Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2024-07-03 12:21:48
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 30607.76 | 660.78 | 660.78 |
Net Site Energy | 30607.76 | 660.78 | 660.78 |
Total Source Energy | 90890.32 | 1962.21 | 1962.21 |
Net Source Energy | 90890.32 | 1962.21 | 1962.21 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 2901.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1287.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3221.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 357.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2566.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2573.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 315.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 417.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2945.89 |
Humidification | 1730.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 643.71 |
Heat Recovery | 46.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 513.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 27705.95 | 2901.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5869.76 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 2901.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1287.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3221.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 357.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 55.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2505.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2573.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 315.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 417.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2945.89 |
Humidification | General | 1730.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 643.71 |
Heat Recovery | General | 46.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 513.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 2901.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1287.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3221.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 357.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 2566.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2573.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 315.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 417.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2945.89 |
Humidification | Unassigned | 1730.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 643.71 |
Heat Recovery | Unassigned | 46.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 513.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 77.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 147.61 | 62.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.13 |
Other | 373.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 598.14 | 62.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.13 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 77.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 147.61 | 62.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.13 |
Other | 373.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 598.14 | 62.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.13 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 27705.953 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 27705.953 | 100.00 |
Total On-Site and Utility Electric Sources | 27705.953 | 100.00 |
Total Electricity End Uses | 27705.953 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 123.68 | 4.38 |
Air to Air Heat Recovery for Heating | 2698.49 | 95.62 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 2822.17 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 5869.76 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 5869.76 | 100.00 |
Total Water End Uses | 5869.76 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 193.17 |
Time Setpoint Not Met During Occupied Cooling | 4304.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 8.6849 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 8.6849 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 8.7339 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 8.7339 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.6849 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 8.6849 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 8.6849 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 8.6849 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 8.6849 | 18.58 | 484.4232 | |
Total | 46320.38 | 8.7339 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 8.7339 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.6845 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 05-JUL-10:00 | 09-JAN-07:30 | - | - | - | - | - | - | - | - | - | - | 08-JUN-12:20 |
Heating | 0.00 | 2677693.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 577293.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 280450.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 660080.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 233151.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 315794.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 56569.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 88191.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 43335.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2254867.53 | 2677693.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 2677693.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 577293.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 280450.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 354874.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3430.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 112.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 315794.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 56569.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 88191.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 43335.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 3145.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4077.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 10203.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1131.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8128.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8150.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 999.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1320.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 5480.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 146.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1626.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 87744.75 | 3145.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 67.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 88.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 220.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 24.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 175.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 21.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 28.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 118.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 3.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 35.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1894.30 | 67.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 67.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 88.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 220.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 24.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 175.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 21.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 28.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 118.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 3.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 35.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1894.30 | 67.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 5.83 | 0.363501 | 0.000000 | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 6.11 | 0.311057 | 0.322000 | 1.97 | 0.829486 | 0.500000 | 0.001225 | 0.000226 | 1.97 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 57.52 | 0.330702 | 0.336000 | 19.33 | 0.881871 | 0.500000 | 0.001152 | 0.004406 | 19.33 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.66 | 0.335757 | 0.349000 | 1.98 | 0.895352 | 0.500000 | 0.001135 | 0.000949 | 3.37 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.02 | 0.233281 | 0.241000 | 0.246723 | 0.622082 | 0.500000 | 0.001633 | 0.000174 | 0.619199 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.54 | 0.099766 | 0.200000 | 0.308531 | 0.300000 | 0.500000 | 0.003819 | 0.000119 | 0.424180 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.86 | 0.128533 | 0.200000 | 0.371619 | 0.342753 | 0.500000 | 0.002964 | 0.000192 | 0.681889 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.84 | 0.083817 | 0.200000 | 0.367242 | 0.300000 | 0.500000 | 0.004546 | 0.000100 | 0.367242 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 9.55 | 0.250169 | 0.254000 | 2.42 | 0.667118 | 0.500000 | 0.001523 | 0.002402 | 8.55 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 16.54 | 0.093072 | 0.200000 | 3.31 | 0.300000 | 0.500000 | 0.004094 | 0.001595 | 5.68 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 19.07 | 0.125254 | 0.200000 | 3.81 | 0.334011 | 0.500000 | 0.003042 | 0.002435 | 8.67 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 17.38 | 0.088571 | 0.200000 | 3.48 | 0.300000 | 0.500000 | 0.004302 | 0.001563 | 5.56 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.10 | 0.217938 | 0.236000 | 0.258613 | 0.581168 | 0.500000 | 0.001748 | 0.000308 | 1.10 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.65 | 0.093066 | 0.200000 | 0.330743 | 0.300000 | 0.500000 | 0.004094 | 0.000203 | 0.722983 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 2.00 | 0.119373 | 0.200000 | 0.400133 | 0.318329 | 0.500000 | 0.003192 | 0.000311 | 1.11 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.81 | 0.085264 | 0.200000 | 0.361008 | 0.300000 | 0.500000 | 0.004468 | 0.000202 | 0.720223 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | User-Specified Rated Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 25826.19 | 0.000226 | 539.75 | |
CORE_MID VAV BOX REHEAT COIL | 503620.82 | 0.004406 | 12238.63 | |
CORE_TOP VAV BOX REHEAT COIL | 108421.46 | 0.000949 | 2861.23 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 19898.99 | 0.000174 | 524.86 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 13629.88 | 0.000119 | 359.48 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 21909.46 | 0.000192 | 577.84 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 11475.87 | 0.000100 | 298.95 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 274620.39 | 0.002402 | 7241.30 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 182262.85 | 0.001595 | 4805.88 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 278313.35 | 0.002435 | 7338.61 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 178693.44 | 0.001563 | 4711.81 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 35181.36 | 0.000308 | 927.53 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 23210.73 | 0.000203 | 611.93 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 35594.06 | 0.000311 | 938.41 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 23122.10 | 0.000202 | 609.59 | |
VAV_BOT WITH REHEAT HEATING COIL | 129328.48 | 0.001131 | 1872.63 | |
VAV_MID WITH REHEAT HEATING COIL | 1313387.11 | 0.011490 | 18597.81 | |
VAV_TOP WITH REHEAT HEATING COIL | 131782.03 | 0.001153 | 1908.74 | |
CAV_BAS HEATING COIL | 315744.00 | 0.000875 | 2622.30 | 100000.00 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.532078 |
DATACENTER_MID_ZN_6 DIRECT AIR | 5.13 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.519581 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 25.63 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 6.19 | 3.26 | 12.38 | 3.26 | 10.31 | 10.31 | 0.300000 | 0.316647 | 10.31 |
VAV_MID WITH REHEAT | 60.02 | 32.35 | 120.04 | 42.44 | 96.59 | 96.59 | 0.300000 | 0.439405 | 96.59 |
VAV_TOP WITH REHEAT | 6.11 | 3.33 | 12.22 | 7.02 | 10.51 | 10.51 | 0.300000 | 0.667465 | 10.51 |
CAV_BAS | 0.000000 | 0.000000 | 5.83 | 1.20 | 5.83 | 5.83 | 1.00 | 0.205984 | 5.83 |
AIRLOOP DATACENTER BASEMENT | 25.63 | 25.63 | 25.63 | 25.63 | 25.63 | 25.63 | 1.00 | 1.000000 | 25.63 |
AIRLOOP DATACENTER BOT | 0.532078 | 0.532078 | 0.532078 | 0.532078 | 0.532078 | 0.532078 | 1.00 | 1.00 | 0.532078 |
AIRLOOP DATACENTER MID | 5.13 | 5.13 | 5.13 | 5.13 | 5.13 | 5.13 | 1.00 | 1.00 | 5.13 |
AIRLOOP DATACENTER TOP | 0.519581 | 0.519581 | 0.519581 | 0.519581 | 0.519581 | 0.519581 | 1.00 | 1.00 | 0.519581 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 10.31 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 96.59 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 10.51 | |
CAV_BAS_OA_CONTROLLER | 5.83 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 25.63 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.532078 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 5.13 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.519581 | 0.015632 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT OA HEAT RECOVERY | 2.54 |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 25.38 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.54 |
CAV_BAS OA HEAT RECOVERY | 1.20 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 25.52 | 6.67 | 10.88 | 0.009802 | 0.008500 | 217143.45 | 0.006210 | 10.31 |
VAV_MID WITH REHEAT COOLING COIL | 25.65 | 6.67 | 10.88 | 0.009922 | 0.008500 | 2084108.58 | 0.059605 | 96.59 |
VAV_TOP WITH REHEAT COOLING COIL | 25.47 | 6.67 | 10.88 | 0.009789 | 0.008500 | 220614.74 | 0.006310 | 10.51 |
CAV_BAS COOLING COIL | 25.27 | 6.67 | 10.85 | 0.009859 | 0.008500 | 122195.02 | 0.003495 | 5.83 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 10.31 |
VAV_MID WITH REHEAT FAN | 96.59 |
VAV_TOP WITH REHEAT FAN | 10.51 |
CAV_BAS FAN | 5.83 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.006210 | 0.000077 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.001131 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.059605 | 0.000008 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.011490 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.006310 | 0.000075 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.001153 | |
CAV_BAS_COOLC_CONTROLLER | 0.003495 | 0.000136 |
CAV_BAS_HEATC_CONTROLLER | 0.000875 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 25.63 | 501495.90 | 346810.59 | 0.012282 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.532078 | 10240.31 | 7133.58 | 0.000251 |
AIRLOOP DATACENTER MID COOLING COIL | 5.13 | 98739.45 | 68748.48 | 0.002418 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.519581 | 10005.58 | 6967.78 | 0.000245 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 25.63 | 25.63 | 25.63 | 25.63 | 501495.90 | 501495.90 | 28525.81 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.532078 | 0.532078 | 0.532078 | 0.532078 | 10240.31 | 10240.31 | 1317.77 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 5.13 | 5.13 | 5.13 | 5.13 | 98739.45 | 98739.45 | 13177.74 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.519581 | 0.519581 | 0.519581 | 0.519581 | 10005.58 | 10005.58 | 1317.77 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 25.63 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.532078 |
AIRLOOP DATACENTER MID SUPPLY FAN | 5.13 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.519581 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 25.63 | 501495.90 | 0.012282 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.532078 | 10240.31 | 0.000251 |
AIRLOOP DATACENTER MID HEATING COIL | 5.13 | 98739.45 | 0.002418 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.519581 | 10005.58 | 0.000245 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 28525.81 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 1317.77 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 13177.74 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 1317.77 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000237 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.075620 | 12346.41 | |
HEATSYS1 PUMP | 0.029835 | 8984.87 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.075620 | 9.07 |
HEATSYS1 | 0.029835 | 3.58 |
COOLSYS1_SUPPLY | 0.075620 | 9.07 |
SINGLE WATER PLANT LOOP | 0.015196 | 1.82 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.075620 | 0.075620 | 317414.38 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 3410278.58 | 3410278.58 | 0.029835 |
CENTRAL BOILER | 625926.21 | 613211.05 | 0.015196 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.037810 | 4273.92 |
COOLSYS1 CHILLER2 PUMP | 0.037810 | 4273.92 |
PLANT CIRC PUMP | 0.015196 | 3875.62 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.075620 | 0.037981 | 1328019.88 | 1328020.27 | 0.066872 |
COOLSYS1 CHILLER2 | 0.075620 | 0.037981 | 1328019.88 | 1328020.27 | 0.066872 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | U-factor Times Area Value at High Fan Speed [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/K] | |
CENTRAL TOWER | 0.015196 | 150880.50 | 76380.64 | 75440.25 | 7879.72 | 45828.38 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.133745 | 16.05 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.133745 | 33112.29 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 53.48 | 1590218.10 | 10.70 | 198777.26 |
TOWERWATERSYS COOLTOWER 2 | 53.48 | 1590218.10 | 10.70 | 198777.26 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.068867 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 8.685 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 13.527 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 8.685 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 493.108 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 24139.153 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 24139.153 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 6806.209 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6806.209 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 0.8300 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 0.7863 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.009 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.2699 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.105 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8237 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.628 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
47 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
48 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
49 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
50 | 9 | -0.18184691E-14 | 0.28097163E-16 | -0.15437903E-09 | 0.42281572E-16 |
51 | 8 | 0.22529355E-07 | 0.11232537E-12 | 0.38463784E-03 | -0.25616649E-09 |
52 | 7 | -0.12445705E-01 | 0.57914341E-08 | -0.23379721E-01 | 0.14151220E-03 |
53 | 6 | 0.41089736 | 0.20123329E-05 | 0.47681267 | -0.48131481E-02 |
54 | 5 | -5.2446941 | 0.75059793E-04 | -4.4775149 | 0.63855043E-01 |
55 | 4 | 33.242279 | 0.61344040E-03 | 21.582026 | -0.42530178 |
56 | 3 | -111.73561 | 0.13358480E-02 | -55.904128 | 1.5225540 |
57 | 2 | 197.63606 | 0.75086744E-03 | 78.131773 | -2.9087348 |
58 | 1 | -171.35103 | 0.80103876E-04 | -55.329475 | 2.7488562 |
59 | 0 | 57.057407 | 0.45563487E-06 | 15.546359 | |
60 | 9 | -0.45719712E-14 | 0.27682002E-16 | -0.15643277E-09 | 0.85453293E-16 |
61 | 8 | 0.22815700E-07 | 0.10660981E-12 | 0.38760953E-03 | -0.25942234E-09 |
62 | 7 | -0.12534255E-01 | 0.54803652E-08 | -0.23507179E-01 | 0.14251905E-03 |
63 | 6 | 0.41330326 | 0.19019750E-05 | 0.47885866 | -0.48415080E-02 |
64 | 5 | -5.2681707 | 0.70870595E-04 | -4.4932156 | 0.64146145E-01 |
65 | 4 | 33.346110 | 0.57866488E-03 | 21.643366 | -0.42668038 |
66 | 3 | -111.95648 | 0.12590731E-02 | -56.025383 | 1.5257451 |
67 | 2 | 197.85492 | 0.70718823E-03 | 78.243035 | -2.9122105 |
68 | 1 | -171.43186 | 0.75392391E-04 | -55.361928 | 2.7502728 |
69 | 0 | 57.057407 | 0.42848903E-06 | 15.541080 | |
70 | 9 | -0.33808012E-15 | 0.34972917E-16 | -0.14598079E-09 | 0.47841714E-18 |
71 | 8 | 0.21349114E-07 | 0.13533401E-12 | 0.37225214E-03 | -0.24274679E-09 |
72 | 7 | -0.12076170E-01 | 0.70668839E-08 | -0.22847671E-01 | 0.13731045E-03 |
73 | 6 | 0.40085647 | 0.24680520E-05 | 0.46826241 | -0.46947901E-02 |
74 | 5 | -5.1467077 | 0.92462493E-04 | -4.4118499 | 0.62640056E-01 |
75 | 4 | 32.808865 | 0.75866459E-03 | 21.325369 | -0.41954723 |
76 | 3 | -110.81348 | 0.16579313E-02 | -55.396723 | 1.5092316 |
77 | 2 | 196.72215 | 0.93484174E-03 | 77.666390 | -2.8942219 |
78 | 1 | -171.01346 | 0.10002080E-03 | -55.194115 | 2.7429399 |
79 | 0 | 57.057407 | 0.57079447E-06 | 15.568689 | |
80 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
81 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
82 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
83 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
84 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
85 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
86 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
87 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
88 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
89 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
90 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
91 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
92 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
93 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
94 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
95 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
96 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
97 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
98 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
99 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
100 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
101 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
102 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
103 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
104 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
105 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
106 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
107 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
108 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
109 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
110 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
111 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
112 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
113 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
114 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
115 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
116 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
117 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
118 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
119 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 | |
120 | 7 | -0.15524988E-08 | -0.27599222E-15 | 0.12191615E-13 | -0.17961055E-15 |
121 | 6 | 0.75408527E-05 | 0.51820635E-08 | 0.31843202E-02 | -0.26712746E-04 |
122 | 5 | -0.54428247E-03 | 0.30714476E-05 | -0.22340912 | 0.19533659E-02 |
123 | 4 | 0.12532102E-01 | 0.13984121E-03 | 4.8242913 | -0.45214473E-01 |
124 | 3 | -0.11008570 | 0.11123587E-02 | -37.991733 | 0.39832565 |
125 | 2 | 0.39093855 | 0.18508074E-02 | 116.42617 | -1.4171665 |
126 | 1 | -0.56428968 | 0.56416853E-03 | -143.87330 | 2.0484809 |
127 | 0 | 0.27512533 | 0.13606908E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.33_SHGC_EAST_0.45 | 35 | 1 | VerySmooth | 1.875 | 1.875 | 1.000 | 0.451 | ||
2 | WINDOW_U_0.33_SHGC_SOUTH_0.45 | 36 | 1 | VerySmooth | 1.875 | 1.875 | 1.000 | 0.451 | ||
3 | WINDOW_U_0.33_SHGC_WEST_0.45 | 37 | 1 | VerySmooth | 1.875 | 1.875 | 1.000 | 0.451 | ||
4 | WINDOW_U_0.33_SHGC_NORTH_0.45 | 38 | 1 | VerySmooth | 1.875 | 1.875 | 1.000 | 0.451 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.93105E-002 | 0.36619 | 0.43710 | 0.43710 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 0.10917 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.93105E-002 | 0.36619 | 0.43710 | 0.43710 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 0.10917 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.93105E-002 | 0.36619 | 0.43710 | 0.43710 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 0.10917 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.93105E-002 | 0.36619 | 0.43710 | 0.43710 | 0.49500 | 0.13079 | 0.16089 | 0.00000 | 0.84000 | 0.84000 | 0.10917 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 1.973E-005 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.7821E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.7848E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.8565E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.8588E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.5890E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.5907E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1188E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1198E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.8443E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.0267E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.9094E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0070E-002 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.6333E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.7637E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1446E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2101E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.2061 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1141 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.2366 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 0.1328 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1344 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.5825E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.6434E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9626E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.8541E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.0783E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.9202E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.0127E-002 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.6412E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.7943E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1452E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.2120E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 8.7818E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.7849E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.8562E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.8589E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.5889E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.5909E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.1187E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.1197E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.5541E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 8.0923E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.3616E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.9904E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.5641E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.7378E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3324E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.3776E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.6065E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2182E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.2822E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9564E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 8.0263E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.3589E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8755E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1975E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.3697E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.5083E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.1170E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 7.2188E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.5096E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.5493E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3325E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.3783E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4484E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4511E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9198E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9221E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5472E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5489E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1189E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.1198E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.5097E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.6668E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9710E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0981E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5892E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6830E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1452E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.2120E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.7292E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0285E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.4061E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3020E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9148E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5168E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 5.6434E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9620E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.5072E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.6664E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9674E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.0925E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5829E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6632E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1446E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.2101E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4482E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.4509E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.9196E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9218E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5471E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5485E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1187E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 3.1197E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.5922E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.7364E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.1136E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.2183E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.9732E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.0096E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3326E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.3784E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 7.2503E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.6547E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.5419E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2308E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 7.0348E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9515E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.8755E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1975E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.7284E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 7.1051E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.2954E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.7128E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 6.0237E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 6.1786E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3323E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.3775E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.2069 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1543 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.2307 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1773 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1505 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 8.2100E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 6.9092E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 3.4167E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 0.1021 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 6.0423E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 9.8531E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 5.7431E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 9.4858E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.9142E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.0861E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.4558E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 7.0553E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 4.6922E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.5604E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.7023E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.0259E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.7187E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 6.9093E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.4161E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 8.6753E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 5.2634E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.8821E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.7385E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 8.3758E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.3765E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.0861E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.4558E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.2069 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1545 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.2308 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1776 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1507 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 8.2294E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 6.9240E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 3.4243E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 0.1022 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 6.0517E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 9.8604E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 5.7523E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 9.5000E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.9247E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.1009E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.4634E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 7.0557E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 4.6977E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.5613E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.7066E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.0339E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.7238E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 6.9241E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.4237E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 8.6797E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 5.2710E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.8870E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.7455E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 8.3884E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.3856E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.1009E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.4634E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 77537.89458 | 77537.89458 | 5.82645 | 5.82645 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27099E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 81381.54788 | 81381.54788 | 6.11477 | 6.11477 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27099E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 6828.40356 | 6828.40356 | 0.30194 | 1.07782 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 765666.16785 | 765666.16785 | 57.51542 | 57.51542 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27099E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 317157.97864 | 317157.97864 | 13.98614 | 13.98614 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 75414.82383 | 75414.82383 | 5.66494 | 5.66494 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 20.92400 | 1.27099E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 75906.05754 | 75906.05754 | 3.36993 | 3.36993 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 13502.34134 | 13502.34134 | 1.02375 | 1.02375 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 25.03667 | 1.27170E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 13926.07581 | 13926.07581 | 0.61920 | 0.61920 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 20346.73838 | 20346.73838 | 1.54266 | 1.54266 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:30:00 | 22.10200 | 1.27119E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 9538.10466 | 9538.10466 | 0.42418 | 0.42418 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 24506.95582 | 24506.95582 | 1.85810 | 1.85810 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 29.68667 | 1.27251E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 15331.60216 | 15331.60216 | 0.68189 | 0.68189 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 24218.43501 | 24218.43501 | 1.83621 | 1.83621 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.15733 | 1.27224E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 7933.72711 | 7933.72711 | 0.35259 | 0.35259 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 125905.76359 | 125905.76359 | 9.54636 | 9.54636 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 30.10000 | 1.27259E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 192149.45151 | 192149.45151 | 8.55090 | 8.55090 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 218096.45814 | 218096.45814 | 16.53615 | 16.53615 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.28000 | 1.27140E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 127525.27544 | 127525.27544 | 5.67542 | 5.67542 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 251478.67727 | 251478.67727 | 19.06729 | 19.06729 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 29.79000 | 1.27253E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 194731.25355 | 194731.25355 | 8.66607 | 8.66607 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 229180.69906 | 229180.69906 | 17.37655 | 17.37655 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 27.74400 | 1.27217E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 125029.57430 | 125029.57430 | 5.56413 | 5.56413 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 13888.45503 | 13888.45503 | 1.05305 | 1.05305 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 30.10000 | 1.27259E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 24612.57172 | 24612.57172 | 1.09582 | 1.09582 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 21810.77738 | 21810.77738 | 1.65372 | 1.65372 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 23.63133 | 1.27146E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 16237.85543 | 16237.85543 | 0.72298 | 0.72298 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 26386.58717 | 26386.58717 | 2.00066 | 2.00066 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 29.89333 | 1.27255E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 24901.10644 | 24901.10644 | 1.10869 | 1.10869 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 23806.58661 | 23806.58661 | 1.80504 | 1.80504 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 27.95067 | 1.27221E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 16175.85718 | 16175.85718 | 0.72022 | 0.72022 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70000 | 1.83376E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8897.49903 | 8897.49903 | 0.53208 | 0.53208 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 24.80933 | 1.27166E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -32.70000 | 1.83376E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 85714.10297 | 85714.10297 | 5.12580 | 5.12580 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 24.80933 | 1.27166E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -32.70000 | 1.83376E-004 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8688.50390 | 8688.50390 | 0.51958 | 0.51958 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 24.80933 | 1.27166E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -32.70000 | 1.83376E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 372690.83973 | 428594.46569 | 22.28901 | 25.63236 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 25.26400 | 1.27174E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -32.70000 | 1.83376E-004 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 150503.43 | 10.30509 | 10.30509 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 133904.54 | 3.15569 | 3.15569 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1400414.45 | 96.59116 | 96.59116 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 1336377.31 | 42.44267 | 42.44267 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 154334.84 | 10.51387 | 10.51387 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 133476.20 | 7.01764 | 7.01764 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 |
7 | CAV_BAS | Cooling | Sensible | 74913.79 | 5.82645 | 5.82645 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 101170.70 | 1.20016 | 1.20016 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 422729.33 | 25.63236 | 25.63236 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 28525.81 | 0.33839 | 0.33839 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8720.23 | 0.53208 | 0.53208 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 1317.77 | 1.56323E-002 | 1.56323E-002 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 83991.88 | 5.12580 | 5.12580 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 13177.74 | 0.15632 | 0.15632 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8514.47 | 0.51958 | 0.51958 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 1317.77 | 1.56323E-002 | 1.56323E-002 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 5.82645 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.36350 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.00000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 0.00000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.11477 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31106 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32200 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.96896 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.82949 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.22486E-003 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.25939E-004 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.96896 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
16 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 25826.18501 |
17 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.25939E-004 |
18 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 539.75431 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 57.51542 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33070 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33600 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 19.32518 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.88187 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.15210E-003 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.40589E-003 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 19.32518 |
28 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
30 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 503620.81827 |
31 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.40589E-003 |
32 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 12238.63394 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.66494 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33576 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34900 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.97707 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.89535 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.13475E-003 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.48518E-004 |
41 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.36993 |
42 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
43 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
44 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 108421.45658 |
45 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.48518E-004 |
46 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2861.23366 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.02375 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23328 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24100 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24672 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.62208 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.63322E-003 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.74085E-004 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.61920 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
58 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19898.99481 |
59 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.74085E-004 |
60 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 524.85942 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.54266 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.97663E-002 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.30853 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.81893E-003 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.19240E-004 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.42418 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
72 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13629.88372 |
73 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.19240E-004 |
74 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 359.48214 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.85810 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12853 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.37162 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34275 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.96423E-003 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.91674E-004 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.68189 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
86 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21909.46490 |
87 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.91674E-004 |
88 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 577.83762 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.83621 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.38167E-002 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.36724 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.54563E-003 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.00396E-004 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.36724 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
100 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11475.86900 |
101 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.00396E-004 |
102 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 298.94759 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.54636 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25017 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25400 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.42478 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66712 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.52297E-003 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.40250E-003 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.55090 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
114 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 274620.39220 |
115 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.40250E-003 |
116 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7241.30088 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 16.53615 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.30719E-002 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.30723 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.09361E-003 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.59451E-003 |
125 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.67542 |
126 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
128 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 182262.85065 |
129 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.59451E-003 |
130 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4805.87652 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 19.06729 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12525 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.81346 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33401 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.04181E-003 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.43481E-003 |
139 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.66607 |
140 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
142 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 278313.34663 |
143 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.43481E-003 |
144 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7338.60838 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 17.37655 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.85706E-002 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.47531 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.30165E-003 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.56329E-003 |
153 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.56413 |
154 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
156 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 178693.44154 |
157 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.56329E-003 |
158 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4711.81198 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.09582 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21794 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23600 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25861 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58117 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.74820E-003 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.07782E-004 |
167 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.09582 |
168 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
170 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 35181.36384 |
171 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.07782E-004 |
172 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 927.53302 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.65372 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.30662E-002 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.33074 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.09386E-003 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.03058E-004 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.72298 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
184 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23210.72874 |
185 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.03058E-004 |
186 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 611.92692 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.00066 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11937 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.40013 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31833 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.19167E-003 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.11392E-004 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.10869 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
198 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 35594.06481 |
199 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.11392E-004 |
200 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 938.40761 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.80504 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.52642E-002 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.36101 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.46846E-003 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.02282E-004 |
209 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.72022 |
210 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
211 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
212 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23122.10225 |
213 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.02282E-004 |
214 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 609.59005 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.53208 |
216 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.12580 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.51958 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 25.63236 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.18774 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.26307 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.37548 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.26307 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.30509 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.30509 |
225 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
226 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.31665 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 60.02088 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 32.34595 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 120.04176 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 42.44267 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 96.59116 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 96.59116 |
233 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
234 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.43941 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.11009 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.32756 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.22018 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 7.01764 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.51387 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.51387 |
241 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
242 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.66746 |
243 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.00000 |
244 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.00000 |
245 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.82645 |
246 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 1.20016 |
247 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.82645 |
248 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.82645 |
249 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
250 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.20598 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 25.63236 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 25.63236 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 25.63236 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 25.63236 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 25.63236 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 25.63236 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 1.00000 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.53208 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.53208 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.53208 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.53208 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.53208 |
264 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.53208 |
265 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
266 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.12580 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.12580 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.12580 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 5.12580 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.12580 |
272 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.12580 |
273 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
274 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.51958 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.51958 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.51958 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.51958 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.51958 |
280 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.51958 |
281 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
282 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
283 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.30509 |
284 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 96.59116 |
285 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.51387 |
286 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.82645 |
287 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 25.63236 |
288 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.53208 |
289 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 5.12580 |
290 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.51958 |
291 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.30509 |
292 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_BOT WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.51586 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.87580 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.80218E-003 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
298 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 217143.44809 |
299 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.21028E-003 |
300 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.30509 |
301 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 129328.47553 |
302 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.13142E-003 |
303 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1872.63367 |
304 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.30509 |
305 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.21028E-003 |
306 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.66778E-005 |
307 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.13142E-003 |
308 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 96.59116 |
309 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 25.38195 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.64577 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.87621 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.92196E-003 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
315 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2084108.58490 |
316 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 5.96052E-002 |
317 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 96.59116 |
318 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 1313387.10575 |
319 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.14901E-002 |
320 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 18597.81255 |
321 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 96.59116 |
322 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.96052E-002 |
323 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.98907E-006 |
324 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.14901E-002 |
325 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.51387 |
326 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.47310 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.87575 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.78931E-003 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
332 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 220614.74370 |
333 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.30955E-003 |
334 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.51387 |
335 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 131782.03244 |
336 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.15289E-003 |
337 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1908.73701 |
338 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.51387 |
339 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.30955E-003 |
340 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.54713E-005 |
341 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.15289E-003 |
342 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.82645 |
343 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
344 | HeatExchanger:AirToAir:SensibleAndLatent | CAV_BAS OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 1.20016 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.26821 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.85324 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.85891E-003 |
349 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
350 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 122195.02411 |
351 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.49476E-003 |
352 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.82645 |
353 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 315743.99603 |
354 | Coil:Heating:Water | CAV_BAS HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
355 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
356 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2622.29956 |
357 | Fan:VariableVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.82645 |
358 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.49476E-003 |
359 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.36258E-004 |
360 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.74844E-004 |
361 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 25.63236 |
362 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
363 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 25.63236 |
364 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 501495.90043 |
365 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 346810.59440 |
366 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.22816E-002 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 25.63236 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 25.63236 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 25.63236 |
370 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 25.63236 |
371 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 501495.90043 |
372 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 501495.90043 |
373 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 28525.80837 |
374 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
375 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 25.63236 |
376 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 25.63236 |
377 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 501495.90043 |
378 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.22816E-002 |
379 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 28525.80837 |
380 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 2.36949E-004 |
381 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
382 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
383 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
384 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.53208 |
385 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
386 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.53208 |
387 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10240.30646 |
388 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 7133.58147 |
389 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.50784E-004 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.53208 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.53208 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.53208 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.53208 |
394 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10240.30646 |
395 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10240.30646 |
396 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1317.77417 |
397 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
398 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.53208 |
399 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.53208 |
400 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 10240.30646 |
401 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.50784E-004 |
402 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1317.77417 |
403 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.12580 |
404 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
405 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.12580 |
406 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 98739.44898 |
407 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 68748.48317 |
408 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.41812E-003 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 5.12580 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 5.12580 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 5.12580 |
412 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.12580 |
413 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 98739.44898 |
414 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 98739.44898 |
415 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 13177.74171 |
416 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
417 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 5.12580 |
418 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.12580 |
419 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 98739.44898 |
420 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.41812E-003 |
421 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 13177.74171 |
422 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.51958 |
423 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
424 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.51958 |
425 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10005.58288 |
426 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6967.77865 |
427 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.45036E-004 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.51958 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.51958 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.51958 |
431 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.51958 |
432 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10005.58288 |
433 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10005.58288 |
434 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1317.77417 |
435 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
436 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.51958 |
437 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.51958 |
438 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 10005.58288 |
439 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.45036E-004 |
440 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1317.77417 |
441 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 7.56198E-002 |
442 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 12346.40801 |
443 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 7.56198E-002 |
444 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 9.07438 |
445 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 7.56198E-002 |
446 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 7.56198E-002 |
447 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 317414.38185 |
448 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
449 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.98346E-002 |
450 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 3.58015 |
451 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.98346E-002 |
452 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 8984.87275 |
453 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
454 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 3410278.57668 |
455 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 3410278.58000 |
456 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.98346E-002 |
457 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 7.56198E-002 |
458 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 9.07438 |
459 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 3.78099E-002 |
460 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 4273.91732 |
461 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 3.78099E-002 |
462 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 4273.91732 |
463 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 7.56198E-002 |
464 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.79812E-002 |
465 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1328019.87772 |
466 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1328020.27500 |
467 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 6.68725E-002 |
468 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 7.56198E-002 |
469 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.79812E-002 |
470 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1328019.87772 |
471 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1328020.27500 |
472 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 6.68725E-002 |
473 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.51955E-002 |
474 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.82347 |
475 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.51955E-002 |
476 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3875.62402 |
477 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.51955E-002 |
478 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 150880.49503 |
479 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at High Fan Speed [W/K] | 76380.63539 |
480 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 75440.24752 |
481 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
482 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/K] | 45828.38124 |
483 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 625926.20663 |
484 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 613211.05000 |
485 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.51955E-002 |
486 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
487 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
488 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
489 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
490 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
491 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.13374 |
492 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 16.04939 |
493 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.13374 |
494 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 33112.28532 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 53.47858 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1590218.10256 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 10.69572 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 198777.26282 |
499 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 53.47858 |
500 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1590218.10256 |
501 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 10.69572 |
502 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 198777.26282 |
503 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 6.88675E-002 |
