Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2024-07-03 12:21:57
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 31627.62 | 682.80 | 682.80 |
Net Site Energy | 31627.62 | 682.80 | 682.80 |
Total Source Energy | 93786.44 | 2024.73 | 2024.73 |
Net Source Energy | 93786.44 | 2024.73 | 2024.73 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 3062.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1304.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3222.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 356.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2566.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2839.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 320.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 370.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3383.68 |
Humidification | 2430.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 904.09 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 478.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 28565.58 | 3062.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6567.95 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 3062.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1304.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3222.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 356.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 55.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2505.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2839.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 320.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 370.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3383.68 |
Humidification | General | 2430.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 904.09 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 478.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 3062.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1304.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3222.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 356.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 2566.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2839.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 320.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 370.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3383.68 |
Humidification | Unassigned | 2430.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 904.09 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 478.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 77.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 167.17 | 66.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Other | 372.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 616.70 | 66.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 77.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 167.17 | 66.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Other | 372.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 616.70 | 66.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 28565.576 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 28565.576 | 100.00 |
Total On-Site and Utility Electric Sources | 28565.576 | 100.00 |
Total Electricity End Uses | 28565.576 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 6567.95 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 6567.95 | 100.00 |
Total Water End Uses | 6567.95 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 102.33 |
Time Setpoint Not Met During Occupied Cooling | 1018.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5936.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 8.6849 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 8.6849 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 8.7339 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 8.7339 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.6849 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 8.6849 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 8.6849 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 8.6849 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 8.6849 | 18.58 | 484.4232 | |
Total | 46320.38 | 8.7339 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 8.7339 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.6845 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 08-AUG-15:39 | 09-JAN-07:19 | - | - | - | - | - | - | - | - | - | - | 25-JUL-12:39 |
Heating | 0.00 | 2312548.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 416144.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 280450.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 233302.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 350437.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 49815.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 82444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 6262.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 35347.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2232576.78 | 2312548.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 2312548.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 416144.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 280450.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3430.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 350437.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 49815.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 82444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 6262.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 35347.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 3319.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4131.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 10206.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1129.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8128.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8992.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1014.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1172.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 7696.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1514.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 90467.18 | 3319.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 71.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 89.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 220.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 24.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 194.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 21.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 25.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 166.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 32.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1953.08 | 71.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 71.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 89.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 220.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 24.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 194.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 21.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 25.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 166.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 32.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1953.08 | 71.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 6.36 | 0.333165 | 0.000000 | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 6.70 | 0.283766 | 0.299000 | 2.00 | 0.756709 | 0.500000 | 0.001343 | 0.000209 | 2.00 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 63.10 | 0.301431 | 0.312000 | 19.69 | 0.803816 | 0.500000 | 0.001264 | 0.004225 | 19.69 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 6.11 | 0.311104 | 0.332000 | 2.03 | 0.829610 | 0.500000 | 0.001225 | 0.000948 | 3.69 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.14 | 0.210324 | 0.222000 | 0.252078 | 0.560864 | 0.500000 | 0.001811 | 0.000167 | 0.652571 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.60 | 0.096448 | 0.200000 | 0.319147 | 0.300000 | 0.500000 | 0.003950 | 0.000115 | 0.447811 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.94 | 0.122907 | 0.200000 | 0.388628 | 0.327752 | 0.500000 | 0.003100 | 0.000185 | 0.721971 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.95 | 0.079115 | 0.200000 | 0.389068 | 0.300000 | 0.500000 | 0.004816 | 0.000096 | 0.389068 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 10.64 | 0.224451 | 0.233000 | 2.48 | 0.598537 | 0.500000 | 0.001697 | 0.002332 | 9.10 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 17.06 | 0.090219 | 0.200000 | 3.41 | 0.300000 | 0.500000 | 0.004223 | 0.001548 | 6.04 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 19.73 | 0.121032 | 0.200000 | 3.95 | 0.322752 | 0.500000 | 0.003148 | 0.002365 | 9.22 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 18.22 | 0.084451 | 0.200000 | 3.64 | 0.300000 | 0.500000 | 0.004511 | 0.001516 | 5.91 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.20 | 0.199206 | 0.213000 | 0.255357 | 0.531217 | 0.500000 | 0.001913 | 0.000300 | 1.17 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.71 | 0.090197 | 0.200000 | 0.341265 | 0.300000 | 0.500000 | 0.004224 | 0.000198 | 0.772836 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 2.10 | 0.113602 | 0.200000 | 0.420460 | 0.302939 | 0.500000 | 0.003354 | 0.000304 | 1.19 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.91 | 0.080421 | 0.200000 | 0.382749 | 0.300000 | 0.500000 | 0.004738 | 0.000197 | 0.769764 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | User-Specified Rated Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 23834.74 | 0.000209 | 497.68 | |
CORE_MID VAV BOX REHEAT COIL | 482960.26 | 0.004225 | 11860.29 | |
CORE_TOP VAV BOX REHEAT COIL | 108321.34 | 0.000948 | 2858.27 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 19137.46 | 0.000167 | 504.75 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 13130.89 | 0.000115 | 346.30 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 21168.77 | 0.000185 | 558.27 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 10995.86 | 0.000096 | 285.31 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 266558.38 | 0.002332 | 7028.40 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 176916.65 | 0.001548 | 4664.70 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 270352.01 | 0.002365 | 7128.36 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 173340.46 | 0.001516 | 4570.46 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 34328.80 | 0.000300 | 905.02 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 22642.41 | 0.000198 | 596.92 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 34748.04 | 0.000304 | 916.07 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 22552.36 | 0.000197 | 594.55 | |
VAV_BOT WITH REHEAT HEATING COIL | 102546.65 | 0.000897 | 1571.64 | |
VAV_MID WITH REHEAT HEATING COIL | 1035805.46 | 0.009062 | 15555.85 | |
VAV_TOP WITH REHEAT HEATING COIL | 101090.07 | 0.000884 | 1571.25 | |
CAV_BAS HEATING COIL | 304147.05 | 0.000875 | 2621.31 | 100000.00 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.577319 |
DATACENTER_MID_ZN_6 DIRECT AIR | 5.55 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.564832 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 28.14 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 6.66 | 3.35 | 13.32 | 3.35 | 11.10 | 11.10 | 0.300000 | 0.302075 | 11.10 |
VAV_MID WITH REHEAT | 64.38 | 33.17 | 128.76 | 45.24 | 103.57 | 103.57 | 0.300000 | 0.436836 | 103.57 |
VAV_TOP WITH REHEAT | 6.52 | 3.43 | 13.04 | 7.59 | 11.69 | 11.69 | 0.300000 | 0.649019 | 11.69 |
CAV_BAS | 0.000000 | 0.000000 | 6.36 | 1.20 | 6.36 | 6.36 | 1.00 | 0.188793 | 6.36 |
AIRLOOP DATACENTER BASEMENT | 28.14 | 28.14 | 28.14 | 28.14 | 28.14 | 28.14 | 1.00 | 0.999995 | 28.14 |
AIRLOOP DATACENTER BOT | 0.577319 | 0.577319 | 0.577319 | 0.577319 | 0.577319 | 0.577319 | 1.00 | 1.00 | 0.577319 |
AIRLOOP DATACENTER MID | 5.55 | 5.55 | 5.55 | 5.55 | 5.55 | 5.55 | 1.00 | 1.00 | 5.55 |
AIRLOOP DATACENTER TOP | 0.564832 | 0.564832 | 0.564832 | 0.564832 | 0.564832 | 0.564832 | 1.00 | 1.00 | 0.564832 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 11.10 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 103.57 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 11.69 | |
CAV_BAS_OA_CONTROLLER | 6.36 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 28.14 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.577319 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 5.55 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.564832 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 26.15 | 6.67 | 10.68 | 0.007087 | 0.007000 | 186642.62 | 0.005338 | 11.10 |
VAV_MID WITH REHEAT COOLING COIL | 26.34 | 6.67 | 10.68 | 0.007084 | 0.007000 | 1761804.38 | 0.050387 | 103.57 |
VAV_TOP WITH REHEAT COOLING COIL | 26.05 | 6.67 | 10.68 | 0.007082 | 0.007000 | 195185.59 | 0.005582 | 11.69 |
CAV_BAS COOLING COIL | 25.83 | 6.67 | 10.67 | 0.007245 | 0.007000 | 107452.80 | 0.003073 | 6.36 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 11.10 |
VAV_MID WITH REHEAT FAN | 103.57 |
VAV_TOP WITH REHEAT FAN | 11.69 |
CAV_BAS FAN | 6.36 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.005338 | 0.000089 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000897 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.050387 | 0.000009 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.009062 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.005582 | 0.000085 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000884 | |
CAV_BAS_COOLC_CONTROLLER | 0.003073 | 0.000155 |
CAV_BAS_HEATC_CONTROLLER | 0.000875 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 28.14 | 534450.68 | 300859.83 | 0.013089 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.577319 | 10659.37 | 6063.48 | 0.000261 |
AIRLOOP DATACENTER MID COOLING COIL | 5.55 | 102553.92 | 58326.61 | 0.002512 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.564832 | 10430.49 | 5932.67 | 0.000255 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 28.14 | 28.14 | 28.14 | 28.14 | 534450.68 | 534450.68 | 24207.99 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.577319 | 0.577319 | 0.577319 | 0.577319 | 10659.37 | 10659.37 | 1118.31 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 5.55 | 5.55 | 5.55 | 5.55 | 102553.92 | 102553.92 | 11183.09 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.564832 | 0.564832 | 0.564832 | 0.564832 | 10430.49 | 10430.49 | 1118.31 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 28.14 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.577319 |
AIRLOOP DATACENTER MID SUPPLY FAN | 5.55 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.564832 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 28.14 | 534450.68 | 0.013089 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.577319 | 10659.37 | 0.000261 |
AIRLOOP DATACENTER MID HEATING COIL | 5.55 | 102553.92 | 0.002512 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.564832 | 10430.49 | 0.000255 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 24207.99 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 1118.31 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 11183.09 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 1118.31 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000219 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.064381 | 10511.41 | |
HEATSYS1 PUMP | 0.026424 | 7957.76 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.064381 | 7.73 |
HEATSYS1 | 0.026424 | 3.17 |
COOLSYS1_SUPPLY | 0.064381 | 7.73 |
SINGLE WATER PLANT LOOP | 0.016117 | 1.93 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.064381 | 0.064381 | 270238.34 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 3020430.61 | 3020430.61 | 0.026424 |
CENTRAL BOILER | 663869.50 | 649418.88 | 0.016117 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.032190 | 3638.70 |
COOLSYS1 CHILLER2 PUMP | 0.032190 | 3638.70 |
PLANT CIRC PUMP | 0.016117 | 4110.56 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.064381 | 0.032377 | 1132053.97 | 1132054.12 | 0.057005 |
COOLSYS1 CHILLER2 | 0.064381 | 0.032377 | 1132053.97 | 1132054.12 | 0.057005 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | U-factor Times Area Value at High Fan Speed [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/K] | |
CENTRAL TOWER | 0.016117 | 160026.79 | 81012.44 | 80013.39 | 7879.72 | 48607.47 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.114009 | 13.68 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.114009 | 28226.15 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 49.95 | 1356777.49 | 9.99 | 169597.19 |
TOWERWATERSYS COOLTOWER 2 | 49.95 | 1356777.49 | 9.99 | 169597.19 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.058705 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 7.03 | 29.40 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 8.685 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 13.527 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 8.685 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 493.108 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 24139.153 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 24139.153 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 6806.209 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6806.209 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 0.8952 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 0.8506 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.077 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.3542 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9497 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.008 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7608 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.747 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | -0.25194710E-14 | 0.31545203E-16 | -0.15133332E-09 | 0.44281407E-16 |
51 | 8 | 0.22101568E-07 | 0.12077324E-12 | 0.38017447E-03 | -0.25130244E-09 |
52 | 7 | -0.12312625E-01 | 0.62550027E-08 | -0.23188143E-01 | 0.13999903E-03 |
53 | 6 | 0.40728147 | 0.21773539E-05 | 0.47373573 | -0.47705255E-02 |
54 | 5 | -5.2094091 | 0.81341902E-04 | -4.4538940 | 0.63417525E-01 |
55 | 4 | 33.086216 | 0.66572093E-03 | 21.489723 | -0.42322968 |
56 | 3 | -111.40360 | 0.14515221E-02 | -55.721658 | 1.5177572 |
57 | 2 | 197.30704 | 0.81680373E-03 | 77.964377 | -2.9035099 |
58 | 1 | -171.22951 | 0.87228510E-04 | -55.280715 | 2.7467265 |
59 | 0 | 57.057407 | 0.49677855E-06 | 15.554344 | |
60 | 9 | -0.24471812E-14 | 0.33150161E-16 | -0.15341684E-09 | 0.41895861E-16 |
61 | 8 | 0.22394247E-07 | 0.11501389E-12 | 0.38323131E-03 | -0.25463030E-09 |
62 | 7 | -0.12403778E-01 | 0.59379868E-08 | -0.23319368E-01 | 0.14103548E-03 |
63 | 6 | 0.40975819 | 0.20644311E-05 | 0.47584355 | -0.47997200E-02 |
64 | 5 | -5.2335779 | 0.77040749E-04 | -4.4700764 | 0.63717207E-01 |
65 | 4 | 33.193114 | 0.62990908E-03 | 21.552961 | -0.42464900 |
66 | 3 | -111.63102 | 0.13722529E-02 | -55.846672 | 1.5210429 |
67 | 2 | 197.53241 | 0.77160263E-03 | 78.079059 | -2.9070889 |
68 | 1 | -171.31275 | 0.82342669E-04 | -55.314112 | 2.7481854 |
69 | 0 | 57.057407 | 0.46858505E-06 | 15.548868 | |
70 | 9 | -0.15654789E-15 | 0.36780279E-16 | -0.14275499E-09 | -0.53833073E-18 |
71 | 8 | 0.20895136E-07 | 0.14393424E-12 | 0.36742668E-03 | -0.23758489E-09 |
72 | 7 | -0.11931991E-01 | 0.75543961E-08 | -0.22640018E-01 | 0.13567108E-03 |
73 | 6 | 0.39693859 | 0.26436989E-05 | 0.46492102 | -0.46486079E-02 |
74 | 5 | -5.1084706 | 0.99216708E-04 | -4.3861655 | 0.62165936E-01 |
75 | 4 | 32.639712 | 0.81537030E-03 | 21.224928 | -0.41730137 |
76 | 3 | -110.45353 | 0.17843548E-02 | -55.198128 | 1.5040313 |
77 | 2 | 196.36533 | 0.10073836E-02 | 77.484335 | -2.8885557 |
78 | 1 | -170.88163 | 0.10790658E-03 | -55.141337 | 2.7406295 |
79 | 0 | 57.057407 | 0.61658484E-06 | 15.577537 | |
80 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
81 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
82 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
83 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
84 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
85 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
86 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
87 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
88 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
89 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
90 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
91 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
92 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
93 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
94 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
95 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
96 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
97 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
98 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
99 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
100 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
101 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
102 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
103 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
104 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
105 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
106 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
107 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
108 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
109 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
110 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
111 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
112 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
113 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
114 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
115 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
116 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
117 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
118 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
119 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 | |
120 | 7 | -0.11729247E-08 | -0.12287178E-15 | 0.68000855E-14 | -0.85819789E-16 |
121 | 6 | 0.99010087E-05 | 0.68275672E-08 | 0.31776201E-02 | -0.26656541E-04 |
122 | 5 | -0.71743827E-03 | 0.40498262E-05 | -0.22302824 | 0.19500041E-02 |
123 | 4 | 0.16534150E-01 | 0.18445051E-03 | 4.8179460 | -0.45153479E-01 |
124 | 3 | -0.14527752 | 0.14677644E-02 | -37.955880 | 0.39792938 |
125 | 2 | 0.51595076 | 0.24428280E-02 | 116.35639 | -1.4162330 |
126 | 1 | -0.74475336 | 0.74501918E-03 | -143.83221 | 2.0478056 |
127 | 0 | 0.36311555 | 0.17917760E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.36_SHGC_EAST_0.4 | 35 | 1 | VerySmooth | 2.045 | 2.045 | 1.000 | 0.401 | ||
2 | WINDOW_U_0.36_SHGC_SOUTH_0.4 | 36 | 1 | VerySmooth | 2.045 | 2.045 | 1.000 | 0.401 | ||
3 | WINDOW_U_0.36_SHGC_WEST_0.4 | 37 | 1 | VerySmooth | 2.045 | 2.045 | 1.000 | 0.401 | ||
4 | WINDOW_U_0.36_SHGC_NORTH_0.4 | 38 | 1 | VerySmooth | 2.045 | 2.045 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.65598E-002 | 0.31435 | 0.48154 | 0.48154 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.65598E-002 | 0.31435 | 0.48154 | 0.48154 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.65598E-002 | 0.31435 | 0.48154 | 0.48154 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.65598E-002 | 0.31435 | 0.48154 | 0.48154 | 0.44000 | 0.13397 | 0.17027 | 0.00000 | 0.84000 | 0.84000 | 0.11562 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 1.973E-005 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7114E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.7138E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.6318E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.6338E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.9702E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9717E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7740E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7748E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7655E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.9212E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.6773E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.8128E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0080E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1195E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7969E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8551E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1825 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.9759E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.2093 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1158 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1197 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9531E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0165E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7447E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7778E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.9872E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.6910E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.8865E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0181E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1586E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7974E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.8568E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7112E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.7140E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.6316E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.6341E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.9701E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9720E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7739E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7747E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.9174E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.4164E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.8025E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.3880E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.9588E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.1161E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.7428E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.7830E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.0221E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8990E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.8391E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7084E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.3623E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0756E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.2230E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.9536E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.7592E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.8797E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.5933E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.6821E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.9106E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.9465E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.7430E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.7836E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.0492E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0516E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5843E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5863E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2615E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2630E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7740E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7749E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1042E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.2430E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6306E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7435E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2998E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3855E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7975E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8569E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.0464E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6651E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.8839E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0271E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4674E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3448E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.0165E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7442E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1014E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.2438E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6261E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7371E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2918E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3604E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7969E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.8551E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.0490E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0514E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5841E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5860E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2613E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2625E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7739E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7748E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7277E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.8556E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2654E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.3581E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.1943E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.2259E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7431E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.7837E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.2155E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.1514E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.5261E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7481E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.0374E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.5330E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2230E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9536E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.8323E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.1338E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.4051E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.7328E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2377E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.3710E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.7428E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.7829E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1875 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1380 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.2098 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1587 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1346 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 7.3171E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.1425E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.0380E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 9.4930E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 5.5725E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 9.2936E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 5.3636E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.6873E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.4880E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.2997E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.0728E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 6.2218E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 4.1364E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.9075E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.2665E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.4534E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.4117E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 6.1425E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.0375E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.4507E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.5428E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.6773E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.0389E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.2041E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.7716E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.2997E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.0728E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1875 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1382 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.2098 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1590 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1348 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 7.3346E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.1557E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.0447E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 9.4994E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 5.5813E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 9.3010E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 5.3724E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.7004E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.4977E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.3129E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.0795E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 6.2221E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 4.1412E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.9082E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.2703E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.4605E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.4162E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 6.1557E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.0442E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.4543E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.5492E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.6813E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.0447E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.2149E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.7794E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.3129E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.0795E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 76974.39564 | 76974.39564 | 6.35699 | 6.35699 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:50:00 | -27.60000 | 3.41898E-004 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 81169.02131 | 81169.02131 | 6.70286 | 6.70286 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 6186.34171 | 6186.34171 | 0.30027 | 1.07782 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 764295.25653 | 764295.25653 | 63.10050 | 63.10050 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 309593.95428 | 309593.95428 | 14.97186 | 14.97186 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 74057.27327 | 74057.27327 | 6.11386 | 6.11386 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 21.56000 | 6.28881E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 75828.07536 | 75828.07536 | 3.68991 | 3.68991 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 13630.98387 | 13630.98387 | 1.13549 | 1.13549 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 33.40000 | 6.30683E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 13392.46895 | 13392.46895 | 0.65257 | 0.65257 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 19156.21502 | 19156.21502 | 1.59573 | 1.59573 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 24.09333 | 6.29258E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 9188.46960 | 9188.46960 | 0.44781 | 0.44781 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 23326.61133 | 23326.61133 | 1.94314 | 1.94314 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.00000 | 6.30621E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 14812.56662 | 14812.56662 | 0.72197 | 0.72197 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 23353.15183 | 23353.15183 | 1.94534 | 1.94534 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.36000 | 6.30211E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 7571.01931 | 7571.01931 | 0.36873 | 0.36873 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 127730.97327 | 127730.97327 | 10.64020 | 10.64020 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.40000 | 6.30683E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 186501.00662 | 186501.00662 | 9.09508 | 9.09508 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 204790.16590 | 204790.16590 | 17.05915 | 17.05915 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 25.50667 | 6.29470E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 123779.83158 | 123779.83158 | 6.03673 | 6.03673 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 236881.42868 | 236881.42868 | 19.73247 | 19.73247 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.13333 | 6.30642E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 189153.21238 | 189153.21238 | 9.22471 | 9.22471 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 218775.28010 | 218775.28010 | 18.22411 | 18.22411 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 30.09333 | 6.30170E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 121279.37119 | 121279.37119 | 5.91457 | 5.91457 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 14391.86413 | 14391.86413 | 1.19886 | 1.19886 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.24000 | 6.30658E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 24015.34683 | 24015.34683 | 1.17169 | 1.17169 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 20483.96914 | 20483.96914 | 1.70632 | 1.70632 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 25.96000 | 6.29539E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 15839.76974 | 15839.76974 | 0.77284 | 0.77284 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 25237.46057 | 25237.46057 | 2.10230 | 2.10230 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 33.26667 | 6.30663E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 24308.45059 | 24308.45059 | 1.18601 | 1.18601 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 22974.02300 | 22974.02300 | 1.91375 | 1.91375 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.36000 | 6.30211E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 15776.77432 | 15776.77432 | 0.76976 | 0.76976 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60000 | 3.41898E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8786.71323 | 8786.71323 | 0.57732 | 0.57732 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 26.28000 | 6.29588E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -27.60000 | 3.41898E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 84514.03071 | 84514.03071 | 5.55290 | 5.55290 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 26.28000 | 6.29588E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -27.60000 | 3.41898E-004 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8596.65112 | 8596.65112 | 0.56483 | 0.56483 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 26.28000 | 6.29588E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -27.60000 | 3.41898E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 372393.40113 | 428252.41130 | 24.46730 | 28.13740 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 18.84000 | 6.28481E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 01:10:00 | -27.60000 | 3.41898E-004 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 156743.15 | 11.10014 | 11.10014 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 108058.03 | 3.26891 | 3.26891 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1460205.49 | 103.56960 | 103.56960 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 1083765.46 | 45.24295 | 45.24295 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:20:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 163352.45 | 11.69490 | 11.69490 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 108394.07 | 7.59021 | 7.59021 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 |
7 | CAV_BAS | Cooling | Sensible | 77844.84 | 6.35699 | 6.35699 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 85856.97 | 1.20016 | 1.20016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 424581.19 | 28.13753 | 28.13753 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 24207.99 | 0.33839 | 0.33839 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8662.66 | 0.57732 | 0.57732 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 1118.31 | 1.56323E-002 | 1.56323E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 83316.27 | 5.55290 | 5.55290 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 11183.09 | 0.15632 | 0.15632 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8475.02 | 0.56483 | 0.56483 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 1118.31 | 1.56323E-002 | 1.56323E-002 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 6.35699 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.33316 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.00000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 0.00000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.70286 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28377 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29900 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.00416 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75671 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.34266E-003 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.08517E-004 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.00416 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
16 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23834.73930 |
17 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.08517E-004 |
18 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 497.67925 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 63.10050 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30143 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31200 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 19.68736 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.80382 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.26397E-003 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.22515E-003 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 19.68736 |
28 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
30 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 482960.26200 |
31 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.22515E-003 |
32 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 11860.29247 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.11386 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31110 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33200 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.02980 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.82961 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.22467E-003 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.47642E-004 |
41 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.68991 |
42 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
43 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
44 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 108321.34129 |
45 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.47642E-004 |
46 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2858.27351 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.13549 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21032 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22200 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25208 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56086 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.81149E-003 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.67423E-004 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.65257 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
58 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19137.46435 |
59 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.67423E-004 |
60 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 504.74516 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.59573 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.64479E-002 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.31915 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.95032E-003 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.14875E-004 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.44781 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
72 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13130.89319 |
73 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.14875E-004 |
74 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 346.30285 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.94314 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12291 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.38863 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32775 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.09990E-003 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.85194E-004 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.72197 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
86 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21168.77324 |
87 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.85194E-004 |
88 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 558.27281 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.94534 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 7.91148E-002 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.38907 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.81579E-003 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.61965E-005 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.38907 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
100 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10995.85557 |
101 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.61965E-005 |
102 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 285.31495 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.64020 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22445 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23300 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.47917 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59854 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.69747E-003 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.33197E-003 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.09508 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
114 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 266558.37602 |
115 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.33197E-003 |
116 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7028.39675 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 17.05915 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.02185E-002 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.41183 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.22308E-003 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.54774E-003 |
125 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 6.03673 |
126 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
128 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 176916.64673 |
129 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.54774E-003 |
130 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4664.70168 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 19.73247 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12103 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.94649 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32275 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.14793E-003 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.36516E-003 |
139 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 9.22471 |
140 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
142 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 270352.01452 |
143 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.36516E-003 |
144 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7128.35746 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 18.22411 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.44513E-002 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.64482 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.51147E-003 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.51646E-003 |
153 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.91457 |
154 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
156 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 173340.45685 |
157 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.51646E-003 |
158 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4570.45811 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.19886 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19921 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21300 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25536 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53122 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.91259E-003 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.00323E-004 |
167 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.17169 |
168 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
170 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 34328.80387 |
171 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.00323E-004 |
172 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 905.02212 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.70632 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.01969E-002 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.34126 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.22409E-003 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.98086E-004 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.77284 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
184 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22642.40869 |
185 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.98086E-004 |
186 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 596.92214 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.10230 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11360 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.42046 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30294 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.35381E-003 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.03991E-004 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.18601 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
198 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 34748.03780 |
199 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.03991E-004 |
200 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 916.06889 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.91375 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.04208E-002 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.38275 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.73758E-003 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.97298E-004 |
209 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.76976 |
210 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
211 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
212 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22552.35765 |
213 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.97298E-004 |
214 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 594.54771 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.57732 |
216 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.55290 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.56483 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 28.13740 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.66128 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.35308 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 13.32256 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.35308 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 11.10014 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 11.10014 |
225 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
226 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.30208 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 64.37822 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 33.16967 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 128.75643 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 45.24295 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 103.56960 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 103.56960 |
233 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
234 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.43684 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.51755 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.42963 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 13.03509 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 7.59021 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 11.69490 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 11.69490 |
241 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
242 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.64902 |
243 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.00000 |
244 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.00000 |
245 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.35699 |
246 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 1.20016 |
247 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.35699 |
248 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 6.35699 |
249 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
250 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.18879 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 28.13740 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 28.13740 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 28.13740 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 28.13740 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 28.13753 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 28.13753 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 1.00000 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.57732 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.57732 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.57732 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.57732 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.57732 |
264 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.57732 |
265 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
266 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.55290 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.55290 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.55290 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 5.55290 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.55290 |
272 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.55290 |
273 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
274 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.56483 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.56483 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.56483 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.56483 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.56483 |
280 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.56483 |
281 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
282 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
283 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 11.10014 |
284 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 103.56960 |
285 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 11.69490 |
286 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 6.35699 |
287 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 28.13753 |
288 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.57732 |
289 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 5.55290 |
290 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.56483 |
291 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 11.10014 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.14943 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.68120 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.08692E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 186642.61588 |
298 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.33796E-003 |
299 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 11.10014 |
300 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 102546.64892 |
301 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.97123E-004 |
302 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1571.64274 |
303 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 11.10014 |
304 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.33796E-003 |
305 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 8.92084E-005 |
306 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.97123E-004 |
307 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 103.56960 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.34040 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.68118 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.08381E-003 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1761804.38112 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.03874E-002 |
315 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 103.56960 |
316 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 1035805.45516 |
317 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.06168E-003 |
318 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 15555.85468 |
319 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 103.56960 |
320 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.03874E-002 |
321 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.45059E-006 |
322 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.06168E-003 |
323 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 11.69490 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.04654 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.68118 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.08158E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 195185.59313 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.58228E-003 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 11.69490 |
332 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 101090.07249 |
333 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.84380E-004 |
334 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1571.25134 |
335 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 11.69490 |
336 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.58228E-003 |
337 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 8.53039E-005 |
338 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.84380E-004 |
339 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.35699 |
340 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.82670 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.67049 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.24457E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 107452.79592 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.07314E-003 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.35699 |
349 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 304147.04722 |
350 | Coil:Heating:Water | CAV_BAS HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
351 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
352 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2621.30818 |
353 | Fan:VariableVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 6.35699 |
354 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.07314E-003 |
355 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.54953E-004 |
356 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.74844E-004 |
357 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 28.13753 |
358 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
359 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 28.13753 |
360 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 534450.67911 |
361 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 300859.83117 |
362 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.30887E-002 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 28.13753 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 28.13753 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 28.13753 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 28.13753 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 534450.67911 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 534450.67911 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 24207.99248 |
370 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
371 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 28.13753 |
372 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 28.13753 |
373 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 534450.67911 |
374 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.30887E-002 |
375 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 24207.99248 |
376 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 2.19108E-004 |
377 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
378 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
379 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
380 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.57732 |
381 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
382 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.57732 |
383 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10659.36794 |
384 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6063.47645 |
385 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.61047E-004 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.57732 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.57732 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.57732 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.57732 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10659.36794 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10659.36794 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1118.30896 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
394 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.57732 |
395 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.57732 |
396 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 10659.36794 |
397 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.61047E-004 |
398 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1118.30896 |
399 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.55290 |
400 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
401 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.55290 |
402 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 102553.92176 |
403 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 58326.60541 |
404 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.51154E-003 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 5.55290 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 5.55290 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 5.55290 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.55290 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 102553.92176 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 102553.92176 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 11183.08965 |
412 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
413 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 5.55290 |
414 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.55290 |
415 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 102553.92176 |
416 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.51154E-003 |
417 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 11183.08965 |
418 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.56483 |
419 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
420 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.56483 |
421 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10430.49173 |
422 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5932.66741 |
423 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.55442E-004 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.56483 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.56483 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.56483 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.56483 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10430.49173 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10430.49173 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1118.30896 |
431 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
432 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.56483 |
433 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.56483 |
434 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 10430.49173 |
435 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.55442E-004 |
436 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1118.30896 |
437 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 6.43808E-002 |
438 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 10511.41037 |
439 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 6.43808E-002 |
440 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 7.72569 |
441 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 6.43808E-002 |
442 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 6.43808E-002 |
443 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 270238.34166 |
444 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
445 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.64240E-002 |
446 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 3.17089 |
447 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.64240E-002 |
448 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 7957.76182 |
449 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
450 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 3020430.60763 |
451 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 3020430.61000 |
452 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.64240E-002 |
453 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 6.43808E-002 |
454 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 7.72569 |
455 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 3.21904E-002 |
456 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 3638.70194 |
457 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 3.21904E-002 |
458 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 3638.70194 |
459 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 6.43808E-002 |
460 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.23766E-002 |
461 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1132053.97336 |
462 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1132054.12500 |
463 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 5.70046E-002 |
464 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 6.43808E-002 |
465 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.23766E-002 |
466 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1132053.97336 |
467 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1132054.12500 |
468 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 5.70046E-002 |
469 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.61167E-002 |
470 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.93400 |
471 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.61167E-002 |
472 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 4110.56216 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.61167E-002 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 160026.78531 |
475 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at High Fan Speed [W/K] | 81012.44449 |
476 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 80013.39266 |
477 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
478 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/K] | 48607.46669 |
479 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 663869.49931 |
480 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 649418.88000 |
481 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.61167E-002 |
482 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
483 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
484 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
485 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
486 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
487 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.11401 |
488 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 13.68110 |
489 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.11401 |
490 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 28226.14978 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 49.94961 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1356777.49425 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 9.98992 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 169597.18678 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 49.94961 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1356777.49425 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 9.98992 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 169597.18678 |
499 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.87050E-002 |
500 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.87050E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 22599.62 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 457591.21 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 102664.80 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 18136.52 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 12443.97 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 20061.27 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 10416.44 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 252603.12 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 167653.81 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 256197.69 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 164265.19 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 32530.68 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 21456.36 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 32927.91 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 21371.02 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 68578.23 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 676263.47 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 68858.82 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 94845.12 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 198353.25 | 140773.32 | 57579.93 | 0.71 | 20274.47 | 205.63 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 1860047.95 | 1317124.38 | 542923.57 | 0.71 | 189496.28 | 1921.98 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 208232.42 | 148006.81 | 60225.61 | 0.71 | 21317.01 | 216.21 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 114798.98 | 81305.59 | 33493.39 | 0.71 | 11887.45 | 120.57 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 8.97 | 30.62 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 8.97 | 30.62 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.354 | 0.336 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.354 | 0.336 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.354 | 0.336 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_NORTH_0.4 | N/A | 2.045 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_NORTH_0.4 | N/A | 2.045 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_NORTH_0.4 | N/A | 2.045 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_NORTH_0.4 | N/A | 2.045 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_NORTH_0.4 | N/A | 2.045 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_EAST_0.4 | N/A | 2.045 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_EAST_0.4 | N/A | 2.045 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_EAST_0.4 | N/A | 2.045 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_SOUTH_0.4 | N/A | 2.045 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_SOUTH_0.4 | N/A | 2.045 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_SOUTH_0.4 | N/A | 2.045 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_SOUTH_0.4 | N/A | 2.045 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_SOUTH_0.4 | N/A | 2.045 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_WEST_0.4 | N/A | 2.045 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_WEST_0.4 | N/A | 2.045 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_WEST_0.4 | N/A | 2.045 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_NORTH_0.4 | N/A | 2.045 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_EAST_0.4 | N/A | 2.045 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_SOUTH_0.4 | N/A | 2.045 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_WEST_0.4 | N/A | 2.045 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_NORTH_0.4 | N/A | 2.045 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_EAST_0.4 | N/A | 2.045 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_SOUTH_0.4 | N/A | 2.045 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.36_SHGC_WEST_0.4 | N/A | 2.045 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.895 | 0.789 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.851 | 0.755 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.077 | 0.928 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.354 | 0.336 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.354 | 0.336 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.354 | 0.336 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.3944407480E-003 | 1.4321979566E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 8.1594131637E-002 | 0.1686991046 | Pass | Pass | 0.1067931700 | 0.3091965703 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 3.4140276446E-002 | 7.4492566850E-002 | Pass | Pass | 6.3379100347E-002 | 0.2430331474 | Pass | Fail |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 4.6432072512E-002 | 3.1684475631E-002 | Pass | Pass | 0.3829640315 | 0.4781675254 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 6.0687476518E-002 | 0.1139899037 | Pass | Pass | 0.1043464530 | 0.3041944356 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1479358717 | 0.2543057554 | Pass | Pass | 0.1071659757 | 0.3098494840 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2285951026 | 0.4462163773 | Pass | Pass | 0.1097220209 | 0.3121565543 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1346102072 | 0.2685967329 | Pass | Pass | 0.1051438614 | 0.3017521119 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.8036320742E-002 | 3.0590005751E-002 | Pass | Pass | 6.2404301479E-002 | 0.2393121879 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 8.6544197414E-002 | 0.1296403673 | Pass | Pass | 6.4039113596E-002 | 0.2451937157 | Pass | Fail |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2091995091 | 0.3284401134 | Pass | Pass | 6.8185664630E-002 | 0.2534486366 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 7.2808376391E-002 | 0.1146759856 | Pass | Pass | 6.1084140088E-002 | 0.2299058349 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2517995548 | 0.2895601478 | Pass | Pass | 23.8223588355 | 99.9103444772 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1785480763 | 0.2407750122 | Pass | Pass | 4.4396455047 | 15.4021421156 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2214772461 | 0.1963998900 | Pass | Pass | 1.0648900862 | 5.4543373506 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1436020650 | 0.1597249654 | Pass | Pass | 2.7127380126 | 19.4581957723 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.6777135323E-002 | 2.5671249498E-002 | Pass | Pass | 0.3581631587 | 1.9780138980 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.0090651551E-002 | 4.1062562411E-002 | Pass | Pass | 8.7055362039E-002 | 0.3486428050 | Fail | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.7056628244E-002 | 7.4441403633E-002 | Pass | Pass | 0.3954931275 | 0.4788384889 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.2330458202E-006 | 5.0667157883E-006 | Pass | Pass | 3.2270258861E-003 | 3.4247237272E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 8.2600023895E-004 | 2.5756403505E-003 | Pass | Pass | 0.1070778850 | 0.3693770204 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.6243540725E-002 | 2.8463956049E-002 | Pass | Pass | 6.2710293885E-003 | 5.6782924223E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.9066826859E-005 | 2.2867924761E-005 | Pass | Pass | 5.4212187728E-005 | 1.0492611029E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 6705.72 | 142.81 | 0.00 | 32012.34 | 9630.32 | 48491.19 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 11.00 | 18 | |||
May | 24.00 | 14 | |||
Jun | 29.00 | 21 | |||
Jul | 6.00 | 9 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.340 | 0.354 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.340 | 0.354 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.340 | 0.354 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.789 | 0.895 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.755 | 0.851 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.928 | 1.077 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.340 | 0.354 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.340 | 0.354 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.340 | 0.354 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.36_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.36_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.36_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.36_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.36_SHGC_NORTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.36_SHGC_EAST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.36_SHGC_EAST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.36_SHGC_EAST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.36_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.36_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.36_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.36_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.36_SHGC_SOUTH_0.4 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.36_SHGC_WEST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.36_SHGC_WEST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.36_SHGC_WEST_0.4 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.045 | 0.401 | 0.442 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.36_SHGC_NORTH_0.4 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.045 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.36_SHGC_EAST_0.4 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.045 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.36_SHGC_SOUTH_0.4 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.045 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.36_SHGC_WEST_0.4 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.045 | 0.401 | 0.442 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.36_SHGC_NORTH_0.4 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.045 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.36_SHGC_EAST_0.4 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.045 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.36_SHGC_SOUTH_0.4 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.045 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.36_SHGC_WEST_0.4 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.045 | 0.401 | 0.442 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.045 | 0.401 | 0.442 | |||||||||||||||||
North Total or Average | 1390.74 | 2.045 | 0.401 | 0.442 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.045 | 0.401 | 0.442 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.6849 | 2779.43 | 24139.15 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 216.17 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 8.6849 | 2496.12 | 21678.66 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 194.14 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 8.6849 | 24961.20 | 216786.56 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 1941.36 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 8.6849 | 2496.12 | 21678.66 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 194.14 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 8.6849 | 313.41 | 2721.97 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.79 | 0.0000 | Y | 14.20 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.37 | 0.0000 | Y | 9.01 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 8.6849 | 313.42 | 2722.03 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.11 | 0.0000 | Y | 13.85 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.45 | 0.0000 | Y | 9.04 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 8.6849 | 3134.13 | 27219.72 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.72 | 0.0000 | Y | 141.65 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 8.6849 | 2019.75 | 17541.42 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.33 | 0.0000 | Y | 90.00 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 8.6849 | 3134.20 | 27220.31 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.08 | 0.0000 | Y | 138.38 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 8.6849 | 2019.75 | 17541.42 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.41 | 0.0000 | Y | 90.26 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 8.6849 | 313.41 | 2721.97 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.72 | 0.0000 | Y | 14.16 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.33 | 0.0000 | Y | 9.00 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 8.6849 | 313.42 | 2722.03 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.08 | 0.0000 | Y | 13.84 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.41 | 0.0000 | Y | 9.03 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 8.6849 | 783.68 | 6806.21 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 62.65 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 13.9016 | 36.20 | 503.28 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.16 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 13.9016 | 362.03 | 5032.75 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 51.55 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 13.9016 | 36.20 | 503.28 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.16 |
Interior Lighting Total | 8.7339 | 46320.38 | 404555.99 | 1014.86 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13271.55 | AstronomicalClock | - | 42.11 | 42.11 | 104.90 | |
EXTERIOR_LIGHTS_B | 989.48 | AstronomicalClock | - | 83.57 | 62.84 | 11.67 | |
EXTERIOR_LIGHTS_C | 26594.85 | AstronomicalClock | - | 83.57 | 48.07 | 239.97 | |
Exterior Lighting Total | 40855.88 | 356.53 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2244151.84 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 3020430.61 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1132054.12 | 5.91 | 1125517.08 | 5.88 | 8.97 | 30.62 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 1132054.12 | 5.91 | 1125517.08 | 5.88 | 8.97 | 30.62 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 666911.63 | |||||
