Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2024-07-03 12:21:45
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:45
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 34260.78 | 739.65 | 739.65 |
Net Site Energy | 34260.78 | 739.65 | 739.65 |
Total Source Energy | 108503.88 | 2342.47 | 2342.47 |
Net Source Energy | 108503.88 | 2342.47 | 2342.47 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6960.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3213.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 348.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2566.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2986.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 987.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2226.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24579.67 |
Humidification | 13.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 279.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 34260.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26865.01 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 6960.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3213.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 348.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 55.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2505.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2986.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 987.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 2226.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24579.67 |
Humidification | General | 13.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 279.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 6960.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3213.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 348.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 2566.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2986.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 987.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 2226.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24579.67 |
Humidification | Unassigned | 13.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 279.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 76.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 290.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Other | 372.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 739.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 76.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 290.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Other | 372.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 739.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 34260.778 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 34260.778 | 100.00 |
Total On-Site and Utility Electric Sources | 34260.778 | 100.00 |
Total Electricity End Uses | 34260.778 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 26865.01 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 26865.01 | 100.00 |
Total Water End Uses | 26865.01 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 4193.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:45
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 8.6849 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 8.6849 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 8.7339 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 8.7339 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.6849 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 8.6849 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 8.6849 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 8.6849 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 8.6849 | 18.58 | 484.4232 | |
Total | 46320.38 | 8.7339 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 8.7339 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.6845 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:45
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-15:00 | - | - | - | - | - | - | - | - | - | - | - | 16-JUN-12:00 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 691057.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 280450.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 233302.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 255711.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 59271.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 96956.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18880.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2414001.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 691057.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 280450.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3430.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 255711.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 59271.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 96956.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 18880.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:45
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 22043.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 10178.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1105.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8128.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9457.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3128.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 7051.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 44.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 886.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 108503.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 475.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 219.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 23.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 204.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 67.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 152.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 19.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2342.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 475.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 219.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 23.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 204.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 67.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 152.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 19.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2342.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:45
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 5.99 | 0.353712 | 0.000000 | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 6.31 | 0.301578 | 0.314000 | 1.98 | 0.804208 | 0.500000 | 0.001263 |
CORE_MID VAV BOX COMPONENT | 60.06 | 0.316675 | 0.325000 | 19.52 | 0.844467 | 0.500000 | 0.001203 |
CORE_TOP VAV BOX COMPONENT | 6.06 | 0.314083 | 0.332000 | 2.01 | 0.837554 | 0.500000 | 0.001213 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.32 | 0.180785 | 0.200000 | 0.264204 | 0.482094 | 0.500000 | 0.002107 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.10 | 0.139309 | 0.200000 | 0.220955 | 0.371491 | 0.500000 | 0.002735 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.48 | 0.161551 | 0.200000 | 0.295666 | 0.430803 | 0.500000 | 0.002358 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.43 | 0.107398 | 0.200000 | 0.286606 | 0.300000 | 0.500000 | 0.003548 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 13.05 | 0.183017 | 0.200000 | 2.61 | 0.488044 | 0.500000 | 0.002082 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 11.49 | 0.133952 | 0.200000 | 2.30 | 0.357206 | 0.500000 | 0.002844 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 14.59 | 0.163689 | 0.200000 | 2.92 | 0.436504 | 0.500000 | 0.002328 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 12.68 | 0.121343 | 0.200000 | 2.54 | 0.323580 | 0.500000 | 0.003140 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.44 | 0.166186 | 0.200000 | 0.287414 | 0.443162 | 0.500000 | 0.002293 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.18 | 0.130614 | 0.200000 | 0.235664 | 0.348305 | 0.500000 | 0.002917 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.58 | 0.150753 | 0.200000 | 0.316843 | 0.402009 | 0.500000 | 0.002527 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.35 | 0.113709 | 0.200000 | 0.270701 | 0.303223 | 0.500000 | 0.003351 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 66111.55 |
CORE_MID VAV BOX REHEAT COIL | 651652.88 |
CORE_TOP VAV BOX REHEAT COIL | 67118.35 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 8819.94 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 7376.15 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 9870.24 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 9567.80 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 101283.76 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 76711.31 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 101135.73 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 84683.01 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 12846.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 8497.59 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 12824.27 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 9036.82 |
VAV_BOT WITH REHEAT HEATING COIL | 6420.31 |
VAV_MID WITH REHEAT HEATING COIL | 0.000000 |
VAV_TOP WITH REHEAT HEATING COIL | 0.000000 |
CAV_BAS HEATING COIL | 271237.24 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 11172.98 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 516.15 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 5161.45 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 516.15 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.480219 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.58 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.460805 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 24.71 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.82 | 3.05 | 11.64 | 3.05 | 10.60 | 10.60 | 0.300000 | 0.287452 | 10.60 |
VAV_MID WITH REHEAT | 55.94 | 29.88 | 111.88 | 29.88 | 100.10 | 100.10 | 0.300000 | 0.298545 | 100.10 |
VAV_TOP WITH REHEAT | 5.80 | 3.12 | 11.61 | 3.12 | 11.25 | 11.25 | 0.300000 | 0.277467 | 11.25 |
CAV_BAS | 0.000000 | 0.000000 | 5.99 | 1.20 | 5.99 | 5.99 | 1.00 | 0.200437 | 5.99 |
AIRLOOP DATACENTER BASEMENT | 24.71 | 24.71 | 24.71 | 24.71 | 24.71 | 24.71 | 1.00 | 0.999992 | 24.71 |
AIRLOOP DATACENTER BOT | 0.480219 | 0.480219 | 0.480219 | 0.480219 | 0.480219 | 0.480219 | 1.00 | 1.00 | 0.480219 |
AIRLOOP DATACENTER MID | 4.58 | 4.58 | 4.58 | 4.58 | 4.58 | 4.58 | 1.00 | 1.00 | 4.58 |
AIRLOOP DATACENTER TOP | 0.460805 | 0.460805 | 0.460805 | 0.460805 | 0.460805 | 0.460805 | 1.00 | 1.00 | 0.460805 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 10.60 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 100.10 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 11.25 | |
CAV_BAS_OA_CONTROLLER | 5.99 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 24.71 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.480219 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.58 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.460805 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 28.50 | 6.67 | 11.05 | 0.008140 | 0.007000 | 263849.23 | 0.007546 | 10.60 |
VAV_MID WITH REHEAT COOLING COIL | 28.84 | 6.67 | 11.04 | 0.008234 | 0.007000 | 2562077.56 | 0.073275 | 100.10 |
VAV_TOP WITH REHEAT COOLING COIL | 28.25 | 6.67 | 11.05 | 0.008100 | 0.007000 | 275101.77 | 0.007868 | 11.25 |
CAV_BAS COOLING COIL | 27.61 | 6.67 | 11.03 | 0.008174 | 0.007000 | 143256.62 | 0.004097 | 5.99 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 10.60 |
VAV_MID WITH REHEAT FAN | 100.10 |
VAV_TOP WITH REHEAT FAN | 11.25 |
CAV_BAS FAN | 5.99 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.007546 | 0.000063 |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.073275 | 0.000006 |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.007868 | 0.000061 |
CAV_BAS_COOLC_CONTROLLER | 0.004097 | 0.000116 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 24.71 | 517977.01 | 330538.91 | 0.012685 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.480219 | 10119.96 | 6428.65 | 0.000248 |
AIRLOOP DATACENTER MID COOLING COIL | 4.58 | 96567.15 | 61320.05 | 0.002365 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.460805 | 9724.66 | 6173.18 | 0.000238 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 24.71 | 24.71 | 24.71 | 24.71 | 517977.01 | 517977.01 | 11172.98 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.480219 | 0.480219 | 0.480219 | 0.480219 | 10119.96 | 10119.96 | 516.15 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.58 | 4.58 | 4.58 | 4.58 | 96567.15 | 96567.15 | 5161.45 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.460805 | 0.460805 | 0.460805 | 0.460805 | 9724.66 | 9724.66 | 516.15 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 24.71 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.480219 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.58 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.460805 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 24.71 | 517977.01 | 0.012685 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.480219 | 10119.96 | 0.000248 |
AIRLOOP DATACENTER MID HEATING COIL | 4.58 | 96567.15 | 0.002365 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.460805 | 9724.66 | 0.000238 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000026 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.092786 | 15149.14 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.092786 | 11.13 |
COOLSYS1_SUPPLY | 0.092786 | 11.13 |
SINGLE WATER PLANT LOOP | 0.015536 | 1.86 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.092786 | 0.092786 | 389470.01 | 8.33 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.046393 | 5244.13 |
COOLSYS1 CHILLER2 PUMP | 0.046393 | 5244.13 |
PLANT CIRC PUMP | 0.015536 | 3962.49 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.092786 | 0.046778 | 1635589.42 | 1635589.14 | 0.082162 |
COOLSYS1 CHILLER2 | 0.092786 | 0.046778 | 1635589.42 | 1635589.14 | 0.082162 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | U-factor Times Area Value at High Fan Speed [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/K] | |
CENTRAL TOWER | 0.015536 | 154262.35 | 78091.95 | 77131.17 | 7879.72 | 46855.17 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
CENTRAL BOILER | 639955.80 | 627621.66 | 0.015536 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.164324 | 19.72 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.164324 | 40682.88 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 62.81 | 1957832.93 | 12.56 | 244729.12 |
TOWERWATERSYS COOLTOWER 2 | 62.81 | 1957832.93 | 12.56 | 244729.12 |
Design Water Flow Rate [m3/s] Equipment # 27 | |
WSHPPLANT OPERATION SCHEME | 0.084818 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:45
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:45
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:45
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 8.685 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 13.527 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 8.685 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 493.108 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 24139.153 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 24139.153 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 6806.209 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6806.209 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 5.069 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2994E-01 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
47 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
48 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
49 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
50 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
51 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
52 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
53 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
54 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
55 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
56 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
57 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
58 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
59 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
60 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
61 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
62 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
63 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
64 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
65 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
66 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
67 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
68 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
69 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
70 | 9 | -0.34109306E-14 | 0.24909287E-15 | -0.70234472E-12 | 0.65513238E-16 |
71 | 8 | 0.13119258E-09 | 0.66225198E-13 | 0.25869970E-04 | -0.14916918E-11 |
72 | 7 | -0.11009939E-02 | 0.13568249E-07 | -0.65256785E-02 | 0.12518681E-04 |
73 | 6 | 0.10140049 | 0.81303169E-05 | 0.18905580 | -0.11654411E-02 |
74 | 5 | -2.2086417 | 0.46066432E-03 | -2.1793248 | 0.26223950E-01 |
75 | 4 | 19.715055 | 0.51780401E-02 | 12.415669 | -0.24584718 |
76 | 3 | -82.671456 | 0.14472115E-01 | -37.782151 | 1.1032137 |
77 | 2 | 168.49726 | 0.99923307E-02 | 62.094262 | -2.4465849 |
78 | 1 | -160.45852 | 0.12849016E-02 | -51.628788 | 2.5579517 |
79 | 0 | 57.057407 | 0.91053392E-05 | 16.929182 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.498_SHGC_EAST_0.22 | 35 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.221 | ||
2 | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 36 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.221 | ||
3 | WINDOW_U_0.498_SHGC_WEST_0.22 | 37 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.221 | ||
4 | WINDOW_U_0.498_SHGC_NORTH_0.22 | 38 | 1 | VerySmooth | 2.831 | 2.831 | 1.000 | 0.221 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 2.00974E-002 | 0.13126 | 0.64120 | 0.64120 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 2.00974E-002 | 0.13126 | 0.64120 | 0.64120 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 2.00974E-002 | 0.13126 | 0.64120 | 0.64120 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 2.00974E-002 | 0.13126 | 0.64120 | 0.64120 | 0.24200 | 0.16318 | 0.24318 | 0.00000 | 0.84000 | 0.84000 | 0.10990 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 1.973E-005 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1451E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1463E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2904E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2914E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6013E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6020E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5496E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5501E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1722E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2479E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.3126E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.3758E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6183E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6680E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5627E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5954E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.6587E-002 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.0247E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.2953E-002 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1348E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 6.2509E-002 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.2325E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.7830E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.6539E-003 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1773E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2718E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.3180E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.4013E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6234E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6872E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5630E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5964E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1450E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1463E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.2903E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2915E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6013E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6021E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.5495E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.5500E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3661E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4855E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.1995E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3197E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0434E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.1089E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6499E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6725E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7338E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7504E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.4772E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5743E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5468E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.4216E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.8983E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.0820E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.3403E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3934E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.1676E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.2067E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0240E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0403E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 2.6499E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6729E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4987E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4999E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2944E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2954E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1453E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1460E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5496E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5501E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5265E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5951E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3171E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3716E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1628E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2007E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5630E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5964E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.2803E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1744E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7740E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.0120E-003 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5572E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 6.0656E-003 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7830E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.6510E-003 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5246E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5922E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3147E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3666E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1588E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1888E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5627E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5955E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4986E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4998E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.2943E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2952E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.1452E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1458E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5495E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5500E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9233E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9785E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6670E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7071E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6194E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6342E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6500E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6729E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0212E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.4895E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6313E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.2658E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8177E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.1509E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.8983E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.0820E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.9444E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0422E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6936E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.7879E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6376E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6960E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 2.6498E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.6725E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.1161E-002 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.5159E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.5992E-002 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.6852E-002 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.9610E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.4521E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.4144E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.6879E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.4615E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.5498E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.1758E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.3347E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.2301E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.1410E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.5002E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.7075E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.8785E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.8944E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.3017E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.5185E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.0558E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.1430E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.4145E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6876E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.6530E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.1861E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.2148E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9027E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.4097E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7732E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.5002E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.7075E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.1272E-002 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.5254E-002 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.6125E-002 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.6957E-002 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.9744E-002 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.4606E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.4218E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.6916E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.4659E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.5539E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.1808E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.3385E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.2375E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.1455E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.5076E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.7112E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.8792E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.8966E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.3024E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.5202E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.0591E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.1450E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.4218E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6914E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.6556E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.1892E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.2176E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9055E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.4154E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7768E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.5076E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.7112E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 82881.47871 | 82881.47871 | 5.98771 | 5.98771 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | 00:10:00 | 12.70000 | 9.15345E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 87305.04104 | 87305.04104 | 6.30697 | 6.30697 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | 00:10:00 | 12.70000 | 9.15345E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 | |
5 | CORE_MID | Cooling | 831595.19900 | 831595.19900 | 60.06290 | 60.06290 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 156648.16790 | 156648.16790 | 6.54991 | 10.77825 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 83843.64001 | 83843.64001 | 6.05587 | 6.05587 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 35.62200 | 1.07695E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 28541.89616 | 28541.89616 | 1.20403 | 1.20403 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 18123.59475 | 18123.59475 | 1.32102 | 1.32102 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 42.80000 | 1.07818E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 112.10754 | 112.10754 | 4.80321E-003 | 0.13533 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 15156.86777 | 15156.86777 | 1.10477 | 1.10477 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 39.35650 | 1.07759E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 379.45114 | 379.45114 | 1.61911E-002 | 8.72129E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 20281.81714 | 20281.81714 | 1.47833 | 1.47833 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 42.80000 | 1.07818E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 1860.74685 | 1860.74685 | 7.85938E-002 | 0.13533 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 19660.46223 | 19660.46223 | 1.43303 | 1.43303 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 41.95933 | 1.07804E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 0.00000 | 0.00000 | 0.00000 | 8.72129E-002 | 00:10:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 | |
17 | PERIMETER_MID_ZN_3 | Cooling | 179022.60015 | 179022.60015 | 13.04912 | 13.04912 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 42.70300 | 1.07816E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 71406.27108 | 71406.27108 | 3.03398 | 3.03398 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 157627.09368 | 157627.09368 | 11.48954 | 11.48954 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 39.59900 | 1.07763E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 47600.07723 | 47600.07723 | 2.02299 | 2.02299 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 200165.37283 | 200165.37283 | 14.59022 | 14.59022 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 42.80000 | 1.07818E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 71302.61882 | 71302.61882 | 3.02955 | 3.02955 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 174007.68270 | 174007.68270 | 12.68352 | 12.68352 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 41.83000 | 1.07801E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 39725.10718 | 39725.10718 | 1.68577 | 1.68577 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 19715.24525 | 19715.24525 | 1.43707 | 1.43707 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 42.60600 | 1.07815E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 9043.62381 | 9043.62381 | 0.38481 | 0.38481 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 16165.42388 | 16165.42388 | 1.17832 | 1.17832 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 39.84150 | 1.07767E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 5981.58017 | 5981.58017 | 0.25455 | 0.25455 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 21733.95266 | 21733.95266 | 1.58422 | 1.58422 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 42.80000 | 1.07818E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 9028.38506 | 9028.38506 | 0.38415 | 0.38415 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 18568.83580 | 18568.83580 | 1.35350 | 1.35350 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 41.95933 | 1.07804E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 5236.86056 | 5236.86056 | 0.22270 | 0.22270 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12.70000 | 9.15345E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8353.97559 | 8353.97559 | 0.48022 | 0.48022 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:10:00 | 33.13233 | 1.07653E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 12.70000 | 9.15345E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 79668.94974 | 79668.94974 | 4.57968 | 4.57968 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 33.16467 | 1.07653E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | 00:10:00 | 12.70000 | 9.15345E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8015.33678 | 8015.33678 | 0.46081 | 0.46081 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | 40.63367 | 1.07781E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 12.70000 | 9.15345E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 373734.48491 | 429794.65764 | 21.48574 | 24.70860 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 33.97300 | 1.07667E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | 00:10:00 | 12.70000 | 9.15345E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 201276.09 | 10.60288 | 10.60288 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 184.19 | 1.52292 | 1.52292 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1912922.77 | 100.09533 | 100.09533 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 2485.47 | 20.55054 | 20.55054 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 209660.05 | 11.24881 | 11.24881 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 296.34 | 2.45024 | 2.45024 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
7 | CAV_BAS | Cooling | Sensible | 98549.98 | 5.98771 | 5.98771 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 39626.51 | 1.20016 | 1.20016 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 430210.82 | 24.70879 | 24.70879 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 11172.98 | 0.33839 | 0.33839 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8372.65 | 0.48022 | 0.48022 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 516.15 | 1.56323E-002 | 1.56323E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 79841.18 | 4.57968 | 4.57968 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 5161.45 | 0.15632 | 0.15632 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8186.41 | 0.46081 | 0.46081 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 516.15 | 1.56323E-002 | 1.56323E-002 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 5.98771 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.35371 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.00000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 0.00000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.30697 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30158 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31400 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.98039 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.80421 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.26336E-003 |
12 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 66111.55146 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 60.06290 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31668 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32500 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 19.52044 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.84447 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.20313E-003 |
20 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 651652.87793 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.05587 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31408 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33200 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.01055 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83755 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.21306E-003 |
28 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 67118.35093 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.32102 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18079 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
32 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26420 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48209 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.10747E-003 |
36 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8819.94382 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.10477 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13931 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.22095 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37149 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.73492E-003 |
44 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7376.14910 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.47833 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16155 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29567 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43080 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.35839E-003 |
52 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9870.23992 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.43303 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10740 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28661 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.54754E-003 |
60 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9567.80033 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.04912 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18302 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.60982 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48804 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.08178E-003 |
68 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 101283.75807 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.48954 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13395 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.29791 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35721 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.84430E-003 |
76 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 76711.31497 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.59022 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16369 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.91804 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43650 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.32758E-003 |
84 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 101135.72675 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.68352 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12134 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.53670 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32358 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.13987E-003 |
92 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 84683.00698 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.43707 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16619 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28741 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44316 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.29262E-003 |
100 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12845.99992 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.17832 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13061 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23566 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34830 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.91699E-003 |
108 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8497.58799 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.58422 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15075 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.31684 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40201 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.52731E-003 |
116 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 12824.26868 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.35350 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11371 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27070 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30322 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.35067E-003 |
124 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9036.82178 |
125 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.48022 |
126 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.57968 |
127 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.46081 |
128 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 24.70860 |
129 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.82206 |
130 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.04782 |
131 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.64413 |
132 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.04782 |
133 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.60288 |
134 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.60288 |
135 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.28745 |
137 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 55.93765 |
138 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 29.88292 |
139 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 111.87530 |
140 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 29.88292 |
141 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 100.09533 |
142 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 100.09533 |
143 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.29854 |
145 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.80449 |
146 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.12117 |
147 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.60898 |
148 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.12117 |
149 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 11.24881 |
150 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 11.24881 |
151 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
152 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.27747 |
153 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.00000 |
154 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.00000 |
155 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.98771 |
156 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 1.20016 |
157 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.98771 |
158 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.98771 |
159 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
160 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.20044 |
161 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 24.70860 |
162 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 24.70860 |
163 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 24.70860 |
164 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 24.70860 |
165 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 24.70879 |
166 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 24.70879 |
167 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
168 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
169 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.48022 |
170 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.48022 |
171 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.48022 |
172 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.48022 |
173 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.48022 |
174 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.48022 |
175 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
176 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
177 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.57968 |
178 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.57968 |
179 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.57968 |
180 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.57968 |
181 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.57968 |
182 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.57968 |
183 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
184 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
185 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.46081 |
186 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.46081 |
187 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.46081 |
188 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.46081 |
189 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.46081 |
190 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.46081 |
191 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
192 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
193 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.60288 |
194 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 100.09533 |
195 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 11.24881 |
196 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.98771 |
197 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 24.70879 |
198 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.48022 |
199 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.57968 |
200 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.46081 |
201 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.60288 |
202 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.50103 |
203 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
204 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04910 |
205 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.14013E-003 |
206 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
207 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 263849.22876 |
208 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.54605E-003 |
209 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.60288 |
210 | Coil:Heating:Electric | VAV_BOT WITH REHEAT HEATING COIL | Design Size Nominal Capacity [W] | 6420.31466 |
211 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.60288 |
212 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.54605E-003 |
213 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.31046E-005 |
214 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 100.09533 |
215 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.83743 |
216 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
217 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04005 |
218 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.23368E-003 |
219 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
220 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2562077.56104 |
221 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.32751E-002 |
222 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 100.09533 |
223 | Coil:Heating:Electric | VAV_MID WITH REHEAT HEATING COIL | Design Size Nominal Capacity [W] | 0.00000 |
224 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 100.09533 |
225 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.32751E-002 |
226 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.49867E-006 |
227 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 11.24881 |
228 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.25245 |
229 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
230 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.04897 |
231 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.09991E-003 |
232 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
233 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 275101.77029 |
234 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.86788E-003 |
235 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 11.24881 |
236 | Coil:Heating:Electric | VAV_TOP WITH REHEAT HEATING COIL | Design Size Nominal Capacity [W] | 0.00000 |
237 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 11.24881 |
238 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.86788E-003 |
239 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.05234E-005 |
240 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.98771 |
241 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
242 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.61428 |
243 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
244 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.02850 |
245 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.17392E-003 |
246 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.00000E-003 |
247 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 143256.61555 |
248 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.09712E-003 |
249 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.98771 |
250 | Coil:Heating:Electric | CAV_BAS HEATING COIL | Design Size Nominal Capacity [W] | 271237.24119 |
251 | Fan:VariableVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.98771 |
252 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.09712E-003 |
253 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.16226E-004 |
254 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 24.70879 |
255 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
256 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.70879 |
257 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 517977.00844 |
258 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 330538.90896 |
259 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.26852E-002 |
260 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 24.70879 |
261 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 24.70879 |
262 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 24.70879 |
263 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 24.70879 |
264 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 517977.00844 |
265 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 517977.00844 |
266 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 11172.98038 |
267 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
268 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 24.70879 |
269 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 24.70879 |
270 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 517977.00844 |
271 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.26852E-002 |
272 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 11172.98038 |
273 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 2.60230E-005 |
274 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
275 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
276 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
277 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.48022 |
278 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
279 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48022 |
280 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10119.96291 |
281 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6428.65102 |
282 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.47837E-004 |
283 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.48022 |
284 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.48022 |
285 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.48022 |
286 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.48022 |
287 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10119.96291 |
288 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10119.96291 |
289 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 516.14541 |
290 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
291 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.48022 |
292 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48022 |
293 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 10119.96291 |
294 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.47837E-004 |
295 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 516.14541 |
296 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.57968 |
297 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
298 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.57968 |
299 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 96567.15007 |
300 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 61320.05400 |
301 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.36492E-003 |
302 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.57968 |
303 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.57968 |
304 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.57968 |
305 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.57968 |
306 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 96567.15007 |
307 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 96567.15007 |
308 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 5161.45407 |
309 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
310 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.57968 |
311 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.57968 |
312 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 96567.15007 |
313 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.36492E-003 |
314 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 5161.45407 |
315 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.46081 |
316 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
317 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46081 |
318 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9724.66228 |
319 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6173.17600 |
320 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.38156E-004 |
321 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.46081 |
322 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.46081 |
323 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.46081 |
324 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.46081 |
325 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9724.66228 |
326 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9724.66228 |
327 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 516.14541 |
328 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
329 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.46081 |
330 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46081 |
331 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9724.66228 |
332 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.38156E-004 |
333 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 516.14541 |
334 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 9.27861E-002 |
335 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 15149.14230 |
336 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 9.27861E-002 |
337 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 11.13434 |
338 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 9.27861E-002 |
339 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 9.27861E-002 |
340 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 389470.00908 |
341 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
342 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 9.27861E-002 |
343 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 11.13434 |
344 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 4.63931E-002 |
345 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 5244.13105 |
346 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 4.63931E-002 |
347 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 5244.13105 |
348 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 9.27861E-002 |
349 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.67777E-002 |
350 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1635589.42406 |
351 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1635589.13500 |
352 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 8.21618E-002 |
353 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 9.27861E-002 |
354 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.67777E-002 |
355 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1635589.42406 |
356 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1635589.13500 |
357 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 8.21618E-002 |
358 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.55361E-002 |
359 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.86434 |
360 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.55361E-002 |
361 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3962.49275 |
362 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.55361E-002 |
363 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 154262.34953 |
364 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at High Fan Speed [W/K] | 78091.95086 |
365 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 77131.17476 |
366 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
367 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/K] | 46855.17052 |
368 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 639955.79579 |
369 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 627621.66000 |
370 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.55361E-002 |
371 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
372 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
373 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
374 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
375 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
376 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.16432 |
377 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 19.71883 |
378 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.16432 |
379 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 40682.87596 |
380 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 62.81081 |
381 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1957832.92833 |
382 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 12.56216 |
383 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 244729.11604 |
384 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 62.81081 |
385 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1957832.92833 |
386 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 12.56216 |
387 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 244729.11604 |
388 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 27 | 8.48175E-002 |
389 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 27 | 8.48175E-002 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 308054.32 | 207337.04 | 100717.28 | 0.67 | 65887.95 | 668.27 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2935876.84 | 1969204.93 | 966671.91 | 0.67 | 616043.25 | 6248.25 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 325032.14 | 219207.15 | 105824.98 | 0.67 | 70538.25 | 715.44 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 172232.53 | 116358.50 | 55874.04 | 0.68 | 38607.65 | 391.58 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 9.21 | 31.42 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 9.21 | 31.42 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.22 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.22 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.22 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.22 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.22 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.22 | N/A | 2.831 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.22 | N/A | 2.831 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.22 | N/A | 2.831 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.22 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.22 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.22 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.22 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.22 | N/A | 2.831 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.22 | N/A | 2.831 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.22 | N/A | 2.831 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.22 | N/A | 2.831 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.22 | N/A | 2.831 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.22 | N/A | 2.831 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.22 | N/A | 2.831 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.22 | N/A | 2.831 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_NORTH_0.22 | N/A | 2.831 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_EAST_0.22 | N/A | 2.831 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_SOUTH_0.22 | N/A | 2.831 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.498_SHGC_WEST_0.22 | N/A | 2.831 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 5.069 | 2.882 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2417242170 | 0.2684642216 | Pass | Pass | 0.9602645223 | 5.3669073757 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.1502908600 | 0.2383802262 | Pass | Pass | 9.8397407364E-002 | 0.2967694731 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 4.0232102213E-002 | 0.1285500509 | Pass | Pass | 1.5053962164E-002 | 0.1219906544 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 1.7928583385E-002 | 1.1417919539E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1329499692 | 0.1867021252 | Pass | Pass | 9.8279620629E-002 | 0.2963440032 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1656719491 | 0.2355627587 | Pass | Pass | 9.8383181134E-002 | 0.2963601646 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1694730116 | 0.2349124238 | Pass | Pass | 0.1013429056 | 0.2996931544 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2083409655 | 0.3213663498 | Pass | Pass | 0.1018679241 | 0.3030643807 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 5.5445696296E-002 | 0.1007199730 | Pass | Pass | 1.4484334176E-002 | 0.1195370548 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 6.8383493151E-002 | 0.1360843569 | Pass | Pass | 1.4480501280E-002 | 0.1195268899 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 9.5076289646E-002 | 0.1437573332 | Pass | Pass | 1.4567315725E-002 | 0.1198793224 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 8.3854703309E-002 | 0.1590818200 | Pass | Pass | 1.4250310308E-002 | 0.1185455584 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.9202820460E-002 | 2.7005572925E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.2684475935E-002 | 2.6068538385E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 6.9183529513E-002 | 5.6048105561E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 5.9505268659E-002 | 4.3238848590E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.7169854549E-002 | 3.8706063124E-002 | Pass | Pass | 0.1523065029 | 0.4898343981 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.1451510282E-002 | 2.2132538529E-002 | Pass | Pass | 1.3516391058E-002 | 8.6189419840E-002 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.0957577562E-002 | 3.4948791335E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.1070424481E-004 | 1.6875357590E-004 | Pass | Pass | 2.1939290903E-003 | 2.2568320709E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 7.9467779525E-005 | 1.1900556178E-004 | Pass | Pass | 5.6550655658E-003 | 3.1905051620E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.9250989804E-005 | 1.0380634059E-004 | Pass | Pass | 1.7701676762E-002 | 7.4573044303E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.3704098906E-004 | 4.0633678929E-004 | Pass | Pass | 6.2940058442E-005 | 1.1302162970E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:45
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3637.19 | -63.3 | 0.00 | -7643.4 | 47996.54 | 43927.06 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:45
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.40 | 26 | |||
Feb | 9.60 | 38 | |||
Mar | 3.60 | 37 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 1.20 | 13 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 18.00 | 37 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:45
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 2.882 | 5.069 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 2.882 | 5.069 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.498_SHGC_NORTH_0.22 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.498_SHGC_NORTH_0.22 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.498_SHGC_NORTH_0.22 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.498_SHGC_NORTH_0.22 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.498_SHGC_NORTH_0.22 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.498_SHGC_EAST_0.22 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.498_SHGC_EAST_0.22 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.498_SHGC_EAST_0.22 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.498_SHGC_WEST_0.22 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.498_SHGC_WEST_0.22 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.498_SHGC_WEST_0.22 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.831 | 0.221 | 0.243 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.498_SHGC_NORTH_0.22 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.831 | 0.221 | 0.243 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.498_SHGC_EAST_0.22 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.831 | 0.221 | 0.243 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.831 | 0.221 | 0.243 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.498_SHGC_WEST_0.22 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.831 | 0.221 | 0.243 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.498_SHGC_NORTH_0.22 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.831 | 0.221 | 0.243 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.498_SHGC_EAST_0.22 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.831 | 0.221 | 0.243 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.498_SHGC_SOUTH_0.22 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.831 | 0.221 | 0.243 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.498_SHGC_WEST_0.22 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.831 | 0.221 | 0.243 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.831 | 0.221 | 0.243 | |||||||||||||||||
North Total or Average | 1390.74 | 2.831 | 0.221 | 0.243 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.831 | 0.221 | 0.243 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:45
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:45
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.6849 | 2779.43 | 24139.15 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 216.17 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 8.6849 | 2496.12 | 21678.66 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 194.14 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 8.6849 | 24961.20 | 216786.56 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 1941.36 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 8.6849 | 2496.12 | 21678.66 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 194.14 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 8.6849 | 313.41 | 2721.97 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.18 | 0.0000 | Y | 13.89 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.04 | 0.0000 | Y | 8.90 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 8.6849 | 313.42 | 2722.03 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.76 | 0.0000 | Y | 13.67 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.06 | 0.0000 | Y | 8.91 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 8.6849 | 3134.13 | 27219.72 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.12 | 0.0000 | Y | 138.56 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 8.6849 | 2019.75 | 17541.42 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.99 | 0.0000 | Y | 88.88 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 8.6849 | 3134.20 | 27220.31 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.73 | 0.0000 | Y | 136.56 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 8.6849 | 2019.75 | 17541.42 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.00 | 0.0000 | Y | 88.92 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 8.6849 | 313.41 | 2721.97 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.12 | 0.0000 | Y | 13.85 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.99 | 0.0000 | Y | 8.89 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 8.6849 | 313.42 | 2722.03 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.73 | 0.0000 | Y | 13.66 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.00 | 0.0000 | Y | 8.89 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 8.6849 | 783.68 | 6806.21 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 62.65 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 13.9016 | 36.20 | 503.28 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.16 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 13.9016 | 362.03 | 5032.75 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 51.55 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 13.9016 | 36.20 | 503.28 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.16 |
Interior Lighting Total | 8.7339 | 46320.38 | 404555.99 | 1012.66 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13271.55 | AstronomicalClock | - | 41.85 | 41.85 | 104.26 | |
EXTERIOR_LIGHTS_B | 989.48 | AstronomicalClock | - | 83.85 | 62.85 | 11.67 | |
EXTERIOR_LIGHTS_C | 26594.85 | AstronomicalClock | - | 83.85 | 46.68 | 233.05 | |
Exterior Lighting Total | 40855.88 | 348.98 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:45
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 3234292.49 | |||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1635589.14 | 6.01 | 1626474.91 | 5.99 | 9.21 | 31.42 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 1635589.14 | 6.01 | 1626474.91 | 5.99 | 9.21 | 31.42 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 642888.34 | |||||
CENTRAL BOILER | Boiler:HotWater | 627621.66 | 1.00 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1957832.93 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1957832.93 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 263849.23 | 308054.32 | 207337.04 | 100717.28 | 0.67 | - | 65887.95 | 668.27 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2562077.56 | 2935876.84 | 1969204.93 | 966671.91 | 0.67 | - | 616043.25 | 6248.25 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 275101.77 | 325032.14 | 219207.15 | 105824.98 | 0.67 | - | 70538.25 | 715.44 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 143256.62 | 172232.53 | 116358.50 | 55874.04 | 0.68 | - | 38607.65 | 391.58 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 517977.01 | 330538.91 | 187438.10 | 0.64 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10119.96 | 6428.65 | 3691.31 | 0.64 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 96567.15 | 61320.05 | 35247.10 | 0.63 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9724.66 | 6173.18 | 3551.49 | 0.63 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 66111.55 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 651652.88 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 67118.35 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8819.94 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7376.15 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9870.24 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9567.80 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 101283.76 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 76711.31 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 101135.73 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 84683.01 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12846.00 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8497.59 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 12824.27 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9036.82 | 1.00 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Electric | 6420.31 | 1.00 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Electric | 0.00 | 1.00 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Electric | 0.00 | 1.00 | |
CAV_BAS HEATING COIL | Coil:Heating:Electric | 271237.24 | 1.00 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 517977.01 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10119.96 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 96567.15 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9724.66 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 11172.98 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 516.15 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 5161.45 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 516.15 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 10.60 | 22790.51 | 2149.46 | 1.00 | 1.12 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 100.10 | 216300.67 | 2160.95 | 1.00 | 1.08 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 11.25 | 24178.92 | 2149.46 | 1.00 | 1.12 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 |
CAV_BAS FAN | Fan:VariableVolume | 0.60 | 1314.72 | 5.99 | 13022.59 | 2174.89 | 1.00 | 1.13 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 24.71 | 40750.89 | 1649.25 | 1.00 | 1.14 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.48 | 537.90 | 1120.11 | 1.00 | 1.62 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.58 | 5129.74 | 1120.11 | 1.00 | 1.16 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.46 | 516.15 | 1120.11 | 1.00 | 1.64 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.092786 | 15149.14 | 163269.45 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.046393 | 5244.13 | 113036.94 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.046393 | 5244.13 | 113036.94 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.015536 | 3962.49 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.164324 | 40682.88 | 247577.87 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:45
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 82881.48 | 82881.48 | 29.82 | 5.988 | 5.988 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00742 | 35.62 | 0.01077 | 1.200 | 0.00 |
CORE_BOTTOM | 87305.04 | 87305.04 | 34.98 | 6.307 | 6.307 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00736 | 35.62 | 0.01077 | 1.078 | 0.00 |
CORE_MID | 831595.20 | 831595.20 | 333.16 | 60.063 | 60.063 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00737 | 35.62 | 0.01077 | 10.778 | 0.00 |
CORE_TOP | 83843.64 | 83843.64 | 33.59 | 6.056 | 6.056 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00737 | 35.62 | 0.01077 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 18123.59 | 18123.59 | 57.83 | 1.321 | 1.321 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00724 | 42.80 | 0.01078 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 15156.87 | 15156.87 | 75.04 | 1.105 | 1.105 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 24.00 | 24.00 | 0.00719 | 39.36 | 0.01078 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 20281.82 | 20281.82 | 64.71 | 1.478 | 1.478 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00722 | 42.80 | 0.01078 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 19660.46 | 19660.46 | 97.34 | 1.433 | 1.433 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 24.00 | 24.00 | 0.00715 | 41.96 | 0.01078 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 179022.60 | 179022.60 | 571.20 | 13.049 | 13.049 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00729 | 42.70 | 0.01078 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 157627.09 | 157627.09 | 780.43 | 11.490 | 11.490 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 24.00 | 24.00 | 0.00722 | 39.60 | 0.01078 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 200165.37 | 200165.37 | 638.65 | 14.590 | 14.590 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00726 | 42.80 | 0.01078 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 174007.68 | 174007.68 | 861.53 | 12.684 | 12.684 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00720 | 41.83 | 0.01078 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 19715.25 | 19715.25 | 62.91 | 1.437 | 1.437 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 24.00 | 24.00 | 0.00728 | 42.61 | 0.01078 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 16165.42 | 16165.42 | 80.04 | 1.178 | 1.178 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 24.00 | 24.00 | 0.00722 | 39.84 | 0.01078 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 21733.95 | 21733.95 | 69.34 | 1.584 | 1.584 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 24.00 | 0.00725 | 42.80 | 0.01078 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 18568.84 | 18568.84 | 91.94 | 1.354 | 1.354 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 24.00 | 24.00 | 0.00719 | 41.96 | 0.01078 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8353.98 | 8353.98 | 230.76 | 0.480 | 0.480 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:10:00 | 27.00 | 27.00 | 0.00700 | 33.13 | 0.01077 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 79668.95 | 79668.95 | 2200.63 | 4.580 | 4.580 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 27.00 | 27.00 | 0.00700 | 33.16 | 0.01077 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8015.34 | 8015.34 | 221.40 | 0.461 | 0.461 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | 27.00 | 27.00 | 0.00709 | 40.63 | 0.01078 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 373734.48 | 429794.66 | 548.43 | 21.486 | 24.709 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 33.97 | 0.01077 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | 00:10:00 | 15.60 | 26.40 | 0.00915 | 12.70 | 0.00915 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | 00:10:00 | 15.60 | 23.80 | 0.00915 | 12.70 | 0.00915 | 1.078 | 0.00 | |
