Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Simulation Timestamp: 2024-07-03 12:21:54
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 31154.39 | 672.58 | 672.58 |
Net Site Energy | 31154.39 | 672.58 | 672.58 |
Total Source Energy | 98665.94 | 2130.08 | 2130.08 |
Net Source Energy | 98665.94 | 2130.08 | 2130.08 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 60.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3643.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3216.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 350.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2566.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2924.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 611.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1225.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13591.35 |
Humidification | 1540.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 572.98 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 338.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 31154.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16444.50 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 60.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 3643.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3216.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 350.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 55.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2505.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2924.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 611.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 1225.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13591.35 |
Humidification | General | 1540.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 572.98 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 338.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 60.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 3643.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3216.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 350.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 2566.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2924.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 611.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 1225.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13591.35 |
Humidification | Unassigned | 1540.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 572.98 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 338.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 77.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 223.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Other | 372.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 672.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 77.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 223.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Other | 372.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 672.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 31154.386 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 31154.386 | 100.00 |
Total On-Site and Utility Electric Sources | 31154.386 | 100.00 |
Total Electricity End Uses | 31154.386 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 16444.50 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 16444.50 | 100.00 |
Total Water End Uses | 16444.50 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 3124.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5859.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Latitude [deg] | 32.17 |
Longitude [deg] | -110.9 |
Elevation [m] | 809.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 8.6849 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 8.6849 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 8.7339 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 8.7339 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.6849 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 8.6849 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 8.6849 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 8.6849 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 8.6849 | 18.58 | 484.4232 | |
Total | 46320.38 | 8.7339 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 8.7339 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.6845 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 25-AUG-15:09 | - | - | - | - | - | - | - | - | - | - | - | 27-JUN-11:00 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 444304.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 280450.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 233302.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 256047.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 44322.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 86268.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 1888.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 23349.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2148306.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 444304.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 280450.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3430.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 256047.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 44322.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 86268.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 1888.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 23349.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 192.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 11539.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 10185.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1110.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8128.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9260.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1936.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 3882.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 4878.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1071.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 98665.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 4.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 249.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 219.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 23.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 199.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 41.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 83.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 105.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 23.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2130.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 4.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 249.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 219.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 23.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 199.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 41.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 83.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 105.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 23.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2130.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 6.24 | 0.339632 | 0.000000 | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | |
CORE_BOTTOM VAV BOX COMPONENT | 6.53 | 0.291308 | 0.304000 | 1.98 | 0.776822 | 0.500000 | 0.001308 |
CORE_MID VAV BOX COMPONENT | 61.63 | 0.308641 | 0.317000 | 19.54 | 0.823042 | 0.500000 | 0.001234 |
CORE_TOP VAV BOX COMPONENT | 6.15 | 0.309413 | 0.327000 | 2.01 | 0.825101 | 0.500000 | 0.001231 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.24 | 0.192450 | 0.201000 | 0.249430 | 0.513201 | 0.500000 | 0.001980 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.22 | 0.126228 | 0.200000 | 0.243852 | 0.336609 | 0.500000 | 0.003018 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.39 | 0.171817 | 0.200000 | 0.278001 | 0.458178 | 0.500000 | 0.002217 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.56 | 0.098650 | 0.200000 | 0.312024 | 0.300000 | 0.500000 | 0.003862 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 11.92 | 0.200324 | 0.206000 | 2.46 | 0.534198 | 0.500000 | 0.001902 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 12.70 | 0.121191 | 0.200000 | 2.54 | 0.323176 | 0.500000 | 0.003144 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 13.36 | 0.178721 | 0.200000 | 2.67 | 0.476589 | 0.500000 | 0.002132 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 13.77 | 0.111728 | 0.200000 | 2.75 | 0.300000 | 0.500000 | 0.003410 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.35 | 0.176881 | 0.200000 | 0.270035 | 0.471684 | 0.500000 | 0.002154 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.30 | 0.118539 | 0.200000 | 0.259671 | 0.316103 | 0.500000 | 0.003214 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.48 | 0.161084 | 0.200000 | 0.296524 | 0.429557 | 0.500000 | 0.002365 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.48 | 0.103884 | 0.200000 | 0.296303 | 0.300000 | 0.500000 | 0.003668 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 60184.56 |
CORE_MID VAV BOX REHEAT COIL | 592338.47 |
CORE_TOP VAV BOX REHEAT COIL | 69148.79 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 7562.98 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 7393.83 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 9923.96 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 9460.87 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 171899.78 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 115486.37 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 173796.25 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 105902.49 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 21892.79 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 14581.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 22094.02 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 13787.72 |
VAV_BOT WITH REHEAT HEATING COIL | 36953.07 |
VAV_MID WITH REHEAT HEATING COIL | 300717.11 |
VAV_TOP WITH REHEAT HEATING COIL | 29125.14 |
CAV_BAS HEATING COIL | 273349.35 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 14683.19 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 678.30 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 6783.03 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 678.30 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.519407 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.95 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.506793 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 27.03 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.97 | 3.07 | 11.94 | 3.07 | 10.69 | 10.69 | 0.300000 | 0.286995 | 10.69 |
VAV_MID WITH REHEAT | 56.69 | 29.96 | 113.39 | 29.96 | 100.24 | 100.24 | 0.300000 | 0.298885 | 100.24 |
VAV_TOP WITH REHEAT | 5.88 | 3.13 | 11.76 | 4.67 | 11.24 | 11.24 | 0.300000 | 0.415217 | 11.24 |
CAV_BAS | 0.000000 | 0.000000 | 6.24 | 1.20 | 6.24 | 6.24 | 1.00 | 0.192458 | 6.24 |
AIRLOOP DATACENTER BASEMENT | 27.03 | 27.03 | 27.03 | 27.03 | 27.03 | 27.03 | 1.00 | 0.999990 | 27.03 |
AIRLOOP DATACENTER BOT | 0.519407 | 0.519407 | 0.519407 | 0.519407 | 0.519407 | 0.519407 | 1.00 | 1.00 | 0.519407 |
AIRLOOP DATACENTER MID | 4.95 | 4.95 | 4.95 | 4.95 | 4.95 | 4.95 | 1.00 | 1.00 | 4.95 |
AIRLOOP DATACENTER TOP | 0.506793 | 0.506793 | 0.506793 | 0.506793 | 0.506793 | 0.506793 | 1.00 | 1.00 | 0.506793 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 10.69 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 100.24 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 11.24 | |
CAV_BAS_OA_CONTROLLER | 6.24 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 27.03 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.519407 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.95 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.506793 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 28.05 | 6.67 | 10.87 | 0.008047 | 0.008047 | 204772.35 | 0.005856 | 10.69 |
VAV_MID WITH REHEAT COOLING COIL | 28.45 | 6.67 | 10.86 | 0.007982 | 0.007982 | 1964942.00 | 0.056197 | 100.24 |
VAV_TOP WITH REHEAT COOLING COIL | 27.81 | 6.67 | 10.87 | 0.008062 | 0.008062 | 212301.05 | 0.006072 | 11.24 |
CAV_BAS COOLING COIL | 27.51 | 6.67 | 10.85 | 0.008259 | 0.008259 | 115892.20 | 0.003315 | 6.24 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 10.69 |
VAV_MID WITH REHEAT FAN | 100.24 |
VAV_TOP WITH REHEAT FAN | 11.24 |
CAV_BAS FAN | 6.24 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.005856 | 0.000081 |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.056197 | 0.000008 |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.006072 | 0.000078 |
CAV_BAS_COOLC_CONTROLLER | 0.003315 | 0.000144 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 27.03 | 508246.95 | 332730.32 | 0.012447 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.519407 | 9557.29 | 6322.04 | 0.000234 |
AIRLOOP DATACENTER MID COOLING COIL | 4.95 | 91230.29 | 60324.96 | 0.002234 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.506793 | 9333.61 | 6171.18 | 0.000229 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 27.03 | 27.03 | 27.03 | 27.03 | 508246.95 | 508246.95 | 14683.19 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.519407 | 0.519407 | 0.519407 | 0.519407 | 9557.29 | 9557.29 | 678.30 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.95 | 4.95 | 4.95 | 4.95 | 91230.29 | 91230.29 | 6783.03 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.506793 | 0.506793 | 0.506793 | 0.506793 | 9333.61 | 9333.61 | 678.30 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 27.03 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.519407 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.95 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.506793 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 27.03 | 508246.95 | 0.012447 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.519407 | 9557.29 | 0.000234 |
AIRLOOP DATACENTER MID HEATING COIL | 4.95 | 91230.29 | 0.002234 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.506793 | 9333.61 | 0.000229 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000119 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.071440 | 11663.94 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.071440 | 8.57 |
COOLSYS1_SUPPLY | 0.071440 | 8.57 |
SINGLE WATER PLANT LOOP | 0.015144 | 1.82 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.071440 | 0.071440 | 299868.86 | 8.33 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.035720 | 4037.67 |
COOLSYS1 CHILLER2 PUMP | 0.035720 | 4037.67 |
PLANT CIRC PUMP | 0.015144 | 3862.43 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.071440 | 0.036107 | 1262477.63 | 1262477.72 | 0.063572 |
COOLSYS1 CHILLER2 | 0.071440 | 0.036107 | 1262477.63 | 1262477.72 | 0.063572 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | U-factor Times Area Value at High Fan Speed [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/K] | |
CENTRAL TOWER | 0.015144 | 150366.66 | 76121.42 | 75183.33 | 7879.72 | 45672.85 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
CENTRAL BOILER | 623794.56 | 610343.60 | 0.015144 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.127144 | 15.26 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.127144 | 31478.08 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 53.66 | 1511757.42 | 10.73 | 188969.68 |
TOWERWATERSYS COOLTOWER 2 | 53.66 | 1511757.42 | 10.73 | 188969.68 |
Design Water Flow Rate [m3/s] Equipment # 27 | |
WSHPPLANT OPERATION SCHEME | 0.065467 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 20.90 | 15.40 | 11.90 | 14.80 | 12.70 | 15.40 | 23.30 | 26.30 | 31.20 | 30.40 | 29.80 | 27.80 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 | 32.17 | -110.88 | -7.00 | 809.00 | 91976 | 1.0932 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.66 | 19.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 8.685 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 13.527 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 8.685 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 493.108 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 24139.153 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 24139.153 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 6806.209 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6806.209 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.452 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.400 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.662 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5215 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.5467 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4343 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
47 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
48 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
49 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
50 | 9 | 0.81534556E-15 | 0.47534309E-16 | -0.12491808E-09 | -0.15651055E-17 |
51 | 8 | 0.18376575E-07 | 0.18892299E-12 | 0.33997552E-03 | -0.20894799E-09 |
52 | 7 | -0.11109444E-01 | 0.10222184E-07 | -0.21454547E-01 | 0.12631841E-03 |
53 | 6 | 0.37458360 | 0.36213810E-05 | 0.44579641 | -0.43850983E-02 |
54 | 5 | -4.8902522 | 0.13734403E-03 | -4.2389002 | 0.59460182E-01 |
55 | 4 | 31.674104 | 0.11393769E-02 | 20.648451 | -0.40448134 |
56 | 3 | -108.39803 | 0.25142476E-02 | -54.058051 | 1.4743366 |
57 | 2 | 194.32686 | 0.14299560E-02 | 76.440274 | -2.8561868 |
58 | 1 | -170.12819 | 0.15421596E-03 | -54.840647 | 2.7274244 |
59 | 0 | 57.057407 | 0.88766417E-06 | 15.629571 | |
60 | 9 | 0.15527634E-14 | 0.48972640E-16 | -0.12737755E-09 | -0.48559044E-17 |
61 | 8 | 0.18724477E-07 | 0.18300980E-12 | 0.34384059E-03 | -0.21290374E-09 |
62 | 7 | -0.11225506E-01 | 0.98577958E-08 | -0.21621905E-01 | 0.12763808E-03 |
63 | 6 | 0.37773826 | 0.34860306E-05 | 0.44850155 | -0.44222837E-02 |
64 | 5 | -4.9210508 | 0.13200769E-03 | -4.2597582 | 0.59842059E-01 |
65 | 4 | 31.810414 | 0.10936068E-02 | 20.730162 | -0.40629104 |
66 | 3 | -108.68827 | 0.24103335E-02 | -54.219675 | 1.4785295 |
67 | 2 | 194.61479 | 0.13693941E-02 | 76.588171 | -2.8607587 |
68 | 1 | -170.23464 | 0.14753937E-03 | -54.883028 | 2.7292902 |
69 | 0 | 57.057407 | 0.84836289E-06 | 15.622061 | |
70 | 9 | 0.10580992E-14 | 0.52916478E-16 | -0.11479962E-09 | -0.26242945E-17 |
71 | 8 | 0.16943687E-07 | 0.21219816E-12 | 0.32378363E-03 | -0.19265555E-09 |
72 | 7 | -0.10622292E-01 | 0.11706466E-07 | -0.20751735E-01 | 0.12077931E-03 |
73 | 6 | 0.36134106 | 0.41796623E-05 | 0.43441658 | -0.42290030E-02 |
74 | 5 | -4.7609497 | 0.15957712E-03 | -4.1510514 | 0.57856955E-01 |
75 | 4 | 31.101728 | 0.13316855E-02 | 20.304070 | -0.39688243 |
76 | 3 | -107.17897 | 0.29539374E-02 | -53.376774 | 1.4567269 |
77 | 2 | 193.11717 | 0.16877407E-02 | 75.817308 | -2.8369794 |
78 | 1 | -169.68078 | 0.18278585E-03 | -54.662957 | 2.7195831 |
79 | 0 | 57.057407 | 0.10570564E-05 | 15.661738 | |
80 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
81 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
82 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
83 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
84 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
85 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
86 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
87 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
88 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
89 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
90 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
91 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
92 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
93 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
94 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
95 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
96 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
97 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
98 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
99 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
100 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
101 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
102 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
103 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
104 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
105 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
106 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
107 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
108 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
109 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
110 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
111 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
112 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
113 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
114 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
115 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
116 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
117 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
118 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
119 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
120 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
121 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
122 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
123 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
124 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
125 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
126 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
127 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.538_SHGC_EAST_0.25 | 35 | 1 | VerySmooth | 3.059 | 3.059 | 1.000 | 0.251 | ||
2 | WINDOW_U_0.538_SHGC_SOUTH_0.25 | 36 | 1 | VerySmooth | 3.059 | 3.059 | 1.000 | 0.251 | ||
3 | WINDOW_U_0.538_SHGC_WEST_0.25 | 37 | 1 | VerySmooth | 3.059 | 3.059 | 1.000 | 0.251 | ||
4 | WINDOW_U_0.538_SHGC_NORTH_0.25 | 38 | 1 | VerySmooth | 3.059 | 3.059 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 1.36932E-002 | 0.16139 | 0.60628 | 0.60628 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 8.71585E-002 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 1.36932E-002 | 0.16139 | 0.60628 | 0.60628 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 8.71585E-002 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 1.36932E-002 | 0.16139 | 0.60628 | 0.60628 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 8.71585E-002 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 1.36932E-002 | 0.16139 | 0.60628 | 0.60628 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 8.71585E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 1.973E-005 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1541E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1555E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4749E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4761E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1446E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1455E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7585E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7591E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1871E-003 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.2816E-003 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5024E-003 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.5833E-003 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1675E-003 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2346E-003 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7734E-003 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8107E-003 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1048 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6139E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1171 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.0515E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7648E-002 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.9542E-002 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1622E-002 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0968E-002 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1916E-003 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.3034E-003 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.5071E-003 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.6067E-003 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1717E-003 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2505E-003 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7738E-003 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8117E-003 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.1540E-003 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.1555E-003 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.4748E-003 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.4761E-003 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1445E-003 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1456E-003 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.7585E-003 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.7590E-003 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.9043E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0903E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7213E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9204E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5390E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6265E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0071E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0329E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.3488E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.0811E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0676E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.8868E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2079E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.7221E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.2931E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.2292E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8539E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9216E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.6570E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7063E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.5116E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.5313E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.0072E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.0333E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7778E-003 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7792E-003 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5183E-003 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5195E-003 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3457E-003 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3465E-003 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7586E-003 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7591E-003 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8102E-003 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8915E-003 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5448E-003 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6093E-003 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3670E-003 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4135E-003 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7738E-003 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8118E-003 |
81 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7838E-002 |
82 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4576E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1413E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.1067E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9200E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 7.4748E-003 |
87 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1622E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0965E-002 |
89 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8087E-003 |
90 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8898E-003 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5429E-003 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6056E-003 |
93 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3638E-003 |
94 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4037E-003 |
95 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7735E-003 |
96 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8107E-003 |
97 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7777E-003 |
98 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7791E-003 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5183E-003 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5194E-003 |
101 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.3456E-003 |
102 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3463E-003 |
103 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7585E-003 |
104 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7591E-003 |
105 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.5106E-003 |
106 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5804E-003 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2340E-003 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2844E-003 |
109 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2155E-003 |
110 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2339E-003 |
111 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0073E-003 |
112 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0334E-003 |
113 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7526E-002 |
114 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.8527E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.3389E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.6077E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6649E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5119E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2931E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.2292E-002 |
121 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.5533E-003 |
122 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7064E-003 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2888E-003 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.4470E-003 |
125 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.2416E-003 |
126 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.3218E-003 |
127 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.0071E-003 |
128 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.0328E-003 |
129 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1049 |
130 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.5516E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1138 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 7.1197E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 8.5402E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 4.4281E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 3.8788E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 1.9168E-002 |
137 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.1871E-002 |
138 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.0141E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.8733E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.7778E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.9992E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.5600E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 3.9762E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 1.9389E-002 |
145 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.4831E-002 |
146 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.3131E-002 |
147 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.7533E-002 |
148 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.8322E-002 |
149 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 2.5075E-002 |
150 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.3800E-002 |
151 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.8788E-002 |
152 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.9165E-002 |
153 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.5124E-002 |
154 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.6982E-002 |
155 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.0478E-002 |
156 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.3907E-002 |
157 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.3899E-002 |
158 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2783E-002 |
159 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 3.9762E-002 |
160 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 1.9389E-002 |
161 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1050 |
162 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.5659E-002 |
163 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1139 |
164 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 7.1362E-002 |
165 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 8.5542E-002 |
166 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 4.4392E-002 |
167 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 3.8871E-002 |
168 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 1.9210E-002 |
169 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.1914E-002 |
170 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.0188E-002 |
171 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.8782E-002 |
172 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.7823E-002 |
173 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.0074E-002 |
174 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.5654E-002 |
175 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 3.9845E-002 |
176 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 1.9432E-002 |
177 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.4835E-002 |
178 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.3158E-002 |
179 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.7539E-002 |
180 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.8343E-002 |
181 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 2.5115E-002 |
182 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.3825E-002 |
183 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.8871E-002 |
184 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.9207E-002 |
185 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.5154E-002 |
186 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.7021E-002 |
187 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.0512E-002 |
188 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.3942E-002 |
189 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.3970E-002 |
190 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2831E-002 |
191 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 3.9845E-002 |
192 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 1.9432E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 78600.67463 | 78600.67463 | 6.23594 | 6.23594 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 30.95800 | 5.61598E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | 00:10:00 | 0.50000 | 4.31558E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 82305.43080 | 82305.43080 | 6.52932 | 6.52932 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 30.95800 | 5.61598E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | 00:10:00 | 0.50000 | 4.31558E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 | |
5 | CORE_MID | Cooling | 777006.48983 | 777006.48983 | 61.62644 | 61.62644 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 30.95800 | 5.61598E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 199376.40583 | 199376.40583 | 9.24287 | 10.77825 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 77505.86428 | 77505.86428 | 6.14727 | 6.14727 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 30.95800 | 5.61598E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 48775.85901 | 48775.85901 | 2.28056 | 2.28056 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 15506.09129 | 15506.09129 | 1.24095 | 1.24095 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 40.80000 | 5.63111E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 5051.11466 | 5051.11466 | 0.23581 | 0.23581 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 15235.18241 | 15235.18241 | 1.21926 | 1.21926 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 34.99233 | 5.62211E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 3770.88902 | 3770.88902 | 0.17625 | 0.17625 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 17368.63325 | 17368.63325 | 1.39000 | 1.39000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 40.57833 | 5.63076E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 6993.19861 | 6993.19861 | 0.32730 | 0.32730 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 19494.42306 | 19494.42306 | 1.56012 | 1.56012 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 39.11533 | 5.62848E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 2277.08926 | 2277.08926 | 0.10590 | 0.10590 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 148968.54192 | 148968.54192 | 11.92171 | 11.92171 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 40.66700 | 5.63090E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 120833.70250 | 120833.70250 | 5.66933 | 5.66933 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 158686.81186 | 158686.81186 | 12.69937 | 12.69937 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 35.36917 | 5.62269E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 81167.05060 | 81167.05060 | 3.80879 | 3.80879 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 166979.11290 | 166979.11290 | 13.36306 | 13.36306 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 40.68917 | 5.63093E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 122161.83517 | 122161.83517 | 5.73188 | 5.73188 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 172127.44943 | 172127.44943 | 13.77499 | 13.77499 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.93800 | 5.62821E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 74453.83769 | 74453.83769 | 3.49271 | 3.49271 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 16871.32393 | 16871.32393 | 1.35017 | 1.35017 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 40.53400 | 5.63070E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 15377.71874 | 15377.71874 | 0.72203 | 0.72203 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 16223.86776 | 16223.86776 | 1.29835 | 1.29835 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 35.74600 | 5.62327E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 10240.91032 | 10240.91032 | 0.48089 | 0.48089 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 18526.32131 | 18526.32131 | 1.48262 | 1.48262 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 40.80000 | 5.63111E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 15518.65074 | 15518.65074 | 0.72867 | 0.72867 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 18512.62996 | 18512.62996 | 1.48152 | 1.48152 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.93800 | 5.62821E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 9685.17587 | 9685.17587 | 0.45473 | 0.45473 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50000 | 4.31558E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8228.41855 | 8228.41855 | 0.51941 | 0.51941 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 35.94550 | 5.62358E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 0.50000 | 4.31558E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 78489.23677 | 78489.23677 | 4.95456 | 4.95456 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 35.94550 | 5.62358E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | 00:10:00 | 0.50000 | 4.31558E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8028.56689 | 8028.56689 | 0.50679 | 0.50679 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 36.27800 | 5.62409E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | 00:10:00 | 0.50000 | 4.31558E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 372329.90037 | 428179.38543 | 23.50238 | 27.02774 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 28.69700 | 5.61258E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | 00:10:00 | 0.50000 | 4.31558E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 176247.99 | 10.69083 | 10.69083 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 25983.94 | 1.92308 | 1.92308 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1647754.82 | 100.23568 | 100.23568 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 342920.93 | 29.48096 | 29.48096 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 184338.07 | 11.23959 | 11.23959 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 34045.17 | 4.66687 | 4.66687 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 |
7 | CAV_BAS | Cooling | Sensible | 89051.05 | 6.23594 | 6.23594 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 52075.95 | 1.20016 | 1.20016 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 426142.85 | 27.02800 | 27.02800 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 14683.19 | 0.33839 | 0.33839 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8257.41 | 0.51941 | 0.51941 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 678.30 | 1.56323E-002 | 1.56323E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 78818.97 | 4.95456 | 4.95456 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 6783.03 | 0.15632 | 0.15632 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8063.85 | 0.50679 | 0.50679 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 678.30 | 1.56323E-002 | 1.56323E-002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 6.23594 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.33963 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.00000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 0.00000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.52932 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29131 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30400 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.98491 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.77682 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.30789E-003 |
12 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 60184.56456 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 61.62644 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30864 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31700 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 19.53558 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.82304 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.23444E-003 |
20 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 592338.46893 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.14727 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30941 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32700 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.01016 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.82510 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.23136E-003 |
28 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 69148.79165 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.24095 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19245 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20100 |
32 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24943 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51320 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.97973E-003 |
36 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7562.97875 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.21926 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12623 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24385 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33661 |
42 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.01834E-003 |
44 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7393.83426 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.39000 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17182 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27800 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45818 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.21748E-003 |
52 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9923.95761 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.56012 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.86496E-002 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.31202 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.86215E-003 |
60 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9460.87235 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.92171 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20032 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20600 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.45587 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.53420 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.90192E-003 |
68 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 171899.77551 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.69937 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12119 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.53987 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32318 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.14379E-003 |
76 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 115486.36646 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.36306 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17872 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.67261 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47659 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.13181E-003 |
84 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 173796.24948 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.77499 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11173 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.75500 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.41007E-003 |
92 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 105902.48900 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.35017 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17688 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27003 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47168 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.15399E-003 |
100 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 21892.78608 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.29835 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11854 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25967 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31610 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.21414E-003 |
108 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14581.00009 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.48262 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16108 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29652 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42956 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.36523E-003 |
116 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 22094.01740 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.48152 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10388 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29630 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.66757E-003 |
124 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 13787.72179 |
125 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.51941 |
126 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.95456 |
127 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.50679 |
128 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 27.02774 |
129 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.96982 |
130 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.06822 |
131 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.93965 |
132 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.06822 |
133 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.69083 |
134 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.69083 |
135 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
136 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.28700 |
137 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 56.69279 |
138 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 29.95894 |
139 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 113.38557 |
140 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 29.95894 |
141 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 100.23568 |
142 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 100.23568 |
143 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
144 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.29888 |
145 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.87997 |
146 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.13269 |
147 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.75993 |
148 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 4.66687 |
149 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 11.23959 |
150 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 11.23959 |
151 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
152 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.41522 |
153 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.00000 |
154 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.00000 |
155 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.23594 |
156 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 1.20016 |
157 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.23594 |
158 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 6.23594 |
159 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
160 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.19246 |
161 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 27.02774 |
162 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 27.02774 |
163 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 27.02774 |
164 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 27.02774 |
165 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 27.02800 |
166 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 27.02800 |
167 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
168 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
169 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.51941 |
170 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.51941 |
171 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.51941 |
172 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.51941 |
173 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.51941 |
174 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.51941 |
175 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
176 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
177 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.95456 |
178 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.95456 |
179 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.95456 |
180 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.95456 |
181 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.95456 |
182 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.95456 |
183 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
184 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
185 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.50679 |
186 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.50679 |
187 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.50679 |
188 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.50679 |
189 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.50679 |
190 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.50679 |
191 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
192 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
193 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.69083 |
194 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 100.23568 |
195 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 11.23959 |
196 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 6.23594 |
197 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 27.02800 |
198 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.51941 |
199 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.95456 |
200 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.50679 |
201 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.69083 |
202 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.05293 |
203 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
204 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.87195 |
205 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.04696E-003 |
206 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.04696E-003 |
207 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 204772.35029 |
208 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.85646E-003 |
209 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.69083 |
210 | Coil:Heating:Electric | VAV_BOT WITH REHEAT HEATING COIL | Design Size Nominal Capacity [W] | 36953.06916 |
211 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.69083 |
212 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.85646E-003 |
213 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 8.13102E-005 |
214 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 100.23568 |
215 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 28.44741 |
216 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
217 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.86142 |
218 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.98235E-003 |
219 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.98235E-003 |
220 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1964942.00154 |
221 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.61971E-002 |
222 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 100.23568 |
223 | Coil:Heating:Electric | VAV_MID WITH REHEAT HEATING COIL | Design Size Nominal Capacity [W] | 300717.11375 |
224 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 100.23568 |
225 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.61971E-002 |
226 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 8.47358E-006 |
227 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 11.23959 |
228 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.81450 |
229 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
230 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.87200 |
231 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.06237E-003 |
232 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.06237E-003 |
233 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 212301.05055 |
234 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.07178E-003 |
235 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 11.23959 |
236 | Coil:Heating:Electric | VAV_TOP WITH REHEAT HEATING COIL | Design Size Nominal Capacity [W] | 29125.14198 |
237 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 11.23959 |
238 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.07178E-003 |
239 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.84268E-005 |
240 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.23594 |
241 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
242 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 27.51364 |
243 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
244 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.84990 |
245 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.25936E-003 |
246 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.25936E-003 |
247 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 115892.20018 |
248 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.31450E-003 |
249 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.23594 |
250 | Coil:Heating:Electric | CAV_BAS HEATING COIL | Design Size Nominal Capacity [W] | 273349.34771 |
251 | Fan:VariableVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 6.23594 |
252 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.31450E-003 |
253 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.43669E-004 |
254 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 27.02800 |
255 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
256 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 27.02800 |
257 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 508246.94973 |
258 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 332730.31571 |
259 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.24469E-002 |
260 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 27.02800 |
261 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 27.02800 |
262 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 27.02800 |
263 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 27.02800 |
264 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 508246.94973 |
265 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 508246.94973 |
266 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 14683.19080 |
267 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
268 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 27.02800 |
269 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 27.02800 |
270 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 508246.94973 |
271 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.24469E-002 |
272 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 14683.19080 |
273 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.19058E-004 |
274 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
275 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
276 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
277 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.51941 |
278 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
279 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.51941 |
280 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9557.29040 |
281 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6322.03619 |
282 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.34057E-004 |
283 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.51941 |
284 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.51941 |
285 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.51941 |
286 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.51941 |
287 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9557.29040 |
288 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9557.29040 |
289 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 678.30259 |
290 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
291 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.51941 |
292 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.51941 |
293 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9557.29040 |
294 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.34057E-004 |
295 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 678.30259 |
296 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.95456 |
297 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
298 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.95456 |
299 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 91230.28685 |
300 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 60324.95998 |
301 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.23422E-003 |
302 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.95456 |
303 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.95456 |
304 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.95456 |
305 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.95456 |
306 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 91230.28685 |
307 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 91230.28685 |
308 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 6783.02586 |
309 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
310 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.95456 |
311 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.95456 |
312 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 91230.28685 |
313 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.23422E-003 |
314 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 6783.02586 |
315 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.50679 |
316 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
317 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.50679 |
318 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9333.60760 |
319 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6171.17692 |
320 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.28579E-004 |
321 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.50679 |
322 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.50679 |
323 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.50679 |
324 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.50679 |
325 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9333.60760 |
326 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9333.60760 |
327 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 678.30259 |
328 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
329 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.50679 |
330 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.50679 |
331 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9333.60760 |
332 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.28579E-004 |
333 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 678.30259 |
334 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 7.14398E-002 |
335 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 11663.94311 |
336 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 7.14398E-002 |
337 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 8.57278 |
338 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 7.14398E-002 |
339 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 7.14398E-002 |
340 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 299868.85985 |
341 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
342 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 7.14398E-002 |
343 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 8.57278 |
344 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 3.57199E-002 |
345 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 4037.67058 |
346 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 3.57199E-002 |
347 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 4037.67058 |
348 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 7.14398E-002 |
349 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.61067E-002 |
350 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1262477.62891 |
351 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1262477.72000 |
352 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 6.35721E-002 |
353 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 7.14398E-002 |
354 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.61067E-002 |
355 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1262477.62891 |
356 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1262477.72000 |
357 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 6.35721E-002 |
358 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.51438E-002 |
359 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.81726 |
360 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.51438E-002 |
361 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3862.42524 |
362 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.51438E-002 |
363 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 150366.65806 |
364 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at High Fan Speed [W/K] | 76121.41897 |
365 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 75183.32903 |
366 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
367 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/K] | 45672.85138 |
368 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 623794.55914 |
369 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 610343.60000 |
370 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.51438E-002 |
371 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
372 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
373 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
374 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
375 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
376 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.12714 |
377 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 15.25730 |
378 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.12714 |
379 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 31478.07550 |
380 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 53.66257 |
381 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1511757.41834 |
382 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 10.73251 |
383 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 188969.67729 |
384 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 53.66257 |
385 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1511757.41834 |
386 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 10.73251 |
387 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 188969.67729 |
388 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 27 | 6.54675E-002 |
389 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 27 | 6.54675E-002 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 268501.16 | 177475.86 | 91025.30 | 0.66 | 60707.17 | 615.73 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2553012.32 | 1677963.56 | 875048.75 | 0.66 | 576284.58 | 5845.00 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 280414.06 | 185861.79 | 94552.26 | 0.66 | 64182.18 | 650.97 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 152387.92 | 101844.80 | 50543.12 | 0.67 | 32883.23 | 333.52 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 8.97 | 30.62 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 8.97 | 30.62 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_NORTH_0.25 | N/A | 3.059 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_NORTH_0.25 | N/A | 3.059 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_NORTH_0.25 | N/A | 3.059 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_NORTH_0.25 | N/A | 3.059 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_NORTH_0.25 | N/A | 3.059 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_EAST_0.25 | N/A | 3.059 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_EAST_0.25 | N/A | 3.059 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_EAST_0.25 | N/A | 3.059 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_SOUTH_0.25 | N/A | 3.059 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_SOUTH_0.25 | N/A | 3.059 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_SOUTH_0.25 | N/A | 3.059 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_SOUTH_0.25 | N/A | 3.059 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_SOUTH_0.25 | N/A | 3.059 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_WEST_0.25 | N/A | 3.059 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_WEST_0.25 | N/A | 3.059 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_WEST_0.25 | N/A | 3.059 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_NORTH_0.25 | N/A | 3.059 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_EAST_0.25 | N/A | 3.059 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_SOUTH_0.25 | N/A | 3.059 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_WEST_0.25 | N/A | 3.059 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_NORTH_0.25 | N/A | 3.059 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_EAST_0.25 | N/A | 3.059 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_SOUTH_0.25 | N/A | 3.059 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.538_SHGC_WEST_0.25 | N/A | 3.059 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.452 | 1.193 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.400 | 1.158 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.662 | 1.331 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.2612959863E-003 | 1.3959275976E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.1293013818 | 0.2073817453 | Pass | Pass | 0.1488598233 | 0.3551639411 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 5.0077438193E-002 | 0.1048453485 | Pass | Pass | 9.0239064280E-002 | 0.2852469880 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 6.2439726355E-002 | 5.4403185912E-002 | Pass | Pass | 0.1568318146 | 0.3562651720 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 9.4031177583E-002 | 0.1325547280 | Pass | Pass | 0.1459957278 | 0.3505588242 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1826357686 | 0.2450304433 | Pass | Pass | 0.1481796026 | 0.3545320088 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2419064976 | 0.3853761037 | Pass | Pass | 0.1881450107 | 0.4260467335 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1991823376 | 0.3242356761 | Pass | Pass | 0.1469457162 | 0.3501036439 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 5.0968832857E-002 | 4.9369237867E-002 | Pass | Pass | 8.9958346877E-002 | 0.2816714450 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1088980952 | 0.1322626037 | Pass | Pass | 9.0834323599E-002 | 0.2866752511 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2040902462 | 0.2779467837 | Pass | Pass | 0.1294778191 | 0.3800251580 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1214599492 | 0.1729135984 | Pass | Pass | 8.7621365167E-002 | 0.2733760893 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1127026639 | 0.1459640748 | Pass | Pass | 95.4330954884 | 1082.2969033013 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 9.8663906524E-002 | 0.1150347821 | Pass | Pass | 3.4972938533 | 16.1456553025 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1721990741 | 0.1265517752 | Pass | Pass | 0.1651181197 | 0.3670809301 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1372386929 | 0.1328377549 | Pass | Pass | 0.2820860788 | 1.2412945884 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.2001940804E-002 | 2.9686917790E-002 | Pass | Pass | 0.4205445787 | 1.9458490359 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.9087338001E-002 | 2.9288942181E-002 | Pass | Pass | 3.6903311123 | 41.4055138446 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.5630503884E-002 | 6.7993395143E-002 | Pass | Pass | 0.1638548012 | 0.3616663300 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.0387197773E-006 | 7.4838336598E-006 | Pass | Pass | 6.3512441322E-003 | 8.4640489144E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.8936926269E-003 | 2.2287714131E-002 | Pass | Pass | 0.2086572537 | 0.6221960421 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.3852374010E-002 | 3.4157866361E-002 | Pass | Pass | 0.2394129235 | 1.5443578854 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.5011273221E-005 | 2.5391925359E-005 | Pass | Pass | 6.9083030532E-005 | 1.0884721633E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 5204.45 | 17.76 | 0.00 | 17233.16 | 24767.23 | 47222.63 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00 | 0.50 | Wetbulb [C] | 2.10 | 140.00 |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 13.30 | 18.50 | Wetbulb [C] | 4.80 | 310.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 2 | |||
Feb | 34.00 | 28 | |||
Mar | 40.00 | 18 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 81.00 | 18 | |||
Aug | 71.00 | 20 | |||
Sep | 27.00 | 12 | |||
Oct | 9.00 | 6 | |||
Nov | 35.00 | 14 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.193 | 1.452 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 1.158 | 1.400 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.331 | 1.662 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.845 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.845 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.538_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.538_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.538_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.538_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.538_SHGC_NORTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.538_SHGC_EAST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.538_SHGC_EAST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.538_SHGC_EAST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.538_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.538_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.538_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.538_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.538_SHGC_SOUTH_0.25 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.538_SHGC_WEST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.538_SHGC_WEST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.538_SHGC_WEST_0.25 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 3.059 | 0.251 | 0.276 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.538_SHGC_NORTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 3.059 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.538_SHGC_EAST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 3.059 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.538_SHGC_SOUTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 3.059 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.538_SHGC_WEST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 3.059 | 0.251 | 0.276 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.538_SHGC_NORTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 3.059 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.538_SHGC_EAST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 3.059 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.538_SHGC_SOUTH_0.25 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 3.059 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.538_SHGC_WEST_0.25 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 3.059 | 0.251 | 0.276 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 3.059 | 0.251 | 0.276 | |||||||||||||||||
North Total or Average | 1390.74 | 3.059 | 0.251 | 0.276 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 3.059 | 0.251 | 0.276 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.6849 | 2779.43 | 24139.15 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 216.17 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 8.6849 | 2496.12 | 21678.66 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 194.14 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 8.6849 | 24961.20 | 216786.56 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 1941.36 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 8.6849 | 2496.12 | 21678.66 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 194.14 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 8.6849 | 313.41 | 2721.97 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.57 | 0.0000 | Y | 14.09 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.93 | 0.0000 | Y | 8.87 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 8.6849 | 313.42 | 2722.03 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.74 | 0.0000 | Y | 13.66 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.30 | 0.0000 | Y | 8.99 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 8.6849 | 3134.13 | 27219.72 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.45 | 0.0000 | Y | 140.27 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 8.6849 | 2019.75 | 17541.42 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.88 | 0.0000 | Y | 88.52 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 8.6849 | 3134.20 | 27220.31 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.69 | 0.0000 | Y | 136.39 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 8.6849 | 2019.75 | 17541.42 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.22 | 0.0000 | Y | 89.63 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 8.6849 | 313.41 | 2721.97 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.45 | 0.0000 | Y | 14.03 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.88 | 0.0000 | Y | 8.85 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 8.6849 | 313.42 | 2722.03 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 26.69 | 0.0000 | Y | 13.64 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.22 | 0.0000 | Y | 8.96 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 8.6849 | 783.68 | 6806.21 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 62.65 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 13.9016 | 36.20 | 503.28 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.16 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 13.9016 | 362.03 | 5032.75 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 51.55 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 13.9016 | 36.20 | 503.28 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.16 |
Interior Lighting Total | 8.7339 | 46320.38 | 404555.99 | 1013.27 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13271.55 | AstronomicalClock | - | 41.79 | 41.79 | 104.10 | |
EXTERIOR_LIGHTS_B | 989.48 | AstronomicalClock | - | 83.79 | 62.79 | 11.66 | |
EXTERIOR_LIGHTS_C | 26594.85 | AstronomicalClock | - | 83.79 | 47.06 | 234.94 | |
Exterior Lighting Total | 40855.88 | 350.70 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2490213.82 | |||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1262477.72 | 5.91 | 1255187.54 | 5.88 | 8.97 | 30.62 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 1262477.72 | 5.91 | 1255187.54 | 5.88 | 8.97 | 30.62 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 626653.05 | |||||
CENTRAL BOILER | Boiler:HotWater | 610343.60 | 1.00 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1511757.42 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1511757.42 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 204772.35 | 268501.16 | 177475.86 | 91025.30 | 0.66 | - | 60707.17 | 615.73 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1964942.00 | 2553012.32 | 1677963.56 | 875048.75 | 0.66 | - | 576284.58 | 5845.00 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 212301.05 | 280414.06 | 185861.79 | 94552.26 | 0.66 | - | 64182.18 | 650.97 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 115892.20 | 152387.92 | 101844.80 | 50543.12 | 0.67 | - | 32883.23 | 333.52 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 508246.95 | 332730.32 | 175516.63 | 0.65 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9557.29 | 6322.04 | 3235.25 | 0.66 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 91230.29 | 60324.96 | 30905.33 | 0.66 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9333.61 | 6171.18 | 3162.43 | 0.66 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 60184.56 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 592338.47 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 69148.79 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7562.98 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7393.83 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9923.96 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9460.87 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 171899.78 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 115486.37 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 173796.25 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 105902.49 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 21892.79 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14581.00 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 22094.02 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 13787.72 | 1.00 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Electric | 36953.07 | 1.00 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Electric | 300717.11 | 1.00 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Electric | 29125.14 | 1.00 | |
CAV_BAS HEATING COIL | Coil:Heating:Electric | 273349.35 | 1.00 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 508246.95 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9557.29 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 91230.29 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9333.61 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 14683.19 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 678.30 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 6783.03 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 678.30 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 10.69 | 22979.57 | 2149.46 | 1.00 | 1.12 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 100.24 | 216603.97 | 2160.95 | 1.00 | 1.08 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 11.24 | 24159.11 | 2149.46 | 1.00 | 1.12 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 |
CAV_BAS FAN | Fan:VariableVolume | 0.60 | 1314.72 | 6.24 | 13562.47 | 2174.89 | 1.00 | 1.13 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 27.03 | 44388.95 | 1642.33 | 1.00 | 1.14 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.52 | 581.79 | 1120.11 | 1.00 | 1.59 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.95 | 5549.64 | 1120.11 | 1.00 | 1.15 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.51 | 567.66 | 1120.11 | 1.00 | 1.60 | General | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.071440 | 11663.94 | 163269.45 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.035720 | 4037.67 | 113036.94 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.035720 | 4037.67 | 113036.94 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.015144 | 3862.43 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.127144 | 31478.08 | 247577.87 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 78600.67 | 78600.67 | 28.28 | 6.236 | 6.236 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00894 | 30.96 | 0.00562 | 1.200 | 0.00 |