504 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 6.88675E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 24485.22 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 477105.10 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 102742.48 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 18854.88 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 12914.56 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 20759.52 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 10868.07 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 260196.46 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 172689.13 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 263694.98 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 169307.57 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 33332.56 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 21990.94 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 33723.54 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 21906.96 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 80758.48 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 797482.40 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 82323.55 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 94839.37 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 258833.66 | 178051.86 | 80781.80 | 0.69 | 44388.84 | 450.22 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2451365.59 | 1679093.92 | 772271.67 | 0.68 | 416342.22 | 4222.77 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 263619.67 | 181476.93 | 82142.74 | 0.69 | 45310.44 | 459.56 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 146297.12 | 100665.31 | 45631.81 | 0.69 | 25303.67 | 256.64 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 8.97 | 30.62 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 8.97 | 30.62 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.270 | 0.259 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.270 | 0.259 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.270 | 0.259 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.830 | 0.738 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_NORTH_0.45 | N/A | 1.875 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_NORTH_0.45 | N/A | 1.875 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_NORTH_0.45 | N/A | 1.875 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_NORTH_0.45 | N/A | 1.875 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_NORTH_0.45 | N/A | 1.875 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.830 | 0.738 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_EAST_0.45 | N/A | 1.875 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_EAST_0.45 | N/A | 1.875 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_EAST_0.45 | N/A | 1.875 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.830 | 0.738 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_SOUTH_0.45 | N/A | 1.875 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_SOUTH_0.45 | N/A | 1.875 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_SOUTH_0.45 | N/A | 1.875 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_SOUTH_0.45 | N/A | 1.875 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_SOUTH_0.45 | N/A | 1.875 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.830 | 0.738 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_WEST_0.45 | N/A | 1.875 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_WEST_0.45 | N/A | 1.875 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_WEST_0.45 | N/A | 1.875 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.786 | 0.703 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_NORTH_0.45 | N/A | 1.875 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.786 | 0.703 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_EAST_0.45 | N/A | 1.875 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.786 | 0.703 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_SOUTH_0.45 | N/A | 1.875 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.786 | 0.703 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_WEST_0.45 | N/A | 1.875 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.009 | 0.877 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_NORTH_0.45 | N/A | 1.875 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.009 | 0.877 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_EAST_0.45 | N/A | 1.875 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.009 | 0.877 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_SOUTH_0.45 | N/A | 1.875 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.009 | 0.877 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.33_SHGC_WEST_0.45 | N/A | 1.875 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.830 | 0.738 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.830 | 0.738 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.830 | 0.738 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.830 | 0.738 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.786 | 0.703 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.786 | 0.703 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.786 | 0.703 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.786 | 0.703 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.009 | 0.877 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.009 | 0.877 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.009 | 0.877 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.009 | 0.877 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.270 | 0.259 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.270 | 0.259 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.270 | 0.259 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 2.7289834633E-003 | 1.7034362193E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 3.3598794355E-002 | 7.2817490956E-002 | Pass | Pass | 2.9205272131E-002 | 0.1675926484 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 2.6996658126E-002 | 1.8976826899E-002 | Pass | Pass | 0.4845231806 | 0.4936184303 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1312959516 | 0.1562391388 | Pass | Pass | 0.6506824407 | 0.6693612297 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.1837346765E-002 | 1.9616885419E-002 | Pass | Pass | 30.2957037471 | 361.2750081765 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 7.7343390464E-002 | 0.1268154320 | Pass | Pass | 0.3695057656 | 3.3486944015 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1678541881 | 0.1849060986 | Pass | Pass | 2.3204946638 | 20.7575440897 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 8.1193781201E-002 | 0.1084130542 | Pass | Pass | 3.5356238807E-002 | 0.1977804019 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.7615447024 | 0.6785421752 | Pass | Pass | 0.6200898737 | 0.5442197133 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.6212456220 | 0.7059220626 | Pass | Pass | 1.3661426580 | 7.7479218283 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4412690294 | 0.4852575046 | Pass | Pass | 0.6677564568 | 0.9951908802 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.5835278029 | 0.6529453515 | Pass | Pass | 1.5012196001 | 7.7940884842 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.0057633849 | 0.8617885028 | Pass | Pass | 0.5779902066 | 0.5421624425 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.8591924234 | 0.9183018245 | Pass | Pass | 0.5992598016 | 0.5804409250 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.5954946383 | 0.6965809199 | Pass | Pass | 0.6056838825 | 0.6651744746 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.8111713102 | 0.9003254251 | Pass | Pass | 0.7890260891 | 2.2097263083 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.5920974281E-003 | 7.0239427287E-003 | Pass | Pass | 0.1047504370 | 0.7773531521 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.6098708704E-002 | 6.1498117092E-002 | Pass | Pass | 0.4854482349 | 0.4874569826 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.2395231826 | 0.1783140803 | Pass | Pass | 0.4920758666 | 0.4994088323 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.5386215037E-003 | 2.1169567684E-002 | Pass | Pass | 0.6282263703 | 5.5344757810 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.7287759566E-002 | 4.8327480765E-002 | Pass | Pass | 1.1096139237E-002 | 1.9273526378E-002 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.1609181575E-002 | 4.7523393348E-002 | Pass | Pass | 1.2888377525E-002 | 1.9384682107E-002 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 7.8188795158E-006 | 5.7113718246E-006 | Pass | Pass | 1.4688995373E-004 | 1.2220781894E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 6243.71 | 145.05 | 0.00 | 32402.10 | 9658.47 | 48449.33 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 12.00 | 13 | |||
Apr | 16.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 190.00 | 53 | |||
Jul | 136.00 | 41 | |||
Aug | 87.00 | 42 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.261 | 0.270 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.261 | 0.270 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.261 | 0.270 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.738 | 0.830 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.738 | 0.830 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.738 | 0.830 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.738 | 0.830 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.703 | 0.786 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.703 | 0.786 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.703 | 0.786 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.703 | 0.786 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.877 | 1.009 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.877 | 1.009 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.877 | 1.009 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.877 | 1.009 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.738 | 0.830 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.738 | 0.830 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.738 | 0.830 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.738 | 0.830 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.703 | 0.786 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.703 | 0.786 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.703 | 0.786 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.703 | 0.786 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.877 | 1.009 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.877 | 1.009 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.877 | 1.009 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.877 | 1.009 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.159 | 0.163 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.261 | 0.270 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.261 | 0.270 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.261 | 0.270 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.33_SHGC_NORTH_0.45 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.875 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.33_SHGC_NORTH_0.45 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.875 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.33_SHGC_NORTH_0.45 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.875 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.33_SHGC_NORTH_0.45 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.875 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.33_SHGC_NORTH_0.45 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.875 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.33_SHGC_EAST_0.45 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.875 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.33_SHGC_EAST_0.45 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.875 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.33_SHGC_EAST_0.45 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.875 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.33_SHGC_SOUTH_0.45 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.875 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.33_SHGC_SOUTH_0.45 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.875 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.33_SHGC_SOUTH_0.45 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.875 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.33_SHGC_SOUTH_0.45 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.875 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.33_SHGC_SOUTH_0.45 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 1.875 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.33_SHGC_WEST_0.45 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.875 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.33_SHGC_WEST_0.45 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.875 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.33_SHGC_WEST_0.45 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 1.875 | 0.451 | 0.497 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.33_SHGC_NORTH_0.45 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 1.875 | 0.451 | 0.497 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.33_SHGC_EAST_0.45 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 1.875 | 0.451 | 0.497 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.33_SHGC_SOUTH_0.45 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 1.875 | 0.451 | 0.497 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.33_SHGC_WEST_0.45 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 1.875 | 0.451 | 0.497 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.33_SHGC_NORTH_0.45 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 1.875 | 0.451 | 0.497 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.33_SHGC_EAST_0.45 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 1.875 | 0.451 | 0.497 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.33_SHGC_SOUTH_0.45 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 1.875 | 0.451 | 0.497 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.33_SHGC_WEST_0.45 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 1.875 | 0.451 | 0.497 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 1.875 | 0.451 | 0.497 | |||||||||||||||||
North Total or Average | 1390.74 | 1.875 | 0.451 | 0.497 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 1.875 | 0.451 | 0.497 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.6849 | 2779.43 | 24139.15 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 216.17 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 8.6849 | 2496.12 | 21678.66 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 194.14 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 8.6849 | 24961.20 | 216786.56 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 1941.36 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 8.6849 | 2496.12 | 21678.66 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 194.14 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 8.6849 | 313.41 | 2721.97 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.67 | 0.0000 | Y | 14.14 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.41 | 0.0000 | Y | 9.03 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 8.6849 | 313.42 | 2722.03 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.14 | 0.0000 | Y | 13.87 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.34 | 0.0000 | Y | 9.00 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 8.6849 | 3134.13 | 27219.72 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.61 | 0.0000 | Y | 141.09 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 8.6849 | 2019.75 | 17541.42 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.37 | 0.0000 | Y | 90.13 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 8.6849 | 3134.20 | 27220.31 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.11 | 0.0000 | Y | 138.53 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 8.6849 | 2019.75 | 17541.42 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.30 | 0.0000 | Y | 89.88 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 8.6849 | 313.41 | 2721.97 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.61 | 0.0000 | Y | 14.11 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.37 | 0.0000 | Y | 9.01 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 8.6849 | 313.42 | 2722.03 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.11 | 0.0000 | Y | 13.85 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.30 | 0.0000 | Y | 8.99 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 8.6849 | 783.68 | 6806.21 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 62.65 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 13.9016 | 36.20 | 503.28 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.16 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 13.9016 | 362.03 | 5032.75 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 51.55 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 13.9016 | 36.20 | 503.28 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.16 |
Interior Lighting Total | 8.7339 | 46320.38 | 404555.99 | 1014.65 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13271.55 | AstronomicalClock | - | 42.55 | 42.55 | 106.01 | |
EXTERIOR_LIGHTS_B | 989.48 | AstronomicalClock | - | 83.52 | 63.04 | 11.71 | |
EXTERIOR_LIGHTS_C | 26594.85 | AstronomicalClock | - | 83.52 | 47.99 | 239.56 | |
Exterior Lighting Total | 40855.88 | 357.28 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2635917.85 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 3410278.58 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1328020.27 | 5.91 | 1320351.62 | 5.88 | 8.97 | 30.62 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 1328020.27 | 5.91 | 1320351.62 | 5.88 | 8.97 | 30.62 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 628794.46 | |||||
CENTRAL BOILER | Boiler:HotWater | 613211.05 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1590218.10 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1590218.10 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 217143.45 | 258833.66 | 178051.86 | 80781.80 | 0.69 | - | 44388.84 | 450.22 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2084108.58 | 2451365.59 | 1679093.92 | 772271.67 | 0.68 | - | 416342.22 | 4222.77 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 220614.74 | 263619.67 | 181476.93 | 82142.74 | 0.69 | - | 45310.44 | 459.56 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 122195.02 | 146297.12 | 100665.31 | 45631.81 | 0.69 | - | 25303.67 | 256.64 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 501495.90 | 346810.59 | 154685.31 | 0.69 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10240.31 | 7133.58 | 3106.72 | 0.70 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 98739.45 | 68748.48 | 29990.97 | 0.70 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10005.58 | 6967.78 | 3037.80 | 0.70 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 25826.19 | 24485.22 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 503620.82 | 477105.10 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 108421.46 | 102742.48 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 19898.99 | 18854.88 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 13629.88 | 12914.56 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 21909.46 | 20759.52 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 11475.87 | 10868.07 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 274620.39 | 260196.46 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 182262.85 | 172689.13 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 278313.35 | 263694.98 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 178693.44 | 169307.57 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 35181.36 | 33332.56 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 23210.73 | 21990.94 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 35594.06 | 33723.54 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 23122.10 | 21906.96 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 129328.48 | 80758.48 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 1313387.11 | 797482.40 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 131782.03 | 82323.55 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 100000.00 | 94839.37 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 501495.90 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10240.31 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 98739.45 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10005.58 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 28525.81 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 1317.77 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 13177.74 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 1317.77 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 10.31 | 23408.97 | 2271.59 | 1.00 | 1.12 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 96.59 | 219415.84 | 2271.59 | 1.00 | 1.08 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 10.51 | 23883.24 | 2271.59 | 1.00 | 1.12 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
CAV_BAS FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.83 | 13391.87 | 2298.46 | 1.00 | 1.13 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 25.63 | 42274.09 | 1649.25 | 1.00 | 1.14 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.53 | 595.98 | 1120.11 | 1.00 | 1.58 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 5.13 | 5741.45 | 1120.11 | 1.00 | 1.15 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.52 | 581.99 | 1120.11 | 1.00 | 1.59 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.075620 | 12346.41 | 163269.45 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.029835 | 8984.87 | 301156.09 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.037810 | 4273.92 | 113036.94 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.037810 | 4273.92 | 113036.94 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.015196 | 3875.62 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.133745 | 33112.29 | 247577.87 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 77537.89 | 77537.89 | 27.90 | 5.826 | 5.826 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00895 | 20.92 | 0.01271 | 1.200 | 0.00 |
CORE_BOTTOM | 81381.55 | 81381.55 | 32.60 | 6.115 | 6.115 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00888 | 20.92 | 0.01271 | 1.078 | 0.00 |
CORE_MID | 765666.17 | 765666.17 | 306.74 | 57.515 | 57.515 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 20.92 | 0.01271 | 10.778 | 0.00 |
CORE_TOP | 75414.82 | 75414.82 | 30.21 | 5.665 | 5.665 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 20.92 | 0.01271 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 13502.34 | 13502.34 | 43.08 | 1.024 | 1.024 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 24.00 | 24.00 | 0.00883 | 25.04 | 0.01272 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 20346.74 | 20346.74 | 100.74 | 1.543 | 1.543 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:30:00 | 24.00 | 24.00 | 0.00864 | 22.10 | 0.01271 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 24506.96 | 24506.96 | 78.19 | 1.858 | 1.858 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00868 | 29.69 | 0.01273 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 24218.44 | 24218.44 | 119.91 | 1.836 | 1.836 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00862 | 28.16 | 0.01272 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 125905.76 | 125905.76 | 401.72 | 9.546 | 9.546 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00892 | 30.10 | 0.01273 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 218096.46 | 218096.46 | 1079.82 | 16.536 | 16.536 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00866 | 23.28 | 0.01271 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 251478.68 | 251478.68 | 802.37 | 19.067 | 19.067 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00871 | 29.79 | 0.01273 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 229180.70 | 229180.70 | 1134.70 | 17.377 | 17.377 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 24.00 | 24.00 | 0.00865 | 27.74 | 0.01272 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 13888.46 | 13888.46 | 44.31 | 1.053 | 1.053 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00890 | 30.10 | 0.01273 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 21810.78 | 21810.78 | 107.99 | 1.654 | 1.654 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 24.00 | 24.00 | 0.00867 | 23.63 | 0.01271 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 26386.59 | 26386.59 | 84.19 | 2.001 | 2.001 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00871 | 29.89 | 0.01273 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 23806.59 | 23806.59 | 117.87 | 1.805 | 1.805 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00866 | 27.95 | 0.01272 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8897.50 | 8897.50 | 245.77 | 0.532 | 0.532 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 27.00 | 27.00 | 0.00858 | 24.81 | 0.01272 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 85714.10 | 85714.10 | 2367.61 | 5.126 | 5.126 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 27.00 | 27.00 | 0.00858 | 24.81 | 0.01272 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8688.50 | 8688.50 | 240.00 | 0.520 | 0.520 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 27.00 | 27.00 | 0.00858 | 24.81 | 0.01272 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 372690.84 | 428594.47 | 546.90 | 22.289 | 25.632 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.00 | 27.00 | 0.00854 | 25.26 | 0.01272 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 22.79 | 0.00018 | -32.70 | 0.00018 | 1.200 | 0.00 |
CORE_BOTTOM | 6828.40 | 6828.40 | 2.74 | 0.302 | 1.078 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -32.70 | 0.00018 | 1.078 | 0.00 |
CORE_MID | 317157.98 | 317157.98 | 127.06 | 13.986 | 13.986 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -32.70 | 0.00018 | 10.778 | 0.00 |
CORE_TOP | 75906.06 | 75906.06 | 30.41 | 3.370 | 3.370 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -32.70 | 0.00018 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 13926.08 | 13926.08 | 44.43 | 0.619 | 0.619 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00789 | -32.70 | 0.00018 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 9538.10 | 9538.10 | 47.22 | 0.424 | 0.424 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00790 | -32.70 | 0.00018 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 15331.60 | 15331.60 | 48.92 | 0.682 | 0.682 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00791 | -32.70 | 0.00018 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 7933.73 | 7933.73 | 39.28 | 0.353 | 0.353 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00785 | -32.70 | 0.00018 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 192149.45 | 192149.45 | 613.09 | 8.551 | 8.551 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -32.70 | 0.00018 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 127525.28 | 127525.28 | 631.39 | 5.675 | 5.675 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -32.70 | 0.00018 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 194731.25 | 194731.25 | 621.31 | 8.666 | 8.666 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -32.70 | 0.00018 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 125029.57 | 125029.57 | 619.03 | 5.564 | 5.564 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00783 | -32.70 | 0.00018 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 24612.57 | 24612.57 | 78.53 | 1.096 | 1.096 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -32.70 | 0.00018 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 16237.86 | 16237.86 | 80.40 | 0.723 | 0.723 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -32.70 | 0.00018 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 24901.11 | 24901.11 | 79.45 | 1.109 | 1.109 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -32.70 | 0.00018 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 16175.86 | 16175.86 | 80.09 | 0.720 | 0.720 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | -32.70 | 0.00018 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 24.30 | 0.00081 | -32.70 | 0.00018 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 22.35 | 0.00081 | -32.70 | 0.00018 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 19.88 | 0.00081 | -32.70 | 0.00018 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 27.00 | 0.00850 | -32.70 | 0.00018 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 10.31 | 10.31 | 3.16 | 3.16 | 10.3051 | 3.2631 | 10.3051 | 0.3166 | 0.3000 |
VAV_MID WITH REHEAT | 96.59 | 96.59 | 42.44 | 42.44 | 96.5912 | 42.4427 | 96.5912 | 0.4394 | 0.3000 |
VAV_TOP WITH REHEAT | 10.51 | 10.51 | 7.02 | 7.02 | 10.5139 | 7.0176 | 10.5139 | 0.6675 | 0.3000 |
CAV_BAS | 5.83 | 5.83 | 1.20 | 1.20 | 5.8265 | 1.2002 | 5.8265 | 0.2060 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 25.63 | 25.63 | 0.34 | 0.34 | 25.6324 | 25.6324 | 25.6324 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.53 | 0.53 | 0.02 | 0.02 | 0.5321 | 0.5321 | 0.5321 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 5.13 | 5.13 | 0.16 | 0.16 | 5.1258 | 5.1258 | 5.1258 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.52 | 0.52 | 0.02 | 0.02 | 0.5196 | 0.5196 | 0.5196 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 25826.185 | 25826.185 | 1.968956 | 0.00022594 | 539.754 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 25826.19 | 25826.19 | 1.968956 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00799758 | 49.5447 | 6828.40 | 0.00 | 25919.75 | 25919.75 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 503620.818 | 503620.818 | 19.325180 | 0.00440589 | 12238.634 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 503620.82 | 503620.82 | 19.325180 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00800000 | 49.5595 | 317157.98 | 0.00 | 505245.73 | 505245.73 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 108421.457 | 108421.457 | 3.369926 | 0.00094852 | 2861.234 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 108421.46 | 108421.46 | 3.369926 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00800000 | 49.5595 | 75906.06 | 0.00 | 108790.66 | 108790.66 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 19898.995 | 19898.995 | 0.619199 | 0.00017409 | 524.859 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19898.99 | 19898.99 | 0.619199 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00788942 | 48.8845 | 13926.08 | 0.00 | 19964.79 | 19964.79 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 13629.884 | 13629.884 | 0.424180 | 0.00011924 | 359.482 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 13629.88 | 13629.88 | 0.424180 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00789615 | 48.9257 | 9538.10 | 0.00 | 13674.79 | 13674.79 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 21909.465 | 21909.465 | 0.681889 | 0.00019167 | 577.838 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21909.46 | 21909.46 | 0.681889 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00790502 | 48.9798 | 15331.60 | 0.00 | 21981.54 | 21981.54 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 11475.869 | 11475.869 | 0.367242 | 0.00010040 | 298.948 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11475.87 | 11475.87 | 0.367242 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00784627 | 48.6209 | 7933.73 | 0.00 | 11510.97 | 11510.97 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 274620.392 | 274620.392 | 8.550904 | 0.00240250 | 7241.301 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 274620.39 | 274620.39 | 8.550904 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00783159 | 48.5318 | 192149.45 | 0.00 | 275513.00 | 275513.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 182262.851 | 182262.851 | 5.675419 | 0.00159451 | 4805.877 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 182262.85 | 182262.85 | 5.675419 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00783121 | 48.5296 | 127525.28 | 0.00 | 182854.52 | 182854.52 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 278313.347 | 278313.347 | 8.666073 | 0.00243481 | 7338.608 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 278313.35 | 278313.35 | 8.666073 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00783395 | 48.5463 | 194731.25 | 0.00 | 279217.45 | 279217.45 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 178693.442 | 178693.442 | 5.564135 | 0.00156329 | 4711.812 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 178693.44 | 178693.44 | 5.564135 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00782763 | 48.5077 | 125029.57 | 0.00 | 179273.90 | 179273.90 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 35181.364 | 35181.364 | 1.095819 | 0.00030778 | 927.533 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 35181.36 | 35072.17 | 1.095819 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00783811 | 48.5721 | 24612.57 | 0.00 | 35294.68 | 35294.68 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 23210.729 | 23210.729 | 0.722983 | 0.00020306 | 611.927 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23210.73 | 23210.73 | 0.722983 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00783645 | 48.5621 | 16237.86 | 0.00 | 23285.43 | 23285.43 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 35594.065 | 35594.065 | 1.108689 | 0.00031139 | 938.408 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 35594.06 | 35594.06 | 1.108689 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00783996 | 48.5835 | 24901.11 | 0.00 | 35708.67 | 35708.67 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 23122.102 | 23122.102 | 0.720223 | 0.00020228 | 609.590 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23122.10 | 23122.10 | 0.720223 | 12.80 | 11.22 | 0.00800000 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00783589 | 48.5586 | 16175.86 | 0.00 | 23196.51 | 23196.51 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 217143.448 | -999.000 | 10.305087 | 0.00621028 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 217143.45 | 177505.41 | 10.305087 | 25.52 | 17.54 | 0.00980218 | 10.88 | 10.88 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 24.6305 | 24.00 | 0.00883458 | 45.5523 | 134628.49 | 0.00 | 224025.31 | 175089.85 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 129328.476 | 129328.476 | 3.091526 | 0.00113142 | 1872.634 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 129328.48 | 129328.48 | 3.091526 | -23.28 | -23.28 | 0.00155738 | 12.80 | 11.22 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 82.1015 | 19.83 | 0.00783246 | 52.1551 | 35772.48 | 0.00 | 97643.95 | 97643.95 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2084108.585 | -999.000 | 96.591164 | 0.05960524 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 2084108.58 | 1678414.45 | 96.591164 | 25.65 | 17.68 | 0.00992196 | 10.88 | 10.88 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 26.2777 | 24.00 | 0.00888507 | 45.8094 | 1240017.49 | 0.00 | 2148981.66 | 1656518.91 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1313387.106 | 1313387.106 | 28.977349 | 0.01149008 | 18597.813 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 1313387.11 | 1313387.11 | 28.977349 | -26.29 | -26.29 | 0.00112758 | 12.80 | 11.22 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 87.5924 | 17.88 | 0.00777310 | 58.4797 | 398529.22 | 0.00 | 963983.03 | 963983.03 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 220614.744 | -999.000 | 10.513871 | 0.00630955 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 220614.74 | 180573.73 | 10.513871 | 25.47 | 17.52 | 0.00978931 | 10.88 | 10.88 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 24.1413 | 24.00 | 0.00885347 | 45.6488 | 138519.60 | 0.00 | 227630.28 | 178103.00 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 131782.032 | 131782.032 | 3.154161 | 0.00115289 | 1908.737 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 131782.03 | 131782.03 | 3.154161 | -23.23 | -23.23 | 0.00166713 | 12.80 | 11.22 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 80.4712 | 17.37 | 0.00771883 | 59.9808 | 58717.32 | 0.00 | 99539.61 | 99539.61 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 122195.024 | -999.000 | 5.826450 | 0.00349476 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 122195.02 | 98781.48 | 5.826450 | 25.27 | 17.51 | 0.00985891 | 10.85 | 10.85 | 0.00850000 | 29.48 | 0.01272477 | 20.95 | 20.5984 | 24.00 | 0.00899506 | 46.3682 | 68342.66 | 0.00 | 126062.15 | 97383.68 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 100000.000 | 100000.000 | 3.170652 | 0.00087484 | 2622.300 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 100000.00 | 100000.00 | 3.170652 | -6.74 | -10.65 | 0.00018338 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 37.8520 | 22.89 | 0.00018338 | 1.0250 | 0.00 | 0.00 | 100072.50 | 100072.50 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 501495.900 | 346810.594 | 25.632358 | 0.01228160 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 463395.01 | 457039.84 | -999.0 | 28.49 | 17.56 | 0.00859745 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | -999.0000 | 27.00 | 0.00854216 | 36.8765 | 372288.93 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10240.306 | 7133.581 | 0.532078 | 0.00025078 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 9435.18 | 9161.35 | -999.0 | 27.92 | 17.46 | 0.00870274 | 12.80 | 11.72 | 0.00850000 | 24.81 | 0.01271660 | 19.55 | -999.0000 | 27.00 | 0.00858124 | 37.0404 | 8897.50 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 98739.449 | 68748.483 | 5.125797 | 0.00241812 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 90989.47 | 88252.63 | -999.0 | 27.92 | 17.46 | 0.00871031 | 12.80 | 11.72 | 0.00850000 | 24.81 | 0.01271660 | 19.55 | -999.0000 | 27.00 | 0.00858429 | 37.0535 | 85714.10 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10005.583 | 6967.779 | 0.519581 | 0.00024504 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | 9219.77 | 8945.95 | -999.0 | 27.92 | 17.46 | 0.00870759 | 12.80 | 11.72 | 0.00850000 | 24.81 | 0.01271660 | 19.55 | -999.0000 | 27.00 | 0.00858323 | 37.0490 | 8688.50 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 501495.900 | 501495.900 | 25.632358 | 0.01228160 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 501495.90 | 501495.90 | 25.632358 | -32.70 | -32.70 | 0.00018338 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 1.3202 | 27.00 | 0.00850000 | 36.6913 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10240.306 | 10240.306 | 0.532078 | 0.00025078 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10240.31 | 10240.31 | 0.532078 | -32.70 | -32.70 | 0.00018338 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 2.9380 | 25.13 | 0.00081482 | 3.9779 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 98739.449 | 98739.449 | 5.125797 | 0.00241812 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 98739.45 | 98739.45 | 5.125797 | -32.70 | -32.70 | 0.00018338 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 3.0497 | 23.58 | 0.00081485 | 4.3648 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10005.583 | 10005.583 | 0.519581 | 0.00024504 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10005.58 | 10005.58 | 0.519581 | -32.70 | -32.70 | 0.00018338 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 3.0086 | 22.11 | 0.00081419 | 4.7660 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 28525.808 | 28525.808 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 28525.81 | 28525.81 | 25.632358 | -0.43 | -0.43 | 0.00839021 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 1.3202 | 27.00 | 0.00850000 | 36.6913 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 1317.774 | 1317.774 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1317.77 | 1317.77 | 0.532078 | -0.96 | -5.61 | 0.00079627 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 2.9380 | 25.13 | 0.00081482 | 3.9779 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 13177.742 | 13177.742 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 13177.74 | 13177.74 | 5.125797 | -1.00 | -5.64 | 0.00079559 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 3.0497 | 23.58 | 0.00081485 | 4.3648 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 1317.774 | 1317.774 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1317.77 | 1317.77 | 0.519581 | -0.98 | -5.63 | 0.00079521 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 3.0086 | 22.11 | 0.00081419 | 4.7660 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 25826.185 | 25826.185 | 1.968956 | 0.00022594 | 539.754 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.83156125 | 54.44 | 82.22 | 27.78 | 3478911.79 | 0.7424 | 0.757304 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 25826.19 | 25826.19 | 1.0000 | 2.27202767 | 1.968956 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.22591568 | 60.00 | 32.22 | 27.78 | 0.000 | 25826.19 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.83 | 0.00799758 | 21.00 | 0.00799758 | 49.5447 | 6828.40 | 0.00 | 25919.75 | 25919.75 | 2.27202767 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 23.99 | 15.95 | 0.00800000 | 44468.0 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 503620.818 | 503620.818 | 19.325180 | 0.00440589 | 12238.634 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.83156125 | 54.44 | 82.22 | 27.78 | 3478911.79 | 14.4764 | 14.767733 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 503620.82 | 503620.82 | 1.0000 | 22.29980583 | 19.325180 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 4.40544517 | 60.00 | 32.22 | 27.78 | 0.000 | 503620.82 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 49.5595 | 317157.98 | 0.00 | 505245.73 | 505245.73 | 22.29980583 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 35.02 | 19.66 | 0.00800000 | 55716.8 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 108421.457 | 108421.457 | 3.369926 | 0.00094852 | 2861.234 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.83156125 | 54.44 | 82.22 | 27.78 | 3478911.79 | 3.1165 | 3.179255 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 108421.46 | 108421.46 | 1.0000 | 3.88864122 | 3.369926 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.94842144 | 60.00 | 32.22 | 27.78 | 0.000 | 108421.46 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 49.5595 | 75906.06 | 0.00 | 108790.66 | 108790.66 | 3.88864122 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.24 | 21.25 | 0.00800000 | 61036.4 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19898.995 | 19898.995 | 0.619199 | 0.00017409 | 524.859 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.83156125 | 54.44 | 82.22 | 27.78 | 3478911.79 | 0.5720 | 0.583501 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19898.99 | 19898.99 | 1.0000 | 0.71450927 | 0.619199 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.17406733 | 60.00 | 32.22 | 27.78 | 0.000 | 19898.99 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00788942 | 21.00 | 0.00788942 | 48.8845 | 13926.08 | 0.00 | 19964.79 | 19964.79 | 0.71450927 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61001.8 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13629.884 | 13629.884 | 0.424180 | 0.00011924 | 359.482 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.83156125 | 54.44 | 82.22 | 27.78 | 3478911.79 | 0.3918 | 0.399671 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 13629.88 | 13629.88 | 1.0000 | 0.48947131 | 0.424180 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.11922800 | 60.00 | 32.22 | 27.78 | 0.000 | 13629.88 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00789615 | 21.00 | 0.00789615 | 48.9257 | 9538.10 | 0.00 | 13674.79 | 13674.79 | 0.48947131 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60997.7 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21909.465 | 21909.465 | 0.681889 | 0.00019167 | 577.838 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.83156125 | 54.44 | 82.22 | 27.78 | 3478911.79 | 0.6298 | 0.642454 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21909.46 | 21909.46 | 1.0000 | 0.78684860 | 0.681889 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.19165400 | 60.00 | 32.22 | 27.78 | 0.000 | 21909.46 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00790502 | 21.00 | 0.00790502 | 48.9798 | 15331.60 | 0.00 | 21981.54 | 21981.54 | 0.78684860 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60996.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11475.869 | 11475.869 | 0.367242 | 0.00010040 | 298.948 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.83156125 | 54.44 | 82.22 | 27.78 | 3478911.79 | 0.3299 | 0.336508 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11475.87 | 11475.87 | 1.0000 | 0.42376981 | 0.367242 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.10038567 | 60.00 | 32.22 | 27.78 | 0.000 | 11475.87 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00784627 | 21.00 | 0.00784627 | 48.6209 | 7933.73 | 0.00 | 11510.97 | 11510.97 | 0.42376981 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 39.44 | 21.02 | 0.00800000 | 60223.1 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 274620.392 | 274620.392 | 8.550904 | 0.00240250 | 7241.301 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.83156125 | 54.44 | 82.22 | 27.78 | 3478911.79 | 7.8939 | 8.052726 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 274620.39 | 274620.39 | 1.0000 | 9.86710085 | 8.550904 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 2.40225391 | 60.00 | 32.22 | 27.78 | 0.000 | 274620.39 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00783159 | 21.00 | 0.00783159 | 48.5318 | 192149.45 | 0.00 | 275513.00 | 275513.00 | 9.86710085 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60982.2 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 182262.851 | 182262.851 | 5.675419 | 0.00159451 | 4805.877 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.83156125 | 54.44 | 82.22 | 27.78 | 3478911.79 | 5.2391 | 5.344515 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 182262.85 | 182262.85 | 1.0000 | 6.54900656 | 5.675419 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 1.59435227 | 60.00 | 32.22 | 27.78 | 0.000 | 182262.85 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00783121 | 21.00 | 0.00783121 | 48.5296 | 127525.28 | 0.00 | 182854.52 | 182854.52 | 6.54900656 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60980.8 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 278313.347 | 278313.347 | 8.666073 | 0.00243481 | 7338.608 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.83156125 | 54.44 | 82.22 | 27.78 | 3478911.79 | 8.0000 | 8.161015 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 278313.35 | 278313.35 | 1.0000 | 9.99999673 | 8.666073 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 2.43455819 | 60.00 | 32.22 | 27.78 | 0.000 | 278313.35 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00783395 | 21.00 | 0.00783395 | 48.5463 | 194731.25 | 0.00 | 279217.45 | 279217.45 | 9.99999673 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60981.6 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 178693.442 | 178693.442 | 5.564135 | 0.00156329 | 4711.812 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.83156125 | 54.44 | 82.22 | 27.78 | 3478911.79 | 5.1365 | 5.239849 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 178693.44 | 178693.44 | 1.0000 | 6.42059360 | 5.564135 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 1.56312871 | 60.00 | 32.22 | 27.78 | 0.000 | 178693.44 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00782763 | 21.00 | 0.00782763 | 48.5077 | 125029.57 | 0.00 | 179273.90 | 179273.90 | 6.42059360 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60981.5 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 35181.364 | 35181.364 | 1.095819 | 0.00030778 | 927.533 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.83156125 | 54.44 | 82.22 | 27.78 | 3478911.79 | 1.0113 | 1.031627 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 35181.36 | 35072.17 | 1.0000 | 1.26449270 | 1.095819 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.30775052 | 60.00 | 32.22 | 27.78 | 0.000 | 35181.36 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00783811 | 21.00 | 0.00783811 | 48.5721 | 24612.57 | 0.00 | 35294.68 | 35294.68 | 1.26449270 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60972.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23210.729 | 23210.729 | 0.722983 | 0.00020306 | 611.927 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.83156125 | 54.44 | 82.22 | 27.78 | 3478911.79 | 0.6672 | 0.680611 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23210.73 | 23210.73 | 1.0000 | 0.83426766 | 0.722983 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.20303687 | 60.00 | 32.22 | 27.78 | 0.000 | 23210.73 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00783645 | 21.00 | 0.00783645 | 48.5621 | 16237.86 | 0.00 | 23285.43 | 23285.43 | 0.83426766 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60971.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 35594.065 | 35594.065 | 1.108689 | 0.00031139 | 938.408 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.83156125 | 54.44 | 82.22 | 27.78 | 3478911.79 | 1.0231 | 1.043729 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 35594.06 | 35594.06 | 1.0000 | 1.27934395 | 1.108689 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.31136064 | 60.00 | 32.22 | 27.78 | 0.000 | 35594.06 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00783996 | 21.00 | 0.00783996 | 48.5835 | 24901.11 | 0.00 | 35708.67 | 35708.67 | 1.27934395 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60971.5 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23122.102 | 23122.102 | 0.720223 | 0.00020228 | 609.590 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 29.83156125 | 54.44 | 82.22 | 27.78 | 3478911.79 | 0.6646 | 0.678012 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23122.10 | 23122.10 | 1.0000 | 0.83108310 | 0.720223 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.20226160 | 60.00 | 32.22 | 27.78 | 0.000 | 23122.10 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 20.95 | 0.00783589 | 21.00 | 0.00783589 | 48.5586 | 16175.86 | 0.00 | 23196.51 | 23196.51 | 0.83108310 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60971.0 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 217143.448 | -999.000 | 10.305087 | 0.00621028 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.0618 | 1004.8586 | 1.1539 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.305087 | 11.89129577 | 4197.9300 | 999.8980 | 75.61211879 | 15.00 | 6.67 | 8.33 | 2644061.80 | 8.2125 | 8.212495 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 217143.45 | 177505.41 | 1.0000 | 11.89129577 | 10.305087 | 25.52 | 17.54 | 0.00980218 | 50619.0 | 10.88 | 10.88 | 0.00850000 | 32358.3 | 6.20964162 | 6.67 | 15.00 | 8.33 | 23408.965 | 193734.48 | 30.10 | 0.01272586 | 21.13 | 2.53819000 | 24.6305 | 24.00 | 0.00883458 | 24.00 | 0.00883458 | 45.5523 | 134628.49 | 0.00 | 224025.31 | 175089.85 | 11.89129577 | 25.52 | 18.00 | 0.00980218 | 50619.0 | 11.12 | 11.06 | 0.00817020 | 31779.5 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 129328.476 | 129328.476 | 3.091526 | 0.00113142 | 1872.634 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 10.305087 | 11.89129577 | 4197.9300 | 999.8980 | 29.83156125 | 54.44 | 82.22 | 27.78 | 3478911.79 | 3.7175 | 3.792314 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:50:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 129328.48 | 129328.48 | 1.0000 | 3.56738873 | 3.091526 | -23.28 | -23.28 | 0.00155738 | -19562.8 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 1.13130651 | 60.00 | 32.22 | 27.78 | 0.000 | 129328.48 | -32.70 | 0.00018338 | -32.70 | 2.53819000 | 82.1015 | 19.94 | 0.00786005 | 19.83 | 0.00783246 | 52.1551 | 35772.48 | 0.00 | 97643.95 | 97643.95 | 3.56738873 | 2.80 | -1.88 | 0.00155738 | 6716.6 | 29.96 | 12.16 | 0.00155738 | 34087.8 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2084108.585 | -999.000 | 96.591164 | 0.05960524 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.2844 | 1004.8586 | 1.1539 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 96.591164 | 111.45894561 | 4197.9300 | 999.8980 | 75.61211879 | 15.00 | 6.67 | 8.33 | 2644061.80 | 78.8222 | 78.822234 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 2084108.58 | 1678414.45 | 1.0000 | 111.45894561 | 96.591164 | 25.65 | 17.68 | 0.00992196 | 51057.1 | 10.88 | 10.88 | 0.00850000 | 32358.7 | 59.59916136 | 6.67 | 15.00 | 8.33 | 219415.835 | 1864692.75 | 30.10 | 0.01272586 | 21.13 | 25.38195000 | 26.2777 | 24.00 | 0.00888507 | 24.00 | 0.00888507 | 45.8094 | 1240017.49 | 0.00 | 2148981.66 | 1656518.91 | 111.45894561 | 25.65 | 18.14 | 0.00992196 | 51057.1 | 11.12 | 11.06 | 0.00816978 | 31776.7 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 1313387.106 | 1313387.106 | 28.977349 | 0.01149008 | 18597.813 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 96.591164 | 111.45894561 | 4197.9300 | 999.8980 | 29.83156125 | 54.44 | 82.22 | 27.78 | 3478911.79 | 37.7528 | 38.512605 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 1313387.11 | 1313387.11 | 1.0000 | 33.43768368 | 28.977349 | -26.29 | -26.29 | 0.00112758 | -23651.1 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 11.48891124 | 60.00 | 32.22 | 27.78 | 0.000 | 1313387.11 | -32.70 | 0.00018338 | -32.70 | 25.38195000 | 87.5924 | 18.97 | 0.00779327 | 17.88 | 0.00777310 | 58.4797 | 398529.22 | 0.00 | 963983.03 | 963983.03 | 33.43768368 | 2.80 | -2.58 | 0.00112758 | 5639.4 | 31.43 | 12.32 | 0.00112758 | 34468.7 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 220614.744 | -999.000 | 10.513871 | 0.00630955 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.0378 | 1004.8586 | 1.1539 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.513871 | 12.13221759 | 4197.9300 | 999.8980 | 75.61211879 | 15.00 | 6.67 | 8.33 | 2644061.80 | 8.3438 | 8.343782 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 220614.74 | 180573.73 | 1.0000 | 12.13221759 | 10.513871 | 25.47 | 17.52 | 0.00978931 | 50542.4 | 10.88 | 10.88 | 0.00850000 | 32358.2 | 6.30891010 | 6.67 | 15.00 | 8.33 | 23883.239 | 196731.50 | 30.10 | 0.01272586 | 21.13 | 2.53819000 | 24.1413 | 24.00 | 0.00885347 | 24.00 | 0.00885347 | 45.6488 | 138519.60 | 0.00 | 227630.28 | 178103.00 | 12.13221759 | 25.47 | 17.97 | 0.00978931 | 50542.4 | 11.12 | 11.06 | 0.00817039 | 31780.0 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 131782.032 | 131782.032 | 3.154161 | 0.00115289 | 1908.737 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.513871 | 12.13221759 | 4197.9300 | 999.8980 | 29.83156125 | 54.44 | 82.22 | 27.78 | 3478911.79 | 3.7880 | 3.864260 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 131782.03 | 131782.03 | 1.0000 | 3.63966528 | 3.154161 | -23.23 | -23.23 | 0.00166713 | -19247.2 | 12.80 | 11.22 | 0.00800000 | 33059.8 | 1.15276910 | 60.00 | 32.22 | 27.78 | 0.000 | 131782.03 | -32.70 | 0.00018338 | -32.70 | 2.53819000 | 80.4712 | 15.78 | 0.00778111 | 17.37 | 0.00771883 | 59.9808 | 58717.32 | 0.00 | 99539.61 | 99539.61 | 3.63966528 | 2.80 | -1.71 | 0.00166713 | 6991.6 | 29.93 | 12.26 | 0.00166713 | 34340.2 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 122195.024 | -999.000 | 5.826450 | 0.00349476 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.1672 | 1004.8586 | 1.1539 | CAV_BAS FAN | Fan:VariableVolume | 5.826450 | 6.72328574 | 4197.9300 | 999.8980 | 75.61211879 | 15.00 | 6.67 | 8.33 | 2644061.80 | 4.6215 | 4.621489 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 122195.02 | 98781.48 | 1.0000 | 6.72328574 | 5.826450 | 25.27 | 17.51 | 0.00985891 | 50510.1 | 10.85 | 10.85 | 0.00850000 | 32335.2 | 3.49440572 | 6.67 | 15.00 | 8.33 | 13391.872 | 108803.15 | 29.48 | 0.01272477 | 20.95 | 1.20015641 | 20.5984 | 24.00 | 0.00899506 | 24.00 | 0.00899506 | 46.3682 | 68342.66 | 0.00 | 126062.15 | 97383.68 | 6.72328574 | 25.27 | 17.96 | 0.00985891 | 50510.1 | 11.11 | 11.05 | 0.00816731 | 31760.1 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.170652 | 0.00087484 | 2622.300 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | CAV_BAS FAN | Fan:VariableVolume | 5.826450 | 6.72328574 | 4197.9300 | 999.8980 | 29.83156125 | 54.44 | 82.22 | 27.78 | 3478911.79 | 2.8745 | 2.932312 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.170652 | -6.74 | -10.65 | 0.00018338 | -6312.0 | 40.00 | 20.69 | 0.00800000 | 60796.0 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | -32.70 | 0.00018338 | -32.70 | 1.20015641 | 37.8520 | 0.00 | 0.00018338 | 22.89 | 0.00018338 | 1.0250 | 0.00 | 0.00 | 100072.50 | 100072.50 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.02 | 14.59 | 0.00000000 | 40239.2 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 501495.900 | 346810.594 | 25.632358 | 0.01228160 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8222 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 463395.01 | 457039.84 | 0.9240 | -999.0 | -999.0 | 28.49 | 17.56 | 0.00859745 | 50586.8 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 463395.01 | 30.10 | 0.01272586 | 21.13 | 0.33839277 | -999.0000 | 27.00 | 0.00854216 | 27.00 | 0.00854216 | 36.8765 | 372288.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10240.306 | 7133.581 | 0.532078 | 0.00025078 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.0180 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | Sensible | 9435.18 | 9161.35 | 0.9214 | -999.0 | -999.0 | 27.92 | 17.46 | 0.00870274 | 50272.8 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9435.18 | 24.81 | 0.01271660 | 19.55 | 0.01563234 | -999.0000 | 27.00 | 0.00858124 | 27.00 | 0.00858124 | 37.0404 | 8897.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 98739.449 | 68748.483 | 5.125797 | 0.00241812 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.0320 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | Sensible | 90989.47 | 88252.63 | 0.9215 | -999.0 | -999.0 | 27.92 | 17.46 | 0.00871031 | 50289.6 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 90989.47 | 24.81 | 0.01271660 | 19.55 | 0.15632344 | -999.0000 | 27.00 | 0.00858429 | 27.00 | 0.00858429 | 37.0535 | 85714.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10005.583 | 6967.779 | 0.519581 | 0.00024504 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.0270 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:20:00 | Sensible | 9219.77 | 8945.95 | 0.9215 | -999.0 | -999.0 | 27.92 | 17.46 | 0.00870759 | 50283.6 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9219.77 | 24.81 | 0.01271660 | 19.55 | 0.01563234 | -999.0000 | 27.00 | 0.00858323 | 27.00 | 0.00858323 | 37.0490 | 8688.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 501495.900 | 501495.900 | 25.632358 | 0.01228160 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 501495.90 | 501495.90 | 1.0000 | 29.57781488 | 25.632358 | -32.70 | -32.70 | 0.00018338 | -32410.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 501495.90 | -32.70 | 0.00018338 | -32.70 | 0.33839277 | 1.3202 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 36.6913 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10240.306 | 10240.306 | 0.532078 | 0.00025078 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 10240.31 | 10240.31 | 1.0000 | 0.61397803 | 0.532078 | -32.70 | -32.70 | 0.00018338 | -32410.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10240.31 | -32.70 | 0.00018338 | -32.70 | 0.01563234 | 2.9380 | 0.00 | 0.00081482 | 25.13 | 0.00081482 | 3.9779 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 98739.449 | 98739.449 | 5.125797 | 0.00241812 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 98739.45 | 98739.45 | 1.0000 | 5.91478411 | 5.125797 | -32.70 | -32.70 | 0.00018338 | -32410.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 98739.45 | -32.70 | 0.00018338 | -32.70 | 0.15632344 | 3.0497 | 0.00 | 0.00081485 | 23.58 | 0.00081485 | 4.3648 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10005.583 | 10005.583 | 0.519581 | 0.00024504 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 10005.58 | 10005.58 | 1.0000 | 0.59955744 | 0.519581 | -32.70 | -32.70 | 0.00018338 | -32410.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10005.58 | -32.70 | 0.00018338 | -32.70 | 0.01563234 | 3.0086 | 0.00 | 0.00081419 | 22.11 | 0.00081419 | 4.7660 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28525.808 | 28525.808 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 25.632358 | 29.57781488 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 28525.81 | 28525.81 | 1.0000 | 29.57781488 | 25.632358 | -0.43 | -0.43 | 0.00839021 | 20542.9 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28525.81 | -32.70 | 0.00018338 | -32.70 | 0.33839277 | 1.3202 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 36.6913 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1317.774 | 1317.774 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.532078 | 0.61397803 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1317.77 | 1317.77 | 1.0000 | 0.61397803 | 0.532078 | -0.96 | -5.61 | 0.00079627 | 1024.6 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1317.77 | -32.70 | 0.00018338 | -32.70 | 0.01563234 | 2.9380 | 0.00 | 0.00081482 | 25.13 | 0.00081482 | 3.9779 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 13177.742 | 13177.742 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 5.125797 | 5.91478411 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 13177.74 | 13177.74 | 1.0000 | 5.91478411 | 5.125797 | -1.00 | -5.64 | 0.00079559 | 986.2 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 13177.74 | -32.70 | 0.00018338 | -32.70 | 0.15632344 | 3.0497 | 0.00 | 0.00081485 | 23.58 | 0.00081485 | 4.3648 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1317.774 | 1317.774 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.519581 | 0.59955744 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1317.77 | 1317.77 | 1.0000 | 0.59955744 | 0.519581 | -0.98 | -5.63 | 0.00079521 | 998.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1317.77 | -32.70 | 0.00018338 | -32.70 | 0.01563234 | 3.0086 | 0.00 | 0.00081419 | 22.11 | 0.00081419 | 4.7660 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 10.31 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 96.59 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 10.51 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 5.83 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 25.63 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 4339.33 | 5146.33 | 4122.00 |
CORE_BOTTOM | 2620.17 | 1606.00 | 30.33 |
CORE_MID | 1888.33 | 3502.83 | 411.83 |
CORE_TOP | 2762.50 | 4002.17 | 1466.00 |
PERIMETER_BOT_ZN_3 | 3142.00 | 3085.33 | 1210.00 |
PERIMETER_BOT_ZN_2 | 3362.83 | 3143.50 | 1275.50 |
PERIMETER_BOT_ZN_1 | 3292.83 | 2861.83 | 1059.83 |
PERIMETER_BOT_ZN_4 | 2881.17 | 2940.50 | 781.17 |
PERIMETER_MID_ZN_3 | 3729.00 | 4085.33 | 2373.50 |
PERIMETER_MID_ZN_2 | 3169.17 | 3470.00 | 1960.50 |
PERIMETER_MID_ZN_1 | 3404.50 | 3543.83 | 1654.67 |
PERIMETER_MID_ZN_4 | 3589.67 | 4065.33 | 2096.67 |
PERIMETER_TOP_ZN_3 | 4014.67 | 4341.33 | 2801.17 |
PERIMETER_TOP_ZN_2 | 3973.33 | 4131.17 | 2568.50 |
PERIMETER_TOP_ZN_1 | 3641.50 | 3849.00 | 2071.50 |
PERIMETER_TOP_ZN_4 | 3817.50 | 4281.17 | 2477.67 |
DATACENTER_BOT_ZN_6 | 5729.17 | 1229.50 | 1228.83 |
DATACENTER_MID_ZN_6 | 4612.33 | 577.83 | 272.50 |
DATACENTER_TOP_ZN_6 | 4106.17 | 1013.83 | 403.50 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5538.33 | 5538.33 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 6291.83 | 0.00 | 4288.67 |
CORE_BOTTOM | 0.00 | 77.33 | 0.00 | 8.50 |
CORE_MID | 2.17 | 0.33 | 0.83 | 0.33 |
CORE_TOP | 26.50 | 0.33 | 4.67 | 0.33 |
PERIMETER_BOT_ZN_3 | 7.83 | 40.50 | 0.67 | 27.00 |
PERIMETER_BOT_ZN_2 | 7.67 | 41.17 | 0.00 | 39.50 |
PERIMETER_BOT_ZN_1 | 9.83 | 61.50 | 0.17 | 57.17 |
PERIMETER_BOT_ZN_4 | 2.50 | 65.50 | 0.00 | 32.83 |
PERIMETER_MID_ZN_3 | 183.50 | 2.83 | 70.00 | 2.83 |
PERIMETER_MID_ZN_2 | 91.67 | 22.50 | 13.50 | 22.50 |
PERIMETER_MID_ZN_1 | 63.67 | 43.17 | 5.17 | 42.33 |
PERIMETER_MID_ZN_4 | 69.00 | 32.00 | 10.17 | 16.33 |
PERIMETER_TOP_ZN_3 | 432.67 | 2.83 | 179.17 | 2.17 |
PERIMETER_TOP_ZN_2 | 222.67 | 19.67 | 41.50 | 19.50 |
PERIMETER_TOP_ZN_1 | 174.67 | 33.67 | 25.67 | 32.33 |
PERIMETER_TOP_ZN_4 | 166.17 | 30.17 | 29.67 | 15.33 |
DATACENTER_BOT_ZN_6 | 0.00 | 5.50 | 0.00 | 2.33 |
DATACENTER_MID_ZN_6 | 0.00 | 3.17 | 0.00 | 0.67 |
DATACENTER_TOP_ZN_6 | 0.00 | 2.50 | 0.00 | 0.17 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 85.17 | 0.00 | 83.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 489.50 | 6309.50 | 193.17 | 4304.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.09 | 149.60 | 6779.02 | 0.148 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.86 | 134.35 | 6849.35 | 1.248 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.86 | 134.35 | 6849.35 | 0.712 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.86 | 134.35 | 6849.35 | 0.681 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.89 | 16.87 | 860.00 | 1.195 | 0.020 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.44 | 10.87 | 554.22 | 1.870 | 0.021 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.89 | 16.87 | 860.02 | 1.760 | 0.020 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.44 | 10.87 | 554.22 | 2.089 | 0.021 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.89 | 16.87 | 860.00 | 0.796 | 0.047 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.87 | 10.87 | 554.22 | 1.528 | 0.051 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.89 | 16.87 | 860.02 | 1.519 | 0.047 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.44 | 10.87 | 554.22 | 1.665 | 0.049 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.89 | 16.87 | 860.00 | 0.819 | 0.058 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.44 | 10.87 | 554.22 | 1.628 | 0.060 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.89 | 16.87 | 860.02 | 1.503 | 0.058 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.44 | 10.87 | 554.22 | 1.684 | 0.060 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.22 | 42.18 | 1911.37 | 24.651 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.09 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.86 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.86 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.86 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.89 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.44 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.89 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.44 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.89 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.87 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.89 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.44 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.89 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.44 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.89 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.44 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.22 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 61.09 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 54.86 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 54.86 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 54.86 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.89 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.44 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.89 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.44 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.89 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.87 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.89 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.44 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.89 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.44 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.89 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.44 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.80 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.22 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1012.40 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 5868005.30 | 0.00 | 5868005.30 | 0.00 | 5868005.30 | 37848132.68 | 7598.87 | 659.44 | 501.69 | 0.00 |
CORE_BOTTOM | 54307084.94 | 0.00 | 54307084.94 | 0.00 | 54307084.94 | 33990283.35 | 4266.65 | 41.55 | 4451.80 | 785.77 |
CORE_MID | 0.29E+09 | 0.00 | 0.29E+09 | 0.00 | 0.29E+09 | 0.34E+09 | 6335.29 | 33.08 | 2391.63 | 463.19 |
CORE_TOP | 27897902.97 | 0.00 | 27897902.97 | 0.00 | 27897902.97 | 33990283.35 | 6637.78 | 22.56 | 2099.66 | 453.51 |
PERIMETER_BOT_ZN_3 | 6492472.57 | 0.00 | 6492472.57 | 194399.86 | 6686872.43 | 4267819.30 | 5290.90 | 35.12 | 3433.98 | 785.77 |
PERIMETER_BOT_ZN_2 | 6656644.65 | 0.00 | 6656644.65 | 129599.82 | 6786244.46 | 2750345.05 | 3120.53 | 5.99 | 5633.47 | 785.77 |
PERIMETER_BOT_ZN_1 | 9563855.20 | 0.00 | 9563855.20 | 194399.86 | 9758255.06 | 4267912.63 | 3236.10 | 26.26 | 5497.64 | 785.77 |
PERIMETER_BOT_ZN_4 | 7531454.13 | 0.00 | 7531454.13 | 129599.82 | 7661053.94 | 2750345.05 | 3087.53 | 3.96 | 5668.50 | 785.77 |
PERIMETER_MID_ZN_3 | 41227654.87 | 0.00 | 41227654.87 | 455926.06 | 41683580.93 | 42678193.03 | 6003.90 | 43.82 | 2712.28 | 463.19 |
PERIMETER_MID_ZN_2 | 55134902.27 | 0.00 | 55134902.27 | 303950.50 | 55438852.76 | 27503450.52 | 3888.38 | 5.33 | 4866.29 | 1372.19 |
PERIMETER_MID_ZN_1 | 78185058.03 | 0.00 | 78185058.03 | 455926.06 | 78640984.09 | 42679126.28 | 3947.18 | 2.07 | 4810.75 | 463.19 |
PERIMETER_MID_ZN_4 | 55996567.37 | 0.00 | 55996567.37 | 303950.50 | 56300517.87 | 27503450.52 | 3878.20 | 4.31 | 4877.49 | 463.19 |
PERIMETER_TOP_ZN_3 | 4204778.51 | 0.00 | 4204778.51 | 566085.68 | 4770864.19 | 4267819.30 | 5707.75 | 41.54 | 3010.71 | 453.51 |
PERIMETER_TOP_ZN_2 | 5379515.56 | 0.00 | 5379515.56 | 377390.20 | 5756905.76 | 2750345.05 | 3999.42 | 1.30 | 4759.28 | 453.51 |
PERIMETER_TOP_ZN_1 | 7680563.69 | 0.00 | 7680563.69 | 566085.68 | 8246649.37 | 4267912.63 | 4017.56 | 1.00 | 4741.44 | 453.51 |
PERIMETER_TOP_ZN_4 | 5605944.84 | 0.00 | 5605944.84 | 377390.20 | 5983335.03 | 2750345.05 | 3991.69 | 2.10 | 4766.21 | 453.51 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.38E+09 | 0.00 | 0.38E+09 | 0.00 | 0.38E+09 | 10671554.30 | 14.94 | 107.50 | 8637.56 | 2813.50 |
Total Facility | 0.58E+10 | 0.00 | 0.58E+10 | 17732482.26 | 0.58E+10 | 0.50E+10 | 8759.33 | 4399.95 | 8745.23 | 3722.50 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 0.2743 | 0.0000 | 0.2743 | 0.0000 | 0.2743 | 1.2002 | 4781.87 | 659.44 | 501.69 |
CORE_BOTTOM | 2.3204 | 0.0000 | 2.3204 | 0.0000 | 2.3204 | 1.0778 | 2027.18 | 32.74 | 3883.08 |
CORE_MID | 13.2474 | 0.0000 | 13.2474 | 0.0000 | 13.2474 | 10.7782 | 3626.83 | 32.56 | 2283.61 |
CORE_TOP | 1.2696 | 0.0000 | 1.2696 | 0.0000 | 1.2696 | 1.0778 | 3900.49 | 22.23 | 2020.27 |
PERIMETER_BOT_ZN_3 | 0.2791 | 0.0000 | 0.2791 | 0.0047 | 0.2838 | 0.1353 | 3021.48 | 25.38 | 2896.14 |
PERIMETER_BOT_ZN_2 | 0.2818 | 0.0000 | 0.2818 | 0.0031 | 0.2849 | 0.0872 | 1020.90 | 4.21 | 4917.89 |
PERIMETER_BOT_ZN_1 | 0.4115 | 0.0000 | 0.4115 | 0.0047 | 0.4162 | 0.1353 | 1097.95 | 20.59 | 4824.45 |
PERIMETER_BOT_ZN_4 | 0.3147 | 0.0000 | 0.3147 | 0.0031 | 0.3179 | 0.0872 | 995.87 | 2.83 | 4944.30 |
PERIMETER_MID_ZN_3 | 1.8631 | 0.0000 | 1.8631 | 0.0111 | 1.8741 | 1.3533 | 3295.82 | 43.20 | 2603.98 |
PERIMETER_MID_ZN_2 | 2.3076 | 0.0000 | 2.3076 | 0.0078 | 2.3154 | 0.8721 | 1208.70 | 3.75 | 3821.56 |
PERIMETER_MID_ZN_1 | 3.5573 | 0.0000 | 3.5573 | 0.0111 | 3.5684 | 1.3533 | 1249.41 | 1.88 | 4691.71 |
PERIMETER_MID_ZN_4 | 2.5148 | 0.0000 | 2.5148 | 0.0074 | 2.5222 | 0.8721 | 1203.83 | 1.15 | 4738.01 |
PERIMETER_TOP_ZN_3 | 0.1919 | 0.0000 | 0.1919 | 0.0137 | 0.2056 | 0.1353 | 2971.95 | 41.34 | 2929.70 |
PERIMETER_TOP_ZN_2 | 0.2457 | 0.0000 | 0.2457 | 0.0092 | 0.2549 | 0.0872 | 1274.40 | 1.02 | 4667.58 |
PERIMETER_TOP_ZN_1 | 0.3520 | 0.0000 | 0.3520 | 0.0137 | 0.3658 | 0.1353 | 1287.93 | 0.78 | 4654.28 |
PERIMETER_TOP_ZN_4 | 0.2544 | 0.0000 | 0.2544 | 0.0092 | 0.2636 | 0.0872 | 1268.69 | 1.49 | 4672.82 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 12.6483 | 0.0000 | 12.6483 | 0.0000 | 12.6483 | 0.3384 | 11.44 | 107.50 | 5824.06 |
Total Facility | 254.9109 | 0.0000 | 254.9109 | 0.4346 | 255.3455 | 158.4706 | 5942.33 | 4373.53 | 5931.73 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 0.11E+09 | 0.00 | 0.11E+09 | 48026705.38 | 3156.73 | 4.99 | 5598.28 | 785.77 |
VAV_MID WITH REHEAT | 0.70E+09 | 0.00 | 0.70E+09 | 0.48E+09 | 3955.18 | 1.74 | 4803.08 | 463.19 |
VAV_TOP WITH REHEAT | 67600999.36 | 0.00 | 67600999.36 | 48026705.38 | 4021.36 | 0.94 | 4737.70 | 453.20 |
CAV_BAS | 7814372.68 | 0.00 | 7814372.68 | 37848132.68 | 7557.14 | 0.82 | 1202.04 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.51E+09 | 0.00 | 0.51E+09 | 10671554.30 | 14.94 | 0.00 | 8745.06 | 2813.50 |
AIRLOOP DATACENTER BOT | 325290.55 | 0.00 | 325290.55 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3252905.49 | 0.00 | 3252905.49 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 325290.55 | 0.00 | 325290.55 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 4.8036 | 0.0000 | 4.8036 | 1.5229 | 1032.58 | 1.80 | 4908.63 |
VAV_MID WITH REHEAT | 31.5255 | 0.0000 | 31.5255 | 15.2292 | 1254.76 | 1.71 | 4686.53 |
VAV_TOP WITH REHEAT | 3.0808 | 0.0000 | 3.0808 | 1.5229 | 1290.54 | 0.79 | 4651.67 |
CAV_BAS | 0.3652 | 0.0000 | 0.3652 | 1.2002 | 4740.14 | 0.82 | 1202.04 |
AIRLOOP DATACENTER BASEMENT | 16.8418 | 0.0000 | 16.8418 | 0.3384 | 11.44 | 0.00 | 5931.56 |
AIRLOOP DATACENTER BOT | 0.0152 | 0.0000 | 0.0152 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1520 | 0.0000 | 0.1520 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0152 | 0.0000 | 0.0152 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 40.03 | 4079.94 | 0.00 | 0.00 | 0.00 | 1690.00 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 1.06 | 3138.43 | 0.00 | 0.00 | 0.00 | 2237.12 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 1.58 | 2914.10 | 0.00 | 0.00 | 0.00 | 2442.81 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 645.69 | 512.78 | 0.00 | 54.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 107.50 | 8637.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 13.7312 | 7.2642 | 0.0000 | 0.0000 | 0.0000 | 2.4082 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 136.4751 | 50.7820 | 0.0000 | 0.0000 | 0.0000 | 22.9672 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 22.1661 | 5.1771 | 0.0000 | 0.0000 | 0.0000 | 2.2733 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.5998 | 2.0802 | 0.0000 | 1.3655 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4527 | 17.1776 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0208 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2082 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0208 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1500 |
Defaulted Fields | 1184 |
Fields with Defaults | 3957 |
Autosized Fields | 338 |
Autosizable Fields | 417 |
Autocalculated Fields | 227 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 27705.95 | 299291.91 | 28-MAY-04:30 | 2254867.53 | 05-JUL-11:00 |
Electricity:Building | 17898.34 | 217189.06 | 07-MAY-17:20 | 1104084.83 | 01-DEC-16:20 |
Electricity:Zone:BASEMENT | 640.57 | 14055.89 | 01-JAN-00:10 | 32859.63 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 17898.34 | 217189.06 | 07-MAY-17:20 | 1104084.83 | 01-DEC-16:20 |
InteriorLights:Electricity | 3221.95 | 9932.90 | 16-APR-17:20 | 325713.14 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 216.17 | 598.35 | 01-JAN-00:10 | 19402.09 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3221.95 | 9932.90 | 16-APR-17:20 | 325713.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 3221.95 | 9932.90 | 16-APR-17:20 | 325713.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 216.17 | 598.35 | 01-JAN-00:10 | 19402.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3221.95 | 9932.90 | 16-APR-17:20 | 325713.14 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 483.75 | 4990.59 | 01-JAN-00:10 | 34631.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4837.49 | 49905.77 | 01-JAN-00:10 | 346310.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1941.37 | 5373.60 | 01-JAN-00:10 | 174244.37 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1941.37 | 5373.60 | 01-JAN-00:10 | 174244.37 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 483.75 | 4990.58 | 01-JAN-00:10 | 34631.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 50.50 | 617.00 | 02-APR-17:10 | 4348.36 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 14.14 | 57.83 | 01-JAN-10:20 | 2187.81 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 14.14 | 57.83 | 01-JAN-10:20 | 2187.81 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 32.46 | 397.62 | 16-APR-17:10 | 2802.25 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 9.03 | 37.27 | 01-JAN-08:40 | 1409.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 9.03 | 37.27 | 01-JAN-08:40 | 1409.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 50.23 | 617.01 | 12-MAR-17:10 | 4348.44 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 13.87 | 57.83 | 01-JAN-08:40 | 2187.86 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 13.87 | 57.83 | 01-JAN-08:40 | 2187.86 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 32.44 | 397.61 | 12-MAR-17:10 | 2802.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 9.00 | 37.27 | 01-JAN-10:20 | 1409.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 9.00 | 37.27 | 01-JAN-10:20 | 1409.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 504.74 | 6169.98 | 02-APR-17:10 | 43483.64 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 141.09 | 578.27 | 01-JAN-10:10 | 21878.12 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 141.09 | 578.27 | 01-JAN-10:10 | 21878.12 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 324.48 | 3976.17 | 16-APR-17:10 | 28022.51 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 90.13 | 372.66 | 01-JAN-08:40 | 14099.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 90.13 | 372.66 | 01-JAN-08:40 | 14099.09 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 502.19 | 6170.07 | 12-MAR-17:10 | 43484.45 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 138.53 | 578.28 | 01-JAN-08:40 | 21878.60 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 138.53 | 578.28 | 01-JAN-08:40 | 21878.60 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 324.23 | 3976.14 | 12-MAR-17:10 | 28022.42 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 89.88 | 372.66 | 01-JAN-10:10 | 14099.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 89.88 | 372.66 | 01-JAN-10:10 | 14099.09 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 50.47 | 617.00 | 26-MAR-17:10 | 4348.36 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 14.11 | 57.83 | 01-JAN-10:10 | 2187.81 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 14.11 | 57.83 | 01-JAN-10:10 | 2187.81 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 32.45 | 397.62 | 16-APR-17:10 | 2802.25 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 9.01 | 37.27 | 01-JAN-08:40 | 1409.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 9.01 | 37.27 | 01-JAN-08:40 | 1409.91 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 50.22 | 617.01 | 12-MAR-17:10 | 4348.44 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 13.85 | 57.83 | 01-JAN-08:40 | 2187.86 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 13.85 | 57.83 | 01-JAN-08:40 | 2187.86 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 32.42 | 397.61 | 12-MAR-17:10 | 2802.24 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 8.99 | 37.27 | 01-JAN-10:10 | 1409.91 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 8.99 | 37.27 | 01-JAN-10:10 | 1409.91 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7557.51 | 95212.03 | 01-JAN-00:10 | 385103.08 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 62.65 | 303.90 | 01-JAN-00:10 | 5470.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 62.65 | 303.90 | 01-JAN-00:10 | 5470.56 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 159.04 | 1973.61 | 01-JAN-00:10 | 8244.54 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1590.36 | 19736.13 | 01-JAN-00:10 | 82445.36 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 51.55 | 250.08 | 01-JAN-00:10 | 4501.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 51.55 | 250.08 | 01-JAN-00:10 | 4501.14 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 159.04 | 1973.61 | 01-JAN-00:10 | 8244.54 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 1716.62 | 3912.07 | 06-JAN-04:40 | 617024.51 | 05-JUL-11:50 |