CORE_MID | 156648.17 | 156648.17 | 62.76 | 6.550 | 10.778 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 12.70 | 0.00915 | 10.778 | 0.00 |
CORE_TOP | 28541.90 | 28541.90 | 11.43 | 1.204 | 1.204 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 12.70 | 0.00915 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 112.11 | 112.11 | 0.36 | 0.005 | 0.135 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00881 | 12.70 | 0.00915 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 379.45 | 379.45 | 1.88 | 0.016 | 0.087 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00842 | 12.70 | 0.00915 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 1860.75 | 1860.75 | 5.94 | 0.079 | 0.135 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00825 | 12.70 | 0.00915 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 0.00 | 0.000 | 0.087 | 00:10:00 | 15.60 | 21.61 | 0.00915 | 12.70 | 0.00915 | 0.087 | 0.00 | |
PERIMETER_MID_ZN_3 | 71406.27 | 71406.27 | 227.83 | 3.034 | 3.034 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00814 | 12.70 | 0.00915 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 47600.08 | 47600.08 | 235.67 | 2.023 | 2.023 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00814 | 12.70 | 0.00915 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 71302.62 | 71302.62 | 227.50 | 3.030 | 3.030 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00814 | 12.70 | 0.00915 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 39725.11 | 39725.11 | 196.68 | 1.686 | 1.686 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00818 | 12.70 | 0.00915 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 9043.62 | 9043.62 | 28.86 | 0.385 | 0.385 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00811 | 12.70 | 0.00915 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 5981.58 | 5981.58 | 29.62 | 0.255 | 0.255 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00811 | 12.70 | 0.00915 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 9028.39 | 9028.39 | 28.81 | 0.384 | 0.384 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00811 | 12.70 | 0.00915 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 5236.86 | 5236.86 | 25.93 | 0.223 | 0.223 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00814 | 12.70 | 0.00915 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 27.00 | 0.00700 | 12.70 | 0.00915 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | 00:10:00 | 18.00 | 25.32 | 0.00701 | 12.70 | 0.00915 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 24.81 | 0.00824 | 12.70 | 0.00915 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | 00:10:00 | 18.00 | 27.00 | 0.00700 | 12.70 | 0.00915 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 10.60 | 10.60 | 1.52 | 1.52 | 10.6029 | 3.0478 | 10.6029 | 0.2875 | 0.3000 |
VAV_MID WITH REHEAT | 100.10 | 100.10 | 20.55 | 20.55 | 100.0953 | 29.8829 | 100.0953 | 0.2985 | 0.3000 |
VAV_TOP WITH REHEAT | 11.25 | 11.25 | 2.45 | 2.45 | 11.2488 | 3.1212 | 11.2488 | 0.2775 | 0.3000 |
CAV_BAS | 5.99 | 5.99 | 1.20 | 1.20 | 5.9877 | 1.2002 | 5.9877 | 0.2004 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.71 | 24.71 | 0.34 | 0.34 | 24.7088 | 24.7086 | 24.7088 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.48 | 0.48 | 0.02 | 0.02 | 0.4802 | 0.4802 | 0.4802 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.58 | 4.58 | 0.16 | 0.16 | 4.5797 | 4.5797 | 4.5797 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.46 | 0.46 | 0.02 | 0.02 | 0.4608 | 0.4608 | 0.4608 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 66111.551 | 66111.551 | -999.0 | -999.0 | -999.000 | 1/21 00:10:00 | 1/21 00:10:00 | 66111.55 | 35981.13 | 1.077825 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | ||
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 651652.878 | 651652.878 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 651652.88 | 359811.31 | 10.778248 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 156648.17 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 67118.351 | 67118.351 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 67118.35 | 40194.19 | 1.204028 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 28541.90 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 8819.944 | 8819.944 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8819.94 | 4517.79 | 0.135332 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00881237 | 56.8686 | 112.11 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 7376.149 | 7376.149 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7376.15 | 2911.44 | 0.087213 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00842054 | 54.3736 | 379.45 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 9870.240 | 9870.240 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9870.24 | 4517.89 | 0.135335 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00824675 | 53.2659 | 1860.75 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 9567.800 | 9567.800 | -999.0 | -999.0 | -999.000 | 1/21 00:10:00 | 1/21 00:10:00 | 9567.80 | 2911.44 | 0.087213 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | ||
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 101283.758 | 101283.758 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 101283.76 | 101283.76 | 3.033983 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00814407 | 52.6106 | 71406.27 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 76711.315 | 76711.315 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 76711.31 | 67533.59 | 2.022988 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00814119 | 52.5922 | 47600.08 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 101135.727 | 101135.727 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 101135.73 | 101135.73 | 3.029549 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00814458 | 52.6139 | 71302.62 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 84683.007 | 84683.007 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 84683.01 | 56276.39 | 1.685775 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00818278 | 52.8573 | 39725.11 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 12846.000 | 12846.000 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12846.00 | 12846.00 | 0.384806 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00811232 | 52.4082 | 9043.62 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 8497.588 | 8497.588 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8497.59 | 8497.59 | 0.254548 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00811035 | 52.3956 | 5981.58 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 12824.269 | 12824.269 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12824.27 | 12824.27 | 0.384155 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00811289 | 52.4118 | 9028.39 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 9036.822 | 9036.822 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9036.82 | 7434.55 | 0.222704 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 0.0000 | 21.00 | 0.00814441 | 52.6126 | 5236.86 | 0.00 | -999.00 | -999.00 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 263849.229 | -999.000 | 10.602876 | 0.00754605 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 263849.23 | 230504.60 | 10.602876 | 28.50 | 17.64 | 0.00814013 | 11.05 | 9.78 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 23.9387 | 24.00 | 0.00730835 | 39.4002 | 145416.53 | 0.00 | 264182.06 | 243627.85 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | VAV_BOT WITH REHEAT | 6420.315 | 6420.315 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 6420.31 | 6420.31 | 3.180863 | 11.13 | 11.13 | 0.00911909 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 79.7956 | 21.48 | 0.00871182 | 54.6001 | 0.00 | 0.00 | -999.00 | -999.00 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2562077.561 | -999.000 | 100.095328 | 0.07327509 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 2562077.56 | 2220270.46 | 100.095328 | 28.84 | 17.83 | 0.00823368 | 11.04 | 9.78 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 25.3578 | 24.00 | 0.00735061 | 39.6256 | 1353031.22 | 0.00 | 2565239.76 | 2342055.70 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | VAV_MID WITH REHEAT | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 0.00 | 0.00 | 30.028598 | 13.95 | 13.04 | 0.00898602 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 84.5259 | 21.00 | 0.00808999 | 52.2662 | 386682.24 | 0.00 | -999.00 | -999.00 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 275101.770 | -999.000 | 11.248812 | 0.00786788 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 275101.77 | 241040.91 | 11.248812 | 28.25 | 17.52 | 0.00809991 | 11.05 | 9.78 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 22.5641 | 24.00 | 0.00731570 | 39.4397 | 153908.46 | 0.00 | 275455.99 | 255032.16 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | VAV_TOP WITH REHEAT | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 0.00 | 0.00 | 3.374644 | 14.73 | 13.25 | 0.00888240 | 12.80 | 11.59 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 75.2136 | 21.00 | 0.00805993 | 52.0745 | 57832.35 | 0.00 | -999.00 | -999.00 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 143256.616 | -999.000 | 5.987707 | 0.00409712 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 143256.62 | 123941.74 | 5.987707 | 27.61 | 17.37 | 0.00817392 | 11.03 | 9.77 | 0.00700000 | 40.57 | 0.01077797 | 23.25 | 20.0437 | 24.00 | 0.00744715 | 40.1397 | 81721.88 | 0.00 | 143453.08 | 131168.88 |
CAV_BAS HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | CAV_BAS | 271237.241 | 271237.241 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 271237.24 | 271237.24 | 5.987707 | 2.55 | 2.55 | 0.00915345 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 20.0437 | 26.40 | 0.00915345 | 42.6473 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 517977.008 | 330538.909 | 24.708786 | 0.01268522 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | 468622.15 | 463173.18 | -999.0 | 28.61 | 16.80 | 0.00709322 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | -999.0000 | 27.00 | 0.00704194 | 31.7841 | 373237.28 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10119.963 | 6428.651 | 0.480219 | 0.00024784 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:10:00 | 9165.66 | 8926.35 | -999.0 | 28.43 | 16.84 | 0.00721059 | 12.80 | 10.55 | 0.00700000 | 41.70 | 0.01077992 | 23.56 | -999.0000 | 27.00 | 0.00708816 | 31.9885 | 8199.36 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 96567.150 | 61320.054 | 4.579684 | 0.00236492 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 87469.39 | 85080.97 | -999.0 | 28.42 | 16.84 | 0.00722036 | 12.80 | 10.55 | 0.00700000 | 40.63 | 0.01077808 | 23.27 | -999.0000 | 27.00 | 0.00709230 | 32.0072 | 78262.33 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9724.662 | 6173.176 | 0.460805 | 0.00023816 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | 8810.05 | 8574.96 | -999.0 | 28.45 | 16.85 | 0.00721553 | 12.80 | 10.55 | 0.00700000 | 41.83 | 0.01078014 | 23.60 | -999.0000 | 27.00 | 0.00709024 | 31.9979 | 8008.23 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 517977.008 | 517977.008 | 24.708786 | 0.01268522 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 517977.01 | 517977.01 | 24.708786 | 12.70 | 12.70 | 0.00915345 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 1.3695 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10119.963 | 10119.963 | 0.480219 | 0.00024784 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10119.96 | 10119.96 | 0.480219 | 12.70 | 12.70 | 0.00915345 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.2553 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 96567.150 | 96567.150 | 4.579684 | 0.00236492 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 96567.15 | 96567.15 | 4.579684 | 12.70 | 12.70 | 0.00915345 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.4134 | 25.32 | 0.00701061 | 34.9495 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9724.662 | 9724.662 | 0.460805 | 0.00023816 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9724.66 | 9724.66 | 0.460805 | 12.70 | 12.70 | 0.00915345 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.3924 | 24.81 | 0.00824360 | 42.2805 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 11172.980 | 11172.980 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 11172.98 | 11172.98 | 24.708786 | 0.17 | 0.17 | 0.00702949 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 1.3695 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 516.145 | 516.145 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 516.15 | 516.15 | 0.480219 | 0.41 | 0.41 | 0.00707010 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.2553 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 5161.454 | 5161.454 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 5161.45 | 5161.45 | 4.579684 | 0.43 | 0.43 | 0.00708375 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.4134 | 25.32 | 0.00701061 | 34.9495 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 516.145 | 516.145 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 516.15 | 516.15 | 0.460805 | 0.43 | 0.43 | 0.00827446 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 3.3924 | 24.81 | 0.00824360 | 42.2805 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:45
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 66111.551 | 66111.551 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 66111.55 | 35981.13 | 1.0000 | 1.29726454 | 1.077825 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 66111.55 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 651652.878 | 651652.878 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 651652.88 | 359811.31 | 1.0000 | 12.97264538 | 10.778248 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 651652.88 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.60 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 156648.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 67118.351 | 67118.351 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 67118.35 | 40194.19 | 1.0000 | 1.44916214 | 1.204028 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 67118.35 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 28541.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 8819.944 | 8819.944 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8819.94 | 4517.79 | 1.0000 | 0.16288451 | 0.135332 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8819.94 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00881237 | 21.00 | 0.00881237 | 56.8686 | 112.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 7376.149 | 7376.149 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7376.15 | 2911.44 | 1.0000 | 0.10496897 | 0.087213 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7376.15 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.97 | 0.00842054 | 21.00 | 0.00842054 | 54.3736 | 379.45 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 9870.240 | 9870.240 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9870.24 | 4517.89 | 1.0000 | 0.16288807 | 0.135335 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9870.24 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.90 | 0.00824675 | 21.00 | 0.00824675 | 53.2659 | 1860.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 9567.800 | 9567.800 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 1/21 00:10:00 | unknown | unknown | 1/21 00:10:00 | Sensible | 9567.80 | 2911.44 | 1.0000 | 0.10496897 | 0.087213 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9567.80 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 101283.758 | 101283.758 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 101283.76 | 101283.76 | 1.0000 | 3.65168698 | 3.033983 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 101283.76 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.92 | 0.00814407 | 21.00 | 0.00814407 | 52.6106 | 71406.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 76711.315 | 76711.315 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 76711.31 | 67533.59 | 1.0000 | 2.43485781 | 2.022988 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 76711.31 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00814119 | 21.00 | 0.00814119 | 52.5922 | 47600.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 101135.727 | 101135.727 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 101135.73 | 101135.73 | 1.0000 | 3.64634986 | 3.029549 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 101135.73 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.92 | 0.00814458 | 21.00 | 0.00814458 | 52.6139 | 71302.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 84683.007 | 84683.007 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 84683.01 | 56276.39 | 1.0000 | 2.02899018 | 1.685775 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 84683.01 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.92 | 0.00818278 | 21.00 | 0.00818278 | 52.8573 | 39725.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 12846.000 | 12846.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12846.00 | 12846.00 | 1.0000 | 0.46314998 | 0.384806 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12846.00 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00811232 | 21.00 | 0.00811232 | 52.4082 | 9043.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 8497.588 | 8497.588 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 8497.59 | 8497.59 | 1.0000 | 0.30637224 | 0.254548 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8497.59 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00811035 | 21.00 | 0.00811035 | 52.3956 | 5981.58 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 12824.269 | 12824.269 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12824.27 | 12824.27 | 1.0000 | 0.46236648 | 0.384155 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 12824.27 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00811289 | 21.00 | 0.00811289 | 52.4118 | 9028.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 9036.822 | 9036.822 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9036.82 | 7434.55 | 1.0000 | 0.26804537 | 0.222704 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9036.82 | 12.70 | 0.00915345 | 12.70 | 0.00000000 | 0.0000 | 20.91 | 0.00814441 | 21.00 | 0.00814441 | 52.6126 | 5236.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 263849.229 | -999.000 | 10.602876 | 0.00754605 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9721 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.602876 | 12.76156795 | 4197.9300 | 999.8980 | 92.77668019 | 15.00 | 6.67 | 8.33 | 3244285.18 | 8.1327 | 8.132738 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 263849.23 | 230504.60 | 1.0000 | 12.76156795 | 10.602876 | 28.50 | 17.64 | 0.00814013 | 49428.2 | 11.05 | 9.78 | 0.00700000 | 28752.9 | 7.54528477 | 6.67 | 15.00 | 8.33 | 22790.506 | 241058.72 | 42.80 | 0.01078182 | 23.86 | 2.53819000 | 23.9387 | 24.00 | 0.00730835 | 24.00 | 0.00730835 | 39.4002 | 145416.53 | 0.00 | 264182.06 | 243627.85 | 12.76156795 | 28.50 | 17.65 | 0.00814013 | 49428.2 | 9.78 | 9.76 | 0.00750077 | 28726.9 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6420.315 | 6420.315 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.602876 | 12.76156795 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 6420.31 | 6420.31 | 1.0000 | 3.82847039 | 3.180863 | 11.13 | 11.13 | 0.00911909 | 34180.0 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6420.31 | 12.70 | 0.00915345 | 12.70 | 2.53819000 | 79.7956 | 4.93 | 0.00898340 | 21.48 | 0.00871182 | 54.6001 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2562077.561 | -999.000 | 100.095328 | 0.07327509 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1460 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 100.095328 | 120.47423456 | 4197.9300 | 999.8980 | 92.77668019 | 15.00 | 6.67 | 8.33 | 3244285.18 | 78.9720 | 78.972021 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 2562077.56 | 2220270.46 | 1.0000 | 120.47423456 | 100.095328 | 28.84 | 17.83 | 0.00823368 | 50010.3 | 11.04 | 9.78 | 0.00700000 | 28743.7 | 73.26761910 | 6.67 | 15.00 | 8.33 | 216300.673 | 2345776.89 | 42.80 | 0.01078182 | 23.86 | 25.38195000 | 25.3578 | 24.00 | 0.00735061 | 24.00 | 0.00735061 | 39.6256 | 1353031.22 | 0.00 | 2565239.76 | 2342055.70 | 120.47423456 | 28.84 | 17.84 | 0.00823368 | 50010.3 | 9.78 | 9.76 | 0.00749828 | 28717.5 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 100.095328 | 120.47423456 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 0.00 | 0.00 | 1.0000 | 36.14227037 | 30.028598 | 13.95 | 13.04 | 0.00898602 | 36719.8 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 0.00 | 12.70 | 0.00915345 | 12.70 | 25.38195000 | 84.5259 | 20.75 | 0.00807148 | 21.00 | 0.00808999 | 52.2662 | 386682.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 275101.770 | -999.000 | 11.248812 | 0.00786788 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.8973 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.248812 | 13.53901343 | 4197.9300 | 999.8980 | 92.77668019 | 15.00 | 6.67 | 8.33 | 3244285.18 | 8.4796 | 8.479580 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | Sensible | 275101.77 | 241040.91 | 1.0000 | 13.53901343 | 11.248812 | 28.25 | 17.52 | 0.00809991 | 49072.0 | 11.05 | 9.78 | 0.00700000 | 28752.8 | 7.86707320 | 6.67 | 15.00 | 8.33 | 24178.922 | 250922.85 | 42.80 | 0.01078182 | 23.86 | 2.53819000 | 22.5641 | 24.00 | 0.00731570 | 24.00 | 0.00731570 | 39.4397 | 153908.46 | 0.00 | 275455.99 | 255032.16 | 13.53901343 | 28.25 | 17.53 | 0.00809991 | 49072.0 | 9.78 | 9.76 | 0.00750109 | 28726.6 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.248812 | 13.53901343 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 0.00 | 0.00 | 1.0000 | 4.06170403 | 3.374644 | 14.73 | 13.25 | 0.00888240 | 37259.3 | 12.80 | 11.59 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 0.00 | 12.70 | 0.00915345 | 12.70 | 2.53819000 | 75.2136 | 20.89 | 0.00805993 | 21.00 | 0.00805993 | 52.0745 | 57832.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 143256.616 | -999.000 | 5.987707 | 0.00409712 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.0349 | 1004.8586 | 1.2036 | CAV_BAS FAN | Fan:VariableVolume | 5.987707 | 7.20677403 | 4197.9300 | 999.8980 | 92.77668019 | 15.00 | 6.67 | 8.33 | 3244285.18 | 4.4157 | 4.415660 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 143256.62 | 123941.74 | 1.0000 | 7.20677403 | 5.987707 | 27.61 | 17.37 | 0.00817392 | 48610.0 | 11.03 | 9.77 | 0.00700000 | 28732.0 | 4.09670312 | 6.67 | 15.00 | 8.33 | 13022.594 | 130234.02 | 40.57 | 0.01077797 | 23.25 | 1.20015641 | 20.0437 | 24.00 | 0.00744715 | 24.00 | 0.00744715 | 40.1397 | 81721.88 | 0.00 | 143453.08 | 131168.88 | 7.20677403 | 27.61 | 17.37 | 0.00817392 | 48610.0 | 9.77 | 9.75 | 0.00749728 | 28704.7 | |
CAV_BAS HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 271237.241 | 271237.241 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | CAV_BAS FAN | Fan:VariableVolume | 5.987707 | 7.20677403 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 271237.24 | 271237.24 | 1.0000 | 7.20677403 | 5.987707 | 2.55 | 2.55 | 0.00915345 | 25493.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 271237.24 | 12.70 | 0.00915345 | 12.70 | 1.20015641 | 20.0437 | 0.00 | 0.00915345 | 26.40 | 0.00915345 | 42.6473 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 517977.008 | 330538.909 | 24.708786 | 0.01268522 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.0259 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | Sensible | 468622.15 | 463173.18 | 0.9047 | -999.0 | -999.0 | 28.61 | 16.80 | 0.00709322 | 46864.4 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 468622.15 | 42.80 | 0.01078182 | 23.86 | 0.33839277 | -999.0000 | 27.00 | 0.00704194 | 27.00 | 0.00704194 | 31.7841 | 373237.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10119.963 | 6428.651 | 0.480219 | 0.00024784 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.2441 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:10:00 | Sensible | 9165.66 | 8926.35 | 0.9057 | -999.0 | -999.0 | 28.43 | 16.84 | 0.00721059 | 46986.1 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9165.66 | 41.70 | 0.01077992 | 23.56 | 0.01563234 | -999.0000 | 27.00 | 0.00708816 | 27.00 | 0.00708816 | 31.9885 | 8199.36 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 96567.150 | 61320.054 | 4.579684 | 0.00236492 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.2623 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | Sensible | 87469.39 | 85080.97 | 0.9058 | -999.0 | -999.0 | 28.42 | 16.84 | 0.00722036 | 46996.9 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 87469.39 | 40.63 | 0.01077808 | 23.27 | 0.15632344 | -999.0000 | 27.00 | 0.00709230 | 27.00 | 0.00709230 | 32.0072 | 78262.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9724.662 | 6173.176 | 0.460805 | 0.00023816 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1018.2533 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | Sensible | 8810.05 | 8574.96 | 0.9059 | -999.0 | -999.0 | 28.45 | 16.85 | 0.00721553 | 47015.1 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8810.05 | 41.83 | 0.01078014 | 23.60 | 0.01563234 | -999.0000 | 27.00 | 0.00709024 | 27.00 | 0.00709024 | 31.9979 | 8008.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 517977.008 | 517977.008 | 24.708786 | 0.01268522 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 517977.01 | 517977.01 | 1.0000 | 29.73937025 | 24.708786 | 12.70 | 12.70 | 0.00915345 | 35869.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 517977.01 | 12.70 | 0.00915345 | 12.70 | 0.33839277 | 1.3695 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10119.963 | 10119.963 | 0.480219 | 0.00024784 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 10119.96 | 10119.96 | 1.0000 | 0.57798950 | 0.480219 | 12.70 | 12.70 | 0.00915345 | 35869.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10119.96 | 12.70 | 0.00915345 | 12.70 | 0.01563234 | 3.2553 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 96567.150 | 96567.150 | 4.579684 | 0.00236492 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 96567.15 | 96567.15 | 1.0000 | 5.51208411 | 4.579684 | 12.70 | 12.70 | 0.00915345 | 35869.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 96567.15 | 12.70 | 0.00915345 | 12.70 | 0.15632344 | 3.4134 | 0.00 | 0.00701061 | 25.32 | 0.00701061 | 34.9495 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9724.662 | 9724.662 | 0.460805 | 0.00023816 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9724.66 | 9724.66 | 1.0000 | 0.55462304 | 0.460805 | 12.70 | 12.70 | 0.00915345 | 35869.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9724.66 | 12.70 | 0.00915345 | 12.70 | 0.01563234 | 3.3924 | 0.00 | 0.00824360 | 24.81 | 0.00824360 | 42.2805 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 11172.980 | 11172.980 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 24.708786 | 29.73937025 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 11172.98 | 11172.98 | 1.0000 | 29.73937025 | 24.708786 | 0.17 | 0.17 | 0.00702949 | 17757.4 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11172.98 | 12.70 | 0.00915345 | 12.70 | 0.33839277 | 1.3695 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 516.145 | 516.145 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.480219 | 0.57798950 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 516.15 | 516.15 | 1.0000 | 0.57798950 | 0.480219 | 0.41 | 0.41 | 0.00707010 | 18102.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 516.15 | 12.70 | 0.00915345 | 12.70 | 0.01563234 | 3.2553 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 31.5922 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 5161.454 | 5161.454 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.579684 | 5.51208411 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 5161.45 | 5161.45 | 1.0000 | 5.51208411 | 4.579684 | 0.43 | 0.43 | 0.00708375 | 18157.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 5161.45 | 12.70 | 0.00915345 | 12.70 | 0.15632344 | 3.4134 | 0.00 | 0.00701061 | 25.32 | 0.00701061 | 34.9495 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 516.145 | 516.145 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.460805 | 0.55462304 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 516.15 | 516.15 | 1.0000 | 0.55462304 | 0.460805 | 0.43 | 0.43 | 0.00827446 | 21133.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 516.15 | 12.70 | 0.00915345 | 12.70 | 0.01563234 | 3.3924 | 0.00 | 0.00824360 | 24.81 | 0.00824360 | 42.2805 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:45
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 5874.33 | 4147.17 | 4147.17 |
CORE_BOTTOM | 5837.67 | 139.83 | 139.00 |
CORE_MID | 5397.67 | 83.00 | 0.00 |
CORE_TOP | 5119.33 | 372.17 | 13.33 |
PERIMETER_BOT_ZN_3 | 5508.17 | 653.17 | 516.33 |
PERIMETER_BOT_ZN_2 | 5497.83 | 737.33 | 563.83 |
PERIMETER_BOT_ZN_1 | 5692.67 | 738.33 | 645.67 |
PERIMETER_BOT_ZN_4 | 5811.17 | 793.17 | 749.00 |
PERIMETER_MID_ZN_3 | 4847.33 | 978.83 | 293.83 |
PERIMETER_MID_ZN_2 | 4226.67 | 870.67 | 399.17 |
PERIMETER_MID_ZN_1 | 5494.33 | 680.67 | 448.33 |
PERIMETER_MID_ZN_4 | 5151.33 | 933.67 | 452.50 |
PERIMETER_TOP_ZN_3 | 4632.00 | 1280.17 | 331.83 |
PERIMETER_TOP_ZN_2 | 4912.50 | 1123.67 | 436.17 |
PERIMETER_TOP_ZN_1 | 5301.00 | 863.17 | 473.50 |
PERIMETER_TOP_ZN_4 | 4925.33 | 1168.50 | 468.00 |
DATACENTER_BOT_ZN_6 | 5943.00 | 2430.00 | 2430.00 |
DATACENTER_MID_ZN_6 | 5943.00 | 464.17 | 464.17 |
DATACENTER_TOP_ZN_6 | 5943.00 | 779.00 | 779.00 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5943.00 | 5943.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 6223.50 | 0.00 | 4169.00 |
CORE_BOTTOM | 0.00 | 88.17 | 0.00 | 2.83 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 331.17 | 0.00 | 99.83 |
PERIMETER_BOT_ZN_2 | 0.00 | 314.50 | 0.00 | 108.50 |
PERIMETER_BOT_ZN_1 | 0.00 | 327.67 | 0.00 | 124.33 |
PERIMETER_BOT_ZN_4 | 0.00 | 410.83 | 0.00 | 136.17 |
PERIMETER_MID_ZN_3 | 0.00 | 128.83 | 0.00 | 53.00 |
PERIMETER_MID_ZN_2 | 0.00 | 148.33 | 0.00 | 80.33 |
PERIMETER_MID_ZN_1 | 0.00 | 163.83 | 0.00 | 84.17 |
PERIMETER_MID_ZN_4 | 0.00 | 189.83 | 0.00 | 66.33 |
PERIMETER_TOP_ZN_3 | 0.00 | 145.50 | 0.00 | 57.67 |
PERIMETER_TOP_ZN_2 | 0.00 | 173.00 | 0.00 | 85.33 |
PERIMETER_TOP_ZN_1 | 0.00 | 177.50 | 0.00 | 85.33 |
PERIMETER_TOP_ZN_4 | 0.00 | 198.00 | 0.00 | 70.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 484.17 | 0.00 | 349.50 |
DATACENTER_MID_ZN_6 | 0.00 | 347.17 | 0.00 | 313.33 |
DATACENTER_TOP_ZN_6 | 0.00 | 357.17 | 0.00 | 311.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 69.50 | 0.00 | 69.50 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 6256.50 | 0.00 | 4193.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:45
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.91 | 149.60 | 6779.02 | 0.163 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.60 | 134.35 | 6849.35 | 0.486 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.60 | 134.35 | 6849.35 | 0.451 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.60 | 134.35 | 6849.35 | 0.446 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.98 | 16.87 | 860.00 | 0.627 | 0.017 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.50 | 10.87 | 554.22 | 0.746 | 0.017 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.98 | 16.87 | 860.02 | 0.747 | 0.017 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.50 | 10.87 | 554.22 | 0.933 | 0.017 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.98 | 16.87 | 860.00 | 0.696 | 0.039 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.93 | 10.87 | 554.22 | 0.870 | 0.043 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.98 | 16.87 | 860.02 | 0.890 | 0.039 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.50 | 10.87 | 554.22 | 0.966 | 0.041 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.98 | 16.87 | 860.00 | 0.684 | 0.049 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.50 | 10.87 | 554.22 | 0.880 | 0.050 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.98 | 16.87 | 860.02 | 0.860 | 0.049 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.50 | 10.87 | 554.22 | 0.936 | 0.050 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.589 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.589 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.589 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.46 | 42.18 | 1911.37 | 0.663 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.91 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.60 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.60 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.60 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.98 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.50 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.98 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.50 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.98 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.93 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.98 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.50 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.98 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.50 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.98 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.50 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.575 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.575 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.575 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.46 | 42.18 | 1911.37 | 0.647 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:45
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 61.91 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.60 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.60 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.60 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.98 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.50 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.98 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.50 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.98 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.93 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.98 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.50 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.98 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.50 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.98 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.50 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.46 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1026.00 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 6894265.03 | 0.00 | 6894265.03 | 0.00 | 6894265.03 | 37848132.68 | 7168.37 | 1591.63 | 0.00 | 118.36 |
CORE_BOTTOM | 24620382.68 | 0.00 | 24620382.68 | 0.00 | 24620382.68 | 33990283.35 | 7958.63 | 105.11 | 696.26 | 1493.72 |
CORE_MID | 0.21E+09 | 0.00 | 0.21E+09 | 0.00 | 0.21E+09 | 0.34E+09 | 8214.91 | 64.13 | 480.96 | 997.91 |
CORE_TOP | 21068375.36 | 0.00 | 21068375.36 | 0.00 | 21068375.36 | 33990283.35 | 8377.81 | 62.80 | 319.39 | 965.74 |
PERIMETER_BOT_ZN_3 | 3922588.26 | 0.00 | 3922588.26 | 144958.23 | 4067546.49 | 4267819.30 | 3257.63 | 244.62 | 5257.75 | 1493.72 |
PERIMETER_BOT_ZN_2 | 3012333.43 | 0.00 | 3012333.43 | 96638.75 | 3108972.19 | 2750345.05 | 2384.68 | 91.53 | 6283.79 | 1493.72 |
PERIMETER_BOT_ZN_1 | 4565483.69 | 0.00 | 4565483.69 | 144958.23 | 4710441.92 | 4267912.63 | 2169.41 | 52.33 | 6538.26 | 1493.72 |
PERIMETER_BOT_ZN_4 | 3817885.47 | 0.00 | 3817885.47 | 96638.75 | 3914524.23 | 2750345.05 | 1890.22 | 4.18 | 6865.60 | 1493.72 |
PERIMETER_MID_ZN_3 | 39619143.22 | 0.00 | 39619143.22 | 339958.49 | 39959101.71 | 42678193.03 | 3615.84 | 194.08 | 4950.08 | 997.91 |
PERIMETER_MID_ZN_2 | 33073210.08 | 0.00 | 33073210.08 | 226638.84 | 33299848.92 | 27503450.52 | 2664.23 | 23.66 | 6072.11 | 1906.91 |
PERIMETER_MID_ZN_1 | 49826022.16 | 0.00 | 49826022.16 | 339958.49 | 50165980.65 | 42679126.28 | 2648.98 | 11.26 | 6099.75 | 997.91 |
PERIMETER_MID_ZN_4 | 35928410.65 | 0.00 | 35928410.65 | 226638.84 | 36155049.49 | 27503450.52 | 2597.97 | 14.41 | 6147.61 | 997.91 |
PERIMETER_TOP_ZN_3 | 3924922.41 | 0.00 | 3924922.41 | 422083.30 | 4347005.71 | 4267819.30 | 3326.79 | 65.70 | 5367.51 | 965.74 |
PERIMETER_TOP_ZN_2 | 3233790.66 | 0.00 | 3233790.66 | 281388.67 | 3515179.34 | 2750345.05 | 2636.74 | 18.63 | 6104.63 | 965.74 |
PERIMETER_TOP_ZN_1 | 4849125.46 | 0.00 | 4849125.46 | 422083.30 | 5271208.76 | 4267912.63 | 2648.54 | 12.42 | 6099.04 | 965.74 |
PERIMETER_TOP_ZN_4 | 3497128.94 | 0.00 | 3497128.94 | 281388.67 | 3778517.61 | 2750345.05 | 2614.07 | 4.92 | 6141.01 | 965.74 |
DATACENTER_BOT_ZN_6 | 492981.60 | 0.00 | 492981.60 | 0.00 | 492981.60 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_MID_ZN_6 | 4929815.99 | 0.00 | 4929815.99 | 0.00 | 4929815.99 | 4929815.99 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_TOP_ZN_6 | 492981.60 | 0.00 | 492981.60 | 0.00 | 492981.60 | 492981.60 | 0.00 | 8760.00 | 0.00 | 2817.00 |
DATACENTER_BASEMENT_ZN_6 | 10671554.30 | 0.00 | 10671554.30 | 0.00 | 10671554.30 | 10671554.30 | 0.00 | 8760.00 | 0.00 | 2817.00 |
Total Facility | 0.39E+10 | 0.00 | 0.39E+10 | 13222084.47 | 0.39E+10 | 0.50E+10 | 8760.00 | 8760.00 | 7293.53 | 3726.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 0.2994 | 0.0000 | 0.2994 | 0.0000 | 0.2994 | 1.2002 | 4461.55 | 1481.45 | 0.00 |
CORE_BOTTOM | 0.8942 | 0.0000 | 0.8942 | 0.0000 | 0.8942 | 1.0778 | 5187.16 | 101.11 | 654.73 |
CORE_MID | 8.3028 | 0.0000 | 8.3028 | 0.0000 | 8.3028 | 10.7782 | 5403.32 | 63.95 | 475.73 |
CORE_TOP | 0.8208 | 0.0000 | 0.8208 | 0.0000 | 0.8208 | 1.0778 | 5562.76 | 62.80 | 317.44 |
PERIMETER_BOT_ZN_3 | 0.1446 | 0.0000 | 0.1446 | 0.0039 | 0.1484 | 0.1353 | 1887.99 | 171.01 | 3884.00 |
PERIMETER_BOT_ZN_2 | 0.1109 | 0.0000 | 0.1109 | 0.0026 | 0.1134 | 0.0872 | 1031.82 | 88.80 | 4822.38 |
PERIMETER_BOT_ZN_1 | 0.1724 | 0.0000 | 0.1724 | 0.0039 | 0.1762 | 0.1353 | 819.83 | 49.23 | 5073.93 |
PERIMETER_BOT_ZN_4 | 0.1387 | 0.0000 | 0.1387 | 0.0026 | 0.1413 | 0.0872 | 558.96 | 2.43 | 5381.60 |
PERIMETER_MID_ZN_3 | 1.6036 | 0.0000 | 1.6036 | 0.0090 | 1.6126 | 1.3533 | 1777.76 | 163.88 | 4001.36 |
PERIMETER_MID_ZN_2 | 1.2921 | 0.0000 | 1.2921 | 0.0063 | 1.2984 | 0.8721 | 784.40 | 14.80 | 4234.80 |
PERIMETER_MID_ZN_1 | 2.0528 | 0.0000 | 2.0528 | 0.0090 | 2.0618 | 1.3533 | 826.45 | 11.09 | 5105.46 |
PERIMETER_MID_ZN_4 | 1.4355 | 0.0000 | 1.4355 | 0.0060 | 1.4415 | 0.8721 | 776.44 | 14.28 | 5152.28 |
PERIMETER_TOP_ZN_3 | 0.1578 | 0.0000 | 0.1578 | 0.0112 | 0.1690 | 0.1353 | 1471.86 | 65.06 | 4406.08 |
PERIMETER_TOP_ZN_2 | 0.1307 | 0.0000 | 0.1307 | 0.0075 | 0.1382 | 0.0872 | 783.93 | 18.57 | 5140.50 |
PERIMETER_TOP_ZN_1 | 0.1985 | 0.0000 | 0.1985 | 0.0112 | 0.2097 | 0.1353 | 796.21 | 12.40 | 5134.39 |
PERIMETER_TOP_ZN_4 | 0.1392 | 0.0000 | 0.1392 | 0.0075 | 0.1466 | 0.0872 | 762.26 | 4.92 | 5175.82 |
DATACENTER_BOT_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1563 | 0.0000 | 0.1563 | 0.0000 | 0.1563 | 0.1563 | 0.00 | 5943.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0156 | 0.0000 | 0.0156 | 0.0000 | 0.0156 | 0.0156 | 0.00 | 5943.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.3384 | 0.0000 | 0.3384 | 0.0000 | 0.3384 | 0.3384 | 0.00 | 5943.00 | 0.00 |
Total Facility | 152.0071 | 0.0000 | 152.0071 | 0.3543 | 152.3614 | 158.4706 | 5943.00 | 5943.00 | 5550.27 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 57856801.62 | 0.00 | 57856801.62 | 48026705.38 | 1873.03 | 0.00 | 6886.97 | 1493.72 |
VAV_MID WITH REHEAT | 0.54E+09 | 0.00 | 0.54E+09 | 0.48E+09 | 2561.03 | 0.00 | 6198.97 | 997.91 |
VAV_TOP WITH REHEAT | 52981640.13 | 0.00 | 52981640.13 | 48026705.38 | 2607.05 | 0.00 | 6152.95 | 965.74 |
CAV_BAS | 9987352.82 | 0.00 | 9987352.82 | 37848132.68 | 7167.41 | 0.06 | 1592.53 | 118.36 |
AIRLOOP DATACENTER BASEMENT | 15459249.82 | 0.00 | 15459249.82 | 10671554.30 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER BOT | 714153.30 | 0.00 | 714153.30 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER MID | 7141532.97 | 0.00 | 7141532.97 | 4929815.99 | 0.00 | 0.00 | 8760.00 | 2817.00 |
AIRLOOP DATACENTER TOP | 714153.30 | 0.00 | 714153.30 | 492981.60 | 0.00 | 0.00 | 8760.00 | 2817.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 2.1160 | 0.0000 | 2.1160 | 1.5229 | 549.75 | 0.00 | 5393.25 |
VAV_MID WITH REHEAT | 21.3395 | 0.0000 | 21.3395 | 15.2292 | 741.93 | 0.00 | 5201.07 |
VAV_TOP WITH REHEAT | 2.0963 | 0.0000 | 2.0963 | 1.5229 | 755.79 | 0.00 | 5187.21 |
CAV_BAS | 0.4338 | 0.0000 | 0.4338 | 1.2002 | 4460.92 | 0.00 | 1482.08 |
AIRLOOP DATACENTER BASEMENT | 0.4902 | 0.0000 | 0.4902 | 0.3384 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER BOT | 0.0226 | 0.0000 | 0.0226 | 0.0156 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER MID | 0.2265 | 0.0000 | 0.2265 | 0.1563 | 0.00 | 0.00 | 5943.00 |
AIRLOOP DATACENTER TOP | 0.0226 | 0.0000 | 0.0226 | 0.0156 | 0.00 | 0.00 | 5943.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6886.97 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6198.97 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6152.95 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 1591.63 | 0.00 | 0.00 | 11.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.3318 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 24.3839 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 2.4018 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.7391 | 0.0000 | 0.0000 | 0.7785 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4902 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2265 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0226 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:45
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1432 |
Defaulted Fields | 1151 |
Fields with Defaults | 3678 |
Autosized Fields | 288 |
Autosizable Fields | 361 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 472 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:45
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 34260.78 | 347904.59 | 15-JAN-05:00 | 2414001.39 | 10-AUG-16:00 |
Electricity:Building | 17890.31 | 217232.45 | 29-MAY-17:20 | 1098534.19 | 14-DEC-17:00 |
Electricity:Zone:BASEMENT | 640.57 | 14055.89 | 01-JAN-00:10 | 32859.63 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 17890.31 | 217232.45 | 29-MAY-17:20 | 1098534.19 | 14-DEC-17:00 |
InteriorLights:Electricity | 3213.91 | 9976.29 | 29-MAY-17:20 | 325713.14 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:BASEMENT | 216.17 | 598.35 | 01-JAN-00:10 | 19402.09 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3213.91 | 9976.29 | 29-MAY-17:20 | 325713.14 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity | 3213.91 | 9976.29 | 29-MAY-17:20 | 325713.14 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 216.17 | 598.35 | 01-JAN-00:10 | 19402.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3213.91 | 9976.29 | 29-MAY-17:20 | 325713.14 | 14-MAR-07:10 |
Electricity:Zone:CORE_BOTTOM | 483.75 | 4990.59 | 01-JAN-00:10 | 34631.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4837.49 | 49905.77 | 01-JAN-00:10 | 346310.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1941.37 | 5373.60 | 01-JAN-00:10 | 174244.37 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1941.37 | 5373.60 | 01-JAN-00:10 | 174244.37 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 483.75 | 4990.58 | 01-JAN-00:10 | 34631.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 50.25 | 617.00 | 23-APR-17:10 | 4348.36 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 13.89 | 57.83 | 01-JAN-10:30 | 2187.81 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 13.89 | 57.83 | 01-JAN-10:30 | 2187.81 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 32.34 | 401.23 | 23-APR-17:10 | 2802.25 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 8.90 | 37.27 | 01-JAN-08:00 | 1409.91 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 8.90 | 37.27 | 01-JAN-08:00 | 1409.91 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 50.04 | 617.01 | 26-MAR-17:10 | 4348.44 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 13.67 | 57.83 | 01-JAN-08:10 | 2187.86 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 13.67 | 57.83 | 01-JAN-08:10 | 2187.86 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 32.35 | 397.61 | 12-MAR-17:10 | 2802.24 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 8.91 | 37.27 | 01-JAN-10:10 | 1409.91 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 8.91 | 37.27 | 01-JAN-10:10 | 1409.91 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 502.21 | 6169.98 | 09-APR-17:10 | 43483.64 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 138.56 | 578.27 | 01-JAN-10:10 | 21878.12 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 138.56 | 578.27 | 01-JAN-10:10 | 21878.12 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 323.23 | 4012.33 | 23-APR-17:10 | 28022.51 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 88.88 | 372.66 | 01-JAN-08:00 | 14099.09 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 88.88 | 372.66 | 01-JAN-08:00 | 14099.09 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 500.22 | 6170.07 | 19-MAR-17:10 | 43484.45 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 136.56 | 578.28 | 01-JAN-08:10 | 21878.60 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 136.56 | 578.28 | 01-JAN-08:10 | 21878.60 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 323.27 | 3976.14 | 12-MAR-17:10 | 28022.42 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 88.92 | 372.66 | 01-JAN-10:00 | 14099.09 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 88.92 | 372.66 | 01-JAN-10:00 | 14099.09 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 50.22 | 617.00 | 09-APR-17:10 | 4348.36 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 13.85 | 57.83 | 01-JAN-10:10 | 2187.81 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 13.85 | 57.83 | 01-JAN-10:10 | 2187.81 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 32.32 | 401.23 | 23-APR-17:10 | 2802.25 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 8.89 | 37.27 | 01-JAN-08:00 | 1409.91 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 8.89 | 37.27 | 01-JAN-08:00 | 1409.91 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 50.02 | 617.01 | 19-MAR-17:10 | 4348.44 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 13.66 | 57.83 | 01-JAN-08:10 | 2187.86 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 13.66 | 57.83 | 01-JAN-08:10 | 2187.86 | 14-MAR-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 32.33 | 397.61 | 12-MAR-17:10 | 2802.24 | 14-MAR-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 8.89 | 37.27 | 01-JAN-10:00 | 1409.91 | 14-MAR-07:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 8.89 | 37.27 | 01-JAN-10:00 | 1409.91 | 14-MAR-07:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7557.51 | 95212.03 | 01-JAN-00:10 | 385103.08 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 62.65 | 303.90 | 01-JAN-00:10 | 5470.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 62.65 | 303.90 | 01-JAN-00:10 | 5470.56 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 159.04 | 1973.61 | 01-JAN-00:10 | 8244.54 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1590.36 | 19736.13 | 01-JAN-00:10 | 82445.36 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 51.55 | 250.08 | 01-JAN-00:10 | 4501.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 51.55 | 250.08 | 01-JAN-00:10 | 4501.14 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 159.04 | 1973.61 | 01-JAN-00:10 | 8244.54 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 6779.72 | 8713.88 | 20-JAN-05:50 | 626847.04 | 10-AUG-16:00 |
HeatRejection:Electricity | 2226.48 | 4727.99 | 20-JAN-07:00 | 96956.19 | 07-FEB-10:50 |
General:HeatRejection:Electricity | 2226.48 | 4727.99 | 20-JAN-07:00 | 96956.19 | 07-FEB-10:50 |
Electricity:HVAC | 6730.17 | 86284.14 | 10-JAN-03:00 | 512183.85 | 16-AUG-12:10 |
ExteriorEquipment:Electricity | 2566.60 | 20217.42 | 01-JAN-00:10 | 233439.18 | 14-MAR-07:20 |
Transformer:ExteriorEquipment:Electricity | 55.01 | 979.82 | 01-JAN-00:10 | 3454.84 | 14-MAR-07:20 |
ElectricityPurchased:Facility | 34260.78 | 347904.59 | 15-JAN-05:00 | 2414001.39 | 10-AUG-16:00 |
ElectricityPurchased:Plant | 34260.78 | 347904.59 | 15-JAN-05:00 | 2414001.39 | 10-AUG-16:00 |
Cogeneration:ElectricityPurchased | 34260.78 | 347904.59 | 15-JAN-05:00 | 2414001.39 | 10-AUG-16:00 |
General:Cogeneration:ElectricityPurchased | 34260.78 | 347904.59 | 15-JAN-05:00 | 2414001.39 | 10-AUG-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 34260.78 | 347904.59 | 15-JAN-05:00 | 2414001.39 | 10-AUG-16:00 |
ElectricityNet:Plant | 34260.78 | 347904.59 | 15-JAN-05:00 | 2414001.39 | 10-AUG-16:00 |
Cogeneration:ElectricityNet | 34260.78 | 347904.59 | 15-JAN-05:00 | 2414001.39 | 10-AUG-16:00 |
General:Cogeneration:ElectricityNet | 34260.78 | 347904.59 | 15-JAN-05:00 | 2414001.39 | 10-AUG-16:00 |
Heating:Electricity | 0.12 | 0.00 | 01-JAN-00:10 | 4565.83 | 20-JAN-07:00 |
General:Heating:Electricity | 0.12 | 0.00 | 01-JAN-00:10 | 4565.83 | 20-JAN-07:00 |
Fans:Electricity | 2986.35 | 46934.68 | 01-JAN-13:30 | 264857.97 | 16-AUG-16:00 |
General:Fans:Electricity | 2986.35 | 46934.68 | 01-JAN-13:30 | 264857.97 | 16-AUG-16:00 |
ExteriorLights:Electricity | 348.98 | 0.00 | 01-JAN-07:10 | 40855.88 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 348.98 | 0.00 | 01-JAN-07:10 | 40855.88 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 2505.76 | 19200.00 | 01-JAN-00:10 | 229608.34 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 6960.39 | 36472.67 | 21-JAN-05:50 | 691057.96 | 10-AUG-16:00 |
General:Cooling:Electricity | 6960.39 | 36472.67 | 21-JAN-05:50 | 691057.96 | 10-AUG-16:00 |
Humidifier:Electricity | 13.89 | 0.00 | 01-JAN-12:10 | 13559.56 | 18-DEC-06:00 |
General:Humidifier:Electricity | 13.89 | 0.00 | 01-JAN-12:10 | 13559.56 | 18-DEC-06:00 |
Boiler:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 279.88 | 0.00 | 01-JAN-00:10 | 37717.36 | 11-JAN-12:40 |
Water Heater:WaterSystems:Electricity | 279.88 | 0.00 | 01-JAN-00:10 | 37717.36 | 11-JAN-12:40 |
Pumps:Electricity | 987.78 | 3962.49 | 01-JAN-00:10 | 60881.18 | 27-MAR-12:30 |
General:Pumps:Electricity | 987.78 | 3962.49 | 01-JAN-00:10 | 60881.18 | 27-MAR-12:30 |
WIRED_LTG_ELECTRICITY | 90.31 | 0.00 | 01-JAN-00:10 | 9152.54 | 14-MAR-07:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 41466.91 | 179380.59 | 21-JAN-05:50 | 3707882.82 | 10-AUG-16:00 |
PlantLoopCoolingDemand:HVAC | 41466.91 | 179380.59 | 21-JAN-05:50 | 3707882.82 | 10-AUG-16:00 |
CoolingCoils:PlantLoopCoolingDemand | 41466.91 | 179380.59 | 21-JAN-05:50 | 3707882.82 | 10-AUG-16:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 26865.01 | 0.00 | 09-JAN-00:10 | 0.00 | 16-JUN-13:00 |
Water:HVAC | 5.17 | 0.00 | 01-JAN-12:10 | 0.00 | 18-DEC-06:00 |
Humidifier:Water | 5.17 | 0.00 | 01-JAN-12:10 | 0.00 | 18-DEC-06:00 |
General:Humidifier:Water | 5.17 | 0.00 | 01-JAN-12:10 | 0.00 | 18-DEC-06:00 |
MainsWater:Facility | 26865.01 | 0.00 | 09-JAN-00:10 | 0.00 | 16-JUN-13:00 |
MainsWater:HVAC | 5.17 | 0.00 | 01-JAN-12:10 | 0.00 | 18-DEC-06:00 |
Humidifier:MainsWater | 5.17 | 0.00 | 01-JAN-12:10 | 0.00 | 18-DEC-06:00 |
General:Humidifier:MainsWater | 5.17 | 0.00 | 01-JAN-12:10 | 0.00 | 18-DEC-06:00 |
Water:Plant | 26859.84 | 0.00 | 01-JAN-00:10 | 0.00 | 16-JUN-13:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 26859.84 | 0.00 | 01-JAN-00:10 | 0.00 | 16-JUN-13:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 24579.67 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUN-10:50 |
General:HeatRejection:Water | 24579.67 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUN-10:50 |
HeatRejection:MainsWater | 24579.67 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUN-10:50 |
General:HeatRejection:MainsWater | 24579.67 | 0.00 | 01-JAN-00:10 | 0.00 | 15-JUN-10:50 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 148950.50 | 244311.09 | 21-JAN-05:50 | 14571643.41 | 10-AUG-16:00 |
EnergyTransfer:Building | 25459.21 | 100017.26 | 21-JAN-18:20 | 1842913.26 | 16-AUG-15:50 |
EnergyTransfer:Zone:BASEMENT | 302.86 | 0.00 | 01-JAN-00:10 | 108945.30 | 21-OCT-09:50 |
Heating:EnergyTransfer | 5.66 | 0.00 | 01-JAN-00:10 | 24050.23 | 01-JAN-13:50 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 1355.31 | 01-JAN-19:20 |
General:Heating:EnergyTransfer | 5.66 | 0.00 | 01-JAN-00:10 | 24050.23 | 01-JAN-13:50 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 1355.31 | 01-JAN-19:20 |
Cooling:EnergyTransfer | 25453.55 | 100017.26 | 21-JAN-18:20 | 1842913.26 | 16-AUG-15:50 |
Cooling:EnergyTransfer:Zone:BASEMENT | 302.86 | 0.00 | 01-JAN-00:10 | 108945.30 | 21-OCT-09:50 |
General:Cooling:EnergyTransfer | 25453.55 | 100017.26 | 21-JAN-18:20 | 1842913.26 | 16-AUG-15:50 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 302.86 | 0.00 | 01-JAN-00:10 | 108945.30 | 21-OCT-09:50 |
EnergyTransfer:Zone:CORE_BOTTOM | 1058.87 | 0.00 | 01-JAN-00:10 | 81817.07 | 07-AUG-05:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 1058.87 | 0.00 | 01-JAN-00:10 | 81817.07 | 07-AUG-05:20 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 1058.87 | 0.00 | 01-JAN-00:10 | 81817.07 | 07-AUG-05:20 |
EnergyTransfer:Zone:CORE_MID | 6441.42 | 0.00 | 01-JAN-00:10 | 462956.08 | 07-AUG-16:00 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 6441.42 | 0.00 | 01-JAN-00:10 | 462956.08 | 07-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 6441.42 | 0.00 | 01-JAN-00:10 | 462956.08 | 07-AUG-16:00 |
EnergyTransfer:Zone:CORE_TOP | 669.32 | 0.00 | 01-JAN-00:10 | 53681.04 | 31-JUL-15:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 669.32 | 0.00 | 01-JAN-00:10 | 53681.04 | 31-JUL-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 669.32 | 0.00 | 01-JAN-00:10 | 53681.04 | 31-JUL-15:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 180.47 | 0.00 | 01-JAN-00:10 | 17221.81 | 16-AUG-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 180.47 | 0.00 | 01-JAN-00:10 | 17221.81 | 16-AUG-14:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 180.47 | 0.00 | 01-JAN-00:10 | 17221.81 | 16-AUG-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 136.52 | 0.00 | 01-JAN-00:10 | 14345.94 | 04-AUG-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 136.52 | 0.00 | 01-JAN-00:10 | 14345.94 | 04-AUG-09:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 136.52 | 0.00 | 01-JAN-00:10 | 14345.94 | 04-AUG-09:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 207.69 | 0.00 | 01-JAN-00:10 | 19142.77 | 05-OCT-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 207.69 | 0.00 | 01-JAN-00:10 | 19142.77 | 05-OCT-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 207.69 | 0.00 | 01-JAN-00:10 | 19142.77 | 05-OCT-13:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 166.46 | 0.00 | 01-JAN-00:10 | 16201.55 | 10-AUG-15:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 166.46 | 0.00 | 01-JAN-00:10 | 16201.55 | 10-AUG-15:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 166.46 | 0.00 | 01-JAN-00:10 | 16201.55 | 10-AUG-15:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1295.19 | 0.00 | 01-JAN-00:10 | 144247.47 | 21-JUL-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1295.19 | 0.00 | 01-JAN-00:10 | 144247.47 | 21-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 1295.19 | 0.00 | 01-JAN-00:10 | 144247.47 | 21-JUL-15:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1073.41 | 0.00 | 01-JAN-00:10 | 125898.53 | 04-AUG-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1073.41 | 0.00 | 01-JAN-00:10 | 125898.53 | 04-AUG-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1073.41 | 0.00 | 01-JAN-00:10 | 125898.53 | 04-AUG-10:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1632.98 | 0.00 | 01-JAN-00:10 | 169394.36 | 19-OCT-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1632.98 | 0.00 | 01-JAN-00:10 | 169394.36 | 19-OCT-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1632.98 | 0.00 | 01-JAN-00:10 | 169394.36 | 19-OCT-13:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1152.22 | 0.00 | 01-JAN-00:10 | 134268.30 | 10-AUG-15:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1152.22 | 0.00 | 01-JAN-00:10 | 134268.30 | 10-AUG-15:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1152.22 | 0.00 | 01-JAN-00:10 | 134268.30 | 10-AUG-15:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 135.13 | 0.00 | 01-JAN-00:10 | 15548.84 | 21-JUL-15:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 204.33 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 204.33 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 135.13 | 0.00 | 01-JAN-00:10 | 15548.84 | 21-JUL-15:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 135.13 | 0.00 | 01-JAN-00:10 | 15548.84 | 21-JUL-15:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 111.30 | 0.00 | 01-JAN-00:10 | 13012.85 | 04-AUG-10:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 160.58 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 160.58 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 111.30 | 0.00 | 01-JAN-00:10 | 13012.85 | 04-AUG-10:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 111.30 | 0.00 | 01-JAN-00:10 | 13012.85 | 04-AUG-10:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 167.39 | 0.00 | 01-JAN-00:10 | 17647.07 | 05-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 167.39 | 0.00 | 01-JAN-00:10 | 17647.07 | 05-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 167.39 | 0.00 | 01-JAN-00:10 | 17647.07 | 05-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 118.37 | 0.00 | 01-JAN-00:10 | 14111.43 | 10-AUG-15:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 118.37 | 0.00 | 01-JAN-00:10 | 14111.43 | 10-AUG-15:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 118.37 | 0.00 | 01-JAN-00:10 | 14111.43 | 10-AUG-15:50 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 199.90 | 0.00 | 01-JAN-00:10 | 24829.56 | 07-AUG-05:20 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.82 | 0.00 | 01-JAN-00:10 | 2984.07 | 16-JAN-10:40 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.82 | 0.00 | 01-JAN-00:10 | 2984.07 | 16-JAN-10:40 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 199.09 | 0.00 | 01-JAN-00:10 | 24829.56 | 07-AUG-05:20 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 199.09 | 0.00 | 01-JAN-00:10 | 24829.56 | 07-AUG-05:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1326.45 | 0.00 | 01-JAN-00:10 | 143137.15 | 07-AUG-16:00 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 3.50 | 0.00 | 01-JAN-00:10 | 24050.23 | 01-JAN-13:50 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 3.50 | 0.00 | 01-JAN-00:10 | 24050.23 | 01-JAN-13:50 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1322.95 | 0.00 | 01-JAN-00:10 | 143137.15 | 07-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 1322.95 | 0.00 | 01-JAN-00:10 | 143137.15 | 07-AUG-16:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 189.56 | 0.00 | 01-JAN-00:10 | 28195.60 | 16-AUG-13:50 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 1.34 | 0.00 | 01-JAN-00:10 | 5534.22 | 21-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 1.34 | 0.00 | 01-JAN-00:10 | 5534.22 | 21-FEB-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 188.23 | 0.00 | 01-JAN-00:10 | 28195.60 | 16-AUG-13:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 188.23 | 0.00 | 01-JAN-00:10 | 28195.60 | 16-AUG-13:50 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 146.87 | 1231.47 | 21-JAN-08:00 | 7893.99 | 30-APR-19:40 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 146.87 | 1231.47 | 21-JAN-08:00 | 7893.99 | 30-APR-19:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 146.87 | 1231.47 | 21-JAN-08:00 | 7893.99 | 30-APR-19:40 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1355.31 | 7854.85 | 21-JAN-08:00 | 73589.29 | 30-APR-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1355.31 | 7854.85 | 21-JAN-08:00 | 73589.29 | 30-APR-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1355.31 | 7854.85 | 21-JAN-08:00 | 73589.29 | 30-APR-18:00 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 134.90 | 375.11 | 21-JAN-08:00 | 7540.61 | 23-APR-17:30 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 134.90 | 375.11 | 21-JAN-08:00 | 7540.61 | 23-APR-17:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 134.90 | 375.11 | 21-JAN-08:00 | 7540.61 | 23-APR-17:30 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7256.63 | 89348.29 | 21-JAN-20:30 | 372164.54 | 14-AUG-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7256.63 | 89348.29 | 21-JAN-20:30 | 372164.54 | 14-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7256.63 | 89348.29 | 21-JAN-20:30 | 372164.54 | 14-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 275.26 | 0.00 | 01-JAN-00:10 | 36892.95 | 12-JAN-12:10 |
PlantLoopHeatingDemand:Plant | 275.26 | 0.00 | 01-JAN-00:10 | 36892.95 | 12-JAN-12:10 |
WaterSystems:PlantLoopHeatingDemand | 275.26 | 0.00 | 01-JAN-00:10 | 36892.95 | 12-JAN-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 275.26 | 0.00 | 01-JAN-00:10 | 36892.95 | 12-JAN-12:10 |
EnergyTransfer:HVAC | 37792.23 | 142907.93 | 21-JAN-05:50 | 3468564.21 | 10-AUG-16:00 |
HeatingCoils:EnergyTransfer | 0.12 | 0.00 | 01-JAN-00:10 | 4565.83 | 20-JAN-07:00 |
CoolingCoils:EnergyTransfer | 37792.11 | 142907.93 | 21-JAN-05:50 | 3468564.21 | 10-AUG-16:00 |
PlantLoopHeatingDemand:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatingCoils:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Plant | 85699.06 | 0.00 | 01-JAN-00:10 | 9269902.95 | 10-AUG-16:00 |
LoopToLoop:EnergyTransfer | 27615.69 | 0.00 | 01-JAN-00:10 | 2932300.05 | 10-AUG-16:00 |
WaterSystems:EnergyTransfer | 275.26 | 0.00 | 01-JAN-00:10 | 36892.95 | 12-JAN-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 275.26 | 0.00 | 01-JAN-00:10 | 36892.95 | 12-JAN-12:10 |
Chillers:EnergyTransfer | 27261.26 | 0.00 | 01-JAN-00:10 | 2933493.45 | 10-AUG-16:00 |
HeatRejection:EnergyTransfer | 30546.85 | 0.00 | 01-JAN-00:10 | 3385232.80 | 10-AUG-16:00 |
General:HeatRejection:EnergyTransfer | 30546.85 | 0.00 | 01-JAN-00:10 | 3385232.80 | 10-AUG-16:00 |
Boilers:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:45
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.001 | -302.844 | 0.000 | 0.000 | 59.885 | 216.171 | 424.397 | 0.000 | 0.000 | 0.000 | 0.017 | 0.000 | 0.000 | 0.000 | 0.000 | -397.610 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -1058.875 | 0.000 | 0.000 | 83.294 | 194.137 | 289.614 | 0.000 | 0.000 | 0.000 | 491.830 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
CORE_MID | 0.000 | 0.000 | 0.000 | -6441.426 | 0.000 | 0.000 | 835.453 | 1941.366 | 2896.128 | 0.000 | 0.000 | 0.000 | 768.480 | 0.000 | 0.000 | 0.000 | 0.000 | -0.010 |
CORE_TOP | 0.000 | 0.000 | 0.000 | -669.317 | 0.000 | 0.000 | 83.682 | 194.137 | 289.613 | 0.000 | 0.000 | 0.000 | 101.886 | 0.000 | 0.000 | 0.000 | 0.000 | -0.003 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -180.468 | 0.000 | 0.000 | 10.461 | 13.889 | 36.365 | 61.199 | 0.000 | 0.768 | 74.962 | 0.000 | -16.920 | 0.000 | -0.257 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -136.518 | 0.000 | 0.000 | 6.743 | 8.904 | 23.435 | 63.452 | 0.000 | 0.515 | 43.914 | 0.000 | -10.279 | 0.000 | -0.165 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -207.688 | 0.000 | 0.000 | 10.452 | 13.673 | 36.366 | 99.465 | 0.000 | 0.764 | 63.887 | 0.000 | -16.641 | 0.000 | -0.278 | -0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -166.461 | 0.000 | 0.000 | 6.731 | 8.912 | 23.435 | 63.340 | 0.000 | 0.509 | 76.755 | 0.000 | -13.013 | 0.000 | -0.208 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.000 | -1295.188 | 0.000 | 0.000 | 105.259 | 138.558 | 363.654 | 647.599 | 0.000 | 18.354 | 172.983 | 0.000 | -145.933 | 0.000 | -5.286 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.000 | -1073.407 | 0.000 | 0.000 | 49.725 | 88.882 | 234.352 | 650.839 | 0.000 | 12.182 | 135.183 | 0.000 | -94.004 | 0.000 | -3.752 | -0.010 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.000 | -1632.978 | 0.000 | 0.000 | 104.760 | 136.563 | 363.660 | 1016.637 | 0.000 | 17.998 | 156.087 | 0.000 | -156.209 | 0.000 | -6.519 | -0.007 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.000 | -1152.216 | 0.000 | 0.000 | 67.859 | 88.918 | 234.351 | 656.457 | 0.000 | 11.997 | 204.235 | 0.000 | -107.530 | 0.000 | -4.072 | -0.006 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 0.000 | -135.128 | 0.000 | 0.000 | 10.583 | 13.855 | 36.365 | 64.359 | 0.000 | 2.241 | 22.316 | 0.000 | -13.973 | 0.000 | -0.618 | -0.001 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.000 | -111.300 | 0.000 | 0.000 | 6.786 | 8.888 | 23.435 | 64.723 | 0.000 | 1.480 | 15.547 | 0.000 | -9.113 | 0.000 | -0.446 | -0.000 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.000 | -167.389 | 0.000 | 0.000 | 10.505 | 13.656 | 36.366 | 101.084 | 0.000 | 2.196 | 19.476 | 0.000 | -15.115 | 0.000 | -0.778 | -0.000 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.000 | -118.374 | 0.000 | 0.000 | 6.819 | 8.892 | 23.435 | 65.284 | 0.000 | 1.467 | 23.360 | 0.000 | -10.397 | 0.000 | -0.487 | -0.001 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -146.871 | 0.000 | 0.000 | 0.940 | 5.155 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -13.105 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.000 | -1355.307 | 0.000 | 0.000 | 9.407 | 51.551 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -244.456 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.000 | -134.896 | 0.000 | 0.000 | 0.940 | 5.155 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -25.081 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7256.638 | 0.000 | 0.000 | 20.509 | 62.653 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -321.381 |
GROUNDFLOOR_PLENUM | 0.817 | -199.088 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.379 | 197.481 | 0.000 | 0.000 | 0.000 | -0.589 | 0.000 |
MIDFLOOR_PLENUM | 3.505 | -1322.945 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 26.715 | 1302.405 | 0.000 | 0.000 | 0.000 | -9.679 | 0.000 |
TOPFLOOR_PLENUM | 1.336 | -188.227 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.909 | 184.998 | 0.000 | 0.000 | 0.000 | -1.015 | -0.001 |
Total Facility | 5.658 | -1710.260 | 0.001 | -23743.286 | 0.000 | 0.000 | 1490.792 | 3213.914 | 14676.396 | 3554.438 | 0.000 | 101.472 | 4055.801 | 0.000 | -609.126 | 0.000 | -34.149 | -1001.672 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 10-FEB-05:41 | 0.00 | 0.00 | 0.00 | -126436.76 | 0.00 | 0.00 | 0.00 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 112380.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 09-FEB-05:13 | 0.00 | 0.00 | 0.00 | -106631.35 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 100156.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 20-OCT-04:13 | 0.00 | 0.00 | 0.00 | -961690.81 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 896940.98 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 21-APR-04:12 | 0.00 | 0.00 | 0.00 | -91025.55 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 84550.57 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 11-JUN-17:02 | 0.00 | 0.00 | 0.00 | -24759.97 | 0.00 | 0.00 | 0.00 | 57.83 | 559.17 | 4875.95 | 0.00 | 173.93 | 19093.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-SEP-10:23 | 0.00 | 0.00 | 0.00 | -20992.81 | 0.00 | 0.00 | 20.11 | 37.27 | 464.11 | 7846.45 | 0.00 | 100.63 | 12524.25 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 29-OCT-13:43 | 0.00 | 0.00 | 0.00 | -28542.27 | 0.00 | 0.00 | 32.18 | 57.83 | 720.19 | 13506.79 | 0.00 | 114.37 | 14110.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 25-JUN-15:41 | 0.00 | 0.00 | 0.00 | -27084.77 | 0.00 | 0.00 | 20.09 | 37.27 | 464.11 | 8730.63 | 0.00 | 66.17 | 17766.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 04-JUN-16:11 | 0.00 | 0.00 | 0.00 | -235096.04 | 0.00 | 0.00 | 386.06 | 578.27 | 7201.84 | 57713.86 | 0.00 | 2555.87 | 166660.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 07-MAY-10:02 | 0.00 | 0.00 | 0.00 | -210606.84 | 0.00 | 0.00 | 227.41 | 372.66 | 4641.14 | 93890.10 | 0.00 | 895.51 | 110580.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 09-OCT-13:31 | 0.00 | 0.00 | 0.00 | -279498.10 | 0.00 | 0.00 | 328.31 | 578.28 | 7201.95 | 128290.38 | 0.00 | 3176.07 | 139923.10 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 04-JUN-16:11 | 0.00 | 0.00 | 0.00 | -242686.66 | 0.00 | 0.00 | 205.45 | 372.66 | 4641.11 | 84977.02 | 0.00 | 1526.29 | 150964.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 04-JUN-16:11 | 0.00 | 0.00 | 0.00 | -26513.56 | 0.00 | 0.00 | 36.69 | 57.83 | 720.18 | 5620.05 | 0.00 | 302.90 | 19775.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 03-SEP-13:31 | 0.00 | 0.00 | 0.00 | -21853.76 | 0.00 | 0.00 | 22.16 | 37.27 | 464.11 | 4272.95 | 0.00 | 323.13 | 16734.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 09-OCT-14:01 | 0.00 | 0.00 | 0.00 | -30822.94 | 0.00 | 0.00 | 31.33 | 57.83 | 720.19 | 11604.91 | 0.00 | 408.34 | 18000.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 04-JUN-16:11 | 0.00 | 0.00 | 0.00 | -26374.88 | 0.00 | 0.00 | 19.43 | 37.27 | 464.11 | 8392.48 | 0.00 | 181.49 | 17280.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 30-APR-18:52 | 0.00 | 0.00 | 0.00 | -7898.80 | 0.00 | 0.00 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 79.37 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 30-APR-17:55 | 0.00 | 0.00 | 0.00 | -73588.78 | 0.00 | 0.00 | 0.00 | 250.08 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4605.52 |
DATACENTER_TOP_ZN_6 | 23-APR-17:22 | 0.00 | 0.00 | 0.00 | -7540.59 | 0.00 | 0.00 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -278.84 |
DATACENTER_BASEMENT_ZN_6 | 10-AUG-21:01 | 0.00 | 0.00 | 0.00 | -375605.09 | 0.00 | 0.00 | 112.80 | 607.86 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4748.10 |
GROUNDFLOOR_PLENUM | 07-AUG-05:20 | 0.00 | -27695.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.99 | 27676.77 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 08-AUG-05:01 | 0.00 | -175482.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 466.27 | 175016.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 16-AUG-13:50 | 0.00 | -28194.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.12 | 27912.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 21-AUG-05:01 | 0.00 | -143175.73 | 0.00 | -2192971.85 | 0.00 | 0.00 | 15051.14 | 10917.52 | 616289.16 | 10818.26 | 0.00 | 1121.03 | 1682060.83 | 0.00 | -110.36 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 01-JAN-19:20 | 0.00 | 0.00 | 1355.58 | 0.00 | 0.00 | 0.00 | 0.00 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -15411.47 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 02-JAN-06:07 | 0.00 | 0.00 | 612.95 | 0.00 | 0.00 | 0.00 | 138.45 | 67.47 | 960.25 | 0.00 | 0.00 | 0.00 | 980.35 | 0.00 | -2739.42 | 0.00 | -20.03 | 0.00 |
PERIMETER_TOP_ZN_2 | 02-JAN-06:07 | 0.00 | 0.00 | 481.70 | 0.00 | 0.00 | 0.00 | 89.07 | 43.48 | 618.82 | 0.00 | 0.00 | 0.00 | 626.53 | 0.00 | -1846.25 | 0.00 | -13.36 | 0.00 |
PERIMETER_TOP_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 28-DEC-05:12 | 12241.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -106.56 | -12134.68 |
MIDFLOOR_PLENUM | 02-MAR-04:02 | 75545.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3185.57 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -78731.37 |
TOPFLOOR_PLENUM | 01-FEB-06:02 | 15554.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -32.73 | -15521.65 |
Total Facility | 21-FEB-05:12 | -1389995.56 | 1468997.32 | 0.00 | -1468997.32 | 0.00 | 0.00 | 0.00 | 10917.52 | 350716.63 | 0.00 | 0.00 | 0.00 | 1154323.66 | 0.00 | -112399.20 | 0.00 | -13563.05 | 0.00 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:45
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 11.6441 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.6029 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 111.8753 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 100.0953 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 11.6090 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.2488 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.9877 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.9877 | 0.2004 | 1.0000 | Not calculated | 1.2002 | 0.2004 | ||
AIRLOOP DATACENTER BASEMENT | 24.7086 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.7088 | 0.0137 | 1.0000 | Not calculated | 0.3384 | 0.0137 | ||
AIRLOOP DATACENTER BOT | 0.4802 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4802 | 0.0326 | 1.0000 | Not calculated | 0.0156 | 0.0326 | ||
AIRLOOP DATACENTER MID | 4.5797 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.5797 | 0.0341 | 1.0000 | Not calculated | 0.1563 | 0.0341 | ||
AIRLOOP DATACENTER TOP | 0.4608 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4608 | 0.0339 | 1.0000 | Not calculated | 0.0156 | 0.0339 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.8221 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.0478 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 55.9377 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 29.8829 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.8045 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.1212 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 0.0000 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 0.0000 | 1.0000 | 1.0000 | Not calculated | 1.2002 | |||
AIRLOOP DATACENTER BASEMENT | 24.7086 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 24.7086 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0137 | ||
AIRLOOP DATACENTER BOT | 0.4802 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4802 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0326 | ||
AIRLOOP DATACENTER MID | 4.5797 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.5797 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0341 | ||
AIRLOOP DATACENTER TOP | 0.4608 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4608 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0339 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 5.9877 | 5.9877 | 0.0000 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.3070 | 6.3070 | 1.9804 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 60.0629 | 60.0629 | 19.5204 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.0559 | 6.0559 | 2.0105 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3210 | 1.3210 | 0.2642 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1048 | 1.1048 | 0.2210 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4783 | 1.4783 | 0.2957 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4330 | 1.4330 | 0.2866 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.0491 | 13.0491 | 2.6098 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.4895 | 11.4895 | 2.2979 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.5902 | 14.5902 | 2.9180 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.6835 | 12.6835 | 2.5367 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4371 | 1.4371 | 0.2874 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1783 | 1.1783 | 0.2357 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5842 | 1.5842 | 0.3168 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3535 | 1.3535 | 0.2707 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4802 | 0.4802 | 0.4802 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.5797 | 4.5797 | 4.5797 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4608 | 0.4608 | 0.4608 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.7086 | 24.7086 | 24.7086 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 11.6441 | 10.6029 | 11.6441 | 3.0478 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 111.8753 | 100.0953 | 111.8753 | 29.8829 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 11.6090 | 11.2488 | 11.6090 | 3.1212 | 0.0000 | 1.0000 |
