14 | 304.72 | 462.43 | 739.51 | 498.26 | 0.00 | 0.00 | 0.00 |
May | 900.04 | 365.99 | 534.05 | 883.45 | 397.23 | 0.00 | 0.00 | 0.00 |
June | 971.94 | 400.11 | 571.83 | 1036.41 | 323.15 | 0.00 | 0.00 | 0.00 |
July | 989.88 | 436.44 | 553.44 | 1099.35 | 309.21 | 0.00 | 0.00 | 0.00 |
August | 831.43 | 359.99 | 471.45 | 928.53 | 342.78 | 0.00 | 0.00 | 0.00 |
September | 667.03 | 299.11 | 367.92 | 719.09 | 404.47 | 0.00 | 0.00 | 0.00 |
October | 355.83 | 127.96 | 227.88 | 283.31 | 560.88 | 0.00 | 0.00 | 0.00 |
November | 192.57 | 56.21 | 136.35 | 98.23 | 708.22 | 0.00 | 0.00 | 0.00 |
December | 109.00 | 23.00 | 86.00 | 29.62 | 871.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 556.64 | 221.31 | 335.33 | 529.23 | 535.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 109.00 | 23.00 | 86.00 | 29.62 | 309.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 989.88 | 436.44 | 571.83 | 1099.35 | 871.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 459.78 | 0.00 | 459.78 | 25.76 | 2907.07 | 0.00 | 0.00 | 0.00 |
February | 717.96 | 0.00 | 717.96 | 87.23 | 2718.34 | 0.00 | 0.00 | 0.00 |
March | 993.53 | 0.00 | 993.53 | 295.04 | 2266.04 | 0.00 | 0.00 | 0.00 |
April | 1617.62 | 7.24 | 1610.38 | 975.04 | 1848.39 | 0.00 | 0.00 | 0.00 |
May | 2022.44 | 97.57 | 1924.87 | 1236.78 | 1484.94 | 0.00 | 0.00 | 0.00 |
June | 2235.68 | 140.19 | 2095.49 | 1795.03 | 1175.69 | 0.00 | 0.00 | 0.00 |
July | 2120.67 | 120.91 | 1999.76 | 1833.49 | 1079.64 | 0.00 | 0.00 | 0.00 |
August | 1666.95 | 26.12 | 1640.83 | 1411.97 | 1202.47 | 0.00 | 0.00 | 0.00 |
September | 1268.78 | 0.28 | 1268.50 | 919.19 | 1597.05 | 0.00 | 0.00 | 0.00 |
October | 813.02 | 0.00 | 813.02 | 311.55 | 2116.77 | 0.00 | 0.00 | 0.00 |
November | 488.51 | 0.00 | 488.51 | 42.47 | 2575.70 | 0.00 | 0.00 | 0.00 |
December | 332.67 | 0.00 | 332.67 | 1.10 | 3100.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1230.42 | 32.92 | 1197.50 | 747.89 | 2002.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 332.67 | 0.00 | 332.67 | 1.10 | 1079.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2235.68 | 140.19 | 2095.49 | 1833.49 | 3100.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 626.51 | 251.67 | 374.84 | 351.42 | 1821.81 | 0.00 | 0.00 | 0.00 |
February | 934.23 | 345.11 | 589.12 | 582.40 | 1722.40 | 0.00 | 0.00 | 0.00 |
March | 976.29 | 192.39 | 783.90 | 567.24 | 1425.43 | 0.00 | 0.00 | 0.00 |
April | 2621.43 | 1231.83 | 1389.60 | 2668.29 | 1180.94 | 0.00 | 0.00 | 0.00 |
May | 2756.35 | 1202.00 | 1554.35 | 2730.05 | 1014.42 | 0.00 | 0.00 | 0.00 |
June | 2728.28 | 1089.65 | 1638.63 | 2892.10 | 797.21 | 0.00 | 0.00 | 0.00 |
July | 2785.04 | 1183.64 | 1601.40 | 3087.74 | 737.24 | 0.00 | 0.00 | 0.00 |
August | 2638.22 | 1260.51 | 1377.70 | 3018.09 | 799.25 | 0.00 | 0.00 | 0.00 |
September | 2375.80 | 1263.34 | 1112.46 | 2621.27 | 1018.74 | 0.00 | 0.00 | 0.00 |
October | 1146.83 | 475.28 | 671.55 | 983.56 | 1355.34 | 0.00 | 0.00 | 0.00 |
November | 597.88 | 203.77 | 394.11 | 331.39 | 1628.59 | 0.00 | 0.00 | 0.00 |
December | 443.10 | 164.74 | 278.36 | 216.70 | 1966.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1721.65 | 739.61 | 982.04 | 1674.79 | 1286.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 443.10 | 164.74 | 278.36 | 216.70 | 737.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2785.04 | 1263.34 | 1638.63 | 3087.74 | 1966.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2610.30 | 1689.76 | 920.55 | 2509.14 | 2687.75 | 0.00 | 0.00 | 0.00 |
February | 3188.01 | 1945.37 | 1242.64 | 3151.33 | 2645.26 | 0.00 | 0.00 | 0.00 |
March | 1971.04 | 573.88 | 1397.16 | 1530.24 | 2208.92 | 0.00 | 0.00 | 0.00 |
April | 4093.02 | 1850.00 | 2243.02 | 4556.29 | 1953.19 | 0.00 | 0.00 | 0.00 |
May | 3385.31 | 1102.15 | 2283.16 | 3474.07 | 1682.42 | 0.00 | 0.00 | 0.00 |
June | 3118.59 | 754.88 | 2363.71 | 3341.69 | 1299.27 | 0.00 | 0.00 | 0.00 |
July | 3378.93 | 1058.15 | 2320.78 | 3913.24 | 1208.12 | 0.00 | 0.00 | 0.00 |
August | 3959.37 | 1781.07 | 2178.30 | 4865.40 | 1320.50 | 0.00 | 0.00 | 0.00 |
September | 4678.94 | 2741.00 | 1937.94 | 5691.19 | 1679.33 | 0.00 | 0.00 | 0.00 |
October | 3214.62 | 1878.80 | 1335.82 | 3470.15 | 2132.21 | 0.00 | 0.00 | 0.00 |
November | 2279.17 | 1386.48 | 892.69 | 2207.74 | 2498.78 | 0.00 | 0.00 | 0.00 |
December | 1806.45 | 1157.40 | 649.05 | 1691.92 | 2973.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3135.51 | 1487.45 | 1648.07 | 3362.26 | 2020.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1806.45 | 573.88 | 649.05 | 1530.24 | 1208.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4678.94 | 2741.00 | 2363.71 | 5691.19 | 2973.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 609.25 | 201.30 | 407.95 | 347.86 | 1894.67 | 0.00 | 0.00 | 0.00 |
February | 1078.71 | 455.46 | 623.24 | 821.46 | 1821.71 | 0.00 | 0.00 | 0.00 |
March | 975.38 | 186.59 | 788.79 | 557.71 | 1487.31 | 0.00 | 0.00 | 0.00 |
April | 2301.45 | 914.15 | 1387.29 | 2296.79 | 1292.26 | 0.00 | 0.00 | 0.00 |
May | 2700.13 | 1097.97 | 1602.16 | 2682.90 | 1111.50 | 0.00 | 0.00 | 0.00 |
June | 2915.85 | 1200.34 | 1715.50 | 3139.30 | 886.72 | 0.00 | 0.00 | 0.00 |
July | 2969.66 | 1309.33 | 1660.33 | 3347.25 | 828.97 | 0.00 | 0.00 | 0.00 |
August | 2494.32 | 1079.97 | 1414.35 | 2841.00 | 899.17 | 0.00 | 0.00 | 0.00 |
September | 2001.11 | 897.34 | 1103.77 | 2192.47 | 1117.36 | 0.00 | 0.00 | 0.00 |
October | 1067.51 | 383.87 | 683.64 | 906.65 | 1435.57 | 0.00 | 0.00 | 0.00 |
November | 577.70 | 168.64 | 409.06 | 335.67 | 1724.39 | 0.00 | 0.00 | 0.00 |
December | 327.00 | 69.00 | 257.99 | 111.39 | 2093.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1669.94 | 663.94 | 1006.00 | 1634.43 | 1380.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 327.00 | 69.00 | 257.99 | 111.39 | 828.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2969.66 | 1309.33 | 1715.50 | 3347.25 | 2093.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 459.78 | 0.00 | 459.78 | 42.76 | 2637.62 | 0.00 | 0.00 | 0.00 |
February | 717.96 | 0.00 | 717.96 | 126.90 | 2472.95 | 0.00 | 0.00 | 0.00 |
March | 993.53 | 0.00 | 993.53 | 348.17 | 2071.25 | 0.00 | 0.00 | 0.00 |
April | 1617.62 | 7.24 | 1610.38 | 1019.15 | 1731.97 | 0.00 | 0.00 | 0.00 |
May | 2022.44 | 97.57 | 1924.87 | 1289.95 | 1398.73 | 0.00 | 0.00 | 0.00 |
June | 2235.68 | 140.19 | 2095.49 | 1813.61 | 1132.93 | 0.00 | 0.00 | 0.00 |
July | 2120.67 | 120.91 | 1999.76 | 1846.48 | 1045.68 | 0.00 | 0.00 | 0.00 |
August | 1666.95 | 26.12 | 1640.83 | 1425.73 | 1158.24 | 0.00 | 0.00 | 0.00 |
September | 1268.78 | 0.28 | 1268.50 | 956.20 | 1500.29 | 0.00 | 0.00 | 0.00 |
October | 813.02 | 0.00 | 813.02 | 364.71 | 1904.45 | 0.00 | 0.00 | 0.00 |
November | 488.51 | 0.00 | 488.51 | 64.87 | 2313.79 | 0.00 | 0.00 | 0.00 |
December | 332.67 | 0.00 | 332.67 | 7.42 | 2832.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1230.42 | 32.92 | 1197.50 | 778.77 | 1846.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 332.67 | 0.00 | 332.67 | 7.42 | 1045.68 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2235.68 | 140.19 | 2095.49 | 1846.48 | 2832.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 626.51 | 251.67 | 374.84 | 376.14 | 1660.95 | 0.00 | 0.00 | 0.00 |
February | 934.23 | 345.11 | 589.12 | 619.19 | 1578.98 | 0.00 | 0.00 | 0.00 |
March | 976.29 | 192.39 | 783.90 | 604.96 | 1316.27 | 0.00 | 0.00 | 0.00 |
April | 2621.43 | 1231.83 | 1389.60 | 2689.05 | 1122.93 | 0.00 | 0.00 | 0.00 |
May | 2756.35 | 1202.00 | 1554.35 | 2749.92 | 968.45 | 0.00 | 0.00 | 0.00 |
June | 2728.28 | 1089.65 | 1638.63 | 2896.45 | 774.63 | 0.00 | 0.00 | 0.00 |
July | 2785.04 | 1183.64 | 1601.40 | 3086.82 | 720.53 | 0.00 | 0.00 | 0.00 |
August | 2638.22 | 1260.51 | 1377.70 | 3018.67 | 778.79 | 0.00 | 0.00 | 0.00 |
September | 2375.80 | 1263.34 | 1112.46 | 2636.21 | 972.84 | 0.00 | 0.00 | 0.00 |
October | 1146.83 | 475.28 | 671.55 | 1016.96 | 1238.41 | 0.00 | 0.00 | 0.00 |
November | 597.88 | 203.77 | 394.11 | 355.10 | 1478.42 | 0.00 | 0.00 | 0.00 |
December | 443.10 | 164.74 | 278.36 | 233.69 | 1805.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1721.65 | 739.61 | 982.04 | 1694.09 | 1199.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 443.10 | 164.74 | 278.36 | 233.69 | 720.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2785.04 | 1263.34 | 1638.63 | 3086.82 | 1805.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2610.30 | 1689.76 | 920.55 | 2569.60 | 2448.27 | 0.00 | 0.00 | 0.00 |
February | 3188.01 | 1945.37 | 1242.64 | 3212.90 | 2430.61 | 0.00 | 0.00 | 0.00 |
March | 1971.04 | 573.88 | 1397.16 | 1589.61 | 2032.75 | 0.00 | 0.00 | 0.00 |
April | 4093.02 | 1850.00 | 2243.02 | 4582.94 | 1852.39 | 0.00 | 0.00 | 0.00 |
May | 3385.31 | 1102.15 | 2283.16 | 3503.37 | 1594.67 | 0.00 | 0.00 | 0.00 |
June | 3118.59 | 754.88 | 2363.71 | 3353.55 | 1253.16 | 0.00 | 0.00 | 0.00 |
July | 3378.93 | 1058.15 | 2320.78 | 3917.71 | 1171.66 | 0.00 | 0.00 | 0.00 |
August | 3959.37 | 1781.07 | 2178.30 | 4868.12 | 1278.39 | 0.00 | 0.00 | 0.00 |
September | 4678.94 | 2741.00 | 1937.94 | 5709.41 | 1598.83 | 0.00 | 0.00 | 0.00 |
October | 3214.62 | 1878.80 | 1335.82 | 3515.66 | 1950.58 | 0.00 | 0.00 | 0.00 |
November | 2279.17 | 1386.48 | 892.69 | 2253.32 | 2268.75 | 0.00 | 0.00 | 0.00 |
December | 1806.45 | 1157.40 | 649.05 | 1733.45 | 2726.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3135.51 | 1487.45 | 1648.07 | 3396.06 | 1880.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1806.45 | 573.88 | 649.05 | 1589.61 | 1171.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4678.94 | 2741.00 | 2363.71 | 5709.41 | 2726.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 609.25 | 201.30 | 407.95 | 365.56 | 1748.99 | 0.00 | 0.00 | 0.00 |
February | 1078.71 | 455.46 | 623.24 | 844.35 | 1697.07 | 0.00 | 0.00 | 0.00 |
March | 975.38 | 186.59 | 788.79 | 584.80 | 1388.21 | 0.00 | 0.00 | 0.00 |
April | 2301.45 | 914.15 | 1387.29 | 2315.63 | 1230.28 | 0.00 | 0.00 | 0.00 |
May | 2700.13 | 1097.97 | 1602.16 | 2699.33 | 1060.66 | 0.00 | 0.00 | 0.00 |
June | 2915.85 | 1200.34 | 1715.50 | 3141.81 | 858.80 | 0.00 | 0.00 | 0.00 |
July | 2969.66 | 1309.33 | 1660.33 | 3345.41 | 806.79 | 0.00 | 0.00 | 0.00 |
August | 2494.32 | 1079.97 | 1414.35 | 2842.33 | 872.14 | 0.00 | 0.00 | 0.00 |
September | 2001.11 | 897.34 | 1103.77 | 2207.69 | 1065.14 | 0.00 | 0.00 | 0.00 |
October | 1067.51 | 383.87 | 683.64 | 932.00 | 1329.32 | 0.00 | 0.00 | 0.00 |
November | 577.70 | 168.64 | 409.06 | 350.10 | 1592.26 | 0.00 | 0.00 | 0.00 |
December | 327.00 | 69.00 | 257.99 | 119.10 | 1949.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1669.94 | 663.94 | 1006.00 | 1648.34 | 1297.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 327.00 | 69.00 | 257.99 | 119.10 | 806.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2969.66 | 1309.33 | 1715.50 | 3345.41 | 1949.94 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246297E+09 | 0.00 | 0.246297E+09 | 6223954.22 | 0.176064E+10 |
February | 0.347383E+09 | 0.00 | 0.347383E+09 | 22488106.56 | 0.148538E+10 |
March | 0.532222E+09 | 0.00 | 0.532222E+09 | 0.121346E+09 | 0.137720E+10 |
April | 0.838586E+09 | 3753159.90 | 0.834833E+09 | 0.474803E+09 | 0.104935E+10 |
May | 0.108339E+10 | 52268564.87 | 0.103113E+10 | 0.639039E+09 | 0.842910E+09 |
June | 0.115899E+10 | 72676274.49 | 0.108632E+10 | 0.918659E+09 | 0.640012E+09 |
July | 0.113601E+10 | 64770054.73 | 0.107124E+10 | 0.958049E+09 | 0.614948E+09 |
August | 0.892964E+09 | 13990527.09 | 0.878973E+09 | 0.732720E+09 | 0.692961E+09 |
September | 0.657743E+09 | 145545.35 | 0.657598E+09 | 0.455041E+09 | 0.886361E+09 |
October | 0.435526E+09 | 0.00 | 0.435526E+09 | 0.137189E+09 | 0.127616E+10 |
November | 0.253245E+09 | 0.00 | 0.253245E+09 | 10009083.44 | 0.155535E+10 |
December | 0.178208E+09 | 0.00 | 0.178208E+09 | 0.00 | 0.194018E+10 |
Annual Sum or Average | 0.776057E+10 | 0.207604E+09 | 0.755297E+10 | 0.447557E+10 | 0.141215E+11 |
Minimum of Months | 0.178208E+09 | 0.00 | 0.178208E+09 | 0.00 | 0.614948E+09 |
Maximum of Months | 0.115899E+10 | 72676274.49 | 0.108632E+10 | 0.958049E+09 | 0.194018E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246296E+09 | 0.00 | 0.246296E+09 | 6223913.14 | 0.176064E+10 |
February | 0.347382E+09 | 0.00 | 0.347382E+09 | 22487984.05 | 0.148538E+10 |
March | 0.532221E+09 | 0.00 | 0.532221E+09 | 0.121346E+09 | 0.137720E+10 |
April | 0.838585E+09 | 3753155.39 | 0.834832E+09 | 0.474802E+09 | 0.104935E+10 |
May | 0.108339E+10 | 52268502.15 | 0.103113E+10 | 0.639038E+09 | 0.842910E+09 |
June | 0.115899E+10 | 72676187.28 | 0.108631E+10 | 0.918658E+09 | 0.640012E+09 |
July | 0.113601E+10 | 64769977.01 | 0.107124E+10 | 0.958048E+09 | 0.614948E+09 |
August | 0.892963E+09 | 13990510.31 | 0.878972E+09 | 0.732720E+09 | 0.692961E+09 |
September | 0.657743E+09 | 145545.18 | 0.657597E+09 | 0.455041E+09 | 0.886361E+09 |
October | 0.435526E+09 | 0.00 | 0.435526E+09 | 0.137189E+09 | 0.127616E+10 |
November | 0.253245E+09 | 0.00 | 0.253245E+09 | 10009022.50 | 0.155535E+10 |
December | 0.178208E+09 | 0.00 | 0.178208E+09 | 0.00 | 0.194018E+10 |
Annual Sum or Average | 0.776057E+10 | 0.207604E+09 | 0.755296E+10 | 0.447556E+10 | 0.141215E+11 |
Minimum of Months | 0.178208E+09 | 0.00 | 0.178208E+09 | 0.00 | 0.614948E+09 |
Maximum of Months | 0.115899E+10 | 72676187.28 | 0.108631E+10 | 0.958048E+09 | 0.194018E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246297E+09 | 0.00 | 0.246297E+09 | 6223954.22 | 0.176064E+10 |
February | 0.347383E+09 | 0.00 | 0.347383E+09 | 22488106.56 | 0.148538E+10 |
March | 0.532222E+09 | 0.00 | 0.532222E+09 | 0.121346E+09 | 0.137720E+10 |
April | 0.838586E+09 | 3753159.90 | 0.834833E+09 | 0.474803E+09 | 0.104935E+10 |
May | 0.108339E+10 | 52268564.87 | 0.103113E+10 | 0.639039E+09 | 0.842910E+09 |
June | 0.115899E+10 | 72676274.49 | 0.108632E+10 | 0.918659E+09 | 0.640012E+09 |
July | 0.113601E+10 | 64770054.73 | 0.107124E+10 | 0.958049E+09 | 0.614948E+09 |
August | 0.892964E+09 | 13990527.09 | 0.878973E+09 | 0.732720E+09 | 0.692961E+09 |
September | 0.657743E+09 | 145545.35 | 0.657598E+09 | 0.455041E+09 | 0.886361E+09 |
October | 0.435526E+09 | 0.00 | 0.435526E+09 | 0.137189E+09 | 0.127616E+10 |
November | 0.253245E+09 | 0.00 | 0.253245E+09 | 10009083.44 | 0.155535E+10 |
December | 0.178208E+09 | 0.00 | 0.178208E+09 | 0.00 | 0.194018E+10 |
Annual Sum or Average | 0.776057E+10 | 0.207604E+09 | 0.755297E+10 | 0.447557E+10 | 0.141215E+11 |
Minimum of Months | 0.178208E+09 | 0.00 | 0.178208E+09 | 0.00 | 0.614948E+09 |
Maximum of Months | 0.115899E+10 | 72676274.49 | 0.108632E+10 | 0.958049E+09 | 0.194018E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246296E+09 | 0.00 | 0.246296E+09 | 6223913.14 | 0.176064E+10 |
February | 0.347382E+09 | 0.00 | 0.347382E+09 | 22487984.05 | 0.148538E+10 |
March | 0.532221E+09 | 0.00 | 0.532221E+09 | 0.121346E+09 | 0.137720E+10 |
April | 0.838585E+09 | 3753155.39 | 0.834832E+09 | 0.474802E+09 | 0.104935E+10 |
May | 0.108339E+10 | 52268502.15 | 0.103113E+10 | 0.639038E+09 | 0.842910E+09 |
June | 0.115899E+10 | 72676187.28 | 0.108631E+10 | 0.918658E+09 | 0.640012E+09 |
July | 0.113601E+10 | 64769977.01 | 0.107124E+10 | 0.958048E+09 | 0.614948E+09 |
August | 0.892963E+09 | 13990510.31 | 0.878972E+09 | 0.732720E+09 | 0.692961E+09 |
September | 0.657743E+09 | 145545.18 | 0.657597E+09 | 0.455041E+09 | 0.886361E+09 |
October | 0.435526E+09 | 0.00 | 0.435526E+09 | 0.137189E+09 | 0.127616E+10 |
November | 0.253245E+09 | 0.00 | 0.253245E+09 | 10009022.50 | 0.155535E+10 |
December | 0.178208E+09 | 0.00 | 0.178208E+09 | 0.00 | 0.194018E+10 |
Annual Sum or Average | 0.776057E+10 | 0.207604E+09 | 0.755296E+10 | 0.447556E+10 | 0.141215E+11 |
Minimum of Months | 0.178208E+09 | 0.00 | 0.178208E+09 | 0.00 | 0.614948E+09 |
Maximum of Months | 0.115899E+10 | 72676187.28 | 0.108631E+10 | 0.958048E+09 | 0.194018E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246287E+09 | 0.00 | 0.246287E+09 | 6223703.37 | 0.176057E+10 |
February | 0.347369E+09 | 0.00 | 0.347369E+09 | 22487200.19 | 0.148532E+10 |
March | 0.532200E+09 | 0.00 | 0.532200E+09 | 0.121341E+09 | 0.137714E+10 |
April | 0.838552E+09 | 3753008.63 | 0.834799E+09 | 0.474784E+09 | 0.104931E+10 |
May | 0.108335E+10 | 52266458.21 | 0.103108E+10 | 0.639013E+09 | 0.842876E+09 |
June | 0.115894E+10 | 72673345.31 | 0.108627E+10 | 0.918622E+09 | 0.639986E+09 |
July | 0.113597E+10 | 64767444.21 | 0.107120E+10 | 0.958010E+09 | 0.614924E+09 |
August | 0.892928E+09 | 13989963.21 | 0.878938E+09 | 0.732691E+09 | 0.692933E+09 |
September | 0.657717E+09 | 145539.49 | 0.657571E+09 | 0.455023E+09 | 0.886325E+09 |
October | 0.435509E+09 | 0.00 | 0.435509E+09 | 0.137184E+09 | 0.127611E+10 |
November | 0.253235E+09 | 0.00 | 0.253235E+09 | 10008680.03 | 0.155529E+10 |
December | 0.178201E+09 | 0.00 | 0.178201E+09 | 0.00 | 0.194010E+10 |
Annual Sum or Average | 0.776026E+10 | 0.207596E+09 | 0.755266E+10 | 0.447539E+10 | 0.141209E+11 |
Minimum of Months | 0.178201E+09 | 0.00 | 0.178201E+09 | 0.00 | 0.614924E+09 |
Maximum of Months | 0.115894E+10 | 72673345.31 | 0.108627E+10 | 0.958010E+09 | 0.194010E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.559353E+09 | 0.224693E+09 | 0.334660E+09 | 0.291032E+09 | 0.179390E+10 |
February | 0.753373E+09 | 0.278302E+09 | 0.475072E+09 | 0.445349E+09 | 0.151448E+10 |
March | 0.871644E+09 | 0.171769E+09 | 0.699875E+09 | 0.466918E+09 | 0.139281E+10 |
April | 0.226494E+10 | 0.106431E+10 | 0.120063E+10 | 0.230472E+10 | 0.106795E+10 |
May | 0.246090E+10 | 0.107315E+10 | 0.138774E+10 | 0.244191E+10 | 0.944301E+09 |
June | 0.235726E+10 | 0.941467E+09 | 0.141579E+10 | 0.250791E+10 | 0.711244E+09 |
July | 0.248651E+10 | 0.105677E+10 | 0.142974E+10 | 0.276583E+10 | 0.678926E+09 |
August | 0.235542E+10 | 0.112540E+10 | 0.123002E+10 | 0.270180E+10 | 0.733173E+09 |
September | 0.205271E+10 | 0.109154E+10 | 0.961175E+09 | 0.226724E+10 | 0.917950E+09 |
October | 0.102390E+10 | 0.424331E+09 | 0.599570E+09 | 0.856261E+09 | 0.131996E+10 |
November | 0.516571E+09 | 0.176055E+09 | 0.340516E+09 | 0.265752E+09 | 0.157382E+10 |
December | 0.395604E+09 | 0.147080E+09 | 0.248524E+09 | 0.175046E+09 | 0.195584E+10 |
Annual Sum or Average | 0.180982E+11 | 0.777486E+10 | 0.103233E+11 | 0.174898E+11 | 0.146043E+11 |
Minimum of Months | 0.395604E+09 | 0.147080E+09 | 0.248524E+09 | 0.175046E+09 | 0.678926E+09 |
Maximum of Months | 0.248651E+10 | 0.112540E+10 | 0.142974E+10 | 0.276583E+10 | 0.195584E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.559353E+09 | 0.224693E+09 | 0.334660E+09 | 0.291032E+09 | 0.179390E+10 |
February | 0.753373E+09 | 0.278302E+09 | 0.475072E+09 | 0.445349E+09 | 0.151448E+10 |
March | 0.871644E+09 | 0.171769E+09 | 0.699875E+09 | 0.466918E+09 | 0.139281E+10 |
April | 0.226494E+10 | 0.106431E+10 | 0.120063E+10 | 0.230472E+10 | 0.106795E+10 |
May | 0.246090E+10 | 0.107315E+10 | 0.138774E+10 | 0.244191E+10 | 0.944301E+09 |
June | 0.235726E+10 | 0.941467E+09 | 0.141579E+10 | 0.250791E+10 | 0.711244E+09 |
July | 0.248651E+10 | 0.105677E+10 | 0.142974E+10 | 0.276583E+10 | 0.678926E+09 |
August | 0.235542E+10 | 0.112540E+10 | 0.123002E+10 | 0.270180E+10 | 0.733173E+09 |
September | 0.205271E+10 | 0.109154E+10 | 0.961175E+09 | 0.226724E+10 | 0.917950E+09 |
October | 0.102390E+10 | 0.424331E+09 | 0.599570E+09 | 0.856261E+09 | 0.131996E+10 |
November | 0.516571E+09 | 0.176055E+09 | 0.340516E+09 | 0.265752E+09 | 0.157382E+10 |
December | 0.395604E+09 | 0.147080E+09 | 0.248524E+09 | 0.175046E+09 | 0.195584E+10 |
Annual Sum or Average | 0.180982E+11 | 0.777486E+10 | 0.103233E+11 | 0.174898E+11 | 0.146043E+11 |
Minimum of Months | 0.395604E+09 | 0.147080E+09 | 0.248524E+09 | 0.175046E+09 | 0.678926E+09 |
Maximum of Months | 0.248651E+10 | 0.112540E+10 | 0.142974E+10 | 0.276583E+10 | 0.195584E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.559342E+09 | 0.224689E+09 | 0.334654E+09 | 0.291027E+09 | 0.179387E+10 |
February | 0.753360E+09 | 0.278297E+09 | 0.475063E+09 | 0.445341E+09 | 0.151445E+10 |
March | 0.871628E+09 | 0.171766E+09 | 0.699862E+09 | 0.466910E+09 | 0.139278E+10 |
April | 0.226490E+10 | 0.106429E+10 | 0.120061E+10 | 0.230468E+10 | 0.106793E+10 |
May | 0.246085E+10 | 0.107313E+10 | 0.138772E+10 | 0.244187E+10 | 0.944284E+09 |
June | 0.235722E+10 | 0.941450E+09 | 0.141577E+10 | 0.250786E+10 | 0.711231E+09 |
July | 0.248646E+10 | 0.105675E+10 | 0.142972E+10 | 0.276578E+10 | 0.678914E+09 |
August | 0.235538E+10 | 0.112538E+10 | 0.123000E+10 | 0.270175E+10 | 0.733160E+09 |
September | 0.205268E+10 | 0.109152E+10 | 0.961157E+09 | 0.226719E+10 | 0.917933E+09 |
October | 0.102388E+10 | 0.424323E+09 | 0.599559E+09 | 0.856245E+09 | 0.131993E+10 |
November | 0.516562E+09 | 0.176052E+09 | 0.340510E+09 | 0.265747E+09 | 0.157379E+10 |
December | 0.395596E+09 | 0.147077E+09 | 0.248519E+09 | 0.175043E+09 | 0.195580E+10 |
Annual Sum or Average | 0.180979E+11 | 0.777472E+10 | 0.103231E+11 | 0.174894E+11 | 0.146041E+11 |
Minimum of Months | 0.395596E+09 | 0.147077E+09 | 0.248519E+09 | 0.175043E+09 | 0.678914E+09 |
Maximum of Months | 0.248646E+10 | 0.112538E+10 | 0.142972E+10 | 0.276578E+10 | 0.195580E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139830E+10 | 0.905180E+09 | 0.493125E+09 | 0.133823E+10 | 0.149668E+10 |
February | 0.154250E+10 | 0.941257E+09 | 0.601247E+09 | 0.152201E+10 | 0.132545E+10 |
March | 0.105586E+10 | 0.307418E+09 | 0.748439E+09 | 0.803206E+09 | 0.125469E+10 |
April | 0.212185E+10 | 0.959049E+09 | 0.116280E+10 | 0.236465E+10 | 0.105069E+10 |
May | 0.181346E+10 | 0.590404E+09 | 0.122306E+10 | 0.186537E+10 | 0.923866E+09 |
June | 0.161670E+10 | 0.391335E+09 | 0.122536E+10 | 0.173295E+10 | 0.694744E+09 |
July | 0.181005E+10 | 0.566837E+09 | 0.124321E+10 | 0.209422E+10 | 0.671325E+09 |
August | 0.212098E+10 | 0.954095E+09 | 0.116688E+10 | 0.260902E+10 | 0.731452E+09 |
September | 0.242559E+10 | 0.142095E+10 | 0.100464E+10 | 0.296357E+10 | 0.885045E+09 |
October | 0.172203E+10 | 0.100645E+10 | 0.715581E+09 | 0.185840E+10 | 0.119089E+10 |
November | 0.118153E+10 | 0.718758E+09 | 0.462777E+09 | 0.113720E+10 | 0.137725E+10 |
December | 0.967691E+09 | 0.620004E+09 | 0.347687E+09 | 0.892727E+09 | 0.170363E+10 |
Annual Sum or Average | 0.197765E+11 | 0.938174E+10 | 0.103948E+11 | 0.211815E+11 | 0.133057E+11 |
Minimum of Months | 0.967691E+09 | 0.307418E+09 | 0.347687E+09 | 0.803206E+09 | 0.671325E+09 |
Maximum of Months | 0.242559E+10 | 0.142095E+10 | 0.124321E+10 | 0.296357E+10 | 0.170363E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139830E+10 | 0.905179E+09 | 0.493124E+09 | 0.133823E+10 | 0.149668E+10 |
February | 0.154250E+10 | 0.941256E+09 | 0.601246E+09 | 0.152200E+10 | 0.132545E+10 |
March | 0.105586E+10 | 0.307418E+09 | 0.748438E+09 | 0.803205E+09 | 0.125469E+10 |
April | 0.212184E+10 | 0.959048E+09 | 0.116280E+10 | 0.236465E+10 | 0.105069E+10 |
May | 0.181346E+10 | 0.590403E+09 | 0.122306E+10 | 0.186536E+10 | 0.923866E+09 |
June | 0.161669E+10 | 0.391334E+09 | 0.122536E+10 | 0.173295E+10 | 0.694744E+09 |
July | 0.181005E+10 | 0.566836E+09 | 0.124321E+10 | 0.209422E+10 | 0.671325E+09 |
August | 0.212098E+10 | 0.954094E+09 | 0.116688E+10 | 0.260902E+10 | 0.731452E+09 |
September | 0.242559E+10 | 0.142095E+10 | 0.100464E+10 | 0.296356E+10 | 0.885045E+09 |
October | 0.172203E+10 | 0.100645E+10 | 0.715581E+09 | 0.185840E+10 | 0.119089E+10 |
November | 0.118153E+10 | 0.718757E+09 | 0.462777E+09 | 0.113720E+10 | 0.137725E+10 |
December | 0.967689E+09 | 0.620003E+09 | 0.347686E+09 | 0.892726E+09 | 0.170363E+10 |
Annual Sum or Average | 0.197765E+11 | 0.938173E+10 | 0.103948E+11 | 0.211815E+11 | 0.133057E+11 |
Minimum of Months | 0.967689E+09 | 0.307418E+09 | 0.347686E+09 | 0.803205E+09 | 0.671325E+09 |
Maximum of Months | 0.242559E+10 | 0.142095E+10 | 0.124321E+10 | 0.296356E+10 | 0.170363E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139830E+10 | 0.905180E+09 | 0.493125E+09 | 0.133823E+10 | 0.149668E+10 |
February | 0.154250E+10 | 0.941257E+09 | 0.601247E+09 | 0.152201E+10 | 0.132545E+10 |
March | 0.105586E+10 | 0.307418E+09 | 0.748439E+09 | 0.803206E+09 | 0.125469E+10 |
April | 0.212185E+10 | 0.959049E+09 | 0.116280E+10 | 0.236465E+10 | 0.105069E+10 |
May | 0.181346E+10 | 0.590404E+09 | 0.122306E+10 | 0.186537E+10 | 0.923866E+09 |
June | 0.161670E+10 | 0.391335E+09 | 0.122536E+10 | 0.173295E+10 | 0.694744E+09 |
July | 0.181005E+10 | 0.566837E+09 | 0.124321E+10 | 0.209422E+10 | 0.671325E+09 |
August | 0.212098E+10 | 0.954095E+09 | 0.116688E+10 | 0.260902E+10 | 0.731452E+09 |
September | 0.242559E+10 | 0.142095E+10 | 0.100464E+10 | 0.296357E+10 | 0.885045E+09 |
October | 0.172203E+10 | 0.100645E+10 | 0.715581E+09 | 0.185840E+10 | 0.119089E+10 |
November | 0.118153E+10 | 0.718758E+09 | 0.462777E+09 | 0.113720E+10 | 0.137725E+10 |
December | 0.967691E+09 | 0.620004E+09 | 0.347687E+09 | 0.892727E+09 | 0.170363E+10 |
Annual Sum or Average | 0.197765E+11 | 0.938174E+10 | 0.103948E+11 | 0.211815E+11 | 0.133057E+11 |
Minimum of Months | 0.967691E+09 | 0.307418E+09 | 0.347687E+09 | 0.803206E+09 | 0.671325E+09 |
Maximum of Months | 0.242559E+10 | 0.142095E+10 | 0.124321E+10 | 0.296357E+10 | 0.170363E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139830E+10 | 0.905179E+09 | 0.493124E+09 | 0.133823E+10 | 0.149668E+10 |
February | 0.154250E+10 | 0.941256E+09 | 0.601246E+09 | 0.152200E+10 | 0.132545E+10 |
March | 0.105586E+10 | 0.307418E+09 | 0.748438E+09 | 0.803205E+09 | 0.125469E+10 |
April | 0.212184E+10 | 0.959048E+09 | 0.116280E+10 | 0.236465E+10 | 0.105069E+10 |
May | 0.181346E+10 | 0.590403E+09 | 0.122306E+10 | 0.186536E+10 | 0.923866E+09 |
June | 0.161669E+10 | 0.391334E+09 | 0.122536E+10 | 0.173295E+10 | 0.694744E+09 |
July | 0.181005E+10 | 0.566836E+09 | 0.124321E+10 | 0.209422E+10 | 0.671325E+09 |
August | 0.212098E+10 | 0.954094E+09 | 0.116688E+10 | 0.260902E+10 | 0.731452E+09 |
September | 0.242559E+10 | 0.142095E+10 | 0.100464E+10 | 0.296356E+10 | 0.885045E+09 |
October | 0.172203E+10 | 0.100645E+10 | 0.715581E+09 | 0.185840E+10 | 0.119089E+10 |
November | 0.118153E+10 | 0.718757E+09 | 0.462777E+09 | 0.113720E+10 | 0.137725E+10 |
December | 0.967689E+09 | 0.620003E+09 | 0.347686E+09 | 0.892726E+09 | 0.170363E+10 |
Annual Sum or Average | 0.197765E+11 | 0.938173E+10 | 0.103948E+11 | 0.211815E+11 | 0.133057E+11 |
Minimum of Months | 0.967689E+09 | 0.307418E+09 | 0.347686E+09 | 0.803205E+09 | 0.671325E+09 |
Maximum of Months | 0.242559E+10 | 0.142095E+10 | 0.124321E+10 | 0.296356E+10 | 0.170363E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.139825E+10 | 0.905144E+09 | 0.493105E+09 | 0.133818E+10 | 0.149662E+10 |
February | 0.154244E+10 | 0.941219E+09 | 0.601223E+09 | 0.152195E+10 | 0.132539E+10 |
March | 0.105581E+10 | 0.307406E+09 | 0.748409E+09 | 0.803174E+09 | 0.125464E+10 |
April | 0.212176E+10 | 0.959011E+09 | 0.116275E+10 | 0.236455E+10 | 0.105065E+10 |
May | 0.181339E+10 | 0.590380E+09 | 0.122301E+10 | 0.186529E+10 | 0.923829E+09 |
June | 0.161663E+10 | 0.391319E+09 | 0.122531E+10 | 0.173288E+10 | 0.694716E+09 |
July | 0.180998E+10 | 0.566814E+09 | 0.124316E+10 | 0.209413E+10 | 0.671298E+09 |
August | 0.212089E+10 | 0.954057E+09 | 0.116684E+10 | 0.260891E+10 | 0.731422E+09 |
September | 0.242549E+10 | 0.142089E+10 | 0.100460E+10 | 0.296345E+10 | 0.885009E+09 |
October | 0.172196E+10 | 0.100641E+10 | 0.715552E+09 | 0.185832E+10 | 0.119084E+10 |
November | 0.118149E+10 | 0.718729E+09 | 0.462758E+09 | 0.113716E+10 | 0.137719E+10 |
December | 0.967652E+09 | 0.619979E+09 | 0.347673E+09 | 0.892691E+09 | 0.170356E+10 |
Annual Sum or Average | 0.197757E+11 | 0.938136E+10 | 0.103944E+11 | 0.211807E+11 | 0.133052E+11 |
Minimum of Months | 0.967652E+09 | 0.307406E+09 | 0.347673E+09 | 0.803174E+09 | 0.671298E+09 |
Maximum of Months | 0.242549E+10 | 0.142089E+10 | 0.124316E+10 | 0.296345E+10 | 0.170356E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.543943E+09 | 0.179721E+09 | 0.364222E+09 | 0.283393E+09 | 0.192030E+10 |
February | 0.869877E+09 | 0.367290E+09 | 0.502587E+09 | 0.622382E+09 | 0.170031E+10 |
March | 0.870829E+09 | 0.166590E+09 | 0.704240E+09 | 0.426462E+09 | 0.160662E+10 |
April | 0.198847E+10 | 0.789837E+09 | 0.119863E+10 | 0.191685E+10 | 0.129152E+10 |