CENTRAL BOILER | Boiler:HotWater | 649418.88 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1356777.49 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1356777.49 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 186642.62 | 198353.25 | 140773.32 | 57579.93 | 0.71 | - | 20274.47 | 205.63 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1761804.38 | 1860047.95 | 1317124.38 | 542923.57 | 0.71 | - | 189496.28 | 1921.98 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 195185.59 | 208232.42 | 148006.81 | 60225.61 | 0.71 | - | 21317.01 | 216.21 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 107452.80 | 114798.98 | 81305.59 | 33493.39 | 0.71 | - | 11887.45 | 120.57 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 534450.68 | 300859.83 | 233590.85 | 0.56 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10659.37 | 6063.48 | 4595.89 | 0.57 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 102553.92 | 58326.61 | 44227.32 | 0.57 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10430.49 | 5932.67 | 4497.82 | 0.57 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 23834.74 | 22599.62 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 482960.26 | 457591.21 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 108321.34 | 102664.80 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 19137.46 | 18136.52 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 13130.89 | 12443.97 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 21168.77 | 20061.27 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 10995.86 | 10416.44 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 266558.38 | 252603.12 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 176916.65 | 167653.81 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 270352.01 | 256197.69 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 173340.46 | 164265.19 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 34328.80 | 32530.68 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 22642.41 | 21456.36 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 34748.04 | 32927.91 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 22552.36 | 21371.02 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 102546.65 | 68578.23 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 1035805.46 | 676263.47 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 101090.07 | 68858.82 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 100000.00 | 94845.12 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 534450.68 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10659.37 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 102553.92 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10430.49 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 24207.99 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 1118.31 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 11183.09 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 1118.31 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 11.10 | 25215.01 | 2271.59 | 1.00 | 1.12 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 103.57 | 235268.00 | 2271.59 | 1.00 | 1.08 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 11.69 | 26566.05 | 2271.59 | 1.00 | 1.11 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
CAV_BAS FAN | Fan:VariableVolume | 0.61 | 1389.42 | 6.36 | 14517.63 | 2283.73 | 1.00 | 1.13 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 28.14 | 46211.16 | 1642.33 | 1.00 | 1.14 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.58 | 646.66 | 1120.11 | 1.00 | 1.55 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 5.55 | 6219.85 | 1120.11 | 1.00 | 1.15 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.56 | 632.67 | 1120.11 | 1.00 | 1.55 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.064381 | 10511.41 | 163269.45 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.026424 | 7957.76 | 301156.09 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.032190 | 3638.70 | 113036.94 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.032190 | 3638.70 | 113036.94 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.016117 | 4110.56 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.114009 | 28226.15 | 247577.87 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 76974.40 | 76974.40 | 27.69 | 6.357 | 6.357 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00745 | 21.56 | 0.00629 | 1.200 | 0.00 |
CORE_BOTTOM | 81169.02 | 81169.02 | 32.52 | 6.703 | 6.703 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00738 | 21.56 | 0.00629 | 1.078 | 0.00 |
CORE_MID | 764295.26 | 764295.26 | 306.19 | 63.101 | 63.101 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00741 | 21.56 | 0.00629 | 10.778 | 0.00 |
CORE_TOP | 74057.27 | 74057.27 | 29.67 | 6.114 | 6.114 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00742 | 21.56 | 0.00629 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 13630.98 | 13630.98 | 43.49 | 1.135 | 1.135 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00727 | 33.40 | 0.00631 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 19156.22 | 19156.22 | 94.84 | 1.596 | 1.596 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 24.00 | 24.00 | 0.00712 | 24.09 | 0.00629 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 23326.61 | 23326.61 | 74.43 | 1.943 | 1.943 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00716 | 33.00 | 0.00631 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 23353.15 | 23353.15 | 115.62 | 1.945 | 1.945 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00710 | 30.36 | 0.00630 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 127730.97 | 127730.97 | 407.55 | 10.640 | 10.640 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00727 | 33.40 | 0.00631 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 204790.17 | 204790.17 | 1013.94 | 17.059 | 17.059 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00711 | 25.51 | 0.00629 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 236881.43 | 236881.43 | 755.80 | 19.732 | 19.732 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00715 | 33.13 | 0.00631 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 218775.28 | 218775.28 | 1083.18 | 18.224 | 18.224 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 24.00 | 24.00 | 0.00710 | 30.09 | 0.00630 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 14391.86 | 14391.86 | 45.92 | 1.199 | 1.199 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00724 | 33.24 | 0.00631 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 20483.97 | 20483.97 | 101.42 | 1.706 | 1.706 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00711 | 25.96 | 0.00630 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 25237.46 | 25237.46 | 80.52 | 2.102 | 2.102 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00714 | 33.27 | 0.00631 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 22974.02 | 22974.02 | 113.75 | 1.914 | 1.914 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00710 | 30.36 | 0.00630 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8786.71 | 8786.71 | 242.71 | 0.577 | 0.577 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 27.00 | 27.00 | 0.00708 | 26.28 | 0.00630 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 84514.03 | 84514.03 | 2334.46 | 5.553 | 5.553 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 27.00 | 27.00 | 0.00709 | 26.28 | 0.00630 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8596.65 | 8596.65 | 237.46 | 0.565 | 0.565 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 27.00 | 27.00 | 0.00708 | 26.28 | 0.00630 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 372393.40 | 428252.41 | 546.46 | 24.467 | 28.137 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 18.84 | 0.00628 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:50:00 | 21.00 | 22.80 | 0.00034 | -27.60 | 0.00034 | 1.200 | 0.00 |
CORE_BOTTOM | 6186.34 | 6186.34 | 2.48 | 0.300 | 1.078 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 1.078 | 0.00 |
CORE_MID | 309593.95 | 309593.95 | 124.03 | 14.972 | 14.972 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 10.778 | 0.00 |
CORE_TOP | 75828.08 | 75828.08 | 30.38 | 3.690 | 3.690 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 13392.47 | 13392.47 | 42.73 | 0.653 | 0.653 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00789 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 9188.47 | 9188.47 | 45.49 | 0.448 | 0.448 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00789 | -27.60 | 0.00034 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 14812.57 | 14812.57 | 47.26 | 0.722 | 0.722 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00790 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 7571.02 | 7571.02 | 37.48 | 0.369 | 0.369 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -27.60 | 0.00034 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 186501.01 | 186501.01 | 595.06 | 9.095 | 9.095 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -27.60 | 0.00034 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 123779.83 | 123779.83 | 612.85 | 6.037 | 6.037 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -27.60 | 0.00034 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 189153.21 | 189153.21 | 603.51 | 9.225 | 9.225 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -27.60 | 0.00034 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 121279.37 | 121279.37 | 600.47 | 5.915 | 5.915 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -27.60 | 0.00034 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 24015.35 | 24015.35 | 76.63 | 1.172 | 1.172 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 15839.77 | 15839.77 | 78.42 | 0.773 | 0.773 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -27.60 | 0.00034 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 24308.45 | 24308.45 | 77.56 | 1.186 | 1.186 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -27.60 | 0.00034 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 15776.77 | 15776.77 | 78.11 | 0.770 | 0.770 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -27.60 | 0.00034 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 24.37 | 0.00097 | -27.60 | 0.00034 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 22.40 | 0.00097 | -27.60 | 0.00034 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 19.89 | 0.00097 | -27.60 | 0.00034 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 01:10:00 | 18.00 | 27.00 | 0.00700 | -27.60 | 0.00034 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 11.10 | 11.10 | 3.27 | 3.27 | 11.1001 | 3.3531 | 11.1001 | 0.3021 | 0.3000 |
VAV_MID WITH REHEAT | 103.57 | 103.57 | 45.24 | 45.24 | 103.5696 | 45.2430 | 103.5696 | 0.4368 | 0.3000 |
VAV_TOP WITH REHEAT | 11.69 | 11.69 | 7.59 | 7.59 | 11.6949 | 7.5902 | 11.6949 | 0.6490 | 0.3000 |
CAV_BAS | 6.36 | 6.36 | 1.20 | 1.20 | 6.3570 | 1.2002 | 6.3570 | 0.1888 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 28.14 | 28.14 | 0.34 | 0.34 | 28.1375 | 28.1374 | 28.1375 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.58 | 0.58 | 0.02 | 0.02 | 0.5773 | 0.5773 | 0.5773 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 5.55 | 5.55 | 0.16 | 0.16 | 5.5529 | 5.5529 | 5.5529 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.56 | 0.56 | 0.02 | 0.02 | 0.5648 | 0.5648 | 0.5648 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 23834.739 | 23834.739 | 2.004157 | 0.00020852 | 497.679 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23834.74 | 23834.74 | 2.004157 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00799547 | 45.2057 | 6186.34 | 0.00 | 23921.13 | 23921.13 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 482960.262 | 482960.262 | 19.687358 | 0.00422515 | 11860.292 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 482960.26 | 482960.26 | 19.687358 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00800000 | 45.2310 | 309593.95 | 0.00 | 484481.55 | 484481.55 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 108321.341 | 108321.341 | 3.689913 | 0.00094764 | 2858.274 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 108321.34 | 108321.34 | 3.689913 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00800000 | 45.2310 | 75828.08 | 0.00 | 108687.91 | 108687.91 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 19137.464 | 19137.464 | 0.652571 | 0.00016742 | 504.745 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19137.46 | 19137.46 | 0.652571 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00788700 | 44.6014 | 13392.47 | 0.00 | 19200.54 | 19200.54 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 13130.893 | 13130.893 | 0.447811 | 0.00011487 | 346.303 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13130.89 | 13130.89 | 0.447811 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00789441 | 44.6427 | 9188.47 | 0.00 | 13174.02 | 13174.02 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 21168.773 | 21168.773 | 0.721971 | 0.00018519 | 558.273 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21168.77 | 21168.77 | 0.721971 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00790376 | 44.6949 | 14812.57 | 0.00 | 21238.20 | 21238.20 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 10995.856 | 10995.856 | 0.389068 | 0.00009620 | 285.315 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10995.86 | 10995.86 | 0.389068 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00783977 | 44.3382 | 7571.02 | 0.00 | 11029.54 | 11029.54 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 266558.376 | 266558.376 | 9.095081 | 0.00233197 | 7028.397 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 266558.38 | 266558.38 | 9.095081 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00782968 | 44.2824 | 186501.01 | 0.00 | 267422.46 | 267422.46 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 176916.647 | 176916.647 | 6.036735 | 0.00154774 | 4664.702 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 176916.65 | 176916.65 | 6.036735 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00782923 | 44.2800 | 123779.83 | 0.00 | 177489.47 | 177489.47 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 270352.015 | 270352.015 | 9.224711 | 0.00236516 | 7128.357 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 270352.01 | 270352.01 | 9.224711 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00783217 | 44.2963 | 189153.21 | 0.00 | 271227.91 | 271227.91 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 173340.457 | 173340.457 | 5.914571 | 0.00151646 | 4570.458 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 173340.46 | 173340.46 | 5.914571 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00782557 | 44.2595 | 121279.37 | 0.00 | 173902.05 | 173902.05 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 34328.804 | 34328.804 | 1.171687 | 0.00030032 | 905.022 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 34328.80 | 34328.80 | 1.171687 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00783667 | 44.3218 | 24015.35 | 0.00 | 34439.13 | 34439.13 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 22642.409 | 22642.409 | 0.772836 | 0.00019809 | 596.922 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22642.41 | 22642.41 | 0.772836 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00783493 | 44.3122 | 15839.77 | 0.00 | 22715.12 | 22715.12 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 34748.038 | 34748.038 | 1.186012 | 0.00030399 | 916.069 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 34748.04 | 34748.04 | 1.186012 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00783860 | 44.3326 | 24308.45 | 0.00 | 34859.67 | 34859.67 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 22552.358 | 22552.358 | 0.769764 | 0.00019730 | 594.548 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22552.36 | 22552.36 | 0.769764 | 12.80 | 10.41 | 0.00800000 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00783437 | 44.3091 | 15776.77 | 0.00 | 22624.78 | 22624.78 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 186642.616 | -999.000 | 11.100142 | 0.00533796 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 186642.62 | 184569.19 | 11.100142 | 26.15 | 14.57 | 0.00708692 | 10.68 | 8.51 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 22.8663 | 24.00 | 0.00731832 | 34.5214 | 133191.23 | 0.00 | 135967.73 | 135967.73 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 102546.649 | 102546.649 | 3.330043 | 0.00089712 | 1571.643 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 102546.65 | 102546.65 | 3.330043 | -16.30 | -16.30 | 0.00212594 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 76.2209 | 19.85 | 0.00781656 | 47.4688 | 33991.12 | 0.00 | 82940.70 | 82940.70 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1761804.381 | -999.000 | 103.569600 | 0.05038738 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 1761804.38 | 1743105.74 | 103.569600 | 26.34 | 14.64 | 0.00708381 | 10.68 | 8.51 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 24.5071 | 24.00 | 0.00734153 | 34.6296 | 1223299.63 | 0.00 | 1284672.52 | 1284672.52 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1035805.455 | 1035805.455 | 31.070880 | 0.00906168 | 15555.855 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:20:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 1035805.46 | 1035805.46 | 31.070880 | -18.70 | -18.70 | 0.00171047 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 81.6905 | 18.15 | 0.00776781 | 52.4445 | 411813.19 | 0.00 | 817725.28 | 817725.28 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 195185.593 | -999.000 | 11.694898 | 0.00558228 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 195185.59 | 193138.46 | 11.694898 | 26.05 | 14.53 | 0.00708158 | 10.68 | 8.51 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 21.7034 | 24.00 | 0.00729733 | 34.4235 | 139886.10 | 0.00 | 142068.90 | 142068.90 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 101090.072 | 101090.072 | 3.508469 | 0.00088438 | 1571.251 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 101090.07 | 101090.07 | 3.508469 | -14.43 | -14.43 | 0.00239985 | 12.80 | 10.41 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 72.3447 | 17.20 | 0.00777163 | 55.7007 | 49869.40 | 0.00 | 83236.62 | 83236.62 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 107452.796 | -999.000 | 6.356989 | 0.00307314 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 107452.80 | 104107.24 | 6.356989 | 25.83 | 14.60 | 0.00724457 | 10.67 | 8.50 | 0.00700000 | 32.60 | 0.00630558 | 16.10 | 18.8793 | 24.00 | 0.00749801 | 35.3593 | 67785.78 | 0.00 | 78754.15 | 78754.15 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 100000.000 | 100000.000 | 3.474082 | 0.00087484 | 2621.308 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 100000.00 | 100000.00 | 3.474082 | -5.21 | -9.59 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 34.5460 | 22.90 | 0.00034190 | 1.7422 | 0.00 | 0.00 | 100050.95 | 100050.95 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 534450.679 | 300859.831 | 28.137529 | 0.01308866 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 464335.47 | 462573.79 | -999.0 | 28.66 | 15.39 | 0.00703323 | 12.80 | 9.41 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | -999.0000 | 27.00 | 0.00704208 | 27.8119 | 371955.66 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10659.368 | 6063.476 | 0.577319 | 0.00026105 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 9212.27 | 9146.79 | -999.0 | 28.06 | 15.21 | 0.00706078 | 12.80 | 9.41 | 0.00700000 | 26.28 | 0.00629588 | 13.94 | -999.0000 | 27.00 | 0.00708207 | 27.9660 | 8786.71 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 102553.922 | 58326.605 | 5.552900 | 0.00251154 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 88635.56 | 87982.03 | -999.0 | 28.06 | 15.21 | 0.00706305 | 12.80 | 9.41 | 0.00700000 | 26.28 | 0.00629588 | 13.94 | -999.0000 | 27.00 | 0.00708528 | 27.9786 | 84514.03 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10430.492 | 5932.667 | 0.564832 | 0.00025544 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | 9014.72 | 8949.23 | -999.0 | 28.06 | 15.21 | 0.00706212 | 12.80 | 9.41 | 0.00700000 | 26.28 | 0.00629588 | 13.94 | -999.0000 | 27.00 | 0.00708393 | 27.9733 | 8596.65 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 534450.679 | 534450.679 | 28.137529 | 0.01308866 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 534450.68 | 534450.68 | 28.137529 | -27.60 | -27.60 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 1.2026 | 27.00 | 0.00700000 | 27.6430 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10659.368 | 10659.368 | 0.577319 | 0.00026105 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10659.37 | 10659.37 | 0.577319 | -27.60 | -27.60 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.7078 | 25.18 | 0.00097294 | 4.3190 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 102553.922 | 102553.922 | 5.552900 | 0.00251154 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 102553.92 | 102553.92 | 5.552900 | -27.60 | -27.60 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.8152 | 23.61 | 0.00097295 | 4.7455 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10430.492 | 10430.492 | 0.564832 | 0.00025544 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10430.49 | 10430.49 | 0.564832 | -27.60 | -27.60 | 0.00034190 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.7676 | 22.11 | 0.00097240 | 5.1942 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 24207.992 | 24207.992 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 24207.99 | 24207.99 | 28.137529 | -0.33 | -0.33 | 0.00691993 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 1.2026 | 27.00 | 0.00700000 | 27.6430 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 1118.309 | 1118.309 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1118.31 | 1118.31 | 0.577319 | -0.75 | -5.61 | 0.00095585 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.7078 | 25.18 | 0.00097294 | 4.3190 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 11183.090 | 11183.090 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 11183.09 | 11183.09 | 5.552900 | -0.78 | -5.63 | 0.00095519 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.8152 | 23.61 | 0.00097295 | 4.7455 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 1118.309 | 1118.309 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1118.31 | 1118.31 | 0.564832 | -0.76 | -5.62 | 0.00095495 | 40.00 | 19.63 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 2.7676 | 22.11 | 0.00097240 | 5.1942 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 23834.739 | 23834.739 | 2.004157 | 0.00020852 | 497.679 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.42134906 | 54.44 | 82.22 | 27.78 | 3081217.97 | 0.7735 | 0.789117 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23834.74 | 23834.74 | 1.0000 | 2.11065724 | 2.004157 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.20849543 | 60.00 | 32.22 | 27.78 | 0.000 | 23834.74 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.84 | 0.00799547 | 21.00 | 0.00799547 | 45.2057 | 6186.34 | 0.00 | 23921.13 | 23921.13 | 2.11065724 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 23.91 | 15.92 | 0.00800000 | 44393.3 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 482960.262 | 482960.262 | 19.687358 | 0.00422515 | 11860.292 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.42134906 | 54.44 | 82.22 | 27.78 | 3081217.97 | 15.6743 | 15.989782 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 482960.26 | 482960.26 | 1.0000 | 20.73354137 | 19.687358 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 4.22471605 | 60.00 | 32.22 | 27.78 | 0.000 | 482960.26 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 45.2310 | 309593.95 | 0.00 | 484481.55 | 484481.55 | 20.73354137 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 35.72 | 19.88 | 0.00800000 | 56426.9 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 108321.341 | 108321.341 | 3.689913 | 0.00094764 | 2858.274 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.42134906 | 54.44 | 82.22 | 27.78 | 3081217.97 | 3.5155 | 3.586288 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 108321.34 | 108321.34 | 1.0000 | 3.88599424 | 3.689913 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.94754568 | 60.00 | 32.22 | 27.78 | 0.000 | 108321.34 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 45.2310 | 75828.08 | 0.00 | 108687.91 | 108687.91 | 3.88599424 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61029.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19137.464 | 19137.464 | 0.652571 | 0.00016742 | 504.745 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.42134906 | 54.44 | 82.22 | 27.78 | 3081217.97 | 0.6211 | 0.633601 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19137.46 | 19137.46 | 1.0000 | 0.68724849 | 0.652571 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.16740581 | 60.00 | 32.22 | 27.78 | 0.000 | 19137.46 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00788700 | 21.00 | 0.00788700 | 44.6014 | 13392.47 | 0.00 | 19200.54 | 19200.54 | 0.68724849 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60998.1 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13130.893 | 13130.893 | 0.447811 | 0.00011487 | 346.303 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.42134906 | 54.44 | 82.22 | 27.78 | 3081217.97 | 0.4262 | 0.434736 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13130.89 | 13130.89 | 1.0000 | 0.47160723 | 0.447811 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.11486306 | 60.00 | 32.22 | 27.78 | 0.000 | 13130.89 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00789441 | 21.00 | 0.00789441 | 44.6427 | 9188.47 | 0.00 | 13174.02 | 13174.02 | 0.47160723 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60994.1 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21168.773 | 21168.773 | 0.721971 | 0.00018519 | 558.273 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.42134906 | 54.44 | 82.22 | 27.78 | 3081217.97 | 0.6870 | 0.700853 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21168.77 | 21168.77 | 1.0000 | 0.76033671 | 0.721971 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.18517477 | 60.00 | 32.22 | 27.78 | 0.000 | 21168.77 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00790376 | 21.00 | 0.00790376 | 44.6949 | 14812.57 | 0.00 | 21238.20 | 21238.20 | 0.76033671 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60992.5 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10995.856 | 10995.856 | 0.389068 | 0.00009620 | 285.315 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.42134906 | 54.44 | 82.22 | 27.78 | 3081217.97 | 0.3569 | 0.364049 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 10995.86 | 10995.86 | 1.0000 | 0.40974259 | 0.389068 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.09618673 | 60.00 | 32.22 | 27.78 | 0.000 | 10995.86 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00783977 | 21.00 | 0.00783977 | 44.3382 | 7571.02 | 0.00 | 11029.54 | 11029.54 | 0.40974259 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 39.20 | 20.94 | 0.00800000 | 59978.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 266558.376 | 266558.376 | 9.095081 | 0.00233197 | 7028.397 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.42134906 | 54.44 | 82.22 | 27.78 | 3081217.97 | 8.6511 | 8.825178 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 266558.38 | 266558.38 | 1.0000 | 9.57839208 | 9.095081 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 2.33173107 | 60.00 | 32.22 | 27.78 | 0.000 | 266558.38 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00782968 | 21.00 | 0.00782968 | 44.2824 | 186501.01 | 0.00 | 267422.46 | 267422.46 | 9.57839208 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60979.2 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 176916.647 | 176916.647 | 6.036735 | 0.00154774 | 4664.702 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.42134906 | 54.44 | 82.22 | 27.78 | 3081217.97 | 5.7418 | 5.857332 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 176916.65 | 176916.65 | 1.0000 | 6.35752607 | 6.036735 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 1.54758612 | 60.00 | 32.22 | 27.78 | 0.000 | 176916.65 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00782923 | 21.00 | 0.00782923 | 44.2800 | 123779.83 | 0.00 | 177489.47 | 177489.47 | 6.35752607 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60977.8 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 270352.015 | 270352.015 | 9.224711 | 0.00236516 | 7128.357 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.42134906 | 54.44 | 82.22 | 27.78 | 3081217.97 | 8.7742 | 8.950777 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 270352.01 | 270352.01 | 1.0000 | 9.71491058 | 9.224711 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 2.36491609 | 60.00 | 32.22 | 27.78 | 0.000 | 270352.01 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00783217 | 21.00 | 0.00783217 | 44.2963 | 189153.21 | 0.00 | 271227.91 | 271227.91 | 9.71491058 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60978.6 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 173340.457 | 173340.457 | 5.914571 | 0.00151646 | 4570.458 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.42134906 | 54.44 | 82.22 | 27.78 | 3081217.97 | 5.6257 | 5.738932 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 173340.46 | 173340.46 | 1.0000 | 6.22887009 | 5.914571 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 1.51630324 | 60.00 | 32.22 | 27.78 | 0.000 | 173340.46 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00782557 | 21.00 | 0.00782557 | 44.2595 | 121279.37 | 0.00 | 173902.05 | 173902.05 | 6.22887009 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60978.5 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 34328.804 | 34328.804 | 1.171687 | 0.00030032 | 905.022 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.42134906 | 54.44 | 82.22 | 27.78 | 3081217.97 | 1.1141 | 1.136553 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 34328.80 | 34328.80 | 1.0000 | 1.23395059 | 1.171687 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.30029272 | 60.00 | 32.22 | 27.78 | 0.000 | 34328.80 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00783667 | 21.00 | 0.00783667 | 44.3218 | 24015.35 | 0.00 | 34439.13 | 34439.13 | 1.23395059 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60969.5 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22642.409 | 22642.409 | 0.772836 | 0.00019809 | 596.922 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.42134906 | 54.44 | 82.22 | 27.78 | 3081217.97 | 0.7349 | 0.749642 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22642.41 | 22642.41 | 1.0000 | 0.81390493 | 0.772836 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.19806546 | 60.00 | 32.22 | 27.78 | 0.000 | 22642.41 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00783493 | 21.00 | 0.00783493 | 44.3122 | 15839.77 | 0.00 | 22715.12 | 22715.12 | 0.81390493 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60968.6 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 34748.038 | 34748.038 | 1.186012 | 0.00030399 | 916.069 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.42134906 | 54.44 | 82.22 | 27.78 | 3081217.97 | 1.1277 | 1.150433 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 34748.04 | 34748.04 | 1.0000 | 1.24903682 | 1.186012 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.30395998 | 60.00 | 32.22 | 27.78 | 0.000 | 34748.04 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00783860 | 21.00 | 0.00783860 | 44.3326 | 24308.45 | 0.00 | 34859.67 | 34859.67 | 1.24903682 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60969.1 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22552.358 | 22552.358 | 0.769764 | 0.00019730 | 594.548 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.42134906 | 54.44 | 82.22 | 27.78 | 3081217.97 | 0.7319 | 0.746660 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22552.36 | 22552.36 | 1.0000 | 0.81066919 | 0.769764 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.19727774 | 60.00 | 32.22 | 27.78 | 0.000 | 22552.36 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 20.95 | 0.00783437 | 21.00 | 0.00783437 | 44.3091 | 15776.77 | 0.00 | 22624.78 | 22624.78 | 0.81066919 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60968.6 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 186642.616 | -999.000 | 11.100142 | 0.00533796 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.0142 | 1004.8586 | 1.0531 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 11.100142 | 11.69000225 | 4197.9300 | 999.8980 | 64.37418958 | 15.00 | 6.67 | 8.33 | 2251085.39 | 8.2912 | 8.291228 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | Sensible | 186642.62 | 184569.19 | 1.0000 | 11.69000225 | 11.100142 | 26.15 | 14.57 | 0.00708692 | 44344.5 | 10.68 | 8.51 | 0.00700000 | 28378.5 | 5.33741066 | 6.67 | 15.00 | 8.33 | 25215.008 | 161427.61 | 33.40 | 0.00630683 | 16.37 | 2.53819000 | 22.8663 | 24.00 | 0.00731832 | 24.00 | 0.00731832 | 34.5214 | 133191.23 | 0.00 | 135967.73 | 135967.73 | 11.69000225 | 26.15 | 15.93 | 0.00708692 | 44344.5 | 14.72 | 11.47 | 0.00708692 | 32713.4 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 102546.649 | 102546.649 | 3.330043 | 0.00089712 | 1571.643 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 11.100142 | 11.69000225 | 4197.9300 | 999.8980 | 26.42134906 | 54.44 | 82.22 | 27.78 | 3081217.97 | 3.3281 | 3.395100 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 102546.65 | 102546.65 | 1.0000 | 3.50700067 | 3.330043 | -16.30 | -16.30 | 0.00212594 | -11125.6 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 0.89703130 | 60.00 | 32.22 | 27.78 | 0.000 | 102546.65 | -27.60 | 0.00034190 | -27.60 | 2.53819000 | 76.2209 | 19.92 | 0.00784446 | 19.85 | 0.00781656 | 47.4688 | 33991.12 | 0.00 | 82940.70 | 82940.70 | 3.50700067 | 2.80 | -0.99 | 0.00212594 | 8141.5 | 26.24 | 11.19 | 0.00212594 | 31791.5 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1761804.381 | -999.000 | 103.569600 | 0.05038738 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.0084 | 1004.8586 | 1.0531 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 103.569600 | 109.07327644 | 4197.9300 | 999.8980 | 64.37418958 | 15.00 | 6.67 | 8.33 | 2251085.39 | 78.2647 | 78.264663 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 1761804.38 | 1743105.74 | 1.0000 | 109.07327644 | 103.569600 | 26.34 | 14.64 | 0.00708381 | 44530.9 | 10.68 | 8.51 | 0.00700000 | 28378.5 | 50.38224224 | 6.67 | 15.00 | 8.33 | 235268.003 | 1526536.38 | 33.40 | 0.00630683 | 16.37 | 25.38195000 | 24.5071 | 24.00 | 0.00734153 | 24.00 | 0.00734153 | 34.6296 | 1223299.63 | 0.00 | 1284672.52 | 1284672.52 | 109.07327644 | 26.34 | 16.00 | 0.00708381 | 44530.9 | 14.77 | 11.49 | 0.00708381 | 32752.9 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 1035805.455 | 1035805.455 | 31.070880 | 0.00906168 | 15555.855 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 103.569600 | 109.07327644 | 4197.9300 | 999.8980 | 26.42134906 | 54.44 | 82.22 | 27.78 | 3081217.97 | 33.6168 | 34.293304 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:20:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 1035805.46 | 1035805.46 | 1.0000 | 32.72198293 | 31.070880 | -18.70 | -18.70 | 0.00171047 | -14573.9 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 9.06075359 | 60.00 | 32.22 | 27.78 | 0.000 | 1035805.46 | -27.60 | 0.00034190 | -27.60 | 25.38195000 | 81.6905 | 21.00 | 0.00781655 | 18.15 | 0.00776781 | 52.4445 | 411813.19 | 0.00 | 817725.28 | 817725.28 | 32.72198293 | 2.80 | -1.64 | 0.00171047 | 7100.2 | 27.59 | 11.32 | 0.00171047 | 32090.3 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 195185.593 | -999.000 | 11.694898 | 0.00558228 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.0043 | 1004.8586 | 1.0531 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.694898 | 12.31636347 | 4197.9300 | 999.8980 | 64.37418958 | 15.00 | 6.67 | 8.33 | 2251085.39 | 8.6707 | 8.670733 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | Sensible | 195185.59 | 193138.46 | 1.0000 | 12.31636347 | 11.694898 | 26.05 | 14.53 | 0.00708158 | 44226.1 | 10.68 | 8.51 | 0.00700000 | 28378.4 | 5.58171380 | 6.67 | 15.00 | 8.33 | 26566.051 | 168619.54 | 33.40 | 0.00630683 | 16.37 | 2.53819000 | 21.7034 | 24.00 | 0.00729733 | 24.00 | 0.00729733 | 34.4235 | 139886.10 | 0.00 | 142068.90 | 142068.90 | 12.31636347 | 26.05 | 15.89 | 0.00708158 | 44226.1 | 14.72 | 11.46 | 0.00708158 | 32691.1 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 101090.072 | 101090.072 | 3.508469 | 0.00088438 | 1571.251 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.694898 | 12.31636347 | 4197.9300 | 999.8980 | 26.42134906 | 54.44 | 82.22 | 27.78 | 3081217.97 | 3.2808 | 3.346876 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 101090.07 | 101090.07 | 1.0000 | 3.69490904 | 3.508469 | -14.43 | -14.43 | 0.00239985 | -8559.3 | 12.80 | 10.41 | 0.00800000 | 33059.8 | 0.88428984 | 60.00 | 32.22 | 27.78 | 0.000 | 101090.07 | -27.60 | 0.00034190 | -27.60 | 2.53819000 | 72.3447 | 20.03 | 0.00778332 | 17.20 | 0.00777163 | 55.7007 | 49869.40 | 0.00 | 83236.62 | 83236.62 | 3.69490904 | 2.80 | -0.57 | 0.00239985 | 8827.9 | 25.12 | 11.00 | 0.00239985 | 31355.3 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 107452.796 | -999.000 | 6.356989 | 0.00307314 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.3073 | 1004.8586 | 1.0531 | CAV_BAS FAN | Fan:VariableVolume | 6.356989 | 6.69479818 | 4197.9300 | 999.8980 | 64.37418958 | 15.00 | 6.67 | 8.33 | 2251085.39 | 4.7734 | 4.773377 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 107452.80 | 104107.24 | 1.0000 | 6.69479818 | 6.356989 | 25.83 | 14.60 | 0.00724457 | 44417.8 | 10.67 | 8.50 | 0.00700000 | 28367.6 | 3.07282287 | 6.67 | 15.00 | 8.33 | 14517.632 | 92935.16 | 32.60 | 0.00630558 | 16.10 | 1.20015641 | 18.8793 | 24.00 | 0.00749801 | 24.00 | 0.00749801 | 35.3593 | 67785.78 | 0.00 | 78754.15 | 78754.15 | 6.69479818 | 25.83 | 15.95 | 0.00724457 | 44417.8 | 14.27 | 11.44 | 0.00724457 | 32654.3 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.474082 | 0.00087484 | 2621.308 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | CAV_BAS FAN | Fan:VariableVolume | 6.356989 | 6.69479818 | 4197.9300 | 999.8980 | 26.42134906 | 54.44 | 82.22 | 27.78 | 3081217.97 | 3.2455 | 3.310786 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.474082 | -5.21 | -9.59 | 0.00034190 | -4384.2 | 40.00 | 19.63 | 0.00800000 | 60796.0 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | -27.60 | 0.00034190 | -27.60 | 1.20015641 | 34.5460 | 0.00 | 0.00034190 | 22.90 | 0.00034190 | 1.7422 | 0.00 | 0.00 | 100050.95 | 100050.95 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.01 | 14.59 | 0.00000000 | 40233.3 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 534450.679 | 300859.831 | 28.137529 | 0.01308866 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9144 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 464335.47 | 462573.79 | 0.8688 | -999.0 | -999.0 | 28.66 | 15.39 | 0.00703323 | 46764.1 | 12.80 | 9.41 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 464335.47 | 33.40 | 0.00630683 | 16.37 | 0.33839277 | -999.0000 | 27.00 | 0.00704208 | 27.00 | 0.00704208 | 27.8119 | 371955.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10659.368 | 6063.476 | 0.577319 | 0.00026105 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9656 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | Sensible | 9212.27 | 9146.79 | 0.8642 | -999.0 | -999.0 | 28.06 | 15.21 | 0.00706078 | 46223.5 | 12.80 | 9.41 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9212.27 | 26.28 | 0.00629588 | 13.94 | 0.01563234 | -999.0000 | 27.00 | 0.00708207 | 27.00 | 0.00708207 | 27.9660 | 8786.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 102553.922 | 58326.605 | 5.552900 | 0.00251154 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9699 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | Sensible | 88635.56 | 87982.03 | 0.8643 | -999.0 | -999.0 | 28.06 | 15.21 | 0.00706305 | 46228.5 | 12.80 | 9.41 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 88635.56 | 26.28 | 0.00629588 | 13.94 | 0.15632344 | -999.0000 | 27.00 | 0.00708528 | 27.00 | 0.00708528 | 27.9786 | 84514.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10430.492 | 5932.667 | 0.564832 | 0.00025544 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9681 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:30:00 | Sensible | 9014.72 | 8949.23 | 0.8643 | -999.0 | -999.0 | 28.06 | 15.21 | 0.00706212 | 46226.5 | 12.80 | 9.41 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9014.72 | 26.28 | 0.00629588 | 13.94 | 0.01563234 | -999.0000 | 27.00 | 0.00708393 | 27.00 | 0.00708393 | 27.9733 | 8596.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 534450.679 | 534450.679 | 28.137529 | 0.01308866 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 534450.68 | 534450.68 | 1.0000 | 29.63275347 | 28.137529 | -27.60 | -27.60 | 0.00034190 | -26896.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 534450.68 | -27.60 | 0.00034190 | -27.60 | 0.33839277 | 1.2026 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 27.6430 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10659.368 | 10659.368 | 0.577319 | 0.00026105 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 10659.37 | 10659.37 | 1.0000 | 0.60799715 | 0.577319 | -27.60 | -27.60 | 0.00034190 | -26896.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10659.37 | -27.60 | 0.00034190 | -27.60 | 0.01563234 | 2.7078 | 0.00 | 0.00097294 | 25.18 | 0.00097294 | 4.3190 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 102553.922 | 102553.922 | 5.552900 | 0.00251154 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 102553.92 | 102553.92 | 1.0000 | 5.84798064 | 5.552900 | -27.60 | -27.60 | 0.00034190 | -26896.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 102553.92 | -27.60 | 0.00034190 | -27.60 | 0.15632344 | 2.8152 | 0.00 | 0.00097295 | 23.61 | 0.00097295 | 4.7455 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10430.492 | 10430.492 | 0.564832 | 0.00025544 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 10430.49 | 10430.49 | 1.0000 | 0.59484699 | 0.564832 | -27.60 | -27.60 | 0.00034190 | -26896.1 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10430.49 | -27.60 | 0.00034190 | -27.60 | 0.01563234 | 2.7676 | 0.00 | 0.00097240 | 22.11 | 0.00097240 | 5.1942 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 24207.992 | 24207.992 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 28.137529 | 29.63275347 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 24207.99 | 24207.99 | 1.0000 | 29.63275347 | 28.137529 | -0.33 | -0.33 | 0.00691993 | 16968.5 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24207.99 | -27.60 | 0.00034190 | -27.60 | 0.33839277 | 1.2026 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 27.6430 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1118.309 | 1118.309 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.577319 | 0.60799715 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1118.31 | 1118.31 | 1.0000 | 0.60799715 | 0.577319 | -0.75 | -5.61 | 0.00095585 | 1638.2 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1118.31 | -27.60 | 0.00034190 | -27.60 | 0.01563234 | 2.7078 | 0.00 | 0.00097294 | 25.18 | 0.00097294 | 4.3190 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11183.090 | 11183.090 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 5.552900 | 5.84798064 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 11183.09 | 11183.09 | 1.0000 | 5.84798064 | 5.552900 | -0.78 | -5.63 | 0.00095519 | 1606.7 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11183.09 | -27.60 | 0.00034190 | -27.60 | 0.15632344 | 2.8152 | 0.00 | 0.00097295 | 23.61 | 0.00097295 | 4.7455 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1118.309 | 1118.309 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.564832 | 0.59484699 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1118.31 | 1118.31 | 1.0000 | 0.59484699 | 0.564832 | -0.76 | -5.62 | 0.00095495 | 1619.4 | 40.00 | 19.63 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1118.31 | -27.60 | 0.00034190 | -27.60 | 0.01563234 | 2.7676 | 0.00 | 0.00097240 | 22.11 | 0.00097240 | 5.1942 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 11.10 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 103.57 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 11.69 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 6.36 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 28.14 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2100.83 | 1447.67 | 411.00 |
CORE_BOTTOM | 1504.83 | 1553.33 | 5.67 |
CORE_MID | 916.67 | 3445.17 | 157.67 |
CORE_TOP | 1797.17 | 4130.33 | 1079.17 |
PERIMETER_BOT_ZN_3 | 1748.83 | 3727.83 | 619.33 |
PERIMETER_BOT_ZN_2 | 2217.83 | 3610.50 | 798.17 |
PERIMETER_BOT_ZN_1 | 2501.33 | 3088.83 | 774.50 |
PERIMETER_BOT_ZN_4 | 2540.33 | 2690.83 | 519.67 |
PERIMETER_MID_ZN_3 | 2670.17 | 4323.67 | 1882.17 |
PERIMETER_MID_ZN_2 | 2505.83 | 3526.17 | 1547.00 |
PERIMETER_MID_ZN_1 | 2763.17 | 3454.50 | 1214.83 |
PERIMETER_MID_ZN_4 | 2793.00 | 4093.50 | 1570.33 |
PERIMETER_TOP_ZN_3 | 3296.00 | 4515.17 | 2557.00 |
PERIMETER_TOP_ZN_2 | 3437.33 | 4169.83 | 2257.67 |
PERIMETER_TOP_ZN_1 | 3156.00 | 3781.83 | 1781.67 |
PERIMETER_TOP_ZN_4 | 3270.83 | 4310.50 | 2157.50 |
DATACENTER_BOT_ZN_6 | 5835.83 | 514.50 | 514.50 |
DATACENTER_MID_ZN_6 | 5332.00 | 234.50 | 119.67 |
DATACENTER_TOP_ZN_6 | 4597.17 | 581.00 | 202.17 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5734.00 | 5734.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5936.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 1527.50 | 0.00 | 854.50 |
CORE_BOTTOM | 0.00 | 77.50 | 0.00 | 70.50 |
CORE_MID | 0.33 | 12.17 | 0.00 | 12.17 |
CORE_TOP | 14.67 | 26.67 | 2.83 | 26.67 |
PERIMETER_BOT_ZN_3 | 4.17 | 109.33 | 0.50 | 104.67 |
PERIMETER_BOT_ZN_2 | 4.33 | 65.17 | 0.17 | 64.33 |
PERIMETER_BOT_ZN_1 | 5.50 | 184.00 | 0.17 | 179.67 |
PERIMETER_BOT_ZN_4 | 2.33 | 124.83 | 0.00 | 83.17 |
PERIMETER_MID_ZN_3 | 80.67 | 37.67 | 27.00 | 37.00 |
PERIMETER_MID_ZN_2 | 48.83 | 51.00 | 5.67 | 40.33 |
PERIMETER_MID_ZN_1 | 34.00 | 125.50 | 3.83 | 122.33 |
PERIMETER_MID_ZN_4 | 36.67 | 59.50 | 5.17 | 40.67 |
PERIMETER_TOP_ZN_3 | 253.83 | 39.83 | 94.83 | 37.33 |
PERIMETER_TOP_ZN_2 | 137.67 | 48.33 | 21.50 | 46.50 |
PERIMETER_TOP_ZN_1 | 105.83 | 106.33 | 12.33 | 101.83 |
PERIMETER_TOP_ZN_4 | 103.33 | 59.50 | 15.50 | 40.83 |
DATACENTER_BOT_ZN_6 | 0.00 | 5.83 | 0.00 | 3.67 |
DATACENTER_MID_ZN_6 | 0.00 | 2.17 | 0.00 | 1.17 |
DATACENTER_TOP_ZN_6 | 0.00 | 3.67 | 0.00 | 1.83 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 288.83 | 1711.50 | 102.33 | 1018.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 1.107 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 1.039 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.753 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.696 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.949 | 0.027 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 1.762 | 0.027 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 1.766 | 0.027 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 2.169 | 0.028 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.754 | 0.062 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 1.577 | 0.068 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 1.670 | 0.062 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 1.662 | 0.064 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.762 | 0.077 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 1.685 | 0.079 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 1.629 | 0.077 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 1.687 | 0.079 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 28.020 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 60.99 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.86 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.79 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.20 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1010.73 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 43766765.46 | 0.00 | 43766765.46 | 0.00 | 43766765.46 | 37848132.68 | 4772.93 | 835.51 | 3151.55 | 0.00 |
CORE_BOTTOM | 44084334.95 | 0.00 | 44084334.95 | 0.00 | 44084334.95 | 33990283.35 | 4535.22 | 42.44 | 4182.34 | 425.81 |
CORE_MID | 0.31E+09 | 0.00 | 0.31E+09 | 0.00 | 0.31E+09 | 0.34E+09 | 5958.41 | 36.97 | 2764.62 | 304.70 |
CORE_TOP | 28680932.61 | 0.00 | 28680932.61 | 0.00 | 28680932.61 | 33990283.35 | 6426.57 | 32.66 | 2300.77 | 364.16 |
PERIMETER_BOT_ZN_3 | 5062466.90 | 0.00 | 5062466.90 | 266213.26 | 5328680.15 | 4267819.30 | 5439.62 | 49.81 | 3270.57 | 425.81 |
PERIMETER_BOT_ZN_2 | 6081256.05 | 0.00 | 6081256.05 | 177475.38 | 6258731.43 | 2750345.05 | 3461.80 | 2.73 | 5295.47 | 425.81 |
PERIMETER_BOT_ZN_1 | 9325397.25 | 0.00 | 9325397.25 | 266213.26 | 9591610.50 | 4267912.63 | 3508.99 | 6.35 | 5244.66 | 425.81 |
PERIMETER_BOT_ZN_4 | 7526489.84 | 0.00 | 7526489.84 | 177475.38 | 7703965.22 | 2750345.05 | 3441.98 | 0.66 | 5317.36 | 425.81 |
PERIMETER_MID_ZN_3 | 39158902.49 | 0.00 | 39158902.49 | 624345.56 | 39783248.05 | 42678193.03 | 5808.55 | 59.69 | 2891.77 | 304.70 |
PERIMETER_MID_ZN_2 | 57616034.61 | 0.00 | 57616034.61 | 416230.09 | 58032264.69 | 27503450.52 | 3817.41 | 3.20 | 4939.39 | 1213.70 |
PERIMETER_MID_ZN_1 | 85848552.65 | 0.00 | 85848552.65 | 624345.56 | 86472898.21 | 42679126.28 | 3901.12 | 7.84 | 4851.04 | 304.70 |
PERIMETER_MID_ZN_4 | 55964034.45 | 0.00 | 55964034.45 | 416230.09 | 56380264.53 | 27503450.52 | 3804.65 | 4.65 | 4950.70 | 304.70 |
PERIMETER_TOP_ZN_3 | 3945728.27 | 0.00 | 3945728.27 | 775192.66 | 4720920.92 | 4267819.30 | 5712.92 | 53.11 | 2993.98 | 364.16 |
PERIMETER_TOP_ZN_2 | 5604874.86 | 0.00 | 5604874.86 | 516794.75 | 6121669.61 | 2750345.05 | 3972.68 | 5.89 | 4781.42 | 364.16 |
PERIMETER_TOP_ZN_1 | 8361569.59 | 0.00 | 8361569.59 | 775192.66 | 9136762.25 | 4267912.63 | 4024.77 | 2.94 | 4732.29 | 364.16 |
PERIMETER_TOP_ZN_4 | 5663347.22 | 0.00 | 5663347.22 | 516794.75 | 6180141.97 | 2750345.05 | 3943.59 | 5.56 | 4810.86 | 364.16 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.44E+09 | 0.00 | 0.44E+09 | 0.00 | 0.44E+09 | 10671554.30 | 65.67 | 261.17 | 8433.17 | 2796.50 |
Total Facility | 0.61E+10 | 0.00 | 0.61E+10 | 24282864.96 | 0.62E+10 | 0.50E+10 | 6966.66 | 4395.99 | 8694.58 | 3705.58 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.0457 | 0.0000 | 2.0457 | 0.0000 | 2.0457 | 1.2002 | 1955.93 | 835.51 | 3151.55 |
CORE_BOTTOM | 1.9403 | 0.0000 | 1.9403 | 0.0000 | 1.9403 | 1.0778 | 2036.96 | 40.30 | 3865.75 |
CORE_MID | 14.0672 | 0.0000 | 14.0672 | 0.0000 | 14.0672 | 10.7782 | 3247.25 | 36.63 | 2659.13 |
CORE_TOP | 1.3017 | 0.0000 | 1.3017 | 0.0000 | 1.3017 | 1.0778 | 3695.10 | 32.66 | 2215.24 |
PERIMETER_BOT_ZN_3 | 0.2225 | 0.0000 | 0.2225 | 0.0062 | 0.2288 | 0.1353 | 2935.39 | 47.47 | 2960.13 |
PERIMETER_BOT_ZN_2 | 0.2667 | 0.0000 | 0.2667 | 0.0042 | 0.2708 | 0.0872 | 1040.03 | 2.16 | 4900.82 |
PERIMETER_BOT_ZN_1 | 0.4144 | 0.0000 | 0.4144 | 0.0062 | 0.4206 | 0.1353 | 1074.77 | 4.91 | 4863.32 |
PERIMETER_BOT_ZN_4 | 0.3281 | 0.0000 | 0.3281 | 0.0042 | 0.3323 | 0.0872 | 1023.69 | 0.38 | 4918.94 |
PERIMETER_MID_ZN_3 | 1.7721 | 0.0000 | 1.7721 | 0.0146 | 1.7867 | 1.3533 | 3100.75 | 59.26 | 2782.99 |
PERIMETER_MID_ZN_2 | 2.3909 | 0.0000 | 2.3909 | 0.0103 | 2.4013 | 0.8721 | 1155.06 | 1.94 | 3876.99 |
PERIMETER_MID_ZN_1 | 3.9226 | 0.0000 | 3.9226 | 0.0146 | 3.9372 | 1.3533 | 1205.72 | 6.16 | 4731.11 |
PERIMETER_MID_ZN_4 | 2.5199 | 0.0000 | 2.5199 | 0.0098 | 2.5296 | 0.8721 | 1147.03 | 2.30 | 4793.68 |
PERIMETER_TOP_ZN_3 | 0.1792 | 0.0000 | 0.1792 | 0.0182 | 0.1974 | 0.1353 | 2984.94 | 52.44 | 2905.62 |
PERIMETER_TOP_ZN_2 | 0.2554 | 0.0000 | 0.2554 | 0.0121 | 0.2676 | 0.0872 | 1268.39 | 4.17 | 4670.44 |
PERIMETER_TOP_ZN_1 | 0.3827 | 0.0000 | 0.3827 | 0.0182 | 0.4009 | 0.1353 | 1304.04 | 1.86 | 4637.10 |
PERIMETER_TOP_ZN_4 | 0.2559 | 0.0000 | 0.2559 | 0.0121 | 0.2680 | 0.0872 | 1250.86 | 3.95 | 4688.19 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 14.4300 | 0.0000 | 14.4300 | 0.0000 | 14.4300 | 0.3384 | 45.17 | 261.17 | 5636.67 |
Total Facility | 269.9141 | 0.0000 | 269.9141 | 0.5750 | 270.4891 | 158.4706 | 4149.66 | 4380.63 | 5898.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 79944038.18 | 0.00 | 79944038.18 | 48026705.38 | 3560.14 | 9.34 | 5190.52 | 425.81 |
VAV_MID WITH REHEAT | 0.61E+09 | 0.00 | 0.61E+09 | 0.48E+09 | 3965.41 | 5.79 | 4788.80 | 304.70 |
VAV_TOP WITH REHEAT | 57957588.25 | 0.00 | 57957588.25 | 48026705.38 | 4061.17 | 1.67 | 4697.16 | 364.16 |
CAV_BAS | 48541889.90 | 0.00 | 48541889.90 | 37848132.68 | 4759.67 | 1.69 | 3998.64 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.49E+09 | 0.00 | 0.49E+09 | 10671554.30 | 65.67 | 0.00 | 8694.33 | 2796.50 |
AIRLOOP DATACENTER BOT | 270949.60 | 0.00 | 270949.60 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 2709495.95 | 0.00 | 2709495.95 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 270949.60 | 0.00 | 270949.60 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.5181 | 0.0000 | 3.5181 | 1.5229 | 1100.23 | 6.68 | 4836.09 |
VAV_MID WITH REHEAT | 27.6140 | 0.0000 | 27.6140 | 15.2292 | 1259.73 | 5.17 | 4678.10 |
VAV_TOP WITH REHEAT | 2.6341 | 0.0000 | 2.6341 | 1.5229 | 1332.40 | 1.60 | 4609.00 |
CAV_BAS | 2.2689 | 0.0000 | 2.2689 | 1.2002 | 1942.67 | 1.69 | 3998.64 |
AIRLOOP DATACENTER BASEMENT | 16.0043 | 0.0000 | 16.0043 | 0.3384 | 45.17 | 0.00 | 5897.83 |
AIRLOOP DATACENTER BOT | 0.0127 | 0.0000 | 0.0127 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1266 | 0.0000 | 0.1266 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0127 | 0.0000 | 0.0127 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 13.90 | 3982.97 | 0.00 | 0.00 | 0.00 | 1372.74 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 2.08 | 3653.79 | 0.00 | 0.00 | 0.00 | 1527.02 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.75 | 3049.10 | 0.00 | 0.00 | 0.00 | 2176.00 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 821.31 | 3163.76 | 0.00 | 36.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 261.17 | 8433.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 13.1320 | 5.0778 | 0.0000 | 0.0000 | 0.0000 | 1.9501 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 119.6556 | 40.2512 | 0.0000 | 0.0000 | 0.0000 | 19.0369 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 4.3046 | 0.0000 | 0.0000 | 0.0000 | 1.8801 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.3316 | 3.9061 | 0.0000 | 0.9902 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.3756 | 16.8587 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0173 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.1734 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0173 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1492 |
Defaulted Fields | 1184 |
Fields with Defaults | 3877 |
Autosized Fields | 334 |
Autosizable Fields | 413 |
Autocalculated Fields | 227 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 28565.58 | 308943.99 | 10-SEP-18:40 | 2232576.78 | 08-AUG-15:40 |
Electricity:Building | 17899.14 | 217189.06 | 06-MAY-18:20 | 1104084.83 | 01-DEC-08:10 |
Electricity:Zone:BASEMENT | 640.57 | 14055.89 | 01-JAN-00:10 | 32859.63 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 17899.14 | 217189.06 | 06-MAY-18:20 | 1104084.83 | 01-DEC-08:10 |
InteriorLights:Electricity | 3222.74 | 9932.90 | 26-MAR-17:20 | 325713.14 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 216.17 | 598.35 | 01-JAN-00:10 | 19402.09 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3222.74 | 9932.90 | 26-MAR-17:20 | 325713.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 3222.74 | 9932.90 | 26-MAR-17:20 | 325713.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 216.17 | 598.35 | 01-JAN-00:10 | 19402.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3222.74 | 9932.90 | 26-MAR-17:20 | 325713.14 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 483.75 | 4990.59 | 01-JAN-00:10 | 34631.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4837.49 | 49905.77 | 01-JAN-00:10 | 346310.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1941.37 | 5373.60 | 01-JAN-00:10 | 174244.37 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1941.37 | 5373.60 | 01-JAN-00:10 | 174244.37 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 483.75 | 4990.58 | 01-JAN-00:10 | 34631.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 50.56 | 617.00 | 19-MAR-17:10 | 4348.36 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 14.20 | 57.83 | 01-JAN-10:30 | 2187.81 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 14.20 | 57.83 | 01-JAN-10:30 | 2187.81 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 32.45 | 397.62 | 26-MAR-17:10 | 2802.25 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 9.01 | 37.27 | 01-JAN-08:50 | 1409.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 9.01 | 37.27 | 01-JAN-08:50 | 1409.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 50.22 | 617.01 | 12-MAR-17:10 | 4348.44 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 13.85 | 57.83 | 01-JAN-08:50 | 2187.86 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 13.85 | 57.83 | 01-JAN-08:50 | 2187.86 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 32.48 | 397.61 | 12-MAR-17:10 | 2802.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 9.04 | 37.27 | 01-JAN-10:20 | 1409.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 9.04 | 37.27 | 01-JAN-10:20 | 1409.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 505.31 | 6169.98 | 12-MAR-17:10 | 43483.64 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 141.65 | 578.27 | 01-JAN-10:20 | 21878.12 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 141.65 | 578.27 | 01-JAN-10:20 | 21878.12 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 324.35 | 3976.17 | 26-MAR-17:10 | 28022.51 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 90.00 | 372.66 | 01-JAN-08:50 | 14099.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 90.00 | 372.66 | 01-JAN-08:50 | 14099.09 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 502.04 | 6170.07 | 12-MAR-17:10 | 43484.45 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 138.38 | 578.28 | 01-JAN-08:50 | 21878.60 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 138.38 | 578.28 | 01-JAN-08:50 | 21878.60 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 324.61 | 3976.14 | 12-MAR-17:10 | 28022.42 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 90.26 | 372.66 | 01-JAN-10:10 | 14099.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 90.26 | 372.66 | 01-JAN-10:10 | 14099.09 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 50.53 | 617.00 | 12-MAR-17:10 | 4348.36 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 14.16 | 57.83 | 01-JAN-10:20 | 2187.81 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 14.16 | 57.83 | 01-JAN-10:20 | 2187.81 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 32.44 | 397.62 | 26-MAR-17:10 | 2802.25 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 9.00 | 37.27 | 01-JAN-08:50 | 1409.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 9.00 | 37.27 | 01-JAN-08:50 | 1409.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 50.20 | 617.01 | 12-MAR-17:10 | 4348.44 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 13.84 | 57.83 | 01-JAN-08:50 | 2187.86 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 13.84 | 57.83 | 01-JAN-08:50 | 2187.86 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 32.46 | 397.61 | 12-MAR-17:10 | 2802.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 9.03 | 37.27 | 01-JAN-10:10 | 1409.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 9.03 | 37.27 | 01-JAN-10:10 | 1409.91 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7557.51 | 95212.03 | 01-JAN-00:10 | 385103.08 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 62.65 | 303.90 | 01-JAN-00:10 | 5470.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 62.65 | 303.90 | 01-JAN-00:10 | 5470.56 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 159.04 | 1973.61 | 01-JAN-00:10 | 8244.54 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1590.36 | 19736.13 | 01-JAN-00:10 | 82445.36 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 51.55 | 250.08 | 01-JAN-00:10 | 4501.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 51.55 | 250.08 | 01-JAN-00:10 | 4501.14 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 159.04 | 1973.61 | 01-JAN-00:10 | 8244.54 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 1599.99 | 4154.06 | 11-JAN-02:20 | 512618.02 | 07-SEP-14:50 |
HeatRejection:Electricity | 370.38 | 36.26 | 10-JAN-22:00 | 82444.89 | 20-JUN-11:10 |
General:HeatRejection:Electricity | 370.38 | 36.26 | 10-JAN-22:00 | 82444.89 | 20-JUN-11:10 |
Electricity:HVAC | 6198.32 | 61106.95 | 11-SEP-21:30 | 623269.07 | 30-AUG-15:40 |
ExteriorEquipment:Electricity | 2566.61 | 20217.42 | 01-JAN-00:10 | 233439.18 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 55.01 | 979.82 | 01-JAN-00:10 | 3454.84 | 01-DEC-08:20 |
ElectricityPurchased:Facility | 28565.58 | 308943.99 | 10-SEP-18:40 | 2232576.78 | 08-AUG-15:40 |
ElectricityPurchased:Plant | 28565.58 | 308943.99 | 10-SEP-18:40 | 2232576.78 | 08-AUG-15:40 |
Cogeneration:ElectricityPurchased | 28565.58 | 308943.99 | 10-SEP-18:40 | 2232576.78 | 08-AUG-15:40 |
General:Cogeneration:ElectricityPurchased | 28565.58 | 308943.99 | 10-SEP-18:40 | 2232576.78 | 08-AUG-15:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 28565.58 | 308943.99 | 10-SEP-18:40 | 2232576.78 | 08-AUG-15:40 |
ElectricityNet:Plant | 28565.58 | 308943.99 | 10-SEP-18:40 | 2232576.78 | 08-AUG-15:40 |
Cogeneration:ElectricityNet | 28565.58 | 308943.99 | 10-SEP-18:40 | 2232576.78 | 08-AUG-15:40 |
General:Cogeneration:ElectricityNet | 28565.58 | 308943.99 | 10-SEP-18:40 | 2232576.78 | 08-AUG-15:40 |
Fans:Electricity | 2839.55 | 53710.34 | 01-JAN-16:20 | 355156.41 | 20-JUN-12:20 |
General:Fans:Electricity | 2839.55 | 53710.34 | 01-JAN-16:20 | 355156.41 | 20-JUN-12:20 |
ExteriorLights:Electricity | 356.53 | 0.00 | 01-JAN-08:20 | 40855.88 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 356.53 | 0.00 | 01-JAN-08:20 | 40855.88 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 2505.76 | 19200.00 | 01-JAN-00:10 | 229608.34 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 1304.51 | 1822.08 | 10-JAN-22:00 | 424515.46 | 10-AUG-15:00 |
General:Cooling:Electricity | 1304.51 | 1822.08 | 10-JAN-22:00 | 424515.46 | 10-AUG-15:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 2430.35 | 0.00 | 02-MAY-11:50 | 100000.00 | 01-FEB-17:20 |
General:Humidifier:Electricity | 2430.35 | 0.00 | 02-MAY-11:50 | 100000.00 | 01-FEB-17:20 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 478.32 | 0.00 | 01-JAN-00:10 | 58670.54 | 17-FEB-13:00 |
Water Heater:WaterSystems:Electricity | 478.32 | 0.00 | 01-JAN-00:10 | 58670.54 | 17-FEB-13:00 |
Pumps:Electricity | 320.20 | 4110.56 | 01-JAN-00:10 | 50204.23 | 07-SEP-14:50 |
General:Pumps:Electricity | 320.20 | 4110.56 | 01-JAN-00:10 | 50204.23 | 07-SEP-14:50 |
WIRED_LTG_ELECTRICITY | 90.56 | 0.00 | 01-JAN-00:10 | 9152.54 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 3062.05 | 0.00 | 01-JAN-00:10 | 2312548.53 | 09-JAN-07:20 |
NaturalGas:Plant | 3062.05 | 0.00 | 01-JAN-00:10 | 2312548.53 | 09-JAN-07:20 |
Heating:NaturalGas | 3062.05 | 0.00 | 01-JAN-00:10 | 2312548.53 | 09-JAN-07:20 |
Boiler:Heating:NaturalGas | 3062.05 | 0.00 | 01-JAN-00:10 | 2312548.53 | 09-JAN-07:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 7509.54 | 4296.53 | 10-JAN-22:00 | 2509606.64 | 07-SEP-15:00 |
PlantLoopCoolingDemand:HVAC | 7509.54 | 4296.53 | 10-JAN-22:00 | 2509606.64 | 07-SEP-15:00 |
CoolingCoils:PlantLoopCoolingDemand | 7509.54 | 4296.53 | 10-JAN-22:00 | 2509606.64 | 07-SEP-15:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 6567.95 | 0.00 | 20-MAY-23:10 | 0.00 | 25-JUL-12:40 |
Water:HVAC | 904.09 | 0.00 | 02-MAY-11:50 | 0.00 | 02-FEB-04:10 |
Humidifier:Water | 904.09 | 0.00 | 02-MAY-11:50 | 0.00 | 02-FEB-04:10 |
General:Humidifier:Water | 904.09 | 0.00 | 02-MAY-11:50 | 0.00 | 02-FEB-04:10 |
MainsWater:Facility | 6567.95 | 0.00 | 20-MAY-23:10 | 0.00 | 25-JUL-12:40 |
MainsWater:HVAC | 904.09 | 0.00 | 02-MAY-11:50 | 0.00 | 02-FEB-04:10 |
Humidifier:MainsWater | 904.09 | 0.00 | 02-MAY-11:50 | 0.00 | 02-FEB-04:10 |
General:Humidifier:MainsWater | 904.09 | 0.00 | 02-MAY-11:50 | 0.00 | 02-FEB-04:10 |
Water:Plant | 5663.85 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUL-12:40 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 5663.85 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUL-12:40 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 3383.68 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUL-12:40 |
General:HeatRejection:Water | 3383.68 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUL-12:40 |
HeatRejection:MainsWater | 3383.68 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUL-12:40 |
General:HeatRejection:MainsWater | 3383.68 | 0.00 | 01-JAN-00:10 | 0.00 | 25-JUL-12:40 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 42613.47 | 95897.89 | 10-JAN-03:30 | 10828559.11 | 07-SEP-14:50 |
EnergyTransfer:Building | 18865.04 | 88498.15 | 21-JAN-21:20 | 1793694.93 | 08-AUG-15:30 |
EnergyTransfer:Zone:BASEMENT | 598.65 | 0.00 | 01-JAN-00:10 | 109910.42 | 02-JAN-07:10 |
Heating:EnergyTransfer | 747.58 | 0.00 | 13-JAN-22:10 | 1230835.87 | 09-JAN-06:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.93 | 01-SEP-21:00 |
General:Heating:EnergyTransfer | 747.58 | 0.00 | 13-JAN-22:10 | 1230835.87 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.93 | 01-SEP-21:00 |
Cooling:EnergyTransfer | 18117.46 | 83942.40 | 09-JAN-04:40 | 1793694.93 | 08-AUG-15:30 |
Cooling:EnergyTransfer:Zone:BASEMENT | 598.65 | 0.00 | 01-JAN-00:10 | 109910.42 | 02-JAN-07:10 |
General:Cooling:EnergyTransfer | 18117.46 | 83942.40 | 09-JAN-04:40 | 1793694.93 | 08-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 598.65 | 0.00 | 01-JAN-00:10 | 109910.42 | 02-JAN-07:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 619.51 | 0.00 | 01-JAN-00:10 | 66997.63 | 21-JUL-09:30 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 619.51 | 0.00 | 01-JAN-00:10 | 66997.63 | 21-JUL-09:30 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 619.51 | 0.00 | 01-JAN-00:10 | 66997.63 | 21-JUL-09:30 |
EnergyTransfer:Zone:CORE_MID | 4196.42 | 0.00 | 01-JAN-00:10 | 516662.76 | 22-JUN-10:20 |
Heating:EnergyTransfer:Zone:CORE_MID | 5.26 | 0.00 | 01-JAN-00:10 | 319127.39 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 5.26 | 0.00 | 01-JAN-00:10 | 319127.39 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4191.16 | 0.00 | 01-JAN-00:10 | 516662.76 | 22-JUN-10:20 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4191.16 | 0.00 | 01-JAN-00:10 | 516662.76 | 22-JUN-10:20 |
EnergyTransfer:Zone:CORE_TOP | 369.07 | 0.00 | 01-JAN-00:10 | 70423.61 | 09-JAN-05:40 |
Heating:EnergyTransfer:Zone:CORE_TOP | 18.77 | 0.00 | 01-JAN-00:10 | 70423.61 | 09-JAN-05:40 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 18.77 | 0.00 | 01-JAN-00:10 | 70423.61 | 09-JAN-05:40 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 350.31 | 0.00 | 01-JAN-00:10 | 57997.48 | 21-JUN-12:50 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 350.31 | 0.00 | 01-JAN-00:10 | 57997.48 | 21-JUN-12:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 66.47 | 0.00 | 01-JAN-00:10 | 11901.90 | 09-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 2.44 | 0.00 | 01-JAN-00:10 | 11901.90 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 2.44 | 0.00 | 01-JAN-00:10 | 11901.90 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 64.02 | 0.00 | 01-JAN-00:10 | 11833.15 | 20-JUL-19:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 64.02 | 0.00 | 01-JAN-00:10 | 11833.15 | 20-JUL-19:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 74.48 | 0.00 | 01-JAN-00:10 | 18075.74 | 07-AUG-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.81 | 0.00 | 01-JAN-00:10 | 9051.53 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.81 | 0.00 | 01-JAN-00:10 | 9051.53 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 72.67 | 0.00 | 01-JAN-00:10 | 18075.74 | 07-AUG-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 72.67 | 0.00 | 01-JAN-00:10 | 18075.74 | 07-AUG-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 124.86 | 0.00 | 01-JAN-00:10 | 25389.81 | 18-OCT-13:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 2.74 | 0.00 | 01-JAN-00:10 | 14632.86 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 2.74 | 0.00 | 01-JAN-00:10 | 14632.86 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 122.13 | 0.00 | 01-JAN-00:10 | 25389.81 | 18-OCT-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 122.13 | 0.00 | 01-JAN-00:10 | 25389.81 | 18-OCT-13:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 101.05 | 0.00 | 01-JAN-00:10 | 22663.26 | 31-JUL-17:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.59 | 0.00 | 01-JAN-00:10 | 6962.32 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.59 | 0.00 | 01-JAN-00:10 | 6962.32 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 100.46 | 0.00 | 01-JAN-00:10 | 22663.26 | 31-JUL-17:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 100.46 | 0.00 | 01-JAN-00:10 | 22663.26 | 31-JUL-17:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 576.43 | 0.00 | 01-JAN-00:10 | 134267.04 | 09-JAN-04:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 163.04 | 0.00 | 01-JAN-00:10 | 134267.04 | 09-JAN-04:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 163.04 | 0.00 | 01-JAN-00:10 | 134267.04 | 09-JAN-04:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 413.38 | 0.00 | 01-JAN-00:10 | 110939.20 | 25-JUL-16:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 413.38 | 0.00 | 01-JAN-00:10 | 110939.20 | 25-JUL-16:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 696.94 | 0.00 | 01-JAN-00:10 | 183399.29 | 07-AUG-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 94.91 | 0.00 | 01-JAN-00:10 | 145007.79 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 94.91 | 0.00 | 01-JAN-00:10 | 145007.79 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 602.04 | 0.00 | 01-JAN-00:10 | 183399.29 | 07-AUG-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 602.04 | 0.00 | 01-JAN-00:10 | 183399.29 | 07-AUG-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1175.08 | 0.00 | 01-JAN-00:10 | 272175.99 | 18-OCT-13:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 92.36 | 0.00 | 01-JAN-00:10 | 203046.09 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 92.36 | 0.00 | 01-JAN-00:10 | 203046.09 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1082.72 | 0.00 | 01-JAN-00:10 | 272175.99 | 18-OCT-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1082.72 | 0.00 | 01-JAN-00:10 | 272175.99 | 18-OCT-13:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 692.81 | 0.00 | 01-JAN-00:10 | 219229.46 | 31-JUL-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 76.16 | 0.00 | 01-JAN-00:10 | 135240.25 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 76.16 | 0.00 | 01-JAN-00:10 | 135240.25 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 616.65 | 0.00 | 01-JAN-00:10 | 219229.46 | 31-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 616.65 | 0.00 | 01-JAN-00:10 | 219229.46 | 31-JUL-17:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 75.74 | 0.00 | 01-JAN-00:10 | 16154.42 | 09-JAN-04:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 38.78 | 0.00 | 01-JAN-00:10 | 16154.42 | 09-JAN-04:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 38.78 | 0.00 | 01-JAN-00:10 | 16154.42 | 09-JAN-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 36.96 | 0.00 | 01-JAN-00:10 | 11414.90 | 25-JUL-17:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 36.96 | 0.00 | 01-JAN-00:10 | 11414.90 | 25-JUL-17:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 77.20 | 0.00 | 01-JAN-00:10 | 18962.53 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 22.10 | 0.00 | 01-JAN-00:10 | 18962.53 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 22.10 | 0.00 | 01-JAN-00:10 | 18962.53 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 55.10 | 0.00 | 01-JAN-00:10 | 18420.66 | 07-AUG-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 55.10 | 0.00 | 01-JAN-00:10 | 18420.66 | 07-AUG-09:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 122.65 | 0.00 | 01-JAN-00:10 | 27491.09 | 18-OCT-13:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 24.89 | 0.00 | 01-JAN-00:10 | 24132.59 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 24.89 | 0.00 | 01-JAN-00:10 | 24132.59 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 97.75 | 0.00 | 01-JAN-00:10 | 27491.09 | 18-OCT-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 97.75 | 0.00 | 01-JAN-00:10 | 27491.09 | 18-OCT-13:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 75.25 | 0.00 | 01-JAN-00:10 | 22538.99 | 31-JUL-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 18.13 | 0.00 | 01-JAN-00:10 | 19291.59 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 18.13 | 0.00 | 01-JAN-00:10 | 19291.59 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 57.12 | 0.00 | 01-JAN-00:10 | 22538.99 | 31-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 57.12 | 0.00 | 01-JAN-00:10 | 22538.99 | 31-JUL-17:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 62.28 | 0.00 | 01-JAN-00:10 | 12623.07 | 18-JUL-16:30 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 3.57 | 0.00 | 01-JAN-00:10 | 6012.51 | 30-JAN-13:10 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 3.57 | 0.00 | 01-JAN-00:10 | 6012.51 | 30-JAN-13:10 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 58.71 | 0.00 | 01-JAN-00:10 | 12623.07 | 18-JUL-16:30 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 58.71 | 0.00 | 01-JAN-00:10 | 12623.07 | 18-JUL-16:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 460.11 | 0.00 | 01-JAN-00:10 | 107180.02 | 09-JAN-06:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 115.34 | 0.00 | 01-JAN-00:10 | 107180.02 | 09-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 115.34 | 0.00 | 01-JAN-00:10 | 107180.02 | 09-JAN-06:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 344.78 | 0.00 | 01-JAN-00:10 | 87015.91 | 10-AUG-15:50 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 344.78 | 0.00 | 01-JAN-00:10 | 87015.91 | 10-AUG-15:50 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 110.36 | 0.00 | 01-JAN-00:10 | 34334.81 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 60.63 | 0.00 | 01-JAN-00:10 | 34334.81 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 60.63 | 0.00 | 01-JAN-00:10 | 34334.81 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 49.73 | 0.00 | 01-JAN-00:10 | 21942.77 | 14-JUL-14:40 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 49.73 | 0.00 | 01-JAN-00:10 | 21942.77 | 14-JUL-14:40 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 137.03 | 6.85 | 08-JAN-11:30 | 8513.29 | 22-APR-18:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.02 | 0.00 | 01-JAN-00:10 | 458.92 | 09-JAN-04:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.02 | 0.00 | 01-JAN-00:10 | 458.92 | 09-JAN-04:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 137.00 | 0.00 | 08-JAN-02:30 | 8513.29 | 22-APR-18:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 137.00 | 0.00 | 08-JAN-02:30 | 8513.29 | 22-APR-18:10 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1173.68 | 8.61 | 11-JAN-12:20 | 81659.68 | 03-AUG-18:50 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 4.94 | 0.00 | 01-JAN-15:20 | 6540.96 | 29-JAN-18:40 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 4.94 | 0.00 | 01-JAN-15:20 | 6540.96 | 29-JAN-18:40 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1168.74 | 0.00 | 01-JAN-00:10 | 81659.68 | 03-AUG-18:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1168.74 | 0.00 | 01-JAN-00:10 | 81659.68 | 03-AUG-18:50 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 106.23 | 0.09 | 18-JAN-11:10 | 8227.78 | 03-AUG-18:50 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 1.09 | 0.00 | 02-JAN-13:10 | 702.52 | 28-JAN-20:00 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 1.09 | 0.00 | 02-JAN-13:10 | 702.52 | 28-JAN-20:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 105.13 | 0.00 | 01-JAN-00:10 | 8227.78 | 03-AUG-18:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 105.13 | 0.00 | 01-JAN-00:10 | 8227.78 | 03-AUG-18:50 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7172.74 | 83922.58 | 09-JAN-05:00 | 370592.81 | 07-AUG-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7172.74 | 83922.58 | 09-JAN-05:00 | 370592.81 | 07-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7172.74 | 83922.58 | 09-JAN-05:00 | 370592.81 | 07-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 2864.92 | 0.00 | 01-JAN-00:10 | 1950289.79 | 09-JAN-07:20 |
PlantLoopHeatingDemand:Plant | 472.97 | 0.00 | 01-JAN-00:10 | 58297.13 | 17-FEB-12:10 |
WaterSystems:PlantLoopHeatingDemand | 472.97 | 0.00 | 01-JAN-00:10 | 58297.13 | 17-FEB-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 472.97 | 0.00 | 01-JAN-00:10 | 58297.13 | 17-FEB-12:10 |
EnergyTransfer:HVAC | 9028.09 | 3419.27 | 10-JAN-22:30 | 2461995.26 | 07-SEP-15:00 |
HeatingCoils:EnergyTransfer | 2391.95 | 0.00 | 01-JAN-00:10 | 1931340.26 | 09-JAN-07:20 |
PlantLoopHeatingDemand:HVAC | 2391.95 | 0.00 | 01-JAN-00:10 | 1931340.26 | 09-JAN-07:20 |
HeatingCoils:PlantLoopHeatingDemand | 2391.95 | 0.00 | 01-JAN-00:10 | 1931340.26 | 09-JAN-07:20 |
CoolingCoils:EnergyTransfer | 6636.14 | 2474.44 | 10-JAN-22:00 | 2461995.26 | 07-SEP-15:00 |
EnergyTransfer:Plant | 14720.35 | 0.00 | 01-JAN-00:10 | 7204873.09 | 07-SEP-14:50 |
LoopToLoop:EnergyTransfer | 3796.99 | 0.00 | 01-JAN-00:10 | 2296927.52 | 07-SEP-14:50 |
WaterSystems:EnergyTransfer | 472.97 | 0.00 | 01-JAN-00:10 | 58297.13 | 17-FEB-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 472.97 | 0.00 | 01-JAN-00:10 | 58297.13 | 17-FEB-12:10 |
Boilers:EnergyTransfer | 2379.50 | 0.00 | 01-JAN-00:10 | 1916453.36 | 09-JAN-07:20 |
Chillers:EnergyTransfer | 3819.89 | 0.00 | 01-JAN-00:10 | 2264108.25 | 07-SEP-14:50 |
HeatRejection:EnergyTransfer | 4250.99 | 0.00 | 01-JAN-00:10 | 2617166.07 | 07-SEP-14:50 |
General:HeatRejection:EnergyTransfer | 4250.99 | 0.00 | 01-JAN-00:10 | 2617166.07 | 07-SEP-14:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -598.631 | 0.000 | 0.000 | 90.112 | 216.171 | 424.397 | 0.000 | 0.000 | 0.000 | 0.001 | 0.000 | 0.000 | 0.000 | 0.000 | -132.049 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -619.513 | 0.000 | 0.000 | 83.307 | 194.137 | 289.614 | 0.000 | 0.000 | 0.000 | 52.455 | 0.000 | 0.000 | 0.000 | 0.000 | -0.009 |
CORE_MID | 0.000 | 0.000 | 5.264 | -4191.134 | 0.000 | 0.000 | 849.787 | 1941.366 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1501.411 |
CORE_TOP | 0.000 | 0.000 | 18.769 | -350.302 | 0.000 | 0.000 | 88.505 | 194.137 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -240.721 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 2.445 | -64.025 | 0.000 | 0.000 | 10.901 | 14.198 | 36.365 | 29.464 | 0.000 | 0.036 | 58.375 | 0.000 | -83.029 | 0.000 | -4.730 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 1.815 | -72.667 | 0.000 | 0.000 | 7.107 | 9.012 | 23.435 | 69.160 | 0.000 | 0.025 | 15.998 | 0.000 | -50.780 | 0.000 | -3.107 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 2.740 | -122.124 | 0.000 | 0.000 | 10.822 | 13.853 | 36.366 | 150.083 | 0.000 | 0.035 | 0.001 | 0.000 | -75.451 | 0.000 | -4.761 | -11.562 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.593 | -100.456 | 0.000 | 0.000 | 6.970 | 9.040 | 23.435 | 64.853 | 0.000 | 0.024 | 56.679 | 0.000 | -57.763 | 0.000 | -3.375 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 163.041 | -413.382 | 0.000 | 0.000 | 114.354 | 141.655 | 363.654 | 308.534 | 0.000 | 0.892 | 183.315 | 0.000 | -762.413 | 0.000 | -99.649 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 94.906 | -602.037 | 0.000 | 0.000 | 54.013 | 89.998 | 234.352 | 695.136 | 0.000 | 0.588 | 0.021 | 0.000 | -479.028 | 0.000 | -67.572 | -20.355 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 92.361 | -1082.709 | 0.000 | 0.000 | 110.384 | 138.377 | 363.660 | 1496.510 | 0.000 | 0.808 | 0.018 | 0.000 | -733.528 | 0.000 | -106.955 | -278.908 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 76.160 | -616.640 | 0.000 | 0.000 | 74.113 | 90.256 | 234.351 | 663.363 | 0.000 | 0.576 | 63.753 | 0.000 | -516.582 | 0.000 | -69.349 | -0.004 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 38.777 | -36.963 | 0.000 | 0.000 | 11.649 | 14.164 | 36.365 | 31.596 | 0.000 | 0.108 | 0.002 | 0.000 | -72.210 | 0.000 | -11.659 | -11.826 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 22.100 | -55.099 | 0.000 | 0.000 | 7.409 | 9.000 | 23.435 | 70.027 | 0.000 | 0.070 | 0.002 | 0.000 | -45.642 | 0.000 | -7.954 | -23.346 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 24.891 | -97.753 | 0.000 | 0.000 | 11.243 | 13.837 | 36.366 | 150.522 | 0.000 | 0.097 | 0.004 | 0.000 | -69.585 | 0.000 | -12.527 | -57.092 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 18.130 | -57.122 | 0.000 | 0.000 | 7.515 | 9.025 | 23.435 | 66.654 | 0.000 | 0.070 | 0.001 | 0.000 | -49.408 | 0.000 | -8.199 | -10.101 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.024 | -137.003 | 0.000 | 0.000 | 0.950 | 5.155 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -23.007 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 4.938 | -1168.737 | 0.000 | 0.000 | 9.519 | 51.551 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -436.077 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 1.091 | -105.134 | 0.000 | 0.000 | 0.957 | 5.155 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -55.949 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7172.737 | 0.000 | 0.000 | 20.565 | 62.653 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -405.339 |
GROUNDFLOOR_PLENUM | 3.574 | -58.708 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.067 | 65.162 | 0.000 | 0.000 | 0.000 | -10.095 | 0.000 |
MIDFLOOR_PLENUM | 115.337 | -344.775 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.300 | 399.322 | 0.000 | 0.000 | 0.000 | -171.184 | -0.005 |
TOPFLOOR_PLENUM | 60.627 | -49.730 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.115 | 6.947 | 0.000 | 0.000 | 0.000 | -17.959 | -0.002 |
Total Facility | 179.539 | -453.212 | 568.045 | -17664.166 | 0.000 | 0.000 | 1570.182 | 3222.740 | 14676.396 | 3795.902 | 0.000 | 4.809 | 902.054 | 0.000 | -2995.418 | 0.000 | -599.077 | -3207.763 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 21-JUL-06:11 | 0.00 | 0.00 | 0.00 | -125792.31 | 0.00 | 0.00 | 1068.96 | 6467.36 | 13457.54 | 0.00 | 0.00 | 0.00 | 104798.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 22-JUN-04:13 | 0.00 | 0.00 | 0.00 | -96899.02 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 90424.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 11-SEP-04:12 | 0.00 | 0.00 | 0.00 | -829889.55 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 765139.72 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 21-JUN-04:12 | 0.00 | 0.00 | 0.00 | -80294.82 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 73819.83 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 23-JUL-18:01 | 0.00 | 0.00 | 0.00 | -16784.16 | 0.00 | 0.00 | 0.00 | 57.83 | 559.17 | 4688.70 | 0.00 | 0.00 | 11565.77 | 0.00 | -0.00 | 0.00 | -87.32 | 0.00 |
PERIMETER_BOT_ZN_2 | 09-JUL-09:51 | 0.00 | 0.00 | 0.00 | -27316.54 | 0.00 | 0.00 | 18.95 | 37.27 | 464.11 | 16908.36 | 0.00 | 0.00 | 9964.35 | 0.00 | -0.00 | 0.00 | -76.49 | 0.00 |
PERIMETER_BOT_ZN_1 | 26-FEB-14:11 | 0.00 | 0.00 | 0.00 | -35467.48 | 0.00 | 0.00 | 26.52 | 57.83 | 720.19 | 35537.33 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -238.31 | -636.08 |
PERIMETER_BOT_ZN_4 | 09-JUL-17:11 | 0.00 | 0.00 | 0.00 | -36205.75 | 0.00 | 0.00 | 0.00 | 37.27 | 360.35 | 22523.42 | 0.00 | 0.00 | 13309.37 | 0.00 | -0.00 | 0.00 | -24.65 | 0.00 |
PERIMETER_MID_ZN_3 | 02-JUL-18:21 | 0.00 | 0.00 | 0.00 | -155877.13 | 0.00 | 0.00 | 0.00 | 578.27 | 5591.71 | 72525.87 | 0.00 | 0.00 | 77624.19 | 0.00 | -0.00 | 0.00 | -442.92 | 0.00 |
PERIMETER_MID_ZN_2 | 06-AUG-09:11 | 0.00 | 0.00 | 0.00 | -323593.48 | 0.00 | 0.00 | 135.11 | 372.66 | 4641.14 | 223716.85 | 0.00 | 0.00 | 95206.21 | 0.00 | -0.00 | 0.00 | -478.49 | 0.00 |
PERIMETER_MID_ZN_1 | 26-FEB-14:11 | 0.00 | 0.00 | 0.00 | -376228.10 | 0.00 | 0.00 | 223.99 | 578.28 | 7201.95 | 351361.27 | 0.00 | 0.00 | 22794.14 | 0.00 | -0.00 | 0.00 | -5931.53 | 0.00 |
PERIMETER_MID_ZN_4 | 02-JUL-18:21 | 0.00 | 0.00 | 0.00 | -341376.39 | 0.00 | 0.00 | 0.00 | 372.66 | 3603.49 | 222584.35 | 0.00 | 0.00 | 115588.67 | 0.00 | -0.00 | 0.00 | -772.78 | 0.00 |
PERIMETER_TOP_ZN_3 | 02-JUL-18:21 | 0.00 | 0.00 | 0.00 | -18004.22 | 0.00 | 0.00 | 0.00 | 57.83 | 559.17 | 7102.99 | 0.00 | 0.00 | 10352.53 | 0.00 | -0.00 | 0.00 | -68.30 | 0.00 |
PERIMETER_TOP_ZN_2 | 02-JUL-09:01 | 0.00 | 0.00 | 0.00 | -32060.94 | 0.00 | 0.00 | 14.63 | 37.27 | 464.11 | 21179.48 | 0.00 | 0.00 | 10550.34 | 0.00 | -0.00 | 0.00 | -184.89 | 0.00 |
PERIMETER_TOP_ZN_1 | 03-SEP-12:41 | 0.00 | 0.00 | 0.00 | -39939.72 | 0.00 | 0.00 | 20.95 | 57.83 | 720.19 | 31802.90 | 0.00 | 131.03 | 7206.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 02-JUL-18:21 | 0.00 | 0.00 | 0.00 | -35959.20 | 0.00 | 0.00 | 0.00 | 37.27 | 360.35 | 22170.95 | 0.00 | 0.00 | 13490.93 | 0.00 | -0.00 | 0.00 | -100.29 | 0.00 |
DATACENTER_BOT_ZN_6 | 16-APR-18:16 | 0.00 | 0.00 | 0.00 | -8516.00 | 0.00 | 0.00 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 696.57 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 03-AUG-18:50 | 0.00 | 0.00 | 0.00 | -81657.06 | 0.00 | 0.00 | 106.16 | 1500.36 | 77944.22 | 0.00 | 0.00 | 0.00 | 2106.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 03-AUG-18:50 | 0.00 | 0.00 | 0.00 | -8227.52 | 0.00 | 0.00 | 10.62 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 272.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 07-AUG-16:00 | 0.00 | 0.00 | 0.00 | -370592.87 | 0.00 | 0.00 | 2181.59 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -16691.80 |
GROUNDFLOOR_PLENUM | 17-JUL-05:15 | 0.00 | -15334.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15356.65 | 0.00 | -0.00 | 0.00 | -21.91 | 0.00 |
MIDFLOOR_PLENUM | 06-JAN-04:11 | 0.00 | -148624.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175898.93 | 0.00 | -0.00 | 0.00 | -27274.04 | 0.00 |