CORE_BOTTOM | 82305.43 | 82305.43 | 32.97 | 6.529 | 6.529 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00888 | 30.96 | 0.00562 | 1.078 | 0.00 |
CORE_MID | 777006.49 | 777006.49 | 311.29 | 61.626 | 61.626 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00890 | 30.96 | 0.00562 | 10.778 | 0.00 |
CORE_TOP | 77505.86 | 77505.86 | 31.05 | 6.147 | 6.147 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00890 | 30.96 | 0.00562 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 15506.09 | 15506.09 | 49.47 | 1.241 | 1.241 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00872 | 40.80 | 0.00563 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 15235.18 | 15235.18 | 75.43 | 1.219 | 1.219 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 24.00 | 24.00 | 0.00864 | 34.99 | 0.00562 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 17368.63 | 17368.63 | 55.42 | 1.390 | 1.390 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00869 | 40.58 | 0.00563 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 19494.42 | 19494.42 | 96.52 | 1.560 | 1.560 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00861 | 39.12 | 0.00563 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 148968.54 | 148968.54 | 475.31 | 11.922 | 11.922 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00868 | 40.67 | 0.00563 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 158686.81 | 158686.81 | 785.67 | 12.699 | 12.699 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 24.00 | 24.00 | 0.00861 | 35.37 | 0.00562 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 166979.11 | 166979.11 | 532.77 | 13.363 | 13.363 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00867 | 40.69 | 0.00563 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 172127.45 | 172127.45 | 852.22 | 13.775 | 13.775 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00860 | 38.94 | 0.00563 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 16871.32 | 16871.32 | 53.83 | 1.350 | 1.350 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 24.00 | 24.00 | 0.00865 | 40.53 | 0.00563 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 16223.87 | 16223.87 | 80.33 | 1.298 | 1.298 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 24.00 | 24.00 | 0.00860 | 35.75 | 0.00562 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 18526.32 | 18526.32 | 59.11 | 1.483 | 1.483 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00864 | 40.80 | 0.00563 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 18512.63 | 18512.63 | 91.66 | 1.482 | 1.482 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00859 | 38.94 | 0.00563 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8228.42 | 8228.42 | 227.29 | 0.519 | 0.519 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00859 | 35.95 | 0.00562 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 78489.24 | 78489.24 | 2168.05 | 4.955 | 4.955 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00859 | 35.95 | 0.00562 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8028.57 | 8028.57 | 221.77 | 0.507 | 0.507 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 36.28 | 0.00562 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 372329.90 | 428179.39 | 546.37 | 23.502 | 27.028 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 28.70 | 0.00561 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | 00:10:00 | 15.60 | 25.18 | 0.00432 | 0.50 | 0.00432 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | 00:10:00 | 15.60 | 22.66 | 0.00432 | 0.50 | 0.00432 | 1.078 | 0.00 | |
CORE_MID | 199376.41 | 199376.41 | 79.87 | 9.243 | 10.778 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 0.50 | 0.00432 | 10.778 | 0.00 |
CORE_TOP | 48775.86 | 48775.86 | 19.54 | 2.281 | 2.281 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 0.50 | 0.00432 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 5051.11 | 5051.11 | 16.12 | 0.236 | 0.236 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00772 | 0.50 | 0.00432 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 3770.89 | 3770.89 | 18.67 | 0.176 | 0.176 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | 0.50 | 0.00432 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 6993.20 | 6993.20 | 22.31 | 0.327 | 0.327 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00784 | 0.50 | 0.00432 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 2277.09 | 2277.09 | 11.27 | 0.106 | 0.106 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00753 | 0.50 | 0.00432 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 120833.70 | 120833.70 | 385.54 | 5.669 | 5.669 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00789 | 0.50 | 0.00432 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 81167.05 | 81167.05 | 401.87 | 3.809 | 3.809 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00790 | 0.50 | 0.00432 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 122161.84 | 122161.84 | 389.77 | 5.732 | 5.732 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00790 | 0.50 | 0.00432 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 74453.84 | 74453.84 | 368.63 | 3.493 | 3.493 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00788 | 0.50 | 0.00432 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 15377.72 | 15377.72 | 49.07 | 0.722 | 0.722 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00791 | 0.50 | 0.00432 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 10240.91 | 10240.91 | 50.70 | 0.481 | 0.481 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00791 | 0.50 | 0.00432 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 15518.65 | 15518.65 | 49.51 | 0.729 | 0.729 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00791 | 0.50 | 0.00432 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 9685.18 | 9685.18 | 47.95 | 0.455 | 0.455 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00790 | 0.50 | 0.00432 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 0.50 | 0.00432 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | 00:10:00 | 18.00 | 24.60 | 0.00650 | 0.50 | 0.00432 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | 00:10:00 | 18.00 | 23.60 | 0.00459 | 0.50 | 0.00432 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | 00:10:00 | 18.00 | 27.00 | 0.00850 | 0.50 | 0.00432 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 10.69 | 10.69 | 1.92 | 1.92 | 10.6908 | 3.0682 | 10.6908 | 0.2870 | 0.3000 |
VAV_MID WITH REHEAT | 100.24 | 100.24 | 29.48 | 29.48 | 100.2357 | 29.9589 | 100.2357 | 0.2989 | 0.3000 |
VAV_TOP WITH REHEAT | 11.24 | 11.24 | 4.67 | 4.67 | 11.2396 | 4.6669 | 11.2396 | 0.4152 | 0.3000 |
CAV_BAS | 6.24 | 6.24 | 1.20 | 1.20 | 6.2359 | 1.2002 | 6.2359 | 0.1925 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 27.03 | 27.03 | 0.34 | 0.34 | 27.0280 | 27.0277 | 27.0280 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.52 | 0.52 | 0.02 | 0.02 | 0.5194 | 0.5194 | 0.5194 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.95 | 4.95 | 0.16 | 0.16 | 4.9546 | 4.9546 | 4.9546 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.51 | 0.51 | 0.02 | 0.02 | 0.5068 | 0.5068 | 0.5068 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 60184.565 | 60184.565 | -999.0 | -999.0 | -999.000 | 12/21 00:10:00 | 12/21 00:10:00 | 60184.56 | 32680.73 | 1.077825 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00800000 | 46.9512 | 0.00 | 0.00 | -999.00 | -999.00 | ||
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 592338.469 | 592338.469 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 592338.47 | 326807.31 | 10.778248 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00800000 | 46.9512 | 199376.41 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 69148.792 | 69148.792 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 69148.79 | 69148.79 | 2.280557 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00800000 | 46.9512 | 48775.86 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 7562.979 | 7562.979 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7562.98 | 7150.02 | 0.235811 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00772283 | 45.3460 | 5051.11 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 7393.834 | 7393.834 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7393.83 | 5343.99 | 0.176247 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00777337 | 45.6390 | 3770.89 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 9923.958 | 9923.958 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9923.96 | 9923.96 | 0.327296 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00784046 | 46.0277 | 6993.20 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 9460.872 | 9460.872 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9460.87 | 3211.06 | 0.105902 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00752637 | 44.2064 | 2277.09 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 171899.776 | 171899.776 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 171899.78 | 171899.78 | 5.669330 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00789373 | 46.3365 | 120833.70 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 115486.366 | 115486.366 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 115486.37 | 115486.37 | 3.808791 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00789822 | 46.3625 | 81167.05 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 173796.249 | 173796.249 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 173796.25 | 173796.25 | 5.731876 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00789592 | 46.3492 | 122161.84 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 105902.489 | 105902.489 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 105902.49 | 105902.49 | 3.492710 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00787889 | 46.2506 | 74453.84 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 21892.786 | 21892.786 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21892.79 | 21892.79 | 0.722034 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00790981 | 46.4297 | 15377.72 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 14581.000 | 14581.000 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 14581.00 | 14581.00 | 0.480888 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00791025 | 46.4322 | 10240.91 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 22094.017 | 22094.017 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 22094.02 | 22094.02 | 0.728670 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00791077 | 46.4352 | 15518.65 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 13787.722 | 13787.722 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 13787.72 | 13787.72 | 0.454725 | 12.80 | 10.74 | 0.00800000 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 0.0000 | 21.00 | 0.00790373 | 46.3945 | 9685.18 | 0.00 | -999.00 | -999.00 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 204772.350 | -999.000 | 10.690834 | 0.00585646 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 204772.35 | 204772.35 | 10.690834 | 28.05 | 16.40 | 0.00804696 | 10.87 | 9.99 | 0.00804696 | 40.80 | 0.00563111 | 18.58 | 23.7417 | 24.00 | 0.00881531 | 43.0619 | 131435.09 | 0.00 | 221077.03 | 212148.05 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | VAV_BOT WITH REHEAT | 36953.069 | 36953.069 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 36953.07 | 36953.07 | 3.207250 | 2.31 | 1.93 | 0.00463088 | 12.80 | 10.74 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 79.1391 | 21.67 | 0.00630791 | 35.6274 | 18092.29 | 0.00 | -999.00 | -999.00 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1964942.002 | -999.000 | 100.235680 | 0.05619709 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 1964942.00 | 1964941.97 | 100.235680 | 28.45 | 16.48 | 0.00798235 | 10.86 | 9.92 | 0.00798235 | 40.80 | 0.00563111 | 18.58 | 25.3223 | 24.00 | 0.00882910 | 43.1282 | 1197825.08 | 0.00 | 2119363.71 | 2041964.39 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | VAV_MID WITH REHEAT | 300717.114 | 300717.114 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 300717.11 | 300717.11 | 30.070704 | 3.70 | 2.99 | 0.00487989 | 12.80 | 10.74 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 84.4076 | 21.00 | 0.00792268 | 46.5038 | 454060.93 | 0.00 | -999.00 | -999.00 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 212301.051 | -999.000 | 11.239594 | 0.00607178 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 212301.05 | 212301.05 | 11.239594 | 27.81 | 16.33 | 0.00806237 | 10.87 | 10.01 | 0.00806237 | 40.80 | 0.00563111 | 18.58 | 22.5826 | 24.00 | 0.00877676 | 42.8759 | 139652.56 | 0.00 | 229342.57 | 219812.63 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | VAV_TOP WITH REHEAT | 29125.142 | 29125.142 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 29125.14 | 29125.14 | 3.371878 | 4.94 | 4.04 | 0.00519892 | 12.80 | 10.74 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 75.2753 | 19.67 | 0.00787347 | 50.1810 | 54215.41 | 0.00 | -999.00 | -999.00 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 115892.200 | -999.000 | 6.235939 | 0.00331450 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 115892.20 | 115892.20 | 6.235939 | 27.51 | 16.39 | 0.00825936 | 10.85 | 10.20 | 0.00825936 | 40.13 | 0.00563007 | 18.37 | 19.2458 | 24.00 | 0.00899161 | 43.9114 | 68841.72 | 0.00 | 125160.29 | 118372.58 |
CAV_BAS HEATING COIL | Coil:Heating:Electric | AirLoopHVAC | CAV_BAS | 273349.348 | 273349.348 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 273349.35 | 273349.35 | 6.235939 | 0.10 | 0.10 | 0.00431558 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 19.2458 | 25.18 | 0.00431558 | 19.7820 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 508246.950 | 332730.316 | 27.028002 | 0.01244693 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 462117.93 | 461761.87 | -999.0 | 28.70 | 16.98 | 0.00850572 | 12.80 | 11.23 | 0.00850000 | 40.80 | 0.00563111 | 18.58 | -999.0000 | 27.00 | 0.00854221 | 34.9361 | 371847.39 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9557.290 | 6322.036 | 0.519407 | 0.00023406 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 8658.62 | 8658.62 | -999.0 | 28.32 | 16.85 | 0.00849876 | 12.80 | 11.23 | 0.00849876 | 36.28 | 0.00562409 | 17.15 | -999.0000 | 27.00 | 0.00858799 | 35.1186 | 8225.25 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 91230.287 | 60324.960 | 4.954558 | 0.00223422 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 82661.76 | 82661.76 | -999.0 | 28.33 | 16.86 | 0.00849852 | 12.80 | 11.23 | 0.00849852 | 36.28 | 0.00562409 | 17.15 | -999.0000 | 27.00 | 0.00859223 | 35.1359 | 78438.34 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9333.608 | 6171.177 | 0.506793 | 0.00022858 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 8457.30 | 8457.30 | -999.0 | 28.34 | 16.86 | 0.00849865 | 12.80 | 11.23 | 0.00849865 | 36.61 | 0.00562460 | 17.26 | -999.0000 | 27.00 | 0.00859019 | 35.1275 | 8022.85 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 508246.950 | 508246.950 | 27.028002 | 0.01244693 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 508246.95 | 508246.95 | 27.028002 | 0.50 | 0.50 | 0.00431558 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 1.2520 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9557.290 | 9557.290 | 0.519407 | 0.00023406 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9557.29 | 9557.29 | 0.519407 | 0.50 | 0.50 | 0.00431558 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 3.0097 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 91230.287 | 91230.287 | 4.954558 | 0.00223422 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 91230.29 | 91230.29 | 4.954558 | 0.50 | 0.50 | 0.00431558 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 3.1551 | 24.60 | 0.00649584 | 30.7212 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9333.608 | 9333.608 | 0.506793 | 0.00022858 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9333.61 | 9333.61 | 0.506793 | 0.50 | 0.50 | 0.00431558 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 3.0846 | 23.60 | 0.00458892 | 23.1212 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 14683.191 | 14683.191 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 14683.19 | 14683.19 | 27.028002 | 0.01 | 0.01 | 0.00844761 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 1.2520 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 678.303 | 678.303 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 678.30 | 678.30 | 0.519407 | 0.02 | 0.02 | 0.00837406 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 3.0097 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 6783.026 | 6783.026 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 6783.03 | 6783.03 | 4.954558 | 0.02 | 0.02 | 0.00642705 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 3.1551 | 24.60 | 0.00649584 | 30.7212 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 678.303 | 678.303 | -999.0 | -999.0 | -999.000 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 678.30 | 678.30 | 0.506793 | 0.02 | 0.02 | 0.00458049 | 40.00 | 20.06 | 0.00800000 | 0.50 | 0.00431558 | 0.50 | 3.0846 | 23.60 | 0.00458892 | 23.1212 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 60184.565 | 60184.565 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | 12/21 00:10:00 | unknown | unknown | 12/21 00:10:00 | Sensible | 60184.56 | 32680.73 | 1.0000 | 1.17827185 | 1.077825 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 60184.56 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 46.9512 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |||
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 592338.469 | 592338.469 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 592338.47 | 326807.31 | 1.0000 | 11.78271854 | 10.778248 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 592338.47 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.90 | 0.00800000 | 21.00 | 0.00800000 | 46.9512 | 199376.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 69148.792 | 69148.792 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 69148.79 | 69148.79 | 1.0000 | 2.49309215 | 2.280557 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 69148.79 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 46.9512 | 48775.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 7562.979 | 7562.979 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7562.98 | 7150.02 | 1.0000 | 0.25778708 | 0.235811 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7562.98 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.86 | 0.00772283 | 21.00 | 0.00772283 | 45.3460 | 5051.11 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 7393.834 | 7393.834 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 7393.83 | 5343.99 | 1.0000 | 0.19267217 | 0.176247 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7393.83 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.92 | 0.00777337 | 21.00 | 0.00777337 | 45.6390 | 3770.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 9923.958 | 9923.958 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9923.96 | 9923.96 | 1.0000 | 0.35779860 | 0.327296 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9923.96 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.91 | 0.00784046 | 21.00 | 0.00784046 | 46.0277 | 6993.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 9460.872 | 9460.872 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 9460.87 | 3211.06 | 1.0000 | 0.11577168 | 0.105902 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9460.87 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.87 | 0.00752637 | 21.00 | 0.00752637 | 44.2064 | 2277.09 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 171899.776 | 171899.776 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 171899.78 | 171899.78 | 1.0000 | 6.19767853 | 5.669330 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 171899.78 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00789373 | 21.00 | 0.00789373 | 46.3365 | 120833.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 115486.366 | 115486.366 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 115486.37 | 115486.37 | 1.0000 | 4.16374816 | 3.808791 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 115486.37 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00789822 | 21.00 | 0.00789822 | 46.3625 | 81167.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 173796.249 | 173796.249 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 173796.25 | 173796.25 | 1.0000 | 6.26605404 | 5.731876 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 173796.25 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00789592 | 21.00 | 0.00789592 | 46.3492 | 122161.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 105902.489 | 105902.489 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 105902.49 | 105902.49 | 1.0000 | 3.81821082 | 3.492710 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 105902.49 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00787889 | 21.00 | 0.00787889 | 46.2506 | 74453.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 21892.786 | 21892.786 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 21892.79 | 21892.79 | 1.0000 | 0.78932302 | 0.722034 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21892.79 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00790981 | 21.00 | 0.00790981 | 46.4297 | 15377.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 14581.000 | 14581.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 14581.00 | 14581.00 | 1.0000 | 0.52570372 | 0.480888 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14581.00 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00791025 | 21.00 | 0.00791025 | 46.4322 | 10240.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 22094.017 | 22094.017 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 22094.02 | 22094.02 | 1.0000 | 0.79657822 | 0.728670 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22094.02 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00791077 | 21.00 | 0.00791077 | 46.4352 | 15518.65 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 13787.722 | 13787.722 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 13787.72 | 13787.72 | 1.0000 | 0.49710284 | 0.454725 | 12.80 | 10.74 | 0.00800000 | 33059.8 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13787.72 | 0.50 | 0.00431558 | 0.50 | 0.00000000 | 0.0000 | 20.95 | 0.00790373 | 21.00 | 0.00790373 | 46.3945 | 9685.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 204772.350 | -999.000 | 10.690834 | 0.00585646 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7989 | 1004.8586 | 1.0932 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.690834 | 11.68715826 | 4197.9300 | 999.8980 | 71.43255363 | 15.00 | 6.67 | 8.33 | 2497907.60 | 8.1978 | 8.197755 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 204772.35 | 204772.35 | 1.0000 | 11.68715826 | 10.690834 | 28.05 | 16.40 | 0.00804696 | 48733.3 | 10.87 | 9.99 | 0.00804696 | 31212.2 | 5.85586588 | 6.67 | 15.00 | 8.33 | 22979.570 | 181792.78 | 40.80 | 0.00563111 | 18.58 | 2.53819000 | 23.7417 | 24.00 | 0.00881531 | 24.00 | 0.00881531 | 43.0619 | 131435.09 | 0.00 | 221077.03 | 212148.05 | 11.68715826 | 28.05 | 17.42 | 0.00804696 | 48733.3 | 10.25 | 10.23 | 0.00774379 | 29817.1 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 36953.069 | 36953.069 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.690834 | 11.68715826 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 36953.07 | 36953.07 | 1.0000 | 3.50614748 | 3.207250 | 2.31 | 1.93 | 0.00463088 | 13924.1 | 12.80 | 10.74 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36953.07 | 0.50 | 0.00431558 | 0.50 | 2.53819000 | 79.1391 | 9.18 | 0.00582701 | 21.67 | 0.00630791 | 35.6274 | 18092.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1964942.002 | -999.000 | 100.235680 | 0.05619709 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.6788 | 1004.8586 | 1.0932 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 100.235680 | 109.57706552 | 4197.9300 | 999.8980 | 71.43255363 | 15.00 | 6.67 | 8.33 | 2497907.60 | 78.6635 | 78.663518 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 1964942.00 | 1964941.97 | 1.0000 | 109.57706552 | 100.235680 | 28.45 | 16.48 | 0.00798235 | 48970.6 | 10.86 | 9.92 | 0.00798235 | 31038.6 | 56.19135982 | 6.67 | 15.00 | 8.33 | 216603.966 | 1748338.04 | 40.80 | 0.00563111 | 18.58 | 25.38195000 | 25.3223 | 24.00 | 0.00882910 | 24.00 | 0.00882910 | 43.1282 | 1197825.08 | 0.00 | 2119363.71 | 2041964.39 | 109.57706552 | 28.45 | 17.50 | 0.00798235 | 48970.6 | 10.17 | 10.15 | 0.00770204 | 29629.3 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 300717.114 | 300717.114 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 100.235680 | 109.57706552 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:40:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 300717.11 | 300717.11 | 1.0000 | 32.87311966 | 30.070704 | 3.70 | 2.99 | 0.00487989 | 15952.2 | 12.80 | 10.74 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 300717.11 | 0.50 | 0.00431558 | 0.50 | 25.38195000 | 84.4076 | 21.00 | 0.00793471 | 21.00 | 0.00792268 | 46.5038 | 454060.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 212301.051 | -999.000 | 11.239594 | 0.00607178 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.8275 | 1004.8586 | 1.0932 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.239594 | 12.28705912 | 4197.9300 | 999.8980 | 71.43255363 | 15.00 | 6.67 | 8.33 | 2497907.60 | 8.4992 | 8.499155 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | Sensible | 212301.05 | 212301.05 | 1.0000 | 12.28705912 | 11.239594 | 27.81 | 16.33 | 0.00806237 | 48529.5 | 10.87 | 10.01 | 0.00806237 | 31251.1 | 6.07116379 | 6.67 | 15.00 | 8.33 | 24159.109 | 188141.94 | 40.80 | 0.00563111 | 18.58 | 2.53819000 | 22.5826 | 24.00 | 0.00877676 | 24.00 | 0.00877676 | 42.8759 | 139652.56 | 0.00 | 229342.57 | 219812.63 | 12.28705912 | 27.81 | 17.35 | 0.00806237 | 48529.5 | 10.27 | 10.25 | 0.00775460 | 29864.1 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29125.142 | 29125.142 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.239594 | 12.28705912 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 29125.14 | 29125.14 | 1.0000 | 3.68611774 | 3.371878 | 4.94 | 4.04 | 0.00519892 | 18010.7 | 12.80 | 10.74 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29125.14 | 0.50 | 0.00431558 | 0.50 | 2.53819000 | 75.2753 | 18.45 | 0.00788827 | 19.67 | 0.00787347 | 50.1810 | 54215.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 115892.200 | -999.000 | 6.235939 | 0.00331450 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1937 | 1004.8586 | 1.0932 | CAV_BAS FAN | Fan:VariableVolume | 6.235939 | 6.81709197 | 4197.9300 | 999.8980 | 71.43255363 | 15.00 | 6.67 | 8.33 | 2497907.60 | 4.6396 | 4.639571 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 115892.20 | 115892.20 | 1.0000 | 6.81709197 | 6.235939 | 27.51 | 16.39 | 0.00825936 | 48725.4 | 10.85 | 10.20 | 0.00825936 | 31725.2 | 3.31416414 | 6.67 | 15.00 | 8.33 | 13562.470 | 102329.73 | 40.13 | 0.00563007 | 18.37 | 1.20015641 | 19.2458 | 24.00 | 0.00899161 | 24.00 | 0.00899161 | 43.9114 | 68841.72 | 0.00 | 125160.29 | 118372.58 | 6.81709197 | 27.51 | 17.41 | 0.00825936 | 48725.4 | 10.49 | 10.47 | 0.00786431 | 30365.6 | |
CAV_BAS HEATING COIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 273349.348 | 273349.348 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | CAV_BAS FAN | Fan:VariableVolume | 6.235939 | 6.81709197 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 273349.35 | 273349.35 | 1.0000 | 6.81709197 | 6.235939 | 0.10 | 0.10 | 0.00431558 | 10890.5 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 273349.35 | 0.50 | 0.00431558 | 0.50 | 1.20015641 | 19.2458 | 0.00 | 0.00431558 | 25.18 | 0.00431558 | 19.7820 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 508246.950 | 332730.316 | 27.028002 | 0.01244693 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6517 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 462117.93 | 461761.87 | 0.9092 | -999.0 | -999.0 | 28.70 | 16.98 | 0.00850572 | 50563.8 | 12.80 | 11.23 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 462117.93 | 40.80 | 0.00563111 | 18.58 | 0.33839277 | -999.0000 | 27.00 | 0.00854221 | 27.00 | 0.00854221 | 34.9361 | 371847.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9557.290 | 6322.036 | 0.519407 | 0.00023406 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6388 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 8658.62 | 8658.62 | 0.9060 | -999.0 | -999.0 | 28.32 | 16.85 | 0.00849876 | 50160.0 | 12.80 | 11.23 | 0.00849876 | 34319.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8658.62 | 36.28 | 0.00562409 | 17.15 | 0.01563234 | -999.0000 | 27.00 | 0.00858799 | 27.00 | 0.00858799 | 35.1186 | 8225.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 91230.287 | 60324.960 | 4.954558 | 0.00223422 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6383 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 82661.76 | 82661.76 | 0.9061 | -999.0 | -999.0 | 28.33 | 16.86 | 0.00849852 | 50173.2 | 12.80 | 11.23 | 0.00849852 | 34318.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 82661.76 | 36.28 | 0.00562409 | 17.15 | 0.15632344 | -999.0000 | 27.00 | 0.00859223 | 27.00 | 0.00859223 | 35.1359 | 78438.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9333.608 | 6171.177 | 0.506793 | 0.00022858 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6386 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 8457.30 | 8457.30 | 0.9061 | -999.0 | -999.0 | 28.34 | 16.86 | 0.00849865 | 50177.4 | 12.80 | 11.23 | 0.00849865 | 34318.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8457.30 | 36.61 | 0.00562460 | 17.26 | 0.01563234 | -999.0000 | 27.00 | 0.00859019 | 27.00 | 0.00859019 | 35.1275 | 8022.85 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 508246.950 | 508246.950 | 27.028002 | 0.01244693 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 508246.95 | 508246.95 | 1.0000 | 29.54685580 | 27.028002 | 0.50 | 0.50 | 0.00431558 | 11299.5 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 508246.95 | 0.50 | 0.00431558 | 0.50 | 0.33839277 | 1.2520 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9557.290 | 9557.290 | 0.519407 | 0.00023406 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9557.29 | 9557.29 | 1.0000 | 0.56781293 | 0.519407 | 0.50 | 0.50 | 0.00431558 | 11299.5 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9557.29 | 0.50 | 0.00431558 | 0.50 | 0.01563234 | 3.0097 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 91230.287 | 91230.287 | 4.954558 | 0.00223422 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 91230.29 | 91230.29 | 1.0000 | 5.41629377 | 4.954558 | 0.50 | 0.50 | 0.00431558 | 11299.5 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 91230.29 | 0.50 | 0.00431558 | 0.50 | 0.15632344 | 3.1551 | 0.00 | 0.00649584 | 24.60 | 0.00649584 | 30.7212 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9333.608 | 9333.608 | 0.506793 | 0.00022858 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.0932 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 9333.61 | 9333.61 | 1.0000 | 0.55402358 | 0.506793 | 0.50 | 0.50 | 0.00431558 | 11299.5 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9333.61 | 0.50 | 0.00431558 | 0.50 | 0.01563234 | 3.0846 | 0.00 | 0.00458892 | 23.60 | 0.00458892 | 23.1212 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14683.191 | 14683.191 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 27.028002 | 29.54685580 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 14683.19 | 14683.19 | 1.0000 | 29.54685580 | 27.028002 | 0.01 | 0.01 | 0.00844761 | 21133.4 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14683.19 | 0.50 | 0.00431558 | 0.50 | 0.33839277 | 1.2520 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 678.303 | 678.303 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.519407 | 0.56781293 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 678.30 | 678.30 | 1.0000 | 0.56781293 | 0.519407 | 0.02 | 0.02 | 0.00837406 | 20958.4 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 678.30 | 0.50 | 0.00431558 | 0.50 | 0.01563234 | 3.0097 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 34.7602 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6783.026 | 6783.026 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.954558 | 5.41629377 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 6783.03 | 6783.03 | 1.0000 | 5.41629377 | 4.954558 | 0.02 | 0.02 | 0.00642705 | 16089.7 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6783.03 | 0.50 | 0.00431558 | 0.50 | 0.15632344 | 3.1551 | 0.00 | 0.00649584 | 24.60 | 0.00649584 | 30.7212 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 678.303 | 678.303 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0932 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.506793 | 0.55402358 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 678.30 | 678.30 | 1.0000 | 0.55402358 | 0.506793 | 0.02 | 0.02 | 0.00458049 | 11471.2 | 40.00 | 20.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 678.30 | 0.50 | 0.00431558 | 0.50 | 0.01563234 | 3.0846 | 0.00 | 0.00458892 | 23.60 | 0.00458892 | 23.1212 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 10.69 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 100.24 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 11.24 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 6.24 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 27.03 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 3849.67 | 2703.33 | 2422.00 |
CORE_BOTTOM | 2723.00 | 500.50 | 64.17 |
CORE_MID | 1655.00 | 2015.50 | 125.00 |
CORE_TOP | 1698.00 | 2689.00 | 241.50 |
PERIMETER_BOT_ZN_3 | 2372.33 | 2302.17 | 178.67 |
PERIMETER_BOT_ZN_2 | 2962.83 | 1899.17 | 269.33 |
PERIMETER_BOT_ZN_1 | 3347.50 | 1371.33 | 270.67 |
PERIMETER_BOT_ZN_4 | 3682.83 | 1105.50 | 355.33 |
PERIMETER_MID_ZN_3 | 2117.17 | 3021.50 | 379.67 |
PERIMETER_MID_ZN_2 | 2244.83 | 2215.83 | 361.17 |
PERIMETER_MID_ZN_1 | 2960.50 | 1759.33 | 292.00 |
PERIMETER_MID_ZN_4 | 2666.83 | 2487.00 | 314.67 |
PERIMETER_TOP_ZN_3 | 2630.67 | 3199.50 | 871.67 |
PERIMETER_TOP_ZN_2 | 2964.33 | 2675.00 | 628.33 |
PERIMETER_TOP_ZN_1 | 3074.00 | 2077.33 | 486.33 |
PERIMETER_TOP_ZN_4 | 2919.67 | 2723.50 | 627.50 |
DATACENTER_BOT_ZN_6 | 5943.00 | 1498.67 | 1498.67 |
DATACENTER_MID_ZN_6 | 5937.50 | 461.67 | 461.67 |
DATACENTER_TOP_ZN_6 | 5777.83 | 617.33 | 606.17 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5812.17 | 5812.17 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5933.17 | 5859.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 4420.17 | 0.00 | 2835.17 |
CORE_BOTTOM | 0.00 | 46.17 | 0.00 | 1.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 109.17 | 0.00 | 43.17 |
PERIMETER_BOT_ZN_2 | 0.00 | 118.33 | 0.00 | 74.17 |
PERIMETER_BOT_ZN_1 | 0.00 | 167.50 | 0.00 | 110.17 |
PERIMETER_BOT_ZN_4 | 0.00 | 201.00 | 0.00 | 78.33 |
PERIMETER_MID_ZN_3 | 0.33 | 23.17 | 0.00 | 14.17 |
PERIMETER_MID_ZN_2 | 0.33 | 70.17 | 0.00 | 64.67 |
PERIMETER_MID_ZN_1 | 0.00 | 130.33 | 0.00 | 119.67 |
PERIMETER_MID_ZN_4 | 0.00 | 75.00 | 0.00 | 34.67 |
PERIMETER_TOP_ZN_3 | 4.50 | 46.00 | 0.00 | 26.00 |
PERIMETER_TOP_ZN_2 | 3.50 | 84.50 | 0.00 | 67.67 |
PERIMETER_TOP_ZN_1 | 2.00 | 89.50 | 0.00 | 68.17 |
PERIMETER_TOP_ZN_4 | 1.83 | 85.33 | 0.00 | 38.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 527.00 | 0.00 | 440.17 |
DATACENTER_MID_ZN_6 | 0.00 | 467.00 | 0.00 | 392.17 |
DATACENTER_TOP_ZN_6 | 0.00 | 387.50 | 0.00 | 321.33 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 218.83 | 0.00 | 181.67 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 4.83 | 4757.33 | 0.00 | 3124.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 0.915 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 1.018 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.731 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.658 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.901 | 0.016 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 1.399 | 0.016 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 1.522 | 0.016 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 1.776 | 0.016 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.746 | 0.037 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 1.241 | 0.041 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 1.399 | 0.037 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 1.330 | 0.038 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.744 | 0.045 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 1.249 | 0.047 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 1.346 | 0.046 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 1.312 | 0.047 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 27.461 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.79 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.79 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.79 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.20 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 60.99 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 54.77 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.86 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.88 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.43 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.79 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.79 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.20 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1010.73 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 36167914.29 | 0.00 | 36167914.29 | 0.00 | 36167914.29 | 37848132.68 | 6247.33 | 646.75 | 1865.92 | 0.00 |
CORE_BOTTOM | 45210458.15 | 0.00 | 45210458.15 | 0.00 | 45210458.15 | 33990283.35 | 5492.53 | 6.71 | 3260.75 | 580.12 |
CORE_MID | 0.30E+09 | 0.00 | 0.30E+09 | 0.00 | 0.30E+09 | 0.34E+09 | 6164.92 | 18.65 | 2576.44 | 125.27 |
CORE_TOP | 27177851.27 | 0.00 | 27177851.27 | 0.00 | 27177851.27 | 33990283.35 | 6359.84 | 19.45 | 2380.71 | 143.26 |
PERIMETER_BOT_ZN_3 | 5055248.78 | 0.00 | 5055248.78 | 156598.03 | 5211846.81 | 4267819.30 | 3634.06 | 52.84 | 5073.11 | 580.12 |
PERIMETER_BOT_ZN_2 | 5015125.25 | 0.00 | 5015125.25 | 104398.62 | 5119523.87 | 2750345.05 | 3372.86 | 9.92 | 5377.22 | 580.12 |
PERIMETER_BOT_ZN_1 | 8222183.77 | 0.00 | 8222183.77 | 156598.03 | 8378781.80 | 4267912.63 | 3412.48 | 40.43 | 5307.09 | 580.12 |
PERIMETER_BOT_ZN_4 | 6398009.84 | 0.00 | 6398009.84 | 104398.62 | 6502408.46 | 2750345.05 | 3308.36 | 1.50 | 5450.14 | 580.12 |
PERIMETER_MID_ZN_3 | 38512154.17 | 0.00 | 38512154.17 | 367259.46 | 38879413.63 | 42678193.03 | 4333.16 | 38.38 | 4388.45 | 125.27 |
PERIMETER_MID_ZN_2 | 43618478.45 | 0.00 | 43618478.45 | 244839.47 | 43863317.93 | 27503450.52 | 3897.34 | 3.67 | 4859.00 | 1034.27 |
PERIMETER_MID_ZN_1 | 71367642.09 | 0.00 | 71367642.09 | 367259.46 | 71734901.55 | 42679126.28 | 3963.15 | 17.34 | 4779.51 | 125.27 |
PERIMETER_MID_ZN_4 | 44281148.10 | 0.00 | 44281148.10 | 244839.47 | 44525987.57 | 27503450.52 | 3907.33 | 6.50 | 4846.17 | 125.27 |
PERIMETER_TOP_ZN_3 | 3854773.40 | 0.00 | 3854773.40 | 455983.33 | 4310756.73 | 4267819.30 | 4298.25 | 32.02 | 4429.73 | 143.26 |
PERIMETER_TOP_ZN_2 | 4148959.52 | 0.00 | 4148959.52 | 303988.68 | 4452948.20 | 2750345.05 | 3949.12 | 3.65 | 4807.23 | 143.26 |
PERIMETER_TOP_ZN_1 | 6882799.21 | 0.00 | 6882799.21 | 455983.33 | 7338782.54 | 4267912.63 | 4050.59 | 15.02 | 4694.39 | 143.26 |
PERIMETER_TOP_ZN_4 | 4377690.46 | 0.00 | 4377690.46 | 303988.68 | 4681679.14 | 2750345.05 | 3958.44 | 8.70 | 4792.86 | 143.26 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.48E+09 | 0.00 | 0.48E+09 | 0.00 | 0.48E+09 | 10671554.30 | 819.89 | 1786.50 | 6153.61 | 2408.35 |
Total Facility | 0.56E+10 | 0.00 | 0.56E+10 | 14283916.04 | 0.57E+10 | 0.50E+10 | 6976.32 | 4380.08 | 7940.41 | 3317.52 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.6905 | 0.0000 | 1.6905 | 0.0000 | 1.6905 | 1.2002 | 3430.33 | 646.75 | 1865.92 |
CORE_BOTTOM | 1.8981 | 0.0000 | 1.8981 | 0.0000 | 1.8981 | 1.0778 | 3241.67 | 3.72 | 2697.61 |
CORE_MID | 13.6195 | 0.0000 | 13.6195 | 0.0000 | 13.6195 | 10.7782 | 3467.31 | 18.48 | 2457.21 |
CORE_TOP | 1.2280 | 0.0000 | 1.2280 | 0.0000 | 1.2280 | 1.0778 | 3646.48 | 19.45 | 2277.07 |
PERIMETER_BOT_ZN_3 | 0.2108 | 0.0000 | 0.2108 | 0.0037 | 0.2144 | 0.1353 | 1380.86 | 48.81 | 4513.32 |
PERIMETER_BOT_ZN_2 | 0.2111 | 0.0000 | 0.2111 | 0.0024 | 0.2136 | 0.0872 | 1135.98 | 9.83 | 4797.19 |
PERIMETER_BOT_ZN_1 | 0.3567 | 0.0000 | 0.3567 | 0.0037 | 0.3603 | 0.1353 | 1167.18 | 38.89 | 4736.93 |
PERIMETER_BOT_ZN_4 | 0.2679 | 0.0000 | 0.2679 | 0.0024 | 0.2704 | 0.0872 | 1071.48 | 1.50 | 4870.02 |
PERIMETER_MID_ZN_3 | 1.7476 | 0.0000 | 1.7476 | 0.0086 | 1.7562 | 1.3533 | 1636.00 | 38.13 | 4268.87 |
PERIMETER_MID_ZN_2 | 1.8749 | 0.0000 | 1.8749 | 0.0061 | 1.8811 | 0.8721 | 1203.32 | 2.17 | 3828.51 |
PERIMETER_MID_ZN_1 | 3.2780 | 0.0000 | 3.2780 | 0.0086 | 3.2866 | 1.3533 | 1265.96 | 17.34 | 4659.70 |
PERIMETER_MID_ZN_4 | 2.0100 | 0.0000 | 2.0100 | 0.0057 | 2.0157 | 0.8721 | 1215.60 | 6.50 | 4720.90 |
PERIMETER_TOP_ZN_3 | 0.1745 | 0.0000 | 0.1745 | 0.0107 | 0.1852 | 0.1353 | 1587.34 | 31.73 | 4323.93 |
PERIMETER_TOP_ZN_2 | 0.1886 | 0.0000 | 0.1886 | 0.0071 | 0.1958 | 0.0872 | 1258.28 | 2.36 | 4682.36 |
PERIMETER_TOP_ZN_1 | 0.3155 | 0.0000 | 0.3155 | 0.0107 | 0.3262 | 0.1353 | 1340.30 | 14.36 | 4588.34 |
PERIMETER_TOP_ZN_4 | 0.1984 | 0.0000 | 0.1984 | 0.0071 | 0.2055 | 0.0872 | 1270.73 | 8.33 | 4663.93 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 14.1315 | 0.0000 | 14.1315 | 0.0000 | 14.1315 | 0.3384 | 411.24 | 1786.50 | 3745.26 |
Total Facility | 247.3375 | 0.0000 | 247.3375 | 0.3380 | 247.6756 | 158.4706 | 4159.32 | 4371.91 | 5531.89 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 83536879.43 | 0.00 | 83536879.43 | 48026705.38 | 3307.92 | 0.74 | 5451.34 | 580.12 |
VAV_MID WITH REHEAT | 0.60E+09 | 0.00 | 0.60E+09 | 0.48E+09 | 3909.31 | 1.77 | 4848.92 | 125.27 |
VAV_TOP WITH REHEAT | 55501696.75 | 0.00 | 55501696.75 | 48026705.38 | 3987.05 | 4.40 | 4768.55 | 143.26 |
CAV_BAS | 43223330.88 | 0.00 | 43223330.88 | 37848132.68 | 6246.97 | 0.17 | 2512.86 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.57E+09 | 0.00 | 0.57E+09 | 10671554.30 | 819.89 | 0.00 | 7940.11 | 2408.35 |
AIRLOOP DATACENTER BOT | 291951.72 | 0.00 | 291951.72 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 2919517.21 | 0.00 | 2919517.21 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 291951.72 | 0.00 | 291951.72 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.5191 | 0.0000 | 3.5191 | 1.5229 | 1069.56 | 0.32 | 4873.12 |
VAV_MID WITH REHEAT | 27.0577 | 0.0000 | 27.0577 | 15.2292 | 1212.62 | 1.48 | 4728.90 |
VAV_TOP WITH REHEAT | 2.5158 | 0.0000 | 2.5158 | 1.5229 | 1283.34 | 2.49 | 4657.16 |
CAV_BAS | 2.0203 | 0.0000 | 2.0203 | 1.2002 | 3429.97 | 0.17 | 2512.86 |
AIRLOOP DATACENTER BASEMENT | 16.8882 | 0.0000 | 16.8882 | 0.3384 | 411.24 | 0.00 | 5531.76 |
AIRLOOP DATACENTER BOT | 0.0136 | 0.0000 | 0.0136 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1365 | 0.0000 | 0.1365 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0136 | 0.0000 | 0.0136 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.89 | 3279.75 | 0.00 | 0.00 | 0.00 | 2173.33 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.51 | 2607.64 | 0.00 | 0.00 | 0.00 | 2259.28 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.00 | 2531.99 | 0.00 | 0.00 | 0.00 | 2314.31 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 646.52 | 1866.15 | 0.00 | 2.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 1786.50 | 6153.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 6.2072 | 0.0000 | 0.0000 | 0.0000 | 1.9103 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 46.2453 | 0.0000 | 0.0000 | 0.0000 | 20.3515 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 4.3368 | 0.0000 | 0.0000 | 0.0000 | 1.9858 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.4354 | 5.9362 | 0.0000 | 1.1112 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4045 | 26.6072 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0187 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.1869 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0187 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1432 |
Defaulted Fields | 1151 |
Fields with Defaults | 3678 |
Autosized Fields | 288 |
Autosizable Fields | 361 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 472 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 31154.39 | 312610.41 | 21-JAN-04:00 | 2148306.33 | 25-AUG-15:10 |
Electricity:Building | 17892.63 | 217189.06 | 07-MAY-17:20 | 1104084.83 | 01-DEC-16:30 |
Electricity:Zone:BASEMENT | 640.57 | 14055.89 | 01-JAN-00:10 | 32859.63 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 17892.63 | 217189.06 | 07-MAY-17:20 | 1104084.83 | 01-DEC-16:30 |
InteriorLights:Electricity | 3216.23 | 9932.90 | 16-APR-17:20 | 325713.14 | 20-JAN-17:00 |
InteriorLights:Electricity:Zone:BASEMENT | 216.17 | 598.35 | 01-JAN-00:10 | 19402.09 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3216.23 | 9932.90 | 16-APR-17:20 | 325713.14 | 20-JAN-17:00 |
LightsWired:InteriorLights:Electricity | 3216.23 | 9932.90 | 16-APR-17:20 | 325713.14 | 20-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 216.17 | 598.35 | 01-JAN-00:10 | 19402.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3216.23 | 9932.90 | 16-APR-17:20 | 325713.14 | 20-JAN-17:00 |
Electricity:Zone:CORE_BOTTOM | 483.75 | 4990.59 | 01-JAN-00:10 | 34631.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4837.49 | 49905.77 | 01-JAN-00:10 | 346310.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1941.37 | 5373.60 | 01-JAN-00:10 | 174244.37 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1941.37 | 5373.60 | 01-JAN-00:10 | 174244.37 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 483.75 | 4990.58 | 01-JAN-00:10 | 34631.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 50.45 | 617.00 | 02-APR-17:10 | 4348.36 | 20-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 14.09 | 57.83 | 01-JAN-10:10 | 2187.81 | 20-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 14.09 | 57.83 | 01-JAN-10:10 | 2187.81 | 20-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 32.30 | 397.62 | 16-APR-17:10 | 2802.25 | 20-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 8.87 | 37.27 | 01-JAN-07:50 | 1409.91 | 20-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 8.87 | 37.27 | 01-JAN-07:50 | 1409.91 | 20-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 50.03 | 617.01 | 02-APR-17:10 | 4348.44 | 20-JAN-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 13.66 | 57.83 | 01-JAN-08:00 | 2187.86 | 20-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 13.66 | 57.83 | 01-JAN-08:00 | 2187.86 | 20-JAN-17:00 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 32.43 | 397.61 | 12-MAR-17:10 | 2802.24 | 20-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 8.99 | 37.27 | 01-JAN-10:00 | 1409.91 | 20-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 8.99 | 37.27 | 01-JAN-10:00 | 1409.91 | 20-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 503.93 | 6169.98 | 02-APR-17:10 | 43483.64 | 20-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 140.27 | 578.27 | 01-JAN-10:00 | 21878.12 | 20-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 140.27 | 578.27 | 01-JAN-10:00 | 21878.12 | 20-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 322.87 | 3976.17 | 02-APR-17:10 | 28022.51 | 20-JAN-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 88.52 | 372.66 | 01-JAN-07:50 | 14099.09 | 20-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 88.52 | 372.66 | 01-JAN-07:50 | 14099.09 | 20-JAN-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 500.05 | 6170.07 | 26-MAR-17:10 | 43484.45 | 20-JAN-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 136.39 | 578.28 | 01-JAN-08:00 | 21878.60 | 20-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 136.39 | 578.28 | 01-JAN-08:00 | 21878.60 | 20-JAN-17:00 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 323.98 | 3976.14 | 12-MAR-17:10 | 28022.42 | 20-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 89.63 | 372.66 | 01-JAN-09:50 | 14099.09 | 20-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 89.63 | 372.66 | 01-JAN-09:50 | 14099.09 | 20-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 50.39 | 617.00 | 02-APR-17:10 | 4348.36 | 20-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 14.03 | 57.83 | 01-JAN-10:00 | 2187.81 | 20-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 14.03 | 57.83 | 01-JAN-10:00 | 2187.81 | 20-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 32.29 | 397.62 | 02-APR-17:10 | 2802.25 | 20-JAN-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 8.85 | 37.27 | 01-JAN-07:50 | 1409.91 | 20-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 8.85 | 37.27 | 01-JAN-07:50 | 1409.91 | 20-JAN-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 50.00 | 617.01 | 26-MAR-17:10 | 4348.44 | 20-JAN-17:00 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 13.64 | 57.83 | 01-JAN-08:00 | 2187.86 | 20-JAN-17:00 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 13.64 | 57.83 | 01-JAN-08:00 | 2187.86 | 20-JAN-17:00 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 32.40 | 397.61 | 12-MAR-17:10 | 2802.24 | 20-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 8.96 | 37.27 | 01-JAN-09:50 | 1409.91 | 20-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 8.96 | 37.27 | 01-JAN-09:50 | 1409.91 | 20-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7557.51 | 95212.03 | 01-JAN-00:10 | 385103.08 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 62.65 | 303.90 | 01-JAN-00:10 | 5470.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 62.65 | 303.90 | 01-JAN-00:10 | 5470.56 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 159.04 | 1973.61 | 01-JAN-00:10 | 8244.54 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1590.36 | 19736.13 | 01-JAN-00:10 | 82445.36 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 51.55 | 250.08 | 01-JAN-00:10 | 4501.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 51.55 | 250.08 | 01-JAN-00:10 | 4501.14 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 159.04 | 1973.61 | 01-JAN-00:10 | 8244.54 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 3624.17 | 4067.13 | 01-JAN-06:00 | 411485.95 | 05-SEP-08:20 |
HeatRejection:Electricity | 1225.77 | 194.75 | 01-JAN-08:00 | 86268.97 | 10-APR-14:50 |
General:HeatRejection:Electricity | 1225.77 | 194.75 | 01-JAN-08:00 | 86268.97 | 10-APR-14:50 |
Electricity:HVAC | 6775.29 | 57564.89 | 21-JAN-04:00 | 577384.98 | 06-DEC-07:10 |
ExteriorEquipment:Electricity | 2566.60 | 20217.42 | 01-JAN-00:10 | 233436.21 | 20-JAN-08:40 |
Transformer:ExteriorEquipment:Electricity | 55.01 | 979.82 | 01-JAN-00:10 | 3454.84 | 01-DEC-16:40 |
ElectricityPurchased:Facility | 31154.39 | 312610.41 | 21-JAN-04:00 | 2148306.33 | 25-AUG-15:10 |
ElectricityPurchased:Plant | 31154.39 | 312610.41 | 21-JAN-04:00 | 2148306.33 | 25-AUG-15:10 |
Cogeneration:ElectricityPurchased | 31154.39 | 312610.41 | 21-JAN-04:00 | 2148306.33 | 25-AUG-15:10 |
General:Cogeneration:ElectricityPurchased | 31154.39 | 312610.41 | 21-JAN-04:00 | 2148306.33 | 25-AUG-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 31154.39 | 312610.41 | 21-JAN-04:00 | 2148306.33 | 25-AUG-15:10 |
ElectricityNet:Plant | 31154.39 | 312610.41 | 21-JAN-04:00 | 2148306.33 | 25-AUG-15:10 |
Cogeneration:ElectricityNet | 31154.39 | 312610.41 | 21-JAN-04:00 | 2148306.33 | 25-AUG-15:10 |
General:Cogeneration:ElectricityNet | 31154.39 | 312610.41 | 21-JAN-04:00 | 2148306.33 | 25-AUG-15:10 |
Heating:Electricity | 60.63 | 0.00 | 01-JAN-00:10 | 367677.48 | 06-DEC-07:10 |
General:Heating:Electricity | 60.63 | 0.00 | 01-JAN-00:10 | 367677.48 | 06-DEC-07:10 |
Fans:Electricity | 2924.21 | 51088.04 | 01-JAN-13:50 | 270281.53 | 24-AUG-15:10 |
General:Fans:Electricity | 2924.21 | 51088.04 | 01-JAN-13:50 | 270281.53 | 24-AUG-15:10 |
ExteriorLights:Electricity | 350.70 | 0.00 | 01-JAN-07:30 | 40855.88 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 350.70 | 0.00 | 01-JAN-07:30 | 40855.88 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 2505.76 | 19200.00 | 01-JAN-00:10 | 229608.34 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 3643.81 | 2863.09 | 02-JAN-07:10 | 460655.15 | 11-AUG-16:00 |
General:Cooling:Electricity | 3643.81 | 2863.09 | 02-JAN-07:10 | 460655.15 | 11-AUG-16:00 |
Humidifier:Electricity | 1540.28 | 0.00 | 08-JAN-06:00 | 100000.00 | 01-JAN-12:30 |
General:Humidifier:Electricity | 1540.28 | 0.00 | 08-JAN-06:00 | 100000.00 | 01-JAN-12:30 |
Boiler:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 338.28 | 0.00 | 01-JAN-00:10 | 44032.98 | 23-JAN-12:40 |
Water Heater:WaterSystems:Electricity | 338.28 | 0.00 | 01-JAN-00:10 | 44032.98 | 23-JAN-12:40 |
Pumps:Electricity | 611.49 | 3862.43 | 04-DEC-05:20 | 54460.39 | 02-NOV-14:10 |
General:Pumps:Electricity | 611.49 | 3862.43 | 04-DEC-05:20 | 54460.39 | 02-NOV-14:10 |
WIRED_LTG_ELECTRICITY | 90.38 | 0.00 | 01-JAN-00:10 | 9152.54 | 20-JAN-17:10 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 21104.82 | 8836.90 | 02-JAN-07:10 | 2636931.11 | 18-JUL-05:10 |
PlantLoopCoolingDemand:HVAC | 21104.82 | 8836.90 | 02-JAN-07:10 | 2636931.11 | 18-JUL-05:10 |
CoolingCoils:PlantLoopCoolingDemand | 21104.82 | 8836.90 | 02-JAN-07:10 | 2636931.11 | 18-JUL-05:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 16444.50 | 0.00 | 08-JAN-06:00 | 0.00 | 27-JUN-12:00 |
Water:HVAC | 572.98 | 0.00 | 08-JAN-06:00 | 0.00 | 03-JAN-07:20 |
Humidifier:Water | 572.98 | 0.00 | 08-JAN-06:00 | 0.00 | 03-JAN-07:20 |
General:Humidifier:Water | 572.98 | 0.00 | 08-JAN-06:00 | 0.00 | 03-JAN-07:20 |
MainsWater:Facility | 16444.50 | 0.00 | 08-JAN-06:00 | 0.00 | 27-JUN-12:00 |
MainsWater:HVAC | 572.98 | 0.00 | 08-JAN-06:00 | 0.00 | 03-JAN-07:20 |
Humidifier:MainsWater | 572.98 | 0.00 | 08-JAN-06:00 | 0.00 | 03-JAN-07:20 |
General:Humidifier:MainsWater | 572.98 | 0.00 | 08-JAN-06:00 | 0.00 | 03-JAN-07:20 |
Water:Plant | 15871.51 | 0.00 | 01-JAN-00:10 | 0.00 | 27-JUN-12:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
MainsWater:Plant | 15871.51 | 0.00 | 01-JAN-00:10 | 0.00 | 27-JUN-12:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:20 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 13591.35 | 0.00 | 01-JAN-00:10 | 0.00 | 18-MAY-14:10 |
General:HeatRejection:Water | 13591.35 | 0.00 | 01-JAN-00:10 | 0.00 | 18-MAY-14:10 |
HeatRejection:MainsWater | 13591.35 | 0.00 | 01-JAN-00:10 | 0.00 | 18-MAY-14:10 |
General:HeatRejection:MainsWater | 13591.35 | 0.00 | 01-JAN-00:10 | 0.00 | 18-MAY-14:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 80862.38 | 101602.88 | 01-JAN-06:00 | 9771529.99 | 11-AUG-16:00 |
EnergyTransfer:Building | 21749.12 | 91657.05 | 01-JAN-13:10 | 1699557.90 | 24-AUG-15:30 |
EnergyTransfer:Zone:BASEMENT | 438.57 | 0.00 | 01-JAN-00:10 | 123856.48 | 24-AUG-06:10 |
Heating:EnergyTransfer | 36.22 | 0.00 | 01-JAN-17:10 | 286016.19 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 36.22 | 0.00 | 01-JAN-17:10 | 286016.19 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 21712.90 | 90820.72 | 01-JAN-09:30 | 1699557.90 | 24-AUG-15:30 |
Cooling:EnergyTransfer:Zone:BASEMENT | 438.57 | 0.00 | 01-JAN-00:10 | 123856.48 | 24-AUG-06:10 |
General:Cooling:EnergyTransfer | 21712.90 | 90820.72 | 01-JAN-09:30 | 1699557.90 | 24-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 438.57 | 0.00 | 01-JAN-00:10 | 123856.48 | 24-AUG-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 859.14 | 0.00 | 01-JAN-00:10 | 74405.74 | 14-AUG-07:40 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 859.14 | 0.00 | 01-JAN-00:10 | 74405.74 | 14-AUG-07:40 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 859.14 | 0.00 | 01-JAN-00:10 | 74405.74 | 14-AUG-07:40 |
EnergyTransfer:Zone:CORE_MID | 5347.26 | 0.00 | 01-JAN-00:10 | 444237.58 | 05-SEP-13:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 5347.26 | 0.00 | 01-JAN-00:10 | 444237.58 | 05-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 5347.26 | 0.00 | 01-JAN-00:10 | 444237.58 | 05-SEP-13:10 |
EnergyTransfer:Zone:CORE_TOP | 525.50 | 0.00 | 01-JAN-00:10 | 52521.63 | 19-JUN-14:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.39 | 0.00 | 01-JAN-00:10 | 38855.59 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 0.39 | 0.00 | 01-JAN-00:10 | 38855.59 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 525.12 | 0.00 | 01-JAN-00:10 | 52521.63 | 19-JUN-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 525.12 | 0.00 | 01-JAN-00:10 | 52521.63 | 19-JUN-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 118.26 | 0.00 | 01-JAN-00:10 | 14120.02 | 09-AUG-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 4.59 | 07-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 4.59 | 07-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 118.26 | 0.00 | 01-JAN-00:10 | 14120.02 | 09-AUG-14:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 118.26 | 0.00 | 01-JAN-00:10 | 14120.02 | 09-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 108.54 | 0.00 | 01-JAN-00:10 | 15313.45 | 14-AUG-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 906.28 | 07-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 906.28 | 07-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 108.54 | 0.00 | 01-JAN-00:10 | 15313.45 | 14-AUG-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 108.54 | 0.00 | 01-JAN-00:10 | 15313.45 | 14-AUG-08:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 164.97 | 0.00 | 01-JAN-00:10 | 19126.71 | 02-OCT-12:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 164.97 | 0.00 | 01-JAN-00:10 | 19126.71 | 02-OCT-12:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 164.97 | 0.00 | 01-JAN-00:10 | 19126.71 | 02-OCT-12:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 136.72 | 0.00 | 01-JAN-00:10 | 18040.23 | 25-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 136.72 | 0.00 | 01-JAN-00:10 | 18040.23 | 25-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 136.72 | 0.00 | 01-JAN-00:10 | 18040.23 | 25-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 805.15 | 0.00 | 01-JAN-00:10 | 117993.08 | 28-JUN-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 4.49 | 0.00 | 01-JAN-00:10 | 75076.91 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 4.49 | 0.00 | 01-JAN-00:10 | 75076.91 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 800.66 | 0.00 | 01-JAN-00:10 | 117993.08 | 28-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 800.66 | 0.00 | 01-JAN-00:10 | 117993.08 | 28-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 869.36 | 0.00 | 01-JAN-00:10 | 142982.00 | 19-JUN-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.89 | 0.00 | 01-JAN-00:10 | 42252.76 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 1.89 | 0.00 | 01-JAN-00:10 | 42252.76 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 867.47 | 0.00 | 01-JAN-00:10 | 142982.00 | 19-JUN-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 867.47 | 0.00 | 01-JAN-00:10 | 142982.00 | 19-JUN-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1327.25 | 0.00 | 01-JAN-00:10 | 182258.76 | 28-SEP-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.80 | 0.00 | 01-JAN-00:10 | 42338.71 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.80 | 0.00 | 01-JAN-00:10 | 42338.71 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1326.45 | 0.00 | 01-JAN-00:10 | 182258.76 | 28-SEP-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1326.45 | 0.00 | 01-JAN-00:10 | 182258.76 | 28-SEP-13:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 904.68 | 0.00 | 01-JAN-00:10 | 157927.38 | 29-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1.01 | 0.00 | 01-JAN-00:10 | 29061.35 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 1.01 | 0.00 | 01-JAN-00:10 | 29061.35 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 903.67 | 0.00 | 01-JAN-00:10 | 157927.38 | 29-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 903.67 | 0.00 | 01-JAN-00:10 | 157927.38 | 29-JUN-17:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 85.81 | 0.00 | 01-JAN-00:10 | 14011.08 | 02-JAN-06:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 3.14 | 0.00 | 01-JAN-00:10 | 14011.08 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 3.14 | 0.00 | 01-JAN-00:10 | 14011.08 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 82.67 | 0.00 | 01-JAN-00:10 | 13194.59 | 28-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 82.67 | 0.00 | 01-JAN-00:10 | 13194.59 | 28-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 89.25 | 0.00 | 01-JAN-00:10 | 14582.75 | 19-JUN-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 1.35 | 0.00 | 01-JAN-00:10 | 8820.09 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 1.35 | 0.00 | 01-JAN-00:10 | 8820.09 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 87.90 | 0.00 | 01-JAN-00:10 | 14582.75 | 19-JUN-09:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 87.90 | 0.00 | 01-JAN-00:10 | 14582.75 | 19-JUN-09:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 133.02 | 0.00 | 01-JAN-00:10 | 19751.04 | 28-SEP-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 1.07 | 0.00 | 01-JAN-00:10 | 9607.07 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 1.07 | 0.00 | 01-JAN-00:10 | 9607.07 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 131.95 | 0.00 | 01-JAN-00:10 | 19751.04 | 28-SEP-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 131.95 | 0.00 | 01-JAN-00:10 | 19751.04 | 28-SEP-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 92.42 | 0.00 | 01-JAN-00:10 | 16682.52 | 29-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.86 | 0.00 | 01-JAN-00:10 | 6768.35 | 02-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.86 | 0.00 | 01-JAN-00:10 | 6768.35 | 02-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 91.56 | 0.00 | 01-JAN-00:10 | 16682.52 | 29-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 91.56 | 0.00 | 01-JAN-00:10 | 16682.52 | 29-JUN-17:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 121.95 | 0.00 | 01-JAN-00:10 | 16904.83 | 14-AUG-05:30 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.28 | 0.00 | 01-JAN-00:10 | 2860.27 | 31-DEC-12:30 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.28 | 0.00 | 01-JAN-00:10 | 2860.27 | 31-DEC-12:30 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 120.66 | 0.00 | 01-JAN-00:10 | 16904.83 | 14-AUG-05:30 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 120.66 | 0.00 | 01-JAN-00:10 | 16904.83 | 14-AUG-05:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 719.88 | 0.00 | 01-JAN-00:10 | 90737.82 | 19-JUN-15:00 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 10.53 | 0.00 | 01-JAN-00:10 | 43440.34 | 02-JAN-16:30 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 10.53 | 0.00 | 01-JAN-00:10 | 43440.34 | 02-JAN-16:30 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 709.34 | 0.00 | 01-JAN-00:10 | 90737.82 | 19-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 709.34 | 0.00 | 01-JAN-00:10 | 90737.82 | 19-JUN-15:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 127.91 | 0.00 | 01-JAN-00:10 | 24580.84 | 28-JUN-14:00 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 9.23 | 0.00 | 01-JAN-00:10 | 14618.04 | 02-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 9.23 | 0.00 | 01-JAN-00:10 | 14618.04 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 118.69 | 0.00 | 01-JAN-00:10 | 24580.84 | 28-JUN-14:00 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 118.69 | 0.00 | 01-JAN-00:10 | 24580.84 | 28-JUN-14:00 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 143.40 | 1111.77 | 21-JAN-08:00 | 8033.81 | 28-DEC-17:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 143.40 | 1111.77 | 21-JAN-08:00 | 8033.81 | 28-DEC-17:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 143.40 | 1111.77 | 21-JAN-08:00 | 8033.81 | 28-DEC-17:00 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1296.63 | 25.68 | 01-JAN-12:50 | 75537.27 | 26-APR-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.10 | 0.00 | 01-JAN-00:10 | 3051.71 | 01-JAN-08:30 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.10 | 0.00 | 01-JAN-00:10 | 3051.71 | 01-JAN-08:30 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1296.54 | 0.00 | 01-JAN-01:30 | 75537.27 | 26-APR-18:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1296.54 | 0.00 | 01-JAN-01:30 | 75537.27 | 26-APR-18:20 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 125.08 | 5.68 | 01-JAN-18:10 | 7597.80 | 26-APR-18:10 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.08 | 0.00 | 01-JAN-16:40 | 594.67 | 01-JAN-02:40 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.08 | 0.00 | 01-JAN-16:40 | 594.67 | 01-JAN-02:40 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 125.00 | 0.00 | 01-JAN-00:10 | 7597.80 | 26-APR-18:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 125.00 | 0.00 | 01-JAN-00:10 | 7597.80 | 26-APR-18:10 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7208.36 | 88163.30 | 22-JAN-06:00 | 374199.87 | 24-APR-13:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7208.36 | 88163.30 | 22-JAN-06:00 | 374199.87 | 24-APR-13:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7208.36 | 88163.30 | 22-JAN-06:00 | 374199.87 | 24-APR-13:00 |
PlantLoopHeatingDemand:Facility | 333.38 | 0.00 | 01-JAN-00:10 | 43477.34 | 23-JAN-12:10 |
PlantLoopHeatingDemand:Plant | 333.38 | 0.00 | 01-JAN-00:10 | 43477.34 | 23-JAN-12:10 |
WaterSystems:PlantLoopHeatingDemand | 333.38 | 0.00 | 01-JAN-00:10 | 43477.34 | 23-JAN-12:10 |
General:WaterSystems:PlantLoopHeatingDemand | 333.38 | 0.00 | 01-JAN-00:10 | 43477.34 | 23-JAN-12:10 |
EnergyTransfer:HVAC | 18970.27 | 7296.86 | 01-JAN-08:00 | 2470811.82 | 18-JUL-05:10 |
HeatingCoils:EnergyTransfer | 60.63 | 0.00 | 01-JAN-00:10 | 367677.48 | 06-DEC-07:10 |
CoolingCoils:EnergyTransfer | 18909.65 | 5973.81 | 02-JAN-07:10 | 2470811.82 | 18-JUL-05:10 |
PlantLoopHeatingDemand:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatingCoils:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Plant | 40142.99 | 0.00 | 01-JAN-00:10 | 6074074.12 | 05-SEP-08:20 |
LoopToLoop:EnergyTransfer | 12920.44 | 0.00 | 01-JAN-00:10 | 1941842.07 | 19-JUN-14:10 |
WaterSystems:EnergyTransfer | 333.38 | 0.00 | 01-JAN-00:10 | 43477.34 | 23-JAN-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 333.38 | 0.00 | 01-JAN-00:10 | 43477.34 | 23-JAN-12:10 |
Chillers:EnergyTransfer | 12720.27 | 0.00 | 01-JAN-00:10 | 1932182.05 | 05-SEP-07:50 |
HeatRejection:EnergyTransfer | 14168.90 | 0.00 | 01-JAN-00:10 | 2190646.55 | 05-SEP-07:50 |
General:HeatRejection:EnergyTransfer | 14168.90 | 0.00 | 01-JAN-00:10 | 2190646.55 | 05-SEP-07:50 |
Boilers:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -438.545 | 0.000 | 0.000 | 74.061 | 216.171 | 424.397 | 0.000 | 0.000 | 0.000 | 0.008 | 0.000 | 0.000 | 0.000 | 0.000 | -276.084 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -859.141 | 0.000 | 0.000 | 83.333 | 194.137 | 289.614 | 0.000 | 0.000 | 0.000 | 292.057 | 0.000 | 0.000 | 0.000 | 0.000 | -0.004 |
CORE_MID | 0.000 | 0.000 | 0.000 | -5347.245 | 0.000 | 0.000 | 836.562 | 1941.366 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -326.811 |
CORE_TOP | 0.000 | 0.000 | 0.387 | -525.113 | 0.000 | 0.000 | 84.682 | 194.137 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -43.706 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -118.261 | 0.000 | 0.000 | 10.545 | 14.089 | 36.365 | 42.949 | 0.000 | 0.342 | 62.112 | 0.000 | -47.225 | 0.000 | -0.916 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.001 | -108.539 | 0.000 | 0.000 | 6.786 | 8.869 | 23.435 | 76.506 | 0.000 | 0.233 | 21.743 | 0.000 | -28.431 | 0.000 | -0.603 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -164.967 | 0.000 | 0.000 | 10.485 | 13.663 | 36.366 | 126.081 | 0.000 | 0.340 | 23.976 | 0.000 | -44.990 | 0.000 | -0.953 | -0.001 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -136.718 | 0.000 | 0.000 | 6.760 | 8.991 | 23.435 | 72.724 | 0.000 | 0.223 | 60.294 | 0.000 | -35.019 | 0.000 | -0.689 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 4.494 | -800.652 | 0.000 | 0.000 | 108.429 | 140.272 | 363.654 | 459.085 | 0.000 | 8.302 | 149.806 | 0.000 | -414.722 | 0.000 | -18.667 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 1.886 | -867.472 | 0.000 | 0.000 | 50.636 | 88.518 | 234.352 | 772.571 | 0.000 | 5.465 | 0.015 | 0.000 | -262.648 | 0.000 | -13.127 | -10.181 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.798 | -1326.428 | 0.000 | 0.000 | 105.404 | 136.392 | 363.660 | 1268.552 | 0.000 | 8.017 | 0.057 | 0.000 | -429.520 | 0.000 | -21.492 | -105.382 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 1.014 | -903.647 | 0.000 | 0.000 | 69.743 | 89.633 | 234.351 | 745.953 | 0.000 | 5.237 | 70.861 | 0.000 | -299.362 | 0.000 | -13.783 | -0.011 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 3.139 | -82.671 | 0.000 | 0.000 | 11.012 | 14.026 | 36.365 | 46.093 | 0.000 | 1.008 | 11.970 | 0.000 | -38.807 | 0.000 | -2.136 | -0.001 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 1.353 | -87.898 | 0.000 | 0.000 | 6.934 | 8.851 | 23.435 | 77.292 | 0.000 | 0.659 | 0.000 | 0.000 | -24.951 | 0.000 | -1.527 | -4.149 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 1.070 | -131.947 | 0.000 | 0.000 | 10.647 | 13.639 | 36.366 | 126.874 | 0.000 | 0.971 | 0.000 | 0.000 | -40.857 | 0.000 | -2.513 | -14.249 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.856 | -91.561 | 0.000 | 0.000 | 7.056 | 8.963 | 23.435 | 74.460 | 0.000 | 0.640 | 6.269 | 0.000 | -28.502 | 0.000 | -1.616 | -0.001 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -143.403 | 0.000 | 0.000 | 0.938 | 5.155 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -16.571 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.097 | -1296.535 | 0.000 | 0.000 | 9.398 | 51.551 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -303.317 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.079 | -125.002 | 0.000 | 0.000 | 0.942 | 5.155 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -35.055 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7208.366 | 0.000 | 0.000 | 20.429 | 62.653 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -369.573 |
GROUNDFLOOR_PLENUM | 1.285 | -120.660 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.634 | 120.786 | 0.000 | 0.000 | 0.000 | -2.045 | 0.000 |
MIDFLOOR_PLENUM | 10.534 | -709.341 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 12.357 | 720.770 | 0.000 | 0.000 | 0.000 | -34.320 | -0.012 |
TOPFLOOR_PLENUM | 9.226 | -118.684 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.276 | 111.652 | 0.000 | 0.000 | 0.000 | -3.469 | -0.003 |
Total Facility | 21.044 | -948.685 | 15.174 | -20764.111 | 0.000 | 0.000 | 1514.782 | 3216.229 | 14676.396 | 3889.140 | 0.000 | 45.704 | 1652.378 | 0.000 | -1695.035 | 0.000 | -117.857 | -1505.109 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 01-JUL-06:11 | 0.00 | 0.00 | 0.00 | -140321.39 | 0.00 | 0.00 | 554.83 | 2155.87 | 13457.54 | 0.00 | 0.00 | 0.00 | 124153.15 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 10-MAY-04:13 | 0.00 | 0.00 | 0.00 | -100401.61 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 93926.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 13-NOV-05:11 | 0.00 | 0.00 | 0.00 | -841989.27 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 777239.44 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 19-JUN-04:13 | 0.00 | 0.00 | 0.00 | -90349.49 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 83874.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 04-JUL-18:12 | 0.00 | 0.00 | 0.00 | -21268.05 | 0.00 | 0.00 | 0.00 | 57.83 | 559.17 | 6361.13 | 0.00 | 139.67 | 14150.26 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 18-JUN-08:41 | 0.00 | 0.00 | 0.00 | -22304.22 | 0.00 | 0.00 | 17.62 | 37.27 | 464.11 | 15181.77 | 0.00 | 18.22 | 6585.23 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 09-OCT-13:43 | 0.00 | 0.00 | 0.00 | -25777.14 | 0.00 | 0.00 | 30.36 | 57.83 | 720.19 | 19080.98 | 0.00 | 13.20 | 5874.57 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 27-AUG-16:22 | 0.00 | 0.00 | 0.00 | -30013.17 | 0.00 | 0.00 | 12.62 | 37.27 | 464.11 | 16939.60 | 0.00 | 91.87 | 12467.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 16-JUL-18:01 | 0.00 | 0.00 | 0.00 | -195494.87 | 0.00 | 0.00 | 0.00 | 578.27 | 5591.71 | 67535.58 | 0.00 | 4200.72 | 117588.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 04-JUN-09:11 | 0.00 | 0.00 | 0.00 | -230603.76 | 0.00 | 0.00 | 188.93 | 372.66 | 4641.14 | 138992.43 | 0.00 | 135.69 | 86272.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 15-OCT-14:21 | 0.00 | 0.00 | 0.00 | -239865.74 | 0.00 | 0.00 | 313.56 | 578.28 | 7201.95 | 167976.77 | 0.00 | 357.57 | 63437.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 13-AUG-16:51 | 0.00 | 0.00 | 0.00 | -265809.63 | 0.00 | 0.00 | 151.33 | 372.66 | 4641.11 | 158928.20 | 0.00 | 2500.02 | 99216.32 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-JUL-17:31 | 0.00 | 0.00 | 0.00 | -22795.05 | 0.00 | 0.00 | 0.00 | 57.83 | 559.17 | 6419.65 | 0.00 | 563.29 | 15195.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 18-JUN-08:41 | 0.00 | 0.00 | 0.00 | -24167.72 | 0.00 | 0.00 | 17.87 | 37.27 | 464.11 | 14955.03 | 0.00 | 51.68 | 8641.77 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 09-OCT-13:41 | 0.00 | 0.00 | 0.00 | -26998.74 | 0.00 | 0.00 | 31.05 | 57.83 | 720.19 | 18934.04 | 0.00 | 25.01 | 7230.63 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 13-AUG-16:51 | 0.00 | 0.00 | 0.00 | -29286.57 | 0.00 | 0.00 | 13.48 | 37.27 | 464.11 | 15715.71 | 0.00 | 290.99 | 12765.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 28-DEC-17:00 | 0.00 | 0.00 | 0.00 | -8033.79 | 0.00 | 0.00 | 100.85 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -311.59 |
DATACENTER_MID_ZN_6 | 26-APR-18:20 | 0.00 | 0.00 | 0.00 | -75536.03 | 0.00 | 0.00 | 105.00 | 1500.36 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4013.55 |
DATACENTER_TOP_ZN_6 | 26-APR-18:10 | 0.00 | 0.00 | 0.00 | -7597.68 | 0.00 | 0.00 | 10.60 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -357.38 |
DATACENTER_BASEMENT_ZN_6 | 05-AUG-17:03 | 0.00 | 0.00 | 0.00 | -381650.87 | 0.00 | 0.00 | 104.45 | 303.90 | 379632.52 | 0.00 | 0.00 | 0.00 | 1610.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 14-AUG-05:09 | 0.00 | -19433.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19434.12 | 0.00 | -0.00 | 0.00 | -0.26 | 0.00 |
MIDFLOOR_PLENUM | 19-JUN-05:02 | 0.00 | -112320.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112577.68 | 0.00 | -0.00 | 0.00 | -257.14 | 0.00 |
TOPFLOOR_PLENUM | 28-JUN-14:00 | 0.00 | -24582.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.16 | 24378.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 14-AUG-05:01 | 0.00 | -65530.81 | 0.00 | -1908979.80 | 0.00 | 0.00 | 15307.58 | 10917.52 | 616289.16 | 0.00 | 0.00 | 197.99 | 1364664.13 | 0.00 | -32863.60 | 0.00 | -2.16 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 02-JAN-05:11 | 0.00 | 0.00 | 60396.87 | 0.00 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -66871.86 |
PERIMETER_BOT_ZN_3 | 07-DEC-06:04 | 0.00 | 0.00 | 32.14 | 0.00 | 0.00 | 0.00 | 137.89 | 67.47 | 960.25 | 0.00 | 0.00 | 0.00 | 5531.76 | 0.00 | -6677.91 | 0.00 | -51.59 | 0.00 |
PERIMETER_BOT_ZN_2 | 07-DEC-06:01 | 0.00 | 0.00 | 5225.77 | 0.00 | 0.00 | 0.00 | 91.40 | 43.48 | 618.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4445.72 | 0.00 | -34.38 | -1499.38 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 02-JAN-05:11 | 0.00 | 0.00 | 143566.47 | 0.00 | 0.00 | 0.00 | 0.00 | 674.71 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -43950.35 | 0.00 | -1230.67 | -106515.77 |
PERIMETER_MID_ZN_2 | 02-JAN-05:11 | 0.00 | 0.00 | 94371.04 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -30634.22 | 0.00 | -845.23 | -68131.08 |
PERIMETER_MID_ZN_1 | 07-DEC-06:01 | 0.00 | 0.00 | 137703.64 | 0.00 | 0.00 | 0.00 | 1460.98 | 674.72 | 9602.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -65613.28 | 0.00 | -1193.85 | -82634.82 |
PERIMETER_MID_ZN_4 | 16-DEC-06:02 | 0.00 | 0.00 | 84615.71 | 0.00 | 0.00 | 0.00 | 939.27 | 434.81 | 6188.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -37016.73 | 0.00 | -252.54 | -54908.67 |
PERIMETER_TOP_ZN_3 | 18-DEC-05:11 | 0.00 | 0.00 | 17864.94 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3806.64 | 0.00 | -234.31 | -14637.02 |
PERIMETER_TOP_ZN_2 | 02-JAN-05:11 | 0.00 | 0.00 | 14168.96 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2551.96 | 0.00 | -88.92 | -12052.03 |
PERIMETER_TOP_ZN_1 | 02-JAN-05:11 | 0.00 | 0.00 | 18351.60 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4313.72 | 0.00 | -147.60 | -14703.32 |
PERIMETER_TOP_ZN_4 | 02-JAN-05:11 | 0.00 | 0.00 | 12505.05 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2755.56 | 0.00 | -95.97 | -10177.46 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 02-JAN-01:15 | 0.00 | 0.00 | 3807.01 | 0.00 | 0.00 | 0.00 | 0.00 | 250.08 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -23543.15 |
DATACENTER_TOP_ZN_6 | 01-JAN-02:40 | 0.00 | 0.00 | 594.67 | 0.00 | 0.00 | 0.00 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2568.28 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 18-DEC-05:11 | 10607.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -271.73 | -10336.20 |
MIDFLOOR_PLENUM | 30-JUL-16:51 | 91083.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7341.76 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -98425.70 |
TOPFLOOR_PLENUM | 02-JAN-06:03 | 16888.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -72.91 | -16815.97 |
Total Facility | 02-JAN-06:03 | -319372.35 | 312157.11 | 534094.84 | -312157.11 | 0.00 | 0.00 | 19644.41 | 10917.52 | 261414.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -192963.18 | 0.00 | -2785.59 | -310950.62 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 11.9396 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.6908 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 113.3856 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 100.2357 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 11.7599 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.2396 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.2359 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.2359 | 0.1925 | 1.0000 | Not calculated | 1.2002 | 0.1925 | ||
AIRLOOP DATACENTER BASEMENT | 27.0277 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 27.0280 | 0.0125 | 1.0000 | Not calculated | 0.3384 | 0.0125 | ||
AIRLOOP DATACENTER BOT | 0.5194 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5194 | 0.0301 | 1.0000 | Not calculated | 0.0156 | 0.0301 | ||
AIRLOOP DATACENTER MID | 4.9546 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.9546 | 0.0316 | 1.0000 | Not calculated | 0.1563 | 0.0316 | ||
AIRLOOP DATACENTER TOP | 0.5068 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5068 | 0.0308 | 1.0000 | Not calculated | 0.0156 | 0.0308 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.9698 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.0682 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 56.6928 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 29.9589 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.8800 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.1327 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 0.0000 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 0.0000 | 1.0000 | 1.0000 | Not calculated | 1.2002 | |||
AIRLOOP DATACENTER BASEMENT | 27.0277 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 27.0277 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0125 | ||
AIRLOOP DATACENTER BOT | 0.5194 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5194 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0301 | ||
AIRLOOP DATACENTER MID | 4.9546 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.9546 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0316 | ||
AIRLOOP DATACENTER TOP | 0.5068 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5068 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0308 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 6.2359 | 6.2359 | 0.0000 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.5293 | 6.5293 | 1.9849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 61.6264 | 61.6264 | 19.5356 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.1473 | 6.1473 | 2.0102 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2409 | 1.2409 | 0.2494 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2193 | 1.2193 | 0.2439 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3900 | 1.3900 | 0.2780 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5601 | 1.5601 | 0.3120 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.9217 | 11.9217 | 2.4559 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.6994 | 12.6994 | 2.5399 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.3631 | 13.3631 | 2.6726 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.7750 | 13.7750 | 2.7550 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3502 | 1.3502 | 0.2700 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2984 | 1.2984 | 0.2597 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4826 | 1.4826 | 0.2965 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4815 | 1.4815 | 0.2963 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5194 | 0.5194 | 0.5194 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.9546 | 4.9546 | 4.9546 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5068 | 0.5068 | 0.5068 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 27.0277 | 27.0277 | 27.0277 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 11.9396 | 10.6908 | 11.9396 | 3.0682 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 113.3856 | 100.2357 | 113.3856 | 29.9589 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 11.7599 | 11.2396 | 11.7599 | 3.1327 | 0.0000 | 1.0000 |