CAV_BAS | 5.9877 | 5.9877 | 5.9877 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.7086 | 24.7088 | 24.7086 | 24.7086 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4802 | 0.4802 | 0.4802 | 0.4802 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.5797 | 4.5797 | 4.5797 | 4.5797 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4608 | 0.4608 | 0.4608 | 0.4608 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 0.0000 | 0.0000 | 0.0000 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.1535 | 3.1535 | 1.9804 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 30.0315 | 30.0315 | 19.5204 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0279 | 3.0279 | 2.0105 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6605 | 0.6605 | 0.2642 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5524 | 0.5524 | 0.2210 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7392 | 0.7392 | 0.2957 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7165 | 0.7165 | 0.2866 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.5246 | 6.5246 | 2.6098 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.7448 | 5.7448 | 2.2979 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.2951 | 7.2951 | 2.9180 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.3418 | 6.3418 | 2.5367 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7185 | 0.7185 | 0.2874 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5892 | 0.5892 | 0.2357 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7921 | 0.7921 | 0.3168 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6768 | 0.6768 | 0.2707 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4802 | 0.4802 | 0.4802 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.5797 | 4.5797 | 4.5797 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4608 | 0.4608 | 0.4608 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 24.7086 | 24.7086 | 24.7086 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.8221 | 3.0478 | 3.0478 | 3.0478 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 55.9377 | 29.8829 | 29.8829 | 29.8829 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.8045 | 3.1212 | 3.1212 | 3.1212 | 0.0000 | 1.0000 |
CAV_BAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 24.7086 | 24.7086 | 24.7086 | 24.7086 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4802 | 0.4802 | 0.4802 | 0.4802 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.5797 | 4.5797 | 4.5797 | 4.5797 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4608 | 0.4608 | 0.4608 | 0.4608 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:45
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 4193.50 |
Number of hours not met | 4193.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.12 | 4565.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 6960.39 | 691057.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3213.91 | 325713.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 348.98 | 40855.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 55.01 | 3454.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 2505.76 | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2986.35 | 264857.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 987.78 | 60881.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 2226.48 | 96956.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 13.89 | 13559.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 279.88 | 37717.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 34260.78 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 34260.78 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 69.38 |
Space Heating | 0.00 |
Space Cooling | 150.27 |
Fans (All) | 64.47 |
Service Water Heating | 6.04 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 739.65 |
Subtotal | 739.65 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 9.38 |
Space Heating | 0.00 |
Space Cooling | 20.32 |
Fans (All) | 8.72 |
Service Water Heating | 0.82 |
Receptacle Equipment | 42.84 |
Miscellaneous | 17.93 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:45
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 2194.00 | 1295.67 | 409.00 | 4325.50 | 535.83 |
CORE_BOTTOM | 8432.50 | 327.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 7910.00 | 850.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8013.83 | 746.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 7925.67 | 834.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7395.33 | 1364.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8388.50 | 371.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8276.00 | 484.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8057.00 | 703.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 7881.67 | 878.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8320.00 | 440.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8185.67 | 574.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8032.83 | 727.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 7911.17 | 848.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 6248.17 | 2511.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 6159.67 | 2600.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 6221.50 | 2538.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8042.50 | 717.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 7310.50 | 1449.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8720.67 | 39.33 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8064.83 | 695.17 | 0.00 | 0.00 | 0.00 |
Min | 2194.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2600.33 | 409.00 | 4325.50 | 535.83 |
Average | 7617.91 | 912.94 | 17.78 | 188.07 | 23.30 |
Sum | 175212.00 | 20997.67 | 409.00 | 4325.50 | 535.83 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 114045.67 | 21430.50 | 19982.17 | 152752.67 | 60405.00 |
CORE_BOTTOM | 330301.00 | 512.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1456.33 | 811.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1416.50 | 851.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1423.50 | 844.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 88977.00 | 14418.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 330813.00 | 21430.50 | 19982.17 | 152752.67 | 60405.00 |
Average | 68508.48 | 1689.92 | 868.79 | 6641.42 | 2626.30 |
Sum | 1575695.00 | 38868.17 | 19982.17 | 152752.67 | 60405.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 1891.50 | 1615.00 | 303.00 | 1647.17 | 3303.33 |
CORE_BOTTOM | 5728.00 | 3032.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 7382.83 | 1377.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 7255.50 | 1504.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 6054.33 | 2705.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 6273.33 | 2486.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 5819.67 | 2940.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 5526.33 | 3233.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 6149.17 | 2610.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 6071.17 | 2688.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 5795.33 | 2964.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 5925.50 | 2834.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 6210.17 | 2549.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 6111.33 | 2648.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 5878.50 | 2881.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 5989.83 | 2770.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7287.00 | 1473.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7224.00 | 1536.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7263.33 | 1496.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8575.83 | 184.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 4919.33 | 3840.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3639.17 | 5120.83 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3311.00 | 5449.00 | 0.00 | 0.00 | 0.00 |
Min | 1891.50 | 184.17 | 0.00 | 0.00 | 0.00 |
Max | 8575.83 | 5449.00 | 303.00 | 1647.17 | 3303.33 |
Average | 5925.31 | 2606.28 | 13.17 | 71.62 | 143.62 |
Sum | 136282.17 | 59944.33 | 303.00 | 1647.17 | 3303.33 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 112605.33 | 25006.00 | 13722.50 | 48646.00 | 168636.17 |
CORE_BOTTOM | 325315.00 | 5498.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 328564.00 | 2249.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 327583.00 | 3230.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1788.33 | 479.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1733.00 | 535.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1752.83 | 515.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 98672.50 | 4722.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 328564.00 | 25006.00 | 13722.50 | 48646.00 | 168636.17 |
Average | 68454.91 | 1836.32 | 596.63 | 2115.04 | 7332.01 |
Sum | 1574463.00 | 42235.33 | 13722.50 | 48646.00 | 168636.17 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:45
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:45
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Environment
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Environment
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.626179E+11 | 120248.88 | 01-JAN-19:02 | 18.33 | 14.90 | 0.579823E+10 | 11352.01 | 30-JAN-14:00 | 22.00 | 20.56 |
February | 0.483230E+11 | 126437.87 | 10-FEB-05:41 | 19.83 | 12.67 | 0.584939E+10 | 12888.85 | 09-FEB-14:00 | 19.83 | 12.67 |
March | 0.468633E+11 | 109139.29 | 06-MAR-05:12 | 16.67 | 12.96 | 0.746059E+10 | 12182.18 | 23-MAR-13:00 | 33.00 | 17.32 |
April | 0.279646E+11 | 110168.59 | 13-APR-05:08 | 18.83 | 14.72 | 0.747149E+10 | 13073.76 | 28-APR-13:00 | 35.00 | 23.22 |
May | 0.454032E+10 | 93121.31 | 01-MAY-10:00 | 28.50 | 21.47 | 0.971951E+10 | 13126.05 | 12-MAY-13:00 | 36.50 | 22.31 |
June | 0.414434E+10 | 98405.64 | 22-JUN-09:50 | 37.17 | 23.71 | 0.995513E+10 | 13369.27 | 16-JUN-13:00 | 37.17 | 23.71 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 | 27.02 | 0.973138E+10 | 13714.04 | 21-JUL-13:00 | 42.00 | 27.65 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 | 28.28 | 0.112561E+11 | 14100.40 | 18-AUG-13:00 | 38.00 | 27.45 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 | 25.04 | 0.979246E+10 | 13997.96 | 01-SEP-13:00 | 39.10 | 25.51 |
October | 0.395342E+10 | 110886.34 | 21-OCT-05:51 | 22.00 | 15.43 | 0.101157E+11 | 13946.88 | 13-OCT-13:00 | 22.00 | 15.43 |
November | 0.446383E+11 | 120456.52 | 13-NOV-06:41 | 20.58 | 17.67 | 0.758567E+10 | 13942.64 | 03-NOV-13:00 | 20.58 | 17.67 |
December | 0.598118E+11 | 118811.31 | 13-DEC-00:42 | 18.42 | 13.89 | 0.606643E+10 | 12721.33 | 12-DEC-14:00 | 18.42 | 13.89 |
Annual Sum or Average | 0.302857E+12 | 0.100802E+12 | ||||||||
Minimum of Months | 0.00 | 0.00 | 16.67 | 12.67 | 0.579823E+10 | 11352.01 | 18.42 | 12.67 | ||
Maximum of Months | 0.626179E+11 | 126437.87 | 37.17 | 28.28 | 0.112561E+11 | 14100.40 | 42.00 | 27.65 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.524765E+11 | 104147.20 | 02-JAN-05:12 | 13.67 | 11.10 | 0.507888E+10 | 6734.81 | 09-JAN-10:09 | 15.75 | 15.22 |
February | 0.553911E+11 | 106666.84 | 09-FEB-05:13 | 23.00 | 19.02 | 0.460994E+10 | 6734.92 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.748211E+11 | 103016.81 | 16-MAR-04:13 | 15.67 | 12.92 | 0.550063E+10 | 6735.12 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.838005E+11 | 99768.03 | 01-APR-04:13 | 18.13 | 16.90 | 0.488403E+10 | 6776.24 | 28-APR-13:00 | 35.00 | 23.22 |
May | 0.981250E+11 | 103477.69 | 15-MAY-04:13 | 23.40 | 18.32 | 0.529762E+10 | 6767.83 | 30-MAY-13:00 | 38.00 | 25.47 |
June | 0.102804E+12 | 95137.63 | 12-JUN-04:23 | 29.60 | 24.63 | 0.528056E+10 | 6762.33 | 20-JUN-13:00 | 38.00 | 26.22 |
July | 0.109852E+12 | 105292.70 | 05-JUL-03:03 | 30.02 | 27.78 | 0.491902E+10 | 6768.66 | 26-JUL-13:00 | 38.00 | 29.49 |
August | 0.121959E+12 | 106104.47 | 28-AUG-03:03 | 31.07 | 27.26 | 0.552452E+10 | 6783.98 | 15-AUG-13:00 | 31.07 | 27.26 |
September | 0.102903E+12 | 104618.96 | 05-SEP-03:03 | 30.95 | 25.68 | 0.489597E+10 | 6750.00 | 05-SEP-09:00 | 37.60 | 24.92 |
October | 0.105070E+12 | 103487.11 | 21-OCT-04:24 | 22.55 | 15.19 | 0.508914E+10 | 6737.10 | 19-OCT-09:20 | 22.55 | 15.19 |
November | 0.837074E+11 | 105670.49 | 27-NOV-05:13 | 18.00 | 16.14 | 0.503240E+10 | 6736.19 | 03-NOV-09:09 | 18.00 | 16.14 |
December | 0.679637E+11 | 104068.57 | 28-DEC-05:12 | 15.00 | 12.67 | 0.490197E+10 | 6734.75 | 20-DEC-10:09 | 15.00 | 12.67 |
Annual Sum or Average | 0.105887E+13 | 0.610147E+11 | ||||||||
Minimum of Months | 0.524765E+11 | 95137.63 | 13.67 | 11.10 | 0.460994E+10 | 6734.75 | 15.00 | 12.67 | ||
Maximum of Months | 0.121959E+12 | 106666.84 | 31.07 | 27.78 | 0.552452E+10 | 6783.98 | 38.00 | 29.49 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.400378E+11 | 88846.67 | 23-JAN-06:02 | 17.98 | 16.09 | 0.505185E+10 | 6734.78 | 09-JAN-10:09 | 17.98 | 16.09 |
February | 0.387929E+11 | 89925.74 | 10-FEB-05:11 | 19.93 | 12.75 | 0.459119E+10 | 6734.97 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.493901E+11 | 91144.52 | 06-MAR-05:12 | 16.67 | 12.96 | 0.549290E+10 | 6735.13 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.508646E+11 | 91233.63 | 05-APR-04:12 | 17.07 | 15.11 | 0.487574E+10 | 6735.18 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.611547E+11 | 90723.30 | 04-MAY-04:13 | 23.53 | 18.44 | 0.527639E+10 | 6735.04 | 08-MAY-13:30 | 35.75 | 23.54 |
June | 0.623538E+11 | 70074.64 | 02-JUN-05:02 | 27.00 | 17.61 | 0.525956E+10 | 6734.93 | 02-JUN-13:09 | 38.83 | 24.30 |
July | 0.637584E+11 | 70866.64 | 06-JUL-05:02 | 29.00 | 27.46 | 0.488404E+10 | 6735.20 | 03-JUL-09:20 | 29.00 | 27.46 |
August | 0.677044E+11 | 71389.46 | 21-AUG-05:01 | 30.00 | 28.44 | 0.548629E+10 | 6734.58 | 24-AUG-09:00 | 34.90 | 25.82 |
September | 0.596549E+11 | 69748.86 | 28-SEP-05:02 | 27.83 | 26.48 | 0.487055E+10 | 6734.69 | 26-SEP-09:00 | 27.83 | 26.48 |
October | 0.575776E+11 | 96182.79 | 20-OCT-04:13 | 22.60 | 16.22 | 0.506945E+10 | 6734.64 | 27-OCT-13:09 | 32.00 | 22.23 |
November | 0.501547E+11 | 90998.11 | 16-NOV-05:11 | 20.00 | 17.84 | 0.502293E+10 | 6734.66 | 22-NOV-10:09 | 23.42 | 16.99 |
December | 0.426979E+11 | 90433.61 | 06-DEC-05:12 | 18.00 | 17.36 | 0.488228E+10 | 6734.75 | 01-DEC-14:09 | 18.00 | 17.36 |
Annual Sum or Average | 0.644142E+12 | 0.607632E+11 | ||||||||
Minimum of Months | 0.387929E+11 | 69748.86 | 16.67 | 12.75 | 0.459119E+10 | 6734.58 | 17.98 | 16.09 | ||
Maximum of Months | 0.677044E+11 | 96182.79 | 30.00 | 28.44 | 0.549290E+10 | 6735.20 | 38.83 | 27.46 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.356930E+11 | 84185.91 | 25-JAN-06:03 | 17.88 | 14.29 | 0.498966E+10 | 6734.75 | 24-JAN-10:00 | 17.88 | 14.29 |
February | 0.363668E+11 | 90170.98 | 08-FEB-05:12 | 22.00 | 18.65 | 0.455745E+10 | 6734.94 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.484951E+11 | 89980.55 | 29-MAR-04:12 | 20.97 | 19.32 | 0.547424E+10 | 6735.13 | 28-MAR-09:00 | 20.97 | 19.32 |
April | 0.525479E+11 | 91042.39 | 21-APR-04:12 | 20.40 | 17.89 | 0.487309E+10 | 6735.16 | 25-APR-09:09 | 31.00 | 20.82 |
May | 0.665428E+11 | 86560.96 | 03-MAY-04:12 | 23.10 | 18.53 | 0.528019E+10 | 6735.01 | 04-MAY-13:00 | 36.00 | 22.99 |
June | 0.688590E+11 | 74959.56 | 02-JUN-05:02 | 27.00 | 17.61 | 0.526323E+10 | 6734.90 | 02-JUN-13:09 | 38.83 | 24.30 |
July | 0.717897E+11 | 84877.92 | 31-JUL-05:03 | 30.83 | 27.07 | 0.489058E+10 | 6735.19 | 03-JUL-09:09 | 30.83 | 27.07 |
August | 0.756880E+11 | 83811.98 | 28-AUG-05:01 | 31.17 | 27.16 | 0.549115E+10 | 6734.55 | 24-AUG-09:00 | 31.17 | 27.16 |
September | 0.649226E+11 | 76595.98 | 11-SEP-05:02 | 29.00 | 27.59 | 0.487487E+10 | 6734.68 | 26-SEP-09:00 | 36.90 | 21.78 |
October | 0.600634E+11 | 88636.43 | 21-OCT-04:12 | 22.40 | 15.15 | 0.507187E+10 | 6734.63 | 20-OCT-09:00 | 22.40 | 15.15 |
November | 0.490334E+11 | 90901.88 | 16-NOV-05:11 | 20.00 | 17.84 | 0.501695E+10 | 6734.62 | 22-NOV-10:09 | 23.42 | 16.99 |
December | 0.393157E+11 | 89475.46 | 12-DEC-05:12 | 23.00 | 18.27 | 0.484363E+10 | 6734.71 | 01-DEC-14:09 | 23.00 | 18.27 |
Annual Sum or Average | 0.669317E+12 | 0.606269E+11 | ||||||||
Minimum of Months | 0.356930E+11 | 74959.56 | 17.88 | 14.29 | 0.455745E+10 | 6734.55 | 17.88 | 14.29 | ||
Maximum of Months | 0.756880E+11 | 91042.39 | 31.17 | 27.59 | 0.549115E+10 | 6735.19 | 38.83 | 27.16 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.555287E+10 | 13113.34 | 23-JAN-06:01 | 17.98 | 16.09 | 0.630555E+09 | 845.63 | 17-JAN-14:09 | 17.98 | 16.09 |
February | 0.663206E+10 | 18185.98 | 09-FEB-05:12 | 23.00 | 19.02 | 0.576021E+09 | 845.65 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.104103E+11 | 16206.49 | 02-MAR-05:12 | 29.07 | 15.68 | 0.689898E+09 | 845.67 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.134571E+11 | 18362.39 | 30-APR-13:42 | 34.52 | 22.68 | 0.614110E+09 | 852.89 | 28-APR-13:00 | 34.52 | 22.68 |
May | 0.188899E+11 | 23507.69 | 07-MAY-14:41 | 37.00 | 20.10 | 0.666794E+09 | 851.58 | 30-MAY-13:00 | 38.00 | 25.47 |
June | 0.208986E+11 | 24769.91 | 11-JUN-17:02 | 36.83 | 25.95 | 0.664658E+09 | 850.63 | 20-JUN-13:00 | 38.00 | 26.22 |
July | 0.233018E+11 | 24739.74 | 02-JUL-17:02 | 37.00 | 23.59 | 0.619629E+09 | 851.73 | 26-JUL-13:00 | 38.00 | 29.49 |
August | 0.250045E+11 | 22851.76 | 13-AUG-13:42 | 40.12 | 25.55 | 0.695597E+09 | 854.52 | 15-AUG-13:00 | 40.00 | 22.91 |
September | 0.192297E+11 | 24617.39 | 04-SEP-13:03 | 40.67 | 25.43 | 0.616032E+09 | 848.15 | 05-SEP-09:00 | 37.60 | 24.92 |
October | 0.171830E+11 | 21935.11 | 29-OCT-11:42 | 34.42 | 15.83 | 0.639724E+09 | 845.61 | 20-OCT-09:00 | 34.42 | 15.83 |
November | 0.119356E+11 | 22151.73 | 05-NOV-14:42 | 32.17 | 20.87 | 0.631882E+09 | 845.62 | 06-NOV-14:00 | 32.00 | 21.82 |
December | 0.797218E+10 | 16537.39 | 11-DEC-06:02 | 21.90 | 19.23 | 0.613473E+09 | 845.63 | 01-DEC-14:09 | 21.90 | 19.23 |
Annual Sum or Average | 0.180467E+12 | 0.765837E+10 | ||||||||
Minimum of Months | 0.555287E+10 | 13113.34 | 17.98 | 15.68 | 0.576021E+09 | 845.61 | 17.98 | 15.83 | ||
Maximum of Months | 0.250045E+11 | 24769.91 | 40.67 | 25.95 | 0.695597E+09 | 854.52 | 40.00 | 29.49 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.452437E+10 | 8653.51 | 30-JAN-05:12 | 20.00 | 17.44 | 0.407040E+09 | 544.96 | 17-JAN-10:09 | 20.00 | 17.44 |
February | 0.515478E+10 | 14746.01 | 09-FEB-05:12 | 23.00 | 19.02 | 0.370880E+09 | 544.97 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.775558E+10 | 9818.69 | 27-MAR-10:30 | 36.50 | 18.44 | 0.443974E+09 | 544.99 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.102234E+11 | 18527.84 | 23-APR-09:23 | 31.85 | 17.35 | 0.395610E+09 | 550.10 | 28-APR-13:00 | 35.00 | 23.22 |
May | 0.149049E+11 | 20476.01 | 07-MAY-10:02 | 36.92 | 18.11 | 0.429851E+09 | 549.15 | 30-MAY-13:00 | 38.00 | 25.47 |
June | 0.156144E+11 | 20305.47 | 11-JUN-10:21 | 38.50 | 26.61 | 0.428326E+09 | 548.44 | 20-JUN-13:00 | 38.00 | 26.22 |
July | 0.169891E+11 | 20875.76 | 02-JUL-10:23 | 37.50 | 24.05 | 0.399420E+09 | 549.15 | 26-JUL-13:00 | 38.00 | 29.49 |
August | 0.182971E+11 | 19318.56 | 13-AUG-10:22 | 38.80 | 25.02 | 0.448423E+09 | 551.11 | 15-AUG-13:00 | 40.00 | 22.91 |
September | 0.150715E+11 | 21004.17 | 04-SEP-10:23 | 38.00 | 23.07 | 0.397137E+09 | 547.10 | 05-SEP-09:00 | 37.60 | 24.92 |
October | 0.133400E+11 | 18784.41 | 09-OCT-10:22 | 34.65 | 23.19 | 0.412357E+09 | 544.95 | 20-OCT-09:00 | 30.40 | 18.49 |
November | 0.894958E+10 | 17693.49 | 05-NOV-10:42 | 31.82 | 18.97 | 0.407161E+09 | 544.95 | 06-NOV-14:00 | 32.00 | 21.82 |
December | 0.569314E+10 | 7832.28 | 11-DEC-06:02 | 21.90 | 19.23 | 0.394074E+09 | 544.96 | 01-DEC-14:09 | 21.90 | 19.23 |
Annual Sum or Average | 0.136518E+12 | 0.493425E+10 | ||||||||
Minimum of Months | 0.452437E+10 | 7832.28 | 20.00 | 17.35 | 0.370880E+09 | 544.95 | 20.00 | 17.44 | ||
Maximum of Months | 0.182971E+11 | 21004.17 | 38.80 | 26.61 | 0.448423E+09 | 551.11 | 40.00 | 29.49 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.932350E+10 | 19427.57 | 30-JAN-05:12 | 20.00 | 17.44 | 0.634925E+09 | 845.65 | 17-JAN-14:09 | 20.00 | 17.44 |
February | 0.100338E+11 | 25784.35 | 05-FEB-12:23 | 31.05 | 19.28 | 0.577426E+09 | 846.43 | 07-FEB-14:09 | 30.50 | 20.52 |
March | 0.133432E+11 | 25611.02 | 26-MAR-12:32 | 34.67 | 17.89 | 0.690353E+09 | 845.97 | 27-MAR-13:00 | 35.00 | 19.40 |
April | 0.148504E+11 | 21701.52 | 02-APR-12:43 | 32.62 | 17.34 | 0.614264E+09 | 853.63 | 28-APR-13:00 | 35.00 | 23.22 |
May | 0.185794E+11 | 26120.23 | 07-MAY-14:41 | 37.00 | 20.10 | 0.666529E+09 | 851.61 | 30-MAY-13:00 | 38.00 | 25.47 |
June | 0.197127E+11 | 25992.83 | 25-JUN-15:01 | 34.93 | 28.61 | 0.664285E+09 | 850.51 | 20-JUN-13:00 | 34.93 | 28.61 |
July | 0.223838E+11 | 26583.19 | 02-JUL-15:03 | 38.07 | 22.80 | 0.619400E+09 | 851.75 | 26-JUL-13:00 | 38.00 | 29.49 |
August | 0.254564E+11 | 25601.62 | 13-AUG-13:42 | 40.12 | 25.55 | 0.695664E+09 | 855.07 | 15-AUG-13:00 | 40.00 | 22.91 |
September | 0.220650E+11 | 28420.76 | 04-SEP-13:03 | 40.67 | 25.43 | 0.616328E+09 | 848.39 | 05-SEP-09:00 | 37.60 | 24.92 |
October | 0.221957E+11 | 28535.24 | 29-OCT-13:43 | 34.18 | 18.90 | 0.640398E+09 | 846.33 | 20-OCT-13:00 | 34.18 | 18.90 |
November | 0.173588E+11 | 27783.19 | 05-NOV-12:42 | 33.50 | 20.30 | 0.633207E+09 | 846.57 | 24-NOV-14:20 | 28.93 | 21.43 |
December | 0.123850E+11 | 27060.54 | 03-DEC-12:32 | 29.20 | 17.98 | 0.615341E+09 | 845.65 | 01-DEC-14:09 | 29.20 | 17.98 |
Annual Sum or Average | 0.207688E+12 | 0.766812E+10 | ||||||||
Minimum of Months | 0.932350E+10 | 19427.57 | 20.00 | 17.34 | 0.577426E+09 | 845.65 | 20.00 | 17.44 | ||
Maximum of Months | 0.254564E+11 | 28535.24 | 40.67 | 28.61 | 0.695664E+09 | 855.07 | 40.00 | 29.49 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.607641E+10 | 18103.34 | 30-JAN-05:12 | 20.00 | 17.44 | 0.408052E+09 | 544.96 | 17-JAN-14:09 | 20.00 | 17.44 |
February | 0.742776E+10 | 20736.36 | 27-FEB-05:12 | 18.00 | 16.52 | 0.373086E+09 | 544.98 | 15-FEB-14:09 | 18.00 | 16.52 |
March | 0.118248E+11 | 21197.04 | 21-MAR-04:12 | 17.67 | 13.93 | 0.446020E+09 | 544.99 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.147313E+11 | 23667.41 | 23-APR-16:02 | 32.25 | 18.47 | 0.396729E+09 | 551.11 | 28-APR-13:00 | 35.00 | 23.22 |
May | 0.151773E+11 | 26502.57 | 07-MAY-15:21 | 35.55 | 21.24 | 0.429616E+09 | 549.62 | 30-MAY-13:00 | 38.00 | 25.47 |
June | 0.172341E+11 | 27100.72 | 25-JUN-15:41 | 34.67 | 28.11 | 0.428399E+09 | 548.89 | 20-JUN-13:00 | 34.67 | 28.11 |
July | 0.195165E+11 | 27007.69 | 02-JUL-15:03 | 38.07 | 22.80 | 0.399640E+09 | 549.85 | 20-JUL-13:00 | 38.00 | 30.77 |
August | 0.221234E+11 | 25383.46 | 13-AUG-15:42 | 39.00 | 26.01 | 0.448943E+09 | 552.30 | 15-AUG-13:00 | 40.00 | 22.91 |
September | 0.151484E+11 | 26228.19 | 04-SEP-15:42 | 40.75 | 24.06 | 0.396880E+09 | 546.63 | 05-SEP-09:00 | 37.60 | 24.92 |
October | 0.145935E+11 | 24422.21 | 29-OCT-15:02 | 32.00 | 19.85 | 0.412266E+09 | 544.95 | 20-OCT-09:00 | 32.00 | 19.85 |
November | 0.123164E+11 | 25794.78 | 05-NOV-15:22 | 31.70 | 21.27 | 0.408039E+09 | 544.95 | 06-NOV-14:00 | 32.00 | 21.82 |
December | 0.102903E+11 | 23971.00 | 03-DEC-14:32 | 27.00 | 20.88 | 0.397722E+09 | 544.96 | 01-DEC-14:09 | 27.00 | 20.88 |
Annual Sum or Average | 0.166460E+12 | 0.494539E+10 | ||||||||
Minimum of Months | 0.607641E+10 | 18103.34 | 17.67 | 13.93 | 0.373086E+09 | 544.95 | 18.00 | 16.52 | ||
Maximum of Months | 0.221234E+11 | 27100.72 | 40.75 | 28.11 | 0.448943E+09 | 552.30 | 40.00 | 30.77 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.403766E+10 | 5319.62 | 23-JAN-14:10 | 27.50 | 16.66 | 0.609413E+09 | 845.62 | 17-JAN-14:09 | 27.50 | 16.66 |
February | 0.454530E+10 | 9502.20 | 06-FEB-06:02 | 21.88 | 19.06 | 0.563599E+09 | 845.65 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.708641E+10 | 15564.29 | 14-MAR-05:02 | 24.00 | 17.16 | 0.684461E+09 | 845.68 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.919552E+10 | 16178.13 | 24-APR-04:12 | 23.00 | 14.49 | 0.612777E+09 | 845.70 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.145880E+11 | 22749.81 | 28-MAY-16:31 | 35.00 | 23.27 | 0.665728E+09 | 845.68 | 08-MAY-13:30 | 35.00 | 23.27 |
June | 0.162795E+11 | 23514.69 | 04-JUN-16:11 | 36.67 | 28.92 | 0.663592E+09 | 845.65 | 02-JUN-13:09 | 36.67 | 28.92 |
July | 0.176126E+11 | 23057.23 | 09-JUL-17:31 | 35.33 | 27.43 | 0.617673E+09 | 845.73 | 21-JUL-13:09 | 42.25 | 27.34 |
August | 0.182969E+11 | 22772.79 | 06-AUG-15:01 | 40.85 | 24.99 | 0.692317E+09 | 845.86 | 04-AUG-13:20 | 40.85 | 24.99 |
September | 0.140645E+11 | 23257.95 | 03-SEP-13:31 | 39.97 | 25.60 | 0.614732E+09 | 845.62 | 26-SEP-09:00 | 36.90 | 21.78 |
October | 0.113554E+11 | 22679.83 | 09-OCT-14:51 | 37.00 | 20.70 | 0.638781E+09 | 845.61 | 20-OCT-09:00 | 30.40 | 18.49 |
November | 0.763559E+10 | 15020.71 | 25-NOV-06:02 | 24.93 | 18.48 | 0.629925E+09 | 845.62 | 06-NOV-14:00 | 24.93 | 18.48 |
December | 0.482183E+10 | 9490.30 | 12-DEC-06:03 | 23.03 | 17.89 | 0.600486E+09 | 845.63 | 01-DEC-14:09 | 23.03 | 17.89 |
Annual Sum or Average | 0.129519E+12 | 0.759348E+10 | ||||||||
Minimum of Months | 0.403766E+10 | 5319.62 | 21.88 | 14.49 | 0.563599E+09 | 845.61 | 23.03 | 16.66 | ||
Maximum of Months | 0.182969E+11 | 23514.69 | 40.85 | 28.92 | 0.692317E+09 | 845.86 | 42.25 | 28.92 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.361090E+10 | 4414.79 | 24-JAN-11:10 | 24.00 | 18.08 | 0.292111E+09 | 521.22 | 24-JAN-11:20 | 24.00 | 18.46 |
February | 0.400540E+10 | 7719.45 | 06-FEB-06:02 | 21.88 | 19.06 | 0.268860E+09 | 521.22 | 06-FEB-16:00 | 26.00 | 21.11 |
March | 0.606063E+10 | 13380.25 | 27-MAR-04:12 | 22.43 | 13.90 | 0.323867E+09 | 521.26 | 28-MAR-10:20 | 27.33 | 20.93 |
April | 0.805880E+10 | 20299.23 | 30-APR-10:52 | 34.00 | 21.75 | 0.291092E+09 | 521.24 | 28-APR-14:09 | 34.00 | 21.75 |
May | 0.122037E+11 | 21056.98 | 07-MAY-10:02 | 36.92 | 18.11 | 0.316047E+09 | 521.26 | 11-MAY-12:09 | 35.87 | 23.99 |
June | 0.129152E+11 | 20823.02 | 04-JUN-10:12 | 36.13 | 25.47 | 0.314503E+09 | 521.23 | 02-JUN-12:20 | 36.13 | 25.47 |
July | 0.138508E+11 | 20495.70 | 30-JUL-09:42 | 41.80 | 21.60 | 0.293839E+09 | 521.73 | 31-JUL-10:50 | 40.82 | 24.66 |
August | 0.147041E+11 | 19973.99 | 06-AUG-15:01 | 40.85 | 24.99 | 0.328101E+09 | 521.80 | 03-AUG-10:00 | 40.85 | 24.99 |
September | 0.116838E+11 | 20817.69 | 03-SEP-13:31 | 39.97 | 25.60 | 0.292069E+09 | 521.20 | 26-SEP-14:20 | 39.00 | 24.26 |
October | 0.963880E+10 | 20200.20 | 09-OCT-14:51 | 37.00 | 20.70 | 0.303876E+09 | 521.21 | 02-OCT-14:20 | 37.00 | 20.70 |
November | 0.650248E+10 | 13990.63 | 05-NOV-11:52 | 34.00 | 17.15 | 0.299461E+09 | 521.21 | 13-NOV-16:19 | 29.80 | 21.47 |
December | 0.410634E+10 | 5864.82 | 11-DEC-06:02 | 21.90 | 19.23 | 0.285379E+09 | 521.21 | 29-DEC-15:09 | 23.00 | 17.06 |
Annual Sum or Average | 0.107341E+12 | 0.360921E+10 | ||||||||
Minimum of Months | 0.361090E+10 | 4414.79 | 21.88 | 13.90 | 0.268860E+09 | 521.20 | 23.00 | 17.06 | ||
Maximum of Months | 0.147041E+11 | 21056.98 | 41.80 | 25.60 | 0.328101E+09 | 521.80 | 40.85 | 25.47 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.814670E+10 | 19401.63 | 23-JAN-06:01 | 17.98 | 16.09 | 0.629892E+09 | 845.66 | 24-JAN-10:00 | 24.00 | 17.69 |
February | 0.831596E+10 | 26569.84 | 05-FEB-13:32 | 31.43 | 19.44 | 0.573410E+09 | 845.70 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.104213E+11 | 25445.58 | 26-MAR-12:53 | 35.00 | 18.29 | 0.687770E+09 | 845.85 | 27-MAR-13:00 | 35.00 | 19.40 |
April | 0.108531E+11 | 22201.63 | 30-APR-14:11 | 33.00 | 24.33 | 0.613312E+09 | 845.73 | 28-APR-13:09 | 33.00 | 24.33 |
May | 0.147837E+11 | 25315.75 | 07-MAY-14:41 | 37.00 | 20.10 | 0.665544E+09 | 845.70 | 04-MAY-13:00 | 37.00 | 20.10 |
June | 0.156318E+11 | 25764.85 | 04-JUN-15:31 | 36.67 | 28.71 | 0.663253E+09 | 845.67 | 02-JUN-13:09 | 36.67 | 28.71 |
July | 0.174968E+11 | 25353.80 | 30-JUL-14:22 | 42.50 | 25.87 | 0.617435E+09 | 845.72 | 03-JUL-09:09 | 42.50 | 25.87 |
August | 0.196721E+11 | 25496.87 | 06-AUG-15:01 | 40.85 | 24.99 | 0.692377E+09 | 845.85 | 31-AUG-13:00 | 38.00 | 28.83 |
September | 0.175892E+11 | 27483.93 | 03-SEP-13:31 | 39.97 | 25.60 | 0.615272E+09 | 845.95 | 28-SEP-13:50 | 35.10 | 25.53 |
October | 0.171702E+11 | 27950.36 | 09-OCT-13:31 | 37.20 | 20.23 | 0.640221E+09 | 846.10 | 20-OCT-13:00 | 34.00 | 18.77 |
November | 0.136776E+11 | 27807.58 | 05-NOV-13:12 | 33.27 | 21.09 | 0.633047E+09 | 846.10 | 13-NOV-14:50 | 33.00 | 18.21 |
December | 0.953996E+10 | 26330.92 | 25-DEC-12:52 | 27.50 | 16.41 | 0.612223E+09 | 845.66 | 29-DEC-14:00 | 23.00 | 17.31 |
Annual Sum or Average | 0.163298E+12 | 0.764376E+10 | ||||||||
Minimum of Months | 0.814670E+10 | 19401.63 | 17.98 | 16.09 | 0.573410E+09 | 845.66 | 23.00 | 17.31 | ||
Maximum of Months | 0.196721E+11 | 27950.36 | 42.50 | 28.71 | 0.692377E+09 | 846.10 | 42.50 | 28.83 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.405885E+10 | 11865.76 | 23-JAN-06:01 | 17.98 | 16.09 | 0.389663E+09 | 544.95 | 17-JAN-14:09 | 17.98 | 16.09 |
February | 0.454826E+10 | 14628.41 | 05-FEB-15:32 | 32.00 | 19.08 | 0.361956E+09 | 544.98 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.691516E+10 | 19048.93 | 26-MAR-14:53 | 32.60 | 18.60 | 0.441206E+09 | 544.99 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.856777E+10 | 21683.82 | 30-APR-16:51 | 31.00 | 25.72 | 0.395364E+09 | 545.01 | 28-APR-13:09 | 31.00 | 25.72 |
May | 0.125256E+11 | 23597.21 | 28-MAY-16:31 | 35.00 | 23.27 | 0.429180E+09 | 544.99 | 04-MAY-13:00 | 35.00 | 23.27 |
June | 0.136659E+11 | 24277.54 | 04-JUN-16:11 | 36.67 | 28.92 | 0.427733E+09 | 544.97 | 02-JUN-13:09 | 36.67 | 28.92 |
July | 0.146881E+11 | 23604.45 | 09-JUL-15:31 | 36.47 | 26.51 | 0.398157E+09 | 545.00 | 03-JUL-09:09 | 36.47 | 26.51 |
August | 0.157651E+11 | 23144.32 | 06-AUG-16:21 | 40.05 | 25.93 | 0.446326E+09 | 544.94 | 04-AUG-13:30 | 40.05 | 25.93 |
September | 0.123103E+11 | 23894.74 | 03-SEP-16:11 | 37.17 | 26.54 | 0.396381E+09 | 544.95 | 26-SEP-09:00 | 36.90 | 21.78 |
October | 0.102259E+11 | 23387.54 | 09-OCT-14:51 | 37.00 | 20.70 | 0.412082E+09 | 544.95 | 20-OCT-09:00 | 30.40 | 18.49 |
November | 0.713531E+10 | 22111.40 | 05-NOV-15:12 | 31.80 | 21.10 | 0.406337E+09 | 544.95 | 06-NOV-14:00 | 32.00 | 21.82 |
December | 0.481548E+10 | 8755.29 | 11-DEC-06:02 | 21.90 | 19.23 | 0.386554E+09 | 544.96 | 29-DEC-14:00 | 23.00 | 17.31 |
Annual Sum or Average | 0.115222E+12 | 0.489094E+10 | ||||||||
Minimum of Months | 0.405885E+10 | 8755.29 | 17.98 | 16.09 | 0.361956E+09 | 544.94 | 17.98 | 16.09 | ||
Maximum of Months | 0.157651E+11 | 24277.54 | 40.05 | 28.92 | 0.446326E+09 | 545.01 | 40.05 | 28.92 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.388794E+10 | 5477.63 | 23-JAN-14:10 | 27.50 | 16.66 | 0.588215E+09 | 845.63 | 17-JAN-14:09 | 27.50 | 16.66 |
February | 0.448585E+10 | 10315.09 | 06-FEB-06:02 | 21.88 | 19.06 | 0.551669E+09 | 845.65 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.712542E+10 | 15215.69 | 14-MAR-05:02 | 24.00 | 17.16 | 0.677681E+09 | 845.68 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.949726E+10 | 18031.62 | 24-APR-04:12 | 23.00 | 14.49 | 0.611198E+09 | 845.70 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.153802E+11 | 26044.65 | 29-MAY-16:01 | 35.25 | 24.36 | 0.665700E+09 | 845.68 | 08-MAY-13:30 | 35.25 | 24.36 |
June | 0.172795E+11 | 26519.67 | 04-JUN-16:11 | 36.67 | 28.92 | 0.663588E+09 | 845.65 | 02-JUN-13:09 | 36.67 | 28.92 |
July | 0.189034E+11 | 26055.90 | 09-JUL-15:31 | 36.47 | 26.51 | 0.617729E+09 | 845.98 | 21-JUL-13:20 | 42.20 | 27.40 |
August | 0.195460E+11 | 25479.10 | 06-AUG-15:01 | 40.85 | 24.99 | 0.692385E+09 | 845.77 | 16-AUG-13:00 | 44.00 | 25.56 |
September | 0.149401E+11 | 26168.36 | 03-SEP-13:31 | 39.97 | 25.60 | 0.614740E+09 | 845.62 | 26-SEP-09:00 | 36.90 | 21.78 |
October | 0.117857E+11 | 25507.28 | 09-OCT-15:21 | 36.90 | 19.74 | 0.638648E+09 | 845.62 | 11-OCT-13:30 | 35.55 | 20.59 |
November | 0.761153E+10 | 15492.38 | 04-NOV-05:02 | 22.00 | 18.65 | 0.627473E+09 | 845.61 | 06-NOV-14:39 | 32.33 | 21.36 |
December | 0.468548E+10 | 6718.07 | 12-DEC-06:03 | 23.03 | 17.89 | 0.587662E+09 | 845.63 | 01-DEC-14:09 | 23.03 | 17.89 |
Annual Sum or Average | 0.135128E+12 | 0.753669E+10 | ||||||||
Minimum of Months | 0.388794E+10 | 5477.63 | 21.88 | 14.49 | 0.551669E+09 | 845.61 | 23.03 | 16.66 | ||
Maximum of Months | 0.195460E+11 | 26519.67 | 40.85 | 28.92 | 0.692385E+09 | 845.98 | 44.00 | 28.92 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.342769E+10 | 4267.96 | 24-JAN-11:00 | 24.00 | 17.69 | 0.392094E+09 | 544.96 | 24-JAN-10:00 | 24.00 | 17.69 |
February | 0.391844E+10 | 9122.44 | 06-FEB-06:02 | 21.88 | 19.06 | 0.363411E+09 | 544.98 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.611037E+10 | 12354.55 | 26-MAR-12:32 | 34.67 | 17.89 | 0.439661E+09 | 544.99 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.830025E+10 | 18641.79 | 02-APR-10:43 | 33.73 | 18.49 | 0.394732E+09 | 545.01 | 25-APR-09:09 | 31.00 | 20.82 |
May | 0.127657E+11 | 21739.16 | 29-MAY-10:42 | 37.35 | 22.00 | 0.429231E+09 | 544.99 | 08-MAY-13:30 | 37.35 | 22.00 |
June | 0.136365E+11 | 21773.02 | 04-JUN-15:31 | 36.67 | 28.71 | 0.427701E+09 | 544.97 | 02-JUN-13:09 | 36.67 | 28.71 |
July | 0.147427E+11 | 21460.46 | 09-JUL-14:51 | 37.00 | 26.64 | 0.398206E+09 | 545.23 | 31-JUL-09:20 | 38.63 | 24.24 |
August | 0.156020E+11 | 20863.86 | 06-AUG-15:01 | 40.85 | 24.99 | 0.446310E+09 | 545.14 | 16-AUG-09:00 | 38.90 | 27.43 |
September | 0.123187E+11 | 21863.55 | 03-SEP-13:31 | 39.97 | 25.60 | 0.396394E+09 | 544.96 | 26-SEP-09:00 | 36.90 | 21.78 |
October | 0.997945E+10 | 21195.28 | 09-OCT-14:41 | 37.00 | 20.65 | 0.412037E+09 | 544.95 | 20-OCT-09:00 | 30.40 | 18.49 |
November | 0.652361E+10 | 10909.58 | 04-NOV-05:02 | 22.00 | 18.65 | 0.405998E+09 | 544.95 | 22-NOV-10:39 | 24.97 | 17.55 |
December | 0.397465E+10 | 5028.83 | 01-DEC-10:40 | 26.47 | 16.31 | 0.384786E+09 | 544.96 | 01-DEC-14:09 | 28.00 | 18.44 |
Annual Sum or Average | 0.111300E+12 | 0.489056E+10 | ||||||||
Minimum of Months | 0.342769E+10 | 4267.96 | 21.88 | 16.31 | 0.363411E+09 | 544.95 | 24.00 | 17.55 | ||
Maximum of Months | 0.156020E+11 | 21863.55 | 40.85 | 28.71 | 0.446310E+09 | 545.23 | 38.90 | 28.71 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.758515E+10 | 15978.89 | 23-JAN-06:01 | 17.98 | 16.09 | 0.619630E+09 | 845.66 | 24-JAN-10:00 | 24.00 | 17.69 |
February | 0.800239E+10 | 28719.68 | 05-FEB-14:02 | 31.67 | 19.34 | 0.566967E+09 | 845.70 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.103229E+11 | 27330.92 | 26-MAR-12:32 | 34.67 | 17.89 | 0.683088E+09 | 845.70 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.111202E+11 | 21965.24 | 02-APR-12:43 | 32.62 | 17.34 | 0.611651E+09 | 845.72 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.155628E+11 | 28374.98 | 29-MAY-16:01 | 35.25 | 24.36 | 0.665491E+09 | 845.70 | 08-MAY-13:30 | 35.25 | 24.36 |
June | 0.166211E+11 | 28677.87 | 04-JUN-15:31 | 36.67 | 28.71 | 0.663264E+09 | 845.67 | 02-JUN-13:09 | 36.67 | 28.71 |
July | 0.187670E+11 | 28376.88 | 09-JUL-15:31 | 36.47 | 26.51 | 0.617513E+09 | 845.72 | 03-JUL-09:09 | 36.47 | 26.51 |
August | 0.209110E+11 | 28119.27 | 06-AUG-15:01 | 40.85 | 24.99 | 0.692440E+09 | 846.01 | 16-AUG-13:20 | 44.13 | 25.65 |
September | 0.184604E+11 | 30414.37 | 03-SEP-13:31 | 39.97 | 25.60 | 0.615238E+09 | 845.99 | 28-SEP-13:50 | 35.10 | 25.53 |
October | 0.175452E+11 | 30824.58 | 09-OCT-14:01 | 37.00 | 20.45 | 0.640130E+09 | 846.08 | 10-OCT-13:00 | 34.50 | 20.13 |
November | 0.134748E+11 | 28773.55 | 12-NOV-14:32 | 29.33 | 18.12 | 0.632228E+09 | 846.14 | 13-NOV-14:09 | 33.00 | 16.45 |
December | 0.901699E+10 | 28701.12 | 03-DEC-13:22 | 28.40 | 19.50 | 0.606634E+09 | 845.66 | 29-DEC-14:00 | 23.00 | 17.31 |
Annual Sum or Average | 0.167390E+12 | 0.761427E+10 | ||||||||
Minimum of Months | 0.758515E+10 | 15978.89 | 17.98 | 16.09 | 0.566967E+09 | 845.66 | 23.00 | 16.45 | ||
Maximum of Months | 0.209110E+11 | 30824.58 | 40.85 | 28.71 | 0.692440E+09 | 846.14 | 44.13 | 28.71 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.390773E+10 | 6945.70 | 30-JAN-06:03 | 20.03 | 17.43 | 0.378635E+09 | 544.95 | 17-JAN-14:09 | 20.03 | 17.43 |
February | 0.447046E+10 | 15165.36 | 05-FEB-15:22 | 32.00 | 19.15 | 0.355051E+09 | 544.98 | 15-FEB-14:09 | 25.67 | 18.27 |
March | 0.690005E+10 | 17680.28 | 27-MAR-04:12 | 22.43 | 13.90 | 0.436916E+09 | 544.99 | 28-MAR-09:00 | 27.00 | 19.86 |
April | 0.873010E+10 | 19648.45 | 23-APR-16:22 | 31.75 | 18.84 | 0.394178E+09 | 545.00 | 28-APR-13:09 | 36.42 | 23.03 |
May | 0.129787E+11 | 26303.52 | 29-MAY-16:01 | 35.25 | 24.36 | 0.429119E+09 | 544.99 | 04-MAY-13:00 | 35.25 | 24.36 |
June | 0.142817E+11 | 26384.45 | 04-JUN-16:11 | 36.67 | 28.92 | 0.427705E+09 | 544.97 | 02-JUN-13:09 | 36.67 | 28.92 |
July | 0.154670E+11 | 25821.28 | 09-JUL-15:31 | 36.47 | 26.51 | 0.398162E+09 | 545.00 | 03-JUL-09:09 | 36.47 | 26.51 |
August | 0.165487E+11 | 25013.47 | 06-AUG-16:21 | 40.05 | 25.93 | 0.446358E+09 | 544.94 | 04-AUG-13:00 | 40.05 | 25.93 |
September | 0.128545E+11 | 26141.14 | 03-SEP-15:31 | 37.60 | 26.81 | 0.396358E+09 | 544.95 | 26-SEP-09:00 | 36.90 | 21.78 |
October | 0.104725E+11 | 25558.93 | 09-OCT-15:21 | 36.90 | 19.74 | 0.411879E+09 | 544.95 | 11-OCT-13:30 | 35.55 | 20.59 |
November | 0.708631E+10 | 17164.84 | 12-NOV-14:32 | 29.33 | 18.12 | 0.404599E+09 | 544.95 | 06-NOV-14:39 | 29.33 | 18.12 |
December | 0.467633E+10 | 7196.89 | 06-DEC-15:30 | 26.85 | 20.67 | 0.379001E+09 | 544.96 | 01-DEC-14:09 | 26.85 | 20.67 |
Annual Sum or Average | 0.118374E+12 | 0.485796E+10 | ||||||||
Minimum of Months | 0.390773E+10 | 6945.70 | 20.03 | 13.90 | 0.355051E+09 | 544.94 | 20.03 | 17.43 | ||
Maximum of Months | 0.165487E+11 | 26384.45 | 40.05 | 28.92 | 0.446358E+09 | 545.00 | 40.05 | 28.92 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.570715E+10 | 9487.73 | 30-JAN-06:13 | 20.07 | 17.42 | 0.00 | 0.00 | 01-JAN-00:10 | 20.07 | 17.42 |
February | 0.713606E+10 | 12721.45 | 09-FEB-06:10 | 22.92 | 19.06 | 0.00 | 0.00 | 01-FEB-00:10 | 22.92 | 19.06 |
March | 0.108520E+11 | 13324.74 | 29-MAR-05:13 | 20.33 | 18.79 | 0.00 | 0.00 | 01-MAR-00:10 | 20.33 | 18.79 |
April | 0.136367E+11 | 15967.09 | 29-APR-05:10 | 25.00 | 16.37 | 0.00 | 0.00 | 01-APR-00:10 | 25.00 | 16.37 |
May | 0.206333E+11 | 22488.87 | 30-MAY-05:10 | 27.00 | 24.83 | 0.00 | 0.00 | 01-MAY-00:10 | 27.00 | 24.83 |
June | 0.227315E+11 | 22105.70 | 12-JUN-05:15 | 29.13 | 24.04 | 0.00 | 0.00 | 01-JUN-00:10 | 29.13 | 24.04 |
July | 0.255873E+11 | 25429.92 | 24-JUL-05:15 | 32.67 | 27.85 | 0.00 | 0.00 | 01-JUL-00:10 | 32.67 | 27.85 |
August | 0.285823E+11 | 27701.54 | 07-AUG-05:20 | 32.63 | 23.12 | 0.00 | 0.00 | 01-AUG-00:10 | 32.63 | 23.12 |
September | 0.221342E+11 | 25228.97 | 05-SEP-05:15 | 30.33 | 24.49 | 0.00 | 0.00 | 01-SEP-00:10 | 30.33 | 24.49 |
October | 0.199607E+11 | 21939.90 | 10-OCT-05:15 | 26.67 | 24.04 | 0.00 | 0.00 | 01-OCT-00:10 | 26.67 | 24.04 |
November | 0.136566E+11 | 17552.98 | 06-NOV-06:10 | 20.02 | 17.47 | 0.00 | 0.00 | 01-NOV-00:10 | 20.02 | 17.47 |
December | 0.847022E+10 | 12754.63 | 11-DEC-06:15 | 21.80 | 19.16 | 0.00 | 0.00 | 01-DEC-00:10 | 21.80 | 19.16 |
Annual Sum or Average | 0.199088E+12 | 0.00 | ||||||||
Minimum of Months | 0.570715E+10 | 9487.73 | 20.02 | 16.37 | 0.00 | 0.00 | 20.02 | 16.37 | ||
Maximum of Months | 0.285823E+11 | 27701.54 | 32.67 | 27.85 | 0.00 | 0.00 | 32.67 | 27.85 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.345521E+10 | 4597.96 | 27-JAN-06:10 | 13.03 | 11.34 | 0.00 | 0.00 | 01-JAN-00:10 | 13.03 | 11.34 |
February | 0.425462E+10 | 6670.45 | 07-FEB-16:20 | 28.00 | 22.57 | 0.00 | 0.00 | 01-FEB-00:10 | 28.00 | 22.57 |
March | 0.700410E+10 | 9950.33 | 27-MAR-16:00 | 35.00 | 18.85 | 0.00 | 0.00 | 01-MAR-00:10 | 35.00 | 18.85 |
April | 0.912798E+10 | 11166.37 | 24-APR-05:03 | 21.83 | 13.96 | 0.00 | 0.00 | 01-APR-00:10 | 21.83 | 13.96 |
May | 0.143375E+11 | 13317.18 | 01-MAY-05:02 | 20.98 | 20.98 | 0.00 | 0.00 | 01-MAY-00:10 | 20.98 | 20.98 |
June | 0.158274E+11 | 13956.33 | 05-JUN-05:02 | 29.00 | 23.92 | 0.00 | 0.00 | 01-JUN-00:10 | 29.00 | 23.92 |
July | 0.177495E+11 | 16319.38 | 05-JUL-05:01 | 30.00 | 28.44 | 0.00 | 0.00 | 01-JUL-00:10 | 30.00 | 28.44 |
August | 0.193801E+11 | 17548.95 | 08-AUG-05:01 | 30.00 | 29.16 | 0.00 | 0.00 | 01-AUG-00:10 | 30.00 | 29.16 |
September | 0.150052E+11 | 15586.46 | 01-SEP-05:02 | 29.75 | 23.78 | 0.00 | 0.00 | 01-SEP-00:10 | 29.75 | 23.78 |
October | 0.125770E+11 | 12105.21 | 24-OCT-05:02 | 24.83 | 22.06 | 0.00 | 0.00 | 01-OCT-00:10 | 24.83 | 22.06 |
November | 0.869870E+10 | 11009.23 | 02-NOV-05:03 | 23.00 | 21.53 | 0.00 | 0.00 | 01-NOV-00:10 | 23.00 | 21.53 |
December | 0.487754E+10 | 6705.64 | 01-DEC-06:12 | 17.33 | 12.60 | 0.00 | 0.00 | 01-DEC-00:10 | 17.33 | 12.60 |
Annual Sum or Average | 0.132295E+12 | 0.00 | ||||||||
Minimum of Months | 0.345521E+10 | 4597.96 | 13.03 | 11.34 | 0.00 | 0.00 | 13.03 | 11.34 | ||
Maximum of Months | 0.193801E+11 | 17548.95 | 35.00 | 29.16 | 0.00 | 0.00 | 35.00 | 29.16 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.380066E+10 | 8838.10 | 23-JAN-14:10 | 27.50 | 16.66 | 0.00 | 0.00 | 01-JAN-00:10 | 27.50 | 16.66 |
February | 0.535697E+10 | 14042.83 | 06-FEB-15:00 | 32.50 | 17.28 | 0.00 | 0.00 | 01-FEB-00:10 | 32.50 | 17.28 |
March | 0.933110E+10 | 19720.83 | 27-MAR-14:30 | 35.00 | 19.13 | 0.00 | 0.00 | 01-MAR-00:10 | 35.00 | 19.13 |
April | 0.131081E+11 | 21938.66 | 28-APR-12:50 | 37.58 | 22.61 | 0.00 | 0.00 | 01-APR-00:10 | 37.58 | 22.61 |
May | 0.217080E+11 | 24817.41 | 10-MAY-14:40 | 40.00 | 20.07 | 0.00 | 0.00 | 01-MAY-00:10 | 40.00 | 20.07 |
June | 0.242284E+11 | 25532.34 | 09-JUN-15:00 | 42.00 | 24.89 | 0.00 | 0.00 | 01-JUN-00:10 | 42.00 | 24.89 |
July | 0.275186E+11 | 27993.50 | 21-JUL-12:10 | 45.38 | 23.17 | 0.00 | 0.00 | 01-JUL-00:10 | 45.38 | 23.17 |
August | 0.292927E+11 | 28195.60 | 16-AUG-13:50 | 44.03 | 25.58 | 0.00 | 0.00 | 01-AUG-00:10 | 44.03 | 25.58 |
September | 0.217432E+11 | 25231.92 | 05-SEP-14:20 | 39.67 | 25.10 | 0.00 | 0.00 | 01-SEP-00:10 | 39.67 | 25.10 |
October | 0.166780E+11 | 20511.21 | 05-OCT-14:40 | 36.00 | 22.65 | 0.00 | 0.00 | 01-OCT-00:10 | 36.00 | 22.65 |
November | 0.102637E+11 | 16492.73 | 01-NOV-14:10 | 32.83 | 26.22 | 0.00 | 0.00 | 01-NOV-00:10 | 32.83 | 26.22 |
December | 0.519821E+10 | 11296.16 | 04-DEC-14:10 | 27.00 | 21.00 | 0.00 | 0.00 | 01-DEC-00:10 | 27.00 | 21.00 |
Annual Sum or Average | 0.188228E+12 | 0.00 | ||||||||
Minimum of Months | 0.380066E+10 | 8838.10 | 27.00 | 16.66 | 0.00 | 0.00 | 27.00 | 16.66 | ||
Maximum of Months | 0.292927E+11 | 28195.60 | 45.38 | 26.22 | 0.00 | 0.00 | 45.38 | 26.22 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.435308E+10 | 1937.05 | 31-JAN-17:00 | 23.00 | 17.31 | 95239934.83 | 126.85 | 17-JAN-14:00 | 23.00 | 17.31 |
February | 0.868363E+10 | 3881.52 | 07-FEB-17:00 | 28.00 | 21.23 | 86410134.64 | 126.86 | 07-FEB-10:09 | 28.00 | 21.23 |
March | 0.147577E+11 | 7241.81 | 31-MAR-24:00 | 22.30 | 20.22 | 0.103245E+09 | 126.84 | 30-MAR-09:09 | 22.30 | 20.22 |
April | 0.192742E+11 | 7898.90 | 30-APR-18:52 | 29.70 | 23.71 | 92030513.59 | 138.95 | 26-APR-13:09 | 29.70 | 23.71 |
May | 0.509387E+10 | 3706.10 | 31-MAY-23:55 | 32.70 | 23.39 | 99240724.90 | 126.86 | 02-MAY-13:30 | 32.70 | 23.39 |
June | 0.988789E+10 | 5548.03 | 30-JUN-24:00 | 31.70 | 26.86 | 98978290.65 | 126.87 | 23-JUN-09:09 | 31.70 | 26.86 |
July | 0.155162E+11 | 7463.59 | 31-JUL-24:00 | 33.30 | 28.31 | 91890479.47 | 126.84 | 26-JUL-09:09 | 33.30 | 28.31 |
August | 0.199061E+11 | 7823.83 | 14-AUG-03:20 | 31.00 | 24.35 | 0.113151E+09 | 152.14 | 10-AUG-13:00 | 31.00 | 24.35 |
September | 0.504393E+10 | 3658.56 | 30-SEP-23:57 | 29.00 | 26.44 | 91607689.49 | 126.85 | 21-SEP-13:09 | 29.00 | 26.44 |
October | 0.101663E+11 | 5519.01 | 31-OCT-23:53 | 27.40 | 21.22 | 95251031.46 | 126.87 | 17-OCT-09:09 | 27.40 | 21.22 |
November | 0.144650E+11 | 5994.88 | 12-NOV-17:00 | 29.00 | 17.88 | 94311100.98 | 126.84 | 07-NOV-10:09 | 29.00 | 17.88 |
December | 0.197225E+11 | 7712.42 | 12-DEC-17:00 | 23.80 | 16.27 | 91884229.46 | 126.83 | 15-DEC-10:09 | 19.67 | 18.50 |
Annual Sum or Average | 0.146870E+12 | 0.115324E+10 | ||||||||
Minimum of Months | 0.435308E+10 | 1937.05 | 22.30 | 16.27 | 86410134.64 | 126.83 | 19.67 | 17.31 | ||
Maximum of Months | 0.199061E+11 | 7898.90 | 33.30 | 28.31 | 0.113151E+09 | 152.14 | 33.30 | 28.31 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.341218E+10 | 1771.46 | 31-JAN-17:00 | 23.00 | 17.31 | 95234924.83 | 126.84 | 31-JAN-14:00 | 23.00 | 17.31 |
February | 0.776812E+10 | 3643.20 | 07-FEB-17:00 | 28.00 | 21.23 | 86409297.77 | 126.85 | 07-FEB-14:00 | 28.00 | 21.23 |
March | 0.138253E+11 | 6951.23 | 31-MAR-24:00 | 22.30 | 20.22 | 0.103245E+09 | 126.85 | 02-MAR-14:50 | 22.30 | 20.22 |
April | 0.182581E+11 | 7358.93 | 30-APR-18:00 | 30.00 | 25.49 | 91960942.49 | 138.69 | 26-APR-13:09 | 30.00 | 25.49 |
May | 0.451562E+10 | 3449.21 | 31-MAY-23:42 | 32.77 | 23.34 | 99238400.53 | 126.85 | 08-MAY-13:50 | 32.77 | 23.34 |
June | 0.910230E+10 | 5222.10 | 30-JUN-24:00 | 31.70 | 26.86 | 98980945.02 | 126.88 | 08-JUN-13:09 | 31.70 | 26.86 |
July | 0.143096E+11 | 7043.65 | 31-JUL-24:00 | 33.30 | 28.31 | 91893322.19 | 126.85 | 18-JUL-09:09 | 33.30 | 28.31 |
August | 0.187394E+11 | 7235.23 | 07-AUG-02:23 | 33.00 | 24.14 | 0.112280E+09 | 150.48 | 10-AUG-13:00 | 43.00 | 27.50 |
September | 0.438242E+10 | 3386.45 | 30-SEP-23:53 | 29.00 | 26.44 | 91606259.44 | 126.85 | 05-SEP-13:00 | 29.00 | 26.44 |
October | 0.931713E+10 | 5238.55 | 31-OCT-23:53 | 27.40 | 21.22 | 95252648.09 | 126.87 | 06-OCT-09:30 | 27.40 | 21.22 |
November | 0.135385E+11 | 5529.00 | 06-NOV-17:00 | 30.00 | 22.38 | 94312533.76 | 126.85 | 01-NOV-13:09 | 30.00 | 22.38 |
December | 0.183619E+11 | 7269.73 | 06-DEC-17:00 | 26.00 | 20.50 | 91884742.13 | 126.83 | 15-DEC-10:09 | 19.67 | 18.50 |
Annual Sum or Average | 0.135531E+12 | 0.115230E+10 | ||||||||
Minimum of Months | 0.341218E+10 | 1771.46 | 22.30 | 17.31 | 86409297.77 | 126.83 | 19.67 | 17.31 | ||
Maximum of Months | 0.187394E+11 | 7358.93 | 33.30 | 28.31 | 0.112280E+09 | 150.48 | 43.00 | 28.31 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.290822E+10 | 1796.94 | 31-JAN-17:00 | 23.00 | 17.31 | 95234296.85 | 126.84 | 31-JAN-14:00 | 23.00 | 17.31 |
February | 0.748168E+10 | 3685.81 | 06-FEB-16:00 | 31.40 | 17.56 | 86409461.41 | 126.85 | 07-FEB-14:00 | 28.00 | 22.41 |
March | 0.136731E+11 | 6892.97 | 31-MAR-24:00 | 22.30 | 20.22 | 0.103245E+09 | 126.85 | 02-MAR-14:30 | 22.30 | 20.22 |
April | 0.182667E+11 | 7540.61 | 23-APR-17:24 | 30.50 | 19.17 | 91976183.54 | 139.39 | 26-APR-13:09 | 37.33 | 19.85 |
May | 0.462606E+10 | 3497.38 | 31-MAY-23:42 | 32.77 | 23.34 | 99239185.96 | 126.86 | 02-MAY-13:30 | 32.77 | 23.34 |
June | 0.922654E+10 | 5238.09 | 30-JUN-24:00 | 31.70 | 26.86 | 98980222.05 | 126.88 | 23-JUN-09:00 | 31.70 | 26.86 |
July | 0.145030E+11 | 7096.89 | 31-JUL-24:00 | 33.30 | 28.31 | 91892781.22 | 126.85 | 18-JUL-09:09 | 33.30 | 28.31 |
August | 0.188812E+11 | 7337.26 | 07-AUG-03:01 | 33.07 | 23.68 | 0.112494E+09 | 152.14 | 10-AUG-13:00 | 43.00 | 27.50 |
September | 0.449655E+10 | 3420.53 | 30-SEP-23:47 | 29.00 | 26.42 | 91606732.22 | 126.85 | 25-SEP-13:20 | 29.00 | 26.42 |
October | 0.936340E+10 | 5236.06 | 31-OCT-23:53 | 27.40 | 21.22 | 95252468.13 | 126.87 | 06-OCT-09:30 | 27.40 | 21.22 |
November | 0.134463E+11 | 5597.75 | 05-NOV-17:05 | 30.83 | 21.62 | 94312480.07 | 126.85 | 01-NOV-09:09 | 30.83 | 21.62 |
December | 0.180226E+11 | 7294.71 | 06-DEC-17:00 | 26.00 | 20.50 | 91885001.40 | 126.83 | 15-DEC-10:09 | 19.67 | 18.50 |
Annual Sum or Average | 0.134895E+12 | 0.115253E+10 | ||||||||
Minimum of Months | 0.290822E+10 | 1796.94 | 22.30 | 17.31 | 86409461.41 | 126.83 | 19.67 | 17.31 | ||
Maximum of Months | 0.188812E+11 | 7540.61 | 33.30 | 28.31 | 0.112494E+09 | 152.14 | 43.00 | 28.31 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.244258E+12 | 94457.31 | 30-JAN-17:00 | 22.00 | 19.30 | 0.206209E+10 | 2747.84 | 19-JAN-10:20 | 22.00 | 19.30 |
February | 0.441258E+12 | 186422.83 | 09-FEB-16:12 | 21.73 | 19.39 | 0.187077E+10 | 2747.69 | 13-FEB-10:09 | 19.50 | 13.91 |
March | 0.733631E+12 | 360106.34 | 31-MAR-24:00 | 22.30 | 20.22 | 0.223517E+10 | 2746.75 | 16-MAR-09:09 | 22.30 | 20.22 |
April | 0.946656E+12 | 370099.51 | 28-APR-16:00 | 34.30 | 21.50 | 0.198529E+10 | 2917.08 | 28-APR-12:20 | 34.30 | 21.50 |
May | 0.247211E+12 | 178349.11 | 31-MAY-23:55 | 32.70 | 23.39 | 0.214874E+10 | 2747.23 | 30-MAY-13:20 | 32.70 | 23.39 |
June | 0.476825E+12 | 270150.89 | 30-JUN-24:00 | 31.70 | 26.86 | 0.214282E+10 | 2746.99 | 20-JUN-09:09 | 31.70 | 26.86 |
July | 0.740263E+12 | 362925.25 | 31-JUL-23:57 | 33.30 | 28.31 | 0.198937E+10 | 2746.26 | 26-JUL-09:09 | 33.30 | 28.31 |
August | 0.987328E+12 | 375618.82 | 10-AUG-21:01 | 34.93 | 27.53 | 0.228733E+10 | 3168.16 | 16-AUG-13:09 | 44.17 | 25.68 |
September | 0.244051E+12 | 179235.03 | 30-SEP-23:57 | 29.00 | 26.44 | 0.198373E+10 | 2747.21 | 15-SEP-09:20 | 29.00 | 26.44 |
October | 0.496869E+12 | 271773.20 | 31-OCT-23:53 | 27.40 | 21.22 | 0.206210E+10 | 2746.90 | 06-OCT-09:39 | 27.40 | 21.22 |
November | 0.715966E+12 | 280125.22 | 03-NOV-16:00 | 30.20 | 23.81 | 0.204167E+10 | 2746.04 | 01-NOV-13:39 | 30.20 | 23.81 |
December | 0.982309E+12 | 370983.24 | 12-DEC-17:00 | 23.80 | 16.27 | 0.198929E+10 | 2747.56 | 18-DEC-10:09 | 20.42 | 13.70 |
Annual Sum or Average | 0.725663E+13 | 0.247984E+11 | ||||||||
Minimum of Months | 0.244051E+12 | 94457.31 | 21.73 | 16.27 | 0.187077E+10 | 2746.04 | 19.50 | 13.70 | ||
Maximum of Months | 0.987328E+12 | 375618.82 | 34.93 | 28.31 | 0.228733E+10 | 3168.16 | 44.17 | 28.31 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 813188.61 | 1355.31 | 01-JAN-19:20 | 18.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 813188.61 | |||
Minimum of Months | 0.00 | 0.00 | 17.20 | |
Maximum of Months | 813188.61 | 1355.31 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 138900.00 | 612.98 | 02-JAN-06:07 | 13.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 138900.00 | |||
Minimum of Months | 0.00 | 0.00 | 13.00 | |
Maximum of Months | 138900.00 | 612.98 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 157027.74 | 481.74 | 02-JAN-06:07 | 13.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 157027.74 | |||
Minimum of Months | 0.00 | 0.00 | 13.00 | |
Maximum of Months | 157027.74 | 481.74 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 69983324.87 | 9275.93 | 31-JAN-05:12 | 16.67 |
February | 77736316.16 | 10065.09 | 10-FEB-05:11 | 19.93 |
March | 94542570.89 | 10849.19 | 06-MAR-05:12 | 16.67 |
April | 69638529.39 | 6885.81 | 01-APR-04:11 | 18.13 |
May | 40220383.55 | 7880.18 | 04-MAY-04:11 | 23.53 |
June | 22017782.56 | 3968.54 | 18-JUN-15:42 | 36.08 |
July | 33959753.05 | 5396.45 | 30-JUL-10:22 | 43.70 |
August | 32375704.43 | 4413.64 | 27-AUG-10:22 | 37.15 |
September | 32191204.65 | 4345.00 | 24-SEP-11:02 | 35.00 |
October | 85954555.46 | 5548.10 | 29-OCT-07:06 | 21.17 |
November | 0.126352E+09 | 8333.95 | 22-NOV-05:12 | 17.00 |
December | 0.132094E+09 | 12240.94 | 28-DEC-05:12 | 15.00 |
Annual Sum or Average | 0.817066E+09 | |||
Minimum of Months | 22017782.56 | 3968.54 | 15.00 | |
Maximum of Months | 0.132094E+09 | 12240.94 | 43.70 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 38011313.88 | 6518.93 | 02-JAN-05:12 | 13.67 |
February | 29060805.96 | 6958.78 | 21-FEB-05:12 | 14.67 |
March | 26766948.30 | 7554.56 | 02-MAR-04:02 | 29.10 |
April | 24867520.25 | 5952.24 | 02-APR-14:31 | 33.33 |
May | 27609336.77 | 5480.08 | 28-MAY-13:52 | 35.00 |
June | 20160266.29 | 4525.53 | 25-JUN-14:42 | 35.17 |
July | 34630374.90 | 5943.26 | 30-JUL-13:42 | 44.08 |
August | 22698737.60 | 5287.10 | 13-AUG-13:42 | 40.12 |
September | 26342496.37 | 5472.50 | 17-SEP-15:01 | 35.90 |
October | 34559295.68 | 5261.98 | 01-OCT-13:51 | 35.00 |
November | 30134077.16 | 4133.02 | 24-NOV-05:11 | 20.00 |
December | 35652427.82 | 5441.18 | 18-DEC-06:03 | 13.17 |
Annual Sum or Average | 0.350494E+09 | |||
Minimum of Months | 20160266.29 | 4133.02 | 13.17 | |
Maximum of Months | 38011313.88 | 7554.56 | 44.08 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.505146E+09 | 14979.12 | 13-JAN-06:02 | 13.93 |
February | 0.270286E+09 | 15554.02 | 01-FEB-06:02 | 13.02 |
March | 0.150264E+09 | 13965.41 | 06-MAR-06:03 | 15.97 |
April | 51613172.61 | 12061.82 | 05-APR-04:12 | 17.07 |
May | 12980209.79 | 8997.81 | 02-MAY-04:11 | 22.87 |
June | 929833.03 | 1576.30 | 02-JUN-03:02 | 28.93 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 6752.68 | 56.27 | 25-AUG-03:02 | 31.88 |
September | 2997197.07 | 3342.34 | 30-SEP-03:02 | 26.62 |
October | 23256036.92 | 9955.67 | 30-OCT-04:12 | 22.40 |
November | 58580704.67 | 12822.84 | 27-NOV-06:02 | 17.90 |
December | 0.259728E+09 | 14222.26 | 19-DEC-06:02 | 14.95 |
Annual Sum or Average | 0.133579E+10 | |||
Minimum of Months | 0.00 | 0.00 | 13.02 | |
Maximum of Months | 0.505146E+09 | 15554.02 | 31.88 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15.70 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 17.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22.85 |
April | 0.00 | 0.00 | 01-APR-00:03 | 22.05 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 26.90 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 32.60 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 31.72 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 33.23 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 31.93 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 28.98 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 27.12 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 21.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 15.70 | |
Maximum of Months | 0.00 | 0.00 | 33.23 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180249E+11 | 19402.09 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.163527E+11 | 19402.09 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.194806E+11 | 19402.09 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.173504E+11 | 19402.09 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.187528E+11 | 19402.09 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.186803E+11 | 19402.09 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.174228E+11 | 19402.09 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.194803E+11 | 19402.09 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.173504E+11 | 19402.09 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.180252E+11 | 19402.09 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.178272E+11 | 19402.09 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.174231E+11 | 19402.09 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.216171E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.163527E+11 | 19402.09 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.194806E+11 | 19402.09 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124735E+10 | 1906.53 | 04-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.108668E+10 | 1906.53 | 09-FEB-16:49 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.125737E+10 | 2187.81 | 14-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.108384E+10 | 1906.53 | 18-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.113384E+10 | 1141.96 | 23-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.111842E+10 | 1141.96 | 08-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.106374E+10 | 1524.25 | 20-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.119484E+10 | 1242.97 | 29-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.109099E+10 | 1242.97 | 06-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.117049E+10 | 1524.25 | 11-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.121322E+10 | 1906.53 | 13-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.122866E+10 | 2187.81 | 11-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.138894E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.106374E+10 | 1141.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.125737E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.786892E+09 | 1228.64 | 02-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.693739E+09 | 1228.64 | 09-FEB-16:40 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.803803E+09 | 1409.91 | 14-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.698206E+09 | 982.28 | 18-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.736393E+09 | 735.93 | 25-MAY-15:00 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.727787E+09 | 670.83 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.689524E+09 | 801.02 | 20-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.772256E+09 | 670.83 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.702361E+09 | 735.93 | 26-SEP-15:00 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.745245E+09 | 735.93 | 02-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.773946E+09 | 1409.91 | 29-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.773458E+09 | 1409.91 | 11-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.890361E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.689524E+09 | 670.83 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.803803E+09 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118212E+10 | 1524.28 | 09-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.105378E+10 | 1906.57 | 09-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.124328E+10 | 2187.86 | 14-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.108693E+10 | 1906.57 | 18-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.114994E+10 | 1141.99 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.113684E+10 | 1141.99 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.107673E+10 | 1524.28 | 14-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.120192E+10 | 1141.99 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.108772E+10 | 1243.00 | 06-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.114593E+10 | 1243.00 | 24-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.115592E+10 | 1805.57 | 29-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.115188E+10 | 1906.57 | 11-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.136730E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.105378E+10 | 1141.99 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.124328E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.780958E+09 | 1228.64 | 09-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.689191E+09 | 1228.64 | 09-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.812643E+09 | 1409.91 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.704966E+09 | 1228.64 | 18-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.741866E+09 | 801.02 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.730880E+09 | 801.02 | 08-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.695735E+09 | 1047.37 | 20-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.779284E+09 | 982.28 | 07-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.707090E+09 | 982.28 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.753321E+09 | 1163.55 | 24-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.756498E+09 | 1163.55 | 03-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.759292E+09 | 1228.64 | 14-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.891173E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.689191E+09 | 801.02 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.812643E+09 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124195E+10 | 1906.53 | 04-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.108270E+10 | 1906.53 | 09-FEB-16:49 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.125459E+10 | 2187.81 | 14-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.108207E+10 | 1906.53 | 18-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.113298E+10 | 1141.96 | 23-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.111679E+10 | 1141.96 | 08-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.106282E+10 | 1524.25 | 20-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.119380E+10 | 1141.96 | 07-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.108926E+10 | 1242.97 | 06-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.116820E+10 | 1524.25 | 11-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.120797E+10 | 1906.53 | 13-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.122272E+10 | 2187.81 | 14-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.138558E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.106282E+10 | 1141.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.125459E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.784708E+09 | 1228.64 | 02-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.692333E+09 | 1228.64 | 09-FEB-16:49 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.802286E+09 | 1409.91 | 14-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.697279E+09 | 982.28 | 18-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.735428E+09 | 670.83 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.726935E+09 | 670.83 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.688689E+09 | 801.02 | 20-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.771444E+09 | 670.83 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.701663E+09 | 670.83 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.744095E+09 | 735.93 | 05-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.772167E+09 | 1409.91 | 29-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.771224E+09 | 1409.91 | 11-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.888825E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.688689E+09 | 670.83 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.802286E+09 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118139E+10 | 1524.28 | 09-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.105276E+10 | 1906.57 | 09-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.124129E+10 | 2187.86 | 14-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.108512E+10 | 1906.57 | 18-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.114817E+10 | 1141.99 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.113494E+10 | 1141.99 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.107537E+10 | 1524.28 | 14-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.120053E+10 | 1141.99 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.108637E+10 | 1243.00 | 06-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.114451E+10 | 1243.00 | 24-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.115512E+10 | 1805.57 | 29-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.115079E+10 | 1906.57 | 11-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.136563E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.105276E+10 | 1141.99 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.124129E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.778432E+09 | 1228.64 | 09-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.687402E+09 | 982.28 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.810073E+09 | 1409.91 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.703319E+09 | 1228.64 | 18-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.740438E+09 | 801.02 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.729532E+09 | 801.02 | 08-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.694159E+09 | 982.28 | 14-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.777874E+09 | 982.28 | 07-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.706043E+09 | 982.28 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.751846E+09 | 1163.55 | 24-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.755079E+09 | 1163.55 | 03-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.757604E+09 | 1228.64 | 14-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.889180E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.687402E+09 | 801.02 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.810073E+09 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.124188E+10 | 1906.53 | 04-JAN-16:00 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.108270E+10 | 1906.53 | 09-FEB-16:49 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.125434E+10 | 2187.81 | 14-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.108195E+10 | 1906.53 | 18-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.113297E+10 | 1141.96 | 23-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.111679E+10 | 1141.96 | 08-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.106282E+10 | 1524.25 | 20-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.119378E+10 | 1141.96 | 07-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.108913E+10 | 1242.97 | 06-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.116813E+10 | 1524.25 | 11-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.120797E+10 | 1906.53 | 13-NOV-16:00 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.122247E+10 | 2187.81 | 14-DEC-16:00 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.138549E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.106282E+10 | 1141.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.125434E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.784593E+09 | 1228.64 | 02-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.692289E+09 | 1228.64 | 09-FEB-16:49 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.802210E+09 | 1409.91 | 14-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.697240E+09 | 982.28 | 18-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.735428E+09 | 670.83 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.726933E+09 | 670.83 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.688629E+09 | 801.02 | 20-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.771431E+09 | 670.83 | 01-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.701547E+09 | 670.83 | 01-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.744034E+09 | 735.93 | 05-OCT-15:00 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.772126E+09 | 1409.91 | 29-NOV-16:00 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.771185E+09 | 1409.91 | 11-DEC-16:00 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.888765E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.688629E+09 | 670.83 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.802210E+09 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118137E+10 | 1524.28 | 09-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.105268E+10 | 1906.57 | 09-FEB-16:00 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.124117E+10 | 2187.86 | 14-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.108499E+10 | 1906.57 | 18-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.114810E+10 | 1141.99 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.113485E+10 | 1141.99 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.107530E+10 | 1524.28 | 14-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.120044E+10 | 1141.99 | 01-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.108635E+10 | 1243.00 | 06-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.114451E+10 | 1243.00 | 24-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.115512E+10 | 1805.57 | 29-NOV-16:00 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.115079E+10 | 1906.57 | 11-DEC-16:00 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.136557E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.105268E+10 | 1141.99 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.124117E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.778432E+09 | 1228.64 | 09-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.687400E+09 | 982.28 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.810328E+09 | 1409.91 | 14-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.703306E+09 | 1228.64 | 18-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.740360E+09 | 801.02 | 01-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.729482E+09 | 801.02 | 08-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.693985E+09 | 982.28 | 14-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.777860E+09 | 982.28 | 07-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.706004E+09 | 982.28 | 01-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.751754E+09 | 1163.55 | 24-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.755040E+09 | 1163.55 | 03-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.757598E+09 | 1228.64 | 14-DEC-16:00 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.889155E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.687400E+09 | 801.02 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.810328E+09 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.522764E+10 | 5470.56 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.474186E+10 | 5470.56 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.563465E+10 | 5470.56 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.503289E+10 | 5470.56 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.543115E+10 | 5470.56 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.540489E+10 | 5470.56 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.505915E+10 | 5470.56 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.563465E+10 | 5470.56 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.503289E+10 | 5470.56 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.522764E+10 | 5470.56 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.516637E+10 | 5470.56 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.505915E+10 | 5470.56 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.626529E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.474186E+10 | 5470.56 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.563465E+10 | 5470.56 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.180249E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.163527E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.194806E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.173504E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.187528E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.186803E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.174228E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.194803E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.173504E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.180252E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.178272E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.174231E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.216171E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.163527E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.194806E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.124735E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 745730.88 | 67082201.59 |
February | 0.136985E+10 | 0.108668E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6193342.92 | 68552158.73 |
March | 0.163685E+10 | 0.125737E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15603851.25 | 36070351.60 |
April | 0.145243E+10 | 0.108384E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36572007.60 | 14425129.26 |
May | 0.157338E+10 | 0.113384E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 89517002.63 | 1531611.71 |
June | 0.156900E+10 | 0.111842E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112499E+09 | 94245.06 |
July | 0.145680E+10 | 0.106374E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158201E+09 | 0.00 |
August | 0.163685E+10 | 0.119484E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151145E+09 | 0.00 |
September | 0.145243E+10 | 0.109099E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107276E+09 | 206164.70 |
October | 0.150991E+10 | 0.117049E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60605435.50 | 2621640.35 |
November | 0.149516E+10 | 0.121322E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25253254.70 | 17210260.53 |
December | 0.145680E+10 | 0.122866E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3889997.01 | 49373339.67 |
Annual Sum or Average | 0.181194E+11 | 0.138894E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767502E+09 | 0.257167E+09 |
Minimum of Months | 0.136985E+10 | 0.106374E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 745730.88 | 0.00 |
Maximum of Months | 0.163685E+10 | 0.125737E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158201E+09 | 68552158.73 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.786892E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 396108.34 | 45147815.72 |
February | 0.882782E+09 | 0.693739E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3913010.04 | 45009456.53 |
March | 0.105485E+10 | 0.803803E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10629283.20 | 22648598.48 |
April | 0.936002E+09 | 0.698206E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24650527.98 | 8499963.08 |
May | 0.101394E+10 | 0.736393E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59762108.02 | 961683.42 |
June | 0.101113E+10 | 0.727787E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75899851.75 | 55178.60 |
July | 0.938820E+09 | 0.689524E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106011E+09 | 0.00 |
August | 0.105485E+10 | 0.772256E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101106E+09 | 0.00 |
September | 0.936002E+09 | 0.702361E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71643495.50 | 130933.17 |
October | 0.973041E+09 | 0.745245E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40702392.34 | 1648247.49 |
November | 0.963541E+09 | 0.773946E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17198739.86 | 10762685.36 |
December | 0.938820E+09 | 0.773458E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2837564.81 | 30301739.07 |
Annual Sum or Average | 0.116768E+11 | 0.890361E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.514750E+09 | 0.165166E+09 |
Minimum of Months | 0.882782E+09 | 0.689524E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 396108.34 | 0.00 |
Maximum of Months | 0.105485E+10 | 0.803803E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106011E+09 | 45147815.72 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.118212E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 335508.67 | 74392457.43 |
February | 0.136988E+10 | 0.105378E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5192583.45 | 73321295.46 |
March | 0.163688E+10 | 0.124328E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14960897.20 | 38129924.50 |
April | 0.145246E+10 | 0.108693E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35991336.14 | 14358611.63 |
May | 0.157341E+10 | 0.114994E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90675486.53 | 1356436.04 |
June | 0.156904E+10 | 0.113684E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114636E+09 | 60685.36 |
July | 0.145684E+10 | 0.107673E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159535E+09 | 0.00 |
August | 0.163688E+10 | 0.120192E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151589E+09 | 0.00 |
September | 0.145246E+10 | 0.108772E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106970E+09 | 198426.87 |
October | 0.150994E+10 | 0.114593E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58984251.64 | 2933469.33 |
November | 0.149520E+10 | 0.115592E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22444769.38 | 19364214.74 |
December | 0.145684E+10 | 0.115188E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3097367.08 | 54005376.88 |
Annual Sum or Average | 0.181198E+11 | 0.136730E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.764412E+09 | 0.278121E+09 |
Minimum of Months | 0.136988E+10 | 0.105378E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 335508.67 | 0.00 |
Maximum of Months | 0.163688E+10 | 0.124328E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159535E+09 | 74392457.43 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.780958E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 391460.24 | 51003087.19 |
February | 0.882782E+09 | 0.689191E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3676573.39 | 53737471.18 |
March | 0.105485E+10 | 0.812643E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9716487.13 | 30825763.15 |
April | 0.936002E+09 | 0.704966E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22752406.92 | 13002829.88 |
May | 0.101394E+10 | 0.741866E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60569047.19 | 1032624.85 |
June | 0.101113E+10 | 0.730880E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75471685.53 | 57504.88 |
July | 0.938820E+09 | 0.695735E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105102E+09 | 0.00 |
August | 0.105485E+10 | 0.779284E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99854865.80 | 0.00 |
September | 0.936002E+09 | 0.707090E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72967286.43 | 102081.41 |
October | 0.973041E+09 | 0.753321E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40609450.80 | 1749600.69 |
November | 0.963541E+09 | 0.756498E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15419183.48 | 14438901.72 |
December | 0.938820E+09 | 0.759292E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2091479.23 | 42326431.17 |
Annual Sum or Average | 0.116768E+11 | 0.891173E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508622E+09 | 0.208276E+09 |
Minimum of Months | 0.882782E+09 | 0.689191E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 391460.24 | 0.00 |
Maximum of Months | 0.105485E+10 | 0.812643E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105102E+09 | 53737471.18 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.124195E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3052241.33 | 0.131013E+09 |
February | 0.136985E+10 | 0.108270E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15775179.63 | 0.135425E+09 |
March | 0.163685E+10 | 0.125459E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35837511.94 | 78148382.26 |
April | 0.145243E+10 | 0.108207E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87252037.39 | 37775921.74 |
May | 0.157338E+10 | 0.113298E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211936E+09 | 3570171.66 |
June | 0.156900E+10 | 0.111679E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266664E+09 | 170151.75 |
July | 0.145680E+10 | 0.106282E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375498E+09 | 0.00 |
August | 0.163685E+10 | 0.119380E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360102E+09 | 0.00 |
September | 0.145243E+10 | 0.108926E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257304E+09 | 437807.57 |
October | 0.150991E+10 | 0.116820E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146995E+09 | 5622232.24 |
November | 0.149516E+10 | 0.120797E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63967569.19 | 38338731.70 |
December | 0.145680E+10 | 0.122272E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11003945.85 | 98068339.44 |
Annual Sum or Average | 0.181194E+11 | 0.138558E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183539E+10 | 0.528570E+09 |
Minimum of Months | 0.136985E+10 | 0.106282E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3052241.33 | 0.00 |
Maximum of Months | 0.163685E+10 | 0.125459E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375498E+09 | 0.135425E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.784708E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1201356.10 | 93756689.46 |
February | 0.649041E+09 | 0.692333E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9087663.54 | 95650820.45 |
March | 0.773965E+09 | 0.802286E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22997012.05 | 55248672.05 |