May | 0.241070E+10 | 0.980273E+09 | 0.143043E+10 | 0.236627E+10 | 0.106396E+10 |
June | 0.251932E+10 | 0.103711E+10 | 0.148221E+10 | 0.268642E+10 | 0.837630E+09 |
July | 0.265134E+10 | 0.116898E+10 | 0.148236E+10 | 0.294456E+10 | 0.828214E+09 |
August | 0.222695E+10 | 0.964207E+09 | 0.126274E+10 | 0.248701E+10 | 0.918113E+09 |
September | 0.172897E+10 | 0.775311E+09 | 0.953663E+09 | 0.186392E+10 | 0.104840E+10 |
October | 0.953085E+09 | 0.342725E+09 | 0.610360E+09 | 0.758841E+09 | 0.150229E+10 |
November | 0.499139E+09 | 0.145705E+09 | 0.353434E+09 | 0.254614E+09 | 0.183575E+10 |
December | 0.291945E+09 | 61606739.49 | 0.230338E+09 | 79326490.79 | 0.233424E+10 |
Annual Sum or Average | 0.175546E+11 | 0.697936E+10 | 0.105752E+11 | 0.166901E+11 | 0.168873E+11 |
Minimum of Months | 0.291945E+09 | 61606739.49 | 0.230338E+09 | 79326490.79 | 0.828214E+09 |
Maximum of Months | 0.265134E+10 | 0.116898E+10 | 0.148236E+10 | 0.294456E+10 | 0.233424E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.543943E+09 | 0.179721E+09 | 0.364222E+09 | 0.283393E+09 | 0.192030E+10 |
February | 0.869877E+09 | 0.367290E+09 | 0.502587E+09 | 0.622382E+09 | 0.170031E+10 |
March | 0.870829E+09 | 0.166590E+09 | 0.704240E+09 | 0.426462E+09 | 0.160662E+10 |
April | 0.198847E+10 | 0.789837E+09 | 0.119863E+10 | 0.191685E+10 | 0.129152E+10 |
May | 0.241070E+10 | 0.980273E+09 | 0.143043E+10 | 0.236627E+10 | 0.106396E+10 |
June | 0.251932E+10 | 0.103711E+10 | 0.148221E+10 | 0.268642E+10 | 0.837630E+09 |
July | 0.265134E+10 | 0.116898E+10 | 0.148236E+10 | 0.294456E+10 | 0.828214E+09 |
August | 0.222695E+10 | 0.964207E+09 | 0.126274E+10 | 0.248701E+10 | 0.918113E+09 |
September | 0.172897E+10 | 0.775311E+09 | 0.953663E+09 | 0.186392E+10 | 0.104840E+10 |
October | 0.953085E+09 | 0.342725E+09 | 0.610360E+09 | 0.758841E+09 | 0.150229E+10 |
November | 0.499139E+09 | 0.145705E+09 | 0.353434E+09 | 0.254614E+09 | 0.183575E+10 |
December | 0.291945E+09 | 61606739.49 | 0.230338E+09 | 79326490.79 | 0.233424E+10 |
Annual Sum or Average | 0.175546E+11 | 0.697936E+10 | 0.105752E+11 | 0.166901E+11 | 0.168873E+11 |
Minimum of Months | 0.291945E+09 | 61606739.49 | 0.230338E+09 | 79326490.79 | 0.828214E+09 |
Maximum of Months | 0.265134E+10 | 0.116898E+10 | 0.148236E+10 | 0.294456E+10 | 0.233424E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.543933E+09 | 0.179718E+09 | 0.364216E+09 | 0.283388E+09 | 0.192027E+10 |
February | 0.869861E+09 | 0.367283E+09 | 0.502578E+09 | 0.622371E+09 | 0.170028E+10 |
March | 0.870813E+09 | 0.166587E+09 | 0.704227E+09 | 0.426454E+09 | 0.160659E+10 |
April | 0.198843E+10 | 0.789823E+09 | 0.119861E+10 | 0.191681E+10 | 0.129150E+10 |
May | 0.241065E+10 | 0.980255E+09 | 0.143040E+10 | 0.236623E+10 | 0.106394E+10 |
June | 0.251927E+10 | 0.103709E+10 | 0.148218E+10 | 0.268637E+10 | 0.837615E+09 |
July | 0.265129E+10 | 0.116896E+10 | 0.148233E+10 | 0.294451E+10 | 0.828199E+09 |
August | 0.222691E+10 | 0.964190E+09 | 0.126272E+10 | 0.248697E+10 | 0.918096E+09 |
September | 0.172894E+10 | 0.775297E+09 | 0.953645E+09 | 0.186389E+10 | 0.104838E+10 |
October | 0.953068E+09 | 0.342719E+09 | 0.610349E+09 | 0.758827E+09 | 0.150226E+10 |
November | 0.499130E+09 | 0.145702E+09 | 0.353427E+09 | 0.254609E+09 | 0.183571E+10 |
December | 0.291940E+09 | 61605613.80 | 0.230334E+09 | 79325041.32 | 0.233419E+10 |
Annual Sum or Average | 0.175542E+11 | 0.697923E+10 | 0.105750E+11 | 0.166897E+11 | 0.168870E+11 |
Minimum of Months | 0.291940E+09 | 61605613.80 | 0.230334E+09 | 79325041.32 | 0.828199E+09 |
Maximum of Months | 0.265129E+10 | 0.116896E+10 | 0.148233E+10 | 0.294451E+10 | 0.233419E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.123147E+10 | 0.00 | 0.123147E+10 | 68987022.20 | 0.778628E+10 |
February | 0.173689E+10 | 0.00 | 0.173689E+10 | 0.211021E+09 | 0.657620E+10 |
March | 0.266108E+10 | 0.00 | 0.266108E+10 | 0.790226E+09 | 0.606937E+10 |
April | 0.419288E+10 | 18765572.57 | 0.417411E+10 | 0.252729E+10 | 0.479104E+10 |
May | 0.541691E+10 | 0.261340E+09 | 0.515557E+10 | 0.331259E+10 | 0.397726E+10 |
June | 0.579489E+10 | 0.363377E+09 | 0.543151E+10 | 0.465271E+10 | 0.304738E+10 |
July | 0.567999E+10 | 0.323846E+09 | 0.535614E+10 | 0.491081E+10 | 0.289172E+10 |
August | 0.446476E+10 | 69951789.61 | 0.439481E+10 | 0.378183E+10 | 0.322068E+10 |
September | 0.328868E+10 | 727717.97 | 0.328795E+10 | 0.238255E+10 | 0.413956E+10 |
October | 0.217761E+10 | 0.00 | 0.217761E+10 | 0.834451E+09 | 0.566955E+10 |
November | 0.126621E+10 | 0.00 | 0.126621E+10 | 0.110084E+09 | 0.667622E+10 |
December | 0.891029E+09 | 0.00 | 0.891029E+09 | 2945367.77 | 0.830374E+10 |
Annual Sum or Average | 0.388024E+11 | 0.103801E+10 | 0.377644E+11 | 0.235855E+11 | 0.631490E+11 |
Minimum of Months | 0.891029E+09 | 0.00 | 0.891029E+09 | 2945367.77 | 0.289172E+10 |
Maximum of Months | 0.579489E+10 | 0.363377E+09 | 0.543151E+10 | 0.491081E+10 | 0.830374E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.167804E+10 | 0.674072E+09 | 0.100397E+10 | 0.941244E+09 | 0.487955E+10 |
February | 0.226010E+10 | 0.834897E+09 | 0.142520E+10 | 0.140894E+10 | 0.416684E+10 |
March | 0.261491E+10 | 0.515302E+09 | 0.209960E+10 | 0.151929E+10 | 0.381786E+10 |
April | 0.679475E+10 | 0.319290E+10 | 0.360185E+10 | 0.691621E+10 | 0.306101E+10 |
May | 0.738261E+10 | 0.321943E+10 | 0.416318E+10 | 0.731217E+10 | 0.271702E+10 |
June | 0.707171E+10 | 0.282437E+10 | 0.424734E+10 | 0.749632E+10 | 0.206636E+10 |
July | 0.745945E+10 | 0.317026E+10 | 0.428918E+10 | 0.827019E+10 | 0.197463E+10 |
August | 0.706620E+10 | 0.337616E+10 | 0.369003E+10 | 0.808364E+10 | 0.214072E+10 |
September | 0.615808E+10 | 0.327459E+10 | 0.288349E+10 | 0.679432E+10 | 0.264057E+10 |
October | 0.307167E+10 | 0.127298E+10 | 0.179869E+10 | 0.263435E+10 | 0.363013E+10 |
November | 0.154970E+10 | 0.528159E+09 | 0.102154E+10 | 0.858960E+09 | 0.422131E+10 |
December | 0.118680E+10 | 0.441235E+09 | 0.745563E+09 | 0.580398E+09 | 0.526655E+10 |
Annual Sum or Average | 0.542940E+11 | 0.233244E+11 | 0.309697E+11 | 0.528160E+11 | 0.405825E+11 |
Minimum of Months | 0.118680E+10 | 0.441235E+09 | 0.745563E+09 | 0.580398E+09 | 0.197463E+10 |
Maximum of Months | 0.745945E+10 | 0.337616E+10 | 0.428918E+10 | 0.827019E+10 | 0.526655E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.699144E+10 | 0.452585E+10 | 0.246559E+10 | 0.672047E+10 | 0.719888E+10 |
February | 0.771243E+10 | 0.470623E+10 | 0.300620E+10 | 0.762369E+10 | 0.639942E+10 |
March | 0.527922E+10 | 0.153707E+10 | 0.374215E+10 | 0.409859E+10 | 0.591638E+10 |
April | 0.106091E+11 | 0.479519E+10 | 0.581391E+10 | 0.118099E+11 | 0.506267E+10 |
May | 0.906720E+10 | 0.295199E+10 | 0.611522E+10 | 0.930494E+10 | 0.450618E+10 |
June | 0.808338E+10 | 0.195665E+10 | 0.612673E+10 | 0.866167E+10 | 0.336771E+10 |
July | 0.905013E+10 | 0.283415E+10 | 0.621598E+10 | 0.104812E+11 | 0.323582E+10 |
August | 0.106048E+11 | 0.477042E+10 | 0.583435E+10 | 0.130315E+11 | 0.353682E+10 |
September | 0.121278E+11 | 0.710467E+10 | 0.502314E+10 | 0.147516E+11 | 0.435281E+10 |
October | 0.861005E+10 | 0.503219E+10 | 0.357786E+10 | 0.929444E+10 | 0.571090E+10 |
November | 0.590760E+10 | 0.359374E+10 | 0.231386E+10 | 0.572246E+10 | 0.647684E+10 |
December | 0.483839E+10 | 0.309998E+10 | 0.173841E+10 | 0.453163E+10 | 0.796411E+10 |
Annual Sum or Average | 0.988815E+11 | 0.469081E+11 | 0.519734E+11 | 0.106032E+12 | 0.637285E+11 |
Minimum of Months | 0.483839E+10 | 0.153707E+10 | 0.173841E+10 | 0.409859E+10 | 0.323582E+10 |
Maximum of Months | 0.121278E+11 | 0.710467E+10 | 0.621598E+10 | 0.147516E+11 | 0.796411E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163181E+10 | 0.539158E+09 | 0.109266E+10 | 0.931711E+09 | 0.507468E+10 |
February | 0.260960E+10 | 0.110186E+10 | 0.150775E+10 | 0.198727E+10 | 0.440708E+10 |
March | 0.261246E+10 | 0.499764E+09 | 0.211270E+10 | 0.149377E+10 | 0.398361E+10 |
April | 0.596535E+10 | 0.236949E+10 | 0.359586E+10 | 0.595328E+10 | 0.334955E+10 |
May | 0.723202E+10 | 0.294079E+10 | 0.429123E+10 | 0.718587E+10 | 0.297704E+10 |
June | 0.755788E+10 | 0.311129E+10 | 0.444659E+10 | 0.813706E+10 | 0.229838E+10 |
July | 0.795394E+10 | 0.350692E+10 | 0.444703E+10 | 0.896528E+10 | 0.222030E+10 |
August | 0.668078E+10 | 0.289259E+10 | 0.378819E+10 | 0.760935E+10 | 0.240834E+10 |
September | 0.518687E+10 | 0.232591E+10 | 0.286096E+10 | 0.568288E+10 | 0.289619E+10 |
October | 0.285923E+10 | 0.102817E+10 | 0.183106E+10 | 0.242837E+10 | 0.384502E+10 |
November | 0.149740E+10 | 0.437110E+09 | 0.106029E+10 | 0.870058E+09 | 0.446961E+10 |
December | 0.875826E+09 | 0.184818E+09 | 0.691007E+09 | 0.298356E+09 | 0.560799E+10 |
Annual Sum or Average | 0.526632E+11 | 0.209379E+11 | 0.317253E+11 | 0.515432E+11 | 0.435378E+11 |
Minimum of Months | 0.875826E+09 | 0.184818E+09 | 0.691007E+09 | 0.298356E+09 | 0.222030E+10 |
Maximum of Months | 0.795394E+10 | 0.350692E+10 | 0.444703E+10 | 0.896528E+10 | 0.560799E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.123147E+10 | 0.00 | 0.123147E+10 | 0.114534E+09 | 0.706460E+10 |
February | 0.173689E+10 | 0.00 | 0.173689E+10 | 0.306991E+09 | 0.598256E+10 |
March | 0.266108E+10 | 0.00 | 0.266108E+10 | 0.932530E+09 | 0.554765E+10 |
April | 0.419288E+10 | 18765572.57 | 0.417411E+10 | 0.264163E+10 | 0.448926E+10 |
May | 0.541691E+10 | 0.261340E+09 | 0.515557E+10 | 0.345501E+10 | 0.374635E+10 |
June | 0.579489E+10 | 0.363377E+09 | 0.543151E+10 | 0.470088E+10 | 0.293655E+10 |
July | 0.567999E+10 | 0.323846E+09 | 0.535614E+10 | 0.494561E+10 | 0.280074E+10 |
August | 0.446476E+10 | 69951789.61 | 0.439481E+10 | 0.381868E+10 | 0.310223E+10 |
September | 0.328868E+10 | 727717.97 | 0.328795E+10 | 0.247847E+10 | 0.388874E+10 |
October | 0.217761E+10 | 0.00 | 0.217761E+10 | 0.976842E+09 | 0.510088E+10 |
November | 0.126621E+10 | 0.00 | 0.126621E+10 | 0.168139E+09 | 0.599734E+10 |
December | 0.891029E+09 | 0.00 | 0.891029E+09 | 19872596.64 | 0.758677E+10 |
Annual Sum or Average | 0.388024E+11 | 0.103801E+10 | 0.377644E+11 | 0.245592E+11 | 0.582437E+11 |
Minimum of Months | 0.891029E+09 | 0.00 | 0.891029E+09 | 19872596.64 | 0.280074E+10 |
Maximum of Months | 0.579489E+10 | 0.363377E+09 | 0.543151E+10 | 0.494561E+10 | 0.758677E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.167804E+10 | 0.674072E+09 | 0.100397E+10 | 0.100746E+10 | 0.444869E+10 |
February | 0.226010E+10 | 0.834897E+09 | 0.142520E+10 | 0.149795E+10 | 0.381987E+10 |
March | 0.261491E+10 | 0.515302E+09 | 0.209960E+10 | 0.162032E+10 | 0.352549E+10 |
April | 0.679475E+10 | 0.319290E+10 | 0.360185E+10 | 0.697001E+10 | 0.291064E+10 |
May | 0.738261E+10 | 0.321943E+10 | 0.416318E+10 | 0.736538E+10 | 0.259389E+10 |
June | 0.707171E+10 | 0.282437E+10 | 0.424734E+10 | 0.750759E+10 | 0.200785E+10 |
July | 0.745945E+10 | 0.317026E+10 | 0.428918E+10 | 0.826773E+10 | 0.192986E+10 |
August | 0.706620E+10 | 0.337616E+10 | 0.369003E+10 | 0.808520E+10 | 0.208590E+10 |
September | 0.615808E+10 | 0.327459E+10 | 0.288349E+10 | 0.683305E+10 | 0.252159E+10 |
October | 0.307167E+10 | 0.127298E+10 | 0.179869E+10 | 0.272383E+10 | 0.331696E+10 |
November | 0.154970E+10 | 0.528159E+09 | 0.102154E+10 | 0.920413E+09 | 0.383207E+10 |
December | 0.118680E+10 | 0.441235E+09 | 0.745563E+09 | 0.625927E+09 | 0.483488E+10 |
Annual Sum or Average | 0.542940E+11 | 0.233244E+11 | 0.309697E+11 | 0.534249E+11 | 0.378277E+11 |
Minimum of Months | 0.118680E+10 | 0.441235E+09 | 0.745563E+09 | 0.625927E+09 | 0.192986E+10 |
Maximum of Months | 0.745945E+10 | 0.337616E+10 | 0.428918E+10 | 0.826773E+10 | 0.483488E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.699144E+10 | 0.452585E+10 | 0.246559E+10 | 0.688241E+10 | 0.655744E+10 |
February | 0.771243E+10 | 0.470623E+10 | 0.300620E+10 | 0.777265E+10 | 0.588013E+10 |
March | 0.527922E+10 | 0.153707E+10 | 0.374215E+10 | 0.425762E+10 | 0.544452E+10 |
April | 0.106091E+11 | 0.479519E+10 | 0.581391E+10 | 0.118790E+11 | 0.480139E+10 |
May | 0.906720E+10 | 0.295199E+10 | 0.611522E+10 | 0.938343E+10 | 0.427116E+10 |
June | 0.808338E+10 | 0.195665E+10 | 0.612673E+10 | 0.869241E+10 | 0.324818E+10 |
July | 0.905013E+10 | 0.283415E+10 | 0.621598E+10 | 0.104932E+11 | 0.313816E+10 |
August | 0.106048E+11 | 0.477042E+10 | 0.583435E+10 | 0.130388E+11 | 0.342403E+10 |
September | 0.121278E+11 | 0.710467E+10 | 0.502314E+10 | 0.147988E+11 | 0.414416E+10 |
October | 0.861005E+10 | 0.503219E+10 | 0.357786E+10 | 0.941633E+10 | 0.522443E+10 |
November | 0.590760E+10 | 0.359374E+10 | 0.231386E+10 | 0.584061E+10 | 0.588061E+10 |
December | 0.483839E+10 | 0.309998E+10 | 0.173841E+10 | 0.464286E+10 | 0.730332E+10 |
Annual Sum or Average | 0.988815E+11 | 0.469081E+11 | 0.519734E+11 | 0.107098E+12 | 0.593175E+11 |
Minimum of Months | 0.483839E+10 | 0.153707E+10 | 0.173841E+10 | 0.425762E+10 | 0.313816E+10 |
Maximum of Months | 0.121278E+11 | 0.710467E+10 | 0.621598E+10 | 0.147988E+11 | 0.730332E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163181E+10 | 0.539158E+09 | 0.109266E+10 | 0.979128E+09 | 0.468449E+10 |
February | 0.260960E+10 | 0.110186E+10 | 0.150775E+10 | 0.204266E+10 | 0.410555E+10 |
March | 0.261246E+10 | 0.499764E+09 | 0.211270E+10 | 0.156633E+10 | 0.371819E+10 |
April | 0.596535E+10 | 0.236949E+10 | 0.359586E+10 | 0.600211E+10 | 0.318888E+10 |
May | 0.723202E+10 | 0.294079E+10 | 0.429123E+10 | 0.722988E+10 | 0.284088E+10 |
June | 0.755788E+10 | 0.311129E+10 | 0.444659E+10 | 0.814356E+10 | 0.222601E+10 |
July | 0.795394E+10 | 0.350692E+10 | 0.444703E+10 | 0.896034E+10 | 0.216089E+10 |
August | 0.668078E+10 | 0.289259E+10 | 0.378819E+10 | 0.761290E+10 | 0.233595E+10 |
September | 0.518687E+10 | 0.232591E+10 | 0.286096E+10 | 0.572232E+10 | 0.276084E+10 |
October | 0.285923E+10 | 0.102817E+10 | 0.183106E+10 | 0.249626E+10 | 0.356046E+10 |
November | 0.149740E+10 | 0.437110E+09 | 0.106029E+10 | 0.907448E+09 | 0.412714E+10 |
December | 0.875826E+09 | 0.184818E+09 | 0.691007E+09 | 0.318999E+09 | 0.522272E+10 |
Annual Sum or Average | 0.526632E+11 | 0.209379E+11 | 0.317253E+11 | 0.519820E+11 | 0.409320E+11 |
Minimum of Months | 0.875826E+09 | 0.184818E+09 | 0.691007E+09 | 0.318999E+09 | 0.216089E+10 |
Maximum of Months | 0.795394E+10 | 0.350692E+10 | 0.444703E+10 | 0.896034E+10 | 0.522272E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 11.62 | 3286.71 | 459.78 | 0.00 | 459.78 | 0.00 | 0.00 |
February | 46.48 | 3069.96 | 717.96 | 0.00 | 717.96 | 0.00 | 0.00 |
March | 226.53 | 2570.91 | 993.54 | 0.00 | 993.54 | 0.00 | 0.00 |
April | 915.89 | 2024.20 | 1617.63 | 7.24 | 1610.39 | 0.00 | 0.00 |
May | 1192.94 | 1573.52 | 2022.45 | 97.57 | 1924.88 | 0.00 | 0.00 |
June | 1772.09 | 1234.58 | 2235.69 | 140.19 | 2095.50 | 0.00 | 0.00 |
July | 1788.46 | 1147.97 | 2120.67 | 120.91 | 1999.76 | 0.00 | 0.00 |
August | 1367.82 | 1293.60 | 1666.96 | 26.12 | 1640.84 | 0.00 | 0.00 |
September | 877.77 | 1709.79 | 1268.78 | 0.28 | 1268.50 | 0.00 | 0.00 |
October | 256.10 | 2382.31 | 813.03 | 0.00 | 813.03 | 0.00 | 0.00 |
November | 19.31 | 3000.27 | 488.51 | 0.00 | 488.51 | 0.00 | 0.00 |
December | 0.00 | 3621.87 | 332.67 | 0.00 | 332.67 | 0.00 | 0.00 |
Annual Sum or Average | 709.59 | 2238.92 | 1230.42 | 32.92 | 1197.51 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 1147.97 | 332.67 | 0.00 | 332.67 | 0.00 | 0.00 |
Maximum of Months | 1788.46 | 3621.87 | 2235.69 | 140.19 | 2095.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 325.97 | 2009.29 | 626.51 | 251.67 | 374.84 | 0.00 | 0.00 |
February | 552.27 | 1878.06 | 934.24 | 345.11 | 589.12 | 0.00 | 0.00 |
March | 522.98 | 1560.04 | 976.30 | 192.39 | 783.91 | 0.00 | 0.00 |
April | 2667.49 | 1236.05 | 2621.44 | 1231.83 | 1389.61 | 0.00 | 0.00 |
May | 2735.10 | 1057.68 | 2756.36 | 1202.00 | 1554.36 | 0.00 | 0.00 |
June | 2902.65 | 823.19 | 2728.29 | 1089.65 | 1638.64 | 0.00 | 0.00 |
July | 3097.91 | 760.44 | 2785.05 | 1183.65 | 1601.40 | 0.00 | 0.00 |
August | 3026.19 | 821.20 | 2638.23 | 1260.52 | 1377.71 | 0.00 | 0.00 |
September | 2624.10 | 1062.44 | 2375.81 | 1263.35 | 1112.46 | 0.00 | 0.00 |
October | 959.07 | 1478.44 | 1146.84 | 475.28 | 671.56 | 0.00 | 0.00 |
November | 307.58 | 1821.54 | 597.88 | 203.77 | 394.11 | 0.00 | 0.00 |
December | 196.06 | 2190.66 | 443.10 | 164.74 | 278.36 | 0.00 | 0.00 |
Annual Sum or Average | 1663.78 | 1389.29 | 1721.66 | 739.61 | 982.05 | 0.00 | 0.00 |
Minimum of Months | 196.06 | 760.44 | 443.10 | 164.74 | 278.36 | 0.00 | 0.00 |
Maximum of Months | 3097.91 | 2190.66 | 2785.05 | 1263.35 | 1638.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2498.17 | 2793.96 | 2610.31 | 1689.76 | 920.55 | 0.00 | 0.00 |
February | 3145.65 | 2739.41 | 3188.02 | 1945.37 | 1242.65 | 0.00 | 0.00 |
March | 1499.40 | 2342.22 | 1971.04 | 573.88 | 1397.16 | 0.00 | 0.00 |
April | 4561.40 | 2026.78 | 4093.03 | 1850.00 | 2243.03 | 0.00 | 0.00 |
May | 3482.21 | 1724.65 | 3385.32 | 1102.15 | 2283.17 | 0.00 | 0.00 |
June | 3342.86 | 1340.16 | 3118.60 | 754.88 | 2363.72 | 0.00 | 0.00 |
July | 3909.43 | 1253.21 | 3378.94 | 1058.15 | 2320.79 | 0.00 | 0.00 |
August | 4870.44 | 1365.45 | 3959.38 | 1781.08 | 2178.30 | 0.00 | 0.00 |
September | 5716.71 | 1707.25 | 4678.96 | 2741.01 | 1937.95 | 0.00 | 0.00 |
October | 3469.20 | 2223.12 | 3214.64 | 1878.81 | 1335.83 | 0.00 | 0.00 |
November | 2193.66 | 2656.71 | 2279.18 | 1386.48 | 892.69 | 0.00 | 0.00 |
December | 1666.52 | 3180.29 | 1806.46 | 1157.40 | 649.05 | 0.00 | 0.00 |
Annual Sum or Average | 3358.28 | 2109.59 | 3135.52 | 1487.45 | 1648.07 | 0.00 | 0.00 |
Minimum of Months | 1499.40 | 1253.21 | 1806.46 | 573.88 | 649.05 | 0.00 | 0.00 |
Maximum of Months | 5716.71 | 3180.29 | 4678.96 | 2741.01 | 2363.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 317.42 | 2150.86 | 609.25 | 201.30 | 407.95 | 0.00 | 0.00 |
February | 771.80 | 2108.50 | 1078.71 | 455.47 | 623.24 | 0.00 | 0.00 |
March | 477.66 | 1799.52 | 975.39 | 186.59 | 788.79 | 0.00 | 0.00 |
April | 2218.56 | 1494.80 | 2301.45 | 914.16 | 1387.30 | 0.00 | 0.00 |
May | 2650.37 | 1191.71 | 2700.14 | 1097.97 | 1602.17 | 0.00 | 0.00 |
June | 3109.26 | 969.47 | 2915.86 | 1200.35 | 1715.51 | 0.00 | 0.00 |
July | 3298.10 | 927.65 | 2969.67 | 1309.34 | 1660.34 | 0.00 | 0.00 |
August | 2785.62 | 1028.35 | 2494.33 | 1079.97 | 1414.35 | 0.00 | 0.00 |
September | 2157.30 | 1213.41 | 2001.11 | 897.34 | 1103.77 | 0.00 | 0.00 |
October | 849.95 | 1682.66 | 1067.52 | 383.87 | 683.64 | 0.00 | 0.00 |
November | 294.69 | 2124.69 | 577.70 | 168.64 | 409.06 | 0.00 | 0.00 |
December | 88.85 | 2614.50 | 327.00 | 69.00 | 257.99 | 0.00 | 0.00 |
Annual Sum or Average | 1587.70 | 1606.47 | 1669.95 | 663.94 | 1006.01 | 0.00 | 0.00 |
Minimum of Months | 88.85 | 927.65 | 327.00 | 69.00 | 257.99 | 0.00 | 0.00 |
Maximum of Months | 3298.10 | 2614.50 | 2969.67 | 1309.34 | 1715.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 25.76 | 2907.07 | 459.78 | 0.00 | 459.78 | 0.00 | 0.00 |
February | 87.23 | 2718.34 | 717.96 | 0.00 | 717.96 | 0.00 | 0.00 |
March | 295.04 | 2266.04 | 993.53 | 0.00 | 993.53 | 0.00 | 0.00 |
April | 975.04 | 1848.39 | 1617.62 | 7.24 | 1610.38 | 0.00 | 0.00 |
May | 1236.78 | 1484.94 | 2022.44 | 97.57 | 1924.87 | 0.00 | 0.00 |
June | 1795.03 | 1175.69 | 2235.68 | 140.19 | 2095.49 | 0.00 | 0.00 |
July | 1833.49 | 1079.64 | 2120.67 | 120.91 | 1999.76 | 0.00 | 0.00 |
August | 1411.97 | 1202.47 | 1666.95 | 26.12 | 1640.83 | 0.00 | 0.00 |
September | 919.19 | 1597.05 | 1268.78 | 0.28 | 1268.50 | 0.00 | 0.00 |
October | 311.55 | 2116.77 | 813.02 | 0.00 | 813.02 | 0.00 | 0.00 |
November | 42.47 | 2575.70 | 488.51 | 0.00 | 488.51 | 0.00 | 0.00 |
December | 1.10 | 3100.26 | 332.67 | 0.00 | 332.67 | 0.00 | 0.00 |
Annual Sum or Average | 747.89 | 2002.44 | 1230.42 | 32.92 | 1197.50 | 0.00 | 0.00 |
Minimum of Months | 1.10 | 1079.64 | 332.67 | 0.00 | 332.67 | 0.00 | 0.00 |
Maximum of Months | 1833.49 | 3100.26 | 2235.68 | 140.19 | 2095.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 351.42 | 1821.81 | 626.51 | 251.67 | 374.84 | 0.00 | 0.00 |
February | 582.40 | 1722.40 | 934.23 | 345.11 | 589.12 | 0.00 | 0.00 |
March | 567.24 | 1425.43 | 976.29 | 192.39 | 783.90 | 0.00 | 0.00 |
April | 2668.29 | 1180.94 | 2621.43 | 1231.83 | 1389.60 | 0.00 | 0.00 |
May | 2730.05 | 1014.42 | 2756.35 | 1202.00 | 1554.35 | 0.00 | 0.00 |
June | 2892.10 | 797.21 | 2728.28 | 1089.65 | 1638.63 | 0.00 | 0.00 |
July | 3087.74 | 737.24 | 2785.04 | 1183.64 | 1601.40 | 0.00 | 0.00 |
August | 3018.09 | 799.25 | 2638.22 | 1260.51 | 1377.70 | 0.00 | 0.00 |
September | 2621.27 | 1018.74 | 2375.80 | 1263.34 | 1112.46 | 0.00 | 0.00 |
October | 983.56 | 1355.34 | 1146.83 | 475.28 | 671.55 | 0.00 | 0.00 |
November | 331.39 | 1628.59 | 597.88 | 203.77 | 394.11 | 0.00 | 0.00 |
December | 216.70 | 1966.30 | 443.10 | 164.74 | 278.36 | 0.00 | 0.00 |
Annual Sum or Average | 1674.79 | 1286.86 | 1721.65 | 739.61 | 982.04 | 0.00 | 0.00 |
Minimum of Months | 216.70 | 737.24 | 443.10 | 164.74 | 278.36 | 0.00 | 0.00 |
Maximum of Months | 3087.74 | 1966.30 | 2785.04 | 1263.34 | 1638.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2509.14 | 2687.75 | 2610.30 | 1689.76 | 920.55 | 0.00 | 0.00 |
February | 3151.33 | 2645.26 | 3188.01 | 1945.37 | 1242.64 | 0.00 | 0.00 |
March | 1530.24 | 2208.92 | 1971.04 | 573.88 | 1397.16 | 0.00 | 0.00 |
April | 4556.29 | 1953.19 | 4093.02 | 1850.00 | 2243.02 | 0.00 | 0.00 |
May | 3474.07 | 1682.42 | 3385.31 | 1102.15 | 2283.16 | 0.00 | 0.00 |
June | 3341.69 | 1299.27 | 3118.59 | 754.88 | 2363.71 | 0.00 | 0.00 |
July | 3913.24 | 1208.12 | 3378.93 | 1058.15 | 2320.78 | 0.00 | 0.00 |
August | 4865.40 | 1320.50 | 3959.37 | 1781.07 | 2178.30 | 0.00 | 0.00 |
September | 5691.19 | 1679.33 | 4678.94 | 2741.00 | 1937.94 | 0.00 | 0.00 |
October | 3470.15 | 2132.21 | 3214.62 | 1878.80 | 1335.82 | 0.00 | 0.00 |
November | 2207.74 | 2498.78 | 2279.17 | 1386.48 | 892.69 | 0.00 | 0.00 |
December | 1691.92 | 2973.46 | 1806.45 | 1157.40 | 649.05 | 0.00 | 0.00 |
Annual Sum or Average | 3362.26 | 2020.82 | 3135.51 | 1487.45 | 1648.07 | 0.00 | 0.00 |
Minimum of Months | 1530.24 | 1208.12 | 1806.45 | 573.88 | 649.05 | 0.00 | 0.00 |
Maximum of Months | 5691.19 | 2973.46 | 4678.94 | 2741.00 | 2363.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 347.86 | 1894.67 | 609.25 | 201.30 | 407.95 | 0.00 | 0.00 |
February | 821.46 | 1821.71 | 1078.71 | 455.46 | 623.24 | 0.00 | 0.00 |
March | 557.71 | 1487.31 | 975.38 | 186.59 | 788.79 | 0.00 | 0.00 |
April | 2296.79 | 1292.26 | 2301.45 | 914.15 | 1387.29 | 0.00 | 0.00 |
May | 2682.90 | 1111.50 | 2700.13 | 1097.97 | 1602.16 | 0.00 | 0.00 |
June | 3139.30 | 886.72 | 2915.85 | 1200.34 | 1715.50 | 0.00 | 0.00 |
July | 3347.25 | 828.97 | 2969.66 | 1309.33 | 1660.33 | 0.00 | 0.00 |
August | 2841.00 | 899.17 | 2494.32 | 1079.97 | 1414.35 | 0.00 | 0.00 |
September | 2192.47 | 1117.36 | 2001.11 | 897.34 | 1103.77 | 0.00 | 0.00 |
October | 906.65 | 1435.57 | 1067.51 | 383.87 | 683.64 | 0.00 | 0.00 |
November | 335.67 | 1724.39 | 577.70 | 168.64 | 409.06 | 0.00 | 0.00 |
December | 111.39 | 2093.78 | 327.00 | 69.00 | 257.99 | 0.00 | 0.00 |
Annual Sum or Average | 1634.43 | 1380.57 | 1669.94 | 663.94 | 1006.00 | 0.00 | 0.00 |
Minimum of Months | 111.39 | 828.97 | 327.00 | 69.00 | 257.99 | 0.00 | 0.00 |
Maximum of Months | 3347.25 | 2093.78 | 2969.66 | 1309.33 | 1715.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 42.76 | 2637.62 | 459.78 | 0.00 | 459.78 | 0.00 | 0.00 |
February | 126.90 | 2472.95 | 717.96 | 0.00 | 717.96 | 0.00 | 0.00 |
March | 348.17 | 2071.25 | 993.53 | 0.00 | 993.53 | 0.00 | 0.00 |
April | 1019.15 | 1731.97 | 1617.62 | 7.24 | 1610.38 | 0.00 | 0.00 |
May | 1289.95 | 1398.73 | 2022.44 | 97.57 | 1924.87 | 0.00 | 0.00 |
June | 1813.61 | 1132.93 | 2235.68 | 140.19 | 2095.49 | 0.00 | 0.00 |
July | 1846.48 | 1045.68 | 2120.67 | 120.91 | 1999.76 | 0.00 | 0.00 |
August | 1425.73 | 1158.24 | 1666.95 | 26.12 | 1640.83 | 0.00 | 0.00 |
September | 956.20 | 1500.29 | 1268.78 | 0.28 | 1268.50 | 0.00 | 0.00 |
October | 364.71 | 1904.45 | 813.02 | 0.00 | 813.02 | 0.00 | 0.00 |
November | 64.87 | 2313.79 | 488.51 | 0.00 | 488.51 | 0.00 | 0.00 |
December | 7.42 | 2832.58 | 332.67 | 0.00 | 332.67 | 0.00 | 0.00 |
Annual Sum or Average | 778.77 | 1846.90 | 1230.42 | 32.92 | 1197.50 | 0.00 | 0.00 |
Minimum of Months | 7.42 | 1045.68 | 332.67 | 0.00 | 332.67 | 0.00 | 0.00 |
Maximum of Months | 1846.48 | 2832.58 | 2235.68 | 140.19 | 2095.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 376.14 | 1660.95 | 626.51 | 251.67 | 374.84 | 0.00 | 0.00 |
February | 619.19 | 1578.98 | 934.23 | 345.11 | 589.12 | 0.00 | 0.00 |
March | 604.96 | 1316.27 | 976.29 | 192.39 | 783.90 | 0.00 | 0.00 |
April | 2689.05 | 1122.93 | 2621.43 | 1231.83 | 1389.60 | 0.00 | 0.00 |
May | 2749.92 | 968.45 | 2756.35 | 1202.00 | 1554.35 | 0.00 | 0.00 |
June | 2896.45 | 774.63 | 2728.28 | 1089.65 | 1638.63 | 0.00 | 0.00 |
July | 3086.82 | 720.53 | 2785.04 | 1183.64 | 1601.40 | 0.00 | 0.00 |
August | 3018.67 | 778.79 | 2638.22 | 1260.51 | 1377.70 | 0.00 | 0.00 |
September | 2636.21 | 972.84 | 2375.80 | 1263.34 | 1112.46 | 0.00 | 0.00 |
October | 1016.96 | 1238.41 | 1146.83 | 475.28 | 671.55 | 0.00 | 0.00 |
November | 355.10 | 1478.42 | 597.88 | 203.77 | 394.11 | 0.00 | 0.00 |
December | 233.69 | 1805.14 | 443.10 | 164.74 | 278.36 | 0.00 | 0.00 |
Annual Sum or Average | 1694.09 | 1199.51 | 1721.65 | 739.61 | 982.04 | 0.00 | 0.00 |
Minimum of Months | 233.69 | 720.53 | 443.10 | 164.74 | 278.36 | 0.00 | 0.00 |
Maximum of Months | 3086.82 | 1805.14 | 2785.04 | 1263.34 | 1638.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2569.60 | 2448.27 | 2610.30 | 1689.76 | 920.55 | 0.00 | 0.00 |
February | 3212.90 | 2430.61 | 3188.01 | 1945.37 | 1242.64 | 0.00 | 0.00 |
March | 1589.61 | 2032.75 | 1971.04 | 573.88 | 1397.16 | 0.00 | 0.00 |
April | 4582.94 | 1852.39 | 4093.02 | 1850.00 | 2243.02 | 0.00 | 0.00 |
May | 3503.37 | 1594.67 | 3385.31 | 1102.15 | 2283.16 | 0.00 | 0.00 |
June | 3353.55 | 1253.16 | 3118.59 | 754.88 | 2363.71 | 0.00 | 0.00 |
July | 3917.71 | 1171.66 | 3378.93 | 1058.15 | 2320.78 | 0.00 | 0.00 |
August | 4868.12 | 1278.39 | 3959.37 | 1781.07 | 2178.30 | 0.00 | 0.00 |
September | 5709.41 | 1598.83 | 4678.94 | 2741.00 | 1937.94 | 0.00 | 0.00 |
October | 3515.66 | 1950.58 | 3214.62 | 1878.80 | 1335.82 | 0.00 | 0.00 |
November | 2253.32 | 2268.75 | 2279.17 | 1386.48 | 892.69 | 0.00 | 0.00 |
December | 1733.45 | 2726.75 | 1806.45 | 1157.40 | 649.05 | 0.00 | 0.00 |
Annual Sum or Average | 3396.06 | 1880.95 | 3135.51 | 1487.45 | 1648.07 | 0.00 | 0.00 |
Minimum of Months | 1589.61 | 1171.66 | 1806.45 | 573.88 | 649.05 | 0.00 | 0.00 |
Maximum of Months | 5709.41 | 2726.75 | 4678.94 | 2741.00 | 2363.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 365.56 | 1748.99 | 609.25 | 201.30 | 407.95 | 0.00 | 0.00 |
February | 844.35 | 1697.07 | 1078.71 | 455.46 | 623.24 | 0.00 | 0.00 |
March | 584.80 | 1388.21 | 975.38 | 186.59 | 788.79 | 0.00 | 0.00 |
April | 2315.63 | 1230.28 | 2301.45 | 914.15 | 1387.29 | 0.00 | 0.00 |
May | 2699.33 | 1060.66 | 2700.13 | 1097.97 | 1602.16 | 0.00 | 0.00 |
June | 3141.81 | 858.80 | 2915.85 | 1200.34 | 1715.50 | 0.00 | 0.00 |
July | 3345.41 | 806.79 | 2969.66 | 1309.33 | 1660.33 | 0.00 | 0.00 |
August | 2842.33 | 872.14 | 2494.32 | 1079.97 | 1414.35 | 0.00 | 0.00 |
September | 2207.69 | 1065.14 | 2001.11 | 897.34 | 1103.77 | 0.00 | 0.00 |
October | 932.00 | 1329.32 | 1067.51 | 383.87 | 683.64 | 0.00 | 0.00 |
November | 350.10 | 1592.26 | 577.70 | 168.64 | 409.06 | 0.00 | 0.00 |
December | 119.10 | 1949.94 | 327.00 | 69.00 | 257.99 | 0.00 | 0.00 |
Annual Sum or Average | 1648.34 | 1297.95 | 1669.94 | 663.94 | 1006.00 | 0.00 | 0.00 |
Minimum of Months | 119.10 | 806.79 | 327.00 | 69.00 | 257.99 | 0.00 | 0.00 |
Maximum of Months | 3345.41 | 1949.94 | 2969.66 | 1309.33 | 1715.50 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 31119438.08 | 0.880311E+10 | 0.123147E+10 | 0.00 | 0.123147E+10 | 0.00 | 0.00 |
February | 0.112439E+09 | 0.742685E+10 | 0.173690E+10 | 0.00 | 0.173690E+10 | 0.00 | 0.00 |
March | 0.606725E+09 | 0.688593E+10 | 0.266109E+10 | 0.00 | 0.266109E+10 | 0.00 | 0.00 |
April | 0.237399E+10 | 0.524673E+10 | 0.419289E+10 | 18765639.20 | 0.417413E+10 | 0.00 | 0.00 |
May | 0.319517E+10 | 0.421452E+10 | 0.541693E+10 | 0.261341E+09 | 0.515559E+10 | 0.00 | 0.00 |