CAV_BAS | 6.2359 | 6.2359 | 6.2359 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 27.0277 | 27.0280 | 27.0277 | 27.0277 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5194 | 0.5194 | 0.5194 | 0.5194 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.9546 | 4.9546 | 4.9546 | 4.9546 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5068 | 0.5068 | 0.5068 | 0.5068 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 0.0000 | 0.0000 | 0.0000 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2647 | 3.2647 | 1.9849 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 30.8132 | 30.8132 | 19.5356 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0736 | 3.0736 | 2.0102 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6205 | 0.6205 | 0.2494 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6096 | 0.6096 | 0.2439 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6950 | 0.6950 | 0.2780 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7801 | 0.7801 | 0.3120 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.9609 | 5.9609 | 2.4559 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.3497 | 6.3497 | 2.5399 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.6815 | 6.6815 | 2.6726 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.8875 | 6.8875 | 2.7550 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6751 | 0.6751 | 0.2700 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6492 | 0.6492 | 0.2597 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7413 | 0.7413 | 0.2965 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7408 | 0.7408 | 0.2963 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5194 | 0.5194 | 0.5194 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.9546 | 4.9546 | 4.9546 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5068 | 0.5068 | 0.5068 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 27.0277 | 27.0277 | 27.0277 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.9698 | 3.0682 | 3.0682 | 3.0682 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 56.6928 | 29.9589 | 29.9589 | 29.9589 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.8800 | 3.1327 | 3.1327 | 3.1327 | 0.0000 | 1.0000 |
CAV_BAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 27.0277 | 27.0277 | 27.0277 | 27.0277 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5194 | 0.5194 | 0.5194 | 0.5194 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.9546 | 4.9546 | 4.9546 | 4.9546 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5068 | 0.5068 | 0.5068 | 0.5068 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 3124.83 |
Number of hours not met | 3124.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 60.63 | 367677.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 3643.81 | 460655.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3216.23 | 325713.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 350.70 | 40855.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 55.01 | 3454.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 2505.76 | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2924.21 | 270281.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 611.49 | 54460.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 1225.77 | 86268.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1540.28 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 338.28 | 44032.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 31154.39 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 31154.39 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 69.43 |
Space Heating | 1.31 |
Space Cooling | 78.67 |
Fans (All) | 63.13 |
Service Water Heating | 7.30 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 672.58 |
Subtotal | 672.58 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 10.32 |
Space Heating | 0.19 |
Space Cooling | 11.70 |
Fans (All) | 9.39 |
Service Water Heating | 1.09 |
Receptacle Equipment | 47.11 |
Miscellaneous | 20.21 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 5036.67 | 594.50 | 346.50 | 2770.00 | 12.33 |
CORE_BOTTOM | 8626.17 | 133.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8758.17 | 1.83 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8745.67 | 14.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8568.83 | 191.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8606.00 | 154.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8569.17 | 190.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8475.17 | 284.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8703.83 | 56.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8638.17 | 121.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8606.00 | 154.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8509.33 | 250.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8675.17 | 84.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8605.50 | 154.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8591.17 | 168.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8514.17 | 245.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7722.83 | 1037.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7769.33 | 990.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7805.17 | 954.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7108.33 | 1651.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8576.00 | 184.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8588.00 | 172.00 | 0.00 | 0.00 | 0.00 |
Min | 5036.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1651.67 | 346.50 | 2770.00 | 12.33 |
Average | 8285.17 | 338.80 | 15.07 | 120.43 | 0.54 |
Sum | 190558.83 | 7792.33 | 346.50 | 2770.00 | 12.33 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 219937.67 | 17809.17 | 9517.50 | 119591.33 | 1760.33 |
CORE_BOTTOM | 330603.00 | 210.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330802.00 | 11.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330788.00 | 25.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1744.00 | 524.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1745.83 | 522.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1759.67 | 508.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 79744.83 | 23650.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 330802.00 | 23650.17 | 9517.50 | 119591.33 | 1760.33 |
Average | 72764.09 | 1880.86 | 413.80 | 5199.62 | 76.54 |
Sum | 1673574.00 | 43259.83 | 9517.50 | 119591.33 | 1760.33 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 5132.00 | 521.50 | 242.33 | 1659.83 | 1204.33 |
CORE_BOTTOM | 8166.00 | 594.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8445.83 | 314.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8453.00 | 307.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8182.17 | 577.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8273.67 | 486.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8205.50 | 554.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8176.33 | 583.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8298.17 | 461.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8285.83 | 474.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8256.83 | 503.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8236.83 | 523.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8299.33 | 460.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8285.67 | 474.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8260.00 | 500.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8256.67 | 503.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8331.33 | 428.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8354.17 | 405.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8385.00 | 375.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7724.00 | 1036.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8131.00 | 629.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8302.50 | 457.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7838.00 | 922.00 | 0.00 | 0.00 | 0.00 |
Min | 5132.00 | 307.00 | 0.00 | 0.00 | 0.00 |
Max | 8453.00 | 1036.00 | 242.33 | 1659.83 | 1204.33 |
Average | 8099.12 | 525.81 | 10.54 | 72.17 | 52.36 |
Sum | 186279.83 | 12093.67 | 242.33 | 1659.83 | 1204.33 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 221817.67 | 17370.83 | 5942.83 | 47288.00 | 76196.67 |
CORE_BOTTOM | 329661.00 | 1152.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330291.00 | 522.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330276.00 | 537.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1987.83 | 280.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1990.33 | 277.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2015.50 | 252.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 92255.50 | 11139.50 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 330291.00 | 17370.83 | 5942.83 | 47288.00 | 76196.67 |
Average | 73336.69 | 1370.94 | 258.38 | 2056.00 | 3312.90 |
Sum | 1686743.83 | 31531.67 | 5942.83 | 47288.00 | 76196.67 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:54
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2B
For: Environment
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AZ_TUCSON
For: Environment
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.827 |
February | 12.716 |
March | 15.425 |
April | 23.310 |
May | 26.312 |
June | 31.196 |
July | 30.423 |
August | 29.815 |
September | 27.754 |
October | 20.869 |
November | 15.431 |
December | 11.863 |
Annual Sum or Average | 21.705 |
Minimum of Months | 11.863 |
Maximum of Months | 31.196 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.561524E+11 | 121750.95 | 02-JAN-07:05 | 6.00 | 2.09 | 0.570234E+10 | 7499.38 | 23-JAN-14:09 | 21.83 | 11.36 |
February | 0.461832E+11 | 117314.27 | 21-FEB-07:11 | 9.00 | 7.89 | 0.519005E+10 | 9863.00 | 10-FEB-10:00 | 9.00 | 7.89 |
March | 0.544360E+11 | 114562.32 | 20-MAR-06:11 | 11.43 | 7.83 | 0.617005E+10 | 7499.33 | 14-MAR-13:00 | 11.43 | 7.83 |
April | 0.477567E+11 | 131645.56 | 26-APR-19:31 | 18.33 | 9.16 | 0.590596E+10 | 11475.79 | 26-APR-13:00 | 18.33 | 9.16 |
May | 0.278268E+11 | 136890.03 | 12-MAY-06:11 | 18.33 | 8.38 | 0.785863E+10 | 12452.71 | 11-MAY-13:00 | 18.33 | 8.38 |
June | 0.431560E+10 | 139550.57 | 21-JUN-06:11 | 20.33 | 9.91 | 0.954365E+10 | 12931.48 | 09-JUN-13:00 | 20.33 | 9.91 |
July | 0.295713E+10 | 140511.94 | 01-JUL-06:11 | 19.67 | 7.38 | 0.939914E+10 | 13437.47 | 21-JUL-13:00 | 38.00 | 20.27 |
August | 0.489633E+10 | 133526.60 | 24-AUG-06:05 | 19.33 | 9.33 | 0.105886E+11 | 13684.46 | 18-AUG-13:00 | 19.33 | 9.33 |
September | 0.197406E+11 | 126175.86 | 21-SEP-06:11 | 20.37 | 16.29 | 0.839677E+10 | 13643.92 | 08-SEP-13:00 | 20.37 | 16.29 |
October | 0.534203E+11 | 132660.21 | 17-OCT-06:11 | 18.33 | 7.34 | 0.661081E+10 | 13438.05 | 03-OCT-13:00 | 18.33 | 7.34 |
November | 0.611803E+11 | 123371.02 | 02-NOV-06:11 | 16.00 | 11.38 | 0.575526E+10 | 10784.68 | 01-NOV-13:00 | 16.00 | 11.38 |
December | 0.597066E+11 | 123468.63 | 26-DEC-07:11 | 8.00 | 2.80 | 0.550545E+10 | 7499.20 | 13-DEC-10:09 | 8.00 | 2.80 |
Annual Sum or Average | 0.438572E+12 | 0.866267E+11 | ||||||||
Minimum of Months | 0.295713E+10 | 114562.32 | 6.00 | 2.09 | 0.519005E+10 | 7499.20 | 8.00 | 2.80 | ||
Maximum of Months | 0.611803E+11 | 140511.94 | 20.37 | 16.29 | 0.105886E+11 | 13684.46 | 38.00 | 20.27 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.498579E+11 | 100373.46 | 02-JAN-05:11 | 4.00 | 1.01 | 0.507655E+10 | 6734.82 | 23-JAN-14:09 | 21.83 | 11.36 |
February | 0.435861E+11 | 91909.96 | 21-FEB-05:12 | 9.33 | 8.41 | 0.460594E+10 | 6735.11 | 15-FEB-14:00 | 9.33 | 8.41 |
March | 0.568042E+11 | 94402.85 | 13-MAR-04:12 | 6.43 | 5.63 | 0.550035E+10 | 6734.86 | 17-MAR-09:00 | 21.60 | 14.25 |
April | 0.694262E+11 | 94369.65 | 07-APR-04:12 | 12.00 | 6.62 | 0.488029E+10 | 6734.83 | 24-APR-13:09 | 33.00 | 13.30 |
May | 0.728042E+11 | 100395.95 | 10-MAY-04:13 | 19.67 | 10.32 | 0.529075E+10 | 6738.26 | 09-MAY-13:00 | 19.67 | 10.32 |
June | 0.937701E+11 | 98322.52 | 10-JUN-04:13 | 20.67 | 10.83 | 0.528223E+10 | 6771.42 | 20-JUN-13:00 | 36.00 | 17.10 |
July | 0.995454E+11 | 99040.48 | 29-JUL-04:13 | 21.00 | 17.45 | 0.491564E+10 | 6773.64 | 18-JUL-13:00 | 21.00 | 17.45 |
August | 0.109160E+12 | 99451.63 | 07-AUG-04:24 | 21.00 | 17.63 | 0.551411E+10 | 6757.83 | 28-AUG-13:30 | 37.50 | 20.42 |
September | 0.840958E+11 | 99128.34 | 30-SEP-04:13 | 21.27 | 12.57 | 0.489112E+10 | 6742.26 | 20-SEP-09:30 | 21.27 | 12.57 |
October | 0.684001E+11 | 99756.24 | 11-OCT-04:13 | 18.00 | 10.82 | 0.508395E+10 | 6738.45 | 02-OCT-09:09 | 18.00 | 10.82 |
November | 0.570989E+11 | 98214.42 | 13-NOV-05:11 | 17.00 | 17.00 | 0.503126E+10 | 6734.99 | 16-NOV-14:09 | 18.00 | 11.84 |
December | 0.545937E+11 | 96955.16 | 04-DEC-05:11 | 3.00 | 0.78 | 0.490340E+10 | 6734.73 | 13-DEC-10:09 | 11.33 | 10.45 |
Annual Sum or Average | 0.859142E+12 | 0.609756E+11 | ||||||||
Minimum of Months | 0.435861E+11 | 91909.96 | 3.00 | 0.78 | 0.460594E+10 | 6734.73 | 9.33 | 8.41 | ||
Maximum of Months | 0.109160E+12 | 100395.95 | 21.27 | 17.63 | 0.551411E+10 | 6773.64 | 37.50 | 20.42 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.359988E+11 | 79538.40 | 27-JAN-06:02 | 12.83 | 5.24 | 0.502226E+10 | 6734.72 | 23-JAN-14:09 | 12.83 | 5.24 |
February | 0.308242E+11 | 78971.23 | 01-FEB-06:02 | 5.00 | 3.59 | 0.456451E+10 | 6735.00 | 15-FEB-14:00 | 20.00 | 13.98 |
March | 0.399964E+11 | 80454.27 | 20-MAR-04:12 | 11.83 | 7.65 | 0.547585E+10 | 6734.82 | 17-MAR-09:00 | 11.83 | 7.65 |
April | 0.464263E+11 | 82852.73 | 05-APR-04:11 | 17.33 | 7.97 | 0.487223E+10 | 6734.84 | 24-APR-13:09 | 33.00 | 13.30 |
May | 0.515181E+11 | 83377.64 | 12-MAY-04:12 | 19.67 | 9.22 | 0.528123E+10 | 6734.73 | 22-MAY-09:00 | 25.00 | 9.85 |
June | 0.556990E+11 | 81369.94 | 21-JUN-04:12 | 18.67 | 8.59 | 0.526205E+10 | 6734.75 | 29-JUN-09:09 | 33.17 | 18.03 |
July | 0.536353E+11 | 83387.44 | 29-JUL-04:12 | 21.00 | 17.45 | 0.488978E+10 | 6734.84 | 05-JUL-09:09 | 21.00 | 17.45 |
August | 0.558766E+11 | 82159.31 | 05-AUG-04:12 | 21.67 | 17.87 | 0.549210E+10 | 6734.86 | 28-AUG-09:09 | 31.50 | 20.35 |
September | 0.493959E+11 | 84057.60 | 22-SEP-04:12 | 17.60 | 14.75 | 0.487960E+10 | 6734.75 | 15-SEP-09:09 | 17.60 | 14.75 |
October | 0.448232E+11 | 84067.77 | 11-OCT-04:11 | 18.00 | 10.82 | 0.506619E+10 | 6734.86 | 03-OCT-13:39 | 18.00 | 10.82 |
November | 0.375685E+11 | 84217.93 | 13-NOV-05:11 | 17.00 | 17.00 | 0.500404E+10 | 6734.95 | 16-NOV-14:09 | 18.00 | 11.84 |
December | 0.329640E+11 | 77547.95 | 28-DEC-06:02 | 8.67 | 3.60 | 0.484243E+10 | 6734.75 | 13-DEC-10:09 | 8.67 | 3.60 |
Annual Sum or Average | 0.534726E+12 | 0.606523E+11 | ||||||||
Minimum of Months | 0.308242E+11 | 77547.95 | 5.00 | 3.59 | 0.456451E+10 | 6734.72 | 8.67 | 3.60 | ||
Maximum of Months | 0.558766E+11 | 84217.93 | 21.67 | 17.87 | 0.549210E+10 | 6735.00 | 33.17 | 20.35 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.292169E+11 | 38478.42 | 27-JAN-17:00 | 26.00 | 9.22 | 0.483354E+10 | 6734.54 | 23-JAN-14:39 | 26.00 | 9.22 |
February | 0.247657E+11 | 36243.94 | 22-FEB-17:00 | 20.00 | 11.26 | 0.437171E+10 | 6734.87 | 15-FEB-14:00 | 20.00 | 11.26 |
March | 0.341321E+11 | 77175.37 | 17-MAR-05:03 | 13.48 | 9.60 | 0.535499E+10 | 6734.79 | 17-MAR-09:00 | 21.60 | 14.25 |
April | 0.469587E+11 | 81708.04 | 05-APR-04:11 | 17.33 | 7.97 | 0.485705E+10 | 6734.84 | 24-APR-13:09 | 33.00 | 13.30 |
May | 0.544719E+11 | 82981.22 | 09-MAY-04:11 | 18.67 | 9.14 | 0.527909E+10 | 6734.73 | 12-MAY-09:09 | 25.33 | 10.84 |
June | 0.632096E+11 | 90403.56 | 19-JUN-04:13 | 22.67 | 10.74 | 0.526536E+10 | 6734.74 | 29-JUN-09:09 | 33.17 | 18.03 |
July | 0.606812E+11 | 83221.09 | 27-JUL-04:12 | 22.00 | 18.54 | 0.489435E+10 | 6734.85 | 05-JUL-09:09 | 22.00 | 18.54 |
August | 0.616980E+11 | 82425.80 | 03-AUG-03:02 | 25.00 | 18.33 | 0.549451E+10 | 6734.87 | 28-AUG-09:30 | 32.50 | 20.80 |
September | 0.527157E+11 | 83622.81 | 14-SEP-04:12 | 20.73 | 17.20 | 0.488145E+10 | 6734.73 | 15-SEP-09:09 | 25.45 | 16.44 |
October | 0.413373E+11 | 82733.83 | 05-OCT-04:12 | 19.67 | 13.65 | 0.501499E+10 | 6734.79 | 10-OCT-09:20 | 27.00 | 15.93 |
November | 0.310097E+11 | 77233.78 | 03-NOV-05:03 | 16.00 | 12.46 | 0.486324E+10 | 6734.89 | 16-NOV-14:09 | 18.00 | 11.84 |
December | 0.249194E+11 | 36119.77 | 22-DEC-17:00 | 24.00 | 9.52 | 0.451583E+10 | 6734.49 | 22-DEC-14:20 | 24.00 | 9.52 |
Annual Sum or Average | 0.525116E+12 | 0.596261E+11 | ||||||||
Minimum of Months | 0.247657E+11 | 36119.77 | 13.48 | 7.97 | 0.437171E+10 | 6734.49 | 18.00 | 9.22 | ||
Maximum of Months | 0.632096E+11 | 90403.56 | 26.00 | 18.54 | 0.549451E+10 | 6734.89 | 33.17 | 20.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.419452E+10 | 5468.69 | 31-JAN-16:30 | 29.00 | 10.73 | 0.619252E+09 | 845.63 | 23-JAN-14:09 | 29.00 | 10.73 |
February | 0.349534E+10 | 5328.90 | 22-FEB-14:00 | 21.00 | 12.01 | 0.560371E+09 | 845.66 | 15-FEB-14:00 | 21.00 | 12.01 |
March | 0.549922E+10 | 7649.00 | 20-MAR-14:00 | 27.70 | 14.42 | 0.678717E+09 | 845.64 | 17-MAR-09:00 | 27.70 | 14.42 |
April | 0.961513E+10 | 18961.00 | 30-APR-16:01 | 32.83 | 11.93 | 0.612262E+09 | 845.63 | 27-APR-13:39 | 32.83 | 11.93 |
May | 0.117305E+11 | 19155.38 | 07-MAY-16:11 | 36.00 | 14.16 | 0.664968E+09 | 846.20 | 09-MAY-13:00 | 35.00 | 14.58 |
June | 0.177194E+11 | 20709.09 | 04-JUN-17:02 | 37.83 | 15.97 | 0.664672E+09 | 851.64 | 20-JUN-13:00 | 36.00 | 17.10 |
July | 0.176249E+11 | 21268.04 | 04-JUL-18:12 | 36.00 | 14.97 | 0.618564E+09 | 852.05 | 18-JUL-13:00 | 38.00 | 21.23 |
August | 0.179206E+11 | 21125.92 | 27-AUG-16:22 | 40.00 | 18.07 | 0.693007E+09 | 849.29 | 28-AUG-13:30 | 37.50 | 20.42 |
September | 0.132198E+11 | 19021.92 | 10-SEP-16:02 | 34.80 | 19.29 | 0.614682E+09 | 846.04 | 29-SEP-13:00 | 35.50 | 16.50 |
October | 0.810787E+10 | 17561.36 | 09-OCT-13:41 | 31.83 | 17.27 | 0.633344E+09 | 846.07 | 02-OCT-09:09 | 31.83 | 17.27 |
November | 0.515358E+10 | 10072.19 | 13-NOV-05:11 | 17.00 | 17.00 | 0.622231E+09 | 845.65 | 16-NOV-14:09 | 18.00 | 11.84 |
December | 0.398062E+10 | 5774.43 | 26-DEC-15:40 | 23.00 | 10.62 | 0.592290E+09 | 845.62 | 13-DEC-10:09 | 23.00 | 10.62 |
Annual Sum or Average | 0.118261E+12 | 0.757436E+10 | ||||||||
Minimum of Months | 0.349534E+10 | 5328.90 | 17.00 | 10.62 | 0.560371E+09 | 845.62 | 18.00 | 10.62 | ||
Maximum of Months | 0.179206E+11 | 21268.04 | 40.00 | 19.29 | 0.693007E+09 | 852.05 | 38.00 | 21.23 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.454472E+10 | 7680.54 | 17-JAN-09:30 | 16.50 | 6.15 | 0.403009E+09 | 544.96 | 23-JAN-14:09 | 21.83 | 11.36 |
February | 0.367194E+10 | 8057.17 | 20-FEB-10:23 | 15.00 | 12.08 | 0.362821E+09 | 544.97 | 15-FEB-14:00 | 15.00 | 12.08 |
March | 0.538285E+10 | 17192.47 | 19-MAR-09:32 | 21.80 | 12.11 | 0.438231E+09 | 544.97 | 16-MAR-09:00 | 21.80 | 12.11 |
April | 0.960146E+10 | 20851.48 | 30-APR-09:21 | 26.50 | 9.83 | 0.394674E+09 | 545.96 | 13-APR-09:00 | 26.50 | 9.83 |
May | 0.116033E+11 | 21375.17 | 07-MAY-08:51 | 27.00 | 11.71 | 0.429082E+09 | 545.93 | 11-MAY-09:00 | 27.00 | 13.50 |
June | 0.155947E+11 | 22304.37 | 18-JUN-08:41 | 31.67 | 17.41 | 0.428602E+09 | 549.25 | 20-JUN-13:00 | 36.00 | 17.10 |
July | 0.149084E+11 | 21734.35 | 04-JUL-08:51 | 30.00 | 12.88 | 0.398758E+09 | 549.39 | 18-JUL-13:00 | 38.00 | 21.23 |
August | 0.151114E+11 | 21527.14 | 27-AUG-09:01 | 33.33 | 15.93 | 0.446665E+09 | 547.59 | 03-AUG-09:00 | 33.33 | 15.93 |
September | 0.114942E+11 | 20387.89 | 10-SEP-10:41 | 33.02 | 19.20 | 0.396140E+09 | 546.51 | 08-SEP-09:00 | 33.02 | 19.20 |
October | 0.794672E+10 | 19575.46 | 09-OCT-10:22 | 26.00 | 14.95 | 0.408704E+09 | 545.67 | 05-OCT-09:20 | 26.00 | 14.95 |
November | 0.487788E+10 | 8710.88 | 02-NOV-08:40 | 21.00 | 14.47 | 0.401374E+09 | 544.98 | 22-NOV-10:50 | 20.00 | 11.34 |
December | 0.380196E+10 | 6911.07 | 26-DEC-09:50 | 17.17 | 7.64 | 0.382835E+09 | 544.95 | 13-DEC-10:09 | 17.17 | 7.64 |
Annual Sum or Average | 0.108539E+12 | 0.489090E+10 | ||||||||
Minimum of Months | 0.367194E+10 | 6911.07 | 15.00 | 6.15 | 0.362821E+09 | 544.95 | 15.00 | 7.64 | ||
Maximum of Months | 0.155947E+11 | 22304.37 | 33.33 | 19.20 | 0.446665E+09 | 549.39 | 38.00 | 21.23 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128071E+11 | 23617.04 | 29-JAN-11:42 | 21.67 | 8.74 | 0.633927E+09 | 893.30 | 17-JAN-14:20 | 21.67 | 8.74 |
February | 0.764610E+10 | 21894.95 | 26-FEB-14:02 | 17.00 | 10.27 | 0.567914E+09 | 847.84 | 23-FEB-14:00 | 17.00 | 10.27 |
March | 0.915437E+10 | 14817.49 | 23-MAR-13:40 | 25.33 | 11.79 | 0.680054E+09 | 847.43 | 17-MAR-13:09 | 25.33 | 11.79 |
April | 0.131090E+11 | 22260.27 | 30-APR-16:01 | 32.83 | 11.93 | 0.612617E+09 | 847.45 | 25-APR-13:20 | 32.83 | 11.93 |
May | 0.124783E+11 | 21582.38 | 07-MAY-16:11 | 36.00 | 14.16 | 0.664848E+09 | 846.28 | 09-MAY-13:00 | 35.00 | 14.58 |
June | 0.168044E+11 | 22504.08 | 04-JUN-16:22 | 38.00 | 16.06 | 0.664286E+09 | 851.99 | 20-JUN-13:00 | 36.00 | 17.10 |
July | 0.174678E+11 | 23005.83 | 04-JUL-16:52 | 37.00 | 15.96 | 0.618337E+09 | 852.59 | 18-JUL-13:00 | 38.00 | 21.23 |
August | 0.196826E+11 | 24271.91 | 27-AUG-15:02 | 40.00 | 18.27 | 0.693438E+09 | 881.81 | 30-AUG-13:50 | 37.83 | 18.97 |
September | 0.170280E+11 | 25181.49 | 10-SEP-13:23 | 34.70 | 19.32 | 0.617425E+09 | 926.70 | 28-SEP-13:39 | 36.47 | 16.05 |
October | 0.150671E+11 | 25777.13 | 09-OCT-13:43 | 31.83 | 17.27 | 0.641588E+09 | 934.65 | 02-OCT-13:09 | 31.83 | 17.27 |
November | 0.123798E+11 | 24330.76 | 19-NOV-13:31 | 26.00 | 11.06 | 0.631765E+09 | 905.66 | 20-NOV-14:20 | 27.00 | 11.68 |
December | 0.113445E+11 | 25452.62 | 25-DEC-13:11 | 25.33 | 11.74 | 0.608814E+09 | 886.14 | 26-DEC-14:09 | 23.00 | 10.20 |
Annual Sum or Average | 0.164969E+12 | 0.763501E+10 | ||||||||
Minimum of Months | 0.764610E+10 | 14817.49 | 17.00 | 8.74 | 0.567914E+09 | 846.28 | 17.00 | 8.74 | ||
Maximum of Months | 0.196826E+11 | 25777.13 | 40.00 | 19.32 | 0.693438E+09 | 934.65 | 38.00 | 21.23 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.633242E+10 | 25012.76 | 29-JAN-16:22 | 24.50 | 9.40 | 0.400062E+09 | 544.97 | 30-JAN-14:00 | 25.00 | 9.66 |
February | 0.530920E+10 | 17332.68 | 20-FEB-16:22 | 17.50 | 9.63 | 0.366203E+09 | 545.00 | 15-FEB-14:00 | 17.50 | 9.63 |
March | 0.852830E+10 | 19444.57 | 26-MAR-15:52 | 18.30 | 6.21 | 0.443455E+09 | 544.97 | 09-MAR-14:00 | 18.30 | 6.21 |
April | 0.148828E+11 | 29459.55 | 30-APR-16:41 | 32.17 | 11.84 | 0.396422E+09 | 544.97 | 27-APR-13:39 | 32.17 | 11.84 |
May | 0.126176E+11 | 28225.80 | 07-MAY-16:11 | 36.00 | 14.16 | 0.429002E+09 | 545.40 | 09-MAY-13:00 | 35.00 | 14.58 |
June | 0.170474E+11 | 29030.90 | 04-JUN-16:21 | 38.00 | 16.06 | 0.428572E+09 | 550.10 | 20-JUN-13:00 | 36.00 | 17.10 |
July | 0.165004E+11 | 29542.78 | 02-JUL-17:21 | 38.00 | 14.95 | 0.398945E+09 | 550.41 | 05-JUL-13:00 | 38.00 | 16.49 |
August | 0.182413E+11 | 30013.19 | 27-AUG-16:22 | 40.00 | 18.07 | 0.447166E+09 | 547.81 | 28-AUG-13:30 | 37.50 | 20.42 |
September | 0.117826E+11 | 24953.66 | 04-SEP-15:52 | 31.60 | 21.45 | 0.395956E+09 | 545.25 | 29-SEP-13:00 | 35.50 | 16.50 |
October | 0.993104E+10 | 25273.50 | 09-OCT-15:41 | 32.83 | 17.35 | 0.410338E+09 | 545.26 | 02-OCT-09:09 | 32.83 | 17.35 |
November | 0.822307E+10 | 25027.32 | 05-NOV-15:12 | 22.67 | 8.62 | 0.406238E+09 | 544.99 | 27-NOV-14:39 | 24.97 | 9.27 |
December | 0.732349E+10 | 26535.49 | 25-DEC-15:11 | 26.00 | 11.71 | 0.394162E+09 | 544.95 | 13-DEC-10:09 | 26.00 | 11.71 |
Annual Sum or Average | 0.136720E+12 | 0.491652E+10 | ||||||||
Minimum of Months | 0.530920E+10 | 17332.68 | 17.50 | 6.21 | 0.366203E+09 | 544.95 | 17.50 | 6.21 | ||
Maximum of Months | 0.182413E+11 | 30013.19 | 40.00 | 21.45 | 0.447166E+09 | 550.41 | 38.00 | 20.42 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.292636E+10 | 3916.19 | 31-JAN-16:30 | 29.00 | 10.73 | 0.563819E+09 | 845.60 | 06-JAN-14:00 | 29.00 | 10.73 |
February | 0.230717E+10 | 3058.66 | 22-FEB-16:10 | 20.83 | 11.61 | 0.507980E+09 | 845.63 | 15-FEB-14:00 | 20.83 | 11.61 |
March | 0.355888E+10 | 5812.32 | 16-MAR-16:00 | 28.80 | 13.95 | 0.641246E+09 | 845.63 | 17-MAR-09:00 | 21.60 | 14.25 |
April | 0.657086E+10 | 10409.87 | 26-APR-05:02 | 19.87 | 10.36 | 0.606701E+09 | 845.63 | 24-APR-13:09 | 19.87 | 10.36 |
May | 0.910223E+10 | 18000.38 | 21-MAY-18:11 | 30.33 | 12.75 | 0.663730E+09 | 845.63 | 22-MAY-09:00 | 25.00 | 9.85 |
June | 0.130377E+11 | 19296.66 | 04-JUN-17:51 | 37.00 | 15.56 | 0.663083E+09 | 845.66 | 28-JUN-13:00 | 41.00 | 19.20 |
July | 0.117634E+11 | 19553.44 | 16-JUL-18:01 | 34.83 | 21.45 | 0.616644E+09 | 845.64 | 05-JUL-09:09 | 34.83 | 21.45 |
August | 0.111385E+11 | 19342.17 | 13-AUG-16:11 | 38.00 | 20.37 | 0.691099E+09 | 845.64 | 28-AUG-09:30 | 32.50 | 20.80 |
September | 0.891659E+10 | 16122.41 | 17-SEP-13:23 | 34.70 | 17.91 | 0.613527E+09 | 845.62 | 19-SEP-09:09 | 28.77 | 14.28 |
October | 0.529678E+10 | 18079.05 | 01-OCT-13:42 | 37.00 | 19.01 | 0.614013E+09 | 845.66 | 03-OCT-13:39 | 33.00 | 20.21 |
November | 0.317683E+10 | 5721.58 | 02-NOV-14:00 | 27.00 | 15.44 | 0.581810E+09 | 845.64 | 16-NOV-14:09 | 18.00 | 11.84 |
December | 0.227061E+10 | 2990.45 | 22-DEC-16:10 | 24.83 | 10.00 | 0.512857E+09 | 820.55 | 22-DEC-14:00 | 24.83 | 10.00 |
Annual Sum or Average | 0.800659E+11 | 0.727651E+10 | ||||||||
Minimum of Months | 0.227061E+10 | 2990.45 | 19.87 | 10.00 | 0.507980E+09 | 820.55 | 18.00 | 9.85 | ||
Maximum of Months | 0.130377E+11 | 19553.44 | 38.00 | 21.45 | 0.691099E+09 | 845.66 | 41.00 | 21.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.354462E+10 | 5861.80 | 27-JAN-10:00 | 20.00 | 7.78 | 0.281670E+09 | 521.20 | 31-JAN-11:09 | 18.83 | 8.01 |
February | 0.278796E+10 | 6412.25 | 23-FEB-10:00 | 14.00 | 11.11 | 0.253445E+09 | 521.21 | 16-FEB-16:10 | 14.00 | 11.11 |
March | 0.435118E+10 | 12928.54 | 19-MAR-09:23 | 21.35 | 11.96 | 0.311553E+09 | 521.22 | 16-MAR-10:09 | 21.35 | 11.96 |
April | 0.840452E+10 | 21868.67 | 30-APR-09:11 | 26.00 | 9.61 | 0.290103E+09 | 521.42 | 14-APR-08:00 | 26.00 | 9.61 |
May | 0.103436E+11 | 22243.36 | 07-MAY-09:01 | 27.17 | 11.80 | 0.315474E+09 | 521.68 | 18-MAY-10:30 | 31.00 | 12.87 |
June | 0.129646E+11 | 23060.09 | 04-JUN-09:11 | 31.37 | 16.06 | 0.314398E+09 | 524.38 | 19-JUN-07:19 | 29.00 | 12.63 |
July | 0.115731E+11 | 22055.75 | 02-JUL-09:31 | 30.33 | 11.95 | 0.293456E+09 | 522.27 | 10-JUL-10:50 | 35.67 | 19.19 |
August | 0.113268E+11 | 22727.43 | 13-AUG-10:11 | 33.33 | 21.27 | 0.327610E+09 | 522.32 | 15-AUG-10:50 | 34.67 | 19.80 |
September | 0.871582E+10 | 21189.21 | 04-SEP-10:22 | 27.15 | 21.76 | 0.291326E+09 | 521.42 | 07-SEP-08:00 | 31.60 | 20.58 |
October | 0.629488E+10 | 20041.05 | 15-OCT-09:42 | 25.67 | 10.35 | 0.296964E+09 | 521.22 | 02-OCT-07:10 | 25.67 | 10.35 |
November | 0.372598E+10 | 7117.00 | 10-NOV-09:30 | 22.00 | 9.55 | 0.284995E+09 | 521.23 | 22-NOV-11:09 | 19.33 | 11.05 |
December | 0.271430E+10 | 4164.32 | 27-DEC-10:00 | 14.00 | 6.80 | 0.257148E+09 | 521.20 | 29-DEC-11:30 | 17.50 | 8.08 |
Annual Sum or Average | 0.867473E+11 | 0.351814E+10 | ||||||||
Minimum of Months | 0.271430E+10 | 4164.32 | 14.00 | 6.80 | 0.253445E+09 | 521.20 | 14.00 | 8.01 | ||
Maximum of Months | 0.129646E+11 | 23060.09 | 33.33 | 21.76 | 0.327610E+09 | 524.38 | 35.67 | 20.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122631E+11 | 22839.18 | 16-JAN-12:12 | 24.00 | 8.78 | 0.632169E+09 | 922.98 | 30-JAN-14:39 | 24.67 | 9.55 |
February | 0.678677E+10 | 21349.35 | 26-FEB-14:02 | 17.00 | 10.27 | 0.557025E+09 | 854.94 | 28-FEB-14:20 | 18.33 | 7.88 |
March | 0.755294E+10 | 14753.03 | 26-MAR-14:13 | 17.20 | 5.88 | 0.666844E+09 | 846.71 | 17-MAR-13:09 | 17.20 | 5.88 |
April | 0.104158E+11 | 21115.17 | 09-APR-14:02 | 30.83 | 12.22 | 0.609472E+09 | 846.70 | 25-APR-13:20 | 31.00 | 14.70 |
May | 0.101952E+11 | 20158.82 | 07-MAY-15:41 | 35.83 | 14.03 | 0.663474E+09 | 845.65 | 22-MAY-09:00 | 25.00 | 9.85 |
June | 0.124909E+11 | 21195.62 | 04-JUN-16:31 | 38.00 | 16.06 | 0.662730E+09 | 845.66 | 19-JUN-13:09 | 38.17 | 18.27 |
July | 0.121013E+11 | 21485.11 | 16-JUL-16:41 | 36.83 | 20.63 | 0.616543E+09 | 845.98 | 31-JUL-13:00 | 37.00 | 19.00 |
August | 0.135246E+11 | 22375.85 | 13-AUG-15:31 | 38.00 | 20.90 | 0.691550E+09 | 848.24 | 30-AUG-13:50 | 37.83 | 18.97 |
September | 0.133483E+11 | 22797.19 | 04-SEP-13:42 | 30.92 | 21.71 | 0.615772E+09 | 931.71 | 28-SEP-13:50 | 36.83 | 16.07 |
October | 0.130730E+11 | 23986.55 | 15-OCT-14:21 | 31.00 | 12.59 | 0.637748E+09 | 924.14 | 31-OCT-13:00 | 27.00 | 12.18 |
November | 0.110479E+11 | 23412.63 | 19-NOV-13:02 | 26.00 | 10.94 | 0.627768E+09 | 921.15 | 20-NOV-14:30 | 27.00 | 11.68 |
December | 0.984541E+10 | 23378.60 | 03-DEC-13:12 | 20.33 | 10.37 | 0.598274E+09 | 900.22 | 22-DEC-14:09 | 25.17 | 10.15 |
Annual Sum or Average | 0.132645E+12 | 0.757937E+10 | ||||||||
Minimum of Months | 0.678677E+10 | 14753.03 | 17.00 | 5.88 | 0.557025E+09 | 845.65 | 17.20 | 5.88 | ||
Maximum of Months | 0.135246E+11 | 23986.55 | 38.00 | 21.71 | 0.691550E+09 | 931.71 | 38.17 | 19.00 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.440049E+10 | 14790.51 | 29-JAN-17:12 | 23.00 | 8.84 | 0.367011E+09 | 544.95 | 17-JAN-14:39 | 23.00 | 8.84 |
February | 0.315998E+10 | 10570.18 | 22-FEB-16:30 | 20.50 | 11.47 | 0.327778E+09 | 544.97 | 15-FEB-14:00 | 20.50 | 11.47 |
March | 0.476118E+10 | 16133.06 | 18-MAR-17:05 | 26.92 | 12.85 | 0.410065E+09 | 544.96 | 09-MAR-14:00 | 26.92 | 12.85 |
April | 0.898334E+10 | 23447.33 | 30-APR-16:31 | 32.33 | 11.86 | 0.391681E+09 | 544.96 | 27-APR-13:30 | 32.33 | 11.86 |
May | 0.104287E+11 | 25564.77 | 28-MAY-17:21 | 32.50 | 12.51 | 0.427742E+09 | 544.96 | 22-MAY-09:00 | 32.50 | 12.51 |
June | 0.132493E+11 | 26225.48 | 04-JUN-16:31 | 38.00 | 16.06 | 0.427453E+09 | 544.96 | 19-JUN-13:09 | 38.17 | 18.27 |
July | 0.110692E+11 | 26047.96 | 16-JUL-17:21 | 36.50 | 21.23 | 0.397525E+09 | 544.97 | 05-JUL-09:09 | 36.50 | 21.23 |
August | 0.112327E+11 | 26587.35 | 13-AUG-16:51 | 38.00 | 19.94 | 0.445617E+09 | 544.97 | 28-AUG-09:30 | 32.50 | 20.80 |
September | 0.866967E+10 | 24220.77 | 04-SEP-15:41 | 31.60 | 21.45 | 0.395253E+09 | 544.95 | 15-SEP-09:09 | 25.45 | 16.44 |
October | 0.649363E+10 | 23189.85 | 15-OCT-17:01 | 29.83 | 12.03 | 0.394080E+09 | 544.99 | 03-OCT-13:39 | 29.83 | 12.03 |
November | 0.459538E+10 | 14843.05 | 26-NOV-16:23 | 18.50 | 8.85 | 0.376612E+09 | 544.97 | 16-NOV-14:09 | 18.50 | 8.85 |
December | 0.332305E+10 | 10356.92 | 22-DEC-16:30 | 24.50 | 9.81 | 0.341654E+09 | 544.93 | 22-DEC-14:30 | 24.50 | 9.81 |
Annual Sum or Average | 0.903666E+11 | 0.470247E+10 | ||||||||
Minimum of Months | 0.315998E+10 | 10356.92 | 18.50 | 8.84 | 0.327778E+09 | 544.93 | 18.50 | 8.84 | ||
Maximum of Months | 0.132493E+11 | 26587.35 | 38.00 | 21.45 | 0.445617E+09 | 544.99 | 38.17 | 21.23 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.252945E+10 | 3716.98 | 31-JAN-17:00 | 29.00 | 10.73 | 0.534016E+09 | 845.57 | 06-JAN-14:00 | 29.00 | 10.73 |
February | 0.190800E+10 | 2947.29 | 22-FEB-16:30 | 20.50 | 11.47 | 0.478223E+09 | 845.56 | 22-FEB-14:00 | 20.50 | 11.47 |
March | 0.327290E+10 | 6259.77 | 16-MAR-16:00 | 28.80 | 13.95 | 0.612957E+09 | 845.62 | 23-MAR-13:09 | 25.08 | 11.95 |
April | 0.682197E+10 | 10030.98 | 26-APR-05:02 | 19.87 | 10.36 | 0.600159E+09 | 845.63 | 24-APR-13:09 | 19.87 | 10.36 |
May | 0.962910E+10 | 20506.91 | 21-MAY-15:41 | 32.00 | 13.36 | 0.662647E+09 | 845.63 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.143299E+11 | 21394.56 | 18-JUN-17:22 | 38.00 | 19.08 | 0.663131E+09 | 845.64 | 19-JUN-13:09 | 38.17 | 18.27 |
July | 0.129493E+11 | 22800.31 | 16-JUL-17:31 | 36.33 | 21.35 | 0.616719E+09 | 845.64 | 05-JUL-09:09 | 36.33 | 21.35 |
August | 0.120857E+11 | 22740.79 | 13-AUG-16:11 | 38.00 | 20.37 | 0.690990E+09 | 845.65 | 28-AUG-09:39 | 33.00 | 21.02 |
September | 0.948435E+10 | 20943.19 | 04-SEP-15:41 | 31.60 | 21.45 | 0.612853E+09 | 845.62 | 19-SEP-09:09 | 28.77 | 14.28 |
October | 0.519630E+10 | 20701.01 | 01-OCT-13:42 | 37.00 | 19.01 | 0.596839E+09 | 845.65 | 03-OCT-13:30 | 33.00 | 20.21 |
November | 0.277883E+10 | 5952.85 | 01-NOV-15:30 | 28.50 | 15.96 | 0.554663E+09 | 845.61 | 02-NOV-13:09 | 26.17 | 15.52 |
December | 0.168619E+10 | 3134.14 | 22-DEC-15:00 | 26.00 | 10.43 | 0.483940E+09 | 801.53 | 22-DEC-16:00 | 24.00 | 9.52 |
Annual Sum or Average | 0.826720E+11 | 0.710714E+10 | ||||||||
Minimum of Months | 0.168619E+10 | 2947.29 | 19.87 | 10.36 | 0.478223E+09 | 801.53 | 19.87 | 9.52 | ||
Maximum of Months | 0.143299E+11 | 22800.31 | 38.00 | 21.45 | 0.690990E+09 | 845.65 | 38.17 | 21.35 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.300573E+10 | 4814.65 | 27-JAN-10:30 | 21.00 | 7.83 | 0.377645E+09 | 544.94 | 09-JAN-10:09 | 21.00 | 7.83 |
February | 0.229257E+10 | 5390.65 | 23-FEB-10:20 | 14.67 | 11.08 | 0.337408E+09 | 544.95 | 23-FEB-10:09 | 14.67 | 11.08 |
March | 0.394638E+10 | 7391.27 | 23-MAR-10:20 | 22.33 | 10.61 | 0.419456E+09 | 544.96 | 14-MAR-13:50 | 22.33 | 10.61 |
April | 0.857370E+10 | 20750.86 | 16-APR-09:52 | 21.00 | 12.82 | 0.393759E+09 | 545.00 | 03-APR-09:20 | 21.00 | 12.82 |
May | 0.107787E+11 | 22643.53 | 21-MAY-09:41 | 28.67 | 11.96 | 0.428472E+09 | 545.63 | 11-MAY-09:00 | 28.67 | 11.96 |
June | 0.139866E+11 | 24168.73 | 18-JUN-08:41 | 31.67 | 17.41 | 0.427635E+09 | 545.52 | 08-JUN-09:00 | 31.67 | 17.41 |
July | 0.124884E+11 | 21470.72 | 30-JUL-09:32 | 31.00 | 18.77 | 0.397827E+09 | 545.50 | 28-JUL-09:00 | 31.00 | 18.77 |
August | 0.121169E+11 | 23450.32 | 13-AUG-10:11 | 33.33 | 21.27 | 0.445712E+09 | 545.49 | 22-AUG-09:00 | 32.00 | 19.27 |
September | 0.922299E+10 | 21816.16 | 04-SEP-10:22 | 27.15 | 21.76 | 0.395457E+09 | 546.09 | 08-SEP-09:00 | 32.20 | 21.03 |
October | 0.608925E+10 | 18427.80 | 01-OCT-13:42 | 37.00 | 19.01 | 0.401780E+09 | 544.99 | 17-OCT-09:30 | 25.00 | 10.00 |
November | 0.323680E+10 | 6284.27 | 01-NOV-10:00 | 23.00 | 16.02 | 0.381911E+09 | 544.98 | 22-NOV-10:00 | 20.00 | 11.57 |
December | 0.215987E+10 | 3070.23 | 22-DEC-15:00 | 26.00 | 10.43 | 0.335548E+09 | 544.93 | 01-DEC-10:00 | 26.00 | 10.43 |
Annual Sum or Average | 0.878978E+11 | 0.474261E+10 | ||||||||
Minimum of Months | 0.215987E+10 | 3070.23 | 14.67 | 7.83 | 0.335548E+09 | 544.93 | 14.67 | 7.83 | ||
Maximum of Months | 0.139866E+11 | 24168.73 | 37.00 | 21.76 | 0.445712E+09 | 546.09 | 32.20 | 21.03 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.110700E+11 | 26131.59 | 29-JAN-14:11 | 24.00 | 9.34 | 0.614553E+09 | 871.63 | 24-JAN-14:00 | 24.00 | 9.34 |
February | 0.583679E+10 | 16583.57 | 28-FEB-14:20 | 18.33 | 7.88 | 0.539504E+09 | 846.37 | 23-FEB-14:50 | 18.33 | 7.88 |
March | 0.687319E+10 | 14545.23 | 16-MAR-13:30 | 27.45 | 13.00 | 0.648562E+09 | 845.98 | 16-MAR-13:00 | 27.70 | 13.27 |
April | 0.106902E+11 | 23402.50 | 30-APR-12:51 | 34.00 | 12.41 | 0.604077E+09 | 846.60 | 25-APR-13:09 | 34.00 | 12.41 |
May | 0.107782E+11 | 23038.59 | 21-MAY-15:41 | 32.00 | 13.36 | 0.661552E+09 | 845.64 | 16-MAY-13:00 | 32.00 | 13.36 |
June | 0.137733E+11 | 23189.45 | 18-JUN-17:22 | 38.00 | 19.08 | 0.662642E+09 | 845.66 | 19-JUN-13:09 | 38.17 | 18.27 |
July | 0.133106E+11 | 24704.33 | 16-JUL-16:51 | 37.00 | 20.84 | 0.616486E+09 | 846.07 | 31-JUL-13:00 | 37.00 | 19.00 |
August | 0.145462E+11 | 25715.87 | 13-AUG-15:31 | 38.00 | 20.90 | 0.691275E+09 | 847.19 | 28-AUG-13:09 | 37.83 | 20.53 |
September | 0.140164E+11 | 25414.30 | 04-SEP-13:42 | 30.92 | 21.71 | 0.614683E+09 | 908.19 | 28-SEP-13:50 | 36.83 | 16.07 |
October | 0.127453E+11 | 26998.45 | 09-OCT-13:41 | 31.83 | 17.27 | 0.626553E+09 | 896.13 | 02-OCT-13:20 | 31.83 | 17.27 |
November | 0.100100E+11 | 25058.37 | 05-NOV-13:42 | 22.00 | 8.01 | 0.613344E+09 | 885.92 | 01-NOV-13:00 | 22.00 | 8.01 |
December | 0.829941E+10 | 26130.22 | 25-DEC-14:21 | 26.00 | 11.78 | 0.579378E+09 | 856.51 | 22-DEC-14:09 | 26.00 | 11.78 |
Annual Sum or Average | 0.131949E+12 | 0.747261E+10 | ||||||||
Minimum of Months | 0.583679E+10 | 14545.23 | 18.33 | 7.88 | 0.539504E+09 | 845.64 | 18.33 | 7.88 | ||
Maximum of Months | 0.145462E+11 | 26998.45 | 38.00 | 21.71 | 0.691275E+09 | 908.19 | 38.17 | 20.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.393513E+10 | 16373.31 | 29-JAN-16:52 | 24.00 | 9.34 | 0.354244E+09 | 544.94 | 06-JAN-14:00 | 24.00 | 9.34 |
February | 0.275045E+10 | 10531.24 | 22-FEB-16:30 | 20.50 | 11.47 | 0.314814E+09 | 544.92 | 23-FEB-14:00 | 18.00 | 10.35 |
March | 0.445107E+10 | 16622.58 | 18-MAR-17:05 | 26.92 | 12.85 | 0.395125E+09 | 544.97 | 10-MAR-14:00 | 26.92 | 12.85 |
April | 0.918193E+10 | 24717.71 | 23-APR-16:21 | 33.15 | 12.72 | 0.387194E+09 | 544.96 | 27-APR-13:00 | 26.00 | 12.23 |
May | 0.108462E+11 | 26486.94 | 29-MAY-15:51 | 32.00 | 13.93 | 0.426235E+09 | 544.95 | 30-MAY-09:00 | 28.00 | 14.40 |
June | 0.141607E+11 | 25942.88 | 25-JUN-17:31 | 38.00 | 15.08 | 0.427390E+09 | 544.96 | 19-JUN-13:09 | 38.00 | 15.08 |
July | 0.119062E+11 | 28693.33 | 16-JUL-16:51 | 37.00 | 20.84 | 0.397411E+09 | 544.97 | 05-JUL-09:09 | 37.00 | 20.84 |
August | 0.119155E+11 | 29293.40 | 13-AUG-16:51 | 38.00 | 19.94 | 0.445305E+09 | 544.97 | 28-AUG-09:39 | 33.00 | 21.02 |
September | 0.911106E+10 | 26430.03 | 04-SEP-15:41 | 31.60 | 21.45 | 0.394316E+09 | 544.95 | 15-SEP-09:20 | 25.90 | 16.61 |
October | 0.637203E+10 | 25373.57 | 15-OCT-15:31 | 31.00 | 12.59 | 0.385225E+09 | 544.98 | 03-OCT-13:30 | 31.00 | 12.59 |
November | 0.417959E+10 | 12542.86 | 01-NOV-16:00 | 28.00 | 15.72 | 0.364387E+09 | 544.96 | 16-NOV-14:30 | 18.00 | 11.97 |
December | 0.275350E+10 | 10279.94 | 22-DEC-16:30 | 24.50 | 9.81 | 0.329469E+09 | 544.94 | 22-DEC-14:39 | 24.50 | 9.81 |
Annual Sum or Average | 0.915633E+11 | 0.462112E+10 | ||||||||
Minimum of Months | 0.275045E+10 | 10279.94 | 20.50 | 9.34 | 0.314814E+09 | 544.92 | 18.00 | 9.34 | ||
Maximum of Months | 0.141607E+11 | 29293.40 | 38.00 | 21.45 | 0.445305E+09 | 544.98 | 38.00 | 21.02 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.487669E+10 | 7941.07 | 02-JAN-06:10 | 4.33 | 1.20 | 0.00 | 0.00 | 01-JAN-00:10 | 4.33 | 1.20 |
February | 0.360998E+10 | 5680.32 | 21-FEB-06:08 | 9.83 | 8.31 | 0.00 | 0.00 | 01-FEB-00:10 | 9.83 | 8.31 |
March | 0.558221E+10 | 7777.58 | 20-MAR-05:15 | 11.27 | 7.51 | 0.00 | 0.00 | 01-MAR-00:10 | 11.27 | 7.51 |
April | 0.968634E+10 | 10130.85 | 24-APR-05:15 | 15.33 | 4.72 | 0.00 | 0.00 | 01-APR-00:10 | 15.33 | 4.72 |
May | 0.119423E+11 | 13306.01 | 30-MAY-05:15 | 18.00 | 8.93 | 0.00 | 0.00 | 01-MAY-00:10 | 18.00 | 8.93 |
June | 0.165053E+11 | 18632.63 | 19-JUN-05:10 | 22.17 | 10.17 | 0.00 | 0.00 | 01-JUN-00:10 | 22.17 | 10.17 |
July | 0.167497E+11 | 18527.34 | 31-JUL-05:08 | 25.83 | 15.57 | 0.00 | 0.00 | 01-JUL-00:10 | 25.83 | 15.57 |
August | 0.179425E+11 | 19434.80 | 14-AUG-05:09 | 26.00 | 16.58 | 0.00 | 0.00 | 01-AUG-00:10 | 26.00 | 16.58 |
September | 0.135491E+11 | 16353.11 | 05-SEP-05:15 | 21.63 | 18.84 | 0.00 | 0.00 | 01-SEP-00:10 | 21.63 | 18.84 |
October | 0.941213E+10 | 16769.77 | 02-OCT-05:08 | 25.83 | 16.98 | 0.00 | 0.00 | 01-OCT-00:10 | 25.83 | 16.98 |
November | 0.617832E+10 | 9720.19 | 13-NOV-06:15 | 16.67 | 16.67 | 0.00 | 0.00 | 01-NOV-00:10 | 16.67 | 16.67 |
December | 0.462575E+10 | 9365.47 | 26-DEC-06:15 | 8.67 | 3.13 | 0.00 | 0.00 | 01-DEC-00:10 | 8.67 | 3.13 |
Annual Sum or Average | 0.120660E+12 | 0.00 | ||||||||
Minimum of Months | 0.360998E+10 | 5680.32 | 4.33 | 1.20 | 0.00 | 0.00 | 4.33 | 1.20 | ||
Maximum of Months | 0.179425E+11 | 19434.80 | 26.00 | 18.84 | 0.00 | 0.00 | 26.00 | 18.84 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.235126E+10 | 4432.20 | 28-JAN-06:10 | 8.00 | 1.64 | 0.00 | 0.00 | 01-JAN-00:10 | 8.00 | 1.64 |
February | 0.175554E+10 | 4650.72 | 01-FEB-06:08 | 5.00 | 3.59 | 0.00 | 0.00 | 01-FEB-00:10 | 5.00 | 3.59 |
March | 0.288546E+10 | 4935.02 | 20-MAR-05:10 | 11.18 | 7.43 | 0.00 | 0.00 | 01-MAR-00:10 | 11.18 | 7.43 |
April | 0.648552E+10 | 7271.47 | 14-APR-15:20 | 35.00 | 14.57 | 0.00 | 0.00 | 01-APR-00:10 | 35.00 | 14.57 |
May | 0.824869E+10 | 7581.69 | 11-MAY-05:15 | 21.67 | 11.92 | 0.00 | 0.00 | 01-MAY-00:10 | 21.67 | 11.92 |
June | 0.106817E+11 | 11234.90 | 19-JUN-05:02 | 22.17 | 10.17 | 0.00 | 0.00 | 01-JUN-00:10 | 22.17 | 10.17 |
July | 0.986226E+10 | 10332.87 | 22-JUL-05:02 | 29.00 | 19.60 | 0.00 | 0.00 | 01-JUL-00:10 | 29.00 | 19.60 |
August | 0.997497E+10 | 8860.61 | 14-AUG-15:10 | 38.00 | 19.83 | 0.00 | 0.00 | 01-AUG-00:10 | 38.00 | 19.83 |
September | 0.842822E+10 | 10500.93 | 05-SEP-05:02 | 21.92 | 18.79 | 0.00 | 0.00 | 01-SEP-00:10 | 21.92 | 18.79 |
October | 0.556842E+10 | 9036.47 | 03-OCT-05:03 | 22.00 | 18.54 | 0.00 | 0.00 | 01-OCT-00:10 | 22.00 | 18.54 |
November | 0.302393E+10 | 5394.89 | 24-NOV-06:02 | 3.17 | -1.7 | 0.00 | 0.00 | 01-NOV-00:10 | 3.17 | -1.7 |
December | 0.166831E+10 | 7099.06 | 06-DEC-06:01 | 0.67 | -4.3 | 0.00 | 0.00 | 01-DEC-00:10 | 0.67 | -4.3 |
Annual Sum or Average | 0.709343E+11 | 0.00 | ||||||||
Minimum of Months | 0.166831E+10 | 4432.20 | 0.67 | -4.3 | 0.00 | 0.00 | 0.67 | -4.3 | ||
Maximum of Months | 0.106817E+11 | 11234.90 | 38.00 | 19.83 | 0.00 | 0.00 | 38.00 | 19.83 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.292418E+10 | 8886.93 | 31-JAN-16:20 | 29.00 | 10.73 | 0.00 | 0.00 | 01-JAN-00:10 | 29.00 | 10.73 |
February | 0.174632E+10 | 8003.44 | 23-FEB-14:50 | 18.00 | 10.42 | 0.00 | 0.00 | 01-FEB-00:10 | 18.00 | 10.42 |
March | 0.414362E+10 | 12623.03 | 16-MAR-15:20 | 28.80 | 13.79 | 0.00 | 0.00 | 01-MAR-00:10 | 28.80 | 13.79 |
April | 0.116087E+11 | 20052.67 | 14-APR-15:20 | 35.00 | 14.57 | 0.00 | 0.00 | 01-APR-00:10 | 35.00 | 14.57 |
May | 0.149465E+11 | 20453.92 | 19-MAY-14:00 | 36.00 | 14.39 | 0.00 | 0.00 | 01-MAY-00:10 | 36.00 | 14.39 |
June | 0.208447E+11 | 24580.84 | 28-JUN-14:00 | 41.00 | 19.20 | 0.00 | 0.00 | 01-JUN-00:10 | 41.00 | 19.20 |
July | 0.184319E+11 | 23344.56 | 20-JUL-14:00 | 39.00 | 20.25 | 0.00 | 0.00 | 01-JUL-00:10 | 39.00 | 20.25 |
August | 0.180543E+11 | 22797.49 | 15-AUG-15:10 | 39.00 | 18.89 | 0.00 | 0.00 | 01-AUG-00:10 | 39.00 | 18.89 |
September | 0.136008E+11 | 20409.21 | 07-SEP-15:20 | 37.37 | 19.77 | 0.00 | 0.00 | 01-SEP-00:10 | 37.37 | 19.77 |
October | 0.759619E+10 | 17816.69 | 02-OCT-14:20 | 35.00 | 19.60 | 0.00 | 0.00 | 01-OCT-00:10 | 35.00 | 19.60 |
November | 0.332881E+10 | 11563.61 | 01-NOV-15:20 | 28.67 | 16.04 | 0.00 | 0.00 | 01-NOV-00:10 | 28.67 | 16.04 |
December | 0.146006E+10 | 6851.59 | 22-DEC-16:00 | 25.00 | 10.09 | 0.00 | 0.00 | 01-DEC-00:10 | 25.00 | 10.09 |
Annual Sum or Average | 0.118686E+12 | 0.00 | ||||||||
Minimum of Months | 0.146006E+10 | 6851.59 | 18.00 | 10.09 | 0.00 | 0.00 | 18.00 | 10.09 | ||
Maximum of Months | 0.208447E+11 | 24580.84 | 41.00 | 20.25 | 0.00 | 0.00 | 41.00 | 20.25 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.414255E+10 | 2280.02 | 24-JAN-17:00 | 24.00 | 10.79 | 95230236.68 | 126.83 | 09-JAN-10:00 | 24.00 | 10.79 |
February | 0.821709E+10 | 4124.13 | 27-FEB-17:40 | 15.67 | 8.53 | 86398871.44 | 126.84 | 16-FEB-10:50 | 15.67 | 8.53 |
March | 0.144519E+11 | 7157.26 | 31-MAR-24:00 | 15.30 | 7.49 | 0.103237E+09 | 126.84 | 06-MAR-10:00 | 15.30 | 7.49 |
April | 0.187202E+11 | 7923.29 | 26-APR-18:30 | 20.00 | 9.88 | 97226498.90 | 156.18 | 24-APR-13:00 | 20.00 | 9.88 |
May | 0.488415E+10 | 3573.03 | 31-MAY-23:50 | 26.17 | 10.67 | 99233113.87 | 126.82 | 01-MAY-13:39 | 26.17 | 10.67 |
June | 0.983504E+10 | 5551.28 | 30-JUN-23:53 | 28.10 | 15.37 | 98957380.03 | 126.83 | 30-JUN-09:00 | 28.10 | 15.37 |
July | 0.152422E+11 | 7482.72 | 31-JUL-23:55 | 29.60 | 17.96 | 91883834.45 | 126.83 | 18-JUL-09:09 | 29.60 | 17.96 |
August | 0.198425E+11 | 7890.81 | 06-AUG-20:17 | 27.33 | 19.22 | 0.109233E+09 | 165.25 | 25-AUG-13:00 | 41.00 | 17.20 |
September | 0.479899E+10 | 3629.09 | 30-SEP-23:47 | 25.25 | 15.43 | 91613752.47 | 126.86 | 05-SEP-09:09 | 25.25 | 15.43 |
October | 0.975163E+10 | 5331.34 | 31-OCT-24:00 | 17.10 | 9.96 | 95231237.23 | 126.85 | 03-OCT-09:20 | 17.10 | 9.96 |
November | 0.141182E+11 | 6276.64 | 14-NOV-17:00 | 19.00 | 14.11 | 94302080.47 | 126.84 | 13-NOV-10:09 | 19.00 | 14.11 |
December | 0.193990E+11 | 8033.81 | 28-DEC-17:00 | 18.60 | 7.88 | 92013920.67 | 132.04 | 22-DEC-16:00 | 18.60 | 7.88 |
Annual Sum or Average | 0.143403E+12 | 0.115456E+10 | ||||||||
Minimum of Months | 0.414255E+10 | 2280.02 | 15.30 | 7.49 | 86398871.44 | 126.82 | 15.30 | 7.49 | ||
Maximum of Months | 0.198425E+11 | 8033.81 | 29.60 | 19.22 | 0.109233E+09 | 165.25 | 41.00 | 17.96 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.290327E+10 | 2106.81 | 24-JAN-17:00 | 24.00 | 10.79 | 95230226.24 | 126.83 | 09-JAN-10:00 | 24.00 | 10.79 |
February | 0.682722E+10 | 3832.16 | 27-FEB-17:40 | 15.67 | 8.53 | 86398688.55 | 126.84 | 16-FEB-10:50 | 15.67 | 8.53 |
March | 0.130607E+11 | 6673.09 | 31-MAR-23:50 | 15.32 | 7.32 | 0.103237E+09 | 126.83 | 06-MAR-10:00 | 15.32 | 7.32 |
April | 0.177393E+11 | 7553.73 | 26-APR-18:20 | 20.33 | 10.02 | 96818545.11 | 153.96 | 24-APR-13:00 | 20.33 | 10.02 |
May | 0.438231E+10 | 3392.85 | 31-MAY-23:53 | 26.00 | 10.61 | 99233114.80 | 126.82 | 12-MAY-13:09 | 26.00 | 10.61 |
June | 0.912431E+10 | 5219.28 | 30-JUN-23:53 | 28.10 | 15.37 | 98957390.16 | 126.83 | 30-JUN-09:00 | 28.10 | 15.37 |
July | 0.141777E+11 | 7001.93 | 31-JUL-23:55 | 29.60 | 17.96 | 91884573.52 | 126.84 | 14-JUL-09:00 | 29.60 | 17.96 |
August | 0.186357E+11 | 7398.24 | 06-AUG-18:30 | 29.50 | 19.18 | 0.108325E+09 | 163.42 | 25-AUG-13:00 | 41.00 | 17.20 |
September | 0.423522E+10 | 3394.01 | 30-SEP-24:00 | 25.20 | 15.49 | 91612341.83 | 126.85 | 05-SEP-13:20 | 25.20 | 15.49 |
October | 0.873914E+10 | 4896.84 | 31-OCT-24:00 | 17.10 | 9.96 | 95231302.45 | 126.85 | 03-OCT-09:20 | 17.10 | 9.96 |
November | 0.126161E+11 | 5893.42 | 14-NOV-17:00 | 19.00 | 14.11 | 94302057.48 | 126.84 | 13-NOV-14:00 | 19.00 | 14.11 |
December | 0.172126E+11 | 7515.54 | 28-DEC-17:00 | 18.60 | 7.88 | 91929788.05 | 129.90 | 22-DEC-16:00 | 18.60 | 7.88 |
Annual Sum or Average | 0.129654E+12 | 0.115316E+10 | ||||||||
Minimum of Months | 0.290327E+10 | 2106.81 | 15.32 | 7.32 | 86398688.55 | 126.82 | 15.32 | 7.32 | ||
Maximum of Months | 0.186357E+11 | 7553.73 | 29.60 | 19.18 | 0.108325E+09 | 163.42 | 41.00 | 17.96 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.203454E+10 | 2125.53 | 24-JAN-17:00 | 24.00 | 10.79 | 95116263.75 | 126.83 | 09-JAN-10:00 | 24.00 | 10.79 |
February | 0.583069E+10 | 3812.85 | 27-FEB-17:40 | 15.67 | 8.53 | 86398683.61 | 126.84 | 16-FEB-10:00 | 15.67 | 8.53 |
March | 0.123876E+11 | 6488.49 | 31-MAR-23:20 | 15.37 | 6.81 | 0.103237E+09 | 126.83 | 06-MAR-10:00 | 15.37 | 6.81 |
April | 0.177277E+11 | 7597.80 | 26-APR-18:10 | 20.67 | 10.17 | 95916963.14 | 153.69 | 24-APR-13:00 | 20.67 | 10.17 |
May | 0.438315E+10 | 3393.69 | 31-MAY-23:53 | 26.00 | 10.61 | 99233115.42 | 126.82 | 01-MAY-13:00 | 26.00 | 10.61 |
June | 0.926269E+10 | 5260.62 | 30-JUN-23:53 | 28.10 | 15.37 | 98957391.54 | 126.83 | 30-JUN-09:00 | 28.10 | 15.37 |
July | 0.143323E+11 | 7059.81 | 31-JUL-23:55 | 29.60 | 17.96 | 91884650.91 | 126.84 | 14-JUL-09:00 | 29.60 | 17.96 |
August | 0.187792E+11 | 7563.15 | 06-AUG-18:30 | 29.50 | 19.18 | 0.107258E+09 | 163.46 | 25-AUG-13:00 | 41.00 | 17.20 |
September | 0.428757E+10 | 3438.62 | 30-SEP-24:00 | 25.20 | 15.49 | 91612641.28 | 126.85 | 11-SEP-13:50 | 25.20 | 15.49 |
October | 0.834147E+10 | 4694.65 | 31-OCT-23:50 | 16.98 | 9.75 | 95231315.90 | 126.85 | 03-OCT-09:00 | 16.98 | 9.75 |
November | 0.117605E+11 | 5921.89 | 21-NOV-17:00 | 24.00 | 10.76 | 94302119.48 | 126.84 | 13-NOV-14:00 | 24.00 | 10.76 |
December | 0.158749E+11 | 7552.86 | 26-DEC-17:00 | 23.00 | 10.75 | 91892139.29 | 126.82 | 13-DEC-10:00 | 23.00 | 10.75 |
Annual Sum or Average | 0.125002E+12 | 0.115104E+10 | ||||||||
Minimum of Months | 0.203454E+10 | 2125.53 | 15.37 | 6.81 | 86398683.61 | 126.82 | 15.37 | 6.81 | ||
Maximum of Months | 0.187792E+11 | 7597.80 | 29.60 | 19.18 | 0.107258E+09 | 163.46 | 41.00 | 17.96 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.240955E+12 | 92933.80 | 02-JAN-17:00 | 20.00 | 7.42 | 0.206145E+10 | 2745.42 | 02-JAN-10:09 | 20.00 | 7.42 |
February | 0.435953E+12 | 183616.39 | 22-FEB-17:00 | 20.00 | 11.26 | 0.187022E+10 | 2745.99 | 17-FEB-14:00 | 20.00 | 11.26 |
March | 0.728283E+12 | 358351.57 | 31-MAR-24:00 | 15.30 | 7.49 | 0.223494E+10 | 2748.43 | 01-MAR-14:50 | 15.30 | 7.49 |
April | 0.942470E+12 | 380618.68 | 09-APR-14:04 | 30.83 | 12.22 | 0.206330E+10 | 3956.86 | 03-APR-15:00 | 30.83 | 12.22 |
May | 0.242733E+12 | 176894.92 | 31-MAY-23:53 | 26.00 | 10.61 | 0.214822E+10 | 2747.02 | 09-MAY-13:00 | 26.00 | 10.61 |
June | 0.473756E+12 | 269249.70 | 30-JUN-23:53 | 28.10 | 15.37 | 0.214278E+10 | 2748.04 | 02-JUN-13:09 | 28.10 | 15.37 |
July | 0.737767E+12 | 362127.17 | 31-JUL-23:55 | 29.60 | 17.96 | 0.199031E+10 | 2810.57 | 14-JUL-09:09 | 29.60 | 17.96 |
August | 0.983079E+12 | 381913.40 | 05-AUG-17:03 | 21.17 | 19.06 | 0.229118E+10 | 3551.82 | 01-AUG-09:09 | 21.17 | 19.06 |
September | 0.241721E+12 | 178620.05 | 30-SEP-24:00 | 25.20 | 15.49 | 0.198323E+10 | 2746.93 | 15-SEP-09:39 | 25.20 | 15.49 |
October | 0.491490E+12 | 269372.38 | 31-OCT-24:00 | 17.10 | 9.96 | 0.206166E+10 | 2747.72 | 19-OCT-13:00 | 17.10 | 9.96 |
November | 0.711247E+12 | 277734.48 | 20-NOV-17:00 | 26.00 | 12.00 | 0.204167E+10 | 2750.15 | 01-NOV-09:00 | 26.00 | 12.00 |
December | 0.978904E+12 | 369383.15 | 26-DEC-17:00 | 23.00 | 10.75 | 0.198901E+10 | 2746.09 | 13-DEC-14:09 | 23.00 | 10.75 |
Annual Sum or Average | 0.720836E+13 | 0.248780E+11 | ||||||||
Minimum of Months | 0.240955E+12 | 92933.80 | 15.30 | 7.42 | 0.187022E+10 | 2745.42 | 15.30 | 7.42 | ||
Maximum of Months | 0.983079E+12 | 381913.40 | 30.83 | 19.06 | 0.229118E+10 | 3956.86 | 30.83 | 19.06 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.221336E+09 | 60396.98 | 02-JAN-05:11 | 4.00 |
February | 26227649.17 | 52633.78 | 13-FEB-06:03 | 8.00 |
March | 8472097.29 | 53574.89 | 27-MAR-05:03 | 2.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 25.15 |
November | 9567738.72 | 51902.57 | 24-NOV-06:02 | 3.17 |
December | 0.121360E+09 | 55569.22 | 18-DEC-05:11 | 4.00 |
Annual Sum or Average | 0.386963E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.52 | |
Maximum of Months | 0.221336E+09 | 60396.98 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 2755.13 | 32.14 | 07-DEC-06:04 | -0.7 |
Annual Sum or Average | 2755.13 | |||
Minimum of Months | 0.00 | 0.00 | -0.7 | |
Maximum of Months | 2755.13 | 32.14 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 1387506.15 | 5225.77 | 07-DEC-06:01 | -0.7 |
Annual Sum or Average | 1387506.15 | |||
Minimum of Months | 0.00 | 0.00 | -0.7 | |
Maximum of Months | 1387506.15 | 5225.77 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 74906937.39 | 14356.70 | 02-JAN-05:11 | 4.00 |
February | 35631728.59 | 11147.59 | 13-FEB-06:03 | 8.00 |
March | 37857617.44 | 13318.46 | 27-MAR-04:11 | 2.37 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 27954.33 | 232.95 | 26-OCT-05:04 | 7.17 |
November | 28388661.96 | 13260.95 | 24-NOV-05:11 | 3.67 |
December | 0.272556E+09 | 13731.96 | 18-DEC-05:11 | 4.00 |
Annual Sum or Average | 0.449369E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.37 | |
Maximum of Months | 0.272556E+09 | 14356.70 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 31564653.63 | 9437.16 | 02-JAN-05:11 | 4.00 |
February | 10991563.02 | 7874.48 | 13-FEB-06:03 | 8.00 |
March | 13777698.85 | 8326.85 | 27-MAR-05:03 | 2.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 25.15 |
November | 9036069.30 | 8440.26 | 24-NOV-06:02 | 3.17 |
December | 0.123225E+09 | 9039.71 | 07-DEC-05:01 | -1.1 |
Annual Sum or Average | 0.188595E+09 | |||
Minimum of Months | 0.00 | 0.00 | -1.1 | |
Maximum of Months | 0.123225E+09 | 9437.16 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9353202.10 | 12931.61 | 02-JAN-06:03 | 4.33 |
February | 6013000.07 | 10786.17 | 13-FEB-06:03 | 8.00 |
March | 7841703.55 | 11718.70 | 27-MAR-05:03 | 2.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 25.15 |
November | 509706.00 | 3147.08 | 24-NOV-06:02 | 3.17 |
December | 56080243.52 | 13770.32 | 07-DEC-06:01 | -0.7 |
Annual Sum or Average | 79797855.24 | |||
Minimum of Months | 0.00 | 0.00 | -0.7 | |
Maximum of Months | 56080243.52 | 13770.32 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 14018340.99 | 8179.49 | 02-JAN-06:03 | 4.33 |
February | 2756931.54 | 4612.44 | 13-FEB-06:03 | 8.00 |
March | 3544812.01 | 7275.01 | 27-MAR-05:03 | 2.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 25.15 |
November | 3821022.01 | 8167.14 | 24-NOV-06:02 | 3.17 |
December | 77259774.40 | 8461.58 | 16-DEC-06:02 | 1.83 |
Annual Sum or Average | 0.101401E+09 | |||
Minimum of Months | 0.00 | 0.00 | 1.83 | |
Maximum of Months | 77259774.40 | 8461.58 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.556423E+09 | 17818.12 | 02-JAN-05:11 | 4.00 |
February | 0.485019E+09 | 16331.76 | 13-FEB-05:11 | 8.00 |
March | 0.311968E+09 | 16793.05 | 27-MAR-04:11 | 2.37 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 61186590.25 | 14575.35 | 26-OCT-05:02 | 7.17 |
November | 0.358346E+09 | 17090.89 | 24-NOV-05:11 | 3.67 |
December | 0.136554E+10 | 17864.85 | 18-DEC-05:11 | 4.00 |
Annual Sum or Average | 0.313848E+10 | |||
Minimum of Months | 0.00 | 0.00 | 2.37 | |
Maximum of Months | 0.136554E+10 | 17864.85 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.235955E+09 | 14168.92 | 02-JAN-05:11 | 4.00 |
February | 0.211224E+09 | 12614.11 | 13-FEB-05:11 | 8.00 |
March | 0.136836E+09 | 12687.69 | 27-MAR-04:11 | 2.37 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 22947177.43 | 11383.71 | 26-OCT-05:02 | 7.17 |
November | 0.140674E+09 | 13231.27 | 24-NOV-05:11 | 3.67 |
December | 0.604982E+09 | 14007.32 | 18-DEC-05:11 | 4.00 |
Annual Sum or Average | 0.135262E+10 | |||
Minimum of Months | 0.00 | 0.00 | 2.37 | |
Maximum of Months | 0.604982E+09 | 14168.92 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121900E+09 | 18351.54 | 02-JAN-05:11 | 4.00 |
February | 0.177230E+09 | 17844.45 | 13-FEB-05:11 | 8.00 |
March | 0.165343E+09 | 17172.06 | 27-MAR-04:11 | 2.37 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 10427543.44 | 10680.40 | 26-OCT-05:02 | 7.17 |
November | 86730442.56 | 17061.97 | 24-NOV-05:11 | 3.67 |
December | 0.508381E+09 | 18058.51 | 18-DEC-05:11 | 4.00 |
Annual Sum or Average | 0.107001E+10 | |||
Minimum of Months | 0.00 | 0.00 | 2.37 | |
Maximum of Months | 0.508381E+09 | 18351.54 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120658E+09 | 12505.02 | 02-JAN-05:11 | 4.00 |
February | 0.127112E+09 | 10873.10 | 13-FEB-05:11 | 8.00 |
March | 71459111.20 | 10616.85 | 27-MAR-04:11 | 2.37 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 6656258.63 | 7534.40 | 26-OCT-05:02 | 7.17 |
November | 78245815.23 | 11242.24 | 24-NOV-05:11 | 3.67 |
December | 0.452152E+09 | 12227.06 | 18-DEC-05:11 | 4.00 |
Annual Sum or Average | 0.856283E+09 | |||
Minimum of Months | 0.00 | 0.00 | 2.37 | |
Maximum of Months | 0.452152E+09 | 12505.02 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 76517198.72 | 8569.67 | 02-JAN-05:11 | 4.00 |
February | 64587903.36 | 9268.51 | 13-FEB-05:11 | 8.00 |
March | 69282091.78 | 8534.65 | 27-MAR-04:11 | 2.37 |
April | 0.101323E+09 | 9528.04 | 30-APR-16:01 | 32.83 |
May | 80120977.12 | 8674.87 | 26-MAY-04:12 | 21.00 |
June | 93686018.88 | 8248.37 | 25-JUN-17:31 | 38.00 |
July | 0.143764E+09 | 8863.72 | 22-JUL-17:41 | 38.00 |
August | 0.160119E+09 | 9932.90 | 27-AUG-15:42 | 40.00 |
September | 0.153950E+09 | 7440.33 | 21-SEP-04:12 | 21.07 |
October | 0.116511E+09 | 8399.41 | 23-OCT-04:12 | 11.00 |
November | 99953173.28 | 9834.63 | 02-NOV-04:12 | 15.33 |
December | 0.125114E+09 | 10607.37 | 18-DEC-05:11 | 4.00 |
Annual Sum or Average | 0.128493E+10 | |||
Minimum of Months | 64587903.36 | 7440.33 | 2.37 | |
Maximum of Months | 0.160119E+09 | 10607.37 | 40.00 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.282831E+09 | 7788.93 | 01-JAN-13:13 | 14.13 |
February | 0.113359E+09 | 5650.71 | 20-FEB-16:03 | 17.83 |
March | 44202770.99 | 5130.63 | 06-MAR-06:03 | 11.87 |
April | 49974878.48 | 7948.60 | 02-APR-16:01 | 31.00 |
May | 47637311.89 | 8793.77 | 07-MAY-16:21 | 36.00 |
June | 47911142.54 | 8883.84 | 04-JUN-15:51 | 38.00 |
July | 61885167.12 | 9108.44 | 30-JUL-16:51 | 38.00 |
August | 48339689.84 | 9030.95 | 13-AUG-14:51 | 38.00 |
September | 41437321.12 | 6639.49 | 04-SEP-15:41 | 31.60 |
October | 49462282.79 | 7914.47 | 15-OCT-15:41 | 31.00 |
November | 51420648.14 | 7648.20 | 26-NOV-16:23 | 18.50 |
December | 0.214908E+09 | 6212.37 | 25-DEC-16:02 | 25.67 |
Annual Sum or Average | 0.105337E+10 | |||
Minimum of Months | 41437321.12 | 5130.63 | 11.87 | |
Maximum of Months | 0.282831E+09 | 9108.44 | 38.00 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.168798E+10 | 16888.94 | 02-JAN-06:03 | 4.33 |
February | 0.136535E+10 | 8269.32 | 13-FEB-06:03 | 8.00 |
March | 0.122892E+10 | 12853.89 | 20-MAR-05:03 | 11.18 |
April | 0.315846E+09 | 14182.39 | 27-APR-05:03 | 12.00 |
May | 0.126382E+09 | 12669.56 | 01-MAY-04:12 | 12.33 |
June | 41367467.83 | 10594.81 | 05-JUN-04:01 | 23.83 |
July | 31980313.04 | 11997.25 | 03-JUL-04:12 | 20.67 |
August | 33230137.87 | 9479.17 | 24-AUG-04:12 | 20.67 |
September | 42099835.41 | 11118.28 | 22-SEP-05:02 | 17.10 |
October | 0.649032E+09 | 13218.01 | 18-OCT-05:03 | 15.83 |
November | 0.109910E+10 | 11698.50 | 24-NOV-06:02 | 3.17 |
December | 0.260425E+10 | 15522.89 | 18-DEC-06:03 | 3.83 |
Annual Sum or Average | 0.922554E+10 | |||
Minimum of Months | 31980313.04 | 8269.32 | 3.17 | |
Maximum of Months | 0.260425E+10 | 16888.94 | 23.83 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9727521.53 | 380.70 | 02-JAN-01:15 | 3.33 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 9727521.53 | |||
Minimum of Months | 0.00 | 0.00 | 3.33 | |
Maximum of Months | 9727521.53 | 380.70 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 79178773.39 | 594.67 | 01-JAN-02:40 | 4.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 79178773.39 | |||
Minimum of Months | 0.00 | 0.00 | 4.00 | |
Maximum of Months | 79178773.39 | 594.67 | 29.40 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 4.27 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 11.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 11.85 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15.28 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 19.10 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 25.83 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 27.73 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 29.40 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 26.22 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 25.15 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 17.23 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 9.20 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.27 | |
Maximum of Months | 0.00 | 0.00 | 29.40 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180249E+11 | 19402.09 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.163527E+11 | 19402.09 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.194806E+11 | 19402.09 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.173504E+11 | 19402.09 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.187528E+11 | 19402.09 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.186803E+11 | 19402.09 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.174228E+11 | 19402.09 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.194803E+11 | 19402.09 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.173504E+11 | 19402.09 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.180252E+11 | 19402.09 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.178272E+11 | 19402.09 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.174231E+11 | 19402.09 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.216171E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.163527E+11 | 19402.09 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.194806E+11 | 19402.09 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.130047E+10 | 2187.81 | 20-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.114044E+10 | 1906.53 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.125595E+10 | 1906.53 | 21-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.106693E+10 | 1524.25 | 04-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.111987E+10 | 1141.96 | 25-MAY-12:20 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.109079E+10 | 1040.96 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.103658E+10 | 1242.97 | 10-JUL-15:50 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.120056E+10 | 1906.53 | 04-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.109722E+10 | 1524.25 | 05-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.123022E+10 | 2187.81 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.126197E+10 | 2187.81 | 02-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.128798E+10 | 2187.81 | 01-DEC-16:19 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.140890E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.103658E+10 | 1040.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.130047E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.787380E+09 | 1409.91 | 20-JAN-16:49 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.708388E+09 | 1228.64 | 07-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.794402E+09 | 982.28 | 02-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.680028E+09 | 670.83 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.725979E+09 | 735.93 | 25-MAY-15:20 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.709833E+09 | 670.83 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.675122E+09 | 801.02 | 10-JUL-15:39 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.769602E+09 | 1228.64 | 04-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.699066E+09 | 801.02 | 29-SEP-14:30 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.754954E+09 | 982.28 | 24-OCT-15:39 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.779998E+09 | 1409.91 | 28-NOV-16:19 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.784173E+09 | 1409.91 | 01-DEC-16:19 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.886892E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.675122E+09 | 670.83 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.794402E+09 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118614E+10 | 2187.86 | 20-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.107594E+10 | 1906.57 | 10-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.122423E+10 | 1906.57 | 21-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.107048E+10 | 1524.28 | 04-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.113982E+10 | 1141.99 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.111664E+10 | 1141.99 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.106058E+10 | 1524.28 | 13-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.120883E+10 | 1906.57 | 04-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.108656E+10 | 1524.28 | 18-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.114589E+10 | 1805.57 | 27-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.117574E+10 | 2187.86 | 28-NOV-16:30 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.117194E+10 | 2187.86 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.136628E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.106058E+10 | 1141.99 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.122423E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.809921E+09 | 1409.91 | 20-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.718437E+09 | 1228.64 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.803069E+09 | 1228.64 | 16-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.691378E+09 | 982.28 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.732480E+09 | 801.02 | 26-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.714851E+09 | 735.93 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.680821E+09 | 982.28 | 13-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.779481E+09 | 1228.64 | 04-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.707190E+09 | 1228.64 | 19-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.772085E+09 | 1409.91 | 27-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.785875E+09 | 1409.91 | 02-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.794939E+09 | 1409.91 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.899053E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.680821E+09 | 735.93 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.809921E+09 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.129010E+10 | 2187.81 | 20-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.113271E+10 | 1906.53 | 02-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.125145E+10 | 1906.53 | 21-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.106478E+10 | 1524.25 | 04-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.111900E+10 | 1141.96 | 26-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.109012E+10 | 1040.96 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.103543E+10 | 1141.96 | 10-JUL-15:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.119790E+10 | 1906.53 | 04-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.109369E+10 | 1524.25 | 05-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.122161E+10 | 2187.81 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.125416E+10 | 2187.81 | 02-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.127624E+10 | 2187.81 | 01-DEC-16:19 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.140272E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.103543E+10 | 1040.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.129010E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.785246E+09 | 1409.91 | 20-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.705721E+09 | 1228.64 | 07-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.793134E+09 | 982.28 | 02-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.679743E+09 | 670.83 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.725284E+09 | 735.93 | 25-MAY-15:20 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.709415E+09 | 670.83 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.674070E+09 | 801.02 | 10-JUL-15:50 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.768569E+09 | 1228.64 | 04-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.698200E+09 | 801.02 | 29-SEP-14:30 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.752769E+09 | 982.28 | 24-OCT-15:39 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.777807E+09 | 1409.91 | 28-NOV-16:19 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.781874E+09 | 1409.91 | 01-DEC-16:19 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.885183E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.674070E+09 | 670.83 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.793134E+09 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118577E+10 | 2187.86 | 20-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.107457E+10 | 1906.57 | 10-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.122220E+10 | 1906.57 | 21-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.106875E+10 | 1524.28 | 04-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.113774E+10 | 1141.99 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.111415E+10 | 1141.99 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.105716E+10 | 1524.28 | 27-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.120574E+10 | 1906.57 | 04-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.108512E+10 | 1524.28 | 18-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.114270E+10 | 1805.57 | 27-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.117394E+10 | 2187.86 | 28-NOV-16:30 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.117137E+10 | 2187.86 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.136392E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.105716E+10 | 1141.99 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.122220E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.806583E+09 | 1409.91 | 20-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.715489E+09 | 1228.64 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.800276E+09 | 1228.64 | 16-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.689489E+09 | 982.28 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.730898E+09 | 801.02 | 26-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.713799E+09 | 735.93 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.678609E+09 | 982.28 | 27-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.777423E+09 | 1228.64 | 04-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.705785E+09 | 1228.64 | 29-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.768899E+09 | 1409.91 | 27-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.784152E+09 | 1409.91 | 02-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.791861E+09 | 1409.91 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.896326E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.678609E+09 | 735.93 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.806583E+09 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.129002E+10 | 2187.81 | 20-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.113240E+10 | 1906.53 | 02-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.125145E+10 | 1906.53 | 21-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.106478E+10 | 1524.25 | 04-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.111899E+10 | 1141.96 | 26-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.109012E+10 | 1040.96 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.103542E+10 | 1141.96 | 10-JUL-15:30 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.119790E+10 | 1906.53 | 04-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.109356E+10 | 1524.25 | 05-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.122154E+10 | 2187.81 | 31-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.125399E+10 | 2187.81 | 02-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.127618E+10 | 2187.81 | 01-DEC-16:19 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.140263E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.103542E+10 | 1040.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.129002E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.785242E+09 | 1409.91 | 20-JAN-16:00 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.705721E+09 | 1228.64 | 07-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.793042E+09 | 982.28 | 02-MAR-16:00 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.679741E+09 | 670.83 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.725258E+09 | 735.93 | 25-MAY-15:20 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.709393E+09 | 670.83 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.673995E+09 | 801.02 | 10-JUL-15:50 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.768481E+09 | 1228.64 | 04-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.698171E+09 | 801.02 | 29-SEP-14:30 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.752730E+09 | 982.28 | 24-OCT-15:39 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.777724E+09 | 1409.91 | 28-NOV-16:19 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.781835E+09 | 1409.91 | 01-DEC-16:19 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.885133E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.673995E+09 | 670.83 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.793042E+09 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.118577E+10 | 2187.86 | 20-JAN-16:00 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.107431E+10 | 1906.57 | 10-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.122217E+10 | 1906.57 | 21-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.106867E+10 | 1524.28 | 04-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.113773E+10 | 1141.99 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.111411E+10 | 1141.99 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.105715E+10 | 1524.28 | 27-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.120557E+10 | 1906.57 | 04-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.108504E+10 | 1524.28 | 18-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.114270E+10 | 1805.57 | 27-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.117393E+10 | 2187.86 | 28-NOV-16:30 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.117137E+10 | 2187.86 | 01-DEC-16:30 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.136385E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.105715E+10 | 1141.99 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.122217E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.806544E+09 | 1409.91 | 20-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.715489E+09 | 1228.64 | 02-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.800198E+09 | 1228.64 | 16-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.689437E+09 | 982.28 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.730885E+09 | 801.02 | 26-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.713802E+09 | 735.93 | 01-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.678552E+09 | 982.28 | 27-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.777332E+09 | 1228.64 | 04-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.705744E+09 | 1228.64 | 29-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.768899E+09 | 1409.91 | 27-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.784111E+09 | 1409.91 | 02-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.791861E+09 | 1409.91 | 01-DEC-16:30 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.896285E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.678552E+09 | 735.93 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.806544E+09 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.522764E+10 | 5470.56 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.474186E+10 | 5470.56 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.563465E+10 | 5470.56 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.503289E+10 | 5470.56 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.543115E+10 | 5470.56 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.540489E+10 | 5470.56 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.505915E+10 | 5470.56 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.563465E+10 | 5470.56 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.503289E+10 | 5470.56 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.522764E+10 | 5470.56 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.516637E+10 | 5470.56 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.505915E+10 | 5470.56 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.626529E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.474186E+10 | 5470.56 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.563465E+10 | 5470.56 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.180249E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.163527E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.194806E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.173504E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.187528E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.186803E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.174228E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.194803E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.173504E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.180252E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.178272E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.174231E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.216171E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.163527E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.194806E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.130047E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 523622.11 | 0.149854E+09 |
February | 0.136985E+10 | 0.114044E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119246E+09 |
March | 0.163685E+10 | 0.125595E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1321510.96 | 0.152947E+09 |
April | 0.145243E+10 | 0.106693E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23565519.92 | 47933584.16 |
May | 0.157338E+10 | 0.111987E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44624550.78 | 32725568.54 |
June | 0.156900E+10 | 0.109079E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80390649.56 | 8973069.32 |
July | 0.145680E+10 | 0.103658E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78765908.50 | 7973785.67 |
August | 0.163685E+10 | 0.120056E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54801555.75 | 12082917.72 |
September | 0.145243E+10 | 0.109722E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41183046.35 | 22480215.05 |
October | 0.150991E+10 | 0.123022E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14962693.45 | 78765314.09 |
November | 0.149516E+10 | 0.126197E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1320749.42 | 0.136837E+09 |
December | 0.145680E+10 | 0.128798E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96152.72 | 0.146515E+09 |
Annual Sum or Average | 0.181194E+11 | 0.140890E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341556E+09 | 0.916333E+09 |
Minimum of Months | 0.136985E+10 | 0.103658E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7973785.67 |
Maximum of Months | 0.163685E+10 | 0.130047E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80390649.56 | 0.152947E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.787380E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 325291.75 | 0.101369E+09 |
February | 0.882782E+09 | 0.708388E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78938993.59 |
March | 0.105485E+10 | 0.794402E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 907960.81 | 0.100783E+09 |
April | 0.936002E+09 | 0.680028E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16165353.33 | 30896759.59 |
May | 0.101394E+10 | 0.725979E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29680615.68 | 22240390.29 |
June | 0.101113E+10 | 0.709833E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54760269.97 | 5413984.66 |
July | 0.938820E+09 | 0.675122E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54298703.33 | 4482388.42 |
August | 0.105485E+10 | 0.769602E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37887251.48 | 6717248.21 |
September | 0.936002E+09 | 0.699066E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27996813.41 | 14337402.12 |
October | 0.973041E+09 | 0.754954E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9983197.90 | 52209750.59 |
November | 0.963541E+09 | 0.779998E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 854572.62 | 90098193.70 |
December | 0.938820E+09 | 0.784173E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78030.06 | 95982094.64 |
Annual Sum or Average | 0.116768E+11 | 0.886892E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232938E+09 | 0.603470E+09 |
Minimum of Months | 0.882782E+09 | 0.675122E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4482388.42 |
Maximum of Months | 0.105485E+10 | 0.794402E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54760269.97 | 0.101369E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.118614E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 405180.60 | 0.162391E+09 |
February | 0.136988E+10 | 0.107594E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122195E+09 |
March | 0.163688E+10 | 0.122423E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1197475.96 | 0.156038E+09 |
April | 0.145246E+10 | 0.107048E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22290672.12 | 49017045.79 |
May | 0.157341E+10 | 0.113982E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44763985.49 | 32010326.05 |
June | 0.156904E+10 | 0.111664E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81986075.02 | 8045573.35 |
July | 0.145684E+10 | 0.106058E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80138166.62 | 7034978.08 |
August | 0.163688E+10 | 0.120883E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55106434.56 | 11174547.79 |
September | 0.145246E+10 | 0.108656E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40215442.11 | 22941846.76 |
October | 0.150994E+10 | 0.114589E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13574389.01 | 83733593.79 |
November | 0.149520E+10 | 0.117574E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 725379.37 | 0.145036E+09 |
December | 0.145684E+10 | 0.117194E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34550.80 | 0.153645E+09 |
Annual Sum or Average | 0.181198E+11 | 0.136628E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340438E+09 | 0.953263E+09 |
Minimum of Months | 0.136988E+10 | 0.106058E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7034978.08 |
Maximum of Months | 0.163688E+10 | 0.122423E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81986075.02 | 0.162391E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.809921E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 304917.24 | 0.109123E+09 |
February | 0.882782E+09 | 0.718437E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87837778.49 |
March | 0.105485E+10 | 0.803069E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 780383.43 | 0.116479E+09 |
April | 0.936002E+09 | 0.691378E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13636584.96 | 39881430.04 |
May | 0.101394E+10 | 0.732480E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28565038.01 | 24579107.37 |
June | 0.101113E+10 | 0.714851E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53657079.78 | 5974301.81 |
July | 0.938820E+09 | 0.680821E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 52273481.00 | 5469631.52 |
August | 0.105485E+10 | 0.779481E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35737352.50 | 8799755.18 |
September | 0.936002E+09 | 0.707190E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28097531.89 | 14468032.27 |
October | 0.973041E+09 | 0.772085E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9664783.53 | 59380781.47 |
November | 0.963541E+09 | 0.785875E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 533888.14 | 0.105122E+09 |