TOPFLOOR_PLENUM | 25-JUL-17:04 | 0.00 | -25895.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.43 | 25803.97 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-AUG-04:12 | 0.00 | 45018.55 | 0.00 | -1928889.08 | 0.00 | 0.00 | 0.00 | 10917.52 | 587299.42 | 0.00 | 0.00 | 0.00 | 1370890.15 | 0.00 | -76196.20 | 0.00 | -9040.37 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 01-SEP-21:00 | 0.00 | 0.00 | 0.93 | 0.00 | 0.00 | 0.00 | 638.00 | 4311.49 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -18407.97 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 09-JAN-05:01 | 0.00 | 0.00 | 483990.81 | 0.00 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -548740.64 |
CORE_TOP | 09-JAN-04:11 | 0.00 | 0.00 | 80451.20 | 0.00 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -86926.18 |
PERIMETER_BOT_ZN_3 | 09-JAN-04:01 | 0.00 | 0.00 | 14235.51 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8724.20 | 0.00 | -381.80 | -5942.55 |
PERIMETER_BOT_ZN_2 | 09-JAN-04:01 | 0.00 | 0.00 | 16126.79 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5775.29 | 0.00 | -254.83 | -10620.61 |
PERIMETER_BOT_ZN_1 | 09-JAN-04:01 | 0.00 | 0.00 | 23444.81 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8339.57 | 0.00 | -378.84 | -15539.44 |
PERIMETER_BOT_ZN_4 | 09-JAN-04:01 | 0.00 | 0.00 | 13937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5827.42 | 0.00 | -261.37 | -8372.77 |
PERIMETER_MID_ZN_3 | 31-DEC-23:31 | 0.00 | 0.00 | 146067.80 | 0.00 | 0.00 | 0.00 | 0.00 | 674.71 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -75127.20 | 0.00 | -8049.38 | -69157.64 |
PERIMETER_MID_ZN_2 | 31-DEC-23:31 | 0.00 | 0.00 | 210943.71 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 3603.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -50082.05 | 0.00 | -5479.43 | -159420.55 |
PERIMETER_MID_ZN_1 | 31-DEC-23:31 | 0.00 | 0.00 | 263021.98 | 0.00 | 0.00 | 0.00 | 0.00 | 674.72 | 5591.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -77855.45 | 0.00 | -8212.18 | -183220.87 |
PERIMETER_MID_ZN_4 | 09-JAN-02:41 | 0.00 | 0.00 | 210961.66 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -54491.99 | 0.00 | -8099.62 | -153609.50 |
PERIMETER_TOP_ZN_3 | 09-JAN-04:11 | 0.00 | 0.00 | 17621.95 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8031.05 | 0.00 | -1013.17 | -9390.76 |
PERIMETER_TOP_ZN_2 | 09-JAN-04:11 | 0.00 | 0.00 | 24545.46 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5350.86 | 0.00 | -685.99 | -19032.56 |
PERIMETER_TOP_ZN_1 | 09-JAN-04:11 | 0.00 | 0.00 | 30194.24 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7821.38 | 0.00 | -1028.71 | -22157.19 |
PERIMETER_TOP_ZN_4 | 09-JAN-04:11 | 0.00 | 0.00 | 26700.23 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5232.10 | 0.00 | -693.09 | -21298.99 |
DATACENTER_BOT_ZN_6 | 30-JAN-01:21 | 0.00 | 0.00 | 541.95 | 0.00 | 0.00 | 0.00 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2515.56 |
DATACENTER_MID_ZN_6 | 29-JAN-18:33 | 0.00 | 0.00 | 6713.06 | 0.00 | 0.00 | 0.00 | 0.00 | 250.08 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -26449.20 |
DATACENTER_TOP_ZN_6 | 29-JAN-17:53 | 0.00 | 0.00 | 737.54 | 0.00 | 0.00 | 0.00 | 6.42 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2717.57 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 16-APR-15:21 | 14960.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -220.63 | -14739.72 |
MIDFLOOR_PLENUM | 16-APR-16:01 | 168826.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2781.49 | -166044.84 |
TOPFLOOR_PLENUM | 09-JAN-05:11 | 35532.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1561.61 | -33971.12 |
Total Facility | 09-JAN-06:01 | -41675.56 | 98249.27 | 1442903.26 | -98249.27 | 0.00 | 0.00 | 22210.98 | 10917.52 | 261414.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -344209.08 | 0.00 | -13274.60 | -1338287.50 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 13.3226 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.1001 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 128.7564 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 103.5696 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 13.0351 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.6949 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.3570 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.3570 | 0.1888 | 1.0000 | Not calculated | 1.2002 | 0.1888 | ||
AIRLOOP DATACENTER BASEMENT | 28.1374 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 28.1375 | 0.0120 | 1.0000 | Not calculated | 0.3384 | 0.0120 | ||
AIRLOOP DATACENTER BOT | 0.5773 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5773 | 0.0271 | 1.0000 | Not calculated | 0.0156 | 0.0271 | ||
AIRLOOP DATACENTER MID | 5.5529 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.5529 | 0.0282 | 1.0000 | Not calculated | 0.1563 | 0.0282 | ||
AIRLOOP DATACENTER TOP | 0.5648 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5648 | 0.0277 | 1.0000 | Not calculated | 0.0156 | 0.0277 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 6.6613 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.3531 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 64.3782 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 33.1697 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 6.5175 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.4296 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 0.0000 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 0.0000 | 1.0000 | 1.0000 | Not calculated | 1.2002 | |||
AIRLOOP DATACENTER BASEMENT | 28.1374 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 28.1374 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0120 | ||
AIRLOOP DATACENTER BOT | 0.5773 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5773 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0271 | ||
AIRLOOP DATACENTER MID | 5.5529 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.5529 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0282 | ||
AIRLOOP DATACENTER TOP | 0.5648 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5648 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0277 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 6.3570 | 6.3570 | 0.0000 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.7029 | 6.7029 | 2.0042 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 63.1005 | 63.1005 | 19.6874 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.1139 | 6.1139 | 2.0298 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1355 | 1.1355 | 0.2521 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5957 | 1.5957 | 0.3191 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9431 | 1.9431 | 0.3886 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9453 | 1.9453 | 0.3891 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.6402 | 10.6402 | 2.4792 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 17.0591 | 17.0591 | 3.4118 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 19.7325 | 19.7325 | 3.9465 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 18.2241 | 18.2241 | 3.6448 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1989 | 1.1989 | 0.2554 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7063 | 1.7063 | 0.3413 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1023 | 2.1023 | 0.4205 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9137 | 1.9137 | 0.3827 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5773 | 0.5773 | 0.5773 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.5529 | 5.5529 | 5.5529 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5648 | 0.5648 | 0.5648 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 28.1374 | 28.1374 | 28.1374 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 13.3226 | 11.1001 | 13.3226 | 3.3531 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 128.7564 | 103.5696 | 128.7564 | 33.1697 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 13.0351 | 11.6949 | 13.0351 | 3.4296 | 0.0000 | 1.0000 |
CAV_BAS | 6.3570 | 6.3570 | 6.3570 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 28.1374 | 28.1375 | 28.1374 | 28.1374 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5773 | 0.5773 | 0.5773 | 0.5773 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.5529 | 5.5529 | 5.5529 | 5.5529 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5648 | 0.5648 | 0.5648 | 0.5648 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 0.0000 | 0.0000 | 0.0000 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3514 | 3.3514 | 2.0042 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 31.5503 | 31.5503 | 19.6874 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0569 | 3.0569 | 2.0298 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5677 | 0.5677 | 0.2521 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7979 | 0.7979 | 0.3191 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9716 | 0.9716 | 0.3886 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9727 | 0.9727 | 0.3891 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.3201 | 5.3201 | 2.4792 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.5296 | 8.5296 | 3.4118 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.8662 | 9.8662 | 3.9465 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.1121 | 9.1121 | 3.6448 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5994 | 0.5994 | 0.2554 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8532 | 0.8532 | 0.3413 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0512 | 1.0512 | 0.4205 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9569 | 0.9569 | 0.3827 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5773 | 0.5773 | 0.5773 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.5529 | 5.5529 | 5.5529 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5648 | 0.5648 | 0.5648 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 28.1374 | 28.1374 | 28.1374 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 6.6613 | 3.3531 | 3.3531 | 3.3531 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 64.3782 | 33.1697 | 33.1697 | 33.1697 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 6.5175 | 3.4296 | 3.4296 | 3.4296 | 0.0000 | 1.0000 |
CAV_BAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 28.1374 | 28.1374 | 28.1374 | 28.1374 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5773 | 0.5773 | 0.5773 | 0.5773 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.5529 | 5.5529 | 5.5529 | 5.5529 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5648 | 0.5648 | 0.5648 | 0.5648 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 102.33 |
Number of hours cooling loads not met | 1018.50 |
Number of hours not met | 1086.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 3062.05 | 2312548.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1304.51 | 424515.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3222.74 | 325713.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 356.53 | 40855.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 55.01 | 3454.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 2505.76 | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2839.55 | 355156.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 320.20 | 50204.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 370.38 | 82444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 2430.35 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 478.32 | 58670.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 28565.58 |
Natural Gas | 0.00 | 3062.05 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 31627.62 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 69.57 |
Space Heating | 0.00 |
Space Cooling | 28.16 |
Fans (All) | 61.30 |
Service Water Heating | 10.33 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 616.70 |
Subtotal | 616.70 |
Natural Gas [MJ/m2] | |
Space Heating | 66.11 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 66.11 |
Subtotal | 66.11 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 10.19 |
Space Heating | 9.68 |
Space Cooling | 4.12 |
Fans (All) | 8.98 |
Service Water Heating | 1.51 |
Receptacle Equipment | 46.40 |
Miscellaneous | 19.11 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8064.83 | 325.83 | 199.17 | 170.17 | 0.00 |
CORE_BOTTOM | 8744.17 | 15.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8754.50 | 5.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8732.83 | 27.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8725.67 | 34.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8680.83 | 79.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8758.33 | 1.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8730.00 | 30.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8724.83 | 35.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8728.50 | 31.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8756.83 | 3.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8732.67 | 27.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8729.50 | 30.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8724.83 | 35.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8755.00 | 5.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8758.50 | 1.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8757.83 | 2.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8610.17 | 149.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8729.67 | 30.33 | 0.00 | 0.00 | 0.00 |
Min | 8064.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 325.83 | 199.17 | 170.17 | 0.00 |
Average | 8706.02 | 37.92 | 8.66 | 7.40 | 0.00 |
Sum | 200238.50 | 872.17 | 199.17 | 170.17 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 345416.50 | 9183.67 | 4727.33 | 9288.50 | 0.00 |
CORE_BOTTOM | 330795.00 | 18.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24902.33 | 6.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24908.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24905.67 | 3.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 101929.83 | 1465.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 345416.50 | 9183.67 | 4727.33 | 9288.50 | 0.00 |
Average | 79261.30 | 464.22 | 205.54 | 403.85 | 0.00 |
Sum | 1823010.00 | 10677.17 | 4727.33 | 9288.50 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8170.17 | 233.33 | 174.50 | 154.50 | 27.50 |
CORE_BOTTOM | 8722.33 | 37.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8722.33 | 37.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8735.67 | 24.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8739.17 | 20.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8737.67 | 22.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8733.17 | 26.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8695.67 | 64.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8748.67 | 11.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8734.33 | 25.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8732.17 | 27.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8725.50 | 34.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8745.67 | 14.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8734.17 | 25.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8733.83 | 26.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8727.50 | 32.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8646.67 | 113.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8739.50 | 20.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8754.67 | 5.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8746.00 | 14.00 | 0.00 | 0.00 | 0.00 |
Min | 8170.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 233.33 | 174.50 | 154.50 | 27.50 |
Average | 8708.91 | 35.59 | 7.59 | 6.72 | 1.20 |
Sum | 200304.83 | 818.67 | 174.50 | 154.50 | 27.50 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 346033.33 | 9149.33 | 3915.00 | 6737.33 | 2781.00 |
CORE_BOTTOM | 330744.00 | 69.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330724.00 | 89.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330765.00 | 48.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24899.00 | 10.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38919.67 | 5.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24908.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38922.33 | 2.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24902.33 | 6.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 102229.33 | 1165.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 346033.33 | 9149.33 | 3915.00 | 6737.33 | 2781.00 |
Average | 79292.34 | 458.51 | 170.22 | 292.93 | 120.91 |
Sum | 1823723.83 | 10545.83 | 3915.00 | 6737.33 | 2781.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:57
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Environment
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Environment
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -8.80 |
February | -2.17 |
March | 0.301 |
April | 6.668 |
May | 10.099 |
June | 16.456 |
July | 20.571 |
August | 19.174 |
September | 14.689 |
October | 8.635 |
November | 2.839 |
December | -4.07 |
Annual Sum or Average | 7.074 |
Minimum of Months | -8.80 |
Maximum of Months | 20.571 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.412662E+11 | 118238.32 | 02-JAN-07:05 | -2.2 | -4.3 | 0.567797E+10 | 7499.12 | 17-JAN-10:09 | 4.68 | 0.96 |
February | 0.403413E+11 | 110700.36 | 21-FEB-07:11 | 6.70 | 0.52 | 0.515041E+10 | 7499.07 | 21-FEB-10:30 | 11.95 | 2.92 |
March | 0.511827E+11 | 103254.49 | 23-MAR-06:12 | 4.07 | 0.56 | 0.614915E+10 | 7499.17 | 13-MAR-09:00 | 4.07 | 0.56 |
April | 0.497753E+11 | 109607.34 | 17-APR-06:11 | 6.33 | 3.59 | 0.546757E+10 | 7499.12 | 04-APR-09:09 | 6.33 | 3.59 |
May | 0.522556E+11 | 110158.51 | 15-MAY-06:11 | 6.70 | 2.03 | 0.592330E+10 | 7499.24 | 04-MAY-13:09 | 6.70 | 2.03 |
June | 0.533686E+11 | 113271.89 | 07-JUN-06:11 | 9.07 | 6.04 | 0.621058E+10 | 10816.27 | 23-JUN-13:00 | 31.70 | 15.26 |
July | 0.418641E+11 | 125874.13 | 21-JUL-06:11 | 15.73 | 9.54 | 0.677075E+10 | 13254.66 | 20-JUL-13:00 | 15.73 | 9.54 |
August | 0.559219E+11 | 116918.59 | 14-AUG-06:11 | 12.07 | 9.96 | 0.673226E+10 | 11940.76 | 11-AUG-13:00 | 12.07 | 9.96 |
September | 0.541168E+11 | 114505.47 | 01-SEP-21:01 | 17.70 | 9.50 | 0.567458E+10 | 11643.92 | 01-SEP-13:00 | 17.70 | 9.50 |
October | 0.571685E+11 | 114287.56 | 23-OCT-06:11 | 10.00 | 4.07 | 0.569731E+10 | 7541.49 | 18-OCT-13:50 | 10.00 | 4.07 |
November | 0.528280E+11 | 109636.73 | 13-NOV-07:03 | -5.9 | -8.5 | 0.563618E+10 | 7499.28 | 16-NOV-14:09 | 10.63 | 6.46 |
December | 0.485583E+11 | 106105.36 | 26-DEC-07:03 | -8.5 | -9.6 | 0.548529E+10 | 7499.17 | 06-DEC-10:09 | -8.5 | -9.6 |
Annual Sum or Average | 0.598647E+12 | 0.705753E+11 | ||||||||
Minimum of Months | 0.403413E+11 | 103254.49 | -8.5 | -9.6 | 0.515041E+10 | 7499.07 | -8.5 | -9.6 | ||
Maximum of Months | 0.571685E+11 | 125874.13 | 17.70 | 9.96 | 0.677075E+10 | 13254.66 | 31.70 | 15.26 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.340148E+11 | 94122.77 | 02-JAN-04:01 | -0.5 | -3.0 | 0.501545E+10 | 6734.77 | 02-JAN-10:09 | 2.48 | -0.4 |
February | 0.356428E+11 | 87150.88 | 27-FEB-05:11 | 4.07 | 0.00 | 0.458254E+10 | 6734.76 | 23-FEB-10:39 | 4.07 | 0.00 |
March | 0.483816E+11 | 86493.04 | 20-MAR-04:01 | -1.1 | -3.1 | 0.549412E+10 | 6734.76 | 07-MAR-10:39 | -1.1 | -3.1 |
April | 0.522137E+11 | 92248.23 | 10-APR-04:11 | 4.23 | 0.21 | 0.488336E+10 | 6734.78 | 04-APR-09:09 | 4.23 | 0.21 |
May | 0.492607E+11 | 92895.19 | 30-MAY-04:13 | 15.60 | 10.93 | 0.528930E+10 | 6735.16 | 02-MAY-13:09 | 15.60 | 10.93 |
June | 0.606173E+11 | 96927.03 | 22-JUN-04:13 | 16.10 | 12.27 | 0.528801E+10 | 7593.78 | 22-JUN-09:00 | 25.60 | 16.64 |
July | 0.733451E+11 | 96317.23 | 05-JUL-04:11 | 9.40 | 8.79 | 0.499891E+10 | 7587.51 | 18-JUL-09:30 | 28.90 | 15.77 |
August | 0.745653E+11 | 91737.60 | 22-AUG-04:13 | 13.30 | 9.89 | 0.555812E+10 | 7661.41 | 07-AUG-13:00 | 13.30 | 9.89 |
September | 0.533912E+11 | 95401.75 | 01-SEP-04:13 | 17.20 | 10.88 | 0.489201E+10 | 7114.31 | 01-SEP-13:00 | 27.80 | 14.52 |
October | 0.498539E+11 | 90590.19 | 02-OCT-04:12 | 4.80 | 2.84 | 0.507977E+10 | 6734.80 | 18-OCT-13:00 | 25.00 | 11.40 |
November | 0.458772E+11 | 88282.83 | 06-NOV-04:03 | -2.8 | -3.9 | 0.502771E+10 | 6734.75 | 03-NOV-09:09 | -2.8 | -3.9 |
December | 0.423511E+11 | 86471.61 | 07-DEC-05:01 | -1.6 | -2.7 | 0.489182E+10 | 6734.81 | 07-DEC-10:20 | 3.90 | 1.50 |
Annual Sum or Average | 0.619515E+12 | 0.610011E+11 | ||||||||
Minimum of Months | 0.340148E+11 | 86471.61 | -2.8 | -3.9 | 0.458254E+10 | 6734.75 | -2.8 | -3.9 | ||
Maximum of Months | 0.745653E+11 | 96927.03 | 17.20 | 12.27 | 0.555812E+10 | 7661.41 | 28.90 | 16.64 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.228082E+11 | 21475.77 | 19-JAN-16:57 | -6.7 | -8.2 | 0.454162E+10 | 6734.49 | 04-JAN-14:00 | -6.7 | -8.2 |
February | 0.234068E+11 | 51402.80 | 28-FEB-06:02 | -3.9 | -4.3 | 0.430872E+10 | 6734.76 | 23-FEB-10:39 | -3.9 | -4.3 |
March | 0.312853E+11 | 72136.04 | 30-MAR-05:02 | 0.00 | -2.1 | 0.534174E+10 | 6734.75 | 01-MAR-10:09 | 0.00 | -2.1 |
April | 0.332363E+11 | 78615.59 | 26-APR-05:02 | 5.37 | 2.97 | 0.483228E+10 | 6734.75 | 04-APR-09:09 | 5.37 | 2.97 |
May | 0.376030E+11 | 79486.97 | 30-MAY-04:12 | 15.60 | 10.93 | 0.525829E+10 | 6735.18 | 02-MAY-13:09 | 15.60 | 10.93 |
June | 0.459860E+11 | 82453.74 | 22-JUN-04:12 | 16.10 | 12.27 | 0.526981E+10 | 7257.05 | 20-JUN-13:09 | 16.10 | 12.27 |
July | 0.479610E+11 | 82483.42 | 27-JUL-04:12 | 14.23 | 9.88 | 0.490916E+10 | 7257.46 | 14-JUL-09:00 | 14.23 | 9.88 |
August | 0.498545E+11 | 81926.28 | 14-AUG-04:12 | 12.20 | 9.88 | 0.550599E+10 | 7081.32 | 07-AUG-13:00 | 12.20 | 9.88 |
September | 0.403754E+11 | 82980.13 | 11-SEP-04:12 | 11.10 | 10.17 | 0.486561E+10 | 6738.28 | 01-SEP-13:00 | 11.10 | 10.17 |
October | 0.341791E+11 | 78468.44 | 20-OCT-05:02 | 2.70 | 0.86 | 0.503346E+10 | 6734.76 | 18-OCT-13:30 | 2.70 | 0.86 |
November | 0.280395E+11 | 72229.41 | 04-NOV-05:02 | 9.43 | 5.60 | 0.487502E+10 | 6734.75 | 03-NOV-09:09 | 9.43 | 5.60 |
December | 0.243803E+11 | 28974.57 | 07-DEC-16:20 | 5.93 | 1.89 | 0.458804E+10 | 6734.80 | 07-DEC-10:20 | 5.93 | 1.89 |
Annual Sum or Average | 0.419116E+12 | 0.593297E+11 | ||||||||
Minimum of Months | 0.228082E+11 | 21475.77 | -6.7 | -8.2 | 0.430872E+10 | 6734.49 | -6.7 | -8.2 | ||
Maximum of Months | 0.498545E+11 | 82980.13 | 16.10 | 12.27 | 0.550599E+10 | 7257.46 | 16.10 | 12.27 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.135426E+11 | 17323.75 | 13-JAN-17:00 | 7.80 | 3.93 | 0.396336E+10 | 6225.18 | 13-JAN-14:00 | 7.80 | 3.93 |
February | 0.159259E+11 | 24549.51 | 28-FEB-17:00 | 10.00 | 4.31 | 0.382540E+10 | 6588.88 | 28-FEB-14:00 | 10.00 | 4.31 |
March | 0.226295E+11 | 29240.02 | 29-MAR-16:00 | 12.20 | 4.07 | 0.486609E+10 | 6734.56 | 15-MAR-13:00 | 12.20 | 4.07 |
April | 0.262577E+11 | 41015.57 | 25-APR-16:00 | 17.80 | 7.70 | 0.458764E+10 | 6734.70 | 25-APR-09:09 | 17.80 | 7.70 |
May | 0.327831E+11 | 74909.64 | 20-MAY-05:02 | 11.47 | 8.41 | 0.507280E+10 | 6735.17 | 02-MAY-13:09 | 11.47 | 8.41 |
June | 0.450951E+11 | 80326.48 | 21-JUN-04:12 | 17.40 | 12.31 | 0.524882E+10 | 7410.26 | 20-JUN-13:09 | 17.40 | 12.31 |
July | 0.490850E+11 | 79215.78 | 27-JUL-04:12 | 14.23 | 9.88 | 0.491257E+10 | 7479.12 | 25-JUL-13:00 | 14.23 | 9.88 |
August | 0.485908E+11 | 79396.37 | 08-AUG-04:12 | 17.97 | 11.68 | 0.550076E+10 | 7415.44 | 07-AUG-13:00 | 17.97 | 11.68 |
September | 0.355845E+11 | 77503.39 | 08-SEP-05:02 | 14.40 | 11.72 | 0.475943E+10 | 6772.85 | 01-SEP-13:00 | 14.40 | 11.72 |
October | 0.257056E+11 | 38730.56 | 18-OCT-16:00 | 24.40 | 11.02 | 0.474009E+10 | 6734.67 | 20-OCT-09:20 | 8.17 | 4.16 |
November | 0.195337E+11 | 26477.80 | 03-NOV-16:00 | 14.30 | 7.69 | 0.434799E+10 | 6734.57 | 09-NOV-14:39 | 9.13 | 3.92 |
December | 0.155718E+11 | 19015.40 | 06-DEC-17:00 | 6.70 | 2.38 | 0.397880E+10 | 6647.26 | 07-DEC-14:00 | 8.30 | 2.55 |
Annual Sum or Average | 0.350305E+12 | 0.558038E+11 | ||||||||
Minimum of Months | 0.135426E+11 | 17323.75 | 6.70 | 2.38 | 0.382540E+10 | 6225.18 | 7.80 | 2.55 | ||
Maximum of Months | 0.490850E+11 | 80326.48 | 24.40 | 12.31 | 0.550076E+10 | 7479.12 | 17.97 | 12.31 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.136572E+10 | 2853.10 | 01-JAN-13:42 | 8.22 | 3.01 | 0.505403E+09 | 845.60 | 02-JAN-14:09 | 6.60 | 1.51 |
February | 0.206292E+10 | 4487.75 | 27-FEB-16:00 | 18.90 | 7.06 | 0.493404E+09 | 845.60 | 21-FEB-14:00 | 18.90 | 7.06 |
March | 0.343872E+10 | 5208.20 | 27-MAR-14:00 | 8.90 | 2.28 | 0.643832E+09 | 845.62 | 14-MAR-09:00 | 8.90 | 2.28 |
April | 0.476140E+10 | 7602.46 | 07-APR-14:00 | 23.30 | 9.68 | 0.597616E+09 | 845.62 | 13-APR-13:00 | 13.30 | 7.60 |
May | 0.571116E+10 | 12494.25 | 30-MAY-04:12 | 15.60 | 10.93 | 0.652334E+09 | 845.68 | 02-MAY-13:09 | 15.60 | 10.93 |
June | 0.925378E+10 | 13713.51 | 26-JUN-04:12 | 12.73 | 10.54 | 0.663676E+09 | 959.45 | 22-JUN-09:00 | 12.73 | 10.54 |
July | 0.115458E+11 | 16784.88 | 23-JUL-18:01 | 22.80 | 13.09 | 0.632864E+09 | 988.00 | 25-JUL-13:00 | 33.90 | 15.43 |
August | 0.105552E+11 | 16634.09 | 06-AUG-16:01 | 35.50 | 16.24 | 0.698604E+09 | 987.58 | 07-AUG-13:00 | 32.80 | 15.97 |
September | 0.603048E+10 | 15941.67 | 04-SEP-15:41 | 32.70 | 16.52 | 0.606327E+09 | 880.68 | 01-SEP-13:00 | 32.70 | 16.52 |
October | 0.413960E+10 | 6201.71 | 19-OCT-14:30 | 21.40 | 10.24 | 0.617981E+09 | 845.63 | 18-OCT-13:00 | 21.40 | 10.24 |
November | 0.300726E+10 | 4410.18 | 24-NOV-14:30 | 14.90 | 6.43 | 0.579538E+09 | 845.62 | 16-NOV-14:09 | 14.90 | 6.43 |
December | 0.215298E+10 | 3008.27 | 06-DEC-13:30 | 12.25 | 6.08 | 0.526913E+09 | 845.60 | 05-DEC-14:09 | 12.25 | 6.08 |
Annual Sum or Average | 0.640249E+11 | 0.721849E+10 | ||||||||
Minimum of Months | 0.136572E+10 | 2853.10 | 8.22 | 2.28 | 0.493404E+09 | 845.60 | 6.60 | 1.51 | ||
Maximum of Months | 0.115458E+11 | 16784.88 | 35.50 | 16.52 | 0.698604E+09 | 988.00 | 33.90 | 16.52 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.160322E+10 | 4009.12 | 17-JAN-10:05 | 4.68 | 0.96 | 0.324079E+09 | 544.95 | 31-JAN-10:39 | -5.7 | -8.4 |
February | 0.258601E+10 | 12752.05 | 26-FEB-10:13 | 10.57 | 3.57 | 0.317464E+09 | 544.95 | 23-FEB-10:39 | 10.57 | 3.57 |
March | 0.431552E+10 | 12089.24 | 28-MAR-09:15 | 5.73 | 0.86 | 0.404112E+09 | 544.96 | 06-MAR-10:09 | 5.73 | 0.86 |
April | 0.583659E+10 | 21474.07 | 16-APR-08:42 | 11.83 | 5.16 | 0.373133E+09 | 545.08 | 24-APR-09:09 | 12.15 | 7.86 |
May | 0.691984E+10 | 14720.70 | 19-MAY-08:30 | 16.95 | 11.09 | 0.414971E+09 | 545.86 | 19-MAY-09:09 | 18.17 | 11.56 |
June | 0.100812E+11 | 26886.40 | 11-JUN-09:01 | 19.37 | 11.25 | 0.425557E+09 | 680.02 | 22-JUN-09:00 | 25.60 | 16.64 |
July | 0.127472E+11 | 27314.86 | 09-JUL-09:51 | 22.80 | 11.96 | 0.403178E+09 | 698.08 | 14-JUL-09:50 | 27.33 | 16.38 |
August | 0.114219E+11 | 26516.25 | 06-AUG-08:41 | 26.55 | 14.17 | 0.447136E+09 | 658.43 | 07-AUG-09:39 | 29.67 | 15.17 |
September | 0.699194E+10 | 25127.89 | 24-SEP-09:52 | 18.30 | 11.96 | 0.386947E+09 | 555.28 | 01-SEP-10:09 | 18.30 | 11.96 |
October | 0.482760E+10 | 13499.39 | 22-OCT-10:22 | 15.00 | 7.29 | 0.391862E+09 | 544.96 | 18-OCT-13:50 | 15.00 | 7.29 |
November | 0.323170E+10 | 7711.68 | 06-NOV-09:25 | 0.80 | -1.3 | 0.357911E+09 | 544.95 | 03-NOV-09:09 | 0.80 | -1.3 |
December | 0.210401E+10 | 3775.48 | 20-DEC-10:10 | 3.48 | -0.5 | 0.323450E+09 | 544.95 | 07-DEC-10:39 | 3.48 | -0.5 |
Annual Sum or Average | 0.726667E+11 | 0.456980E+10 | ||||||||
Minimum of Months | 0.160322E+10 | 3775.48 | 0.80 | -1.3 | 0.317464E+09 | 544.95 | -5.7 | -8.4 | ||
Maximum of Months | 0.127472E+11 | 27314.86 | 26.55 | 14.17 | 0.447136E+09 | 698.08 | 29.67 | 16.64 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.429593E+10 | 29216.44 | 01-JAN-13:42 | 8.22 | 3.01 | 0.539283E+09 | 845.64 | 13-JAN-14:50 | 9.63 | 4.92 |
February | 0.694591E+10 | 35467.99 | 26-FEB-14:11 | 15.97 | 6.00 | 0.529327E+09 | 849.68 | 27-FEB-14:09 | 18.40 | 7.06 |
March | 0.910642E+10 | 29503.80 | 26-MAR-13:32 | 9.63 | 1.94 | 0.642138E+09 | 865.27 | 01-MAR-14:09 | 9.63 | 1.94 |
April | 0.917990E+10 | 29630.69 | 16-APR-14:02 | 19.40 | 8.41 | 0.582843E+09 | 846.54 | 24-APR-13:00 | 17.80 | 9.82 |
May | 0.916666E+10 | 28202.82 | 29-MAY-13:42 | 23.30 | 12.18 | 0.636958E+09 | 846.49 | 19-MAY-13:50 | 23.30 | 12.18 |
June | 0.121195E+11 | 29539.44 | 11-JUN-13:02 | 25.82 | 13.32 | 0.659696E+09 | 1004.57 | 20-JUN-13:09 | 27.48 | 18.05 |
July | 0.158957E+11 | 30680.08 | 09-JUL-13:12 | 26.87 | 12.73 | 0.630916E+09 | 1047.69 | 25-JUL-13:50 | 33.90 | 15.43 |
August | 0.171915E+11 | 30686.12 | 06-AUG-13:22 | 34.15 | 15.08 | 0.711749E+09 | 1132.55 | 07-AUG-13:50 | 32.80 | 15.88 |
September | 0.131723E+11 | 32636.68 | 03-SEP-12:51 | 33.30 | 15.94 | 0.607931E+09 | 1090.42 | 01-SEP-13:50 | 33.30 | 15.94 |
October | 0.113635E+11 | 32455.20 | 15-OCT-13:21 | 22.75 | 10.91 | 0.618662E+09 | 1033.07 | 18-OCT-13:50 | 24.90 | 11.31 |
November | 0.809943E+10 | 29634.84 | 12-NOV-12:42 | -2.0 | -4.6 | 0.589663E+09 | 863.87 | 03-NOV-13:20 | -2.0 | -4.6 |
December | 0.558828E+10 | 27148.58 | 17-DEC-13:13 | -1.5 | -4.1 | 0.548775E+09 | 845.64 | 07-DEC-10:20 | -1.5 | -4.1 |
Annual Sum or Average | 0.122125E+12 | 0.729794E+10 | ||||||||
Minimum of Months | 0.429593E+10 | 27148.58 | -2.0 | -4.6 | 0.529327E+09 | 845.64 | -2.0 | -4.6 | ||
Maximum of Months | 0.171915E+11 | 35467.99 | 34.15 | 15.94 | 0.711749E+09 | 1132.55 | 33.90 | 18.05 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.245645E+10 | 6350.76 | 13-JAN-15:30 | 9.45 | 4.93 | 0.326631E+09 | 544.94 | 13-JAN-14:00 | 9.45 | 4.93 |
February | 0.422780E+10 | 26912.88 | 26-FEB-15:31 | 16.30 | 6.32 | 0.329655E+09 | 544.94 | 23-FEB-14:00 | 16.30 | 6.32 |
March | 0.672150E+10 | 19707.27 | 12-MAR-15:42 | 6.02 | -0.7 | 0.425595E+09 | 544.95 | 21-MAR-13:50 | 2.25 | 0.50 |
April | 0.920984E+10 | 32441.09 | 16-APR-17:21 | 19.70 | 8.86 | 0.392842E+09 | 544.96 | 13-APR-13:00 | 19.70 | 8.86 |
May | 0.882416E+10 | 31214.34 | 28-MAY-16:51 | 21.10 | 10.41 | 0.415937E+09 | 544.99 | 02-MAY-13:09 | 21.10 | 10.41 |
June | 0.122619E+11 | 31508.50 | 18-JUN-17:11 | 25.40 | 14.50 | 0.427225E+09 | 601.54 | 30-JUN-15:00 | 31.10 | 14.62 |
July | 0.154036E+11 | 36206.09 | 09-JUL-17:11 | 28.13 | 13.04 | 0.403232E+09 | 648.67 | 25-JUL-15:00 | 33.90 | 15.43 |
August | 0.157141E+11 | 32416.80 | 06-AUG-16:41 | 35.10 | 15.80 | 0.450433E+09 | 648.60 | 07-AUG-15:00 | 32.20 | 16.16 |
September | 0.851139E+10 | 30286.75 | 03-SEP-15:31 | 33.67 | 16.05 | 0.387307E+09 | 587.97 | 01-SEP-15:00 | 33.67 | 16.05 |
October | 0.686991E+10 | 29514.48 | 15-OCT-15:21 | 22.50 | 10.93 | 0.399313E+09 | 544.97 | 18-OCT-13:50 | 24.90 | 11.31 |
November | 0.562059E+10 | 13232.11 | 12-NOV-16:03 | -0.8 | -3.9 | 0.385474E+09 | 544.96 | 16-NOV-14:09 | 10.63 | 6.46 |
December | 0.463585E+10 | 10166.02 | 06-DEC-15:30 | 10.25 | 4.94 | 0.363509E+09 | 544.95 | 19-DEC-14:09 | 10.97 | 6.81 |
Annual Sum or Average | 0.100457E+12 | 0.470715E+10 | ||||||||
Minimum of Months | 0.245645E+10 | 6350.76 | -0.8 | -3.9 | 0.326631E+09 | 544.94 | 2.25 | 0.50 | ||
Maximum of Months | 0.157141E+11 | 36206.09 | 35.10 | 16.05 | 0.450433E+09 | 648.67 | 33.90 | 16.16 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.205399E+09 | 1543.24 | 13-JAN-16:50 | 7.98 | 4.06 | 0.464491E+09 | 647.63 | 13-JAN-14:00 | 7.98 | 4.06 |
February | 0.758497E+09 | 2634.59 | 27-FEB-14:20 | 18.50 | 7.10 | 0.435975E+09 | 770.12 | 27-FEB-16:30 | 15.55 | 6.44 |
March | 0.179485E+10 | 2742.07 | 23-MAR-13:45 | 9.90 | 2.40 | 0.557143E+09 | 842.75 | 29-MAR-13:00 | 12.80 | 4.50 |
April | 0.265911E+10 | 5878.10 | 07-APR-14:30 | 22.50 | 9.29 | 0.545523E+09 | 845.61 | 13-APR-13:00 | 13.30 | 7.60 |
May | 0.418061E+10 | 7704.78 | 19-MAY-16:00 | 27.80 | 14.54 | 0.619963E+09 | 845.68 | 02-MAY-13:09 | 27.80 | 14.54 |
June | 0.726764E+10 | 12255.41 | 21-JUN-05:03 | 15.87 | 11.84 | 0.657607E+09 | 925.29 | 20-JUN-13:09 | 15.87 | 11.84 |
July | 0.837229E+10 | 15588.52 | 02-JUL-18:21 | 24.75 | 14.30 | 0.619148E+09 | 967.69 | 25-JUL-13:00 | 33.90 | 15.43 |
August | 0.728133E+10 | 15175.94 | 06-AUG-15:51 | 35.60 | 16.36 | 0.687914E+09 | 935.78 | 07-AUG-13:00 | 32.80 | 15.97 |
September | 0.437457E+10 | 15392.83 | 04-SEP-11:31 | 31.27 | 15.72 | 0.582241E+09 | 846.14 | 01-SEP-13:00 | 31.27 | 15.72 |
October | 0.259035E+10 | 4735.41 | 19-OCT-14:30 | 21.40 | 10.24 | 0.561724E+09 | 845.62 | 18-OCT-13:30 | 21.40 | 10.24 |
November | 0.138018E+10 | 2607.30 | 03-NOV-14:20 | 14.87 | 7.79 | 0.497769E+09 | 814.98 | 08-NOV-14:30 | 13.55 | 7.81 |
December | 0.473661E+09 | 1768.32 | 06-DEC-16:00 | 9.40 | 4.51 | 0.454494E+09 | 712.71 | 06-DEC-14:00 | 9.40 | 4.51 |
Annual Sum or Average | 0.413385E+11 | 0.668399E+10 | ||||||||
Minimum of Months | 0.205399E+09 | 1543.24 | 7.98 | 2.40 | 0.435975E+09 | 647.63 | 7.98 | 4.06 | ||
Maximum of Months | 0.837229E+10 | 15588.52 | 35.60 | 16.36 | 0.687914E+09 | 967.69 | 33.90 | 15.97 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.478970E+09 | 2713.12 | 15-JAN-13:12 | 5.20 | -0.5 | 0.221062E+09 | 441.18 | 20-JAN-09:00 | -3.3 | -5.9 |
February | 0.145468E+10 | 6329.94 | 28-FEB-10:00 | 1.10 | -0.5 | 0.213127E+09 | 521.20 | 28-FEB-11:20 | 4.83 | 1.71 |
March | 0.299906E+10 | 10323.02 | 23-MAR-10:10 | 8.40 | 1.62 | 0.271356E+09 | 521.21 | 22-MAR-10:09 | 8.40 | 1.62 |
April | 0.471454E+10 | 19490.53 | 16-APR-09:22 | 13.60 | 5.94 | 0.259945E+09 | 521.21 | 13-APR-14:09 | 13.60 | 5.94 |
May | 0.626319E+10 | 15565.24 | 19-MAY-08:50 | 17.52 | 11.29 | 0.294387E+09 | 521.56 | 19-MAY-08:39 | 17.52 | 11.29 |
June | 0.973066E+10 | 30409.40 | 25-JUN-08:31 | 16.33 | 11.66 | 0.309575E+09 | 637.70 | 22-JUN-10:20 | 16.33 | 11.66 |
July | 0.115393E+11 | 32181.81 | 02-JUL-09:01 | 22.48 | 15.33 | 0.293274E+09 | 668.13 | 14-JUL-10:09 | 27.98 | 16.36 |
August | 0.103246E+11 | 32358.47 | 06-AUG-09:11 | 28.13 | 14.48 | 0.324420E+09 | 628.58 | 07-AUG-10:20 | 30.60 | 15.25 |
September | 0.627350E+10 | 28670.20 | 04-SEP-08:51 | 26.70 | 14.88 | 0.274102E+09 | 532.26 | 01-SEP-10:50 | 26.70 | 14.88 |
October | 0.379391E+10 | 9718.22 | 18-OCT-10:10 | 20.28 | 8.90 | 0.268275E+09 | 521.21 | 19-OCT-10:09 | 19.18 | 9.33 |
November | 0.189882E+10 | 5584.20 | 03-NOV-10:10 | 9.10 | 5.57 | 0.236336E+09 | 521.20 | 03-NOV-10:20 | 9.50 | 5.81 |
December | 0.732447E+09 | 2549.82 | 20-DEC-10:00 | 3.30 | -0.6 | 0.214537E+09 | 450.46 | 20-DEC-09:00 | 3.30 | -0.6 |
Annual Sum or Average | 0.602036E+11 | 0.318040E+10 | ||||||||
Minimum of Months | 0.478970E+09 | 2549.82 | 1.10 | -0.6 | 0.213127E+09 | 441.18 | -3.3 | -5.9 | ||
Maximum of Months | 0.115393E+11 | 32358.47 | 28.13 | 15.33 | 0.324420E+09 | 668.13 | 30.60 | 16.36 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.337306E+10 | 29596.98 | 15-JAN-13:12 | 5.20 | -0.5 | 0.520527E+09 | 845.64 | 19-JAN-14:20 | -5.4 | -7.3 |
February | 0.632706E+10 | 37623.58 | 26-FEB-14:11 | 15.97 | 6.00 | 0.513543E+09 | 884.45 | 28-FEB-14:09 | 10.10 | 4.57 |
March | 0.806703E+10 | 30931.70 | 26-MAR-13:12 | 9.27 | 1.72 | 0.613825E+09 | 903.83 | 01-MAR-14:09 | 9.27 | 1.72 |
April | 0.773768E+10 | 30711.07 | 16-APR-14:02 | 19.40 | 8.41 | 0.556730E+09 | 846.17 | 24-APR-13:00 | 17.80 | 9.82 |
May | 0.839546E+10 | 30380.55 | 14-MAY-13:02 | 15.78 | 6.63 | 0.619522E+09 | 846.28 | 19-MAY-13:00 | 27.20 | 15.02 |
June | 0.108722E+11 | 29953.77 | 11-JUN-13:12 | 25.53 | 13.23 | 0.650479E+09 | 996.16 | 20-JUN-13:09 | 27.48 | 18.05 |
July | 0.133759E+11 | 31494.80 | 02-JUL-13:41 | 24.68 | 14.07 | 0.620458E+09 | 1050.59 | 25-JUL-13:00 | 33.90 | 15.43 |
August | 0.151649E+11 | 32357.28 | 06-AUG-10:31 | 30.40 | 14.95 | 0.696366E+09 | 1129.10 | 07-AUG-13:00 | 32.80 | 15.97 |
September | 0.130171E+11 | 37454.04 | 03-SEP-12:41 | 33.22 | 15.94 | 0.594417E+09 | 1058.46 | 01-SEP-13:00 | 33.22 | 15.94 |
October | 0.109433E+11 | 34122.01 | 15-OCT-13:21 | 22.75 | 10.91 | 0.604844E+09 | 1024.27 | 18-OCT-13:50 | 24.90 | 11.31 |
November | 0.697512E+10 | 32643.10 | 12-NOV-11:51 | -3.3 | -5.4 | 0.568257E+09 | 886.18 | 03-NOV-13:39 | -3.3 | -5.4 |
December | 0.402299E+10 | 17771.31 | 12-DEC-12:40 | -2.8 | -5.7 | 0.522372E+09 | 845.64 | 07-DEC-10:39 | -2.8 | -5.7 |
Annual Sum or Average | 0.108272E+12 | 0.708134E+10 | ||||||||
Minimum of Months | 0.337306E+10 | 17771.31 | -3.3 | -5.7 | 0.513543E+09 | 845.64 | -5.4 | -7.3 | ||
Maximum of Months | 0.151649E+11 | 37623.58 | 33.22 | 15.94 | 0.696366E+09 | 1129.10 | 33.90 | 18.05 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.613728E+09 | 3241.40 | 13-JAN-15:50 | 9.08 | 4.76 | 0.304586E+09 | 517.06 | 13-JAN-15:00 | 8.90 | 4.67 |
February | 0.175197E+10 | 13373.08 | 26-FEB-16:52 | 15.60 | 5.90 | 0.289552E+09 | 544.88 | 28-FEB-14:00 | 10.60 | 4.78 |
March | 0.325479E+10 | 12471.05 | 28-MAR-17:00 | 10.60 | 2.97 | 0.357764E+09 | 544.93 | 02-MAR-14:20 | 10.60 | 2.97 |
April | 0.491115E+10 | 29397.26 | 16-APR-17:21 | 19.70 | 8.86 | 0.340886E+09 | 544.94 | 13-APR-13:00 | 19.70 | 8.86 |
May | 0.686668E+10 | 31150.55 | 14-MAY-17:01 | 14.13 | 5.05 | 0.386833E+09 | 544.96 | 25-MAY-13:09 | 17.20 | 8.78 |
June | 0.930817E+10 | 30116.83 | 25-JUN-18:31 | 22.23 | 13.99 | 0.414804E+09 | 603.44 | 30-JUN-15:00 | 31.10 | 14.62 |
July | 0.108244E+11 | 34147.28 | 02-JUL-18:21 | 24.75 | 14.30 | 0.395474E+09 | 641.08 | 25-JUL-15:00 | 33.90 | 15.43 |
August | 0.986529E+10 | 32423.62 | 06-AUG-16:31 | 35.20 | 15.91 | 0.436352E+09 | 627.60 | 07-AUG-15:00 | 32.20 | 16.16 |
September | 0.659782E+10 | 32428.96 | 04-SEP-16:51 | 32.80 | 16.77 | 0.361819E+09 | 575.97 | 01-SEP-15:00 | 32.80 | 16.77 |
October | 0.426760E+10 | 23128.63 | 15-OCT-16:42 | 21.28 | 10.50 | 0.351381E+09 | 544.95 | 18-OCT-13:00 | 25.00 | 11.40 |
November | 0.236564E+10 | 7432.21 | 03-NOV-15:40 | 14.40 | 7.69 | 0.326472E+09 | 544.93 | 09-NOV-14:00 | 9.00 | 3.82 |
December | 0.103765E+10 | 4680.70 | 06-DEC-15:40 | 9.97 | 4.80 | 0.299564E+09 | 538.96 | 06-DEC-14:00 | 9.97 | 4.80 |
Annual Sum or Average | 0.616649E+11 | 0.426549E+10 | ||||||||
Minimum of Months | 0.613728E+09 | 3241.40 | 9.08 | 2.97 | 0.289552E+09 | 517.06 | 8.90 | 2.97 | ||
Maximum of Months | 0.108244E+11 | 34147.28 | 35.20 | 16.77 | 0.436352E+09 | 641.08 | 33.90 | 16.77 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 49344537.74 | 1504.87 | 13-JAN-16:50 | 7.98 | 4.06 | 0.459553E+09 | 626.03 | 26-JAN-10:30 | -21.9 | -22.6 |
February | 0.362380E+09 | 2424.44 | 27-FEB-13:30 | 17.75 | 6.76 | 0.424948E+09 | 729.26 | 27-FEB-16:30 | 15.55 | 6.44 |
March | 0.111740E+10 | 2623.05 | 23-MAR-13:30 | 9.70 | 2.18 | 0.528894E+09 | 795.36 | 29-MAR-13:00 | 12.80 | 4.50 |
April | 0.205119E+10 | 5736.30 | 07-APR-14:30 | 22.50 | 9.29 | 0.512774E+09 | 845.61 | 13-APR-13:00 | 13.30 | 7.60 |
May | 0.372102E+10 | 8461.21 | 19-MAY-16:00 | 27.80 | 14.54 | 0.594318E+09 | 845.63 | 19-MAY-13:09 | 27.80 | 14.54 |
June | 0.716122E+10 | 13619.69 | 25-JUN-18:41 | 21.97 | 13.95 | 0.649261E+09 | 917.92 | 20-JUN-13:09 | 21.97 | 13.95 |
July | 0.855064E+10 | 18005.80 | 02-JUL-18:21 | 24.75 | 14.30 | 0.616466E+09 | 964.02 | 25-JUL-13:00 | 33.90 | 15.43 |
August | 0.723288E+10 | 17273.25 | 06-AUG-17:21 | 34.15 | 15.38 | 0.678810E+09 | 936.49 | 07-AUG-13:00 | 32.80 | 15.97 |
September | 0.396900E+10 | 17561.37 | 04-SEP-11:31 | 31.27 | 15.72 | 0.559688E+09 | 845.66 | 07-SEP-09:00 | 16.70 | 15.61 |
October | 0.185645E+10 | 4263.23 | 19-OCT-14:40 | 21.50 | 10.24 | 0.524755E+09 | 845.61 | 18-OCT-13:00 | 21.50 | 10.24 |
November | 0.715738E+09 | 2369.60 | 03-NOV-13:30 | 14.35 | 7.74 | 0.473437E+09 | 756.68 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 0.175888E+09 | 1662.38 | 06-DEC-16:20 | 8.50 | 3.80 | 0.447570E+09 | 667.17 | 06-DEC-14:00 | 8.50 | 3.80 |
Annual Sum or Average | 0.369632E+11 | 0.647047E+10 | ||||||||
Minimum of Months | 49344537.74 | 1504.87 | 7.98 | 2.18 | 0.424948E+09 | 626.03 | -21.9 | -22.6 | ||
Maximum of Months | 0.855064E+10 | 18005.80 | 34.15 | 15.72 | 0.678810E+09 | 964.02 | 33.90 | 15.97 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.217278E+09 | 2239.61 | 31-JAN-10:35 | -5.7 | -8.4 | 0.299454E+09 | 437.91 | 31-JAN-10:39 | -5.7 | -8.4 |
February | 0.978325E+09 | 4198.29 | 28-FEB-10:20 | 2.03 | 0.11 | 0.283325E+09 | 544.95 | 28-FEB-10:09 | 2.03 | 0.11 |
March | 0.223432E+10 | 8856.42 | 23-MAR-10:10 | 8.40 | 1.62 | 0.362226E+09 | 544.95 | 22-MAR-09:50 | 8.40 | 1.62 |
April | 0.392754E+10 | 16371.36 | 16-APR-10:23 | 15.55 | 6.66 | 0.346804E+09 | 544.96 | 25-APR-09:09 | 9.87 | 4.86 |
May | 0.573955E+10 | 15128.94 | 19-MAY-08:50 | 17.52 | 11.29 | 0.396638E+09 | 544.99 | 02-MAY-13:09 | 17.52 | 11.29 |
June | 0.962898E+10 | 30102.75 | 25-JUN-08:41 | 16.52 | 11.73 | 0.420145E+09 | 661.66 | 22-JUN-09:00 | 16.52 | 11.73 |
July | 0.117161E+11 | 32058.34 | 02-JUL-09:01 | 22.48 | 15.33 | 0.396970E+09 | 700.18 | 14-JUL-09:00 | 27.80 | 16.34 |
August | 0.103113E+11 | 29082.62 | 06-AUG-09:21 | 28.60 | 14.63 | 0.439988E+09 | 640.33 | 07-AUG-09:50 | 30.13 | 15.30 |
September | 0.580156E+10 | 28775.82 | 04-SEP-08:51 | 26.70 | 14.88 | 0.367703E+09 | 544.97 | 14-SEP-13:00 | 21.70 | 13.42 |
October | 0.297212E+10 | 8934.08 | 18-OCT-09:40 | 19.07 | 8.41 | 0.355338E+09 | 544.95 | 27-OCT-09:39 | 9.07 | 4.22 |
November | 0.122030E+10 | 3778.73 | 03-NOV-10:00 | 8.70 | 5.33 | 0.309592E+09 | 544.94 | 03-NOV-09:00 | 8.70 | 5.33 |
December | 0.352116E+09 | 2304.69 | 20-DEC-10:30 | 3.85 | -0.4 | 0.289436E+09 | 445.27 | 20-DEC-10:39 | 4.03 | -0.3 |
Annual Sum or Average | 0.550995E+11 | 0.426762E+10 | ||||||||
Minimum of Months | 0.217278E+09 | 2239.61 | -5.7 | -8.4 | 0.283325E+09 | 437.91 | -5.7 | -8.4 | ||
Maximum of Months | 0.117161E+11 | 32058.34 | 28.60 | 15.33 | 0.439988E+09 | 700.18 | 30.13 | 16.34 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.238045E+10 | 26909.50 | 15-JAN-13:41 | 5.50 | -0.5 | 0.505678E+09 | 845.64 | 13-JAN-14:30 | 5.50 | -0.5 |
February | 0.493676E+10 | 34550.51 | 26-FEB-14:21 | 16.15 | 6.12 | 0.496817E+09 | 845.67 | 27-FEB-14:00 | 18.90 | 7.23 |
March | 0.665844E+10 | 32443.95 | 26-MAR-14:02 | 10.00 | 2.16 | 0.589738E+09 | 847.47 | 01-MAR-14:09 | 10.00 | 2.16 |
April | 0.656788E+10 | 29028.46 | 16-APR-13:42 | 19.22 | 8.29 | 0.535208E+09 | 846.24 | 24-APR-13:00 | 17.80 | 9.82 |
May | 0.775453E+10 | 31782.27 | 14-MAY-13:02 | 15.78 | 6.63 | 0.600992E+09 | 846.43 | 19-MAY-13:50 | 27.02 | 15.00 |
June | 0.107884E+11 | 31823.40 | 25-JUN-13:22 | 23.60 | 13.28 | 0.640141E+09 | 981.69 | 20-JUN-13:09 | 23.60 | 13.28 |
July | 0.136367E+11 | 33570.50 | 02-JUL-13:41 | 24.68 | 14.07 | 0.615502E+09 | 1040.70 | 25-JUL-13:00 | 33.90 | 15.43 |
August | 0.151527E+11 | 33864.10 | 06-AUG-13:22 | 34.15 | 15.08 | 0.686676E+09 | 1116.48 | 07-AUG-13:00 | 32.80 | 15.97 |
September | 0.123346E+11 | 39940.18 | 03-SEP-12:41 | 33.22 | 15.94 | 0.576699E+09 | 1048.05 | 01-SEP-13:00 | 33.22 | 15.94 |
October | 0.929538E+10 | 35314.85 | 15-OCT-13:21 | 22.75 | 10.91 | 0.582333E+09 | 964.45 | 18-OCT-13:50 | 24.90 | 11.31 |
November | 0.533573E+10 | 31559.64 | 11-NOV-13:41 | -0.3 | -3.0 | 0.545258E+09 | 845.67 | 09-NOV-14:20 | -0.3 | -3.0 |
December | 0.291260E+10 | 14530.75 | 12-DEC-14:30 | -2.2 | -5.4 | 0.501338E+09 | 845.64 | 19-DEC-14:09 | 10.97 | 6.81 |
Annual Sum or Average | 0.977542E+11 | 0.687638E+10 | ||||||||
Minimum of Months | 0.238045E+10 | 14530.75 | -2.2 | -5.4 | 0.496817E+09 | 845.64 | -0.3 | -3.0 | ||
Maximum of Months | 0.151527E+11 | 39940.18 | 34.15 | 15.94 | 0.686676E+09 | 1116.48 | 33.90 | 15.97 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.373359E+09 | 3270.47 | 13-JAN-15:50 | 9.08 | 4.76 | 0.301807E+09 | 501.68 | 13-JAN-15:00 | 8.90 | 4.67 |
February | 0.125857E+10 | 8952.62 | 28-FEB-16:40 | 10.37 | 4.49 | 0.284691E+09 | 543.49 | 27-FEB-14:00 | 10.37 | 4.49 |
March | 0.253686E+10 | 12184.13 | 28-MAR-17:00 | 10.60 | 2.97 | 0.348400E+09 | 544.93 | 02-MAR-14:00 | 10.60 | 2.97 |
April | 0.426512E+10 | 29483.32 | 22-APR-17:41 | 16.10 | 8.34 | 0.327242E+09 | 544.94 | 07-APR-13:09 | 16.10 | 8.34 |
May | 0.649839E+10 | 32474.27 | 14-MAY-17:01 | 14.13 | 5.05 | 0.374495E+09 | 544.96 | 19-MAY-13:09 | 26.28 | 14.91 |
June | 0.929033E+10 | 31545.69 | 25-JUN-18:41 | 21.97 | 13.95 | 0.407205E+09 | 603.25 | 30-JUN-15:00 | 31.10 | 14.62 |
July | 0.110109E+11 | 35969.30 | 02-JUL-18:21 | 24.75 | 14.30 | 0.391404E+09 | 636.97 | 25-JUL-15:00 | 33.90 | 15.43 |
August | 0.986707E+10 | 31288.50 | 06-AUG-16:41 | 35.10 | 15.80 | 0.428729E+09 | 621.32 | 07-AUG-15:00 | 32.20 | 16.16 |
September | 0.624772E+10 | 34124.07 | 04-SEP-16:51 | 32.80 | 16.77 | 0.350298E+09 | 565.82 | 01-SEP-15:00 | 32.80 | 16.77 |
October | 0.349128E+10 | 20105.43 | 15-OCT-16:42 | 21.28 | 10.50 | 0.337062E+09 | 544.95 | 18-OCT-13:00 | 25.00 | 11.40 |
November | 0.164282E+10 | 6768.75 | 03-NOV-15:40 | 14.40 | 7.69 | 0.316664E+09 | 544.85 | 09-NOV-14:00 | 9.00 | 3.82 |
December | 0.640384E+09 | 3950.84 | 06-DEC-15:40 | 9.97 | 4.80 | 0.294266E+09 | 521.18 | 06-DEC-16:10 | 8.95 | 4.16 |
Annual Sum or Average | 0.571228E+11 | 0.416226E+10 | ||||||||
Minimum of Months | 0.373359E+09 | 3270.47 | 9.08 | 2.97 | 0.284691E+09 | 501.68 | 8.90 | 2.97 | ||
Maximum of Months | 0.110109E+11 | 35969.30 | 35.10 | 16.77 | 0.428729E+09 | 636.97 | 33.90 | 16.77 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.101327E+10 | 11842.13 | 06-JAN-05:01 | -24.5 | -24.9 | 0.00 | 0.00 | 01-JAN-00:10 | -24.5 | -24.9 |
February | 0.124688E+10 | 7404.13 | 09-FEB-06:01 | -17.9 | -18.2 | 0.00 | 0.00 | 01-FEB-00:10 | -17.9 | -18.2 |
March | 0.280462E+10 | 8247.84 | 04-MAR-06:01 | -20.1 | -20.7 | 0.00 | 0.00 | 01-MAR-00:10 | -20.1 | -20.7 |
April | 0.452965E+10 | 6547.57 | 24-APR-16:00 | 18.90 | 10.03 | 0.00 | 0.00 | 01-APR-00:10 | 18.90 | 10.03 |
May | 0.459089E+10 | 9072.11 | 30-MAY-05:13 | 15.60 | 11.34 | 0.00 | 0.00 | 01-MAY-00:10 | 15.60 | 11.34 |
June | 0.818642E+10 | 10343.23 | 26-JUN-05:15 | 10.33 | 9.12 | 0.00 | 0.00 | 01-JUN-00:10 | 10.33 | 9.12 |
July | 0.109222E+11 | 15334.34 | 17-JUL-05:15 | 16.83 | 12.38 | 0.00 | 0.00 | 01-JUL-00:10 | 16.83 | 12.38 |
August | 0.104226E+11 | 14497.55 | 08-AUG-05:08 | 18.22 | 11.63 | 0.00 | 0.00 | 01-AUG-00:10 | 18.22 | 11.63 |
September | 0.631818E+10 | 14562.86 | 05-SEP-05:15 | 18.50 | 11.75 | 0.00 | 0.00 | 01-SEP-00:10 | 18.50 | 11.75 |
October | 0.448768E+10 | 6381.36 | 16-OCT-15:50 | 19.68 | 8.22 | 0.00 | 0.00 | 01-OCT-00:10 | 19.68 | 8.22 |
November | 0.272752E+10 | 5820.20 | 06-NOV-06:07 | -3.5 | -4.3 | 0.00 | 0.00 | 01-NOV-00:10 | -3.5 | -4.3 |
December | 0.145818E+10 | 6637.23 | 29-DEC-05:01 | -25.0 | -25.3 | 0.00 | 0.00 | 01-DEC-00:10 | -25.0 | -25.3 |
Annual Sum or Average | 0.587081E+11 | 0.00 | ||||||||
Minimum of Months | 0.101327E+10 | 5820.20 | -25.0 | -25.3 | 0.00 | 0.00 | -25.0 | -25.3 | ||
Maximum of Months | 0.109222E+11 | 15334.34 | 19.68 | 12.38 | 0.00 | 0.00 | 19.68 | 12.38 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.527415E+09 | 14862.57 | 06-JAN-04:11 | -24.4 | -24.9 | 0.00 | 0.00 | 01-JAN-00:10 | -24.4 | -24.9 |
February | 0.501683E+09 | 14024.31 | 04-FEB-04:11 | -21.7 | -22.0 | 0.00 | 0.00 | 01-FEB-00:10 | -21.7 | -22.0 |
March | 0.117493E+10 | 11271.62 | 04-MAR-05:01 | -19.1 | -19.6 | 0.00 | 0.00 | 01-MAR-00:10 | -19.1 | -19.6 |
April | 0.186851E+10 | 8271.94 | 29-APR-04:01 | -7.8 | -8.7 | 0.00 | 0.00 | 01-APR-00:10 | -7.8 | -8.7 |
May | 0.265602E+10 | 9559.52 | 08-MAY-04:01 | -2.3 | -2.7 | 0.00 | 0.00 | 01-MAY-00:10 | -2.3 | -2.7 |
June | 0.564422E+10 | 8595.08 | 22-JUN-10:35 | 26.67 | 16.56 | 0.00 | 0.00 | 01-JUN-00:10 | 26.67 | 16.56 |
July | 0.716526E+10 | 11331.73 | 25-JUL-16:56 | 33.90 | 15.42 | 0.00 | 0.00 | 01-JUL-00:10 | 33.90 | 15.42 |
August | 0.698146E+10 | 8779.74 | 10-AUG-12:35 | 32.03 | 14.10 | 0.00 | 0.00 | 01-AUG-00:10 | 32.03 | 14.10 |
September | 0.420538E+10 | 8584.98 | 05-SEP-15:40 | 22.93 | 14.37 | 0.00 | 0.00 | 01-SEP-00:10 | 22.93 | 14.37 |
October | 0.216670E+10 | 8106.00 | 10-OCT-04:01 | -5.2 | -5.7 | 0.00 | 0.00 | 01-OCT-00:10 | -5.2 | -5.7 |
November | 0.108796E+10 | 11627.97 | 27-NOV-04:01 | -15.8 | -16.7 | 0.00 | 0.00 | 01-NOV-00:10 | -15.8 | -16.7 |
December | 0.498132E+09 | 11374.58 | 28-DEC-04:01 | -22.7 | -23.1 | 0.00 | 0.00 | 01-DEC-00:10 | -22.7 | -23.1 |
Annual Sum or Average | 0.344777E+11 | 0.00 | ||||||||
Minimum of Months | 0.498132E+09 | 8106.00 | -24.4 | -24.9 | 0.00 | 0.00 | -24.4 | -24.9 | ||
Maximum of Months | 0.716526E+10 | 14862.57 | 33.90 | 16.56 | 0.00 | 0.00 | 33.90 | 16.56 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 1389914.67 | 436.15 | 14-JAN-13:30 | 10.00 | 4.73 | 0.00 | 0.00 | 01-JAN-00:10 | 10.00 | 4.73 |
February | 0.118587E+09 | 4421.47 | 26-FEB-14:24 | 16.15 | 6.12 | 0.00 | 0.00 | 01-FEB-00:10 | 16.15 | 6.12 |
March | 0.709241E+09 | 5295.85 | 23-MAR-13:55 | 10.00 | 2.51 | 0.00 | 0.00 | 01-MAR-00:10 | 10.00 | 2.51 |
April | 0.239690E+10 | 12143.03 | 25-APR-15:20 | 17.27 | 7.54 | 0.00 | 0.00 | 01-APR-00:10 | 17.27 | 7.54 |
May | 0.505326E+10 | 18849.97 | 19-MAY-15:00 | 28.30 | 14.88 | 0.00 | 0.00 | 01-MAY-00:10 | 28.30 | 14.88 |
June | 0.100798E+11 | 21913.59 | 21-JUN-12:50 | 26.52 | 17.70 | 0.00 | 0.00 | 01-JUN-00:10 | 26.52 | 17.70 |
July | 0.132108E+11 | 25896.23 | 25-JUL-17:04 | 33.80 | 15.36 | 0.00 | 0.00 | 01-JUL-00:10 | 33.80 | 15.36 |
August | 0.112997E+11 | 22352.59 | 10-AUG-13:05 | 32.30 | 13.85 | 0.00 | 0.00 | 01-AUG-00:10 | 32.30 | 13.85 |
September | 0.534487E+10 | 15800.18 | 01-SEP-16:17 | 28.13 | 13.81 | 0.00 | 0.00 | 01-SEP-00:10 | 28.13 | 13.81 |
October | 0.141624E+10 | 9470.13 | 18-OCT-15:20 | 24.80 | 11.42 | 0.00 | 0.00 | 01-OCT-00:10 | 24.80 | 11.42 |
November | 99690927.02 | 2319.33 | 03-NOV-13:40 | 14.57 | 7.78 | 0.00 | 0.00 | 01-NOV-00:10 | 14.57 | 7.78 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.2 | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 | -4.2 |
Annual Sum or Average | 0.497305E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -2.1 | -4.2 | 0.00 | 0.00 | -2.1 | -4.2 | ||
Maximum of Months | 0.132108E+11 | 25896.23 | 33.80 | 17.70 | 0.00 | 0.00 | 33.80 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.228032E+10 | 2219.45 | 19-JAN-16:50 | -6.4 | -8.0 | 95216604.49 | 126.82 | 03-JAN-14:09 | -6.4 | -8.0 |
February | 0.743042E+10 | 4648.88 | 26-FEB-17:17 | 14.10 | 5.35 | 86396434.16 | 126.82 | 08-FEB-14:09 | 14.10 | 5.35 |
March | 0.139126E+11 | 6861.76 | 31-MAR-24:00 | 2.50 | 0.99 | 0.103236E+09 | 126.82 | 15-MAR-13:09 | 2.50 | 0.99 |
April | 0.188468E+11 | 8516.00 | 16-APR-18:16 | 18.50 | 8.83 | 91605279.23 | 126.82 | 21-APR-09:00 | 3.30 | 2.53 |
May | 0.434272E+10 | 3507.24 | 31-MAY-24:00 | 15.50 | 10.27 | 99235088.06 | 126.84 | 30-MAY-09:30 | 15.50 | 10.27 |
June | 0.947128E+10 | 5374.97 | 30-JUN-24:00 | 19.60 | 12.23 | 98962970.24 | 126.85 | 01-JUN-13:00 | 19.60 | 12.23 |
July | 0.150937E+11 | 7287.68 | 31-JUL-23:50 | 19.48 | 11.61 | 91884069.79 | 126.84 | 07-JUL-09:09 | 19.48 | 11.61 |
August | 0.199683E+11 | 8493.98 | 03-AUG-18:50 | 24.60 | 12.54 | 0.103267E+09 | 126.83 | 22-AUG-09:30 | 17.25 | 12.58 |
September | 0.433719E+10 | 3338.72 | 30-SEP-24:00 | 11.80 | 6.26 | 91611034.88 | 126.86 | 06-SEP-13:00 | 11.80 | 6.26 |
October | 0.926640E+10 | 4997.57 | 31-OCT-24:00 | 4.70 | 1.47 | 95230962.16 | 126.83 | 25-OCT-09:00 | 4.70 | 1.47 |
November | 0.135129E+11 | 6299.93 | 13-NOV-16:30 | 3.15 | -2.5 | 94300330.72 | 126.83 | 08-NOV-14:00 | 3.15 | -2.5 |
December | 0.185402E+11 | 8030.04 | 06-DEC-16:10 | 8.95 | 4.16 | 91880773.27 | 126.82 | 13-DEC-14:09 | -5.6 | -7.0 |
Annual Sum or Average | 0.137003E+12 | 0.114283E+10 | ||||||||
Minimum of Months | 0.228032E+10 | 2219.45 | -6.4 | -8.0 | 86396434.16 | 126.82 | -6.4 | -8.0 | ||
Maximum of Months | 0.199683E+11 | 8516.00 | 24.60 | 12.54 | 0.103267E+09 | 126.86 | 19.60 | 12.58 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.566943E+09 | 1877.88 | 19-JAN-16:50 | -6.4 | -8.0 | 93536363.50 | 126.82 | 03-JAN-14:09 | -6.4 | -8.0 |
February | 0.522089E+10 | 4185.43 | 28-FEB-17:00 | 10.00 | 4.31 | 86396454.07 | 126.82 | 08-FEB-14:09 | 10.00 | 4.31 |
March | 0.116136E+11 | 6211.03 | 28-MAR-17:50 | 9.18 | 2.32 | 0.103236E+09 | 126.82 | 15-MAR-13:09 | 9.18 | 2.32 |
April | 0.169658E+11 | 8050.87 | 25-APR-18:10 | 16.73 | 7.64 | 91605323.62 | 126.83 | 24-APR-09:00 | 16.73 | 7.64 |
May | 0.343928E+10 | 3312.97 | 31-MAY-24:00 | 15.50 | 10.27 | 99234970.16 | 126.84 | 30-MAY-09:30 | 15.50 | 10.27 |
June | 0.866885E+10 | 5260.80 | 30-JUN-24:00 | 19.60 | 12.23 | 98962856.06 | 126.85 | 01-JUN-13:00 | 19.60 | 12.23 |
July | 0.141104E+11 | 7049.82 | 31-JUL-23:53 | 19.20 | 11.32 | 91884498.90 | 126.84 | 03-JUL-13:20 | 19.20 | 11.32 |
August | 0.188064E+11 | 8165.97 | 03-AUG-18:50 | 24.60 | 12.54 | 0.103245E+09 | 126.83 | 22-AUG-09:39 | 17.43 | 12.63 |
September | 0.351778E+10 | 2959.21 | 30-SEP-23:30 | 12.50 | 6.83 | 91609927.66 | 126.84 | 11-SEP-13:00 | 12.50 | 6.83 |
October | 0.766264E+10 | 4307.83 | 15-OCT-17:10 | 20.45 | 10.12 | 95230887.08 | 126.83 | 25-OCT-09:00 | 13.30 | 8.54 |
November | 0.111471E+11 | 5715.99 | 06-NOV-16:30 | 6.95 | 2.42 | 94300361.32 | 126.83 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 0.151541E+11 | 7370.35 | 06-DEC-16:20 | 8.50 | 3.80 | 91880812.15 | 126.82 | 13-DEC-14:09 | -5.6 | -7.0 |
Annual Sum or Average | 0.116874E+12 | 0.114112E+10 | ||||||||
Minimum of Months | 0.566943E+09 | 1877.88 | -6.4 | -8.0 | 86396454.07 | 126.82 | -6.4 | -8.0 | ||
Maximum of Months | 0.188064E+11 | 8165.97 | 24.60 | 12.54 | 0.103245E+09 | 126.85 | 19.60 | 12.63 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.222563E+09 | 1589.77 | 13-JAN-16:40 | 8.17 | 4.18 | 88805869.62 | 128.15 | 13-JAN-10:09 | 8.17 | 4.18 |
February | 0.367710E+10 | 4098.58 | 28-FEB-17:00 | 10.00 | 4.31 | 86393300.42 | 126.82 | 08-FEB-14:09 | 10.00 | 4.31 |
March | 0.996995E+10 | 6175.26 | 28-MAR-17:50 | 9.18 | 2.32 | 0.103236E+09 | 126.82 | 15-MAR-13:09 | 9.18 | 2.32 |
April | 0.158300E+11 | 8107.62 | 25-APR-18:10 | 16.73 | 7.64 | 91605351.49 | 126.83 | 24-APR-09:00 | 16.73 | 7.64 |
May | 0.282817E+10 | 3230.27 | 31-MAY-23:40 | 15.70 | 10.35 | 99044507.04 | 126.84 | 30-MAY-09:30 | 15.70 | 10.35 |
June | 0.843513E+10 | 5261.96 | 30-JUN-24:00 | 19.60 | 12.23 | 98962861.41 | 126.85 | 01-JUN-13:00 | 19.60 | 12.23 |
July | 0.140310E+11 | 7013.79 | 31-JUL-23:53 | 19.20 | 11.32 | 91884496.56 | 126.84 | 03-JUL-13:20 | 19.20 | 11.32 |
August | 0.186384E+11 | 8227.78 | 03-AUG-18:50 | 24.60 | 12.54 | 0.103247E+09 | 126.83 | 22-AUG-09:39 | 17.43 | 12.63 |
September | 0.297116E+10 | 3071.22 | 04-SEP-17:43 | 31.88 | 16.41 | 91607971.82 | 126.84 | 05-SEP-09:00 | 17.20 | 11.96 |
October | 0.630297E+10 | 4283.22 | 18-OCT-17:00 | 21.70 | 10.27 | 95230867.50 | 126.83 | 25-OCT-09:00 | 13.30 | 8.54 |
November | 0.925316E+10 | 5634.18 | 03-NOV-16:00 | 14.30 | 7.69 | 94300370.69 | 126.83 | 08-NOV-14:00 | 13.20 | 7.65 |
December | 0.129748E+11 | 7273.13 | 06-DEC-16:20 | 8.50 | 3.80 | 91880824.65 | 126.82 | 13-DEC-14:09 | -5.6 | -7.0 |
Annual Sum or Average | 0.105134E+12 | 0.113620E+10 | ||||||||
Minimum of Months | 0.222563E+09 | 1589.77 | 8.17 | 2.32 | 86393300.42 | 126.82 | -5.6 | -7.0 | ||
Maximum of Months | 0.186384E+11 | 8227.78 | 31.88 | 16.41 | 0.103247E+09 | 128.15 | 19.60 | 12.63 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.235524E+12 | 92487.13 | 02-JAN-17:00 | 2.20 | -1.7 | 0.206152E+10 | 2745.43 | 03-JAN-14:00 | 5.60 | -1.1 |
February | 0.434443E+12 | 183945.08 | 28-FEB-17:00 | 10.00 | 4.31 | 0.187031E+10 | 2745.66 | 24-FEB-10:20 | 10.00 | 4.31 |
March | 0.728112E+12 | 357963.40 | 31-MAR-24:00 | 2.50 | 0.99 | 0.223479E+10 | 2745.59 | 23-MAR-09:30 | 2.50 | 0.99 |
April | 0.942442E+12 | 367750.56 | 25-APR-16:00 | 17.80 | 7.70 | 0.198309E+10 | 2747.32 | 24-APR-13:09 | 17.80 | 7.70 |
May | 0.240788E+12 | 176455.14 | 31-MAY-24:00 | 15.50 | 10.27 | 0.214819E+10 | 2747.07 | 19-MAY-13:09 | 15.50 | 10.27 |
June | 0.471190E+12 | 268457.64 | 30-JUN-23:55 | 19.60 | 12.23 | 0.214251E+10 | 2749.54 | 26-JUN-09:00 | 19.60 | 12.23 |
July | 0.734974E+12 | 361039.99 | 31-JUL-23:53 | 19.20 | 11.32 | 0.199016E+10 | 2752.16 | 06-JUL-09:00 | 19.20 | 11.32 |
August | 0.979773E+12 | 370592.81 | 07-AUG-16:00 | 32.20 | 16.16 | 0.223635E+10 | 2754.83 | 22-AUG-09:50 | 17.62 | 12.68 |
September | 0.236207E+12 | 176003.79 | 30-SEP-24:00 | 11.80 | 6.26 | 0.198306E+10 | 2746.67 | 05-SEP-13:39 | 11.80 | 6.26 |
October | 0.487376E+12 | 267901.27 | 31-OCT-24:00 | 4.70 | 1.47 | 0.206153E+10 | 2745.55 | 30-OCT-09:00 | 4.70 | 1.47 |
November | 0.707556E+12 | 276764.97 | 06-NOV-16:55 | 6.70 | 2.26 | 0.204136E+10 | 2745.50 | 16-NOV-14:00 | 10.80 | 6.43 |
December | 0.974355E+12 | 368013.10 | 06-DEC-17:00 | 6.70 | 2.38 | 0.198896E+10 | 2745.56 | 11-DEC-10:39 | 0.93 | -2.6 |
Annual Sum or Average | 0.717274E+13 | 0.247418E+11 | ||||||||
Minimum of Months | 0.235524E+12 | 92487.13 | 2.20 | -1.7 | 0.187031E+10 | 2745.43 | 0.93 | -2.6 | ||
Maximum of Months | 0.979773E+12 | 370592.81 | 32.20 | 16.16 | 0.223635E+10 | 2754.83 | 19.60 | 12.68 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.38 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 558.53 | 0.93 | 01-SEP-21:00 | 17.80 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 558.53 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 558.53 | 0.93 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.38 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 0.00 | 0.00 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.373447E+09 | 48399.13 | 09-JAN-05:01 | -27.2 |
February | 0.114363E+09 | 47047.77 | 06-FEB-05:01 | -0.4 |
March | 20634348.75 | 42872.95 | 06-MAR-06:02 | -16.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 5186296.61 | 41451.62 | 27-NOV-06:02 | -14.5 |
December | 12744112.93 | 42653.48 | 26-DEC-06:01 | -7.9 |
Annual Sum or Average | 0.526374E+09 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.373447E+09 | 48399.13 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.798144E+10 | 80450.68 | 09-JAN-04:11 | -27.2 |
February | 0.265575E+10 | 77587.33 | 06-FEB-04:01 | -0.6 |
March | 0.148029E+10 | 77568.56 | 06-MAR-04:01 | -18.4 |
April | 31240546.47 | 62582.32 | 10-APR-05:03 | 3.90 |
May | 0.385184E+09 | 69458.64 | 08-MAY-04:01 | -2.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.43 |
October | 0.226763E+09 | 69332.65 | 10-OCT-04:01 | -5.2 |
November | 0.187995E+10 | 77635.57 | 27-NOV-04:01 | -15.8 |
December | 0.412851E+10 | 79280.91 | 31-DEC-23:31 | -23.5 |
Annual Sum or Average | 0.187691E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.798144E+10 | 80450.68 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.166939E+10 | 14235.43 | 09-JAN-04:01 | -27.2 |
February | 0.396864E+09 | 12709.11 | 04-FEB-05:01 | -20.4 |
March | 71108164.31 | 12639.59 | 06-MAR-05:01 | -18.4 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 20940101.48 | 12126.71 | 27-NOV-05:01 | -15.4 |
December | 0.286284E+09 | 12605.34 | 29-DEC-05:01 | -25.0 |
Annual Sum or Average | 0.244459E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.166939E+10 | 14235.43 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107861E+10 | 16126.70 | 09-JAN-04:01 | -27.2 |
February | 0.315656E+09 | 13983.75 | 04-FEB-05:01 | -20.4 |
March | 65945582.48 | 14045.03 | 06-MAR-05:01 | -18.4 |
April | 872453.02 | 7079.24 | 29-APR-05:01 | -7.7 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.43 |
October | 35568.33 | 296.40 | 05-OCT-05:04 | -1.9 |
November | 34218285.41 | 12970.10 | 27-NOV-05:01 | -15.4 |
December | 0.319582E+09 | 14139.26 | 29-DEC-05:01 | -25.0 |
Annual Sum or Average | 0.181492E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.107861E+10 | 16126.70 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.166300E+10 | 23444.67 | 09-JAN-04:01 | -27.2 |
February | 0.398509E+09 | 20956.59 | 04-FEB-05:01 | -20.4 |
March | 0.127430E+09 | 21275.83 | 06-MAR-05:01 | -18.4 |
April | 2486949.74 | 14875.23 | 29-APR-05:01 | -7.7 |
May | 8775586.40 | 16913.80 | 08-MAY-05:01 | -2.8 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.43 |
October | 3392049.76 | 11072.91 | 10-OCT-05:03 | -6.1 |
November | 84896695.45 | 20233.66 | 27-NOV-05:01 | -15.4 |
December | 0.451400E+09 | 21142.39 | 29-DEC-05:01 | -25.0 |
Annual Sum or Average | 0.273989E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.166300E+10 | 23444.67 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.547382E+09 | 13937.55 | 09-JAN-04:01 | -27.2 |
February | 34679964.06 | 10674.51 | 01-FEB-06:01 | -25.0 |
March | 3701844.84 | 10429.13 | 04-MAR-06:01 | -20.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 939472.69 | 7288.96 | 27-NOV-06:02 | -14.5 |
December | 6197970.06 | 9018.89 | 29-DEC-06:02 | -25.1 |
Annual Sum or Average | 0.592902E+09 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.547382E+09 | 13937.55 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.685660E+10 | 14390.38 | 09-JAN-04:01 | -27.2 |
February | 0.301719E+10 | 13821.19 | 05-FEB-21:02 | -17.7 |
March | 0.123938E+10 | 13893.48 | 06-MAR-03:41 | -18.4 |
April | 0.101813E+09 | 11684.68 | 29-APR-04:01 | -7.8 |
May | 94437474.86 | 11994.33 | 08-MAY-04:01 | -2.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 9513507.47 | 9108.16 | 19-SEP-05:03 | 2.20 |
October | 0.112892E+09 | 11937.01 | 10-OCT-04:01 | -5.2 |
November | 0.116130E+10 | 13533.55 | 27-NOV-04:01 | -15.8 |
December | 0.371105E+10 | 14606.86 | 31-DEC-23:31 | -23.5 |
Annual Sum or Average | 0.163042E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.685660E+10 | 14606.86 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.403779E+10 | 20900.59 | 09-JAN-02:41 | -27.2 |
February | 0.164476E+10 | 19808.36 | 04-FEB-04:11 | -21.7 |
March | 0.681363E+09 | 19321.72 | 06-MAR-04:01 | -18.4 |
April | 65789221.84 | 16597.10 | 29-APR-04:01 | -7.8 |
May | 62656128.85 | 16949.94 | 08-MAY-04:01 | -2.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 6055640.17 | 6388.89 | 19-SEP-05:03 | 2.20 |
October | 66952341.23 | 16808.54 | 10-OCT-04:01 | -5.2 |
November | 0.707111E+09 | 19425.70 | 27-NOV-04:01 | -15.8 |
December | 0.221816E+10 | 21094.43 | 31-DEC-23:31 | -23.5 |
Annual Sum or Average | 0.949064E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.403779E+10 | 21094.43 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.416767E+10 | 26147.16 | 09-JAN-04:01 | -27.2 |
February | 0.143457E+10 | 24700.48 | 04-FEB-04:11 | -21.7 |
March | 0.669586E+09 | 24436.35 | 06-MAR-04:01 | -18.4 |
April | 85649380.58 | 21105.73 | 29-APR-04:01 | -7.8 |
May | 99074813.84 | 21560.39 | 08-MAY-04:01 | -2.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 3102942.47 | 5838.30 | 19-SEP-05:03 | 2.20 |
October | 53802718.77 | 21315.33 | 10-OCT-04:01 | -5.2 |
November | 0.618281E+09 | 24628.68 | 27-NOV-04:01 | -15.8 |
December | 0.210436E+10 | 26302.26 | 31-DEC-23:31 | -23.5 |
Annual Sum or Average | 0.923610E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.416767E+10 | 26302.26 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.358516E+10 | 21096.14 | 09-JAN-02:41 | -27.2 |
February | 0.125371E+10 | 19832.54 | 04-FEB-04:11 | -21.7 |
March | 0.499321E+09 | 19568.39 | 06-MAR-04:01 | -18.4 |
April | 30330489.45 | 15141.42 | 29-APR-05:01 | -7.7 |
May | 39393711.69 | 16692.75 | 08-MAY-04:01 | -2.3 |
June | 45210.80 | 301.41 | 17-JUN-05:05 | 2.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 2530223.87 | 4714.31 | 19-SEP-05:03 | 2.20 |
October | 40702025.43 | 14725.31 | 10-OCT-04:01 | -5.2 |
November | 0.473255E+09 | 19724.31 | 27-NOV-04:01 | -15.8 |
December | 0.169154E+10 | 21076.54 | 31-DEC-23:31 | -23.5 |
Annual Sum or Average | 0.761598E+10 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.358516E+10 | 21096.14 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.127310E+11 | 17622.06 | 09-JAN-04:11 | -27.2 |
February | 0.629969E+10 | 16535.76 | 05-FEB-19:12 | -18.1 |
March | 0.380327E+10 | 16836.17 | 06-MAR-02:32 | -17.6 |
April | 0.922769E+09 | 14256.10 | 29-APR-03:02 | -6.9 |
May | 0.620775E+09 | 15526.31 | 01-MAY-03:01 | -0.7 |
June | 10446349.17 | 12212.99 | 17-JUN-05:03 | 2.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 4623816.96 | 12452.29 | 18-AUG-05:02 | 7.30 |
September | 0.210698E+09 | 13705.28 | 19-SEP-04:11 | 2.20 |
October | 0.962636E+09 | 15424.05 | 10-OCT-03:11 | -4.3 |
November | 0.407343E+10 | 16889.14 | 27-NOV-03:52 | -15.8 |
December | 0.913805E+10 | 17268.48 | 31-DEC-23:31 | -23.5 |
Annual Sum or Average | 0.387774E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.127310E+11 | 17622.06 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.755344E+10 | 24545.79 | 09-JAN-04:11 | -27.2 |
February | 0.343507E+10 | 22549.21 | 05-FEB-03:12 | -20.0 |
March | 0.206971E+10 | 23072.25 | 06-MAR-02:32 | -17.6 |
April | 0.469578E+09 | 19616.35 | 01-APR-04:11 | 6.33 |
May | 0.351372E+09 | 21431.75 | 01-MAY-03:01 | -0.7 |
June | 6774162.59 | 9782.39 | 17-JUN-04:12 | 2.03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 3595093.35 | 13711.83 | 18-AUG-05:02 | 7.30 |
September | 0.112737E+09 | 18860.79 | 19-SEP-04:11 | 2.20 |
October | 0.497859E+09 | 21362.47 | 10-OCT-03:11 | -4.3 |
November | 0.225901E+10 | 23108.55 | 27-NOV-03:52 | -15.8 |
December | 0.534117E+10 | 23773.16 | 31-DEC-23:31 | -23.5 |
Annual Sum or Average | 0.221003E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.755344E+10 | 24545.79 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.858032E+10 | 30194.63 | 09-JAN-04:11 | -27.2 |
February | 0.360087E+10 | 28027.91 | 05-FEB-03:12 | -20.0 |
March | 0.255510E+10 | 28557.88 | 06-MAR-02:32 | -17.6 |
April | 0.740353E+09 | 24140.86 | 01-APR-04:11 | 6.33 |
May | 0.624310E+09 | 26479.34 | 08-MAY-03:01 | -2.7 |
June | 23912676.19 | 13923.14 | 17-JUN-05:03 | 2.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 10196151.16 | 19532.06 | 18-AUG-05:02 | 7.30 |
September | 0.137381E+09 | 23202.13 | 19-SEP-04:11 | 2.20 |
October | 0.528271E+09 | 26418.06 | 10-OCT-03:11 | -4.3 |
November | 0.233063E+10 | 28590.08 | 27-NOV-03:52 | -15.8 |
December | 0.576011E+10 | 29442.46 | 31-DEC-23:31 | -23.5 |
Annual Sum or Average | 0.248915E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.858032E+10 | 30194.63 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.693104E+10 | 26700.54 | 09-JAN-04:11 | -27.2 |
February | 0.276788E+10 | 23807.83 | 10-FEB-04:11 | -19.4 |
March | 0.164963E+10 | 24741.73 | 06-MAR-02:32 | -17.6 |
April | 0.325427E+09 | 20827.65 | 01-APR-04:11 | 6.33 |
May | 0.266406E+09 | 23023.54 | 08-MAY-03:01 | -2.7 |
June | 9734761.66 | 8231.32 | 17-JUN-05:03 | 2.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 3729792.27 | 9473.28 | 18-AUG-05:02 | 7.30 |
September | 73421924.71 | 19951.96 | 19-SEP-04:11 | 2.20 |
October | 0.340829E+09 | 22640.22 | 10-OCT-03:11 | -4.3 |
November | 0.163042E+10 | 24840.93 | 27-NOV-03:52 | -15.8 |
December | 0.413178E+10 | 25676.33 | 31-DEC-23:31 | -23.5 |
Annual Sum or Average | 0.181303E+11 | |||
Minimum of Months | 0.00 | 0.00 | -27.2 | |
Maximum of Months | 0.693104E+10 | 26700.54 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.154670E+10 | 9726.62 | 24-JAN-06:03 | 8.22 |
February | 0.596753E+09 | 14853.44 | 26-FEB-15:31 | 16.30 |
March | 0.254297E+09 | 11658.09 | 12-MAR-15:42 | 6.02 |
April | 0.138603E+09 | 14960.31 | 16-APR-15:21 | 19.70 |
May | 65677481.46 | 9781.38 | 14-MAY-15:12 | 16.50 |
June | 93378836.01 | 10615.19 | 18-JUN-15:12 | 24.60 |
July | 0.165789E+09 | 13610.04 | 09-JUL-15:51 | 28.30 |
August | 0.116388E+09 | 14901.02 | 06-AUG-16:01 | 35.50 |
September | 90501792.17 | 12400.16 | 03-SEP-15:31 | 33.67 |
October | 92946699.25 | 14251.55 | 15-OCT-15:21 | 22.50 |
November | 0.151453E+09 | 11274.54 | 30-NOV-06:01 | 1.10 |
December | 0.261657E+09 | 12304.97 | 19-DEC-05:11 | 3.50 |
Annual Sum or Average | 0.357415E+10 | |||
Minimum of Months | 65677481.46 | 9726.62 | 1.10 | |
Maximum of Months | 0.154670E+10 | 14960.31 | 35.50 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.407267E+10 | 13369.69 | 01-JAN-14:43 | 7.38 |
February | 0.232782E+10 | 14293.99 | 26-FEB-14:12 | 15.97 |
March | 0.112748E+10 | 11537.68 | 26-MAR-13:12 | 9.27 |
April | 0.133501E+09 | 16882.55 | 16-APR-16:01 | 20.00 |
May | 0.257428E+09 | 11685.05 | 14-MAY-15:01 | 16.60 |
June | 71284871.61 | 11368.61 | 18-JUN-15:32 | 24.80 |
July | 0.100157E+09 | 14414.53 | 30-JUL-16:01 | 30.68 |
August | 57763253.53 | 16410.22 | 06-AUG-15:51 | 35.60 |
September | 81583264.55 | 15475.98 | 03-SEP-15:21 | 33.30 |
October | 0.214352E+09 | 14836.70 | 15-OCT-15:21 | 22.50 |
November | 0.967872E+09 | 10598.98 | 12-NOV-13:51 | 0.00 |
December | 0.212160E+10 | 6142.85 | 17-DEC-14:53 | -1.7 |
Annual Sum or Average | 0.115335E+11 | |||
Minimum of Months | 57763253.53 | 6142.85 | -1.7 | |
Maximum of Months | 0.407267E+10 | 16882.55 | 35.60 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.174490E+11 | 35532.74 | 09-JAN-05:11 | -27.2 |
February | 0.893532E+10 | 30219.89 | 04-FEB-05:21 | -20.0 |
March | 0.626679E+10 | 32519.46 | 06-MAR-05:22 | -17.2 |
April | 0.238410E+10 | 13188.38 | 29-APR-05:01 | -7.7 |
May | 0.166200E+10 | 18836.03 | 08-MAY-05:13 | -2.8 |
June | 0.375653E+09 | 14574.62 | 28-JUN-05:03 | 9.27 |
July | 0.157214E+09 | 15103.11 | 12-JUL-05:03 | 6.85 |
August | 0.265379E+09 | 13841.13 | 28-AUG-05:03 | 7.12 |
September | 0.939894E+09 | 13988.24 | 28-SEP-05:03 | 8.90 |
October | 0.247106E+10 | 18251.44 | 10-OCT-05:03 | -6.1 |
November | 0.665825E+10 | 31331.24 | 27-NOV-05:22 | -15.1 |
December | 0.130621E+11 | 32159.23 | 29-DEC-05:23 | -25.0 |
Annual Sum or Average | 0.606267E+11 | |||
Minimum of Months | 0.157214E+09 | 13188.38 | -27.2 | |
Maximum of Months | 0.174490E+11 | 35532.74 | 9.27 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 23542454.01 | 541.95 | 30-JAN-01:21 | -26.9 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 23542454.01 | |||
Minimum of Months | 0.00 | 0.00 | -26.9 | |
Maximum of Months | 23542454.01 | 541.95 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.493840E+09 | 671.31 | 29-JAN-18:33 | -24.5 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 0.493840E+09 | |||
Minimum of Months | 0.00 | 0.00 | -24.5 | |
Maximum of Months | 0.493840E+09 | 671.31 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.897863E+09 | 737.54 | 29-JAN-17:53 | -22.2 |
February | 61370130.16 | 646.17 | 05-FEB-20:10 | -17.9 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 2393891.22 | 674.80 | 30-APR-23:30 | -1.2 |
May | 0.109021E+09 | 671.14 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 20305016.60 | 454.53 | 19-SEP-04:27 | 2.20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 0.109095E+10 | |||
Minimum of Months | 0.00 | 0.00 | -22.2 | |
Maximum of Months | 0.897863E+09 | 737.54 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.38 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -12.4 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.42 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 18.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -2.1 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -12.4 | |
Maximum of Months | 0.00 | 0.00 | 19.45 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180249E+11 | 19402.09 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.163527E+11 | 19402.09 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.194806E+11 | 19402.09 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.173504E+11 | 19402.09 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.187528E+11 | 19402.09 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.186803E+11 | 19402.09 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.174228E+11 | 19402.09 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.194803E+11 | 19402.09 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.173504E+11 | 19402.09 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.180252E+11 | 19402.09 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.178272E+11 | 19402.09 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.174231E+11 | 19402.09 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.216171E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.163527E+11 | 19402.09 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.194806E+11 | 19402.09 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.141606E+10 | 2187.81 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.112920E+10 | 1906.53 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.125033E+10 | 2187.81 | 17-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.105743E+10 | 1625.25 | 14-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.110005E+10 | 1524.25 | 03-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.107147E+10 | 1141.96 | 16-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.101873E+10 | 1242.97 | 07-JUL-07:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.114783E+10 | 1242.97 | 17-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.108645E+10 | 1906.53 | 11-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.121054E+10 | 2187.81 | 25-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.132756E+10 | 2187.81 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.138255E+10 | 2187.81 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.141982E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.101873E+10 | 1141.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.141606E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.877161E+09 | 1409.91 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.711476E+09 | 1228.64 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.795609E+09 | 1409.91 | 17-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.677638E+09 | 982.28 | 14-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.710820E+09 | 801.02 | 03-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.697333E+09 | 670.83 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.658489E+09 | 735.93 | 07-JUL-07:19 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.742895E+09 | 735.93 | 17-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.694385E+09 | 982.28 | 13-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.760052E+09 | 1409.91 | 25-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.830807E+09 | 1409.91 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.855791E+09 | 1409.91 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.901246E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.658489E+09 | 670.83 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.877161E+09 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.133153E+10 | 2187.86 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.108040E+10 | 1906.57 | 02-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.123178E+10 | 2187.86 | 17-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.105801E+10 | 1625.29 | 14-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.110645E+10 | 1524.28 | 03-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.108194E+10 | 1141.99 | 16-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.102561E+10 | 1243.00 | 07-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.115616E+10 | 1243.00 | 17-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.108007E+10 | 1524.28 | 11-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.116836E+10 | 2187.86 | 25-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.124874E+10 | 2187.86 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.128360E+10 | 2187.86 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.138526E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.102561E+10 | 1141.99 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.133153E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.888182E+09 | 1409.91 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.711176E+09 | 1409.91 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.801803E+09 | 1409.91 | 17-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.684211E+09 | 1228.64 | 14-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.710901E+09 | 982.28 | 03-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.691232E+09 | 735.93 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.658870E+09 | 801.02 | 07-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.742344E+09 | 982.28 | 17-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.699571E+09 | 1228.64 | 11-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.770854E+09 | 1409.91 | 25-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.825218E+09 | 1409.91 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.855817E+09 | 1409.91 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.904018E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.658870E+09 | 735.93 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.888182E+09 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.141106E+10 | 2187.81 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.112506E+10 | 1906.53 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.124786E+10 | 2187.81 | 17-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.105552E+10 | 1524.25 | 14-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.109912E+10 | 1524.25 | 03-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.107105E+10 | 1141.96 | 26-JUN-11:30 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.101839E+10 | 1242.97 | 07-JUL-07:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.114716E+10 | 1242.97 | 17-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.108421E+10 | 1805.53 | 11-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.120717E+10 | 2187.81 | 25-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.132293E+10 | 2187.81 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.137593E+10 | 2187.81 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.141655E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.101839E+10 | 1141.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.141106E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.875600E+09 | 1409.91 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.710173E+09 | 1228.64 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.794829E+09 | 1409.91 | 17-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.676798E+09 | 982.28 | 14-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.710233E+09 | 801.02 | 03-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.696834E+09 | 670.83 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.658171E+09 | 735.93 | 07-JUL-07:19 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.742352E+09 | 735.93 | 17-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.693834E+09 | 982.28 | 13-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.758802E+09 | 1409.91 | 25-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.829060E+09 | 1409.91 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.853092E+09 | 1409.91 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.899978E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.658171E+09 | 670.83 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.875600E+09 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.133024E+10 | 2187.86 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.107910E+10 | 1805.57 | 02-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.123054E+10 | 2187.86 | 17-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.105669E+10 | 1524.28 | 14-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.110528E+10 | 1524.28 | 03-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.108088E+10 | 1141.99 | 16-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.102485E+10 | 1243.00 | 07-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.115503E+10 | 1243.00 | 17-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.107902E+10 | 1524.28 | 11-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.116597E+10 | 2187.86 | 25-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.124780E+10 | 2187.86 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.128233E+10 | 2187.86 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.138377E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.102485E+10 | 1141.99 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.133024E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.886074E+09 | 1409.91 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.709355E+09 | 1409.91 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.800462E+09 | 1409.91 | 17-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.683426E+09 | 1228.64 | 14-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.710371E+09 | 982.28 | 03-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.690759E+09 | 735.93 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.658373E+09 | 801.02 | 07-JUL-07:19 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.741789E+09 | 982.28 | 17-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.698297E+09 | 1228.64 | 11-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.769016E+09 | 1409.91 | 25-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.823878E+09 | 1409.91 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.853827E+09 | 1409.91 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.902562E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.658373E+09 | 735.93 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.886074E+09 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.141065E+10 | 2187.81 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.112496E+10 | 1906.53 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.124771E+10 | 2187.81 | 17-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.105537E+10 | 1524.25 | 14-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.109900E+10 | 1524.25 | 03-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.107103E+10 | 1141.96 | 26-JUN-11:30 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.101836E+10 | 1242.97 | 07-JUL-07:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.114714E+10 | 1242.97 | 17-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.108416E+10 | 1805.53 | 11-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.120695E+10 | 2187.81 | 25-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.132285E+10 | 2187.81 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.137559E+10 | 2187.81 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.141638E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.101836E+10 | 1141.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.141065E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.875600E+09 | 1409.91 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.710097E+09 | 1228.64 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.794729E+09 | 1409.91 | 17-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.676798E+09 | 982.28 | 14-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.710201E+09 | 801.02 | 03-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.696816E+09 | 670.83 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.658171E+09 | 735.93 | 07-JUL-07:19 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.742326E+09 | 735.93 | 17-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.693812E+09 | 982.28 | 13-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.758953E+09 | 1409.91 | 25-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.829399E+09 | 1409.91 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.853092E+09 | 1409.91 | 01-DEC-08:09 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.900000E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.658171E+09 | 670.83 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.875600E+09 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.133018E+10 | 2187.86 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.107910E+10 | 1805.57 | 02-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.123052E+10 | 2187.86 | 17-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.105665E+10 | 1524.28 | 14-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.110528E+10 | 1524.28 | 03-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.108088E+10 | 1141.99 | 16-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.102483E+10 | 1243.00 | 07-JUL-07:30 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.115501E+10 | 1243.00 | 17-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.107897E+10 | 1524.28 | 11-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.116597E+10 | 2187.86 | 25-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.124780E+10 | 2187.86 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.128216E+10 | 2187.86 | 01-DEC-08:09 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.138373E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.102483E+10 | 1141.99 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.133018E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.885965E+09 | 1409.91 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.709307E+09 | 1409.91 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.800423E+09 | 1409.91 | 17-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.683426E+09 | 1228.64 | 14-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.710353E+09 | 982.28 | 03-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.690748E+09 | 735.93 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.658366E+09 | 801.02 | 07-JUL-07:19 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.741789E+09 | 982.28 | 17-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.698219E+09 | 1228.64 | 11-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.769007E+09 | 1409.91 | 25-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.823839E+09 | 1409.91 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.853788E+09 | 1409.91 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.902523E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.658366E+09 | 735.93 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.885965E+09 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.522764E+10 | 5470.56 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.474186E+10 | 5470.56 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.563465E+10 | 5470.56 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.503289E+10 | 5470.56 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.543115E+10 | 5470.56 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.540489E+10 | 5470.56 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.505915E+10 | 5470.56 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.563465E+10 | 5470.56 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.503289E+10 | 5470.56 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.522764E+10 | 5470.56 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.516637E+10 | 5470.56 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.505915E+10 | 5470.56 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.626529E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.474186E+10 | 5470.56 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.563465E+10 | 5470.56 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.180249E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.163527E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.194806E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.173504E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.187528E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.186803E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.174228E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.194803E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.173504E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.180252E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.178272E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.174231E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.216171E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.163527E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.194806E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.141606E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.704256E+09 |