HeatRejection:Electricity | 417.09 | 31.23 | 06-JAN-08:50 | 88191.61 | 16-MAY-14:10 |
General:HeatRejection:Electricity | 417.09 | 31.23 | 06-JAN-08:50 | 88191.61 | 16-MAY-14:10 |
Electricity:HVAC | 5222.11 | 55722.18 | 17-SEP-04:30 | 501038.66 | 08-AUG-15:20 |
ExteriorEquipment:Electricity | 2566.61 | 20217.42 | 01-JAN-00:10 | 233439.18 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 55.01 | 979.82 | 01-JAN-00:10 | 3454.84 | 20-DEC-16:30 |
ElectricityPurchased:Facility | 27705.95 | 299291.91 | 28-MAY-04:30 | 2254867.53 | 05-JUL-11:00 |
ElectricityPurchased:Plant | 27705.95 | 299291.91 | 28-MAY-04:30 | 2254867.53 | 05-JUL-11:00 |
Cogeneration:ElectricityPurchased | 27705.95 | 299291.91 | 28-MAY-04:30 | 2254867.53 | 05-JUL-11:00 |
General:Cogeneration:ElectricityPurchased | 27705.95 | 299291.91 | 28-MAY-04:30 | 2254867.53 | 05-JUL-11:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 27705.95 | 299291.91 | 28-MAY-04:30 | 2254867.53 | 05-JUL-11:00 |
ElectricityNet:Plant | 27705.95 | 299291.91 | 28-MAY-04:30 | 2254867.53 | 05-JUL-11:00 |
Cogeneration:ElectricityNet | 27705.95 | 299291.91 | 28-MAY-04:30 | 2254867.53 | 05-JUL-11:00 |
General:Cogeneration:ElectricityNet | 27705.95 | 299291.91 | 28-MAY-04:30 | 2254867.53 | 05-JUL-11:00 |
Fans:Electricity | 2573.47 | 49193.51 | 01-JAN-00:40 | 315794.86 | 05-JUL-10:50 |
General:Fans:Electricity | 2573.47 | 49193.51 | 01-JAN-00:40 | 315794.86 | 05-JUL-10:50 |
ExteriorLights:Electricity | 357.28 | 0.00 | 01-JAN-08:20 | 40855.88 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 357.28 | 0.00 | 01-JAN-08:20 | 40855.88 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 2505.76 | 19200.00 | 01-JAN-00:10 | 229608.34 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 46.17 | 0.00 | 01-JAN-00:10 | 6524.59 | 02-JAN-07:30 |
General:HeatRecovery:Electricity | 46.17 | 0.00 | 01-JAN-00:10 | 6524.59 | 02-JAN-07:30 |
Cooling:Electricity | 1287.52 | 1528.33 | 06-JAN-08:50 | 595156.51 | 05-JUL-10:20 |
General:Cooling:Electricity | 1287.52 | 1528.33 | 06-JAN-08:50 | 595156.51 | 05-JUL-10:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1730.40 | 0.00 | 23-APR-10:00 | 100000.00 | 04-FEB-17:20 |
General:Humidifier:Electricity | 1730.40 | 0.00 | 23-APR-10:00 | 100000.00 | 04-FEB-17:20 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 513.60 | 0.00 | 01-JAN-00:10 | 62801.25 | 24-FEB-12:50 |
Water Heater:WaterSystems:Electricity | 513.60 | 0.00 | 01-JAN-00:10 | 62801.25 | 24-FEB-12:50 |
Pumps:Electricity | 315.47 | 3875.62 | 01-JAN-00:40 | 56569.26 | 05-JUL-11:10 |
General:Pumps:Electricity | 315.47 | 3875.62 | 01-JAN-00:40 | 56569.26 | 05-JUL-11:10 |
WIRED_LTG_ELECTRICITY | 90.54 | 0.00 | 01-JAN-00:10 | 9152.54 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 2901.81 | 0.00 | 01-JAN-00:40 | 2677693.85 | 09-JAN-07:30 |
NaturalGas:Plant | 2901.81 | 0.00 | 01-JAN-00:40 | 2677693.85 | 09-JAN-07:30 |
Heating:NaturalGas | 2901.81 | 0.00 | 01-JAN-00:40 | 2677693.85 | 09-JAN-07:30 |
Boiler:Heating:NaturalGas | 2901.81 | 0.00 | 01-JAN-00:40 | 2677693.85 | 09-JAN-07:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 7708.85 | 3204.95 | 06-JAN-08:50 | 3736623.89 | 05-JUL-10:40 |
PlantLoopCoolingDemand:HVAC | 7708.85 | 3204.95 | 06-JAN-08:50 | 3736623.89 | 05-JUL-10:40 |
CoolingCoils:PlantLoopCoolingDemand | 7708.85 | 3204.95 | 06-JAN-08:50 | 3736623.89 | 05-JUL-10:40 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 5869.76 | 0.00 | 18-MAY-23:10 | 0.00 | 08-JUN-12:20 |
Water:HVAC | 643.71 | 0.00 | 23-APR-10:00 | 0.00 | 01-MAR-05:10 |
Humidifier:Water | 643.71 | 0.00 | 23-APR-10:00 | 0.00 | 01-MAR-05:10 |
General:Humidifier:Water | 643.71 | 0.00 | 23-APR-10:00 | 0.00 | 01-MAR-05:10 |
MainsWater:Facility | 5869.76 | 0.00 | 18-MAY-23:10 | 0.00 | 08-JUN-12:20 |
MainsWater:HVAC | 643.71 | 0.00 | 23-APR-10:00 | 0.00 | 01-MAR-05:10 |
Humidifier:MainsWater | 643.71 | 0.00 | 23-APR-10:00 | 0.00 | 01-MAR-05:10 |
General:Humidifier:MainsWater | 643.71 | 0.00 | 23-APR-10:00 | 0.00 | 01-MAR-05:10 |
Water:Plant | 5226.05 | 0.00 | 01-JAN-00:10 | 0.00 | 08-JUN-12:20 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 5226.05 | 0.00 | 01-JAN-00:10 | 0.00 | 08-JUN-12:20 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 2945.89 | 0.00 | 01-JAN-00:10 | 0.00 | 18-MAY-14:10 |
General:HeatRejection:Water | 2945.89 | 0.00 | 01-JAN-00:10 | 0.00 | 18-MAY-14:10 |
HeatRejection:MainsWater | 2945.89 | 0.00 | 01-JAN-00:10 | 0.00 | 18-MAY-14:10 |
General:HeatRejection:MainsWater | 2945.89 | 0.00 | 01-JAN-00:10 | 0.00 | 18-MAY-14:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 46243.86 | 92325.49 | 01-JAN-06:00 | 13599633.95 | 05-JUL-12:10 |
EnergyTransfer:Building | 19031.05 | 89201.46 | 27-JAN-22:50 | 1759516.05 | 26-DEC-06:10 |
EnergyTransfer:Zone:BASEMENT | 148.59 | 0.00 | 01-JAN-00:10 | 112865.20 | 25-NOV-07:20 |
Heating:EnergyTransfer | 1327.98 | 0.00 | 01-FEB-00:40 | 1456130.51 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 850.44 | 17-JAN-07:30 |
General:Heating:EnergyTransfer | 1327.98 | 0.00 | 01-FEB-00:40 | 1456130.51 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 850.44 | 17-JAN-07:30 |
Cooling:EnergyTransfer | 17703.06 | 83304.68 | 01-JAN-10:00 | 1685208.08 | 08-AUG-15:20 |
Cooling:EnergyTransfer:Zone:BASEMENT | 148.59 | 0.00 | 01-JAN-00:10 | 112865.20 | 25-NOV-07:20 |
General:Cooling:EnergyTransfer | 17703.06 | 83304.68 | 01-JAN-10:00 | 1685208.08 | 08-AUG-15:20 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 148.59 | 0.00 | 01-JAN-00:10 | 112865.20 | 25-NOV-07:20 |
EnergyTransfer:Zone:CORE_BOTTOM | 833.87 | 0.00 | 01-JAN-00:10 | 71483.60 | 08-AUG-10:30 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 833.87 | 0.00 | 01-JAN-00:10 | 71483.60 | 08-AUG-10:30 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 833.87 | 0.00 | 01-JAN-00:10 | 71483.60 | 08-AUG-10:30 |
EnergyTransfer:Zone:CORE_MID | 4135.40 | 0.00 | 01-JAN-00:40 | 481996.94 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 22.03 | 0.00 | 01-JAN-00:10 | 481996.94 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 22.03 | 0.00 | 01-JAN-00:10 | 481996.94 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4113.37 | 0.00 | 01-JAN-00:40 | 443859.10 | 05-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4113.37 | 0.00 | 01-JAN-00:40 | 443859.10 | 05-JUL-13:50 |
EnergyTransfer:Zone:CORE_TOP | 374.59 | 0.00 | 01-JAN-00:40 | 71777.33 | 09-JAN-05:30 |
Heating:EnergyTransfer:Zone:CORE_TOP | 31.29 | 0.00 | 01-JAN-00:40 | 71777.33 | 09-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 31.29 | 0.00 | 01-JAN-00:40 | 71777.33 | 09-JAN-05:30 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 343.30 | 0.00 | 01-JAN-00:20 | 49478.61 | 30-JUN-15:20 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 343.30 | 0.00 | 01-JAN-00:20 | 49478.61 | 30-JUN-15:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 91.09 | 0.00 | 01-JAN-00:10 | 13299.69 | 29-JUN-14:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 4.75 | 0.00 | 01-JAN-00:10 | 12078.73 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 4.75 | 0.00 | 01-JAN-00:10 | 12078.73 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 86.35 | 0.00 | 01-JAN-00:10 | 13299.69 | 29-JUN-14:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 86.35 | 0.00 | 01-JAN-00:10 | 13299.69 | 29-JUN-14:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 89.34 | 0.00 | 01-JAN-00:10 | 19148.93 | 31-JUL-08:10 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 3.25 | 0.00 | 01-JAN-00:10 | 9170.30 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 3.25 | 0.00 | 01-JAN-00:10 | 9170.30 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 86.09 | 0.00 | 01-JAN-00:10 | 19148.93 | 31-JUL-08:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 86.09 | 0.00 | 01-JAN-00:10 | 19148.93 | 31-JUL-08:10 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 139.74 | 0.00 | 01-JAN-00:10 | 26458.16 | 01-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 4.52 | 0.00 | 01-JAN-00:10 | 15000.50 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 4.52 | 0.00 | 01-JAN-00:10 | 15000.50 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 135.22 | 0.00 | 01-JAN-00:10 | 26458.16 | 01-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 135.22 | 0.00 | 01-JAN-00:10 | 26458.16 | 01-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 106.81 | 0.00 | 01-JAN-00:10 | 20903.40 | 24-JUL-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.89 | 0.00 | 01-JAN-00:10 | 7220.65 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.89 | 0.00 | 01-JAN-00:10 | 7220.65 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 105.92 | 0.00 | 01-JAN-00:10 | 20903.40 | 24-JUL-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 105.92 | 0.00 | 01-JAN-00:10 | 20903.40 | 24-JUL-17:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 726.57 | 0.00 | 01-JAN-00:40 | 132425.03 | 02-JAN-04:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 308.32 | 0.00 | 01-JAN-00:40 | 132425.03 | 02-JAN-04:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 308.32 | 0.00 | 01-JAN-00:40 | 132425.03 | 02-JAN-04:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 418.25 | 0.00 | 01-JAN-00:10 | 106868.88 | 29-JUN-14:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 418.25 | 0.00 | 01-JAN-00:10 | 106868.88 | 29-JUN-14:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 733.81 | 0.00 | 01-JAN-00:40 | 183954.02 | 24-JUL-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 173.63 | 0.00 | 01-JAN-00:40 | 149728.01 | 26-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 173.63 | 0.00 | 01-JAN-00:40 | 149728.01 | 26-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 560.18 | 0.00 | 01-JAN-00:20 | 183954.02 | 24-JUL-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 560.18 | 0.00 | 01-JAN-00:20 | 183954.02 | 24-JUL-08:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1158.60 | 0.00 | 01-JAN-00:40 | 269251.46 | 01-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 167.44 | 0.00 | 01-JAN-00:40 | 215770.92 | 26-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 167.44 | 0.00 | 01-JAN-00:40 | 215770.92 | 26-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 991.17 | 0.00 | 01-JAN-00:20 | 269251.46 | 01-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 991.17 | 0.00 | 01-JAN-00:20 | 269251.46 | 01-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 743.58 | 0.00 | 01-JAN-00:40 | 200702.92 | 30-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 140.05 | 0.00 | 01-JAN-00:40 | 141516.37 | 09-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 140.05 | 0.00 | 01-JAN-00:40 | 141516.37 | 09-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 603.53 | 0.00 | 01-JAN-00:20 | 200702.92 | 30-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 603.53 | 0.00 | 01-JAN-00:20 | 200702.92 | 30-JUN-17:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 96.29 | 0.00 | 01-JAN-00:40 | 16141.85 | 09-JAN-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 58.31 | 0.00 | 01-JAN-00:40 | 16141.85 | 09-JAN-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 58.31 | 0.00 | 01-JAN-00:40 | 16141.85 | 09-JAN-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 37.98 | 0.00 | 01-JAN-00:10 | 11458.23 | 29-JUN-14:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 37.98 | 0.00 | 01-JAN-00:10 | 11458.23 | 29-JUN-14:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 84.70 | 0.00 | 01-JAN-00:40 | 19096.67 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 33.29 | 0.00 | 01-JAN-00:40 | 19096.67 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 33.29 | 0.00 | 01-JAN-00:40 | 19096.67 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 51.40 | 0.00 | 01-JAN-00:10 | 18500.57 | 24-JUL-08:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 51.40 | 0.00 | 01-JAN-00:10 | 18500.57 | 24-JUL-08:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 126.95 | 0.00 | 01-JAN-00:40 | 27867.54 | 01-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 37.18 | 0.00 | 01-JAN-00:40 | 24696.11 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 37.18 | 0.00 | 01-JAN-00:40 | 24696.11 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 89.77 | 0.00 | 01-JAN-00:20 | 27867.54 | 01-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 89.77 | 0.00 | 01-JAN-00:20 | 27867.54 | 01-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 83.72 | 0.00 | 01-JAN-00:40 | 20686.95 | 30-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 27.48 | 0.00 | 01-JAN-00:40 | 18701.28 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 27.48 | 0.00 | 01-JAN-00:40 | 18701.28 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 56.24 | 0.00 | 01-JAN-00:20 | 20686.95 | 30-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 56.24 | 0.00 | 01-JAN-00:20 | 20686.95 | 30-JUN-17:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 89.87 | 0.00 | 01-JAN-00:10 | 13875.66 | 24-JUL-05:30 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 7.29 | 0.00 | 01-JAN-00:10 | 7842.42 | 02-JAN-12:00 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 7.29 | 0.00 | 01-JAN-00:10 | 7842.42 | 02-JAN-12:00 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 82.58 | 0.00 | 01-JAN-00:10 | 13875.66 | 24-JUL-05:30 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 82.58 | 0.00 | 01-JAN-00:10 | 13875.66 | 24-JUL-05:30 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 567.63 | 0.00 | 01-JAN-00:40 | 195947.91 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 215.89 | 0.00 | 01-JAN-00:40 | 195947.91 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 215.89 | 0.00 | 01-JAN-00:40 | 195947.91 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 351.74 | 0.00 | 01-JAN-00:10 | 79387.24 | 30-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 351.74 | 0.00 | 01-JAN-00:10 | 79387.24 | 30-JUN-16:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 126.55 | 0.00 | 01-JAN-00:40 | 34956.19 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 83.92 | 0.00 | 01-JAN-00:40 | 34956.19 | 09-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 83.92 | 0.00 | 01-JAN-00:40 | 34956.19 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 42.63 | 0.00 | 01-JAN-00:10 | 20108.72 | 30-JUN-14:40 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 42.63 | 0.00 | 01-JAN-00:10 | 20108.72 | 30-JUN-14:40 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 137.14 | 2.79 | 01-JAN-18:30 | 8912.97 | 13-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.05 | 0.00 | 01-JAN-14:20 | 598.35 | 01-JAN-08:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.05 | 0.00 | 01-JAN-14:20 | 598.35 | 01-JAN-08:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 137.09 | 0.00 | 01-JAN-00:10 | 8912.97 | 13-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 137.09 | 0.00 | 01-JAN-00:10 | 8912.97 | 13-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1136.60 | 5.64 | 17-JAN-13:40 | 84228.78 | 21-APR-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 7.45 | 0.00 | 02-JAN-07:20 | 6331.38 | 01-JAN-17:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 7.45 | 0.00 | 02-JAN-07:20 | 6331.38 | 01-JAN-17:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1129.15 | 0.00 | 01-JAN-00:10 | 84228.78 | 21-APR-18:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1129.15 | 0.00 | 01-JAN-00:10 | 84228.78 | 21-APR-18:20 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 102.11 | 0.35 | 21-JAN-15:40 | 8404.38 | 21-APR-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.95 | 0.00 | 02-JAN-07:20 | 643.98 | 01-JAN-17:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.95 | 0.00 | 02-JAN-07:20 | 643.98 | 01-JAN-17:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 101.16 | 0.00 | 01-JAN-00:10 | 8404.38 | 21-APR-18:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 101.16 | 0.00 | 01-JAN-00:10 | 8404.38 | 21-APR-18:20 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7197.50 | 83302.47 | 01-JAN-09:40 | 374724.84 | 08-AUG-21:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7197.50 | 83302.47 | 01-JAN-09:40 | 374724.84 | 08-AUG-21:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7197.50 | 83302.47 | 01-JAN-09:40 | 374724.84 | 08-AUG-21:10 |
PlantLoopHeatingDemand:Facility | 2708.21 | 0.00 | 01-JAN-00:40 | 2252518.90 | 09-JAN-07:20 |
PlantLoopHeatingDemand:Plant | 508.68 | 0.00 | 01-JAN-00:10 | 62462.67 | 24-FEB-12:20 |
WaterSystems:PlantLoopHeatingDemand | 508.68 | 0.00 | 01-JAN-00:10 | 62462.67 | 24-FEB-12:20 |
General:WaterSystems:PlantLoopHeatingDemand | 508.68 | 0.00 | 01-JAN-00:10 | 62462.67 | 24-FEB-12:20 |
EnergyTransfer:HVAC | 11913.49 | 1989.06 | 01-JAN-08:40 | 3573892.02 | 05-JUL-10:40 |
HeatingCoils:EnergyTransfer | 2199.53 | 0.00 | 01-JAN-00:40 | 2232371.44 | 09-JAN-07:20 |
PlantLoopHeatingDemand:HVAC | 2199.53 | 0.00 | 01-JAN-00:40 | 2232371.44 | 09-JAN-07:20 |
HeatingCoils:PlantLoopHeatingDemand | 2199.53 | 0.00 | 01-JAN-00:40 | 2232371.44 | 09-JAN-07:20 |
CoolingCoils:EnergyTransfer | 6891.78 | 1676.62 | 06-JAN-08:50 | 3573892.02 | 05-JUL-10:40 |
HeatRecoveryForHeating:EnergyTransfer | 2698.49 | 0.00 | 01-JAN-00:10 | 907094.66 | 13-JAN-12:20 |
HeatRecoveryForCooling:EnergyTransfer | 123.68 | 0.00 | 01-JAN-00:10 | 504816.46 | 15-JUL-14:00 |
EnergyTransfer:Plant | 15299.32 | 0.00 | 01-JAN-00:40 | 8607000.40 | 05-JUL-12:10 |
LoopToLoop:EnergyTransfer | 4038.30 | 0.00 | 01-JAN-00:10 | 2832373.74 | 05-JUL-10:40 |
WaterSystems:EnergyTransfer | 508.68 | 0.00 | 01-JAN-00:10 | 62462.67 | 24-FEB-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 508.68 | 0.00 | 01-JAN-00:10 | 62462.67 | 24-FEB-12:20 |
Boilers:EnergyTransfer | 2188.06 | 0.00 | 01-JAN-00:40 | 2216897.93 | 09-JAN-07:30 |
Chillers:EnergyTransfer | 4046.92 | 0.00 | 01-JAN-00:10 | 2656040.55 | 05-JUL-10:20 |
HeatRejection:EnergyTransfer | 4517.37 | 0.00 | 01-JAN-00:10 | 3090862.72 | 05-JUL-10:20 |
General:HeatRejection:EnergyTransfer | 4517.37 | 0.00 | 01-JAN-00:10 | 3090862.72 | 05-JUL-10:20 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.001 | -148.581 | 0.000 | 0.000 | 60.062 | 216.171 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -552.050 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -833.871 | 0.000 | 0.000 | 83.463 | 194.137 | 289.614 | 0.000 | 0.000 | 0.000 | 266.658 | 0.000 | 0.000 | 0.000 | 0.000 | -0.007 |
CORE_MID | 0.000 | 0.000 | 22.029 | -4113.360 | 0.000 | 0.000 | 864.436 | 1941.366 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1610.598 |
CORE_TOP | 0.000 | 0.000 | 31.285 | -343.299 | 0.000 | 0.000 | 89.752 | 194.137 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -261.488 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 4.748 | -86.345 | 0.000 | 0.000 | 11.012 | 14.137 | 36.365 | 30.788 | 0.000 | 0.013 | 87.674 | 0.000 | -93.573 | 0.000 | -4.819 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 3.248 | -86.090 | 0.000 | 0.000 | 7.131 | 9.026 | 23.435 | 63.986 | 0.000 | 0.009 | 39.501 | 0.000 | -57.073 | 0.000 | -3.174 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 4.520 | -135.223 | 0.000 | 0.000 | 10.884 | 13.866 | 36.366 | 137.429 | 0.000 | 0.013 | 18.283 | 0.000 | -81.352 | 0.000 | -4.787 | -0.001 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.893 | -105.917 | 0.000 | 0.000 | 7.044 | 9.002 | 23.435 | 64.597 | 0.000 | 0.009 | 65.798 | 0.000 | -61.550 | 0.000 | -3.312 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 308.317 | -418.250 | 0.000 | 0.000 | 115.251 | 141.091 | 363.654 | 326.593 | 0.000 | 0.329 | 112.374 | 0.000 | -847.909 | 0.000 | -101.449 | -0.003 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 173.629 | -560.176 | 0.000 | 0.000 | 54.607 | 90.130 | 234.352 | 649.865 | 0.000 | 0.230 | 0.011 | 0.000 | -524.986 | 0.000 | -68.259 | -49.392 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 167.434 | -991.162 | 0.000 | 0.000 | 111.859 | 138.530 | 363.660 | 1381.225 | 0.000 | 0.309 | 0.003 | 0.000 | -772.904 | 0.000 | -106.026 | -292.923 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 140.053 | -603.524 | 0.000 | 0.000 | 74.476 | 89.883 | 234.351 | 659.568 | 0.000 | 0.209 | 30.938 | 0.000 | -556.206 | 0.000 | -69.747 | -0.003 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 58.313 | -37.978 | 0.000 | 0.000 | 11.686 | 14.108 | 36.365 | 33.286 | 0.000 | 0.040 | 0.001 | 0.000 | -81.523 | 0.000 | -12.165 | -22.133 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 33.294 | -51.404 | 0.000 | 0.000 | 7.471 | 9.013 | 23.435 | 65.376 | 0.000 | 0.027 | 0.001 | 0.000 | -50.655 | 0.000 | -8.225 | -28.332 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 37.175 | -89.773 | 0.000 | 0.000 | 11.355 | 13.852 | 36.366 | 138.900 | 0.000 | 0.037 | 0.000 | 0.000 | -74.169 | 0.000 | -12.673 | -61.070 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 27.484 | -56.238 | 0.000 | 0.000 | 7.529 | 8.988 | 23.435 | 66.247 | 0.000 | 0.025 | 0.001 | 0.000 | -53.804 | 0.000 | -8.397 | -15.269 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.051 | -137.092 | 0.000 | 0.000 | 0.950 | 5.155 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -22.945 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 7.446 | -1129.150 | 0.000 | 0.000 | 9.553 | 51.551 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -478.206 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.953 | -101.161 | 0.000 | 0.000 | 0.961 | 5.155 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -59.789 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7197.501 | 0.000 | 0.000 | 20.491 | 62.653 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -380.500 |
GROUNDFLOOR_PLENUM | 7.292 | -82.580 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.021 | 85.429 | 0.000 | 0.000 | 0.000 | -10.161 | -0.001 |
MIDFLOOR_PLENUM | 215.898 | -351.736 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.449 | 304.786 | 0.000 | 0.000 | 0.000 | -169.396 | -0.014 |
TOPFLOOR_PLENUM | 83.922 | -42.627 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.035 | 0.003 | 0.000 | 0.000 | 0.000 | -18.382 | -22.948 |
Total Facility | 307.111 | -476.944 | 1020.871 | -17226.094 | 0.000 | 0.000 | 1559.974 | 3221.948 | 14676.396 | 3617.862 | 0.000 | 1.755 | 1011.460 | 0.000 | -3255.705 | 0.000 | -600.972 | -3857.673 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 25-NOV-07:11 | 0.00 | 0.00 | 0.00 | -134174.60 | 0.00 | 0.00 | 607.85 | 2155.87 | 13457.54 | 0.00 | 0.00 | 0.00 | 117953.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 29-SEP-04:12 | 0.00 | 0.00 | 0.00 | -98789.77 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 92314.77 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 30-MAY-04:12 | 0.00 | 0.00 | 0.00 | -861969.40 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 797219.57 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 09-AUG-04:12 | 0.00 | 0.00 | 0.00 | -80696.88 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 74221.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 23-JUL-15:12 | 0.00 | 0.00 | 0.00 | -18699.63 | 0.00 | 0.00 | 38.38 | 57.83 | 720.18 | 6470.37 | 0.00 | 54.37 | 11358.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 23-JUL-09:12 | 0.00 | 0.00 | 0.00 | -29996.01 | 0.00 | 0.00 | 17.19 | 37.27 | 464.11 | 20062.98 | 0.00 | 0.00 | 9432.26 | 0.00 | -0.00 | 0.00 | -17.80 | 0.00 |
PERIMETER_BOT_ZN_1 | 13-AUG-12:42 | 0.00 | 0.00 | 0.00 | -36879.04 | 0.00 | 0.00 | 27.31 | 57.83 | 720.19 | 28491.58 | 0.00 | 0.00 | 7669.83 | 0.00 | -0.00 | 0.00 | -87.71 | 0.00 |
PERIMETER_BOT_ZN_4 | 23-APR-16:21 | 0.00 | 0.00 | 0.00 | -38054.75 | 0.00 | 0.00 | 10.28 | 37.27 | 464.11 | 27189.14 | 0.00 | 0.00 | 10450.48 | 0.00 | -0.00 | 0.00 | -96.52 | 0.00 |
PERIMETER_MID_ZN_3 | 25-JUN-11:21 | 0.00 | 0.00 | 0.00 | -153748.65 | 0.00 | 0.00 | 439.78 | 578.27 | 7201.84 | 75066.96 | 0.00 | 92.74 | 70369.07 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 25-JUN-08:41 | 0.00 | 0.00 | 0.00 | -335958.69 | 0.00 | 0.00 | 155.57 | 372.66 | 4641.14 | 201817.99 | 0.00 | 0.00 | 130171.87 | 0.00 | -0.00 | 0.00 | -1200.54 | 0.00 |
PERIMETER_MID_ZN_1 | 04-SEP-13:01 | 0.00 | 0.00 | 0.00 | -394829.85 | 0.00 | 0.00 | 238.14 | 578.28 | 7201.95 | 306914.00 | 0.00 | 0.00 | 86774.63 | 0.00 | -0.00 | 0.00 | -6877.15 | 0.00 |
PERIMETER_MID_ZN_4 | 23-APR-16:51 | 0.00 | 0.00 | 0.00 | -360333.40 | 0.00 | 0.00 | 128.32 | 372.66 | 4641.11 | 251637.12 | 0.00 | 0.00 | 105359.84 | 0.00 | -0.00 | 0.00 | -1805.64 | 0.00 |
PERIMETER_TOP_ZN_3 | 25-JUN-11:31 | 0.00 | 0.00 | 0.00 | -17924.14 | 0.00 | 0.00 | 42.41 | 57.83 | 720.18 | 6610.39 | 0.00 | 0.00 | 10500.05 | 0.00 | -0.00 | 0.00 | -6.73 | 0.00 |
PERIMETER_TOP_ZN_2 | 25-JUN-08:11 | 0.00 | 0.00 | 0.00 | -33522.09 | 0.00 | 0.00 | 15.83 | 37.27 | 464.11 | 23058.65 | 0.00 | 0.00 | 10123.00 | 0.00 | -0.00 | 0.00 | -176.77 | 0.00 |
PERIMETER_TOP_ZN_1 | 04-SEP-12:31 | 0.00 | 0.00 | 0.00 | -40758.26 | 0.00 | 0.00 | 25.06 | 57.83 | 720.19 | 32788.64 | 0.00 | 0.00 | 8043.52 | 0.00 | -0.00 | 0.00 | -876.98 | 0.00 |
PERIMETER_TOP_ZN_4 | 14-MAY-17:21 | 0.00 | 0.00 | 0.00 | -36702.73 | 0.00 | 0.00 | 0.00 | 37.27 | 360.35 | 26218.40 | 0.00 | 0.00 | 10482.07 | 0.00 | -0.00 | 0.00 | -395.36 | 0.00 |
DATACENTER_BOT_ZN_6 | 13-AUG-18:33 | 0.00 | 0.00 | 0.00 | -8912.97 | 0.00 | 0.00 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 1093.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 21-APR-18:20 | 0.00 | 0.00 | 0.00 | -84222.64 | 0.00 | 0.00 | 106.16 | 1500.36 | 77944.22 | 0.00 | 0.00 | 0.00 | 4671.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 21-APR-18:20 | 0.00 | 0.00 | 0.00 | -8403.78 | 0.00 | 0.00 | 10.62 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 448.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 08-AUG-21:02 | 0.00 | 0.00 | 0.00 | -379139.38 | 0.00 | 0.00 | 110.44 | 607.86 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1211.44 |
GROUNDFLOOR_PLENUM | 24-JUL-05:10 | 0.00 | -17599.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17648.20 | 0.00 | -0.00 | 0.00 | -48.89 | 0.00 |
MIDFLOOR_PLENUM | 02-DEC-04:01 | 0.00 | -143964.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161488.76 | 0.00 | -0.00 | 0.00 | -17524.18 | 0.00 |
TOPFLOOR_PLENUM | 30-JUN-14:40 | 0.00 | -20109.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.28 | 19959.64 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-JUL-05:03 | 0.00 | -44620.85 | 0.00 | -1817340.61 | 0.00 | 0.00 | 15485.37 | 10917.52 | 497997.76 | 123025.71 | 0.00 | 0.00 | 1235962.92 | 0.00 | -18498.04 | 0.00 | -2929.78 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 17-JAN-07:30 | 0.00 | 0.00 | 850.39 | 0.00 | 0.00 | 0.00 | 2022.59 | 6467.36 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -22797.88 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-04:01 | 0.00 | 0.00 | 563320.64 | 0.00 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -628070.47 |
CORE_TOP | 09-JAN-04:01 | 0.00 | 0.00 | 80355.63 | 0.00 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -86830.62 |
PERIMETER_BOT_ZN_3 | 09-JAN-04:01 | 0.00 | 0.00 | 14095.39 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9015.55 | 0.00 | -422.04 | -5470.83 |
PERIMETER_BOT_ZN_2 | 09-JAN-04:01 | 0.00 | 0.00 | 16832.94 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5986.17 | 0.00 | -282.11 | -11088.61 |
PERIMETER_BOT_ZN_1 | 09-JAN-04:01 | 0.00 | 0.00 | 24113.58 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -9049.06 | 0.00 | -421.77 | -15455.79 |
PERIMETER_BOT_ZN_4 | 09-JAN-04:01 | 0.00 | 0.00 | 14611.29 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6264.81 | 0.00 | -288.15 | -8582.28 |
PERIMETER_MID_ZN_3 | 01-JAN-08:61 | 0.00 | 0.00 | 142214.61 | 0.00 | 0.00 | 0.00 | 915.30 | 1215.36 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -74995.17 | 0.00 | -14143.99 | -62407.95 |
PERIMETER_MID_ZN_2 | 02-JAN-04:01 | 0.00 | 0.00 | 219457.05 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -41346.92 | 0.00 | -7651.18 | -175698.43 |
PERIMETER_MID_ZN_1 | 01-JAN-08:61 | 0.00 | 0.00 | 275744.38 | 0.00 | 0.00 | 0.00 | 909.93 | 1215.39 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -77862.81 | 0.00 | -14400.90 | -192807.94 |
PERIMETER_MID_ZN_4 | 02-JAN-04:01 | 0.00 | 0.00 | 220281.40 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -41849.37 | 0.00 | -7697.31 | -175974.18 |
PERIMETER_TOP_ZN_3 | 09-JAN-05:21 | 0.00 | 0.00 | 17484.49 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8408.68 | 0.00 | -1310.55 | -8578.29 |
PERIMETER_TOP_ZN_2 | 12-FEB-23:02 | 0.00 | 0.00 | 24831.99 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 360.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4043.23 | 0.00 | -2636.07 | -18556.52 |
PERIMETER_TOP_ZN_1 | 08-JAN-08:62 | 0.00 | 0.00 | 30202.78 | 0.00 | 0.00 | 0.00 | 91.59 | 121.54 | 720.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6840.88 | 0.00 | -1820.40 | -22474.83 |
PERIMETER_TOP_ZN_4 | 08-JAN-08:62 | 0.00 | 0.00 | 26308.96 | 0.00 | 0.00 | 0.00 | 59.10 | 78.32 | 464.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4718.85 | 0.00 | -1228.27 | -20963.38 |
DATACENTER_BOT_ZN_6 | 01-JAN-08:20 | 0.00 | 0.00 | 598.77 | 0.00 | 0.00 | 0.00 | 5.32 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2577.70 |
DATACENTER_MID_ZN_6 | 01-JAN-17:05 | 0.00 | 0.00 | 6497.96 | 0.00 | 0.00 | 0.00 | 66.23 | 250.08 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -26300.32 |
DATACENTER_TOP_ZN_6 | 01-JAN-17:05 | 0.00 | 0.00 | 661.63 | 0.00 | 0.00 | 0.00 | 7.14 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2642.39 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 26-MAR-14:51 | 17961.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -405.48 | -17556.16 |
MIDFLOOR_PLENUM | 26-MAR-16:01 | 215956.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -6976.01 | -208980.07 |
TOPFLOOR_PLENUM | 09-JAN-05:41 | 35621.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1743.04 | -33878.28 |
Total Facility | 02-JAN-06:01 | 68823.71 | 97690.07 | 1538328.43 | -97690.07 | 0.00 | 0.00 | 23085.41 | 10917.52 | 261414.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -251680.59 | 0.00 | -10196.55 | -1640692.90 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 12.3755 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.3051 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 120.0418 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 96.5912 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 12.2202 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.5139 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.8265 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.8265 | 0.2060 | 1.0000 | Not calculated | 1.2002 | 0.2060 | ||
AIRLOOP DATACENTER BASEMENT | 25.6324 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 25.6324 | 0.0132 | 1.0000 | Not calculated | 0.3384 | 0.0132 | ||
AIRLOOP DATACENTER BOT | 0.5321 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5321 | 0.0294 | 1.0000 | Not calculated | 0.0156 | 0.0294 | ||
AIRLOOP DATACENTER MID | 5.1258 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.1258 | 0.0305 | 1.0000 | Not calculated | 0.1563 | 0.0305 | ||
AIRLOOP DATACENTER TOP | 0.5196 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5196 | 0.0301 | 1.0000 | Not calculated | 0.0156 | 0.0301 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 6.1877 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.2631 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 60.0209 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 32.3460 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 6.1101 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.3276 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 0.0000 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 0.0000 | 1.0000 | 1.0000 | Not calculated | 1.2002 | |||
AIRLOOP DATACENTER BASEMENT | 25.6324 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 25.6324 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0132 | ||
AIRLOOP DATACENTER BOT | 0.5321 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5321 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0294 | ||
AIRLOOP DATACENTER MID | 5.1258 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.1258 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0305 | ||
AIRLOOP DATACENTER TOP | 0.5196 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5196 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0301 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 5.8265 | 5.8265 | 0.0000 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.1148 | 6.1148 | 1.9690 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 57.5154 | 57.5154 | 19.3252 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.6649 | 5.6649 | 1.9771 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0237 | 1.0237 | 0.2467 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5427 | 1.5427 | 0.3085 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8581 | 1.8581 | 0.3716 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8362 | 1.8362 | 0.3672 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.5464 | 9.5464 | 2.4248 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 16.5362 | 16.5362 | 3.3072 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 19.0673 | 19.0673 | 3.8135 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 17.3765 | 17.3765 | 3.4753 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0958 | 1.0958 | 0.2586 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6537 | 1.6537 | 0.3307 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0007 | 2.0007 | 0.4001 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8050 | 1.8050 | 0.3610 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5321 | 0.5321 | 0.5321 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.1258 | 5.1258 | 5.1258 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5196 | 0.5196 | 0.5196 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 25.6324 | 25.6324 | 25.6324 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 12.3755 | 10.3051 | 12.3755 | 3.2631 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 120.0418 | 96.5912 | 120.0418 | 32.3460 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 12.2202 | 10.5139 | 12.2202 | 3.3276 | 0.0000 | 1.0000 |
CAV_BAS | 5.8265 | 5.8265 | 5.8265 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 25.6324 | 25.6324 | 25.6324 | 25.6324 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5321 | 0.5321 | 0.5321 | 0.5321 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.1258 | 5.1258 | 5.1258 | 5.1258 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5196 | 0.5196 | 0.5196 | 0.5196 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 0.0000 | 0.0000 | 0.0000 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0574 | 3.0574 | 1.9690 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 28.7577 | 28.7577 | 19.3252 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8325 | 2.8325 | 1.9771 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5119 | 0.5119 | 0.2467 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7713 | 0.7713 | 0.3085 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9290 | 0.9290 | 0.3716 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9181 | 0.9181 | 0.3672 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.7732 | 4.7732 | 2.4248 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.2681 | 8.2681 | 3.3072 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.5336 | 9.5336 | 3.8135 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.6883 | 8.6883 | 3.4753 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5479 | 0.5479 | 0.2586 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8269 | 0.8269 | 0.3307 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0003 | 1.0003 | 0.4001 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9025 | 0.9025 | 0.3610 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5321 | 0.5321 | 0.5321 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.1258 | 5.1258 | 5.1258 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5196 | 0.5196 | 0.5196 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 25.6324 | 25.6324 | 25.6324 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 6.1877 | 3.2631 | 3.2631 | 3.2631 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 60.0209 | 32.3460 | 32.3460 | 32.3460 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 6.1101 | 3.3276 | 3.3276 | 3.3276 | 0.0000 | 1.0000 |
CAV_BAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 25.6324 | 25.6324 | 25.6324 | 25.6324 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5321 | 0.5321 | 0.5321 | 0.5321 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.1258 | 5.1258 | 5.1258 | 5.1258 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5196 | 0.5196 | 0.5196 | 0.5196 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 193.17 |
Number of hours cooling loads not met | 4304.67 |
Number of hours not met | 4421.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 2901.81 | 2677693.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1287.52 | 595156.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3221.95 | 325713.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 357.28 | 40855.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 55.01 | 3454.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 2505.76 | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2573.47 | 315794.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 315.47 | 56569.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 417.09 | 88191.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1730.40 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 46.17 | 6524.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 513.60 | 62801.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 27705.95 |
Natural Gas | 0.00 | 2901.81 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 30607.76 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 69.56 |
Space Heating | 0.00 |
Space Cooling | 27.80 |
Fans (All) | 55.56 |
Service Water Heating | 11.09 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 598.14 |
Subtotal | 598.14 |
Natural Gas [MJ/m2] | |
Space Heating | 62.65 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 62.65 |
Subtotal | 62.65 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 10.53 |
Space Heating | 9.48 |
Space Cooling | 4.21 |
Fans (All) | 8.41 |
Service Water Heating | 1.68 |
Receptacle Equipment | 47.95 |
Miscellaneous | 17.75 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 2719.50 | 145.00 | 89.67 | 5805.00 | 0.83 |
CORE_BOTTOM | 8519.67 | 240.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8676.33 | 83.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8693.83 | 66.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8682.83 | 77.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8560.17 | 199.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8753.33 | 6.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8711.83 | 48.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8702.17 | 57.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8629.67 | 130.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8750.67 | 9.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8711.83 | 48.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8706.17 | 53.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8646.50 | 113.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8215.67 | 544.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8193.33 | 566.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8183.33 | 576.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6982.33 | 1773.00 | 4.67 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8731.00 | 29.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8735.33 | 24.67 | 0.00 | 0.00 | 0.00 |
Min | 2719.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1773.00 | 89.67 | 5805.00 | 0.83 |
Average | 8295.02 | 208.45 | 4.10 | 252.39 | 0.04 |
Sum | 190785.50 | 4794.33 | 94.33 | 5805.00 | 0.83 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 109171.50 | 8205.50 | 4042.50 | 247078.17 | 118.33 |
CORE_BOTTOM | 330538.00 | 275.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1948.33 | 319.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1939.17 | 328.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1935.67 | 332.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 81674.67 | 21615.50 | 104.83 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 330813.00 | 21615.50 | 4042.50 | 247078.17 | 118.33 |
Average | 68055.75 | 1351.17 | 180.32 | 10742.53 | 5.14 |
Sum | 1565282.33 | 31076.83 | 4147.33 | 247078.17 | 118.33 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 2691.33 | 172.67 | 63.17 | 4351.67 | 1481.17 |
CORE_BOTTOM | 8132.33 | 627.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8327.83 | 432.17 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8372.33 | 387.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8249.17 | 510.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8433.50 | 326.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8339.00 | 421.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8243.17 | 516.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8439.00 | 321.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8456.17 | 303.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8371.17 | 388.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8290.83 | 469.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8473.33 | 286.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8479.33 | 280.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8406.67 | 353.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8334.17 | 425.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8524.17 | 235.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8503.17 | 256.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8501.33 | 258.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7153.00 | 1607.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8186.50 | 573.50 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8320.00 | 440.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8257.33 | 502.67 | 0.00 | 0.00 | 0.00 |
Min | 2691.33 | 172.67 | 0.00 | 0.00 | 0.00 |
Max | 8524.17 | 1607.00 | 63.17 | 4351.67 | 1481.17 |
Average | 8064.56 | 439.09 | 2.75 | 189.20 | 64.40 |
Sum | 185484.83 | 10099.17 | 63.17 | 4351.67 | 1481.17 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 108826.17 | 8575.00 | 2944.17 | 121081.50 | 127189.17 |
CORE_BOTTOM | 329168.33 | 1644.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330041.50 | 771.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330025.83 | 787.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38858.33 | 66.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24901.50 | 7.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38883.67 | 41.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24901.50 | 7.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38894.33 | 30.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18350.67 | 3.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38901.00 | 24.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24901.50 | 7.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38905.00 | 20.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24901.50 | 7.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38905.00 | 20.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24901.50 | 7.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2113.67 | 154.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2099.17 | 168.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2097.67 | 170.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 83572.17 | 19822.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 330041.50 | 19822.83 | 2944.17 | 121081.50 | 127189.17 |
Average | 68006.52 | 1406.01 | 128.01 | 5264.41 | 5529.96 |
Sum | 1564150.00 | 32338.17 | 2944.17 | 121081.50 | 127189.17 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Environment
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Environment
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.326957E+11 | 106867.81 | 30-JAN-08:51 | -6.1 | -6.4 | 0.576430E+10 | 9716.21 | 19-JAN-14:00 | -6.1 | -6.4 |
February | 0.352900E+11 | 119883.18 | 09-FEB-09:21 | -4.8 | -5.3 | 0.533555E+10 | 10176.68 | 21-FEB-14:00 | 6.10 | 2.99 |
March | 0.329269E+11 | 123116.21 | 23-MAR-06:11 | -18.7 | -19.0 | 0.712302E+10 | 12360.60 | 31-MAR-13:00 | 8.30 | 3.10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 | 0.38 | 0.895454E+10 | 12919.40 | 21-APR-13:00 | 11.10 | 2.82 |
May | 0.00 | 0.00 | 01-MAY-00:03 | -0.0 | -1.4 | 0.976137E+10 | 12897.43 | 19-MAY-13:00 | 17.60 | 14.57 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 | 8.93 | 0.994702E+10 | 13158.29 | 30-JUN-13:00 | 31.10 | 23.76 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 | 13.57 | 0.944222E+10 | 13382.35 | 21-JUL-13:00 | 28.90 | 22.62 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 | 15.36 | 0.107719E+11 | 13609.51 | 25-AUG-13:00 | 28.30 | 18.83 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 | 18.15 | 0.933802E+10 | 13559.94 | 01-SEP-13:00 | 25.60 | 18.11 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 | 6.57 | 0.957771E+10 | 13303.63 | 20-OCT-13:00 | 18.90 | 10.07 |
November | 0.976894E+10 | 134255.73 | 25-NOV-07:11 | -19.0 | -19.3 | 0.871362E+10 | 13040.16 | 17-NOV-14:00 | -19.0 | -19.3 |
December | 0.379080E+11 | 127940.07 | 08-DEC-07:11 | -20.3 | -20.7 | 0.589556E+10 | 11478.73 | 07-DEC-14:00 | -20.3 | -20.7 |
Annual Sum or Average | 0.148590E+12 | 0.100625E+12 | ||||||||
Minimum of Months | 0.00 | 0.00 | -20.3 | -20.7 | 0.533555E+10 | 9716.21 | -20.3 | -20.7 | ||
Maximum of Months | 0.379080E+11 | 134255.73 | 19.75 | 18.15 | 0.107719E+11 | 13609.51 | 31.10 | 23.76 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.301783E+11 | 79829.25 | 20-JAN-06:01 | -6.8 | -7.3 | 0.496234E+10 | 6734.78 | 31-JAN-10:20 | -15.6 | -16.0 |
February | 0.336736E+11 | 84596.08 | 22-FEB-05:01 | -11.0 | -11.3 | 0.456822E+10 | 6736.54 | 22-FEB-10:20 | -4.0 | -5.7 |
March | 0.503039E+11 | 93468.81 | 30-MAR-03:02 | -0.7 | -1.3 | 0.548812E+10 | 6800.75 | 23-MAR-09:20 | -0.7 | -1.3 |
April | 0.797776E+11 | 97675.22 | 08-APR-04:12 | 4.03 | 0.87 | 0.489576E+10 | 6770.79 | 18-APR-09:00 | 18.30 | 11.28 |
May | 0.831793E+11 | 98464.24 | 16-MAY-04:12 | 8.50 | 6.34 | 0.530061E+10 | 6771.73 | 16-MAY-13:50 | 24.92 | 15.36 |
June | 0.903628E+11 | 98313.76 | 23-JUN-04:13 | 17.20 | 16.88 | 0.528388E+10 | 6780.25 | 15-JUN-13:00 | 17.20 | 16.88 |
July | 0.970509E+11 | 98376.54 | 20-JUL-04:13 | 16.13 | 15.65 | 0.493019E+10 | 7587.59 | 05-JUL-13:09 | 16.13 | 15.65 |
August | 0.106095E+12 | 98384.02 | 23-AUG-04:13 | 16.33 | 15.71 | 0.551514E+10 | 6856.72 | 30-AUG-09:50 | 24.03 | 20.50 |
September | 0.815552E+11 | 98786.27 | 29-SEP-04:12 | 7.20 | 7.20 | 0.489473E+10 | 6785.71 | 01-SEP-09:50 | 7.20 | 7.20 |
October | 0.780683E+11 | 98734.05 | 19-OCT-04:12 | 7.60 | 6.01 | 0.509124E+10 | 6739.38 | 20-OCT-09:20 | 9.10 | 7.99 |
November | 0.648472E+11 | 98259.38 | 20-NOV-05:12 | 5.00 | 4.07 | 0.504041E+10 | 6783.61 | 28-NOV-14:50 | -7.3 | -8.6 |
December | 0.387787E+11 | 88385.48 | 08-DEC-04:01 | -19.4 | -19.7 | 0.487479E+10 | 6754.40 | 01-DEC-10:39 | -19.4 | -19.7 |
Annual Sum or Average | 0.833870E+12 | 0.608454E+11 | ||||||||
Minimum of Months | 0.301783E+11 | 79829.25 | -19.4 | -19.7 | 0.456822E+10 | 6734.78 | -19.4 | -19.7 | ||
Maximum of Months | 0.106095E+12 | 98786.27 | 17.20 | 16.88 | 0.551514E+10 | 7587.59 | 24.92 | 20.50 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.212028E+11 | 30923.30 | 17-JAN-16:20 | -4.5 | -5.5 | 0.421526E+10 | 6567.49 | 27-JAN-14:00 | -14.4 | -15.6 |
February | 0.223498E+11 | 40248.24 | 10-FEB-14:48 | -11.9 | -13.3 | 0.408429E+10 | 6734.46 | 09-FEB-14:30 | -11.9 | -13.3 |
March | 0.289900E+11 | 60855.52 | 30-MAR-05:03 | -1.9 | -2.1 | 0.517568E+10 | 6785.18 | 30-MAR-09:09 | -1.6 | -2.3 |
April | 0.327464E+11 | 77543.39 | 14-APR-05:03 | 2.12 | 1.45 | 0.480305E+10 | 6738.68 | 25-APR-09:30 | 3.60 | 1.92 |
May | 0.438002E+11 | 86211.64 | 30-MAY-04:12 | 10.60 | 8.25 | 0.526969E+10 | 6734.86 | 24-MAY-09:09 | 10.60 | 8.25 |
June | 0.471386E+11 | 82567.97 | 27-JUN-04:12 | 15.60 | 14.89 | 0.526065E+10 | 6734.84 | 13-JUN-09:00 | 15.60 | 14.89 |
July | 0.476095E+11 | 82855.19 | 26-JUL-04:12 | 14.23 | 12.40 | 0.489288E+10 | 6820.12 | 05-JUL-13:09 | 14.23 | 12.40 |
August | 0.489428E+11 | 82360.47 | 01-AUG-04:12 | 18.13 | 17.48 | 0.548781E+10 | 6734.90 | 10-AUG-13:39 | 19.03 | 16.37 |
September | 0.391959E+11 | 81102.00 | 01-SEP-04:12 | 15.93 | 15.93 | 0.485552E+10 | 6734.78 | 14-SEP-09:09 | 13.27 | 10.50 |
October | 0.315170E+11 | 75795.77 | 20-OCT-05:03 | 7.52 | 7.52 | 0.498123E+10 | 6762.78 | 05-OCT-13:09 | 7.52 | 7.52 |
November | 0.247537E+11 | 29394.36 | 17-NOV-16:30 | 8.35 | 2.28 | 0.470231E+10 | 6779.84 | 10-NOV-10:00 | 8.35 | 2.28 |
December | 0.230903E+11 | 22156.21 | 22-DEC-16:20 | -11.1 | -11.3 | 0.413651E+10 | 6698.71 | 01-DEC-14:00 | -11.1 | -11.3 |
Annual Sum or Average | 0.411337E+12 | 0.578649E+11 | ||||||||
Minimum of Months | 0.212028E+11 | 22156.21 | -11.9 | -13.3 | 0.408429E+10 | 6567.49 | -14.4 | -15.6 | ||
Maximum of Months | 0.489428E+11 | 86211.64 | 18.13 | 17.48 | 0.548781E+10 | 6820.12 | 19.03 | 16.37 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122573E+11 | 16908.42 | 20-JAN-16:50 | -6.9 | -8.2 | 0.385599E+10 | 5877.66 | 20-JAN-14:00 | -6.9 | -8.2 |
February | 0.145680E+11 | 20093.97 | 28-FEB-14:10 | 4.27 | 0.38 | 0.362541E+10 | 6311.94 | 08-FEB-14:00 | 4.27 | 0.38 |
March | 0.209725E+11 | 26759.44 | 29-MAR-16:00 | 5.00 | 1.34 | 0.459085E+10 | 6734.45 | 29-MAR-13:00 | 5.00 | 1.34 |
April | 0.261660E+11 | 38728.12 | 13-APR-16:00 | 20.00 | 8.11 | 0.447946E+10 | 6763.59 | 25-APR-13:50 | 5.60 | 2.84 |
May | 0.403097E+11 | 79913.39 | 26-MAY-04:12 | 19.40 | 15.71 | 0.520133E+10 | 6734.85 | 24-MAY-09:09 | 19.40 | 15.71 |
June | 0.464410E+11 | 79752.19 | 26-JUN-04:12 | 16.87 | 15.70 | 0.523754E+10 | 6734.81 | 13-JUN-09:00 | 16.87 | 15.70 |
July | 0.478025E+11 | 80630.86 | 05-JUL-04:12 | 19.80 | 18.77 | 0.488108E+10 | 6864.64 | 05-JUL-13:09 | 23.30 | 21.28 |
August | 0.468476E+11 | 80713.69 | 09-AUG-04:12 | 18.70 | 17.59 | 0.546734E+10 | 6734.87 | 10-AUG-13:39 | 19.03 | 16.37 |
September | 0.332212E+11 | 75052.72 | 02-SEP-05:03 | 13.80 | 10.55 | 0.476662E+10 | 6734.75 | 14-SEP-09:09 | 13.27 | 10.50 |
October | 0.238261E+11 | 36678.75 | 20-OCT-16:00 | 18.30 | 9.93 | 0.454587E+10 | 6734.59 | 24-OCT-13:00 | 9.40 | 5.35 |
November | 0.179373E+11 | 20047.19 | 17-NOV-17:00 | 6.70 | 1.30 | 0.415368E+10 | 6607.71 | 17-NOV-14:00 | 6.70 | 1.30 |
December | 0.129514E+11 | 16915.17 | 28-DEC-17:00 | -2.4 | -4.0 | 0.375100E+10 | 5979.84 | 28-DEC-14:00 | -2.4 | -4.0 |
Annual Sum or Average | 0.343301E+12 | 0.545562E+11 | ||||||||
Minimum of Months | 0.122573E+11 | 16908.42 | -6.9 | -8.2 | 0.362541E+10 | 5877.66 | -6.9 | -8.2 | ||
Maximum of Months | 0.478025E+11 | 80713.69 | 20.00 | 18.77 | 0.546734E+10 | 6864.64 | 23.30 | 21.28 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.548302E+09 | 2415.56 | 20-JAN-06:02 | -6.8 | -7.3 | 0.475657E+09 | 740.86 | 19-JAN-14:20 | -6.8 | -7.3 |
February | 0.142727E+10 | 2718.90 | 22-FEB-13:20 | -0.9 | -3.9 | 0.461116E+09 | 845.60 | 21-FEB-14:09 | -0.9 | -3.9 |
March | 0.316051E+10 | 6180.17 | 28-MAR-14:00 | 6.10 | 2.91 | 0.605625E+09 | 845.62 | 31-MAR-09:09 | 0.28 | -1.7 |
April | 0.693563E+10 | 16226.57 | 23-APR-17:41 | 25.68 | 16.51 | 0.607278E+09 | 849.87 | 18-APR-09:00 | 25.68 | 16.51 |
May | 0.109937E+11 | 14612.55 | 26-MAY-04:12 | 19.40 | 15.71 | 0.664783E+09 | 850.93 | 16-MAY-13:50 | 19.40 | 15.71 |
June | 0.138344E+11 | 16906.23 | 25-JUN-18:22 | 24.45 | 20.48 | 0.663550E+09 | 856.69 | 21-JUN-13:00 | 24.45 | 20.48 |
July | 0.150322E+11 | 18703.45 | 23-JUL-15:12 | 30.00 | 22.58 | 0.619957E+09 | 981.26 | 05-JUL-13:09 | 30.00 | 22.58 |
August | 0.143445E+11 | 17120.27 | 13-AUG-14:02 | 23.22 | 14.47 | 0.692188E+09 | 851.94 | 30-AUG-09:50 | 24.03 | 20.50 |
September | 0.880395E+10 | 14275.69 | 01-SEP-04:12 | 15.93 | 15.93 | 0.612955E+09 | 852.02 | 01-SEP-09:50 | 21.42 | 17.69 |
October | 0.616042E+10 | 8461.09 | 02-OCT-05:03 | 7.80 | 7.29 | 0.631792E+09 | 845.63 | 25-OCT-09:00 | 3.30 | 3.04 |
November | 0.385961E+10 | 7057.57 | 01-NOV-13:30 | 17.80 | 13.07 | 0.595287E+09 | 845.63 | 21-NOV-10:00 | 12.80 | 12.80 |
December | 0.124479E+10 | 2651.87 | 06-DEC-06:03 | -0.8 | -0.8 | 0.477592E+09 | 791.82 | 06-DEC-14:20 | -6.6 | -6.7 |
Annual Sum or Average | 0.863452E+11 | 0.710778E+10 | ||||||||
Minimum of Months | 0.548302E+09 | 2415.56 | -6.8 | -7.3 | 0.461116E+09 | 740.86 | -6.8 | -7.3 | ||
Maximum of Months | 0.150322E+11 | 18703.45 | 30.00 | 22.58 | 0.692188E+09 | 981.26 | 30.00 | 22.58 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.872645E+09 | 3034.53 | 20-JAN-06:02 | -6.8 | -7.3 | 0.307403E+09 | 515.98 | 25-JAN-10:20 | -23.1 | -23.4 |
February | 0.191259E+10 | 6788.82 | 27-FEB-09:35 | -14.6 | -15.6 | 0.302825E+09 | 544.95 | 28-FEB-10:09 | -5.5 | -7.3 |
March | 0.404138E+10 | 12664.93 | 31-MAR-09:05 | 0.28 | -1.7 | 0.389914E+09 | 551.06 | 23-MAR-09:20 | 0.28 | -1.7 |
April | 0.839703E+10 | 26271.87 | 30-APR-08:22 | 6.70 | 3.63 | 0.387711E+09 | 551.53 | 18-APR-09:00 | 6.70 | 3.63 |
May | 0.109798E+11 | 26917.33 | 14-MAY-08:22 | 9.00 | 3.13 | 0.428305E+09 | 553.86 | 18-MAY-09:50 | 24.98 | 16.17 |
June | 0.132700E+11 | 28101.62 | 25-JUN-07:41 | 23.72 | 20.71 | 0.427531E+09 | 551.99 | 27-JUN-09:00 | 26.10 | 19.03 |
July | 0.144274E+11 | 30010.32 | 23-JUL-09:12 | 25.57 | 22.50 | 0.398020E+09 | 555.69 | 05-JUL-13:09 | 25.57 | 22.50 |
August | 0.126022E+11 | 28505.21 | 06-AUG-08:41 | 17.93 | 13.93 | 0.445694E+09 | 552.57 | 08-AUG-09:00 | 23.90 | 20.07 |
September | 0.880658E+10 | 26945.99 | 10-SEP-07:42 | 9.35 | 8.06 | 0.393164E+09 | 554.43 | 01-SEP-09:50 | 9.35 | 8.06 |
October | 0.588642E+10 | 21531.24 | 09-OCT-08:52 | 2.20 | -1.1 | 0.398812E+09 | 544.97 | 19-OCT-09:00 | 13.90 | 10.03 |
November | 0.378993E+10 | 8019.47 | 16-NOV-09:25 | 0.55 | -1.2 | 0.366880E+09 | 544.95 | 10-NOV-10:09 | 0.55 | -1.2 |
December | 0.110355E+10 | 3126.85 | 01-DEC-10:25 | -20.3 | -20.6 | 0.299185E+09 | 537.31 | 01-DEC-10:20 | -20.3 | -20.6 |
Annual Sum or Average | 0.860896E+11 | 0.454544E+10 | ||||||||
Minimum of Months | 0.872645E+09 | 3034.53 | -20.3 | -20.6 | 0.299185E+09 | 515.98 | -23.1 | -23.4 | ||
Maximum of Months | 0.144274E+11 | 30010.32 | 25.57 | 22.50 | 0.445694E+09 | 555.69 | 26.10 | 22.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.360382E+10 | 18716.89 | 27-JAN-13:25 | -15.0 | -16.1 | 0.537967E+09 | 846.00 | 27-JAN-14:09 | -14.4 | -15.6 |
February | 0.607222E+10 | 31409.23 | 19-FEB-13:12 | -11.3 | -12.9 | 0.515456E+09 | 854.35 | 27-FEB-14:00 | -7.8 | -10.2 |
March | 0.836024E+10 | 34092.69 | 19-MAR-12:31 | 2.93 | 0.06 | 0.626375E+09 | 877.35 | 06-MAR-14:00 | 2.93 | 0.06 |
April | 0.127240E+11 | 36057.21 | 23-APR-13:41 | 24.13 | 15.95 | 0.597428E+09 | 853.54 | 18-APR-09:00 | 24.13 | 15.95 |
May | 0.146567E+11 | 30799.25 | 21-MAY-12:42 | 19.22 | 10.58 | 0.662490E+09 | 864.92 | 16-MAY-13:50 | 19.22 | 10.58 |
June | 0.161056E+11 | 31097.47 | 18-JUN-12:32 | 26.10 | 17.75 | 0.662790E+09 | 856.44 | 15-JUN-13:00 | 26.10 | 17.75 |
July | 0.187266E+11 | 36218.73 | 23-JUL-12:32 | 29.43 | 22.71 | 0.618779E+09 | 969.07 | 05-JUL-13:09 | 29.43 | 22.71 |
August | 0.194469E+11 | 36880.84 | 13-AUG-12:42 | 22.80 | 14.26 | 0.692465E+09 | 893.00 | 29-AUG-13:30 | 25.00 | 20.03 |
September | 0.144481E+11 | 34321.02 | 10-SEP-11:01 | 17.20 | 10.52 | 0.611107E+09 | 918.31 | 01-SEP-13:20 | 17.20 | 10.52 |
October | 0.106303E+11 | 35038.36 | 22-OCT-12:51 | 18.30 | 13.08 | 0.619227E+09 | 899.27 | 18-OCT-13:09 | 18.30 | 13.08 |
November | 0.707223E+10 | 23956.84 | 17-NOV-12:00 | 8.90 | 2.91 | 0.586510E+09 | 856.77 | 28-NOV-14:09 | -7.7 | -8.9 |
December | 0.337658E+10 | 15998.20 | 20-DEC-13:05 | -21.3 | -21.8 | 0.504695E+09 | 845.64 | 26-DEC-10:50 | -22.7 | -23.1 |
Annual Sum or Average | 0.135223E+12 | 0.723529E+10 | ||||||||
Minimum of Months | 0.337658E+10 | 15998.20 | -21.3 | -21.8 | 0.504695E+09 | 845.64 | -22.7 | -23.1 | ||
Maximum of Months | 0.194469E+11 | 36880.84 | 29.43 | 22.71 | 0.692465E+09 | 969.07 | 29.43 | 22.71 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.159224E+10 | 5499.00 | 20-JAN-15:50 | -5.5 | -7.2 | 0.317116E+09 | 544.45 | 27-JAN-14:00 | -14.4 | -15.6 |
February | 0.347924E+10 | 10935.08 | 28-FEB-15:40 | 6.10 | 1.55 | 0.314862E+09 | 544.95 | 10-FEB-14:50 | 6.10 | 1.55 |
March | 0.659965E+10 | 31987.39 | 19-MAR-15:11 | 4.60 | 1.46 | 0.408970E+09 | 549.44 | 06-MAR-16:40 | 4.60 | 1.46 |
April | 0.106584E+11 | 38053.73 | 23-APR-16:21 | 26.40 | 16.81 | 0.392231E+09 | 548.55 | 18-APR-09:00 | 26.40 | 16.81 |
May | 0.117862E+11 | 32997.08 | 14-MAY-17:01 | 20.00 | 8.43 | 0.426350E+09 | 549.89 | 16-MAY-13:50 | 24.92 | 15.36 |
June | 0.138199E+11 | 32397.52 | 17-JUN-17:41 | 23.90 | 13.28 | 0.427364E+09 | 551.72 | 15-JUN-13:00 | 23.90 | 13.28 |
July | 0.165271E+11 | 36565.41 | 23-JUL-16:32 | 28.87 | 22.11 | 0.398726E+09 | 564.30 | 06-JUL-15:30 | 28.87 | 22.11 |
August | 0.164282E+11 | 32801.53 | 05-AUG-17:41 | 22.30 | 14.14 | 0.446708E+09 | 549.86 | 30-AUG-09:50 | 24.03 | 20.50 |
September | 0.904977E+10 | 32087.49 | 03-SEP-15:51 | 21.70 | 15.83 | 0.389109E+09 | 549.46 | 01-SEP-09:50 | 21.70 | 15.83 |
October | 0.718337E+10 | 26226.98 | 22-OCT-15:32 | 19.07 | 12.50 | 0.397107E+09 | 544.95 | 19-OCT-09:00 | 19.07 | 12.50 |
November | 0.524612E+10 | 9865.05 | 09-NOV-15:30 | 1.65 | -3.5 | 0.381254E+09 | 544.96 | 21-NOV-10:00 | 12.80 | 12.80 |
December | 0.354681E+10 | 5546.23 | 20-DEC-15:30 | -19.5 | -20.3 | 0.332516E+09 | 544.94 | 08-DEC-14:00 | -19.5 | -20.3 |
Annual Sum or Average | 0.105917E+12 | 0.463231E+10 | ||||||||
Minimum of Months | 0.159224E+10 | 5499.00 | -19.5 | -20.3 | 0.314862E+09 | 544.45 | -19.5 | -20.3 | ||
Maximum of Months | 0.165271E+11 | 38053.73 | 28.87 | 22.11 | 0.446708E+09 | 564.30 | 28.87 | 22.11 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 22486706.50 | 1434.16 | 28-JAN-17:02 | -7.8 | -9.1 | 0.461487E+09 | 625.97 | 04-JAN-14:00 | -7.8 | -9.1 |
February | 0.212914E+09 | 2023.83 | 08-FEB-13:50 | 4.90 | -0.5 | 0.422564E+09 | 667.32 | 08-FEB-14:00 | 5.00 | -0.5 |
March | 0.100696E+10 | 2808.52 | 31-MAR-14:00 | 8.30 | 3.10 | 0.525361E+09 | 803.56 | 28-MAR-13:00 | 8.30 | 3.10 |
April | 0.257722E+10 | 5074.92 | 18-APR-14:00 | 17.80 | 10.49 | 0.529329E+09 | 845.60 | 18-APR-13:00 | 17.80 | 10.49 |
May | 0.623589E+10 | 11879.10 | 26-MAY-05:02 | 19.40 | 15.69 | 0.650832E+09 | 845.64 | 24-MAY-09:09 | 19.40 | 15.69 |
June | 0.840389E+10 | 15377.46 | 25-JUN-11:21 | 27.25 | 21.76 | 0.660048E+09 | 845.92 | 29-JUN-13:50 | 32.88 | 24.59 |
July | 0.875385E+10 | 15220.00 | 04-JUL-15:41 | 23.90 | 19.82 | 0.615295E+09 | 903.35 | 05-JUL-13:09 | 23.30 | 21.28 |
August | 0.719418E+10 | 9018.02 | 09-AUG-05:03 | 18.40 | 17.30 | 0.685665E+09 | 845.65 | 10-AUG-13:39 | 19.03 | 16.37 |
September | 0.417564E+10 | 7328.14 | 01-SEP-15:20 | 26.10 | 17.76 | 0.586240E+09 | 845.63 | 11-SEP-13:09 | 18.90 | 14.33 |
October | 0.236671E+10 | 3286.14 | 20-OCT-15:00 | 18.90 | 10.07 | 0.534786E+09 | 845.60 | 02-OCT-13:00 | 18.90 | 10.07 |
November | 0.847606E+09 | 2252.45 | 01-NOV-15:30 | 18.05 | 13.35 | 0.476282E+09 | 801.40 | 01-NOV-13:00 | 18.05 | 13.35 |
December | 27808485.72 | 1444.57 | 30-DEC-17:02 | -3.3 | -3.3 | 0.446382E+09 | 625.95 | 22-DEC-14:50 | -3.3 | -3.3 |
Annual Sum or Average | 0.418252E+11 | 0.659427E+10 | ||||||||
Minimum of Months | 22486706.50 | 1434.16 | -7.8 | -9.1 | 0.422564E+09 | 625.95 | -7.8 | -9.1 | ||
Maximum of Months | 0.875385E+10 | 15377.46 | 27.25 | 21.76 | 0.685665E+09 | 903.35 | 32.88 | 24.59 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113331E+09 | 2282.31 | 25-JAN-10:00 | -23.3 | -23.6 | 0.218812E+09 | 405.17 | 25-JAN-09:00 | -23.3 | -23.6 |
February | 0.733425E+09 | 3490.31 | 28-FEB-09:55 | -6.1 | -7.7 | 0.202897E+09 | 519.31 | 28-FEB-09:00 | -6.1 | -7.7 |
March | 0.228570E+10 | 11044.91 | 17-MAR-08:58 | -9.4 | -10.4 | 0.261300E+09 | 521.20 | 20-MAR-10:20 | -0.5 | -2.6 |
April | 0.525005E+10 | 19335.82 | 16-APR-09:51 | 5.60 | 2.25 | 0.264653E+09 | 524.35 | 10-APR-08:50 | 5.60 | 2.25 |
May | 0.805491E+10 | 31650.64 | 21-MAY-09:11 | 12.83 | 7.73 | 0.307418E+09 | 530.01 | 01-MAY-08:20 | 12.83 | 7.73 |
June | 0.102322E+11 | 33616.93 | 25-JUN-08:41 | 24.82 | 21.01 | 0.310524E+09 | 522.42 | 07-JUN-08:50 | 24.82 | 21.01 |
July | 0.107648E+11 | 29132.75 | 23-JUL-10:01 | 26.97 | 23.13 | 0.291188E+09 | 530.80 | 05-JUL-10:00 | 26.97 | 23.13 |
August | 0.859207E+10 | 32914.56 | 20-AUG-09:01 | 20.97 | 15.56 | 0.318130E+09 | 521.30 | 22-AUG-08:00 | 20.00 | 14.40 |
September | 0.581183E+10 | 27535.52 | 04-SEP-10:22 | 14.70 | 9.57 | 0.267865E+09 | 521.22 | 13-SEP-10:30 | 15.80 | 11.43 |
October | 0.298508E+10 | 12984.49 | 22-OCT-09:32 | 14.03 | 11.42 | 0.243263E+09 | 521.22 | 19-OCT-10:09 | 14.03 | 11.42 |
November | 0.108918E+10 | 4153.97 | 09-NOV-10:00 | 0.00 | -1.2 | 0.223676E+09 | 520.86 | 16-NOV-09:00 | 1.70 | -0.5 |
December | 0.104957E+09 | 2313.22 | 01-DEC-10:00 | -20.8 | -21.1 | 0.211287E+09 | 408.92 | 01-DEC-09:00 | -20.8 | -21.1 |
Annual Sum or Average | 0.560175E+11 | 0.312101E+10 | ||||||||
Minimum of Months | 0.104957E+09 | 2282.31 | -23.3 | -23.6 | 0.202897E+09 | 405.17 | -23.3 | -23.6 | ||
Maximum of Months | 0.107648E+11 | 33616.93 | 26.97 | 23.13 | 0.318130E+09 | 530.80 | 26.97 | 23.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.295051E+10 | 19869.19 | 27-JAN-13:35 | -14.8 | -15.9 | 0.518362E+09 | 846.07 | 27-JAN-14:09 | -14.4 | -15.6 |
February | 0.537832E+10 | 27489.83 | 10-FEB-14:48 | -11.9 | -13.3 | 0.497579E+09 | 877.63 | 10-FEB-13:39 | -11.9 | -13.3 |
March | 0.701047E+10 | 36433.92 | 26-MAR-12:41 | 8.03 | 3.95 | 0.597438E+09 | 849.87 | 23-MAR-13:39 | 8.03 | 3.95 |
April | 0.911863E+10 | 38026.61 | 23-APR-13:31 | 23.87 | 15.83 | 0.561781E+09 | 846.41 | 18-APR-13:00 | 23.87 | 15.83 |
May | 0.111780E+11 | 34394.52 | 21-MAY-13:11 | 20.03 | 10.84 | 0.648145E+09 | 847.28 | 24-MAY-13:00 | 27.10 | 17.69 |
June | 0.118335E+11 | 34276.93 | 18-JUN-13:01 | 26.20 | 17.95 | 0.654870E+09 | 846.51 | 30-JUN-13:00 | 31.10 | 23.76 |
July | 0.133556E+11 | 33234.55 | 23-JUL-13:22 | 30.00 | 22.65 | 0.612948E+09 | 906.10 | 05-JUL-13:09 | 30.00 | 22.65 |
August | 0.135591E+11 | 37290.48 | 13-AUG-13:11 | 22.97 | 14.28 | 0.681936E+09 | 848.09 | 01-AUG-13:00 | 22.97 | 14.28 |
September | 0.111118E+11 | 39484.13 | 04-SEP-13:01 | 16.10 | 9.72 | 0.588470E+09 | 908.82 | 01-SEP-13:39 | 16.10 | 9.72 |
October | 0.761124E+10 | 36444.75 | 22-OCT-12:51 | 18.30 | 13.08 | 0.563090E+09 | 893.34 | 18-OCT-13:30 | 18.30 | 13.08 |
November | 0.417029E+10 | 23743.33 | 29-NOV-12:13 | -2.2 | -4.5 | 0.529424E+09 | 862.98 | 10-NOV-10:00 | -2.2 | -4.5 |
December | 0.183939E+10 | 15075.43 | 02-DEC-13:20 | -18.8 | -19.5 | 0.479791E+09 | 845.64 | 26-DEC-14:39 | -19.1 | -19.8 |
Annual Sum or Average | 0.991167E+11 | 0.693383E+10 | ||||||||
Minimum of Months | 0.183939E+10 | 15075.43 | -18.8 | -19.5 | 0.479791E+09 | 845.64 | -19.1 | -19.8 | ||
Maximum of Months | 0.135591E+11 | 39484.13 | 30.00 | 22.65 | 0.681936E+09 | 908.82 | 31.10 | 23.76 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.342194E+09 | 5480.65 | 17-JAN-16:20 | -4.5 | -5.5 | 0.302955E+09 | 502.08 | 27-JAN-16:10 | -14.8 | -15.9 |
February | 0.110183E+10 | 7427.00 | 27-FEB-16:40 | -7.8 | -10.2 | 0.284412E+09 | 544.61 | 08-FEB-14:00 | -7.8 | -10.2 |
March | 0.276452E+10 | 29079.52 | 26-MAR-17:21 | 9.45 | 4.66 | 0.349122E+09 | 544.83 | 10-MAR-14:00 | 9.45 | 4.66 |
April | 0.549206E+10 | 36032.01 | 23-APR-16:51 | 26.10 | 16.67 | 0.338075E+09 | 544.94 | 18-APR-13:00 | 26.10 | 16.67 |
May | 0.901193E+10 | 35787.39 | 14-MAY-17:31 | 20.00 | 8.52 | 0.411237E+09 | 544.96 | 16-MAY-13:09 | 24.58 | 15.35 |
June | 0.989285E+10 | 30946.85 | 17-JUN-17:41 | 23.90 | 13.28 | 0.420000E+09 | 544.96 | 13-JUN-09:00 | 23.90 | 13.28 |
July | 0.108878E+11 | 33808.87 | 04-JUL-16:21 | 24.45 | 19.90 | 0.394595E+09 | 551.89 | 05-JUL-13:09 | 23.30 | 21.28 |
August | 0.943967E+10 | 30697.50 | 05-AUG-17:41 | 22.30 | 14.14 | 0.434775E+09 | 544.97 | 10-AUG-13:39 | 19.03 | 16.37 |
September | 0.611634E+10 | 30638.54 | 03-SEP-16:51 | 21.70 | 16.12 | 0.360313E+09 | 544.96 | 11-SEP-13:09 | 18.90 | 14.33 |
October | 0.363374E+10 | 16169.24 | 22-OCT-15:32 | 19.07 | 12.50 | 0.334993E+09 | 544.91 | 19-OCT-13:00 | 19.07 | 12.50 |
November | 0.140276E+10 | 4937.72 | 09-NOV-15:40 | 1.47 | -3.6 | 0.309366E+09 | 541.14 | 17-NOV-14:00 | 10.60 | 3.43 |
December | 0.266908E+09 | 2665.30 | 20-DEC-15:40 | -19.8 | -20.5 | 0.289374E+09 | 436.37 | 20-DEC-15:50 | -20.0 | -20.7 |
Annual Sum or Average | 0.603526E+11 | 0.422922E+10 | ||||||||
Minimum of Months | 0.266908E+09 | 2665.30 | -19.8 | -20.5 | 0.284412E+09 | 436.37 | -20.0 | -20.7 | ||
Maximum of Months | 0.108878E+11 | 36032.01 | 26.10 | 19.90 | 0.434775E+09 | 551.89 | 26.10 | 21.28 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 10927359.59 | 1494.63 | 28-JAN-17:02 | -7.8 | -9.1 | 0.457224E+09 | 626.03 | 04-JAN-14:30 | -7.8 | -9.1 |
February | 0.101799E+09 | 1758.73 | 08-FEB-14:00 | 5.00 | -0.5 | 0.418835E+09 | 643.41 | 08-FEB-14:00 | 5.00 | -0.5 |
March | 0.535139E+09 | 2478.50 | 31-MAR-14:00 | 8.30 | 3.10 | 0.511679E+09 | 747.57 | 28-MAR-13:00 | 8.30 | 3.10 |
April | 0.192293E+10 | 4958.44 | 18-APR-15:10 | 14.45 | 8.32 | 0.499523E+09 | 845.60 | 18-APR-13:00 | 14.45 | 8.32 |
May | 0.585888E+10 | 11414.36 | 26-MAY-05:02 | 19.40 | 15.69 | 0.635055E+09 | 845.64 | 23-MAY-13:50 | 19.40 | 15.69 |
June | 0.828265E+10 | 17928.97 | 25-JUN-11:31 | 27.07 | 21.57 | 0.656372E+09 | 846.08 | 28-JUN-13:00 | 30.00 | 21.52 |
July | 0.877084E+10 | 17658.70 | 04-JUL-16:21 | 24.45 | 19.90 | 0.613415E+09 | 874.68 | 05-JUL-13:09 | 23.30 | 21.28 |
August | 0.696156E+10 | 9565.10 | 09-AUG-15:30 | 27.25 | 21.19 | 0.678915E+09 | 845.65 | 10-AUG-13:39 | 19.03 | 16.37 |
September | 0.361216E+10 | 7896.36 | 01-SEP-15:20 | 26.10 | 17.76 | 0.559653E+09 | 845.63 | 11-SEP-13:09 | 18.90 | 14.33 |
October | 0.152516E+10 | 3168.79 | 20-OCT-13:10 | 18.40 | 9.83 | 0.496111E+09 | 822.20 | 20-OCT-13:00 | 18.90 | 10.07 |
November | 0.383324E+09 | 2193.08 | 01-NOV-16:00 | 17.80 | 13.26 | 0.462997E+09 | 739.63 | 01-NOV-13:00 | 17.80 | 13.26 |
December | 12912771.41 | 1662.00 | 06-DEC-06:06 | -0.8 | -0.8 | 0.443281E+09 | 626.02 | 21-DEC-10:09 | -25.7 | -26.0 |
Annual Sum or Average | 0.379783E+11 | 0.643306E+10 | ||||||||
Minimum of Months | 10927359.59 | 1494.63 | -7.8 | -9.1 | 0.418835E+09 | 626.02 | -25.7 | -26.0 | ||
Maximum of Months | 0.877084E+10 | 17928.97 | 27.25 | 21.57 | 0.678915E+09 | 874.68 | 30.00 | 21.52 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 38134504.05 | 2224.27 | 20-JAN-06:04 | -6.8 | -7.3 | 0.298433E+09 | 403.41 | 04-JAN-10:09 | -6.8 | -7.3 |
February | 0.431370E+09 | 2902.68 | 28-FEB-10:30 | -4.4 | -6.4 | 0.273995E+09 | 512.76 | 28-FEB-10:39 | -3.9 | -5.9 |
March | 0.159647E+10 | 7070.25 | 31-MAR-09:50 | 1.42 | -1.1 | 0.350955E+09 | 544.95 | 17-MAR-09:09 | 1.42 | -1.1 |
April | 0.430144E+10 | 14026.39 | 19-APR-09:05 | 3.22 | -2.3 | 0.354568E+09 | 544.96 | 18-APR-09:00 | 3.22 | -2.3 |
May | 0.766892E+10 | 28265.55 | 21-MAY-09:01 | 12.52 | 7.56 | 0.414019E+09 | 546.36 | 01-MAY-09:00 | 12.52 | 7.56 |
June | 0.101544E+11 | 33541.82 | 25-JUN-08:11 | 24.27 | 20.87 | 0.421625E+09 | 546.22 | 27-JUN-09:50 | 25.92 | 19.10 |
July | 0.108569E+11 | 29293.47 | 23-JUL-10:01 | 26.97 | 23.13 | 0.394727E+09 | 546.25 | 31-JUL-09:00 | 19.40 | 13.46 |
August | 0.842461E+10 | 29027.92 | 20-AUG-09:11 | 21.33 | 15.66 | 0.430821E+09 | 544.98 | 10-AUG-13:39 | 21.33 | 15.66 |
September | 0.522653E+10 | 25811.11 | 10-SEP-10:22 | 16.40 | 10.55 | 0.357503E+09 | 544.96 | 14-SEP-09:09 | 13.27 | 10.50 |
October | 0.203298E+10 | 8666.25 | 19-OCT-09:30 | 12.50 | 9.01 | 0.321724E+09 | 544.96 | 19-OCT-09:00 | 13.90 | 10.03 |
November | 0.623517E+09 | 2854.23 | 16-NOV-10:10 | 2.15 | -0.3 | 0.299929E+09 | 495.66 | 16-NOV-10:09 | 2.15 | -0.3 |
December | 48546274.03 | 2256.13 | 07-DEC-06:04 | -7.8 | -8.0 | 0.287906E+09 | 403.40 | 22-DEC-10:09 | -12.7 | -13.0 |
Annual Sum or Average | 0.514038E+11 | 0.420620E+10 | ||||||||
Minimum of Months | 38134504.05 | 2224.27 | -7.8 | -8.0 | 0.273995E+09 | 403.40 | -12.7 | -13.0 | ||
Maximum of Months | 0.108569E+11 | 33541.82 | 26.97 | 23.13 | 0.430821E+09 | 546.36 | 25.92 | 19.10 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.228315E+10 | 17157.14 | 27-JAN-13:35 | -14.8 | -15.9 | 0.508085E+09 | 845.65 | 06-JAN-14:09 | -14.8 | -15.9 |
February | 0.433029E+10 | 24607.07 | 28-FEB-13:40 | 3.33 | -0.5 | 0.484341E+09 | 846.31 | 22-FEB-14:20 | 3.33 | -0.5 |
March | 0.550350E+10 | 33223.92 | 26-MAR-14:22 | 9.75 | 4.96 | 0.581395E+09 | 847.09 | 23-MAR-13:09 | 9.75 | 4.96 |
April | 0.773812E+10 | 35082.69 | 23-APR-13:52 | 24.40 | 16.08 | 0.544883E+09 | 846.40 | 13-APR-13:00 | 24.40 | 16.08 |
May | 0.106148E+11 | 34816.65 | 21-MAY-13:42 | 20.83 | 11.09 | 0.635101E+09 | 847.45 | 24-MAY-13:00 | 27.10 | 17.69 |
June | 0.117593E+11 | 35884.25 | 25-JUN-11:31 | 27.07 | 21.57 | 0.648252E+09 | 846.60 | 30-JUN-13:00 | 31.10 | 23.76 |
July | 0.134614E+11 | 34919.49 | 23-JUL-13:22 | 30.00 | 22.65 | 0.609113E+09 | 884.82 | 05-JUL-13:09 | 30.00 | 22.65 |
August | 0.132880E+11 | 35187.77 | 13-AUG-13:32 | 23.13 | 14.35 | 0.673017E+09 | 847.40 | 01-AUG-13:50 | 23.13 | 14.35 |
September | 0.102138E+11 | 40759.45 | 04-SEP-12:31 | 15.93 | 9.56 | 0.568308E+09 | 895.79 | 01-SEP-13:39 | 15.93 | 9.56 |
October | 0.615238E+10 | 37483.19 | 22-OCT-13:31 | 19.03 | 12.89 | 0.531603E+09 | 855.74 | 19-OCT-13:09 | 19.03 | 12.89 |
November | 0.316041E+10 | 20366.50 | 17-NOV-13:10 | 10.10 | 3.25 | 0.507829E+09 | 845.64 | 29-NOV-14:50 | 2.12 | -1.5 |
December | 0.126813E+10 | 12362.60 | 20-DEC-13:25 | -20.9 | -21.5 | 0.472968E+09 | 845.64 | 26-DEC-14:39 | -19.1 | -19.8 |
Annual Sum or Average | 0.897733E+11 | 0.676489E+10 | ||||||||
Minimum of Months | 0.126813E+10 | 12362.60 | -20.9 | -21.5 | 0.472968E+09 | 845.64 | -19.1 | -19.8 | ||
Maximum of Months | 0.134614E+11 | 40759.45 | 30.00 | 22.65 | 0.673017E+09 | 895.79 | 31.10 | 23.76 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.244064E+09 | 3093.54 | 27-JAN-16:00 | -14.4 | -15.6 | 0.300804E+09 | 471.01 | 27-JAN-16:10 | -14.8 | -15.9 |
February | 0.872628E+09 | 6833.38 | 08-FEB-16:30 | 3.85 | -1.1 | 0.280938E+09 | 539.99 | 08-FEB-14:00 | 3.85 | -1.1 |
March | 0.213635E+10 | 13303.06 | 26-MAR-17:03 | 9.82 | 4.83 | 0.342931E+09 | 528.83 | 10-MAR-14:00 | 9.82 | 4.83 |
April | 0.471160E+10 | 33113.89 | 23-APR-16:31 | 26.30 | 16.77 | 0.326851E+09 | 544.94 | 18-APR-13:00 | 26.30 | 16.77 |
May | 0.872655E+10 | 36703.98 | 14-MAY-17:21 | 20.00 | 8.49 | 0.401262E+09 | 544.97 | 23-MAY-13:50 | 25.63 | 17.00 |
June | 0.987003E+10 | 32131.83 | 17-JUN-17:41 | 23.90 | 13.28 | 0.415147E+09 | 544.98 | 26-JUN-13:09 | 25.78 | 17.07 |
July | 0.109509E+11 | 35252.60 | 04-JUL-16:21 | 24.45 | 19.90 | 0.391900E+09 | 546.16 | 05-JUL-13:00 | 23.30 | 20.61 |
August | 0.928854E+10 | 31849.45 | 05-AUG-17:41 | 22.30 | 14.14 | 0.428057E+09 | 544.97 | 10-AUG-13:39 | 19.03 | 16.37 |
September | 0.563942E+10 | 31603.13 | 03-SEP-17:11 | 21.33 | 15.90 | 0.346081E+09 | 544.95 | 11-SEP-13:50 | 18.90 | 14.67 |
October | 0.276507E+10 | 11528.07 | 22-OCT-16:12 | 18.17 | 11.82 | 0.322179E+09 | 544.80 | 20-OCT-13:00 | 18.17 | 11.82 |
November | 0.882754E+09 | 4105.99 | 09-NOV-15:40 | 1.47 | -3.6 | 0.303767E+09 | 521.18 | 09-NOV-16:19 | 0.53 | -4.0 |
December | 0.150566E+09 | 2504.20 | 20-DEC-15:40 | -19.8 | -20.5 | 0.288259E+09 | 409.07 | 20-DEC-15:50 | -20.0 | -20.7 |
Annual Sum or Average | 0.562385E+11 | 0.414818E+10 | ||||||||
Minimum of Months | 0.150566E+09 | 2504.20 | -19.8 | -20.5 | 0.280938E+09 | 409.07 | -20.0 | -20.7 | ||
Maximum of Months | 0.109509E+11 | 36703.98 | 26.30 | 19.90 | 0.428057E+09 | 546.16 | 26.30 | 20.61 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.185621E+09 | 10710.44 | 09-JAN-04:01 | -32.4 | -32.5 | 0.00 | 0.00 | 01-JAN-00:10 | -32.4 | -32.5 |
February | 0.548519E+09 | 9986.08 | 13-FEB-05:01 | -23.4 | -23.8 | 0.00 | 0.00 | 01-FEB-00:10 | -23.4 | -23.8 |
March | 0.214114E+10 | 6793.53 | 15-MAR-05:01 | -22.2 | -22.5 | 0.00 | 0.00 | 01-MAR-00:10 | -22.2 | -22.5 |
April | 0.750092E+10 | 10746.66 | 24-APR-05:15 | 4.40 | 3.41 | 0.00 | 0.00 | 01-APR-00:10 | 4.40 | 3.41 |
May | 0.107585E+11 | 12168.87 | 26-MAY-05:08 | 19.40 | 15.69 | 0.00 | 0.00 | 01-MAY-00:10 | 19.40 | 15.69 |
June | 0.125704E+11 | 14093.74 | 26-JUN-05:15 | 17.20 | 15.80 | 0.00 | 0.00 | 01-JUN-00:10 | 17.20 | 15.80 |
July | 0.139346E+11 | 17601.93 | 24-JUL-05:10 | 17.88 | 16.12 | 0.00 | 0.00 | 01-JUL-00:10 | 17.88 | 16.12 |
August | 0.139093E+11 | 14965.41 | 14-AUG-05:10 | 15.92 | 13.40 | 0.00 | 0.00 | 01-AUG-00:10 | 15.92 | 13.40 |
September | 0.948208E+10 | 12380.26 | 05-SEP-05:15 | 5.60 | 5.31 | 0.00 | 0.00 | 01-SEP-00:10 | 5.60 | 5.31 |
October | 0.704594E+10 | 11094.42 | 23-OCT-05:08 | 5.60 | 4.10 | 0.00 | 0.00 | 01-OCT-00:10 | 5.60 | 4.10 |
November | 0.411475E+10 | 7811.12 | 20-NOV-06:06 | 4.90 | 3.75 | 0.00 | 0.00 | 01-NOV-00:10 | 4.90 | 3.75 |
December | 0.388343E+09 | 6857.46 | 26-DEC-05:01 | -25.9 | -26.2 | 0.00 | 0.00 | 01-DEC-00:10 | -25.9 | -26.2 |
Annual Sum or Average | 0.825801E+11 | 0.00 | ||||||||
Minimum of Months | 0.185621E+09 | 6793.53 | -32.4 | -32.5 | 0.00 | 0.00 | -32.4 | -32.5 | ||
Maximum of Months | 0.139346E+11 | 17601.93 | 19.40 | 16.12 | 0.00 | 0.00 | 19.40 | 16.12 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.572432E+09 | 13239.19 | 28-JAN-04:01 | -26.7 | -26.9 | 0.00 | 0.00 | 01-JAN-00:10 | -26.7 | -26.9 |
February | 0.496253E+09 | 14391.02 | 25-FEB-04:01 | -27.5 | -27.7 | 0.00 | 0.00 | 01-FEB-00:10 | -27.5 | -27.7 |
March | 0.658344E+09 | 11228.07 | 06-MAR-04:01 | -17.4 | -17.8 | 0.00 | 0.00 | 01-MAR-00:10 | -17.4 | -17.8 |
April | 0.193635E+10 | 8523.13 | 04-APR-04:01 | -7.5 | -9.4 | 0.00 | 0.00 | 01-APR-00:10 | -7.5 | -9.4 |