June | 0.459326E+10 | 0.320003E+10 | 0.579491E+10 | 0.363378E+09 | 0.543153E+10 | 0.00 | 0.00 |
July | 0.479020E+10 | 0.307472E+10 | 0.568001E+10 | 0.323848E+09 | 0.535616E+10 | 0.00 | 0.00 |
August | 0.366357E+10 | 0.346478E+10 | 0.446478E+10 | 69952038.01 | 0.439483E+10 | 0.00 | 0.00 |
September | 0.227519E+10 | 0.443177E+10 | 0.328869E+10 | 727720.56 | 0.328796E+10 | 0.00 | 0.00 |
October | 0.685940E+09 | 0.638077E+10 | 0.217761E+10 | 0.00 | 0.217761E+10 | 0.00 | 0.00 |
November | 50044891.90 | 0.777670E+10 | 0.126622E+10 | 0.00 | 0.126622E+10 | 0.00 | 0.00 |
December | 0.00 | 0.970081E+10 | 0.891033E+09 | 0.00 | 0.891033E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.223776E+11 | 0.706067E+11 | 0.388025E+11 | 0.103801E+10 | 0.377645E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.307472E+10 | 0.891033E+09 | 0.00 | 0.891033E+09 | 0.00 | 0.00 |
Maximum of Months | 0.479020E+10 | 0.970081E+10 | 0.579491E+10 | 0.363378E+09 | 0.543153E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.873091E+09 | 0.538168E+10 | 0.167805E+10 | 0.674074E+09 | 0.100397E+10 | 0.00 | 0.00 |
February | 0.133604E+10 | 0.454340E+10 | 0.226011E+10 | 0.834900E+09 | 0.142521E+10 | 0.00 | 0.00 |
March | 0.140075E+10 | 0.417840E+10 | 0.261492E+10 | 0.515305E+09 | 0.209961E+10 | 0.00 | 0.00 |
April | 0.691413E+10 | 0.320383E+10 | 0.679477E+10 | 0.319291E+10 | 0.360186E+10 | 0.00 | 0.00 |
May | 0.732569E+10 | 0.283289E+10 | 0.738264E+10 | 0.321944E+10 | 0.416320E+10 | 0.00 | 0.00 |
June | 0.752368E+10 | 0.213372E+10 | 0.707174E+10 | 0.282438E+10 | 0.424736E+10 | 0.00 | 0.00 |
July | 0.829744E+10 | 0.203677E+10 | 0.745948E+10 | 0.317028E+10 | 0.428920E+10 | 0.00 | 0.00 |
August | 0.810535E+10 | 0.219951E+10 | 0.706622E+10 | 0.337618E+10 | 0.369005E+10 | 0.00 | 0.00 |
September | 0.680167E+10 | 0.275383E+10 | 0.615811E+10 | 0.327460E+10 | 0.288351E+10 | 0.00 | 0.00 |
October | 0.256877E+10 | 0.395985E+10 | 0.307168E+10 | 0.127299E+10 | 0.179870E+10 | 0.00 | 0.00 |
November | 0.797252E+09 | 0.472143E+10 | 0.154970E+10 | 0.528162E+09 | 0.102154E+10 | 0.00 | 0.00 |
December | 0.525134E+09 | 0.586747E+10 | 0.118680E+10 | 0.441237E+09 | 0.745567E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.524690E+11 | 0.438128E+11 | 0.542942E+11 | 0.233244E+11 | 0.309698E+11 | 0.00 | 0.00 |
Minimum of Months | 0.525134E+09 | 0.203677E+10 | 0.118680E+10 | 0.441237E+09 | 0.745567E+09 | 0.00 | 0.00 |
Maximum of Months | 0.829744E+10 | 0.586747E+10 | 0.745948E+10 | 0.337618E+10 | 0.428920E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.669109E+10 | 0.748333E+10 | 0.699146E+10 | 0.452586E+10 | 0.246560E+10 | 0.00 | 0.00 |
February | 0.760997E+10 | 0.662718E+10 | 0.771245E+10 | 0.470625E+10 | 0.300621E+10 | 0.00 | 0.00 |
March | 0.401599E+10 | 0.627340E+10 | 0.527924E+10 | 0.153708E+10 | 0.374216E+10 | 0.00 | 0.00 |
April | 0.118231E+11 | 0.525342E+10 | 0.106091E+11 | 0.479521E+10 | 0.581393E+10 | 0.00 | 0.00 |
May | 0.932675E+10 | 0.461929E+10 | 0.906723E+10 | 0.295200E+10 | 0.611524E+10 | 0.00 | 0.00 |
June | 0.866468E+10 | 0.347369E+10 | 0.808341E+10 | 0.195666E+10 | 0.612676E+10 | 0.00 | 0.00 |
July | 0.104710E+11 | 0.335660E+10 | 0.905017E+10 | 0.283416E+10 | 0.621601E+10 | 0.00 | 0.00 |
August | 0.130450E+11 | 0.365723E+10 | 0.106048E+11 | 0.477044E+10 | 0.583437E+10 | 0.00 | 0.00 |
September | 0.148177E+11 | 0.442519E+10 | 0.121279E+11 | 0.710470E+10 | 0.502315E+10 | 0.00 | 0.00 |
October | 0.929191E+10 | 0.595441E+10 | 0.861008E+10 | 0.503220E+10 | 0.357788E+10 | 0.00 | 0.00 |
November | 0.568597E+10 | 0.688618E+10 | 0.590762E+10 | 0.359376E+10 | 0.231387E+10 | 0.00 | 0.00 |
December | 0.446360E+10 | 0.851809E+10 | 0.483841E+10 | 0.309999E+10 | 0.173842E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.105907E+12 | 0.665280E+11 | 0.988819E+11 | 0.469083E+11 | 0.519736E+11 | 0.00 | 0.00 |
Minimum of Months | 0.401599E+10 | 0.335660E+10 | 0.483841E+10 | 0.153708E+10 | 0.173842E+10 | 0.00 | 0.00 |
Maximum of Months | 0.148177E+11 | 0.851809E+10 | 0.121279E+11 | 0.710470E+10 | 0.621601E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.850174E+09 | 0.576087E+10 | 0.163182E+10 | 0.539160E+09 | 0.109266E+10 | 0.00 | 0.00 |
February | 0.186714E+10 | 0.510089E+10 | 0.260962E+10 | 0.110186E+10 | 0.150775E+10 | 0.00 | 0.00 |
March | 0.127938E+10 | 0.481982E+10 | 0.261247E+10 | 0.499766E+09 | 0.211271E+10 | 0.00 | 0.00 |
April | 0.575051E+10 | 0.387453E+10 | 0.596537E+10 | 0.236950E+10 | 0.359587E+10 | 0.00 | 0.00 |
May | 0.709876E+10 | 0.319187E+10 | 0.723205E+10 | 0.294080E+10 | 0.429125E+10 | 0.00 | 0.00 |
June | 0.805921E+10 | 0.251288E+10 | 0.755791E+10 | 0.311130E+10 | 0.444660E+10 | 0.00 | 0.00 |
July | 0.883363E+10 | 0.248463E+10 | 0.795398E+10 | 0.350693E+10 | 0.444705E+10 | 0.00 | 0.00 |
August | 0.746099E+10 | 0.275432E+10 | 0.668081E+10 | 0.289260E+10 | 0.378821E+10 | 0.00 | 0.00 |
September | 0.559173E+10 | 0.314517E+10 | 0.518689E+10 | 0.232592E+10 | 0.286097E+10 | 0.00 | 0.00 |
October | 0.227651E+10 | 0.450683E+10 | 0.285924E+10 | 0.102817E+10 | 0.183107E+10 | 0.00 | 0.00 |
November | 0.763837E+09 | 0.550721E+10 | 0.149741E+10 | 0.437112E+09 | 0.106030E+10 | 0.00 | 0.00 |
December | 0.237978E+09 | 0.700266E+10 | 0.875829E+09 | 0.184819E+09 | 0.691010E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.500698E+11 | 0.506617E+11 | 0.526634E+11 | 0.209379E+11 | 0.317254E+11 | 0.00 | 0.00 |
Minimum of Months | 0.237978E+09 | 0.248463E+10 | 0.875829E+09 | 0.184819E+09 | 0.691010E+09 | 0.00 | 0.00 |
Maximum of Months | 0.883363E+10 | 0.700266E+10 | 0.795398E+10 | 0.350693E+10 | 0.444705E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 68987022.20 | 0.778628E+10 | 0.123147E+10 | 0.00 | 0.123147E+10 | 0.00 | 0.00 |
February | 0.211021E+09 | 0.657620E+10 | 0.173689E+10 | 0.00 | 0.173689E+10 | 0.00 | 0.00 |
March | 0.790226E+09 | 0.606937E+10 | 0.266108E+10 | 0.00 | 0.266108E+10 | 0.00 | 0.00 |
April | 0.252729E+10 | 0.479104E+10 | 0.419288E+10 | 18765572.57 | 0.417411E+10 | 0.00 | 0.00 |
May | 0.331259E+10 | 0.397726E+10 | 0.541691E+10 | 0.261340E+09 | 0.515557E+10 | 0.00 | 0.00 |
June | 0.465271E+10 | 0.304738E+10 | 0.579489E+10 | 0.363377E+09 | 0.543151E+10 | 0.00 | 0.00 |
July | 0.491081E+10 | 0.289172E+10 | 0.567999E+10 | 0.323846E+09 | 0.535614E+10 | 0.00 | 0.00 |
August | 0.378183E+10 | 0.322068E+10 | 0.446476E+10 | 69951789.61 | 0.439481E+10 | 0.00 | 0.00 |
September | 0.238255E+10 | 0.413956E+10 | 0.328868E+10 | 727717.97 | 0.328795E+10 | 0.00 | 0.00 |
October | 0.834451E+09 | 0.566955E+10 | 0.217761E+10 | 0.00 | 0.217761E+10 | 0.00 | 0.00 |
November | 0.110084E+09 | 0.667622E+10 | 0.126621E+10 | 0.00 | 0.126621E+10 | 0.00 | 0.00 |
December | 2945367.77 | 0.830374E+10 | 0.891029E+09 | 0.00 | 0.891029E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.235855E+11 | 0.631490E+11 | 0.388024E+11 | 0.103801E+10 | 0.377644E+11 | 0.00 | 0.00 |
Minimum of Months | 2945367.77 | 0.289172E+10 | 0.891029E+09 | 0.00 | 0.891029E+09 | 0.00 | 0.00 |
Maximum of Months | 0.491081E+10 | 0.830374E+10 | 0.579489E+10 | 0.363377E+09 | 0.543151E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.941244E+09 | 0.487955E+10 | 0.167804E+10 | 0.674072E+09 | 0.100397E+10 | 0.00 | 0.00 |
February | 0.140894E+10 | 0.416684E+10 | 0.226010E+10 | 0.834897E+09 | 0.142520E+10 | 0.00 | 0.00 |
March | 0.151929E+10 | 0.381786E+10 | 0.261491E+10 | 0.515302E+09 | 0.209960E+10 | 0.00 | 0.00 |
April | 0.691621E+10 | 0.306101E+10 | 0.679475E+10 | 0.319290E+10 | 0.360185E+10 | 0.00 | 0.00 |
May | 0.731217E+10 | 0.271702E+10 | 0.738261E+10 | 0.321943E+10 | 0.416318E+10 | 0.00 | 0.00 |
June | 0.749632E+10 | 0.206636E+10 | 0.707171E+10 | 0.282437E+10 | 0.424734E+10 | 0.00 | 0.00 |
July | 0.827019E+10 | 0.197463E+10 | 0.745945E+10 | 0.317026E+10 | 0.428918E+10 | 0.00 | 0.00 |
August | 0.808364E+10 | 0.214072E+10 | 0.706620E+10 | 0.337616E+10 | 0.369003E+10 | 0.00 | 0.00 |
September | 0.679432E+10 | 0.264057E+10 | 0.615808E+10 | 0.327459E+10 | 0.288349E+10 | 0.00 | 0.00 |
October | 0.263435E+10 | 0.363013E+10 | 0.307167E+10 | 0.127298E+10 | 0.179869E+10 | 0.00 | 0.00 |
November | 0.858960E+09 | 0.422131E+10 | 0.154970E+10 | 0.528159E+09 | 0.102154E+10 | 0.00 | 0.00 |
December | 0.580398E+09 | 0.526655E+10 | 0.118680E+10 | 0.441235E+09 | 0.745563E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.528160E+11 | 0.405825E+11 | 0.542940E+11 | 0.233244E+11 | 0.309697E+11 | 0.00 | 0.00 |
Minimum of Months | 0.580398E+09 | 0.197463E+10 | 0.118680E+10 | 0.441235E+09 | 0.745563E+09 | 0.00 | 0.00 |
Maximum of Months | 0.827019E+10 | 0.526655E+10 | 0.745945E+10 | 0.337616E+10 | 0.428918E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.672047E+10 | 0.719888E+10 | 0.699144E+10 | 0.452585E+10 | 0.246559E+10 | 0.00 | 0.00 |
February | 0.762369E+10 | 0.639942E+10 | 0.771243E+10 | 0.470623E+10 | 0.300620E+10 | 0.00 | 0.00 |
March | 0.409859E+10 | 0.591638E+10 | 0.527922E+10 | 0.153707E+10 | 0.374215E+10 | 0.00 | 0.00 |
April | 0.118099E+11 | 0.506267E+10 | 0.106091E+11 | 0.479519E+10 | 0.581391E+10 | 0.00 | 0.00 |
May | 0.930494E+10 | 0.450618E+10 | 0.906720E+10 | 0.295199E+10 | 0.611522E+10 | 0.00 | 0.00 |
June | 0.866167E+10 | 0.336771E+10 | 0.808338E+10 | 0.195665E+10 | 0.612673E+10 | 0.00 | 0.00 |
July | 0.104812E+11 | 0.323582E+10 | 0.905013E+10 | 0.283415E+10 | 0.621598E+10 | 0.00 | 0.00 |
August | 0.130315E+11 | 0.353682E+10 | 0.106048E+11 | 0.477042E+10 | 0.583435E+10 | 0.00 | 0.00 |
September | 0.147516E+11 | 0.435281E+10 | 0.121278E+11 | 0.710467E+10 | 0.502314E+10 | 0.00 | 0.00 |
October | 0.929444E+10 | 0.571090E+10 | 0.861005E+10 | 0.503219E+10 | 0.357786E+10 | 0.00 | 0.00 |
November | 0.572246E+10 | 0.647684E+10 | 0.590760E+10 | 0.359374E+10 | 0.231386E+10 | 0.00 | 0.00 |
December | 0.453163E+10 | 0.796411E+10 | 0.483839E+10 | 0.309998E+10 | 0.173841E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.106032E+12 | 0.637285E+11 | 0.988815E+11 | 0.469081E+11 | 0.519734E+11 | 0.00 | 0.00 |
Minimum of Months | 0.409859E+10 | 0.323582E+10 | 0.483839E+10 | 0.153707E+10 | 0.173841E+10 | 0.00 | 0.00 |
Maximum of Months | 0.147516E+11 | 0.796411E+10 | 0.121278E+11 | 0.710467E+10 | 0.621598E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.931711E+09 | 0.507468E+10 | 0.163181E+10 | 0.539158E+09 | 0.109266E+10 | 0.00 | 0.00 |
February | 0.198727E+10 | 0.440708E+10 | 0.260960E+10 | 0.110186E+10 | 0.150775E+10 | 0.00 | 0.00 |
March | 0.149377E+10 | 0.398361E+10 | 0.261246E+10 | 0.499764E+09 | 0.211270E+10 | 0.00 | 0.00 |
April | 0.595328E+10 | 0.334955E+10 | 0.596535E+10 | 0.236949E+10 | 0.359586E+10 | 0.00 | 0.00 |
May | 0.718587E+10 | 0.297704E+10 | 0.723202E+10 | 0.294079E+10 | 0.429123E+10 | 0.00 | 0.00 |
June | 0.813706E+10 | 0.229838E+10 | 0.755788E+10 | 0.311129E+10 | 0.444659E+10 | 0.00 | 0.00 |
July | 0.896528E+10 | 0.222030E+10 | 0.795394E+10 | 0.350692E+10 | 0.444703E+10 | 0.00 | 0.00 |
August | 0.760935E+10 | 0.240834E+10 | 0.668078E+10 | 0.289259E+10 | 0.378819E+10 | 0.00 | 0.00 |
September | 0.568288E+10 | 0.289619E+10 | 0.518687E+10 | 0.232591E+10 | 0.286096E+10 | 0.00 | 0.00 |
October | 0.242837E+10 | 0.384502E+10 | 0.285923E+10 | 0.102817E+10 | 0.183106E+10 | 0.00 | 0.00 |
November | 0.870058E+09 | 0.446961E+10 | 0.149740E+10 | 0.437110E+09 | 0.106029E+10 | 0.00 | 0.00 |
December | 0.298356E+09 | 0.560799E+10 | 0.875826E+09 | 0.184818E+09 | 0.691007E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.515432E+11 | 0.435378E+11 | 0.526632E+11 | 0.209379E+11 | 0.317253E+11 | 0.00 | 0.00 |
Minimum of Months | 0.298356E+09 | 0.222030E+10 | 0.875826E+09 | 0.184818E+09 | 0.691007E+09 | 0.00 | 0.00 |
Maximum of Months | 0.896528E+10 | 0.560799E+10 | 0.795394E+10 | 0.350692E+10 | 0.444703E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.114534E+09 | 0.706460E+10 | 0.123147E+10 | 0.00 | 0.123147E+10 | 0.00 | 0.00 |
February | 0.306991E+09 | 0.598256E+10 | 0.173689E+10 | 0.00 | 0.173689E+10 | 0.00 | 0.00 |
March | 0.932530E+09 | 0.554765E+10 | 0.266108E+10 | 0.00 | 0.266108E+10 | 0.00 | 0.00 |
April | 0.264163E+10 | 0.448926E+10 | 0.419288E+10 | 18765572.57 | 0.417411E+10 | 0.00 | 0.00 |
May | 0.345501E+10 | 0.374635E+10 | 0.541691E+10 | 0.261340E+09 | 0.515557E+10 | 0.00 | 0.00 |
June | 0.470088E+10 | 0.293655E+10 | 0.579489E+10 | 0.363377E+09 | 0.543151E+10 | 0.00 | 0.00 |
July | 0.494561E+10 | 0.280074E+10 | 0.567999E+10 | 0.323846E+09 | 0.535614E+10 | 0.00 | 0.00 |
August | 0.381868E+10 | 0.310223E+10 | 0.446476E+10 | 69951789.61 | 0.439481E+10 | 0.00 | 0.00 |
September | 0.247847E+10 | 0.388874E+10 | 0.328868E+10 | 727717.97 | 0.328795E+10 | 0.00 | 0.00 |
October | 0.976842E+09 | 0.510088E+10 | 0.217761E+10 | 0.00 | 0.217761E+10 | 0.00 | 0.00 |
November | 0.168139E+09 | 0.599734E+10 | 0.126621E+10 | 0.00 | 0.126621E+10 | 0.00 | 0.00 |
December | 19872596.64 | 0.758677E+10 | 0.891029E+09 | 0.00 | 0.891029E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.245592E+11 | 0.582437E+11 | 0.388024E+11 | 0.103801E+10 | 0.377644E+11 | 0.00 | 0.00 |
Minimum of Months | 19872596.64 | 0.280074E+10 | 0.891029E+09 | 0.00 | 0.891029E+09 | 0.00 | 0.00 |
Maximum of Months | 0.494561E+10 | 0.758677E+10 | 0.579489E+10 | 0.363377E+09 | 0.543151E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.100746E+10 | 0.444869E+10 | 0.167804E+10 | 0.674072E+09 | 0.100397E+10 | 0.00 | 0.00 |
February | 0.149795E+10 | 0.381987E+10 | 0.226010E+10 | 0.834897E+09 | 0.142520E+10 | 0.00 | 0.00 |
March | 0.162032E+10 | 0.352549E+10 | 0.261491E+10 | 0.515302E+09 | 0.209960E+10 | 0.00 | 0.00 |
April | 0.697001E+10 | 0.291064E+10 | 0.679475E+10 | 0.319290E+10 | 0.360185E+10 | 0.00 | 0.00 |
May | 0.736538E+10 | 0.259389E+10 | 0.738261E+10 | 0.321943E+10 | 0.416318E+10 | 0.00 | 0.00 |
June | 0.750759E+10 | 0.200785E+10 | 0.707171E+10 | 0.282437E+10 | 0.424734E+10 | 0.00 | 0.00 |
July | 0.826773E+10 | 0.192986E+10 | 0.745945E+10 | 0.317026E+10 | 0.428918E+10 | 0.00 | 0.00 |
August | 0.808520E+10 | 0.208590E+10 | 0.706620E+10 | 0.337616E+10 | 0.369003E+10 | 0.00 | 0.00 |
September | 0.683305E+10 | 0.252159E+10 | 0.615808E+10 | 0.327459E+10 | 0.288349E+10 | 0.00 | 0.00 |
October | 0.272383E+10 | 0.331696E+10 | 0.307167E+10 | 0.127298E+10 | 0.179869E+10 | 0.00 | 0.00 |
November | 0.920413E+09 | 0.383207E+10 | 0.154970E+10 | 0.528159E+09 | 0.102154E+10 | 0.00 | 0.00 |
December | 0.625927E+09 | 0.483488E+10 | 0.118680E+10 | 0.441235E+09 | 0.745563E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.534249E+11 | 0.378277E+11 | 0.542940E+11 | 0.233244E+11 | 0.309697E+11 | 0.00 | 0.00 |
Minimum of Months | 0.625927E+09 | 0.192986E+10 | 0.118680E+10 | 0.441235E+09 | 0.745563E+09 | 0.00 | 0.00 |
Maximum of Months | 0.826773E+10 | 0.483488E+10 | 0.745945E+10 | 0.337616E+10 | 0.428918E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.688241E+10 | 0.655744E+10 | 0.699144E+10 | 0.452585E+10 | 0.246559E+10 | 0.00 | 0.00 |
February | 0.777265E+10 | 0.588013E+10 | 0.771243E+10 | 0.470623E+10 | 0.300620E+10 | 0.00 | 0.00 |
March | 0.425762E+10 | 0.544452E+10 | 0.527922E+10 | 0.153707E+10 | 0.374215E+10 | 0.00 | 0.00 |
April | 0.118790E+11 | 0.480139E+10 | 0.106091E+11 | 0.479519E+10 | 0.581391E+10 | 0.00 | 0.00 |
May | 0.938343E+10 | 0.427116E+10 | 0.906720E+10 | 0.295199E+10 | 0.611522E+10 | 0.00 | 0.00 |
June | 0.869241E+10 | 0.324818E+10 | 0.808338E+10 | 0.195665E+10 | 0.612673E+10 | 0.00 | 0.00 |
July | 0.104932E+11 | 0.313816E+10 | 0.905013E+10 | 0.283415E+10 | 0.621598E+10 | 0.00 | 0.00 |
August | 0.130388E+11 | 0.342403E+10 | 0.106048E+11 | 0.477042E+10 | 0.583435E+10 | 0.00 | 0.00 |
September | 0.147988E+11 | 0.414416E+10 | 0.121278E+11 | 0.710467E+10 | 0.502314E+10 | 0.00 | 0.00 |
October | 0.941633E+10 | 0.522443E+10 | 0.861005E+10 | 0.503219E+10 | 0.357786E+10 | 0.00 | 0.00 |
November | 0.584061E+10 | 0.588061E+10 | 0.590760E+10 | 0.359374E+10 | 0.231386E+10 | 0.00 | 0.00 |
December | 0.464286E+10 | 0.730332E+10 | 0.483839E+10 | 0.309998E+10 | 0.173841E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.107098E+12 | 0.593175E+11 | 0.988815E+11 | 0.469081E+11 | 0.519734E+11 | 0.00 | 0.00 |
Minimum of Months | 0.425762E+10 | 0.313816E+10 | 0.483839E+10 | 0.153707E+10 | 0.173841E+10 | 0.00 | 0.00 |
Maximum of Months | 0.147988E+11 | 0.730332E+10 | 0.121278E+11 | 0.710467E+10 | 0.621598E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.979128E+09 | 0.468449E+10 | 0.163181E+10 | 0.539158E+09 | 0.109266E+10 | 0.00 | 0.00 |
February | 0.204266E+10 | 0.410555E+10 | 0.260960E+10 | 0.110186E+10 | 0.150775E+10 | 0.00 | 0.00 |
March | 0.156633E+10 | 0.371819E+10 | 0.261246E+10 | 0.499764E+09 | 0.211270E+10 | 0.00 | 0.00 |
April | 0.600211E+10 | 0.318888E+10 | 0.596535E+10 | 0.236949E+10 | 0.359586E+10 | 0.00 | 0.00 |
May | 0.722988E+10 | 0.284088E+10 | 0.723202E+10 | 0.294079E+10 | 0.429123E+10 | 0.00 | 0.00 |
June | 0.814356E+10 | 0.222601E+10 | 0.755788E+10 | 0.311129E+10 | 0.444659E+10 | 0.00 | 0.00 |
July | 0.896034E+10 | 0.216089E+10 | 0.795394E+10 | 0.350692E+10 | 0.444703E+10 | 0.00 | 0.00 |
August | 0.761290E+10 | 0.233595E+10 | 0.668078E+10 | 0.289259E+10 | 0.378819E+10 | 0.00 | 0.00 |
September | 0.572232E+10 | 0.276084E+10 | 0.518687E+10 | 0.232591E+10 | 0.286096E+10 | 0.00 | 0.00 |
October | 0.249626E+10 | 0.356046E+10 | 0.285923E+10 | 0.102817E+10 | 0.183106E+10 | 0.00 | 0.00 |
November | 0.907448E+09 | 0.412714E+10 | 0.149740E+10 | 0.437110E+09 | 0.106029E+10 | 0.00 | 0.00 |
December | 0.318999E+09 | 0.522272E+10 | 0.875826E+09 | 0.184818E+09 | 0.691007E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.519820E+11 | 0.409320E+11 | 0.526632E+11 | 0.209379E+11 | 0.317253E+11 | 0.00 | 0.00 |
Minimum of Months | 0.318999E+09 | 0.216089E+10 | 0.875826E+09 | 0.184818E+09 | 0.691007E+09 | 0.00 | 0.00 |
Maximum of Months | 0.896034E+10 | 0.522272E+10 | 0.795394E+10 | 0.350692E+10 | 0.444703E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.18 | 3.23 | 2.03 | 1.05 | -4.0 | 28.28 | 62.93 | 0.00 |
February | 4.25 | 3.55 | 2.74 | 1.60 | -5.0 | 43.80 | 86.73 | 0.02 |
March | 5.90 | 4.45 | 2.76 | 1.18 | -1.9 | 68.95 | 35.00 | 0.00 |
April | 8.96 | 6.24 | 3.38 | 1.56 | -0.7 | 96.13 | 186.12 | 0.00 |
May | 9.99 | 8.07 | 6.28 | 3.35 | -0.9 | 110.92 | 199.68 | 0.02 |
June | 13.31 | 11.27 | 9.70 | 3.33 | 3.35 | 121.69 | 199.28 | 0.00 |
July | 15.02 | 12.39 | 10.49 | 3.21 | 4.49 | 111.91 | 220.83 | 0.00 |
August | 15.65 | 12.75 | 10.65 | 2.92 | 3.95 | 91.47 | 211.91 | 0.00 |
September | 13.43 | 11.01 | 9.10 | 2.64 | 1.43 | 68.72 | 198.32 | 0.01 |
October | 9.33 | 8.03 | 6.81 | 1.97 | -1.0 | 48.92 | 91.86 | 0.04 |
November | 6.66 | 5.66 | 4.54 | 2.05 | -2.3 | 30.27 | 53.24 | 0.04 |
December | 4.10 | 3.14 | 1.95 | 2.36 | -5.1 | 20.52 | 40.74 | 0.04 |
Annual Sum or Average | 9.26 | 7.50 | 5.89 | 2.27 | -0.6 | 70.25 | 132.30 | 0.02 |
Minimum of Months | 4.10 | 3.14 | 1.95 | 1.05 | -5.1 | 20.52 | 35.00 | 0.00 |
Maximum of Months | 15.65 | 12.75 | 10.65 | 3.35 | 4.49 | 121.69 | 220.83 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 29-JAN-05:00 | 9.37 | 5.00 | 3.60 | 8.35 | 0.00 | 0.00 |
February | 11.00 | 07-FEB-14:00 | 9.86 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 14.00 | 25-MAR-12:00 | 11.22 | 9.00 | 2.60 | 7.35 | 287.00 | 93.00 |
April | 24.00 | 30-APR-14:00 | 13.13 | 4.00 | 1.50 | 7.75 | 167.50 | 716.00 |
May | 24.00 | 22-MAY-14:00 | 16.08 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 27.00 | 13-JUN-16:00 | 17.53 | 12.00 | 3.10 | 12.41 | 141.50 | 652.50 |
July | 30.00 | 22-JUL-17:00 | 16.80 | 8.00 | 0.00 | 14.28 | 122.00 | 407.00 |
August | 27.00 | 14-AUG-17:19 | 14.18 | 3.33 | 2.60 | 10.37 | 133.00 | 358.83 |
September | 23.00 | 11-SEP-16:00 | 16.22 | 12.00 | 2.60 | 8.74 | 108.00 | 325.50 |
October | 19.00 | 07-OCT-14:00 | 10.10 | 1.00 | 1.50 | 2.22 | 131.00 | 540.50 |
November | 16.00 | 24-NOV-11:00 | 12.01 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 13.00 | 23-DEC-10:00 | 7.64 | 2.00 | 7.70 | 6.75 | 70.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.00 | 7.64 | 1.00 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 17.53 | 12.00 | 7.70 | 14.28 | 287.00 | 769.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.0 | 10-JAN-07:00 | -7.0 | -9.0 | 0.00 | -20.0 | 0.00 | 0.00 |
February | -4.0 | 17-FEB-06:00 | -4.0 | -4.0 | 0.00 | -20.5 | 0.00 | 0.00 |
March | -1.0 | 08-MAR-06:00 | -1.4 | -2.0 | 0.00 | -14.4 | 17.50 | 184.50 |
April | 0.00 | 08-APR-04:00 | -0.9 | -2.0 | 0.00 | -12.7 | 0.00 | 0.00 |
May | 2.00 | 06-MAY-04:00 | 1.57 | 1.00 | 3.60 | -13.7 | 12.50 | 117.00 |
June | 6.00 | 01-JUN-03:00 | 5.05 | 4.00 | 0.00 | -9.2 | 0.00 | 0.00 |
July | 7.00 | 05-JUL-04:00 | 6.47 | 6.00 | 3.10 | -7.8 | 28.00 | 155.00 |
August | 8.00 | 20-AUG-04:00 | 7.45 | 7.00 | 0.00 | -6.6 | 0.00 | 0.00 |
September | 5.00 | 20-SEP-03:00 | 5.00 | 5.00 | 2.60 | -10.0 | 0.00 | 0.00 |
October | 2.00 | 07-OCT-03:00 | 2.00 | 2.00 | 0.00 | -13.4 | 0.00 | 0.00 |
November | -2.0 | 29-NOV-01:00 | -2.0 | -2.0 | 3.10 | -10.7 | 0.00 | 0.00 |
December | -3.0 | 29-DEC-20:00 | -4.5 | -7.0 | 3.60 | -20.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -6.0 | -7.0 | -9.0 | 0.00 | -20.5 | 0.00 | 0.00 | |
Maximum of Months | 8.00 | 7.45 | 7.00 | 3.60 | -6.6 | 28.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.44 | 29-JAN-04:00 | 13.00 | 12.00 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.86 | 07-FEB-14:00 | 11.00 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.39 | 28-APR-07:00 | 16.00 | 15.00 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 16.08 | 22-MAY-14:00 | 24.00 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 19.93 | 25-JUN-17:00 | 22.00 | 19.00 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 17.31 | 22-JUL-09:00 | 26.00 | 12.00 | 4.60 | 11.46 | 224.50 | 619.50 |
August | 17.06 | 14-AUG-12:00 | 24.00 | 13.00 | 2.60 | 9.91 | 205.50 | 669.50 |
September | 16.54 | 10-SEP-15:00 | 21.00 | 14.00 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.58 | 17-OCT-14:00 | 16.00 | 12.00 | 0.00 | 12.03 | 144.00 | 44.50 |
November | 12.01 | 24-NOV-11:00 | 16.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 7.93 | 02-DEC-12:00 | 9.00 | 7.00 | 0.00 | 2.01 | 135.50 | 84.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.93 | 9.00 | 7.00 | 0.00 | 2.01 | 0.00 | 0.00 | |
Maximum of Months | 19.93 | 26.00 | 19.00 | 4.60 | 15.94 | 224.50 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 29-JAN-04:00 | 13.00 | 12.44 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.00 | 07-FEB-14:00 | 11.00 | 9.86 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.00 | 28-APR-07:00 | 16.00 | 15.39 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 12.00 | 23-MAY-07:00 | 17.00 | 13.95 | 3.10 | 5.13 | 112.00 | 719.50 |
June | 19.00 | 25-JUN-17:00 | 22.00 | 19.93 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 14.00 | 17-JUL-17:00 | 18.00 | 15.45 | 3.60 | 9.91 | 120.00 | 0.00 |
August | 16.00 | 08-AUG-12:00 | 18.00 | 16.70 | 1.50 | 11.46 | 154.00 | 0.00 |
September | 14.00 | 10-SEP-15:00 | 21.00 | 16.54 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.00 | 17-OCT-18:00 | 13.00 | 13.00 | 2.60 | 9.33 | 0.00 | 0.00 |
November | 12.00 | 08-NOV-14:00 | 12.00 | 12.00 | 0.00 | 8.15 | 93.00 | 106.00 |
December | 7.00 | 02-DEC-11:00 | 8.00 | 7.45 | 3.10 | 1.16 | 144.50 | 146.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.00 | 8.00 | 7.45 | 0.00 | 1.16 | 0.00 | 0.00 | |
Maximum of Months | 19.00 | 22.00 | 19.93 | 3.60 | 15.94 | 160.50 | 719.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.33 | 8.85 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.00 | 14.79 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.33 | 17.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 11.26 | 40.86 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.54 | 47.73 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 13.82 | 50.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 14.77 | 51.67 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 15.12 | 44.67 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 14.78 | 34.25 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.84 | 17.71 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.55 | 9.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 11.27 | 6.14 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.57 | 28.73 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.00 | 6.14 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 15.12 | 51.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.399683E+11 | -0.395251E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -443294229.4 | 60.05 | 0.00 | 0.00 |
February | 0.365524E+11 | -0.361510E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -401343111.6 | 60.05 | 0.00 | 0.00 |
March | 0.426938E+11 | -0.422488E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -445016696.9 | 60.05 | 0.00 | 0.00 |
April | 0.380228E+11 | -0.375950E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -427822779.2 | 60.05 | 0.00 | 0.00 |
May | 0.395395E+11 | -0.390963E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -443175296.8 | 60.05 | 0.00 | 0.00 |
June | 0.381598E+11 | -0.377310E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -428825508.7 | 60.05 | 0.00 | 0.00 |
July | 0.355765E+11 | -0.351370E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -439449489.3 | 60.05 | 0.00 | 0.00 |
August | 0.386186E+11 | -0.381766E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -442017986.2 | 60.05 | 0.00 | 0.00 |
September | 0.353125E+11 | -0.348850E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -427474389.7 | 60.05 | 0.00 | 0.00 |
October | 0.371809E+11 | -0.367393E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -441592401.4 | 60.05 | 0.00 | 0.00 |
November | 0.374731E+11 | -0.370454E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -427708238.5 | 60.05 | 0.00 | 0.00 |
December | 0.382970E+11 | -0.378540E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -443046219.6 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.457395E+12 | -0.452184E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.521077E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.353125E+11 | -0.422488E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -445016696.9 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.426938E+11 | -0.348850E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -401343111.6 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.52 | 0.48 | 01-JAN-08:39 | 4009.58 | 36.45 | 191.17 | 222.17 | 3328.65 | 37.57 | 193.67 | 194.67 |
February | 217.00 | 0.51 | 0.48 | 01-FEB-11:39 | 5750.32 | 36.15 | 213.67 | 246.17 | 2653.30 | 30.40 | 199.83 | 218.83 |
March | 215.50 | 0.51 | 0.48 | 01-MAR-11:39 | 4254.16 | 31.42 | 190.83 | 310.67 | 1200.82 | 22.35 | 211.67 | 266.83 |
April | 359.67 | 0.51 | 0.48 | 01-APR-07:10 | 2695.08 | 21.24 | 219.50 | 355.50 | 1501.20 | 22.65 | 292.83 | 329.50 |
May | 417.17 | 0.51 | 0.48 | 01-MAY-06:00 | 2153.32 | 20.83 | 198.67 | 410.67 | 1195.05 | 22.24 | 313.50 | 374.17 |
June | 410.67 | 0.50 | 0.48 | 01-JUN-05:00 | 2099.28 | 21.10 | 204.00 | 413.17 | 1153.66 | 22.51 | 319.67 | 372.33 |
July | 429.00 | 0.51 | 0.48 | 01-JUL-05:00 | 2092.00 | 20.88 | 200.33 | 421.50 | 1177.61 | 22.29 | 328.17 | 383.17 |
August | 396.33 | 0.51 | 0.48 | 01-AUG-06:19 | 2413.32 | 20.88 | 194.33 | 382.50 | 1372.68 | 22.31 | 309.83 | 349.00 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-07:49 | 3543.99 | 22.83 | 185.67 | 331.17 | 1652.51 | 22.88 | 271.67 | 304.33 |
October | 234.00 | 0.50 | 0.48 | 01-OCT-06:00 | 7274.45 | 35.37 | 217.17 | 280.00 | 2130.42 | 25.35 | 206.50 | 239.33 |
November | 171.33 | 0.51 | 0.48 | 01-NOV-11:39 | 4623.14 | 36.29 | 167.17 | 216.67 | 3816.53 | 37.47 | 170.83 | 173.33 |
December | 131.67 | 0.50 | 0.48 | 02-DEC-08:50 | 3889.58 | 37.35 | 128.67 | 183.33 | 3230.06 | 38.54 | 128.67 | 132.67 |
Annual Sum or Average | 3515.67 | 0.51 | 3338.18 | 25.91 | 2311.17 | 3773.50 | 1758.71 | 25.31 | 2946.83 | 3338.17 | ||
Minimum of Months | 131.67 | 0.50 | 0.48 | 2092.00 | 20.83 | 128.67 | 183.33 | 1153.66 | 22.24 | 128.67 | 132.67 | |
Maximum of Months | 429.00 | 0.52 | 0.48 | 7274.45 | 37.35 | 219.50 | 421.50 | 3816.53 | 38.54 | 328.17 | 383.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.54 | 0.48 | 01-JAN-08:39 | 1480.02 | 24.87 | 88.17 | 210.67 | 871.33 | 24.86 | 102.00 | 146.33 |