April | 0.688021E+09 | 0.697279E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55542975.60 | 27117196.36 |
May | 0.744847E+09 | 0.735428E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141238E+09 | 2529676.57 |
June | 0.742030E+09 | 0.726935E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179786E+09 | 105673.30 |
July | 0.690839E+09 | 0.688689E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252303E+09 | 0.00 |
August | 0.773965E+09 | 0.771444E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241437E+09 | 0.00 |
September | 0.688021E+09 | 0.701663E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171323E+09 | 314855.36 |
October | 0.715730E+09 | 0.744095E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96449278.41 | 4341509.47 |
November | 0.708685E+09 | 0.772167E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40099934.55 | 27996010.46 |
December | 0.690839E+09 | 0.771224E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6709324.75 | 68137404.83 |
Annual Sum or Average | 0.858171E+10 | 0.888825E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121817E+10 | 0.375199E+09 |
Minimum of Months | 0.649041E+09 | 0.688689E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1201356.10 | 0.00 |
Maximum of Months | 0.773965E+09 | 0.802286E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252303E+09 | 95650820.45 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.118139E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 705718.78 | 0.167858E+09 |
February | 0.136988E+10 | 0.105276E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11763303.03 | 0.163065E+09 |
March | 0.163688E+10 | 0.124129E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32985240.20 | 91438419.72 |
April | 0.145246E+10 | 0.108512E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83384817.46 | 40695450.14 |
May | 0.157341E+10 | 0.114817E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214059E+09 | 3540484.70 |
June | 0.156904E+10 | 0.113494E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271700E+09 | 116169.92 |
July | 0.145684E+10 | 0.107537E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379379E+09 | 0.00 |
August | 0.163688E+10 | 0.120053E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360435E+09 | 0.00 |
September | 0.145246E+10 | 0.108637E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251702E+09 | 561697.80 |
October | 0.150994E+10 | 0.114451E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136278E+09 | 8722883.12 |
November | 0.149520E+10 | 0.115512E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50630992.74 | 50417254.75 |
December | 0.145684E+10 | 0.115079E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6790552.75 | 0.125454E+09 |
Annual Sum or Average | 0.181198E+11 | 0.136563E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179981E+10 | 0.651870E+09 |
Minimum of Months | 0.136988E+10 | 0.105276E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 705718.78 | 0.00 |
Maximum of Months | 0.163688E+10 | 0.124129E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379379E+09 | 0.167858E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.778432E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1471576.64 | 97562029.78 |
February | 0.882782E+09 | 0.687402E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9562449.92 | 0.101612E+09 |
March | 0.105485E+10 | 0.810073E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22503389.42 | 62126714.40 |
April | 0.936002E+09 | 0.703319E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54772216.55 | 30939663.94 |
May | 0.101394E+10 | 0.740438E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139530E+09 | 3041170.63 |
June | 0.101113E+10 | 0.729532E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176624E+09 | 145971.48 |
July | 0.938820E+09 | 0.694159E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249583E+09 | 0.00 |
August | 0.105485E+10 | 0.777874E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238386E+09 | 0.00 |
September | 0.936002E+09 | 0.706043E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168568E+09 | 399220.21 |
October | 0.973041E+09 | 0.751846E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93941168.09 | 5437298.81 |
November | 0.963541E+09 | 0.755079E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38591517.23 | 30911688.05 |
December | 0.938820E+09 | 0.757604E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6178728.50 | 75004827.68 |
Annual Sum or Average | 0.116768E+11 | 0.889180E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119971E+10 | 0.407180E+09 |
Minimum of Months | 0.882782E+09 | 0.687402E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1471576.64 | 0.00 |
Maximum of Months | 0.105485E+10 | 0.810073E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249583E+09 | 0.101612E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.124188E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4177576.50 | 0.147670E+09 |
February | 0.136985E+10 | 0.108270E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19228405.92 | 0.158534E+09 |
March | 0.163685E+10 | 0.125434E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43361290.77 | 93471219.59 |
April | 0.145243E+10 | 0.108195E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104826E+09 | 46748883.64 |
May | 0.157338E+10 | 0.113297E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258541E+09 | 4674615.12 |
June | 0.156900E+10 | 0.111679E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325978E+09 | 211401.53 |
July | 0.145680E+10 | 0.106282E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459882E+09 | 0.00 |
August | 0.163685E+10 | 0.119378E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441184E+09 | 0.00 |
September | 0.145243E+10 | 0.108913E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313716E+09 | 602602.23 |
October | 0.150991E+10 | 0.116813E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178131E+09 | 7281753.00 |
November | 0.149516E+10 | 0.120797E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77446362.59 | 45856550.56 |
December | 0.145680E+10 | 0.122247E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14190867.20 | 0.112685E+09 |
Annual Sum or Average | 0.181194E+11 | 0.138549E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224066E+10 | 0.617736E+09 |
Minimum of Months | 0.136985E+10 | 0.106282E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4177576.50 | 0.00 |
Maximum of Months | 0.163685E+10 | 0.125434E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.459882E+09 | 0.158534E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.784593E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1484755.22 | 0.108263E+09 |
February | 0.882782E+09 | 0.692289E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10899557.09 | 0.113893E+09 |
March | 0.105485E+10 | 0.802210E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27668385.40 | 67152406.56 |
April | 0.936002E+09 | 0.697240E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66741575.59 | 33733634.54 |
May | 0.101394E+10 | 0.735428E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171605E+09 | 3362072.78 |
June | 0.101113E+10 | 0.726933E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218654E+09 | 147704.60 |
July | 0.938820E+09 | 0.688629E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307731E+09 | 0.00 |
August | 0.105485E+10 | 0.771431E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294681E+09 | 0.00 |
September | 0.936002E+09 | 0.701547E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207984E+09 | 441689.15 |
October | 0.973041E+09 | 0.744034E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116299E+09 | 5708068.86 |
November | 0.963541E+09 | 0.772126E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47778846.98 | 33976623.82 |
December | 0.938820E+09 | 0.771185E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8241515.80 | 79728754.79 |
Annual Sum or Average | 0.116768E+11 | 0.888765E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147977E+10 | 0.446407E+09 |
Minimum of Months | 0.882782E+09 | 0.688629E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1484755.22 | 0.00 |
Maximum of Months | 0.105485E+10 | 0.802210E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307731E+09 | 0.113893E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.118137E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 819462.58 | 0.195937E+09 |
February | 0.136988E+10 | 0.105268E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14162875.57 | 0.194224E+09 |
March | 0.163688E+10 | 0.124117E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39930997.18 | 0.110703E+09 |
April | 0.145246E+10 | 0.108499E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100787E+09 | 50320544.23 |
May | 0.157341E+10 | 0.114810E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260951E+09 | 4631539.44 |
June | 0.156904E+10 | 0.113485E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331547E+09 | 151762.83 |
July | 0.145684E+10 | 0.107530E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464025E+09 | 0.00 |
August | 0.163688E+10 | 0.120044E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441499E+09 | 0.00 |
September | 0.145246E+10 | 0.108635E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307400E+09 | 781601.72 |
October | 0.150994E+10 | 0.114451E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165672E+09 | 11280400.05 |
November | 0.149520E+10 | 0.115512E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60971238.82 | 61222801.46 |
December | 0.145684E+10 | 0.115079E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7996738.21 | 0.148649E+09 |
Annual Sum or Average | 0.181198E+11 | 0.136557E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219576E+10 | 0.777903E+09 |
Minimum of Months | 0.136988E+10 | 0.105268E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 819462.58 | 0.00 |
Maximum of Months | 0.163688E+10 | 0.124117E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464025E+09 | 0.195937E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.778432E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1789064.21 | 0.114052E+09 |
February | 0.882782E+09 | 0.687400E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11551799.15 | 0.121355E+09 |
March | 0.105485E+10 | 0.810328E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27330877.23 | 75449382.64 |
April | 0.936002E+09 | 0.703306E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66507717.33 | 38161033.31 |
May | 0.101394E+10 | 0.740360E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170583E+09 | 3911576.10 |
June | 0.101113E+10 | 0.729482E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216328E+09 | 204153.78 |
July | 0.938820E+09 | 0.693985E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306184E+09 | 0.00 |
August | 0.105485E+10 | 0.777860E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292411E+09 | 0.00 |
September | 0.936002E+09 | 0.706004E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206116E+09 | 553578.29 |
October | 0.973041E+09 | 0.751754E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114447E+09 | 6986120.45 |
November | 0.963541E+09 | 0.755040E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46504655.76 | 37458576.67 |
December | 0.938820E+09 | 0.757598E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7616364.13 | 88440653.35 |
Annual Sum or Average | 0.116768E+11 | 0.889155E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146737E+10 | 0.486572E+09 |
Minimum of Months | 0.882782E+09 | 0.687400E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1789064.21 | 0.00 |
Maximum of Months | 0.105485E+10 | 0.810328E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306184E+09 | 0.121355E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.522764E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.474186E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.563465E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.503289E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.543115E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.540489E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.505915E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.563465E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.503289E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.522764E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.516637E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.505915E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.626529E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.474186E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.563465E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 871705.17 | 0.150239E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10465074.36 | 0.150719E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25543234.52 | 82991433.41 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64726368.35 | 36045279.24 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163316E+09 | 4468172.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204408E+09 | 508875.10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290622E+09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275571E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192688E+09 | 694590.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104950E+09 | 8087142.67 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40646238.28 | 42092871.22 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5475484.88 | 0.113096E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137928E+10 | 0.588943E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 871705.17 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290622E+09 | 0.150719E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2627074.14 | 0.245871E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20671489.77 | 0.246912E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47123184.05 | 0.139545E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122497E+09 | 63635884.09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314908E+09 | 6058487.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392201E+09 | 502222.01 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.563046E+09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531843E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376147E+09 | 761768.23 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207748E+09 | 10966791.17 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80611366.35 | 69519797.69 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12045272.59 | 0.184148E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267147E+10 | 0.967921E+09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2627074.14 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.563046E+09 | 0.246912E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1678477.13 | 0.254459E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19697493.75 | 0.263979E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47231032.06 | 0.153762E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118355E+09 | 68332920.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337292E+09 | 6278525.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433685E+09 | 444768.87 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621969E+09 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.595839E+09 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413514E+09 | 795186.68 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225116E+09 | 11057588.66 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83751639.71 | 67480259.44 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10452422.47 | 0.188808E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290858E+10 | 0.101540E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1678477.13 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621969E+09 | 0.263979E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 19402.09 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 19402.09 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 19402.09 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 19402.09 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 19402.09 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 19402.09 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 19402.09 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 19402.09 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 19402.09 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 19402.09 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 19402.09 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 19402.09 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 19402.09 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 19402.09 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1906.53 | 04-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 46.21 | 29-JAN-11:35 | 182.61 | 18-JAN-04:00 |
February | 2010.79 | 01-FEB-10:09 | 1906.53 | 09-FEB-16:49 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 140.07 | 05-FEB-15:10 | 154.52 | 10-FEB-24:00 |
March | 2010.79 | 01-MAR-10:09 | 2187.81 | 14-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 119.28 | 26-MAR-14:00 | 124.41 | 17-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 1906.53 | 18-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.00 | 30-APR-13:08 | 93.41 | 05-APR-01:20 |
May | 2010.79 | 01-MAY-09:09 | 1141.96 | 23-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 936.64 | 21-MAY-12:51 | 30.98 | 01-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 1141.96 | 08-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.36 | 11-JUN-14:26 | 22.50 | 07-JUN-04:30 |
July | 2010.79 | 03-JUL-09:09 | 1524.25 | 20-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 350.73 | 30-JUL-14:25 | 0.00 | 01-JUL-00:03 |
August | 2010.79 | 01-AUG-09:09 | 1242.97 | 29-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 327.48 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 2010.79 | 01-SEP-09:09 | 1242.97 | 06-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.85 | 03-SEP-15:45 | 23.39 | 25-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 1524.25 | 11-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 220.58 | 09-OCT-15:06 | 56.01 | 20-OCT-04:20 |
November | 2010.79 | 01-NOV-09:09 | 1906.53 | 13-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.97 | 19-NOV-14:00 | 77.54 | 22-NOV-03:55 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 11-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 54.79 | 10-DEC-12:50 | 117.90 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 46.21 | 0.00 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 936.64 | 182.61 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1228.64 | 02-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 23.20 | 29-JAN-12:00 | 121.19 | 18-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 1228.64 | 09-FEB-16:40 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 93.76 | 05-FEB-15:10 | 101.22 | 13-FEB-03:55 |
March | 1295.83 | 01-MAR-10:09 | 1409.91 | 14-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 82.41 | 26-MAR-14:00 | 80.97 | 17-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 982.28 | 18-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.81 | 30-APR-13:08 | 59.44 | 05-APR-01:20 |
May | 1295.83 | 01-MAY-09:09 | 735.93 | 25-MAY-15:00 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 624.45 | 21-MAY-12:51 | 20.37 | 01-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 670.83 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.05 | 11-JUN-14:26 | 14.89 | 07-JUN-04:30 |
July | 1295.83 | 03-JUL-09:09 | 801.02 | 20-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.53 | 30-JUL-14:50 | 0.00 | 01-JUL-00:03 |
August | 1295.83 | 01-AUG-09:09 | 670.83 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.31 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 1295.83 | 01-SEP-09:09 | 735.93 | 26-SEP-15:00 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.70 | 03-SEP-15:45 | 15.91 | 25-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 735.93 | 02-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.27 | 09-OCT-15:06 | 36.56 | 20-OCT-04:20 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 29-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.87 | 19-NOV-14:00 | 49.65 | 22-NOV-03:55 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 11-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 41.88 | 10-DEC-12:30 | 73.32 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 23.20 | 0.00 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 624.45 | 121.19 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1524.28 | 09-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.27 | 29-JAN-12:00 | 190.98 | 18-JAN-04:00 |
February | 2010.83 | 01-FEB-10:09 | 1906.57 | 09-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 124.52 | 05-FEB-15:05 | 164.82 | 10-FEB-23:50 |
March | 2010.83 | 01-MAR-10:09 | 2187.86 | 14-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 116.36 | 26-MAR-13:55 | 136.48 | 17-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 1906.57 | 18-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.61 | 30-APR-13:05 | 94.31 | 05-APR-01:20 |
May | 2010.83 | 01-MAY-09:09 | 1141.99 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 936.65 | 21-MAY-12:51 | 30.34 | 01-MAY-05:00 |
June | 2010.83 | 01-JUN-09:09 | 1141.99 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.20 | 11-JUN-14:26 | 20.49 | 07-JUN-04:30 |
July | 2010.83 | 03-JUL-09:09 | 1524.28 | 14-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 350.29 | 30-JUL-14:50 | 0.00 | 01-JUL-00:03 |
August | 2010.83 | 01-AUG-09:09 | 1141.99 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 327.47 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 2010.83 | 01-SEP-09:09 | 1243.00 | 06-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.12 | 03-SEP-16:00 | 23.23 | 25-SEP-05:00 |
October | 2010.83 | 02-OCT-09:09 | 1243.00 | 24-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.30 | 09-OCT-15:10 | 57.42 | 20-OCT-04:20 |
November | 2010.83 | 01-NOV-09:09 | 1805.57 | 29-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.23 | 05-NOV-14:45 | 78.86 | 22-NOV-03:55 |
December | 2010.83 | 01-DEC-10:09 | 1906.57 | 11-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 49.92 | 10-DEC-11:48 | 114.31 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1141.99 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 25.27 | 0.00 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 936.65 | 190.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1228.64 | 09-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.43 | 29-JAN-11:35 | 139.64 | 18-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 1228.64 | 09-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 84.67 | 05-FEB-15:08 | 124.79 | 10-FEB-24:00 |
March | 1295.83 | 01-MAR-10:09 | 1409.91 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 78.33 | 26-MAR-13:55 | 113.78 | 17-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 1228.64 | 18-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.17 | 30-APR-13:05 | 80.00 | 05-APR-01:20 |
May | 1295.83 | 01-MAY-09:09 | 801.02 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 624.62 | 21-MAY-12:51 | 23.65 | 01-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 801.02 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.23 | 11-JUN-14:24 | 16.98 | 07-JUN-04:30 |
July | 1295.83 | 03-JUL-09:09 | 1047.37 | 20-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.52 | 30-JUL-14:50 | 0.00 | 01-JUL-00:03 |
August | 1295.83 | 01-AUG-09:09 | 982.28 | 07-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.31 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 1295.83 | 01-SEP-09:09 | 982.28 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.44 | 04-SEP-17:05 | 15.78 | 25-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 1163.55 | 24-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.09 | 09-OCT-15:04 | 38.61 | 20-OCT-05:00 |
November | 1295.83 | 01-NOV-09:09 | 1163.55 | 03-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.05 | 19-NOV-13:36 | 62.33 | 22-NOV-03:55 |
December | 1295.83 | 01-DEC-10:09 | 1228.64 | 14-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.54 | 10-DEC-11:50 | 95.57 | 16-DEC-24:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 801.02 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 30.43 | 0.00 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 624.62 | 139.64 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1906.53 | 04-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 151.67 | 29-JAN-11:43 | 352.23 | 18-JAN-04:00 |
February | 2010.79 | 01-FEB-10:09 | 1906.53 | 09-FEB-16:49 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 350.43 | 05-FEB-14:40 | 300.33 | 10-FEB-23:20 |
March | 2010.79 | 01-MAR-10:09 | 2187.81 | 14-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 290.62 | 26-MAR-14:00 | 291.82 | 05-MAR-14:53 |
April | 2010.79 | 03-APR-09:09 | 1906.53 | 18-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 387.58 | 30-APR-12:57 | 214.78 | 05-APR-00:53 |
May | 2010.79 | 01-MAY-09:09 | 1141.96 | 23-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2119.01 | 21-MAY-12:51 | 63.50 | 02-MAY-02:53 |
June | 2010.79 | 01-JUN-09:09 | 1141.96 | 08-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 535.10 | 11-JUN-14:34 | 45.25 | 07-JUN-05:00 |
July | 2010.79 | 03-JUL-09:09 | 1524.25 | 20-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 815.46 | 30-JUL-14:50 | 0.00 | 01-JUL-00:03 |
August | 2010.79 | 01-AUG-09:09 | 1141.96 | 07-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 761.71 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 2010.79 | 01-SEP-09:09 | 1242.97 | 06-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 586.61 | 03-SEP-15:35 | 41.86 | 25-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 1524.25 | 11-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 501.69 | 09-OCT-15:34 | 115.62 | 20-OCT-04:03 |
November | 2010.79 | 01-NOV-09:09 | 1906.53 | 13-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 345.23 | 19-NOV-13:52 | 163.71 | 22-NOV-06:00 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 14-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 163.05 | 10-DEC-13:00 | 231.08 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 151.67 | 0.00 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 2119.01 | 352.23 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1228.64 | 02-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 61.18 | 29-JAN-11:50 | 244.14 | 18-JAN-04:00 |
February | 1239.33 | 01-FEB-08:09 | 1228.64 | 09-FEB-16:49 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 219.62 | 05-FEB-15:00 | 205.87 | 10-FEB-24:00 |
March | 1239.33 | 01-MAR-08:09 | 1409.91 | 14-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 197.57 | 02-MAR-04:10 | 202.22 | 05-MAR-14:53 |
April | 1239.33 | 03-APR-07:10 | 982.28 | 18-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 264.44 | 30-APR-12:55 | 148.18 | 05-APR-00:53 |
May | 1239.33 | 01-MAY-07:10 | 670.83 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1398.09 | 21-MAY-12:51 | 45.28 | 02-MAY-02:53 |
June | 1239.33 | 01-JUN-07:10 | 670.83 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 360.78 | 11-JUN-13:16 | 28.20 | 07-JUN-05:00 |
July | 1239.33 | 03-JUL-07:10 | 801.02 | 20-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 543.64 | 30-JUL-14:50 | 0.00 | 01-JUL-00:03 |
August | 1239.33 | 01-AUG-07:10 | 670.83 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 508.14 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 1239.33 | 01-SEP-07:10 | 670.83 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 391.90 | 03-SEP-15:34 | 27.77 | 25-SEP-05:00 |
October | 1239.33 | 02-OCT-07:10 | 735.93 | 05-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 341.19 | 09-OCT-15:34 | 80.85 | 20-OCT-04:03 |
November | 1239.33 | 01-NOV-07:10 | 1409.91 | 29-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.94 | 19-NOV-14:10 | 108.10 | 22-NOV-06:00 |
December | 1239.33 | 01-DEC-08:09 | 1409.91 | 11-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 105.58 | 10-DEC-13:00 | 150.57 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 61.18 | 0.00 | |||||
Maximum of Months | 1239.33 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 1398.09 | 244.14 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1524.28 | 09-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.94 | 23-JAN-13:00 | 404.38 | 18-JAN-04:00 |
February | 2010.83 | 01-FEB-10:09 | 1906.57 | 09-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 278.16 | 05-FEB-14:56 | 349.02 | 10-FEB-23:10 |
March | 2010.83 | 01-MAR-10:09 | 2187.86 | 14-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 276.23 | 02-MAR-04:08 | 345.66 | 05-MAR-14:53 |
April | 2010.83 | 03-APR-09:09 | 1906.57 | 18-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 389.88 | 30-APR-12:55 | 222.34 | 05-APR-00:53 |
May | 2010.83 | 01-MAY-09:09 | 1141.99 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2115.38 | 21-MAY-12:51 | 64.99 | 02-MAY-02:53 |
June | 2010.83 | 01-JUN-09:09 | 1141.99 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 538.96 | 11-JUN-13:16 | 41.45 | 07-JUN-05:00 |
July | 2010.83 | 03-JUL-09:09 | 1524.28 | 14-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 815.46 | 30-JUL-14:50 | 0.00 | 01-JUL-00:03 |
August | 2010.83 | 01-AUG-09:09 | 1141.99 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 761.71 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 2010.83 | 01-SEP-09:09 | 1243.00 | 06-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 580.64 | 03-SEP-16:00 | 46.07 | 25-SEP-05:00 |
October | 2010.83 | 02-OCT-09:09 | 1243.00 | 24-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 497.61 | 09-OCT-14:54 | 132.09 | 20-OCT-04:03 |
November | 2010.83 | 01-NOV-09:09 | 1805.57 | 29-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 265.78 | 05-NOV-14:35 | 173.03 | 22-NOV-06:00 |
December | 2010.83 | 01-DEC-10:09 | 1906.57 | 11-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 110.11 | 10-DEC-12:58 | 233.56 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1141.99 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 37.94 | 0.00 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 2115.38 | 404.38 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1228.64 | 09-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 103.10 | 29-JAN-11:43 | 254.36 | 18-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 982.28 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 214.45 | 05-FEB-13:00 | 222.84 | 10-FEB-23:20 |
March | 1295.83 | 01-MAR-10:09 | 1409.91 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 201.21 | 02-MAR-04:08 | 229.74 | 05-MAR-14:53 |
April | 1295.83 | 03-APR-09:09 | 1228.64 | 18-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 262.87 | 30-APR-12:57 | 160.85 | 05-APR-00:53 |
May | 1295.83 | 01-MAY-09:09 | 801.02 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1403.01 | 21-MAY-12:51 | 50.17 | 02-MAY-02:53 |
June | 1295.83 | 01-JUN-09:09 | 801.02 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 360.60 | 11-JUN-13:16 | 33.44 | 07-JUN-05:00 |
July | 1295.83 | 03-JUL-09:09 | 982.28 | 14-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 543.63 | 30-JUL-14:50 | 0.00 | 01-JUL-00:03 |
August | 1295.83 | 01-AUG-09:09 | 982.28 | 07-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 507.80 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 1295.83 | 01-SEP-09:09 | 982.28 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 390.34 | 04-SEP-13:54 | 30.85 | 25-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 1163.55 | 24-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 338.70 | 09-OCT-14:54 | 89.93 | 20-OCT-04:03 |
November | 1295.83 | 01-NOV-09:09 | 1163.55 | 03-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.17 | 19-NOV-13:43 | 114.35 | 22-NOV-06:00 |
December | 1295.83 | 01-DEC-10:09 | 1228.64 | 14-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 112.01 | 10-DEC-12:20 | 158.22 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 801.02 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 103.10 | 0.00 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1403.01 | 254.36 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1906.53 | 04-JAN-16:00 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 200.67 | 29-JAN-11:43 | 401.50 | 18-JAN-04:00 |
February | 2010.79 | 01-FEB-10:09 | 1906.53 | 09-FEB-16:49 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 433.57 | 05-FEB-15:00 | 347.73 | 10-FEB-23:10 |
March | 2010.79 | 01-MAR-10:09 | 2187.81 | 14-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 350.05 | 26-MAR-14:00 | 353.14 | 05-MAR-15:05 |
April | 2010.79 | 03-APR-09:09 | 1906.53 | 18-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 464.18 | 30-APR-13:08 | 258.91 | 05-APR-00:53 |
May | 2010.79 | 01-MAY-09:09 | 1141.96 | 23-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2586.07 | 21-MAY-12:51 | 78.78 | 02-MAY-02:53 |
June | 2010.79 | 01-JUN-09:09 | 1141.96 | 08-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 662.39 | 11-JUN-13:16 | 43.65 | 07-JUN-04:40 |
July | 2010.79 | 03-JUL-09:09 | 1524.25 | 20-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1004.93 | 30-JUL-14:50 | 0.00 | 01-JUL-00:03 |
August | 2010.79 | 01-AUG-09:09 | 1141.96 | 07-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 937.89 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 2010.79 | 01-SEP-09:09 | 1242.97 | 06-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 719.60 | 04-SEP-13:54 | 52.67 | 25-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 1524.25 | 11-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 615.47 | 09-OCT-16:05 | 144.12 | 20-OCT-04:03 |
November | 2010.79 | 01-NOV-09:09 | 1906.53 | 13-NOV-16:00 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 425.63 | 19-NOV-14:00 | 198.81 | 22-NOV-05:53 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 14-DEC-16:00 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 198.34 | 10-DEC-12:20 | 264.45 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 198.34 | 0.00 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 2586.07 | 401.50 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1228.64 | 02-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 80.33 | 29-JAN-11:50 | 280.62 | 18-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 1228.64 | 09-FEB-16:49 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 269.50 | 05-FEB-14:52 | 239.77 | 10-FEB-23:10 |
March | 1295.83 | 01-MAR-10:09 | 1409.91 | 14-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 245.15 | 02-MAR-04:00 | 244.91 | 05-MAR-15:05 |
April | 1295.83 | 03-APR-09:09 | 982.28 | 18-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 314.54 | 30-APR-13:08 | 178.81 | 05-APR-00:53 |
May | 1295.83 | 01-MAY-09:09 | 670.83 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1705.47 | 21-MAY-12:51 | 56.10 | 02-MAY-02:53 |
June | 1295.83 | 01-JUN-09:09 | 670.83 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 448.78 | 11-JUN-13:16 | 28.31 | 07-JUN-04:40 |
July | 1295.83 | 03-JUL-09:09 | 801.02 | 20-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 669.95 | 30-JUL-14:50 | 0.00 | 01-JUL-00:03 |
August | 1295.83 | 01-AUG-09:09 | 670.83 | 01-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 625.26 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 1295.83 | 01-SEP-09:09 | 670.83 | 01-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 488.68 | 03-SEP-15:35 | 35.46 | 25-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 735.93 | 05-OCT-15:00 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 416.69 | 09-OCT-16:05 | 100.45 | 20-OCT-04:03 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 29-NOV-16:00 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 264.27 | 19-NOV-13:50 | 133.41 | 22-NOV-05:53 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 11-DEC-16:00 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 127.65 | 10-DEC-12:40 | 172.66 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 80.33 | 0.00 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 1705.47 | 280.62 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1524.28 | 09-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.54 | 23-JAN-13:00 | 467.48 | 18-JAN-04:00 |
February | 2010.83 | 01-FEB-10:09 | 1906.57 | 09-FEB-16:00 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 332.48 | 05-FEB-15:26 | 409.29 | 10-FEB-23:10 |
March | 2010.83 | 01-MAR-10:09 | 2187.86 | 14-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 329.12 | 26-MAR-13:55 | 421.50 | 05-MAR-14:53 |
April | 2010.83 | 03-APR-09:09 | 1906.57 | 18-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 464.22 | 30-APR-13:08 | 268.09 | 05-APR-00:53 |
May | 2010.83 | 01-MAY-09:09 | 1141.99 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2581.40 | 21-MAY-12:51 | 82.22 | 01-MAY-03:00 |
June | 2010.83 | 01-JUN-09:09 | 1141.99 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 668.23 | 11-JUN-14:36 | 39.68 | 07-JUN-04:40 |
July | 2010.83 | 03-JUL-09:09 | 1524.28 | 14-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1004.93 | 30-JUL-14:50 | 0.00 | 01-JUL-00:03 |
August | 2010.83 | 01-AUG-09:09 | 1141.99 | 01-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 937.89 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 2010.83 | 01-SEP-09:09 | 1243.00 | 06-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 713.49 | 03-SEP-16:00 | 57.59 | 25-SEP-05:00 |
October | 2010.83 | 02-OCT-09:09 | 1243.00 | 24-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 615.58 | 09-OCT-15:24 | 163.59 | 20-OCT-04:03 |
November | 2010.83 | 01-NOV-09:09 | 1805.57 | 29-NOV-16:00 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 330.25 | 19-NOV-13:45 | 212.36 | 22-NOV-05:53 |
December | 2010.83 | 01-DEC-10:09 | 1906.57 | 11-DEC-16:00 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 125.40 | 10-DEC-11:35 | 267.80 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1141.99 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 45.54 | 0.00 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 2581.40 | 467.48 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1228.64 | 09-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 130.24 | 29-JAN-11:43 | 294.94 | 18-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 982.28 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 263.47 | 05-FEB-14:50 | 260.84 | 10-FEB-23:10 |
March | 1295.83 | 01-MAR-10:09 | 1409.91 | 14-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 238.11 | 02-MAR-04:00 | 282.48 | 05-MAR-15:00 |
April | 1295.83 | 03-APR-09:09 | 1228.64 | 18-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 314.72 | 30-APR-13:10 | 194.02 | 05-APR-00:53 |
May | 1295.83 | 01-MAY-09:09 | 801.02 | 01-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1712.47 | 21-MAY-12:51 | 61.84 | 02-MAY-02:53 |
June | 1295.83 | 01-JUN-09:09 | 801.02 | 08-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 448.83 | 11-JUN-13:16 | 33.47 | 07-JUN-04:40 |
July | 1295.83 | 03-JUL-09:09 | 982.28 | 14-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 669.94 | 30-JUL-14:50 | 0.00 | 01-JUL-00:03 |
August | 1295.83 | 01-AUG-09:09 | 982.28 | 07-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 625.25 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 1295.83 | 01-SEP-09:09 | 982.28 | 01-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 482.70 | 04-SEP-13:54 | 38.12 | 25-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 1163.55 | 24-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 415.31 | 09-OCT-15:24 | 111.40 | 20-OCT-04:03 |
November | 1295.83 | 01-NOV-09:09 | 1163.55 | 03-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 255.56 | 19-NOV-13:50 | 142.96 | 22-NOV-05:53 |
December | 1295.83 | 01-DEC-10:09 | 1228.64 | 14-DEC-16:00 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 137.13 | 10-DEC-12:00 | 182.86 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 801.02 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 130.24 | 0.00 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 1712.47 | 294.94 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 5470.56 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 5470.56 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 5470.56 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 5470.56 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 5470.56 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 5470.56 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 5470.56 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 5470.56 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 5470.56 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 5470.56 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 5470.56 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 5470.56 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 5470.56 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.92 | 29-JAN-11:43 | 396.35 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.59 | 05-FEB-14:52 | 329.74 | 13-FEB-03:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.27 | 26-MAR-14:00 | 280.88 | 06-MAR-05:55 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.53 | 30-APR-12:52 | 202.19 | 05-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1786.30 | 21-MAY-13:00 | 66.05 | 01-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.13 | 11-JUN-12:52 | 47.03 | 07-JUN-04:53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 657.51 | 30-JUL-14:50 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 603.42 | 13-AUG-14:10 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.62 | 03-SEP-16:00 | 51.07 | 25-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 384.96 | 09-OCT-14:51 | 111.68 | 20-OCT-04:23 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.26 | 19-NOV-14:00 | 174.54 | 22-NOV-05:53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.24 | 10-DEC-12:50 | 246.26 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.92 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1786.30 | 396.35 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.96 | 29-JAN-11:53 | 645.37 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 529.35 | 05-FEB-14:42 | 546.34 | 10-FEB-24:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 456.70 | 26-MAR-14:00 | 481.54 | 06-MAR-06:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 614.58 | 30-APR-13:00 | 364.28 | 05-APR-00:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3429.59 | 21-MAY-12:51 | 101.07 | 01-MAY-04:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 838.85 | 11-JUN-13:00 | 76.97 | 07-JUN-05:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1261.17 | 30-JUL-14:50 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1187.57 | 13-AUG-14:00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 902.68 | 03-SEP-16:00 | 69.91 | 25-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 762.69 | 09-OCT-15:20 | 183.58 | 20-OCT-04:12 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.83 | 19-NOV-13:52 | 302.79 | 22-NOV-06:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.84 | 10-DEC-12:40 | 416.83 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.96 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3429.59 | 645.37 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.28 | 29-JAN-11:53 | 653.96 | 18-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 511.38 | 05-FEB-15:00 | 532.59 | 13-FEB-03:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 413.95 | 26-MAR-14:00 | 578.93 | 05-MAR-15:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 618.72 | 30-APR-12:52 | 382.53 | 05-APR-00:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3370.76 | 21-MAY-12:51 | 115.92 | 01-MAY-04:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.74 | 11-JUN-13:00 | 74.50 | 07-JUN-04:53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1302.83 | 30-JUL-14:10 | 0.00 | 01-JUL-00:03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1205.82 | 13-AUG-14:10 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 929.85 | 04-SEP-17:00 | 71.08 | 25-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 774.10 | 09-OCT-15:00 | 212.57 | 20-OCT-04:13 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 481.07 | 19-NOV-14:00 | 297.26 | 22-NOV-05:53 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.40 | 10-DEC-12:20 | 414.96 | 16-DEC-03:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.28 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3370.76 | 653.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 120248.88 | 01-JAN-19:02 | 0.00 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 126437.87 | 10-FEB-05:41 | 0.00 | 5983.50 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 109139.29 | 06-MAR-05:12 | 0.00 | 3590.10 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 110168.59 | 13-APR-05:08 | 8976.13 | 2991.75 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 93121.31 | 01-MAY-10:00 | 17832.21 | 19402.09 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 98405.64 | 22-JUN-09:50 | 17832.21 | 19402.09 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 01-JUL-00:03 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 01-AUG-00:05 | 0.00 | 1196.70 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 01-SEP-00:03 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 110886.34 | 21-OCT-05:51 | 16157.03 | 19402.81 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 120456.52 | 13-NOV-06:41 | 17952.25 | 21558.68 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 118811.31 | 13-DEC-00:42 | 0.00 | 2393.40 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 0.00 | 0.00 | 1196.70 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 126437.87 | 17952.25 | 21558.68 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 104147.20 | 02-JAN-05:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 106666.84 | 09-FEB-05:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 103016.81 | 16-MAR-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 99768.03 | 01-APR-04:13 | 0.00 | 3761.52 | 31172.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 103477.69 | 15-MAY-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 95137.63 | 12-JUN-04:23 | 0.00 | 2149.44 | 23750.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 105292.70 | 05-JUL-03:03 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 106104.47 | 28-AUG-03:03 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 104618.96 | 05-SEP-03:03 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 103487.11 | 21-OCT-04:24 | 0.00 | 2686.80 | 22266.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 105670.49 | 27-NOV-05:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 104068.57 | 28-DEC-05:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 95137.63 | 0.00 | 2149.44 | 22266.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 106666.84 | 0.00 | 3761.52 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 88846.67 | 23-JAN-06:02 | 14510.15 | 4836.24 | 68826.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 89925.74 | 10-FEB-05:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 91144.52 | 06-MAR-05:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 91233.63 | 05-APR-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 90723.30 | 04-MAY-04:13 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 70074.64 | 02-JUN-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 70866.64 | 06-JUL-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 71389.46 | 21-AUG-05:01 | 11285.67 | 3761.52 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 69748.86 | 28-SEP-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 96182.79 | 20-OCT-04:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 90998.11 | 16-NOV-05:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 90433.61 | 06-DEC-05:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 69748.86 | 0.00 | 2686.80 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 96182.79 | 14510.15 | 4836.24 | 68826.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 84185.91 | 25-JAN-06:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 90170.98 | 08-FEB-05:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 89980.55 | 29-MAR-04:12 | 0.00 | 2149.44 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 91042.39 | 21-APR-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 86560.96 | 03-MAY-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 74959.56 | 02-JUN-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 84877.92 | 31-JUL-05:03 | 11285.67 | 3761.52 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 83811.98 | 28-AUG-05:01 | 11285.67 | 3761.52 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 76595.98 | 11-SEP-05:02 | 9673.43 | 3224.16 | 45884.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 88636.43 | 21-OCT-04:12 | 0.00 | 2686.80 | 22266.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 90901.88 | 16-NOV-05:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 89475.46 | 12-DEC-05:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 74959.56 | 0.00 | 2149.44 | 22266.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 91042.39 | 11285.67 | 3761.52 | 53531.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13113.34 | 23-JAN-06:01 | 1821.89 | 607.24 | 8642.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.89 |
February | 18185.98 | 09-FEB-05:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.58 |
March | 16206.49 | 02-MAR-05:12 | 0.00 | 269.88 | 2982.24 | 0.00 | 0.00 | 0.00 | 0.00 | 72.16 | 0.00 |
April | 18362.39 | 30-APR-13:42 | 506.08 | 289.13 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 132.88 | 0.00 |
May | 23507.69 | 07-MAY-14:41 | 708.51 | 404.79 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 148.03 | 0.00 |
June | 24769.91 | 11-JUN-17:02 | 0.00 | 462.61 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 173.93 | 0.00 |
July | 24739.74 | 02-JUL-17:02 | 0.00 | 462.61 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 137.56 | 0.00 |
August | 22851.76 | 13-AUG-13:42 | 607.30 | 346.96 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 275.33 | 0.00 |
September | 24617.39 | 04-SEP-13:03 | 708.51 | 404.79 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 214.05 | 0.00 |
October | 21935.11 | 29-OCT-11:42 | 607.30 | 346.96 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.98 | 0.00 |
November | 22151.73 | 05-NOV-14:42 | 607.30 | 346.96 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.79 | 0.00 |
December | 16537.39 | 11-DEC-06:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13113.34 | 0.00 | 269.88 | 2982.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24769.91 | 1821.89 | 607.24 | 8642.21 | 0.00 | 0.00 | 0.00 | 0.00 | 275.33 | 34.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8653.51 | 30-JAN-05:12 | 0.00 | 260.89 | 2882.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.76 |
February | 14746.01 | 09-FEB-05:12 | 0.00 | 260.89 | 2882.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.78 |
March | 9818.69 | 27-MAR-10:30 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 44.36 | 0.00 |
April | 18527.84 | 23-APR-09:23 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 18.61 | 0.00 |
May | 20476.01 | 07-MAY-10:02 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 37.08 | 0.00 |
June | 20305.47 | 11-JUN-10:21 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 75.72 | 0.00 |
July | 20875.76 | 02-JUL-10:23 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 119.88 | 0.00 |
August | 19318.56 | 13-AUG-10:22 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 166.38 | 0.00 |
September | 21004.17 | 04-SEP-10:23 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 100.63 | 0.00 |
October | 18784.41 | 09-OCT-10:22 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 15.96 | 0.00 |
November | 17693.49 | 05-NOV-10:42 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 25.53 | 0.00 |
December | 7832.28 | 11-DEC-06:02 | 652.28 | 217.40 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7832.28 | 0.00 | 149.06 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21004.17 | 1239.33 | 670.83 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 166.38 | 19.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19427.57 | 30-JAN-05:12 | 0.00 | 404.83 | 4473.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.30 |
February | 25784.35 | 05-FEB-12:23 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 81.33 | 0.00 |
March | 25611.02 | 26-MAR-12:32 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 44.56 | 0.00 |
April | 21701.52 | 02-APR-12:43 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 54.14 | 0.00 |
May | 26120.23 | 07-MAY-14:41 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 149.67 | 0.00 |
June | 25992.83 | 25-JUN-15:01 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 137.70 | 0.00 |
July | 26583.19 | 02-JUL-15:03 | 809.75 | 462.62 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 207.94 | 0.00 |
August | 25601.62 | 13-AUG-13:42 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 274.99 | 0.00 |
September | 28420.76 | 04-SEP-13:03 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 206.58 | 0.00 |
October | 28535.24 | 29-OCT-13:43 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 114.37 | 0.00 |
November | 27783.19 | 05-NOV-12:42 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 65.48 | 0.00 |
December | 27060.54 | 03-DEC-12:32 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 5.57 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19427.57 | 0.00 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28535.24 | 809.75 | 462.62 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 274.99 | 19.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18103.34 | 30-JAN-05:12 | 0.00 | 260.89 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.09 |
February | 20736.36 | 27-FEB-05:12 | 0.00 | 260.89 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.47 |
March | 21197.04 | 21-MAR-04:12 | 0.00 | 260.89 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.84 |
April | 23667.41 | 23-APR-16:02 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 70.48 | 0.00 |
May | 26502.57 | 07-MAY-15:21 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 91.93 | 0.00 |
June | 27100.72 | 25-JUN-15:41 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 66.17 | 0.00 |
July | 27007.69 | 02-JUL-15:03 | 521.82 | 298.13 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 132.60 | 0.00 |
August | 25383.46 | 13-AUG-15:42 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 161.87 | 0.00 |
September | 26228.19 | 04-SEP-15:42 | 587.05 | 335.39 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.01 | 0.00 |
October | 24422.21 | 29-OCT-15:02 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 54.38 | 0.00 |
November | 25794.78 | 05-NOV-15:22 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 54.67 | 0.00 |
December | 23971.00 | 03-DEC-14:32 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1.56 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18103.34 | 0.00 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27100.72 | 587.05 | 335.39 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.87 | 29.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5319.62 | 23-JAN-14:10 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 29.52 | 0.00 |
February | 9502.20 | 06-FEB-06:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.05 |
March | 15564.29 | 14-MAR-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.21 |
April | 16178.13 | 24-APR-04:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.72 |
May | 22749.81 | 28-MAY-16:31 | 708.51 | 404.79 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 248.10 | 0.00 |
June | 23514.69 | 04-JUN-16:11 | 809.73 | 462.61 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 255.59 | 0.00 |
July | 23057.23 | 09-JUL-17:31 | 0.00 | 404.79 | 3914.20 | 0.00 | 0.00 | 0.00 | 0.00 | 280.14 | 0.00 |
August | 22772.79 | 06-AUG-15:01 | 708.51 | 404.79 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 474.43 | 0.00 |
September | 23257.95 | 03-SEP-13:31 | 708.51 | 404.79 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 412.37 | 0.00 |
October | 22679.83 | 09-OCT-14:51 | 708.51 | 404.79 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 459.99 | 0.00 |
November | 15020.71 | 25-NOV-06:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 0.00 |
December | 9490.30 | 12-DEC-06:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.86 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5319.62 | 0.00 | 269.88 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23514.69 | 2010.79 | 1040.96 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 474.43 | 21.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4414.79 | 24-JAN-11:10 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
February | 7719.45 | 06-FEB-06:02 | 652.28 | 217.40 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.12 |
March | 13380.25 | 27-MAR-04:12 | 0.00 | 260.89 | 2882.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.51 |
April | 20299.23 | 30-APR-10:52 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 83.82 | 0.00 |
May | 21056.98 | 07-MAY-10:02 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 89.55 | 0.00 |
June | 20823.02 | 04-JUN-10:12 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 146.06 | 0.00 |
July | 20495.70 | 30-JUL-09:42 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 235.32 | 0.00 |
August | 19973.99 | 06-AUG-15:01 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 317.53 | 0.00 |
September | 20817.69 | 03-SEP-13:31 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 269.51 | 0.00 |
October | 20200.20 | 09-OCT-14:51 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 301.37 | 0.00 |
November | 13990.63 | 05-NOV-11:52 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 73.07 | 0.00 |
December | 5864.82 | 11-DEC-06:02 | 652.28 | 217.40 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4414.79 | 0.00 | 186.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21056.98 | 1239.33 | 670.83 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 317.53 | 16.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19401.63 | 23-JAN-06:01 | 1821.93 | 607.25 | 8642.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.82 |
February | 26569.84 | 05-FEB-13:32 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 186.39 | 0.00 |
March | 25445.58 | 26-MAR-12:53 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 118.15 | 0.00 |
April | 22201.63 | 30-APR-14:11 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 295.64 | 0.00 |
May | 25315.75 | 07-MAY-14:41 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 355.14 | 0.00 |
June | 25764.85 | 04-JUN-15:31 | 809.75 | 462.62 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 274.84 | 0.00 |
July | 25353.80 | 30-JUL-14:22 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 787.81 | 0.00 |
August | 25496.87 | 06-AUG-15:01 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 473.74 | 0.00 |
September | 27483.93 | 03-SEP-13:31 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 384.66 | 0.00 |
October | 27950.36 | 09-OCT-13:31 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 317.61 | 0.00 |
November | 27807.58 | 05-NOV-13:12 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 164.58 | 0.00 |
December | 26330.92 | 25-DEC-12:52 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 19401.63 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27950.36 | 1821.93 | 607.25 | 8642.34 | 0.00 | 0.00 | 0.00 | 0.00 | 787.81 | 24.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11865.76 | 23-JAN-06:01 | 1174.10 | 391.33 | 5569.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.80 |
February | 14628.41 | 05-FEB-15:32 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 172.25 | 0.00 |
March | 19048.93 | 26-MAR-14:53 | 260.91 | 149.06 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 144.86 | 0.00 |
April | 21683.82 | 30-APR-16:51 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 99.45 | 0.00 |
May | 23597.21 | 28-MAY-16:31 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 144.53 | 0.00 |
June | 24277.54 | 04-JUN-16:11 | 521.82 | 298.13 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 152.63 | 0.00 |
July | 23604.45 | 09-JUL-15:31 | 521.82 | 298.13 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 231.20 | 0.00 |
August | 23144.32 | 06-AUG-16:21 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 259.22 | 0.00 |
September | 23894.74 | 03-SEP-16:11 | 521.82 | 298.13 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 289.83 | 0.00 |
October | 23387.54 | 09-OCT-14:51 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 279.02 | 0.00 |
November | 22111.40 | 05-NOV-15:12 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 148.05 | 0.00 |
December | 8755.29 | 11-DEC-06:02 | 652.28 | 217.40 | 3094.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8755.29 | 260.91 | 149.06 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24277.54 | 1174.10 | 391.33 | 5569.33 | 0.00 | 0.00 | 0.00 | 0.00 | 289.83 | 17.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5477.63 | 23-JAN-14:10 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 35.47 | 0.00 |
February | 10315.09 | 06-FEB-06:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.53 |
March | 15215.69 | 14-MAR-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.05 |
April | 18031.62 | 24-APR-04:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.91 |
May | 26044.65 | 29-MAY-16:01 | 809.73 | 462.61 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 283.48 | 0.00 |
June | 26519.67 | 04-JUN-16:11 | 809.73 | 462.61 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 302.90 | 0.00 |
July | 26055.90 | 09-JUL-15:31 | 809.73 | 462.61 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 454.43 | 0.00 |
August | 25479.10 | 06-AUG-15:01 | 708.51 | 404.79 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 576.29 | 0.00 |
September | 26168.36 | 03-SEP-13:31 | 708.51 | 404.79 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 496.44 | 0.00 |
October | 25507.28 | 09-OCT-15:21 | 708.51 | 404.79 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 543.19 | 0.00 |
November | 15492.38 | 04-NOV-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.68 |
December | 6718.07 | 12-DEC-06:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5477.63 | 0.00 | 269.88 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26519.67 | 2010.79 | 1040.96 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 576.29 | 27.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4267.96 | 24-JAN-11:00 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.05 |
February | 9122.44 | 06-FEB-06:02 | 652.28 | 217.40 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.58 |
March | 12354.55 | 26-MAR-12:32 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 87.40 | 0.00 |
April | 18641.79 | 02-APR-10:43 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 90.32 | 0.00 |
May | 21739.16 | 29-MAY-10:42 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 154.83 | 0.00 |
June | 21773.02 | 04-JUN-15:31 | 521.82 | 298.13 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 209.59 | 0.00 |
July | 21460.46 | 09-JUL-14:51 | 521.82 | 298.13 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 336.11 | 0.00 |
August | 20863.86 | 06-AUG-15:01 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 384.71 | 0.00 |
September | 21863.55 | 03-SEP-13:31 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 323.13 | 0.00 |
October | 21195.28 | 09-OCT-14:41 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 349.77 | 0.00 |
November | 10909.58 | 04-NOV-05:02 | 652.28 | 217.40 | 3094.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.79 |
December | 5028.83 | 01-DEC-10:40 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 12.58 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4267.96 | 260.91 | 149.06 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21863.55 | 1295.83 | 670.83 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 384.71 | 18.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15978.89 | 23-JAN-06:01 | 1821.93 | 607.25 | 8642.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.90 |
February | 28719.68 | 05-FEB-14:02 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 247.76 | 0.00 |
March | 27330.92 | 26-MAR-12:32 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 128.33 | 0.00 |
April | 21965.24 | 02-APR-12:43 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 151.49 | 0.00 |
May | 28374.98 | 29-MAY-16:01 | 809.75 | 462.62 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 290.24 | 0.00 |
June | 28677.87 | 04-JUN-15:31 | 809.75 | 462.62 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 325.95 | 0.00 |
July | 28376.88 | 09-JUL-15:31 | 809.75 | 462.62 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 464.42 | 0.00 |
August | 28119.27 | 06-AUG-15:01 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 575.57 | 0.00 |
September | 30414.37 | 03-SEP-13:31 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 462.89 | 0.00 |
October | 30824.58 | 09-OCT-14:01 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 408.34 | 0.00 |
November | 28773.55 | 12-NOV-14:32 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 65.64 | 0.00 |
December | 28701.12 | 03-DEC-13:22 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 19.84 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15978.89 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30824.58 | 1821.93 | 607.25 | 8642.34 | 0.00 | 0.00 | 0.00 | 0.00 | 575.57 | 29.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6945.70 | 30-JAN-06:03 | 521.82 | 173.92 | 2475.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.05 |
February | 15165.36 | 05-FEB-15:22 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 211.84 | 0.00 |
March | 17680.28 | 27-MAR-04:12 | 0.00 | 260.89 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.39 |
April | 19648.45 | 23-APR-16:22 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 170.27 | 0.00 |
May | 26303.52 | 29-MAY-16:01 | 521.82 | 298.13 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 160.94 | 0.00 |
June | 26384.45 | 04-JUN-16:11 | 521.82 | 298.13 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 181.49 | 0.00 |
July | 25821.28 | 09-JUL-15:31 | 521.82 | 298.13 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 274.04 | 0.00 |
August | 25013.47 | 06-AUG-16:21 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 315.06 | 0.00 |
September | 26141.14 | 03-SEP-15:31 | 521.82 | 298.13 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 356.22 | 0.00 |
October | 25558.93 | 09-OCT-15:21 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 325.37 | 0.00 |
November | 17164.84 | 12-NOV-14:32 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 70.65 | 0.00 |
December | 7196.89 | 06-DEC-15:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 22.99 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6945.70 | 0.00 | 173.92 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26384.45 | 1239.33 | 670.83 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 356.22 | 18.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9487.73 | 30-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.49 |
February | 12721.45 | 09-FEB-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.74 |
March | 13324.74 | 29-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.47 |
April | 15967.09 | 29-APR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
May | 22488.87 | 30-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.93 | 0.00 |
June | 22105.70 | 12-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.90 | 0.00 |
July | 25429.92 | 24-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.58 | 0.00 |
August | 27701.54 | 07-AUG-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.99 | 0.00 |
September | 25228.97 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.57 | 0.00 |
October | 21939.90 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.49 | 0.00 |
November | 17552.98 | 06-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.69 |
December | 12754.63 | 11-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9487.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27701.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.99 | 30.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4597.96 | 27-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.46 |
February | 6670.45 | 07-FEB-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.26 | 0.00 |
March | 9950.33 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.31 | 0.00 |
April | 11166.37 | 24-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.14 |
May | 13317.18 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.56 |
June | 13956.33 | 05-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.65 | 0.00 |
July | 16319.38 | 05-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.58 | 0.00 |
August | 17548.95 | 08-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.63 | 0.00 |
September | 15586.46 | 01-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.61 | 0.00 |
October | 12105.21 | 24-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.81 |
November | 11009.23 | 02-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.76 |
December | 6705.64 | 01-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4597.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17548.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.31 | 59.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8838.10 | 23-JAN-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.44 | 0.00 |
February | 14042.83 | 06-FEB-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.92 | 0.00 |
March | 19720.83 | 27-MAR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.31 | 0.00 |
April | 21938.66 | 28-APR-12:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.13 | 0.00 |
May | 24817.41 | 10-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.20 | 0.00 |
June | 25532.34 | 09-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.65 | 0.00 |
July | 27993.50 | 21-JUL-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.71 | 0.00 |
August | 28195.60 | 16-AUG-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.12 | 0.00 |
September | 25231.92 | 05-SEP-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.59 | 0.00 |
October | 20511.21 | 05-OCT-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.80 | 0.00 |
November | 16492.73 | 01-NOV-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.62 | 0.00 |
December | 11296.16 | 04-DEC-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8838.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.81 | 0.00 | |
Maximum of Months | 28195.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.65 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1937.05 | 31-JAN-17:00 | 222.14 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3881.52 | 07-FEB-17:00 | 222.14 | 450.11 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7241.81 | 31-MAR-24:00 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7898.90 | 30-APR-18:52 | 0.00 | 125.04 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3706.10 | 31-MAY-23:55 | 0.00 | 50.02 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5548.03 | 30-JUN-24:00 | 0.00 | 75.02 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7463.59 | 31-JUL-24:00 | 0.00 | 75.02 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7823.83 | 14-AUG-03:20 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3658.56 | 30-SEP-23:57 | 0.00 | 75.02 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5519.01 | 31-OCT-23:53 | 0.00 | 75.02 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5994.88 | 12-NOV-17:00 | 23.38 | 50.02 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7712.42 | 12-DEC-17:00 | 222.14 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1937.05 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7898.90 | 222.14 | 450.11 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1771.46 | 31-JAN-17:00 | 222.14 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3643.20 | 07-FEB-17:00 | 222.14 | 450.11 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6951.23 | 31-MAR-24:00 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7358.93 | 30-APR-18:00 | 0.00 | 50.02 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3449.21 | 31-MAY-23:42 | 0.00 | 100.03 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5222.10 | 30-JUN-24:00 | 0.00 | 75.02 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7043.65 | 31-JUL-24:00 | 0.00 | 75.02 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7235.23 | 07-AUG-02:23 | 0.00 | 100.03 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3386.45 | 30-SEP-23:53 | 0.00 | 75.02 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5238.55 | 31-OCT-23:53 | 0.00 | 75.02 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5529.00 | 06-NOV-17:00 | 222.14 | 450.11 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7269.73 | 06-DEC-17:00 | 222.14 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1771.46 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7358.93 | 222.14 | 450.11 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1796.94 | 31-JAN-17:00 | 222.14 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3685.81 | 06-FEB-16:00 | 222.14 | 450.11 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6892.97 | 31-MAR-24:00 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7540.61 | 23-APR-17:24 | 0.00 | 125.04 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3497.38 | 31-MAY-23:42 | 0.00 | 100.03 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5238.09 | 30-JUN-24:00 | 0.00 | 75.02 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7096.89 | 31-JUL-24:00 | 0.00 | 75.02 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7337.26 | 07-AUG-03:01 | 0.00 | 175.05 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3420.53 | 30-SEP-23:47 | 0.00 | 75.02 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5236.06 | 31-OCT-23:53 | 0.00 | 75.02 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5597.75 | 05-NOV-17:05 | 0.00 | 100.03 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7294.71 | 06-DEC-17:00 | 222.14 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1796.94 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7540.61 | 222.14 | 450.11 | 54560.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 94457.31 | 30-JAN-17:00 | 4808.68 | 5470.56 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 186422.83 | 09-FEB-16:12 | 28852.07 | 32823.35 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 360106.34 | 31-MAR-24:00 | 0.00 | 303.90 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 370099.51 | 28-APR-16:00 | 4808.68 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 178349.11 | 31-MAY-23:55 | 0.00 | 607.79 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 270150.89 | 30-JUN-24:00 | 0.00 | 911.69 | 854173.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 362925.25 | 31-JUL-23:57 | 0.00 | 911.69 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 375618.82 | 10-AUG-21:01 | 2024.71 | 4862.90 | 3037060.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 179235.03 | 30-SEP-23:57 | 0.00 | 911.69 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 271773.20 | 31-OCT-23:53 | 0.00 | 911.69 | 854173.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 280125.22 | 03-NOV-16:00 | 4808.68 | 5470.56 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 370983.24 | 12-DEC-17:00 | 4808.68 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 94457.31 | 0.00 | 303.90 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 375618.82 | 28852.07 | 32823.35 | 3037060.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [] | NATURALGAS:FACILITY [] | |
January | 0.186643E+13 | 1393938.82 | 24-JAN-16:10 | 0.00 | 0.00 |
February | 0.211102E+13 | 1689505.82 | 07-FEB-15:00 | 0.00 | 0.00 |
March | 0.288112E+13 | 1920051.09 | 27-MAR-14:30 | 0.00 | 0.00 |
April | 0.326431E+13 | 2108363.42 | 28-APR-15:09 | 0.00 | 0.00 |
May | 0.237468E+13 | 1749954.10 | 31-MAY-15:00 | 0.00 | 0.00 |
June | 0.291178E+13 | 1934769.74 | 22-JUN-14:09 | 0.00 | 0.00 |
July | 0.350070E+13 | 2202922.75 | 19-JUL-15:09 | 0.00 | 0.00 |
August | 0.408983E+13 | 2414001.39 | 10-AUG-15:00 | 0.00 | 0.00 |
September | 0.246502E+13 | 1826069.18 | 07-SEP-15:30 | 0.00 | 0.00 |
October | 0.276252E+13 | 1868173.48 | 06-OCT-15:50 | 0.00 | 0.00 |
November | 0.288197E+13 | 1963950.62 | 01-NOV-15:20 | 0.00 | 0.00 |
December | 0.315139E+13 | 2000311.45 | 06-DEC-16:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.342608E+14 | 0.00 | 0.00 | ||
Minimum of Months | 0.186643E+13 | 1393938.82 | 0.00 | 0.00 | |
Maximum of Months | 0.408983E+13 | 2414001.39 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.270514E+12 | 0.353743E+11 | 0.766053E+12 | 0.213343E+12 | 0.197455E+12 | 0.522820E+11 | 0.108380E+09 | 0.194129E+12 | 0.106015E+12 | 0.279697E+10 | 0.00 | 0.283619E+11 | 0.00 |
February | 0.244198E+12 | 0.297811E+11 | 0.978954E+12 | 0.195333E+12 | 0.185889E+12 | 0.493611E+11 | 7318508.18 | 0.280670E+12 | 0.118838E+12 | 0.291652E+10 | 0.00 | 0.250730E+11 | 0.00 |
March | 0.289926E+12 | 0.301448E+11 | 0.141687E+13 | 0.226059E+12 | 0.223491E+12 | 0.644489E+11 | 0.00 | 0.453590E+12 | 0.146845E+12 | 0.227849E+10 | 0.00 | 0.274684E+11 | 0.00 |
April | 0.257155E+12 | 0.262757E+11 | 0.165903E+13 | 0.211502E+12 | 0.230196E+12 | 0.746312E+11 | 0.00 | 0.618736E+12 | 0.163986E+12 | 0.293496E+09 | 0.00 | 0.225102E+11 | 0.00 |
May | 0.276731E+12 | 0.247812E+11 | 0.774844E+12 | 0.219700E+12 | 0.275141E+12 | 0.913419E+11 | 0.00 | 0.483360E+12 | 0.207274E+12 | 5755347.06 | 0.00 | 0.215005E+11 | 0.00 |
June | 0.275241E+12 | 0.230488E+11 | 0.106252E+13 | 0.217935E+12 | 0.283739E+12 | 0.102341E+12 | 0.00 | 0.695850E+12 | 0.231621E+12 | 0.00 | 0.00 | 0.194822E+11 | 0.00 |
July | 0.257497E+12 | 0.242828E+11 | 0.139340E+13 | 0.213266E+12 | 0.297930E+12 | 0.111133E+12 | 0.00 | 0.941371E+12 | 0.243807E+12 | 0.00 | 0.00 | 0.180058E+11 | 0.00 |