May | 0.466317E+10 | 7499.74 | 19-MAY-05:13 | 14.27 | 9.81 | 0.00 | 0.00 | 01-MAY-00:10 | 14.27 | 9.81 |
June | 0.635720E+10 | 7938.72 | 30-JUN-16:00 | 31.70 | 24.66 | 0.00 | 0.00 | 01-JUN-00:10 | 31.70 | 24.66 |
July | 0.724213E+10 | 8646.91 | 05-JUL-05:13 | 19.80 | 19.00 | 0.00 | 0.00 | 01-JUL-00:10 | 19.80 | 19.00 |
August | 0.627491E+10 | 7459.68 | 01-AUG-05:13 | 17.97 | 17.31 | 0.00 | 0.00 | 01-AUG-00:10 | 17.97 | 17.31 |
September | 0.384779E+10 | 6548.85 | 01-SEP-16:00 | 26.10 | 17.64 | 0.00 | 0.00 | 01-SEP-00:10 | 26.10 | 17.64 |
October | 0.177032E+10 | 11031.32 | 30-OCT-04:01 | -10.0 | -10.7 | 0.00 | 0.00 | 01-OCT-00:10 | -10.0 | -10.7 |
November | 0.606769E+09 | 13473.79 | 24-NOV-04:01 | -11.0 | -11.5 | 0.00 | 0.00 | 01-NOV-00:10 | -11.0 | -11.5 |
December | 0.748102E+09 | 14396.76 | 02-DEC-04:01 | -26.8 | -27.0 | 0.00 | 0.00 | 01-DEC-00:10 | -26.8 | -27.0 |
Annual Sum or Average | 0.351738E+11 | 0.00 | ||||||||
Minimum of Months | 0.496253E+09 | 6548.85 | -27.5 | -27.7 | 0.00 | 0.00 | -27.5 | -27.7 | ||
Maximum of Months | 0.724213E+10 | 14396.76 | 31.70 | 24.66 | 0.00 | 0.00 | 31.70 | 24.66 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -21.9 | -22.1 | 0.00 | 0.00 | 01-JAN-00:10 | -21.9 | -22.1 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -23.1 | -23.5 | 0.00 | 0.00 | 01-FEB-00:10 | -23.1 | -23.5 |
March | 0.159634E+09 | 3088.40 | 26-MAR-14:24 | 9.75 | 4.96 | 0.00 | 0.00 | 01-MAR-00:10 | 9.75 | 4.96 |
April | 0.198914E+10 | 10250.46 | 13-APR-14:50 | 19.82 | 7.99 | 0.00 | 0.00 | 01-APR-00:10 | 19.82 | 7.99 |
May | 0.682421E+10 | 17840.50 | 18-MAY-14:40 | 28.77 | 16.65 | 0.00 | 0.00 | 01-MAY-00:10 | 28.77 | 16.65 |
June | 0.980232E+10 | 20108.72 | 30-JUN-14:40 | 31.83 | 24.26 | 0.00 | 0.00 | 01-JUN-00:10 | 31.83 | 24.26 |
July | 0.111805E+11 | 18769.84 | 24-JUL-14:40 | 29.40 | 19.47 | 0.00 | 0.00 | 01-JUL-00:10 | 29.40 | 19.47 |
August | 0.835997E+10 | 17187.07 | 08-AUG-15:20 | 30.60 | 23.24 | 0.00 | 0.00 | 01-AUG-00:10 | 30.60 | 23.24 |
September | 0.357135E+10 | 14592.35 | 01-SEP-16:00 | 26.10 | 17.64 | 0.00 | 0.00 | 01-SEP-00:10 | 26.10 | 17.64 |
October | 0.720358E+09 | 6703.00 | 20-OCT-14:50 | 18.90 | 10.07 | 0.00 | 0.00 | 01-OCT-00:10 | 18.90 | 10.07 |
November | 19995059.23 | 1785.13 | 01-NOV-16:30 | 17.25 | 13.03 | 0.00 | 0.00 | 01-NOV-00:10 | 17.25 | 13.03 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 | -9.9 |
Annual Sum or Average | 0.426274E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -23.1 | -23.5 | 0.00 | 0.00 | -23.1 | -23.5 | ||
Maximum of Months | 0.111805E+11 | 20108.72 | 31.83 | 24.26 | 0.00 | 0.00 | 31.83 | 24.26 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.167795E+10 | 2268.25 | 25-JAN-16:30 | -18.4 | -19.1 | 95138465.04 | 126.82 | 02-JAN-10:50 | -18.4 | -19.1 |
February | 0.703316E+10 | 4732.57 | 27-FEB-17:00 | -7.8 | -10.2 | 86396438.55 | 126.82 | 22-FEB-14:09 | -7.8 | -10.2 |
March | 0.137439E+11 | 7204.85 | 31-MAR-24:00 | 3.60 | 0.45 | 0.103236E+09 | 126.82 | 14-MAR-13:09 | 3.60 | 0.45 |
April | 0.191084E+11 | 8823.40 | 21-APR-18:10 | 10.82 | 2.42 | 91611351.86 | 126.82 | 27-APR-13:20 | 1.47 | -1.8 |
May | 0.489466E+10 | 3453.34 | 31-MAY-24:00 | 11.20 | 9.10 | 99236561.07 | 126.86 | 26-MAY-13:39 | 11.20 | 9.10 |
June | 0.969433E+10 | 5494.56 | 30-JUN-24:00 | 16.10 | 13.43 | 98967204.03 | 126.86 | 23-JUN-09:09 | 16.10 | 13.43 |
July | 0.152494E+11 | 7382.03 | 31-JUL-23:54 | 17.00 | 15.17 | 91888196.85 | 126.84 | 05-JUL-09:00 | 17.00 | 15.17 |
August | 0.202183E+11 | 8912.97 | 13-AUG-18:33 | 21.13 | 14.84 | 0.103240E+09 | 126.83 | 31-AUG-09:09 | 18.40 | 17.58 |
September | 0.456986E+10 | 3543.55 | 30-SEP-24:00 | 7.80 | 6.76 | 91609231.89 | 126.86 | 19-SEP-13:00 | 7.80 | 6.76 |
October | 0.942902E+10 | 5122.04 | 31-OCT-24:00 | 3.30 | -0.4 | 95230355.77 | 126.83 | 02-OCT-09:00 | 3.30 | -0.4 |
November | 0.135536E+11 | 6319.22 | 09-NOV-16:10 | 0.82 | -3.8 | 94300530.73 | 126.83 | 21-NOV-14:09 | 13.77 | 12.33 |
December | 0.179194E+11 | 7856.92 | 20-DEC-16:00 | -20.2 | -20.8 | 91880829.36 | 126.82 | 01-DEC-10:09 | -20.2 | -20.8 |
Annual Sum or Average | 0.137092E+12 | 0.114274E+10 | ||||||||
Minimum of Months | 0.167795E+10 | 2268.25 | -20.2 | -20.8 | 86396438.55 | 126.82 | -20.2 | -20.8 | ||
Maximum of Months | 0.202183E+11 | 8912.97 | 21.13 | 15.17 | 0.103240E+09 | 126.86 | 18.40 | 17.58 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.457874E+09 | 1813.11 | 27-JAN-16:30 | -15.6 | -16.5 | 90108589.12 | 126.82 | 20-JAN-14:09 | -15.6 | -16.5 |
February | 0.442472E+10 | 4119.03 | 27-FEB-17:00 | -7.8 | -10.2 | 86396459.40 | 126.82 | 22-FEB-14:09 | -7.8 | -10.2 |
March | 0.111055E+11 | 6405.78 | 31-MAR-23:30 | 3.85 | 0.59 | 0.103236E+09 | 126.82 | 14-MAR-13:09 | 3.85 | 0.59 |
April | 0.168001E+11 | 8422.88 | 21-APR-18:20 | 10.53 | 2.25 | 91606314.71 | 126.82 | 27-APR-13:20 | 1.47 | -1.8 |
May | 0.396810E+10 | 2972.06 | 14-MAY-18:43 | 18.17 | 8.43 | 99236126.20 | 126.85 | 26-MAY-09:00 | 22.60 | 18.32 |
June | 0.874397E+10 | 5222.31 | 30-JUN-24:00 | 16.10 | 13.43 | 98967689.36 | 126.86 | 30-JUN-13:00 | 16.10 | 13.43 |
July | 0.141303E+11 | 6924.27 | 31-JUL-23:54 | 17.00 | 15.17 | 91889777.24 | 126.85 | 05-JUL-09:00 | 17.00 | 15.17 |
August | 0.187351E+11 | 8251.62 | 02-AUG-18:40 | 18.53 | 13.51 | 0.103241E+09 | 126.83 | 28-AUG-13:00 | 20.60 | 18.71 |
September | 0.338770E+10 | 3016.51 | 03-SEP-17:41 | 20.78 | 15.57 | 91607274.53 | 126.85 | 01-SEP-13:00 | 20.78 | 15.57 |
October | 0.713808E+10 | 4242.44 | 18-OCT-16:50 | 15.28 | 10.42 | 95230323.95 | 126.83 | 02-OCT-13:00 | 15.28 | 10.42 |
November | 0.102260E+11 | 5651.60 | 09-NOV-16:20 | 0.53 | -4.0 | 94300520.38 | 126.83 | 21-NOV-14:09 | 13.77 | 12.33 |
December | 0.137977E+11 | 6944.20 | 20-DEC-16:10 | -20.4 | -21.0 | 91880843.27 | 126.82 | 01-DEC-10:09 | -20.4 | -21.0 |
Annual Sum or Average | 0.112915E+12 | 0.113770E+10 | ||||||||
Minimum of Months | 0.457874E+09 | 1813.11 | -20.4 | -21.0 | 86396459.40 | 126.82 | -20.4 | -21.0 | ||
Maximum of Months | 0.187351E+11 | 8422.88 | 20.78 | 15.57 | 0.103241E+09 | 126.86 | 22.60 | 18.71 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.340960E+09 | 1510.19 | 25-JAN-16:30 | -18.4 | -19.1 | 84369205.59 | 126.82 | 19-JAN-14:00 | -18.4 | -19.1 |
February | 0.281208E+10 | 3969.14 | 27-FEB-17:00 | -7.8 | -10.2 | 86390637.86 | 126.82 | 22-FEB-14:09 | -7.8 | -10.2 |
March | 0.935520E+10 | 6218.85 | 28-MAR-17:50 | 7.20 | 2.87 | 0.103236E+09 | 126.82 | 14-MAR-13:09 | 7.20 | 2.87 |
April | 0.155306E+11 | 8404.38 | 21-APR-18:20 | 10.53 | 2.25 | 91605582.92 | 126.82 | 27-APR-13:20 | 1.47 | -1.8 |
May | 0.351759E+10 | 2869.44 | 14-MAY-18:47 | 18.17 | 8.43 | 99233464.47 | 126.85 | 26-MAY-09:00 | 22.60 | 18.32 |
June | 0.850749E+10 | 5247.03 | 30-JUN-23:40 | 16.60 | 13.50 | 98967665.48 | 126.86 | 30-JUN-09:00 | 16.60 | 13.50 |
July | 0.140096E+11 | 6842.51 | 31-JUL-23:54 | 17.00 | 15.17 | 91889730.67 | 126.85 | 05-JUL-09:00 | 17.00 | 15.17 |
August | 0.185403E+11 | 8285.61 | 02-AUG-18:40 | 18.53 | 13.51 | 0.103242E+09 | 126.83 | 28-AUG-13:00 | 20.60 | 18.71 |
September | 0.273611E+10 | 2989.47 | 05-SEP-17:50 | 15.78 | 9.39 | 91607109.82 | 126.85 | 01-SEP-13:00 | 15.78 | 9.39 |
October | 0.556885E+10 | 4207.17 | 18-OCT-16:50 | 15.28 | 10.42 | 95230316.01 | 126.83 | 02-OCT-13:00 | 15.28 | 10.42 |
November | 0.823825E+10 | 5491.79 | 09-NOV-16:20 | 0.53 | -4.0 | 94300528.14 | 126.83 | 21-NOV-14:09 | 13.77 | 12.33 |
December | 0.120035E+11 | 6673.19 | 20-DEC-16:10 | -20.4 | -21.0 | 91880847.09 | 126.82 | 01-DEC-10:09 | -20.4 | -21.0 |
Annual Sum or Average | 0.101161E+12 | 0.113195E+10 | ||||||||
Minimum of Months | 0.340960E+09 | 1510.19 | -20.4 | -21.0 | 84369205.59 | 126.82 | -20.4 | -21.0 | ||
Maximum of Months | 0.185403E+11 | 8404.38 | 18.53 | 15.17 | 0.103242E+09 | 126.86 | 22.60 | 18.71 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.233646E+12 | 91202.48 | 20-JAN-17:00 | -7.2 | -8.4 | 0.206144E+10 | 2745.29 | 20-JAN-14:00 | -7.2 | -8.4 |
February | 0.433562E+12 | 183616.32 | 22-FEB-17:00 | -1.1 | -3.9 | 0.187023E+10 | 2745.42 | 13-FEB-10:09 | -1.1 | -3.9 |
March | 0.727852E+12 | 360426.56 | 31-MAR-24:00 | 3.60 | 0.45 | 0.223477E+10 | 2745.45 | 20-MAR-09:09 | 3.60 | 0.45 |
April | 0.946849E+12 | 369545.00 | 19-APR-16:00 | 7.20 | 1.06 | 0.198300E+10 | 2746.10 | 13-APR-09:09 | 7.20 | 1.06 |
May | 0.245169E+12 | 176934.20 | 31-MAY-24:00 | 11.20 | 9.10 | 0.214814E+10 | 2747.04 | 23-MAY-13:50 | 11.20 | 9.10 |
June | 0.474902E+12 | 270114.23 | 30-JUN-23:55 | 16.10 | 13.43 | 0.214246E+10 | 2748.93 | 22-JUN-09:00 | 16.10 | 13.43 |
July | 0.738001E+12 | 362144.94 | 31-JUL-23:52 | 17.00 | 15.17 | 0.199772E+10 | 3016.00 | 03-JUL-15:00 | 17.00 | 15.17 |
August | 0.983721E+12 | 379183.15 | 08-AUG-21:02 | 22.62 | 18.95 | 0.230373E+10 | 3855.10 | 08-AUG-13:00 | 22.62 | 18.95 |
September | 0.239892E+12 | 177804.92 | 30-SEP-24:00 | 7.80 | 6.76 | 0.198296E+10 | 2745.81 | 15-SEP-09:39 | 7.80 | 6.76 |
October | 0.490983E+12 | 269042.50 | 31-OCT-24:00 | 3.30 | -0.4 | 0.206146E+10 | 2746.94 | 19-OCT-13:00 | 3.30 | -0.4 |
November | 0.710309E+12 | 278122.79 | 17-NOV-17:00 | 6.70 | 1.30 | 0.204134E+10 | 2747.13 | 01-NOV-13:00 | 6.70 | 1.30 |
December | 0.972612E+12 | 368089.63 | 07-DEC-17:00 | -8.7 | -8.9 | 0.198896E+10 | 2745.44 | 26-DEC-10:20 | -23.7 | -24.0 |
Annual Sum or Average | 0.719750E+13 | 0.248162E+11 | ||||||||
Minimum of Months | 0.233646E+12 | 91202.48 | -8.7 | -8.9 | 0.187023E+10 | 2745.29 | -23.7 | -24.0 | ||
Maximum of Months | 0.983721E+12 | 379183.15 | 22.62 | 18.95 | 0.230373E+10 | 3855.10 | 22.62 | 18.95 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 510263.14 | 850.44 | 17-JAN-07:30 | -7.8 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -23.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:03 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 |
Annual Sum or Average | 510263.14 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 510263.14 | 850.44 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -21.9 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -23.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:03 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.00 | 0.00 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.136181E+10 | 56332.09 | 02-JAN-04:01 | -18.8 |
February | 85084602.24 | 44982.15 | 27-FEB-05:01 | -17.4 |
March | 17665755.10 | 43143.62 | 06-MAR-06:01 | -19.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:03 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 78516503.73 | 46921.16 | 27-NOV-05:01 | -7.2 |
December | 0.659778E+09 | 50949.34 | 26-DEC-05:01 | -25.9 |
Annual Sum or Average | 0.220285E+10 | |||
Minimum of Months | 0.00 | 0.00 | -25.9 | |
Maximum of Months | 0.136181E+10 | 56332.09 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107201E+11 | 80355.70 | 09-JAN-04:01 | -32.4 |
February | 0.529689E+10 | 78193.92 | 27-FEB-04:01 | -16.3 |
March | 0.255156E+10 | 78653.12 | 06-MAR-04:01 | -17.4 |
April | 0.529408E+09 | 71346.78 | 03-APR-04:11 | -5.2 |
May | 4327935.07 | 28852.90 | 01-MAY-05:03 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
October | 0.640175E+09 | 73801.26 | 30-OCT-03:01 | -9.5 |
November | 0.335008E+10 | 78001.88 | 27-NOV-04:01 | -7.2 |
December | 0.819279E+10 | 79169.47 | 11-DEC-04:01 | -24.8 |
Annual Sum or Average | 0.312853E+11 | |||
Minimum of Months | 0.00 | 0.00 | -32.4 | |
Maximum of Months | 0.107201E+11 | 80355.70 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.277713E+10 | 14095.27 | 09-JAN-04:01 | -32.4 |
February | 0.846587E+09 | 12907.85 | 14-FEB-05:01 | -32.1 |
March | 0.173124E+09 | 12111.55 | 07-MAR-05:01 | -23.6 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:03 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 17844851.53 | 11630.96 | 29-NOV-06:01 | -20.3 |
December | 0.933112E+09 | 12967.41 | 26-DEC-05:01 | -25.9 |
Annual Sum or Average | 0.474779E+10 | |||
Minimum of Months | 0.00 | 0.00 | -32.4 | |
Maximum of Months | 0.277713E+10 | 14095.27 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.165690E+10 | 16832.67 | 09-JAN-04:01 | -32.4 |
February | 0.574862E+09 | 15065.19 | 14-FEB-05:01 | -32.1 |
March | 0.141816E+09 | 13782.62 | 07-MAR-05:01 | -23.6 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:03 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 32237540.59 | 12880.35 | 29-NOV-06:01 | -20.3 |
December | 0.842538E+09 | 15301.60 | 20-DEC-05:01 | -28.7 |
Annual Sum or Average | 0.324835E+10 | |||
Minimum of Months | 0.00 | 0.00 | -32.4 | |
Maximum of Months | 0.165690E+10 | 16832.67 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.215987E+10 | 24113.25 | 09-JAN-04:01 | -32.4 |
February | 0.850162E+09 | 21886.45 | 14-FEB-05:01 | -32.1 |
March | 0.262409E+09 | 21173.21 | 06-MAR-05:01 | -18.4 |
April | 182913.78 | 2133.99 | 04-APR-05:01 | -9.0 |
May | 0.00 | 0.00 | 01-MAY-00:03 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
October | 3236921.04 | 17115.16 | 30-OCT-05:01 | -9.9 |
November | 0.100868E+09 | 19228.78 | 29-NOV-06:01 | -20.3 |
December | 0.114352E+10 | 22978.22 | 26-DEC-04:01 | -25.0 |
Annual Sum or Average | 0.452024E+10 | |||
Minimum of Months | 0.00 | 0.00 | -32.4 | |
Maximum of Months | 0.215987E+10 | 24113.25 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.763326E+09 | 14611.05 | 09-JAN-04:01 | -32.4 |
February | 95338049.01 | 12043.61 | 13-FEB-05:01 | -23.4 |
March | 3835929.55 | 11254.38 | 06-MAR-06:01 | -19.0 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:03 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 1298824.59 | 9046.40 | 25-NOV-06:01 | -19.4 |
December | 29372040.92 | 12081.28 | 26-DEC-05:01 | -25.9 |
Annual Sum or Average | 0.893171E+09 | |||
Minimum of Months | 0.00 | 0.00 | -32.4 | |
Maximum of Months | 0.763326E+09 | 14611.05 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107214E+11 | 14221.44 | 01-JAN-08:61 | -26.7 |
February | 0.540012E+10 | 13898.14 | 13-FEB-04:11 | -23.0 |
March | 0.276219E+10 | 13777.71 | 06-MAR-03:22 | -16.6 |
April | 0.315408E+09 | 12048.29 | 03-APR-04:01 | -5.4 |
May | 1375424.53 | 7697.94 | 01-MAY-05:03 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
October | 0.201173E+09 | 12161.52 | 30-OCT-04:01 | -10.0 |
November | 0.214471E+10 | 13482.04 | 27-NOV-04:11 | -7.2 |
December | 0.928543E+10 | 14117.30 | 25-DEC-05:31 | -29.5 |
Annual Sum or Average | 0.308318E+11 | |||
Minimum of Months | 0.00 | 0.00 | -29.5 | |
Maximum of Months | 0.107214E+11 | 14221.44 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.614640E+10 | 21945.68 | 02-JAN-04:01 | -18.8 |
February | 0.268838E+10 | 21413.10 | 13-FEB-04:11 | -23.0 |
March | 0.134346E+10 | 21023.71 | 06-MAR-04:01 | -17.4 |
April | 0.140670E+09 | 17813.65 | 04-APR-04:01 | -7.5 |
May | 0.00 | 0.00 | 01-MAY-00:03 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
September | 167481.59 | 454.89 | 28-SEP-05:05 | 6.70 |
October | 0.138082E+09 | 18476.71 | 30-OCT-04:01 | -10.0 |
November | 0.133896E+10 | 20591.69 | 27-NOV-04:11 | -7.2 |
December | 0.556690E+10 | 21749.88 | 25-DEC-05:31 | -29.5 |
Annual Sum or Average | 0.173630E+11 | |||
Minimum of Months | 0.00 | 0.00 | -29.5 | |
Maximum of Months | 0.614640E+10 | 21945.68 | 17.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.586234E+10 | 27574.35 | 01-JAN-08:61 | -26.7 |
February | 0.254120E+10 | 27121.56 | 13-FEB-04:11 | -23.0 |
March | 0.133292E+10 | 26449.96 | 06-MAR-04:01 | -17.4 |
April | 0.180275E+09 | 22908.77 | 04-APR-04:01 | -7.5 |
May | 0.00 | 0.00 | 01-MAY-00:03 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
October | 0.123681E+09 | 23599.36 | 30-OCT-04:01 | -10.0 |
November | 0.130701E+10 | 26338.99 | 27-NOV-04:11 | -7.2 |
December | 0.539608E+10 | 27518.79 | 26-DEC-04:11 | -25.1 |
Annual Sum or Average | 0.167435E+11 | |||
Minimum of Months | 0.00 | 0.00 | -26.7 | |
Maximum of Months | 0.586234E+10 | 27574.35 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.538723E+10 | 22028.11 | 02-JAN-04:01 | -18.8 |
February | 0.224832E+10 | 21360.52 | 13-FEB-04:11 | -23.0 |
March | 0.965058E+09 | 20952.14 | 06-MAR-04:01 | -17.4 |
April | 93606492.36 | 17339.56 | 04-APR-04:01 | -7.5 |
May | 11424.49 | 76.16 | 01-MAY-05:08 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
October | 73335731.77 | 17947.39 | 30-OCT-04:01 | -10.0 |
November | 0.898188E+09 | 20441.03 | 27-NOV-04:11 | -7.2 |
December | 0.433969E+10 | 21633.90 | 26-DEC-04:11 | -25.1 |
Annual Sum or Average | 0.140054E+11 | |||
Minimum of Months | 0.00 | 0.00 | -25.1 | |
Maximum of Months | 0.538723E+10 | 22028.11 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.167812E+11 | 17484.62 | 09-JAN-05:21 | -32.5 |
February | 0.105492E+11 | 17072.53 | 12-FEB-23:02 | -17.4 |
March | 0.658106E+10 | 16657.62 | 06-MAR-03:22 | -16.6 |
April | 0.149139E+10 | 15421.86 | 10-APR-03:11 | -2.1 |
May | 55572646.99 | 13532.43 | 01-MAY-04:02 | -2.9 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 23631.07 | 196.93 | 19-AUG-05:04 | 4.60 |
September | 35299539.21 | 12150.34 | 23-SEP-05:03 | 4.90 |
October | 0.139384E+10 | 15712.25 | 30-OCT-03:01 | -9.5 |
November | 0.595992E+10 | 16132.24 | 27-NOV-01:42 | -6.7 |
December | 0.154655E+11 | 17026.85 | 24-DEC-04:22 | -30.2 |
Annual Sum or Average | 0.583130E+11 | |||
Minimum of Months | 0.00 | 0.00 | -32.5 | |
Maximum of Months | 0.167812E+11 | 17484.62 | 15.83 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.997250E+10 | 24702.48 | 08-JAN-08:62 | -22.9 |
February | 0.555423E+10 | 24832.64 | 12-FEB-23:02 | -17.4 |
March | 0.321651E+10 | 23955.49 | 06-MAR-04:01 | -17.4 |
April | 0.663342E+09 | 22572.06 | 10-APR-03:11 | -2.1 |
May | 16512825.75 | 12738.35 | 01-MAY-04:02 | -2.9 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 463365.64 | 1627.79 | 19-AUG-05:02 | 4.60 |
September | 29119151.60 | 9956.58 | 23-SEP-05:03 | 4.90 |
October | 0.821222E+09 | 23104.30 | 30-OCT-03:01 | -9.5 |
November | 0.355515E+10 | 22842.25 | 20-NOV-05:21 | 5.00 |
December | 0.946557E+10 | 24687.36 | 24-DEC-04:22 | -30.2 |
Annual Sum or Average | 0.332946E+11 | |||
Minimum of Months | 0.00 | 0.00 | -30.2 | |
Maximum of Months | 0.997250E+10 | 24832.64 | 15.83 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.107552E+11 | 30202.96 | 08-JAN-08:62 | -22.9 |
February | 0.596474E+10 | 30103.81 | 12-FEB-23:02 | -17.4 |
March | 0.383035E+10 | 29255.08 | 05-MAR-06:42 | -28.6 |
April | 0.991949E+09 | 27546.31 | 10-APR-03:11 | -2.1 |
May | 43203065.97 | 14569.20 | 01-MAY-04:02 | -2.9 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 22020.34 | 183.50 | 19-AUG-05:04 | 4.60 |
September | 26646358.30 | 11475.67 | 28-SEP-05:03 | 6.70 |
October | 0.972308E+09 | 28130.09 | 30-OCT-03:01 | -9.5 |
November | 0.405220E+10 | 27797.54 | 20-NOV-05:21 | 5.00 |
December | 0.105384E+11 | 30126.30 | 24-DEC-04:22 | -30.2 |
Annual Sum or Average | 0.371750E+11 | |||
Minimum of Months | 0.00 | 0.00 | -30.2 | |
Maximum of Months | 0.107552E+11 | 30202.96 | 15.83 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.912064E+10 | 26308.99 | 08-JAN-08:62 | -22.9 |
February | 0.467988E+10 | 25849.72 | 12-FEB-23:02 | -17.4 |
March | 0.253908E+10 | 25264.35 | 06-MAR-04:01 | -17.4 |
April | 0.484845E+09 | 22972.67 | 03-APR-03:01 | -7.4 |
May | 13590043.21 | 8995.72 | 01-MAY-05:03 | -3.4 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
September | 6099938.96 | 5137.25 | 28-SEP-05:03 | 6.70 |
October | 0.526433E+09 | 24242.29 | 30-OCT-03:01 | -9.5 |
November | 0.249592E+10 | 23800.40 | 13-NOV-04:01 | -8.2 |
December | 0.761774E+10 | 25914.34 | 24-DEC-04:22 | -30.2 |
Annual Sum or Average | 0.274842E+11 | |||
Minimum of Months | 0.00 | 0.00 | -30.2 | |
Maximum of Months | 0.912064E+10 | 26308.99 | 17.07 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.265801E+10 | 9400.77 | 20-JAN-06:01 | -6.8 |
February | 0.102155E+10 | 13151.07 | 20-FEB-13:32 | 4.83 |
March | 0.456395E+09 | 17961.94 | 26-MAR-14:51 | 10.60 |
April | 0.259080E+09 | 15330.87 | 23-APR-15:41 | 26.52 |
May | 0.167004E+09 | 11108.07 | 21-MAY-15:22 | 22.60 |
June | 0.229915E+09 | 10616.96 | 04-JUN-14:52 | 21.10 |
July | 0.304359E+09 | 13214.86 | 23-JUL-15:52 | 30.00 |
August | 0.373581E+09 | 13821.97 | 20-AUG-15:11 | 25.20 |
September | 0.211699E+09 | 11423.42 | 29-SEP-04:12 | 7.20 |
October | 0.208831E+09 | 13640.91 | 31-OCT-04:11 | 10.00 |
November | 0.196251E+09 | 14023.59 | 14-NOV-05:11 | 3.13 |
December | 0.120475E+10 | 13652.27 | 06-DEC-05:01 | -0.4 |
Annual Sum or Average | 0.729141E+10 | |||
Minimum of Months | 0.167004E+09 | 9400.77 | -6.8 | |
Maximum of Months | 0.265801E+10 | 17961.94 | 30.00 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.711389E+10 | 21140.49 | 02-JAN-06:12 | -17.8 |
February | 0.371199E+10 | 16887.00 | 20-FEB-13:53 | 5.60 |
March | 0.231781E+10 | 21595.65 | 26-MAR-16:01 | 10.92 |
April | 0.562336E+09 | 17026.92 | 23-APR-15:31 | 26.33 |
May | 88720801.48 | 14781.26 | 14-MAY-16:11 | 20.00 |
June | 64877469.74 | 12791.87 | 04-JUN-15:21 | 21.10 |
July | 75468503.48 | 14174.37 | 23-JUL-16:01 | 29.72 |
August | 77973703.13 | 14695.58 | 20-AUG-15:01 | 25.40 |
September | 70236182.40 | 13361.43 | 03-SEP-15:32 | 21.70 |
October | 0.341986E+09 | 11810.93 | 09-OCT-13:12 | 5.77 |
November | 0.191569E+10 | 9489.34 | 28-NOV-13:35 | -8.3 |
December | 0.524834E+10 | 15056.72 | 26-DEC-06:15 | -26.6 |
Annual Sum or Average | 0.215893E+11 | |||
Minimum of Months | 64877469.74 | 9489.34 | -26.6 | |
Maximum of Months | 0.711389E+10 | 21595.65 | 29.72 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.222425E+11 | 35621.33 | 09-JAN-05:41 | -32.0 |
February | 0.145020E+11 | 33529.34 | 13-FEB-05:12 | -23.5 |
March | 0.976332E+10 | 29519.99 | 06-MAR-06:12 | -19.1 |
April | 0.303537E+10 | 20123.60 | 03-APR-05:03 | -4.3 |
May | 0.523253E+09 | 14322.43 | 16-MAY-05:02 | 8.98 |
June | 0.130448E+09 | 14194.39 | 16-JUN-05:03 | 8.68 |
July | 0.103458E+09 | 13858.18 | 18-JUL-05:03 | 8.27 |
August | 0.142590E+09 | 13313.84 | 25-AUG-05:03 | 7.88 |
September | 0.635459E+09 | 11986.65 | 08-SEP-05:03 | 10.10 |
October | 0.320668E+10 | 25386.34 | 30-OCT-05:13 | -9.8 |
November | 0.940517E+10 | 27695.22 | 24-NOV-05:22 | -10.6 |
December | 0.202312E+11 | 35023.87 | 26-DEC-05:12 | -26.1 |
Annual Sum or Average | 0.839214E+11 | |||
Minimum of Months | 0.103458E+09 | 11986.65 | -32.0 | |
Maximum of Months | 0.222425E+11 | 35621.33 | 10.10 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 50587666.22 | 598.77 | 01-JAN-08:20 | -26.7 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -23.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:03 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 |
Annual Sum or Average | 50587666.22 | |||
Minimum of Months | 0.00 | 0.00 | -26.7 | |
Maximum of Months | 50587666.22 | 598.77 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.744593E+09 | 649.80 | 01-JAN-17:05 | -19.1 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -23.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:03 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 |
Annual Sum or Average | 0.744593E+09 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.744593E+09 | 649.80 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.815819E+09 | 661.63 | 01-JAN-17:05 | -19.1 |
February | 0.130142E+09 | 593.39 | 13-FEB-04:00 | -22.8 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 3453193.04 | 390.26 | 01-MAY-01:55 | -1.3 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
October | 3404950.33 | 402.17 | 29-OCT-22:45 | -7.1 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 |
Annual Sum or Average | 0.952819E+09 | |||
Minimum of Months | 0.00 | 0.00 | -22.8 | |
Maximum of Months | 0.815819E+09 | 661.63 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -21.9 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -23.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
May | 0.00 | 0.00 | 01-MAY-00:03 | -0.0 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 |
December | 0.00 | 0.00 | 01-DEC-00:10 | -8.8 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -23.1 | |
Maximum of Months | 0.00 | 0.00 | 19.75 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180249E+11 | 19402.09 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.163527E+11 | 19402.09 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.194806E+11 | 19402.09 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.173504E+11 | 19402.09 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.187528E+11 | 19402.09 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.186803E+11 | 19402.09 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.174228E+11 | 19402.09 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.194803E+11 | 19402.09 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.173504E+11 | 19402.09 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.180252E+11 | 19402.09 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.178272E+11 | 19402.09 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.174231E+11 | 19402.09 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.216171E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.163527E+11 | 19402.09 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.194806E+11 | 19402.09 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.138279E+10 | 2187.81 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.111701E+10 | 1906.53 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.124722E+10 | 1906.53 | 03-MAR-16:49 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.104919E+10 | 1242.97 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.109024E+10 | 1040.96 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.107702E+10 | 1242.97 | 30-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.101020E+10 | 1040.96 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.116513E+10 | 1524.25 | 31-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.107567E+10 | 1524.25 | 19-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.120907E+10 | 2187.81 | 26-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.133651E+10 | 2187.81 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.137727E+10 | 2187.81 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.141373E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.101020E+10 | 1040.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.138279E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.863920E+09 | 1409.91 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.710529E+09 | 1409.91 | 02-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.796818E+09 | 1228.64 | 03-MAR-16:49 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.676203E+09 | 735.93 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.708023E+09 | 670.83 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.699937E+09 | 735.93 | 09-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.656249E+09 | 670.83 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.751886E+09 | 982.28 | 31-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.691204E+09 | 982.28 | 19-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.765229E+09 | 1409.91 | 26-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.843332E+09 | 1409.91 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.862379E+09 | 1409.91 | 01-DEC-16:19 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.902571E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.656249E+09 | 670.83 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.863920E+09 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.130223E+10 | 2187.86 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.108264E+10 | 1906.57 | 02-FEB-16:49 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.123180E+10 | 1906.57 | 03-MAR-16:00 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.105108E+10 | 1243.00 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.109831E+10 | 1040.98 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.108544E+10 | 1243.00 | 30-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.101756E+10 | 1040.98 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.116893E+10 | 1524.28 | 31-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.107240E+10 | 1524.28 | 19-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.117614E+10 | 2187.86 | 26-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.127688E+10 | 2187.86 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.130238E+10 | 2187.86 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.138658E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.101756E+10 | 1040.98 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.130238E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.863410E+09 | 1409.91 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.705223E+09 | 1228.64 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.798045E+09 | 1228.64 | 13-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.675449E+09 | 801.02 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.702950E+09 | 735.93 | 12-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.693762E+09 | 801.02 | 09-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.650528E+09 | 735.93 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.751566E+09 | 982.28 | 28-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.692927E+09 | 982.28 | 12-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.770800E+09 | 1409.91 | 26-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.837462E+09 | 1409.91 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.859578E+09 | 1409.91 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.900170E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.650528E+09 | 735.93 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.863410E+09 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.137823E+10 | 2187.81 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.111406E+10 | 1906.53 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.124440E+10 | 1906.53 | 03-MAR-16:49 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.104821E+10 | 1242.97 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.108988E+10 | 1040.96 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.107607E+10 | 1141.96 | 09-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.100992E+10 | 1040.96 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.116409E+10 | 1524.25 | 31-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.107425E+10 | 1524.25 | 19-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.120486E+10 | 2187.81 | 26-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.133285E+10 | 2187.81 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.137226E+10 | 2187.81 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.141091E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.100992E+10 | 1040.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.137823E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.862055E+09 | 1409.91 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.709792E+09 | 1409.91 | 02-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.795600E+09 | 1228.64 | 03-MAR-16:49 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.675787E+09 | 735.93 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.707630E+09 | 670.83 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.699270E+09 | 735.93 | 09-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.655815E+09 | 670.83 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.750856E+09 | 982.28 | 31-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.690467E+09 | 982.28 | 19-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.763804E+09 | 1409.91 | 30-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.841588E+09 | 1409.91 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.860357E+09 | 1409.91 | 01-DEC-16:19 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.901302E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.655815E+09 | 670.83 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.862055E+09 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.130187E+10 | 2187.86 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.108099E+10 | 1906.57 | 02-FEB-16:49 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.123053E+10 | 1906.57 | 03-MAR-16:00 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.105030E+10 | 1141.99 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.109756E+10 | 1040.98 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.108455E+10 | 1141.99 | 09-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.101704E+10 | 1040.98 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.116759E+10 | 1524.28 | 31-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.107102E+10 | 1524.28 | 19-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.117488E+10 | 2187.86 | 26-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.127544E+10 | 2187.86 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.130123E+10 | 2187.86 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.138530E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.101704E+10 | 1040.98 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.130187E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.861381E+09 | 1409.91 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.704284E+09 | 1228.64 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.796693E+09 | 1228.64 | 13-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.674718E+09 | 801.02 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.702632E+09 | 735.93 | 12-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.693321E+09 | 801.02 | 30-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.650138E+09 | 735.93 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.750385E+09 | 982.28 | 28-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.692223E+09 | 982.28 | 12-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.769083E+09 | 1409.91 | 26-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.835740E+09 | 1409.91 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.857668E+09 | 1409.91 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.898827E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.650138E+09 | 735.93 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.861381E+09 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.137811E+10 | 2187.81 | 02-JAN-08:09 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.111406E+10 | 1906.53 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.124423E+10 | 1906.53 | 03-MAR-16:49 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.104817E+10 | 1242.97 | 03-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.108984E+10 | 1040.96 | 01-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.107607E+10 | 1141.96 | 09-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.100988E+10 | 1040.96 | 03-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.116407E+10 | 1524.25 | 31-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.107421E+10 | 1524.25 | 19-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.120445E+10 | 2187.81 | 26-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.133233E+10 | 2187.81 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.137214E+10 | 2187.81 | 01-DEC-08:09 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.141075E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.100988E+10 | 1040.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.137811E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.862014E+09 | 1409.91 | 02-JAN-08:09 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.709806E+09 | 1409.91 | 02-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.795294E+09 | 1228.64 | 03-MAR-16:49 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.675812E+09 | 735.93 | 03-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.707608E+09 | 670.83 | 01-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.699270E+09 | 735.93 | 09-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.655800E+09 | 670.83 | 03-JUL-07:10 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.750856E+09 | 982.28 | 31-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.690441E+09 | 982.28 | 19-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.763690E+09 | 1409.91 | 30-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.841575E+09 | 1409.91 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.860355E+09 | 1409.91 | 01-DEC-16:19 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.901252E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.655800E+09 | 670.83 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.862014E+09 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.130187E+10 | 2187.86 | 02-JAN-08:09 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.108099E+10 | 1906.57 | 02-FEB-16:49 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.123049E+10 | 1906.57 | 03-MAR-16:00 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.105022E+10 | 1141.99 | 03-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.109752E+10 | 1040.98 | 01-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.108452E+10 | 1141.99 | 09-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.101697E+10 | 1040.98 | 03-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.116752E+10 | 1524.28 | 31-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.107090E+10 | 1524.28 | 19-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.117478E+10 | 2187.86 | 26-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.127538E+10 | 2187.86 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.130089E+10 | 2187.86 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.138520E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.101697E+10 | 1040.98 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.130187E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.861329E+09 | 1409.91 | 02-JAN-08:09 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.704134E+09 | 1228.64 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.796654E+09 | 1228.64 | 13-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.674677E+09 | 801.02 | 03-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.702632E+09 | 735.93 | 12-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.693345E+09 | 801.02 | 30-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.650138E+09 | 735.93 | 03-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.750379E+09 | 982.28 | 28-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.692072E+09 | 982.28 | 12-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.769070E+09 | 1409.91 | 26-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.835701E+09 | 1409.91 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.857541E+09 | 1409.91 | 01-DEC-08:09 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.898767E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.650138E+09 | 735.93 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.861329E+09 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.522764E+10 | 5470.56 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.474186E+10 | 5470.56 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.563465E+10 | 5470.56 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.503289E+10 | 5470.56 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.543115E+10 | 5470.56 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.540489E+10 | 5470.56 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.505915E+10 | 5470.56 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.563465E+10 | 5470.56 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.503289E+10 | 5470.56 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.522764E+10 | 5470.56 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.516637E+10 | 5470.56 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.505915E+10 | 5470.56 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.626529E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.474186E+10 | 5470.56 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.563465E+10 | 5470.56 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.180249E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.163527E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.194806E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.173504E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.187528E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.186803E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.174228E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.194803E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.173504E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.180252E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.178272E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.174231E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.216171E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.163527E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.194806E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.138279E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.750162E+09 |
February | 0.136985E+10 | 0.111701E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667169E+09 |
March | 0.163685E+10 | 0.124722E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462211E+09 |
April | 0.145243E+10 | 0.104919E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8372.42 | 0.464058E+09 |
May | 0.157338E+10 | 0.109024E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1246711.61 | 0.218476E+09 |
June | 0.156900E+10 | 0.107702E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4534247.03 | 0.120493E+09 |
July | 0.145680E+10 | 0.101020E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5413752.37 | 86796665.86 |
August | 0.163685E+10 | 0.116513E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1895726.79 | 0.122548E+09 |
September | 0.145243E+10 | 0.107567E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62564.94 | 0.211159E+09 |
October | 0.150991E+10 | 0.120907E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329228E+09 |
November | 0.149516E+10 | 0.133651E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.571293E+09 |
December | 0.145680E+10 | 0.137727E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.815235E+09 |
Annual Sum or Average | 0.181194E+11 | 0.141373E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13161375.15 | 0.481883E+10 |
Minimum of Months | 0.136985E+10 | 0.101020E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86796665.86 |
Maximum of Months | 0.163685E+10 | 0.138279E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5413752.37 | 0.815235E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.863920E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499544E+09 |
February | 0.882782E+09 | 0.710529E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444926E+09 |
March | 0.105485E+10 | 0.796818E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306876E+09 |
April | 0.936002E+09 | 0.676203E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 117703.73 | 0.304151E+09 |
May | 0.101394E+10 | 0.708023E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 829643.39 | 0.144242E+09 |
June | 0.101113E+10 | 0.699937E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3324231.39 | 77500105.68 |
July | 0.938820E+09 | 0.656249E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3785160.58 | 53054888.12 |
August | 0.105485E+10 | 0.751886E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1270622.66 | 77144986.43 |
September | 0.936002E+09 | 0.691204E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41659.52 | 0.138451E+09 |
October | 0.973041E+09 | 0.765229E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215991E+09 |
November | 0.963541E+09 | 0.843332E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374297E+09 |
December | 0.938820E+09 | 0.862379E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538281E+09 |
Annual Sum or Average | 0.116768E+11 | 0.902571E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 9369021.26 | 0.317446E+10 |
Minimum of Months | 0.882782E+09 | 0.656249E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53054888.12 |
Maximum of Months | 0.105485E+10 | 0.863920E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3785160.58 | 0.538281E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.130223E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.754103E+09 |
February | 0.136988E+10 | 0.108264E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.677720E+09 |
March | 0.163688E+10 | 0.123180E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466653E+09 |
April | 0.145246E+10 | 0.105108E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1644.14 | 0.456047E+09 |
May | 0.157341E+10 | 0.109831E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1238640.32 | 0.213615E+09 |
June | 0.156904E+10 | 0.108544E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4735446.04 | 0.114839E+09 |
July | 0.145684E+10 | 0.101756E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5403624.11 | 81731354.36 |
August | 0.163688E+10 | 0.116893E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1878454.59 | 0.119248E+09 |
September | 0.145246E+10 | 0.107240E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49780.75 | 0.209375E+09 |
October | 0.150994E+10 | 0.117614E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321621E+09 |
November | 0.149520E+10 | 0.127688E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556810E+09 |
December | 0.145684E+10 | 0.130238E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.815190E+09 |
Annual Sum or Average | 0.181198E+11 | 0.138658E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13307589.96 | 0.478695E+10 |
Minimum of Months | 0.136988E+10 | 0.101756E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81731354.36 |
Maximum of Months | 0.163688E+10 | 0.130238E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5403624.11 | 0.815190E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.863410E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512817E+09 |
February | 0.882782E+09 | 0.705223E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465869E+09 |
March | 0.105485E+10 | 0.798045E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326209E+09 |
April | 0.936002E+09 | 0.675449E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.64 | 0.321555E+09 |
May | 0.101394E+10 | 0.702950E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 824897.50 | 0.144808E+09 |
June | 0.101113E+10 | 0.693762E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3143662.21 | 79474227.95 |
July | 0.938820E+09 | 0.650528E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3592933.97 | 57902249.20 |
August | 0.105485E+10 | 0.751566E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1249887.22 | 83507527.07 |
September | 0.936002E+09 | 0.692927E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40994.09 | 0.137359E+09 |
October | 0.973041E+09 | 0.770800E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219621E+09 |
November | 0.963541E+09 | 0.837462E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388854E+09 |
December | 0.938820E+09 | 0.859578E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.573662E+09 |
Annual Sum or Average | 0.116768E+11 | 0.900170E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8852382.64 | 0.331164E+10 |
Minimum of Months | 0.882782E+09 | 0.650528E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57902249.20 |
Maximum of Months | 0.105485E+10 | 0.863410E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3592933.97 | 0.573662E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.137823E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165298E+10 |
February | 0.136985E+10 | 0.111406E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142606E+10 |
March | 0.163685E+10 | 0.124440E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.990963E+09 |
April | 0.145243E+10 | 0.104821E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1448805.73 | 0.933939E+09 |
May | 0.157338E+10 | 0.108988E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2792378.46 | 0.466019E+09 |
June | 0.156900E+10 | 0.107607E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10991061.25 | 0.255302E+09 |
July | 0.145680E+10 | 0.100992E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13128739.02 | 0.185223E+09 |
August | 0.163685E+10 | 0.116409E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4374204.33 | 0.251808E+09 |
September | 0.145243E+10 | 0.107425E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 135281.42 | 0.432370E+09 |
October | 0.150991E+10 | 0.120486E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646530E+09 |
November | 0.149516E+10 | 0.133285E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114048E+10 |
December | 0.145680E+10 | 0.137226E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176320E+10 |
Annual Sum or Average | 0.181194E+11 | 0.141091E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32870470.22 | 0.101449E+11 |
Minimum of Months | 0.136985E+10 | 0.100992E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185223E+09 |
Maximum of Months | 0.163685E+10 | 0.137823E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13128739.02 | 0.176320E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.862055E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110523E+10 |
February | 0.649041E+09 | 0.709792E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.962279E+09 |
March | 0.773965E+09 | 0.795600E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674065E+09 |
April | 0.688021E+09 | 0.675787E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1137972.95 | 0.640043E+09 |
May | 0.744847E+09 | 0.707630E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1871704.67 | 0.315985E+09 |
June | 0.742030E+09 | 0.699270E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7946927.52 | 0.170389E+09 |
July | 0.690839E+09 | 0.655815E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9024754.65 | 0.120686E+09 |
August | 0.773965E+09 | 0.750856E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2950136.04 | 0.171168E+09 |
September | 0.688021E+09 | 0.690467E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90172.13 | 0.289712E+09 |
October | 0.715730E+09 | 0.763804E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434676E+09 |
November | 0.708685E+09 | 0.841588E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.764102E+09 |
December | 0.690839E+09 | 0.860357E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117761E+10 |
Annual Sum or Average | 0.858171E+10 | 0.901302E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23021667.95 | 0.682594E+10 |
Minimum of Months | 0.649041E+09 | 0.655815E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120686E+09 |
Maximum of Months | 0.773965E+09 | 0.862055E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9024754.65 | 0.117761E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.130187E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169411E+10 |
February | 0.136988E+10 | 0.108099E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152010E+10 |
March | 0.163688E+10 | 0.123053E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105286E+10 |
April | 0.145246E+10 | 0.105030E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3680.46 | 0.994019E+09 |
May | 0.157341E+10 | 0.109756E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2789624.36 | 0.477067E+09 |
June | 0.156904E+10 | 0.108455E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11182568.05 | 0.253905E+09 |
July | 0.145684E+10 | 0.101704E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12529052.11 | 0.186230E+09 |
August | 0.163688E+10 | 0.116759E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4269003.01 | 0.268646E+09 |
September | 0.145246E+10 | 0.107102E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 110421.80 | 0.464209E+09 |
October | 0.150994E+10 | 0.117488E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.692726E+09 |
November | 0.149520E+10 | 0.127544E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119274E+10 |
December | 0.145684E+10 | 0.130123E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180604E+10 |
Annual Sum or Average | 0.181198E+11 | 0.138530E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30884349.80 | 0.106026E+11 |
Minimum of Months | 0.136988E+10 | 0.101704E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186230E+09 |
Maximum of Months | 0.163688E+10 | 0.130187E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12529052.11 | 0.180604E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.861381E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111452E+10 |
February | 0.882782E+09 | 0.704284E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.981915E+09 |
March | 0.105485E+10 | 0.796693E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.688725E+09 |
April | 0.936002E+09 | 0.674718E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655856E+09 |
May | 0.101394E+10 | 0.702632E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1861578.34 | 0.327237E+09 |
June | 0.101113E+10 | 0.693321E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7463324.69 | 0.176998E+09 |
July | 0.938820E+09 | 0.650138E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8547011.32 | 0.133886E+09 |
August | 0.105485E+10 | 0.750385E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2891197.16 | 0.182093E+09 |
September | 0.936002E+09 | 0.692223E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90206.32 | 0.299525E+09 |
October | 0.973041E+09 | 0.769083E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.446395E+09 |
November | 0.963541E+09 | 0.835740E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.777060E+09 |
December | 0.938820E+09 | 0.857668E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119046E+10 |
Annual Sum or Average | 0.116768E+11 | 0.898827E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 20853317.84 | 0.697468E+10 |
Minimum of Months | 0.882782E+09 | 0.650138E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133886E+09 |
Maximum of Months | 0.105485E+10 | 0.861381E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8547011.32 | 0.119046E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.137811E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203499E+10 |
February | 0.136985E+10 | 0.111406E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173526E+10 |
March | 0.163685E+10 | 0.124423E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118481E+10 |
April | 0.145243E+10 | 0.104817E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2427017.93 | 0.107433E+10 |
May | 0.157338E+10 | 0.108984E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3280801.19 | 0.553404E+09 |
June | 0.156900E+10 | 0.107607E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13165603.94 | 0.306644E+09 |
July | 0.145680E+10 | 0.100988E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15337934.30 | 0.225994E+09 |
August | 0.163685E+10 | 0.116407E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5203613.08 | 0.304398E+09 |
September | 0.145243E+10 | 0.107421E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 152845.02 | 0.502892E+09 |
October | 0.150991E+10 | 0.120445E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.732744E+09 |
November | 0.149516E+10 | 0.133233E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134702E+10 |
December | 0.145680E+10 | 0.137214E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216216E+10 |
Annual Sum or Average | 0.181194E+11 | 0.141075E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39567815.45 | 0.121647E+11 |
Minimum of Months | 0.136985E+10 | 0.100988E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225994E+09 |
Maximum of Months | 0.163685E+10 | 0.137811E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15337934.30 | 0.216216E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.862014E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136384E+10 |
February | 0.882782E+09 | 0.709806E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116583E+10 |
March | 0.105485E+10 | 0.795294E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.806143E+09 |
April | 0.936002E+09 | 0.675812E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1626399.11 | 0.748030E+09 |
May | 0.101394E+10 | 0.707608E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2193226.51 | 0.380979E+09 |
June | 0.101113E+10 | 0.699270E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9480858.36 | 0.207203E+09 |
July | 0.938820E+09 | 0.655800E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10461512.87 | 0.148739E+09 |
August | 0.105485E+10 | 0.750856E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3461479.22 | 0.210554E+09 |
September | 0.936002E+09 | 0.690441E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 101890.42 | 0.343365E+09 |
October | 0.973041E+09 | 0.763690E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499771E+09 |
November | 0.963541E+09 | 0.841575E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.903789E+09 |
December | 0.938820E+09 | 0.860355E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144721E+10 |
Annual Sum or Average | 0.116768E+11 | 0.901252E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27325366.49 | 0.822545E+10 |
Minimum of Months | 0.882782E+09 | 0.655800E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148739E+09 |
Maximum of Months | 0.105485E+10 | 0.862014E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10461512.87 | 0.144721E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.130187E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206918E+10 |
February | 0.136988E+10 | 0.108099E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181708E+10 |
March | 0.163688E+10 | 0.123049E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125750E+10 |
April | 0.145246E+10 | 0.105022E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 649.35 | 0.115876E+10 |
May | 0.157341E+10 | 0.109752E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3277400.50 | 0.571838E+09 |
June | 0.156904E+10 | 0.108452E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13443306.77 | 0.305259E+09 |
July | 0.145684E+10 | 0.101697E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14741144.46 | 0.227023E+09 |
August | 0.163688E+10 | 0.116752E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5039480.45 | 0.326849E+09 |
September | 0.145246E+10 | 0.107090E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 131144.79 | 0.550167E+09 |
October | 0.150994E+10 | 0.117478E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.796034E+09 |
November | 0.149520E+10 | 0.127538E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139668E+10 |
December | 0.145684E+10 | 0.130089E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219695E+10 |
Annual Sum or Average | 0.181198E+11 | 0.138520E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36633126.32 | 0.126733E+11 |
Minimum of Months | 0.136988E+10 | 0.101697E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227023E+09 |
Maximum of Months | 0.163688E+10 | 0.130187E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14741144.46 | 0.219695E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.861329E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136859E+10 |
February | 0.882782E+09 | 0.704134E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118520E+10 |
March | 0.105485E+10 | 0.796654E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.826905E+09 |
April | 0.936002E+09 | 0.674677E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.770798E+09 |
May | 0.101394E+10 | 0.702632E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2187197.68 | 0.394631E+09 |
June | 0.101113E+10 | 0.693345E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9085808.70 | 0.214111E+09 |
July | 0.938820E+09 | 0.650138E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10114006.71 | 0.164006E+09 |
August | 0.105485E+10 | 0.750379E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3467643.76 | 0.221894E+09 |
September | 0.936002E+09 | 0.692072E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 101884.45 | 0.355401E+09 |
October | 0.973041E+09 | 0.769070E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519825E+09 |
November | 0.963541E+09 | 0.835701E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.919139E+09 |
December | 0.938820E+09 | 0.857541E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145607E+10 |
Annual Sum or Average | 0.116768E+11 | 0.898767E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24956541.29 | 0.839656E+10 |
Minimum of Months | 0.882782E+09 | 0.650138E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164006E+09 |
Maximum of Months | 0.105485E+10 | 0.861329E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10114006.71 | 0.145607E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.522764E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.474186E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.563465E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.503289E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.543115E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.540489E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.505915E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.563465E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.503289E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.522764E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.516637E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.505915E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.626529E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.474186E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.563465E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159222E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142512E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.981035E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18407.99 | 0.965081E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1618127.81 | 0.449821E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7559354.08 | 0.247460E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8786624.86 | 0.180024E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2472820.20 | 0.256443E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51079.07 | 0.438828E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683750E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120090E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174042E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20506414.01 | 0.101611E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180024E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8786624.86 | 0.174042E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268403E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240148E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166892E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1425405.31 | 0.160030E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3151216.81 | 0.761366E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16336309.56 | 0.409392E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18988338.85 | 0.293575E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4911863.26 | 0.416543E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104666.99 | 0.731089E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111553E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195920E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289817E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44917800.78 | 0.169396E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293575E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18988338.85 | 0.289817E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296622E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258826E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180828E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 381294.32 | 0.170200E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2229136.01 | 0.857895E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14771205.85 | 0.468412E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14304089.44 | 0.343645E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3758996.06 | 0.480576E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26841.69 | 0.802888E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115531E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204453E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.316366E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35471563.37 | 0.183817E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343645E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14771205.85 | 0.316366E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 19402.09 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 19402.09 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 19402.09 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 19402.09 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 19402.09 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 19402.09 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 19402.09 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 19402.09 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 19402.09 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 19402.09 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 19402.09 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 19402.09 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 19402.09 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 19402.09 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2187.81 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1311.76 | 04-JAN-05:51 |
February | 2010.79 | 01-FEB-10:09 | 1906.53 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1668.79 | 12-FEB-22:52 |
March | 2010.79 | 01-MAR-10:09 | 1906.53 | 03-MAR-16:49 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 803.75 | 15-MAR-04:51 |
April | 2010.79 | 03-APR-09:09 | 1242.97 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.38 | 23-APR-15:50 | 757.83 | 09-APR-13:00 |
May | 2010.79 | 01-MAY-09:09 | 1040.96 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.39 | 24-MAY-15:00 | 373.23 | 08-MAY-24:00 |
June | 2010.79 | 01-JUN-09:09 | 1242.97 | 30-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.21 | 29-JUN-21:02 | 274.83 | 10-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 1040.96 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 | 23-JUL-15:00 | 253.92 | 09-JUL-10:00 |
August | 2010.79 | 01-AUG-09:09 | 1524.25 | 31-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.55 | 08-AUG-16:00 | 348.81 | 27-AUG-05:57 |
September | 2010.79 | 01-SEP-09:09 | 1524.25 | 19-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.76 | 01-SEP-15:00 | 447.45 | 20-SEP-00:30 |
October | 2010.79 | 02-OCT-09:09 | 2187.81 | 26-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 566.86 | 31-OCT-21:10 |
November | 2010.79 | 01-NOV-09:09 | 2187.81 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1074.30 | 22-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1303.42 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.92 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 81.26 | 1668.79 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 874.28 | 04-JAN-05:51 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 02-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1102.27 | 12-FEB-22:52 |
March | 1295.83 | 01-MAR-10:09 | 1228.64 | 03-MAR-16:49 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 535.84 | 15-MAR-04:56 |
April | 1295.83 | 03-APR-09:09 | 735.93 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.07 | 23-APR-15:50 | 495.96 | 16-APR-12:00 |
May | 1295.83 | 01-MAY-09:09 | 670.83 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.94 | 24-MAY-15:00 | 264.66 | 14-MAY-07:40 |
June | 1295.83 | 01-JUN-09:09 | 735.93 | 09-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.68 | 24-JUN-17:10 | 177.73 | 10-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 670.83 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.58 | 23-JUL-15:14 | 164.16 | 09-JUL-10:00 |
August | 1295.83 | 01-AUG-09:09 | 982.28 | 31-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.68 | 08-AUG-16:00 | 223.98 | 27-AUG-05:57 |
September | 1295.83 | 01-SEP-09:09 | 982.28 | 19-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.84 | 01-SEP-15:00 | 296.97 | 20-SEP-00:30 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 26-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 368.95 | 31-OCT-21:10 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 703.32 | 22-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-16:19 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 868.95 | 16-DEC-05:56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.16 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 57.58 | 1102.27 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2187.86 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1311.09 | 04-JAN-05:51 |
February | 2010.83 | 01-FEB-10:09 | 1906.57 | 02-FEB-16:49 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1619.02 | 12-FEB-22:52 |
March | 2010.83 | 01-MAR-10:09 | 1906.57 | 03-MAR-16:00 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 803.76 | 15-MAR-04:56 |
April | 2010.83 | 03-APR-09:09 | 1243.00 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.01 | 23-APR-16:24 | 827.91 | 16-APR-12:00 |
May | 2010.83 | 01-MAY-09:09 | 1040.98 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.41 | 24-MAY-15:00 | 364.75 | 08-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 1243.00 | 30-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.01 | 29-JUN-21:02 | 255.67 | 10-JUN-22:00 |
July | 2010.83 | 03-JUL-09:09 | 1040.98 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.25 | 23-JUL-15:00 | 232.77 | 09-JUL-10:00 |
August | 2010.83 | 01-AUG-09:09 | 1524.28 | 31-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.36 | 08-AUG-16:00 | 339.54 | 27-AUG-05:57 |
September | 2010.83 | 01-SEP-09:09 | 1524.28 | 19-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.65 | 01-SEP-15:00 | 436.11 | 20-SEP-00:30 |
October | 2010.83 | 02-OCT-09:09 | 2187.86 | 26-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 547.71 | 31-OCT-21:10 |
November | 2010.83 | 01-NOV-09:09 | 2187.86 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1026.40 | 22-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 2187.86 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1303.43 | 16-DEC-05:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.77 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 81.25 | 1619.02 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 875.95 | 04-JAN-05:51 |
February | 1295.83 | 01-FEB-10:09 | 1228.64 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 1161.50 | 12-FEB-22:52 |
March | 1295.83 | 01-MAR-10:09 | 1228.64 | 13-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 561.73 | 17-MAR-04:00 |
April | 1295.83 | 03-APR-09:09 | 801.02 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 | 23-APR-15:57 | 531.91 | 09-APR-13:00 |
May | 1295.83 | 01-MAY-09:09 | 735.93 | 12-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.94 | 24-MAY-15:00 | 247.69 | 08-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 801.02 | 09-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.33 | 29-JUN-16:00 | 189.66 | 10-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 735.93 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.72 | 23-JUL-14:34 | 183.21 | 16-JUL-17:20 |
August | 1295.83 | 01-AUG-09:09 | 982.28 | 28-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.31 | 08-AUG-16:00 | 247.11 | 27-AUG-05:57 |
September | 1295.83 | 01-SEP-09:09 | 982.28 | 12-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.84 | 01-SEP-15:00 | 294.27 | 20-SEP-00:30 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 26-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 373.87 | 31-OCT-21:10 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 730.10 | 22-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 878.71 | 16-DEC-05:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 735.93 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.21 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 58.72 | 1161.50 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2187.81 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2976.10 | 04-JAN-06:00 |
February | 2010.79 | 01-FEB-10:09 | 1906.53 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3528.22 | 12-FEB-23:00 |
March | 2010.79 | 01-MAR-10:09 | 1906.53 | 03-MAR-16:49 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1871.31 | 15-MAR-04:51 |
April | 2010.79 | 03-APR-09:09 | 1242.97 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.18 | 23-APR-15:53 | 1496.93 | 01-APR-19:00 |
May | 2010.79 | 01-MAY-09:09 | 1040.96 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.38 | 24-MAY-15:00 | 794.98 | 29-MAY-18:00 |
June | 2010.79 | 01-JUN-09:09 | 1141.96 | 09-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.73 | 29-JUN-21:02 | 532.86 | 20-JUN-04:00 |
July | 2010.79 | 03-JUL-09:09 | 1040.96 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.25 | 23-JUL-15:00 | 530.56 | 06-JUL-22:00 |
August | 2010.79 | 01-AUG-09:09 | 1524.25 | 31-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.05 | 08-AUG-16:00 | 695.29 | 27-AUG-05:53 |
September | 2010.79 | 01-SEP-09:09 | 1524.25 | 19-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.81 | 01-SEP-15:00 | 914.24 | 20-SEP-01:00 |
October | 2010.79 | 02-OCT-09:09 | 2187.81 | 26-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1205.35 | 31-OCT-21:03 |
November | 2010.79 | 01-NOV-09:09 | 2187.81 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2062.33 | 22-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3013.86 | 16-DEC-05:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 530.56 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 212.25 | 3528.22 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1409.91 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2067.76 | 04-JAN-06:00 |
February | 1239.33 | 01-FEB-08:09 | 1409.91 | 02-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2361.84 | 12-FEB-22:53 |
March | 1239.33 | 01-MAR-08:09 | 1228.64 | 03-MAR-16:49 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1249.37 | 15-MAR-04:51 |
April | 1239.33 | 03-APR-07:10 | 735.93 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 135.57 | 23-APR-16:00 | 1069.25 | 16-APR-11:50 |
May | 1239.33 | 01-MAY-07:10 | 670.83 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.92 | 24-MAY-15:00 | 599.17 | 14-MAY-08:10 |
June | 1239.33 | 01-JUN-07:10 | 735.93 | 09-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.63 | 24-JUN-17:10 | 370.54 | 18-JUN-07:00 |
July | 1239.33 | 03-JUL-07:10 | 670.83 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.53 | 23-JUL-15:00 | 346.26 | 09-JUL-09:55 |
August | 1239.33 | 01-AUG-07:10 | 982.28 | 31-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.37 | 08-AUG-16:00 | 472.83 | 27-AUG-06:00 |
September | 1239.33 | 01-SEP-07:10 | 982.28 | 19-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.54 | 01-SEP-15:00 | 594.75 | 20-SEP-01:00 |
October | 1239.33 | 02-OCT-07:10 | 1409.91 | 30-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 803.30 | 31-OCT-21:03 |
November | 1239.33 | 01-NOV-07:10 | 1409.91 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1358.28 | 22-NOV-02:00 |
December | 1239.33 | 01-DEC-08:09 | 1409.91 | 01-DEC-16:19 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2018.25 | 16-DEC-05:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 346.26 | |||||