December | 0.938820E+09 | 0.794939E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26399.12 | 0.111873E+09 |
Annual Sum or Average | 0.116768E+11 | 0.899053E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223277E+09 | 0.688989E+09 |
Minimum of Months | 0.882782E+09 | 0.680821E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5469631.52 |
Maximum of Months | 0.105485E+10 | 0.809921E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53657079.78 | 0.116479E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.129010E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3071551.70 | 0.297525E+09 |
February | 0.136985E+10 | 0.113271E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241149E+09 |
March | 0.163685E+10 | 0.125145E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3205744.40 | 0.317694E+09 |
April | 0.145243E+10 | 0.106478E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58668646.34 | 0.107980E+09 |
May | 0.157338E+10 | 0.111900E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106575E+09 | 70093403.51 |
June | 0.156900E+10 | 0.109012E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190973E+09 | 20140555.14 |
July | 0.145680E+10 | 0.103543E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189214E+09 | 17447828.51 |
August | 0.163685E+10 | 0.119790E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134299E+09 | 24105342.83 |
September | 0.145243E+10 | 0.109369E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98671155.13 | 47081752.89 |
October | 0.150991E+10 | 0.122161E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38755050.91 | 0.161786E+09 |
November | 0.149516E+10 | 0.125416E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5311050.15 | 0.273516E+09 |
December | 0.145680E+10 | 0.127624E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1443311.77 | 0.288220E+09 |
Annual Sum or Average | 0.181194E+11 | 0.140272E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.830188E+09 | 0.186674E+10 |
Minimum of Months | 0.136985E+10 | 0.103543E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17447828.51 |
Maximum of Months | 0.163685E+10 | 0.129010E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190973E+09 | 0.317694E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.785246E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1181032.59 | 0.210360E+09 |
February | 0.649041E+09 | 0.705721E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168030E+09 |
March | 0.773965E+09 | 0.793134E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1965896.21 | 0.222067E+09 |
April | 0.688021E+09 | 0.679743E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36326100.83 | 78490233.12 |
May | 0.744847E+09 | 0.725284E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68950570.89 | 50084606.59 |
June | 0.742030E+09 | 0.709415E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129141E+09 | 13709054.82 |
July | 0.690839E+09 | 0.674070E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128039E+09 | 12286345.91 |
August | 0.773965E+09 | 0.768569E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88844786.90 | 17561478.60 |
September | 0.688021E+09 | 0.698200E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65301642.64 | 33394728.82 |
October | 0.715730E+09 | 0.752769E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23853279.19 | 0.114842E+09 |
November | 0.708685E+09 | 0.777807E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2346120.32 | 0.191533E+09 |
December | 0.690839E+09 | 0.781874E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 587488.07 | 0.200384E+09 |
Annual Sum or Average | 0.858171E+10 | 0.885183E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546537E+09 | 0.131274E+10 |
Minimum of Months | 0.649041E+09 | 0.674070E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12286345.91 |
Maximum of Months | 0.773965E+09 | 0.793134E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129141E+09 | 0.222067E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.118577E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 745186.26 | 0.367475E+09 |
February | 0.136988E+10 | 0.107457E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272801E+09 |
March | 0.163688E+10 | 0.122220E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2639246.08 | 0.348701E+09 |
April | 0.145246E+10 | 0.106875E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51425433.33 | 0.116744E+09 |
May | 0.157341E+10 | 0.113774E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104995E+09 | 70966654.18 |
June | 0.156904E+10 | 0.111415E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194645E+09 | 19154380.93 |
July | 0.145684E+10 | 0.105716E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190684E+09 | 16971383.12 |
August | 0.163688E+10 | 0.120574E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131268E+09 | 25775574.50 |
September | 0.145246E+10 | 0.108512E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92684187.27 | 53799834.45 |
October | 0.150994E+10 | 0.114270E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31052982.71 | 0.190555E+09 |
November | 0.149520E+10 | 0.117394E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1493418.70 | 0.324391E+09 |
December | 0.145684E+10 | 0.117137E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63904.71 | 0.341899E+09 |
Annual Sum or Average | 0.181198E+11 | 0.136392E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.801696E+09 | 0.214924E+10 |
Minimum of Months | 0.136988E+10 | 0.105716E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16971383.12 |
Maximum of Months | 0.163688E+10 | 0.122220E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194645E+09 | 0.367475E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.806583E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1122550.82 | 0.219907E+09 |
February | 0.882782E+09 | 0.715489E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171943E+09 |
March | 0.105485E+10 | 0.800276E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1836417.51 | 0.229724E+09 |
April | 0.936002E+09 | 0.689489E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32940076.36 | 85758831.22 |
May | 0.101394E+10 | 0.730898E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66185518.28 | 54684260.03 |
June | 0.101113E+10 | 0.713799E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124819E+09 | 16042492.31 |
July | 0.938820E+09 | 0.678609E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122529E+09 | 14444545.57 |
August | 0.105485E+10 | 0.777423E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85319318.32 | 19934336.97 |
September | 0.936002E+09 | 0.705785E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63242360.39 | 36523336.52 |
October | 0.973041E+09 | 0.768899E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23186871.01 | 0.120293E+09 |
November | 0.963541E+09 | 0.784152E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2255913.37 | 0.200743E+09 |
December | 0.938820E+09 | 0.791861E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 296488.81 | 0.208340E+09 |
Annual Sum or Average | 0.116768E+11 | 0.896326E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523733E+09 | 0.137834E+10 |
Minimum of Months | 0.882782E+09 | 0.678609E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14444545.57 |
Maximum of Months | 0.105485E+10 | 0.806583E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124819E+09 | 0.229724E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.129002E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5691187.13 | 0.330471E+09 |
February | 0.136985E+10 | 0.113240E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268808E+09 |
March | 0.163685E+10 | 0.125145E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3784855.68 | 0.365699E+09 |
April | 0.145243E+10 | 0.106478E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69344646.09 | 0.131013E+09 |
May | 0.157338E+10 | 0.111899E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127648E+09 | 86382022.74 |
June | 0.156900E+10 | 0.109012E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232335E+09 | 25662383.05 |
July | 0.145680E+10 | 0.103542E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228412E+09 | 22921118.25 |
August | 0.163685E+10 | 0.119790E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162297E+09 | 30650014.59 |
September | 0.145243E+10 | 0.109356E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118816E+09 | 60197042.36 |
October | 0.150991E+10 | 0.122154E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48048240.12 | 0.187315E+09 |
November | 0.149516E+10 | 0.125399E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8413281.45 | 0.305605E+09 |
December | 0.145680E+10 | 0.127618E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3257811.37 | 0.320955E+09 |
Annual Sum or Average | 0.181194E+11 | 0.140263E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100805E+10 | 0.213568E+10 |
Minimum of Months | 0.136985E+10 | 0.103542E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22921118.25 |
Maximum of Months | 0.163685E+10 | 0.129002E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232335E+09 | 0.365699E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.785242E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2030864.69 | 0.237674E+09 |
February | 0.882782E+09 | 0.705721E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190986E+09 |
March | 0.105485E+10 | 0.793042E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2263833.56 | 0.260567E+09 |
April | 0.936002E+09 | 0.679741E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42762847.46 | 96993148.53 |
May | 0.101394E+10 | 0.725258E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82249622.40 | 62352082.27 |
June | 0.101113E+10 | 0.709393E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156488E+09 | 17602547.14 |
July | 0.938820E+09 | 0.673995E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153846E+09 | 16205777.86 |
August | 0.105485E+10 | 0.768481E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107072E+09 | 22446238.27 |
September | 0.936002E+09 | 0.698171E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78599869.46 | 42774885.76 |
October | 0.973041E+09 | 0.752730E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28745492.87 | 0.136188E+09 |
November | 0.963541E+09 | 0.777724E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3392916.60 | 0.217655E+09 |
December | 0.938820E+09 | 0.781835E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1173604.08 | 0.225143E+09 |
Annual Sum or Average | 0.116768E+11 | 0.885133E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.658625E+09 | 0.152659E+10 |
Minimum of Months | 0.882782E+09 | 0.673995E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16205777.86 |
Maximum of Months | 0.105485E+10 | 0.793042E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156488E+09 | 0.260567E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.118577E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1037639.78 | 0.422859E+09 |
February | 0.136988E+10 | 0.107431E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311197E+09 |
March | 0.163688E+10 | 0.122217E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3083321.08 | 0.408833E+09 |
April | 0.145246E+10 | 0.106867E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61704805.99 | 0.142387E+09 |
May | 0.157341E+10 | 0.113773E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126423E+09 | 87266321.55 |
June | 0.156904E+10 | 0.111411E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236607E+09 | 24300125.03 |
July | 0.145684E+10 | 0.105715E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230520E+09 | 22243615.09 |
August | 0.163688E+10 | 0.120557E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159225E+09 | 32689568.32 |
September | 0.145246E+10 | 0.108504E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112383E+09 | 68585719.77 |
October | 0.150994E+10 | 0.114270E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37732223.95 | 0.226194E+09 |
November | 0.149520E+10 | 0.117393E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1897185.00 | 0.374762E+09 |
December | 0.145684E+10 | 0.117137E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86640.64 | 0.391381E+09 |
Annual Sum or Average | 0.181198E+11 | 0.136385E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.970700E+09 | 0.251270E+10 |
Minimum of Months | 0.136988E+10 | 0.105715E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22243615.09 |
Maximum of Months | 0.163688E+10 | 0.122217E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236607E+09 | 0.422859E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.806544E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1756921.49 | 0.252132E+09 |
February | 0.882782E+09 | 0.715489E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197915E+09 |
March | 0.105485E+10 | 0.800198E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2218706.69 | 0.270844E+09 |
April | 0.936002E+09 | 0.689437E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39856257.51 | 0.104851E+09 |
May | 0.101394E+10 | 0.730885E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80441724.47 | 67335258.34 |
June | 0.101113E+10 | 0.713802E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152686E+09 | 20086323.92 |
July | 0.938820E+09 | 0.678552E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149470E+09 | 18532900.06 |
August | 0.105485E+10 | 0.777332E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104167E+09 | 25004273.62 |
September | 0.936002E+09 | 0.705744E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77103380.50 | 45983593.98 |
October | 0.973041E+09 | 0.768899E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28528934.68 | 0.142574E+09 |
November | 0.963541E+09 | 0.784111E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3206386.85 | 0.231558E+09 |
December | 0.938820E+09 | 0.791861E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 621460.26 | 0.238877E+09 |
Annual Sum or Average | 0.116768E+11 | 0.896285E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.640057E+09 | 0.161569E+10 |
Minimum of Months | 0.882782E+09 | 0.678552E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18532900.06 |
Maximum of Months | 0.105485E+10 | 0.806544E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152686E+09 | 0.270844E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.522764E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.474186E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.563465E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.503289E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.543115E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.540489E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.505915E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.563465E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.503289E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.522764E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.516637E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.505915E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.626529E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.474186E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.563465E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 540787.28 | 0.340201E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263248E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1814632.83 | 0.336923E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42649926.62 | 0.109596E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83461024.86 | 70256320.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152790E+09 | 20485917.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148890E+09 | 18727996.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100805E+09 | 28791106.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75922390.65 | 48849818.86 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25665615.57 | 0.176203E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1456328.74 | 0.305029E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37307.81 | 0.326539E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.634032E+09 | 0.204485E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18727996.51 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152790E+09 | 0.340201E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1166718.79 | 0.565132E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446382E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3690941.13 | 0.577226E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82317318.10 | 0.191913E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157884E+09 | 0.118874E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291494E+09 | 31864800.40 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294489E+09 | 26822177.28 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201289E+09 | 40998418.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146758E+09 | 76237905.32 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51923356.90 | 0.297923E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4186239.41 | 0.514005E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 524828.50 | 0.544616E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123572E+10 | 0.343200E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26822177.28 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294489E+09 | 0.577226E+09 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1131094.54 | 0.554735E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449429E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2286486.46 | 0.600668E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74694507.21 | 0.205317E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155609E+09 | 0.122155E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314247E+09 | 33787075.96 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304904E+09 | 30160872.03 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213171E+09 | 44163932.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151882E+09 | 86698286.95 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52598071.21 | 0.305884E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4397822.02 | 0.509468E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 706089.81 | 0.526841E+09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127563E+10 | 0.346931E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30160872.03 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314247E+09 | 0.600668E+09 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 19402.09 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 19402.09 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 19402.09 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 19402.09 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 19402.09 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 19402.09 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 19402.09 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 19402.09 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 19402.09 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 19402.09 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 19402.09 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 19402.09 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 19402.09 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 19402.09 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2187.81 | 20-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.85 | 29-JAN-16:00 | 338.25 | 01-JAN-01:00 |
February | 2010.79 | 01-FEB-10:09 | 1906.53 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 343.79 | 02-FEB-23:00 |
March | 2010.79 | 01-MAR-10:09 | 1906.53 | 21-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.34 | 18-MAR-17:10 | 296.70 | 28-MAR-04:00 |
April | 2010.79 | 03-APR-09:09 | 1524.25 | 04-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 176.87 | 30-APR-15:24 | 146.06 | 26-APR-21:20 |
May | 2010.79 | 01-MAY-09:09 | 1141.96 | 25-MAY-12:20 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 159.18 | 20-MAY-18:30 | 113.07 | 23-MAY-04:55 |
June | 2010.79 | 01-JUN-09:09 | 1040.96 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 259.15 | 17-JUN-17:10 | 62.71 | 13-JUN-04:20 |
July | 2010.79 | 03-JUL-09:09 | 1242.97 | 10-JUL-15:50 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 323.31 | 22-JUL-18:00 | 108.25 | 26-JUL-24:00 |
August | 2010.79 | 01-AUG-09:09 | 1906.53 | 04-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 292.40 | 13-AUG-16:00 | 160.78 | 05-AUG-17:35 |
September | 2010.79 | 01-SEP-09:09 | 1524.25 | 05-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.97 | 17-SEP-12:30 | 109.20 | 03-SEP-05:10 |
October | 2010.79 | 02-OCT-09:09 | 2187.81 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.09 | 01-OCT-14:38 | 293.47 | 22-OCT-14:00 |
November | 2010.79 | 01-NOV-09:09 | 2187.81 | 02-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.66 | 19-NOV-15:00 | 297.96 | 29-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 01-DEC-16:19 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.57 | 25-DEC-16:00 | 246.31 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.71 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 323.31 | 343.79 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 20-JAN-16:49 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.89 | 29-JAN-15:50 | 228.41 | 01-JAN-01:00 |
February | 1295.83 | 01-FEB-10:09 | 1228.64 | 07-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 226.94 | 02-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 982.28 | 02-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 20.10 | 18-MAR-17:10 | 194.84 | 28-MAR-04:00 |
April | 1295.83 | 03-APR-09:09 | 670.83 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 123.39 | 30-APR-15:30 | 138.70 | 16-APR-08:40 |
May | 1295.83 | 01-MAY-09:09 | 735.93 | 25-MAY-15:20 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.37 | 20-MAY-17:50 | 76.22 | 28-MAY-06:10 |
June | 1295.83 | 01-JUN-09:09 | 670.83 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.20 | 17-JUN-17:10 | 46.56 | 11-JUN-06:50 |
July | 1295.83 | 03-JUL-09:09 | 801.02 | 10-JUL-15:39 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 222.54 | 22-JUL-17:44 | 68.88 | 26-JUL-24:00 |
August | 1295.83 | 01-AUG-09:09 | 1228.64 | 04-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.82 | 13-AUG-16:00 | 105.80 | 05-AUG-17:35 |
September | 1295.83 | 01-SEP-09:09 | 801.02 | 29-SEP-14:30 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.33 | 17-SEP-12:30 | 69.56 | 03-SEP-05:10 |
October | 1295.83 | 02-OCT-09:09 | 982.28 | 24-OCT-15:39 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.20 | 01-OCT-14:38 | 201.53 | 22-OCT-14:00 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 28-NOV-16:19 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.67 | 19-NOV-15:00 | 194.08 | 29-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-16:19 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.24 | 25-DEC-16:00 | 160.78 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.56 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 222.54 | 228.41 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2187.86 | 20-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.95 | 31-JAN-14:00 | 337.08 | 01-JAN-01:00 |
February | 2010.83 | 01-FEB-10:09 | 1906.57 | 10-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 364.87 | 02-FEB-23:00 |
March | 2010.83 | 01-MAR-10:09 | 1906.57 | 21-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.95 | 15-MAR-13:00 | 295.35 | 28-MAR-04:00 |
April | 2010.83 | 03-APR-09:09 | 1524.28 | 04-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 171.00 | 30-APR-16:04 | 148.87 | 26-APR-21:20 |
May | 2010.83 | 01-MAY-09:09 | 1141.99 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.63 | 20-MAY-17:50 | 110.36 | 23-MAY-04:55 |
June | 2010.83 | 01-JUN-09:09 | 1141.99 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 259.86 | 17-JUN-17:10 | 59.55 | 13-JUN-04:20 |
July | 2010.83 | 03-JUL-09:09 | 1524.28 | 13-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 329.77 | 22-JUL-17:44 | 103.76 | 26-JUL-24:00 |
August | 2010.83 | 01-AUG-09:09 | 1906.57 | 04-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 292.40 | 13-AUG-16:00 | 162.49 | 05-AUG-17:35 |
September | 2010.83 | 01-SEP-09:09 | 1524.28 | 18-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 203.56 | 17-SEP-12:30 | 106.54 | 03-SEP-05:10 |
October | 2010.83 | 02-OCT-09:09 | 1805.57 | 27-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.52 | 01-OCT-14:35 | 327.57 | 22-OCT-14:00 |
November | 2010.83 | 01-NOV-09:09 | 2187.86 | 28-NOV-16:30 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.06 | 01-NOV-16:10 | 305.99 | 29-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 2187.86 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.74 | 21-DEC-15:00 | 249.78 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1141.99 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.55 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 329.77 | 364.87 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 20-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6.21 | 16-JAN-12:30 | 233.83 | 01-JAN-01:00 |
February | 1295.83 | 01-FEB-10:09 | 1228.64 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 259.25 | 02-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 1228.64 | 16-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.63 | 15-MAR-13:00 | 219.95 | 28-MAR-04:00 |
April | 1295.83 | 03-APR-09:09 | 982.28 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.30 | 30-APR-15:23 | 114.74 | 26-APR-21:20 |
May | 1295.83 | 01-MAY-09:09 | 801.02 | 26-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.80 | 20-MAY-17:50 | 80.68 | 01-MAY-04:50 |
June | 1295.83 | 01-JUN-09:09 | 735.93 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.71 | 17-JUN-17:10 | 44.09 | 13-JUN-04:20 |
July | 1295.83 | 03-JUL-09:09 | 982.28 | 13-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.45 | 22-JUL-18:00 | 79.68 | 26-JUL-24:00 |
August | 1295.83 | 01-AUG-09:09 | 1228.64 | 04-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.93 | 13-AUG-16:00 | 120.24 | 05-AUG-17:35 |
September | 1295.83 | 01-SEP-09:09 | 1228.64 | 19-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.34 | 17-SEP-12:30 | 65.15 | 03-SEP-05:17 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 27-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.64 | 01-OCT-14:38 | 219.64 | 22-OCT-14:00 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 02-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.76 | 01-NOV-16:00 | 225.10 | 29-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.52 | 21-DEC-15:00 | 181.80 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 735.93 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.09 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 215.45 | 259.25 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2187.81 | 20-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 71.88 | 16-JAN-12:00 | 559.85 | 01-JAN-01:00 |
February | 2010.79 | 01-FEB-10:09 | 1906.53 | 02-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 708.01 | 02-FEB-23:00 |
March | 2010.79 | 01-MAR-10:09 | 1906.53 | 21-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 73.69 | 18-MAR-17:02 | 615.48 | 28-MAR-04:00 |
April | 2010.79 | 03-APR-09:09 | 1524.25 | 04-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 426.14 | 30-APR-15:00 | 317.53 | 21-APR-05:00 |
May | 2010.79 | 01-MAY-09:09 | 1141.96 | 26-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 388.55 | 20-MAY-17:01 | 262.28 | 23-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 1040.96 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 597.70 | 17-JUN-17:03 | 140.68 | 13-JUN-03:53 |
July | 2010.79 | 03-JUL-09:09 | 1141.96 | 10-JUL-15:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 760.08 | 22-JUL-17:44 | 216.52 | 26-JUL-24:00 |
August | 2010.79 | 01-AUG-09:09 | 1906.53 | 04-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 679.11 | 13-AUG-16:00 | 315.58 | 05-AUG-18:00 |
September | 2010.79 | 01-SEP-09:09 | 1524.25 | 05-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 473.75 | 17-SEP-12:10 | 232.07 | 03-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 2187.81 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 308.39 | 01-OCT-14:25 | 598.86 | 22-OCT-14:00 |
November | 2010.79 | 01-NOV-09:09 | 2187.81 | 02-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.85 | 19-NOV-14:50 | 602.68 | 29-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 01-DEC-16:19 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 71.59 | 25-DEC-15:52 | 511.92 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.68 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 760.08 | 708.01 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1409.91 | 20-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.23 | 29-JAN-16:00 | 392.76 | 01-JAN-01:00 |
February | 1239.33 | 01-FEB-08:09 | 1228.64 | 07-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 484.92 | 02-FEB-23:00 |
March | 1239.33 | 01-MAR-08:09 | 982.28 | 02-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 47.10 | 18-MAR-17:02 | 417.85 | 28-MAR-04:00 |
April | 1239.33 | 03-APR-07:10 | 670.83 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 287.44 | 30-APR-16:00 | 330.55 | 16-APR-08:50 |
May | 1239.33 | 01-MAY-07:10 | 735.93 | 25-MAY-15:20 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 276.29 | 20-MAY-18:30 | 175.05 | 23-MAY-05:00 |
June | 1239.33 | 01-JUN-07:10 | 670.83 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 402.26 | 17-JUN-17:03 | 101.98 | 11-JUN-06:10 |
July | 1239.33 | 03-JUL-07:10 | 801.02 | 10-JUL-15:50 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 522.81 | 22-JUL-18:00 | 147.92 | 26-JUL-24:00 |
August | 1239.33 | 01-AUG-07:10 | 1228.64 | 04-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 452.74 | 13-AUG-16:00 | 215.69 | 05-AUG-18:00 |
September | 1239.33 | 01-SEP-07:10 | 801.02 | 29-SEP-14:30 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 329.02 | 17-SEP-12:10 | 156.88 | 03-SEP-05:00 |
October | 1239.33 | 02-OCT-07:10 | 982.28 | 24-OCT-15:39 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 214.31 | 01-OCT-15:10 | 450.13 | 22-OCT-14:00 |
November | 1239.33 | 01-NOV-07:10 | 1409.91 | 28-NOV-16:19 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 99.10 | 19-NOV-15:10 | 408.44 | 29-NOV-02:00 |
December | 1239.33 | 01-DEC-08:09 | 1409.91 | 01-DEC-16:19 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.34 | 25-DEC-16:10 | 344.62 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.98 | |||||
Maximum of Months | 1239.33 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 522.81 | 484.92 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2187.86 | 20-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.53 | 31-JAN-15:00 | 700.06 | 01-JAN-01:00 |
February | 2010.83 | 01-FEB-10:09 | 1906.57 | 10-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 810.70 | 02-FEB-23:00 |
March | 2010.83 | 01-MAR-10:09 | 1906.57 | 21-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.93 | 15-MAR-13:00 | 648.40 | 28-MAR-04:00 |
April | 2010.83 | 03-APR-09:09 | 1524.28 | 04-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 390.93 | 30-APR-15:13 | 323.98 | 21-APR-05:00 |
May | 2010.83 | 01-MAY-09:09 | 1141.99 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 385.82 | 20-MAY-18:00 | 262.29 | 23-MAY-05:00 |
June | 2010.83 | 01-JUN-09:09 | 1141.99 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 601.67 | 17-JUN-17:03 | 138.31 | 13-JUN-03:53 |
July | 2010.83 | 03-JUL-09:09 | 1524.28 | 27-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 762.61 | 22-JUL-18:00 | 215.39 | 26-JUL-24:00 |
August | 2010.83 | 01-AUG-09:09 | 1906.57 | 04-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 679.11 | 13-AUG-16:00 | 329.48 | 05-AUG-18:00 |
September | 2010.83 | 01-SEP-09:09 | 1524.28 | 18-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 475.09 | 17-SEP-12:07 | 241.78 | 03-SEP-05:00 |
October | 2010.83 | 02-OCT-09:09 | 1805.57 | 27-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 297.59 | 01-OCT-14:23 | 750.42 | 22-OCT-14:00 |
November | 2010.83 | 01-NOV-09:09 | 2187.86 | 28-NOV-16:30 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.57 | 01-NOV-16:10 | 663.75 | 29-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 2187.86 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 21-DEC-15:00 | 552.27 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1141.99 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.31 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 762.61 | 810.70 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 20-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 43.09 | 16-JAN-12:20 | 432.43 | 01-JAN-01:00 |
February | 1295.83 | 01-FEB-10:09 | 1228.64 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 515.18 | 02-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 1228.64 | 16-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.62 | 15-MAR-13:00 | 438.22 | 28-MAR-04:00 |
April | 1295.83 | 03-APR-09:09 | 982.28 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 262.29 | 30-APR-15:13 | 233.44 | 26-APR-21:20 |
May | 1295.83 | 01-MAY-09:09 | 801.02 | 26-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 243.72 | 20-MAY-17:47 | 185.60 | 23-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 735.93 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 407.08 | 17-JUN-17:03 | 106.74 | 13-JUN-03:53 |
July | 1295.83 | 03-JUL-09:09 | 982.28 | 27-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 500.45 | 22-JUL-18:00 | 170.34 | 26-JUL-24:00 |
August | 1295.83 | 01-AUG-09:09 | 1228.64 | 04-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 452.74 | 13-AUG-16:00 | 225.84 | 05-AUG-18:00 |
September | 1295.83 | 01-SEP-09:09 | 1228.64 | 29-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 338.32 | 17-SEP-12:10 | 162.51 | 03-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 27-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.14 | 01-OCT-14:25 | 418.99 | 22-OCT-14:00 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 02-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.26 | 19-NOV-12:30 | 419.16 | 29-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.58 | 25-DEC-13:41 | 354.04 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 735.93 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.74 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 500.45 | 515.18 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2187.81 | 20-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 147.73 | 16-JAN-12:00 | 573.22 | 01-JAN-02:00 |
February | 2010.79 | 01-FEB-10:09 | 1906.53 | 02-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 815.36 | 02-FEB-23:00 |
March | 2010.79 | 01-MAR-10:09 | 1906.53 | 21-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 88.14 | 18-MAR-17:02 | 699.54 | 28-MAR-04:00 |
April | 2010.79 | 03-APR-09:09 | 1524.25 | 04-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 497.97 | 30-APR-15:40 | 378.48 | 26-APR-21:10 |
May | 2010.79 | 01-MAY-09:09 | 1141.96 | 26-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 458.76 | 20-MAY-17:01 | 312.35 | 23-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 1040.96 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 739.10 | 17-JUN-17:10 | 173.08 | 13-JUN-03:53 |
July | 2010.79 | 03-JUL-09:09 | 1141.96 | 10-JUL-15:30 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 925.17 | 22-JUL-17:43 | 277.82 | 26-JUL-24:00 |
August | 2010.79 | 01-AUG-09:09 | 1906.53 | 04-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 834.94 | 13-AUG-16:00 | 401.60 | 05-AUG-17:42 |
September | 2010.79 | 01-SEP-09:09 | 1524.25 | 05-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 584.93 | 17-SEP-12:10 | 299.74 | 03-SEP-05:00 |
October | 2010.79 | 02-OCT-09:09 | 2187.81 | 31-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 382.60 | 01-OCT-14:25 | 722.55 | 22-OCT-14:00 |
November | 2010.79 | 01-NOV-09:09 | 2187.81 | 02-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 288.72 | 19-NOV-12:52 | 687.57 | 29-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 01-DEC-16:19 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 113.42 | 25-DEC-16:00 | 607.91 | 07-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.08 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 925.17 | 815.36 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 20-JAN-16:00 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 54.67 | 16-JAN-14:00 | 396.24 | 01-JAN-01:00 |
February | 1295.83 | 01-FEB-10:09 | 1228.64 | 07-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 564.22 | 02-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 982.28 | 02-MAR-16:00 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 52.60 | 18-MAR-17:02 | 478.35 | 28-MAR-04:00 |
April | 1295.83 | 03-APR-09:09 | 670.83 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 358.98 | 30-APR-15:40 | 384.82 | 16-APR-08:30 |
May | 1295.83 | 01-MAY-09:09 | 735.93 | 25-MAY-15:20 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 321.78 | 20-MAY-18:30 | 209.42 | 23-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 670.83 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 496.13 | 17-JUN-17:10 | 123.81 | 25-JUN-06:00 |
July | 1295.83 | 03-JUL-09:09 | 801.02 | 10-JUL-15:50 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 634.52 | 22-JUL-17:44 | 190.13 | 26-JUL-24:00 |
August | 1295.83 | 01-AUG-09:09 | 1228.64 | 04-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 561.10 | 13-AUG-16:14 | 275.12 | 05-AUG-17:42 |
September | 1295.83 | 01-SEP-09:09 | 801.02 | 29-SEP-14:30 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 404.33 | 17-SEP-12:10 | 202.60 | 03-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 982.28 | 24-OCT-15:39 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 264.11 | 01-OCT-14:27 | 554.54 | 22-OCT-13:55 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 28-NOV-16:19 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 141.15 | 19-NOV-14:40 | 471.24 | 29-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-16:19 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 62.60 | 25-DEC-16:00 | 405.28 | 07-DEC-05:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.81 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 634.52 | 564.22 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2187.86 | 20-JAN-16:00 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.65 | 31-JAN-14:00 | 741.37 | 01-JAN-01:00 |
February | 2010.83 | 01-FEB-10:09 | 1906.57 | 10-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 944.07 | 02-FEB-23:00 |
March | 2010.83 | 01-MAR-10:09 | 1906.57 | 21-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 51.42 | 15-MAR-13:00 | 745.52 | 28-MAR-04:00 |
April | 2010.83 | 03-APR-09:09 | 1524.28 | 04-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 491.92 | 30-APR-14:54 | 395.02 | 26-APR-21:10 |
May | 2010.83 | 01-MAY-09:09 | 1141.99 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 456.22 | 20-MAY-17:01 | 312.18 | 23-MAY-05:00 |
June | 2010.83 | 01-JUN-09:09 | 1141.99 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 738.84 | 17-JUN-17:10 | 170.08 | 13-JUN-03:53 |
July | 2010.83 | 03-JUL-09:09 | 1524.28 | 27-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 942.93 | 22-JUL-17:44 | 276.23 | 26-JUL-24:00 |
August | 2010.83 | 01-AUG-09:09 | 1906.57 | 04-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 834.94 | 13-AUG-16:00 | 419.97 | 05-AUG-17:42 |
September | 2010.83 | 01-SEP-09:09 | 1524.28 | 18-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 583.88 | 17-SEP-12:10 | 311.88 | 03-SEP-05:00 |
October | 2010.83 | 02-OCT-09:09 | 1805.57 | 27-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 364.39 | 01-OCT-14:23 | 917.20 | 22-OCT-13:55 |
November | 2010.83 | 01-NOV-09:09 | 2187.86 | 28-NOV-16:30 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.36 | 01-NOV-16:00 | 771.78 | 29-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 2187.86 | 01-DEC-16:30 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.79 | 21-DEC-15:00 | 631.81 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1141.99 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.08 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 942.93 | 944.07 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 20-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 78.73 | 16-JAN-12:00 | 463.06 | 01-JAN-01:00 |
February | 1295.83 | 01-FEB-10:09 | 1228.64 | 02-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 599.85 | 02-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 1228.64 | 16-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.28 | 15-MAR-13:00 | 509.67 | 28-MAR-04:00 |
April | 1295.83 | 03-APR-09:09 | 982.28 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 325.67 | 30-APR-14:54 | 288.68 | 26-APR-21:20 |
May | 1295.83 | 01-MAY-09:09 | 801.02 | 26-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 299.02 | 20-MAY-17:47 | 222.61 | 23-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 735.93 | 01-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 495.66 | 17-JUN-17:10 | 131.34 | 13-JUN-03:53 |
July | 1295.83 | 03-JUL-09:09 | 982.28 | 27-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 615.23 | 22-JUL-18:00 | 217.93 | 26-JUL-24:00 |
August | 1295.83 | 01-AUG-09:09 | 1228.64 | 04-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 556.62 | 13-AUG-16:00 | 286.82 | 05-AUG-17:42 |
September | 1295.83 | 01-SEP-09:09 | 1228.64 | 29-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 413.07 | 17-SEP-12:10 | 208.03 | 03-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 27-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 261.26 | 01-OCT-14:25 | 517.54 | 22-OCT-14:00 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 02-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.38 | 19-NOV-12:40 | 486.94 | 29-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-16:30 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 44.51 | 25-DEC-13:51 | 409.37 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 735.93 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.34 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 615.23 | 599.85 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 5470.56 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 5470.56 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 5470.56 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 5470.56 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 5470.56 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 5470.56 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 5470.56 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 5470.56 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 5470.56 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 5470.56 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 5470.56 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 5470.56 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 5470.56 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.13 | 31-JAN-14:00 | 763.93 | 01-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 771.66 | 02-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.78 | 18-MAR-17:02 | 656.63 | 28-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 354.26 | 30-APR-15:10 | 324.95 | 21-APR-04:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.85 | 20-MAY-17:01 | 260.91 | 23-MAY-04:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 526.13 | 17-JUN-17:03 | 137.56 | 13-JUN-03:53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 649.86 | 22-JUL-18:00 | 210.28 | 26-JUL-24:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 550.98 | 13-AUG-16:00 | 313.98 | 05-AUG-17:47 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 425.62 | 17-SEP-12:00 | 231.25 | 03-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 250.62 | 01-OCT-14:22 | 583.40 | 22-OCT-14:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.53 | 19-NOV-15:00 | 658.89 | 29-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.42 | 21-DEC-15:00 | 550.12 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.56 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 649.86 | 771.66 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.28 | 31-JAN-14:00 | 1095.32 | 01-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1345.71 | 02-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.03 | 18-MAR-17:02 | 1127.07 | 28-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 685.64 | 30-APR-15:00 | 576.79 | 21-APR-05:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 626.65 | 20-MAY-17:01 | 461.49 | 23-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 999.89 | 17-JUN-17:03 | 223.76 | 13-JUN-03:53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1235.89 | 22-JUL-18:00 | 346.35 | 26-JUL-23:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1101.82 | 13-AUG-16:00 | 510.84 | 05-AUG-17:50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 802.56 | 17-SEP-11:53 | 378.98 | 03-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 498.37 | 01-OCT-14:50 | 986.06 | 22-OCT-14:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.07 | 19-NOV-14:51 | 1114.22 | 29-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.28 | 25-DEC-15:52 | 950.55 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.76 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1235.89 | 1345.71 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.08 | 16-JAN-11:55 | 944.45 | 01-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1338.18 | 02-FEB-23:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.07 | 18-MAR-17:02 | 1121.48 | 28-MAR-04:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 592.92 | 30-APR-16:00 | 580.01 | 26-APR-21:02 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 614.96 | 20-MAY-17:01 | 480.27 | 23-MAY-04:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1082.60 | 17-JUN-17:03 | 237.45 | 13-JUN-03:53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1288.36 | 22-JUL-18:00 | 424.16 | 26-JUL-23:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1051.19 | 13-AUG-16:00 | 636.69 | 05-AUG-17:42 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 818.89 | 17-SEP-11:53 | 462.06 | 03-SEP-05:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 483.55 | 01-OCT-14:30 | 1263.74 | 22-OCT-13:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.50 | 19-NOV-15:00 | 1119.62 | 29-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.34 | 25-DEC-16:00 | 927.30 | 07-DEC-02:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.45 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1288.36 | 1338.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 121750.95 | 02-JAN-07:05 | 7180.90 | 12934.72 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 117314.27 | 21-FEB-07:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 114562.32 | 20-MAR-06:11 | 32314.05 | 58206.26 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 131645.56 | 26-APR-19:31 | 17952.25 | 43114.94 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 136890.03 | 12-MAY-06:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 139550.57 | 21-JUN-06:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 140511.94 | 01-JUL-06:11 | 17952.25 | 21558.68 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 133526.60 | 24-AUG-06:05 | 7180.90 | 12934.72 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 126175.86 | 21-SEP-06:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 132660.21 | 17-OCT-06:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 123371.02 | 02-NOV-06:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 123468.63 | 26-DEC-07:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 114562.32 | 7180.90 | 12934.72 | 26915.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 140511.94 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 100373.46 | 02-JAN-05:11 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 91909.96 | 21-FEB-05:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 94402.85 | 13-MAR-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 94369.65 | 07-APR-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 100395.95 | 10-MAY-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 98322.52 | 10-JUN-04:13 | 0.00 | 3224.16 | 26719.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 99040.48 | 29-JUL-04:13 | 0.00 | 3224.16 | 26719.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 99451.63 | 07-AUG-04:24 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 99128.34 | 30-SEP-04:13 | 0.00 | 3224.16 | 26719.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 99756.24 | 11-OCT-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 98214.42 | 13-NOV-05:11 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 96955.16 | 04-DEC-05:11 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 91909.96 | 0.00 | 2686.80 | 26719.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 100395.95 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 79538.40 | 27-JAN-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 78971.23 | 01-FEB-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 80454.27 | 20-MAR-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 82852.73 | 05-APR-04:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 83377.64 | 12-MAY-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 81369.94 | 21-JUN-04:12 | 0.00 | 2149.44 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 83387.44 | 29-JUL-04:12 | 0.00 | 3224.16 | 26719.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 82159.31 | 05-AUG-04:12 | 0.00 | 2686.80 | 22266.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 84057.60 | 22-SEP-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 84067.77 | 11-OCT-04:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 84217.93 | 13-NOV-05:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 77547.95 | 28-DEC-06:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 77547.95 | 0.00 | 2149.44 | 22266.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 84217.93 | 8061.19 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 38478.42 | 27-JAN-17:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 36243.94 | 22-FEB-17:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 77175.37 | 17-MAR-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 81708.04 | 05-APR-04:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 82981.22 | 09-MAY-04:11 | 0.00 | 3761.52 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 90403.56 | 19-JUN-04:13 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 83221.09 | 27-JUL-04:12 | 0.00 | 2149.44 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 82425.80 | 03-AUG-03:02 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 83622.81 | 14-SEP-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 82733.83 | 05-OCT-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 77233.78 | 03-NOV-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 36119.77 | 22-DEC-17:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 36119.77 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 90403.56 | 15316.26 | 17424.44 | 41563.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5468.69 | 31-JAN-16:30 | 1923.11 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 7.55 | 0.00 |
February | 5328.90 | 22-FEB-14:00 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 |
March | 7649.00 | 20-MAR-14:00 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 9.59 | 0.00 |
April | 18961.00 | 30-APR-16:01 | 1012.16 | 578.27 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 147.63 | 0.00 |
May | 19155.38 | 07-MAY-16:11 | 910.95 | 520.44 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 109.39 | 0.00 |
June | 20709.09 | 04-JUN-17:02 | 0.00 | 578.27 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 132.49 | 0.00 |
July | 21268.04 | 04-JUL-18:12 | 0.00 | 578.27 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 139.67 | 0.00 |
August | 21125.92 | 27-AUG-16:22 | 1012.16 | 578.27 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 163.47 | 0.00 |
September | 19021.92 | 10-SEP-16:02 | 607.30 | 346.96 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.76 | 0.00 |
October | 17561.36 | 09-OCT-13:41 | 809.73 | 462.61 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 18.09 | 0.00 |
November | 10072.19 | 13-NOV-05:11 | 0.00 | 472.30 | 5218.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.01 |
December | 5774.43 | 26-DEC-15:40 | 1923.11 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5328.90 | 0.00 | 346.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21268.04 | 2010.79 | 1141.96 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 163.47 | 15.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7680.54 | 17-JAN-09:30 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.19 |
February | 8057.17 | 20-FEB-10:23 | 195.68 | 111.80 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.07 |
March | 17192.47 | 19-MAR-09:32 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.86 |
April | 20851.48 | 30-APR-09:21 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.64 |
May | 21375.17 | 07-MAY-08:51 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.86 |
June | 22304.37 | 18-JUN-08:41 | 587.05 | 335.39 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 18.22 | 0.00 |
July | 21734.35 | 04-JUL-08:51 | 521.82 | 298.13 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 2.29 | 0.00 |
August | 21527.14 | 27-AUG-09:01 | 521.82 | 298.13 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 22.73 | 0.00 |
September | 20387.89 | 10-SEP-10:41 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 28.85 | 0.00 |
October | 19575.46 | 09-OCT-10:22 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.51 |
November | 8710.88 | 02-NOV-08:40 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.56 |
December | 6911.07 | 26-DEC-09:50 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6911.07 | 195.68 | 111.80 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22304.37 | 1239.33 | 670.83 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 28.85 | 66.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 23617.04 | 29-JAN-11:42 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.13 |
February | 21894.95 | 26-FEB-14:02 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.58 |
March | 14817.49 | 23-MAR-13:40 | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 8.85 | 0.00 |
April | 22260.27 | 30-APR-16:01 | 1012.19 | 578.28 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 130.49 | 0.00 |
May | 21582.38 | 07-MAY-16:11 | 910.97 | 520.45 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 108.37 | 0.00 |
June | 22504.08 | 04-JUN-16:22 | 1012.19 | 578.28 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 150.85 | 0.00 |
July | 23005.83 | 04-JUL-16:52 | 1012.19 | 578.28 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 175.99 | 0.00 |
August | 24271.91 | 27-AUG-15:02 | 1012.19 | 578.28 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 162.75 | 0.00 |
September | 25181.49 | 10-SEP-13:23 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 110.87 | 0.00 |
October | 25777.13 | 09-OCT-13:43 | 809.75 | 462.62 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 13.20 | 0.00 |
November | 24330.76 | 19-NOV-13:31 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.03 |
December | 25452.62 | 25-DEC-13:11 | 809.75 | 462.62 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14817.49 | 404.87 | 231.31 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25777.13 | 2010.83 | 1040.98 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 175.99 | 109.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25012.76 | 29-JAN-16:22 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.35 |
February | 17332.68 | 20-FEB-16:22 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.97 |
March | 19444.57 | 26-MAR-15:52 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.16 |
April | 29459.55 | 30-APR-16:41 | 652.28 | 372.66 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 28.32 | 0.00 |
May | 28225.80 | 07-MAY-16:11 | 587.05 | 335.39 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.03 | 0.00 |
June | 29030.90 | 04-JUN-16:21 | 652.28 | 372.66 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 67.96 | 0.00 |
July | 29542.78 | 02-JUL-17:21 | 0.00 | 372.66 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 87.88 | 0.00 |
August | 30013.19 | 27-AUG-16:22 | 652.28 | 372.66 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 91.87 | 0.00 |
September | 24953.66 | 04-SEP-15:52 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 20.22 | 0.00 |
October | 25273.50 | 09-OCT-15:41 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 37.21 | 0.00 |
November | 25027.32 | 05-NOV-15:12 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.72 |
December | 26535.49 | 25-DEC-15:11 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 17332.68 | 0.00 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30013.19 | 652.28 | 372.66 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 91.87 | 43.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3916.19 | 31-JAN-16:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 17.32 | 0.00 |
February | 3058.66 | 22-FEB-16:10 | 1923.11 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.74 |
March | 5812.32 | 16-MAR-16:00 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 32.27 | 0.00 |
April | 10409.87 | 26-APR-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 |
May | 18000.38 | 21-MAY-18:11 | 0.00 | 520.44 | 5032.54 | 0.00 | 0.00 | 0.00 | 0.00 | 152.17 | 0.00 |
June | 19296.66 | 04-JUN-17:51 | 0.00 | 578.27 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 241.56 | 0.00 |
July | 19553.44 | 16-JUL-18:01 | 0.00 | 578.27 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 420.07 | 0.00 |
August | 19342.17 | 13-AUG-16:11 | 1012.16 | 578.27 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 585.01 | 0.00 |
September | 16122.41 | 17-SEP-13:23 | 404.87 | 231.31 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 371.13 | 0.00 |
October | 18079.05 | 01-OCT-13:42 | 506.08 | 289.13 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 271.51 | 0.00 |
November | 5721.58 | 02-NOV-14:00 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 30.28 | 0.00 |
December | 2990.45 | 22-DEC-16:10 | 1923.11 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2990.45 | 0.00 | 231.31 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19553.44 | 2010.79 | 1141.96 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 585.01 | 28.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5861.80 | 27-JAN-10:00 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.95 |
February | 6412.25 | 23-FEB-10:00 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.89 |
March | 12928.54 | 19-MAR-09:23 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.33 |
April | 21868.67 | 30-APR-09:11 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.51 |
May | 22243.36 | 07-MAY-09:01 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.70 |
June | 23060.09 | 04-JUN-09:11 | 521.82 | 298.13 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 13.57 | 0.00 |
July | 22055.75 | 02-JUL-09:31 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 12.53 | 0.00 |
August | 22727.43 | 13-AUG-10:11 | 521.82 | 298.13 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 37.88 | 0.00 |
September | 21189.21 | 04-SEP-10:22 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.90 |
October | 20041.05 | 15-OCT-09:42 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.77 |
November | 7117.00 | 10-NOV-09:30 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.30 |
December | 4164.32 | 27-DEC-10:00 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.94 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4164.32 | 260.91 | 149.06 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23060.09 | 1239.33 | 670.83 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 37.88 | 84.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22839.18 | 16-JAN-12:12 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.23 |
February | 21349.35 | 26-FEB-14:02 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.02 |
March | 14753.03 | 26-MAR-14:13 | 303.66 | 173.48 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.34 |
April | 21115.17 | 09-APR-14:02 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 81.48 | 0.00 |
May | 20158.82 | 07-MAY-15:41 | 910.97 | 520.45 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 251.47 | 0.00 |
June | 21195.62 | 04-JUN-16:31 | 1012.19 | 578.28 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 321.06 | 0.00 |
July | 21485.11 | 16-JUL-16:41 | 1012.19 | 578.28 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 415.83 | 0.00 |
August | 22375.85 | 13-AUG-15:31 | 1012.19 | 578.28 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 492.40 | 0.00 |
September | 22797.19 | 04-SEP-13:42 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 51.94 | 0.00 |
October | 23986.55 | 15-OCT-14:21 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 35.76 | 0.00 |
November | 23412.63 | 19-NOV-13:02 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.45 |
December | 23378.60 | 03-DEC-13:12 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14753.03 | 303.66 | 173.48 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23986.55 | 1012.19 | 578.28 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 492.40 | 265.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14790.51 | 29-JAN-17:12 | 260.91 | 149.06 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.95 |
February | 10570.18 | 22-FEB-16:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.14 |
March | 16133.06 | 18-MAR-17:05 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 | 0.00 |
April | 23447.33 | 30-APR-16:31 | 652.28 | 372.66 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 143.64 | 0.00 |
May | 25564.77 | 28-MAY-17:21 | 0.00 | 372.66 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 68.96 | 0.00 |
June | 26225.48 | 04-JUN-16:31 | 652.28 | 372.66 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 155.00 | 0.00 |
July | 26047.96 | 16-JUL-17:21 | 0.00 | 372.66 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 234.09 | 0.00 |
August | 26587.35 | 13-AUG-16:51 | 652.28 | 372.66 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 250.00 | 0.00 |
September | 24220.77 | 04-SEP-15:41 | 521.82 | 298.13 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 35.91 | 0.00 |
October | 23189.85 | 15-OCT-17:01 | 0.00 | 260.86 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 28.65 | 0.00 |
November | 14843.05 | 26-NOV-16:23 | 260.91 | 149.06 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.35 |
December | 10356.92 | 22-DEC-16:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10356.92 | 0.00 | 149.06 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26587.35 | 1239.33 | 670.83 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 250.00 | 169.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3716.98 | 31-JAN-17:00 | 1923.11 | 1524.25 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 21.02 | 0.00 |
February | 2947.29 | 22-FEB-16:30 | 1923.11 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.55 |
March | 6259.77 | 16-MAR-16:00 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 39.13 | 0.00 |
April | 10030.98 | 26-APR-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.95 |
May | 20506.91 | 21-MAY-15:41 | 910.95 | 520.44 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 264.81 | 0.00 |
June | 21394.56 | 18-JUN-17:22 | 0.00 | 289.13 | 2795.85 | 0.00 | 0.00 | 0.00 | 0.00 | 171.66 | 0.00 |
July | 22800.31 | 16-JUL-17:31 | 0.00 | 578.27 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 563.29 | 0.00 |
August | 22740.79 | 13-AUG-16:11 | 1012.16 | 578.27 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 683.84 | 0.00 |
September | 20943.19 | 04-SEP-15:41 | 809.73 | 462.61 | 5761.47 | 0.00 | 0.00 | 0.00 | 0.00 | 112.22 | 0.00 |
October | 20701.01 | 01-OCT-13:42 | 506.08 | 289.13 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 328.45 | 0.00 |
November | 5952.85 | 01-NOV-15:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 34.41 | 0.00 |
December | 3134.14 | 22-DEC-15:00 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2947.29 | 0.00 | 289.13 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22800.31 | 2010.79 | 1524.25 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 683.84 | 40.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4814.65 | 27-JAN-10:30 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.26 |
February | 5390.65 | 23-FEB-10:20 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.66 |
March | 7391.27 | 23-MAR-10:20 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.83 |
April | 20750.86 | 16-APR-09:52 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.81 |
May | 22643.53 | 21-MAY-09:41 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.70 |
June | 24168.73 | 18-JUN-08:41 | 587.05 | 335.39 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 51.68 | 0.00 |
July | 21470.72 | 30-JUL-09:32 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 51.07 | 0.00 |
August | 23450.32 | 13-AUG-10:11 | 521.82 | 298.13 | 3712.91 | 0.00 | 0.00 | 0.00 | 0.00 | 43.42 | 0.00 |
September | 21816.16 | 04-SEP-10:22 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.70 |
October | 18427.80 | 01-OCT-13:42 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 221.22 | 0.00 |
November | 6284.27 | 01-NOV-10:00 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.36 |
December | 3070.23 | 22-DEC-15:00 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3070.23 | 326.14 | 186.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24168.73 | 1295.83 | 670.83 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 221.22 | 186.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26131.59 | 29-JAN-14:11 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.82 |
February | 16583.57 | 28-FEB-14:20 | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.99 |
March | 14545.23 | 16-MAR-13:30 | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 22.34 | 0.00 |
April | 23402.50 | 30-APR-12:51 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 334.97 | 0.00 |
May | 23038.59 | 21-MAY-15:41 | 910.97 | 520.45 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 247.34 | 0.00 |
June | 23189.45 | 18-JUN-17:22 | 0.00 | 289.14 | 2795.90 | 0.00 | 0.00 | 0.00 | 0.00 | 174.69 | 0.00 |
July | 24704.33 | 16-JUL-16:51 | 1012.19 | 578.28 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 548.20 | 0.00 |
August | 25715.87 | 13-AUG-15:31 | 1012.19 | 578.28 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 575.07 | 0.00 |
September | 25414.30 | 04-SEP-13:42 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 57.44 | 0.00 |
October | 26998.45 | 09-OCT-13:41 | 809.75 | 462.62 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 25.01 | 0.00 |
November | 25058.37 | 05-NOV-13:42 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.41 |
December | 26130.22 | 25-DEC-14:21 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14545.23 | 0.00 | 289.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26998.45 | 2010.83 | 1040.98 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 575.07 | 199.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 16373.31 | 29-JAN-16:52 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.97 |
February | 10531.24 | 22-FEB-16:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.03 |
March | 16622.58 | 18-MAR-17:05 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.20 |
April | 24717.71 | 23-APR-16:21 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 160.49 | 0.00 |
May | 26486.94 | 29-MAY-15:51 | 587.05 | 335.39 | 4177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.08 | 0.00 |
June | 25942.88 | 25-JUN-17:31 | 0.00 | 298.13 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 294.44 | 0.00 |
July | 28693.33 | 16-JUL-16:51 | 652.28 | 372.66 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 264.92 | 0.00 |
August | 29293.40 | 13-AUG-16:51 | 652.28 | 372.66 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 290.99 | 0.00 |
September | 26430.03 | 04-SEP-15:41 | 521.82 | 298.13 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 39.12 | 0.00 |
October | 25373.57 | 15-OCT-15:31 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 36.41 | 0.00 |
November | 12542.86 | 01-NOV-16:00 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 26.87 | 0.00 |
December | 10279.94 | 22-DEC-16:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10279.94 | 0.00 | 186.33 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29293.40 | 1239.33 | 670.83 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 294.44 | 69.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7941.07 | 02-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.99 |
February | 5680.32 | 21-FEB-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.48 |
March | 7777.58 | 20-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.51 |
April | 10130.85 | 24-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 |
May | 13306.01 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.02 |
June | 18632.63 | 19-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.90 |
July | 18527.34 | 31-JUL-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 | 0.00 |
August | 19434.80 | 14-AUG-05:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
September | 16353.11 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.39 |
October | 16769.77 | 02-OCT-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.26 | 0.00 |
November | 9720.19 | 13-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.26 |
December | 9365.47 | 26-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5680.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19434.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.26 | 81.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4432.20 | 28-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.77 |
February | 4650.72 | 01-FEB-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.14 |
March | 4935.02 | 20-MAR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.59 |
April | 7271.47 | 14-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.02 | 0.00 |
May | 7581.69 | 11-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.74 |
June | 11234.90 | 19-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.71 |
July | 10332.87 | 22-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.23 | 0.00 |
August | 8860.61 | 14-AUG-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.66 | 0.00 |
September | 10500.93 | 05-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.58 |
October | 9036.47 | 03-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.39 |
November | 5394.89 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.31 |
December | 7099.06 | 06-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4432.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11234.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.66 | 194.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8886.93 | 31-JAN-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.77 | 0.00 |
February | 8003.44 | 23-FEB-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.28 |
March | 12623.03 | 16-MAR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.97 | 0.00 |
April | 20052.67 | 14-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.59 | 0.00 |
May | 20453.92 | 19-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.85 | 0.00 |
June | 24580.84 | 28-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.16 | 0.00 |
July | 23344.56 | 20-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.65 | 0.00 |
August | 22797.49 | 15-AUG-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.42 | 0.00 |
September | 20409.21 | 07-SEP-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.10 | 0.00 |
October | 17816.69 | 02-OCT-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.16 | 0.00 |
November | 11563.61 | 01-NOV-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.37 | 0.00 |
December | 6851.59 | 22-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6851.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24580.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.85 | 103.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2280.02 | 24-JAN-17:00 | 222.14 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4124.13 | 27-FEB-17:40 | 70.15 | 250.06 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7157.26 | 31-MAR-24:00 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7923.29 | 26-APR-18:30 | 23.38 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3573.03 | 31-MAY-23:50 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5551.28 | 30-JUN-23:53 | 0.00 | 100.03 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7482.72 | 31-JUL-23:55 | 0.00 | 50.02 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7890.81 | 06-AUG-20:17 | 0.00 | 100.03 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3629.09 | 30-SEP-23:47 | 0.00 | 75.02 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5331.34 | 31-OCT-24:00 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6276.64 | 14-NOV-17:00 | 222.14 | 450.11 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8033.81 | 28-DEC-17:00 | 222.14 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2280.02 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8033.81 | 222.14 | 450.11 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2106.81 | 24-JAN-17:00 | 222.14 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3832.16 | 27-FEB-17:40 | 70.15 | 250.06 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6673.09 | 31-MAR-23:50 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7553.73 | 26-APR-18:20 | 23.38 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3392.85 | 31-MAY-23:53 | 0.00 | 100.03 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5219.28 | 30-JUN-23:53 | 0.00 | 100.03 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7001.93 | 31-JUL-23:55 | 0.00 | 50.02 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7398.24 | 06-AUG-18:30 | 0.00 | 125.04 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3394.01 | 30-SEP-24:00 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4896.84 | 31-OCT-24:00 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5893.42 | 14-NOV-17:00 | 222.14 | 450.11 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7515.54 | 28-DEC-17:00 | 222.14 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2106.81 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7553.73 | 222.14 | 450.11 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2125.53 | 24-JAN-17:00 | 222.14 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3812.85 | 27-FEB-17:40 | 70.15 | 250.06 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6488.49 | 31-MAR-23:20 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7597.80 | 26-APR-18:10 | 23.38 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3393.69 | 31-MAY-23:53 | 0.00 | 100.03 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5260.62 | 30-JUN-23:53 | 0.00 | 100.03 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7059.81 | 31-JUL-23:55 | 0.00 | 50.02 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7563.15 | 06-AUG-18:30 | 0.00 | 125.04 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3438.62 | 30-SEP-24:00 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4694.65 | 31-OCT-23:50 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5921.89 | 21-NOV-17:00 | 222.14 | 450.11 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7552.86 | 26-DEC-17:00 | 222.14 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2125.53 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7597.80 | 222.14 | 450.11 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 92933.80 | 02-JAN-17:00 | 4808.68 | 5470.56 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 183616.39 | 22-FEB-17:00 | 4808.68 | 5470.56 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358351.57 | 31-MAR-24:00 | 0.00 | 303.90 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 380618.68 | 09-APR-14:04 | 1265.44 | 1519.49 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176894.92 | 31-MAY-23:53 | 0.00 | 1215.59 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 269249.70 | 30-JUN-23:53 | 0.00 | 1215.59 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 362127.17 | 31-JUL-23:55 | 0.00 | 607.79 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 381913.40 | 05-AUG-17:03 | 1012.35 | 1215.59 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 178620.05 | 30-SEP-24:00 | 0.00 | 303.90 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 269372.38 | 31-OCT-24:00 | 0.00 | 303.90 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 277734.48 | 20-NOV-17:00 | 4808.68 | 5470.56 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 369383.15 | 26-DEC-17:00 | 4808.68 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 92933.80 | 0.00 | 303.90 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 381913.40 | 4808.68 | 5470.56 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [] | NATURALGAS:FACILITY [] | |
January | 0.188613E+13 | 1509916.45 | 27-JAN-16:19 | 0.00 | 0.00 |
February | 0.184515E+13 | 1516175.03 | 22-FEB-16:30 | 0.00 | 0.00 |
March | 0.265528E+13 | 1883438.61 | 17-MAR-15:20 | 0.00 | 0.00 |
April | 0.325600E+13 | 2084797.22 | 03-APR-15:20 | 0.00 | 0.00 |
May | 0.220179E+13 | 1587785.00 | 18-MAY-15:09 | 0.00 | 0.00 |
June | 0.267780E+13 | 1847333.86 | 19-JUN-14:09 | 0.00 | 0.00 |
July | 0.308519E+13 | 1992333.19 | 20-JUL-15:09 | 0.00 | 0.00 |
August | 0.357764E+13 | 2148306.33 | 25-AUG-15:09 | 0.00 | 0.00 |
September | 0.208411E+13 | 1613305.59 | 19-SEP-15:09 | 0.00 | 0.00 |
October | 0.240102E+13 | 1730321.44 | 20-OCT-15:50 | 0.00 | 0.00 |
November | 0.252697E+13 | 1871173.87 | 20-NOV-16:00 | 0.00 | 0.00 |
December | 0.295731E+13 | 1942697.55 | 22-DEC-16:30 | 0.00 | 0.00 |
Annual Sum or Average | 0.311544E+14 | 0.00 | 0.00 | ||
Minimum of Months | 0.184515E+13 | 1509916.45 | 0.00 | 0.00 | |
Maximum of Months | 0.357764E+13 | 2148306.33 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.271494E+12 | 0.373844E+11 | 0.766053E+12 | 0.213343E+12 | 0.206369E+12 | 0.331080E+11 | 0.856882E+10 | 0.788626E+11 | 0.457322E+11 | 0.191877E+12 | 0.00 | 0.333368E+11 | 0.00 |
February | 0.245564E+12 | 0.309088E+11 | 0.978954E+12 | 0.195334E+12 | 0.181603E+12 | 0.246911E+11 | 0.864416E+10 | 0.400077E+11 | 0.155517E+11 | 0.938885E+11 | 0.00 | 0.300047E+11 | 0.00 |
March | 0.289433E+12 | 0.303717E+11 | 0.141687E+13 | 0.226058E+12 | 0.213362E+12 | 0.369995E+11 | 0.736854E+10 | 0.150846E+12 | 0.574017E+11 | 0.192965E+12 | 0.00 | 0.336046E+11 | 0.00 |
April | 0.256374E+12 | 0.256650E+11 | 0.165903E+13 | 0.211502E+12 | 0.254499E+12 | 0.565604E+11 | 18108103.88 | 0.450048E+12 | 0.114451E+12 | 0.199699E+12 | 0.00 | 0.281593E+11 | 0.00 |
May | 0.276202E+12 | 0.232835E+11 | 0.774844E+12 | 0.219699E+12 | 0.276258E+12 | 0.593331E+11 | 0.00 | 0.276825E+12 | 0.126697E+12 | 0.141284E+12 | 0.00 | 0.273617E+11 | 0.00 |
June | 0.274271E+12 | 0.213378E+11 | 0.106252E+13 | 0.217935E+12 | 0.299940E+12 | 0.740099E+11 | 0.00 | 0.482679E+12 | 0.152517E+12 | 0.677233E+11 | 0.00 | 0.248698E+11 | 0.00 |
July | 0.256591E+12 | 0.226209E+11 | 0.139340E+13 | 0.213266E+12 | 0.290509E+12 | 0.755212E+11 | 0.00 | 0.613650E+12 | 0.176417E+12 | 0.205589E+11 | 0.00 | 0.226480E+11 | 0.00 |
August | 0.288019E+12 | 0.251910E+11 | 0.173200E+13 | 0.226058E+12 | 0.297657E+12 | 0.765646E+11 | 0.00 | 0.713726E+12 | 0.177312E+12 | 0.159986E+11 | 0.00 | 0.251112E+11 | 0.00 |
September | 0.257336E+12 | 0.275813E+11 | 0.740713E+12 | 0.211501E+12 | 0.258978E+12 | 0.638998E+11 | 0.00 | 0.316278E+12 | 0.163163E+12 | 0.202783E+11 | 0.00 | 0.243854E+11 | 0.00 |
October | 0.269317E+12 | 0.325062E+11 | 0.108340E+13 | 0.213343E+12 | 0.234487E+12 | 0.488297E+11 | 0.997049E+09 | 0.231674E+12 | 0.100275E+12 | 0.158578E+12 | 0.00 | 0.276085E+11 | 0.00 |
November | 0.268110E+12 | 0.352667E+11 | 0.135889E+13 | 0.205297E+12 | 0.208171E+12 | 0.343628E+11 | 0.468240E+10 | 0.151834E+12 | 0.558321E+11 | 0.174887E+12 | 0.00 | 0.296396E+11 | 0.00 |
December | 0.263517E+12 | 0.385856E+11 | 0.170972E+13 | 0.213267E+12 | 0.202375E+12 | 0.276051E+11 | 0.303469E+11 | 0.137380E+12 | 0.404176E+11 | 0.262541E+12 | 0.00 | 0.315507E+11 | 0.00 |
Annual Sum or Average | 0.321623E+13 | 0.350703E+12 | 0.146764E+14 | 0.256660E+13 | 0.292421E+13 | 0.611485E+12 | 0.606260E+11 | 0.364381E+13 | 0.122577E+13 | 0.154028E+13 | 0.00 | 0.338280E+12 | 0.00 |
Minimum of Months | 0.245564E+12 | 0.213378E+11 | 0.740713E+12 | 0.195334E+12 | 0.181603E+12 | 0.246911E+11 | 0.00 | 0.400077E+11 | 0.155517E+11 | 0.159986E+11 | 0.00 | 0.226480E+11 | 0.00 |
Maximum of Months | 0.289433E+12 | 0.385856E+11 | 0.173200E+13 | 0.226058E+12 | 0.299940E+12 | 0.765646E+11 | 0.303469E+11 | 0.713726E+12 | 0.177312E+12 | 0.262541E+12 | 0.00 | 0.336046E+11 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 325713.14 | 20-JAN-16:00 | 40855.88 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 233436.21 | 20-JAN-08:39 | 170913.62 | 31-JAN-16:00 | 44448.58 | 31-JAN-15:30 | 360403.59 | 02-JAN-06:10 |
February | 314611.94 | 10-FEB-08:09 | 40855.88 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 233433.23 | 10-FEB-08:20 | 163374.89 | 22-FEB-16:30 | 24057.61 | 16-FEB-13:30 | 223188.29 | 13-FEB-06:10 |
March | 310693.28 | 21-MAR-07:10 | 40855.88 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 233431.14 | 21-MAR-07:19 | 198592.10 | 16-MAR-15:50 | 45700.05 | 20-MAR-15:00 | 275893.91 | 27-MAR-06:10 |
April | 295787.05 | 04-APR-07:10 | 40855.88 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 233423.17 | 04-APR-07:19 | 245746.26 | 13-APR-15:20 | 44168.49 | 14-APR-15:50 | 3126.24 | 21-APR-05:49 |
May | 284436.93 | 26-MAY-07:10 | 40855.88 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 233417.11 | 26-MAY-07:19 | 255756.23 | 18-MAY-15:09 | 44165.34 | 18-MAY-15:20 | 0.00 | 01-MAY-00:10 |