February | 0.136985E+10 | 0.112920E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564910E+09 |
March | 0.163685E+10 | 0.125033E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512526E+09 |
April | 0.145243E+10 | 0.105743E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373048E+09 |
May | 0.157338E+10 | 0.110005E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 818205.46 | 0.365906E+09 |
June | 0.156900E+10 | 0.107147E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4038365.12 | 0.182090E+09 |
July | 0.145680E+10 | 0.101873E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12505463.22 | 0.123345E+09 |
August | 0.163685E+10 | 0.114783E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11576734.71 | 0.132526E+09 |
September | 0.145243E+10 | 0.108645E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7206496.83 | 0.240757E+09 |
October | 0.150991E+10 | 0.121054E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48757.23 | 0.363700E+09 |
November | 0.149516E+10 | 0.132756E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.513529E+09 |
December | 0.145680E+10 | 0.138255E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.653639E+09 |
Annual Sum or Average | 0.181194E+11 | 0.141982E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36194022.55 | 0.473023E+10 |
Minimum of Months | 0.136985E+10 | 0.101873E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123345E+09 |
Maximum of Months | 0.163685E+10 | 0.141606E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12505463.22 | 0.704256E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.877161E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.468930E+09 |
February | 0.882782E+09 | 0.711476E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376573E+09 |
March | 0.105485E+10 | 0.795609E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337305E+09 |
April | 0.936002E+09 | 0.677638E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243791E+09 |
May | 0.101394E+10 | 0.710820E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 580829.93 | 0.238963E+09 |
June | 0.101113E+10 | 0.697333E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2802889.49 | 0.118770E+09 |
July | 0.938820E+09 | 0.658489E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9123464.29 | 77815226.86 |
August | 0.105485E+10 | 0.742895E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7980874.61 | 82830474.73 |
September | 0.936002E+09 | 0.694385E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4957547.80 | 0.159386E+09 |
October | 0.973041E+09 | 0.760052E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32503.51 | 0.240729E+09 |
November | 0.963541E+09 | 0.830807E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334845E+09 |
December | 0.938820E+09 | 0.855791E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427128E+09 |
Annual Sum or Average | 0.116768E+11 | 0.901246E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 25478109.62 | 0.310707E+10 |
Minimum of Months | 0.882782E+09 | 0.658489E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77815226.86 |
Maximum of Months | 0.105485E+10 | 0.877161E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9123464.29 | 0.468930E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.133153E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.709683E+09 |
February | 0.136988E+10 | 0.108040E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.581493E+09 |
March | 0.163688E+10 | 0.123178E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.515596E+09 |
April | 0.145246E+10 | 0.105801E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.371743E+09 |
May | 0.157341E+10 | 0.110645E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 825570.54 | 0.360080E+09 |
June | 0.156904E+10 | 0.108194E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4055775.86 | 0.179144E+09 |
July | 0.145684E+10 | 0.102561E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12520541.25 | 0.119762E+09 |
August | 0.163688E+10 | 0.115616E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10827492.22 | 0.131521E+09 |
September | 0.145246E+10 | 0.108007E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6247799.12 | 0.244379E+09 |
October | 0.150994E+10 | 0.116836E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26058.79 | 0.373094E+09 |
November | 0.149520E+10 | 0.124874E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516806E+09 |
December | 0.145684E+10 | 0.128360E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.657619E+09 |
Annual Sum or Average | 0.181198E+11 | 0.138526E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34503237.78 | 0.476092E+10 |
Minimum of Months | 0.136988E+10 | 0.102561E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119762E+09 |
Maximum of Months | 0.163688E+10 | 0.133153E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12520541.25 | 0.709683E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.888182E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.481187E+09 |
February | 0.882782E+09 | 0.711176E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401399E+09 |
March | 0.105485E+10 | 0.801803E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.365378E+09 |
April | 0.936002E+09 | 0.684211E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275245E+09 |
May | 0.101394E+10 | 0.710901E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 530771.06 | 0.258151E+09 |
June | 0.101113E+10 | 0.691232E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2664642.11 | 0.131384E+09 |
July | 0.938820E+09 | 0.658870E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8166844.48 | 90014525.72 |
August | 0.105485E+10 | 0.742344E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7475632.83 | 97872270.34 |
September | 0.936002E+09 | 0.699571E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4788464.41 | 0.169599E+09 |
October | 0.973041E+09 | 0.770854E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32505.46 | 0.261835E+09 |
November | 0.963541E+09 | 0.825218E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369299E+09 |
December | 0.938820E+09 | 0.855817E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473279E+09 |
Annual Sum or Average | 0.116768E+11 | 0.904018E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23658860.34 | 0.337464E+10 |
Minimum of Months | 0.882782E+09 | 0.658870E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90014525.72 |
Maximum of Months | 0.105485E+10 | 0.888182E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8166844.48 | 0.481187E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.141106E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150395E+10 |
February | 0.136985E+10 | 0.112506E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116990E+10 |
March | 0.163685E+10 | 0.124786E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108357E+10 |
April | 0.145243E+10 | 0.105552E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.782944E+09 |
May | 0.157338E+10 | 0.109912E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1821537.58 | 0.798886E+09 |
June | 0.156900E+10 | 0.107105E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9409149.26 | 0.406145E+09 |
July | 0.145680E+10 | 0.101839E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32249071.38 | 0.273873E+09 |
August | 0.163685E+10 | 0.114716E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27671288.58 | 0.296775E+09 |
September | 0.145243E+10 | 0.108421E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17653260.58 | 0.522128E+09 |
October | 0.150991E+10 | 0.120717E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 382569.89 | 0.747247E+09 |
November | 0.149516E+10 | 0.132293E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105334E+10 |
December | 0.145680E+10 | 0.137593E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132619E+10 |
Annual Sum or Average | 0.181194E+11 | 0.141655E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 89186877.28 | 0.996495E+10 |
Minimum of Months | 0.136985E+10 | 0.101839E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273873E+09 |
Maximum of Months | 0.163685E+10 | 0.141106E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32249071.38 | 0.150395E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.875600E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101382E+10 |
February | 0.649041E+09 | 0.710173E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.802868E+09 |
March | 0.773965E+09 | 0.794829E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738512E+09 |
April | 0.688021E+09 | 0.676798E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537679E+09 |
May | 0.744847E+09 | 0.710233E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1312617.84 | 0.530026E+09 |
June | 0.742030E+09 | 0.696834E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6431041.47 | 0.272698E+09 |
July | 0.690839E+09 | 0.658171E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21258821.21 | 0.186184E+09 |
August | 0.773965E+09 | 0.742352E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18298852.58 | 0.199854E+09 |
September | 0.688021E+09 | 0.693834E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11411080.81 | 0.355008E+09 |
October | 0.715730E+09 | 0.758802E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68262.63 | 0.515243E+09 |
November | 0.708685E+09 | 0.829060E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.709970E+09 |
December | 0.690839E+09 | 0.853092E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.895380E+09 |
Annual Sum or Average | 0.858171E+10 | 0.899978E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58780676.54 | 0.675724E+10 |
Minimum of Months | 0.649041E+09 | 0.658171E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186184E+09 |
Maximum of Months | 0.773965E+09 | 0.875600E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21258821.21 | 0.101382E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.133024E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159650E+10 |
February | 0.136988E+10 | 0.107910E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130270E+10 |
March | 0.163688E+10 | 0.123054E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116131E+10 |
April | 0.145246E+10 | 0.105669E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.833748E+09 |
May | 0.157341E+10 | 0.110528E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1814682.06 | 0.814200E+09 |
June | 0.156904E+10 | 0.108088E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9299072.21 | 0.407926E+09 |
July | 0.145684E+10 | 0.102485E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29648122.04 | 0.279388E+09 |
August | 0.163688E+10 | 0.115503E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25725958.07 | 0.309278E+09 |
September | 0.145246E+10 | 0.107902E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14246869.45 | 0.557326E+09 |
October | 0.150994E+10 | 0.116597E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19685.49 | 0.841029E+09 |
November | 0.149520E+10 | 0.124780E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114868E+10 |
December | 0.145684E+10 | 0.128233E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144342E+10 |
Annual Sum or Average | 0.181198E+11 | 0.138377E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 80754389.32 | 0.106955E+11 |
Minimum of Months | 0.136988E+10 | 0.102485E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279388E+09 |
Maximum of Months | 0.163688E+10 | 0.133024E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29648122.04 | 0.159650E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.886074E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102526E+10 |
February | 0.882782E+09 | 0.709355E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.818432E+09 |
March | 0.105485E+10 | 0.800462E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.750622E+09 |
April | 0.936002E+09 | 0.683426E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557205E+09 |
May | 0.101394E+10 | 0.710371E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1181266.88 | 0.560934E+09 |
June | 0.101113E+10 | 0.690759E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6142980.10 | 0.284404E+09 |
July | 0.938820E+09 | 0.658373E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20551053.02 | 0.199968E+09 |
August | 0.105485E+10 | 0.741789E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18060208.10 | 0.209804E+09 |
September | 0.936002E+09 | 0.698297E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11535486.99 | 0.362684E+09 |
October | 0.973041E+09 | 0.769016E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98377.81 | 0.523766E+09 |
November | 0.963541E+09 | 0.823878E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.727193E+09 |
December | 0.938820E+09 | 0.853827E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.914607E+09 |
Annual Sum or Average | 0.116768E+11 | 0.902562E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57569372.91 | 0.693488E+10 |
Minimum of Months | 0.882782E+09 | 0.658373E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199968E+09 |
Maximum of Months | 0.105485E+10 | 0.886074E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20551053.02 | 0.102526E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.141065E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179730E+10 |
February | 0.136985E+10 | 0.112496E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135115E+10 |
March | 0.163685E+10 | 0.124771E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126769E+10 |
April | 0.145243E+10 | 0.105537E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.898829E+09 |
May | 0.157338E+10 | 0.109900E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2116125.82 | 0.939834E+09 |
June | 0.156900E+10 | 0.107103E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11230503.56 | 0.493018E+09 |
July | 0.145680E+10 | 0.101836E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38555428.85 | 0.335424E+09 |
August | 0.163685E+10 | 0.114714E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33428961.29 | 0.358730E+09 |
September | 0.145243E+10 | 0.108416E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20827410.18 | 0.610054E+09 |
October | 0.150991E+10 | 0.120695E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1541867.71 | 0.831702E+09 |
November | 0.149516E+10 | 0.132285E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120710E+10 |
December | 0.145680E+10 | 0.137559E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156850E+10 |
Annual Sum or Average | 0.181194E+11 | 0.141638E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107700E+09 | 0.116593E+11 |
Minimum of Months | 0.136985E+10 | 0.101836E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335424E+09 |
Maximum of Months | 0.163685E+10 | 0.141065E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38555428.85 | 0.179730E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.875600E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121138E+10 |
February | 0.882782E+09 | 0.710097E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.931367E+09 |
March | 0.105485E+10 | 0.794729E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.870198E+09 |
April | 0.936002E+09 | 0.676798E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.627253E+09 |
May | 0.101394E+10 | 0.710201E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1506590.46 | 0.629465E+09 |
June | 0.101113E+10 | 0.696816E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7614600.59 | 0.334433E+09 |
July | 0.938820E+09 | 0.658171E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25030801.30 | 0.230222E+09 |
August | 0.105485E+10 | 0.742326E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22153033.74 | 0.244261E+09 |
September | 0.936002E+09 | 0.693812E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13356132.29 | 0.422289E+09 |
October | 0.973041E+09 | 0.758953E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108460.33 | 0.583813E+09 |
November | 0.963541E+09 | 0.829399E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.815941E+09 |
December | 0.938820E+09 | 0.853092E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105380E+10 |
Annual Sum or Average | 0.116768E+11 | 0.900000E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 69769618.71 | 0.795443E+10 |
Minimum of Months | 0.882782E+09 | 0.658171E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230222E+09 |
Maximum of Months | 0.105485E+10 | 0.875600E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25030801.30 | 0.121138E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.133018E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188619E+10 |
February | 0.136988E+10 | 0.107910E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151953E+10 |
March | 0.163688E+10 | 0.123052E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136797E+10 |
April | 0.145246E+10 | 0.105665E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.971529E+09 |
May | 0.157341E+10 | 0.110528E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2119176.74 | 0.961944E+09 |
June | 0.156904E+10 | 0.108088E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11104057.55 | 0.495076E+09 |
July | 0.145684E+10 | 0.102483E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35625340.32 | 0.341621E+09 |
August | 0.163688E+10 | 0.115501E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31107303.10 | 0.374962E+09 |
September | 0.145246E+10 | 0.107897E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17134249.62 | 0.659833E+09 |
October | 0.150994E+10 | 0.116597E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39301.70 | 0.963295E+09 |
November | 0.149520E+10 | 0.124780E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131642E+10 |
December | 0.145684E+10 | 0.128216E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166861E+10 |
Annual Sum or Average | 0.181198E+11 | 0.138373E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97129429.03 | 0.125270E+11 |
Minimum of Months | 0.136988E+10 | 0.102483E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341621E+09 |
Maximum of Months | 0.163688E+10 | 0.133018E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35625340.32 | 0.188619E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.885965E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122233E+10 |
February | 0.882782E+09 | 0.709307E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.961795E+09 |
March | 0.105485E+10 | 0.800423E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.890740E+09 |
April | 0.936002E+09 | 0.683426E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.654372E+09 |
May | 0.101394E+10 | 0.710353E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1382285.78 | 0.667349E+09 |
June | 0.101113E+10 | 0.690748E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7414712.97 | 0.346344E+09 |
July | 0.938820E+09 | 0.658366E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25072647.30 | 0.245075E+09 |
August | 0.105485E+10 | 0.741789E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22064578.13 | 0.254987E+09 |
September | 0.936002E+09 | 0.698219E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13902603.12 | 0.430825E+09 |
October | 0.973041E+09 | 0.769007E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 229587.96 | 0.602600E+09 |
November | 0.963541E+09 | 0.823839E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.845518E+09 |
December | 0.938820E+09 | 0.853788E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107673E+10 |
Annual Sum or Average | 0.116768E+11 | 0.902523E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 70066415.26 | 0.819867E+10 |
Minimum of Months | 0.882782E+09 | 0.658366E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245075E+09 |
Maximum of Months | 0.105485E+10 | 0.885965E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25072647.30 | 0.122233E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.522764E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.474186E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.563465E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.503289E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.543115E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.540489E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.505915E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.563465E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.503289E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.522764E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.516637E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.505915E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.626529E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.474186E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.563465E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151321E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121598E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108960E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.788268E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1280633.13 | 0.766949E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6620660.33 | 0.379531E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23984576.42 | 0.258954E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21407687.58 | 0.282599E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13706997.59 | 0.514546E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17102.40 | 0.776940E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110259E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140606E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67017657.45 | 0.100952E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258954E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23984576.42 | 0.151321E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253758E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203089E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185999E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134743E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2371854.40 | 0.133594E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12238010.27 | 0.664138E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47919956.17 | 0.445678E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40268088.44 | 0.494646E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27161309.96 | 0.899301E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33431.64 | 0.132121E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185466E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232696E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129993E+09 | 0.171184E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.445678E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47919956.17 | 0.253758E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266169E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209430E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196635E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142496E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1519211.50 | 0.145874E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10329240.81 | 0.756717E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41575523.41 | 0.510058E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38273591.13 | 0.554562E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23016973.11 | 0.966145E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134113E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186657E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235817E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114715E+09 | 0.179594E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510058E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41575523.41 | 0.266169E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 19402.09 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 19402.09 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 19402.09 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 19402.09 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 19402.09 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 19402.09 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 19402.09 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 19402.09 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 19402.09 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 19402.09 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 19402.09 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 19402.09 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 19402.09 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 19402.09 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2187.81 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1131.13 | 05-JAN-22:01 |
February | 2010.79 | 01-FEB-10:09 | 1906.53 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 727.12 | 17-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 2187.81 | 17-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 879.50 | 02-MAR-23:00 |
April | 2010.79 | 03-APR-09:09 | 1625.25 | 14-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 626.96 | 27-APR-02:00 |
May | 2010.79 | 01-MAY-09:09 | 1524.25 | 03-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.92 | 20-MAY-17:02 | 1212.83 | 22-MAY-04:00 |
June | 2010.79 | 01-JUN-09:09 | 1141.96 | 16-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.46 | 29-JUN-15:00 | 504.01 | 14-JUN-02:00 |
July | 2010.79 | 03-JUL-09:09 | 1242.97 | 07-JUL-07:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.81 | 30-JUL-12:06 | 304.27 | 05-JUL-01:00 |
August | 2010.79 | 01-AUG-09:09 | 1242.97 | 17-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.64 | 06-AUG-17:24 | 386.62 | 23-AUG-03:00 |
September | 2010.79 | 01-SEP-09:09 | 1906.53 | 11-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.29 | 03-SEP-12:56 | 674.68 | 12-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 2187.81 | 25-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.39 | 18-OCT-13:55 | 578.94 | 30-OCT-22:00 |
November | 2010.79 | 01-NOV-09:09 | 2187.81 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 686.11 | 28-NOV-05:58 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1088.01 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.27 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 170.29 | 1212.83 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 753.80 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 1228.64 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 475.64 | 17-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 1409.91 | 17-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 574.95 | 02-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 982.28 | 14-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 409.35 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 801.02 | 03-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.28 | 20-MAY-17:20 | 797.26 | 22-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 670.83 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.31 | 29-JUN-15:00 | 327.05 | 14-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 735.93 | 07-JUL-07:19 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.37 | 30-JUL-12:08 | 195.74 | 05-JUL-01:00 |
August | 1295.83 | 01-AUG-09:09 | 735.93 | 17-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.28 | 06-AUG-17:41 | 248.62 | 23-AUG-03:00 |
September | 1295.83 | 01-SEP-09:09 | 982.28 | 13-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.91 | 03-SEP-13:00 | 442.59 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 25-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.60 | 18-OCT-13:55 | 383.26 | 08-OCT-08:40 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 454.55 | 26-NOV-19:52 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 702.24 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.74 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 120.91 | 797.26 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2187.86 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1130.43 | 05-JAN-22:01 |
February | 2010.83 | 01-FEB-10:09 | 1906.57 | 02-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 755.68 | 19-FEB-12:00 |
March | 2010.83 | 01-MAR-10:09 | 2187.86 | 17-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 892.25 | 02-MAR-23:00 |
April | 2010.83 | 03-APR-09:09 | 1625.29 | 14-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 619.62 | 27-APR-02:00 |
May | 2010.83 | 01-MAY-09:09 | 1524.28 | 03-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.58 | 20-MAY-17:02 | 1180.41 | 22-MAY-04:00 |
June | 2010.83 | 01-JUN-09:09 | 1141.99 | 16-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.46 | 29-JUN-15:00 | 495.18 | 14-JUN-02:00 |
July | 2010.83 | 03-JUL-09:09 | 1243.00 | 07-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.35 | 30-JUL-12:06 | 297.34 | 05-JUL-01:00 |
August | 2010.83 | 01-AUG-09:09 | 1243.00 | 17-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.79 | 06-AUG-17:24 | 385.25 | 23-AUG-03:00 |
September | 2010.83 | 01-SEP-09:09 | 1524.28 | 11-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.06 | 03-SEP-13:00 | 657.36 | 12-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 2187.86 | 25-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.16 | 18-OCT-15:00 | 611.65 | 08-OCT-15:00 |
November | 2010.83 | 01-NOV-09:09 | 2187.86 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 691.14 | 26-NOV-13:43 |
December | 2010.83 | 01-DEC-10:09 | 2187.86 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1050.88 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1141.99 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.34 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 158.06 | 1180.41 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 754.91 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 517.33 | 17-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 1409.91 | 17-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 626.62 | 02-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 1228.64 | 14-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 458.08 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 982.28 | 03-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.84 | 20-MAY-17:02 | 821.93 | 22-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 735.93 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.31 | 29-JUN-15:00 | 366.20 | 14-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 801.02 | 07-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.82 | 30-JUL-12:08 | 226.28 | 05-JUL-01:00 |
August | 1295.83 | 01-AUG-09:09 | 982.28 | 17-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.23 | 06-AUG-17:24 | 299.64 | 23-AUG-03:00 |
September | 1295.83 | 01-SEP-09:09 | 1228.64 | 11-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.96 | 03-SEP-13:00 | 465.50 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 25-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.60 | 18-OCT-13:55 | 419.21 | 08-OCT-15:00 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 486.50 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 794.28 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 735.93 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.28 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 123.96 | 821.93 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2187.81 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2648.09 | 05-JAN-22:01 |
February | 2010.79 | 01-FEB-10:09 | 1906.53 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1483.72 | 17-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 2187.81 | 17-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1916.66 | 02-MAR-23:00 |
April | 2010.79 | 03-APR-09:09 | 1524.25 | 14-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1350.64 | 27-APR-02:00 |
May | 2010.79 | 01-MAY-09:09 | 1524.25 | 03-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.40 | 20-MAY-17:02 | 2569.25 | 22-MAY-04:00 |
June | 2010.79 | 01-JUN-09:09 | 1141.96 | 26-JUN-11:30 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.97 | 29-JUN-15:00 | 1093.51 | 14-JUN-02:00 |
July | 2010.79 | 03-JUL-09:09 | 1242.97 | 07-JUL-07:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 263.24 | 30-JUL-12:10 | 647.21 | 05-JUL-01:00 |
August | 2010.79 | 01-AUG-09:09 | 1242.97 | 17-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 339.76 | 06-AUG-18:00 | 805.29 | 23-AUG-03:00 |
September | 2010.79 | 01-SEP-09:09 | 1805.53 | 11-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 399.15 | 03-SEP-13:00 | 1432.32 | 12-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 2187.81 | 25-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.12 | 15-OCT-14:10 | 1212.88 | 30-OCT-22:00 |
November | 2010.79 | 01-NOV-09:09 | 2187.81 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1588.08 | 28-NOV-05:47 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2269.48 | 01-DEC-05:08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 647.21 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 399.15 | 2648.09 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1409.91 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1765.38 | 05-JAN-22:01 |
February | 1239.33 | 01-FEB-08:09 | 1228.64 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 988.51 | 17-FEB-04:00 |
March | 1239.33 | 01-MAR-08:09 | 1409.91 | 17-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1273.18 | 02-MAR-23:00 |
April | 1239.33 | 03-APR-07:10 | 982.28 | 14-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 900.55 | 27-APR-02:00 |
May | 1239.33 | 01-MAY-07:10 | 801.02 | 03-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.84 | 20-MAY-17:02 | 1707.36 | 22-MAY-04:00 |
June | 1239.33 | 01-JUN-07:10 | 670.83 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.65 | 29-JUN-15:00 | 723.86 | 04-JUN-14:00 |
July | 1239.33 | 03-JUL-07:10 | 735.93 | 07-JUL-07:19 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.22 | 30-JUL-12:06 | 428.31 | 05-JUL-01:00 |
August | 1239.33 | 01-AUG-07:10 | 735.93 | 17-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.86 | 06-AUG-17:55 | 535.40 | 23-AUG-03:00 |
September | 1239.33 | 01-SEP-07:10 | 982.28 | 13-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 263.00 | 03-SEP-12:51 | 937.82 | 12-SEP-03:00 |
October | 1239.33 | 02-OCT-07:10 | 1409.91 | 25-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.98 | 18-OCT-13:55 | 808.21 | 30-OCT-22:00 |
November | 1239.33 | 01-NOV-07:10 | 1409.91 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1058.75 | 28-NOV-05:43 |
December | 1239.33 | 01-DEC-08:09 | 1409.91 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1530.69 | 01-DEC-05:04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 428.31 | |||||
Maximum of Months | 1239.33 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 263.00 | 1765.38 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2187.86 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2649.51 | 05-JAN-22:01 |
February | 2010.83 | 01-FEB-10:09 | 1805.57 | 02-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1769.51 | 19-FEB-12:30 |
March | 2010.83 | 01-MAR-10:09 | 2187.86 | 17-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2004.77 | 02-MAR-23:00 |
April | 2010.83 | 03-APR-09:09 | 1524.28 | 14-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1364.75 | 27-APR-02:00 |
May | 2010.83 | 01-MAY-09:09 | 1524.28 | 03-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.98 | 20-MAY-17:02 | 2582.88 | 22-MAY-04:00 |
June | 2010.83 | 01-JUN-09:09 | 1141.99 | 16-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.97 | 29-JUN-15:00 | 1086.18 | 14-JUN-02:00 |
July | 2010.83 | 03-JUL-09:09 | 1243.00 | 07-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 279.54 | 30-JUL-12:06 | 652.81 | 05-JUL-01:00 |
August | 2010.83 | 01-AUG-09:09 | 1243.00 | 17-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 333.10 | 06-AUG-17:55 | 827.32 | 23-AUG-03:00 |
September | 2010.83 | 01-SEP-09:09 | 1524.28 | 11-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 364.56 | 03-SEP-13:00 | 1429.07 | 12-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 2187.86 | 25-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.61 | 18-OCT-15:40 | 1422.67 | 08-OCT-15:00 |
November | 2010.83 | 01-NOV-09:09 | 2187.86 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1588.09 | 28-NOV-05:43 |
December | 2010.83 | 01-DEC-10:09 | 2187.86 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2288.49 | 01-DEC-05:04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1141.99 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 652.81 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 364.56 | 2649.51 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1765.66 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1018.15 | 17-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 1409.91 | 17-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1319.14 | 02-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 1228.64 | 14-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 919.11 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 982.28 | 03-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.74 | 20-MAY-17:02 | 1715.65 | 22-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 735.93 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.65 | 29-JUN-15:00 | 747.29 | 14-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 801.02 | 07-JUL-07:19 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.83 | 30-JUL-12:10 | 465.58 | 05-JUL-01:00 |
August | 1295.83 | 01-AUG-09:09 | 982.28 | 17-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 247.31 | 06-AUG-12:00 | 560.09 | 23-AUG-03:00 |
September | 1295.83 | 01-SEP-09:09 | 1228.64 | 11-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 289.19 | 03-SEP-12:53 | 942.21 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 25-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.02 | 15-OCT-12:50 | 833.40 | 30-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1058.74 | 28-NOV-05:50 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1513.25 | 01-DEC-05:04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 735.93 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 465.58 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 289.19 | 1765.66 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2187.81 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3283.92 | 05-JAN-22:01 |
February | 2010.79 | 01-FEB-10:09 | 1906.53 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1808.96 | 08-FEB-22:02 |
March | 2010.79 | 01-MAR-10:09 | 2187.81 | 17-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2278.00 | 02-MAR-23:00 |
April | 2010.79 | 03-APR-09:09 | 1524.25 | 14-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1573.10 | 27-APR-02:00 |
May | 2010.79 | 01-MAY-09:09 | 1524.25 | 03-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.41 | 20-MAY-17:02 | 3196.52 | 22-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 1141.96 | 26-JUN-11:30 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.87 | 29-JUN-15:00 | 1285.88 | 14-JUN-02:00 |
July | 2010.79 | 03-JUL-09:09 | 1242.97 | 07-JUL-07:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 342.79 | 30-JUL-11:52 | 758.58 | 05-JUL-01:00 |
August | 2010.79 | 01-AUG-09:09 | 1242.97 | 17-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 414.29 | 06-AUG-17:26 | 944.05 | 22-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 1805.53 | 11-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 477.64 | 03-SEP-12:51 | 1611.59 | 12-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 2187.81 | 25-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.24 | 15-OCT-13:51 | 1438.02 | 30-OCT-21:03 |
November | 2010.79 | 01-NOV-09:09 | 2187.81 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1988.88 | 28-NOV-06:00 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2834.06 | 01-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 758.58 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 477.64 | 3283.92 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2189.31 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 1228.64 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1205.64 | 17-FEB-05:47 |
March | 1295.83 | 01-MAR-10:09 | 1409.91 | 17-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1519.24 | 02-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 982.28 | 14-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1053.32 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 801.02 | 03-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.79 | 20-MAY-17:02 | 2151.04 | 22-MAY-04:45 |
June | 1295.83 | 01-JUN-09:09 | 670.83 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.58 | 29-JUN-15:00 | 881.82 | 04-JUN-14:00 |
July | 1295.83 | 03-JUL-09:09 | 735.93 | 07-JUL-07:19 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.75 | 30-JUL-15:00 | 504.14 | 05-JUL-01:00 |
August | 1295.83 | 01-AUG-09:09 | 735.93 | 17-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 287.44 | 06-AUG-17:40 | 623.00 | 22-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 982.28 | 13-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 319.09 | 03-SEP-12:51 | 1057.53 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 25-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.92 | 15-OCT-14:10 | 960.60 | 30-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1326.98 | 28-NOV-05:52 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-08:09 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1889.38 | 01-DEC-05:09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.14 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 319.09 | 2189.31 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2187.86 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3285.90 | 05-JAN-22:01 |
February | 2010.83 | 01-FEB-10:09 | 1805.57 | 02-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2000.36 | 19-FEB-12:40 |
March | 2010.83 | 01-MAR-10:09 | 2187.86 | 17-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2388.22 | 02-MAR-23:00 |
April | 2010.83 | 03-APR-09:09 | 1524.28 | 14-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1594.29 | 27-APR-02:00 |
May | 2010.83 | 01-MAY-09:09 | 1524.28 | 03-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.55 | 20-MAY-17:02 | 3207.36 | 22-MAY-04:45 |
June | 2010.83 | 01-JUN-09:09 | 1141.99 | 16-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.87 | 29-JUN-15:00 | 1277.47 | 04-JUN-14:00 |
July | 2010.83 | 03-JUL-09:09 | 1243.00 | 07-JUL-07:30 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 309.58 | 30-JUL-11:52 | 766.98 | 05-JUL-01:00 |
August | 2010.83 | 01-AUG-09:09 | 1243.00 | 17-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 420.24 | 06-AUG-17:24 | 967.04 | 22-AUG-24:00 |
September | 2010.83 | 01-SEP-09:09 | 1524.28 | 11-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 445.03 | 03-SEP-13:00 | 1603.76 | 12-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 2187.86 | 25-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.26 | 18-OCT-15:10 | 1564.77 | 08-OCT-15:00 |
November | 2010.83 | 01-NOV-09:09 | 2187.86 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1990.46 | 28-NOV-06:00 |
December | 2010.83 | 01-DEC-10:09 | 2187.86 | 01-DEC-08:09 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2835.57 | 01-DEC-05:04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1141.99 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 766.98 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 445.03 | 3285.90 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2190.22 | 05-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1209.47 | 08-FEB-22:02 |
March | 1295.83 | 01-MAR-10:09 | 1409.91 | 17-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1581.45 | 02-MAR-23:00 |
April | 1295.83 | 03-APR-09:09 | 1228.64 | 14-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1076.36 | 27-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 982.28 | 03-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.86 | 20-MAY-17:02 | 2152.26 | 22-MAY-04:45 |
June | 1295.83 | 01-JUN-09:09 | 735.93 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.58 | 29-JUN-15:00 | 882.26 | 14-JUN-02:00 |
July | 1295.83 | 03-JUL-09:09 | 801.02 | 07-JUL-07:19 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 290.74 | 30-JUL-11:52 | 552.80 | 05-JUL-01:00 |
August | 1295.83 | 01-AUG-09:09 | 982.28 | 17-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 300.11 | 06-AUG-12:10 | 656.47 | 22-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 1228.64 | 11-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 351.83 | 03-SEP-12:51 | 1070.24 | 12-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 25-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.54 | 15-OCT-12:50 | 976.28 | 30-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1326.95 | 28-NOV-05:54 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1889.39 | 01-DEC-05:09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 735.93 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 552.80 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 351.83 | 2190.22 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 5470.56 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 5470.56 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 5470.56 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 5470.56 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 5470.56 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 5470.56 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 5470.56 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 5470.56 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 5470.56 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 5470.56 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 5470.56 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 5470.56 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 5470.56 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2352.60 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1592.30 | 17-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1874.75 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1335.35 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.71 | 20-MAY-17:02 | 2665.14 | 22-MAY-04:03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.30 | 29-JUN-15:00 | 1065.12 | 14-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.97 | 30-JUL-11:52 | 627.52 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.56 | 06-AUG-17:51 | 816.91 | 23-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.26 | 03-SEP-13:00 | 1459.08 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.66 | 18-OCT-15:00 | 1235.87 | 30-OCT-23:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1500.76 | 26-NOV-19:52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2374.15 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 627.52 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.26 | 2665.14 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4150.53 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2718.49 | 17-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3291.05 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2340.99 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.31 | 20-MAY-17:02 | 4688.95 | 22-MAY-04:01 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.11 | 29-JUN-15:00 | 1868.08 | 14-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 492.11 | 30-JUL-11:52 | 1083.35 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 552.94 | 06-AUG-18:00 | 1412.00 | 23-AUG-03:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 634.61 | 03-SEP-13:00 | 2555.97 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.63 | 18-OCT-15:00 | 2119.85 | 30-OCT-22:30 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2520.58 | 26-NOV-19:52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3908.81 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1083.35 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 634.61 | 4688.95 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4650.75 | 05-JAN-22:01 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2646.22 | 17-FEB-04:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3591.91 | 02-MAR-23:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2476.73 | 27-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.50 | 20-MAY-17:02 | 4807.32 | 22-MAY-04:10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.56 | 29-JUN-15:00 | 1965.12 | 14-JUN-02:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 472.44 | 30-JUL-11:52 | 1156.40 | 05-JUL-01:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 523.36 | 06-AUG-17:50 | 1457.10 | 22-AUG-21:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 574.56 | 03-SEP-13:00 | 2576.68 | 12-SEP-03:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2211.71 | 30-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2638.57 | 28-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3899.78 | 01-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1156.40 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 574.56 | 4807.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 118238.32 | 02-JAN-07:05 | 7180.90 | 12934.72 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 110700.36 | 21-FEB-07:11 | 28723.60 | 51738.90 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 103254.49 | 23-MAR-06:12 | 21542.70 | 38804.17 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 109607.34 | 17-APR-06:11 | 28723.60 | 51738.90 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 110158.51 | 15-MAY-06:11 | 28723.60 | 51738.90 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 113271.89 | 07-JUN-06:11 | 32314.05 | 58206.26 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 125874.13 | 21-JUL-06:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 116918.59 | 14-AUG-06:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 114505.47 | 01-SEP-21:01 | 6283.29 | 15091.07 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 114287.56 | 23-OCT-06:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 109636.73 | 13-NOV-07:03 | 10771.35 | 19402.09 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 106105.36 | 26-DEC-07:03 | 10771.35 | 19402.09 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 103254.49 | 6283.29 | 12934.72 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 125874.13 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 94122.77 | 02-JAN-04:01 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 87150.88 | 27-FEB-05:11 | 0.00 | 4836.24 | 53438.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 86493.04 | 20-MAR-04:01 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 92248.23 | 10-APR-04:11 | 0.00 | 4298.88 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 92895.19 | 30-MAY-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 96927.03 | 22-JUN-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 96317.23 | 05-JUL-04:11 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 91737.60 | 22-AUG-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 95401.75 | 01-SEP-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 90590.19 | 02-OCT-04:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 88282.83 | 06-NOV-04:03 | 0.00 | 2149.44 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 86471.61 | 07-DEC-05:01 | 0.00 | 4298.88 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 86471.61 | 0.00 | 2149.44 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 96927.03 | 0.00 | 4836.24 | 53438.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 21475.77 | 19-JAN-16:57 | 45948.79 | 52273.31 | 51619.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 51402.80 | 28-FEB-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 72136.04 | 30-MAR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 78615.59 | 26-APR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 79486.97 | 30-MAY-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 82453.74 | 22-JUN-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 82483.42 | 27-JUL-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 81926.28 | 14-AUG-04:12 | 0.00 | 2149.44 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 82980.13 | 11-SEP-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 78468.44 | 20-OCT-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 72229.41 | 04-NOV-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 28974.57 | 07-DEC-16:20 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 21475.77 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 82980.13 | 45948.79 | 52273.31 | 51619.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17323.75 | 13-JAN-17:00 | 30632.53 | 34848.87 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 24549.51 | 28-FEB-17:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 29240.02 | 29-MAR-16:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 41015.57 | 25-APR-16:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 74909.64 | 20-MAY-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 80326.48 | 21-JUN-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 79215.78 | 27-JUL-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 79396.37 | 08-AUG-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 77503.39 | 08-SEP-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 38730.56 | 18-OCT-16:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 26477.80 | 03-NOV-16:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19015.40 | 06-DEC-17:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 17323.75 | 0.00 | 2686.80 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 80326.48 | 30632.53 | 34848.87 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2853.10 | 01-JAN-13:42 | 506.08 | 289.13 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 326.34 |
February | 4487.75 | 27-FEB-16:00 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.80 |
March | 5208.20 | 27-MAR-14:00 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.57 |
April | 7602.46 | 07-APR-14:00 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.53 |
May | 12494.25 | 30-MAY-04:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.78 |
June | 13713.51 | 26-JUN-04:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.77 |
July | 16784.88 | 23-JUL-18:01 | 0.00 | 578.27 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.32 |
August | 16634.09 | 06-AUG-16:01 | 809.73 | 462.61 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 122.37 | 0.00 |
September | 15941.67 | 04-SEP-15:41 | 708.51 | 404.79 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 52.60 | 0.00 |
October | 6201.71 | 19-OCT-14:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.19 |
November | 4410.18 | 24-NOV-14:30 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.09 |
December | 3008.27 | 06-DEC-13:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2853.10 | 0.00 | 289.13 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16784.88 | 2010.79 | 1040.96 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 122.37 | 326.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4009.12 | 17-JAN-10:05 | 2591.66 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.11 |
February | 12752.05 | 26-FEB-10:13 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.41 |
March | 12089.24 | 28-MAR-09:15 | 2591.66 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.89 |
April | 21474.07 | 16-APR-08:42 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.30 |
May | 14720.70 | 19-MAY-08:30 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.74 |
June | 26886.40 | 11-JUN-09:01 | 521.82 | 298.13 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.22 |
July | 27314.86 | 09-JUL-09:51 | 521.82 | 298.13 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.49 |
August | 26516.25 | 06-AUG-08:41 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.54 |
September | 25127.89 | 24-SEP-09:52 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.69 |
October | 13499.39 | 22-OCT-10:22 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.49 |
November | 7711.68 | 06-NOV-09:25 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.09 |
December | 3775.48 | 20-DEC-10:10 | 2591.66 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3775.48 | 260.91 | 149.06 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.54 | |
Maximum of Months | 27314.86 | 2591.66 | 1341.67 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 29216.44 | 01-JAN-13:42 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 400.94 |
February | 35467.99 | 26-FEB-14:11 | 1012.19 | 578.28 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.31 |
March | 29503.80 | 26-MAR-13:32 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 351.74 |
April | 29630.69 | 16-APR-14:02 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.44 |
May | 28202.82 | 29-MAY-13:42 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.51 |
June | 29539.44 | 11-JUN-13:02 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.63 |
July | 30680.08 | 09-JUL-13:12 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.63 |
August | 30686.12 | 06-AUG-13:22 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 89.50 | 0.00 |
September | 32636.68 | 03-SEP-12:51 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 112.61 | 0.00 |
October | 32455.20 | 15-OCT-13:21 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.76 |
November | 29634.84 | 12-NOV-12:42 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.71 |
December | 27148.58 | 17-DEC-13:13 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 647.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 27148.58 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35467.99 | 1012.19 | 578.28 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 112.61 | 647.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6350.76 | 13-JAN-15:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.75 |
February | 26912.88 | 26-FEB-15:31 | 521.82 | 298.13 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.37 |
March | 19707.27 | 12-MAR-15:42 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442.47 |
April | 32441.09 | 16-APR-17:21 | 0.00 | 298.13 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.85 |
May | 31214.34 | 28-MAY-16:51 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.60 |
June | 31508.50 | 18-JUN-17:11 | 0.00 | 260.86 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.55 |
July | 36206.09 | 09-JUL-17:11 | 0.00 | 372.66 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.65 |
August | 32416.80 | 06-AUG-16:41 | 521.82 | 298.13 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 63.82 | 0.00 |
September | 30286.75 | 03-SEP-15:31 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 73.70 | 0.00 |
October | 29514.48 | 15-OCT-15:21 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.59 |
November | 13232.11 | 12-NOV-16:03 | 260.91 | 149.06 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.72 |
December | 10166.02 | 06-DEC-15:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6350.76 | 0.00 | 149.06 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36206.09 | 1239.33 | 670.83 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 73.70 | 442.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1543.24 | 13-JAN-16:50 | 1923.11 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.31 |
February | 2634.59 | 27-FEB-14:20 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.17 |
March | 2742.07 | 23-MAR-13:45 | 4021.58 | 2081.92 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.72 |
April | 5878.10 | 07-APR-14:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.13 |
May | 7704.78 | 19-MAY-16:00 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 80.48 | 0.00 |
June | 12255.41 | 21-JUN-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.41 |
July | 15588.52 | 02-JUL-18:21 | 0.00 | 578.27 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.29 |
August | 15175.94 | 06-AUG-15:51 | 1012.16 | 578.27 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 266.05 | 0.00 |
September | 15392.83 | 04-SEP-11:31 | 809.73 | 462.61 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 176.73 | 0.00 |
October | 4735.41 | 19-OCT-14:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.24 |
November | 2607.30 | 03-NOV-14:20 | 3846.22 | 2081.92 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.10 |
December | 1768.32 | 06-DEC-16:00 | 1923.11 | 1524.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1543.24 | 0.00 | 269.88 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15588.52 | 4021.58 | 2187.81 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 266.05 | 275.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2713.12 | 15-JAN-13:12 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 395.41 |
February | 6329.94 | 28-FEB-10:00 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.86 |
March | 10323.02 | 23-MAR-10:10 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.33 |
April | 19490.53 | 16-APR-09:22 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 443.99 |
May | 15565.24 | 19-MAY-08:50 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.50 |
June | 30409.40 | 25-JUN-08:31 | 587.05 | 335.39 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.16 |
July | 32181.81 | 02-JUL-09:01 | 652.28 | 372.66 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.43 |
August | 32358.47 | 06-AUG-09:11 | 652.28 | 372.66 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.85 |
September | 28670.20 | 04-SEP-08:51 | 521.82 | 298.13 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.87 |
October | 9718.22 | 18-OCT-10:10 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.12 |
November | 5584.20 | 03-NOV-10:10 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.91 |
December | 2549.82 | 20-DEC-10:00 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2549.82 | 326.14 | 186.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.50 | |
Maximum of Months | 32358.47 | 2478.65 | 1341.67 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 443.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 29596.98 | 15-JAN-13:12 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 850.59 |
February | 37623.58 | 26-FEB-14:11 | 1012.19 | 578.28 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 593.15 |
March | 30931.70 | 26-MAR-13:12 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 890.99 |
April | 30711.07 | 16-APR-14:02 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 394.99 |
May | 30380.55 | 14-MAY-13:02 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 852.07 |
June | 29953.77 | 11-JUN-13:12 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.28 |
July | 31494.80 | 02-JUL-13:41 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.00 |
August | 32357.28 | 06-AUG-10:31 | 1012.19 | 578.28 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 54.56 | 0.00 |
September | 37454.04 | 03-SEP-12:41 | 1012.19 | 578.28 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 117.17 | 0.00 |
October | 34122.01 | 15-OCT-13:21 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 404.71 |
November | 32643.10 | 12-NOV-11:51 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 536.23 |
December | 17771.31 | 12-DEC-12:40 | 1058.33 | 1040.98 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.53 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17771.31 | 506.09 | 289.14 | 1920.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 37623.58 | 1058.33 | 1040.98 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 117.17 | 890.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3241.40 | 13-JAN-15:50 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.07 |
February | 13373.08 | 26-FEB-16:52 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.89 |
March | 12471.05 | 28-MAR-17:00 | 391.37 | 372.68 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.41 |
April | 29397.26 | 16-APR-17:21 | 0.00 | 298.13 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.82 |
May | 31150.55 | 14-MAY-17:01 | 0.00 | 335.39 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 787.79 |
June | 30116.83 | 25-JUN-18:31 | 0.00 | 298.13 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.01 |
July | 34147.28 | 02-JUL-18:21 | 0.00 | 372.66 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.28 |
August | 32423.62 | 06-AUG-16:31 | 652.28 | 372.66 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 101.99 | 0.00 |
September | 32428.96 | 04-SEP-16:51 | 652.28 | 372.66 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 24.08 | 0.00 |
October | 23128.63 | 15-OCT-16:42 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.49 |
November | 7432.21 | 03-NOV-15:40 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.11 |
December | 4680.70 | 06-DEC-15:40 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3241.40 | 0.00 | 186.33 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34147.28 | 1239.33 | 670.83 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 101.99 | 787.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1504.87 | 13-JAN-16:50 | 1923.11 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.59 |
February | 2424.44 | 27-FEB-13:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.43 |
March | 2623.05 | 23-MAR-13:30 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 310.84 |
April | 5736.30 | 07-APR-14:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.97 |
May | 8461.21 | 19-MAY-16:00 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 96.97 | 0.00 |
June | 13619.69 | 25-JUN-18:41 | 0.00 | 462.61 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.95 |
July | 18005.80 | 02-JUL-18:21 | 0.00 | 578.27 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.30 |
August | 17273.25 | 06-AUG-17:21 | 0.00 | 404.79 | 3914.20 | 0.00 | 0.00 | 0.00 | 0.00 | 380.11 | 0.00 |
September | 17561.37 | 04-SEP-11:31 | 809.73 | 462.61 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 207.97 | 0.00 |
October | 4263.23 | 19-OCT-14:40 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.14 |
November | 2369.60 | 03-NOV-13:30 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.04 |
December | 1662.38 | 06-DEC-16:20 | 1923.11 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 300.62 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1504.87 | 0.00 | 404.79 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18005.80 | 2010.79 | 2187.81 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 380.11 | 310.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2239.61 | 31-JAN-10:35 | 2591.66 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.30 |
February | 4198.29 | 28-FEB-10:20 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.23 |
March | 8856.42 | 23-MAR-10:10 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.72 |
April | 16371.36 | 16-APR-10:23 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.03 |
May | 15128.94 | 19-MAY-08:50 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.24 |
June | 30102.75 | 25-JUN-08:41 | 587.05 | 335.39 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.47 |
July | 32058.34 | 02-JUL-09:01 | 652.28 | 372.66 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.89 |
August | 29082.62 | 06-AUG-09:21 | 521.82 | 298.13 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.20 |
September | 28775.82 | 04-SEP-08:51 | 521.82 | 298.13 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.73 |
October | 8934.08 | 18-OCT-09:40 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.20 |
November | 3778.73 | 03-NOV-10:00 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.11 |
December | 2304.69 | 20-DEC-10:30 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2239.61 | 260.91 | 149.06 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.20 | |
Maximum of Months | 32058.34 | 2591.66 | 1341.67 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26909.50 | 15-JAN-13:41 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 992.40 |
February | 34550.51 | 26-FEB-14:21 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 593.31 |
March | 32443.95 | 26-MAR-14:02 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 991.62 |
April | 29028.46 | 16-APR-13:42 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 475.75 |
May | 31782.27 | 14-MAY-13:02 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1042.52 |
June | 31823.40 | 25-JUN-13:22 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.02 |
July | 33570.50 | 02-JUL-13:41 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.79 |
August | 33864.10 | 06-AUG-13:22 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 243.60 | 0.00 |
September | 39940.18 | 03-SEP-12:41 | 1012.19 | 578.28 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 131.03 | 0.00 |
October | 35314.85 | 15-OCT-13:21 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.73 |
November | 31559.64 | 11-NOV-13:41 | 809.75 | 462.62 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 979.08 |
December | 14530.75 | 12-DEC-14:30 | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14530.75 | 506.09 | 289.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39940.18 | 2010.83 | 1040.98 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 243.60 | 1042.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3270.47 | 13-JAN-15:50 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.73 |
February | 8952.62 | 28-FEB-16:40 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.29 |
March | 12184.13 | 28-MAR-17:00 | 391.37 | 372.68 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.77 |
April | 29483.32 | 22-APR-17:41 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.22 |
May | 32474.27 | 14-MAY-17:01 | 0.00 | 335.39 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 976.20 |
June | 31545.69 | 25-JUN-18:41 | 0.00 | 298.13 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.35 |
July | 35969.30 | 02-JUL-18:21 | 0.00 | 372.66 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.29 |
August | 31288.50 | 06-AUG-16:41 | 521.82 | 298.13 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 179.75 | 0.00 |
September | 34124.07 | 04-SEP-16:51 | 652.28 | 372.66 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 25.65 | 0.00 |
October | 20105.43 | 15-OCT-16:42 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.91 |
November | 6768.75 | 03-NOV-15:40 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.00 |
December | 3950.84 | 06-DEC-15:40 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3270.47 | 0.00 | 223.59 | 773.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35969.30 | 1239.33 | 670.83 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 179.75 | 976.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11842.13 | 06-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1180.20 |
February | 7404.13 | 09-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.92 |
March | 8247.84 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.67 |
April | 6547.57 | 24-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.30 |
May | 9072.11 | 30-MAY-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.73 |
June | 10343.23 | 26-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.29 |
July | 15334.34 | 17-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.91 |
August | 14497.55 | 08-AUG-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.27 |
September | 14562.86 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.99 |
October | 6381.36 | 16-OCT-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.69 |
November | 5820.20 | 06-NOV-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.54 |
December | 6637.23 | 29-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5820.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15334.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1180.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14862.57 | 06-JAN-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2727.40 |
February | 14024.31 | 04-FEB-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1329.26 |
March | 11271.62 | 04-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1295.44 |
April | 8271.94 | 29-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1491.01 |
May | 9559.52 | 08-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1963.07 |
June | 8595.08 | 22-JUN-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.57 | 0.00 |
July | 11331.73 | 25-JUL-16:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.03 | 0.00 |
August | 8779.74 | 10-AUG-12:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.12 | 0.00 |
September | 8584.98 | 05-SEP-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.48 |
October | 8106.00 | 10-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1244.26 |
November | 11627.97 | 27-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2308.93 |
December | 11374.58 | 28-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1613.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8106.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14862.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.12 | 2727.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 436.15 | 14-JAN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.90 |
February | 4421.47 | 26-FEB-14:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509.07 |
March | 5295.85 | 23-MAR-13:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 542.83 |
April | 12143.03 | 25-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.14 |
May | 18849.97 | 19-MAY-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.55 | 0.00 |
June | 21913.59 | 21-JUN-12:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.49 | 0.00 |
July | 25896.23 | 25-JUL-17:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.43 | 0.00 |
August | 22352.59 | 10-AUG-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.55 | 0.00 |
September | 15800.18 | 01-SEP-16:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.71 | 0.00 |
October | 9470.13 | 18-OCT-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.48 |
November | 2319.33 | 03-NOV-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.57 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2397.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25896.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.55 | 2397.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2219.45 | 19-JAN-16:50 | 222.14 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4648.88 | 26-FEB-17:17 | 35.07 | 75.02 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6861.76 | 31-MAR-24:00 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8516.00 | 16-APR-18:16 | 0.00 | 125.04 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3507.24 | 31-MAY-24:00 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5374.97 | 30-JUN-24:00 | 0.00 | 50.02 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7287.68 | 31-JUL-23:50 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8493.98 | 03-AUG-18:50 | 23.38 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3338.72 | 30-SEP-24:00 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4997.57 | 31-OCT-24:00 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6299.93 | 13-NOV-16:30 | 222.14 | 450.11 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8030.04 | 06-DEC-16:10 | 222.14 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2219.45 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8516.00 | 222.14 | 450.11 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1877.88 | 19-JAN-16:50 | 222.14 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4185.43 | 28-FEB-17:00 | 222.14 | 450.11 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6211.03 | 28-MAR-17:50 | 23.38 | 150.04 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8050.87 | 25-APR-18:10 | 23.38 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3312.97 | 31-MAY-24:00 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5260.80 | 30-JUN-24:00 | 0.00 | 50.02 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7049.82 | 31-JUL-23:53 | 0.00 | 100.03 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8165.97 | 03-AUG-18:50 | 23.38 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2959.21 | 30-SEP-23:30 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4307.83 | 15-OCT-17:10 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5715.99 | 06-NOV-16:30 | 222.14 | 450.11 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7370.35 | 06-DEC-16:20 | 222.14 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1877.88 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8165.97 | 222.14 | 450.11 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1589.77 | 13-JAN-16:40 | 222.14 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4098.58 | 28-FEB-17:00 | 222.14 | 450.11 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6175.26 | 28-MAR-17:50 | 23.38 | 150.04 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8107.62 | 25-APR-18:10 | 23.38 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3230.27 | 31-MAY-23:40 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5261.96 | 30-JUN-24:00 | 0.00 | 50.02 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7013.79 | 31-JUL-23:53 | 0.00 | 100.03 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8227.78 | 03-AUG-18:50 | 23.38 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3071.22 | 04-SEP-17:43 | 0.00 | 175.05 | 13640.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4283.22 | 18-OCT-17:00 | 70.15 | 250.06 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5634.18 | 03-NOV-16:00 | 222.14 | 450.11 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7273.13 | 06-DEC-16:20 | 222.14 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1589.77 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8227.78 | 222.14 | 450.11 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 92487.13 | 02-JAN-17:00 | 4808.68 | 5470.56 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 183945.08 | 28-FEB-17:00 | 4808.68 | 5470.56 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357963.40 | 31-MAR-24:00 | 0.00 | 303.90 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 367750.56 | 25-APR-16:00 | 4808.68 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176455.14 | 31-MAY-24:00 | 0.00 | 303.90 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 268457.64 | 30-JUN-23:55 | 0.00 | 607.79 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 361039.99 | 31-JUL-23:53 | 0.00 | 1215.59 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 370592.81 | 07-AUG-16:00 | 4808.68 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 176003.79 | 30-SEP-24:00 | 0.00 | 303.90 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 267901.27 | 31-OCT-24:00 | 0.00 | 303.90 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 276764.97 | 06-NOV-16:55 | 9617.36 | 10941.12 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 368013.10 | 06-DEC-17:00 | 4808.68 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 92487.13 | 0.00 | 303.90 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 370592.81 | 9617.36 | 10941.12 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.173150E+13 | 1255022.98 | 03-JAN-16:49 | 0.104958E+13 | 2312548.53 | 09-JAN-07:19 |
February | 0.195364E+13 | 1470838.62 | 27-FEB-15:00 | 0.544784E+12 | 1501766.72 | 01-FEB-07:19 |
March | 0.255124E+13 | 1536914.99 | 28-MAR-15:00 | 0.322252E+12 | 1548583.20 | 06-MAR-07:19 |
April | 0.277946E+13 | 1962389.50 | 06-APR-15:00 | 0.831303E+11 | 581366.08 | 29-APR-06:10 |
May | 0.182947E+13 | 1600593.97 | 19-MAY-15:30 | 0.492448E+11 | 591143.02 | 08-MAY-04:10 |
June | 0.229952E+13 | 1932063.70 | 22-JUN-10:20 | 0.148492E+10 | 163956.02 | 16-JUN-06:00 |
July | 0.284522E+13 | 2063219.31 | 14-JUL-10:09 | 3319603.89 | 807.54 | 08-JUL-05:19 |
August | 0.332327E+13 | 2232576.78 | 08-AUG-15:39 | 0.276765E+09 | 82848.01 | 18-AUG-05:10 |
September | 0.179994E+13 | 1851188.63 | 07-SEP-14:00 | 0.128528E+11 | 307638.19 | 19-SEP-06:10 |
October | 0.219665E+13 | 1690459.09 | 18-OCT-15:00 | 0.640600E+11 | 677466.27 | 10-OCT-06:30 |
November | 0.243966E+13 | 1614066.51 | 17-NOV-16:00 | 0.266162E+12 | 1303436.79 | 27-NOV-07:19 |
December | 0.281601E+13 | 1679576.40 | 06-DEC-16:40 | 0.668218E+12 | 1685884.69 | 29-DEC-07:00 |
Annual Sum or Average | 0.285656E+14 | 0.306205E+13 | ||||
Minimum of Months | 0.173150E+13 | 1255022.98 | 3319603.89 | 807.54 | ||
Maximum of Months | 0.332327E+13 | 2232576.78 | 0.104958E+13 | 2312548.53 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.276710E+12 | 0.439785E+11 | 0.766053E+12 | 0.213345E+12 | 0.197362E+12 | 0.119625E+11 | 0.00 | 0.973341E+10 | 0.508438E+09 | 0.167958E+12 | 0.00 | 0.438916E+11 | 0.00 |
February | 0.245500E+12 | 0.343652E+11 | 0.978954E+12 | 0.195333E+12 | 0.180090E+12 | 0.131765E+11 | 0.00 | 0.275916E+11 | 0.235003E+10 | 0.235713E+12 | 0.00 | 0.405624E+11 | 0.00 |
March | 0.289508E+12 | 0.309919E+11 | 0.141687E+13 | 0.226058E+12 | 0.208146E+12 | 0.150741E+11 | 0.00 | 0.463408E+11 | 0.319668E+10 | 0.267840E+12 | 0.00 | 0.472083E+11 | 0.00 |
April | 0.256009E+12 | 0.234963E+11 | 0.165903E+13 | 0.211502E+12 | 0.212697E+12 | 0.204779E+11 | 0.00 | 0.806896E+11 | 0.163128E+11 | 0.257941E+12 | 0.00 | 0.413084E+11 | 0.00 |
May | 0.275145E+12 | 0.190970E+11 | 0.774844E+12 | 0.219699E+12 | 0.233020E+12 | 0.275719E+11 | 0.00 | 0.484804E+11 | 0.249986E+11 | 0.164869E+12 | 0.00 | 0.417471E+11 | 0.00 |
June | 0.273214E+12 | 0.165593E+11 | 0.106252E+13 | 0.217934E+12 | 0.287685E+12 | 0.407495E+11 | 0.00 | 0.160350E+12 | 0.611044E+11 | 0.140523E+12 | 0.00 | 0.388871E+11 | 0.00 |
July | 0.255560E+12 | 0.178083E+11 | 0.139340E+13 | 0.213265E+12 | 0.327482E+12 | 0.560437E+11 | 0.00 | 0.331782E+12 | 0.994129E+11 | 0.115292E+12 | 0.00 | 0.351748E+11 | 0.00 |
August | 0.286054E+12 | 0.218398E+11 | 0.173200E+13 | 0.226058E+12 | 0.323981E+12 | 0.528064E+11 | 0.00 | 0.357571E+12 | 0.934312E+11 | 0.191881E+12 | 0.00 | 0.376441E+11 | 0.00 |
September | 0.257005E+12 | 0.269399E+11 | 0.740713E+12 | 0.211501E+12 | 0.245367E+12 | 0.336717E+11 | 0.00 | 0.900565E+11 | 0.471355E+11 | 0.112919E+12 | 0.00 | 0.346320E+11 | 0.00 |
October | 0.269489E+12 | 0.349085E+11 | 0.108340E+13 | 0.213343E+12 | 0.223544E+12 | 0.212497E+11 | 0.00 | 0.505016E+11 | 0.144897E+11 | 0.248380E+12 | 0.00 | 0.373442E+11 | 0.00 |
November | 0.270909E+12 | 0.406352E+11 | 0.135889E+13 | 0.205298E+12 | 0.202448E+12 | 0.141627E+11 | 0.00 | 0.450240E+11 | 0.420581E+10 | 0.259199E+12 | 0.00 | 0.388855E+11 | 0.00 |
December | 0.267638E+12 | 0.459151E+11 | 0.170972E+13 | 0.213269E+12 | 0.197725E+12 | 0.132500E+11 | 0.00 | 0.563847E+11 | 0.323408E+10 | 0.267840E+12 | 0.00 | 0.410300E+11 | 0.00 |
Annual Sum or Average | 0.322274E+13 | 0.356535E+12 | 0.146764E+14 | 0.256661E+13 | 0.283955E+13 | 0.320197E+12 | 0.00 | 0.130451E+13 | 0.370380E+12 | 0.243035E+13 | 0.00 | 0.478315E+12 | 0.00 |
Minimum of Months | 0.245500E+12 | 0.165593E+11 | 0.740713E+12 | 0.195333E+12 | 0.180090E+12 | 0.119625E+11 | 0.00 | 0.973341E+10 | 0.508438E+09 | 0.112919E+12 | 0.00 | 0.346320E+11 | 0.00 |