Maximum of Months | 1239.33 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 154.53 | 2361.84 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2187.86 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 3101.60 | 04-JAN-05:57 |
February | 2010.83 | 01-FEB-10:09 | 1906.57 | 02-FEB-16:49 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3533.63 | 12-FEB-22:53 |
March | 2010.83 | 01-MAR-10:09 | 1906.57 | 03-MAR-16:00 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1877.55 | 15-MAR-04:51 |
April | 2010.83 | 03-APR-09:09 | 1141.99 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.15 | 23-APR-16:14 | 1775.51 | 16-APR-12:30 |
May | 2010.83 | 01-MAY-09:09 | 1040.98 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.38 | 24-MAY-15:00 | 803.61 | 29-MAY-18:00 |
June | 2010.83 | 01-JUN-09:09 | 1141.99 | 09-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 133.04 | 24-JUN-17:10 | 529.89 | 20-JUN-04:00 |
July | 2010.83 | 03-JUL-09:09 | 1040.98 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.26 | 23-JUL-15:00 | 539.92 | 06-JUL-22:00 |
August | 2010.83 | 01-AUG-09:09 | 1524.28 | 31-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.05 | 08-AUG-16:00 | 725.98 | 27-AUG-05:53 |
September | 2010.83 | 01-SEP-09:09 | 1524.28 | 19-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.63 | 01-SEP-15:00 | 912.50 | 20-SEP-01:00 |
October | 2010.83 | 02-OCT-09:09 | 2187.86 | 26-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1207.18 | 31-OCT-21:03 |
November | 2010.83 | 01-NOV-09:09 | 2187.86 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2058.55 | 22-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 2187.86 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3030.96 | 16-DEC-05:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 529.89 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 184.26 | 3533.63 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2067.76 | 04-JAN-06:00 |
February | 1295.83 | 01-FEB-10:09 | 1228.64 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2355.18 | 12-FEB-22:53 |
March | 1295.83 | 01-MAR-10:09 | 1228.64 | 13-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1251.03 | 15-MAR-04:51 |
April | 1295.83 | 03-APR-09:09 | 801.02 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1026.95 | 01-APR-19:00 |
May | 1295.83 | 01-MAY-09:09 | 735.93 | 12-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.92 | 24-MAY-15:00 | 543.47 | 29-MAY-18:00 |
June | 1295.83 | 01-JUN-09:09 | 801.02 | 30-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.36 | 29-JUN-16:00 | 363.67 | 20-JUN-04:00 |
July | 1295.83 | 03-JUL-09:09 | 735.93 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 135.98 | 23-JUL-14:43 | 432.56 | 16-JUL-17:00 |
August | 1295.83 | 01-AUG-09:09 | 982.28 | 28-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.37 | 08-AUG-16:00 | 507.17 | 27-AUG-05:53 |
September | 1295.83 | 01-SEP-09:09 | 982.28 | 12-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.54 | 01-SEP-15:00 | 604.50 | 20-SEP-01:00 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 26-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 804.63 | 31-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1382.75 | 22-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2021.79 | 16-DEC-05:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 735.93 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 363.67 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 135.98 | 2355.18 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2187.81 | 02-JAN-08:09 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 3654.94 | 04-JAN-06:00 |
February | 2010.79 | 01-FEB-10:09 | 1906.53 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4331.97 | 12-FEB-22:52 |
March | 2010.79 | 01-MAR-10:09 | 1906.53 | 03-MAR-16:49 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2298.03 | 15-MAR-05:00 |
April | 2010.79 | 03-APR-09:09 | 1242.97 | 03-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.97 | 23-APR-16:00 | 1724.15 | 01-APR-18:00 |
May | 2010.79 | 01-MAY-09:09 | 1040.96 | 01-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.04 | 24-MAY-15:00 | 980.50 | 29-MAY-18:00 |
June | 2010.79 | 01-JUN-09:09 | 1141.96 | 09-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.54 | 29-JUN-16:00 | 637.23 | 20-JUN-04:00 |
July | 2010.79 | 03-JUL-09:09 | 1040.96 | 03-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 244.13 | 23-JUL-15:00 | 652.44 | 06-JUL-22:00 |
August | 2010.79 | 01-AUG-09:09 | 1524.25 | 31-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.39 | 08-AUG-16:00 | 834.31 | 27-AUG-05:53 |
September | 2010.79 | 01-SEP-09:09 | 1524.25 | 19-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.04 | 01-SEP-15:00 | 1069.61 | 20-SEP-01:00 |
October | 2010.79 | 02-OCT-09:09 | 2187.81 | 26-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1491.81 | 31-OCT-21:03 |
November | 2010.79 | 01-NOV-09:09 | 2187.81 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2356.21 | 22-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 01-DEC-08:09 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3667.33 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 637.23 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 258.97 | 4331.97 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-08:09 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2573.23 | 04-JAN-06:00 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 02-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2887.47 | 12-FEB-22:52 |
March | 1295.83 | 01-MAR-10:09 | 1228.64 | 03-MAR-16:49 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1568.51 | 15-MAR-05:00 |
April | 1295.83 | 03-APR-09:09 | 735.93 | 03-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.96 | 23-APR-16:00 | 1298.10 | 16-APR-11:52 |
May | 1295.83 | 01-MAY-09:09 | 670.83 | 01-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.03 | 24-MAY-15:00 | 709.81 | 14-MAY-08:00 |
June | 1295.83 | 01-JUN-09:09 | 735.93 | 09-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.49 | 24-JUN-17:10 | 453.27 | 18-JUN-07:10 |
July | 1295.83 | 03-JUL-09:09 | 670.83 | 03-JUL-07:10 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 178.14 | 23-JUL-15:00 | 427.57 | 06-JUL-22:00 |
August | 1295.83 | 01-AUG-09:09 | 982.28 | 31-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.59 | 08-AUG-16:00 | 568.47 | 27-AUG-06:00 |
September | 1295.83 | 01-SEP-09:09 | 982.28 | 19-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.03 | 01-SEP-15:00 | 696.66 | 20-SEP-01:00 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 30-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 994.66 | 31-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1559.96 | 21-NOV-22:03 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-16:19 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2545.97 | 16-DEC-05:59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.57 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 196.96 | 2887.47 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2187.86 | 02-JAN-08:09 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 3859.84 | 04-JAN-05:54 |
February | 2010.83 | 01-FEB-10:09 | 1906.57 | 02-FEB-16:49 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4340.02 | 12-FEB-22:52 |
March | 2010.83 | 01-MAR-10:09 | 1906.57 | 03-MAR-16:00 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2352.78 | 15-MAR-04:59 |
April | 2010.83 | 03-APR-09:09 | 1141.99 | 03-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.32 | 23-APR-16:34 | 2131.65 | 16-APR-12:00 |
May | 2010.83 | 01-MAY-09:09 | 1040.98 | 01-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.04 | 24-MAY-15:00 | 992.58 | 29-MAY-18:00 |
June | 2010.83 | 01-JUN-09:09 | 1141.99 | 09-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.20 | 24-JUN-17:10 | 632.62 | 20-JUN-04:00 |
July | 2010.83 | 03-JUL-09:09 | 1040.98 | 03-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 220.96 | 23-JUL-15:00 | 664.13 | 06-JUL-22:00 |
August | 2010.83 | 01-AUG-09:09 | 1524.28 | 31-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.38 | 08-AUG-16:00 | 874.09 | 27-AUG-05:53 |
September | 2010.83 | 01-SEP-09:09 | 1524.28 | 19-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.92 | 01-SEP-15:00 | 1067.36 | 20-SEP-01:00 |
October | 2010.83 | 02-OCT-09:09 | 2187.86 | 26-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1494.01 | 31-OCT-21:03 |
November | 2010.83 | 01-NOV-09:09 | 2187.86 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2354.91 | 22-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 2187.86 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3818.94 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 632.62 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 220.96 | 4340.02 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-08:09 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2573.22 | 04-JAN-05:56 |
February | 1295.83 | 01-FEB-10:09 | 1228.64 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2897.55 | 12-FEB-22:52 |
March | 1295.83 | 01-MAR-10:09 | 1228.64 | 13-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1568.51 | 15-MAR-04:57 |
April | 1295.83 | 03-APR-09:09 | 801.02 | 03-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1200.48 | 01-APR-19:00 |
May | 1295.83 | 01-MAY-09:09 | 735.93 | 12-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.03 | 24-MAY-15:00 | 670.73 | 29-MAY-18:00 |
June | 1295.83 | 01-JUN-09:09 | 801.02 | 30-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.70 | 29-JUN-16:00 | 435.63 | 20-JUN-04:00 |
July | 1295.83 | 03-JUL-09:09 | 735.93 | 03-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.03 | 23-JUL-14:45 | 551.53 | 16-JUL-17:00 |
August | 1295.83 | 01-AUG-09:09 | 982.28 | 28-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.59 | 08-AUG-16:00 | 611.37 | 27-AUG-05:53 |
September | 1295.83 | 01-SEP-09:09 | 982.28 | 12-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.02 | 01-SEP-15:00 | 709.80 | 20-SEP-01:00 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 26-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 997.18 | 31-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1603.92 | 22-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-08:09 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2545.95 | 16-DEC-05:56 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 735.93 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 435.63 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 172.03 | 2897.55 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 5470.56 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 5470.56 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 5470.56 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 5470.56 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 5470.56 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 5470.56 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 5470.56 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 5470.56 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 5470.56 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 5470.56 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 5470.56 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 5470.56 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 5470.56 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2677.82 | 04-JAN-05:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3601.89 | 12-FEB-22:52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1705.62 | 15-MAR-04:51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.94 | 23-APR-16:00 | 1563.55 | 01-APR-19:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.88 | 24-MAY-15:00 | 772.80 | 09-MAY-03:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.42 | 24-JUN-17:01 | 537.18 | 10-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.59 | 23-JUL-15:00 | 493.08 | 06-JUL-22:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.89 | 08-AUG-16:00 | 709.72 | 27-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.44 | 01-SEP-15:00 | 925.49 | 20-SEP-00:35 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1171.67 | 31-OCT-21:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2239.66 | 22-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2761.73 | 16-DEC-05:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 493.08 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.59 | 3601.89 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 4610.65 | 04-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6029.18 | 12-FEB-22:52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2952.98 | 15-MAR-04:51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.67 | 23-APR-16:00 | 2602.25 | 01-APR-19:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.42 | 24-MAY-15:00 | 1312.93 | 08-MAY-24:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.13 | 24-JUN-17:01 | 880.64 | 20-JUN-04:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.70 | 23-JUL-15:00 | 836.14 | 06-JUL-22:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.15 | 08-AUG-16:00 | 1173.87 | 27-AUG-05:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.60 | 01-SEP-15:00 | 1561.65 | 20-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1966.26 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3639.31 | 22-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4695.75 | 16-DEC-05:51 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 836.14 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 365.70 | 6029.18 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 5282.32 | 04-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6257.60 | 12-FEB-22:52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3241.60 | 15-MAR-05:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.89 | 23-APR-16:00 | 2708.74 | 01-APR-19:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.32 | 24-MAY-15:00 | 1461.94 | 29-MAY-18:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.93 | 29-JUN-16:00 | 959.51 | 20-JUN-04:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.82 | 15-JUL-17:03 | 911.32 | 06-JUL-22:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.92 | 08-AUG-16:00 | 1301.97 | 27-AUG-05:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.14 | 01-SEP-16:00 | 1670.33 | 20-SEP-01:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2180.17 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3758.77 | 22-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5166.53 | 16-DEC-06:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 911.32 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.82 | 6257.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 106867.81 | 30-JAN-08:51 | 119382.48 | 135814.60 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 119883.18 | 09-FEB-09:21 | 170546.39 | 194020.86 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 123116.21 | 23-MAR-06:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 01-APR-00:10 | 0.00 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 01-MAY-00:03 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 01-JUN-00:10 | 0.00 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 01-JUL-00:03 | 0.00 | 2393.40 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 01-AUG-00:03 | 0.00 | 1795.05 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 01-SEP-00:03 | 0.00 | 2393.40 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 01-OCT-00:10 | 0.00 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 134255.73 | 25-NOV-07:11 | 17952.25 | 21558.68 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 127940.07 | 08-DEC-07:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 0.00 | 0.00 | 598.35 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 134255.73 | 170546.39 | 194020.86 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 79829.25 | 20-JAN-06:01 | 12897.91 | 4298.88 | 61179.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 84596.08 | 22-FEB-05:01 | 0.00 | 4298.88 | 47501.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 93468.81 | 30-MAR-03:02 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 97675.22 | 08-APR-04:12 | 0.00 | 3224.16 | 26719.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 98464.24 | 16-MAY-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 98313.76 | 23-JUN-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 98376.54 | 20-JUL-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 98384.02 | 23-AUG-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 98786.27 | 29-SEP-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 98734.05 | 19-OCT-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 98259.38 | 20-NOV-05:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 88385.48 | 08-DEC-04:01 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 79829.25 | 0.00 | 2686.80 | 26719.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 98786.27 | 12897.91 | 4298.88 | 61179.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 30923.30 | 17-JAN-16:20 | 30632.53 | 34848.87 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 40248.24 | 10-FEB-14:48 | 96087.48 | 104546.62 | 103239.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 60855.52 | 30-MAR-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 77543.39 | 14-APR-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 86211.64 | 30-MAY-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 82567.97 | 27-JUN-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 82855.19 | 26-JUL-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 82360.47 | 01-AUG-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 81102.00 | 01-SEP-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 75795.77 | 20-OCT-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 29394.36 | 17-NOV-16:30 | 30632.53 | 34848.87 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 22156.21 | 22-DEC-16:20 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 22156.21 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 86211.64 | 96087.48 | 104546.62 | 103239.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16908.42 | 20-JAN-16:50 | 30632.53 | 34848.87 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 20093.97 | 28-FEB-14:10 | 32029.16 | 34848.87 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 26759.44 | 29-MAR-16:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 38728.12 | 13-APR-16:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 79913.39 | 26-MAY-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 79752.19 | 26-JUN-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 80630.86 | 05-JUL-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 80713.69 | 09-AUG-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 75052.72 | 02-SEP-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 36678.75 | 20-OCT-16:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 20047.19 | 17-NOV-17:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16915.17 | 28-DEC-17:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 16908.42 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 80713.69 | 32029.16 | 34848.87 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2415.56 | 20-JAN-06:02 | 1619.46 | 539.77 | 7681.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.76 |
February | 2718.90 | 22-FEB-13:20 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.14 |
March | 6180.17 | 28-MAR-14:00 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.32 |
April | 16226.57 | 23-APR-17:41 | 0.00 | 578.27 | 5591.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.34 |
May | 14612.55 | 26-MAY-04:12 | 0.00 | 337.35 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.18 |
June | 16906.23 | 25-JUN-18:22 | 0.00 | 346.96 | 3355.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.11 |
July | 18703.45 | 23-JUL-15:12 | 1012.16 | 578.27 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 54.37 | 0.00 |
August | 17120.27 | 13-AUG-14:02 | 910.95 | 520.44 | 6481.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.66 |
September | 14275.69 | 01-SEP-04:12 | 0.00 | 337.35 | 3727.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.80 |
October | 8461.09 | 02-OCT-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.71 |
November | 7057.57 | 01-NOV-13:30 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.13 |
December | 2651.87 | 06-DEC-06:03 | 1417.03 | 472.30 | 6721.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2415.56 | 0.00 | 269.88 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18703.45 | 2010.79 | 1040.96 | 7681.96 | 0.00 | 0.00 | 0.00 | 0.00 | 54.37 | 171.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3034.53 | 20-JAN-06:02 | 1043.64 | 347.85 | 4950.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.67 |
February | 6788.82 | 27-FEB-09:35 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.50 |
March | 12664.93 | 31-MAR-09:05 | 2591.66 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.22 |
April | 26271.87 | 30-APR-08:22 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.98 |
May | 26917.33 | 14-MAY-08:22 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.27 |
June | 28101.62 | 25-JUN-07:41 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.43 |
July | 30010.32 | 23-JUL-09:12 | 587.05 | 335.39 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.80 |
August | 28505.21 | 06-AUG-08:41 | 587.05 | 335.39 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.80 |
September | 26945.99 | 10-SEP-07:42 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.84 |
October | 21531.24 | 09-OCT-08:52 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 8019.47 | 16-NOV-09:25 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.61 |
December | 3126.85 | 01-DEC-10:25 | 2591.66 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3034.53 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 30010.32 | 2591.66 | 1341.67 | 4950.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18716.89 | 27-JAN-13:25 | 3846.30 | 2081.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 31409.23 | 19-FEB-13:12 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 939.91 |
March | 34092.69 | 19-MAR-12:31 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.68 |
April | 36057.21 | 23-APR-13:41 | 910.97 | 520.45 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.25 |
May | 30799.25 | 21-MAY-12:42 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.29 |
June | 31097.47 | 18-JUN-12:32 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.67 |
July | 36218.73 | 23-JUL-12:32 | 910.97 | 520.45 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 12.86 | 0.00 |
August | 36880.84 | 13-AUG-12:42 | 910.97 | 520.45 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.71 |
September | 34321.02 | 10-SEP-11:01 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.50 |
October | 35038.36 | 22-OCT-12:51 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.32 |
November | 23956.84 | 17-NOV-12:00 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.07 |
December | 15998.20 | 20-DEC-13:05 | 3846.30 | 2081.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15998.20 | 506.09 | 289.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36880.84 | 3846.30 | 2081.97 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 12.86 | 939.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5499.00 | 20-JAN-15:50 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.88 |
February | 10935.08 | 28-FEB-15:40 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.53 |
March | 31987.39 | 19-MAR-15:11 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.33 |
April | 38053.73 | 23-APR-16:21 | 652.28 | 372.66 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.52 |
May | 32997.08 | 14-MAY-17:01 | 0.00 | 260.86 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.13 |
June | 32397.52 | 17-JUN-17:41 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.20 |
July | 36565.41 | 23-JUL-16:32 | 652.28 | 372.66 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 |
August | 32801.53 | 05-AUG-17:41 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.40 |
September | 32087.49 | 03-SEP-15:51 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.64 |
October | 26226.98 | 22-OCT-15:32 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.43 |
November | 9865.05 | 09-NOV-15:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.51 |
December | 5546.23 | 20-DEC-15:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5499.00 | 0.00 | 223.59 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | |
Maximum of Months | 38053.73 | 1239.33 | 670.83 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1434.16 | 28-JAN-17:02 | 607.30 | 729.22 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.27 |
February | 2023.83 | 08-FEB-13:50 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.77 |
March | 2808.52 | 31-MAR-14:00 | 4021.58 | 2081.92 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.92 |
April | 5074.92 | 18-APR-14:00 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.27 |
May | 11879.10 | 26-MAY-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.01 |
June | 15377.46 | 25-JUN-11:21 | 708.51 | 404.79 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 9.27 | 0.00 |
July | 15220.00 | 04-JUL-15:41 | 1012.16 | 578.27 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.85 |
August | 9018.02 | 09-AUG-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.03 |
September | 7328.14 | 01-SEP-15:20 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 12.22 | 0.00 |
October | 3286.14 | 20-OCT-15:00 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.36 |
November | 2252.45 | 01-NOV-15:30 | 1923.11 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.60 |
December | 1444.57 | 30-DEC-17:02 | 506.08 | 607.68 | 3600.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1434.16 | 506.08 | 269.88 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15377.46 | 4021.58 | 2081.92 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 12.22 | 348.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2282.31 | 25-JAN-10:00 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.38 |
February | 3490.31 | 28-FEB-09:55 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.22 |
March | 11044.91 | 17-MAR-08:58 | 4957.30 | 2683.34 | 5569.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.04 |
April | 19335.82 | 16-APR-09:51 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 839.48 |
May | 31650.64 | 21-MAY-09:11 | 587.05 | 335.39 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.24 |
June | 33616.93 | 25-JUN-08:41 | 652.28 | 372.66 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.05 |
July | 29132.75 | 23-JUL-10:01 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.12 |
August | 32914.56 | 20-AUG-09:01 | 652.28 | 372.66 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.89 |
September | 27535.52 | 04-SEP-10:22 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 423.08 |
October | 12984.49 | 22-OCT-09:32 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.13 |
November | 4153.97 | 09-NOV-10:00 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.33 |
December | 2313.22 | 01-DEC-10:00 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2282.31 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.12 | |
Maximum of Months | 33616.93 | 4957.30 | 2683.34 | 5569.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 839.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19869.19 | 27-JAN-13:35 | 3846.30 | 2081.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 27489.83 | 10-FEB-14:48 | 12065.01 | 6245.90 | 12963.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.53 |
March | 36433.92 | 26-MAR-12:41 | 809.75 | 462.62 | 5761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 977.46 |
April | 38026.61 | 23-APR-13:31 | 910.97 | 520.45 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 452.98 |
May | 34394.52 | 21-MAY-13:11 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.00 |
June | 34276.93 | 18-JUN-13:01 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.94 |
July | 33234.55 | 23-JUL-13:22 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 72.11 | 0.00 |
August | 37290.48 | 13-AUG-13:11 | 910.97 | 520.45 | 6481.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.67 |
September | 39484.13 | 04-SEP-13:01 | 1012.19 | 578.28 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 687.71 |
October | 36444.75 | 22-OCT-12:51 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.21 |
November | 23743.33 | 29-NOV-12:13 | 4233.34 | 4163.93 | 7682.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.07 |
December | 15075.43 | 02-DEC-13:20 | 202.44 | 173.50 | 840.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.47 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 15075.43 | 202.44 | 173.50 | 840.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39484.13 | 12065.01 | 6245.90 | 12963.51 | 0.00 | 0.00 | 0.00 | 0.00 | 72.11 | 977.46 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5480.65 | 17-JAN-16:20 | 2478.65 | 1341.67 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.81 |
February | 7427.00 | 27-FEB-16:40 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.16 |
March | 29079.52 | 26-MAR-17:21 | 0.00 | 335.39 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 437.66 |
April | 36032.01 | 23-APR-16:51 | 652.28 | 372.66 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.56 |
May | 35787.39 | 14-MAY-17:31 | 0.00 | 372.66 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.60 |
June | 30946.85 | 17-JUN-17:41 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.29 |
July | 33808.87 | 04-JUL-16:21 | 652.28 | 372.66 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.88 |
August | 30697.50 | 05-AUG-17:41 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.10 |
September | 30638.54 | 03-SEP-16:51 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.57 |
October | 16169.24 | 22-OCT-15:32 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.15 |
November | 4937.72 | 09-NOV-15:40 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.13 |
December | 2665.30 | 20-DEC-15:40 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2665.30 | 0.00 | 223.59 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.29 | |
Maximum of Months | 36032.01 | 2478.65 | 1341.67 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 437.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1494.63 | 28-JAN-17:02 | 607.30 | 729.22 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 432.28 |
February | 1758.73 | 08-FEB-14:00 | 3846.22 | 2081.92 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.32 |
March | 2478.50 | 31-MAR-14:00 | 4021.58 | 2081.92 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.32 |
April | 4958.44 | 18-APR-15:10 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.58 |
May | 11414.36 | 26-MAY-05:02 | 1012.16 | 337.35 | 4801.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.12 |
June | 17928.97 | 25-JUN-11:31 | 708.51 | 404.79 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.73 |
July | 17658.70 | 04-JUL-16:21 | 1012.16 | 578.27 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.73 |
August | 9565.10 | 09-AUG-15:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 20.90 | 0.00 |
September | 7896.36 | 01-SEP-15:20 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 14.34 | 0.00 |
October | 3168.79 | 20-OCT-13:10 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.81 |
November | 2193.08 | 01-NOV-16:00 | 1923.11 | 1242.97 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.51 |
December | 1662.00 | 06-DEC-06:06 | 1417.03 | 472.30 | 6721.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.77 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1494.63 | 607.30 | 337.35 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17928.97 | 4021.58 | 2081.92 | 7201.84 | 0.00 | 0.00 | 0.00 | 0.00 | 20.90 | 432.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2224.27 | 20-JAN-06:04 | 1043.64 | 347.85 | 4950.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.61 |
February | 2902.68 | 28-FEB-10:30 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.86 |
March | 7070.25 | 31-MAR-09:50 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.26 |
April | 14026.39 | 19-APR-09:05 | 2591.66 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 390.22 |
May | 28265.55 | 21-MAY-09:01 | 587.05 | 335.39 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.88 |
June | 33541.82 | 25-JUN-08:11 | 652.28 | 372.66 | 4641.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.77 |
July | 29293.47 | 23-JUL-10:01 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.92 |
August | 29027.92 | 20-AUG-09:11 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.43 |
September | 25811.11 | 10-SEP-10:22 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.78 |
October | 8666.25 | 19-OCT-09:30 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.42 |
November | 2854.23 | 16-NOV-10:10 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.92 |
December | 2256.13 | 07-DEC-06:04 | 1043.64 | 347.85 | 4950.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.89 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2224.27 | 391.37 | 223.59 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.92 | |
Maximum of Months | 33541.82 | 2591.66 | 1341.67 | 4950.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 390.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17157.14 | 27-JAN-13:35 | 3846.30 | 2081.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 24607.07 | 28-FEB-13:40 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.88 |
March | 33223.92 | 26-MAR-14:22 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 748.51 |
April | 35082.69 | 23-APR-13:52 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.49 |
May | 34816.65 | 21-MAY-13:42 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.87 |
June | 35884.25 | 25-JUN-11:31 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.67 |
July | 34919.49 | 23-JUL-13:22 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 80.51 | 0.00 |
August | 35187.77 | 13-AUG-13:32 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.77 |
September | 40759.45 | 04-SEP-12:31 | 1012.19 | 578.28 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 876.98 |
October | 37483.19 | 22-OCT-13:31 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 340.28 |
November | 20366.50 | 17-NOV-13:10 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.71 |
December | 12362.60 | 20-DEC-13:25 | 3846.30 | 2081.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 407.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12362.60 | 506.09 | 289.14 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40759.45 | 3846.30 | 2081.97 | 7201.95 | 0.00 | 0.00 | 0.00 | 0.00 | 80.51 | 876.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3093.54 | 27-JAN-16:00 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6833.38 | 08-FEB-16:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.61 |
March | 13303.06 | 26-MAR-17:03 | 0.00 | 149.06 | 1441.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.76 |
April | 33113.89 | 23-APR-16:31 | 521.82 | 298.13 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.18 |
May | 36703.98 | 14-MAY-17:21 | 0.00 | 372.66 | 3603.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 395.36 |
June | 32131.83 | 17-JUN-17:41 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.85 |
July | 35252.60 | 04-JUL-16:21 | 652.28 | 372.66 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.91 |
August | 31849.45 | 05-AUG-17:41 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.21 |
September | 31603.13 | 03-SEP-17:11 | 0.00 | 260.86 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.99 |
October | 11528.07 | 22-OCT-16:12 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.92 |
November | 4105.99 | 09-NOV-15:40 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.36 |
December | 2504.20 | 20-DEC-15:40 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.65 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2504.20 | 0.00 | 149.06 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36703.98 | 1239.33 | 670.83 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10710.44 | 09-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 905.91 |
February | 9986.08 | 13-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2022.97 |
March | 6793.53 | 15-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 417.54 |
April | 10746.66 | 24-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.94 |
May | 12168.87 | 26-MAY-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.17 |
June | 14093.74 | 26-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.05 |
July | 17601.93 | 24-JUL-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.89 |
August | 14965.41 | 14-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.61 |
September | 12380.26 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.18 |
October | 11094.42 | 23-OCT-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.98 |
November | 7811.12 | 20-NOV-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.02 |
December | 6857.46 | 26-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 905.76 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6793.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.17 | |
Maximum of Months | 17601.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2022.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13239.19 | 28-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1665.29 |
February | 14391.02 | 25-FEB-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11228.07 | 06-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2156.75 |
April | 8523.13 | 04-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1788.96 |
May | 7499.74 | 19-MAY-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 |
June | 7938.72 | 30-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.51 | 0.00 |
July | 8646.91 | 05-JUL-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.33 |
August | 7459.68 | 01-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.59 |
September | 6548.85 | 01-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.45 | 0.00 |
October | 11031.32 | 30-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 603.85 |
November | 13473.79 | 24-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 823.46 |
December | 14396.76 | 02-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1752.42 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 6548.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14396.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.51 | 2156.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1749.33 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3059.53 |
March | 3088.40 | 26-MAR-14:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 780.98 |
April | 10250.46 | 13-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.17 |
May | 17840.50 | 18-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.27 | 0.00 |
June | 20108.72 | 30-JUN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.28 | 0.00 |
July | 18769.84 | 24-JUL-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.28 | 0.00 |
August | 17187.07 | 08-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.88 | 0.00 |
September | 14592.35 | 01-SEP-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.14 | 0.00 |
October | 6703.00 | 20-OCT-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.11 |
November | 1785.13 | 01-NOV-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.48 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1920.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20108.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.28 | 3059.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2268.25 | 25-JAN-16:30 | 222.14 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4732.57 | 27-FEB-17:00 | 444.28 | 900.23 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7204.85 | 31-MAR-24:00 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8823.40 | 21-APR-18:10 | 23.38 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3453.34 | 31-MAY-24:00 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5494.56 | 30-JUN-24:00 | 0.00 | 50.02 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7382.03 | 31-JUL-23:54 | 0.00 | 125.04 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8912.97 | 13-AUG-18:33 | 0.00 | 225.07 | 70149.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3543.55 | 30-SEP-24:00 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5122.04 | 31-OCT-24:00 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6319.22 | 09-NOV-16:10 | 222.14 | 450.11 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7856.92 | 20-DEC-16:00 | 222.14 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2268.25 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8912.97 | 444.28 | 900.23 | 70149.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1813.11 | 27-JAN-16:30 | 222.14 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4119.03 | 27-FEB-17:00 | 444.28 | 900.23 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6405.78 | 31-MAR-23:30 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8422.88 | 21-APR-18:20 | 23.38 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2972.06 | 14-MAY-18:43 | 0.00 | 225.07 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5222.31 | 30-JUN-24:00 | 0.00 | 50.02 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6924.27 | 31-JUL-23:54 | 0.00 | 125.04 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8251.62 | 02-AUG-18:40 | 23.38 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3016.51 | 03-SEP-17:41 | 0.00 | 225.07 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4242.44 | 18-OCT-16:50 | 70.15 | 250.06 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5651.60 | 09-NOV-16:20 | 222.14 | 450.11 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6944.20 | 20-DEC-16:10 | 444.28 | 900.23 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1813.11 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8422.88 | 444.28 | 900.23 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1510.19 | 25-JAN-16:30 | 222.14 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3969.14 | 27-FEB-17:00 | 444.28 | 900.23 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6218.85 | 28-MAR-17:50 | 23.38 | 150.04 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8404.38 | 21-APR-18:20 | 23.38 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2869.44 | 14-MAY-18:47 | 0.00 | 225.07 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5247.03 | 30-JUN-23:40 | 0.00 | 75.02 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6842.51 | 31-JUL-23:54 | 0.00 | 125.04 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8285.61 | 02-AUG-18:40 | 23.38 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2989.47 | 05-SEP-17:50 | 23.38 | 150.04 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4207.17 | 18-OCT-16:50 | 70.15 | 250.06 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5491.79 | 09-NOV-16:20 | 222.14 | 450.11 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6673.19 | 20-DEC-16:10 | 444.28 | 900.23 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1510.19 | 0.00 | 75.02 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8404.38 | 444.28 | 900.23 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 91202.48 | 20-JAN-17:00 | 9617.36 | 10941.12 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 183616.32 | 22-FEB-17:00 | 4808.68 | 5470.56 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 360426.56 | 31-MAR-24:00 | 0.00 | 303.90 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 369545.00 | 19-APR-16:00 | 4808.68 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176934.20 | 31-MAY-24:00 | 0.00 | 303.90 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 270114.23 | 30-JUN-23:55 | 0.00 | 607.79 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 362144.94 | 31-JUL-23:52 | 0.00 | 1519.49 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 379183.15 | 08-AUG-21:02 | 1518.53 | 3647.17 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 177804.92 | 30-SEP-24:00 | 0.00 | 303.90 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 269042.50 | 31-OCT-24:00 | 0.00 | 303.90 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 278122.79 | 17-NOV-17:00 | 4808.68 | 5470.56 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 368089.63 | 07-DEC-17:00 | 4808.68 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 91202.48 | 0.00 | 303.90 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 379183.15 | 9617.36 | 10941.12 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.169106E+13 | 1243107.13 | 09-JAN-16:00 | 0.101812E+13 | 2677693.85 | 09-JAN-07:30 |
February | 0.192525E+13 | 1356618.01 | 27-FEB-16:00 | 0.473155E+12 | 2017719.83 | 14-FEB-07:10 |
March | 0.254402E+13 | 1513005.66 | 31-MAR-15:39 | 0.256189E+12 | 1549301.13 | 06-MAR-07:10 |
April | 0.275060E+13 | 1888875.06 | 13-APR-15:09 | 0.502977E+11 | 622219.92 | 03-APR-06:10 |
May | 0.183518E+13 | 1627647.54 | 25-MAY-15:20 | 0.215381E+10 | 231393.80 | 02-MAY-06:10 |
June | 0.225766E+13 | 1854299.19 | 30-JUN-15:00 | 14367300.42 | 2299.28 | 10-JUN-05:40 |
July | 0.273122E+13 | 2254867.53 | 05-JUL-10:00 | 2645.49 | 4.41 | 17-JUL-19:00 |
August | 0.307607E+13 | 2178594.02 | 08-AUG-10:09 | 79456557.15 | 14236.20 | 19-AUG-05:10 |
September | 0.161730E+13 | 1595573.78 | 01-SEP-15:00 | 0.312711E+10 | 146701.82 | 23-SEP-06:10 |
October | 0.206075E+13 | 1515826.25 | 20-OCT-15:20 | 0.579657E+11 | 876219.57 | 30-OCT-06:10 |
November | 0.239978E+13 | 1529128.24 | 17-NOV-16:30 | 0.237918E+12 | 1343491.72 | 25-NOV-07:10 |
December | 0.281706E+13 | 1667351.60 | 18-DEC-16:00 | 0.802791E+12 | 2466755.16 | 26-DEC-07:19 |
Annual Sum or Average | 0.277060E+14 | 0.290181E+13 | ||||
Minimum of Months | 0.161730E+13 | 1243107.13 | 2645.49 | 4.41 | ||
Maximum of Months | 0.307607E+13 | 2254867.53 | 0.101812E+13 | 2677693.85 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.275516E+12 | 0.447385E+11 | 0.766053E+12 | 0.213345E+12 | 0.192022E+12 | 0.130799E+11 | 0.00 | 0.606242E+10 | 0.216567E+09 | 0.125144E+12 | 0.818609E+10 | 0.466932E+11 | 0.00 |
February | 0.245323E+12 | 0.346593E+11 | 0.978954E+12 | 0.195333E+12 | 0.174175E+12 | 0.127239E+11 | 0.00 | 0.224797E+11 | 0.100281E+10 | 0.210472E+12 | 0.676083E+10 | 0.433668E+11 | 0.00 |
March | 0.289431E+12 | 0.308329E+11 | 0.141687E+13 | 0.226058E+12 | 0.196343E+12 | 0.134619E+11 | 0.00 | 0.432846E+11 | 0.231435E+10 | 0.267711E+12 | 0.692359E+10 | 0.507856E+11 | 0.00 |
April | 0.255726E+12 | 0.230118E+11 | 0.165903E+13 | 0.211501E+12 | 0.199975E+12 | 0.156478E+11 | 0.00 | 0.735995E+11 | 0.125759E+11 | 0.252187E+12 | 0.268062E+10 | 0.446730E+11 | 0.00 |
May | 0.274816E+12 | 0.190482E+11 | 0.774844E+12 | 0.219699E+12 | 0.241344E+12 | 0.326727E+11 | 0.00 | 0.799383E+11 | 0.424873E+11 | 0.103788E+12 | 0.117284E+10 | 0.453652E+11 | 0.00 |
June | 0.273378E+12 | 0.164183E+11 | 0.106252E+13 | 0.217934E+12 | 0.260958E+12 | 0.476412E+11 | 0.00 | 0.200979E+12 | 0.887045E+11 | 0.455499E+11 | 0.123047E+10 | 0.423454E+11 | 0.00 |
July | 0.255237E+12 | 0.177170E+11 | 0.139340E+13 | 0.213265E+12 | 0.278799E+12 | 0.583601E+11 | 0.00 | 0.349193E+12 | 0.124061E+12 | 0.772453E+09 | 0.218589E+10 | 0.382270E+11 | 0.00 |
August | 0.286615E+12 | 0.213137E+11 | 0.173200E+13 | 0.226058E+12 | 0.259683E+12 | 0.542243E+11 | 0.00 | 0.342042E+12 | 0.110728E+12 | 0.161546E+10 | 0.114234E+10 | 0.406504E+11 | 0.00 |
September | 0.256675E+12 | 0.266104E+11 | 0.740713E+12 | 0.211501E+12 | 0.209519E+12 | 0.265093E+11 | 0.00 | 0.429825E+11 | 0.231377E+11 | 0.422008E+11 | 0.368992E+09 | 0.370841E+11 | 0.00 |
October | 0.269628E+12 | 0.351537E+11 | 0.108340E+13 | 0.213343E+12 | 0.189933E+12 | 0.145646E+11 | 0.00 | 0.344057E+11 | 0.645042E+10 | 0.171296E+12 | 0.286961E+10 | 0.397087E+11 | 0.00 |
November | 0.271651E+12 | 0.411500E+11 | 0.135889E+13 | 0.205298E+12 | 0.178302E+12 | 0.121889E+11 | 0.00 | 0.408867E+11 | 0.342709E+10 | 0.241819E+12 | 0.497251E+10 | 0.411979E+11 | 0.00 |
December | 0.267951E+12 | 0.466260E+11 | 0.170972E+13 | 0.213269E+12 | 0.192420E+12 | 0.144000E+11 | 0.00 | 0.516661E+11 | 0.198340E+10 | 0.267840E+12 | 0.767819E+10 | 0.435032E+11 | 0.00 |
Annual Sum or Average | 0.322195E+13 | 0.357280E+12 | 0.146764E+14 | 0.256661E+13 | 0.257347E+13 | 0.315475E+12 | 0.00 | 0.128752E+13 | 0.417090E+12 | 0.173040E+13 | 0.461720E+11 | 0.513600E+12 | 0.00 |
Minimum of Months | 0.245323E+12 | 0.164183E+11 | 0.740713E+12 | 0.195333E+12 | 0.174175E+12 | 0.121889E+11 | 0.00 | 0.606242E+10 | 0.216567E+09 | 0.772453E+09 | 0.368992E+09 | 0.370841E+11 | 0.00 |
Maximum of Months | 0.289431E+12 | 0.466260E+11 | 0.173200E+13 | 0.226058E+12 | 0.278799E+12 | 0.583601E+11 | 0.00 | 0.349193E+12 | 0.124061E+12 | 0.267840E+12 | 0.818609E+10 | 0.507856E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.101812E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.473155E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.256189E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.502977E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.215381E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 14367300.42 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 2645.49 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 79456557.15 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.312711E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.579657E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.237918E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.802791E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.290181E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 2645.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.101812E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 325713.14 | 02-JAN-08:09 | 40855.88 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 233439.18 | 02-JAN-08:20 | 111418.39 | 02-JAN-06:19 | 24819.04 | 23-JAN-07:40 | 0.00 | 01-JAN-00:10 |
February | 316787.15 | 02-FEB-16:00 | 40855.88 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 233429.20 | 15-FEB-08:20 | 172233.81 | 10-FEB-14:00 | 24845.12 | 01-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 311655.64 | 03-MAR-16:00 | 40855.88 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 233431.65 | 13-MAR-07:19 | 166848.53 | 31-MAR-15:39 | 24680.87 | 07-MAR-07:30 | 0.00 | 01-MAR-00:10 |
April | 286531.07 | 03-APR-07:10 | 40855.88 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 233418.23 | 03-APR-07:19 | 212292.13 | 13-APR-15:09 | 25214.65 | 23-APR-15:39 | 0.00 | 01-APR-00:10 |
May | 281231.72 | 12-MAY-07:10 | 27558.46 | 01-MAY-19:30 | 423497.50 | 01-MAY-07:10 | 233415.40 | 12-MAY-07:19 | 280590.72 | 18-MAY-14:39 | 49126.34 | 18-MAY-09:30 | 0.00 | 01-MAY-00:10 |
June | 285420.03 | 30-JUN-07:10 | 27558.46 | 01-JUN-19:00 | 541788.89 | 01-JUN-07:10 | 233417.64 | 30-JUN-07:19 | 265555.73 | 30-JUN-14:30 | 48951.86 | 19-JUN-15:20 | 0.00 | 01-JUN-00:10 |
July | 281231.72 | 03-JUL-07:10 | 27558.46 | 01-JUL-20:19 | 660080.29 | 03-JUL-07:10 | 233415.40 | 03-JUL-07:19 | 315794.86 | 05-JUL-10:50 | 56569.26 | 05-JUL-11:09 | 0.00 | 01-JUL-00:10 |
August | 299524.43 | 31-AUG-07:10 | 40855.88 | 15-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 233425.17 | 31-AUG-07:19 | 295637.81 | 08-AUG-15:20 | 49922.21 | 22-AUG-14:09 | 0.00 | 01-AUG-00:10 |
September | 299524.43 | 19-SEP-07:10 | 40855.88 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 233425.17 | 19-SEP-07:19 | 267301.73 | 01-SEP-15:00 | 48546.74 | 01-SEP-13:09 | 0.00 | 01-SEP-00:10 |
October | 325713.14 | 30-OCT-07:10 | 40855.88 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 233439.18 | 30-OCT-07:19 | 184460.29 | 20-OCT-15:20 | 26882.15 | 19-OCT-14:20 | 0.00 | 01-OCT-00:10 |
November | 325713.14 | 01-NOV-07:10 | 40855.88 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 233439.18 | 01-NOV-07:19 | 128360.91 | 17-NOV-14:09 | 24712.61 | 01-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 325713.14 | 01-DEC-16:19 | 40855.88 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 233439.18 | 04-DEC-08:20 | 108837.14 | 26-DEC-06:10 | 24766.62 | 18-DEC-07:49 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 281231.72 | 27558.46 | 423497.50 | 233415.40 | 108837.14 | 24680.87 | 0.00 | |||||||
Maximum of Months | 325713.14 | 40855.88 | 778371.69 | 233439.18 | 315794.86 | 56569.26 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 8502.96 | 26-JAN-16:19 | 644.27 | 27-JAN-15:00 | 60266.96 | 21-JAN-15:00 | 6524.59 | 02-JAN-07:30 | 62559.55 | 31-JAN-12:30 | 0.00 |
February | 16800.93 | 08-FEB-16:30 | 2449.10 | 07-FEB-21:30 | 100000.00 | 04-FEB-17:19 | 6524.59 | 01-FEB-07:10 | 62801.25 | 24-FEB-12:50 | 0.00 |
March | 22521.96 | 31-MAR-23:30 | 3195.09 | 21-MAR-10:50 | 100000.00 | 01-MAR-04:10 | 6524.59 | 01-MAR-19:19 | 62791.91 | 02-MAR-12:00 | 0.00 |
April | 227515.85 | 23-APR-15:00 | 53042.08 | 23-APR-15:00 | 100000.00 | 01-APR-04:10 | 5613.48 | 01-APR-06:00 | 61789.82 | 04-APR-11:20 | 0.00 |
May | 260482.97 | 25-MAY-16:49 | 88191.61 | 16-MAY-14:09 | 100000.00 | 06-MAY-17:10 | 5613.48 | 01-MAY-06:10 | 59195.07 | 01-MAY-11:00 | 0.00 |
June | 444875.72 | 19-JUN-15:20 | 88191.61 | 06-JUN-12:20 | 100000.00 | 04-JUN-10:20 | 5613.48 | 06-JUN-11:00 | 55917.57 | 01-JUN-11:50 | 0.00 |
July | 595156.51 | 05-JUL-10:20 | 88191.61 | 03-JUL-12:20 | 49079.06 | 07-JUL-17:00 | 5613.48 | 03-JUL-13:50 | 52574.90 | 03-JUL-11:30 | 0.00 |
August | 519192.45 | 31-AUG-12:50 | 88191.61 | 07-AUG-12:00 | 81494.83 | 19-AUG-04:00 | 5613.48 | 08-AUG-10:30 | 50686.81 | 02-AUG-11:30 | 0.00 |
September | 232582.51 | 01-SEP-13:09 | 88191.61 | 01-SEP-09:09 | 100000.00 | 08-SEP-14:30 | 5613.48 | 01-SEP-14:09 | 51391.67 | 29-SEP-11:30 | 0.00 |
October | 141607.05 | 19-OCT-14:20 | 51993.36 | 19-OCT-14:20 | 100000.00 | 08-OCT-11:30 | 5613.48 | 05-OCT-19:49 | 53455.44 | 31-OCT-11:39 | 0.00 |
November | 57639.47 | 01-NOV-14:00 | 49620.83 | 01-NOV-14:00 | 100000.00 | 02-NOV-21:10 | 6524.59 | 25-NOV-07:10 | 56699.63 | 29-NOV-12:20 | 0.00 |
December | 22726.73 | 20-DEC-16:19 | 2187.87 | 05-DEC-16:00 | 100000.00 | 01-DEC-04:30 | 6524.59 | 01-DEC-07:10 | 60163.03 | 29-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 8502.96 | 644.27 | 49079.06 | 5613.48 | 50686.81 | 0.00 | |||||
Maximum of Months | 595156.51 | 88191.61 | 100000.00 | 6524.59 | 62801.25 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1243107.13 | 09-JAN-16:00 | 325713.14 | 423497.50 | 40855.88 | 233326.38 | 88521.41 | 24642.16 | 0.00 | 4229.51 | 116.48 |
February | 1356618.01 | 27-FEB-16:00 | 289271.47 | 541788.89 | 0.00 | 233303.25 | 118503.55 | 3947.01 | 0.00 | 15189.06 | 669.15 |
March | 1513005.66 | 31-MAR-15:39 | 280450.63 | 660080.29 | 0.00 | 233302.19 | 166848.53 | 3931.83 | 0.00 | 18766.52 | 2116.80 |
April | 1888875.06 | 13-APR-15:09 | 280450.63 | 778371.69 | 0.00 | 233302.19 | 212292.13 | 24902.93 | 0.00 | 164034.44 | 49637.32 |
May | 1627647.54 | 25-MAY-15:20 | 280450.63 | 423497.50 | 0.00 | 233302.19 | 263942.43 | 47241.35 | 0.00 | 241488.92 | 88191.61 |
June | 1854299.19 | 30-JUN-15:00 | 280450.63 | 541788.89 | 0.00 | 233302.19 | 263674.22 | 48316.60 | 0.00 | 352246.34 | 88191.61 |
July | 2254867.53 | 05-JUL-10:00 | 280450.63 | 660080.29 | 0.00 | 233151.79 | 315794.86 | 56569.07 | 0.00 | 577293.41 | 88191.61 |
August | 2178594.02 | 08-AUG-10:09 | 280450.63 | 778371.69 | 0.00 | 233151.79 | 223626.96 | 49150.79 | 0.00 | 485208.00 | 88191.61 |
September | 1595573.78 | 01-SEP-15:00 | 280450.63 | 423497.50 | 0.00 | 233302.19 | 267301.73 | 47280.77 | 0.00 | 211884.46 | 88191.61 |
October | 1515826.25 | 20-OCT-15:20 | 280450.63 | 541788.89 | 0.00 | 233302.19 | 184460.29 | 24786.52 | 0.00 | 61149.70 | 49559.82 |
November | 1529128.24 | 17-NOV-16:30 | 325713.14 | 660080.29 | 40855.88 | 233318.95 | 101511.65 | 3931.83 | 0.00 | 19288.74 | 2093.96 |
December | 1667351.60 | 18-DEC-16:00 | 325713.14 | 778371.69 | 40855.88 | 233326.38 | 90060.14 | 24699.19 | 0.00 | 21682.75 | 550.74 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1243107.13 | 280450.63 | 423497.50 | 0.00 | 233151.79 | 88521.41 | 3931.83 | 0.00 | 4229.51 | 116.48 | |
Maximum of Months | 2254867.53 | 325713.14 | 778371.69 | 40855.88 | 233326.38 | 315794.86 | 56569.07 | 0.00 | 577293.41 | 88191.61 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 2677693.85 | 09-JAN-07:30 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 2017719.83 | 14-FEB-07:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 1549301.13 | 06-MAR-07:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 622219.92 | 03-APR-06:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 231393.80 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 2299.28 | 10-JUN-05:40 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 4.41 | 17-JUL-19:00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 14236.20 | 19-AUG-05:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 146701.82 | 23-SEP-06:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 876219.57 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 1343491.72 | 25-NOV-07:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 2466755.16 | 26-DEC-07:19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 4.41 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 2677693.85 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 51.67 | 25.94 | 41.67 | 25.95 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 90.83 | 26.49 | 60.00 | 26.55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 238.67 | 27.86 | 179.67 | 27.90 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 720.00 | 29.82 | 485.00 | 29.87 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 29.92 | 508.00 | 29.97 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 720.00 | 30.22 | 496.00 | 30.27 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 30.52 | 497.00 | 30.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 30.78 | 514.00 | 30.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 720.00 | 30.44 | 485.00 | 30.48 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 30.23 | 502.00 | 30.28 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 626.50 | 29.84 | 420.50 | 29.89 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 148.17 | 27.17 | 99.83 | 27.22 |
Annual Sum or Average | 0.00 | 0.00 | 6291.83 | 29.98 | 4288.67 | 30.02 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 51.67 | 25.94 | 41.67 | 25.95 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 744.00 | 30.78 | 514.00 | 30.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.57 | 0.00 | 25.57 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 10.17 | 26.25 | 0.17 | 26.27 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 26.44 | 0.33 | 26.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 26.71 | 0.17 | 26.71 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 26.09 | 5.67 | 25.89 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 26.49 | 0.50 | 26.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 26.59 | 0.83 | 26.64 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 26.20 | 0.83 | 26.31 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 25.65 | 0.00 | 25.65 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.59 | 0.00 | 25.59 |
Annual Sum or Average | 0.00 | 0.00 | 77.33 | 26.34 | 8.50 | 26.31 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.83 | 26.71 | 5.67 | 26.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 19.17 | 0.83 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.67 | 0.33 | 24.67 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
Annual Sum or Average | 2.17 | 19.18 | 0.83 | 19.35 | 0.33 | 19.88 | 0.33 | 20.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.83 | 19.24 | 0.83 | 19.37 | 0.33 | 24.67 | 0.33 | 24.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.17 | 18.79 | 2.50 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
February | 3.83 | 18.72 | 0.50 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
March | 2.00 | 19.03 | 0.33 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
April | 0.17 | 18.12 | 0.00 | 18.12 | 0.00 | 18.12 | 0.00 | 18.12 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.64 | 0.33 | 24.64 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.33 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 | 0.00 | 19.01 |
November | 2.83 | 18.59 | 0.00 | 18.59 | 0.00 | 18.59 | 0.00 | 18.59 |
December | 7.17 | 18.73 | 1.33 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 |
Annual Sum or Average | 26.50 | 18.76 | 4.67 | 18.93 | 0.33 | 18.99 | 0.33 | 19.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 10.17 | 19.03 | 2.50 | 19.16 | 0.33 | 24.64 | 0.33 | 24.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.50 | 18.86 | 0.67 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
February | 1.33 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.15 | 1.50 | 27.23 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.10 | 4.50 | 27.24 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 26.80 | 15.17 | 26.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 27.08 | 5.83 | 27.25 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.66 | 0.00 | 25.66 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.00 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
Annual Sum or Average | 7.83 | 18.95 | 0.67 | 19.04 | 40.50 | 25.56 | 27.00 | 26.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.50 | 19.23 | 0.67 | 19.23 | 21.50 | 27.15 | 15.17 | 27.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.67 | 18.63 | 0.00 | 18.63 | 0.00 | 18.63 | 0.00 | 18.63 |
February | 1.33 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 | 0.00 | 19.11 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.34 | 0.33 | 27.34 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.46 | 2.00 | 28.46 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.33 | 6.00 | 28.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 28.41 | 8.00 | 28.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 28.05 | 8.67 | 28.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 28.39 | 8.50 | 28.41 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.31 | 3.33 | 28.33 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.09 | 2.67 | 28.09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.67 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 | 0.00 | 19.07 |
Annual Sum or Average | 7.67 | 18.81 | 0.00 | 18.81 | 41.17 | 26.79 | 39.50 | 27.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.67 | 19.11 | 0.00 | 19.11 | 9.33 | 28.46 | 8.67 | 28.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.33 | 18.68 | 0.17 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 |
February | 2.00 | 19.09 | 0.00 | 19.09 | 2.00 | 23.52 | 2.00 | 24.99 |
March | 0.17 | 19.20 | 0.00 | 19.20 | 4.17 | 28.01 | 4.17 | 28.19 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.31 | 4.00 | 28.33 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.03 | 3.50 | 28.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.01 | 4.33 | 28.10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 27.14 | 11.67 | 27.13 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 28.25 | 8.17 | 28.34 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.71 | 9.33 | 27.71 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 27.42 | 8.00 | 27.42 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.72 | 1.67 | 27.72 |
December | 2.33 | 18.91 | 0.00 | 18.91 | 0.33 | 19.96 | 0.33 | 20.78 |
Annual Sum or Average | 9.83 | 18.83 | 0.17 | 18.85 | 61.50 | 26.52 | 57.17 | 27.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.73 | 0.00 | 18.73 |
Maximum of Months | 5.33 | 19.20 | 0.17 | 19.20 | 13.50 | 28.31 | 11.67 | 28.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.50 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.55 | 0.33 | 27.55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.82 | 1.83 | 28.78 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 28.36 | 3.67 | 28.50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.86 | 2.50 | 28.95 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 28.02 | 3.83 | 28.06 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 19.33 | 28.09 | 9.67 | 28.22 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 27.91 | 7.00 | 28.15 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.32 | 2.33 | 28.37 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.10 | 1.67 | 28.10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.50 | 18.95 | 0.00 | 18.95 | 65.50 | 27.83 | 32.83 | 28.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.50 | 18.95 | 0.00 | 18.95 | 19.33 | 28.86 | 9.67 | 28.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 73.17 | 17.40 | 31.83 | 17.73 | 0.00 | 17.73 | 0.00 | 17.73 |
February | 31.00 | 17.99 | 9.50 | 18.32 | 0.00 | 18.32 | 0.00 | 18.32 |
March | 11.33 | 18.51 | 2.50 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 |
April | 0.67 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 25.44 | 2.83 | 25.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 |
November | 6.33 | 18.73 | 1.17 | 18.96 | 0.00 | 18.96 | 0.00 | 18.96 |
December | 60.83 | 17.03 | 25.00 | 17.25 | 0.00 | 17.25 | 0.00 | 17.25 |
Annual Sum or Average | 183.50 | 17.50 | 70.00 | 17.76 | 2.83 | 17.85 | 2.83 | 17.93 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 73.17 | 19.30 | 31.83 | 19.30 | 2.83 | 25.44 | 2.83 | 25.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 34.00 | 15.67 | 5.83 | 15.57 | 0.00 | 15.57 | 0.00 | 15.57 |
February | 13.50 | 16.98 | 0.67 | 17.00 | 0.00 | 17.00 | 0.00 | 17.00 |
March | 5.83 | 18.14 | 0.33 | 18.12 | 0.00 | 18.12 | 0.00 | 18.12 |
April | 0.67 | 19.33 | 0.00 | 19.33 | 0.83 | 24.09 | 0.83 | 25.44 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.44 | 3.50 | 28.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.69 | 6.00 | 28.69 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.30 | 4.83 | 28.30 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.62 | 4.83 | 28.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.04 | 2.17 | 28.04 |
October | 0.17 | 19.06 | 0.00 | 19.06 | 0.33 | 24.90 | 0.33 | 26.07 |
November | 4.33 | 18.08 | 0.00 | 18.08 | 0.00 | 18.08 | 0.00 | 18.08 |
December | 33.17 | 15.63 | 6.67 | 15.47 | 0.00 | 15.47 | 0.00 | 15.47 |
Annual Sum or Average | 91.67 | 16.15 | 13.50 | 16.01 | 22.50 | 18.20 | 22.50 | 19.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.47 | 0.00 | 15.47 |
Maximum of Months | 34.00 | 19.33 | 6.67 | 19.33 | 6.00 | 28.69 | 6.00 | 28.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 25.00 | 16.25 | 2.33 | 16.18 | 0.00 | 16.18 | 0.00 | 16.18 |
February | 9.33 | 17.81 | 0.67 | 17.80 | 1.83 | 19.33 | 1.83 | 20.45 |
March | 4.17 | 18.74 | 0.17 | 18.80 | 4.17 | 23.62 | 4.17 | 25.27 |
April | 0.17 | 19.34 | 0.00 | 19.34 | 2.83 | 27.91 | 2.67 | 28.17 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.17 | 2.83 | 28.17 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.05 | 3.33 | 28.05 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.62 | 6.83 | 27.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 28.43 | 6.50 | 28.44 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.77 | 8.50 | 27.78 |
October | 0.17 | 19.19 | 0.00 | 19.19 | 5.67 | 27.94 | 5.67 | 28.06 |
November | 3.50 | 18.19 | 0.00 | 18.19 | 0.00 | 18.19 | 0.00 | 18.19 |
December | 21.33 | 16.32 | 2.00 | 16.17 | 0.00 | 16.17 | 0.00 | 16.17 |
Annual Sum or Average | 63.67 | 16.79 | 5.17 | 16.69 | 43.17 | 21.08 | 42.33 | 23.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 0.00 | 16.17 |
Maximum of Months | 25.00 | 19.34 | 2.33 | 19.34 | 8.67 | 28.43 | 8.50 | 28.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 27.17 | 15.96 | 4.50 | 15.82 | 0.00 | 15.82 | 0.00 | 15.82 |
February | 8.67 | 17.88 | 0.17 | 17.93 | 0.00 | 17.93 | 0.00 | 17.93 |
March | 4.00 | 18.71 | 0.17 | 18.78 | 1.33 | 21.08 | 0.67 | 21.86 |
April | 0.17 | 19.43 | 0.00 | 19.43 | 2.83 | 28.26 | 1.50 | 28.44 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.94 | 2.00 | 29.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.37 | 1.83 | 28.33 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 28.77 | 4.50 | 28.86 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.63 | 3.67 | 28.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.50 | 1.67 | 28.50 |
October | 0.17 | 19.30 | 0.00 | 19.30 | 0.50 | 25.80 | 0.50 | 26.72 |
November | 3.33 | 18.29 | 0.00 | 18.29 | 0.00 | 18.29 | 0.00 | 18.29 |
December | 25.50 | 15.93 | 5.33 | 15.72 | 0.00 | 15.72 | 0.00 | 15.72 |
Annual Sum or Average | 69.00 | 16.48 | 10.17 | 16.29 | 32.00 | 19.85 | 16.33 | 20.99 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.72 | 0.00 | 15.72 |
Maximum of Months | 27.17 | 19.43 | 5.33 | 19.43 | 9.17 | 28.94 | 4.50 | 29.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 143.00 | 16.76 | 67.50 | 17.17 | 0.00 | 17.17 | 0.00 | 17.17 |
February | 84.67 | 16.92 | 34.50 | 17.35 | 0.00 | 17.35 | 0.00 | 17.35 |
March | 42.17 | 17.46 | 14.33 | 17.79 | 0.00 | 17.79 | 0.00 | 17.79 |
April | 5.00 | 18.41 | 0.50 | 18.57 | 0.00 | 18.57 | 0.00 | 18.57 |
May | 0.17 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.35 | 0.17 | 27.35 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 26.63 | 2.00 | 26.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4.50 | 18.53 | 0.83 | 18.76 | 0.00 | 18.76 | 0.00 | 18.76 |
November | 39.83 | 16.83 | 12.83 | 17.08 | 0.00 | 17.08 | 0.00 | 17.08 |
December | 113.33 | 16.56 | 48.67 | 16.92 | 0.00 | 16.92 | 0.00 | 16.92 |
Annual Sum or Average | 432.67 | 16.85 | 179.17 | 17.21 | 2.83 | 17.26 | 2.17 | 17.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 143.00 | 19.32 | 67.50 | 19.32 | 2.67 | 27.35 | 2.00 | 27.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 68.67 | 14.90 | 17.17 | 14.87 | 0.00 | 14.87 | 0.00 | 14.87 |
February | 39.67 | 15.37 | 3.83 | 15.39 | 0.00 | 15.39 | 0.00 | 15.39 |
March | 19.83 | 16.33 | 1.50 | 16.26 | 0.00 | 16.26 | 0.00 | 16.26 |
April | 3.83 | 18.15 | 0.00 | 18.15 | 0.00 | 18.15 | 0.00 | 18.15 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.16 | 2.50 | 28.16 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 28.63 | 5.83 | 28.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.35 | 4.67 | 28.36 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.42 | 5.00 | 28.42 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.80 | 1.50 | 27.80 |
October | 3.00 | 17.85 | 0.00 | 17.85 | 0.00 | 17.85 | 0.00 | 17.85 |
November | 26.33 | 15.62 | 5.00 | 15.50 | 0.00 | 15.50 | 0.00 | 15.50 |
December | 61.33 | 14.84 | 14.00 | 14.75 | 0.00 | 14.75 | 0.00 | 14.75 |
Annual Sum or Average | 222.67 | 15.28 | 41.50 | 15.19 | 19.67 | 16.10 | 19.50 | 16.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.75 | 0.00 | 14.75 |
Maximum of Months | 68.67 | 18.15 | 17.17 | 18.15 | 5.83 | 28.63 | 5.83 | 28.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 55.17 | 15.29 | 10.00 | 15.29 | 0.00 | 15.29 | 0.00 | 15.29 |
February | 30.00 | 15.82 | 3.00 | 15.82 | 0.00 | 15.82 | 0.00 | 15.82 |
March | 15.67 | 16.79 | 1.50 | 16.66 | 3.00 | 18.36 | 3.00 | 19.63 |
April | 3.17 | 18.20 | 0.00 | 18.20 | 1.83 | 21.96 | 1.67 | 23.60 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.01 | 2.33 | 28.01 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.06 | 3.17 | 28.06 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.23 | 5.33 | 28.26 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 28.44 | 6.17 | 28.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.89 | 6.67 | 27.89 |
October | 1.83 | 18.23 | 0.00 | 18.23 | 4.00 | 25.34 | 4.00 | 26.67 |
November | 18.50 | 16.12 | 2.50 | 15.97 | 0.00 | 15.97 | 0.00 | 15.97 |
December | 50.33 | 15.27 | 8.67 | 15.20 | 0.00 | 15.20 | 0.00 | 15.20 |
Annual Sum or Average | 174.67 | 15.68 | 25.67 | 15.61 | 33.67 | 17.43 | 32.33 | 18.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.20 | 0.00 | 15.20 |
Maximum of Months | 55.17 | 18.23 | 10.00 | 18.23 | 6.83 | 28.44 | 6.67 | 28.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 56.83 | 15.01 | 13.50 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 |
February | 28.83 | 15.78 | 3.67 | 15.77 | 0.00 | 15.77 | 0.00 | 15.77 |
March | 13.67 | 17.00 | 0.83 | 16.92 | 0.83 | 17.51 | 0.50 | 17.83 |
April | 2.17 | 18.30 | 0.00 | 18.30 | 2.17 | 23.61 | 1.00 | 24.63 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 28.96 | 2.00 | 28.99 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.47 | 1.50 | 28.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 28.77 | 4.83 | 28.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 28.58 | 3.83 | 28.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.75 | 1.17 | 28.72 |
October | 1.33 | 18.56 | 0.00 | 18.56 | 0.50 | 20.99 | 0.50 | 22.39 |
November | 14.83 | 16.37 | 1.17 | 16.27 | 0.00 | 16.27 | 0.00 | 16.27 |
December | 48.50 | 15.12 | 10.50 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 |
Annual Sum or Average | 166.17 | 15.53 | 29.67 | 15.42 | 30.17 | 17.19 | 15.33 | 17.93 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.97 | 0.00 | 14.97 |
Maximum of Months | 56.83 | 18.56 | 13.50 | 18.56 | 9.67 | 28.96 | 4.83 | 28.99 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.87 | 2.33 | 28.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.50 | 28.87 | 2.33 | 28.70 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.87 | 2.33 | 28.70 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.62 | 0.67 | 28.48 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.17 | 28.62 | 0.67 | 28.48 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.62 | 0.67 | 28.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.55 | 0.17 | 28.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 2.50 | 28.55 | 0.17 | 28.51 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.55 | 0.17 | 28.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 28.51 | 21.00 | 28.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 62.00 | 29.00 | 62.00 | 29.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 85.17 | 28.86 | 83.00 | 28.88 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 62.00 | 29.00 | 62.00 | 29.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 366.67 | 24.22 | 33.33 | 24.33 | 21.17 | 24.40 |
February | 278.17 | 24.35 | 56.33 | 24.73 | 26.17 | 24.91 |
March | 307.50 | 25.93 | 208.50 | 26.66 | 126.17 | 27.05 |
April | 485.00 | 29.94 | 485.00 | 29.94 | 485.00 | 29.94 |
May | 508.00 | 30.04 | 508.00 | 30.04 | 508.00 | 30.04 |
June | 496.00 | 30.34 | 496.00 | 30.34 | 496.00 | 30.34 |
July | 497.00 | 30.64 | 497.00 | 30.64 | 497.00 | 30.64 |
August | 514.00 | 30.89 | 514.00 | 30.89 | 514.00 | 30.89 |
September | 485.00 | 30.55 | 485.00 | 30.55 | 485.00 | 30.55 |
October | 502.00 | 30.34 | 502.00 | 30.34 | 502.00 | 30.34 |
November | 424.50 | 29.80 | 431.33 | 29.84 | 404.83 | 29.92 |
December | 282.50 | 24.84 | 122.83 | 25.52 | 56.67 | 25.82 |
Annual Sum or Average | 5146.33 | 29.01 | 4339.33 | 29.48 | 4122.00 | 29.71 |
Minimum of Months | 278.17 | 24.22 | 33.33 | 24.33 | 21.17 | 24.40 |
Maximum of Months | 514.00 | 30.89 | 514.00 | 30.89 | 514.00 | 30.89 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 493.67 | 23.56 | 0.00 | 23.56 | 0.00 | 23.56 |
February | 379.50 | 23.87 | 0.33 | 23.87 | 0.00 | 23.87 |
March | 276.67 | 23.94 | 14.00 | 24.05 | 0.00 | 24.05 |
April | 3.50 | 24.00 | 111.00 | 26.04 | 0.00 | 26.04 |
May | 0.00 | 0.00 | 309.50 | 24.73 | 0.00 | 24.73 |
June | 2.17 | 27.16 | 453.67 | 24.47 | 2.17 | 24.49 |
July | 16.50 | 26.58 | 497.00 | 24.61 | 16.50 | 24.67 |
August | 6.83 | 26.93 | 514.00 | 24.47 | 6.83 | 24.50 |
September | 4.83 | 27.14 | 380.67 | 24.66 | 4.83 | 24.69 |
October | 0.00 | 0.00 | 203.17 | 25.37 | 0.00 | 25.37 |
November | 52.00 | 23.96 | 127.67 | 25.32 | 0.00 | 25.32 |