June | 282443.79 | 01-JUN-07:10 | 40855.88 | 01-JUN-05:10 | 541788.89 | 01-JUN-07:10 | 233416.05 | 01-JUN-07:19 | 266299.02 | 16-JUN-14:00 | 48650.36 | 19-JUN-14:30 | 0.00 | 01-JUN-00:10 |
July | 290088.60 | 27-JUL-07:10 | 40855.88 | 01-JUL-05:10 | 660080.29 | 03-JUL-07:10 | 233420.13 | 27-JUL-07:19 | 266630.54 | 21-JUL-15:39 | 46222.49 | 11-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 314611.94 | 04-AUG-07:10 | 40855.88 | 01-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 233433.23 | 04-AUG-07:19 | 270281.53 | 24-AUG-15:09 | 47908.65 | 23-AUG-15:00 | 0.00 | 01-AUG-00:10 |
September | 298808.44 | 29-SEP-07:10 | 40855.88 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 233424.78 | 29-SEP-07:19 | 249613.99 | 14-SEP-15:00 | 48212.54 | 28-SEP-13:39 | 0.00 | 01-SEP-00:10 |
October | 309662.48 | 27-OCT-07:10 | 40855.88 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 233430.59 | 27-OCT-07:19 | 219222.69 | 02-OCT-15:00 | 48065.77 | 05-OCT-15:00 | 65441.78 | 25-OCT-06:30 |
November | 325713.14 | 28-NOV-16:30 | 40855.88 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 233431.06 | 01-NOV-07:19 | 186410.51 | 02-NOV-15:00 | 54460.39 | 02-NOV-14:09 | 215536.82 | 24-NOV-06:10 |
December | 325713.14 | 01-DEC-16:30 | 40855.88 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 233433.23 | 12-DEC-08:20 | 157547.47 | 26-DEC-16:00 | 24252.20 | 22-DEC-16:19 | 367677.48 | 06-DEC-07:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 282443.79 | 40855.88 | 423497.50 | 233416.05 | 157547.47 | 24057.61 | 0.00 | |||||||
Maximum of Months | 325713.14 | 40855.88 | 778371.69 | 233436.21 | 270281.53 | 54460.39 | 367677.48 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 227805.00 | 31-JAN-16:19 | 53702.82 | 31-JAN-14:50 | 100000.00 | 01-JAN-12:30 | 0.00 | 44032.98 | 23-JAN-12:39 | 0.00 |
February | 98243.90 | 22-FEB-15:00 | 50456.86 | 22-FEB-15:00 | 100000.00 | 01-FEB-22:10 | 0.00 | 43951.24 | 01-FEB-12:30 | 0.00 |
March | 315721.25 | 17-MAR-12:00 | 67758.62 | 16-MAR-15:00 | 100000.00 | 08-MAR-05:30 | 0.00 | 42656.64 | 01-MAR-12:39 | 0.00 |
April | 393659.18 | 14-APR-15:09 | 86268.97 | 10-APR-14:50 | 100000.00 | 01-APR-04:30 | 0.00 | 39455.53 | 03-APR-11:30 | 0.00 |
May | 271787.63 | 18-MAY-15:20 | 86268.97 | 09-MAY-13:39 | 100000.00 | 01-MAY-01:30 | 0.00 | 36587.59 | 01-MAY-11:30 | 0.00 |
June | 381646.42 | 19-JUN-14:09 | 86268.97 | 01-JUN-08:50 | 100000.00 | 01-JUN-01:19 | 0.00 | 33300.50 | 01-JUN-11:39 | 0.00 |
July | 427748.10 | 19-JUL-13:39 | 86268.97 | 03-JUL-11:50 | 100000.00 | 01-JUL-00:40 | 0.00 | 31030.76 | 03-JUL-11:39 | 0.00 |
August | 460655.15 | 11-AUG-15:00 | 86268.97 | 01-AUG-05:49 | 100000.00 | 23-AUG-04:19 | 0.00 | 31519.30 | 31-AUG-11:30 | 0.00 |
September | 315840.73 | 01-SEP-12:20 | 86268.97 | 01-SEP-05:30 | 100000.00 | 15-SEP-21:10 | 0.00 | 34320.87 | 29-SEP-11:39 | 0.00 |
October | 320088.20 | 04-OCT-14:00 | 86268.97 | 02-OCT-07:30 | 100000.00 | 05-OCT-21:10 | 0.00 | 38199.31 | 31-OCT-11:30 | 0.00 |
November | 314052.16 | 20-NOV-16:19 | 86268.97 | 01-NOV-12:50 | 100000.00 | 03-NOV-21:10 | 0.00 | 40882.79 | 28-NOV-12:39 | 0.00 |
December | 321840.02 | 22-DEC-14:00 | 51489.20 | 22-DEC-15:09 | 100000.00 | 01-DEC-05:30 | 0.00 | 43396.77 | 29-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 98243.90 | 50456.86 | 100000.00 | 0.00 | 31030.76 | 0.00 | ||||
Maximum of Months | 460655.15 | 86268.97 | 100000.00 | 0.00 | 44032.98 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1509916.45 | 27-JAN-16:19 | 280616.72 | 423497.50 | 0.00 | 233302.19 | 133495.53 | 43942.25 | 0.00 | 211394.44 | 49544.44 |
February | 1516175.03 | 22-FEB-16:30 | 282443.77 | 541788.89 | 0.00 | 233303.25 | 163374.89 | 23769.01 | 0.00 | 87874.60 | 50274.76 |
March | 1883438.61 | 17-MAR-15:20 | 280450.63 | 660080.29 | 0.00 | 233302.19 | 179321.14 | 25628.26 | 0.00 | 305218.02 | 67758.62 |
April | 2084797.22 | 03-APR-15:20 | 280450.63 | 778371.69 | 0.00 | 233302.19 | 219359.74 | 43950.97 | 0.00 | 347746.58 | 50942.27 |
May | 1587785.00 | 18-MAY-15:09 | 280450.63 | 423497.50 | 0.00 | 233302.19 | 255756.23 | 44158.85 | 0.00 | 271379.27 | 51629.19 |
June | 1847333.86 | 19-JUN-14:09 | 280450.63 | 541788.89 | 0.00 | 233151.79 | 257355.26 | 48002.68 | 0.00 | 381646.42 | 86268.97 |
July | 1992333.19 | 20-JUL-15:09 | 280450.63 | 660080.29 | 0.00 | 233302.19 | 263279.06 | 45604.45 | 0.00 | 401306.70 | 86268.97 |
August | 2148306.33 | 25-AUG-15:09 | 280450.63 | 778371.69 | 0.00 | 233302.19 | 256047.59 | 44322.85 | 0.00 | 444304.74 | 86268.97 |
September | 1613305.59 | 19-SEP-15:09 | 280450.63 | 423497.50 | 0.00 | 233302.19 | 237775.46 | 47664.70 | 0.00 | 279358.80 | 86268.97 |
October | 1730321.44 | 20-OCT-15:50 | 280515.72 | 541788.89 | 0.00 | 233302.19 | 200342.55 | 43827.28 | 0.00 | 251298.07 | 51420.12 |
November | 1871173.87 | 20-NOV-16:00 | 297733.18 | 660080.29 | 0.00 | 233310.24 | 172302.08 | 43789.39 | 0.00 | 279961.16 | 52788.85 |
December | 1942697.55 | 22-DEC-16:30 | 289987.47 | 778371.69 | 0.00 | 233303.25 | 124108.71 | 24243.13 | 0.00 | 307924.41 | 51364.37 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1509916.45 | 280450.63 | 423497.50 | 0.00 | 233151.79 | 124108.71 | 23769.01 | 0.00 | 87874.60 | 49544.44 | |
Maximum of Months | 2148306.33 | 297733.18 | 778371.69 | 0.00 | 233310.24 | 263279.06 | 48002.68 | 0.00 | 444304.74 | 86268.97 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 99.00 | 27.49 | 49.50 | 27.43 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 60.17 | 26.56 | 31.17 | 26.52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 65.17 | 26.44 | 38.67 | 26.43 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 208.50 | 27.47 | 136.83 | 27.47 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 525.33 | 28.41 | 357.50 | 28.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 705.00 | 29.84 | 483.33 | 29.89 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 737.33 | 30.40 | 490.33 | 30.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 735.50 | 30.66 | 505.50 | 30.70 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 653.17 | 29.81 | 428.50 | 29.83 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 337.33 | 28.94 | 195.83 | 28.95 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 162.50 | 27.53 | 68.50 | 27.51 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 131.17 | 27.34 | 49.50 | 27.31 |
Annual Sum or Average | 0.00 | 0.00 | 4420.17 | 29.41 | 2835.17 | 29.47 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 60.17 | 26.44 | 31.17 | 26.43 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 737.33 | 30.66 | 505.50 | 30.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.66 | 0.00 | 25.66 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.57 | 0.00 | 25.57 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.62 | 0.00 | 25.62 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 25.81 | 0.00 | 25.81 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 26.03 | 0.17 | 25.99 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 26.21 | 0.00 | 26.21 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 26.27 | 0.00 | 26.27 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 26.42 | 0.33 | 26.45 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 26.55 | 0.50 | 26.64 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.63 | 0.00 | 25.63 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.65 | 0.00 | 25.65 |
Annual Sum or Average | 0.00 | 0.00 | 46.17 | 26.21 | 1.00 | 26.22 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 26.55 | 0.50 | 26.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.33 | 27.27 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.37 | 1.33 | 27.36 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 24.67 | 27.23 | 10.33 | 27.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 36.67 | 27.26 | 13.33 | 27.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 27.67 | 27.14 | 9.00 | 27.29 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 26.87 | 6.67 | 27.08 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.14 | 2.17 | 27.30 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 109.17 | 27.18 | 43.17 | 27.31 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 36.67 | 27.37 | 13.33 | 27.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.41 | 0.50 | 27.41 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.49 | 1.00 | 27.49 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 28.00 | 7.00 | 28.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 27.98 | 12.50 | 28.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 27.67 | 11.67 | 27.94 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 28.83 | 27.58 | 15.17 | 27.82 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 | 27.49 | 10.83 | 27.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 27.29 | 9.00 | 27.53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.57 | 6.50 | 27.67 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 118.33 | 27.61 | 74.17 | 27.81 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 28.83 | 28.00 | 15.17 | 28.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.74 | 9.50 | 27.74 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.69 | 1.67 | 27.69 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.43 | 0.67 | 27.43 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 27.77 | 7.00 | 27.78 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.47 | 5.33 | 27.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 27.16 | 7.67 | 27.33 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 28.50 | 27.22 | 11.50 | 27.40 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 27.20 | 8.17 | 27.40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 21.00 | 26.88 | 12.17 | 26.97 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 27.67 | 26.23 | 24.50 | 26.19 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 26.40 | 12.83 | 26.40 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.76 | 9.17 | 27.76 |
Annual Sum or Average | 0.00 | 0.00 | 167.50 | 27.04 | 110.17 | 27.10 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.23 | 0.67 | 26.19 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 28.50 | 27.77 | 24.50 | 27.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.89 | 2.50 | 27.89 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 28.15 | 0.50 | 28.15 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.79 | 2.17 | 27.80 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 27.82 | 8.17 | 28.03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 28.22 | 6.67 | 28.32 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 28.83 | 27.69 | 9.17 | 27.85 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 46.83 | 27.77 | 15.00 | 27.90 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 49.67 | 27.74 | 15.00 | 27.86 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 27.40 | 5.67 | 27.64 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.68 | 5.83 | 27.89 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.91 | 4.00 | 28.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.17 | 3.67 | 28.17 |
Annual Sum or Average | 0.00 | 0.00 | 201.00 | 27.77 | 78.33 | 27.92 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.40 | 0.50 | 27.64 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 49.67 | 28.22 | 15.00 | 28.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.47 | 4.50 | 27.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.40 | 4.67 | 27.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.34 | 2.50 | 27.40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.37 | 2.00 | 27.37 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.36 | 0.50 | 27.36 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
Annual Sum or Average | 0.33 | 19.28 | 0.00 | 19.28 | 23.17 | 27.30 | 14.17 | 27.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.37 | 0.00 | 19.37 | 8.67 | 27.47 | 4.67 | 27.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.42 | 0.17 | 27.42 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.96 | 8.17 | 27.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 27.99 | 12.50 | 27.99 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 28.22 | 10.83 | 28.27 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 28.03 | 13.50 | 28.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 28.11 | 8.33 | 28.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.76 | 7.50 | 27.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.70 | 3.67 | 27.70 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
Annual Sum or Average | 0.33 | 19.35 | 0.00 | 19.35 | 70.17 | 27.97 | 64.67 | 28.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.38 | 0.00 | 19.38 | 15.33 | 28.22 | 13.50 | 28.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 25.94 | 23.33 | 25.94 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.66 | 1.67 | 27.66 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.42 | 0.67 | 27.42 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 27.69 | 6.17 | 27.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.41 | 2.50 | 27.41 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.54 | 3.83 | 27.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 27.54 | 7.67 | 27.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 27.63 | 5.17 | 27.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 26.97 | 10.67 | 26.98 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 25.93 | 26.17 | 25.92 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 | 25.89 | 19.67 | 25.89 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 26.77 | 12.17 | 26.77 |
Annual Sum or Average | 0.00 | 0.00 | 130.33 | 26.55 | 119.67 | 26.53 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.89 | 0.67 | 25.89 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 27.17 | 27.69 | 26.17 | 27.74 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.70 | 0.50 | 27.70 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.60 | 0.33 | 27.64 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 28.42 | 4.17 | 28.49 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 28.57 | 5.00 | 28.64 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 28.12 | 5.00 | 28.23 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 27.96 | 6.33 | 28.11 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 27.92 | 4.67 | 28.13 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.05 | 4.17 | 28.13 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 28.12 | 3.17 | 28.15 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.66 | 0.67 | 27.66 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.65 | 0.67 | 27.65 |
Annual Sum or Average | 0.00 | 0.00 | 75.00 | 28.12 | 34.67 | 28.24 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 17.33 | 28.57 | 6.33 | 28.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 18.45 | 0.00 | 18.45 | 0.00 | 18.45 | 0.00 | 18.45 |
February | 0.50 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
March | 0.17 | 18.76 | 0.00 | 18.76 | 0.00 | 18.76 | 0.00 | 18.76 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.44 | 1.00 | 27.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 27.66 | 6.67 | 27.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 27.44 | 8.83 | 27.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.48 | 4.50 | 27.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.51 | 3.67 | 27.51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.26 | 1.33 | 27.36 |
November | 0.50 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
December | 2.83 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 |
Annual Sum or Average | 4.50 | 18.84 | 0.00 | 18.84 | 46.00 | 26.74 | 26.00 | 27.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.83 | 19.28 | 0.00 | 19.28 | 16.33 | 27.66 | 8.83 | 27.68 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 18.26 | 0.00 | 18.26 | 0.00 | 18.26 | 0.00 | 18.26 |
February | 0.17 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
March | 0.17 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.90 | 9.17 | 27.91 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 28.04 | 12.67 | 28.07 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 28.24 | 11.17 | 28.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 28.08 | 14.00 | 28.18 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 28.08 | 8.50 | 28.21 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.87 | 8.67 | 27.90 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.70 | 3.50 | 27.70 |
November | 0.17 | 18.74 | 0.00 | 18.74 | 0.00 | 18.74 | 0.00 | 18.74 |
December | 2.67 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
Annual Sum or Average | 3.50 | 18.90 | 0.00 | 18.90 | 84.50 | 27.68 | 67.67 | 27.90 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.26 | 0.00 | 18.26 |
Maximum of Months | 2.67 | 19.07 | 0.00 | 19.07 | 18.83 | 28.24 | 14.00 | 28.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 18.45 | 0.00 | 18.45 | 5.83 | 27.88 | 5.83 | 28.01 |
February | 0.17 | 19.12 | 0.00 | 19.12 | 0.67 | 25.77 | 0.67 | 26.51 |
March | 0.17 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.80 | 6.17 | 27.82 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.51 | 5.50 | 27.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.65 | 6.00 | 27.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 27.55 | 9.17 | 27.66 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.78 | 5.50 | 27.91 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.44 | 9.00 | 27.47 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 | 27.49 | 10.00 | 27.52 |
November | 0.17 | 19.34 | 0.00 | 19.34 | 5.17 | 27.44 | 5.17 | 27.57 |
December | 1.33 | 19.05 | 0.00 | 19.05 | 5.17 | 26.21 | 5.17 | 27.03 |
Annual Sum or Average | 2.00 | 19.05 | 0.00 | 19.05 | 89.50 | 27.47 | 68.17 | 27.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.28 | 0.00 | 19.28 |
Maximum of Months | 1.33 | 19.34 | 0.00 | 19.34 | 15.33 | 27.88 | 10.00 | 28.01 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 18.22 | 0.00 | 18.22 | 0.17 | 22.88 | 0.17 | 24.43 |
February | 0.17 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.71 | 0.17 | 27.81 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 28.47 | 4.50 | 28.56 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 28.69 | 5.00 | 28.77 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | 28.20 | 5.67 | 28.33 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 28.11 | 8.67 | 28.22 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 28.03 | 5.33 | 28.24 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 28.21 | 4.67 | 28.28 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.09 | 3.50 | 28.14 |
November | 0.17 | 19.23 | 0.00 | 19.23 | 0.17 | 23.36 | 0.17 | 24.74 |
December | 1.33 | 18.96 | 0.00 | 18.96 | 0.17 | 19.88 | 0.17 | 20.62 |
Annual Sum or Average | 1.83 | 18.96 | 0.00 | 18.96 | 85.33 | 28.03 | 38.00 | 28.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.40 | 0.00 | 19.40 |
Maximum of Months | 1.33 | 19.40 | 0.00 | 19.40 | 21.50 | 28.69 | 8.67 | 28.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 275.33 | 28.73 | 225.67 | 28.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 242.67 | 28.62 | 205.50 | 28.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 28.10 | 9.00 | 28.10 |
Annual Sum or Average | 0.00 | 0.00 | 527.00 | 28.67 | 440.17 | 28.63 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 275.33 | 28.73 | 225.67 | 28.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 260.33 | 28.61 | 212.83 | 28.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 205.00 | 28.54 | 177.67 | 28.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.71 | 1.67 | 27.71 |
Annual Sum or Average | 0.00 | 0.00 | 467.00 | 28.58 | 392.17 | 28.55 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 260.33 | 28.61 | 212.83 | 28.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 215.67 | 28.66 | 176.17 | 28.64 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 171.67 | 28.63 | 145.00 | 28.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.56 | 0.17 | 27.56 |
Annual Sum or Average | 0.00 | 0.00 | 387.50 | 28.65 | 321.33 | 28.61 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 215.67 | 28.66 | 176.17 | 28.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 83.33 | 29.74 | 80.33 | 29.76 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.16 | 3.33 | 28.16 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 132.17 | 28.59 | 98.00 | 28.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 218.83 | 29.02 | 181.67 | 29.07 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 132.17 | 29.74 | 98.00 | 29.76 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 47.83 | 25.39 | 151.17 | 26.26 | 13.50 | 26.43 |
February | 13.33 | 24.30 | 251.67 | 25.16 | 1.17 | 25.17 |
March | 51.50 | 24.03 | 166.67 | 25.33 | 0.50 | 25.33 |
April | 115.50 | 26.23 | 216.67 | 26.70 | 64.83 | 26.90 |
May | 293.00 | 28.70 | 403.67 | 28.38 | 289.67 | 28.49 |
June | 477.50 | 30.00 | 494.00 | 29.91 | 477.50 | 29.94 |
July | 479.50 | 30.61 | 492.00 | 30.56 | 479.50 | 30.58 |
August | 495.67 | 30.85 | 510.50 | 30.77 | 495.67 | 30.80 |
September | 405.50 | 30.09 | 481.50 | 29.64 | 405.50 | 29.78 |
October | 170.50 | 29.00 | 300.50 | 28.18 | 148.33 | 28.56 |
November | 47.67 | 26.94 | 243.50 | 26.13 | 36.67 | 26.32 |
December | 105.83 | 24.37 | 137.83 | 25.72 | 9.17 | 25.82 |
Annual Sum or Average | 2703.33 | 29.42 | 3849.67 | 28.88 | 2422.00 | 29.19 |
Minimum of Months | 13.33 | 24.03 | 137.83 | 25.16 | 0.50 | 25.17 |
Maximum of Months | 495.67 | 30.85 | 510.50 | 30.77 | 495.67 | 30.80 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 83.67 | 23.98 | 77.33 | 24.81 | 0.00 | 24.81 |
February | 19.83 | 23.94 | 203.67 | 24.64 | 0.00 | 24.64 |
March | 51.00 | 24.01 | 127.67 | 24.72 | 0.00 | 24.72 |
April | 45.00 | 24.01 | 57.33 | 24.60 | 0.00 | 24.60 |
May | 13.83 | 24.01 | 103.83 | 25.16 | 0.00 | 25.16 |
June | 0.00 | 0.00 | 277.33 | 24.63 | 0.00 | 24.63 |
July | 13.17 | 26.57 | 453.83 | 24.59 | 13.17 | 24.64 |
August | 26.00 | 26.54 | 480.33 | 24.55 | 26.00 | 24.65 |
September | 19.17 | 26.61 | 444.50 | 24.57 | 19.17 | 24.66 |
October | 37.67 | 24.03 | 230.00 | 24.77 | 0.33 | 24.77 |
November | 41.67 | 24.37 | 187.83 | 24.78 | 5.50 | 24.83 |
December | 149.50 | 24.00 | 79.33 | 24.68 | 0.00 | 24.68 |
Annual Sum or Average | 500.50 | 24.33 | 2723.00 | 24.66 | 64.17 | 24.70 |
Minimum of Months | 0.00 | 0.00 | 57.33 | 24.55 | 0.00 | 24.60 |
Maximum of Months | 149.50 | 26.61 | 480.33 | 25.16 | 26.00 | 25.16 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 310.33 | 23.64 | 15.17 | 23.70 | 0.00 | 23.70 |
February | 168.83 | 23.56 | 65.67 | 23.79 | 0.00 | 23.79 |
March | 193.17 | 23.80 | 51.17 | 24.02 | 0.00 | 24.02 |
April | 179.00 | 23.94 | 18.00 | 24.11 | 0.00 | 24.11 |
May | 154.00 | 24.01 | 20.33 | 24.23 | 0.00 | 24.23 |
June | 41.83 | 23.97 | 59.17 | 24.21 | 0.00 | 24.21 |
July | 36.83 | 24.18 | 371.33 | 24.19 | 15.67 | 24.20 |
August | 57.50 | 24.34 | 430.50 | 24.19 | 39.67 | 24.21 |
September | 43.50 | 24.94 | 382.83 | 24.39 | 41.83 | 24.44 |
October | 151.33 | 23.89 | 129.17 | 24.19 | 2.83 | 24.19 |
November | 257.17 | 23.86 | 111.67 | 24.08 | 25.00 | 24.11 |
December | 422.00 | 23.74 | 0.00 | 23.74 | 0.00 | 23.74 |
Annual Sum or Average | 2015.50 | 23.84 | 1655.00 | 24.07 | 125.00 | 24.09 |
Minimum of Months | 36.83 | 23.56 | 0.00 | 23.70 | 0.00 | 23.70 |
Maximum of Months | 422.00 | 24.94 | 430.50 | 24.39 | 41.83 | 24.44 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 438.17 | 23.03 | 18.50 | 22.88 | 18.17 | 22.75 |
February | 357.50 | 22.85 | 13.17 | 22.86 | 3.50 | 22.84 |
March | 321.00 | 23.32 | 24.17 | 23.33 | 6.33 | 23.29 |
April | 184.33 | 23.83 | 22.17 | 23.95 | 0.00 | 23.95 |
May | 149.67 | 23.98 | 24.17 | 24.20 | 0.00 | 24.20 |
June | 26.00 | 23.98 | 119.33 | 24.37 | 0.00 | 24.37 |
July | 42.67 | 24.14 | 395.67 | 24.27 | 24.50 | 24.26 |
August | 61.33 | 24.31 | 439.67 | 24.23 | 52.83 | 24.24 |
September | 65.33 | 24.66 | 398.17 | 24.41 | 64.33 | 24.44 |
October | 229.83 | 23.59 | 117.67 | 23.86 | 6.67 | 23.86 |
November | 331.67 | 23.11 | 86.67 | 23.34 | 26.50 | 23.37 |
December | 481.50 | 22.67 | 38.67 | 22.53 | 38.67 | 22.41 |
Annual Sum or Average | 2689.00 | 23.24 | 1698.00 | 23.60 | 241.50 | 23.58 |
Minimum of Months | 26.00 | 22.67 | 13.17 | 22.53 | 0.00 | 22.41 |
Maximum of Months | 481.50 | 24.66 | 439.67 | 24.41 | 64.33 | 24.44 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 454.33 | 23.42 | 8.33 | 23.45 | 0.00 | 23.45 |
February | 321.00 | 23.18 | 12.50 | 23.22 | 0.00 | 23.22 |
March | 277.17 | 23.44 | 39.17 | 23.58 | 0.00 | 23.58 |
April | 108.33 | 23.93 | 86.17 | 24.42 | 0.00 | 24.42 |
May | 25.33 | 24.00 | 154.00 | 25.05 | 0.00 | 25.05 |
June | 26.50 | 27.05 | 403.17 | 24.78 | 26.50 | 24.91 |
July | 51.33 | 26.90 | 470.50 | 24.89 | 51.33 | 25.07 |
August | 38.83 | 26.87 | 487.50 | 24.68 | 38.67 | 24.83 |
September | 41.00 | 26.71 | 452.83 | 24.74 | 41.00 | 24.89 |
October | 193.00 | 23.86 | 163.33 | 24.24 | 8.33 | 24.30 |
November | 309.50 | 23.57 | 89.83 | 23.75 | 8.50 | 23.78 |
December | 455.83 | 23.32 | 5.00 | 23.30 | 4.33 | 23.28 |
Annual Sum or Average | 2302.17 | 23.69 | 2372.33 | 24.17 | 178.67 | 24.26 |
Minimum of Months | 25.33 | 23.18 | 5.00 | 23.22 | 0.00 | 23.22 |
Maximum of Months | 455.83 | 27.05 | 487.50 | 25.05 | 51.33 | 25.07 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 299.50 | 23.15 | 38.00 | 23.38 | 0.00 | 23.38 |
February | 268.67 | 22.87 | 66.17 | 23.19 | 1.67 | 23.20 |
March | 232.33 | 23.15 | 100.67 | 23.58 | 0.83 | 23.59 |
April | 80.50 | 24.20 | 198.50 | 24.58 | 13.67 | 24.71 |
May | 38.67 | 26.08 | 299.83 | 24.95 | 25.00 | 25.12 |
June | 44.50 | 27.12 | 446.83 | 24.79 | 44.50 | 24.98 |
July | 57.00 | 27.04 | 480.83 | 24.89 | 56.67 | 25.10 |
August | 44.83 | 26.99 | 500.33 | 24.68 | 44.00 | 24.85 |
September | 49.50 | 26.70 | 464.00 | 24.75 | 49.00 | 24.93 |
October | 150.00 | 23.83 | 228.17 | 24.36 | 17.67 | 24.48 |
November | 245.00 | 23.24 | 116.33 | 23.62 | 9.50 | 23.64 |
December | 388.67 | 22.99 | 23.17 | 23.07 | 6.83 | 23.04 |
Annual Sum or Average | 1899.17 | 23.64 | 2962.83 | 24.23 | 269.33 | 24.36 |
Minimum of Months | 38.67 | 22.87 | 23.17 | 23.07 | 0.00 | 23.04 |
Maximum of Months | 388.67 | 27.12 | 500.33 | 24.95 | 56.67 | 25.12 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 192.50 | 23.84 | 206.83 | 24.32 | 22.33 | 24.47 |
February | 202.83 | 23.12 | 145.50 | 23.66 | 4.50 | 23.70 |
March | 178.17 | 23.26 | 143.83 | 23.82 | 0.17 | 23.82 |
April | 87.50 | 24.12 | 189.00 | 24.56 | 6.83 | 24.63 |
May | 51.00 | 24.08 | 180.67 | 24.77 | 1.33 | 24.79 |
June | 21.50 | 26.89 | 364.33 | 24.75 | 20.50 | 24.87 |
July | 43.67 | 26.91 | 463.50 | 24.83 | 43.17 | 24.99 |
August | 37.50 | 26.94 | 493.67 | 24.67 | 37.17 | 24.82 |
September | 48.83 | 26.86 | 462.67 | 24.82 | 48.83 | 25.00 |
October | 121.50 | 24.62 | 294.83 | 24.75 | 38.50 | 24.93 |
November | 143.00 | 23.97 | 262.83 | 24.38 | 23.00 | 24.49 |
December | 243.33 | 23.59 | 139.83 | 24.09 | 24.33 | 24.21 |
Annual Sum or Average | 1371.33 | 24.06 | 3347.50 | 24.48 | 270.67 | 24.61 |
Minimum of Months | 21.50 | 23.12 | 139.83 | 23.66 | 0.17 | 23.70 |
Maximum of Months | 243.33 | 26.94 | 493.67 | 24.83 | 48.83 | 25.00 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 258.33 | 23.39 | 95.00 | 23.76 | 4.00 | 23.80 |
February | 137.00 | 23.25 | 166.50 | 23.95 | 1.83 | 23.97 |
March | 74.67 | 23.74 | 250.33 | 24.47 | 5.50 | 24.51 |
April | 34.67 | 26.76 | 334.67 | 25.02 | 29.67 | 25.18 |
May | 29.17 | 26.48 | 283.00 | 25.01 | 22.67 | 25.16 |
June | 32.17 | 27.12 | 438.50 | 24.75 | 32.17 | 24.90 |
July | 79.50 | 26.78 | 482.83 | 24.97 | 79.50 | 25.19 |
August | 90.00 | 26.26 | 506.00 | 24.80 | 90.00 | 24.99 |
September | 37.50 | 26.65 | 467.50 | 24.67 | 37.50 | 24.81 |
October | 78.67 | 24.59 | 297.67 | 24.73 | 22.67 | 24.86 |
November | 88.83 | 24.42 | 237.17 | 24.68 | 21.17 | 24.81 |
December | 165.00 | 23.86 | 123.67 | 24.46 | 8.67 | 24.54 |
Annual Sum or Average | 1105.50 | 24.52 | 3682.83 | 24.64 | 355.33 | 24.79 |
Minimum of Months | 29.17 | 23.25 | 95.00 | 23.76 | 1.83 | 23.80 |
Maximum of Months | 258.33 | 27.12 | 506.00 | 25.02 | 90.00 | 25.19 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.31 | 40.17 | 22.14 | 40.17 | 22.01 |
February | 439.67 | 22.13 | 7.17 | 22.11 | 7.17 | 22.08 |
March | 426.83 | 22.72 | 25.33 | 22.65 | 19.50 | 22.57 |
April | 215.00 | 23.66 | 31.67 | 23.84 | 0.00 | 23.84 |
May | 103.67 | 23.93 | 66.67 | 24.59 | 0.00 | 24.59 |
June | 14.50 | 26.09 | 274.00 | 24.84 | 10.33 | 24.91 |
July | 31.17 | 26.09 | 450.33 | 24.67 | 28.67 | 24.76 |
August | 31.33 | 25.29 | 463.17 | 24.43 | 25.17 | 24.49 |
September | 43.17 | 25.50 | 411.17 | 24.59 | 36.17 | 24.68 |
October | 287.83 | 23.14 | 109.83 | 23.48 | 3.33 | 23.47 |
November | 429.33 | 22.54 | 91.33 | 22.59 | 62.83 | 22.54 |
December | 497.00 | 21.74 | 146.33 | 21.52 | 146.33 | 21.38 |
Annual Sum or Average | 3021.50 | 22.64 | 2117.17 | 23.24 | 379.67 | 23.18 |
Minimum of Months | 14.50 | 21.74 | 7.17 | 21.52 | 0.00 | 21.38 |
Maximum of Months | 502.00 | 26.09 | 463.17 | 24.84 | 146.33 | 24.91 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 363.33 | 22.49 | 29.33 | 22.46 | 18.83 | 22.37 |
February | 317.00 | 22.22 | 28.83 | 22.38 | 3.50 | 22.36 |
March | 284.50 | 22.68 | 60.83 | 22.99 | 9.00 | 22.94 |
April | 99.17 | 24.01 | 150.00 | 24.67 | 14.83 | 24.82 |
May | 56.83 | 25.09 | 197.83 | 25.11 | 22.17 | 25.29 |
June | 40.67 | 26.83 | 314.00 | 24.97 | 36.83 | 25.17 |
July | 54.67 | 26.82 | 393.83 | 24.99 | 53.33 | 25.19 |
August | 45.83 | 26.53 | 406.83 | 24.73 | 43.00 | 24.91 |
September | 55.50 | 25.97 | 365.00 | 24.81 | 45.67 | 24.98 |
October | 181.33 | 23.20 | 154.50 | 23.95 | 7.83 | 24.00 |
November | 308.33 | 22.63 | 67.67 | 22.82 | 30.50 | 22.80 |
December | 408.67 | 22.11 | 76.17 | 21.91 | 75.67 | 21.77 |
Annual Sum or Average | 2215.83 | 22.98 | 2244.83 | 23.76 | 361.17 | 23.83 |
Minimum of Months | 40.67 | 22.11 | 28.83 | 21.91 | 3.50 | 21.77 |
Maximum of Months | 408.67 | 26.83 | 406.83 | 25.11 | 75.67 | 25.29 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 228.50 | 23.47 | 199.33 | 24.06 | 28.67 | 24.17 |
February | 258.83 | 22.62 | 127.17 | 23.22 | 5.67 | 23.24 |
March | 247.67 | 22.89 | 116.83 | 23.34 | 9.17 | 23.27 |
April | 127.67 | 23.70 | 155.83 | 24.33 | 4.00 | 24.38 |
May | 100.83 | 23.82 | 110.50 | 24.56 | 0.00 | 24.56 |
June | 26.50 | 25.07 | 256.67 | 24.75 | 9.67 | 24.82 |
July | 43.17 | 25.92 | 442.33 | 24.68 | 36.00 | 24.79 |
August | 40.33 | 25.81 | 477.17 | 24.53 | 34.17 | 24.63 |
September | 52.17 | 26.40 | 438.00 | 24.78 | 49.50 | 24.95 |
October | 149.00 | 24.11 | 264.67 | 24.55 | 31.50 | 24.72 |
November | 203.00 | 23.48 | 228.67 | 24.06 | 41.50 | 24.15 |
December | 281.67 | 23.02 | 143.33 | 23.50 | 42.17 | 23.51 |
Annual Sum or Average | 1759.33 | 23.51 | 2960.50 | 24.20 | 292.00 | 24.28 |
Minimum of Months | 26.50 | 22.62 | 110.50 | 23.22 | 0.00 | 23.24 |
Maximum of Months | 281.67 | 26.40 | 477.17 | 24.78 | 49.50 | 24.95 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 391.83 | 22.34 | 50.33 | 22.46 | 14.17 | 22.39 |
February | 382.83 | 22.13 | 28.00 | 22.26 | 2.17 | 22.25 |
March | 343.83 | 22.65 | 80.00 | 22.92 | 10.17 | 22.88 |
April | 128.50 | 23.88 | 185.33 | 24.45 | 16.17 | 24.58 |
May | 90.83 | 24.47 | 211.67 | 24.81 | 19.67 | 24.96 |
June | 26.67 | 26.55 | 348.00 | 24.79 | 22.33 | 24.92 |
July | 45.67 | 26.78 | 461.50 | 24.79 | 43.67 | 24.96 |
August | 34.00 | 26.49 | 487.50 | 24.57 | 33.00 | 24.69 |
September | 47.17 | 25.94 | 432.17 | 24.67 | 40.17 | 24.80 |
October | 222.33 | 23.20 | 184.17 | 23.83 | 10.67 | 23.91 |
November | 332.67 | 22.61 | 113.83 | 23.00 | 30.83 | 23.02 |
December | 440.67 | 22.02 | 84.33 | 21.94 | 71.67 | 21.81 |
Annual Sum or Average | 2487.00 | 22.81 | 2666.83 | 23.66 | 314.67 | 23.71 |
Minimum of Months | 26.67 | 22.02 | 28.00 | 21.94 | 2.17 | 21.81 |
Maximum of Months | 440.67 | 26.78 | 487.50 | 24.81 | 71.67 | 24.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.69 | 119.67 | 21.40 | 119.67 | 21.20 |
February | 449.17 | 21.49 | 87.00 | 21.29 | 87.00 | 21.14 |
March | 449.50 | 22.23 | 60.83 | 22.05 | 56.50 | 21.88 |
April | 222.50 | 23.36 | 54.83 | 23.62 | 3.33 | 23.59 |
May | 111.67 | 23.76 | 95.00 | 24.43 | 0.17 | 24.43 |
June | 27.50 | 26.07 | 321.67 | 24.78 | 19.17 | 24.89 |
July | 49.33 | 26.01 | 451.83 | 24.71 | 44.50 | 24.84 |
August | 52.17 | 25.09 | 469.33 | 24.44 | 44.50 | 24.51 |
September | 78.83 | 25.03 | 416.17 | 24.58 | 58.17 | 24.69 |
October | 314.17 | 22.71 | 133.33 | 23.00 | 35.17 | 22.91 |
November | 445.67 | 21.96 | 147.50 | 21.81 | 130.00 | 21.66 |
December | 497.00 | 21.07 | 273.50 | 20.85 | 273.50 | 20.74 |
Annual Sum or Average | 3199.50 | 22.21 | 2630.67 | 22.78 | 871.67 | 22.62 |
Minimum of Months | 27.50 | 21.07 | 54.83 | 20.85 | 0.17 | 20.74 |
Maximum of Months | 502.00 | 26.07 | 469.33 | 24.78 | 273.50 | 24.89 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 460.17 | 22.33 | 63.00 | 22.09 | 60.67 | 21.89 |
February | 391.33 | 21.93 | 57.33 | 21.83 | 45.83 | 21.69 |
March | 337.33 | 22.48 | 69.83 | 22.62 | 21.17 | 22.52 |
April | 103.00 | 23.80 | 212.50 | 24.47 | 15.83 | 24.58 |
May | 64.00 | 25.06 | 288.83 | 24.83 | 25.83 | 25.00 |
June | 47.83 | 26.71 | 411.83 | 24.79 | 42.00 | 24.98 |
July | 63.67 | 26.72 | 470.00 | 24.88 | 61.33 | 25.08 |
August | 54.50 | 26.42 | 491.67 | 24.64 | 50.67 | 24.81 |
September | 68.83 | 25.76 | 441.83 | 24.70 | 54.17 | 24.87 |
October | 209.83 | 22.99 | 199.17 | 23.66 | 22.83 | 23.63 |
November | 377.50 | 22.34 | 100.17 | 22.33 | 69.83 | 22.22 |
December | 497.00 | 21.68 | 158.17 | 21.41 | 158.17 | 21.24 |
Annual Sum or Average | 2675.00 | 22.70 | 2964.33 | 23.43 | 628.33 | 23.41 |
Minimum of Months | 47.83 | 21.68 | 57.33 | 21.41 | 15.83 | 21.24 |
Maximum of Months | 497.00 | 26.72 | 491.67 | 24.88 | 158.17 | 25.08 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 255.17 | 22.83 | 195.50 | 23.34 | 47.17 | 23.28 |
February | 292.17 | 22.01 | 130.83 | 22.41 | 33.83 | 22.26 |
March | 289.83 | 22.49 | 112.83 | 22.79 | 27.00 | 22.65 |
April | 153.00 | 23.47 | 169.17 | 24.14 | 8.00 | 24.19 |
May | 120.17 | 23.69 | 147.67 | 24.38 | 2.17 | 24.41 |
June | 42.67 | 25.16 | 297.50 | 24.70 | 17.67 | 24.81 |
July | 55.00 | 25.82 | 443.50 | 24.70 | 46.17 | 24.83 |
August | 58.17 | 25.45 | 479.83 | 24.52 | 50.83 | 24.62 |
September | 74.00 | 25.72 | 438.00 | 24.75 | 60.83 | 24.91 |
October | 178.00 | 23.62 | 260.00 | 24.20 | 38.67 | 24.32 |
November | 241.17 | 22.83 | 223.50 | 23.38 | 58.67 | 23.29 |
December | 318.00 | 22.43 | 175.67 | 22.61 | 95.33 | 22.42 |
Annual Sum or Average | 2077.33 | 23.07 | 3074.00 | 23.82 | 486.33 | 23.81 |
Minimum of Months | 42.67 | 22.01 | 112.83 | 22.41 | 2.17 | 22.26 |
Maximum of Months | 318.00 | 25.82 | 479.83 | 24.75 | 95.33 | 24.91 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 404.67 | 21.87 | 94.83 | 21.81 | 66.67 | 21.63 |
February | 395.50 | 21.65 | 58.33 | 21.66 | 37.50 | 21.57 |
March | 371.33 | 22.25 | 95.50 | 22.44 | 32.00 | 22.33 |
April | 155.00 | 23.59 | 189.17 | 24.24 | 18.50 | 24.38 |
May | 113.83 | 24.20 | 225.17 | 24.65 | 21.83 | 24.81 |
June | 34.50 | 26.27 | 369.50 | 24.75 | 25.83 | 24.90 |
July | 59.50 | 26.48 | 457.50 | 24.81 | 54.17 | 24.99 |
August | 49.50 | 25.97 | 489.17 | 24.56 | 45.33 | 24.68 |
September | 75.67 | 25.20 | 429.50 | 24.63 | 54.83 | 24.76 |
October | 250.17 | 22.83 | 188.33 | 23.50 | 24.50 | 23.54 |
November | 360.17 | 22.16 | 139.67 | 22.36 | 72.33 | 22.26 |
December | 453.67 | 21.54 | 183.00 | 21.35 | 174.00 | 21.20 |
Annual Sum or Average | 2723.50 | 22.48 | 2919.67 | 23.30 | 627.50 | 23.26 |
Minimum of Months | 34.50 | 21.54 | 58.33 | 21.35 | 18.50 | 21.20 |
Maximum of Months | 453.67 | 26.48 | 489.17 | 24.81 | 174.00 | 24.99 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.83 | 27.00 | 502.00 | 27.00 | 2.83 | 27.00 |
February | 8.50 | 27.00 | 454.00 | 27.00 | 8.50 | 27.00 |
March | 29.17 | 27.00 | 514.00 | 27.00 | 29.17 | 27.00 |
April | 244.00 | 28.54 | 485.00 | 28.06 | 244.00 | 28.18 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 71.67 | 27.00 | 496.00 | 27.00 | 71.67 | 27.00 |
July | 370.17 | 27.00 | 497.00 | 27.00 | 370.17 | 27.00 |
August | 503.67 | 27.67 | 514.00 | 27.67 | 503.67 | 27.67 |
September | 104.50 | 27.00 | 485.00 | 27.00 | 104.50 | 27.00 |
October | 69.50 | 27.00 | 502.00 | 27.00 | 69.50 | 27.00 |
November | 65.17 | 27.00 | 489.00 | 27.00 | 65.17 | 27.00 |
December | 29.50 | 27.41 | 497.00 | 27.05 | 29.50 | 27.07 |
Annual Sum or Average | 1498.67 | 27.48 | 5943.00 | 27.20 | 1498.67 | 27.25 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 503.67 | 28.54 | 514.00 | 28.06 | 503.67 | 28.18 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
April | 151.67 | 28.81 | 485.00 | 27.99 | 151.67 | 28.15 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 5.33 | 27.00 | 496.00 | 27.00 | 5.33 | 27.00 |
July | 48.17 | 27.00 | 497.00 | 27.00 | 48.17 | 27.00 |
August | 228.50 | 28.19 | 514.00 | 27.75 | 228.50 | 27.85 |
September | 12.83 | 27.00 | 485.00 | 27.00 | 12.83 | 27.00 |
October | 5.50 | 27.00 | 502.00 | 27.00 | 5.50 | 27.00 |
November | 8.17 | 27.00 | 489.00 | 27.00 | 8.17 | 27.00 |
December | 1.50 | 27.58 | 491.50 | 27.01 | 1.50 | 27.01 |
Annual Sum or Average | 461.67 | 28.19 | 5937.50 | 27.19 | 461.67 | 27.25 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 228.50 | 28.81 | 514.00 | 27.99 | 228.50 | 28.15 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.17 | 24.64 | 463.50 | 26.94 | 0.00 | 26.94 |
February | 0.00 | 0.00 | 447.33 | 27.00 | 0.00 | 27.00 |
March | 0.67 | 27.00 | 501.17 | 27.00 | 0.67 | 27.00 |
April | 142.50 | 28.75 | 485.00 | 27.87 | 142.50 | 28.04 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 30.17 | 27.00 | 496.00 | 27.00 | 30.17 | 27.00 |
July | 132.50 | 27.00 | 497.00 | 27.00 | 132.50 | 27.00 |
August | 229.67 | 28.02 | 514.00 | 27.64 | 229.67 | 27.73 |
September | 42.67 | 27.00 | 485.00 | 27.00 | 42.67 | 27.00 |
October | 18.00 | 27.00 | 502.00 | 27.00 | 18.00 | 27.00 |
November | 9.33 | 27.00 | 474.67 | 27.00 | 9.33 | 27.00 |
December | 0.67 | 27.48 | 404.17 | 27.00 | 0.67 | 27.00 |
Annual Sum or Average | 617.33 | 27.74 | 5777.83 | 27.16 | 606.17 | 27.21 |
Minimum of Months | 0.00 | 0.00 | 404.17 | 26.94 | 0.00 | 26.94 |
Maximum of Months | 229.67 | 28.75 | 514.00 | 27.87 | 229.67 | 28.04 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 433.00 | 27.00 | 502.00 | 27.00 | 433.00 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.48 | 485.00 | 27.48 | 485.00 | 27.48 |
May | 446.17 | 27.00 | 508.00 | 27.00 | 446.17 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
August | 514.00 | 27.34 | 514.00 | 27.34 | 514.00 | 27.34 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5812.17 | 27.07 | 5943.00 | 27.07 | 5812.17 | 27.07 |
Minimum of Months | 433.00 | 27.00 | 454.00 | 27.00 | 433.00 | 27.00 |
Maximum of Months | 514.00 | 27.48 | 514.00 | 27.48 | 514.00 | 27.48 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00001 | 22.79932 | 0.81914 | 19.25410 |
February | 454.00000 | 27.00023 | 29.32168 | 0.89107 | 21.83930 |
March | 514.00000 | 27.00003 | 26.51067 | 0.91928 | 22.94198 |
April | 485.00000 | 27.81602 | 18.28260 | 1.05755 | 29.12742 |
May | 508.00000 | 27.00000 | 17.54048 | 0.17762 | 5.73737 |
June | 496.00000 | 27.00000 | 23.64316 | 0.31013 | 7.10648 |
July | 497.00000 | 27.00027 | 33.03171 | 0.42655 | 8.91204 |
August | 514.00000 | 27.65959 | 33.80201 | 0.63345 | 14.49957 |
September | 485.00000 | 27.00076 | 34.43858 | 0.33134 | 7.37868 |
October | 502.00000 | 27.00010 | 25.17970 | 0.91040 | 22.66668 |
November | 489.00000 | 27.00014 | 24.62866 | 0.91756 | 22.91396 |
December | 497.00000 | 27.02791 | 17.34158 | 0.87116 | 21.15697 |
Annual Sum or Average | 5943.00000 | 27.12610 | 25.52322 | 0.68689 | 16.91037 |
Minimum of Months | 454.00000 | 27.00000 | 17.34158 | 0.17762 | 5.73737 |
Maximum of Months | 514.00000 | 27.81602 | 34.43858 | 1.05755 | 29.12742 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00001 | 22.78382 | 0.73817 | 16.61249 |
February | 454.00000 | 27.00021 | 29.34567 | 0.78922 | 18.23636 |
March | 514.00000 | 27.00003 | 26.48217 | 0.81446 | 19.13199 |
April | 485.00000 | 27.72972 | 18.29052 | 0.95119 | 24.72672 |
May | 508.00000 | 27.00000 | 17.51523 | 0.11016 | 5.35972 |
June | 496.00000 | 27.00000 | 23.62581 | 0.21209 | 6.05578 |
July | 497.00000 | 27.00032 | 33.04897 | 0.29569 | 6.93588 |
August | 514.00000 | 27.54990 | 33.90833 | 0.45527 | 10.33254 |
September | 485.00000 | 27.00064 | 34.52908 | 0.25032 | 6.39864 |
October | 502.00000 | 27.00011 | 25.16227 | 0.82711 | 19.62581 |
November | 489.00000 | 27.00014 | 24.61526 | 0.80208 | 18.76964 |
December | 497.00000 | 27.00576 | 17.33726 | 0.71087 | 15.81586 |
Annual Sum or Average | 5943.00000 | 27.10771 | 25.53341 | 0.57767 | 13.95320 |
Minimum of Months | 454.00000 | 27.00000 | 17.33726 | 0.11016 | 5.35972 |
Maximum of Months | 514.00000 | 27.72972 | 34.52908 | 0.95119 | 24.72672 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.94519 | 22.97097 | 0.68286 | 15.23496 |
February | 454.00000 | 27.00021 | 29.38003 | 0.73880 | 16.70485 |
March | 514.00000 | 27.00003 | 26.49973 | 0.78206 | 18.14179 |
April | 485.00000 | 27.61651 | 18.36594 | 0.92977 | 24.00309 |
May | 508.00000 | 27.00000 | 17.52598 | 0.11974 | 5.49347 |
June | 496.00000 | 27.00000 | 23.63401 | 0.23862 | 6.37488 |
July | 497.00000 | 27.00033 | 33.04381 | 0.32098 | 7.31912 |
August | 514.00000 | 27.46975 | 33.96354 | 0.45525 | 10.47231 |
September | 485.00000 | 27.00067 | 34.51706 | 0.26272 | 6.58903 |
October | 502.00000 | 27.00011 | 25.17335 | 0.80867 | 19.08953 |
November | 489.00000 | 27.00015 | 24.63154 | 0.75924 | 17.48302 |
December | 497.00000 | 27.00097 | 17.34843 | 0.64506 | 14.05417 |
Annual Sum or Average | 5943.00000 | 27.08651 | 25.56769 | 0.56017 | 13.37440 |
Minimum of Months | 454.00000 | 26.94519 | 17.34843 | 0.11974 | 5.49347 |
Maximum of Months | 514.00000 | 27.61651 | 34.51706 | 0.92977 | 24.00309 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00001 | 25.27716 | 1.04472 | 28.08792 |
February | 454.00000 | 27.00006 | 30.94380 | 1.22007 | 36.25563 |
March | 514.00000 | 27.00111 | 25.41906 | 1.31643 | 41.14896 |
April | 485.00000 | 27.48136 | 21.45847 | 1.52534 | 52.14778 |
May | 508.00000 | 27.00039 | 26.05270 | 0.48417 | 9.98908 |
June | 496.00000 | 27.00324 | 29.35940 | 0.75773 | 17.13124 |
July | 497.00000 | 27.01405 | 35.96862 | 1.04293 | 28.06081 |
August | 514.00000 | 27.34277 | 36.55390 | 1.34500 | 42.70356 |
September | 485.00000 | 27.00134 | 38.32942 | 0.68626 | 15.03939 |
October | 502.00000 | 27.00101 | 27.10598 | 1.26232 | 38.41841 |
November | 489.00000 | 27.00170 | 25.45158 | 1.37171 | 44.06783 |
December | 497.00000 | 27.00019 | 17.38063 | 1.41928 | 46.55267 |
Annual Sum or Average | 5943.00000 | 27.07086 | 28.26072 | 1.12215 | 33.27205 |
Minimum of Months | 454.00000 | 27.00001 | 17.38063 | 0.48417 | 9.98908 |
Maximum of Months | 514.00000 | 27.48136 | 38.32942 | 1.52534 | 52.14778 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.79607 | 22.86786 | 0.44845 | 10.94681 |
February | 454.00000 | 24.67857 | 32.60285 | 0.47541 | 10.47661 |
March | 514.00000 | 24.60904 | 26.35987 | 0.41850 | 9.32195 |
April | 485.00000 | 25.36796 | 25.20308 | 0.58562 | 15.48600 |
May | 508.00000 | 27.30947 | 57.32800 | 0.66574 | 28.51242 |
June | 496.00000 | 29.81029 | 96.39941 | 1.83490 | 69.61915 |
July | 497.00000 | 30.45098 | 93.85293 | 2.05609 | 78.78474 |
August | 514.00000 | 30.65052 | 95.80957 | 2.15849 | 82.19667 |
September | 485.00000 | 29.22490 | 81.83450 | 1.55763 | 59.31787 |
October | 502.00000 | 26.23960 | 38.11272 | 0.93115 | 29.56539 |
November | 489.00000 | 24.99222 | 26.60659 | 0.53303 | 12.88464 |
December | 497.00000 | 24.83064 | 14.63195 | 0.40079 | 9.35388 |
Annual Sum or Average | 5943.00000 | 26.93256 | 51.15036 | 1.01001 | 34.92089 |
Minimum of Months | 454.00000 | 24.60904 | 14.63195 | 0.40079 | 9.32195 |
Maximum of Months | 514.00000 | 30.65052 | 96.39941 | 2.15849 | 82.19667 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.32846 | 21.67372 | 0.33847 | 7.71965 |
February | 454.00000 | 24.33346 | 33.89221 | 0.41923 | 9.05912 |
March | 514.00000 | 24.29471 | 26.70929 | 0.37660 | 8.28618 |
April | 485.00000 | 24.27092 | 19.72125 | 0.34962 | 7.74254 |
May | 508.00000 | 24.33443 | 19.31012 | -0.4692 | 10.07542 |
June | 496.00000 | 24.35926 | 27.09589 | -0.3489 | 8.21492 |
July | 497.00000 | 24.49428 | 43.25123 | -0.1795 | 6.68466 |
August | 514.00000 | 24.41813 | 45.39048 | -0.1710 | 6.57792 |
September | 485.00000 | 24.44687 | 45.36080 | -0.2110 | 6.99675 |
October | 502.00000 | 24.44647 | 27.31007 | 0.44447 | 9.86207 |
November | 489.00000 | 24.40693 | 26.84246 | 0.41317 | 9.19656 |
December | 497.00000 | 24.41285 | 15.63264 | 0.32463 | 7.56737 |
Annual Sum or Average | 5943.00000 | 24.37908 | 29.31875 | 0.10416 | 8.16101 |
Minimum of Months | 454.00000 | 24.27092 | 15.63264 | -0.4692 | 6.57792 |
Maximum of Months | 514.00000 | 24.49428 | 45.39048 | 0.44447 | 10.07542 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.89255 | 23.00099 | 0.20635 | 6.34727 |
February | 454.00000 | 23.91841 | 35.51363 | 0.29154 | 7.00695 |
March | 514.00000 | 24.06584 | 27.88368 | 0.28829 | 6.99962 |
April | 485.00000 | 24.14568 | 20.10078 | 0.27881 | 6.81410 |
May | 508.00000 | 24.18803 | 19.50075 | -0.5846 | 12.41352 |
June | 496.00000 | 24.11783 | 27.26201 | -0.5395 | 11.24728 |
July | 497.00000 | 24.17835 | 46.02726 | -0.3979 | 8.69051 |
August | 514.00000 | 24.15960 | 48.80897 | -0.3809 | 8.34766 |
September | 485.00000 | 24.25883 | 47.29831 | -0.3639 | 8.29506 |
October | 502.00000 | 24.20160 | 28.16790 | 0.34016 | 7.82272 |
November | 489.00000 | 24.09702 | 28.32012 | 0.29967 | 7.54225 |
December | 497.00000 | 23.82439 | 17.26568 | 0.14262 | 5.71427 |
Annual Sum or Average | 5943.00000 | 24.08835 | 30.73398 | -0.0382 | 8.11762 |
Minimum of Months | 454.00000 | 23.82439 | 17.26568 | -0.5846 | 5.71427 |
Maximum of Months | 514.00000 | 24.25883 | 48.80897 | 0.34016 | 12.41352 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.15573 | 24.43547 | 0.01606 | 6.62156 |
February | 454.00000 | 23.08962 | 38.09800 | 0.08108 | 6.18272 |
March | 514.00000 | 23.61940 | 28.96162 | 0.17010 | 6.42838 |
April | 485.00000 | 24.08106 | 20.24827 | 0.26807 | 6.77951 |
May | 508.00000 | 24.18939 | 19.65677 | -0.5693 | 12.09421 |
June | 496.00000 | 24.17626 | 27.35688 | -0.4887 | 10.29400 |
July | 497.00000 | 24.25481 | 45.93896 | -0.3444 | 7.95377 |
August | 514.00000 | 24.20019 | 48.89614 | -0.3432 | 7.82834 |
September | 485.00000 | 24.30227 | 47.52154 | -0.3341 | 7.96425 |
October | 502.00000 | 23.94772 | 28.81213 | 0.27416 | 7.34006 |
November | 489.00000 | 23.45116 | 29.67930 | 0.13258 | 6.97636 |
December | 497.00000 | 22.71064 | 18.86828 | -0.1404 | 6.83835 |
Annual Sum or Average | 5943.00000 | 23.76963 | 31.49774 | -0.1087 | 7.79188 |
Minimum of Months | 454.00000 | 22.71064 | 18.86828 | -0.5693 | 6.18272 |
Maximum of Months | 514.00000 | 24.30227 | 48.89614 | 0.27416 | 12.09421 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.49522 | 22.68975 | 0.09583 | 5.68107 |
February | 454.00000 | 23.42406 | 35.51389 | 0.15664 | 6.12880 |
March | 514.00000 | 23.76609 | 27.16016 | 0.20925 | 6.61239 |
April | 485.00000 | 24.26504 | 19.12900 | 0.33750 | 7.79881 |
May | 508.00000 | 24.41996 | 18.49433 | -0.4209 | 9.52190 |
June | 496.00000 | 24.51108 | 26.14016 | -0.2234 | 7.46980 |
July | 497.00000 | 24.63567 | 42.41092 | -0.0766 | 6.73969 |
August | 514.00000 | 24.48243 | 44.66292 | -0.1159 | 6.60907 |
September | 485.00000 | 24.52245 | 44.58633 | -0.1687 | 7.04042 |
October | 502.00000 | 24.17704 | 27.25691 | 0.35069 | 8.77858 |
November | 489.00000 | 23.78316 | 27.49419 | 0.21519 | 6.89442 |
December | 497.00000 | 23.39401 | 16.48516 | 0.02440 | 5.87009 |
Annual Sum or Average | 5943.00000 | 24.07727 | 29.29365 | 0.03026 | 7.10326 |
Minimum of Months | 454.00000 | 23.39401 | 16.48516 | -0.4209 | 5.68107 |
Maximum of Months | 514.00000 | 24.63567 | 44.66292 | 0.35069 | 9.52190 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.60152 | 21.82048 | 0.16597 | 6.58194 |
February | 454.00000 | 23.38905 | 35.03454 | 0.18923 | 7.00697 |
March | 514.00000 | 23.73335 | 26.72811 | 0.24651 | 7.43342 |
April | 485.00000 | 24.29828 | 18.79382 | 0.41911 | 9.67879 |
May | 508.00000 | 24.50713 | 18.21337 | -0.2767 | 8.32472 |
June | 496.00000 | 24.50085 | 26.01821 | -0.1169 | 7.19688 |
July | 497.00000 | 24.61801 | 42.33791 | 0.01003 | 6.89371 |
August | 514.00000 | 24.45986 | 44.56240 | -0.0329 | 6.72142 |
September | 485.00000 | 24.52154 | 44.37642 | -0.0869 | 6.87612 |
October | 502.00000 | 24.19842 | 26.78389 | 0.41541 | 10.36196 |
November | 489.00000 | 23.70992 | 27.22901 | 0.23874 | 7.36684 |
December | 497.00000 | 23.29891 | 15.97132 | 0.03588 | 6.48362 |
Annual Sum or Average | 5943.00000 | 24.07438 | 28.94801 | 0.09924 | 7.57888 |
Minimum of Months | 454.00000 | 23.29891 | 15.97132 | -0.2767 | 6.48362 |
Maximum of Months | 514.00000 | 24.61801 | 44.56240 | 0.41911 | 10.36196 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.14393 | 20.60470 | 0.36804 | 9.67098 |
February | 454.00000 | 23.71229 | 34.06835 | 0.28956 | 8.12757 |
March | 514.00000 | 23.91376 | 26.41384 | 0.29599 | 7.98162 |
April | 485.00000 | 24.33676 | 18.84704 | 0.40396 | 9.23917 |
May | 508.00000 | 24.40428 | 18.47790 | -0.4136 | 9.60860 |
June | 496.00000 | 24.46143 | 26.23607 | -0.2595 | 7.72756 |
July | 497.00000 | 24.59761 | 42.48760 | -0.0938 | 6.82451 |
August | 514.00000 | 24.47557 | 44.63108 | -0.0891 | 6.59110 |
September | 485.00000 | 24.57996 | 44.27727 | -0.0769 | 6.97362 |
October | 502.00000 | 24.44038 | 26.27652 | 0.50827 | 12.29479 |
November | 489.00000 | 24.22384 | 26.09196 | 0.42183 | 10.23961 |
December | 497.00000 | 24.00122 | 14.83418 | 0.27139 | 8.96376 |
Annual Sum or Average | 5943.00000 | 24.27743 | 28.56832 | 0.13329 | 8.68893 |
Minimum of Months | 454.00000 | 23.71229 | 14.83418 | -0.4136 | 6.59110 |
Maximum of Months | 514.00000 | 24.59761 | 44.63108 | 0.50827 | 12.29479 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.85746 | 21.27914 | 0.26049 | 7.46929 |
February | 454.00000 | 23.95053 | 33.59191 | 0.35204 | 8.32913 |
March | 514.00000 | 24.28008 | 25.58692 | 0.43045 | 9.69824 |
April | 485.00000 | 24.57614 | 18.38919 | 0.57137 | 12.96425 |
May | 508.00000 | 24.49484 | 18.23036 | -0.2654 | 8.35823 |
June | 496.00000 | 24.50600 | 26.03521 | -0.0975 | 7.21225 |
July | 497.00000 | 24.64932 | 42.29217 | 0.03767 | 7.19924 |
August | 514.00000 | 24.53402 | 44.39483 | 0.04642 | 7.07074 |
September | 485.00000 | 24.49242 | 44.56699 | -0.0956 | 6.73559 |
October | 502.00000 | 24.43792 | 26.38044 | 0.50438 | 11.60535 |
November | 489.00000 | 24.39018 | 25.77351 | 0.46059 | 10.60467 |
December | 497.00000 | 24.29672 | 14.56534 | 0.33200 | 8.32077 |
Annual Sum or Average | 5943.00000 | 24.37453 | 28.38905 | 0.20957 | 8.79235 |
Minimum of Months | 454.00000 | 23.85746 | 14.56534 | -0.2654 | 6.73559 |
Maximum of Months | 514.00000 | 24.64932 | 44.56699 | 0.57137 | 12.96425 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.30524 | 24.72731 | -0.1975 | 7.29895 |
February | 454.00000 | 22.19005 | 38.64282 | -0.1464 | 6.48145 |
March | 514.00000 | 22.94699 | 29.15911 | -0.0057 | 6.57235 |
April | 485.00000 | 24.01223 | 19.43102 | 0.24142 | 6.80861 |
May | 508.00000 | 24.30672 | 18.25185 | -0.5155 | 11.21550 |
June | 496.00000 | 24.42971 | 25.42425 | -0.3391 | 8.49070 |
July | 497.00000 | 24.52435 | 44.33727 | -0.2045 | 7.05157 |
August | 514.00000 | 24.34910 | 47.36289 | -0.2598 | 7.23007 |
September | 485.00000 | 24.40528 | 46.23895 | -0.2790 | 7.69553 |
October | 502.00000 | 23.61689 | 28.33676 | 0.18357 | 7.42388 |
November | 489.00000 | 22.72929 | 29.89885 | -0.0539 | 7.14733 |
December | 497.00000 | 21.73617 | 18.34738 | -0.3866 | 9.34702 |
Annual Sum or Average | 5943.00000 | 23.47147 | 30.79613 | -0.1646 | 7.74296 |
Minimum of Months | 454.00000 | 21.73617 | 18.25185 | -0.5155 | 6.48145 |
Maximum of Months | 514.00000 | 24.52435 | 47.36289 | 0.24142 | 11.21550 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.75992 | 23.00493 | -0.0567 | 6.84756 |
February | 385.00000 | 22.58155 | 36.94740 | -0.0227 | 6.75559 |
March | 433.00000 | 23.26519 | 27.49276 | 0.10761 | 7.16859 |
April | 410.00000 | 24.35882 | 18.17559 | 0.39606 | 9.67487 |
May | 430.00000 | 24.55373 | 17.31824 | -0.3284 | 9.45925 |
June | 418.00000 | 24.54902 | 24.70520 | -0.1976 | 8.04944 |
July | 422.00000 | 24.68528 | 43.43950 | -0.0662 | 7.21864 |
August | 433.00000 | 24.50005 | 46.23135 | -0.1245 | 7.23744 |
September | 410.00000 | 24.53976 | 45.38431 | -0.1693 | 7.55270 |
October | 427.00000 | 23.93097 | 26.68828 | 0.30597 | 9.28369 |
November | 417.00000 | 23.04339 | 28.61100 | 0.05538 | 6.97287 |
December | 422.00000 | 22.18241 | 16.66133 | -0.2556 | 8.09873 |
Annual Sum or Average | 5034.00000 | 23.75219 | 29.49797 | -0.0304 | 7.86528 |
Minimum of Months | 385.00000 | 22.18241 | 16.66133 | -0.3284 | 6.75559 |
Maximum of Months | 433.00000 | 24.68528 | 46.23135 | 0.39606 | 9.67487 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.96186 | 21.02252 | 0.31921 | 9.88968 |
February | 454.00000 | 23.32339 | 35.14965 | 0.18921 | 7.98302 |
March | 514.00000 | 23.60153 | 27.24652 | 0.20501 | 7.70332 |
April | 485.00000 | 24.23536 | 18.82840 | 0.35048 | 8.61464 |
May | 508.00000 | 24.31918 | 18.17311 | -0.4901 | 11.09999 |
June | 496.00000 | 24.38421 | 25.51965 | -0.3668 | 8.87549 |
July | 497.00000 | 24.50972 | 44.34281 | -0.2035 | 7.23687 |
August | 514.00000 | 24.39085 | 47.11377 | -0.2013 | 7.03008 |
September | 485.00000 | 24.52488 | 45.60968 | -0.1490 | 7.26596 |
October | 502.00000 | 24.30183 | 26.39786 | 0.45187 | 11.48464 |
November | 489.00000 | 23.97628 | 26.85963 | 0.34991 | 9.85203 |
December | 497.00000 | 23.63478 | 15.36743 | 0.16861 | 9.19800 |
Annual Sum or Average | 5943.00000 | 24.10145 | 29.26748 | 0.04971 | 8.86018 |
Minimum of Months | 454.00000 | 23.32339 | 15.36743 | -0.4901 | 7.03008 |
Maximum of Months | 514.00000 | 24.52488 | 47.11377 | 0.45187 | 11.48464 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.76291 | 23.01517 | -0.0308 | 7.16824 |
February | 454.00000 | 22.44390 | 37.22454 | -0.0412 | 6.48573 |
March | 514.00000 | 23.16669 | 27.91594 | 0.10257 | 7.15086 |
April | 485.00000 | 24.23886 | 18.75501 | 0.39490 | 9.67322 |
May | 508.00000 | 24.39650 | 17.94169 | -0.3618 | 9.89280 |
June | 496.00000 | 24.45713 | 25.26380 | -0.2070 | 7.79235 |
July | 497.00000 | 24.55934 | 44.11993 | -0.1063 | 7.17365 |
August | 514.00000 | 24.41141 | 47.00573 | -0.1347 | 7.05754 |
September | 485.00000 | 24.45082 | 45.90139 | -0.1771 | 7.34544 |
October | 502.00000 | 23.81616 | 27.29791 | 0.29716 | 9.08417 |
November | 489.00000 | 23.12232 | 28.28780 | 0.09836 | 7.66959 |
December | 497.00000 | 22.27603 | 16.80780 | -0.2125 | 8.14803 |
Annual Sum or Average | 5943.00000 | 23.68333 | 29.91490 | -0.0324 | 7.89437 |
Minimum of Months | 454.00000 | 22.27603 | 16.80780 | -0.3618 | 6.48573 |
Maximum of Months | 514.00000 | 24.55934 | 47.00573 | 0.39490 | 9.89280 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.69344 | 25.46862 | -0.3593 | 9.93471 |
February | 454.00000 | 21.51470 | 40.19348 | -0.3236 | 8.77013 |
March | 514.00000 | 22.46411 | 29.78967 | -0.1298 | 7.77075 |
April | 485.00000 | 23.87406 | 19.70212 | 0.21566 | 7.07334 |
May | 508.00000 | 24.26385 | 18.55273 | -0.5144 | 11.60796 |
June | 496.00000 | 24.43519 | 25.81575 | -0.3072 | 8.28879 |
July | 497.00000 | 24.53255 | 44.52672 | -0.1746 | 7.07659 |
August | 514.00000 | 24.34686 | 47.66069 | -0.2379 | 7.22068 |
September | 485.00000 | 24.39482 | 46.69688 | -0.2663 | 7.84585 |
October | 502.00000 | 23.28488 | 28.82484 | 0.10314 | 7.93829 |
November | 489.00000 | 22.13961 | 30.72653 | -0.2071 | 8.97547 |
December | 497.00000 | 21.06705 | 18.82274 | -0.5765 | 13.79312 |
Annual Sum or Average | 5943.00000 | 23.17907 | 31.34032 | -0.2318 | 8.86162 |
Minimum of Months | 454.00000 | 21.06705 | 18.55273 | -0.5765 | 7.07334 |
Maximum of Months | 514.00000 | 24.53255 | 47.66069 | 0.21566 | 13.79312 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.47014 | 23.71307 | -0.1392 | 7.78625 |
February | 454.00000 | 22.22257 | 38.08977 | -0.1246 | 7.52830 |
March | 514.00000 | 23.06850 | 28.07499 | 0.05696 | 7.34973 |
April | 485.00000 | 24.25875 | 18.74716 | 0.39986 | 9.82270 |
May | 508.00000 | 24.45716 | 18.05109 | -0.3152 | 9.17941 |
June | 496.00000 | 24.47002 | 25.58360 | -0.1632 | 7.63463 |
July | 497.00000 | 24.59448 | 44.19285 | -0.0385 | 7.09566 |
August | 514.00000 | 24.42148 | 47.18175 | -0.0939 | 7.01127 |
September | 485.00000 | 24.45487 | 46.17106 | -0.1514 | 7.41943 |
October | 502.00000 | 23.77479 | 27.42942 | 0.28001 | 9.33190 |
November | 489.00000 | 22.72101 | 29.30165 | -0.0311 | 7.51243 |
December | 497.00000 | 21.68045 | 17.60549 | -0.3955 | 10.37291 |
Annual Sum or Average | 5943.00000 | 23.55890 | 30.29367 | -0.0599 | 8.17105 |
Minimum of Months | 454.00000 | 21.68045 | 17.60549 | -0.3955 | 7.01127 |
Maximum of Months | 514.00000 | 24.59448 | 47.18175 | 0.39986 | 10.37291 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.54920 | 21.67097 | 0.20032 | 9.75835 |
February | 454.00000 | 22.80236 | 36.58578 | 0.04574 | 8.36236 |
March | 514.00000 | 23.24858 | 27.85844 | 0.10797 | 7.98584 |
April | 485.00000 | 24.10701 | 19.11993 | 0.32738 | 8.81878 |
May | 508.00000 | 24.25428 | 18.50274 | -0.4950 | 11.73344 |
June | 496.00000 | 24.38381 | 25.91833 | -0.3369 | 8.71784 |
July | 497.00000 | 24.51084 | 44.55728 | -0.1759 | 7.31536 |
August | 514.00000 | 24.38025 | 47.45524 | -0.1817 | 7.11936 |
September | 485.00000 | 24.50726 | 46.12095 | -0.1379 | 7.49557 |
October | 502.00000 | 24.07743 | 26.86209 | 0.39421 | 11.26460 |
November | 489.00000 | 23.58074 | 27.58081 | 0.23772 | 9.42975 |
December | 497.00000 | 23.12524 | 15.90420 | 0.01405 | 9.82151 |
Annual Sum or Average | 5943.00000 | 23.88383 | 29.80277 | -0.0016 | 8.99199 |
Minimum of Months | 454.00000 | 22.80236 | 15.90420 | -0.4950 | 7.11936 |
Maximum of Months | 514.00000 | 24.51084 | 47.45524 | 0.39421 | 11.73344 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.32654 | 23.65370 | -0.1503 | 8.61123 |
February | 454.00000 | 21.96110 | 38.45487 | -0.1724 | 7.67446 |
March | 514.00000 | 22.79363 | 28.44553 | 0.00497 | 7.76184 |
April | 485.00000 | 24.10093 | 19.03380 | 0.36957 | 9.83948 |
May | 508.00000 | 24.32737 | 18.27929 | -0.3683 | 10.61182 |
June | 496.00000 | 24.45300 | 25.69304 | -0.1798 | 7.89013 |
July | 497.00000 | 24.55273 | 44.36520 | -0.0829 | 7.38711 |
August | 514.00000 | 24.39238 | 47.37494 | -0.1190 | 7.26262 |
September | 485.00000 | 24.42226 | 46.43423 | -0.1699 | 7.65332 |
October | 502.00000 | 23.56144 | 27.75049 | 0.23533 | 9.30945 |
November | 489.00000 | 22.69116 | 28.97830 | -0.0169 | 8.34440 |
December | 497.00000 | 21.77911 | 17.26785 | -0.3580 | 10.60415 |
Annual Sum or Average | 5943.00000 | 23.45673 | 30.42551 | -0.0843 | 8.58377 |
Minimum of Months | 454.00000 | 21.77911 | 17.26785 | -0.3683 | 7.26262 |
Maximum of Months | 514.00000 | 24.55273 | 47.37494 | 0.36957 | 10.61182 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.517982E+11 | 159342.34 | 27-JAN-14:20 | 315.14 | 0.464890E+12 | 0.00 | 0.516689E+12 | 4.01 | 10.00 | 16-JAN-12:13 | 0.00 | 0.00 |
February | 0.112149E+11 | 67763.76 | 22-FEB-16:00 | 214.96 | 0.109584E+12 | 0.00 | 0.120799E+12 | 3.12 | 10.00 | 28-FEB-16:30 | 0.00 | 0.00 |
March | 0.490729E+11 | 184599.71 | 17-MAR-13:00 | 368.09 | 0.443395E+12 | 0.00 | 0.492468E+12 | 4.72 | 10.00 | 18-MAR-10:00 | 0.00 | 0.00 |
April | 0.105043E+12 | 170585.15 | 11-APR-11:50 | 556.08 | 0.937762E+12 | 0.00 | 0.104280E+13 | 7.22 | 10.01 | 14-APR-05:04 | 0.00 | 0.00 |
May | 0.126783E+12 | 165584.15 | 05-MAY-09:30 | 539.64 | 0.112342E+13 | 0.00 | 0.125020E+13 | 6.68 | 10.05 | 17-MAY-04:12 | 0.00 | 0.00 |
June | 0.150825E+12 | 180254.78 | 17-JUN-08:30 | 648.04 | 0.133212E+13 | 0.00 | 0.148294E+13 | 8.29 | 10.04 | 10-JUN-04:12 | 0.00 | 0.00 |
July | 0.160967E+12 | 198421.63 | 14-JUL-05:03 | 685.56 | 0.137427E+13 | 0.00 | 0.153524E+13 | 8.33 | 10.06 | 03-JUL-04:12 | 0.00 | 0.00 |
August | 0.161774E+12 | 192207.59 | 17-AUG-18:40 | 683.07 | 0.138234E+13 | 0.00 | 0.154412E+13 | 8.30 | 10.03 | 24-AUG-04:12 | 0.00 | 0.00 |
September | 0.142234E+12 | 192155.05 | 01-SEP-05:04 | 571.83 | 0.120857E+13 | 0.00 | 0.135080E+13 | 7.14 | 10.03 | 30-SEP-04:12 | 0.00 | 0.00 |
October | 0.878237E+11 | 189279.13 | 03-OCT-07:10 | 457.87 | 0.780162E+12 | 0.00 | 0.867986E+12 | 5.75 | 10.03 | 07-OCT-04:12 | 0.00 | 0.00 |
November | 0.523463E+11 | 185313.43 | 01-NOV-12:30 | 329.02 | 0.461967E+12 | 0.00 | 0.514313E+12 | 4.30 | 10.00 | 24-NOV-13:55 | 0.00 | 0.00 |
December | 0.254506E+11 | 155135.77 | 22-DEC-16:20 | 241.32 | 0.236576E+12 | 0.00 | 0.262026E+12 | 3.13 | 10.00 | 25-DEC-12:46 | 0.00 | 0.00 |
Annual Sum or Average | 0.112533E+13 | 5610.61 | 0.985505E+13 | 0.00 | 0.109804E+14 | 5.93 | 0.00 | 0.00 | ||||
Minimum of Months | 0.112149E+11 | 67763.76 | 214.96 | 0.109584E+12 | 0.00 | 0.120799E+12 | 3.12 | 10.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.161774E+12 | 198421.63 | 685.56 | 0.138234E+13 | 0.00 | 0.154412E+13 | 8.33 | 10.06 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.404232E+09 | 82667.31 | 31-JAN-16:20 | 2.00 | 0.379720E+10 | 0.00 | 0.420143E+10 | 0.03 | 10.66 | 27-JAN-14:50 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.718475E+09 | 80529.24 | 20-MAR-14:40 | 3.00 | 0.668847E+10 | 0.00 | 0.740694E+10 | 0.04 | 10.69 | 20-MAR-14:30 | 0.00 | 0.00 |
April | 0.220969E+11 | 101053.86 | 24-APR-10:25 | 84.11 | 0.203718E+12 | 0.00 | 0.225815E+12 | 1.08 | 10.72 | 11-APR-09:45 | 0.00 | 0.00 |
May | 0.343995E+11 | 106879.20 | 20-MAY-16:02 | 129.54 | 0.316642E+12 | 0.00 | 0.351042E+12 | 1.61 | 10.70 | 23-MAY-18:30 | 0.00 | 0.00 |
June | 0.664368E+11 | 123495.51 | 19-JUN-14:10 | 232.00 | 0.595652E+12 | 0.00 | 0.662089E+12 | 2.91 | 10.71 | 09-JUN-07:20 | 0.00 | 0.00 |
July | 0.617351E+11 | 198421.63 | 14-JUL-05:03 | 206.83 | 0.536102E+12 | 0.00 | 0.597837E+12 | 2.44 | 10.71 | 01-JUL-11:10 | 0.00 | 0.00 |
August | 0.672840E+11 | 144631.02 | 28-AUG-16:20 | 223.25 | 0.583526E+12 | 0.00 | 0.650810E+12 | 2.62 | 10.70 | 23-AUG-19:30 | 0.00 | 0.00 |
September | 0.485766E+11 | 192155.05 | 01-SEP-05:04 | 163.30 | 0.424210E+12 | 0.00 | 0.472787E+12 | 2.00 | 10.70 | 18-SEP-18:30 | 0.00 | 0.00 |
October | 0.196428E+11 | 102417.51 | 04-OCT-15:00 | 70.89 | 0.176358E+12 | 0.00 | 0.196001E+12 | 0.86 | 10.70 | 17-OCT-16:20 | 0.00 | 0.00 |
November | 0.200805E+10 | 86974.12 | 20-NOV-16:20 | 8.75 | 0.185210E+11 | 0.00 | 0.205291E+11 | 0.11 | 10.70 | 20-NOV-16:50 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.323303E+12 | 1123.67 | 0.286521E+13 | 0.00 | 0.318852E+13 | 1.15 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.672840E+11 | 198421.63 | 232.00 | 0.595652E+12 | 0.00 | 0.662089E+12 | 2.91 | 10.72 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.451658E+11 | 744.00 | 49248.27 | 02-JAN-12:10 | 242764.42 | 27-JAN-16:00 | 20.32 | 19.56 | 16.13 |
February | 0.154356E+11 | 672.00 | 49248.27 | 06-FEB-14:00 | 164232.93 | 18-FEB-14:10 | 19.49 | 18.45 | 16.13 |
March | 0.563363E+11 | 744.00 | 49248.27 | 01-MAR-10:20 | 541352.95 | 16-MAR-16:00 | 23.25 | 20.25 | 16.13 |
April | 0.111219E+12 | 720.00 | 49248.27 | 01-APR-07:15 | 733429.89 | 24-APR-12:50 | 35.53 | 26.90 | 16.13 |
May | 0.122608E+12 | 744.00 | 49248.27 | 01-MAY-00:05 | 373691.90 | 31-MAY-23:13 | 30.24 | 27.45 | 16.13 |
June | 0.127652E+12 | 720.00 | 49248.27 | 01-JUN-00:03 | 539654.67 | 30-JUN-23:23 | 39.83 | 33.47 | 16.13 |
July | 0.131907E+12 | 744.00 | 49248.27 | 01-JUL-00:03 | 818014.85 | 13-JUL-17:55 | 43.71 | 33.94 | 16.13 |
August | 0.131907E+12 | 744.00 | 49248.27 | 01-AUG-00:03 | 843788.67 | 28-AUG-16:13 | 46.66 | 34.29 | 16.13 |
September | 0.126784E+12 | 720.00 | 49248.27 | 01-SEP-00:05 | 358449.19 | 04-SEP-10:20 | 32.18 | 28.92 | 16.13 |
October | 0.905713E+11 | 744.00 | 49248.27 | 01-OCT-00:03 | 525093.88 | 03-OCT-08:30 | 26.85 | 23.54 | 16.13 |
November | 0.539781E+11 | 720.00 | 49248.27 | 01-NOV-00:40 | 560314.75 | 09-NOV-17:00 | 23.07 | 20.07 | 16.13 |
December | 0.402084E+11 | 744.00 | 49248.27 | 01-DEC-10:00 | 657751.29 | 21-DEC-15:00 | 22.75 | 19.35 | 16.12 |
Annual Sum or Average | 0.105377E+13 | 8760.00 | 30.39 | 25.55 | 16.13 | ||||
Minimum of Months | 0.154356E+11 | 672.00 | 49248.27 | 164232.93 | 19.49 | 18.45 | 16.12 | ||
Maximum of Months | 0.131907E+12 | 744.00 | 49248.27 | 843788.67 | 46.66 | 34.29 | 16.13 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.562414E+09 | 236.26 | 2616.93 | 31-JAN-14:10 | 1329576.25 | 27-JAN-14:20 | 21.93 | 21.18 | 23.94 |
February | 0.116066E+09 | 92.00 | 1208.59 | 22-FEB-16:00 | 725252.44 | 22-FEB-16:00 | 21.23 | 21.03 | 14.19 |
March | 0.105385E+10 | 246.87 | 18510.35 | 16-MAR-16:00 | 1436084.09 | 17-MAR-13:10 | 21.82 | 21.09 | 25.80 |
April | 0.243371E+10 | 412.21 | 18510.35 | 10-APR-14:50 | 1348588.81 | 04-APR-11:25 | 22.75 | 21.08 | 42.15 |
May | 0.308636E+10 | 487.86 | 18510.35 | 04-MAY-16:10 | 1330663.76 | 05-MAY-09:30 | 23.24 | 21.29 | 44.68 |
June | 0.154922E+11 | 573.36 | 18510.35 | 01-JUN-08:20 | 1333061.39 | 15-JUN-08:40 | 23.79 | 21.40 | 55.21 |
July | 0.303752E+11 | 655.33 | 18510.35 | 01-JUL-14:30 | 1292316.67 | 03-JUL-07:40 | 24.66 | 22.43 | 56.25 |
August | 0.301158E+11 | 645.54 | 18510.35 | 01-AUG-00:23 | 1304820.10 | 22-AUG-07:30 | 24.62 | 22.39 | 56.38 |
September | 0.255290E+11 | 548.96 | 18510.35 | 01-SEP-03:02 | 1372241.22 | 28-SEP-09:30 | 24.20 | 22.16 | 49.21 |
October | 0.659019E+10 | 379.72 | 18510.35 | 01-OCT-09:55 | 1366650.89 | 10-OCT-09:00 | 22.63 | 21.33 | 36.14 |
November | 0.173001E+10 | 237.81 | 18510.35 | 01-NOV-10:20 | 1339875.72 | 01-NOV-12:20 | 21.88 | 21.10 | 25.72 |
December | 0.209182E+09 | 145.77 | 2240.93 | 22-DEC-15:10 | 1307522.15 | 22-DEC-16:20 | 21.40 | 21.01 | 16.47 |
Annual Sum or Average | 0.117294E+12 | 4661.68 | 22.85 | 21.46 | 37.30 | ||||
Minimum of Months | 0.116066E+09 | 92.00 | 1208.59 | 725252.44 | 21.23 | 21.01 | 14.19 | ||
Maximum of Months | 0.303752E+11 | 655.33 | 18510.35 | 1436084.09 | 24.66 | 22.43 | 56.38 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 4026056.11 | 0.83 | 2227.27 | 31-JAN-14:50 | 1194928.89 | 31-JAN-15:40 | 21.93 | 21.93 | 0.07 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.23 | 21.23 | 0.00 |
March | 11535763.35 | 1.50 | 2826.35 | 20-MAR-14:40 | 1197118.89 | 20-MAR-14:40 | 21.82 | 21.81 | 0.13 |
April | 0.798100E+09 | 53.47 | 18510.35 | 10-APR-14:50 | 1259098.28 | 24-APR-15:20 | 22.75 | 22.43 | 4.70 |
May | 0.100172E+10 | 82.02 | 18510.35 | 09-MAY-13:40 | 1309359.46 | 18-MAY-14:10 | 23.24 | 22.77 | 6.98 |
June | 0.937279E+10 | 193.17 | 18510.35 | 01-JUN-08:50 | 1238338.38 | 05-JUN-13:40 | 23.79 | 22.77 | 16.89 |
July | 0.141357E+11 | 222.12 | 18510.35 | 03-JUL-11:50 | 1210156.62 | 14-JUL-05:03 | 24.66 | 23.61 | 17.73 |
August | 0.152899E+11 | 235.03 | 18510.35 | 01-AUG-05:03 | 1186656.42 | 24-AUG-12:00 | 24.62 | 23.55 | 19.10 |
September | 0.108505E+11 | 167.27 | 18510.35 | 01-SEP-05:04 | 1160654.94 | 18-SEP-09:10 | 24.20 | 23.38 | 13.89 |
October | 0.311341E+10 | 62.72 | 18510.35 | 02-OCT-07:30 | 1221034.50 | 17-OCT-11:50 | 22.63 | 22.32 | 5.27 |
November | 0.123997E+09 | 3.92 | 18510.35 | 01-NOV-12:50 | 1175704.30 | 21-NOV-15:50 | 21.88 | 21.86 | 0.34 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 21.40 | 21.40 | 0.00 |
Annual Sum or Average | 0.547016E+11 | 1022.05 | 22.85 | 22.43 | 7.13 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.23 | 21.23 | 0.00 | ||
Maximum of Months | 0.152899E+11 | 235.03 | 18510.35 | 1309359.46 | 24.66 | 23.61 | 19.10 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 20.32 | 20.32 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 19.49 | 19.49 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 23.25 | 23.25 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 35.53 | 35.53 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 30.24 | 30.24 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 39.83 | 39.83 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 43.71 | 43.71 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 46.66 | 46.66 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 32.18 | 32.18 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 26.85 | 26.85 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 23.07 | 23.07 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 22.75 | 22.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 30.39 | 30.39 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.49 | 19.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.66 | 46.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.421981E+11 | 0.00 | 286.70 | 0.421844E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102532.56 | 31-JAN-16:40 | 102532.56 | 31-JAN-16:40 | 0.00 | 0.00 | 0.00 |
February | 0.108052E+11 | 0.00 | 170.67 | 0.108052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66466.59 | 21-FEB-15:00 | 66466.59 | 21-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.456138E+11 | 0.00 | 325.93 | 0.456138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 113513.28 | 20-MAR-14:50 | 113513.28 | 20-MAR-14:50 | 0.00 | 0.00 | 0.00 |
April | 0.120107E+12 | 0.00 | 535.45 | 0.120107E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 142345.29 | 25-APR-15:10 | 142345.29 | 25-APR-15:10 | 0.00 | 0.00 | 0.00 |
May | 0.149453E+12 | 0.00 | 516.13 | 0.149453E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 157033.04 | 31-MAY-16:00 | 157033.04 | 31-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.218329E+12 | 0.00 | 615.46 | 0.218314E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 182262.79 | 16-JUN-16:00 | 182262.79 | 16-JUN-16:00 | 0.00 | 0.00 | 0.00 |
July | 0.237553E+12 | 0.00 | 637.93 | 0.221861E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 307012.04 | 14-JUL-05:02 | 185846.67 | 17-JUL-03:02 | 0.00 | 0.00 | 0.00 |
August | 0.253621E+12 | 0.00 | 651.87 | 0.236781E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 298543.56 | 01-AUG-03:13 | 187207.91 | 14-AUG-14:20 | 0.00 | 0.00 | 0.00 |
September | 0.189311E+12 | 0.00 | 548.55 | 0.173627E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 271713.94 | 01-SEP-05:02 | 177898.33 | 10-SEP-16:42 | 0.00 | 0.00 | 0.00 |
October | 0.102048E+12 | 0.00 | 433.62 | 0.998396E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 206023.94 | 03-OCT-07:40 | 172001.90 | 09-OCT-13:41 | 0.00 | 0.00 | 0.00 |
November | 0.496432E+11 | 0.00 | 307.75 | 0.466756E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 156948.94 | 13-NOV-05:11 | 120146.17 | 01-NOV-15:20 | 0.00 | 0.00 | 0.00 |
December | 0.246260E+11 | 0.00 | 216.63 | 0.246260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100915.78 | 22-DEC-16:20 | 100915.78 | 22-DEC-16:20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144331E+13 | 0.00 | 5246.69 | 0.138989E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.108052E+11 | 0.00 | 170.67 | 0.108052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66466.59 | 66466.59 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.253621E+12 | 0.00 | 651.87 | 0.236781E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 307012.04 | 187207.91 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.345655E+12 | 0.00 | 291.04 | 0.345502E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 879647.63 | 31-JAN-16:30 | 879647.63 | 31-JAN-16:30 | 0.00 | 0.00 | 0.00 |
February | 0.811817E+11 | 0.00 | 176.35 | 0.811817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 494500.41 | 22-FEB-16:00 | 494500.41 | 22-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.333575E+12 | 0.00 | 319.34 | 0.333575E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 948611.76 | 16-MAR-15:50 | 948611.76 | 16-MAR-15:50 | 0.00 | 0.00 | 0.00 |
April | 0.889614E+12 | 0.00 | 432.15 | 0.889614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1247814.33 | 14-APR-15:20 | 1247814.33 | 14-APR-15:20 | 0.00 | 0.00 | 0.00 |
May | 0.115928E+13 | 0.00 | 481.63 | 0.115928E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1254678.27 | 18-MAY-15:10 | 1254678.27 | 18-MAY-15:10 | 0.00 | 0.00 | 0.00 |
June | 0.153406E+13 | 0.00 | 538.10 | 0.153405E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1533244.80 | 30-JUN-05:02 | 1533244.80 | 30-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.147548E+13 | 0.00 | 534.48 | 0.140078E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2921752.12 | 14-JUL-05:02 | 1550065.53 | 07-JUL-05:03 | 0.00 | 0.00 | 0.00 |
August | 0.150023E+13 | 0.00 | 533.26 | 0.143199E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1921781.72 | 04-AUG-05:02 | 1525237.83 | 14-AUG-05:01 | 0.00 | 0.00 | 0.00 |
September | 0.124531E+13 | 0.00 | 460.78 | 0.117090E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2584285.88 | 01-SEP-05:02 | 1531170.96 | 19-SEP-05:03 | 0.00 | 0.00 | 0.00 |
October | 0.724364E+12 | 0.00 | 389.41 | 0.712430E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1915480.68 | 03-OCT-04:12 | 1314918.53 | 02-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.345475E+12 | 0.00 | 296.70 | 0.330976E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1104941.80 | 13-NOV-05:11 | 965300.57 | 01-NOV-15:30 | 0.00 | 0.00 | 0.00 |
December | 0.172492E+12 | 0.00 | 209.62 | 0.172492E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 768627.88 | 22-DEC-16:30 | 768627.88 | 22-DEC-16:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.980671E+13 | 0.00 | 4662.86 | 0.956276E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.811817E+11 | 0.00 | 176.35 | 0.811817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 494500.41 | 494500.41 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.153406E+13 | 0.00 | 538.10 | 0.153405E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2921752.12 | 1550065.53 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.310552E+11 | 0.00 | 277.07 | 0.310490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92412.73 | 31-JAN-16:40 | 92412.73 | 31-JAN-16:40 | 0.00 | 0.00 | 0.00 |
February | 0.660719E+10 | 0.00 | 154.68 | 0.660719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48089.68 | 22-FEB-16:00 | 48089.68 | 22-FEB-16:00 | 0.00 | 0.00 | 0.00 |
March | 0.322661E+11 | 0.00 | 301.44 | 0.322661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 108022.93 | 16-MAR-15:30 | 108022.93 | 16-MAR-15:30 | 0.00 | 0.00 | 0.00 |
April | 0.970296E+11 | 0.00 | 428.10 | 0.970296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 148717.55 | 14-APR-15:20 | 148717.55 | 14-APR-15:20 | 0.00 | 0.00 | 0.00 |
May | 0.127870E+12 | 0.00 | 481.37 | 0.127870E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 149469.91 | 18-MAY-15:20 | 149469.91 | 18-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.174753E+12 | 0.00 | 546.44 | 0.174753E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 174906.97 | 28-JUN-15:00 | 174906.97 | 28-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.166823E+12 | 0.00 | 543.62 | 0.159189E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 317817.39 | 18-JUL-05:02 | 174005.16 | 17-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.167034E+12 | 0.00 | 537.77 | 0.159895E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 278457.49 | 01-AUG-05:03 | 171873.42 | 28-AUG-05:01 | 0.00 | 0.00 | 0.00 |
September | 0.134939E+12 | 0.00 | 466.10 | 0.127547E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 282783.43 | 01-SEP-05:02 | 158737.49 | 08-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.738619E+11 | 0.00 | 381.06 | 0.727544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 208204.51 | 03-OCT-04:12 | 156190.91 | 02-OCT-03:02 | 0.00 | 0.00 | 0.00 |
November | 0.310150E+11 | 0.00 | 278.88 | 0.300183E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109428.44 | 01-NOV-15:30 | 109428.44 | 01-NOV-15:30 | 0.00 | 0.00 | 0.00 |
December | 0.141798E+11 | 0.00 | 187.22 | 0.141798E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79022.65 | 22-DEC-15:50 | 79022.65 | 22-DEC-15:50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.105743E+13 | 0.00 | 4583.75 | 0.103316E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.660719E+10 | 0.00 | 154.68 | 0.660719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48089.68 | 48089.68 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.174753E+12 | 0.00 | 546.44 | 0.174753E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 317817.39 | 174906.97 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.315537E+11 | 0.00 | 251.39 | 0.315497E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75323.80 | 17-JAN-13:10 | 75323.80 | 17-JAN-13:10 | 0.00 | 0.00 | 0.00 |
February | 0.849904E+10 | 0.00 | 154.42 | 0.846222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61999.31 | 10-FEB-11:21 | 61999.31 | 10-FEB-11:21 | 0.00 | 0.00 | 0.00 |
March | 0.316547E+11 | 0.00 | 304.46 | 0.316356E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 71459.58 | 20-MAR-13:10 | 71459.58 | 20-MAR-13:10 | 0.00 | 0.00 | 0.00 |
April | 0.542250E+11 | 0.00 | 263.39 | 0.542250E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85173.18 | 13-APR-10:00 | 85173.18 | 13-APR-10:00 | 0.00 | 0.00 | 0.00 |
May | 0.342397E+11 | 0.00 | 124.04 | 0.342397E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 113791.95 | 12-MAY-11:00 | 113791.95 | 12-MAY-11:00 | 0.00 | 0.00 | 0.00 |
June | 0.556507E+10 | 0.00 | 14.83 | 0.556231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 122788.70 | 21-JUN-09:35 | 122788.70 | 21-JUN-09:35 | 0.00 | 0.00 | 0.00 |
July | 0.374088E+10 | 0.00 | 9.83 | 0.374088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 119847.47 | 01-JUL-10:50 | 119847.47 | 01-JUL-10:50 | 0.00 | 0.00 | 0.00 |
August | 0.609651E+10 | 0.00 | 15.00 | 0.609651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 127090.91 | 24-AUG-15:00 | 127090.91 | 24-AUG-15:00 | 0.00 | 0.00 | 0.00 |
September | 0.261624E+11 | 0.00 | 74.17 | 0.233689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 138251.97 | 14-SEP-09:00 | 110020.42 | 14-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.455367E+11 | 0.00 | 235.79 | 0.449098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 138451.54 | 04-OCT-08:30 | 114277.10 | 10-OCT-14:00 | 0.00 | 0.00 | 0.00 |
November | 0.360178E+11 | 0.00 | 236.25 | 0.326174E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 124692.52 | 13-NOV-14:10 | 91860.37 | 02-NOV-13:40 | 0.00 | 0.00 | 0.00 |
December | 0.172057E+11 | 0.00 | 180.23 | 0.172035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81726.60 | 26-DEC-13:10 | 81726.60 | 26-DEC-13:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.300497E+12 | 0.00 | 1863.81 | 0.293611E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.374088E+10 | 0.00 | 9.83 | 0.374088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61999.31 | 61999.31 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.542250E+11 | 0.00 | 304.46 | 0.542250E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 138451.54 | 127090.91 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.273486E+11 | 0.125148E+11 | 718.55 | 0.273261E+11 | 22539458.90 | 0.00 | 0.42 | 27-JAN-16:00 | 0.00 | 21-JAN-08:15 | 141647.62 | 27-JAN-16:00 | 141647.62 | 27-JAN-16:00 | 144.43 | 09-JAN-12:00 | 57476.35 | 27-JAN-16:00 | 0.00 |
February | 0.771774E+10 | 0.556914E+10 | 479.72 | 0.737339E+10 | 0.344354E+09 | 0.00 | 0.22 | 18-FEB-14:00 | 0.01 | 21-FEB-04:30 | 84546.30 | 18-FEB-14:00 | 73811.84 | 18-FEB-15:00 | 11869.00 | 18-FEB-14:00 | 26643.21 | 18-FEB-14:00 | 0.00 |
March | 0.167126E+12 | 0.579568E+11 | 713.84 | 0.164888E+12 | 0.223883E+10 | 0.00 | 0.81 | 15-MAR-12:40 | 0.00 | 04-MAR-22:50 | 323774.62 | 17-MAR-15:20 | 323774.62 | 17-MAR-15:20 | 24232.18 | 17-MAR-10:00 | 116450.56 | 16-MAR-12:40 | 0.00 |
April | 0.699541E+12 | 0.252642E+12 | 720.00 | 0.698256E+12 | 0.128497E+10 | 0.00 | 1.00 | 01-APR-09:55 | 0.02 | 30-APR-24:00 | 440544.98 | 02-APR-14:07 | 440544.98 | 02-APR-14:07 | 28551.95 | 16-APR-23:20 | 171935.10 | 14-APR-16:10 | 0.00 |
May | 0.224488E+12 | 0.896043E+11 | 743.50 | 0.224488E+12 | 246593.98 | 0.00 | 0.60 | 31-MAY-23:10 | 0.01 | 26-MAY-03:10 | 220075.48 | 31-MAY-23:10 | 220075.48 | 31-MAY-23:10 | 52.50 | 26-MAY-03:30 | 84248.96 | 31-MAY-23:10 | 0.00 |
June | 0.529188E+12 | 0.214836E+12 | 720.00 | 0.529179E+12 | 8212742.29 | 0.00 | 0.74 | 30-JUN-23:10 | 0.02 | 11-JUN-05:00 | 313638.64 | 30-JUN-23:57 | 313638.64 | 30-JUN-23:57 | 2838.31 | 04-JUN-05:00 | 120898.78 | 16-JUN-16:00 | 0.00 |
July | 0.889486E+12 | 0.321930E+12 | 744.00 | 0.805019E+12 | 0.844673E+11 | 0.00 | 1.00 | 08-JUL-22:50 | 0.17 | 01-JUL-06:00 | 544272.86 | 14-JUL-01:00 | 406516.53 | 31-JUL-24:00 | 363400.13 | 14-JUL-01:00 | 153236.84 | 05-JUL-16:00 | 0.00 |
August | 0.113928E+13 | 0.400017E+12 | 744.00 | 0.101197E+13 | 0.127312E+12 | 0.00 | 1.00 | 01-AUG-02:11 | 0.32 | 31-AUG-24:00 | 526019.83 | 09-AUG-18:20 | 431299.15 | 20-AUG-09:13 | 303499.05 | 28-AUG-17:00 | 190525.19 | 25-AUG-16:10 | 0.00 |
September | 0.272038E+12 | 0.100986E+12 | 668.87 | 0.246803E+12 | 0.252352E+11 | 0.00 | 0.51 | 04-SEP-10:20 | 0.01 | 27-SEP-04:12 | 245685.29 | 04-SEP-10:17 | 175656.31 | 30-SEP-23:10 | 116337.22 | 04-SEP-09:58 | 72313.44 | 04-SEP-10:20 | 0.00 |
October | 0.242803E+12 | 0.882559E+11 | 712.29 | 0.232430E+12 | 0.103736E+11 | 0.00 | 0.72 | 03-OCT-08:30 | 0.00 | 07-OCT-21:33 | 349355.64 | 03-OCT-08:30 | 234982.45 | 03-OCT-16:00 | 122459.92 | 02-OCT-22:55 | 104755.44 | 03-OCT-08:30 | 0.00 |
November | 0.162237E+12 | 0.556574E+11 | 664.62 | 0.147413E+12 | 0.148244E+11 | 0.00 | 0.86 | 09-NOV-13:00 | 0.00 | 16-NOV-01:10 | 326518.55 | 20-NOV-15:20 | 326518.55 | 20-NOV-15:20 | 141507.96 | 12-NOV-14:43 | 123729.99 | 09-NOV-17:00 | 0.00 |
December | 0.165856E+12 | 0.577289E+11 | 734.69 | 0.165733E+12 | 0.123317E+09 | 0.00 | 1.00 | 22-DEC-15:00 | 0.01 | 13-DEC-05:10 | 387605.39 | 21-DEC-15:00 | 387605.39 | 21-DEC-15:00 | 11399.77 | 12-DEC-16:00 | 142664.66 | 22-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.452711E+13 | 0.165770E+13 | 8364.07 | 0.426088E+13 | 0.266235E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.771774E+10 | 0.556914E+10 | 479.72 | 0.737339E+10 | 246593.98 | 0.00 | 0.22 | 0.00 | 84546.30 | 73811.84 | 52.50 | 26643.21 | 0.00 | ||||||