Maximum of Months | 0.289508E+12 | 0.459151E+11 | 0.173200E+13 | 0.226058E+12 | 0.327482E+12 | 0.560437E+11 | 0.00 | 0.357571E+12 | 0.994129E+11 | 0.267840E+12 | 0.00 | 0.472083E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.104958E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.544784E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.322252E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.831303E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.492448E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.148492E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 3319603.89 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.276765E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.128528E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.640600E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.266162E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.668218E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.306205E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 3319603.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.104958E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 325713.14 | 02-JAN-08:09 | 40855.88 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 233439.18 | 02-JAN-08:20 | 116996.83 | 02-JAN-13:30 | 21939.81 | 25-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 312719.78 | 02-FEB-08:09 | 40855.88 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 233432.22 | 02-FEB-08:20 | 165232.22 | 28-FEB-16:30 | 22184.90 | 27-FEB-14:20 | 0.00 | 01-FEB-00:10 |
March | 325713.14 | 17-MAR-07:10 | 40855.88 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 233439.18 | 17-MAR-07:19 | 173777.19 | 28-MAR-15:00 | 21967.51 | 04-MAR-06:10 | 0.00 | 01-MAR-00:10 |
April | 302682.74 | 14-APR-07:10 | 40855.88 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 233426.85 | 14-APR-07:19 | 243218.30 | 25-APR-15:30 | 23063.16 | 07-APR-13:00 | 0.00 | 01-APR-00:10 |
May | 297349.23 | 03-MAY-07:10 | 40855.88 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 233424.00 | 03-MAY-07:19 | 297638.93 | 19-MAY-12:20 | 50083.38 | 19-MAY-12:20 | 0.00 | 01-MAY-00:10 |
June | 282544.80 | 16-JUN-07:10 | 27558.46 | 01-JUN-20:10 | 541788.89 | 01-JUN-07:10 | 233416.10 | 16-JUN-07:19 | 355156.41 | 20-JUN-12:09 | 50123.96 | 30-JUN-15:00 | 0.00 | 01-JUN-00:10 |
July | 287642.14 | 07-JUL-07:30 | 27558.46 | 01-JUL-20:30 | 660080.29 | 03-JUL-07:10 | 233418.82 | 07-JUL-07:40 | 355156.41 | 11-JUL-13:00 | 50124.52 | 24-JUL-15:09 | 0.00 | 01-JUL-00:10 |
August | 289817.35 | 17-AUG-07:10 | 40855.88 | 03-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 233419.98 | 17-AUG-07:19 | 355156.41 | 09-AUG-13:30 | 50124.23 | 30-AUG-13:00 | 0.00 | 01-AUG-00:10 |
September | 303000.80 | 11-SEP-07:10 | 40855.88 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 233427.02 | 11-SEP-07:19 | 355103.48 | 07-SEP-14:00 | 50204.23 | 07-SEP-14:50 | 0.00 | 01-SEP-00:10 |
October | 325713.14 | 25-OCT-07:10 | 40855.88 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 233439.18 | 25-OCT-07:19 | 202585.46 | 02-OCT-15:39 | 45545.98 | 18-OCT-13:50 | 0.00 | 01-OCT-00:10 |
November | 325713.14 | 01-NOV-07:10 | 40855.88 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 233439.18 | 01-NOV-07:19 | 177987.24 | 03-NOV-15:39 | 22176.96 | 27-NOV-06:10 | 0.00 | 01-NOV-00:10 |
December | 325713.14 | 01-DEC-08:09 | 40855.88 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 233439.18 | 01-DEC-08:20 | 133394.72 | 06-DEC-14:39 | 22149.90 | 26-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 282544.80 | 27558.46 | 423497.50 | 233416.10 | 116996.83 | 21939.81 | 0.00 | |||||||
Maximum of Months | 325713.14 | 40855.88 | 778371.69 | 233439.18 | 355156.41 | 50204.23 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 8625.67 | 13-JAN-16:00 | 902.66 | 13-JAN-15:00 | 100000.00 | 03-JAN-14:39 | 0.00 | 58515.83 | 31-JAN-12:00 | 0.00 |
February | 63309.20 | 27-FEB-15:30 | 49248.27 | 27-FEB-13:50 | 100000.00 | 01-FEB-17:19 | 0.00 | 58670.54 | 17-FEB-12:00 | 0.00 |
March | 34433.15 | 14-MAR-13:30 | 4553.41 | 14-MAR-13:00 | 100000.00 | 01-MAR-05:19 | 0.00 | 58618.75 | 01-MAR-12:00 | 0.00 |
April | 279779.61 | 07-APR-13:00 | 51002.57 | 06-APR-15:00 | 100000.00 | 01-APR-04:30 | 0.00 | 57210.98 | 03-APR-11:00 | 0.00 |
May | 231475.24 | 19-MAY-15:30 | 54899.57 | 19-MAY-16:40 | 100000.00 | 02-MAY-21:19 | 0.00 | 54864.73 | 02-MAY-11:39 | 0.00 |
June | 375203.80 | 21-JUN-12:39 | 82444.89 | 20-JUN-11:09 | 100000.00 | 04-JUN-12:50 | 0.00 | 51691.35 | 01-JUN-11:39 | 0.00 |
July | 415214.85 | 14-JUL-10:09 | 82444.89 | 13-JUL-12:50 | 100000.00 | 07-JUL-18:00 | 0.00 | 47968.90 | 03-JUL-11:50 | 0.00 |
August | 424515.46 | 10-AUG-14:00 | 82444.89 | 05-AUG-13:09 | 100000.00 | 02-AUG-21:10 | 0.00 | 46517.46 | 01-AUG-11:20 | 0.00 |
September | 399424.99 | 07-SEP-14:00 | 82444.89 | 02-SEP-13:30 | 100000.00 | 01-SEP-17:00 | 0.00 | 47484.91 | 29-SEP-11:30 | 0.00 |
October | 238175.68 | 18-OCT-13:50 | 53819.01 | 18-OCT-13:50 | 100000.00 | 02-OCT-21:10 | 0.00 | 50531.09 | 31-OCT-11:00 | 0.00 |
November | 44814.45 | 17-NOV-16:00 | 33037.42 | 17-NOV-16:00 | 100000.00 | 01-NOV-04:19 | 0.00 | 53571.34 | 30-NOV-12:50 | 0.00 |
December | 27195.84 | 10-DEC-01:00 | 4641.34 | 10-DEC-01:00 | 100000.00 | 01-DEC-05:30 | 0.00 | 56256.02 | 29-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 8625.67 | 902.66 | 100000.00 | 0.00 | 46517.46 | 0.00 | ||||
Maximum of Months | 424515.46 | 82444.89 | 100000.00 | 0.00 | 58670.54 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1255022.98 | 03-JAN-16:49 | 325713.14 | 423497.50 | 40855.88 | 233326.38 | 97991.38 | 4174.63 | 0.00 | 7151.47 | 388.41 |
February | 1470838.62 | 27-FEB-15:00 | 280450.63 | 541788.89 | 0.00 | 233151.79 | 155113.57 | 21975.96 | 0.00 | 55471.80 | 49248.27 |
March | 1536914.99 | 28-MAR-15:00 | 280450.63 | 660080.29 | 0.00 | 233302.19 | 173777.19 | 21807.59 | 0.00 | 20445.59 | 2477.65 |
April | 1962389.50 | 06-APR-15:00 | 280450.63 | 778371.69 | 0.00 | 233302.19 | 217504.52 | 22902.82 | 0.00 | 235425.32 | 51002.57 |
May | 1600593.97 | 19-MAY-15:30 | 280450.63 | 423497.50 | 0.00 | 233302.19 | 285260.82 | 48518.35 | 0.00 | 231475.24 | 52806.70 |
June | 1932063.70 | 22-JUN-10:20 | 280450.63 | 541788.89 | 0.00 | 233151.79 | 330166.92 | 49863.64 | 0.00 | 373769.19 | 82444.89 |
July | 2063219.31 | 14-JUL-10:09 | 280450.63 | 660080.29 | 0.00 | 233151.79 | 300517.13 | 48899.91 | 0.00 | 415214.85 | 82444.89 |
August | 2232576.78 | 08-AUG-15:39 | 280450.63 | 778371.69 | 0.00 | 233302.19 | 350437.74 | 49815.34 | 0.00 | 416144.23 | 82444.89 |
September | 1851188.63 | 07-SEP-14:00 | 280450.63 | 423497.50 | 0.00 | 233151.79 | 355103.48 | 50204.23 | 0.00 | 399424.99 | 82444.89 |
October | 1690459.09 | 18-OCT-15:00 | 282443.77 | 541788.89 | 0.00 | 233303.25 | 199592.97 | 41800.83 | 0.00 | 199826.55 | 53819.01 |
November | 1614066.51 | 17-NOV-16:00 | 325713.14 | 660080.29 | 40855.88 | 233326.38 | 114229.47 | 21845.38 | 0.00 | 44814.45 | 33037.42 |
December | 1679576.40 | 06-DEC-16:40 | 325713.14 | 778371.69 | 40855.88 | 233326.38 | 110917.28 | 21806.28 | 0.00 | 24267.71 | 2316.77 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1255022.98 | 280450.63 | 423497.50 | 0.00 | 233151.79 | 97991.38 | 4174.63 | 0.00 | 7151.47 | 388.41 | |
Maximum of Months | 2232576.78 | 325713.14 | 778371.69 | 40855.88 | 233326.38 | 355103.48 | 50204.23 | 0.00 | 416144.23 | 82444.89 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 2312548.53 | 09-JAN-07:19 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 1501766.72 | 01-FEB-07:19 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 1548583.20 | 06-MAR-07:19 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 581366.08 | 29-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 591143.02 | 08-MAY-04:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 163956.02 | 16-JUN-06:00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 807.54 | 08-JUL-05:19 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 82848.01 | 18-AUG-05:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 307638.19 | 19-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 677466.27 | 10-OCT-06:30 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 1303436.79 | 27-NOV-07:19 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 1685884.69 | 29-DEC-07:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 807.54 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 2312548.53 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 70.67 | 27.15 | 37.83 | 27.03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 45.50 | 26.01 | 23.50 | 26.01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 60.00 | 26.16 | 27.33 | 26.17 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 54.67 | 26.31 | 26.00 | 26.32 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 72.33 | 26.60 | 33.83 | 26.57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 133.83 | 27.23 | 90.17 | 27.23 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 420.67 | 28.19 | 271.50 | 28.17 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 269.00 | 27.65 | 162.00 | 27.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 169.67 | 27.64 | 88.17 | 27.59 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 93.17 | 26.94 | 36.83 | 26.91 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 79.17 | 26.77 | 31.50 | 26.74 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 58.83 | 26.28 | 25.83 | 26.28 |
Annual Sum or Average | 0.00 | 0.00 | 1527.50 | 27.39 | 854.50 | 27.40 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 45.50 | 26.01 | 23.50 | 26.01 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 420.67 | 28.19 | 271.50 | 28.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.61 | 0.00 | 25.61 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.60 | 0.00 | 25.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 25.01 | 6.67 | 24.99 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 47.67 | 24.90 | 45.00 | 24.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 25.05 | 16.17 | 25.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 25.07 | 2.67 | 24.91 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.67 | 0.00 | 25.67 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 77.50 | 24.96 | 70.50 | 24.92 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 47.67 | 25.67 | 45.00 | 25.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 24.72 | 4.33 | 24.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 24.73 | 5.50 | 24.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 24.58 | 2.33 | 24.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 19.12 | 0.00 | 19.12 | 12.17 | 24.55 | 12.17 | 24.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 19.12 | 0.00 | 19.12 | 5.50 | 24.73 | 5.50 | 24.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.83 | 18.69 | 1.67 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 |
February | 1.50 | 18.66 | 0.33 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 |
March | 1.33 | 18.61 | 0.33 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.33 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 24.78 | 7.83 | 24.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 24.89 | 12.33 | 24.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 24.90 | 6.50 | 24.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.67 | 18.72 | 0.33 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
December | 3.00 | 18.43 | 0.17 | 18.53 | 0.00 | 18.53 | 0.00 | 18.53 |
Annual Sum or Average | 14.67 | 18.64 | 2.83 | 18.88 | 26.67 | 22.49 | 26.67 | 23.38 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.83 | 19.34 | 1.67 | 19.34 | 12.33 | 24.90 | 12.33 | 24.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 18.77 | 0.50 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 |
February | 0.33 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
March | 0.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 25.10 | 7.83 | 25.08 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 71.83 | 25.33 | 68.83 | 25.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 25.17 | 25.25 | 24.17 | 25.22 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 26.64 | 3.83 | 26.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
Annual Sum or Average | 4.17 | 18.89 | 0.50 | 19.03 | 109.33 | 25.09 | 104.67 | 25.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.33 | 19.43 | 0.50 | 19.43 | 71.83 | 26.64 | 68.83 | 26.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 18.48 | 0.17 | 18.57 | 0.00 | 18.57 | 0.00 | 18.57 |
February | 0.50 | 19.24 | 0.00 | 19.24 | 0.33 | 22.55 | 0.33 | 23.97 |
March | 0.17 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.14 | 1.83 | 28.14 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.01 | 10.83 | 27.01 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 27.00 | 26.65 | 26.50 | 26.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 26.03 | 16.83 | 26.01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.08 | 6.83 | 28.08 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.82 | 1.17 | 27.82 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
Annual Sum or Average | 4.33 | 18.67 | 0.17 | 18.73 | 65.17 | 26.24 | 64.33 | 26.49 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 19.24 | 0.17 | 19.24 | 27.00 | 28.14 | 26.50 | 28.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.83 | 18.32 | 0.17 | 18.39 | 2.00 | 21.67 | 2.00 | 23.30 |
February | 0.67 | 19.24 | 0.00 | 19.24 | 4.50 | 27.10 | 4.50 | 27.65 |
March | 0.33 | 19.12 | 0.00 | 19.12 | 2.00 | 26.93 | 2.00 | 27.53 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.08 | 3.67 | 28.08 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.84 | 1.83 | 27.84 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 14.50 | 25.91 | 14.50 | 25.91 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 53.67 | 25.83 | 51.50 | 25.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 62.83 | 25.73 | 62.00 | 25.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 26.41 | 25.33 | 26.39 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.59 | 6.83 | 27.59 |
November | 0.17 | 19.19 | 0.00 | 19.19 | 3.50 | 27.76 | 3.50 | 27.96 |
December | 0.50 | 19.04 | 0.00 | 19.04 | 2.00 | 26.03 | 2.00 | 26.81 |
Annual Sum or Average | 5.50 | 18.57 | 0.17 | 18.62 | 184.00 | 25.97 | 179.67 | 26.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 21.67 | 1.83 | 23.30 |
Maximum of Months | 3.83 | 19.24 | 0.17 | 19.24 | 62.83 | 28.08 | 62.00 | 28.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.16 | 1.33 | 28.16 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.93 | 1.17 | 27.93 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.32 | 3.17 | 28.41 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.56 | 2.50 | 28.50 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 27.40 | 7.50 | 27.18 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 48.50 | 26.86 | 33.83 | 26.71 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 36.17 | 26.53 | 23.50 | 26.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.30 | 7.33 | 27.21 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.31 | 2.00 | 28.29 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.36 | 0.67 | 27.36 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
Annual Sum or Average | 2.33 | 18.94 | 0.00 | 18.94 | 124.83 | 26.90 | 83.17 | 26.83 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.94 | 0.00 | 18.94 |
Maximum of Months | 2.33 | 18.94 | 0.00 | 18.94 | 48.50 | 28.56 | 33.83 | 28.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 45.17 | 17.11 | 18.17 | 17.39 | 0.00 | 17.39 | 0.00 | 17.39 |
February | 11.83 | 17.08 | 2.50 | 17.14 | 0.00 | 17.14 | 0.00 | 17.14 |
March | 5.67 | 17.84 | 1.33 | 18.27 | 0.00 | 18.27 | 0.00 | 18.27 |
April | 0.17 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
May | 0.17 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 24.94 | 5.83 | 24.94 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 25.07 | 19.17 | 25.05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 25.09 | 11.00 | 25.06 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.38 | 1.00 | 27.38 |
October | 0.17 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
November | 3.83 | 17.99 | 0.50 | 18.23 | 0.00 | 18.23 | 0.00 | 18.23 |
December | 13.67 | 16.91 | 4.50 | 16.82 | 0.00 | 16.82 | 0.00 | 16.82 |
Annual Sum or Average | 80.67 | 17.18 | 27.00 | 17.36 | 37.67 | 19.37 | 37.00 | 20.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.82 | 0.00 | 16.82 |
Maximum of Months | 45.17 | 19.38 | 18.17 | 19.38 | 19.50 | 27.38 | 19.17 | 27.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 22.83 | 15.65 | 3.17 | 15.56 | 0.00 | 15.56 | 0.00 | 15.56 |
February | 8.67 | 16.68 | 0.50 | 16.58 | 0.00 | 16.58 | 0.00 | 16.58 |
March | 3.67 | 16.71 | 0.00 | 16.71 | 0.00 | 16.71 | 0.00 | 16.71 |
April | 0.17 | 19.32 | 0.00 | 19.32 | 1.00 | 27.01 | 1.00 | 27.60 |
May | 0.33 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.10 | 8.67 | 27.30 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 20.67 | 27.17 | 16.17 | 27.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 26.69 | 7.83 | 26.90 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.19 | 6.33 | 28.19 |
October | 0.17 | 19.29 | 0.00 | 19.29 | 0.33 | 24.75 | 0.33 | 25.84 |
November | 2.67 | 17.64 | 0.00 | 17.64 | 0.00 | 17.64 | 0.00 | 17.64 |
December | 10.33 | 16.48 | 2.00 | 16.17 | 0.00 | 16.17 | 0.00 | 16.17 |
Annual Sum or Average | 48.83 | 16.25 | 5.67 | 16.10 | 51.00 | 21.46 | 40.33 | 23.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.56 | 0.00 | 15.56 |
Maximum of Months | 22.83 | 19.33 | 3.17 | 19.33 | 20.67 | 28.19 | 16.17 | 28.19 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 17.00 | 16.14 | 2.00 | 16.03 | 1.50 | 16.92 | 1.50 | 17.68 |
February | 5.17 | 17.34 | 0.50 | 17.13 | 4.83 | 22.21 | 4.83 | 24.08 |
March | 1.67 | 17.94 | 0.00 | 17.94 | 3.50 | 23.89 | 3.50 | 25.03 |
April | 0.17 | 19.39 | 0.00 | 19.39 | 3.33 | 27.67 | 3.33 | 27.88 |
May | 0.17 | 19.33 | 0.00 | 19.33 | 1.67 | 27.14 | 1.67 | 27.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 25.96 | 12.50 | 25.96 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 30.83 | 26.25 | 29.67 | 26.22 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 34.33 | 26.09 | 33.67 | 26.08 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 27.13 | 16.33 | 27.11 |
October | 0.17 | 19.43 | 0.00 | 19.43 | 11.17 | 26.50 | 11.00 | 26.55 |
November | 1.67 | 18.24 | 0.00 | 18.24 | 3.17 | 24.94 | 3.17 | 26.33 |
December | 8.00 | 16.49 | 1.33 | 16.23 | 1.17 | 17.48 | 1.17 | 18.48 |
Annual Sum or Average | 34.00 | 16.64 | 3.83 | 16.47 | 125.50 | 24.24 | 122.33 | 25.23 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 16.92 | 1.17 | 17.68 |
Maximum of Months | 17.00 | 19.43 | 2.00 | 19.43 | 34.33 | 27.67 | 33.67 | 27.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 20.17 | 15.84 | 3.33 | 15.72 | 0.00 | 15.72 | 0.00 | 15.72 |
February | 4.17 | 18.04 | 0.00 | 18.04 | 0.50 | 19.07 | 0.50 | 19.91 |
March | 1.83 | 17.84 | 0.00 | 17.84 | 0.00 | 17.84 | 0.00 | 17.84 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.63 | 0.83 | 28.66 |
May | 0.17 | 19.40 | 0.00 | 19.40 | 4.17 | 28.30 | 1.67 | 28.42 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.51 | 4.83 | 27.23 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 26.67 | 26.91 | 19.83 | 26.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 26.80 | 8.67 | 26.59 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.92 | 3.83 | 27.84 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 28.51 | 0.50 | 28.55 |
November | 1.83 | 18.49 | 0.00 | 18.49 | 0.00 | 18.49 | 0.00 | 18.49 |
December | 8.50 | 16.52 | 1.83 | 16.21 | 0.00 | 16.21 | 0.00 | 16.21 |
Annual Sum or Average | 36.67 | 16.49 | 5.17 | 16.30 | 59.50 | 22.75 | 40.67 | 23.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.72 | 0.00 | 15.72 |
Maximum of Months | 20.17 | 19.40 | 3.33 | 19.40 | 26.67 | 28.63 | 19.83 | 28.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 95.17 | 16.72 | 41.83 | 17.14 | 0.00 | 17.14 | 0.00 | 17.14 |
February | 37.50 | 17.32 | 13.00 | 17.64 | 0.00 | 17.64 | 0.00 | 17.64 |
March | 23.83 | 16.96 | 7.17 | 17.13 | 0.00 | 17.13 | 0.00 | 17.13 |
April | 2.33 | 18.84 | 0.17 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
May | 3.33 | 18.22 | 0.50 | 18.49 | 0.00 | 18.49 | 0.00 | 18.49 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.79 | 5.17 | 24.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 25.44 | 21.67 | 25.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 25.45 | 8.33 | 25.37 |
September | 0.50 | 19.32 | 0.00 | 19.32 | 2.50 | 26.15 | 2.17 | 26.72 |
October | 2.67 | 18.16 | 0.17 | 18.30 | 0.00 | 18.30 | 0.00 | 18.30 |
November | 26.50 | 16.57 | 8.33 | 16.69 | 0.00 | 16.69 | 0.00 | 16.69 |
December | 62.00 | 16.40 | 23.67 | 16.62 | 0.00 | 16.62 | 0.00 | 16.62 |
Annual Sum or Average | 253.83 | 16.80 | 94.83 | 17.08 | 39.83 | 17.94 | 37.33 | 18.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.62 | 0.00 | 16.62 |
Maximum of Months | 95.17 | 19.32 | 41.83 | 19.32 | 23.17 | 26.15 | 21.67 | 26.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 42.83 | 14.95 | 7.83 | 14.84 | 0.00 | 14.84 | 0.00 | 14.84 |
February | 19.17 | 15.84 | 2.00 | 15.71 | 0.00 | 15.71 | 0.00 | 15.71 |
March | 14.67 | 16.26 | 1.33 | 16.12 | 0.00 | 16.12 | 0.00 | 16.12 |
April | 2.17 | 18.70 | 0.00 | 18.70 | 0.67 | 20.81 | 0.67 | 22.12 |
May | 2.33 | 17.55 | 0.00 | 17.55 | 0.00 | 17.55 | 0.00 | 17.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 27.11 | 11.17 | 27.11 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 27.23 | 20.17 | 27.22 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 26.80 | 8.83 | 26.77 |
September | 0.33 | 19.29 | 0.00 | 19.29 | 6.00 | 27.73 | 5.67 | 27.98 |
October | 2.00 | 18.46 | 0.00 | 18.46 | 0.00 | 18.46 | 0.00 | 18.46 |
November | 15.67 | 15.81 | 2.83 | 15.65 | 0.00 | 15.65 | 0.00 | 15.65 |
December | 38.50 | 15.27 | 7.50 | 15.13 | 0.00 | 15.13 | 0.00 | 15.13 |
Annual Sum or Average | 137.67 | 15.57 | 21.50 | 15.41 | 48.33 | 18.17 | 46.50 | 19.83 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.84 | 0.00 | 14.84 |
Maximum of Months | 42.83 | 19.29 | 7.83 | 19.29 | 21.17 | 27.73 | 20.17 | 27.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 34.67 | 15.41 | 5.00 | 15.36 | 0.50 | 15.52 | 0.50 | 15.66 |
February | 15.00 | 16.27 | 0.67 | 16.18 | 1.83 | 17.49 | 1.83 | 18.56 |
March | 12.50 | 16.44 | 1.00 | 16.36 | 0.67 | 16.90 | 0.67 | 17.40 |
April | 1.67 | 18.59 | 0.00 | 18.59 | 2.00 | 23.71 | 2.00 | 25.22 |
May | 2.00 | 18.06 | 0.00 | 18.06 | 1.33 | 22.00 | 1.33 | 23.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 25.98 | 11.67 | 25.97 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 32.83 | 26.25 | 31.00 | 26.21 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 33.83 | 26.04 | 33.00 | 26.02 |
September | 0.17 | 19.32 | 0.00 | 19.32 | 15.00 | 27.27 | 13.50 | 27.29 |
October | 1.33 | 18.23 | 0.00 | 18.23 | 5.33 | 25.39 | 5.17 | 26.17 |
November | 9.00 | 16.38 | 0.83 | 16.34 | 1.17 | 17.56 | 1.17 | 18.54 |
December | 29.50 | 15.59 | 4.83 | 15.43 | 0.00 | 15.43 | 0.00 | 15.43 |
Annual Sum or Average | 105.83 | 15.93 | 12.33 | 15.81 | 106.33 | 20.87 | 101.83 | 22.61 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.43 | 0.00 | 15.43 |
Maximum of Months | 34.67 | 19.32 | 5.00 | 19.32 | 33.83 | 27.27 | 33.00 | 27.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 34.83 | 15.01 | 5.67 | 14.88 | 0.00 | 14.88 | 0.00 | 14.88 |
February | 16.00 | 16.18 | 1.83 | 16.01 | 0.00 | 16.01 | 0.00 | 16.01 |
March | 12.00 | 16.48 | 1.00 | 16.33 | 0.00 | 16.33 | 0.00 | 16.33 |
April | 1.17 | 18.85 | 0.00 | 18.85 | 1.33 | 24.16 | 0.67 | 25.20 |
May | 1.50 | 18.46 | 0.00 | 18.46 | 4.17 | 25.94 | 1.67 | 26.57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.80 | 4.33 | 27.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 26.99 | 20.67 | 26.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 26.80 | 9.33 | 26.60 |
September | 0.17 | 19.41 | 0.00 | 19.41 | 6.17 | 27.80 | 3.67 | 27.84 |
October | 1.33 | 18.41 | 0.00 | 18.41 | 0.67 | 21.65 | 0.50 | 22.95 |
November | 9.33 | 16.30 | 1.67 | 16.09 | 0.00 | 16.09 | 0.00 | 16.09 |
December | 27.00 | 15.66 | 5.33 | 15.47 | 0.00 | 15.47 | 0.00 | 15.47 |
Annual Sum or Average | 103.33 | 15.79 | 15.50 | 15.61 | 59.50 | 19.52 | 40.83 | 20.87 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.88 | 0.00 | 14.88 |
Maximum of Months | 34.83 | 19.41 | 5.67 | 19.41 | 27.33 | 27.80 | 20.67 | 27.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.78 | 3.67 | 27.77 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.83 | 27.78 | 3.67 | 27.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.78 | 3.67 | 27.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.78 | 1.17 | 27.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.17 | 27.78 | 1.17 | 27.80 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.78 | 1.17 | 27.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.73 | 1.83 | 27.73 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.67 | 27.73 | 1.83 | 27.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.73 | 1.83 | 27.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 321.83 | 24.30 | 48.83 | 24.64 | 13.67 | 24.78 |
February | 209.17 | 24.02 | 63.67 | 24.54 | 0.00 | 24.54 |
March | 170.33 | 24.00 | 71.67 | 24.65 | 0.00 | 24.65 |
April | 61.83 | 24.00 | 111.83 | 25.46 | 0.00 | 25.46 |
May | 52.83 | 24.08 | 144.00 | 25.48 | 1.17 | 25.50 |
June | 52.17 | 27.44 | 264.00 | 26.11 | 52.17 | 26.30 |
July | 191.17 | 29.00 | 442.50 | 27.53 | 191.17 | 27.87 |
August | 96.83 | 28.51 | 337.33 | 26.72 | 96.83 | 27.05 |
September | 60.17 | 27.83 | 269.67 | 26.21 | 55.17 | 26.49 |
October | 11.33 | 24.28 | 143.67 | 26.39 | 0.83 | 26.39 |
November | 64.67 | 24.00 | 120.33 | 25.65 | 0.00 | 25.65 |
December | 155.33 | 24.01 | 83.33 | 24.82 | 0.00 | 24.82 |
Annual Sum or Average | 1447.67 | 25.32 | 2100.83 | 25.91 | 411.00 | 26.18 |
Minimum of Months | 11.33 | 24.00 | 48.83 | 24.54 | 0.00 | 24.54 |
Maximum of Months | 321.83 | 29.00 | 442.50 | 27.53 | 191.17 | 27.87 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 407.67 | 23.73 | 14.17 | 23.82 | 0.00 | 23.82 |
February | 292.83 | 23.89 | 4.50 | 23.92 | 0.00 | 23.92 |
March | 233.50 | 24.01 | 25.33 | 24.19 | 0.00 | 24.19 |
April | 70.50 | 24.00 | 60.67 | 24.91 | 0.00 | 24.91 |
May | 87.00 | 23.98 | 92.83 | 24.71 | 0.00 | 24.71 |
June | 0.67 | 23.92 | 237.00 | 24.53 | 0.00 | 24.53 |
July | 0.50 | 26.80 | 407.17 | 24.58 | 0.50 | 24.59 |
August | 0.00 | 0.00 | 292.33 | 24.58 | 0.00 | 24.58 |
September | 21.50 | 24.06 | 215.50 | 24.63 | 5.17 | 24.63 |
October | 40.00 | 23.98 | 80.33 | 25.33 | 0.00 | 25.33 |
November | 141.50 | 23.99 | 51.17 | 24.50 | 0.00 | 24.50 |
December | 257.67 | 23.98 | 23.83 | 24.14 | 0.00 | 24.14 |
Annual Sum or Average | 1553.33 | 23.91 | 1504.83 | 24.38 | 5.67 | 24.38 |
Minimum of Months | 0.00 | 0.00 | 4.50 | 23.82 | 0.00 | 23.82 |
Maximum of Months | 407.67 | 26.80 | 407.17 | 25.33 | 5.17 | 25.33 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.35 | 78.00 | 22.12 | 78.00 | 21.95 |
February | 448.83 | 22.87 | 26.17 | 22.73 | 26.17 | 22.61 |
March | 491.83 | 23.43 | 9.50 | 23.38 | 9.50 | 23.34 |
April | 330.17 | 23.64 | 0.00 | 23.64 | 0.00 | 23.64 |
May | 225.00 | 23.79 | 46.83 | 24.03 | 0.00 | 24.03 |
June | 63.67 | 23.74 | 149.83 | 24.21 | 0.00 | 24.21 |
July | 24.67 | 23.82 | 269.50 | 24.34 | 0.50 | 24.34 |
August | 16.00 | 23.76 | 154.33 | 24.53 | 0.00 | 24.53 |
September | 122.33 | 23.73 | 138.17 | 24.16 | 6.17 | 24.16 |
October | 295.83 | 23.71 | 7.00 | 23.75 | 0.00 | 23.75 |
November | 427.83 | 23.45 | 2.17 | 23.44 | 2.17 | 23.43 |
December | 497.00 | 22.81 | 35.17 | 22.66 | 35.17 | 22.52 |
Annual Sum or Average | 3445.17 | 23.20 | 916.67 | 23.34 | 157.67 | 23.25 |
Minimum of Months | 16.00 | 22.35 | 0.00 | 22.12 | 0.00 | 21.95 |
Maximum of Months | 502.00 | 23.82 | 269.50 | 24.53 | 78.00 | 24.53 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.78 | 312.33 | 20.53 | 312.33 | 20.42 |
February | 454.00 | 21.48 | 183.33 | 21.16 | 183.33 | 20.98 |
March | 514.00 | 22.17 | 111.17 | 21.84 | 111.17 | 21.61 |
April | 438.83 | 22.78 | 37.00 | 22.62 | 37.00 | 22.49 |
May | 321.50 | 23.16 | 51.67 | 23.19 | 20.17 | 23.07 |
June | 118.83 | 23.41 | 152.17 | 23.92 | 0.00 | 23.92 |
July | 50.17 | 23.60 | 273.67 | 24.25 | 3.17 | 24.26 |
August | 73.17 | 23.55 | 154.00 | 24.20 | 0.00 | 24.20 |
September | 227.67 | 23.14 | 118.00 | 23.58 | 8.17 | 23.60 |
October | 446.83 | 22.74 | 23.67 | 22.64 | 23.67 | 22.54 |
November | 486.33 | 21.92 | 122.67 | 21.60 | 122.67 | 21.38 |
December | 497.00 | 21.06 | 257.50 | 20.71 | 257.50 | 20.54 |
Annual Sum or Average | 4130.33 | 22.10 | 1797.17 | 22.05 | 1079.17 | 21.78 |
Minimum of Months | 50.17 | 20.78 | 23.67 | 20.53 | 0.00 | 20.42 |
Maximum of Months | 514.00 | 23.60 | 312.33 | 24.25 | 312.33 | 24.26 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.23 | 263.50 | 20.97 | 263.50 | 20.83 |
February | 454.00 | 21.97 | 117.00 | 21.69 | 117.00 | 21.51 |
March | 510.83 | 22.82 | 41.50 | 22.66 | 41.50 | 22.52 |
April | 359.83 | 23.42 | 5.00 | 23.44 | 0.00 | 23.44 |
May | 260.83 | 23.45 | 66.17 | 23.77 | 0.00 | 23.77 |
June | 38.17 | 23.73 | 253.00 | 24.36 | 0.00 | 24.36 |
July | 13.17 | 26.51 | 413.33 | 24.77 | 11.17 | 24.83 |
August | 28.17 | 24.03 | 260.17 | 24.56 | 2.33 | 24.58 |
September | 189.83 | 23.50 | 148.17 | 24.02 | 8.50 | 24.08 |
October | 398.50 | 23.35 | 5.67 | 23.38 | 0.00 | 23.38 |
November | 475.50 | 22.70 | 32.33 | 22.58 | 32.33 | 22.48 |
December | 497.00 | 21.87 | 143.00 | 21.60 | 143.00 | 21.42 |
Annual Sum or Average | 3727.83 | 22.58 | 1748.83 | 22.80 | 619.33 | 22.60 |
Minimum of Months | 13.17 | 21.23 | 5.00 | 20.97 | 0.00 | 20.83 |
Maximum of Months | 510.83 | 26.51 | 413.33 | 24.77 | 263.50 | 24.83 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 494.00 | 21.18 | 266.50 | 20.97 | 263.17 | 20.85 |
February | 419.33 | 21.74 | 140.33 | 21.58 | 130.33 | 21.42 |
March | 432.50 | 22.16 | 67.50 | 22.14 | 45.33 | 22.02 |
April | 312.17 | 22.72 | 70.67 | 23.07 | 5.83 | 23.11 |
May | 216.50 | 22.83 | 137.50 | 23.46 | 0.00 | 23.46 |
June | 100.67 | 24.15 | 302.33 | 24.40 | 25.67 | 24.54 |
July | 66.83 | 25.84 | 419.33 | 24.76 | 49.67 | 24.94 |
August | 95.00 | 23.99 | 330.33 | 24.32 | 24.67 | 24.43 |
September | 192.33 | 23.30 | 206.00 | 24.00 | 23.00 | 24.15 |
October | 333.17 | 22.73 | 44.50 | 22.99 | 2.17 | 23.01 |
November | 456.67 | 22.15 | 51.00 | 22.06 | 46.50 | 21.96 |
December | 491.33 | 21.43 | 181.83 | 21.22 | 181.83 | 21.09 |
Annual Sum or Average | 3610.50 | 22.25 | 2217.83 | 22.68 | 798.17 | 22.55 |
Minimum of Months | 66.83 | 21.18 | 44.50 | 20.97 | 0.00 | 20.85 |
Maximum of Months | 494.00 | 25.84 | 419.33 | 24.76 | 263.17 | 24.94 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 420.67 | 21.37 | 254.50 | 21.28 | 227.83 | 21.13 |
February | 323.33 | 22.05 | 162.83 | 22.19 | 107.67 | 22.02 |
March | 369.50 | 22.41 | 119.83 | 22.57 | 46.67 | 22.45 |
April | 293.67 | 22.92 | 87.00 | 23.29 | 12.00 | 23.35 |
May | 238.67 | 22.86 | 139.00 | 23.46 | 8.67 | 23.47 |
June | 110.00 | 23.81 | 261.67 | 24.27 | 17.33 | 24.39 |
July | 72.83 | 25.68 | 404.17 | 24.82 | 51.50 | 25.00 |
August | 102.33 | 24.86 | 340.83 | 24.73 | 53.00 | 24.90 |
September | 176.17 | 23.78 | 262.83 | 24.37 | 43.33 | 24.57 |
October | 256.00 | 23.14 | 150.00 | 23.70 | 16.50 | 23.83 |
November | 328.83 | 22.48 | 127.83 | 22.78 | 48.50 | 22.69 |
December | 396.83 | 21.75 | 190.83 | 21.73 | 141.50 | 21.52 |
Annual Sum or Average | 3088.83 | 22.58 | 2501.33 | 23.12 | 774.50 | 23.02 |
Minimum of Months | 72.83 | 21.37 | 87.00 | 21.28 | 8.67 | 21.13 |
Maximum of Months | 420.67 | 25.68 | 404.17 | 24.82 | 227.83 | 25.00 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 489.50 | 21.42 | 202.17 | 21.18 | 202.17 | 21.05 |
February | 379.17 | 22.29 | 90.17 | 22.23 | 68.83 | 22.08 |
March | 313.17 | 23.01 | 64.17 | 23.17 | 13.83 | 23.13 |
April | 98.67 | 23.81 | 172.67 | 24.60 | 12.00 | 24.71 |
May | 165.33 | 23.21 | 202.00 | 24.07 | 8.67 | 24.14 |
June | 45.00 | 24.90 | 382.33 | 24.57 | 21.33 | 24.67 |
July | 75.50 | 26.23 | 480.17 | 24.93 | 75.50 | 25.08 |
August | 46.67 | 25.95 | 472.83 | 24.70 | 45.50 | 24.80 |
September | 152.67 | 23.53 | 244.50 | 24.24 | 22.17 | 24.36 |
October | 218.50 | 23.28 | 115.33 | 23.86 | 5.83 | 23.92 |
November | 306.67 | 22.93 | 59.00 | 23.27 | 2.00 | 23.26 |
December | 400.00 | 22.62 | 55.00 | 22.54 | 41.83 | 22.40 |
Annual Sum or Average | 2690.83 | 22.82 | 2540.33 | 23.49 | 519.67 | 23.43 |
Minimum of Months | 45.00 | 21.42 | 55.00 | 21.18 | 2.00 | 21.05 |
Maximum of Months | 489.50 | 26.23 | 480.17 | 24.93 | 202.17 | 25.08 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.12 | 475.17 | 20.09 | 475.17 | 20.08 |
February | 454.00 | 20.64 | 352.00 | 20.52 | 352.00 | 20.47 |
March | 514.00 | 21.28 | 229.50 | 21.02 | 229.50 | 20.88 |
April | 472.33 | 22.28 | 58.17 | 22.10 | 58.17 | 21.95 |
May | 356.67 | 22.80 | 69.17 | 22.84 | 29.00 | 22.69 |
June | 118.50 | 23.39 | 184.50 | 23.97 | 0.00 | 23.97 |
July | 33.33 | 23.74 | 309.17 | 24.44 | 1.17 | 24.45 |
August | 109.50 | 23.41 | 166.50 | 24.08 | 0.67 | 24.09 |
September | 284.17 | 22.75 | 101.17 | 23.20 | 11.67 | 23.18 |
October | 493.17 | 22.19 | 48.50 | 22.05 | 48.50 | 21.94 |
November | 489.00 | 21.04 | 249.17 | 20.78 | 249.17 | 20.65 |
December | 497.00 | 20.25 | 427.17 | 20.17 | 427.17 | 20.14 |
Annual Sum or Average | 4323.67 | 21.50 | 2670.17 | 21.50 | 1882.17 | 21.24 |
Minimum of Months | 33.33 | 20.12 | 48.50 | 20.09 | 0.00 | 20.08 |
Maximum of Months | 514.00 | 23.74 | 475.17 | 24.44 | 475.17 | 24.45 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.19 | 382.67 | 20.13 | 382.67 | 20.11 |
February | 375.83 | 20.85 | 246.17 | 20.67 | 244.33 | 20.58 |
March | 408.50 | 21.30 | 172.33 | 21.09 | 166.50 | 20.94 |
April | 314.33 | 21.96 | 80.17 | 22.12 | 43.00 | 22.03 |
May | 246.00 | 22.27 | 113.00 | 22.70 | 26.00 | 22.55 |
June | 126.83 | 23.68 | 226.83 | 24.29 | 25.00 | 24.46 |
July | 82.17 | 25.22 | 319.33 | 24.82 | 46.67 | 25.03 |
August | 110.33 | 23.55 | 244.33 | 24.25 | 19.00 | 24.39 |
September | 228.83 | 22.75 | 139.67 | 23.54 | 24.00 | 23.71 |
October | 371.50 | 22.00 | 43.17 | 21.99 | 31.67 | 21.90 |
November | 412.83 | 21.10 | 192.83 | 20.88 | 192.83 | 20.77 |
December | 422.00 | 20.25 | 345.33 | 20.15 | 345.33 | 20.12 |
Annual Sum or Average | 3526.17 | 21.51 | 2505.83 | 21.77 | 1547.00 | 21.56 |
Minimum of Months | 82.17 | 20.19 | 43.17 | 20.13 | 19.00 | 20.11 |
Maximum of Months | 427.00 | 25.22 | 382.67 | 24.82 | 382.67 | 25.03 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 438.00 | 20.94 | 321.50 | 20.83 | 300.17 | 20.69 |
February | 343.50 | 21.60 | 229.33 | 21.66 | 178.67 | 21.48 |
March | 389.83 | 21.77 | 196.83 | 21.87 | 125.50 | 21.69 |
April | 328.67 | 22.23 | 109.67 | 22.55 | 42.17 | 22.51 |
May | 279.50 | 22.48 | 147.00 | 22.93 | 33.83 | 22.83 |
June | 161.83 | 23.28 | 229.00 | 23.98 | 15.00 | 24.09 |
July | 94.83 | 24.69 | 345.33 | 24.65 | 41.83 | 24.83 |
August | 135.00 | 23.99 | 307.83 | 24.45 | 36.83 | 24.61 |
September | 209.00 | 23.31 | 242.83 | 24.09 | 39.00 | 24.30 |
October | 294.83 | 22.64 | 158.50 | 23.20 | 35.83 | 23.26 |
November | 358.00 | 21.90 | 191.67 | 22.07 | 119.50 | 21.89 |
December | 421.50 | 21.04 | 283.67 | 20.95 | 246.50 | 20.77 |
Annual Sum or Average | 3454.50 | 22.08 | 2763.17 | 22.53 | 1214.83 | 22.35 |
Minimum of Months | 94.83 | 20.94 | 109.67 | 20.83 | 15.00 | 20.69 |
Maximum of Months | 438.00 | 24.69 | 345.33 | 24.65 | 300.17 | 24.83 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 501.50 | 20.41 | 424.33 | 20.32 | 424.33 | 20.29 |
February | 432.67 | 20.92 | 264.00 | 20.77 | 259.33 | 20.68 |
March | 469.83 | 21.30 | 183.00 | 21.17 | 166.33 | 21.03 |
April | 386.33 | 22.08 | 70.83 | 22.29 | 27.17 | 22.26 |
May | 283.17 | 22.41 | 147.83 | 23.01 | 24.67 | 22.99 |
June | 146.33 | 23.12 | 260.83 | 23.95 | 14.17 | 24.05 |
July | 94.50 | 24.46 | 367.50 | 24.57 | 43.00 | 24.71 |
August | 128.83 | 23.33 | 294.67 | 24.16 | 18.67 | 24.25 |
September | 272.17 | 22.51 | 170.33 | 23.36 | 17.00 | 23.47 |
October | 420.17 | 21.97 | 64.33 | 22.08 | 31.50 | 22.03 |
November | 463.33 | 21.24 | 184.33 | 21.01 | 183.17 | 20.88 |
December | 494.67 | 20.52 | 361.00 | 20.38 | 361.00 | 20.32 |
Annual Sum or Average | 4093.50 | 21.55 | 2793.00 | 21.87 | 1570.33 | 21.66 |
Minimum of Months | 94.50 | 20.41 | 64.33 | 20.32 | 14.17 | 20.29 |
Maximum of Months | 501.50 | 24.46 | 424.33 | 24.57 | 424.33 | 24.71 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.72 | 493.83 | 19.71 | 493.83 | 19.71 |
February | 454.00 | 20.16 | 412.33 | 20.10 | 412.33 | 20.08 |
March | 514.00 | 20.67 | 339.00 | 20.46 | 339.00 | 20.37 |
April | 474.17 | 21.56 | 166.67 | 21.21 | 166.67 | 21.00 |
May | 384.17 | 22.30 | 108.50 | 22.17 | 74.33 | 21.92 |
June | 154.17 | 22.96 | 181.00 | 23.69 | 0.50 | 23.69 |
July | 75.00 | 23.67 | 292.50 | 24.34 | 7.83 | 24.38 |
August | 149.50 | 23.11 | 162.17 | 23.81 | 3.17 | 23.83 |
September | 322.33 | 22.31 | 124.50 | 22.64 | 43.83 | 22.54 |
October | 499.83 | 21.40 | 177.33 | 21.09 | 177.33 | 20.91 |
November | 489.00 | 20.36 | 364.67 | 20.19 | 364.67 | 20.12 |
December | 497.00 | 19.90 | 473.50 | 19.86 | 473.50 | 19.85 |
Annual Sum or Average | 4515.17 | 21.03 | 3296.00 | 21.03 | 2557.00 | 20.78 |
Minimum of Months | 75.00 | 19.72 | 108.50 | 19.71 | 0.50 | 19.71 |
Maximum of Months | 514.00 | 23.67 | 493.83 | 24.34 | 493.83 | 24.38 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.96 | 474.83 | 19.93 | 474.83 | 19.91 |
February | 451.00 | 20.55 | 332.67 | 20.38 | 332.67 | 20.31 |
March | 492.50 | 21.01 | 259.50 | 20.74 | 257.00 | 20.60 |
April | 370.17 | 21.53 | 154.17 | 21.46 | 113.17 | 21.24 |
May | 284.83 | 21.97 | 155.33 | 22.27 | 56.33 | 22.02 |
June | 141.00 | 23.42 | 283.83 | 24.15 | 28.00 | 24.31 |
July | 97.67 | 24.91 | 385.50 | 24.65 | 51.67 | 24.85 |
August | 125.00 | 23.24 | 316.00 | 24.09 | 17.83 | 24.18 |
September | 265.00 | 22.46 | 187.50 | 23.20 | 44.17 | 23.27 |
October | 456.33 | 21.62 | 120.17 | 21.38 | 114.17 | 21.20 |
November | 487.33 | 20.57 | 314.00 | 20.38 | 314.00 | 20.30 |
December | 497.00 | 20.00 | 453.83 | 19.94 | 453.83 | 19.93 |
Annual Sum or Average | 4169.83 | 21.17 | 3437.33 | 21.43 | 2257.67 | 21.19 |
Minimum of Months | 97.67 | 19.96 | 120.17 | 19.93 | 17.83 | 19.91 |
Maximum of Months | 502.00 | 24.91 | 474.83 | 24.65 | 474.83 | 24.85 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 459.00 | 20.51 | 375.17 | 20.36 | 364.83 | 20.26 |
February | 366.00 | 21.12 | 267.33 | 21.08 | 228.33 | 20.89 |
March | 403.83 | 21.12 | 277.67 | 21.15 | 215.83 | 20.94 |
April | 351.00 | 21.60 | 188.33 | 21.69 | 126.67 | 21.47 |
May | 305.50 | 22.02 | 173.83 | 22.32 | 72.00 | 22.10 |
June | 186.67 | 22.87 | 223.00 | 23.73 | 17.67 | 23.83 |
July | 130.50 | 24.11 | 325.50 | 24.48 | 44.33 | 24.67 |
August | 166.17 | 23.56 | 298.00 | 24.23 | 39.67 | 24.39 |
September | 232.50 | 22.74 | 239.50 | 23.58 | 55.67 | 23.68 |
October | 333.83 | 21.93 | 200.00 | 22.26 | 94.00 | 22.09 |
November | 397.50 | 21.26 | 251.17 | 21.21 | 200.00 | 20.99 |
December | 449.33 | 20.54 | 336.50 | 20.35 | 322.67 | 20.22 |
Annual Sum or Average | 3781.83 | 21.58 | 3156.00 | 21.91 | 1781.67 | 21.67 |
Minimum of Months | 130.50 | 20.51 | 173.83 | 20.35 | 17.67 | 20.22 |
Maximum of Months | 459.00 | 24.11 | 375.17 | 24.48 | 364.83 | 24.67 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.04 | 460.83 | 19.98 | 460.83 | 19.96 |
February | 436.00 | 20.57 | 327.50 | 20.43 | 323.67 | 20.35 |
March | 476.17 | 20.89 | 269.83 | 20.74 | 256.33 | 20.62 |
April | 401.33 | 21.57 | 157.83 | 21.58 | 117.67 | 21.42 |
May | 316.17 | 22.08 | 170.50 | 22.48 | 62.17 | 22.33 |
June | 186.83 | 22.81 | 251.00 | 23.73 | 16.00 | 23.82 |
July | 127.00 | 24.01 | 339.50 | 24.44 | 48.17 | 24.60 |
August | 164.33 | 23.01 | 279.33 | 23.94 | 21.00 | 24.04 |
September | 294.00 | 22.14 | 175.17 | 22.89 | 39.67 | 22.91 |
October | 436.00 | 21.44 | 140.83 | 21.38 | 114.17 | 21.24 |
November | 474.83 | 20.76 | 280.00 | 20.53 | 279.33 | 20.43 |
December | 495.83 | 20.15 | 418.50 | 20.04 | 418.50 | 20.00 |
Annual Sum or Average | 4310.50 | 21.21 | 3270.83 | 21.45 | 2157.50 | 21.23 |
Minimum of Months | 127.00 | 20.04 | 140.83 | 19.98 | 16.00 | 19.96 |
Maximum of Months | 502.00 | 24.01 | 460.83 | 24.44 | 460.83 | 24.60 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 405.83 | 27.00 | 0.00 | 27.00 |
February | 4.17 | 27.00 | 443.00 | 27.00 | 4.17 | 27.00 |
March | 9.33 | 27.00 | 514.00 | 27.00 | 9.33 | 27.00 |
April | 29.50 | 27.00 | 485.00 | 27.00 | 29.50 | 27.00 |
May | 4.67 | 27.00 | 508.00 | 27.00 | 4.67 | 27.00 |
June | 42.33 | 27.00 | 496.00 | 27.00 | 42.33 | 27.00 |
July | 167.17 | 27.00 | 497.00 | 27.00 | 167.17 | 27.00 |
August | 211.00 | 27.03 | 514.00 | 27.01 | 211.00 | 27.02 |
September | 21.17 | 27.00 | 485.00 | 27.00 | 21.17 | 27.00 |
October | 11.33 | 27.00 | 502.00 | 27.00 | 11.33 | 27.00 |
November | 10.33 | 27.00 | 489.00 | 27.00 | 10.33 | 27.00 |
December | 3.50 | 27.00 | 497.00 | 27.00 | 3.50 | 27.00 |
Annual Sum or Average | 514.50 | 27.01 | 5835.83 | 27.00 | 514.50 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 405.83 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 211.00 | 27.03 | 514.00 | 27.01 | 211.00 | 27.02 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 87.33 | 25.58 | 228.67 | 26.61 | 0.00 | 26.61 |
February | 11.67 | 27.00 | 329.83 | 27.00 | 0.67 | 27.00 |
March | 7.33 | 27.00 | 468.83 | 27.00 | 2.83 | 27.00 |
April | 6.33 | 27.00 | 485.00 | 27.00 | 6.33 | 27.00 |
May | 2.17 | 27.00 | 504.33 | 27.00 | 2.17 | 27.00 |
June | 11.33 | 27.00 | 496.00 | 27.00 | 11.33 | 27.00 |
July | 37.17 | 27.00 | 497.00 | 27.00 | 37.17 | 27.00 |
August | 46.83 | 27.05 | 514.00 | 27.01 | 46.83 | 27.01 |
September | 7.83 | 27.00 | 485.00 | 27.00 | 7.83 | 27.00 |
October | 4.50 | 27.00 | 502.00 | 27.00 | 4.50 | 27.00 |
November | 0.00 | 0.00 | 460.50 | 27.00 | 0.00 | 27.00 |
December | 12.00 | 27.00 | 360.83 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 234.50 | 26.48 | 5332.00 | 26.98 | 119.67 | 26.98 |
Minimum of Months | 0.00 | 0.00 | 228.67 | 26.61 | 0.00 | 26.61 |
Maximum of Months | 87.33 | 27.05 | 514.00 | 27.01 | 46.83 | 27.01 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 260.67 | 24.74 | 125.17 | 25.12 | 26.67 | 24.91 |
February | 35.67 | 26.95 | 197.83 | 26.99 | 0.00 | 26.99 |
March | 21.50 | 27.00 | 367.17 | 27.00 | 1.33 | 27.00 |
April | 6.67 | 27.00 | 440.67 | 27.00 | 6.67 | 27.00 |
May | 10.17 | 26.11 | 475.67 | 26.98 | 3.67 | 26.98 |
June | 17.17 | 27.00 | 496.00 | 27.00 | 17.17 | 27.00 |
July | 59.33 | 27.00 | 497.00 | 27.00 | 59.33 | 27.00 |
August | 69.67 | 27.04 | 514.00 | 27.01 | 69.67 | 27.01 |
September | 13.50 | 27.00 | 476.67 | 27.00 | 13.50 | 27.00 |
October | 4.17 | 27.00 | 463.17 | 27.00 | 4.17 | 27.00 |
November | 21.33 | 27.00 | 333.33 | 27.00 | 0.00 | 27.00 |
December | 61.17 | 27.00 | 210.50 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 581.00 | 25.97 | 4597.17 | 26.86 | 202.17 | 26.84 |
Minimum of Months | 4.17 | 24.74 | 125.17 | 25.12 | 0.00 | 24.91 |
Maximum of Months | 260.67 | 27.04 | 514.00 | 27.01 | 69.67 | 27.01 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 302.33 | 27.00 | 502.00 | 27.00 | 302.33 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 498.67 | 27.00 | 508.00 | 27.00 | 498.67 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
August | 514.00 | 27.01 | 514.00 | 27.01 | 514.00 | 27.01 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5734.00 | 27.00 | 5943.00 | 27.00 | 5734.00 | 27.00 |
Minimum of Months | 302.33 | 27.00 | 454.00 | 27.00 | 302.33 | 27.00 |
Maximum of Months | 514.00 | 27.01 | 514.00 | 27.01 | 514.00 | 27.01 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99865 | 13.65465 | 0.62952 | 13.53799 |
February | 454.00000 | 27.00000 | 14.90776 | 0.72022 | 16.09681 |
March | 514.00000 | 26.99999 | 16.88053 | 0.80129 | 18.67233 |
April | 485.00000 | 27.00002 | 19.97083 | 0.89531 | 22.01279 |
May | 508.00000 | 27.00016 | 22.18978 | 0.15888 | 5.71125 |
June | 496.00000 | 27.00046 | 25.46529 | 0.27414 | 6.68007 |
July | 497.00000 | 27.00028 | 26.35759 | 0.35883 | 7.81069 |
August | 514.00000 | 27.01036 | 25.85530 | 0.38056 | 8.17296 |
September | 485.00000 | 27.00051 | 25.26139 | 0.19493 | 5.98214 |
October | 502.00000 | 27.00006 | 22.32718 | 0.84653 | 20.19967 |
November | 489.00000 | 27.00000 | 18.46678 | 0.81619 | 19.16404 |
December | 497.00000 | 26.99999 | 14.81353 | 0.77768 | 17.90513 |
Annual Sum or Average | 5943.00000 | 27.00090 | 20.55029 | 0.56955 | 13.45901 |
Minimum of Months | 454.00000 | 26.99865 | 13.65465 | 0.15888 | 5.71125 |
Maximum of Months | 514.00000 | 27.01036 | 26.35759 | 0.89531 | 22.01279 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.72571 | 13.65724 | 0.45378 | 10.11631 |
February | 454.00000 | 27.00000 | 14.90071 | 0.58246 | 12.36579 |
March | 514.00000 | 26.99999 | 16.86579 | 0.65736 | 14.31172 |
April | 485.00000 | 27.00002 | 19.94501 | 0.75197 | 17.08979 |
May | 508.00000 | 27.00015 | 22.20418 | 0.06635 | 5.40948 |
June | 496.00000 | 27.00045 | 25.48333 | 0.17483 | 5.83992 |
July | 497.00000 | 27.00031 | 26.36748 | 0.23450 | 6.32685 |
August | 514.00000 | 27.00423 | 25.86009 | 0.24061 | 6.42249 |
September | 485.00000 | 27.00043 | 25.36098 | 0.10269 | 5.49588 |
October | 502.00000 | 27.00006 | 22.31315 | 0.73867 | 16.62109 |
November | 489.00000 | 27.00001 | 18.44500 | 0.66409 | 14.46460 |
December | 497.00000 | 26.99999 | 14.79061 | 0.58289 | 12.37199 |
Annual Sum or Average | 5943.00000 | 26.97731 | 20.55379 | 0.43589 | 10.54329 |
Minimum of Months | 454.00000 | 26.72571 | 13.65724 | 0.06635 | 5.40948 |
Maximum of Months | 514.00000 | 27.00423 | 26.36748 | 0.75197 | 17.08979 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 25.78536 | 14.49815 | 0.20312 | 8.75563 |
February | 454.00000 | 26.99633 | 14.90171 | 0.50958 | 10.79972 |
March | 514.00000 | 26.99999 | 16.87225 | 0.58720 | 12.61471 |
April | 485.00000 | 27.00002 | 19.95961 | 0.69453 | 15.50096 |
May | 508.00000 | 26.97613 | 22.23499 | 0.01269 | 5.81409 |
June | 496.00000 | 27.00045 | 25.49532 | 0.16354 | 5.93450 |
July | 497.00000 | 27.00031 | 26.37544 | 0.23529 | 6.47669 |
August | 514.00000 | 27.00516 | 25.86748 | 0.23134 | 6.49083 |
September | 485.00000 | 27.00014 | 25.43592 | 0.06313 | 5.61166 |
October | 502.00000 | 27.00006 | 22.33422 | 0.67459 | 14.83068 |
November | 489.00000 | 27.00001 | 18.45573 | 0.57889 | 12.35393 |
December | 497.00000 | 27.00000 | 14.80094 | 0.49542 | 10.50810 |
Annual Sum or Average | 5943.00000 | 26.89561 | 20.64123 | 0.36917 | 9.62188 |
Minimum of Months | 454.00000 | 25.78536 | 14.49815 | 0.01269 | 5.61166 |
Maximum of Months | 514.00000 | 27.00516 | 26.37544 | 0.69453 | 15.50096 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00043 | 30.00035 | 1.01228 | 26.67126 |
February | 454.00000 | 27.00049 | 27.04654 | 1.16885 | 33.76044 |
March | 514.00000 | 27.00017 | 22.05118 | 1.28524 | 39.52228 |
April | 485.00000 | 27.00058 | 21.44195 | 1.42441 | 46.82827 |
May | 508.00000 | 27.00048 | 29.00284 | 0.47509 | 9.76356 |
June | 496.00000 | 27.00175 | 29.55293 | 0.72403 | 16.07107 |
July | 497.00000 | 27.00576 | 30.18570 | 0.96175 | 24.57525 |
August | 514.00000 | 27.00705 | 28.42086 | 1.13164 | 31.99745 |
September | 485.00000 | 27.00051 | 31.04011 | 0.54338 | 11.28422 |
October | 502.00000 | 27.00046 | 27.01325 | 1.22548 | 36.51128 |
November | 489.00000 | 27.00021 | 22.41556 | 1.31395 | 40.99660 |
December | 497.00000 | 27.00003 | 19.40896 | 1.40047 | 45.54432 |
Annual Sum or Average | 5943.00000 | 27.00151 | 26.46775 | 1.05463 | 30.25719 |
Minimum of Months | 454.00000 | 27.00003 | 19.40896 | 0.47509 | 9.76356 |
Maximum of Months | 514.00000 | 27.00705 | 31.04011 | 1.42441 | 46.82827 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.55806 | 14.65130 | 0.29753 | 8.44373 |
February | 454.00000 | 24.53577 | 14.32818 | 0.29500 | 7.23585 |
March | 514.00000 | 24.48450 | 15.54834 | 0.30486 | 7.25351 |
April | 485.00000 | 24.60034 | 19.11618 | 0.36073 | 8.17588 |
May | 508.00000 | 24.61727 | 22.77802 | -0.4524 | 10.48822 |
June | 496.00000 | 24.98981 | 34.00848 | -0.2370 | 10.30173 |
July | 497.00000 | 26.58081 | 52.03461 | 0.42390 | 23.14836 |
August | 514.00000 | 25.45462 | 37.25855 | -0.0508 | 12.79309 |
September | 485.00000 | 25.03354 | 32.39274 | -0.2263 | 10.96435 |
October | 502.00000 | 24.74989 | 21.03028 | 0.42172 | 9.45927 |
November | 489.00000 | 24.71308 | 16.50415 | 0.37300 | 8.54285 |
December | 497.00000 | 24.61536 | 13.79419 | 0.31958 | 7.59952 |
Annual Sum or Average | 5943.00000 | 24.91379 | 24.52778 | 0.15065 | 10.39141 |
Minimum of Months | 454.00000 | 24.48450 | 13.79419 | -0.4524 | 7.23585 |
Maximum of Months | 514.00000 | 26.58081 | 52.03461 | 0.42390 | 23.14836 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.91388 | 13.75630 | 0.13268 | 6.00340 |
February | 454.00000 | 24.07977 | 15.29455 | 0.20165 | 6.10285 |
March | 514.00000 | 24.21938 | 16.26282 | 0.26095 | 6.60325 |
April | 485.00000 | 24.32716 | 19.68998 | 0.32765 | 7.49260 |
May | 508.00000 | 24.32600 | 23.67483 | -0.5214 | 11.30430 |
June | 496.00000 | 24.27025 | 32.15424 | -0.4340 | 9.36279 |
July | 497.00000 | 24.47910 | 35.77807 | -0.3060 | 7.66716 |
August | 514.00000 | 24.33453 | 31.58642 | -0.3894 | 8.62744 |
September | 485.00000 | 24.32872 | 31.34473 | -0.4399 | 9.72697 |
October | 502.00000 | 24.38070 | 22.36163 | 0.35186 | 7.89470 |
November | 489.00000 | 24.35479 | 17.69355 | 0.30255 | 7.15431 |
December | 497.00000 | 24.25364 | 14.77493 | 0.24561 | 6.50179 |
Annual Sum or Average | 5943.00000 | 24.27330 | 22.91327 | -0.0249 | 7.88399 |
Minimum of Months | 454.00000 | 23.91388 | 13.75630 | -0.5214 | 6.00340 |
Maximum of Months | 514.00000 | 24.47910 | 35.77807 | 0.35186 | 11.30430 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.34672 | 15.44443 | -0.2689 | 8.02889 |
February | 454.00000 | 22.88313 | 17.29582 | -0.1139 | 6.60552 |
March | 514.00000 | 23.46307 | 18.11025 | 0.04598 | 5.89553 |
April | 485.00000 | 23.83750 | 21.31559 | 0.17545 | 6.00265 |
May | 508.00000 | 24.08544 | 24.58627 | -0.6394 | 14.24397 |
June | 496.00000 | 24.12269 | 32.84722 | -0.5290 | 11.21651 |
July | 497.00000 | 24.22252 | 36.87513 | -0.4587 | 9.80276 |
August | 514.00000 | 24.20024 | 32.20537 | -0.4983 | 10.48346 |
September | 485.00000 | 24.11570 | 32.20691 | -0.5534 | 11.98368 |
October | 502.00000 | 23.93935 | 23.92683 | 0.21639 | 6.20401 |
November | 489.00000 | 23.54912 | 19.79458 | 0.07277 | 5.75955 |
December | 497.00000 | 22.81494 | 17.15097 | -0.1342 | 6.77995 |
Annual Sum or Average | 5943.00000 | 23.63691 | 24.35637 | -0.2255 | 8.60564 |
Minimum of Months | 454.00000 | 22.34672 | 15.44443 | -0.6394 | 5.75955 |
Maximum of Months | 514.00000 | 24.22252 | 36.87513 | 0.21639 | 14.24397 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.77673 | 16.25383 | -0.6814 | 17.42460 |
February | 454.00000 | 21.47777 | 18.66308 | -0.4763 | 12.04841 |
March | 514.00000 | 22.16616 | 19.79438 | -0.2849 | 9.28287 |
April | 485.00000 | 22.90602 | 23.03056 | -0.0610 | 6.79193 |
May | 508.00000 | 23.56598 | 25.49467 | -0.8313 | 21.93410 |
June | 496.00000 | 23.98157 | 33.00795 | -0.5753 | 12.80032 |
July | 497.00000 | 24.17947 | 36.84269 | -0.4651 | 10.10477 |
August | 514.00000 | 24.12813 | 32.33386 | -0.5239 | 11.28719 |
September | 485.00000 | 23.73051 | 33.22794 | -0.6983 | 17.23298 |
October | 502.00000 | 22.88511 | 26.25085 | -0.0524 | 6.47317 |
November | 489.00000 | 21.93444 | 21.81617 | -0.3359 | 9.93312 |
December | 497.00000 | 21.05863 | 18.23845 | -0.5868 | 15.56584 |
Annual Sum or Average | 5943.00000 | 22.74252 | 25.45118 | -0.4650 | 12.58604 |
Minimum of Months | 454.00000 | 20.77673 | 16.25383 | -0.8313 | 6.47317 |
Maximum of Months | 514.00000 | 24.17947 | 36.84269 | -0.0524 | 21.93410 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.23421 | 14.37287 | -0.5562 | 13.89784 |
February | 454.00000 | 21.96532 | 16.40493 | -0.3409 | 9.36627 |
March | 514.00000 | 22.82368 | 17.15259 | -0.1134 | 6.77646 |
April | 485.00000 | 23.60344 | 20.11350 | 0.11538 | 5.93451 |
May | 508.00000 | 23.89248 | 23.69258 | -0.6904 | 16.86423 |
June | 496.00000 | 24.24620 | 31.47925 | -0.4319 | 9.75607 |
July | 497.00000 | 24.60994 | 34.85721 | -0.2433 | 7.62220 |
August | 514.00000 | 24.33330 | 31.02592 | -0.3967 | 9.26364 |
September | 485.00000 | 23.98899 | 31.51627 | -0.5913 | 14.48266 |
October | 502.00000 | 23.51621 | 23.06297 | 0.10238 | 5.86092 |
November | 489.00000 | 22.74283 | 18.88966 | -0.1259 | 6.70463 |
December | 497.00000 | 21.87302 | 15.95335 | -0.3650 | 9.58871 |
Annual Sum or Average | 5943.00000 | 23.24495 | 23.25160 | -0.3036 | 9.68476 |
Minimum of Months | 454.00000 | 21.23421 | 14.37287 | -0.6904 | 5.86092 |
Maximum of Months | 514.00000 | 24.60994 | 34.85721 | 0.11538 | 16.86423 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.24196 | 13.33680 | -0.5401 | 13.75043 |
February | 454.00000 | 21.96007 | 15.38680 | -0.3118 | 9.77010 |
March | 514.00000 | 22.48224 | 16.45812 | -0.1440 | 7.78497 |
April | 485.00000 | 23.24778 | 19.90897 | 0.10038 | 7.34112 |
May | 508.00000 | 23.64581 | 23.37768 | -0.6673 | 17.64114 |
June | 496.00000 | 24.18322 | 31.34577 | -0.3273 | 10.23483 |
July | 497.00000 | 24.48370 | 34.88837 | -0.1365 | 8.20196 |
August | 514.00000 | 24.15310 | 31.04620 | -0.3263 | 9.75004 |
September | 485.00000 | 23.86123 | 31.28870 | -0.5284 | 14.98316 |
October | 502.00000 | 23.23931 | 22.67820 | 0.09104 | 6.81140 |
November | 489.00000 | 22.30075 | 18.36189 | -0.1971 | 7.55348 |
December | 497.00000 | 21.46843 | 15.29070 | -0.4456 | 10.85143 |
Annual Sum or Average | 5943.00000 | 23.03014 | 22.82594 | -0.2866 | 10.39867 |
Minimum of Months | 454.00000 | 21.24196 | 13.33680 | -0.6673 | 6.81140 |
Maximum of Months | 514.00000 | 24.48370 | 34.88837 | 0.10038 | 17.64114 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.88031 | 13.03989 | -0.3657 | 13.29928 |
February | 454.00000 | 22.72738 | 14.68683 | -0.0905 | 10.34557 |
March | 514.00000 | 22.89836 | 16.03015 | -0.0205 | 8.51327 |
April | 485.00000 | 23.42655 | 19.74963 | 0.13966 | 7.75312 |
May | 508.00000 | 23.62480 | 23.49984 | -0.7069 | 19.53332 |
June | 496.00000 | 24.12217 | 31.51831 | -0.4168 | 11.03332 |
July | 497.00000 | 24.52562 | 34.86491 | -0.1927 | 8.28280 |
August | 514.00000 | 24.40466 | 30.57483 | -0.2535 | 9.49404 |
September | 485.00000 | 24.11074 | 30.75807 | -0.4028 | 13.83615 |
October | 502.00000 | 23.68142 | 21.93300 | 0.24275 | 8.84730 |
November | 489.00000 | 23.10040 | 17.47997 | 0.02899 | 8.69987 |
December | 497.00000 | 22.28986 | 14.59644 | -0.2231 | 10.63754 |
Annual Sum or Average | 5943.00000 | 23.40383 | 22.44261 | -0.1901 | 10.86894 |
Minimum of Months | 454.00000 | 21.88031 | 13.03989 | -0.7069 | 7.75312 |
Maximum of Months | 514.00000 | 24.52562 | 34.86491 | 0.24275 | 19.53332 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.49188 | 12.95908 | -0.4522 | 11.55459 |
February | 454.00000 | 22.62324 | 14.53902 | -0.1152 | 8.01772 |
March | 514.00000 | 23.50215 | 15.29694 | 0.13379 | 7.04083 |
April | 485.00000 | 24.30723 | 18.49930 | 0.40384 | 9.53864 |
May | 508.00000 | 24.02565 | 22.83177 | -0.4966 | 13.65599 |
June | 496.00000 | 24.37183 | 30.96523 | -0.2174 | 8.00870 |
July | 497.00000 | 24.69794 | 34.44112 | -0.0191 | 7.89324 |
August | 514.00000 | 24.52527 | 30.24677 | -0.1108 | 7.42118 |
September | 485.00000 | 24.07625 | 30.76160 | -0.4205 | 12.38613 |
October | 502.00000 | 23.92422 | 21.55862 | 0.28591 | 7.94362 |
November | 489.00000 | 23.51054 | 16.85310 | 0.12862 | 6.88653 |
December | 497.00000 | 22.96381 | 13.79246 | -0.0459 | 6.99669 |
Annual Sum or Average | 5943.00000 | 23.67490 | 21.94181 | -0.0777 | 8.94708 |
Minimum of Months | 454.00000 | 21.49188 | 12.95908 | -0.4966 | 6.88653 |
Maximum of Months | 514.00000 | 24.69794 | 34.44112 | 0.40384 | 13.65599 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.11521 | 14.79567 | -0.9110 | 24.49218 |
February | 454.00000 | 20.63518 | 17.51763 | -0.7183 | 17.53090 |
March | 514.00000 | 21.27763 | 18.81732 | -0.5082 | 12.46361 |
April | 485.00000 | 22.32561 | 22.32825 | -0.2041 | 7.65795 |
May | 508.00000 | 23.24190 | 24.95161 | -0.9316 | 26.50823 |
June | 496.00000 | 24.00477 | 32.13764 | -0.5489 | 12.49761 |
July | 497.00000 | 24.31836 | 35.56445 | -0.3947 | 9.26465 |
August | 514.00000 | 24.07526 | 31.61883 | -0.5366 | 12.20092 |
September | 485.00000 | 23.40603 | 32.82855 | -0.8150 | 22.53051 |
October | 502.00000 | 22.22567 | 25.33174 | -0.2145 | 7.46322 |
November | 489.00000 | 21.04457 | 20.62085 | -0.5604 | 13.85068 |
December | 497.00000 | 20.25057 | 17.26673 | -0.8234 | 21.55966 |
Annual Sum or Average | 5943.00000 | 22.25636 | 24.52105 | -0.5969 | 15.66166 |
Minimum of Months | 454.00000 | 20.11521 | 14.79567 | -0.9316 | 7.46322 |
Maximum of Months | 514.00000 | 24.31836 | 35.56445 | -0.2041 | 26.50823 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.18562 | 13.36120 | -0.8779 | 23.34532 |
February | 385.00000 | 20.93886 | 15.84220 | -0.6195 | 15.85619 |
March | 433.00000 | 21.46679 | 17.05469 | -0.4301 | 11.83832 |
April | 410.00000 | 22.50606 | 20.76520 | -0.1020 | 8.51557 |
May | 430.00000 | 23.12917 | 23.98938 | -0.8711 | 25.91241 |
June | 418.00000 | 24.06639 | 31.37663 | -0.3965 | 12.75416 |
July | 422.00000 | 24.45674 | 34.78517 | -0.1975 | 9.62676 |
August | 433.00000 | 24.09576 | 30.68498 | -0.3937 | 11.85790 |
September | 410.00000 | 23.44209 | 31.89299 | -0.7029 | 21.82222 |
October | 427.00000 | 22.29497 | 23.79343 | -0.1562 | 7.65825 |
November | 417.00000 | 21.13309 | 18.94806 | -0.5212 | 12.66557 |
December | 422.00000 | 20.24930 | 15.75819 | -0.8124 | 21.03611 |
Annual Sum or Average | 5034.00000 | 22.33845 | 23.21949 | -0.5067 | 15.24373 |
Minimum of Months | 385.00000 | 20.18562 | 13.36120 | -0.8779 | 7.65825 |
Maximum of Months | 433.00000 | 24.45674 | 34.78517 | -0.1020 | 25.91241 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.38950 | 13.09843 | -0.5239 | 16.93614 |
February | 454.00000 | 22.28467 | 15.06334 | -0.2175 | 12.78301 |
March | 514.00000 | 22.35760 | 16.68852 | -0.1616 | 10.56212 |
April | 485.00000 | 22.86648 | 20.72263 | -0.0017 | 8.64968 |
May | 508.00000 | 23.28088 | 24.10730 | -0.8295 | 24.68264 |
June | 496.00000 | 23.90523 | 32.00718 | -0.5073 | 13.77412 |
July | 497.00000 | 24.34016 | 35.30217 | -0.2892 | 9.78159 |
August | 514.00000 | 24.21650 | 30.80873 | -0.3396 | 11.29517 |
September | 485.00000 | 23.87067 | 31.22826 | -0.4834 | 16.98757 |
October | 502.00000 | 23.29636 | 22.69059 | 0.15305 | 9.43181 |
November | 489.00000 | 22.57136 | 18.05462 | -0.1134 | 10.58223 |
December | 497.00000 | 21.55623 | 15.25339 | -0.4349 | 14.93436 |
Annual Sum or Average | 5943.00000 | 22.99979 | 22.96677 | -0.3140 | 13.38351 |
Minimum of Months | 454.00000 | 21.38950 | 13.09843 | -0.8295 | 8.64968 |
Maximum of Months | 514.00000 | 24.34016 | 35.30217 | 0.15305 | 24.68264 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.40964 | 13.58599 | -0.8116 | 21.00208 |
February | 454.00000 | 21.08531 | 15.97271 | -0.5612 | 14.67735 |
March | 514.00000 | 21.54139 | 17.37295 | -0.3915 | 11.13375 |
April | 485.00000 | 22.52392 | 21.05342 | -0.0821 | 8.06668 |
May | 508.00000 | 23.24907 | 24.10142 | -0.8005 | 24.36430 |
June | 496.00000 | 23.87804 | 32.07741 | -0.4548 | 13.15619 |
July | 497.00000 | 24.30396 | 35.41193 | -0.2523 | 9.74301 |
August | 514.00000 | 24.03469 | 31.21604 | -0.4014 | 11.71379 |
September | 485.00000 | 23.32095 | 32.20615 | -0.7187 | 22.20412 |
October | 502.00000 | 22.33438 | 23.99900 | -0.1266 | 7.67064 |
November | 489.00000 | 21.38709 | 19.12035 | -0.4372 | 11.56848 |
December | 497.00000 | 20.54006 | 15.95724 | -0.7200 | 18.32764 |
Annual Sum or Average | 5943.00000 | 22.39456 | 23.55025 | -0.4797 | 14.46960 |
Minimum of Months | 454.00000 | 20.40964 | 13.58599 | -0.8116 | 7.67064 |
Maximum of Months | 514.00000 | 24.30396 | 35.41193 | -0.0821 | 24.36430 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.72353 | 14.99993 | -1.0684 | 31.39711 |
February | 454.00000 | 20.16220 | 17.91623 | -0.8838 | 23.70188 |
March | 514.00000 | 20.67381 | 19.47586 | -0.6954 | 17.77162 |
April | 485.00000 | 21.61144 | 23.29244 | -0.3965 | 11.39704 |
May | 508.00000 | 22.77860 | 25.62690 | -1.1044 | 33.92593 |
June | 496.00000 | 23.81217 | 32.43517 | -0.6126 | 15.19484 |
July | 497.00000 | 24.22749 | 35.66683 | -0.4181 | 10.32879 |
August | 514.00000 | 23.90877 | 31.93096 | -0.5907 | 14.42906 |
September | 485.00000 | 22.97419 | 33.70150 | -0.9720 | 29.76563 |
October | 502.00000 | 21.40964 | 26.64072 | -0.4340 | 11.42396 |
November | 489.00000 | 20.35643 | 21.63568 | -0.7761 | 20.54108 |
December | 497.00000 | 19.89511 | 17.57529 | -0.9808 | 27.81362 |
Annual Sum or Average | 5943.00000 | 21.80844 | 25.11362 | -0.7437 | 20.61993 |
Minimum of Months | 454.00000 | 19.72353 | 14.99993 | -1.1044 | 10.32879 |
Maximum of Months | 514.00000 | 24.22749 | 35.66683 | -0.3965 | 33.92593 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.95613 | 14.16810 | -0.9893 | 27.95978 |
February | 454.00000 | 20.57145 | 16.64313 | -0.7474 | 19.63916 |
March | 514.00000 | 21.13949 | 18.01917 | -0.5393 | 14.92798 |
April | 485.00000 | 22.14918 | 21.59941 | -0.2042 | 10.48580 |
May | 508.00000 | 22.94425 | 24.49837 | -0.9376 | 28.56030 |
June | 496.00000 | 23.96952 | 31.62532 | -0.4054 | 13.29258 |
July | 497.00000 | 24.35044 | 35.09451 | -0.1936 | 9.60082 |
August | 514.00000 | 23.99439 | 31.15021 | -0.3925 | 12.20520 |
September | 485.00000 | 23.25349 | 32.54354 | -0.7664 | 24.39882 |
October | 502.00000 | 21.84379 | 25.03014 | -0.2839 | 9.66089 |
November | 489.00000 | 20.58268 | 20.42196 | -0.6932 | 17.68300 |
December | 497.00000 | 19.99509 | 16.69323 | -0.9348 | 25.96872 |
Annual Sum or Average | 5943.00000 | 22.07493 | 23.99833 | -0.5898 | 17.85194 |
Minimum of Months | 454.00000 | 19.95613 | 14.16810 | -0.9893 | 9.60082 |
Maximum of Months | 514.00000 | 24.35044 | 35.09451 | -0.1936 | 28.56030 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.84249 | 13.57891 | -0.7127 | 21.73173 |
February | 454.00000 | 21.75909 | 15.60517 | -0.3923 | 15.80583 |
March | 514.00000 | 21.78479 | 17.36917 | -0.3407 | 13.84600 |
April | 485.00000 | 22.33463 | 21.48868 | -0.1572 | 10.97605 |
May | 508.00000 | 22.90815 | 24.65880 | -0.9762 | 30.81188 |
June | 496.00000 | 23.70359 | 32.29450 | -0.5730 | 16.70393 |
July | 497.00000 | 24.20950 | 35.50369 | -0.3228 | 11.31462 |
August | 514.00000 | 24.04675 | 31.11230 | -0.3931 | 13.44567 |
September | 485.00000 | 23.54121 | 31.93743 | -0.6103 | 22.08226 |
October | 502.00000 | 22.69560 | 23.74277 | -0.0206 | 10.62058 |
November | 489.00000 | 21.83189 | 19.10948 | -0.3354 | 13.55207 |
December | 497.00000 | 20.88572 | 15.94506 | -0.6520 | 20.12898 |
Annual Sum or Average | 5943.00000 | 22.55164 | 23.57575 | -0.4584 | 16.77098 |
Minimum of Months | 454.00000 | 20.84249 | 13.57891 | -0.9762 | 10.62058 |
Maximum of Months | 514.00000 | 24.20950 | 35.50369 | -0.0206 | 30.81188 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.04296 | 14.00172 | -0.9573 | 26.92193 |
February | 454.00000 | 20.71916 | 16.37774 | -0.6940 | 18.79602 |
March | 514.00000 | 21.12495 | 17.90784 | -0.5311 | 14.68221 |
April | 485.00000 | 22.02790 | 21.75042 | -0.2237 | 10.16443 |
May | 508.00000 | 22.90185 | 24.58320 | -0.9344 | 30.11065 |
June | 496.00000 | 23.67575 | 32.34274 | -0.5189 | 15.93126 |
July | 497.00000 | 24.17198 | 35.61268 | -0.2858 | 11.24042 |
August | 514.00000 | 23.85909 | 31.52457 | -0.4558 | 13.98498 |
September | 485.00000 | 22.99842 | 32.88160 | -0.8396 | 27.65445 |
October | 502.00000 | 21.79325 | 24.93182 | -0.2823 | 9.86190 |
November | 489.00000 | 20.84882 | 20.01181 | -0.6094 | 16.13499 |
December | 497.00000 | 20.16154 | 16.43179 | -0.8674 | 23.80790 |
Annual Sum or Average | 5943.00000 | 22.03836 | 24.07321 | -0.5996 | 18.27076 |
Minimum of Months | 454.00000 | 20.04296 | 14.00172 | -0.9573 | 9.86190 |
Maximum of Months | 514.00000 | 24.17198 | 35.61268 | -0.2237 | 30.11065 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 12724951.54 | 339.30 | 13-JAN-15:20 | 10.56 | 0.124111E+09 | 0.00 | 0.136836E+09 | 0.14 | 9.84 | 25-JAN-07:00 | 0.00 | 0.00 |
February | 0.945217E+09 | 48088.98 | 27-FEB-15:30 | 48.38 | 0.932521E+10 | 0.00 | 0.102704E+11 | 0.70 | 10.00 | 27-FEB-16:00 | 0.00 | 0.00 |
March | 0.210368E+09 | 15706.01 | 14-MAR-13:30 | 61.89 | 0.205447E+10 | 0.00 | 0.226484E+10 | 0.81 | 9.85 | 15-MAR-15:30 | 0.00 | 0.00 |
April | 0.763994E+10 | 143850.99 | 07-APR-14:00 | 152.33 | 0.718664E+11 | 0.00 | 0.795063E+11 | 2.06 | 10.03 | 16-APR-16:03 | 0.00 | 0.00 |
May | 0.223656E+11 | 161572.40 | 31-MAY-16:50 | 247.17 | 0.208278E+12 | 0.00 | 0.230643E+12 | 3.21 | 10.01 | 30-MAY-04:13 | 0.00 | 0.00 |
June | 0.640017E+11 | 166752.28 | 22-JUN-10:00 | 381.41 | 0.562187E+12 | 0.00 | 0.626188E+12 | 4.95 | 10.00 | 11-JUN-10:33 | 0.00 | 0.00 |
July | 0.978135E+11 | 169062.47 | 19-JUL-08:40 | 518.20 | 0.857395E+12 | 0.00 | 0.955208E+12 | 6.45 | 10.02 | 19-JUL-04:12 | 0.00 | 0.00 |
August | 0.854198E+11 | 163543.65 | 08-AUG-09:30 | 486.03 | 0.750616E+12 | 0.00 | 0.836035E+12 | 6.07 | 10.02 | 07-AUG-05:03 | 0.00 | 0.00 |
September | 0.451662E+11 | 177428.24 | 07-SEP-15:03 | 306.11 | 0.402654E+12 | 0.00 | 0.447820E+12 | 4.01 | 10.00 | 24-SEP-11:34 | 0.00 | 0.00 |
October | 0.125884E+11 | 156432.93 | 18-OCT-13:40 | 154.41 | 0.115836E+12 | 0.00 | 0.128424E+12 | 2.00 | 10.00 | 17-OCT-14:40 | 0.00 | 0.00 |
November | 0.685323E+09 | 23170.26 | 03-NOV-14:00 | 53.26 | 0.668296E+10 | 0.00 | 0.736829E+10 | 0.72 | 9.84 | 22-NOV-15:50 | 0.00 | 0.00 |
December | 50879977.34 | 2113.51 | 19-DEC-15:00 | 32.42 | 0.496406E+09 | 0.00 | 0.547286E+09 | 0.43 | 9.85 | 01-DEC-15:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.336900E+12 | 2452.16 | 0.298751E+13 | 0.00 | 0.332441E+13 | 2.64 | 0.00 | 0.00 | ||||
Minimum of Months | 12724951.54 | 339.30 | 10.56 | 0.124111E+09 | 0.00 | 0.136836E+09 | 0.14 | 9.84 | 0.00 | 0.00 | ||
Maximum of Months | 0.978135E+11 | 177428.24 | 518.20 | 0.857395E+12 | 0.00 | 0.955208E+12 | 6.45 | 10.03 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.162515E+10 | 87387.84 | 19-MAY-12:30 | 6.70 | 0.147077E+11 | 0.00 | 0.163329E+11 | 0.08 | 10.72 | 31-MAY-17:00 | 0.00 | 0.00 |
June | 0.170005E+11 | 151665.10 | 21-JUN-12:33 | 62.74 | 0.150474E+12 | 0.00 | 0.167475E+12 | 0.78 | 10.72 | 12-JUN-14:20 | 0.00 | 0.00 |
July | 0.350696E+11 | 161688.81 | 14-JUL-10:02 | 125.92 | 0.310140E+12 | 0.00 | 0.345210E+12 | 1.51 | 10.73 | 24-JUL-09:40 | 0.00 | 0.00 |
August | 0.310023E+11 | 155690.80 | 22-AUG-13:53 | 111.88 | 0.274572E+12 | 0.00 | 0.305574E+12 | 1.34 | 10.73 | 08-AUG-18:40 | 0.00 | 0.00 |
September | 0.896386E+10 | 177428.24 | 07-SEP-15:03 | 32.00 | 0.774165E+11 | 0.00 | 0.863804E+11 | 0.39 | 10.72 | 01-SEP-09:50 | 0.00 | 0.00 |
October | 0.541017E+09 | 99653.39 | 18-OCT-13:45 | 2.33 | 0.506507E+10 | 0.00 | 0.560608E+10 | 0.03 | 9.55 | 18-OCT-13:55 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.942024E+11 | 341.56 | 0.832375E+12 | 0.00 | 0.926578E+12 | 0.35 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.350696E+11 | 177428.24 | 125.92 | 0.310140E+12 | 0.00 | 0.345210E+12 | 1.51 | 10.73 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.508438E+09 | 744.00 | 902.66 | 13-JAN-16:00 | 39731.81 | 13-JAN-16:30 | 18.60 | 18.33 | 17.17 |
February | 0.235003E+10 | 672.00 | 49248.27 | 27-FEB-13:50 | 95848.96 | 18-FEB-16:40 | 19.20 | 18.33 | 17.15 |
March | 0.319668E+10 | 744.00 | 4553.41 | 14-MAR-14:00 | 129429.78 | 31-MAR-17:30 | 19.74 | 18.33 | 17.16 |
April | 0.162732E+11 | 720.00 | 49248.27 | 01-APR-13:45 | 541415.91 | 07-APR-14:00 | 20.84 | 18.51 | 17.17 |
May | 0.247041E+11 | 744.00 | 49248.27 | 02-MAY-11:40 | 257867.38 | 20-MAY-17:02 | 19.59 | 18.90 | 17.17 |
June | 0.573360E+11 | 720.00 | 49248.27 | 01-JUN-15:00 | 510726.89 | 20-JUN-19:00 | 22.99 | 20.79 | 17.16 |
July | 0.918338E+11 | 744.00 | 49248.27 | 01-JUL-00:03 | 671056.90 | 19-JUL-10:50 | 29.02 | 23.90 | 17.17 |
August | 0.895567E+11 | 744.00 | 49248.27 | 01-AUG-00:03 | 776149.17 | 08-AUG-12:00 | 29.59 | 23.21 | 17.17 |
September | 0.444545E+11 | 720.00 | 49248.27 | 01-SEP-00:03 | 338668.93 | 07-SEP-16:00 | 21.03 | 20.06 | 17.15 |
October | 0.143660E+11 | 744.00 | 49248.27 | 12-OCT-10:50 | 312324.06 | 18-OCT-15:00 | 19.65 | 18.54 | 17.17 |
November | 0.420543E+10 | 720.00 | 33001.69 | 17-NOV-17:00 | 136894.29 | 17-NOV-17:00 | 19.74 | 18.33 | 17.17 |
December | 0.323408E+10 | 744.00 | 4641.34 | 10-DEC-02:00 | 177531.04 | 22-DEC-17:20 | 20.07 | 18.33 | 17.17 |
Annual Sum or Average | 0.352019E+12 | 8760.00 | 21.70 | 19.64 | 17.16 | ||||
Minimum of Months | 0.508438E+09 | 672.00 | 902.66 | 39731.81 | 18.60 | 18.33 | 17.15 | ||
Maximum of Months | 0.918338E+11 | 744.00 | 49248.27 | 776149.17 | 29.59 | 23.90 | 17.17 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 223171.78 | 25-JAN-06:25 | 20.97 | 20.97 | 0.06 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 535280.37 | 27-FEB-15:30 | 20.92 | 20.90 | 1.15 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 223407.43 | 03-MAR-06:13 | 20.85 | 20.84 | 0.47 |
April | 39575145.41 | 40.80 | 1754.30 | 06-APR-16:00 | 1189009.43 | 07-APR-14:00 | 21.05 | 20.91 | 5.55 |
May | 0.265451E+09 | 130.40 | 3417.94 | 19-MAY-17:00 | 1243750.17 | 31-MAY-16:50 | 21.51 | 21.12 | 12.75 |
June | 0.270320E+10 | 289.85 | 16598.31 | 06-JUN-14:05 | 1288609.79 | 05-JUN-12:30 | 22.21 | 21.10 | 26.83 |
July | 0.512298E+10 | 408.56 | 16598.31 | 01-JUL-13:00 | 1310506.13 | 13-JUL-18:53 | 22.82 | 21.15 | 35.50 |
August | 0.254926E+10 | 356.47 | 16598.31 | 05-AUG-11:00 | 1285965.93 | 08-AUG-09:30 | 22.54 | 21.07 | 31.55 |
September | 0.186703E+10 | 219.38 | 16598.31 | 02-SEP-11:00 | 1319293.04 | 07-SEP-15:03 | 21.94 | 21.16 | 20.10 |
October | 0.104514E+09 | 66.03 | 2285.37 | 18-OCT-13:45 | 1262118.48 | 18-OCT-13:40 | 21.22 | 21.01 | 7.18 |
November | 380614.76 | 3.58 | 68.49 | 03-NOV-14:00 | 258347.95 | 03-NOV-14:00 | 20.95 | 20.94 | 1.41 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 223350.34 | 03-DEC-12:23 | 20.99 | 20.98 | 0.19 |
Annual Sum or Average | 0.126524E+11 | 1515.08 | 21.50 | 21.01 | 11.96 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 223171.78 | 20.85 | 20.84 | 0.06 | ||
Maximum of Months | 0.512298E+10 | 408.56 | 16598.31 | 1319293.04 | 22.82 | 21.16 | 35.50 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 20.97 | 20.97 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 20.92 | 20.92 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 20.85 | 20.85 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 21.05 | 21.05 | 0.00 |
May | 29102430.27 | 4.70 | 2825.65 | 19-MAY-16:30 | 1167147.35 | 19-MAY-14:40 | 21.51 | 21.48 | 0.36 |
June | 0.106519E+10 | 53.32 | 16598.31 | 20-JUN-11:10 | 1173435.25 | 30-JUN-16:00 | 22.21 | 21.91 | 4.20 |
July | 0.245603E+10 | 109.08 | 16598.31 | 13-JUL-12:50 | 1179048.37 | 24-JUL-15:10 | 22.82 | 22.20 | 8.32 |
August | 0.132523E+10 | 97.90 | 16598.31 | 05-AUG-13:10 | 1176161.55 | 30-AUG-14:00 | 22.54 | 21.98 | 7.47 |
September | 0.813968E+09 | 24.92 | 16598.31 | 02-SEP-13:03 | 1319293.04 | 07-SEP-15:03 | 21.94 | 21.79 | 1.94 |
October | 19197123.93 | 2.33 | 2285.37 | 18-OCT-13:45 | 1002335.87 | 18-OCT-13:45 | 21.22 | 21.21 | 0.18 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 20.95 | 20.95 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 20.99 | 20.99 | 0.00 |
Annual Sum or Average | 0.570871E+10 | 292.26 | 21.50 | 21.36 | 1.89 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.85 | 20.85 | 0.00 | ||
Maximum of Months | 0.245603E+10 | 109.08 | 16598.31 | 1319293.04 | 22.82 | 22.20 | 8.32 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.843703E+12 | 0.00 | 575.17 | 1924066.64 | 09-JAN-07:15 | 0.00 | 32.38 | 69.74 | 1.72 | 0.00 | 0.10 | 0.64 | 09-JAN-07:15 |
February | 0.428068E+12 | 0.00 | 417.53 | 2015336.17 | 07-FEB-06:01 | 0.00 | 28.27 | 60.54 | 0.89 | 0.00 | 0.06 | 0.67 | 07-FEB-06:01 |
March | 0.239316E+12 | 0.00 | 389.00 | 1718696.90 | 06-MAR-06:02 | 0.00 | 26.00 | 54.49 | 0.42 | 0.00 | 0.03 | 0.57 | 06-MAR-06:02 |
April | 0.565124E+11 | 0.00 | 206.54 | 1477967.30 | 29-APR-05:01 | 0.00 | 23.09 | 39.71 | 0.09 | 0.00 | 0.01 | 0.49 | 29-APR-05:01 |
May | 0.341470E+11 | 0.00 | 125.61 | 1567932.15 | 08-MAY-04:01 | 0.00 | 23.19 | 32.87 | 0.06 | 0.00 | 0.00 | 0.52 | 08-MAY-04:01 |
June | 0.963996E+09 | 0.00 | 25.32 | 127503.67 | 17-JUN-05:03 | 0.00 | 22.30 | 24.39 | 0.00 | 0.00 | 0.00 | 0.04 | 17-JUN-05:03 |
July | 2155051.52 | 0.00 | 1.64 | 1484.52 | 08-JUL-05:10 | 0.00 | 22.16 | 22.29 | 0.00 | 0.00 | 0.00 | 0.00 | 08-JUL-05:10 |
August | 0.179673E+09 | 0.00 | 7.97 | 128029.53 | 18-AUG-05:02 | 0.00 | 22.11 | 22.75 | 0.00 | 0.00 | 0.00 | 0.04 | 18-AUG-05:02 |
September | 0.844001E+10 | 0.00 | 87.08 | 570554.62 | 19-SEP-05:03 | 0.00 | 21.85 | 29.08 | 0.01 | 0.00 | 0.00 | 0.19 | 19-SEP-05:03 |
October | 0.441662E+11 | 0.00 | 204.00 | 1611023.12 | 10-OCT-04:01 | 0.00 | 22.70 | 38.68 | 0.07 | 0.00 | 0.01 | 0.53 | 10-OCT-04:01 |
November | 0.199052E+12 | 0.00 | 382.44 | 1699993.10 | 27-NOV-06:02 | 0.00 | 25.50 | 54.78 | 0.36 | 0.00 | 0.03 | 0.56 | 27-NOV-06:02 |
December | 0.524955E+12 | 0.00 | 531.19 | 1722956.70 | 26-DEC-06:01 | 0.00 | 30.21 | 66.61 | 0.99 | 0.00 | 0.06 | 0.57 | 26-DEC-06:01 |
Annual Sum or Average | 0.237950E+13 | 0.00 | 2953.51 | 0.00 | 24.97 | 42.92 | 0.38 | 0.00 | 0.02 | ||||
Minimum of Months | 2155051.52 | 0.00 | 1.64 | 1484.52 | 0.00 | 21.85 | 22.29 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.843703E+12 | 0.00 | 575.17 | 2015336.17 | 0.00 | 32.38 | 69.74 | 1.72 | 0.00 | 0.10 | 0.67 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 18.60 | 18.60 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 19.20 | 19.20 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 19.74 | 19.74 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 20.84 | 20.84 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 19.59 | 19.59 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 22.99 | 22.99 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 29.02 | 29.02 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 29.59 | 29.59 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 21.03 | 21.03 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 19.65 | 19.65 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 19.74 | 19.74 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 20.07 | 20.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 21.70 | 21.70 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.60 | 18.60 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.59 | 29.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 |
February | 0.829644E+09 | 0.00 | 13.22 | 0.829644E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49035.44 | 27-FEB-15:30 | 49035.44 | 27-FEB-15:30 | 0.00 | 0.00 | 0.00 |
March | 96048767.10 | 0.00 | 3.60 | 96048767.10 | 0.00 | 0.00 | 0.00 | 0.00 | 16129.04 | 14-MAR-13:30 | 16129.04 | 14-MAR-13:30 | 0.00 | 0.00 | 0.00 |
April | 0.723999E+10 | 0.00 | 78.99 | 0.723999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88869.05 | 06-APR-16:00 | 88869.05 | 06-APR-16:00 | 0.00 | 0.00 | 0.00 |
May | 0.196788E+11 | 0.00 | 171.37 | 0.196788E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 119387.31 | 19-MAY-15:20 | 119387.31 | 19-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.656334E+11 | 0.00 | 350.32 | 0.652533E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 158091.90 | 21-JUN-12:43 | 147542.53 | 22-JUN-10:23 | 0.00 | 0.00 | 0.00 |
July | 0.118398E+12 | 0.00 | 490.43 | 0.117563E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 165591.25 | 19-JUL-09:30 | 163733.19 | 25-JUL-17:06 | 0.00 | 0.00 | 0.00 |
August | 0.101488E+12 | 0.00 | 462.10 | 0.101487E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 162842.82 | 10-AUG-12:48 | 162842.82 | 10-AUG-12:48 | 0.00 | 0.00 | 0.00 |
September | 0.439599E+11 | 0.00 | 260.19 | 0.421459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 205965.45 | 07-SEP-15:10 | 144674.58 | 01-SEP-10:53 | 0.00 | 0.00 | 0.00 |
October | 0.115280E+11 | 0.00 | 111.77 | 0.115280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 111545.47 | 18-OCT-13:40 | 111545.47 | 18-OCT-13:40 | 0.00 | 0.00 | 0.00 |
November | 0.657276E+09 | 0.00 | 22.77 | 0.657276E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23712.77 | 03-NOV-13:55 | 23712.77 | 03-NOV-13:55 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.369509E+12 | 0.00 | 1964.75 | 0.366479E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.118398E+12 | 0.00 | 490.43 | 0.117563E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 205965.45 | 163733.19 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 39167.31 | 0.00 | 16.42 | 39167.31 | 0.00 | 0.00 | 0.00 | 0.00 | 1.36 | 25-JAN-05:01 | 1.36 | 25-JAN-05:01 | 0.00 | 0.00 | 0.00 |
February | 0.697947E+10 | 0.00 | 37.47 | 0.697947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 370116.31 | 27-FEB-15:30 | 370116.31 | 27-FEB-15:30 | 0.00 | 0.00 | 0.00 |
March | 0.572049E+09 | 0.00 | 37.22 | 0.572049E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 113681.55 | 14-MAR-13:30 | 113681.55 | 14-MAR-13:30 | 0.00 | 0.00 | 0.00 |
April | 0.526562E+11 | 0.00 | 112.45 | 0.526562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 721726.87 | 06-APR-16:00 | 721726.87 | 06-APR-16:00 | 0.00 | 0.00 | 0.00 |
May | 0.169393E+12 | 0.00 | 188.41 | 0.169393E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1135370.82 | 19-MAY-15:30 | 1135370.82 | 19-MAY-15:30 | 0.00 | 0.00 | 0.00 |
June | 0.541920E+12 | 0.00 | 334.06 | 0.539102E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1470662.12 | 21-JUN-12:55 | 1353329.56 | 20-JUN-13:13 | 0.00 | 0.00 | 0.00 |
July | 0.900239E+12 | 0.00 | 421.64 | 0.896957E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1528604.40 | 25-JUL-16:42 | 1528604.40 | 25-JUL-16:42 | 0.00 | 0.00 | 0.00 |
August | 0.782169E+12 | 0.00 | 389.44 | 0.782162E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1500890.69 | 10-AUG-12:25 | 1500890.69 | 10-AUG-12:25 | 0.00 | 0.00 | 0.00 |
September | 0.367892E+12 | 0.00 | 267.56 | 0.353045E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1843900.44 | 07-SEP-14:45 | 1239851.41 | 04-SEP-14:11 | 0.00 | 0.00 | 0.00 |
October | 0.912374E+11 | 0.00 | 134.58 | 0.912374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 944621.83 | 18-OCT-15:30 | 944621.83 | 18-OCT-15:30 | 0.00 | 0.00 | 0.00 |
November | 0.476004E+10 | 0.00 | 48.31 | 0.476004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 188549.79 | 03-NOV-13:55 | 188549.79 | 03-NOV-13:55 | 0.00 | 0.00 | 0.00 |
December | 67101.34 | 0.00 | 28.59 | 67101.34 | 0.00 | 0.00 | 0.00 | 0.00 | 1.96 | 26-DEC-06:01 | 1.96 | 26-DEC-06:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.291782E+13 | 0.00 | 2016.14 | 0.289687E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 39167.31 | 0.00 | 16.42 | 39167.31 | 0.00 | 0.00 | 0.00 | 0.00 | 1.36 | 1.36 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.900239E+12 | 0.00 | 421.64 | 0.896957E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1843900.44 | 1528604.40 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 171.26 | 0.00 | 0.14 | 171.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 | 29-JAN-16:00 | 0.35 | 29-JAN-16:00 | 0.00 | 0.00 | 0.00 |
February | 0.456340E+09 | 0.00 | 11.66 | 0.456340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31333.67 | 27-FEB-13:40 | 31333.67 | 27-FEB-13:40 | 0.00 | 0.00 | 0.00 |
March | 8668216.63 | 0.00 | 1.17 | 8668216.63 | 0.00 | 0.00 | 0.00 | 0.00 | 3519.53 | 14-MAR-13:30 | 3519.53 | 14-MAR-13:30 | 0.00 | 0.00 | 0.00 |
April | 0.487962E+10 | 0.00 | 70.58 | 0.487962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72929.22 | 06-APR-16:00 | 72929.22 | 06-APR-16:00 | 0.00 | 0.00 | 0.00 |
May | 0.174351E+11 | 0.00 | 160.16 | 0.174351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 142243.07 | 19-MAY-15:00 | 142243.07 | 19-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.587930E+11 | 0.00 | 324.86 | 0.584634E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 170130.31 | 21-JUN-12:43 | 155363.93 | 21-JUN-12:43 | 0.00 | 0.00 | 0.00 |
July | 0.984974E+11 | 0.00 | 418.82 | 0.981940E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 178771.37 | 25-JUL-16:58 | 178771.37 | 25-JUL-16:58 | 0.00 | 0.00 | 0.00 |
August | 0.832925E+11 | 0.00 | 381.27 | 0.832925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 174534.18 | 10-AUG-12:43 | 174534.18 | 10-AUG-12:43 | 0.00 | 0.00 | 0.00 |
September | 0.373875E+11 | 0.00 | 240.92 | 0.358716E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 215213.69 | 07-SEP-15:10 | 147678.88 | 04-SEP-16:51 | 0.00 | 0.00 | 0.00 |
October | 0.777640E+10 | 0.00 | 100.17 | 0.777640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96691.40 | 18-OCT-15:10 | 96691.40 | 18-OCT-15:10 | 0.00 | 0.00 | 0.00 |
November | 0.352038E+09 | 0.00 | 17.77 | 0.352038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11631.75 | 03-NOV-14:00 | 11631.75 | 03-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 63966.67 | 0.00 | 0.19 | 63966.67 | 0.00 | 0.00 | 0.00 | 0.00 | 743.91 | 26-DEC-05:07 | 743.91 | 26-DEC-05:07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.308879E+12 | 0.00 | 1727.71 | 0.306730E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 171.26 | 0.00 | 0.14 | 171.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 | 0.35 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.984974E+11 | 0.00 | 418.82 | 0.981940E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 215213.69 | 178771.37 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 2426094.96 | 0.00 | 0.83 | 2426094.96 | 0.00 | 0.00 | 0.00 | 0.00 | 1645.76 | 13-JAN-15:00 | 1645.76 | 13-JAN-15:00 | 0.00 | 0.00 | 0.00 |
February | 0.612397E+09 | 0.00 | 19.35 | 0.612397E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 31518.44 | 27-FEB-15:00 | 31518.44 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.607438E+09 | 0.00 | 26.83 | 0.607438E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18326.93 | 14-MAR-14:00 | 18326.93 | 14-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.512983E+10 | 0.00 | 92.83 | 0.512983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48308.17 | 07-APR-14:00 | 48308.17 | 07-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.138276E+11 | 0.00 | 180.98 | 0.137866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58504.63 | 19-MAY-15:00 | 58504.63 | 19-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.329090E+11 | 0.00 | 234.54 | 0.326215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91364.00 | 20-JUN-13:13 | 84279.82 | 22-JUN-16:00 | 0.00 | 0.00 | 0.00 |
July | 0.362294E+11 | 0.00 | 201.34 | 0.361969E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91647.30 | 31-JUL-15:45 | 91647.30 | 31-JUL-15:45 | 0.00 | 0.00 | 0.00 |
August | 0.435176E+11 | 0.00 | 261.12 | 0.435137E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88405.11 | 12-AUG-14:00 | 88405.11 | 12-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.236166E+11 | 0.00 | 187.66 | 0.223046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 113858.90 | 07-SEP-14:35 | 92580.11 | 02-SEP-13:07 | 0.00 | 0.00 | 0.00 |
October | 0.813891E+10 | 0.00 | 96.50 | 0.813891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67498.39 | 18-OCT-13:45 | 67498.39 | 18-OCT-13:45 | 0.00 | 0.00 | 0.00 |
November | 0.270991E+09 | 0.00 | 11.06 | 0.270991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 27727.14 | 17-NOV-07:11 | 27727.14 | 17-NOV-07:11 | 0.00 | 0.00 | 0.00 |
December | 66662951.59 | 0.00 | 4.00 | 66662951.59 | 0.00 | 0.00 | 0.00 | 0.00 | 10964.81 | 19-DEC-15:00 | 10964.81 | 19-DEC-15:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164929E+12 | 0.00 | 1317.06 | 0.163252E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2426094.96 | 0.00 | 0.83 | 2426094.96 | 0.00 | 0.00 | 0.00 | 0.00 | 1645.76 | 1645.76 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.435176E+11 | 0.00 | 261.12 | 0.435137E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 113858.90 | 92580.11 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.932156E+10 | 0.563467E+10 | 744.00 | 0.814413E+10 | 0.117743E+10 | 0.00 | 0.02 | 03-JAN-14:40 | 0.02 | 10-JAN-22:01 | 5358.43 | 03-JAN-14:40 | 4855.01 | 03-JAN-15:00 | 511.37 | 22-JAN-14:00 | 2638.44 | 03-JAN-14:40 | 0.00 |
February | 0.133897E+11 | 0.665729E+10 | 672.00 | 0.119217E+11 | 0.146807E+10 | 0.00 | 0.03 | 13-FEB-19:40 | 0.02 | 01-FEB-08:10 | 5990.05 | 22-FEB-19:00 | 5142.05 | 13-FEB-05:22 | 932.64 | 28-FEB-01:00 | 3532.76 | 13-FEB-19:40 | 0.00 |
March | 0.147274E+11 | 0.765149E+10 | 744.00 | 0.141123E+11 | 0.615098E+09 | 0.00 | 0.03 | 31-MAR-23:10 | 0.02 | 06-MAR-09:05 | 6525.62 | 31-MAR-23:10 | 5495.39 | 31-MAR-23:10 | 1093.50 | 01-MAR-00:10 | 3196.34 | 31-MAR-23:10 | 0.00 |
April | 0.567507E+11 | 0.209766E+11 | 720.00 | 0.545570E+11 | 0.219364E+10 | 0.00 | 0.78 | 07-APR-14:00 | 0.02 | 30-APR-23:20 | 307283.12 | 07-APR-14:00 | 307283.12 | 07-APR-14:00 | 16359.78 | 24-APR-11:00 | 108146.17 | 07-APR-14:00 | 0.00 |
May | 0.176319E+11 | 0.876987E+10 | 728.71 | 0.164396E+11 | 0.119226E+10 | 0.00 | 0.35 | 19-MAY-15:00 | 0.00 | 04-MAY-18:00 | 145894.10 | 19-MAY-13:50 | 139334.88 | 19-MAY-16:00 | 9442.94 | 19-MAY-12:30 | 53860.00 | 20-MAY-16:00 | 0.00 |
June | 0.128729E+12 | 0.463661E+11 | 641.03 | 0.116404E+12 | 0.123248E+11 | 0.00 | 0.69 | 20-JUN-18:50 | 0.00 | 17-JUN-24:00 | 335421.14 | 20-JUN-18:50 | 234742.11 | 23-JUN-15:50 | 114280.99 | 20-JUN-20:00 | 103797.61 | 20-JUN-18:50 | 0.00 |
July | 0.422518E+12 | 0.144909E+12 | 677.97 | 0.380650E+12 | 0.418677E+11 | 0.00 | 0.87 | 19-JUL-10:50 | 0.00 | 27-JUL-06:22 | 428612.04 | 19-JUL-10:50 | 328420.19 | 17-JUL-16:00 | 140387.14 | 18-JUL-20:00 | 146731.63 | 17-JUL-16:00 | 0.00 |
August | 0.524374E+12 | 0.175033E+12 | 733.28 | 0.483500E+12 | 0.408741E+11 | 0.00 | 1.00 | 08-AUG-12:00 | 0.01 | 21-AUG-00:55 | 485040.74 | 08-AUG-12:00 | 418757.56 | 07-AUG-16:00 | 112425.64 | 01-AUG-00:53 | 176501.45 | 05-AUG-16:00 | 0.00 |