August | 0.287943E+12 | 0.262287E+11 | 0.173200E+13 | 0.226058E+12 | 0.322235E+12 | 0.116166E+12 | 0.00 | 0.110826E+13 | 0.250421E+12 | 0.00 | 0.00 | 0.205203E+11 | 0.00 |
September | 0.257340E+12 | 0.277324E+11 | 0.740713E+12 | 0.211501E+12 | 0.273187E+12 | 0.102081E+12 | 0.00 | 0.598140E+12 | 0.233806E+12 | 0.00 | 0.00 | 0.205162E+11 | 0.00 |
October | 0.268379E+12 | 0.316237E+11 | 0.108340E+13 | 0.213342E+12 | 0.260610E+12 | 0.911003E+11 | 0.00 | 0.577795E+12 | 0.212544E+12 | 75867837.02 | 0.00 | 0.236539E+11 | 0.00 |
November | 0.266909E+12 | 0.334772E+11 | 0.135889E+13 | 0.205296E+12 | 0.230984E+12 | 0.724547E+11 | 0.00 | 0.521135E+12 | 0.166859E+12 | 0.361504E+09 | 0.00 | 0.256044E+11 | 0.00 |
December | 0.262082E+12 | 0.362323E+11 | 0.170972E+13 | 0.213267E+12 | 0.205493E+12 | 0.604338E+11 | 6518239.39 | 0.487353E+12 | 0.144461E+12 | 0.516486E+10 | 0.00 | 0.271824E+11 | 0.00 |
Annual Sum or Average | 0.321391E+13 | 0.348983E+12 | 0.146764E+14 | 0.256660E+13 | 0.298635E+13 | 0.987775E+12 | 0.122217E+09 | 0.696039E+13 | 0.222648E+13 | 0.138935E+11 | 0.00 | 0.279879E+12 | 0.00 |
Minimum of Months | 0.244198E+12 | 0.230488E+11 | 0.740713E+12 | 0.195333E+12 | 0.185889E+12 | 0.493611E+11 | 0.00 | 0.194129E+12 | 0.106015E+12 | 0.00 | 0.00 | 0.180058E+11 | 0.00 |
Maximum of Months | 0.289926E+12 | 0.362323E+11 | 0.173200E+13 | 0.226059E+12 | 0.322235E+12 | 0.116166E+12 | 0.108380E+09 | 0.110826E+13 | 0.250421E+12 | 0.516486E+10 | 0.00 | 0.283619E+11 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 307068.14 | 09-JAN-08:09 | 40855.88 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 233429.20 | 09-JAN-08:20 | 133092.58 | 23-JAN-13:30 | 30203.28 | 24-JAN-13:20 | 4565.83 | 20-JAN-06:00 |
February | 311655.64 | 09-FEB-16:00 | 40855.88 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 233424.13 | 09-FEB-08:20 | 166500.65 | 06-FEB-15:09 | 56381.08 | 07-FEB-16:49 | 1504.48 | 13-FEB-06:49 |
March | 325713.14 | 14-MAR-07:10 | 40855.88 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 233439.18 | 14-MAR-07:19 | 214061.06 | 27-MAR-15:20 | 60881.18 | 27-MAR-12:30 | 0.00 | 01-MAR-00:10 |
April | 311655.64 | 18-APR-07:10 | 40855.88 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 233431.65 | 18-APR-07:19 | 218724.54 | 28-APR-15:20 | 60585.72 | 24-APR-13:09 | 0.00 | 01-APR-00:10 |
May | 284436.93 | 23-MAY-07:10 | 40855.88 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 233417.11 | 23-MAY-07:19 | 233618.05 | 10-MAY-15:20 | 59352.90 | 11-MAY-09:09 | 0.00 | 01-MAY-00:10 |
June | 284436.93 | 08-JUN-07:10 | 40855.88 | 01-JUN-05:10 | 541788.89 | 01-JUN-07:10 | 233417.11 | 08-JUN-07:19 | 243434.57 | 09-JUN-15:20 | 58015.57 | 22-JUN-13:00 | 0.00 | 01-JUN-00:10 |
July | 297414.32 | 20-JUL-07:10 | 40855.88 | 01-JUL-05:10 | 660080.29 | 03-JUL-07:10 | 233424.04 | 20-JUL-07:19 | 261689.47 | 31-JUL-15:50 | 58919.33 | 19-JUL-14:00 | 0.00 | 01-JUL-00:10 |
August | 286713.14 | 29-AUG-07:10 | 40855.88 | 01-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 233418.33 | 29-AUG-07:19 | 264857.97 | 16-AUG-15:00 | 59271.07 | 10-AUG-15:00 | 0.00 | 01-AUG-00:10 |
September | 289036.26 | 06-SEP-07:10 | 40855.88 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 233419.57 | 06-SEP-07:19 | 259176.72 | 05-SEP-15:50 | 58451.74 | 07-SEP-14:09 | 0.00 | 01-SEP-00:10 |
October | 294586.83 | 24-OCT-07:10 | 40855.88 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 233422.53 | 24-OCT-07:19 | 224539.66 | 05-OCT-15:39 | 59474.29 | 19-OCT-13:30 | 0.00 | 01-OCT-00:10 |
November | 312618.77 | 29-NOV-16:00 | 40855.88 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 233421.88 | 03-NOV-07:19 | 204568.90 | 13-NOV-14:00 | 57284.28 | 13-NOV-14:30 | 0.00 | 01-NOV-00:10 |
December | 320162.50 | 14-DEC-16:00 | 40855.88 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 233433.23 | 15-DEC-08:20 | 164120.91 | 04-DEC-14:09 | 56535.49 | 06-DEC-14:09 | 1358.59 | 18-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 284436.93 | 40855.88 | 423497.50 | 233417.11 | 133092.58 | 30203.28 | 0.00 | |||||||
Maximum of Months | 325713.14 | 40855.88 | 778371.69 | 233439.18 | 264857.97 | 60881.18 | 4565.83 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 212066.06 | 30-JAN-14:09 | 73102.23 | 09-JAN-13:20 | 5457.35 | 01-JAN-05:00 | 0.00 | 37717.36 | 11-JAN-12:39 | 0.00 |
February | 332410.33 | 07-FEB-13:09 | 96956.19 | 07-FEB-10:50 | 6794.96 | 15-FEB-05:00 | 0.00 | 37362.65 | 01-FEB-12:00 | 0.00 |
March | 401702.46 | 01-MAR-13:30 | 96956.19 | 01-MAR-13:50 | 9421.70 | 08-MAR-05:00 | 0.00 | 34904.56 | 01-MAR-12:00 | 0.00 |
April | 483051.79 | 26-APR-12:20 | 96956.19 | 03-APR-07:19 | 5035.74 | 05-APR-04:00 | 0.00 | 31635.57 | 03-APR-11:39 | 0.00 |
May | 410942.23 | 31-MAY-15:00 | 96956.19 | 01-MAY-07:19 | 1439.88 | 07-MAY-10:00 | 0.00 | 28823.27 | 01-MAY-11:00 | 0.00 |
June | 481824.05 | 22-JUN-13:00 | 96956.19 | 01-JUN-07:19 | 0.00 | 01-JUN-00:10 | 0.00 | 26170.55 | 02-JUN-11:39 | 0.00 |
July | 618117.42 | 19-JUL-14:00 | 96956.19 | 01-JUL-01:10 | 0.00 | 01-JUL-00:10 | 0.00 | 24659.80 | 27-JUL-11:50 | 0.00 |
August | 691057.96 | 10-AUG-15:00 | 96956.19 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 26519.22 | 30-AUG-11:39 | 0.00 |
September | 486165.48 | 07-SEP-13:00 | 96956.19 | 01-SEP-00:40 | 0.00 | 01-SEP-00:10 | 0.00 | 29008.33 | 29-SEP-11:20 | 0.00 |
October | 422048.99 | 06-OCT-15:00 | 96956.19 | 01-OCT-00:40 | 4475.77 | 29-OCT-12:00 | 0.00 | 32963.78 | 31-OCT-11:39 | 0.00 |
November | 429093.84 | 01-NOV-13:00 | 96956.19 | 01-NOV-07:19 | 5621.96 | 22-NOV-06:00 | 0.00 | 35632.59 | 30-NOV-12:00 | 0.00 |
December | 399312.57 | 06-DEC-16:10 | 96956.19 | 04-DEC-09:50 | 13559.56 | 18-DEC-05:00 | 0.00 | 37516.80 | 27-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 212066.06 | 73102.23 | 0.00 | 0.00 | 24659.80 | 0.00 | ||||
Maximum of Months | 691057.96 | 96956.19 | 13559.56 | 0.00 | 37717.36 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1393938.82 | 24-JAN-16:10 | 282443.77 | 423497.50 | 0.00 | 233303.25 | 125955.48 | 30147.26 | 0.00 | 196993.32 | 73102.23 |
February | 1689505.82 | 07-FEB-15:00 | 281231.72 | 541788.89 | 0.00 | 233151.79 | 156033.96 | 30821.81 | 0.00 | 327990.88 | 96956.19 |
March | 1920051.09 | 27-MAR-14:30 | 280450.63 | 660080.29 | 0.00 | 233151.79 | 208492.19 | 58254.70 | 0.00 | 363838.12 | 96956.19 |
April | 2108363.42 | 28-APR-15:09 | 280450.63 | 778371.69 | 0.00 | 233302.19 | 217907.71 | 56660.19 | 0.00 | 422992.44 | 96956.19 |
May | 1749954.10 | 31-MAY-15:00 | 280450.63 | 423497.50 | 0.00 | 233302.19 | 227675.79 | 57698.75 | 0.00 | 410942.23 | 96956.19 |
June | 1934769.74 | 22-JUN-14:09 | 280450.63 | 541788.89 | 0.00 | 233151.79 | 231045.21 | 57975.08 | 0.00 | 479467.85 | 96956.19 |
July | 2202922.75 | 19-JUL-15:09 | 280450.63 | 660080.29 | 0.00 | 233302.19 | 239856.29 | 58889.23 | 0.00 | 615755.20 | 96956.19 |
August | 2414001.39 | 10-AUG-15:00 | 280450.63 | 778371.69 | 0.00 | 233302.19 | 255711.24 | 59271.07 | 0.00 | 691057.96 | 96956.19 |
September | 1826069.18 | 07-SEP-15:30 | 280450.63 | 423497.50 | 0.00 | 233302.19 | 232665.12 | 58406.06 | 0.00 | 479921.02 | 96956.19 |
October | 1868173.48 | 06-OCT-15:50 | 280450.63 | 541788.89 | 0.00 | 233302.19 | 214506.45 | 57385.72 | 0.00 | 420600.20 | 96956.19 |
November | 1963950.62 | 01-NOV-15:20 | 280450.63 | 660080.29 | 0.00 | 233302.19 | 196957.74 | 56990.52 | 0.00 | 414109.37 | 96956.19 |
December | 2000311.45 | 06-DEC-16:10 | 283325.86 | 778371.69 | 0.00 | 233303.25 | 151333.00 | 30745.77 | 0.00 | 399312.57 | 96956.19 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1393938.82 | 280450.63 | 423497.50 | 0.00 | 233151.79 | 125955.48 | 30147.26 | 0.00 | 196993.32 | 73102.23 | |
Maximum of Months | 2414001.39 | 283325.86 | 778371.69 | 0.00 | 233303.25 | 255711.24 | 59271.07 | 0.00 | 691057.96 | 96956.19 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 76.83 | 27.76 | 38.17 | 27.85 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 190.67 | 28.39 | 120.83 | 28.47 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 327.00 | 28.20 | 226.17 | 28.24 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 502.83 | 28.77 | 336.00 | 28.81 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 726.83 | 30.11 | 494.83 | 30.14 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 713.67 | 30.35 | 489.67 | 30.39 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 30.95 | 497.00 | 31.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 31.43 | 514.00 | 31.47 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 720.00 | 31.11 | 485.00 | 31.16 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 737.50 | 30.97 | 495.50 | 31.02 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 527.00 | 29.05 | 332.17 | 29.07 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 213.17 | 28.06 | 139.67 | 28.10 |
Annual Sum or Average | 0.00 | 0.00 | 6223.50 | 30.16 | 4169.00 | 30.21 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 76.83 | 27.76 | 38.17 | 27.85 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 31.43 | 514.00 | 31.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.58 | 0.00 | 25.58 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 26.01 | 0.00 | 26.01 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 25.72 | 0.00 | 25.72 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 25.86 | 0.00 | 25.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 25.97 | 0.00 | 25.97 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 26.10 | 0.00 | 26.10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 26.20 | 0.33 | 26.16 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 26.50 | 2.17 | 26.44 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 26.16 | 0.00 | 26.16 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.33 | 26.12 | 0.17 | 26.10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 25.82 | 0.17 | 25.77 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.76 | 0.00 | 25.76 |
Annual Sum or Average | 0.00 | 0.00 | 88.17 | 26.17 | 2.83 | 26.15 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.58 | 0.00 | 25.58 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 26.50 | 2.17 | 26.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 25.57 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.66 | 0.00 | 25.66 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 26.95 | 3.00 | 27.15 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 35.00 | 27.20 | 12.33 | 27.35 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 45.00 | 27.31 | 12.00 | 27.43 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 84.67 | 27.58 | 24.00 | 27.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 81.00 | 27.50 | 23.17 | 27.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 44.00 | 27.32 | 13.17 | 27.45 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 27.07 | 11.33 | 27.23 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 26.28 | 0.83 | 26.51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 331.17 | 27.37 | 99.83 | 27.47 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 84.67 | 27.58 | 24.00 | 27.66 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.26 | 0.33 | 27.26 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.26 | 0.67 | 27.26 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.49 | 0.67 | 27.49 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.48 | 7.00 | 27.58 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 36.00 | 27.41 | 13.67 | 27.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 37.33 | 27.39 | 11.33 | 27.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 75.50 | 27.67 | 22.17 | 27.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 72.83 | 27.59 | 20.50 | 27.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 45.33 | 27.50 | 14.67 | 27.68 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 33.17 | 27.29 | 15.00 | 27.50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 26.97 | 2.50 | 27.16 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 314.50 | 27.51 | 108.50 | 27.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 75.50 | 27.67 | 22.17 | 27.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.41 | 2.17 | 27.41 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.52 | 4.00 | 27.56 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.41 | 3.17 | 27.53 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.24 | 7.50 | 27.39 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 27.33 | 27.09 | 10.17 | 27.28 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 29.33 | 27.13 | 9.33 | 27.29 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 68.00 | 27.51 | 20.17 | 27.60 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 74.67 | 27.50 | 21.00 | 27.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 45.83 | 27.42 | 14.00 | 27.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 38.50 | 27.42 | 14.17 | 27.65 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 27.59 | 11.67 | 27.75 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.68 | 7.00 | 27.68 |
Annual Sum or Average | 0.00 | 0.00 | 327.67 | 27.41 | 124.33 | 27.55 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.09 | 2.17 | 27.28 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 74.67 | 27.68 | 21.00 | 27.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.23 | 2.50 | 27.39 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 13.67 | 27.19 | 5.83 | 27.36 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 33.50 | 27.55 | 11.67 | 27.69 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 33.33 | 27.38 | 10.33 | 27.56 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 50.67 | 27.53 | 14.17 | 27.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 88.00 | 27.93 | 26.67 | 28.01 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 82.00 | 28.04 | 24.17 | 28.11 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 38.17 | 27.45 | 11.83 | 27.62 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 33.00 | 27.33 | 11.33 | 27.54 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 27.27 | 9.00 | 27.47 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 27.16 | 8.67 | 27.33 |
Annual Sum or Average | 0.00 | 0.00 | 410.83 | 27.64 | 136.17 | 27.76 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 88.00 | 28.04 | 26.67 | 28.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.36 | 1.00 | 27.36 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 15.50 | 27.16 | 8.50 | 27.32 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 26.99 | 8.50 | 27.19 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 40.83 | 27.22 | 13.83 | 27.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 29.50 | 27.06 | 9.00 | 27.23 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 27.08 | 8.33 | 27.26 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.23 | 3.83 | 27.32 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 128.83 | 27.12 | 53.00 | 27.29 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 40.83 | 27.36 | 13.83 | 27.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.42 | 1.67 | 27.42 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.68 | 7.67 | 27.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 27.60 | 11.83 | 27.78 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 27.39 | 9.50 | 27.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 38.50 | 27.44 | 15.33 | 27.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 30.00 | 27.25 | 10.00 | 27.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 27.53 | 11.83 | 27.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 27.68 | 12.00 | 27.70 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.32 | 0.50 | 27.32 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 148.33 | 27.46 | 80.33 | 27.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 38.50 | 27.68 | 15.33 | 27.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.42 | 1.50 | 27.42 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.73 | 2.50 | 27.73 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.54 | 2.00 | 27.62 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.53 | 4.67 | 27.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.19 | 7.83 | 27.36 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.00 | 6.50 | 27.21 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 32.50 | 27.15 | 12.33 | 27.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 30.00 | 27.12 | 9.17 | 27.31 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 25.17 | 27.24 | 10.17 | 27.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 27.53 | 11.67 | 27.76 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.84 | 11.17 | 27.86 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.68 | 4.67 | 27.68 |
Annual Sum or Average | 0.00 | 0.00 | 163.83 | 27.29 | 84.17 | 27.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.00 | 1.50 | 27.21 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 32.50 | 27.84 | 12.33 | 27.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.32 | 0.50 | 27.32 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.65 | 0.83 | 27.79 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.75 | 4.67 | 27.82 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 21.67 | 27.51 | 8.50 | 27.69 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 28.17 | 27.27 | 8.00 | 27.46 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 48.33 | 27.51 | 14.17 | 27.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 42.17 | 27.43 | 11.00 | 27.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 25.33 | 27.37 | 9.00 | 27.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 27.60 | 6.67 | 27.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.65 | 3.00 | 27.65 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 189.83 | 27.46 | 66.33 | 27.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 48.33 | 27.75 | 14.17 | 27.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.39 | 2.00 | 27.39 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 27.39 | 8.83 | 27.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 | 27.24 | 8.67 | 27.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 45.00 | 27.38 | 14.17 | 27.54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 34.17 | 27.23 | 10.00 | 27.40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 | 27.35 | 8.83 | 27.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.48 | 5.17 | 27.53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 145.50 | 27.32 | 57.67 | 27.48 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 45.00 | 27.48 | 14.17 | 27.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.53 | 1.83 | 27.53 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.67 | 9.67 | 27.68 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 27.72 | 12.00 | 27.91 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 27.55 | 9.83 | 27.77 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 45.17 | 27.59 | 15.83 | 27.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 34.83 | 27.42 | 10.67 | 27.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 | 27.67 | 11.67 | 27.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 27.75 | 12.50 | 27.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.37 | 1.33 | 27.37 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 173.00 | 27.59 | 85.33 | 27.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 45.17 | 27.75 | 15.83 | 27.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.34 | 0.83 | 27.34 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.76 | 2.33 | 27.76 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.78 | 1.83 | 27.79 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.61 | 6.00 | 27.62 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 27.39 | 8.33 | 27.55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 15.67 | 27.28 | 7.50 | 27.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 40.17 | 27.36 | 13.17 | 27.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 34.67 | 27.29 | 10.00 | 27.47 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 | 27.46 | 10.17 | 27.68 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 27.78 | 11.67 | 27.97 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 27.93 | 10.50 | 27.93 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.74 | 3.00 | 27.74 |
Annual Sum or Average | 0.00 | 0.00 | 177.50 | 27.46 | 85.33 | 27.64 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.28 | 0.83 | 27.34 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 40.17 | 27.93 | 13.17 | 27.97 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.48 | 0.33 | 27.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.92 | 1.00 | 27.93 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.86 | 5.17 | 27.93 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 22.50 | 27.71 | 9.17 | 27.87 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 28.33 | 27.42 | 8.00 | 27.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 51.00 | 27.64 | 14.33 | 27.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 44.50 | 27.54 | 11.50 | 27.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 25.17 | 27.62 | 9.33 | 27.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.84 | 7.67 | 27.95 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.70 | 3.50 | 27.71 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 198.00 | 27.62 | 70.00 | 27.78 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 51.00 | 27.92 | 14.33 | 27.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.93 | 10.50 | 27.93 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 473.67 | 28.21 | 339.00 | 28.26 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 484.17 | 28.21 | 349.50 | 28.25 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 473.67 | 28.21 | 339.00 | 28.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 28.04 | 7.17 | 28.04 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 340.00 | 28.24 | 306.17 | 28.26 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 347.17 | 28.23 | 313.33 | 28.25 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 340.00 | 28.24 | 306.17 | 28.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 28.00 | 8.00 | 28.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 349.17 | 28.32 | 303.00 | 28.34 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 357.17 | 28.31 | 311.00 | 28.33 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 349.17 | 28.32 | 303.00 | 28.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.97 | 1.83 | 27.97 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 67.67 | 27.95 | 67.67 | 27.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 69.50 | 27.95 | 69.50 | 27.95 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 67.67 | 27.97 | 67.67 | 27.97 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 32.33 | 28.21 | 461.83 | 25.10 | 32.33 | 25.29 |
February | 141.83 | 28.09 | 447.17 | 26.24 | 141.83 | 26.60 |
March | 212.83 | 28.44 | 506.83 | 26.92 | 212.83 | 27.26 |
April | 335.33 | 28.89 | 480.50 | 28.13 | 335.33 | 28.35 |
May | 490.83 | 30.23 | 508.00 | 30.14 | 490.83 | 30.17 |
June | 484.50 | 30.50 | 496.00 | 30.43 | 484.50 | 30.46 |
July | 497.00 | 31.06 | 497.00 | 31.06 | 497.00 | 31.06 |
August | 514.00 | 31.53 | 514.00 | 31.53 | 514.00 | 31.53 |
September | 485.00 | 31.22 | 485.00 | 31.22 | 485.00 | 31.22 |
October | 492.67 | 31.13 | 502.00 | 31.07 | 492.67 | 31.09 |
November | 314.83 | 29.33 | 488.17 | 28.28 | 314.83 | 28.57 |
December | 146.00 | 27.89 | 487.83 | 26.08 | 146.00 | 26.42 |
Annual Sum or Average | 4147.17 | 30.31 | 5874.33 | 29.32 | 4147.17 | 29.61 |
Minimum of Months | 32.33 | 27.89 | 447.17 | 25.10 | 32.33 | 25.29 |
Maximum of Months | 514.00 | 31.53 | 514.00 | 31.53 | 514.00 | 31.53 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 23.65 | 444.67 | 24.42 | 0.00 | 24.42 |
February | 1.67 | 27.12 | 444.33 | 24.42 | 1.67 | 24.43 |
March | 0.00 | 0.00 | 502.83 | 24.31 | 0.00 | 24.31 |
April | 0.67 | 26.63 | 479.33 | 24.31 | 0.67 | 24.31 |
May | 1.50 | 26.74 | 507.50 | 24.41 | 1.50 | 24.41 |
June | 4.17 | 26.63 | 496.00 | 24.38 | 4.17 | 24.40 |
July | 40.67 | 26.55 | 497.00 | 24.68 | 40.67 | 24.81 |
August | 47.83 | 26.54 | 514.00 | 24.62 | 47.83 | 24.77 |
September | 20.33 | 26.61 | 485.00 | 24.54 | 20.33 | 24.62 |
October | 20.00 | 26.61 | 497.67 | 24.59 | 20.00 | 24.66 |
November | 1.33 | 27.05 | 485.83 | 24.43 | 1.33 | 24.44 |
December | 0.83 | 27.13 | 483.50 | 24.40 | 0.83 | 24.40 |
Annual Sum or Average | 139.83 | 26.57 | 5837.67 | 24.46 | 139.00 | 24.51 |
Minimum of Months | 0.00 | 0.00 | 444.33 | 24.31 | 0.00 | 24.31 |
Maximum of Months | 47.83 | 27.13 | 514.00 | 24.68 | 47.83 | 24.81 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 42.17 | 23.42 | 317.83 | 24.16 | 0.00 | 24.16 |
February | 14.17 | 23.41 | 371.00 | 24.23 | 0.00 | 24.23 |
March | 3.83 | 23.48 | 424.50 | 24.27 | 0.00 | 24.27 |
April | 4.50 | 23.70 | 436.67 | 24.22 | 0.00 | 24.22 |
May | 0.00 | 0.00 | 479.67 | 24.13 | 0.00 | 24.13 |
June | 0.00 | 0.00 | 496.00 | 24.09 | 0.00 | 24.09 |
July | 0.00 | 0.00 | 495.00 | 24.08 | 0.00 | 24.08 |
August | 0.00 | 0.00 | 514.00 | 24.06 | 0.00 | 24.06 |
September | 0.00 | 0.00 | 485.00 | 24.11 | 0.00 | 24.11 |
October | 0.00 | 0.00 | 485.83 | 24.22 | 0.00 | 24.22 |
November | 2.50 | 23.73 | 478.33 | 24.27 | 0.00 | 24.27 |
December | 15.83 | 23.38 | 413.83 | 24.20 | 0.00 | 24.20 |
Annual Sum or Average | 83.00 | 23.44 | 5397.67 | 24.17 | 0.00 | 24.17 |
Minimum of Months | 0.00 | 0.00 | 317.83 | 24.06 | 0.00 | 24.06 |
Maximum of Months | 42.17 | 23.73 | 514.00 | 24.27 | 0.00 | 24.27 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 172.33 | 23.21 | 227.67 | 23.70 | 13.33 | 23.70 |
February | 81.17 | 23.19 | 299.50 | 23.97 | 0.00 | 23.97 |
March | 27.83 | 23.29 | 391.17 | 24.16 | 0.00 | 24.16 |
April | 0.00 | 0.00 | 432.83 | 24.25 | 0.00 | 24.25 |
May | 0.00 | 0.00 | 487.00 | 24.19 | 0.00 | 24.19 |
June | 0.00 | 0.00 | 496.00 | 24.15 | 0.00 | 24.15 |
July | 0.00 | 0.00 | 496.50 | 24.19 | 0.00 | 24.19 |
August | 0.00 | 0.00 | 514.00 | 24.14 | 0.00 | 24.14 |
September | 0.00 | 0.00 | 485.00 | 24.19 | 0.00 | 24.19 |
October | 0.00 | 0.00 | 489.00 | 24.26 | 0.00 | 24.26 |
November | 0.83 | 23.66 | 471.17 | 24.23 | 0.00 | 24.23 |
December | 90.00 | 23.17 | 329.50 | 23.93 | 0.00 | 23.93 |
Annual Sum or Average | 372.17 | 23.20 | 5119.33 | 24.12 | 13.33 | 24.12 |
Minimum of Months | 0.00 | 0.00 | 227.67 | 23.70 | 0.00 | 23.70 |
Maximum of Months | 172.33 | 23.66 | 514.00 | 24.26 | 13.33 | 24.26 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 92.67 | 23.26 | 272.83 | 23.99 | 0.00 | 23.99 |
February | 26.50 | 23.23 | 377.33 | 24.23 | 0.00 | 24.23 |
March | 5.67 | 23.40 | 463.50 | 24.28 | 0.00 | 24.28 |
April | 18.00 | 26.77 | 477.83 | 24.50 | 18.00 | 24.58 |
May | 68.83 | 26.85 | 508.00 | 24.84 | 68.83 | 25.06 |
June | 79.50 | 26.82 | 496.00 | 24.86 | 79.50 | 25.10 |
July | 111.17 | 26.94 | 497.00 | 25.12 | 111.17 | 25.40 |
August | 93.00 | 26.94 | 514.00 | 24.95 | 93.00 | 25.21 |
September | 79.33 | 26.84 | 485.00 | 24.92 | 79.33 | 25.16 |
October | 60.00 | 26.80 | 502.00 | 24.83 | 60.00 | 25.02 |
November | 6.50 | 26.80 | 486.83 | 24.46 | 6.50 | 24.49 |
December | 12.00 | 23.40 | 427.83 | 24.25 | 0.00 | 24.25 |
Annual Sum or Average | 653.17 | 26.12 | 5508.17 | 24.65 | 516.33 | 24.83 |
Minimum of Months | 5.67 | 23.23 | 272.83 | 23.99 | 0.00 | 23.99 |
Maximum of Months | 111.17 | 26.94 | 514.00 | 25.12 | 111.17 | 25.40 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 90.50 | 23.10 | 306.00 | 24.03 | 0.33 | 24.04 |
February | 29.50 | 23.16 | 372.50 | 24.24 | 1.33 | 24.25 |
March | 20.50 | 24.00 | 457.00 | 24.27 | 4.67 | 24.29 |
April | 39.83 | 26.59 | 473.00 | 24.59 | 38.00 | 24.74 |
May | 73.50 | 26.92 | 508.00 | 24.88 | 73.50 | 25.11 |
June | 72.50 | 26.84 | 496.00 | 24.83 | 72.50 | 25.05 |
July | 108.83 | 26.95 | 497.00 | 25.11 | 108.83 | 25.39 |
August | 91.83 | 26.93 | 514.00 | 24.94 | 91.83 | 25.20 |
September | 85.50 | 26.89 | 485.00 | 24.96 | 85.50 | 25.21 |
October | 68.50 | 26.87 | 502.00 | 24.88 | 68.50 | 25.09 |
November | 18.83 | 26.70 | 485.00 | 24.52 | 18.83 | 24.60 |
December | 37.50 | 23.09 | 402.33 | 24.11 | 0.00 | 24.11 |
Annual Sum or Average | 737.33 | 25.99 | 5497.83 | 24.66 | 563.83 | 24.85 |
Minimum of Months | 18.83 | 23.09 | 306.00 | 24.03 | 0.00 | 24.04 |
Maximum of Months | 108.83 | 26.95 | 514.00 | 25.11 | 108.83 | 25.39 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 62.50 | 23.91 | 382.50 | 24.41 | 13.33 | 24.47 |
February | 41.33 | 24.71 | 407.33 | 24.49 | 17.17 | 24.58 |
March | 25.17 | 25.53 | 472.33 | 24.42 | 15.67 | 24.50 |
April | 31.83 | 26.82 | 477.67 | 24.59 | 31.83 | 24.72 |
May | 53.50 | 26.83 | 508.00 | 24.76 | 53.50 | 24.94 |
June | 57.00 | 26.78 | 496.00 | 24.74 | 57.00 | 24.93 |
July | 105.67 | 26.87 | 497.00 | 25.07 | 105.67 | 25.34 |
August | 92.00 | 26.91 | 514.00 | 24.94 | 92.00 | 25.20 |
September | 87.83 | 26.88 | 485.00 | 24.97 | 87.83 | 25.22 |
October | 84.17 | 26.95 | 502.00 | 24.99 | 84.17 | 25.23 |
November | 55.50 | 26.94 | 488.83 | 24.82 | 55.50 | 25.01 |
December | 41.83 | 26.03 | 462.00 | 24.61 | 32.00 | 24.74 |
Annual Sum or Average | 738.33 | 26.41 | 5692.67 | 24.75 | 645.67 | 24.95 |
Minimum of Months | 25.17 | 23.91 | 382.50 | 24.41 | 13.33 | 24.47 |
Maximum of Months | 105.67 | 26.95 | 514.00 | 25.07 | 105.67 | 25.34 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 46.83 | 23.34 | 392.50 | 24.32 | 2.83 | 24.34 |
February | 17.67 | 26.84 | 436.50 | 24.61 | 17.50 | 24.69 |
March | 29.33 | 26.95 | 510.33 | 24.62 | 29.33 | 24.74 |
April | 76.33 | 26.82 | 485.00 | 24.89 | 76.33 | 25.12 |
May | 64.33 | 26.83 | 508.00 | 24.80 | 64.33 | 25.00 |
June | 89.00 | 26.74 | 496.00 | 24.87 | 89.00 | 25.12 |
July | 118.50 | 26.95 | 497.00 | 25.16 | 118.50 | 25.45 |
August | 101.17 | 27.01 | 514.00 | 25.02 | 101.17 | 25.30 |
September | 73.83 | 26.79 | 485.00 | 24.86 | 73.83 | 25.08 |
October | 71.83 | 26.83 | 502.00 | 24.87 | 71.83 | 25.09 |
November | 57.33 | 26.85 | 489.00 | 24.83 | 57.33 | 25.02 |
December | 47.00 | 26.84 | 495.83 | 24.79 | 47.00 | 24.96 |
Annual Sum or Average | 793.17 | 26.65 | 5811.17 | 24.82 | 749.00 | 25.03 |
Minimum of Months | 17.67 | 23.34 | 392.50 | 24.32 | 2.83 | 24.34 |
Maximum of Months | 118.50 | 27.01 | 514.00 | 25.16 | 118.50 | 25.45 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 301.33 | 22.92 | 115.67 | 23.22 | 0.00 | 23.22 |
February | 143.00 | 22.98 | 212.83 | 23.67 | 0.00 | 23.67 |
March | 65.83 | 23.13 | 360.67 | 24.07 | 0.00 | 24.07 |
April | 14.83 | 24.95 | 451.17 | 24.42 | 9.17 | 24.45 |
May | 37.00 | 26.86 | 506.83 | 24.67 | 37.00 | 24.81 |
June | 42.83 | 26.83 | 496.00 | 24.67 | 42.83 | 24.83 |
July | 74.67 | 26.85 | 497.00 | 24.92 | 74.67 | 25.15 |
August | 54.17 | 26.80 | 514.00 | 24.71 | 54.17 | 24.89 |
September | 47.67 | 26.69 | 485.00 | 24.71 | 47.67 | 24.87 |
October | 28.33 | 26.55 | 495.83 | 24.61 | 28.33 | 24.71 |
November | 5.83 | 23.12 | 459.50 | 24.29 | 0.00 | 24.29 |
December | 163.33 | 23.00 | 252.83 | 23.67 | 0.00 | 23.67 |
Annual Sum or Average | 978.83 | 24.11 | 4847.33 | 24.37 | 293.83 | 24.48 |
Minimum of Months | 5.83 | 22.92 | 115.67 | 23.22 | 0.00 | 23.22 |
Maximum of Months | 301.33 | 26.86 | 514.00 | 24.92 | 74.67 | 25.15 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 194.33 | 22.81 | 128.00 | 23.37 | 0.00 | 23.37 |
February | 95.50 | 22.82 | 222.00 | 23.88 | 0.00 | 23.88 |
March | 58.67 | 23.31 | 321.50 | 24.23 | 5.50 | 24.27 |
April | 51.00 | 26.18 | 386.17 | 24.79 | 43.50 | 24.97 |
May | 53.00 | 26.96 | 429.83 | 24.90 | 53.00 | 25.10 |
June | 46.83 | 26.93 | 418.00 | 24.81 | 46.83 | 25.01 |
July | 74.00 | 26.97 | 422.00 | 25.08 | 74.00 | 25.33 |
August | 56.33 | 26.89 | 433.00 | 24.85 | 56.33 | 25.06 |
September | 54.67 | 26.90 | 410.00 | 24.92 | 54.67 | 25.12 |
October | 56.67 | 26.77 | 425.67 | 24.92 | 56.67 | 25.12 |
November | 13.67 | 25.38 | 397.33 | 24.53 | 8.67 | 24.57 |
December | 116.00 | 22.87 | 233.17 | 23.76 | 0.00 | 23.76 |
Annual Sum or Average | 870.67 | 24.70 | 4226.67 | 24.58 | 399.17 | 24.75 |
Minimum of Months | 13.67 | 22.81 | 128.00 | 23.37 | 0.00 | 23.37 |
Maximum of Months | 194.33 | 26.97 | 433.00 | 25.08 | 74.00 | 25.33 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 106.67 | 23.43 | 336.83 | 24.21 | 12.33 | 24.28 |
February | 66.33 | 23.78 | 370.67 | 24.31 | 15.00 | 24.39 |
March | 45.67 | 23.93 | 428.33 | 24.34 | 10.33 | 24.39 |
April | 30.83 | 26.12 | 457.83 | 24.57 | 26.33 | 24.68 |
May | 34.17 | 26.85 | 506.67 | 24.64 | 34.17 | 24.77 |
June | 32.50 | 26.78 | 496.00 | 24.59 | 32.50 | 24.71 |
July | 62.00 | 26.85 | 497.00 | 24.85 | 62.00 | 25.05 |
August | 54.00 | 26.83 | 514.00 | 24.71 | 54.00 | 24.90 |
September | 59.17 | 26.89 | 485.00 | 24.83 | 59.17 | 25.03 |
October | 66.33 | 26.97 | 502.00 | 24.92 | 66.33 | 25.14 |
November | 51.67 | 26.86 | 484.83 | 24.81 | 50.50 | 24.99 |
December | 71.33 | 24.39 | 415.17 | 24.46 | 25.67 | 24.58 |
Annual Sum or Average | 680.67 | 25.54 | 5494.33 | 24.62 | 448.33 | 24.77 |
Minimum of Months | 30.83 | 23.43 | 336.83 | 24.21 | 10.33 | 24.28 |
Maximum of Months | 106.67 | 26.97 | 514.00 | 24.92 | 66.33 | 25.14 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 223.83 | 22.76 | 185.00 | 23.40 | 0.00 | 23.40 |
February | 98.83 | 22.80 | 292.50 | 23.88 | 1.33 | 23.89 |
March | 51.33 | 23.38 | 415.67 | 24.26 | 5.67 | 24.29 |
April | 32.50 | 26.40 | 465.17 | 24.63 | 29.67 | 24.75 |
May | 54.67 | 26.93 | 508.00 | 24.77 | 54.67 | 24.96 |
June | 62.00 | 26.83 | 496.00 | 24.76 | 62.00 | 24.97 |
July | 92.33 | 26.85 | 497.00 | 24.99 | 92.33 | 25.25 |
August | 80.17 | 26.78 | 514.00 | 24.82 | 80.17 | 25.06 |
September | 65.17 | 26.86 | 485.00 | 24.83 | 65.17 | 25.05 |
October | 45.67 | 26.85 | 499.67 | 24.77 | 45.67 | 24.93 |
November | 20.67 | 25.88 | 473.17 | 24.49 | 15.83 | 24.56 |
December | 106.50 | 22.84 | 320.17 | 23.88 | 0.00 | 23.88 |
Annual Sum or Average | 933.67 | 24.75 | 5151.33 | 24.52 | 452.50 | 24.68 |
Minimum of Months | 20.67 | 22.76 | 185.00 | 23.40 | 0.00 | 23.40 |
Maximum of Months | 223.83 | 26.93 | 514.00 | 24.99 | 92.33 | 25.25 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 359.00 | 22.50 | 88.17 | 22.79 | 0.00 | 22.79 |
February | 207.17 | 22.70 | 176.50 | 23.34 | 0.00 | 23.34 |
March | 112.50 | 22.93 | 327.67 | 23.89 | 0.00 | 23.89 |
April | 34.67 | 24.49 | 429.00 | 24.42 | 18.00 | 24.47 |
May | 41.33 | 26.84 | 506.33 | 24.69 | 41.33 | 24.84 |
June | 43.33 | 26.86 | 496.00 | 24.68 | 43.33 | 24.84 |
July | 80.50 | 26.86 | 497.00 | 24.95 | 80.50 | 25.18 |
August | 58.83 | 26.82 | 514.00 | 24.73 | 58.83 | 24.93 |
September | 51.17 | 26.71 | 485.00 | 24.73 | 51.17 | 24.90 |
October | 36.83 | 26.56 | 492.50 | 24.65 | 36.83 | 24.77 |
November | 25.67 | 23.13 | 424.17 | 24.22 | 0.33 | 24.22 |
December | 229.17 | 22.65 | 195.67 | 23.30 | 1.50 | 23.30 |
Annual Sum or Average | 1280.17 | 23.71 | 4632.00 | 24.27 | 331.83 | 24.40 |
Minimum of Months | 25.67 | 22.50 | 88.17 | 22.79 | 0.00 | 22.79 |
Maximum of Months | 359.00 | 26.86 | 514.00 | 24.95 | 80.50 | 25.18 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 272.17 | 22.63 | 140.17 | 23.13 | 0.00 | 23.13 |
February | 135.00 | 22.62 | 246.33 | 23.66 | 0.00 | 23.66 |
March | 86.83 | 23.17 | 372.83 | 24.09 | 7.33 | 24.14 |
April | 63.83 | 25.82 | 450.50 | 24.68 | 50.50 | 24.85 |
May | 56.33 | 26.95 | 507.67 | 24.79 | 56.33 | 24.98 |
June | 48.67 | 26.96 | 496.00 | 24.71 | 48.67 | 24.90 |
July | 81.67 | 26.97 | 497.00 | 24.98 | 81.67 | 25.23 |
August | 63.00 | 26.91 | 514.00 | 24.77 | 63.00 | 24.98 |
September | 57.67 | 26.93 | 485.00 | 24.81 | 57.67 | 25.02 |
October | 58.33 | 26.80 | 500.33 | 24.81 | 58.33 | 25.00 |
November | 25.50 | 24.68 | 453.33 | 24.42 | 11.83 | 24.48 |
December | 174.67 | 22.71 | 249.33 | 23.54 | 0.83 | 23.54 |
Annual Sum or Average | 1123.67 | 24.31 | 4912.50 | 24.44 | 436.17 | 24.60 |
Minimum of Months | 25.50 | 22.62 | 140.17 | 23.13 | 0.00 | 23.13 |
Maximum of Months | 272.17 | 26.97 | 514.00 | 24.98 | 81.67 | 25.23 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 151.17 | 22.82 | 294.17 | 23.87 | 7.50 | 23.92 |
February | 90.17 | 23.10 | 333.00 | 24.09 | 11.67 | 24.17 |
March | 78.50 | 23.53 | 394.67 | 24.23 | 12.33 | 24.29 |
April | 52.17 | 25.35 | 438.67 | 24.56 | 36.17 | 24.69 |
May | 37.33 | 26.83 | 505.17 | 24.65 | 37.33 | 24.79 |
June | 36.50 | 26.81 | 496.00 | 24.61 | 36.50 | 24.75 |
July | 70.33 | 26.85 | 497.00 | 24.89 | 70.33 | 25.10 |
August | 60.83 | 26.82 | 514.00 | 24.74 | 60.83 | 24.94 |
September | 63.33 | 26.88 | 485.00 | 24.84 | 63.33 | 25.05 |
October | 66.50 | 26.96 | 502.00 | 24.92 | 66.50 | 25.13 |
November | 53.83 | 26.50 | 474.00 | 24.76 | 47.83 | 24.94 |
December | 102.50 | 23.61 | 367.33 | 24.26 | 23.17 | 24.37 |
Annual Sum or Average | 863.17 | 24.96 | 5301.00 | 24.56 | 473.50 | 24.73 |
Minimum of Months | 36.50 | 22.82 | 294.17 | 23.87 | 7.50 | 23.92 |
Maximum of Months | 151.17 | 26.96 | 514.00 | 24.92 | 70.33 | 25.13 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 283.50 | 22.44 | 145.33 | 23.02 | 0.00 | 23.02 |
February | 146.17 | 22.60 | 250.00 | 23.63 | 2.33 | 23.64 |
March | 86.33 | 23.11 | 373.50 | 24.12 | 6.50 | 24.16 |
April | 50.00 | 25.47 | 446.50 | 24.61 | 35.17 | 24.74 |
May | 55.33 | 26.92 | 507.00 | 24.77 | 55.33 | 24.96 |
June | 60.33 | 26.85 | 496.00 | 24.75 | 60.33 | 24.96 |
July | 93.50 | 26.86 | 497.00 | 25.00 | 93.50 | 25.25 |
August | 81.50 | 26.79 | 514.00 | 24.83 | 81.50 | 25.07 |
September | 67.17 | 26.86 | 485.00 | 24.84 | 67.17 | 25.06 |
October | 49.33 | 26.81 | 494.83 | 24.77 | 49.33 | 24.94 |
November | 31.33 | 24.88 | 451.67 | 24.43 | 16.17 | 24.51 |
December | 164.00 | 22.61 | 264.50 | 23.59 | 0.67 | 23.59 |
Annual Sum or Average | 1168.50 | 24.26 | 4925.33 | 24.43 | 468.00 | 24.60 |
Minimum of Months | 31.33 | 22.44 | 145.33 | 23.02 | 0.00 | 23.02 |
Maximum of Months | 283.50 | 26.92 | 514.00 | 25.00 | 93.50 | 25.25 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 1.33 | 27.00 | 454.00 | 27.00 | 1.33 | 27.00 |
March | 55.83 | 27.00 | 514.00 | 27.00 | 55.83 | 27.00 |
April | 264.00 | 27.06 | 485.00 | 27.04 | 264.00 | 27.05 |
May | 103.67 | 27.00 | 508.00 | 27.00 | 103.67 | 27.00 |
June | 302.17 | 27.00 | 496.00 | 27.00 | 302.17 | 27.00 |
July | 477.67 | 27.00 | 497.00 | 27.00 | 477.67 | 27.00 |
August | 514.00 | 27.96 | 514.00 | 27.96 | 514.00 | 27.96 |
September | 228.17 | 27.00 | 485.00 | 27.00 | 228.17 | 27.00 |
October | 207.50 | 27.00 | 502.00 | 27.00 | 207.50 | 27.00 |
November | 154.50 | 27.00 | 489.00 | 27.00 | 154.50 | 27.00 |
December | 121.17 | 27.00 | 497.00 | 27.00 | 121.17 | 27.00 |
Annual Sum or Average | 2430.00 | 27.21 | 5943.00 | 27.12 | 2430.00 | 27.14 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 514.00 | 27.96 | 514.00 | 27.96 | 514.00 | 27.96 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
April | 15.83 | 27.64 | 485.00 | 27.04 | 15.83 | 27.06 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 9.33 | 27.00 | 496.00 | 27.00 | 9.33 | 27.00 |
July | 66.67 | 27.00 | 497.00 | 27.00 | 66.67 | 27.00 |
August | 357.33 | 28.15 | 514.00 | 27.96 | 357.33 | 28.02 |
September | 14.67 | 27.00 | 485.00 | 27.00 | 14.67 | 27.00 |
October | 0.33 | 27.00 | 502.00 | 27.00 | 0.33 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 464.17 | 27.91 | 5943.00 | 27.14 | 464.17 | 27.19 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 357.33 | 28.15 | 514.00 | 27.96 | 357.33 | 28.02 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 0.50 | 27.00 | 514.00 | 27.00 | 0.50 | 27.00 |
April | 36.00 | 27.32 | 485.00 | 27.05 | 36.00 | 27.06 |
May | 30.67 | 27.00 | 508.00 | 27.00 | 30.67 | 27.00 |
June | 84.83 | 27.00 | 496.00 | 27.00 | 84.83 | 27.00 |
July | 166.50 | 27.00 | 497.00 | 27.00 | 166.50 | 27.00 |
August | 363.67 | 28.20 | 514.00 | 28.00 | 363.67 | 28.06 |
September | 78.50 | 27.00 | 485.00 | 27.00 | 78.50 | 27.00 |
October | 17.00 | 27.00 | 502.00 | 27.00 | 17.00 | 27.00 |
November | 1.33 | 27.00 | 489.00 | 27.00 | 1.33 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 779.00 | 27.58 | 5943.00 | 27.14 | 779.00 | 27.18 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 363.67 | 28.20 | 514.00 | 28.00 | 363.67 | 28.06 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.01 | 485.00 | 27.01 | 485.00 | 27.01 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 27.18 | 514.00 | 27.18 | 514.00 | 27.18 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5943.00 | 27.02 | 5943.00 | 27.02 | 5943.00 | 27.02 |
Minimum of Months | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
Maximum of Months | 514.00 | 27.18 | 514.00 | 27.18 | 514.00 | 27.18 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00107 | 31.50246 | 0.89962 | 22.12397 |
February | 454.00000 | 27.00166 | 31.10390 | 0.94545 | 23.90945 |
March | 514.00000 | 27.00089 | 30.94413 | 0.98626 | 25.57065 |
April | 485.00000 | 27.03258 | 31.77716 | 1.04190 | 27.96248 |
May | 508.00000 | 27.00073 | 36.40314 | 0.36736 | 7.87191 |
June | 496.00000 | 27.00247 | 36.66061 | 0.42410 | 8.79605 |
July | 497.00000 | 27.00116 | 36.40337 | 0.48309 | 9.92595 |
August | 514.00000 | 27.96244 | 35.33672 | 0.75707 | 17.85078 |
September | 485.00000 | 27.00025 | 39.95349 | 0.41171 | 8.58891 |
October | 502.00000 | 27.00229 | 34.76898 | 1.03052 | 27.45048 |
November | 489.00000 | 27.00120 | 32.32608 | 1.01643 | 26.84148 |
December | 497.00000 | 27.00042 | 30.43049 | 1.00342 | 26.28754 |
Annual Sum or Average | 5943.00000 | 27.08691 | 33.98073 | 0.77941 | 19.39638 |
Minimum of Months | 454.00000 | 27.00025 | 30.43049 | 0.36736 | 7.87191 |
Maximum of Months | 514.00000 | 27.96244 | 39.95349 | 1.04190 | 27.96248 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00050 | 31.94189 | 0.83547 | 19.78063 |
February | 454.00000 | 27.00156 | 31.26820 | 0.86485 | 20.83321 |
March | 514.00000 | 27.00091 | 30.99234 | 0.90266 | 22.24768 |
April | 485.00000 | 27.02332 | 31.81625 | 0.95086 | 24.14280 |
May | 508.00000 | 27.00051 | 36.76326 | 0.28875 | 6.79145 |
June | 496.00000 | 27.00265 | 36.90633 | 0.32151 | 7.19813 |
July | 497.00000 | 27.00144 | 36.59083 | 0.35224 | 7.62933 |
August | 514.00000 | 27.82762 | 35.53552 | 0.57110 | 12.65449 |
September | 485.00000 | 27.00010 | 40.64194 | 0.32329 | 7.22366 |
October | 502.00000 | 27.00236 | 34.99946 | 0.95244 | 24.18950 |
November | 489.00000 | 27.00129 | 32.41340 | 0.92970 | 23.28732 |
December | 497.00000 | 27.00046 | 30.47113 | 0.88837 | 21.70721 |
Annual Sum or Average | 5943.00000 | 27.07446 | 34.20816 | 0.68030 | 16.43477 |
Minimum of Months | 454.00000 | 27.00010 | 30.47113 | 0.28875 | 6.79145 |
Maximum of Months | 514.00000 | 27.82762 | 40.64194 | 0.95244 | 24.18950 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00042 | 32.22170 | 0.81232 | 19.01927 |
February | 454.00000 | 27.00157 | 31.31571 | 0.84975 | 20.32786 |
March | 514.00000 | 27.00092 | 30.98957 | 0.89651 | 22.05010 |
April | 485.00000 | 27.02550 | 31.80143 | 0.95491 | 24.33839 |
May | 508.00000 | 27.00058 | 36.69013 | 0.30808 | 7.07803 |
June | 496.00000 | 27.00261 | 36.84724 | 0.34328 | 7.54485 |
July | 497.00000 | 27.00140 | 36.54237 | 0.37969 | 8.09148 |
August | 514.00000 | 27.86340 | 35.47872 | 0.60434 | 13.73657 |
September | 485.00000 | 27.00015 | 40.52189 | 0.34193 | 7.52544 |
October | 502.00000 | 27.00235 | 34.97862 | 0.95935 | 24.48737 |
November | 489.00000 | 27.00129 | 32.41178 | 0.92561 | 23.15052 |
December | 497.00000 | 27.00049 | 30.47696 | 0.86898 | 21.02639 |
Annual Sum or Average | 5943.00000 | 27.07773 | 34.20262 | 0.68577 | 16.49799 |
Minimum of Months | 454.00000 | 27.00015 | 30.47696 | 0.30808 | 7.07803 |
Maximum of Months | 514.00000 | 27.86340 | 40.52189 | 0.95935 | 24.48737 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00373 | 30.87350 | 1.12629 | 31.73630 |
February | 454.00000 | 27.00397 | 30.98717 | 1.27359 | 38.92528 |
March | 514.00000 | 27.00236 | 31.33664 | 1.40954 | 46.02470 |
April | 485.00000 | 27.00759 | 32.12037 | 1.54838 | 53.53355 |
May | 508.00000 | 27.00324 | 34.68957 | 0.62308 | 13.18486 |
June | 496.00000 | 27.00365 | 35.34690 | 0.84565 | 20.10706 |
July | 497.00000 | 27.00221 | 35.63905 | 1.06426 | 28.91862 |
August | 514.00000 | 27.18361 | 35.37063 | 1.32328 | 41.54741 |
September | 485.00000 | 27.00389 | 36.65503 | 0.70549 | 15.50727 |
October | 502.00000 | 27.00333 | 33.80735 | 1.36514 | 43.66930 |
November | 489.00000 | 27.00190 | 32.18555 | 1.46528 | 49.02027 |
December | 497.00000 | 27.00253 | 30.92836 | 1.55798 | 54.05612 |
Annual Sum or Average | 5943.00000 | 27.01906 | 33.34320 | 1.19173 | 36.32895 |
Minimum of Months | 454.00000 | 27.00190 | 30.87350 | 0.62308 | 13.18486 |
Maximum of Months | 514.00000 | 27.18361 | 36.65503 | 1.55798 | 54.05612 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.80834 | 49.13774 | 0.64839 | 15.19912 |
February | 454.00000 | 25.63181 | 58.58232 | 0.91593 | 26.22464 |
March | 514.00000 | 26.24509 | 65.05738 | 1.10733 | 35.01296 |
April | 485.00000 | 27.56932 | 74.67724 | 1.49734 | 51.87792 |
May | 508.00000 | 30.04185 | 97.56551 | 1.93498 | 73.97198 |
June | 496.00000 | 30.36714 | 97.61722 | 2.05965 | 78.71868 |
July | 497.00000 | 31.06448 | 99.99872 | 2.33687 | 89.00206 |
August | 514.00000 | 31.53371 | 99.99904 | 2.52168 | 93.63799 |
September | 485.00000 | 31.21826 | 99.99967 | 2.39815 | 90.73403 |
October | 502.00000 | 31.00660 | 94.07206 | 2.56266 | 91.87537 |
November | 489.00000 | 27.59754 | 67.52911 | 1.48552 | 49.95028 |
December | 497.00000 | 25.51104 | 56.41821 | 0.87790 | 24.40774 |
Annual Sum or Average | 5943.00000 | 28.57190 | 80.22672 | 1.70135 | 60.30008 |
Minimum of Months | 454.00000 | 24.80834 | 49.13774 | 0.64839 | 15.19912 |
Maximum of Months | 514.00000 | 31.53371 | 99.99967 | 2.56266 | 93.63799 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.36580 | 50.09189 | 0.55389 | 11.76323 |
February | 454.00000 | 24.40537 | 53.12798 | 0.60421 | 13.05179 |
March | 514.00000 | 24.29889 | 51.00352 | 0.58350 | 12.38601 |
April | 485.00000 | 24.30179 | 52.30809 | 0.61461 | 13.17830 |
May | 508.00000 | 24.40057 | 52.66064 | -0.1516 | 6.18064 |
June | 496.00000 | 24.36051 | 53.91932 | -0.1369 | 6.02601 |
July | 497.00000 | 24.52295 | 52.22758 | -0.0760 | 6.18121 |
August | 514.00000 | 24.44565 | 51.86042 | -0.0790 | 6.11519 |
September | 485.00000 | 24.45816 | 53.45384 | -0.1021 | 6.13299 |
October | 502.00000 | 24.50285 | 52.21384 | 0.70194 | 15.88088 |
November | 489.00000 | 24.42440 | 54.44857 | 0.66157 | 14.50704 |
December | 497.00000 | 24.38428 | 53.53654 | 0.61241 | 13.17435 |
Annual Sum or Average | 5943.00000 | 24.40587 | 52.55425 | 0.31261 | 10.35181 |
Minimum of Months | 454.00000 | 24.29889 | 50.09189 | -0.1516 | 6.02601 |
Maximum of Months | 514.00000 | 24.52295 | 54.44857 | 0.70194 | 15.88088 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.08402 | 51.22586 | 0.46057 | 9.69712 |
February | 454.00000 | 24.16246 | 54.31127 | 0.50842 | 10.64670 |
March | 514.00000 | 24.20302 | 51.89452 | 0.51441 | 10.74659 |
April | 485.00000 | 24.19920 | 53.61619 | 0.53541 | 11.20705 |
May | 508.00000 | 24.11633 | 54.94248 | -0.3421 | 7.58898 |
June | 496.00000 | 24.08633 | 57.11763 | -0.3330 | 7.38735 |
July | 497.00000 | 24.08091 | 56.95853 | -0.3334 | 7.37176 |
August | 514.00000 | 24.06450 | 57.50536 | -0.3282 | 7.29244 |
September | 485.00000 | 24.10716 | 57.42832 | -0.3262 | 7.31688 |
October | 502.00000 | 24.20967 | 55.61466 | 0.55827 | 11.67650 |
November | 489.00000 | 24.26562 | 56.42127 | 0.57052 | 12.00844 |
December | 497.00000 | 24.14145 | 54.99118 | 0.51066 | 10.69220 |
Annual Sum or Average | 5943.00000 | 24.14296 | 55.16566 | 0.16282 | 9.45458 |
Minimum of Months | 454.00000 | 24.06450 | 51.22586 | -0.3421 | 7.29244 |
Maximum of Months | 514.00000 | 24.26562 | 57.50536 | 0.57052 | 12.00844 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.73774 | 54.08784 | 0.38063 | 8.53034 |
February | 454.00000 | 23.94711 | 55.44475 | 0.45560 | 9.69273 |
March | 514.00000 | 24.09801 | 52.51768 | 0.49161 | 10.29826 |
April | 485.00000 | 24.21118 | 53.77951 | 0.54522 | 11.42354 |
May | 508.00000 | 24.18269 | 54.83998 | -0.2980 | 7.07777 |
June | 496.00000 | 24.15116 | 56.98644 | -0.2860 | 6.86407 |
July | 497.00000 | 24.19113 | 56.60319 | -0.2670 | 6.68519 |
August | 514.00000 | 24.14215 | 57.27087 | -0.2733 | 6.68630 |
September | 485.00000 | 24.18689 | 57.29470 | -0.2791 | 6.83274 |
October | 502.00000 | 24.25760 | 55.75863 | 0.57824 | 12.17863 |
November | 489.00000 | 24.21577 | 56.97983 | 0.56024 | 11.72473 |
December | 497.00000 | 23.88706 | 56.23903 | 0.44680 | 9.56597 |
Annual Sum or Average | 5943.00000 | 24.10135 | 55.64309 | 0.16819 | 8.95021 |
Minimum of Months | 454.00000 | 23.73774 | 52.51768 | -0.2980 | 6.68519 |
Maximum of Months | 514.00000 | 24.25760 | 57.29470 | 0.57824 | 12.17863 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.97352 | 50.64446 | 0.42603 | 9.18087 |
February | 454.00000 | 24.19644 | 53.19333 | 0.52686 | 11.14382 |
March | 514.00000 | 24.24647 | 50.57420 | 0.55928 | 11.81836 |
April | 485.00000 | 24.41286 | 51.48041 | 0.65428 | 14.50192 |
May | 508.00000 | 24.57218 | 51.57130 | -0.0169 | 6.59100 |
June | 496.00000 | 24.54341 | 52.84908 | 0.02498 | 6.56021 |
July | 497.00000 | 24.71166 | 51.24449 | 0.10362 | 7.36187 |
August | 514.00000 | 24.58790 | 51.01188 | 0.07647 | 6.91708 |
September | 485.00000 | 24.60587 | 52.58877 | 0.01870 | 6.77381 |
October | 502.00000 | 24.59694 | 51.48869 | 0.74414 | 17.42826 |
November | 489.00000 | 24.42703 | 53.93348 | 0.65426 | 14.36752 |
December | 497.00000 | 24.20987 | 53.66468 | 0.53843 | 11.34441 |
Annual Sum or Average | 5943.00000 | 24.42496 | 51.99968 | 0.35716 | 10.31308 |
Minimum of Months | 454.00000 | 23.97352 | 50.57420 | -0.0169 | 6.56021 |
Maximum of Months | 514.00000 | 24.71166 | 53.93348 | 0.74414 | 17.42826 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.98761 | 50.29686 | 0.45278 | 9.86704 |
February | 454.00000 | 24.16585 | 53.07682 | 0.54287 | 11.67865 |
March | 514.00000 | 24.20296 | 50.54075 | 0.56995 | 12.22939 |
April | 485.00000 | 24.40167 | 51.37650 | 0.68054 | 15.38544 |
May | 508.00000 | 24.58233 | 51.39508 | 0.05298 | 6.84773 |
June | 496.00000 | 24.53128 | 52.77849 | 0.07255 | 6.70249 |
July | 497.00000 | 24.70978 | 51.17225 | 0.15068 | 7.78011 |
August | 514.00000 | 24.58460 | 50.92341 | 0.12720 | 7.16773 |
September | 485.00000 | 24.61662 | 52.41772 | 0.08903 | 7.13966 |
October | 502.00000 | 24.60618 | 51.27665 | 0.78583 | 18.84848 |
November | 489.00000 | 24.42767 | 53.80672 | 0.67891 | 15.15548 |
December | 497.00000 | 24.06857 | 53.99126 | 0.52002 | 11.02834 |
Annual Sum or Average | 5943.00000 | 24.40844 | 51.90041 | 0.39173 | 10.79825 |
Minimum of Months | 454.00000 | 23.98761 | 50.29686 | 0.05298 | 6.70249 |
Maximum of Months | 514.00000 | 24.70978 | 53.99126 | 0.78583 | 18.84848 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.28838 | 49.23574 | 0.55390 | 12.29672 |
February | 454.00000 | 24.36565 | 52.32300 | 0.61952 | 13.74677 |
March | 514.00000 | 24.31682 | 50.16359 | 0.61404 | 13.40653 |
April | 485.00000 | 24.42875 | 51.36852 | 0.67515 | 15.17715 |
May | 508.00000 | 24.53959 | 51.67818 | -0.0352 | 6.45577 |
June | 496.00000 | 24.50024 | 53.01727 | -0.0118 | 6.33487 |
July | 497.00000 | 24.68622 | 51.32878 | 0.07943 | 7.10335 |
August | 514.00000 | 24.58155 | 51.01433 | 0.08175 | 6.88447 |
September | 485.00000 | 24.62279 | 52.45774 | 0.07216 | 7.03061 |
October | 502.00000 | 24.65948 | 51.12312 | 0.81811 | 20.05241 |
November | 489.00000 | 24.57824 | 53.19914 | 0.76220 | 18.01662 |
December | 497.00000 | 24.42039 | 52.65044 | 0.64964 | 14.62809 |
Annual Sum or Average | 5943.00000 | 24.49950 | 51.61318 | 0.40408 | 11.73026 |
Minimum of Months | 454.00000 | 24.28838 | 49.23574 | -0.0352 | 6.33487 |
Maximum of Months | 514.00000 | 24.68622 | 53.19914 | 0.81811 | 20.05241 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.23453 | 49.29361 | 0.54096 | 11.72470 |
February | 454.00000 | 24.48704 | 51.82992 | 0.66627 | 14.95592 |
March | 514.00000 | 24.48132 | 49.46814 | 0.70761 | 16.16693 |
April | 485.00000 | 24.58274 | 50.66409 | 0.79846 | 19.27942 |
May | 508.00000 | 24.53860 | 51.58564 | 0.03605 | 6.66963 |
June | 496.00000 | 24.53905 | 52.77174 | 0.10384 | 6.94973 |
July | 497.00000 | 24.73141 | 51.08627 | 0.20397 | 8.31363 |
August | 514.00000 | 24.62421 | 50.78506 | 0.21264 | 8.11761 |
September | 485.00000 | 24.56515 | 52.64058 | 0.06571 | 6.89402 |
October | 502.00000 | 24.59249 | 51.37463 | 0.79821 | 19.24211 |
November | 489.00000 | 24.58896 | 53.14703 | 0.77611 | 18.38121 |
December | 497.00000 | 24.59930 | 51.94631 | 0.72868 | 16.91949 |
Annual Sum or Average | 5943.00000 | 24.54713 | 51.36724 | 0.46773 | 12.76732 |
Minimum of Months | 454.00000 | 24.23453 | 49.29361 | 0.03605 | 6.66963 |
Maximum of Months | 514.00000 | 24.73141 | 53.14703 | 0.79846 | 19.27942 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.32651 | 52.67590 | 0.25382 | 7.10284 |
February | 454.00000 | 23.69776 | 55.13800 | 0.37994 | 8.61507 |
March | 514.00000 | 24.03812 | 51.60913 | 0.47090 | 10.07227 |
April | 485.00000 | 24.35235 | 52.71794 | 0.59577 | 12.89999 |
May | 508.00000 | 24.51225 | 52.87338 | -0.1060 | 6.55862 |
June | 496.00000 | 24.48502 | 55.23430 | -0.0626 | 6.37230 |
July | 497.00000 | 24.63404 | 54.68782 | 0.00274 | 6.73462 |
August | 514.00000 | 24.48838 | 55.58691 | -0.0362 | 6.34146 |
September | 485.00000 | 24.51737 | 55.79952 | -0.0834 | 6.50103 |
October | 502.00000 | 24.49448 | 54.41062 | 0.66508 | 14.86225 |
November | 489.00000 | 24.26541 | 55.85688 | 0.57237 | 12.12029 |
December | 497.00000 | 23.67801 | 56.07890 | 0.38018 | 8.63869 |
Annual Sum or Average | 5943.00000 | 24.21050 | 54.37335 | 0.25088 | 8.89175 |
Minimum of Months | 454.00000 | 23.32651 | 51.60913 | -0.1060 | 6.34146 |
Maximum of Months | 514.00000 | 24.63404 | 56.07890 | 0.66508 | 14.86225 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 23.49555 | 51.27726 | 0.31192 | 7.92063 |
February | 385.00000 | 23.84226 | 54.11759 | 0.43388 | 9.75669 |
March | 433.00000 | 24.13557 | 50.76041 | 0.51360 | 11.28051 |
April | 410.00000 | 24.54092 | 52.06897 | 0.67082 | 15.38295 |
May | 430.00000 | 24.64029 | 52.48533 | -0.0116 | 6.93405 |
June | 418.00000 | 24.57705 | 54.96298 | 0.00765 | 6.71723 |
July | 422.00000 | 24.74990 | 54.16480 | 0.08103 | 7.46986 |
August | 433.00000 | 24.58664 | 55.19492 | 0.04396 | 6.77212 |
September | 410.00000 | 24.65111 | 55.21704 | 0.00914 | 7.00257 |
October | 427.00000 | 24.67219 | 53.69024 | 0.73694 | 17.33602 |
November | 417.00000 | 24.44704 | 54.90854 | 0.63733 | 14.08827 |
December | 422.00000 | 23.74679 | 55.21707 | 0.41420 | 9.32207 |
Annual Sum or Average | 5034.00000 | 24.34265 | 53.65942 | 0.31944 | 9.98932 |
Minimum of Months | 385.00000 | 23.49555 | 50.76041 | -0.0116 | 6.71723 |
Maximum of Months | 433.00000 | 24.74990 | 55.21707 | 0.73694 | 17.33602 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.11135 | 49.61202 | 0.49609 | 11.32070 |
February | 454.00000 | 24.19221 | 52.97325 | 0.55484 | 12.38777 |
March | 514.00000 | 24.24359 | 50.60782 | 0.56479 | 12.35723 |
April | 485.00000 | 24.42173 | 52.34269 | 0.63502 | 14.10348 |
May | 508.00000 | 24.48883 | 52.92965 | -0.1123 | 6.51816 |
June | 496.00000 | 24.44227 | 55.40964 | -0.0909 | 6.29234 |
July | 497.00000 | 24.60271 | 54.77440 | -0.0116 | 6.61377 |
August | 514.00000 | 24.49172 | 55.49332 | -0.0138 | 6.37381 |
September | 485.00000 | 24.57617 | 55.36028 | -0.0006 | 6.74435 |
October | 502.00000 | 24.65224 | 53.50469 | 0.77559 | 18.63622 |
November | 489.00000 | 24.58195 | 54.35276 | 0.73113 | 17.10458 |
December | 497.00000 | 24.28511 | 53.46816 | 0.58954 | 13.34020 |
Annual Sum or Average | 5943.00000 | 24.42504 | 53.39607 | 0.34053 | 10.95656 |
Minimum of Months | 454.00000 | 24.11135 | 49.61202 | -0.1123 | 6.29234 |
Maximum of Months | 514.00000 | 24.65224 | 55.49332 | 0.77559 | 18.63622 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.45883 | 51.61940 | 0.31939 | 8.12657 |
February | 454.00000 | 23.84688 | 54.12867 | 0.45554 | 10.18205 |
March | 514.00000 | 24.17561 | 50.75640 | 0.55220 | 12.10054 |
April | 485.00000 | 24.46712 | 52.04068 | 0.67623 | 15.40736 |
May | 508.00000 | 24.54199 | 52.59935 | -0.0224 | 6.73555 |
June | 496.00000 | 24.50143 | 54.97409 | 0.01630 | 6.60159 |
July | 497.00000 | 24.65014 | 54.42133 | 0.08336 | 7.20338 |
August | 514.00000 | 24.51821 | 55.25515 | 0.06368 | 6.75587 |
September | 485.00000 | 24.56119 | 55.33796 | 0.01074 | 6.79537 |
October | 502.00000 | 24.57456 | 53.83389 | 0.73616 | 17.20163 |
November | 489.00000 | 24.39051 | 55.12561 | 0.64928 | 14.38779 |
December | 497.00000 | 23.85056 | 54.94114 | 0.45978 | 10.20644 |
Annual Sum or Average | 5943.00000 | 24.29723 | 53.74015 | 0.33158 | 10.12658 |
Minimum of Months | 454.00000 | 23.45883 | 50.75640 | -0.0224 | 6.60159 |
Maximum of Months | 514.00000 | 24.65014 | 55.33796 | 0.73616 | 17.20163 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.89140 | 54.17580 | 0.15149 | 6.80123 |
February | 454.00000 | 23.40512 | 56.25277 | 0.31320 | 8.11973 |
March | 514.00000 | 23.88189 | 52.27059 | 0.43775 | 9.72877 |
April | 485.00000 | 24.30788 | 53.09054 | 0.59272 | 12.96400 |
May | 508.00000 | 24.50913 | 53.07543 | -0.0880 | 6.62768 |
June | 496.00000 | 24.48406 | 55.45749 | -0.0415 | 6.45907 |
July | 497.00000 | 24.63908 | 54.85556 | 0.03049 | 6.96916 |
August | 514.00000 | 24.49291 | 55.77980 | -0.0106 | 6.48298 |
September | 485.00000 | 24.51928 | 56.08226 | -0.0636 | 6.62657 |
October | 502.00000 | 24.49078 | 54.79143 | 0.67304 | 15.15976 |
November | 489.00000 | 24.17653 | 56.49641 | 0.55448 | 11.81115 |
December | 497.00000 | 23.35582 | 57.36213 | 0.30561 | 8.02645 |
Annual Sum or Average | 5943.00000 | 24.10031 | 54.95460 | 0.23644 | 8.80768 |
Minimum of Months | 454.00000 | 22.89140 | 52.27059 | -0.0880 | 6.45907 |
Maximum of Months | 514.00000 | 24.63908 | 57.36213 | 0.67304 | 15.15976 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.25119 | 52.68719 | 0.25793 | 7.67319 |
February | 454.00000 | 23.67051 | 55.03016 | 0.40161 | 9.44094 |
March | 514.00000 | 24.01391 | 51.50315 | 0.50088 | 11.14123 |
April | 485.00000 | 24.42635 | 52.36125 | 0.66582 | 15.23695 |
May | 508.00000 | 24.54657 | 52.71752 | -0.0017 | 6.82236 |
June | 496.00000 | 24.49232 | 55.20257 | 0.02340 | 6.62490 |
July | 497.00000 | 24.65110 | 54.62451 | 0.09707 | 7.45676 |
August | 514.00000 | 24.50575 | 55.49807 | 0.06488 | 6.74937 |
September | 485.00000 | 24.55941 | 55.62523 | 0.02042 | 6.92216 |
October | 502.00000 | 24.57454 | 54.13434 | 0.73750 | 17.31068 |
November | 489.00000 | 24.32848 | 55.68948 | 0.62514 | 13.76760 |
December | 497.00000 | 23.54815 | 56.35702 | 0.37346 | 8.90097 |
Annual Sum or Average | 5943.00000 | 24.21700 | 54.27076 | 0.31230 | 9.82414 |
Minimum of Months | 454.00000 | 23.25119 | 51.50315 | -0.0017 | 6.62490 |
Maximum of Months | 514.00000 | 24.65110 | 56.35702 | 0.73750 | 17.31068 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.81959 | 50.74867 | 0.42128 | 10.48200 |
February | 454.00000 | 23.98975 | 53.85085 | 0.50499 | 11.71427 |
March | 514.00000 | 24.12647 | 51.18550 | 0.53870 | 12.02389 |
April | 485.00000 | 24.37339 | 52.72974 | 0.63084 | 14.13532 |
May | 508.00000 | 24.48597 | 53.13283 | -0.0943 | 6.59563 |
June | 496.00000 | 24.44418 | 55.62485 | -0.0688 | 6.37074 |
July | 497.00000 | 24.61083 | 54.93428 | 0.01705 | 6.84826 |
August | 514.00000 | 24.49608 | 55.69060 | 0.01145 | 6.54850 |
September | 485.00000 | 24.57478 | 55.66240 | 0.01719 | 6.95399 |
October | 502.00000 | 24.64682 | 53.90582 | 0.78211 | 18.91711 |
November | 489.00000 | 24.53069 | 54.86562 | 0.71953 | 16.82386 |
December | 497.00000 | 24.09521 | 54.37025 | 0.53977 | 12.52825 |
Annual Sum or Average | 5943.00000 | 24.35116 | 53.88262 | 0.33266 | 10.80576 |
Minimum of Months | 454.00000 | 23.81959 | 50.74867 | -0.0943 | 6.37074 |
Maximum of Months | 514.00000 | 24.64682 | 55.69060 | 0.78211 | 18.91711 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.12005 | 52.88399 | 0.23852 | 7.73427 |
February | 454.00000 | 23.60612 | 55.09450 | 0.40031 | 9.64888 |
March | 514.00000 | 24.04215 | 51.36244 | 0.52379 | 11.73472 |
April | 485.00000 | 24.41511 | 52.42382 | 0.67068 | 15.38712 |
May | 508.00000 | 24.53434 | 52.82254 | -0.0079 | 6.88604 |
June | 496.00000 | 24.49638 | 55.21745 | 0.03398 | 6.75978 |
July | 497.00000 | 24.65036 | 54.61344 | 0.10679 | 7.50438 |
August | 514.00000 | 24.52004 | 55.46114 | 0.08595 | 6.99251 |
September | 485.00000 | 24.55800 | 55.63927 | 0.02668 | 6.99505 |
October | 502.00000 | 24.56204 | 54.23999 | 0.74114 | 17.43043 |
November | 489.00000 | 24.30821 | 55.73378 | 0.63257 | 14.06712 |
December | 497.00000 | 23.58633 | 56.03997 | 0.39805 | 9.50751 |
Annual Sum or Average | 5943.00000 | 24.20335 | 54.27853 | 0.31941 | 10.04191 |
Minimum of Months | 454.00000 | 23.12005 | 51.36244 | -0.0079 | 6.75978 |
Maximum of Months | 514.00000 | 24.65036 | 56.03997 | 0.74114 | 17.43043 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.793556E+11 | 160281.47 | 30-JAN-14:10 | 450.44 | 0.797448E+12 | 0.00 | 0.876804E+12 | 6.24 | 10.67 | 01-JAN-06:00 | 0.00 | 0.00 |
February | 0.951447E+11 | 230685.92 | 08-FEB-14:40 | 426.25 | 0.905596E+12 | 0.00 | 0.100074E+13 | 6.37 | 10.64 | 12-FEB-06:13 | 0.00 | 0.00 |
March | 0.139546E+12 | 239367.67 | 01-MAR-16:50 | 557.83 | 0.127199E+13 | 0.00 | 0.141153E+13 | 7.38 | 10.67 | 22-MAR-04:12 | 0.00 | 0.00 |
April | 0.179613E+12 | 248407.22 | 27-APR-11:30 | 636.28 | 0.156584E+13 | 0.00 | 0.174545E+13 | 8.44 | 10.63 | 26-APR-01:15 | 0.00 | 0.00 |
May | 0.246859E+12 | 250869.92 | 24-MAY-05:02 | 688.52 | 0.208069E+13 | 0.00 | 0.232755E+13 | 8.34 | 10.63 | 05-MAY-03:02 | 0.00 | 0.00 |
June | 0.288387E+12 | 258643.34 | 04-JUN-15:42 | 693.16 | 0.231852E+13 | 0.00 | 0.260691E+13 | 8.17 | 10.61 | 02-JUN-02:25 | 0.00 | 0.00 |
July | 0.330418E+12 | 273042.72 | 01-JUL-17:08 | 706.75 | 0.255590E+13 | 0.00 | 0.288632E+13 | 7.73 | 10.61 | 04-JUL-04:53 | 0.00 | 0.00 |
August | 0.348152E+12 | 269685.39 | 26-AUG-05:03 | 709.54 | 0.266496E+13 | 0.00 | 0.301311E+13 | 7.60 | 10.39 | 15-AUG-22:00 | 0.00 | 0.00 |
September | 0.291282E+12 | 266778.10 | 09-SEP-17:10 | 682.19 | 0.230822E+13 | 0.00 | 0.259950E+13 | 7.91 | 10.61 | 26-SEP-04:40 | 0.00 | 0.00 |
October | 0.237456E+12 | 264561.11 | 07-OCT-17:10 | 677.16 | 0.198149E+13 | 0.00 | 0.221895E+13 | 8.15 | 10.62 | 21-OCT-03:00 | 0.00 | 0.00 |
November | 0.172346E+12 | 234426.35 | 27-NOV-16:40 | 587.12 | 0.148520E+13 | 0.00 | 0.165755E+13 | 7.73 | 10.63 | 26-NOV-05:50 | 0.00 | 0.00 |
December | 0.112314E+12 | 233195.10 | 06-DEC-11:10 | 530.30 | 0.105632E+13 | 0.00 | 0.116863E+13 | 7.16 | 10.67 | 18-DEC-06:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.252087E+13 | 7345.55 | 0.209922E+14 | 0.00 | 0.235130E+14 | 7.61 | 0.00 | 0.00 | ||||
Minimum of Months | 0.793556E+11 | 160281.47 | 426.25 | 0.797448E+12 | 0.00 | 0.876804E+12 | 6.24 | 10.39 | 0.00 | 0.00 | ||
Maximum of Months | 0.348152E+12 | 273042.72 | 709.54 | 0.266496E+13 | 0.00 | 0.301311E+13 | 8.44 | 10.67 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.615309E+09 | 99931.90 | 07-FEB-15:20 | 1.83 | 0.565507E+10 | 0.00 | 0.627038E+10 | 0.03 | 9.39 | 07-FEB-17:00 | 0.00 | 0.00 |
March | 0.531861E+10 | 112167.41 | 27-MAR-10:10 | 16.90 | 0.497863E+11 | 0.00 | 0.551049E+11 | 0.22 | 11.16 | 23-MAR-13:10 | 0.00 | 0.00 |
April | 0.149143E+11 | 128118.30 | 26-APR-12:20 | 45.92 | 0.138084E+12 | 0.00 | 0.152998E+12 | 0.60 | 11.28 | 28-APR-08:30 | 0.00 | 0.00 |
May | 0.596953E+11 | 250869.92 | 24-MAY-05:02 | 163.20 | 0.524861E+12 | 0.00 | 0.584556E+12 | 1.95 | 11.13 | 11-MAY-08:70 | 0.00 | 0.00 |
June | 0.111750E+12 | 218743.37 | 04-JUN-16:14 | 275.73 | 0.938240E+12 | 0.00 | 0.104999E+13 | 3.26 | 10.76 | 16-JUN-16:20 | 0.00 | 0.00 |
July | 0.164610E+12 | 269593.42 | 05-JUL-05:03 | 347.51 | 0.129797E+13 | 0.00 | 0.146258E+13 | 3.76 | 10.64 | 03-JUL-09:00 | 0.00 | 0.00 |
August | 0.195600E+12 | 269685.39 | 26-AUG-05:03 | 396.29 | 0.151877E+13 | 0.00 | 0.171437E+13 | 4.22 | 10.70 | 31-AUG-07:20 | 0.00 | 0.00 |
September | 0.122687E+12 | 251133.67 | 11-SEP-05:02 | 285.95 | 0.100495E+13 | 0.00 | 0.112764E+13 | 3.30 | 10.67 | 14-SEP-07:20 | 0.00 | 0.00 |
October | 0.638442E+11 | 250326.15 | 18-OCT-05:02 | 174.32 | 0.559176E+12 | 0.00 | 0.623020E+12 | 2.07 | 11.12 | 20-OCT-11:50 | 0.00 | 0.00 |
November | 0.238957E+11 | 134912.29 | 01-NOV-14:00 | 69.05 | 0.215084E+12 | 0.00 | 0.238979E+12 | 0.87 | 11.29 | 16-NOV-06:04 | 0.00 | 0.00 |
December | 0.178628E+10 | 103560.32 | 06-DEC-13:50 | 5.83 | 0.165115E+11 | 0.00 | 0.182978E+11 | 0.07 | 10.90 | 06-DEC-15:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.764717E+12 | 1782.54 | 0.626909E+13 | 0.00 | 0.703381E+13 | 1.71 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.195600E+12 | 269685.39 | 396.29 | 0.151877E+13 | 0.00 | 0.171437E+13 | 4.22 | 11.29 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.102966E+12 | 744.00 | 49248.27 | 01-JAN-09:43 | 233718.77 | 23-JAN-14:20 | 24.64 | 21.14 | 16.55 |
February | 0.111111E+12 | 672.00 | 49248.27 | 01-FEB-00:10 | 433345.75 | 22-FEB-05:30 | 29.22 | 23.10 | 16.55 |
March | 0.131394E+12 | 744.00 | 49248.27 | 01-MAR-00:10 | 657529.39 | 31-MAR-23:23 | 35.03 | 26.25 | 16.55 |
April | 0.127652E+12 | 720.00 | 49248.27 | 01-APR-00:03 | 764575.45 | 28-APR-12:40 | 42.24 | 30.65 | 16.55 |
May | 0.131907E+12 | 744.00 | 49248.27 | 01-MAY-00:03 | 402327.86 | 31-MAY-23:25 | 37.02 | 32.85 | 16.55 |
June | 0.127652E+12 | 720.00 | 49248.27 | 01-JUN-00:05 | 563139.73 | 30-JUN-23:17 | 42.58 | 35.51 | 16.55 |
July | 0.131907E+12 | 744.00 | 49248.27 | 01-JUL-00:03 | 738897.29 | 31-JUL-23:33 | 48.69 | 38.71 | 16.55 |
August | 0.131907E+12 | 744.00 | 49248.27 | 01-AUG-00:05 | 801777.89 | 04-AUG-13:50 | 52.57 | 39.93 | 16.55 |
September | 0.127652E+12 | 720.00 | 49248.27 | 01-SEP-00:03 | 406686.66 | 30-SEP-23:15 | 38.51 | 34.07 | 16.55 |
October | 0.131907E+12 | 744.00 | 49248.27 | 01-OCT-00:03 | 533063.76 | 31-OCT-23:23 | 38.81 | 31.97 | 16.55 |
November | 0.127652E+12 | 720.00 | 49248.27 | 01-NOV-00:03 | 588465.72 | 01-NOV-14:20 | 37.83 | 28.76 | 16.55 |
December | 0.131486E+12 | 744.00 | 49248.27 | 01-DEC-00:05 | 702231.52 | 05-DEC-16:50 | 36.30 | 25.11 | 16.55 |
Annual Sum or Average | 0.151519E+13 | 8760.00 | 38.68 | 30.71 | 16.55 | ||||
Minimum of Months | 0.102966E+12 | 672.00 | 49248.27 | 233718.77 | 24.64 | 21.14 | 16.55 | ||
Maximum of Months | 0.131907E+12 | 744.00 | 49248.27 | 801777.89 | 52.57 | 39.93 | 16.55 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.304982E+10 | 410.70 | 23853.96 | 09-JAN-13:20 | 1419981.27 | 24-JAN-13:30 | 22.47 | 21.48 | 47.84 |
February | 0.728368E+10 | 399.86 | 23853.96 | 02-FEB-12:00 | 1788555.71 | 06-FEB-15:10 | 22.75 | 21.51 | 50.86 |
March | 0.132350E+11 | 495.47 | 23853.96 | 01-MAR-06:04 | 1833640.50 | 01-MAR-13:30 | 23.03 | 21.45 | 58.54 |
April | 0.294965E+11 | 587.51 | 23853.96 | 03-APR-05:05 | 1870806.88 | 06-APR-13:50 | 24.02 | 22.01 | 68.50 |
May | 0.501553E+11 | 683.95 | 23853.96 | 01-MAY-00:03 | 1867279.34 | 04-MAY-09:00 | 26.48 | 23.92 | 68.32 |
June | 0.580719E+11 | 693.05 | 23853.96 | 01-JUN-00:05 | 1788086.64 | 02-JUN-08:70 | 29.21 | 26.24 | 63.99 |
July | 0.593069E+11 | 706.08 | 23853.96 | 01-JUL-00:03 | 1821757.01 | 31-JUL-05:03 | 30.56 | 27.37 | 63.21 |
August | 0.609310E+11 | 709.54 | 23853.96 | 01-AUG-00:05 | 1793643.09 | 01-AUG-05:03 | 31.15 | 27.82 | 63.00 |
September | 0.583270E+11 | 682.19 | 23853.96 | 01-SEP-00:03 | 1582820.65 | 07-SEP-14:10 | 29.83 | 26.87 | 62.13 |
October | 0.518381E+11 | 669.86 | 23853.96 | 01-OCT-00:03 | 1868981.91 | 20-OCT-10:30 | 26.79 | 24.34 | 65.37 |
November | 0.288965E+11 | 534.01 | 23853.96 | 01-NOV-02:00 | 1827391.27 | 13-NOV-09:50 | 24.13 | 22.23 | 62.61 |
December | 0.115585E+11 | 464.12 | 23853.96 | 01-DEC-13:10 | 1665685.73 | 08-DEC-14:40 | 22.75 | 21.44 | 55.88 |
Annual Sum or Average | 0.432150E+12 | 7036.37 | 26.12 | 23.90 | 60.90 | ||||
Minimum of Months | 0.304982E+10 | 399.86 | 23853.96 | 1419981.27 | 22.47 | 21.44 | 47.84 | ||
Maximum of Months | 0.609310E+11 | 709.54 | 23853.96 | 1870806.88 | 31.15 | 27.82 | 68.50 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 22.47 | 22.47 | 0.00 |
February | 0.443684E+09 | 5.17 | 23853.96 | 07-FEB-10:50 | 1038055.55 | 07-FEB-16:50 | 22.75 | 22.72 | 0.43 |
March | 0.221681E+10 | 26.53 | 23853.96 | 01-MAR-13:50 | 1435283.36 | 23-MAR-14:50 | 23.03 | 22.89 | 2.27 |
April | 0.683800E+10 | 80.97 | 23853.96 | 03-APR-07:20 | 1482896.03 | 25-APR-14:30 | 24.02 | 23.61 | 6.91 |
May | 0.252122E+11 | 293.72 | 23853.96 | 01-MAY-07:20 | 1480110.24 | 24-MAY-05:02 | 26.48 | 25.13 | 24.89 |
June | 0.458974E+11 | 534.47 | 23853.96 | 01-JUN-07:20 | 1437627.57 | 22-JUN-14:10 | 29.21 | 26.68 | 45.95 |
July | 0.525934E+11 | 612.45 | 23853.96 | 01-JUL-00:03 | 1821757.01 | 31-JUL-05:03 | 30.56 | 27.62 | 52.84 |
August | 0.575833E+11 | 670.55 | 23853.96 | 01-AUG-00:05 | 1793643.09 | 01-AUG-05:03 | 31.15 | 27.91 | 58.71 |
September | 0.478273E+11 | 556.95 | 23853.96 | 01-SEP-00:03 | 1582820.65 | 07-SEP-14:10 | 29.83 | 27.17 | 47.90 |
October | 0.287994E+11 | 336.08 | 23853.96 | 01-OCT-00:15 | 1447164.41 | 18-OCT-05:04 | 26.79 | 25.27 | 27.92 |
November | 0.103112E+11 | 120.40 | 23853.96 | 01-NOV-07:20 | 1514970.34 | 13-NOV-14:00 | 24.13 | 23.53 | 10.67 |
December | 0.141693E+10 | 16.50 | 23853.96 | 04-DEC-09:50 | 1086941.95 | 06-DEC-15:40 | 22.75 | 22.66 | 1.23 |
Annual Sum or Average | 0.279140E+12 | 3253.80 | 26.12 | 24.82 | 23.45 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 22.47 | 22.47 | 0.00 | ||
Maximum of Months | 0.575833E+11 | 670.55 | 23853.96 | 1821757.01 | 31.15 | 27.91 | 58.71 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 24.64 | 24.64 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 29.22 | 29.22 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 35.03 | 35.03 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 42.24 | 42.24 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 37.02 | 37.02 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 42.58 | 42.58 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 48.69 | 48.69 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 52.57 | 52.57 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 38.51 | 38.51 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 38.81 | 38.81 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 37.83 | 37.83 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 36.30 | 36.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 38.68 | 38.68 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.64 | 24.64 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.57 | 52.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.790113E+11 | 0.00 | 429.00 | 0.760340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 239705.30 | 30-JAN-05:12 | 167959.42 | 30-JAN-05:12 | 0.00 | 0.00 | 0.00 |
February | 0.976002E+11 | 0.00 | 408.60 | 0.913336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 267882.68 | 09-FEB-05:12 | 183619.05 | 09-FEB-05:12 | 0.00 | 0.00 | 0.00 |
March | 0.146046E+12 | 0.00 | 538.97 | 0.137738E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 232471.65 | 24-MAR-05:02 | 184216.42 | 02-MAR-06:03 | 0.00 | 0.00 | 0.00 |
April | 0.193752E+12 | 0.00 | 606.40 | 0.173831E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 248454.30 | 08-APR-05:02 | 189397.58 | 29-APR-05:03 | 0.00 | 0.00 | 0.00 |
May | 0.275630E+12 | 0.00 | 632.88 | 0.236778E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 322583.13 | 30-MAY-04:12 | 214806.80 | 29-MAY-16:51 | 0.00 | 0.00 | 0.00 |
June | 0.338324E+12 | 0.00 | 637.47 | 0.259080E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 332456.03 | 11-JUN-13:02 | 220495.12 | 11-JUN-17:01 | 0.00 | 0.00 | 0.00 |
July | 0.397963E+12 | 0.00 | 651.91 | 0.289687E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 356138.29 | 24-JUL-03:02 | 222880.97 | 02-JUL-13:02 | 0.00 | 0.00 | 0.00 |
August | 0.439625E+12 | 0.00 | 659.13 | 0.319820E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 356598.47 | 08-AUG-03:02 | 225637.94 | 06-AUG-15:01 | 0.00 | 0.00 | 0.00 |
September | 0.348590E+12 | 0.00 | 626.76 | 0.252474E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 340131.10 | 11-SEP-03:02 | 249647.76 | 04-SEP-16:22 | 0.00 | 0.00 | 0.00 |
October | 0.293635E+12 | 0.00 | 631.74 | 0.234061E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 323831.14 | 02-OCT-04:12 | 212741.44 | 09-OCT-19:42 | 0.00 | 0.00 | 0.00 |
November | 0.193738E+12 | 0.00 | 557.57 | 0.167395E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 283456.32 | 01-NOV-05:02 | 188432.63 | 01-NOV-05:02 | 0.00 | 0.00 | 0.00 |
December | 0.123668E+12 | 0.00 | 506.53 | 0.112241E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 251653.60 | 11-DEC-06:02 | 174277.50 | 11-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.292758E+13 | 0.00 | 6886.97 | 0.235047E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.790113E+11 | 0.00 | 408.60 | 0.760340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 232471.65 | 167959.42 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.439625E+12 | 0.00 | 659.13 | 0.319820E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 356598.47 | 249647.76 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.582513E+12 | 0.00 | 410.76 | 0.558953E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1588408.28 | 30-JAN-06:03 | 1167062.06 | 23-JAN-06:01 | 0.00 | 0.00 | 0.00 |
February | 0.674535E+12 | 0.00 | 382.18 | 0.625564E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2158885.85 | 06-FEB-06:02 | 1506019.94 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 |
March | 0.992814E+12 | 0.00 | 457.64 | 0.927118E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2186741.68 | 29-MAR-05:02 | 1626645.46 | 27-MAR-04:12 | 0.00 | 0.00 | 0.00 |
April | 0.129662E+13 | 0.00 | 475.82 | 0.114875E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2411739.19 | 20-APR-04:12 | 1652320.81 | 26-APR-04:12 | 0.00 | 0.00 | 0.00 |
May | 0.206309E+13 | 0.00 | 587.38 | 0.171347E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2825276.34 | 24-MAY-05:02 | 1764689.98 | 11-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.261862E+13 | 0.00 | 605.65 | 0.186385E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2841680.72 | 04-JUN-16:11 | 1755117.37 | 02-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.312218E+13 | 0.00 | 635.30 | 0.206821E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3196787.87 | 06-JUL-05:02 | 1921004.17 | 24-JUL-05:01 | 0.00 | 0.00 | 0.00 |
August | 0.337914E+13 | 0.00 | 649.92 | 0.221245E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3235777.35 | 08-AUG-05:01 | 1870016.89 | 02-AUG-05:01 | 0.00 | 0.00 | 0.00 |
September | 0.266465E+13 | 0.00 | 585.51 | 0.176296E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3044620.19 | 28-SEP-05:02 | 1758469.96 | 28-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.199781E+13 | 0.00 | 539.67 | 0.149865E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2845060.53 | 18-OCT-05:02 | 1694681.93 | 18-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.129797E+13 | 0.00 | 449.26 | 0.108217E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2477759.56 | 01-NOV-04:12 | 1638384.33 | 04-NOV-04:12 | 0.00 | 0.00 | 0.00 |
December | 0.779450E+12 | 0.00 | 419.89 | 0.695622E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2149396.90 | 11-DEC-06:02 | 1410900.92 | 11-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.214694E+14 | 0.00 | 6198.97 | 0.161578E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.582513E+12 | 0.00 | 382.18 | 0.558953E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1588408.28 | 1167062.06 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.337914E+13 | 0.00 | 649.92 | 0.221245E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 3235777.35 | 1921004.17 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.538507E+11 | 0.00 | 400.58 | 0.514882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 165278.96 | 30-JAN-06:03 | 108288.37 | 30-JAN-06:03 | 0.00 | 0.00 | 0.00 |
February | 0.658562E+11 | 0.00 | 372.14 | 0.609441E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 220930.00 | 06-FEB-06:02 | 150396.36 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 |
March | 0.100311E+12 | 0.00 | 449.49 | 0.937291E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 225623.12 | 29-MAR-05:02 | 165448.61 | 14-MAR-05:02 | 0.00 | 0.00 | 0.00 |
April | 0.135068E+12 | 0.00 | 474.18 | 0.120158E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 255047.36 | 18-APR-03:02 | 175637.93 | 18-APR-03:02 | 0.00 | 0.00 | 0.00 |
May | 0.219630E+12 | 0.00 | 587.23 | 0.184645E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 294295.09 | 29-MAY-13:22 | 194142.86 | 12-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.278212E+12 | 0.00 | 607.15 | 0.202532E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 310125.97 | 25-JUN-14:32 | 189858.31 | 02-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.331628E+12 | 0.00 | 637.34 | 0.226227E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 355242.80 | 24-JUL-05:01 | 216896.08 | 24-JUL-05:01 | 0.00 | 0.00 | 0.00 |
August | 0.357066E+12 | 0.00 | 650.78 | 0.240762E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 355118.16 | 08-AUG-05:01 | 214373.51 | 28-AUG-05:03 | 0.00 | 0.00 | 0.00 |
September | 0.279660E+12 | 0.00 | 586.59 | 0.189337E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 326861.94 | 28-SEP-05:02 | 196582.28 | 05-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.206180E+12 | 0.00 | 537.83 | 0.156356E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 287917.20 | 18-OCT-05:02 | 182303.07 | 20-OCT-04:12 | 0.00 | 0.00 | 0.00 |
November | 0.128876E+12 | 0.00 | 441.81 | 0.107515E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 245379.53 | 01-NOV-04:12 | 164797.67 | 25-NOV-06:02 | 0.00 | 0.00 | 0.00 |
December | 0.741810E+11 | 0.00 | 407.85 | 0.659674E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 188498.10 | 11-DEC-06:02 | 120398.84 | 11-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.223052E+13 | 0.00 | 6152.95 | 0.169966E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.538507E+11 | 0.00 | 372.14 | 0.514882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 165278.96 | 108288.37 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.357066E+12 | 0.00 | 650.78 | 0.240762E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 355242.80 | 216896.08 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.728139E+11 | 0.00 | 384.53 | 0.711012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 276292.06 | 30-JAN-21:11 | 125135.16 | 01-JAN-19:02 | 0.00 | 0.00 | 0.00 |