Maximum of Months | 0.113928E+13 | 0.400017E+12 | 744.00 | 0.101197E+13 | 0.127312E+12 | 0.00 | 1.00 | 0.32 | 544272.86 | 440544.98 | 363400.13 | 190525.19 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.550598E+10 | 0.150288E+10 | 744.00 | 0.550283E+10 | 3149844.15 | 0.00 | 0.40 | 29-JAN-17:12 | 0.18 | 21-JAN-08:00 | 2812.64 | 29-JAN-17:17 | 2812.64 | 29-JAN-17:17 | 101.28 | 09-JAN-11:20 | 1032.15 | 31-JAN-17:00 | 0.00 |
February | 0.941202E+10 | 0.225181E+10 | 672.00 | 0.936924E+10 | 42777099.59 | 0.00 | 0.54 | 28-FEB-17:00 | 0.40 | 08-FEB-07:10 | 4561.00 | 22-FEB-17:00 | 4508.97 | 27-FEB-17:40 | 171.59 | 16-FEB-10:30 | 1134.32 | 22-FEB-17:00 | 0.00 |
March | 0.158129E+11 | 0.390753E+10 | 744.00 | 0.158010E+11 | 11906327.85 | 0.00 | 0.93 | 31-MAR-24:00 | 0.62 | 07-MAR-08:00 | 7739.06 | 31-MAR-24:00 | 7739.06 | 31-MAR-24:00 | 212.06 | 06-MAR-11:10 | 2197.35 | 16-MAR-16:00 | 0.00 |
April | 0.201894E+11 | 0.612734E+10 | 720.00 | 0.201894E+11 | 0.00 | 0.00 | 1.00 | 01-APR-09:30 | 0.37 | 30-APR-24:00 | 8417.05 | 26-APR-18:20 | 8417.05 | 26-APR-18:20 | 0.00 | 04-APR-12:00 | 3109.89 | 14-APR-16:10 | 0.00 |
May | 0.649915E+10 | 0.234327E+10 | 744.00 | 0.649915E+10 | -0.0 | 0.00 | 0.58 | 31-MAY-23:13 | 0.26 | 13-MAY-06:30 | 4154.82 | 31-MAY-23:50 | 4154.82 | 31-MAY-23:50 | 0.00 | 12-MAY-07:05 | 1483.06 | 31-MAY-23:10 | 0.00 |
June | 0.115151E+11 | 0.447407E+10 | 720.00 | 0.115137E+11 | 1489690.65 | 0.00 | 0.78 | 30-JUN-23:15 | 0.50 | 21-JUN-06:10 | 6133.07 | 30-JUN-23:57 | 6133.07 | 30-JUN-23:57 | 104.71 | 30-JUN-10:00 | 2530.65 | 16-JUN-16:00 | 0.00 |
July | 0.170870E+11 | 0.610114E+10 | 744.00 | 0.169302E+11 | 0.156877E+09 | 0.00 | 1.00 | 02-JUL-17:21 | 0.68 | 01-JUL-06:10 | 8083.18 | 31-JUL-23:55 | 8064.52 | 31-JUL-23:55 | 413.14 | 13-JUL-18:00 | 3207.91 | 02-JUL-18:00 | 0.00 |
August | 0.216710E+11 | 0.741929E+10 | 744.00 | 0.215108E+11 | 0.160259E+09 | 0.00 | 1.00 | 01-AUG-09:00 | 0.35 | 31-AUG-24:00 | 8822.70 | 28-AUG-16:17 | 8497.46 | 06-AUG-20:15 | 563.78 | 28-AUG-16:25 | 3442.03 | 25-AUG-16:10 | 0.00 |
September | 0.651696E+10 | 0.222462E+10 | 720.00 | 0.638175E+10 | 0.135212E+09 | 0.00 | 0.55 | 30-SEP-23:43 | 0.26 | 22-SEP-06:10 | 4210.88 | 30-SEP-23:47 | 4210.88 | 30-SEP-23:47 | 301.72 | 11-SEP-15:10 | 1340.79 | 30-SEP-23:43 | 0.00 |
October | 0.112585E+11 | 0.326629E+10 | 744.00 | 0.112288E+11 | 29713724.08 | 0.00 | 0.72 | 15-OCT-17:22 | 0.42 | 25-OCT-06:45 | 5913.14 | 31-OCT-24:00 | 5913.14 | 31-OCT-24:00 | 310.66 | 03-OCT-09:40 | 1990.09 | 01-OCT-13:55 | 0.00 |
November | 0.154806E+11 | 0.382840E+10 | 720.00 | 0.154334E+11 | 47212071.04 | 0.00 | 0.89 | 09-NOV-17:00 | 0.62 | 18-NOV-07:35 | 6950.84 | 14-NOV-17:00 | 6820.21 | 20-NOV-17:00 | 385.62 | 13-NOV-16:40 | 2327.05 | 09-NOV-16:50 | 0.00 |
December | 0.206826E+11 | 0.499476E+10 | 744.00 | 0.206822E+11 | 459210.80 | 0.00 | 1.00 | 02-DEC-14:50 | 0.83 | 14-DEC-07:05 | 8469.32 | 28-DEC-17:00 | 8469.32 | 28-DEC-17:00 | 70.70 | 13-DEC-11:20 | 2596.01 | 21-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.161631E+12 | 0.484414E+11 | 8760.00 | 0.161042E+12 | 0.589056E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.550598E+10 | 0.150288E+10 | 672.00 | 0.550283E+10 | -0.0 | 0.00 | 0.40 | 0.18 | 2812.64 | 2812.64 | 0.00 | 1032.15 | 0.00 | ||||||
Maximum of Months | 0.216710E+11 | 0.741929E+10 | 744.00 | 0.215108E+11 | 0.160259E+09 | 0.00 | 1.00 | 0.83 | 8822.70 | 8497.46 | 563.78 | 3442.03 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.418504E+11 | 0.117001E+11 | 743.83 | 0.418204E+11 | 30082362.83 | 0.00 | 0.39 | 31-JAN-17:00 | 0.00 | 01-JAN-01:05 | 26096.24 | 24-JAN-17:00 | 26096.24 | 24-JAN-17:00 | 930.22 | 09-JAN-11:30 | 9623.82 | 31-JAN-17:00 | 0.00 |
February | 0.795654E+11 | 0.192586E+11 | 672.00 | 0.791449E+11 | 0.420547E+09 | 0.00 | 0.53 | 22-FEB-17:00 | 0.32 | 13-FEB-07:10 | 42628.75 | 22-FEB-17:00 | 42103.70 | 22-FEB-17:00 | 1691.39 | 16-FEB-10:30 | 10626.79 | 22-FEB-17:00 | 0.00 |
March | 0.143500E+12 | 0.357420E+11 | 744.00 | 0.143380E+12 | 0.119531E+09 | 0.00 | 0.91 | 31-MAR-23:50 | 0.56 | 07-MAR-08:00 | 72280.49 | 31-MAR-23:50 | 72280.49 | 31-MAR-23:50 | 2104.95 | 06-MAR-11:20 | 20837.00 | 16-MAR-16:00 | 0.00 |
April | 0.191400E+12 | 0.582649E+11 | 720.00 | 0.191400E+12 | -0.0 | 0.00 | 1.00 | 01-APR-10:20 | 0.33 | 30-APR-24:00 | 80249.20 | 26-APR-18:20 | 80249.20 | 26-APR-18:20 | 0.00 | 06-APR-02:17 | 29687.39 | 14-APR-16:10 | 0.00 |
May | 0.592546E+11 | 0.215160E+11 | 744.00 | 0.592546E+11 | 0.00 | 0.00 | 0.58 | 31-MAY-23:10 | 0.23 | 13-MAY-06:30 | 39478.15 | 31-MAY-23:53 | 39478.15 | 31-MAY-23:53 | 0.00 | 14-MAY-10:17 | 14104.00 | 31-MAY-23:10 | 0.00 |
June | 0.107351E+12 | 0.418455E+11 | 720.00 | 0.107334E+12 | 16700128.35 | 0.00 | 0.77 | 30-JUN-23:10 | 0.48 | 21-JUN-06:10 | 57742.42 | 30-JUN-23:57 | 57742.42 | 30-JUN-23:57 | 1054.75 | 30-JUN-10:00 | 23800.59 | 16-JUN-16:00 | 0.00 |
July | 0.159495E+12 | 0.571239E+11 | 744.00 | 0.157938E+12 | 0.155728E+10 | 0.00 | 1.00 | 02-JUL-18:21 | 0.67 | 01-JUL-06:10 | 75749.32 | 31-JUL-23:55 | 75569.02 | 31-JUL-23:55 | 4097.85 | 13-JUL-18:00 | 30483.80 | 02-JUL-18:01 | 0.00 |
August | 0.203948E+12 | 0.701291E+11 | 744.00 | 0.202340E+12 | 0.160857E+10 | 0.00 | 1.00 | 01-AUG-09:30 | 0.31 | 31-AUG-24:00 | 83880.29 | 28-AUG-16:13 | 79756.83 | 06-AUG-18:52 | 5568.43 | 28-AUG-16:13 | 32853.89 | 25-AUG-16:10 | 0.00 |
September | 0.588064E+11 | 0.202002E+11 | 720.00 | 0.574843E+11 | 0.132214E+10 | 0.00 | 0.54 | 30-SEP-24:00 | 0.22 | 22-SEP-06:10 | 39489.78 | 30-SEP-24:00 | 39489.78 | 30-SEP-24:00 | 2961.22 | 11-SEP-15:10 | 12608.33 | 30-SEP-23:30 | 0.00 |
October | 0.101739E+12 | 0.297812E+11 | 744.00 | 0.101444E+12 | 0.294567E+09 | 0.00 | 0.70 | 15-OCT-17:12 | 0.38 | 25-OCT-06:45 | 54518.08 | 31-OCT-24:00 | 54518.08 | 31-OCT-24:00 | 3085.30 | 03-OCT-09:40 | 18405.63 | 06-OCT-16:00 | 0.00 |
November | 0.139087E+12 | 0.346931E+11 | 720.00 | 0.138618E+12 | 0.469634E+09 | 0.00 | 0.88 | 09-NOV-17:00 | 0.56 | 18-NOV-07:45 | 65379.70 | 14-NOV-17:00 | 64208.63 | 09-NOV-17:00 | 3813.52 | 13-NOV-16:40 | 21948.30 | 09-NOV-16:50 | 0.00 |
December | 0.184243E+12 | 0.449709E+11 | 744.00 | 0.184237E+12 | 5316338.10 | 0.00 | 1.00 | 21-DEC-15:00 | 0.76 | 14-DEC-07:05 | 79890.08 | 26-DEC-17:10 | 79890.08 | 26-DEC-17:10 | 768.66 | 13-DEC-11:20 | 24775.11 | 21-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.147024E+13 | 0.445226E+12 | 8759.83 | 0.146440E+13 | 0.584436E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.418504E+11 | 0.117001E+11 | 672.00 | 0.418204E+11 | -0.0 | 0.00 | 0.39 | 0.00 | 26096.24 | 26096.24 | 0.00 | 9623.82 | 0.00 | ||||||
Maximum of Months | 0.203948E+12 | 0.701291E+11 | 744.00 | 0.202340E+12 | 0.160857E+10 | 0.00 | 1.00 | 0.76 | 83880.29 | 80249.20 | 5568.43 | 32853.89 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.328120E+10 | 0.942321E+09 | 713.56 | 0.327842E+10 | 2784312.43 | 0.00 | 0.38 | 31-JAN-17:00 | 0.00 | 01-JAN-00:10 | 2641.05 | 24-JAN-17:00 | 2641.05 | 24-JAN-17:00 | 85.87 | 09-JAN-11:50 | 978.04 | 31-JAN-17:00 | 0.00 |
February | 0.699028E+10 | 0.171320E+10 | 672.00 | 0.694871E+10 | 41572073.73 | 0.00 | 0.52 | 22-FEB-17:00 | 0.21 | 13-FEB-07:10 | 4300.76 | 22-FEB-17:00 | 4247.74 | 22-FEB-17:00 | 169.50 | 16-FEB-10:40 | 1073.63 | 22-FEB-17:00 | 0.00 |
March | 0.137108E+11 | 0.344823E+10 | 744.00 | 0.136990E+11 | 11827323.53 | 0.00 | 0.88 | 31-MAR-23:30 | 0.46 | 27-MAR-06:05 | 7056.15 | 31-MAR-23:20 | 7056.15 | 31-MAR-23:20 | 209.30 | 06-MAR-11:20 | 2112.17 | 16-MAR-16:00 | 0.00 |
April | 0.191647E+11 | 0.587398E+10 | 720.00 | 0.191647E+11 | -0.0 | 0.00 | 1.00 | 01-APR-11:50 | 0.32 | 30-APR-24:00 | 8059.61 | 26-APR-18:10 | 8059.61 | 26-APR-18:10 | 0.00 | 29-APR-00:10 | 3037.03 | 14-APR-16:10 | 0.00 |
May | 0.596032E+10 | 0.217823E+10 | 744.00 | 0.596032E+10 | 0.00 | 0.00 | 0.57 | 31-MAY-23:53 | 0.20 | 13-MAY-06:50 | 3961.35 | 31-MAY-23:53 | 3961.35 | 31-MAY-23:53 | 0.00 | 11-MAY-19:00 | 1412.56 | 31-MAY-23:10 | 0.00 |
June | 0.109063E+11 | 0.426115E+10 | 720.00 | 0.109047E+11 | 1566070.07 | 0.00 | 0.76 | 30-JUN-23:10 | 0.46 | 21-JUN-06:10 | 5828.29 | 30-JUN-23:57 | 5828.29 | 30-JUN-23:57 | 104.57 | 30-JUN-10:00 | 2451.72 | 16-JUN-16:00 | 0.00 |
July | 0.161383E+11 | 0.579314E+10 | 744.00 | 0.159824E+11 | 0.155868E+09 | 0.00 | 1.00 | 02-JUL-17:31 | 0.65 | 29-JUL-06:05 | 7645.68 | 31-JUL-23:55 | 7627.48 | 31-JUL-23:55 | 409.96 | 13-JUL-18:00 | 3132.68 | 02-JUL-18:00 | 0.00 |
August | 0.205764E+11 | 0.710285E+10 | 744.00 | 0.204144E+11 | 0.161962E+09 | 0.00 | 1.00 | 01-AUG-11:30 | 0.30 | 31-AUG-24:00 | 8504.78 | 28-AUG-15:52 | 8153.56 | 06-AUG-18:43 | 566.64 | 28-AUG-15:52 | 3361.17 | 25-AUG-16:10 | 0.00 |
September | 0.596635E+10 | 0.205624E+10 | 720.00 | 0.583370E+10 | 0.132648E+09 | 0.00 | 0.54 | 30-SEP-24:00 | 0.20 | 22-SEP-06:55 | 4006.28 | 30-SEP-24:00 | 4006.28 | 30-SEP-24:00 | 298.20 | 11-SEP-15:10 | 1280.88 | 30-SEP-23:30 | 0.00 |
October | 0.981020E+10 | 0.290363E+10 | 744.00 | 0.978082E+10 | 29380259.86 | 0.00 | 0.70 | 15-OCT-17:12 | 0.31 | 26-OCT-06:10 | 5262.32 | 31-OCT-23:50 | 5262.32 | 31-OCT-23:50 | 309.38 | 03-OCT-09:40 | 1885.88 | 01-OCT-13:55 | 0.00 |
November | 0.130859E+11 | 0.330059E+10 | 720.00 | 0.130392E+11 | 46757641.77 | 0.00 | 0.87 | 09-NOV-17:00 | 0.44 | 24-NOV-07:05 | 6562.62 | 14-NOV-17:00 | 6477.81 | 09-NOV-17:00 | 381.97 | 13-NOV-16:40 | 2219.14 | 09-NOV-16:50 | 0.00 |
December | 0.171206E+11 | 0.423509E+10 | 744.00 | 0.171201E+11 | 501934.91 | 0.00 | 1.00 | 22-DEC-16:00 | 0.64 | 18-DEC-05:11 | 8050.62 | 26-DEC-17:00 | 8050.62 | 26-DEC-17:00 | 71.96 | 13-DEC-11:20 | 2524.11 | 22-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.142711E+12 | 0.438087E+11 | 8729.56 | 0.142126E+12 | 0.584869E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.328120E+10 | 0.942321E+09 | 672.00 | 0.327842E+10 | -0.0 | 0.00 | 0.38 | 0.00 | 2641.05 | 2641.05 | 0.00 | 978.04 | 0.00 | ||||||
Maximum of Months | 0.205764E+11 | 0.710285E+10 | 744.00 | 0.204144E+11 | 0.161962E+09 | 0.00 | 1.00 | 0.65 | 8504.78 | 8153.56 | 566.64 | 3361.17 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.00 | 0.00 | 101.00 | 61.89 | 507.33 | 0.00 | 0.00 | 0.00 |
February | 115.09 | 0.00 | 115.09 | 38.43 | 514.29 | 0.00 | 0.00 | 0.00 |
March | 152.96 | 0.00 | 152.96 | 123.14 | 441.94 | 0.00 | 0.00 | 0.00 |
April | 186.35 | 1.93 | 184.42 | 299.13 | 232.64 | 0.00 | 0.00 | 0.00 |
May | 218.15 | 17.47 | 200.68 | 416.25 | 159.90 | 0.00 | 0.00 | 0.00 |
June | 253.50 | 46.06 | 207.44 | 657.99 | 72.49 | 0.00 | 0.00 | 0.00 |
July | 216.19 | 22.52 | 193.67 | 554.24 | 59.64 | 0.00 | 0.00 | 0.00 |
August | 174.50 | 4.34 | 170.17 | 456.32 | 78.78 | 0.00 | 0.00 | 0.00 |
September | 164.64 | 0.04 | 164.60 | 382.98 | 107.78 | 0.00 | 0.00 | 0.00 |
October | 127.38 | 0.00 | 127.38 | 173.78 | 319.93 | 0.00 | 0.00 | 0.00 |
November | 106.13 | 0.00 | 106.13 | 63.33 | 475.56 | 0.00 | 0.00 | 0.00 |
December | 94.35 | 0.00 | 94.35 | 28.64 | 634.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 159.35 | 7.71 | 151.63 | 272.39 | 299.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.35 | 0.00 | 94.35 | 28.64 | 59.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 253.50 | 46.06 | 207.44 | 657.99 | 634.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.00 | 0.00 | 101.00 | 61.89 | 507.33 | 0.00 | 0.00 | 0.00 |
February | 115.09 | 0.00 | 115.09 | 38.43 | 514.29 | 0.00 | 0.00 | 0.00 |
March | 152.96 | 0.00 | 152.96 | 123.14 | 441.94 | 0.00 | 0.00 | 0.00 |
April | 186.35 | 1.93 | 184.42 | 299.13 | 232.64 | 0.00 | 0.00 | 0.00 |
May | 218.15 | 17.47 | 200.68 | 416.25 | 159.90 | 0.00 | 0.00 | 0.00 |
June | 253.50 | 46.06 | 207.44 | 657.99 | 72.49 | 0.00 | 0.00 | 0.00 |
July | 216.19 | 22.52 | 193.67 | 554.24 | 59.64 | 0.00 | 0.00 | 0.00 |
August | 174.50 | 4.34 | 170.17 | 456.32 | 78.78 | 0.00 | 0.00 | 0.00 |
September | 164.64 | 0.04 | 164.60 | 382.98 | 107.78 | 0.00 | 0.00 | 0.00 |
October | 127.38 | 0.00 | 127.38 | 173.78 | 319.93 | 0.00 | 0.00 | 0.00 |
November | 106.13 | 0.00 | 106.13 | 63.33 | 475.56 | 0.00 | 0.00 | 0.00 |
December | 94.35 | 0.00 | 94.35 | 28.64 | 634.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 159.35 | 7.71 | 151.63 | 272.39 | 299.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.35 | 0.00 | 94.35 | 28.64 | 59.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 253.50 | 46.06 | 207.44 | 657.99 | 634.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.00 | 0.00 | 101.00 | 61.89 | 507.33 | 0.00 | 0.00 | 0.00 |
February | 115.09 | 0.00 | 115.09 | 38.43 | 514.29 | 0.00 | 0.00 | 0.00 |
March | 152.96 | 0.00 | 152.96 | 123.14 | 441.94 | 0.00 | 0.00 | 0.00 |
April | 186.35 | 1.93 | 184.42 | 299.13 | 232.64 | 0.00 | 0.00 | 0.00 |
May | 218.15 | 17.47 | 200.68 | 416.25 | 159.90 | 0.00 | 0.00 | 0.00 |
June | 253.50 | 46.06 | 207.44 | 657.99 | 72.49 | 0.00 | 0.00 | 0.00 |
July | 216.19 | 22.52 | 193.67 | 554.24 | 59.64 | 0.00 | 0.00 | 0.00 |
August | 174.50 | 4.34 | 170.17 | 456.32 | 78.78 | 0.00 | 0.00 | 0.00 |
September | 164.64 | 0.04 | 164.60 | 382.98 | 107.78 | 0.00 | 0.00 | 0.00 |
October | 127.38 | 0.00 | 127.38 | 173.78 | 319.93 | 0.00 | 0.00 | 0.00 |
November | 106.13 | 0.00 | 106.13 | 63.33 | 475.56 | 0.00 | 0.00 | 0.00 |
December | 94.35 | 0.00 | 94.35 | 28.64 | 634.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 159.35 | 7.71 | 151.63 | 272.39 | 299.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.35 | 0.00 | 94.35 | 28.64 | 59.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 253.50 | 46.06 | 207.44 | 657.99 | 634.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.00 | 0.00 | 101.00 | 61.89 | 507.33 | 0.00 | 0.00 | 0.00 |
February | 115.09 | 0.00 | 115.09 | 38.43 | 514.29 | 0.00 | 0.00 | 0.00 |
March | 152.96 | 0.00 | 152.96 | 123.14 | 441.94 | 0.00 | 0.00 | 0.00 |
April | 186.35 | 1.93 | 184.42 | 299.13 | 232.64 | 0.00 | 0.00 | 0.00 |
May | 218.15 | 17.47 | 200.68 | 416.25 | 159.90 | 0.00 | 0.00 | 0.00 |
June | 253.50 | 46.06 | 207.44 | 657.99 | 72.49 | 0.00 | 0.00 | 0.00 |
July | 216.19 | 22.52 | 193.67 | 554.24 | 59.64 | 0.00 | 0.00 | 0.00 |
August | 174.50 | 4.34 | 170.17 | 456.32 | 78.78 | 0.00 | 0.00 | 0.00 |
September | 164.64 | 0.04 | 164.60 | 382.98 | 107.78 | 0.00 | 0.00 | 0.00 |
October | 127.38 | 0.00 | 127.38 | 173.78 | 319.93 | 0.00 | 0.00 | 0.00 |
November | 106.13 | 0.00 | 106.13 | 63.33 | 475.56 | 0.00 | 0.00 | 0.00 |
December | 94.35 | 0.00 | 94.35 | 28.64 | 634.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 159.35 | 7.71 | 151.63 | 272.39 | 299.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.35 | 0.00 | 94.35 | 28.64 | 59.64 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 253.50 | 46.06 | 207.44 | 657.99 | 634.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 101.00 | 0.00 | 101.00 | 61.89 | 507.31 | 0.00 | 0.00 | 0.00 |
February | 115.09 | 0.00 | 115.09 | 38.43 | 514.27 | 0.00 | 0.00 | 0.00 |
March | 152.95 | 0.00 | 152.95 | 123.14 | 441.92 | 0.00 | 0.00 | 0.00 |
April | 186.35 | 1.93 | 184.41 | 299.12 | 232.63 | 0.00 | 0.00 | 0.00 |
May | 218.14 | 17.47 | 200.67 | 416.23 | 159.90 | 0.00 | 0.00 | 0.00 |
June | 253.49 | 46.06 | 207.43 | 657.96 | 72.49 | 0.00 | 0.00 | 0.00 |
July | 216.18 | 22.52 | 193.66 | 554.22 | 59.63 | 0.00 | 0.00 | 0.00 |
August | 174.50 | 4.33 | 170.16 | 456.30 | 78.78 | 0.00 | 0.00 | 0.00 |
September | 164.63 | 0.04 | 164.59 | 382.97 | 107.78 | 0.00 | 0.00 | 0.00 |
October | 127.37 | 0.00 | 127.37 | 173.78 | 319.91 | 0.00 | 0.00 | 0.00 |
November | 106.13 | 0.00 | 106.13 | 63.32 | 475.54 | 0.00 | 0.00 | 0.00 |
December | 94.34 | 0.00 | 94.34 | 28.64 | 634.53 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 159.34 | 7.71 | 151.63 | 272.38 | 299.49 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 94.34 | 0.00 | 94.34 | 28.64 | 59.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 253.49 | 46.06 | 207.43 | 657.96 | 634.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 362.54 | 227.43 | 135.11 | 438.94 | 509.73 | 0.00 | 0.00 | 0.00 |
February | 357.36 | 204.42 | 152.93 | 381.40 | 517.07 | 0.00 | 0.00 | 0.00 |
March | 447.22 | 230.05 | 217.16 | 560.64 | 440.64 | 0.00 | 0.00 | 0.00 |
April | 638.38 | 380.48 | 257.90 | 1051.78 | 231.53 | 0.00 | 0.00 | 0.00 |
May | 661.59 | 392.18 | 269.40 | 1166.74 | 176.73 | 0.00 | 0.00 | 0.00 |
June | 689.59 | 428.50 | 261.09 | 1409.58 | 75.40 | 0.00 | 0.00 | 0.00 |
July | 582.40 | 328.39 | 254.01 | 1198.22 | 60.19 | 0.00 | 0.00 | 0.00 |
August | 552.75 | 315.45 | 237.30 | 1129.06 | 78.91 | 0.00 | 0.00 | 0.00 |
September | 453.57 | 218.63 | 234.94 | 888.85 | 111.32 | 0.00 | 0.00 | 0.00 |
October | 455.58 | 277.26 | 178.32 | 701.66 | 321.12 | 0.00 | 0.00 | 0.00 |
November | 350.32 | 210.30 | 140.02 | 423.43 | 474.10 | 0.00 | 0.00 | 0.00 |
December | 319.40 | 192.86 | 126.54 | 329.77 | 620.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 489.83 | 284.20 | 205.63 | 808.67 | 300.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 319.40 | 192.86 | 126.54 | 329.77 | 60.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 689.59 | 428.50 | 269.40 | 1409.58 | 620.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 362.54 | 227.43 | 135.11 | 438.94 | 509.73 | 0.00 | 0.00 | 0.00 |
February | 357.36 | 204.42 | 152.93 | 381.40 | 517.07 | 0.00 | 0.00 | 0.00 |
March | 447.22 | 230.05 | 217.16 | 560.64 | 440.64 | 0.00 | 0.00 | 0.00 |
April | 638.38 | 380.48 | 257.90 | 1051.78 | 231.53 | 0.00 | 0.00 | 0.00 |
May | 661.59 | 392.18 | 269.40 | 1166.74 | 176.73 | 0.00 | 0.00 | 0.00 |
June | 689.59 | 428.50 | 261.09 | 1409.58 | 75.40 | 0.00 | 0.00 | 0.00 |
July | 582.40 | 328.39 | 254.01 | 1198.22 | 60.19 | 0.00 | 0.00 | 0.00 |
August | 552.75 | 315.45 | 237.30 | 1129.06 | 78.91 | 0.00 | 0.00 | 0.00 |
September | 453.57 | 218.63 | 234.94 | 888.85 | 111.32 | 0.00 | 0.00 | 0.00 |
October | 455.58 | 277.26 | 178.32 | 701.66 | 321.12 | 0.00 | 0.00 | 0.00 |
November | 350.32 | 210.30 | 140.02 | 423.43 | 474.10 | 0.00 | 0.00 | 0.00 |
December | 319.40 | 192.86 | 126.54 | 329.77 | 620.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 489.83 | 284.20 | 205.63 | 808.67 | 300.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 319.40 | 192.86 | 126.54 | 329.77 | 60.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 689.59 | 428.50 | 269.40 | 1409.58 | 620.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 362.54 | 227.43 | 135.11 | 438.93 | 509.72 | 0.00 | 0.00 | 0.00 |
February | 357.35 | 204.42 | 152.93 | 381.39 | 517.06 | 0.00 | 0.00 | 0.00 |
March | 447.21 | 230.05 | 217.16 | 560.63 | 440.63 | 0.00 | 0.00 | 0.00 |
April | 638.36 | 380.47 | 257.89 | 1051.76 | 231.52 | 0.00 | 0.00 | 0.00 |
May | 661.57 | 392.18 | 269.40 | 1166.71 | 176.73 | 0.00 | 0.00 | 0.00 |
June | 689.58 | 428.49 | 261.08 | 1409.55 | 75.40 | 0.00 | 0.00 | 0.00 |
July | 582.39 | 328.39 | 254.00 | 1198.19 | 60.19 | 0.00 | 0.00 | 0.00 |
August | 552.74 | 315.45 | 237.29 | 1129.04 | 78.91 | 0.00 | 0.00 | 0.00 |
September | 453.56 | 218.62 | 234.94 | 888.83 | 111.32 | 0.00 | 0.00 | 0.00 |
October | 455.57 | 277.26 | 178.31 | 701.64 | 321.12 | 0.00 | 0.00 | 0.00 |
November | 350.31 | 210.30 | 140.01 | 423.42 | 474.10 | 0.00 | 0.00 | 0.00 |
December | 319.39 | 192.86 | 126.53 | 329.76 | 620.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 489.82 | 284.20 | 205.62 | 808.65 | 300.51 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 319.39 | 192.86 | 126.53 | 329.76 | 60.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 689.58 | 428.49 | 269.40 | 1409.55 | 620.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 831.67 | 664.23 | 167.44 | 1246.93 | 478.33 | 0.00 | 0.00 | 0.00 |
February | 525.85 | 354.65 | 171.20 | 695.83 | 469.62 | 0.00 | 0.00 | 0.00 |
March | 437.55 | 225.36 | 212.19 | 624.55 | 426.78 | 0.00 | 0.00 | 0.00 |
April | 372.47 | 150.51 | 221.96 | 698.77 | 242.35 | 0.00 | 0.00 | 0.00 |
May | 249.59 | 41.24 | 208.36 | 518.27 | 174.15 | 0.00 | 0.00 | 0.00 |
June | 213.72 | 16.48 | 197.25 | 595.50 | 73.77 | 0.00 | 0.00 | 0.00 |
July | 218.39 | 22.59 | 195.79 | 575.62 | 58.38 | 0.00 | 0.00 | 0.00 |
August | 265.55 | 73.38 | 192.16 | 666.46 | 77.31 | 0.00 | 0.00 | 0.00 |
September | 382.63 | 163.24 | 219.39 | 808.89 | 107.90 | 0.00 | 0.00 | 0.00 |
October | 609.68 | 421.99 | 187.69 | 1011.08 | 306.41 | 0.00 | 0.00 | 0.00 |
November | 710.51 | 544.22 | 166.30 | 1046.92 | 443.24 | 0.00 | 0.00 | 0.00 |
December | 773.21 | 612.10 | 161.11 | 1094.83 | 574.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 465.91 | 274.11 | 191.80 | 799.60 | 285.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 213.72 | 16.48 | 161.11 | 518.27 | 58.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 831.67 | 664.23 | 221.96 | 1246.93 | 574.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 831.67 | 664.23 | 167.44 | 1246.92 | 478.33 | 0.00 | 0.00 | 0.00 |
February | 525.85 | 354.65 | 171.20 | 695.83 | 469.62 | 0.00 | 0.00 | 0.00 |
March | 437.55 | 225.36 | 212.19 | 624.55 | 426.78 | 0.00 | 0.00 | 0.00 |
April | 372.47 | 150.51 | 221.95 | 698.77 | 242.35 | 0.00 | 0.00 | 0.00 |
May | 249.59 | 41.24 | 208.36 | 518.27 | 174.15 | 0.00 | 0.00 | 0.00 |
June | 213.72 | 16.48 | 197.25 | 595.50 | 73.77 | 0.00 | 0.00 | 0.00 |
July | 218.39 | 22.59 | 195.79 | 575.62 | 58.38 | 0.00 | 0.00 | 0.00 |
August | 265.55 | 73.38 | 192.16 | 666.46 | 77.30 | 0.00 | 0.00 | 0.00 |
September | 382.63 | 163.24 | 219.39 | 808.89 | 107.90 | 0.00 | 0.00 | 0.00 |
October | 609.68 | 421.99 | 187.69 | 1011.08 | 306.41 | 0.00 | 0.00 | 0.00 |
November | 710.51 | 544.22 | 166.30 | 1046.92 | 443.24 | 0.00 | 0.00 | 0.00 |
December | 773.21 | 612.10 | 161.11 | 1094.83 | 574.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 465.91 | 274.11 | 191.80 | 799.60 | 285.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 213.72 | 16.48 | 161.11 | 518.27 | 58.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 831.67 | 664.23 | 221.95 | 1246.92 | 574.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 831.67 | 664.23 | 167.44 | 1246.93 | 478.33 | 0.00 | 0.00 | 0.00 |
February | 525.85 | 354.65 | 171.20 | 695.83 | 469.62 | 0.00 | 0.00 | 0.00 |
March | 437.55 | 225.36 | 212.19 | 624.55 | 426.78 | 0.00 | 0.00 | 0.00 |
April | 372.47 | 150.51 | 221.96 | 698.77 | 242.35 | 0.00 | 0.00 | 0.00 |
May | 249.59 | 41.24 | 208.36 | 518.27 | 174.15 | 0.00 | 0.00 | 0.00 |
June | 213.72 | 16.48 | 197.25 | 595.50 | 73.77 | 0.00 | 0.00 | 0.00 |
July | 218.39 | 22.59 | 195.79 | 575.62 | 58.38 | 0.00 | 0.00 | 0.00 |
August | 265.55 | 73.38 | 192.16 | 666.46 | 77.31 | 0.00 | 0.00 | 0.00 |
September | 382.63 | 163.24 | 219.39 | 808.89 | 107.90 | 0.00 | 0.00 | 0.00 |
October | 609.68 | 421.99 | 187.69 | 1011.08 | 306.41 | 0.00 | 0.00 | 0.00 |
November | 710.51 | 544.22 | 166.30 | 1046.92 | 443.24 | 0.00 | 0.00 | 0.00 |
December | 773.21 | 612.10 | 161.11 | 1094.83 | 574.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 465.91 | 274.11 | 191.80 | 799.60 | 285.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 213.72 | 16.48 | 161.11 | 518.27 | 58.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 831.67 | 664.23 | 221.96 | 1246.93 | 574.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 831.67 | 664.23 | 167.44 | 1246.92 | 478.33 | 0.00 | 0.00 | 0.00 |
February | 525.85 | 354.65 | 171.20 | 695.83 | 469.62 | 0.00 | 0.00 | 0.00 |
March | 437.55 | 225.36 | 212.19 | 624.55 | 426.78 | 0.00 | 0.00 | 0.00 |
April | 372.47 | 150.51 | 221.95 | 698.77 | 242.35 | 0.00 | 0.00 | 0.00 |
May | 249.59 | 41.24 | 208.36 | 518.27 | 174.15 | 0.00 | 0.00 | 0.00 |
June | 213.72 | 16.48 | 197.25 | 595.50 | 73.77 | 0.00 | 0.00 | 0.00 |
July | 218.39 | 22.59 | 195.79 | 575.62 | 58.38 | 0.00 | 0.00 | 0.00 |
August | 265.55 | 73.38 | 192.16 | 666.46 | 77.30 | 0.00 | 0.00 | 0.00 |
September | 382.63 | 163.24 | 219.39 | 808.89 | 107.90 | 0.00 | 0.00 | 0.00 |
October | 609.68 | 421.99 | 187.69 | 1011.08 | 306.41 | 0.00 | 0.00 | 0.00 |
November | 710.51 | 544.22 | 166.30 | 1046.92 | 443.24 | 0.00 | 0.00 | 0.00 |
December | 773.21 | 612.10 | 161.11 | 1094.83 | 574.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 465.91 | 274.11 | 191.80 | 799.60 | 285.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 213.72 | 16.48 | 161.11 | 518.27 | 58.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 831.67 | 664.23 | 221.95 | 1246.92 | 574.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 831.64 | 664.21 | 167.43 | 1246.88 | 478.31 | 0.00 | 0.00 | 0.00 |
February | 525.83 | 354.64 | 171.19 | 695.80 | 469.60 | 0.00 | 0.00 | 0.00 |
March | 437.53 | 225.35 | 212.18 | 624.52 | 426.77 | 0.00 | 0.00 | 0.00 |
April | 372.45 | 150.51 | 221.95 | 698.74 | 242.34 | 0.00 | 0.00 | 0.00 |
May | 249.58 | 41.23 | 208.35 | 518.25 | 174.14 | 0.00 | 0.00 | 0.00 |
June | 213.72 | 16.47 | 197.24 | 595.48 | 73.77 | 0.00 | 0.00 | 0.00 |
July | 218.38 | 22.59 | 195.79 | 575.59 | 58.37 | 0.00 | 0.00 | 0.00 |
August | 265.54 | 73.38 | 192.16 | 666.43 | 77.30 | 0.00 | 0.00 | 0.00 |
September | 382.62 | 163.23 | 219.38 | 808.86 | 107.89 | 0.00 | 0.00 | 0.00 |
October | 609.66 | 421.98 | 187.68 | 1011.04 | 306.39 | 0.00 | 0.00 | 0.00 |
November | 710.48 | 544.19 | 166.29 | 1046.88 | 443.22 | 0.00 | 0.00 | 0.00 |
December | 773.18 | 612.07 | 161.10 | 1094.79 | 574.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 465.90 | 274.10 | 191.79 | 799.57 | 285.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 213.72 | 16.47 | 161.10 | 518.25 | 58.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 831.64 | 664.21 | 221.95 | 1246.88 | 574.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 379.10 | 235.62 | 143.48 | 524.38 | 598.51 | 0.00 | 0.00 | 0.00 |
February | 307.11 | 148.47 | 158.64 | 327.01 | 614.28 | 0.00 | 0.00 | 0.00 |
March | 406.78 | 193.92 | 212.86 | 508.04 | 540.82 | 0.00 | 0.00 | 0.00 |
April | 624.62 | 356.30 | 268.32 | 1035.01 | 319.73 | 0.00 | 0.00 | 0.00 |
May | 626.22 | 351.12 | 275.10 | 1130.60 | 216.65 | 0.00 | 0.00 | 0.00 |
June | 665.74 | 391.56 | 274.18 | 1373.95 | 96.95 | 0.00 | 0.00 | 0.00 |
July | 484.54 | 226.18 | 258.36 | 1020.41 | 79.41 | 0.00 | 0.00 | 0.00 |
August | 462.05 | 232.05 | 230.00 | 962.12 | 107.47 | 0.00 | 0.00 | 0.00 |
September | 402.75 | 169.22 | 233.53 | 811.00 | 124.55 | 0.00 | 0.00 | 0.00 |
October | 412.10 | 235.64 | 176.46 | 651.06 | 388.19 | 0.00 | 0.00 | 0.00 |
November | 379.56 | 229.17 | 150.39 | 502.29 | 589.01 | 0.00 | 0.00 | 0.00 |
December | 305.91 | 174.17 | 131.73 | 356.54 | 778.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 455.23 | 245.63 | 209.60 | 768.69 | 370.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 305.91 | 148.47 | 131.73 | 327.01 | 79.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 665.74 | 391.56 | 275.10 | 1373.95 | 778.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 379.10 | 235.62 | 143.48 | 524.38 | 598.51 | 0.00 | 0.00 | 0.00 |
February | 307.11 | 148.47 | 158.64 | 327.01 | 614.28 | 0.00 | 0.00 | 0.00 |
March | 406.78 | 193.92 | 212.86 | 508.04 | 540.82 | 0.00 | 0.00 | 0.00 |
April | 624.62 | 356.30 | 268.32 | 1035.01 | 319.73 | 0.00 | 0.00 | 0.00 |
May | 626.22 | 351.12 | 275.10 | 1130.60 | 216.65 | 0.00 | 0.00 | 0.00 |
June | 665.74 | 391.56 | 274.18 | 1373.95 | 96.95 | 0.00 | 0.00 | 0.00 |
July | 484.54 | 226.18 | 258.36 | 1020.41 | 79.41 | 0.00 | 0.00 | 0.00 |
August | 462.05 | 232.05 | 230.00 | 962.12 | 107.47 | 0.00 | 0.00 | 0.00 |
September | 402.75 | 169.22 | 233.53 | 811.00 | 124.55 | 0.00 | 0.00 | 0.00 |
October | 412.10 | 235.64 | 176.46 | 651.06 | 388.19 | 0.00 | 0.00 | 0.00 |
November | 379.56 | 229.17 | 150.39 | 502.29 | 589.01 | 0.00 | 0.00 | 0.00 |
December | 305.91 | 174.17 | 131.73 | 356.54 | 778.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 455.23 | 245.63 | 209.60 | 768.69 | 370.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 305.91 | 148.47 | 131.73 | 327.01 | 79.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 665.74 | 391.56 | 275.10 | 1373.95 | 778.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 379.10 | 235.61 | 143.48 | 524.37 | 598.50 | 0.00 | 0.00 | 0.00 |
February | 307.11 | 148.47 | 158.64 | 327.00 | 614.27 | 0.00 | 0.00 | 0.00 |
March | 406.77 | 193.91 | 212.86 | 508.03 | 540.81 | 0.00 | 0.00 | 0.00 |
April | 624.61 | 356.30 | 268.31 | 1034.99 | 319.72 | 0.00 | 0.00 | 0.00 |
May | 626.21 | 351.12 | 275.09 | 1130.58 | 216.64 | 0.00 | 0.00 | 0.00 |
June | 665.73 | 391.55 | 274.17 | 1373.92 | 96.95 | 0.00 | 0.00 | 0.00 |
July | 484.53 | 226.18 | 258.35 | 1020.40 | 79.41 | 0.00 | 0.00 | 0.00 |
August | 462.04 | 232.05 | 230.00 | 962.10 | 107.47 | 0.00 | 0.00 | 0.00 |
September | 402.75 | 169.22 | 233.53 | 810.98 | 124.54 | 0.00 | 0.00 | 0.00 |
October | 412.09 | 235.63 | 176.46 | 651.05 | 388.18 | 0.00 | 0.00 | 0.00 |
November | 379.55 | 229.16 | 150.39 | 502.28 | 589.00 | 0.00 | 0.00 | 0.00 |
December | 305.90 | 174.17 | 131.73 | 356.53 | 778.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 455.22 | 245.62 | 209.59 | 768.67 | 370.15 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 305.90 | 148.47 | 131.73 | 327.00 | 79.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 665.73 | 391.55 | 275.09 | 1373.92 | 778.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 505.01 | 0.00 | 505.01 | 397.67 | 2236.16 | 0.00 | 0.00 | 0.00 |
February | 575.45 | 0.00 | 575.45 | 251.26 | 2252.80 | 0.00 | 0.00 | 0.00 |
March | 764.77 | 0.00 | 764.77 | 684.22 | 1993.19 | 0.00 | 0.00 | 0.00 |
April | 931.76 | 9.67 | 922.09 | 1566.73 | 1085.57 | 0.00 | 0.00 | 0.00 |
May | 1090.72 | 87.33 | 1003.39 | 2154.45 | 733.08 | 0.00 | 0.00 | 0.00 |
June | 1267.49 | 230.29 | 1037.20 | 3416.60 | 306.12 | 0.00 | 0.00 | 0.00 |
July | 1080.93 | 112.61 | 968.32 | 2921.47 | 234.50 | 0.00 | 0.00 | 0.00 |
August | 872.50 | 21.68 | 850.83 | 2431.16 | 294.29 | 0.00 | 0.00 | 0.00 |
September | 823.19 | 0.22 | 822.97 | 2006.31 | 456.01 | 0.00 | 0.00 | 0.00 |
October | 636.89 | 0.00 | 636.89 | 948.19 | 1424.12 | 0.00 | 0.00 | 0.00 |
November | 530.64 | 0.00 | 530.64 | 390.90 | 2080.33 | 0.00 | 0.00 | 0.00 |
December | 471.73 | 0.00 | 471.73 | 233.71 | 2732.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 796.72 | 38.56 | 758.16 | 1455.75 | 1315.07 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 471.73 | 0.00 | 471.73 | 233.71 | 234.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1267.49 | 230.29 | 1037.20 | 3416.60 | 2732.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1087.62 | 682.29 | 405.32 | 1348.64 | 1402.29 | 0.00 | 0.00 | 0.00 |
February | 1072.06 | 613.27 | 458.79 | 1158.05 | 1426.10 | 0.00 | 0.00 | 0.00 |
March | 1341.63 | 690.15 | 651.49 | 1685.00 | 1255.64 | 0.00 | 0.00 | 0.00 |
April | 1915.11 | 1141.43 | 773.68 | 3137.63 | 700.75 | 0.00 | 0.00 | 0.00 |
May | 1984.74 | 1176.54 | 808.20 | 3501.75 | 498.81 | 0.00 | 0.00 | 0.00 |
June | 2068.74 | 1285.49 | 783.26 | 4267.68 | 196.39 | 0.00 | 0.00 | 0.00 |
July | 1747.18 | 985.17 | 762.02 | 3649.65 | 150.86 | 0.00 | 0.00 | 0.00 |
August | 1658.23 | 946.35 | 711.88 | 3435.22 | 192.42 | 0.00 | 0.00 | 0.00 |
September | 1360.69 | 655.88 | 704.81 | 2695.81 | 291.92 | 0.00 | 0.00 | 0.00 |
October | 1366.73 | 831.78 | 534.95 | 2117.25 | 898.53 | 0.00 | 0.00 | 0.00 |
November | 1050.94 | 630.89 | 420.05 | 1291.25 | 1312.07 | 0.00 | 0.00 | 0.00 |
December | 958.18 | 578.58 | 379.60 | 1036.12 | 1699.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1469.47 | 852.60 | 616.87 | 2449.81 | 832.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 958.18 | 578.58 | 379.60 | 1036.12 | 150.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2068.74 | 1285.49 | 808.20 | 4267.68 | 1699.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4158.30 | 3321.12 | 837.18 | 6180.92 | 2349.38 | 0.00 | 0.00 | 0.00 |
February | 2629.24 | 1773.25 | 855.99 | 3453.14 | 2257.60 | 0.00 | 0.00 | 0.00 |
March | 2187.72 | 1126.79 | 1060.93 | 3111.18 | 2058.06 | 0.00 | 0.00 | 0.00 |
April | 1862.32 | 752.56 | 1109.76 | 3503.61 | 1175.46 | 0.00 | 0.00 | 0.00 |
May | 1247.95 | 206.18 | 1041.77 | 2641.45 | 813.18 | 0.00 | 0.00 | 0.00 |
June | 1068.61 | 82.38 | 986.23 | 3102.25 | 315.05 | 0.00 | 0.00 | 0.00 |
July | 1091.93 | 112.97 | 978.96 | 3010.21 | 236.56 | 0.00 | 0.00 | 0.00 |
August | 1327.73 | 366.92 | 960.81 | 3441.74 | 305.66 | 0.00 | 0.00 | 0.00 |
September | 1913.14 | 816.19 | 1096.95 | 4080.37 | 483.61 | 0.00 | 0.00 | 0.00 |
October | 3048.38 | 2109.94 | 938.45 | 5031.86 | 1475.10 | 0.00 | 0.00 | 0.00 |
November | 3552.52 | 2721.05 | 831.47 | 5197.04 | 2142.70 | 0.00 | 0.00 | 0.00 |
December | 3865.99 | 3060.45 | 805.54 | 5455.09 | 2775.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2329.55 | 1370.55 | 958.99 | 4022.55 | 1362.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1068.61 | 82.38 | 805.54 | 2641.45 | 236.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4158.30 | 3321.12 | 1109.76 | 6180.92 | 2775.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1137.30 | 706.85 | 430.45 | 1624.65 | 1597.22 | 0.00 | 0.00 | 0.00 |
February | 921.32 | 445.40 | 475.92 | 1032.28 | 1548.85 | 0.00 | 0.00 | 0.00 |
March | 1220.32 | 581.75 | 638.58 | 1596.19 | 1383.73 | 0.00 | 0.00 | 0.00 |
April | 1873.84 | 1068.90 | 804.95 | 3160.72 | 843.59 | 0.00 | 0.00 | 0.00 |
May | 1878.65 | 1053.36 | 825.29 | 3409.95 | 605.70 | 0.00 | 0.00 | 0.00 |
June | 1997.20 | 1174.67 | 822.52 | 4174.01 | 260.63 | 0.00 | 0.00 | 0.00 |
July | 1453.61 | 678.54 | 775.07 | 3147.48 | 193.16 | 0.00 | 0.00 | 0.00 |
August | 1386.14 | 696.15 | 689.99 | 2981.52 | 241.13 | 0.00 | 0.00 | 0.00 |
September | 1208.25 | 507.66 | 700.59 | 2463.11 | 340.60 | 0.00 | 0.00 | 0.00 |
October | 1236.29 | 706.91 | 529.38 | 2001.74 | 1018.67 | 0.00 | 0.00 | 0.00 |
November | 1138.66 | 687.49 | 451.17 | 1569.10 | 1479.31 | 0.00 | 0.00 | 0.00 |
December | 917.71 | 522.52 | 395.19 | 1156.52 | 1908.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1365.66 | 736.88 | 628.78 | 2365.40 | 949.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 917.71 | 445.40 | 395.19 | 1032.28 | 193.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1997.20 | 1174.67 | 825.29 | 4174.01 | 1908.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 505.01 | 0.00 | 505.01 | 450.19 | 2052.77 | 0.00 | 0.00 | 0.00 |
February | 575.45 | 0.00 | 575.45 | 291.13 | 2035.65 | 0.00 | 0.00 | 0.00 |
March | 764.77 | 0.00 | 764.77 | 722.38 | 1867.35 | 0.00 | 0.00 | 0.00 |
April | 931.76 | 9.67 | 922.09 | 1557.79 | 1060.32 | 0.00 | 0.00 | 0.00 |
May | 1090.72 | 87.33 | 1003.39 | 2136.39 | 730.61 | 0.00 | 0.00 | 0.00 |
June | 1267.49 | 230.29 | 1037.20 | 3376.45 | 313.28 | 0.00 | 0.00 | 0.00 |
July | 1080.93 | 112.61 | 968.32 | 2876.17 | 244.22 | 0.00 | 0.00 | 0.00 |
August | 872.50 | 21.68 | 850.83 | 2396.64 | 300.56 | 0.00 | 0.00 | 0.00 |
September | 823.19 | 0.22 | 822.97 | 1980.06 | 460.58 | 0.00 | 0.00 | 0.00 |
October | 636.89 | 0.00 | 636.89 | 965.26 | 1341.76 | 0.00 | 0.00 | 0.00 |
November | 530.64 | 0.00 | 530.64 | 434.21 | 1904.59 | 0.00 | 0.00 | 0.00 |
December | 471.73 | 0.00 | 471.73 | 287.58 | 2494.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 796.72 | 38.56 | 758.16 | 1461.59 | 1230.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 471.73 | 0.00 | 471.73 | 287.58 | 244.22 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1267.49 | 230.29 | 1037.20 | 3376.45 | 2494.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1087.62 | 682.29 | 405.32 | 1386.63 | 1310.22 | 0.00 | 0.00 | 0.00 |
February | 1072.06 | 613.27 | 458.79 | 1188.66 | 1312.42 | 0.00 | 0.00 | 0.00 |
March | 1341.63 | 690.15 | 651.49 | 1705.74 | 1196.34 | 0.00 | 0.00 | 0.00 |
April | 1915.11 | 1141.43 | 773.68 | 3122.08 | 694.78 | 0.00 | 0.00 | 0.00 |
May | 1984.74 | 1176.54 | 808.20 | 3479.78 | 499.34 | 0.00 | 0.00 | 0.00 |
June | 2068.74 | 1285.49 | 783.26 | 4232.40 | 201.51 | 0.00 | 0.00 | 0.00 |
July | 1747.18 | 985.17 | 762.02 | 3612.36 | 157.57 | 0.00 | 0.00 | 0.00 |
August | 1658.23 | 946.35 | 711.88 | 3405.09 | 197.04 | 0.00 | 0.00 | 0.00 |
September | 1360.69 | 655.88 | 704.81 | 2672.68 | 296.21 | 0.00 | 0.00 | 0.00 |
October | 1366.73 | 831.78 | 534.95 | 2120.66 | 862.38 | 0.00 | 0.00 | 0.00 |
November | 1050.94 | 630.89 | 420.05 | 1322.35 | 1223.23 | 0.00 | 0.00 | 0.00 |
December | 958.18 | 578.58 | 379.60 | 1090.28 | 1569.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1469.47 | 852.60 | 616.87 | 2450.92 | 791.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 958.18 | 578.58 | 379.60 | 1090.28 | 157.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2068.74 | 1285.49 | 808.20 | 4232.40 | 1569.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4158.30 | 3321.12 | 837.18 | 6220.94 | 2212.78 | 0.00 | 0.00 | 0.00 |
February | 2629.24 | 1773.25 | 855.99 | 3492.73 | 2079.62 | 0.00 | 0.00 | 0.00 |
March | 2187.72 | 1126.79 | 1060.93 | 3136.29 | 1954.06 | 0.00 | 0.00 | 0.00 |
April | 1862.32 | 752.56 | 1109.76 | 3485.73 | 1152.15 | 0.00 | 0.00 | 0.00 |
May | 1247.95 | 206.18 | 1041.77 | 2620.81 | 805.01 | 0.00 | 0.00 | 0.00 |
June | 1068.61 | 82.38 | 986.23 | 3062.79 | 319.30 | 0.00 | 0.00 | 0.00 |
July | 1091.93 | 112.97 | 978.96 | 2965.37 | 244.45 | 0.00 | 0.00 | 0.00 |
August | 1327.73 | 366.92 | 960.81 | 3405.01 | 310.25 | 0.00 | 0.00 | 0.00 |
September | 1913.14 | 816.19 | 1096.95 | 4049.24 | 489.05 | 0.00 | 0.00 | 0.00 |
October | 3048.38 | 2109.94 | 938.45 | 5033.75 | 1415.08 | 0.00 | 0.00 | 0.00 |
November | 3552.52 | 2721.05 | 831.47 | 5232.04 | 2013.73 | 0.00 | 0.00 | 0.00 |
December | 3865.99 | 3060.45 | 805.54 | 5513.18 | 2588.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2329.55 | 1370.55 | 958.99 | 4023.14 | 1295.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1068.61 | 82.38 | 805.54 | 2620.81 | 244.45 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4158.30 | 3321.12 | 1109.76 | 6220.94 | 2588.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1137.30 | 706.85 | 430.45 | 1642.56 | 1499.78 | 0.00 | 0.00 | 0.00 |
February | 921.32 | 445.40 | 475.92 | 1047.14 | 1436.37 | 0.00 | 0.00 | 0.00 |
March | 1220.32 | 581.75 | 638.58 | 1609.12 | 1317.32 | 0.00 | 0.00 | 0.00 |
April | 1873.84 | 1068.90 | 804.95 | 3146.70 | 828.01 | 0.00 | 0.00 | 0.00 |
May | 1878.65 | 1053.36 | 825.29 | 3390.96 | 600.02 | 0.00 | 0.00 | 0.00 |
June | 1997.20 | 1174.67 | 822.52 | 4143.18 | 262.60 | 0.00 | 0.00 | 0.00 |
July | 1453.61 | 678.54 | 775.07 | 3118.35 | 197.53 | 0.00 | 0.00 | 0.00 |
August | 1386.14 | 696.15 | 689.99 | 2958.03 | 243.25 | 0.00 | 0.00 | 0.00 |
September | 1208.25 | 507.66 | 700.59 | 2444.47 | 341.97 | 0.00 | 0.00 | 0.00 |
October | 1236.29 | 706.91 | 529.38 | 2002.65 | 975.04 | 0.00 | 0.00 | 0.00 |
November | 1138.66 | 687.49 | 451.17 | 1583.96 | 1387.61 | 0.00 | 0.00 | 0.00 |
December | 917.71 | 522.52 | 395.19 | 1179.67 | 1782.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1365.66 | 736.88 | 628.78 | 2361.12 | 903.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 917.71 | 445.40 | 395.19 | 1047.14 | 197.53 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1997.20 | 1174.67 | 825.29 | 4143.18 | 1782.01 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270528E+09 | 0.00 | 0.270528E+09 | 0.165770E+09 | 0.135884E+10 |
February | 0.278428E+09 | 0.00 | 0.278428E+09 | 92968255.44 | 0.124417E+10 |
March | 0.409677E+09 | 0.00 | 0.409677E+09 | 0.329827E+09 | 0.118370E+10 |
April | 0.483030E+09 | 5012605.91 | 0.478017E+09 | 0.775339E+09 | 0.603007E+09 |
May | 0.584285E+09 | 46784161.73 | 0.537501E+09 | 0.111488E+10 | 0.428280E+09 |
June | 0.657074E+09 | 0.119384E+09 | 0.537690E+09 | 0.170551E+10 | 0.187904E+09 |
July | 0.579038E+09 | 60324299.85 | 0.518714E+09 | 0.148448E+10 | 0.159727E+09 |
August | 0.467388E+09 | 11611013.59 | 0.455777E+09 | 0.122220E+10 | 0.211007E+09 |
September | 0.426749E+09 | 113921.23 | 0.426635E+09 | 0.992688E+09 | 0.279375E+09 |
October | 0.341171E+09 | 0.00 | 0.341171E+09 | 0.465460E+09 | 0.856891E+09 |
November | 0.275089E+09 | 0.00 | 0.275089E+09 | 0.164139E+09 | 0.123266E+10 |
December | 0.252698E+09 | 0.00 | 0.252698E+09 | 76711412.97 | 0.169958E+10 |
Annual Sum or Average | 0.502515E+10 | 0.243230E+09 | 0.478192E+10 | 0.858997E+10 | 0.944514E+10 |
Minimum of Months | 0.252698E+09 | 0.00 | 0.252698E+09 | 76711412.97 | 0.159727E+09 |
Maximum of Months | 0.657074E+09 | 0.119384E+09 | 0.537690E+09 | 0.170551E+10 | 0.169958E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270527E+09 | 0.00 | 0.270527E+09 | 0.165770E+09 | 0.135884E+10 |
February | 0.278428E+09 | 0.00 | 0.278428E+09 | 92968100.99 | 0.124417E+10 |
March | 0.409676E+09 | 0.00 | 0.409676E+09 | 0.329827E+09 | 0.118370E+10 |
April | 0.483029E+09 | 5012599.89 | 0.478017E+09 | 0.775339E+09 | 0.603006E+09 |
May | 0.584285E+09 | 46784105.59 | 0.537501E+09 | 0.111488E+10 | 0.428280E+09 |
June | 0.657073E+09 | 0.119383E+09 | 0.537690E+09 | 0.170551E+10 | 0.187904E+09 |
July | 0.579038E+09 | 60324227.47 | 0.518713E+09 | 0.148448E+10 | 0.159726E+09 |
August | 0.467388E+09 | 11610999.65 | 0.455777E+09 | 0.122219E+10 | 0.211006E+09 |
September | 0.426748E+09 | 113921.09 | 0.426635E+09 | 0.992687E+09 | 0.279375E+09 |
October | 0.341171E+09 | 0.00 | 0.341171E+09 | 0.465460E+09 | 0.856890E+09 |
November | 0.275089E+09 | 0.00 | 0.275089E+09 | 0.164139E+09 | 0.123266E+10 |
December | 0.252698E+09 | 0.00 | 0.252698E+09 | 76711342.72 | 0.169958E+10 |
Annual Sum or Average | 0.502515E+10 | 0.243229E+09 | 0.478192E+10 | 0.858996E+10 | 0.944514E+10 |
Minimum of Months | 0.252698E+09 | 0.00 | 0.252698E+09 | 76711342.72 | 0.159726E+09 |
Maximum of Months | 0.657073E+09 | 0.119383E+09 | 0.537690E+09 | 0.170551E+10 | 0.169958E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270528E+09 | 0.00 | 0.270528E+09 | 0.165770E+09 | 0.135884E+10 |
February | 0.278428E+09 | 0.00 | 0.278428E+09 | 92968255.44 | 0.124417E+10 |
March | 0.409677E+09 | 0.00 | 0.409677E+09 | 0.329827E+09 | 0.118370E+10 |
April | 0.483030E+09 | 5012605.91 | 0.478017E+09 | 0.775339E+09 | 0.603007E+09 |
May | 0.584285E+09 | 46784161.73 | 0.537501E+09 | 0.111488E+10 | 0.428280E+09 |
June | 0.657074E+09 | 0.119384E+09 | 0.537690E+09 | 0.170551E+10 | 0.187904E+09 |
July | 0.579038E+09 | 60324299.85 | 0.518714E+09 | 0.148448E+10 | 0.159727E+09 |
August | 0.467388E+09 | 11611013.59 | 0.455777E+09 | 0.122220E+10 | 0.211007E+09 |
September | 0.426749E+09 | 113921.23 | 0.426635E+09 | 0.992688E+09 | 0.279375E+09 |
October | 0.341171E+09 | 0.00 | 0.341171E+09 | 0.465460E+09 | 0.856891E+09 |
November | 0.275089E+09 | 0.00 | 0.275089E+09 | 0.164139E+09 | 0.123266E+10 |
December | 0.252698E+09 | 0.00 | 0.252698E+09 | 76711412.97 | 0.169958E+10 |
Annual Sum or Average | 0.502515E+10 | 0.243230E+09 | 0.478192E+10 | 0.858997E+10 | 0.944514E+10 |
Minimum of Months | 0.252698E+09 | 0.00 | 0.252698E+09 | 76711412.97 | 0.159727E+09 |
Maximum of Months | 0.657074E+09 | 0.119384E+09 | 0.537690E+09 | 0.170551E+10 | 0.169958E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270527E+09 | 0.00 | 0.270527E+09 | 0.165770E+09 | 0.135884E+10 |
February | 0.278428E+09 | 0.00 | 0.278428E+09 | 92968100.99 | 0.124417E+10 |
March | 0.409676E+09 | 0.00 | 0.409676E+09 | 0.329827E+09 | 0.118370E+10 |
April | 0.483029E+09 | 5012599.89 | 0.478017E+09 | 0.775339E+09 | 0.603006E+09 |
May | 0.584285E+09 | 46784105.59 | 0.537501E+09 | 0.111488E+10 | 0.428280E+09 |
June | 0.657073E+09 | 0.119383E+09 | 0.537690E+09 | 0.170551E+10 | 0.187904E+09 |
July | 0.579038E+09 | 60324227.47 | 0.518713E+09 | 0.148448E+10 | 0.159726E+09 |
August | 0.467388E+09 | 11610999.65 | 0.455777E+09 | 0.122219E+10 | 0.211006E+09 |
September | 0.426748E+09 | 113921.09 | 0.426635E+09 | 0.992687E+09 | 0.279375E+09 |
October | 0.341171E+09 | 0.00 | 0.341171E+09 | 0.465460E+09 | 0.856890E+09 |
November | 0.275089E+09 | 0.00 | 0.275089E+09 | 0.164139E+09 | 0.123266E+10 |
December | 0.252698E+09 | 0.00 | 0.252698E+09 | 76711342.72 | 0.169958E+10 |
Annual Sum or Average | 0.502515E+10 | 0.243229E+09 | 0.478192E+10 | 0.858996E+10 | 0.944514E+10 |
Minimum of Months | 0.252698E+09 | 0.00 | 0.252698E+09 | 76711342.72 | 0.159726E+09 |
Maximum of Months | 0.657073E+09 | 0.119383E+09 | 0.537690E+09 | 0.170551E+10 | 0.169958E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.270517E+09 | 0.00 | 0.270517E+09 | 0.165763E+09 | 0.135879E+10 |
February | 0.278417E+09 | 0.00 | 0.278417E+09 | 92964508.40 | 0.124412E+10 |
March | 0.409660E+09 | 0.00 | 0.409660E+09 | 0.329814E+09 | 0.118365E+10 |
April | 0.483010E+09 | 5012403.88 | 0.477998E+09 | 0.775308E+09 | 0.602982E+09 |
May | 0.584262E+09 | 46782276.12 | 0.537479E+09 | 0.111483E+10 | 0.428263E+09 |
June | 0.657047E+09 | 0.119379E+09 | 0.537668E+09 | 0.170544E+10 | 0.187897E+09 |
July | 0.579015E+09 | 60321868.52 | 0.518693E+09 | 0.148442E+10 | 0.159720E+09 |
August | 0.467369E+09 | 11610545.61 | 0.455759E+09 | 0.122215E+10 | 0.210998E+09 |
September | 0.426732E+09 | 113916.64 | 0.426618E+09 | 0.992648E+09 | 0.279364E+09 |
October | 0.341158E+09 | 0.00 | 0.341158E+09 | 0.465442E+09 | 0.856856E+09 |
November | 0.275078E+09 | 0.00 | 0.275078E+09 | 0.164132E+09 | 0.123261E+10 |
December | 0.252688E+09 | 0.00 | 0.252688E+09 | 76708321.17 | 0.169952E+10 |
Annual Sum or Average | 0.502495E+10 | 0.243220E+09 | 0.478173E+10 | 0.858962E+10 | 0.944476E+10 |
Minimum of Months | 0.252688E+09 | 0.00 | 0.252688E+09 | 76708321.17 | 0.159720E+09 |
Maximum of Months | 0.657047E+09 | 0.119379E+09 | 0.537668E+09 | 0.170544E+10 | 0.169952E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.971035E+09 | 0.609157E+09 | 0.361878E+09 | 0.117565E+10 | 0.136527E+10 |
February | 0.864517E+09 | 0.494543E+09 | 0.369974E+09 | 0.922676E+09 | 0.125089E+10 |
March | 0.119782E+10 | 0.616168E+09 | 0.581653E+09 | 0.150163E+10 | 0.118022E+10 |
April | 0.165467E+10 | 0.986204E+09 | 0.668465E+09 | 0.272621E+10 | 0.600122E+09 |
May | 0.177199E+10 | 0.105042E+10 | 0.721572E+09 | 0.312499E+10 | 0.473360E+09 |
June | 0.178741E+10 | 0.111067E+10 | 0.676739E+09 | 0.365363E+10 | 0.195442E+09 |
July | 0.155990E+10 | 0.879565E+09 | 0.680337E+09 | 0.320930E+10 | 0.161213E+09 |
August | 0.148048E+10 | 0.844910E+09 | 0.635572E+09 | 0.302409E+10 | 0.211361E+09 |
September | 0.117565E+10 | 0.566684E+09 | 0.608965E+09 | 0.230389E+10 | 0.288540E+09 |
October | 0.122023E+10 | 0.742625E+09 | 0.477607E+09 | 0.187932E+10 | 0.860096E+09 |
November | 0.908023E+09 | 0.545098E+09 | 0.362925E+09 | 0.109753E+10 | 0.122888E+10 |
December | 0.855475E+09 | 0.516561E+09 | 0.338914E+09 | 0.883255E+09 | 0.166158E+10 |
Annual Sum or Average | 0.154472E+11 | 0.896261E+10 | 0.648460E+10 | 0.255022E+11 | 0.947697E+10 |
Minimum of Months | 0.855475E+09 | 0.494543E+09 | 0.338914E+09 | 0.883255E+09 | 0.161213E+09 |
Maximum of Months | 0.178741E+10 | 0.111067E+10 | 0.721572E+09 | 0.365363E+10 | 0.166158E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.971035E+09 | 0.609157E+09 | 0.361878E+09 | 0.117565E+10 | 0.136527E+10 |
February | 0.864517E+09 | 0.494543E+09 | 0.369974E+09 | 0.922676E+09 | 0.125089E+10 |
March | 0.119782E+10 | 0.616168E+09 | 0.581653E+09 | 0.150163E+10 | 0.118022E+10 |
April | 0.165467E+10 | 0.986204E+09 | 0.668465E+09 | 0.272621E+10 | 0.600122E+09 |
May | 0.177199E+10 | 0.105042E+10 | 0.721572E+09 | 0.312499E+10 | 0.473360E+09 |
June | 0.178741E+10 | 0.111067E+10 | 0.676739E+09 | 0.365363E+10 | 0.195442E+09 |
July | 0.155990E+10 | 0.879565E+09 | 0.680337E+09 | 0.320930E+10 | 0.161213E+09 |
August | 0.148048E+10 | 0.844910E+09 | 0.635572E+09 | 0.302409E+10 | 0.211361E+09 |
September | 0.117565E+10 | 0.566684E+09 | 0.608965E+09 | 0.230389E+10 | 0.288540E+09 |
October | 0.122023E+10 | 0.742625E+09 | 0.477607E+09 | 0.187932E+10 | 0.860096E+09 |
November | 0.908023E+09 | 0.545098E+09 | 0.362925E+09 | 0.109753E+10 | 0.122888E+10 |
December | 0.855475E+09 | 0.516561E+09 | 0.338914E+09 | 0.883255E+09 | 0.166158E+10 |
Annual Sum or Average | 0.154472E+11 | 0.896261E+10 | 0.648460E+10 | 0.255022E+11 | 0.947697E+10 |
Minimum of Months | 0.855475E+09 | 0.494543E+09 | 0.338914E+09 | 0.883255E+09 | 0.161213E+09 |
Maximum of Months | 0.178741E+10 | 0.111067E+10 | 0.721572E+09 | 0.365363E+10 | 0.166158E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.971017E+09 | 0.609146E+09 | 0.361871E+09 | 0.117563E+10 | 0.136524E+10 |
February | 0.864501E+09 | 0.494534E+09 | 0.369967E+09 | 0.922659E+09 | 0.125087E+10 |
March | 0.119780E+10 | 0.616157E+09 | 0.581642E+09 | 0.150160E+10 | 0.118020E+10 |
April | 0.165464E+10 | 0.986186E+09 | 0.668453E+09 | 0.272616E+10 | 0.600111E+09 |
May | 0.177196E+10 | 0.105040E+10 | 0.721558E+09 | 0.312493E+10 | 0.473352E+09 |
June | 0.178738E+10 | 0.111065E+10 | 0.676727E+09 | 0.365357E+10 | 0.195438E+09 |
July | 0.155987E+10 | 0.879549E+09 | 0.680324E+09 | 0.320924E+10 | 0.161210E+09 |
August | 0.148046E+10 | 0.844895E+09 | 0.635561E+09 | 0.302403E+10 | 0.211357E+09 |
September | 0.117563E+10 | 0.566673E+09 | 0.608954E+09 | 0.230385E+10 | 0.288535E+09 |
October | 0.122021E+10 | 0.742611E+09 | 0.477599E+09 | 0.187928E+10 | 0.860081E+09 |
November | 0.908006E+09 | 0.545088E+09 | 0.362918E+09 | 0.109751E+10 | 0.122886E+10 |
December | 0.855460E+09 | 0.516552E+09 | 0.338908E+09 | 0.883239E+09 | 0.166155E+10 |
Annual Sum or Average | 0.154469E+11 | 0.896245E+10 | 0.648448E+10 | 0.255017E+11 | 0.947680E+10 |
Minimum of Months | 0.855460E+09 | 0.494534E+09 | 0.338908E+09 | 0.883239E+09 | 0.161210E+09 |
Maximum of Months | 0.178738E+10 | 0.111065E+10 | 0.721558E+09 | 0.365357E+10 | 0.166155E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222755E+10 | 0.177908E+10 | 0.448468E+09 | 0.333977E+10 | 0.128116E+10 |
February | 0.127215E+10 | 0.857979E+09 | 0.414166E+09 | 0.168335E+10 | 0.113610E+10 |
March | 0.117193E+10 | 0.603606E+09 | 0.568326E+09 | 0.167279E+10 | 0.114310E+10 |
April | 0.965439E+09 | 0.390132E+09 | 0.575308E+09 | 0.181120E+10 | 0.628177E+09 |
May | 0.668510E+09 | 0.110446E+09 | 0.558064E+09 | 0.138813E+10 | 0.466432E+09 |
June | 0.553972E+09 | 42704110.21 | 0.511268E+09 | 0.154354E+10 | 0.191211E+09 |
July | 0.584932E+09 | 60516029.40 | 0.524416E+09 | 0.154173E+10 | 0.156355E+09 |
August | 0.711248E+09 | 0.196554E+09 | 0.514694E+09 | 0.178505E+10 | 0.207054E+09 |
September | 0.991782E+09 | 0.423119E+09 | 0.568663E+09 | 0.209665E+10 | 0.279670E+09 |
October | 0.163298E+10 | 0.113026E+10 | 0.502713E+09 | 0.270808E+10 | 0.820679E+09 |
November | 0.184165E+10 | 0.141061E+10 | 0.431040E+09 | 0.271361E+10 | 0.114888E+10 |
December | 0.207096E+10 | 0.163944E+10 | 0.431516E+09 | 0.293241E+10 | 0.153933E+10 |
Annual Sum or Average | 0.146931E+11 | 0.864445E+10 | 0.604864E+10 | 0.252163E+11 | 0.899814E+10 |
Minimum of Months | 0.553972E+09 | 42704110.21 | 0.414166E+09 | 0.138813E+10 | 0.156355E+09 |
Maximum of Months | 0.222755E+10 | 0.177908E+10 | 0.575308E+09 | 0.333977E+10 | 0.153933E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222754E+10 | 0.177908E+10 | 0.448467E+09 | 0.333976E+10 | 0.128116E+10 |
February | 0.127214E+10 | 0.857978E+09 | 0.414166E+09 | 0.168335E+10 | 0.113610E+10 |
March | 0.117193E+10 | 0.603606E+09 | 0.568325E+09 | 0.167279E+10 | 0.114310E+10 |
April | 0.965438E+09 | 0.390131E+09 | 0.575307E+09 | 0.181120E+10 | 0.628177E+09 |
May | 0.668509E+09 | 0.110445E+09 | 0.558064E+09 | 0.138813E+10 | 0.466432E+09 |
June | 0.553972E+09 | 42704058.97 | 0.511268E+09 | 0.154354E+10 | 0.191211E+09 |
July | 0.584931E+09 | 60515956.79 | 0.524415E+09 | 0.154173E+10 | 0.156355E+09 |
August | 0.711248E+09 | 0.196554E+09 | 0.514694E+09 | 0.178505E+10 | 0.207054E+09 |
September | 0.991781E+09 | 0.423119E+09 | 0.568663E+09 | 0.209664E+10 | 0.279670E+09 |
October | 0.163298E+10 | 0.113026E+10 | 0.502713E+09 | 0.270808E+10 | 0.820679E+09 |
November | 0.184165E+10 | 0.141061E+10 | 0.431040E+09 | 0.271361E+10 | 0.114888E+10 |
December | 0.207095E+10 | 0.163944E+10 | 0.431515E+09 | 0.293240E+10 | 0.153933E+10 |
Annual Sum or Average | 0.146931E+11 | 0.864444E+10 | 0.604864E+10 | 0.252163E+11 | 0.899814E+10 |
Minimum of Months | 0.553972E+09 | 42704058.97 | 0.414166E+09 | 0.138813E+10 | 0.156355E+09 |
Maximum of Months | 0.222754E+10 | 0.177908E+10 | 0.575307E+09 | 0.333976E+10 | 0.153933E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222755E+10 | 0.177908E+10 | 0.448468E+09 | 0.333977E+10 | 0.128116E+10 |
February | 0.127215E+10 | 0.857979E+09 | 0.414166E+09 | 0.168335E+10 | 0.113610E+10 |
March | 0.117193E+10 | 0.603606E+09 | 0.568326E+09 | 0.167279E+10 | 0.114310E+10 |
April | 0.965439E+09 | 0.390132E+09 | 0.575308E+09 | 0.181120E+10 | 0.628177E+09 |
May | 0.668510E+09 | 0.110446E+09 | 0.558064E+09 | 0.138813E+10 | 0.466432E+09 |
June | 0.553972E+09 | 42704110.21 | 0.511268E+09 | 0.154354E+10 | 0.191211E+09 |
July | 0.584932E+09 | 60516029.40 | 0.524416E+09 | 0.154173E+10 | 0.156355E+09 |
August | 0.711248E+09 | 0.196554E+09 | 0.514694E+09 | 0.178505E+10 | 0.207054E+09 |
September | 0.991782E+09 | 0.423119E+09 | 0.568663E+09 | 0.209665E+10 | 0.279670E+09 |
October | 0.163298E+10 | 0.113026E+10 | 0.502713E+09 | 0.270808E+10 | 0.820679E+09 |
November | 0.184165E+10 | 0.141061E+10 | 0.431040E+09 | 0.271361E+10 | 0.114888E+10 |
December | 0.207096E+10 | 0.163944E+10 | 0.431516E+09 | 0.293241E+10 | 0.153933E+10 |
Annual Sum or Average | 0.146931E+11 | 0.864445E+10 | 0.604864E+10 | 0.252163E+11 | 0.899814E+10 |
Minimum of Months | 0.553972E+09 | 42704110.21 | 0.414166E+09 | 0.138813E+10 | 0.156355E+09 |
Maximum of Months | 0.222755E+10 | 0.177908E+10 | 0.575308E+09 | 0.333977E+10 | 0.153933E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222754E+10 | 0.177908E+10 | 0.448467E+09 | 0.333976E+10 | 0.128116E+10 |
February | 0.127214E+10 | 0.857978E+09 | 0.414166E+09 | 0.168335E+10 | 0.113610E+10 |
March | 0.117193E+10 | 0.603606E+09 | 0.568325E+09 | 0.167279E+10 | 0.114310E+10 |
April | 0.965438E+09 | 0.390131E+09 | 0.575307E+09 | 0.181120E+10 | 0.628177E+09 |
May | 0.668509E+09 | 0.110445E+09 | 0.558064E+09 | 0.138813E+10 | 0.466432E+09 |
June | 0.553972E+09 | 42704058.97 | 0.511268E+09 | 0.154354E+10 | 0.191211E+09 |
July | 0.584931E+09 | 60515956.79 | 0.524415E+09 | 0.154173E+10 | 0.156355E+09 |
August | 0.711248E+09 | 0.196554E+09 | 0.514694E+09 | 0.178505E+10 | 0.207054E+09 |
September | 0.991781E+09 | 0.423119E+09 | 0.568663E+09 | 0.209664E+10 | 0.279670E+09 |
October | 0.163298E+10 | 0.113026E+10 | 0.502713E+09 | 0.270808E+10 | 0.820679E+09 |
November | 0.184165E+10 | 0.141061E+10 | 0.431040E+09 | 0.271361E+10 | 0.114888E+10 |
December | 0.207095E+10 | 0.163944E+10 | 0.431515E+09 | 0.293240E+10 | 0.153933E+10 |
Annual Sum or Average | 0.146931E+11 | 0.864444E+10 | 0.604864E+10 | 0.252163E+11 | 0.899814E+10 |
Minimum of Months | 0.553972E+09 | 42704058.97 | 0.414166E+09 | 0.138813E+10 | 0.156355E+09 |
Maximum of Months | 0.222754E+10 | 0.177908E+10 | 0.575307E+09 | 0.333976E+10 | 0.153933E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222746E+10 | 0.177901E+10 | 0.448450E+09 | 0.333963E+10 | 0.128111E+10 |
February | 0.127209E+10 | 0.857945E+09 | 0.414150E+09 | 0.168329E+10 | 0.113606E+10 |
March | 0.117188E+10 | 0.603582E+09 | 0.568303E+09 | 0.167273E+10 | 0.114305E+10 |
April | 0.965400E+09 | 0.390116E+09 | 0.575284E+09 | 0.181113E+10 | 0.628152E+09 |
May | 0.668483E+09 | 0.110441E+09 | 0.558042E+09 | 0.138808E+10 | 0.466413E+09 |
June | 0.553950E+09 | 42702389.04 | 0.511247E+09 | 0.154347E+10 | 0.191203E+09 |
July | 0.584908E+09 | 60513590.34 | 0.524394E+09 | 0.154167E+10 | 0.156349E+09 |
August | 0.711220E+09 | 0.196546E+09 | 0.514673E+09 | 0.178498E+10 | 0.207045E+09 |
September | 0.991742E+09 | 0.423102E+09 | 0.568640E+09 | 0.209656E+10 | 0.279659E+09 |
October | 0.163291E+10 | 0.113022E+10 | 0.502693E+09 | 0.270797E+10 | 0.820646E+09 |
November | 0.184157E+10 | 0.141055E+10 | 0.431023E+09 | 0.271350E+10 | 0.114883E+10 |
December | 0.207087E+10 | 0.163937E+10 | 0.431498E+09 | 0.293229E+10 | 0.153926E+10 |
Annual Sum or Average | 0.146925E+11 | 0.864410E+10 | 0.604840E+10 | 0.252153E+11 | 0.899778E+10 |
Minimum of Months | 0.553950E+09 | 42702389.04 | 0.414150E+09 | 0.138808E+10 | 0.156349E+09 |
Maximum of Months | 0.222746E+10 | 0.177901E+10 | 0.575284E+09 | 0.333963E+10 | 0.153926E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101539E+10 | 0.631082E+09 | 0.384310E+09 | 0.140451E+10 | 0.160305E+10 |
February | 0.742963E+09 | 0.359177E+09 | 0.383786E+09 | 0.791095E+09 | 0.148608E+10 |
March | 0.108952E+10 | 0.519389E+09 | 0.570126E+09 | 0.136072E+10 | 0.144853E+10 |
April | 0.161902E+10 | 0.923537E+09 | 0.695481E+09 | 0.268273E+10 | 0.828733E+09 |
May | 0.167728E+10 | 0.940453E+09 | 0.736827E+09 | 0.302820E+10 | 0.580272E+09 |
June | 0.172559E+10 | 0.101493E+10 | 0.710667E+09 | 0.356127E+10 | 0.251291E+09 |
July | 0.129779E+10 | 0.605805E+09 | 0.691988E+09 | 0.273308E+10 | 0.212690E+09 |
August | 0.123756E+10 | 0.621529E+09 | 0.616033E+09 | 0.257694E+10 | 0.287860E+09 |
September | 0.104394E+10 | 0.438621E+09 | 0.605319E+09 | 0.210211E+10 | 0.322825E+09 |
October | 0.110377E+10 | 0.631136E+09 | 0.472638E+09 | 0.174381E+10 | 0.103971E+10 |
November | 0.983810E+09 | 0.593996E+09 | 0.389814E+09 | 0.130194E+10 | 0.152670E+10 |
December | 0.819340E+09 | 0.466507E+09 | 0.352833E+09 | 0.954951E+09 | 0.208540E+10 |
Annual Sum or Average | 0.143560E+11 | 0.774616E+10 | 0.660982E+10 | 0.242414E+11 | 0.116731E+11 |
Minimum of Months | 0.742963E+09 | 0.359177E+09 | 0.352833E+09 | 0.791095E+09 | 0.212690E+09 |
Maximum of Months | 0.172559E+10 | 0.101493E+10 | 0.736827E+09 | 0.356127E+10 | 0.208540E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101539E+10 | 0.631082E+09 | 0.384310E+09 | 0.140451E+10 | 0.160305E+10 |
February | 0.742963E+09 | 0.359177E+09 | 0.383786E+09 | 0.791095E+09 | 0.148608E+10 |
March | 0.108952E+10 | 0.519389E+09 | 0.570126E+09 | 0.136072E+10 | 0.144853E+10 |
April | 0.161902E+10 | 0.923537E+09 | 0.695481E+09 | 0.268273E+10 | 0.828733E+09 |
May | 0.167728E+10 | 0.940453E+09 | 0.736827E+09 | 0.302820E+10 | 0.580272E+09 |
June | 0.172559E+10 | 0.101493E+10 | 0.710667E+09 | 0.356127E+10 | 0.251291E+09 |
July | 0.129779E+10 | 0.605805E+09 | 0.691988E+09 | 0.273308E+10 | 0.212690E+09 |
August | 0.123756E+10 | 0.621529E+09 | 0.616033E+09 | 0.257694E+10 | 0.287860E+09 |
September | 0.104394E+10 | 0.438621E+09 | 0.605319E+09 | 0.210211E+10 | 0.322825E+09 |
October | 0.110377E+10 | 0.631136E+09 | 0.472638E+09 | 0.174381E+10 | 0.103971E+10 |
November | 0.983810E+09 | 0.593996E+09 | 0.389814E+09 | 0.130194E+10 | 0.152670E+10 |
December | 0.819340E+09 | 0.466507E+09 | 0.352833E+09 | 0.954951E+09 | 0.208540E+10 |
Annual Sum or Average | 0.143560E+11 | 0.774616E+10 | 0.660982E+10 | 0.242414E+11 | 0.116731E+11 |
Minimum of Months | 0.742963E+09 | 0.359177E+09 | 0.352833E+09 | 0.791095E+09 | 0.212690E+09 |
Maximum of Months | 0.172559E+10 | 0.101493E+10 | 0.736827E+09 | 0.356127E+10 | 0.208540E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.101537E+10 | 0.631071E+09 | 0.384303E+09 | 0.140449E+10 | 0.160302E+10 |
February | 0.742950E+09 | 0.359171E+09 | 0.383779E+09 | 0.791080E+09 | 0.148605E+10 |
March | 0.108950E+10 | 0.519380E+09 | 0.570116E+09 | 0.136070E+10 | 0.144850E+10 |
April | 0.161899E+10 | 0.923520E+09 | 0.695468E+09 | 0.268268E+10 | 0.828717E+09 |
May | 0.167725E+10 | 0.940435E+09 | 0.736813E+09 | 0.302815E+10 | 0.580261E+09 |
June | 0.172556E+10 | 0.101491E+10 | 0.710654E+09 | 0.356120E+10 | 0.251287E+09 |
July | 0.129777E+10 | 0.605794E+09 | 0.691975E+09 | 0.273303E+10 | 0.212686E+09 |
August | 0.123754E+10 | 0.621517E+09 | 0.616021E+09 | 0.257689E+10 | 0.287854E+09 |
September | 0.104392E+10 | 0.438613E+09 | 0.605308E+09 | 0.210207E+10 | 0.322819E+09 |
October | 0.110375E+10 | 0.631124E+09 | 0.472630E+09 | 0.174378E+10 | 0.103970E+10 |
November | 0.983792E+09 | 0.593985E+09 | 0.389807E+09 | 0.130191E+10 | 0.152668E+10 |
December | 0.819325E+09 | 0.466499E+09 | 0.352827E+09 | 0.954933E+09 | 0.208536E+10 |
Annual Sum or Average | 0.143557E+11 | 0.774602E+10 | 0.660970E+10 | 0.242409E+11 | 0.116729E+11 |
Minimum of Months | 0.742950E+09 | 0.359171E+09 | 0.352827E+09 | 0.791080E+09 | 0.212686E+09 |
Maximum of Months | 0.172556E+10 | 0.101491E+10 | 0.736813E+09 | 0.356120E+10 | 0.208536E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135262E+10 | 0.00 | 0.135262E+10 | 0.106511E+10 | 0.598932E+10 |
February | 0.139212E+10 | 0.00 | 0.139212E+10 | 0.607840E+09 | 0.544998E+10 |
March | 0.204836E+10 | 0.00 | 0.204836E+10 | 0.183262E+10 | 0.533857E+10 |
April | 0.241512E+10 | 25062726.47 | 0.239006E+10 | 0.406096E+10 | 0.281381E+10 |
May | 0.292139E+10 | 0.233918E+09 | 0.268747E+10 | 0.577049E+10 | 0.196347E+10 |
June | 0.328533E+10 | 0.596911E+09 | 0.268842E+10 | 0.885582E+10 | 0.793459E+09 |
July | 0.289516E+10 | 0.301618E+09 | 0.259354E+10 | 0.782488E+10 | 0.628078E+09 |
August | 0.233691E+10 | 58054365.94 | 0.227886E+10 | 0.651161E+10 | 0.788229E+09 |
September | 0.213372E+10 | 569599.25 | 0.213315E+10 | 0.520035E+10 | 0.118198E+10 |
October | 0.170584E+10 | 0.00 | 0.170584E+10 | 0.253963E+10 | 0.381438E+10 |
November | 0.137543E+10 | 0.00 | 0.137543E+10 | 0.101320E+10 | 0.539223E+10 |
December | 0.126347E+10 | 0.00 | 0.126347E+10 | 0.625976E+09 | 0.731870E+10 |
Annual Sum or Average | 0.251255E+11 | 0.121613E+10 | 0.239093E+11 | 0.459085E+11 | 0.414722E+11 |
Minimum of Months | 0.126347E+10 | 0.00 | 0.126347E+10 | 0.607840E+09 | 0.628078E+09 |
Maximum of Months | 0.328533E+10 | 0.596911E+09 | 0.268842E+10 | 0.885582E+10 | 0.731870E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.291307E+10 | 0.182745E+10 | 0.108562E+10 | 0.361218E+10 | 0.375590E+10 |
February | 0.259352E+10 | 0.148361E+10 | 0.110991E+10 | 0.280155E+10 | 0.345003E+10 |
March | 0.359343E+10 | 0.184849E+10 | 0.174494E+10 | 0.451310E+10 | 0.336311E+10 |
April | 0.496396E+10 | 0.295858E+10 | 0.200537E+10 | 0.813275E+10 | 0.181635E+10 |
May | 0.531593E+10 | 0.315124E+10 | 0.216469E+10 | 0.937909E+10 | 0.133601E+10 |
June | 0.536218E+10 | 0.333198E+10 | 0.203020E+10 | 0.110618E+11 | 0.509035E+09 |
July | 0.467966E+10 | 0.263867E+10 | 0.204099E+10 | 0.977522E+10 | 0.404060E+09 |
August | 0.444140E+10 | 0.253470E+10 | 0.190670E+10 | 0.920089E+10 | 0.515376E+09 |
September | 0.352691E+10 | 0.170003E+10 | 0.182688E+10 | 0.698755E+10 | 0.756655E+09 |
October | 0.366066E+10 | 0.222785E+10 | 0.143281E+10 | 0.567084E+10 | 0.240663E+10 |
November | 0.272404E+10 | 0.163528E+10 | 0.108876E+10 | 0.334692E+10 | 0.340089E+10 |
December | 0.256640E+10 | 0.154967E+10 | 0.101673E+10 | 0.277514E+10 | 0.455078E+10 |
Annual Sum or Average | 0.463412E+11 | 0.268876E+11 | 0.194536E+11 | 0.772571E+11 | 0.262648E+11 |
Minimum of Months | 0.256640E+10 | 0.148361E+10 | 0.101673E+10 | 0.277514E+10 | 0.404060E+09 |
Maximum of Months | 0.536218E+10 | 0.333198E+10 | 0.216469E+10 | 0.110618E+11 | 0.455078E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111376E+11 | 0.889529E+10 | 0.224231E+10 | 0.165550E+11 | 0.629258E+10 |
February | 0.636065E+10 | 0.428984E+10 | 0.207081E+10 | 0.835383E+10 | 0.546159E+10 |
March | 0.585959E+10 | 0.301799E+10 | 0.284159E+10 | 0.833298E+10 | 0.551230E+10 |
April | 0.482714E+10 | 0.195064E+10 | 0.287650E+10 | 0.908136E+10 | 0.304679E+10 |
May | 0.334251E+10 | 0.552221E+09 | 0.279029E+10 | 0.707486E+10 | 0.217803E+10 |
June | 0.276983E+10 | 0.213518E+09 | 0.255631E+10 | 0.804103E+10 | 0.816613E+09 |
July | 0.292462E+10 | 0.302576E+09 | 0.262205E+10 | 0.806256E+10 | 0.633607E+09 |
August | 0.355620E+10 | 0.982758E+09 | 0.257344E+10 | 0.921836E+10 | 0.818682E+09 |
September | 0.495885E+10 | 0.211557E+10 | 0.284328E+10 | 0.105763E+11 | 0.125352E+10 |
October | 0.816479E+10 | 0.565125E+10 | 0.251354E+10 | 0.134773E+11 | 0.395092E+10 |
November | 0.920812E+10 | 0.705295E+10 | 0.215517E+10 | 0.134707E+11 | 0.555387E+10 |
December | 0.103547E+11 | 0.819710E+10 | 0.215755E+10 | 0.146109E+11 | 0.743357E+10 |
Annual Sum or Average | 0.734646E+11 | 0.432217E+11 | 0.302428E+11 | 0.126855E+12 | 0.429520E+11 |
Minimum of Months | 0.276983E+10 | 0.213518E+09 | 0.207081E+10 | 0.707486E+10 | 0.633607E+09 |
Maximum of Months | 0.111376E+11 | 0.889529E+10 | 0.287650E+10 | 0.165550E+11 | 0.743357E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.304615E+10 | 0.189323E+10 | 0.115292E+10 | 0.435146E+10 | 0.427799E+10 |
February | 0.222887E+10 | 0.107752E+10 | 0.115135E+10 | 0.249730E+10 | 0.374698E+10 |
March | 0.326851E+10 | 0.155815E+10 | 0.171036E+10 | 0.427523E+10 | 0.370619E+10 |
April | 0.485700E+10 | 0.277058E+10 | 0.208642E+10 | 0.819259E+10 | 0.218659E+10 |
May | 0.503179E+10 | 0.282133E+10 | 0.221046E+10 | 0.913320E+10 | 0.162231E+10 |
June | 0.517673E+10 | 0.304475E+10 | 0.213198E+10 | 0.108190E+11 | 0.675563E+09 |
July | 0.389334E+10 | 0.181740E+10 | 0.207594E+10 | 0.843022E+10 | 0.517363E+09 |
August | 0.371265E+10 | 0.186457E+10 | 0.184808E+10 | 0.798571E+10 | 0.645842E+09 |
September | 0.313179E+10 | 0.131585E+10 | 0.181594E+10 | 0.638438E+10 | 0.882824E+09 |
October | 0.331129E+10 | 0.189339E+10 | 0.141790E+10 | 0.536145E+10 | 0.272841E+10 |
November | 0.295140E+10 | 0.178197E+10 | 0.116943E+10 | 0.406710E+10 | 0.383437E+10 |
December | 0.245800E+10 | 0.139951E+10 | 0.105849E+10 | 0.309763E+10 | 0.511174E+10 |
Annual Sum or Average | 0.430675E+11 | 0.232382E+11 | 0.198293E+11 | 0.745953E+11 | 0.299362E+11 |
Minimum of Months | 0.222887E+10 | 0.107752E+10 | 0.105849E+10 | 0.249730E+10 | 0.517363E+09 |
Maximum of Months | 0.517673E+10 | 0.304475E+10 | 0.221046E+10 | 0.108190E+11 | 0.511174E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135262E+10 | 0.00 | 0.135262E+10 | 0.120579E+10 | 0.549814E+10 |
February | 0.139212E+10 | 0.00 | 0.139212E+10 | 0.704310E+09 | 0.492464E+10 |
March | 0.204836E+10 | 0.00 | 0.204836E+10 | 0.193481E+10 | 0.500151E+10 |
April | 0.241512E+10 | 25062726.47 | 0.239006E+10 | 0.403780E+10 | 0.274834E+10 |
May | 0.292139E+10 | 0.233918E+09 | 0.268747E+10 | 0.572210E+10 | 0.195686E+10 |
June | 0.328533E+10 | 0.596911E+09 | 0.268842E+10 | 0.875176E+10 | 0.812013E+09 |
July | 0.289516E+10 | 0.301618E+09 | 0.259354E+10 | 0.770354E+10 | 0.654122E+09 |
August | 0.233691E+10 | 58054365.94 | 0.227886E+10 | 0.641916E+10 | 0.805008E+09 |
September | 0.213372E+10 | 569599.25 | 0.213315E+10 | 0.513232E+10 | 0.119381E+10 |
October | 0.170584E+10 | 0.00 | 0.170584E+10 | 0.258536E+10 | 0.359376E+10 |
November | 0.137543E+10 | 0.00 | 0.137543E+10 | 0.112548E+10 | 0.493669E+10 |
December | 0.126347E+10 | 0.00 | 0.126347E+10 | 0.770248E+09 | 0.668173E+10 |
Annual Sum or Average | 0.251255E+11 | 0.121613E+10 | 0.239093E+11 | 0.460927E+11 | 0.388066E+11 |
Minimum of Months | 0.126347E+10 | 0.00 | 0.126347E+10 | 0.704310E+09 | 0.654122E+09 |
Maximum of Months | 0.328533E+10 | 0.596911E+09 | 0.268842E+10 | 0.875176E+10 | 0.668173E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.291307E+10 | 0.182745E+10 | 0.108562E+10 | 0.371395E+10 | 0.350928E+10 |
February | 0.259352E+10 | 0.148361E+10 | 0.110991E+10 | 0.287561E+10 | 0.317500E+10 |
March | 0.359343E+10 | 0.184849E+10 | 0.174494E+10 | 0.456865E+10 | 0.320427E+10 |
April | 0.496396E+10 | 0.295858E+10 | 0.200537E+10 | 0.809244E+10 | 0.180086E+10 |
May | 0.531593E+10 | 0.315124E+10 | 0.216469E+10 | 0.932025E+10 | 0.133744E+10 |
June | 0.536218E+10 | 0.333198E+10 | 0.203020E+10 | 0.109704E+11 | 0.522314E+09 |
July | 0.467966E+10 | 0.263867E+10 | 0.204099E+10 | 0.967534E+10 | 0.422047E+09 |
August | 0.444140E+10 | 0.253470E+10 | 0.190670E+10 | 0.912020E+10 | 0.527743E+09 |
September | 0.352691E+10 | 0.170003E+10 | 0.182688E+10 | 0.692758E+10 | 0.767772E+09 |
October | 0.366066E+10 | 0.222785E+10 | 0.143281E+10 | 0.567997E+10 | 0.230979E+10 |
November | 0.272404E+10 | 0.163528E+10 | 0.108876E+10 | 0.342753E+10 | 0.317060E+10 |
December | 0.256640E+10 | 0.154967E+10 | 0.101673E+10 | 0.292020E+10 | 0.420388E+10 |
Annual Sum or Average | 0.463412E+11 | 0.268876E+11 | 0.194536E+11 | 0.772921E+11 | 0.249510E+11 |
Minimum of Months | 0.256640E+10 | 0.148361E+10 | 0.101673E+10 | 0.287561E+10 | 0.422047E+09 |
Maximum of Months | 0.536218E+10 | 0.333198E+10 | 0.216469E+10 | 0.109704E+11 | 0.420388E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111376E+11 | 0.889529E+10 | 0.224231E+10 | 0.166622E+11 | 0.592672E+10 |
February | 0.636065E+10 | 0.428984E+10 | 0.207081E+10 | 0.844962E+10 | 0.503101E+10 |
March | 0.585959E+10 | 0.301799E+10 | 0.284159E+10 | 0.840025E+10 | 0.523375E+10 |
April | 0.482714E+10 | 0.195064E+10 | 0.287650E+10 | 0.903502E+10 | 0.298638E+10 |
May | 0.334251E+10 | 0.552221E+09 | 0.279029E+10 | 0.701959E+10 | 0.215615E+10 |
June | 0.276983E+10 | 0.213518E+09 | 0.255631E+10 | 0.793875E+10 | 0.827631E+09 |
July | 0.292462E+10 | 0.302576E+09 | 0.262205E+10 | 0.794245E+10 | 0.654730E+09 |
August | 0.355620E+10 | 0.982758E+09 | 0.257344E+10 | 0.911997E+10 | 0.830970E+09 |
September | 0.495885E+10 | 0.211557E+10 | 0.284328E+10 | 0.104956E+11 | 0.126761E+10 |
October | 0.816479E+10 | 0.565125E+10 | 0.251354E+10 | 0.134824E+11 | 0.379015E+10 |
November | 0.920812E+10 | 0.705295E+10 | 0.215517E+10 | 0.135615E+11 | 0.521960E+10 |
December | 0.103547E+11 | 0.819710E+10 | 0.215755E+10 | 0.147665E+11 | 0.693238E+10 |
Annual Sum or Average | 0.734646E+11 | 0.432217E+11 | 0.302428E+11 | 0.126874E+12 | 0.408571E+11 |
Minimum of Months | 0.276983E+10 | 0.213518E+09 | 0.207081E+10 | 0.701959E+10 | 0.654730E+09 |
Maximum of Months | 0.111376E+11 | 0.889529E+10 | 0.287650E+10 | 0.166622E+11 | 0.693238E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.304615E+10 | 0.189323E+10 | 0.115292E+10 | 0.439945E+10 | 0.401702E+10 |
February | 0.222887E+10 | 0.107752E+10 | 0.115135E+10 | 0.253324E+10 | 0.347487E+10 |
March | 0.326851E+10 | 0.155815E+10 | 0.171036E+10 | 0.430988E+10 | 0.352831E+10 |
April | 0.485700E+10 | 0.277058E+10 | 0.208642E+10 | 0.815623E+10 | 0.214619E+10 |
May | 0.503179E+10 | 0.282133E+10 | 0.221046E+10 | 0.908234E+10 | 0.160710E+10 |
June | 0.517673E+10 | 0.304475E+10 | 0.213198E+10 | 0.107391E+11 | 0.680662E+09 |
July | 0.389334E+10 | 0.181740E+10 | 0.207594E+10 | 0.835218E+10 | 0.529076E+09 |
August | 0.371265E+10 | 0.186457E+10 | 0.184808E+10 | 0.792279E+10 | 0.651522E+09 |
September | 0.313179E+10 | 0.131585E+10 | 0.181594E+10 | 0.633607E+10 | 0.886383E+09 |
October | 0.331129E+10 | 0.189339E+10 | 0.141790E+10 | 0.536390E+10 | 0.261156E+10 |
November | 0.295140E+10 | 0.178197E+10 | 0.116943E+10 | 0.410563E+10 | 0.359668E+10 |
December | 0.245800E+10 | 0.139951E+10 | 0.105849E+10 | 0.315962E+10 | 0.477293E+10 |
Annual Sum or Average | 0.430675E+11 | 0.232382E+11 | 0.198293E+11 | 0.744604E+11 | 0.285023E+11 |
Minimum of Months | 0.222887E+10 | 0.107752E+10 | 0.105849E+10 | 0.253324E+10 | 0.529076E+09 |
Maximum of Months | 0.517673E+10 | 0.304475E+10 | 0.221046E+10 | 0.107391E+11 | 0.477293E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 309.45 | 2536.65 | 505.01 | 0.00 | 505.01 | 0.00 | 0.00 |
February | 192.15 | 2571.42 | 575.45 | 0.00 | 575.45 | 0.00 | 0.00 |
March | 615.71 | 2209.69 | 764.77 | 0.00 | 764.77 | 0.00 | 0.00 |
April | 1495.63 | 1163.20 | 931.76 | 9.67 | 922.09 | 0.00 | 0.00 |
May | 2081.22 | 799.50 | 1090.73 | 87.34 | 1003.39 | 0.00 | 0.00 |
June | 3289.92 | 362.47 | 1267.49 | 230.29 | 1037.20 | 0.00 | 0.00 |
July | 2771.19 | 298.17 | 1080.93 | 112.61 | 968.32 | 0.00 | 0.00 |
August | 2281.56 | 393.90 | 872.51 | 21.68 | 850.83 | 0.00 | 0.00 |
September | 1914.89 | 538.91 | 823.20 | 0.22 | 822.98 | 0.00 | 0.00 |
October | 868.91 | 1599.62 | 636.89 | 0.00 | 636.89 | 0.00 | 0.00 |
November | 316.62 | 2377.79 | 530.65 | 0.00 | 530.65 | 0.00 | 0.00 |
December | 143.20 | 3172.73 | 471.73 | 0.00 | 471.73 | 0.00 | 0.00 |
Annual Sum or Average | 1361.92 | 1497.51 | 796.73 | 38.56 | 758.16 | 0.00 | 0.00 |
Minimum of Months | 143.20 | 298.17 | 471.73 | 0.00 | 471.73 | 0.00 | 0.00 |
Maximum of Months | 3289.92 | 3172.73 | 1267.49 | 230.29 | 1037.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1316.81 | 1529.19 | 1087.62 | 682.30 | 405.33 | 0.00 | 0.00 |
February | 1144.18 | 1551.20 | 1072.06 | 613.27 | 458.79 | 0.00 | 0.00 |
March | 1681.92 | 1321.92 | 1341.64 | 690.15 | 651.49 | 0.00 | 0.00 |
April | 3155.32 | 694.58 | 1915.11 | 1141.43 | 773.68 | 0.00 | 0.00 |
May | 3500.19 | 530.19 | 1984.75 | 1176.54 | 808.21 | 0.00 | 0.00 |
June | 4228.72 | 226.20 | 2068.75 | 1285.49 | 783.26 | 0.00 | 0.00 |
July | 3594.63 | 180.57 | 1747.19 | 985.17 | 762.02 | 0.00 | 0.00 |
August | 3387.17 | 236.74 | 1658.24 | 946.35 | 711.88 | 0.00 | 0.00 |
September | 2666.52 | 333.96 | 1360.70 | 655.88 | 704.82 | 0.00 | 0.00 |
October | 2104.96 | 963.36 | 1366.74 | 831.79 | 534.95 | 0.00 | 0.00 |
November | 1270.28 | 1422.30 | 1050.95 | 630.90 | 420.05 | 0.00 | 0.00 |
December | 989.30 | 1861.08 | 958.19 | 578.58 | 379.61 | 0.00 | 0.00 |
Annual Sum or Average | 2425.99 | 901.53 | 1469.47 | 852.60 | 616.87 | 0.00 | 0.00 |
Minimum of Months | 989.30 | 180.57 | 958.19 | 578.58 | 379.61 | 0.00 | 0.00 |
Maximum of Months | 4228.72 | 1861.08 | 2068.75 | 1285.49 | 808.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6234.58 | 2391.63 | 4158.32 | 3321.13 | 837.19 | 0.00 | 0.00 |
February | 3479.12 | 2348.08 | 2629.25 | 1773.26 | 855.99 | 0.00 | 0.00 |
March | 3122.72 | 2133.90 | 2187.73 | 1126.79 | 1060.93 | 0.00 | 0.00 |
April | 3493.80 | 1211.75 | 1862.33 | 752.56 | 1109.77 | 0.00 | 0.00 |
May | 2591.33 | 870.72 | 1247.95 | 206.18 | 1041.78 | 0.00 | 0.00 |
June | 2977.48 | 368.84 | 1068.61 | 82.38 | 986.23 | 0.00 | 0.00 |
July | 2878.06 | 291.88 | 1091.93 | 112.97 | 978.96 | 0.00 | 0.00 |
August | 3332.28 | 386.52 | 1327.74 | 366.92 | 960.82 | 0.00 | 0.00 |
September | 4044.42 | 539.48 | 1913.14 | 816.19 | 1096.95 | 0.00 | 0.00 |
October | 5055.36 | 1532.02 | 3048.39 | 2109.94 | 938.45 | 0.00 | 0.00 |
November | 5234.55 | 2216.18 | 3552.53 | 2721.06 | 831.47 | 0.00 | 0.00 |
December | 5474.13 | 2873.57 | 3866.00 | 3060.46 | 805.54 | 0.00 | 0.00 |
Annual Sum or Average | 3997.99 | 1426.63 | 2329.55 | 1370.56 | 959.00 | 0.00 | 0.00 |
Minimum of Months | 2591.33 | 291.88 | 1068.61 | 82.38 | 805.54 | 0.00 | 0.00 |
Maximum of Months | 6234.58 | 2873.57 | 4158.32 | 3321.13 | 1109.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1573.14 | 1795.52 | 1137.31 | 706.85 | 430.45 | 0.00 | 0.00 |
February | 981.01 | 1842.84 | 921.33 | 445.41 | 475.92 | 0.00 | 0.00 |
March | 1524.10 | 1622.45 | 1220.33 | 581.75 | 638.58 | 0.00 | 0.00 |
April | 3105.00 | 959.18 | 1873.85 | 1068.90 | 804.95 | 0.00 | 0.00 |
May | 3391.78 | 649.94 | 1878.66 | 1053.37 | 825.29 | 0.00 | 0.00 |
June | 4121.81 | 290.84 | 1997.20 | 1174.68 | 822.53 | 0.00 | 0.00 |
July | 3061.22 | 238.23 | 1453.61 | 678.54 | 775.07 | 0.00 | 0.00 |
August | 2886.34 | 322.42 | 1386.15 | 696.15 | 690.00 | 0.00 | 0.00 |
September | 2432.98 | 373.64 | 1208.26 | 507.66 | 700.60 | 0.00 | 0.00 |
October | 1953.18 | 1164.55 | 1236.30 | 706.91 | 529.39 | 0.00 | 0.00 |
November | 1506.86 | 1767.01 | 1138.66 | 687.49 | 451.17 | 0.00 | 0.00 |
December | 1069.61 | 2335.78 | 917.71 | 522.52 | 395.20 | 0.00 | 0.00 |
Annual Sum or Average | 2306.05 | 1110.45 | 1365.67 | 736.88 | 628.78 | 0.00 | 0.00 |
Minimum of Months | 981.01 | 238.23 | 917.71 | 445.41 | 395.20 | 0.00 | 0.00 |
Maximum of Months | 4121.81 | 2335.78 | 1997.20 | 1174.68 | 825.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 397.67 | 2236.16 | 505.01 | 0.00 | 505.01 | 0.00 | 0.00 |
February | 251.26 | 2252.80 | 575.45 | 0.00 | 575.45 | 0.00 | 0.00 |
March | 684.22 | 1993.19 | 764.77 | 0.00 | 764.77 | 0.00 | 0.00 |
April | 1566.73 | 1085.57 | 931.76 | 9.67 | 922.09 | 0.00 | 0.00 |
May | 2154.45 | 733.08 | 1090.72 | 87.33 | 1003.39 | 0.00 | 0.00 |
June | 3416.60 | 306.12 | 1267.49 | 230.29 | 1037.20 | 0.00 | 0.00 |
July | 2921.47 | 234.50 | 1080.93 | 112.61 | 968.32 | 0.00 | 0.00 |
August | 2431.16 | 294.29 | 872.50 | 21.68 | 850.83 | 0.00 | 0.00 |
September | 2006.31 | 456.01 | 823.19 | 0.22 | 822.97 | 0.00 | 0.00 |
October | 948.19 | 1424.12 | 636.89 | 0.00 | 636.89 | 0.00 | 0.00 |
November | 390.90 | 2080.33 | 530.64 | 0.00 | 530.64 | 0.00 | 0.00 |
December | 233.71 | 2732.49 | 471.73 | 0.00 | 471.73 | 0.00 | 0.00 |
Annual Sum or Average | 1455.75 | 1315.07 | 796.72 | 38.56 | 758.16 | 0.00 | 0.00 |
Minimum of Months | 233.71 | 234.50 | 471.73 | 0.00 | 471.73 | 0.00 | 0.00 |
Maximum of Months | 3416.60 | 2732.49 | 1267.49 | 230.29 | 1037.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1348.64 | 1402.29 | 1087.62 | 682.29 | 405.32 | 0.00 | 0.00 |
February | 1158.05 | 1426.10 | 1072.06 | 613.27 | 458.79 | 0.00 | 0.00 |
March | 1685.00 | 1255.64 | 1341.63 | 690.15 | 651.49 | 0.00 | 0.00 |
April | 3137.63 | 700.75 | 1915.11 | 1141.43 | 773.68 | 0.00 | 0.00 |
May | 3501.75 | 498.81 | 1984.74 | 1176.54 | 808.20 | 0.00 | 0.00 |
June | 4267.68 | 196.39 | 2068.74 | 1285.49 | 783.26 | 0.00 | 0.00 |
July | 3649.65 | 150.86 | 1747.18 | 985.17 | 762.02 | 0.00 | 0.00 |
August | 3435.22 | 192.42 | 1658.23 | 946.35 | 711.88 | 0.00 | 0.00 |
September | 2695.81 | 291.92 | 1360.69 | 655.88 | 704.81 | 0.00 | 0.00 |
October | 2117.25 | 898.53 | 1366.73 | 831.78 | 534.95 | 0.00 | 0.00 |
November | 1291.25 | 1312.07 | 1050.94 | 630.89 | 420.05 | 0.00 | 0.00 |
December | 1036.12 | 1699.07 | 958.18 | 578.58 | 379.60 | 0.00 | 0.00 |
Annual Sum or Average | 2449.81 | 832.85 | 1469.47 | 852.60 | 616.87 | 0.00 | 0.00 |
Minimum of Months | 1036.12 | 150.86 | 958.18 | 578.58 | 379.60 | 0.00 | 0.00 |
Maximum of Months | 4267.68 | 1699.07 | 2068.74 | 1285.49 | 808.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6180.92 | 2349.38 | 4158.30 | 3321.12 | 837.18 | 0.00 | 0.00 |
February | 3453.14 | 2257.60 | 2629.24 | 1773.25 | 855.99 | 0.00 | 0.00 |
March | 3111.18 | 2058.06 | 2187.72 | 1126.79 | 1060.93 | 0.00 | 0.00 |
April | 3503.61 | 1175.46 | 1862.32 | 752.56 | 1109.76 | 0.00 | 0.00 |
May | 2641.45 | 813.18 | 1247.95 | 206.18 | 1041.77 | 0.00 | 0.00 |
June | 3102.25 | 315.05 | 1068.61 | 82.38 | 986.23 | 0.00 | 0.00 |
July | 3010.21 | 236.56 | 1091.93 | 112.97 | 978.96 | 0.00 | 0.00 |
August | 3441.74 | 305.66 | 1327.73 | 366.92 | 960.81 | 0.00 | 0.00 |
September | 4080.37 | 483.61 | 1913.14 | 816.19 | 1096.95 | 0.00 | 0.00 |
October | 5031.86 | 1475.10 | 3048.38 | 2109.94 | 938.45 | 0.00 | 0.00 |
November | 5197.04 | 2142.70 | 3552.52 | 2721.05 | 831.47 | 0.00 | 0.00 |
December | 5455.09 | 2775.38 | 3865.99 | 3060.45 | 805.54 | 0.00 | 0.00 |
Annual Sum or Average | 4022.55 | 1362.00 | 2329.55 | 1370.55 | 958.99 | 0.00 | 0.00 |
Minimum of Months | 2641.45 | 236.56 | 1068.61 | 82.38 | 805.54 | 0.00 | 0.00 |
Maximum of Months | 6180.92 | 2775.38 | 4158.30 | 3321.12 | 1109.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1624.65 | 1597.22 | 1137.30 | 706.85 | 430.45 | 0.00 | 0.00 |
February | 1032.28 | 1548.85 | 921.32 | 445.40 | 475.92 | 0.00 | 0.00 |
March | 1596.19 | 1383.73 | 1220.32 | 581.75 | 638.58 | 0.00 | 0.00 |
April | 3160.72 | 843.59 | 1873.84 | 1068.90 | 804.95 | 0.00 | 0.00 |
May | 3409.95 | 605.70 | 1878.65 | 1053.36 | 825.29 | 0.00 | 0.00 |
June | 4174.01 | 260.63 | 1997.20 | 1174.67 | 822.52 | 0.00 | 0.00 |
July | 3147.48 | 193.16 | 1453.61 | 678.54 | 775.07 | 0.00 | 0.00 |
August | 2981.52 | 241.13 | 1386.14 | 696.15 | 689.99 | 0.00 | 0.00 |
September | 2463.11 | 340.60 | 1208.25 | 507.66 | 700.59 | 0.00 | 0.00 |
October | 2001.74 | 1018.67 | 1236.29 | 706.91 | 529.38 | 0.00 | 0.00 |
November | 1569.10 | 1479.31 | 1138.66 | 687.49 | 451.17 | 0.00 | 0.00 |
December | 1156.52 | 1908.51 | 917.71 | 522.52 | 395.19 | 0.00 | 0.00 |
Annual Sum or Average | 2365.40 | 949.27 | 1365.66 | 736.88 | 628.78 | 0.00 | 0.00 |
Minimum of Months | 1032.28 | 193.16 | 917.71 | 445.40 | 395.19 | 0.00 | 0.00 |
Maximum of Months | 4174.01 | 1908.51 | 1997.20 | 1174.67 | 825.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 450.19 | 2052.77 | 505.01 | 0.00 | 505.01 | 0.00 | 0.00 |
February | 291.13 | 2035.65 | 575.45 | 0.00 | 575.45 | 0.00 | 0.00 |
March | 722.38 | 1867.35 | 764.77 | 0.00 | 764.77 | 0.00 | 0.00 |
April | 1557.79 | 1060.32 | 931.76 | 9.67 | 922.09 | 0.00 | 0.00 |
May | 2136.39 | 730.61 | 1090.72 | 87.33 | 1003.39 | 0.00 | 0.00 |
June | 3376.45 | 313.28 | 1267.49 | 230.29 | 1037.20 | 0.00 | 0.00 |
July | 2876.17 | 244.22 | 1080.93 | 112.61 | 968.32 | 0.00 | 0.00 |
August | 2396.64 | 300.56 | 872.50 | 21.68 | 850.83 | 0.00 | 0.00 |
September | 1980.06 | 460.58 | 823.19 | 0.22 | 822.97 | 0.00 | 0.00 |
October | 965.26 | 1341.76 | 636.89 | 0.00 | 636.89 | 0.00 | 0.00 |
November | 434.21 | 1904.59 | 530.64 | 0.00 | 530.64 | 0.00 | 0.00 |
December | 287.58 | 2494.67 | 471.73 | 0.00 | 471.73 | 0.00 | 0.00 |
Annual Sum or Average | 1461.59 | 1230.55 | 796.72 | 38.56 | 758.16 | 0.00 | 0.00 |
Minimum of Months | 287.58 | 244.22 | 471.73 | 0.00 | 471.73 | 0.00 | 0.00 |
Maximum of Months | 3376.45 | 2494.67 | 1267.49 | 230.29 | 1037.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1386.63 | 1310.22 | 1087.62 | 682.29 | 405.32 | 0.00 | 0.00 |
February | 1188.66 | 1312.42 | 1072.06 | 613.27 | 458.79 | 0.00 | 0.00 |
March | 1705.74 | 1196.34 | 1341.63 | 690.15 | 651.49 | 0.00 | 0.00 |
April | 3122.08 | 694.78 | 1915.11 | 1141.43 | 773.68 | 0.00 | 0.00 |
May | 3479.78 | 499.34 | 1984.74 | 1176.54 | 808.20 | 0.00 | 0.00 |
June | 4232.40 | 201.51 | 2068.74 | 1285.49 | 783.26 | 0.00 | 0.00 |
July | 3612.36 | 157.57 | 1747.18 | 985.17 | 762.02 | 0.00 | 0.00 |
August | 3405.09 | 197.04 | 1658.23 | 946.35 | 711.88 | 0.00 | 0.00 |
September | 2672.68 | 296.21 | 1360.69 | 655.88 | 704.81 | 0.00 | 0.00 |
October | 2120.66 | 862.38 | 1366.73 | 831.78 | 534.95 | 0.00 | 0.00 |
November | 1322.35 | 1223.23 | 1050.94 | 630.89 | 420.05 | 0.00 | 0.00 |
December | 1090.28 | 1569.55 | 958.18 | 578.58 | 379.60 | 0.00 | 0.00 |
Annual Sum or Average | 2450.92 | 791.19 | 1469.47 | 852.60 | 616.87 | 0.00 | 0.00 |
Minimum of Months | 1090.28 | 157.57 | 958.18 | 578.58 | 379.60 | 0.00 | 0.00 |
Maximum of Months | 4232.40 | 1569.55 | 2068.74 | 1285.49 | 808.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 6220.94 | 2212.78 | 4158.30 | 3321.12 | 837.18 | 0.00 | 0.00 |
February | 3492.73 | 2079.62 | 2629.24 | 1773.25 | 855.99 | 0.00 | 0.00 |
March | 3136.29 | 1954.06 | 2187.72 | 1126.79 | 1060.93 | 0.00 | 0.00 |
April | 3485.73 | 1152.15 | 1862.32 | 752.56 | 1109.76 | 0.00 | 0.00 |
May | 2620.81 | 805.01 | 1247.95 | 206.18 | 1041.77 | 0.00 | 0.00 |
June | 3062.79 | 319.30 | 1068.61 | 82.38 | 986.23 | 0.00 | 0.00 |
July | 2965.37 | 244.45 | 1091.93 | 112.97 | 978.96 | 0.00 | 0.00 |
August | 3405.01 | 310.25 | 1327.73 | 366.92 | 960.81 | 0.00 | 0.00 |
September | 4049.24 | 489.05 | 1913.14 | 816.19 | 1096.95 | 0.00 | 0.00 |
October | 5033.75 | 1415.08 | 3048.38 | 2109.94 | 938.45 | 0.00 | 0.00 |
November | 5232.04 | 2013.73 | 3552.52 | 2721.05 | 831.47 | 0.00 | 0.00 |
December | 5513.18 | 2588.26 | 3865.99 | 3060.45 | 805.54 | 0.00 | 0.00 |