February | 217.00 | 0.51 | 0.48 | 01-FEB-11:39 | 1804.35 | 25.06 | 94.00 | 239.33 | 994.67 | 25.18 | 126.00 | 195.00 |
March | 215.50 | 0.52 | 0.48 | 01-MAR-11:39 | 2036.81 | 25.11 | 98.83 | 304.83 | 1071.00 | 25.34 | 167.50 | 252.83 |
April | 359.67 | 0.50 | 0.48 | 01-APR-06:10 | 3789.21 | 26.21 | 167.50 | 364.67 | 2180.12 | 26.45 | 259.67 | 339.67 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-06:40 | 3885.28 | 25.10 | 152.67 | 423.00 | 1738.11 | 24.49 | 254.83 | 382.50 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-04:49 | 3918.46 | 25.62 | 151.17 | 420.83 | 1780.79 | 25.20 | 271.17 | 389.67 |
July | 429.00 | 0.49 | 0.48 | 01-JUL-04:49 | 3831.56 | 25.78 | 168.17 | 432.17 | 1733.57 | 25.25 | 276.00 | 401.83 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-05:30 | 3685.82 | 25.46 | 147.50 | 390.83 | 1619.48 | 24.72 | 268.83 | 361.50 |
September | 337.67 | 0.50 | 0.48 | 01-SEP-07:40 | 3489.17 | 25.87 | 152.67 | 338.50 | 1910.44 | 25.90 | 237.33 | 308.33 |
October | 234.00 | 0.51 | 0.48 | 01-OCT-06:40 | 2759.36 | 26.32 | 118.50 | 273.83 | 1240.19 | 25.13 | 158.17 | 216.00 |
November | 171.33 | 0.52 | 0.48 | 01-NOV-11:50 | 1516.18 | 24.80 | 82.50 | 205.17 | 859.44 | 24.87 | 97.33 | 137.17 |
December | 131.67 | 0.52 | 0.48 | 02-DEC-08:50 | 1280.34 | 25.47 | 65.67 | 166.00 | 880.40 | 26.79 | 79.50 | 99.67 |
Annual Sum or Average | 3515.67 | 0.51 | 3148.67 | 25.54 | 1487.33 | 3769.83 | 1547.83 | 25.29 | 2298.33 | 3230.50 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 1280.34 | 24.80 | 65.67 | 166.00 | 859.44 | 24.49 | 79.50 | 99.67 | |
Maximum of Months | 429.00 | 0.54 | 0.48 | 3918.46 | 26.32 | 168.17 | 432.17 | 2180.12 | 26.79 | 276.00 | 401.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.59 | 0.48 | 01-JAN-10:30 | 547.26 | 16.20 | 0.00 | 188.83 | 315.11 | 17.76 | 0.00 | 77.33 |
February | 217.00 | 0.54 | 0.48 | 01-FEB-12:09 | 726.39 | 17.91 | 0.00 | 224.50 | 421.64 | 19.38 | 16.67 | 143.50 |
March | 215.50 | 0.53 | 0.48 | 01-MAR-11:39 | 891.03 | 18.63 | 0.17 | 300.67 | 481.28 | 19.89 | 41.17 | 220.83 |
April | 359.67 | 0.51 | 0.48 | 01-APR-07:19 | 1191.74 | 20.25 | 28.00 | 360.83 | 706.01 | 21.59 | 248.67 | 329.50 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-06:00 | 1407.18 | 22.04 | 135.00 | 425.50 | 803.58 | 23.27 | 322.50 | 398.50 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-04:00 | 1598.82 | 23.11 | 162.33 | 428.17 | 881.59 | 23.51 | 340.33 | 401.00 |
July | 429.00 | 0.49 | 0.48 | 01-JUL-04:00 | 1486.54 | 22.88 | 171.17 | 438.83 | 868.86 | 24.16 | 358.67 | 416.50 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-05:00 | 1197.74 | 20.30 | 58.00 | 390.00 | 728.39 | 21.69 | 288.17 | 360.17 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-07:00 | 979.81 | 19.65 | 0.83 | 326.33 | 608.54 | 21.13 | 165.50 | 284.17 |
October | 234.00 | 0.53 | 0.48 | 01-OCT-07:49 | 825.30 | 18.54 | 0.00 | 263.83 | 490.19 | 20.02 | 43.67 | 178.67 |
November | 171.33 | 0.56 | 0.48 | 01-NOV-12:20 | 607.31 | 16.97 | 0.00 | 182.33 | 351.96 | 18.49 | 0.00 | 79.67 |
December | 131.67 | 0.59 | 0.48 | 02-DEC-10:00 | 514.04 | 16.45 | 0.00 | 135.00 | 299.58 | 18.07 | 0.00 | 42.00 |
Annual Sum or Average | 3515.67 | 0.52 | 1119.87 | 20.18 | 555.50 | 3664.83 | 651.21 | 21.45 | 1825.33 | 2931.83 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 514.04 | 16.20 | 0.00 | 135.00 | 299.58 | 17.76 | 0.00 | 42.00 | |
Maximum of Months | 429.00 | 0.59 | 0.48 | 1598.82 | 23.11 | 171.17 | 438.83 | 881.59 | 24.16 | 358.67 | 416.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.55 | 0.48 | 01-JAN-10:20 | 1337.70 | 24.12 | 85.33 | 203.83 | 760.18 | 24.14 | 99.50 | 147.00 |
February | 217.00 | 0.53 | 0.48 | 01-FEB-11:39 | 2088.04 | 24.32 | 91.50 | 234.00 | 1116.96 | 24.27 | 125.17 | 183.67 |
March | 215.50 | 0.52 | 0.48 | 01-MAR-11:39 | 1921.36 | 24.01 | 98.50 | 304.17 | 1031.86 | 24.26 | 158.00 | 252.00 |
April | 359.67 | 0.51 | 0.48 | 01-APR-08:09 | 3626.14 | 24.08 | 139.17 | 355.33 | 1633.79 | 23.67 | 234.50 | 328.17 |
May | 417.17 | 0.51 | 0.48 | 01-MAY-07:19 | 3286.11 | 22.30 | 95.00 | 413.50 | 1811.40 | 23.15 | 249.50 | 383.50 |
June | 410.67 | 0.50 | 0.48 | 01-JUN-06:10 | 3798.79 | 21.57 | 72.50 | 419.00 | 1691.52 | 21.85 | 248.50 | 381.00 |
July | 429.00 | 0.50 | 0.48 | 01-JUL-06:10 | 3773.36 | 21.47 | 65.33 | 428.00 | 1719.82 | 21.78 | 242.83 | 395.00 |
August | 396.33 | 0.51 | 0.48 | 01-AUG-06:30 | 3366.59 | 22.99 | 116.83 | 383.33 | 1866.10 | 23.61 | 239.00 | 351.50 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-08:20 | 3265.43 | 24.62 | 129.17 | 326.00 | 1777.71 | 24.98 | 205.33 | 298.50 |
October | 234.00 | 0.52 | 0.48 | 01-OCT-07:49 | 2596.89 | 25.54 | 113.50 | 269.17 | 1159.15 | 24.52 | 149.00 | 211.50 |
November | 171.33 | 0.54 | 0.48 | 01-NOV-11:00 | 1469.61 | 23.97 | 77.17 | 197.67 | 782.68 | 23.93 | 91.33 | 132.83 |
December | 131.67 | 0.56 | 0.48 | 02-DEC-10:20 | 1060.12 | 22.34 | 46.33 | 161.17 | 549.15 | 22.11 | 54.00 | 83.00 |
Annual Sum or Average | 3515.67 | 0.52 | 2963.51 | 23.23 | 1130.33 | 3695.17 | 1481.01 | 23.39 | 2096.67 | 3147.67 | ||
Minimum of Months | 131.67 | 0.50 | 0.48 | 1060.12 | 21.47 | 46.33 | 161.17 | 549.15 | 21.78 | 54.00 | 83.00 | |
Maximum of Months | 429.00 | 0.56 | 0.48 | 3798.79 | 25.54 | 139.17 | 428.00 | 1866.10 | 24.98 | 249.50 | 395.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.52 | 0.48 | 01-JAN-08:39 | 4034.20 | 36.02 | 190.67 | 222.17 | 3419.26 | 37.20 | 189.83 | 196.67 |
February | 217.00 | 0.50 | 0.48 | 01-FEB-11:39 | 5788.22 | 35.72 | 213.33 | 246.17 | 2817.48 | 29.99 | 141.83 | 224.83 |
March | 215.50 | 0.51 | 0.48 | 01-MAR-11:39 | 4267.23 | 30.13 | 181.17 | 310.67 | 1273.86 | 17.60 | 4.67 | 272.83 |
April | 359.67 | 0.51 | 0.48 | 01-APR-07:10 | 2740.76 | 15.03 | 0.00 | 356.00 | 1605.88 | 18.51 | 17.17 | 333.33 |
May | 417.17 | 0.51 | 0.48 | 01-MAY-06:00 | 2187.87 | 14.74 | 0.00 | 410.83 | 1276.27 | 18.18 | 0.00 | 379.00 |
June | 410.67 | 0.50 | 0.48 | 01-JUN-05:49 | 2129.77 | 15.07 | 0.00 | 413.50 | 1230.20 | 18.48 | 0.00 | 376.83 |
July | 429.00 | 0.50 | 0.48 | 01-JUL-05:49 | 2127.70 | 14.87 | 0.00 | 421.83 | 1258.14 | 18.31 | 2.67 | 387.33 |
August | 396.33 | 0.51 | 0.48 | 01-AUG-06:19 | 2595.47 | 15.05 | 5.50 | 382.67 | 1469.83 | 18.20 | 8.67 | 352.00 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-07:49 | 4626.64 | 19.98 | 76.17 | 331.50 | 1772.83 | 18.54 | 12.33 | 307.33 |
October | 234.00 | 0.50 | 0.48 | 01-OCT-06:49 | 7310.13 | 34.61 | 216.17 | 280.17 | 2249.12 | 21.06 | 33.67 | 244.83 |
November | 171.33 | 0.51 | 0.48 | 01-NOV-11:39 | 4641.62 | 35.84 | 166.83 | 216.67 | 3915.40 | 37.12 | 167.17 | 176.33 |
December | 131.67 | 0.50 | 0.48 | 02-DEC-08:50 | 3899.47 | 36.85 | 128.50 | 183.67 | 3322.53 | 38.16 | 128.67 | 135.67 |
Annual Sum or Average | 3515.67 | 0.51 | 3487.55 | 21.96 | 1178.33 | 3775.83 | 1856.16 | 21.92 | 706.67 | 3387.00 | ||
Minimum of Months | 131.67 | 0.50 | 0.48 | 2127.70 | 14.74 | 0.00 | 183.67 | 1230.20 | 17.60 | 0.00 | 135.67 | |
Maximum of Months | 429.00 | 0.52 | 0.48 | 7310.13 | 36.85 | 216.17 | 421.83 | 3915.40 | 38.16 | 189.83 | 387.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.54 | 0.48 | 01-JAN-08:39 | 1501.80 | 22.79 | 82.50 | 211.17 | 903.88 | 23.31 | 73.50 | 150.00 |
February | 217.00 | 0.51 | 0.48 | 01-FEB-11:39 | 1835.65 | 22.66 | 75.33 | 239.67 | 1038.65 | 23.33 | 70.17 | 201.67 |
March | 215.50 | 0.52 | 0.48 | 01-MAR-11:39 | 2061.78 | 21.21 | 71.33 | 305.67 | 1116.38 | 23.38 | 65.17 | 257.33 |
April | 359.67 | 0.50 | 0.48 | 01-APR-06:10 | 3807.79 | 22.15 | 107.17 | 364.33 | 2266.30 | 24.35 | 92.83 | 345.00 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-06:40 | 3942.40 | 22.24 | 134.00 | 423.17 | 1818.13 | 21.95 | 72.17 | 389.50 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-04:49 | 3969.56 | 22.82 | 139.17 | 421.17 | 1862.80 | 22.77 | 81.50 | 392.50 |
July | 429.00 | 0.49 | 0.48 | 01-JUL-04:49 | 3876.24 | 22.35 | 139.67 | 433.00 | 1816.65 | 22.83 | 87.17 | 404.67 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-05:30 | 3747.33 | 22.70 | 127.83 | 391.83 | 1700.53 | 22.29 | 72.00 | 365.17 |
September | 337.67 | 0.50 | 0.48 | 01-SEP-07:40 | 3546.39 | 23.02 | 109.33 | 338.83 | 1988.73 | 23.79 | 85.33 | 311.67 |
October | 234.00 | 0.51 | 0.48 | 01-OCT-06:40 | 2768.48 | 22.90 | 85.00 | 274.50 | 1298.39 | 23.14 | 69.00 | 221.00 |
November | 171.33 | 0.52 | 0.48 | 01-NOV-11:50 | 1540.59 | 22.56 | 64.83 | 206.17 | 895.00 | 23.22 | 69.00 | 140.83 |
December | 131.67 | 0.52 | 0.48 | 02-DEC-08:50 | 1301.83 | 23.34 | 52.67 | 167.50 | 911.94 | 25.49 | 65.67 | 102.50 |
Annual Sum or Average | 3515.67 | 0.50 | 3188.48 | 22.53 | 1188.83 | 3777.00 | 1616.62 | 23.14 | 903.50 | 3281.83 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 1301.83 | 21.21 | 52.67 | 167.50 | 895.00 | 21.95 | 65.17 | 102.50 | |
Maximum of Months | 429.00 | 0.54 | 0.48 | 3969.56 | 23.34 | 139.67 | 433.00 | 2266.30 | 25.49 | 92.83 | 404.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.58 | 0.48 | 01-JAN-10:20 | 552.50 | 10.31 | 0.00 | 189.50 | 334.29 | 13.82 | 0.00 | 89.33 |
February | 217.00 | 0.54 | 0.48 | 01-FEB-11:00 | 735.03 | 12.19 | 0.00 | 224.83 | 447.83 | 15.67 | 0.00 | 153.33 |
March | 215.50 | 0.53 | 0.48 | 01-MAR-11:39 | 902.91 | 12.69 | 0.00 | 300.67 | 510.92 | 16.01 | 0.00 | 232.83 |
April | 359.67 | 0.51 | 0.48 | 01-APR-07:19 | 1212.63 | 15.04 | 0.00 | 360.83 | 751.98 | 18.46 | 5.83 | 334.67 |
May | 417.17 | 0.49 | 0.48 | 01-MAY-06:00 | 1431.05 | 16.95 | 38.00 | 425.83 | 855.98 | 20.21 | 54.17 | 402.83 |
June | 410.67 | 0.48 | 0.48 | 01-JUN-04:00 | 1625.97 | 18.21 | 58.17 | 428.17 | 969.03 | 21.32 | 80.83 | 405.67 |
July | 429.00 | 0.49 | 0.48 | 01-JUL-04:49 | 1515.83 | 18.08 | 58.83 | 439.17 | 924.02 | 21.23 | 80.33 | 419.67 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-05:00 | 1235.13 | 14.95 | 0.00 | 391.83 | 776.00 | 18.45 | 6.83 | 363.00 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-07:00 | 996.23 | 14.55 | 0.00 | 326.50 | 648.19 | 18.03 | 0.00 | 289.00 |
October | 234.00 | 0.53 | 0.48 | 01-OCT-07:40 | 836.23 | 13.07 | 0.00 | 264.17 | 521.04 | 16.52 | 0.00 | 186.17 |
November | 171.33 | 0.56 | 0.48 | 01-NOV-12:09 | 613.53 | 11.06 | 0.00 | 182.83 | 373.52 | 14.59 | 0.00 | 88.33 |
December | 131.67 | 0.58 | 0.48 | 02-DEC-10:50 | 518.64 | 10.26 | 0.00 | 135.67 | 317.74 | 13.96 | 0.00 | 50.17 |
Annual Sum or Average | 3515.67 | 0.51 | 1140.14 | 14.86 | 155.00 | 3670.00 | 696.53 | 18.23 | 228.00 | 3015.00 | ||
Minimum of Months | 131.67 | 0.48 | 0.48 | 518.64 | 10.26 | 0.00 | 135.67 | 317.74 | 13.82 | 0.00 | 50.17 | |
Maximum of Months | 429.00 | 0.58 | 0.48 | 1625.97 | 18.21 | 58.83 | 439.17 | 969.03 | 21.32 | 80.83 | 419.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.55 | 0.48 | 01-JAN-10:09 | 1357.81 | 22.02 | 78.00 | 205.00 | 791.52 | 22.56 | 68.83 | 154.17 |
February | 217.00 | 0.53 | 0.48 | 01-FEB-11:39 | 2085.44 | 20.35 | 58.33 | 234.33 | 1166.66 | 22.25 | 61.50 | 188.83 |
March | 215.50 | 0.52 | 0.48 | 01-MAR-11:39 | 1954.16 | 21.18 | 72.33 | 305.33 | 1076.36 | 22.15 | 54.17 | 255.83 |
April | 359.67 | 0.51 | 0.48 | 01-APR-07:00 | 3683.53 | 21.13 | 101.83 | 355.83 | 1710.82 | 21.10 | 50.00 | 332.50 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-07:10 | 3336.51 | 18.73 | 73.83 | 414.00 | 1889.47 | 20.35 | 45.50 | 386.50 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-05:00 | 3850.23 | 17.73 | 50.33 | 420.33 | 1775.89 | 18.63 | 0.00 | 384.50 |
July | 429.00 | 0.50 | 0.48 | 01-JUL-05:00 | 3822.28 | 17.63 | 53.17 | 428.83 | 1804.95 | 18.59 | 3.67 | 399.00 |
August | 396.33 | 0.51 | 0.48 | 01-AUG-06:30 | 3410.33 | 19.72 | 86.83 | 383.17 | 1945.99 | 21.02 | 57.33 | 354.50 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-08:09 | 3302.10 | 21.52 | 96.83 | 325.33 | 1848.48 | 22.78 | 76.50 | 302.67 |
October | 234.00 | 0.52 | 0.48 | 01-OCT-07:49 | 2613.30 | 22.27 | 81.67 | 270.83 | 1213.99 | 22.49 | 64.83 | 216.83 |
November | 171.33 | 0.54 | 0.48 | 01-NOV-11:50 | 1492.92 | 21.61 | 59.50 | 199.67 | 817.33 | 22.19 | 65.00 | 136.83 |
December | 131.67 | 0.55 | 0.48 | 02-DEC-10:09 | 1077.29 | 19.80 | 37.67 | 161.83 | 575.37 | 20.30 | 37.00 | 89.00 |
Annual Sum or Average | 3515.67 | 0.51 | 3001.64 | 19.95 | 850.33 | 3704.50 | 1548.06 | 20.90 | 584.33 | 3201.17 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 1077.29 | 17.63 | 37.67 | 161.83 | 575.37 | 18.59 | 0.00 | 89.00 | |
Maximum of Months | 429.00 | 0.55 | 0.48 | 3850.23 | 22.27 | 101.83 | 428.83 | 1945.99 | 22.78 | 76.50 | 399.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.52 | 0.48 | 01-JAN-08:39 | 4035.07 | 36.02 | 190.67 | 222.17 | 3421.02 | 37.19 | 189.83 | 196.83 |
February | 217.00 | 0.50 | 0.48 | 01-FEB-11:39 | 5790.02 | 35.71 | 213.33 | 246.17 | 2820.02 | 29.98 | 141.83 | 224.83 |
March | 215.50 | 0.51 | 0.48 | 01-MAR-11:39 | 4270.56 | 30.12 | 181.17 | 310.83 | 1276.39 | 17.59 | 4.67 | 272.83 |
April | 359.67 | 0.51 | 0.48 | 01-APR-07:10 | 2744.66 | 15.00 | 0.00 | 356.00 | 1608.37 | 18.50 | 16.83 | 333.50 |
May | 417.17 | 0.51 | 0.48 | 01-MAY-06:00 | 2191.06 | 14.71 | 0.00 | 410.83 | 1278.23 | 18.17 | 0.00 | 379.17 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-05:49 | 2132.94 | 15.04 | 0.00 | 413.67 | 1232.12 | 18.46 | 0.00 | 376.83 |
July | 429.00 | 0.50 | 0.48 | 01-JUL-05:49 | 2130.68 | 14.84 | 0.00 | 421.83 | 1260.00 | 18.30 | 2.50 | 387.50 |
August | 396.33 | 0.51 | 0.48 | 01-AUG-06:19 | 2598.81 | 15.02 | 5.50 | 382.67 | 1471.97 | 18.19 | 8.17 | 352.00 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-07:49 | 4629.94 | 19.96 | 76.17 | 331.50 | 1775.35 | 18.53 | 12.00 | 307.33 |
October | 234.00 | 0.50 | 0.48 | 01-OCT-06:49 | 7312.44 | 34.60 | 216.17 | 280.17 | 2251.99 | 21.05 | 33.67 | 244.83 |
November | 171.33 | 0.51 | 0.48 | 01-NOV-11:39 | 4642.61 | 35.83 | 166.83 | 216.67 | 3917.68 | 37.12 | 167.17 | 176.67 |
December | 131.67 | 0.50 | 0.48 | 02-DEC-08:50 | 3900.25 | 36.84 | 128.50 | 183.67 | 3324.20 | 38.16 | 128.67 | 136.00 |
Annual Sum or Average | 3515.67 | 0.51 | 3490.35 | 21.94 | 1178.33 | 3776.17 | 1858.36 | 21.91 | 705.33 | 3388.33 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 2130.68 | 14.71 | 0.00 | 183.67 | 1232.12 | 17.59 | 0.00 | 136.00 | |
Maximum of Months | 429.00 | 0.52 | 0.48 | 7312.44 | 36.84 | 216.17 | 421.83 | 3917.68 | 38.16 | 189.83 | 387.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.54 | 0.48 | 01-JAN-08:39 | 1502.63 | 22.77 | 82.50 | 211.17 | 904.76 | 23.30 | 73.33 | 150.00 |
February | 217.00 | 0.51 | 0.48 | 01-FEB-11:39 | 1836.79 | 22.63 | 75.33 | 239.67 | 1039.84 | 23.32 | 69.83 | 201.83 |
March | 215.50 | 0.52 | 0.48 | 01-MAR-11:39 | 2063.84 | 21.19 | 71.33 | 305.67 | 1117.94 | 23.37 | 65.00 | 257.83 |
April | 359.67 | 0.50 | 0.48 | 01-APR-06:10 | 3809.81 | 22.13 | 107.17 | 364.33 | 2268.26 | 24.34 | 92.83 | 345.00 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-06:40 | 3944.80 | 22.22 | 134.00 | 423.17 | 1820.09 | 21.94 | 72.17 | 389.67 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-04:49 | 3972.15 | 22.79 | 139.17 | 421.17 | 1864.85 | 22.76 | 81.50 | 392.50 |
July | 429.00 | 0.49 | 0.48 | 01-JUL-04:49 | 3878.56 | 22.32 | 139.67 | 433.00 | 1818.61 | 22.82 | 87.17 | 404.83 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-05:30 | 3749.14 | 22.68 | 127.83 | 391.83 | 1702.34 | 22.27 | 72.00 | 365.50 |
September | 337.67 | 0.50 | 0.48 | 01-SEP-07:40 | 3547.68 | 22.99 | 109.33 | 339.00 | 1990.38 | 23.77 | 85.00 | 311.83 |
October | 234.00 | 0.51 | 0.48 | 01-OCT-06:40 | 2769.76 | 22.88 | 85.00 | 274.83 | 1299.80 | 23.12 | 68.67 | 221.17 |
November | 171.33 | 0.52 | 0.48 | 01-NOV-11:50 | 1541.54 | 22.53 | 64.83 | 206.33 | 896.01 | 23.21 | 68.33 | 140.83 |
December | 131.67 | 0.52 | 0.48 | 02-DEC-08:50 | 1302.56 | 23.31 | 52.67 | 167.67 | 912.82 | 25.48 | 65.33 | 102.50 |
Annual Sum or Average | 3515.67 | 0.50 | 3190.28 | 22.51 | 1188.83 | 3777.83 | 1618.28 | 23.12 | 901.17 | 3283.50 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 1302.56 | 21.19 | 52.67 | 167.67 | 896.01 | 21.94 | 65.00 | 102.50 | |
Maximum of Months | 429.00 | 0.54 | 0.48 | 3972.15 | 23.31 | 139.67 | 433.00 | 2268.26 | 25.48 | 92.83 | 404.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.58 | 0.48 | 01-JAN-10:20 | 553.06 | 10.28 | 0.00 | 189.67 | 334.78 | 13.80 | 0.00 | 90.00 |
February | 217.00 | 0.54 | 0.48 | 01-FEB-11:00 | 735.78 | 12.16 | 0.00 | 224.83 | 448.47 | 15.65 | 0.00 | 153.33 |
March | 215.50 | 0.53 | 0.48 | 01-MAR-11:39 | 904.19 | 12.66 | 0.00 | 301.00 | 511.80 | 15.99 | 0.00 | 233.33 |
April | 359.67 | 0.51 | 0.48 | 01-APR-07:19 | 1213.77 | 15.01 | 0.00 | 361.00 | 752.99 | 18.44 | 5.17 | 335.00 |
May | 417.17 | 0.49 | 0.48 | 01-MAY-06:00 | 1432.53 | 16.93 | 38.00 | 426.00 | 857.16 | 20.20 | 53.50 | 402.83 |
June | 410.67 | 0.48 | 0.48 | 01-JUN-04:00 | 1627.69 | 18.19 | 58.17 | 428.17 | 970.36 | 21.31 | 79.50 | 405.83 |
July | 429.00 | 0.49 | 0.48 | 01-JUL-04:49 | 1517.28 | 18.05 | 58.83 | 439.17 | 925.23 | 21.21 | 79.50 | 420.00 |
August | 396.33 | 0.50 | 0.48 | 01-AUG-05:00 | 1236.19 | 14.92 | 0.00 | 391.83 | 776.98 | 18.44 | 6.67 | 363.00 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-07:00 | 996.96 | 14.52 | 0.00 | 326.50 | 648.96 | 18.02 | 0.00 | 289.33 |
October | 234.00 | 0.53 | 0.48 | 01-OCT-07:40 | 837.00 | 13.03 | 0.00 | 264.17 | 521.75 | 16.50 | 0.00 | 186.33 |
November | 171.33 | 0.56 | 0.48 | 01-NOV-12:09 | 614.14 | 11.03 | 0.00 | 183.17 | 374.06 | 14.57 | 0.00 | 88.67 |
December | 131.67 | 0.58 | 0.48 | 02-DEC-10:50 | 519.11 | 10.23 | 0.00 | 136.00 | 318.20 | 13.94 | 0.00 | 50.17 |
Annual Sum or Average | 3515.67 | 0.51 | 1141.25 | 14.83 | 155.00 | 3671.50 | 697.47 | 18.22 | 224.33 | 3017.83 | ||
Minimum of Months | 131.67 | 0.48 | 0.48 | 519.11 | 10.23 | 0.00 | 136.00 | 318.20 | 13.80 | 0.00 | 50.17 | |
Maximum of Months | 429.00 | 0.58 | 0.48 | 1627.69 | 18.19 | 58.83 | 439.17 | 970.36 | 21.31 | 79.50 | 420.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.55 | 0.48 | 01-JAN-10:09 | 1358.66 | 21.99 | 78.00 | 205.33 | 792.43 | 22.55 | 68.83 | 154.17 |
February | 217.00 | 0.53 | 0.48 | 01-FEB-11:39 | 2086.58 | 20.32 | 58.33 | 234.50 | 1167.93 | 22.24 | 60.83 | 189.17 |
March | 215.50 | 0.52 | 0.48 | 01-MAR-11:39 | 1956.21 | 21.15 | 72.33 | 305.50 | 1077.95 | 22.14 | 54.00 | 256.17 |
April | 359.67 | 0.51 | 0.48 | 01-APR-07:00 | 3685.56 | 21.10 | 101.83 | 355.83 | 1712.73 | 21.08 | 50.00 | 332.50 |
May | 417.17 | 0.50 | 0.48 | 01-MAY-07:10 | 3338.79 | 18.70 | 73.83 | 414.00 | 1891.42 | 20.34 | 45.50 | 386.50 |
June | 410.67 | 0.49 | 0.48 | 01-JUN-05:00 | 3852.82 | 17.70 | 50.33 | 420.33 | 1778.02 | 18.61 | 0.00 | 384.50 |
July | 429.00 | 0.50 | 0.48 | 01-JUL-05:00 | 3824.49 | 17.60 | 53.17 | 428.83 | 1806.93 | 18.57 | 3.67 | 399.17 |
August | 396.33 | 0.51 | 0.48 | 01-AUG-06:30 | 3412.36 | 19.69 | 86.83 | 383.17 | 1947.92 | 21.00 | 57.00 | 354.83 |
September | 337.67 | 0.51 | 0.48 | 01-SEP-08:09 | 3303.63 | 21.49 | 96.83 | 325.33 | 1850.13 | 22.77 | 76.17 | 302.83 |
October | 234.00 | 0.52 | 0.48 | 01-OCT-07:49 | 2614.65 | 22.24 | 81.67 | 270.83 | 1215.43 | 22.47 | 64.67 | 217.17 |
November | 171.33 | 0.54 | 0.48 | 01-NOV-11:50 | 1493.92 | 21.58 | 59.50 | 199.83 | 818.35 | 22.18 | 65.00 | 137.00 |
December | 131.67 | 0.55 | 0.48 | 02-DEC-10:09 | 1078.07 | 19.78 | 37.67 | 162.17 | 576.18 | 20.29 | 36.83 | 89.00 |
Annual Sum or Average | 3515.67 | 0.51 | 3003.47 | 19.92 | 850.33 | 3705.67 | 1549.75 | 20.89 | 582.50 | 3203.00 | ||
Minimum of Months | 131.67 | 0.49 | 0.48 | 1078.07 | 17.60 | 37.67 | 162.17 | 576.18 | 18.57 | 0.00 | 89.00 | |
Maximum of Months | 429.00 | 0.55 | 0.48 | 3852.82 | 22.24 | 101.83 | 428.83 | 1947.92 | 22.77 | 76.17 | 399.17 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.583678E+10 | 27734.77 | 10-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.351590E+10 | 23242.26 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.164828E+10 | 15346.91 | 08-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.117848E+09 | 11670.79 | 08-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 34907832.76 | 7642.96 | 06-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5231.21 | 2.15 | 26-JUN-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4028.93 | 2.14 | 24-JUL-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 3912.94 | 1.00 | 22-AUG-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2975486.75 | 2306.22 | 21-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169321E+09 | 7663.31 | 07-OCT-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138042E+10 | 17483.99 | 29-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.379399E+10 | 20984.24 | 29-DEC-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165004E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 3912.94 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.583678E+10 | 27734.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 64420615.96 | 6606.06 | 10-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2081217.02 | 532.89 | 17-FEB-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66501832.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 64420615.96 | 6606.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.184729E+09 | 9061.23 | 12-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 69557243.72 | 3377.62 | 17-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12265530.51 | 1315.98 | 16-MAR-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 506958.46 | 272.71 | 28-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 35384642.41 | 2088.93 | 29-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.188857E+09 | 4849.17 | 30-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.491300E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.188857E+09 | 9061.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.302449E+09 | 15260.87 | 09-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119265E+09 | 7484.01 | 17-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 34695820.92 | 3070.73 | 16-MAR-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2076533.81 | 674.98 | 28-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 63533053.34 | 5991.06 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261690E+09 | 15274.40 | 26-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.783709E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.302449E+09 | 15274.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 17105033.81 | 1363.34 | 10-JAN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 17105033.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17105033.81 | 1363.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.104909E+12 | 306917.29 | 10-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.662733E+11 | 257843.51 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.468527E+11 | 186433.39 | 08-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.621692E+10 | 152124.16 | 08-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146555E+10 | 93063.97 | 06-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7575084.57 | 9916.82 | 07-JUN-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.252142E+09 | 50594.78 | 21-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.684928E+10 | 99223.93 | 12-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.393228E+11 | 206504.23 | 29-NOV-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.982995E+11 | 239547.00 | 29-DEC-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.370449E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.104909E+12 | 306917.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.171080E+11 | 113375.54 | 30-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108718E+11 | 114930.21 | 24-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.540094E+10 | 113077.51 | 06-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.323864E+09 | 56007.70 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4303168.78 | 12897.86 | 05-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.190748E+10 | 112517.86 | 23-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.853252E+10 | 116185.43 | 17-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.218038E+11 | 113112.77 | 21-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.659527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.218038E+11 | 116185.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.171949E+11 | 146801.71 | 09-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115839E+11 | 146496.95 | 21-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.779106E+10 | 146417.18 | 06-MAR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.400758E+09 | 53882.78 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.111827E+09 | 29999.04 | 05-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16562695.11 | 5107.79 | 21-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.363425E+10 | 81405.10 | 21-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.109067E+11 | 146486.21 | 21-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.228848E+11 | 146845.02 | 18-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.745248E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.228848E+11 | 146845.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.136483E+11 | 213039.77 | 30-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.841683E+10 | 212864.86 | 13-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.697739E+10 | 213081.00 | 27-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.474104E+09 | 34886.11 | 11-APR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.278241E+09 | 62245.83 | 05-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.255333E+10 | 90016.63 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.818510E+10 | 212878.11 | 30-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.224911E+11 | 213570.26 | 11-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.630245E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.224911E+11 | 213570.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.141245E+11 | 140002.43 | 02-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.813184E+10 | 140080.70 | 27-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.522807E+10 | 139848.73 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.278552E+09 | 21881.62 | 11-APR-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149688E+09 | 25880.19 | 05-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15158155.43 | 3744.19 | 07-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.259636E+10 | 43322.34 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.814895E+10 | 139933.70 | 29-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.190121E+11 | 140176.74 | 26-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.576852E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.190121E+11 | 140176.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.137392E+11 | 35142.26 | 10-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.955425E+10 | 31078.69 | 17-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.744296E+10 | 23465.36 | 08-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141222E+10 | 19943.66 | 08-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.459910E+09 | 13520.46 | 06-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 8420129.67 | 3790.09 | 08-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1145.87 | 0.68 | 28-JUL-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 166475.80 | 300.16 | 24-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 92369799.22 | 8888.47 | 21-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.167223E+10 | 14710.48 | 23-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.648614E+10 | 25281.07 | 29-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132494E+11 | 27755.54 | 29-DEC-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.541173E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 1145.87 | 0.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.137392E+11 | 35142.