February | 0.581197E+11 | 0.00 | 279.95 | 0.557414E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 312075.12 | 09-FEB-16:12 | 129853.37 | 10-FEB-05:41 | 0.00 | 0.00 | 0.00 |
March | 0.606604E+11 | 0.00 | 236.98 | 0.547933E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 297796.46 | 24-MAR-03:23 | 111622.65 | 06-MAR-05:12 | 0.00 | 0.00 | 0.00 |
April | 0.421885E+11 | 0.00 | 124.92 | 0.343672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 303749.04 | 30-APR-03:51 | 114931.40 | 13-APR-05:08 | 0.00 | 0.00 | 0.00 |
May | 0.729560E+10 | 0.00 | 16.00 | 0.559568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 222796.88 | 01-MAY-05:12 | 118079.28 | 01-MAY-11:00 | 0.00 | 0.00 | 0.00 |
June | 0.734394E+10 | 0.00 | 13.17 | 0.556720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 314554.20 | 22-JUN-07:51 | 130531.37 | 22-JUN-12:00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 |
October | 0.591246E+10 | 0.00 | 11.70 | 0.478400E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 314716.87 | 21-OCT-03:45 | 134036.70 | 21-OCT-09:45 | 0.00 | 0.00 | 0.00 |
November | 0.641948E+11 | 0.00 | 170.51 | 0.541087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 309866.33 | 04-NOV-04:23 | 127072.84 | 06-NOV-04:25 | 0.00 | 0.00 | 0.00 |
December | 0.754585E+11 | 0.00 | 318.16 | 0.687956E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 293547.07 | 12-DEC-20:51 | 120474.61 | 13-DEC-00:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.393988E+12 | 0.00 | 1555.92 | 0.354854E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.754585E+11 | 0.00 | 384.53 | 0.711012E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 314716.87 | 134036.70 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.355737E+12 | 0.989545E+11 | 744.00 | 0.344986E+12 | 0.107509E+11 | 0.00 | 0.33 | 23-JAN-14:00 | 0.29 | 21-JAN-06:00 | 144009.73 | 30-JAN-15:00 | 134771.68 | 23-JAN-14:00 | 10962.22 | 30-JAN-15:00 | 48414.81 | 23-JAN-14:00 | 0.00 |
February | 0.546859E+12 | 0.154323E+12 | 672.00 | 0.533790E+12 | 0.130692E+11 | 0.00 | 0.56 | 07-FEB-14:00 | 0.48 | 01-FEB-05:00 | 239100.78 | 07-FEB-16:10 | 228537.17 | 06-FEB-15:00 | 11749.76 | 07-FEB-16:10 | 89889.87 | 06-FEB-15:00 | 0.00 |
March | 0.851298E+12 | 0.254505E+12 | 744.00 | 0.838653E+12 | 0.126444E+11 | 0.00 | 0.87 | 31-MAR-23:13 | 0.66 | 19-MAR-05:00 | 408892.43 | 31-MAR-23:05 | 398958.20 | 31-MAR-24:00 | 12108.85 | 28-MAR-16:00 | 144059.53 | 27-MAR-11:00 | 0.00 |
April | 0.106523E+13 | 0.347710E+12 | 720.00 | 0.105184E+13 | 0.133918E+11 | 0.00 | 1.00 | 26-APR-10:00 | 0.37 | 30-APR-23:13 | 422975.34 | 28-APR-14:10 | 419958.82 | 28-APR-12:40 | 16008.19 | 10-APR-10:00 | 196491.92 | 28-APR-12:00 | 0.00 |
May | 0.379179E+12 | 0.146145E+12 | 744.00 | 0.361396E+12 | 0.177829E+11 | 0.00 | 0.55 | 31-MAY-23:03 | 0.31 | 03-MAY-06:00 | 232112.17 | 31-MAY-23:03 | 221575.77 | 31-MAY-23:42 | 15811.43 | 30-MAY-00:57 | 90347.92 | 31-MAY-23:15 | 0.00 |
June | 0.616896E+12 | 0.241903E+12 | 720.00 | 0.589200E+12 | 0.276964E+11 | 0.00 | 0.75 | 30-JUN-24:00 | 0.52 | 22-JUN-08:00 | 330177.77 | 30-JUN-23:03 | 313024.43 | 30-JUN-24:00 | 18702.14 | 08-JUN-13:00 | 122018.90 | 30-JUN-24:00 | 0.00 |
July | 0.892248E+12 | 0.363986E+12 | 744.00 | 0.858850E+12 | 0.333986E+11 | 0.00 | 0.96 | 31-JUL-23:03 | 0.72 | 03-JUL-06:00 | 426021.15 | 31-JUL-23:03 | 406507.30 | 31-JUL-24:00 | 22665.38 | 20-JUL-11:00 | 174539.51 | 21-JUL-12:00 | 0.00 |
August | 0.114053E+13 | 0.462530E+12 | 744.00 | 0.110605E+13 | 0.344790E+11 | 0.00 | 1.00 | 01-AUG-10:10 | 0.39 | 31-AUG-23:15 | 446923.06 | 04-AUG-14:00 | 422644.70 | 10-AUG-21:01 | 24755.59 | 04-AUG-14:00 | 209409.72 | 16-AUG-12:00 | 0.00 |
September | 0.386507E+12 | 0.151542E+12 | 720.00 | 0.355953E+12 | 0.305538E+11 | 0.00 | 0.55 | 30-SEP-23:03 | 0.33 | 30-SEP-05:00 | 242706.63 | 30-SEP-23:03 | 220972.73 | 30-SEP-23:57 | 22502.07 | 30-SEP-23:03 | 83673.85 | 30-SEP-23:15 | 0.00 |
October | 0.633170E+12 | 0.227253E+12 | 744.00 | 0.609065E+12 | 0.241047E+11 | 0.00 | 0.72 | 31-OCT-23:12 | 0.51 | 29-OCT-07:00 | 320633.19 | 31-OCT-23:10 | 312758.38 | 31-OCT-23:53 | 18523.82 | 07-OCT-10:20 | 107491.52 | 31-OCT-23:15 | 0.00 |
November | 0.837144E+12 | 0.267201E+12 | 720.00 | 0.820160E+12 | 0.169840E+11 | 0.00 | 0.78 | 01-NOV-14:00 | 0.67 | 26-NOV-05:30 | 337385.13 | 01-NOV-15:00 | 322823.45 | 02-NOV-15:00 | 15624.49 | 01-NOV-15:00 | 129699.12 | 01-NOV-14:00 | 0.00 |
December | 0.110248E+13 | 0.307746E+12 | 744.00 | 0.108529E+13 | 0.171886E+11 | 0.00 | 0.92 | 04-DEC-13:10 | 0.84 | 31-DEC-06:00 | 423543.98 | 05-DEC-17:00 | 411358.45 | 11-DEC-17:00 | 13726.79 | 26-DEC-07:30 | 146342.33 | 10-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.880728E+13 | 0.302380E+13 | 8760.00 | 0.855523E+13 | 0.252044E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.355737E+12 | 0.989545E+11 | 672.00 | 0.344986E+12 | 0.107509E+11 | 0.00 | 0.33 | 0.29 | 144009.73 | 134771.68 | 10962.22 | 48414.81 | 0.00 | ||||||
Maximum of Months | 0.114053E+13 | 0.462530E+12 | 744.00 | 0.110605E+13 | 0.344790E+11 | 0.00 | 1.00 | 0.84 | 446923.06 | 422644.70 | 24755.59 | 209409.72 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.573873E+10 | 0.156971E+10 | 744.00 | 0.539798E+10 | 0.340750E+09 | 0.00 | 0.32 | 30-JAN-12:00 | 0.19 | 21-JAN-08:00 | 2761.29 | 30-JAN-15:00 | 2435.77 | 23-JAN-14:00 | 425.51 | 30-JAN-15:10 | 869.41 | 23-JAN-14:00 | 0.00 |
February | 0.101491E+11 | 0.278603E+10 | 672.00 | 0.969808E+10 | 0.450998E+09 | 0.00 | 0.58 | 07-FEB-16:10 | 0.42 | 01-FEB-07:00 | 4924.42 | 07-FEB-16:10 | 4489.01 | 06-FEB-15:40 | 493.23 | 07-FEB-16:10 | 1717.31 | 06-FEB-15:00 | 0.00 |
March | 0.164695E+11 | 0.477644E+10 | 744.00 | 0.160024E+11 | 0.467129E+09 | 0.00 | 0.88 | 31-MAR-23:05 | 0.62 | 08-MAR-07:00 | 8145.64 | 31-MAR-23:05 | 7692.14 | 31-MAR-24:00 | 495.17 | 28-MAR-16:00 | 2767.96 | 27-MAR-11:00 | 0.00 |
April | 0.212503E+11 | 0.668216E+10 | 720.00 | 0.206466E+11 | 0.603672E+09 | 0.00 | 1.00 | 24-APR-12:00 | 0.39 | 30-APR-23:53 | 8997.06 | 30-APR-18:00 | 8503.90 | 26-APR-14:30 | 597.17 | 30-APR-15:00 | 3693.75 | 28-APR-12:00 | 0.00 |
May | 0.750375E+10 | 0.276696E+10 | 744.00 | 0.676709E+10 | 0.736656E+09 | 0.00 | 0.58 | 31-MAY-23:03 | 0.27 | 03-MAY-06:00 | 4771.64 | 31-MAY-23:03 | 4357.54 | 31-MAY-24:00 | 658.54 | 30-MAY-02:00 | 1766.21 | 31-MAY-23:15 | 0.00 |
June | 0.127932E+11 | 0.476817E+10 | 720.00 | 0.115934E+11 | 0.119976E+10 | 0.00 | 0.79 | 30-JUN-23:03 | 0.51 | 07-JUN-06:00 | 6933.46 | 30-JUN-23:03 | 6183.86 | 30-JUN-24:00 | 801.22 | 08-JUN-13:00 | 2419.78 | 09-JUN-15:00 | 0.00 |
July | 0.188862E+11 | 0.729785E+10 | 744.00 | 0.173925E+11 | 0.149364E+10 | 0.00 | 1.00 | 31-JUL-23:03 | 0.73 | 03-JUL-06:30 | 8819.75 | 31-JUL-24:00 | 8120.47 | 31-JUL-24:00 | 959.61 | 20-JUL-14:00 | 3444.29 | 30-JUL-13:55 | 0.00 |
August | 0.233069E+11 | 0.889163E+10 | 744.00 | 0.217489E+11 | 0.155805E+10 | 0.00 | 1.00 | 01-AUG-00:05 | 0.40 | 31-AUG-23:05 | 9087.30 | 27-AUG-06:00 | 8443.64 | 14-AUG-03:23 | 972.75 | 30-AUG-20:00 | 3939.23 | 16-AUG-12:00 | 0.00 |
September | 0.800796E+10 | 0.296572E+10 | 720.00 | 0.672700E+10 | 0.128096E+10 | 0.00 | 0.59 | 30-SEP-23:03 | 0.30 | 26-SEP-07:00 | 5203.69 | 30-SEP-23:03 | 4241.68 | 30-SEP-23:57 | 984.91 | 30-SEP-23:03 | 1671.74 | 30-SEP-23:07 | 0.00 |
October | 0.127803E+11 | 0.438631E+10 | 744.00 | 0.117474E+11 | 0.103295E+10 | 0.00 | 0.74 | 31-OCT-23:10 | 0.48 | 21-OCT-07:00 | 6412.09 | 31-OCT-23:10 | 6067.71 | 31-OCT-23:53 | 846.20 | 07-OCT-10:10 | 2101.37 | 09-OCT-15:11 | 0.00 |
November | 0.165226E+11 | 0.508232E+10 | 720.00 | 0.157923E+11 | 0.730308E+09 | 0.00 | 0.83 | 01-NOV-14:20 | 0.65 | 22-NOV-07:00 | 7143.08 | 01-NOV-16:00 | 6611.63 | 05-NOV-16:55 | 675.44 | 01-NOV-15:00 | 2589.43 | 01-NOV-14:00 | 0.00 |
December | 0.214399E+11 | 0.580101E+10 | 744.00 | 0.208655E+11 | 0.574314E+09 | 0.00 | 0.96 | 05-DEC-17:00 | 0.80 | 30-DEC-08:00 | 8777.91 | 05-DEC-17:00 | 8199.28 | 05-DEC-17:00 | 578.63 | 05-DEC-17:00 | 2808.62 | 10-DEC-12:43 | 0.00 |
Annual Sum or Average | 0.174848E+12 | 0.577743E+11 | 8760.00 | 0.164379E+12 | 0.104692E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.573873E+10 | 0.156971E+10 | 672.00 | 0.539798E+10 | 0.340750E+09 | 0.00 | 0.32 | 0.19 | 2761.29 | 2435.77 | 425.51 | 869.41 | 0.00 | ||||||
Maximum of Months | 0.233069E+11 | 0.889163E+10 | 744.00 | 0.217489E+11 | 0.155805E+10 | 0.00 | 1.00 | 0.80 | 9087.30 | 8503.90 | 984.91 | 3939.23 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.471563E+11 | 0.130667E+11 | 744.00 | 0.439002E+11 | 0.325610E+10 | 0.00 | 0.31 | 24-JAN-17:00 | 0.14 | 21-JAN-08:00 | 25309.16 | 30-JAN-15:00 | 22095.11 | 31-JAN-17:00 | 4163.56 | 30-JAN-15:10 | 7938.53 | 23-JAN-14:00 | 0.00 |
February | 0.916726E+11 | 0.253314E+11 | 672.00 | 0.872224E+11 | 0.445019E+10 | 0.00 | 0.57 | 07-FEB-16:10 | 0.38 | 13-FEB-07:00 | 46540.89 | 07-FEB-16:10 | 42344.83 | 06-FEB-15:50 | 4888.04 | 07-FEB-16:10 | 16230.42 | 06-FEB-15:00 | 0.00 |
March | 0.154677E+12 | 0.449750E+11 | 744.00 | 0.150032E+12 | 0.464536E+10 | 0.00 | 0.89 | 31-MAR-23:05 | 0.59 | 08-MAR-07:00 | 78291.71 | 31-MAR-23:05 | 73766.21 | 31-MAR-24:00 | 4911.31 | 28-MAR-16:00 | 26343.25 | 27-MAR-11:00 | 0.00 |
April | 0.201685E+12 | 0.634552E+11 | 720.00 | 0.195661E+12 | 0.602358E+10 | 0.00 | 1.00 | 24-APR-12:10 | 0.32 | 30-APR-23:13 | 84980.04 | 30-APR-17:55 | 80605.88 | 26-APR-14:00 | 6011.03 | 30-APR-14:59 | 35244.28 | 28-APR-12:00 | 0.00 |
May | 0.684446E+11 | 0.253154E+11 | 744.00 | 0.612180E+11 | 0.722655E+10 | 0.00 | 0.57 | 31-MAY-23:03 | 0.26 | 03-MAY-06:00 | 45163.61 | 31-MAY-23:03 | 40777.02 | 31-MAY-23:42 | 6397.65 | 16-MAY-15:00 | 16682.26 | 31-MAY-23:15 | 0.00 |
June | 0.119325E+12 | 0.445357E+11 | 720.00 | 0.107431E+12 | 0.118942E+11 | 0.00 | 0.79 | 30-JUN-23:03 | 0.50 | 07-JUN-06:00 | 66093.33 | 30-JUN-23:03 | 58329.64 | 30-JUN-24:00 | 8079.94 | 30-JUN-23:03 | 22846.96 | 30-JUN-23:57 | 0.00 |
July | 0.176047E+12 | 0.681646E+11 | 744.00 | 0.161191E+12 | 0.148569E+11 | 0.00 | 1.00 | 31-JUL-23:03 | 0.71 | 03-JUL-06:00 | 84298.06 | 31-JUL-23:03 | 76850.33 | 31-JUL-24:00 | 9547.89 | 20-JUL-14:00 | 32299.82 | 21-JUL-12:00 | 0.00 |
August | 0.220899E+12 | 0.845759E+11 | 744.00 | 0.205266E+12 | 0.156336E+11 | 0.00 | 1.00 | 01-AUG-00:05 | 0.35 | 31-AUG-23:15 | 86004.77 | 08-AUG-07:20 | 78743.70 | 07-AUG-02:23 | 9690.58 | 30-AUG-20:00 | 37584.57 | 16-AUG-12:00 | 0.00 |
September | 0.725718E+11 | 0.269213E+11 | 720.00 | 0.600047E+11 | 0.125671E+11 | 0.00 | 0.58 | 30-SEP-23:03 | 0.28 | 26-SEP-06:00 | 49248.58 | 30-SEP-23:03 | 39445.73 | 30-SEP-23:43 | 10215.36 | 30-SEP-23:03 | 15748.46 | 30-SEP-23:07 | 0.00 |
October | 0.118541E+12 | 0.407570E+11 | 744.00 | 0.108313E+12 | 0.102287E+11 | 0.00 | 0.73 | 31-OCT-23:12 | 0.46 | 21-OCT-07:00 | 61032.10 | 31-OCT-23:10 | 57623.27 | 31-OCT-23:53 | 8408.91 | 07-OCT-10:10 | 19591.22 | 31-OCT-23:12 | 0.00 |
November | 0.155274E+12 | 0.478408E+11 | 720.00 | 0.148011E+12 | 0.726299E+10 | 0.00 | 0.82 | 01-NOV-14:00 | 0.62 | 22-NOV-07:00 | 67579.98 | 01-NOV-16:00 | 61077.70 | 01-NOV-16:00 | 6714.75 | 01-NOV-15:00 | 24510.04 | 01-NOV-14:00 | 0.00 |
December | 0.200106E+12 | 0.543392E+11 | 744.00 | 0.194382E+12 | 0.572379E+10 | 0.00 | 0.96 | 05-DEC-17:00 | 0.76 | 30-DEC-08:00 | 83411.04 | 05-DEC-17:00 | 77661.68 | 06-DEC-17:00 | 5769.49 | 05-DEC-17:00 | 26210.75 | 10-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.162640E+13 | 0.539278E+12 | 8760.00 | 0.152263E+13 | 0.103769E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.471563E+11 | 0.130667E+11 | 672.00 | 0.439002E+11 | 0.325610E+10 | 0.00 | 0.31 | 0.14 | 25309.16 | 22095.11 | 4163.56 | 7938.53 | 0.00 | ||||||
Maximum of Months | 0.220899E+12 | 0.845759E+11 | 744.00 | 0.205266E+12 | 0.156336E+11 | 0.00 | 1.00 | 0.76 | 86004.77 | 80605.88 | 10215.36 | 37584.57 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.421098E+10 | 0.118222E+10 | 744.00 | 0.389453E+10 | 0.316456E+09 | 0.00 | 0.31 | 24-JAN-17:00 | 0.09 | 01-JAN-08:00 | 2564.21 | 30-JAN-15:00 | 2255.68 | 23-JAN-14:10 | 419.38 | 30-JAN-15:00 | 809.78 | 23-JAN-14:00 | 0.00 |
February | 0.888685E+10 | 0.246955E+10 | 672.00 | 0.844348E+10 | 0.443369E+09 | 0.00 | 0.57 | 07-FEB-16:10 | 0.33 | 13-FEB-08:00 | 4701.89 | 07-FEB-16:10 | 4289.13 | 06-FEB-15:40 | 489.83 | 07-FEB-16:10 | 1642.36 | 06-FEB-15:00 | 0.00 |
March | 0.153239E+11 | 0.446987E+10 | 744.00 | 0.148595E+11 | 0.464429E+09 | 0.00 | 0.88 | 31-MAR-23:05 | 0.56 | 08-MAR-07:00 | 7779.00 | 31-MAR-23:05 | 7321.54 | 31-MAR-24:00 | 491.92 | 28-MAR-16:00 | 2642.60 | 27-MAR-11:00 | 0.00 |
April | 0.201857E+11 | 0.636051E+10 | 720.00 | 0.195830E+11 | 0.602682E+09 | 0.00 | 1.00 | 24-APR-12:10 | 0.32 | 30-APR-23:13 | 8607.13 | 30-APR-18:00 | 8143.71 | 26-APR-14:10 | 597.94 | 30-APR-15:00 | 3549.36 | 28-APR-12:00 | 0.00 |
May | 0.696666E+10 | 0.257860E+10 | 744.00 | 0.624087E+10 | 0.725796E+09 | 0.00 | 0.57 | 31-MAY-23:03 | 0.25 | 03-MAY-07:00 | 4566.22 | 31-MAY-23:03 | 4129.04 | 31-MAY-23:42 | 643.87 | 16-MAY-15:00 | 1686.46 | 31-MAY-23:15 | 0.00 |
June | 0.120673E+11 | 0.450552E+10 | 720.00 | 0.108756E+11 | 0.119165E+10 | 0.00 | 0.79 | 30-JUN-23:03 | 0.49 | 07-JUN-06:00 | 6628.45 | 30-JUN-23:03 | 5852.14 | 30-JUN-24:00 | 807.41 | 30-JUN-23:03 | 2328.65 | 09-JUN-15:00 | 0.00 |
July | 0.178085E+11 | 0.689535E+10 | 744.00 | 0.163210E+11 | 0.148755E+10 | 0.00 | 1.00 | 31-JUL-23:03 | 0.71 | 03-JUL-06:00 | 8486.44 | 31-JUL-23:03 | 7741.45 | 31-JUL-24:00 | 957.55 | 20-JUL-14:00 | 3279.17 | 21-JUL-12:00 | 0.00 |
August | 0.222375E+11 | 0.851172E+10 | 744.00 | 0.206747E+11 | 0.156275E+10 | 0.00 | 1.00 | 01-AUG-00:05 | 0.35 | 31-AUG-23:23 | 8650.74 | 08-AUG-07:30 | 7978.65 | 07-AUG-02:52 | 973.51 | 30-AUG-20:00 | 3785.18 | 16-AUG-12:00 | 0.00 |
September | 0.738433E+10 | 0.274120E+10 | 720.00 | 0.612294E+10 | 0.126139E+10 | 0.00 | 0.58 | 30-SEP-23:03 | 0.27 | 26-SEP-07:00 | 4954.36 | 30-SEP-23:03 | 3982.74 | 30-SEP-23:47 | 1010.71 | 30-SEP-23:03 | 1586.31 | 30-SEP-23:07 | 0.00 |
October | 0.119099E+11 | 0.409928E+10 | 744.00 | 0.108861E+11 | 0.102379E+10 | 0.00 | 0.73 | 31-OCT-23:12 | 0.45 | 21-OCT-07:00 | 6099.90 | 31-OCT-23:10 | 5763.02 | 31-OCT-23:53 | 844.14 | 07-OCT-10:20 | 1960.49 | 31-OCT-23:23 | 0.00 |
November | 0.154434E+11 | 0.476918E+10 | 720.00 | 0.147172E+11 | 0.726181E+09 | 0.00 | 0.82 | 01-NOV-14:20 | 0.60 | 22-NOV-07:00 | 6815.71 | 01-NOV-16:00 | 6190.76 | 05-NOV-16:55 | 672.58 | 01-NOV-15:00 | 2470.66 | 01-NOV-14:00 | 0.00 |
December | 0.196794E+11 | 0.536597E+10 | 744.00 | 0.191074E+11 | 0.571964E+09 | 0.00 | 0.95 | 05-DEC-17:00 | 0.71 | 31-DEC-07:50 | 8369.42 | 05-DEC-17:00 | 7794.34 | 06-DEC-17:00 | 577.06 | 05-DEC-17:00 | 2618.48 | 10-DEC-12:53 | 0.00 |
Annual Sum or Average | 0.162104E+12 | 0.539490E+11 | 8760.00 | 0.151726E+12 | 0.103780E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.421098E+10 | 0.118222E+10 | 672.00 | 0.389453E+10 | 0.316456E+09 | 0.00 | 0.31 | 0.09 | 2564.21 | 2255.68 | 419.38 | 809.78 | 0.00 | ||||||
Maximum of Months | 0.222375E+11 | 0.851172E+10 | 744.00 | 0.206747E+11 | 0.156275E+10 | 0.00 | 1.00 | 0.71 | 8650.74 | 8143.71 | 1010.71 | 3785.18 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.94 | 0.00 | 112.94 | 121.26 | 276.79 | 0.00 | 0.00 | 0.00 |
February | 129.46 | 0.00 | 129.46 | 169.27 | 237.21 | 0.00 | 0.00 | 0.00 |
March | 148.70 | 0.00 | 148.70 | 247.35 | 179.56 | 0.00 | 0.00 | 0.00 |
April | 167.53 | 0.35 | 167.19 | 358.68 | 113.42 | 0.00 | 0.00 | 0.00 |
May | 188.58 | 5.53 | 183.04 | 540.01 | 33.51 | 0.00 | 0.00 | 0.00 |
June | 201.91 | 11.21 | 190.70 | 621.13 | 11.61 | 0.00 | 0.00 | 0.00 |
July | 185.27 | 5.34 | 179.93 | 683.14 | 0.78 | 0.00 | 0.00 | 0.00 |
August | 172.47 | 1.43 | 171.04 | 667.14 | 0.31 | 0.00 | 0.00 | 0.00 |
September | 157.10 | 0.02 | 157.08 | 505.94 | 15.01 | 0.00 | 0.00 | 0.00 |
October | 139.27 | 0.00 | 139.27 | 361.88 | 58.59 | 0.00 | 0.00 | 0.00 |
November | 119.56 | 0.00 | 119.56 | 231.19 | 134.82 | 0.00 | 0.00 | 0.00 |
December | 105.41 | 0.00 | 105.41 | 134.63 | 233.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 152.44 | 2.00 | 150.44 | 388.13 | 107.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 105.41 | 0.00 | 105.41 | 121.26 | 0.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.91 | 11.21 | 190.70 | 683.14 | 276.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.94 | 0.00 | 112.94 | 121.26 | 276.79 | 0.00 | 0.00 | 0.00 |
February | 129.46 | 0.00 | 129.46 | 169.27 | 237.21 | 0.00 | 0.00 | 0.00 |
March | 148.70 | 0.00 | 148.70 | 247.35 | 179.56 | 0.00 | 0.00 | 0.00 |
April | 167.53 | 0.35 | 167.19 | 358.68 | 113.42 | 0.00 | 0.00 | 0.00 |
May | 188.57 | 5.53 | 183.04 | 540.01 | 33.51 | 0.00 | 0.00 | 0.00 |
June | 201.91 | 11.21 | 190.70 | 621.13 | 11.61 | 0.00 | 0.00 | 0.00 |
July | 185.27 | 5.34 | 179.93 | 683.14 | 0.78 | 0.00 | 0.00 | 0.00 |
August | 172.47 | 1.43 | 171.04 | 667.14 | 0.31 | 0.00 | 0.00 | 0.00 |
September | 157.10 | 0.02 | 157.08 | 505.94 | 15.01 | 0.00 | 0.00 | 0.00 |
October | 139.27 | 0.00 | 139.27 | 361.88 | 58.59 | 0.00 | 0.00 | 0.00 |
November | 119.56 | 0.00 | 119.56 | 231.19 | 134.82 | 0.00 | 0.00 | 0.00 |
December | 105.41 | 0.00 | 105.41 | 134.63 | 233.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 152.44 | 2.00 | 150.44 | 388.13 | 107.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 105.41 | 0.00 | 105.41 | 121.26 | 0.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.91 | 11.21 | 190.70 | 683.14 | 276.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.94 | 0.00 | 112.94 | 121.26 | 276.79 | 0.00 | 0.00 | 0.00 |
February | 129.46 | 0.00 | 129.46 | 169.27 | 237.21 | 0.00 | 0.00 | 0.00 |
March | 148.70 | 0.00 | 148.70 | 247.35 | 179.56 | 0.00 | 0.00 | 0.00 |
April | 167.53 | 0.35 | 167.19 | 358.68 | 113.42 | 0.00 | 0.00 | 0.00 |
May | 188.58 | 5.53 | 183.04 | 540.01 | 33.51 | 0.00 | 0.00 | 0.00 |
June | 201.91 | 11.21 | 190.70 | 621.13 | 11.61 | 0.00 | 0.00 | 0.00 |
July | 185.27 | 5.34 | 179.93 | 683.14 | 0.78 | 0.00 | 0.00 | 0.00 |
August | 172.47 | 1.43 | 171.04 | 667.14 | 0.31 | 0.00 | 0.00 | 0.00 |
September | 157.10 | 0.02 | 157.08 | 505.94 | 15.01 | 0.00 | 0.00 | 0.00 |
October | 139.27 | 0.00 | 139.27 | 361.88 | 58.59 | 0.00 | 0.00 | 0.00 |
November | 119.56 | 0.00 | 119.56 | 231.19 | 134.82 | 0.00 | 0.00 | 0.00 |
December | 105.41 | 0.00 | 105.41 | 134.63 | 233.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 152.44 | 2.00 | 150.44 | 388.13 | 107.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 105.41 | 0.00 | 105.41 | 121.26 | 0.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.91 | 11.21 | 190.70 | 683.14 | 276.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.94 | 0.00 | 112.94 | 121.26 | 276.79 | 0.00 | 0.00 | 0.00 |
February | 129.46 | 0.00 | 129.46 | 169.27 | 237.21 | 0.00 | 0.00 | 0.00 |
March | 148.70 | 0.00 | 148.70 | 247.35 | 179.56 | 0.00 | 0.00 | 0.00 |
April | 167.53 | 0.35 | 167.19 | 358.68 | 113.42 | 0.00 | 0.00 | 0.00 |
May | 188.57 | 5.53 | 183.04 | 540.01 | 33.51 | 0.00 | 0.00 | 0.00 |
June | 201.91 | 11.21 | 190.70 | 621.13 | 11.61 | 0.00 | 0.00 | 0.00 |
July | 185.27 | 5.34 | 179.93 | 683.14 | 0.78 | 0.00 | 0.00 | 0.00 |
August | 172.47 | 1.43 | 171.04 | 667.14 | 0.31 | 0.00 | 0.00 | 0.00 |
September | 157.10 | 0.02 | 157.08 | 505.94 | 15.01 | 0.00 | 0.00 | 0.00 |
October | 139.27 | 0.00 | 139.27 | 361.88 | 58.59 | 0.00 | 0.00 | 0.00 |
November | 119.56 | 0.00 | 119.56 | 231.19 | 134.82 | 0.00 | 0.00 | 0.00 |
December | 105.41 | 0.00 | 105.41 | 134.63 | 233.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 152.44 | 2.00 | 150.44 | 388.13 | 107.31 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 105.41 | 0.00 | 105.41 | 121.26 | 0.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.91 | 11.21 | 190.70 | 683.14 | 276.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 112.93 | 0.00 | 112.93 | 121.25 | 276.78 | 0.00 | 0.00 | 0.00 |
February | 129.45 | 0.00 | 129.45 | 169.27 | 237.20 | 0.00 | 0.00 | 0.00 |
March | 148.69 | 0.00 | 148.69 | 247.34 | 179.55 | 0.00 | 0.00 | 0.00 |
April | 167.53 | 0.35 | 167.18 | 358.67 | 113.41 | 0.00 | 0.00 | 0.00 |
May | 188.57 | 5.53 | 183.04 | 539.99 | 33.51 | 0.00 | 0.00 | 0.00 |
June | 201.90 | 11.21 | 190.69 | 621.10 | 11.61 | 0.00 | 0.00 | 0.00 |
July | 185.26 | 5.34 | 179.92 | 683.12 | 0.78 | 0.00 | 0.00 | 0.00 |
August | 172.46 | 1.43 | 171.04 | 667.12 | 0.31 | 0.00 | 0.00 | 0.00 |
September | 157.10 | 0.02 | 157.08 | 505.92 | 15.01 | 0.00 | 0.00 | 0.00 |
October | 139.26 | 0.00 | 139.26 | 361.86 | 58.59 | 0.00 | 0.00 | 0.00 |
November | 119.55 | 0.00 | 119.55 | 231.18 | 134.81 | 0.00 | 0.00 | 0.00 |
December | 105.41 | 0.00 | 105.41 | 134.62 | 233.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 152.43 | 2.00 | 150.43 | 388.11 | 107.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 105.41 | 0.00 | 105.41 | 121.25 | 0.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.90 | 11.21 | 190.69 | 683.12 | 276.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 227.00 | 68.68 | 158.32 | 303.46 | 282.95 | 0.00 | 0.00 | 0.00 |
February | 247.37 | 67.04 | 180.33 | 369.32 | 242.79 | 0.00 | 0.00 | 0.00 |
March | 273.25 | 67.35 | 205.90 | 473.83 | 182.90 | 0.00 | 0.00 | 0.00 |
April | 332.69 | 96.94 | 235.76 | 677.41 | 114.29 | 0.00 | 0.00 | 0.00 |
May | 371.79 | 118.46 | 253.34 | 903.43 | 35.59 | 0.00 | 0.00 | 0.00 |
June | 364.11 | 111.35 | 252.76 | 950.18 | 10.91 | 0.00 | 0.00 | 0.00 |
July | 339.84 | 97.98 | 241.87 | 1015.34 | 0.56 | 0.00 | 0.00 | 0.00 |
August | 348.00 | 106.80 | 241.19 | 1045.07 | 0.20 | 0.00 | 0.00 | 0.00 |
September | 327.16 | 101.12 | 226.04 | 851.27 | 15.08 | 0.00 | 0.00 | 0.00 |
October | 296.86 | 96.98 | 199.88 | 669.84 | 59.31 | 0.00 | 0.00 | 0.00 |
November | 248.77 | 78.80 | 169.97 | 470.68 | 135.53 | 0.00 | 0.00 | 0.00 |
December | 201.36 | 55.24 | 146.11 | 297.83 | 231.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 298.38 | 88.98 | 209.40 | 670.69 | 108.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 201.36 | 55.24 | 146.11 | 297.83 | 0.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 371.79 | 118.46 | 253.34 | 1045.07 | 282.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 227.00 | 68.68 | 158.32 | 303.46 | 282.95 | 0.00 | 0.00 | 0.00 |
February | 247.37 | 67.04 | 180.33 | 369.32 | 242.79 | 0.00 | 0.00 | 0.00 |
March | 273.25 | 67.35 | 205.90 | 473.83 | 182.90 | 0.00 | 0.00 | 0.00 |
April | 332.69 | 96.94 | 235.76 | 677.41 | 114.29 | 0.00 | 0.00 | 0.00 |
May | 371.79 | 118.46 | 253.34 | 903.43 | 35.59 | 0.00 | 0.00 | 0.00 |
June | 364.11 | 111.35 | 252.76 | 950.18 | 10.91 | 0.00 | 0.00 | 0.00 |
July | 339.84 | 97.98 | 241.87 | 1015.34 | 0.56 | 0.00 | 0.00 | 0.00 |
August | 348.00 | 106.80 | 241.19 | 1045.07 | 0.20 | 0.00 | 0.00 | 0.00 |
September | 327.16 | 101.12 | 226.04 | 851.27 | 15.08 | 0.00 | 0.00 | 0.00 |
October | 296.86 | 96.98 | 199.88 | 669.84 | 59.31 | 0.00 | 0.00 | 0.00 |
November | 248.77 | 78.80 | 169.97 | 470.68 | 135.53 | 0.00 | 0.00 | 0.00 |
December | 201.36 | 55.24 | 146.11 | 297.83 | 231.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 298.38 | 88.98 | 209.40 | 670.69 | 108.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 201.36 | 55.24 | 146.11 | 297.83 | 0.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 371.79 | 118.46 | 253.34 | 1045.07 | 282.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 226.99 | 68.68 | 158.32 | 303.46 | 282.94 | 0.00 | 0.00 | 0.00 |
February | 247.37 | 67.04 | 180.33 | 369.32 | 242.79 | 0.00 | 0.00 | 0.00 |
March | 273.25 | 67.34 | 205.90 | 473.82 | 182.90 | 0.00 | 0.00 | 0.00 |
April | 332.69 | 96.93 | 235.75 | 677.40 | 114.29 | 0.00 | 0.00 | 0.00 |
May | 371.79 | 118.45 | 253.33 | 903.41 | 35.59 | 0.00 | 0.00 | 0.00 |
June | 364.11 | 111.35 | 252.76 | 950.16 | 10.91 | 0.00 | 0.00 | 0.00 |
July | 339.84 | 97.97 | 241.86 | 1015.32 | 0.56 | 0.00 | 0.00 | 0.00 |
August | 347.99 | 106.80 | 241.19 | 1045.05 | 0.20 | 0.00 | 0.00 | 0.00 |
September | 327.15 | 101.12 | 226.03 | 851.25 | 15.08 | 0.00 | 0.00 | 0.00 |
October | 296.86 | 96.98 | 199.87 | 669.83 | 59.30 | 0.00 | 0.00 | 0.00 |
November | 248.77 | 78.80 | 169.97 | 470.67 | 135.53 | 0.00 | 0.00 | 0.00 |
December | 201.35 | 55.24 | 146.11 | 297.83 | 231.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 298.38 | 88.98 | 209.39 | 670.67 | 108.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 201.35 | 55.24 | 146.11 | 297.83 | 0.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 371.79 | 118.45 | 253.33 | 1045.05 | 282.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 365.00 | 171.60 | 193.40 | 570.62 | 266.45 | 0.00 | 0.00 | 0.00 |
February | 342.75 | 140.20 | 202.55 | 569.49 | 233.61 | 0.00 | 0.00 | 0.00 |
March | 282.10 | 76.59 | 205.51 | 523.62 | 182.10 | 0.00 | 0.00 | 0.00 |
April | 221.75 | 23.51 | 198.24 | 484.73 | 115.05 | 0.00 | 0.00 | 0.00 |
May | 187.84 | 2.88 | 184.96 | 541.97 | 31.93 | 0.00 | 0.00 | 0.00 |
June | 176.90 | 0.22 | 176.68 | 570.39 | 8.27 | 0.00 | 0.00 | 0.00 |
July | 176.90 | 1.50 | 175.39 | 667.15 | 0.39 | 0.00 | 0.00 | 0.00 |
August | 205.19 | 14.54 | 190.65 | 746.26 | 0.19 | 0.00 | 0.00 | 0.00 |
September | 270.54 | 62.00 | 208.54 | 752.92 | 14.24 | 0.00 | 0.00 | 0.00 |
October | 354.19 | 140.81 | 213.38 | 791.93 | 58.35 | 0.00 | 0.00 | 0.00 |
November | 390.75 | 188.37 | 202.38 | 743.27 | 135.83 | 0.00 | 0.00 | 0.00 |
December | 362.73 | 179.18 | 183.55 | 602.34 | 227.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 277.66 | 83.15 | 194.52 | 630.81 | 105.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 176.90 | 0.22 | 175.39 | 484.73 | 0.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 390.75 | 188.37 | 213.38 | 791.93 | 266.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 365.00 | 171.60 | 193.39 | 570.62 | 266.45 | 0.00 | 0.00 | 0.00 |
February | 342.75 | 140.20 | 202.55 | 569.49 | 233.61 | 0.00 | 0.00 | 0.00 |
March | 282.10 | 76.59 | 205.51 | 523.62 | 182.10 | 0.00 | 0.00 | 0.00 |
April | 221.75 | 23.51 | 198.24 | 484.73 | 115.05 | 0.00 | 0.00 | 0.00 |
May | 187.84 | 2.88 | 184.96 | 541.97 | 31.93 | 0.00 | 0.00 | 0.00 |
June | 176.90 | 0.22 | 176.68 | 570.39 | 8.27 | 0.00 | 0.00 | 0.00 |
July | 176.90 | 1.50 | 175.39 | 667.15 | 0.39 | 0.00 | 0.00 | 0.00 |
August | 205.19 | 14.54 | 190.65 | 746.26 | 0.19 | 0.00 | 0.00 | 0.00 |
September | 270.54 | 62.00 | 208.54 | 752.92 | 14.24 | 0.00 | 0.00 | 0.00 |
October | 354.19 | 140.81 | 213.38 | 791.93 | 58.35 | 0.00 | 0.00 | 0.00 |
November | 390.75 | 188.37 | 202.38 | 743.27 | 135.83 | 0.00 | 0.00 | 0.00 |
December | 362.73 | 179.18 | 183.55 | 602.34 | 227.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 277.66 | 83.15 | 194.52 | 630.81 | 105.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 176.90 | 0.22 | 175.39 | 484.73 | 0.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 390.75 | 188.37 | 213.38 | 791.93 | 266.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 365.00 | 171.60 | 193.40 | 570.62 | 266.45 | 0.00 | 0.00 | 0.00 |
February | 342.75 | 140.20 | 202.55 | 569.49 | 233.61 | 0.00 | 0.00 | 0.00 |
March | 282.10 | 76.59 | 205.51 | 523.62 | 182.10 | 0.00 | 0.00 | 0.00 |
April | 221.75 | 23.51 | 198.24 | 484.73 | 115.05 | 0.00 | 0.00 | 0.00 |
May | 187.84 | 2.88 | 184.96 | 541.97 | 31.93 | 0.00 | 0.00 | 0.00 |
June | 176.90 | 0.22 | 176.68 | 570.39 | 8.27 | 0.00 | 0.00 | 0.00 |
July | 176.90 | 1.50 | 175.39 | 667.15 | 0.39 | 0.00 | 0.00 | 0.00 |
August | 205.19 | 14.54 | 190.65 | 746.26 | 0.19 | 0.00 | 0.00 | 0.00 |
September | 270.54 | 62.00 | 208.54 | 752.92 | 14.24 | 0.00 | 0.00 | 0.00 |
October | 354.19 | 140.81 | 213.38 | 791.93 | 58.35 | 0.00 | 0.00 | 0.00 |
November | 390.75 | 188.37 | 202.38 | 743.27 | 135.83 | 0.00 | 0.00 | 0.00 |
December | 362.73 | 179.18 | 183.55 | 602.34 | 227.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 277.66 | 83.15 | 194.52 | 630.81 | 105.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 176.90 | 0.22 | 175.39 | 484.73 | 0.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 390.75 | 188.37 | 213.38 | 791.93 | 266.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 365.00 | 171.60 | 193.39 | 570.62 | 266.45 | 0.00 | 0.00 | 0.00 |
February | 342.75 | 140.20 | 202.55 | 569.49 | 233.61 | 0.00 | 0.00 | 0.00 |
March | 282.10 | 76.59 | 205.51 | 523.62 | 182.10 | 0.00 | 0.00 | 0.00 |
April | 221.75 | 23.51 | 198.24 | 484.73 | 115.05 | 0.00 | 0.00 | 0.00 |
May | 187.84 | 2.88 | 184.96 | 541.97 | 31.93 | 0.00 | 0.00 | 0.00 |
June | 176.90 | 0.22 | 176.68 | 570.39 | 8.27 | 0.00 | 0.00 | 0.00 |
July | 176.90 | 1.50 | 175.39 | 667.15 | 0.39 | 0.00 | 0.00 | 0.00 |
August | 205.19 | 14.54 | 190.65 | 746.26 | 0.19 | 0.00 | 0.00 | 0.00 |
September | 270.54 | 62.00 | 208.54 | 752.92 | 14.24 | 0.00 | 0.00 | 0.00 |
October | 354.19 | 140.81 | 213.38 | 791.93 | 58.35 | 0.00 | 0.00 | 0.00 |
November | 390.75 | 188.37 | 202.38 | 743.27 | 135.83 | 0.00 | 0.00 | 0.00 |
December | 362.73 | 179.18 | 183.55 | 602.34 | 227.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 277.66 | 83.15 | 194.52 | 630.81 | 105.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 176.90 | 0.22 | 175.39 | 484.73 | 0.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 390.75 | 188.37 | 213.38 | 791.93 | 266.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 364.98 | 171.59 | 193.39 | 570.60 | 266.44 | 0.00 | 0.00 | 0.00 |
February | 342.73 | 140.19 | 202.54 | 569.46 | 233.60 | 0.00 | 0.00 | 0.00 |
March | 282.08 | 76.58 | 205.50 | 523.60 | 182.09 | 0.00 | 0.00 | 0.00 |
April | 221.74 | 23.51 | 198.23 | 484.71 | 115.05 | 0.00 | 0.00 | 0.00 |
May | 187.83 | 2.88 | 184.96 | 541.95 | 31.93 | 0.00 | 0.00 | 0.00 |
June | 176.90 | 0.22 | 176.68 | 570.37 | 8.27 | 0.00 | 0.00 | 0.00 |
July | 176.89 | 1.50 | 175.39 | 667.12 | 0.39 | 0.00 | 0.00 | 0.00 |
August | 205.18 | 14.54 | 190.64 | 746.23 | 0.19 | 0.00 | 0.00 | 0.00 |
September | 270.53 | 62.00 | 208.53 | 752.89 | 14.24 | 0.00 | 0.00 | 0.00 |
October | 354.18 | 140.81 | 213.37 | 791.90 | 58.35 | 0.00 | 0.00 | 0.00 |
November | 390.73 | 188.36 | 202.37 | 743.24 | 135.83 | 0.00 | 0.00 | 0.00 |
December | 362.72 | 179.17 | 183.55 | 602.32 | 227.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 277.65 | 83.14 | 194.51 | 630.78 | 105.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 176.89 | 0.22 | 175.39 | 484.71 | 0.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 390.73 | 188.36 | 213.37 | 791.90 | 266.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 222.61 | 63.94 | 158.68 | 304.69 | 333.37 | 0.00 | 0.00 | 0.00 |
February | 254.20 | 72.49 | 181.71 | 382.28 | 296.53 | 0.00 | 0.00 | 0.00 |
March | 301.11 | 89.14 | 211.96 | 515.46 | 236.17 | 0.00 | 0.00 | 0.00 |
April | 329.06 | 92.45 | 236.61 | 652.39 | 160.75 | 0.00 | 0.00 | 0.00 |
May | 358.18 | 107.22 | 250.96 | 881.88 | 40.74 | 0.00 | 0.00 | 0.00 |
June | 370.15 | 116.68 | 253.47 | 954.66 | 14.17 | 0.00 | 0.00 | 0.00 |
July | 339.57 | 97.14 | 242.43 | 994.47 | 1.42 | 0.00 | 0.00 | 0.00 |
August | 348.36 | 105.92 | 242.44 | 1012.76 | 0.91 | 0.00 | 0.00 | 0.00 |
September | 331.38 | 104.11 | 227.27 | 862.83 | 16.05 | 0.00 | 0.00 | 0.00 |
October | 294.50 | 95.13 | 199.37 | 665.44 | 70.64 | 0.00 | 0.00 | 0.00 |
November | 253.09 | 82.77 | 170.32 | 476.61 | 178.35 | 0.00 | 0.00 | 0.00 |
December | 211.87 | 64.05 | 147.83 | 311.44 | 310.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 301.34 | 90.98 | 210.36 | 669.51 | 137.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 211.87 | 63.94 | 147.83 | 304.69 | 0.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 370.15 | 116.68 | 253.47 | 1012.76 | 333.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 222.61 | 63.94 | 158.68 | 304.69 | 333.37 | 0.00 | 0.00 | 0.00 |
February | 254.20 | 72.49 | 181.71 | 382.28 | 296.53 | 0.00 | 0.00 | 0.00 |
March | 301.11 | 89.14 | 211.96 | 515.46 | 236.17 | 0.00 | 0.00 | 0.00 |
April | 329.06 | 92.45 | 236.61 | 652.39 | 160.75 | 0.00 | 0.00 | 0.00 |
May | 358.18 | 107.22 | 250.96 | 881.88 | 40.74 | 0.00 | 0.00 | 0.00 |
June | 370.15 | 116.68 | 253.47 | 954.66 | 14.17 | 0.00 | 0.00 | 0.00 |
July | 339.57 | 97.14 | 242.43 | 994.47 | 1.42 | 0.00 | 0.00 | 0.00 |
August | 348.36 | 105.92 | 242.44 | 1012.76 | 0.91 | 0.00 | 0.00 | 0.00 |
September | 331.38 | 104.11 | 227.27 | 862.83 | 16.05 | 0.00 | 0.00 | 0.00 |
October | 294.50 | 95.13 | 199.37 | 665.44 | 70.64 | 0.00 | 0.00 | 0.00 |
November | 253.09 | 82.77 | 170.32 | 476.61 | 178.35 | 0.00 | 0.00 | 0.00 |
December | 211.87 | 64.05 | 147.83 | 311.44 | 310.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 301.34 | 90.98 | 210.36 | 669.51 | 137.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 211.87 | 63.94 | 147.83 | 304.69 | 0.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 370.15 | 116.68 | 253.47 | 1012.76 | 333.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 222.61 | 63.93 | 158.67 | 304.68 | 333.37 | 0.00 | 0.00 | 0.00 |
February | 254.19 | 72.49 | 181.71 | 382.28 | 296.52 | 0.00 | 0.00 | 0.00 |
March | 301.10 | 89.14 | 211.96 | 515.45 | 236.16 | 0.00 | 0.00 | 0.00 |
April | 329.05 | 92.45 | 236.61 | 652.38 | 160.75 | 0.00 | 0.00 | 0.00 |
May | 358.17 | 107.22 | 250.96 | 881.86 | 40.74 | 0.00 | 0.00 | 0.00 |
June | 370.14 | 116.68 | 253.46 | 954.65 | 14.17 | 0.00 | 0.00 | 0.00 |
July | 339.56 | 97.14 | 242.42 | 994.45 | 1.42 | 0.00 | 0.00 | 0.00 |
August | 348.36 | 105.91 | 242.44 | 1012.75 | 0.91 | 0.00 | 0.00 | 0.00 |
September | 331.38 | 104.11 | 227.27 | 862.82 | 16.05 | 0.00 | 0.00 | 0.00 |
October | 294.50 | 95.13 | 199.37 | 665.43 | 70.64 | 0.00 | 0.00 | 0.00 |
November | 253.08 | 82.77 | 170.32 | 476.61 | 178.35 | 0.00 | 0.00 | 0.00 |
December | 211.87 | 64.04 | 147.83 | 311.43 | 310.97 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 301.34 | 90.98 | 210.36 | 669.49 | 137.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 211.87 | 63.93 | 147.83 | 304.68 | 0.91 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 370.14 | 116.68 | 253.46 | 1012.75 | 333.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 564.67 | 0.00 | 564.67 | 660.60 | 1221.83 | 0.00 | 0.00 | 0.00 |
February | 647.28 | 0.00 | 647.28 | 899.79 | 1036.62 | 0.00 | 0.00 | 0.00 |
March | 743.48 | 0.00 | 743.48 | 1280.57 | 808.88 | 0.00 | 0.00 | 0.00 |
April | 837.66 | 1.73 | 835.94 | 1853.68 | 516.57 | 0.00 | 0.00 | 0.00 |
May | 942.86 | 27.65 | 915.21 | 2814.77 | 126.50 | 0.00 | 0.00 | 0.00 |
June | 1009.51 | 56.05 | 953.47 | 3251.03 | 29.57 | 0.00 | 0.00 | 0.00 |
July | 926.33 | 26.69 | 899.64 | 3623.53 | 0.57 | 0.00 | 0.00 | 0.00 |
August | 862.33 | 7.13 | 855.20 | 3573.85 | 0.06 | 0.00 | 0.00 | 0.00 |
September | 785.51 | 0.09 | 785.42 | 2703.35 | 42.77 | 0.00 | 0.00 | 0.00 |
October | 696.33 | 0.00 | 696.33 | 1935.35 | 208.29 | 0.00 | 0.00 | 0.00 |
November | 597.79 | 0.00 | 597.79 | 1227.62 | 582.74 | 0.00 | 0.00 | 0.00 |
December | 527.05 | 0.00 | 527.05 | 733.00 | 1012.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 762.17 | 9.98 | 752.19 | 2053.52 | 462.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 527.05 | 0.00 | 527.05 | 660.60 | 0.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1009.51 | 56.05 | 953.47 | 3623.53 | 1221.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 680.98 | 206.03 | 474.95 | 932.42 | 779.44 | 0.00 | 0.00 | 0.00 |
February | 742.12 | 201.12 | 541.00 | 1124.80 | 668.50 | 0.00 | 0.00 | 0.00 |
March | 819.74 | 202.04 | 617.71 | 1428.28 | 526.04 | 0.00 | 0.00 | 0.00 |
April | 998.07 | 290.80 | 707.27 | 2038.52 | 343.57 | 0.00 | 0.00 | 0.00 |
May | 1115.37 | 355.36 | 760.01 | 2765.89 | 81.41 | 0.00 | 0.00 | 0.00 |
June | 1092.33 | 334.05 | 758.29 | 2926.75 | 15.92 | 0.00 | 0.00 | 0.00 |
July | 1019.52 | 293.93 | 725.60 | 3159.66 | 0.22 | 0.00 | 0.00 | 0.00 |
August | 1043.98 | 320.41 | 723.57 | 3263.23 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 981.46 | 303.36 | 678.10 | 2649.49 | 25.63 | 0.00 | 0.00 | 0.00 |
October | 890.58 | 290.95 | 599.62 | 2066.97 | 132.00 | 0.00 | 0.00 | 0.00 |
November | 746.31 | 236.39 | 509.91 | 1432.15 | 378.35 | 0.00 | 0.00 | 0.00 |
December | 604.06 | 165.73 | 438.33 | 912.06 | 647.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 895.14 | 266.95 | 628.19 | 2063.80 | 298.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 604.06 | 165.73 | 438.33 | 912.06 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1115.37 | 355.36 | 760.01 | 3263.23 | 779.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1824.96 | 858.00 | 966.96 | 2838.25 | 1287.24 | 0.00 | 0.00 | 0.00 |
February | 1713.71 | 700.98 | 1012.73 | 2841.41 | 1106.98 | 0.00 | 0.00 | 0.00 |
March | 1410.46 | 382.93 | 1027.53 | 2622.95 | 869.79 | 0.00 | 0.00 | 0.00 |
April | 1108.73 | 117.55 | 991.18 | 2456.84 | 546.62 | 0.00 | 0.00 | 0.00 |
May | 939.19 | 14.38 | 924.81 | 2811.05 | 125.39 | 0.00 | 0.00 | 0.00 |
June | 884.50 | 1.09 | 883.41 | 3000.18 | 20.15 | 0.00 | 0.00 | 0.00 |
July | 884.48 | 7.52 | 876.96 | 3525.36 | 0.12 | 0.00 | 0.00 | 0.00 |
August | 1025.92 | 72.69 | 953.23 | 3934.77 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 1352.69 | 310.01 | 1042.68 | 3878.91 | 48.35 | 0.00 | 0.00 | 0.00 |
October | 1770.94 | 704.05 | 1066.89 | 4013.67 | 241.27 | 0.00 | 0.00 | 0.00 |
November | 1953.71 | 941.83 | 1011.87 | 3719.62 | 645.70 | 0.00 | 0.00 | 0.00 |
December | 1813.63 | 895.88 | 917.75 | 3009.99 | 1088.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1388.30 | 415.73 | 972.57 | 3223.74 | 495.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 884.48 | 1.09 | 876.96 | 2456.84 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1953.71 | 941.83 | 1066.89 | 4013.67 | 1287.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 667.83 | 191.81 | 476.02 | 958.94 | 860.68 | 0.00 | 0.00 | 0.00 |
February | 762.59 | 217.46 | 545.13 | 1196.71 | 740.52 | 0.00 | 0.00 | 0.00 |
March | 903.31 | 267.43 | 635.88 | 1593.34 | 596.67 | 0.00 | 0.00 | 0.00 |
April | 987.16 | 277.34 | 709.82 | 2015.70 | 403.31 | 0.00 | 0.00 | 0.00 |
May | 1074.52 | 321.65 | 752.88 | 2686.61 | 105.63 | 0.00 | 0.00 | 0.00 |
June | 1110.43 | 350.04 | 760.39 | 2947.21 | 24.03 | 0.00 | 0.00 | 0.00 |
July | 1018.70 | 291.43 | 727.27 | 3120.27 | 0.59 | 0.00 | 0.00 | 0.00 |
August | 1045.07 | 317.75 | 727.33 | 3207.32 | 0.20 | 0.00 | 0.00 | 0.00 |
September | 994.13 | 312.33 | 681.81 | 2648.92 | 37.59 | 0.00 | 0.00 | 0.00 |
October | 883.49 | 285.39 | 598.10 | 2053.93 | 172.27 | 0.00 | 0.00 | 0.00 |
November | 759.25 | 248.30 | 510.95 | 1483.76 | 440.31 | 0.00 | 0.00 | 0.00 |
December | 635.61 | 192.13 | 443.48 | 1005.81 | 733.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 904.02 | 272.94 | 631.08 | 2081.61 | 340.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 635.61 | 191.81 | 443.48 | 958.94 | 0.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1110.43 | 350.04 | 760.39 | 3207.32 | 860.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 564.67 | 0.00 | 564.67 | 689.77 | 1137.71 | 0.00 | 0.00 | 0.00 |
February | 647.28 | 0.00 | 647.28 | 914.69 | 983.69 | 0.00 | 0.00 | 0.00 |
March | 743.48 | 0.00 | 743.48 | 1279.54 | 781.53 | 0.00 | 0.00 | 0.00 |
April | 837.66 | 1.73 | 835.94 | 1837.35 | 514.16 | 0.00 | 0.00 | 0.00 |
May | 942.86 | 27.65 | 915.21 | 2784.61 | 129.51 | 0.00 | 0.00 | 0.00 |
June | 1009.51 | 56.05 | 953.47 | 3217.83 | 30.95 | 0.00 | 0.00 | 0.00 |
July | 926.33 | 26.69 | 899.64 | 3580.82 | 0.81 | 0.00 | 0.00 | 0.00 |
August | 862.33 | 7.13 | 855.20 | 3535.04 | 0.09 | 0.00 | 0.00 | 0.00 |
September | 785.51 | 0.09 | 785.42 | 2672.45 | 43.92 | 0.00 | 0.00 | 0.00 |
October | 696.33 | 0.00 | 696.33 | 1916.29 | 209.62 | 0.00 | 0.00 | 0.00 |
November | 597.79 | 0.00 | 597.79 | 1225.10 | 564.93 | 0.00 | 0.00 | 0.00 |
December | 527.05 | 0.00 | 527.05 | 752.61 | 952.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 762.17 | 9.98 | 752.19 | 2040.80 | 443.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 527.05 | 0.00 | 527.05 | 689.77 | 0.09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1009.51 | 56.05 | 953.47 | 3580.82 | 1137.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 680.98 | 206.03 | 474.95 | 952.22 | 737.72 | 0.00 | 0.00 | 0.00 |
February | 742.12 | 201.12 | 541.00 | 1132.46 | 643.08 | 0.00 | 0.00 | 0.00 |
March | 819.74 | 202.04 | 617.71 | 1425.45 | 513.35 | 0.00 | 0.00 | 0.00 |
April | 998.07 | 290.80 | 707.27 | 2026.14 | 343.86 | 0.00 | 0.00 | 0.00 |
May | 1115.37 | 355.36 | 760.01 | 2742.10 | 84.04 | 0.00 | 0.00 | 0.00 |
June | 1092.33 | 334.05 | 758.29 | 2899.92 | 17.12 | 0.00 | 0.00 | 0.00 |
July | 1019.52 | 293.93 | 725.60 | 3126.18 | 0.36 | 0.00 | 0.00 | 0.00 |
August | 1043.98 | 320.41 | 723.57 | 3232.13 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 981.46 | 303.36 | 678.10 | 2624.25 | 26.65 | 0.00 | 0.00 | 0.00 |
October | 890.58 | 290.95 | 599.62 | 2050.97 | 133.78 | 0.00 | 0.00 | 0.00 |
November | 746.31 | 236.39 | 509.91 | 1427.87 | 370.50 | 0.00 | 0.00 | 0.00 |
December | 604.06 | 165.73 | 438.33 | 924.28 | 618.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 895.14 | 266.95 | 628.19 | 2052.35 | 288.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 604.06 | 165.73 | 438.33 | 924.28 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1115.37 | 355.36 | 760.01 | 3232.13 | 737.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1824.96 | 858.00 | 966.96 | 2855.83 | 1220.00 | 0.00 | 0.00 | 0.00 |
February | 1713.71 | 700.98 | 1012.73 | 2844.65 | 1062.82 | 0.00 | 0.00 | 0.00 |
March | 1410.46 | 382.93 | 1027.53 | 2614.37 | 845.24 | 0.00 | 0.00 | 0.00 |
April | 1108.73 | 117.55 | 991.18 | 2439.00 | 543.18 | 0.00 | 0.00 | 0.00 |
May | 939.19 | 14.38 | 924.81 | 2779.86 | 127.60 | 0.00 | 0.00 | 0.00 |
June | 884.50 | 1.09 | 883.41 | 2966.31 | 20.61 | 0.00 | 0.00 | 0.00 |
July | 884.48 | 7.52 | 876.96 | 3480.82 | 0.21 | 0.00 | 0.00 | 0.00 |
August | 1025.92 | 72.69 | 953.23 | 3894.58 | 0.05 | 0.00 | 0.00 | 0.00 |
September | 1352.69 | 310.01 | 1042.68 | 3845.15 | 49.25 | 0.00 | 0.00 | 0.00 |
October | 1770.94 | 704.05 | 1066.89 | 3988.79 | 242.34 | 0.00 | 0.00 | 0.00 |
November | 1953.71 | 941.83 | 1011.87 | 3707.10 | 631.84 | 0.00 | 0.00 | 0.00 |
December | 1813.63 | 895.88 | 917.75 | 3017.08 | 1043.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1388.30 | 415.73 | 972.57 | 3205.34 | 479.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 884.48 | 1.09 | 876.96 | 2439.00 | 0.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1953.71 | 941.83 | 1066.89 | 3988.79 | 1220.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 667.83 | 191.81 | 476.02 | 969.15 | 815.07 | 0.00 | 0.00 | 0.00 |
February | 762.59 | 217.46 | 545.13 | 1199.63 | 711.02 | 0.00 | 0.00 | 0.00 |
March | 903.31 | 267.43 | 635.88 | 1587.18 | 580.67 | 0.00 | 0.00 | 0.00 |
April | 987.16 | 277.34 | 709.82 | 2002.22 | 399.82 | 0.00 | 0.00 | 0.00 |
May | 1074.52 | 321.65 | 752.88 | 2665.56 | 106.75 | 0.00 | 0.00 | 0.00 |
June | 1110.43 | 350.04 | 760.39 | 2925.46 | 24.42 | 0.00 | 0.00 | 0.00 |
July | 1018.70 | 291.43 | 727.27 | 3093.11 | 0.72 | 0.00 | 0.00 | 0.00 |
August | 1045.07 | 317.75 | 727.33 | 3181.13 | 0.23 | 0.00 | 0.00 | 0.00 |
September | 994.13 | 312.33 | 681.81 | 2628.13 | 38.20 | 0.00 | 0.00 | 0.00 |
October | 883.49 | 285.39 | 598.10 | 2039.92 | 172.17 | 0.00 | 0.00 | 0.00 |
November | 759.25 | 248.30 | 510.95 | 1478.22 | 429.35 | 0.00 | 0.00 | 0.00 |
December | 635.61 | 192.13 | 443.48 | 1012.07 | 700.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 904.02 | 272.94 | 631.08 | 2070.14 | 329.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 635.61 | 191.81 | 443.48 | 969.15 | 0.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1110.43 | 350.04 | 760.39 | 3181.13 | 815.07 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302487E+09 | 0.00 | 0.302487E+09 | 0.324782E+09 | 0.741366E+09 |
February | 0.313182E+09 | 0.00 | 0.313182E+09 | 0.409507E+09 | 0.573864E+09 |
March | 0.398274E+09 | 0.00 | 0.398274E+09 | 0.662493E+09 | 0.480929E+09 |
April | 0.434250E+09 | 894749.10 | 0.433355E+09 | 0.929704E+09 | 0.293980E+09 |
May | 0.505079E+09 | 14813672.07 | 0.490266E+09 | 0.144637E+10 | 89746754.22 |
June | 0.523339E+09 | 29054180.91 | 0.494284E+09 | 0.160997E+10 | 30102941.05 |
July | 0.496221E+09 | 14297338.37 | 0.481924E+09 | 0.182973E+10 | 2098379.80 |
August | 0.461940E+09 | 3820699.13 | 0.458119E+09 | 0.178688E+10 | 834826.37 |
September | 0.407211E+09 | 46662.64 | 0.407164E+09 | 0.131139E+10 | 38914381.39 |
October | 0.373016E+09 | 0.00 | 0.373016E+09 | 0.969256E+09 | 0.156921E+09 |
November | 0.309897E+09 | 0.00 | 0.309897E+09 | 0.599252E+09 | 0.349446E+09 |
December | 0.282332E+09 | 0.00 | 0.282332E+09 | 0.360585E+09 | 0.625794E+09 |
Annual Sum or Average | 0.480723E+10 | 62927302.22 | 0.474430E+10 | 0.122399E+11 | 0.338400E+10 |
Minimum of Months | 0.282332E+09 | 0.00 | 0.282332E+09 | 0.324782E+09 | 834826.37 |
Maximum of Months | 0.523339E+09 | 29054180.91 | 0.494284E+09 | 0.182973E+10 | 0.741366E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302487E+09 | 0.00 | 0.302487E+09 | 0.324782E+09 | 0.741366E+09 |
February | 0.313181E+09 | 0.00 | 0.313181E+09 | 0.409507E+09 | 0.573864E+09 |
March | 0.398273E+09 | 0.00 | 0.398273E+09 | 0.662493E+09 | 0.480929E+09 |
April | 0.434249E+09 | 894748.03 | 0.433355E+09 | 0.929703E+09 | 0.293980E+09 |
May | 0.505079E+09 | 14813654.29 | 0.490265E+09 | 0.144637E+10 | 89746649.19 |
June | 0.523338E+09 | 29054146.04 | 0.494284E+09 | 0.160997E+10 | 30102872.55 |
July | 0.496221E+09 | 14297321.21 | 0.481924E+09 | 0.182973E+10 | 2098368.68 |
August | 0.461939E+09 | 3820694.54 | 0.458119E+09 | 0.178688E+10 | 834821.92 |
September | 0.407211E+09 | 46662.59 | 0.407164E+09 | 0.131139E+10 | 38914314.57 |
October | 0.373016E+09 | 0.00 | 0.373016E+09 | 0.969256E+09 | 0.156921E+09 |
November | 0.309897E+09 | 0.00 | 0.309897E+09 | 0.599251E+09 | 0.349446E+09 |
December | 0.282332E+09 | 0.00 | 0.282332E+09 | 0.360585E+09 | 0.625793E+09 |
Annual Sum or Average | 0.480722E+10 | 62927226.71 | 0.474430E+10 | 0.122399E+11 | 0.338399E+10 |
Minimum of Months | 0.282332E+09 | 0.00 | 0.282332E+09 | 0.324782E+09 | 834821.92 |
Maximum of Months | 0.523338E+09 | 29054146.04 | 0.494284E+09 | 0.182973E+10 | 0.741366E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302487E+09 | 0.00 | 0.302487E+09 | 0.324782E+09 | 0.741366E+09 |
February | 0.313182E+09 | 0.00 | 0.313182E+09 | 0.409507E+09 | 0.573864E+09 |
March | 0.398274E+09 | 0.00 | 0.398274E+09 | 0.662493E+09 | 0.480929E+09 |
April | 0.434250E+09 | 894749.10 | 0.433355E+09 | 0.929704E+09 | 0.293980E+09 |
May | 0.505079E+09 | 14813672.07 | 0.490266E+09 | 0.144637E+10 | 89746754.22 |
June | 0.523339E+09 | 29054180.91 | 0.494284E+09 | 0.160997E+10 | 30102941.05 |
July | 0.496221E+09 | 14297338.37 | 0.481924E+09 | 0.182973E+10 | 2098379.80 |
August | 0.461940E+09 | 3820699.13 | 0.458119E+09 | 0.178688E+10 | 834826.37 |
September | 0.407211E+09 | 46662.64 | 0.407164E+09 | 0.131139E+10 | 38914381.39 |
October | 0.373016E+09 | 0.00 | 0.373016E+09 | 0.969256E+09 | 0.156921E+09 |
November | 0.309897E+09 | 0.00 | 0.309897E+09 | 0.599252E+09 | 0.349446E+09 |
December | 0.282332E+09 | 0.00 | 0.282332E+09 | 0.360585E+09 | 0.625794E+09 |
Annual Sum or Average | 0.480723E+10 | 62927302.22 | 0.474430E+10 | 0.122399E+11 | 0.338400E+10 |
Minimum of Months | 0.282332E+09 | 0.00 | 0.282332E+09 | 0.324782E+09 | 834826.37 |
Maximum of Months | 0.523339E+09 | 29054180.91 | 0.494284E+09 | 0.182973E+10 | 0.741366E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302487E+09 | 0.00 | 0.302487E+09 | 0.324782E+09 | 0.741366E+09 |
February | 0.313181E+09 | 0.00 | 0.313181E+09 | 0.409507E+09 | 0.573864E+09 |
March | 0.398273E+09 | 0.00 | 0.398273E+09 | 0.662493E+09 | 0.480929E+09 |
April | 0.434249E+09 | 894748.03 | 0.433355E+09 | 0.929703E+09 | 0.293980E+09 |
May | 0.505079E+09 | 14813654.29 | 0.490265E+09 | 0.144637E+10 | 89746649.19 |
June | 0.523338E+09 | 29054146.04 | 0.494284E+09 | 0.160997E+10 | 30102872.55 |
July | 0.496221E+09 | 14297321.21 | 0.481924E+09 | 0.182973E+10 | 2098368.68 |
August | 0.461939E+09 | 3820694.54 | 0.458119E+09 | 0.178688E+10 | 834821.92 |
September | 0.407211E+09 | 46662.59 | 0.407164E+09 | 0.131139E+10 | 38914314.57 |
October | 0.373016E+09 | 0.00 | 0.373016E+09 | 0.969256E+09 | 0.156921E+09 |
November | 0.309897E+09 | 0.00 | 0.309897E+09 | 0.599251E+09 | 0.349446E+09 |
December | 0.282332E+09 | 0.00 | 0.282332E+09 | 0.360585E+09 | 0.625793E+09 |
Annual Sum or Average | 0.480722E+10 | 62927226.71 | 0.474430E+10 | 0.122399E+11 | 0.338399E+10 |
Minimum of Months | 0.282332E+09 | 0.00 | 0.282332E+09 | 0.324782E+09 | 834821.92 |
Maximum of Months | 0.523338E+09 | 29054146.04 | 0.494284E+09 | 0.182973E+10 | 0.741366E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.302475E+09 | 0.00 | 0.302475E+09 | 0.324769E+09 | 0.741336E+09 |
February | 0.313169E+09 | 0.00 | 0.313169E+09 | 0.409491E+09 | 0.573841E+09 |
March | 0.398258E+09 | 0.00 | 0.398258E+09 | 0.662467E+09 | 0.480909E+09 |
April | 0.434232E+09 | 894713.04 | 0.433337E+09 | 0.929666E+09 | 0.293969E+09 |
May | 0.505059E+09 | 14813075.01 | 0.490246E+09 | 0.144631E+10 | 89743137.03 |
June | 0.523317E+09 | 29053009.89 | 0.494264E+09 | 0.160990E+10 | 30101727.76 |
July | 0.496201E+09 | 14296762.12 | 0.481905E+09 | 0.182966E+10 | 2098295.22 |
August | 0.461921E+09 | 3820545.13 | 0.458101E+09 | 0.178681E+10 | 834792.72 |
September | 0.407194E+09 | 46660.76 | 0.407148E+09 | 0.131134E+10 | 38912812.97 |
October | 0.373001E+09 | 0.00 | 0.373001E+09 | 0.969217E+09 | 0.156914E+09 |
November | 0.309884E+09 | 0.00 | 0.309884E+09 | 0.599228E+09 | 0.349432E+09 |
December | 0.282321E+09 | 0.00 | 0.282321E+09 | 0.360571E+09 | 0.625768E+09 |
Annual Sum or Average | 0.480703E+10 | 62924765.97 | 0.474411E+10 | 0.122394E+11 | 0.338386E+10 |
Minimum of Months | 0.282321E+09 | 0.00 | 0.282321E+09 | 0.324769E+09 | 834792.72 |
Maximum of Months | 0.523317E+09 | 29053009.89 | 0.494264E+09 | 0.182966E+10 | 0.741336E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.607988E+09 | 0.183946E+09 | 0.424042E+09 | 0.812800E+09 | 0.757853E+09 |
February | 0.598448E+09 | 0.162182E+09 | 0.436265E+09 | 0.893471E+09 | 0.587359E+09 |
March | 0.731873E+09 | 0.180380E+09 | 0.551493E+09 | 0.126910E+10 | 0.489882E+09 |
April | 0.862341E+09 | 0.251258E+09 | 0.611083E+09 | 0.175585E+10 | 0.296236E+09 |
May | 0.995813E+09 | 0.317271E+09 | 0.678541E+09 | 0.241974E+10 | 95323420.65 |
June | 0.943786E+09 | 0.288620E+09 | 0.655166E+09 | 0.246287E+10 | 28279022.62 |
July | 0.910241E+09 | 0.262421E+09 | 0.647820E+09 | 0.271949E+10 | 1513285.63 |
August | 0.932071E+09 | 0.286065E+09 | 0.646006E+09 | 0.279911E+10 | 547857.35 |
September | 0.847989E+09 | 0.262103E+09 | 0.585886E+09 | 0.220649E+10 | 39075852.21 |
October | 0.795114E+09 | 0.259764E+09 | 0.535350E+09 | 0.179410E+10 | 0.158845E+09 |
November | 0.644814E+09 | 0.204244E+09 | 0.440570E+09 | 0.122000E+10 | 0.351292E+09 |
December | 0.539312E+09 | 0.147965E+09 | 0.391347E+09 | 0.797719E+09 | 0.620087E+09 |
Annual Sum or Average | 0.940979E+10 | 0.280622E+10 | 0.660357E+10 | 0.211507E+11 | 0.342629E+10 |
Minimum of Months | 0.539312E+09 | 0.147965E+09 | 0.391347E+09 | 0.797719E+09 | 547857.35 |
Maximum of Months | 0.995813E+09 | 0.317271E+09 | 0.678541E+09 | 0.279911E+10 | 0.757853E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.607988E+09 | 0.183946E+09 | 0.424042E+09 | 0.812800E+09 | 0.757853E+09 |
February | 0.598448E+09 | 0.162182E+09 | 0.436265E+09 | 0.893471E+09 | 0.587359E+09 |
March | 0.731873E+09 | 0.180380E+09 | 0.551493E+09 | 0.126910E+10 | 0.489882E+09 |
April | 0.862341E+09 | 0.251258E+09 | 0.611083E+09 | 0.175585E+10 | 0.296236E+09 |
May | 0.995813E+09 | 0.317271E+09 | 0.678541E+09 | 0.241974E+10 | 95323420.65 |
June | 0.943786E+09 | 0.288620E+09 | 0.655166E+09 | 0.246287E+10 | 28279022.62 |
July | 0.910241E+09 | 0.262421E+09 | 0.647820E+09 | 0.271949E+10 | 1513285.63 |
August | 0.932071E+09 | 0.286065E+09 | 0.646006E+09 | 0.279911E+10 | 547857.35 |
September | 0.847989E+09 | 0.262103E+09 | 0.585886E+09 | 0.220649E+10 | 39075852.21 |
October | 0.795114E+09 | 0.259764E+09 | 0.535350E+09 | 0.179410E+10 | 0.158845E+09 |
November | 0.644814E+09 | 0.204244E+09 | 0.440570E+09 | 0.122000E+10 | 0.351292E+09 |
December | 0.539312E+09 | 0.147965E+09 | 0.391347E+09 | 0.797719E+09 | 0.620087E+09 |
Annual Sum or Average | 0.940979E+10 | 0.280622E+10 | 0.660357E+10 | 0.211507E+11 | 0.342629E+10 |
Minimum of Months | 0.539312E+09 | 0.147965E+09 | 0.391347E+09 | 0.797719E+09 | 547857.35 |
Maximum of Months | 0.995813E+09 | 0.317271E+09 | 0.678541E+09 | 0.279911E+10 | 0.757853E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.607977E+09 | 0.183943E+09 | 0.424034E+09 | 0.812786E+09 | 0.757839E+09 |
February | 0.598437E+09 | 0.162179E+09 | 0.436257E+09 | 0.893455E+09 | 0.587348E+09 |
March | 0.731860E+09 | 0.180377E+09 | 0.551483E+09 | 0.126908E+10 | 0.489873E+09 |
April | 0.862326E+09 | 0.251253E+09 | 0.611072E+09 | 0.175582E+10 | 0.296230E+09 |
May | 0.995794E+09 | 0.317265E+09 | 0.678529E+09 | 0.241970E+10 | 95321678.88 |
June | 0.943769E+09 | 0.288615E+09 | 0.655154E+09 | 0.246283E+10 | 28278505.90 |
July | 0.910224E+09 | 0.262416E+09 | 0.647808E+09 | 0.271944E+10 | 1513257.98 |
August | 0.932054E+09 | 0.286060E+09 | 0.645994E+09 | 0.279905E+10 | 547847.34 |
September | 0.847973E+09 | 0.262099E+09 | 0.585875E+09 | 0.220645E+10 | 39075138.21 |
October | 0.795100E+09 | 0.259760E+09 | 0.535340E+09 | 0.179406E+10 | 0.158842E+09 |
November | 0.644803E+09 | 0.204241E+09 | 0.440562E+09 | 0.121998E+10 | 0.351286E+09 |
December | 0.539302E+09 | 0.147963E+09 | 0.391340E+09 | 0.797705E+09 | 0.620076E+09 |
Annual Sum or Average | 0.940962E+10 | 0.280617E+10 | 0.660345E+10 | 0.211504E+11 | 0.342623E+10 |
Minimum of Months | 0.539302E+09 | 0.147963E+09 | 0.391340E+09 | 0.797705E+09 | 547847.34 |
Maximum of Months | 0.995794E+09 | 0.317265E+09 | 0.678529E+09 | 0.279905E+10 | 0.757839E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.977606E+09 | 0.459617E+09 | 0.517989E+09 | 0.152835E+10 | 0.713666E+09 |
February | 0.829174E+09 | 0.339168E+09 | 0.490005E+09 | 0.137770E+10 | 0.565151E+09 |
March | 0.755567E+09 | 0.205132E+09 | 0.550434E+09 | 0.140246E+10 | 0.487733E+09 |
April | 0.574773E+09 | 60936812.68 | 0.513836E+09 | 0.125641E+10 | 0.298216E+09 |
May | 0.503112E+09 | 7704657.16 | 0.495407E+09 | 0.145162E+10 | 85512179.63 |
June | 0.458531E+09 | 567449.66 | 0.457964E+09 | 0.147845E+10 | 21440599.86 |
July | 0.473803E+09 | 4025878.51 | 0.469777E+09 | 0.178690E+10 | 1037837.35 |
August | 0.549574E+09 | 38939508.08 | 0.510634E+09 | 0.199878E+10 | 518130.30 |
September | 0.701244E+09 | 0.160711E+09 | 0.540534E+09 | 0.195156E+10 | 36909990.24 |
October | 0.948668E+09 | 0.377149E+09 | 0.571519E+09 | 0.212111E+10 | 0.156285E+09 |
November | 0.101281E+10 | 0.488251E+09 | 0.524562E+09 | 0.192657E+10 | 0.352084E+09 |
December | 0.971538E+09 | 0.479910E+09 | 0.491628E+09 | 0.161331E+10 | 0.609696E+09 |
Annual Sum or Average | 0.875640E+10 | 0.262211E+10 | 0.613429E+10 | 0.198932E+11 | 0.332825E+10 |
Minimum of Months | 0.458531E+09 | 567449.66 | 0.457964E+09 | 0.125641E+10 | 518130.30 |
Maximum of Months | 0.101281E+10 | 0.488251E+09 | 0.571519E+09 | 0.212111E+10 | 0.713666E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.977605E+09 | 0.459616E+09 | 0.517989E+09 | 0.152835E+10 | 0.713666E+09 |
February | 0.829173E+09 | 0.339168E+09 | 0.490005E+09 | 0.137770E+10 | 0.565151E+09 |
March | 0.755566E+09 | 0.205132E+09 | 0.550434E+09 | 0.140246E+10 | 0.487733E+09 |
April | 0.574772E+09 | 60936739.56 | 0.513836E+09 | 0.125641E+10 | 0.298216E+09 |
May | 0.503111E+09 | 7704647.92 | 0.495407E+09 | 0.145162E+10 | 85512078.45 |
June | 0.458531E+09 | 567448.98 | 0.457963E+09 | 0.147845E+10 | 21440546.76 |
July | 0.473802E+09 | 4025873.68 | 0.469777E+09 | 0.178689E+10 | 1037830.64 |
August | 0.549573E+09 | 38939461.36 | 0.510634E+09 | 0.199878E+10 | 518127.17 |
September | 0.701244E+09 | 0.160710E+09 | 0.540533E+09 | 0.195156E+10 | 36909926.50 |
October | 0.948667E+09 | 0.377149E+09 | 0.571519E+09 | 0.212111E+10 | 0.156284E+09 |
November | 0.101281E+10 | 0.488251E+09 | 0.524562E+09 | 0.192656E+10 | 0.352084E+09 |
December | 0.971537E+09 | 0.479910E+09 | 0.491627E+09 | 0.161330E+10 | 0.609696E+09 |
Annual Sum or Average | 0.875639E+10 | 0.262211E+10 | 0.613428E+10 | 0.198932E+11 | 0.332825E+10 |
Minimum of Months | 0.458531E+09 | 567448.98 | 0.457963E+09 | 0.125641E+10 | 518127.17 |
Maximum of Months | 0.101281E+10 | 0.488251E+09 | 0.571519E+09 | 0.212111E+10 | 0.713666E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.977606E+09 | 0.459617E+09 | 0.517989E+09 | 0.152835E+10 | 0.713666E+09 |
February | 0.829174E+09 | 0.339168E+09 | 0.490005E+09 | 0.137770E+10 | 0.565151E+09 |
March | 0.755567E+09 | 0.205132E+09 | 0.550434E+09 | 0.140246E+10 | 0.487733E+09 |
April | 0.574773E+09 | 60936812.68 | 0.513836E+09 | 0.125641E+10 | 0.298216E+09 |
May | 0.503112E+09 | 7704657.16 | 0.495407E+09 | 0.145162E+10 | 85512179.63 |
June | 0.458531E+09 | 567449.66 | 0.457964E+09 | 0.147845E+10 | 21440599.86 |
July | 0.473803E+09 | 4025878.51 | 0.469777E+09 | 0.178690E+10 | 1037837.35 |
August | 0.549574E+09 | 38939508.08 | 0.510634E+09 | 0.199878E+10 | 518130.30 |
September | 0.701244E+09 | 0.160711E+09 | 0.540534E+09 | 0.195156E+10 | 36909990.24 |
October | 0.948668E+09 | 0.377149E+09 | 0.571519E+09 | 0.212111E+10 | 0.156285E+09 |
November | 0.101281E+10 | 0.488251E+09 | 0.524562E+09 | 0.192657E+10 | 0.352084E+09 |
December | 0.971538E+09 | 0.479910E+09 | 0.491628E+09 | 0.161331E+10 | 0.609696E+09 |
Annual Sum or Average | 0.875640E+10 | 0.262211E+10 | 0.613429E+10 | 0.198932E+11 | 0.332825E+10 |
Minimum of Months | 0.458531E+09 | 567449.66 | 0.457964E+09 | 0.125641E+10 | 518130.30 |
Maximum of Months | 0.101281E+10 | 0.488251E+09 | 0.571519E+09 | 0.212111E+10 | 0.713666E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.977605E+09 | 0.459616E+09 | 0.517989E+09 | 0.152835E+10 | 0.713666E+09 |
February | 0.829173E+09 | 0.339168E+09 | 0.490005E+09 | 0.137770E+10 | 0.565151E+09 |
March | 0.755566E+09 | 0.205132E+09 | 0.550434E+09 | 0.140246E+10 | 0.487733E+09 |
April | 0.574772E+09 | 60936739.56 | 0.513836E+09 | 0.125641E+10 | 0.298216E+09 |
May | 0.503111E+09 | 7704647.92 | 0.495407E+09 | 0.145162E+10 | 85512078.45 |
June | 0.458531E+09 | 567448.98 | 0.457963E+09 | 0.147845E+10 | 21440546.76 |
July | 0.473802E+09 | 4025873.68 | 0.469777E+09 | 0.178689E+10 | 1037830.64 |
August | 0.549573E+09 | 38939461.36 | 0.510634E+09 | 0.199878E+10 | 518127.17 |
September | 0.701244E+09 | 0.160710E+09 | 0.540533E+09 | 0.195156E+10 | 36909926.50 |
October | 0.948667E+09 | 0.377149E+09 | 0.571519E+09 | 0.212111E+10 | 0.156284E+09 |
November | 0.101281E+10 | 0.488251E+09 | 0.524562E+09 | 0.192656E+10 | 0.352084E+09 |
December | 0.971537E+09 | 0.479910E+09 | 0.491627E+09 | 0.161330E+10 | 0.609696E+09 |
Annual Sum or Average | 0.875639E+10 | 0.262211E+10 | 0.613428E+10 | 0.198932E+11 | 0.332825E+10 |
Minimum of Months | 0.458531E+09 | 567448.98 | 0.457963E+09 | 0.125641E+10 | 518127.17 |
Maximum of Months | 0.101281E+10 | 0.488251E+09 | 0.571519E+09 | 0.212111E+10 | 0.713666E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.977567E+09 | 0.459598E+09 | 0.517968E+09 | 0.152829E+10 | 0.713637E+09 |
February | 0.829140E+09 | 0.339155E+09 | 0.489986E+09 | 0.137764E+10 | 0.565128E+09 |
March | 0.755536E+09 | 0.205124E+09 | 0.550412E+09 | 0.140240E+10 | 0.487714E+09 |
April | 0.574750E+09 | 60934356.66 | 0.513815E+09 | 0.125636E+10 | 0.298204E+09 |
May | 0.503092E+09 | 7704346.63 | 0.495387E+09 | 0.145156E+10 | 85508733.11 |
June | 0.458513E+09 | 567426.79 | 0.457945E+09 | 0.147839E+10 | 21439735.71 |
July | 0.473784E+09 | 4025716.25 | 0.469758E+09 | 0.178682E+10 | 1037795.52 |
August | 0.549551E+09 | 38937938.65 | 0.510613E+09 | 0.199870E+10 | 518109.41 |
September | 0.701216E+09 | 0.160704E+09 | 0.540512E+09 | 0.195148E+10 | 36908502.61 |
October | 0.948630E+09 | 0.377134E+09 | 0.571496E+09 | 0.212103E+10 | 0.156278E+09 |
November | 0.101277E+10 | 0.488232E+09 | 0.524541E+09 | 0.192649E+10 | 0.352070E+09 |
December | 0.971499E+09 | 0.479891E+09 | 0.491608E+09 | 0.161324E+10 | 0.609671E+09 |
Annual Sum or Average | 0.875605E+10 | 0.262201E+10 | 0.613404E+10 | 0.198924E+11 | 0.332812E+10 |
Minimum of Months | 0.458513E+09 | 567426.79 | 0.457945E+09 | 0.125636E+10 | 518109.41 |
Maximum of Months | 0.101277E+10 | 0.488232E+09 | 0.571496E+09 | 0.212103E+10 | 0.713637E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.596243E+09 | 0.171246E+09 | 0.424997E+09 | 0.816081E+09 | 0.892903E+09 |
February | 0.614960E+09 | 0.175362E+09 | 0.439598E+09 | 0.924817E+09 | 0.717355E+09 |
March | 0.806485E+09 | 0.238762E+09 | 0.567723E+09 | 0.138061E+10 | 0.632553E+09 |
April | 0.852919E+09 | 0.239625E+09 | 0.613295E+09 | 0.169100E+10 | 0.416675E+09 |
May | 0.959345E+09 | 0.287171E+09 | 0.672174E+09 | 0.236202E+10 | 0.109107E+09 |
June | 0.959422E+09 | 0.302436E+09 | 0.656987E+09 | 0.247449E+10 | 36741451.89 |
July | 0.909506E+09 | 0.260192E+09 | 0.649314E+09 | 0.266358E+10 | 3804402.06 |
August | 0.933052E+09 | 0.283688E+09 | 0.649364E+09 | 0.271259E+10 | 2433144.05 |
September | 0.858941E+09 | 0.269855E+09 | 0.589086E+09 | 0.223647E+10 | 41607922.79 |
October | 0.788791E+09 | 0.254801E+09 | 0.533990E+09 | 0.178232E+10 | 0.189196E+09 |
November | 0.656002E+09 | 0.214534E+09 | 0.441468E+09 | 0.123538E+10 | 0.462293E+09 |
December | 0.567482E+09 | 0.171540E+09 | 0.395942E+09 | 0.834162E+09 | 0.832925E+09 |
Annual Sum or Average | 0.950315E+10 | 0.286921E+10 | 0.663394E+10 | 0.211135E+11 | 0.433759E+10 |
Minimum of Months | 0.567482E+09 | 0.171246E+09 | 0.395942E+09 | 0.816081E+09 | 2433144.05 |
Maximum of Months | 0.959422E+09 | 0.302436E+09 | 0.672174E+09 | 0.271259E+10 | 0.892903E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.596243E+09 | 0.171246E+09 | 0.424997E+09 | 0.816081E+09 | 0.892903E+09 |
February | 0.614960E+09 | 0.175362E+09 | 0.439598E+09 | 0.924817E+09 | 0.717355E+09 |
March | 0.806485E+09 | 0.238762E+09 | 0.567723E+09 | 0.138061E+10 | 0.632553E+09 |
April | 0.852919E+09 | 0.239625E+09 | 0.613295E+09 | 0.169100E+10 | 0.416675E+09 |
May | 0.959345E+09 | 0.287171E+09 | 0.672174E+09 | 0.236202E+10 | 0.109107E+09 |
June | 0.959422E+09 | 0.302436E+09 | 0.656987E+09 | 0.247449E+10 | 36741451.89 |
July | 0.909506E+09 | 0.260192E+09 | 0.649314E+09 | 0.266358E+10 | 3804402.06 |
August | 0.933052E+09 | 0.283688E+09 | 0.649364E+09 | 0.271259E+10 | 2433144.05 |
September | 0.858941E+09 | 0.269855E+09 | 0.589086E+09 | 0.223647E+10 | 41607922.79 |
October | 0.788791E+09 | 0.254801E+09 | 0.533990E+09 | 0.178232E+10 | 0.189196E+09 |
November | 0.656002E+09 | 0.214534E+09 | 0.441468E+09 | 0.123538E+10 | 0.462293E+09 |
December | 0.567482E+09 | 0.171540E+09 | 0.395942E+09 | 0.834162E+09 | 0.832925E+09 |
Annual Sum or Average | 0.950315E+10 | 0.286921E+10 | 0.663394E+10 | 0.211135E+11 | 0.433759E+10 |
Minimum of Months | 0.567482E+09 | 0.171246E+09 | 0.395942E+09 | 0.816081E+09 | 2433144.05 |
Maximum of Months | 0.959422E+09 | 0.302436E+09 | 0.672174E+09 | 0.271259E+10 | 0.892903E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.596232E+09 | 0.171243E+09 | 0.424989E+09 | 0.816066E+09 | 0.892887E+09 |
February | 0.614948E+09 | 0.175358E+09 | 0.439590E+09 | 0.924800E+09 | 0.717342E+09 |
March | 0.806470E+09 | 0.238757E+09 | 0.567713E+09 | 0.138059E+10 | 0.632541E+09 |
April | 0.852904E+09 | 0.239620E+09 | 0.613283E+09 | 0.169097E+10 | 0.416668E+09 |
May | 0.959327E+09 | 0.287165E+09 | 0.672162E+09 | 0.236198E+10 | 0.109105E+09 |
June | 0.959405E+09 | 0.302430E+09 | 0.656975E+09 | 0.247445E+10 | 36740780.54 |
July | 0.909489E+09 | 0.260187E+09 | 0.649302E+09 | 0.266353E+10 | 3804332.55 |
August | 0.933035E+09 | 0.283682E+09 | 0.649352E+09 | 0.271254E+10 | 2433099.59 |
September | 0.858925E+09 | 0.269850E+09 | 0.589076E+09 | 0.223643E+10 | 41607162.52 |
October | 0.788777E+09 | 0.254797E+09 | 0.533980E+09 | 0.178229E+10 | 0.189192E+09 |
November | 0.655990E+09 | 0.214530E+09 | 0.441460E+09 | 0.123536E+10 | 0.462284E+09 |
December | 0.567472E+09 | 0.171537E+09 | 0.395935E+09 | 0.834147E+09 | 0.832910E+09 |
Annual Sum or Average | 0.950297E+10 | 0.286916E+10 | 0.663382E+10 | 0.211131E+11 | 0.433752E+10 |
Minimum of Months | 0.567472E+09 | 0.171243E+09 | 0.395935E+09 | 0.816066E+09 | 2433099.59 |
Maximum of Months | 0.959405E+09 | 0.302430E+09 | 0.672162E+09 | 0.271254E+10 | 0.892887E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.151242E+10 | 0.00 | 0.151242E+10 | 0.176935E+10 | 0.327255E+10 |
February | 0.156589E+10 | 0.00 | 0.156589E+10 | 0.217676E+10 | 0.250780E+10 |
March | 0.199134E+10 | 0.00 | 0.199134E+10 | 0.342988E+10 | 0.216650E+10 |
April | 0.217122E+10 | 4473691.42 | 0.216675E+10 | 0.480474E+10 | 0.133895E+10 |
May | 0.252537E+10 | 74067464.72 | 0.245130E+10 | 0.753908E+10 | 0.338815E+09 |
June | 0.261666E+10 | 0.145269E+09 | 0.247139E+10 | 0.842667E+10 | 76634837.65 |
July | 0.248108E+10 | 71485827.43 | 0.240959E+10 | 0.970527E+10 | 1533405.55 |
August | 0.230967E+10 | 19103264.63 | 0.229057E+10 | 0.957220E+10 | 167704.34 |
September | 0.203603E+10 | 233310.40 | 0.203580E+10 | 0.700709E+10 | 0.110871E+09 |
October | 0.186506E+10 | 0.00 | 0.186506E+10 | 0.518364E+10 | 0.557880E+09 |
November | 0.154947E+10 | 0.00 | 0.154947E+10 | 0.318199E+10 | 0.151047E+10 |
December | 0.141165E+10 | 0.00 | 0.141165E+10 | 0.196328E+10 | 0.271114E+10 |
Annual Sum or Average | 0.240358E+11 | 0.314633E+09 | 0.237212E+11 | 0.647599E+11 | 0.145933E+11 |
Minimum of Months | 0.141165E+10 | 0.00 | 0.141165E+10 | 0.176935E+10 | 167704.34 |
Maximum of Months | 0.261666E+10 | 0.145269E+09 | 0.247139E+10 | 0.970527E+10 | 0.327255E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182395E+10 | 0.551833E+09 | 0.127211E+10 | 0.249740E+10 | 0.208766E+10 |
February | 0.179532E+10 | 0.486542E+09 | 0.130878E+10 | 0.272112E+10 | 0.161724E+10 |
March | 0.219560E+10 | 0.541135E+09 | 0.165446E+10 | 0.382552E+10 | 0.140894E+10 |
April | 0.258700E+10 | 0.753766E+09 | 0.183323E+10 | 0.528384E+10 | 0.890536E+09 |
May | 0.298741E+10 | 0.951804E+09 | 0.203560E+10 | 0.740815E+10 | 0.218054E+09 |
June | 0.283133E+10 | 0.865852E+09 | 0.196548E+10 | 0.758614E+10 | 41256783.57 |
July | 0.273069E+10 | 0.787254E+09 | 0.194344E+10 | 0.846283E+10 | 598810.02 |
August | 0.279618E+10 | 0.858187E+09 | 0.193800E+10 | 0.874022E+10 | 22028.62 |
September | 0.254394E+10 | 0.786302E+09 | 0.175764E+10 | 0.686747E+10 | 66434154.16 |
October | 0.238532E+10 | 0.779285E+09 | 0.160603E+10 | 0.553617E+10 | 0.353561E+09 |
November | 0.193442E+10 | 0.612727E+09 | 0.132170E+10 | 0.371214E+10 | 0.980690E+09 |
December | 0.161792E+10 | 0.443892E+09 | 0.117403E+10 | 0.244285E+10 | 0.173541E+10 |
Annual Sum or Average | 0.282291E+11 | 0.841858E+10 | 0.198105E+11 | 0.650839E+11 | 0.940039E+10 |
Minimum of Months | 0.161792E+10 | 0.443892E+09 | 0.117403E+10 | 0.244285E+10 | 22028.62 |
Maximum of Months | 0.298741E+10 | 0.951804E+09 | 0.203560E+10 | 0.874022E+10 | 0.208766E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.488797E+10 | 0.229806E+10 | 0.258992E+10 | 0.760198E+10 | 0.344774E+10 |
February | 0.414582E+10 | 0.169582E+10 | 0.245000E+10 | 0.687395E+10 | 0.267800E+10 |
March | 0.377779E+10 | 0.102565E+10 | 0.275214E+10 | 0.702531E+10 | 0.232964E+10 |
April | 0.287383E+10 | 0.304680E+09 | 0.256915E+10 | 0.636812E+10 | 0.141685E+10 |
May | 0.251553E+10 | 38522820.00 | 0.247701E+10 | 0.752911E+10 | 0.335849E+09 |
June | 0.229263E+10 | 2837213.97 | 0.228979E+10 | 0.777647E+10 | 52241561.25 |
July | 0.236899E+10 | 20129149.13 | 0.234886E+10 | 0.944233E+10 | 322536.90 |
August | 0.274783E+10 | 0.194695E+09 | 0.255314E+10 | 0.105389E+11 | 96006.56 |
September | 0.350618E+10 | 0.803543E+09 | 0.270264E+10 | 0.100541E+11 | 0.125319E+09 |
October | 0.474328E+10 | 0.188572E+10 | 0.285756E+10 | 0.107502E+11 | 0.646205E+09 |
November | 0.506401E+10 | 0.244123E+10 | 0.262278E+10 | 0.964126E+10 | 0.167365E+10 |
December | 0.485763E+10 | 0.239952E+10 | 0.245811E+10 | 0.806195E+10 | 0.291500E+10 |
Annual Sum or Average | 0.437815E+11 | 0.131104E+11 | 0.306711E+11 | 0.101664E+12 | 0.156209E+11 |
Minimum of Months | 0.229263E+10 | 2837213.97 | 0.228979E+10 | 0.636812E+10 | 96006.56 |
Maximum of Months | 0.506401E+10 | 0.244123E+10 | 0.285756E+10 | 0.107502E+11 | 0.344774E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.178871E+10 | 0.513732E+09 | 0.127498E+10 | 0.256842E+10 | 0.230523E+10 |
February | 0.184486E+10 | 0.526080E+09 | 0.131878E+10 | 0.289508E+10 | 0.179146E+10 |
March | 0.241943E+10 | 0.716278E+09 | 0.170315E+10 | 0.426760E+10 | 0.159812E+10 |
April | 0.255873E+10 | 0.718867E+09 | 0.183986E+10 | 0.522470E+10 | 0.104537E+10 |
May | 0.287801E+10 | 0.861503E+09 | 0.201650E+10 | 0.719582E+10 | 0.282916E+09 |
June | 0.287824E+10 | 0.907297E+09 | 0.197094E+10 | 0.763917E+10 | 62288233.85 |
July | 0.272849E+10 | 0.780567E+09 | 0.194792E+10 | 0.835734E+10 | 1587936.99 |
August | 0.279913E+10 | 0.851054E+09 | 0.194807E+10 | 0.859048E+10 | 523913.55 |
September | 0.257680E+10 | 0.809556E+09 | 0.176724E+10 | 0.686600E+10 | 97425579.87 |
October | 0.236635E+10 | 0.764396E+09 | 0.160195E+10 | 0.550124E+10 | 0.461400E+09 |
November | 0.196799E+10 | 0.643595E+09 | 0.132439E+10 | 0.384590E+10 | 0.114129E+10 |
December | 0.170243E+10 | 0.514614E+09 | 0.118781E+10 | 0.269396E+10 | 0.196536E+10 |
Annual Sum or Average | 0.285092E+11 | 0.860754E+10 | 0.199016E+11 | 0.656457E+11 | 0.107530E+11 |
Minimum of Months | 0.170243E+10 | 0.513732E+09 | 0.118781E+10 | 0.256842E+10 | 523913.55 |
Maximum of Months | 0.287824E+10 | 0.907297E+09 | 0.201650E+10 | 0.859048E+10 | 0.230523E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.151242E+10 | 0.00 | 0.151242E+10 | 0.184748E+10 | 0.304725E+10 |
February | 0.156589E+10 | 0.00 | 0.156589E+10 | 0.221283E+10 | 0.237973E+10 |
March | 0.199134E+10 | 0.00 | 0.199134E+10 | 0.342713E+10 | 0.209324E+10 |
April | 0.217122E+10 | 4473691.42 | 0.216675E+10 | 0.476241E+10 | 0.133270E+10 |
May | 0.252537E+10 | 74067464.72 | 0.245130E+10 | 0.745831E+10 | 0.346882E+09 |
June | 0.261666E+10 | 0.145269E+09 | 0.247139E+10 | 0.834062E+10 | 80226965.21 |
July | 0.248108E+10 | 71485827.43 | 0.240959E+10 | 0.959087E+10 | 2157986.63 |
August | 0.230967E+10 | 19103264.63 | 0.229057E+10 | 0.946826E+10 | 248089.88 |
September | 0.203603E+10 | 233310.40 | 0.203580E+10 | 0.692699E+10 | 0.113837E+09 |
October | 0.186506E+10 | 0.00 | 0.186506E+10 | 0.513260E+10 | 0.561441E+09 |
November | 0.154947E+10 | 0.00 | 0.154947E+10 | 0.317545E+10 | 0.146430E+10 |
December | 0.141165E+10 | 0.00 | 0.141165E+10 | 0.201579E+10 | 0.255116E+10 |
Annual Sum or Average | 0.240358E+11 | 0.314633E+09 | 0.237212E+11 | 0.643587E+11 | 0.139732E+11 |
Minimum of Months | 0.141165E+10 | 0.00 | 0.141165E+10 | 0.184748E+10 | 248089.88 |
Maximum of Months | 0.261666E+10 | 0.145269E+09 | 0.247139E+10 | 0.959087E+10 | 0.304725E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.182395E+10 | 0.551833E+09 | 0.127211E+10 | 0.255043E+10 | 0.197591E+10 |
February | 0.179532E+10 | 0.486542E+09 | 0.130878E+10 | 0.273964E+10 | 0.155575E+10 |
March | 0.219560E+10 | 0.541135E+09 | 0.165446E+10 | 0.381794E+10 | 0.137495E+10 |
April | 0.258700E+10 | 0.753766E+09 | 0.183323E+10 | 0.525176E+10 | 0.891289E+09 |
May | 0.298741E+10 | 0.951804E+09 | 0.203560E+10 | 0.734443E+10 | 0.225100E+09 |
June | 0.283133E+10 | 0.865852E+09 | 0.196548E+10 | 0.751660E+10 | 44375797.15 |
July | 0.273069E+10 | 0.787254E+09 | 0.194344E+10 | 0.837317E+10 | 951346.87 |
August | 0.279618E+10 | 0.858187E+09 | 0.193800E+10 | 0.865695E+10 | 46228.47 |
September | 0.254394E+10 | 0.786302E+09 | 0.175764E+10 | 0.680206E+10 | 69065974.09 |
October | 0.238532E+10 | 0.779285E+09 | 0.160603E+10 | 0.549333E+10 | 0.358316E+09 |
November | 0.193442E+10 | 0.612727E+09 | 0.132170E+10 | 0.370103E+10 | 0.960325E+09 |
December | 0.161792E+10 | 0.443892E+09 | 0.117403E+10 | 0.247558E+10 | 0.165655E+10 |
Annual Sum or Average | 0.282291E+11 | 0.841858E+10 | 0.198105E+11 | 0.647229E+11 | 0.911262E+10 |
Minimum of Months | 0.161792E+10 | 0.443892E+09 | 0.117403E+10 | 0.247558E+10 | 46228.47 |
Maximum of Months | 0.298741E+10 | 0.951804E+09 | 0.203560E+10 | 0.865695E+10 | 0.197591E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.488797E+10 | 0.229806E+10 | 0.258992E+10 | 0.764907E+10 | 0.326765E+10 |
February | 0.414582E+10 | 0.169582E+10 | 0.245000E+10 | 0.688178E+10 | 0.257116E+10 |
March | 0.377779E+10 | 0.102565E+10 | 0.275214E+10 | 0.700233E+10 | 0.226388E+10 |
April | 0.287383E+10 | 0.304680E+09 | 0.256915E+10 | 0.632188E+10 | 0.140793E+10 |
May | 0.251553E+10 | 38522820.00 | 0.247701E+10 | 0.744559E+10 | 0.341760E+09 |
June | 0.229263E+10 | 2837213.97 | 0.228979E+10 | 0.768866E+10 | 53417866.40 |
July | 0.236899E+10 | 20129149.13 | 0.234886E+10 | 0.932302E+10 | 571207.32 |
August | 0.274783E+10 | 0.194695E+09 | 0.255314E+10 | 0.104312E+11 | 144854.94 |
September | 0.350618E+10 | 0.803543E+09 | 0.270264E+10 | 0.996664E+10 | 0.127659E+09 |
October | 0.474328E+10 | 0.188572E+10 | 0.285756E+10 | 0.106836E+11 | 0.649079E+09 |
November | 0.506401E+10 | 0.244123E+10 | 0.262278E+10 | 0.960881E+10 | 0.163773E+10 |
December | 0.485763E+10 | 0.239952E+10 | 0.245811E+10 | 0.808095E+10 | 0.279397E+10 |
Annual Sum or Average | 0.437815E+11 | 0.131104E+11 | 0.306711E+11 | 0.101084E+12 | 0.151150E+11 |
Minimum of Months | 0.229263E+10 | 2837213.97 | 0.228979E+10 | 0.632188E+10 | 144854.94 |
Maximum of Months | 0.506401E+10 | 0.244123E+10 | 0.285756E+10 | 0.106836E+11 | 0.326765E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.178871E+10 | 0.513732E+09 | 0.127498E+10 | 0.259577E+10 | 0.218308E+10 |
February | 0.184486E+10 | 0.526080E+09 | 0.131878E+10 | 0.290215E+10 | 0.172009E+10 |
March | 0.241943E+10 | 0.716278E+09 | 0.170315E+10 | 0.425110E+10 | 0.155526E+10 |
April | 0.255873E+10 | 0.718867E+09 | 0.183986E+10 | 0.518977E+10 | 0.103633E+10 |
May | 0.287801E+10 | 0.861503E+09 | 0.201650E+10 | 0.713943E+10 | 0.285925E+09 |
June | 0.287824E+10 | 0.907297E+09 | 0.197094E+10 | 0.758278E+10 | 63306280.34 |
July | 0.272849E+10 | 0.780567E+09 | 0.194792E+10 | 0.828458E+10 | 1928528.67 |
August | 0.279913E+10 | 0.851054E+09 | 0.194807E+10 | 0.852033E+10 | 609106.21 |
September | 0.257680E+10 | 0.809556E+09 | 0.176724E+10 | 0.681210E+10 | 99013143.60 |
October | 0.236635E+10 | 0.764396E+09 | 0.160195E+10 | 0.546372E+10 | 0.461135E+09 |
November | 0.196799E+10 | 0.643595E+09 | 0.132439E+10 | 0.383153E+10 | 0.111288E+10 |
December | 0.170243E+10 | 0.514614E+09 | 0.118781E+10 | 0.271074E+10 | 0.187699E+10 |
Annual Sum or Average | 0.285092E+11 | 0.860754E+10 | 0.199016E+11 | 0.652840E+11 | 0.103965E+11 |
Minimum of Months | 0.170243E+10 | 0.513732E+09 | 0.118781E+10 | 0.259577E+10 | 609106.21 |
Maximum of Months | 0.287824E+10 | 0.907297E+09 | 0.201650E+10 | 0.852033E+10 | 0.218308E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 606.29 | 1383.96 | 564.67 | 0.00 | 564.67 | 0.00 | 0.00 |
February | 846.36 | 1186.05 | 647.28 | 0.00 | 647.28 | 0.00 | 0.00 |
March | 1236.72 | 897.78 | 743.49 | 0.00 | 743.49 | 0.00 | 0.00 |
April | 1793.39 | 567.09 | 837.67 | 1.73 | 835.94 | 0.00 | 0.00 |
May | 2700.04 | 167.54 | 942.87 | 27.65 | 915.21 | 0.00 | 0.00 |
June | 3105.62 | 58.07 | 1009.52 | 56.05 | 953.47 | 0.00 | 0.00 |
July | 3415.70 | 3.92 | 926.33 | 26.69 | 899.64 | 0.00 | 0.00 |
August | 3335.69 | 1.56 | 862.34 | 7.13 | 855.20 | 0.00 | 0.00 |
September | 2529.67 | 75.07 | 785.51 | 0.09 | 785.42 | 0.00 | 0.00 |
October | 1809.38 | 292.93 | 696.34 | 0.00 | 696.34 | 0.00 | 0.00 |
November | 1155.95 | 674.08 | 597.79 | 0.00 | 597.79 | 0.00 | 0.00 |
December | 673.13 | 1168.21 | 527.05 | 0.00 | 527.05 | 0.00 | 0.00 |
Annual Sum or Average | 1940.61 | 536.52 | 762.17 | 9.98 | 752.20 | 0.00 | 0.00 |
Minimum of Months | 606.29 | 1.56 | 527.05 | 0.00 | 527.05 | 0.00 | 0.00 |
Maximum of Months | 3415.70 | 1383.96 | 1009.52 | 56.05 | 953.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 910.39 | 848.84 | 680.99 | 206.03 | 474.95 | 0.00 | 0.00 |
February | 1107.97 | 728.37 | 742.12 | 201.12 | 541.00 | 0.00 | 0.00 |
March | 1421.48 | 548.70 | 819.75 | 202.04 | 617.71 | 0.00 | 0.00 |
April | 2032.22 | 342.86 | 998.07 | 290.81 | 707.27 | 0.00 | 0.00 |
May | 2710.27 | 106.77 | 1115.37 | 355.36 | 760.01 | 0.00 | 0.00 |
June | 2850.53 | 32.73 | 1092.34 | 334.05 | 758.29 | 0.00 | 0.00 |
July | 3046.01 | 1.69 | 1019.53 | 293.93 | 725.60 | 0.00 | 0.00 |
August | 3135.18 | 0.61 | 1043.98 | 320.41 | 723.57 | 0.00 | 0.00 |
September | 2553.79 | 45.23 | 981.46 | 303.36 | 678.10 | 0.00 | 0.00 |
October | 2009.51 | 177.92 | 890.58 | 290.95 | 599.63 | 0.00 | 0.00 |
November | 1412.03 | 406.59 | 746.31 | 236.39 | 509.92 | 0.00 | 0.00 |
December | 893.50 | 694.54 | 604.06 | 165.73 | 438.33 | 0.00 | 0.00 |
Annual Sum or Average | 2012.04 | 325.94 | 895.14 | 266.95 | 628.19 | 0.00 | 0.00 |
Minimum of Months | 893.50 | 0.61 | 604.06 | 165.73 | 438.33 | 0.00 | 0.00 |
Maximum of Months | 3135.18 | 848.84 | 1115.37 | 355.36 | 760.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2853.08 | 1332.25 | 1824.97 | 858.00 | 966.97 | 0.00 | 0.00 |
February | 2847.41 | 1168.04 | 1713.72 | 700.99 | 1012.73 | 0.00 | 0.00 |
March | 2618.07 | 910.49 | 1410.47 | 382.93 | 1027.53 | 0.00 | 0.00 |
April | 2423.62 | 575.26 | 1108.73 | 117.55 | 991.19 | 0.00 | 0.00 |
May | 2709.85 | 159.63 | 939.19 | 14.38 | 924.81 | 0.00 | 0.00 |
June | 2851.93 | 41.36 | 884.50 | 1.09 | 883.41 | 0.00 | 0.00 |
July | 3335.72 | 1.94 | 884.48 | 7.52 | 876.97 | 0.00 | 0.00 |
August | 3731.27 | 0.97 | 1025.93 | 72.69 | 953.24 | 0.00 | 0.00 |
September | 3764.56 | 71.20 | 1352.70 | 310.01 | 1042.69 | 0.00 | 0.00 |
October | 3959.63 | 291.75 | 1770.95 | 704.05 | 1066.90 | 0.00 | 0.00 |
November | 3716.34 | 679.17 | 1953.71 | 941.84 | 1011.88 | 0.00 | 0.00 |
December | 3011.67 | 1138.16 | 1813.64 | 895.88 | 917.76 | 0.00 | 0.00 |
Annual Sum or Average | 3154.02 | 527.69 | 1388.31 | 415.73 | 972.58 | 0.00 | 0.00 |
Minimum of Months | 2423.62 | 0.97 | 884.48 | 1.09 | 876.97 | 0.00 | 0.00 |
Maximum of Months | 3959.63 | 1332.25 | 1953.71 | 941.84 | 1066.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 914.06 | 1000.11 | 667.83 | 191.81 | 476.02 | 0.00 | 0.00 |
February | 1146.84 | 889.57 | 762.59 | 217.46 | 545.13 | 0.00 | 0.00 |
March | 1546.37 | 708.50 | 903.32 | 267.43 | 635.89 | 0.00 | 0.00 |
April | 1957.17 | 482.26 | 987.17 | 277.34 | 709.83 | 0.00 | 0.00 |
May | 2645.62 | 122.21 | 1074.53 | 321.65 | 752.88 | 0.00 | 0.00 |
June | 2863.98 | 42.52 | 1110.44 | 350.04 | 760.40 | 0.00 | 0.00 |
July | 2983.38 | 4.26 | 1018.71 | 291.43 | 727.27 | 0.00 | 0.00 |
August | 3038.27 | 2.73 | 1045.08 | 317.75 | 727.33 | 0.00 | 0.00 |
September | 2588.49 | 48.16 | 994.14 | 312.33 | 681.81 | 0.00 | 0.00 |
October | 1996.32 | 211.91 | 883.50 | 285.39 | 598.10 | 0.00 | 0.00 |
November | 1429.83 | 535.06 | 759.26 | 248.30 | 510.96 | 0.00 | 0.00 |
December | 934.32 | 932.93 | 635.62 | 192.14 | 443.48 | 0.00 | 0.00 |