Annual Sum or Average | 4023.14 | 1295.57 | 2329.55 | 1370.55 | 958.99 | 0.00 | 0.00 |
Minimum of Months | 2620.81 | 244.45 | 1068.61 | 82.38 | 805.54 | 0.00 | 0.00 |
Maximum of Months | 6220.94 | 2588.26 | 4158.30 | 3321.12 | 1109.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1642.56 | 1499.78 | 1137.30 | 706.85 | 430.45 | 0.00 | 0.00 |
February | 1047.14 | 1436.37 | 921.32 | 445.40 | 475.92 | 0.00 | 0.00 |
March | 1609.12 | 1317.32 | 1220.32 | 581.75 | 638.58 | 0.00 | 0.00 |
April | 3146.70 | 828.01 | 1873.84 | 1068.90 | 804.95 | 0.00 | 0.00 |
May | 3390.96 | 600.02 | 1878.65 | 1053.36 | 825.29 | 0.00 | 0.00 |
June | 4143.18 | 262.60 | 1997.20 | 1174.67 | 822.52 | 0.00 | 0.00 |
July | 3118.35 | 197.53 | 1453.61 | 678.54 | 775.07 | 0.00 | 0.00 |
August | 2958.03 | 243.25 | 1386.14 | 696.15 | 689.99 | 0.00 | 0.00 |
September | 2444.47 | 341.97 | 1208.25 | 507.66 | 700.59 | 0.00 | 0.00 |
October | 2002.65 | 975.04 | 1236.29 | 706.91 | 529.38 | 0.00 | 0.00 |
November | 1583.96 | 1387.61 | 1138.66 | 687.49 | 451.17 | 0.00 | 0.00 |
December | 1179.67 | 1782.01 | 917.71 | 522.52 | 395.19 | 0.00 | 0.00 |
Annual Sum or Average | 2361.12 | 903.80 | 1365.66 | 736.88 | 628.78 | 0.00 | 0.00 |
Minimum of Months | 1047.14 | 197.53 | 917.71 | 445.40 | 395.19 | 0.00 | 0.00 |
Maximum of Months | 4143.18 | 1782.01 | 1997.20 | 1174.67 | 825.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.828842E+09 | 0.679417E+10 | 0.135263E+10 | 0.00 | 0.135263E+10 | 0.00 | 0.00 |
February | 0.464837E+09 | 0.622078E+10 | 0.139213E+10 | 0.00 | 0.139213E+10 | 0.00 | 0.00 |
March | 0.164912E+10 | 0.591844E+10 | 0.204837E+10 | 0.00 | 0.204837E+10 | 0.00 | 0.00 |
April | 0.387666E+10 | 0.301501E+10 | 0.241513E+10 | 25062815.47 | 0.239006E+10 | 0.00 | 0.00 |
May | 0.557434E+10 | 0.214138E+10 | 0.292140E+10 | 0.233919E+09 | 0.268748E+10 | 0.00 | 0.00 |
June | 0.852747E+10 | 0.939513E+09 | 0.328534E+10 | 0.596913E+09 | 0.268843E+10 | 0.00 | 0.00 |
July | 0.742235E+10 | 0.798626E+09 | 0.289517E+10 | 0.301619E+09 | 0.259355E+10 | 0.00 | 0.00 |
August | 0.611093E+10 | 0.105502E+10 | 0.233692E+10 | 58054572.09 | 0.227887E+10 | 0.00 | 0.00 |
September | 0.496340E+10 | 0.139686E+10 | 0.213373E+10 | 569601.27 | 0.213316E+10 | 0.00 | 0.00 |
October | 0.232728E+10 | 0.428442E+10 | 0.170584E+10 | 0.00 | 0.170584E+10 | 0.00 | 0.00 |
November | 0.820687E+09 | 0.616324E+10 | 0.137543E+10 | 0.00 | 0.137543E+10 | 0.00 | 0.00 |
December | 0.383554E+09 | 0.849785E+10 | 0.126348E+10 | 0.00 | 0.126348E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.429495E+11 | 0.472253E+11 | 0.251256E+11 | 0.121614E+10 | 0.239094E+11 | 0.00 | 0.00 |
Minimum of Months | 0.383554E+09 | 0.798626E+09 | 0.126348E+10 | 0.00 | 0.126348E+10 | 0.00 | 0.00 |
Maximum of Months | 0.852747E+10 | 0.849785E+10 | 0.328534E+10 | 0.596913E+09 | 0.268843E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.352694E+10 | 0.409578E+10 | 0.291309E+10 | 0.182746E+10 | 0.108563E+10 | 0.00 | 0.00 |
February | 0.276801E+10 | 0.375265E+10 | 0.259353E+10 | 0.148362E+10 | 0.110991E+10 | 0.00 | 0.00 |
March | 0.450486E+10 | 0.354063E+10 | 0.359344E+10 | 0.184849E+10 | 0.174495E+10 | 0.00 | 0.00 |
April | 0.817858E+10 | 0.180036E+10 | 0.496398E+10 | 0.295859E+10 | 0.200538E+10 | 0.00 | 0.00 |
May | 0.937490E+10 | 0.142007E+10 | 0.531595E+10 | 0.315125E+10 | 0.216470E+10 | 0.00 | 0.00 |
June | 0.109608E+11 | 0.586321E+09 | 0.536220E+10 | 0.333200E+10 | 0.203021E+10 | 0.00 | 0.00 |
July | 0.962785E+10 | 0.483636E+09 | 0.467968E+10 | 0.263868E+10 | 0.204100E+10 | 0.00 | 0.00 |
August | 0.907221E+10 | 0.634078E+09 | 0.444142E+10 | 0.253472E+10 | 0.190671E+10 | 0.00 | 0.00 |
September | 0.691163E+10 | 0.865616E+09 | 0.352693E+10 | 0.170004E+10 | 0.182688E+10 | 0.00 | 0.00 |
October | 0.563792E+10 | 0.258027E+10 | 0.366067E+10 | 0.222786E+10 | 0.143281E+10 | 0.00 | 0.00 |
November | 0.329257E+10 | 0.368661E+10 | 0.272405E+10 | 0.163528E+10 | 0.108877E+10 | 0.00 | 0.00 |
December | 0.264975E+10 | 0.498471E+10 | 0.256641E+10 | 0.154967E+10 | 0.101674E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.765061E+11 | 0.284307E+11 | 0.463414E+11 | 0.268877E+11 | 0.194537E+11 | 0.00 | 0.00 |
Minimum of Months | 0.264975E+10 | 0.483636E+09 | 0.256641E+10 | 0.148362E+10 | 0.101674E+10 | 0.00 | 0.00 |
Maximum of Months | 0.109608E+11 | 0.498471E+10 | 0.536220E+10 | 0.333200E+10 | 0.216470E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.166987E+11 | 0.640574E+10 | 0.111376E+11 | 0.889532E+10 | 0.224232E+10 | 0.00 | 0.00 |
February | 0.841670E+10 | 0.568047E+10 | 0.636067E+10 | 0.428986E+10 | 0.207081E+10 | 0.00 | 0.00 |
March | 0.836390E+10 | 0.571544E+10 | 0.585961E+10 | 0.301801E+10 | 0.284160E+10 | 0.00 | 0.00 |
April | 0.905593E+10 | 0.314086E+10 | 0.482716E+10 | 0.195064E+10 | 0.287651E+10 | 0.00 | 0.00 |
May | 0.694061E+10 | 0.233214E+10 | 0.334252E+10 | 0.552223E+09 | 0.279030E+10 | 0.00 | 0.00 |
June | 0.771762E+10 | 0.956045E+09 | 0.276984E+10 | 0.213519E+09 | 0.255632E+10 | 0.00 | 0.00 |
July | 0.770859E+10 | 0.781769E+09 | 0.292463E+10 | 0.302578E+09 | 0.262206E+10 | 0.00 | 0.00 |
August | 0.892518E+10 | 0.103526E+10 | 0.355621E+10 | 0.982762E+09 | 0.257345E+10 | 0.00 | 0.00 |
September | 0.104831E+11 | 0.139834E+10 | 0.495887E+10 | 0.211558E+10 | 0.284329E+10 | 0.00 | 0.00 |
October | 0.135403E+11 | 0.410336E+10 | 0.816482E+10 | 0.565127E+10 | 0.251354E+10 | 0.00 | 0.00 |
November | 0.135680E+11 | 0.574434E+10 | 0.920816E+10 | 0.705297E+10 | 0.215518E+10 | 0.00 | 0.00 |
December | 0.146619E+11 | 0.769657E+10 | 0.103547E+11 | 0.819713E+10 | 0.215756E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.126081E+12 | 0.449903E+11 | 0.734648E+11 | 0.432219E+11 | 0.302430E+11 | 0.00 | 0.00 |
Minimum of Months | 0.694061E+10 | 0.781769E+09 | 0.276984E+10 | 0.213519E+09 | 0.207081E+10 | 0.00 | 0.00 |
Maximum of Months | 0.166987E+11 | 0.769657E+10 | 0.111376E+11 | 0.889532E+10 | 0.287651E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.421351E+10 | 0.480913E+10 | 0.304616E+10 | 0.189324E+10 | 0.115292E+10 | 0.00 | 0.00 |
February | 0.237327E+10 | 0.445820E+10 | 0.222888E+10 | 0.107753E+10 | 0.115135E+10 | 0.00 | 0.00 |
March | 0.408215E+10 | 0.434557E+10 | 0.326853E+10 | 0.155816E+10 | 0.171037E+10 | 0.00 | 0.00 |
April | 0.804815E+10 | 0.248618E+10 | 0.485702E+10 | 0.277059E+10 | 0.208643E+10 | 0.00 | 0.00 |
May | 0.908455E+10 | 0.174081E+10 | 0.503181E+10 | 0.282134E+10 | 0.221047E+10 | 0.00 | 0.00 |
June | 0.106837E+11 | 0.753870E+09 | 0.517675E+10 | 0.304477E+10 | 0.213199E+10 | 0.00 | 0.00 |
July | 0.819918E+10 | 0.638067E+09 | 0.389335E+10 | 0.181740E+10 | 0.207595E+10 | 0.00 | 0.00 |
August | 0.773078E+10 | 0.863574E+09 | 0.371266E+10 | 0.186457E+10 | 0.184809E+10 | 0.00 | 0.00 |
September | 0.630628E+10 | 0.968469E+09 | 0.313180E+10 | 0.131586E+10 | 0.181595E+10 | 0.00 | 0.00 |
October | 0.523140E+10 | 0.311913E+10 | 0.331130E+10 | 0.189340E+10 | 0.141791E+10 | 0.00 | 0.00 |
November | 0.390579E+10 | 0.458009E+10 | 0.295141E+10 | 0.178198E+10 | 0.116944E+10 | 0.00 | 0.00 |
December | 0.286483E+10 | 0.625615E+10 | 0.245801E+10 | 0.139951E+10 | 0.105849E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.727236E+11 | 0.350192E+11 | 0.430677E+11 | 0.232383E+11 | 0.198293E+11 | 0.00 | 0.00 |
Minimum of Months | 0.237327E+10 | 0.638067E+09 | 0.222888E+10 | 0.107753E+10 | 0.105849E+10 | 0.00 | 0.00 |
Maximum of Months | 0.106837E+11 | 0.625615E+10 | 0.517675E+10 | 0.304477E+10 | 0.221047E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.106511E+10 | 0.598932E+10 | 0.135262E+10 | 0.00 | 0.135262E+10 | 0.00 | 0.00 |
February | 0.607840E+09 | 0.544998E+10 | 0.139212E+10 | 0.00 | 0.139212E+10 | 0.00 | 0.00 |
March | 0.183262E+10 | 0.533857E+10 | 0.204836E+10 | 0.00 | 0.204836E+10 | 0.00 | 0.00 |
April | 0.406096E+10 | 0.281381E+10 | 0.241512E+10 | 25062726.47 | 0.239006E+10 | 0.00 | 0.00 |
May | 0.577049E+10 | 0.196347E+10 | 0.292139E+10 | 0.233918E+09 | 0.268747E+10 | 0.00 | 0.00 |
June | 0.885582E+10 | 0.793459E+09 | 0.328533E+10 | 0.596911E+09 | 0.268842E+10 | 0.00 | 0.00 |
July | 0.782488E+10 | 0.628078E+09 | 0.289516E+10 | 0.301618E+09 | 0.259354E+10 | 0.00 | 0.00 |
August | 0.651161E+10 | 0.788229E+09 | 0.233691E+10 | 58054365.94 | 0.227886E+10 | 0.00 | 0.00 |
September | 0.520035E+10 | 0.118198E+10 | 0.213372E+10 | 569599.25 | 0.213315E+10 | 0.00 | 0.00 |
October | 0.253963E+10 | 0.381438E+10 | 0.170584E+10 | 0.00 | 0.170584E+10 | 0.00 | 0.00 |
November | 0.101320E+10 | 0.539223E+10 | 0.137543E+10 | 0.00 | 0.137543E+10 | 0.00 | 0.00 |
December | 0.625976E+09 | 0.731870E+10 | 0.126347E+10 | 0.00 | 0.126347E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.459085E+11 | 0.414722E+11 | 0.251255E+11 | 0.121613E+10 | 0.239093E+11 | 0.00 | 0.00 |
Minimum of Months | 0.607840E+09 | 0.628078E+09 | 0.126347E+10 | 0.00 | 0.126347E+10 | 0.00 | 0.00 |
Maximum of Months | 0.885582E+10 | 0.731870E+10 | 0.328533E+10 | 0.596911E+09 | 0.268842E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.361218E+10 | 0.375590E+10 | 0.291307E+10 | 0.182745E+10 | 0.108562E+10 | 0.00 | 0.00 |
February | 0.280155E+10 | 0.345003E+10 | 0.259352E+10 | 0.148361E+10 | 0.110991E+10 | 0.00 | 0.00 |
March | 0.451310E+10 | 0.336311E+10 | 0.359343E+10 | 0.184849E+10 | 0.174494E+10 | 0.00 | 0.00 |
April | 0.813275E+10 | 0.181635E+10 | 0.496396E+10 | 0.295858E+10 | 0.200537E+10 | 0.00 | 0.00 |
May | 0.937909E+10 | 0.133601E+10 | 0.531593E+10 | 0.315124E+10 | 0.216469E+10 | 0.00 | 0.00 |
June | 0.110618E+11 | 0.509035E+09 | 0.536218E+10 | 0.333198E+10 | 0.203020E+10 | 0.00 | 0.00 |
July | 0.977522E+10 | 0.404060E+09 | 0.467966E+10 | 0.263867E+10 | 0.204099E+10 | 0.00 | 0.00 |
August | 0.920089E+10 | 0.515376E+09 | 0.444140E+10 | 0.253470E+10 | 0.190670E+10 | 0.00 | 0.00 |
September | 0.698755E+10 | 0.756655E+09 | 0.352691E+10 | 0.170003E+10 | 0.182688E+10 | 0.00 | 0.00 |
October | 0.567084E+10 | 0.240663E+10 | 0.366066E+10 | 0.222785E+10 | 0.143281E+10 | 0.00 | 0.00 |
November | 0.334692E+10 | 0.340089E+10 | 0.272404E+10 | 0.163528E+10 | 0.108876E+10 | 0.00 | 0.00 |
December | 0.277514E+10 | 0.455078E+10 | 0.256640E+10 | 0.154967E+10 | 0.101673E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.772571E+11 | 0.262648E+11 | 0.463412E+11 | 0.268876E+11 | 0.194536E+11 | 0.00 | 0.00 |
Minimum of Months | 0.277514E+10 | 0.404060E+09 | 0.256640E+10 | 0.148361E+10 | 0.101673E+10 | 0.00 | 0.00 |
Maximum of Months | 0.110618E+11 | 0.455078E+10 | 0.536218E+10 | 0.333198E+10 | 0.216469E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.165550E+11 | 0.629258E+10 | 0.111376E+11 | 0.889529E+10 | 0.224231E+10 | 0.00 | 0.00 |
February | 0.835383E+10 | 0.546159E+10 | 0.636065E+10 | 0.428984E+10 | 0.207081E+10 | 0.00 | 0.00 |
March | 0.833298E+10 | 0.551230E+10 | 0.585959E+10 | 0.301799E+10 | 0.284159E+10 | 0.00 | 0.00 |
April | 0.908136E+10 | 0.304679E+10 | 0.482714E+10 | 0.195064E+10 | 0.287650E+10 | 0.00 | 0.00 |
May | 0.707486E+10 | 0.217803E+10 | 0.334251E+10 | 0.552221E+09 | 0.279029E+10 | 0.00 | 0.00 |
June | 0.804103E+10 | 0.816613E+09 | 0.276983E+10 | 0.213518E+09 | 0.255631E+10 | 0.00 | 0.00 |
July | 0.806256E+10 | 0.633607E+09 | 0.292462E+10 | 0.302576E+09 | 0.262205E+10 | 0.00 | 0.00 |
August | 0.921836E+10 | 0.818682E+09 | 0.355620E+10 | 0.982758E+09 | 0.257344E+10 | 0.00 | 0.00 |
September | 0.105763E+11 | 0.125352E+10 | 0.495885E+10 | 0.211557E+10 | 0.284328E+10 | 0.00 | 0.00 |
October | 0.134773E+11 | 0.395092E+10 | 0.816479E+10 | 0.565125E+10 | 0.251354E+10 | 0.00 | 0.00 |
November | 0.134707E+11 | 0.555387E+10 | 0.920812E+10 | 0.705295E+10 | 0.215517E+10 | 0.00 | 0.00 |
December | 0.146109E+11 | 0.743357E+10 | 0.103547E+11 | 0.819710E+10 | 0.215755E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.126855E+12 | 0.429520E+11 | 0.734646E+11 | 0.432217E+11 | 0.302428E+11 | 0.00 | 0.00 |
Minimum of Months | 0.707486E+10 | 0.633607E+09 | 0.276983E+10 | 0.213518E+09 | 0.207081E+10 | 0.00 | 0.00 |
Maximum of Months | 0.165550E+11 | 0.743357E+10 | 0.111376E+11 | 0.889529E+10 | 0.287650E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.435146E+10 | 0.427799E+10 | 0.304615E+10 | 0.189323E+10 | 0.115292E+10 | 0.00 | 0.00 |
February | 0.249730E+10 | 0.374698E+10 | 0.222887E+10 | 0.107752E+10 | 0.115135E+10 | 0.00 | 0.00 |
March | 0.427523E+10 | 0.370619E+10 | 0.326851E+10 | 0.155815E+10 | 0.171036E+10 | 0.00 | 0.00 |
April | 0.819259E+10 | 0.218659E+10 | 0.485700E+10 | 0.277058E+10 | 0.208642E+10 | 0.00 | 0.00 |
May | 0.913320E+10 | 0.162231E+10 | 0.503179E+10 | 0.282133E+10 | 0.221046E+10 | 0.00 | 0.00 |
June | 0.108190E+11 | 0.675563E+09 | 0.517673E+10 | 0.304475E+10 | 0.213198E+10 | 0.00 | 0.00 |
July | 0.843022E+10 | 0.517363E+09 | 0.389334E+10 | 0.181740E+10 | 0.207594E+10 | 0.00 | 0.00 |
August | 0.798571E+10 | 0.645842E+09 | 0.371265E+10 | 0.186457E+10 | 0.184808E+10 | 0.00 | 0.00 |
September | 0.638438E+10 | 0.882824E+09 | 0.313179E+10 | 0.131585E+10 | 0.181594E+10 | 0.00 | 0.00 |
October | 0.536145E+10 | 0.272841E+10 | 0.331129E+10 | 0.189339E+10 | 0.141790E+10 | 0.00 | 0.00 |
November | 0.406710E+10 | 0.383437E+10 | 0.295140E+10 | 0.178197E+10 | 0.116943E+10 | 0.00 | 0.00 |
December | 0.309763E+10 | 0.511174E+10 | 0.245800E+10 | 0.139951E+10 | 0.105849E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.745953E+11 | 0.299362E+11 | 0.430675E+11 | 0.232382E+11 | 0.198293E+11 | 0.00 | 0.00 |
Minimum of Months | 0.249730E+10 | 0.517363E+09 | 0.222887E+10 | 0.107752E+10 | 0.105849E+10 | 0.00 | 0.00 |
Maximum of Months | 0.108190E+11 | 0.511174E+10 | 0.517673E+10 | 0.304475E+10 | 0.221046E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.120579E+10 | 0.549814E+10 | 0.135262E+10 | 0.00 | 0.135262E+10 | 0.00 | 0.00 |
February | 0.704310E+09 | 0.492464E+10 | 0.139212E+10 | 0.00 | 0.139212E+10 | 0.00 | 0.00 |
March | 0.193481E+10 | 0.500151E+10 | 0.204836E+10 | 0.00 | 0.204836E+10 | 0.00 | 0.00 |
April | 0.403780E+10 | 0.274834E+10 | 0.241512E+10 | 25062726.47 | 0.239006E+10 | 0.00 | 0.00 |
May | 0.572210E+10 | 0.195686E+10 | 0.292139E+10 | 0.233918E+09 | 0.268747E+10 | 0.00 | 0.00 |
June | 0.875176E+10 | 0.812013E+09 | 0.328533E+10 | 0.596911E+09 | 0.268842E+10 | 0.00 | 0.00 |
July | 0.770354E+10 | 0.654122E+09 | 0.289516E+10 | 0.301618E+09 | 0.259354E+10 | 0.00 | 0.00 |
August | 0.641916E+10 | 0.805008E+09 | 0.233691E+10 | 58054365.94 | 0.227886E+10 | 0.00 | 0.00 |
September | 0.513232E+10 | 0.119381E+10 | 0.213372E+10 | 569599.25 | 0.213315E+10 | 0.00 | 0.00 |
October | 0.258536E+10 | 0.359376E+10 | 0.170584E+10 | 0.00 | 0.170584E+10 | 0.00 | 0.00 |
November | 0.112548E+10 | 0.493669E+10 | 0.137543E+10 | 0.00 | 0.137543E+10 | 0.00 | 0.00 |
December | 0.770248E+09 | 0.668173E+10 | 0.126347E+10 | 0.00 | 0.126347E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.460927E+11 | 0.388066E+11 | 0.251255E+11 | 0.121613E+10 | 0.239093E+11 | 0.00 | 0.00 |
Minimum of Months | 0.704310E+09 | 0.654122E+09 | 0.126347E+10 | 0.00 | 0.126347E+10 | 0.00 | 0.00 |
Maximum of Months | 0.875176E+10 | 0.668173E+10 | 0.328533E+10 | 0.596911E+09 | 0.268842E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.371395E+10 | 0.350928E+10 | 0.291307E+10 | 0.182745E+10 | 0.108562E+10 | 0.00 | 0.00 |
February | 0.287561E+10 | 0.317500E+10 | 0.259352E+10 | 0.148361E+10 | 0.110991E+10 | 0.00 | 0.00 |
March | 0.456865E+10 | 0.320427E+10 | 0.359343E+10 | 0.184849E+10 | 0.174494E+10 | 0.00 | 0.00 |
April | 0.809244E+10 | 0.180086E+10 | 0.496396E+10 | 0.295858E+10 | 0.200537E+10 | 0.00 | 0.00 |
May | 0.932025E+10 | 0.133744E+10 | 0.531593E+10 | 0.315124E+10 | 0.216469E+10 | 0.00 | 0.00 |
June | 0.109704E+11 | 0.522314E+09 | 0.536218E+10 | 0.333198E+10 | 0.203020E+10 | 0.00 | 0.00 |
July | 0.967534E+10 | 0.422047E+09 | 0.467966E+10 | 0.263867E+10 | 0.204099E+10 | 0.00 | 0.00 |
August | 0.912020E+10 | 0.527743E+09 | 0.444140E+10 | 0.253470E+10 | 0.190670E+10 | 0.00 | 0.00 |
September | 0.692758E+10 | 0.767772E+09 | 0.352691E+10 | 0.170003E+10 | 0.182688E+10 | 0.00 | 0.00 |
October | 0.567997E+10 | 0.230979E+10 | 0.366066E+10 | 0.222785E+10 | 0.143281E+10 | 0.00 | 0.00 |
November | 0.342753E+10 | 0.317060E+10 | 0.272404E+10 | 0.163528E+10 | 0.108876E+10 | 0.00 | 0.00 |
December | 0.292020E+10 | 0.420388E+10 | 0.256640E+10 | 0.154967E+10 | 0.101673E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.772921E+11 | 0.249510E+11 | 0.463412E+11 | 0.268876E+11 | 0.194536E+11 | 0.00 | 0.00 |
Minimum of Months | 0.287561E+10 | 0.422047E+09 | 0.256640E+10 | 0.148361E+10 | 0.101673E+10 | 0.00 | 0.00 |
Maximum of Months | 0.109704E+11 | 0.420388E+10 | 0.536218E+10 | 0.333198E+10 | 0.216469E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.166622E+11 | 0.592672E+10 | 0.111376E+11 | 0.889529E+10 | 0.224231E+10 | 0.00 | 0.00 |
February | 0.844962E+10 | 0.503101E+10 | 0.636065E+10 | 0.428984E+10 | 0.207081E+10 | 0.00 | 0.00 |
March | 0.840025E+10 | 0.523375E+10 | 0.585959E+10 | 0.301799E+10 | 0.284159E+10 | 0.00 | 0.00 |
April | 0.903502E+10 | 0.298638E+10 | 0.482714E+10 | 0.195064E+10 | 0.287650E+10 | 0.00 | 0.00 |
May | 0.701959E+10 | 0.215615E+10 | 0.334251E+10 | 0.552221E+09 | 0.279029E+10 | 0.00 | 0.00 |
June | 0.793875E+10 | 0.827631E+09 | 0.276983E+10 | 0.213518E+09 | 0.255631E+10 | 0.00 | 0.00 |
July | 0.794245E+10 | 0.654730E+09 | 0.292462E+10 | 0.302576E+09 | 0.262205E+10 | 0.00 | 0.00 |
August | 0.911997E+10 | 0.830970E+09 | 0.355620E+10 | 0.982758E+09 | 0.257344E+10 | 0.00 | 0.00 |
September | 0.104956E+11 | 0.126761E+10 | 0.495885E+10 | 0.211557E+10 | 0.284328E+10 | 0.00 | 0.00 |
October | 0.134824E+11 | 0.379015E+10 | 0.816479E+10 | 0.565125E+10 | 0.251354E+10 | 0.00 | 0.00 |
November | 0.135615E+11 | 0.521960E+10 | 0.920812E+10 | 0.705295E+10 | 0.215517E+10 | 0.00 | 0.00 |
December | 0.147665E+11 | 0.693238E+10 | 0.103547E+11 | 0.819710E+10 | 0.215755E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.126874E+12 | 0.408571E+11 | 0.734646E+11 | 0.432217E+11 | 0.302428E+11 | 0.00 | 0.00 |
Minimum of Months | 0.701959E+10 | 0.654730E+09 | 0.276983E+10 | 0.213518E+09 | 0.207081E+10 | 0.00 | 0.00 |
Maximum of Months | 0.166622E+11 | 0.693238E+10 | 0.111376E+11 | 0.889529E+10 | 0.287650E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.439945E+10 | 0.401702E+10 | 0.304615E+10 | 0.189323E+10 | 0.115292E+10 | 0.00 | 0.00 |
February | 0.253324E+10 | 0.347487E+10 | 0.222887E+10 | 0.107752E+10 | 0.115135E+10 | 0.00 | 0.00 |
March | 0.430988E+10 | 0.352831E+10 | 0.326851E+10 | 0.155815E+10 | 0.171036E+10 | 0.00 | 0.00 |
April | 0.815623E+10 | 0.214619E+10 | 0.485700E+10 | 0.277058E+10 | 0.208642E+10 | 0.00 | 0.00 |
May | 0.908234E+10 | 0.160710E+10 | 0.503179E+10 | 0.282133E+10 | 0.221046E+10 | 0.00 | 0.00 |
June | 0.107391E+11 | 0.680662E+09 | 0.517673E+10 | 0.304475E+10 | 0.213198E+10 | 0.00 | 0.00 |
July | 0.835218E+10 | 0.529076E+09 | 0.389334E+10 | 0.181740E+10 | 0.207594E+10 | 0.00 | 0.00 |
August | 0.792279E+10 | 0.651522E+09 | 0.371265E+10 | 0.186457E+10 | 0.184808E+10 | 0.00 | 0.00 |
September | 0.633607E+10 | 0.886383E+09 | 0.313179E+10 | 0.131585E+10 | 0.181594E+10 | 0.00 | 0.00 |
October | 0.536390E+10 | 0.261156E+10 | 0.331129E+10 | 0.189339E+10 | 0.141790E+10 | 0.00 | 0.00 |
November | 0.410563E+10 | 0.359668E+10 | 0.295140E+10 | 0.178197E+10 | 0.116943E+10 | 0.00 | 0.00 |
December | 0.315962E+10 | 0.477293E+10 | 0.245800E+10 | 0.139951E+10 | 0.105849E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.744604E+11 | 0.285023E+11 | 0.430675E+11 | 0.232382E+11 | 0.198293E+11 | 0.00 | 0.00 |
Minimum of Months | 0.253324E+10 | 0.529076E+09 | 0.222887E+10 | 0.107752E+10 | 0.105849E+10 | 0.00 | 0.00 |
Maximum of Months | 0.107391E+11 | 0.477293E+10 | 0.517673E+10 | 0.304475E+10 | 0.221046E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 14.83 | 7.47 | -0.8 | 2.99 | -0.8 | 34.08 | 283.26 | 0.00 |
February | 12.72 | 9.35 | 6.24 | 2.64 | 2.53 | 52.02 | 191.85 | 0.02 |
March | 15.42 | 8.67 | 1.96 | 3.53 | 3.02 | 74.19 | 207.67 | 0.01 |
April | 23.31 | 10.14 | -4.1 | 3.42 | 6.81 | 72.47 | 350.22 | 0.00 |
May | 26.31 | 11.07 | -4.9 | 3.62 | 8.60 | 75.22 | 359.64 | 0.00 |
June | 31.20 | 14.28 | 0.18 | 3.69 | 15.53 | 67.31 | 396.02 | 0.00 |
July | 30.42 | 17.99 | 9.86 | 3.72 | 19.28 | 82.46 | 278.62 | 0.02 |
August | 29.82 | 18.15 | 11.14 | 3.33 | 18.26 | 71.82 | 270.19 | 0.02 |
September | 27.75 | 17.59 | 11.45 | 3.72 | 17.29 | 82.54 | 200.28 | 0.01 |
October | 20.87 | 10.99 | 1.63 | 3.42 | 6.03 | 49.01 | 269.00 | 0.00 |
November | 15.43 | 8.80 | 1.49 | 3.02 | 1.83 | 40.49 | 251.35 | 0.01 |
December | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.74 | 244.35 | 0.00 |
Annual Sum or Average | 21.70 | 11.57 | 2.33 | 3.28 | 7.86 | 61.39 | 275.62 | 0.01 |
Minimum of Months | 11.86 | 4.25 | -5.9 | 2.21 | -4.3 | 34.08 | 191.85 | 0.00 |
Maximum of Months | 31.20 | 18.15 | 11.45 | 3.72 | 19.28 | 82.54 | 396.02 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 29.00 | 31-JAN-15:00 | 10.73 | -14.0 | 2.10 | 7.75 | 109.00 | 697.00 |
February | 22.00 | 18-FEB-14:09 | 14.42 | 9.67 | 5.20 | 14.10 | 264.00 | 225.33 |
March | 28.80 | 16-MAR-15:20 | 13.79 | 1.47 | 3.77 | 14.35 | 156.17 | 666.17 |
April | 35.00 | 14-APR-14:00 | 14.57 | -4.0 | 1.50 | 19.70 | 150.00 | 819.50 |
May | 37.00 | 15-MAY-16:00 | 15.57 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 42.00 | 16-JUN-15:00 | 16.74 | -5.0 | 5.70 | 25.49 | 135.00 | 753.50 |
July | 40.00 | 12-JUL-13:00 | 19.40 | 7.00 | 2.10 | 27.95 | 147.00 | 3.00 |
August | 41.00 | 25-AUG-14:09 | 17.27 | -0.7 | 3.43 | 25.74 | 162.33 | 768.67 |
September | 38.30 | 08-SEP-14:00 | 19.81 | 10.00 | 3.00 | 25.82 | 142.00 | 699.00 |
October | 37.00 | 01-OCT-12:00 | 19.01 | 9.00 | 4.10 | 27.14 | 262.50 | 136.00 |
November | 29.00 | 01-NOV-14:00 | 16.20 | 8.00 | 2.60 | 16.49 | 73.50 | 907.50 |
December | 26.00 | 21-DEC-14:00 | 10.90 | -5.0 | 2.60 | 7.35 | 68.50 | 756.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 22.00 | 10.73 | -14.0 | 1.50 | 7.35 | 68.50 | 3.00 | |
Maximum of Months | 42.00 | 19.81 | 10.00 | 5.70 | 27.95 | 264.00 | 907.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.50 | 01-JAN-07:00 | -1.2 | -3.3 | 3.30 | -16.2 | 17.50 | 352.00 |
February | 5.00 | 01-FEB-04:00 | 3.59 | 2.00 | 3.10 | -10.7 | 0.00 | 0.00 |
March | 0.50 | 26-MAR-03:00 | -2.4 | -6.7 | 2.50 | -17.0 | 0.00 | 0.00 |
April | 8.00 | 21-APR-03:00 | 0.42 | -14.0 | 1.00 | -11.7 | 0.00 | 0.00 |
May | 12.00 | 01-MAY-03:00 | 3.97 | -7.0 | 2.60 | -6.2 | 0.00 | 0.00 |
June | 18.00 | 21-JUN-04:00 | 8.24 | -2.0 | 1.50 | 3.48 | 0.00 | 0.00 |
July | 18.00 | 01-JUL-05:00 | 6.53 | -9.0 | 3.10 | -1.2 | 16.00 | 325.00 |
August | 17.00 | 05-AUG-17:00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 0.00 |
September | 16.60 | 22-SEP-05:00 | 13.83 | 12.20 | 3.00 | 4.92 | 0.00 | 0.00 |
October | 5.00 | 25-OCT-05:00 | 0.48 | -6.0 | 3.10 | -12.7 | 0.00 | 0.00 |
November | 0.00 | 23-NOV-05:00 | -2.5 | -6.0 | 2.10 | -17.3 | 0.00 | 0.00 |
December | -1.1 | 07-DEC-04:00 | -5.6 | -16.0 | 3.10 | -20.8 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -5.6 | -16.0 | 1.00 | -20.8 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 15.02 | 14.00 | 5.70 | 11.46 | 29.00 | 352.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.66 | 08-JAN-15:00 | 18.00 | 16.00 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.73 | 18-FEB-17:00 | 16.00 | 14.00 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 15.18 | 17-MAR-10:00 | 25.50 | 8.30 | 2.50 | 18.46 | 167.50 | 459.00 |
April | 15.71 | 11-APR-14:00 | 33.00 | 3.00 | 2.10 | 15.94 | 178.50 | 758.00 |
May | 15.57 | 15-MAY-16:00 | 37.00 | -2.0 | 4.60 | 20.75 | 127.50 | 679.00 |
June | 23.18 | 17-JUN-15:00 | 41.00 | 16.00 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 23.11 | 13-JUL-17:00 | 26.00 | 22.00 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 22.19 | 16-AUG-10:00 | 35.00 | 17.00 | 2.10 | 24.33 | 140.50 | 837.00 |
September | 22.23 | 01-SEP-11:00 | 34.40 | 17.20 | 4.60 | 23.82 | 193.50 | 725.50 |
October | 21.53 | 01-OCT-17:00 | 32.00 | 17.00 | 2.10 | 25.33 | 30.50 | 1.50 |
November | 18.59 | 12-NOV-14:00 | 20.00 | 18.00 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 12.06 | 12-DEC-12:00 | 20.00 | 6.00 | 1.50 | 12.60 | 182.50 | 6.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.06 | 16.00 | -2.0 | 1.50 | 10.50 | 0.00 | 0.00 | |
Maximum of Months | 23.18 | 41.00 | 22.00 | 6.20 | 31.13 | 257.00 | 837.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 16.00 | 08-JAN-15:00 | 18.00 | 16.66 | 4.60 | 11.46 | 102.00 | 332.00 |
February | 14.00 | 18-FEB-17:00 | 16.00 | 14.73 | 6.20 | 10.50 | 0.00 | 0.00 |
March | 13.30 | 06-MAR-10:00 | 14.40 | 13.70 | 6.10 | 10.69 | 254.50 | 82.00 |
April | 8.00 | 15-APR-20:00 | 23.00 | 14.00 | 6.20 | 7.75 | 0.00 | 0.00 |
May | 9.00 | 26-MAY-02:00 | 21.00 | 13.75 | 3.60 | 16.30 | 0.00 | 0.00 |
June | 16.00 | 17-JUN-15:00 | 41.00 | 23.18 | 3.60 | 31.13 | 257.00 | 9.00 |
July | 22.00 | 13-JUL-17:00 | 26.00 | 23.11 | 4.60 | 22.13 | 79.00 | 56.50 |
August | 20.00 | 09-AUG-17:00 | 25.00 | 21.44 | 5.10 | 19.17 | 35.00 | 0.00 |
September | 20.50 | 02-SEP-22:10 | 22.62 | 21.05 | 3.18 | 20.17 | 0.00 | 0.00 |
October | 19.00 | 03-OCT-02:00 | 23.00 | 20.15 | 2.10 | 10.30 | 0.00 | 0.00 |
November | 18.00 | 12-NOV-14:00 | 20.00 | 18.59 | 3.10 | 15.39 | 115.00 | 0.00 |
December | 10.00 | 12-DEC-23:00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.00 | 12.00 | 10.87 | 1.50 | 7.55 | 0.00 | 0.00 | |
Maximum of Months | 22.00 | 41.00 | 23.18 | 6.20 | 31.13 | 257.00 | 332.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 18.65 | 31.23 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 19.06 | 29.93 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 20.99 | 39.76 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.03 | 60.89 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 27.32 | 65.75 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 29.99 | 69.24 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 31.31 | 56.42 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 30.91 | 52.05 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.91 | 42.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.85 | 39.20 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 22.56 | 30.64 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 19.93 | 27.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 24.99 | 45.50 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 18.65 | 27.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 31.31 | 69.24 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.333371E+11 | -0.328972E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -439920262.0 | 60.05 | 0.00 | 0.00 |
February | 0.300045E+11 | -0.296048E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -399725535.3 | 60.05 | 0.00 | 0.00 |
March | 0.336046E+11 | -0.331611E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -443447973.1 | 60.05 | 0.00 | 0.00 |
April | 0.281595E+11 | -0.277393E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -420274518.9 | 60.05 | 0.00 | 0.00 |
May | 0.273613E+11 | -0.269476E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -413738639.8 | 60.05 | 0.00 | 0.00 |
June | 0.248702E+11 | -0.244977E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -372485255.1 | 60.05 | 0.00 | 0.00 |
July | 0.226475E+11 | -0.222703E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -377245930.0 | 60.05 | 0.00 | 0.00 |
August | 0.251114E+11 | -0.247372E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -374157862.6 | 60.05 | 0.00 | 0.00 |
September | 0.243854E+11 | -0.240080E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -377428308.7 | 60.05 | 0.00 | 0.00 |
October | 0.276085E+11 | -0.271862E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -422324115.1 | 60.05 | 0.00 | 0.00 |
November | 0.296395E+11 | -0.292165E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -422929216.8 | 60.05 | 0.00 | 0.00 |
December | 0.315510E+11 | -0.311120E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -438971471.5 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.338281E+12 | -0.333378E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.490265E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.226475E+11 | -0.331611E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -443447973.1 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.336046E+11 | -0.222703E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -372485255.1 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.50 | 0.48 | 01-JAN-07:00 | 9203.49 | 39.09 | 306.50 | 291.50 | 2392.35 | 29.17 | 193.17 | 287.17 |
February | 241.00 | 0.51 | 0.48 | 01-FEB-07:49 | 8290.48 | 36.52 | 234.33 | 265.00 | 1315.61 | 23.40 | 146.17 | 223.67 |
March | 344.33 | 0.52 | 0.48 | 01-MAR-07:30 | 1597.31 | 19.59 | 47.83 | 328.83 | 930.87 | 20.92 | 181.00 | 287.00 |
April | 380.33 | 0.53 | 0.48 | 01-APR-08:09 | 1243.82 | 19.20 | 19.67 | 333.50 | 780.88 | 20.52 | 131.33 | 303.00 |
May | 403.17 | 0.52 | 0.48 | 01-MAY-07:30 | 993.15 | 18.93 | 0.17 | 359.50 | 625.61 | 20.33 | 71.00 | 318.50 |
June | 418.17 | 0.53 | 0.48 | 01-JUN-07:30 | 828.08 | 18.19 | 0.00 | 363.17 | 537.08 | 19.64 | 19.00 | 313.17 |
July | 399.50 | 0.53 | 0.48 | 01-JUL-07:49 | 954.43 | 18.63 | 0.00 | 363.83 | 577.14 | 20.03 | 80.00 | 297.33 |
August | 361.83 | 0.53 | 0.48 | 01-AUG-07:49 | 1091.69 | 18.98 | 3.50 | 337.83 | 665.38 | 20.34 | 91.50 | 289.00 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-07:10 | 1549.51 | 19.95 | 59.00 | 319.17 | 868.07 | 20.89 | 178.33 | 286.67 |
October | 348.00 | 0.52 | 0.48 | 01-OCT-07:19 | 3162.87 | 25.24 | 154.83 | 314.67 | 1128.80 | 20.59 | 126.00 | 298.50 |
November | 288.50 | 0.50 | 0.48 | 01-NOV-07:40 | 8715.81 | 37.79 | 282.50 | 285.33 | 1595.42 | 24.33 | 150.33 | 263.67 |
December | 290.67 | 0.50 | 0.48 | 01-DEC-07:40 | 8526.15 | 39.08 | 289.33 | 280.00 | 2228.03 | 28.90 | 188.17 | 274.50 |
Annual Sum or Average | 4135.50 | 0.52 | 3392.98 | 24.80 | 1397.67 | 3842.33 | 1070.89 | 22.09 | 1556.00 | 3442.17 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 828.08 | 18.19 | 0.00 | 265.00 | 537.08 | 19.64 | 19.00 | 223.67 | |
Maximum of Months | 418.17 | 0.53 | 0.48 | 9203.49 | 39.09 | 306.50 | 363.83 | 2392.35 | 29.17 | 193.17 | 318.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.53 | 0.48 | 01-JAN-07:49 | 2192.14 | 24.59 | 107.83 | 274.67 | 1199.55 | 24.29 | 103.50 | 232.17 |
February | 241.00 | 0.52 | 0.48 | 01-FEB-07:49 | 2641.19 | 25.06 | 87.83 | 254.33 | 1465.09 | 24.83 | 101.67 | 190.33 |
March | 344.33 | 0.53 | 0.48 | 01-MAR-07:30 | 2214.91 | 23.48 | 100.17 | 316.17 | 1163.30 | 23.57 | 131.33 | 282.83 |
April | 380.33 | 0.51 | 0.48 | 01-APR-06:40 | 3095.57 | 23.61 | 112.33 | 348.17 | 1732.56 | 23.90 | 101.17 | 327.50 |
May | 403.17 | 0.50 | 0.48 | 01-MAY-05:00 | 3515.24 | 24.69 | 134.17 | 380.83 | 1401.62 | 23.56 | 85.00 | 357.67 |
June | 418.17 | 0.51 | 0.48 | 01-JUN-05:49 | 3528.35 | 24.15 | 134.83 | 386.67 | 1384.66 | 23.04 | 78.00 | 353.67 |
July | 399.50 | 0.51 | 0.48 | 01-JUL-05:49 | 3077.60 | 24.13 | 128.17 | 381.33 | 1248.91 | 23.03 | 90.00 | 325.83 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-06:19 | 3009.08 | 23.93 | 114.50 | 353.33 | 1662.54 | 24.11 | 109.83 | 310.33 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-06:30 | 2383.91 | 23.57 | 105.00 | 319.00 | 1272.19 | 23.77 | 127.67 | 279.33 |
October | 348.00 | 0.54 | 0.48 | 01-OCT-06:00 | 2309.82 | 23.24 | 103.33 | 295.33 | 1237.75 | 23.17 | 114.67 | 257.67 |
November | 288.50 | 0.52 | 0.48 | 01-NOV-07:40 | 1868.70 | 23.17 | 80.33 | 273.67 | 982.81 | 23.04 | 86.33 | 210.50 |
December | 290.67 | 0.52 | 0.48 | 01-DEC-07:40 | 2181.70 | 25.15 | 106.33 | 260.83 | 1199.01 | 24.74 | 103.50 | 209.00 |
Annual Sum or Average | 4135.50 | 0.52 | 2727.25 | 24.04 | 1314.83 | 3844.33 | 1338.93 | 23.70 | 1232.67 | 3336.83 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 1868.70 | 23.17 | 80.33 | 254.33 | 982.81 | 23.03 | 78.00 | 190.33 | |
Maximum of Months | 418.17 | 0.54 | 0.48 | 3528.35 | 25.15 | 134.83 | 386.67 | 1732.56 | 24.83 | 131.33 | 357.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.58 | 0.48 | 01-JAN-10:09 | 480.90 | 15.63 | 0.00 | 229.83 | 330.41 | 17.51 | 0.00 | 147.17 |
February | 241.00 | 0.57 | 0.48 | 01-FEB-12:30 | 588.06 | 16.56 | 0.00 | 228.17 | 377.87 | 18.15 | 0.00 | 136.00 |
March | 344.33 | 0.55 | 0.48 | 01-MAR-08:20 | 672.01 | 17.78 | 0.00 | 304.17 | 419.26 | 19.16 | 3.50 | 233.50 |
April | 380.33 | 0.52 | 0.48 | 01-APR-08:30 | 796.33 | 18.90 | 0.00 | 336.33 | 522.06 | 20.24 | 48.17 | 305.00 |
May | 403.17 | 0.49 | 0.48 | 01-MAY-06:10 | 935.27 | 19.67 | 26.67 | 388.67 | 612.15 | 20.96 | 96.00 | 373.17 |
June | 418.17 | 0.49 | 0.48 | 01-JUN-05:00 | 1079.26 | 22.45 | 108.00 | 400.00 | 636.23 | 22.54 | 140.33 | 391.17 |
July | 399.50 | 0.50 | 0.48 | 01-JUL-05:00 | 958.26 | 21.82 | 83.50 | 394.17 | 606.45 | 23.02 | 152.17 | 360.67 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-07:40 | 803.87 | 18.99 | 0.50 | 348.83 | 509.65 | 20.32 | 49.50 | 295.83 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-07:19 | 762.32 | 18.32 | 0.00 | 315.50 | 465.96 | 19.65 | 13.00 | 257.67 |
October | 348.00 | 0.57 | 0.48 | 01-OCT-07:00 | 553.73 | 16.49 | 0.00 | 264.33 | 368.99 | 18.08 | 1.00 | 191.17 |
November | 288.50 | 0.57 | 0.48 | 01-NOV-08:39 | 520.41 | 16.34 | 0.00 | 239.17 | 345.02 | 18.11 | 0.00 | 140.00 |
December | 290.67 | 0.58 | 0.48 | 01-DEC-09:20 | 483.34 | 15.81 | 0.00 | 217.17 | 324.11 | 17.70 | 0.00 | 118.50 |
Annual Sum or Average | 4135.50 | 0.54 | 744.12 | 18.50 | 218.67 | 3666.33 | 474.24 | 19.84 | 503.67 | 2949.83 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 480.90 | 15.63 | 0.00 | 217.17 | 324.11 | 17.51 | 0.00 | 118.50 | |
Maximum of Months | 418.17 | 0.58 | 0.48 | 1079.26 | 22.45 | 108.00 | 400.00 | 636.23 | 23.02 | 152.17 | 391.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.55 | 0.48 | 01-JAN-09:00 | 2356.63 | 24.00 | 107.83 | 248.83 | 1310.66 | 23.76 | 109.00 | 216.17 |
February | 241.00 | 0.54 | 0.48 | 01-FEB-10:30 | 2388.33 | 23.29 | 83.00 | 239.67 | 931.02 | 21.83 | 93.33 | 179.67 |
March | 344.33 | 0.53 | 0.48 | 02-MAR-09:09 | 2025.85 | 22.99 | 95.33 | 315.50 | 1094.74 | 23.27 | 142.67 | 278.00 |
April | 380.33 | 0.52 | 0.48 | 01-APR-08:39 | 2892.48 | 21.67 | 85.00 | 335.17 | 1601.69 | 22.28 | 85.50 | 309.67 |
May | 403.17 | 0.52 | 0.48 | 01-MAY-07:49 | 3100.44 | 19.74 | 54.50 | 365.83 | 1706.16 | 19.65 | 56.67 | 335.83 |
June | 418.17 | 0.52 | 0.48 | 01-JUN-07:40 | 3155.22 | 16.68 | 0.00 | 373.00 | 1269.99 | 19.27 | 56.83 | 345.17 |
July | 399.50 | 0.52 | 0.48 | 01-JUL-07:00 | 2363.26 | 17.40 | 3.67 | 372.33 | 1059.18 | 19.61 | 70.33 | 326.50 |
August | 361.83 | 0.52 | 0.48 | 01-AUG-08:09 | 2421.46 | 19.55 | 49.17 | 343.33 | 1322.45 | 19.70 | 51.33 | 298.67 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-07:49 | 1935.35 | 21.73 | 82.83 | 318.33 | 1038.31 | 22.23 | 116.83 | 282.83 |
October | 348.00 | 0.54 | 0.48 | 01-OCT-08:09 | 2344.56 | 23.55 | 112.00 | 289.00 | 1274.73 | 23.59 | 122.67 | 257.67 |
November | 288.50 | 0.54 | 0.48 | 01-NOV-08:50 | 2189.26 | 23.75 | 93.00 | 254.67 | 1180.36 | 23.58 | 96.67 | 211.33 |
December | 290.67 | 0.54 | 0.48 | 01-DEC-09:20 | 1840.94 | 23.25 | 92.00 | 241.50 | 977.80 | 22.94 | 102.33 | 202.17 |
Annual Sum or Average | 4135.50 | 0.53 | 2455.18 | 21.18 | 858.33 | 3697.17 | 1249.94 | 21.65 | 1104.17 | 3243.67 | ||
Minimum of Months | 241.00 | 0.52 | 0.48 | 1840.94 | 16.68 | 0.00 | 239.67 | 931.02 | 19.27 | 51.33 | 179.67 | |
Maximum of Months | 418.17 | 0.55 | 0.48 | 3155.22 | 24.00 | 112.00 | 373.00 | 1706.16 | 23.76 | 142.67 | 345.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.50 | 0.48 | 01-JAN-07:00 | 9294.01 | 38.70 | 306.33 | 291.67 | 2515.89 | 25.51 | 145.33 | 288.17 |
February | 241.00 | 0.51 | 0.48 | 01-FEB-07:49 | 8352.26 | 36.08 | 234.00 | 265.33 | 1412.70 | 19.02 | 38.33 | 227.00 |
March | 344.33 | 0.52 | 0.48 | 01-MAR-07:30 | 1636.67 | 13.18 | 2.33 | 329.33 | 1000.32 | 16.75 | 1.83 | 292.17 |
April | 380.33 | 0.53 | 0.48 | 01-APR-07:00 | 1280.31 | 13.43 | 0.00 | 334.00 | 839.61 | 16.98 | 0.00 | 308.83 |
May | 403.17 | 0.52 | 0.48 | 01-MAY-07:30 | 1018.29 | 13.32 | 0.00 | 360.83 | 669.95 | 16.88 | 0.00 | 325.83 |
June | 418.17 | 0.53 | 0.48 | 01-JUN-07:19 | 849.68 | 12.63 | 0.00 | 363.83 | 574.95 | 16.23 | 0.00 | 323.00 |
July | 399.50 | 0.53 | 0.48 | 01-JUL-07:30 | 974.41 | 12.89 | 0.00 | 365.00 | 616.58 | 16.42 | 0.00 | 306.67 |
August | 361.83 | 0.52 | 0.48 | 01-AUG-07:40 | 1118.30 | 13.12 | 0.00 | 338.83 | 713.11 | 16.68 | 0.00 | 296.50 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-07:10 | 1583.85 | 13.88 | 10.83 | 320.00 | 930.10 | 16.83 | 0.00 | 290.67 |
October | 348.00 | 0.51 | 0.48 | 01-OCT-07:19 | 3245.05 | 20.64 | 139.83 | 318.17 | 1225.75 | 16.34 | 13.17 | 301.00 |
November | 288.50 | 0.50 | 0.48 | 01-NOV-07:40 | 8791.35 | 37.29 | 282.17 | 285.33 | 1746.00 | 21.56 | 89.17 | 268.67 |
December | 290.67 | 0.49 | 0.48 | 01-DEC-07:40 | 8608.03 | 38.68 | 289.33 | 280.17 | 2350.45 | 25.03 | 130.50 | 275.50 |
Annual Sum or Average | 4135.50 | 0.52 | 3439.73 | 20.54 | 1264.83 | 3852.50 | 1145.64 | 18.37 | 418.33 | 3504.00 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 849.68 | 12.63 | 0.00 | 265.33 | 574.95 | 16.23 | 0.00 | 227.00 | |
Maximum of Months | 418.17 | 0.53 | 0.48 | 9294.01 | 38.70 | 306.33 | 365.00 | 2515.89 | 25.51 | 145.33 | 325.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.53 | 0.48 | 01-JAN-07:49 | 2232.69 | 22.20 | 105.17 | 275.33 | 1249.11 | 22.48 | 74.67 | 240.67 |
February | 241.00 | 0.52 | 0.48 | 01-FEB-07:49 | 2689.33 | 22.51 | 85.83 | 256.00 | 1520.09 | 22.85 | 62.83 | 197.33 |
March | 344.33 | 0.53 | 0.48 | 01-MAR-07:30 | 2223.72 | 19.04 | 86.17 | 316.67 | 1220.65 | 21.18 | 69.67 | 286.67 |
April | 380.33 | 0.51 | 0.48 | 01-APR-06:40 | 3141.34 | 20.63 | 112.33 | 348.50 | 1801.64 | 21.47 | 82.33 | 330.67 |
May | 403.17 | 0.50 | 0.48 | 01-MAY-05:00 | 3561.42 | 21.76 | 134.17 | 381.67 | 1475.36 | 20.86 | 72.33 | 361.33 |
June | 418.17 | 0.51 | 0.48 | 01-JUN-05:49 | 3583.74 | 21.14 | 134.83 | 387.17 | 1455.15 | 20.31 | 74.83 | 358.17 |
July | 399.50 | 0.51 | 0.48 | 01-JUL-05:49 | 3121.75 | 21.14 | 128.17 | 382.50 | 1314.44 | 20.32 | 68.33 | 331.67 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-06:19 | 3047.39 | 20.88 | 114.50 | 353.83 | 1728.26 | 21.62 | 83.50 | 315.00 |
September | 350.17 | 0.52 | 0.48 | 01-SEP-06:30 | 2429.96 | 20.64 | 104.00 | 319.67 | 1328.63 | 21.46 | 75.17 | 284.00 |
October | 348.00 | 0.53 | 0.48 | 01-OCT-06:00 | 2360.98 | 20.39 | 102.83 | 297.00 | 1293.74 | 20.90 | 72.17 | 263.83 |
November | 288.50 | 0.52 | 0.48 | 01-NOV-07:40 | 1906.80 | 20.34 | 80.17 | 274.17 | 1030.19 | 20.87 | 52.83 | 217.83 |
December | 290.67 | 0.52 | 0.48 | 01-DEC-07:40 | 2217.85 | 22.79 | 105.00 | 261.67 | 1245.34 | 22.99 | 74.00 | 215.83 |
Annual Sum or Average | 4135.50 | 0.52 | 2769.16 | 21.07 | 1293.17 | 3854.17 | 1399.42 | 21.34 | 862.67 | 3403.00 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 1906.80 | 19.04 | 80.17 | 256.00 | 1030.19 | 20.31 | 52.83 | 197.33 | |
Maximum of Months | 418.17 | 0.53 | 0.48 | 3583.74 | 22.79 | 134.83 | 387.17 | 1801.64 | 22.99 | 83.50 | 361.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.58 | 0.48 | 01-JAN-09:00 | 490.54 | 10.05 | 0.00 | 231.67 | 352.63 | 13.86 | 0.00 | 167.33 |
February | 241.00 | 0.56 | 0.48 | 01-FEB-10:20 | 600.01 | 11.05 | 0.00 | 229.17 | 403.11 | 14.66 | 0.00 | 151.00 |
March | 344.33 | 0.54 | 0.48 | 01-MAR-08:20 | 686.18 | 12.36 | 0.00 | 305.17 | 447.30 | 15.88 | 0.00 | 244.17 |
April | 380.33 | 0.52 | 0.48 | 01-APR-08:20 | 816.50 | 13.75 | 0.00 | 337.67 | 558.34 | 17.34 | 0.00 | 310.83 |
May | 403.17 | 0.49 | 0.48 | 01-MAY-06:10 | 959.60 | 14.16 | 2.67 | 389.67 | 653.97 | 17.81 | 2.67 | 375.00 |
June | 418.17 | 0.49 | 0.48 | 01-JUN-05:00 | 1106.11 | 17.71 | 81.33 | 401.00 | 703.09 | 20.93 | 81.50 | 395.33 |
July | 399.50 | 0.50 | 0.48 | 01-JUL-05:00 | 980.33 | 16.93 | 62.50 | 394.50 | 646.11 | 20.15 | 62.83 | 366.00 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-07:30 | 823.30 | 13.50 | 0.00 | 349.17 | 544.79 | 17.13 | 0.00 | 302.83 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-07:10 | 777.49 | 12.94 | 0.00 | 316.17 | 496.84 | 16.38 | 0.00 | 269.50 |
October | 348.00 | 0.57 | 0.48 | 01-OCT-07:49 | 566.55 | 11.05 | 0.00 | 266.50 | 394.17 | 14.72 | 0.00 | 207.00 |
November | 288.50 | 0.56 | 0.48 | 01-NOV-08:39 | 530.79 | 10.62 | 0.00 | 240.67 | 368.12 | 14.44 | 0.00 | 159.17 |
December | 290.67 | 0.57 | 0.48 | 01-DEC-09:20 | 492.19 | 10.04 | 0.00 | 221.00 | 345.62 | 13.90 | 0.00 | 140.83 |
Annual Sum or Average | 4135.50 | 0.53 | 761.21 | 13.15 | 146.50 | 3682.33 | 508.65 | 16.72 | 147.00 | 3089.00 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 490.54 | 10.04 | 0.00 | 221.00 | 345.62 | 13.86 | 0.00 | 140.83 | |
Maximum of Months | 418.17 | 0.58 | 0.48 | 1106.11 | 17.71 | 81.33 | 401.00 | 703.09 | 20.93 | 81.50 | 395.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.55 | 0.48 | 01-JAN-09:50 | 2396.16 | 21.58 | 105.67 | 250.83 | 1362.09 | 21.92 | 74.67 | 221.67 |
February | 241.00 | 0.54 | 0.48 | 01-FEB-10:20 | 2429.74 | 20.75 | 81.17 | 241.83 | 979.24 | 19.50 | 36.50 | 185.33 |
March | 344.33 | 0.53 | 0.48 | 01-MAR-08:39 | 2072.73 | 19.93 | 93.67 | 317.67 | 1147.42 | 20.87 | 65.33 | 284.00 |
April | 380.33 | 0.52 | 0.48 | 01-APR-08:30 | 2932.31 | 18.20 | 85.00 | 336.83 | 1670.32 | 19.44 | 55.00 | 314.50 |
May | 403.17 | 0.51 | 0.48 | 01-MAY-07:40 | 3139.47 | 15.78 | 54.50 | 366.33 | 1776.96 | 16.19 | 0.00 | 342.00 |
June | 418.17 | 0.52 | 0.48 | 01-JUN-07:30 | 3173.97 | 11.90 | 0.00 | 373.50 | 1339.13 | 15.74 | 0.00 | 350.50 |
July | 399.50 | 0.52 | 0.48 | 01-JUL-07:49 | 2399.58 | 12.85 | 3.67 | 374.00 | 1115.06 | 16.26 | 0.00 | 333.33 |
August | 361.83 | 0.52 | 0.48 | 01-AUG-07:00 | 2453.19 | 15.65 | 49.17 | 344.33 | 1380.01 | 16.40 | 5.00 | 304.17 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-07:40 | 1976.05 | 18.51 | 81.83 | 319.17 | 1089.49 | 19.68 | 53.83 | 287.00 |
October | 348.00 | 0.54 | 0.48 | 01-OCT-08:09 | 2378.88 | 20.53 | 109.33 | 290.67 | 1326.34 | 21.43 | 81.17 | 263.83 |
November | 288.50 | 0.54 | 0.48 | 01-NOV-08:39 | 2170.61 | 19.73 | 80.83 | 255.67 | 1233.27 | 21.49 | 62.50 | 217.67 |
December | 290.67 | 0.54 | 0.48 | 01-DEC-09:09 | 1838.67 | 19.72 | 80.67 | 243.83 | 1024.38 | 21.02 | 57.50 | 209.17 |
Annual Sum or Average | 4135.50 | 0.53 | 2484.98 | 17.57 | 825.50 | 3714.67 | 1307.26 | 18.93 | 491.50 | 3313.17 | ||
Minimum of Months | 241.00 | 0.51 | 0.48 | 1838.67 | 11.90 | 0.00 | 241.83 | 979.24 | 15.74 | 0.00 | 185.33 | |
Maximum of Months | 418.17 | 0.55 | 0.48 | 3173.97 | 21.58 | 109.33 | 374.00 | 1776.96 | 21.92 | 81.17 | 350.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.50 | 0.48 | 01-JAN-07:00 | 9295.03 | 38.69 | 306.33 | 291.67 | 2517.32 | 25.50 | 145.33 | 288.17 |
February | 241.00 | 0.51 | 0.48 | 01-FEB-07:49 | 8354.27 | 36.07 | 234.00 | 265.33 | 1414.27 | 19.01 | 38.33 | 227.17 |
March | 344.33 | 0.52 | 0.48 | 01-MAR-07:30 | 1638.79 | 13.15 | 2.33 | 329.33 | 1001.67 | 16.74 | 1.83 | 292.33 |
April | 380.33 | 0.53 | 0.48 | 01-APR-07:00 | 1281.62 | 13.40 | 0.00 | 334.17 | 840.55 | 16.97 | 0.00 | 309.00 |
May | 403.17 | 0.52 | 0.48 | 01-MAY-07:30 | 1019.25 | 13.29 | 0.00 | 360.83 | 670.70 | 16.87 | 0.00 | 325.83 |
June | 418.17 | 0.53 | 0.48 | 01-JUN-07:19 | 850.37 | 12.60 | 0.00 | 363.83 | 575.54 | 16.21 | 0.00 | 323.17 |
July | 399.50 | 0.53 | 0.48 | 01-JUL-07:30 | 975.48 | 12.86 | 0.00 | 365.00 | 617.34 | 16.41 | 0.00 | 306.83 |
August | 361.83 | 0.52 | 0.48 | 01-AUG-07:40 | 1119.56 | 13.09 | 0.00 | 339.00 | 713.97 | 16.67 | 0.00 | 296.83 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-07:10 | 1585.93 | 13.86 | 10.83 | 320.00 | 931.42 | 16.82 | 0.00 | 290.67 |
October | 348.00 | 0.51 | 0.48 | 01-OCT-07:19 | 3246.74 | 20.62 | 139.83 | 318.17 | 1226.99 | 16.33 | 13.17 | 301.17 |
November | 288.50 | 0.50 | 0.48 | 01-NOV-07:40 | 8792.63 | 37.29 | 282.17 | 285.33 | 1747.44 | 21.55 | 89.17 | 268.67 |
December | 290.67 | 0.49 | 0.48 | 01-DEC-07:40 | 8608.92 | 38.68 | 289.33 | 280.17 | 2352.00 | 25.02 | 130.50 | 275.50 |
Annual Sum or Average | 4135.50 | 0.52 | 3441.07 | 20.51 | 1264.83 | 3852.83 | 1146.74 | 18.36 | 418.33 | 3505.33 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 850.37 | 12.60 | 0.00 | 265.33 | 575.54 | 16.21 | 0.00 | 227.17 | |
Maximum of Months | 418.17 | 0.53 | 0.48 | 9295.03 | 38.69 | 306.33 | 365.00 | 2517.32 | 25.50 | 145.33 | 325.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.53 | 0.48 | 01-JAN-07:49 | 2233.10 | 22.18 | 105.17 | 275.33 | 1249.71 | 22.47 | 74.67 | 240.67 |
February | 241.00 | 0.52 | 0.48 | 01-FEB-07:49 | 2690.10 | 22.48 | 85.83 | 256.00 | 1520.96 | 22.84 | 62.83 | 197.33 |
March | 344.33 | 0.53 | 0.48 | 01-MAR-07:30 | 2224.79 | 19.01 | 86.17 | 316.67 | 1221.69 | 21.17 | 69.67 | 286.67 |
April | 380.33 | 0.51 | 0.48 | 01-APR-06:40 | 3142.20 | 20.60 | 112.33 | 348.50 | 1802.63 | 21.46 | 82.33 | 330.83 |
May | 403.17 | 0.50 | 0.48 | 01-MAY-05:00 | 3562.25 | 21.73 | 134.17 | 381.67 | 1476.34 | 20.84 | 72.33 | 361.50 |
June | 418.17 | 0.51 | 0.48 | 01-JUN-05:49 | 3584.37 | 21.11 | 134.83 | 387.17 | 1455.99 | 20.29 | 74.83 | 358.33 |
July | 399.50 | 0.51 | 0.48 | 01-JUL-05:49 | 3122.78 | 21.12 | 128.17 | 382.67 | 1315.45 | 20.31 | 68.33 | 331.83 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-06:19 | 3048.44 | 20.85 | 114.50 | 354.00 | 1729.31 | 21.61 | 83.50 | 315.33 |
September | 350.17 | 0.52 | 0.48 | 01-SEP-06:30 | 2431.29 | 20.62 | 104.00 | 319.67 | 1329.82 | 21.45 | 75.17 | 284.17 |
October | 348.00 | 0.53 | 0.48 | 01-OCT-06:00 | 2361.62 | 20.36 | 102.83 | 297.00 | 1294.54 | 20.89 | 72.17 | 264.00 |
November | 288.50 | 0.52 | 0.48 | 01-NOV-07:40 | 1907.37 | 20.31 | 80.17 | 274.17 | 1030.89 | 20.86 | 52.83 | 218.00 |
December | 290.67 | 0.52 | 0.48 | 01-DEC-07:40 | 2218.32 | 22.77 | 105.00 | 261.67 | 1246.00 | 22.98 | 74.00 | 216.00 |
Annual Sum or Average | 4135.50 | 0.52 | 2769.98 | 21.04 | 1293.17 | 3854.50 | 1400.33 | 21.33 | 862.67 | 3404.67 | ||
Minimum of Months | 241.00 | 0.50 | 0.48 | 1907.37 | 19.01 | 80.17 | 256.00 | 1030.89 | 20.29 | 52.83 | 197.33 | |
Maximum of Months | 418.17 | 0.53 | 0.48 | 3584.37 | 22.77 | 134.83 | 387.17 | 1802.63 | 22.98 | 83.50 | 361.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.58 | 0.48 | 01-JAN-09:00 | 490.69 | 10.02 | 0.00 | 231.67 | 352.94 | 13.84 | 0.00 | 167.67 |
February | 241.00 | 0.56 | 0.48 | 01-FEB-10:20 | 600.43 | 11.02 | 0.00 | 229.33 | 403.54 | 14.64 | 0.00 | 151.17 |
March | 344.33 | 0.54 | 0.48 | 01-MAR-08:20 | 686.76 | 12.33 | 0.00 | 305.17 | 447.83 | 15.87 | 0.00 | 244.17 |
April | 380.33 | 0.52 | 0.48 | 01-APR-08:20 | 817.00 | 13.72 | 0.00 | 337.67 | 558.91 | 17.32 | 0.00 | 310.83 |
May | 403.17 | 0.49 | 0.48 | 01-MAY-06:10 | 960.27 | 14.13 | 2.67 | 389.67 | 654.62 | 17.79 | 2.67 | 375.00 |
June | 418.17 | 0.49 | 0.48 | 01-JUN-05:00 | 1106.75 | 17.68 | 81.33 | 401.00 | 703.74 | 20.91 | 81.50 | 395.33 |
July | 399.50 | 0.50 | 0.48 | 01-JUL-05:00 | 981.18 | 16.90 | 62.50 | 394.67 | 646.84 | 20.14 | 62.83 | 366.00 |
August | 361.83 | 0.51 | 0.48 | 01-AUG-07:30 | 823.96 | 13.47 | 0.00 | 349.17 | 545.40 | 17.11 | 0.00 | 303.00 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-07:10 | 778.21 | 12.91 | 0.00 | 316.33 | 497.45 | 16.37 | 0.00 | 270.00 |
October | 348.00 | 0.57 | 0.48 | 01-OCT-07:49 | 566.86 | 11.01 | 0.00 | 266.50 | 394.55 | 14.71 | 0.00 | 207.17 |
November | 288.50 | 0.56 | 0.48 | 01-NOV-08:39 | 531.07 | 10.58 | 0.00 | 240.83 | 368.48 | 14.43 | 0.00 | 159.83 |
December | 290.67 | 0.57 | 0.48 | 01-DEC-09:20 | 492.40 | 10.01 | 0.00 | 221.00 | 345.95 | 13.88 | 0.00 | 140.83 |
Annual Sum or Average | 4135.50 | 0.53 | 761.73 | 13.12 | 146.50 | 3683.00 | 509.18 | 16.70 | 147.00 | 3091.00 | ||
Minimum of Months | 241.00 | 0.49 | 0.48 | 490.69 | 10.01 | 0.00 | 221.00 | 345.95 | 13.84 | 0.00 | 140.83 | |
Maximum of Months | 418.17 | 0.58 | 0.48 | 1106.75 | 17.68 | 81.33 | 401.00 | 703.74 | 20.91 | 81.50 | 395.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 309.83 | 0.55 | 0.48 | 01-JAN-09:50 | 2396.56 | 21.55 | 105.67 | 250.83 | 1362.80 | 21.90 | 74.67 | 221.67 |
February | 241.00 | 0.54 | 0.48 | 01-FEB-10:20 | 2430.65 | 20.73 | 81.17 | 241.83 | 980.19 | 19.48 | 36.50 | 185.33 |
March | 344.33 | 0.53 | 0.48 | 01-MAR-08:39 | 2073.84 | 19.90 | 93.67 | 317.67 | 1148.44 | 20.86 | 65.33 | 284.00 |
April | 380.33 | 0.52 | 0.48 | 01-APR-08:30 | 2933.28 | 18.17 | 85.00 | 336.83 | 1671.43 | 19.43 | 55.00 | 314.67 |
May | 403.17 | 0.51 | 0.48 | 01-MAY-07:40 | 3140.38 | 15.75 | 54.50 | 366.33 | 1778.05 | 16.17 | 0.00 | 342.00 |
June | 418.17 | 0.52 | 0.48 | 01-JUN-07:30 | 3173.14 | 11.86 | 0.00 | 373.33 | 1340.08 | 15.73 | 0.00 | 350.50 |
July | 399.50 | 0.52 | 0.48 | 01-JUL-07:49 | 2378.56 | 12.81 | 3.67 | 373.83 | 1116.10 | 16.24 | 0.00 | 333.67 |
August | 361.83 | 0.52 | 0.48 | 01-AUG-07:00 | 2454.16 | 15.61 | 49.17 | 344.33 | 1380.99 | 16.38 | 5.00 | 304.50 |
September | 350.17 | 0.53 | 0.48 | 01-SEP-07:40 | 1977.36 | 18.48 | 81.83 | 319.17 | 1090.62 | 19.66 | 53.83 | 287.33 |
October | 348.00 | 0.54 | 0.48 | 01-OCT-08:09 | 2379.56 | 20.50 | 109.33 | 290.67 | 1327.14 | 21.41 | 81.17 | 263.83 |
November | 288.50 | 0.54 | 0.48 | 01-NOV-08:39 | 2171.13 | 19.71 | 80.83 | 255.67 | 1234.05 | 21.48 | 62.50 | 218.00 |
December | 290.67 | 0.54 | 0.48 | 01-DEC-09:09 | 1839.13 | 19.70 | 80.67 | 243.83 | 1025.09 | 21.01 | 57.50 | 209.17 |
Annual Sum or Average | 4135.50 | 0.53 | 2483.55 | 17.54 | 825.50 | 3714.33 | 1308.22 | 18.91 | 491.50 | 3314.67 | ||
Minimum of Months | 241.00 | 0.51 | 0.48 | 1839.13 | 11.86 | 0.00 | 241.83 | 980.19 | 15.73 | 0.00 | 185.33 | |
Maximum of Months | 418.17 | 0.55 | 0.48 | 3173.14 | 21.55 | 109.33 | 373.83 | 1778.05 | 21.90 | 81.17 | 350.50 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 3342231.35 | 1794.08 | 12-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 38095961.99 | 6097.03 | 27-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.178683E+09 | 10945.69 | 06-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.220121E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.178683E+09 | 10945.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1609856.24 | 1667.88 | 07-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1609856.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 1609856.24 | 1667.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 851317.93 | 344.58 | 27-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 24822080.12 | 7393.83 | 06-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 25673398.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24822080.12 | 7393.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 78717.52 | 221.05 | 13-FEB-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 101419.89 | 169.03 | 27-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7857907.95 | 2224.23 | 07-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 8038045.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7857907.95 | 2224.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.595485E+09 | 65623.43 | 02-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.675615E+09 | 42842.55 | 28-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174311E+10 | 111448.10 | 27-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147890E+09 | 40274.79 | 25-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.332338E+09 | 61756.02 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.672050E+10 | 154105.12 | 06-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.672050E+10 | 154105.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.216895E+10 | 160930.45 | 02-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.180483E+10 | 142647.83 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.126058E+10 | 171899.78 | 28-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 71904534.91 | 18120.44 | 26-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.112184E+10 | 160188.07 | 24-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.657609E+10 | 170367.03 | 14-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.657609E+10 | 171899.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.148780E+10 | 115486.37 | 02-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154684E+10 | 100730.90 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.951196E+09 | 106513.41 | 27-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140429E+09 | 13675.67 | 26-OCT-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.753828E+09 | 115486.37 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.405842E+10 | 115486.37 | 06-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.893851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.405842E+10 | 115486.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.303950E+09 | 165265.86 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.306387E+09 | 138038.79 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.537234E+09 | 149982.46 | 27-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 65030529.78 | 47280.73 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168724E+10 | 173796.25 | 06-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.289984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.168724E+10 | 173796.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.100561E+10 | 105902.49 | 02-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110150E+10 | 62560.05 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.658560E+09 | 93117.77 | 27-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 76291847.58 | 13019.25 | 26-OCT-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.522216E+09 | 104601.72 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.356766E+10 | 105902.49 | 06-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.693184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.356766E+10 | 105902.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.218210E+09 | 9991.85 | 02-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.333548E+09 | 8755.77 | 28-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.414255E+09 | 16530.66 | 27-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 72605000.01 | 7819.03 | 25-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144897E+09 | 12168.28 | 24-NOV-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140947E+10 | 21455.60 | 06-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.259299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.140947E+10 | 21455.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.392804E+09 | 69148.79 | 02-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159970E+09 | 69148.79 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 64719196.42 | 68516.33 | 27-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102766E+09 | 69148.79 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.516765E+09 | 69148.79 | 11-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.123702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.516765E+09 | 69148.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.102663E+10 | 18347.08 | 02-JAN-05:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.103119E+10 | 18402.92 | 13-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.616861E+09 | 18319.35 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10007346.59 | 1308.46 | 21-APR-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.184212E+09 | 18169.01 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.716740E+09 | 18346.79 | 17-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.234884E+10 | 18322.86 | 18-DEC-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.593448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.234884E+10 | 18402.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.524501E+09 | 14581.00 | 02-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.576526E+09 | 14581.00 | 04-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.329078E+09 | 14581.00 | 07-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4148317.31 | 1405.54 | 21-APR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.111847E+09 | 14581.00 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.343788E+09 | 14581.00 | 07-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118549E+10 | 14581.00 | 01-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.118549E+10 | 14581.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.334855E+09 | 20014.21 | 02-JAN-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.523610E+09 | 20208.25 | 13-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.400984E+09 | 20096.91 | 07-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3327975.36 | 776.43 | 21-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 81434591.99 | 13687.45 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.235341E+09 | 19930.04 | 24-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.888414E+09 | 20067.72 | 18-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.246797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.888414E+09 | 20208.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.504652E+09 | 13787.72 | 02-JAN-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.579990E+09 | 13787.72 | 13-FEB-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.340744E+09 | 13787.72 | 27-MAR-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 624464.61 | 238.88 | 21-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.110424E+09 | 9653.24 | 26-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.343616E+09 | 13787.72 | 24-NOV-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.117238E+10 | 13787.72 | 04-DEC-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.305243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.117238E+10 | 13787.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 2030509.77 | 2376.58 | 13-JAN-07:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4082725.04 | 2944.32 | 28-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12174995.08 | 5641.01 | 29-MAR-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10097.74 | 134.64 | 12-OCT-06:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2653807.00 | 8846.02 | 16-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 20952134.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12174995.08 | 8846.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.421981E+11 | 0.421844E+11 | 102532.56 | 31-JAN-16:40 | 102532.56 | 0.01 |
February | 0.00 | 0.00 | 0.108052E+11 | 0.108052E+11 | 66466.59 | 21-FEB-15:00 | 66466.59 | 0.10 |
March | 0.00 | 0.00 | 0.456138E+11 | 0.456138E+11 | 113513.28 | 20-MAR-14:50 | 113513.28 | 0.09 |
April | 0.00 | 0.00 | 0.120107E+12 | 0.120107E+12 | 142345.29 | 25-APR-15:10 | 142345.29 | 0.02 |
May | 0.00 | 0.00 | 0.149453E+12 | 0.149453E+12 | 157033.04 | 31-MAY-16:00 | 157033.04 | 0.00 |
June | 0.00 | 0.00 | 0.218329E+12 | 0.218314E+12 | 182262.79 | 16-JUN-16:00 | 182262.79 | 0.12 |
July | 0.00 | 0.00 | 0.237553E+12 | 0.221861E+12 | 307012.04 | 14-JUL-05:02 | 124177.81 | 0.66 |
August | 0.00 | 0.00 | 0.253621E+12 | 0.236781E+12 | 298543.56 | 01-AUG-03:13 | 153643.37 | 0.74 |
September | 0.00 | 0.00 | 0.189311E+12 | 0.173627E+12 | 271713.94 | 01-SEP-05:02 | 137621.78 | 0.62 |
October | 0.00 | 0.00 | 0.102048E+12 | 0.998396E+11 | 206023.94 | 03-OCT-07:40 | 127363.43 | 0.20 |
November | 0.00 | 0.00 | 0.496432E+11 | 0.466756E+11 | 156948.94 | 13-NOV-05:11 | 55681.52 | 0.15 |
December | 0.00 | 0.00 | 0.246260E+11 | 0.246260E+11 | 100915.78 | 22-DEC-16:20 | 100915.78 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.144331E+13 | 0.138989E+13 | 0.23 | |||
Minimum of Months | 0.00 | 0.00 | 0.108052E+11 | 0.108052E+11 | 66466.59 | 55681.52 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.253621E+12 | 0.236781E+12 | 307012.04 | 182262.79 | 0.74 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.345655E+12 | 0.345502E+12 | 879647.63 | 31-JAN-16:30 | 879647.63 | 0.01 |
February | 0.00 | 0.00 | 0.811817E+11 | 0.811817E+11 | 494500.41 | 22-FEB-16:00 | 494500.41 | 0.10 |
March | 0.00 | 0.00 | 0.333575E+12 | 0.333575E+12 | 948611.76 | 16-MAR-15:50 | 948611.76 | 0.09 |
April | 0.00 | 0.00 | 0.889614E+12 | 0.889614E+12 | 1247814.33 | 14-APR-15:20 | 1247814.33 | 0.01 |
May | 0.00 | 0.00 | 0.115928E+13 | 0.115928E+13 | 1254678.27 | 18-MAY-15:10 | 1254678.27 | 0.00 |
June | 0.00 | 0.00 | 0.153406E+13 | 0.153405E+13 | 1533244.80 | 30-JUN-05:02 | 1533244.80 | 0.09 |
July | 0.00 | 0.00 | 0.147548E+13 | 0.140078E+13 | 2921752.12 | 14-JUL-05:02 | 1180206.42 | 0.55 |
August | 0.00 | 0.00 | 0.150023E+13 | 0.143199E+13 | 1921781.72 | 04-AUG-05:02 | 933698.76 | 0.60 |
September | 0.00 | 0.00 | 0.124531E+13 | 0.117090E+13 | 2584285.88 | 01-SEP-05:02 | 1304484.90 | 0.51 |
October | 0.00 | 0.00 | 0.724364E+12 | 0.712430E+12 | 1915480.68 | 03-OCT-04:12 | 1026748.74 | 0.15 |
November | 0.00 | 0.00 | 0.345475E+12 | 0.330976E+12 | 1104941.80 | 13-NOV-05:11 | 388388.57 | 0.13 |
December | 0.00 | 0.00 | 0.172492E+12 | 0.172492E+12 | 768627.88 | 22-DEC-16:30 | 768627.88 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.980671E+13 | 0.956276E+13 | 0.19 | |||
Minimum of Months | 0.00 | 0.00 | 0.811817E+11 | 0.811817E+11 | 494500.41 | 388388.57 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.153406E+13 | 0.153405E+13 | 2921752.12 | 1533244.80 | 0.60 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.310552E+11 | 0.310490E+11 | 92412.73 | 31-JAN-16:40 | 92412.73 | 0.01 |
February | 0.00 | 0.00 | 0.660719E+10 | 0.660719E+10 | 48089.68 | 22-FEB-16:00 | 48089.68 | 0.09 |
March | 0.00 | 0.00 | 0.322661E+11 | 0.322661E+11 | 108022.93 | 16-MAR-15:30 | 108022.93 | 0.08 |
April | 0.00 | 0.00 | 0.970296E+11 | 0.970296E+11 | 148717.55 | 14-APR-15:20 | 148717.55 | 0.00 |
May | 0.00 | 0.00 | 0.127870E+12 | 0.127870E+12 | 149469.91 | 18-MAY-15:20 | 149469.91 | 0.00 |
June | 0.00 | 0.00 | 0.174753E+12 | 0.174753E+12 | 174906.97 | 28-JUN-15:00 | 174906.97 | 0.10 |
July | 0.00 | 0.00 | 0.166823E+12 | 0.159189E+12 | 317817.39 | 18-JUL-05:02 | 145222.01 | 0.56 |
August | 0.00 | 0.00 | 0.167034E+12 | 0.159895E+12 | 278457.49 | 01-AUG-05:03 | 133649.81 | 0.61 |
September | 0.00 | 0.00 | 0.134939E+12 | 0.127547E+12 | 282783.43 | 01-SEP-05:02 | 143268.63 | 0.52 |
October | 0.00 | 0.00 | 0.738619E+11 | 0.727544E+11 | 208204.51 | 03-OCT-04:12 | 111770.29 | 0.15 |
November | 0.00 | 0.00 | 0.310150E+11 | 0.300183E+11 | 109428.44 | 01-NOV-15:30 | 109428.44 | 0.12 |
December | 0.00 | 0.00 | 0.141798E+11 | 0.141798E+11 | 79022.65 | 22-DEC-15:50 | 79022.65 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.105743E+13 | 0.103316E+13 | 0.19 | |||
Minimum of Months | 0.00 | 0.00 | 0.660719E+10 | 0.660719E+10 | 48089.68 | 48089.68 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.174753E+12 | 0.174753E+12 | 317817.39 | 174906.97 | 0.61 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.315537E+11 | 0.315497E+11 | 75323.80 | 17-JAN-13:10 | 75323.80 | 0.01 |
February | 0.00 | 0.00 | 0.849904E+10 | 0.846222E+10 | 61999.31 | 10-FEB-11:21 | 61999.31 | 0.09 |
March | 0.00 | 0.00 | 0.316547E+11 | 0.316356E+11 | 71459.58 | 20-MAR-13:10 | 71459.58 | 0.07 |
April | 0.00 | 0.00 | 0.542250E+11 | 0.542250E+11 | 85173.18 | 13-APR-10:00 | 85173.18 | 0.00 |
May | 0.00 | 0.00 | 0.342397E+11 | 0.342397E+11 | 113791.95 | 12-MAY-11:00 | 113791.95 | 0.00 |
June | 0.00 | 0.00 | 0.556507E+10 | 0.556231E+10 | 122788.70 | 21-JUN-09:35 | 122788.70 | 0.00 |
July | 0.00 | 0.00 | 0.374088E+10 | 0.374088E+10 | 119847.47 | 01-JUL-10:50 | 119847.47 | 0.00 |
August | 0.00 | 0.00 | 0.609651E+10 | 0.609651E+10 | 127090.91 | 24-AUG-15:00 | 127090.91 | 0.00 |
September | 0.00 | 0.00 | 0.261624E+11 | 0.233689E+11 | 138251.97 | 14-SEP-09:00 | 97655.14 | 0.10 |
October | 0.00 | 0.00 | 0.455367E+11 | 0.449098E+11 | 138451.54 | 04-OCT-08:30 | 101371.15 | 0.05 |
November | 0.00 | 0.00 | 0.360178E+11 | 0.326174E+11 | 124692.52 | 13-NOV-14:10 | 52368.58 | 0.09 |
December | 0.00 | 0.00 | 0.172057E+11 | 0.172035E+11 | 81726.60 | 26-DEC-13:10 | 81726.60 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.300497E+12 | 0.293611E+12 | 0.03 | |||
Minimum of Months | 0.00 | 0.00 | 0.374088E+10 | 0.374088E+10 | 61999.31 | 52368.58 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.542250E+11 | 0.542250E+11 | 138451.54 | 127090.91 | 0.10 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.273486E+11 | 0.273261E+11 | 141647.62 | 27-JAN-16:00 | 141647.62 | 0.00 |
February | 0.00 | 0.00 | 0.771774E+10 | 0.737339E+10 | 84546.30 | 18-FEB-14:00 | 72677.30 | 0.00 |
March | 0.00 | 0.00 | 0.167126E+12 | 0.164888E+12 | 323774.62 | 17-MAR-15:20 | 323774.62 | 0.00 |
April | 0.00 | 0.00 | 0.699541E+12 | 0.698256E+12 | 440544.98 | 02-APR-14:07 | 440544.98 | 0.00 |
May | 0.00 | 0.00 | 0.224488E+12 | 0.224488E+12 | 220075.48 | 31-MAY-23:10 | 220075.48 | 0.00 |
June | 0.00 | 0.00 | 0.529188E+12 | 0.529179E+12 | 313638.64 | 30-JUN-23:57 | 313638.64 | 0.00 |
July | 0.00 | 0.00 | 0.889486E+12 | 0.805019E+12 | 544272.86 | 14-JUL-01:00 | 180872.74 | 0.00 |
August | 0.00 | 0.00 | 0.113928E+13 | 0.101197E+13 | 526019.83 | 09-AUG-18:20 | 265824.32 | 0.00 |
September | 0.00 | 0.00 | 0.272038E+12 | 0.246803E+12 | 245685.29 | 04-SEP-10:17 | 136109.22 | 0.00 |
October | 0.00 | 0.00 | 0.242803E+12 | 0.232430E+12 | 349355.64 | 03-OCT-08:30 | 231764.81 | 0.00 |
November | 0.00 | 0.00 | 0.162237E+12 | 0.147413E+12 | 326518.55 | 20-NOV-15:20 | 326518.55 | 0.00 |
December | 0.00 | 0.00 | 0.165856E+12 | 0.165733E+12 | 387605.39 | 21-DEC-15:00 | 387605.39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.452711E+13 | 0.426088E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.771774E+10 | 0.737339E+10 | 84546.30 | 72677.30 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.113928E+13 | 0.101197E+13 | 544272.86 | 440544.98 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.550598E+10 | 0.550283E+10 | 2812.64 | 29-JAN-17:17 | 2812.64 | 0.00 |
February | 0.00 | 0.00 | 0.941202E+10 | 0.936924E+10 | 4561.00 | 22-FEB-17:00 | 4506.00 | 0.00 |
March | 0.00 | 0.00 | 0.158129E+11 | 0.158010E+11 | 7739.06 | 31-MAR-24:00 | 7739.06 | 0.00 |
April | 0.00 | 0.00 | 0.201894E+11 | 0.201894E+11 | 8417.05 | 26-APR-18:20 | 8417.05 | 0.00 |
May | 0.00 | 0.00 | 0.649915E+10 | 0.649915E+10 | 4154.82 | 31-MAY-23:50 | 4154.82 | 0.00 |
June | 0.00 | 0.00 | 0.115151E+11 | 0.115137E+11 | 6133.07 | 30-JUN-23:57 | 6133.07 | 0.00 |
July | 0.00 | 0.00 | 0.170870E+11 | 0.169302E+11 | 8083.18 | 31-JUL-23:55 | 8064.52 | 0.00 |
August | 0.00 | 0.00 | 0.216710E+11 | 0.215108E+11 | 8822.70 | 28-AUG-16:17 | 8262.87 | 0.00 |
September | 0.00 | 0.00 | 0.651696E+10 | 0.638175E+10 | 4210.88 | 30-SEP-23:47 | 4210.88 | 0.00 |
October | 0.00 | 0.00 | 0.112585E+11 | 0.112288E+11 | 5913.14 | 31-OCT-24:00 | 5913.14 | 0.00 |
November | 0.00 | 0.00 | 0.154806E+11 | 0.154334E+11 | 6950.84 | 14-NOV-17:00 | 6719.56 | 0.00 |
December | 0.00 | 0.00 | 0.206826E+11 | 0.206822E+11 | 8469.32 | 28-DEC-17:00 | 8469.32 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.161631E+12 | 0.161042E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.550598E+10 | 0.550283E+10 | 2812.64 | 2812.64 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.216710E+11 | 0.215108E+11 | 8822.70 | 8469.32 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.418504E+11 | 0.418204E+11 | 26096.24 | 24-JAN-17:00 | 26096.24 | 0.00 |
February | 0.00 | 0.00 | 0.795654E+11 | 0.791449E+11 | 42628.75 | 22-FEB-17:00 | 42103.70 | 0.00 |
March | 0.00 | 0.00 | 0.143500E+12 | 0.143380E+12 | 72280.49 | 31-MAR-23:50 | 72280.49 | 0.00 |
April | 0.00 | 0.00 | 0.191400E+12 | 0.191400E+12 | 80249.20 | 26-APR-18:20 | 80249.20 | 0.00 |
May | 0.00 | 0.00 | 0.592546E+11 | 0.592546E+11 | 39478.15 | 31-MAY-23:53 | 39478.15 | 0.00 |
June | 0.00 | 0.00 | 0.107351E+12 | 0.107334E+12 | 57742.42 | 30-JUN-23:57 | 57742.42 | 0.00 |
July | 0.00 | 0.00 | 0.159495E+12 | 0.157938E+12 | 75749.32 | 31-JUL-23:55 | 75569.02 | 0.00 |
August | 0.00 | 0.00 | 0.203948E+12 | 0.202340E+12 | 83880.29 | 28-AUG-16:13 | 78311.86 | 0.00 |
September | 0.00 | 0.00 | 0.588064E+11 | 0.574843E+11 | 39489.78 | 30-SEP-24:00 | 39489.78 | 0.00 |
October | 0.00 | 0.00 | 0.101739E+12 | 0.101444E+12 | 54518.08 | 31-OCT-24:00 | 54518.08 | 0.00 |
November | 0.00 | 0.00 | 0.139087E+12 | 0.138618E+12 | 65379.70 | 14-NOV-17:00 | 63095.29 | 0.00 |
December | 0.00 | 0.00 | 0.184243E+12 | 0.184237E+12 | 79890.08 | 26-DEC-17:10 | 79890.08 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.147024E+13 | 0.146440E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.418504E+11 | 0.418204E+11 | 26096.24 | 26096.24 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.203948E+12 | 0.202340E+12 | 83880.29 | 80249.20 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.328120E+10 | 0.327842E+10 | 2641.05 | 24-JAN-17:00 | 2641.05 | 0.00 |
February | 0.00 | 0.00 | 0.699028E+10 | 0.694871E+10 | 4300.76 | 22-FEB-17:00 | 4247.74 | 0.00 |
March | 0.00 | 0.00 | 0.137108E+11 | 0.136990E+11 | 7056.15 | 31-MAR-23:20 | 7056.15 | 0.00 |
April | 0.00 | 0.00 | 0.191647E+11 | 0.191647E+11 | 8059.61 | 26-APR-18:10 | 8059.61 | 0.00 |
May | 0.00 | 0.00 | 0.596032E+10 | 0.596032E+10 | 3961.35 | 31-MAY-23:53 | 3961.35 | 0.00 |
June | 0.00 | 0.00 | 0.109063E+11 | 0.109047E+11 | 5828.29 | 30-JUN-23:57 | 5828.29 | 0.00 |
July | 0.00 | 0.00 | 0.161383E+11 | 0.159824E+11 | 7645.68 | 31-JUL-23:55 | 7627.48 | 0.00 |
August | 0.00 | 0.00 | 0.205764E+11 | 0.204144E+11 | 8504.78 | 28-AUG-15:52 | 7938.15 | 0.00 |
September | 0.00 | 0.00 | 0.596635E+10 | 0.583370E+10 | 4006.28 | 30-SEP-24:00 | 4006.28 | 0.00 |
October | 0.00 | 0.00 | 0.981020E+10 | 0.978082E+10 | 5262.32 | 31-OCT-23:50 | 5262.32 | 0.00 |
November | 0.00 | 0.00 | 0.130859E+11 | 0.130392E+11 | 6562.62 | 14-NOV-17:00 | 6333.55 | 0.00 |
December | 0.00 | 0.00 | 0.171206E+11 | 0.171201E+11 | 8050.62 | 26-DEC-17:00 | 8050.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.142711E+12 | 0.142126E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.328120E+10 | 0.327842E+10 | 2641.05 | 2641.05 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.205764E+11 | 0.204144E+11 | 8504.78 | 8059.61 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 177029.29 | 1512812.65 | 31-JAN-15:30 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 45297.48 | 644185.74 | 22-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 171798.47 | 1479405.89 | 16-MAR-13:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 468855.40 | 1717162.81 | 24-APR-10:25 | 0.00 | 0.00 | 01-APR-00:10 |
May | 574482.36 | 1769782.03 | 20-MAY-16:02 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 766057.93 | 1919287.70 | 19-JUN-14:10 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 731805.96 | 3288108.25 | 18-JUL-05:04 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 745916.40 | 2078835.46 | 28-AUG-16:20 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 642513.59 | 2648098.57 | 01-SEP-05:04 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 368662.68 | 1684818.99 | 04-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 189102.16 | 1526978.95 | 20-NOV-16:20 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 88327.31 | 1139430.02 | 22-DEC-16:20 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 416062.74 | 0.00 | ||||
Minimum of Months | 45297.48 | 644185.74 | 0.00 | 0.00 | ||
Maximum of Months | 766057.93 | 3288108.25 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 175390.49 | 1490654.94 | 31-JAN-16:20 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 44163.92 | 641939.10 | 22-FEB-16:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 170059.64 | 1453937.89 | 17-MAR-13:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 461708.25 | 1604150.68 | 14-APR-15:20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 566224.26 | 1663045.28 | 08-MAY-04:12 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 758755.37 | 2149602.87 | 28-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 727292.28 | 3848482.64 | 14-JUL-04:03 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 742347.16 | 3291051.25 | 04-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 639864.08 | 3490291.97 | 05-SEP-03:02 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 365091.30 | 3406343.17 | 03-OCT-04:12 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 188246.56 | 2641192.36 | 02-NOV-14:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 87244.98 | 1139200.69 | 22-DEC-16:20 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 412430.06 | 0.00 | ||||
Minimum of Months | 44163.92 | 641939.10 | 0.00 | 0.00 | ||
Maximum of Months | 758755.37 | 3848482.64 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 111831.53 | 925818.73 | 31-JAN-17:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 64620.71 | 428016.13 | 18-FEB-14:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 277889.14 | 1333353.71 | 16-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 982103.36 | 1945534.35 | 14-APR-16:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 675745.32 | 1418309.13 | 31-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1228927.89 | 1973319.11 | 28-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1453969.49 | 2078167.01 | 19-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1627669.46 | 2324669.39 | 25-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 786361.26 | 1507957.32 | 08-SEP-16:00 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 483735.79 | 1620547.59 | 01-OCT-14:00 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 267655.69 | 1343606.59 | 01-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 248653.17 | 1331515.71 | 21-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 687740.10 | 0.00 | ||||
Minimum of Months | 64620.71 | 428016.13 | 0.00 | 0.00 | ||
Maximum of Months | 1627669.46 | 2324669.39 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 12201.44 | 43368.99 | 23-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 12156.54 | 43288.06 | 01-FEB-12:20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 12299.88 | 42042.02 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 10623.06 | 39019.98 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 9983.11 | 35812.03 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 9374.21 | 32497.38 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 8239.12 | 30277.62 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 9159.04 | 31173.29 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 9185.45 | 33782.14 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 10072.05 | 37424.18 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 11192.15 | 40635.45 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 11535.83 | 42745.22 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 10492.70 | ||||
Minimum of Months | 0.00 | 0.00 | 8239.12 | 30277.62 | ||
Maximum of Months | 0.00 | 0.00 | 12299.88 | 43368.99 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 196641.98 | 2389857.78 | 31-JAN-15:40 | 1183.34 | 102895.17 | 30-JAN-09:50 |
February | 46012.96 | 725252.44 | 22-FEB-16:00 | 2421.55 | 110037.10 | 03-FEB-09:50 |
March | 189039.09 | 2394237.78 | 20-MAR-14:40 | 2360.20 | 110827.95 | 25-MAR-09:50 |
April | 548990.64 | 2541589.09 | 14-APR-14:30 | 2571.10 | 101498.87 | 23-APR-00:50 |
May | 691043.90 | 2618718.93 | 18-MAY-14:10 | 436.68 | 82459.55 | 22-MAY-05:30 |
June | 1042471.37 | 3995713.26 | 17-JUN-16:00 | 454.97 | 66078.64 | 13-JUN-04:10 |
July | 1322353.98 | 5277956.28 | 14-JUL-05:03 | 256.11 | 63170.53 | 03-JUL-03:10 |
August | 1346271.80 | 4655595.43 | 16-AUG-11:00 | 268.94 | 61348.98 | 25-AUG-03:40 |
September | 1086629.25 | 4812874.21 | 01-SEP-12:20 | 35.02 | 30448.20 | 30-SEP-01:45 |
October | 493379.54 | 3798818.47 | 03-OCT-09:40 | 1145.33 | 127547.86 | 25-OCT-05:50 |
November | 215597.53 | 2511303.27 | 02-NOV-14:20 | 1137.81 | 115429.94 | 29-NOV-07:11 |
December | 95153.29 | 1307522.15 | 22-DEC-16:20 | 2094.69 | 136725.36 | 05-DEC-06:30 |
Annual Sum or Average | 609450.46 | 1188.70 | ||||
Minimum of Months | 46012.96 | 725252.44 | 35.02 | 30448.20 | ||
Maximum of Months | 1346271.80 | 5277956.28 | 2571.10 | 136725.36 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.671090E+10 | 0.42 | 13316.94 | 02-JAN-16:20 | 1.38 |
February | 0.587183E+10 | 0.41 | 12694.71 | 21-FEB-15:50 | 1.33 |
March | 0.881741E+10 | 0.50 | 15239.88 | 20-MAR-14:50 | 1.49 |
April | 0.142200E+11 | 0.72 | 22970.38 | 26-APR-14:58 | 1.94 |
May | 0.169285E+11 | 0.74 | 22970.38 | 04-MAY-15:10 | 1.94 |
June | 0.240502E+11 | 1.00 | 22970.38 | 01-JUN-12:10 | 1.93 |
July | 0.249662E+11 | 0.99 | 22970.38 | 01-JUL-04:12 | 1.95 |
August | 0.270817E+11 | 1.06 | 22970.38 | 01-AUG-03:13 | 1.92 |
September | 0.184490E+11 | 0.81 | 22970.38 | 01-SEP-04:03 | 1.92 |
October | 0.120574E+11 | 0.60 | 22970.38 | 02-OCT-05:02 | 1.92 |
November | 0.870030E+10 | 0.49 | 16016.46 | 13-NOV-05:11 | 1.53 |
December | 0.759778E+10 | 0.45 | 17883.16 | 26-DEC-17:00 | 1.66 |
Annual Sum or Average | 0.175451E+12 | 0.68 | |||
Minimum of Months | 0.587183E+10 | 0.41 | 12694.71 | 1.33 | |
Maximum of Months | 0.270817E+11 | 1.06 | 22970.38 | 1.95 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.448103E+11 | 0.36 | 90706.77 | 23-JAN-06:03 | 1.13 |
February | 0.373992E+11 | 0.34 | 97245.06 | 28-FEB-06:02 | 1.18 |
March | 0.527765E+11 | 0.39 | 109259.70 | 16-MAR-15:50 | 1.27 |
April | 0.874905E+11 | 0.53 | 194839.87 | 26-APR-05:02 | 1.82 |
May | 0.106088E+12 | 0.58 | 216517.32 | 08-MAY-04:12 | 1.95 |
June | 0.128582E+12 | 0.69 | 216517.32 | 02-JUN-04:12 | 1.95 |
July | 0.115664E+12 | 0.63 | 216517.32 | 03-JUL-04:12 | 1.96 |
August | 0.120174E+12 | 0.64 | 216517.32 | 02-AUG-05:03 | 1.93 |
September | 0.948133E+11 | 0.54 | 216517.32 | 01-SEP-05:02 | 1.93 |
October | 0.675192E+11 | 0.44 | 216517.32 | 02-OCT-05:02 | 1.94 |
November | 0.484357E+11 | 0.37 | 97322.87 | 02-NOV-16:00 | 1.17 |
December | 0.401750E+11 | 0.34 | 134090.05 | 16-DEC-06:02 | 1.45 |
Annual Sum or Average | 0.943928E+12 | 0.49 | |||
Minimum of Months | 0.373992E+11 | 0.34 | 90706.77 | 1.13 | |
Maximum of Months | 0.128582E+12 | 0.69 | 216517.32 | 1.96 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.387954E+10 | 0.33 | 7772.23 | 27-JAN-17:00 | 0.97 |
February | 0.312472E+10 | 0.31 | 7024.65 | 22-FEB-16:30 | 0.91 |
March | 0.440753E+10 | 0.35 | 11056.27 | 16-MAR-15:30 | 1.19 |
April | 0.856427E+10 | 0.49 | 17541.47 | 14-APR-15:20 | 1.58 |
May | 0.107367E+11 | 0.55 | 24149.45 | 08-MAY-04:12 | 1.94 |
June | 0.141632E+11 | 0.69 | 24149.45 | 19-JUN-04:12 | 1.94 |
July | 0.125571E+11 | 0.62 | 24149.45 | 05-JUL-04:12 | 1.94 |
August | 0.128374E+11 | 0.62 | 24149.45 | 04-AUG-05:02 | 1.92 |
September | 0.968063E+10 | 0.52 | 24149.45 | 20-SEP-04:12 | 1.93 |
October | 0.610586E+10 | 0.40 | 24149.45 | 02-OCT-05:02 | 1.93 |
November | 0.404445E+10 | 0.33 | 9814.30 | 02-NOV-15:50 | 1.10 |
December | 0.341955E+10 | 0.32 | 6947.81 | 22-DEC-16:50 | 0.91 |
Annual Sum or Average | 0.935210E+11 | 0.46 | |||
Minimum of Months | 0.312472E+10 | 0.31 | 6947.81 | 0.91 | |
Maximum of Months | 0.141632E+11 | 0.69 | 24149.45 | 1.94 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.141336E+11 | 0.81 | 13557.05 | 02-JAN-07:05 | 1.96 |
February | 0.116149E+11 | 0.75 | 13557.05 | 01-FEB-07:05 | 1.96 |
March | 0.105266E+11 | 0.67 | 13557.05 | 01-MAR-07:10 | 1.96 |
April | 0.118039E+11 | 0.69 | 13557.05 | 01-APR-06:10 | 1.97 |
May | 0.567056E+10 | 0.32 | 13557.05 | 01-MAY-06:05 | 1.97 |
June | 0.723998E+09 | 0.04 | 13557.05 | 21-JUN-06:10 | 1.89 |
July | 0.487793E+09 | 0.03 | 13557.05 | 01-JUL-06:10 | 1.89 |
August | 0.729848E+09 | 0.04 | 13557.05 | 24-AUG-06:05 | 1.96 |
September | 0.361521E+10 | 0.20 | 13557.05 | 14-SEP-06:10 | 1.88 |
October | 0.119707E+11 | 0.67 | 13557.05 | 04-OCT-06:10 | 1.88 |
November | 0.145706E+11 | 0.84 | 13557.05 | 01-NOV-21:00 | 1.91 |
December | 0.143489E+11 | 0.82 | 13557.05 | 01-DEC-07:10 | 1.97 |
Annual Sum or Average | 0.100197E+12 | 0.49 | |||
Minimum of Months | 0.487793E+09 | 0.03 | 13557.05 | 1.88 | |
Maximum of Months | 0.145706E+11 | 0.84 | 13557.05 | 1.97 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.118891E+12 | 1.48 | 44388.95 | 01-JAN-00:10 | 1.48 |
February | 0.107386E+12 | 1.48 | 44388.95 | 01-FEB-00:10 | 1.48 |
March | 0.118891E+12 | 1.48 | 44388.95 | 01-MAR-00:10 | 1.48 |
April | 0.115056E+12 | 1.48 | 44388.95 | 01-APR-00:10 | 1.48 |
May | 0.118891E+12 | 1.48 | 44388.95 | 01-MAY-00:05 | 1.49 |
June | 0.115056E+12 | 1.48 | 44388.95 | 01-JUN-00:03 | 1.49 |
July | 0.118891E+12 | 1.47 | 44388.95 | 01-JUL-00:03 | 1.47 |
August | 0.118891E+12 | 1.47 | 44388.95 | 01-AUG-00:03 | 1.47 |
September | 0.115056E+12 | 1.47 | 44388.95 | 01-SEP-00:05 | 1.47 |
October | 0.118891E+12 | 1.48 | 44388.95 | 01-OCT-00:03 | 1.47 |
November | 0.115056E+12 | 1.48 | 44388.95 | 01-NOV-00:10 | 1.48 |
December | 0.118891E+12 | 1.49 | 44388.95 | 01-DEC-00:10 | 1.49 |
Annual Sum or Average | 0.139985E+13 | 1.48 | |||
Minimum of Months | 0.107386E+12 | 1.47 | 44388.95 | 1.47 | |
Maximum of Months | 0.118891E+12 | 1.49 | 44388.95 | 1.49 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.155827E+10 | 1.01 | 581.79 | 01-JAN-00:10 | 1.01 |
February | 0.140747E+10 | 1.01 | 581.79 | 01-FEB-00:10 | 1.01 |
March | 0.155827E+10 | 1.01 | 581.79 | 01-MAR-00:10 | 1.01 |
April | 0.150801E+10 | 1.01 | 581.79 | 01-APR-00:10 | 1.01 |
May | 0.155827E+10 | 1.01 | 581.79 | 01-MAY-00:05 | 1.01 |
June | 0.150801E+10 | 1.01 | 581.79 | 01-JUN-00:03 | 1.01 |
July | 0.155827E+10 | 1.01 | 581.79 | 01-JUL-00:03 | 1.01 |
August | 0.155827E+10 | 1.00 | 581.79 | 01-AUG-00:03 | 1.00 |
September | 0.150801E+10 | 1.00 | 581.79 | 01-SEP-00:05 | 1.00 |
October | 0.155827E+10 | 1.01 | 581.79 | 01-OCT-00:03 | 1.01 |
November | 0.150801E+10 | 1.01 | 581.79 | 01-NOV-00:10 | 1.01 |
December | 0.155827E+10 | 1.01 | 581.79 | 01-DEC-00:10 | 1.01 |
Annual Sum or Average | 0.183474E+11 | 1.01 | |||
Minimum of Months | 0.140747E+10 | 1.00 | 581.79 | 1.00 | |
Maximum of Months | 0.155827E+10 | 1.01 | 581.79 | 1.01 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.148642E+11 | 1.01 | 5549.64 | 01-JAN-00:10 | 1.01 |
February | 0.134257E+11 | 1.01 | 5549.64 | 01-FEB-00:10 | 1.01 |
March | 0.148642E+11 | 1.01 | 5549.64 | 01-MAR-00:10 | 1.01 |
April | 0.143847E+11 | 1.01 | 5549.64 | 01-APR-00:10 | 1.01 |
May | 0.148642E+11 | 1.01 | 5549.64 | 01-MAY-00:05 | 1.01 |
June | 0.143847E+11 | 1.01 | 5549.64 | 01-JUN-00:03 | 1.01 |
July | 0.148642E+11 | 1.01 | 5549.64 | 01-JUL-00:03 | 1.01 |
August | 0.148642E+11 | 1.00 | 5549.64 | 01-AUG-00:03 | 1.00 |