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.404291E+10 | 75347.15 | 23-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.220255E+10 | 75350.82 | 27-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114658E+10 | 75310.03 | 06-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3987022.84 | 1937.62 | 03-APR-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.403682E+09 | 75060.34 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.180865E+10 | 75317.24 | 27-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.480498E+10 | 75322.51 | 18-DEC-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.480498E+10 | 75350.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.506340E+10 | 12609.76 | 30-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.360806E+10 | 12589.43 | 27-FEB-05:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.256311E+10 | 12604.50 | 20-MAR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.510828E+09 | 12493.56 | 01-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.205040E+09 | 12481.93 | 16-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2153297.40 | 1283.89 | 07-JUN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1676992.86 | 1787.21 | 31-JUL-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 495638.36 | 332.24 | 28-AUG-05:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.148025E+09 | 12485.20 | 18-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146059E+10 | 12555.93 | 23-OCT-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.330049E+10 | 12583.30 | 24-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.565841E+10 | 12611.75 | 05-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.225223E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 495638.36 | 332.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.565841E+10 | 12611.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.373830E+10 | 17198.27 | 17-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.268808E+10 | 17185.79 | 27-FEB-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.218153E+10 | 17166.24 | 06-MAR-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.278701E+09 | 17132.78 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.134546E+09 | 12125.61 | 02-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4546689.72 | 1571.38 | 07-JUN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 445585.08 | 1825.07 | 31-JUL-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1305884.74 | 1614.20 | 23-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 86703407.79 | 5944.45 | 18-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.126332E+10 | 17180.55 | 30-OCT-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.271259E+10 | 17173.94 | 13-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.437918E+10 | 17169.46 | 27-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 445585.08 | 1571.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.437918E+10 | 17198.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.396611E+10 | 25619.80 | 30-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.281989E+10 | 25631.44 | 27-FEB-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.272453E+10 | 25602.02 | 06-MAR-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.546961E+09 | 25544.54 | 24-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.406896E+09 | 25570.15 | 15-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 35609702.29 | 8886.51 | 08-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7264534.42 | 2181.56 | 01-JUL-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2513416.63 | 649.94 | 24-AUG-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.112802E+09 | 3231.45 | 20-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143771E+10 | 25564.59 | 20-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.293344E+10 | 25613.82 | 13-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.523446E+10 | 25595.73 | 26-DEC-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.202282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2513416.63 | 649.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.523446E+10 | 25631.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.326587E+10 | 17421.87 | 30-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.216741E+10 | 17415.66 | 06-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174839E+10 | 17389.01 | 13-MAR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.314027E+09 | 14311.58 | 01-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.204376E+09 | 11741.07 | 05-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6315493.41 | 1795.43 | 08-JUN-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3219887.22 | 1174.93 | 01-JUL-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 142462.02 | 189.49 | 24-AUG-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.105059E+09 | 4006.35 | 07-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.109990E+10 | 17368.84 | 30-OCT-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.225630E+10 | 17418.44 | 13-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.375948E+10 | 17394.62 | 18-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.149305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 142462.02 | 189.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.375948E+10 | 17421.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.112910E+10 | 16127.68 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.614758E+09 | 11486.63 | 16-FEB-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.132305E+09 | 6946.02 | 08-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5146052.41 | 9803.33 | 08-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4344760.86 | 2554.53 | 06-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 226.93 | 0.38 | 10-JUN-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 736.44 | 0.68 | 29-JUL-06:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1653.50 | 1.37 | 23-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 35150.57 | 409.29 | 27-SEP-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1644692.38 | 3249.50 | 19-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 23177514.24 | 10798.94 | 29-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.344171E+09 | 9709.61 | 29-DEC-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.225468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 226.93 | 0.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.112910E+10 | 16127.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.469895E+10 | 0.469350E+10 | 83403.40 | 30-APR-15:12 | 83403.40 | 0.03 |
May | 0.00 | 0.00 | 0.577104E+10 | 0.577104E+10 | 101062.63 | 22-MAY-15:00 | 101062.63 | 0.07 |
June | 0.00 | 0.00 | 0.186705E+11 | 0.183866E+11 | 126264.58 | 13-JUN-16:00 | 115019.46 | 0.23 |
July | 0.00 | 0.00 | 0.320333E+11 | 0.319156E+11 | 121442.92 | 21-JUL-15:20 | 121442.92 | 0.40 |
August | 0.00 | 0.00 | 0.420379E+11 | 0.418832E+11 | 127047.73 | 14-AUG-15:10 | 127047.73 | 0.48 |
September | 0.00 | 0.00 | 0.197180E+11 | 0.196649E+11 | 91042.88 | 13-SEP-14:20 | 91042.88 | 0.27 |
October | 0.00 | 0.00 | 0.107330E+10 | 0.107330E+10 | 25714.58 | 11-OCT-15:00 | 25714.58 | 0.00 |
November | 0.00 | 0.00 | 13567362.30 | 13567362.30 | 8282.98 | 24-NOV-12:00 | 8282.98 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.124017E+12 | 0.123402E+12 | 0.13 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.420379E+11 | 0.418832E+11 | 127047.73 | 127047.73 | 0.48 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 50013.79 | 50013.79 | 3.62 | 02-JAN-05:20 | 3.62 | 0.00 |
February | 0.00 | 0.00 | 53685.99 | 53685.99 | 2.66 | 22-FEB-06:03 | 2.66 | 0.01 |
March | 0.00 | 0.00 | 83825.41 | 83825.41 | 4.17 | 27-MAR-05:02 | 4.17 | 0.00 |
April | 0.00 | 0.00 | 0.386430E+11 | 0.386237E+11 | 823661.06 | 30-APR-15:12 | 823661.06 | 0.03 |
May | 0.00 | 0.00 | 0.490828E+11 | 0.490828E+11 | 867273.71 | 22-MAY-15:00 | 867273.71 | 0.08 |
June | 0.00 | 0.00 | 0.154291E+12 | 0.152079E+12 | 1140253.53 | 13-JUN-16:00 | 1026187.06 | 0.23 |
July | 0.00 | 0.00 | 0.250011E+12 | 0.249749E+12 | 1078193.67 | 21-JUL-15:30 | 1078193.67 | 0.39 |
August | 0.00 | 0.00 | 0.314850E+12 | 0.314159E+12 | 1024779.59 | 14-AUG-15:40 | 1024779.59 | 0.48 |
September | 0.00 | 0.00 | 0.172191E+12 | 0.171167E+12 | 851809.15 | 13-SEP-14:40 | 851809.15 | 0.29 |
October | 0.00 | 0.00 | 0.900400E+10 | 0.900400E+10 | 228092.02 | 07-OCT-15:00 | 228092.02 | 0.01 |
November | 0.00 | 0.00 | 51926402.11 | 51926402.11 | 38544.45 | 24-NOV-12:00 | 38544.45 | 0.01 |
December | 0.00 | 0.00 | 56088.88 | 56088.88 | 3.76 | 11-DEC-05:52 | 3.76 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.988125E+12 | 0.983918E+12 | 0.13 | |||
Minimum of Months | 0.00 | 0.00 | 50013.79 | 50013.79 | 2.66 | 2.66 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.314850E+12 | 0.314159E+12 | 1140253.53 | 1078193.67 | 0.48 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.372357E+10 | 0.372357E+10 | 84581.73 | 30-APR-15:32 | 84581.73 | 0.03 |
May | 0.00 | 0.00 | 0.498357E+10 | 0.498357E+10 | 95263.14 | 22-MAY-15:00 | 95263.14 | 0.07 |
June | 0.00 | 0.00 | 0.159832E+11 | 0.157662E+11 | 132655.03 | 13-JUN-16:00 | 121884.08 | 0.21 |
July | 0.00 | 0.00 | 0.254910E+11 | 0.254727E+11 | 125461.13 | 21-JUL-15:30 | 125461.13 | 0.37 |
August | 0.00 | 0.00 | 0.302570E+11 | 0.302215E+11 | 116844.80 | 14-AUG-15:40 | 116844.80 | 0.46 |
September | 0.00 | 0.00 | 0.155879E+11 | 0.155431E+11 | 86922.98 | 13-SEP-14:50 | 86922.98 | 0.26 |
October | 0.00 | 0.00 | 0.635572E+09 | 0.635572E+09 | 21679.94 | 07-OCT-15:00 | 21679.94 | 0.00 |
November | 0.00 | 0.00 | 4561892.58 | 4561892.58 | 3487.25 | 24-NOV-12:00 | 3487.25 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.966663E+11 | 0.963509E+11 | 0.12 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.302570E+11 | 0.302215E+11 | 132655.03 | 125461.13 | 0.46 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 36600270.12 | 36600270.12 | 4589.48 | 25-JAN-15:00 | 4589.48 | 0.00 |
February | 0.00 | 0.00 | 10231437.37 | 10231437.37 | 4322.83 | 07-FEB-15:00 | 4322.83 | 0.00 |
March | 0.00 | 0.00 | 0.244250E+09 | 0.242978E+09 | 11734.98 | 18-MAR-06:13 | 5363.73 | 0.00 |
April | 0.00 | 0.00 | 0.114216E+10 | 0.114216E+10 | 32589.85 | 28-APR-15:00 | 32589.85 | 0.02 |
May | 0.00 | 0.00 | 0.375880E+10 | 0.373947E+10 | 61700.94 | 22-MAY-15:00 | 61700.94 | 0.08 |
June | 0.00 | 0.00 | 0.109175E+11 | 0.104489E+11 | 74791.42 | 27-JUN-06:23 | 29629.14 | 0.18 |
July | 0.00 | 0.00 | 0.189652E+11 | 0.175440E+11 | 82529.13 | 10-JUL-06:35 | 64093.17 | 0.28 |
August | 0.00 | 0.00 | 0.266857E+11 | 0.255918E+11 | 75324.19 | 14-AUG-13:10 | 70606.73 | 0.39 |
September | 0.00 | 0.00 | 0.118183E+11 | 0.116714E+11 | 61816.41 | 16-SEP-06:14 | 27963.90 | 0.20 |
October | 0.00 | 0.00 | 0.552948E+09 | 0.522043E+09 | 37519.60 | 20-OCT-06:12 | 18740.57 | 0.02 |
November | 0.00 | 0.00 | 49763889.70 | 41700750.73 | 32887.21 | 24-NOV-07:11 | 18150.21 | 0.00 |
December | 0.00 | 0.00 | 276615.73 | 276615.73 | 461.03 | 23-DEC-11:00 | 461.03 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.741817E+11 | 0.709915E+11 | 0.10 | |||
Minimum of Months | 0.00 | 0.00 | 276615.73 | 276615.73 | 461.03 | 461.03 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.266857E+11 | 0.255918E+11 | 82529.13 | 70606.73 | 0.39 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.383784E+10 | 0.383774E+10 | 3053.55 | 10-JAN-17:05 | 3053.55 | 0.00 |
February | 0.00 | 0.00 | 0.609449E+10 | 0.603894E+10 | 5067.51 | 20-FEB-16:03 | 5067.51 | 0.00 |
March | 0.00 | 0.00 | 0.108219E+11 | 0.104530E+11 | 5492.72 | 31-MAR-23:10 | 5492.72 | 0.00 |
April | 0.00 | 0.00 | 0.448575E+11 | 0.427937E+11 | 320463.21 | 30-APR-17:41 | 320463.21 | 0.00 |
May | 0.00 | 0.00 | 0.223940E+10 | 0.221967E+10 | 46321.86 | 22-MAY-15:00 | 42761.66 | 0.00 |
June | 0.00 | 0.00 | 0.184084E+11 | 0.157597E+11 | 227269.40 | 13-JUN-17:00 | 223825.62 | 0.00 |
July | 0.00 | 0.00 | 0.866000E+11 | 0.717615E+11 | 317886.71 | 21-JUL-16:00 | 317886.71 | 0.00 |
August | 0.00 | 0.00 | 0.285665E+12 | 0.212277E+12 | 412254.14 | 14-AUG-17:00 | 412254.14 | 0.00 |
September | 0.00 | 0.00 | 0.960196E+09 | 0.929773E+09 | 17219.81 | 27-SEP-16:00 | 17219.81 | 0.00 |
October | 0.00 | 0.00 | 0.311770E+10 | 0.304440E+10 | 5330.38 | 31-OCT-23:10 | 5290.45 | 0.00 |
November | 0.00 | 0.00 | 0.742988E+10 | 0.707765E+10 | 5376.21 | 16-NOV-22:50 | 5281.20 | 0.00 |
December | 0.00 | 0.00 | 0.140647E+11 | 0.131705E+11 | 5983.72 | 22-DEC-00:50 | 5488.93 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.484096E+12 | 0.389363E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.960196E+09 | 0.929773E+09 | 3053.55 | 3053.55 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.285665E+12 | 0.212277E+12 | 412254.14 | 412254.14 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.425415E+10 | 0.425267E+10 | 2401.57 | 01-JAN-16:10 | 2395.92 | 0.00 |
February | 0.00 | 0.00 | 0.874401E+10 | 0.874274E+10 | 4559.60 | 19-FEB-17:10 | 4559.60 | 0.00 |
March | 0.00 | 0.00 | 0.150820E+11 | 0.150817E+11 | 7606.47 | 31-MAR-24:00 | 7606.47 | 0.00 |
April | 0.00 | 0.00 | 0.200811E+11 | 0.200805E+11 | 9041.68 | 30-APR-18:10 | 9041.68 | 0.00 |
May | 0.00 | 0.00 | 0.548176E+10 | 0.546199E+10 | 3956.82 | 31-MAY-24:00 | 3956.82 | 0.00 |
June | 0.00 | 0.00 | 0.106079E+11 | 0.105232E+11 | 5793.01 | 30-JUN-24:00 | 5793.01 | 0.00 |
July | 0.00 | 0.00 | 0.162150E+11 | 0.161034E+11 | 7847.20 | 31-JUL-24:00 | 7847.20 | 0.00 |
August | 0.00 | 0.00 | 0.212362E+11 | 0.210980E+11 | 8841.59 | 13-AUG-18:14 | 8816.67 | 0.00 |
September | 0.00 | 0.00 | 0.547658E+10 | 0.541217E+10 | 3821.48 | 30-SEP-24:00 | 3821.48 | 0.00 |
October | 0.00 | 0.00 | 0.102865E+11 | 0.102603E+11 | 5667.40 | 31-OCT-24:00 | 5667.40 | 0.00 |
November | 0.00 | 0.00 | 0.146259E+11 | 0.146103E+11 | 6227.30 | 19-NOV-16:00 | 6227.30 | 0.00 |
December | 0.00 | 0.00 | 0.198916E+11 | 0.198915E+11 | 7984.32 | 25-DEC-15:10 | 7984.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.151983E+12 | 0.151518E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.425415E+10 | 0.425267E+10 | 2401.57 | 2395.92 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.212362E+11 | 0.210980E+11 | 9041.68 | 9041.68 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.225841E+11 | 0.225698E+11 | 19795.60 | 19-JAN-16:20 | 19795.60 | 0.00 |
February | 0.00 | 0.00 | 0.681566E+11 | 0.681436E+11 | 40747.89 | 27-FEB-17:00 | 40747.89 | 0.00 |
March | 0.00 | 0.00 | 0.127996E+12 | 0.127993E+12 | 68370.37 | 31-MAR-23:40 | 68370.37 | 0.00 |
April | 0.00 | 0.00 | 0.184102E+12 | 0.184095E+12 | 85131.53 | 30-APR-18:10 | 85131.53 | 0.00 |
May | 0.00 | 0.00 | 0.453305E+11 | 0.451354E+11 | 36313.26 | 31-MAY-23:40 | 36313.26 | 0.00 |
June | 0.00 | 0.00 | 0.967459E+11 | 0.959053E+11 | 52787.29 | 30-JUN-24:00 | 52787.29 | 0.00 |
July | 0.00 | 0.00 | 0.150458E+12 | 0.149350E+12 | 73693.06 | 31-JUL-23:50 | 73693.06 | 0.00 |
August | 0.00 | 0.00 | 0.198835E+12 | 0.197467E+12 | 82550.22 | 13-AUG-18:03 | 82322.88 | 0.00 |
September | 0.00 | 0.00 | 0.456480E+11 | 0.450202E+11 | 34117.59 | 30-SEP-23:30 | 34117.59 | 0.00 |
October | 0.00 | 0.00 | 0.851235E+11 | 0.848642E+11 | 49067.13 | 31-OCT-24:00 | 49067.13 | 0.00 |
November | 0.00 | 0.00 | 0.121813E+12 | 0.121656E+12 | 56449.69 | 10-NOV-16:10 | 56231.99 | 0.00 |
December | 0.00 | 0.00 | 0.166467E+12 | 0.166466E+12 | 70750.42 | 21-DEC-15:20 | 70750.42 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.131326E+13 | 0.130867E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.225841E+11 | 0.225698E+11 | 19795.60 | 19795.60 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.198835E+12 | 0.197467E+12 | 85131.53 | 85131.53 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.721067E+09 | 0.720154E+09 | 1881.85 | 19-JAN-16:30 | 1881.85 | 0.00 |
February | 0.00 | 0.00 | 0.512921E+10 | 0.512798E+10 | 3858.27 | 27-FEB-17:00 | 3858.27 | 0.00 |
March | 0.00 | 0.00 | 0.112792E+11 | 0.112789E+11 | 6390.32 | 31-MAR-23:20 | 6390.32 | 0.00 |
April | 0.00 | 0.00 | 0.176189E+11 | 0.176182E+11 | 8629.84 | 30-APR-18:00 | 8629.84 | 0.00 |
May | 0.00 | 0.00 | 0.382618E+10 | 0.380683E+10 | 3491.95 | 31-MAY-23:20 | 3491.95 | 0.00 |
June | 0.00 | 0.00 | 0.932354E+10 | 0.923966E+10 | 5044.49 | 30-JUN-23:30 | 5044.49 | 0.00 |
July | 0.00 | 0.00 | 0.147640E+11 | 0.146534E+11 | 7221.71 | 31-JUL-23:20 | 7221.71 | 0.00 |
August | 0.00 | 0.00 | 0.195761E+11 | 0.194395E+11 | 8344.49 | 13-AUG-17:52 | 8321.97 | 0.00 |
September | 0.00 | 0.00 | 0.390848E+10 | 0.384667E+10 | 2889.09 | 30-SEP-23:20 | 2889.09 | 0.00 |
October | 0.00 | 0.00 | 0.708509E+10 | 0.705978E+10 | 4398.28 | 31-OCT-23:20 | 4398.28 | 0.00 |
November | 0.00 | 0.00 | 0.104638E+11 | 0.104484E+11 | 5578.91 | 10-NOV-16:10 | 5557.34 | 0.00 |
December | 0.00 | 0.00 | 0.146742E+11 | 0.146740E+11 | 6855.48 | 21-DEC-15:20 | 6855.48 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.118370E+12 | 0.117914E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.721067E+09 | 0.720154E+09 | 1881.85 | 1881.85 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.195761E+11 | 0.194395E+11 | 8629.84 | 8629.84 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 77369.01 | 1020629.72 | 03-JAN-06:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 54547.97 | 1020227.09 | 17-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 34125.24 | 1014600.53 | 27-MAR-05:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4175.74 | 256250.92 | 01-APR-05:02 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 1282.34 | 235608.74 | 05-MAY-05:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 24.37 | 12552.97 | 08-JUN-05:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 4.46 | 3129.14 | 31-JUL-05:08 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 1.63 | 1613.22 | 23-AUG-05:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 319.69 | 71358.10 | 21-SEP-06:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 9306.19 | 564680.93 | 23-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 36890.05 | 1213381.79 | 27-NOV-05:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 84012.23 | 1126112.50 | 26-DEC-05:11 |
Annual Sum or Average | 0.00 | 25092.53 | ||||
Minimum of Months | 0.00 | 0.00 | 1.63 | 1613.22 | ||
Maximum of Months | 0.00 | 0.00 | 84012.23 | 1213381.79 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 54.42 | 5003.83 | 25-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 98.49 | 5182.25 | 07-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 247.46 | 14904.98 | 18-MAR-06:13 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 18783.01 | 784498.20 | 28-APR-15:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 24172.24 | 1127863.51 | 22-MAY-14:10 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 79953.18 | 1464382.51 | 13-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 125149.26 | 1388364.67 | 21-JUL-15:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 157182.29 | 1337707.08 | 14-AUG-15:40 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 87087.93 | 1134218.02 | 25-SEP-15:40 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 4412.66 | 271522.39 | 07-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 86.06 | 54360.38 | 24-NOV-12:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 61.97 | 3130.72 | 23-DEC-11:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 41725.35 | 0.00 | ||||
Minimum of Months | 54.42 | 3130.72 | 0.00 | 0.00 | ||
Maximum of Months | 157182.29 | 1464382.51 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 5.05 | 2192.18 | 25-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 2.65 | 2455.48 | 07-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 77.85 | 17194.16 | 18-MAR-06:12 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 18812.46 | 1129782.65 | 30-APR-15:51 | 0.00 | 0.00 | 01-APR-00:10 |
May | 23944.98 | 1314769.56 | 22-MAY-13:40 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 80185.81 | 1829311.33 | 21-JUN-15:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 125323.58 | 1731008.65 | 10-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 156079.85 | 1578998.14 | 28-AUG-13:40 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 86887.25 | 1302065.66 | 12-SEP-15:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 4214.56 | 273201.73 | 07-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 45.38 | 55363.08 | 24-NOV-12:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.10 | 371.55 | 23-DEC-11:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 41580.89 | 0.00 | ||||
Minimum of Months | 0.10 | 371.55 | 0.00 | 0.00 | ||
Maximum of Months | 156079.85 | 1829311.33 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 19286.98 | 34754.56 | 19-JAN-16:30 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 49904.50 | 68375.96 | 17-FEB-17:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 80742.18 | 112859.00 | 31-MAR-23:40 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 142130.58 | 1083237.52 | 30-APR-18:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 34039.94 | 447433.32 | 22-MAY-15:00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 90307.44 | 991414.78 | 13-JUN-17:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 176645.55 | 1377485.67 | 22-JUL-18:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 318842.90 | 1423828.72 | 14-AUG-17:20 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 45197.08 | 343471.54 | 13-SEP-16:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 53020.98 | 118130.44 | 07-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 77771.99 | 94368.30 | 03-NOV-16:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 103580.56 | 114830.98 | 18-DEC-15:20 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 99809.51 | 0.00 | ||||
Minimum of Months | 19286.98 | 34754.56 | 0.00 | 0.00 | ||
Maximum of Months | 318842.90 | 1423828.72 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 14672.84 | 52248.24 | 31-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 14859.04 | 52330.96 | 14-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15688.43 | 52245.65 | 01-MAR-13:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 14420.48 | 51469.90 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 14512.95 | 50340.28 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14472.80 | 48910.01 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 13036.65 | 47643.83 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 14169.97 | 46995.40 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 13376.29 | 47647.93 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 13634.04 | 48915.73 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14208.61 | 50301.10 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14049.77 | 51474.64 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 14255.08 | ||||
Minimum of Months | 0.00 | 0.00 | 13036.65 | 46995.40 | ||
Maximum of Months | 0.00 | 0.00 | 15688.43 | 52330.96 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 3.01 | 5015.34 | 26-JAN-06:40 | 482.55 | 104297.98 | 31-JAN-05:43 |
February | 10.18 | 7399.21 | 24-FEB-06:30 | 998.36 | 104845.04 | 17-FEB-13:50 |
March | 16.84 | 13563.30 | 23-MAR-13:50 | 1823.39 | 104286.97 | 08-MAR-06:02 |
April | 20951.58 | 898259.78 | 28-APR-15:00 | 605.23 | 91359.81 | 05-APR-05:40 |
May | 27625.25 | 1907211.01 | 22-MAY-14:10 | 1711.78 | 81857.19 | 10-MAY-09:50 |
June | 98755.03 | 2230421.44 | 13-JUN-16:00 | 1148.38 | 78243.20 | 01-JUN-05:40 |
July | 148885.19 | 1990698.66 | 21-JUL-10:40 | 1059.50 | 63189.19 | 03-JUL-12:10 |
August | 184734.76 | 2041811.99 | 14-AUG-12:10 | 558.68 | 69779.67 | 28-AUG-05:40 |
September | 101370.75 | 1878382.75 | 13-SEP-14:40 | 910.97 | 82320.39 | 08-SEP-06:12 |
October | 4394.72 | 311525.09 | 07-OCT-15:10 | 925.25 | 94543.24 | 23-OCT-05:40 |
November | 23.83 | 33304.53 | 24-NOV-11:50 | 325.91 | 100466.69 | 16-NOV-06:50 |
December | 4.75 | 6318.55 | 18-DEC-07:00 | 612.21 | 107988.16 | 15-DEC-06:50 |
Annual Sum or Average | 49229.92 | 931.62 | ||||
Minimum of Months | 3.01 | 5015.34 | 325.91 | 63189.19 | ||
Maximum of Months | 184734.76 | 2230421.44 | 1823.39 | 107988.16 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.432764E+10 | 0.32 | 12779.95 | 10-JAN-06:01 | 1.33 |
February | 0.444314E+10 | 0.34 | 9230.77 | 01-FEB-06:03 | 1.09 |
March | 0.566345E+10 | 0.38 | 9950.29 | 18-MAR-05:02 | 1.13 |
April | 0.995246E+10 | 0.52 | 19763.87 | 28-APR-14:40 | 1.74 |
May | 0.787898E+10 | 0.45 | 14926.85 | 22-MAY-14:50 | 1.45 |
June | 0.100107E+11 | 0.53 | 17507.97 | 26-JUN-15:20 | 1.60 |
July | 0.117912E+11 | 0.57 | 20460.16 | 10-JUL-13:50 | 1.78 |
August | 0.137083E+11 | 0.64 | 20460.16 | 14-AUG-14:00 | 1.78 |
September | 0.865715E+10 | 0.48 | 16546.81 | 11-SEP-14:40 | 1.55 |
October | 0.642553E+10 | 0.39 | 13847.56 | 03-OCT-14:40 | 1.40 |
November | 0.527190E+10 | 0.36 | 10898.85 | 06-NOV-05:11 | 1.20 |
December | 0.491308E+10 | 0.34 | 11195.30 | 26-DEC-06:03 | 1.22 |
Annual Sum or Average | 0.930435E+11 | 0.44 | |||
Minimum of Months | 0.432764E+10 | 0.32 | 9230.77 | 1.09 | |
Maximum of Months | 0.137083E+11 | 0.64 | 20460.16 | 1.78 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.323183E+11 | 0.31 | 90561.95 | 26-JAN-06:02 | 1.15 |
February | 0.314761E+11 | 0.32 | 92104.71 | 24-FEB-06:02 | 1.17 |
March | 0.357833E+11 | 0.33 | 96747.66 | 22-MAR-05:02 | 1.20 |
April | 0.590696E+11 | 0.41 | 155342.34 | 28-APR-14:50 | 1.61 |
May | 0.621451E+11 | 0.42 | 128926.06 | 23-MAY-15:20 | 1.43 |
June | 0.743269E+11 | 0.47 | 157292.49 | 26-JUN-05:02 | 1.62 |
July | 0.790421E+11 | 0.48 | 154216.55 | 21-JUL-15:30 | 1.60 |
August | 0.876700E+11 | 0.51 | 150947.47 | 14-AUG-15:20 | 1.57 |
September | 0.700603E+11 | 0.45 | 155626.29 | 12-SEP-15:20 | 1.60 |
October | 0.440809E+11 | 0.34 | 107069.31 | 03-OCT-15:00 | 1.28 |
November | 0.326187E+11 | 0.31 | 124316.40 | 17-NOV-06:02 | 1.40 |
December | 0.304417E+11 | 0.30 | 41021.95 | 07-DEC-06:02 | 0.74 |
Annual Sum or Average | 0.639033E+12 | 0.39 | |||
Minimum of Months | 0.304417E+11 | 0.30 | 41021.95 | 0.74 | |
Maximum of Months | 0.876700E+11 | 0.51 | 157292.49 | 1.62 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.313063E+10 | 0.30 | 4945.30 | 02-JAN-04:01 | 0.75 |
February | 0.278607E+10 | 0.29 | 4945.30 | 06-FEB-05:11 | 0.75 |
March | 0.311317E+10 | 0.30 | 4945.30 | 06-MAR-05:11 | 0.75 |
April | 0.441641E+10 | 0.33 | 14569.63 | 28-APR-15:20 | 1.42 |
May | 0.493368E+10 | 0.35 | 13421.02 | 23-MAY-15:20 | 1.35 |
June | 0.623802E+10 | 0.40 | 16859.53 | 13-JUN-15:30 | 1.55 |
July | 0.681771E+10 | 0.40 | 15912.15 | 21-JUL-15:30 | 1.50 |
August | 0.715452E+10 | 0.43 | 14851.49 | 14-AUG-15:20 | 1.44 |
September | 0.529178E+10 | 0.36 | 14409.08 | 12-SEP-15:10 | 1.41 |
October | 0.327109E+10 | 0.29 | 7130.17 | 03-OCT-14:40 | 0.92 |
November | 0.284581E+10 | 0.28 | 4945.30 | 13-NOV-05:11 | 0.75 |
December | 0.311888E+10 | 0.30 | 4945.30 | 04-DEC-05:11 | 0.75 |
Annual Sum or Average | 0.531178E+11 | 0.34 | |||
Minimum of Months | 0.278607E+10 | 0.28 | 4945.30 | 0.75 | |
Maximum of Months | 0.715452E+10 | 0.43 | 16859.53 | 1.55 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.514314E+10 | 0.41 | 12116.26 | 02-JAN-07:05 | 1.79 |
February | 0.453090E+10 | 0.41 | 12116.26 | 01-FEB-07:05 | 1.80 |
March | 0.650901E+10 | 0.49 | 12116.26 | 01-MAR-07:05 | 1.80 |
April | 0.136768E+11 | 0.81 | 12116.26 | 01-APR-06:05 | 1.80 |
May | 0.106722E+11 | 0.66 | 12116.26 | 01-MAY-06:05 | 1.80 |
June | 0.143850E+11 | 0.85 | 12116.26 | 01-JUN-06:10 | 1.79 |
July | 0.126971E+11 | 0.73 | 12116.26 | 01-JUL-06:05 | 1.79 |
August | 0.135161E+11 | 0.80 | 12116.26 | 01-AUG-06:05 | 1.79 |
September | 0.137598E+11 | 0.81 | 12116.26 | 01-SEP-06:10 | 1.79 |
October | 0.124858E+11 | 0.73 | 12116.26 | 02-OCT-06:10 | 1.79 |
November | 0.115432E+11 | 0.71 | 12116.26 | 01-NOV-06:05 | 1.80 |
December | 0.632950E+10 | 0.46 | 12116.26 | 01-DEC-07:05 | 1.80 |
Annual Sum or Average | 0.125248E+12 | 0.66 | |||
Minimum of Months | 0.453090E+10 | 0.41 | 12116.26 | 1.79 | |
Maximum of Months | 0.143850E+11 | 0.85 | 12116.26 | 1.80 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.109506E+12 | 1.36 | 40884.90 | 01-JAN-00:05 | 1.36 |