December | 370.33 | 23.95 | 9.17 | 24.00 | 0.00 | 24.00 |
Annual Sum or Average | 1606.00 | 23.86 | 2620.17 | 24.41 | 30.33 | 24.43 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 23.56 | 0.00 | 23.56 |
Maximum of Months | 493.67 | 27.16 | 514.00 | 26.04 | 16.50 | 26.04 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.50 | 181.17 | 21.21 | 181.17 | 21.04 |
February | 454.00 | 22.26 | 55.67 | 22.08 | 55.67 | 21.93 |
March | 506.33 | 22.98 | 11.50 | 22.93 | 11.50 | 22.89 |
April | 418.33 | 23.62 | 0.00 | 23.62 | 0.00 | 23.62 |
May | 148.17 | 23.76 | 148.83 | 24.11 | 0.00 | 24.11 |
June | 35.50 | 23.98 | 316.67 | 24.20 | 5.17 | 24.21 |
July | 3.17 | 24.10 | 463.67 | 24.24 | 2.67 | 24.24 |
August | 11.17 | 23.48 | 425.50 | 24.16 | 0.00 | 24.16 |
September | 109.17 | 23.54 | 127.50 | 24.03 | 3.50 | 24.03 |
October | 351.83 | 23.45 | 3.50 | 23.46 | 0.00 | 23.46 |
November | 466.17 | 22.92 | 25.67 | 22.83 | 23.50 | 22.73 |
December | 497.00 | 21.70 | 128.67 | 21.44 | 128.67 | 21.28 |
Annual Sum or Average | 3502.83 | 22.67 | 1888.33 | 22.95 | 411.83 | 22.78 |
Minimum of Months | 3.17 | 21.50 | 0.00 | 21.21 | 0.00 | 21.04 |
Maximum of Months | 506.33 | 24.10 | 463.67 | 24.24 | 181.17 | 24.24 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.45 | 375.33 | 20.27 | 375.33 | 20.20 |
February | 454.00 | 20.89 | 266.00 | 20.63 | 266.00 | 20.51 |
March | 514.00 | 21.59 | 173.00 | 21.27 | 173.00 | 21.08 |
April | 465.67 | 22.61 | 54.50 | 22.39 | 54.50 | 22.21 |
May | 205.33 | 23.24 | 137.67 | 23.70 | 0.83 | 23.70 |
June | 82.50 | 23.23 | 288.67 | 23.97 | 5.00 | 23.97 |
July | 29.50 | 23.32 | 432.50 | 24.17 | 2.67 | 24.17 |
August | 49.33 | 23.27 | 387.83 | 24.03 | 3.17 | 24.03 |
September | 246.17 | 23.15 | 73.33 | 23.38 | 11.83 | 23.41 |
October | 467.83 | 22.23 | 47.17 | 22.04 | 47.17 | 21.88 |
November | 488.83 | 21.33 | 187.67 | 20.97 | 187.67 | 20.76 |
December | 497.00 | 20.54 | 338.83 | 20.33 | 338.83 | 20.24 |
Annual Sum or Average | 4002.17 | 21.65 | 2762.50 | 21.82 | 1466.00 | 21.52 |
Minimum of Months | 29.50 | 20.45 | 47.17 | 20.27 | 0.83 | 20.20 |
Maximum of Months | 514.00 | 23.32 | 432.50 | 24.17 | 375.33 | 24.17 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.62 | 427.83 | 20.55 | 427.83 | 20.52 |
February | 454.00 | 21.31 | 242.33 | 21.10 | 242.33 | 21.01 |
March | 496.83 | 22.15 | 96.17 | 21.94 | 96.17 | 21.78 |
April | 290.17 | 23.76 | 26.00 | 23.90 | 0.83 | 23.91 |
May | 47.67 | 24.17 | 253.33 | 24.55 | 2.83 | 24.57 |
June | 20.67 | 26.82 | 456.50 | 24.56 | 20.67 | 24.66 |
July | 56.67 | 26.75 | 494.67 | 24.81 | 56.67 | 24.99 |
August | 24.67 | 26.85 | 503.83 | 24.52 | 24.67 | 24.63 |
September | 33.67 | 24.11 | 246.33 | 24.55 | 3.50 | 24.57 |
October | 226.67 | 23.70 | 44.67 | 23.88 | 0.00 | 23.88 |
November | 435.33 | 22.97 | 41.17 | 22.90 | 25.33 | 22.79 |
December | 497.00 | 21.00 | 309.17 | 20.81 | 309.17 | 20.72 |
Annual Sum or Average | 3085.33 | 22.18 | 3142.00 | 22.67 | 1210.00 | 22.42 |
Minimum of Months | 20.67 | 20.62 | 26.00 | 20.55 | 0.00 | 20.52 |
Maximum of Months | 502.00 | 26.85 | 503.83 | 24.81 | 427.83 | 24.99 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.66 | 396.50 | 20.57 | 396.50 | 20.54 |
February | 445.50 | 21.37 | 205.17 | 21.16 | 205.17 | 21.06 |
March | 439.33 | 21.83 | 117.67 | 21.77 | 96.83 | 21.63 |
April | 243.00 | 23.28 | 97.17 | 23.69 | 7.50 | 23.76 |
May | 58.83 | 24.62 | 321.50 | 24.61 | 17.50 | 24.73 |
June | 37.50 | 26.60 | 464.50 | 24.59 | 36.50 | 24.74 |
July | 65.00 | 25.94 | 494.00 | 24.65 | 65.00 | 24.78 |
August | 42.33 | 26.65 | 496.17 | 24.54 | 40.50 | 24.70 |
September | 80.33 | 23.89 | 298.17 | 24.37 | 15.50 | 24.47 |
October | 287.67 | 23.23 | 71.00 | 23.57 | 8.33 | 23.65 |
November | 445.00 | 22.40 | 54.83 | 22.34 | 40.00 | 22.23 |
December | 497.00 | 20.81 | 346.17 | 20.69 | 346.17 | 20.64 |
Annual Sum or Average | 3143.50 | 22.05 | 3362.83 | 22.66 | 1275.50 | 22.46 |
Minimum of Months | 37.50 | 20.66 | 54.83 | 20.57 | 7.50 | 20.54 |
Maximum of Months | 502.00 | 26.65 | 496.17 | 24.65 | 396.50 | 24.78 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 448.50 | 20.99 | 315.00 | 20.80 | 301.67 | 20.68 |
February | 353.50 | 21.64 | 200.50 | 21.62 | 159.00 | 21.43 |
March | 383.33 | 22.11 | 158.50 | 22.24 | 100.17 | 22.11 |
April | 249.00 | 23.27 | 118.50 | 23.70 | 15.00 | 23.77 |
May | 85.00 | 23.88 | 298.33 | 24.40 | 10.83 | 24.47 |
June | 29.00 | 25.88 | 425.50 | 24.49 | 19.83 | 24.59 |
July | 44.00 | 26.74 | 488.50 | 24.69 | 43.83 | 24.84 |
August | 36.17 | 26.74 | 491.67 | 24.57 | 32.83 | 24.72 |
September | 106.83 | 24.39 | 298.50 | 24.55 | 32.83 | 24.73 |
October | 293.33 | 23.35 | 116.17 | 23.77 | 24.83 | 23.91 |
November | 383.83 | 22.37 | 113.83 | 22.41 | 60.83 | 22.24 |
December | 449.33 | 21.09 | 267.83 | 20.94 | 258.17 | 20.83 |
Annual Sum or Average | 2861.83 | 22.29 | 3292.83 | 22.92 | 1059.83 | 22.74 |
Minimum of Months | 29.00 | 20.99 | 113.83 | 20.80 | 10.83 | 20.68 |
Maximum of Months | 449.33 | 26.74 | 491.67 | 24.69 | 301.67 | 24.84 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 495.67 | 21.01 | 310.00 | 20.87 | 310.00 | 20.81 |
February | 410.67 | 21.87 | 112.50 | 21.75 | 101.50 | 21.62 |
March | 385.50 | 22.67 | 60.67 | 22.85 | 17.67 | 22.86 |
April | 124.33 | 23.81 | 135.00 | 24.43 | 12.00 | 24.56 |
May | 90.50 | 23.93 | 315.33 | 24.39 | 26.33 | 24.46 |
June | 44.50 | 25.60 | 458.50 | 24.53 | 42.67 | 24.62 |
July | 94.50 | 25.81 | 496.83 | 24.77 | 94.50 | 24.92 |
August | 70.67 | 25.91 | 511.67 | 24.64 | 70.67 | 24.78 |
September | 115.33 | 23.50 | 270.50 | 24.18 | 15.83 | 24.28 |
October | 246.83 | 23.18 | 100.00 | 23.61 | 5.00 | 23.66 |
November | 378.00 | 22.86 | 30.33 | 22.95 | 5.17 | 22.92 |
December | 484.00 | 21.94 | 79.83 | 21.78 | 79.83 | 21.66 |
Annual Sum or Average | 2940.50 | 22.57 | 2881.17 | 23.21 | 781.17 | 23.13 |
Minimum of Months | 44.50 | 21.01 | 30.33 | 20.87 | 5.00 | 20.81 |
Maximum of Months | 495.67 | 25.91 | 511.67 | 24.77 | 310.00 | 24.92 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.79 | 500.33 | 19.79 | 500.33 | 19.79 |
February | 454.00 | 20.14 | 431.00 | 20.11 | 431.00 | 20.10 |
March | 514.00 | 20.74 | 364.00 | 20.59 | 364.00 | 20.52 |
April | 473.33 | 21.99 | 117.17 | 21.71 | 115.17 | 21.52 |
May | 216.83 | 23.23 | 153.17 | 23.70 | 1.50 | 23.69 |
June | 50.50 | 23.69 | 323.50 | 24.20 | 3.17 | 24.22 |
July | 37.17 | 25.23 | 462.67 | 24.44 | 26.67 | 24.51 |
August | 62.33 | 23.16 | 378.17 | 24.02 | 0.00 | 24.02 |
September | 292.17 | 22.84 | 71.00 | 23.11 | 3.67 | 23.11 |
October | 497.00 | 21.72 | 87.67 | 21.52 | 87.67 | 21.37 |
November | 489.00 | 20.51 | 345.67 | 20.34 | 345.67 | 20.27 |
December | 497.00 | 19.88 | 494.67 | 19.87 | 494.67 | 19.87 |
Annual Sum or Average | 4085.33 | 21.08 | 3729.00 | 21.35 | 2373.50 | 21.06 |
Minimum of Months | 37.17 | 19.79 | 71.00 | 19.79 | 0.00 | 19.79 |
Maximum of Months | 514.00 | 25.23 | 500.33 | 24.44 | 500.33 | 24.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.69 | 426.17 | 19.69 | 426.17 | 19.69 |
February | 385.00 | 20.24 | 335.67 | 20.15 | 335.67 | 20.12 |
March | 413.33 | 21.00 | 241.67 | 20.82 | 238.67 | 20.72 |
April | 314.50 | 21.83 | 113.00 | 21.96 | 65.67 | 21.79 |
May | 170.00 | 23.07 | 190.83 | 23.94 | 11.17 | 24.04 |
June | 84.67 | 24.13 | 298.67 | 24.37 | 29.17 | 24.54 |
July | 63.50 | 25.16 | 374.67 | 24.57 | 45.50 | 24.72 |
August | 122.83 | 23.40 | 284.17 | 24.09 | 22.50 | 24.24 |
September | 256.00 | 22.38 | 106.67 | 23.02 | 7.00 | 23.09 |
October | 394.17 | 21.37 | 95.00 | 21.39 | 76.33 | 21.29 |
November | 417.00 | 20.44 | 283.83 | 20.27 | 283.83 | 20.20 |
December | 422.00 | 19.75 | 418.83 | 19.74 | 418.83 | 19.74 |
Annual Sum or Average | 3470.00 | 21.09 | 3169.17 | 21.47 | 1960.50 | 21.22 |
Minimum of Months | 63.50 | 19.69 | 95.00 | 19.69 | 7.00 | 19.69 |
Maximum of Months | 427.00 | 25.16 | 426.17 | 24.57 | 426.17 | 24.72 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 461.67 | 20.39 | 375.50 | 20.21 | 364.33 | 20.10 |
February | 362.50 | 21.00 | 272.33 | 20.96 | 232.83 | 20.79 |
March | 405.67 | 21.54 | 250.00 | 21.58 | 199.00 | 21.44 |
April | 331.67 | 22.15 | 148.00 | 22.42 | 69.33 | 22.29 |
May | 175.83 | 23.03 | 227.67 | 23.85 | 8.50 | 23.92 |
June | 111.33 | 23.45 | 329.67 | 24.10 | 13.83 | 24.18 |
July | 73.17 | 24.77 | 432.50 | 24.48 | 37.50 | 24.61 |
August | 99.83 | 24.00 | 387.33 | 24.28 | 26.83 | 24.43 |
September | 228.17 | 23.10 | 211.17 | 23.83 | 29.83 | 24.03 |
October | 396.50 | 22.11 | 133.17 | 22.41 | 70.33 | 22.40 |
November | 430.00 | 21.04 | 244.00 | 20.95 | 209.17 | 20.76 |
December | 467.50 | 20.37 | 393.17 | 20.21 | 393.17 | 20.15 |
Annual Sum or Average | 3543.83 | 21.61 | 3404.50 | 22.08 | 1654.67 | 21.83 |
Minimum of Months | 73.17 | 20.37 | 133.17 | 20.21 | 8.50 | 20.10 |
Maximum of Months | 467.50 | 24.77 | 432.50 | 24.48 | 393.17 | 24.61 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.04 | 472.17 | 19.99 | 472.17 | 19.97 |
February | 444.33 | 20.58 | 340.83 | 20.43 | 340.83 | 20.37 |
March | 469.83 | 21.04 | 274.67 | 20.94 | 257.33 | 20.83 |
April | 391.50 | 21.91 | 119.17 | 22.02 | 69.50 | 21.90 |
May | 209.33 | 23.02 | 234.00 | 23.81 | 22.67 | 23.89 |
June | 114.50 | 23.28 | 348.50 | 24.09 | 24.00 | 24.15 |
July | 85.67 | 24.81 | 447.17 | 24.53 | 58.50 | 24.64 |
August | 113.17 | 23.58 | 379.17 | 24.15 | 32.50 | 24.26 |
September | 295.00 | 22.52 | 135.17 | 23.12 | 10.50 | 23.21 |
October | 457.00 | 21.57 | 92.00 | 21.62 | 61.83 | 21.53 |
November | 486.00 | 20.71 | 280.50 | 20.53 | 280.50 | 20.45 |
December | 497.00 | 20.07 | 466.33 | 20.04 | 466.33 | 20.03 |
Annual Sum or Average | 4065.33 | 21.27 | 3589.67 | 21.67 | 2096.67 | 21.43 |
Minimum of Months | 85.67 | 20.04 | 92.00 | 19.99 | 10.50 | 19.97 |
Maximum of Months | 502.00 | 24.81 | 472.17 | 24.53 | 472.17 | 24.64 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.57 | 502.00 | 19.57 | 502.00 | 19.57 |
February | 454.00 | 19.80 | 445.17 | 19.79 | 445.17 | 19.78 |
March | 514.00 | 20.33 | 440.17 | 20.24 | 440.17 | 20.21 |
April | 477.67 | 21.28 | 214.50 | 20.93 | 214.33 | 20.74 |
May | 252.83 | 22.67 | 157.67 | 23.18 | 16.33 | 23.09 |
June | 99.33 | 23.27 | 297.33 | 24.00 | 7.17 | 24.05 |
July | 69.67 | 24.51 | 438.17 | 24.37 | 38.17 | 24.48 |
August | 115.17 | 22.87 | 337.50 | 23.82 | 3.33 | 23.82 |
September | 368.67 | 22.37 | 63.67 | 22.54 | 16.00 | 22.51 |
October | 502.00 | 20.88 | 204.33 | 20.59 | 204.33 | 20.44 |
November | 489.00 | 19.97 | 417.17 | 19.87 | 417.17 | 19.84 |
December | 497.00 | 19.64 | 497.00 | 19.64 | 497.00 | 19.64 |
Annual Sum or Average | 4341.33 | 20.75 | 4014.67 | 20.97 | 2801.17 | 20.71 |
Minimum of Months | 69.67 | 19.57 | 63.67 | 19.57 | 3.33 | 19.57 |
Maximum of Months | 514.00 | 24.51 | 502.00 | 24.37 | 502.00 | 24.48 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.75 | 502.00 | 19.75 | 502.00 | 19.75 |
February | 454.00 | 20.00 | 410.50 | 19.93 | 410.50 | 19.90 |
March | 497.33 | 20.75 | 345.33 | 20.54 | 345.33 | 20.45 |
April | 365.83 | 21.40 | 170.00 | 21.31 | 127.50 | 21.06 |
May | 200.83 | 22.67 | 223.33 | 23.63 | 10.50 | 23.67 |
June | 111.83 | 23.69 | 361.33 | 24.17 | 30.17 | 24.32 |
July | 86.83 | 24.61 | 431.67 | 24.43 | 53.00 | 24.57 |
August | 150.83 | 23.11 | 337.50 | 23.93 | 22.33 | 24.07 |
September | 307.50 | 22.04 | 120.83 | 22.64 | 10.67 | 22.67 |
October | 468.17 | 20.90 | 189.50 | 20.75 | 175.17 | 20.59 |
November | 489.00 | 20.08 | 386.50 | 19.94 | 386.50 | 19.89 |
December | 497.00 | 19.77 | 494.83 | 19.76 | 494.83 | 19.76 |
Annual Sum or Average | 4131.17 | 20.86 | 3973.33 | 21.22 | 2568.50 | 20.97 |
Minimum of Months | 86.83 | 19.75 | 120.83 | 19.75 | 10.50 | 19.75 |
Maximum of Months | 502.00 | 24.61 | 502.00 | 24.43 | 502.00 | 24.57 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 473.67 | 20.11 | 398.17 | 19.91 | 393.17 | 19.83 |
February | 384.67 | 20.57 | 303.50 | 20.43 | 275.67 | 20.26 |
March | 416.17 | 21.01 | 315.67 | 21.01 | 271.00 | 20.85 |
April | 351.00 | 21.56 | 206.00 | 21.62 | 139.17 | 21.38 |
May | 203.83 | 22.52 | 223.00 | 23.39 | 20.83 | 23.35 |
June | 141.17 | 22.97 | 309.67 | 23.87 | 15.83 | 23.96 |
July | 100.33 | 24.07 | 407.00 | 24.35 | 40.17 | 24.49 |
August | 144.67 | 23.39 | 353.17 | 24.07 | 25.50 | 24.22 |
September | 283.33 | 22.61 | 184.17 | 23.37 | 29.33 | 23.53 |
October | 419.50 | 21.34 | 205.50 | 21.48 | 145.67 | 21.33 |
November | 447.83 | 20.43 | 310.33 | 20.26 | 289.83 | 20.11 |
December | 482.83 | 20.11 | 425.33 | 19.96 | 425.33 | 19.91 |
Annual Sum or Average | 3849.00 | 21.20 | 3641.50 | 21.59 | 2071.50 | 21.32 |
Minimum of Months | 100.33 | 20.11 | 184.17 | 19.91 | 15.83 | 19.83 |
Maximum of Months | 482.83 | 24.07 | 425.33 | 24.35 | 425.33 | 24.49 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.84 | 478.50 | 19.80 | 478.50 | 19.78 |
February | 445.00 | 20.23 | 374.50 | 20.10 | 374.50 | 20.06 |
March | 476.83 | 20.70 | 343.50 | 20.59 | 327.00 | 20.50 |
April | 404.00 | 21.42 | 193.67 | 21.39 | 146.50 | 21.20 |
May | 243.00 | 22.62 | 225.33 | 23.47 | 29.83 | 23.54 |
June | 144.67 | 22.96 | 321.83 | 23.91 | 29.00 | 23.99 |
July | 115.83 | 24.31 | 423.67 | 24.42 | 65.33 | 24.56 |
August | 164.00 | 23.18 | 336.33 | 23.95 | 34.83 | 24.07 |
September | 337.67 | 22.15 | 110.50 | 22.70 | 9.83 | 22.78 |
October | 463.00 | 21.02 | 173.17 | 20.95 | 145.83 | 20.79 |
November | 488.17 | 20.24 | 354.17 | 20.07 | 354.17 | 20.00 |
December | 497.00 | 19.85 | 482.33 | 19.83 | 482.33 | 19.82 |
Annual Sum or Average | 4281.17 | 20.99 | 3817.50 | 21.32 | 2477.67 | 21.09 |
Minimum of Months | 115.83 | 19.84 | 110.50 | 19.80 | 9.83 | 19.78 |
Maximum of Months | 502.00 | 24.31 | 482.33 | 24.42 | 482.33 | 24.56 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 26.13 | 308.17 | 27.00 | 0.00 | 27.00 |
February | 1.83 | 27.00 | 434.00 | 27.00 | 1.83 | 27.00 |
March | 12.83 | 27.00 | 514.00 | 27.00 | 12.83 | 27.00 |
April | 48.83 | 27.07 | 485.00 | 27.01 | 48.83 | 27.02 |
May | 52.67 | 27.00 | 508.00 | 27.00 | 52.67 | 27.00 |
June | 194.50 | 27.00 | 496.00 | 27.00 | 194.50 | 27.00 |
July | 388.17 | 27.00 | 497.00 | 27.00 | 388.17 | 27.00 |
August | 455.83 | 27.00 | 514.00 | 27.00 | 455.83 | 27.00 |
September | 45.67 | 27.00 | 485.00 | 27.00 | 45.67 | 27.00 |
October | 25.33 | 27.00 | 502.00 | 27.00 | 25.33 | 27.00 |
November | 3.17 | 27.00 | 489.00 | 27.00 | 3.17 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 1229.50 | 27.00 | 5729.17 | 27.00 | 1228.83 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 308.17 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 455.83 | 27.07 | 514.00 | 27.01 | 455.83 | 27.02 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 243.00 | 25.44 | 69.17 | 25.67 | 7.33 | 25.60 |
February | 20.33 | 27.00 | 172.67 | 27.00 | 0.00 | 27.00 |
March | 2.83 | 27.00 | 376.00 | 27.00 | 2.83 | 27.00 |
April | 9.33 | 27.05 | 481.83 | 27.00 | 9.33 | 27.00 |
May | 23.33 | 27.00 | 508.00 | 27.00 | 23.33 | 27.00 |
June | 45.83 | 27.00 | 496.00 | 27.00 | 45.83 | 27.00 |
July | 88.67 | 27.00 | 497.00 | 27.00 | 88.67 | 27.00 |
August | 76.17 | 27.00 | 514.00 | 27.00 | 76.17 | 27.00 |
September | 14.83 | 27.00 | 485.00 | 27.00 | 14.83 | 27.00 |
October | 4.17 | 27.00 | 502.00 | 27.00 | 4.17 | 27.00 |
November | 5.67 | 27.00 | 360.00 | 27.00 | 0.00 | 27.00 |
December | 43.67 | 27.00 | 150.67 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 577.83 | 26.35 | 4612.33 | 26.92 | 272.50 | 26.92 |
Minimum of Months | 2.83 | 25.44 | 69.17 | 25.67 | 0.00 | 25.60 |
Maximum of Months | 243.00 | 27.05 | 514.00 | 27.00 | 88.67 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 384.33 | 24.59 | 100.33 | 24.42 | 70.00 | 24.16 |
February | 94.00 | 26.97 | 96.33 | 26.99 | 0.00 | 26.99 |
March | 41.67 | 27.00 | 251.67 | 27.00 | 1.33 | 27.00 |
April | 9.17 | 27.02 | 407.83 | 27.00 | 9.17 | 27.00 |
May | 31.67 | 27.00 | 502.50 | 27.00 | 31.67 | 27.00 |
June | 65.50 | 27.00 | 496.00 | 27.00 | 65.50 | 27.00 |
July | 115.33 | 27.00 | 497.00 | 27.00 | 115.33 | 27.00 |
August | 92.00 | 27.00 | 514.00 | 27.00 | 92.00 | 27.00 |
September | 14.83 | 27.00 | 485.00 | 27.00 | 14.83 | 27.00 |
October | 3.67 | 27.00 | 447.67 | 27.00 | 3.67 | 27.00 |
November | 58.67 | 27.00 | 230.83 | 27.00 | 0.00 | 27.00 |
December | 103.00 | 27.00 | 77.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 1013.83 | 26.08 | 4106.17 | 26.76 | 403.50 | 26.71 |
Minimum of Months | 3.67 | 24.59 | 77.00 | 24.42 | 0.00 | 24.16 |
Maximum of Months | 384.33 | 27.02 | 514.00 | 27.00 | 115.33 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 97.33 | 27.00 | 502.00 | 27.00 | 97.33 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.08 | 497.00 | 27.08 | 497.00 | 27.08 |
August | 514.00 | 27.27 | 514.00 | 27.27 | 514.00 | 27.27 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5538.33 | 27.03 | 5943.00 | 27.03 | 5538.33 | 27.03 |
Minimum of Months | 97.33 | 27.00 | 454.00 | 27.00 | 97.33 | 27.00 |
Maximum of Months | 514.00 | 27.27 | 514.00 | 27.27 | 514.00 | 27.27 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99101 | 11.11529 | 0.57718 | 12.12538 |
February | 454.00000 | 27.00000 | 11.47474 | 0.66884 | 14.57583 |
March | 514.00000 | 27.00000 | 14.96683 | 0.77373 | 17.79843 |
April | 485.00000 | 27.00715 | 18.08873 | 0.90516 | 22.40928 |
May | 508.00000 | 27.00028 | 29.07579 | 0.27758 | 6.82449 |
June | 496.00000 | 27.00090 | 34.49539 | 0.38327 | 8.19492 |
July | 497.00000 | 27.00070 | 36.11846 | 0.45918 | 9.50270 |
August | 514.00000 | 27.00035 | 35.45372 | 0.47841 | 9.88234 |
September | 485.00000 | 27.00037 | 32.66500 | 0.28354 | 6.84176 |
October | 502.00000 | 27.00003 | 27.21235 | 0.89784 | 22.12954 |
November | 489.00000 | 27.00002 | 17.95761 | 0.81328 | 19.10366 |
December | 497.00000 | 27.00000 | 11.46662 | 0.70892 | 15.69069 |
Annual Sum or Average | 5943.00000 | 27.00005 | 23.43816 | 0.60131 | 13.73421 |
Minimum of Months | 454.00000 | 26.99101 | 11.11529 | 0.27758 | 6.82449 |
Maximum of Months | 514.00000 | 27.00715 | 36.11846 | 0.90516 | 22.40928 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.17367 | 10.99342 | 0.28818 | 8.02435 |
February | 454.00000 | 27.00000 | 11.46685 | 0.51651 | 10.82114 |
March | 514.00000 | 27.00000 | 14.95824 | 0.61568 | 13.23752 |
April | 485.00000 | 27.00163 | 18.08076 | 0.73260 | 16.52295 |
May | 508.00000 | 27.00025 | 29.09261 | 0.17133 | 5.98260 |
June | 496.00000 | 27.00093 | 34.54528 | 0.26211 | 6.66542 |
July | 497.00000 | 27.00082 | 36.15230 | 0.32181 | 7.31442 |
August | 514.00000 | 27.00043 | 35.47130 | 0.30531 | 7.12767 |
September | 485.00000 | 27.00023 | 32.74669 | 0.15165 | 5.73974 |
October | 502.00000 | 27.00003 | 27.19735 | 0.74758 | 16.94961 |
November | 489.00000 | 27.00002 | 17.93420 | 0.61028 | 13.06783 |
December | 497.00000 | 27.00000 | 11.45415 | 0.49232 | 10.25962 |
Annual Sum or Average | 5943.00000 | 26.93056 | 23.43825 | 0.43358 | 10.12696 |
Minimum of Months | 454.00000 | 26.17367 | 10.99342 | 0.15165 | 5.73974 |
Maximum of Months | 514.00000 | 27.00163 | 36.15230 | 0.74758 | 16.94961 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 25.10277 | 11.01567 | 0.02978 | 8.02170 |
February | 454.00000 | 26.99409 | 11.46699 | 0.44415 | 9.49947 |
March | 514.00000 | 27.00000 | 14.96139 | 0.54316 | 11.59204 |
April | 485.00000 | 27.00078 | 18.08540 | 0.67199 | 14.90050 |
May | 508.00000 | 26.99976 | 29.09873 | 0.14190 | 6.04039 |
June | 496.00000 | 27.00093 | 34.56631 | 0.25052 | 6.70605 |
July | 497.00000 | 27.00082 | 36.16546 | 0.31740 | 7.37383 |
August | 514.00000 | 27.00045 | 35.49015 | 0.29082 | 7.06033 |
September | 485.00000 | 27.00021 | 32.80873 | 0.10307 | 5.64285 |
October | 502.00000 | 27.00003 | 27.21446 | 0.67614 | 14.92094 |
November | 489.00000 | 27.00002 | 17.94618 | 0.52928 | 11.25283 |
December | 497.00000 | 27.00000 | 11.45867 | 0.42720 | 9.10831 |
Annual Sum or Average | 5943.00000 | 26.83954 | 23.45368 | 0.36780 | 9.33363 |
Minimum of Months | 454.00000 | 25.10277 | 11.01567 | 0.02978 | 5.64285 |
Maximum of Months | 514.00000 | 27.00093 | 36.16546 | 0.67614 | 14.92094 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99999 | 30.00035 | 0.98924 | 25.69792 |
February | 454.00000 | 27.00014 | 29.70493 | 1.18063 | 34.32013 |
March | 514.00000 | 27.00009 | 25.25884 | 1.30857 | 40.72306 |
April | 485.00000 | 27.00016 | 21.03782 | 1.45554 | 48.49779 |
May | 508.00000 | 27.00019 | 31.65301 | 0.56719 | 11.81746 |
June | 496.00000 | 27.00146 | 39.45516 | 0.85535 | 20.59886 |
July | 497.00000 | 27.07827 | 42.65885 | 1.12127 | 31.65073 |
August | 514.00000 | 27.26572 | 39.12595 | 1.34344 | 42.49249 |
September | 485.00000 | 26.99999 | 33.77052 | 0.62048 | 13.22359 |
October | 502.00000 | 27.00015 | 30.02111 | 1.28154 | 39.32917 |
November | 489.00000 | 27.00011 | 25.53815 | 1.36256 | 43.53919 |
December | 497.00000 | 27.00008 | 22.07789 | 1.40714 | 45.89899 |
Annual Sum or Average | 5943.00000 | 27.02972 | 30.89424 | 1.12422 | 33.14585 |
Minimum of Months | 454.00000 | 26.99999 | 21.03782 | 0.56719 | 11.81746 |
Maximum of Months | 514.00000 | 27.26572 | 42.65885 | 1.45554 | 48.49779 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.49961 | 15.18958 | 0.26272 | 7.16830 |
February | 454.00000 | 24.76771 | 15.32290 | 0.34447 | 8.96990 |
March | 514.00000 | 25.74776 | 34.14433 | 0.72534 | 23.33425 |
April | 485.00000 | 29.93987 | 99.99650 | 2.29409 | 87.76546 |
May | 508.00000 | 30.04373 | 99.99670 | 1.93650 | 73.54308 |
June | 496.00000 | 30.34196 | 99.99813 | 2.05260 | 78.73693 |
July | 497.00000 | 30.63760 | 99.99662 | 2.16936 | 83.41322 |
August | 514.00000 | 30.89341 | 99.99658 | 2.26880 | 86.96600 |
September | 485.00000 | 30.54573 | 99.99833 | 2.13312 | 82.06170 |
October | 502.00000 | 30.34395 | 99.99785 | 2.41152 | 91.12736 |
November | 489.00000 | 29.20915 | 84.41171 | 2.00100 | 74.87736 |
December | 497.00000 | 25.15589 | 20.98377 | 0.48275 | 13.82630 |
Annual Sum or Average | 5943.00000 | 28.52929 | 72.77950 | 1.59573 | 59.53790 |
Minimum of Months | 454.00000 | 24.49961 | 15.18958 | 0.26272 | 7.16830 |
Maximum of Months | 514.00000 | 30.89341 | 99.99833 | 2.41152 | 91.12736 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.57052 | 15.63994 | 0.05016 | 5.50822 |
February | 454.00000 | 23.96417 | 14.89667 | 0.16255 | 5.78443 |
March | 514.00000 | 24.16263 | 16.63092 | 0.25329 | 6.55454 |
April | 485.00000 | 24.50135 | 16.51490 | 0.40654 | 9.03319 |
May | 508.00000 | 24.45496 | 31.11113 | -0.3187 | 8.05894 |
June | 496.00000 | 24.42187 | 43.56069 | -0.2190 | 6.86545 |
July | 497.00000 | 24.54435 | 49.41496 | -0.1248 | 6.39377 |
August | 514.00000 | 24.43844 | 48.67129 | -0.1515 | 6.30717 |
September | 485.00000 | 24.49729 | 36.68463 | -0.2618 | 7.55045 |
October | 502.00000 | 24.56211 | 26.23586 | 0.48140 | 10.47653 |
November | 489.00000 | 24.55655 | 17.75163 | 0.39322 | 8.87144 |
December | 497.00000 | 24.11622 | 14.95742 | 0.20099 | 6.06599 |
Annual Sum or Average | 5943.00000 | 24.31708 | 27.80347 | 0.07115 | 7.29166 |
Minimum of Months | 454.00000 | 23.57052 | 14.89667 | -0.3187 | 5.50822 |
Maximum of Months | 514.00000 | 24.56211 | 49.41496 | 0.48140 | 10.47653 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.50438 | 16.82927 | -0.4708 | 11.64563 |
February | 454.00000 | 22.25976 | 17.74795 | -0.2678 | 7.75752 |
March | 514.00000 | 22.99488 | 20.31456 | -0.0604 | 6.09341 |
April | 485.00000 | 23.71828 | 20.06369 | 0.13475 | 5.73599 |
May | 508.00000 | 24.10833 | 33.20951 | -0.5422 | 11.92245 |
June | 496.00000 | 24.12426 | 46.24699 | -0.4298 | 9.26165 |
July | 497.00000 | 24.21663 | 53.05956 | -0.3482 | 7.87020 |
August | 514.00000 | 24.11993 | 52.67034 | -0.3865 | 8.44293 |
September | 485.00000 | 24.02685 | 39.45128 | -0.5354 | 11.52976 |
October | 502.00000 | 23.65322 | 31.52123 | 0.19053 | 6.16343 |
November | 489.00000 | 22.97039 | 23.63509 | -0.0537 | 6.26846 |
December | 497.00000 | 21.69879 | 18.41688 | -0.4046 | 10.01428 |
Annual Sum or Average | 5943.00000 | 23.29019 | 31.22982 | -0.2651 | 8.56670 |
Minimum of Months | 454.00000 | 21.50438 | 16.82927 | -0.5422 | 5.73599 |
Maximum of Months | 514.00000 | 24.21663 | 53.05956 | 0.19053 | 11.92245 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.44568 | 17.79242 | -0.7615 | 20.17170 |
February | 454.00000 | 20.89078 | 19.21436 | -0.6274 | 15.88346 |
March | 514.00000 | 21.59033 | 22.46276 | -0.4171 | 11.04272 |
April | 485.00000 | 22.66402 | 22.03836 | -0.1303 | 7.27717 |
May | 508.00000 | 23.82028 | 33.76280 | -0.6480 | 15.73499 |
June | 496.00000 | 23.96746 | 46.91447 | -0.4785 | 10.63478 |
July | 497.00000 | 24.14046 | 53.41087 | -0.3690 | 8.38694 |
August | 514.00000 | 24.00082 | 53.35861 | -0.4277 | 9.35064 |
September | 485.00000 | 23.59218 | 41.04036 | -0.6992 | 16.51662 |
October | 502.00000 | 22.35423 | 35.10225 | -0.1330 | 7.26140 |
November | 489.00000 | 21.33321 | 26.02549 | -0.4651 | 12.59775 |
December | 497.00000 | 20.53770 | 20.17314 | -0.7181 | 18.81103 |
Annual Sum or Average | 5943.00000 | 22.45728 | 32.73778 | -0.4887 | 12.77984 |
Minimum of Months | 454.00000 | 20.44568 | 17.79242 | -0.7615 | 7.26140 |
Maximum of Months | 514.00000 | 24.14046 | 53.41087 | -0.1303 | 20.17170 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.62310 | 16.04299 | -0.7183 | 17.21183 |
February | 454.00000 | 21.30648 | 15.93761 | -0.5124 | 11.75753 |
March | 514.00000 | 22.21364 | 17.93733 | -0.2557 | 8.18545 |
April | 485.00000 | 23.98981 | 16.81418 | 0.21586 | 6.59342 |
May | 508.00000 | 24.36711 | 30.73390 | -0.3719 | 9.05714 |
June | 496.00000 | 24.42576 | 43.03046 | -0.2034 | 6.96836 |
July | 497.00000 | 24.58521 | 48.80757 | -0.0900 | 6.66463 |
August | 514.00000 | 24.39992 | 48.35699 | -0.1847 | 6.65955 |
September | 485.00000 | 24.32305 | 36.73525 | -0.3887 | 9.21724 |
October | 502.00000 | 23.99404 | 26.88802 | 0.26939 | 6.95434 |
November | 489.00000 | 23.08745 | 19.07964 | -0.0286 | 6.53669 |
December | 497.00000 | 21.00160 | 16.18781 | -0.5868 | 13.82124 |
Annual Sum or Average | 5943.00000 | 23.20413 | 28.17136 | -0.2370 | 9.12049 |
Minimum of Months | 454.00000 | 20.62310 | 15.93761 | -0.7183 | 6.53669 |
Maximum of Months | 514.00000 | 24.58521 | 48.80757 | 0.26939 | 17.21183 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.65824 | 15.04150 | -0.6974 | 16.46289 |
February | 454.00000 | 21.42108 | 14.86377 | -0.4636 | 11.13855 |
March | 514.00000 | 22.18634 | 16.95884 | -0.2205 | 8.65471 |
April | 485.00000 | 23.76859 | 16.58590 | 0.24883 | 7.96809 |
May | 508.00000 | 24.36998 | 30.54113 | -0.2643 | 8.60436 |
June | 496.00000 | 24.40008 | 42.96687 | -0.0991 | 7.29792 |
July | 497.00000 | 24.47365 | 48.91920 | -0.0109 | 6.81097 |
August | 514.00000 | 24.33638 | 48.43201 | -0.1266 | 7.33881 |
September | 485.00000 | 24.19405 | 36.76246 | -0.3411 | 9.60337 |
October | 502.00000 | 23.66680 | 26.93749 | 0.23303 | 7.46658 |
November | 489.00000 | 22.55687 | 18.81460 | -0.1237 | 7.11122 |
December | 497.00000 | 20.81115 | 15.37688 | -0.6325 | 14.58591 |
Annual Sum or Average | 5943.00000 | 23.08096 | 27.81229 | -0.2070 | 9.40851 |
Minimum of Months | 454.00000 | 20.65824 | 14.86377 | -0.6974 | 6.81097 |
Maximum of Months | 514.00000 | 24.47365 | 48.91920 | 0.24883 | 16.46289 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.32670 | 14.72215 | -0.5021 | 14.63290 |
February | 454.00000 | 22.22185 | 14.23820 | -0.2325 | 10.84532 |
March | 514.00000 | 22.64775 | 16.58805 | -0.0910 | 9.51868 |
April | 485.00000 | 23.75898 | 16.62418 | 0.24020 | 8.49255 |
May | 508.00000 | 24.25709 | 30.72981 | -0.3433 | 9.69778 |
June | 496.00000 | 24.33073 | 43.17634 | -0.2005 | 7.36607 |
July | 497.00000 | 24.49199 | 48.91544 | -0.0635 | 6.91207 |
August | 514.00000 | 24.38154 | 48.27786 | -0.1090 | 7.26876 |
September | 485.00000 | 24.27032 | 36.60844 | -0.2987 | 10.19012 |
October | 502.00000 | 23.71648 | 26.87294 | 0.26211 | 8.98646 |
November | 489.00000 | 22.77640 | 18.67133 | -0.0599 | 8.17467 |
December | 497.00000 | 21.41763 | 15.23175 | -0.4676 | 13.04718 |
Annual Sum or Average | 5943.00000 | 23.30692 | 27.68659 | -0.1555 | 9.58569 |
Minimum of Months | 454.00000 | 21.32670 | 14.23820 | -0.5021 | 6.91207 |
Maximum of Months | 514.00000 | 24.49199 | 48.91544 | 0.26211 | 14.63290 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.04567 | 14.55054 | -0.5719 | 13.27806 |
February | 454.00000 | 22.09637 | 14.04082 | -0.2619 | 8.64853 |
March | 514.00000 | 23.06231 | 15.90265 | 0.02972 | 7.24314 |
April | 485.00000 | 24.20785 | 16.06295 | 0.38338 | 9.40602 |
May | 508.00000 | 24.23618 | 30.69641 | -0.2958 | 9.39941 |
June | 496.00000 | 24.38042 | 43.01205 | -0.1025 | 6.97267 |
July | 497.00000 | 24.57739 | 48.65227 | 0.06098 | 7.44324 |
August | 514.00000 | 24.46554 | 47.96371 | -0.0026 | 7.10386 |
September | 485.00000 | 24.03757 | 37.10744 | -0.3887 | 10.71228 |
October | 502.00000 | 23.72122 | 26.64354 | 0.26903 | 7.69210 |
November | 489.00000 | 23.17830 | 17.99940 | 0.04654 | 6.36185 |
December | 497.00000 | 22.00238 | 14.23989 | -0.2917 | 8.29486 |
Annual Sum or Average | 5943.00000 | 23.42623 | 27.36930 | -0.0930 | 8.53968 |
Minimum of Months | 454.00000 | 21.04567 | 14.04082 | -0.5719 | 6.36185 |
Maximum of Months | 514.00000 | 24.57739 | 48.65227 | 0.38338 | 13.27806 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.78843 | 16.18555 | -1.0290 | 29.55877 |
February | 454.00000 | 20.13946 | 17.59734 | -0.8774 | 23.21752 |
March | 514.00000 | 20.74348 | 20.82743 | -0.6618 | 16.17525 |
April | 485.00000 | 22.03917 | 20.71775 | -0.2853 | 8.75511 |
May | 508.00000 | 23.80851 | 32.57408 | -0.6378 | 15.93974 |
June | 496.00000 | 24.14585 | 45.15796 | -0.3849 | 9.00813 |
July | 497.00000 | 24.32834 | 52.04322 | -0.2651 | 7.41405 |
August | 514.00000 | 24.00088 | 52.21428 | -0.4216 | 9.50907 |
September | 485.00000 | 23.32669 | 40.30244 | -0.7946 | 20.34642 |
October | 502.00000 | 21.74011 | 32.67013 | -0.2912 | 8.30809 |
November | 489.00000 | 20.51078 | 24.22615 | -0.6909 | 17.45358 |
December | 497.00000 | 19.87673 | 18.09121 | -0.9807 | 27.59614 |
Annual Sum or Average | 5943.00000 | 22.05324 | 31.17993 | -0.6081 | 16.04681 |
Minimum of Months | 454.00000 | 19.78843 | 16.18555 | -1.0290 | 7.41405 |
Maximum of Months | 514.00000 | 24.32834 | 52.21428 | -0.2651 | 29.55877 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.68851 | 15.12937 | -1.0292 | 29.77308 |
February | 385.00000 | 20.23760 | 16.24900 | -0.8210 | 21.23888 |
March | 433.00000 | 21.15387 | 18.91950 | -0.5282 | 13.71269 |
April | 410.00000 | 22.41967 | 18.94684 | -0.1253 | 9.17740 |
May | 430.00000 | 23.85311 | 31.68659 | -0.5171 | 15.14207 |
June | 418.00000 | 24.12606 | 44.93565 | -0.2679 | 10.07013 |
July | 422.00000 | 24.32417 | 51.62024 | -0.1436 | 8.12133 |
August | 433.00000 | 23.86798 | 52.07423 | -0.3638 | 11.60623 |
September | 410.00000 | 23.05910 | 40.04733 | -0.7885 | 22.92696 |
October | 427.00000 | 21.61707 | 31.22394 | -0.2949 | 9.26077 |
November | 417.00000 | 20.44055 | 22.70498 | -0.6986 | 17.54538 |
December | 422.00000 | 19.74918 | 16.97476 | -0.9955 | 28.31682 |
Annual Sum or Average | 5034.00000 | 22.05680 | 30.15495 | -0.5460 | 16.36552 |
Minimum of Months | 385.00000 | 19.68851 | 15.12937 | -1.0292 | 8.12133 |
Maximum of Months | 433.00000 | 24.32417 | 52.07423 | -0.1253 | 29.77308 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.67867 | 14.97519 | -0.7025 | 21.13950 |
February | 454.00000 | 21.65870 | 15.51999 | -0.3909 | 14.80656 |
March | 514.00000 | 22.09215 | 18.54845 | -0.2438 | 12.19795 |
April | 485.00000 | 22.81447 | 18.81595 | -0.0086 | 9.51605 |
May | 508.00000 | 23.83320 | 32.06837 | -0.5301 | 14.85411 |
June | 496.00000 | 23.99614 | 45.31869 | -0.3670 | 10.32156 |
July | 497.00000 | 24.27313 | 51.84682 | -0.1960 | 8.13284 |
August | 514.00000 | 24.05966 | 51.63776 | -0.2802 | 9.83863 |
September | 485.00000 | 23.66788 | 38.77730 | -0.5375 | 17.18218 |
October | 502.00000 | 22.55296 | 30.19383 | -0.0283 | 9.80531 |
November | 489.00000 | 21.44058 | 22.43221 | -0.4085 | 13.37835 |
December | 497.00000 | 20.58565 | 17.03124 | -0.7297 | 20.69074 |
Annual Sum or Average | 5943.00000 | 22.64680 | 29.90071 | -0.3684 | 13.47209 |
Minimum of Months | 454.00000 | 20.58565 | 14.97519 | -0.7297 | 8.13284 |
Maximum of Months | 514.00000 | 24.27313 | 51.84682 | -0.0086 | 21.13950 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.04111 | 15.13128 | -0.9276 | 25.76573 |
February | 454.00000 | 20.65463 | 16.15371 | -0.7002 | 18.16028 |
March | 514.00000 | 21.30274 | 19.11067 | -0.4662 | 13.10569 |
April | 485.00000 | 22.33649 | 19.31241 | -0.1281 | 9.14367 |
May | 508.00000 | 23.76145 | 32.04390 | -0.5094 | 15.37725 |
June | 496.00000 | 23.99144 | 45.32064 | -0.3077 | 10.07695 |
July | 497.00000 | 24.33371 | 51.65860 | -0.1197 | 8.22686 |
August | 514.00000 | 23.95177 | 51.91504 | -0.3000 | 10.30235 |
September | 485.00000 | 23.14632 | 39.89663 | -0.7377 | 21.16179 |
October | 502.00000 | 21.80145 | 31.31054 | -0.2260 | 8.36769 |
November | 489.00000 | 20.72626 | 23.01815 | -0.6079 | 14.85961 |
December | 497.00000 | 20.07246 | 17.03455 | -0.8941 | 24.06955 |
Annual Sum or Average | 5943.00000 | 22.19043 | 30.29192 | -0.4919 | 14.84723 |
Minimum of Months | 454.00000 | 20.04111 | 15.13128 | -0.9276 | 8.22686 |
Maximum of Months | 514.00000 | 24.33371 | 51.91504 | -0.1197 | 25.76573 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.56975 | 16.41888 | -1.1379 | 34.34255 |
February | 454.00000 | 19.79855 | 18.30570 | -1.0151 | 29.24039 |
March | 514.00000 | 20.32974 | 22.10180 | -0.8122 | 21.35969 |
April | 485.00000 | 21.32113 | 21.96046 | -0.4803 | 13.13891 |
May | 508.00000 | 23.44705 | 33.07815 | -0.7649 | 21.33509 |
June | 496.00000 | 23.97327 | 45.78404 | -0.4409 | 10.84995 |
July | 497.00000 | 24.22618 | 52.47849 | -0.2955 | 8.32391 |
August | 514.00000 | 23.81885 | 52.98887 | -0.4828 | 11.40121 |
September | 485.00000 | 22.76352 | 41.86214 | -0.9936 | 28.69430 |
October | 502.00000 | 20.88467 | 34.54848 | -0.5256 | 13.49414 |
November | 489.00000 | 19.97483 | 25.72655 | -0.8726 | 24.36678 |
December | 497.00000 | 19.64145 | 19.00878 | -1.0938 | 32.45869 |
Annual Sum or Average | 5943.00000 | 21.66277 | 32.15026 | -0.7405 | 20.66658 |
Minimum of Months | 454.00000 | 19.56975 | 16.41888 | -1.1379 | 8.32391 |
Maximum of Months | 514.00000 | 24.22618 | 52.98887 | -0.2955 | 34.34255 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.75364 | 15.82710 | -1.0684 | 31.40185 |
February | 454.00000 | 19.99728 | 17.49603 | -0.9193 | 25.67274 |
March | 514.00000 | 20.85116 | 20.67606 | -0.6353 | 16.97691 |
April | 485.00000 | 22.08527 | 20.18481 | -0.2224 | 11.15831 |
May | 508.00000 | 23.66030 | 32.28861 | -0.5724 | 16.91301 |
June | 496.00000 | 23.99226 | 45.43047 | -0.2903 | 10.60499 |
July | 497.00000 | 24.20720 | 51.99129 | -0.1513 | 8.50524 |
August | 514.00000 | 23.76027 | 52.72879 | -0.3811 | 12.18373 |
September | 485.00000 | 22.79284 | 41.05207 | -0.8830 | 26.62238 |
October | 502.00000 | 21.13139 | 33.08366 | -0.4418 | 12.57914 |
November | 489.00000 | 20.07716 | 24.84513 | -0.8303 | 22.79016 |
December | 497.00000 | 19.76739 | 18.39747 | -1.0477 | 30.51903 |
Annual Sum or Average | 5943.00000 | 21.85628 | 31.29648 | -0.6177 | 18.75104 |
Minimum of Months | 454.00000 | 19.75364 | 15.82710 | -1.0684 | 8.50524 |
Maximum of Months | 514.00000 | 24.20720 | 52.72879 | -0.1513 | 31.40185 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.32512 | 15.58549 | -0.8365 | 25.83086 |
February | 454.00000 | 21.11832 | 16.56656 | -0.5662 | 19.54448 |
March | 514.00000 | 21.63638 | 19.93949 | -0.4012 | 15.27721 |
April | 485.00000 | 22.29253 | 19.95760 | -0.1635 | 11.86589 |
May | 508.00000 | 23.55821 | 32.46783 | -0.6321 | 18.92889 |
June | 496.00000 | 23.79375 | 46.03201 | -0.4304 | 12.71818 |
July | 497.00000 | 24.14145 | 52.39485 | -0.2338 | 9.42512 |
August | 514.00000 | 23.88425 | 52.36400 | -0.3385 | 11.66913 |
September | 485.00000 | 23.25583 | 39.96735 | -0.6929 | 22.93537 |
October | 502.00000 | 21.82405 | 31.92561 | -0.2353 | 12.80388 |
November | 489.00000 | 20.73546 | 24.17937 | -0.6206 | 19.00819 |
December | 497.00000 | 20.22218 | 18.26286 | -0.8676 | 25.52848 |
Annual Sum or Average | 5943.00000 | 22.24345 | 30.93816 | -0.5008 | 17.09371 |
Minimum of Months | 454.00000 | 20.22218 | 15.58549 | -0.8676 | 9.42512 |
Maximum of Months | 514.00000 | 24.14145 | 52.39485 | -0.1635 | 25.83086 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.83848 | 15.66437 | -1.0299 | 30.04697 |
February | 454.00000 | 20.30125 | 17.08920 | -0.8278 | 23.01622 |
March | 514.00000 | 20.94775 | 20.46829 | -0.5932 | 16.73393 |
April | 485.00000 | 21.87049 | 20.34307 | -0.2649 | 11.69791 |
May | 508.00000 | 23.48347 | 32.44031 | -0.6082 | 19.44069 |
June | 496.00000 | 23.80696 | 45.96404 | -0.3644 | 12.17857 |
July | 497.00000 | 24.21792 | 52.14251 | -0.1525 | 9.24730 |
August | 514.00000 | 23.76922 | 52.64868 | -0.3588 | 12.11850 |
September | 485.00000 | 22.73614 | 41.05676 | -0.8882 | 27.29188 |
October | 502.00000 | 21.26271 | 32.73601 | -0.3866 | 11.49558 |
November | 489.00000 | 20.24985 | 24.53526 | -0.7636 | 20.52500 |
December | 497.00000 | 19.84644 | 18.23580 | -0.9949 | 28.40300 |
Annual Sum or Average | 5943.00000 | 21.87587 | 31.24182 | -0.6005 | 18.46025 |
Minimum of Months | 454.00000 | 19.83848 | 15.66437 | -1.0299 | 9.24730 |
Maximum of Months | 514.00000 | 24.21792 | 52.64868 | -0.1525 | 30.04697 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 48006847.19 | 766.75 | 26-JAN-11:00 | 32.39 | 0.468280E+09 | 0.00 | 0.516287E+09 | 0.42 | 9.84 | 23-JAN-19:20 | 0.00 | 0.00 |
February | 73746203.76 | 1335.72 | 24-FEB-09:20 | 42.90 | 0.719302E+09 | 0.00 | 0.793048E+09 | 0.62 | 9.84 | 11-FEB-12:10 | 0.00 | 0.00 |
March | 73765665.77 | 1777.02 | 14-MAR-11:08 | 39.65 | 0.719581E+09 | 0.00 | 0.793347E+09 | 0.52 | 9.84 | 16-MAR-07:30 | 0.00 | 0.00 |
April | 0.542299E+10 | 78263.50 | 23-APR-16:13 | 73.43 | 0.530874E+11 | 0.00 | 0.585104E+11 | 1.00 | 10.00 | 23-APR-13:38 | 0.00 | 0.00 |
May | 0.446990E+11 | 198960.82 | 25-MAY-16:50 | 267.79 | 0.394123E+12 | 0.00 | 0.438822E+12 | 3.39 | 10.00 | 21-MAY-16:33 | 0.00 | 0.00 |
June | 0.955859E+11 | 202983.16 | 30-JUN-17:30 | 428.96 | 0.818469E+12 | 0.00 | 0.914055E+12 | 5.45 | 10.01 | 23-JUN-04:12 | 0.00 | 0.00 |
July | 0.121918E+12 | 217533.93 | 05-JUL-11:50 | 527.01 | 0.101955E+13 | 0.00 | 0.114146E+13 | 6.41 | 10.00 | 15-JUL-05:03 | 0.00 | 0.00 |
August | 0.906237E+11 | 199284.16 | 30-AUG-17:20 | 505.63 | 0.787229E+12 | 0.00 | 0.877852E+12 | 6.34 | 10.02 | 31-AUG-04:12 | 0.00 | 0.00 |
September | 0.221822E+11 | 171091.13 | 01-SEP-09:50 | 209.77 | 0.207346E+12 | 0.00 | 0.229529E+12 | 2.81 | 10.02 | 01-SEP-04:12 | 0.00 | 0.00 |
October | 0.433416E+10 | 104011.52 | 19-OCT-14:20 | 54.13 | 0.417304E+11 | 0.00 | 0.460646E+11 | 0.71 | 10.00 | 20-OCT-15:20 | 0.00 | 0.00 |
November | 0.395705E+09 | 21187.98 | 01-NOV-15:00 | 27.12 | 0.384847E+10 | 0.00 | 0.424418E+10 | 0.37 | 9.83 | 08-NOV-06:30 | 0.00 | 0.00 |
December | 97115911.02 | 3120.27 | 01-DEC-07:30 | 51.09 | 0.947528E+09 | 0.00 | 0.104464E+10 | 0.67 | 9.84 | 09-DEC-12:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.385455E+12 | 2259.88 | 0.332823E+13 | 0.00 | 0.371369E+13 | 2.41 | 0.00 | 0.00 | ||||
Minimum of Months | 48006847.19 | 766.75 | 27.12 | 0.468280E+09 | 0.00 | 0.516287E+09 | 0.37 | 9.83 | 0.00 | 0.00 | ||
Maximum of Months | 0.121918E+12 | 217533.93 | 527.01 | 0.101955E+13 | 0.00 | 0.114146E+13 | 6.41 | 10.02 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.652204E+10 | 119704.28 | 17-MAY-12:25 | 23.83 | 0.593322E+11 | 0.00 | 0.658543E+11 | 0.29 | 10.53 | 16-MAY-16:10 | 0.00 | 0.00 |
June | 0.206897E+11 | 170280.19 | 19-JUN-15:20 | 61.56 | 0.172663E+12 | 0.00 | 0.193352E+12 | 0.73 | 10.68 | 08-JUN-12:40 | 0.00 | 0.00 |
July | 0.334665E+11 | 217533.93 | 05-JUL-11:50 | 95.71 | 0.277322E+12 | 0.00 | 0.310789E+12 | 1.10 | 10.38 | 10-JUL-12:20 | 0.00 | 0.00 |
August | 0.221765E+11 | 178905.93 | 31-AUG-12:50 | 68.33 | 0.190261E+12 | 0.00 | 0.212437E+12 | 0.80 | 10.44 | 25-AUG-10:00 | 0.00 | 0.00 |
September | 0.214769E+10 | 99488.87 | 01-SEP-11:00 | 7.00 | 0.191042E+11 | 0.00 | 0.212518E+11 | 0.09 | 10.27 | 01-SEP-09:00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.850025E+11 | 256.43 | 0.718682E+12 | 0.00 | 0.803685E+12 | 0.25 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.334665E+11 | 217533.93 | 95.71 | 0.277322E+12 | 0.00 | 0.310789E+12 | 1.10 | 10.68 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.216567E+09 | 744.00 | 644.27 | 27-JAN-16:00 | 57035.09 | 27-JAN-16:10 | 18.53 | 18.33 | 15.81 |
February | 0.100281E+10 | 672.00 | 2477.74 | 04-FEB-16:55 | 147879.44 | 08-FEB-17:35 | 19.15 | 18.33 | 15.87 |
March | 0.231435E+10 | 744.00 | 3195.09 | 21-MAR-10:50 | 252731.47 | 15-MAR-21:02 | 19.79 | 18.33 | 16.01 |
April | 0.125040E+11 | 720.00 | 49248.27 | 12-APR-13:10 | 672131.79 | 23-APR-16:01 | 20.89 | 18.51 | 16.08 |
May | 0.367882E+11 | 744.00 | 49248.27 | 02-MAY-14:50 | 261724.56 | 25-MAY-13:20 | 20.30 | 19.45 | 16.19 |
June | 0.710265E+11 | 720.00 | 49248.27 | 01-JUN-07:50 | 718346.63 | 30-JUN-01:40 | 23.86 | 21.27 | 16.19 |
July | 0.954821E+11 | 744.00 | 49248.27 | 01-JUL-08:70 | 827797.70 | 15-JUL-14:10 | 28.97 | 23.05 | 16.19 |
August | 0.923658E+11 | 744.00 | 49248.27 | 01-AUG-00:03 | 833862.04 | 08-AUG-15:10 | 29.27 | 21.96 | 16.19 |
September | 0.213220E+11 | 720.00 | 49248.27 | 01-SEP-00:03 | 224109.63 | 01-SEP-15:10 | 19.24 | 18.63 | 16.19 |
October | 0.638951E+10 | 744.00 | 49248.27 | 19-OCT-12:00 | 179395.36 | 19-OCT-15:00 | 19.37 | 18.37 | 16.15 |
November | 0.342154E+10 | 720.00 | 49248.27 | 01-NOV-12:40 | 184577.61 | 17-NOV-17:05 | 19.75 | 18.33 | 16.08 |
December | 0.198340E+10 | 744.00 | 2187.87 | 05-DEC-17:00 | 307669.71 | 12-DEC-22:02 | 20.06 | 18.33 | 16.03 |
Annual Sum or Average | 0.344817E+12 | 8760.00 | 21.63 | 19.42 | 16.08 | ||||
Minimum of Months | 0.216567E+09 | 672.00 | 644.27 | 57035.09 | 18.53 | 18.33 | 15.81 | ||
Maximum of Months | 0.954821E+11 | 744.00 | 49248.27 | 833862.04 | 29.27 | 23.05 | 16.19 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 242292.28 | 28-JAN-11:00 | 20.88 | 20.87 | 0.16 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 242265.10 | 06-FEB-20:50 | 20.91 | 20.91 | 0.20 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 242290.50 | 07-MAR-20:50 | 20.89 | 20.89 | 0.34 |
April | 71873141.44 | 25.96 | 3852.55 | 23-APR-15:59 | 752450.98 | 13-APR-15:20 | 21.04 | 20.95 | 5.14 |
May | 0.422128E+10 | 193.38 | 19471.67 | 16-MAY-12:10 | 1486926.91 | 16-MAY-13:50 | 21.77 | 21.16 | 20.51 |
June | 0.123911E+11 | 370.85 | 19471.67 | 06-JUN-09:50 | 1426342.38 | 14-JUN-14:00 | 23.06 | 21.76 | 36.56 |
July | 0.195827E+11 | 458.91 | 19471.67 | 03-JUL-07:30 | 1569180.57 | 05-JUL-11:43 | 23.60 | 22.05 | 43.42 |
August | 0.127780E+11 | 387.69 | 19471.67 | 01-AUG-05:08 | 1410388.41 | 04-AUG-15:30 | 22.78 | 21.57 | 40.50 |
September | 0.132497E+10 | 142.32 | 19471.67 | 01-SEP-08:20 | 1321608.87 | 07-SEP-14:10 | 21.40 | 21.07 | 16.78 |
October | 60915542.57 | 28.48 | 2745.09 | 19-OCT-14:20 | 1001723.28 | 19-OCT-14:20 | 21.04 | 20.98 | 3.33 |
November | 5553316.55 | 5.17 | 372.56 | 01-NOV-15:00 | 242281.97 | 10-NOV-11:10 | 20.98 | 20.97 | 0.89 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 242289.74 | 27-DEC-16:40 | 20.91 | 20.91 | 0.28 |
Annual Sum or Average | 0.504364E+11 | 1612.76 | 21.61 | 21.18 | 14.11 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 242265.10 | 20.88 | 20.87 | 0.16 | ||
Maximum of Months | 0.195827E+11 | 458.91 | 19471.67 | 1569180.57 | 23.60 | 22.05 | 43.42 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 20.88 | 20.88 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 20.91 | 20.91 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 20.89 | 20.89 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 21.04 | 21.04 | 0.00 |
May | 0.147790E+10 | 21.08 | 19471.67 | 16-MAY-14:10 | 1160021.62 | 16-MAY-15:20 | 21.77 | 21.67 | 1.81 |
June | 0.528681E+10 | 75.85 | 19471.67 | 06-JUN-12:20 | 1340088.52 | 19-JUN-15:20 | 23.06 | 22.67 | 6.18 |
July | 0.899636E+10 | 128.34 | 19471.67 | 03-JUL-12:20 | 1569180.57 | 05-JUL-11:43 | 23.60 | 22.97 | 9.96 |
August | 0.558447E+10 | 79.67 | 19471.67 | 07-AUG-13:00 | 1344941.83 | 31-AUG-12:50 | 22.78 | 22.41 | 6.61 |
September | 0.490686E+09 | 7.00 | 19471.67 | 01-SEP-09:10 | 950747.81 | 01-SEP-11:00 | 21.40 | 21.37 | 0.64 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 21.04 | 21.04 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 20.98 | 20.98 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 20.91 | 20.91 | 0.00 |
Annual Sum or Average | 0.218362E+11 | 311.94 | 21.61 | 21.48 | 2.12 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.88 | 20.88 | 0.00 | ||
Maximum of Months | 0.899636E+10 | 128.34 | 19471.67 | 1569180.57 | 23.60 | 22.97 | 9.96 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.798950E+12 | 0.00 | 635.72 | 2231696.65 | 09-JAN-07:15 | 0.00 | 35.07 | 75.01 | 1.72 | 0.00 | 0.09 | 0.65 | 09-JAN-07:15 |
February | 0.355435E+12 | 0.00 | 521.07 | 2039571.54 | 27-FEB-05:01 | 0.00 | 31.66 | 70.31 | 0.80 | 0.00 | 0.04 | 0.60 | 27-FEB-05:01 |
March | 0.180754E+12 | 0.00 | 481.07 | 1880610.16 | 06-MAR-05:01 | 0.00 | 27.43 | 61.93 | 0.34 | 0.00 | 0.02 | 0.55 | 06-MAR-05:01 |
April | 0.340257E+11 | 0.00 | 239.87 | 1667562.64 | 04-APR-04:01 | 0.00 | 24.28 | 43.30 | 0.06 | 0.00 | 0.00 | 0.49 | 04-APR-04:01 |
May | 0.140484E+10 | 0.00 | 37.60 | 309660.33 | 01-MAY-05:03 | 0.00 | 24.34 | 27.21 | 0.00 | 0.00 | 0.00 | 0.09 | 01-MAY-05:03 |
June | 9327098.52 | 0.00 | 5.93 | 1588.59 | 10-JUN-05:10 | 0.00 | 23.25 | 23.74 | 0.00 | 0.00 | 0.00 | 0.00 | 10-JUN-05:10 |
July | 1717.43 | 0.00 | 0.17 | 2.86 | 17-JUL-20:00 | 0.00 | 23.21 | 23.23 | 0.00 | 0.00 | 0.00 | 0.00 | 17-JUL-20:00 |
August | 51582351.26 | 0.00 | 7.62 | 17490.87 | 19-AUG-05:10 | 0.00 | 23.01 | 23.61 | 0.00 | 0.00 | 0.00 | 0.01 | 19-AUG-05:10 |
September | 0.203023E+10 | 0.00 | 76.94 | 95237.26 | 23-SEP-06:10 | 0.00 | 22.31 | 28.78 | 0.00 | 0.00 | 0.00 | 0.03 | 23-SEP-06:10 |
October | 0.389055E+11 | 0.00 | 297.44 | 1618450.89 | 30-OCT-04:01 | 0.00 | 22.20 | 45.67 | 0.06 | 0.00 | 0.00 | 0.47 | 30-OCT-04:01 |
November | 0.167005E+12 | 0.00 | 485.37 | 2057984.80 | 27-NOV-05:01 | 0.00 | 26.16 | 63.15 | 0.32 | 0.00 | 0.02 | 0.60 | 27-NOV-05:01 |
December | 0.609485E+12 | 0.00 | 625.62 | 2166164.61 | 28-DEC-06:01 | 0.00 | 33.84 | 74.09 | 1.26 | 0.00 | 0.07 | 0.64 | 28-DEC-06:01 |
Annual Sum or Average | 0.218806E+13 | 0.00 | 3414.43 | 0.00 | 26.38 | 46.55 | 0.38 | 0.00 | 0.02 | ||||
Minimum of Months | 1717.43 | 0.00 | 0.17 | 2.86 | 0.00 | 22.20 | 23.23 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.798950E+12 | 0.00 | 635.72 | 2231696.65 | 0.00 | 35.07 | 75.01 | 1.72 | 0.00 | 0.09 | 0.65 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 18.53 | 18.53 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 19.15 | 19.15 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 19.79 | 19.79 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 20.89 | 20.89 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 20.30 | 20.30 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 23.86 | 23.86 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 28.97 | 28.97 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 29.27 | 29.27 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 19.24 | 19.24 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 19.37 | 19.37 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 19.75 | 19.75 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 20.06 | 20.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 21.63 | 21.63 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.53 | 18.53 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.27 | 29.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 11185621.17 | 0.00 | 27.06 | 11185621.17 | 0.00 | 0.00 | 0.00 | 0.00 | 2364.52 | 25-JAN-13:10 | 2364.52 | 25-JAN-13:10 | 0.00 | 0.00 | 0.00 |
February | 9643875.26 | 0.00 | 27.14 | 9643875.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2763.93 | 27-FEB-15:10 | 2763.93 | 27-FEB-15:10 | 0.00 | 0.00 | 0.00 |
March | 15984459.23 | 0.00 | 22.97 | 15984459.23 | 0.00 | 0.00 | 0.00 | 0.00 | 18373.14 | 06-MAR-16:55 | 18373.14 | 06-MAR-16:55 | 0.00 | 0.00 | 0.00 |
April | 0.788600E+10 | 0.00 | 64.63 | 0.788600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 159072.26 | 23-APR-16:21 | 159072.26 | 23-APR-16:21 | 0.00 | 0.00 | 0.00 |
May | 0.550303E+11 | 0.00 | 256.90 | 0.535118E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 195117.58 | 26-MAY-11:00 | 150141.33 | 18-MAY-14:00 | 0.00 | 0.00 | 0.00 |
June | 0.124916E+12 | 0.00 | 418.70 | 0.992782E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 307868.29 | 30-JUN-03:02 | 164779.90 | 30-JUN-04:03 | 0.00 | 0.00 | 0.00 |
July | 0.169570E+12 | 0.00 | 509.21 | 0.126951E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 322647.32 | 23-JUL-09:11 | 181627.47 | 23-JUL-15:51 | 0.00 | 0.00 | 0.00 |
August | 0.142467E+12 | 0.00 | 491.60 | 0.103219E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 296635.03 | 31-AUG-12:45 | 166142.63 | 08-AUG-14:20 | 0.00 | 0.00 | 0.00 |
September | 0.303812E+11 | 0.00 | 199.02 | 0.264661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 207236.86 | 01-SEP-11:00 | 161133.91 | 01-SEP-15:30 | 0.00 | 0.00 | 0.00 |
October | 0.548083E+10 | 0.00 | 44.12 | 0.548083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 109122.00 | 19-OCT-15:00 | 109122.00 | 19-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.711087E+09 | 0.00 | 13.02 | 0.711087E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39498.87 | 01-NOV-15:00 | 39498.87 | 01-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 15831256.88 | 0.00 | 27.67 | 15831256.88 | 0.00 | 0.00 | 0.00 | 0.00 | 2931.58 | 15-DEC-08:10 | 2931.58 | 15-DEC-08:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.536495E+12 | 0.00 | 2102.03 | 0.423557E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 9643875.26 | 0.00 | 13.02 | 9643875.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2364.52 | 2364.52 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.169570E+12 | 0.00 | 509.21 | 0.126951E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 322647.32 | 181627.47 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 17473615.81 | 0.00 | 10.42 | 17473615.81 | 0.00 | 0.00 | 0.00 | 0.00 | 3964.12 | 26-JAN-11:50 | 3964.12 | 26-JAN-11:50 | 0.00 | 0.00 | 0.00 |
February | 31518254.19 | 0.00 | 24.39 | 31518254.19 | 0.00 | 0.00 | 0.00 | 0.00 | 5664.40 | 10-FEB-11:00 | 5664.40 | 10-FEB-11:00 | 0.00 | 0.00 | 0.00 |
March | 25462051.29 | 0.00 | 17.83 | 25462051.29 | 0.00 | 0.00 | 0.00 | 0.00 | 22197.20 | 14-MAR-11:08 | 22197.20 | 14-MAR-11:08 | 0.00 | 0.00 | 0.00 |
April | 0.406221E+11 | 0.00 | 59.27 | 0.406221E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 944888.05 | 23-APR-16:12 | 944888.05 | 23-APR-16:12 | 0.00 | 0.00 | 0.00 |
May | 0.349254E+12 | 0.00 | 227.85 | 0.341876E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1276488.13 | 25-MAY-16:00 | 1173205.69 | 18-MAY-14:40 | 0.00 | 0.00 | 0.00 |
June | 0.764954E+12 | 0.00 | 366.39 | 0.626061E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1963690.47 | 29-JUN-04:12 | 1282530.43 | 30-JUN-05:03 | 0.00 | 0.00 | 0.00 |
July | 0.986641E+12 | 0.00 | 414.30 | 0.773749E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2546637.35 | 05-JUL-10:35 | 1221315.38 | 24-JUL-15:20 | 0.00 | 0.00 | 0.00 |
August | 0.736072E+12 | 0.00 | 398.88 | 0.577499E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1911781.44 | 31-AUG-12:50 | 1219406.90 | 08-AUG-15:20 | 0.00 | 0.00 | 0.00 |
September | 0.176214E+12 | 0.00 | 171.20 | 0.160947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1354579.04 | 01-SEP-11:00 | 1176104.02 | 01-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.326185E+11 | 0.00 | 42.78 | 0.326185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 679722.67 | 19-OCT-15:00 | 679722.67 | 19-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.249864E+10 | 0.00 | 15.59 | 0.249864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 152331.10 | 01-NOV-15:00 | 152331.10 | 01-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 16160531.70 | 0.00 | 24.18 | 16160531.70 | 0.00 | 0.00 | 0.00 | 0.00 | 4364.34 | 02-DEC-11:20 | 4364.34 | 02-DEC-11:20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.308896E+13 | 0.00 | 1773.08 | 0.255596E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 16160531.70 | 0.00 | 10.42 | 16160531.70 | 0.00 | 0.00 | 0.00 | 0.00 | 3964.12 | 3964.12 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.986641E+12 | 0.00 | 414.30 | 0.773749E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2546637.35 | 1282530.43 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1955716.33 | 0.00 | 5.94 | 1955716.33 | 0.00 | 0.00 | 0.00 | 0.00 | 438.07 | 25-JAN-13:10 | 438.07 | 25-JAN-13:10 | 0.00 | 0.00 | 0.00 |
February | 3787443.51 | 0.00 | 8.63 | 3787443.51 | 0.00 | 0.00 | 0.00 | 0.00 | 2223.68 | 01-FEB-06:01 | 2223.68 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 |
March | 16005505.04 | 0.00 | 14.95 | 16005505.04 | 0.00 | 0.00 | 0.00 | 0.00 | 1222.02 | 20-MAR-12:50 | 1222.02 | 20-MAR-12:50 | 0.00 | 0.00 | 0.00 |
April | 0.367565E+10 | 0.00 | 57.11 | 0.367565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 102997.07 | 23-APR-15:51 | 102997.07 | 23-APR-15:51 | 0.00 | 0.00 | 0.00 |
May | 0.368646E+11 | 0.00 | 224.79 | 0.360900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 145452.94 | 25-MAY-16:00 | 139180.41 | 18-MAY-14:40 | 0.00 | 0.00 | 0.00 |
June | 0.802929E+11 | 0.00 | 362.50 | 0.659502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 247848.56 | 25-JUN-11:31 | 150199.17 | 30-JUN-14:40 | 0.00 | 0.00 | 0.00 |
July | 0.104781E+12 | 0.00 | 411.07 | 0.821597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 270272.89 | 05-JUL-11:50 | 149950.48 | 23-JUL-16:41 | 0.00 | 0.00 | 0.00 |
August | 0.757714E+11 | 0.00 | 393.42 | 0.594074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 213770.68 | 29-AUG-15:40 | 142706.90 | 08-AUG-15:20 | 0.00 | 0.00 | 0.00 |
September | 0.166300E+11 | 0.00 | 167.31 | 0.152341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 155615.76 | 01-SEP-14:00 | 133865.91 | 01-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.291659E+10 | 0.00 | 46.26 | 0.291659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65676.67 | 19-OCT-15:00 | 65676.67 | 19-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.234006E+09 | 0.00 | 18.42 | 0.234006E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12754.81 | 01-NOV-15:00 | 12754.81 | 01-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 2841429.79 | 0.00 | 10.84 | 2841429.79 | 0.00 | 0.00 | 0.00 | 0.00 | 421.80 | 12-DEC-05:01 | 421.80 | 12-DEC-05:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.321191E+12 | 0.00 | 1721.25 | 0.265692E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1955716.33 | 0.00 | 5.94 | 1955716.33 | 0.00 | 0.00 | 0.00 | 0.00 | 421.80 | 421.80 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.104781E+12 | 0.00 | 411.07 | 0.821597E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 270272.89 | 150199.17 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 62140555.16 | 0.00 | 12.33 | 62140555.16 | 0.00 | 0.00 | 0.00 | 0.00 | 9983.61 | 27-JAN-21:00 | 9983.61 | 27-JAN-21:00 | 0.00 | 0.00 | 0.00 |
February | 0.157383E+09 | 0.00 | 19.62 | 0.156865E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22196.55 | 22-FEB-07:17 | 15540.15 | 24-FEB-09:20 | 0.00 | 0.00 | 0.00 |
March | 0.146400E+09 | 0.00 | 23.54 | 0.143539E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 62060.51 | 23-MAR-06:18 | 20483.32 | 02-MAR-07:20 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 21350011.67 | 0.00 | 1.69 | 21350011.67 | 0.00 | 0.00 | 0.00 | 0.00 | 17539.08 | 29-NOV-07:15 | 17539.08 | 29-NOV-07:15 | 0.00 | 0.00 | 0.00 |
December | 0.254932E+09 | 0.00 | 26.26 | 0.237754E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 109904.55 | 08-DEC-07:19 | 29632.91 | 01-DEC-21:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.642205E+09 | 0.00 | 83.44 | 0.621648E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.254932E+09 | 0.00 | 26.26 | 0.237754E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 109904.55 | 29632.91 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.606516E+10 | 0.455525E+10 | 744.00 | 0.606516E+10 | -0.0 | 0.00 | 0.02 | 28-JAN-15:00 | 0.01 | 06-JAN-09:00 | 2922.98 | 21-JAN-16:00 | 2922.98 | 21-JAN-16:00 | 0.00 | 22-JAN-13:20 | 2319.04 | 28-JAN-15:00 | 0.00 |
February | 0.106773E+11 | 0.565103E+10 | 672.00 | 0.106465E+11 | 30827920.34 | 0.00 | 0.03 | 08-FEB-16:30 | 0.02 | 14-FEB-07:00 | 5095.25 | 20-FEB-17:42 | 5095.25 | 20-FEB-17:42 | 91.45 | 14-FEB-07:10 | 3288.02 | 08-FEB-16:30 | 0.00 |
March | 0.141402E+11 | 0.717415E+10 | 744.00 | 0.141076E+11 | 32536529.95 | 0.00 | 0.03 | 23-MAR-17:20 | 0.02 | 20-MAR-15:00 | 5532.17 | 05-MAR-06:50 | 5502.78 | 31-MAR-23:10 | 288.94 | 20-MAR-18:00 | 3473.58 | 23-MAR-17:20 | 0.00 |
April | 0.465603E+11 | 0.173662E+11 | 720.00 | 0.453335E+11 | 0.122681E+10 | 0.00 | 0.89 | 23-APR-16:00 | 0.02 | 30-APR-23:47 | 402783.22 | 23-APR-15:51 | 399013.74 | 23-APR-15:51 | 39986.26 | 23-APR-11:42 | 129442.79 | 23-APR-16:00 | 0.00 |
May | 0.275318E+11 | 0.118384E+11 | 634.12 | 0.261604E+11 | 0.137138E+10 | 0.00 | 0.38 | 25-MAY-13:10 | 0.01 | 28-MAY-19:17 | 165713.38 | 25-MAY-13:10 | 137480.51 | 25-MAY-16:00 | 48233.85 | 26-MAY-12:00 | 52714.28 | 25-MAY-13:20 | 0.00 |
June | 0.162729E+12 | 0.526306E+11 | 509.76 | 0.121124E+12 | 0.416044E+11 | 0.00 | 0.94 | 29-JUN-24:00 | 0.01 | 01-JUN-02:50 | 503505.90 | 29-JUN-24:00 | 231926.47 | 29-JUN-16:00 | 286772.86 | 29-JUN-23:30 | 137925.87 | 29-JUN-24:00 | 0.00 |
July | 0.501739E+12 | 0.144215E+12 | 614.37 | 0.316919E+12 | 0.184820E+12 | 0.00 | 1.00 | 03-JUL-13:50 | 0.01 | 27-JUL-03:07 | 550211.32 | 15-JUL-14:00 | 375778.02 | 15-JUL-14:42 | 359060.11 | 04-JUL-01:00 | 162998.06 | 15-JUL-14:10 | 0.00 |
August | 0.618317E+12 | 0.169461E+12 | 663.27 | 0.377396E+12 | 0.240921E+12 | 0.00 | 1.00 | 07-AUG-15:00 | 0.01 | 13-AUG-02:20 | 525617.67 | 31-AUG-12:55 | 414212.59 | 25-AUG-16:00 | 296712.42 | 30-AUG-08:00 | 161000.10 | 08-AUG-15:10 | 0.00 |
September | 0.518606E+10 | 0.446611E+10 | 489.14 | 0.464426E+10 | 0.541793E+09 | 0.00 | 0.32 | 01-SEP-15:00 | 0.01 | 24-SEP-15:27 | 133504.10 | 01-SEP-15:00 | 115237.64 | 01-SEP-15:00 | 23967.50 | 01-SEP-13:50 | 43109.50 | 01-SEP-15:00 | 0.00 |
October | 0.989795E+10 | 0.573565E+10 | 714.37 | 0.971103E+10 | 0.186915E+09 | 0.00 | 0.23 | 19-OCT-15:00 | 0.00 | 07-OCT-03:10 | 85830.25 | 19-OCT-15:00 | 85830.25 | 19-OCT-15:00 | 4007.43 | 19-OCT-13:10 | 27867.00 | 19-OCT-15:00 | 0.00 |
November | 0.137675E+11 | 0.698107E+10 | 699.46 | 0.134734E+11 | 0.294114E+09 | 0.00 | 0.19 | 01-NOV-15:00 | 0.01 | 21-NOV-06:20 | 72355.89 | 01-NOV-15:00 | 55888.29 | 01-NOV-15:00 | 16467.60 | 01-NOV-15:00 | 21016.22 | 01-NOV-15:00 | 0.00 |
December | 0.147093E+11 | 0.763567E+10 | 744.00 | 0.146796E+11 | 29745775.03 | 0.00 | 0.03 | 11-DEC-18:20 | 0.03 | 17-DEC-12:25 | 5836.84 | 06-DEC-03:00 | 5518.11 | 17-DEC-05:45 | 349.13 | 06-DEC-03:00 | 3712.35 | 11-DEC-18:20 | 0.00 |
Annual Sum or Average | 0.143132E+13 | 0.437710E+12 | 7948.50 | 0.960260E+12 | 0.471059E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.518606E+10 | 0.446611E+10 | 489.14 | 0.464426E+10 | -0.0 | 0.00 | 0.02 | 0.00 | 2922.98 | 2922.98 | 0.00 | 2319.04 | 0.00 | ||||||
Maximum of Months | 0.618317E+12 | 0.169461E+12 | 744.00 | 0.377396E+12 | 0.240921E+12 | 0.00 | 1.00 | 0.03 | 550211.32 | 414212.59 | 359060.11 | 162998.06 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.218816E+10 | 0.656608E+09 | 726.52 | 0.218816E+10 | 0.00 | 0.00 | 0.28 | 20-JAN-16:20 | 0.00 | 01-JAN-07:51 | 2164.18 | 20-JAN-16:25 | 2164.18 | 20-JAN-16:25 | 0.00 | 01-JAN-12:40 | 578.95 | 20-JAN-16:20 | 0.00 |
February | 0.766412E+10 | 0.204077E+10 | 672.00 | 0.766412E+10 | -0.0 | 0.00 | 0.58 | 20-FEB-16:53 | 0.26 | 14-FEB-07:02 | 4731.36 | 20-FEB-16:57 | 4731.36 | 20-FEB-16:57 | 0.00 | 22-FEB-06:07 | 1219.53 | 20-FEB-16:53 | 0.00 |
March | 0.145386E+11 | 0.359693E+10 | 744.00 | 0.145386E+11 | 0.00 | 0.00 | 0.87 | 19-MAR-17:33 | 0.52 | 06-MAR-07:10 | 7800.84 | 31-MAR-24:00 | 7800.84 | 31-MAR-24:00 | 0.00 | 01-MAR-10:30 | 1812.85 | 19-MAR-17:37 | 0.00 |
April | 0.201623E+11 | 0.471497E+10 | 720.00 | 0.201623E+11 | -0.0 | 0.00 | 1.00 | 21-APR-18:00 | 0.32 | 30-APR-24:00 | 9400.35 | 16-APR-18:20 | 9400.35 | 16-APR-18:20 | 0.00 | 12-APR-01:07 | 2821.92 | 23-APR-16:00 | 0.00 |
May | 0.626238E+10 | 0.163554E+10 | 744.00 | 0.621967E+10 | 42706421.31 | 0.00 | 0.47 | 14-MAY-18:41 | 0.20 | 20-MAY-06:40 | 4049.33 | 31-MAY-24:00 | 4049.33 | 31-MAY-24:00 | 256.24 | 26-MAY-13:20 | 1169.51 | 25-MAY-18:40 | 0.00 |
June | 0.112786E+11 | 0.289669E+10 | 720.00 | 0.110814E+11 | 0.197161E+09 | 0.00 | 0.64 | 30-JUN-23:55 | 0.42 | 09-JUN-21:00 | 6096.54 | 30-JUN-23:55 | 6090.58 | 30-JUN-24:00 | 486.88 | 30-JUN-16:00 | 2042.97 | 29-JUN-16:00 | 0.00 |
July | 0.170132E+11 | 0.439603E+10 | 744.00 | 0.167354E+11 | 0.277794E+09 | 0.00 | 0.81 | 31-JUL-24:00 | 0.61 | 08-JUL-07:00 | 7978.01 | 31-JUL-23:54 | 7978.01 | 31-JUL-23:54 | 509.12 | 05-JUL-11:00 | 2411.35 | 15-JUL-14:32 | 0.00 |
August | 0.219210E+11 | 0.530147E+10 | 744.00 | 0.216316E+11 | 0.289352E+09 | 0.00 | 1.00 | 08-AUG-15:40 | 0.31 | 31-AUG-24:00 | 9508.96 | 13-AUG-18:31 | 9508.96 | 13-AUG-18:31 | 415.97 | 08-AUG-15:20 | 3129.18 | 08-AUG-15:40 | 0.00 |
September | 0.585507E+10 | 0.146087E+10 | 720.00 | 0.580012E+10 | 54949287.88 | 0.00 | 0.46 | 30-SEP-24:00 | 0.19 | 23-SEP-06:55 | 4139.54 | 30-SEP-24:00 | 4139.54 | 30-SEP-24:00 | 254.51 | 18-SEP-16:00 | 1019.92 | 03-SEP-17:31 | 0.00 |
October | 0.105542E+11 | 0.254041E+10 | 744.00 | 0.105485E+11 | 5670146.06 | 0.00 | 0.65 | 31-OCT-24:00 | 0.35 | 30-OCT-06:10 | 5718.02 | 31-OCT-24:00 | 5718.02 | 31-OCT-24:00 | 93.41 | 02-OCT-10:40 | 1371.65 | 31-OCT-24:00 | 0.00 |
November | 0.144869E+11 | 0.352332E+10 | 720.00 | 0.144817E+11 | 5190107.15 | 0.00 | 0.76 | 12-NOV-16:03 | 0.54 | 29-NOV-07:10 | 6720.59 | 12-NOV-16:10 | 6720.59 | 12-NOV-16:10 | 186.05 | 21-NOV-12:10 | 1605.32 | 12-NOV-16:03 | 0.00 |
December | 0.185701E+11 | 0.454215E+10 | 744.00 | 0.185701E+11 | -0.0 | 0.00 | 0.93 | 10-DEC-15:52 | 0.70 | 26-DEC-07:02 | 7990.78 | 10-DEC-16:00 | 7990.78 | 10-DEC-16:00 | 0.00 | 27-DEC-07:20 | 1952.63 | 10-DEC-15:52 | 0.00 |
Annual Sum or Average | 0.150495E+12 | 0.373058E+11 | 8742.52 | 0.149622E+12 | 0.872822E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.218816E+10 | 0.656608E+09 | 672.00 | 0.218816E+10 | -0.0 | 0.00 | 0.28 | 0.00 | 2164.18 | 2164.18 | 0.00 | 578.95 | 0.00 | ||||||
Maximum of Months | 0.219210E+11 | 0.530147E+10 | 744.00 | 0.216316E+11 | 0.289352E+09 | 0.00 | 1.00 | 0.70 | 9508.96 | 9508.96 | 509.12 | 3129.18 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.231242E+10 | 0.776089E+09 | 188.81 | 0.231242E+10 | -0.0 | 0.00 | 0.23 | 26-JAN-16:20 | 0.00 | 01-JAN-00:01 | 16393.23 | 20-JAN-16:25 | 16393.23 | 20-JAN-16:25 | 0.00 | 19-JAN-12:30 | 5406.95 | 26-JAN-16:20 | 0.00 |
February | 0.500291E+11 | 0.137928E+11 | 672.00 | 0.500291E+11 | -0.0 | 0.00 | 0.52 | 27-FEB-16:55 | 0.11 | 14-FEB-07:02 | 41581.39 | 08-FEB-17:00 | 41581.39 | 08-FEB-17:00 | 0.00 | 22-FEB-11:00 | 11408.39 | 08-FEB-16:30 | 0.00 |
March | 0.118417E+12 | 0.298553E+11 | 744.00 | 0.118417E+12 | -0.0 | 0.00 | 0.81 | 19-MAR-17:43 | 0.35 | 06-MAR-07:10 | 69799.28 | 31-MAR-23:30 | 69799.28 | 31-MAR-23:30 | 0.00 | 22-MAR-09:00 | 16364.65 | 19-MAR-17:41 | 0.00 |
April | 0.177974E+12 | 0.421360E+11 | 720.00 | 0.177974E+12 | 0.00 | 0.00 | 1.00 | 23-APR-15:21 | 0.21 | 30-APR-23:55 | 86969.28 | 21-APR-18:20 | 86969.28 | 21-APR-18:20 | 0.00 | 16-APR-11:45 | 27178.95 | 23-APR-16:00 | 0.00 |
May | 0.527668E+11 | 0.139513E+11 | 744.00 | 0.523463E+11 | 0.420487E+09 | 0.00 | 0.44 | 14-MAY-18:31 | 0.09 | 01-MAY-06:05 | 35462.05 | 14-MAY-18:43 | 35462.05 | 14-MAY-18:43 | 2517.25 | 26-MAY-13:20 | 11249.40 | 25-MAY-18:40 | 0.00 |
June | 0.102698E+12 | 0.265620E+11 | 720.00 | 0.100745E+12 | 0.195305E+10 | 0.00 | 0.63 | 30-JUN-23:55 | 0.37 | 10-JUN-07:00 | 58121.47 | 30-JUN-23:03 | 57964.93 | 30-JUN-24:00 | 4845.16 | 30-JUN-16:00 | 19289.33 | 29-JUN-16:00 | 0.00 |
July | 0.158335E+12 | 0.410977E+11 | 744.00 | 0.155578E+12 | 0.275783E+10 | 0.00 | 0.80 | 28-JUL-18:50 | 0.57 | 08-JUL-17:00 | 74984.19 | 31-JUL-23:54 | 74984.19 | 31-JUL-23:54 | 5053.14 | 05-JUL-11:00 | 22689.33 | 15-JUL-14:32 | 0.00 |
August | 0.203776E+12 | 0.495477E+11 | 744.00 | 0.200899E+12 | 0.287730E+10 | 0.00 | 0.98 | 08-AUG-16:00 | 0.25 | 31-AUG-24:00 | 87609.24 | 05-AUG-18:40 | 87609.24 | 05-AUG-18:40 | 4143.94 | 08-AUG-15:20 | 29484.88 | 08-AUG-16:00 | 0.00 |
September | 0.461465E+11 | 0.117030E+11 | 720.00 | 0.456137E+11 | 0.532729E+09 | 0.00 | 0.42 | 09-SEP-17:55 | 0.11 | 23-SEP-06:55 | 36009.82 | 03-SEP-17:42 | 35907.23 | 03-SEP-17:43 | 2476.87 | 18-SEP-16:00 | 9255.80 | 03-SEP-17:41 | 0.00 |
October | 0.820482E+11 | 0.201368E+11 | 744.00 | 0.819918E+11 | 56483426.51 | 0.00 | 0.55 | 31-OCT-23:50 | 0.22 | 30-OCT-06:10 | 46797.25 | 19-OCT-16:50 | 46192.98 | 19-OCT-16:50 | 925.60 | 02-OCT-14:10 | 11783.22 | 19-OCT-16:00 | 0.00 |
November | 0.111028E+12 | 0.276729E+11 | 720.00 | 0.110976E+12 | 51834515.19 | 0.00 | 0.69 | 09-NOV-16:10 | 0.38 | 27-NOV-04:12 | 57921.53 | 17-NOV-16:10 | 57921.53 | 17-NOV-16:10 | 1813.63 | 21-NOV-12:10 | 14114.12 | 17-NOV-17:00 | 0.00 |
December | 0.143901E+12 | 0.361741E+11 | 744.00 | 0.143901E+12 | 0.00 | 0.00 | 0.81 | 20-DEC-16:00 | 0.51 | 26-DEC-07:02 | 66871.72 | 08-DEC-15:55 | 66871.72 | 08-DEC-15:55 | 0.00 | 07-DEC-05:01 | 16393.84 | 20-DEC-16:00 | 0.00 |
Annual Sum or Average | 0.124943E+13 | 0.313406E+12 | 8204.81 | 0.124078E+13 | 0.864973E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.231242E+10 | 0.776089E+09 | 188.81 | 0.231242E+10 | -0.0 | 0.00 | 0.23 | 0.00 | 16393.23 | 16393.23 | 0.00 | 5406.95 | 0.00 | ||||||
Maximum of Months | 0.203776E+12 | 0.495477E+11 | 744.00 | 0.200899E+12 | 0.287730E+10 | 0.00 | 1.00 | 0.57 | 87609.24 | 87609.24 | 5053.14 | 29484.88 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 82875228.49 | 26467462.78 | 53.01 | 82875228.49 | 0.00 | 0.00 | 0.20 | 20-JAN-16:25 | 0.00 | 01-JAN-00:01 | 1450.05 | 20-JAN-16:25 | 1450.05 | 20-JAN-16:25 | 0.00 | 18-JAN-14:50 | 400.67 | 20-JAN-16:25 | 0.00 |
February | 0.327915E+10 | 0.921294E+09 | 640.79 | 0.327915E+10 | -0.0 | 0.00 | 0.50 | 08-FEB-17:00 | 0.00 | 01-FEB-00:03 | 4101.37 | 08-FEB-17:00 | 4101.37 | 08-FEB-17:00 | 0.00 | 22-FEB-03:50 | 1027.07 | 08-FEB-17:00 | 0.00 |
March | 0.101125E+11 | 0.258444E+10 | 744.00 | 0.101125E+11 | 0.00 | 0.00 | 0.75 | 31-MAR-23:20 | 0.22 | 06-MAR-04:14 | 6557.89 | 31-MAR-23:20 | 6557.89 | 31-MAR-23:20 | 0.00 | 22-MAR-01:40 | 1548.97 | 31-MAR-23:20 | 0.00 |
April | 0.165483E+11 | 0.395931E+10 | 720.00 | 0.165483E+11 | 0.00 | 0.00 | 1.00 | 23-APR-15:51 | 0.12 | 30-APR-23:55 | 8686.29 | 21-APR-18:20 | 8686.29 | 21-APR-18:20 | 0.00 | 16-APR-10:34 | 2753.16 | 23-APR-16:00 | 0.00 |
May | 0.484377E+10 | 0.129204E+10 | 742.64 | 0.480171E+10 | 42059741.81 | 0.00 | 0.43 | 25-MAY-18:40 | 0.00 | 01-MAY-01:55 | 3542.22 | 25-MAY-18:50 | 3451.42 | 14-MAY-18:43 | 252.98 | 26-MAY-13:20 | 1151.84 | 25-MAY-18:40 | 0.00 |
June | 0.100533E+11 | 0.261448E+10 | 720.00 | 0.985832E+10 | 0.194990E+09 | 0.00 | 0.63 | 30-JUN-23:03 | 0.33 | 10-JUN-07:00 | 5856.61 | 30-JUN-23:03 | 5829.09 | 30-JUN-23:33 | 485.80 | 30-JUN-16:00 | 1967.70 | 29-JUN-16:00 | 0.00 |
July | 0.157336E+11 | 0.409948E+10 | 744.00 | 0.154581E+11 | 0.275518E+09 | 0.00 | 0.80 | 28-JUL-18:50 | 0.53 | 09-JUL-04:55 | 7424.50 | 31-JUL-23:54 | 7424.50 | 31-JUL-23:54 | 504.95 | 05-JUL-11:00 | 2289.24 | 15-JUL-14:32 | 0.00 |
August | 0.202034E+11 | 0.493130E+10 | 744.00 | 0.199162E+11 | 0.287257E+09 | 0.00 | 0.98 | 08-AUG-16:00 | 0.24 | 31-AUG-24:00 | 8853.68 | 05-AUG-18:35 | 8853.68 | 05-AUG-18:35 | 414.62 | 08-AUG-15:20 | 2985.79 | 08-AUG-16:00 | 0.00 |
September | 0.398251E+10 | 0.102265E+10 | 720.00 | 0.393012E+10 | 52390301.35 | 0.00 | 0.41 | 03-SEP-17:41 | 0.05 | 23-SEP-06:55 | 3579.04 | 03-SEP-17:42 | 3568.61 | 03-SEP-17:43 | 249.49 | 18-SEP-16:00 | 923.15 | 03-SEP-17:31 | 0.00 |
October | 0.665315E+10 | 0.165870E+10 | 743.92 | 0.664763E+10 | 5525814.33 | 0.00 | 0.52 | 19-OCT-16:50 | 0.00 | 29-OCT-22:45 | 4708.55 | 19-OCT-16:50 | 4647.86 | 19-OCT-16:50 | 92.67 | 02-OCT-14:10 | 1185.34 | 19-OCT-16:00 | 0.00 |
November | 0.913528E+10 | 0.231371E+10 | 720.00 | 0.913018E+10 | 5093638.12 | 0.00 | 0.66 | 09-NOV-16:20 | 0.23 | 27-NOV-04:01 | 5670.78 | 17-NOV-16:10 | 5670.78 | 17-NOV-16:10 | 176.91 | 21-NOV-12:10 | 1358.66 | 09-NOV-16:20 | 0.00 |
December | 0.126170E+11 | 0.321712E+10 | 744.00 | 0.126170E+11 | -0.0 | 0.00 | 0.77 | 20-DEC-16:00 | 0.39 | 25-DEC-05:53 | 6396.76 | 20-DEC-16:00 | 6396.76 | 20-DEC-16:00 | 0.00 | 19-DEC-05:59 | 1586.02 | 20-DEC-16:00 | 0.00 |
Annual Sum or Average | 0.113245E+12 | 0.286410E+11 | 8036.36 | 0.112382E+12 | 0.862835E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 82875228.49 | 26467462.78 | 53.01 | 82875228.49 | -0.0 | 0.00 | 0.20 | 0.00 | 1450.05 | 1450.05 | 0.00 | 400.67 | 0.00 | ||||||
Maximum of Months | 0.202034E+11 | 0.493130E+10 | 744.00 | 0.199162E+11 | 0.287257E+09 | 0.00 | 1.00 | 0.53 | 8853.68 | 8853.68 | 504.95 | 2985.79 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.28 | 0.00 | 137.28 | 0.52 | 1208.94 | 0.00 | 0.00 | 0.00 |
February | 210.87 | 0.00 | 210.87 | 11.49 | 980.33 | 0.00 | 0.00 | 0.00 |
March | 259.44 | 0.00 | 259.44 | 32.63 | 782.87 | 0.00 | 0.00 | 0.00 |
April | 340.10 | 2.65 | 337.45 | 133.30 | 508.88 | 0.00 | 0.00 | 0.00 |
May | 478.34 | 25.76 | 452.59 | 398.77 | 257.22 | 0.00 | 0.00 | 0.00 |
June | 533.84 | 58.68 | 475.16 | 552.60 | 179.64 | 0.00 | 0.00 | 0.00 |
July | 509.90 | 43.76 | 466.14 | 553.56 | 166.99 | 0.00 | 0.00 | 0.00 |
August | 387.28 | 6.65 | 380.63 | 374.55 | 202.22 | 0.00 | 0.00 | 0.00 |
September | 301.80 | 0.07 | 301.73 | 207.94 | 331.25 | 0.00 | 0.00 | 0.00 |
October | 209.55 | 0.00 | 209.55 | 57.54 | 530.57 | 0.00 | 0.00 | 0.00 |
November | 138.75 | 0.00 | 138.75 | 6.27 | 805.51 | 0.00 | 0.00 | 0.00 |
December | 116.31 | 0.00 | 116.31 | 0.00 | 1186.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 302.41 | 11.52 | 290.90 | 195.26 | 593.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 116.31 | 0.00 | 116.31 | 0.00 | 166.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 533.84 | 58.68 | 475.16 | 553.56 | 1208.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.28 | 0.00 | 137.28 | 0.52 | 1208.94 | 0.00 | 0.00 | 0.00 |
February | 210.87 | 0.00 | 210.87 | 11.49 | 980.33 | 0.00 | 0.00 | 0.00 |
March | 259.44 | 0.00 | 259.44 | 32.63 | 782.87 | 0.00 | 0.00 | 0.00 |
April | 340.10 | 2.65 | 337.45 | 133.30 | 508.88 | 0.00 | 0.00 | 0.00 |
May | 478.34 | 25.76 | 452.58 | 398.77 | 257.22 | 0.00 | 0.00 | 0.00 |
June | 533.84 | 58.68 | 475.16 | 552.60 | 179.64 | 0.00 | 0.00 | 0.00 |
July | 509.90 | 43.76 | 466.14 | 553.56 | 166.99 | 0.00 | 0.00 | 0.00 |
August | 387.28 | 6.65 | 380.63 | 374.55 | 202.22 | 0.00 | 0.00 | 0.00 |
September | 301.80 | 0.07 | 301.73 | 207.94 | 331.25 | 0.00 | 0.00 | 0.00 |
October | 209.55 | 0.00 | 209.55 | 57.54 | 530.57 | 0.00 | 0.00 | 0.00 |
November | 138.75 | 0.00 | 138.75 | 6.27 | 805.51 | 0.00 | 0.00 | 0.00 |
December | 116.31 | 0.00 | 116.31 | 0.00 | 1186.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 302.41 | 11.52 | 290.90 | 195.26 | 593.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 116.31 | 0.00 | 116.31 | 0.00 | 166.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 533.84 | 58.68 | 475.16 | 553.56 | 1208.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.28 | 0.00 | 137.28 | 0.52 | 1208.94 | 0.00 | 0.00 | 0.00 |
February | 210.87 | 0.00 | 210.87 | 11.49 | 980.33 | 0.00 | 0.00 | 0.00 |
March | 259.44 | 0.00 | 259.44 | 32.63 | 782.87 | 0.00 | 0.00 | 0.00 |
April | 340.10 | 2.65 | 337.45 | 133.30 | 508.88 | 0.00 | 0.00 | 0.00 |
May | 478.34 | 25.76 | 452.59 | 398.77 | 257.22 | 0.00 | 0.00 | 0.00 |
June | 533.84 | 58.68 | 475.16 | 552.60 | 179.64 | 0.00 | 0.00 | 0.00 |
July | 509.90 | 43.76 | 466.14 | 553.56 | 166.99 | 0.00 | 0.00 | 0.00 |
August | 387.28 | 6.65 | 380.63 | 374.55 | 202.22 | 0.00 | 0.00 | 0.00 |
September | 301.80 | 0.07 | 301.73 | 207.94 | 331.25 | 0.00 | 0.00 | 0.00 |
October | 209.55 | 0.00 | 209.55 | 57.54 | 530.57 | 0.00 | 0.00 | 0.00 |
November | 138.75 | 0.00 | 138.75 | 6.27 | 805.51 | 0.00 | 0.00 | 0.00 |
December | 116.31 | 0.00 | 116.31 | 0.00 | 1186.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 302.41 | 11.52 | 290.90 | 195.26 | 593.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 116.31 | 0.00 | 116.31 | 0.00 | 166.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 533.84 | 58.68 | 475.16 | 553.56 | 1208.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.28 | 0.00 | 137.28 | 0.52 | 1208.94 | 0.00 | 0.00 | 0.00 |
February | 210.87 | 0.00 | 210.87 | 11.49 | 980.33 | 0.00 | 0.00 | 0.00 |
March | 259.44 | 0.00 | 259.44 | 32.63 | 782.87 | 0.00 | 0.00 | 0.00 |
April | 340.10 | 2.65 | 337.45 | 133.30 | 508.88 | 0.00 | 0.00 | 0.00 |
May | 478.34 | 25.76 | 452.58 | 398.77 | 257.22 | 0.00 | 0.00 | 0.00 |
June | 533.84 | 58.68 | 475.16 | 552.60 | 179.64 | 0.00 | 0.00 | 0.00 |
July | 509.90 | 43.76 | 466.14 | 553.56 | 166.99 | 0.00 | 0.00 | 0.00 |
August | 387.28 | 6.65 | 380.63 | 374.55 | 202.22 | 0.00 | 0.00 | 0.00 |
September | 301.80 | 0.07 | 301.73 | 207.94 | 331.25 | 0.00 | 0.00 | 0.00 |
October | 209.55 | 0.00 | 209.55 | 57.54 | 530.57 | 0.00 | 0.00 | 0.00 |
November | 138.75 | 0.00 | 138.75 | 6.27 | 805.51 | 0.00 | 0.00 | 0.00 |
December | 116.31 | 0.00 | 116.31 | 0.00 | 1186.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 302.41 | 11.52 | 290.90 | 195.26 | 593.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 116.31 | 0.00 | 116.31 | 0.00 | 166.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 533.84 | 58.68 | 475.16 | 553.56 | 1208.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 137.27 | 0.00 | 137.27 | 0.52 | 1208.89 | 0.00 | 0.00 | 0.00 |
February | 210.86 | 0.00 | 210.86 | 11.49 | 980.29 | 0.00 | 0.00 | 0.00 |
March | 259.43 | 0.00 | 259.43 | 32.63 | 782.84 | 0.00 | 0.00 | 0.00 |
April | 340.09 | 2.65 | 337.44 | 133.29 | 508.86 | 0.00 | 0.00 | 0.00 |
May | 478.32 | 25.76 | 452.57 | 398.75 | 257.21 | 0.00 | 0.00 | 0.00 |
June | 533.82 | 58.68 | 475.14 | 552.58 | 179.63 | 0.00 | 0.00 | 0.00 |
July | 509.88 | 43.76 | 466.12 | 553.54 | 166.98 | 0.00 | 0.00 | 0.00 |
August | 387.27 | 6.65 | 380.62 | 374.53 | 202.21 | 0.00 | 0.00 | 0.00 |
September | 301.79 | 0.07 | 301.71 | 207.93 | 331.24 | 0.00 | 0.00 | 0.00 |
October | 209.55 | 0.00 | 209.55 | 57.54 | 530.55 | 0.00 | 0.00 | 0.00 |
November | 138.75 | 0.00 | 138.75 | 6.27 | 805.48 | 0.00 | 0.00 | 0.00 |
December | 116.31 | 0.00 | 116.31 | 0.00 | 1186.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 302.40 | 11.52 | 290.88 | 195.25 | 593.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 116.31 | 0.00 | 116.31 | 0.00 | 166.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 533.82 | 58.68 | 475.14 | 553.54 | 1208.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 334.41 | 139.59 | 194.81 | 121.73 | 1207.95 | 0.00 | 0.00 | 0.00 |
February | 525.49 | 224.15 | 301.34 | 292.57 | 971.74 | 0.00 | 0.00 | 0.00 |
March | 716.01 | 359.16 | 356.85 | 517.10 | 783.23 | 0.00 | 0.00 | 0.00 |
April | 992.60 | 535.39 | 457.21 | 908.38 | 516.57 | 0.00 | 0.00 | 0.00 |
May | 1074.29 | 472.27 | 602.02 | 1135.71 | 286.39 | 0.00 | 0.00 | 0.00 |
June | 1216.17 | 581.76 | 634.41 | 1410.56 | 201.28 | 0.00 | 0.00 | 0.00 |
July | 1191.40 | 559.40 | 631.99 | 1419.77 | 181.61 | 0.00 | 0.00 | 0.00 |
August | 918.57 | 401.48 | 517.09 | 1047.48 | 215.67 | 0.00 | 0.00 | 0.00 |
September | 735.62 | 329.26 | 406.36 | 735.27 | 346.49 | 0.00 | 0.00 | 0.00 |
October | 445.43 | 168.91 | 276.52 | 311.85 | 544.72 | 0.00 | 0.00 | 0.00 |