Annual Sum or Average | 2008.50 | 412.63 | 904.02 | 272.94 | 631.08 | 0.00 | 0.00 |
Minimum of Months | 914.06 | 2.73 | 635.62 | 191.81 | 443.48 | 0.00 | 0.00 |
Maximum of Months | 3038.27 | 1000.11 | 1110.44 | 350.04 | 760.40 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 660.60 | 1221.83 | 564.67 | 0.00 | 564.67 | 0.00 | 0.00 |
February | 899.79 | 1036.62 | 647.28 | 0.00 | 647.28 | 0.00 | 0.00 |
March | 1280.57 | 808.88 | 743.48 | 0.00 | 743.48 | 0.00 | 0.00 |
April | 1853.68 | 516.57 | 837.66 | 1.73 | 835.94 | 0.00 | 0.00 |
May | 2814.77 | 126.50 | 942.86 | 27.65 | 915.21 | 0.00 | 0.00 |
June | 3251.03 | 29.57 | 1009.51 | 56.05 | 953.47 | 0.00 | 0.00 |
July | 3623.53 | 0.57 | 926.33 | 26.69 | 899.64 | 0.00 | 0.00 |
August | 3573.85 | 0.06 | 862.33 | 7.13 | 855.20 | 0.00 | 0.00 |
September | 2703.35 | 42.77 | 785.51 | 0.09 | 785.42 | 0.00 | 0.00 |
October | 1935.35 | 208.29 | 696.33 | 0.00 | 696.33 | 0.00 | 0.00 |
November | 1227.62 | 582.74 | 597.79 | 0.00 | 597.79 | 0.00 | 0.00 |
December | 733.00 | 1012.22 | 527.05 | 0.00 | 527.05 | 0.00 | 0.00 |
Annual Sum or Average | 2053.52 | 462.75 | 762.17 | 9.98 | 752.19 | 0.00 | 0.00 |
Minimum of Months | 660.60 | 0.06 | 527.05 | 0.00 | 527.05 | 0.00 | 0.00 |
Maximum of Months | 3623.53 | 1221.83 | 1009.51 | 56.05 | 953.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 932.42 | 779.44 | 680.98 | 206.03 | 474.95 | 0.00 | 0.00 |
February | 1124.80 | 668.50 | 742.12 | 201.12 | 541.00 | 0.00 | 0.00 |
March | 1428.28 | 526.04 | 819.74 | 202.04 | 617.71 | 0.00 | 0.00 |
April | 2038.52 | 343.57 | 998.07 | 290.80 | 707.27 | 0.00 | 0.00 |
May | 2765.89 | 81.41 | 1115.37 | 355.36 | 760.01 | 0.00 | 0.00 |
June | 2926.75 | 15.92 | 1092.33 | 334.05 | 758.29 | 0.00 | 0.00 |
July | 3159.66 | 0.22 | 1019.52 | 293.93 | 725.60 | 0.00 | 0.00 |
August | 3263.23 | 0.01 | 1043.98 | 320.41 | 723.57 | 0.00 | 0.00 |
September | 2649.49 | 25.63 | 981.46 | 303.36 | 678.10 | 0.00 | 0.00 |
October | 2066.97 | 132.00 | 890.58 | 290.95 | 599.62 | 0.00 | 0.00 |
November | 1432.15 | 378.35 | 746.31 | 236.39 | 509.91 | 0.00 | 0.00 |
December | 912.06 | 647.93 | 604.06 | 165.73 | 438.33 | 0.00 | 0.00 |
Annual Sum or Average | 2063.80 | 298.08 | 895.14 | 266.95 | 628.19 | 0.00 | 0.00 |
Minimum of Months | 912.06 | 0.01 | 604.06 | 165.73 | 438.33 | 0.00 | 0.00 |
Maximum of Months | 3263.23 | 779.44 | 1115.37 | 355.36 | 760.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2838.25 | 1287.24 | 1824.96 | 858.00 | 966.96 | 0.00 | 0.00 |
February | 2841.41 | 1106.98 | 1713.71 | 700.98 | 1012.73 | 0.00 | 0.00 |
March | 2622.95 | 869.79 | 1410.46 | 382.93 | 1027.53 | 0.00 | 0.00 |
April | 2456.84 | 546.62 | 1108.73 | 117.55 | 991.18 | 0.00 | 0.00 |
May | 2811.05 | 125.39 | 939.19 | 14.38 | 924.81 | 0.00 | 0.00 |
June | 3000.18 | 20.15 | 884.50 | 1.09 | 883.41 | 0.00 | 0.00 |
July | 3525.36 | 0.12 | 884.48 | 7.52 | 876.96 | 0.00 | 0.00 |
August | 3934.77 | 0.04 | 1025.92 | 72.69 | 953.23 | 0.00 | 0.00 |
September | 3878.91 | 48.35 | 1352.69 | 310.01 | 1042.68 | 0.00 | 0.00 |
October | 4013.67 | 241.27 | 1770.94 | 704.05 | 1066.89 | 0.00 | 0.00 |
November | 3719.62 | 645.70 | 1953.71 | 941.83 | 1011.87 | 0.00 | 0.00 |
December | 3009.99 | 1088.34 | 1813.63 | 895.88 | 917.75 | 0.00 | 0.00 |
Annual Sum or Average | 3223.74 | 495.34 | 1388.30 | 415.73 | 972.57 | 0.00 | 0.00 |
Minimum of Months | 2456.84 | 0.04 | 884.48 | 1.09 | 876.96 | 0.00 | 0.00 |
Maximum of Months | 4013.67 | 1287.24 | 1953.71 | 941.83 | 1066.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 958.94 | 860.68 | 667.83 | 191.81 | 476.02 | 0.00 | 0.00 |
February | 1196.71 | 740.52 | 762.59 | 217.46 | 545.13 | 0.00 | 0.00 |
March | 1593.34 | 596.67 | 903.31 | 267.43 | 635.88 | 0.00 | 0.00 |
April | 2015.70 | 403.31 | 987.16 | 277.34 | 709.82 | 0.00 | 0.00 |
May | 2686.61 | 105.63 | 1074.52 | 321.65 | 752.88 | 0.00 | 0.00 |
June | 2947.21 | 24.03 | 1110.43 | 350.04 | 760.39 | 0.00 | 0.00 |
July | 3120.27 | 0.59 | 1018.70 | 291.43 | 727.27 | 0.00 | 0.00 |
August | 3207.32 | 0.20 | 1045.07 | 317.75 | 727.33 | 0.00 | 0.00 |
September | 2648.92 | 37.59 | 994.13 | 312.33 | 681.81 | 0.00 | 0.00 |
October | 2053.93 | 172.27 | 883.49 | 285.39 | 598.10 | 0.00 | 0.00 |
November | 1483.76 | 440.31 | 759.25 | 248.30 | 510.95 | 0.00 | 0.00 |
December | 1005.81 | 733.78 | 635.61 | 192.13 | 443.48 | 0.00 | 0.00 |
Annual Sum or Average | 2081.61 | 340.97 | 904.02 | 272.94 | 631.08 | 0.00 | 0.00 |
Minimum of Months | 958.94 | 0.20 | 635.61 | 191.81 | 443.48 | 0.00 | 0.00 |
Maximum of Months | 3207.32 | 860.68 | 1110.43 | 350.04 | 760.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 689.77 | 1137.71 | 564.67 | 0.00 | 564.67 | 0.00 | 0.00 |
February | 914.69 | 983.69 | 647.28 | 0.00 | 647.28 | 0.00 | 0.00 |
March | 1279.54 | 781.53 | 743.48 | 0.00 | 743.48 | 0.00 | 0.00 |
April | 1837.35 | 514.16 | 837.66 | 1.73 | 835.94 | 0.00 | 0.00 |
May | 2784.61 | 129.51 | 942.86 | 27.65 | 915.21 | 0.00 | 0.00 |
June | 3217.83 | 30.95 | 1009.51 | 56.05 | 953.47 | 0.00 | 0.00 |
July | 3580.82 | 0.81 | 926.33 | 26.69 | 899.64 | 0.00 | 0.00 |
August | 3535.04 | 0.09 | 862.33 | 7.13 | 855.20 | 0.00 | 0.00 |
September | 2672.45 | 43.92 | 785.51 | 0.09 | 785.42 | 0.00 | 0.00 |
October | 1916.29 | 209.62 | 696.33 | 0.00 | 696.33 | 0.00 | 0.00 |
November | 1225.10 | 564.93 | 597.79 | 0.00 | 597.79 | 0.00 | 0.00 |
December | 752.61 | 952.49 | 527.05 | 0.00 | 527.05 | 0.00 | 0.00 |
Annual Sum or Average | 2040.80 | 443.09 | 762.17 | 9.98 | 752.19 | 0.00 | 0.00 |
Minimum of Months | 689.77 | 0.09 | 527.05 | 0.00 | 527.05 | 0.00 | 0.00 |
Maximum of Months | 3580.82 | 1137.71 | 1009.51 | 56.05 | 953.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 952.22 | 737.72 | 680.98 | 206.03 | 474.95 | 0.00 | 0.00 |
February | 1132.46 | 643.08 | 742.12 | 201.12 | 541.00 | 0.00 | 0.00 |
March | 1425.45 | 513.35 | 819.74 | 202.04 | 617.71 | 0.00 | 0.00 |
April | 2026.14 | 343.86 | 998.07 | 290.80 | 707.27 | 0.00 | 0.00 |
May | 2742.10 | 84.04 | 1115.37 | 355.36 | 760.01 | 0.00 | 0.00 |
June | 2899.92 | 17.12 | 1092.33 | 334.05 | 758.29 | 0.00 | 0.00 |
July | 3126.18 | 0.36 | 1019.52 | 293.93 | 725.60 | 0.00 | 0.00 |
August | 3232.13 | 0.02 | 1043.98 | 320.41 | 723.57 | 0.00 | 0.00 |
September | 2624.25 | 26.65 | 981.46 | 303.36 | 678.10 | 0.00 | 0.00 |
October | 2050.97 | 133.78 | 890.58 | 290.95 | 599.62 | 0.00 | 0.00 |
November | 1427.87 | 370.50 | 746.31 | 236.39 | 509.91 | 0.00 | 0.00 |
December | 924.28 | 618.48 | 604.06 | 165.73 | 438.33 | 0.00 | 0.00 |
Annual Sum or Average | 2052.35 | 288.96 | 895.14 | 266.95 | 628.19 | 0.00 | 0.00 |
Minimum of Months | 924.28 | 0.02 | 604.06 | 165.73 | 438.33 | 0.00 | 0.00 |
Maximum of Months | 3232.13 | 737.72 | 1115.37 | 355.36 | 760.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2855.83 | 1220.00 | 1824.96 | 858.00 | 966.96 | 0.00 | 0.00 |
February | 2844.65 | 1062.82 | 1713.71 | 700.98 | 1012.73 | 0.00 | 0.00 |
March | 2614.37 | 845.24 | 1410.46 | 382.93 | 1027.53 | 0.00 | 0.00 |
April | 2439.00 | 543.18 | 1108.73 | 117.55 | 991.18 | 0.00 | 0.00 |
May | 2779.86 | 127.60 | 939.19 | 14.38 | 924.81 | 0.00 | 0.00 |
June | 2966.31 | 20.61 | 884.50 | 1.09 | 883.41 | 0.00 | 0.00 |
July | 3480.82 | 0.21 | 884.48 | 7.52 | 876.96 | 0.00 | 0.00 |
August | 3894.58 | 0.05 | 1025.92 | 72.69 | 953.23 | 0.00 | 0.00 |
September | 3845.15 | 49.25 | 1352.69 | 310.01 | 1042.68 | 0.00 | 0.00 |
October | 3988.79 | 242.34 | 1770.94 | 704.05 | 1066.89 | 0.00 | 0.00 |
November | 3707.10 | 631.84 | 1953.71 | 941.83 | 1011.87 | 0.00 | 0.00 |
December | 3017.08 | 1043.15 | 1813.63 | 895.88 | 917.75 | 0.00 | 0.00 |
Annual Sum or Average | 3205.34 | 479.29 | 1388.30 | 415.73 | 972.57 | 0.00 | 0.00 |
Minimum of Months | 2439.00 | 0.05 | 884.48 | 1.09 | 876.96 | 0.00 | 0.00 |
Maximum of Months | 3988.79 | 1220.00 | 1953.71 | 941.83 | 1066.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 969.15 | 815.07 | 667.83 | 191.81 | 476.02 | 0.00 | 0.00 |
February | 1199.63 | 711.02 | 762.59 | 217.46 | 545.13 | 0.00 | 0.00 |
March | 1587.18 | 580.67 | 903.31 | 267.43 | 635.88 | 0.00 | 0.00 |
April | 2002.22 | 399.82 | 987.16 | 277.34 | 709.82 | 0.00 | 0.00 |
May | 2665.56 | 106.75 | 1074.52 | 321.65 | 752.88 | 0.00 | 0.00 |
June | 2925.46 | 24.42 | 1110.43 | 350.04 | 760.39 | 0.00 | 0.00 |
July | 3093.11 | 0.72 | 1018.70 | 291.43 | 727.27 | 0.00 | 0.00 |
August | 3181.13 | 0.23 | 1045.07 | 317.75 | 727.33 | 0.00 | 0.00 |
September | 2628.13 | 38.20 | 994.13 | 312.33 | 681.81 | 0.00 | 0.00 |
October | 2039.92 | 172.17 | 883.49 | 285.39 | 598.10 | 0.00 | 0.00 |
November | 1478.22 | 429.35 | 759.25 | 248.30 | 510.95 | 0.00 | 0.00 |
December | 1012.07 | 700.79 | 635.61 | 192.13 | 443.48 | 0.00 | 0.00 |
Annual Sum or Average | 2070.14 | 329.67 | 904.02 | 272.94 | 631.08 | 0.00 | 0.00 |
Minimum of Months | 969.15 | 0.23 | 635.61 | 191.81 | 443.48 | 0.00 | 0.00 |
Maximum of Months | 3181.13 | 815.07 | 1110.43 | 350.04 | 760.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.162390E+10 | 0.370680E+10 | 0.151242E+10 | 0.00 | 0.151242E+10 | 0.00 | 0.00 |
February | 0.204752E+10 | 0.286930E+10 | 0.156589E+10 | 0.00 | 0.156589E+10 | 0.00 | 0.00 |
March | 0.331244E+10 | 0.240462E+10 | 0.199135E+10 | 0.00 | 0.199135E+10 | 0.00 | 0.00 |
April | 0.464848E+10 | 0.146989E+10 | 0.217123E+10 | 4473707.31 | 0.216676E+10 | 0.00 | 0.00 |
May | 0.723180E+10 | 0.448730E+09 | 0.252538E+10 | 74067727.74 | 0.245131E+10 | 0.00 | 0.00 |
June | 0.804978E+10 | 0.150513E+09 | 0.261667E+10 | 0.145270E+09 | 0.247140E+10 | 0.00 | 0.00 |
July | 0.914860E+10 | 10491792.17 | 0.248109E+10 | 71486081.28 | 0.240960E+10 | 0.00 | 0.00 |
August | 0.893432E+10 | 4174089.30 | 0.230968E+10 | 19103332.47 | 0.229058E+10 | 0.00 | 0.00 |
September | 0.655690E+10 | 0.194570E+09 | 0.203604E+10 | 233311.23 | 0.203580E+10 | 0.00 | 0.00 |
October | 0.484624E+10 | 0.784597E+09 | 0.186507E+10 | 0.00 | 0.186507E+10 | 0.00 | 0.00 |
November | 0.299623E+10 | 0.174722E+10 | 0.154947E+10 | 0.00 | 0.154947E+10 | 0.00 | 0.00 |
December | 0.180291E+10 | 0.312894E+10 | 0.141165E+10 | 0.00 | 0.141165E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.611991E+11 | 0.169198E+11 | 0.240359E+11 | 0.314634E+09 | 0.237213E+11 | 0.00 | 0.00 |
Minimum of Months | 0.162390E+10 | 4174089.30 | 0.141165E+10 | 0.00 | 0.141165E+10 | 0.00 | 0.00 |
Maximum of Months | 0.914860E+10 | 0.370680E+10 | 0.261667E+10 | 0.145270E+09 | 0.247140E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.243839E+10 | 0.227355E+10 | 0.182395E+10 | 0.551835E+09 | 0.127212E+10 | 0.00 | 0.00 |
February | 0.268040E+10 | 0.176207E+10 | 0.179533E+10 | 0.486544E+09 | 0.130879E+10 | 0.00 | 0.00 |
March | 0.380728E+10 | 0.146964E+10 | 0.219561E+10 | 0.541137E+09 | 0.165447E+10 | 0.00 | 0.00 |
April | 0.526753E+10 | 0.888702E+09 | 0.258701E+10 | 0.753769E+09 | 0.183324E+10 | 0.00 | 0.00 |
May | 0.725917E+10 | 0.285969E+09 | 0.298742E+10 | 0.951807E+09 | 0.203561E+10 | 0.00 | 0.00 |
June | 0.738857E+10 | 84836551.15 | 0.283134E+10 | 0.865855E+09 | 0.196549E+10 | 0.00 | 0.00 |
July | 0.815842E+10 | 4539829.25 | 0.273071E+10 | 0.787257E+09 | 0.194345E+10 | 0.00 | 0.00 |
August | 0.839726E+10 | 1643562.04 | 0.279620E+10 | 0.858190E+09 | 0.193801E+10 | 0.00 | 0.00 |
September | 0.661942E+10 | 0.117227E+09 | 0.254395E+10 | 0.786305E+09 | 0.175765E+10 | 0.00 | 0.00 |
October | 0.538226E+10 | 0.476533E+09 | 0.238533E+10 | 0.779288E+09 | 0.160604E+10 | 0.00 | 0.00 |
November | 0.365998E+10 | 0.105387E+10 | 0.193443E+10 | 0.612729E+09 | 0.132170E+10 | 0.00 | 0.00 |
December | 0.239314E+10 | 0.186025E+10 | 0.161793E+10 | 0.443894E+09 | 0.117403E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.634518E+11 | 0.102788E+11 | 0.282292E+11 | 0.841861E+10 | 0.198106E+11 | 0.00 | 0.00 |
Minimum of Months | 0.239314E+10 | 1643562.04 | 0.161793E+10 | 0.443894E+09 | 0.117403E+10 | 0.00 | 0.00 |
Maximum of Months | 0.839726E+10 | 0.227355E+10 | 0.298742E+10 | 0.951807E+09 | 0.203561E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.764170E+10 | 0.356830E+10 | 0.488799E+10 | 0.229806E+10 | 0.258992E+10 | 0.00 | 0.00 |
February | 0.688844E+10 | 0.282573E+10 | 0.414583E+10 | 0.169583E+10 | 0.245001E+10 | 0.00 | 0.00 |
March | 0.701224E+10 | 0.243865E+10 | 0.377780E+10 | 0.102565E+10 | 0.275215E+10 | 0.00 | 0.00 |
April | 0.628201E+10 | 0.149107E+10 | 0.287384E+10 | 0.304681E+09 | 0.256916E+10 | 0.00 | 0.00 |
May | 0.725805E+10 | 0.427557E+09 | 0.251554E+10 | 38522956.80 | 0.247702E+10 | 0.00 | 0.00 |
June | 0.739220E+10 | 0.107202E+09 | 0.229264E+10 | 2837224.05 | 0.228980E+10 | 0.00 | 0.00 |
July | 0.893440E+10 | 5189131.50 | 0.236899E+10 | 20129220.61 | 0.234886E+10 | 0.00 | 0.00 |
August | 0.999384E+10 | 2590624.35 | 0.274784E+10 | 0.194696E+09 | 0.255315E+10 | 0.00 | 0.00 |
September | 0.975773E+10 | 0.184548E+09 | 0.350619E+10 | 0.803546E+09 | 0.270265E+10 | 0.00 | 0.00 |
October | 0.106055E+11 | 0.781416E+09 | 0.474330E+10 | 0.188573E+10 | 0.285757E+10 | 0.00 | 0.00 |
November | 0.963275E+10 | 0.176041E+10 | 0.506403E+10 | 0.244124E+10 | 0.262279E+10 | 0.00 | 0.00 |
December | 0.806646E+10 | 0.304845E+10 | 0.485765E+10 | 0.239953E+10 | 0.245812E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.994653E+11 | 0.166411E+11 | 0.437816E+11 | 0.131105E+11 | 0.306712E+11 | 0.00 | 0.00 |
Minimum of Months | 0.628201E+10 | 2590624.35 | 0.229264E+10 | 2837224.05 | 0.228980E+10 | 0.00 | 0.00 |
Maximum of Months | 0.106055E+11 | 0.356830E+10 | 0.506403E+10 | 0.244124E+10 | 0.285757E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.244823E+10 | 0.267869E+10 | 0.178872E+10 | 0.513735E+09 | 0.127498E+10 | 0.00 | 0.00 |
February | 0.277443E+10 | 0.215205E+10 | 0.184487E+10 | 0.526082E+09 | 0.131879E+10 | 0.00 | 0.00 |
March | 0.414181E+10 | 0.189765E+10 | 0.241944E+10 | 0.716281E+09 | 0.170316E+10 | 0.00 | 0.00 |
April | 0.507298E+10 | 0.125002E+10 | 0.255874E+10 | 0.718870E+09 | 0.183987E+10 | 0.00 | 0.00 |
May | 0.708603E+10 | 0.327320E+09 | 0.287802E+10 | 0.861506E+09 | 0.201651E+10 | 0.00 | 0.00 |
June | 0.742343E+10 | 0.110224E+09 | 0.287825E+10 | 0.907301E+09 | 0.197095E+10 | 0.00 | 0.00 |
July | 0.799068E+10 | 11413136.68 | 0.272850E+10 | 0.780570E+09 | 0.194793E+10 | 0.00 | 0.00 |
August | 0.813771E+10 | 7299387.68 | 0.279914E+10 | 0.851058E+09 | 0.194808E+10 | 0.00 | 0.00 |
September | 0.670936E+10 | 0.124823E+09 | 0.257681E+10 | 0.809559E+09 | 0.176725E+10 | 0.00 | 0.00 |
October | 0.534694E+10 | 0.567584E+09 | 0.236636E+10 | 0.764399E+09 | 0.160196E+10 | 0.00 | 0.00 |
November | 0.370613E+10 | 0.138687E+10 | 0.196799E+10 | 0.643597E+09 | 0.132440E+10 | 0.00 | 0.00 |
December | 0.250247E+10 | 0.249876E+10 | 0.170244E+10 | 0.514616E+09 | 0.118782E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.633402E+11 | 0.130127E+11 | 0.285093E+11 | 0.860757E+10 | 0.199017E+11 | 0.00 | 0.00 |
Minimum of Months | 0.244823E+10 | 7299387.68 | 0.170244E+10 | 0.513735E+09 | 0.118782E+10 | 0.00 | 0.00 |
Maximum of Months | 0.813771E+10 | 0.267869E+10 | 0.287825E+10 | 0.907301E+09 | 0.201651E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.176935E+10 | 0.327255E+10 | 0.151242E+10 | 0.00 | 0.151242E+10 | 0.00 | 0.00 |
February | 0.217676E+10 | 0.250780E+10 | 0.156589E+10 | 0.00 | 0.156589E+10 | 0.00 | 0.00 |
March | 0.342988E+10 | 0.216650E+10 | 0.199134E+10 | 0.00 | 0.199134E+10 | 0.00 | 0.00 |
April | 0.480474E+10 | 0.133895E+10 | 0.217122E+10 | 4473691.42 | 0.216675E+10 | 0.00 | 0.00 |
May | 0.753908E+10 | 0.338815E+09 | 0.252537E+10 | 74067464.72 | 0.245130E+10 | 0.00 | 0.00 |
June | 0.842667E+10 | 76634837.65 | 0.261666E+10 | 0.145269E+09 | 0.247139E+10 | 0.00 | 0.00 |
July | 0.970527E+10 | 1533405.55 | 0.248108E+10 | 71485827.43 | 0.240959E+10 | 0.00 | 0.00 |
August | 0.957220E+10 | 167704.34 | 0.230967E+10 | 19103264.63 | 0.229057E+10 | 0.00 | 0.00 |
September | 0.700709E+10 | 0.110871E+09 | 0.203603E+10 | 233310.40 | 0.203580E+10 | 0.00 | 0.00 |
October | 0.518364E+10 | 0.557880E+09 | 0.186506E+10 | 0.00 | 0.186506E+10 | 0.00 | 0.00 |
November | 0.318199E+10 | 0.151047E+10 | 0.154947E+10 | 0.00 | 0.154947E+10 | 0.00 | 0.00 |
December | 0.196328E+10 | 0.271114E+10 | 0.141165E+10 | 0.00 | 0.141165E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.647599E+11 | 0.145933E+11 | 0.240358E+11 | 0.314633E+09 | 0.237212E+11 | 0.00 | 0.00 |
Minimum of Months | 0.176935E+10 | 167704.34 | 0.141165E+10 | 0.00 | 0.141165E+10 | 0.00 | 0.00 |
Maximum of Months | 0.970527E+10 | 0.327255E+10 | 0.261666E+10 | 0.145269E+09 | 0.247139E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.249740E+10 | 0.208766E+10 | 0.182395E+10 | 0.551833E+09 | 0.127211E+10 | 0.00 | 0.00 |
February | 0.272112E+10 | 0.161724E+10 | 0.179532E+10 | 0.486542E+09 | 0.130878E+10 | 0.00 | 0.00 |
March | 0.382552E+10 | 0.140894E+10 | 0.219560E+10 | 0.541135E+09 | 0.165446E+10 | 0.00 | 0.00 |
April | 0.528384E+10 | 0.890536E+09 | 0.258700E+10 | 0.753766E+09 | 0.183323E+10 | 0.00 | 0.00 |
May | 0.740815E+10 | 0.218054E+09 | 0.298741E+10 | 0.951804E+09 | 0.203560E+10 | 0.00 | 0.00 |
June | 0.758614E+10 | 41256783.57 | 0.283133E+10 | 0.865852E+09 | 0.196548E+10 | 0.00 | 0.00 |
July | 0.846283E+10 | 598810.02 | 0.273069E+10 | 0.787254E+09 | 0.194344E+10 | 0.00 | 0.00 |
August | 0.874022E+10 | 22028.62 | 0.279618E+10 | 0.858187E+09 | 0.193800E+10 | 0.00 | 0.00 |
September | 0.686747E+10 | 66434154.16 | 0.254394E+10 | 0.786302E+09 | 0.175764E+10 | 0.00 | 0.00 |
October | 0.553617E+10 | 0.353561E+09 | 0.238532E+10 | 0.779285E+09 | 0.160603E+10 | 0.00 | 0.00 |
November | 0.371214E+10 | 0.980690E+09 | 0.193442E+10 | 0.612727E+09 | 0.132170E+10 | 0.00 | 0.00 |
December | 0.244285E+10 | 0.173541E+10 | 0.161792E+10 | 0.443892E+09 | 0.117403E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.650839E+11 | 0.940039E+10 | 0.282291E+11 | 0.841858E+10 | 0.198105E+11 | 0.00 | 0.00 |
Minimum of Months | 0.244285E+10 | 22028.62 | 0.161792E+10 | 0.443892E+09 | 0.117403E+10 | 0.00 | 0.00 |
Maximum of Months | 0.874022E+10 | 0.208766E+10 | 0.298741E+10 | 0.951804E+09 | 0.203560E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.760198E+10 | 0.344774E+10 | 0.488797E+10 | 0.229806E+10 | 0.258992E+10 | 0.00 | 0.00 |
February | 0.687395E+10 | 0.267800E+10 | 0.414582E+10 | 0.169582E+10 | 0.245000E+10 | 0.00 | 0.00 |
March | 0.702531E+10 | 0.232964E+10 | 0.377779E+10 | 0.102565E+10 | 0.275214E+10 | 0.00 | 0.00 |
April | 0.636812E+10 | 0.141685E+10 | 0.287383E+10 | 0.304680E+09 | 0.256915E+10 | 0.00 | 0.00 |
May | 0.752911E+10 | 0.335849E+09 | 0.251553E+10 | 38522820.00 | 0.247701E+10 | 0.00 | 0.00 |
June | 0.777647E+10 | 52241561.25 | 0.229263E+10 | 2837213.97 | 0.228979E+10 | 0.00 | 0.00 |
July | 0.944233E+10 | 322536.90 | 0.236899E+10 | 20129149.13 | 0.234886E+10 | 0.00 | 0.00 |
August | 0.105389E+11 | 96006.56 | 0.274783E+10 | 0.194695E+09 | 0.255314E+10 | 0.00 | 0.00 |
September | 0.100541E+11 | 0.125319E+09 | 0.350618E+10 | 0.803543E+09 | 0.270264E+10 | 0.00 | 0.00 |
October | 0.107502E+11 | 0.646205E+09 | 0.474328E+10 | 0.188572E+10 | 0.285756E+10 | 0.00 | 0.00 |
November | 0.964126E+10 | 0.167365E+10 | 0.506401E+10 | 0.244123E+10 | 0.262278E+10 | 0.00 | 0.00 |
December | 0.806195E+10 | 0.291500E+10 | 0.485763E+10 | 0.239952E+10 | 0.245811E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.101664E+12 | 0.156209E+11 | 0.437815E+11 | 0.131104E+11 | 0.306711E+11 | 0.00 | 0.00 |
Minimum of Months | 0.636812E+10 | 96006.56 | 0.229263E+10 | 2837213.97 | 0.228979E+10 | 0.00 | 0.00 |
Maximum of Months | 0.107502E+11 | 0.344774E+10 | 0.506401E+10 | 0.244123E+10 | 0.285756E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.256842E+10 | 0.230523E+10 | 0.178871E+10 | 0.513732E+09 | 0.127498E+10 | 0.00 | 0.00 |
February | 0.289508E+10 | 0.179146E+10 | 0.184486E+10 | 0.526080E+09 | 0.131878E+10 | 0.00 | 0.00 |
March | 0.426760E+10 | 0.159812E+10 | 0.241943E+10 | 0.716278E+09 | 0.170315E+10 | 0.00 | 0.00 |
April | 0.522470E+10 | 0.104537E+10 | 0.255873E+10 | 0.718867E+09 | 0.183986E+10 | 0.00 | 0.00 |
May | 0.719582E+10 | 0.282916E+09 | 0.287801E+10 | 0.861503E+09 | 0.201650E+10 | 0.00 | 0.00 |
June | 0.763917E+10 | 62288233.85 | 0.287824E+10 | 0.907297E+09 | 0.197094E+10 | 0.00 | 0.00 |
July | 0.835734E+10 | 1587936.99 | 0.272849E+10 | 0.780567E+09 | 0.194792E+10 | 0.00 | 0.00 |
August | 0.859048E+10 | 523913.55 | 0.279913E+10 | 0.851054E+09 | 0.194807E+10 | 0.00 | 0.00 |
September | 0.686600E+10 | 97425579.87 | 0.257680E+10 | 0.809556E+09 | 0.176724E+10 | 0.00 | 0.00 |
October | 0.550124E+10 | 0.461400E+09 | 0.236635E+10 | 0.764396E+09 | 0.160195E+10 | 0.00 | 0.00 |
November | 0.384590E+10 | 0.114129E+10 | 0.196799E+10 | 0.643595E+09 | 0.132439E+10 | 0.00 | 0.00 |
December | 0.269396E+10 | 0.196536E+10 | 0.170243E+10 | 0.514614E+09 | 0.118781E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.656457E+11 | 0.107530E+11 | 0.285092E+11 | 0.860754E+10 | 0.199016E+11 | 0.00 | 0.00 |
Minimum of Months | 0.256842E+10 | 523913.55 | 0.170243E+10 | 0.513732E+09 | 0.118781E+10 | 0.00 | 0.00 |
Maximum of Months | 0.859048E+10 | 0.230523E+10 | 0.287824E+10 | 0.907297E+09 | 0.201650E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.184748E+10 | 0.304725E+10 | 0.151242E+10 | 0.00 | 0.151242E+10 | 0.00 | 0.00 |
February | 0.221283E+10 | 0.237973E+10 | 0.156589E+10 | 0.00 | 0.156589E+10 | 0.00 | 0.00 |
March | 0.342713E+10 | 0.209324E+10 | 0.199134E+10 | 0.00 | 0.199134E+10 | 0.00 | 0.00 |
April | 0.476241E+10 | 0.133270E+10 | 0.217122E+10 | 4473691.42 | 0.216675E+10 | 0.00 | 0.00 |
May | 0.745831E+10 | 0.346882E+09 | 0.252537E+10 | 74067464.72 | 0.245130E+10 | 0.00 | 0.00 |
June | 0.834062E+10 | 80226965.21 | 0.261666E+10 | 0.145269E+09 | 0.247139E+10 | 0.00 | 0.00 |
July | 0.959087E+10 | 2157986.63 | 0.248108E+10 | 71485827.43 | 0.240959E+10 | 0.00 | 0.00 |
August | 0.946826E+10 | 248089.88 | 0.230967E+10 | 19103264.63 | 0.229057E+10 | 0.00 | 0.00 |
September | 0.692699E+10 | 0.113837E+09 | 0.203603E+10 | 233310.40 | 0.203580E+10 | 0.00 | 0.00 |
October | 0.513260E+10 | 0.561441E+09 | 0.186506E+10 | 0.00 | 0.186506E+10 | 0.00 | 0.00 |
November | 0.317545E+10 | 0.146430E+10 | 0.154947E+10 | 0.00 | 0.154947E+10 | 0.00 | 0.00 |
December | 0.201579E+10 | 0.255116E+10 | 0.141165E+10 | 0.00 | 0.141165E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.643587E+11 | 0.139732E+11 | 0.240358E+11 | 0.314633E+09 | 0.237212E+11 | 0.00 | 0.00 |
Minimum of Months | 0.184748E+10 | 248089.88 | 0.141165E+10 | 0.00 | 0.141165E+10 | 0.00 | 0.00 |
Maximum of Months | 0.959087E+10 | 0.304725E+10 | 0.261666E+10 | 0.145269E+09 | 0.247139E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.255043E+10 | 0.197591E+10 | 0.182395E+10 | 0.551833E+09 | 0.127211E+10 | 0.00 | 0.00 |
February | 0.273964E+10 | 0.155575E+10 | 0.179532E+10 | 0.486542E+09 | 0.130878E+10 | 0.00 | 0.00 |
March | 0.381794E+10 | 0.137495E+10 | 0.219560E+10 | 0.541135E+09 | 0.165446E+10 | 0.00 | 0.00 |
April | 0.525176E+10 | 0.891289E+09 | 0.258700E+10 | 0.753766E+09 | 0.183323E+10 | 0.00 | 0.00 |
May | 0.734443E+10 | 0.225100E+09 | 0.298741E+10 | 0.951804E+09 | 0.203560E+10 | 0.00 | 0.00 |
June | 0.751660E+10 | 44375797.15 | 0.283133E+10 | 0.865852E+09 | 0.196548E+10 | 0.00 | 0.00 |
July | 0.837317E+10 | 951346.87 | 0.273069E+10 | 0.787254E+09 | 0.194344E+10 | 0.00 | 0.00 |
August | 0.865695E+10 | 46228.47 | 0.279618E+10 | 0.858187E+09 | 0.193800E+10 | 0.00 | 0.00 |
September | 0.680206E+10 | 69065974.09 | 0.254394E+10 | 0.786302E+09 | 0.175764E+10 | 0.00 | 0.00 |
October | 0.549333E+10 | 0.358316E+09 | 0.238532E+10 | 0.779285E+09 | 0.160603E+10 | 0.00 | 0.00 |
November | 0.370103E+10 | 0.960325E+09 | 0.193442E+10 | 0.612727E+09 | 0.132170E+10 | 0.00 | 0.00 |
December | 0.247558E+10 | 0.165655E+10 | 0.161792E+10 | 0.443892E+09 | 0.117403E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.647229E+11 | 0.911262E+10 | 0.282291E+11 | 0.841858E+10 | 0.198105E+11 | 0.00 | 0.00 |
Minimum of Months | 0.247558E+10 | 46228.47 | 0.161792E+10 | 0.443892E+09 | 0.117403E+10 | 0.00 | 0.00 |
Maximum of Months | 0.865695E+10 | 0.197591E+10 | 0.298741E+10 | 0.951804E+09 | 0.203560E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.764907E+10 | 0.326765E+10 | 0.488797E+10 | 0.229806E+10 | 0.258992E+10 | 0.00 | 0.00 |
February | 0.688178E+10 | 0.257116E+10 | 0.414582E+10 | 0.169582E+10 | 0.245000E+10 | 0.00 | 0.00 |
March | 0.700233E+10 | 0.226388E+10 | 0.377779E+10 | 0.102565E+10 | 0.275214E+10 | 0.00 | 0.00 |
April | 0.632188E+10 | 0.140793E+10 | 0.287383E+10 | 0.304680E+09 | 0.256915E+10 | 0.00 | 0.00 |
May | 0.744559E+10 | 0.341760E+09 | 0.251553E+10 | 38522820.00 | 0.247701E+10 | 0.00 | 0.00 |
June | 0.768866E+10 | 53417866.40 | 0.229263E+10 | 2837213.97 | 0.228979E+10 | 0.00 | 0.00 |
July | 0.932302E+10 | 571207.32 | 0.236899E+10 | 20129149.13 | 0.234886E+10 | 0.00 | 0.00 |
August | 0.104312E+11 | 144854.94 | 0.274783E+10 | 0.194695E+09 | 0.255314E+10 | 0.00 | 0.00 |
September | 0.996664E+10 | 0.127659E+09 | 0.350618E+10 | 0.803543E+09 | 0.270264E+10 | 0.00 | 0.00 |
October | 0.106836E+11 | 0.649079E+09 | 0.474328E+10 | 0.188572E+10 | 0.285756E+10 | 0.00 | 0.00 |
November | 0.960881E+10 | 0.163773E+10 | 0.506401E+10 | 0.244123E+10 | 0.262278E+10 | 0.00 | 0.00 |
December | 0.808095E+10 | 0.279397E+10 | 0.485763E+10 | 0.239952E+10 | 0.245811E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.101084E+12 | 0.151150E+11 | 0.437815E+11 | 0.131104E+11 | 0.306711E+11 | 0.00 | 0.00 |
Minimum of Months | 0.632188E+10 | 144854.94 | 0.229263E+10 | 2837213.97 | 0.228979E+10 | 0.00 | 0.00 |
Maximum of Months | 0.106836E+11 | 0.326765E+10 | 0.506401E+10 | 0.244123E+10 | 0.285756E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.259577E+10 | 0.218308E+10 | 0.178871E+10 | 0.513732E+09 | 0.127498E+10 | 0.00 | 0.00 |
February | 0.290215E+10 | 0.172009E+10 | 0.184486E+10 | 0.526080E+09 | 0.131878E+10 | 0.00 | 0.00 |
March | 0.425110E+10 | 0.155526E+10 | 0.241943E+10 | 0.716278E+09 | 0.170315E+10 | 0.00 | 0.00 |
April | 0.518977E+10 | 0.103633E+10 | 0.255873E+10 | 0.718867E+09 | 0.183986E+10 | 0.00 | 0.00 |
May | 0.713943E+10 | 0.285925E+09 | 0.287801E+10 | 0.861503E+09 | 0.201650E+10 | 0.00 | 0.00 |
June | 0.758278E+10 | 63306280.34 | 0.287824E+10 | 0.907297E+09 | 0.197094E+10 | 0.00 | 0.00 |
July | 0.828458E+10 | 1928528.67 | 0.272849E+10 | 0.780567E+09 | 0.194792E+10 | 0.00 | 0.00 |
August | 0.852033E+10 | 609106.21 | 0.279913E+10 | 0.851054E+09 | 0.194807E+10 | 0.00 | 0.00 |
September | 0.681210E+10 | 99013143.60 | 0.257680E+10 | 0.809556E+09 | 0.176724E+10 | 0.00 | 0.00 |
October | 0.546372E+10 | 0.461135E+09 | 0.236635E+10 | 0.764396E+09 | 0.160195E+10 | 0.00 | 0.00 |
November | 0.383153E+10 | 0.111288E+10 | 0.196799E+10 | 0.643595E+09 | 0.132439E+10 | 0.00 | 0.00 |
December | 0.271074E+10 | 0.187699E+10 | 0.170243E+10 | 0.514614E+09 | 0.118781E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.652840E+11 | 0.103965E+11 | 0.285092E+11 | 0.860754E+10 | 0.199016E+11 | 0.00 | 0.00 |
Minimum of Months | 0.259577E+10 | 609106.21 | 0.170243E+10 | 0.513732E+09 | 0.118781E+10 | 0.00 | 0.00 |
Maximum of Months | 0.852033E+10 | 0.218308E+10 | 0.287824E+10 | 0.907297E+09 | 0.201650E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.74 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.26 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.75 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.17 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.91 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.78 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.48 | 23.16 | 3.85 | 24.14 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.02 | 24.10 | 3.89 | 24.33 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.68 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.66 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.62 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.84 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.02 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.74 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.02 | 24.10 | 3.95 | 24.33 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.55 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.28 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.84 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.18 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.76 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.56 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 22.01 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.38 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.43 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.81 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.15 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.04 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.55 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.38 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.45 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.74 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.74 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.06 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.95 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.24 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.44 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.82 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.82 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.95 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.21 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.05 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.11 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.86 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.14 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.24 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.14 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.21 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.11 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.86 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.10 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.86 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.283622E+11 | -0.279220E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -440230137.9 | 60.05 | 0.00 | 0.00 |
February | 0.250728E+11 | -0.246830E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -389795559.0 | 60.05 | 0.00 | 0.00 |
March | 0.274684E+11 | -0.270429E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -425534031.8 | 60.05 | 0.00 | 0.00 |
April | 0.225101E+11 | -0.221129E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -397228073.9 | 60.05 | 0.00 | 0.00 |
May | 0.215006E+11 | -0.211188E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -381727176.0 | 60.05 | 0.00 | 0.00 |
June | 0.194824E+11 | -0.191167E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -365688953.0 | 60.05 | 0.00 | 0.00 |
July | 0.180056E+11 | -0.176362E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -369486188.8 | 60.05 | 0.00 | 0.00 |
August | 0.205203E+11 | -0.201569E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -363420042.9 | 60.05 | 0.00 | 0.00 |
September | 0.205161E+11 | -0.201605E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -355620616.0 | 60.05 | 0.00 | 0.00 |
October | 0.236541E+11 | -0.232840E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -370054273.6 | 60.05 | 0.00 | 0.00 |
November | 0.256041E+11 | -0.252094E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -394720090.5 | 60.05 | 0.00 | 0.00 |
December | 0.271825E+11 | -0.267502E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -432377951.5 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.279879E+12 | -0.275193E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.468588E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.180056E+11 | -0.279220E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -440230137.9 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.283622E+11 | -0.176362E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -355620616.0 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.52 | 0.48 | 01-JAN-08:09 | 4206.95 | 34.39 | 311.00 | 293.00 | 1086.35 | 25.76 | 306.67 | 280.50 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-08:20 | 2178.86 | 26.04 | 162.33 | 274.83 | 970.93 | 21.72 | 216.00 | 244.50 |
March | 357.50 | 0.53 | 0.48 | 01-MAR-08:30 | 1611.77 | 20.07 | 43.33 | 314.83 | 831.32 | 21.25 | 243.33 | 277.33 |
April | 375.00 | 0.54 | 0.48 | 01-APR-07:49 | 1264.12 | 19.01 | 0.67 | 323.00 | 666.57 | 20.29 | 227.50 | 285.00 |
May | 405.33 | 0.54 | 0.48 | 01-MAY-07:30 | 1078.55 | 18.95 | 0.00 | 350.00 | 589.28 | 20.26 | 189.00 | 304.67 |
June | 403.50 | 0.54 | 0.48 | 01-JUN-07:30 | 1033.72 | 18.88 | 0.00 | 344.33 | 574.05 | 20.23 | 191.00 | 299.17 |
July | 405.00 | 0.54 | 0.48 | 01-JUL-07:30 | 1085.61 | 18.81 | 0.00 | 345.17 | 595.44 | 20.15 | 222.67 | 304.50 |
August | 395.83 | 0.54 | 0.48 | 01-AUG-07:30 | 1271.25 | 19.28 | 14.50 | 343.50 | 678.75 | 20.61 | 262.17 | 304.50 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-07:30 | 1584.75 | 20.04 | 73.67 | 318.67 | 830.55 | 21.37 | 258.17 | 285.17 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:30 | 2105.65 | 21.90 | 118.67 | 316.83 | 997.41 | 22.24 | 272.67 | 288.00 |
November | 318.83 | 0.50 | 0.48 | 01-NOV-07:19 | 3546.05 | 32.31 | 258.00 | 298.17 | 1126.10 | 25.41 | 312.83 | 281.83 |
December | 319.00 | 0.51 | 0.48 | 01-DEC-07:30 | 4194.97 | 34.75 | 308.17 | 289.00 | 1159.91 | 26.90 | 301.17 | 275.50 |
Annual Sum or Average | 4323.33 | 0.53 | 2003.86 | 23.20 | 1290.33 | 3811.33 | 822.80 | 22.00 | 3003.17 | 3430.67 | ||
Minimum of Months | 308.33 | 0.50 | 0.48 | 1033.72 | 18.81 | 0.00 | 274.83 | 574.05 | 20.15 | 189.00 | 244.50 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 4206.95 | 34.75 | 311.00 | 350.00 | 1159.91 | 26.90 | 312.83 | 304.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.54 | 0.48 | 01-JAN-07:00 | 1550.21 | 23.79 | 112.00 | 275.67 | 809.19 | 23.86 | 173.83 | 237.00 |
February | 308.33 | 0.53 | 0.48 | 01-FEB-07:49 | 1675.94 | 23.50 | 102.67 | 263.33 | 719.18 | 22.43 | 156.33 | 228.17 |
March | 357.50 | 0.53 | 0.48 | 01-MAR-07:00 | 1579.30 | 22.76 | 97.50 | 309.67 | 801.58 | 23.03 | 168.00 | 271.83 |
April | 375.00 | 0.54 | 0.48 | 01-APR-06:00 | 1834.02 | 22.66 | 109.50 | 320.67 | 933.74 | 22.98 | 151.83 | 284.83 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-06:30 | 2080.75 | 23.42 | 129.50 | 359.50 | 881.22 | 22.70 | 159.67 | 321.83 |
June | 403.50 | 0.53 | 0.48 | 01-JUN-06:10 | 2004.97 | 23.34 | 126.50 | 353.67 | 870.20 | 22.79 | 165.83 | 318.83 |
July | 405.00 | 0.53 | 0.48 | 01-JUL-06:40 | 1889.36 | 23.07 | 123.67 | 348.33 | 831.79 | 22.47 | 168.83 | 312.83 |
August | 395.83 | 0.53 | 0.48 | 01-AUG-06:40 | 1937.54 | 22.78 | 114.17 | 341.67 | 864.48 | 22.18 | 173.67 | 308.00 |
September | 358.83 | 0.53 | 0.48 | 01-SEP-06:49 | 1934.99 | 23.60 | 107.00 | 311.67 | 991.35 | 23.91 | 184.00 | 285.50 |
October | 351.17 | 0.53 | 0.48 | 01-OCT-06:49 | 1801.69 | 23.60 | 107.00 | 305.50 | 926.10 | 23.80 | 194.83 | 275.83 |
November | 318.83 | 0.52 | 0.48 | 01-NOV-06:00 | 1557.77 | 23.63 | 93.83 | 279.50 | 797.73 | 23.75 | 179.67 | 244.50 |
December | 319.00 | 0.54 | 0.48 | 01-DEC-07:19 | 1282.29 | 22.58 | 86.00 | 269.83 | 663.28 | 22.69 | 162.17 | 226.33 |
Annual Sum or Average | 4323.33 | 0.53 | 1778.77 | 23.22 | 1309.33 | 3739.00 | 845.58 | 23.02 | 2038.67 | 3315.50 | ||
Minimum of Months | 308.33 | 0.52 | 0.48 | 1282.29 | 22.58 | 86.00 | 263.33 | 663.28 | 22.18 | 151.83 | 226.33 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 2080.75 | 23.79 | 129.50 | 359.50 | 991.35 | 23.91 | 194.83 | 321.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.57 | 0.48 | 01-JAN-10:30 | 607.43 | 16.89 | 0.00 | 260.33 | 348.59 | 18.20 | 0.00 | 181.00 |
February | 308.33 | 0.55 | 0.48 | 01-FEB-09:09 | 690.78 | 17.73 | 0.00 | 253.67 | 395.48 | 19.04 | 0.00 | 192.67 |
March | 357.50 | 0.54 | 0.48 | 01-MAR-09:09 | 804.92 | 18.36 | 0.00 | 306.33 | 454.48 | 19.62 | 1.50 | 255.33 |
April | 375.00 | 0.54 | 0.48 | 01-APR-07:49 | 921.46 | 18.59 | 0.00 | 327.17 | 513.06 | 19.83 | 78.50 | 287.00 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-07:10 | 1084.96 | 19.62 | 3.50 | 368.50 | 594.83 | 20.83 | 188.67 | 334.33 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-06:49 | 1198.96 | 22.47 | 99.33 | 366.00 | 644.31 | 21.26 | 239.17 | 332.17 |
July | 405.00 | 0.53 | 0.48 | 01-JUL-06:00 | 1160.00 | 20.51 | 42.50 | 359.00 | 628.71 | 21.85 | 256.00 | 327.33 |
August | 395.83 | 0.53 | 0.48 | 01-AUG-07:10 | 1051.99 | 19.27 | 0.17 | 350.50 | 583.82 | 20.59 | 189.50 | 316.17 |
September | 358.83 | 0.53 | 0.48 | 01-SEP-07:40 | 919.30 | 18.98 | 0.00 | 317.17 | 522.86 | 20.29 | 74.67 | 275.67 |
October | 351.17 | 0.54 | 0.48 | 01-OCT-07:00 | 761.75 | 18.12 | 0.00 | 300.50 | 443.47 | 19.45 | 1.67 | 248.17 |
November | 318.83 | 0.55 | 0.48 | 01-NOV-08:20 | 659.67 | 17.80 | 0.00 | 263.00 | 385.41 | 19.18 | 0.00 | 200.00 |
December | 319.00 | 0.57 | 0.48 | 01-DEC-09:09 | 589.02 | 17.01 | 0.00 | 250.33 | 338.50 | 18.35 | 0.00 | 161.33 |
Annual Sum or Average | 4323.33 | 0.54 | 890.30 | 18.90 | 145.50 | 3722.50 | 497.56 | 19.97 | 1029.67 | 3111.17 | ||
Minimum of Months | 308.33 | 0.52 | 0.48 | 589.02 | 16.89 | 0.00 | 250.33 | 338.50 | 18.20 | 0.00 | 161.33 | |
Maximum of Months | 405.33 | 0.57 | 0.48 | 1198.96 | 22.47 | 99.33 | 368.50 | 644.31 | 21.85 | 256.00 | 334.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.54 | 0.48 | 01-JAN-10:09 | 1503.82 | 23.50 | 108.17 | 274.33 | 778.00 | 23.60 | 176.33 | 235.67 |
February | 308.33 | 0.54 | 0.48 | 01-FEB-09:30 | 1474.79 | 22.30 | 76.33 | 262.33 | 740.09 | 22.45 | 159.33 | 224.33 |
March | 357.50 | 0.53 | 0.48 | 01-MAR-09:20 | 1691.39 | 22.96 | 96.67 | 310.00 | 853.57 | 23.14 | 176.83 | 273.33 |
April | 375.00 | 0.54 | 0.48 | 01-APR-08:39 | 1708.91 | 19.64 | 55.00 | 325.17 | 882.74 | 19.51 | 117.50 | 289.00 |
May | 405.33 | 0.53 | 0.48 | 01-MAY-07:00 | 1792.80 | 17.88 | 0.00 | 350.17 | 925.98 | 19.84 | 119.83 | 316.00 |
June | 403.50 | 0.53 | 0.48 | 01-JUN-07:00 | 1907.47 | 18.07 | 0.00 | 346.00 | 978.71 | 20.03 | 130.33 | 313.33 |
July | 405.00 | 0.54 | 0.48 | 01-JUL-08:09 | 1826.58 | 18.05 | 3.67 | 348.33 | 826.64 | 19.78 | 131.67 | 310.83 |
August | 395.83 | 0.53 | 0.48 | 01-AUG-08:09 | 1864.73 | 20.13 | 59.83 | 342.67 | 958.06 | 20.17 | 143.67 | 309.33 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-08:09 | 1805.58 | 22.22 | 87.17 | 318.17 | 924.81 | 22.60 | 175.17 | 287.33 |
October | 351.17 | 0.53 | 0.48 | 01-OCT-08:20 | 1864.72 | 23.83 | 110.33 | 303.67 | 959.22 | 24.02 | 194.00 | 274.33 |
November | 318.83 | 0.52 | 0.48 | 01-NOV-08:30 | 1622.10 | 24.04 | 99.50 | 278.33 | 832.49 | 24.13 | 181.67 | 245.50 |
December | 319.00 | 0.54 | 0.48 | 01-DEC-09:09 | 1417.63 | 23.64 | 101.83 | 269.67 | 726.93 | 23.71 | 173.50 | 228.00 |
Annual Sum or Average | 4323.33 | 0.53 | 1719.82 | 21.15 | 798.50 | 3728.83 | 871.43 | 21.77 | 1879.83 | 3307.00 | ||
Minimum of Months | 308.33 | 0.52 | 0.48 | 1417.63 | 17.88 | 0.00 | 262.33 | 726.93 | 19.51 | 117.50 | 224.33 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 1907.47 | 24.04 | 110.33 | 350.17 | 978.71 | 24.13 | 194.00 | 316.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.52 | 0.48 | 01-JAN-08:09 | 4227.10 | 33.85 | 310.17 | 293.00 | 1152.35 | 21.85 | 91.50 | 281.00 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-08:09 | 2197.95 | 22.16 | 140.83 | 274.83 | 1033.51 | 16.95 | 0.00 | 246.67 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-08:30 | 1628.94 | 13.69 | 5.00 | 315.33 | 884.29 | 16.87 | 0.00 | 281.33 |
April | 375.00 | 0.54 | 0.48 | 01-APR-07:49 | 1279.41 | 13.02 | 0.00 | 323.50 | 708.54 | 16.31 | 0.00 | 289.83 |
May | 405.33 | 0.53 | 0.48 | 01-MAY-07:19 | 1093.58 | 13.10 | 0.00 | 350.17 | 626.59 | 16.46 | 0.00 | 310.50 |
June | 403.50 | 0.54 | 0.48 | 01-JUN-07:19 | 1048.75 | 12.95 | 0.00 | 344.50 | 610.49 | 16.36 | 0.00 | 304.67 |
July | 405.00 | 0.54 | 0.48 | 01-JUL-07:19 | 1100.73 | 12.78 | 0.00 | 345.33 | 633.00 | 16.13 | 0.00 | 308.50 |
August | 395.83 | 0.53 | 0.48 | 01-AUG-07:19 | 1287.18 | 13.33 | 0.00 | 344.17 | 721.28 | 16.67 | 0.00 | 308.83 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-07:30 | 1604.49 | 13.92 | 0.00 | 318.83 | 883.21 | 17.32 | 0.00 | 289.50 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:19 | 2135.07 | 16.00 | 34.50 | 317.67 | 1062.05 | 18.04 | 10.50 | 291.50 |
November | 318.83 | 0.50 | 0.48 | 01-NOV-07:10 | 3565.43 | 30.56 | 255.33 | 298.33 | 1197.09 | 21.60 | 76.33 | 284.17 |
December | 319.00 | 0.51 | 0.48 | 01-DEC-07:30 | 4206.06 | 34.29 | 306.00 | 289.50 | 1226.35 | 23.27 | 113.00 | 276.50 |
Annual Sum or Average | 4323.33 | 0.53 | 2021.45 | 18.48 | 1051.83 | 3815.17 | 874.32 | 17.98 | 291.33 | 3473.00 | ||
Minimum of Months | 308.33 | 0.50 | 0.48 | 1048.75 | 12.78 | 0.00 | 274.83 | 610.49 | 16.13 | 0.00 | 246.67 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 4227.10 | 34.29 | 310.17 | 350.17 | 1226.35 | 23.27 | 113.00 | 310.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.54 | 0.48 | 01-JAN-07:00 | 1575.67 | 21.26 | 111.83 | 276.50 | 844.05 | 21.91 | 80.67 | 241.00 |
February | 308.33 | 0.53 | 0.48 | 01-FEB-07:49 | 1705.66 | 20.79 | 102.33 | 263.67 | 756.61 | 20.06 | 47.17 | 231.50 |
March | 357.50 | 0.53 | 0.48 | 01-MAR-07:00 | 1616.48 | 19.73 | 97.33 | 310.33 | 842.59 | 20.67 | 66.00 | 276.17 |
April | 375.00 | 0.54 | 0.48 | 01-APR-06:00 | 1857.20 | 19.74 | 109.33 | 321.17 | 977.49 | 20.71 | 79.67 | 288.83 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-06:19 | 2097.35 | 19.66 | 119.33 | 360.00 | 928.55 | 20.21 | 67.83 | 326.17 |
June | 403.50 | 0.53 | 0.48 | 01-JUN-06:10 | 2035.48 | 20.37 | 125.83 | 354.67 | 916.53 | 20.27 | 66.67 | 322.17 |
July | 405.00 | 0.53 | 0.48 | 01-JUL-06:40 | 1913.22 | 19.26 | 114.17 | 349.00 | 877.55 | 19.91 | 61.83 | 316.17 |
August | 395.83 | 0.53 | 0.48 | 01-AUG-06:30 | 1957.16 | 19.87 | 113.67 | 342.33 | 911.20 | 19.65 | 56.00 | 311.33 |
September | 358.83 | 0.53 | 0.48 | 01-SEP-06:49 | 1968.41 | 20.72 | 107.00 | 312.00 | 1037.89 | 21.68 | 77.33 | 288.17 |
October | 351.17 | 0.53 | 0.48 | 01-OCT-06:49 | 1838.63 | 20.67 | 104.67 | 306.50 | 969.32 | 21.67 | 75.83 | 279.33 |
November | 318.83 | 0.52 | 0.48 | 01-NOV-06:00 | 1574.69 | 19.87 | 84.33 | 279.83 | 836.55 | 21.62 | 63.00 | 249.33 |
December | 319.00 | 0.54 | 0.48 | 01-DEC-07:19 | 1304.62 | 19.74 | 85.17 | 271.00 | 695.48 | 20.53 | 55.67 | 231.83 |
Annual Sum or Average | 4323.33 | 0.53 | 1804.99 | 20.12 | 1275.00 | 3747.00 | 887.99 | 20.70 | 797.67 | 3362.00 | ||
Minimum of Months | 308.33 | 0.52 | 0.48 | 1304.62 | 19.26 | 84.33 | 263.67 | 695.48 | 19.65 | 47.17 | 231.50 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 2097.35 | 21.26 | 125.83 | 360.00 | 1037.89 | 21.91 | 80.67 | 326.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.56 | 0.48 | 01-JAN-10:09 | 616.92 | 11.13 | 0.00 | 260.83 | 370.63 | 14.52 | 0.00 | 194.33 |
February | 308.33 | 0.55 | 0.48 | 01-FEB-09:09 | 701.81 | 11.88 | 0.00 | 253.83 | 420.57 | 15.32 | 0.00 | 201.83 |
March | 357.50 | 0.53 | 0.48 | 01-MAR-08:00 | 817.93 | 12.58 | 0.00 | 306.83 | 483.37 | 15.95 | 0.00 | 260.67 |
April | 375.00 | 0.53 | 0.48 | 01-APR-07:49 | 936.16 | 12.95 | 0.00 | 327.67 | 545.65 | 16.26 | 0.00 | 292.00 |
May | 405.33 | 0.51 | 0.48 | 01-MAY-06:00 | 1102.13 | 13.78 | 2.83 | 368.83 | 632.68 | 17.17 | 1.17 | 339.00 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-06:30 | 1217.34 | 17.76 | 77.33 | 366.50 | 688.92 | 18.85 | 34.17 | 339.33 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-06:00 | 1177.35 | 14.90 | 26.83 | 359.33 | 668.13 | 18.18 | 27.33 | 331.33 |
August | 395.83 | 0.53 | 0.48 | 01-AUG-07:10 | 1068.33 | 13.51 | 0.00 | 350.50 | 620.68 | 16.90 | 0.00 | 319.67 |
September | 358.83 | 0.53 | 0.48 | 01-SEP-07:30 | 934.15 | 13.48 | 0.00 | 317.33 | 556.08 | 16.84 | 0.00 | 281.00 |
October | 351.17 | 0.54 | 0.48 | 01-OCT-07:49 | 774.26 | 12.68 | 0.00 | 300.83 | 471.75 | 16.08 | 0.00 | 253.83 |
November | 318.83 | 0.54 | 0.48 | 01-NOV-08:09 | 670.05 | 12.13 | 0.00 | 263.67 | 409.87 | 15.65 | 0.00 | 210.00 |
December | 319.00 | 0.56 | 0.48 | 01-DEC-08:00 | 597.88 | 11.09 | 0.00 | 251.17 | 359.82 | 14.56 | 0.00 | 175.83 |
Annual Sum or Average | 4323.33 | 0.53 | 904.27 | 13.29 | 107.00 | 3727.33 | 529.44 | 16.47 | 62.67 | 3198.83 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 597.88 | 11.09 | 0.00 | 251.17 | 359.82 | 14.52 | 0.00 | 175.83 | |
Maximum of Months | 405.33 | 0.56 | 0.48 | 1217.34 | 17.76 | 77.33 | 368.83 | 688.92 | 18.85 | 34.17 | 339.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.54 | 0.48 | 01-JAN-09:00 | 1528.96 | 20.95 | 108.17 | 276.00 | 812.53 | 21.64 | 77.17 | 241.33 |
February | 308.33 | 0.53 | 0.48 | 01-FEB-09:20 | 1505.21 | 19.18 | 76.33 | 263.00 | 778.47 | 20.06 | 48.33 | 228.17 |
March | 357.50 | 0.53 | 0.48 | 01-MAR-09:20 | 1731.58 | 19.88 | 96.67 | 311.17 | 897.43 | 20.75 | 65.67 | 278.33 |
April | 375.00 | 0.53 | 0.48 | 01-APR-08:30 | 1730.52 | 16.00 | 55.00 | 326.17 | 925.61 | 16.39 | 0.00 | 292.67 |
May | 405.33 | 0.53 | 0.48 | 01-MAY-07:00 | 1816.26 | 13.44 | 0.00 | 351.67 | 972.32 | 16.67 | 0.00 | 321.00 |
June | 403.50 | 0.53 | 0.48 | 01-JUN-07:49 | 1939.25 | 13.61 | 0.00 | 347.17 | 1025.54 | 16.85 | 0.00 | 317.00 |
July | 405.00 | 0.53 | 0.48 | 01-JUL-07:00 | 1852.62 | 13.65 | 3.67 | 349.33 | 872.37 | 16.65 | 0.00 | 314.83 |
August | 395.83 | 0.53 | 0.48 | 01-AUG-07:00 | 1882.68 | 16.47 | 59.83 | 343.00 | 1004.89 | 17.09 | 5.50 | 312.83 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-08:09 | 1832.28 | 19.12 | 86.83 | 318.50 | 971.36 | 20.16 | 57.33 | 290.17 |
October | 351.17 | 0.53 | 0.48 | 01-OCT-08:20 | 1903.47 | 21.13 | 110.33 | 304.67 | 1002.32 | 21.92 | 79.33 | 277.50 |
November | 318.83 | 0.52 | 0.48 | 01-NOV-08:30 | 1650.23 | 21.31 | 98.67 | 279.17 | 871.76 | 22.07 | 69.00 | 249.50 |
December | 319.00 | 0.54 | 0.48 | 01-DEC-08:00 | 1441.42 | 20.96 | 101.83 | 270.50 | 760.50 | 21.68 | 71.00 | 233.83 |
Annual Sum or Average | 4323.33 | 0.53 | 1747.52 | 17.71 | 797.33 | 3740.33 | 914.14 | 19.14 | 473.33 | 3357.17 | ||
Minimum of Months | 308.33 | 0.52 | 0.48 | 1441.42 | 13.44 | 0.00 | 263.00 | 760.50 | 16.39 | 0.00 | 228.17 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 1939.25 | 21.31 | 110.33 | 351.67 | 1025.54 | 22.07 | 79.33 | 321.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.52 | 0.48 | 01-JAN-08:09 | 4229.75 | 33.84 | 310.17 | 293.00 | 1154.36 | 21.84 | 91.50 | 281.00 |
February | 308.33 | 0.52 | 0.48 | 01-FEB-08:09 | 2200.97 | 22.14 | 140.67 | 275.00 | 1035.39 | 16.93 | 0.00 | 246.67 |
March | 357.50 | 0.52 | 0.48 | 01-MAR-08:30 | 1631.67 | 13.66 | 5.00 | 315.50 | 885.87 | 16.86 | 0.00 | 281.50 |
April | 375.00 | 0.54 | 0.48 | 01-APR-07:49 | 1281.50 | 13.00 | 0.00 | 323.50 | 709.75 | 16.30 | 0.00 | 290.17 |
May | 405.33 | 0.53 | 0.48 | 01-MAY-07:19 | 1095.19 | 13.07 | 0.00 | 350.17 | 627.57 | 16.45 | 0.00 | 310.83 |
June | 403.50 | 0.54 | 0.48 | 01-JUN-07:19 | 1050.21 | 12.92 | 0.00 | 344.50 | 611.42 | 16.35 | 0.00 | 304.67 |
July | 405.00 | 0.54 | 0.48 | 01-JUL-07:19 | 1102.32 | 12.75 | 0.00 | 345.33 | 633.99 | 16.11 | 0.00 | 308.67 |
August | 395.83 | 0.53 | 0.48 | 01-AUG-07:19 | 1289.17 | 13.30 | 0.00 | 344.17 | 722.48 | 16.66 | 0.00 | 309.00 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-07:30 | 1607.09 | 13.90 | 0.00 | 318.83 | 884.74 | 17.30 | 0.00 | 289.50 |
October | 351.17 | 0.52 | 0.48 | 01-OCT-07:19 | 2138.09 | 15.98 | 34.50 | 317.67 | 1063.91 | 18.03 | 10.50 | 291.50 |
November | 318.83 | 0.50 | 0.48 | 01-NOV-07:10 | 3568.36 | 30.55 | 255.33 | 298.33 | 1199.17 | 21.59 | 76.33 | 284.17 |
December | 319.00 | 0.51 | 0.48 | 01-DEC-07:30 | 4208.53 | 34.28 | 306.00 | 289.50 | 1228.38 | 23.26 | 113.00 | 276.50 |
Annual Sum or Average | 4323.33 | 0.53 | 2023.75 | 18.46 | 1051.67 | 3815.50 | 875.80 | 17.97 | 291.33 | 3474.17 | ||
Minimum of Months | 308.33 | 0.50 | 0.48 | 1050.21 | 12.75 | 0.00 | 275.00 | 611.42 | 16.11 | 0.00 | 246.67 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 4229.75 | 34.28 | 310.17 | 350.17 | 1228.38 | 23.26 | 113.00 | 310.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.54 | 0.48 | 01-JAN-07:00 | 1577.02 | 21.24 | 111.83 | 276.67 | 845.16 | 21.90 | 80.67 | 241.00 |
February | 308.33 | 0.53 | 0.48 | 01-FEB-07:49 | 1707.25 | 20.77 | 102.33 | 263.67 | 757.80 | 20.04 | 47.17 | 231.67 |
March | 357.50 | 0.53 | 0.48 | 01-MAR-07:00 | 1618.38 | 19.70 | 97.33 | 310.33 | 843.84 | 20.66 | 66.00 | 276.67 |
April | 375.00 | 0.54 | 0.48 | 01-APR-06:00 | 1859.10 | 19.72 | 109.33 | 321.17 | 978.76 | 20.70 | 79.67 | 289.00 |
May | 405.33 | 0.52 | 0.48 | 01-MAY-06:19 | 2099.20 | 19.64 | 119.33 | 360.00 | 929.85 | 20.20 | 67.83 | 326.17 |
June | 403.50 | 0.53 | 0.48 | 01-JUN-06:10 | 2037.37 | 20.35 | 125.83 | 354.67 | 917.85 | 20.26 | 66.67 | 322.33 |
July | 405.00 | 0.53 | 0.48 | 01-JUL-06:40 | 1915.18 | 19.23 | 114.17 | 349.17 | 878.88 | 19.90 | 61.83 | 316.50 |
August | 395.83 | 0.53 | 0.48 | 01-AUG-06:30 | 1959.15 | 19.85 | 113.67 | 342.33 | 912.59 | 19.63 | 56.00 | 311.33 |
September | 358.83 | 0.53 | 0.48 | 01-SEP-06:49 | 1970.37 | 20.69 | 107.00 | 312.33 | 1039.30 | 21.67 | 77.33 | 288.33 |
October | 351.17 | 0.53 | 0.48 | 01-OCT-06:49 | 1840.21 | 20.65 | 104.67 | 306.50 | 970.64 | 21.66 | 75.83 | 279.33 |
November | 318.83 | 0.52 | 0.48 | 01-NOV-06:00 | 1576.10 | 19.84 | 84.33 | 279.67 | 837.72 | 21.61 | 63.00 | 249.33 |
December | 319.00 | 0.54 | 0.48 | 01-DEC-07:19 | 1305.90 | 19.71 | 85.17 | 271.00 | 696.53 | 20.52 | 55.67 | 231.83 |
Annual Sum or Average | 4323.33 | 0.53 | 1806.73 | 20.09 | 1275.00 | 3747.50 | 889.26 | 20.69 | 797.67 | 3363.50 | ||
Minimum of Months | 308.33 | 0.52 | 0.48 | 1305.90 | 19.23 | 84.33 | 263.67 | 696.53 | 19.63 | 47.17 | 231.67 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 2099.20 | 21.24 | 125.83 | 360.00 | 1039.30 | 21.90 | 80.67 | 326.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.56 | 0.48 | 01-JAN-10:09 | 617.63 | 11.10 | 0.00 | 261.00 | 371.18 | 14.51 | 0.00 | 194.33 |
February | 308.33 | 0.55 | 0.48 | 01-FEB-09:09 | 702.64 | 11.85 | 0.00 | 253.83 | 421.19 | 15.30 | 0.00 | 201.83 |
March | 357.50 | 0.53 | 0.48 | 01-MAR-08:00 | 818.98 | 12.55 | 0.00 | 307.00 | 484.10 | 15.94 | 0.00 | 260.67 |
April | 375.00 | 0.53 | 0.48 | 01-APR-07:49 | 937.42 | 12.93 | 0.00 | 327.67 | 546.49 | 16.24 | 0.00 | 292.33 |
May | 405.33 | 0.51 | 0.48 | 01-MAY-06:00 | 1103.63 | 13.75 | 2.83 | 368.83 | 633.66 | 17.15 | 1.17 | 339.00 |
June | 403.50 | 0.52 | 0.48 | 01-JUN-06:30 | 1219.01 | 17.74 | 77.33 | 366.50 | 690.02 | 18.84 | 34.17 | 339.33 |
July | 405.00 | 0.52 | 0.48 | 01-JUL-06:00 | 1178.99 | 14.88 | 26.83 | 359.33 | 669.20 | 18.16 | 27.17 | 331.50 |
August | 395.83 | 0.53 | 0.48 | 01-AUG-07:10 | 1069.74 | 13.48 | 0.00 | 350.50 | 621.64 | 16.89 | 0.00 | 319.67 |
September | 358.83 | 0.53 | 0.48 | 01-SEP-07:30 | 935.27 | 13.45 | 0.00 | 317.50 | 556.90 | 16.82 | 0.00 | 281.33 |
October | 351.17 | 0.54 | 0.48 | 01-OCT-07:49 | 775.10 | 12.65 | 0.00 | 300.83 | 472.42 | 16.07 | 0.00 | 254.17 |
November | 318.83 | 0.54 | 0.48 | 01-NOV-08:09 | 670.75 | 12.10 | 0.00 | 263.67 | 410.45 | 15.63 | 0.00 | 210.00 |
December | 319.00 | 0.56 | 0.48 | 01-DEC-08:00 | 598.55 | 11.06 | 0.00 | 251.17 | 360.35 | 14.55 | 0.00 | 176.00 |
Annual Sum or Average | 4323.33 | 0.53 | 905.42 | 13.26 | 107.00 | 3727.83 | 530.24 | 16.45 | 62.50 | 3200.17 | ||
Minimum of Months | 308.33 | 0.51 | 0.48 | 598.55 | 11.06 | 0.00 | 251.17 | 360.35 | 14.51 | 0.00 | 176.00 | |
Maximum of Months | 405.33 | 0.56 | 0.48 | 1219.01 | 17.74 | 77.33 | 368.83 | 690.02 | 18.84 | 34.17 | 339.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 325.00 | 0.54 | 0.48 | 01-JAN-09:00 | 1530.31 | 20.92 | 108.17 | 276.00 | 813.64 | 21.63 | 77.17 | 241.33 |
February | 308.33 | 0.53 | 0.48 | 01-FEB-09:20 | 1506.82 | 19.16 | 76.33 | 263.00 | 779.68 | 20.05 | 48.33 | 228.17 |
March | 357.50 | 0.53 | 0.48 | 01-MAR-09:20 | 1722.86 | 18.74 | 85.83 | 310.33 | 898.72 | 20.74 | 65.67 | 278.50 |
April | 375.00 | 0.53 | 0.48 | 01-APR-08:30 | 1732.44 | 15.97 | 55.00 | 326.17 | 926.91 | 16.38 | 0.00 | 292.83 |
May | 405.33 | 0.53 | 0.48 | 01-MAY-07:00 | 1818.14 | 13.40 | 0.00 | 351.67 | 973.63 | 16.65 | 0.00 | 321.33 |
June | 403.50 | 0.53 | 0.48 | 01-JUN-07:49 | 1941.21 | 13.58 | 0.00 | 347.33 | 1026.88 | 16.84 | 0.00 | 317.00 |
July | 405.00 | 0.53 | 0.48 | 01-JUL-07:00 | 1854.62 | 13.62 | 3.67 | 349.50 | 873.73 | 16.63 | 0.00 | 315.33 |
August | 395.83 | 0.53 | 0.48 | 01-AUG-07:00 | 1884.73 | 16.44 | 59.83 | 343.00 | 1006.32 | 17.08 | 5.50 | 312.83 |
September | 358.83 | 0.52 | 0.48 | 01-SEP-08:09 | 1834.32 | 19.09 | 86.83 | 318.50 | 972.79 | 20.14 | 57.33 | 290.33 |
October | 351.17 | 0.53 | 0.48 | 01-OCT-08:20 | 1905.17 | 21.11 | 110.33 | 304.67 | 1003.62 | 21.90 | 79.33 | 277.50 |
November | 318.83 | 0.52 | 0.48 | 01-NOV-08:30 | 1651.62 | 21.29 | 98.67 | 279.17 | 872.93 | 22.06 | 69.00 | 249.67 |
December | 319.00 | 0.54 | 0.48 | 01-DEC-08:00 | 1442.72 | 20.93 | 101.83 | 270.50 | 761.56 | 21.67 | 71.00 | 233.83 |
Annual Sum or Average | 4323.33 | 0.53 | 1748.42 | 17.59 | 786.50 | 3739.83 | 915.42 | 19.12 | 473.33 | 3358.67 | ||
Minimum of Months | 308.33 | 0.52 | 0.48 | 1442.72 | 13.40 | 0.00 | 263.00 | 761.56 | 16.38 | 0.00 | 228.17 | |
Maximum of Months | 405.33 | 0.54 | 0.48 | 1941.21 | 21.29 | 110.33 | 351.67 | 1026.88 | 22.06 | 79.33 | 321.33 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 55057840.51 | 2516.51 | 02-JAN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4963258.75 | 875.19 | 13-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4277786.44 | 692.93 | 18-DEC-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 64298885.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 55057840.51 | 2516.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 26468886.10 | 2042.59 | 02-JAN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1788374.46 | 589.89 | 13-FEB-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2240452.95 | 673.45 | 18-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 30497713.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26468886.10 | 2042.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 2916958.00 | 745.39 | 20-JAN-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2916958.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2916958.00 | 745.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 23936637.91 | 1533.75 | 20-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 566874.96 | 146.53 | 13-FEB-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 24503512.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23936637.91 | 1533.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.790113E+11 | 0.760340E+11 | 239705.30 | 30-JAN-05:12 | 167959.42 | 0.56 |
February | 0.00 | 0.00 | 0.976002E+11 | 0.913336E+11 | 267882.68 | 09-FEB-05:12 | 183619.05 | 0.61 |
March | 0.00 | 0.00 | 0.146046E+12 | 0.137738E+12 | 232471.65 | 24-MAR-05:02 | 158422.90 | 0.70 |
April | 0.00 | 0.00 | 0.193752E+12 | 0.173831E+12 | 248454.30 | 08-APR-05:02 | 171799.58 | 0.82 |
May | 0.00 | 0.00 | 0.275630E+12 | 0.236778E+12 | 322583.13 | 30-MAY-04:12 | 205269.27 | 0.85 |
June | 0.00 | 0.00 | 0.338324E+12 | 0.259080E+12 | 332456.03 | 11-JUN-13:02 | 216739.85 | 0.89 |
July | 0.00 | 0.00 | 0.397963E+12 | 0.289687E+12 | 356138.29 | 24-JUL-03:02 | 220443.98 | 0.88 |
August | 0.00 | 0.00 | 0.439625E+12 | 0.319820E+12 | 356598.47 | 08-AUG-03:02 | 210724.59 | 0.89 |
September | 0.00 | 0.00 | 0.348590E+12 | 0.252474E+12 | 340131.10 | 11-SEP-03:02 | 210271.93 | 0.87 |
October | 0.00 | 0.00 | 0.293635E+12 | 0.234061E+12 | 323831.14 | 02-OCT-04:12 | 204363.13 | 0.84 |
November | 0.00 | 0.00 | 0.193738E+12 | 0.167395E+12 | 283456.32 | 01-NOV-05:02 | 188432.63 | 0.77 |
December | 0.00 | 0.00 | 0.123668E+12 | 0.112241E+12 | 251653.60 | 11-DEC-06:02 | 174277.50 | 0.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.292758E+13 | 0.235047E+13 | 0.78 | |||
Minimum of Months | 0.00 | 0.00 | 0.790113E+11 | 0.760340E+11 | 232471.65 | 158422.90 | 0.56 | |
Maximum of Months | 0.00 | 0.00 | 0.439625E+12 | 0.319820E+12 | 356598.47 | 220443.98 | 0.89 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.582513E+12 | 0.558953E+12 | 1588408.28 | 30-JAN-06:03 | 1063103.90 | 0.54 |
February | 0.00 | 0.00 | 0.674535E+12 | 0.625564E+12 | 2158885.85 | 06-FEB-06:02 | 1506019.94 | 0.57 |
March | 0.00 | 0.00 | 0.992814E+12 | 0.927118E+12 | 2186741.68 | 29-MAR-05:02 | 1492078.97 | 0.60 |
April | 0.00 | 0.00 | 0.129662E+13 | 0.114875E+13 | 2411739.19 | 20-APR-04:12 | 1579717.72 | 0.65 |
May | 0.00 | 0.00 | 0.206309E+13 | 0.171347E+13 | 2825276.34 | 24-MAY-05:02 | 1711310.03 | 0.78 |
June | 0.00 | 0.00 | 0.261862E+13 | 0.186385E+13 | 2841680.72 | 04-JUN-16:11 | 1563876.86 | 0.84 |
July | 0.00 | 0.00 | 0.312218E+13 | 0.206821E+13 | 3196787.87 | 06-JUL-05:02 | 1819665.37 | 0.85 |
August | 0.00 | 0.00 | 0.337914E+13 | 0.221245E+13 | 3235777.35 | 08-AUG-05:01 | 1788106.25 | 0.87 |
September | 0.00 | 0.00 | 0.266465E+13 | 0.176296E+13 | 3044620.19 | 28-SEP-05:02 | 1758469.96 | 0.81 |
October | 0.00 | 0.00 | 0.199781E+13 | 0.149865E+13 | 2845060.53 | 18-OCT-05:02 | 1694681.93 | 0.72 |
November | 0.00 | 0.00 | 0.129797E+13 | 0.108217E+13 | 2477759.56 | 01-NOV-04:12 | 1621190.02 | 0.62 |
December | 0.00 | 0.00 | 0.779450E+12 | 0.695622E+12 | 2149396.90 | 11-DEC-06:02 | 1410900.92 | 0.56 |
Annual Sum or Average | 0.00 | 0.00 | 0.214694E+14 | 0.161578E+14 | 0.70 | |||
Minimum of Months | 0.00 | 0.00 | 0.582513E+12 | 0.558953E+12 | 1588408.28 | 1063103.90 | 0.54 | |
Maximum of Months | 0.00 | 0.00 | 0.337914E+13 | 0.221245E+13 | 3235777.35 | 1819665.37 | 0.87 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.538507E+11 | 0.514882E+11 | 165278.96 | 30-JAN-06:03 | 108288.37 | 0.53 |
February | 0.00 | 0.00 | 0.658562E+11 | 0.609441E+11 | 220930.00 | 06-FEB-06:02 | 150396.36 | 0.55 |
March | 0.00 | 0.00 | 0.100311E+12 | 0.937291E+11 | 225623.12 | 29-MAR-05:02 | 147538.70 | 0.59 |
April | 0.00 | 0.00 | 0.135068E+12 | 0.120158E+12 | 255047.36 | 18-APR-03:02 | 175637.93 | 0.64 |
May | 0.00 | 0.00 | 0.219630E+12 | 0.184645E+12 | 294295.09 | 29-MAY-13:22 | 167477.43 | 0.78 |
June | 0.00 | 0.00 | 0.278212E+12 | 0.202532E+12 | 310125.97 | 25-JUN-14:32 | 172968.58 | 0.84 |
July | 0.00 | 0.00 | 0.331628E+12 | 0.226227E+12 | 355242.80 | 24-JUL-05:01 | 216896.08 | 0.86 |
August | 0.00 | 0.00 | 0.357066E+12 | 0.240762E+12 | 355118.16 | 08-AUG-05:01 | 197885.43 | 0.87 |
September | 0.00 | 0.00 | 0.279660E+12 | 0.189337E+12 | 326861.94 | 28-SEP-05:02 | 189951.60 | 0.81 |
October | 0.00 | 0.00 | 0.206180E+12 | 0.156356E+12 | 287917.20 | 18-OCT-05:02 | 170391.21 | 0.71 |
November | 0.00 | 0.00 | 0.128876E+12 | 0.107515E+12 | 245379.53 | 01-NOV-04:12 | 155315.94 | 0.61 |
December | 0.00 | 0.00 | 0.741810E+11 | 0.659674E+11 | 188498.10 | 11-DEC-06:02 | 120398.84 | 0.55 |
Annual Sum or Average | 0.00 | 0.00 | 0.223052E+13 | 0.169966E+13 | 0.70 | |||
Minimum of Months | 0.00 | 0.00 | 0.538507E+11 | 0.514882E+11 | 165278.96 | 108288.37 | 0.53 | |
Maximum of Months | 0.00 | 0.00 | 0.357066E+12 | 0.240762E+12 | 355242.80 | 216896.08 | 0.87 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.728139E+11 | 0.711012E+11 | 276292.06 | 30-JAN-21:11 | 84704.79 | 0.51 |
February | 0.00 | 0.00 | 0.581197E+11 | 0.557414E+11 | 312075.12 | 09-FEB-16:12 | 86530.22 | 0.42 |
March | 0.00 | 0.00 | 0.606604E+11 | 0.547933E+11 | 297796.46 | 24-MAR-03:23 | 81665.48 | 0.32 |
April | 0.00 | 0.00 | 0.421885E+11 | 0.343672E+11 | 303749.04 | 30-APR-03:51 | 82195.79 | 0.17 |
May | 0.00 | 0.00 | 0.729560E+10 | 0.559568E+10 | 222796.88 | 01-MAY-05:12 | 93207.42 | 0.02 |
June | 0.00 | 0.00 | 0.734394E+10 | 0.556720E+10 | 314554.20 | 22-JUN-07:51 | 83754.34 | 0.02 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.591246E+10 | 0.478400E+10 | 314716.87 | 21-OCT-03:45 | 89727.95 | 0.01 |
November | 0.00 | 0.00 | 0.641948E+11 | 0.541087E+11 | 309866.33 | 04-NOV-04:23 | 82787.85 | 0.23 |
December | 0.00 | 0.00 | 0.754585E+11 | 0.687956E+11 | 293547.07 | 12-DEC-20:51 | 89965.07 | 0.43 |
Annual Sum or Average | 0.00 | 0.00 | 0.393988E+12 | 0.354854E+12 | 0.18 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.754585E+11 | 0.711012E+11 | 314716.87 | 93207.42 | 0.51 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.355737E+12 | 0.344986E+12 | 144009.73 | 30-JAN-15:00 | 133047.51 | 0.00 |
February | 0.00 | 0.00 | 0.546859E+12 | 0.533790E+12 | 239100.78 | 07-FEB-16:10 | 227351.02 | 0.00 |
March | 0.00 | 0.00 | 0.851298E+12 | 0.838653E+12 | 408892.43 | 31-MAR-23:05 | 398397.71 | 0.00 |
April | 0.00 | 0.00 | 0.106523E+13 | 0.105184E+13 | 422975.34 | 28-APR-14:10 | 414438.91 | 0.00 |
May | 0.00 | 0.00 | 0.379179E+12 | 0.361396E+12 | 232112.17 | 31-MAY-23:03 | 221103.02 | 0.00 |
June | 0.00 | 0.00 | 0.616896E+12 | 0.589200E+12 | 330177.77 | 30-JUN-23:03 | 312209.96 | 0.00 |
July | 0.00 | 0.00 | 0.892248E+12 | 0.858850E+12 | 426021.15 | 31-JUL-23:03 | 405909.91 | 0.00 |
August | 0.00 | 0.00 | 0.114053E+13 | 0.110605E+13 | 446923.06 | 04-AUG-14:00 | 422167.47 | 0.00 |
September | 0.00 | 0.00 | 0.386507E+12 | 0.355953E+12 | 242706.63 | 30-SEP-23:03 | 220204.56 | 0.00 |
October | 0.00 | 0.00 | 0.633170E+12 | 0.609065E+12 | 320633.19 | 31-OCT-23:10 | 312098.10 | 0.00 |
November | 0.00 | 0.00 | 0.837144E+12 | 0.820160E+12 | 337385.13 | 01-NOV-15:00 | 321760.65 | 0.00 |
December | 0.00 | 0.00 | 0.110248E+13 | 0.108529E+13 | 423543.98 | 05-DEC-17:00 | 410659.15 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.880728E+13 | 0.855523E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.355737E+12 | 0.344986E+12 | 144009.73 | 133047.51 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.114053E+13 | 0.110605E+13 | 446923.06 | 422167.47 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.573873E+10 | 0.539798E+10 | 2761.29 | 30-JAN-15:00 | 2335.95 | 0.00 |
February | 0.00 | 0.00 | 0.101491E+11 | 0.969808E+10 | 4924.42 | 07-FEB-16:10 | 4431.18 | 0.00 |
March | 0.00 | 0.00 | 0.164695E+11 | 0.160024E+11 | 8145.64 | 31-MAR-23:05 | 7666.37 | 0.00 |
April | 0.00 | 0.00 | 0.212503E+11 | 0.206466E+11 | 8997.06 | 30-APR-18:00 | 8440.72 | 0.00 |
May | 0.00 | 0.00 | 0.750375E+10 | 0.676709E+10 | 4771.64 | 31-MAY-23:03 | 4320.06 | 0.00 |
June | 0.00 | 0.00 | 0.127932E+11 | 0.115934E+11 | 6933.46 | 30-JUN-23:03 | 6133.91 | 0.00 |
July | 0.00 | 0.00 | 0.188862E+11 | 0.173925E+11 | 8819.75 | 31-JUL-24:00 | 8120.47 | 0.00 |
August | 0.00 | 0.00 | 0.233069E+11 | 0.217489E+11 | 9087.30 | 27-AUG-06:00 | 8279.12 | 0.00 |
September | 0.00 | 0.00 | 0.800796E+10 | 0.672700E+10 | 5203.69 | 30-SEP-23:03 | 4218.78 | 0.00 |
October | 0.00 | 0.00 | 0.127803E+11 | 0.117474E+11 | 6412.09 | 31-OCT-23:10 | 6031.07 | 0.00 |
November | 0.00 | 0.00 | 0.165226E+11 | 0.157923E+11 | 7143.08 | 01-NOV-16:00 | 6489.97 | 0.00 |
December | 0.00 | 0.00 | 0.214399E+11 | 0.208655E+11 | 8777.91 | 05-DEC-17:00 | 8199.28 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.174848E+12 | 0.164379E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.573873E+10 | 0.539798E+10 | 2761.29 | 2335.95 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.233069E+11 | 0.217489E+11 | 9087.30 | 8440.72 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.471563E+11 | 0.439002E+11 | 25309.16 | 30-JAN-15:00 | 21147.74 | 0.00 |
February | 0.00 | 0.00 | 0.916726E+11 | 0.872224E+11 | 46540.89 | 07-FEB-16:10 | 41652.85 | 0.00 |
March | 0.00 | 0.00 | 0.154677E+12 | 0.150032E+12 | 78291.71 | 31-MAR-23:05 | 73446.13 | 0.00 |
April | 0.00 | 0.00 | 0.201685E+12 | 0.195661E+12 | 84980.04 | 30-APR-17:55 | 79358.39 | 0.00 |
May | 0.00 | 0.00 | 0.684446E+11 | 0.612180E+11 | 45163.61 | 31-MAY-23:03 | 40621.68 | 0.00 |
June | 0.00 | 0.00 | 0.119325E+12 | 0.107431E+12 | 66093.33 | 30-JUN-23:03 | 58013.39 | 0.00 |
July | 0.00 | 0.00 | 0.176047E+12 | 0.161191E+12 | 84298.06 | 31-JUL-23:03 | 75535.29 | 0.00 |
August | 0.00 | 0.00 | 0.220899E+12 | 0.205266E+12 | 86004.77 | 08-AUG-07:20 | 77026.85 | 0.00 |
September | 0.00 | 0.00 | 0.725718E+11 | 0.600047E+11 | 49248.58 | 30-SEP-23:03 | 39033.22 | 0.00 |
October | 0.00 | 0.00 | 0.118541E+12 | 0.108313E+12 | 61032.10 | 31-OCT-23:10 | 57167.61 | 0.00 |
November | 0.00 | 0.00 | 0.155274E+12 | 0.148011E+12 | 67579.98 | 01-NOV-16:00 | 61077.70 | 0.00 |
December | 0.00 | 0.00 | 0.200106E+12 | 0.194382E+12 | 83411.04 | 05-DEC-17:00 | 77641.56 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.162640E+13 | 0.152263E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.471563E+11 | 0.439002E+11 | 25309.16 | 21147.74 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.220899E+12 | 0.205266E+12 | 86004.77 | 79358.39 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.421098E+10 | 0.389453E+10 | 2564.21 | 30-JAN-15:00 | 2144.83 | 0.00 |
February | 0.00 | 0.00 | 0.888685E+10 | 0.844348E+10 | 4701.89 | 07-FEB-16:10 | 4212.06 | 0.00 |
March | 0.00 | 0.00 | 0.153239E+11 | 0.148595E+11 | 7779.00 | 31-MAR-23:05 | 7293.84 | 0.00 |
April | 0.00 | 0.00 | 0.201857E+11 | 0.195830E+11 | 8607.13 | 30-APR-18:00 | 8046.68 | 0.00 |
May | 0.00 | 0.00 | 0.696666E+10 | 0.624087E+10 | 4566.22 | 31-MAY-23:03 | 4112.95 | 0.00 |
June | 0.00 | 0.00 | 0.120673E+11 | 0.108756E+11 | 6628.45 | 30-JUN-23:03 | 5821.05 | 0.00 |
July | 0.00 | 0.00 | 0.178085E+11 | 0.163210E+11 | 8486.44 | 31-JUL-23:03 | 7609.73 | 0.00 |
August | 0.00 | 0.00 | 0.222375E+11 | 0.206747E+11 | 8650.74 | 08-AUG-07:30 | 7727.88 | 0.00 |
September | 0.00 | 0.00 | 0.738433E+10 | 0.612294E+10 | 4954.36 | 30-SEP-23:03 | 3943.65 | 0.00 |
October | 0.00 | 0.00 | 0.119099E+11 | 0.108861E+11 | 6099.90 | 31-OCT-23:10 | 5713.00 | 0.00 |
November | 0.00 | 0.00 | 0.154434E+11 | 0.147172E+11 | 6815.71 | 01-NOV-16:00 | 6164.92 | 0.00 |
December | 0.00 | 0.00 | 0.196794E+11 | 0.191074E+11 | 8369.42 | 05-DEC-17:00 | 7792.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.162104E+12 | 0.151726E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.421098E+10 | 0.389453E+10 | 2564.21 | 2144.83 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.222375E+11 | 0.206747E+11 | 8650.74 | 8046.68 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 297733.12 | 1245363.53 | 30-JAN-14:10 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 379498.47 | 1792124.18 | 07-FEB-15:20 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 506979.70 | 2010359.01 | 27-MAR-10:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 684844.12 | 2199818.43 | 26-APR-12:20 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1005228.92 | 3196613.97 | 24-MAY-05:02 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1290588.54 | 2918636.11 | 04-JUN-16:14 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 1469439.39 | 4284679.40 | 16-JUL-17:02 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1586262.63 | 4087420.18 | 21-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 1303392.52 | 3862804.64 | 09-SEP-17:08 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 976093.78 | 3505883.58 | 07-OCT-17:10 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 693834.31 | 2132200.93 | 01-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:03 |
December | 406202.81 | 1870337.46 | 06-DEC-13:50 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 886279.16 | 0.00 | ||||
Minimum of Months | 297733.12 | 1245363.53 | 0.00 | 0.00 | ||
Maximum of Months | 1586262.63 | 4284679.40 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 295203.81 | 2076490.72 | 30-JAN-06:03 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 377045.17 | 3617336.46 | 06-FEB-06:02 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 503839.17 | 4229289.62 | 29-MAR-05:02 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 680427.36 | 4211560.81 | 12-APR-04:12 | 0.00 | 0.00 | 01-APR-00:03 |
May | 999220.00 | 4590877.35 | 31-MAY-05:02 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1284330.91 | 4739036.86 | 24-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 1461956.68 | 4813277.96 | 01-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1580290.47 | 4996471.39 | 30-AUG-05:01 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 1298304.89 | 4726743.65 | 09-SEP-05:02 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 970390.50 | 4609704.35 | 10-OCT-05:02 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 688327.72 | 4236644.38 | 04-NOV-05:02 | 0.00 | 0.00 | 01-NOV-00:03 |
December | 402855.44 | 3524588.98 | 11-DEC-06:02 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 881439.53 | 0.00 | ||||
Minimum of Months | 295203.81 | 2076490.72 | 0.00 | 0.00 | ||
Maximum of Months | 1580290.47 | 4996471.39 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 363995.84 | 869270.49 | 23-JAN-14:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 631599.71 | 1370948.98 | 06-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 973337.28 | 1947446.34 | 27-MAR-11:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1402953.40 | 2425936.41 | 28-APR-12:00 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1091631.56 | 1759156.69 | 31-MAY-19:00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1423141.04 | 2075276.73 | 12-JUN-12:00 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 1791435.17 | 2505547.11 | 21-JUL-12:00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 2027918.73 | 2703891.20 | 16-AUG-12:00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 1179578.71 | 1717570.10 | 26-SEP-13:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 1197863.17 | 1730809.03 | 04-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 1139087.85 | 1676902.37 | 05-NOV-12:00 | 0.00 | 0.00 | 01-NOV-00:03 |
December | 1048147.37 | 1625738.53 | 10-DEC-12:03 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 1192744.73 | 0.00 | ||||
Minimum of Months | 363995.84 | 869270.49 | 0.00 | 0.00 | ||
Maximum of Months | 2027918.73 | 2703891.20 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 10346.39 | 36784.62 | 12-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 10124.80 | 36400.73 | 01-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 10018.70 | 34668.87 | 01-MAR-13:00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 8455.30 | 31368.87 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 7809.91 | 28236.53 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 7301.10 | 25320.07 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 6511.34 | 23923.01 | 31-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 7451.37 | 25781.83 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 7703.11 | 28649.12 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 8617.11 | 32224.08 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 9648.28 | 35051.77 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 9909.48 | 36590.25 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 8650.19 | ||||
Minimum of Months | 0.00 | 0.00 | 6511.34 | 23923.01 | ||
Maximum of Months | 0.00 | 0.00 | 10346.39 | 36784.62 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 343380.39 | 2315786.42 | 30-JAN-14:10 | 545.00 | 127258.17 | 01-JAN-04:40 |
February | 465487.21 | 4546917.31 | 07-FEB-15:40 | 127.93 | 57772.31 | 18-FEB-05:40 |
March | 653157.37 | 4237169.30 | 28-MAR-16:00 | 415.39 | 77132.98 | 16-MAR-02:40 |
April | 1082915.82 | 4820288.54 | 28-APR-15:00 | 315.72 | 79356.41 | 26-APR-03:00 |
May | 2273674.08 | 7917405.06 | 31-MAY-16:00 | 0.10 | 1740.61 | 07-MAY-03:38 |
June | 3814531.98 | 8066398.64 | 22-JUN-14:10 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 4692137.77 | 9196676.19 | 31-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 5191913.83 | 9115222.74 | 01-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 4136422.48 | 8498122.29 | 07-SEP-14:10 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 2446887.27 | 7652222.83 | 06-OCT-16:00 | 10.96 | 33883.51 | 21-OCT-03:10 |
November | 1205356.69 | 7141878.41 | 01-NOV-14:00 | 113.34 | 38933.96 | 26-NOV-02:15 |
December | 524936.57 | 4616864.34 | 05-DEC-15:30 | 411.02 | 101481.91 | 18-DEC-01:30 |
Annual Sum or Average | 2246901.80 | 162.49 | ||||
Minimum of Months | 343380.39 | 2315786.42 | 0.00 | 0.00 | ||
Maximum of Months | 5191913.83 | 9196676.19 | 545.00 | 127258.17 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.643652E+10 | 0.37 | 22310.02 | 30-JAN-05:12 | 1.73 |
February | 0.815681E+10 | 0.45 | 22781.39 | 08-FEB-05:12 | 1.75 |
March | 0.123809E+11 | 0.57 | 22781.39 | 02-MAR-05:12 | 1.75 |
April | 0.157929E+11 | 0.71 | 22781.39 | 08-APR-05:02 | 1.75 |
May | 0.224665E+11 | 0.85 | 22781.39 | 01-MAY-04:22 | 1.75 |
June | 0.252232E+11 | 0.94 | 22781.39 | 01-JUN-03:13 | 1.75 |
July | 0.271029E+11 | 0.96 | 22781.39 | 01-JUL-05:02 | 1.74 |
August | 0.315079E+11 | 1.06 | 22781.39 | 01-AUG-03:42 | 1.74 |
September | 0.238172E+11 | 0.90 | 22781.39 | 01-SEP-03:02 | 1.75 |
October | 0.223642E+11 | 0.85 | 22781.39 | 02-OCT-10:20 | 1.75 |
November | 0.156268E+11 | 0.68 | 22781.39 | 01-NOV-03:02 | 1.75 |
December | 0.100708E+11 | 0.50 | 22781.39 | 11-DEC-06:02 | 1.75 |
Annual Sum or Average | 0.220947E+12 | 0.74 | |||
Minimum of Months | 0.643652E+10 | 0.37 | 22310.02 | 1.73 | |
Maximum of Months | 0.315079E+11 | 1.06 | 22781.39 | 1.75 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.438628E+11 | 0.32 | 155497.42 | 23-JAN-06:01 | 1.43 |
February | 0.473541E+11 | 0.35 | 197011.44 | 06-FEB-06:02 | 1.66 |
March | 0.690155E+11 | 0.41 | 216214.15 | 02-MAR-06:03 | 1.76 |
April | 0.797732E+11 | 0.46 | 216214.15 | 12-APR-05:03 | 1.76 |
May | 0.114539E+12 | 0.59 | 216214.15 | 01-MAY-05:02 | 1.76 |
June | 0.123420E+12 | 0.65 | 216214.15 | 07-JUN-05:03 | 1.76 |
July | 0.131226E+12 | 0.66 | 216214.15 | 05-JUL-05:01 | 1.76 |
August | 0.149392E+12 | 0.71 | 216214.15 | 04-AUG-05:01 | 1.76 |
September | 0.115901E+12 | 0.61 | 216214.15 | 01-SEP-05:02 | 1.76 |
October | 0.102045E+12 | 0.54 | 216214.15 | 07-OCT-05:03 | 1.75 |
November | 0.787767E+11 | 0.45 | 216214.15 | 01-NOV-04:12 | 1.76 |
December | 0.516779E+11 | 0.35 | 168069.96 | 11-DEC-06:02 | 1.50 |
Annual Sum or Average | 0.110698E+13 | 0.51 | |||
Minimum of Months | 0.438628E+11 | 0.32 | 155497.42 | 1.43 | |
Maximum of Months | 0.149392E+12 | 0.71 | 216214.15 | 1.76 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.374854E+10 | 0.29 | 10572.36 | 23-JAN-06:01 | 1.04 |
February | 0.419760E+10 | 0.31 | 17917.76 | 06-FEB-06:02 | 1.45 |
March | 0.633651E+10 | 0.37 | 22080.82 | 28-MAR-03:02 | 1.66 |
April | 0.768342E+10 | 0.43 | 24169.25 | 24-APR-04:12 | 1.75 |
May | 0.116840E+11 | 0.57 | 24169.25 | 01-MAY-04:12 | 1.75 |
June | 0.128164E+11 | 0.62 | 24169.25 | 02-JUN-05:02 | 1.75 |
July | 0.138909E+11 | 0.64 | 24169.25 | 05-JUL-05:01 | 1.75 |
August | 0.156249E+11 | 0.69 | 24169.25 | 01-AUG-05:01 | 1.75 |
September | 0.118134E+11 | 0.59 | 24169.25 | 05-SEP-05:02 | 1.75 |
October | 0.992591E+10 | 0.50 | 24169.25 | 03-OCT-05:02 | 1.75 |
November | 0.703292E+10 | 0.40 | 22561.13 | 04-NOV-05:02 | 1.67 |
December | 0.444632E+10 | 0.31 | 10697.43 | 11-DEC-06:02 | 1.05 |
Annual Sum or Average | 0.109201E+12 | 0.48 | |||
Minimum of Months | 0.374854E+10 | 0.29 | 10572.36 | 1.04 | |
Maximum of Months | 0.156249E+11 | 0.69 | 24169.25 | 1.75 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.176974E+11 | 0.92 | 13017.38 | 01-JAN-00:30 | 1.77 |
February | 0.126357E+11 | 0.74 | 13017.38 | 01-FEB-05:12 | 1.77 |
March | 0.100482E+11 | 0.53 | 13017.38 | 03-MAR-06:03 | 1.76 |
April | 0.529128E+10 | 0.29 | 13017.38 | 01-APR-04:40 | 1.76 |
May | 0.741923E+09 | 0.04 | 13017.38 | 01-MAY-05:02 | 1.76 |
June | 0.624575E+09 | 0.03 | 13017.38 | 22-JUN-07:50 | 1.71 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 |
October | 0.564671E+09 | 0.03 | 13017.38 | 21-OCT-03:45 | 1.76 |
November | 0.789260E+10 | 0.42 | 13017.38 | 04-NOV-04:23 | 1.75 |
December | 0.135877E+11 | 0.72 | 13017.38 | 01-DEC-05:12 | 1.77 |
Annual Sum or Average | 0.690841E+11 | 0.31 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.176974E+11 | 0.92 | 13017.38 | 1.77 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.109147E+12 | 1.35 | 40750.89 | 01-JAN-00:05 | 1.35 |
February | 0.985846E+11 | 1.35 | 40750.89 | 01-FEB-00:20 | 1.35 |
March | 0.109147E+12 | 1.35 | 40750.89 | 01-MAR-00:10 | 1.35 |
April | 0.105626E+12 | 1.35 | 40750.89 | 01-APR-00:03 | 1.35 |
May | 0.109147E+12 | 1.34 | 40750.89 | 01-MAY-00:03 | 1.34 |
June | 0.105626E+12 | 1.34 | 40750.89 | 01-JUN-00:05 | 1.34 |
July | 0.109147E+12 | 1.34 | 40750.89 | 01-JUL-00:10 | 1.34 |
August | 0.109147E+12 | 1.34 | 40750.89 | 01-AUG-00:05 | 1.34 |
September | 0.105626E+12 | 1.34 | 40750.89 | 01-SEP-00:03 | 1.34 |
October | 0.109147E+12 | 1.34 | 40750.89 | 01-OCT-00:03 | 1.34 |
November | 0.105626E+12 | 1.35 | 40750.89 | 01-NOV-00:03 | 1.35 |
December | 0.109147E+12 | 1.35 | 40750.89 | 01-DEC-00:05 | 1.35 |
Annual Sum or Average | 0.128512E+13 | 1.35 | |||
Minimum of Months | 0.985846E+11 | 1.34 | 40750.89 | 1.34 | |
Maximum of Months | 0.109147E+12 | 1.35 | 40750.89 | 1.35 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.144070E+10 | 0.91 | 537.90 | 01-JAN-00:05 | 0.92 |
February | 0.130128E+10 | 0.91 | 537.90 | 01-FEB-00:10 | 0.91 |
March | 0.144070E+10 | 0.91 | 537.90 | 01-MAR-00:10 | 0.91 |
April | 0.139423E+10 | 0.91 | 537.90 | 01-APR-00:03 | 0.91 |
May | 0.144070E+10 | 0.91 | 537.90 | 01-MAY-00:03 | 0.91 |
June | 0.139423E+10 | 0.91 | 537.90 | 01-JUN-00:05 | 0.91 |
July | 0.144070E+10 | 0.91 | 537.90 | 01-JUL-00:03 | 0.91 |
August | 0.144070E+10 | 0.91 | 537.90 | 01-AUG-00:05 | 0.91 |
September | 0.139423E+10 | 0.91 | 537.90 | 01-SEP-00:03 | 0.91 |
October | 0.144070E+10 | 0.91 | 537.90 | 01-OCT-00:03 | 0.91 |
November | 0.139423E+10 | 0.91 | 537.90 | 01-NOV-00:03 | 0.91 |
December | 0.144070E+10 | 0.91 | 537.90 | 01-DEC-00:05 | 0.91 |
Annual Sum or Average | 0.169631E+11 | 0.91 | |||
Minimum of Months | 0.130128E+10 | 0.91 | 537.90 | 0.91 | |
Maximum of Months | 0.144070E+10 | 0.91 | 537.90 | 0.92 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.137395E+11 | 0.91 | 5129.74 | 01-JAN-00:05 | 0.91 |
February | 0.124099E+11 | 0.91 | 5129.74 | 01-FEB-00:10 | 0.91 |
March | 0.137395E+11 | 0.91 | 5129.74 | 01-MAR-00:10 | 0.91 |
April | 0.132963E+11 | 0.91 | 5129.74 | 01-APR-00:03 | 0.91 |
May | 0.137395E+11 | 0.91 | 5129.74 | 01-MAY-00:03 | 0.91 |
June | 0.132963E+11 | 0.91 | 5129.74 | 01-JUN-00:05 | 0.91 |
July | 0.137395E+11 | 0.91 | 5129.74 | 01-JUL-00:03 | 0.91 |
August | 0.137395E+11 | 0.91 | 5129.74 | 01-AUG-00:05 | 0.91 |
September | 0.132963E+11 | 0.91 | 5129.74 | 01-SEP-00:03 | 0.91 |
October | 0.137395E+11 | 0.91 | 5129.74 | 01-OCT-00:03 | 0.91 |
November | 0.132963E+11 | 0.91 | 5129.74 | 01-NOV-00:03 | 0.91 |
December | 0.137395E+11 | 0.91 | 5129.74 | 01-DEC-00:05 | 0.91 |
Annual Sum or Average | 0.161771E+12 | 0.91 | |||
Minimum of Months | 0.124099E+11 | 0.91 | 5129.74 | 0.91 | |