February | 0.989088E+11 | 1.36 | 40884.90 | 01-FEB-00:10 | 1.36 |
March | 0.109506E+12 | 1.36 | 40884.90 | 01-MAR-00:10 | 1.36 |
April | 0.105974E+12 | 1.36 | 40884.90 | 01-APR-00:10 | 1.37 |
May | 0.109506E+12 | 1.36 | 40884.90 | 01-MAY-00:07 | 1.36 |
June | 0.105974E+12 | 1.36 | 40884.90 | 01-JUN-00:10 | 1.36 |
July | 0.109506E+12 | 1.36 | 40884.90 | 01-JUL-00:10 | 1.36 |
August | 0.109506E+12 | 1.36 | 40884.90 | 01-AUG-00:10 | 1.36 |
September | 0.105974E+12 | 1.36 | 40884.90 | 01-SEP-00:10 | 1.36 |
October | 0.109506E+12 | 1.36 | 40884.90 | 01-OCT-00:10 | 1.36 |
November | 0.105974E+12 | 1.36 | 40884.90 | 01-NOV-00:10 | 1.36 |
December | 0.109506E+12 | 1.36 | 40884.90 | 01-DEC-00:10 | 1.36 |
Annual Sum or Average | 0.128935E+13 | 1.36 | |||
Minimum of Months | 0.989088E+11 | 1.36 | 40884.90 | 1.36 | |
Maximum of Months | 0.109506E+12 | 1.36 | 40884.90 | 1.37 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.153606E+10 | 0.93 | 573.50 | 01-JAN-00:05 | 0.92 |
February | 0.138741E+10 | 0.93 | 573.50 | 01-FEB-00:10 | 0.93 |
March | 0.153606E+10 | 0.93 | 573.50 | 01-MAR-00:10 | 0.92 |
April | 0.148651E+10 | 0.93 | 573.50 | 01-APR-00:10 | 0.93 |
May | 0.153606E+10 | 0.92 | 573.50 | 01-MAY-00:03 | 0.92 |
June | 0.148651E+10 | 0.92 | 573.50 | 01-JUN-00:10 | 0.92 |
July | 0.153606E+10 | 0.92 | 573.50 | 01-JUL-00:10 | 0.92 |
August | 0.153606E+10 | 0.92 | 573.50 | 01-AUG-00:10 | 0.92 |
September | 0.148651E+10 | 0.92 | 573.50 | 01-SEP-00:10 | 0.92 |
October | 0.153606E+10 | 0.92 | 573.50 | 01-OCT-00:10 | 0.93 |
November | 0.148651E+10 | 0.92 | 573.50 | 01-NOV-00:10 | 0.93 |
December | 0.153606E+10 | 0.93 | 573.50 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.180858E+11 | 0.92 | |||
Minimum of Months | 0.138741E+10 | 0.92 | 573.50 | 0.92 | |
Maximum of Months | 0.153606E+10 | 0.93 | 573.50 | 0.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.147562E+11 | 0.93 | 5509.32 | 01-JAN-00:05 | 0.92 |
February | 0.133281E+11 | 0.93 | 5509.32 | 01-FEB-00:20 | 0.93 |
March | 0.147562E+11 | 0.93 | 5509.32 | 01-MAR-00:10 | 0.92 |
April | 0.142802E+11 | 0.93 | 5509.32 | 01-APR-00:10 | 0.93 |
May | 0.147562E+11 | 0.92 | 5509.32 | 01-MAY-00:03 | 0.92 |
June | 0.142802E+11 | 0.92 | 5509.32 | 01-JUN-00:10 | 0.92 |
July | 0.147562E+11 | 0.92 | 5509.32 | 01-JUL-00:10 | 0.92 |
August | 0.147562E+11 | 0.92 | 5509.32 | 01-AUG-00:10 | 0.92 |
September | 0.142802E+11 | 0.92 | 5509.32 | 01-SEP-00:10 | 0.92 |
October | 0.147562E+11 | 0.92 | 5509.32 | 01-OCT-00:10 | 0.93 |
November | 0.142802E+11 | 0.92 | 5509.32 | 01-NOV-00:10 | 0.93 |
December | 0.147562E+11 | 0.93 | 5509.32 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.173742E+12 | 0.92 | |||
Minimum of Months | 0.133281E+11 | 0.92 | 5509.32 | 0.92 | |
Maximum of Months | 0.147562E+11 | 0.93 | 5509.32 | 0.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.149492E+10 | 0.93 | 558.14 | 01-JAN-00:05 | 0.92 |
February | 0.135025E+10 | 0.93 | 558.14 | 01-FEB-00:10 | 0.93 |
March | 0.149492E+10 | 0.93 | 558.14 | 01-MAR-00:10 | 0.92 |
April | 0.144669E+10 | 0.93 | 558.14 | 01-APR-00:10 | 0.93 |
May | 0.149492E+10 | 0.92 | 558.14 | 01-MAY-00:03 | 0.92 |
June | 0.144669E+10 | 0.92 | 558.14 | 01-JUN-00:10 | 0.92 |
July | 0.149492E+10 | 0.92 | 558.14 | 01-JUL-00:10 | 0.92 |
August | 0.149492E+10 | 0.92 | 558.14 | 01-AUG-00:10 | 0.92 |
September | 0.144669E+10 | 0.92 | 558.14 | 01-SEP-00:10 | 0.92 |
October | 0.149492E+10 | 0.92 | 558.14 | 01-OCT-00:10 | 0.93 |
November | 0.144669E+10 | 0.92 | 558.14 | 01-NOV-00:20 | 0.93 |
December | 0.149492E+10 | 0.93 | 558.14 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.176014E+11 | 0.92 | |||
Minimum of Months | 0.135025E+10 | 0.92 | 558.14 | 0.92 | |
Maximum of Months | 0.149492E+10 | 0.93 | 558.14 | 0.93 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 17475341.49 | 15727807.34 | 371.59 | 10-JAN-06:01 | 334.43 | 334.43 | 39.98 | 5.36 |
February | 8583220.57 | 7724898.51 | 350.05 | 17-FEB-06:01 | 315.05 | 315.05 | 35.29 | 5.23 |
March | 4868312.46 | 4381481.21 | 342.69 | 06-MAR-06:02 | 308.42 | 308.42 | 38.70 | 5.17 |
April | 412159.34 | 370943.41 | 17.25 | 01-APR-05:02 | 15.53 | 15.53 | 26.19 | 1.10 |
May | 106190.82 | 95571.73 | 14.41 | 05-MAY-05:03 | 12.97 | 12.97 | 24.76 | 0.99 |
June | 1564.56 | 1408.11 | 0.32 | 08-JUN-05:03 | 0.29 | 0.29 | 20.96 | 0.05 |
July | 290.91 | 261.82 | 0.08 | 31-JUL-05:08 | 0.07 | 0.07 | 20.77 | 0.01 |
August | 105.56 | 95.00 | 0.04 | 23-AUG-05:10 | 0.04 | 0.04 | 20.73 | 0.01 |
September | 22634.23 | 20370.80 | 2.42 | 21-SEP-06:10 | 2.18 | 2.18 | 22.13 | 0.28 |
October | 985535.53 | 886981.98 | 85.53 | 23-OCT-05:03 | 76.98 | 76.98 | 31.15 | 2.66 |
November | 5970000.55 | 5373000.49 | 347.66 | 27-NOV-06:03 | 312.89 | 312.89 | 39.72 | 5.20 |
December | 17279870.92 | 15551883.82 | 357.31 | 11-DEC-06:03 | 321.58 | 321.58 | 42.04 | 5.26 |
Annual Sum or Average | 55705226.93 | 50134704.24 | ||||||
Minimum of Months | 105.56 | 95.00 | 0.04 | 0.04 | 0.04 | 20.73 | 0.01 | |
Maximum of Months | 17475341.49 | 15727807.34 | 371.59 | 334.43 | 334.43 | 42.04 | 5.36 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 13080.41 | 11772.37 | 2.00 | 25-JAN-14:00 | 1.80 | 1.80 | 6.70 | 0.50 |
February | 3090.33 | 2781.29 | 1.22 | 07-FEB-15:00 | 1.09 | 1.09 | 6.70 | 0.32 |
March | 52826.62 | 47543.96 | 6.47 | 18-MAR-06:13 | 5.82 | 5.82 | 6.70 | 1.30 |
April | 35643263.74 | 32078937.36 | 3218.44 | 28-APR-14:30 | 2896.60 | 2896.60 | 8.11 | 36.59 |
May | 56899353.53 | 51209418.17 | 3707.82 | 22-MAY-13:40 | 3337.04 | 3337.04 | 8.66 | 38.79 |
June | 0.214881E+09 | 0.193393E+09 | 8873.87 | 21-JUN-15:20 | 7986.49 | 7986.49 | 11.11 | 55.01 |
July | 0.322131E+09 | 0.289918E+09 | 7809.29 | 10-JUL-14:00 | 7028.36 | 7028.36 | 10.91 | 52.31 |
August | 0.337325E+09 | 0.303592E+09 | 5950.35 | 21-AUG-12:10 | 5355.31 | 5355.31 | 9.43 | 46.96 |
September | 0.220965E+09 | 0.198868E+09 | 3137.55 | 12-SEP-15:30 | 2823.79 | 2823.79 | 8.55 | 36.21 |
October | 2509655.60 | 2258690.04 | 73.25 | 11-OCT-15:20 | 65.92 | 65.92 | 6.70 | 6.16 |
November | 35551.85 | 31996.66 | 18.86 | 24-NOV-07:15 | 16.97 | 16.97 | 6.70 | 2.74 |
December | 40.66 | 36.59 | 0.06 | 23-DEC-11:00 | 0.05 | 0.05 | 6.70 | 0.02 |
Annual Sum or Average | 0.119046E+10 | 0.107141E+10 | ||||||
Minimum of Months | 40.66 | 36.59 | 0.06 | 0.05 | 0.05 | 6.70 | 0.02 | |
Maximum of Months | 0.337325E+09 | 0.303592E+09 | 8873.87 | 7986.49 | 7986.49 | 11.11 | 55.01 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.147308E+09 | 0.132577E+09 | 3147.60 | 19-JAN-11:40 | 2832.84 | 2832.84 | 6.72 | 27.84 |
February | 0.257631E+09 | 0.231868E+09 | 3147.60 | 01-FEB-15:20 | 2832.84 | 2832.84 | 6.72 | 27.84 |
March | 0.504812E+09 | 0.454330E+09 | 3147.60 | 01-MAR-15:10 | 2832.84 | 2832.84 | 6.72 | 27.84 |
April | 0.815799E+09 | 0.734219E+09 | 3147.60 | 01-APR-16:13 | 2832.84 | 2832.84 | 6.73 | 27.84 |
May | 0.130183E+10 | 0.117165E+10 | 3147.60 | 03-MAY-05:03 | 2832.84 | 2832.84 | 6.73 | 27.84 |
June | 0.235705E+10 | 0.212134E+10 | 3147.60 | 01-JUN-05:02 | 2832.84 | 2832.84 | 6.73 | 27.84 |
July | 0.392865E+10 | 0.353579E+10 | 3147.60 | 01-JUL-05:08 | 2832.84 | 2832.84 | 6.79 | 27.84 |
August | 0.461469E+10 | 0.415322E+10 | 3147.60 | 01-AUG-04:12 | 2832.84 | 2832.84 | 6.88 | 27.84 |
September | 0.279411E+10 | 0.251470E+10 | 3147.60 | 01-SEP-04:12 | 2832.84 | 2832.84 | 7.06 | 27.84 |
October | 0.595301E+09 | 0.535770E+09 | 3147.60 | 01-OCT-11:02 | 2832.84 | 2832.84 | 7.09 | 27.84 |
November | 0.117172E+09 | 0.105454E+09 | 3147.60 | 03-NOV-05:40 | 2832.84 | 2832.84 | 6.72 | 27.84 |
December | 0.184134E+09 | 0.165721E+09 | 3147.60 | 04-DEC-05:11 | 2832.84 | 2832.84 | 6.72 | 27.84 |
Annual Sum or Average | 0.176185E+11 | 0.158566E+11 | ||||||
Minimum of Months | 0.117172E+09 | 0.105454E+09 | 3147.60 | 2832.84 | 2832.84 | 6.72 | 27.84 | |
Maximum of Months | 0.461469E+10 | 0.415322E+10 | 3147.60 | 2832.84 | 2832.84 | 7.09 | 27.84 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 6.70 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 6.73 | 0.00 |
May | 24551256.84 | 22096131.15 | 3147.60 | 22-MAY-14:00 | 2832.84 | 2832.84 | 15.21 | 13.92 |
June | 0.177524E+09 | 0.159772E+09 | 3147.60 | 12-JUN-12:40 | 2832.84 | 2832.84 | 15.66 | 13.92 |
July | 0.185079E+09 | 0.166571E+09 | 3147.60 | 10-JUL-08:50 | 2832.84 | 2832.84 | 15.42 | 13.92 |
August | 0.135976E+09 | 0.122379E+09 | 3147.60 | 14-AUG-10:10 | 2832.84 | 2832.84 | 15.67 | 13.92 |
September | 0.126533E+09 | 0.113880E+09 | 3147.60 | 11-SEP-13:50 | 2832.84 | 2832.84 | 15.33 | 13.92 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
Annual Sum or Average | 0.649664E+09 | 0.584698E+09 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 | |
Maximum of Months | 0.185079E+09 | 0.166571E+09 | 3147.60 | 2832.84 | 2832.84 | 15.67 | 13.92 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.101057E+11 | 0.909515E+10 | 3773.04 | 01-JAN-00:05 | 3395.74 | 3395.74 | 18.59 | 15.76 |
February | 0.912775E+10 | 0.821497E+10 | 3773.04 | 01-FEB-00:10 | 3395.74 | 3395.74 | 19.16 | 15.76 |
March | 0.101057E+11 | 0.909515E+10 | 3773.04 | 01-MAR-00:10 | 3395.74 | 3395.74 | 19.73 | 15.76 |
April | 0.977973E+10 | 0.880176E+10 | 3773.04 | 01-APR-00:10 | 3395.74 | 3395.74 | 20.39 | 15.76 |
May | 0.101057E+11 | 0.909515E+10 | 3773.04 | 01-MAY-00:03 | 3395.74 | 3395.74 | 19.02 | 15.76 |
June | 0.977973E+10 | 0.880176E+10 | 3773.04 | 01-JUN-00:10 | 3395.74 | 3395.74 | 19.44 | 15.76 |
July | 0.101057E+11 | 0.909515E+10 | 3773.04 | 01-JUL-00:10 | 3395.74 | 3395.74 | 19.82 | 15.76 |
August | 0.101057E+11 | 0.909515E+10 | 3773.04 | 01-AUG-00:10 | 3395.74 | 3395.74 | 20.37 | 15.76 |
September | 0.977973E+10 | 0.880176E+10 | 3773.04 | 01-SEP-00:10 | 3395.74 | 3395.74 | 18.93 | 15.76 |
October | 0.101057E+11 | 0.909515E+10 | 3773.04 | 01-OCT-00:10 | 3395.74 | 3395.74 | 19.39 | 15.76 |
November | 0.977973E+10 | 0.880176E+10 | 3773.04 | 01-NOV-00:10 | 3395.74 | 3395.74 | 19.87 | 15.76 |
December | 0.101057E+11 | 0.909515E+10 | 3773.04 | 01-DEC-00:10 | 3395.74 | 3395.74 | 20.22 | 15.76 |
Annual Sum or Average | 0.118987E+12 | 0.107088E+12 | ||||||
Minimum of Months | 0.912775E+10 | 0.821497E+10 | 3773.04 | 3395.74 | 3395.74 | 18.59 | 15.76 | |
Maximum of Months | 0.101057E+11 | 0.909515E+10 | 3773.04 | 3395.74 | 3395.74 | 20.39 | 15.76 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 56.90 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:03 | 16.86 | 16.86 | 56.93 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:03 | 16.86 | 16.86 | 56.93 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:02 | 16.86 | 16.86 | 57.04 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:02 | 16.86 | 16.86 | 57.31 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:02 | 16.86 | 16.86 | 57.19 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 57.20 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 57.17 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 57.17 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 56.96 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:02 | 16.86 | 16.86 | 57.19 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:03 | 16.86 | 16.86 | 57.04 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 56.90 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.31 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.578921E+09 | 0.521029E+09 | 12371.49 | 26-JAN-06:40 | 11134.34 | 11134.34 | 21.12 | 50.15 |
February | 0.101249E+10 | 0.911239E+09 | 12371.59 | 24-FEB-06:30 | 11134.43 | 11134.43 | 21.14 | 50.15 |
March | 0.198390E+10 | 0.178551E+10 | 12371.85 | 23-MAR-13:50 | 11134.66 | 11134.66 | 21.16 | 50.15 |
April | 0.320865E+10 | 0.288778E+10 | 12410.04 | 28-APR-15:00 | 11169.04 | 11169.04 | 25.39 | 50.15 |
May | 0.521617E+10 | 0.469455E+10 | 24825.67 | 22-MAY-14:10 | 22343.10 | 22343.10 | 25.65 | 100.31 |
June | 0.992819E+10 | 0.893537E+10 | 24841.71 | 13-JUN-16:00 | 22357.54 | 22357.54 | 26.42 | 100.31 |
July | 0.161335E+11 | 0.145202E+11 | 24829.81 | 21-JUL-10:40 | 22346.83 | 22346.83 | 25.85 | 100.31 |
August | 0.186411E+11 | 0.167770E+11 | 24832.35 | 14-AUG-12:10 | 22349.11 | 22349.11 | 25.97 | 100.31 |
September | 0.114087E+11 | 0.102679E+11 | 24824.24 | 13-SEP-14:40 | 22341.81 | 22341.81 | 25.58 | 100.31 |
October | 0.234016E+10 | 0.210614E+10 | 12384.50 | 07-OCT-15:10 | 11146.05 | 11146.05 | 22.59 | 50.15 |
November | 0.460496E+09 | 0.414447E+09 | 12372.69 | 24-NOV-11:50 | 11135.42 | 11135.42 | 21.26 | 50.15 |
December | 0.723650E+09 | 0.651285E+09 | 12371.54 | 18-DEC-07:00 | 11134.39 | 11134.39 | 21.13 | 50.15 |
Annual Sum or Average | 0.716360E+11 | 0.644724E+11 | ||||||
Minimum of Months | 0.460496E+09 | 0.414447E+09 | 12371.49 | 11134.34 | 11134.34 | 21.12 | 50.15 | |
Maximum of Months | 0.186411E+11 | 0.167770E+11 | 24841.71 | 22357.54 | 22357.54 | 26.42 | 100.31 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 31.33 | 82.00 | 77369.01 | 1020629.72 | 03-JAN-06:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 22.91 | 22.91 | 54547.97 | 1020227.09 | 17-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.56 | 25.56 | 34125.24 | 1014600.53 | 27-MAR-05:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.93 | 23.93 | 4175.74 | 256250.92 | 01-APR-05:02 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 23.02 | 23.02 | 1282.34 | 235608.74 | 05-MAY-05:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 21.18 | 21.18 | 24.37 | 12552.97 | 08-JUN-05:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.90 | 20.90 | 4.46 | 3129.14 | 31-JUL-05:08 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 20.74 | 20.74 | 1.63 | 1613.22 | 23-AUG-05:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 20.68 | 20.68 | 319.69 | 71358.10 | 21-SEP-06:05 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 20.92 | 20.92 | 9306.19 | 564680.93 | 23-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.66 | 21.66 | 36890.05 | 1213381.79 | 27-NOV-05:11 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 26.19 | 26.19 | 84012.23 | 1126112.50 | 26-DEC-05:11 |
Annual Sum or Average | 0.00 | 25092.53 | ||||||
Minimum of Months | 0.00 | 0.00 | 20.68 | 20.68 | 1.63 | 1613.22 | ||
Maximum of Months | 0.00 | 0.00 | 31.33 | 82.00 | 84012.23 | 1213381.79 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 54.42 | 5003.83 | 25-JAN-15:00 | 6.74 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 98.49 | 5182.25 | 07-FEB-15:00 | 6.74 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 247.46 | 14904.98 | 18-MAR-06:13 | 6.83 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 18783.01 | 784498.20 | 28-APR-15:00 | 13.43 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 24172.24 | 1127863.51 | 22-MAY-14:10 | 11.53 | 6.70 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 79953.18 | 1464382.51 | 13-JUN-16:00 | 12.98 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 125149.26 | 1388364.67 | 21-JUL-15:30 | 12.65 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 157182.29 | 1337707.08 | 14-AUG-15:40 | 12.44 | 6.70 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 87087.93 | 1134218.02 | 25-SEP-15:40 | 11.56 | 8.79 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 4412.66 | 271522.39 | 07-OCT-15:00 | 9.03 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 86.06 | 54360.38 | 24-NOV-12:00 | 7.17 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 61.97 | 3130.72 | 23-DEC-11:00 | 6.73 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 41725.35 | 0.00 | ||||||
Minimum of Months | 54.42 | 3130.72 | 6.73 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 157182.29 | 1464382.51 | 13.43 | 8.79 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 5.05 | 2192.18 | 25-JAN-15:00 | 7.99 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 2.65 | 2455.48 | 07-FEB-15:00 | 8.50 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 77.85 | 17194.16 | 18-MAR-06:12 | 9.86 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 18812.46 | 1129782.65 | 30-APR-15:51 | 21.00 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 23944.98 | 1314769.56 | 22-MAY-13:40 | 14.80 | 8.97 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 80185.81 | 1829311.33 | 21-JUN-15:20 | 14.65 | 10.95 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 125323.58 | 1731008.65 | 10-JUL-14:00 | 14.61 | 10.74 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 156079.85 | 1578998.14 | 28-AUG-13:40 | 17.53 | 8.85 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 86887.25 | 1302065.66 | 12-SEP-15:30 | 15.29 | 8.67 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 4214.56 | 273201.73 | 07-OCT-15:00 | 18.27 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 45.38 | 55363.08 | 24-NOV-12:00 | 11.57 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.10 | 371.55 | 23-DEC-11:00 | 11.78 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 41580.89 | 0.00 | ||||||
Minimum of Months | 0.10 | 371.55 | 7.99 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 156079.85 | 1829311.33 | 21.00 | 10.95 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 19286.98 | 34754.56 | 19-JAN-16:30 | 18.97 | 18.33 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 49904.50 | 68375.96 | 17-FEB-17:00 | 19.58 | 18.33 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 80742.18 | 112859.00 | 31-MAR-23:40 | 20.39 | 18.33 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 142130.58 | 1083237.52 | 30-APR-18:10 | 37.82 | 27.63 | 0.00 | 0.00 | 01-APR-00:10 |
May | 34039.94 | 447433.32 | 22-MAY-15:00 | 26.47 | 24.64 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 90307.44 | 991414.78 | 13-JUN-17:00 | 36.19 | 29.41 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 176645.55 | 1377485.67 | 22-JUL-18:00 | 42.99 | 33.43 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 318842.90 | 1423828.72 | 14-AUG-17:20 | 43.80 | 31.44 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 45197.08 | 343471.54 | 13-SEP-16:00 | 24.59 | 23.41 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 53020.98 | 118130.44 | 07-OCT-15:00 | 20.49 | 19.38 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 77771.99 | 94368.30 | 03-NOV-16:00 | 20.06 | 18.33 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 103580.56 | 114830.98 | 18-DEC-15:20 | 20.43 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 99809.51 | 0.00 | ||||||
Minimum of Months | 19286.98 | 34754.56 | 18.97 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 318842.90 | 1423828.72 | 43.80 | 33.43 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 58.09 | 58.09 | 14672.84 | 52248.24 | 31-JAN-13:00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.56 | 57.56 | 14859.04 | 52330.96 | 14-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.56 | 57.56 | 15688.43 | 52245.65 | 01-MAR-13:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.59 | 57.59 | 14420.48 | 51469.90 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 58.13 | 58.13 | 14512.95 | 50340.28 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.72 | 57.72 | 14472.80 | 48910.01 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.78 | 57.78 | 13036.65 | 47643.83 | 03-JUL-11:40 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.81 | 57.81 | 14169.97 | 46995.40 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.81 | 57.81 | 13376.29 | 47647.93 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.78 | 57.78 | 13634.04 | 48915.73 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.72 | 57.72 | 14208.61 | 50301.10 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.65 | 57.65 | 14049.77 | 51474.64 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 14255.08 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.56 | 57.56 | 13036.65 | 46995.40 | ||
Maximum of Months | 0.00 | 0.00 | 58.13 | 58.13 | 15688.43 | 52330.96 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 3.01 | 5015.34 | 26-JAN-06:40 | 21.12 | 20.38 | 482.55 | 104297.98 | 31-JAN-05:43 |
February | 10.18 | 7399.21 | 24-FEB-06:30 | 21.14 | 20.21 | 998.36 | 104845.04 | 17-FEB-13:50 |
March | 16.84 | 13563.30 | 23-MAR-13:50 | 21.16 | 20.50 | 1823.39 | 104286.97 | 08-MAR-06:02 |
April | 20951.58 | 898259.78 | 28-APR-15:00 | 25.39 | 21.10 | 605.23 | 91359.81 | 05-APR-05:40 |
May | 27625.25 | 1907211.01 | 22-MAY-14:10 | 25.65 | 21.29 | 1711.78 | 81857.19 | 10-MAY-09:50 |
June | 98755.03 | 2230421.44 | 13-JUN-16:00 | 26.42 | 22.39 | 1148.38 | 78243.20 | 01-JUN-05:40 |
July | 148885.19 | 1990698.66 | 21-JUL-10:40 | 25.85 | 21.42 | 1059.50 | 63189.19 | 03-JUL-12:10 |
August | 184734.76 | 2041811.99 | 14-AUG-12:10 | 25.97 | 21.73 | 558.68 | 69779.67 | 28-AUG-05:40 |
September | 101370.75 | 1878382.75 | 13-SEP-14:40 | 25.58 | 21.41 | 910.97 | 82320.39 | 08-SEP-06:12 |
October | 4394.72 | 311525.09 | 07-OCT-15:10 | 22.59 | 21.10 | 925.25 | 94543.24 | 23-OCT-05:40 |
November | 23.83 | 33304.53 | 24-NOV-11:50 | 21.26 | 20.80 | 325.91 | 100466.69 | 16-NOV-06:50 |
December | 4.75 | 6318.55 | 18-DEC-07:00 | 21.13 | 20.25 | 612.21 | 107988.16 | 15-DEC-06:50 |
Annual Sum or Average | 49229.92 | 931.62 | ||||||
Minimum of Months | 3.01 | 5015.34 | 21.12 | 20.21 | 325.91 | 63189.19 | ||
Maximum of Months | 184734.76 | 2230421.44 | 26.42 | 22.39 | 1823.39 | 107988.16 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.640548E+10 | 0.00 | 0.00 | 0.432764E+10 | 0.00 | 0.00 |
February | 0.370681E+10 | 0.00 | 0.00 | 0.444314E+10 | 0.00 | 0.00 |
March | 0.169524E+10 | 0.00 | 0.00 | 0.566345E+10 | 0.00 | 0.00 |
April | 0.117848E+09 | 0.00 | 0.469895E+10 | 0.995246E+10 | 0.00 | 0.00 |
May | 34907832.76 | 0.00 | 0.577104E+10 | 0.787898E+10 | 0.00 | 0.00 |
June | 5231.21 | 0.00 | 0.186705E+11 | 0.100107E+11 | 0.00 | 0.00 |
July | 4028.93 | 0.00 | 0.320333E+11 | 0.117912E+11 | 0.00 | 0.00 |
August | 3912.94 | 0.00 | 0.420379E+11 | 0.137083E+11 | 0.00 | 0.00 |
September | 2975486.75 | 0.00 | 0.197180E+11 | 0.865715E+10 | 0.00 | 0.00 |
October | 0.171905E+09 | 0.00 | 0.107330E+10 | 0.642553E+10 | 0.00 | 0.00 |
November | 0.147934E+10 | 0.00 | 13567362.30 | 0.527190E+10 | 0.00 | 0.00 |
December | 0.424453E+10 | 0.00 | 0.00 | 0.491308E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.178591E+11 | 0.00 | 0.124017E+12 | 0.930435E+11 | 0.00 | 0.00 |
Minimum of Months | 3912.94 | 0.00 | 0.00 | 0.432764E+10 | 0.00 | 0.00 |
Maximum of Months | 0.640548E+10 | 0.00 | 0.420379E+11 | 0.137083E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.166985E+12 | 0.00 | 50013.79 | 0.323183E+11 | 0.00 | 0.00 |
February | 0.105278E+12 | 0.00 | 53685.99 | 0.314761E+11 | 0.00 | 0.00 |
March | 0.722501E+11 | 0.00 | 83825.41 | 0.357833E+11 | 0.00 | 0.00 |
April | 0.769420E+10 | 0.00 | 0.386430E+11 | 0.590696E+11 | 0.00 | 0.00 |
May | 0.200961E+10 | 0.00 | 0.490828E+11 | 0.621451E+11 | 0.00 | 0.00 |
June | 7575084.57 | 0.00 | 0.154291E+12 | 0.743269E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.250011E+12 | 0.790421E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.314850E+12 | 0.876700E+11 | 0.00 | 0.00 |
September | 0.283863E+09 | 0.00 | 0.172191E+12 | 0.700603E+11 | 0.00 | 0.00 |
October | 0.175407E+11 | 0.00 | 0.900400E+10 | 0.440809E+11 | 0.00 | 0.00 |
November | 0.750961E+11 | 0.00 | 51926402.11 | 0.326187E+11 | 0.00 | 0.00 |
December | 0.184491E+12 | 0.00 | 56088.88 | 0.304417E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.631636E+12 | 0.00 | 0.988125E+12 | 0.639033E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 50013.79 | 0.304417E+11 | 0.00 | 0.00 |
Maximum of Months | 0.184491E+12 | 0.00 | 0.314850E+12 | 0.876700E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.338158E+11 | 0.00 | 0.00 | 0.313063E+10 | 0.00 | 0.00 |
February | 0.230402E+11 | 0.00 | 0.00 | 0.278607E+10 | 0.00 | 0.00 |
March | 0.178071E+11 | 0.00 | 0.00 | 0.311317E+10 | 0.00 | 0.00 |
April | 0.306672E+10 | 0.00 | 0.372357E+10 | 0.441641E+10 | 0.00 | 0.00 |
May | 0.141077E+10 | 0.00 | 0.498357E+10 | 0.493368E+10 | 0.00 | 0.00 |
June | 57045312.49 | 0.00 | 0.159832E+11 | 0.623802E+10 | 0.00 | 0.00 |
July | 12608145.46 | 0.00 | 0.254910E+11 | 0.681771E+10 | 0.00 | 0.00 |
August | 4623877.55 | 0.00 | 0.302570E+11 | 0.715452E+10 | 0.00 | 0.00 |
September | 0.544959E+09 | 0.00 | 0.155879E+11 | 0.529178E+10 | 0.00 | 0.00 |
October | 0.733743E+10 | 0.00 | 0.635572E+09 | 0.327109E+10 | 0.00 | 0.00 |
November | 0.194976E+11 | 0.00 | 4561892.58 | 0.284581E+10 | 0.00 | 0.00 |
December | 0.370859E+11 | 0.00 | 0.00 | 0.311888E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.143681E+12 | 0.00 | 0.966663E+11 | 0.531178E+11 | 0.00 | 0.00 |
Minimum of Months | 4623877.55 | 0.00 | 0.00 | 0.278607E+10 | 0.00 | 0.00 |
Maximum of Months | 0.370859E+11 | 0.00 | 0.302570E+11 | 0.715452E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.112910E+10 | 0.00 | 36600270.12 | 0.514314E+10 | 0.00 | 0.00 |
February | 0.614758E+09 | 0.00 | 10231437.37 | 0.453090E+10 | 0.00 | 0.00 |
March | 0.132305E+09 | 0.00 | 0.244250E+09 | 0.650901E+10 | 0.00 | 0.00 |
April | 5146052.41 | 0.00 | 0.114216E+10 | 0.136768E+11 | 0.00 | 0.00 |
May | 4344760.86 | 0.00 | 0.375880E+10 | 0.106722E+11 | 0.00 | 0.00 |
June | 226.93 | 0.00 | 0.109175E+11 | 0.143850E+11 | 0.00 | 0.00 |
July | 736.44 | 0.00 | 0.189652E+11 | 0.126971E+11 | 0.00 | 0.00 |
August | 1653.50 | 0.00 | 0.266857E+11 | 0.135161E+11 | 0.00 | 0.00 |
September | 35150.57 | 0.00 | 0.118183E+11 | 0.137598E+11 | 0.00 | 0.00 |
October | 1644692.38 | 0.00 | 0.552948E+09 | 0.124858E+11 | 0.00 | 0.00 |
November | 23177514.24 | 0.00 | 49763889.70 | 0.115432E+11 | 0.00 | 0.00 |
December | 0.344171E+09 | 0.00 | 276615.73 | 0.632950E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.225468E+10 | 0.00 | 0.741817E+11 | 0.125248E+12 | 0.00 | 0.00 |
Minimum of Months | 226.93 | 0.00 | 276615.73 | 0.453090E+10 | 0.00 | 0.00 |
Maximum of Months | 0.112910E+10 | 0.00 | 0.266857E+11 | 0.143850E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.768990E+10 | 0.192493E+12 | 0.00 | 29.44 |
February | 0.00 | 0.00 | 0.103375E+11 | 0.222487E+12 | 0.00 | 44.39 |
March | 0.00 | 0.00 | 0.167925E+11 | 0.313854E+12 | 0.00 | 73.80 |
April | 0.00 | 0.00 | 0.609332E+11 | 0.339388E+12 | 0.00 | 80.85 |
May | 0.00 | 0.00 | 0.575406E+10 | 0.154439E+12 | 0.00 | 15.41 |
June | 0.00 | 0.00 | 0.274070E+11 | 0.128471E+12 | 0.00 | 5.02 |
July | 0.00 | 0.00 | 0.115473E+12 | 0.148807E+12 | 0.00 | 3.88 |
August | 0.00 | 0.00 | 0.366364E+12 | 0.204242E+12 | 0.00 | 5.22 |
September | 0.00 | 0.00 | 0.405763E+10 | 0.124420E+12 | 0.00 | 5.71 |
October | 0.00 | 0.00 | 0.690392E+10 | 0.173568E+12 | 0.00 | 22.42 |
November | 0.00 | 0.00 | 0.123466E+11 | 0.245333E+12 | 0.00 | 50.01 |
December | 0.00 | 0.00 | 0.211764E+11 | 0.356915E+12 | 0.00 | 89.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.655235E+12 | 0.260442E+13 | 0.00 | 425.54 |
Minimum of Months | 0.00 | 0.00 | 0.405763E+10 | 0.124420E+12 | 0.00 | 3.88 |