September | 0.456912E+11 | 0.190933E+11 | 642.59 | 0.416767E+11 | 0.401451E+10 | 0.00 | 0.46 | 07-SEP-16:00 | 0.00 | 24-SEP-10:52 | 224253.23 | 07-SEP-16:00 | 145299.95 | 01-SEP-13:10 | 92821.31 | 07-SEP-16:00 | 68529.11 | 07-SEP-16:00 | 0.00 |
October | 0.220698E+11 | 0.990214E+10 | 743.33 | 0.205604E+11 | 0.150934E+10 | 0.00 | 0.45 | 18-OCT-14:00 | 0.01 | 01-OCT-01:10 | 175994.44 | 18-OCT-15:00 | 175994.44 | 18-OCT-15:00 | 944.59 | 14-OCT-08:50 | 63629.59 | 18-OCT-14:00 | 0.00 |
November | 0.147600E+11 | 0.754706E+10 | 720.00 | 0.139996E+11 | 0.760416E+09 | 0.00 | 0.10 | 17-NOV-17:00 | 0.02 | 18-NOV-13:25 | 34438.33 | 17-NOV-17:00 | 32730.80 | 17-NOV-17:00 | 1707.53 | 17-NOV-17:00 | 11594.32 | 17-NOV-17:00 | 0.00 |
December | 0.149816E+11 | 0.803717E+10 | 744.00 | 0.147299E+11 | 0.251689E+09 | 0.00 | 0.07 | 10-DEC-02:00 | 0.03 | 10-DEC-09:25 | 21371.73 | 10-DEC-02:00 | 21371.73 | 10-DEC-02:00 | 1384.96 | 19-DEC-19:20 | 8356.80 | 10-DEC-02:00 | 0.00 |
Annual Sum or Average | 0.128494E+13 | 0.460578E+12 | 8510.92 | 0.117670E+13 | 0.108249E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.932156E+10 | 0.563467E+10 | 641.03 | 0.814413E+10 | 0.251689E+09 | 0.00 | 0.02 | 0.00 | 5358.43 | 4855.01 | 511.37 | 2638.44 | 0.00 | ||||||
Maximum of Months | 0.524374E+12 | 0.175033E+12 | 744.00 | 0.483500E+12 | 0.418677E+11 | 0.00 | 1.00 | 0.03 | 485040.74 | 418757.56 | 140387.14 | 176501.45 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.323685E+10 | 0.925622E+09 | 739.14 | 0.323653E+10 | 318211.64 | 0.00 | 0.31 | 29-JAN-16:42 | 0.00 | 08-JAN-02:12 | 2382.32 | 13-JAN-16:20 | 2382.32 | 13-JAN-16:20 | 13.98 | 02-JAN-07:05 | 663.41 | 29-JAN-16:42 | 0.00 |
February | 0.842734E+10 | 0.221311E+10 | 672.00 | 0.842734E+10 | 0.00 | 0.00 | 0.61 | 26-FEB-17:13 | 0.28 | 01-FEB-07:03 | 5295.53 | 26-FEB-17:17 | 5295.53 | 26-FEB-17:17 | 0.00 | 28-FEB-13:20 | 1343.02 | 26-FEB-17:13 | 0.00 |
March | 0.150744E+11 | 0.373497E+10 | 744.00 | 0.150744E+11 | -0.0 | 0.00 | 0.81 | 31-MAR-24:00 | 0.53 | 06-MAR-07:03 | 7508.42 | 31-MAR-24:00 | 7508.42 | 31-MAR-24:00 | 0.00 | 08-MAR-04:00 | 1771.08 | 31-MAR-24:00 | 0.00 |
April | 0.201382E+11 | 0.474485E+10 | 720.00 | 0.201294E+11 | 8822366.52 | 0.00 | 1.00 | 16-APR-17:31 | 0.31 | 30-APR-24:00 | 9189.30 | 16-APR-18:16 | 9189.30 | 16-APR-18:16 | 127.90 | 17-APR-16:10 | 2426.88 | 07-APR-14:00 | 0.00 |
May | 0.576410E+10 | 0.155015E+10 | 744.00 | 0.573897E+10 | 25128106.30 | 0.00 | 0.47 | 31-MAY-24:00 | 0.15 | 08-MAY-06:30 | 4153.90 | 31-MAY-24:00 | 4153.90 | 31-MAY-24:00 | 152.28 | 30-MAY-09:30 | 1036.03 | 31-MAY-24:00 | 0.00 |
June | 0.110618E+11 | 0.294954E+10 | 720.00 | 0.109697E+11 | 92076928.61 | 0.00 | 0.66 | 30-JUN-23:13 | 0.39 | 17-JUN-06:20 | 6035.60 | 30-JUN-23:55 | 6021.70 | 30-JUN-24:00 | 307.96 | 06-JUN-16:40 | 1821.48 | 29-JUN-15:00 | 0.00 |
July | 0.168624E+11 | 0.475667E+10 | 744.00 | 0.167581E+11 | 0.104279E+09 | 0.00 | 0.90 | 16-JUL-18:45 | 0.62 | 08-JUL-06:11 | 7934.34 | 31-JUL-23:50 | 7934.34 | 31-JUL-23:50 | 350.63 | 03-JUL-16:50 | 3051.04 | 17-JUL-16:00 | 0.00 |
August | 0.216585E+11 | 0.579484E+10 | 744.00 | 0.215777E+11 | 80814033.94 | 0.00 | 1.00 | 04-AUG-17:50 | 0.30 | 31-AUG-24:00 | 9138.51 | 05-AUG-19:44 | 9138.51 | 05-AUG-19:44 | 416.68 | 22-AUG-15:50 | 3488.65 | 06-AUG-16:00 | 0.00 |
September | 0.586339E+10 | 0.162169E+10 | 720.00 | 0.577534E+10 | 88052966.58 | 0.00 | 0.46 | 04-SEP-17:55 | 0.17 | 19-SEP-06:55 | 3985.38 | 30-SEP-24:00 | 3985.38 | 30-SEP-24:00 | 348.35 | 07-SEP-15:10 | 1430.96 | 04-SEP-17:21 | 0.00 |
October | 0.106501E+11 | 0.267316E+10 | 744.00 | 0.106387E+11 | 11425496.22 | 0.00 | 0.64 | 31-OCT-24:00 | 0.36 | 10-OCT-06:03 | 5644.22 | 31-OCT-24:00 | 5644.22 | 31-OCT-24:00 | 111.08 | 25-OCT-11:00 | 1515.23 | 15-OCT-16:55 | 0.00 |
November | 0.147285E+11 | 0.360443E+10 | 720.00 | 0.147263E+11 | 2198065.95 | 0.00 | 0.74 | 12-NOV-16:23 | 0.53 | 27-NOV-07:03 | 6766.64 | 12-NOV-16:27 | 6766.64 | 12-NOV-16:27 | 76.69 | 17-NOV-17:05 | 1613.26 | 12-NOV-16:23 | 0.00 |
December | 0.196341E+11 | 0.476255E+10 | 744.00 | 0.196338E+11 | 229999.18 | 0.00 | 0.91 | 10-DEC-16:03 | 0.73 | 29-DEC-07:02 | 8438.72 | 10-DEC-16:05 | 8438.72 | 10-DEC-16:05 | 48.90 | 19-DEC-17:05 | 1986.70 | 10-DEC-16:03 | 0.00 |
Annual Sum or Average | 0.153100E+12 | 0.393316E+11 | 8755.14 | 0.152686E+12 | 0.413345E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.323685E+10 | 0.925622E+09 | 672.00 | 0.323653E+10 | -0.0 | 0.00 | 0.31 | 0.00 | 2382.32 | 2382.32 | 0.00 | 663.41 | 0.00 | ||||||
Maximum of Months | 0.216585E+11 | 0.579484E+10 | 744.00 | 0.215777E+11 | 0.104279E+09 | 0.00 | 1.00 | 0.73 | 9189.30 | 9189.30 | 416.68 | 3488.65 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.990813E+10 | 0.306943E+10 | 519.07 | 0.990492E+10 | 3203610.35 | 0.00 | 0.26 | 19-JAN-16:50 | 0.00 | 01-JAN-07:20 | 19755.37 | 13-JAN-16:30 | 19755.37 | 13-JAN-16:30 | 114.77 | 01-JAN-15:43 | 5363.89 | 19-JAN-16:50 | 0.00 |
February | 0.615817E+11 | 0.165247E+11 | 672.00 | 0.615817E+11 | 0.00 | 0.00 | 0.57 | 26-FEB-17:22 | 0.13 | 06-FEB-04:04 | 46714.05 | 26-FEB-17:23 | 46714.05 | 26-FEB-17:23 | 0.00 | 16-FEB-08:10 | 11962.34 | 26-FEB-17:22 | 0.00 |
March | 0.127095E+12 | 0.319214E+11 | 744.00 | 0.127095E+12 | -0.0 | 0.00 | 0.75 | 28-MAR-17:50 | 0.37 | 06-MAR-07:03 | 65721.59 | 31-MAR-23:40 | 65721.59 | 31-MAR-23:40 | 0.00 | 15-MAR-22:40 | 15730.42 | 28-MAR-17:50 | 0.00 |
April | 0.181933E+12 | 0.432304E+11 | 720.00 | 0.181844E+12 | 89189699.54 | 0.00 | 0.98 | 16-APR-17:51 | 0.17 | 30-APR-24:00 | 85543.24 | 22-APR-18:19 | 85543.24 | 22-APR-18:19 | 1275.66 | 17-APR-16:10 | 23041.33 | 07-APR-14:00 | 0.00 |
May | 0.479401E+11 | 0.130430E+11 | 744.00 | 0.476947E+11 | 0.245372E+09 | 0.00 | 0.47 | 31-MAY-24:00 | 0.05 | 08-MAY-06:05 | 39349.52 | 31-MAY-24:00 | 39349.52 | 31-MAY-24:00 | 1468.16 | 30-MAY-09:40 | 9833.56 | 31-MAY-24:00 | 0.00 |
June | 0.101946E+12 | 0.273375E+11 | 720.00 | 0.101033E+12 | 0.912618E+09 | 0.00 | 0.67 | 30-JUN-23:13 | 0.34 | 17-JUN-06:10 | 58966.25 | 30-JUN-23:55 | 58828.61 | 30-JUN-24:00 | 3022.87 | 06-JUN-16:40 | 17476.60 | 28-JUN-19:00 | 0.00 |
July | 0.158125E+12 | 0.447517E+11 | 744.00 | 0.157088E+12 | 0.103695E+10 | 0.00 | 0.88 | 16-JUL-18:45 | 0.58 | 08-JUL-06:10 | 76718.08 | 31-JUL-23:53 | 76718.08 | 31-JUL-23:53 | 3431.20 | 03-JUL-16:50 | 28291.07 | 17-JUL-16:00 | 0.00 |
August | 0.204303E+12 | 0.548470E+11 | 744.00 | 0.203498E+12 | 0.804523E+09 | 0.00 | 1.00 | 04-AUG-18:00 | 0.26 | 31-AUG-24:00 | 87496.49 | 05-AUG-19:42 | 87496.49 | 05-AUG-19:42 | 4080.64 | 22-AUG-15:50 | 33550.68 | 06-AUG-16:00 | 0.00 |
September | 0.497790E+11 | 0.139476E+11 | 720.00 | 0.489197E+11 | 0.859365E+09 | 0.00 | 0.45 | 04-SEP-17:41 | 0.10 | 19-SEP-06:05 | 35811.90 | 30-SEP-23:30 | 35811.90 | 30-SEP-23:30 | 3486.20 | 07-SEP-15:10 | 13430.32 | 04-SEP-17:41 | 0.00 |
October | 0.898030E+11 | 0.228242E+11 | 744.00 | 0.896889E+11 | 0.114093E+09 | 0.00 | 0.59 | 15-OCT-16:55 | 0.25 | 10-OCT-06:03 | 49298.18 | 15-OCT-17:10 | 49298.18 | 15-OCT-17:10 | 1091.33 | 25-OCT-11:00 | 13919.11 | 18-OCT-16:00 | 0.00 |
November | 0.122989E+12 | 0.305538E+11 | 720.00 | 0.122967E+12 | 22508070.08 | 0.00 | 0.69 | 13-NOV-16:30 | 0.38 | 27-NOV-07:03 | 61719.31 | 03-NOV-16:00 | 61169.74 | 03-NOV-16:00 | 742.06 | 17-NOV-17:05 | 14587.95 | 13-NOV-16:30 | 0.00 |
December | 0.161820E+12 | 0.400072E+11 | 744.00 | 0.161817E+12 | 3060348.99 | 0.00 | 0.83 | 06-DEC-16:10 | 0.55 | 31-DEC-24:00 | 77192.30 | 06-DEC-16:10 | 76896.46 | 06-DEC-16:10 | 519.95 | 19-DEC-17:05 | 17572.77 | 06-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.131722E+13 | 0.342058E+12 | 8535.07 | 0.131313E+13 | 0.409088E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.990813E+10 | 0.306943E+10 | 519.07 | 0.990492E+10 | -0.0 | 0.00 | 0.26 | 0.00 | 19755.37 | 19755.37 | 0.00 | 5363.89 | 0.00 | ||||||
Maximum of Months | 0.204303E+12 | 0.548470E+11 | 744.00 | 0.203498E+12 | 0.103695E+10 | 0.00 | 1.00 | 0.58 | 87496.49 | 87496.49 | 4080.64 | 33550.68 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.284527E+09 | 90959335.74 | 188.88 | 0.284337E+09 | 190286.93 | 0.00 | 0.24 | 13-JAN-16:30 | 0.00 | 01-JAN-00:05 | 1910.82 | 13-JAN-16:30 | 1910.82 | 13-JAN-16:30 | 15.60 | 02-JAN-13:50 | 505.58 | 13-JAN-16:30 | 0.00 |
February | 0.457896E+10 | 0.125134E+10 | 653.32 | 0.457896E+10 | -0.0 | 0.00 | 0.52 | 26-FEB-17:22 | 0.00 | 05-FEB-04:10 | 4447.73 | 28-FEB-17:00 | 4447.73 | 28-FEB-17:00 | 0.00 | 28-FEB-21:30 | 1107.24 | 26-FEB-17:22 | 0.00 |
March | 0.110945E+11 | 0.282259E+10 | 744.00 | 0.110945E+11 | -0.0 | 0.00 | 0.73 | 28-MAR-17:50 | 0.20 | 06-MAR-04:01 | 6511.27 | 28-MAR-17:50 | 6511.27 | 28-MAR-17:50 | 0.00 | 30-MAR-19:00 | 1570.93 | 28-MAR-17:50 | 0.00 |
April | 0.170829E+11 | 0.409775E+10 | 719.17 | 0.170741E+11 | 8803338.19 | 0.00 | 0.95 | 16-APR-17:51 | 0.00 | 30-APR-23:20 | 8568.55 | 25-APR-18:10 | 8568.55 | 25-APR-18:10 | 126.41 | 17-APR-16:10 | 2314.24 | 07-APR-14:00 | 0.00 |
May | 0.410281E+10 | 0.112651E+10 | 702.25 | 0.407857E+10 | 24237437.48 | 0.00 | 0.45 | 31-MAY-23:40 | 0.00 | 01-MAY-00:10 | 3862.94 | 31-MAY-23:40 | 3862.94 | 31-MAY-23:40 | 142.98 | 30-MAY-09:40 | 986.06 | 19-MAY-16:00 | 0.00 |
June | 0.998846E+10 | 0.269429E+10 | 720.00 | 0.989732E+10 | 91132017.02 | 0.00 | 0.66 | 30-JUN-23:13 | 0.25 | 17-JUN-06:10 | 5908.56 | 30-JUN-23:55 | 5894.70 | 30-JUN-24:00 | 303.96 | 06-JUN-16:40 | 1782.41 | 28-JUN-19:00 | 0.00 |
July | 0.157615E+11 | 0.448151E+10 | 744.00 | 0.156580E+11 | 0.103530E+09 | 0.00 | 0.90 | 16-JUL-18:45 | 0.53 | 08-JUL-06:11 | 7646.47 | 31-JUL-23:53 | 7646.47 | 31-JUL-23:53 | 343.80 | 03-JUL-16:50 | 2911.04 | 17-JUL-16:00 | 0.00 |
August | 0.202907E+11 | 0.547415E+10 | 744.00 | 0.202104E+11 | 80298300.84 | 0.00 | 1.00 | 04-AUG-18:00 | 0.25 | 31-AUG-24:00 | 8930.79 | 05-AUG-19:44 | 8930.79 | 05-AUG-19:44 | 409.35 | 22-AUG-15:50 | 3413.05 | 06-AUG-16:00 | 0.00 |
September | 0.443767E+10 | 0.126385E+10 | 718.53 | 0.435285E+10 | 84816253.85 | 0.00 | 0.47 | 04-SEP-17:41 | 0.00 | 13-SEP-00:25 | 3703.89 | 04-SEP-17:43 | 3703.89 | 04-SEP-17:43 | 348.75 | 07-SEP-15:10 | 1442.18 | 04-SEP-17:41 | 0.00 |
October | 0.764908E+10 | 0.197266E+10 | 744.00 | 0.763790E+10 | 11180781.42 | 0.00 | 0.56 | 15-OCT-16:55 | 0.11 | 10-OCT-03:30 | 4827.15 | 18-OCT-17:00 | 4827.15 | 18-OCT-17:00 | 108.51 | 25-OCT-11:00 | 1405.10 | 18-OCT-16:00 | 0.00 |
November | 0.104327E+11 | 0.263339E+10 | 720.00 | 0.104305E+11 | 2197636.73 | 0.00 | 0.67 | 03-NOV-16:00 | 0.20 | 27-NOV-04:02 | 6109.79 | 03-NOV-16:00 | 6054.76 | 03-NOV-16:00 | 73.24 | 08-NOV-15:20 | 1430.97 | 03-NOV-16:00 | 0.00 |
December | 0.140314E+11 | 0.352697E+10 | 744.00 | 0.140311E+11 | 267080.91 | 0.00 | 0.81 | 06-DEC-16:10 | 0.40 | 31-DEC-24:00 | 7626.37 | 06-DEC-16:10 | 7598.30 | 06-DEC-16:10 | 48.76 | 19-DEC-17:05 | 1742.76 | 06-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.119735E+12 | 0.314360E+11 | 8142.14 | 0.119328E+12 | 0.406653E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.284527E+09 | 90959335.74 | 188.88 | 0.284337E+09 | -0.0 | 0.00 | 0.24 | 0.00 | 1910.82 | 1910.82 | 0.00 | 505.58 | 0.00 | ||||||
Maximum of Months | 0.202907E+11 | 0.547415E+10 | 744.00 | 0.202104E+11 | 0.103530E+09 | 0.00 | 1.00 | 0.53 | 8930.79 | 8930.79 | 409.35 | 3413.05 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.54 | 0.00 | 120.54 | 1.64 | 1059.04 | 0.00 | 0.00 | 0.00 |
February | 170.20 | 0.00 | 170.20 | 18.98 | 797.76 | 0.00 | 0.00 | 0.00 |
March | 276.48 | 0.00 | 276.48 | 80.32 | 648.53 | 0.00 | 0.00 | 0.00 |
April | 315.24 | 1.84 | 313.40 | 150.40 | 465.98 | 0.00 | 0.00 | 0.00 |
May | 413.99 | 24.53 | 389.45 | 295.45 | 336.50 | 0.00 | 0.00 | 0.00 |
June | 482.06 | 55.41 | 426.65 | 480.82 | 211.58 | 0.00 | 0.00 | 0.00 |
July | 440.39 | 41.25 | 399.14 | 516.96 | 179.25 | 0.00 | 0.00 | 0.00 |
August | 352.89 | 9.46 | 343.43 | 376.45 | 203.65 | 0.00 | 0.00 | 0.00 |
September | 264.29 | 0.09 | 264.19 | 218.22 | 313.98 | 0.00 | 0.00 | 0.00 |
October | 192.78 | 0.00 | 192.78 | 75.56 | 479.50 | 0.00 | 0.00 | 0.00 |
November | 131.06 | 0.00 | 131.06 | 14.55 | 694.24 | 0.00 | 0.00 | 0.00 |
December | 101.08 | 0.00 | 101.08 | 0.53 | 941.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 272.29 | 11.10 | 261.19 | 186.86 | 526.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.08 | 0.00 | 101.08 | 0.53 | 179.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 482.06 | 55.41 | 426.65 | 516.96 | 1059.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.54 | 0.00 | 120.54 | 1.64 | 1059.04 | 0.00 | 0.00 | 0.00 |
February | 170.20 | 0.00 | 170.20 | 18.98 | 797.76 | 0.00 | 0.00 | 0.00 |
March | 276.47 | 0.00 | 276.47 | 80.32 | 648.53 | 0.00 | 0.00 | 0.00 |
April | 315.24 | 1.84 | 313.40 | 150.40 | 465.98 | 0.00 | 0.00 | 0.00 |
May | 413.99 | 24.53 | 389.45 | 295.45 | 336.50 | 0.00 | 0.00 | 0.00 |
June | 482.06 | 55.41 | 426.65 | 480.82 | 211.58 | 0.00 | 0.00 | 0.00 |
July | 440.39 | 41.25 | 399.14 | 516.96 | 179.25 | 0.00 | 0.00 | 0.00 |
August | 352.89 | 9.46 | 343.43 | 376.45 | 203.65 | 0.00 | 0.00 | 0.00 |
September | 264.29 | 0.09 | 264.19 | 218.22 | 313.98 | 0.00 | 0.00 | 0.00 |
October | 192.78 | 0.00 | 192.78 | 75.56 | 479.50 | 0.00 | 0.00 | 0.00 |
November | 131.06 | 0.00 | 131.06 | 14.55 | 694.24 | 0.00 | 0.00 | 0.00 |
December | 101.08 | 0.00 | 101.08 | 0.53 | 941.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 272.29 | 11.10 | 261.19 | 186.86 | 526.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.08 | 0.00 | 101.08 | 0.53 | 179.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 482.06 | 55.41 | 426.65 | 516.96 | 1059.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.54 | 0.00 | 120.54 | 1.64 | 1059.04 | 0.00 | 0.00 | 0.00 |
February | 170.20 | 0.00 | 170.20 | 18.98 | 797.76 | 0.00 | 0.00 | 0.00 |
March | 276.48 | 0.00 | 276.48 | 80.32 | 648.53 | 0.00 | 0.00 | 0.00 |
April | 315.24 | 1.84 | 313.40 | 150.40 | 465.98 | 0.00 | 0.00 | 0.00 |
May | 413.99 | 24.53 | 389.45 | 295.45 | 336.50 | 0.00 | 0.00 | 0.00 |
June | 482.06 | 55.41 | 426.65 | 480.82 | 211.58 | 0.00 | 0.00 | 0.00 |
July | 440.39 | 41.25 | 399.14 | 516.96 | 179.25 | 0.00 | 0.00 | 0.00 |
August | 352.89 | 9.46 | 343.43 | 376.45 | 203.65 | 0.00 | 0.00 | 0.00 |
September | 264.29 | 0.09 | 264.19 | 218.22 | 313.98 | 0.00 | 0.00 | 0.00 |
October | 192.78 | 0.00 | 192.78 | 75.56 | 479.50 | 0.00 | 0.00 | 0.00 |
November | 131.06 | 0.00 | 131.06 | 14.55 | 694.24 | 0.00 | 0.00 | 0.00 |
December | 101.08 | 0.00 | 101.08 | 0.53 | 941.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 272.29 | 11.10 | 261.19 | 186.86 | 526.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.08 | 0.00 | 101.08 | 0.53 | 179.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 482.06 | 55.41 | 426.65 | 516.96 | 1059.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.54 | 0.00 | 120.54 | 1.64 | 1059.04 | 0.00 | 0.00 | 0.00 |
February | 170.20 | 0.00 | 170.20 | 18.98 | 797.76 | 0.00 | 0.00 | 0.00 |
March | 276.47 | 0.00 | 276.47 | 80.32 | 648.53 | 0.00 | 0.00 | 0.00 |
April | 315.24 | 1.84 | 313.40 | 150.40 | 465.98 | 0.00 | 0.00 | 0.00 |
May | 413.99 | 24.53 | 389.45 | 295.45 | 336.50 | 0.00 | 0.00 | 0.00 |
June | 482.06 | 55.41 | 426.65 | 480.82 | 211.58 | 0.00 | 0.00 | 0.00 |
July | 440.39 | 41.25 | 399.14 | 516.96 | 179.25 | 0.00 | 0.00 | 0.00 |
August | 352.89 | 9.46 | 343.43 | 376.45 | 203.65 | 0.00 | 0.00 | 0.00 |
September | 264.29 | 0.09 | 264.19 | 218.22 | 313.98 | 0.00 | 0.00 | 0.00 |
October | 192.78 | 0.00 | 192.78 | 75.56 | 479.50 | 0.00 | 0.00 | 0.00 |
November | 131.06 | 0.00 | 131.06 | 14.55 | 694.24 | 0.00 | 0.00 | 0.00 |
December | 101.08 | 0.00 | 101.08 | 0.53 | 941.54 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 272.29 | 11.10 | 261.19 | 186.86 | 526.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.08 | 0.00 | 101.08 | 0.53 | 179.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 482.06 | 55.41 | 426.65 | 516.96 | 1059.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 120.54 | 0.00 | 120.54 | 1.64 | 1058.99 | 0.00 | 0.00 | 0.00 |
February | 170.19 | 0.00 | 170.19 | 18.98 | 797.73 | 0.00 | 0.00 | 0.00 |
March | 276.46 | 0.00 | 276.46 | 80.31 | 648.51 | 0.00 | 0.00 | 0.00 |
April | 315.23 | 1.84 | 313.39 | 150.40 | 465.96 | 0.00 | 0.00 | 0.00 |
May | 413.97 | 24.53 | 389.44 | 295.44 | 336.49 | 0.00 | 0.00 | 0.00 |
June | 482.04 | 55.41 | 426.64 | 480.80 | 211.58 | 0.00 | 0.00 | 0.00 |
July | 440.37 | 41.25 | 399.13 | 516.93 | 179.25 | 0.00 | 0.00 | 0.00 |
August | 352.87 | 9.46 | 343.41 | 376.43 | 203.64 | 0.00 | 0.00 | 0.00 |
September | 264.28 | 0.09 | 264.18 | 218.21 | 313.96 | 0.00 | 0.00 | 0.00 |
October | 192.78 | 0.00 | 192.78 | 75.56 | 479.48 | 0.00 | 0.00 | 0.00 |
November | 131.05 | 0.00 | 131.05 | 14.55 | 694.21 | 0.00 | 0.00 | 0.00 |
December | 101.08 | 0.00 | 101.08 | 0.53 | 941.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 272.28 | 11.10 | 261.18 | 186.86 | 526.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 101.08 | 0.00 | 101.08 | 0.53 | 179.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 482.04 | 55.41 | 426.64 | 516.93 | 1058.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 307.54 | 141.00 | 166.55 | 154.52 | 1074.24 | 0.00 | 0.00 | 0.00 |
February | 481.03 | 238.82 | 242.21 | 345.45 | 801.77 | 0.00 | 0.00 | 0.00 |
March | 646.78 | 267.62 | 379.16 | 511.49 | 660.70 | 0.00 | 0.00 | 0.00 |
April | 825.23 | 408.98 | 416.25 | 783.36 | 476.12 | 0.00 | 0.00 | 0.00 |
May | 911.58 | 405.59 | 505.98 | 933.73 | 370.30 | 0.00 | 0.00 | 0.00 |
June | 1179.92 | 607.19 | 572.73 | 1395.03 | 236.19 | 0.00 | 0.00 | 0.00 |
July | 1238.36 | 700.08 | 538.28 | 1575.78 | 192.10 | 0.00 | 0.00 | 0.00 |
August | 1076.19 | 599.62 | 476.57 | 1339.65 | 212.56 | 0.00 | 0.00 | 0.00 |
September | 761.30 | 392.98 | 368.32 | 856.89 | 322.79 | 0.00 | 0.00 | 0.00 |
October | 546.19 | 277.35 | 268.84 | 503.70 | 486.50 | 0.00 | 0.00 | 0.00 |
November | 346.17 | 161.61 | 184.55 | 227.51 | 682.82 | 0.00 | 0.00 | 0.00 |
December | 255.32 | 109.66 | 145.66 | 118.74 | 936.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 715.86 | 359.83 | 356.03 | 731.02 | 536.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 255.32 | 109.66 | 145.66 | 118.74 | 192.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1238.36 | 700.08 | 572.73 | 1575.78 | 1074.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 307.54 | 141.00 | 166.55 | 154.52 | 1074.24 | 0.00 | 0.00 | 0.00 |
February | 481.03 | 238.82 | 242.21 | 345.45 | 801.77 | 0.00 | 0.00 | 0.00 |
March | 646.78 | 267.62 | 379.16 | 511.49 | 660.70 | 0.00 | 0.00 | 0.00 |
April | 825.23 | 408.98 | 416.25 | 783.36 | 476.12 | 0.00 | 0.00 | 0.00 |
May | 911.58 | 405.59 | 505.98 | 933.73 | 370.30 | 0.00 | 0.00 | 0.00 |
June | 1179.92 | 607.19 | 572.73 | 1395.03 | 236.19 | 0.00 | 0.00 | 0.00 |
July | 1238.36 | 700.08 | 538.28 | 1575.78 | 192.10 | 0.00 | 0.00 | 0.00 |
August | 1076.19 | 599.62 | 476.57 | 1339.65 | 212.56 | 0.00 | 0.00 | 0.00 |
September | 761.30 | 392.98 | 368.32 | 856.89 | 322.79 | 0.00 | 0.00 | 0.00 |
October | 546.19 | 277.35 | 268.84 | 503.70 | 486.50 | 0.00 | 0.00 | 0.00 |
November | 346.17 | 161.61 | 184.55 | 227.51 | 682.82 | 0.00 | 0.00 | 0.00 |
December | 255.32 | 109.66 | 145.66 | 118.74 | 936.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 715.86 | 359.83 | 356.03 | 731.02 | 536.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 255.32 | 109.66 | 145.66 | 118.74 | 192.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1238.36 | 700.08 | 572.73 | 1575.78 | 1074.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 307.54 | 140.99 | 166.54 | 154.51 | 1074.22 | 0.00 | 0.00 | 0.00 |
February | 481.02 | 238.81 | 242.20 | 345.45 | 801.75 | 0.00 | 0.00 | 0.00 |
March | 646.77 | 267.62 | 379.16 | 511.48 | 660.69 | 0.00 | 0.00 | 0.00 |
April | 825.22 | 408.97 | 416.25 | 783.34 | 476.11 | 0.00 | 0.00 | 0.00 |
May | 911.56 | 405.59 | 505.97 | 933.71 | 370.29 | 0.00 | 0.00 | 0.00 |
June | 1179.90 | 607.17 | 572.72 | 1395.01 | 236.18 | 0.00 | 0.00 | 0.00 |
July | 1238.34 | 700.06 | 538.27 | 1575.75 | 192.10 | 0.00 | 0.00 | 0.00 |
August | 1076.17 | 599.61 | 476.56 | 1339.62 | 212.56 | 0.00 | 0.00 | 0.00 |
September | 761.28 | 392.97 | 368.31 | 856.87 | 322.78 | 0.00 | 0.00 | 0.00 |
October | 546.18 | 277.34 | 268.84 | 503.70 | 486.49 | 0.00 | 0.00 | 0.00 |
November | 346.16 | 161.61 | 184.55 | 227.51 | 682.81 | 0.00 | 0.00 | 0.00 |
December | 255.31 | 109.66 | 145.66 | 118.74 | 936.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 715.84 | 359.82 | 356.02 | 731.01 | 536.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 255.31 | 109.66 | 145.66 | 118.74 | 192.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1238.34 | 700.06 | 572.72 | 1575.75 | 1074.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 849.68 | 606.86 | 242.82 | 779.40 | 888.07 | 0.00 | 0.00 | 0.00 |
February | 1082.05 | 778.25 | 303.80 | 1093.69 | 679.04 | 0.00 | 0.00 | 0.00 |
March | 967.21 | 543.14 | 424.07 | 974.70 | 608.35 | 0.00 | 0.00 | 0.00 |
April | 777.48 | 371.87 | 405.60 | 812.37 | 458.72 | 0.00 | 0.00 | 0.00 |
May | 690.77 | 229.42 | 461.34 | 737.06 | 355.60 | 0.00 | 0.00 | 0.00 |
June | 686.35 | 200.17 | 486.17 | 836.08 | 241.17 | 0.00 | 0.00 | 0.00 |
July | 739.95 | 273.34 | 466.61 | 1001.91 | 193.56 | 0.00 | 0.00 | 0.00 |
August | 879.38 | 443.37 | 436.01 | 1158.02 | 216.72 | 0.00 | 0.00 | 0.00 |
September | 975.34 | 597.62 | 377.72 | 1195.57 | 311.42 | 0.00 | 0.00 | 0.00 |
October | 1019.67 | 705.09 | 314.58 | 1144.85 | 445.26 | 0.00 | 0.00 | 0.00 |
November | 929.63 | 673.39 | 256.24 | 947.04 | 578.79 | 0.00 | 0.00 | 0.00 |
December | 807.99 | 583.45 | 224.54 | 754.45 | 774.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 865.63 | 498.65 | 366.98 | 951.83 | 478.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 686.35 | 200.17 | 224.54 | 737.06 | 193.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1082.05 | 778.25 | 486.17 | 1195.57 | 888.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 849.67 | 606.85 | 242.82 | 779.40 | 888.07 | 0.00 | 0.00 | 0.00 |
February | 1082.05 | 778.25 | 303.80 | 1093.68 | 679.04 | 0.00 | 0.00 | 0.00 |
March | 967.21 | 543.14 | 424.07 | 974.70 | 608.35 | 0.00 | 0.00 | 0.00 |
April | 777.47 | 371.87 | 405.60 | 812.37 | 458.72 | 0.00 | 0.00 | 0.00 |
May | 690.77 | 229.42 | 461.34 | 737.06 | 355.60 | 0.00 | 0.00 | 0.00 |
June | 686.35 | 200.17 | 486.17 | 836.08 | 241.17 | 0.00 | 0.00 | 0.00 |
July | 739.95 | 273.34 | 466.61 | 1001.90 | 193.56 | 0.00 | 0.00 | 0.00 |
August | 879.38 | 443.37 | 436.01 | 1158.02 | 216.72 | 0.00 | 0.00 | 0.00 |
September | 975.34 | 597.62 | 377.72 | 1195.57 | 311.42 | 0.00 | 0.00 | 0.00 |
October | 1019.67 | 705.09 | 314.58 | 1144.85 | 445.26 | 0.00 | 0.00 | 0.00 |
November | 929.63 | 673.39 | 256.24 | 947.04 | 578.79 | 0.00 | 0.00 | 0.00 |
December | 807.99 | 583.45 | 224.54 | 754.45 | 774.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 865.63 | 498.65 | 366.98 | 951.83 | 478.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 686.35 | 200.17 | 224.54 | 737.06 | 193.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1082.05 | 778.25 | 486.17 | 1195.57 | 888.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 849.68 | 606.86 | 242.82 | 779.40 | 888.07 | 0.00 | 0.00 | 0.00 |
February | 1082.05 | 778.25 | 303.80 | 1093.69 | 679.04 | 0.00 | 0.00 | 0.00 |
March | 967.21 | 543.14 | 424.07 | 974.70 | 608.35 | 0.00 | 0.00 | 0.00 |
April | 777.48 | 371.87 | 405.60 | 812.37 | 458.72 | 0.00 | 0.00 | 0.00 |
May | 690.77 | 229.42 | 461.34 | 737.06 | 355.60 | 0.00 | 0.00 | 0.00 |
June | 686.35 | 200.17 | 486.17 | 836.08 | 241.17 | 0.00 | 0.00 | 0.00 |
July | 739.95 | 273.34 | 466.61 | 1001.91 | 193.56 | 0.00 | 0.00 | 0.00 |
August | 879.38 | 443.37 | 436.01 | 1158.02 | 216.72 | 0.00 | 0.00 | 0.00 |
September | 975.34 | 597.62 | 377.72 | 1195.57 | 311.42 | 0.00 | 0.00 | 0.00 |
October | 1019.67 | 705.09 | 314.58 | 1144.85 | 445.26 | 0.00 | 0.00 | 0.00 |
November | 929.63 | 673.39 | 256.24 | 947.04 | 578.79 | 0.00 | 0.00 | 0.00 |
December | 807.99 | 583.45 | 224.54 | 754.45 | 774.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 865.63 | 498.65 | 366.98 | 951.83 | 478.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 686.35 | 200.17 | 224.54 | 737.06 | 193.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1082.05 | 778.25 | 486.17 | 1195.57 | 888.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 849.67 | 606.85 | 242.82 | 779.40 | 888.07 | 0.00 | 0.00 | 0.00 |
February | 1082.05 | 778.25 | 303.80 | 1093.68 | 679.04 | 0.00 | 0.00 | 0.00 |
March | 967.21 | 543.14 | 424.07 | 974.70 | 608.35 | 0.00 | 0.00 | 0.00 |
April | 777.47 | 371.87 | 405.60 | 812.37 | 458.72 | 0.00 | 0.00 | 0.00 |
May | 690.77 | 229.42 | 461.34 | 737.06 | 355.60 | 0.00 | 0.00 | 0.00 |
June | 686.35 | 200.17 | 486.17 | 836.08 | 241.17 | 0.00 | 0.00 | 0.00 |
July | 739.95 | 273.34 | 466.61 | 1001.90 | 193.56 | 0.00 | 0.00 | 0.00 |
August | 879.38 | 443.37 | 436.01 | 1158.02 | 216.72 | 0.00 | 0.00 | 0.00 |
September | 975.34 | 597.62 | 377.72 | 1195.57 | 311.42 | 0.00 | 0.00 | 0.00 |
October | 1019.67 | 705.09 | 314.58 | 1144.85 | 445.26 | 0.00 | 0.00 | 0.00 |
November | 929.63 | 673.39 | 256.24 | 947.04 | 578.79 | 0.00 | 0.00 | 0.00 |
December | 807.99 | 583.45 | 224.54 | 754.45 | 774.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 865.63 | 498.65 | 366.98 | 951.83 | 478.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 686.35 | 200.17 | 224.54 | 737.06 | 193.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1082.05 | 778.25 | 486.17 | 1195.57 | 888.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 849.64 | 606.83 | 242.81 | 779.37 | 888.03 | 0.00 | 0.00 | 0.00 |
February | 1082.01 | 778.22 | 303.79 | 1093.64 | 679.02 | 0.00 | 0.00 | 0.00 |
March | 967.17 | 543.12 | 424.05 | 974.66 | 608.33 | 0.00 | 0.00 | 0.00 |
April | 777.44 | 371.86 | 405.59 | 812.34 | 458.70 | 0.00 | 0.00 | 0.00 |
May | 690.74 | 229.41 | 461.33 | 737.03 | 355.59 | 0.00 | 0.00 | 0.00 |
June | 686.32 | 200.16 | 486.16 | 836.04 | 241.16 | 0.00 | 0.00 | 0.00 |
July | 739.92 | 273.32 | 466.60 | 1001.87 | 193.56 | 0.00 | 0.00 | 0.00 |
August | 879.35 | 443.35 | 436.00 | 1157.97 | 216.71 | 0.00 | 0.00 | 0.00 |
September | 975.30 | 597.60 | 377.70 | 1195.52 | 311.40 | 0.00 | 0.00 | 0.00 |
October | 1019.63 | 705.06 | 314.57 | 1144.80 | 445.24 | 0.00 | 0.00 | 0.00 |
November | 929.60 | 673.36 | 256.23 | 947.00 | 578.77 | 0.00 | 0.00 | 0.00 |
December | 807.96 | 583.43 | 224.53 | 754.42 | 774.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 865.60 | 498.63 | 366.97 | 951.79 | 478.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 686.32 | 200.16 | 224.53 | 737.03 | 193.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1082.01 | 778.22 | 486.16 | 1195.52 | 888.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 278.57 | 112.27 | 166.30 | 133.77 | 1148.47 | 0.00 | 0.00 | 0.00 |
February | 475.48 | 233.72 | 241.76 | 340.84 | 874.37 | 0.00 | 0.00 | 0.00 |
March | 608.49 | 222.96 | 385.53 | 454.09 | 752.96 | 0.00 | 0.00 | 0.00 |
April | 794.39 | 351.95 | 442.44 | 736.69 | 571.64 | 0.00 | 0.00 | 0.00 |
May | 982.61 | 448.12 | 534.49 | 1026.56 | 418.15 | 0.00 | 0.00 | 0.00 |
June | 1069.04 | 491.05 | 577.99 | 1249.99 | 288.63 | 0.00 | 0.00 | 0.00 |
July | 1095.11 | 553.38 | 541.74 | 1387.65 | 243.89 | 0.00 | 0.00 | 0.00 |
August | 929.90 | 456.37 | 473.52 | 1140.72 | 271.41 | 0.00 | 0.00 | 0.00 |
September | 748.04 | 378.18 | 369.86 | 847.13 | 369.23 | 0.00 | 0.00 | 0.00 |
October | 534.65 | 265.64 | 269.01 | 493.41 | 558.23 | 0.00 | 0.00 | 0.00 |
November | 378.48 | 187.76 | 190.72 | 273.48 | 780.66 | 0.00 | 0.00 | 0.00 |
December | 254.41 | 107.38 | 147.03 | 120.10 | 1060.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 680.02 | 317.70 | 362.32 | 685.50 | 610.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 254.41 | 107.38 | 147.03 | 120.10 | 243.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1095.11 | 553.38 | 577.99 | 1387.65 | 1148.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 278.57 | 112.27 | 166.30 | 133.77 | 1148.47 | 0.00 | 0.00 | 0.00 |
February | 475.48 | 233.72 | 241.76 | 340.84 | 874.37 | 0.00 | 0.00 | 0.00 |
March | 608.49 | 222.96 | 385.53 | 454.09 | 752.96 | 0.00 | 0.00 | 0.00 |
April | 794.39 | 351.95 | 442.44 | 736.69 | 571.64 | 0.00 | 0.00 | 0.00 |
May | 982.61 | 448.12 | 534.49 | 1026.56 | 418.15 | 0.00 | 0.00 | 0.00 |
June | 1069.04 | 491.05 | 577.99 | 1249.99 | 288.63 | 0.00 | 0.00 | 0.00 |
July | 1095.11 | 553.38 | 541.74 | 1387.65 | 243.89 | 0.00 | 0.00 | 0.00 |
August | 929.90 | 456.37 | 473.52 | 1140.72 | 271.41 | 0.00 | 0.00 | 0.00 |
September | 748.04 | 378.18 | 369.86 | 847.13 | 369.23 | 0.00 | 0.00 | 0.00 |
October | 534.65 | 265.64 | 269.01 | 493.41 | 558.23 | 0.00 | 0.00 | 0.00 |
November | 378.48 | 187.76 | 190.72 | 273.48 | 780.66 | 0.00 | 0.00 | 0.00 |
December | 254.41 | 107.38 | 147.03 | 120.10 | 1060.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 680.02 | 317.70 | 362.32 | 685.50 | 610.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 254.41 | 107.38 | 147.03 | 120.10 | 243.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1095.11 | 553.38 | 577.99 | 1387.65 | 1148.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 278.56 | 112.26 | 166.30 | 133.77 | 1148.45 | 0.00 | 0.00 | 0.00 |
February | 475.47 | 233.72 | 241.75 | 340.83 | 874.35 | 0.00 | 0.00 | 0.00 |
March | 608.48 | 222.96 | 385.53 | 454.08 | 752.95 | 0.00 | 0.00 | 0.00 |
April | 794.38 | 351.95 | 442.43 | 736.68 | 571.63 | 0.00 | 0.00 | 0.00 |
May | 982.59 | 448.11 | 534.48 | 1026.54 | 418.14 | 0.00 | 0.00 | 0.00 |
June | 1069.02 | 491.04 | 577.98 | 1249.97 | 288.62 | 0.00 | 0.00 | 0.00 |
July | 1095.09 | 553.37 | 541.73 | 1387.62 | 243.88 | 0.00 | 0.00 | 0.00 |
August | 929.88 | 456.37 | 473.51 | 1140.70 | 271.41 | 0.00 | 0.00 | 0.00 |
September | 748.03 | 378.17 | 369.86 | 847.12 | 369.22 | 0.00 | 0.00 | 0.00 |
October | 534.64 | 265.63 | 269.00 | 493.40 | 558.22 | 0.00 | 0.00 | 0.00 |
November | 378.47 | 187.75 | 190.72 | 273.47 | 780.64 | 0.00 | 0.00 | 0.00 |
December | 254.40 | 107.38 | 147.03 | 120.10 | 1060.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 680.01 | 317.70 | 362.31 | 685.49 | 610.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 254.40 | 107.38 | 147.03 | 120.10 | 243.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1095.09 | 553.37 | 577.98 | 1387.62 | 1148.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 602.69 | 0.00 | 602.69 | 18.34 | 4949.39 | 0.00 | 0.00 | 0.00 |
February | 850.97 | 0.00 | 850.97 | 146.79 | 3669.52 | 0.00 | 0.00 | 0.00 |
March | 1382.36 | 0.00 | 1382.36 | 480.90 | 2967.27 | 0.00 | 0.00 | 0.00 |
April | 1576.18 | 9.20 | 1566.98 | 827.36 | 2115.09 | 0.00 | 0.00 | 0.00 |
May | 2069.90 | 122.65 | 1947.25 | 1517.76 | 1585.33 | 0.00 | 0.00 | 0.00 |
June | 2410.29 | 277.04 | 2133.25 | 2435.28 | 1013.19 | 0.00 | 0.00 | 0.00 |
July | 2201.93 | 206.24 | 1995.69 | 2642.55 | 843.66 | 0.00 | 0.00 | 0.00 |
August | 1764.42 | 47.29 | 1717.12 | 1926.32 | 963.19 | 0.00 | 0.00 | 0.00 |
September | 1321.43 | 0.47 | 1320.95 | 1129.43 | 1465.48 | 0.00 | 0.00 | 0.00 |
October | 963.90 | 0.00 | 963.90 | 439.13 | 2167.58 | 0.00 | 0.00 | 0.00 |
November | 655.27 | 0.00 | 655.27 | 105.02 | 3090.66 | 0.00 | 0.00 | 0.00 |
December | 505.39 | 0.00 | 505.39 | 9.74 | 4237.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1361.45 | 55.52 | 1305.94 | 978.36 | 2417.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 505.39 | 0.00 | 505.39 | 9.74 | 843.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2410.29 | 277.04 | 2133.25 | 2642.55 | 4949.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 922.62 | 422.99 | 499.64 | 487.65 | 3044.53 | 0.00 | 0.00 | 0.00 |
February | 1443.07 | 716.45 | 726.62 | 1067.97 | 2261.27 | 0.00 | 0.00 | 0.00 |
March | 1940.33 | 802.86 | 1137.48 | 1562.12 | 1870.02 | 0.00 | 0.00 | 0.00 |
April | 2475.67 | 1226.93 | 1248.75 | 2361.42 | 1351.48 | 0.00 | 0.00 | 0.00 |
May | 2734.70 | 1216.77 | 1517.93 | 2800.35 | 1060.23 | 0.00 | 0.00 | 0.00 |
June | 3539.72 | 1821.54 | 1718.18 | 4169.29 | 691.40 | 0.00 | 0.00 | 0.00 |
July | 3715.04 | 2100.21 | 1614.83 | 4719.10 | 564.48 | 0.00 | 0.00 | 0.00 |
August | 3228.53 | 1798.84 | 1429.69 | 4005.71 | 637.16 | 0.00 | 0.00 | 0.00 |
September | 2283.87 | 1178.92 | 1104.94 | 2570.97 | 922.33 | 0.00 | 0.00 | 0.00 |
October | 1638.56 | 832.03 | 806.52 | 1532.76 | 1361.73 | 0.00 | 0.00 | 0.00 |
November | 1038.49 | 484.84 | 553.65 | 713.37 | 1891.68 | 0.00 | 0.00 | 0.00 |
December | 765.94 | 328.97 | 436.97 | 382.63 | 2604.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2147.55 | 1079.48 | 1068.07 | 2204.26 | 1518.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 765.94 | 328.97 | 436.97 | 382.63 | 564.48 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3715.04 | 2100.21 | 1718.18 | 4719.10 | 3044.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4248.33 | 3034.24 | 1214.09 | 3886.90 | 4348.05 | 0.00 | 0.00 | 0.00 |
February | 5410.18 | 3891.20 | 1518.98 | 5440.27 | 3311.08 | 0.00 | 0.00 | 0.00 |
March | 4835.99 | 2715.67 | 2120.32 | 4850.32 | 2959.10 | 0.00 | 0.00 | 0.00 |
April | 3887.33 | 1859.33 | 2027.99 | 4054.10 | 2207.10 | 0.00 | 0.00 | 0.00 |
May | 3453.79 | 1147.10 | 2306.69 | 3669.90 | 1733.69 | 0.00 | 0.00 | 0.00 |
June | 3431.69 | 1000.84 | 2430.85 | 4172.74 | 1174.19 | 0.00 | 0.00 | 0.00 |
July | 3699.71 | 1366.66 | 2333.05 | 5017.76 | 936.82 | 0.00 | 0.00 | 0.00 |
August | 4396.86 | 2216.82 | 2180.04 | 5781.01 | 1063.95 | 0.00 | 0.00 | 0.00 |
September | 4876.64 | 2988.08 | 1888.57 | 5938.77 | 1527.47 | 0.00 | 0.00 | 0.00 |
October | 5098.27 | 3525.39 | 1572.88 | 5689.97 | 2171.37 | 0.00 | 0.00 | 0.00 |
November | 4648.11 | 3366.91 | 1281.21 | 4724.90 | 2802.76 | 0.00 | 0.00 | 0.00 |
December | 4039.92 | 2917.23 | 1122.69 | 3782.50 | 3720.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4328.10 | 2493.22 | 1834.88 | 4745.40 | 2326.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 3431.69 | 1000.84 | 1122.69 | 3669.90 | 936.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5410.18 | 3891.20 | 2430.85 | 5938.77 | 4348.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 835.70 | 336.79 | 498.91 | 421.41 | 3216.79 | 0.00 | 0.00 | 0.00 |
February | 1426.42 | 701.16 | 725.26 | 1075.89 | 2370.69 | 0.00 | 0.00 | 0.00 |
March | 1825.47 | 668.88 | 1156.59 | 1436.27 | 1997.86 | 0.00 | 0.00 | 0.00 |
April | 2383.16 | 1055.85 | 1327.31 | 2289.06 | 1482.11 | 0.00 | 0.00 | 0.00 |
May | 2947.79 | 1344.35 | 1603.44 | 3104.89 | 1169.96 | 0.00 | 0.00 | 0.00 |
June | 3207.09 | 1473.13 | 1733.95 | 3782.31 | 799.43 | 0.00 | 0.00 | 0.00 |
July | 3285.30 | 1660.11 | 1625.19 | 4205.99 | 672.95 | 0.00 | 0.00 | 0.00 |
August | 2789.66 | 1369.11 | 1420.56 | 3475.11 | 726.27 | 0.00 | 0.00 | 0.00 |
September | 2244.11 | 1134.53 | 1109.58 | 2568.22 | 1022.04 | 0.00 | 0.00 | 0.00 |
October | 1603.92 | 796.90 | 807.02 | 1540.13 | 1475.03 | 0.00 | 0.00 | 0.00 |
November | 1135.42 | 563.27 | 572.16 | 876.54 | 2016.12 | 0.00 | 0.00 | 0.00 |
December | 763.21 | 322.13 | 441.08 | 402.40 | 2738.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2040.04 | 953.10 | 1086.94 | 2103.51 | 1638.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 763.21 | 322.13 | 441.08 | 402.40 | 672.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3285.30 | 1660.11 | 1733.95 | 4205.99 | 3216.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 602.69 | 0.00 | 602.69 | 27.87 | 4766.40 | 0.00 | 0.00 | 0.00 |
February | 850.97 | 0.00 | 850.97 | 176.71 | 3492.34 | 0.00 | 0.00 | 0.00 |
March | 1382.36 | 0.00 | 1382.36 | 528.78 | 2794.92 | 0.00 | 0.00 | 0.00 |
April | 1576.18 | 9.20 | 1566.98 | 881.36 | 1964.60 | 0.00 | 0.00 | 0.00 |
May | 2069.90 | 122.65 | 1947.25 | 1551.81 | 1495.75 | 0.00 | 0.00 | 0.00 |
June | 2410.29 | 277.04 | 2133.25 | 2441.59 | 987.98 | 0.00 | 0.00 | 0.00 |
July | 2201.93 | 206.24 | 1995.69 | 2635.26 | 833.61 | 0.00 | 0.00 | 0.00 |
August | 1764.42 | 47.29 | 1717.12 | 1927.77 | 938.41 | 0.00 | 0.00 | 0.00 |
September | 1321.43 | 0.47 | 1320.95 | 1152.33 | 1386.40 | 0.00 | 0.00 | 0.00 |
October | 963.90 | 0.00 | 963.90 | 494.13 | 1985.11 | 0.00 | 0.00 | 0.00 |
November | 655.27 | 0.00 | 655.27 | 131.25 | 2854.39 | 0.00 | 0.00 | 0.00 |
December | 505.39 | 0.00 | 505.39 | 13.26 | 4030.37 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1361.45 | 55.52 | 1305.94 | 1001.89 | 2289.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 505.39 | 0.00 | 505.39 | 13.26 | 833.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2410.29 | 277.04 | 2133.25 | 2635.26 | 4766.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 922.62 | 422.99 | 499.64 | 504.98 | 2935.42 | 0.00 | 0.00 | 0.00 |
February | 1443.07 | 716.45 | 726.62 | 1099.37 | 2157.78 | 0.00 | 0.00 | 0.00 |
March | 1940.33 | 802.86 | 1137.48 | 1596.14 | 1771.88 | 0.00 | 0.00 | 0.00 |
April | 2475.67 | 1226.93 | 1248.75 | 2389.88 | 1271.59 | 0.00 | 0.00 | 0.00 |
May | 2734.70 | 1216.77 | 1517.93 | 2811.04 | 1010.09 | 0.00 | 0.00 | 0.00 |
June | 3539.72 | 1821.54 | 1718.18 | 4163.78 | 680.21 | 0.00 | 0.00 | 0.00 |
July | 3715.04 | 2100.21 | 1614.83 | 4708.04 | 560.37 | 0.00 | 0.00 | 0.00 |
August | 3228.53 | 1798.84 | 1429.69 | 4000.13 | 626.44 | 0.00 | 0.00 | 0.00 |
September | 2283.87 | 1178.92 | 1104.94 | 2579.50 | 885.46 | 0.00 | 0.00 | 0.00 |
October | 1638.56 | 832.03 | 806.52 | 1569.23 | 1263.80 | 0.00 | 0.00 | 0.00 |
November | 1038.49 | 484.84 | 553.65 | 748.40 | 1757.00 | 0.00 | 0.00 | 0.00 |
December | 765.94 | 328.97 | 436.97 | 399.68 | 2477.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2147.55 | 1079.48 | 1068.07 | 2220.54 | 1447.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 765.94 | 328.97 | 436.97 | 399.68 | 560.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3715.04 | 2100.21 | 1718.18 | 4708.04 | 2935.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4248.33 | 3034.24 | 1214.09 | 3928.80 | 4162.52 | 0.00 | 0.00 | 0.00 |
February | 5410.18 | 3891.20 | 1518.98 | 5484.58 | 3147.30 | 0.00 | 0.00 | 0.00 |
March | 4835.99 | 2715.67 | 2120.32 | 4894.44 | 2795.79 | 0.00 | 0.00 | 0.00 |
April | 3887.33 | 1859.33 | 2027.99 | 4089.76 | 2071.24 | 0.00 | 0.00 | 0.00 |
May | 3453.79 | 1147.10 | 2306.69 | 3687.24 | 1644.65 | 0.00 | 0.00 | 0.00 |
June | 3431.69 | 1000.84 | 2430.85 | 4169.72 | 1144.45 | 0.00 | 0.00 | 0.00 |
July | 3699.71 | 1366.66 | 2333.05 | 5005.30 | 922.85 | 0.00 | 0.00 | 0.00 |
August | 4396.86 | 2216.82 | 2180.04 | 5772.82 | 1038.78 | 0.00 | 0.00 | 0.00 |
September | 4876.64 | 2988.08 | 1888.57 | 5946.43 | 1459.82 | 0.00 | 0.00 | 0.00 |
October | 5098.27 | 3525.39 | 1572.88 | 5731.99 | 2018.60 | 0.00 | 0.00 | 0.00 |
November | 4648.11 | 3366.91 | 1281.21 | 4791.02 | 2600.08 | 0.00 | 0.00 | 0.00 |
December | 4039.92 | 2917.23 | 1122.69 | 3839.80 | 3513.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4328.10 | 2493.22 | 1834.88 | 4773.01 | 2206.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 3431.69 | 1000.84 | 1122.69 | 3687.24 | 922.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5410.18 | 3891.20 | 2430.85 | 5946.43 | 4162.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 835.70 | 336.79 | 498.91 | 432.00 | 3103.90 | 0.00 | 0.00 | 0.00 |
February | 1426.42 | 701.16 | 725.26 | 1091.44 | 2274.05 | 0.00 | 0.00 | 0.00 |
March | 1825.47 | 668.88 | 1156.59 | 1455.66 | 1904.38 | 0.00 | 0.00 | 0.00 |
April | 2383.16 | 1055.85 | 1327.31 | 2310.51 | 1403.03 | 0.00 | 0.00 | 0.00 |
May | 2947.79 | 1344.35 | 1603.44 | 3113.36 | 1117.26 | 0.00 | 0.00 | 0.00 |
June | 3207.09 | 1473.13 | 1733.95 | 3778.67 | 781.61 | 0.00 | 0.00 | 0.00 |
July | 3285.30 | 1660.11 | 1625.19 | 4197.63 | 664.10 | 0.00 | 0.00 | 0.00 |
August | 2789.66 | 1369.11 | 1420.56 | 3471.80 | 710.72 | 0.00 | 0.00 | 0.00 |
September | 2244.11 | 1134.53 | 1109.58 | 2575.14 | 980.36 | 0.00 | 0.00 | 0.00 |
October | 1603.92 | 796.90 | 807.02 | 1563.85 | 1381.61 | 0.00 | 0.00 | 0.00 |
November | 1135.42 | 563.27 | 572.16 | 897.08 | 1891.58 | 0.00 | 0.00 | 0.00 |
December | 763.21 | 322.13 | 441.08 | 412.77 | 2617.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2040.04 | 953.10 | 1086.94 | 2113.59 | 1566.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 763.21 | 322.13 | 441.08 | 412.77 | 664.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3285.30 | 1660.11 | 1733.95 | 4197.63 | 3103.90 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.322855E+09 | 0.00 | 0.322855E+09 | 4391582.81 | 0.283652E+10 |
February | 0.411737E+09 | 0.00 | 0.411737E+09 | 45916795.89 | 0.192994E+10 |
March | 0.740511E+09 | 0.00 | 0.740511E+09 | 0.215120E+09 | 0.173703E+10 |
April | 0.817102E+09 | 4768427.33 | 0.812334E+09 | 0.389840E+09 | 0.120783E+10 |
May | 0.110882E+10 | 65704405.30 | 0.104311E+10 | 0.791343E+09 | 0.901288E+09 |
June | 0.124951E+10 | 0.143620E+09 | 0.110589E+10 | 0.124628E+10 | 0.548425E+09 |
July | 0.117954E+10 | 0.110478E+09 | 0.106907E+10 | 0.138461E+10 | 0.480109E+09 |
August | 0.945175E+09 | 25335095.46 | 0.919840E+09 | 0.100828E+10 | 0.545456E+09 |
September | 0.685036E+09 | 245828.01 | 0.684790E+09 | 0.565621E+09 | 0.813829E+09 |
October | 0.516350E+09 | 0.00 | 0.516350E+09 | 0.202382E+09 | 0.128429E+10 |
November | 0.339697E+09 | 0.00 | 0.339697E+09 | 37721362.82 | 0.179947E+10 |
December | 0.270733E+09 | 0.00 | 0.270733E+09 | 1413412.84 | 0.252183E+10 |
Annual Sum or Average | 0.858707E+10 | 0.350153E+09 | 0.823692E+10 | 0.589292E+10 | 0.166060E+11 |
Minimum of Months | 0.270733E+09 | 0.00 | 0.270733E+09 | 1413412.84 | 0.480109E+09 |
Maximum of Months | 0.124951E+10 | 0.143620E+09 | 0.110589E+10 | 0.138461E+10 | 0.283652E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.322855E+09 | 0.00 | 0.322855E+09 | 4391556.59 | 0.283652E+10 |
February | 0.411736E+09 | 0.00 | 0.411736E+09 | 45916666.70 | 0.192994E+10 |
March | 0.740511E+09 | 0.00 | 0.740511E+09 | 0.215119E+09 | 0.173703E+10 |
April | 0.817102E+09 | 4768421.61 | 0.812333E+09 | 0.389839E+09 | 0.120783E+10 |
May | 0.110882E+10 | 65704326.46 | 0.104311E+10 | 0.791342E+09 | 0.901288E+09 |
June | 0.124951E+10 | 0.143620E+09 | 0.110589E+10 | 0.124628E+10 | 0.548425E+09 |
July | 0.117954E+10 | 0.110478E+09 | 0.106906E+10 | 0.138461E+10 | 0.480109E+09 |
August | 0.945174E+09 | 25335065.06 | 0.919839E+09 | 0.100828E+10 | 0.545456E+09 |
September | 0.685035E+09 | 245827.72 | 0.684790E+09 | 0.565621E+09 | 0.813829E+09 |
October | 0.516350E+09 | 0.00 | 0.516350E+09 | 0.202382E+09 | 0.128429E+10 |
November | 0.339696E+09 | 0.00 | 0.339696E+09 | 37721253.83 | 0.179947E+10 |
December | 0.270732E+09 | 0.00 | 0.270732E+09 | 1413403.43 | 0.252183E+10 |
Annual Sum or Average | 0.858706E+10 | 0.350152E+09 | 0.823691E+10 | 0.589291E+10 | 0.166060E+11 |
Minimum of Months | 0.270732E+09 | 0.00 | 0.270732E+09 | 1413403.43 | 0.480109E+09 |
Maximum of Months | 0.124951E+10 | 0.143620E+09 | 0.110589E+10 | 0.138461E+10 | 0.283652E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.322855E+09 | 0.00 | 0.322855E+09 | 4391582.81 | 0.283652E+10 |
February | 0.411737E+09 | 0.00 | 0.411737E+09 | 45916795.89 | 0.192994E+10 |
March | 0.740511E+09 | 0.00 | 0.740511E+09 | 0.215120E+09 | 0.173703E+10 |
April | 0.817102E+09 | 4768427.33 | 0.812334E+09 | 0.389840E+09 | 0.120783E+10 |
May | 0.110882E+10 | 65704405.30 | 0.104311E+10 | 0.791343E+09 | 0.901288E+09 |
June | 0.124951E+10 | 0.143620E+09 | 0.110589E+10 | 0.124628E+10 | 0.548425E+09 |
July | 0.117954E+10 | 0.110478E+09 | 0.106907E+10 | 0.138461E+10 | 0.480109E+09 |
August | 0.945175E+09 | 25335095.46 | 0.919840E+09 | 0.100828E+10 | 0.545456E+09 |
September | 0.685036E+09 | 245828.01 | 0.684790E+09 | 0.565621E+09 | 0.813829E+09 |
October | 0.516350E+09 | 0.00 | 0.516350E+09 | 0.202382E+09 | 0.128429E+10 |
November | 0.339697E+09 | 0.00 | 0.339697E+09 | 37721362.82 | 0.179947E+10 |
December | 0.270733E+09 | 0.00 | 0.270733E+09 | 1413412.84 | 0.252183E+10 |
Annual Sum or Average | 0.858707E+10 | 0.350153E+09 | 0.823692E+10 | 0.589292E+10 | 0.166060E+11 |
Minimum of Months | 0.270733E+09 | 0.00 | 0.270733E+09 | 1413412.84 | 0.480109E+09 |
Maximum of Months | 0.124951E+10 | 0.143620E+09 | 0.110589E+10 | 0.138461E+10 | 0.283652E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.322855E+09 | 0.00 | 0.322855E+09 | 4391556.59 | 0.283652E+10 |
February | 0.411736E+09 | 0.00 | 0.411736E+09 | 45916666.70 | 0.192994E+10 |
March | 0.740511E+09 | 0.00 | 0.740511E+09 | 0.215119E+09 | 0.173703E+10 |
April | 0.817102E+09 | 4768421.61 | 0.812333E+09 | 0.389839E+09 | 0.120783E+10 |
May | 0.110882E+10 | 65704326.46 | 0.104311E+10 | 0.791342E+09 | 0.901288E+09 |
June | 0.124951E+10 | 0.143620E+09 | 0.110589E+10 | 0.124628E+10 | 0.548425E+09 |
July | 0.117954E+10 | 0.110478E+09 | 0.106906E+10 | 0.138461E+10 | 0.480109E+09 |
August | 0.945174E+09 | 25335065.06 | 0.919839E+09 | 0.100828E+10 | 0.545456E+09 |
September | 0.685035E+09 | 245827.72 | 0.684790E+09 | 0.565621E+09 | 0.813829E+09 |
October | 0.516350E+09 | 0.00 | 0.516350E+09 | 0.202382E+09 | 0.128429E+10 |
November | 0.339696E+09 | 0.00 | 0.339696E+09 | 37721253.83 | 0.179947E+10 |
December | 0.270732E+09 | 0.00 | 0.270732E+09 | 1413403.43 | 0.252183E+10 |
Annual Sum or Average | 0.858706E+10 | 0.350152E+09 | 0.823691E+10 | 0.589291E+10 | 0.166060E+11 |
Minimum of Months | 0.270732E+09 | 0.00 | 0.270732E+09 | 1413403.43 | 0.480109E+09 |
Maximum of Months | 0.124951E+10 | 0.143620E+09 | 0.110589E+10 | 0.138461E+10 | 0.283652E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.322842E+09 | 0.00 | 0.322842E+09 | 4391405.81 | 0.283641E+10 |
February | 0.411720E+09 | 0.00 | 0.411720E+09 | 45914945.24 | 0.192986E+10 |
March | 0.740481E+09 | 0.00 | 0.740481E+09 | 0.215111E+09 | 0.173696E+10 |
April | 0.817070E+09 | 4768235.14 | 0.812301E+09 | 0.389824E+09 | 0.120778E+10 |
May | 0.110877E+10 | 65701757.12 | 0.104307E+10 | 0.791311E+09 | 0.901251E+09 |
June | 0.124946E+10 | 0.143615E+09 | 0.110584E+10 | 0.124623E+10 | 0.548403E+09 |
July | 0.117950E+10 | 0.110474E+09 | 0.106902E+10 | 0.138456E+10 | 0.480090E+09 |
August | 0.945137E+09 | 25334074.34 | 0.919803E+09 | 0.100824E+10 | 0.545434E+09 |
September | 0.685008E+09 | 245818.10 | 0.684762E+09 | 0.565598E+09 | 0.813796E+09 |
October | 0.516329E+09 | 0.00 | 0.516329E+09 | 0.202374E+09 | 0.128424E+10 |
November | 0.339683E+09 | 0.00 | 0.339683E+09 | 37719842.48 | 0.179940E+10 |
December | 0.270722E+09 | 0.00 | 0.270722E+09 | 1413355.87 | 0.252173E+10 |
Annual Sum or Average | 0.858672E+10 | 0.350138E+09 | 0.823658E+10 | 0.589268E+10 | 0.166053E+11 |
Minimum of Months | 0.270722E+09 | 0.00 | 0.270722E+09 | 1413355.87 | 0.480090E+09 |
Maximum of Months | 0.124946E+10 | 0.143615E+09 | 0.110584E+10 | 0.138456E+10 | 0.283641E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.823727E+09 | 0.377645E+09 | 0.446082E+09 | 0.413856E+09 | 0.287725E+10 |
February | 0.116370E+10 | 0.577749E+09 | 0.585951E+09 | 0.835718E+09 | 0.193963E+10 |
March | 0.173235E+10 | 0.716797E+09 | 0.101555E+10 | 0.136999E+10 | 0.176962E+10 |
April | 0.213900E+10 | 0.106007E+10 | 0.107893E+10 | 0.203046E+10 | 0.123411E+10 |
May | 0.244157E+10 | 0.108635E+10 | 0.135522E+10 | 0.250091E+10 | 0.991807E+09 |
June | 0.305835E+10 | 0.157382E+10 | 0.148453E+10 | 0.361592E+10 | 0.612197E+09 |
July | 0.331682E+10 | 0.187509E+10 | 0.144173E+10 | 0.422056E+10 | 0.514521E+09 |
August | 0.288246E+10 | 0.160602E+10 | 0.127644E+10 | 0.358811E+10 | 0.569321E+09 |
September | 0.197328E+10 | 0.101860E+10 | 0.954682E+09 | 0.222105E+10 | 0.836664E+09 |
October | 0.146292E+10 | 0.742847E+09 | 0.720071E+09 | 0.134912E+10 | 0.130303E+10 |
November | 0.897261E+09 | 0.418903E+09 | 0.478358E+09 | 0.589709E+09 | 0.176987E+10 |
December | 0.683841E+09 | 0.293711E+09 | 0.390130E+09 | 0.318045E+09 | 0.250861E+10 |
Annual Sum or Average | 0.225753E+11 | 0.113476E+11 | 0.112277E+11 | 0.230535E+11 | 0.169266E+11 |
Minimum of Months | 0.683841E+09 | 0.293711E+09 | 0.390130E+09 | 0.318045E+09 | 0.514521E+09 |
Maximum of Months | 0.331682E+10 | 0.187509E+10 | 0.148453E+10 | 0.422056E+10 | 0.287725E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.823727E+09 | 0.377645E+09 | 0.446082E+09 | 0.413856E+09 | 0.287725E+10 |
February | 0.116370E+10 | 0.577749E+09 | 0.585951E+09 | 0.835718E+09 | 0.193963E+10 |
March | 0.173235E+10 | 0.716797E+09 | 0.101555E+10 | 0.136999E+10 | 0.176962E+10 |
April | 0.213900E+10 | 0.106007E+10 | 0.107893E+10 | 0.203046E+10 | 0.123411E+10 |
May | 0.244157E+10 | 0.108635E+10 | 0.135522E+10 | 0.250091E+10 | 0.991807E+09 |
June | 0.305835E+10 | 0.157382E+10 | 0.148453E+10 | 0.361592E+10 | 0.612197E+09 |
July | 0.331682E+10 | 0.187509E+10 | 0.144173E+10 | 0.422056E+10 | 0.514521E+09 |
August | 0.288246E+10 | 0.160602E+10 | 0.127644E+10 | 0.358811E+10 | 0.569321E+09 |
September | 0.197328E+10 | 0.101860E+10 | 0.954682E+09 | 0.222105E+10 | 0.836664E+09 |
October | 0.146292E+10 | 0.742847E+09 | 0.720071E+09 | 0.134912E+10 | 0.130303E+10 |
November | 0.897261E+09 | 0.418903E+09 | 0.478358E+09 | 0.589709E+09 | 0.176987E+10 |
December | 0.683841E+09 | 0.293711E+09 | 0.390130E+09 | 0.318045E+09 | 0.250861E+10 |
Annual Sum or Average | 0.225753E+11 | 0.113476E+11 | 0.112277E+11 | 0.230535E+11 | 0.169266E+11 |
Minimum of Months | 0.683841E+09 | 0.293711E+09 | 0.390130E+09 | 0.318045E+09 | 0.514521E+09 |
Maximum of Months | 0.331682E+10 | 0.187509E+10 | 0.148453E+10 | 0.422056E+10 | 0.287725E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.823712E+09 | 0.377639E+09 | 0.446073E+09 | 0.413849E+09 | 0.287720E+10 |
February | 0.116368E+10 | 0.577739E+09 | 0.585940E+09 | 0.835703E+09 | 0.193960E+10 |
March | 0.173232E+10 | 0.716784E+09 | 0.101553E+10 | 0.136996E+10 | 0.176959E+10 |
April | 0.213897E+10 | 0.106006E+10 | 0.107891E+10 | 0.203043E+10 | 0.123409E+10 |
May | 0.244152E+10 | 0.108633E+10 | 0.135520E+10 | 0.250086E+10 | 0.991788E+09 |
June | 0.305829E+10 | 0.157380E+10 | 0.148450E+10 | 0.361586E+10 | 0.612186E+09 |
July | 0.331676E+10 | 0.187505E+10 | 0.144171E+10 | 0.422048E+10 | 0.514511E+09 |
August | 0.288241E+10 | 0.160599E+10 | 0.127642E+10 | 0.358805E+10 | 0.569310E+09 |
September | 0.197325E+10 | 0.101858E+10 | 0.954664E+09 | 0.222101E+10 | 0.836649E+09 |
October | 0.146289E+10 | 0.742834E+09 | 0.720058E+09 | 0.134910E+10 | 0.130301E+10 |
November | 0.897244E+09 | 0.418895E+09 | 0.478349E+09 | 0.589698E+09 | 0.176984E+10 |
December | 0.683829E+09 | 0.293706E+09 | 0.390123E+09 | 0.318039E+09 | 0.250857E+10 |
Annual Sum or Average | 0.225749E+11 | 0.113474E+11 | 0.112275E+11 | 0.230530E+11 | 0.169263E+11 |
Minimum of Months | 0.683829E+09 | 0.293706E+09 | 0.390123E+09 | 0.318039E+09 | 0.514511E+09 |
Maximum of Months | 0.331676E+10 | 0.187505E+10 | 0.148450E+10 | 0.422048E+10 | 0.287720E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.227577E+10 | 0.162540E+10 | 0.650370E+09 | 0.208755E+10 | 0.237860E+10 |
February | 0.261769E+10 | 0.188274E+10 | 0.734950E+09 | 0.264584E+10 | 0.164274E+10 |
March | 0.259058E+10 | 0.145475E+10 | 0.113583E+10 | 0.261063E+10 | 0.162941E+10 |
April | 0.201522E+10 | 0.963891E+09 | 0.105133E+10 | 0.210567E+10 | 0.118900E+10 |
May | 0.185015E+10 | 0.614486E+09 | 0.123566E+10 | 0.197414E+10 | 0.952450E+09 |
June | 0.177901E+10 | 0.518844E+09 | 0.126017E+10 | 0.216711E+10 | 0.625119E+09 |
July | 0.198188E+10 | 0.732101E+09 | 0.124978E+10 | 0.268350E+10 | 0.518439E+09 |
August | 0.235534E+10 | 0.118752E+10 | 0.116782E+10 | 0.310163E+10 | 0.580460E+09 |
September | 0.252808E+10 | 0.154904E+10 | 0.979045E+09 | 0.309891E+10 | 0.807190E+09 |
October | 0.273107E+10 | 0.188850E+10 | 0.842571E+09 | 0.306637E+10 | 0.119257E+10 |
November | 0.240961E+10 | 0.174543E+10 | 0.664186E+09 | 0.245473E+10 | 0.150022E+10 |
December | 0.216413E+10 | 0.156272E+10 | 0.601409E+09 | 0.202072E+10 | 0.207407E+10 |
Annual Sum or Average | 0.272985E+11 | 0.157254E+11 | 0.115731E+11 | 0.300168E+11 | 0.150903E+11 |
Minimum of Months | 0.177901E+10 | 0.518844E+09 | 0.601409E+09 | 0.197414E+10 | 0.518439E+09 |
Maximum of Months | 0.273107E+10 | 0.188850E+10 | 0.126017E+10 | 0.310163E+10 | 0.237860E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.227577E+10 | 0.162540E+10 | 0.650369E+09 | 0.208755E+10 | 0.237860E+10 |
February | 0.261769E+10 | 0.188274E+10 | 0.734950E+09 | 0.264584E+10 | 0.164274E+10 |
March | 0.259057E+10 | 0.145475E+10 | 0.113583E+10 | 0.261063E+10 | 0.162941E+10 |
April | 0.201521E+10 | 0.963890E+09 | 0.105132E+10 | 0.210566E+10 | 0.118900E+10 |
May | 0.185015E+10 | 0.614485E+09 | 0.123566E+10 | 0.197414E+10 | 0.952450E+09 |
June | 0.177901E+10 | 0.518843E+09 | 0.126016E+10 | 0.216711E+10 | 0.625119E+09 |
July | 0.198188E+10 | 0.732101E+09 | 0.124978E+10 | 0.268350E+10 | 0.518439E+09 |
August | 0.235534E+10 | 0.118752E+10 | 0.116782E+10 | 0.310163E+10 | 0.580460E+09 |
September | 0.252808E+10 | 0.154904E+10 | 0.979044E+09 | 0.309891E+10 | 0.807189E+09 |
October | 0.273107E+10 | 0.188850E+10 | 0.842571E+09 | 0.306636E+10 | 0.119257E+10 |
November | 0.240961E+10 | 0.174542E+10 | 0.664185E+09 | 0.245473E+10 | 0.150022E+10 |
December | 0.216413E+10 | 0.156272E+10 | 0.601409E+09 | 0.202071E+10 | 0.207407E+10 |
Annual Sum or Average | 0.272985E+11 | 0.157254E+11 | 0.115731E+11 | 0.300168E+11 | 0.150903E+11 |
Minimum of Months | 0.177901E+10 | 0.518843E+09 | 0.601409E+09 | 0.197414E+10 | 0.518439E+09 |
Maximum of Months | 0.273107E+10 | 0.188850E+10 | 0.126016E+10 | 0.310163E+10 | 0.237860E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.227577E+10 | 0.162540E+10 | 0.650370E+09 | 0.208755E+10 | 0.237860E+10 |
February | 0.261769E+10 | 0.188274E+10 | 0.734950E+09 | 0.264584E+10 | 0.164274E+10 |
March | 0.259058E+10 | 0.145475E+10 | 0.113583E+10 | 0.261063E+10 | 0.162941E+10 |
April | 0.201522E+10 | 0.963891E+09 | 0.105133E+10 | 0.210567E+10 | 0.118900E+10 |
May | 0.185015E+10 | 0.614486E+09 | 0.123566E+10 | 0.197414E+10 | 0.952450E+09 |
June | 0.177901E+10 | 0.518844E+09 | 0.126017E+10 | 0.216711E+10 | 0.625119E+09 |
July | 0.198188E+10 | 0.732101E+09 | 0.124978E+10 | 0.268350E+10 | 0.518439E+09 |
August | 0.235534E+10 | 0.118752E+10 | 0.116782E+10 | 0.310163E+10 | 0.580460E+09 |
September | 0.252808E+10 | 0.154904E+10 | 0.979045E+09 | 0.309891E+10 | 0.807190E+09 |
October | 0.273107E+10 | 0.188850E+10 | 0.842571E+09 | 0.306637E+10 | 0.119257E+10 |
November | 0.240961E+10 | 0.174543E+10 | 0.664186E+09 | 0.245473E+10 | 0.150022E+10 |
December | 0.216413E+10 | 0.156272E+10 | 0.601409E+09 | 0.202072E+10 | 0.207407E+10 |
Annual Sum or Average | 0.272985E+11 | 0.157254E+11 | 0.115731E+11 | 0.300168E+11 | 0.150903E+11 |
Minimum of Months | 0.177901E+10 | 0.518844E+09 | 0.601409E+09 | 0.197414E+10 | 0.518439E+09 |
Maximum of Months | 0.273107E+10 | 0.188850E+10 | 0.126017E+10 | 0.310163E+10 | 0.237860E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.227577E+10 | 0.162540E+10 | 0.650369E+09 | 0.208755E+10 | 0.237860E+10 |
February | 0.261769E+10 | 0.188274E+10 | 0.734950E+09 | 0.264584E+10 | 0.164274E+10 |
March | 0.259057E+10 | 0.145475E+10 | 0.113583E+10 | 0.261063E+10 | 0.162941E+10 |
April | 0.201521E+10 | 0.963890E+09 | 0.105132E+10 | 0.210566E+10 | 0.118900E+10 |
May | 0.185015E+10 | 0.614485E+09 | 0.123566E+10 | 0.197414E+10 | 0.952450E+09 |
June | 0.177901E+10 | 0.518843E+09 | 0.126016E+10 | 0.216711E+10 | 0.625119E+09 |
July | 0.198188E+10 | 0.732101E+09 | 0.124978E+10 | 0.268350E+10 | 0.518439E+09 |
August | 0.235534E+10 | 0.118752E+10 | 0.116782E+10 | 0.310163E+10 | 0.580460E+09 |
September | 0.252808E+10 | 0.154904E+10 | 0.979044E+09 | 0.309891E+10 | 0.807189E+09 |
October | 0.273107E+10 | 0.188850E+10 | 0.842571E+09 | 0.306636E+10 | 0.119257E+10 |
November | 0.240961E+10 | 0.174542E+10 | 0.664185E+09 | 0.245473E+10 | 0.150022E+10 |
December | 0.216413E+10 | 0.156272E+10 | 0.601409E+09 | 0.202071E+10 | 0.207407E+10 |
Annual Sum or Average | 0.272985E+11 | 0.157254E+11 | 0.115731E+11 | 0.300168E+11 | 0.150903E+11 |
Minimum of Months | 0.177901E+10 | 0.518843E+09 | 0.601409E+09 | 0.197414E+10 | 0.518439E+09 |
Maximum of Months | 0.273107E+10 | 0.188850E+10 | 0.126016E+10 | 0.310163E+10 | 0.237860E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.227568E+10 | 0.162534E+10 | 0.650343E+09 | 0.208746E+10 | 0.237850E+10 |
February | 0.261759E+10 | 0.188267E+10 | 0.734921E+09 | 0.264574E+10 | 0.164268E+10 |
March | 0.259047E+10 | 0.145469E+10 | 0.113578E+10 | 0.261053E+10 | 0.162934E+10 |
April | 0.201513E+10 | 0.963852E+09 | 0.105128E+10 | 0.210558E+10 | 0.118895E+10 |
May | 0.185008E+10 | 0.614461E+09 | 0.123561E+10 | 0.197406E+10 | 0.952411E+09 |
June | 0.177894E+10 | 0.518823E+09 | 0.126011E+10 | 0.216702E+10 | 0.625094E+09 |
July | 0.198180E+10 | 0.732072E+09 | 0.124973E+10 | 0.268340E+10 | 0.518418E+09 |
August | 0.235524E+10 | 0.118747E+10 | 0.116777E+10 | 0.310151E+10 | 0.580436E+09 |
September | 0.252798E+10 | 0.154898E+10 | 0.979005E+09 | 0.309879E+10 | 0.807157E+09 |
October | 0.273096E+10 | 0.188843E+10 | 0.842537E+09 | 0.306625E+10 | 0.119253E+10 |
November | 0.240951E+10 | 0.174535E+10 | 0.664159E+09 | 0.245463E+10 | 0.150016E+10 |
December | 0.216404E+10 | 0.156266E+10 | 0.601385E+09 | 0.202063E+10 | 0.207398E+10 |
Annual Sum or Average | 0.272974E+11 | 0.157248E+11 | 0.115726E+11 | 0.300156E+11 | 0.150897E+11 |
Minimum of Months | 0.177894E+10 | 0.518823E+09 | 0.601385E+09 | 0.197406E+10 | 0.518418E+09 |
Maximum of Months | 0.273096E+10 | 0.188843E+10 | 0.126011E+10 | 0.310151E+10 | 0.237850E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.746122E+09 | 0.300693E+09 | 0.445429E+09 | 0.358292E+09 | 0.307606E+10 |
February | 0.115027E+10 | 0.565418E+09 | 0.584856E+09 | 0.824561E+09 | 0.211527E+10 |
March | 0.162979E+10 | 0.597181E+09 | 0.103261E+10 | 0.121623E+10 | 0.201673E+10 |
April | 0.205907E+10 | 0.912262E+09 | 0.114681E+10 | 0.190951E+10 | 0.148169E+10 |
May | 0.263182E+10 | 0.120025E+10 | 0.143157E+10 | 0.274954E+10 | 0.111997E+10 |
June | 0.277095E+10 | 0.127280E+10 | 0.149815E+10 | 0.323997E+10 | 0.748124E+09 |
July | 0.293315E+10 | 0.148216E+10 | 0.145098E+10 | 0.371668E+10 | 0.653225E+09 |
August | 0.249064E+10 | 0.122235E+10 | 0.126829E+10 | 0.305531E+10 | 0.726952E+09 |
September | 0.193893E+10 | 0.980245E+09 | 0.958686E+09 | 0.219577E+10 | 0.957048E+09 |
October | 0.143200E+10 | 0.711482E+09 | 0.720515E+09 | 0.132155E+10 | 0.149516E+10 |
November | 0.981017E+09 | 0.486668E+09 | 0.494349E+09 | 0.708858E+09 | 0.202346E+10 |
December | 0.681403E+09 | 0.287601E+09 | 0.393802E+09 | 0.321674E+09 | 0.284078E+10 |
Annual Sum or Average | 0.214452E+11 | 0.100191E+11 | 0.114260E+11 | 0.216180E+11 | 0.192545E+11 |
Minimum of Months | 0.681403E+09 | 0.287601E+09 | 0.393802E+09 | 0.321674E+09 | 0.653225E+09 |
Maximum of Months | 0.293315E+10 | 0.148216E+10 | 0.149815E+10 | 0.371668E+10 | 0.307606E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.746122E+09 | 0.300693E+09 | 0.445429E+09 | 0.358292E+09 | 0.307606E+10 |
February | 0.115027E+10 | 0.565418E+09 | 0.584856E+09 | 0.824561E+09 | 0.211527E+10 |
March | 0.162979E+10 | 0.597181E+09 | 0.103261E+10 | 0.121623E+10 | 0.201673E+10 |
April | 0.205907E+10 | 0.912262E+09 | 0.114681E+10 | 0.190951E+10 | 0.148169E+10 |
May | 0.263182E+10 | 0.120025E+10 | 0.143157E+10 | 0.274954E+10 | 0.111997E+10 |
June | 0.277095E+10 | 0.127280E+10 | 0.149815E+10 | 0.323997E+10 | 0.748124E+09 |
July | 0.293315E+10 | 0.148216E+10 | 0.145098E+10 | 0.371668E+10 | 0.653225E+09 |
August | 0.249064E+10 | 0.122235E+10 | 0.126829E+10 | 0.305531E+10 | 0.726952E+09 |
September | 0.193893E+10 | 0.980245E+09 | 0.958686E+09 | 0.219577E+10 | 0.957048E+09 |
October | 0.143200E+10 | 0.711482E+09 | 0.720515E+09 | 0.132155E+10 | 0.149516E+10 |
November | 0.981017E+09 | 0.486668E+09 | 0.494349E+09 | 0.708858E+09 | 0.202346E+10 |
December | 0.681403E+09 | 0.287601E+09 | 0.393802E+09 | 0.321674E+09 | 0.284078E+10 |
Annual Sum or Average | 0.214452E+11 | 0.100191E+11 | 0.114260E+11 | 0.216180E+11 | 0.192545E+11 |
Minimum of Months | 0.681403E+09 | 0.287601E+09 | 0.393802E+09 | 0.321674E+09 | 0.653225E+09 |
Maximum of Months | 0.293315E+10 | 0.148216E+10 | 0.149815E+10 | 0.371668E+10 | 0.307606E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.746108E+09 | 0.300687E+09 | 0.445421E+09 | 0.358286E+09 | 0.307601E+10 |
February | 0.115025E+10 | 0.565408E+09 | 0.584845E+09 | 0.824546E+09 | 0.211523E+10 |
March | 0.162976E+10 | 0.597170E+09 | 0.103259E+10 | 0.121621E+10 | 0.201669E+10 |
April | 0.205903E+10 | 0.912245E+09 | 0.114678E+10 | 0.190948E+10 | 0.148166E+10 |
May | 0.263177E+10 | 0.120023E+10 | 0.143154E+10 | 0.274949E+10 | 0.111995E+10 |
June | 0.277090E+10 | 0.127278E+10 | 0.149812E+10 | 0.323991E+10 | 0.748111E+09 |
July | 0.293309E+10 | 0.148214E+10 | 0.145096E+10 | 0.371661E+10 | 0.653213E+09 |
August | 0.249059E+10 | 0.122233E+10 | 0.126826E+10 | 0.305525E+10 | 0.726938E+09 |
September | 0.193890E+10 | 0.980227E+09 | 0.958669E+09 | 0.219573E+10 | 0.957030E+09 |
October | 0.143197E+10 | 0.711469E+09 | 0.720502E+09 | 0.132153E+10 | 0.149513E+10 |
November | 0.980999E+09 | 0.486659E+09 | 0.494340E+09 | 0.708845E+09 | 0.202343E+10 |
December | 0.681391E+09 | 0.287596E+09 | 0.393795E+09 | 0.321668E+09 | 0.284073E+10 |
Annual Sum or Average | 0.214448E+11 | 0.100189E+11 | 0.114258E+11 | 0.216176E+11 | 0.192541E+11 |
Minimum of Months | 0.681391E+09 | 0.287596E+09 | 0.393795E+09 | 0.321668E+09 | 0.653213E+09 |
Maximum of Months | 0.293309E+10 | 0.148214E+10 | 0.149812E+10 | 0.371661E+10 | 0.307601E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161426E+10 | 0.00 | 0.161426E+10 | 49115720.69 | 0.132565E+11 |
February | 0.205866E+10 | 0.00 | 0.205866E+10 | 0.355108E+09 | 0.887730E+10 |
March | 0.370251E+10 | 0.00 | 0.370251E+10 | 0.128804E+10 | 0.794753E+10 |
April | 0.408546E+10 | 23841848.37 | 0.406162E+10 | 0.214453E+10 | 0.548231E+10 |
May | 0.554403E+10 | 0.328518E+09 | 0.521551E+10 | 0.406516E+10 | 0.424614E+10 |
June | 0.624747E+10 | 0.718093E+09 | 0.552937E+10 | 0.631226E+10 | 0.262620E+10 |
July | 0.589765E+10 | 0.552386E+09 | 0.534526E+10 | 0.707780E+10 | 0.225965E+10 |
August | 0.472582E+10 | 0.126674E+09 | 0.459914E+10 | 0.515944E+10 | 0.257981E+10 |
September | 0.342514E+10 | 1229125.19 | 0.342391E+10 | 0.292748E+10 | 0.379852E+10 |
October | 0.258172E+10 | 0.00 | 0.258172E+10 | 0.117618E+10 | 0.580564E+10 |
November | 0.169846E+10 | 0.00 | 0.169846E+10 | 0.272222E+09 | 0.801099E+10 |
December | 0.135365E+10 | 0.00 | 0.135365E+10 | 26074433.61 | 0.113508E+11 |
Annual Sum or Average | 0.429348E+11 | 0.175074E+10 | 0.411841E+11 | 0.308534E+11 | 0.762413E+11 |
Minimum of Months | 0.135365E+10 | 0.00 | 0.135365E+10 | 26074433.61 | 0.225965E+10 |
Maximum of Months | 0.624747E+10 | 0.718093E+09 | 0.552937E+10 | 0.707780E+10 | 0.132565E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247116E+10 | 0.113292E+10 | 0.133823E+10 | 0.130611E+10 | 0.815448E+10 |
February | 0.349106E+10 | 0.173323E+10 | 0.175783E+10 | 0.258364E+10 | 0.547047E+10 |
March | 0.519699E+10 | 0.215037E+10 | 0.304662E+10 | 0.418398E+10 | 0.500866E+10 |
April | 0.641695E+10 | 0.318019E+10 | 0.323676E+10 | 0.612081E+10 | 0.350303E+10 |
May | 0.732463E+10 | 0.325900E+10 | 0.406563E+10 | 0.750047E+10 | 0.283973E+10 |
June | 0.917496E+10 | 0.472143E+10 | 0.445353E+10 | 0.108068E+11 | 0.179212E+10 |
July | 0.995035E+10 | 0.562520E+10 | 0.432515E+10 | 0.126396E+11 | 0.151191E+10 |
August | 0.864730E+10 | 0.481801E+10 | 0.382929E+10 | 0.107289E+11 | 0.170657E+10 |
September | 0.591979E+10 | 0.305577E+10 | 0.286402E+10 | 0.666397E+10 | 0.239069E+10 |
October | 0.438871E+10 | 0.222852E+10 | 0.216019E+10 | 0.410535E+10 | 0.364727E+10 |
November | 0.269175E+10 | 0.125670E+10 | 0.143506E+10 | 0.184906E+10 | 0.490323E+10 |
December | 0.205150E+10 | 0.881125E+09 | 0.117038E+10 | 0.102485E+10 | 0.697467E+10 |
Annual Sum or Average | 0.677252E+11 | 0.340425E+11 | 0.336827E+11 | 0.695136E+11 | 0.479028E+11 |
Minimum of Months | 0.205150E+10 | 0.881125E+09 | 0.117038E+10 | 0.102485E+10 | 0.151191E+10 |
Maximum of Months | 0.995035E+10 | 0.562520E+10 | 0.445353E+10 | 0.126396E+11 | 0.815448E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.113787E+11 | 0.812691E+10 | 0.325181E+10 | 0.104107E+11 | 0.116458E+11 |
February | 0.130883E+11 | 0.941360E+10 | 0.367471E+10 | 0.131611E+11 | 0.801016E+10 |
March | 0.129527E+11 | 0.727366E+10 | 0.567907E+10 | 0.129911E+11 | 0.792566E+10 |
April | 0.100760E+11 | 0.481940E+10 | 0.525656E+10 | 0.105082E+11 | 0.572081E+10 |
May | 0.925064E+10 | 0.307239E+10 | 0.617825E+10 | 0.982945E+10 | 0.464353E+10 |
June | 0.889494E+10 | 0.259419E+10 | 0.630075E+10 | 0.108157E+11 | 0.304351E+10 |
July | 0.990930E+10 | 0.366046E+10 | 0.624883E+10 | 0.134396E+11 | 0.250917E+10 |
August | 0.117765E+11 | 0.593752E+10 | 0.583902E+10 | 0.154839E+11 | 0.284969E+10 |
September | 0.126403E+11 | 0.774510E+10 | 0.489516E+10 | 0.153933E+11 | 0.395919E+10 |
October | 0.136552E+11 | 0.944240E+10 | 0.421281E+10 | 0.152400E+11 | 0.581578E+10 |
November | 0.120479E+11 | 0.872702E+10 | 0.332089E+10 | 0.122469E+11 | 0.726474E+10 |
December | 0.108205E+11 | 0.781351E+10 | 0.300701E+10 | 0.101311E+11 | 0.996469E+10 |
Annual Sum or Average | 0.136491E+12 | 0.786262E+11 | 0.578649E+11 | 0.149651E+12 | 0.733528E+11 |
Minimum of Months | 0.889494E+10 | 0.259419E+10 | 0.300701E+10 | 0.982945E+10 | 0.250917E+10 |
Maximum of Months | 0.136552E+11 | 0.944240E+10 | 0.630075E+10 | 0.154839E+11 | 0.116458E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223834E+10 | 0.902069E+09 | 0.133627E+10 | 0.112870E+10 | 0.861586E+10 |
February | 0.345079E+10 | 0.169624E+10 | 0.175455E+10 | 0.260279E+10 | 0.573517E+10 |
March | 0.488933E+10 | 0.179152E+10 | 0.309780E+10 | 0.384690E+10 | 0.535106E+10 |
April | 0.617714E+10 | 0.273676E+10 | 0.344038E+10 | 0.593324E+10 | 0.384163E+10 |
May | 0.789537E+10 | 0.360071E+10 | 0.429466E+10 | 0.831614E+10 | 0.313363E+10 |
June | 0.831276E+10 | 0.381836E+10 | 0.449440E+10 | 0.980374E+10 | 0.207213E+10 |
July | 0.879935E+10 | 0.444644E+10 | 0.435291E+10 | 0.112653E+11 | 0.180243E+10 |
August | 0.747184E+10 | 0.366702E+10 | 0.380482E+10 | 0.930774E+10 | 0.194524E+10 |
September | 0.581673E+10 | 0.294070E+10 | 0.287603E+10 | 0.665682E+10 | 0.264913E+10 |
October | 0.429595E+10 | 0.213442E+10 | 0.216152E+10 | 0.412509E+10 | 0.395072E+10 |
November | 0.294302E+10 | 0.145999E+10 | 0.148303E+10 | 0.227200E+10 | 0.522579E+10 |
December | 0.204419E+10 | 0.862794E+09 | 0.118139E+10 | 0.107778E+10 | 0.733542E+10 |
Annual Sum or Average | 0.643348E+11 | 0.300570E+11 | 0.342778E+11 | 0.663363E+11 | 0.516582E+11 |
Minimum of Months | 0.204419E+10 | 0.862794E+09 | 0.118139E+10 | 0.107778E+10 | 0.180243E+10 |
Maximum of Months | 0.879935E+10 | 0.444644E+10 | 0.449440E+10 | 0.112653E+11 | 0.861586E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.161426E+10 | 0.00 | 0.161426E+10 | 74659710.91 | 0.127663E+11 |
February | 0.205866E+10 | 0.00 | 0.205866E+10 | 0.427485E+09 | 0.844866E+10 |
March | 0.370251E+10 | 0.00 | 0.370251E+10 | 0.141629E+10 | 0.748592E+10 |
April | 0.408546E+10 | 23841848.37 | 0.406162E+10 | 0.228449E+10 | 0.509224E+10 |
May | 0.554403E+10 | 0.328518E+09 | 0.521551E+10 | 0.415637E+10 | 0.400621E+10 |
June | 0.624747E+10 | 0.718093E+09 | 0.552937E+10 | 0.632859E+10 | 0.256085E+10 |
July | 0.589765E+10 | 0.552386E+09 | 0.534526E+10 | 0.705827E+10 | 0.223273E+10 |
August | 0.472582E+10 | 0.126674E+09 | 0.459914E+10 | 0.516335E+10 | 0.251344E+10 |
September | 0.342514E+10 | 1229125.19 | 0.342391E+10 | 0.298683E+10 | 0.359354E+10 |
October | 0.258172E+10 | 0.00 | 0.258172E+10 | 0.132348E+10 | 0.531691E+10 |
November | 0.169846E+10 | 0.00 | 0.169846E+10 | 0.340190E+09 | 0.739857E+10 |
December | 0.135365E+10 | 0.00 | 0.135365E+10 | 35507480.39 | 0.107949E+11 |
Annual Sum or Average | 0.429348E+11 | 0.175074E+10 | 0.411841E+11 | 0.315955E+11 | 0.722103E+11 |
Minimum of Months | 0.135365E+10 | 0.00 | 0.135365E+10 | 35507480.39 | 0.223273E+10 |
Maximum of Months | 0.624747E+10 | 0.718093E+09 | 0.552937E+10 | 0.705827E+10 | 0.127663E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.247116E+10 | 0.113292E+10 | 0.133823E+10 | 0.135253E+10 | 0.786224E+10 |
February | 0.349106E+10 | 0.173323E+10 | 0.175783E+10 | 0.265961E+10 | 0.522010E+10 |
March | 0.519699E+10 | 0.215037E+10 | 0.304662E+10 | 0.427510E+10 | 0.474580E+10 |
April | 0.641695E+10 | 0.318019E+10 | 0.323676E+10 | 0.619458E+10 | 0.329595E+10 |
May | 0.732463E+10 | 0.325900E+10 | 0.406563E+10 | 0.752908E+10 | 0.270543E+10 |
June | 0.917496E+10 | 0.472143E+10 | 0.445353E+10 | 0.107925E+11 | 0.176311E+10 |
July | 0.995035E+10 | 0.562520E+10 | 0.432515E+10 | 0.126100E+11 | 0.150090E+10 |
August | 0.864730E+10 | 0.481801E+10 | 0.382929E+10 | 0.107140E+11 | 0.167787E+10 |
September | 0.591979E+10 | 0.305577E+10 | 0.286402E+10 | 0.668607E+10 | 0.229512E+10 |
October | 0.438871E+10 | 0.222852E+10 | 0.216019E+10 | 0.420302E+10 | 0.338496E+10 |
November | 0.269175E+10 | 0.125670E+10 | 0.143506E+10 | 0.193985E+10 | 0.455414E+10 |
December | 0.205150E+10 | 0.881125E+09 | 0.117038E+10 | 0.107050E+10 | 0.663592E+10 |
Annual Sum or Average | 0.677252E+11 | 0.340425E+11 | 0.336827E+11 | 0.700268E+11 | 0.456415E+11 |
Minimum of Months | 0.205150E+10 | 0.881125E+09 | 0.117038E+10 | 0.107050E+10 | 0.150090E+10 |
Maximum of Months | 0.995035E+10 | 0.562520E+10 | 0.445353E+10 | 0.126100E+11 | 0.786224E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.113787E+11 | 0.812691E+10 | 0.325181E+10 | 0.105229E+11 | 0.111489E+11 |
February | 0.130883E+11 | 0.941360E+10 | 0.367471E+10 | 0.132683E+11 | 0.761395E+10 |
March | 0.129527E+11 | 0.727366E+10 | 0.567907E+10 | 0.131093E+11 | 0.748825E+10 |
April | 0.100760E+11 | 0.481940E+10 | 0.525656E+10 | 0.106007E+11 | 0.536865E+10 |
May | 0.925064E+10 | 0.307239E+10 | 0.617825E+10 | 0.987589E+10 | 0.440503E+10 |
June | 0.889494E+10 | 0.259419E+10 | 0.630075E+10 | 0.108079E+11 | 0.296642E+10 |
July | 0.990930E+10 | 0.366046E+10 | 0.624883E+10 | 0.134062E+11 | 0.247177E+10 |
August | 0.117765E+11 | 0.593752E+10 | 0.583902E+10 | 0.154619E+11 | 0.278226E+10 |
September | 0.126403E+11 | 0.774510E+10 | 0.489516E+10 | 0.154131E+11 | 0.378385E+10 |
October | 0.136552E+11 | 0.944240E+10 | 0.421281E+10 | 0.153526E+11 | 0.540661E+10 |
November | 0.120479E+11 | 0.872702E+10 | 0.332089E+10 | 0.124183E+11 | 0.673942E+10 |
December | 0.108205E+11 | 0.781351E+10 | 0.300701E+10 | 0.102845E+11 | 0.941005E+10 |
Annual Sum or Average | 0.136491E+12 | 0.786262E+11 | 0.578649E+11 | 0.150522E+12 | 0.695851E+11 |
Minimum of Months | 0.889494E+10 | 0.259419E+10 | 0.300701E+10 | 0.987589E+10 | 0.247177E+10 |
Maximum of Months | 0.136552E+11 | 0.944240E+10 | 0.630075E+10 | 0.154619E+11 | 0.111489E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.223834E+10 | 0.902069E+09 | 0.133627E+10 | 0.115706E+10 | 0.831348E+10 |
February | 0.345079E+10 | 0.169624E+10 | 0.175455E+10 | 0.264041E+10 | 0.550138E+10 |
March | 0.488933E+10 | 0.179152E+10 | 0.309780E+10 | 0.389885E+10 | 0.510069E+10 |
April | 0.617714E+10 | 0.273676E+10 | 0.344038E+10 | 0.598884E+10 | 0.363665E+10 |
May | 0.789537E+10 | 0.360071E+10 | 0.429466E+10 | 0.833883E+10 | 0.299247E+10 |
June | 0.831276E+10 | 0.381836E+10 | 0.449440E+10 | 0.979432E+10 | 0.202594E+10 |
July | 0.879935E+10 | 0.444644E+10 | 0.435291E+10 | 0.112429E+11 | 0.177872E+10 |
August | 0.747184E+10 | 0.366702E+10 | 0.380482E+10 | 0.929887E+10 | 0.190360E+10 |
September | 0.581673E+10 | 0.294070E+10 | 0.287603E+10 | 0.667477E+10 | 0.254108E+10 |
October | 0.429595E+10 | 0.213442E+10 | 0.216152E+10 | 0.418863E+10 | 0.370050E+10 |
November | 0.294302E+10 | 0.145999E+10 | 0.148303E+10 | 0.232524E+10 | 0.490297E+10 |
December | 0.204419E+10 | 0.862794E+09 | 0.118139E+10 | 0.110557E+10 | 0.701010E+10 |
Annual Sum or Average | 0.643348E+11 | 0.300570E+11 | 0.342778E+11 | 0.666543E+11 | 0.494076E+11 |
Minimum of Months | 0.204419E+10 | 0.862794E+09 | 0.118139E+10 | 0.110557E+10 | 0.177872E+10 |
Maximum of Months | 0.879935E+10 | 0.444644E+10 | 0.449440E+10 | 0.112429E+11 | 0.831348E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 8.20 | 5295.14 | 602.70 | 0.00 | 602.70 | 0.00 | 0.00 |
February | 94.90 | 3988.77 | 850.97 | 0.00 | 850.97 | 0.00 | 0.00 |
March | 401.58 | 3242.63 | 1382.36 | 0.00 | 1382.36 | 0.00 | 0.00 |
April | 752.00 | 2329.90 | 1576.19 | 9.20 | 1566.99 | 0.00 | 0.00 |
May | 1477.26 | 1682.50 | 2069.91 | 122.66 | 1947.26 | 0.00 | 0.00 |
June | 2404.07 | 1057.91 | 2410.30 | 277.04 | 2133.25 | 0.00 | 0.00 |
July | 2584.76 | 896.25 | 2201.94 | 206.24 | 1995.70 | 0.00 | 0.00 |
August | 1882.22 | 1018.24 | 1764.42 | 47.29 | 1717.13 | 0.00 | 0.00 |
September | 1091.08 | 1569.87 | 1321.43 | 0.47 | 1320.96 | 0.00 | 0.00 |
October | 377.80 | 2397.47 | 963.91 | 0.00 | 963.91 | 0.00 | 0.00 |
November | 72.76 | 3471.17 | 655.27 | 0.00 | 655.27 | 0.00 | 0.00 |
December | 2.64 | 4707.68 | 505.40 | 0.00 | 505.40 | 0.00 | 0.00 |
Annual Sum or Average | 934.31 | 2632.85 | 1361.46 | 55.52 | 1305.94 | 0.00 | 0.00 |
Minimum of Months | 2.64 | 896.25 | 505.40 | 0.00 | 505.40 | 0.00 | 0.00 |
Maximum of Months | 2584.76 | 5295.14 | 2410.30 | 277.04 | 2133.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 463.55 | 3222.71 | 922.63 | 422.99 | 499.64 | 0.00 | 0.00 |
February | 1036.35 | 2405.28 | 1443.07 | 716.45 | 726.62 | 0.00 | 0.00 |
March | 1534.47 | 1982.09 | 1940.34 | 802.86 | 1137.48 | 0.00 | 0.00 |
April | 2350.06 | 1428.36 | 2475.68 | 1226.93 | 1248.75 | 0.00 | 0.00 |
May | 2801.18 | 1110.89 | 2734.72 | 1216.78 | 1517.94 | 0.00 | 0.00 |
June | 4185.07 | 708.56 | 3539.73 | 1821.55 | 1718.19 | 0.00 | 0.00 |
July | 4727.30 | 576.30 | 3715.05 | 2100.22 | 1614.83 | 0.00 | 0.00 |
August | 4018.92 | 637.68 | 3228.55 | 1798.85 | 1429.70 | 0.00 | 0.00 |
September | 2570.65 | 968.36 | 2283.88 | 1178.93 | 1104.95 | 0.00 | 0.00 |
October | 1511.10 | 1459.48 | 1638.56 | 832.04 | 806.53 | 0.00 | 0.00 |
November | 682.53 | 2048.45 | 1038.49 | 484.84 | 553.65 | 0.00 | 0.00 |
December | 356.23 | 2809.81 | 765.95 | 328.98 | 436.97 | 0.00 | 0.00 |
Annual Sum or Average | 2193.05 | 1610.21 | 2147.56 | 1079.48 | 1068.08 | 0.00 | 0.00 |
Minimum of Months | 356.23 | 576.30 | 765.95 | 328.98 | 436.97 | 0.00 | 0.00 |
Maximum of Months | 4727.30 | 3222.71 | 3715.05 | 2100.22 | 1718.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3896.97 | 4440.30 | 4248.34 | 3034.25 | 1214.09 | 0.00 | 0.00 |
February | 5468.38 | 3395.19 | 5410.20 | 3891.22 | 1518.98 | 0.00 | 0.00 |
March | 4873.45 | 3041.74 | 4836.01 | 2715.68 | 2120.33 | 0.00 | 0.00 |
April | 4061.82 | 2293.57 | 3887.34 | 1859.34 | 2028.00 | 0.00 | 0.00 |
May | 3685.27 | 1778.01 | 3453.81 | 1147.10 | 2306.70 | 0.00 | 0.00 |
June | 4180.35 | 1205.85 | 3431.70 | 1000.85 | 2430.85 | 0.00 | 0.00 |
July | 5009.49 | 967.81 | 3699.72 | 1366.67 | 2333.06 | 0.00 | 0.00 |
August | 5790.04 | 1083.59 | 4396.87 | 2216.82 | 2180.05 | 0.00 | 0.00 |
September | 5977.79 | 1557.07 | 4876.66 | 2988.09 | 1888.57 | 0.00 | 0.00 |
October | 5724.21 | 2226.26 | 5098.29 | 3525.40 | 1572.89 | 0.00 | 0.00 |
November | 4735.17 | 2893.92 | 4648.13 | 3366.92 | 1281.21 | 0.00 | 0.00 |
December | 3772.21 | 3871.81 | 4039.93 | 2917.24 | 1122.69 | 0.00 | 0.00 |
Annual Sum or Average | 4759.09 | 2392.53 | 4328.12 | 2493.23 | 1834.89 | 0.00 | 0.00 |
Minimum of Months | 3685.27 | 967.81 | 3431.70 | 1000.85 | 1122.69 | 0.00 | 0.00 |
Maximum of Months | 5977.79 | 4440.30 | 5410.20 | 3891.22 | 2430.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 401.31 | 3445.39 | 835.70 | 336.80 | 498.91 | 0.00 | 0.00 |
February | 1022.51 | 2623.08 | 1426.42 | 701.16 | 725.26 | 0.00 | 0.00 |
March | 1362.26 | 2258.86 | 1825.47 | 668.88 | 1156.59 | 0.00 | 0.00 |
April | 2210.07 | 1714.91 | 2383.17 | 1055.85 | 1327.31 | 0.00 | 0.00 |
May | 3079.66 | 1254.44 | 2947.80 | 1344.36 | 1603.45 | 0.00 | 0.00 |
June | 3749.94 | 865.88 | 3207.10 | 1473.14 | 1733.96 | 0.00 | 0.00 |
July | 4162.92 | 731.65 | 3285.32 | 1660.12 | 1625.20 | 0.00 | 0.00 |
August | 3422.14 | 814.23 | 2789.68 | 1369.11 | 1420.56 | 0.00 | 0.00 |
September | 2541.39 | 1107.69 | 2244.12 | 1134.54 | 1109.58 | 0.00 | 0.00 |
October | 1480.22 | 1674.68 | 1603.93 | 796.91 | 807.02 | 0.00 | 0.00 |
November | 820.43 | 2341.96 | 1135.43 | 563.27 | 572.16 | 0.00 | 0.00 |
December | 360.30 | 3181.86 | 763.22 | 322.13 | 441.08 | 0.00 | 0.00 |
Annual Sum or Average | 2056.49 | 1831.65 | 2040.05 | 953.11 | 1086.95 | 0.00 | 0.00 |
Minimum of Months | 360.30 | 731.65 | 763.22 | 322.13 | 441.08 | 0.00 | 0.00 |
Maximum of Months | 4162.92 | 3445.39 | 3285.32 | 1660.12 | 1733.96 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 18.34 | 4949.39 | 602.69 | 0.00 | 602.69 | 0.00 | 0.00 |
February | 146.79 | 3669.52 | 850.97 | 0.00 | 850.97 | 0.00 | 0.00 |
March | 480.90 | 2967.27 | 1382.36 | 0.00 | 1382.36 | 0.00 | 0.00 |
April | 827.36 | 2115.09 | 1576.18 | 9.20 | 1566.98 | 0.00 | 0.00 |
May | 1517.76 | 1585.33 | 2069.90 | 122.65 | 1947.25 | 0.00 | 0.00 |
June | 2435.28 | 1013.19 | 2410.29 | 277.04 | 2133.25 | 0.00 | 0.00 |
July | 2642.55 | 843.66 | 2201.93 | 206.24 | 1995.69 | 0.00 | 0.00 |
August | 1926.32 | 963.19 | 1764.42 | 47.29 | 1717.12 | 0.00 | 0.00 |
September | 1129.43 | 1465.48 | 1321.43 | 0.47 | 1320.95 | 0.00 | 0.00 |
October | 439.13 | 2167.58 | 963.90 | 0.00 | 963.90 | 0.00 | 0.00 |
November | 105.02 | 3090.66 | 655.27 | 0.00 | 655.27 | 0.00 | 0.00 |
December | 9.74 | 4237.89 | 505.39 | 0.00 | 505.39 | 0.00 | 0.00 |
Annual Sum or Average | 978.36 | 2417.60 | 1361.45 | 55.52 | 1305.94 | 0.00 | 0.00 |
Minimum of Months | 9.74 | 843.66 | 505.39 | 0.00 | 505.39 | 0.00 | 0.00 |
Maximum of Months | 2642.55 | 4949.39 | 2410.29 | 277.04 | 2133.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 487.65 | 3044.53 | 922.62 | 422.99 | 499.64 | 0.00 | 0.00 |
February | 1067.97 | 2261.27 | 1443.07 | 716.45 | 726.62 | 0.00 | 0.00 |
March | 1562.12 | 1870.02 | 1940.33 | 802.86 | 1137.48 | 0.00 | 0.00 |
April | 2361.42 | 1351.48 | 2475.67 | 1226.93 | 1248.75 | 0.00 | 0.00 |
May | 2800.35 | 1060.23 | 2734.70 | 1216.77 | 1517.93 | 0.00 | 0.00 |
June | 4169.29 | 691.40 | 3539.72 | 1821.54 | 1718.18 | 0.00 | 0.00 |
July | 4719.10 | 564.48 | 3715.04 | 2100.21 | 1614.83 | 0.00 | 0.00 |
August | 4005.71 | 637.16 | 3228.53 | 1798.84 | 1429.69 | 0.00 | 0.00 |
September | 2570.97 | 922.33 | 2283.87 | 1178.92 | 1104.94 | 0.00 | 0.00 |
October | 1532.76 | 1361.73 | 1638.56 | 832.03 | 806.52 | 0.00 | 0.00 |
November | 713.37 | 1891.68 | 1038.49 | 484.84 | 553.65 | 0.00 | 0.00 |
December | 382.63 | 2604.04 | 765.94 | 328.97 | 436.97 | 0.00 | 0.00 |
Annual Sum or Average | 2204.26 | 1518.99 | 2147.55 | 1079.48 | 1068.07 | 0.00 | 0.00 |
Minimum of Months | 382.63 | 564.48 | 765.94 | 328.97 | 436.97 | 0.00 | 0.00 |
Maximum of Months | 4719.10 | 3044.53 | 3715.04 | 2100.21 | 1718.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3886.90 | 4348.05 | 4248.33 | 3034.24 | 1214.09 | 0.00 | 0.00 |
February | 5440.27 | 3311.08 | 5410.18 | 3891.20 | 1518.98 | 0.00 | 0.00 |
March | 4850.32 | 2959.10 | 4835.99 | 2715.67 | 2120.32 | 0.00 | 0.00 |
April | 4054.10 | 2207.10 | 3887.33 | 1859.33 | 2027.99 | 0.00 | 0.00 |
May | 3669.90 | 1733.69 | 3453.79 | 1147.10 | 2306.69 | 0.00 | 0.00 |
June | 4172.74 | 1174.19 | 3431.69 | 1000.84 | 2430.85 | 0.00 | 0.00 |
July | 5017.76 | 936.82 | 3699.71 | 1366.66 | 2333.05 | 0.00 | 0.00 |
August | 5781.01 | 1063.95 | 4396.86 | 2216.82 | 2180.04 | 0.00 | 0.00 |
September | 5938.77 | 1527.47 | 4876.64 | 2988.08 | 1888.57 | 0.00 | 0.00 |
October | 5689.97 | 2171.37 | 5098.27 | 3525.39 | 1572.88 | 0.00 | 0.00 |
November | 4724.90 | 2802.76 | 4648.11 | 3366.91 | 1281.21 | 0.00 | 0.00 |
December | 3782.50 | 3720.39 | 4039.92 | 2917.23 | 1122.69 | 0.00 | 0.00 |
Annual Sum or Average | 4745.40 | 2326.00 | 4328.10 | 2493.22 | 1834.88 | 0.00 | 0.00 |
Minimum of Months | 3669.90 | 936.82 | 3431.69 | 1000.84 | 1122.69 | 0.00 | 0.00 |
Maximum of Months | 5938.77 | 4348.05 | 5410.18 | 3891.20 | 2430.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 421.41 | 3216.79 | 835.70 | 336.79 | 498.91 | 0.00 | 0.00 |
February | 1075.89 | 2370.69 | 1426.42 | 701.16 | 725.26 | 0.00 | 0.00 |
March | 1436.27 | 1997.86 | 1825.47 | 668.88 | 1156.59 | 0.00 | 0.00 |
April | 2289.06 | 1482.11 | 2383.16 | 1055.85 | 1327.31 | 0.00 | 0.00 |
May | 3104.89 | 1169.96 | 2947.79 | 1344.35 | 1603.44 | 0.00 | 0.00 |
June | 3782.31 | 799.43 | 3207.09 | 1473.13 | 1733.95 | 0.00 | 0.00 |
July | 4205.99 | 672.95 | 3285.30 | 1660.11 | 1625.19 | 0.00 | 0.00 |
August | 3475.11 | 726.27 | 2789.66 | 1369.11 | 1420.56 | 0.00 | 0.00 |
September | 2568.22 | 1022.04 | 2244.11 | 1134.53 | 1109.58 | 0.00 | 0.00 |
October | 1540.13 | 1475.03 | 1603.92 | 796.90 | 807.02 | 0.00 | 0.00 |
November | 876.54 | 2016.12 | 1135.42 | 563.27 | 572.16 | 0.00 | 0.00 |
December | 402.40 | 2738.73 | 763.21 | 322.13 | 441.08 | 0.00 | 0.00 |
Annual Sum or Average | 2103.51 | 1638.07 | 2040.04 | 953.10 | 1086.94 | 0.00 | 0.00 |
Minimum of Months | 402.40 | 672.95 | 763.21 | 322.13 | 441.08 | 0.00 | 0.00 |
Maximum of Months | 4205.99 | 3216.79 | 3285.30 | 1660.11 | 1733.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 27.87 | 4766.40 | 602.69 | 0.00 | 602.69 | 0.00 | 0.00 |
February | 176.71 | 3492.34 | 850.97 | 0.00 | 850.97 | 0.00 | 0.00 |
March | 528.78 | 2794.92 | 1382.36 | 0.00 | 1382.36 | 0.00 | 0.00 |
April | 881.36 | 1964.60 | 1576.18 | 9.20 | 1566.98 | 0.00 | 0.00 |
May | 1551.81 | 1495.75 | 2069.90 | 122.65 | 1947.25 | 0.00 | 0.00 |
June | 2441.59 | 987.98 | 2410.29 | 277.04 | 2133.25 | 0.00 | 0.00 |
July | 2635.26 | 833.61 | 2201.93 | 206.24 | 1995.69 | 0.00 | 0.00 |
August | 1927.77 | 938.41 | 1764.42 | 47.29 | 1717.12 | 0.00 | 0.00 |
September | 1152.33 | 1386.40 | 1321.43 | 0.47 | 1320.95 | 0.00 | 0.00 |
October | 494.13 | 1985.11 | 963.90 | 0.00 | 963.90 | 0.00 | 0.00 |
November | 131.25 | 2854.39 | 655.27 | 0.00 | 655.27 | 0.00 | 0.00 |
December | 13.26 | 4030.37 | 505.39 | 0.00 | 505.39 | 0.00 | 0.00 |
Annual Sum or Average | 1001.89 | 2289.77 | 1361.45 | 55.52 | 1305.94 | 0.00 | 0.00 |
Minimum of Months | 13.26 | 833.61 | 505.39 | 0.00 | 505.39 | 0.00 | 0.00 |
Maximum of Months | 2635.26 | 4766.40 | 2410.29 | 277.04 | 2133.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 504.98 | 2935.42 | 922.62 | 422.99 | 499.64 | 0.00 | 0.00 |
February | 1099.37 | 2157.78 | 1443.07 | 716.45 | 726.62 | 0.00 | 0.00 |
March | 1596.14 | 1771.88 | 1940.33 | 802.86 | 1137.48 | 0.00 | 0.00 |
April | 2389.88 | 1271.59 | 2475.67 | 1226.93 | 1248.75 | 0.00 | 0.00 |
May | 2811.04 | 1010.09 | 2734.70 | 1216.77 | 1517.93 | 0.00 | 0.00 |
June | 4163.78 | 680.21 | 3539.72 | 1821.54 | 1718.18 | 0.00 | 0.00 |
July | 4708.04 | 560.37 | 3715.04 | 2100.21 | 1614.83 | 0.00 | 0.00 |
August | 4000.13 | 626.44 | 3228.53 | 1798.84 | 1429.69 | 0.00 | 0.00 |
September | 2579.50 | 885.46 | 2283.87 | 1178.92 | 1104.94 | 0.00 | 0.00 |
October | 1569.23 | 1263.80 | 1638.56 | 832.03 | 806.52 | 0.00 | 0.00 |
November | 748.40 | 1757.00 | 1038.49 | 484.84 | 553.65 | 0.00 | 0.00 |
December | 399.68 | 2477.57 | 765.94 | 328.97 | 436.97 | 0.00 | 0.00 |
Annual Sum or Average | 2220.54 | 1447.28 | 2147.55 | 1079.48 | 1068.07 | 0.00 | 0.00 |
Minimum of Months | 399.68 | 560.37 | 765.94 | 328.97 | 436.97 | 0.00 | 0.00 |
Maximum of Months | 4708.04 | 2935.42 | 3715.04 | 2100.21 | 1718.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3928.80 | 4162.52 | 4248.33 | 3034.24 | 1214.09 | 0.00 | 0.00 |
February | 5484.58 | 3147.30 | 5410.18 | 3891.20 | 1518.98 | 0.00 | 0.00 |
March | 4894.44 | 2795.79 | 4835.99 | 2715.67 | 2120.32 | 0.00 | 0.00 |
April | 4089.76 | 2071.24 | 3887.33 | 1859.33 | 2027.99 | 0.00 | 0.00 |
May | 3687.24 | 1644.65 | 3453.79 | 1147.10 | 2306.69 | 0.00 | 0.00 |
June | 4169.72 | 1144.45 | 3431.69 | 1000.84 | 2430.85 | 0.00 | 0.00 |
July | 5005.30 | 922.85 | 3699.71 | 1366.66 | 2333.05 | 0.00 | 0.00 |
August | 5772.82 | 1038.78 | 4396.86 | 2216.82 | 2180.04 | 0.00 | 0.00 |
September | 5946.43 | 1459.82 | 4876.64 | 2988.08 | 1888.57 | 0.00 | 0.00 |
October | 5731.99 | 2018.60 | 5098.27 | 3525.39 | 1572.88 | 0.00 | 0.00 |
November | 4791.02 | 2600.08 | 4648.11 | 3366.91 | 1281.21 | 0.00 | 0.00 |
December | 3839.80 | 3513.31 | 4039.92 | 2917.23 | 1122.69 | 0.00 | 0.00 |
Annual Sum or Average | 4773.01 | 2206.53 | 4328.10 | 2493.22 | 1834.88 | 0.00 | 0.00 |
Minimum of Months | 3687.24 | 922.85 | 3431.69 | 1000.84 | 1122.69 | 0.00 | 0.00 |
Maximum of Months | 5946.43 | 4162.52 | 5410.18 | 3891.20 | 2430.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 432.00 | 3103.90 | 835.70 | 336.79 | 498.91 | 0.00 | 0.00 |
February | 1091.44 | 2274.05 | 1426.42 | 701.16 | 725.26 | 0.00 | 0.00 |
March | 1455.66 | 1904.38 | 1825.47 | 668.88 | 1156.59 | 0.00 | 0.00 |
April | 2310.51 | 1403.03 | 2383.16 | 1055.85 | 1327.31 | 0.00 | 0.00 |
May | 3113.36 | 1117.26 | 2947.79 | 1344.35 | 1603.44 | 0.00 | 0.00 |
June | 3778.67 | 781.61 | 3207.09 | 1473.13 | 1733.95 | 0.00 | 0.00 |
July | 4197.63 | 664.10 | 3285.30 | 1660.11 | 1625.19 | 0.00 | 0.00 |
August | 3471.80 | 710.72 | 2789.66 | 1369.11 | 1420.56 | 0.00 | 0.00 |
September | 2575.14 | 980.36 | 2244.11 | 1134.53 | 1109.58 | 0.00 | 0.00 |
October | 1563.85 | 1381.61 | 1603.92 | 796.90 | 807.02 | 0.00 | 0.00 |
November | 897.08 | 1891.58 | 1135.42 | 563.27 | 572.16 | 0.00 | 0.00 |
December | 412.77 | 2617.27 | 763.21 | 322.13 | 441.08 | 0.00 | 0.00 |
Annual Sum or Average | 2113.59 | 1566.70 | 2040.04 | 953.10 | 1086.94 | 0.00 | 0.00 |
Minimum of Months | 412.77 | 664.10 | 763.21 | 322.13 | 441.08 | 0.00 | 0.00 |
Maximum of Months | 4197.63 | 3103.90 | 3285.30 | 1660.11 | 1733.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 21957684.59 | 0.141825E+11 | 0.161426E+10 | 0.00 | 0.161426E+10 | 0.00 | 0.00 |
February | 0.229582E+09 | 0.964962E+10 | 0.205867E+10 | 0.00 | 0.205867E+10 | 0.00 | 0.00 |
March | 0.107559E+10 | 0.868507E+10 | 0.370252E+10 | 0.00 | 0.370252E+10 | 0.00 | 0.00 |
April | 0.194918E+10 | 0.603910E+10 | 0.408548E+10 | 23841933.03 | 0.406164E+10 | 0.00 | 0.00 |
May | 0.395668E+10 | 0.450640E+10 | 0.554405E+10 | 0.328519E+09 | 0.521553E+10 | 0.00 | 0.00 |