November | 283.56 | 94.80 | 188.76 | 119.45 | 809.79 | 0.00 | 0.00 | 0.00 |
December | 258.75 | 95.64 | 163.11 | 74.15 | 1191.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 725.09 | 330.42 | 394.67 | 676.34 | 603.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 258.75 | 94.80 | 163.11 | 74.15 | 181.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1216.17 | 581.76 | 634.41 | 1419.77 | 1207.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 334.41 | 139.59 | 194.81 | 121.73 | 1207.95 | 0.00 | 0.00 | 0.00 |
February | 525.49 | 224.15 | 301.34 | 292.57 | 971.74 | 0.00 | 0.00 | 0.00 |
March | 716.01 | 359.16 | 356.85 | 517.10 | 783.23 | 0.00 | 0.00 | 0.00 |
April | 992.60 | 535.39 | 457.21 | 908.38 | 516.57 | 0.00 | 0.00 | 0.00 |
May | 1074.29 | 472.27 | 602.02 | 1135.71 | 286.39 | 0.00 | 0.00 | 0.00 |
June | 1216.17 | 581.76 | 634.41 | 1410.56 | 201.28 | 0.00 | 0.00 | 0.00 |
July | 1191.40 | 559.40 | 631.99 | 1419.77 | 181.61 | 0.00 | 0.00 | 0.00 |
August | 918.57 | 401.48 | 517.09 | 1047.48 | 215.67 | 0.00 | 0.00 | 0.00 |
September | 735.62 | 329.26 | 406.36 | 735.27 | 346.49 | 0.00 | 0.00 | 0.00 |
October | 445.43 | 168.91 | 276.52 | 311.85 | 544.72 | 0.00 | 0.00 | 0.00 |
November | 283.56 | 94.80 | 188.76 | 119.45 | 809.79 | 0.00 | 0.00 | 0.00 |
December | 258.75 | 95.64 | 163.11 | 74.15 | 1191.95 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 725.09 | 330.42 | 394.67 | 676.34 | 603.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 258.75 | 94.80 | 163.11 | 74.15 | 181.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1216.17 | 581.76 | 634.41 | 1419.77 | 1207.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 334.40 | 139.59 | 194.81 | 121.72 | 1207.93 | 0.00 | 0.00 | 0.00 |
February | 525.48 | 224.15 | 301.33 | 292.56 | 971.72 | 0.00 | 0.00 | 0.00 |
March | 716.00 | 359.16 | 356.84 | 517.09 | 783.22 | 0.00 | 0.00 | 0.00 |
April | 992.58 | 535.38 | 457.20 | 908.36 | 516.56 | 0.00 | 0.00 | 0.00 |
May | 1074.27 | 472.26 | 602.01 | 1135.69 | 286.38 | 0.00 | 0.00 | 0.00 |
June | 1216.15 | 581.75 | 634.40 | 1410.53 | 201.28 | 0.00 | 0.00 | 0.00 |
July | 1191.37 | 559.39 | 631.98 | 1419.74 | 181.61 | 0.00 | 0.00 | 0.00 |
August | 918.55 | 401.47 | 517.08 | 1047.46 | 215.67 | 0.00 | 0.00 | 0.00 |
September | 735.61 | 329.25 | 406.35 | 735.26 | 346.49 | 0.00 | 0.00 | 0.00 |
October | 445.42 | 168.90 | 276.52 | 311.85 | 544.71 | 0.00 | 0.00 | 0.00 |
November | 283.56 | 94.80 | 188.76 | 119.44 | 809.77 | 0.00 | 0.00 | 0.00 |
December | 258.75 | 95.64 | 163.11 | 74.15 | 1191.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 725.07 | 330.41 | 394.66 | 676.32 | 603.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 258.75 | 94.80 | 163.11 | 74.15 | 181.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1216.15 | 581.75 | 634.40 | 1419.74 | 1207.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 945.29 | 657.62 | 287.67 | 771.55 | 956.42 | 0.00 | 0.00 | 0.00 |
February | 1196.97 | 808.47 | 388.49 | 1102.72 | 818.39 | 0.00 | 0.00 | 0.00 |
March | 1054.67 | 667.46 | 387.21 | 993.26 | 691.65 | 0.00 | 0.00 | 0.00 |
April | 955.50 | 518.62 | 436.88 | 976.34 | 488.38 | 0.00 | 0.00 | 0.00 |
May | 803.33 | 274.64 | 528.69 | 894.93 | 276.60 | 0.00 | 0.00 | 0.00 |
June | 720.81 | 192.13 | 528.68 | 855.93 | 191.20 | 0.00 | 0.00 | 0.00 |
July | 788.08 | 249.66 | 538.42 | 979.42 | 174.38 | 0.00 | 0.00 | 0.00 |
August | 841.62 | 352.04 | 489.58 | 1015.82 | 206.50 | 0.00 | 0.00 | 0.00 |
September | 901.50 | 480.12 | 421.38 | 1006.83 | 321.32 | 0.00 | 0.00 | 0.00 |
October | 769.82 | 452.77 | 317.05 | 749.81 | 475.01 | 0.00 | 0.00 | 0.00 |
November | 685.74 | 430.37 | 255.37 | 588.13 | 665.21 | 0.00 | 0.00 | 0.00 |
December | 729.88 | 478.59 | 251.29 | 544.67 | 942.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 863.93 | 461.34 | 402.59 | 871.58 | 515.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 685.74 | 192.13 | 251.29 | 544.67 | 174.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1196.97 | 808.47 | 538.42 | 1102.72 | 956.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 945.29 | 657.62 | 287.67 | 771.55 | 956.42 | 0.00 | 0.00 | 0.00 |
February | 1196.97 | 808.47 | 388.49 | 1102.72 | 818.39 | 0.00 | 0.00 | 0.00 |
March | 1054.67 | 667.46 | 387.21 | 993.26 | 691.65 | 0.00 | 0.00 | 0.00 |
April | 955.50 | 518.62 | 436.88 | 976.34 | 488.38 | 0.00 | 0.00 | 0.00 |
May | 803.33 | 274.64 | 528.69 | 894.93 | 276.60 | 0.00 | 0.00 | 0.00 |
June | 720.81 | 192.13 | 528.68 | 855.93 | 191.20 | 0.00 | 0.00 | 0.00 |
July | 788.08 | 249.66 | 538.42 | 979.42 | 174.38 | 0.00 | 0.00 | 0.00 |
August | 841.62 | 352.04 | 489.58 | 1015.82 | 206.50 | 0.00 | 0.00 | 0.00 |
September | 901.50 | 480.12 | 421.38 | 1006.83 | 321.32 | 0.00 | 0.00 | 0.00 |
October | 769.82 | 452.77 | 317.05 | 749.81 | 475.01 | 0.00 | 0.00 | 0.00 |
November | 685.74 | 430.37 | 255.37 | 588.13 | 665.21 | 0.00 | 0.00 | 0.00 |
December | 729.88 | 478.59 | 251.29 | 544.67 | 942.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 863.93 | 461.34 | 402.59 | 871.58 | 515.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 685.74 | 192.13 | 251.29 | 544.67 | 174.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1196.97 | 808.47 | 538.42 | 1102.72 | 956.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 945.29 | 657.62 | 287.67 | 771.55 | 956.42 | 0.00 | 0.00 | 0.00 |
February | 1196.97 | 808.47 | 388.49 | 1102.72 | 818.39 | 0.00 | 0.00 | 0.00 |
March | 1054.67 | 667.46 | 387.21 | 993.26 | 691.65 | 0.00 | 0.00 | 0.00 |
April | 955.50 | 518.62 | 436.88 | 976.34 | 488.38 | 0.00 | 0.00 | 0.00 |
May | 803.33 | 274.64 | 528.69 | 894.93 | 276.60 | 0.00 | 0.00 | 0.00 |
June | 720.81 | 192.13 | 528.68 | 855.93 | 191.20 | 0.00 | 0.00 | 0.00 |
July | 788.08 | 249.66 | 538.42 | 979.42 | 174.38 | 0.00 | 0.00 | 0.00 |
August | 841.62 | 352.04 | 489.58 | 1015.82 | 206.50 | 0.00 | 0.00 | 0.00 |
September | 901.50 | 480.12 | 421.38 | 1006.83 | 321.32 | 0.00 | 0.00 | 0.00 |
October | 769.82 | 452.77 | 317.05 | 749.81 | 475.01 | 0.00 | 0.00 | 0.00 |
November | 685.74 | 430.37 | 255.37 | 588.13 | 665.21 | 0.00 | 0.00 | 0.00 |
December | 729.88 | 478.59 | 251.29 | 544.67 | 942.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 863.93 | 461.34 | 402.59 | 871.58 | 515.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 685.74 | 192.13 | 251.29 | 544.67 | 174.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1196.97 | 808.47 | 538.42 | 1102.72 | 956.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 945.29 | 657.62 | 287.67 | 771.55 | 956.42 | 0.00 | 0.00 | 0.00 |
February | 1196.97 | 808.47 | 388.49 | 1102.72 | 818.39 | 0.00 | 0.00 | 0.00 |
March | 1054.67 | 667.46 | 387.21 | 993.26 | 691.65 | 0.00 | 0.00 | 0.00 |
April | 955.50 | 518.62 | 436.88 | 976.34 | 488.38 | 0.00 | 0.00 | 0.00 |
May | 803.33 | 274.64 | 528.69 | 894.93 | 276.60 | 0.00 | 0.00 | 0.00 |
June | 720.81 | 192.13 | 528.68 | 855.93 | 191.20 | 0.00 | 0.00 | 0.00 |
July | 788.08 | 249.66 | 538.42 | 979.42 | 174.38 | 0.00 | 0.00 | 0.00 |
August | 841.62 | 352.04 | 489.58 | 1015.82 | 206.50 | 0.00 | 0.00 | 0.00 |
September | 901.50 | 480.12 | 421.38 | 1006.83 | 321.32 | 0.00 | 0.00 | 0.00 |
October | 769.82 | 452.77 | 317.05 | 749.81 | 475.01 | 0.00 | 0.00 | 0.00 |
November | 685.74 | 430.37 | 255.37 | 588.13 | 665.21 | 0.00 | 0.00 | 0.00 |
December | 729.88 | 478.59 | 251.29 | 544.67 | 942.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 863.93 | 461.34 | 402.59 | 871.58 | 515.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 685.74 | 192.13 | 251.29 | 544.67 | 174.38 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1196.97 | 808.47 | 538.42 | 1102.72 | 956.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 945.26 | 657.59 | 287.66 | 771.52 | 956.38 | 0.00 | 0.00 | 0.00 |
February | 1196.92 | 808.44 | 388.48 | 1102.67 | 818.36 | 0.00 | 0.00 | 0.00 |
March | 1054.63 | 667.44 | 387.20 | 993.22 | 691.62 | 0.00 | 0.00 | 0.00 |
April | 955.46 | 518.60 | 436.86 | 976.30 | 488.36 | 0.00 | 0.00 | 0.00 |
May | 803.29 | 274.63 | 528.67 | 894.90 | 276.59 | 0.00 | 0.00 | 0.00 |
June | 720.78 | 192.12 | 528.66 | 855.89 | 191.19 | 0.00 | 0.00 | 0.00 |
July | 788.05 | 249.65 | 538.40 | 979.38 | 174.37 | 0.00 | 0.00 | 0.00 |
August | 841.59 | 352.03 | 489.56 | 1015.78 | 206.49 | 0.00 | 0.00 | 0.00 |
September | 901.47 | 480.10 | 421.37 | 1006.79 | 321.31 | 0.00 | 0.00 | 0.00 |
October | 769.79 | 452.75 | 317.04 | 749.78 | 474.99 | 0.00 | 0.00 | 0.00 |
November | 685.71 | 430.35 | 255.36 | 588.10 | 665.18 | 0.00 | 0.00 | 0.00 |
December | 729.85 | 478.57 | 251.28 | 544.65 | 942.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 863.90 | 461.33 | 402.57 | 871.54 | 515.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 685.71 | 192.12 | 251.28 | 544.65 | 174.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1196.92 | 808.44 | 538.40 | 1102.67 | 956.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 337.99 | 141.53 | 196.46 | 132.69 | 1264.63 | 0.00 | 0.00 | 0.00 |
February | 550.68 | 251.51 | 299.17 | 336.62 | 1053.12 | 0.00 | 0.00 | 0.00 |
March | 724.65 | 370.80 | 353.85 | 539.82 | 867.84 | 0.00 | 0.00 | 0.00 |
April | 925.70 | 468.86 | 456.84 | 831.11 | 578.27 | 0.00 | 0.00 | 0.00 |
May | 1137.39 | 542.54 | 594.85 | 1238.40 | 307.91 | 0.00 | 0.00 | 0.00 |
June | 1097.55 | 474.57 | 622.98 | 1264.01 | 218.25 | 0.00 | 0.00 | 0.00 |
July | 1171.75 | 544.74 | 627.01 | 1393.75 | 205.66 | 0.00 | 0.00 | 0.00 |
August | 964.27 | 438.16 | 526.11 | 1105.56 | 246.12 | 0.00 | 0.00 | 0.00 |
September | 753.61 | 338.59 | 415.03 | 768.62 | 358.88 | 0.00 | 0.00 | 0.00 |
October | 476.06 | 191.11 | 284.95 | 360.52 | 570.85 | 0.00 | 0.00 | 0.00 |
November | 289.14 | 97.49 | 191.65 | 127.22 | 862.39 | 0.00 | 0.00 | 0.00 |
December | 257.75 | 90.21 | 167.54 | 70.10 | 1293.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 724.83 | 329.64 | 395.19 | 682.79 | 650.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 257.75 | 90.21 | 167.54 | 70.10 | 205.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1171.75 | 544.74 | 627.01 | 1393.75 | 1293.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 337.99 | 141.53 | 196.46 | 132.69 | 1264.63 | 0.00 | 0.00 | 0.00 |
February | 550.68 | 251.51 | 299.17 | 336.62 | 1053.12 | 0.00 | 0.00 | 0.00 |
March | 724.65 | 370.80 | 353.85 | 539.82 | 867.84 | 0.00 | 0.00 | 0.00 |
April | 925.70 | 468.86 | 456.84 | 831.11 | 578.27 | 0.00 | 0.00 | 0.00 |
May | 1137.39 | 542.54 | 594.85 | 1238.40 | 307.91 | 0.00 | 0.00 | 0.00 |
June | 1097.55 | 474.57 | 622.98 | 1264.01 | 218.25 | 0.00 | 0.00 | 0.00 |
July | 1171.75 | 544.74 | 627.01 | 1393.75 | 205.66 | 0.00 | 0.00 | 0.00 |
August | 964.27 | 438.16 | 526.11 | 1105.56 | 246.12 | 0.00 | 0.00 | 0.00 |
September | 753.61 | 338.59 | 415.03 | 768.62 | 358.88 | 0.00 | 0.00 | 0.00 |
October | 476.06 | 191.11 | 284.95 | 360.52 | 570.85 | 0.00 | 0.00 | 0.00 |
November | 289.14 | 97.49 | 191.65 | 127.22 | 862.39 | 0.00 | 0.00 | 0.00 |
December | 257.75 | 90.21 | 167.54 | 70.10 | 1293.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 724.83 | 329.64 | 395.19 | 682.79 | 650.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 257.75 | 90.21 | 167.54 | 70.10 | 205.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1171.75 | 544.74 | 627.01 | 1393.75 | 1293.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 337.98 | 141.53 | 196.45 | 132.69 | 1264.61 | 0.00 | 0.00 | 0.00 |
February | 550.67 | 251.51 | 299.16 | 336.62 | 1053.10 | 0.00 | 0.00 | 0.00 |
March | 724.64 | 370.79 | 353.84 | 539.81 | 867.83 | 0.00 | 0.00 | 0.00 |
April | 925.68 | 468.85 | 456.83 | 831.09 | 578.26 | 0.00 | 0.00 | 0.00 |
May | 1137.37 | 542.53 | 594.84 | 1238.37 | 307.90 | 0.00 | 0.00 | 0.00 |
June | 1097.53 | 474.57 | 622.97 | 1263.99 | 218.25 | 0.00 | 0.00 | 0.00 |
July | 1171.72 | 544.73 | 626.99 | 1393.72 | 205.66 | 0.00 | 0.00 | 0.00 |
August | 964.25 | 438.15 | 526.10 | 1105.54 | 246.11 | 0.00 | 0.00 | 0.00 |
September | 753.60 | 338.58 | 415.02 | 768.60 | 358.87 | 0.00 | 0.00 | 0.00 |
October | 476.05 | 191.11 | 284.94 | 360.51 | 570.84 | 0.00 | 0.00 | 0.00 |
November | 289.13 | 97.48 | 191.65 | 127.22 | 862.37 | 0.00 | 0.00 | 0.00 |
December | 257.74 | 90.21 | 167.53 | 70.10 | 1293.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 724.82 | 329.64 | 395.18 | 682.78 | 650.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 257.74 | 90.21 | 167.53 | 70.10 | 205.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1171.72 | 544.73 | 626.99 | 1393.72 | 1293.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 686.37 | 0.00 | 686.37 | 8.46 | 5754.73 | 0.00 | 0.00 | 0.00 |
February | 1054.32 | 0.00 | 1054.32 | 91.77 | 4580.48 | 0.00 | 0.00 | 0.00 |
March | 1297.16 | 0.00 | 1297.16 | 212.84 | 3590.67 | 0.00 | 0.00 | 0.00 |
April | 1700.50 | 13.27 | 1687.23 | 783.44 | 2191.44 | 0.00 | 0.00 | 0.00 |
May | 2391.69 | 128.79 | 2262.90 | 2070.89 | 1166.87 | 0.00 | 0.00 | 0.00 |
June | 2669.16 | 293.41 | 2375.75 | 2835.64 | 809.36 | 0.00 | 0.00 | 0.00 |
July | 2549.47 | 218.79 | 2330.68 | 2845.93 | 752.28 | 0.00 | 0.00 | 0.00 |
August | 1936.40 | 33.25 | 1903.15 | 1955.72 | 883.88 | 0.00 | 0.00 | 0.00 |
September | 1508.98 | 0.37 | 1508.61 | 1117.57 | 1451.07 | 0.00 | 0.00 | 0.00 |
October | 1047.76 | 0.00 | 1047.76 | 379.85 | 2232.26 | 0.00 | 0.00 | 0.00 |
November | 693.75 | 0.00 | 693.75 | 54.39 | 3415.50 | 0.00 | 0.00 | 0.00 |
December | 581.55 | 0.00 | 581.55 | 0.50 | 5525.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1512.04 | 57.58 | 1454.46 | 1035.62 | 2688.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 581.55 | 0.00 | 581.55 | 0.50 | 752.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2669.16 | 293.41 | 2375.75 | 2845.93 | 5754.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1003.21 | 418.77 | 584.44 | 382.08 | 3462.76 | 0.00 | 0.00 | 0.00 |
February | 1576.45 | 672.44 | 904.01 | 912.23 | 2753.61 | 0.00 | 0.00 | 0.00 |
March | 2148.02 | 1077.48 | 1070.54 | 1574.42 | 2209.13 | 0.00 | 0.00 | 0.00 |
April | 2977.78 | 1606.15 | 1371.62 | 2769.35 | 1384.21 | 0.00 | 0.00 | 0.00 |
May | 3222.83 | 1416.79 | 1806.04 | 3431.03 | 784.35 | 0.00 | 0.00 | 0.00 |
June | 3648.47 | 1745.26 | 1903.20 | 4251.22 | 548.83 | 0.00 | 0.00 | 0.00 |
July | 3574.15 | 1678.20 | 1895.96 | 4281.99 | 504.78 | 0.00 | 0.00 | 0.00 |
August | 2755.68 | 1204.42 | 1551.25 | 3172.12 | 582.26 | 0.00 | 0.00 | 0.00 |
September | 2206.84 | 987.77 | 1219.07 | 2252.01 | 917.39 | 0.00 | 0.00 | 0.00 |
October | 1336.28 | 506.71 | 829.56 | 1005.02 | 1403.09 | 0.00 | 0.00 | 0.00 |
November | 850.69 | 284.40 | 566.28 | 396.45 | 2108.82 | 0.00 | 0.00 | 0.00 |
December | 776.24 | 286.91 | 489.33 | 235.44 | 3367.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2175.24 | 991.24 | 1183.99 | 2060.71 | 1664.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 776.24 | 284.40 | 489.33 | 235.44 | 504.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3648.47 | 1745.26 | 1903.20 | 4281.99 | 3462.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4726.41 | 3288.06 | 1438.35 | 3870.09 | 4665.71 | 0.00 | 0.00 | 0.00 |
February | 5984.77 | 4042.32 | 1942.45 | 5501.28 | 3986.75 | 0.00 | 0.00 | 0.00 |
March | 5273.31 | 3337.27 | 1936.04 | 4960.62 | 3351.57 | 0.00 | 0.00 | 0.00 |
April | 4777.45 | 2593.07 | 2184.38 | 4908.60 | 2268.61 | 0.00 | 0.00 | 0.00 |
May | 4016.58 | 1373.17 | 2643.41 | 4493.37 | 1299.05 | 0.00 | 0.00 | 0.00 |
June | 3604.00 | 960.62 | 2643.37 | 4316.17 | 883.82 | 0.00 | 0.00 | 0.00 |
July | 3940.34 | 1248.28 | 2692.06 | 4930.39 | 814.35 | 0.00 | 0.00 | 0.00 |
August | 4208.06 | 1760.20 | 2447.86 | 5104.19 | 951.24 | 0.00 | 0.00 | 0.00 |
September | 4507.46 | 2400.56 | 2106.90 | 5046.04 | 1500.30 | 0.00 | 0.00 | 0.00 |
October | 3849.05 | 2263.82 | 1585.23 | 3790.99 | 2187.61 | 0.00 | 0.00 | 0.00 |
November | 3428.65 | 2151.83 | 1276.83 | 2985.47 | 3062.25 | 0.00 | 0.00 | 0.00 |
December | 3649.36 | 2392.93 | 1256.43 | 2750.85 | 4520.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4319.61 | 2306.69 | 2012.91 | 4379.84 | 2450.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 3428.65 | 960.62 | 1256.43 | 2750.85 | 814.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5984.77 | 4042.32 | 2692.06 | 5501.28 | 4665.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1013.95 | 424.58 | 589.37 | 417.72 | 3579.47 | 0.00 | 0.00 | 0.00 |
February | 1652.02 | 754.53 | 897.49 | 1051.11 | 2910.43 | 0.00 | 0.00 | 0.00 |
March | 2173.93 | 1112.39 | 1061.54 | 1672.99 | 2342.23 | 0.00 | 0.00 | 0.00 |
April | 2777.07 | 1406.56 | 1370.51 | 2576.14 | 1507.63 | 0.00 | 0.00 | 0.00 |
May | 3412.13 | 1627.60 | 1784.53 | 3738.63 | 876.37 | 0.00 | 0.00 | 0.00 |
June | 3292.63 | 1423.71 | 1868.92 | 3829.88 | 607.26 | 0.00 | 0.00 | 0.00 |
July | 3515.20 | 1634.20 | 1881.00 | 4218.12 | 576.88 | 0.00 | 0.00 | 0.00 |
August | 2892.78 | 1314.46 | 1578.32 | 3368.70 | 655.71 | 0.00 | 0.00 | 0.00 |
September | 2260.81 | 1015.75 | 1245.06 | 2344.26 | 994.88 | 0.00 | 0.00 | 0.00 |
October | 1428.17 | 573.33 | 854.84 | 1147.86 | 1488.41 | 0.00 | 0.00 | 0.00 |
November | 867.40 | 292.45 | 574.95 | 426.06 | 2203.57 | 0.00 | 0.00 | 0.00 |
December | 773.24 | 270.64 | 502.60 | 231.71 | 3476.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2174.48 | 988.92 | 1185.56 | 2091.48 | 1763.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 773.24 | 270.64 | 502.60 | 231.71 | 576.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3515.20 | 1634.20 | 1881.00 | 4218.12 | 3579.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 686.37 | 0.00 | 686.37 | 11.37 | 5647.75 | 0.00 | 0.00 | 0.00 |
February | 1054.32 | 0.00 | 1054.32 | 104.62 | 4442.78 | 0.00 | 0.00 | 0.00 |
March | 1297.16 | 0.00 | 1297.16 | 237.79 | 3437.07 | 0.00 | 0.00 | 0.00 |
April | 1700.50 | 13.27 | 1687.23 | 837.55 | 2042.73 | 0.00 | 0.00 | 0.00 |
May | 2391.69 | 128.79 | 2262.90 | 2099.97 | 1120.99 | 0.00 | 0.00 | 0.00 |
June | 2669.16 | 293.41 | 2375.75 | 2844.08 | 785.72 | 0.00 | 0.00 | 0.00 |
July | 2549.47 | 218.79 | 2330.68 | 2844.81 | 740.59 | 0.00 | 0.00 | 0.00 |
August | 1936.40 | 33.25 | 1903.15 | 1961.05 | 860.24 | 0.00 | 0.00 | 0.00 |
September | 1508.98 | 0.37 | 1508.61 | 1153.23 | 1366.43 | 0.00 | 0.00 | 0.00 |
October | 1047.76 | 0.00 | 1047.76 | 431.72 | 2045.01 | 0.00 | 0.00 | 0.00 |
November | 693.75 | 0.00 | 693.75 | 67.89 | 3212.19 | 0.00 | 0.00 | 0.00 |
December | 581.55 | 0.00 | 581.55 | 1.88 | 5404.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1512.04 | 57.58 | 1454.46 | 1055.50 | 2585.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 581.55 | 0.00 | 581.55 | 1.88 | 740.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2669.16 | 293.41 | 2375.75 | 2844.81 | 5647.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1003.21 | 418.77 | 584.44 | 388.23 | 3403.55 | 0.00 | 0.00 | 0.00 |
February | 1576.45 | 672.44 | 904.01 | 932.13 | 2669.53 | 0.00 | 0.00 | 0.00 |
March | 2148.02 | 1077.48 | 1070.54 | 1600.56 | 2115.42 | 0.00 | 0.00 | 0.00 |
April | 2977.78 | 1606.15 | 1371.62 | 2798.25 | 1305.46 | 0.00 | 0.00 | 0.00 |
May | 3222.83 | 1416.79 | 1806.04 | 3439.12 | 760.32 | 0.00 | 0.00 | 0.00 |
June | 3648.47 | 1745.26 | 1903.20 | 4248.59 | 535.82 | 0.00 | 0.00 | 0.00 |
July | 3574.15 | 1678.20 | 1895.96 | 4276.13 | 499.50 | 0.00 | 0.00 | 0.00 |
August | 2755.68 | 1204.42 | 1551.25 | 3169.12 | 571.54 | 0.00 | 0.00 | 0.00 |
September | 2206.84 | 987.77 | 1219.07 | 2267.88 | 876.22 | 0.00 | 0.00 | 0.00 |
October | 1336.28 | 506.71 | 829.56 | 1037.77 | 1302.66 | 0.00 | 0.00 | 0.00 |
November | 850.69 | 284.40 | 566.28 | 414.01 | 1985.95 | 0.00 | 0.00 | 0.00 |
December | 776.24 | 286.91 | 489.33 | 240.75 | 3296.51 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2175.24 | 991.24 | 1183.99 | 2073.05 | 1606.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 776.24 | 284.40 | 489.33 | 240.75 | 499.50 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3648.47 | 1745.26 | 1903.20 | 4276.13 | 3403.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4726.41 | 3288.06 | 1438.35 | 3895.27 | 4559.68 | 0.00 | 0.00 | 0.00 |
February | 5984.77 | 4042.32 | 1942.45 | 5540.63 | 3836.03 | 0.00 | 0.00 | 0.00 |
March | 5273.31 | 3337.27 | 1936.04 | 4998.52 | 3202.49 | 0.00 | 0.00 | 0.00 |
April | 4777.45 | 2593.07 | 2184.38 | 4946.03 | 2134.74 | 0.00 | 0.00 | 0.00 |
May | 4016.58 | 1373.17 | 2643.41 | 4504.47 | 1251.78 | 0.00 | 0.00 | 0.00 |
June | 3604.00 | 960.62 | 2643.37 | 4320.22 | 857.02 | 0.00 | 0.00 | 0.00 |
July | 3940.34 | 1248.28 | 2692.06 | 4925.52 | 800.77 | 0.00 | 0.00 | 0.00 |
August | 4208.06 | 1760.20 | 2447.86 | 5101.27 | 928.86 | 0.00 | 0.00 | 0.00 |
September | 4507.46 | 2400.56 | 2106.90 | 5066.24 | 1428.79 | 0.00 | 0.00 | 0.00 |
October | 3849.05 | 2263.82 | 1585.23 | 3845.78 | 2027.39 | 0.00 | 0.00 | 0.00 |
November | 3428.65 | 2151.83 | 1276.83 | 3034.32 | 2868.23 | 0.00 | 0.00 | 0.00 |
December | 3649.36 | 2392.93 | 1256.43 | 2777.64 | 4401.93 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4319.61 | 2306.69 | 2012.91 | 4404.51 | 2351.87 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 3428.65 | 960.62 | 1256.43 | 2777.64 | 800.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5984.77 | 4042.32 | 2692.06 | 5540.63 | 4559.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1013.95 | 424.58 | 589.37 | 422.92 | 3513.07 | 0.00 | 0.00 | 0.00 |
February | 1652.02 | 754.53 | 897.49 | 1062.60 | 2826.08 | 0.00 | 0.00 | 0.00 |
March | 2173.93 | 1112.39 | 1061.54 | 1687.86 | 2254.42 | 0.00 | 0.00 | 0.00 |
April | 2777.07 | 1406.56 | 1370.51 | 2597.59 | 1430.99 | 0.00 | 0.00 | 0.00 |
May | 3412.13 | 1627.60 | 1784.53 | 3745.25 | 849.39 | 0.00 | 0.00 | 0.00 |
June | 3292.63 | 1423.71 | 1868.92 | 3830.43 | 592.09 | 0.00 | 0.00 | 0.00 |
July | 3515.20 | 1634.20 | 1881.00 | 4212.74 | 568.89 | 0.00 | 0.00 | 0.00 |
August | 2892.78 | 1314.46 | 1578.32 | 3367.71 | 642.34 | 0.00 | 0.00 | 0.00 |
September | 2260.81 | 1015.75 | 1245.06 | 2358.68 | 952.35 | 0.00 | 0.00 | 0.00 |
October | 1428.17 | 573.33 | 854.84 | 1172.38 | 1396.81 | 0.00 | 0.00 | 0.00 |
November | 867.40 | 292.45 | 574.95 | 439.93 | 2090.05 | 0.00 | 0.00 | 0.00 |
December | 773.24 | 270.64 | 502.60 | 236.29 | 3408.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2174.48 | 988.92 | 1185.56 | 2100.69 | 1706.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 773.24 | 270.64 | 502.60 | 236.29 | 568.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3515.20 | 1634.20 | 1881.00 | 4212.74 | 3513.07 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.367681E+09 | 0.00 | 0.367681E+09 | 1403807.21 | 0.323803E+10 |
February | 0.510130E+09 | 0.00 | 0.510130E+09 | 27791006.16 | 0.237162E+10 |
March | 0.694872E+09 | 0.00 | 0.694872E+09 | 87388354.24 | 0.209683E+10 |
April | 0.881549E+09 | 6880384.05 | 0.874669E+09 | 0.345503E+09 | 0.131902E+10 |
May | 0.128119E+10 | 68990411.35 | 0.121220E+10 | 0.106807E+10 | 0.688943E+09 |
June | 0.138371E+10 | 0.152107E+09 | 0.123160E+10 | 0.143234E+10 | 0.465624E+09 |
July | 0.136572E+10 | 0.117204E+09 | 0.124851E+10 | 0.148266E+10 | 0.447271E+09 |
August | 0.103730E+10 | 17813684.08 | 0.101949E+10 | 0.100318E+10 | 0.541622E+09 |
September | 0.782265E+09 | 191758.42 | 0.782073E+09 | 0.538988E+09 | 0.858603E+09 |
October | 0.561271E+09 | 0.00 | 0.561271E+09 | 0.154122E+09 | 0.142109E+10 |
November | 0.359644E+09 | 0.00 | 0.359644E+09 | 16250618.15 | 0.208788E+10 |
December | 0.311529E+09 | 0.00 | 0.311529E+09 | 0.00 | 0.317827E+10 |
Annual Sum or Average | 0.953687E+10 | 0.363187E+09 | 0.917368E+10 | 0.615770E+10 | 0.187148E+11 |
Minimum of Months | 0.311529E+09 | 0.00 | 0.311529E+09 | 0.00 | 0.447271E+09 |
Maximum of Months | 0.138371E+10 | 0.152107E+09 | 0.124851E+10 | 0.148266E+10 | 0.323803E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.367681E+09 | 0.00 | 0.367681E+09 | 1403797.43 | 0.323803E+10 |
February | 0.510130E+09 | 0.00 | 0.510130E+09 | 27790898.15 | 0.237162E+10 |
March | 0.694871E+09 | 0.00 | 0.694871E+09 | 87388093.46 | 0.209683E+10 |
April | 0.881548E+09 | 6880375.79 | 0.874668E+09 | 0.345502E+09 | 0.131902E+10 |
May | 0.128119E+10 | 68990328.57 | 0.121220E+10 | 0.106806E+10 | 0.688943E+09 |
June | 0.138371E+10 | 0.152106E+09 | 0.123160E+10 | 0.143234E+10 | 0.465624E+09 |
July | 0.136571E+10 | 0.117204E+09 | 0.124851E+10 | 0.148265E+10 | 0.447270E+09 |
August | 0.103730E+10 | 17813662.71 | 0.101949E+10 | 0.100318E+10 | 0.541622E+09 |
September | 0.782265E+09 | 191758.19 | 0.782073E+09 | 0.538988E+09 | 0.858603E+09 |
October | 0.561270E+09 | 0.00 | 0.561270E+09 | 0.154122E+09 | 0.142109E+10 |
November | 0.359644E+09 | 0.00 | 0.359644E+09 | 16250567.39 | 0.208788E+10 |
December | 0.311529E+09 | 0.00 | 0.311529E+09 | 0.00 | 0.317827E+10 |
Annual Sum or Average | 0.953686E+10 | 0.363187E+09 | 0.917367E+10 | 0.615769E+10 | 0.187148E+11 |
Minimum of Months | 0.311529E+09 | 0.00 | 0.311529E+09 | 0.00 | 0.447270E+09 |
Maximum of Months | 0.138371E+10 | 0.152106E+09 | 0.124851E+10 | 0.148265E+10 | 0.323803E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.367681E+09 | 0.00 | 0.367681E+09 | 1403807.21 | 0.323803E+10 |
February | 0.510130E+09 | 0.00 | 0.510130E+09 | 27791006.16 | 0.237162E+10 |
March | 0.694872E+09 | 0.00 | 0.694872E+09 | 87388354.24 | 0.209683E+10 |
April | 0.881549E+09 | 6880384.05 | 0.874669E+09 | 0.345503E+09 | 0.131902E+10 |
May | 0.128119E+10 | 68990411.35 | 0.121220E+10 | 0.106807E+10 | 0.688943E+09 |
June | 0.138371E+10 | 0.152107E+09 | 0.123160E+10 | 0.143234E+10 | 0.465624E+09 |
July | 0.136572E+10 | 0.117204E+09 | 0.124851E+10 | 0.148266E+10 | 0.447271E+09 |
August | 0.103730E+10 | 17813684.08 | 0.101949E+10 | 0.100318E+10 | 0.541622E+09 |
September | 0.782265E+09 | 191758.42 | 0.782073E+09 | 0.538988E+09 | 0.858603E+09 |
October | 0.561271E+09 | 0.00 | 0.561271E+09 | 0.154122E+09 | 0.142109E+10 |
November | 0.359644E+09 | 0.00 | 0.359644E+09 | 16250618.15 | 0.208788E+10 |
December | 0.311529E+09 | 0.00 | 0.311529E+09 | 0.00 | 0.317827E+10 |
Annual Sum or Average | 0.953687E+10 | 0.363187E+09 | 0.917368E+10 | 0.615770E+10 | 0.187148E+11 |
Minimum of Months | 0.311529E+09 | 0.00 | 0.311529E+09 | 0.00 | 0.447271E+09 |
Maximum of Months | 0.138371E+10 | 0.152107E+09 | 0.124851E+10 | 0.148266E+10 | 0.323803E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.367681E+09 | 0.00 | 0.367681E+09 | 1403797.43 | 0.323803E+10 |
February | 0.510130E+09 | 0.00 | 0.510130E+09 | 27790898.15 | 0.237162E+10 |
March | 0.694871E+09 | 0.00 | 0.694871E+09 | 87388093.46 | 0.209683E+10 |
April | 0.881548E+09 | 6880375.79 | 0.874668E+09 | 0.345502E+09 | 0.131902E+10 |
May | 0.128119E+10 | 68990328.57 | 0.121220E+10 | 0.106806E+10 | 0.688943E+09 |
June | 0.138371E+10 | 0.152106E+09 | 0.123160E+10 | 0.143234E+10 | 0.465624E+09 |
July | 0.136571E+10 | 0.117204E+09 | 0.124851E+10 | 0.148265E+10 | 0.447270E+09 |
August | 0.103730E+10 | 17813662.71 | 0.101949E+10 | 0.100318E+10 | 0.541622E+09 |
September | 0.782265E+09 | 191758.19 | 0.782073E+09 | 0.538988E+09 | 0.858603E+09 |
October | 0.561270E+09 | 0.00 | 0.561270E+09 | 0.154122E+09 | 0.142109E+10 |
November | 0.359644E+09 | 0.00 | 0.359644E+09 | 16250567.39 | 0.208788E+10 |
December | 0.311529E+09 | 0.00 | 0.311529E+09 | 0.00 | 0.317827E+10 |
Annual Sum or Average | 0.953686E+10 | 0.363187E+09 | 0.917367E+10 | 0.615769E+10 | 0.187148E+11 |
Minimum of Months | 0.311529E+09 | 0.00 | 0.311529E+09 | 0.00 | 0.447270E+09 |
Maximum of Months | 0.138371E+10 | 0.152106E+09 | 0.124851E+10 | 0.148265E+10 | 0.323803E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.367667E+09 | 0.00 | 0.367667E+09 | 1403750.63 | 0.323790E+10 |
February | 0.510110E+09 | 0.00 | 0.510110E+09 | 27789886.06 | 0.237153E+10 |
March | 0.694844E+09 | 0.00 | 0.694844E+09 | 87384832.11 | 0.209675E+10 |
April | 0.881513E+09 | 6880106.74 | 0.874633E+09 | 0.345489E+09 | 0.131896E+10 |
May | 0.128114E+10 | 68987630.74 | 0.121216E+10 | 0.106802E+10 | 0.688915E+09 |
June | 0.138365E+10 | 0.152101E+09 | 0.123155E+10 | 0.143229E+10 | 0.465605E+09 |
July | 0.136566E+10 | 0.117200E+09 | 0.124846E+10 | 0.148260E+10 | 0.447253E+09 |
August | 0.103726E+10 | 17812966.11 | 0.101945E+10 | 0.100314E+10 | 0.541600E+09 |
September | 0.782234E+09 | 191750.69 | 0.782042E+09 | 0.538967E+09 | 0.858569E+09 |
October | 0.561248E+09 | 0.00 | 0.561248E+09 | 0.154116E+09 | 0.142103E+10 |
November | 0.359630E+09 | 0.00 | 0.359630E+09 | 16249963.18 | 0.208780E+10 |
December | 0.311517E+09 | 0.00 | 0.311517E+09 | 0.00 | 0.317814E+10 |
Annual Sum or Average | 0.953648E+10 | 0.363173E+09 | 0.917331E+10 | 0.615745E+10 | 0.187141E+11 |
Minimum of Months | 0.311517E+09 | 0.00 | 0.311517E+09 | 0.00 | 0.447253E+09 |
Maximum of Months | 0.138365E+10 | 0.152101E+09 | 0.124846E+10 | 0.148260E+10 | 0.323790E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.895674E+09 | 0.373882E+09 | 0.521792E+09 | 0.326031E+09 | 0.323537E+10 |
February | 0.127126E+10 | 0.542265E+09 | 0.729000E+09 | 0.707786E+09 | 0.235084E+10 |
March | 0.191777E+10 | 0.961982E+09 | 0.955788E+09 | 0.138501E+10 | 0.209780E+10 |
April | 0.257282E+10 | 0.138773E+10 | 0.118509E+10 | 0.235452E+10 | 0.133895E+10 |
May | 0.287737E+10 | 0.126492E+10 | 0.161245E+10 | 0.304188E+10 | 0.767064E+09 |
June | 0.315231E+10 | 0.150792E+10 | 0.164438E+10 | 0.365616E+10 | 0.521722E+09 |
July | 0.319104E+10 | 0.149831E+10 | 0.169273E+10 | 0.380270E+10 | 0.486429E+09 |
August | 0.246029E+10 | 0.107532E+10 | 0.138497E+10 | 0.280556E+10 | 0.577663E+09 |
September | 0.190673E+10 | 0.853441E+09 | 0.105329E+10 | 0.190582E+10 | 0.898110E+09 |
October | 0.119304E+10 | 0.452399E+09 | 0.740643E+09 | 0.835268E+09 | 0.145897E+10 |
November | 0.735000E+09 | 0.245727E+09 | 0.489272E+09 | 0.309603E+09 | 0.209897E+10 |
December | 0.693036E+09 | 0.256157E+09 | 0.436879E+09 | 0.198612E+09 | 0.319251E+10 |
Annual Sum or Average | 0.228663E+11 | 0.104201E+11 | 0.124463E+11 | 0.213290E+11 | 0.190244E+11 |
Minimum of Months | 0.693036E+09 | 0.245727E+09 | 0.436879E+09 | 0.198612E+09 | 0.486429E+09 |
Maximum of Months | 0.319104E+10 | 0.150792E+10 | 0.169273E+10 | 0.380270E+10 | 0.323537E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.895674E+09 | 0.373882E+09 | 0.521792E+09 | 0.326031E+09 | 0.323537E+10 |
February | 0.127126E+10 | 0.542265E+09 | 0.729000E+09 | 0.707786E+09 | 0.235084E+10 |
March | 0.191777E+10 | 0.961982E+09 | 0.955788E+09 | 0.138501E+10 | 0.209780E+10 |
April | 0.257282E+10 | 0.138773E+10 | 0.118509E+10 | 0.235452E+10 | 0.133895E+10 |
May | 0.287737E+10 | 0.126492E+10 | 0.161245E+10 | 0.304188E+10 | 0.767064E+09 |
June | 0.315231E+10 | 0.150792E+10 | 0.164438E+10 | 0.365616E+10 | 0.521722E+09 |
July | 0.319104E+10 | 0.149831E+10 | 0.169273E+10 | 0.380270E+10 | 0.486429E+09 |
August | 0.246029E+10 | 0.107532E+10 | 0.138497E+10 | 0.280556E+10 | 0.577663E+09 |
September | 0.190673E+10 | 0.853441E+09 | 0.105329E+10 | 0.190582E+10 | 0.898110E+09 |
October | 0.119304E+10 | 0.452399E+09 | 0.740643E+09 | 0.835268E+09 | 0.145897E+10 |
November | 0.735000E+09 | 0.245727E+09 | 0.489272E+09 | 0.309603E+09 | 0.209897E+10 |
December | 0.693036E+09 | 0.256157E+09 | 0.436879E+09 | 0.198612E+09 | 0.319251E+10 |
Annual Sum or Average | 0.228663E+11 | 0.104201E+11 | 0.124463E+11 | 0.213290E+11 | 0.190244E+11 |
Minimum of Months | 0.693036E+09 | 0.245727E+09 | 0.436879E+09 | 0.198612E+09 | 0.486429E+09 |
Maximum of Months | 0.319104E+10 | 0.150792E+10 | 0.169273E+10 | 0.380270E+10 | 0.323537E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.895658E+09 | 0.373875E+09 | 0.521782E+09 | 0.326025E+09 | 0.323531E+10 |
February | 0.127124E+10 | 0.542255E+09 | 0.728987E+09 | 0.707773E+09 | 0.235079E+10 |
March | 0.191774E+10 | 0.961965E+09 | 0.955771E+09 | 0.138498E+10 | 0.209777E+10 |
April | 0.257278E+10 | 0.138771E+10 | 0.118507E+10 | 0.235447E+10 | 0.133893E+10 |
May | 0.287732E+10 | 0.126490E+10 | 0.161242E+10 | 0.304183E+10 | 0.767050E+09 |
June | 0.315225E+10 | 0.150790E+10 | 0.164435E+10 | 0.365610E+10 | 0.521712E+09 |
July | 0.319098E+10 | 0.149828E+10 | 0.169270E+10 | 0.380263E+10 | 0.486420E+09 |
August | 0.246025E+10 | 0.107530E+10 | 0.138495E+10 | 0.280551E+10 | 0.577652E+09 |
September | 0.190669E+10 | 0.853425E+09 | 0.105327E+10 | 0.190578E+10 | 0.898094E+09 |
October | 0.119302E+10 | 0.452391E+09 | 0.740629E+09 | 0.835253E+09 | 0.145894E+10 |
November | 0.734986E+09 | 0.245723E+09 | 0.489263E+09 | 0.309597E+09 | 0.209893E+10 |
December | 0.693024E+09 | 0.256153E+09 | 0.436871E+09 | 0.198609E+09 | 0.319245E+10 |
Annual Sum or Average | 0.228659E+11 | 0.104199E+11 | 0.124461E+11 | 0.213286E+11 | 0.190240E+11 |
Minimum of Months | 0.693024E+09 | 0.245723E+09 | 0.436871E+09 | 0.198609E+09 | 0.486420E+09 |
Maximum of Months | 0.319098E+10 | 0.150790E+10 | 0.169270E+10 | 0.380263E+10 | 0.323531E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.253188E+10 | 0.176137E+10 | 0.770506E+09 | 0.206651E+10 | 0.256167E+10 |
February | 0.289571E+10 | 0.195586E+10 | 0.939845E+09 | 0.266769E+10 | 0.197985E+10 |
March | 0.282484E+10 | 0.178773E+10 | 0.103711E+10 | 0.266034E+10 | 0.185252E+10 |
April | 0.247666E+10 | 0.134426E+10 | 0.113240E+10 | 0.253067E+10 | 0.126587E+10 |
May | 0.215163E+10 | 0.735590E+09 | 0.141604E+10 | 0.239698E+10 | 0.740836E+09 |
June | 0.186833E+10 | 0.497993E+09 | 0.137034E+10 | 0.221856E+10 | 0.495594E+09 |
July | 0.211079E+10 | 0.668687E+09 | 0.144210E+10 | 0.262327E+10 | 0.467062E+09 |
August | 0.225420E+10 | 0.942914E+09 | 0.131128E+10 | 0.272077E+10 | 0.553089E+09 |
September | 0.233669E+10 | 0.124446E+10 | 0.109223E+10 | 0.260970E+10 | 0.832867E+09 |
October | 0.206188E+10 | 0.121270E+10 | 0.849187E+09 | 0.200829E+10 | 0.127226E+10 |
November | 0.177744E+10 | 0.111552E+10 | 0.661915E+09 | 0.152443E+10 | 0.172422E+10 |
December | 0.195491E+10 | 0.128186E+10 | 0.673052E+09 | 0.145884E+10 | 0.252466E+10 |
Annual Sum or Average | 0.272450E+11 | 0.145489E+11 | 0.126960E+11 | 0.274861E+11 | 0.162705E+11 |
Minimum of Months | 0.177744E+10 | 0.497993E+09 | 0.661915E+09 | 0.145884E+10 | 0.467062E+09 |
Maximum of Months | 0.289571E+10 | 0.195586E+10 | 0.144210E+10 | 0.272077E+10 | 0.256167E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.253187E+10 | 0.176137E+10 | 0.770505E+09 | 0.206651E+10 | 0.256167E+10 |
February | 0.289570E+10 | 0.195586E+10 | 0.939844E+09 | 0.266769E+10 | 0.197985E+10 |
March | 0.282484E+10 | 0.178773E+10 | 0.103711E+10 | 0.266034E+10 | 0.185252E+10 |
April | 0.247666E+10 | 0.134426E+10 | 0.113240E+10 | 0.253066E+10 | 0.126587E+10 |
May | 0.215163E+10 | 0.735590E+09 | 0.141604E+10 | 0.239698E+10 | 0.740836E+09 |
June | 0.186833E+10 | 0.497993E+09 | 0.137034E+10 | 0.221856E+10 | 0.495594E+09 |
July | 0.211078E+10 | 0.668686E+09 | 0.144210E+10 | 0.262327E+10 | 0.467062E+09 |
August | 0.225420E+10 | 0.942913E+09 | 0.131128E+10 | 0.272077E+10 | 0.553089E+09 |
September | 0.233669E+10 | 0.124446E+10 | 0.109223E+10 | 0.260970E+10 | 0.832867E+09 |
October | 0.206188E+10 | 0.121270E+10 | 0.849186E+09 | 0.200829E+10 | 0.127226E+10 |
November | 0.177743E+10 | 0.111552E+10 | 0.661914E+09 | 0.152442E+10 | 0.172422E+10 |
December | 0.195491E+10 | 0.128186E+10 | 0.673052E+09 | 0.145884E+10 | 0.252466E+10 |
Annual Sum or Average | 0.272449E+11 | 0.145489E+11 | 0.126960E+11 | 0.274860E+11 | 0.162705E+11 |
Minimum of Months | 0.177743E+10 | 0.497993E+09 | 0.661914E+09 | 0.145884E+10 | 0.467062E+09 |
Maximum of Months | 0.289570E+10 | 0.195586E+10 | 0.144210E+10 | 0.272077E+10 | 0.256167E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.253188E+10 | 0.176137E+10 | 0.770506E+09 | 0.206651E+10 | 0.256167E+10 |
February | 0.289571E+10 | 0.195586E+10 | 0.939845E+09 | 0.266769E+10 | 0.197985E+10 |
March | 0.282484E+10 | 0.178773E+10 | 0.103711E+10 | 0.266034E+10 | 0.185252E+10 |
April | 0.247666E+10 | 0.134426E+10 | 0.113240E+10 | 0.253067E+10 | 0.126587E+10 |
May | 0.215163E+10 | 0.735590E+09 | 0.141604E+10 | 0.239698E+10 | 0.740836E+09 |
June | 0.186833E+10 | 0.497993E+09 | 0.137034E+10 | 0.221856E+10 | 0.495594E+09 |
July | 0.211079E+10 | 0.668687E+09 | 0.144210E+10 | 0.262327E+10 | 0.467062E+09 |
August | 0.225420E+10 | 0.942914E+09 | 0.131128E+10 | 0.272077E+10 | 0.553089E+09 |
September | 0.233669E+10 | 0.124446E+10 | 0.109223E+10 | 0.260970E+10 | 0.832867E+09 |
October | 0.206188E+10 | 0.121270E+10 | 0.849187E+09 | 0.200829E+10 | 0.127226E+10 |
November | 0.177744E+10 | 0.111552E+10 | 0.661915E+09 | 0.152443E+10 | 0.172422E+10 |
December | 0.195491E+10 | 0.128186E+10 | 0.673052E+09 | 0.145884E+10 | 0.252466E+10 |
Annual Sum or Average | 0.272450E+11 | 0.145489E+11 | 0.126960E+11 | 0.274861E+11 | 0.162705E+11 |
Minimum of Months | 0.177744E+10 | 0.497993E+09 | 0.661915E+09 | 0.145884E+10 | 0.467062E+09 |
Maximum of Months | 0.289571E+10 | 0.195586E+10 | 0.144210E+10 | 0.272077E+10 | 0.256167E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.253187E+10 | 0.176137E+10 | 0.770505E+09 | 0.206651E+10 | 0.256167E+10 |
February | 0.289570E+10 | 0.195586E+10 | 0.939844E+09 | 0.266769E+10 | 0.197985E+10 |
March | 0.282484E+10 | 0.178773E+10 | 0.103711E+10 | 0.266034E+10 | 0.185252E+10 |
April | 0.247666E+10 | 0.134426E+10 | 0.113240E+10 | 0.253066E+10 | 0.126587E+10 |
May | 0.215163E+10 | 0.735590E+09 | 0.141604E+10 | 0.239698E+10 | 0.740836E+09 |
June | 0.186833E+10 | 0.497993E+09 | 0.137034E+10 | 0.221856E+10 | 0.495594E+09 |
July | 0.211078E+10 | 0.668686E+09 | 0.144210E+10 | 0.262327E+10 | 0.467062E+09 |
August | 0.225420E+10 | 0.942913E+09 | 0.131128E+10 | 0.272077E+10 | 0.553089E+09 |
September | 0.233669E+10 | 0.124446E+10 | 0.109223E+10 | 0.260970E+10 | 0.832867E+09 |
October | 0.206188E+10 | 0.121270E+10 | 0.849186E+09 | 0.200829E+10 | 0.127226E+10 |
November | 0.177743E+10 | 0.111552E+10 | 0.661914E+09 | 0.152442E+10 | 0.172422E+10 |
December | 0.195491E+10 | 0.128186E+10 | 0.673052E+09 | 0.145884E+10 | 0.252466E+10 |
Annual Sum or Average | 0.272449E+11 | 0.145489E+11 | 0.126960E+11 | 0.274860E+11 | 0.162705E+11 |
Minimum of Months | 0.177743E+10 | 0.497993E+09 | 0.661914E+09 | 0.145884E+10 | 0.467062E+09 |
Maximum of Months | 0.289570E+10 | 0.195586E+10 | 0.144210E+10 | 0.272077E+10 | 0.256167E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.253177E+10 | 0.176130E+10 | 0.770475E+09 | 0.206643E+10 | 0.256156E+10 |
February | 0.289559E+10 | 0.195578E+10 | 0.939807E+09 | 0.266759E+10 | 0.197977E+10 |
March | 0.282473E+10 | 0.178766E+10 | 0.103707E+10 | 0.266023E+10 | 0.185244E+10 |
April | 0.247656E+10 | 0.134421E+10 | 0.113235E+10 | 0.253056E+10 | 0.126582E+10 |
May | 0.215154E+10 | 0.735561E+09 | 0.141598E+10 | 0.239689E+10 | 0.740807E+09 |
June | 0.186826E+10 | 0.497973E+09 | 0.137029E+10 | 0.221847E+10 | 0.495574E+09 |
July | 0.211070E+10 | 0.668660E+09 | 0.144204E+10 | 0.262316E+10 | 0.467043E+09 |
August | 0.225411E+10 | 0.942876E+09 | 0.131123E+10 | 0.272066E+10 | 0.553067E+09 |
September | 0.233660E+10 | 0.124441E+10 | 0.109219E+10 | 0.260960E+10 | 0.832834E+09 |
October | 0.206180E+10 | 0.121265E+10 | 0.849153E+09 | 0.200821E+10 | 0.127221E+10 |
November | 0.177736E+10 | 0.111548E+10 | 0.661888E+09 | 0.152436E+10 | 0.172415E+10 |
December | 0.195483E+10 | 0.128181E+10 | 0.673025E+09 | 0.145878E+10 | 0.252456E+10 |
Annual Sum or Average | 0.272439E+11 | 0.145484E+11 | 0.126955E+11 | 0.274850E+11 | 0.162698E+11 |
Minimum of Months | 0.177736E+10 | 0.497973E+09 | 0.661888E+09 | 0.145878E+10 | 0.467043E+09 |
Maximum of Months | 0.289559E+10 | 0.195578E+10 | 0.144204E+10 | 0.272066E+10 | 0.256156E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.905261E+09 | 0.379070E+09 | 0.526191E+09 | 0.355392E+09 | 0.338719E+10 |
February | 0.133220E+10 | 0.608461E+09 | 0.723740E+09 | 0.814358E+09 | 0.254770E+10 |
March | 0.194090E+10 | 0.993147E+09 | 0.947756E+09 | 0.144584E+10 | 0.232444E+10 |
April | 0.239942E+10 | 0.121528E+10 | 0.118414E+10 | 0.215423E+10 | 0.149887E+10 |
May | 0.304638E+10 | 0.145314E+10 | 0.159324E+10 | 0.331692E+10 | 0.824695E+09 |
June | 0.284486E+10 | 0.123010E+10 | 0.161477E+10 | 0.327632E+10 | 0.565713E+09 |
July | 0.313840E+10 | 0.145903E+10 | 0.167937E+10 | 0.373302E+10 | 0.550852E+09 |
August | 0.258270E+10 | 0.117356E+10 | 0.140913E+10 | 0.296113E+10 | 0.659196E+09 |
September | 0.195336E+10 | 0.877617E+09 | 0.107575E+10 | 0.199225E+10 | 0.930211E+09 |
October | 0.127509E+10 | 0.511875E+09 | 0.763210E+09 | 0.965608E+09 | 0.152897E+10 |
November | 0.749443E+09 | 0.252684E+09 | 0.496759E+09 | 0.329751E+09 | 0.223531E+10 |
December | 0.690356E+09 | 0.241629E+09 | 0.448726E+09 | 0.187760E+09 | 0.346375E+10 |
Annual Sum or Average | 0.228584E+11 | 0.103956E+11 | 0.124628E+11 | 0.215326E+11 | 0.205169E+11 |
Minimum of Months | 0.690356E+09 | 0.241629E+09 | 0.448726E+09 | 0.187760E+09 | 0.550852E+09 |
Maximum of Months | 0.313840E+10 | 0.145903E+10 | 0.167937E+10 | 0.373302E+10 | 0.346375E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.905261E+09 | 0.379070E+09 | 0.526191E+09 | 0.355392E+09 | 0.338719E+10 |
February | 0.133220E+10 | 0.608461E+09 | 0.723740E+09 | 0.814358E+09 | 0.254770E+10 |
March | 0.194090E+10 | 0.993147E+09 | 0.947756E+09 | 0.144584E+10 | 0.232444E+10 |
April | 0.239942E+10 | 0.121528E+10 | 0.118414E+10 | 0.215423E+10 | 0.149887E+10 |
May | 0.304638E+10 | 0.145314E+10 | 0.159324E+10 | 0.331692E+10 | 0.824695E+09 |
June | 0.284486E+10 | 0.123010E+10 | 0.161477E+10 | 0.327632E+10 | 0.565713E+09 |
July | 0.313840E+10 | 0.145903E+10 | 0.167937E+10 | 0.373302E+10 | 0.550852E+09 |
August | 0.258270E+10 | 0.117356E+10 | 0.140913E+10 | 0.296113E+10 | 0.659196E+09 |
September | 0.195336E+10 | 0.877617E+09 | 0.107575E+10 | 0.199225E+10 | 0.930211E+09 |
October | 0.127509E+10 | 0.511875E+09 | 0.763210E+09 | 0.965608E+09 | 0.152897E+10 |
November | 0.749443E+09 | 0.252684E+09 | 0.496759E+09 | 0.329751E+09 | 0.223531E+10 |
December | 0.690356E+09 | 0.241629E+09 | 0.448726E+09 | 0.187760E+09 | 0.346375E+10 |
Annual Sum or Average | 0.228584E+11 | 0.103956E+11 | 0.124628E+11 | 0.215326E+11 | 0.205169E+11 |
Minimum of Months | 0.690356E+09 | 0.241629E+09 | 0.448726E+09 | 0.187760E+09 | 0.550852E+09 |
Maximum of Months | 0.313840E+10 | 0.145903E+10 | 0.167937E+10 | 0.373302E+10 | 0.346375E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.905245E+09 | 0.379063E+09 | 0.526182E+09 | 0.355386E+09 | 0.338712E+10 |
February | 0.133218E+10 | 0.608450E+09 | 0.723727E+09 | 0.814343E+09 | 0.254766E+10 |
March | 0.194087E+10 | 0.993129E+09 | 0.947738E+09 | 0.144582E+10 | 0.232439E+10 |
April | 0.239937E+10 | 0.121526E+10 | 0.118411E+10 | 0.215419E+10 | 0.149884E+10 |
May | 0.304632E+10 | 0.145311E+10 | 0.159321E+10 | 0.331686E+10 | 0.824680E+09 |
June | 0.284481E+10 | 0.123007E+10 | 0.161474E+10 | 0.327626E+10 | 0.565702E+09 |
July | 0.313835E+10 | 0.145901E+10 | 0.167934E+10 | 0.373295E+10 | 0.550842E+09 |
August | 0.258265E+10 | 0.117354E+10 | 0.140911E+10 | 0.296107E+10 | 0.659184E+09 |
September | 0.195333E+10 | 0.877601E+09 | 0.107573E+10 | 0.199221E+10 | 0.930194E+09 |
October | 0.127506E+10 | 0.511866E+09 | 0.763196E+09 | 0.965591E+09 | 0.152894E+10 |
November | 0.749429E+09 | 0.252679E+09 | 0.496750E+09 | 0.329745E+09 | 0.223527E+10 |
December | 0.690343E+09 | 0.241625E+09 | 0.448718E+09 | 0.187757E+09 | 0.346369E+10 |
Annual Sum or Average | 0.228580E+11 | 0.103954E+11 | 0.124625E+11 | 0.215322E+11 | 0.205165E+11 |
Minimum of Months | 0.690343E+09 | 0.241625E+09 | 0.448718E+09 | 0.187757E+09 | 0.550842E+09 |
Maximum of Months | 0.313835E+10 | 0.145901E+10 | 0.167934E+10 | 0.373295E+10 | 0.346369E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183838E+10 | 0.00 | 0.183838E+10 | 22669027.07 | 0.154135E+11 |
February | 0.255062E+10 | 0.00 | 0.255062E+10 | 0.222016E+09 | 0.110811E+11 |
March | 0.347432E+10 | 0.00 | 0.347432E+10 | 0.570076E+09 | 0.961726E+10 |
April | 0.440769E+10 | 34401504.24 | 0.437329E+10 | 0.203068E+10 | 0.568022E+10 |
May | 0.640589E+10 | 0.344948E+09 | 0.606095E+10 | 0.554668E+10 | 0.312534E+10 |
June | 0.691846E+10 | 0.760524E+09 | 0.615794E+10 | 0.734998E+10 | 0.209785E+10 |
July | 0.682850E+10 | 0.586014E+09 | 0.624248E+10 | 0.762255E+10 | 0.201491E+10 |
August | 0.518646E+10 | 89067343.42 | 0.509739E+10 | 0.523821E+10 | 0.236740E+10 |
September | 0.391128E+10 | 958780.49 | 0.391032E+10 | 0.289675E+10 | 0.376117E+10 |
October | 0.280632E+10 | 0.00 | 0.280632E+10 | 0.101739E+10 | 0.597889E+10 |
November | 0.179820E+10 | 0.00 | 0.179820E+10 | 0.140976E+09 | 0.885297E+10 |
December | 0.155763E+10 | 0.00 | 0.155763E+10 | 1342323.90 | 0.148004E+11 |
Annual Sum or Average | 0.476837E+11 | 0.181591E+10 | 0.458678E+11 | 0.326593E+11 | 0.847909E+11 |
Minimum of Months | 0.155763E+10 | 0.00 | 0.155763E+10 | 1342323.90 | 0.201491E+10 |
Maximum of Months | 0.691846E+10 | 0.760524E+09 | 0.624248E+10 | 0.762255E+10 | 0.154135E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.268699E+10 | 0.112164E+10 | 0.156536E+10 | 0.102335E+10 | 0.927467E+10 |
February | 0.381376E+10 | 0.162678E+10 | 0.218698E+10 | 0.220687E+10 | 0.666153E+10 |
March | 0.575325E+10 | 0.288592E+10 | 0.286733E+10 | 0.421693E+10 | 0.591694E+10 |
April | 0.771840E+10 | 0.416315E+10 | 0.355525E+10 | 0.717816E+10 | 0.358787E+10 |
May | 0.863202E+10 | 0.379474E+10 | 0.483729E+10 | 0.918966E+10 | 0.210080E+10 |
June | 0.945682E+10 | 0.452372E+10 | 0.493310E+10 | 0.110192E+11 | 0.142257E+10 |
July | 0.957301E+10 | 0.449488E+10 | 0.507813E+10 | 0.114689E+11 | 0.135200E+10 |
August | 0.738081E+10 | 0.322593E+10 | 0.415488E+10 | 0.849620E+10 | 0.155953E+10 |
September | 0.572012E+10 | 0.256030E+10 | 0.315982E+10 | 0.583720E+10 | 0.237787E+10 |
October | 0.357909E+10 | 0.135718E+10 | 0.222190E+10 | 0.269185E+10 | 0.375805E+10 |
November | 0.220498E+10 | 0.737174E+09 | 0.146780E+10 | 0.102761E+10 | 0.546607E+10 |
December | 0.207909E+10 | 0.768464E+09 | 0.131062E+10 | 0.630616E+09 | 0.902069E+10 |
Annual Sum or Average | 0.685983E+11 | 0.312599E+11 | 0.373385E+11 | 0.649865E+11 | 0.524986E+11 |
Minimum of Months | 0.207909E+10 | 0.737174E+09 | 0.131062E+10 | 0.630616E+09 | 0.135200E+10 |
Maximum of Months | 0.957301E+10 | 0.452372E+10 | 0.507813E+10 | 0.114689E+11 | 0.927467E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126592E+11 | 0.880674E+10 | 0.385248E+10 | 0.103657E+11 | 0.124966E+11 |
February | 0.144784E+11 | 0.977919E+10 | 0.469917E+10 | 0.133087E+11 | 0.964475E+10 |
March | 0.141240E+11 | 0.893855E+10 | 0.518548E+10 | 0.132865E+11 | 0.897686E+10 |
April | 0.123832E+11 | 0.672123E+10 | 0.566192E+10 | 0.127231E+11 | 0.588024E+10 |
May | 0.107580E+11 | 0.367791E+10 | 0.708010E+10 | 0.120351E+11 | 0.347938E+10 |
June | 0.934156E+10 | 0.248994E+10 | 0.685162E+10 | 0.111875E+11 | 0.229086E+10 |
July | 0.105538E+11 | 0.334339E+10 | 0.721041E+10 | 0.132055E+11 | 0.218115E+10 |
August | 0.112709E+11 | 0.471451E+10 | 0.655634E+10 | 0.136711E+11 | 0.254781E+10 |
September | 0.116833E+11 | 0.622225E+10 | 0.546108E+10 | 0.130793E+11 | 0.388877E+10 |
October | 0.103093E+11 | 0.606341E+10 | 0.424588E+10 | 0.101538E+11 | 0.585930E+10 |
November | 0.888707E+10 | 0.557754E+10 | 0.330953E+10 | 0.773834E+10 | 0.793735E+10 |
December | 0.977444E+10 | 0.640922E+10 | 0.336522E+10 | 0.736787E+10 | 0.121073E+11 |
Annual Sum or Average | 0.136223E+12 | 0.727439E+11 | 0.634792E+11 | 0.138122E+12 | 0.772904E+11 |
Minimum of Months | 0.888707E+10 | 0.248994E+10 | 0.330953E+10 | 0.736787E+10 | 0.218115E+10 |
Maximum of Months | 0.144784E+11 | 0.977919E+10 | 0.721041E+10 | 0.136711E+11 | 0.124966E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.271576E+10 | 0.113720E+10 | 0.157856E+10 | 0.111882E+10 | 0.958725E+10 |
February | 0.399656E+10 | 0.182536E+10 | 0.217120E+10 | 0.254286E+10 | 0.704090E+10 |
March | 0.582265E+10 | 0.297941E+10 | 0.284324E+10 | 0.448094E+10 | 0.627342E+10 |
April | 0.719818E+10 | 0.364581E+10 | 0.355237E+10 | 0.667735E+10 | 0.390777E+10 |
May | 0.913905E+10 | 0.435937E+10 | 0.477968E+10 | 0.100135E+11 | 0.234727E+10 |
June | 0.853450E+10 | 0.369025E+10 | 0.484425E+10 | 0.992706E+10 | 0.157402E+10 |
July | 0.941511E+10 | 0.437705E+10 | 0.503806E+10 | 0.112978E+11 | 0.154510E+10 |
August | 0.774801E+10 | 0.352065E+10 | 0.422736E+10 | 0.902272E+10 | 0.175626E+10 |
September | 0.586003E+10 | 0.263283E+10 | 0.322721E+10 | 0.607631E+10 | 0.257874E+10 |
October | 0.382522E+10 | 0.153561E+10 | 0.228961E+10 | 0.307444E+10 | 0.398655E+10 |
November | 0.224831E+10 | 0.758043E+09 | 0.149026E+10 | 0.110436E+10 | 0.571165E+10 |
December | 0.207105E+10 | 0.724881E+09 | 0.134617E+10 | 0.620612E+09 | 0.931169E+10 |
Annual Sum or Average | 0.685744E+11 | 0.311865E+11 | 0.373879E+11 | 0.659568E+11 | 0.556206E+11 |
Minimum of Months | 0.207105E+10 | 0.724881E+09 | 0.134617E+10 | 0.620612E+09 | 0.154510E+10 |
Maximum of Months | 0.941511E+10 | 0.437705E+10 | 0.503806E+10 | 0.112978E+11 | 0.958725E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.183838E+10 | 0.00 | 0.183838E+10 | 30451338.61 | 0.151269E+11 |
February | 0.255062E+10 | 0.00 | 0.255062E+10 | 0.253088E+09 | 0.107480E+11 |
March | 0.347432E+10 | 0.00 | 0.347432E+10 | 0.636909E+09 | 0.920585E+10 |
April | 0.440769E+10 | 34401504.24 | 0.437329E+10 | 0.217093E+10 | 0.529476E+10 |
May | 0.640589E+10 | 0.344948E+09 | 0.606095E+10 | 0.562456E+10 | 0.300246E+10 |
June | 0.691846E+10 | 0.760524E+09 | 0.615794E+10 | 0.737186E+10 | 0.203659E+10 |
July | 0.682850E+10 | 0.586014E+09 | 0.624248E+10 | 0.761953E+10 | 0.198358E+10 |
August | 0.518646E+10 | 89067343.42 | 0.509739E+10 | 0.525247E+10 | 0.230406E+10 |
September | 0.391128E+10 | 958780.49 | 0.391032E+10 | 0.298916E+10 | 0.354178E+10 |
October | 0.280632E+10 | 0.00 | 0.280632E+10 | 0.115633E+10 | 0.547735E+10 |
November | 0.179820E+10 | 0.00 | 0.179820E+10 | 0.175975E+09 | 0.832598E+10 |
December | 0.155763E+10 | 0.00 | 0.155763E+10 | 5048274.70 | 0.144752E+11 |
Annual Sum or Average | 0.476837E+11 | 0.181591E+10 | 0.458678E+11 | 0.332863E+11 | 0.815226E+11 |
Minimum of Months | 0.155763E+10 | 0.00 | 0.155763E+10 | 5048274.70 | 0.198358E+10 |
Maximum of Months | 0.691846E+10 | 0.760524E+09 | 0.624248E+10 | 0.761953E+10 | 0.151269E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.268699E+10 | 0.112164E+10 | 0.156536E+10 | 0.103985E+10 | 0.911606E+10 |
February | 0.381376E+10 | 0.162678E+10 | 0.218698E+10 | 0.225501E+10 | 0.645813E+10 |
March | 0.575325E+10 | 0.288592E+10 | 0.286733E+10 | 0.428694E+10 | 0.566595E+10 |
April | 0.771840E+10 | 0.416315E+10 | 0.355525E+10 | 0.725305E+10 | 0.338375E+10 |
May | 0.863202E+10 | 0.379474E+10 | 0.483729E+10 | 0.921135E+10 | 0.203645E+10 |
June | 0.945682E+10 | 0.452372E+10 | 0.493310E+10 | 0.110124E+11 | 0.138885E+10 |
July | 0.957301E+10 | 0.449488E+10 | 0.507813E+10 | 0.114532E+11 | 0.133786E+10 |
August | 0.738081E+10 | 0.322593E+10 | 0.415488E+10 | 0.848818E+10 | 0.153082E+10 |
September | 0.572012E+10 | 0.256030E+10 | 0.315982E+10 | 0.587834E+10 | 0.227115E+10 |
October | 0.357909E+10 | 0.135718E+10 | 0.222190E+10 | 0.277955E+10 | 0.348904E+10 |
November | 0.220498E+10 | 0.737174E+09 | 0.146780E+10 | 0.107312E+10 | 0.514759E+10 |
December | 0.207909E+10 | 0.768464E+09 | 0.131062E+10 | 0.644824E+09 | 0.882937E+10 |
Annual Sum or Average | 0.685983E+11 | 0.312599E+11 | 0.373385E+11 | 0.653758E+11 | 0.506550E+11 |
Minimum of Months | 0.207909E+10 | 0.737174E+09 | 0.131062E+10 | 0.644824E+09 | 0.133786E+10 |
Maximum of Months | 0.957301E+10 | 0.452372E+10 | 0.507813E+10 | 0.114532E+11 | 0.911606E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.126592E+11 | 0.880674E+10 | 0.385248E+10 | 0.104331E+11 | 0.122127E+11 |
February | 0.144784E+11 | 0.977919E+10 | 0.469917E+10 | 0.134039E+11 | 0.928013E+10 |
March | 0.141240E+11 | 0.893855E+10 | 0.518548E+10 | 0.133880E+11 | 0.857755E+10 |
April | 0.123832E+11 | 0.672123E+10 | 0.566192E+10 | 0.128201E+11 | 0.553325E+10 |
May | 0.107580E+11 | 0.367791E+10 | 0.708010E+10 | 0.120648E+11 | 0.335277E+10 |
June | 0.934156E+10 | 0.248994E+10 | 0.685162E+10 | 0.111980E+11 | 0.222139E+10 |
July | 0.105538E+11 | 0.334339E+10 | 0.721041E+10 | 0.131925E+11 | 0.214478E+10 |
August | 0.112709E+11 | 0.471451E+10 | 0.655634E+10 | 0.136632E+11 | 0.248785E+10 |
September | 0.116833E+11 | 0.622225E+10 | 0.546108E+10 | 0.131317E+11 | 0.370342E+10 |
October | 0.103093E+11 | 0.606341E+10 | 0.424588E+10 | 0.103005E+11 | 0.543016E+10 |
November | 0.888707E+10 | 0.557754E+10 | 0.330953E+10 | 0.786495E+10 | 0.743444E+10 |
December | 0.977444E+10 | 0.640922E+10 | 0.336522E+10 | 0.743964E+10 | 0.117901E+11 |
Annual Sum or Average | 0.136223E+12 | 0.727439E+11 | 0.634792E+11 | 0.138900E+12 | 0.741685E+11 |
Minimum of Months | 0.888707E+10 | 0.248994E+10 | 0.330953E+10 | 0.743964E+10 | 0.214478E+10 |
Maximum of Months | 0.144784E+11 | 0.977919E+10 | 0.721041E+10 | 0.136632E+11 | 0.122127E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.271576E+10 | 0.113720E+10 | 0.157856E+10 | 0.113276E+10 | 0.940941E+10 |
February | 0.399656E+10 | 0.182536E+10 | 0.217120E+10 | 0.257064E+10 | 0.683686E+10 |
March | 0.582265E+10 | 0.297941E+10 | 0.284324E+10 | 0.452075E+10 | 0.603823E+10 |
April | 0.719818E+10 | 0.364581E+10 | 0.355237E+10 | 0.673296E+10 | 0.370912E+10 |
May | 0.913905E+10 | 0.435937E+10 | 0.477968E+10 | 0.100313E+11 | 0.227500E+10 |
June | 0.853450E+10 | 0.369025E+10 | 0.484425E+10 | 0.992847E+10 | 0.153470E+10 |
July | 0.941511E+10 | 0.437705E+10 | 0.503806E+10 | 0.112834E+11 | 0.152371E+10 |
August | 0.774801E+10 | 0.352065E+10 | 0.422736E+10 | 0.902006E+10 | 0.172044E+10 |
September | 0.586003E+10 | 0.263283E+10 | 0.322721E+10 | 0.611369E+10 | 0.246850E+10 |
October | 0.382522E+10 | 0.153561E+10 | 0.228961E+10 | 0.314010E+10 | 0.374122E+10 |
November | 0.224831E+10 | 0.758043E+09 | 0.149026E+10 | 0.114030E+10 | 0.541741E+10 |
December | 0.207105E+10 | 0.724881E+09 | 0.134617E+10 | 0.632874E+09 | 0.912960E+10 |
Annual Sum or Average | 0.685744E+11 | 0.311865E+11 | 0.373879E+11 | 0.662473E+11 | 0.538042E+11 |
Minimum of Months | 0.207105E+10 | 0.724881E+09 | 0.134617E+10 | 0.632874E+09 | 0.152371E+10 |
Maximum of Months | 0.941511E+10 | 0.437705E+10 | 0.503806E+10 | 0.112834E+11 | 0.940941E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2.62 | 6044.66 | 686.38 | 0.00 | 686.38 | 0.00 | 0.00 |
February | 57.44 | 4901.63 | 1054.33 | 0.00 | 1054.33 | 0.00 | 0.00 |
March | 163.13 | 3914.31 | 1297.17 | 0.00 | 1297.17 | 0.00 | 0.00 |
April | 666.47 | 2544.38 | 1700.50 | 13.27 | 1687.23 | 0.00 | 0.00 |
May | 1993.83 | 1286.10 | 2391.70 | 128.79 | 2262.91 | 0.00 | 0.00 |
June | 2762.98 | 898.19 | 2669.17 | 293.41 | 2375.76 | 0.00 | 0.00 |
July | 2767.78 | 834.95 | 2549.48 | 218.79 | 2330.68 | 0.00 | 0.00 |
August | 1872.71 | 1011.08 | 1936.41 | 33.25 | 1903.15 | 0.00 | 0.00 |
September | 1039.71 | 1656.24 | 1508.99 | 0.37 | 1508.62 | 0.00 | 0.00 |
October | 287.71 | 2652.84 | 1047.76 | 0.00 | 1047.76 | 0.00 | 0.00 |
November | 31.35 | 4027.52 | 693.75 | 0.00 | 693.75 | 0.00 | 0.00 |
December | 0.00 | 5933.11 | 581.55 | 0.00 | 581.55 | 0.00 | 0.00 |
Annual Sum or Average | 976.29 | 2967.19 | 1512.05 | 57.58 | 1454.46 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 834.95 | 581.55 | 0.00 | 581.55 | 0.00 | 0.00 |
Maximum of Months | 2767.78 | 6044.66 | 2669.17 | 293.41 | 2375.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 365.18 | 3623.83 | 1003.21 | 418.77 | 584.44 | 0.00 | 0.00 |
February | 877.71 | 2915.21 | 1576.46 | 672.45 | 904.01 | 0.00 | 0.00 |
March | 1551.30 | 2349.68 | 2148.03 | 1077.48 | 1070.54 | 0.00 | 0.00 |
April | 2725.12 | 1549.70 | 2977.79 | 1606.16 | 1371.63 | 0.00 | 0.00 |
May | 3407.10 | 859.16 | 3222.84 | 1416.80 | 1806.04 | 0.00 | 0.00 |
June | 4231.64 | 603.84 | 3648.48 | 1745.27 | 1903.21 | 0.00 | 0.00 |
July | 4259.27 | 544.83 | 3574.17 | 1678.20 | 1895.96 | 0.00 | 0.00 |
August | 3142.41 | 647.02 | 2755.69 | 1204.43 | 1551.26 | 0.00 | 0.00 |
September | 2205.80 | 1039.47 | 2206.85 | 987.77 | 1219.07 | 0.00 | 0.00 |
October | 935.55 | 1634.14 | 1336.28 | 506.72 | 829.57 | 0.00 | 0.00 |
November | 358.33 | 2429.35 | 850.69 | 284.40 | 566.28 | 0.00 | 0.00 |
December | 222.46 | 3575.82 | 776.25 | 286.91 | 489.33 | 0.00 | 0.00 |
Annual Sum or Average | 2029.00 | 1809.77 | 2175.25 | 991.25 | 1184.00 | 0.00 | 0.00 |
Minimum of Months | 222.46 | 544.83 | 776.25 | 284.40 | 489.33 | 0.00 | 0.00 |
Maximum of Months | 4259.27 | 3623.83 | 3648.48 | 1745.27 | 1903.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3857.70 | 4782.05 | 4726.43 | 3288.07 | 1438.36 | 0.00 | 0.00 |
February | 5513.54 | 4091.92 | 5984.79 | 4042.34 | 1942.45 | 0.00 | 0.00 |
March | 4966.24 | 3458.23 | 5273.33 | 3337.28 | 1936.04 | 0.00 | 0.00 |
April | 4881.65 | 2441.86 | 4777.47 | 2593.08 | 2184.39 | 0.00 | 0.00 |
May | 4474.62 | 1382.97 | 4016.60 | 1373.18 | 2643.42 | 0.00 | 0.00 |
June | 4279.60 | 956.00 | 3604.01 | 960.63 | 2643.38 | 0.00 | 0.00 |
July | 4897.04 | 871.90 | 3940.35 | 1248.28 | 2692.07 | 0.00 | 0.00 |
August | 5079.06 | 1032.49 | 4208.07 | 1760.20 | 2447.87 | 0.00 | 0.00 |
September | 5034.11 | 1606.60 | 4507.47 | 2400.57 | 2106.91 | 0.00 | 0.00 |
October | 3749.02 | 2375.02 | 3849.06 | 2263.83 | 1585.24 | 0.00 | 0.00 |
November | 2940.61 | 3326.01 | 3428.67 | 2151.84 | 1276.83 | 0.00 | 0.00 |
December | 2723.32 | 4712.97 | 3649.37 | 2392.94 | 1256.43 | 0.00 | 0.00 |
Annual Sum or Average | 4357.85 | 2579.65 | 4319.62 | 2306.70 | 2012.92 | 0.00 | 0.00 |
Minimum of Months | 2723.32 | 871.90 | 3428.67 | 960.63 | 1256.43 | 0.00 | 0.00 |
Maximum of Months | 5513.54 | 4782.05 | 5984.79 | 4042.34 | 2692.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 398.06 | 3793.87 | 1013.95 | 424.58 | 589.37 | 0.00 | 0.00 |
February | 1009.86 | 3159.33 | 1652.02 | 754.54 | 897.49 | 0.00 | 0.00 |
March | 1619.44 | 2603.52 | 2173.94 | 1112.39 | 1061.55 | 0.00 | 0.00 |
April | 2493.30 | 1734.79 | 2777.09 | 1406.57 | 1370.52 | 0.00 | 0.00 |
May | 3715.17 | 923.71 | 3412.14 | 1627.61 | 1784.53 | 0.00 | 0.00 |
June | 3792.01 | 654.76 | 3292.64 | 1423.71 | 1868.93 | 0.00 | 0.00 |
July | 4181.22 | 616.99 | 3515.21 | 1634.21 | 1881.00 | 0.00 | 0.00 |
August | 3316.66 | 738.34 | 2892.79 | 1314.47 | 1578.32 | 0.00 | 0.00 |
September | 2305.83 | 1076.63 | 2260.82 | 1015.75 | 1245.07 | 0.00 | 0.00 |
October | 1081.54 | 1712.55 | 1428.18 | 573.33 | 854.84 | 0.00 | 0.00 |
November | 381.65 | 2587.15 | 867.41 | 292.46 | 574.95 | 0.00 | 0.00 |
December | 210.30 | 3879.62 | 773.24 | 270.64 | 502.60 | 0.00 | 0.00 |
Annual Sum or Average | 2048.37 | 1951.75 | 2174.49 | 988.92 | 1185.57 | 0.00 | 0.00 |
Minimum of Months | 210.30 | 616.99 | 773.24 | 270.64 | 502.60 | 0.00 | 0.00 |
Maximum of Months | 4181.22 | 3879.62 | 3515.21 | 1634.21 | 1881.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 8.46 | 5754.73 | 686.37 | 0.00 | 686.37 | 0.00 | 0.00 |
February | 91.77 | 4580.48 | 1054.32 | 0.00 | 1054.32 | 0.00 | 0.00 |
March | 212.84 | 3590.67 | 1297.16 | 0.00 | 1297.16 | 0.00 | 0.00 |
April | 783.44 | 2191.44 | 1700.50 | 13.27 | 1687.23 | 0.00 | 0.00 |
May | 2070.89 | 1166.87 | 2391.69 | 128.79 | 2262.90 | 0.00 | 0.00 |
June | 2835.64 | 809.36 | 2669.16 | 293.41 | 2375.75 | 0.00 | 0.00 |
July | 2845.93 | 752.28 | 2549.47 | 218.79 | 2330.68 | 0.00 | 0.00 |
August | 1955.72 | 883.88 | 1936.40 | 33.25 | 1903.15 | 0.00 | 0.00 |
September | 1117.57 | 1451.07 | 1508.98 | 0.37 | 1508.61 | 0.00 | 0.00 |
October | 379.85 | 2232.26 | 1047.76 | 0.00 | 1047.76 | 0.00 | 0.00 |
November | 54.39 | 3415.50 | 693.75 | 0.00 | 693.75 | 0.00 | 0.00 |
December | 0.50 | 5525.83 | 581.55 | 0.00 | 581.55 | 0.00 | 0.00 |
Annual Sum or Average | 1035.62 | 2688.70 | 1512.04 | 57.58 | 1454.46 | 0.00 | 0.00 |
Minimum of Months | 0.50 | 752.28 | 581.55 | 0.00 | 581.55 | 0.00 | 0.00 |
Maximum of Months | 2845.93 | 5754.73 | 2669.16 | 293.41 | 2375.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 382.08 | 3462.76 | 1003.21 | 418.77 | 584.44 | 0.00 | 0.00 |
February | 912.23 | 2753.61 | 1576.45 | 672.44 | 904.01 | 0.00 | 0.00 |
March | 1574.42 | 2209.13 | 2148.02 | 1077.48 | 1070.54 | 0.00 | 0.00 |
April | 2769.35 | 1384.21 | 2977.78 | 1606.15 | 1371.62 | 0.00 | 0.00 |
May | 3431.03 | 784.35 | 3222.83 | 1416.79 | 1806.04 | 0.00 | 0.00 |
June | 4251.22 | 548.83 | 3648.47 | 1745.26 | 1903.20 | 0.00 | 0.00 |
July | 4281.99 | 504.78 | 3574.15 | 1678.20 | 1895.96 | 0.00 | 0.00 |
August | 3172.12 | 582.26 | 2755.68 | 1204.42 | 1551.25 | 0.00 | 0.00 |
September | 2252.01 | 917.39 | 2206.84 | 987.77 | 1219.07 | 0.00 | 0.00 |
October | 1005.02 | 1403.09 | 1336.28 | 506.71 | 829.56 | 0.00 | 0.00 |
November | 396.45 | 2108.82 | 850.69 | 284.40 | 566.28 | 0.00 | 0.00 |
December | 235.44 | 3367.94 | 776.24 | 286.91 | 489.33 | 0.00 | 0.00 |
Annual Sum or Average | 2060.71 | 1664.72 | 2175.24 | 991.24 | 1183.99 | 0.00 | 0.00 |
Minimum of Months | 235.44 | 504.78 | 776.24 | 284.40 | 489.33 | 0.00 | 0.00 |
Maximum of Months | 4281.99 | 3462.76 | 3648.47 | 1745.26 | 1903.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3870.09 | 4665.71 | 4726.41 | 3288.06 | 1438.35 | 0.00 | 0.00 |
February | 5501.28 | 3986.75 | 5984.77 | 4042.32 | 1942.45 | 0.00 | 0.00 |
March | 4960.62 | 3351.57 | 5273.31 | 3337.27 | 1936.04 | 0.00 | 0.00 |
April | 4908.60 | 2268.61 | 4777.45 | 2593.07 | 2184.38 | 0.00 | 0.00 |
May | 4493.37 | 1299.05 | 4016.58 | 1373.17 | 2643.41 | 0.00 | 0.00 |
June | 4316.17 | 883.82 | 3604.00 | 960.62 | 2643.37 | 0.00 | 0.00 |
July | 4930.39 | 814.35 | 3940.34 | 1248.28 | 2692.06 | 0.00 | 0.00 |
August | 5104.19 | 951.24 | 4208.06 | 1760.20 | 2447.86 | 0.00 | 0.00 |
September | 5046.04 | 1500.30 | 4507.46 | 2400.56 | 2106.90 | 0.00 | 0.00 |
October | 3790.99 | 2187.61 | 3849.05 | 2263.82 | 1585.23 | 0.00 | 0.00 |
November | 2985.47 | 3062.25 | 3428.65 | 2151.83 | 1276.83 | 0.00 | 0.00 |
December | 2750.85 | 4520.35 | 3649.36 | 2392.93 | 1256.43 | 0.00 | 0.00 |
Annual Sum or Average | 4379.84 | 2450.86 | 4319.61 | 2306.69 | 2012.91 | 0.00 | 0.00 |
Minimum of Months | 2750.85 | 814.35 | 3428.65 | 960.62 | 1256.43 | 0.00 | 0.00 |
Maximum of Months | 5501.28 | 4665.71 | 5984.77 | 4042.32 | 2692.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 417.72 | 3579.47 | 1013.95 | 424.58 | 589.37 | 0.00 | 0.00 |
February | 1051.11 | 2910.43 | 1652.02 | 754.53 | 897.49 | 0.00 | 0.00 |
March | 1672.99 | 2342.23 | 2173.93 | 1112.39 | 1061.54 | 0.00 | 0.00 |
April | 2576.14 | 1507.63 | 2777.07 | 1406.56 | 1370.51 | 0.00 | 0.00 |
May | 3738.63 | 876.37 | 3412.13 | 1627.60 | 1784.53 | 0.00 | 0.00 |
June | 3829.88 | 607.26 | 3292.63 | 1423.71 | 1868.92 | 0.00 | 0.00 |
July | 4218.12 | 576.88 | 3515.20 | 1634.20 | 1881.00 | 0.00 | 0.00 |
August | 3368.70 | 655.71 | 2892.78 | 1314.46 | 1578.32 | 0.00 | 0.00 |
September | 2344.26 | 994.88 | 2260.81 | 1015.75 | 1245.06 | 0.00 | 0.00 |
October | 1147.86 | 1488.41 | 1428.17 | 573.33 | 854.84 | 0.00 | 0.00 |
November | 426.06 | 2203.57 | 867.40 | 292.45 | 574.95 | 0.00 | 0.00 |
December | 231.71 | 3476.59 | 773.24 | 270.64 | 502.60 | 0.00 | 0.00 |
Annual Sum or Average | 2091.48 | 1763.72 | 2174.48 | 988.92 | 1185.56 | 0.00 | 0.00 |
Minimum of Months | 231.71 | 576.88 | 773.24 | 270.64 | 502.60 | 0.00 | 0.00 |
Maximum of Months | 4218.12 | 3579.47 | 3515.20 | 1634.20 | 1881.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 11.37 | 5647.75 | 686.37 | 0.00 | 686.37 | 0.00 | 0.00 |
February | 104.62 | 4442.78 | 1054.32 | 0.00 | 1054.32 | 0.00 | 0.00 |
March | 237.79 | 3437.07 | 1297.16 | 0.00 | 1297.16 | 0.00 | 0.00 |
April | 837.55 | 2042.73 | 1700.50 | 13.27 | 1687.23 | 0.00 | 0.00 |
May | 2099.97 | 1120.99 | 2391.69 | 128.79 | 2262.90 | 0.00 | 0.00 |
June | 2844.08 | 785.72 | 2669.16 | 293.41 | 2375.75 | 0.00 | 0.00 |
July | 2844.81 | 740.59 | 2549.47 | 218.79 | 2330.68 | 0.00 | 0.00 |
August | 1961.05 | 860.24 | 1936.40 | 33.25 | 1903.15 | 0.00 | 0.00 |
September | 1153.23 | 1366.43 | 1508.98 | 0.37 | 1508.61 | 0.00 | 0.00 |
October | 431.72 | 2045.01 | 1047.76 | 0.00 | 1047.76 | 0.00 | 0.00 |
November | 67.89 | 3212.19 | 693.75 | 0.00 | 693.75 | 0.00 | 0.00 |
December | 1.88 | 5404.43 | 581.55 | 0.00 | 581.55 | 0.00 | 0.00 |
Annual Sum or Average | 1055.50 | 2585.06 | 1512.04 | 57.58 | 1454.46 | 0.00 | 0.00 |
Minimum of Months | 1.88 | 740.59 | 581.55 | 0.00 | 581.55 | 0.00 | 0.00 |
Maximum of Months | 2844.81 | 5647.75 | 2669.16 | 293.41 | 2375.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 388.23 | 3403.55 | 1003.21 | 418.77 | 584.44 | 0.00 | 0.00 |
February | 932.13 | 2669.53 | 1576.45 | 672.44 | 904.01 | 0.00 | 0.00 |
March | 1600.56 | 2115.42 | 2148.02 | 1077.48 | 1070.54 | 0.00 | 0.00 |
April | 2798.25 | 1305.46 | 2977.78 | 1606.15 | 1371.62 | 0.00 | 0.00 |
May | 3439.12 | 760.32 | 3222.83 | 1416.79 | 1806.04 | 0.00 | 0.00 |
June | 4248.59 | 535.82 | 3648.47 | 1745.26 | 1903.20 | 0.00 | 0.00 |
July | 4276.13 | 499.50 | 3574.15 | 1678.20 | 1895.96 | 0.00 | 0.00 |
August | 3169.12 | 571.54 | 2755.68 | 1204.42 | 1551.25 | 0.00 | 0.00 |
September | 2267.88 | 876.22 | 2206.84 | 987.77 | 1219.07 | 0.00 | 0.00 |
October | 1037.77 | 1302.66 | 1336.28 | 506.71 | 829.56 | 0.00 | 0.00 |
November | 414.01 | 1985.95 | 850.69 | 284.40 | 566.28 | 0.00 | 0.00 |
December | 240.75 | 3296.51 | 776.24 | 286.91 | 489.33 | 0.00 | 0.00 |
Annual Sum or Average | 2073.05 | 1606.26 | 2175.24 | 991.24 | 1183.99 | 0.00 | 0.00 |
Minimum of Months | 240.75 | 499.50 | 776.24 | 284.40 | 489.33 | 0.00 | 0.00 |
Maximum of Months | 4276.13 | 3403.55 | 3648.47 | 1745.26 | 1903.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3895.27 | 4559.68 | 4726.41 | 3288.06 | 1438.35 | 0.00 | 0.00 |
February | 5540.63 | 3836.03 | 5984.77 | 4042.32 | 1942.45 | 0.00 | 0.00 |
March | 4998.52 | 3202.49 | 5273.31 | 3337.27 | 1936.04 | 0.00 | 0.00 |
April | 4946.03 | 2134.74 | 4777.45 | 2593.07 | 2184.38 | 0.00 | 0.00 |
May | 4504.47 | 1251.78 | 4016.58 | 1373.17 | 2643.41 | 0.00 | 0.00 |
June | 4320.22 | 857.02 | 3604.00 | 960.62 | 2643.37 | 0.00 | 0.00 |
July | 4925.52 | 800.77 | 3940.34 | 1248.28 | 2692.06 | 0.00 | 0.00 |
August | 5101.27 | 928.86 | 4208.06 | 1760.20 | 2447.86 | 0.00 | 0.00 |
September | 5066.24 | 1428.79 | 4507.46 | 2400.56 | 2106.90 | 0.00 | 0.00 |
October | 3845.78 | 2027.39 | 3849.05 | 2263.82 | 1585.23 | 0.00 | 0.00 |
November | 3034.32 | 2868.23 | 3428.65 | 2151.83 | 1276.83 | 0.00 | 0.00 |
December | 2777.64 | 4401.93 | 3649.36 | 2392.93 | 1256.43 | 0.00 | 0.00 |
Annual Sum or Average | 4404.51 | 2351.87 | 4319.61 | 2306.69 | 2012.91 | 0.00 | 0.00 |
Minimum of Months | 2777.64 | 800.77 | 3428.65 | 960.62 | 1256.43 | 0.00 | 0.00 |
Maximum of Months | 5540.63 | 4559.68 | 5984.77 | 4042.32 | 2692.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 422.92 | 3513.07 | 1013.95 | 424.58 | 589.37 | 0.00 | 0.00 |
February | 1062.60 | 2826.08 | 1652.02 | 754.53 | 897.49 | 0.00 | 0.00 |
March | 1687.86 | 2254.42 | 2173.93 | 1112.39 | 1061.54 | 0.00 | 0.00 |
April | 2597.59 | 1430.99 | 2777.07 | 1406.56 | 1370.51 | 0.00 | 0.00 |
May | 3745.25 | 849.39 | 3412.13 | 1627.60 | 1784.53 | 0.00 | 0.00 |
June | 3830.43 | 592.09 | 3292.63 | 1423.71 | 1868.92 | 0.00 | 0.00 |
July | 4212.74 | 568.89 | 3515.20 | 1634.20 | 1881.00 | 0.00 | 0.00 |
August | 3367.71 | 642.34 | 2892.78 | 1314.46 | 1578.32 | 0.00 | 0.00 |
September | 2358.68 | 952.35 | 2260.81 | 1015.75 | 1245.06 | 0.00 | 0.00 |
October | 1172.38 | 1396.81 | 1428.17 | 573.33 | 854.84 | 0.00 | 0.00 |
November | 439.93 | 2090.05 | 867.40 | 292.45 | 574.95 | 0.00 | 0.00 |
December | 236.29 | 3408.60 | 773.24 | 270.64 | 502.60 | 0.00 | 0.00 |
Annual Sum or Average | 2100.69 | 1706.12 | 2174.48 | 988.92 | 1185.56 | 0.00 | 0.00 |
Minimum of Months | 236.29 | 568.89 | 773.24 | 270.64 | 502.60 | 0.00 | 0.00 |
Maximum of Months | 4212.74 | 3513.07 | 3515.20 | 1634.20 | 1881.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 7018959.91 | 0.161900E+11 | 0.183839E+10 | 0.00 | 0.183839E+10 | 0.00 | 0.00 |
February | 0.138954E+09 | 0.118580E+11 | 0.255063E+10 | 0.00 | 0.255063E+10 | 0.00 | 0.00 |
March | 0.436938E+09 | 0.104841E+11 | 0.347433E+10 | 0.00 | 0.347433E+10 | 0.00 | 0.00 |
April | 0.172750E+10 | 0.659504E+10 | 0.440771E+10 | 34401626.41 | 0.437331E+10 | 0.00 | 0.00 |
May | 0.534028E+10 | 0.344469E+10 | 0.640592E+10 | 0.344949E+09 | 0.606097E+10 | 0.00 | 0.00 |
June | 0.716165E+10 | 0.232810E+10 | 0.691849E+10 | 0.760527E+09 | 0.615796E+10 | 0.00 | 0.00 |
July | 0.741321E+10 | 0.223633E+10 | 0.682852E+10 | 0.586017E+09 | 0.624250E+10 | 0.00 | 0.00 |
August | 0.501588E+10 | 0.270809E+10 | 0.518648E+10 | 89067659.70 | 0.509741E+10 | 0.00 | 0.00 |
September | 0.269492E+10 | 0.429298E+10 | 0.391129E+10 | 958783.89 | 0.391033E+10 | 0.00 | 0.00 |
October | 0.770603E+09 | 0.710537E+10 | 0.280633E+10 | 0.00 | 0.280633E+10 | 0.00 | 0.00 |
November | 81252334.27 | 0.104393E+11 | 0.179821E+10 | 0.00 | 0.179821E+10 | 0.00 | 0.00 |
December | 0.00 | 0.158912E+11 | 0.155763E+10 | 0.00 | 0.155763E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.307882E+11 | 0.935733E+11 | 0.476839E+11 | 0.181592E+10 | 0.458680E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.223633E+10 | 0.155763E+10 | 0.00 | 0.155763E+10 | 0.00 | 0.00 |
Maximum of Months | 0.741321E+10 | 0.161900E+11 | 0.691849E+10 | 0.760527E+09 | 0.624250E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.978088E+09 | 0.970606E+10 | 0.268701E+10 | 0.112164E+10 | 0.156537E+10 | 0.00 | 0.00 |
February | 0.212334E+10 | 0.705247E+10 | 0.381377E+10 | 0.162678E+10 | 0.218699E+10 | 0.00 | 0.00 |
March | 0.415500E+10 | 0.629337E+10 | 0.575328E+10 | 0.288593E+10 | 0.286735E+10 | 0.00 | 0.00 |
April | 0.706351E+10 | 0.401683E+10 | 0.771843E+10 | 0.416317E+10 | 0.355526E+10 | 0.00 | 0.00 |
May | 0.912559E+10 | 0.230118E+10 | 0.863206E+10 | 0.379475E+10 | 0.483731E+10 | 0.00 | 0.00 |
June | 0.109684E+11 | 0.156516E+10 | 0.945686E+10 | 0.452374E+10 | 0.493312E+10 | 0.00 | 0.00 |
July | 0.114080E+11 | 0.145928E+10 | 0.957305E+10 | 0.449490E+10 | 0.507815E+10 | 0.00 | 0.00 |
August | 0.841664E+10 | 0.173298E+10 | 0.738084E+10 | 0.322594E+10 | 0.415489E+10 | 0.00 | 0.00 |
September | 0.571742E+10 | 0.269431E+10 | 0.572014E+10 | 0.256031E+10 | 0.315984E+10 | 0.00 | 0.00 |
October | 0.250579E+10 | 0.437688E+10 | 0.357910E+10 | 0.135719E+10 | 0.222191E+10 | 0.00 | 0.00 |
November | 0.928803E+09 | 0.629686E+10 | 0.220499E+10 | 0.737177E+09 | 0.146781E+10 | 0.00 | 0.00 |
December | 0.595834E+09 | 0.957747E+10 | 0.207910E+10 | 0.768467E+09 | 0.131063E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.639865E+11 | 0.570728E+11 | 0.685986E+11 | 0.312600E+11 | 0.373386E+11 | 0.00 | 0.00 |
Minimum of Months | 0.595834E+09 | 0.145928E+10 | 0.207910E+10 | 0.737177E+09 | 0.131063E+10 | 0.00 | 0.00 |
Maximum of Months | 0.114080E+11 | 0.970606E+10 | 0.957305E+10 | 0.452374E+10 | 0.507815E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.103325E+11 | 0.128082E+11 | 0.126593E+11 | 0.880677E+10 | 0.385250E+10 | 0.00 | 0.00 |
February | 0.133383E+11 | 0.989918E+10 | 0.144784E+11 | 0.977922E+10 | 0.469919E+10 | 0.00 | 0.00 |
March | 0.133016E+11 | 0.926252E+10 | 0.141241E+11 | 0.893858E+10 | 0.518550E+10 | 0.00 | 0.00 |
April | 0.126532E+11 | 0.632929E+10 | 0.123832E+11 | 0.672125E+10 | 0.566194E+10 | 0.00 | 0.00 |
May | 0.119848E+11 | 0.370415E+10 | 0.107580E+11 | 0.367792E+10 | 0.708013E+10 | 0.00 | 0.00 |
June | 0.110927E+11 | 0.247795E+10 | 0.934159E+10 | 0.248994E+10 | 0.685165E+10 | 0.00 | 0.00 |
July | 0.131162E+11 | 0.233529E+10 | 0.105538E+11 | 0.334341E+10 | 0.721043E+10 | 0.00 | 0.00 |
August | 0.136037E+11 | 0.276542E+10 | 0.112709E+11 | 0.471453E+10 | 0.655637E+10 | 0.00 | 0.00 |
September | 0.130484E+11 | 0.416430E+10 | 0.116834E+11 | 0.622227E+10 | 0.546110E+10 | 0.00 | 0.00 |
October | 0.100414E+11 | 0.636124E+10 | 0.103093E+11 | 0.606343E+10 | 0.424590E+10 | 0.00 | 0.00 |
November | 0.762206E+10 | 0.862101E+10 | 0.888711E+10 | 0.557756E+10 | 0.330955E+10 | 0.00 | 0.00 |
December | 0.729415E+10 | 0.126232E+11 | 0.977447E+10 | 0.640924E+10 | 0.336523E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.137429E+12 | 0.813518E+11 | 0.136224E+12 | 0.727441E+11 | 0.634795E+11 | 0.00 | 0.00 |
Minimum of Months | 0.729415E+10 | 0.233529E+10 | 0.888711E+10 | 0.248994E+10 | 0.330955E+10 | 0.00 | 0.00 |
Maximum of Months | 0.136037E+11 | 0.128082E+11 | 0.144784E+11 | 0.977922E+10 | 0.721043E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.106617E+10 | 0.101615E+11 | 0.271577E+10 | 0.113720E+10 | 0.157856E+10 | 0.00 | 0.00 |
February | 0.244306E+10 | 0.764306E+10 | 0.399658E+10 | 0.182537E+10 | 0.217121E+10 | 0.00 | 0.00 |
March | 0.433750E+10 | 0.697326E+10 | 0.582267E+10 | 0.297942E+10 | 0.284325E+10 | 0.00 | 0.00 |
April | 0.646264E+10 | 0.449657E+10 | 0.719821E+10 | 0.364582E+10 | 0.355238E+10 | 0.00 | 0.00 |
May | 0.995070E+10 | 0.247407E+10 | 0.913909E+10 | 0.435939E+10 | 0.477970E+10 | 0.00 | 0.00 |
June | 0.982889E+10 | 0.169713E+10 | 0.853453E+10 | 0.369026E+10 | 0.484427E+10 | 0.00 | 0.00 |
July | 0.111990E+11 | 0.165255E+10 | 0.941515E+10 | 0.437707E+10 | 0.503808E+10 | 0.00 | 0.00 |
August | 0.888333E+10 | 0.197758E+10 | 0.774804E+10 | 0.352066E+10 | 0.422738E+10 | 0.00 | 0.00 |
September | 0.597672E+10 | 0.279062E+10 | 0.586006E+10 | 0.263284E+10 | 0.322722E+10 | 0.00 | 0.00 |
October | 0.289681E+10 | 0.458688E+10 | 0.382523E+10 | 0.153562E+10 | 0.228962E+10 | 0.00 | 0.00 |
November | 0.989248E+09 | 0.670590E+10 | 0.224831E+10 | 0.758046E+09 | 0.149027E+10 | 0.00 | 0.00 |
December | 0.563277E+09 | 0.103912E+11 | 0.207105E+10 | 0.724884E+09 | 0.134617E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.645973E+11 | 0.615503E+11 | 0.685747E+11 | 0.311866E+11 | 0.373881E+11 | 0.00 | 0.00 |
Minimum of Months | 0.563277E+09 | 0.165255E+10 | 0.207105E+10 | 0.724884E+09 | 0.134617E+10 | 0.00 | 0.00 |
Maximum of Months | 0.111990E+11 | 0.103912E+11 | 0.941515E+10 | 0.437707E+10 | 0.503808E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 22669027.07 | 0.154135E+11 | 0.183838E+10 | 0.00 | 0.183838E+10 | 0.00 | 0.00 |
February | 0.222016E+09 | 0.110811E+11 | 0.255062E+10 | 0.00 | 0.255062E+10 | 0.00 | 0.00 |
March | 0.570076E+09 | 0.961726E+10 | 0.347432E+10 | 0.00 | 0.347432E+10 | 0.00 | 0.00 |
April | 0.203068E+10 | 0.568022E+10 | 0.440769E+10 | 34401504.24 | 0.437329E+10 | 0.00 | 0.00 |
May | 0.554668E+10 | 0.312534E+10 | 0.640589E+10 | 0.344948E+09 | 0.606095E+10 | 0.00 | 0.00 |
June | 0.734998E+10 | 0.209785E+10 | 0.691846E+10 | 0.760524E+09 | 0.615794E+10 | 0.00 | 0.00 |
July | 0.762255E+10 | 0.201491E+10 | 0.682850E+10 | 0.586014E+09 | 0.624248E+10 | 0.00 | 0.00 |
August | 0.523821E+10 | 0.236740E+10 | 0.518646E+10 | 89067343.42 | 0.509739E+10 | 0.00 | 0.00 |
September | 0.289675E+10 | 0.376117E+10 | 0.391128E+10 | 958780.49 | 0.391032E+10 | 0.00 | 0.00 |
October | 0.101739E+10 | 0.597889E+10 | 0.280632E+10 | 0.00 | 0.280632E+10 | 0.00 | 0.00 |
November | 0.140976E+09 | 0.885297E+10 | 0.179820E+10 | 0.00 | 0.179820E+10 | 0.00 | 0.00 |
December | 1342323.90 | 0.148004E+11 | 0.155763E+10 | 0.00 | 0.155763E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.326593E+11 | 0.847909E+11 | 0.476837E+11 | 0.181591E+10 | 0.458678E+11 | 0.00 | 0.00 |
Minimum of Months | 1342323.90 | 0.201491E+10 | 0.155763E+10 | 0.00 | 0.155763E+10 | 0.00 | 0.00 |
Maximum of Months | 0.762255E+10 | 0.154135E+11 | 0.691846E+10 | 0.760524E+09 | 0.624248E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.102335E+10 | 0.927467E+10 | 0.268699E+10 | 0.112164E+10 | 0.156536E+10 | 0.00 | 0.00 |
February | 0.220687E+10 | 0.666153E+10 | 0.381376E+10 | 0.162678E+10 | 0.218698E+10 | 0.00 | 0.00 |
March | 0.421693E+10 | 0.591694E+10 | 0.575325E+10 | 0.288592E+10 | 0.286733E+10 | 0.00 | 0.00 |
April | 0.717816E+10 | 0.358787E+10 | 0.771840E+10 | 0.416315E+10 | 0.355525E+10 | 0.00 | 0.00 |
May | 0.918966E+10 | 0.210080E+10 | 0.863202E+10 | 0.379474E+10 | 0.483729E+10 | 0.00 | 0.00 |
June | 0.110192E+11 | 0.142257E+10 | 0.945682E+10 | 0.452372E+10 | 0.493310E+10 | 0.00 | 0.00 |
July | 0.114689E+11 | 0.135200E+10 | 0.957301E+10 | 0.449488E+10 | 0.507813E+10 | 0.00 | 0.00 |
August | 0.849620E+10 | 0.155953E+10 | 0.738081E+10 | 0.322593E+10 | 0.415488E+10 | 0.00 | 0.00 |
September | 0.583720E+10 | 0.237787E+10 | 0.572012E+10 | 0.256030E+10 | 0.315982E+10 | 0.00 | 0.00 |
October | 0.269185E+10 | 0.375805E+10 | 0.357909E+10 | 0.135718E+10 | 0.222190E+10 | 0.00 | 0.00 |