Maximum of Months | 0.00 | 0.00 | 0.366364E+12 | 0.356915E+12 | 0.00 | 89.39 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.534915E+10 | 0.263106E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.108491E+11 | 0.349248E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.185438E+11 | 0.499785E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.245293E+11 | 0.593468E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.683891E+10 | 0.289320E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.130765E+11 | 0.395514E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.198891E+11 | 0.521009E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.259419E+11 | 0.624176E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.681931E+10 | 0.282923E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.126964E+11 | 0.394595E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.179447E+11 | 0.480530E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.243295E+11 | 0.597396E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.186808E+12 | 0.529107E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.534915E+10 | 0.263106E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.259419E+11 | 0.624176E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.287052E+11 | 0.208773E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.848683E+11 | 0.300398E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.157783E+12 | 0.445430E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.225142E+12 | 0.553202E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.566861E+11 | 0.261119E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.119378E+12 | 0.369125E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.184698E+12 | 0.489958E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.243059E+12 | 0.589804E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.569711E+11 | 0.256033E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.105338E+12 | 0.349706E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.149888E+12 | 0.423553E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.204272E+12 | 0.525609E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.161679E+13 | 0.477271E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.287052E+11 | 0.208773E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.243059E+12 | 0.589804E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.929336E+09 | 0.170319E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.641381E+10 | 0.263485E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.139400E+11 | 0.415570E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.215747E+11 | 0.540250E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.479717E+10 | 0.246591E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.115154E+11 | 0.363851E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.181377E+11 | 0.486861E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.239485E+11 | 0.586729E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.489098E+10 | 0.242919E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.879385E+10 | 0.320368E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.129133E+11 | 0.389614E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.180591E+11 | 0.487988E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.145914E+12 | 0.451454E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.929336E+09 | 0.170319E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.239485E+11 | 0.586729E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.432764E+10 | 0.00 | 0.640548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.444314E+10 | 0.00 | 0.370681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.566345E+10 | 0.00 | 0.169524E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.995246E+10 | 0.469895E+10 | 0.117848E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.787898E+10 | 0.577104E+10 | 34907832.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.100107E+11 | 0.186705E+11 | 5231.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.117912E+11 | 0.320333E+11 | 4028.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137083E+11 | 0.420379E+11 | 3912.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.865715E+10 | 0.197180E+11 | 2975486.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.642553E+10 | 0.107330E+10 | 0.171905E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.527190E+10 | 13567362.30 | 0.147934E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.491308E+10 | 0.00 | 0.424453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.930435E+11 | 0.124017E+12 | 0.178591E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.432764E+10 | 0.00 | 3912.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137083E+11 | 0.420379E+11 | 0.640548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.323183E+11 | 50013.79 | 0.166985E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.314761E+11 | 53685.99 | 0.105278E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.357833E+11 | 83825.41 | 0.722501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.590696E+11 | 0.386430E+11 | 0.769420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.621451E+11 | 0.490828E+11 | 0.200961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.743269E+11 | 0.154291E+12 | 7575084.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.790421E+11 | 0.250011E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.876700E+11 | 0.314850E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.700603E+11 | 0.172191E+12 | 0.283863E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.440809E+11 | 0.900400E+10 | 0.175407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.326187E+11 | 51926402.11 | 0.750961E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.304417E+11 | 56088.88 | 0.184491E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.639033E+12 | 0.988125E+12 | 0.631636E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.304417E+11 | 50013.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.876700E+11 | 0.314850E+12 | 0.184491E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.313063E+10 | 0.00 | 0.338158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.278607E+10 | 0.00 | 0.230402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.311317E+10 | 0.00 | 0.178071E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.441641E+10 | 0.372357E+10 | 0.306672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.493368E+10 | 0.498357E+10 | 0.141077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.623802E+10 | 0.159832E+11 | 57045312.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.681771E+10 | 0.254910E+11 | 12608145.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.715452E+10 | 0.302570E+11 | 4623877.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.529178E+10 | 0.155879E+11 | 0.544959E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.327109E+10 | 0.635572E+09 | 0.733743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.284581E+10 | 4561892.58 | 0.194976E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.311888E+10 | 0.00 | 0.370859E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.531178E+11 | 0.966663E+11 | 0.143681E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.278607E+10 | 0.00 | 4623877.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.715452E+10 | 0.302570E+11 | 0.370859E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.514314E+10 | 36600270.12 | 0.112910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.453090E+10 | 10231437.37 | 0.614758E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.650901E+10 | 0.244250E+09 | 0.132305E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136768E+11 | 0.114216E+10 | 5146052.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106722E+11 | 0.375880E+10 | 4344760.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.143850E+11 | 0.109175E+11 | 226.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.126971E+11 | 0.189652E+11 | 736.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135161E+11 | 0.266857E+11 | 1653.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137598E+11 | 0.118183E+11 | 35150.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124858E+11 | 0.552948E+09 | 1644692.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.115432E+11 | 49763889.70 | 23177514.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.632950E+10 | 276615.73 | 0.344171E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125248E+12 | 0.741817E+11 | 0.225468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.453090E+10 | 276615.73 | 226.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143850E+11 | 0.266857E+11 | 0.112910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.109506E+12 | 0.383784E+10 | 0.00 | 0.00 | 0.00 | 0.787803E+11 | 0.00 | 0.00 |
February | 0.989088E+11 | 0.609449E+10 | 0.00 | 0.00 | 0.00 | 0.118801E+12 | 0.00 | 0.00 |
March | 0.109506E+12 | 0.108219E+11 | 0.00 | 0.00 | 0.00 | 0.197488E+12 | 0.00 | 0.00 |
April | 0.105974E+12 | 0.448575E+11 | 0.00 | 0.00 | 0.00 | 0.216365E+12 | 0.00 | 0.00 |
May | 0.109506E+12 | 0.223940E+10 | 0.00 | 0.00 | 0.00 | 0.412325E+11 | 0.00 | 0.00 |
June | 0.105974E+12 | 0.184084E+11 | 0.00 | 0.00 | 0.00 | 0.134381E+11 | 0.00 | 0.00 |
July | 0.109506E+12 | 0.866000E+11 | 0.00 | 0.00 | 0.00 | 0.103812E+11 | 0.00 | 0.00 |
August | 0.109506E+12 | 0.285665E+12 | 0.00 | 0.00 | 0.00 | 0.139732E+11 | 0.00 | 0.00 |
September | 0.105974E+12 | 0.960196E+09 | 0.00 | 0.00 | 0.00 | 0.152804E+11 | 0.00 | 0.00 |
October | 0.109506E+12 | 0.311770E+10 | 0.00 | 0.00 | 0.00 | 0.600058E+11 | 0.00 | 0.00 |
November | 0.105974E+12 | 0.742988E+10 | 0.00 | 0.00 | 0.00 | 0.133841E+12 | 0.00 | 0.00 |
December | 0.109506E+12 | 0.140647E+11 | 0.00 | 0.00 | 0.00 | 0.239220E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.128935E+13 | 0.484096E+12 | 0.00 | 0.00 | 0.00 | 0.113881E+13 | 0.00 | 0.00 |
Minimum of Months | 0.989088E+11 | 0.960196E+09 | 0.00 | 0.00 | 0.00 | 0.103812E+11 | 0.00 | 0.00 |
Maximum of Months | 0.109506E+12 | 0.285665E+12 | 0.00 | 0.00 | 0.00 | 0.239220E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.153606E+10 | 0.425415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138741E+10 | 0.874401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153606E+10 | 0.150820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148651E+10 | 0.200811E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153606E+10 | 0.548176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.148651E+10 | 0.106079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153606E+10 | 0.162150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153606E+10 | 0.212362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.148651E+10 | 0.547658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153606E+10 | 0.102865E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148651E+10 | 0.146259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153606E+10 | 0.198916E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180858E+11 | 0.151983E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.138741E+10 | 0.425415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153606E+10 | 0.212362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.147562E+11 | 0.225841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133281E+11 | 0.681566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147562E+11 | 0.127996E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142802E+11 | 0.184102E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147562E+11 | 0.453305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142802E+11 | 0.967459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147562E+11 | 0.150458E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147562E+11 | 0.198835E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142802E+11 | 0.456480E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147562E+11 | 0.851235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142802E+11 | 0.121813E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147562E+11 | 0.166467E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173742E+12 | 0.131326E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133281E+11 | 0.225841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147562E+11 | 0.198835E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.149492E+10 | 0.721067E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135025E+10 | 0.512921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149492E+10 | 0.112792E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144669E+10 | 0.176189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149492E+10 | 0.382618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144669E+10 | 0.932354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149492E+10 | 0.147640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149492E+10 | 0.195761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144669E+10 | 0.390848E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149492E+10 | 0.708509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144669E+10 | 0.104638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149492E+10 | 0.146742E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176014E+11 | 0.118370E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135025E+10 | 0.721067E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149492E+10 | 0.195761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.432764E+10 | 0.640548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.444314E+10 | 0.370681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.566345E+10 | 0.169524E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.995246E+10 | 0.117848E+09 | 0.469895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.787898E+10 | 34907832.76 | 0.577104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.100107E+11 | 5231.21 | 0.186705E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.117912E+11 | 4028.93 | 0.320333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137083E+11 | 3912.94 | 0.420379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.865715E+10 | 2975486.75 | 0.197180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.642553E+10 | 0.171905E+09 | 0.107330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.527190E+10 | 0.147934E+10 | 13567362.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.491308E+10 | 0.424453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.930435E+11 | 0.178591E+11 | 0.124017E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.432764E+10 | 3912.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137083E+11 | 0.640548E+10 | 0.420379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.323183E+11 | 0.166985E+12 | 50013.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.314761E+11 | 0.105278E+12 | 53685.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.357833E+11 | 0.722501E+11 | 83825.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.590696E+11 | 0.769420E+10 | 0.386430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.621451E+11 | 0.200961E+10 | 0.490828E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.743269E+11 | 7575084.57 | 0.154291E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.790421E+11 | 0.00 | 0.250011E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.876700E+11 | 0.00 | 0.314850E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.700603E+11 | 0.283863E+09 | 0.172191E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.440809E+11 | 0.175407E+11 | 0.900400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.326187E+11 | 0.750961E+11 | 51926402.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.304417E+11 | 0.184491E+12 | 56088.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.639033E+12 | 0.631636E+12 | 0.988125E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.304417E+11 | 0.00 | 50013.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.876700E+11 | 0.184491E+12 | 0.314850E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.313063E+10 | 0.338158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.278607E+10 | 0.230402E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.311317E+10 | 0.178071E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.441641E+10 | 0.306672E+10 | 0.372357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.493368E+10 | 0.141077E+10 | 0.498357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.623802E+10 | 57045312.49 | 0.159832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.681771E+10 | 12608145.46 | 0.254910E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.715452E+10 | 4623877.55 | 0.302570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.529178E+10 | 0.544959E+09 | 0.155879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.327109E+10 | 0.733743E+10 | 0.635572E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.284581E+10 | 0.194976E+11 | 4561892.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.311888E+10 | 0.370859E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.531178E+11 | 0.143681E+12 | 0.966663E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.278607E+10 | 4623877.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.715452E+10 | 0.370859E+11 | 0.302570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.514314E+10 | 0.112910E+10 | 36600270.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.453090E+10 | 0.614758E+09 | 10231437.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.650901E+10 | 0.132305E+09 | 0.244250E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136768E+11 | 5146052.41 | 0.114216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106722E+11 | 4344760.86 | 0.375880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.143850E+11 | 226.93 | 0.109175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.126971E+11 | 736.44 | 0.189652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135161E+11 | 1653.50 | 0.266857E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137598E+11 | 35150.57 | 0.118183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.124858E+11 | 1644692.38 | 0.552948E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.115432E+11 | 23177514.24 | 49763889.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.632950E+10 | 0.344171E+09 | 276615.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125248E+12 | 0.225468E+10 | 0.741817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.453090E+10 | 226.93 | 276615.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143850E+11 | 0.112910E+10 | 0.266857E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.109506E+12 | 0.00 | 0.768990E+10 | 0.00 | 0.385206E+10 | 0.00 | 0.00 | 0.00 | 0.791349E+11 | 0.00 | 0.00 | 0.00 |
February | 0.989088E+11 | 0.00 | 0.103375E+11 | 0.00 | 0.424297E+10 | 0.00 | 0.00 | 0.00 | 0.119335E+12 | 0.00 | 0.00 | 0.00 |
March | 0.109506E+12 | 0.00 | 0.167925E+11 | 0.00 | 0.597060E+10 | 0.00 | 0.00 | 0.00 | 0.198377E+12 | 0.00 | 0.00 | 0.00 |
April | 0.105974E+12 | 0.00 | 0.609332E+11 | 0.00 | 0.160757E+11 | 0.00 | 0.00 | 0.00 | 0.217339E+12 | 0.00 | 0.00 | 0.00 |
May | 0.109506E+12 | 0.00 | 0.575406E+10 | 0.00 | 0.351465E+10 | 0.00 | 0.00 | 0.00 | 0.414181E+11 | 0.00 | 0.00 | 0.00 |
June | 0.105974E+12 | 0.00 | 0.274070E+11 | 0.00 | 0.899869E+10 | 0.00 | 0.00 | 0.00 | 0.134986E+11 | 0.00 | 0.00 | 0.00 |
July | 0.109506E+12 | 0.00 | 0.115473E+12 | 0.00 | 0.288726E+11 | 0.00 | 0.00 | 0.00 | 0.104280E+11 | 0.00 | 0.00 | 0.00 |
August | 0.109506E+12 | 0.00 | 0.366364E+12 | 0.00 | 0.806993E+11 | 0.00 | 0.00 | 0.00 | 0.140361E+11 | 0.00 | 0.00 | 0.00 |
September | 0.105974E+12 | 0.00 | 0.405763E+10 | 0.00 | 0.309744E+10 | 0.00 | 0.00 | 0.00 | 0.153492E+11 | 0.00 | 0.00 | 0.00 |
October | 0.109506E+12 | 0.00 | 0.690392E+10 | 0.00 | 0.378622E+10 | 0.00 | 0.00 | 0.00 | 0.602759E+11 | 0.00 | 0.00 | 0.00 |
November | 0.105974E+12 | 0.00 | 0.123466E+11 | 0.00 | 0.491671E+10 | 0.00 | 0.00 | 0.00 | 0.134443E+12 | 0.00 | 0.00 | 0.00 |
December | 0.109506E+12 | 0.00 | 0.211764E+11 | 0.00 | 0.711172E+10 | 0.00 | 0.00 | 0.00 | 0.240297E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128935E+13 | 0.00 | 0.655235E+12 | 0.00 | 0.171139E+12 | 0.00 | 0.00 | 0.00 | 0.114393E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.989088E+11 | 0.00 | 0.405763E+10 | 0.00 | 0.309744E+10 | 0.00 | 0.00 | 0.00 | 0.104280E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.109506E+12 | 0.00 | 0.366364E+12 | 0.00 | 0.806993E+11 | 0.00 | 0.00 | 0.00 | 0.240297E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.153606E+10 | 0.00 | 0.534915E+10 | 0.00 | 0.109501E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138741E+10 | 0.00 | 0.108491E+11 | 0.00 | 0.210507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153606E+10 | 0.00 | 0.185438E+11 | 0.00 | 0.346179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148651E+10 | 0.00 | 0.245293E+11 | 0.00 | 0.444818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153606E+10 | 0.00 | 0.683891E+10 | 0.00 | 0.135715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.148651E+10 | 0.00 | 0.130765E+11 | 0.00 | 0.246864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153606E+10 | 0.00 | 0.198891E+11 | 0.00 | 0.367403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153606E+10 | 0.00 | 0.259419E+11 | 0.00 | 0.470570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.148651E+10 | 0.00 | 0.681931E+10 | 0.00 | 0.134273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153606E+10 | 0.00 | 0.126964E+11 | 0.00 | 0.240989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148651E+10 | 0.00 | 0.179447E+11 | 0.00 | 0.331879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153606E+10 | 0.00 | 0.243295E+11 | 0.00 | 0.443791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.180858E+11 | 0.00 | 0.186808E+12 | 0.00 | 0.348249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.138741E+10 | 0.00 | 0.534915E+10 | 0.00 | 0.109501E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153606E+10 | 0.00 | 0.259419E+11 | 0.00 | 0.470570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.147562E+11 | 0.00 | 0.287052E+11 | 0.00 | 0.612113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133281E+11 | 0.00 | 0.848683E+11 | 0.00 | 0.167117E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147562E+11 | 0.00 | 0.157783E+12 | 0.00 | 0.297868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142802E+11 | 0.00 | 0.225142E+12 | 0.00 | 0.410400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147562E+11 | 0.00 | 0.566861E+11 | 0.00 | 0.113557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142802E+11 | 0.00 | 0.119378E+12 | 0.00 | 0.226324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147562E+11 | 0.00 | 0.184698E+12 | 0.00 | 0.342396E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147562E+11 | 0.00 | 0.243059E+12 | 0.00 | 0.442242E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142802E+11 | 0.00 | 0.569711E+11 | 0.00 | 0.113231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147562E+11 | 0.00 | 0.105338E+12 | 0.00 | 0.202144E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142802E+11 | 0.00 | 0.149888E+12 | 0.00 | 0.280751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147562E+11 | 0.00 | 0.204272E+12 | 0.00 | 0.378047E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173742E+12 | 0.00 | 0.161679E+13 | 0.00 | 0.303529E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133281E+11 | 0.00 | 0.287052E+11 | 0.00 | 0.612113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147562E+11 | 0.00 | 0.243059E+12 | 0.00 | 0.442242E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.149492E+10 | 0.00 | 0.929336E+09 | 0.00 | 0.208270E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135025E+10 | 0.00 | 0.641381E+10 | 0.00 | 0.128460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149492E+10 | 0.00 | 0.139400E+11 | 0.00 | 0.266078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144669E+10 | 0.00 | 0.215747E+11 | 0.00 | 0.395580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149492E+10 | 0.00 | 0.479717E+10 | 0.00 | 0.970990E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144669E+10 | 0.00 | 0.115154E+11 | 0.00 | 0.219182E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149492E+10 | 0.00 | 0.181377E+11 | 0.00 | 0.337370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149492E+10 | 0.00 | 0.239485E+11 | 0.00 | 0.437238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144669E+10 | 0.00 | 0.489098E+10 | 0.00 | 0.982494E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149492E+10 | 0.00 | 0.879385E+10 | 0.00 | 0.170876E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144669E+10 | 0.00 | 0.129133E+11 | 0.00 | 0.244945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149492E+10 | 0.00 | 0.180591E+11 | 0.00 | 0.338497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176014E+11 | 0.00 | 0.145914E+12 | 0.00 | 0.275440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135025E+10 | 0.00 | 0.929336E+09 | 0.00 | 0.208270E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149492E+10 | 0.00 | 0.239485E+11 | 0.00 | 0.437238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 91894122.77 | 0.00 | 0.00 | 0.598287E+11 | 0.00 | 0.48 |
February | 0.00 | 0.00 | 0.00 | 85805411.30 | 0.00 | 0.00 | 0.532655E+11 | 0.00 | 0.49 |
March | 0.00 | 0.00 | 0.00 | 97954953.24 | 0.00 | 0.00 | 0.653137E+11 | 0.00 | 0.59 |
April | 0.00 | 0.00 | 0.00 | 0.102912E+09 | 0.00 | 0.00 | 0.714889E+11 | 0.00 | 0.91 |
May | 0.00 | 0.00 | 0.00 | 0.106418E+09 | 0.00 | 0.00 | 0.665948E+11 | 0.00 | 0.86 |
June | 0.00 | 1736743.07 | 0.00 | 0.120431E+09 | 0.00 | 0.00 | 0.655235E+11 | 0.00 | 1.17 |
July | 0.00 | 3008754.51 | 0.00 | 0.128198E+09 | 0.00 | 0.00 | 0.553092E+11 | 0.00 | 1.14 |
August | 0.00 | 0.00 | 0.00 | 0.134978E+09 | 0.00 | 0.00 | 0.558829E+11 | 0.00 | 1.33 |
September | 0.00 | 0.00 | 0.00 | 0.114250E+09 | 0.00 | 0.00 | 0.614075E+11 | 0.00 | 1.18 |
October | 0.00 | 0.00 | 0.00 | 0.113153E+09 | 0.00 | 0.00 | 0.716842E+11 | 0.00 | 0.86 |
November | 0.00 | 0.00 | 0.00 | 0.103580E+09 | 0.00 | 0.00 | 0.689953E+11 | 0.00 | 0.68 |
December | 0.00 | 0.00 | 0.00 | 93901556.90 | 0.00 | 0.00 | 0.616441E+11 | 0.00 | 0.50 |
Annual Sum or Average | 0.00 | 4745497.58 | 0.00 | 0.129348E+10 | 0.00 | 0.00 | 0.756938E+12 | 0.00 | 0.85 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 85805411.30 | 0.00 | 0.00 | 0.532655E+11 | 0.00 | 0.48 |
Maximum of Months | 0.00 | 3008754.51 | 0.00 | 0.134978E+09 | 0.00 | 0.00 | 0.716842E+11 | 0.00 | 1.33 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.267641E+10 | 0.00 | 0.00 | 68669150.38 | 0.00 | 0.00 | 0.486946E+11 | 0.00 | 0.40 |
February | 0.192423E+10 | 0.00 | 0.00 | 72835199.61 | 0.00 | 0.00 | 0.463973E+11 | 0.00 | 0.43 |
March | 0.159925E+10 | 0.00 | 0.00 | 92471145.84 | 0.00 | 0.00 | 0.599152E+11 | 0.00 | 0.53 |
April | 0.436313E+10 | 0.00 | 0.00 | 0.105483E+09 | 0.00 | 0.00 | 0.636803E+11 | 0.00 | 0.81 |
May | 0.447612E+10 | 0.00 | 0.00 | 91368956.02 | 0.00 | 0.00 | 0.569492E+11 | 0.00 | 0.74 |
June | 0.416019E+10 | 4428028.34 | 0.00 | 0.104613E+09 | 59194772.01 | 0.00 | 0.578373E+11 | 0.00 | 0.99 |
July | 0.726875E+10 | 20897361.51 | 0.00 | 0.107515E+09 | 9591064.69 | 0.00 | 0.526606E+11 | 0.00 | 1.09 |
August | 0.749498E+10 | 0.00 | 0.00 | 0.121756E+09 | 0.00 | 0.00 | 0.549888E+11 | 0.00 | 1.25 |
September | 0.422245E+10 | 0.00 | 0.00 | 93652742.48 | 0.00 | 0.00 | 0.489776E+11 | 0.00 | 0.92 |
October | 0.205861E+10 | 0.00 | 0.00 | 92476850.44 | 0.00 | 0.00 | 0.565759E+11 | 0.00 | 0.66 |
November | 0.184136E+10 | 0.00 | 0.00 | 88767070.51 | 0.00 | 0.00 | 0.547429E+11 | 0.00 | 0.53 |
December | 0.170306E+10 | 0.00 | 0.00 | 85844380.40 | 0.00 | 0.00 | 0.535405E+11 | 0.00 | 0.44 |
Annual Sum or Average | 0.437886E+11 | 25325389.85 | 0.00 | 0.112545E+10 | 68785836.70 | 0.00 | 0.654960E+12 | 0.00 | 0.73 |
Minimum of Months | 0.159925E+10 | 0.00 | 0.00 | 68669150.38 | 0.00 | 0.00 | 0.463973E+11 | 0.00 | 0.40 |
Maximum of Months | 0.749498E+10 | 20897361.51 | 0.00 | 0.121756E+09 | 59194772.01 | 0.00 | 0.636803E+11 | 0.00 | 1.25 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.198135E+12 | 0.00 | 0.00 | 0.200103E+09 | 0.00 | 0.00 | 0.180163E+12 | 0.00 | 0.30 |
February | 0.158586E+12 | 0.00 | 0.00 | 0.240345E+09 | 0.00 | 0.00 | 0.181570E+12 | 0.00 | 0.31 |
March | 0.146243E+12 | 0.00 | 0.00 | 0.332217E+09 | 0.00 | 0.00 | 0.258478E+12 | 0.00 | 0.35 |
April | 0.575448E+11 | 0.00 | 0.00 | 0.525358E+09 | 0.00 | 0.00 | 0.383850E+12 | 0.00 | 0.54 |
May | 0.693647E+11 | 0.00 | 0.00 | 0.563714E+09 | 0.00 | 0.00 | 0.408036E+12 | 0.00 | 0.59 |
June | 0.382003E+11 | 40859146.92 | 0.00 | 0.692184E+09 | 0.677707E+09 | 0.00 | 0.432725E+12 | 0.00 | 0.77 |
July | 0.521399E+11 | 0.249222E+09 | 0.00 | 0.657943E+09 | 0.132661E+09 | 0.00 | 0.365810E+12 | 0.00 | 0.79 |
August | 0.429455E+11 | 0.00 | 0.00 | 0.738290E+09 | 0.00 | 0.00 | 0.380365E+12 | 0.00 | 0.88 |
September | 0.574372E+11 | 0.00 | 0.00 | 0.595065E+09 | 0.00 | 0.00 | 0.355742E+12 | 0.00 | 0.74 |
October | 0.976178E+11 | 0.00 | 0.00 | 0.421463E+09 | 0.00 | 0.00 | 0.300811E+12 | 0.00 | 0.46 |
November | 0.141669E+12 | 0.00 | 0.00 | 0.272832E+09 | 0.00 | 0.00 | 0.210532E+12 | 0.00 | 0.34 |