June | 0.623135E+10 | 0.274210E+10 | 0.624749E+10 | 0.718096E+09 | 0.552939E+10 | 0.00 | 0.00 |
July | 0.692301E+10 | 0.240053E+10 | 0.589767E+10 | 0.552388E+09 | 0.534528E+10 | 0.00 | 0.00 |
August | 0.504134E+10 | 0.272726E+10 | 0.472583E+10 | 0.126674E+09 | 0.459916E+10 | 0.00 | 0.00 |
September | 0.282808E+10 | 0.406911E+10 | 0.342515E+10 | 1229129.56 | 0.342392E+10 | 0.00 | 0.00 |
October | 0.101190E+10 | 0.642139E+10 | 0.258173E+10 | 0.00 | 0.258173E+10 | 0.00 | 0.00 |
November | 0.188605E+09 | 0.899727E+10 | 0.169847E+10 | 0.00 | 0.169847E+10 | 0.00 | 0.00 |
December | 7066988.40 | 0.126091E+11 | 0.135365E+10 | 0.00 | 0.135365E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.294643E+11 | 0.830294E+11 | 0.429350E+11 | 0.175075E+10 | 0.411842E+11 | 0.00 | 0.00 |
Minimum of Months | 7066988.40 | 0.240053E+10 | 0.135365E+10 | 0.00 | 0.135365E+10 | 0.00 | 0.00 |
Maximum of Months | 0.692301E+10 | 0.141825E+11 | 0.624749E+10 | 0.718096E+09 | 0.552939E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.124156E+10 | 0.863169E+10 | 0.247117E+10 | 0.113293E+10 | 0.133824E+10 | 0.00 | 0.00 |
February | 0.250714E+10 | 0.581886E+10 | 0.349108E+10 | 0.173324E+10 | 0.175784E+10 | 0.00 | 0.00 |
March | 0.410993E+10 | 0.530884E+10 | 0.519701E+10 | 0.215038E+10 | 0.304663E+10 | 0.00 | 0.00 |
April | 0.609135E+10 | 0.370231E+10 | 0.641697E+10 | 0.318021E+10 | 0.323677E+10 | 0.00 | 0.00 |
May | 0.750267E+10 | 0.297540E+10 | 0.732466E+10 | 0.325902E+10 | 0.406565E+10 | 0.00 | 0.00 |
June | 0.108477E+11 | 0.183658E+10 | 0.917499E+10 | 0.472145E+10 | 0.445355E+10 | 0.00 | 0.00 |
July | 0.126616E+11 | 0.154355E+10 | 0.995039E+10 | 0.562522E+10 | 0.432517E+10 | 0.00 | 0.00 |
August | 0.107643E+11 | 0.170795E+10 | 0.864734E+10 | 0.481803E+10 | 0.382931E+10 | 0.00 | 0.00 |
September | 0.666312E+10 | 0.250998E+10 | 0.591981E+10 | 0.305578E+10 | 0.286403E+10 | 0.00 | 0.00 |
October | 0.404734E+10 | 0.390907E+10 | 0.438873E+10 | 0.222853E+10 | 0.216020E+10 | 0.00 | 0.00 |
November | 0.176912E+10 | 0.530957E+10 | 0.269177E+10 | 0.125670E+10 | 0.143507E+10 | 0.00 | 0.00 |
December | 0.954129E+09 | 0.752580E+10 | 0.205151E+10 | 0.881129E+09 | 0.117038E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.691600E+11 | 0.507796E+11 | 0.677254E+11 | 0.340426E+11 | 0.336828E+11 | 0.00 | 0.00 |
Minimum of Months | 0.954129E+09 | 0.154355E+10 | 0.205151E+10 | 0.881129E+09 | 0.117038E+10 | 0.00 | 0.00 |
Maximum of Months | 0.126616E+11 | 0.863169E+10 | 0.995039E+10 | 0.562522E+10 | 0.445355E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.104377E+11 | 0.118929E+11 | 0.113788E+11 | 0.812693E+10 | 0.325182E+10 | 0.00 | 0.00 |
February | 0.132291E+11 | 0.821365E+10 | 0.130884E+11 | 0.941363E+10 | 0.367472E+10 | 0.00 | 0.00 |
March | 0.130531E+11 | 0.814699E+10 | 0.129528E+11 | 0.727368E+10 | 0.567909E+10 | 0.00 | 0.00 |
April | 0.105282E+11 | 0.594493E+10 | 0.100760E+11 | 0.481941E+10 | 0.525658E+10 | 0.00 | 0.00 |
May | 0.987062E+10 | 0.476221E+10 | 0.925067E+10 | 0.307240E+10 | 0.617827E+10 | 0.00 | 0.00 |
June | 0.108355E+11 | 0.312557E+10 | 0.889497E+10 | 0.259420E+10 | 0.630078E+10 | 0.00 | 0.00 |
July | 0.134174E+11 | 0.259217E+10 | 0.990933E+10 | 0.366048E+10 | 0.624886E+10 | 0.00 | 0.00 |
August | 0.155080E+11 | 0.290227E+10 | 0.117766E+11 | 0.593754E+10 | 0.583905E+10 | 0.00 | 0.00 |
September | 0.154944E+11 | 0.403591E+10 | 0.126403E+11 | 0.774513E+10 | 0.489518E+10 | 0.00 | 0.00 |
October | 0.153317E+11 | 0.596282E+10 | 0.136553E+11 | 0.944244E+10 | 0.421282E+10 | 0.00 | 0.00 |
November | 0.122736E+11 | 0.750105E+10 | 0.120480E+11 | 0.872705E+10 | 0.332090E+10 | 0.00 | 0.00 |
December | 0.101035E+11 | 0.103702E+11 | 0.108206E+11 | 0.781354E+10 | 0.300702E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.150083E+12 | 0.754507E+11 | 0.136492E+12 | 0.786264E+11 | 0.578651E+11 | 0.00 | 0.00 |
Minimum of Months | 0.987062E+10 | 0.259217E+10 | 0.889497E+10 | 0.259420E+10 | 0.300702E+10 | 0.00 | 0.00 |
Maximum of Months | 0.155080E+11 | 0.118929E+11 | 0.136553E+11 | 0.944244E+10 | 0.630078E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.107487E+10 | 0.922813E+10 | 0.223835E+10 | 0.902072E+09 | 0.133628E+10 | 0.00 | 0.00 |
February | 0.247367E+10 | 0.634576E+10 | 0.345080E+10 | 0.169624E+10 | 0.175456E+10 | 0.00 | 0.00 |
March | 0.364867E+10 | 0.605014E+10 | 0.488935E+10 | 0.179153E+10 | 0.309782E+10 | 0.00 | 0.00 |
April | 0.572850E+10 | 0.444505E+10 | 0.617716E+10 | 0.273677E+10 | 0.344039E+10 | 0.00 | 0.00 |
May | 0.824857E+10 | 0.335990E+10 | 0.789540E+10 | 0.360072E+10 | 0.429468E+10 | 0.00 | 0.00 |
June | 0.971985E+10 | 0.224436E+10 | 0.831280E+10 | 0.381838E+10 | 0.449442E+10 | 0.00 | 0.00 |
July | 0.111500E+11 | 0.195966E+10 | 0.879939E+10 | 0.444646E+10 | 0.435293E+10 | 0.00 | 0.00 |
August | 0.916587E+10 | 0.218084E+10 | 0.747187E+10 | 0.366703E+10 | 0.380483E+10 | 0.00 | 0.00 |
September | 0.658728E+10 | 0.287113E+10 | 0.581676E+10 | 0.294072E+10 | 0.287604E+10 | 0.00 | 0.00 |
October | 0.396463E+10 | 0.448546E+10 | 0.429596E+10 | 0.213443E+10 | 0.216153E+10 | 0.00 | 0.00 |
November | 0.212656E+10 | 0.607036E+10 | 0.294303E+10 | 0.146000E+10 | 0.148304E+10 | 0.00 | 0.00 |
December | 0.965017E+09 | 0.852229E+10 | 0.204420E+10 | 0.862798E+09 | 0.118140E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.648535E+11 | 0.577631E+11 | 0.643351E+11 | 0.300572E+11 | 0.342779E+11 | 0.00 | 0.00 |
Minimum of Months | 0.965017E+09 | 0.195966E+10 | 0.204420E+10 | 0.862798E+09 | 0.118140E+10 | 0.00 | 0.00 |
Maximum of Months | 0.111500E+11 | 0.922813E+10 | 0.879939E+10 | 0.444646E+10 | 0.449442E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 49115720.69 | 0.132565E+11 | 0.161426E+10 | 0.00 | 0.161426E+10 | 0.00 | 0.00 |
February | 0.355108E+09 | 0.887730E+10 | 0.205866E+10 | 0.00 | 0.205866E+10 | 0.00 | 0.00 |
March | 0.128804E+10 | 0.794753E+10 | 0.370251E+10 | 0.00 | 0.370251E+10 | 0.00 | 0.00 |
April | 0.214453E+10 | 0.548231E+10 | 0.408546E+10 | 23841848.37 | 0.406162E+10 | 0.00 | 0.00 |
May | 0.406516E+10 | 0.424614E+10 | 0.554403E+10 | 0.328518E+09 | 0.521551E+10 | 0.00 | 0.00 |
June | 0.631226E+10 | 0.262620E+10 | 0.624747E+10 | 0.718093E+09 | 0.552937E+10 | 0.00 | 0.00 |
July | 0.707780E+10 | 0.225965E+10 | 0.589765E+10 | 0.552386E+09 | 0.534526E+10 | 0.00 | 0.00 |
August | 0.515944E+10 | 0.257981E+10 | 0.472582E+10 | 0.126674E+09 | 0.459914E+10 | 0.00 | 0.00 |
September | 0.292748E+10 | 0.379852E+10 | 0.342514E+10 | 1229125.19 | 0.342391E+10 | 0.00 | 0.00 |
October | 0.117618E+10 | 0.580564E+10 | 0.258172E+10 | 0.00 | 0.258172E+10 | 0.00 | 0.00 |
November | 0.272222E+09 | 0.801099E+10 | 0.169846E+10 | 0.00 | 0.169846E+10 | 0.00 | 0.00 |
December | 26074433.61 | 0.113508E+11 | 0.135365E+10 | 0.00 | 0.135365E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.308534E+11 | 0.762413E+11 | 0.429348E+11 | 0.175074E+10 | 0.411841E+11 | 0.00 | 0.00 |
Minimum of Months | 26074433.61 | 0.225965E+10 | 0.135365E+10 | 0.00 | 0.135365E+10 | 0.00 | 0.00 |
Maximum of Months | 0.707780E+10 | 0.132565E+11 | 0.624747E+10 | 0.718093E+09 | 0.552937E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.130611E+10 | 0.815448E+10 | 0.247116E+10 | 0.113292E+10 | 0.133823E+10 | 0.00 | 0.00 |
February | 0.258364E+10 | 0.547047E+10 | 0.349106E+10 | 0.173323E+10 | 0.175783E+10 | 0.00 | 0.00 |
March | 0.418398E+10 | 0.500866E+10 | 0.519699E+10 | 0.215037E+10 | 0.304662E+10 | 0.00 | 0.00 |
April | 0.612081E+10 | 0.350303E+10 | 0.641695E+10 | 0.318019E+10 | 0.323676E+10 | 0.00 | 0.00 |
May | 0.750047E+10 | 0.283973E+10 | 0.732463E+10 | 0.325900E+10 | 0.406563E+10 | 0.00 | 0.00 |
June | 0.108068E+11 | 0.179212E+10 | 0.917496E+10 | 0.472143E+10 | 0.445353E+10 | 0.00 | 0.00 |
July | 0.126396E+11 | 0.151191E+10 | 0.995035E+10 | 0.562520E+10 | 0.432515E+10 | 0.00 | 0.00 |
August | 0.107289E+11 | 0.170657E+10 | 0.864730E+10 | 0.481801E+10 | 0.382929E+10 | 0.00 | 0.00 |
September | 0.666397E+10 | 0.239069E+10 | 0.591979E+10 | 0.305577E+10 | 0.286402E+10 | 0.00 | 0.00 |
October | 0.410535E+10 | 0.364727E+10 | 0.438871E+10 | 0.222852E+10 | 0.216019E+10 | 0.00 | 0.00 |
November | 0.184906E+10 | 0.490323E+10 | 0.269175E+10 | 0.125670E+10 | 0.143506E+10 | 0.00 | 0.00 |
December | 0.102485E+10 | 0.697467E+10 | 0.205150E+10 | 0.881125E+09 | 0.117038E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.695136E+11 | 0.479028E+11 | 0.677252E+11 | 0.340425E+11 | 0.336827E+11 | 0.00 | 0.00 |
Minimum of Months | 0.102485E+10 | 0.151191E+10 | 0.205150E+10 | 0.881125E+09 | 0.117038E+10 | 0.00 | 0.00 |
Maximum of Months | 0.126396E+11 | 0.815448E+10 | 0.995035E+10 | 0.562520E+10 | 0.445353E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.104107E+11 | 0.116458E+11 | 0.113787E+11 | 0.812691E+10 | 0.325181E+10 | 0.00 | 0.00 |
February | 0.131611E+11 | 0.801016E+10 | 0.130883E+11 | 0.941360E+10 | 0.367471E+10 | 0.00 | 0.00 |
March | 0.129911E+11 | 0.792566E+10 | 0.129527E+11 | 0.727366E+10 | 0.567907E+10 | 0.00 | 0.00 |
April | 0.105082E+11 | 0.572081E+10 | 0.100760E+11 | 0.481940E+10 | 0.525656E+10 | 0.00 | 0.00 |
May | 0.982945E+10 | 0.464353E+10 | 0.925064E+10 | 0.307239E+10 | 0.617825E+10 | 0.00 | 0.00 |
June | 0.108157E+11 | 0.304351E+10 | 0.889494E+10 | 0.259419E+10 | 0.630075E+10 | 0.00 | 0.00 |
July | 0.134396E+11 | 0.250917E+10 | 0.990930E+10 | 0.366046E+10 | 0.624883E+10 | 0.00 | 0.00 |
August | 0.154839E+11 | 0.284969E+10 | 0.117765E+11 | 0.593752E+10 | 0.583902E+10 | 0.00 | 0.00 |
September | 0.153933E+11 | 0.395919E+10 | 0.126403E+11 | 0.774510E+10 | 0.489516E+10 | 0.00 | 0.00 |
October | 0.152400E+11 | 0.581578E+10 | 0.136552E+11 | 0.944240E+10 | 0.421281E+10 | 0.00 | 0.00 |
November | 0.122469E+11 | 0.726474E+10 | 0.120479E+11 | 0.872702E+10 | 0.332089E+10 | 0.00 | 0.00 |
December | 0.101311E+11 | 0.996469E+10 | 0.108205E+11 | 0.781351E+10 | 0.300701E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.149651E+12 | 0.733528E+11 | 0.136491E+12 | 0.786262E+11 | 0.578649E+11 | 0.00 | 0.00 |
Minimum of Months | 0.982945E+10 | 0.250917E+10 | 0.889494E+10 | 0.259419E+10 | 0.300701E+10 | 0.00 | 0.00 |
Maximum of Months | 0.154839E+11 | 0.116458E+11 | 0.136552E+11 | 0.944240E+10 | 0.630075E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.112870E+10 | 0.861586E+10 | 0.223834E+10 | 0.902069E+09 | 0.133627E+10 | 0.00 | 0.00 |
February | 0.260279E+10 | 0.573517E+10 | 0.345079E+10 | 0.169624E+10 | 0.175455E+10 | 0.00 | 0.00 |
March | 0.384690E+10 | 0.535106E+10 | 0.488933E+10 | 0.179152E+10 | 0.309780E+10 | 0.00 | 0.00 |
April | 0.593324E+10 | 0.384163E+10 | 0.617714E+10 | 0.273676E+10 | 0.344038E+10 | 0.00 | 0.00 |
May | 0.831614E+10 | 0.313363E+10 | 0.789537E+10 | 0.360071E+10 | 0.429466E+10 | 0.00 | 0.00 |
June | 0.980374E+10 | 0.207213E+10 | 0.831276E+10 | 0.381836E+10 | 0.449440E+10 | 0.00 | 0.00 |
July | 0.112653E+11 | 0.180243E+10 | 0.879935E+10 | 0.444644E+10 | 0.435291E+10 | 0.00 | 0.00 |
August | 0.930774E+10 | 0.194524E+10 | 0.747184E+10 | 0.366702E+10 | 0.380482E+10 | 0.00 | 0.00 |
September | 0.665682E+10 | 0.264913E+10 | 0.581673E+10 | 0.294070E+10 | 0.287603E+10 | 0.00 | 0.00 |
October | 0.412509E+10 | 0.395072E+10 | 0.429595E+10 | 0.213442E+10 | 0.216152E+10 | 0.00 | 0.00 |
November | 0.227200E+10 | 0.522579E+10 | 0.294302E+10 | 0.145999E+10 | 0.148303E+10 | 0.00 | 0.00 |
December | 0.107778E+10 | 0.733542E+10 | 0.204419E+10 | 0.862794E+09 | 0.118139E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.663363E+11 | 0.516582E+11 | 0.643348E+11 | 0.300570E+11 | 0.342778E+11 | 0.00 | 0.00 |
Minimum of Months | 0.107778E+10 | 0.180243E+10 | 0.204419E+10 | 0.862794E+09 | 0.118139E+10 | 0.00 | 0.00 |
Maximum of Months | 0.112653E+11 | 0.861586E+10 | 0.879935E+10 | 0.444644E+10 | 0.449440E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 74659710.91 | 0.127663E+11 | 0.161426E+10 | 0.00 | 0.161426E+10 | 0.00 | 0.00 |
February | 0.427485E+09 | 0.844866E+10 | 0.205866E+10 | 0.00 | 0.205866E+10 | 0.00 | 0.00 |
March | 0.141629E+10 | 0.748592E+10 | 0.370251E+10 | 0.00 | 0.370251E+10 | 0.00 | 0.00 |
April | 0.228449E+10 | 0.509224E+10 | 0.408546E+10 | 23841848.37 | 0.406162E+10 | 0.00 | 0.00 |
May | 0.415637E+10 | 0.400621E+10 | 0.554403E+10 | 0.328518E+09 | 0.521551E+10 | 0.00 | 0.00 |
June | 0.632859E+10 | 0.256085E+10 | 0.624747E+10 | 0.718093E+09 | 0.552937E+10 | 0.00 | 0.00 |
July | 0.705827E+10 | 0.223273E+10 | 0.589765E+10 | 0.552386E+09 | 0.534526E+10 | 0.00 | 0.00 |
August | 0.516335E+10 | 0.251344E+10 | 0.472582E+10 | 0.126674E+09 | 0.459914E+10 | 0.00 | 0.00 |
September | 0.298683E+10 | 0.359354E+10 | 0.342514E+10 | 1229125.19 | 0.342391E+10 | 0.00 | 0.00 |
October | 0.132348E+10 | 0.531691E+10 | 0.258172E+10 | 0.00 | 0.258172E+10 | 0.00 | 0.00 |
November | 0.340190E+09 | 0.739857E+10 | 0.169846E+10 | 0.00 | 0.169846E+10 | 0.00 | 0.00 |
December | 35507480.39 | 0.107949E+11 | 0.135365E+10 | 0.00 | 0.135365E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.315955E+11 | 0.722103E+11 | 0.429348E+11 | 0.175074E+10 | 0.411841E+11 | 0.00 | 0.00 |
Minimum of Months | 35507480.39 | 0.223273E+10 | 0.135365E+10 | 0.00 | 0.135365E+10 | 0.00 | 0.00 |
Maximum of Months | 0.705827E+10 | 0.127663E+11 | 0.624747E+10 | 0.718093E+09 | 0.552937E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.135253E+10 | 0.786224E+10 | 0.247116E+10 | 0.113292E+10 | 0.133823E+10 | 0.00 | 0.00 |
February | 0.265961E+10 | 0.522010E+10 | 0.349106E+10 | 0.173323E+10 | 0.175783E+10 | 0.00 | 0.00 |
March | 0.427510E+10 | 0.474580E+10 | 0.519699E+10 | 0.215037E+10 | 0.304662E+10 | 0.00 | 0.00 |
April | 0.619458E+10 | 0.329595E+10 | 0.641695E+10 | 0.318019E+10 | 0.323676E+10 | 0.00 | 0.00 |
May | 0.752908E+10 | 0.270543E+10 | 0.732463E+10 | 0.325900E+10 | 0.406563E+10 | 0.00 | 0.00 |
June | 0.107925E+11 | 0.176311E+10 | 0.917496E+10 | 0.472143E+10 | 0.445353E+10 | 0.00 | 0.00 |
July | 0.126100E+11 | 0.150090E+10 | 0.995035E+10 | 0.562520E+10 | 0.432515E+10 | 0.00 | 0.00 |
August | 0.107140E+11 | 0.167787E+10 | 0.864730E+10 | 0.481801E+10 | 0.382929E+10 | 0.00 | 0.00 |
September | 0.668607E+10 | 0.229512E+10 | 0.591979E+10 | 0.305577E+10 | 0.286402E+10 | 0.00 | 0.00 |
October | 0.420302E+10 | 0.338496E+10 | 0.438871E+10 | 0.222852E+10 | 0.216019E+10 | 0.00 | 0.00 |
November | 0.193985E+10 | 0.455414E+10 | 0.269175E+10 | 0.125670E+10 | 0.143506E+10 | 0.00 | 0.00 |
December | 0.107050E+10 | 0.663592E+10 | 0.205150E+10 | 0.881125E+09 | 0.117038E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.700268E+11 | 0.456415E+11 | 0.677252E+11 | 0.340425E+11 | 0.336827E+11 | 0.00 | 0.00 |
Minimum of Months | 0.107050E+10 | 0.150090E+10 | 0.205150E+10 | 0.881125E+09 | 0.117038E+10 | 0.00 | 0.00 |
Maximum of Months | 0.126100E+11 | 0.786224E+10 | 0.995035E+10 | 0.562520E+10 | 0.445353E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.105229E+11 | 0.111489E+11 | 0.113787E+11 | 0.812691E+10 | 0.325181E+10 | 0.00 | 0.00 |
February | 0.132683E+11 | 0.761395E+10 | 0.130883E+11 | 0.941360E+10 | 0.367471E+10 | 0.00 | 0.00 |
March | 0.131093E+11 | 0.748825E+10 | 0.129527E+11 | 0.727366E+10 | 0.567907E+10 | 0.00 | 0.00 |
April | 0.106007E+11 | 0.536865E+10 | 0.100760E+11 | 0.481940E+10 | 0.525656E+10 | 0.00 | 0.00 |
May | 0.987589E+10 | 0.440503E+10 | 0.925064E+10 | 0.307239E+10 | 0.617825E+10 | 0.00 | 0.00 |
June | 0.108079E+11 | 0.296642E+10 | 0.889494E+10 | 0.259419E+10 | 0.630075E+10 | 0.00 | 0.00 |
July | 0.134062E+11 | 0.247177E+10 | 0.990930E+10 | 0.366046E+10 | 0.624883E+10 | 0.00 | 0.00 |
August | 0.154619E+11 | 0.278226E+10 | 0.117765E+11 | 0.593752E+10 | 0.583902E+10 | 0.00 | 0.00 |
September | 0.154131E+11 | 0.378385E+10 | 0.126403E+11 | 0.774510E+10 | 0.489516E+10 | 0.00 | 0.00 |
October | 0.153526E+11 | 0.540661E+10 | 0.136552E+11 | 0.944240E+10 | 0.421281E+10 | 0.00 | 0.00 |
November | 0.124183E+11 | 0.673942E+10 | 0.120479E+11 | 0.872702E+10 | 0.332089E+10 | 0.00 | 0.00 |
December | 0.102845E+11 | 0.941005E+10 | 0.108205E+11 | 0.781351E+10 | 0.300701E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.150522E+12 | 0.695851E+11 | 0.136491E+12 | 0.786262E+11 | 0.578649E+11 | 0.00 | 0.00 |
Minimum of Months | 0.987589E+10 | 0.247177E+10 | 0.889494E+10 | 0.259419E+10 | 0.300701E+10 | 0.00 | 0.00 |
Maximum of Months | 0.154619E+11 | 0.111489E+11 | 0.136552E+11 | 0.944240E+10 | 0.630075E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.115706E+10 | 0.831348E+10 | 0.223834E+10 | 0.902069E+09 | 0.133627E+10 | 0.00 | 0.00 |
February | 0.264041E+10 | 0.550138E+10 | 0.345079E+10 | 0.169624E+10 | 0.175455E+10 | 0.00 | 0.00 |
March | 0.389885E+10 | 0.510069E+10 | 0.488933E+10 | 0.179152E+10 | 0.309780E+10 | 0.00 | 0.00 |
April | 0.598884E+10 | 0.363665E+10 | 0.617714E+10 | 0.273676E+10 | 0.344038E+10 | 0.00 | 0.00 |
May | 0.833883E+10 | 0.299247E+10 | 0.789537E+10 | 0.360071E+10 | 0.429466E+10 | 0.00 | 0.00 |
June | 0.979432E+10 | 0.202594E+10 | 0.831276E+10 | 0.381836E+10 | 0.449440E+10 | 0.00 | 0.00 |
July | 0.112429E+11 | 0.177872E+10 | 0.879935E+10 | 0.444644E+10 | 0.435291E+10 | 0.00 | 0.00 |
August | 0.929887E+10 | 0.190360E+10 | 0.747184E+10 | 0.366702E+10 | 0.380482E+10 | 0.00 | 0.00 |
September | 0.667477E+10 | 0.254108E+10 | 0.581673E+10 | 0.294070E+10 | 0.287603E+10 | 0.00 | 0.00 |
October | 0.418863E+10 | 0.370050E+10 | 0.429595E+10 | 0.213442E+10 | 0.216152E+10 | 0.00 | 0.00 |
November | 0.232524E+10 | 0.490297E+10 | 0.294302E+10 | 0.145999E+10 | 0.148303E+10 | 0.00 | 0.00 |
December | 0.110557E+10 | 0.701010E+10 | 0.204419E+10 | 0.862794E+09 | 0.118139E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.666543E+11 | 0.494076E+11 | 0.643348E+11 | 0.300570E+11 | 0.342778E+11 | 0.00 | 0.00 |
Minimum of Months | 0.110557E+10 | 0.177872E+10 | 0.204419E+10 | 0.862794E+09 | 0.118139E+10 | 0.00 | 0.00 |
Maximum of Months | 0.112429E+11 | 0.831348E+10 | 0.879935E+10 | 0.444644E+10 | 0.449440E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -8.8 | -10.9 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
February | -2.2 | -5.0 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
March | 0.30 | -2.9 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
April | 6.67 | 2.34 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
June | 16.46 | 10.06 | 4.91 | 4.56 | 5.05 | 103.05 | 264.47 | 0.02 |
July | 20.57 | 12.46 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
August | 19.17 | 11.04 | 4.61 | 4.29 | 7.19 | 78.96 | 261.05 | 0.00 |
September | 14.69 | 9.08 | 4.37 | 5.43 | 3.42 | 63.03 | 204.21 | 0.00 |
October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
November | 2.84 | -0.9 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
December | -4.1 | -6.5 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
Annual Sum or Average | 7.07 | 2.37 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
Minimum of Months | -8.8 | -10.9 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
Maximum of Months | 20.57 | 12.46 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.60 | 14-JAN-12:00 | 5.16 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
February | 18.90 | 27-FEB-14:00 | 7.23 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 15.00 | 14-MAR-13:20 | 6.67 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
April | 23.30 | 07-APR-13:00 | 9.68 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
May | 30.00 | 20-MAY-15:00 | 15.22 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 32.20 | 29-JUN-12:00 | 14.40 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
July | 37.20 | 17-JUL-15:00 | 17.28 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
August | 35.60 | 05-AUG-15:00 | 17.65 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 34.40 | 02-SEP-14:00 | 16.28 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
October | 25.00 | 18-OCT-13:00 | 11.40 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
November | 17.20 | 04-NOV-13:00 | 8.18 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
December | 13.90 | 10-DEC-01:00 | 5.50 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.60 | 5.16 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
Maximum of Months | 37.20 | 17.65 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -33.9 | 10-JAN-21:00 | -34.1 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
April | -7.8 | 29-APR-03:00 | -8.7 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
June | 0.60 | 15-JUN-03:00 | -0.5 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
July | 5.60 | 08-JUL-03:00 | 2.99 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
September | 0.00 | 17-SEP-02:00 | -1.6 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
December | -28.3 | 29-DEC-08:00 | -28.6 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -33.9 | -34.1 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.18 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
February | 7.23 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
March | 6.94 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
April | 11.02 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
May | 15.22 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
June | 19.20 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
July | 19.21 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
August | 17.65 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
September | 20.12 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
October | 11.61 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
November | 8.89 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
December | 7.62 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 5.18 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.70 | 12-JAN-14:00 | 7.20 | 4.48 | 5.20 | -1.0 | 107.00 | 61.00 |
February | -0.6 | 11-FEB-08:00 | 4.40 | 2.16 | 10.80 | -5.7 | 69.50 | 50.50 |
March | -0.6 | 10-MAR-12:00 | 8.90 | 4.51 | 10.30 | -2.3 | 253.00 | 140.50 |
April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.87 | 201.50 | 117.50 |
May | 12.20 | 02-MAY-12:00 | 18.90 | 14.61 | 12.90 | 14.84 | 108.50 | 934.50 |
June | 15.60 | 20-JUN-19:00 | 25.60 | 18.76 | 3.60 | 20.22 | 17.50 | 17.00 |
July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
August | 11.10 | 08-AUG-11:00 | 26.70 | 16.75 | 2.60 | 12.03 | 134.50 | 869.00 |
September | 18.30 | 07-SEP-14:00 | 24.40 | 20.10 | 4.10 | 15.57 | 111.00 | 720.00 |
October | 6.70 | 01-OCT-14:09 | 9.08 | 7.78 | 2.10 | 4.07 | 260.33 | 0.33 |
November | 3.30 | 16-NOV-19:00 | 10.60 | 6.88 | 9.80 | -1.7 | 0.00 | 0.00 |
December | 2.80 | 19-DEC-14:09 | 10.97 | 6.81 | 10.78 | -1.0 | 95.00 | 292.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.6 | 4.40 | 2.16 | 2.10 | -5.7 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 26.70 | 20.10 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.438917E+11 | -0.434465E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -445190320.4 | 60.05 | 0.00 | 0.00 |
February | 0.405625E+11 | -0.401603E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -402207774.2 | 60.05 | 0.00 | 0.00 |
March | 0.472083E+11 | -0.467627E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -445598787.6 | 60.05 | 0.00 | 0.00 |
April | 0.413086E+11 | -0.408794E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -429120481.3 | 60.05 | 0.00 | 0.00 |
May | 0.417468E+11 | -0.413036E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -443215710.1 | 60.05 | 0.00 | 0.00 |
June | 0.388872E+11 | -0.384626E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -424583141.3 | 60.05 | 0.00 | 0.00 |
July | 0.351749E+11 | -0.347545E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -420470039.2 | 60.05 | 0.00 | 0.00 |
August | 0.376441E+11 | -0.372113E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -432761544.1 | 60.05 | 0.00 | 0.00 |
September | 0.346319E+11 | -0.342090E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -422897243.6 | 60.05 | 0.00 | 0.00 |
October | 0.373443E+11 | -0.369037E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -440635652.9 | 60.05 | 0.00 | 0.00 |
November | 0.388853E+11 | -0.384580E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -427300694.6 | 60.05 | 0.00 | 0.00 |
December | 0.410303E+11 | -0.405868E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -443527784.7 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.478316E+12 | -0.473138E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.517751E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.346319E+11 | -0.467627E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -445598787.6 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.472083E+11 | -0.342090E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -402207774.2 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.51 | 0.48 | 01-JAN-08:50 | 6268.52 | 37.11 | 219.83 | 232.50 | 5241.31 | 37.97 | 224.67 | 214.67 |
February | 275.00 | 0.50 | 0.48 | 01-FEB-08:20 | 8484.48 | 37.44 | 268.67 | 259.67 | 3613.70 | 31.80 | 235.50 | 245.67 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:49 | 9903.93 | 33.46 | 272.17 | 324.17 | 2044.76 | 23.50 | 257.00 | 297.50 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:50 | 2514.15 | 21.09 | 160.00 | 351.50 | 1434.51 | 22.54 | 240.17 | 318.17 |
May | 385.83 | 0.51 | 0.48 | 01-MAY-06:30 | 2226.70 | 20.83 | 163.33 | 399.83 | 1248.17 | 22.26 | 279.83 | 360.17 |
June | 434.17 | 0.52 | 0.48 | 01-JUN-13:39 | 1912.30 | 20.30 | 173.83 | 414.00 | 1108.82 | 21.75 | 288.33 | 368.17 |
July | 417.33 | 0.50 | 0.48 | 01-JUL-06:40 | 2057.24 | 20.69 | 139.67 | 406.83 | 1227.05 | 22.16 | 277.17 | 373.33 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-06:40 | 2193.88 | 20.22 | 156.00 | 386.33 | 1309.39 | 21.66 | 246.33 | 351.17 |
September | 352.17 | 0.52 | 0.48 | 01-SEP-06:00 | 3085.65 | 21.63 | 150.00 | 328.00 | 1532.49 | 21.86 | 218.50 | 300.50 |
October | 317.67 | 0.50 | 0.48 | 01-OCT-08:39 | 8591.47 | 35.15 | 289.33 | 302.00 | 2349.71 | 24.42 | 214.50 | 282.33 |
November | 269.50 | 0.50 | 0.48 | 01-NOV-07:00 | 6399.52 | 37.45 | 262.67 | 250.67 | 5632.23 | 38.62 | 264.17 | 241.17 |
December | 236.83 | 0.51 | 0.48 | 01-DEC-08:50 | 4980.48 | 37.80 | 237.83 | 232.33 | 4337.08 | 38.97 | 241.17 | 219.67 |
Annual Sum or Average | 3965.83 | 0.51 | 4482.25 | 27.13 | 2493.33 | 3887.83 | 2301.83 | 26.06 | 2987.33 | 3572.50 | ||
Minimum of Months | 226.83 | 0.50 | 0.48 | 1912.30 | 20.22 | 139.67 | 232.33 | 1108.82 | 21.66 | 214.50 | 214.67 | |
Maximum of Months | 434.17 | 0.52 | 0.48 | 9903.93 | 37.80 | 289.33 | 414.00 | 5632.23 | 38.97 | 288.33 | 373.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.53 | 0.48 | 01-JAN-08:50 | 1982.29 | 25.53 | 106.50 | 218.67 | 1123.30 | 25.20 | 138.17 | 186.50 |
February | 275.00 | 0.52 | 0.48 | 01-FEB-08:09 | 2220.78 | 24.62 | 120.67 | 248.67 | 1195.29 | 24.54 | 153.50 | 218.50 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:40 | 3488.50 | 25.83 | 153.83 | 321.00 | 1943.07 | 26.01 | 234.17 | 291.00 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:39 | 3477.13 | 24.48 | 112.33 | 358.33 | 1928.14 | 24.85 | 186.33 | 325.33 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-05:40 | 3821.68 | 24.61 | 139.17 | 410.17 | 1674.31 | 24.08 | 226.33 | 373.50 |
June | 434.17 | 0.51 | 0.48 | 01-JUN-13:39 | 4650.30 | 25.69 | 153.67 | 425.83 | 2016.91 | 25.02 | 271.83 | 394.00 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:40 | 5042.98 | 25.82 | 148.83 | 423.50 | 2158.28 | 24.93 | 220.67 | 397.17 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-05:30 | 4026.77 | 25.14 | 155.50 | 393.67 | 2311.46 | 25.41 | 219.17 | 363.33 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:19 | 3034.73 | 24.30 | 141.33 | 328.50 | 1679.31 | 24.60 | 190.33 | 300.67 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-08:20 | 2725.75 | 24.82 | 143.00 | 292.33 | 1547.48 | 24.99 | 181.17 | 258.50 |
November | 269.50 | 0.53 | 0.48 | 01-NOV-07:49 | 1765.97 | 24.54 | 118.33 | 234.83 | 971.20 | 24.42 | 146.00 | 204.00 |
December | 236.83 | 0.54 | 0.48 | 01-DEC-08:50 | 1542.15 | 25.46 | 109.67 | 211.83 | 910.02 | 25.23 | 133.00 | 173.83 |
Annual Sum or Average | 3965.83 | 0.51 | 3359.20 | 25.08 | 1602.83 | 3867.33 | 1703.98 | 24.93 | 2300.67 | 3486.33 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1542.15 | 24.30 | 106.50 | 211.83 | 910.02 | 24.08 | 133.00 | 173.83 | |
Maximum of Months | 434.17 | 0.54 | 0.48 | 5042.98 | 25.83 | 155.50 | 425.83 | 2311.46 | 26.01 | 271.83 | 397.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.57 | 0.48 | 01-JAN-10:30 | 656.31 | 16.83 | 0.00 | 196.67 | 385.79 | 18.47 | 7.50 | 134.00 |
February | 275.00 | 0.54 | 0.48 | 01-FEB-10:50 | 721.92 | 17.82 | 0.00 | 234.83 | 442.01 | 19.47 | 18.00 | 182.00 |
March | 304.00 | 0.51 | 0.48 | 01-MAR-08:09 | 1133.25 | 19.67 | 1.50 | 314.00 | 663.64 | 21.15 | 156.67 | 273.83 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:00 | 1182.72 | 20.27 | 20.83 | 353.83 | 703.37 | 21.65 | 183.17 | 315.67 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-06:10 | 1458.10 | 22.11 | 109.33 | 413.17 | 851.19 | 23.32 | 289.00 | 380.83 |
June | 434.17 | 0.49 | 0.48 | 01-JUN-13:39 | 1526.02 | 24.16 | 201.33 | 441.83 | 854.81 | 23.41 | 345.67 | 416.50 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:40 | 1490.02 | 23.12 | 147.50 | 427.33 | 857.59 | 22.40 | 290.50 | 401.00 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-05:49 | 1158.53 | 19.90 | 42.50 | 400.33 | 733.74 | 21.30 | 223.00 | 380.33 |
September | 352.17 | 0.52 | 0.48 | 01-SEP-06:00 | 948.22 | 18.96 | 1.17 | 325.33 | 586.24 | 20.43 | 114.67 | 282.67 |
October | 317.67 | 0.53 | 0.48 | 01-OCT-09:09 | 780.81 | 18.14 | 0.00 | 277.83 | 473.70 | 19.72 | 49.67 | 221.83 |
November | 269.50 | 0.56 | 0.48 | 01-NOV-08:00 | 617.01 | 16.97 | 0.00 | 214.67 | 368.96 | 18.63 | 2.67 | 150.83 |
December | 236.83 | 0.58 | 0.48 | 01-DEC-09:50 | 536.17 | 16.35 | 0.00 | 190.17 | 318.49 | 18.06 | 0.17 | 103.50 |
Annual Sum or Average | 3965.83 | 0.52 | 1080.94 | 19.98 | 524.17 | 3790.00 | 639.95 | 20.99 | 1680.67 | 3243.00 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 536.17 | 16.35 | 0.00 | 190.17 | 318.49 | 18.06 | 0.17 | 103.50 | |
Maximum of Months | 434.17 | 0.58 | 0.48 | 1526.02 | 24.16 | 201.33 | 441.83 | 857.59 | 23.41 | 345.67 | 416.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.54 | 0.48 | 01-JAN-10:20 | 1845.49 | 24.30 | 99.33 | 212.67 | 1069.69 | 24.24 | 135.50 | 176.50 |
February | 275.00 | 0.52 | 0.48 | 01-FEB-10:50 | 2381.76 | 25.30 | 125.83 | 246.17 | 1291.42 | 25.16 | 154.17 | 219.00 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-08:20 | 3275.84 | 25.59 | 152.33 | 319.50 | 1793.51 | 25.87 | 232.17 | 289.17 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:00 | 3388.31 | 23.41 | 111.50 | 351.33 | 1891.65 | 23.94 | 191.00 | 317.83 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-06:49 | 3861.55 | 22.57 | 102.83 | 405.17 | 2261.87 | 23.39 | 222.17 | 372.17 |
June | 434.17 | 0.51 | 0.48 | 01-JUN-13:39 | 3955.85 | 21.00 | 69.33 | 427.67 | 1784.18 | 21.37 | 235.33 | 395.00 |
July | 417.33 | 0.50 | 0.48 | 01-JUL-06:00 | 4586.26 | 22.64 | 94.83 | 412.67 | 2071.17 | 21.66 | 195.83 | 385.17 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-06:49 | 3564.68 | 22.47 | 118.17 | 392.33 | 1965.18 | 23.05 | 196.50 | 363.50 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-07:10 | 3552.16 | 25.12 | 145.83 | 330.00 | 1484.89 | 24.15 | 189.83 | 301.17 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-09:20 | 2388.06 | 24.65 | 141.00 | 290.50 | 1314.10 | 24.76 | 184.67 | 257.67 |
November | 269.50 | 0.53 | 0.48 | 01-NOV-08:00 | 2056.71 | 25.35 | 120.83 | 233.33 | 1161.83 | 25.19 | 149.00 | 201.67 |
December | 236.83 | 0.54 | 0.48 | 01-DEC-09:50 | 1449.87 | 24.72 | 106.67 | 213.17 | 809.46 | 24.47 | 128.50 | 177.00 |
Annual Sum or Average | 3965.83 | 0.51 | 3202.80 | 23.69 | 1388.50 | 3834.50 | 1649.84 | 23.72 | 2214.67 | 3455.83 | ||
Minimum of Months | 226.83 | 0.50 | 0.48 | 1449.87 | 21.00 | 69.33 | 212.67 | 809.46 | 21.37 | 128.50 | 176.50 | |
Maximum of Months | 434.17 | 0.54 | 0.48 | 4586.26 | 25.59 | 152.33 | 427.67 | 2261.87 | 25.87 | 235.33 | 395.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.51 | 0.48 | 01-JAN-08:50 | 6316.76 | 36.63 | 216.33 | 232.67 | 5372.66 | 37.50 | 215.33 | 216.00 |
February | 275.00 | 0.50 | 0.48 | 01-FEB-08:20 | 8551.12 | 36.96 | 266.33 | 259.83 | 3787.62 | 30.09 | 179.83 | 248.17 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:49 | 9963.92 | 32.27 | 254.17 | 324.17 | 2182.62 | 18.77 | 14.00 | 299.83 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:50 | 2562.85 | 14.74 | 0.00 | 351.67 | 1537.64 | 18.26 | 8.83 | 321.67 |
May | 385.83 | 0.51 | 0.48 | 01-MAY-06:30 | 2263.57 | 14.70 | 0.00 | 399.83 | 1334.01 | 18.16 | 1.67 | 364.33 |
June | 434.17 | 0.52 | 0.48 | 01-JUN-13:39 | 1948.85 | 14.32 | 0.00 | 415.00 | 1185.85 | 17.86 | 0.00 | 373.50 |
July | 417.33 | 0.50 | 0.48 | 01-JUL-06:40 | 2102.54 | 14.69 | 0.00 | 407.00 | 1315.46 | 18.26 | 1.17 | 377.67 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-06:40 | 2248.43 | 13.95 | 0.00 | 386.67 | 1407.18 | 17.50 | 2.67 | 355.33 |
September | 352.17 | 0.52 | 0.48 | 01-SEP-06:00 | 3150.88 | 15.53 | 29.50 | 328.17 | 1665.48 | 17.59 | 14.33 | 303.67 |
October | 317.67 | 0.50 | 0.48 | 01-OCT-08:30 | 8650.58 | 34.24 | 283.00 | 302.00 | 2585.30 | 22.00 | 80.83 | 287.33 |
November | 269.50 | 0.50 | 0.48 | 01-NOV-07:00 | 6453.29 | 36.99 | 262.00 | 251.00 | 5755.27 | 38.26 | 263.00 | 242.50 |
December | 236.83 | 0.51 | 0.48 | 01-DEC-08:50 | 5018.36 | 37.38 | 231.33 | 232.50 | 4450.62 | 38.64 | 232.17 | 221.33 |
Annual Sum or Average | 3965.83 | 0.51 | 4532.81 | 23.23 | 1542.67 | 3890.50 | 2422.73 | 22.90 | 1013.83 | 3611.33 | ||
Minimum of Months | 226.83 | 0.50 | 0.48 | 1948.85 | 13.95 | 0.00 | 232.50 | 1185.85 | 17.50 | 0.00 | 216.00 | |
Maximum of Months | 434.17 | 0.52 | 0.48 | 9963.92 | 37.38 | 283.00 | 415.00 | 5755.27 | 38.64 | 263.00 | 377.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.53 | 0.48 | 01-JAN-08:50 | 2014.10 | 23.38 | 89.67 | 219.67 | 1167.64 | 23.58 | 76.67 | 189.67 |
February | 275.00 | 0.52 | 0.48 | 01-FEB-08:09 | 2216.52 | 20.72 | 75.00 | 248.67 | 1252.84 | 22.61 | 76.00 | 222.00 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:40 | 3520.40 | 22.27 | 94.67 | 321.17 | 2021.98 | 24.01 | 92.67 | 293.83 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:39 | 3541.86 | 21.39 | 85.33 | 359.17 | 2011.14 | 22.44 | 60.17 | 328.83 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-05:40 | 3884.51 | 21.66 | 113.00 | 410.83 | 1758.21 | 21.48 | 57.83 | 377.17 |
June | 434.17 | 0.51 | 0.48 | 01-JUN-13:39 | 4697.80 | 22.02 | 134.17 | 426.33 | 2112.82 | 22.53 | 89.50 | 397.33 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:40 | 5117.95 | 22.90 | 134.00 | 424.00 | 2264.13 | 22.31 | 75.50 | 399.00 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-05:30 | 4097.85 | 22.24 | 131.33 | 394.33 | 2403.42 | 23.13 | 101.17 | 367.50 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:19 | 3093.98 | 21.44 | 104.17 | 328.83 | 1752.31 | 22.36 | 78.33 | 303.50 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-08:20 | 2771.23 | 22.32 | 110.50 | 292.83 | 1604.65 | 23.09 | 101.50 | 262.00 |
November | 269.50 | 0.53 | 0.48 | 01-NOV-07:49 | 1797.46 | 22.24 | 95.17 | 235.33 | 1014.20 | 22.70 | 82.00 | 208.50 |
December | 236.83 | 0.54 | 0.48 | 01-DEC-08:50 | 1565.37 | 23.46 | 101.83 | 213.00 | 943.72 | 23.80 | 89.67 | 178.67 |
Annual Sum or Average | 3965.83 | 0.51 | 3407.66 | 22.13 | 1268.83 | 3874.17 | 1778.93 | 22.76 | 981.00 | 3528.00 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1565.37 | 20.72 | 75.00 | 213.00 | 943.72 | 21.48 | 57.83 | 178.67 | |
Maximum of Months | 434.17 | 0.54 | 0.48 | 5117.95 | 23.46 | 134.17 | 426.33 | 2403.42 | 24.01 | 101.50 | 399.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.56 | 0.48 | 01-JAN-10:20 | 664.14 | 10.99 | 0.00 | 197.17 | 409.77 | 14.55 | 0.00 | 143.17 |
February | 275.00 | 0.54 | 0.48 | 01-FEB-10:30 | 732.51 | 12.05 | 0.00 | 235.17 | 470.23 | 15.69 | 0.00 | 189.67 |
March | 304.00 | 0.51 | 0.48 | 01-MAR-08:09 | 1150.69 | 14.08 | 0.00 | 314.50 | 705.90 | 17.54 | 0.00 | 279.17 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:50 | 1203.56 | 14.86 | 0.00 | 354.50 | 749.30 | 18.34 | 4.00 | 321.67 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-05:00 | 1484.41 | 16.97 | 38.50 | 413.33 | 905.52 | 20.18 | 46.83 | 384.33 |
June | 434.17 | 0.49 | 0.48 | 01-JUN-13:39 | 1556.24 | 19.85 | 107.67 | 442.50 | 912.32 | 20.13 | 44.00 | 419.33 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:40 | 1521.68 | 18.42 | 72.17 | 427.33 | 916.56 | 18.99 | 22.00 | 403.67 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-05:49 | 1182.13 | 14.42 | 0.00 | 400.67 | 780.92 | 17.99 | 5.83 | 381.83 |
September | 352.17 | 0.52 | 0.48 | 01-SEP-06:00 | 965.37 | 13.54 | 0.00 | 326.33 | 624.75 | 17.02 | 0.00 | 288.67 |
October | 317.67 | 0.53 | 0.48 | 01-OCT-08:00 | 792.49 | 12.49 | 0.00 | 278.33 | 504.04 | 16.07 | 0.00 | 230.00 |
November | 269.50 | 0.56 | 0.48 | 01-NOV-08:50 | 624.96 | 11.07 | 0.00 | 215.50 | 392.11 | 14.73 | 0.00 | 162.17 |
December | 236.83 | 0.58 | 0.48 | 01-DEC-09:50 | 541.36 | 10.27 | 0.00 | 190.83 | 338.01 | 13.97 | 0.00 | 121.00 |
Annual Sum or Average | 3965.83 | 0.52 | 1100.18 | 14.62 | 218.33 | 3796.17 | 681.67 | 17.48 | 122.67 | 3324.67 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 541.36 | 10.27 | 0.00 | 190.83 | 338.01 | 13.97 | 0.00 | 121.00 | |
Maximum of Months | 434.17 | 0.58 | 0.48 | 1556.24 | 19.85 | 107.67 | 442.50 | 916.56 | 20.18 | 46.83 | 419.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.54 | 0.48 | 01-JAN-10:09 | 1874.81 | 22.19 | 85.33 | 213.33 | 1110.77 | 22.66 | 72.33 | 180.00 |
February | 275.00 | 0.52 | 0.48 | 01-FEB-10:30 | 2423.57 | 22.85 | 95.17 | 247.33 | 1346.94 | 23.32 | 88.17 | 222.67 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-08:20 | 3307.46 | 21.99 | 92.50 | 319.50 | 1866.31 | 23.87 | 92.00 | 292.67 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:00 | 3451.55 | 20.09 | 75.83 | 351.33 | 1975.73 | 21.31 | 48.00 | 320.33 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-06:40 | 3921.55 | 18.98 | 75.00 | 405.67 | 2351.51 | 20.53 | 46.00 | 375.50 |
June | 434.17 | 0.50 | 0.48 | 01-JUN-13:39 | 4011.29 | 17.03 | 52.00 | 428.17 | 1871.02 | 18.04 | 0.00 | 399.33 |
July | 417.33 | 0.50 | 0.48 | 01-JUL-06:00 | 4652.50 | 19.08 | 79.67 | 413.00 | 2171.29 | 18.36 | 3.67 | 388.50 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-06:49 | 3628.80 | 19.06 | 91.00 | 392.67 | 2048.42 | 20.32 | 58.00 | 365.67 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-07:10 | 3611.41 | 22.47 | 116.83 | 331.17 | 1558.17 | 21.82 | 67.50 | 303.50 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-09:09 | 2434.21 | 22.01 | 100.67 | 291.50 | 1372.36 | 22.76 | 91.00 | 262.33 |
November | 269.50 | 0.53 | 0.48 | 01-NOV-08:00 | 2087.75 | 22.89 | 102.83 | 233.17 | 1205.95 | 23.52 | 95.50 | 206.00 |
December | 236.83 | 0.54 | 0.48 | 01-DEC-09:39 | 1434.08 | 20.93 | 79.33 | 214.00 | 844.09 | 22.95 | 86.83 | 182.50 |
Annual Sum or Average | 3965.83 | 0.51 | 3250.80 | 20.49 | 1046.17 | 3840.83 | 1722.37 | 21.28 | 749.00 | 3499.00 | ||
Minimum of Months | 226.83 | 0.50 | 0.48 | 1434.08 | 17.03 | 52.00 | 213.33 | 844.09 | 18.04 | 0.00 | 180.00 | |
Maximum of Months | 434.17 | 0.54 | 0.48 | 4652.50 | 22.89 | 116.83 | 428.17 | 2351.51 | 23.87 | 95.50 | 399.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.51 | 0.48 | 01-JAN-08:50 | 6317.94 | 36.62 | 216.33 | 232.67 | 5374.73 | 37.49 | 215.33 | 216.00 |
February | 275.00 | 0.50 | 0.48 | 01-FEB-08:20 | 8552.79 | 36.96 | 266.33 | 259.83 | 3790.09 | 30.09 | 179.83 | 248.17 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:49 | 9967.73 | 32.26 | 254.17 | 324.17 | 2185.79 | 18.75 | 13.83 | 300.00 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:50 | 2566.38 | 14.71 | 0.00 | 351.67 | 1539.90 | 18.25 | 8.50 | 321.83 |
May | 385.83 | 0.51 | 0.48 | 01-MAY-06:30 | 2266.84 | 14.67 | 0.00 | 399.83 | 1336.01 | 18.15 | 1.67 | 364.33 |
June | 434.17 | 0.52 | 0.48 | 01-JUN-13:39 | 1951.39 | 14.29 | 0.00 | 415.00 | 1187.47 | 17.84 | 0.00 | 373.50 |
July | 417.33 | 0.50 | 0.48 | 01-JUL-06:40 | 2105.11 | 14.66 | 0.00 | 407.00 | 1317.13 | 18.24 | 1.17 | 377.83 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-06:40 | 2251.24 | 13.92 | 0.00 | 386.67 | 1409.00 | 17.48 | 2.67 | 355.50 |
September | 352.17 | 0.52 | 0.48 | 01-SEP-06:00 | 3153.91 | 15.50 | 29.50 | 328.33 | 1667.66 | 17.57 | 14.17 | 303.67 |
October | 317.67 | 0.50 | 0.48 | 01-OCT-08:30 | 8652.57 | 34.23 | 283.00 | 302.00 | 2587.72 | 21.99 | 80.67 | 287.33 |
November | 269.50 | 0.50 | 0.48 | 01-NOV-07:00 | 6454.34 | 36.98 | 262.00 | 251.00 | 5757.37 | 38.26 | 263.00 | 242.50 |
December | 236.83 | 0.51 | 0.48 | 01-DEC-08:50 | 5019.03 | 37.37 | 231.33 | 232.50 | 4452.28 | 38.64 | 232.17 | 221.33 |
Annual Sum or Average | 3965.83 | 0.51 | 4535.29 | 23.21 | 1542.67 | 3890.67 | 2424.82 | 22.89 | 1013.00 | 3612.00 | ||
Minimum of Months | 226.83 | 0.50 | 0.48 | 1951.39 | 13.92 | 0.00 | 232.50 | 1187.47 | 17.48 | 0.00 | 216.00 | |
Maximum of Months | 434.17 | 0.52 | 0.48 | 9967.73 | 37.37 | 283.00 | 415.00 | 5757.37 | 38.64 | 263.00 | 377.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.53 | 0.48 | 01-JAN-08:50 | 2015.13 | 23.36 | 89.67 | 219.67 | 1168.68 | 23.57 | 76.67 | 189.67 |
February | 275.00 | 0.52 | 0.48 | 01-FEB-08:09 | 2217.52 | 20.69 | 75.00 | 248.83 | 1253.99 | 22.59 | 75.83 | 222.00 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-07:40 | 3522.52 | 22.24 | 94.50 | 321.33 | 2023.85 | 24.00 | 92.00 | 294.00 |
April | 325.17 | 0.49 | 0.48 | 01-APR-08:39 | 3543.73 | 21.36 | 85.33 | 359.17 | 2012.86 | 22.42 | 60.17 | 328.83 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-05:40 | 3886.78 | 21.63 | 113.00 | 411.00 | 1760.04 | 21.46 | 57.83 | 377.33 |
June | 434.17 | 0.51 | 0.48 | 01-JUN-13:39 | 4699.75 | 21.99 | 134.17 | 426.33 | 2114.65 | 22.52 | 89.50 | 397.33 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:40 | 5119.60 | 22.87 | 134.00 | 424.00 | 2265.82 | 22.29 | 75.50 | 399.00 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-05:30 | 4099.47 | 22.22 | 131.33 | 394.33 | 2405.03 | 23.11 | 101.00 | 367.67 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-06:19 | 3095.43 | 21.41 | 104.17 | 328.83 | 1753.78 | 22.34 | 78.33 | 303.50 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-08:20 | 2757.10 | 21.93 | 107.00 | 292.67 | 1605.88 | 23.08 | 101.17 | 262.00 |
November | 269.50 | 0.53 | 0.48 | 01-NOV-07:49 | 1747.31 | 20.68 | 83.00 | 234.83 | 1015.16 | 22.69 | 82.00 | 208.50 |
December | 236.83 | 0.54 | 0.48 | 01-DEC-08:50 | 1566.11 | 23.44 | 101.83 | 213.00 | 944.55 | 23.79 | 89.33 | 178.67 |
Annual Sum or Average | 3965.83 | 0.51 | 3404.52 | 21.97 | 1253.00 | 3874.00 | 1780.42 | 22.74 | 979.33 | 3528.50 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 1566.11 | 20.68 | 75.00 | 213.00 | 944.55 | 21.46 | 57.83 | 178.67 | |
Maximum of Months | 434.17 | 0.54 | 0.48 | 5119.60 | 23.44 | 134.17 | 426.33 | 2405.03 | 24.00 | 101.17 | 399.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.56 | 0.48 | 01-JAN-10:20 | 664.79 | 10.96 | 0.00 | 197.33 | 410.34 | 14.54 | 0.00 | 143.83 |
February | 275.00 | 0.54 | 0.48 | 01-FEB-10:30 | 733.10 | 12.02 | 0.00 | 235.17 | 470.82 | 15.67 | 0.00 | 189.83 |
March | 304.00 | 0.51 | 0.48 | 01-MAR-08:09 | 1151.92 | 14.05 | 0.00 | 314.50 | 706.89 | 17.52 | 0.00 | 279.17 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:50 | 1204.79 | 14.83 | 0.00 | 354.50 | 750.31 | 18.32 | 3.83 | 322.17 |
May | 385.83 | 0.49 | 0.48 | 01-MAY-05:00 | 1485.90 | 16.94 | 38.50 | 413.33 | 906.71 | 20.16 | 46.67 | 384.83 |
June | 434.17 | 0.49 | 0.48 | 01-JUN-13:39 | 1557.45 | 19.82 | 107.50 | 442.50 | 913.44 | 20.11 | 43.33 | 419.50 |
July | 417.33 | 0.49 | 0.48 | 01-JUL-06:40 | 1522.76 | 18.39 | 72.17 | 427.33 | 917.61 | 18.98 | 21.33 | 403.83 |
August | 421.33 | 0.50 | 0.48 | 01-AUG-05:49 | 1183.08 | 14.39 | 0.00 | 400.67 | 781.81 | 17.97 | 5.67 | 381.83 |
September | 352.17 | 0.52 | 0.48 | 01-SEP-06:00 | 966.17 | 13.51 | 0.00 | 326.33 | 625.50 | 17.01 | 0.00 | 288.67 |
October | 317.67 | 0.53 | 0.48 | 01-OCT-08:00 | 793.19 | 12.46 | 0.00 | 278.50 | 504.69 | 16.06 | 0.00 | 230.00 |
November | 269.50 | 0.56 | 0.48 | 01-NOV-08:50 | 625.52 | 11.04 | 0.00 | 215.50 | 392.64 | 14.72 | 0.00 | 162.33 |
December | 236.83 | 0.58 | 0.48 | 01-DEC-09:50 | 541.82 | 10.24 | 0.00 | 191.17 | 338.48 | 13.95 | 0.00 | 121.17 |
Annual Sum or Average | 3965.83 | 0.52 | 1101.14 | 14.59 | 218.17 | 3796.83 | 682.53 | 17.46 | 120.83 | 3327.17 | ||
Minimum of Months | 226.83 | 0.49 | 0.48 | 541.82 | 10.24 | 0.00 | 191.17 | 338.48 | 13.95 | 0.00 | 121.17 | |
Maximum of Months | 434.17 | 0.58 | 0.48 | 1557.45 | 19.82 | 107.50 | 442.50 | 917.61 | 20.16 | 46.67 | 419.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 226.83 | 0.54 | 0.48 | 01-JAN-10:09 | 1875.86 | 22.17 | 85.33 | 213.33 | 1111.81 | 22.65 | 72.17 | 180.00 |
February | 275.00 | 0.52 | 0.48 | 01-FEB-10:30 | 2424.60 | 22.83 | 95.17 | 247.33 | 1348.08 | 23.31 | 87.67 | 222.67 |
March | 304.00 | 0.50 | 0.48 | 01-MAR-08:20 | 3309.65 | 21.97 | 92.50 | 319.50 | 1868.19 | 23.86 | 90.67 | 292.83 |
April | 325.17 | 0.50 | 0.48 | 01-APR-08:00 | 3453.56 | 20.06 | 75.83 | 351.33 | 1977.65 | 21.29 | 48.00 | 320.33 |
May | 385.83 | 0.50 | 0.48 | 01-MAY-06:40 | 3923.82 | 18.95 | 75.00 | 405.67 | 2353.53 | 20.52 | 46.00 | 375.50 |
June | 434.17 | 0.50 | 0.48 | 01-JUN-13:39 | 4013.35 | 17.00 | 52.00 | 428.33 | 1872.86 | 18.02 | 0.00 | 399.50 |
July | 417.33 | 0.50 | 0.48 | 01-JUL-06:00 | 4654.34 | 19.04 | 79.67 | 413.00 | 2173.10 | 18.34 | 3.67 | 388.50 |
August | 421.33 | 0.51 | 0.48 | 01-AUG-06:49 | 3630.51 | 19.03 | 91.00 | 392.67 | 2050.06 | 20.30 | 58.00 | 365.67 |
September | 352.17 | 0.51 | 0.48 | 01-SEP-07:10 | 3612.83 | 22.45 | 116.83 | 331.17 | 1559.63 | 21.81 | 67.33 | 304.00 |
October | 317.67 | 0.52 | 0.48 | 01-OCT-09:09 | 2435.34 | 21.99 | 100.67 | 291.50 | 1373.59 | 22.75 | 90.33 | 262.33 |
November | 269.50 | 0.53 | 0.48 | 01-NOV-08:00 | 2088.64 | 22.86 | 102.83 | 233.17 | 1206.95 | 23.51 | 95.17 | 206.17 |
December | 236.83 | 0.54 | 0.48 | 01-DEC-09:39 | 1434.81 | 20.90 | 79.17 | 214.00 | 844.92 | 22.94 | 86.83 | 182.50 |
Annual Sum or Average | 3965.83 | 0.51 | 3252.41 | 20.47 | 1046.00 | 3841.00 | 1723.91 | 21.27 | 745.83 | 3500.00 | ||
Minimum of Months | 226.83 | 0.50 | 0.48 | 1434.81 | 17.00 | 52.00 | 213.33 | 844.92 | 18.02 | 0.00 | 180.00 | |
Maximum of Months | 434.17 | 0.54 | 0.48 | 4654.34 | 22.86 | 116.83 | 428.33 | 2353.53 | 23.86 | 95.17 | 399.50 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.329076E+11 | 75421.81 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.167338E+11 | 58095.63 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.744178E+10 | 49013.09 | 04-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.955326E+09 | 23276.02 | 29-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.615936E+09 | 16538.68 | 08-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7248846.77 | 2723.71 | 16-JUN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 77304889.52 | 6159.51 | 19-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.746161E+09 | 18551.79 | 10-OCT-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.493652E+10 | 36896.55 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.181026E+11 | 63710.81 | 29-DEC-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.825243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.329076E+11 | 75421.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.265487E+10 | 15920.51 | 18-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.799384E+09 | 15974.84 | 24-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166195E+09 | 14697.63 | 06-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 76601730.77 | 15835.89 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.654093E+09 | 15937.92 | 23-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.435115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.265487E+10 | 15974.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.237708E+10 | 17126.48 | 20-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.955067E+09 | 17184.06 | 24-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.312876E+09 | 16708.51 | 06-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 20567913.73 | 9929.40 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12622075.00 | 2162.36 | 08-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 97990.99 | 85.53 | 20-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 20022804.69 | 2498.65 | 10-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.277376E+09 | 17131.61 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.115657E+10 | 17178.20 | 23-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.513229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.237708E+10 | 17184.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.292210E+10 | 24411.02 | 21-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.949903E+09 | 24480.72 | 23-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.365329E+09 | 23760.05 | 06-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 36320342.22 | 20850.97 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 61721074.90 | 24502.49 | 08-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1002750.64 | 901.80 | 19-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 30505084.59 | 15562.38 | 10-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.311770E+09 | 24472.80 | 29-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110824E+10 | 24459.12 | 18-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.578689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.292210E+10 | 24502.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.173616E+10 | 15790.68 | 09-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.323569E+09 | 15762.51 | 09-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 40789132.16 | 15759.72 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 287337.94 | 193.71 | 08-MAY-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 12157156.21 | 9491.31 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122162E+09 | 11628.49 | 29-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.223512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.173616E+10 | 15790.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.393793E+12 | 813156.71 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.216681E+12 | 633583.20 | 01-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.125578E+12 | 542144.93 | 06-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.297709E+11 | 259403.50 | 29-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.167487E+11 | 193333.11 | 08-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.296719E+09 | 76566.36 | 16-JUN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.302065E+10 | 92070.14 | 19-SEP-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.211351E+11 | 257588.28 | 10-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.929573E+11 | 426630.56 | 27-NOV-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.254243E+12 | 694097.94 | 29-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115422E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.393793E+12 | 813156.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.105640E+11 | 582667.59 | 30-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.277022E+10 | 583098.21 | 06-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.103886E+10 | 578782.04 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.411103E+09 | 578787.99 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159841E+10 | 581711.08 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.105640E+11 | 583098.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.904413E+11 | 139053.53 | 11-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.439850E+11 | 139900.85 | 07-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.201875E+11 | 139825.50 | 30-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.321921E+10 | 138072.96 | 03-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.185198E+10 | 149669.40 | 22-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.478054E+09 | 114556.88 | 19-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.306529E+10 | 150262.46 | 04-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.201109E+11 | 148791.74 | 06-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.543010E+11 | 139954.90 | 26-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.237640E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.904413E+11 | 150262.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.650116E+11 | 203908.49 | 30-JAN-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.321780E+11 | 203662.76 | 11-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170611E+11 | 203235.17 | 06-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.416043E+10 | 203033.21 | 29-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.236797E+10 | 203107.05 | 09-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 64723682.65 | 17898.29 | 17-JUN-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 14694433.47 | 20539.20 | 18-AUG-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.935667E+09 | 81736.97 | 19-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.411252E+10 | 203035.20 | 10-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.187947E+11 | 208460.78 | 06-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.434875E+11 | 203499.64 | 26-DEC-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.188189E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.650116E+11 | 208460.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.617125E+11 | 257389.19 | 30-JAN-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.253226E+11 | 257160.83 | 06-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148383E+11 | 256541.64 | 06-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.404831E+10 | 254495.45 | 29-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.308738E+10 | 255057.32 | 09-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 84707346.58 | 26858.47 | 17-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 18373724.96 | 13549.49 | 18-AUG-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.554765E+09 | 79092.58 | 19-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.211742E+10 | 255428.27 | 10-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136476E+11 | 257137.95 | 29-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.355985E+11 | 255999.15 | 26-DEC-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161030E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.617125E+11 | 257389.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.613382E+11 | 207811.74 | 31-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.283445E+11 | 207258.69 | 06-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.154359E+11 | 207203.67 | 06-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.328212E+10 | 196188.93 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.210440E+10 | 206898.19 | 08-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 81124276.12 | 26679.03 | 17-JUN-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 41932832.32 | 17196.95 | 18-AUG-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.825565E+09 | 66225.70 | 19-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.342738E+10 | 178016.06 | 10-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.155291E+11 | 207255.32 | 27-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.378006E+11 | 207286.41 | 18-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168211E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.613382E+11 | 207811.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.451842E+11 | 87143.86 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.249679E+11 | 70155.69 | 01-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161766E+11 | 61404.87 | 04-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.521107E+10 | 32429.46 | 29-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.300422E+10 | 24983.20 | 08-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.173338E+09 | 10721.43 | 16-JUN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 1543878.02 | 1535.95 | 18-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.934437E+09 | 14505.90 | 19-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.386716E+10 | 31575.63 | 10-OCT-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.122070E+11 | 46608.62 | 27-NOV-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.306638E+11 | 76769.15 | 29-DEC-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.142391E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.451842E+11 | 87143.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.147650E+11 | 80136.19 | 02-JAN-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.607346E+10 | 79941.87 | 13-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.330809E+10 | 80086.65 | 13-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.352018E+09 | 79131.26 | 10-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.715530E+09 | 80102.38 | 08-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5475553.40 | 1906.95 | 19-SEP-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.493817E+09 | 80083.01 | 10-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.378193E+10 | 79870.17 | 20-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.926249E+10 | 79879.22 | 04-DEC-05:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.387578E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.147650E+11 | 80136.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.155054E+11 | 15744.61 | 12-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.827846E+10 | 15754.30 | 13-FEB-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.529297E+10 | 15751.38 | 10-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.157932E+10 | 15654.31 | 29-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.992441E+09 | 15747.44 | 08-MAY-04:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 33256216.32 | 15628.25 | 17-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 15043217.09 | 15617.95 | 18-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.428476E+09 | 15693.69 | 19-SEP-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.167581E+10 | 15760.74 | 10-OCT-04:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.562289E+10 | 15755.13 | 06-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.115128E+11 | 15748.41 | 09-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.509369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.155054E+11 | 15760.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.103682E+11 | 22264.41 | 25-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.530725E+10 | 22362.45 | 13-FEB-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.356498E+10 | 22170.93 | 09-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.121658E+10 | 22153.73 | 22-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.755971E+09 | 22165.83 | 08-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 44178207.51 | 11890.20 | 17-JUN-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 120832.13 | 120.75 | 05-JUL-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 21272641.38 | 17488.23 | 18-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.389326E+09 | 22136.71 | 19-SEP-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.125102E+10 | 22147.35 | 06-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.395687E+10 | 22171.33 | 22-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.789139E+10 | 22270.90 | 19-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.347671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 120832.13 | 120.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.103682E+11 | 22362.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.113442E+11 | 27468.58 | 04-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.523827E+10 | 27462.28 | 04-FEB-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.407160E+10 | 27439.97 | 20-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164815E+10 | 27467.68 | 29-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.122736E+10 | 27449.00 | 08-MAY-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.116137E+09 | 17816.98 | 17-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 2236247.30 | 1582.82 | 08-JUL-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 37358990.29 | 24928.01 | 18-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.427918E+09 | 27249.46 | 19-SEP-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.117774E+10 | 27526.61 | 10-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.370869E+10 | 27548.66 | 29-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.796331E+10 | 27470.19 | 15-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.369629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2236247.30 | 1582.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.113442E+11 | 27548.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.991347E+10 | 24396.01 | 25-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.481763E+10 | 24399.91 | 11-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.340509E+10 | 24337.79 | 06-MAR-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.114895E+10 | 24316.96 | 01-APR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.747078E+09 | 24340.63 | 22-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 69076873.40 | 10531.32 | 17-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 31007585.44 | 12113.04 | 18-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.409092E+09 | 24162.79 | 19-SEP-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.123031E+10 | 24337.93 | 10-OCT-03:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.340667E+10 | 24355.76 | 20-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.675428E+10 | 24402.92 | 19-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.319327E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.991347E+10 | 24402.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.156455E+11 | 50771.13 | 10-JAN-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.661082E+10 | 36136.17 | 01-FEB-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.227487E+10 | 32037.32 | 04-MAR-17:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.177998E+09 | 14835.40 | 29-APR-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 30990785.06 | 10647.34 | 23-MAY-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1357044.58 | 4237.34 | 16-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 198.71 | 0.66 | 19-AUG-06:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3671610.89 | 6724.25 | 19-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14018241.71 | 8642.44 | 21-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.320000E+09 | 26314.46 | 27-NOV-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.541498E+10 | 37523.63 | 29-DEC-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.304942E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.156455E+11 | 50771.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.829644E+09 | 0.829644E+09 | 49035.44 | 27-FEB-15:30 | 49035.44 | 0.00 |
March | 0.00 | 0.00 | 96048767.10 | 96048767.10 | 16129.04 | 14-MAR-13:30 | 16129.04 | 0.00 |
April | 0.00 | 0.00 | 0.723999E+10 | 0.723999E+10 | 88869.05 | 06-APR-16:00 | 88869.05 | 0.00 |
May | 0.00 | 0.00 | 0.196788E+11 | 0.196788E+11 | 119387.31 | 19-MAY-15:20 | 119387.31 | 0.05 |
June | 0.00 | 0.00 | 0.656334E+11 | 0.652533E+11 | 158091.90 | 21-JUN-12:43 | 144312.09 | 0.22 |
July | 0.00 | 0.00 | 0.118398E+12 | 0.117563E+12 | 165591.25 | 19-JUL-09:30 | 135715.35 | 0.38 |
August | 0.00 | 0.00 | 0.101488E+12 | 0.101487E+12 | 162842.82 | 10-AUG-12:48 | 162842.82 | 0.20 |
September | 0.00 | 0.00 | 0.439599E+11 | 0.421459E+11 | 205965.45 | 07-SEP-15:10 | 113837.36 | 0.15 |
October | 0.00 | 0.00 | 0.115280E+11 | 0.115280E+11 | 111545.47 | 18-OCT-13:40 | 111545.47 | 0.00 |
November | 0.00 | 0.00 | 0.657276E+09 | 0.657276E+09 | 23712.77 | 03-NOV-13:55 | 23712.77 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.369509E+12 | 0.366479E+12 | 0.08 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.118398E+12 | 0.117563E+12 | 205965.45 | 162842.82 | 0.38 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 39167.31 | 39167.31 | 1.36 | 25-JAN-05:01 | 1.36 | 0.00 |
February | 0.00 | 0.00 | 0.697947E+10 | 0.697947E+10 | 370116.31 | 27-FEB-15:30 | 370116.31 | 0.00 |
March | 0.00 | 0.00 | 0.572049E+09 | 0.572049E+09 | 113681.55 | 14-MAR-13:30 | 113681.55 | 0.00 |
April | 0.00 | 0.00 | 0.526562E+11 | 0.526562E+11 | 721726.87 | 06-APR-16:00 | 721726.87 | 0.00 |
May | 0.00 | 0.00 | 0.169393E+12 | 0.169393E+12 | 1135370.82 | 19-MAY-15:30 | 1135370.82 | 0.04 |
June | 0.00 | 0.00 | 0.541920E+12 | 0.539102E+12 | 1470662.12 | 21-JUN-12:55 | 1326580.81 | 0.20 |
July | 0.00 | 0.00 | 0.900239E+12 | 0.896957E+12 | 1528604.40 | 25-JUL-16:42 | 1528604.40 | 0.33 |
August | 0.00 | 0.00 | 0.782169E+12 | 0.782162E+12 | 1500890.69 | 10-AUG-12:25 | 1500890.69 | 0.17 |
September | 0.00 | 0.00 | 0.367892E+12 | 0.353045E+12 | 1843900.44 | 07-SEP-14:45 | 974289.49 | 0.15 |
October | 0.00 | 0.00 | 0.912374E+11 | 0.912374E+11 | 944621.83 | 18-OCT-15:30 | 944621.83 | 0.00 |
November | 0.00 | 0.00 | 0.476004E+10 | 0.476004E+10 | 188549.79 | 03-NOV-13:55 | 188549.79 | 0.00 |
December | 0.00 | 0.00 | 67101.34 | 67101.34 | 1.96 | 26-DEC-06:01 | 1.96 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.291782E+13 | 0.289687E+13 | 0.07 | |||
Minimum of Months | 0.00 | 0.00 | 39167.31 | 39167.31 | 1.36 | 1.36 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.900239E+12 | 0.896957E+12 | 1843900.44 | 1528604.40 | 0.33 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 171.26 | 171.26 | 0.35 | 29-JAN-16:00 | 0.35 | 0.00 |
February | 0.00 | 0.00 | 0.456340E+09 | 0.456340E+09 | 31333.67 | 27-FEB-13:40 | 31333.67 | 0.00 |
March | 0.00 | 0.00 | 8668216.63 | 8668216.63 | 3519.53 | 14-MAR-13:30 | 3519.53 | 0.00 |
April | 0.00 | 0.00 | 0.487962E+10 | 0.487962E+10 | 72929.22 | 06-APR-16:00 | 72929.22 | 0.00 |
May | 0.00 | 0.00 | 0.174351E+11 | 0.174351E+11 | 142243.07 | 19-MAY-15:00 | 142243.07 | 0.04 |
June | 0.00 | 0.00 | 0.587930E+11 | 0.584634E+11 | 170130.31 | 21-JUN-12:43 | 155363.93 | 0.20 |
July | 0.00 | 0.00 | 0.984974E+11 | 0.981940E+11 | 178771.37 | 25-JUL-16:58 | 178771.37 | 0.32 |
August | 0.00 | 0.00 | 0.832925E+11 | 0.832925E+11 | 174534.18 | 10-AUG-12:43 | 174534.18 | 0.16 |
September | 0.00 | 0.00 | 0.373875E+11 | 0.358716E+11 | 215213.69 | 07-SEP-15:10 | 118808.08 | 0.13 |
October | 0.00 | 0.00 | 0.777640E+10 | 0.777640E+10 | 96691.40 | 18-OCT-15:10 | 96691.40 | 0.00 |
November | 0.00 | 0.00 | 0.352038E+09 | 0.352038E+09 | 11631.75 | 03-NOV-14:00 | 11631.75 | 0.00 |
December | 0.00 | 0.00 | 63966.67 | 63966.67 | 743.91 | 26-DEC-05:07 | 743.91 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.308879E+12 | 0.306730E+12 | 0.07 | |||
Minimum of Months | 0.00 | 0.00 | 171.26 | 171.26 | 0.35 | 0.35 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.984974E+11 | 0.981940E+11 | 215213.69 | 178771.37 | 0.32 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2426094.96 | 2426094.96 | 1645.76 | 13-JAN-15:00 | 1645.76 | 0.00 |
February | 0.00 | 0.00 | 0.612397E+09 | 0.612397E+09 | 31518.44 | 27-FEB-15:00 | 31518.44 | 0.00 |
March | 0.00 | 0.00 | 0.607438E+09 | 0.607438E+09 | 18326.93 | 14-MAR-14:00 | 18326.93 | 0.00 |
April | 0.00 | 0.00 | 0.512983E+10 | 0.512983E+10 | 48308.17 | 07-APR-14:00 | 48308.17 | 0.00 |
May | 0.00 | 0.00 | 0.138276E+11 | 0.137866E+11 | 58504.63 | 19-MAY-15:00 | 58504.63 | 0.04 |
June | 0.00 | 0.00 | 0.329090E+11 | 0.326215E+11 | 91364.00 | 20-JUN-13:13 | 79264.74 | 0.11 |
July | 0.00 | 0.00 | 0.362294E+11 | 0.361969E+11 | 91647.30 | 31-JUL-15:45 | 91647.30 | 0.13 |
August | 0.00 | 0.00 | 0.435176E+11 | 0.435137E+11 | 88405.11 | 12-AUG-14:00 | 88405.11 | 0.12 |
September | 0.00 | 0.00 | 0.236166E+11 | 0.223046E+11 | 113858.90 | 07-SEP-14:35 | 58761.29 | 0.11 |
October | 0.00 | 0.00 | 0.813891E+10 | 0.813891E+10 | 67498.39 | 18-OCT-13:45 | 67498.39 | 0.00 |
November | 0.00 | 0.00 | 0.270991E+09 | 0.270991E+09 | 27727.14 | 17-NOV-07:11 | 27727.14 | 0.00 |
December | 0.00 | 0.00 | 66662951.59 | 66662951.59 | 10964.81 | 19-DEC-15:00 | 10964.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.164929E+12 | 0.163252E+12 | 0.04 | |||
Minimum of Months | 0.00 | 0.00 | 2426094.96 | 2426094.96 | 1645.76 | 1645.76 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.435176E+11 | 0.435137E+11 | 113858.90 | 91647.30 | 0.13 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.932156E+10 | 0.814413E+10 | 5358.43 | 03-JAN-14:40 | 4854.64 | 0.00 |
February | 0.00 | 0.00 | 0.133897E+11 | 0.119217E+11 | 5990.05 | 22-FEB-19:00 | 5058.54 | 0.00 |
March | 0.00 | 0.00 | 0.147274E+11 | 0.141123E+11 | 6525.62 | 31-MAR-23:10 | 5495.39 | 0.00 |
April | 0.00 | 0.00 | 0.567507E+11 | 0.545570E+11 | 307283.12 | 07-APR-14:00 | 307283.12 | 0.00 |
May | 0.00 | 0.00 | 0.176319E+11 | 0.164396E+11 | 145894.10 | 19-MAY-13:50 | 138677.39 | 0.00 |
June | 0.00 | 0.00 | 0.128729E+12 | 0.116404E+12 | 335421.14 | 20-JUN-18:50 | 226600.32 | 0.00 |
July | 0.00 | 0.00 | 0.422518E+12 | 0.380650E+12 | 428612.04 | 19-JUL-10:50 | 322024.55 | 0.00 |
August | 0.00 | 0.00 | 0.524374E+12 | 0.483500E+12 | 485040.74 | 08-AUG-12:00 | 401841.15 | 0.00 |
September | 0.00 | 0.00 | 0.456912E+11 | 0.416767E+11 | 224253.23 | 07-SEP-16:00 | 131431.92 | 0.00 |
October | 0.00 | 0.00 | 0.220698E+11 | 0.205604E+11 | 175994.44 | 18-OCT-15:00 | 175994.44 | 0.00 |
November | 0.00 | 0.00 | 0.147600E+11 | 0.139996E+11 | 34438.33 | 17-NOV-17:00 | 32730.80 | 0.00 |
December | 0.00 | 0.00 | 0.149816E+11 | 0.147299E+11 | 21371.73 | 10-DEC-02:00 | 21371.73 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.128494E+13 | 0.117670E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.932156E+10 | 0.814413E+10 | 5358.43 | 4854.64 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.524374E+12 | 0.483500E+12 | 485040.74 | 401841.15 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.323685E+10 | 0.323653E+10 | 2382.32 | 13-JAN-16:20 | 2382.32 | 0.00 |
February | 0.00 | 0.00 | 0.842734E+10 | 0.842734E+10 | 5295.53 | 26-FEB-17:17 | 5295.53 | 0.00 |
March | 0.00 | 0.00 | 0.150744E+11 | 0.150744E+11 | 7508.42 | 31-MAR-24:00 | 7508.42 | 0.00 |
April | 0.00 | 0.00 | 0.201382E+11 | 0.201294E+11 | 9189.30 | 16-APR-18:16 | 9189.30 | 0.00 |
May | 0.00 | 0.00 | 0.576410E+10 | 0.573897E+10 | 4153.90 | 31-MAY-24:00 | 4153.90 | 0.00 |
June | 0.00 | 0.00 | 0.110618E+11 | 0.109697E+11 | 6035.60 | 30-JUN-23:55 | 6021.64 | 0.00 |
July | 0.00 | 0.00 | 0.168624E+11 | 0.167581E+11 | 7934.34 | 31-JUL-23:50 | 7934.34 | 0.00 |
August | 0.00 | 0.00 | 0.216585E+11 | 0.215777E+11 | 9138.51 | 05-AUG-19:44 | 9138.51 | 0.00 |
September | 0.00 | 0.00 | 0.586339E+10 | 0.577534E+10 | 3985.38 | 30-SEP-24:00 | 3985.38 | 0.00 |
October | 0.00 | 0.00 | 0.106501E+11 | 0.106387E+11 | 5644.22 | 31-OCT-24:00 | 5644.22 | 0.00 |
November | 0.00 | 0.00 | 0.147285E+11 | 0.147263E+11 | 6766.64 | 12-NOV-16:27 | 6766.64 | 0.00 |
December | 0.00 | 0.00 | 0.196341E+11 | 0.196338E+11 | 8438.72 | 10-DEC-16:05 | 8438.72 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.153100E+12 | 0.152686E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.323685E+10 | 0.323653E+10 | 2382.32 | 2382.32 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.216585E+11 | 0.215777E+11 | 9189.30 | 9189.30 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.990813E+10 | 0.990492E+10 | 19755.37 | 13-JAN-16:30 | 19755.37 | 0.00 |
February | 0.00 | 0.00 | 0.615817E+11 | 0.615817E+11 | 46714.05 | 26-FEB-17:23 | 46714.05 | 0.00 |
March | 0.00 | 0.00 | 0.127095E+12 | 0.127095E+12 | 65721.59 | 31-MAR-23:40 | 65721.59 | 0.00 |
April | 0.00 | 0.00 | 0.181933E+12 | 0.181844E+12 | 85543.24 | 22-APR-18:19 | 85543.24 | 0.00 |
May | 0.00 | 0.00 | 0.479401E+11 | 0.476947E+11 | 39349.52 | 31-MAY-24:00 | 39349.52 | 0.00 |
June | 0.00 | 0.00 | 0.101946E+12 | 0.101033E+12 | 58966.25 | 30-JUN-23:55 | 58827.97 | 0.00 |
July | 0.00 | 0.00 | 0.158125E+12 | 0.157088E+12 | 76718.08 | 31-JUL-23:53 | 76718.08 | 0.00 |
August | 0.00 | 0.00 | 0.204303E+12 | 0.203498E+12 | 87496.49 | 05-AUG-19:42 | 87496.49 | 0.00 |
September | 0.00 | 0.00 | 0.497790E+11 | 0.489197E+11 | 35811.90 | 30-SEP-23:30 | 35811.90 | 0.00 |
October | 0.00 | 0.00 | 0.898030E+11 | 0.896889E+11 | 49298.18 | 15-OCT-17:10 | 49298.18 | 0.00 |
November | 0.00 | 0.00 | 0.122989E+12 | 0.122967E+12 | 61719.31 | 03-NOV-16:00 | 61169.74 | 0.00 |
December | 0.00 | 0.00 | 0.161820E+12 | 0.161817E+12 | 77192.30 | 06-DEC-16:10 | 76896.46 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.131722E+13 | 0.131313E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.990813E+10 | 0.990492E+10 | 19755.37 | 19755.37 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.204303E+12 | 0.203498E+12 | 87496.49 | 87496.49 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.284527E+09 | 0.284337E+09 | 1910.82 | 13-JAN-16:30 | 1910.82 | 0.00 |
February | 0.00 | 0.00 | 0.457896E+10 | 0.457896E+10 | 4447.73 | 28-FEB-17:00 | 4447.73 | 0.00 |
March | 0.00 | 0.00 | 0.110945E+11 | 0.110945E+11 | 6511.27 | 28-MAR-17:50 | 6511.27 | 0.00 |
April | 0.00 | 0.00 | 0.170829E+11 | 0.170741E+11 | 8568.55 | 25-APR-18:10 | 8568.55 | 0.00 |
May | 0.00 | 0.00 | 0.410281E+10 | 0.407857E+10 | 3862.94 | 31-MAY-23:40 | 3862.94 | 0.00 |
June | 0.00 | 0.00 | 0.998846E+10 | 0.989732E+10 | 5908.56 | 30-JUN-23:55 | 5894.64 | 0.00 |
July | 0.00 | 0.00 | 0.157615E+11 | 0.156580E+11 | 7646.47 | 31-JUL-23:53 | 7646.47 | 0.00 |
August | 0.00 | 0.00 | 0.202907E+11 | 0.202104E+11 | 8930.79 | 05-AUG-19:44 | 8930.79 | 0.00 |
September | 0.00 | 0.00 | 0.443767E+10 | 0.435285E+10 | 3703.89 | 04-SEP-17:43 | 3703.89 | 0.00 |
October | 0.00 | 0.00 | 0.764908E+10 | 0.763790E+10 | 4827.15 | 18-OCT-17:00 | 4827.15 | 0.00 |
November | 0.00 | 0.00 | 0.104327E+11 | 0.104305E+11 | 6109.79 | 03-NOV-16:00 | 6054.76 | 0.00 |
December | 0.00 | 0.00 | 0.140314E+11 | 0.140311E+11 | 7626.37 | 06-DEC-16:10 | 7598.30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.119735E+12 | 0.119328E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.284527E+09 | 0.284337E+09 | 1910.82 | 1910.82 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.202907E+11 | 0.202104E+11 | 8930.79 | 8930.79 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 315002.57 | 1924066.64 | 09-JAN-07:15 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 176945.93 | 2015336.17 | 07-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 89350.32 | 1718696.90 | 06-MAR-06:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 21802.62 | 1477967.30 | 29-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 12749.02 | 1567932.15 | 08-MAY-04:01 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 371.91 | 127503.67 | 17-JUN-05:03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.80 | 1484.52 | 08-JUL-05:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 67.08 | 128029.53 | 18-AUG-05:02 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 3256.18 | 570554.62 | 19-SEP-05:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 16489.78 | 1611023.12 | 10-OCT-04:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 76794.82 | 1699993.10 | 27-NOV-06:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 195995.69 | 1722956.70 | 26-DEC-06:01 |
Annual Sum or Average | 0.00 | 75453.60 | ||||
Minimum of Months | 0.00 | 0.00 | 0.80 | 1484.52 | ||
Maximum of Months | 0.00 | 0.00 | 315002.57 | 2015336.17 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 46.34 | 3306.20 | 13-JAN-15:10 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 3854.67 | 475528.42 | 27-FEB-15:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 767.05 | 153205.42 | 14-MAR-13:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 27726.22 | 1043175.32 | 07-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 83692.65 | 1505203.24 | 19-MAY-12:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 276805.84 | 2119544.42 | 21-JUN-12:33 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 437711.19 | 2605422.06 | 14-JUL-10:02 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 385133.42 | 2171982.08 | 22-AUG-13:53 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 186673.63 | 2562404.77 | 07-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 45139.31 | 1648994.44 | 18-OCT-13:45 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 2578.30 | 225150.86 | 03-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 185.34 | 20605.40 | 19-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 121792.84 | 0.00 | ||||
Minimum of Months | 46.34 | 3306.20 | 0.00 | 0.00 | ||
Maximum of Months | 437711.19 | 2605422.06 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.02 | 31.84 | 13-JAN-15:10 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 3621.91 | 473683.48 | 27-FEB-15:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 494.57 | 151002.42 | 14-MAR-13:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 27061.83 | 1051297.55 | 07-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 84576.99 | 2450474.20 | 19-MAY-12:20 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 292215.06 | 2400381.80 | 20-JUN-11:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 462955.15 | 2717699.55 | 14-JUL-10:00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 401924.31 | 2400776.58 | 10-AUG-08:20 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 195775.71 | 2567065.41 | 07-SEP-15:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 46740.29 | 2197911.17 | 18-OCT-13:40 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 2336.75 | 222660.43 | 03-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 42.64 | 17574.12 | 19-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 127457.11 | 0.00 | ||||
Minimum of Months | 0.02 | 31.84 | 0.00 | 0.00 | ||
Maximum of Months | 462955.15 | 2717699.55 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 15826.76 | 39731.81 | 13-JAN-16:30 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 51277.93 | 132276.49 | 27-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 83753.73 | 129429.78 | 31-MAR-17:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 149620.34 | 1033629.80 | 07-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 75337.56 | 1020218.96 | 20-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 280105.71 | 1399987.39 | 29-JUN-15:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 646695.63 | 1970891.55 | 17-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 681235.54 | 2064343.62 | 06-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 161926.09 | 1318958.80 | 02-SEP-17:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 78926.28 | 824147.26 | 18-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 83767.94 | 136894.29 | 17-NOV-17:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 103482.60 | 177531.04 | 22-DEC-17:20 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 202579.14 | 0.00 | ||||
Minimum of Months | 15826.76 | 39731.81 | 0.00 | 0.00 | ||
Maximum of Months | 681235.54 | 2064343.62 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 16135.06 | 57876.84 | 31-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16514.11 | 58184.03 | 17-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17371.53 | 58080.79 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15686.02 | 56501.24 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15336.03 | 54000.05 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14754.70 | 50704.58 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 12894.00 | 47668.68 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 13810.05 | 45986.67 | 01-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 13115.78 | 47091.89 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 13695.35 | 49894.21 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14752.91 | 53085.57 | 30-NOV-12:45 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 15068.81 | 55889.13 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 14918.66 | ||||
Minimum of Months | 0.00 | 0.00 | 12894.00 | 45986.67 | ||
Maximum of Months | 0.00 | 0.00 | 17371.53 | 58184.03 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1.93 | 4043.23 | 15-JAN-13:30 | 476.07 | 94192.71 | 13-JAN-15:30 |
February | 3323.34 | 535280.37 | 27-FEB-15:30 | 1816.10 | 132440.02 | 08-FEB-06:50 |
March | 177.59 | 130306.31 | 14-MAR-13:40 | 3014.43 | 145291.10 | 10-MAR-05:01 |
April | 28354.78 | 1189009.43 | 07-APR-14:00 | 4174.83 | 142024.73 | 28-APR-05:50 |
May | 95294.23 | 2334294.70 | 19-MAY-14:40 | 3885.49 | 129640.20 | 22-MAY-13:10 |
June | 350345.24 | 3010988.12 | 20-JUN-13:05 | 1442.95 | 111239.88 | 02-JUN-05:03 |
July | 569065.98 | 2899512.57 | 19-JUL-08:43 | 1288.09 | 91875.68 | 08-JUL-08:30 |
August | 489072.35 | 2358260.50 | 07-AUG-11:30 | 1920.20 | 86963.23 | 30-AUG-07:50 |
September | 235097.67 | 4705455.64 | 07-SEP-15:03 | 2156.97 | 118612.50 | 16-SEP-05:50 |
October | 49794.75 | 2004671.74 | 18-OCT-13:45 | 2843.10 | 133381.16 | 11-OCT-05:30 |
November | 1688.33 | 258347.95 | 03-NOV-14:00 | 1738.94 | 142077.92 | 13-NOV-16:10 |
December | 13.73 | 10322.36 | 19-DEC-14:50 | 1555.50 | 132262.94 | 08-DEC-06:30 |
Annual Sum or Average | 153051.16 | 2193.78 | ||||
Minimum of Months | 1.93 | 4043.23 | 476.07 | 86963.23 | ||
Maximum of Months | 569065.98 | 4705455.64 | 4174.83 | 145291.10 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.454071E+10 | 0.37 | 16172.72 | 20-JAN-06:01 | 1.62 |
February | 0.512360E+10 | 0.41 | 16172.72 | 07-FEB-06:01 | 1.61 |
March | 0.748535E+10 | 0.47 | 16655.31 | 28-MAR-15:50 | 1.64 |
April | 0.952010E+10 | 0.54 | 21975.28 | 24-APR-15:10 | 1.95 |
May | 0.897271E+10 | 0.51 | 25204.92 | 19-MAY-16:22 | 2.11 |
June | 0.150972E+11 | 0.72 | 25204.92 | 06-JUN-13:50 | 2.11 |
July | 0.220628E+11 | 0.91 | 25204.92 | 03-JUL-08:40 | 2.11 |
August | 0.209743E+11 | 0.89 | 25204.92 | 01-AUG-12:55 | 2.11 |
September | 0.108199E+11 | 0.58 | 25204.92 | 01-SEP-09:55 | 2.12 |
October | 0.851297E+10 | 0.49 | 22650.53 | 18-OCT-13:40 | 1.99 |
November | 0.687185E+10 | 0.45 | 16172.72 | 27-NOV-05:01 | 1.62 |
December | 0.590223E+10 | 0.41 | 16172.72 | 16-DEC-06:02 | 1.61 |
Annual Sum or Average | 0.125884E+12 | 0.56 | |||
Minimum of Months | 0.454071E+10 | 0.37 | 16172.72 | 1.61 | |
Maximum of Months | 0.220628E+11 | 0.91 | 25204.92 | 2.12 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.402730E+11 | 0.40 | 69164.62 | 09-JAN-05:01 | 1.01 |
February | 0.380595E+11 | 0.40 | 123869.51 | 28-FEB-06:02 | 1.43 |
March | 0.478333E+11 | 0.41 | 115862.79 | 02-MAR-06:03 | 1.37 |
April | 0.535239E+11 | 0.41 | 151378.01 | 25-APR-15:30 | 1.61 |
May | 0.664234E+11 | 0.45 | 235173.90 | 19-MAY-16:22 | 2.11 |
June | 0.108604E+12 | 0.61 | 235173.90 | 06-JUN-14:00 | 2.11 |
July | 0.137047E+12 | 0.67 | 235173.90 | 03-JUL-08:57 | 2.11 |
August | 0.131751E+12 | 0.66 | 235173.90 | 01-AUG-13:00 | 2.11 |
September | 0.760956E+11 | 0.50 | 235173.90 | 01-SEP-10:37 | 2.12 |
October | 0.540870E+11 | 0.40 | 131512.00 | 05-OCT-05:02 | 1.48 |
November | 0.416434E+11 | 0.37 | 144610.91 | 06-NOV-06:01 | 1.57 |
December | 0.376885E+11 | 0.37 | 69164.62 | 26-DEC-06:01 | 1.01 |
Annual Sum or Average | 0.833029E+12 | 0.47 | |||
Minimum of Months | 0.376885E+11 | 0.37 | 69164.62 | 1.01 | |
Maximum of Months | 0.137047E+12 | 0.67 | 235173.90 | 2.12 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.491338E+10 | 0.47 | 6124.60 | 02-JAN-04:01 | 0.88 |
February | 0.385949E+10 | 0.40 | 6124.60 | 03-FEB-06:01 | 0.89 |
March | 0.437676E+10 | 0.40 | 7166.47 | 28-MAR-15:50 | 0.96 |
April | 0.435640E+10 | 0.37 | 13937.72 | 25-APR-15:40 | 1.42 |
May | 0.571834E+10 | 0.41 | 26555.42 | 19-MAY-15:00 | 2.11 |
June | 0.102298E+11 | 0.55 | 26555.42 | 06-JUN-14:00 | 2.11 |
July | 0.136397E+11 | 0.62 | 26555.42 | 11-JUL-14:00 | 2.12 |
August | 0.123979E+11 | 0.59 | 26555.42 | 01-AUG-13:00 | 2.11 |
September | 0.647163E+10 | 0.44 | 26555.42 | 01-SEP-14:30 | 2.11 |
October | 0.418548E+10 | 0.36 | 10625.40 | 18-OCT-16:00 | 1.21 |
November | 0.392639E+10 | 0.39 | 6124.60 | 14-NOV-06:01 | 0.89 |
December | 0.456033E+10 | 0.44 | 6124.60 | 18-DEC-06:01 | 0.88 |
Annual Sum or Average | 0.786356E+11 | 0.45 | |||
Minimum of Months | 0.385949E+10 | 0.36 | 6124.60 | 0.88 | |
Maximum of Months | 0.136397E+11 | 0.62 | 26555.42 | 2.12 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.377685E+10 | 0.40 | 14511.82 | 02-JAN-07:05 | 2.12 |
February | 0.311083E+10 | 0.38 | 14511.82 | 02-FEB-07:03 | 2.15 |
March | 0.459264E+10 | 0.45 | 14511.82 | 01-MAR-07:03 | 2.15 |
April | 0.607964E+10 | 0.51 | 14511.82 | 01-APR-06:10 | 2.14 |
May | 0.804764E+10 | 0.59 | 14511.82 | 01-MAY-06:05 | 2.14 |
June | 0.145376E+11 | 0.86 | 14511.82 | 01-JUN-06:10 | 2.14 |
July | 0.108745E+11 | 0.60 | 14511.82 | 03-JUL-06:10 | 2.12 |
August | 0.150001E+11 | 0.85 | 14511.82 | 01-AUG-06:10 | 2.13 |
September | 0.127624E+11 | 0.79 | 14511.82 | 01-SEP-21:00 | 2.06 |
October | 0.129006E+11 | 0.79 | 14511.82 | 02-OCT-06:10 | 2.13 |
November | 0.107895E+11 | 0.71 | 14511.82 | 01-NOV-06:10 | 2.15 |
December | 0.571616E+10 | 0.47 | 14511.82 | 01-DEC-07:05 | 2.15 |
Annual Sum or Average | 0.108188E+12 | 0.62 | |||
Minimum of Months | 0.311083E+10 | 0.38 | 14511.82 | 2.06 | |
Maximum of Months | 0.150001E+11 | 0.86 | 14511.82 | 2.15 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.123772E+12 | 1.53 | 46211.16 | 01-JAN-00:05 | 1.53 |
February | 0.111794E+12 | 1.54 | 46211.16 | 01-FEB-00:20 | 1.53 |
March | 0.123772E+12 | 1.54 | 46211.16 | 01-MAR-00:10 | 1.54 |
April | 0.119779E+12 | 1.54 | 46211.16 | 01-APR-00:10 | 1.54 |