September | 0.143847E+11 | 1.00 | 5549.64 | 01-SEP-00:05 | 1.00 |
October | 0.148642E+11 | 1.01 | 5549.64 | 01-OCT-00:03 | 1.01 |
November | 0.143847E+11 | 1.01 | 5549.64 | 01-NOV-00:10 | 1.01 |
December | 0.148642E+11 | 1.01 | 5549.64 | 01-DEC-00:10 | 1.01 |
Annual Sum or Average | 0.175013E+12 | 1.01 | |||
Minimum of Months | 0.134257E+11 | 1.00 | 5549.64 | 1.00 | |
Maximum of Months | 0.148642E+11 | 1.01 | 5549.64 | 1.01 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.152043E+10 | 1.01 | 567.66 | 01-JAN-00:10 | 1.00 |
February | 0.137329E+10 | 1.01 | 567.66 | 01-FEB-00:10 | 1.01 |
March | 0.152043E+10 | 1.01 | 567.66 | 01-MAR-00:10 | 1.01 |
April | 0.147138E+10 | 1.01 | 567.66 | 01-APR-00:10 | 1.01 |
May | 0.152043E+10 | 1.01 | 567.66 | 01-MAY-00:05 | 1.01 |
June | 0.147138E+10 | 1.01 | 567.66 | 01-JUN-00:03 | 1.01 |
July | 0.152043E+10 | 1.01 | 567.66 | 01-JUL-00:03 | 1.01 |
August | 0.152043E+10 | 1.00 | 567.66 | 01-AUG-00:03 | 1.00 |
September | 0.147138E+10 | 1.00 | 567.66 | 01-SEP-00:10 | 1.00 |
October | 0.152043E+10 | 1.01 | 567.66 | 01-OCT-00:07 | 1.01 |
November | 0.147138E+10 | 1.01 | 567.66 | 01-NOV-00:10 | 1.01 |
December | 0.152043E+10 | 1.01 | 567.66 | 01-DEC-00:10 | 1.01 |
Annual Sum or Average | 0.179018E+11 | 1.01 | |||
Minimum of Months | 0.137329E+10 | 1.00 | 567.66 | 1.00 | |
Maximum of Months | 0.152043E+10 | 1.01 | 567.66 | 1.01 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.152070E+09 | 0.136863E+09 | 1146.10 | 31-JAN-15:30 | 1031.49 | 1031.49 | 7.88 | 27.10 |
February | 32862954.23 | 29576658.81 | 466.01 | 16-FEB-13:30 | 419.41 | 419.41 | 6.71 | 17.90 |
March | 0.184077E+09 | 0.165670E+09 | 3240.44 | 17-MAR-13:10 | 2916.40 | 2916.40 | 7.93 | 42.45 |
April | 0.392652E+09 | 0.353387E+09 | 837.38 | 14-APR-16:00 | 753.64 | 753.64 | 6.71 | 23.53 |
May | 0.510299E+09 | 0.459270E+09 | 1081.73 | 11-MAY-05:03 | 973.55 | 973.55 | 6.70 | 26.41 |
June | 0.105228E+10 | 0.947048E+09 | 5295.26 | 19-JUN-14:30 | 4765.74 | 4765.74 | 6.72 | 51.99 |
July | 0.137552E+10 | 0.123796E+10 | 10404.19 | 14-JUL-04:03 | 9363.77 | 9363.77 | 10.69 | 68.12 |
August | 0.158877E+10 | 0.142990E+10 | 10406.79 | 04-AUG-05:03 | 9366.11 | 9366.11 | 11.51 | 68.12 |
September | 0.136780E+10 | 0.123102E+10 | 10402.75 | 08-SEP-05:03 | 9362.47 | 9362.47 | 10.23 | 68.12 |
October | 0.643117E+09 | 0.578805E+09 | 10401.97 | 03-OCT-05:03 | 9361.77 | 9361.77 | 9.96 | 68.12 |
November | 0.258370E+09 | 0.232533E+09 | 11169.16 | 02-NOV-14:10 | 10052.24 | 10052.24 | 11.45 | 70.04 |
December | 63720176.36 | 57348158.72 | 623.75 | 22-DEC-16:20 | 561.38 | 561.38 | 6.71 | 20.54 |
Annual Sum or Average | 0.762154E+10 | 0.685938E+10 | ||||||
Minimum of Months | 32862954.23 | 29576658.81 | 466.01 | 419.41 | 419.41 | 6.70 | 17.90 | |
Maximum of Months | 0.158877E+10 | 0.142990E+10 | 11169.16 | 10052.24 | 10052.24 | 11.51 | 70.04 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.458071E+10 | 0.412264E+10 | 4037.67 | 01-JAN-13:13 | 3633.90 | 3633.90 | 6.75 | 35.72 |
February | 0.312454E+10 | 0.281209E+10 | 4037.67 | 01-FEB-12:10 | 3633.90 | 3633.90 | 6.74 | 35.72 |
March | 0.535036E+10 | 0.481532E+10 | 4037.67 | 01-MAR-07:12 | 3633.90 | 3633.90 | 6.80 | 35.72 |
April | 0.808297E+10 | 0.727467E+10 | 4037.67 | 01-APR-04:12 | 3633.90 | 3633.90 | 6.90 | 35.72 |
May | 0.784393E+10 | 0.705954E+10 | 4037.67 | 01-MAY-00:05 | 3633.90 | 3633.90 | 6.84 | 35.72 |
June | 0.941968E+10 | 0.847772E+10 | 4037.67 | 01-JUN-00:42 | 3633.90 | 3633.90 | 6.97 | 35.72 |
July | 0.996502E+10 | 0.896852E+10 | 4037.67 | 01-JUL-00:03 | 3633.90 | 3633.90 | 9.63 | 35.72 |
August | 0.992889E+10 | 0.893600E+10 | 4037.67 | 01-AUG-00:03 | 3633.90 | 3633.90 | 7.11 | 35.72 |
September | 0.831190E+10 | 0.748071E+10 | 4037.67 | 01-SEP-00:05 | 3633.90 | 3633.90 | 7.00 | 35.72 |
October | 0.665542E+10 | 0.598988E+10 | 4037.67 | 01-OCT-01:03 | 3633.90 | 3633.90 | 7.14 | 35.72 |
November | 0.478257E+10 | 0.430432E+10 | 4037.67 | 01-NOV-04:12 | 3633.90 | 3633.90 | 8.99 | 35.72 |
December | 0.350769E+10 | 0.315693E+10 | 4037.67 | 01-DEC-09:30 | 3633.90 | 3633.90 | 6.81 | 35.72 |
Annual Sum or Average | 0.815537E+11 | 0.733983E+11 | ||||||
Minimum of Months | 0.312454E+10 | 0.281209E+10 | 4037.67 | 3633.90 | 3633.90 | 6.74 | 35.72 | |
Maximum of Months | 0.996502E+10 | 0.896852E+10 | 4037.67 | 3633.90 | 3633.90 | 9.63 | 35.72 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 67832865.81 | 61049579.23 | 4037.67 | 27-JAN-14:30 | 3633.90 | 3633.90 | 14.53 | 17.86 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
March | 0.125975E+09 | 0.113378E+09 | 4037.67 | 15-MAR-14:50 | 3633.90 | 3633.90 | 14.31 | 17.86 |
April | 0.182301E+10 | 0.164071E+10 | 4037.67 | 03-APR-10:10 | 3633.90 | 3633.90 | 14.73 | 17.86 |
May | 0.268485E+10 | 0.241636E+10 | 4037.67 | 01-MAY-10:30 | 3633.90 | 3633.90 | 14.47 | 17.86 |
June | 0.379380E+10 | 0.341442E+10 | 4037.67 | 01-JUN-07:30 | 3633.90 | 3633.90 | 14.47 | 17.86 |
July | 0.335470E+10 | 0.301923E+10 | 4037.67 | 01-JUL-09:30 | 3633.90 | 3633.90 | 14.41 | 17.86 |
August | 0.346307E+10 | 0.311676E+10 | 4037.67 | 01-AUG-05:05 | 3633.90 | 3633.90 | 15.82 | 17.86 |
September | 0.260442E+10 | 0.234398E+10 | 4037.67 | 01-SEP-04:05 | 3633.90 | 3633.90 | 14.88 | 17.86 |
October | 0.125572E+10 | 0.113014E+10 | 4037.67 | 02-OCT-07:50 | 3633.90 | 3633.90 | 15.57 | 17.86 |
November | 0.190174E+09 | 0.171157E+09 | 4037.67 | 01-NOV-12:40 | 3633.90 | 3633.90 | 15.41 | 17.86 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
Annual Sum or Average | 0.193635E+11 | 0.174272E+11 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.72 | 0.00 | |
Maximum of Months | 0.379380E+10 | 0.341442E+10 | 4037.67 | 3633.90 | 3633.90 | 15.82 | 17.86 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.103451E+11 | 0.931061E+10 | 3862.43 | 01-JAN-00:10 | 3476.18 | 3476.18 | 18.66 | 16.13 |
February | 0.934398E+10 | 0.840958E+10 | 3862.43 | 01-FEB-00:10 | 3476.18 | 3476.18 | 19.43 | 16.13 |
March | 0.103451E+11 | 0.931061E+10 | 3862.43 | 01-MAR-00:10 | 3476.18 | 3476.18 | 19.81 | 16.13 |
April | 0.100114E+11 | 0.901027E+10 | 3862.43 | 01-APR-00:10 | 3476.18 | 3476.18 | 21.68 | 16.13 |
May | 0.103451E+11 | 0.931061E+10 | 3862.43 | 01-MAY-00:05 | 3476.18 | 3476.18 | 20.34 | 16.13 |
June | 0.100114E+11 | 0.901027E+10 | 3862.43 | 01-JUN-00:03 | 3476.18 | 3476.18 | 33.97 | 16.13 |
July | 0.103451E+11 | 0.931061E+10 | 3862.43 | 01-JUL-00:03 | 3476.18 | 3476.18 | 40.39 | 16.13 |
August | 0.103451E+11 | 0.931061E+10 | 3862.43 | 01-AUG-00:03 | 3476.18 | 3476.18 | 45.75 | 16.13 |
September | 0.100114E+11 | 0.901027E+10 | 3862.43 | 01-SEP-00:05 | 3476.18 | 3476.18 | 31.48 | 16.13 |
October | 0.103451E+11 | 0.931061E+10 | 3862.43 | 01-OCT-00:03 | 3476.18 | 3476.18 | 32.30 | 16.13 |
November | 0.100114E+11 | 0.901027E+10 | 3862.43 | 01-NOV-00:10 | 3476.18 | 3476.18 | 20.46 | 16.13 |
December | 0.103451E+11 | 0.931061E+10 | 3862.43 | 01-DEC-00:10 | 3476.18 | 3476.18 | 20.34 | 16.13 |
Annual Sum or Average | 0.121805E+12 | 0.109625E+12 | ||||||
Minimum of Months | 0.934398E+10 | 0.840958E+10 | 3862.43 | 3476.18 | 3476.18 | 18.66 | 16.13 | |
Maximum of Months | 0.103451E+11 | 0.931061E+10 | 3862.43 | 3476.18 | 3476.18 | 45.75 | 16.13 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:05 | 16.86 | 16.86 | 57.43 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:02 | 16.86 | 16.86 | 57.52 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:02 | 16.86 | 16.86 | 57.59 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:03 | 16.86 | 16.86 | 57.70 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 58.04 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 58.10 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 58.23 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 58.26 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:02 | 16.86 | 16.86 | 58.23 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:03 | 16.86 | 16.86 | 58.02 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:03 | 16.86 | 16.86 | 57.75 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:02 | 16.86 | 16.86 | 57.67 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 57.43 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 58.26 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.178494E+11 | 0.160645E+11 | 31333.20 | 31-JAN-15:40 | 28199.88 | 28199.88 | 25.62 | 126.60 |
February | 0.120878E+11 | 0.108790E+11 | 15645.39 | 22-FEB-16:00 | 14080.85 | 14080.85 | 23.84 | 63.30 |
March | 0.208810E+11 | 0.187929E+11 | 31333.42 | 20-MAR-14:40 | 28200.08 | 28200.08 | 25.63 | 126.60 |
April | 0.361411E+11 | 0.325270E+11 | 31340.73 | 14-APR-14:30 | 28206.66 | 28206.66 | 25.90 | 126.60 |
May | 0.378360E+11 | 0.340524E+11 | 31344.56 | 18-MAY-14:10 | 28210.10 | 28210.10 | 26.05 | 126.60 |
June | 0.496235E+11 | 0.446612E+11 | 31413.05 | 17-JUN-16:00 | 28271.75 | 28271.75 | 28.65 | 126.60 |
July | 0.503679E+11 | 0.453312E+11 | 31434.01 | 14-JUL-05:02 | 28290.61 | 28290.61 | 29.61 | 126.60 |
August | 0.511258E+11 | 0.460132E+11 | 31434.01 | 01-AUG-14:00 | 28290.61 | 28290.61 | 29.46 | 126.60 |
September | 0.414950E+11 | 0.373455E+11 | 31434.01 | 01-SEP-10:50 | 28290.61 | 28290.61 | 29.45 | 126.60 |
October | 0.298175E+11 | 0.268357E+11 | 31403.24 | 03-OCT-09:40 | 28262.92 | 28262.92 | 28.28 | 126.60 |
November | 0.190110E+11 | 0.171099E+11 | 31339.23 | 02-NOV-14:20 | 28205.30 | 28205.30 | 25.85 | 126.60 |
December | 0.135757E+11 | 0.122181E+11 | 15672.14 | 22-DEC-16:20 | 14104.93 | 14104.93 | 26.04 | 63.30 |
Annual Sum or Average | 0.379812E+12 | 0.341830E+12 | ||||||
Minimum of Months | 0.120878E+11 | 0.108790E+11 | 15645.39 | 14080.85 | 14080.85 | 23.84 | 63.30 | |
Maximum of Months | 0.511258E+11 | 0.460132E+11 | 31434.01 | 28290.61 | 28290.61 | 29.61 | 126.60 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 177029.29 | 1512812.65 | 31-JAN-15:30 | 16.82 | 9.24 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 45297.48 | 644185.74 | 22-FEB-16:00 | 11.00 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 171798.47 | 1479405.89 | 16-MAR-13:30 | 16.60 | 9.35 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 468855.40 | 1717162.81 | 24-APR-10:25 | 12.44 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 574482.36 | 1769782.03 | 20-MAY-16:02 | 12.62 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 766057.93 | 1919287.70 | 19-JUN-14:10 | 13.12 | 6.70 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 731805.96 | 3288108.25 | 18-JUL-05:04 | 17.70 | 9.25 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 745916.40 | 2078835.46 | 28-AUG-16:20 | 13.65 | 6.70 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 642513.59 | 2648098.57 | 01-SEP-05:04 | 15.56 | 7.11 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 368662.68 | 1684818.99 | 04-OCT-15:00 | 12.33 | 6.70 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 189102.16 | 1526978.95 | 20-NOV-16:20 | 16.92 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 88327.31 | 1139430.02 | 22-DEC-16:20 | 14.32 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 416062.74 | 0.00 | ||||||
Minimum of Months | 45297.48 | 644185.74 | 11.00 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 766057.93 | 3288108.25 | 17.70 | 9.35 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 175390.49 | 1490654.94 | 31-JAN-16:20 | 20.93 | 7.36 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 44163.92 | 641939.10 | 22-FEB-16:00 | 19.97 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 170059.64 | 1453937.89 | 17-MAR-13:10 | 14.88 | 7.98 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 461708.25 | 1604150.68 | 14-APR-15:20 | 23.02 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 566224.26 | 1663045.28 | 08-MAY-04:12 | 22.36 | 6.70 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 758755.37 | 2149602.87 | 28-JUN-05:02 | 22.57 | 6.70 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 727292.28 | 3848482.64 | 14-JUL-04:03 | 20.21 | 13.10 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 742347.16 | 3291051.25 | 04-AUG-05:02 | 18.25 | 12.18 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 639864.08 | 3490291.97 | 05-SEP-03:02 | 18.95 | 12.51 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 365091.30 | 3406343.17 | 03-OCT-04:12 | 18.66 | 12.37 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 188246.56 | 2641192.36 | 02-NOV-14:10 | 15.71 | 11.43 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 87244.98 | 1139200.69 | 22-DEC-16:20 | 19.97 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 412430.06 | 0.00 | ||||||
Minimum of Months | 44163.92 | 641939.10 | 14.88 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 758755.37 | 3848482.64 | 23.02 | 13.10 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 111831.53 | 925818.73 | 31-JAN-17:00 | 34.65 | 30.48 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 64620.71 | 428016.13 | 18-FEB-14:10 | 25.94 | 23.02 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 277889.14 | 1333353.71 | 16-MAR-16:00 | 41.68 | 32.20 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 982103.36 | 1945534.35 | 14-APR-16:10 | 52.06 | 39.56 | 0.00 | 0.00 | 01-APR-00:10 |
May | 675745.32 | 1418309.13 | 31-MAY-16:00 | 43.13 | 38.62 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 1228927.89 | 1973319.11 | 28-JUN-16:00 | 52.53 | 44.82 | 0.00 | 0.00 | 01-JUN-00:03 |
July | 1453969.49 | 2078167.01 | 19-JUL-14:00 | 54.29 | 43.83 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 1627669.46 | 2324669.39 | 25-AUG-16:10 | 58.40 | 45.69 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 786361.26 | 1507957.32 | 08-SEP-16:00 | 44.66 | 39.98 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 483735.79 | 1620547.59 | 01-OCT-14:00 | 46.57 | 39.54 | 0.00 | 0.00 | 01-OCT-00:03 |
November | 267655.69 | 1343606.59 | 01-NOV-15:00 | 41.85 | 32.39 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 248653.17 | 1331515.71 | 21-DEC-15:00 | 41.64 | 30.13 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 687740.10 | 0.00 | ||||||
Minimum of Months | 64620.71 | 428016.13 | 25.94 | 23.02 | 0.00 | 0.00 | ||
Maximum of Months | 1627669.46 | 2324669.39 | 58.40 | 45.69 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 58.42 | 58.42 | 12201.44 | 43368.99 | 23-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 57.99 | 57.99 | 12156.54 | 43288.06 | 01-FEB-12:20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 58.05 | 58.05 | 12299.88 | 42042.02 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 58.17 | 58.17 | 10623.06 | 39019.98 | 03-APR-12:00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 58.69 | 58.69 | 9983.11 | 35812.03 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:03 | 58.49 | 58.49 | 9374.21 | 32497.38 | 01-JUN-12:00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 58.60 | 58.60 | 8239.12 | 30277.62 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 58.62 | 58.62 | 9159.04 | 31173.29 | 31-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 58.57 | 58.57 | 9185.45 | 33782.14 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:03 | 58.44 | 58.44 | 10072.05 | 37424.18 | 31-OCT-11:40 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 58.27 | 58.27 | 11192.15 | 40635.45 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 58.12 | 58.12 | 11535.83 | 42745.22 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 10492.70 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.99 | 57.99 | 8239.12 | 30277.62 | ||
Maximum of Months | 0.00 | 0.00 | 58.69 | 58.69 | 12299.88 | 43368.99 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 196641.98 | 2389857.78 | 31-JAN-15:40 | 25.62 | 21.10 | 1183.34 | 102895.17 | 30-JAN-09:50 |
February | 46012.96 | 725252.44 | 22-FEB-16:00 | 23.84 | 21.10 | 2421.55 | 110037.10 | 03-FEB-09:50 |
March | 189039.09 | 2394237.78 | 20-MAR-14:40 | 25.63 | 21.10 | 2360.20 | 110827.95 | 25-MAR-09:50 |
April | 548990.64 | 2541589.09 | 14-APR-14:30 | 25.90 | 21.22 | 2571.10 | 101498.87 | 23-APR-00:50 |
May | 691043.90 | 2618718.93 | 18-MAY-14:10 | 26.05 | 21.10 | 436.68 | 82459.55 | 22-MAY-05:30 |
June | 1042471.37 | 3995713.26 | 17-JUN-16:00 | 28.65 | 25.96 | 454.97 | 66078.64 | 13-JUN-04:10 |
July | 1322353.98 | 5277956.28 | 14-JUL-05:03 | 31.07 | 26.50 | 256.11 | 63170.53 | 03-JUL-03:10 |
August | 1346271.80 | 4655595.43 | 16-AUG-11:00 | 29.90 | 26.15 | 268.94 | 61348.98 | 25-AUG-03:40 |
September | 1086629.25 | 4812874.21 | 01-SEP-12:20 | 30.19 | 26.27 | 35.02 | 30448.20 | 30-SEP-01:45 |
October | 493379.54 | 3798818.47 | 03-OCT-09:40 | 28.28 | 24.77 | 1145.33 | 127547.86 | 25-OCT-05:50 |
November | 215597.53 | 2511303.27 | 02-NOV-14:20 | 25.85 | 21.58 | 1137.81 | 115429.94 | 29-NOV-07:11 |
December | 95153.29 | 1307522.15 | 22-DEC-16:20 | 26.04 | 21.10 | 2094.69 | 136725.36 | 05-DEC-06:30 |
Annual Sum or Average | 609450.46 | 1188.70 | ||||||
Minimum of Months | 46012.96 | 725252.44 | 23.84 | 21.10 | 35.02 | 30448.20 | ||
Maximum of Months | 1346271.80 | 5277956.28 | 31.07 | 26.50 | 2571.10 | 136725.36 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.421981E+11 | 0.671424E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.108052E+11 | 0.587191E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.456138E+11 | 0.885645E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.120107E+12 | 0.142200E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.149453E+12 | 0.169285E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.218329E+12 | 0.240502E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.237553E+12 | 0.249662E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.253621E+12 | 0.270817E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.189311E+12 | 0.184490E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.102048E+12 | 0.120574E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.496432E+11 | 0.870030E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.246260E+11 | 0.781075E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.144331E+13 | 0.175707E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.108052E+11 | 0.587191E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.253621E+12 | 0.270817E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.345655E+12 | 0.503721E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.811817E+11 | 0.428343E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.333575E+12 | 0.579272E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.889614E+12 | 0.874905E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.115928E+13 | 0.106088E+12 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.153406E+13 | 0.128582E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.147548E+13 | 0.115664E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.150023E+13 | 0.120174E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.124531E+13 | 0.948133E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.724364E+12 | 0.679557E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.345475E+12 | 0.512309E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.172492E+12 | 0.627849E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.980671E+13 | 0.985917E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.811817E+11 | 0.428343E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.153406E+13 | 0.128582E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.310552E+11 | 0.688120E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.660719E+10 | 0.632956E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.322661E+11 | 0.657417E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.970296E+11 | 0.858238E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.127870E+12 | 0.107367E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.174753E+12 | 0.141632E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.166823E+12 | 0.125571E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.167034E+12 | 0.128374E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.134939E+12 | 0.968063E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.738619E+11 | 0.666638E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.310150E+11 | 0.593159E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.141798E+11 | 0.109409E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.105743E+13 | 0.111881E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.660719E+10 | 0.593159E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.174753E+12 | 0.141632E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.315537E+11 | 0.141357E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.849904E+10 | 0.116190E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.316547E+11 | 0.105387E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.542250E+11 | 0.118039E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.342397E+11 | 0.567056E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.556507E+10 | 0.723998E+09 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.374088E+10 | 0.487793E+09 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.609651E+10 | 0.729848E+09 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.261624E+11 | 0.361521E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.455367E+11 | 0.119707E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.360178E+11 | 0.145706E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.172057E+11 | 0.143515E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.300497E+12 | 0.100218E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.374088E+10 | 0.487793E+09 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.542250E+11 | 0.145706E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.398634E+11 | 0.323283E+12 | 0.00 | 71.38 |
February | 0.00 | 0.00 | 0.132869E+11 | 0.206843E+12 | 0.00 | 34.93 |
March | 0.00 | 0.00 | 0.225083E+12 | 0.369813E+12 | 0.00 | 71.78 |
April | 0.00 | 0.00 | 0.952182E+12 | 0.567397E+12 | 0.00 | 74.29 |
May | 0.00 | 0.00 | 0.314092E+12 | 0.349780E+12 | 0.00 | 52.56 |
June | 0.00 | 0.00 | 0.744024E+12 | 0.397615E+12 | 0.00 | 25.19 |
July | 0.00 | 0.00 | 0.121142E+13 | 0.461380E+12 | 0.00 | 7.65 |
August | 0.00 | 0.00 | 0.153930E+13 | 0.534907E+12 | 0.00 | 5.95 |
September | 0.00 | 0.00 | 0.373024E+12 | 0.236321E+12 | 0.00 | 7.54 |
October | 0.00 | 0.00 | 0.331059E+12 | 0.365726E+12 | 0.00 | 58.99 |
November | 0.00 | 0.00 | 0.217894E+12 | 0.345601E+12 | 0.00 | 65.06 |
December | 0.00 | 0.00 | 0.223585E+12 | 0.439161E+12 | 0.00 | 97.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.618481E+13 | 0.459783E+13 | 0.00 | 572.98 |
Minimum of Months | 0.00 | 0.00 | 0.132869E+11 | 0.206843E+12 | 0.00 | 5.95 |
Maximum of Months | 0.00 | 0.00 | 0.153930E+13 | 0.567397E+12 | 0.00 | 97.67 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.700886E+10 | 0.306115E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.116638E+11 | 0.365928E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.197205E+11 | 0.546580E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.263168E+11 | 0.763534E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.884242E+10 | 0.390154E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.159892E+11 | 0.598207E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.231882E+11 | 0.765942E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.290903E+11 | 0.897756E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.874158E+10 | 0.373262E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.145248E+11 | 0.482456E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.193090E+11 | 0.533641E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.256774E+11 | 0.655303E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.210073E+12 | 0.667888E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.700886E+10 | 0.306115E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.290903E+11 | 0.897756E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.535506E+11 | 0.265643E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.988240E+11 | 0.326843E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.179242E+12 | 0.506061E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.249665E+12 | 0.726495E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.807706E+11 | 0.363802E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.149196E+12 | 0.562302E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.216619E+12 | 0.719881E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.274077E+12 | 0.849932E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.790066E+11 | 0.345848E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.131520E+12 | 0.446454E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.173780E+12 | 0.490777E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.229213E+12 | 0.598351E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.191546E+13 | 0.620239E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.535506E+11 | 0.265643E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.274077E+12 | 0.849932E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.422352E+10 | 0.246275E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.870348E+10 | 0.308649E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.171590E+11 | 0.496866E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.250387E+11 | 0.734536E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.813855E+10 | 0.369866E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.151674E+11 | 0.573253E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.219314E+11 | 0.731357E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.276792E+11 | 0.862328E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.802259E+10 | 0.352762E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.127138E+11 | 0.442406E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.163865E+11 | 0.477197E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.213557E+11 | 0.575552E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.186520E+12 | 0.617105E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.422352E+10 | 0.246275E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.276792E+11 | 0.862328E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.671090E+10 | 0.421981E+11 | 3342231.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.587183E+10 | 0.108052E+11 | 78717.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.881741E+10 | 0.456138E+11 | 39048699.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142200E+11 | 0.120107E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169285E+11 | 0.149453E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.240502E+11 | 0.218329E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.249662E+11 | 0.237553E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.270817E+11 | 0.253621E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.184490E+11 | 0.189311E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120574E+11 | 0.102048E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.870030E+10 | 0.496432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.759778E+10 | 0.246260E+11 | 0.212972E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175451E+12 | 0.144331E+13 | 0.255442E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.587183E+10 | 0.108052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.270817E+11 | 0.253621E+12 | 0.212972E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.448103E+11 | 0.345655E+12 | 0.556179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.373992E+11 | 0.811817E+11 | 0.543517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.527765E+11 | 0.333575E+12 | 0.515067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.874905E+11 | 0.889614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106088E+12 | 0.115928E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128582E+12 | 0.153406E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.115664E+12 | 0.147548E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.120174E+12 | 0.150023E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.948133E+11 | 0.124531E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.675192E+11 | 0.724364E+12 | 0.436516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.484357E+11 | 0.345475E+12 | 0.279526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.401750E+11 | 0.172492E+12 | 0.226099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.943928E+12 | 0.980671E+13 | 0.419893E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.373992E+11 | 0.811817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.128582E+12 | 0.153406E+13 | 0.226099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.387954E+10 | 0.310552E+11 | 0.300166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.312472E+10 | 0.660719E+10 | 0.320484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.440753E+10 | 0.322661E+11 | 0.216664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.856427E+10 | 0.970296E+11 | 18108103.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.107367E+11 | 0.127870E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.141632E+11 | 0.174753E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.125571E+11 | 0.166823E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.128374E+11 | 0.167034E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.968063E+10 | 0.134939E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.610586E+10 | 0.738619E+11 | 0.560522E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.404445E+10 | 0.310150E+11 | 0.188715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.341955E+10 | 0.141798E+11 | 0.752136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.935210E+11 | 0.105743E+13 | 0.183603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.312472E+10 | 0.660719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141632E+11 | 0.174753E+12 | 0.752136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.141336E+11 | 0.315537E+11 | 2030509.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116149E+11 | 0.849904E+10 | 4082725.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.105266E+11 | 0.316547E+11 | 12174995.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.118039E+11 | 0.542250E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.567056E+10 | 0.342397E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.723998E+09 | 0.556507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.487793E+09 | 0.374088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.729848E+09 | 0.609651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.361521E+10 | 0.261624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.119707E+11 | 0.455367E+11 | 10097.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145706E+11 | 0.360178E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143489E+11 | 0.172057E+11 | 2653807.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100197E+12 | 0.300497E+12 | 20952134.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.487793E+09 | 0.374088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145706E+11 | 0.542250E+11 | 12174995.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.118891E+12 | 0.273486E+11 | 0.00 | 0.00 | 0.00 | 0.191017E+12 | 0.00 | 0.00 |
February | 0.107386E+12 | 0.771774E+10 | 0.00 | 0.00 | 0.00 | 0.934677E+11 | 0.00 | 0.00 |
March | 0.118891E+12 | 0.167126E+12 | 0.00 | 0.00 | 0.00 | 0.192101E+12 | 0.00 | 0.00 |
April | 0.115056E+12 | 0.699541E+12 | 0.00 | 0.00 | 0.00 | 0.198804E+12 | 0.00 | 0.00 |
May | 0.118891E+12 | 0.224488E+12 | 0.00 | 0.00 | 0.00 | 0.140651E+12 | 0.00 | 0.00 |
June | 0.115056E+12 | 0.529188E+12 | 0.00 | 0.00 | 0.00 | 0.674198E+11 | 0.00 | 0.00 |
July | 0.118891E+12 | 0.889486E+12 | 0.00 | 0.00 | 0.00 | 0.204667E+11 | 0.00 | 0.00 |
August | 0.118891E+12 | 0.113928E+13 | 0.00 | 0.00 | 0.00 | 0.159269E+11 | 0.00 | 0.00 |
September | 0.115056E+12 | 0.272038E+12 | 0.00 | 0.00 | 0.00 | 0.201874E+11 | 0.00 | 0.00 |
October | 0.118891E+12 | 0.242803E+12 | 0.00 | 0.00 | 0.00 | 0.157868E+12 | 0.00 | 0.00 |
November | 0.115056E+12 | 0.162237E+12 | 0.00 | 0.00 | 0.00 | 0.174103E+12 | 0.00 | 0.00 |
December | 0.118891E+12 | 0.165856E+12 | 0.00 | 0.00 | 0.00 | 0.261364E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.139985E+13 | 0.452711E+13 | 0.00 | 0.00 | 0.00 | 0.153338E+13 | 0.00 | 0.00 |
Minimum of Months | 0.107386E+12 | 0.771774E+10 | 0.00 | 0.00 | 0.00 | 0.159269E+11 | 0.00 | 0.00 |
Maximum of Months | 0.118891E+12 | 0.113928E+13 | 0.00 | 0.00 | 0.00 | 0.261364E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.155827E+10 | 0.550598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140747E+10 | 0.941202E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155827E+10 | 0.158129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150801E+10 | 0.201894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.155827E+10 | 0.649915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.150801E+10 | 0.115151E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155827E+10 | 0.170870E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.155827E+10 | 0.216710E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150801E+10 | 0.651696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155827E+10 | 0.112585E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150801E+10 | 0.154806E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155827E+10 | 0.206826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183474E+11 | 0.161631E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.140747E+10 | 0.550598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.155827E+10 | 0.216710E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.148642E+11 | 0.418504E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134257E+11 | 0.795654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148642E+11 | 0.143500E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143847E+11 | 0.191400E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.148642E+11 | 0.592546E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.143847E+11 | 0.107351E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.148642E+11 | 0.159495E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.148642E+11 | 0.203948E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143847E+11 | 0.588064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148642E+11 | 0.101739E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143847E+11 | 0.139087E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148642E+11 | 0.184243E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175013E+12 | 0.147024E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134257E+11 | 0.418504E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.148642E+11 | 0.203948E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.152043E+10 | 0.328120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137329E+10 | 0.699028E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152043E+10 | 0.137108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147138E+10 | 0.191647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.152043E+10 | 0.596032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147138E+10 | 0.109063E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.152043E+10 | 0.161383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.152043E+10 | 0.205764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147138E+10 | 0.596635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152043E+10 | 0.981020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147138E+10 | 0.130859E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152043E+10 | 0.171206E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179018E+11 | 0.142711E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137329E+10 | 0.328120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.152043E+10 | 0.205764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.671090E+10 | 0.00 | 0.421981E+11 | 0.00 | 0.00 | 3342231.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.587183E+10 | 0.00 | 0.108052E+11 | 0.00 | 0.00 | 78717.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.881741E+10 | 0.00 | 0.456138E+11 | 0.00 | 0.00 | 39048699.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142200E+11 | 0.00 | 0.120107E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169285E+11 | 0.00 | 0.149453E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.240502E+11 | 0.00 | 0.218329E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.249662E+11 | 0.00 | 0.237553E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.270817E+11 | 0.00 | 0.253621E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.184490E+11 | 0.00 | 0.189311E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120574E+11 | 0.00 | 0.102048E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.870030E+10 | 0.00 | 0.496432E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.759778E+10 | 0.00 | 0.246260E+11 | 0.00 | 0.00 | 0.212972E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175451E+12 | 0.00 | 0.144331E+13 | 0.00 | 0.00 | 0.255442E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.587183E+10 | 0.00 | 0.108052E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.270817E+11 | 0.00 | 0.253621E+12 | 0.00 | 0.00 | 0.212972E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.448103E+11 | 0.00 | 0.345655E+12 | 0.00 | 0.00 | 0.556179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.373992E+11 | 0.00 | 0.811817E+11 | 0.00 | 0.00 | 0.543517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.527765E+11 | 0.00 | 0.333575E+12 | 0.00 | 0.00 | 0.515067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.874905E+11 | 0.00 | 0.889614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.106088E+12 | 0.00 | 0.115928E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128582E+12 | 0.00 | 0.153406E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.115664E+12 | 0.00 | 0.147548E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.120174E+12 | 0.00 | 0.150023E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.948133E+11 | 0.00 | 0.124531E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.675192E+11 | 0.00 | 0.724364E+12 | 0.00 | 0.00 | 0.436516E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.484357E+11 | 0.00 | 0.345475E+12 | 0.00 | 0.00 | 0.279526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.401750E+11 | 0.00 | 0.172492E+12 | 0.00 | 0.00 | 0.226099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.943928E+12 | 0.00 | 0.980671E+13 | 0.00 | 0.00 | 0.419893E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.373992E+11 | 0.00 | 0.811817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.128582E+12 | 0.00 | 0.153406E+13 | 0.00 | 0.00 | 0.226099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.387954E+10 | 0.00 | 0.310552E+11 | 0.00 | 0.00 | 0.300166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.312472E+10 | 0.00 | 0.660719E+10 | 0.00 | 0.00 | 0.320484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.440753E+10 | 0.00 | 0.322661E+11 | 0.00 | 0.00 | 0.216664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.856427E+10 | 0.00 | 0.970296E+11 | 0.00 | 0.00 | 18108103.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.107367E+11 | 0.00 | 0.127870E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.141632E+11 | 0.00 | 0.174753E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.125571E+11 | 0.00 | 0.166823E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.128374E+11 | 0.00 | 0.167034E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.968063E+10 | 0.00 | 0.134939E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.610586E+10 | 0.00 | 0.738619E+11 | 0.00 | 0.00 | 0.560522E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.404445E+10 | 0.00 | 0.310150E+11 | 0.00 | 0.00 | 0.188715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.341955E+10 | 0.00 | 0.141798E+11 | 0.00 | 0.00 | 0.752136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.935210E+11 | 0.00 | 0.105743E+13 | 0.00 | 0.00 | 0.183603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.312472E+10 | 0.00 | 0.660719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141632E+11 | 0.00 | 0.174753E+12 | 0.00 | 0.00 | 0.752136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.141336E+11 | 0.00 | 0.315537E+11 | 0.00 | 0.00 | 2030509.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.116149E+11 | 0.00 | 0.849904E+10 | 0.00 | 0.00 | 4082725.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.105266E+11 | 0.00 | 0.316547E+11 | 0.00 | 0.00 | 12174995.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.118039E+11 | 0.00 | 0.542250E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.567056E+10 | 0.00 | 0.342397E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.723998E+09 | 0.00 | 0.556507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.487793E+09 | 0.00 | 0.374088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.729848E+09 | 0.00 | 0.609651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.361521E+10 | 0.00 | 0.261624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.119707E+11 | 0.00 | 0.455367E+11 | 0.00 | 0.00 | 10097.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145706E+11 | 0.00 | 0.360178E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143489E+11 | 0.00 | 0.172057E+11 | 0.00 | 0.00 | 2653807.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.100197E+12 | 0.00 | 0.300497E+12 | 0.00 | 0.00 | 20952134.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.487793E+09 | 0.00 | 0.374088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145706E+11 | 0.00 | 0.542250E+11 | 0.00 | 0.00 | 12174995.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.118891E+12 | 0.00 | 0.398634E+11 | 0.00 | 0.125148E+11 | 0.00 | 0.00 | 0.00 | 0.191877E+12 | 0.00 | 0.00 | 0.00 |
February | 0.107386E+12 | 0.00 | 0.132869E+11 | 0.00 | 0.556914E+10 | 0.00 | 0.00 | 0.00 | 0.938885E+11 | 0.00 | 0.00 | 0.00 |
March | 0.118891E+12 | 0.00 | 0.225083E+12 | 0.00 | 0.579568E+11 | 0.00 | 0.00 | 0.00 | 0.192965E+12 | 0.00 | 0.00 | 0.00 |
April | 0.115056E+12 | 0.00 | 0.952182E+12 | 0.00 | 0.252642E+12 | 0.00 | 0.00 | 0.00 | 0.199699E+12 | 0.00 | 0.00 | 0.00 |
May | 0.118891E+12 | 0.00 | 0.314092E+12 | 0.00 | 0.896043E+11 | 0.00 | 0.00 | 0.00 | 0.141284E+12 | 0.00 | 0.00 | 0.00 |
June | 0.115056E+12 | 0.00 | 0.744024E+12 | 0.00 | 0.214836E+12 | 0.00 | 0.00 | 0.00 | 0.677233E+11 | 0.00 | 0.00 | 0.00 |
July | 0.118891E+12 | 0.00 | 0.121142E+13 | 0.00 | 0.321930E+12 | 0.00 | 0.00 | 0.00 | 0.205589E+11 | 0.00 | 0.00 | 0.00 |
August | 0.118891E+12 | 0.00 | 0.153930E+13 | 0.00 | 0.400017E+12 | 0.00 | 0.00 | 0.00 | 0.159986E+11 | 0.00 | 0.00 | 0.00 |
September | 0.115056E+12 | 0.00 | 0.373024E+12 | 0.00 | 0.100986E+12 | 0.00 | 0.00 | 0.00 | 0.202783E+11 | 0.00 | 0.00 | 0.00 |
October | 0.118891E+12 | 0.00 | 0.331059E+12 | 0.00 | 0.882559E+11 | 0.00 | 0.00 | 0.00 | 0.158578E+12 | 0.00 | 0.00 | 0.00 |
November | 0.115056E+12 | 0.00 | 0.217894E+12 | 0.00 | 0.556574E+11 | 0.00 | 0.00 | 0.00 | 0.174887E+12 | 0.00 | 0.00 | 0.00 |
December | 0.118891E+12 | 0.00 | 0.223585E+12 | 0.00 | 0.577289E+11 | 0.00 | 0.00 | 0.00 | 0.262541E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.139985E+13 | 0.00 | 0.618481E+13 | 0.00 | 0.165770E+13 | 0.00 | 0.00 | 0.00 | 0.154028E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.107386E+12 | 0.00 | 0.132869E+11 | 0.00 | 0.556914E+10 | 0.00 | 0.00 | 0.00 | 0.159986E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.118891E+12 | 0.00 | 0.153930E+13 | 0.00 | 0.400017E+12 | 0.00 | 0.00 | 0.00 | 0.262541E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.155827E+10 | 0.00 | 0.700886E+10 | 0.00 | 0.150288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140747E+10 | 0.00 | 0.116638E+11 | 0.00 | 0.225181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155827E+10 | 0.00 | 0.197205E+11 | 0.00 | 0.390753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150801E+10 | 0.00 | 0.263168E+11 | 0.00 | 0.612734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.155827E+10 | 0.00 | 0.884242E+10 | 0.00 | 0.234327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.150801E+10 | 0.00 | 0.159892E+11 | 0.00 | 0.447407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155827E+10 | 0.00 | 0.231882E+11 | 0.00 | 0.610114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.155827E+10 | 0.00 | 0.290903E+11 | 0.00 | 0.741929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150801E+10 | 0.00 | 0.874158E+10 | 0.00 | 0.222462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155827E+10 | 0.00 | 0.145248E+11 | 0.00 | 0.326629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150801E+10 | 0.00 | 0.193090E+11 | 0.00 | 0.382840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155827E+10 | 0.00 | 0.256774E+11 | 0.00 | 0.499476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183474E+11 | 0.00 | 0.210073E+12 | 0.00 | 0.484414E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.140747E+10 | 0.00 | 0.700886E+10 | 0.00 | 0.150288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.155827E+10 | 0.00 | 0.290903E+11 | 0.00 | 0.741929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.148642E+11 | 0.00 | 0.535506E+11 | 0.00 | 0.117001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134257E+11 | 0.00 | 0.988240E+11 | 0.00 | 0.192586E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148642E+11 | 0.00 | 0.179242E+12 | 0.00 | 0.357420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143847E+11 | 0.00 | 0.249665E+12 | 0.00 | 0.582649E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.148642E+11 | 0.00 | 0.807706E+11 | 0.00 | 0.215160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.143847E+11 | 0.00 | 0.149196E+12 | 0.00 | 0.418455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.148642E+11 | 0.00 | 0.216619E+12 | 0.00 | 0.571239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.148642E+11 | 0.00 | 0.274077E+12 | 0.00 | 0.701291E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143847E+11 | 0.00 | 0.790066E+11 | 0.00 | 0.202002E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148642E+11 | 0.00 | 0.131520E+12 | 0.00 | 0.297812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143847E+11 | 0.00 | 0.173780E+12 | 0.00 | 0.346931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148642E+11 | 0.00 | 0.229213E+12 | 0.00 | 0.449709E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175013E+12 | 0.00 | 0.191546E+13 | 0.00 | 0.445226E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134257E+11 | 0.00 | 0.535506E+11 | 0.00 | 0.117001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.148642E+11 | 0.00 | 0.274077E+12 | 0.00 | 0.701291E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.152043E+10 | 0.00 | 0.422352E+10 | 0.00 | 0.942321E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137329E+10 | 0.00 | 0.870348E+10 | 0.00 | 0.171320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152043E+10 | 0.00 | 0.171590E+11 | 0.00 | 0.344823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.147138E+10 | 0.00 | 0.250387E+11 | 0.00 | 0.587398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.152043E+10 | 0.00 | 0.813855E+10 | 0.00 | 0.217823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147138E+10 | 0.00 | 0.151674E+11 | 0.00 | 0.426115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.152043E+10 | 0.00 | 0.219314E+11 | 0.00 | 0.579314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.152043E+10 | 0.00 | 0.276792E+11 | 0.00 | 0.710285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147138E+10 | 0.00 | 0.802259E+10 | 0.00 | 0.205624E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152043E+10 | 0.00 | 0.127138E+11 | 0.00 | 0.290363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147138E+10 | 0.00 | 0.163865E+11 | 0.00 | 0.330059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152043E+10 | 0.00 | 0.213557E+11 | 0.00 | 0.423509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179018E+11 | 0.00 | 0.186520E+12 | 0.00 | 0.438087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137329E+10 | 0.00 | 0.422352E+10 | 0.00 | 0.942321E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.152043E+10 | 0.00 | 0.276792E+11 | 0.00 | 0.710285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 27272561.49 | 0.00 | 0.134503E+09 | 0.00 | 0.00 | 0.452521E+11 | 0.00 | 1.17 |
February | 0.00 | 0.00 | 0.00 | 0.106196E+09 | 0.00 | 0.00 | 0.544859E+11 | 0.00 | 1.13 |
March | 0.00 | 30464241.79 | 0.00 | 0.113489E+09 | 0.00 | 0.00 | 0.396598E+11 | 0.00 | 1.01 |
April | 0.00 | 0.184853E+10 | 0.00 | 77841388.16 | 0.00 | 0.00 | 0.135506E+11 | 0.00 | 0.56 |
May | 0.00 | 0.133700E+10 | 0.00 | 48088748.90 | 0.00 | 0.00 | 0.690446E+10 | 0.00 | 0.19 |
June | 0.00 | 0.345843E+09 | 0.00 | 14119233.97 | 0.00 | 0.00 | 0.877058E+09 | 0.00 | 0.02 |
July | 0.00 | 0.335420E+09 | 0.00 | 10860425.97 | 0.00 | 0.00 | 0.947452E+09 | 0.00 | 0.01 |
August | 0.00 | 0.364390E+09 | 0.00 | 7784766.16 | 0.00 | 0.00 | 0.109159E+10 | 0.00 | 0.02 |
September | 0.00 | 0.149046E+10 | 0.00 | 50589825.76 | 0.00 | 0.00 | 0.244704E+10 | 0.00 | 0.14 |
October | 0.00 | 0.773058E+09 | 0.00 | 0.148226E+09 | 0.00 | 0.00 | 0.272097E+11 | 0.00 | 0.82 |
November | 0.00 | 0.632573E+09 | 0.00 | 0.136708E+09 | 0.00 | 0.00 | 0.465542E+11 | 0.00 | 1.23 |
December | 0.00 | 1334067.61 | 0.00 | 0.139427E+09 | 0.00 | 0.00 | 0.623709E+11 | 0.00 | 1.20 |
Annual Sum or Average | 0.00 | 0.718635E+10 | 0.00 | 0.987833E+09 | 0.00 | 0.00 | 0.301351E+12 | 0.00 | 0.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 7784766.16 | 0.00 | 0.00 | 0.877058E+09 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.184853E+10 | 0.00 | 0.148226E+09 | 0.00 | 0.00 | 0.623709E+11 | 0.00 | 1.23 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.242577E+10 | 3013780.18 | 0.00 | 99266505.27 | 22234924.57 | 0.00 | 0.350757E+11 | 0.00 | 0.86 |
February | 0.225881E+10 | 0.00 | 0.00 | 85764065.69 | 0.00 | 0.00 | 0.455227E+11 | 0.00 | 0.90 |
March | 0.241079E+10 | 12113765.69 | 0.00 | 0.108120E+09 | 900391.65 | 0.00 | 0.417674E+11 | 0.00 | 1.00 |
April | 0.508736E+10 | 0.116060E+10 | 0.00 | 76828657.10 | 0.250477E+09 | 0.00 | 0.160817E+11 | 0.00 | 0.82 |
May | 0.121159E+10 | 0.248073E+10 | 0.00 | 64027121.66 | 0.185486E+09 | 0.00 | 0.887298E+10 | 0.00 | 0.58 |
June | 0.174834E+10 | 0.793624E+10 | 0.00 | 30321234.37 | 0.328477E+09 | 0.00 | 0.300754E+10 | 0.00 | 0.50 |
July | 0.956264E+09 | 0.130796E+11 | 0.00 | 15287818.44 | 0.133128E+10 | 0.00 | 0.100625E+10 | 0.00 | 0.48 |
August | 0.120830E+10 | 0.129532E+11 | 0.00 | 31113464.06 | 0.883228E+09 | 0.00 | 0.177247E+10 | 0.00 | 0.63 |
September | 0.549119E+09 | 0.863415E+10 | 0.00 | 45024170.53 | 0.167412E+10 | 0.00 | 0.396114E+10 | 0.00 | 0.65 |
October | 0.242873E+10 | 0.159747E+10 | 0.00 | 95398405.83 | 0.149144E+09 | 0.00 | 0.255202E+11 | 0.00 | 0.88 |
November | 0.239109E+10 | 72855325.68 | 0.00 | 0.112923E+09 | 25157602.51 | 0.00 | 0.395032E+11 | 0.00 | 1.01 |
December | 0.251933E+10 | 197260.55 | 0.00 | 0.113564E+09 | 1222304.71 | 0.00 | 0.506352E+11 | 0.00 | 0.93 |
Annual Sum or Average | 0.251955E+11 | 0.479302E+11 | 0.00 | 0.877639E+09 | 0.485174E+10 | 0.00 | 0.272726E+12 | 0.00 | 0.77 |
Minimum of Months | 0.549119E+09 | 0.00 | 0.00 | 15287818.44 | 0.00 | 0.00 | 0.100625E+10 | 0.00 | 0.48 |
Maximum of Months | 0.508736E+10 | 0.130796E+11 | 0.00 | 0.113564E+09 | 0.167412E+10 | 0.00 | 0.506352E+11 | 0.00 | 1.01 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.442823E+11 | 1489277.90 | 0.00 | 0.522468E+09 | 0.413933E+09 | 0.00 | 0.207671E+12 | 0.00 | 0.63 |
February | 0.566084E+11 | 0.00 | 0.00 | 0.431611E+09 | 0.00 | 0.00 | 0.275129E+12 | 0.00 | 0.65 |
March | 0.327994E+11 | 0.103192E+09 | 0.00 | 0.620145E+09 | 20860281.69 | 0.00 | 0.269225E+12 | 0.00 | 0.71 |
April | 0.114952E+11 | 0.116948E+11 | 0.00 | 0.524755E+09 | 0.244759E+10 | 0.00 | 0.108249E+12 | 0.00 | 0.53 |
May | 0.642488E+10 | 0.260344E+11 | 0.00 | 0.382008E+09 | 0.145621E+10 | 0.00 | 0.518911E+11 | 0.00 | 0.42 |
June | 0.565435E+10 | 0.776357E+11 | 0.00 | 0.112589E+09 | 0.235997E+10 | 0.00 | 0.138758E+11 | 0.00 | 0.33 |
July | 0.246603E+10 | 0.916991E+11 | 0.00 | 44246398.78 | 0.455343E+10 | 0.00 | 0.493708E+10 | 0.00 | 0.29 |
August | 0.281368E+10 | 0.858400E+11 | 0.00 | 94378717.42 | 0.310584E+10 | 0.00 | 0.836310E+10 | 0.00 | 0.35 |
September | 0.227173E+10 | 0.590579E+11 | 0.00 | 0.238850E+09 | 0.606404E+10 | 0.00 | 0.228485E+11 | 0.00 | 0.40 |
October | 0.128720E+11 | 0.130711E+11 | 0.00 | 0.550004E+09 | 0.124605E+10 | 0.00 | 0.165582E+12 | 0.00 | 0.59 |
November | 0.362784E+11 | 0.350154E+09 | 0.00 | 0.597111E+09 | 0.359127E+09 | 0.00 | 0.232772E+12 | 0.00 | 0.67 |
December | 0.726831E+11 | 7661313.70 | 0.00 | 0.429646E+09 | 6349471.38 | 0.00 | 0.236567E+12 | 0.00 | 0.57 |
Annual Sum or Average | 0.286649E+12 | 0.365495E+12 | 0.00 | 0.454781E+10 | 0.220334E+11 | 0.00 | 0.159711E+13 | 0.00 | 0.51 |
Minimum of Months | 0.227173E+10 | 0.00 | 0.00 | 44246398.78 | 0.00 | 0.00 | 0.493708E+10 | 0.00 | 0.29 |
Maximum of Months | 0.726831E+11 | 0.916991E+11 | 0.00 | 0.620145E+09 | 0.606404E+10 | 0.00 | 0.275129E+12 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.972809E+10 | 0.00 | 0.00 | 25259274.63 | 29841099.72 | 95393898.96 | 0.100874E+11 | 0.00 | 0.55 |
February | 0.111324E+11 | 0.00 | 0.00 | 20279674.64 | 261500.84 | 49298172.41 | 0.156560E+11 | 0.00 | 0.55 |
March | 0.816611E+10 | 3942563.11 | 0.00 | 38955101.72 | 811415.71 | 5994392.16 | 0.163037E+11 | 0.00 | 0.63 |
April | 0.207533E+10 | 0.782819E+09 | 0.00 | 48299850.17 | 0.208421E+09 | 0.00 | 0.756145E+10 | 0.00 | 0.50 |
May | 0.785111E+09 | 0.190428E+10 | 0.00 | 38870721.88 | 0.132989E+09 | 0.00 | 0.367556E+10 | 0.00 | 0.39 |
June | 0.551429E+09 | 0.681428E+10 | 0.00 | 10636689.44 | 0.243919E+09 | 0.00 | 0.113977E+10 | 0.00 | 0.32 |
July | 0.221213E+09 | 0.839004E+10 | 0.00 | 3949730.74 | 0.438051E+09 | 0.00 | 0.393677E+09 | 0.00 | 0.29 |
August | 0.245037E+09 | 0.779612E+10 | 0.00 | 8412909.38 | 0.318042E+09 | 0.00 | 0.612282E+09 | 0.00 | 0.34 |
September | 0.253276E+09 | 0.519516E+10 | 0.00 | 22930751.10 | 0.712311E+09 | 0.00 | 0.175575E+10 | 0.00 | 0.38 |
October | 0.352035E+10 | 0.103013E+10 | 0.00 | 38967884.92 | 0.160311E+09 | 0.00 | 0.102187E+11 | 0.00 | 0.52 |
November | 0.856272E+10 | 18151189.91 | 0.00 | 33537259.28 | 39932191.54 | 10777773.79 | 0.133418E+11 | 0.00 | 0.59 |
December | 0.148395E+11 | 0.00 | 0.00 | 13756810.16 | 9488882.59 | 0.106391E+09 | 0.870722E+10 | 0.00 | 0.48 |
Annual Sum or Average | 0.600806E+11 | 0.319349E+11 | 0.00 | 0.303857E+09 | 0.229438E+10 | 0.267855E+09 | 0.894534E+11 | 0.00 | 0.46 |
Minimum of Months | 0.221213E+09 | 0.00 | 0.00 | 3949730.74 | 261500.84 | 0.00 | 0.393677E+09 | 0.00 | 0.29 |
Maximum of Months | 0.148395E+11 | 0.839004E+10 | 0.00 | 48299850.17 | 0.712311E+09 | 0.106391E+09 | 0.163037E+11 | 0.00 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.184258E+10 | 348090.80 | 0.00 | 3906722.39 | 2824080.24 | 0.00 | 0.130819E+10 | 0.00 | 0.60 |
February | 0.192259E+10 | 0.00 | 0.00 | 3140761.02 | 0.00 | 0.00 | 0.211298E+10 | 0.00 | 0.62 |
March | 0.147588E+10 | 1768758.68 | 0.00 | 6605413.32 | 113146.00 | 0.00 | 0.245541E+10 | 0.00 | 0.77 |
April | 0.876503E+09 | 0.214244E+09 | 0.00 | 7408387.93 | 31475775.74 | 0.00 | 0.129694E+10 | 0.00 | 0.79 |
May | 0.231082E+09 | 0.489027E+09 | 0.00 | 6839320.42 | 23400421.09 | 0.00 | 0.925745E+09 | 0.00 | 0.65 |
June | 0.203278E+09 | 0.170198E+10 | 0.00 | 3918158.93 | 30054545.62 | 0.00 | 0.438789E+09 | 0.00 | 0.68 |
July | 0.123408E+09 | 0.236556E+10 | 0.00 | 1891734.69 | 0.147203E+09 | 0.00 | 0.133566E+09 | 0.00 | 0.61 |
August | 0.168296E+09 | 0.222455E+10 | 0.00 | 3354260.03 | 0.101280E+09 | 0.00 | 0.198207E+09 | 0.00 | 0.74 |
September | 90402302.64 | 0.144292E+10 | 0.00 | 4834772.04 | 0.188346E+09 | 0.00 | 0.416561E+09 | 0.00 | 0.72 |
October | 0.884529E+09 | 0.247386E+09 | 0.00 | 6663810.28 | 19256080.84 | 0.00 | 0.159852E+10 | 0.00 | 0.73 |
November | 0.148030E+10 | 3209728.11 | 0.00 | 6359259.91 | 6602700.60 | 0.00 | 0.207174E+10 | 0.00 | 0.72 |
December | 0.220497E+10 | 21220.92 | 0.00 | 3367894.41 | 153598.59 | 237232.98 | 0.178270E+10 | 0.00 | 0.58 |
Annual Sum or Average | 0.115038E+11 | 0.869102E+10 | 0.00 | 58290495.37 | 0.550710E+09 | 237232.98 | 0.147393E+11 | 0.00 | 0.69 |
Minimum of Months | 90402302.64 | 0.00 | 0.00 | 1891734.69 | 0.00 | 0.00 | 0.133566E+09 | 0.00 | 0.58 |
Maximum of Months | 0.220497E+10 | 0.236556E+10 | 0.00 | 7408387.93 | 0.188346E+09 | 237232.98 | 0.245541E+10 | 0.00 | 0.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.148679E+10 | 367533.91 | 0.00 | 5796485.79 | 2731619.78 | 0.00 | 0.228279E+10 | 0.00 | 1.04 |
February | 0.164181E+10 | 0.00 | 0.00 | 4388741.65 | 0.00 | 0.00 | 0.276875E+10 | 0.00 | 0.99 |
March | 0.134427E+10 | 1233849.39 | 0.00 | 7130144.80 | 110615.52 | 0.00 | 0.299340E+10 | 0.00 | 1.22 |
April | 0.895999E+09 | 0.169246E+09 | 0.00 | 9425347.99 | 30730514.92 | 0.00 | 0.181522E+10 | 0.00 | 1.41 |
May | 0.222477E+09 | 0.389167E+09 | 0.00 | 8970844.90 | 22638150.25 | 0.00 | 0.113558E+10 | 0.00 | 1.11 |
June | 0.232713E+09 | 0.135494E+10 | 0.00 | 2960416.96 | 30360148.29 | 0.00 | 0.324970E+09 | 0.00 | 0.93 |
July | 0.122206E+09 | 0.188828E+10 | 0.00 | 1536972.15 | 0.173638E+09 | 0.00 | 0.104969E+09 | 0.00 | 0.80 |
August | 0.176005E+09 | 0.180548E+10 | 0.00 | 2268341.38 | 0.117400E+09 | 0.00 | 0.143083E+09 | 0.00 | 0.96 |
September | 0.101132E+09 | 0.125006E+10 | 0.00 | 3808129.40 | 0.184551E+09 | 0.00 | 0.364297E+09 | 0.00 | 1.00 |
October | 0.829460E+09 | 0.209173E+09 | 0.00 | 7614075.62 | 18135764.08 | 0.00 | 0.209971E+10 | 0.00 | 1.21 |
November | 0.142018E+10 | 845614.62 | 0.00 | 6370336.91 | 8336140.18 | 0.00 | 0.237350E+10 | 0.00 | 1.11 |
December | 0.197000E+10 | 19544.38 | 0.00 | 3902212.24 | 150163.39 | 9155013.81 | 0.210757E+10 | 0.00 | 0.88 |
Annual Sum or Average | 0.104430E+11 | 0.706882E+10 | 0.00 | 64172049.80 | 0.588782E+09 | 9155013.81 | 0.185138E+11 | 0.00 | 1.05 |
Minimum of Months | 0.101132E+09 | 0.00 | 0.00 | 1536972.15 | 0.00 | 0.00 | 0.104969E+09 | 0.00 | 0.80 |
Maximum of Months | 0.197000E+10 | 0.188828E+10 | 0.00 | 9425347.99 | 0.184551E+09 | 9155013.81 | 0.299340E+10 | 0.00 | 1.41 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.931931E+09 | 4514730.41 | 0.00 | 24962020.54 | 1177967.42 | 0.00 | 0.682714E+10 | 0.00 | 1.72 |
February | 0.136476E+10 | 0.00 | 0.00 | 11545533.84 | 0.00 | 0.00 | 0.716835E+10 | 0.00 | 1.33 |
March | 0.131811E+10 | 2678879.37 | 0.00 | 13070574.12 | 126106.07 | 0.00 | 0.478257E+10 | 0.00 | 1.27 |
April | 0.102211E+10 | 0.323423E+09 | 0.00 | 9708451.11 | 35081100.97 | 0.00 | 0.151140E+10 | 0.00 | 1.00 |
May | 0.291443E+09 | 0.536821E+09 | 0.00 | 6184561.51 | 26204812.90 | 0.00 | 0.754069E+09 | 0.00 | 0.65 |
June | 0.276958E+09 | 0.163134E+10 | 0.00 | 2828494.42 | 37328991.08 | 0.00 | 0.311604E+09 | 0.00 | 0.63 |
July | 0.146485E+09 | 0.229446E+10 | 0.00 | 1495625.26 | 0.188907E+09 | 0.00 | 0.104740E+09 | 0.00 | 0.59 |
August | 0.196901E+09 | 0.243732E+10 | 0.00 | 2929738.93 | 0.122652E+09 | 0.00 | 0.176178E+09 | 0.00 | 0.77 |
September | 0.102025E+09 | 0.186081E+10 | 0.00 | 5485891.56 | 0.192020E+09 | 0.00 | 0.440871E+09 | 0.00 | 0.84 |
October | 0.759023E+09 | 0.392667E+09 | 0.00 | 16371255.19 | 17711225.08 | 0.00 | 0.369354E+10 | 0.00 | 1.34 |
November | 0.846063E+09 | 5253342.27 | 0.00 | 22851570.84 | 7358992.78 | 0.00 | 0.688869E+10 | 0.00 | 1.64 |
December | 0.133052E+10 | 695434.49 | 0.00 | 22996156.27 | 0.00 | 0.00 | 0.847421E+10 | 0.00 | 1.60 |
Annual Sum or Average | 0.858633E+10 | 0.948999E+10 | 0.00 | 0.140430E+09 | 0.628568E+09 | 0.00 | 0.411334E+11 | 0.00 | 1.11 |
Minimum of Months | 0.102025E+09 | 0.00 | 0.00 | 1495625.26 | 0.00 | 0.00 | 0.104740E+09 | 0.00 | 0.59 |
Maximum of Months | 0.136476E+10 | 0.243732E+10 | 0.00 | 24962020.54 | 0.192020E+09 | 0.00 | 0.847421E+10 | 0.00 | 1.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.156882E+10 | 2809682.21 | 0.00 | 7912139.60 | 1991015.03 | 0.00 | 0.267839E+10 | 0.00 | 1.36 |
February | 0.129971E+10 | 0.00 | 0.00 | 6838889.41 | 0.00 | 0.00 | 0.452518E+10 | 0.00 | 1.42 |
March | 0.693481E+09 | 2317659.69 | 0.00 | 13590343.42 | 0.00 | 0.00 | 0.504597E+10 | 0.00 | 1.83 |
April | 0.612184E+09 | 0.393070E+09 | 0.00 | 15070162.77 | 7473713.73 | 0.00 | 0.254998E+10 | 0.00 | 1.81 |
May | 0.243987E+09 | 0.606207E+09 | 0.00 | 6190962.24 | 14664249.27 | 0.00 | 0.834459E+09 | 0.00 | 0.99 |
June | 0.269699E+09 | 0.168084E+10 | 0.00 | 3022970.70 | 30983661.56 | 0.00 | 0.341830E+09 | 0.00 | 0.98 |
July | 0.122753E+09 | 0.210487E+10 | 0.00 | 1676329.62 | 0.171117E+09 | 0.00 | 0.148312E+09 | 0.00 | 0.87 |
August | 0.133606E+09 | 0.218889E+10 | 0.00 | 3595161.51 | 73351094.69 | 0.00 | 0.275660E+09 | 0.00 | 1.15 |
September | 0.116731E+09 | 0.116205E+10 | 0.00 | 3686353.54 | 0.283294E+09 | 0.00 | 0.347821E+09 | 0.00 | 0.98 |
October | 0.691222E+09 | 0.238284E+09 | 0.00 | 10733778.90 | 20357478.20 | 0.00 | 0.257675E+10 | 0.00 | 1.44 |
November | 0.609436E+09 | 13094200.40 | 0.00 | 13883378.91 | 2530967.49 | 0.00 | 0.474334E+10 | 0.00 | 1.73 |
December | 0.908585E+09 | 210185.69 | 0.00 | 12328989.44 | 77643.87 | 0.00 | 0.566942E+10 | 0.00 | 1.59 |
Annual Sum or Average | 0.727021E+10 | 0.839265E+10 | 0.00 | 98529460.06 | 0.605840E+09 | 0.00 | 0.297371E+11 | 0.00 | 1.35 |
Minimum of Months | 0.116731E+09 | 0.00 | 0.00 | 1676329.62 | 0.00 | 0.00 | 0.148312E+09 | 0.00 | 0.87 |
Maximum of Months | 0.156882E+10 | 0.218889E+10 | 0.00 | 15070162.77 | 0.283294E+09 | 0.00 | 0.566942E+10 | 0.00 | 1.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.228175E+11 | 126082.81 | 0.00 | 7089444.72 | 52036668.41 | 0.110937E+10 | 0.176222E+10 | 0.00 | 0.50 |
February | 0.273481E+11 | 0.00 | 0.00 | 3453531.71 | 0.00 | 0.161209E+10 | 0.296771E+10 | 0.00 | 0.49 |
March | 0.209722E+11 | 13251034.76 | 0.00 | 25023555.98 | 2622404.16 | 0.636696E+09 | 0.729449E+10 | 0.00 | 0.55 |
April | 0.627161E+10 | 0.232531E+10 | 0.00 | 42389341.65 | 0.247170E+09 | 0.00 | 0.579951E+10 | 0.00 | 0.52 |
May | 0.200363E+10 | 0.597516E+10 | 0.00 | 40137122.40 | 0.188528E+09 | 0.00 | 0.464954E+10 | 0.00 | 0.54 |
June | 0.658324E+09 | 0.221867E+11 | 0.00 | 18673160.61 | 0.245091E+09 | 0.00 | 0.240607E+10 | 0.00 | 0.62 |
July | 0.333768E+09 | 0.225243E+11 | 0.00 | 6676483.51 | 0.510281E+09 | 0.00 | 0.766346E+09 | 0.00 | 0.51 |
August | 0.388971E+09 | 0.192455E+11 | 0.00 | 11165180.63 | 0.324757E+09 | 0.00 | 0.101433E+10 | 0.00 | 0.53 |
September | 0.740976E+09 | 0.124878E+11 | 0.00 | 24735564.33 | 0.727602E+09 | 0.00 | 0.209169E+10 | 0.00 | 0.52 |
October | 0.113077E+11 | 0.231209E+10 | 0.00 | 26772911.53 | 0.120691E+09 | 2959562.65 | 0.537109E+10 | 0.00 | 0.50 |
November | 0.204854E+11 | 11466869.83 | 0.00 | 17958004.34 | 63381580.45 | 0.548056E+09 | 0.555792E+10 | 0.00 | 0.51 |
December | 0.273932E+11 | 0.00 | 0.00 | 774089.90 | 1536032.19 | 0.417933E+10 | 0.463132E+09 | 0.00 | 0.46 |
Annual Sum or Average | 0.140721E+12 | 0.870817E+11 | 0.00 | 0.224848E+09 | 0.248370E+10 | 0.808851E+10 | 0.401441E+11 | 0.00 | 0.52 |
Minimum of Months | 0.333768E+09 | 0.00 | 0.00 | 774089.90 | 0.00 | 0.00 | 0.463132E+09 | 0.00 | 0.46 |
Maximum of Months | 0.273932E+11 | 0.225243E+11 | 0.00 | 42389341.65 | 0.727602E+09 | 0.417933E+10 | 0.729449E+10 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.160621E+11 | 148333.21 | 0.00 | 27691396.10 | 53816541.97 | 0.650281E+09 | 0.128028E+11 | 0.00 | 0.88 |
February | 0.187415E+11 | 0.00 | 0.00 | 20817152.12 | 0.00 | 0.727418E+09 | 0.167203E+11 | 0.00 | 0.85 |
March | 0.154195E+11 | 11497956.77 | 0.00 | 48109253.64 | 2712101.44 | 0.576575E+09 | 0.199482E+11 | 0.00 | 1.04 |
April | 0.447920E+10 | 0.232730E+10 | 0.00 | 83759929.37 | 0.242581E+09 | 0.00 | 0.155309E+11 | 0.00 | 1.18 |
May | 0.177127E+10 | 0.515462E+10 | 0.00 | 70416404.18 | 0.187089E+09 | 0.00 | 0.852049E+10 | 0.00 | 1.05 |
June | 0.750601E+09 | 0.191491E+11 | 0.00 | 17723824.21 | 0.253502E+09 | 0.00 | 0.221117E+10 | 0.00 | 0.93 |
July | 0.334517E+09 | 0.205361E+11 | 0.00 | 8958674.95 | 0.595052E+09 | 0.00 | 0.806773E+09 | 0.00 | 0.77 |
August | 0.389688E+09 | 0.185387E+11 | 0.00 | 12650293.69 | 0.376677E+09 | 0.00 | 0.114538E+10 | 0.00 | 0.82 |
September | 0.850470E+09 | 0.117977E+11 | 0.00 | 25509242.54 | 0.675412E+09 | 0.00 | 0.240452E+10 | 0.00 | 0.82 |
October | 0.794984E+10 | 0.222792E+10 | 0.00 | 50672924.48 | 91184786.81 | 0.00 | 0.146111E+11 | 0.00 | 0.99 |
November | 0.157520E+11 | 9682050.06 | 0.00 | 35319117.81 | 65549497.85 | 0.231705E+09 | 0.145688E+11 | 0.00 | 0.91 |
December | 0.253044E+11 | 0.00 | 0.00 | 8932279.55 | 1588570.97 | 0.262484E+10 | 0.583727E+10 | 0.00 | 0.76 |
Annual Sum or Average | 0.107805E+12 | 0.797527E+11 | 0.00 | 0.410560E+09 | 0.254517E+10 | 0.481082E+10 | 0.115108E+12 | 0.00 | 0.92 |
Minimum of Months | 0.334517E+09 | 0.00 | 0.00 | 8932279.55 | 0.00 | 0.00 | 0.806773E+09 | 0.00 | 0.76 |
Maximum of Months | 0.253044E+11 | 0.205361E+11 | 0.00 | 83759929.37 | 0.675412E+09 | 0.262484E+10 | 0.199482E+11 | 0.00 | 1.18 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.848756E+10 | 91927163.88 | 0.00 | 0.243044E+09 | 24197619.46 | 0.178245E+09 | 0.581527E+11 | 0.00 | 1.60 |
February | 0.139863E+11 | 0.00 | 0.00 | 98454865.70 | 0.00 | 0.170144E+09 | 0.604980E+11 | 0.00 | 1.19 |
March | 0.138952E+11 | 25406550.77 | 0.00 | 0.104048E+09 | 2853839.84 | 0.185084E+09 | 0.351684E+11 | 0.00 | 1.06 |
April | 0.585388E+10 | 0.412110E+10 | 0.00 | 72999078.83 | 0.253632E+09 | 0.00 | 0.992807E+10 | 0.00 | 0.77 |
May | 0.268224E+10 | 0.678784E+10 | 0.00 | 38182616.38 | 0.205166E+09 | 0.00 | 0.405100E+10 | 0.00 | 0.57 |
June | 0.791394E+09 | 0.213183E+11 | 0.00 | 14352063.03 | 0.295529E+09 | 0.00 | 0.186012E+10 | 0.00 | 0.57 |
July | 0.381249E+09 | 0.229124E+11 | 0.00 | 5337605.84 | 0.563381E+09 | 0.00 | 0.629380E+09 | 0.00 | 0.51 |
August | 0.396366E+09 | 0.235044E+11 | 0.00 | 12188632.80 | 0.307699E+09 | 0.00 | 0.109853E+10 | 0.00 | 0.62 |
September | 0.611741E+09 | 0.190804E+11 | 0.00 | 36400986.58 | 0.647700E+09 | 0.00 | 0.280510E+10 | 0.00 | 0.72 |
October | 0.622135E+10 | 0.467391E+10 | 0.00 | 0.129008E+09 | 58264056.57 | 0.00 | 0.293975E+11 | 0.00 | 1.17 |
November | 0.901333E+10 | 42692609.25 | 0.00 | 0.201680E+09 | 54795485.26 | 41391534.31 | 0.569550E+11 | 0.00 | 1.44 |
December | 0.124294E+11 | 1476786.84 | 0.00 | 0.188597E+09 | 874218.55 | 0.129324E+10 | 0.673478E+11 | 0.00 | 1.39 |
Annual Sum or Average | 0.747500E+11 | 0.102560E+12 | 0.00 | 0.114429E+10 | 0.241409E+10 | 0.186811E+10 | 0.327892E+12 | 0.00 | 0.97 |
Minimum of Months | 0.381249E+09 | 0.00 | 0.00 | 5337605.84 | 0.00 | 0.00 | 0.629380E+09 | 0.00 | 0.51 |
Maximum of Months | 0.139863E+11 | 0.235044E+11 | 0.00 | 0.243044E+09 | 0.647700E+09 | 0.129324E+10 | 0.673478E+11 | 0.00 | 1.60 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.231230E+11 | 24518662.42 | 0.00 | 34415858.84 | 45801463.59 | 0.301364E+09 | 0.813439E+10 | 0.00 | 1.03 |
February | 0.277193E+11 | 0.00 | 0.00 | 19279135.07 | 0.00 | 0.263898E+09 | 0.123268E+11 | 0.00 | 0.99 |
March | 0.217410E+11 | 17933354.34 | 0.00 | 45143410.04 | 0.00 | 0.183609E+09 | 0.132981E+11 | 0.00 | 1.12 |
April | 0.559307E+10 | 0.381922E+10 | 0.00 | 58978858.16 | 94090584.61 | 0.00 | 0.870524E+10 | 0.00 | 1.04 |
May | 0.226657E+10 | 0.795521E+10 | 0.00 | 34288117.74 | 72512253.04 | 0.00 | 0.425800E+10 | 0.00 | 0.88 |
June | 0.671978E+09 | 0.236497E+11 | 0.00 | 15235881.98 | 0.171511E+09 | 0.00 | 0.196902E+10 | 0.00 | 0.92 |
July | 0.346902E+09 | 0.208185E+11 | 0.00 | 5534817.08 | 0.404678E+09 | 0.00 | 0.682427E+09 | 0.00 | 0.71 |
August | 0.387317E+09 | 0.191056E+11 | 0.00 | 10511946.96 | 0.227637E+09 | 0.00 | 0.103748E+10 | 0.00 | 0.80 |
September | 0.837983E+09 | 0.121128E+11 | 0.00 | 20629222.70 | 0.734875E+09 | 0.00 | 0.191386E+10 | 0.00 | 0.76 |
October | 0.115570E+11 | 0.241525E+10 | 0.00 | 43256257.72 | 86812440.56 | 0.00 | 0.896962E+10 | 0.00 | 0.95 |
November | 0.201601E+11 | 19796091.68 | 0.00 | 43038216.65 | 71101490.04 | 0.186145E+09 | 0.130852E+11 | 0.00 | 1.04 |
December | 0.272661E+11 | 44842.98 | 0.00 | 19962459.75 | 1678278.73 | 0.241705E+10 | 0.897312E+10 | 0.00 | 0.90 |
Annual Sum or Average | 0.141670E+12 | 0.899386E+11 | 0.00 | 0.350274E+09 | 0.191070E+10 | 0.335206E+10 | 0.833532E+11 | 0.00 | 0.93 |
Minimum of Months | 0.346902E+09 | 0.00 | 0.00 | 5534817.08 | 0.00 | 0.00 | 0.682427E+09 | 0.00 | 0.71 |
Maximum of Months | 0.277193E+11 | 0.236497E+11 | 0.00 | 58978858.16 | 0.734875E+09 | 0.241705E+10 | 0.132981E+11 | 0.00 | 1.12 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.197232E+10 | 0.00 | 0.00 | 344182.88 | 4008709.74 | 0.446203E+09 | 95238214.60 | 0.00 | 0.54 |
February | 0.264313E+10 | 0.00 | 0.00 | 132374.14 | 35128.76 | 0.435029E+09 | 0.141261E+09 | 0.00 | 0.52 |
March | 0.207247E+10 | 442488.25 | 0.00 | 2013807.74 | 109001.68 | 0.303441E+09 | 0.503390E+09 | 0.00 | 0.57 |
April | 0.618831E+09 | 0.147657E+09 | 0.00 | 5152503.54 | 26339793.99 | 0.00 | 0.502877E+09 | 0.00 | 0.52 |
May | 0.265610E+09 | 0.415416E+09 | 0.00 | 4823034.01 | 18596223.08 | 0.00 | 0.305148E+09 | 0.00 | 0.51 |
June | 76680828.78 | 0.178775E+10 | 0.00 | 1716210.37 | 26605284.32 | 0.00 | 0.185307E+09 | 0.00 | 0.57 |
July | 33461622.99 | 0.192116E+10 | 0.00 | 626725.25 | 51652869.30 | 0.00 | 59414359.32 | 0.00 | 0.48 |
August | 37062556.26 | 0.164169E+10 | 0.00 | 986275.93 | 34784114.96 | 0.00 | 77795186.64 | 0.00 | 0.51 |
September | 0.106311E+09 | 0.104664E+10 | 0.00 | 2680080.15 | 93099646.90 | 0.00 | 0.154402E+09 | 0.00 | 0.50 |
October | 0.108574E+10 | 0.180856E+09 | 0.00 | 2712489.90 | 18762809.05 | 0.121006E+09 | 0.374958E+09 | 0.00 | 0.50 |
November | 0.191380E+10 | 610810.76 | 0.00 | 1179275.16 | 5901437.41 | 0.307405E+09 | 0.357171E+09 | 0.00 | 0.54 |
December | 0.209901E+10 | 0.00 | 0.00 | 23083.16 | 1274690.83 | 0.982310E+09 | 16665660.72 | 0.00 | 0.49 |
Annual Sum or Average | 0.129244E+11 | 0.714222E+10 | 0.00 | 22390042.23 | 0.281170E+09 | 0.259539E+10 | 0.277363E+10 | 0.00 | 0.52 |
Minimum of Months | 33461622.99 | 0.00 | 0.00 | 23083.16 | 35128.76 | 0.00 | 16665660.72 | 0.00 | 0.48 |
Maximum of Months | 0.264313E+10 | 0.192116E+10 | 0.00 | 5152503.54 | 93099646.90 | 0.982310E+09 | 0.503390E+09 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.131661E+10 | 0.00 | 0.00 | 1838007.80 | 3854850.79 | 0.268871E+09 | 0.918927E+09 | 0.00 | 0.83 |
February | 0.173772E+10 | 0.00 | 0.00 | 1251013.87 | 33780.48 | 0.295964E+09 | 0.115030E+10 | 0.00 | 0.80 |
March | 0.136129E+10 | 477115.77 | 0.00 | 4163617.99 | 104818.07 | 0.168704E+09 | 0.165991E+10 | 0.00 | 0.99 |
April | 0.375056E+09 | 0.155431E+09 | 0.00 | 9115631.05 | 22473553.44 | 0.00 | 0.135691E+10 | 0.00 | 1.14 |
May | 0.184695E+09 | 0.357385E+09 | 0.00 | 7944074.33 | 16886685.64 | 0.00 | 0.664522E+09 | 0.00 | 0.99 |
June | 81325637.57 | 0.157361E+10 | 0.00 | 1675983.10 | 24104970.20 | 0.00 | 0.167263E+09 | 0.00 | 0.87 |
July | 30469811.04 | 0.176804E+10 | 0.00 | 805613.35 | 54819061.77 | 0.00 | 62271426.09 | 0.00 | 0.72 |
August | 35789685.07 | 0.161162E+10 | 0.00 | 1139718.33 | 35393651.99 | 0.00 | 86634644.43 | 0.00 | 0.79 |
September | 92118374.35 | 0.102261E+10 | 0.00 | 2841388.17 | 73583465.75 | 0.00 | 0.191297E+09 | 0.00 | 0.79 |
October | 0.617146E+09 | 0.185721E+09 | 0.00 | 5025182.33 | 9277786.44 | 77022891.47 | 0.120102E+10 | 0.00 | 0.92 |
November | 0.132941E+10 | 539181.48 | 0.00 | 2750933.27 | 5674933.37 | 0.154250E+09 | 0.113116E+10 | 0.00 | 0.87 |
December | 0.219299E+10 | 0.00 | 0.00 | 331597.29 | 1225766.71 | 0.513840E+09 | 0.243854E+09 | 0.00 | 0.73 |
Annual Sum or Average | 0.935462E+10 | 0.667544E+10 | 0.00 | 38882760.88 | 0.247433E+09 | 0.147865E+10 | 0.883406E+10 | 0.00 | 0.87 |
Minimum of Months | 30469811.04 | 0.00 | 0.00 | 331597.29 | 33780.48 | 0.00 | 62271426.09 | 0.00 | 0.72 |
Maximum of Months | 0.219299E+10 | 0.176804E+10 | 0.00 | 9115631.05 | 73583465.75 | 0.513840E+09 | 0.165991E+10 | 0.00 | 1.14 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.856783E+09 | 6255971.91 | 0.00 | 19135792.84 | 2355002.96 | 0.154409E+09 | 0.528228E+10 | 0.00 | 1.59 |
February | 0.143356E+10 | 0.00 | 0.00 | 7782016.14 | 38574.70 | 0.227469E+09 | 0.538653E+10 | 0.00 | 1.12 |
March | 0.131180E+10 | 992061.03 | 0.00 | 9223148.25 | 119694.15 | 0.222645E+09 | 0.318243E+10 | 0.00 | 1.03 |
April | 0.602694E+09 | 0.257911E+09 | 0.00 | 9004909.63 | 25593546.37 | 0.00 | 0.916946E+09 | 0.00 | 0.76 |
May | 0.360166E+09 | 0.460759E+09 | 0.00 | 5071983.78 | 20420410.88 | 0.00 | 0.255060E+09 | 0.00 | 0.55 |
June | 94155927.36 | 0.170946E+10 | 0.00 | 1270059.96 | 31122108.61 | 0.00 | 0.148770E+09 | 0.00 | 0.53 |
July | 44392416.97 | 0.193162E+10 | 0.00 | 475739.70 | 61236813.63 | 0.00 | 44605185.38 | 0.00 | 0.48 |
August | 41496078.73 | 0.195889E+10 | 0.00 | 1095809.18 | 33239207.12 | 0.00 | 82994109.96 | 0.00 | 0.59 |
September | 91491777.75 | 0.156252E+10 | 0.00 | 4081543.71 | 78035029.39 | 0.00 | 0.229440E+09 | 0.00 | 0.69 |
October | 0.587569E+09 | 0.365939E+09 | 0.00 | 13386724.35 | 7282452.86 | 38925566.37 | 0.274104E+10 | 0.00 | 1.13 |
November | 0.899860E+09 | 2037895.59 | 0.00 | 16573645.80 | 5890506.80 | 0.111981E+09 | 0.518796E+10 | 0.00 | 1.43 |
December | 0.118044E+10 | 1232214.51 | 0.00 | 13192005.04 | 492843.18 | 0.351485E+09 | 0.553519E+10 | 0.00 | 1.27 |
Annual Sum or Average | 0.750441E+10 | 0.825762E+10 | 0.00 | 0.100293E+09 | 0.265826E+09 | 0.110692E+10 | 0.289932E+11 | 0.00 | 0.93 |
Minimum of Months | 41496078.73 | 0.00 | 0.00 | 475739.70 | 38574.70 | 0.00 | 44605185.38 | 0.00 | 0.48 |
Maximum of Months | 0.143356E+10 | 0.195889E+10 | 0.00 | 19135792.84 | 78035029.39 | 0.351485E+09 | 0.553519E+10 | 0.00 | 1.59 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.197140E+10 | 1907038.90 | 0.00 | 3038874.61 | 3393402.85 | 0.237911E+09 | 0.827489E+09 | 0.00 | 1.08 |
February | 0.253304E+10 | 0.00 | 0.00 | 1655490.07 | 38546.01 | 0.244544E+09 | 0.116982E+10 | 0.00 | 1.00 |
March | 0.206097E+10 | 618454.64 | 0.00 | 4182749.87 | 9978.40 | 0.186520E+09 | 0.123593E+10 | 0.00 | 1.14 |
April | 0.591913E+09 | 0.240700E+09 | 0.00 | 7732520.32 | 11737365.20 | 0.00 | 0.758021E+09 | 0.00 | 1.04 |
May | 0.291083E+09 | 0.532780E+09 | 0.00 | 4343679.86 | 9003987.92 | 0.00 | 0.293621E+09 | 0.00 | 0.83 |
June | 81295876.25 | 0.180652E+10 | 0.00 | 1349396.97 | 22465485.32 | 0.00 | 0.156544E+09 | 0.00 | 0.84 |
July | 36299226.05 | 0.171039E+10 | 0.00 | 476589.80 | 47962353.60 | 0.00 | 52875937.12 | 0.00 | 0.66 |
August | 36769838.08 | 0.155453E+10 | 0.00 | 945778.71 | 26766333.36 | 0.00 | 82190960.51 | 0.00 | 0.75 |
September | 0.119047E+09 | 0.985085E+09 | 0.00 | 2362794.32 | 93334020.26 | 0.00 | 0.137961E+09 | 0.00 | 0.74 |
October | 0.106964E+10 | 0.185670E+09 | 0.00 | 4835968.17 | 14530660.27 | 45740247.35 | 0.825141E+09 | 0.00 | 0.94 |
November | 0.184093E+10 | 1667188.34 | 0.00 | 3757060.48 | 5886124.72 | 0.184464E+09 | 0.118105E+10 | 0.00 | 1.09 |
December | 0.223985E+10 | 0.00 | 0.00 | 1567773.10 | 1398689.73 | 0.559222E+09 | 0.788540E+09 | 0.00 | 0.91 |
Annual Sum or Average | 0.128722E+11 | 0.701987E+10 | 0.00 | 36248676.28 | 0.236527E+09 | 0.145840E+10 | 0.750919E+10 | 0.00 | 0.92 |
Minimum of Months | 36299226.05 | 0.00 | 0.00 | 476589.80 | 9978.40 | 0.00 | 52875937.12 | 0.00 | 0.66 |
Maximum of Months | 0.253304E+10 | 0.180652E+10 | 0.00 | 7732520.32 | 93334020.26 | 0.559222E+09 | 0.123593E+10 | 0.00 | 1.14 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 4206375.51 | 0.00 | 0.00 | 0.293779E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 8160274.92 | 0.00 | 0.00 | 0.292613E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 14579345.12 | 0.00 | 0.00 | 0.292046E+09 | 0.00 | 0.31 |
April | 0.00 | 603280.77 | 0.00 | 17618063.23 | 0.00 | 0.00 | 0.117876E+09 | 0.00 | 0.29 |
May | 0.00 | 13922207.47 | 0.00 | 3117694.16 | 0.00 | 0.00 | 54663943.72 | 0.00 | 0.29 |
June | 0.00 | 92572001.28 | 0.00 | 1649423.37 | 0.00 | 0.00 | 14514941.52 | 0.00 | 0.30 |
July | 0.00 | 0.189390E+09 | 0.00 | 580973.41 | 0.00 | 0.00 | 3971656.98 | 0.00 | 0.28 |
August | 0.00 | 0.169241E+09 | 0.00 | 1979503.95 | 0.00 | 0.00 | 5535500.13 | 0.00 | 0.31 |
September | 0.00 | 0.114772E+09 | 0.00 | 790803.85 | 0.00 | 0.00 | 10680106.25 | 0.00 | 0.29 |
October | 0.00 | 22857349.12 | 0.00 | 7668727.25 | 0.00 | 0.00 | 0.168412E+09 | 0.00 | 0.28 |
November | 0.00 | 2153181.17 | 0.00 | 12537674.89 | 0.00 | 0.00 | 0.236404E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 19062016.87 | 0.00 | 0.00 | 0.348729E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.605511E+09 | 0.00 | 91950876.51 | 0.00 | 0.00 | 0.183923E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 580973.41 | 0.00 | 0.00 | 3971656.98 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.189390E+09 | 0.00 | 19062016.87 | 0.00 | 0.00 | 0.348729E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 19856876.58 | 0.00 | 0.00 | 31887041.48 | 0.00 | 0.00 | 0.292691E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 70073066.28 | 0.00 | 0.00 | 0.294279E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.133245E+09 | 0.00 | 0.00 | 0.293122E+10 | 0.00 | 0.31 |
April | 0.00 | 8423414.71 | 0.00 | 0.166260E+09 | 0.00 | 0.00 | 0.117714E+10 | 0.00 | 0.29 |
May | 0.00 | 0.138711E+09 | 0.00 | 28177093.15 | 0.00 | 0.00 | 0.548671E+09 | 0.00 | 0.29 |
June | 0.00 | 0.924267E+09 | 0.00 | 15319776.39 | 0.00 | 0.00 | 0.144783E+09 | 0.00 | 0.30 |
July | 0.00 | 0.188889E+10 | 0.00 | 5461787.09 | 0.00 | 0.00 | 39274411.17 | 0.00 | 0.28 |
August | 0.00 | 0.172393E+10 | 0.00 | 18051095.55 | 0.00 | 0.00 | 52362941.54 | 0.00 | 0.31 |
September | 0.00 | 0.113112E+10 | 0.00 | 7011215.93 | 0.00 | 0.00 | 0.107183E+09 | 0.00 | 0.29 |
October | 0.00 | 0.227041E+09 | 0.00 | 69001276.59 | 0.00 | 0.00 | 0.168938E+10 | 0.00 | 0.28 |
November | 0.00 | 20737892.54 | 0.00 | 0.113873E+09 | 0.00 | 0.00 | 0.237414E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.171872E+09 | 0.00 | 0.00 | 0.350313E+10 | 0.00 | 0.28 |
Annual Sum or Average | 19856876.58 | 0.606312E+10 | 0.00 | 0.830232E+09 | 0.00 | 0.00 | 0.184370E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 5461787.09 | 0.00 | 0.00 | 39274411.17 | 0.00 | 0.28 |
Maximum of Months | 19856876.58 | 0.188889E+10 | 0.00 | 0.171872E+09 | 0.00 | 0.00 | 0.350313E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 9515020.22 | 0.00 | 0.00 | 2472008.13 | 0.00 | 0.00 | 0.286153E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 6298308.91 | 0.00 | 0.00 | 0.295456E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 12809802.01 | 0.00 | 0.00 | 0.293805E+09 | 0.00 | 0.31 |
April | 0.00 | 1139046.40 | 0.00 | 16127559.22 | 0.00 | 0.00 | 0.114798E+09 | 0.00 | 0.29 |
May | 0.00 | 13894546.21 | 0.00 | 2788802.04 | 0.00 | 0.00 | 54919631.13 | 0.00 | 0.29 |
June | 0.00 | 92498985.08 | 0.00 | 1527103.23 | 0.00 | 0.00 | 14555093.28 | 0.00 | 0.30 |
July | 0.00 | 0.189039E+09 | 0.00 | 545402.76 | 0.00 | 0.00 | 3964844.57 | 0.00 | 0.28 |
August | 0.00 | 0.176849E+09 | 0.00 | 1689119.39 | 0.00 | 0.00 | 4957837.84 | 0.00 | 0.31 |
September | 0.00 | 0.113415E+09 | 0.00 | 684358.09 | 0.00 | 0.00 | 10800372.97 | 0.00 | 0.29 |
October | 0.00 | 22739977.59 | 0.00 | 6558127.36 | 0.00 | 0.00 | 0.169411E+09 | 0.00 | 0.28 |
November | 0.00 | 2024716.88 | 0.00 | 10832897.28 | 0.00 | 0.00 | 0.238136E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 16185366.41 | 0.00 | 0.00 | 0.351228E+09 | 0.00 | 0.28 |
Annual Sum or Average | 9515020.22 | 0.611600E+09 | 0.00 | 78518854.82 | 0.00 | 0.00 | 0.183818E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 545402.76 | 0.00 | 0.00 | 3964844.57 | 0.00 | 0.28 |
Maximum of Months | 9515020.22 | 0.189039E+09 | 0.00 | 16185366.41 | 0.00 | 0.00 | 0.351228E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.565783E+09 | 0.00 | 0.00 | 0.525030E+12 | 0.00 | 23.94 |
February | 0.00 | 0.00 | 0.00 | 0.925277E+09 | 0.00 | 0.00 | 0.630067E+12 | 0.00 | 29.48 |
March | 0.00 | 0.00 | 0.00 | 0.160216E+10 | 0.00 | 0.00 | 0.872787E+12 | 0.00 | 42.31 |
April | 0.00 | 185380.68 | 0.00 | 0.284943E+10 | 0.00 | 0.00 | 0.555330E+12 | 0.00 | 40.49 |
May | 0.00 | 28317.82 | 0.00 | 0.515601E+09 | 0.00 | 0.00 | 0.278145E+12 | 0.00 | 21.10 |
June | 0.00 | 0.932429E+09 | 0.00 | 0.698666E+09 | 0.00 | 0.00 | 0.128152E+12 | 0.00 | 13.98 |
July | 0.00 | 0.542392E+11 | 0.00 | 0.399594E+09 | 0.00 | 0.00 | 0.445991E+11 | 0.00 | 15.38 |
August | 0.00 | 0.561782E+11 | 0.00 | 0.519528E+09 | 0.00 | 0.00 | 0.372197E+11 | 0.00 | 20.27 |
September | 0.00 | 0.992034E+10 | 0.00 | 0.358919E+09 | 0.00 | 0.00 | 0.117922E+12 | 0.00 | 23.75 |
October | 0.00 | 0.285842E+10 | 0.00 | 0.110759E+10 | 0.00 | 0.00 | 0.529475E+12 | 0.00 | 34.35 |
November | 0.00 | 406336.39 | 0.00 | 0.167425E+10 | 0.00 | 0.00 | 0.838695E+12 | 0.00 | 43.50 |
December | 0.00 | 0.00 | 0.00 | 0.237536E+10 | 0.00 | 0.00 | 0.119279E+13 | 0.00 | 44.05 |
Annual Sum or Average | 0.00 | 0.124129E+12 | 0.00 | 0.135922E+11 | 0.00 | 0.00 | 0.575021E+13 | 0.00 | 29.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.358919E+09 | 0.00 | 0.00 | 0.372197E+11 | 0.00 | 13.98 |
Maximum of Months | 0.00 | 0.561782E+11 | 0.00 | 0.284943E+10 | 0.00 | 0.00 | 0.119279E+13 | 0.00 | 44.05 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:54
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.321901E+12 | 0.446260E+10 | 0.00 | 0.225781E+13 | 0.697902E+12 |
February | 0.362232E+12 | 0.349446E+10 | 0.00 | 0.247586E+13 | 0.287244E+12 |
March | 0.469200E+12 | 0.463391E+10 | 0.00 | 0.265592E+13 | 0.103071E+13 |
April | 0.555269E+12 | 0.116525E+10 | 0.00 | 0.143220E+13 | 0.274818E+13 |
May | 0.549254E+12 | 0.203216E+09 | 0.00 | 0.887076E+12 | 0.227518E+13 |
June | 0.560759E+12 | -0.120740E+10 | 0.00 | 0.194277E+12 | 0.342488E+13 |
July | 0.531666E+12 | -0.258495E+10 | 0.00 | -0.174730E+12 | 0.386171E+13 |
August | 0.475935E+12 | -0.160634E+10 | 0.00 | -0.519079E+11 | 0.432021E+13 |
September | 0.397817E+12 | -0.113011E+10 | 0.00 | 0.694680E+11 | 0.251355E+13 |
October | 0.374512E+12 | 0.190581E+10 | 0.00 | 0.179127E+13 | 0.173657E+13 |
November | 0.337376E+12 | 0.409294E+10 | 0.00 | 0.255373E+13 | 0.104453E+13 |
December | 0.268530E+12 | 0.433228E+10 | 0.00 | 0.314160E+13 | 0.826548E+12 |
Annual Sum or Average | 0.520445E+13 | 0.177617E+11 | 0.00 | 0.172326E+14 | 0.247672E+14 |
Minimum of Months | 0.268530E+12 | -0.258495E+10 | 0.00 | -0.174730E+12 | 0.287244E+12 |
Maximum of Months | 0.560759E+12 | 0.463391E+10 | 0.00 | 0.314160E+13 | 0.432021E+13 |