December | 0.205849E+12 | 0.00 | 0.00 | 0.147120E+09 | 0.00 | 0.00 | 0.144842E+12 | 0.00 | 0.29 |
Annual Sum or Average | 0.126573E+13 | 0.290081E+09 | 0.00 | 0.538663E+10 | 0.810368E+09 | 0.00 | 0.360292E+13 | 0.00 | 0.53 |
Minimum of Months | 0.382003E+11 | 0.00 | 0.00 | 0.147120E+09 | 0.00 | 0.00 | 0.144842E+12 | 0.00 | 0.29 |
Maximum of Months | 0.205849E+12 | 0.249222E+09 | 0.00 | 0.738290E+09 | 0.677707E+09 | 0.00 | 0.432725E+12 | 0.00 | 0.88 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.291105E+11 | 0.00 | 0.00 | 958616.36 | 0.00 | 0.133756E+10 | 0.150333E+10 | 0.00 | 0.28 |
February | 0.256870E+11 | 0.00 | 0.00 | 1483260.33 | 0.00 | 0.512608E+09 | 0.247214E+10 | 0.00 | 0.28 |
March | 0.269845E+11 | 0.00 | 0.00 | 4452718.44 | 0.00 | 0.409121E+09 | 0.603666E+10 | 0.00 | 0.31 |
April | 0.125328E+11 | 3091844.85 | 0.00 | 29009641.36 | 0.00 | 0.00 | 0.252511E+11 | 0.00 | 0.47 |
May | 0.124129E+11 | 0.00 | 0.00 | 36721179.49 | 0.00 | 0.00 | 0.297721E+11 | 0.00 | 0.53 |
June | 0.840550E+10 | 947749.98 | 0.00 | 53351789.55 | 55172870.56 | 0.00 | 0.363549E+11 | 0.00 | 0.74 |
July | 0.831694E+10 | 16189520.24 | 0.00 | 54364142.96 | 6397488.69 | 0.00 | 0.326226E+11 | 0.00 | 0.77 |
August | 0.775465E+10 | 0.00 | 0.00 | 57418121.77 | 0.00 | 0.00 | 0.324763E+11 | 0.00 | 0.84 |
September | 0.109749E+11 | 0.00 | 0.00 | 37480786.78 | 0.00 | 0.00 | 0.247472E+11 | 0.00 | 0.66 |
October | 0.191045E+11 | 0.00 | 0.00 | 10538474.65 | 0.00 | 0.124945E+09 | 0.110750E+11 | 0.00 | 0.37 |
November | 0.245772E+11 | 0.00 | 0.00 | 2380941.41 | 0.00 | 0.537683E+09 | 0.325679E+10 | 0.00 | 0.29 |
December | 0.288862E+11 | 0.00 | 0.00 | 105711.19 | 0.00 | 0.107952E+10 | 0.438482E+09 | 0.00 | 0.27 |
Annual Sum or Average | 0.214748E+12 | 20229115.07 | 0.00 | 0.288265E+09 | 61570359.25 | 0.400145E+10 | 0.206006E+12 | 0.00 | 0.49 |
Minimum of Months | 0.775465E+10 | 0.00 | 0.00 | 105711.19 | 0.00 | 0.00 | 0.438482E+09 | 0.00 | 0.27 |
Maximum of Months | 0.291105E+11 | 16189520.24 | 0.00 | 57418121.77 | 55172870.56 | 0.133756E+10 | 0.363549E+11 | 0.00 | 0.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.396864E+10 | 0.00 | 0.00 | 402031.63 | 0.00 | 13005956.25 | 0.568574E+09 | 0.00 | 0.28 |
February | 0.335077E+10 | 0.00 | 0.00 | 741525.86 | 0.00 | 0.00 | 0.835462E+09 | 0.00 | 0.29 |
March | 0.276119E+10 | 0.00 | 0.00 | 2895157.96 | 0.00 | 0.00 | 0.251264E+10 | 0.00 | 0.36 |
April | 0.169684E+10 | 0.00 | 0.00 | 7003624.10 | 0.00 | 0.00 | 0.534166E+10 | 0.00 | 0.69 |
May | 0.154174E+10 | 0.00 | 0.00 | 7341228.46 | 0.00 | 0.00 | 0.535350E+10 | 0.00 | 0.69 |
June | 0.841012E+09 | 973251.05 | 0.00 | 11610846.36 | 7445323.94 | 0.00 | 0.714963E+10 | 0.00 | 1.07 |
July | 0.108939E+10 | 4473714.63 | 0.00 | 12616230.58 | 1206332.61 | 0.00 | 0.676844E+10 | 0.00 | 1.18 |
August | 0.125588E+10 | 0.00 | 0.00 | 12465136.12 | 0.00 | 0.00 | 0.634091E+10 | 0.00 | 1.27 |
September | 0.169625E+10 | 0.00 | 0.00 | 6423058.96 | 0.00 | 0.00 | 0.397838E+10 | 0.00 | 0.81 |
October | 0.228969E+10 | 0.00 | 0.00 | 3370485.80 | 0.00 | 0.00 | 0.287136E+10 | 0.00 | 0.47 |
November | 0.288572E+10 | 0.00 | 0.00 | 1605864.43 | 0.00 | 0.00 | 0.159718E+10 | 0.00 | 0.33 |
December | 0.389793E+10 | 0.00 | 0.00 | 215390.76 | 0.00 | 0.00 | 0.544423E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.272751E+11 | 5446965.67 | 0.00 | 66690581.02 | 8651656.55 | 13005956.25 | 0.438622E+11 | 0.00 | 0.65 |
Minimum of Months | 0.841012E+09 | 0.00 | 0.00 | 215390.76 | 0.00 | 0.00 | 0.544423E+09 | 0.00 | 0.28 |
Maximum of Months | 0.396864E+10 | 4473714.63 | 0.00 | 12616230.58 | 7445323.94 | 13005956.25 | 0.714963E+10 | 0.00 | 1.27 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.443230E+10 | 0.00 | 0.00 | 358529.66 | 0.00 | 63713378.45 | 0.436286E+09 | 0.00 | 0.47 |
February | 0.398560E+10 | 0.00 | 0.00 | 831905.23 | 0.00 | 1037358.59 | 0.616324E+09 | 0.00 | 0.50 |
March | 0.385944E+10 | 0.00 | 0.00 | 1175996.15 | 0.00 | 0.00 | 0.139669E+10 | 0.00 | 0.56 |
April | 0.195966E+10 | 0.00 | 0.00 | 9650815.65 | 0.00 | 0.00 | 0.626980E+10 | 0.00 | 1.24 |
May | 0.171694E+10 | 0.00 | 0.00 | 10184427.54 | 0.00 | 0.00 | 0.641130E+10 | 0.00 | 1.25 |
June | 0.129063E+10 | 593037.65 | 0.00 | 12273979.46 | 8037135.93 | 0.00 | 0.674631E+10 | 0.00 | 1.67 |
July | 0.147356E+10 | 5853195.54 | 0.00 | 13533786.71 | 1302221.26 | 0.00 | 0.635222E+10 | 0.00 | 1.80 |
August | 0.178562E+10 | 0.00 | 0.00 | 13268933.99 | 0.00 | 0.00 | 0.624333E+10 | 0.00 | 2.00 |
September | 0.181778E+10 | 0.00 | 0.00 | 10074981.56 | 0.00 | 0.00 | 0.522264E+10 | 0.00 | 1.54 |
October | 0.299349E+10 | 0.00 | 0.00 | 3409059.60 | 0.00 | 0.00 | 0.258850E+10 | 0.00 | 0.78 |
November | 0.418219E+10 | 0.00 | 0.00 | 487581.05 | 0.00 | 0.00 | 0.551729E+09 | 0.00 | 0.54 |
December | 0.462285E+10 | 0.00 | 0.00 | 232408.74 | 0.00 | 2165547.75 | 0.176261E+09 | 0.00 | 0.46 |
Annual Sum or Average | 0.341201E+11 | 6446233.19 | 0.00 | 75482405.34 | 9339357.19 | 66916284.80 | 0.430114E+11 | 0.00 | 1.07 |
Minimum of Months | 0.129063E+10 | 0.00 | 0.00 | 232408.74 | 0.00 | 0.00 | 0.176261E+09 | 0.00 | 0.46 |
Maximum of Months | 0.462285E+10 | 5853195.54 | 0.00 | 13533786.71 | 8037135.93 | 63713378.45 | 0.674631E+10 | 0.00 | 2.00 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.505860E+10 | 0.00 | 0.00 | 4658905.69 | 0.00 | 0.146198E+09 | 0.322217E+10 | 0.00 | 0.53 |
February | 0.438925E+10 | 0.00 | 0.00 | 6612179.91 | 0.00 | 18093123.13 | 0.414547E+10 | 0.00 | 0.61 |
March | 0.481905E+10 | 0.00 | 0.00 | 3939040.06 | 0.00 | 1061234.15 | 0.338563E+10 | 0.00 | 0.57 |
April | 0.263060E+10 | 0.00 | 0.00 | 17043231.75 | 0.00 | 0.00 | 0.109046E+11 | 0.00 | 1.39 |
May | 0.283665E+10 | 0.00 | 0.00 | 11515499.49 | 0.00 | 0.00 | 0.832314E+10 | 0.00 | 1.14 |
June | 0.213913E+10 | 1004892.02 | 0.00 | 13774577.63 | 11261072.21 | 0.00 | 0.849324E+10 | 0.00 | 1.46 |
July | 0.223564E+10 | 6376315.43 | 0.00 | 17480620.37 | 1824581.26 | 0.00 | 0.868349E+10 | 0.00 | 1.68 |
August | 0.235201E+10 | 0.00 | 0.00 | 23783950.10 | 0.00 | 0.00 | 0.999728E+10 | 0.00 | 2.13 |
September | 0.223043E+10 | 0.00 | 0.00 | 21583527.48 | 0.00 | 0.00 | 0.101268E+11 | 0.00 | 1.89 |
October | 0.366564E+10 | 0.00 | 0.00 | 10630129.70 | 0.00 | 0.00 | 0.740232E+10 | 0.00 | 1.07 |
November | 0.475026E+10 | 0.00 | 0.00 | 5029113.98 | 0.00 | 2961643.39 | 0.340332E+10 | 0.00 | 0.61 |
December | 0.551932E+10 | 0.00 | 0.00 | 2839708.40 | 0.00 | 32271223.00 | 0.211128E+10 | 0.00 | 0.48 |
Annual Sum or Average | 0.426266E+11 | 7381207.45 | 0.00 | 0.138890E+09 | 13085653.47 | 0.200585E+09 | 0.801988E+11 | 0.00 | 1.13 |
Minimum of Months | 0.213913E+10 | 0.00 | 0.00 | 2839708.40 | 0.00 | 0.00 | 0.211128E+10 | 0.00 | 0.48 |
Maximum of Months | 0.551932E+10 | 6376315.43 | 0.00 | 23783950.10 | 11261072.21 | 0.146198E+09 | 0.109046E+11 | 0.00 | 2.13 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.490513E+10 | 0.00 | 0.00 | 1072438.72 | 0.00 | 0.00 | 0.117289E+10 | 0.00 | 0.59 |
February | 0.311056E+10 | 0.00 | 0.00 | 3731455.13 | 0.00 | 0.00 | 0.313061E+10 | 0.00 | 0.69 |
March | 0.172107E+10 | 0.00 | 0.00 | 6990496.16 | 0.00 | 0.00 | 0.586404E+10 | 0.00 | 0.81 |
April | 0.635192E+09 | 0.00 | 0.00 | 19346603.44 | 0.00 | 0.00 | 0.111886E+11 | 0.00 | 1.86 |
May | 0.139573E+10 | 0.00 | 0.00 | 13740986.15 | 0.00 | 0.00 | 0.827822E+10 | 0.00 | 1.54 |
June | 0.629787E+09 | 23567975.89 | 0.00 | 20008966.80 | 439915.39 | 0.00 | 0.102291E+11 | 0.00 | 2.31 |
July | 0.860469E+09 | 9395058.27 | 0.00 | 26956959.23 | 96279.21 | 0.00 | 0.104635E+11 | 0.00 | 2.70 |
August | 0.880287E+09 | 0.00 | 0.00 | 28335990.01 | 0.00 | 0.00 | 0.107876E+11 | 0.00 | 3.02 |
September | 0.144332E+10 | 0.00 | 0.00 | 11424431.85 | 0.00 | 0.00 | 0.618578E+10 | 0.00 | 1.75 |
October | 0.188483E+10 | 0.00 | 0.00 | 6455470.18 | 0.00 | 0.00 | 0.537304E+10 | 0.00 | 1.05 |
November | 0.200647E+10 | 0.00 | 0.00 | 4785685.24 | 0.00 | 0.00 | 0.432038E+10 | 0.00 | 0.74 |
December | 0.258725E+10 | 0.00 | 0.00 | 3865578.13 | 0.00 | 0.00 | 0.357051E+10 | 0.00 | 0.60 |
Annual Sum or Average | 0.220601E+11 | 32963034.17 | 0.00 | 0.146715E+09 | 536194.59 | 0.00 | 0.805642E+11 | 0.00 | 1.47 |
Minimum of Months | 0.629787E+09 | 0.00 | 0.00 | 1072438.72 | 0.00 | 0.00 | 0.117289E+10 | 0.00 | 0.59 |
Maximum of Months | 0.490513E+10 | 23567975.89 | 0.00 | 28335990.01 | 439915.39 | 0.00 | 0.111886E+11 | 0.00 | 3.02 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.301510E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147606E+11 | 0.00 | 0.00 | 0.28 |
February | 0.308921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.855563E+10 | 0.00 | 0.00 | 0.28 |
March | 0.397113E+11 | 0.00 | 0.00 | 127045.61 | 0.00 | 0.431010E+10 | 0.415395E+09 | 0.00 | 0.31 |
April | 0.243596E+11 | 0.00 | 0.00 | 24205098.76 | 0.00 | 65433880.47 | 0.205996E+11 | 0.00 | 0.44 |
May | 0.229501E+11 | 0.00 | 0.00 | 36206726.41 | 0.00 | 0.00 | 0.284473E+11 | 0.00 | 0.52 |
June | 0.120468E+11 | 10600496.36 | 0.00 | 73646696.87 | 85077306.02 | 0.00 | 0.465511E+11 | 0.00 | 0.81 |
July | 0.130525E+11 | 60299955.80 | 0.00 | 73044712.53 | 16653825.47 | 0.00 | 0.415297E+11 | 0.00 | 0.85 |
August | 0.148385E+11 | 0.00 | 0.00 | 69706050.29 | 0.00 | 0.00 | 0.361348E+11 | 0.00 | 0.87 |
September | 0.234918E+11 | 0.00 | 0.00 | 33378301.43 | 0.00 | 0.00 | 0.200608E+11 | 0.00 | 0.63 |
October | 0.351223E+11 | 0.00 | 0.00 | 3873050.47 | 0.00 | 0.100091E+10 | 0.398607E+10 | 0.00 | 0.36 |
November | 0.333403E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.630786E+10 | 0.00 | 0.00 | 0.30 |
December | 0.237826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190825E+11 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.303739E+12 | 70900452.16 | 0.00 | 0.314188E+09 | 0.101731E+09 | 0.540831E+11 | 0.197725E+12 | 0.00 | 0.50 |
Minimum of Months | 0.120468E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.397113E+11 | 60299955.80 | 0.00 | 73646696.87 | 85077306.02 | 0.190825E+11 | 0.465511E+11 | 0.00 | 0.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.367111E+11 | 0.00 | 0.00 | 105367.84 | 0.00 | 0.151022E+11 | 0.216724E+09 | 0.00 | 0.51 |
February | 0.359511E+11 | 0.00 | 0.00 | 1606420.69 | 0.00 | 0.858620E+10 | 0.125724E+10 | 0.00 | 0.51 |
March | 0.453240E+11 | 0.00 | 0.00 | 774211.58 | 0.00 | 0.520219E+10 | 0.980599E+09 | 0.00 | 0.55 |
April | 0.184138E+11 | 0.00 | 0.00 | 80523859.18 | 0.00 | 79525944.09 | 0.515679E+11 | 0.00 | 1.08 |
May | 0.218062E+11 | 0.00 | 0.00 | 82453613.40 | 0.00 | 7146699.04 | 0.523001E+11 | 0.00 | 1.17 |
June | 0.146144E+11 | 8445464.10 | 0.00 | 0.107649E+09 | 97474607.38 | 0.00 | 0.589711E+11 | 0.00 | 1.57 |
July | 0.142111E+11 | 90926741.69 | 0.00 | 0.117942E+09 | 19298820.72 | 0.00 | 0.543226E+11 | 0.00 | 1.64 |
August | 0.155122E+11 | 0.00 | 0.00 | 0.117719E+09 | 0.00 | 0.00 | 0.550815E+11 | 0.00 | 1.83 |
September | 0.209890E+11 | 0.00 | 0.00 | 85131592.55 | 0.00 | 0.00 | 0.429512E+11 | 0.00 | 1.43 |
October | 0.349531E+11 | 0.00 | 0.00 | 19003819.32 | 0.00 | 0.133047E+10 | 0.134670E+11 | 0.00 | 0.71 |
November | 0.386447E+11 | 0.00 | 0.00 | 63438.09 | 0.00 | 0.708210E+10 | 0.220296E+09 | 0.00 | 0.53 |
December | 0.275509E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221155E+11 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 0.324681E+12 | 99372205.79 | 0.00 | 0.612972E+09 | 0.116773E+09 | 0.595053E+11 | 0.331336E+12 | 0.00 | 1.00 |
Minimum of Months | 0.142111E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.453240E+11 | 90926741.69 | 0.00 | 0.117942E+09 | 97474607.38 | 0.221155E+11 | 0.589711E+11 | 0.00 | 1.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.474737E+11 | 0.00 | 0.00 | 37572775.93 | 0.00 | 0.104821E+11 | 0.271098E+11 | 0.00 | 0.54 |
February | 0.414781E+11 | 0.00 | 0.00 | 56063126.33 | 0.00 | 0.653912E+10 | 0.342244E+11 | 0.00 | 0.60 |
March | 0.519422E+11 | 0.00 | 0.00 | 21528720.25 | 0.00 | 0.495262E+10 | 0.188671E+11 | 0.00 | 0.53 |
April | 0.267373E+11 | 0.00 | 0.00 | 0.151736E+09 | 0.00 | 12269527.62 | 0.909993E+11 | 0.00 | 1.24 |
May | 0.330356E+11 | 0.00 | 0.00 | 98074336.02 | 0.00 | 24756517.73 | 0.706574E+11 | 0.00 | 1.08 |
June | 0.255319E+11 | 13888899.83 | 0.00 | 0.111363E+09 | 0.134841E+09 | 0.00 | 0.686154E+11 | 0.00 | 1.33 |
July | 0.230528E+11 | 0.109802E+09 | 0.00 | 0.143912E+09 | 33470782.20 | 0.00 | 0.694802E+11 | 0.00 | 1.48 |
August | 0.207523E+11 | 0.00 | 0.00 | 0.209258E+09 | 0.00 | 0.00 | 0.852470E+11 | 0.00 | 1.91 |
September | 0.246159E+11 | 0.00 | 0.00 | 0.222644E+09 | 0.00 | 0.00 | 0.951005E+11 | 0.00 | 1.90 |
October | 0.394639E+11 | 0.00 | 0.00 | 98165344.93 | 0.00 | 0.579026E+09 | 0.643006E+11 | 0.00 | 1.03 |
November | 0.462199E+11 | 0.00 | 0.00 | 36519557.75 | 0.00 | 0.552211E+10 | 0.225257E+11 | 0.00 | 0.56 |
December | 0.421758E+11 | 0.00 | 0.00 | 15623705.50 | 0.00 | 0.203155E+11 | 0.113380E+11 | 0.00 | 0.48 |
Annual Sum or Average | 0.422479E+12 | 0.123691E+09 | 0.00 | 0.120246E+10 | 0.168312E+09 | 0.484275E+11 | 0.658466E+12 | 0.00 | 1.06 |
Minimum of Months | 0.207523E+11 | 0.00 | 0.00 | 15623705.50 | 0.00 | 0.00 | 0.113380E+11 | 0.00 | 0.48 |
Maximum of Months | 0.519422E+11 | 0.109802E+09 | 0.00 | 0.222644E+09 | 0.134841E+09 | 0.203155E+11 | 0.951005E+11 | 0.00 | 1.91 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.427032E+11 | 0.00 | 0.00 | 1011338.41 | 0.00 | 0.114243E+11 | 0.104401E+10 | 0.00 | 0.54 |
February | 0.388288E+11 | 0.00 | 0.00 | 8010551.60 | 0.00 | 0.534158E+10 | 0.598744E+10 | 0.00 | 0.56 |
March | 0.484979E+11 | 0.00 | 0.00 | 4945633.99 | 0.00 | 0.249677E+10 | 0.469150E+10 | 0.00 | 0.60 |
April | 0.263422E+11 | 0.00 | 0.00 | 70575110.99 | 0.00 | 8748389.79 | 0.426317E+11 | 0.00 | 1.11 |
May | 0.275798E+11 | 0.00 | 0.00 | 85043653.57 | 0.00 | 0.00 | 0.490265E+11 | 0.00 | 1.25 |
June | 0.156328E+11 | 0.271121E+09 | 0.00 | 0.118579E+09 | 7139311.60 | 0.00 | 0.619305E+11 | 0.00 | 1.71 |
July | 0.150151E+11 | 0.120618E+09 | 0.00 | 0.152021E+09 | 7074074.48 | 0.00 | 0.586278E+11 | 0.00 | 1.85 |
August | 0.149990E+11 | 0.00 | 0.00 | 0.132468E+09 | 0.00 | 0.00 | 0.528597E+11 | 0.00 | 1.83 |
September | 0.260734E+11 | 0.00 | 0.00 | 64864905.43 | 0.00 | 0.00 | 0.334840E+11 | 0.00 | 1.40 |
October | 0.413390E+11 | 0.00 | 0.00 | 14928290.58 | 0.00 | 0.212399E+09 | 0.122448E+11 | 0.00 | 0.78 |
November | 0.420989E+11 | 0.00 | 0.00 | 1732040.28 | 0.00 | 0.504762E+10 | 0.173200E+10 | 0.00 | 0.57 |
December | 0.357467E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168313E+11 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.374857E+12 | 0.391739E+09 | 0.00 | 0.654180E+09 | 14213386.08 | 0.413626E+11 | 0.324260E+12 | 0.00 | 1.06 |
Minimum of Months | 0.149990E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.484979E+11 | 0.271121E+09 | 0.00 | 0.152021E+09 | 7139311.60 | 0.168313E+11 | 0.619305E+11 | 0.00 | 1.85 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.116763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293772E+10 | 0.00 | 0.00 | 0.28 |
February | 0.156018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209487E+10 | 0.00 | 0.00 | 0.28 |
March | 0.283450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137322E+10 | 0.00 | 0.00 | 0.31 |
April | 0.245982E+10 | 0.00 | 0.00 | 1559824.00 | 363377.42 | 0.331603E+09 | 0.144693E+10 | 0.00 | 0.42 |
May | 0.271982E+10 | 0.00 | 0.00 | 2560649.39 | 0.00 | 0.110573E+09 | 0.207176E+10 | 0.00 | 0.50 |
June | 0.152152E+10 | 232075.40 | 0.00 | 6248337.51 | 6930403.65 | 0.00 | 0.413849E+10 | 0.00 | 0.78 |
July | 0.137515E+10 | 2802957.68 | 0.00 | 6841728.26 | 803604.72 | 365254.20 | 0.403773E+10 | 0.00 | 0.84 |
August | 0.157281E+10 | 0.00 | 0.00 | 6065750.76 | 0.00 | 0.00 | 0.339119E+10 | 0.00 | 0.84 |
September | 0.234611E+10 | 0.00 | 0.00 | 2464025.53 | 0.00 | 68498345.62 | 0.157858E+10 | 0.00 | 0.59 |
October | 0.279267E+10 | 0.00 | 0.00 | 56069.31 | 0.00 | 0.732043E+09 | 0.132605E+09 | 0.00 | 0.35 |
November | 0.179796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180506E+10 | 0.00 | 0.00 | 0.30 |
December | 0.946153E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297048E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.230943E+11 | 3035033.09 | 0.00 | 25796384.77 | 8097385.78 | 0.124244E+11 | 0.167973E+11 | 0.00 | 0.48 |
Minimum of Months | 0.946153E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.283450E+10 | 2802957.68 | 0.00 | 6841728.26 | 6930403.65 | 0.297048E+10 | 0.413849E+10 | 0.00 | 0.84 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.184362E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263147E+10 | 0.00 | 0.00 | 0.48 |
February | 0.211527E+10 | 0.00 | 0.00 | 7771.55 | 0.00 | 0.187956E+10 | 18957333.42 | 0.00 | 0.49 |
March | 0.336345E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129181E+10 | 0.00 | 0.00 | 0.53 |
April | 0.161610E+10 | 1401356.98 | 0.00 | 6777680.11 | 0.00 | 0.143372E+09 | 0.450060E+10 | 0.00 | 0.98 |
May | 0.211004E+10 | 0.00 | 0.00 | 6972980.07 | 0.00 | 64444487.37 | 0.466583E+10 | 0.00 | 1.09 |
June | 0.151128E+10 | 418243.17 | 0.00 | 10008702.71 | 7569732.54 | 0.00 | 0.565470E+10 | 0.00 | 1.53 |
July | 0.125937E+10 | 7136723.61 | 0.00 | 11334321.39 | 892819.84 | 416337.11 | 0.546028E+10 | 0.00 | 1.61 |
August | 0.141317E+10 | 0.00 | 0.00 | 10921749.51 | 0.00 | 0.00 | 0.542715E+10 | 0.00 | 1.78 |
September | 0.186857E+10 | 0.00 | 0.00 | 6961001.25 | 0.00 | 22753591.29 | 0.382798E+10 | 0.00 | 1.32 |
October | 0.270128E+10 | 0.00 | 0.00 | 1147362.81 | 0.00 | 0.679499E+09 | 0.834995E+09 | 0.00 | 0.63 |
November | 0.228785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167385E+10 | 0.00 | 0.00 | 0.51 |
December | 0.145386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281113E+10 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.235439E+11 | 8956323.76 | 0.00 | 54131569.39 | 8462552.38 | 0.111983E+11 | 0.303905E+11 | 0.00 | 0.95 |
Minimum of Months | 0.125937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.336345E+10 | 7136723.61 | 0.00 | 11334321.39 | 7569732.54 | 0.281113E+10 | 0.565470E+10 | 0.00 | 1.78 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.322165E+10 | 0.00 | 0.00 | 2056392.21 | 0.00 | 0.247287E+10 | 0.155305E+10 | 0.00 | 0.50 |
February | 0.312734E+10 | 0.00 | 0.00 | 3531632.19 | 0.00 | 0.168549E+10 | 0.226084E+10 | 0.00 | 0.55 |
March | 0.456920E+10 | 0.00 | 0.00 | 979012.21 | 0.00 | 0.155758E+10 | 0.894364E+09 | 0.00 | 0.52 |
April | 0.234439E+10 | 0.00 | 0.00 | 13592652.40 | 590196.28 | 0.373887E+09 | 0.859659E+10 | 0.00 | 1.17 |
May | 0.358066E+10 | 0.00 | 0.00 | 8567917.55 | 0.00 | 0.225072E+09 | 0.641280E+10 | 0.00 | 1.05 |
June | 0.287464E+10 | 585247.76 | 0.00 | 10430889.31 | 11066179.52 | 5737506.82 | 0.663954E+10 | 0.00 | 1.31 |
July | 0.228007E+10 | 2582848.63 | 0.00 | 14022964.28 | 3623811.90 | 0.00 | 0.719107E+10 | 0.00 | 1.48 |
August | 0.211278E+10 | 0.00 | 0.00 | 19741785.30 | 0.00 | 0.00 | 0.875156E+10 | 0.00 | 1.88 |
September | 0.238463E+10 | 0.00 | 0.00 | 20192295.36 | 0.00 | 6256419.25 | 0.919681E+10 | 0.00 | 1.81 |
October | 0.316390E+10 | 0.00 | 0.00 | 7571027.57 | 0.00 | 0.801205E+09 | 0.519495E+10 | 0.00 | 0.93 |
November | 0.337828E+10 | 0.00 | 0.00 | 1994283.42 | 0.00 | 0.166603E+10 | 0.132801E+10 | 0.00 | 0.53 |
December | 0.250446E+10 | 0.00 | 0.00 | 853432.28 | 0.00 | 0.336207E+10 | 0.596440E+09 | 0.00 | 0.46 |
Annual Sum or Average | 0.355420E+11 | 3168096.39 | 0.00 | 0.103534E+09 | 15280187.70 | 0.121562E+11 | 0.586160E+11 | 0.00 | 1.02 |
Minimum of Months | 0.211278E+10 | 0.00 | 0.00 | 853432.28 | 0.00 | 0.00 | 0.596440E+09 | 0.00 | 0.46 |
Maximum of Months | 0.456920E+10 | 2582848.63 | 0.00 | 20192295.36 | 11066179.52 | 0.336207E+10 | 0.919681E+10 | 0.00 | 1.88 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.253161E+10 | 0.00 | 0.00 | 38750.19 | 0.00 | 0.241027E+10 | 45504586.99 | 0.00 | 0.54 |
February | 0.274294E+10 | 0.00 | 0.00 | 499093.38 | 0.00 | 0.138143E+10 | 0.440402E+09 | 0.00 | 0.55 |
March | 0.399532E+10 | 0.00 | 0.00 | 327568.63 | 0.00 | 0.959225E+09 | 0.308856E+09 | 0.00 | 0.60 |
April | 0.279543E+10 | 0.00 | 0.00 | 6566654.34 | 450916.65 | 0.153110E+09 | 0.386757E+10 | 0.00 | 1.09 |
May | 0.296816E+10 | 0.00 | 0.00 | 8016203.25 | 0.00 | 66517393.15 | 0.460200E+10 | 0.00 | 1.23 |
June | 0.192940E+10 | 21377860.74 | 0.00 | 11604111.17 | 0.00 | 0.00 | 0.597536E+10 | 0.00 | 1.72 |
July | 0.148716E+10 | 4482552.28 | 0.00 | 15058402.36 | 1000364.70 | 0.00 | 0.607128E+10 | 0.00 | 1.84 |
August | 0.165063E+10 | 0.00 | 0.00 | 12523893.12 | 0.00 | 0.00 | 0.524466E+10 | 0.00 | 1.82 |
September | 0.266105E+10 | 0.00 | 0.00 | 5668355.06 | 0.00 | 7595560.04 | 0.311199E+10 | 0.00 | 1.37 |
October | 0.333753E+10 | 0.00 | 0.00 | 1167971.53 | 0.00 | 0.588249E+09 | 0.992609E+09 | 0.00 | 0.75 |
November | 0.297547E+10 | 0.00 | 0.00 | 102124.01 | 0.00 | 0.132731E+10 | 0.116950E+09 | 0.00 | 0.56 |
December | 0.197092E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.277870E+10 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.310456E+11 | 25860413.03 | 0.00 | 61573127.02 | 1451281.35 | 0.967241E+10 | 0.307772E+11 | 0.00 | 1.05 |
Minimum of Months | 0.148716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.399532E+10 | 21377860.74 | 0.00 | 15058402.36 | 1000364.70 | 0.277870E+10 | 0.607128E+10 | 0.00 | 1.84 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 3178123.58 | 0.00 | 0.00 | 0.637373E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7771219.41 | 0.00 | 0.00 | 0.561725E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 13511238.17 | 0.00 | 0.00 | 0.622799E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 17690338.74 | 0.00 | 0.00 | 0.465757E+09 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 4171452.69 | 0.00 | 0.00 | 0.471979E+09 | 0.00 | 0.29 |
June | 0.00 | 140285.21 | 0.00 | 8951698.22 | 0.00 | 0.00 | 0.322283E+09 | 0.00 | 0.30 |
July | 0.00 | 0.00 | 0.00 | 13220305.46 | 0.00 | 0.00 | 0.226884E+09 | 0.00 | 0.28 |
August | 0.00 | 0.00 | 0.00 | 19344540.74 | 0.00 | 0.00 | 0.220686E+09 | 0.00 | 0.31 |
September | 0.00 | 0.00 | 0.00 | 4096040.89 | 0.00 | 0.00 | 0.311055E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 8581596.17 | 0.00 | 0.00 | 0.462108E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 12459962.15 | 0.00 | 0.00 | 0.529499E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 16872369.26 | 0.00 | 0.00 | 0.611529E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 140285.21 | 0.00 | 0.129849E+09 | 0.00 | 0.00 | 0.544368E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3178123.58 | 0.00 | 0.00 | 0.220686E+09 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 140285.21 | 0.00 | 19344540.74 | 0.00 | 0.00 | 0.637373E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 49910739.15 | 0.00 | 0.00 | 17841616.34 | 0.00 | 0.00 | 0.633813E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 62953578.46 | 0.00 | 0.00 | 0.563158E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.117202E+09 | 0.00 | 0.00 | 0.624566E+10 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 0.163594E+09 | 0.00 | 0.00 | 0.467105E+10 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 34586652.39 | 0.00 | 0.00 | 0.472954E+10 | 0.00 | 0.29 |
June | 0.00 | 1281498.97 | 0.00 | 82285192.01 | 0.00 | 0.00 | 0.323457E+10 | 0.00 | 0.30 |
July | 0.00 | 0.00 | 0.00 | 0.123490E+09 | 0.00 | 0.00 | 0.228005E+10 | 0.00 | 0.28 |
August | 0.00 | 0.00 | 0.00 | 0.182045E+09 | 0.00 | 0.00 | 0.221943E+10 | 0.00 | 0.31 |
September | 0.00 | 0.00 | 0.00 | 34013409.02 | 0.00 | 0.00 | 0.313260E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 72066698.22 | 0.00 | 0.00 | 0.463788E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.106076E+09 | 0.00 | 0.00 | 0.531346E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.145054E+09 | 0.00 | 0.00 | 0.613788E+10 | 0.00 | 0.28 |
Annual Sum or Average | 49910739.15 | 1281498.97 | 0.00 | 0.114121E+10 | 0.00 | 0.00 | 0.545718E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 17841616.34 | 0.00 | 0.00 | 0.221943E+10 | 0.00 | 0.28 |
Maximum of Months | 49910739.15 | 1281498.97 | 0.00 | 0.182045E+09 | 0.00 | 0.00 | 0.633813E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.217835E+09 | 0.00 | 0.00 | 726042.12 | 0.00 | 0.00 | 0.418808E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 5197823.55 | 0.00 | 0.00 | 0.564320E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 10643668.78 | 0.00 | 0.00 | 0.625661E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 15826928.30 | 0.00 | 0.00 | 0.467634E+09 | 0.00 | 0.29 |
May | 323465.59 | 0.00 | 0.00 | 2995034.36 | 0.00 | 0.00 | 0.473257E+09 | 0.00 | 0.29 |
June | 0.00 | 133271.93 | 0.00 | 7983287.09 | 0.00 | 0.00 | 0.323945E+09 | 0.00 | 0.30 |
July | 0.00 | 0.00 | 0.00 | 12183519.63 | 0.00 | 0.00 | 0.228334E+09 | 0.00 | 0.28 |
August | 0.00 | 0.00 | 0.00 | 17988764.01 | 0.00 | 0.00 | 0.222334E+09 | 0.00 | 0.31 |
September | 0.00 | 0.00 | 0.00 | 2926341.45 | 0.00 | 0.00 | 0.314756E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 6203312.47 | 0.00 | 0.00 | 0.465398E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 9461216.05 | 0.00 | 0.00 | 0.532743E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 13340814.93 | 0.00 | 0.00 | 0.614991E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.218158E+09 | 133271.93 | 0.00 | 0.105477E+09 | 0.00 | 0.00 | 0.525218E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 726042.12 | 0.00 | 0.00 | 0.222334E+09 | 0.00 | 0.28 |
Maximum of Months | 0.217835E+09 | 133271.93 | 0.00 | 17988764.01 | 0.00 | 0.00 | 0.625661E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.505725E+09 | 0.00 | 0.00 | 0.423732E+12 | 0.00 | 9.35 |
February | 0.00 | 0.00 | 0.00 | 0.939869E+09 | 0.00 | 0.00 | 0.648092E+12 | 0.00 | 15.88 |
March | 0.00 | 0.00 | 0.00 | 0.142958E+10 | 0.00 | 0.00 | 0.102598E+13 | 0.00 | 24.22 |
April | 0.00 | 0.00 | 0.00 | 0.224768E+10 | 0.00 | 0.00 | 0.122151E+13 | 0.00 | 36.36 |
May | 0.00 | 0.00 | 0.00 | 0.554716E+09 | 0.00 | 0.00 | 0.391221E+12 | 0.00 | 13.06 |
June | 0.00 | 263028.90 | 0.00 | 0.113481E+10 | 0.00 | 0.00 | 0.572941E+12 | 0.00 | 27.35 |
July | 0.00 | 20739977.11 | 0.00 | 0.204720E+10 | 0.00 | 0.00 | 0.766163E+12 | 0.00 | 39.57 |
August | 0.00 | 0.00 | 0.00 | 0.273644E+10 | 0.00 | 0.00 | 0.815731E+12 | 0.00 | 46.62 |
September | 0.00 | 0.00 | 0.00 | 0.563868E+09 | 0.00 | 0.00 | 0.356728E+12 | 0.00 | 17.24 |
October | 0.00 | 0.00 | 0.00 | 0.999487E+09 | 0.00 | 0.00 | 0.653087E+12 | 0.00 | 20.79 |
November | 0.00 | 0.00 | 0.00 | 0.145914E+10 | 0.00 | 0.00 | 0.939784E+12 | 0.00 | 25.12 |
December | 0.00 | 0.00 | 0.00 | 0.206575E+10 | 0.00 | 0.00 | 0.130938E+13 | 0.00 | 28.85 |
Annual Sum or Average | 0.00 | 21003006.01 | 0.00 | 0.166843E+11 | 0.00 | 0.00 | 0.912435E+13 | 0.00 | 25.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.505725E+09 | 0.00 | 0.00 | 0.356728E+12 | 0.00 | 9.35 |
Maximum of Months | 0.00 | 20739977.11 | 0.00 | 0.273644E+10 | 0.00 | 0.00 | 0.130938E+13 | 0.00 | 46.62 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:26:47
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.146661E+12 | 0.303980E+10 | 0.00 | 0.236078E+13 | 0.118753E+12 |
February | 0.236415E+12 | 0.431076E+10 | 0.00 | 0.241753E+13 | 0.172574E+12 |
March | 0.283998E+12 | 0.269616E+10 | 0.00 | 0.305623E+13 | 0.260468E+12 |
April | 0.731895E+12 | 0.333952E+10 | 0.00 | 0.351240E+13 | 0.420169E+12 |
May | 0.903260E+12 | 0.795660E+10 | 0.00 | 0.265573E+13 | 0.169329E+12 |
June | 0.906474E+12 | 0.627709E+10 | 0.00 | 0.284089E+13 | 0.438469E+12 |
July | 0.914141E+12 | 0.599721E+10 | 0.00 | 0.301739E+13 | 0.780119E+12 |
August | 0.746920E+12 | 0.441945E+10 | 0.00 | 0.300409E+13 | 0.123996E+13 |
September | 0.552642E+12 | 0.473654E+10 | 0.00 | 0.264722E+13 | 0.359413E+12 |
October | 0.254818E+12 | 0.464063E+10 | 0.00 | 0.277013E+13 | 0.173632E+12 |
November | 0.114569E+12 | 0.569494E+10 | 0.00 | 0.288266E+13 | 0.244215E+12 |
December | 0.563345E+11 | 0.772637E+10 | 0.00 | 0.314394E+13 | 0.356390E+12 |
Annual Sum or Average | 0.584813E+13 | 0.608351E+11 | 0.00 | 0.343090E+14 | 0.473349E+13 |
Minimum of Months | 0.563345E+11 | 0.269616E+10 | 0.00 | 0.236078E+13 | 0.118753E+12 |
Maximum of Months | 0.914141E+12 | 0.795660E+10 | 0.00 | 0.351240E+13 | 0.123996E+13 |