May | 0.123772E+12 | 1.53 | 46211.16 | 01-MAY-00:10 | 1.53 |
June | 0.119779E+12 | 1.53 | 46211.16 | 01-JUN-00:10 | 1.53 |
July | 0.123772E+12 | 1.53 | 46211.16 | 01-JUL-00:03 | 1.53 |
August | 0.123772E+12 | 1.53 | 46211.16 | 01-AUG-00:03 | 1.53 |
September | 0.119779E+12 | 1.53 | 46211.16 | 01-SEP-00:03 | 1.53 |
October | 0.123772E+12 | 1.54 | 46211.16 | 01-OCT-00:10 | 1.53 |
November | 0.119779E+12 | 1.54 | 46211.16 | 01-NOV-00:10 | 1.54 |
December | 0.123772E+12 | 1.54 | 46211.16 | 01-DEC-00:10 | 1.54 |
Annual Sum or Average | 0.145732E+13 | 1.54 | |||
Minimum of Months | 0.111794E+12 | 1.53 | 46211.16 | 1.53 | |
Maximum of Months | 0.123772E+12 | 1.54 | 46211.16 | 1.54 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.173201E+10 | 1.05 | 646.66 | 01-JAN-00:05 | 1.05 |
February | 0.156440E+10 | 1.05 | 646.66 | 01-FEB-00:10 | 1.05 |
March | 0.173201E+10 | 1.05 | 646.66 | 01-MAR-00:10 | 1.05 |
April | 0.167614E+10 | 1.05 | 646.66 | 01-APR-00:10 | 1.05 |
May | 0.173201E+10 | 1.05 | 646.66 | 01-MAY-00:10 | 1.05 |
June | 0.167614E+10 | 1.05 | 646.66 | 01-JUN-00:10 | 1.05 |
July | 0.173201E+10 | 1.05 | 646.66 | 01-JUL-00:03 | 1.05 |
August | 0.173201E+10 | 1.05 | 646.66 | 01-AUG-00:03 | 1.05 |
September | 0.167614E+10 | 1.05 | 646.66 | 01-SEP-00:03 | 1.05 |
October | 0.173201E+10 | 1.05 | 646.66 | 01-OCT-00:10 | 1.05 |
November | 0.167614E+10 | 1.05 | 646.66 | 01-NOV-00:10 | 1.05 |
December | 0.173201E+10 | 1.05 | 646.66 | 01-DEC-00:10 | 1.05 |
Annual Sum or Average | 0.203930E+11 | 1.05 | |||
Minimum of Months | 0.156440E+10 | 1.05 | 646.66 | 1.05 | |
Maximum of Months | 0.173201E+10 | 1.05 | 646.66 | 1.05 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.166592E+11 | 1.05 | 6219.85 | 01-JAN-00:05 | 1.05 |
February | 0.150471E+11 | 1.05 | 6219.85 | 01-FEB-00:10 | 1.05 |
March | 0.166592E+11 | 1.05 | 6219.85 | 01-MAR-00:10 | 1.05 |
April | 0.161218E+11 | 1.05 | 6219.85 | 01-APR-00:10 | 1.05 |
May | 0.166592E+11 | 1.05 | 6219.85 | 01-MAY-00:10 | 1.05 |
June | 0.161218E+11 | 1.05 | 6219.85 | 01-JUN-00:10 | 1.05 |
July | 0.166592E+11 | 1.05 | 6219.85 | 01-JUL-00:03 | 1.05 |
August | 0.166592E+11 | 1.05 | 6219.85 | 01-AUG-00:03 | 1.05 |
September | 0.161218E+11 | 1.05 | 6219.85 | 01-SEP-00:03 | 1.05 |
October | 0.166592E+11 | 1.05 | 6219.85 | 01-OCT-00:10 | 1.05 |
November | 0.161218E+11 | 1.05 | 6219.85 | 01-NOV-00:10 | 1.05 |
December | 0.166592E+11 | 1.05 | 6219.85 | 01-DEC-00:10 | 1.05 |
Annual Sum or Average | 0.196149E+12 | 1.05 | |||
Minimum of Months | 0.150471E+11 | 1.05 | 6219.85 | 1.05 | |
Maximum of Months | 0.166592E+11 | 1.05 | 6219.85 | 1.05 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.169455E+10 | 1.05 | 632.67 | 01-JAN-00:05 | 1.04 |
February | 0.153056E+10 | 1.05 | 632.67 | 01-FEB-00:10 | 1.05 |
March | 0.169455E+10 | 1.05 | 632.67 | 01-MAR-00:20 | 1.05 |
April | 0.163989E+10 | 1.05 | 632.67 | 01-APR-00:10 | 1.05 |
May | 0.169455E+10 | 1.05 | 632.67 | 01-MAY-00:10 | 1.05 |
June | 0.163989E+10 | 1.05 | 632.67 | 01-JUN-00:20 | 1.05 |
July | 0.169455E+10 | 1.05 | 632.67 | 01-JUL-00:03 | 1.05 |
August | 0.169455E+10 | 1.05 | 632.67 | 01-AUG-00:03 | 1.05 |
September | 0.163989E+10 | 1.05 | 632.67 | 01-SEP-00:03 | 1.05 |
October | 0.169455E+10 | 1.05 | 632.67 | 01-OCT-00:10 | 1.05 |
November | 0.163989E+10 | 1.05 | 632.67 | 01-NOV-00:10 | 1.05 |
December | 0.169455E+10 | 1.05 | 632.67 | 01-DEC-00:10 | 1.05 |
Annual Sum or Average | 0.199520E+11 | 1.05 | |||
Minimum of Months | 0.153056E+10 | 1.05 | 632.67 | 1.04 | |
Maximum of Months | 0.169455E+10 | 1.05 | 632.67 | 1.05 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.169641E+09 | 0.152677E+09 | 1357.26 | 09-JAN-07:03 | 1221.54 | 1221.54 | 46.86 | 12.63 |
February | 53379844.96 | 48041860.47 | 1182.28 | 07-FEB-06:01 | 1064.05 | 1064.05 | 41.58 | 11.93 |
March | 21399487.22 | 19259538.50 | 1207.71 | 06-MAR-06:02 | 1086.94 | 1086.94 | 47.76 | 12.01 |
April | 2454093.42 | 2208684.08 | 428.47 | 29-APR-05:01 | 385.63 | 385.63 | 35.33 | 7.58 |
May | 1740110.02 | 1566099.01 | 422.53 | 08-MAY-05:01 | 380.27 | 380.27 | 38.80 | 7.52 |
June | 28160.78 | 25344.71 | 4.58 | 17-JUN-05:03 | 4.13 | 4.13 | 23.91 | 0.53 |
July | 53.42 | 48.08 | 0.04 | 08-JUL-05:10 | 0.03 | 0.03 | 22.18 | 0.01 |
August | 4861.57 | 4375.41 | 4.45 | 18-AUG-05:02 | 4.01 | 4.01 | 22.38 | 0.51 |
September | 281158.76 | 253042.88 | 49.49 | 19-SEP-05:03 | 44.54 | 44.54 | 27.80 | 2.52 |
October | 2071738.72 | 1864564.84 | 393.64 | 10-OCT-04:01 | 354.28 | 354.28 | 29.17 | 7.30 |
November | 15438336.08 | 13894502.47 | 1202.81 | 27-NOV-06:02 | 1082.53 | 1082.53 | 48.07 | 11.98 |
December | 68717898.79 | 61846108.91 | 1186.74 | 26-DEC-06:01 | 1068.06 | 1068.06 | 47.42 | 11.92 |
Annual Sum or Average | 0.335156E+09 | 0.301641E+09 | ||||||
Minimum of Months | 53.42 | 48.08 | 0.04 | 0.03 | 0.03 | 22.18 | 0.01 | |
Maximum of Months | 0.169641E+09 | 0.152677E+09 | 1357.26 | 1221.54 | 1221.54 | 48.07 | 12.63 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 657.81 | 592.03 | 0.43 | 13-JAN-15:00 | 0.39 | 0.39 | 6.70 | 0.12 |
February | 4256977.68 | 3831279.91 | 355.78 | 27-FEB-14:20 | 320.20 | 320.20 | 6.71 | 14.90 |
March | 354824.96 | 319342.46 | 50.85 | 14-MAR-13:30 | 45.76 | 45.76 | 6.70 | 5.33 |
April | 35099605.26 | 31589644.73 | 1203.78 | 07-APR-14:00 | 1083.40 | 1083.40 | 6.71 | 26.14 |
May | 0.310722E+09 | 0.279650E+09 | 10573.43 | 19-MAY-12:20 | 9516.08 | 9516.08 | 11.26 | 64.37 |
June | 0.172160E+10 | 0.154944E+10 | 10573.43 | 20-JUN-10:43 | 9516.08 | 9516.08 | 9.74 | 64.37 |
July | 0.392173E+10 | 0.352956E+10 | 10573.43 | 03-JUL-08:40 | 9516.08 | 9516.08 | 9.38 | 64.37 |
August | 0.361541E+10 | 0.325387E+10 | 10573.43 | 01-AUG-12:55 | 9516.08 | 9516.08 | 9.38 | 64.37 |
September | 0.137801E+10 | 0.124021E+10 | 10573.43 | 02-SEP-11:30 | 9516.08 | 9516.08 | 10.64 | 64.37 |
October | 0.165997E+09 | 0.149397E+09 | 10573.43 | 18-OCT-13:00 | 9516.08 | 9516.08 | 10.52 | 64.37 |
November | 1292127.47 | 1162914.73 | 102.68 | 03-NOV-13:55 | 92.41 | 92.41 | 6.70 | 7.91 |
December | 17675.93 | 15908.33 | 3.06 | 19-DEC-15:00 | 2.76 | 2.76 | 6.70 | 0.74 |
Annual Sum or Average | 0.111545E+11 | 0.100390E+11 | ||||||
Minimum of Months | 657.81 | 592.03 | 0.43 | 0.39 | 0.39 | 6.70 | 0.12 | |
Maximum of Months | 0.392173E+10 | 0.352956E+10 | 10573.43 | 9516.08 | 9516.08 | 11.26 | 64.37 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.138271E+09 | 0.124444E+09 | 3638.70 | 13-JAN-14:50 | 3274.83 | 3274.83 | 6.72 | 32.19 |
February | 0.633776E+09 | 0.570398E+09 | 3638.70 | 01-FEB-04:01 | 3274.83 | 3274.83 | 6.72 | 32.19 |
March | 0.810665E+09 | 0.729598E+09 | 3638.70 | 01-MAR-06:06 | 3274.83 | 3274.83 | 6.74 | 32.19 |
April | 0.199546E+10 | 0.179592E+10 | 3638.70 | 01-APR-04:14 | 3274.83 | 3274.83 | 6.72 | 32.19 |
May | 0.323779E+10 | 0.291401E+10 | 3638.70 | 01-MAY-12:00 | 3274.83 | 3274.83 | 6.72 | 32.19 |
June | 0.499623E+10 | 0.449661E+10 | 3638.70 | 01-JUN-04:12 | 3274.83 | 3274.83 | 7.70 | 32.19 |
July | 0.678805E+10 | 0.610924E+10 | 3638.70 | 01-JUL-00:03 | 3274.83 | 3274.83 | 6.94 | 32.19 |
August | 0.636672E+10 | 0.573005E+10 | 3638.70 | 01-AUG-00:05 | 3274.83 | 3274.83 | 6.86 | 32.19 |
September | 0.400979E+10 | 0.360881E+10 | 3638.70 | 01-SEP-00:52 | 3274.83 | 3274.83 | 6.82 | 32.19 |
October | 0.202261E+10 | 0.182035E+10 | 3638.70 | 02-OCT-05:08 | 3274.83 | 3274.83 | 7.83 | 32.19 |
November | 0.697640E+09 | 0.627876E+09 | 3638.70 | 01-NOV-06:11 | 3274.83 | 3274.83 | 6.98 | 32.19 |
December | 0.424673E+09 | 0.382206E+09 | 3638.70 | 01-DEC-12:20 | 3274.83 | 3274.83 | 6.72 | 32.19 |
Annual Sum or Average | 0.321217E+11 | 0.289095E+11 | ||||||
Minimum of Months | 0.138271E+09 | 0.124444E+09 | 3638.70 | 3274.83 | 3274.83 | 6.72 | 32.19 | |
Maximum of Months | 0.678805E+10 | 0.610924E+10 | 3638.70 | 3274.83 | 3274.83 | 7.83 | 32.19 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 6.70 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 6.75 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
May | 92131933.18 | 82918739.86 | 3638.70 | 19-MAY-12:00 | 3274.83 | 3274.83 | 12.87 | 16.09 |
June | 0.841450E+09 | 0.757305E+09 | 3638.70 | 05-JUN-12:40 | 3274.83 | 3274.83 | 15.41 | 16.09 |
July | 0.167890E+10 | 0.151101E+10 | 3638.70 | 03-JUL-10:05 | 3274.83 | 3274.83 | 13.04 | 32.19 |
August | 0.149933E+10 | 0.134939E+10 | 3638.70 | 01-AUG-12:30 | 3274.83 | 3274.83 | 15.14 | 16.09 |
September | 0.438827E+09 | 0.394945E+09 | 3638.70 | 01-SEP-09:50 | 3274.83 | 3274.83 | 15.27 | 16.09 |
October | 30565096.32 | 27508586.68 | 3638.70 | 18-OCT-13:45 | 3274.83 | 3274.83 | 12.82 | 32.19 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
Annual Sum or Average | 0.458120E+10 | 0.412308E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 | |
Maximum of Months | 0.167890E+10 | 0.151101E+10 | 3638.70 | 3274.83 | 3274.83 | 15.41 | 32.19 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.110097E+11 | 0.990876E+10 | 4110.56 | 01-JAN-00:05 | 3699.51 | 3699.51 | 18.58 | 17.17 |
February | 0.994427E+10 | 0.894984E+10 | 4110.56 | 01-FEB-00:10 | 3699.51 | 3699.51 | 19.05 | 17.17 |
March | 0.110097E+11 | 0.990876E+10 | 4110.56 | 01-MAR-00:10 | 3699.51 | 3699.51 | 19.76 | 17.17 |
April | 0.106546E+11 | 0.958912E+10 | 4110.56 | 01-APR-00:10 | 3699.51 | 3699.51 | 20.20 | 17.17 |
May | 0.110097E+11 | 0.990876E+10 | 4110.56 | 01-MAY-00:10 | 3699.51 | 3699.51 | 18.80 | 17.17 |
June | 0.106546E+11 | 0.958912E+10 | 4110.56 | 01-JUN-00:10 | 3699.51 | 3699.51 | 19.46 | 17.17 |
July | 0.110097E+11 | 0.990876E+10 | 4110.56 | 01-JUL-00:03 | 3699.51 | 3699.51 | 25.22 | 17.17 |
August | 0.110097E+11 | 0.990876E+10 | 4110.56 | 01-AUG-00:03 | 3699.51 | 3699.51 | 27.98 | 17.17 |
September | 0.106546E+11 | 0.958912E+10 | 4110.56 | 01-SEP-00:03 | 3699.51 | 3699.51 | 19.39 | 17.17 |
October | 0.110097E+11 | 0.990876E+10 | 4110.56 | 01-OCT-00:10 | 3699.51 | 3699.51 | 19.42 | 17.17 |
November | 0.106546E+11 | 0.958912E+10 | 4110.56 | 01-NOV-00:10 | 3699.51 | 3699.51 | 19.76 | 17.17 |
December | 0.110097E+11 | 0.990876E+10 | 4110.56 | 01-DEC-00:10 | 3699.51 | 3699.51 | 20.06 | 17.17 |
Annual Sum or Average | 0.129631E+12 | 0.116668E+12 | ||||||
Minimum of Months | 0.994427E+10 | 0.894984E+10 | 4110.56 | 3699.51 | 3699.51 | 18.58 | 17.17 | |
Maximum of Months | 0.110097E+11 | 0.990876E+10 | 4110.56 | 3699.51 | 3699.51 | 27.98 | 17.17 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:03 | 16.86 | 16.86 | 56.77 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:01 | 16.86 | 16.86 | 56.82 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:01 | 16.86 | 16.86 | 56.76 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:02 | 16.86 | 16.86 | 56.74 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:01 | 16.86 | 16.86 | 57.33 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 57.02 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 57.19 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 57.31 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:02 | 16.86 | 16.86 | 57.37 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 56.99 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:03 | 16.86 | 16.86 | 57.07 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:01 | 16.86 | 16.86 | 57.08 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 56.74 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.37 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.532002E+09 | 0.478802E+09 | 14001.64 | 15-JAN-13:30 | 12601.48 | 12601.48 | 21.12 | 56.76 |
February | 0.243888E+10 | 0.219499E+10 | 14024.20 | 27-FEB-15:30 | 12621.78 | 12621.78 | 23.36 | 56.76 |
March | 0.311906E+10 | 0.280715E+10 | 14007.00 | 14-MAR-13:40 | 12606.30 | 12606.30 | 21.65 | 56.76 |
April | 0.768107E+10 | 0.691297E+10 | 14053.92 | 07-APR-14:00 | 12648.52 | 12648.52 | 26.11 | 56.76 |
May | 0.128069E+11 | 0.115262E+11 | 28105.74 | 19-MAY-14:40 | 25295.16 | 25295.16 | 26.02 | 113.53 |
June | 0.224264E+11 | 0.201837E+11 | 28139.36 | 20-JUN-13:05 | 25325.43 | 25325.43 | 27.45 | 113.53 |
July | 0.325324E+11 | 0.292792E+11 | 28133.82 | 19-JUL-08:43 | 25320.44 | 25320.44 | 27.21 | 113.53 |
August | 0.302023E+11 | 0.271821E+11 | 28106.92 | 07-AUG-11:30 | 25296.23 | 25296.23 | 26.07 | 113.53 |
September | 0.170810E+11 | 0.153729E+11 | 28186.63 | 07-SEP-14:30 | 25367.97 | 25367.97 | 29.52 | 113.53 |
October | 0.790583E+10 | 0.711524E+10 | 28089.38 | 18-OCT-13:45 | 25280.44 | 25280.44 | 25.33 | 113.53 |
November | 0.268446E+10 | 0.241602E+10 | 14012.43 | 03-NOV-14:00 | 12611.19 | 12611.19 | 22.19 | 56.76 |
December | 0.163394E+10 | 0.147054E+10 | 14001.91 | 19-DEC-14:50 | 12601.72 | 12601.72 | 21.14 | 56.76 |
Annual Sum or Average | 0.141044E+12 | 0.126940E+12 | ||||||
Minimum of Months | 0.532002E+09 | 0.478802E+09 | 14001.64 | 12601.48 | 12601.48 | 21.12 | 56.76 | |
Maximum of Months | 0.325324E+11 | 0.292792E+11 | 28186.63 | 25367.97 | 25367.97 | 29.52 | 113.53 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 36.89 | 36.89 | 315002.57 | 1924066.64 | 09-JAN-07:15 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 30.54 | 30.54 | 176945.93 | 2015336.17 | 07-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 24.58 | 24.58 | 89350.32 | 1718696.90 | 06-MAR-06:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 25.34 | 25.34 | 21802.62 | 1477967.30 | 29-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.46 | 22.46 | 12749.02 | 1567932.15 | 08-MAY-04:01 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.62 | 22.62 | 371.91 | 127503.67 | 17-JUN-05:03 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 22.18 | 22.18 | 0.80 | 1484.52 | 08-JUL-05:10 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 22.15 | 22.15 | 67.08 | 128029.53 | 18-AUG-05:02 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 22.06 | 22.06 | 3256.18 | 570554.62 | 19-SEP-05:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 20.84 | 20.84 | 16489.78 | 1611023.12 | 10-OCT-04:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 25.63 | 25.63 | 76794.82 | 1699993.10 | 27-NOV-06:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 28.80 | 28.80 | 195995.69 | 1722956.70 | 26-DEC-06:01 |
Annual Sum or Average | 0.00 | 75453.60 | ||||||
Minimum of Months | 0.00 | 0.00 | 20.84 | 20.84 | 0.80 | 1484.52 | ||
Maximum of Months | 0.00 | 0.00 | 36.89 | 36.89 | 315002.57 | 2015336.17 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 46.34 | 3306.20 | 13-JAN-15:10 | 6.72 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 3854.67 | 475528.42 | 27-FEB-15:30 | 10.23 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 767.05 | 153205.42 | 14-MAR-13:30 | 7.83 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 27726.22 | 1043175.32 | 07-APR-14:00 | 14.44 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 83692.65 | 1505203.24 | 19-MAY-12:30 | 12.28 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 276805.84 | 2119544.42 | 21-JUN-12:33 | 14.57 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 437711.19 | 2605422.06 | 14-JUL-10:02 | 16.37 | 7.97 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 385133.42 | 2171982.08 | 22-AUG-13:53 | 14.76 | 6.70 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 186673.63 | 2562404.77 | 07-SEP-15:00 | 16.21 | 7.81 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 45139.31 | 1648994.44 | 18-OCT-13:45 | 12.82 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 2578.30 | 225150.86 | 03-NOV-14:00 | 8.37 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 185.34 | 20605.40 | 19-DEC-15:00 | 6.85 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 121792.84 | 0.00 | ||||||
Minimum of Months | 46.34 | 3306.20 | 6.72 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 437711.19 | 2605422.06 | 16.37 | 7.97 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.02 | 31.84 | 13-JAN-15:10 | 6.80 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 3621.91 | 473683.48 | 27-FEB-15:30 | 15.28 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 494.57 | 151002.42 | 14-MAR-13:30 | 13.47 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 27061.83 | 1051297.55 | 07-APR-14:00 | 16.31 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 84576.99 | 2450474.20 | 19-MAY-12:20 | 15.80 | 11.24 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 292215.06 | 2400381.80 | 20-JUN-11:00 | 15.64 | 11.14 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 462955.15 | 2717699.55 | 14-JUL-10:00 | 17.30 | 13.19 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 401924.31 | 2400776.58 | 10-AUG-08:20 | 16.06 | 11.15 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 195775.71 | 2567065.41 | 07-SEP-15:00 | 16.23 | 7.78 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 46740.29 | 2197911.17 | 18-OCT-13:40 | 14.86 | 10.77 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 2336.75 | 222660.43 | 03-NOV-14:00 | 13.44 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 42.64 | 17574.12 | 19-DEC-15:00 | 12.36 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 127457.11 | 0.00 | ||||||
Minimum of Months | 0.02 | 31.84 | 6.80 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 462955.15 | 2717699.55 | 17.30 | 13.19 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 15826.76 | 39731.81 | 13-JAN-16:30 | 19.00 | 18.33 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 51277.93 | 132276.49 | 27-FEB-16:00 | 20.55 | 19.32 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 83753.73 | 129429.78 | 31-MAR-17:30 | 20.50 | 18.33 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 149620.34 | 1033629.80 | 07-APR-14:00 | 35.44 | 26.48 | 0.00 | 0.00 | 01-APR-00:10 |
May | 75337.56 | 1020218.96 | 20-MAY-16:00 | 35.22 | 31.37 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 280105.71 | 1399987.39 | 29-JUN-15:00 | 41.37 | 34.62 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 646695.63 | 1970891.55 | 17-JUL-16:00 | 50.48 | 40.74 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 681235.54 | 2064343.62 | 06-AUG-16:00 | 51.96 | 39.97 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 161926.09 | 1318958.80 | 02-SEP-17:00 | 40.06 | 35.89 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 78926.28 | 824147.26 | 18-OCT-15:00 | 32.01 | 26.83 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 83767.94 | 136894.29 | 17-NOV-17:00 | 20.63 | 18.33 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 103482.60 | 177531.04 | 22-DEC-17:20 | 21.31 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 202579.14 | 0.00 | ||||||
Minimum of Months | 15826.76 | 39731.81 | 19.00 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 681235.54 | 2064343.62 | 51.96 | 40.74 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 57.91 | 57.91 | 16135.06 | 57876.84 | 31-JAN-12:50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.29 | 57.29 | 16514.11 | 58184.03 | 17-FEB-12:50 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.28 | 57.28 | 17371.53 | 58080.79 | 01-MAR-12:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.35 | 57.35 | 15686.02 | 56501.24 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.99 | 57.99 | 15336.03 | 54000.05 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.63 | 57.63 | 14754.70 | 50704.58 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 57.77 | 57.77 | 12894.00 | 47668.68 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 57.86 | 57.86 | 13810.05 | 45986.67 | 01-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 57.87 | 57.87 | 13115.78 | 47091.89 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.81 | 57.81 | 13695.35 | 49894.21 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.68 | 57.68 | 14752.91 | 53085.57 | 30-NOV-12:45 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.52 | 57.52 | 15068.81 | 55889.13 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 14918.66 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.28 | 57.28 | 12894.00 | 45986.67 | ||
Maximum of Months | 0.00 | 0.00 | 57.99 | 57.99 | 17371.53 | 58184.03 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1.93 | 4043.23 | 15-JAN-13:30 | 21.12 | 20.19 | 476.07 | 94192.71 | 13-JAN-15:30 |
February | 3323.34 | 535280.37 | 27-FEB-15:30 | 23.36 | 21.10 | 1816.10 | 132440.02 | 08-FEB-06:50 |
March | 177.59 | 130306.31 | 14-MAR-13:40 | 21.65 | 20.95 | 3014.43 | 145291.10 | 10-MAR-05:01 |
April | 28354.78 | 1189009.43 | 07-APR-14:00 | 26.11 | 21.10 | 4174.83 | 142024.73 | 28-APR-05:50 |
May | 95294.23 | 2334294.70 | 19-MAY-14:40 | 26.02 | 21.10 | 3885.49 | 129640.20 | 22-MAY-13:10 |
June | 350345.24 | 3010988.12 | 20-JUN-13:05 | 27.45 | 22.97 | 1442.95 | 111239.88 | 02-JUN-05:03 |
July | 569065.98 | 2899512.57 | 19-JUL-08:43 | 27.21 | 22.58 | 1288.09 | 91875.68 | 08-JUL-08:30 |
August | 489072.35 | 2358260.50 | 07-AUG-11:30 | 26.07 | 21.31 | 1920.20 | 86963.23 | 30-AUG-07:50 |
September | 235097.67 | 4705455.64 | 07-SEP-15:03 | 31.02 | 25.46 | 2156.97 | 118612.50 | 16-SEP-05:50 |
October | 49794.75 | 2004671.74 | 18-OCT-13:45 | 25.33 | 21.10 | 2843.10 | 133381.16 | 11-OCT-05:30 |
November | 1688.33 | 258347.95 | 03-NOV-14:00 | 22.19 | 21.10 | 1738.94 | 142077.92 | 13-NOV-16:10 |
December | 13.73 | 10322.36 | 19-DEC-14:50 | 21.14 | 20.50 | 1555.50 | 132262.94 | 08-DEC-06:30 |
Annual Sum or Average | 153051.16 | 2193.78 | ||||||
Minimum of Months | 1.93 | 4043.23 | 21.12 | 20.19 | 476.07 | 86963.23 | ||
Maximum of Months | 569065.98 | 4705455.64 | 31.02 | 25.46 | 4174.83 | 145291.10 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.425978E+11 | 0.00 | 0.00 | 0.454071E+10 | 0.00 | 0.00 |
February | 0.197617E+11 | 0.00 | 0.829644E+09 | 0.512360E+10 | 0.00 | 0.00 |
March | 0.832697E+10 | 0.00 | 96048767.10 | 0.748535E+10 | 0.00 | 0.00 |
April | 0.101221E+10 | 0.00 | 0.723999E+10 | 0.952010E+10 | 0.00 | 0.00 |
May | 0.690566E+09 | 0.00 | 0.196788E+11 | 0.897271E+10 | 0.00 | 0.00 |
June | 7248846.77 | 0.00 | 0.656334E+11 | 0.150972E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.118398E+12 | 0.220628E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.101488E+12 | 0.209743E+11 | 0.00 | 0.00 |
September | 78405631.15 | 0.00 | 0.439599E+11 | 0.108199E+11 | 0.00 | 0.00 |
October | 0.796689E+09 | 0.00 | 0.115280E+11 | 0.851297E+10 | 0.00 | 0.00 |
November | 0.561443E+10 | 0.00 | 0.657276E+09 | 0.687185E+10 | 0.00 | 0.00 |
December | 0.211437E+11 | 0.00 | 0.00 | 0.590223E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.100030E+12 | 0.00 | 0.369509E+12 | 0.125884E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.454071E+10 | 0.00 | 0.00 |
Maximum of Months | 0.425978E+11 | 0.00 | 0.118398E+12 | 0.220628E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.682860E+12 | 0.00 | 39167.31 | 0.402730E+11 | 0.00 | 0.00 |
February | 0.349281E+12 | 0.00 | 0.697947E+10 | 0.380595E+11 | 0.00 | 0.00 |
March | 0.194140E+12 | 0.00 | 0.572049E+09 | 0.478333E+11 | 0.00 | 0.00 |
April | 0.444810E+11 | 0.00 | 0.526562E+11 | 0.535239E+11 | 0.00 | 0.00 |
May | 0.261605E+11 | 0.00 | 0.169393E+12 | 0.664234E+11 | 0.00 | 0.00 |
June | 0.527275E+09 | 0.00 | 0.541920E+12 | 0.108604E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.900239E+12 | 0.137047E+12 | 0.00 | 0.00 |
August | 75000990.75 | 0.00 | 0.782169E+12 | 0.131751E+12 | 0.00 | 0.00 |
September | 0.581470E+10 | 0.00 | 0.367892E+12 | 0.760956E+11 | 0.00 | 0.00 |
October | 0.338577E+11 | 0.00 | 0.912374E+11 | 0.540870E+11 | 0.00 | 0.00 |
November | 0.161451E+12 | 0.00 | 0.476004E+10 | 0.416434E+11 | 0.00 | 0.00 |
December | 0.427029E+12 | 0.00 | 67101.34 | 0.376885E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.192568E+13 | 0.00 | 0.291782E+13 | 0.833029E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 39167.31 | 0.376885E+11 | 0.00 | 0.00 |
Maximum of Months | 0.682860E+12 | 0.00 | 0.900239E+12 | 0.137047E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.107080E+12 | 0.00 | 171.26 | 0.491338E+10 | 0.00 | 0.00 |
February | 0.546830E+11 | 0.00 | 0.456340E+09 | 0.385949E+10 | 0.00 | 0.00 |
March | 0.358193E+11 | 0.00 | 8668216.63 | 0.437676E+10 | 0.00 | 0.00 |
April | 0.111561E+11 | 0.00 | 0.487962E+10 | 0.435640E+10 | 0.00 | 0.00 |
May | 0.744260E+10 | 0.00 | 0.174351E+11 | 0.571834E+10 | 0.00 | 0.00 |
June | 0.435986E+09 | 0.00 | 0.587930E+11 | 0.102298E+11 | 0.00 | 0.00 |
July | 2357079.44 | 0.00 | 0.984974E+11 | 0.136397E+11 | 0.00 | 0.00 |
August | 0.106226E+09 | 0.00 | 0.832925E+11 | 0.123979E+11 | 0.00 | 0.00 |
September | 0.259472E+10 | 0.00 | 0.373875E+11 | 0.647163E+10 | 0.00 | 0.00 |
October | 0.969585E+10 | 0.00 | 0.777640E+10 | 0.418548E+10 | 0.00 | 0.00 |
November | 0.326841E+11 | 0.00 | 0.352038E+09 | 0.392639E+10 | 0.00 | 0.00 |
December | 0.740481E+11 | 0.00 | 63966.67 | 0.456033E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.335749E+12 | 0.00 | 0.308879E+12 | 0.786356E+11 | 0.00 | 0.00 |
Minimum of Months | 2357079.44 | 0.00 | 171.26 | 0.385949E+10 | 0.00 | 0.00 |
Maximum of Months | 0.107080E+12 | 0.00 | 0.984974E+11 | 0.136397E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.156455E+11 | 0.00 | 2426094.96 | 0.377685E+10 | 0.00 | 0.00 |
February | 0.661082E+10 | 0.00 | 0.612397E+09 | 0.311083E+10 | 0.00 | 0.00 |
March | 0.227487E+10 | 0.00 | 0.607438E+09 | 0.459264E+10 | 0.00 | 0.00 |
April | 0.177998E+09 | 0.00 | 0.512983E+10 | 0.607964E+10 | 0.00 | 0.00 |
May | 30990785.06 | 0.00 | 0.138276E+11 | 0.804764E+10 | 0.00 | 0.00 |
June | 1357044.58 | 0.00 | 0.329090E+11 | 0.145376E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.362294E+11 | 0.108745E+11 | 0.00 | 0.00 |
August | 198.71 | 0.00 | 0.435176E+11 | 0.150001E+11 | 0.00 | 0.00 |
September | 3671610.89 | 0.00 | 0.236166E+11 | 0.127624E+11 | 0.00 | 0.00 |
October | 14018241.71 | 0.00 | 0.813891E+10 | 0.129006E+11 | 0.00 | 0.00 |
November | 0.320000E+09 | 0.00 | 0.270991E+09 | 0.107895E+11 | 0.00 | 0.00 |
December | 0.541498E+10 | 0.00 | 66662951.59 | 0.571616E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.304942E+11 | 0.00 | 0.164929E+12 | 0.108188E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 2426094.96 | 0.311083E+10 | 0.00 | 0.00 |
Maximum of Months | 0.156455E+11 | 0.00 | 0.435176E+11 | 0.150001E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.149562E+11 | 0.297365E+12 | 0.00 | 62.48 |
February | 0.00 | 0.00 | 0.200470E+11 | 0.354164E+12 | 0.00 | 87.69 |
March | 0.00 | 0.00 | 0.223789E+11 | 0.399263E+12 | 0.00 | 99.64 |
April | 0.00 | 0.00 | 0.777273E+11 | 0.398697E+12 | 0.00 | 95.95 |
May | 0.00 | 0.00 | 0.264018E+11 | 0.297410E+12 | 0.00 | 61.33 |
June | 0.00 | 0.00 | 0.175095E+12 | 0.306669E+12 | 0.00 | 52.27 |
July | 0.00 | 0.00 | 0.567427E+12 | 0.383973E+12 | 0.00 | 42.89 |
August | 0.00 | 0.00 | 0.699407E+12 | 0.490686E+12 | 0.00 | 71.38 |
September | 0.00 | 0.00 | 0.647845E+11 | 0.251792E+12 | 0.00 | 42.01 |
October | 0.00 | 0.00 | 0.319719E+11 | 0.382054E+12 | 0.00 | 92.40 |
November | 0.00 | 0.00 | 0.223070E+11 | 0.386526E+12 | 0.00 | 96.42 |
December | 0.00 | 0.00 | 0.230187E+11 | 0.399649E+12 | 0.00 | 99.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.174552E+13 | 0.434825E+13 | 0.00 | 904.09 |
Minimum of Months | 0.00 | 0.00 | 0.149562E+11 | 0.251792E+12 | 0.00 | 42.01 |
Maximum of Months | 0.00 | 0.00 | 0.699407E+12 | 0.490686E+12 | 0.00 | 99.64 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.416247E+10 | 0.265763E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.106404E+11 | 0.377750E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.188094E+11 | 0.546698E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.248830E+11 | 0.642099E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.731425E+10 | 0.328216E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.140113E+11 | 0.462568E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.216191E+11 | 0.648869E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.274533E+11 | 0.752685E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.748508E+10 | 0.329783E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.133233E+11 | 0.440517E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.183329E+11 | 0.528057E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.243966E+11 | 0.649457E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.192431E+12 | 0.597246E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.416247E+10 | 0.265763E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.274533E+11 | 0.752685E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.129776E+11 | 0.197287E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.781064E+11 | 0.315717E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.159016E+12 | 0.485806E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.225163E+12 | 0.593523E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.609831E+11 | 0.297023E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.129283E+12 | 0.434593E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.202876E+12 | 0.614109E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.259150E+12 | 0.715063E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.637266E+11 | 0.300694E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.112627E+12 | 0.394835E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.153543E+12 | 0.466757E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.201827E+12 | 0.566664E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.165928E+13 | 0.538207E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.129776E+11 | 0.197287E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.259150E+12 | 0.715063E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.375486E+09 | 0.178551E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.583030E+10 | 0.278191E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.139171E+11 | 0.451714E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.211807E+11 | 0.573764E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.522933E+10 | 0.282107E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.126827E+11 | 0.433418E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.202430E+11 | 0.617606E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.257648E+11 | 0.716870E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.570152E+10 | 0.290374E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.962174E+10 | 0.366721E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.130661E+11 | 0.427328E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.175583E+11 | 0.522152E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.151171E+12 | 0.513879E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.375486E+09 | 0.178551E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.257648E+11 | 0.716870E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.454071E+10 | 0.00 | 0.425978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.512360E+10 | 0.829644E+09 | 0.197617E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.748535E+10 | 96048767.10 | 0.832697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.952010E+10 | 0.723999E+10 | 0.101221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.897271E+10 | 0.196788E+11 | 0.690566E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.150972E+11 | 0.656334E+11 | 7248846.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.220628E+11 | 0.118398E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.209743E+11 | 0.101488E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.108199E+11 | 0.439599E+11 | 78405631.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.851297E+10 | 0.115280E+11 | 0.796689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.687185E+10 | 0.657276E+09 | 0.561443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.590223E+10 | 0.00 | 0.211437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125884E+12 | 0.369509E+12 | 0.100030E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.454071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.220628E+11 | 0.118398E+12 | 0.425978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.402730E+11 | 39167.31 | 0.682860E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.380595E+11 | 0.697947E+10 | 0.349281E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.478333E+11 | 0.572049E+09 | 0.194140E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.535239E+11 | 0.526562E+11 | 0.444810E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.664234E+11 | 0.169393E+12 | 0.261605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.108604E+12 | 0.541920E+12 | 0.527275E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137047E+12 | 0.900239E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.131751E+12 | 0.782169E+12 | 75000990.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.760956E+11 | 0.367892E+12 | 0.581470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.540870E+11 | 0.912374E+11 | 0.338577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.416434E+11 | 0.476004E+10 | 0.161451E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.376885E+11 | 67101.34 | 0.427029E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.833029E+12 | 0.291782E+13 | 0.192568E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.376885E+11 | 39167.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137047E+12 | 0.900239E+12 | 0.682860E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.491338E+10 | 171.26 | 0.107080E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.385949E+10 | 0.456340E+09 | 0.546830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.437676E+10 | 8668216.63 | 0.358193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.435640E+10 | 0.487962E+10 | 0.111561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.571834E+10 | 0.174351E+11 | 0.744260E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.102298E+11 | 0.587930E+11 | 0.435986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136397E+11 | 0.984974E+11 | 2357079.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.123979E+11 | 0.832925E+11 | 0.106226E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.647163E+10 | 0.373875E+11 | 0.259472E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.418548E+10 | 0.777640E+10 | 0.969585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.392639E+10 | 0.352038E+09 | 0.326841E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.456033E+10 | 63966.67 | 0.740481E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.786356E+11 | 0.308879E+12 | 0.335749E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.385949E+10 | 171.26 | 2357079.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136397E+11 | 0.984974E+11 | 0.107080E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.377685E+10 | 2426094.96 | 0.156455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.311083E+10 | 0.612397E+09 | 0.661082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.459264E+10 | 0.607438E+09 | 0.227487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.607964E+10 | 0.512983E+10 | 0.177998E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.804764E+10 | 0.138276E+11 | 30990785.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.145376E+11 | 0.329090E+11 | 1357044.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.108745E+11 | 0.362294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.150001E+11 | 0.435176E+11 | 198.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.127624E+11 | 0.236166E+11 | 3671610.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.129006E+11 | 0.813891E+10 | 14018241.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107895E+11 | 0.270991E+09 | 0.320000E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.571616E+10 | 66662951.59 | 0.541498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108188E+12 | 0.164929E+12 | 0.304942E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.311083E+10 | 2426094.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.150001E+11 | 0.435176E+11 | 0.156455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.123772E+12 | 0.932156E+10 | 0.00 | 0.00 | 0.00 | 0.167206E+12 | 0.00 | 0.00 |
February | 0.111794E+12 | 0.133897E+11 | 0.00 | 0.00 | 0.00 | 0.234657E+12 | 0.00 | 0.00 |
March | 0.123772E+12 | 0.147274E+11 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
April | 0.119779E+12 | 0.567507E+11 | 0.00 | 0.00 | 0.00 | 0.256785E+12 | 0.00 | 0.00 |
May | 0.123772E+12 | 0.176319E+11 | 0.00 | 0.00 | 0.00 | 0.164130E+12 | 0.00 | 0.00 |
June | 0.119779E+12 | 0.128729E+12 | 0.00 | 0.00 | 0.00 | 0.139894E+12 | 0.00 | 0.00 |
July | 0.123772E+12 | 0.422518E+12 | 0.00 | 0.00 | 0.00 | 0.114775E+12 | 0.00 | 0.00 |
August | 0.123772E+12 | 0.524374E+12 | 0.00 | 0.00 | 0.00 | 0.191021E+12 | 0.00 | 0.00 |
September | 0.119779E+12 | 0.456912E+11 | 0.00 | 0.00 | 0.00 | 0.112413E+12 | 0.00 | 0.00 |
October | 0.123772E+12 | 0.220698E+11 | 0.00 | 0.00 | 0.00 | 0.247267E+12 | 0.00 | 0.00 |
November | 0.119779E+12 | 0.147600E+11 | 0.00 | 0.00 | 0.00 | 0.258038E+12 | 0.00 | 0.00 |
December | 0.123772E+12 | 0.149816E+11 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.145732E+13 | 0.128494E+13 | 0.00 | 0.00 | 0.00 | 0.241946E+13 | 0.00 | 0.00 |
Minimum of Months | 0.111794E+12 | 0.932156E+10 | 0.00 | 0.00 | 0.00 | 0.112413E+12 | 0.00 | 0.00 |
Maximum of Months | 0.123772E+12 | 0.524374E+12 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.173201E+10 | 0.323685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.156440E+10 | 0.842734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173201E+10 | 0.150744E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167614E+10 | 0.201382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.173201E+10 | 0.576410E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.167614E+10 | 0.110618E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.173201E+10 | 0.168624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.173201E+10 | 0.216585E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167614E+10 | 0.586339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.173201E+10 | 0.106501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167614E+10 | 0.147285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.173201E+10 | 0.196341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203930E+11 | 0.153100E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.156440E+10 | 0.323685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.173201E+10 | 0.216585E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.166592E+11 | 0.990813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150471E+11 | 0.615817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166592E+11 | 0.127095E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161218E+11 | 0.181933E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.166592E+11 | 0.479401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.161218E+11 | 0.101946E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.166592E+11 | 0.158125E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.166592E+11 | 0.204303E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.161218E+11 | 0.497790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166592E+11 | 0.898030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.161218E+11 | 0.122989E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166592E+11 | 0.161820E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196149E+12 | 0.131722E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.150471E+11 | 0.990813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.166592E+11 | 0.204303E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.169455E+10 | 0.284527E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153056E+10 | 0.457896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169455E+10 | 0.110945E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163989E+10 | 0.170829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169455E+10 | 0.410281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.163989E+10 | 0.998846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.169455E+10 | 0.157615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169455E+10 | 0.202907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163989E+10 | 0.443767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169455E+10 | 0.764908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163989E+10 | 0.104327E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169455E+10 | 0.140314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199520E+11 | 0.119735E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.153056E+10 | 0.284527E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.169455E+10 | 0.202907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.454071E+10 | 0.425978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.512360E+10 | 0.197617E+11 | 0.829644E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.748535E+10 | 0.832697E+10 | 96048767.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.952010E+10 | 0.101221E+10 | 0.723999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.897271E+10 | 0.690566E+09 | 0.196788E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.150972E+11 | 7248846.77 | 0.656334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.220628E+11 | 0.00 | 0.118398E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.209743E+11 | 0.00 | 0.101488E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.108199E+11 | 78405631.15 | 0.439599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.851297E+10 | 0.796689E+09 | 0.115280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.687185E+10 | 0.561443E+10 | 0.657276E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.590223E+10 | 0.211437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125884E+12 | 0.100030E+12 | 0.369509E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.454071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.220628E+11 | 0.425978E+11 | 0.118398E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.402730E+11 | 0.682860E+12 | 39167.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.380595E+11 | 0.349281E+12 | 0.697947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.478333E+11 | 0.194140E+12 | 0.572049E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.535239E+11 | 0.444810E+11 | 0.526562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.664234E+11 | 0.261605E+11 | 0.169393E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.108604E+12 | 0.527275E+09 | 0.541920E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137047E+12 | 0.00 | 0.900239E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.131751E+12 | 75000990.75 | 0.782169E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.760956E+11 | 0.581470E+10 | 0.367892E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.540870E+11 | 0.338577E+11 | 0.912374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.416434E+11 | 0.161451E+12 | 0.476004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.376885E+11 | 0.427029E+12 | 67101.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.833029E+12 | 0.192568E+13 | 0.291782E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.376885E+11 | 0.00 | 39167.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137047E+12 | 0.682860E+12 | 0.900239E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.491338E+10 | 0.107080E+12 | 171.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.385949E+10 | 0.546830E+11 | 0.456340E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.437676E+10 | 0.358193E+11 | 8668216.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.435640E+10 | 0.111561E+11 | 0.487962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.571834E+10 | 0.744260E+10 | 0.174351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.102298E+11 | 0.435986E+09 | 0.587930E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.136397E+11 | 2357079.44 | 0.984974E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.123979E+11 | 0.106226E+09 | 0.832925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.647163E+10 | 0.259472E+10 | 0.373875E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.418548E+10 | 0.969585E+10 | 0.777640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.392639E+10 | 0.326841E+11 | 0.352038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.456033E+10 | 0.740481E+11 | 63966.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.786356E+11 | 0.335749E+12 | 0.308879E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.385949E+10 | 2357079.44 | 171.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.136397E+11 | 0.107080E+12 | 0.984974E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.377685E+10 | 0.156455E+11 | 2426094.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.311083E+10 | 0.661082E+10 | 0.612397E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.459264E+10 | 0.227487E+10 | 0.607438E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.607964E+10 | 0.177998E+09 | 0.512983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.804764E+10 | 30990785.06 | 0.138276E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.145376E+11 | 1357044.58 | 0.329090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.108745E+11 | 0.00 | 0.362294E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.150001E+11 | 198.71 | 0.435176E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.127624E+11 | 3671610.89 | 0.236166E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.129006E+11 | 14018241.71 | 0.813891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.107895E+11 | 0.320000E+09 | 0.270991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.571616E+10 | 0.541498E+10 | 66662951.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.108188E+12 | 0.304942E+11 | 0.164929E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.311083E+10 | 0.00 | 2426094.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.150001E+11 | 0.156455E+11 | 0.435176E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.123772E+12 | 0.00 | 0.149562E+11 | 0.00 | 0.563467E+10 | 0.00 | 0.00 | 0.00 | 0.167958E+12 | 0.00 | 0.00 | 0.00 |
February | 0.111794E+12 | 0.00 | 0.200470E+11 | 0.00 | 0.665729E+10 | 0.00 | 0.00 | 0.00 | 0.235713E+12 | 0.00 | 0.00 | 0.00 |
March | 0.123772E+12 | 0.00 | 0.223789E+11 | 0.00 | 0.765149E+10 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
April | 0.119779E+12 | 0.00 | 0.777273E+11 | 0.00 | 0.209766E+11 | 0.00 | 0.00 | 0.00 | 0.257941E+12 | 0.00 | 0.00 | 0.00 |
May | 0.123772E+12 | 0.00 | 0.264018E+11 | 0.00 | 0.876987E+10 | 0.00 | 0.00 | 0.00 | 0.164869E+12 | 0.00 | 0.00 | 0.00 |
June | 0.119779E+12 | 0.00 | 0.175095E+12 | 0.00 | 0.463661E+11 | 0.00 | 0.00 | 0.00 | 0.140523E+12 | 0.00 | 0.00 | 0.00 |
July | 0.123772E+12 | 0.00 | 0.567427E+12 | 0.00 | 0.144909E+12 | 0.00 | 0.00 | 0.00 | 0.115292E+12 | 0.00 | 0.00 | 0.00 |
August | 0.123772E+12 | 0.00 | 0.699407E+12 | 0.00 | 0.175033E+12 | 0.00 | 0.00 | 0.00 | 0.191881E+12 | 0.00 | 0.00 | 0.00 |
September | 0.119779E+12 | 0.00 | 0.647845E+11 | 0.00 | 0.190933E+11 | 0.00 | 0.00 | 0.00 | 0.112919E+12 | 0.00 | 0.00 | 0.00 |
October | 0.123772E+12 | 0.00 | 0.319719E+11 | 0.00 | 0.990214E+10 | 0.00 | 0.00 | 0.00 | 0.248380E+12 | 0.00 | 0.00 | 0.00 |
November | 0.119779E+12 | 0.00 | 0.223070E+11 | 0.00 | 0.754706E+10 | 0.00 | 0.00 | 0.00 | 0.259199E+12 | 0.00 | 0.00 | 0.00 |
December | 0.123772E+12 | 0.00 | 0.230187E+11 | 0.00 | 0.803717E+10 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145732E+13 | 0.00 | 0.174552E+13 | 0.00 | 0.460578E+12 | 0.00 | 0.00 | 0.00 | 0.243035E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.111794E+12 | 0.00 | 0.149562E+11 | 0.00 | 0.563467E+10 | 0.00 | 0.00 | 0.00 | 0.112919E+12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.123772E+12 | 0.00 | 0.699407E+12 | 0.00 | 0.175033E+12 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.173201E+10 | 0.00 | 0.416247E+10 | 0.00 | 0.925622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.156440E+10 | 0.00 | 0.106404E+11 | 0.00 | 0.221311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173201E+10 | 0.00 | 0.188094E+11 | 0.00 | 0.373497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167614E+10 | 0.00 | 0.248830E+11 | 0.00 | 0.474485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.173201E+10 | 0.00 | 0.731425E+10 | 0.00 | 0.155015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.167614E+10 | 0.00 | 0.140113E+11 | 0.00 | 0.294954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.173201E+10 | 0.00 | 0.216191E+11 | 0.00 | 0.475667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.173201E+10 | 0.00 | 0.274533E+11 | 0.00 | 0.579484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167614E+10 | 0.00 | 0.748508E+10 | 0.00 | 0.162169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.173201E+10 | 0.00 | 0.133233E+11 | 0.00 | 0.267316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167614E+10 | 0.00 | 0.183329E+11 | 0.00 | 0.360443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.173201E+10 | 0.00 | 0.243966E+11 | 0.00 | 0.476255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203930E+11 | 0.00 | 0.192431E+12 | 0.00 | 0.393316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.156440E+10 | 0.00 | 0.416247E+10 | 0.00 | 0.925622E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.173201E+10 | 0.00 | 0.274533E+11 | 0.00 | 0.579484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.166592E+11 | 0.00 | 0.129776E+11 | 0.00 | 0.306943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150471E+11 | 0.00 | 0.781064E+11 | 0.00 | 0.165247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166592E+11 | 0.00 | 0.159016E+12 | 0.00 | 0.319214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.161218E+11 | 0.00 | 0.225163E+12 | 0.00 | 0.432304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.166592E+11 | 0.00 | 0.609831E+11 | 0.00 | 0.130430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.161218E+11 | 0.00 | 0.129283E+12 | 0.00 | 0.273375E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.166592E+11 | 0.00 | 0.202876E+12 | 0.00 | 0.447517E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.166592E+11 | 0.00 | 0.259150E+12 | 0.00 | 0.548470E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.161218E+11 | 0.00 | 0.637266E+11 | 0.00 | 0.139476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166592E+11 | 0.00 | 0.112627E+12 | 0.00 | 0.228242E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.161218E+11 | 0.00 | 0.153543E+12 | 0.00 | 0.305538E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166592E+11 | 0.00 | 0.201827E+12 | 0.00 | 0.400072E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196149E+12 | 0.00 | 0.165928E+13 | 0.00 | 0.342058E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.150471E+11 | 0.00 | 0.129776E+11 | 0.00 | 0.306943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.166592E+11 | 0.00 | 0.259150E+12 | 0.00 | 0.548470E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.169455E+10 | 0.00 | 0.375486E+09 | 0.00 | 90959335.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153056E+10 | 0.00 | 0.583030E+10 | 0.00 | 0.125134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.169455E+10 | 0.00 | 0.139171E+11 | 0.00 | 0.282259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163989E+10 | 0.00 | 0.211807E+11 | 0.00 | 0.409775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169455E+10 | 0.00 | 0.522933E+10 | 0.00 | 0.112651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.163989E+10 | 0.00 | 0.126827E+11 | 0.00 | 0.269429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.169455E+10 | 0.00 | 0.202430E+11 | 0.00 | 0.448151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.169455E+10 | 0.00 | 0.257648E+11 | 0.00 | 0.547415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163989E+10 | 0.00 | 0.570152E+10 | 0.00 | 0.126385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169455E+10 | 0.00 | 0.962174E+10 | 0.00 | 0.197266E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163989E+10 | 0.00 | 0.130661E+11 | 0.00 | 0.263339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169455E+10 | 0.00 | 0.175583E+11 | 0.00 | 0.352697E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.199520E+11 | 0.00 | 0.151171E+12 | 0.00 | 0.314360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.153056E+10 | 0.00 | 0.375486E+09 | 0.00 | 90959335.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.169455E+10 | 0.00 | 0.257648E+11 | 0.00 | 0.547415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 84767636.41 | 0.00 | 0.00 | 0.669777E+11 | 0.00 | 0.39 |
February | 0.00 | 0.00 | 0.00 | 86358884.44 | 0.00 | 0.00 | 0.544709E+11 | 0.00 | 0.46 |
March | 0.00 | 0.00 | 0.00 | 0.104274E+09 | 0.00 | 0.00 | 0.635256E+11 | 0.00 | 0.55 |
April | 0.00 | 0.00 | 0.00 | 0.100466E+09 | 0.00 | 0.00 | 0.563342E+11 | 0.00 | 0.72 |
May | 0.00 | 38815805.11 | 0.00 | 0.106242E+09 | 0.00 | 0.00 | 0.524561E+11 | 0.00 | 0.83 |
June | 0.00 | 0.417707E+09 | 0.00 | 0.121197E+09 | 0.00 | 0.00 | 0.422384E+11 | 0.00 | 1.07 |
July | 0.00 | 0.194264E+09 | 0.00 | 0.142854E+09 | 0.00 | 0.00 | 0.225097E+11 | 0.00 | 0.69 |
August | 0.00 | 0.302077E+09 | 0.00 | 0.131768E+09 | 0.00 | 0.00 | 0.344767E+11 | 0.00 | 1.02 |
September | 0.00 | 0.675076E+09 | 0.00 | 0.130525E+09 | 0.00 | 0.00 | 0.500865E+11 | 0.00 | 1.05 |
October | 0.00 | 0.00 | 0.00 | 0.130337E+09 | 0.00 | 0.00 | 0.677762E+11 | 0.00 | 0.99 |
November | 0.00 | 0.00 | 0.00 | 0.111558E+09 | 0.00 | 0.00 | 0.692967E+11 | 0.00 | 0.76 |
December | 0.00 | 0.00 | 0.00 | 98268148.13 | 0.00 | 0.00 | 0.650778E+11 | 0.00 | 0.47 |
Annual Sum or Average | 0.00 | 0.162794E+10 | 0.00 | 0.134861E+10 | 0.00 | 0.00 | 0.645226E+12 | 0.00 | 0.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 84767636.41 | 0.00 | 0.00 | 0.225097E+11 | 0.00 | 0.39 |
Maximum of Months | 0.00 | 0.675076E+09 | 0.00 | 0.142854E+09 | 0.00 | 0.00 | 0.692967E+11 | 0.00 | 1.07 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.152582E+11 | 0.00 | 0.00 | 49181233.50 | 0.00 | 0.00 | 0.443242E+11 | 0.00 | 0.34 |
February | 0.647130E+10 | 0.00 | 0.00 | 65470616.70 | 0.00 | 0.00 | 0.461679E+11 | 0.00 | 0.44 |
March | 0.314066E+10 | 0.00 | 0.00 | 97243528.02 | 0.00 | 0.00 | 0.608990E+11 | 0.00 | 0.55 |
April | 0.412793E+10 | 0.00 | 0.00 | 0.100738E+09 | 0.00 | 0.00 | 0.582900E+11 | 0.00 | 0.79 |
May | 0.246639E+10 | 16406533.30 | 0.00 | 91441454.46 | 7658153.41 | 0.00 | 0.499957E+11 | 0.00 | 0.80 |
June | 0.379042E+10 | 0.269743E+09 | 0.00 | 0.106597E+09 | 13461756.94 | 0.00 | 0.403893E+11 | 0.00 | 1.07 |
July | 0.705561E+10 | 0.565824E+09 | 0.00 | 0.126138E+09 | 64448552.25 | 0.00 | 0.257318E+11 | 0.00 | 1.07 |
August | 0.777728E+10 | 0.345543E+09 | 0.00 | 0.127047E+09 | 47786634.58 | 0.00 | 0.354869E+11 | 0.00 | 1.18 |
September | 0.245024E+10 | 0.538420E+09 | 0.00 | 99224733.20 | 34948701.23 | 0.00 | 0.429510E+11 | 0.00 | 0.91 |
October | 0.228714E+10 | 0.00 | 0.00 | 0.102108E+09 | 0.00 | 0.00 | 0.548547E+11 | 0.00 | 0.79 |
November | 0.253815E+10 | 0.00 | 0.00 | 92141868.92 | 0.00 | 0.00 | 0.566093E+11 | 0.00 | 0.60 |
December | 0.331830E+10 | 0.00 | 0.00 | 83136157.55 | 0.00 | 0.00 | 0.590741E+11 | 0.00 | 0.43 |
Annual Sum or Average | 0.606816E+11 | 0.173594E+10 | 0.00 | 0.114047E+10 | 0.168304E+09 | 0.00 | 0.574774E+12 | 0.00 | 0.75 |
Minimum of Months | 0.228714E+10 | 0.00 | 0.00 | 49181233.50 | 0.00 | 0.00 | 0.257318E+11 | 0.00 | 0.34 |
Maximum of Months | 0.152582E+11 | 0.565824E+09 | 0.00 | 0.127047E+09 | 64448552.25 | 0.00 | 0.608990E+11 | 0.00 | 1.18 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.386363E+12 | 0.00 | 0.00 | 50708820.85 | 0.00 | 0.596828E+10 | 0.904012E+11 | 0.00 | 0.28 |
February | 0.260634E+12 | 0.00 | 0.00 | 0.145230E+09 | 0.00 | 0.113992E+10 | 0.131180E+12 | 0.00 | 0.33 |
March | 0.178342E+12 | 0.00 | 0.00 | 0.341325E+09 | 0.00 | 0.331507E+09 | 0.267318E+12 | 0.00 | 0.38 |
April | 0.799703E+11 | 0.00 | 0.00 | 0.462214E+09 | 0.00 | 0.00 | 0.320965E+12 | 0.00 | 0.52 |
May | 0.447324E+11 | 0.174515E+09 | 0.00 | 0.570583E+09 | 86591749.31 | 0.00 | 0.351248E+12 | 0.00 | 0.63 |
June | 0.278200E+11 | 0.267281E+10 | 0.00 | 0.733840E+09 | 0.120345E+09 | 0.00 | 0.296674E+12 | 0.00 | 0.81 |
July | 0.248949E+11 | 0.595188E+10 | 0.00 | 0.728342E+09 | 0.272888E+09 | 0.00 | 0.163056E+12 | 0.00 | 0.68 |
August | 0.210706E+11 | 0.396605E+10 | 0.00 | 0.823295E+09 | 0.478195E+09 | 0.00 | 0.245582E+12 | 0.00 | 0.78 |
September | 0.281684E+11 | 0.453744E+10 | 0.00 | 0.637692E+09 | 0.387219E+09 | 0.00 | 0.305533E+12 | 0.00 | 0.69 |
October | 0.663835E+11 | 0.00 | 0.00 | 0.504165E+09 | 0.00 | 0.00 | 0.322259E+12 | 0.00 | 0.55 |
November | 0.161232E+12 | 0.00 | 0.00 | 0.303314E+09 | 0.00 | 56095120.66 | 0.224082E+12 | 0.00 | 0.39 |
December | 0.292034E+12 | 0.00 | 0.00 | 0.142554E+09 | 0.00 | 0.135581E+09 | 0.136462E+12 | 0.00 | 0.29 |
Annual Sum or Average | 0.157164E+13 | 0.173027E+11 | 0.00 | 0.544326E+10 | 0.134524E+10 | 0.763139E+10 | 0.285476E+13 | 0.00 | 0.53 |
Minimum of Months | 0.210706E+11 | 0.00 | 0.00 | 50708820.85 | 0.00 | 0.00 | 0.904012E+11 | 0.00 | 0.28 |
Maximum of Months | 0.386363E+12 | 0.595188E+10 | 0.00 | 0.823295E+09 | 0.478195E+09 | 0.596828E+10 | 0.351248E+12 | 0.00 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.312891E+11 | 0.00 | 0.00 | 20083.97 | 0.00 | 0.991071E+10 | 84609545.32 | 0.00 | 0.26 |
February | 0.286304E+11 | 0.00 | 0.00 | 1032533.69 | 0.00 | 0.321130E+10 | 0.163450E+10 | 0.00 | 0.29 |
March | 0.264296E+11 | 0.00 | 0.00 | 6864829.28 | 0.00 | 0.201107E+10 | 0.789286E+10 | 0.00 | 0.32 |
April | 0.158208E+11 | 0.00 | 0.00 | 20506824.10 | 0.00 | 25339956.13 | 0.170781E+11 | 0.00 | 0.45 |
May | 0.106771E+11 | 10353548.55 | 0.00 | 36093792.51 | 5731012.66 | 0.249792E+09 | 0.242150E+11 | 0.00 | 0.58 |
June | 0.502828E+10 | 0.181891E+09 | 0.00 | 64052127.23 | 12459334.10 | 0.00 | 0.254533E+11 | 0.00 | 0.82 |
July | 0.335263E+10 | 0.380669E+09 | 0.00 | 71408851.58 | 23535710.45 | 0.00 | 0.142889E+11 | 0.00 | 0.69 |
August | 0.356202E+10 | 0.242991E+09 | 0.00 | 75864289.97 | 38986210.54 | 0.00 | 0.200972E+11 | 0.00 | 0.76 |
September | 0.807966E+10 | 0.431501E+09 | 0.00 | 41063960.83 | 29269035.81 | 0.00 | 0.195123E+11 | 0.00 | 0.62 |
October | 0.160094E+11 | 0.00 | 0.00 | 18419102.83 | 0.00 | 0.176814E+09 | 0.135707E+11 | 0.00 | 0.45 |
November | 0.230471E+11 | 0.00 | 0.00 | 4846986.00 | 0.00 | 0.172091E+10 | 0.507972E+10 | 0.00 | 0.32 |
December | 0.294031E+11 | 0.00 | 0.00 | 924275.48 | 0.00 | 0.544508E+10 | 0.122593E+10 | 0.00 | 0.27 |
Annual Sum or Average | 0.201329E+12 | 0.124741E+10 | 0.00 | 0.341098E+09 | 0.109981E+09 | 0.227510E+11 | 0.150133E+12 | 0.00 | 0.49 |
Minimum of Months | 0.335263E+10 | 0.00 | 0.00 | 20083.97 | 0.00 | 0.00 | 84609545.32 | 0.00 | 0.26 |
Maximum of Months | 0.312891E+11 | 0.431501E+09 | 0.00 | 75864289.97 | 38986210.54 | 0.991071E+10 | 0.254533E+11 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.288331E+10 | 0.00 | 0.00 | 73488.78 | 0.00 | 0.301345E+10 | 90162961.54 | 0.00 | 0.26 |
February | 0.326370E+10 | 0.00 | 0.00 | 495249.46 | 0.00 | 0.100394E+10 | 0.459410E+09 | 0.00 | 0.31 |
March | 0.311569E+10 | 0.00 | 0.00 | 2473747.29 | 0.00 | 0.180492E+09 | 0.208740E+10 | 0.00 | 0.37 |
April | 0.198395E+10 | 0.00 | 0.00 | 5464570.34 | 0.00 | 0.00 | 0.386002E+10 | 0.00 | 0.64 |
May | 0.124813E+10 | 5120069.47 | 0.00 | 7812635.45 | 963225.57 | 0.00 | 0.446074E+10 | 0.00 | 0.79 |
June | 0.668095E+09 | 52851486.52 | 0.00 | 14522011.69 | 1693189.97 | 0.00 | 0.526983E+10 | 0.00 | 1.27 |
July | 0.960058E+09 | 0.106315E+09 | 0.00 | 18713156.82 | 6288112.68 | 0.00 | 0.346228E+10 | 0.00 | 1.26 |
August | 0.118641E+10 | 73798889.71 | 0.00 | 15543048.14 | 6010497.05 | 0.00 | 0.399872E+10 | 0.00 | 1.26 |
September | 0.118534E+10 | 93312904.32 | 0.00 | 7760883.46 | 4395770.23 | 0.00 | 0.334646E+10 | 0.00 | 0.82 |
October | 0.210038E+10 | 0.00 | 0.00 | 4216199.34 | 0.00 | 0.00 | 0.279306E+10 | 0.00 | 0.57 |
November | 0.317890E+10 | 0.00 | 0.00 | 1538105.26 | 0.00 | 47284723.26 | 0.137602E+10 | 0.00 | 0.37 |
December | 0.378308E+10 | 0.00 | 0.00 | 350290.46 | 0.00 | 0.822257E+09 | 0.376163E+09 | 0.00 | 0.27 |
Annual Sum or Average | 0.255570E+11 | 0.331399E+09 | 0.00 | 78963386.50 | 19350795.50 | 0.506743E+10 | 0.315803E+11 | 0.00 | 0.68 |
Minimum of Months | 0.668095E+09 | 0.00 | 0.00 | 73488.78 | 0.00 | 0.00 | 90162961.54 | 0.00 | 0.26 |
Maximum of Months | 0.378308E+10 | 0.106315E+09 | 0.00 | 18713156.82 | 6288112.68 | 0.301345E+10 | 0.526983E+10 | 0.00 | 1.27 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.407701E+10 | 0.00 | 0.00 | 273386.54 | 0.00 | 0.317510E+10 | 0.242830E+09 | 0.00 | 0.52 |
February | 0.384903E+10 | 0.00 | 0.00 | 1676883.14 | 0.00 | 0.130578E+10 | 0.103362E+10 | 0.00 | 0.64 |
March | 0.403947E+10 | 0.00 | 0.00 | 4364855.94 | 0.00 | 0.319564E+09 | 0.285498E+10 | 0.00 | 0.75 |
April | 0.292811E+10 | 0.00 | 0.00 | 7761454.49 | 0.00 | 4561674.30 | 0.470374E+10 | 0.00 | 1.21 |
May | 0.188043E+10 | 3539873.18 | 0.00 | 9569261.62 | 1219502.09 | 0.00 | 0.567422E+10 | 0.00 | 1.48 |
June | 0.105064E+10 | 43778491.54 | 0.00 | 18774619.04 | 2143681.36 | 0.00 | 0.597418E+10 | 0.00 | 2.25 |
July | 0.130006E+10 | 0.100160E+09 | 0.00 | 23081568.29 | 10262936.77 | 0.00 | 0.432350E+10 | 0.00 | 2.35 |
August | 0.184040E+10 | 66095921.83 | 0.00 | 15529240.31 | 7485009.60 | 0.00 | 0.461444E+10 | 0.00 | 2.28 |
September | 0.174776E+10 | 69972856.58 | 0.00 | 9771201.43 | 5305568.16 | 0.00 | 0.405876E+10 | 0.00 | 1.53 |
October | 0.275609E+10 | 0.00 | 0.00 | 5639369.99 | 0.00 | 442529.51 | 0.332720E+10 | 0.00 | 1.04 |
November | 0.410827E+10 | 0.00 | 0.00 | 1471678.78 | 0.00 | 0.197057E+09 | 0.136637E+10 | 0.00 | 0.69 |
December | 0.453751E+10 | 0.00 | 0.00 | 269762.70 | 0.00 | 0.152984E+10 | 0.221177E+09 | 0.00 | 0.52 |
Annual Sum or Average | 0.341148E+11 | 0.283547E+09 | 0.00 | 98183282.28 | 26416697.98 | 0.653234E+10 | 0.383950E+11 | 0.00 | 1.27 |
Minimum of Months | 0.105064E+10 | 0.00 | 0.00 | 269762.70 | 0.00 | 0.00 | 0.221177E+09 | 0.00 | 0.52 |
Maximum of Months | 0.453751E+10 | 0.100160E+09 | 0.00 | 23081568.29 | 10262936.77 | 0.317510E+10 | 0.597418E+10 | 0.00 | 2.35 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.417443E+10 | 0.00 | 0.00 | 6026529.36 | 0.00 | 0.332880E+10 | 0.411099E+10 | 0.00 | 0.54 |
February | 0.349890E+10 | 0.00 | 0.00 | 13528741.72 | 0.00 | 0.105735E+10 | 0.682631E+10 | 0.00 | 0.87 |
March | 0.406517E+10 | 0.00 | 0.00 | 14120585.39 | 0.00 | 0.347636E+09 | 0.884724E+10 | 0.00 | 0.98 |
April | 0.324850E+10 | 0.00 | 0.00 | 13746723.94 | 0.00 | 12381990.98 | 0.796145E+10 | 0.00 | 1.29 |
May | 0.244005E+10 | 7282064.48 | 0.00 | 12387653.02 | 1485000.15 | 43419303.54 | 0.685668E+10 | 0.00 | 1.30 |
June | 0.155433E+10 | 76065326.36 | 0.00 | 17484453.06 | 2610382.69 | 0.00 | 0.578783E+10 | 0.00 | 1.64 |
July | 0.169465E+10 | 0.162803E+09 | 0.00 | 21767473.81 | 8492208.50 | 0.00 | 0.375783E+10 | 0.00 | 1.64 |
August | 0.209611E+10 | 0.144230E+09 | 0.00 | 27036500.25 | 5598532.92 | 0.00 | 0.547922E+10 | 0.00 | 1.98 |
September | 0.178950E+10 | 0.209608E+09 | 0.00 | 20626398.60 | 1508104.09 | 0.00 | 0.729500E+10 | 0.00 | 1.76 |
October | 0.240596E+10 | 0.00 | 0.00 | 20588581.78 | 0.00 | 14506003.15 | 0.100292E+11 | 0.00 | 1.55 |
November | 0.342678E+10 | 0.00 | 0.00 | 13359371.52 | 0.00 | 0.275587E+09 | 0.777066E+10 | 0.00 | 0.96 |
December | 0.408974E+10 | 0.00 | 0.00 | 7210475.05 | 0.00 | 0.142259E+10 | 0.496668E+10 | 0.00 | 0.60 |
Annual Sum or Average | 0.344841E+11 | 0.599988E+09 | 0.00 | 0.187883E+09 | 19694228.34 | 0.650227E+10 | 0.796891E+11 | 0.00 | 1.26 |
Minimum of Months | 0.155433E+10 | 0.00 | 0.00 | 6026529.36 | 0.00 | 0.00 | 0.375783E+10 | 0.00 | 0.54 |
Maximum of Months | 0.417443E+10 | 0.209608E+09 | 0.00 | 27036500.25 | 8492208.50 | 0.332880E+10 | 0.100292E+11 | 0.00 | 1.98 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.583615E+10 | 0.00 | 0.00 | 469122.92 | 0.00 | 0.283140E+10 | 0.508342E+09 | 0.00 | 0.63 |
February | 0.508540E+10 | 0.00 | 0.00 | 3483307.63 | 0.00 | 0.237850E+09 | 0.255063E+10 | 0.00 | 0.84 |
March | 0.320445E+10 | 0.00 | 0.00 | 8139616.18 | 0.00 | 25356255.28 | 0.635521E+10 | 0.00 | 1.05 |
April | 0.112256E+10 | 0.00 | 0.00 | 17204767.69 | 0.00 | 0.00 | 0.947350E+10 | 0.00 | 1.86 |
May | 0.166348E+10 | 5683473.59 | 0.00 | 13778656.12 | 1486679.86 | 0.00 | 0.707091E+10 | 0.00 | 1.84 |
June | 0.784893E+09 | 77215512.30 | 0.00 | 21984106.64 | 504410.89 | 0.00 | 0.659074E+10 | 0.00 | 2.51 |
July | 0.112539E+10 | 0.156075E+09 | 0.00 | 26221234.55 | 7288481.39 | 0.00 | 0.433902E+10 | 0.00 | 2.44 |
August | 0.123067E+10 | 0.113603E+09 | 0.00 | 26598156.76 | 1818367.45 | 0.00 | 0.621718E+10 | 0.00 | 2.81 |
September | 0.154229E+10 | 0.152752E+09 | 0.00 | 10706993.19 | 761265.48 | 0.00 | 0.472872E+10 | 0.00 | 1.76 |
October | 0.198757E+10 | 0.00 | 0.00 | 9116496.11 | 0.00 | 0.00 | 0.588404E+10 | 0.00 | 1.44 |
November | 0.317981E+10 | 0.00 | 0.00 | 5671927.73 | 0.00 | 886359.62 | 0.471364E+10 | 0.00 | 1.01 |
December | 0.514393E+10 | 0.00 | 0.00 | 3223158.04 | 0.00 | 54114026.50 | 0.301539E+10 | 0.00 | 0.70 |
Annual Sum or Average | 0.319066E+11 | 0.505329E+09 | 0.00 | 0.146598E+09 | 11859205.08 | 0.314961E+10 | 0.614473E+11 | 0.00 | 1.58 |
Minimum of Months | 0.784893E+09 | 0.00 | 0.00 | 469122.92 | 0.00 | 0.00 | 0.508342E+09 | 0.00 | 0.63 |
Maximum of Months | 0.583615E+10 | 0.156075E+09 | 0.00 | 26598156.76 | 7288481.39 | 0.283140E+10 | 0.947350E+10 | 0.00 | 2.81 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.819850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.640513E+11 | 0.00 | 0.00 | 0.32 |
February | 0.163574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336127E+11 | 0.00 | 0.00 | 0.32 |
March | 0.328766E+11 | 0.00 | 0.00 | 865842.78 | 0.00 | 0.151257E+11 | 0.136200E+10 | 0.00 | 0.32 |
April | 0.268977E+11 | 0.00 | 0.00 | 13966928.54 | 0.00 | 0.256207E+10 | 0.103990E+11 | 0.00 | 0.42 |
May | 0.192567E+11 | 57755233.93 | 0.00 | 42756924.61 | 10904221.46 | 0.145211E+10 | 0.229161E+11 | 0.00 | 0.61 |
June | 0.796633E+10 | 0.569458E+09 | 0.00 | 0.100418E+09 | 14917871.52 | 0.00 | 0.356187E+11 | 0.00 | 0.98 |
July | 0.459076E+10 | 0.141295E+10 | 0.00 | 0.111370E+09 | 34444351.76 | 0.00 | 0.213178E+11 | 0.00 | 0.85 |
August | 0.800702E+10 | 0.997927E+09 | 0.00 | 91841756.43 | 60217615.88 | 0.00 | 0.229459E+11 | 0.00 | 0.84 |
September | 0.181819E+11 | 0.821757E+09 | 0.00 | 39780146.10 | 47475858.69 | 0.364049E+09 | 0.152181E+11 | 0.00 | 0.61 |
October | 0.287727E+11 | 0.00 | 0.00 | 9570943.18 | 0.00 | 0.240422E+10 | 0.666405E+10 | 0.00 | 0.42 |
November | 0.262289E+11 | 0.00 | 0.00 | 45002.63 | 0.00 | 0.160063E+11 | 0.319375E+09 | 0.00 | 0.33 |
December | 0.133273E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418598E+11 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.210662E+12 | 0.385985E+10 | 0.00 | 0.410616E+09 | 0.167960E+09 | 0.177438E+12 | 0.136761E+12 | 0.00 | 0.53 |
Minimum of Months | 0.459076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.328766E+11 | 0.141295E+10 | 0.00 | 0.111370E+09 | 60217615.88 | 0.640513E+11 | 0.356187E+11 | 0.00 | 0.98 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.193338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.649935E+11 | 0.00 | 0.00 | 0.60 |
February | 0.271031E+11 | 0.00 | 0.00 | 5362638.51 | 0.00 | 0.358539E+11 | 0.349761E+10 | 0.00 | 0.68 |
March | 0.383924E+11 | 0.00 | 0.00 | 23408947.65 | 0.00 | 0.173362E+11 | 0.159754E+11 | 0.00 | 0.74 |
April | 0.292800E+11 | 0.00 | 0.00 | 59585422.23 | 0.00 | 0.280217E+10 | 0.357497E+11 | 0.00 | 1.09 |
May | 0.223604E+11 | 43474442.77 | 0.00 | 79217939.71 | 15006395.25 | 0.189086E+10 | 0.463378E+11 | 0.00 | 1.42 |
June | 0.108814E+11 | 0.545254E+09 | 0.00 | 0.183344E+09 | 17300696.21 | 0.00 | 0.540176E+11 | 0.00 | 2.16 |
July | 0.608531E+10 | 0.132801E+10 | 0.00 | 0.218696E+09 | 47402334.81 | 0.00 | 0.391586E+11 | 0.00 | 2.08 |
August | 0.111466E+11 | 0.107039E+10 | 0.00 | 0.142408E+09 | 82733024.20 | 0.00 | 0.417491E+11 | 0.00 | 2.01 |
September | 0.222797E+11 | 0.759690E+09 | 0.00 | 76744008.10 | 64352879.64 | 0.380189E+09 | 0.302045E+11 | 0.00 | 1.40 |
October | 0.340174E+11 | 0.00 | 0.00 | 28967554.50 | 0.00 | 0.223899E+10 | 0.188489E+11 | 0.00 | 0.96 |
November | 0.365712E+11 | 0.00 | 0.00 | 3155016.63 | 0.00 | 0.189547E+11 | 0.256046E+10 | 0.00 | 0.70 |
December | 0.251118E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463209E+11 | 0.00 | 0.00 | 0.59 |
Annual Sum or Average | 0.282563E+12 | 0.374682E+10 | 0.00 | 0.820889E+09 | 0.226795E+09 | 0.190772E+12 | 0.288100E+12 | 0.00 | 1.21 |
Minimum of Months | 0.608531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Maximum of Months | 0.383924E+11 | 0.132801E+10 | 0.00 | 0.218696E+09 | 82733024.20 | 0.649935E+11 | 0.540176E+11 | 0.00 | 2.16 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.300942E+11 | 0.00 | 0.00 | 47121866.71 | 0.00 | 0.544723E+11 | 0.355518E+11 | 0.00 | 0.56 |
February | 0.292286E+11 | 0.00 | 0.00 | 0.133830E+09 | 0.00 | 0.243408E+11 | 0.612136E+11 | 0.00 | 0.89 |
March | 0.385411E+11 | 0.00 | 0.00 | 0.131153E+09 | 0.00 | 0.130045E+11 | 0.776827E+11 | 0.00 | 0.96 |
April | 0.314544E+11 | 0.00 | 0.00 | 0.117273E+09 | 0.00 | 0.291439E+10 | 0.636262E+11 | 0.00 | 1.16 |
May | 0.260217E+11 | 92570937.34 | 0.00 | 0.111422E+09 | 17358033.80 | 0.229126E+10 | 0.582954E+11 | 0.00 | 1.23 |
June | 0.173338E+11 | 0.920701E+09 | 0.00 | 0.143510E+09 | 10356055.78 | 0.00 | 0.455990E+11 | 0.00 | 1.45 |
July | 0.103628E+11 | 0.231156E+10 | 0.00 | 0.166351E+09 | 16767682.86 | 0.00 | 0.276730E+11 | 0.00 | 1.29 |
August | 0.132324E+11 | 0.233216E+10 | 0.00 | 0.226881E+09 | 66183782.25 | 0.00 | 0.438849E+11 | 0.00 | 1.67 |
September | 0.199350E+11 | 0.255161E+10 | 0.00 | 0.193557E+09 | 13621510.79 | 0.220479E+09 | 0.645502E+11 | 0.00 | 1.70 |
October | 0.244172E+11 | 0.00 | 0.00 | 0.202041E+09 | 0.00 | 0.193257E+10 | 0.903490E+11 | 0.00 | 1.51 |
November | 0.315946E+11 | 0.00 | 0.00 | 0.124546E+09 | 0.00 | 0.112586E+11 | 0.654910E+11 | 0.00 | 0.90 |
December | 0.346406E+11 | 0.00 | 0.00 | 48496136.15 | 0.00 | 0.328249E+11 | 0.354866E+11 | 0.00 | 0.58 |
Annual Sum or Average | 0.306856E+12 | 0.820860E+10 | 0.00 | 0.164618E+10 | 0.124287E+09 | 0.143260E+12 | 0.669403E+12 | 0.00 | 1.16 |
Minimum of Months | 0.103628E+11 | 0.00 | 0.00 | 47121866.71 | 0.00 | 0.00 | 0.276730E+11 | 0.00 | 0.56 |
Maximum of Months | 0.385411E+11 | 0.255161E+10 | 0.00 | 0.226881E+09 | 66183782.25 | 0.544723E+11 | 0.903490E+11 | 0.00 | 1.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.214894E+11 | 0.00 | 0.00 | 341008.41 | 0.00 | 0.675395E+11 | 0.557089E+09 | 0.00 | 0.63 |
February | 0.333295E+11 | 0.00 | 0.00 | 8693634.49 | 0.00 | 0.327587E+11 | 0.588049E+10 | 0.00 | 0.75 |
March | 0.463684E+11 | 0.00 | 0.00 | 19583382.17 | 0.00 | 0.157310E+11 | 0.154084E+11 | 0.00 | 0.82 |
April | 0.372601E+11 | 0.00 | 0.00 | 54827772.24 | 0.00 | 0.163887E+10 | 0.293503E+11 | 0.00 | 1.20 |
May | 0.261498E+11 | 58538291.01 | 0.00 | 95866721.02 | 16020970.49 | 0.162269E+10 | 0.437846E+11 | 0.00 | 1.53 |
June | 0.145947E+11 | 0.793814E+09 | 0.00 | 0.129321E+09 | 9874651.18 | 6660919.44 | 0.385658E+11 | 0.00 | 1.90 |
July | 0.834066E+10 | 0.210795E+10 | 0.00 | 0.154890E+09 | 6741895.12 | 0.00 | 0.226873E+11 | 0.00 | 1.61 |
August | 0.133918E+11 | 0.139934E+10 | 0.00 | 0.123465E+09 | 39411030.39 | 0.00 | 0.263726E+11 | 0.00 | 1.69 |
September | 0.273653E+11 | 0.146009E+10 | 0.00 | 61071890.67 | 6326808.97 | 0.240603E+09 | 0.228631E+11 | 0.00 | 1.41 |
October | 0.408168E+11 | 0.00 | 0.00 | 29327868.86 | 0.00 | 0.240046E+10 | 0.168873E+11 | 0.00 | 1.08 |
November | 0.416558E+11 | 0.00 | 0.00 | 8582549.74 | 0.00 | 0.140413E+11 | 0.748375E+10 | 0.00 | 0.77 |
December | 0.308461E+11 | 0.00 | 0.00 | 830100.06 | 0.00 | 0.442507E+11 | 0.115129E+10 | 0.00 | 0.63 |
Annual Sum or Average | 0.341608E+12 | 0.581973E+10 | 0.00 | 0.686801E+09 | 78375356.15 | 0.180230E+12 | 0.230992E+12 | 0.00 | 1.17 |
Minimum of Months | 0.834066E+10 | 0.00 | 0.00 | 341008.41 | 0.00 | 0.00 | 0.557089E+09 | 0.00 | 0.63 |
Maximum of Months | 0.463684E+11 | 0.210795E+10 | 0.00 | 0.154890E+09 | 39411030.39 | 0.675395E+11 | 0.437846E+11 | 0.00 | 1.90 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.189268E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.731103E+10 | 0.00 | 0.00 | 0.35 |
February | 0.930927E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401834E+10 | 0.00 | 0.00 | 0.33 |
March | 0.226923E+10 | 0.00 | 0.00 | 7041.59 | 0.00 | 0.246762E+10 | 21228192.97 | 0.00 | 0.33 |
April | 0.245012E+10 | 0.00 | 0.00 | 875806.60 | 0.00 | 0.755978E+09 | 0.643970E+09 | 0.00 | 0.41 |
May | 0.188423E+10 | 3439937.33 | 0.00 | 3603373.55 | 720985.11 | 0.449556E+09 | 0.195872E+10 | 0.00 | 0.61 |
June | 0.911830E+09 | 36710663.09 | 0.00 | 9872095.65 | 1567435.78 | 10133137.18 | 0.329523E+10 | 0.00 | 1.00 |
July | 0.526056E+09 | 84097012.79 | 0.00 | 12008572.12 | 1860608.35 | 0.00 | 0.197080E+10 | 0.00 | 0.87 |
August | 0.899263E+09 | 61360852.98 | 0.00 | 9511199.70 | 4904626.60 | 6061017.04 | 0.203755E+10 | 0.00 | 0.83 |
September | 0.172727E+10 | 76166771.67 | 0.00 | 3388908.03 | 3742266.18 | 0.217569E+09 | 0.119836E+10 | 0.00 | 0.59 |
October | 0.234325E+10 | 0.00 | 0.00 | 415536.99 | 0.00 | 0.876203E+09 | 0.302075E+09 | 0.00 | 0.41 |
November | 0.143546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250048E+10 | 0.00 | 0.00 | 0.33 |
December | 0.515226E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506232E+10 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.160821E+11 | 0.261775E+09 | 0.00 | 39682534.23 | 12795922.02 | 0.236753E+11 | 0.114279E+11 | 0.00 | 0.53 |
Minimum of Months | 0.189268E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.245012E+10 | 84097012.79 | 0.00 | 12008572.12 | 4904626.60 | 0.731103E+10 | 0.329523E+10 | 0.00 | 1.00 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.885980E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624778E+10 | 0.00 | 0.00 | 0.55 |
February | 0.200934E+10 | 0.00 | 0.00 | 160711.38 | 0.00 | 0.354988E+10 | 0.122660E+09 | 0.00 | 0.61 |
March | 0.304078E+10 | 0.00 | 0.00 | 1403672.31 | 0.00 | 0.214999E+10 | 0.106939E+10 | 0.00 | 0.68 |
April | 0.245774E+10 | 0.00 | 0.00 | 4545409.85 | 0.00 | 0.726009E+09 | 0.297353E+10 | 0.00 | 1.02 |
May | 0.198549E+10 | 2571306.63 | 0.00 | 7050838.82 | 963539.12 | 0.418752E+09 | 0.427159E+10 | 0.00 | 1.38 |
June | 0.100065E+10 | 33902643.74 | 0.00 | 17929705.01 | 2094752.97 | 13313731.51 | 0.526707E+10 | 0.00 | 2.20 |
July | 0.567551E+09 | 80223641.22 | 0.00 | 22695343.16 | 3992854.95 | 0.00 | 0.386139E+10 | 0.00 | 2.13 |
August | 0.995368E+09 | 68012399.71 | 0.00 | 14512461.69 | 6408945.89 | 3857868.07 | 0.401610E+10 | 0.00 | 2.01 |
September | 0.197838E+10 | 71232603.57 | 0.00 | 6663368.29 | 4912694.56 | 0.208679E+09 | 0.259456E+10 | 0.00 | 1.34 |
October | 0.294546E+10 | 0.00 | 0.00 | 1712668.80 | 0.00 | 0.759041E+09 | 0.109990E+10 | 0.00 | 0.89 |
November | 0.254075E+10 | 0.00 | 0.00 | 56640.75 | 0.00 | 0.237762E+10 | 63415120.75 | 0.00 | 0.66 |
December | 0.125941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.487057E+10 | 0.00 | 0.00 | 0.56 |
Annual Sum or Average | 0.216669E+11 | 0.255943E+09 | 0.00 | 76730820.07 | 18372787.49 | 0.213255E+11 | 0.253396E+11 | 0.00 | 1.17 |
Minimum of Months | 0.567551E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 0.304078E+10 | 80223641.22 | 0.00 | 22695343.16 | 6408945.89 | 0.624778E+10 | 0.526707E+10 | 0.00 | 2.20 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.193312E+10 | 0.00 | 0.00 | 2709031.63 | 0.00 | 0.596930E+10 | 0.231408E+10 | 0.00 | 0.51 |
February | 0.228134E+10 | 0.00 | 0.00 | 9054409.79 | 0.00 | 0.299630E+10 | 0.456640E+10 | 0.00 | 0.79 |
March | 0.307248E+10 | 0.00 | 0.00 | 9890676.73 | 0.00 | 0.222062E+10 | 0.649220E+10 | 0.00 | 0.89 |
April | 0.275321E+10 | 0.00 | 0.00 | 9410032.15 | 0.00 | 0.961802E+09 | 0.567964E+10 | 0.00 | 1.09 |
May | 0.250098E+10 | 5171688.61 | 0.00 | 9981491.01 | 1187142.09 | 0.672037E+09 | 0.558881E+10 | 0.00 | 1.24 |
June | 0.180895E+10 | 55074661.76 | 0.00 | 15155553.30 | 2580870.23 | 32068335.66 | 0.462284E+10 | 0.00 | 1.52 |
July | 0.111620E+10 | 0.130582E+09 | 0.00 | 19045959.29 | 1467575.45 | 0.00 | 0.289441E+10 | 0.00 | 1.37 |
August | 0.142102E+10 | 0.140912E+09 | 0.00 | 24482117.08 | 5109604.77 | 21105336.00 | 0.442831E+10 | 0.00 | 1.72 |
September | 0.198271E+10 | 0.227591E+09 | 0.00 | 17781939.02 | 988342.06 | 0.232869E+09 | 0.603583E+10 | 0.00 | 1.67 |
October | 0.238681E+10 | 0.00 | 0.00 | 15941895.70 | 0.00 | 0.623251E+09 | 0.738346E+10 | 0.00 | 1.40 |
November | 0.245564E+10 | 0.00 | 0.00 | 7606262.20 | 0.00 | 0.195881E+10 | 0.450268E+10 | 0.00 | 0.79 |
December | 0.240773E+10 | 0.00 | 0.00 | 2903462.85 | 0.00 | 0.413694E+10 | 0.225068E+10 | 0.00 | 0.53 |
Annual Sum or Average | 0.261202E+11 | 0.559331E+09 | 0.00 | 0.143963E+09 | 11333534.60 | 0.198251E+11 | 0.567593E+11 | 0.00 | 1.13 |
Minimum of Months | 0.111620E+10 | 0.00 | 0.00 | 2709031.63 | 0.00 | 0.00 | 0.225068E+10 | 0.00 | 0.51 |
Maximum of Months | 0.307248E+10 | 0.227591E+09 | 0.00 | 24482117.08 | 5109604.77 | 0.596930E+10 | 0.738346E+10 | 0.00 | 1.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117650E+10 | 0.00 | 0.00 | 11716.87 | 0.00 | 0.667875E+10 | 20135495.63 | 0.00 | 0.61 |
February | 0.225010E+10 | 0.00 | 0.00 | 591672.06 | 0.00 | 0.372920E+10 | 0.471747E+09 | 0.00 | 0.70 |
March | 0.362247E+10 | 0.00 | 0.00 | 1619113.72 | 0.00 | 0.229488E+10 | 0.136643E+10 | 0.00 | 0.81 |
April | 0.346671E+10 | 0.00 | 0.00 | 4745251.35 | 0.00 | 0.672028E+09 | 0.262754E+10 | 0.00 | 1.19 |
May | 0.268612E+10 | 3366188.10 | 0.00 | 9053575.79 | 1080667.77 | 0.385639E+09 | 0.425874E+10 | 0.00 | 1.57 |
June | 0.157647E+10 | 51143784.86 | 0.00 | 15169748.32 | 312759.09 | 23486796.12 | 0.386681E+10 | 0.00 | 2.02 |
July | 0.910376E+09 | 0.118444E+09 | 0.00 | 17078253.64 | 773756.46 | 0.00 | 0.227277E+10 | 0.00 | 1.68 |
August | 0.142995E+10 | 80746997.24 | 0.00 | 13231385.94 | 2505164.13 | 14814099.43 | 0.253405E+10 | 0.00 | 1.73 |
September | 0.261752E+10 | 0.132265E+09 | 0.00 | 5617642.17 | 1125653.71 | 0.182372E+09 | 0.213577E+10 | 0.00 | 1.43 |
October | 0.350642E+10 | 0.00 | 0.00 | 2396143.55 | 0.00 | 0.720697E+09 | 0.142551E+10 | 0.00 | 1.07 |
November | 0.281315E+10 | 0.00 | 0.00 | 536741.60 | 0.00 | 0.233721E+10 | 0.488872E+09 | 0.00 | 0.75 |
December | 0.180359E+10 | 0.00 | 0.00 | 40978.08 | 0.00 | 0.496349E+10 | 50489794.03 | 0.00 | 0.62 |
Annual Sum or Average | 0.278594E+11 | 0.385966E+09 | 0.00 | 70092223.09 | 5798001.15 | 0.220026E+11 | 0.215189E+11 | 0.00 | 1.18 |
Minimum of Months | 0.910376E+09 | 0.00 | 0.00 | 11716.87 | 0.00 | 0.00 | 20135495.63 | 0.00 | 0.61 |
Maximum of Months | 0.362247E+10 | 0.132265E+09 | 0.00 | 17078253.64 | 2505164.13 | 0.667875E+10 | 0.425874E+10 | 0.00 | 2.02 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 5233448.03 | 0.00 | 0.00 | 2641037.24 | 0.00 | 0.00 | 0.844651E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7793939.87 | 0.00 | 0.00 | 0.645024E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 14729413.28 | 0.00 | 0.00 | 0.660714E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 18483366.27 | 0.00 | 0.00 | 0.461230E+09 | 0.00 | 0.29 |
May | 0.00 | 163153.63 | 0.00 | 4215095.47 | 0.00 | 0.00 | 0.407340E+09 | 0.00 | 0.29 |
June | 0.00 | 14129090.07 | 0.00 | 8153718.48 | 0.00 | 0.00 | 0.197448E+09 | 0.00 | 0.30 |
July | 0.00 | 23472027.55 | 0.00 | 10453689.18 | 0.00 | 0.00 | 74815727.75 | 0.00 | 0.28 |
August | 0.00 | 6770398.08 | 0.00 | 17891408.02 | 0.00 | 0.00 | 0.141331E+09 | 0.00 | 0.31 |
September | 0.00 | 11617780.91 | 0.00 | 3955290.58 | 0.00 | 0.00 | 0.256111E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 9197012.42 | 0.00 | 0.00 | 0.438305E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 13038110.93 | 0.00 | 0.00 | 0.542480E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 17785176.14 | 0.00 | 0.00 | 0.715541E+09 | 0.00 | 0.28 |
Annual Sum or Average | 5233448.03 | 56152450.23 | 0.00 | 0.128337E+09 | 0.00 | 0.00 | 0.538499E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2641037.24 | 0.00 | 0.00 | 74815727.75 | 0.00 | 0.28 |
Maximum of Months | 5233448.03 | 23472027.55 | 0.00 | 18483366.27 | 0.00 | 0.00 | 0.844651E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.277713E+10 | 0.00 | 0.00 | 9624648.15 | 0.00 | 0.00 | 0.567144E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 60315649.55 | 0.00 | 0.00 | 0.646816E+10 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 0.127353E+09 | 0.00 | 0.00 | 0.662674E+10 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 0.168677E+09 | 0.00 | 0.00 | 0.462636E+10 | 0.00 | 0.29 |
May | 0.00 | 1554907.22 | 0.00 | 34454626.18 | 0.00 | 0.00 | 0.408532E+10 | 0.00 | 0.29 |
June | 0.00 | 0.139773E+09 | 0.00 | 75209181.10 | 0.00 | 0.00 | 0.198344E+10 | 0.00 | 0.30 |
July | 0.00 | 0.233289E+09 | 0.00 | 98204095.30 | 0.00 | 0.00 | 0.755589E+09 | 0.00 | 0.28 |
August | 0.00 | 68373388.55 | 0.00 | 0.168745E+09 | 0.00 | 0.00 | 0.142256E+10 | 0.00 | 0.31 |
September | 0.00 | 0.113268E+09 | 0.00 | 32398109.48 | 0.00 | 0.00 | 0.258307E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 78650849.48 | 0.00 | 0.00 | 0.439612E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.112012E+09 | 0.00 | 0.00 | 0.544248E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.152756E+09 | 0.00 | 0.00 | 0.717863E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.277713E+10 | 0.556258E+09 | 0.00 | 0.111840E+10 | 0.00 | 0.00 | 0.512399E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 9624648.15 | 0.00 | 0.00 | 0.755589E+09 | 0.00 | 0.28 |
Maximum of Months | 0.277713E+10 | 0.233289E+09 | 0.00 | 0.168745E+09 | 0.00 | 0.00 | 0.717863E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.594392E+09 | 0.00 | 0.00 | 334449.36 | 0.00 | 0.00 | 0.235727E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 4950186.45 | 0.00 | 0.00 | 0.647840E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 11583376.38 | 0.00 | 0.00 | 0.663842E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 16069795.59 | 0.00 | 0.00 | 0.463584E+09 | 0.00 | 0.29 |
May | 24416113.15 | 157576.13 | 0.00 | 2950410.27 | 0.00 | 0.00 | 0.384180E+09 | 0.00 | 0.29 |
June | 0.00 | 14013334.39 | 0.00 | 7353166.12 | 0.00 | 0.00 | 0.198703E+09 | 0.00 | 0.30 |
July | 0.00 | 23337028.75 | 0.00 | 9760153.09 | 0.00 | 0.00 | 75728563.32 | 0.00 | 0.28 |
August | 0.00 | 6835909.84 | 0.00 | 16746986.04 | 0.00 | 0.00 | 0.142523E+09 | 0.00 | 0.31 |
September | 6786687.20 | 11324453.58 | 0.00 | 2759233.17 | 0.00 | 0.00 | 0.253163E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 6892143.91 | 0.00 | 0.00 | 0.440825E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 10010701.78 | 0.00 | 0.00 | 0.545487E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 13959702.72 | 0.00 | 0.00 | 0.719266E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.625595E+09 | 55668302.69 | 0.00 | 0.103370E+09 | 0.00 | 0.00 | 0.477087E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 334449.36 | 0.00 | 0.00 | 75728563.32 | 0.00 | 0.28 |
Maximum of Months | 0.594392E+09 | 23337028.75 | 0.00 | 16746986.04 | 0.00 | 0.00 | 0.719266E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.779087E+09 | 0.00 | 0.00 | 0.518461E+12 | 0.00 | 7.75 |
February | 0.00 | 0.00 | 0.00 | 0.121914E+10 | 0.00 | 0.00 | 0.768054E+12 | 0.00 | 15.92 |
March | 0.00 | 0.00 | 0.00 | 0.180045E+10 | 0.00 | 0.00 | 0.110422E+13 | 0.00 | 23.34 |
April | 0.00 | 0.00 | 0.00 | 0.232751E+10 | 0.00 | 0.00 | 0.126189E+13 | 0.00 | 38.05 |
May | 0.00 | 0.00 | 0.00 | 0.554025E+09 | 0.00 | 0.00 | 0.512690E+12 | 0.00 | 18.38 |
June | 0.00 | 0.227381E+10 | 0.00 | 0.130377E+10 | 0.00 | 0.00 | 0.605415E+12 | 0.00 | 35.51 |
July | 0.00 | 0.245901E+10 | 0.00 | 0.224458E+10 | 0.00 | 0.00 | 0.553529E+12 | 0.00 | 41.38 |
August | 0.00 | 0.446841E+09 | 0.00 | 0.293748E+10 | 0.00 | 0.00 | 0.770336E+12 | 0.00 | 45.55 |
September | 0.00 | 0.860748E+09 | 0.00 | 0.567662E+09 | 0.00 | 0.00 | 0.424993E+12 | 0.00 | 22.59 |
October | 0.00 | 0.00 | 0.00 | 0.110173E+10 | 0.00 | 0.00 | 0.837319E+12 | 0.00 | 25.44 |
November | 0.00 | 0.00 | 0.00 | 0.177908E+10 | 0.00 | 0.00 | 0.107084E+13 | 0.00 | 26.64 |
December | 0.00 | 0.00 | 0.00 | 0.274843E+10 | 0.00 | 0.00 | 0.134905E+13 | 0.00 | 26.30 |
Annual Sum or Average | 0.00 | 0.604041E+10 | 0.00 | 0.193629E+11 | 0.00 | 0.00 | 0.977679E+13 | 0.00 | 27.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.554025E+09 | 0.00 | 0.00 | 0.424993E+12 | 0.00 | 7.75 |
Maximum of Months | 0.00 | 0.245901E+10 | 0.00 | 0.293748E+10 | 0.00 | 0.00 | 0.134905E+13 | 0.00 | 45.55 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:57
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.255571E+12 | 0.214603E+11 | 0.00 | 0.230403E+13 | 0.249351E+12 |
February | 0.347429E+12 | 0.168668E+11 | 0.00 | 0.244755E+13 | 0.255822E+12 |
March | 0.604874E+12 | 0.157481E+11 | 0.00 | 0.312095E+13 | 0.314615E+12 |
April | 0.651690E+12 | 0.112724E+11 | 0.00 | 0.336450E+13 | 0.487390E+12 |
May | 0.864197E+12 | 0.110946E+11 | 0.00 | 0.257267E+13 | 0.414897E+12 |
June | 0.945493E+12 | 0.569765E+10 | 0.00 | 0.234378E+13 | 0.127093E+13 |
July | 0.937530E+12 | 0.378610E+10 | 0.00 | 0.199787E+13 | 0.237890E+13 |
August | 0.777406E+12 | 0.407754E+10 | 0.00 | 0.236436E+13 | 0.240999E+13 |
September | 0.581892E+12 | 0.739563E+10 | 0.00 | 0.222616E+13 | 0.765924E+12 |
October | 0.376312E+12 | 0.108678E+11 | 0.00 | 0.303650E+13 | 0.357404E+12 |
November | 0.200921E+12 | 0.152205E+11 | 0.00 | 0.304993E+13 | 0.299574E+12 |
December | 0.162401E+12 | 0.193253E+11 | 0.00 | 0.318376E+13 | 0.425520E+12 |
Annual Sum or Average | 0.670572E+13 | 0.142813E+12 | 0.00 | 0.320121E+14 | 0.963032E+13 |
Minimum of Months | 0.162401E+12 | 0.378610E+10 | 0.00 | 0.199787E+13 | 0.249351E+12 |
Maximum of Months | 0.945493E+12 | 0.214603E+11 | 0.00 | 0.336450E+13 | 0.240999E+13 |