Maximum of Months | 0.137395E+11 | 0.91 | 5129.74 | 0.91 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.138246E+10 | 0.91 | 516.15 | 01-JAN-00:05 | 0.91 |
February | 0.124867E+10 | 0.91 | 516.15 | 01-FEB-00:10 | 0.91 |
March | 0.138246E+10 | 0.91 | 516.15 | 01-MAR-00:10 | 0.91 |
April | 0.133787E+10 | 0.91 | 516.15 | 01-APR-00:03 | 0.91 |
May | 0.138246E+10 | 0.91 | 516.15 | 01-MAY-00:03 | 0.91 |
June | 0.133787E+10 | 0.91 | 516.15 | 01-JUN-00:05 | 0.91 |
July | 0.138246E+10 | 0.91 | 516.15 | 01-JUL-00:03 | 0.91 |
August | 0.138246E+10 | 0.91 | 516.15 | 01-AUG-00:05 | 0.91 |
September | 0.133787E+10 | 0.91 | 516.15 | 01-SEP-00:03 | 0.91 |
October | 0.138246E+10 | 0.91 | 516.15 | 01-OCT-00:03 | 0.91 |
November | 0.133787E+10 | 0.91 | 516.15 | 01-NOV-00:03 | 0.91 |
December | 0.138246E+10 | 0.91 | 516.15 | 01-DEC-00:05 | 0.91 |
Annual Sum or Average | 0.162774E+11 | 0.91 | |||
Minimum of Months | 0.124867E+10 | 0.91 | 516.15 | 0.91 | |
Maximum of Months | 0.138246E+10 | 0.91 | 516.15 | 0.91 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.288325E+09 | 0.259493E+09 | 2563.85 | 30-JAN-06:03 | 2307.47 | 2307.47 | 6.71 | 44.68 |
February | 0.373846E+09 | 0.336462E+09 | 9931.84 | 06-FEB-06:02 | 8938.65 | 8938.65 | 9.05 | 78.31 |
March | 0.734938E+09 | 0.661445E+09 | 13590.44 | 29-MAR-05:02 | 12231.40 | 12231.40 | 9.74 | 88.68 |
April | 0.102694E+10 | 0.924245E+09 | 13590.96 | 12-APR-05:03 | 12231.87 | 12231.87 | 10.04 | 88.68 |
May | 0.164107E+10 | 0.147696E+10 | 15238.52 | 01-MAY-05:02 | 13714.67 | 13714.67 | 9.72 | 92.78 |
June | 0.210135E+10 | 0.189121E+10 | 13591.16 | 24-JUN-05:02 | 12232.05 | 12232.05 | 10.09 | 88.68 |
July | 0.269598E+10 | 0.242638E+10 | 13591.38 | 01-JUL-05:02 | 12232.24 | 12232.24 | 10.14 | 88.68 |
August | 0.313436E+10 | 0.282093E+10 | 13597.51 | 14-AUG-05:03 | 12237.75 | 12237.75 | 11.62 | 88.68 |
September | 0.215446E+10 | 0.193902E+10 | 13591.13 | 09-SEP-05:02 | 12232.01 | 12232.01 | 10.08 | 88.68 |
October | 0.155767E+10 | 0.140191E+10 | 13590.75 | 06-OCT-05:02 | 12231.67 | 12231.67 | 9.96 | 88.68 |
November | 0.102170E+10 | 0.919528E+09 | 13835.14 | 06-NOV-05:12 | 12451.63 | 12451.63 | 10.20 | 89.30 |
December | 0.447056E+09 | 0.402350E+09 | 9188.13 | 11-DEC-06:02 | 8269.32 | 8269.32 | 8.90 | 75.90 |
Annual Sum or Average | 0.171777E+11 | 0.154599E+11 | ||||||
Minimum of Months | 0.288325E+09 | 0.259493E+09 | 2563.85 | 2307.47 | 2307.47 | 6.71 | 44.68 | |
Maximum of Months | 0.313436E+10 | 0.282093E+10 | 15238.52 | 13714.67 | 13714.67 | 11.62 | 92.78 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.850383E+10 | 0.765345E+10 | 5244.13 | 01-JAN-00:15 | 4719.72 | 4719.72 | 6.94 | 46.39 |
February | 0.804712E+10 | 0.724241E+10 | 5244.13 | 01-FEB-05:12 | 4719.72 | 4719.72 | 9.61 | 46.39 |
March | 0.105313E+11 | 0.947814E+10 | 5244.13 | 01-MAR-03:42 | 4719.72 | 4719.72 | 8.00 | 46.39 |
April | 0.120122E+11 | 0.108110E+11 | 5244.13 | 01-APR-00:03 | 4719.72 | 4719.72 | 6.99 | 46.39 |
May | 0.129985E+11 | 0.116987E+11 | 5244.13 | 01-MAY-00:03 | 4719.72 | 4719.72 | 10.86 | 46.39 |
June | 0.130862E+11 | 0.117776E+11 | 5244.13 | 01-JUN-00:05 | 4719.72 | 4719.72 | 10.99 | 46.39 |
July | 0.133426E+11 | 0.120083E+11 | 5244.13 | 01-JUL-00:03 | 4719.72 | 4719.72 | 12.86 | 46.39 |
August | 0.133953E+11 | 0.120557E+11 | 5244.13 | 01-AUG-00:05 | 4719.72 | 4719.72 | 11.56 | 46.39 |
September | 0.128791E+11 | 0.115912E+11 | 5244.13 | 01-SEP-00:03 | 4719.72 | 4719.72 | 9.64 | 46.39 |
October | 0.127840E+11 | 0.115056E+11 | 5244.13 | 01-OCT-00:03 | 4719.72 | 4719.72 | 7.25 | 46.39 |
November | 0.110842E+11 | 0.997578E+10 | 5244.13 | 01-NOV-00:13 | 4719.72 | 4719.72 | 7.01 | 46.39 |
December | 0.100114E+11 | 0.901027E+10 | 5244.13 | 01-DEC-01:03 | 4719.72 | 4719.72 | 6.89 | 46.39 |
Annual Sum or Average | 0.138676E+12 | 0.124808E+12 | ||||||
Minimum of Months | 0.804712E+10 | 0.724241E+10 | 5244.13 | 4719.72 | 4719.72 | 6.89 | 46.39 | |
Maximum of Months | 0.133953E+11 | 0.120557E+11 | 5244.13 | 4719.72 | 4719.72 | 12.86 | 46.39 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 6.84 | 0.00 |
February | 91247880.28 | 82123092.25 | 5244.13 | 07-FEB-13:20 | 4719.72 | 4719.72 | 14.99 | 23.19 |
March | 0.602236E+09 | 0.542012E+09 | 5244.13 | 01-MAR-13:40 | 4719.72 | 4719.72 | 15.63 | 23.19 |
April | 0.143007E+10 | 0.128707E+10 | 5244.13 | 03-APR-09:30 | 4719.72 | 4719.72 | 14.89 | 23.19 |
May | 0.373692E+10 | 0.336322E+10 | 5244.13 | 01-MAY-07:30 | 4719.72 | 4719.72 | 14.84 | 23.19 |
June | 0.587231E+10 | 0.528508E+10 | 5244.13 | 01-JUN-07:30 | 4719.72 | 4719.72 | 15.09 | 23.19 |
July | 0.720640E+10 | 0.648576E+10 | 5244.13 | 01-JUL-05:02 | 4719.72 | 4719.72 | 15.24 | 23.19 |
August | 0.798231E+10 | 0.718408E+10 | 5244.13 | 01-AUG-02:23 | 4719.72 | 4719.72 | 11.80 | 46.39 |
September | 0.589205E+10 | 0.530284E+10 | 5244.13 | 01-SEP-05:03 | 4719.72 | 4719.72 | 15.72 | 23.19 |
October | 0.382968E+10 | 0.344672E+10 | 5244.13 | 02-OCT-05:07 | 4719.72 | 4719.72 | 15.26 | 23.19 |
November | 0.209965E+10 | 0.188968E+10 | 5244.13 | 01-NOV-07:50 | 4719.72 | 4719.72 | 14.87 | 23.19 |
December | 0.226546E+09 | 0.203892E+09 | 5244.13 | 04-DEC-11:20 | 4719.72 | 4719.72 | 14.88 | 23.19 |
Annual Sum or Average | 0.389694E+11 | 0.350725E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.84 | 0.00 | |
Maximum of Months | 0.798231E+10 | 0.718408E+10 | 5244.13 | 4719.72 | 4719.72 | 15.72 | 46.39 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.106131E+11 | 0.955183E+10 | 3962.49 | 01-JAN-00:05 | 3566.24 | 3566.24 | 21.69 | 16.55 |
February | 0.958606E+10 | 0.862746E+10 | 3962.49 | 01-FEB-00:10 | 3566.24 | 3566.24 | 24.54 | 16.55 |
March | 0.106131E+11 | 0.955183E+10 | 3962.49 | 01-MAR-00:10 | 3566.24 | 3566.24 | 33.96 | 16.55 |
April | 0.102708E+11 | 0.924370E+10 | 3962.49 | 01-APR-00:03 | 3566.24 | 3566.24 | 37.42 | 16.55 |
May | 0.106131E+11 | 0.955183E+10 | 3962.49 | 01-MAY-00:03 | 3566.24 | 3566.24 | 32.89 | 16.55 |
June | 0.102708E+11 | 0.924370E+10 | 3962.49 | 01-JUN-00:05 | 3566.24 | 3566.24 | 41.89 | 16.55 |
July | 0.106131E+11 | 0.955183E+10 | 3962.49 | 01-JUL-00:03 | 3566.24 | 3566.24 | 44.75 | 16.55 |
August | 0.106131E+11 | 0.955183E+10 | 3962.49 | 01-AUG-00:05 | 3566.24 | 3566.24 | 50.24 | 16.55 |
September | 0.102708E+11 | 0.924370E+10 | 3962.49 | 01-SEP-00:03 | 3566.24 | 3566.24 | 38.23 | 16.55 |
October | 0.106131E+11 | 0.955183E+10 | 3962.49 | 01-OCT-00:03 | 3566.24 | 3566.24 | 38.27 | 16.55 |
November | 0.102708E+11 | 0.924370E+10 | 3962.49 | 01-NOV-00:03 | 3566.24 | 3566.24 | 39.65 | 16.55 |
December | 0.106131E+11 | 0.955183E+10 | 3962.49 | 01-DEC-00:05 | 3566.24 | 3566.24 | 35.12 | 16.55 |
Annual Sum or Average | 0.124961E+12 | 0.112465E+12 | ||||||
Minimum of Months | 0.958606E+10 | 0.862746E+10 | 3962.49 | 3566.24 | 3566.24 | 21.69 | 16.55 | |
Maximum of Months | 0.106131E+11 | 0.955183E+10 | 3962.49 | 3566.24 | 3566.24 | 50.24 | 16.55 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 57.81 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:02 | 16.86 | 16.86 | 57.92 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:02 | 16.86 | 16.86 | 58.02 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:02 | 16.86 | 16.86 | 58.20 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:02 | 16.86 | 16.86 | 58.56 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 58.50 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:02 | 16.86 | 16.86 | 58.66 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:01 | 16.86 | 16.86 | 58.70 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:02 | 16.86 | 16.86 | 58.57 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:03 | 16.86 | 16.86 | 58.28 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:02 | 16.86 | 16.86 | 58.16 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:03 | 16.86 | 16.86 | 57.95 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 57.81 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 58.70 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.327638E+11 | 0.294874E+11 | 20286.14 | 30-JAN-14:10 | 18257.53 | 18257.53 | 27.87 | 81.81 |
February | 0.311608E+11 | 0.280447E+11 | 40568.10 | 07-FEB-15:40 | 36511.29 | 36511.29 | 27.75 | 163.63 |
March | 0.418544E+11 | 0.376690E+11 | 40552.68 | 28-MAR-16:00 | 36497.42 | 36497.42 | 27.30 | 163.63 |
April | 0.497819E+11 | 0.448038E+11 | 40581.71 | 28-APR-15:00 | 36523.54 | 36523.54 | 28.15 | 163.63 |
May | 0.622393E+11 | 0.560154E+11 | 40625.92 | 08-MAY-14:00 | 36563.33 | 36563.33 | 29.68 | 163.63 |
June | 0.709013E+11 | 0.638112E+11 | 40625.92 | 01-JUN-20:10 | 36563.33 | 36563.33 | 30.06 | 163.63 |
July | 0.771620E+11 | 0.694458E+11 | 40625.92 | 01-JUL-05:02 | 36563.33 | 36563.33 | 31.34 | 163.63 |
August | 0.809283E+11 | 0.728355E+11 | 40625.92 | 01-AUG-02:23 | 36563.33 | 36563.33 | 32.27 | 163.63 |
September | 0.707753E+11 | 0.636978E+11 | 40625.92 | 01-SEP-07:30 | 36563.33 | 36563.33 | 29.59 | 163.63 |
October | 0.622030E+11 | 0.559827E+11 | 40625.92 | 03-OCT-13:40 | 36563.33 | 36563.33 | 29.63 | 163.63 |
November | 0.478691E+11 | 0.430822E+11 | 40625.92 | 01-NOV-10:00 | 36563.33 | 36563.33 | 29.48 | 163.63 |
December | 0.390228E+11 | 0.351205E+11 | 40571.58 | 05-DEC-15:30 | 36514.42 | 36514.42 | 27.85 | 163.63 |
Annual Sum or Average | 0.666662E+12 | 0.599996E+12 | ||||||
Minimum of Months | 0.311608E+11 | 0.280447E+11 | 20286.14 | 18257.53 | 18257.53 | 27.30 | 81.81 | |
Maximum of Months | 0.809283E+11 | 0.728355E+11 | 40625.92 | 36563.33 | 36563.33 | 32.27 | 163.63 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 297733.12 | 1245363.53 | 30-JAN-14:10 | 13.11 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 379498.47 | 1792124.18 | 07-FEB-15:20 | 11.31 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 506979.70 | 2010359.01 | 27-MAR-10:10 | 11.87 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 684844.12 | 2199818.43 | 26-APR-12:20 | 12.36 | 6.70 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1005228.92 | 3196613.97 | 24-MAY-05:02 | 14.93 | 6.70 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1290588.54 | 2918636.11 | 04-JUN-16:14 | 14.22 | 6.70 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 1469439.39 | 4284679.40 | 16-JUL-17:02 | 17.74 | 9.31 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1586262.63 | 4087420.18 | 21-AUG-05:03 | 17.23 | 8.80 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 1303392.52 | 3862804.64 | 09-SEP-17:08 | 16.65 | 12.44 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 976093.78 | 3505883.58 | 07-OCT-17:10 | 15.73 | 11.52 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 693834.31 | 2132200.93 | 01-NOV-14:00 | 12.19 | 6.70 | 0.00 | 0.00 | 01-NOV-00:03 |
December | 406202.81 | 1870337.46 | 06-DEC-13:50 | 11.51 | 6.70 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 886279.16 | 0.00 | ||||||
Minimum of Months | 297733.12 | 1245363.53 | 11.31 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 1586262.63 | 4284679.40 | 17.74 | 12.44 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 295203.81 | 2076490.72 | 30-JAN-06:03 | 17.81 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 377045.17 | 3617336.46 | 06-FEB-06:02 | 17.74 | 11.18 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 503839.17 | 4229289.62 | 29-MAR-05:02 | 18.10 | 12.12 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 680427.36 | 4211560.81 | 12-APR-04:12 | 18.16 | 12.09 | 0.00 | 0.00 | 01-APR-00:03 |
May | 999220.00 | 4590877.35 | 31-MAY-05:02 | 19.08 | 12.58 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1284330.91 | 4739036.86 | 24-JUN-05:02 | 19.48 | 12.77 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 1461956.68 | 4813277.96 | 01-JUL-05:02 | 19.68 | 12.87 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1580290.47 | 4996471.39 | 30-AUG-05:01 | 20.18 | 13.10 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 1298304.89 | 4726743.65 | 09-SEP-05:02 | 19.45 | 12.76 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 970390.50 | 4609704.35 | 10-OCT-05:02 | 19.13 | 12.61 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 688327.72 | 4236644.38 | 04-NOV-05:02 | 18.12 | 12.13 | 0.00 | 0.00 | 01-NOV-00:03 |
December | 402855.44 | 3524588.98 | 11-DEC-06:02 | 17.80 | 11.00 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 881439.53 | 0.00 | ||||||
Minimum of Months | 295203.81 | 2076490.72 | 17.74 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 1580290.47 | 4996471.39 | 20.18 | 13.10 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 363995.84 | 869270.49 | 23-JAN-14:00 | 33.28 | 29.38 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 631599.71 | 1370948.98 | 06-FEB-15:00 | 41.73 | 34.93 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 973337.28 | 1947446.34 | 27-MAR-11:10 | 51.26 | 41.46 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1402953.40 | 2425936.41 | 28-APR-12:00 | 59.06 | 46.60 | 0.00 | 0.00 | 01-APR-00:03 |
May | 1091631.56 | 1759156.69 | 31-MAY-19:00 | 48.17 | 43.71 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 1423141.04 | 2075276.73 | 12-JUN-12:00 | 53.36 | 45.77 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 1791435.17 | 2505547.11 | 21-JUL-12:00 | 60.35 | 49.87 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 2027918.73 | 2703891.20 | 16-AUG-12:00 | 63.54 | 50.75 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 1179578.71 | 1717570.10 | 26-SEP-13:00 | 47.48 | 42.87 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 1197863.17 | 1730809.03 | 04-OCT-12:00 | 47.70 | 40.58 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 1139087.85 | 1676902.37 | 05-NOV-12:00 | 46.81 | 37.40 | 0.00 | 0.00 | 01-NOV-00:03 |
December | 1048147.37 | 1625738.53 | 10-DEC-12:03 | 45.96 | 34.21 | 0.00 | 0.00 | 01-DEC-00:05 |
Annual Sum or Average | 1192744.73 | 0.00 | ||||||
Minimum of Months | 363995.84 | 869270.49 | 33.28 | 29.38 | 0.00 | 0.00 | ||
Maximum of Months | 2027918.73 | 2703891.20 | 63.54 | 50.75 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 58.66 | 58.66 | 10346.39 | 36784.62 | 12-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 58.31 | 58.31 | 10124.80 | 36400.73 | 01-FEB-12:30 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 58.40 | 58.40 | 10018.70 | 34668.87 | 01-MAR-13:00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 58.55 | 58.55 | 8455.30 | 31368.87 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 58.98 | 58.98 | 7809.91 | 28236.53 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:05 | 58.84 | 58.84 | 7301.10 | 25320.07 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 58.92 | 58.92 | 6511.34 | 23923.01 | 31-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 58.92 | 58.92 | 7451.37 | 25781.83 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 58.83 | 58.83 | 7703.11 | 28649.12 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 58.68 | 58.68 | 8617.11 | 32224.08 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:03 | 58.52 | 58.52 | 9648.28 | 35051.77 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:05 | 58.38 | 58.38 | 9909.48 | 36590.25 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 8650.19 | ||||||
Minimum of Months | 0.00 | 0.00 | 58.31 | 58.31 | 6511.34 | 23923.01 | ||
Maximum of Months | 0.00 | 0.00 | 58.98 | 58.98 | 10346.39 | 36784.62 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 343380.39 | 2315786.42 | 30-JAN-14:10 | 27.87 | 23.73 | 545.00 | 127258.17 | 01-JAN-04:40 |
February | 465487.21 | 4546917.31 | 07-FEB-15:40 | 27.75 | 24.74 | 127.93 | 57772.31 | 18-FEB-05:40 |
March | 653157.37 | 4237169.30 | 28-MAR-16:00 | 27.30 | 24.36 | 415.39 | 77132.98 | 16-MAR-02:40 |
April | 1082915.82 | 4820288.54 | 28-APR-15:00 | 28.15 | 25.04 | 315.72 | 79356.41 | 26-APR-03:00 |
May | 2273674.08 | 7917405.06 | 31-MAY-16:00 | 32.68 | 28.62 | 0.10 | 1740.61 | 07-MAY-03:38 |
June | 3814531.98 | 8066398.64 | 22-JUN-14:10 | 32.89 | 28.69 | 0.00 | 0.00 | 01-JUN-00:05 |
July | 4692137.77 | 9196676.19 | 31-JUL-05:03 | 34.55 | 29.22 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 5191913.83 | 9115222.74 | 01-AUG-05:03 | 34.43 | 29.18 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 4136422.48 | 8498122.29 | 07-SEP-14:10 | 33.52 | 28.90 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 2446887.27 | 7652222.83 | 06-OCT-16:00 | 32.29 | 28.49 | 10.96 | 33883.51 | 21-OCT-03:10 |
November | 1205356.69 | 7141878.41 | 01-NOV-14:00 | 31.54 | 27.98 | 113.34 | 38933.96 | 26-NOV-02:15 |
December | 524936.57 | 4616864.34 | 05-DEC-15:30 | 27.85 | 24.87 | 411.02 | 101481.91 | 18-DEC-01:30 |
Annual Sum or Average | 2246901.80 | 162.49 | ||||||
Minimum of Months | 343380.39 | 2315786.42 | 27.30 | 23.73 | 0.00 | 0.00 | ||
Maximum of Months | 5191913.83 | 9196676.19 | 34.55 | 29.22 | 545.00 | 127258.17 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.790113E+11 | 0.643652E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.976002E+11 | 0.815681E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.146046E+12 | 0.123809E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.193752E+12 | 0.157929E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.275630E+12 | 0.224665E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.338324E+12 | 0.252232E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.397963E+12 | 0.271029E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.439625E+12 | 0.315079E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.348590E+12 | 0.238172E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.293635E+12 | 0.223642E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.193738E+12 | 0.156268E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.123668E+12 | 0.100708E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.292758E+13 | 0.220947E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.790113E+11 | 0.643652E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.439625E+12 | 0.315079E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.582513E+12 | 0.438628E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.674535E+12 | 0.473541E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.992814E+12 | 0.690155E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.129662E+13 | 0.797732E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.206309E+13 | 0.114539E+12 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.261862E+13 | 0.123420E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.312218E+13 | 0.131226E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.337914E+13 | 0.149392E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.266465E+13 | 0.115901E+12 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.199781E+13 | 0.102045E+12 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.129797E+13 | 0.787767E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.779450E+12 | 0.516779E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.214694E+14 | 0.110698E+13 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.582513E+12 | 0.438628E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.337914E+13 | 0.149392E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.538507E+11 | 0.385692E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.658562E+11 | 0.420492E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.100311E+12 | 0.633651E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.135068E+12 | 0.768342E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.219630E+12 | 0.116840E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.278212E+12 | 0.128164E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.331628E+12 | 0.138909E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.357066E+12 | 0.156249E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.279660E+12 | 0.118134E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.206180E+12 | 0.992591E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.128876E+12 | 0.703292E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.741810E+11 | 0.445284E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.223052E+13 | 0.109323E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.538507E+11 | 0.385692E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.357066E+12 | 0.156249E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.728139E+11 | 0.176974E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.581197E+11 | 0.126357E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.606604E+11 | 0.100482E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.421885E+11 | 0.529128E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.729560E+10 | 0.741923E+09 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.734394E+10 | 0.624575E+09 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.591246E+10 | 0.564671E+09 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.641948E+11 | 0.789260E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.754585E+11 | 0.135877E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.393988E+12 | 0.690841E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.754585E+11 | 0.176974E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.454691E+12 | 0.210899E+12 | 0.00 | 1.04 |
February | 0.00 | 0.00 | 0.701182E+12 | 0.255824E+12 | 0.00 | 1.08 |
March | 0.00 | 0.00 | 0.110580E+13 | 0.365930E+12 | 0.00 | 0.85 |
April | 0.00 | 0.00 | 0.141294E+13 | 0.453630E+12 | 0.00 | 0.11 |
May | 0.00 | 0.00 | 0.525324E+12 | 0.255298E+12 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.858799E+12 | 0.347529E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.125623E+13 | 0.473133E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.160306E+13 | 0.571677E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.538048E+12 | 0.257168E+12 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.860422E+12 | 0.336476E+12 | 0.00 | 0.03 |
November | 0.00 | 0.00 | 0.110435E+13 | 0.373189E+12 | 0.00 | 0.13 |
December | 0.00 | 0.00 | 0.141022E+13 | 0.422058E+12 | 0.00 | 1.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.118311E+14 | 0.432281E+13 | 0.00 | 5.17 |
Minimum of Months | 0.00 | 0.00 | 0.454691E+12 | 0.210899E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.160306E+13 | 0.571677E+12 | 0.00 | 1.92 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.730844E+10 | 0.301042E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.129351E+11 | 0.408731E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.212460E+11 | 0.621715E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.279324E+11 | 0.807639E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.102707E+11 | 0.420766E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.175614E+11 | 0.616240E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.261840E+11 | 0.873856E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.321986E+11 | 0.103323E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.109737E+11 | 0.435995E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.171666E+11 | 0.582701E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.216049E+11 | 0.647655E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.272409E+11 | 0.724172E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.232623E+12 | 0.747374E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.730844E+10 | 0.301042E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.321986E+11 | 0.103323E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.602230E+11 | 0.268062E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.117004E+12 | 0.377413E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.199652E+12 | 0.587145E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.265140E+12 | 0.767515E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.937600E+11 | 0.390549E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.163861E+12 | 0.578319E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.244212E+12 | 0.819041E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.305475E+12 | 0.983154E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.994931E+11 | 0.402176E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.159298E+12 | 0.544965E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.203115E+12 | 0.611371E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.254445E+12 | 0.680786E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.216568E+13 | 0.701050E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.602230E+11 | 0.268062E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.305475E+12 | 0.983154E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.539321E+10 | 0.256468E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.113564E+11 | 0.371822E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.197938E+11 | 0.585233E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.265462E+11 | 0.769838E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.954526E+10 | 0.396106E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.165728E+11 | 0.584338E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.247039E+11 | 0.827781E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.307492E+11 | 0.989418E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.101255E+11 | 0.407907E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.160092E+11 | 0.548174E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.202126E+11 | 0.610704E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.250454E+11 | 0.674843E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.216053E+12 | 0.702263E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.539321E+10 | 0.256468E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.307492E+11 | 0.989418E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.643652E+10 | 0.790113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.815681E+10 | 0.976002E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123809E+11 | 0.146046E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.157929E+11 | 0.193752E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.224665E+11 | 0.275630E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.252232E+11 | 0.338324E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271029E+11 | 0.397963E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.315079E+11 | 0.439625E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.238172E+11 | 0.348590E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.223642E+11 | 0.293635E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.156268E+11 | 0.193738E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100708E+11 | 0.123668E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.220947E+12 | 0.292758E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.643652E+10 | 0.790113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.315079E+11 | 0.439625E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.438628E+11 | 0.582513E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.473541E+11 | 0.674535E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.690155E+11 | 0.992814E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.797732E+11 | 0.129662E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114539E+12 | 0.206309E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.123420E+12 | 0.261862E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131226E+12 | 0.312218E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149392E+12 | 0.337914E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115901E+12 | 0.266465E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.102045E+12 | 0.199781E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.787767E+11 | 0.129797E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.516779E+11 | 0.779450E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110698E+13 | 0.214694E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.438628E+11 | 0.582513E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149392E+12 | 0.337914E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.374854E+10 | 0.538507E+11 | 0.108380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.419760E+10 | 0.658562E+11 | 7318508.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.633651E+10 | 0.100311E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.768342E+10 | 0.135068E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.116840E+11 | 0.219630E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128164E+11 | 0.278212E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138909E+11 | 0.331628E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.156249E+11 | 0.357066E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118134E+11 | 0.279660E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.992591E+10 | 0.206180E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.703292E+10 | 0.128876E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.444632E+10 | 0.741810E+11 | 6518239.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109201E+12 | 0.223052E+13 | 0.122217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.374854E+10 | 0.538507E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.156249E+11 | 0.357066E+12 | 0.108380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.176974E+11 | 0.728139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126357E+11 | 0.581197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.100482E+11 | 0.606604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.529128E+10 | 0.421885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.741923E+09 | 0.729560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.624575E+09 | 0.734394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.564671E+09 | 0.591246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.789260E+10 | 0.641948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135877E+11 | 0.754585E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.690841E+11 | 0.393988E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.176974E+11 | 0.754585E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.109147E+12 | 0.355737E+12 | 0.00 | 0.00 | 0.00 | 0.278444E+10 | 0.00 | 0.00 |
February | 0.985846E+11 | 0.546859E+12 | 0.00 | 0.00 | 0.00 | 0.290345E+10 | 0.00 | 0.00 |
March | 0.109147E+12 | 0.851298E+12 | 0.00 | 0.00 | 0.00 | 0.226828E+10 | 0.00 | 0.00 |
April | 0.105626E+12 | 0.106523E+13 | 0.00 | 0.00 | 0.00 | 0.292181E+09 | 0.00 | 0.00 |
May | 0.109147E+12 | 0.379179E+12 | 0.00 | 0.00 | 0.00 | 5729556.01 | 0.00 | 0.00 |
June | 0.105626E+12 | 0.616896E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.109147E+12 | 0.892248E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109147E+12 | 0.114053E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.105626E+12 | 0.386507E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.109147E+12 | 0.633170E+12 | 0.00 | 0.00 | 0.00 | 75527855.53 | 0.00 | 0.00 |
November | 0.105626E+12 | 0.837144E+12 | 0.00 | 0.00 | 0.00 | 0.359884E+09 | 0.00 | 0.00 |
December | 0.109147E+12 | 0.110248E+13 | 0.00 | 0.00 | 0.00 | 0.514172E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.128512E+13 | 0.880728E+13 | 0.00 | 0.00 | 0.00 | 0.138312E+11 | 0.00 | 0.00 |
Minimum of Months | 0.985846E+11 | 0.355737E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.109147E+12 | 0.114053E+13 | 0.00 | 0.00 | 0.00 | 0.514172E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.144070E+10 | 0.573873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130128E+10 | 0.101491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144070E+10 | 0.164695E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139423E+10 | 0.212503E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144070E+10 | 0.750375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139423E+10 | 0.127932E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144070E+10 | 0.188862E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144070E+10 | 0.233069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139423E+10 | 0.800796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144070E+10 | 0.127803E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139423E+10 | 0.165226E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144070E+10 | 0.214399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169631E+11 | 0.174848E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130128E+10 | 0.573873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144070E+10 | 0.233069E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.137395E+11 | 0.471563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124099E+11 | 0.916726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137395E+11 | 0.154677E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132963E+11 | 0.201685E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137395E+11 | 0.684446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132963E+11 | 0.119325E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137395E+11 | 0.176047E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137395E+11 | 0.220899E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132963E+11 | 0.725718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137395E+11 | 0.118541E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132963E+11 | 0.155274E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137395E+11 | 0.200106E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161771E+12 | 0.162640E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124099E+11 | 0.471563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137395E+11 | 0.220899E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.138246E+10 | 0.421098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124867E+10 | 0.888685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138246E+10 | 0.153239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133787E+10 | 0.201857E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138246E+10 | 0.696666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133787E+10 | 0.120673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138246E+10 | 0.178085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138246E+10 | 0.222375E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133787E+10 | 0.738433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138246E+10 | 0.119099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133787E+10 | 0.154434E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138246E+10 | 0.196794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162774E+11 | 0.162104E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124867E+10 | 0.421098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138246E+10 | 0.222375E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.643652E+10 | 0.00 | 0.790113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.815681E+10 | 0.00 | 0.976002E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123809E+11 | 0.00 | 0.146046E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.157929E+11 | 0.00 | 0.193752E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.224665E+11 | 0.00 | 0.275630E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.252232E+11 | 0.00 | 0.338324E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.271029E+11 | 0.00 | 0.397963E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.315079E+11 | 0.00 | 0.439625E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.238172E+11 | 0.00 | 0.348590E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.223642E+11 | 0.00 | 0.293635E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.156268E+11 | 0.00 | 0.193738E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.100708E+11 | 0.00 | 0.123668E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.220947E+12 | 0.00 | 0.292758E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.643652E+10 | 0.00 | 0.790113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.315079E+11 | 0.00 | 0.439625E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.438628E+11 | 0.00 | 0.582513E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.473541E+11 | 0.00 | 0.674535E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.690155E+11 | 0.00 | 0.992814E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.797732E+11 | 0.00 | 0.129662E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114539E+12 | 0.00 | 0.206309E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.123420E+12 | 0.00 | 0.261862E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131226E+12 | 0.00 | 0.312218E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149392E+12 | 0.00 | 0.337914E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115901E+12 | 0.00 | 0.266465E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.102045E+12 | 0.00 | 0.199781E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.787767E+11 | 0.00 | 0.129797E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.516779E+11 | 0.00 | 0.779450E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110698E+13 | 0.00 | 0.214694E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.438628E+11 | 0.00 | 0.582513E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149392E+12 | 0.00 | 0.337914E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.374854E+10 | 0.00 | 0.538507E+11 | 0.00 | 0.00 | 0.108380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.419760E+10 | 0.00 | 0.658562E+11 | 0.00 | 0.00 | 7318508.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.633651E+10 | 0.00 | 0.100311E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.768342E+10 | 0.00 | 0.135068E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.116840E+11 | 0.00 | 0.219630E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128164E+11 | 0.00 | 0.278212E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138909E+11 | 0.00 | 0.331628E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.156249E+11 | 0.00 | 0.357066E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.118134E+11 | 0.00 | 0.279660E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.992591E+10 | 0.00 | 0.206180E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.703292E+10 | 0.00 | 0.128876E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.444632E+10 | 0.00 | 0.741810E+11 | 0.00 | 0.00 | 6518239.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109201E+12 | 0.00 | 0.223052E+13 | 0.00 | 0.00 | 0.122217E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.374854E+10 | 0.00 | 0.538507E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.156249E+11 | 0.00 | 0.357066E+12 | 0.00 | 0.00 | 0.108380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.176974E+11 | 0.00 | 0.728139E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126357E+11 | 0.00 | 0.581197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.100482E+11 | 0.00 | 0.606604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.529128E+10 | 0.00 | 0.421885E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.741923E+09 | 0.00 | 0.729560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.624575E+09 | 0.00 | 0.734394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.564671E+09 | 0.00 | 0.591246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.789260E+10 | 0.00 | 0.641948E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135877E+11 | 0.00 | 0.754585E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.690841E+11 | 0.00 | 0.393988E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.176974E+11 | 0.00 | 0.754585E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.109147E+12 | 0.00 | 0.454691E+12 | 0.00 | 0.989545E+11 | 0.00 | 0.00 | 0.00 | 0.279697E+10 | 0.00 | 0.00 | 0.00 |
February | 0.985846E+11 | 0.00 | 0.701182E+12 | 0.00 | 0.154323E+12 | 0.00 | 0.00 | 0.00 | 0.291652E+10 | 0.00 | 0.00 | 0.00 |
March | 0.109147E+12 | 0.00 | 0.110580E+13 | 0.00 | 0.254505E+12 | 0.00 | 0.00 | 0.00 | 0.227849E+10 | 0.00 | 0.00 | 0.00 |
April | 0.105626E+12 | 0.00 | 0.141294E+13 | 0.00 | 0.347710E+12 | 0.00 | 0.00 | 0.00 | 0.293496E+09 | 0.00 | 0.00 | 0.00 |
May | 0.109147E+12 | 0.00 | 0.525324E+12 | 0.00 | 0.146145E+12 | 0.00 | 0.00 | 0.00 | 5755347.06 | 0.00 | 0.00 | 0.00 |
June | 0.105626E+12 | 0.00 | 0.858799E+12 | 0.00 | 0.241903E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.109147E+12 | 0.00 | 0.125623E+13 | 0.00 | 0.363986E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.109147E+12 | 0.00 | 0.160306E+13 | 0.00 | 0.462530E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.105626E+12 | 0.00 | 0.538048E+12 | 0.00 | 0.151542E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.109147E+12 | 0.00 | 0.860422E+12 | 0.00 | 0.227253E+12 | 0.00 | 0.00 | 0.00 | 75867837.02 | 0.00 | 0.00 | 0.00 |
November | 0.105626E+12 | 0.00 | 0.110435E+13 | 0.00 | 0.267201E+12 | 0.00 | 0.00 | 0.00 | 0.361504E+09 | 0.00 | 0.00 | 0.00 |
December | 0.109147E+12 | 0.00 | 0.141022E+13 | 0.00 | 0.307746E+12 | 0.00 | 0.00 | 0.00 | 0.516486E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128512E+13 | 0.00 | 0.118311E+14 | 0.00 | 0.302380E+13 | 0.00 | 0.00 | 0.00 | 0.138935E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.985846E+11 | 0.00 | 0.454691E+12 | 0.00 | 0.989545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.109147E+12 | 0.00 | 0.160306E+13 | 0.00 | 0.462530E+12 | 0.00 | 0.00 | 0.00 | 0.516486E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.144070E+10 | 0.00 | 0.730844E+10 | 0.00 | 0.156971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130128E+10 | 0.00 | 0.129351E+11 | 0.00 | 0.278603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144070E+10 | 0.00 | 0.212460E+11 | 0.00 | 0.477644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139423E+10 | 0.00 | 0.279324E+11 | 0.00 | 0.668216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144070E+10 | 0.00 | 0.102707E+11 | 0.00 | 0.276696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139423E+10 | 0.00 | 0.175614E+11 | 0.00 | 0.476817E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144070E+10 | 0.00 | 0.261840E+11 | 0.00 | 0.729785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144070E+10 | 0.00 | 0.321986E+11 | 0.00 | 0.889163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139423E+10 | 0.00 | 0.109737E+11 | 0.00 | 0.296572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144070E+10 | 0.00 | 0.171666E+11 | 0.00 | 0.438631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139423E+10 | 0.00 | 0.216049E+11 | 0.00 | 0.508232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144070E+10 | 0.00 | 0.272409E+11 | 0.00 | 0.580101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169631E+11 | 0.00 | 0.232623E+12 | 0.00 | 0.577743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130128E+10 | 0.00 | 0.730844E+10 | 0.00 | 0.156971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144070E+10 | 0.00 | 0.321986E+11 | 0.00 | 0.889163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.137395E+11 | 0.00 | 0.602230E+11 | 0.00 | 0.130667E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124099E+11 | 0.00 | 0.117004E+12 | 0.00 | 0.253314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137395E+11 | 0.00 | 0.199652E+12 | 0.00 | 0.449750E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132963E+11 | 0.00 | 0.265140E+12 | 0.00 | 0.634552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137395E+11 | 0.00 | 0.937600E+11 | 0.00 | 0.253154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132963E+11 | 0.00 | 0.163861E+12 | 0.00 | 0.445357E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137395E+11 | 0.00 | 0.244212E+12 | 0.00 | 0.681646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137395E+11 | 0.00 | 0.305475E+12 | 0.00 | 0.845759E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.132963E+11 | 0.00 | 0.994931E+11 | 0.00 | 0.269213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137395E+11 | 0.00 | 0.159298E+12 | 0.00 | 0.407570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132963E+11 | 0.00 | 0.203115E+12 | 0.00 | 0.478408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137395E+11 | 0.00 | 0.254445E+12 | 0.00 | 0.543392E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161771E+12 | 0.00 | 0.216568E+13 | 0.00 | 0.539278E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124099E+11 | 0.00 | 0.602230E+11 | 0.00 | 0.130667E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137395E+11 | 0.00 | 0.305475E+12 | 0.00 | 0.845759E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.138246E+10 | 0.00 | 0.539321E+10 | 0.00 | 0.118222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124867E+10 | 0.00 | 0.113564E+11 | 0.00 | 0.246955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138246E+10 | 0.00 | 0.197938E+11 | 0.00 | 0.446987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133787E+10 | 0.00 | 0.265462E+11 | 0.00 | 0.636051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138246E+10 | 0.00 | 0.954526E+10 | 0.00 | 0.257860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133787E+10 | 0.00 | 0.165728E+11 | 0.00 | 0.450552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138246E+10 | 0.00 | 0.247039E+11 | 0.00 | 0.689535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138246E+10 | 0.00 | 0.307492E+11 | 0.00 | 0.851172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133787E+10 | 0.00 | 0.101255E+11 | 0.00 | 0.274120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138246E+10 | 0.00 | 0.160092E+11 | 0.00 | 0.409928E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133787E+10 | 0.00 | 0.202126E+11 | 0.00 | 0.476918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138246E+10 | 0.00 | 0.250454E+11 | 0.00 | 0.536597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162774E+11 | 0.00 | 0.216053E+12 | 0.00 | 0.539490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124867E+10 | 0.00 | 0.539321E+10 | 0.00 | 0.118222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138246E+10 | 0.00 | 0.307492E+11 | 0.00 | 0.851172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.216384E+09 | 0.00 | 0.132472E+09 | 0.00 | 0.00 | 0.139079E+11 | 0.00 | 0.35 |
February | 0.00 | 0.400376E+09 | 0.00 | 0.111725E+09 | 0.00 | 0.00 | 0.869045E+10 | 0.00 | 0.28 |
March | 0.00 | 0.267095E+10 | 0.00 | 94611224.13 | 0.00 | 0.00 | 0.537799E+10 | 0.00 | 0.21 |
April | 0.00 | 0.499540E+10 | 0.00 | 58345666.99 | 0.00 | 0.00 | 0.139403E+10 | 0.00 | 0.12 |
May | 0.00 | 0.148340E+10 | 0.00 | 5943070.04 | 0.00 | 0.00 | 9687227.74 | 0.00 | 0.01 |
June | 0.00 | 0.173847E+10 | 0.00 | 13698017.20 | 0.00 | 0.00 | 0.117003E+09 | 0.00 | 0.01 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.304668E+09 | 0.00 | 30775548.89 | 0.00 | 0.00 | 0.461909E+09 | 0.00 | 0.01 |
November | 0.00 | 0.647156E+10 | 0.00 | 0.102557E+09 | 0.00 | 0.00 | 0.165423E+10 | 0.00 | 0.16 |
December | 0.00 | 0.278630E+10 | 0.00 | 0.128878E+09 | 0.00 | 0.00 | 0.721658E+10 | 0.00 | 0.29 |
Annual Sum or Average | 0.00 | 0.210675E+11 | 0.00 | 0.679005E+09 | 0.00 | 0.00 | 0.388298E+11 | 0.00 | 0.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.647156E+10 | 0.00 | 0.132472E+09 | 0.00 | 0.00 | 0.139079E+11 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.103682E+10 | 0.326049E+09 | 0.00 | 89227981.18 | 0.167989E+09 | 0.00 | 0.132158E+11 | 0.00 | 0.35 |
February | 0.757832E+09 | 0.145961E+10 | 0.00 | 76064966.63 | 0.337819E+09 | 0.00 | 0.850061E+10 | 0.00 | 0.35 |
March | 0.166010E+10 | 0.359977E+10 | 0.00 | 76844446.06 | 0.709927E+09 | 0.00 | 0.678488E+10 | 0.00 | 0.40 |
April | 0.130168E+10 | 0.891511E+10 | 0.00 | 36564247.21 | 0.488822E+10 | 0.00 | 0.211899E+10 | 0.00 | 0.45 |
May | 0.200939E+09 | 0.226375E+11 | 0.00 | 16287230.55 | 0.114375E+11 | 0.00 | 0.385116E+09 | 0.00 | 0.45 |
June | 23950139.30 | 0.391454E+11 | 0.00 | 1702410.65 | 0.217551E+11 | 0.00 | 15389742.63 | 0.00 | 0.46 |
July | 72824453.57 | 0.578453E+11 | 0.00 | 3094116.90 | 0.250416E+11 | 0.00 | 33312268.53 | 0.00 | 0.45 |
August | 0.00 | 0.683789E+11 | 0.00 | 0.00 | 0.213740E+11 | 0.00 | 0.00 | 0.00 | 0.45 |
September | 0.00 | 0.466687E+11 | 0.00 | 1347193.24 | 0.233991E+11 | 0.00 | 5812152.37 | 0.00 | 0.46 |
October | 0.262167E+09 | 0.288944E+11 | 0.00 | 12947336.87 | 0.136491E+11 | 0.00 | 0.326678E+09 | 0.00 | 0.45 |
November | 0.930015E+09 | 0.123198E+11 | 0.00 | 35373303.69 | 0.226732E+10 | 0.00 | 0.115918E+10 | 0.00 | 0.42 |
December | 0.147690E+10 | 0.237451E+10 | 0.00 | 89939315.56 | 0.913908E+09 | 0.00 | 0.786096E+10 | 0.00 | 0.39 |
Annual Sum or Average | 0.772323E+10 | 0.292565E+12 | 0.00 | 0.439393E+09 | 0.125942E+12 | 0.00 | 0.404068E+11 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.326049E+09 | 0.00 | 0.00 | 0.167989E+09 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.166010E+10 | 0.683789E+11 | 0.00 | 89939315.56 | 0.250416E+11 | 0.00 | 0.132158E+11 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.101179E+11 | 0.229676E+10 | 0.00 | 0.555522E+09 | 0.267860E+10 | 0.00 | 0.114909E+12 | 0.00 | 0.33 |
February | 0.806642E+10 | 0.119655E+11 | 0.00 | 0.465887E+09 | 0.361272E+10 | 0.00 | 0.721091E+11 | 0.00 | 0.33 |
March | 0.816788E+10 | 0.328288E+11 | 0.00 | 0.493640E+09 | 0.301219E+10 | 0.00 | 0.595122E+11 | 0.00 | 0.34 |
April | 0.524333E+10 | 0.809121E+11 | 0.00 | 0.237788E+09 | 0.309398E+11 | 0.00 | 0.198143E+11 | 0.00 | 0.35 |
May | 0.210725E+10 | 0.190785E+12 | 0.00 | 56728242.85 | 0.110914E+12 | 0.00 | 0.308161E+10 | 0.00 | 0.40 |
June | 0.254551E+09 | 0.319076E+12 | 0.00 | 6658976.74 | 0.219832E+12 | 0.00 | 0.229685E+09 | 0.00 | 0.42 |
July | 0.794909E+09 | 0.417783E+12 | 0.00 | 1425729.70 | 0.330343E+12 | 0.00 | 78025771.84 | 0.00 | 0.42 |
August | 0.00 | 0.485842E+12 | 0.00 | 0.00 | 0.317816E+12 | 0.00 | 0.00 | 0.00 | 0.42 |
September | 2948384.38 | 0.362512E+12 | 0.00 | 6602332.66 | 0.241909E+12 | 0.00 | 0.137206E+09 | 0.00 | 0.40 |
October | 0.173172E+10 | 0.221040E+12 | 0.00 | 55659606.82 | 0.120526E+12 | 0.00 | 0.305017E+10 | 0.00 | 0.37 |
November | 0.157492E+10 | 0.106256E+12 | 0.00 | 0.219574E+09 | 0.136168E+11 | 0.00 | 0.101374E+11 | 0.00 | 0.33 |
December | 0.723644E+10 | 0.212876E+11 | 0.00 | 0.513224E+09 | 0.649209E+10 | 0.00 | 0.671517E+11 | 0.00 | 0.33 |
Annual Sum or Average | 0.452982E+11 | 0.225259E+13 | 0.00 | 0.261271E+10 | 0.140169E+13 | 0.00 | 0.350210E+12 | 0.00 | 0.37 |
Minimum of Months | 0.00 | 0.229676E+10 | 0.00 | 0.00 | 0.267860E+10 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.101179E+11 | 0.485842E+12 | 0.00 | 0.555522E+09 | 0.330343E+12 | 0.00 | 0.114909E+12 | 0.00 | 0.42 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.406873E+10 | 0.193080E+09 | 0.00 | 38269389.86 | 0.229790E+09 | 0.00 | 0.711081E+10 | 0.00 | 0.31 |
February | 0.234245E+10 | 0.108783E+10 | 0.00 | 35592625.38 | 0.354451E+09 | 0.00 | 0.480696E+10 | 0.00 | 0.31 |
March | 0.142806E+10 | 0.298752E+10 | 0.00 | 39141043.71 | 0.251788E+09 | 0.00 | 0.470702E+10 | 0.00 | 0.33 |
April | 0.546842E+09 | 0.759909E+10 | 0.00 | 20177500.77 | 0.282458E+10 | 0.00 | 0.171972E+10 | 0.00 | 0.35 |
May | 0.194128E+09 | 0.185637E+11 | 0.00 | 5232189.05 | 0.104992E+11 | 0.00 | 0.278237E+09 | 0.00 | 0.40 |
June | 22735660.01 | 0.315849E+11 | 0.00 | 713591.16 | 0.213018E+11 | 0.00 | 21872245.51 | 0.00 | 0.42 |
July | 78887874.61 | 0.417849E+11 | 0.00 | 398277.91 | 0.318711E+11 | 0.00 | 6869140.66 | 0.00 | 0.42 |
August | 0.00 | 0.486513E+11 | 0.00 | 0.00 | 0.306473E+11 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 294654.75 | 0.360773E+11 | 0.00 | 554460.26 | 0.233427E+11 | 0.00 | 8492156.27 | 0.00 | 0.40 |
October | 0.167599E+09 | 0.216489E+11 | 0.00 | 5121727.92 | 0.115193E+11 | 0.00 | 0.274917E+09 | 0.00 | 0.36 |
November | 0.203989E+09 | 0.102560E+11 | 0.00 | 14601573.70 | 0.119941E+10 | 0.00 | 0.763954E+09 | 0.00 | 0.32 |
December | 0.208794E+10 | 0.187357E+10 | 0.00 | 35900629.05 | 0.733833E+09 | 0.00 | 0.443556E+10 | 0.00 | 0.31 |
Annual Sum or Average | 0.111417E+11 | 0.222308E+12 | 0.00 | 0.195703E+09 | 0.134775E+12 | 0.00 | 0.241344E+11 | 0.00 | 0.36 |
Minimum of Months | 0.00 | 0.193080E+09 | 0.00 | 0.00 | 0.229790E+09 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.406873E+10 | 0.486513E+11 | 0.00 | 39141043.71 | 0.318711E+11 | 0.00 | 0.711081E+10 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.615338E+09 | 43852682.59 | 0.00 | 6043839.12 | 22411440.82 | 0.00 | 0.870174E+09 | 0.00 | 0.30 |
February | 0.342606E+09 | 0.209982E+09 | 0.00 | 6478657.51 | 45865781.49 | 0.00 | 0.642264E+09 | 0.00 | 0.33 |
March | 0.313990E+09 | 0.590757E+09 | 0.00 | 7858295.76 | 94832771.53 | 0.00 | 0.656925E+09 | 0.00 | 0.44 |
April | 0.194068E+09 | 0.178658E+10 | 0.00 | 4203457.07 | 0.508959E+09 | 0.00 | 0.235672E+09 | 0.00 | 0.55 |
May | 21522168.12 | 0.570453E+10 | 0.00 | 2852055.65 | 0.706498E+09 | 0.00 | 66698774.40 | 0.00 | 0.65 |
June | 1952758.34 | 0.107565E+11 | 0.00 | 307377.37 | 0.106432E+10 | 0.00 | 3907711.45 | 0.00 | 0.70 |
July | 2740626.00 | 0.160286E+11 | 0.00 | 704077.80 | 0.807967E+09 | 0.00 | 13788763.19 | 0.00 | 0.73 |
August | 0.00 | 0.170705E+11 | 0.00 | 0.00 | 0.777605E+09 | 0.00 | 0.00 | 0.00 | 0.72 |
September | 6587.51 | 0.112381E+11 | 0.00 | 185765.76 | 0.139302E+10 | 0.00 | 838793.02 | 0.00 | 0.64 |
October | 31760961.37 | 0.564464E+10 | 0.00 | 1806160.28 | 0.116929E+10 | 0.00 | 45623133.23 | 0.00 | 0.57 |
November | 0.142829E+09 | 0.188486E+10 | 0.00 | 3303048.29 | 0.296232E+09 | 0.00 | 0.106011E+09 | 0.00 | 0.47 |
December | 0.367030E+09 | 0.324333E+09 | 0.00 | 7439238.51 | 0.122712E+09 | 0.00 | 0.613276E+09 | 0.00 | 0.37 |
Annual Sum or Average | 0.203384E+10 | 0.712831E+11 | 0.00 | 41181973.12 | 0.700972E+10 | 0.00 | 0.325518E+10 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 43852682.59 | 0.00 | 0.00 | 22411440.82 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.615338E+09 | 0.170705E+11 | 0.00 | 7858295.76 | 0.139302E+10 | 0.00 | 0.870174E+09 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.534941E+09 | 32662985.70 | 0.00 | 4924919.19 | 18462928.43 | 0.00 | 0.716889E+09 | 0.00 | 0.39 |
February | 0.303300E+09 | 0.148547E+09 | 0.00 | 4918498.34 | 36573100.37 | 0.00 | 0.515712E+09 | 0.00 | 0.41 |
March | 0.309593E+09 | 0.427846E+09 | 0.00 | 5410018.60 | 79830100.31 | 0.00 | 0.449435E+09 | 0.00 | 0.51 |
April | 0.181711E+09 | 0.132204E+10 | 0.00 | 2958712.47 | 0.418374E+09 | 0.00 | 0.164532E+09 | 0.00 | 0.66 |
May | 15474754.93 | 0.432546E+10 | 0.00 | 2369941.51 | 0.643092E+09 | 0.00 | 56663347.82 | 0.00 | 0.80 |
June | 2276970.85 | 0.759956E+10 | 0.00 | 193490.43 | 0.124522E+10 | 0.00 | 2277383.90 | 0.00 | 0.82 |
July | 4745736.09 | 0.111538E+11 | 0.00 | 360188.56 | 0.104198E+10 | 0.00 | 7261031.24 | 0.00 | 0.83 |
August | 0.00 | 0.120148E+11 | 0.00 | 0.00 | 0.931769E+09 | 0.00 | 0.00 | 0.00 | 0.81 |
September | 0.00 | 0.861736E+10 | 0.00 | 141591.88 | 0.124624E+10 | 0.00 | 659975.17 | 0.00 | 0.79 |
October | 18424418.96 | 0.434176E+10 | 0.00 | 1623197.59 | 0.102096E+10 | 0.00 | 51222037.64 | 0.00 | 0.69 |
November | 0.121614E+09 | 0.136451E+10 | 0.00 | 2240930.45 | 0.252034E+09 | 0.00 | 80144326.19 | 0.00 | 0.55 |
December | 0.371828E+09 | 0.213031E+09 | 0.00 | 4618266.33 | 0.103033E+09 | 0.00 | 0.395110E+09 | 0.00 | 0.43 |
Annual Sum or Average | 0.186391E+10 | 0.515613E+11 | 0.00 | 29759755.35 | 0.703758E+10 | 0.00 | 0.243991E+10 | 0.00 | 0.64 |
Minimum of Months | 0.00 | 32662985.70 | 0.00 | 0.00 | 18462928.43 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.534941E+09 | 0.120148E+11 | 0.00 | 5410018.60 | 0.124624E+10 | 0.00 | 0.716889E+09 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.516377E+09 | 90697990.39 | 0.00 | 13017986.65 | 12840245.77 | 0.00 | 0.168530E+10 | 0.00 | 0.48 |
February | 0.356693E+09 | 0.331696E+09 | 0.00 | 11157999.50 | 27231212.61 | 0.00 | 0.102243E+10 | 0.00 | 0.49 |
March | 0.354559E+09 | 0.784977E+09 | 0.00 | 10447569.84 | 88338557.78 | 0.00 | 0.823024E+09 | 0.00 | 0.55 |
April | 0.218515E+09 | 0.204086E+10 | 0.00 | 4275360.16 | 0.532025E+09 | 0.00 | 0.240510E+09 | 0.00 | 0.61 |
May | 28477376.77 | 0.532802E+10 | 0.00 | 2385255.65 | 0.103489E+10 | 0.00 | 57847656.47 | 0.00 | 0.64 |
June | 3231364.42 | 0.939091E+10 | 0.00 | 250631.51 | 0.192361E+10 | 0.00 | 2714031.33 | 0.00 | 0.67 |
July | 6159994.37 | 0.148193E+11 | 0.00 | 519059.27 | 0.141238E+10 | 0.00 | 10131059.29 | 0.00 | 0.70 |
August | 0.00 | 0.171305E+11 | 0.00 | 0.00 | 0.104305E+10 | 0.00 | 0.00 | 0.00 | 0.73 |
September | 7371.97 | 0.130012E+11 | 0.00 | 189500.88 | 0.144959E+10 | 0.00 | 848475.75 | 0.00 | 0.74 |
October | 23994113.81 | 0.772655E+10 | 0.00 | 3020605.49 | 0.903327E+09 | 0.00 | 77726905.50 | 0.00 | 0.72 |
November | 0.142242E+09 | 0.288639E+10 | 0.00 | 5862537.29 | 0.206855E+09 | 0.00 | 0.169123E+09 | 0.00 | 0.65 |
December | 0.358540E+09 | 0.611277E+09 | 0.00 | 13146335.03 | 93034955.82 | 0.00 | 0.101319E+10 | 0.00 | 0.54 |
Annual Sum or Average | 0.200880E+10 | 0.741424E+11 | 0.00 | 64272841.28 | 0.872718E+10 | 0.00 | 0.510285E+10 | 0.00 | 0.63 |
Minimum of Months | 0.00 | 90697990.39 | 0.00 | 0.00 | 12840245.77 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 0.516377E+09 | 0.171305E+11 | 0.00 | 13146335.03 | 0.192361E+10 | 0.00 | 0.168530E+10 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.502722E+09 | 50242195.51 | 0.00 | 7655497.61 | 21321884.47 | 0.00 | 0.112120E+10 | 0.00 | 0.51 |
February | 0.158189E+09 | 0.224057E+09 | 0.00 | 8765485.20 | 36462624.40 | 0.00 | 0.979456E+09 | 0.00 | 0.59 |
March | 0.205781E+09 | 0.687978E+09 | 0.00 | 11492567.64 | 55757122.51 | 0.00 | 0.972688E+09 | 0.00 | 0.78 |
April | 0.115593E+09 | 0.235552E+10 | 0.00 | 5965967.33 | 0.220460E+09 | 0.00 | 0.380802E+09 | 0.00 | 0.96 |
May | 28615947.08 | 0.452002E+10 | 0.00 | 1766908.10 | 0.951074E+09 | 0.00 | 44922187.71 | 0.00 | 0.85 |
June | 2953519.80 | 0.909999E+10 | 0.00 | 208036.83 | 0.123279E+10 | 0.00 | 2475617.79 | 0.00 | 0.94 |
July | 3135804.02 | 0.136821E+11 | 0.00 | 540091.42 | 0.933013E+09 | 0.00 | 12734149.58 | 0.00 | 0.99 |
August | 0.00 | 0.156966E+11 | 0.00 | 0.00 | 0.705960E+09 | 0.00 | 0.00 | 0.00 | 1.02 |
September | 14020.45 | 0.843823E+10 | 0.00 | 120771.16 | 0.217135E+10 | 0.00 | 565465.14 | 0.00 | 0.83 |
October | 38023725.76 | 0.476552E+10 | 0.00 | 1193491.29 | 0.132408E+10 | 0.00 | 32561266.11 | 0.00 | 0.79 |
November | 0.123928E+09 | 0.195104E+10 | 0.00 | 4708086.38 | 0.217442E+09 | 0.00 | 0.156651E+09 | 0.00 | 0.77 |
December | 0.186952E+09 | 0.488335E+09 | 0.00 | 12705150.29 | 71762517.56 | 0.00 | 0.110337E+10 | 0.00 | 0.74 |
Annual Sum or Average | 0.136591E+10 | 0.619596E+11 | 0.00 | 55122053.23 | 0.794147E+10 | 0.00 | 0.480742E+10 | 0.00 | 0.82 |
Minimum of Months | 0.00 | 50242195.51 | 0.00 | 0.00 | 21321884.47 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.502722E+09 | 0.156966E+11 | 0.00 | 12705150.29 | 0.217135E+10 | 0.00 | 0.112120E+10 | 0.00 | 1.02 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.988629E+10 | 0.280218E+09 | 0.00 | 25063323.19 | 0.358121E+09 | 0.00 | 0.395795E+10 | 0.00 | 0.29 |
February | 0.569516E+10 | 0.178658E+10 | 0.00 | 30456929.47 | 0.502955E+09 | 0.00 | 0.361115E+10 | 0.00 | 0.32 |
March | 0.366469E+10 | 0.590247E+10 | 0.00 | 43260119.50 | 0.390452E+09 | 0.00 | 0.450463E+10 | 0.00 | 0.38 |
April | 0.130577E+10 | 0.177176E+11 | 0.00 | 24868896.05 | 0.377110E+10 | 0.00 | 0.195600E+10 | 0.00 | 0.48 |
May | 0.204815E+09 | 0.587916E+11 | 0.00 | 15297632.56 | 0.969106E+10 | 0.00 | 0.742346E+09 | 0.00 | 0.69 |
June | 25300677.24 | 0.111664E+12 | 0.00 | 2526437.64 | 0.173247E+11 | 0.00 | 69215478.81 | 0.00 | 0.79 |
July | 74632383.82 | 0.162942E+12 | 0.00 | 2615833.66 | 0.211808E+11 | 0.00 | 65124094.30 | 0.00 | 0.82 |
August | 0.00 | 0.173406E+12 | 0.00 | 0.00 | 0.232929E+11 | 0.00 | 0.00 | 0.00 | 0.82 |
September | 155082.61 | 0.109714E+12 | 0.00 | 1304323.80 | 0.223217E+11 | 0.00 | 25654158.80 | 0.00 | 0.69 |
October | 0.240506E+09 | 0.501386E+11 | 0.00 | 7748018.71 | 0.139679E+11 | 0.00 | 0.426978E+09 | 0.00 | 0.54 |
November | 0.644159E+09 | 0.178280E+11 | 0.00 | 14969232.25 | 0.187545E+10 | 0.00 | 0.762503E+09 | 0.00 | 0.39 |
December | 0.538060E+10 | 0.268523E+10 | 0.00 | 30672578.45 | 0.943196E+09 | 0.00 | 0.316052E+10 | 0.00 | 0.31 |
Annual Sum or Average | 0.271221E+11 | 0.712857E+12 | 0.00 | 0.198783E+09 | 0.115620E+12 | 0.00 | 0.192821E+11 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 0.280218E+09 | 0.00 | 0.00 | 0.358121E+09 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.988629E+10 | 0.173406E+12 | 0.00 | 43260119.50 | 0.232929E+11 | 0.00 | 0.450463E+10 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.723210E+10 | 0.313555E+09 | 0.00 | 28560904.77 | 0.212242E+09 | 0.00 | 0.503636E+10 | 0.00 | 0.40 |
February | 0.421488E+10 | 0.141416E+10 | 0.00 | 32938169.02 | 0.411938E+09 | 0.00 | 0.423916E+10 | 0.00 | 0.44 |
March | 0.305741E+10 | 0.485412E+10 | 0.00 | 40139571.39 | 0.316317E+09 | 0.00 | 0.424037E+10 | 0.00 | 0.51 |
April | 0.111872E+10 | 0.157727E+11 | 0.00 | 26191245.90 | 0.249799E+10 | 0.00 | 0.197726E+10 | 0.00 | 0.65 |
May | 0.148283E+09 | 0.472111E+11 | 0.00 | 14403092.76 | 0.843379E+10 | 0.00 | 0.663127E+09 | 0.00 | 0.90 |
June | 23193303.22 | 0.855527E+11 | 0.00 | 1699631.43 | 0.164170E+11 | 0.00 | 51900874.85 | 0.00 | 0.98 |
July | 71258385.66 | 0.123008E+12 | 0.00 | 1453818.49 | 0.207009E+11 | 0.00 | 42578114.38 | 0.00 | 1.01 |
August | 0.00 | 0.134421E+12 | 0.00 | 0.00 | 0.220444E+11 | 0.00 | 0.00 | 0.00 | 1.02 |
September | 500514.55 | 0.894130E+11 | 0.00 | 995024.12 | 0.189489E+11 | 0.00 | 20184133.55 | 0.00 | 0.89 |
October | 0.148797E+09 | 0.434148E+11 | 0.00 | 8970910.32 | 0.108093E+11 | 0.00 | 0.514556E+09 | 0.00 | 0.71 |
November | 0.478344E+09 | 0.146041E+11 | 0.00 | 14432077.10 | 0.161650E+10 | 0.00 | 0.817943E+09 | 0.00 | 0.52 |
December | 0.412481E+10 | 0.236942E+10 | 0.00 | 27211385.88 | 0.684518E+09 | 0.00 | 0.334058E+10 | 0.00 | 0.41 |
Annual Sum or Average | 0.206183E+11 | 0.562348E+12 | 0.00 | 0.196996E+09 | 0.103094E+12 | 0.00 | 0.209440E+11 | 0.00 | 0.71 |
Minimum of Months | 0.00 | 0.313555E+09 | 0.00 | 0.00 | 0.212242E+09 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.723210E+10 | 0.134421E+12 | 0.00 | 40139571.39 | 0.220444E+11 | 0.00 | 0.503636E+10 | 0.00 | 1.02 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.585676E+10 | 0.102592E+10 | 0.00 | 0.107449E+09 | 93127573.69 | 0.00 | 0.163559E+11 | 0.00 | 0.52 |
February | 0.406843E+10 | 0.365548E+10 | 0.00 | 90174030.38 | 0.164321E+09 | 0.00 | 0.102789E+11 | 0.00 | 0.53 |
March | 0.333796E+10 | 0.881191E+10 | 0.00 | 77845102.76 | 0.218926E+09 | 0.00 | 0.758750E+10 | 0.00 | 0.55 |
April | 0.143482E+10 | 0.221263E+11 | 0.00 | 29442034.05 | 0.341949E+10 | 0.00 | 0.225283E+10 | 0.00 | 0.56 |
May | 0.241194E+09 | 0.574264E+11 | 0.00 | 14398939.67 | 0.122234E+11 | 0.00 | 0.707630E+09 | 0.00 | 0.71 |
June | 29749182.65 | 0.101428E+12 | 0.00 | 2173378.03 | 0.238376E+11 | 0.00 | 62004196.21 | 0.00 | 0.77 |
July | 91767636.90 | 0.156513E+12 | 0.00 | 2154736.98 | 0.279027E+11 | 0.00 | 56874790.91 | 0.00 | 0.82 |
August | 0.00 | 0.185883E+12 | 0.00 | 0.00 | 0.258658E+11 | 0.00 | 0.00 | 0.00 | 0.88 |
September | 0.00 | 0.143742E+12 | 0.00 | 1511205.74 | 0.189716E+11 | 0.00 | 29399976.52 | 0.00 | 0.85 |
October | 0.120724E+09 | 0.838592E+11 | 0.00 | 22549981.32 | 0.894495E+10 | 0.00 | 0.863819E+09 | 0.00 | 0.80 |
November | 0.377942E+09 | 0.326096E+11 | 0.00 | 42726887.85 | 0.909005E+09 | 0.00 | 0.173472E+10 | 0.00 | 0.67 |
December | 0.349741E+10 | 0.689859E+10 | 0.00 | 0.100042E+09 | 0.416440E+09 | 0.00 | 0.100359E+11 | 0.00 | 0.55 |
Annual Sum or Average | 0.190568E+11 | 0.803980E+12 | 0.00 | 0.490467E+09 | 0.122967E+12 | 0.00 | 0.499656E+11 | 0.00 | 0.69 |
Minimum of Months | 0.00 | 0.102592E+10 | 0.00 | 0.00 | 93127573.69 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.585676E+10 | 0.185883E+12 | 0.00 | 0.107449E+09 | 0.279027E+11 | 0.00 | 0.163559E+11 | 0.00 | 0.88 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.899216E+10 | 0.357144E+09 | 0.00 | 27909516.02 | 0.235104E+09 | 0.00 | 0.475341E+10 | 0.00 | 0.45 |
February | 0.494033E+10 | 0.185799E+10 | 0.00 | 34771876.57 | 0.362322E+09 | 0.00 | 0.437804E+10 | 0.00 | 0.49 |
March | 0.316172E+10 | 0.594951E+10 | 0.00 | 45629853.45 | 0.195155E+09 | 0.00 | 0.497809E+10 | 0.00 | 0.59 |
April | 0.108669E+10 | 0.186775E+11 | 0.00 | 23493913.52 | 0.229310E+10 | 0.00 | 0.193727E+10 | 0.00 | 0.71 |
May | 0.191092E+09 | 0.537218E+11 | 0.00 | 12334744.51 | 0.753598E+10 | 0.00 | 0.591402E+09 | 0.00 | 0.94 |
June | 24246174.26 | 0.974790E+11 | 0.00 | 1824283.82 | 0.143660E+11 | 0.00 | 53006119.35 | 0.00 | 1.05 |
July | 68576785.19 | 0.137977E+12 | 0.00 | 2241251.26 | 0.187106E+11 | 0.00 | 61626070.89 | 0.00 | 1.08 |
August | 0.00 | 0.155712E+12 | 0.00 | 0.00 | 0.179646E+11 | 0.00 | 0.00 | 0.00 | 1.12 |
September | 552527.05 | 0.102131E+12 | 0.00 | 953017.44 | 0.170349E+11 | 0.00 | 19980852.03 | 0.00 | 0.95 |
October | 0.227979E+09 | 0.481868E+11 | 0.00 | 6529165.93 | 0.106021E+11 | 0.00 | 0.369707E+09 | 0.00 | 0.77 |
November | 0.580465E+09 | 0.167279E+11 | 0.00 | 16415821.66 | 0.150757E+10 | 0.00 | 0.780675E+09 | 0.00 | 0.57 |
December | 0.460332E+10 | 0.298077E+10 | 0.00 | 31310616.26 | 0.747883E+09 | 0.00 | 0.377075E+10 | 0.00 | 0.47 |
Annual Sum or Average | 0.238771E+11 | 0.641758E+12 | 0.00 | 0.203414E+09 | 0.915553E+11 | 0.00 | 0.216940E+11 | 0.00 | 0.77 |
Minimum of Months | 0.00 | 0.357144E+09 | 0.00 | 0.00 | 0.195155E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.899216E+10 | 0.155712E+12 | 0.00 | 45629853.45 | 0.187106E+11 | 0.00 | 0.497809E+10 | 0.00 | 1.12 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.106181E+10 | 22966740.79 | 0.00 | 1840720.60 | 32850890.62 | 1030389.53 | 0.344866E+09 | 0.00 | 0.31 |
February | 0.586371E+09 | 0.154764E+09 | 0.00 | 2675281.53 | 58768647.56 | 0.00 | 0.326022E+09 | 0.00 | 0.32 |
March | 0.411236E+09 | 0.515866E+09 | 0.00 | 3916697.02 | 40124775.22 | 0.00 | 0.395344E+09 | 0.00 | 0.38 |
April | 0.165564E+09 | 0.161059E+10 | 0.00 | 2435245.64 | 0.360279E+09 | 0.00 | 0.156558E+09 | 0.00 | 0.48 |
May | 20982286.22 | 0.546692E+10 | 0.00 | 1424960.25 | 0.925006E+09 | 0.00 | 65006350.95 | 0.00 | 0.68 |
June | 2116314.55 | 0.105191E+11 | 0.00 | 259376.66 | 0.175932E+10 | 0.00 | 6416872.23 | 0.00 | 0.77 |
July | 7820244.67 | 0.154181E+11 | 0.00 | 276436.61 | 0.212278E+10 | 0.00 | 6044116.03 | 0.00 | 0.80 |
August | 0.00 | 0.164243E+11 | 0.00 | 0.00 | 0.234082E+10 | 0.00 | 0.00 | 0.00 | 0.80 |
September | 42121.83 | 0.105702E+11 | 0.00 | 108901.00 | 0.221514E+10 | 0.00 | 1574379.86 | 0.00 | 0.68 |
October | 28369248.19 | 0.482707E+10 | 0.00 | 693129.89 | 0.138885E+10 | 0.00 | 38293286.62 | 0.00 | 0.54 |
November | 72232931.98 | 0.168654E+10 | 0.00 | 1319669.36 | 0.187425E+09 | 0.00 | 60343189.67 | 0.00 | 0.39 |
December | 0.532881E+09 | 0.245151E+09 | 0.00 | 2440814.80 | 0.105046E+09 | 0.00 | 0.288546E+09 | 0.00 | 0.31 |
Annual Sum or Average | 0.288943E+10 | 0.674616E+11 | 0.00 | 17391233.38 | 0.115364E+11 | 1030389.53 | 0.168902E+10 | 0.00 | 0.54 |
Minimum of Months | 0.00 | 22966740.79 | 0.00 | 0.00 | 32850890.62 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.106181E+10 | 0.164243E+11 | 0.00 | 3916697.02 | 0.234082E+10 | 1030389.53 | 0.395344E+09 | 0.00 | 0.80 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.723608E+09 | 27059147.72 | 0.00 | 2445073.43 | 18414577.20 | 885345.78 | 0.450335E+09 | 0.00 | 0.40 |
February | 0.371281E+09 | 0.124095E+09 | 0.00 | 3160855.25 | 45022664.11 | 0.00 | 0.416922E+09 | 0.00 | 0.43 |
March | 0.283204E+09 | 0.435087E+09 | 0.00 | 3927213.86 | 28096154.21 | 0.00 | 0.411297E+09 | 0.00 | 0.51 |
April | 0.114894E+09 | 0.144733E+10 | 0.00 | 2753554.32 | 0.212496E+09 | 0.00 | 0.182601E+09 | 0.00 | 0.65 |
May | 13141274.06 | 0.440504E+10 | 0.00 | 1443544.29 | 0.727954E+09 | 0.00 | 59989343.64 | 0.00 | 0.87 |
June | 1865421.11 | 0.809139E+10 | 0.00 | 190671.27 | 0.151492E+10 | 0.00 | 5068289.73 | 0.00 | 0.94 |
July | 6814333.43 | 0.116386E+11 | 0.00 | 164929.87 | 0.188419E+10 | 0.00 | 4036828.64 | 0.00 | 0.97 |
August | 0.00 | 0.128089E+11 | 0.00 | 0.00 | 0.196185E+10 | 0.00 | 0.00 | 0.00 | 0.99 |
September | 34537.52 | 0.866119E+10 | 0.00 | 87840.15 | 0.170373E+10 | 0.00 | 1244432.47 | 0.00 | 0.88 |
October | 11970849.46 | 0.422856E+10 | 0.00 | 981924.43 | 0.991840E+09 | 0.00 | 52229640.11 | 0.00 | 0.71 |
November | 49602107.22 | 0.142581E+10 | 0.00 | 1341671.81 | 0.140440E+09 | 0.00 | 64856132.69 | 0.00 | 0.52 |
December | 0.385996E+09 | 0.222026E+09 | 0.00 | 2448814.92 | 71260805.20 | 0.00 | 0.296121E+09 | 0.00 | 0.41 |
Annual Sum or Average | 0.196241E+10 | 0.535150E+11 | 0.00 | 18946093.60 | 0.930022E+10 | 885345.78 | 0.194470E+10 | 0.00 | 0.69 |
Minimum of Months | 0.00 | 27059147.72 | 0.00 | 0.00 | 18414577.20 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.723608E+09 | 0.128089E+11 | 0.00 | 3927213.86 | 0.196185E+10 | 885345.78 | 0.450335E+09 | 0.00 | 0.99 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.685749E+09 | 81834745.26 | 0.00 | 9351758.49 | 12234468.90 | 0.00 | 0.150121E+10 | 0.00 | 0.50 |
February | 0.401146E+09 | 0.313292E+09 | 0.00 | 8436374.33 | 21720250.32 | 0.00 | 0.100990E+10 | 0.00 | 0.51 |
March | 0.343816E+09 | 0.753089E+09 | 0.00 | 7481815.27 | 23310391.06 | 0.00 | 0.728774E+09 | 0.00 | 0.53 |
April | 0.176875E+09 | 0.199062E+10 | 0.00 | 2981748.45 | 0.315810E+09 | 0.00 | 0.187293E+09 | 0.00 | 0.56 |
May | 24173446.32 | 0.532674E+10 | 0.00 | 1338584.58 | 0.115733E+10 | 0.00 | 62517040.23 | 0.00 | 0.69 |
June | 2786235.33 | 0.963125E+10 | 0.00 | 220994.99 | 0.230975E+10 | 0.00 | 5637655.08 | 0.00 | 0.75 |
July | 9515769.12 | 0.147952E+11 | 0.00 | 230892.01 | 0.275451E+10 | 0.00 | 5231821.52 | 0.00 | 0.80 |
August | 0.00 | 0.175000E+11 | 0.00 | 0.00 | 0.257582E+10 | 0.00 | 0.00 | 0.00 | 0.86 |
September | 46434.76 | 0.135398E+11 | 0.00 | 124469.23 | 0.196627E+10 | 0.00 | 1813839.05 | 0.00 | 0.83 |
October | 11890983.05 | 0.783761E+10 | 0.00 | 2314401.73 | 0.943527E+09 | 0.00 | 84264076.05 | 0.00 | 0.78 |
November | 46230831.84 | 0.302212E+10 | 0.00 | 4165358.67 | 98528526.24 | 0.00 | 0.152508E+09 | 0.00 | 0.66 |
December | 0.340608E+09 | 0.618004E+09 | 0.00 | 8931400.71 | 45227431.63 | 0.00 | 0.949507E+09 | 0.00 | 0.53 |
Annual Sum or Average | 0.204284E+10 | 0.754095E+11 | 0.00 | 45577798.45 | 0.122240E+11 | 0.00 | 0.468866E+10 | 0.00 | 0.67 |
Minimum of Months | 0.00 | 81834745.26 | 0.00 | 0.00 | 12234468.90 | 0.00 | 0.00 | 0.00 | 0.50 |
Maximum of Months | 0.685749E+09 | 0.175000E+11 | 0.00 | 9351758.49 | 0.275451E+10 | 0.00 | 0.150121E+10 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.941137E+09 | 30098302.33 | 0.00 | 2396255.34 | 19664406.18 | 0.00 | 0.426922E+09 | 0.00 | 0.46 |
February | 0.484571E+09 | 0.159784E+09 | 0.00 | 3222071.04 | 43683291.68 | 0.00 | 0.415563E+09 | 0.00 | 0.49 |
March | 0.332161E+09 | 0.506743E+09 | 0.00 | 4309834.49 | 25372023.33 | 0.00 | 0.459150E+09 | 0.00 | 0.58 |
April | 0.137689E+09 | 0.165145E+10 | 0.00 | 2296476.63 | 0.221591E+09 | 0.00 | 0.157490E+09 | 0.00 | 0.69 |
May | 19076863.62 | 0.482787E+10 | 0.00 | 1155235.62 | 0.751861E+09 | 0.00 | 52107135.73 | 0.00 | 0.90 |
June | 2068881.13 | 0.893254E+10 | 0.00 | 192990.64 | 0.149495E+10 | 0.00 | 4914247.37 | 0.00 | 1.00 |
July | 7178894.11 | 0.126943E+11 | 0.00 | 224425.45 | 0.192385E+10 | 0.00 | 5425840.90 | 0.00 | 1.04 |
August | 0.00 | 0.144087E+11 | 0.00 | 0.00 | 0.182556E+10 | 0.00 | 0.00 | 0.00 | 1.07 |
September | 39672.35 | 0.954446E+10 | 0.00 | 83748.01 | 0.174382E+10 | 0.00 | 1254926.46 | 0.00 | 0.93 |
October | 24583124.78 | 0.452515E+10 | 0.00 | 584364.41 | 0.106297E+10 | 0.00 | 34963833.97 | 0.00 | 0.75 |
November | 61250037.85 | 0.157684E+10 | 0.00 | 1516711.91 | 0.142874E+09 | 0.00 | 65243979.07 | 0.00 | 0.57 |
December | 0.446297E+09 | 0.273933E+09 | 0.00 | 2680770.92 | 76358651.18 | 0.00 | 0.348358E+09 | 0.00 | 0.47 |
Annual Sum or Average | 0.245605E+10 | 0.591318E+11 | 0.00 | 18662884.47 | 0.933255E+10 | 0.00 | 0.197139E+10 | 0.00 | 0.75 |
Minimum of Months | 0.00 | 30098302.33 | 0.00 | 0.00 | 19664406.18 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.941137E+09 | 0.144087E+11 | 0.00 | 4309834.49 | 0.192385E+10 | 0.00 | 0.459150E+09 | 0.00 | 1.07 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 51381519.47 | 0.00 | 6429828.50 | 0.00 | 0.00 | 0.209273E+09 | 0.00 | 0.58 |
February | 0.00 | 0.137499E+09 | 0.00 | 8224642.25 | 0.00 | 0.00 | 72213182.72 | 0.00 | 0.58 |
March | 0.00 | 0.209834E+09 | 0.00 | 14137604.06 | 0.00 | 0.00 | 52720269.95 | 0.00 | 0.59 |
April | 0.00 | 0.494791E+09 | 0.00 | 5415402.46 | 0.00 | 0.00 | 8996950.12 | 0.00 | 0.59 |
May | 0.00 | 0.846092E+09 | 0.00 | 112790.37 | 0.00 | 0.00 | 618178.07 | 0.00 | 0.59 |
June | 0.00 | 0.137906E+10 | 0.00 | 6259.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.181445E+10 | 0.00 | 5646.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.185027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.145365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.104145E+10 | 0.00 | 468659.74 | 0.00 | 0.00 | 677585.71 | 0.00 | 0.59 |
November | 0.00 | 0.543011E+09 | 0.00 | 1543367.72 | 0.00 | 0.00 | 1156660.05 | 0.00 | 0.58 |
December | 0.00 | 0.239091E+09 | 0.00 | 15734165.72 | 0.00 | 0.00 | 52537416.10 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.100606E+11 | 0.00 | 52078366.46 | 0.00 | 0.00 | 0.398193E+09 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 51381519.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.185027E+10 | 0.00 | 15734165.72 | 0.00 | 0.00 | 0.209273E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.467294E+09 | 0.00 | 49757599.87 | 0.00 | 0.00 | 0.219400E+10 | 0.00 | 0.58 |
February | 0.00 | 0.134747E+10 | 0.00 | 72828323.01 | 0.00 | 0.00 | 0.748742E+09 | 0.00 | 0.58 |
March | 0.00 | 0.208768E+10 | 0.00 | 0.132658E+09 | 0.00 | 0.00 | 0.537799E+09 | 0.00 | 0.59 |
April | 0.00 | 0.494530E+10 | 0.00 | 51955532.23 | 0.00 | 0.00 | 91678298.78 | 0.00 | 0.59 |
May | 0.00 | 0.833979E+10 | 0.00 | 1028159.32 | 0.00 | 0.00 | 6536926.82 | 0.00 | 0.59 |
June | 0.00 | 0.137088E+11 | 0.00 | 71519.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.180785E+11 | 0.00 | 55672.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.186886E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.143160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.103393E+11 | 0.00 | 4372795.15 | 0.00 | 0.00 | 7211214.40 | 0.00 | 0.59 |
November | 0.00 | 0.540692E+10 | 0.00 | 14569111.14 | 0.00 | 0.00 | 12893306.57 | 0.00 | 0.58 |
December | 0.00 | 0.238130E+10 | 0.00 | 0.146785E+09 | 0.00 | 0.00 | 0.537397E+09 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.100107E+12 | 0.00 | 0.474082E+09 | 0.00 | 0.00 | 0.413626E+10 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 0.467294E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.186886E+11 | 0.00 | 0.146785E+09 | 0.00 | 0.00 | 0.219400E+10 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 45149163.88 | 0.00 | 4003182.52 | 0.00 | 0.00 | 0.227539E+09 | 0.00 | 0.58 |
February | 0.00 | 0.134210E+09 | 0.00 | 6837890.19 | 0.00 | 0.00 | 76298806.44 | 0.00 | 0.58 |
March | 0.00 | 0.208848E+09 | 0.00 | 12994903.04 | 0.00 | 0.00 | 54149175.65 | 0.00 | 0.59 |
April | 0.00 | 0.494697E+09 | 0.00 | 5160252.81 | 0.00 | 0.00 | 9182914.27 | 0.00 | 0.59 |
May | 0.00 | 0.836565E+09 | 0.00 | 100598.39 | 0.00 | 0.00 | 654596.68 | 0.00 | 0.59 |
June | 0.00 | 0.137276E+10 | 0.00 | 7011.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.180947E+10 | 0.00 | 5320.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
August | 0.00 | 0.186575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.60 |
September | 0.00 | 0.143575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
October | 0.00 | 0.103469E+10 | 0.00 | 430556.94 | 0.00 | 0.00 | 729850.23 | 0.00 | 0.59 |
November | 0.00 | 0.540690E+09 | 0.00 | 1421582.80 | 0.00 | 0.00 | 1354399.92 | 0.00 | 0.58 |
December | 0.00 | 0.237944E+09 | 0.00 | 14294490.14 | 0.00 | 0.00 | 54210768.20 | 0.00 | 0.58 |
Annual Sum or Average | 0.00 | 0.100165E+11 | 0.00 | 45255789.36 | 0.00 | 0.00 | 0.424119E+09 | 0.00 | 0.59 |
Minimum of Months | 0.00 | 45149163.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.00 | 0.186575E+10 | 0.00 | 14294490.14 | 0.00 | 0.00 | 0.227539E+09 | 0.00 | 0.60 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.143944E+10 | 0.00 | 0.344828E+09 | 0.00 | 0.00 | 0.440665E+10 | 0.00 | 0.66 |
February | 0.00 | 0.311998E+10 | 0.00 | 0.402128E+09 | 0.00 | 0.00 | 0.152376E+10 | 0.00 | 0.66 |
March | 0.00 | 0.450552E+10 | 0.00 | 0.650182E+09 | 0.00 | 0.00 | 0.108986E+10 | 0.00 | 0.66 |
April | 0.00 | 0.105968E+11 | 0.00 | 0.223712E+09 | 0.00 | 0.00 | 0.157354E+09 | 0.00 | 0.66 |
May | 0.00 | 0.194533E+11 | 0.00 | 5796317.16 | 0.00 | 0.00 | 13604642.61 | 0.00 | 0.66 |
June | 0.00 | 0.306798E+11 | 0.00 | 134323.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
July | 0.00 | 0.397534E+11 | 0.00 | 565597.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
August | 0.00 | 0.418780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
September | 0.00 | 0.335179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
October | 0.00 | 0.231821E+11 | 0.00 | 22759796.33 | 0.00 | 0.00 | 11824035.51 | 0.00 | 0.66 |
November | 0.00 | 0.118117E+11 | 0.00 | 67020552.20 | 0.00 | 0.00 | 16034256.75 | 0.00 | 0.66 |
December | 0.00 | 0.504497E+10 | 0.00 | 0.729687E+09 | 0.00 | 0.00 | 0.103017E+10 | 0.00 | 0.66 |
Annual Sum or Average | 0.00 | 0.224983E+12 | 0.00 | 0.244681E+10 | 0.00 | 0.00 | 0.824927E+10 | 0.00 | 0.66 |
Minimum of Months | 0.00 | 0.143944E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
Maximum of Months | 0.00 | 0.418780E+11 | 0.00 | 0.729687E+09 | 0.00 | 0.00 | 0.440665E+10 | 0.00 | 0.67 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:45
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.254542E+12 | 0.232497E+10 | 0.00 | 0.456376E+12 | 0.155303E+13 |
February | 0.287307E+12 | 0.179249E+10 | 0.00 | 0.289571E+12 | 0.201264E+13 |
March | 0.352519E+12 | 0.812415E+09 | 0.00 | 0.202414E+12 | 0.302412E+13 |
April | 0.370726E+12 | -0.201297E+10 | 0.00 | -0.169365E+12 | 0.385859E+13 |
May | 0.377192E+12 | -0.572124E+10 | 0.00 | -0.684863E+12 | 0.380640E+13 |
June | 0.358868E+12 | -0.113632E+11 | 0.00 | -0.136445E+13 | 0.501641E+13 |
July | 0.349281E+12 | -0.153587E+11 | 0.00 | -0.191977E+13 | 0.623301E+13 |
August | 0.332307E+12 | -0.151887E+11 | 0.00 | -0.205463E+13 | 0.705157E+13 |
September | 0.290953E+12 | -0.120100E+11 | 0.00 | -0.156733E+13 | 0.468838E+13 |
October | 0.246268E+12 | -0.621627E+10 | 0.00 | -0.843368E+12 | 0.417092E+13 |
November | 0.202190E+12 | -0.143000E+10 | 0.00 | -0.211848E+12 | 0.346867E+13 |
December | 0.215037E+12 | 0.104653E+10 | 0.00 | 0.223823E+12 | 0.311274E+13 |
Annual Sum or Average | 0.363719E+13 | -0.633246E+11 | 0.00 | -0.764344E+13 | 0.479965E+14 |
Minimum of Months | 0.202190E+12 | -0.153587E+11 | 0.00 | -0.205463E+13 | 0.155303E+13 |
Maximum of Months | 0.377192E+12 | 0.232497E+10 | 0.00 | 0.456376E+12 | 0.705157E+13 |