November | 0.102761E+10 | 0.546607E+10 | 0.220498E+10 | 0.737174E+09 | 0.146780E+10 | 0.00 | 0.00 |
December | 0.630616E+09 | 0.902069E+10 | 0.207909E+10 | 0.768464E+09 | 0.131062E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.649865E+11 | 0.524986E+11 | 0.685983E+11 | 0.312599E+11 | 0.373385E+11 | 0.00 | 0.00 |
Minimum of Months | 0.630616E+09 | 0.135200E+10 | 0.207909E+10 | 0.737174E+09 | 0.131062E+10 | 0.00 | 0.00 |
Maximum of Months | 0.114689E+11 | 0.927467E+10 | 0.957301E+10 | 0.452372E+10 | 0.507813E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.103657E+11 | 0.124966E+11 | 0.126592E+11 | 0.880674E+10 | 0.385248E+10 | 0.00 | 0.00 |
February | 0.133087E+11 | 0.964475E+10 | 0.144784E+11 | 0.977919E+10 | 0.469917E+10 | 0.00 | 0.00 |
March | 0.132865E+11 | 0.897686E+10 | 0.141240E+11 | 0.893855E+10 | 0.518548E+10 | 0.00 | 0.00 |
April | 0.127231E+11 | 0.588024E+10 | 0.123832E+11 | 0.672123E+10 | 0.566192E+10 | 0.00 | 0.00 |
May | 0.120351E+11 | 0.347938E+10 | 0.107580E+11 | 0.367791E+10 | 0.708010E+10 | 0.00 | 0.00 |
June | 0.111875E+11 | 0.229086E+10 | 0.934156E+10 | 0.248994E+10 | 0.685162E+10 | 0.00 | 0.00 |
July | 0.132055E+11 | 0.218115E+10 | 0.105538E+11 | 0.334339E+10 | 0.721041E+10 | 0.00 | 0.00 |
August | 0.136711E+11 | 0.254781E+10 | 0.112709E+11 | 0.471451E+10 | 0.655634E+10 | 0.00 | 0.00 |
September | 0.130793E+11 | 0.388877E+10 | 0.116833E+11 | 0.622225E+10 | 0.546108E+10 | 0.00 | 0.00 |
October | 0.101538E+11 | 0.585930E+10 | 0.103093E+11 | 0.606341E+10 | 0.424588E+10 | 0.00 | 0.00 |
November | 0.773834E+10 | 0.793735E+10 | 0.888707E+10 | 0.557754E+10 | 0.330953E+10 | 0.00 | 0.00 |
December | 0.736787E+10 | 0.121073E+11 | 0.977444E+10 | 0.640922E+10 | 0.336522E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.138122E+12 | 0.772904E+11 | 0.136223E+12 | 0.727439E+11 | 0.634792E+11 | 0.00 | 0.00 |
Minimum of Months | 0.736787E+10 | 0.218115E+10 | 0.888707E+10 | 0.248994E+10 | 0.330953E+10 | 0.00 | 0.00 |
Maximum of Months | 0.136711E+11 | 0.124966E+11 | 0.144784E+11 | 0.977919E+10 | 0.721041E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.111882E+10 | 0.958725E+10 | 0.271576E+10 | 0.113720E+10 | 0.157856E+10 | 0.00 | 0.00 |
February | 0.254286E+10 | 0.704090E+10 | 0.399656E+10 | 0.182536E+10 | 0.217120E+10 | 0.00 | 0.00 |
March | 0.448094E+10 | 0.627342E+10 | 0.582265E+10 | 0.297941E+10 | 0.284324E+10 | 0.00 | 0.00 |
April | 0.667735E+10 | 0.390777E+10 | 0.719818E+10 | 0.364581E+10 | 0.355237E+10 | 0.00 | 0.00 |
May | 0.100135E+11 | 0.234727E+10 | 0.913905E+10 | 0.435937E+10 | 0.477968E+10 | 0.00 | 0.00 |
June | 0.992706E+10 | 0.157402E+10 | 0.853450E+10 | 0.369025E+10 | 0.484425E+10 | 0.00 | 0.00 |
July | 0.112978E+11 | 0.154510E+10 | 0.941511E+10 | 0.437705E+10 | 0.503806E+10 | 0.00 | 0.00 |
August | 0.902272E+10 | 0.175626E+10 | 0.774801E+10 | 0.352065E+10 | 0.422736E+10 | 0.00 | 0.00 |
September | 0.607631E+10 | 0.257874E+10 | 0.586003E+10 | 0.263283E+10 | 0.322721E+10 | 0.00 | 0.00 |
October | 0.307444E+10 | 0.398655E+10 | 0.382522E+10 | 0.153561E+10 | 0.228961E+10 | 0.00 | 0.00 |
November | 0.110436E+10 | 0.571165E+10 | 0.224831E+10 | 0.758043E+09 | 0.149026E+10 | 0.00 | 0.00 |
December | 0.620612E+09 | 0.931169E+10 | 0.207105E+10 | 0.724881E+09 | 0.134617E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.659568E+11 | 0.556206E+11 | 0.685744E+11 | 0.311865E+11 | 0.373879E+11 | 0.00 | 0.00 |
Minimum of Months | 0.620612E+09 | 0.154510E+10 | 0.207105E+10 | 0.724881E+09 | 0.134617E+10 | 0.00 | 0.00 |
Maximum of Months | 0.112978E+11 | 0.958725E+10 | 0.941511E+10 | 0.437705E+10 | 0.503806E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 30451338.61 | 0.151269E+11 | 0.183838E+10 | 0.00 | 0.183838E+10 | 0.00 | 0.00 |
February | 0.253088E+09 | 0.107480E+11 | 0.255062E+10 | 0.00 | 0.255062E+10 | 0.00 | 0.00 |
March | 0.636909E+09 | 0.920585E+10 | 0.347432E+10 | 0.00 | 0.347432E+10 | 0.00 | 0.00 |
April | 0.217093E+10 | 0.529476E+10 | 0.440769E+10 | 34401504.24 | 0.437329E+10 | 0.00 | 0.00 |
May | 0.562456E+10 | 0.300246E+10 | 0.640589E+10 | 0.344948E+09 | 0.606095E+10 | 0.00 | 0.00 |
June | 0.737186E+10 | 0.203659E+10 | 0.691846E+10 | 0.760524E+09 | 0.615794E+10 | 0.00 | 0.00 |
July | 0.761953E+10 | 0.198358E+10 | 0.682850E+10 | 0.586014E+09 | 0.624248E+10 | 0.00 | 0.00 |
August | 0.525247E+10 | 0.230406E+10 | 0.518646E+10 | 89067343.42 | 0.509739E+10 | 0.00 | 0.00 |
September | 0.298916E+10 | 0.354178E+10 | 0.391128E+10 | 958780.49 | 0.391032E+10 | 0.00 | 0.00 |
October | 0.115633E+10 | 0.547735E+10 | 0.280632E+10 | 0.00 | 0.280632E+10 | 0.00 | 0.00 |
November | 0.175975E+09 | 0.832598E+10 | 0.179820E+10 | 0.00 | 0.179820E+10 | 0.00 | 0.00 |
December | 5048274.70 | 0.144752E+11 | 0.155763E+10 | 0.00 | 0.155763E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.332863E+11 | 0.815226E+11 | 0.476837E+11 | 0.181591E+10 | 0.458678E+11 | 0.00 | 0.00 |
Minimum of Months | 5048274.70 | 0.198358E+10 | 0.155763E+10 | 0.00 | 0.155763E+10 | 0.00 | 0.00 |
Maximum of Months | 0.761953E+10 | 0.151269E+11 | 0.691846E+10 | 0.760524E+09 | 0.624248E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.103985E+10 | 0.911606E+10 | 0.268699E+10 | 0.112164E+10 | 0.156536E+10 | 0.00 | 0.00 |
February | 0.225501E+10 | 0.645813E+10 | 0.381376E+10 | 0.162678E+10 | 0.218698E+10 | 0.00 | 0.00 |
March | 0.428694E+10 | 0.566595E+10 | 0.575325E+10 | 0.288592E+10 | 0.286733E+10 | 0.00 | 0.00 |
April | 0.725305E+10 | 0.338375E+10 | 0.771840E+10 | 0.416315E+10 | 0.355525E+10 | 0.00 | 0.00 |
May | 0.921135E+10 | 0.203645E+10 | 0.863202E+10 | 0.379474E+10 | 0.483729E+10 | 0.00 | 0.00 |
June | 0.110124E+11 | 0.138885E+10 | 0.945682E+10 | 0.452372E+10 | 0.493310E+10 | 0.00 | 0.00 |
July | 0.114532E+11 | 0.133786E+10 | 0.957301E+10 | 0.449488E+10 | 0.507813E+10 | 0.00 | 0.00 |
August | 0.848818E+10 | 0.153082E+10 | 0.738081E+10 | 0.322593E+10 | 0.415488E+10 | 0.00 | 0.00 |
September | 0.587834E+10 | 0.227115E+10 | 0.572012E+10 | 0.256030E+10 | 0.315982E+10 | 0.00 | 0.00 |
October | 0.277955E+10 | 0.348904E+10 | 0.357909E+10 | 0.135718E+10 | 0.222190E+10 | 0.00 | 0.00 |
November | 0.107312E+10 | 0.514759E+10 | 0.220498E+10 | 0.737174E+09 | 0.146780E+10 | 0.00 | 0.00 |
December | 0.644824E+09 | 0.882937E+10 | 0.207909E+10 | 0.768464E+09 | 0.131062E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.653758E+11 | 0.506550E+11 | 0.685983E+11 | 0.312599E+11 | 0.373385E+11 | 0.00 | 0.00 |
Minimum of Months | 0.644824E+09 | 0.133786E+10 | 0.207909E+10 | 0.737174E+09 | 0.131062E+10 | 0.00 | 0.00 |
Maximum of Months | 0.114532E+11 | 0.911606E+10 | 0.957301E+10 | 0.452372E+10 | 0.507813E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.104331E+11 | 0.122127E+11 | 0.126592E+11 | 0.880674E+10 | 0.385248E+10 | 0.00 | 0.00 |
February | 0.134039E+11 | 0.928013E+10 | 0.144784E+11 | 0.977919E+10 | 0.469917E+10 | 0.00 | 0.00 |
March | 0.133880E+11 | 0.857755E+10 | 0.141240E+11 | 0.893855E+10 | 0.518548E+10 | 0.00 | 0.00 |
April | 0.128201E+11 | 0.553325E+10 | 0.123832E+11 | 0.672123E+10 | 0.566192E+10 | 0.00 | 0.00 |
May | 0.120648E+11 | 0.335277E+10 | 0.107580E+11 | 0.367791E+10 | 0.708010E+10 | 0.00 | 0.00 |
June | 0.111980E+11 | 0.222139E+10 | 0.934156E+10 | 0.248994E+10 | 0.685162E+10 | 0.00 | 0.00 |
July | 0.131925E+11 | 0.214478E+10 | 0.105538E+11 | 0.334339E+10 | 0.721041E+10 | 0.00 | 0.00 |
August | 0.136632E+11 | 0.248785E+10 | 0.112709E+11 | 0.471451E+10 | 0.655634E+10 | 0.00 | 0.00 |
September | 0.131317E+11 | 0.370342E+10 | 0.116833E+11 | 0.622225E+10 | 0.546108E+10 | 0.00 | 0.00 |
October | 0.103005E+11 | 0.543016E+10 | 0.103093E+11 | 0.606341E+10 | 0.424588E+10 | 0.00 | 0.00 |
November | 0.786495E+10 | 0.743444E+10 | 0.888707E+10 | 0.557754E+10 | 0.330953E+10 | 0.00 | 0.00 |
December | 0.743964E+10 | 0.117901E+11 | 0.977444E+10 | 0.640922E+10 | 0.336522E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.138900E+12 | 0.741685E+11 | 0.136223E+12 | 0.727439E+11 | 0.634792E+11 | 0.00 | 0.00 |
Minimum of Months | 0.743964E+10 | 0.214478E+10 | 0.888707E+10 | 0.248994E+10 | 0.330953E+10 | 0.00 | 0.00 |
Maximum of Months | 0.136632E+11 | 0.122127E+11 | 0.144784E+11 | 0.977919E+10 | 0.721041E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.113276E+10 | 0.940941E+10 | 0.271576E+10 | 0.113720E+10 | 0.157856E+10 | 0.00 | 0.00 |
February | 0.257064E+10 | 0.683686E+10 | 0.399656E+10 | 0.182536E+10 | 0.217120E+10 | 0.00 | 0.00 |
March | 0.452075E+10 | 0.603823E+10 | 0.582265E+10 | 0.297941E+10 | 0.284324E+10 | 0.00 | 0.00 |
April | 0.673296E+10 | 0.370912E+10 | 0.719818E+10 | 0.364581E+10 | 0.355237E+10 | 0.00 | 0.00 |
May | 0.100313E+11 | 0.227500E+10 | 0.913905E+10 | 0.435937E+10 | 0.477968E+10 | 0.00 | 0.00 |
June | 0.992847E+10 | 0.153470E+10 | 0.853450E+10 | 0.369025E+10 | 0.484425E+10 | 0.00 | 0.00 |
July | 0.112834E+11 | 0.152371E+10 | 0.941511E+10 | 0.437705E+10 | 0.503806E+10 | 0.00 | 0.00 |
August | 0.902006E+10 | 0.172044E+10 | 0.774801E+10 | 0.352065E+10 | 0.422736E+10 | 0.00 | 0.00 |
September | 0.611369E+10 | 0.246850E+10 | 0.586003E+10 | 0.263283E+10 | 0.322721E+10 | 0.00 | 0.00 |
October | 0.314010E+10 | 0.374122E+10 | 0.382522E+10 | 0.153561E+10 | 0.228961E+10 | 0.00 | 0.00 |
November | 0.114030E+10 | 0.541741E+10 | 0.224831E+10 | 0.758043E+09 | 0.149026E+10 | 0.00 | 0.00 |
December | 0.632874E+09 | 0.912960E+10 | 0.207105E+10 | 0.724881E+09 | 0.134617E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.662473E+11 | 0.538042E+11 | 0.685744E+11 | 0.311865E+11 | 0.373879E+11 | 0.00 | 0.00 |
Minimum of Months | 0.632874E+09 | 0.152371E+10 | 0.207105E+10 | 0.724881E+09 | 0.134617E+10 | 0.00 | 0.00 |
Maximum of Months | 0.112834E+11 | 0.940941E+10 | 0.941511E+10 | 0.437705E+10 | 0.503806E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.4 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.7 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.6 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.41 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.19 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.97 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.20 | 13.59 | 3.45 | 8.99 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.34 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.47 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.04 | -2.0 | 3.82 | -8.4 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.4 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.99 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -1.0 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.87 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.48 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.95 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.26 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.72 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.35 | 23.33 | 8.07 | 19.93 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.36 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.82 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.62 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.44 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -1.0 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.35 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.4 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.2 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.62 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.7 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.5 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.34 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.48 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.95 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.91 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.72 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.76 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.36 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.72 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.5 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.76 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.25 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.08 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.91 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.76 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.36 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.23 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.17 | 3.43 | 9.20 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 05-DEC-17:00 | 0.00 | -0.0 | 1.50 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.76 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.466934E+11 | -0.462454E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -447922687.8 | 60.05 | 0.00 | 0.00 |
February | 0.433671E+11 | -0.429664E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -400624670.3 | 60.05 | 0.00 | 0.00 |
March | 0.507851E+11 | -0.503523E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -432873336.3 | 60.05 | 0.00 | 0.00 |
April | 0.446731E+11 | -0.443016E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -371521780.9 | 60.05 | 0.00 | 0.00 |
May | 0.453652E+11 | -0.449826E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -382551526.4 | 60.05 | 0.00 | 0.00 |
June | 0.423458E+11 | -0.419792E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -366594746.7 | 60.05 | 0.00 | 0.00 |
July | 0.382267E+11 | -0.378517E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -375008316.4 | 60.05 | 0.00 | 0.00 |
August | 0.406504E+11 | -0.402787E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -371644377.0 | 60.05 | 0.00 | 0.00 |
September | 0.370843E+11 | -0.367204E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -363901130.3 | 60.05 | 0.00 | 0.00 |
October | 0.397084E+11 | -0.393298E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -378685980.7 | 60.05 | 0.00 | 0.00 |
November | 0.411982E+11 | -0.408194E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -378810806.9 | 60.05 | 0.00 | 0.00 |
December | 0.435032E+11 | -0.430645E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -438667015.2 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.513601E+12 | -0.508892E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.470881E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.370843E+11 | -0.503523E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -447922687.8 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.507851E+11 | -0.367204E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -363901130.3 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.49 | 0.48 | 01-JAN-08:39 | 5711.58 | 36.01 | 239.83 | 239.17 | 4738.56 | 36.96 | 241.83 | 227.83 |
February | 265.33 | 0.49 | 0.48 | 01-FEB-08:39 | 8829.80 | 36.52 | 261.83 | 258.83 | 3735.18 | 30.65 | 232.50 | 241.83 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 12441.99 | 35.71 | 242.33 | 324.17 | 2027.11 | 22.86 | 232.17 | 291.17 |
April | 296.33 | 0.52 | 0.48 | 01-APR-07:00 | 2631.77 | 20.43 | 135.67 | 352.33 | 1601.52 | 21.86 | 238.67 | 321.17 |
May | 437.50 | 0.51 | 0.48 | 01-MAY-06:19 | 2317.56 | 20.92 | 206.83 | 414.83 | 1284.43 | 22.34 | 307.50 | 374.17 |
June | 401.83 | 0.51 | 0.48 | 01-JUN-05:30 | 2212.70 | 20.98 | 202.17 | 415.00 | 1242.18 | 22.41 | 302.33 | 376.33 |
July | 409.17 | 0.50 | 0.48 | 01-JUL-05:30 | 2396.08 | 21.26 | 217.50 | 421.83 | 1354.93 | 22.69 | 321.50 | 384.67 |
August | 352.83 | 0.50 | 0.48 | 01-AUG-07:40 | 3020.85 | 21.88 | 203.67 | 380.67 | 1566.21 | 22.94 | 291.17 | 342.17 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:49 | 5858.11 | 25.67 | 236.33 | 334.17 | 1613.06 | 22.97 | 253.33 | 302.00 |
October | 299.00 | 0.49 | 0.48 | 01-OCT-06:49 | 6244.62 | 32.37 | 277.50 | 298.83 | 1732.96 | 26.46 | 256.67 | 275.17 |
November | 255.50 | 0.51 | 0.48 | 01-NOV-08:09 | 4521.60 | 34.56 | 246.00 | 241.33 | 3706.50 | 35.75 | 248.50 | 220.83 |
December | 226.33 | 0.50 | 0.48 | 01-DEC-08:20 | 4253.41 | 34.12 | 215.33 | 225.00 | 3498.54 | 35.37 | 218.33 | 205.33 |
Annual Sum or Average | 3785.50 | 0.50 | 4656.05 | 27.12 | 2685.00 | 3906.17 | 2143.49 | 26.03 | 3144.50 | 3562.67 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 2212.70 | 20.43 | 135.67 | 225.00 | 1242.18 | 21.86 | 218.33 | 205.33 | |
Maximum of Months | 437.50 | 0.52 | 0.48 | 12441.99 | 36.52 | 277.50 | 421.83 | 4738.56 | 36.96 | 321.50 | 384.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.52 | 0.48 | 01-JAN-08:39 | 1911.24 | 25.04 | 118.50 | 225.17 | 1111.59 | 25.14 | 157.00 | 195.33 |
February | 265.33 | 0.51 | 0.48 | 01-FEB-08:39 | 2531.35 | 25.10 | 140.83 | 249.50 | 1348.16 | 25.18 | 185.83 | 225.17 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 4274.53 | 26.83 | 124.33 | 320.50 | 2579.51 | 26.98 | 190.00 | 285.50 |
April | 296.33 | 0.51 | 0.48 | 01-APR-06:00 | 4571.60 | 25.72 | 124.00 | 358.33 | 2674.87 | 25.98 | 199.17 | 328.33 |
May | 437.50 | 0.50 | 0.48 | 01-MAY-05:10 | 4150.62 | 25.10 | 187.67 | 424.50 | 1849.82 | 24.84 | 282.67 | 390.33 |
June | 401.83 | 0.50 | 0.48 | 01-JUN-04:49 | 5040.49 | 25.96 | 158.50 | 422.50 | 2348.32 | 25.59 | 270.67 | 390.50 |
July | 409.17 | 0.50 | 0.48 | 01-JUL-04:49 | 4820.18 | 26.02 | 171.00 | 428.33 | 2221.63 | 25.58 | 286.67 | 396.50 |
August | 352.83 | 0.50 | 0.48 | 01-AUG-07:40 | 4041.44 | 25.13 | 142.67 | 384.33 | 1799.99 | 24.72 | 246.83 | 351.00 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:19 | 3155.86 | 24.00 | 155.67 | 334.17 | 1673.76 | 24.42 | 224.17 | 301.17 |
October | 299.00 | 0.50 | 0.48 | 01-OCT-06:40 | 2360.86 | 24.38 | 139.50 | 290.67 | 1038.70 | 23.83 | 189.67 | 252.67 |
November | 255.50 | 0.52 | 0.48 | 01-NOV-07:00 | 1568.24 | 23.90 | 103.00 | 228.50 | 853.23 | 24.14 | 153.00 | 191.00 |
December | 226.33 | 0.52 | 0.48 | 01-DEC-08:20 | 1390.81 | 23.36 | 84.50 | 207.83 | 918.06 | 24.77 | 130.67 | 175.33 |
Annual Sum or Average | 3785.50 | 0.51 | 3519.99 | 25.11 | 1650.17 | 3874.33 | 1766.20 | 25.09 | 2516.33 | 3482.83 | ||
Minimum of Months | 226.33 | 0.50 | 0.48 | 1390.81 | 23.36 | 84.50 | 207.83 | 853.23 | 23.83 | 130.67 | 175.33 | |
Maximum of Months | 437.50 | 0.52 | 0.48 | 5040.49 | 26.83 | 187.67 | 428.33 | 2674.87 | 26.98 | 286.67 | 396.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.54 | 0.48 | 01-JAN-10:20 | 712.91 | 17.67 | 0.00 | 210.83 | 409.06 | 19.31 | 10.50 | 156.17 |
February | 265.33 | 0.52 | 0.48 | 01-FEB-09:30 | 906.20 | 18.84 | 0.00 | 240.17 | 537.98 | 20.45 | 77.50 | 200.67 |
March | 254.17 | 0.51 | 0.48 | 02-MAR-10:39 | 990.99 | 19.37 | 1.50 | 313.67 | 626.85 | 20.95 | 102.50 | 261.83 |
April | 296.33 | 0.51 | 0.48 | 01-APR-08:09 | 1127.42 | 19.69 | 25.17 | 356.50 | 709.83 | 21.12 | 148.33 | 322.83 |
May | 437.50 | 0.49 | 0.48 | 01-MAY-05:30 | 1521.42 | 22.71 | 163.50 | 432.17 | 867.94 | 23.21 | 345.50 | 411.00 |
June | 401.83 | 0.49 | 0.48 | 01-JUN-04:49 | 1799.01 | 23.97 | 214.50 | 440.50 | 990.19 | 24.14 | 348.00 | 409.33 |
July | 409.17 | 0.49 | 0.48 | 01-JUL-04:49 | 1722.52 | 23.53 | 218.67 | 440.83 | 1011.20 | 24.81 | 362.83 | 417.50 |
August | 352.83 | 0.49 | 0.48 | 01-AUG-07:40 | 1428.86 | 20.96 | 101.67 | 388.17 | 853.78 | 22.33 | 262.00 | 353.83 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:49 | 1096.26 | 19.82 | 1.17 | 332.00 | 641.64 | 21.22 | 176.83 | 288.83 |
October | 299.00 | 0.52 | 0.48 | 01-OCT-07:19 | 893.98 | 18.80 | 0.00 | 280.50 | 499.90 | 20.21 | 54.33 | 224.83 |
November | 255.50 | 0.55 | 0.48 | 01-NOV-08:50 | 690.39 | 17.48 | 0.00 | 215.17 | 382.95 | 18.88 | 1.33 | 149.33 |
December | 226.33 | 0.55 | 0.48 | 01-DEC-09:30 | 658.69 | 17.40 | 0.00 | 194.50 | 365.78 | 18.92 | 1.83 | 128.83 |
Annual Sum or Average | 3785.50 | 0.51 | 1206.56 | 20.47 | 726.17 | 3845.00 | 701.49 | 21.67 | 1891.50 | 3325.00 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 658.69 | 17.40 | 0.00 | 194.50 | 365.78 | 18.88 | 1.33 | 128.83 | |
Maximum of Months | 437.50 | 0.55 | 0.48 | 1799.01 | 23.97 | 218.67 | 440.83 | 1011.20 | 24.81 | 362.83 | 417.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.52 | 0.48 | 01-JAN-10:20 | 1859.50 | 24.95 | 113.50 | 226.50 | 1050.56 | 24.96 | 156.50 | 197.33 |
February | 265.33 | 0.51 | 0.48 | 01-FEB-09:30 | 2543.52 | 25.33 | 145.00 | 251.67 | 1365.37 | 25.38 | 189.17 | 227.33 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 3919.54 | 25.54 | 117.33 | 320.17 | 2267.93 | 25.74 | 188.50 | 284.17 |
April | 296.33 | 0.51 | 0.48 | 01-APR-08:20 | 4667.97 | 24.22 | 111.83 | 355.50 | 2030.53 | 23.39 | 174.83 | 325.67 |
May | 437.50 | 0.50 | 0.48 | 01-MAY-06:30 | 3810.78 | 22.49 | 133.83 | 423.17 | 2183.38 | 23.38 | 254.17 | 396.00 |
June | 401.83 | 0.49 | 0.48 | 01-JUN-05:30 | 4086.04 | 21.60 | 84.17 | 433.33 | 1798.26 | 22.07 | 256.50 | 401.17 |
July | 409.17 | 0.49 | 0.48 | 01-JUL-05:40 | 4401.96 | 22.02 | 95.33 | 436.00 | 1956.30 | 22.28 | 254.17 | 405.67 |
August | 352.83 | 0.49 | 0.48 | 01-AUG-07:49 | 3999.62 | 23.74 | 135.33 | 386.50 | 2234.73 | 24.30 | 235.67 | 351.50 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-07:10 | 3395.05 | 24.41 | 155.50 | 334.67 | 1928.98 | 24.89 | 224.83 | 303.83 |
October | 299.00 | 0.50 | 0.48 | 01-OCT-07:30 | 2543.52 | 25.08 | 141.50 | 291.33 | 1085.74 | 24.21 | 184.83 | 254.00 |
November | 255.50 | 0.53 | 0.48 | 01-NOV-08:50 | 1549.06 | 23.76 | 103.50 | 229.33 | 812.62 | 23.84 | 149.33 | 193.17 |
December | 226.33 | 0.52 | 0.48 | 01-DEC-09:30 | 1420.29 | 22.91 | 84.50 | 213.83 | 738.84 | 23.10 | 126.17 | 176.83 |
Annual Sum or Average | 3785.50 | 0.50 | 3348.18 | 23.65 | 1421.33 | 3902.00 | 1697.58 | 23.83 | 2394.67 | 3516.67 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 1420.29 | 21.60 | 84.17 | 213.83 | 738.84 | 22.07 | 126.17 | 176.83 | |
Maximum of Months | 437.50 | 0.53 | 0.48 | 4667.97 | 25.54 | 155.50 | 436.00 | 2267.93 | 25.74 | 256.50 | 405.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.49 | 0.48 | 01-JAN-08:39 | 5752.13 | 35.44 | 233.33 | 239.17 | 4880.29 | 36.50 | 234.17 | 228.50 |
February | 265.33 | 0.49 | 0.48 | 01-FEB-08:39 | 8890.07 | 35.98 | 256.50 | 258.83 | 4826.55 | 32.01 | 200.33 | 246.33 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 12525.61 | 34.67 | 215.00 | 324.33 | 2184.39 | 18.16 | 11.67 | 293.33 |
April | 296.33 | 0.52 | 0.48 | 01-APR-07:49 | 2698.82 | 14.12 | 0.00 | 352.33 | 1725.18 | 17.70 | 12.33 | 324.50 |
May | 437.50 | 0.50 | 0.48 | 01-MAY-06:19 | 2353.06 | 14.78 | 0.00 | 415.33 | 1371.96 | 18.24 | 1.67 | 380.67 |
June | 401.83 | 0.51 | 0.48 | 01-JUN-05:19 | 2248.21 | 15.08 | 0.00 | 415.17 | 1326.18 | 18.53 | 0.17 | 380.83 |
July | 409.17 | 0.50 | 0.48 | 01-JUL-05:30 | 2436.80 | 15.35 | 0.00 | 422.00 | 1447.84 | 18.82 | 8.00 | 387.00 |
August | 352.83 | 0.50 | 0.48 | 01-AUG-07:40 | 3064.64 | 15.90 | 10.00 | 380.83 | 1674.79 | 18.79 | 23.00 | 346.33 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:40 | 5899.60 | 21.52 | 115.00 | 334.83 | 1725.19 | 18.49 | 19.00 | 306.00 |
October | 299.00 | 0.49 | 0.48 | 01-OCT-06:49 | 6276.22 | 31.37 | 264.17 | 299.00 | 1834.08 | 22.86 | 106.67 | 277.50 |
November | 255.50 | 0.50 | 0.48 | 01-NOV-08:09 | 4548.06 | 34.02 | 243.67 | 241.33 | 3802.53 | 35.31 | 245.67 | 223.50 |
December | 226.33 | 0.50 | 0.48 | 01-DEC-08:20 | 4276.70 | 33.32 | 207.50 | 225.17 | 3598.88 | 34.71 | 211.17 | 207.00 |
Annual Sum or Average | 3785.50 | 0.50 | 4699.54 | 23.41 | 1545.17 | 3908.33 | 2319.20 | 23.00 | 1073.83 | 3601.50 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 2248.21 | 14.12 | 0.00 | 225.17 | 1326.18 | 17.70 | 0.17 | 207.00 | |
Maximum of Months | 437.50 | 0.52 | 0.48 | 12525.61 | 35.98 | 264.17 | 422.00 | 4880.29 | 36.50 | 245.67 | 387.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.52 | 0.48 | 01-JAN-08:39 | 1941.12 | 22.89 | 99.17 | 225.67 | 1154.17 | 23.54 | 88.67 | 198.67 |
February | 265.33 | 0.51 | 0.48 | 01-FEB-08:39 | 2577.93 | 22.60 | 86.67 | 249.67 | 1410.43 | 23.29 | 98.17 | 227.00 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 4280.02 | 22.77 | 80.83 | 320.83 | 2668.11 | 25.08 | 87.67 | 288.50 |
April | 296.33 | 0.51 | 0.48 | 01-APR-06:00 | 4592.69 | 21.62 | 84.33 | 359.00 | 2777.08 | 23.80 | 75.83 | 332.17 |
May | 437.50 | 0.50 | 0.48 | 01-MAY-05:10 | 4204.47 | 21.66 | 135.17 | 424.67 | 1936.49 | 22.34 | 86.50 | 393.50 |
June | 401.83 | 0.50 | 0.48 | 01-JUN-04:49 | 5107.15 | 23.14 | 133.00 | 423.33 | 2449.08 | 23.16 | 83.17 | 394.33 |
July | 409.17 | 0.50 | 0.48 | 01-JUL-04:40 | 4870.10 | 22.53 | 126.00 | 429.17 | 2323.24 | 23.14 | 81.67 | 400.33 |
August | 352.83 | 0.50 | 0.48 | 01-AUG-07:40 | 4105.07 | 22.18 | 99.83 | 384.83 | 1889.17 | 22.19 | 60.83 | 355.67 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:19 | 3215.12 | 21.03 | 96.83 | 334.33 | 1746.13 | 22.11 | 72.83 | 304.83 |
October | 299.00 | 0.50 | 0.48 | 01-OCT-06:40 | 2379.27 | 21.15 | 99.50 | 290.83 | 1089.87 | 21.64 | 62.17 | 257.33 |
November | 255.50 | 0.52 | 0.48 | 01-NOV-07:00 | 1594.91 | 21.46 | 90.33 | 228.83 | 890.10 | 22.30 | 71.67 | 194.83 |
December | 226.33 | 0.52 | 0.48 | 01-DEC-08:20 | 1416.00 | 20.79 | 67.33 | 208.67 | 952.98 | 23.13 | 78.67 | 179.33 |
Annual Sum or Average | 3785.50 | 0.50 | 3561.97 | 22.01 | 1199.00 | 3879.83 | 1842.45 | 22.91 | 947.83 | 3526.50 | ||
Minimum of Months | 226.33 | 0.50 | 0.48 | 1416.00 | 20.79 | 67.33 | 208.67 | 890.10 | 21.64 | 60.83 | 179.33 | |
Maximum of Months | 437.50 | 0.52 | 0.48 | 5107.15 | 23.14 | 135.17 | 429.17 | 2777.08 | 25.08 | 98.17 | 400.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.54 | 0.48 | 01-JAN-10:09 | 720.98 | 11.76 | 0.00 | 211.33 | 434.20 | 15.38 | 0.00 | 165.33 |
February | 265.33 | 0.52 | 0.48 | 01-FEB-09:30 | 918.29 | 13.18 | 0.00 | 240.33 | 571.80 | 16.74 | 0.00 | 206.00 |
March | 254.17 | 0.51 | 0.48 | 02-MAR-10:39 | 1009.19 | 14.07 | 0.00 | 314.17 | 668.05 | 17.64 | 0.00 | 269.00 |
April | 296.33 | 0.51 | 0.48 | 01-APR-07:00 | 1151.70 | 14.51 | 0.00 | 356.67 | 757.79 | 18.03 | 4.00 | 327.00 |
May | 437.50 | 0.49 | 0.48 | 01-MAY-05:19 | 1547.60 | 17.79 | 53.67 | 432.33 | 930.72 | 20.92 | 69.17 | 415.67 |
June | 401.83 | 0.49 | 0.48 | 01-JUN-04:49 | 1830.45 | 19.35 | 76.83 | 440.50 | 1094.57 | 22.39 | 113.83 | 417.67 |
July | 409.17 | 0.49 | 0.48 | 01-JUL-04:49 | 1756.79 | 18.85 | 65.17 | 441.00 | 1075.52 | 21.98 | 110.33 | 419.33 |
August | 352.83 | 0.49 | 0.48 | 01-AUG-07:40 | 1471.84 | 15.54 | 0.00 | 388.67 | 909.11 | 19.01 | 31.00 | 356.67 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:49 | 1113.55 | 14.32 | 0.00 | 332.17 | 682.85 | 17.74 | 0.00 | 294.17 |
October | 299.00 | 0.51 | 0.48 | 01-OCT-07:19 | 905.47 | 12.96 | 0.00 | 281.17 | 531.06 | 16.40 | 0.00 | 232.83 |
November | 255.50 | 0.55 | 0.48 | 01-NOV-08:50 | 698.13 | 11.38 | 0.00 | 215.33 | 406.41 | 14.85 | 0.00 | 156.50 |
December | 226.33 | 0.54 | 0.48 | 01-DEC-09:20 | 665.67 | 11.28 | 0.00 | 194.67 | 388.03 | 14.85 | 0.00 | 140.17 |
Annual Sum or Average | 3785.50 | 0.51 | 1228.54 | 15.12 | 195.67 | 3848.33 | 751.56 | 18.50 | 328.33 | 3400.33 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 665.67 | 11.28 | 0.00 | 194.67 | 388.03 | 14.85 | 0.00 | 140.17 | |
Maximum of Months | 437.50 | 0.55 | 0.48 | 1830.45 | 19.35 | 76.83 | 441.00 | 1094.57 | 22.39 | 113.83 | 419.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.52 | 0.48 | 01-JAN-10:09 | 1889.09 | 22.70 | 92.67 | 227.67 | 1094.10 | 23.32 | 83.00 | 200.67 |
February | 265.33 | 0.50 | 0.48 | 01-FEB-09:30 | 2539.98 | 21.43 | 75.33 | 251.50 | 1428.89 | 23.48 | 95.67 | 229.33 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 3989.72 | 22.80 | 78.83 | 321.17 | 2352.86 | 23.63 | 72.50 | 287.67 |
April | 296.33 | 0.51 | 0.48 | 01-APR-08:09 | 4742.17 | 21.18 | 84.50 | 355.67 | 2125.42 | 20.69 | 40.67 | 329.67 |
May | 437.50 | 0.50 | 0.48 | 01-MAY-06:30 | 3873.97 | 18.89 | 81.00 | 424.00 | 2272.84 | 20.56 | 51.83 | 398.50 |
June | 401.83 | 0.49 | 0.48 | 01-JUN-05:30 | 4143.94 | 17.71 | 46.83 | 433.83 | 1888.66 | 18.80 | 0.00 | 404.17 |
July | 409.17 | 0.49 | 0.48 | 01-JUL-05:30 | 4465.21 | 18.18 | 53.67 | 436.83 | 2055.01 | 19.03 | 2.17 | 408.50 |
August | 352.83 | 0.49 | 0.48 | 01-AUG-07:49 | 4045.99 | 20.40 | 79.17 | 388.00 | 2330.65 | 21.64 | 58.50 | 355.33 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:00 | 3410.48 | 21.35 | 99.83 | 334.83 | 2004.82 | 22.61 | 78.17 | 306.83 |
October | 299.00 | 0.50 | 0.48 | 01-OCT-07:19 | 2561.03 | 21.64 | 102.67 | 291.50 | 1139.23 | 21.99 | 65.17 | 258.67 |
November | 255.50 | 0.52 | 0.48 | 01-NOV-08:50 | 1575.20 | 21.26 | 86.67 | 230.33 | 849.51 | 21.92 | 72.67 | 196.83 |
December | 226.33 | 0.52 | 0.48 | 01-DEC-09:20 | 1444.26 | 20.35 | 65.67 | 214.83 | 773.03 | 21.16 | 58.00 | 181.50 |
Annual Sum or Average | 3785.50 | 0.50 | 3390.94 | 20.38 | 946.83 | 3910.17 | 1773.16 | 21.33 | 678.33 | 3557.67 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 1444.26 | 17.71 | 46.83 | 214.83 | 773.03 | 18.80 | 0.00 | 181.50 | |
Maximum of Months | 437.50 | 0.52 | 0.48 | 4742.17 | 22.80 | 102.67 | 436.83 | 2352.86 | 23.63 | 95.67 | 408.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.49 | 0.48 | 01-JAN-08:39 | 5753.53 | 35.43 | 233.33 | 239.17 | 4882.46 | 36.49 | 234.17 | 228.50 |
February | 265.33 | 0.49 | 0.48 | 01-FEB-08:39 | 8892.29 | 35.98 | 256.50 | 258.83 | 4829.67 | 32.01 | 200.33 | 246.33 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 12528.62 | 34.66 | 215.00 | 324.33 | 2187.22 | 18.14 | 11.33 | 293.50 |
April | 296.33 | 0.52 | 0.48 | 01-APR-07:49 | 2702.03 | 14.09 | 0.00 | 352.33 | 1727.32 | 17.69 | 12.17 | 324.67 |
May | 437.50 | 0.50 | 0.48 | 01-MAY-06:19 | 2356.55 | 14.75 | 0.00 | 415.33 | 1374.08 | 18.22 | 1.50 | 381.00 |
June | 401.83 | 0.51 | 0.48 | 01-JUN-05:19 | 2251.36 | 15.05 | 0.00 | 415.17 | 1328.15 | 18.52 | 0.00 | 381.00 |
July | 409.17 | 0.50 | 0.48 | 01-JUL-05:30 | 2440.16 | 15.32 | 0.00 | 422.17 | 1449.96 | 18.80 | 7.33 | 387.00 |
August | 352.83 | 0.50 | 0.48 | 01-AUG-07:40 | 3068.69 | 15.87 | 10.00 | 381.00 | 1677.35 | 18.78 | 22.17 | 346.50 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:40 | 5903.35 | 21.50 | 115.00 | 334.83 | 1727.85 | 18.47 | 18.83 | 306.00 |
October | 299.00 | 0.49 | 0.48 | 01-OCT-06:49 | 6278.90 | 31.36 | 264.17 | 299.17 | 1836.65 | 22.85 | 106.67 | 277.50 |
November | 255.50 | 0.50 | 0.48 | 01-NOV-08:09 | 4549.61 | 34.01 | 243.67 | 241.33 | 3804.69 | 35.30 | 245.67 | 223.50 |
December | 226.33 | 0.50 | 0.48 | 01-DEC-08:20 | 4278.15 | 33.31 | 207.50 | 225.33 | 3600.74 | 34.71 | 211.00 | 207.00 |
Annual Sum or Average | 3785.50 | 0.50 | 4702.47 | 23.39 | 1545.17 | 3909.00 | 2321.53 | 22.99 | 1071.17 | 3602.50 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 2251.36 | 14.09 | 0.00 | 225.33 | 1328.15 | 17.69 | 0.00 | 207.00 | |
Maximum of Months | 437.50 | 0.52 | 0.48 | 12528.62 | 35.98 | 264.17 | 422.17 | 4882.46 | 36.49 | 245.67 | 387.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.52 | 0.48 | 01-JAN-08:39 | 1942.31 | 22.86 | 99.00 | 225.67 | 1155.32 | 23.53 | 88.67 | 199.00 |
February | 265.33 | 0.51 | 0.48 | 01-FEB-08:39 | 2516.84 | 21.10 | 73.83 | 249.67 | 1411.92 | 23.27 | 97.83 | 227.17 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 4281.45 | 22.74 | 80.83 | 321.17 | 2669.71 | 25.07 | 87.50 | 288.67 |
April | 296.33 | 0.51 | 0.48 | 01-APR-06:00 | 4594.16 | 21.59 | 84.33 | 359.00 | 2778.74 | 23.78 | 75.83 | 332.17 |
May | 437.50 | 0.50 | 0.48 | 01-MAY-05:10 | 4207.11 | 21.63 | 135.17 | 424.83 | 1938.56 | 22.33 | 86.50 | 393.50 |
June | 401.83 | 0.50 | 0.48 | 01-JUN-04:49 | 5109.68 | 23.11 | 133.00 | 423.33 | 2451.31 | 23.14 | 83.17 | 394.33 |
July | 409.17 | 0.50 | 0.48 | 01-JUL-04:40 | 4872.57 | 22.50 | 126.00 | 429.17 | 2325.51 | 23.13 | 81.67 | 400.33 |
August | 352.83 | 0.50 | 0.48 | 01-AUG-07:40 | 4107.36 | 22.15 | 99.83 | 384.83 | 1891.29 | 22.18 | 60.67 | 355.67 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:19 | 3217.01 | 21.00 | 96.83 | 334.50 | 1747.87 | 22.10 | 72.50 | 305.00 |
October | 299.00 | 0.50 | 0.48 | 01-OCT-06:40 | 2380.96 | 21.12 | 99.50 | 290.83 | 1091.29 | 21.63 | 62.00 | 257.50 |
November | 255.50 | 0.52 | 0.48 | 01-NOV-07:00 | 1596.19 | 21.43 | 90.33 | 228.83 | 891.21 | 22.29 | 71.50 | 194.83 |
December | 226.33 | 0.52 | 0.48 | 01-DEC-08:20 | 1417.18 | 20.76 | 67.33 | 208.67 | 954.02 | 23.12 | 78.50 | 179.50 |
Annual Sum or Average | 3785.50 | 0.50 | 3559.50 | 21.88 | 1186.00 | 3880.50 | 1844.19 | 22.90 | 946.33 | 3527.67 | ||
Minimum of Months | 226.33 | 0.50 | 0.48 | 1417.18 | 20.76 | 67.33 | 208.67 | 891.21 | 21.63 | 60.67 | 179.50 | |
Maximum of Months | 437.50 | 0.52 | 0.48 | 5109.68 | 23.11 | 135.17 | 429.17 | 2778.74 | 25.07 | 97.83 | 400.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.54 | 0.48 | 01-JAN-10:09 | 721.75 | 11.73 | 0.00 | 211.33 | 434.84 | 15.37 | 0.00 | 165.50 |
February | 265.33 | 0.52 | 0.48 | 01-FEB-09:30 | 919.16 | 13.15 | 0.00 | 240.33 | 572.58 | 16.73 | 0.00 | 206.00 |
March | 254.17 | 0.51 | 0.48 | 02-MAR-10:39 | 1009.89 | 14.04 | 0.00 | 314.17 | 668.82 | 17.63 | 0.00 | 269.67 |
April | 296.33 | 0.51 | 0.48 | 01-APR-07:00 | 1152.52 | 14.48 | 0.00 | 356.67 | 758.63 | 18.01 | 3.83 | 327.00 |
May | 437.50 | 0.49 | 0.48 | 01-MAY-05:19 | 1549.28 | 17.76 | 53.67 | 432.33 | 932.00 | 20.90 | 69.00 | 415.67 |
June | 401.83 | 0.49 | 0.48 | 01-JUN-04:49 | 1832.12 | 19.32 | 76.83 | 440.50 | 1095.97 | 22.38 | 113.33 | 417.67 |
July | 409.17 | 0.49 | 0.48 | 01-JUL-04:49 | 1758.34 | 18.82 | 65.17 | 441.00 | 1076.88 | 21.97 | 110.17 | 419.50 |
August | 352.83 | 0.49 | 0.48 | 01-AUG-07:40 | 1473.27 | 15.51 | 0.00 | 388.67 | 910.32 | 19.00 | 29.67 | 356.67 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:49 | 1114.76 | 14.29 | 0.00 | 332.17 | 683.81 | 17.73 | 0.00 | 294.33 |
October | 299.00 | 0.51 | 0.48 | 01-OCT-07:19 | 906.63 | 12.93 | 0.00 | 281.17 | 531.89 | 16.39 | 0.00 | 233.67 |
November | 255.50 | 0.55 | 0.48 | 01-NOV-08:50 | 699.01 | 11.35 | 0.00 | 215.50 | 407.06 | 14.84 | 0.00 | 157.17 |
December | 226.33 | 0.54 | 0.48 | 01-DEC-09:20 | 666.49 | 11.25 | 0.00 | 194.67 | 388.65 | 14.83 | 0.00 | 140.67 |
Annual Sum or Average | 3785.50 | 0.51 | 1229.74 | 15.09 | 195.67 | 3848.50 | 752.57 | 18.48 | 326.00 | 3403.50 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 666.49 | 11.25 | 0.00 | 194.67 | 388.65 | 14.83 | 0.00 | 140.67 | |
Maximum of Months | 437.50 | 0.55 | 0.48 | 1832.12 | 19.32 | 76.83 | 441.00 | 1095.97 | 22.38 | 113.33 | 419.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 243.33 | 0.52 | 0.48 | 01-JAN-10:09 | 1890.28 | 22.68 | 92.67 | 227.67 | 1095.24 | 23.31 | 83.00 | 200.83 |
February | 265.33 | 0.50 | 0.48 | 01-FEB-09:30 | 2541.39 | 21.40 | 75.33 | 251.67 | 1430.36 | 23.47 | 94.83 | 229.50 |
March | 254.17 | 0.50 | 0.48 | 02-MAR-10:39 | 3991.07 | 22.77 | 78.83 | 321.17 | 2354.46 | 23.61 | 71.83 | 287.67 |
April | 296.33 | 0.51 | 0.48 | 01-APR-08:09 | 4743.71 | 21.16 | 84.50 | 355.67 | 2127.07 | 20.67 | 40.67 | 329.83 |
May | 437.50 | 0.50 | 0.48 | 01-MAY-06:30 | 3876.39 | 18.86 | 81.00 | 424.00 | 2274.83 | 20.54 | 51.83 | 398.50 |
June | 401.83 | 0.49 | 0.48 | 01-JUN-05:30 | 4146.40 | 17.68 | 46.83 | 433.83 | 1890.80 | 18.79 | 0.00 | 404.17 |
July | 409.17 | 0.49 | 0.48 | 01-JUL-05:30 | 4467.68 | 18.15 | 53.67 | 436.83 | 2057.23 | 19.01 | 2.17 | 408.50 |
August | 352.83 | 0.49 | 0.48 | 01-AUG-07:49 | 4048.47 | 20.37 | 79.17 | 388.00 | 2332.91 | 21.62 | 58.50 | 355.33 |
September | 344.17 | 0.50 | 0.48 | 01-SEP-06:00 | 3412.52 | 21.33 | 99.83 | 335.00 | 2006.61 | 22.59 | 77.67 | 307.00 |
October | 299.00 | 0.50 | 0.48 | 01-OCT-07:19 | 2562.77 | 21.62 | 102.50 | 291.50 | 1140.73 | 21.97 | 64.83 | 258.67 |
November | 255.50 | 0.52 | 0.48 | 01-NOV-08:50 | 1576.48 | 21.23 | 86.67 | 230.33 | 850.63 | 21.91 | 72.33 | 197.00 |
December | 226.33 | 0.52 | 0.48 | 01-DEC-09:20 | 1445.45 | 20.33 | 65.67 | 214.83 | 774.09 | 21.15 | 57.83 | 182.00 |
Annual Sum or Average | 3785.50 | 0.50 | 3392.85 | 20.36 | 946.67 | 3910.50 | 1774.91 | 21.32 | 675.50 | 3559.00 | ||
Minimum of Months | 226.33 | 0.49 | 0.48 | 1445.45 | 17.68 | 46.83 | 214.83 | 774.09 | 18.79 | 0.00 | 182.00 | |
Maximum of Months | 437.50 | 0.52 | 0.48 | 4743.71 | 22.77 | 102.50 | 436.83 | 2354.46 | 23.61 | 94.83 | 408.50 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.185101E+11 | 87045.67 | 06-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.601044E+10 | 80658.09 | 14-FEB-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.108113E+10 | 61502.27 | 15-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 77901470.39 | 15333.87 | 06-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 405558.14 | 712.70 | 01-MAY-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2.91 | 0.00 | 16-JUN-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 460.77 | 0.42 | 07-JUL-20:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 713.95 | 0.90 | 17-AUG-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 779.78 | 0.68 | 06-SEP-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 46065804.63 | 24854.08 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.413886E+09 | 50702.25 | 25-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.962716E+10 | 76275.76 | 20-DEC-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.357671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.185101E+11 | 87045.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.454612E+10 | 14650.49 | 18-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.170082E+10 | 15706.99 | 28-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.451487E+09 | 15854.43 | 18-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 81154709.97 | 15767.14 | 25-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203515E+10 | 15850.48 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.881473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.454612E+10 | 15854.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.363881E+10 | 17510.51 | 02-JAN-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.161359E+10 | 17961.01 | 28-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.706118E+09 | 18020.91 | 18-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1672415.86 | 1987.88 | 05-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1172091.18 | 1430.12 | 30-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.234101E+09 | 17993.40 | 25-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.256969E+10 | 18013.72 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.876514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.363881E+10 | 18020.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.390417E+10 | 25472.35 | 20-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.174496E+10 | 25431.57 | 07-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.776227E+09 | 25496.08 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13595992.36 | 5679.73 | 04-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 21773710.27 | 25636.73 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.333617E+09 | 25629.76 | 24-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.254392E+10 | 25473.90 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.933826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.390417E+10 | 25636.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.269049E+10 | 16500.96 | 02-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.685174E+09 | 16469.58 | 13-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 58992351.88 | 16466.24 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 23340715.80 | 16979.25 | 25-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.357506E+09 | 16471.70 | 26-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.381550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.269049E+10 | 16979.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.217474E+12 | 940248.74 | 06-JAN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.705815E+11 | 880338.19 | 14-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131144E+11 | 661565.01 | 15-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.243696E+10 | 271362.00 | 06-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.538030E+09 | 125264.65 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1713.20 | 2.79 | 17-JUL-20:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2057.14 | 3.43 | 04-AUG-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.116626E+09 | 54437.76 | 23-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.249116E+10 | 358922.15 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.783049E+10 | 573306.55 | 25-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120310E+12 | 818949.07 | 20-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.434893E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.217474E+12 | 940248.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.385589E+11 | 588553.58 | 03-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.466631E+10 | 588354.32 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.115095E+10 | 586701.21 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.276594E+10 | 586804.60 | 27-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.210521E+11 | 588553.61 | 04-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.681942E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.385589E+11 | 588553.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.133865E+12 | 137502.13 | 18-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.744460E+11 | 136968.12 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.439354E+11 | 138592.06 | 30-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.660673E+10 | 136581.46 | 04-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 66496371.74 | 98216.03 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3935303.75 | 1302.04 | 23-SEP-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.532316E+10 | 136633.21 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.356961E+11 | 137392.22 | 28-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.117831E+12 | 137471.41 | 05-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.417775E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.133865E+12 | 138592.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.913931E+11 | 212994.94 | 11-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.488138E+11 | 213003.95 | 27-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.309474E+11 | 212912.21 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.572508E+10 | 212308.93 | 03-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 47893282.17 | 15841.63 | 09-MAY-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2052487.18 | 10890.11 | 19-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.571453E+09 | 27721.45 | 28-SEP-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.871765E+10 | 212098.06 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.325593E+11 | 212753.78 | 13-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.853425E+11 | 212969.24 | 21-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.304120E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.913931E+11 | 213003.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.831752E+11 | 273581.04 | 23-JAN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.404300E+11 | 273457.60 | 14-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.275023E+11 | 272284.79 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.552397E+10 | 270563.59 | 10-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.102036E+09 | 19166.46 | 01-MAY-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.102617E+09 | 10115.92 | 28-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.541232E+10 | 269445.96 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.271456E+11 | 272144.70 | 27-NOV-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.815344E+11 | 273623.15 | 18-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.270928E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.831752E+11 | 273623.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.832125E+11 | 215498.07 | 11-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.438708E+11 | 215145.69 | 27-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.273708E+11 | 215418.94 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.494102E+10 | 214505.84 | 04-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.108514E+09 | 22636.30 | 01-MAY-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 191232.07 | 424.79 | 19-AUG-05:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.325518E+09 | 20514.31 | 29-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.643656E+10 | 214582.08 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.270697E+11 | 214994.29 | 25-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.729796E+11 | 215450.44 | 27-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.266315E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.832125E+11 | 215498.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.283962E+11 | 103392.40 | 06-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.100897E+11 | 96985.32 | 14-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.225640E+10 | 72725.54 | 15-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.202402E+09 | 32709.05 | 06-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 34874073.26 | 16967.46 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 107.19 | 0.18 | 16-JUN-20:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 4.48 | 0.00 | 26-JUL-20:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17426.77 | 32.71 | 19-AUG-06:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 29785926.37 | 9383.71 | 23-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.260946E+09 | 42600.22 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.116061E+10 | 63784.30 | 25-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.175993E+11 | 89729.62 | 20-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.600302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 4.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.283962E+11 | 103392.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.200255E+11 | 81361.88 | 19-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113350E+11 | 81356.73 | 22-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.632531E+10 | 81371.54 | 27-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.125961E+10 | 81113.00 | 10-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 35153447.51 | 41190.43 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148877E+10 | 81352.93 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.737574E+10 | 81154.52 | 20-NOV-05:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167810E+11 | 81145.45 | 28-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.646261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.200255E+11 | 81371.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.199500E+11 | 15776.23 | 19-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130626E+11 | 15775.62 | 08-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.892951E+10 | 15782.47 | 22-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.243986E+10 | 15777.55 | 10-APR-04:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.121956E+09 | 15602.69 | 09-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5393634.97 | 1837.44 | 19-AUG-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.193716E+09 | 15554.85 | 23-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.251541E+10 | 15768.44 | 30-OCT-05:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.807041E+10 | 15778.60 | 09-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.184601E+11 | 15824.51 | 06-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.737490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.199500E+11 | 15824.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.131671E+11 | 23625.77 | 28-JAN-05:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.806014E+10 | 23625.15 | 14-FEB-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.541260E+10 | 23621.47 | 15-MAR-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151366E+10 | 23503.26 | 03-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 74289343.91 | 15474.29 | 01-MAY-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7029634.03 | 1625.32 | 10-JUN-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10577684.90 | 3721.87 | 19-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.269659E+09 | 12733.74 | 23-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.229933E+10 | 23608.29 | 30-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.592364E+10 | 23713.06 | 29-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.125578E+11 | 23712.10 | 08-DEC-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.492958E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.131671E+11 | 23713.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.137770E+11 | 28729.41 | 20-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.803425E+10 | 28646.28 | 25-FEB-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.596758E+10 | 28719.66 | 03-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.201890E+10 | 28633.55 | 10-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.167763E+09 | 18461.89 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 854531.70 | 273.52 | 10-JUN-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 19072817.99 | 2721.69 | 19-AUG-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.217849E+09 | 14692.16 | 28-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.220513E+10 | 28720.15 | 16-OCT-04:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.618800E+10 | 28720.38 | 28-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138267E+11 | 28723.33 | 29-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.524231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.138267E+11 | 28729.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.123446E+11 | 25110.17 | 25-JAN-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.714996E+10 | 25110.17 | 16-FEB-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.488906E+10 | 25068.38 | 14-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148826E+10 | 25069.88 | 03-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.109793E+09 | 11511.73 | 01-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2481912.64 | 996.85 | 10-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 18184507.40 | 2279.09 | 19-AUG-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.234012E+09 | 7398.59 | 28-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.185939E+10 | 25087.80 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.491705E+10 | 25084.01 | 20-NOV-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108251E+11 | 25117.76 | 01-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.438379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.123446E+11 | 25117.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.145088E+11 | 60700.84 | 06-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.510958E+10 | 59571.74 | 14-FEB-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.775421E+09 | 33944.65 | 15-MAR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 62988757.02 | 12419.28 | 28-NOV-21:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.638926E+10 | 50615.95 | 02-DEC-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.268461E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.145088E+11 | 60700.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 11185621.17 | 11185621.17 | 2364.52 | 25-JAN-13:10 | 2364.52 | 0.00 |
February | 0.00 | 0.00 | 9643875.26 | 9643875.26 | 2763.93 | 27-FEB-15:10 | 2763.93 | 0.00 |
March | 0.00 | 0.00 | 15984459.23 | 15984459.23 | 18373.14 | 06-MAR-16:55 | 18373.14 | 0.00 |
April | 0.00 | 0.00 | 0.788600E+10 | 0.788600E+10 | 159072.26 | 23-APR-16:21 | 159072.26 | 0.01 |
May | 0.00 | 0.00 | 0.550303E+11 | 0.535118E+11 | 195117.58 | 26-MAY-11:00 | 122022.60 | 0.23 |
June | 0.00 | 0.00 | 0.124916E+12 | 0.992782E+11 | 307868.29 | 30-JUN-03:02 | 121971.76 | 0.48 |
July | 0.00 | 0.00 | 0.169570E+12 | 0.126951E+12 | 322647.32 | 23-JUL-09:11 | 139229.45 | 0.68 |
August | 0.00 | 0.00 | 0.142467E+12 | 0.103219E+12 | 296635.03 | 31-AUG-12:45 | 133016.80 | 0.66 |
September | 0.00 | 0.00 | 0.303812E+11 | 0.264661E+11 | 207236.86 | 01-SEP-11:00 | 129429.79 | 0.18 |
October | 0.00 | 0.00 | 0.548083E+10 | 0.548083E+10 | 109122.00 | 19-OCT-15:00 | 109122.00 | 0.02 |
November | 0.00 | 0.00 | 0.711087E+09 | 0.711087E+09 | 39498.87 | 01-NOV-15:00 | 39498.87 | 0.01 |
December | 0.00 | 0.00 | 15831256.88 | 15831256.88 | 2931.58 | 15-DEC-08:10 | 2931.58 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.536495E+12 | 0.423557E+12 | 0.19 | |||
Minimum of Months | 0.00 | 0.00 | 9643875.26 | 9643875.26 | 2364.52 | 2364.52 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.169570E+12 | 0.126951E+12 | 322647.32 | 159072.26 | 0.68 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 17473615.81 | 17473615.81 | 3964.12 | 26-JAN-11:50 | 3964.12 | 0.00 |
February | 0.00 | 0.00 | 31518254.19 | 31518254.19 | 5664.40 | 10-FEB-11:00 | 5664.40 | 0.00 |
March | 0.00 | 0.00 | 25462051.29 | 25462051.29 | 22197.20 | 14-MAR-11:08 | 22197.20 | 0.00 |
April | 0.00 | 0.00 | 0.406221E+11 | 0.406221E+11 | 944888.05 | 23-APR-16:12 | 944888.05 | 0.01 |
May | 0.00 | 0.00 | 0.349254E+12 | 0.341876E+12 | 1276488.13 | 25-MAY-16:00 | 1098776.92 | 0.21 |
June | 0.00 | 0.00 | 0.764954E+12 | 0.626061E+12 | 1963690.47 | 29-JUN-04:12 | 958678.77 | 0.42 |
July | 0.00 | 0.00 | 0.986641E+12 | 0.773749E+12 | 2546637.35 | 05-JUL-10:35 | 905086.17 | 0.56 |
August | 0.00 | 0.00 | 0.736072E+12 | 0.577499E+12 | 1911781.44 | 31-AUG-12:50 | 871974.71 | 0.54 |
September | 0.00 | 0.00 | 0.176214E+12 | 0.160947E+12 | 1354579.04 | 01-SEP-11:00 | 893832.06 | 0.16 |
October | 0.00 | 0.00 | 0.326185E+11 | 0.326185E+11 | 679722.67 | 19-OCT-15:00 | 679722.67 | 0.02 |
November | 0.00 | 0.00 | 0.249864E+10 | 0.249864E+10 | 152331.10 | 01-NOV-15:00 | 152331.10 | 0.01 |
December | 0.00 | 0.00 | 16160531.70 | 16160531.70 | 4364.34 | 02-DEC-11:20 | 4364.34 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.308896E+13 | 0.255596E+13 | 0.16 | |||
Minimum of Months | 0.00 | 0.00 | 16160531.70 | 16160531.70 | 3964.12 | 3964.12 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.986641E+12 | 0.773749E+12 | 2546637.35 | 1098776.92 | 0.56 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1955716.33 | 1955716.33 | 438.07 | 25-JAN-13:10 | 438.07 | 0.00 |
February | 0.00 | 0.00 | 3787443.51 | 3787443.51 | 2223.68 | 01-FEB-06:01 | 2223.68 | 0.00 |
March | 0.00 | 0.00 | 16005505.04 | 16005505.04 | 1222.02 | 20-MAR-12:50 | 1222.02 | 0.00 |
April | 0.00 | 0.00 | 0.367565E+10 | 0.367565E+10 | 102997.07 | 23-APR-15:51 | 102997.07 | 0.01 |
May | 0.00 | 0.00 | 0.368646E+11 | 0.360900E+11 | 145452.94 | 25-MAY-16:00 | 127598.25 | 0.20 |
June | 0.00 | 0.00 | 0.802929E+11 | 0.659502E+11 | 247848.56 | 25-JUN-11:31 | 130780.16 | 0.41 |
July | 0.00 | 0.00 | 0.104781E+12 | 0.821597E+11 | 270272.89 | 05-JUL-11:50 | 115938.13 | 0.55 |
August | 0.00 | 0.00 | 0.757714E+11 | 0.594074E+11 | 213770.68 | 29-AUG-15:40 | 125859.63 | 0.53 |
September | 0.00 | 0.00 | 0.166300E+11 | 0.152341E+11 | 155615.76 | 01-SEP-14:00 | 121596.98 | 0.15 |
October | 0.00 | 0.00 | 0.291659E+10 | 0.291659E+10 | 65676.67 | 19-OCT-15:00 | 65676.67 | 0.02 |
November | 0.00 | 0.00 | 0.234006E+09 | 0.234006E+09 | 12754.81 | 01-NOV-15:00 | 12754.81 | 0.01 |
December | 0.00 | 0.00 | 2841429.79 | 2841429.79 | 421.80 | 12-DEC-05:01 | 421.80 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.321191E+12 | 0.265692E+12 | 0.16 | |||
Minimum of Months | 0.00 | 0.00 | 1955716.33 | 1955716.33 | 421.80 | 421.80 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.104781E+12 | 0.821597E+11 | 270272.89 | 130780.16 | 0.55 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 62140555.16 | 62140555.16 | 9983.61 | 27-JAN-21:00 | 9983.61 | 0.00 |
February | 0.00 | 0.00 | 0.157383E+09 | 0.156865E+09 | 22196.55 | 22-FEB-07:17 | 13569.24 | 0.00 |
March | 0.00 | 0.00 | 0.146400E+09 | 0.143539E+09 | 62060.51 | 23-MAR-06:18 | 14375.15 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 21350011.67 | 21350011.67 | 17539.08 | 29-NOV-07:15 | 17539.08 | 0.00 |
December | 0.00 | 0.00 | 0.254932E+09 | 0.237754E+09 | 109904.55 | 08-DEC-07:19 | 28264.06 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.642205E+09 | 0.621648E+09 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.254932E+09 | 0.237754E+09 | 109904.55 | 28264.06 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.606516E+10 | 0.606516E+10 | 2922.98 | 21-JAN-16:00 | 2922.98 | 0.00 |
February | 0.00 | 0.00 | 0.106773E+11 | 0.106465E+11 | 5095.25 | 20-FEB-17:42 | 5095.25 | 0.00 |
March | 0.00 | 0.00 | 0.141402E+11 | 0.141076E+11 | 5532.17 | 05-MAR-06:50 | 5266.96 | 0.00 |
April | 0.00 | 0.00 | 0.465603E+11 | 0.453335E+11 | 402783.22 | 23-APR-15:51 | 399013.74 | 0.00 |
May | 0.00 | 0.00 | 0.275318E+11 | 0.261604E+11 | 165713.38 | 25-MAY-13:10 | 132865.08 | 0.00 |
June | 0.00 | 0.00 | 0.162729E+12 | 0.121124E+12 | 503505.90 | 29-JUN-24:00 | 217108.45 | 0.00 |
July | 0.00 | 0.00 | 0.501739E+12 | 0.316919E+12 | 550211.32 | 15-JUL-14:00 | 285528.42 | 0.00 |
August | 0.00 | 0.00 | 0.618317E+12 | 0.377396E+12 | 525617.67 | 31-AUG-12:55 | 249257.95 | 0.00 |
September | 0.00 | 0.00 | 0.518606E+10 | 0.464426E+10 | 133504.10 | 01-SEP-15:00 | 115237.64 | 0.00 |
October | 0.00 | 0.00 | 0.989795E+10 | 0.971103E+10 | 85830.25 | 19-OCT-15:00 | 85830.25 | 0.00 |
November | 0.00 | 0.00 | 0.137675E+11 | 0.134734E+11 | 72355.89 | 01-NOV-15:00 | 55888.29 | 0.00 |
December | 0.00 | 0.00 | 0.147093E+11 | 0.146796E+11 | 5836.84 | 06-DEC-03:00 | 5487.71 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.143132E+13 | 0.960260E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.518606E+10 | 0.464426E+10 | 2922.98 | 2922.98 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.618317E+12 | 0.377396E+12 | 550211.32 | 399013.74 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.218816E+10 | 0.218816E+10 | 2164.18 | 20-JAN-16:25 | 2164.18 | 0.00 |
February | 0.00 | 0.00 | 0.766412E+10 | 0.766412E+10 | 4731.36 | 20-FEB-16:57 | 4731.36 | 0.00 |
March | 0.00 | 0.00 | 0.145386E+11 | 0.145386E+11 | 7800.84 | 31-MAR-24:00 | 7800.84 | 0.00 |
April | 0.00 | 0.00 | 0.201623E+11 | 0.201623E+11 | 9400.35 | 16-APR-18:20 | 9400.35 | 0.00 |
May | 0.00 | 0.00 | 0.626238E+10 | 0.621967E+10 | 4049.33 | 31-MAY-24:00 | 4049.33 | 0.00 |
June | 0.00 | 0.00 | 0.112786E+11 | 0.110814E+11 | 6096.54 | 30-JUN-23:55 | 6090.56 | 0.00 |
July | 0.00 | 0.00 | 0.170132E+11 | 0.167354E+11 | 7978.01 | 31-JUL-23:54 | 7978.01 | 0.00 |
August | 0.00 | 0.00 | 0.219210E+11 | 0.216316E+11 | 9508.96 | 13-AUG-18:31 | 9508.96 | 0.00 |
September | 0.00 | 0.00 | 0.585507E+10 | 0.580012E+10 | 4139.54 | 30-SEP-24:00 | 4139.54 | 0.00 |
October | 0.00 | 0.00 | 0.105542E+11 | 0.105485E+11 | 5718.02 | 31-OCT-24:00 | 5718.02 | 0.00 |
November | 0.00 | 0.00 | 0.144869E+11 | 0.144817E+11 | 6720.59 | 12-NOV-16:10 | 6720.59 | 0.00 |
December | 0.00 | 0.00 | 0.185701E+11 | 0.185701E+11 | 7990.78 | 10-DEC-16:00 | 7990.78 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.150495E+12 | 0.149622E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.218816E+10 | 0.218816E+10 | 2164.18 | 2164.18 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.219210E+11 | 0.216316E+11 | 9508.96 | 9508.96 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.231242E+10 | 0.231242E+10 | 16393.23 | 20-JAN-16:25 | 16393.23 | 0.00 |
February | 0.00 | 0.00 | 0.500291E+11 | 0.500291E+11 | 41581.39 | 08-FEB-17:00 | 41581.39 | 0.00 |
March | 0.00 | 0.00 | 0.118417E+12 | 0.118417E+12 | 69799.28 | 31-MAR-23:30 | 69799.28 | 0.00 |
April | 0.00 | 0.00 | 0.177974E+12 | 0.177974E+12 | 86969.28 | 21-APR-18:20 | 86969.28 | 0.00 |
May | 0.00 | 0.00 | 0.527668E+11 | 0.523463E+11 | 35462.05 | 14-MAY-18:43 | 35462.05 | 0.00 |
June | 0.00 | 0.00 | 0.102698E+12 | 0.100745E+12 | 58121.47 | 30-JUN-23:03 | 57736.78 | 0.00 |
July | 0.00 | 0.00 | 0.158335E+12 | 0.155578E+12 | 74984.19 | 31-JUL-23:54 | 74984.19 | 0.00 |
August | 0.00 | 0.00 | 0.203776E+12 | 0.200899E+12 | 87609.24 | 05-AUG-18:40 | 87609.24 | 0.00 |
September | 0.00 | 0.00 | 0.461465E+11 | 0.456137E+11 | 36009.82 | 03-SEP-17:42 | 35907.17 | 0.00 |
October | 0.00 | 0.00 | 0.820482E+11 | 0.819918E+11 | 46797.25 | 19-OCT-16:50 | 46192.98 | 0.00 |
November | 0.00 | 0.00 | 0.111028E+12 | 0.110976E+12 | 57921.53 | 17-NOV-16:10 | 57921.53 | 0.00 |
December | 0.00 | 0.00 | 0.143901E+12 | 0.143901E+12 | 66871.72 | 08-DEC-15:55 | 66871.72 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.124943E+13 | 0.124078E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.231242E+10 | 0.231242E+10 | 16393.23 | 16393.23 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.203776E+12 | 0.200899E+12 | 87609.24 | 87609.24 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 82875228.49 | 82875228.49 | 1450.05 | 20-JAN-16:25 | 1450.05 | 0.00 |
February | 0.00 | 0.00 | 0.327915E+10 | 0.327915E+10 | 4101.37 | 08-FEB-17:00 | 4101.37 | 0.00 |
March | 0.00 | 0.00 | 0.101125E+11 | 0.101125E+11 | 6557.89 | 31-MAR-23:20 | 6557.89 | 0.00 |
April | 0.00 | 0.00 | 0.165483E+11 | 0.165483E+11 | 8686.29 | 21-APR-18:20 | 8686.29 | 0.00 |
May | 0.00 | 0.00 | 0.484377E+10 | 0.480171E+10 | 3542.22 | 25-MAY-18:50 | 3395.80 | 0.00 |
June | 0.00 | 0.00 | 0.100533E+11 | 0.985832E+10 | 5856.61 | 30-JUN-23:03 | 5817.71 | 0.00 |
July | 0.00 | 0.00 | 0.157336E+11 | 0.154581E+11 | 7424.50 | 31-JUL-23:54 | 7424.50 | 0.00 |
August | 0.00 | 0.00 | 0.202034E+11 | 0.199162E+11 | 8853.68 | 05-AUG-18:35 | 8853.68 | 0.00 |
September | 0.00 | 0.00 | 0.398251E+10 | 0.393012E+10 | 3579.04 | 03-SEP-17:42 | 3568.60 | 0.00 |
October | 0.00 | 0.00 | 0.665315E+10 | 0.664763E+10 | 4708.55 | 19-OCT-16:50 | 4647.86 | 0.00 |
November | 0.00 | 0.00 | 0.913528E+10 | 0.913018E+10 | 5670.78 | 17-NOV-16:10 | 5670.78 | 0.00 |
December | 0.00 | 0.00 | 0.126170E+11 | 0.126170E+11 | 6396.76 | 20-DEC-16:00 | 6396.76 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.113245E+12 | 0.112382E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 82875228.49 | 82875228.49 | 1450.05 | 1450.05 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.202034E+11 | 0.199162E+11 | 8853.68 | 8853.68 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 298293.91 | 2231696.65 | 09-JAN-07:15 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 146922.60 | 2039571.54 | 27-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 67485.73 | 1880610.16 | 06-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 13127.19 | 1667562.64 | 04-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 524.51 | 309660.33 | 01-MAY-05:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 3.60 | 1588.59 | 10-JUN-05:10 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 2.86 | 17-JUL-20:00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 19.26 | 17490.87 | 19-AUG-05:10 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 783.27 | 95237.26 | 23-SEP-06:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14525.66 | 1618450.89 | 30-OCT-04:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 64430.82 | 2057984.80 | 27-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 227555.53 | 2166164.61 | 28-DEC-06:01 |
Annual Sum or Average | 0.00 | 69382.80 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 2.86 | ||
Maximum of Months | 0.00 | 0.00 | 298293.91 | 2231696.65 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 174.84 | 7457.37 | 26-JAN-11:00 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 297.33 | 13011.99 | 24-FEB-09:20 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 268.66 | 17286.73 | 14-MAR-11:08 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 20481.24 | 728210.04 | 23-APR-16:13 | 0.00 | 0.00 | 01-APR-00:10 |
May | 171265.43 | 1946582.23 | 17-MAY-12:25 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 385907.81 | 2304630.65 | 19-JUN-15:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 495106.71 | 4445176.46 | 05-JUL-11:00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 368609.21 | 2379867.55 | 31-AUG-12:50 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 87602.12 | 1695616.08 | 01-SEP-11:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 15580.34 | 893622.07 | 19-OCT-14:20 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 1484.75 | 205888.61 | 01-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 353.77 | 30403.63 | 01-DEC-07:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 130040.36 | 0.00 | ||||
Minimum of Months | 174.84 | 7457.37 | 0.00 | 0.00 | ||
Maximum of Months | 495106.71 | 4445176.46 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 7.53 | 4502.55 | 26-JAN-11:00 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 51.97 | 12416.76 | 22-FEB-07:17 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 63.50 | 41645.58 | 23-MAR-06:18 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 20104.12 | 1228164.96 | 23-APR-14:11 | 0.00 | 0.00 | 01-APR-00:10 |
May | 170782.06 | 2186229.16 | 17-MAY-12:15 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 383809.53 | 3373364.11 | 29-JUN-04:12 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 494021.27 | 4366429.05 | 05-JUL-11:00 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 366469.14 | 2749319.91 | 09-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 86979.93 | 1777516.69 | 01-SEP-10:10 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 15314.65 | 900574.87 | 19-OCT-14:20 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 1340.32 | 203238.17 | 01-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 89.62 | 71173.78 | 08-DEC-07:19 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 129363.43 | 0.00 | ||||
Minimum of Months | 7.53 | 4502.55 | 0.00 | 0.00 | ||
Maximum of Months | 494021.27 | 4366429.05 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 9695.48 | 57035.09 | 27-JAN-16:10 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 42351.23 | 147879.44 | 08-FEB-17:35 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 78391.15 | 252731.47 | 15-MAR-21:02 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 141130.44 | 1389303.86 | 23-APR-16:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 111473.50 | 961868.09 | 25-MAY-18:00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 314150.57 | 1542327.62 | 29-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 606585.57 | 1867185.70 | 15-JUL-14:10 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 623187.41 | 1846156.71 | 08-AUG-15:10 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 50884.24 | 744039.83 | 01-SEP-15:10 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 57911.53 | 460641.89 | 19-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 76561.27 | 238524.31 | 01-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 93737.05 | 307669.71 | 12-DEC-22:02 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 185419.35 | 0.00 | ||||
Minimum of Months | 9695.48 | 57035.09 | 0.00 | 0.00 | ||
Maximum of Months | 623187.41 | 1867185.70 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 17178.46 | 61748.29 | 31-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17672.25 | 62342.20 | 24-FEB-12:20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 18709.63 | 62328.45 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 17004.36 | 61075.57 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 16707.80 | 58692.69 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 16109.70 | 55326.86 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 14048.94 | 52009.01 | 03-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 14953.83 | 49961.48 | 01-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 14083.48 | 50382.61 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14600.01 | 53040.05 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 15662.82 | 56302.84 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 15992.62 | 59349.72 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 16050.86 | ||||
Minimum of Months | 0.00 | 0.00 | 14048.94 | 49961.48 | ||
Maximum of Months | 0.00 | 0.00 | 18709.63 | 62342.20 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 15.50 | 9983.12 | 28-JAN-11:00 | 2744.39 | 153804.21 | 26-JAN-20:30 |
February | 14.16 | 9420.92 | 06-FEB-20:50 | 3452.51 | 151678.76 | 28-FEB-07:15 |
March | 28.58 | 9946.26 | 07-MAR-20:50 | 2731.34 | 158527.81 | 06-MAR-07:15 |
April | 21482.10 | 752450.98 | 13-APR-15:20 | 1057.97 | 150618.12 | 20-APR-05:05 |
May | 225507.44 | 3194880.16 | 25-MAY-16:00 | 1215.42 | 105605.59 | 06-MAY-12:30 |
June | 693009.29 | 6012305.97 | 30-JUN-15:20 | 703.37 | 103158.20 | 02-JUN-15:10 |
July | 898294.62 | 7212774.46 | 05-JUL-11:00 | 354.92 | 54059.51 | 31-JUL-03:10 |
August | 611918.85 | 5734355.47 | 31-AUG-12:50 | 795.55 | 66827.09 | 18-AUG-16:10 |
September | 105022.56 | 2802952.04 | 01-SEP-11:00 | 760.45 | 89746.19 | 09-SEP-08:50 |
October | 17063.15 | 1001723.28 | 19-OCT-14:20 | 788.44 | 119610.03 | 17-OCT-09:10 |
November | 1487.47 | 240621.76 | 01-NOV-15:00 | 1148.22 | 143217.61 | 27-NOV-14:40 |
December | 24.66 | 9930.45 | 27-DEC-16:40 | 3503.74 | 158944.83 | 10-DEC-05:02 |
Annual Sum or Average | 216353.08 | 1597.04 | ||||
Minimum of Months | 14.16 | 9420.92 | 354.92 | 54059.51 | ||
Maximum of Months | 898294.62 | 7212774.46 | 3503.74 | 158944.83 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.371814E+10 | 0.32 | 12641.90 | 20-JAN-06:01 | 1.32 |
February | 0.433051E+10 | 0.36 | 16470.98 | 22-FEB-10:07 | 1.56 |
March | 0.753553E+10 | 0.45 | 23399.60 | 06-MAR-15:10 | 1.95 |
April | 0.159184E+11 | 0.72 | 23399.60 | 10-APR-14:40 | 1.95 |
May | 0.193750E+11 | 0.79 | 23399.60 | 02-MAY-14:40 | 1.95 |
June | 0.221591E+11 | 0.89 | 23399.60 | 01-JUN-09:40 | 1.94 |
July | 0.239129E+11 | 0.93 | 23399.60 | 03-JUL-05:02 | 1.93 |
August | 0.242652E+11 | 0.96 | 23399.60 | 01-AUG-11:10 | 1.93 |
September | 0.159344E+11 | 0.72 | 23399.60 | 01-SEP-09:10 | 1.92 |
October | 0.127036E+11 | 0.61 | 23399.60 | 18-OCT-15:40 | 1.94 |
November | 0.970799E+10 | 0.51 | 19367.05 | 17-NOV-14:20 | 1.73 |
December | 0.461989E+10 | 0.34 | 15382.65 | 01-DEC-10:30 | 1.50 |
Annual Sum or Average | 0.164181E+12 | 0.63 | |||
Minimum of Months | 0.371814E+10 | 0.32 | 12641.90 | 1.32 | |
Maximum of Months | 0.242652E+11 | 0.96 | 23399.60 | 1.95 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.438038E+11 | 0.41 | 64455.84 | 02-JAN-04:01 | 0.92 |
February | 0.367246E+11 | 0.37 | 158560.98 | 10-FEB-14:47 | 1.59 |
March | 0.427769E+11 | 0.38 | 103298.77 | 30-MAR-05:03 | 1.21 |
April | 0.520518E+11 | 0.39 | 128135.19 | 13-APR-15:10 | 1.39 |
May | 0.828325E+11 | 0.48 | 187126.77 | 18-MAY-14:40 | 1.74 |
June | 0.101574E+12 | 0.55 | 219328.07 | 29-JUN-04:12 | 1.92 |
July | 0.112317E+12 | 0.56 | 219328.07 | 03-JUL-05:02 | 1.93 |
August | 0.949723E+11 | 0.53 | 201008.84 | 08-AUG-15:20 | 1.82 |
September | 0.610388E+11 | 0.42 | 175448.26 | 01-SEP-16:00 | 1.67 |
October | 0.417508E+11 | 0.34 | 103165.34 | 20-OCT-15:20 | 1.21 |
November | 0.345470E+11 | 0.33 | 64455.84 | 27-NOV-05:01 | 0.92 |
December | 0.419998E+11 | 0.40 | 64455.84 | 26-DEC-05:32 | 0.92 |
Annual Sum or Average | 0.746389E+12 | 0.43 | |||
Minimum of Months | 0.345470E+11 | 0.33 | 64455.84 | 0.92 | |
Maximum of Months | 0.112317E+12 | 0.56 | 219328.07 | 1.93 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.529768E+10 | 0.47 | 6031.49 | 02-JAN-04:01 | 0.85 |
February | 0.448228E+10 | 0.44 | 6031.49 | 01-FEB-05:01 | 0.85 |
March | 0.449836E+10 | 0.40 | 6031.49 | 01-MAR-06:01 | 0.85 |
April | 0.449556E+10 | 0.36 | 11664.11 | 13-APR-15:00 | 1.24 |
May | 0.737652E+10 | 0.43 | 20870.84 | 18-MAY-14:40 | 1.76 |
June | 0.971594E+10 | 0.51 | 23534.91 | 29-JUN-04:12 | 1.90 |
July | 0.108090E+11 | 0.52 | 23873.69 | 05-JUL-10:45 | 1.91 |
August | 0.868531E+10 | 0.48 | 22035.86 | 08-AUG-15:20 | 1.83 |
September | 0.503606E+10 | 0.37 | 19260.37 | 01-SEP-16:00 | 1.68 |
October | 0.371879E+10 | 0.33 | 9062.22 | 20-OCT-15:10 | 1.07 |
November | 0.410765E+10 | 0.39 | 6031.49 | 04-NOV-05:01 | 0.85 |
December | 0.502084E+10 | 0.46 | 6031.49 | 01-DEC-05:11 | 0.85 |
Annual Sum or Average | 0.732440E+11 | 0.43 | |||
Minimum of Months | 0.371879E+10 | 0.33 | 6031.49 | 0.85 | |
Maximum of Months | 0.108090E+11 | 0.52 | 23873.69 | 1.91 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.744233E+10 | 0.53 | 13386.51 | 02-JAN-07:30 | 1.94 |
February | 0.962823E+10 | 0.65 | 13386.51 | 01-FEB-07:10 | 1.98 |
March | 0.977242E+10 | 0.57 | 13386.51 | 01-MAR-19:20 | 1.92 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
November | 0.242962E+10 | 0.14 | 13386.51 | 25-NOV-07:10 | 1.89 |
December | 0.901972E+10 | 0.56 | 13386.51 | 01-DEC-07:10 | 1.92 |
Annual Sum or Average | 0.382923E+11 | 0.20 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.977242E+10 | 0.65 | 13386.51 | 1.98 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.113227E+12 | 1.41 | 42274.09 | 01-JAN-00:01 | 1.41 |
February | 0.102269E+12 | 1.41 | 42274.09 | 01-FEB-00:03 | 1.41 |
March | 0.113227E+12 | 1.41 | 42274.09 | 01-MAR-00:10 | 1.41 |
April | 0.109574E+12 | 1.41 | 42274.09 | 01-APR-00:10 | 1.41 |
May | 0.113227E+12 | 1.40 | 42274.09 | 01-MAY-00:03 | 1.41 |
June | 0.109574E+12 | 1.40 | 42274.09 | 01-JUN-00:10 | 1.40 |
July | 0.113227E+12 | 1.39 | 42274.09 | 01-JUL-00:03 | 1.40 |
August | 0.113227E+12 | 1.40 | 42274.09 | 01-AUG-00:03 | 1.39 |
September | 0.109574E+12 | 1.40 | 42274.09 | 01-SEP-00:03 | 1.39 |
October | 0.113227E+12 | 1.41 | 42274.09 | 01-OCT-00:10 | 1.41 |
November | 0.109574E+12 | 1.41 | 42274.09 | 01-NOV-00:10 | 1.41 |
December | 0.113227E+12 | 1.41 | 42274.09 | 01-DEC-00:10 | 1.41 |
Annual Sum or Average | 0.133316E+13 | 1.41 | |||
Minimum of Months | 0.102269E+12 | 1.39 | 42274.09 | 1.39 | |
Maximum of Months | 0.113227E+12 | 1.41 | 42274.09 | 1.41 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.159629E+10 | 0.96 | 595.98 | 01-JAN-00:01 | 0.95 |
February | 0.144181E+10 | 0.96 | 595.98 | 01-FEB-00:03 | 0.96 |
March | 0.159629E+10 | 0.96 | 595.98 | 01-MAR-00:10 | 0.96 |
April | 0.154479E+10 | 0.96 | 595.98 | 01-APR-00:10 | 0.96 |
May | 0.159629E+10 | 0.95 | 595.98 | 01-MAY-00:03 | 0.96 |
June | 0.154479E+10 | 0.95 | 595.98 | 01-JUN-00:10 | 0.95 |
July | 0.159629E+10 | 0.95 | 595.98 | 01-JUL-00:03 | 0.95 |
August | 0.159629E+10 | 0.95 | 595.98 | 01-AUG-00:03 | 0.95 |
September | 0.154479E+10 | 0.95 | 595.98 | 01-SEP-00:03 | 0.95 |
October | 0.159629E+10 | 0.96 | 595.98 | 01-OCT-00:10 | 0.95 |
November | 0.154479E+10 | 0.96 | 595.98 | 01-NOV-00:10 | 0.96 |
December | 0.159629E+10 | 0.96 | 595.98 | 01-DEC-00:10 | 0.96 |
Annual Sum or Average | 0.187950E+11 | 0.96 | |||
Minimum of Months | 0.144181E+10 | 0.95 | 595.98 | 0.95 | |
Maximum of Months | 0.159629E+10 | 0.96 | 595.98 | 0.96 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.153779E+11 | 0.96 | 5741.45 | 01-JAN-00:01 | 0.96 |
February | 0.138897E+11 | 0.96 | 5741.45 | 01-FEB-00:03 | 0.96 |
March | 0.153779E+11 | 0.96 | 5741.45 | 01-MAR-00:10 | 0.96 |
April | 0.148818E+11 | 0.96 | 5741.45 | 01-APR-00:10 | 0.96 |
May | 0.153779E+11 | 0.95 | 5741.45 | 01-MAY-00:03 | 0.96 |
June | 0.148818E+11 | 0.95 | 5741.45 | 01-JUN-00:10 | 0.95 |
July | 0.153779E+11 | 0.95 | 5741.45 | 01-JUL-00:03 | 0.95 |
August | 0.153779E+11 | 0.95 | 5741.45 | 01-AUG-00:03 | 0.95 |
September | 0.148818E+11 | 0.95 | 5741.45 | 01-SEP-00:03 | 0.95 |
October | 0.153779E+11 | 0.96 | 5741.45 | 01-OCT-00:10 | 0.95 |
November | 0.148818E+11 | 0.96 | 5741.45 | 01-NOV-00:10 | 0.96 |
December | 0.153779E+11 | 0.96 | 5741.45 | 01-DEC-00:10 | 0.96 |
Annual Sum or Average | 0.181062E+12 | 0.96 | |||
Minimum of Months | 0.138897E+11 | 0.95 | 5741.45 | 0.95 | |
Maximum of Months | 0.153779E+11 | 0.96 | 5741.45 | 0.96 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.155879E+10 | 0.96 | 581.99 | 01-JAN-00:01 | 0.96 |
February | 0.140794E+10 | 0.96 | 581.99 | 01-FEB-00:03 | 0.96 |
March | 0.155879E+10 | 0.96 | 581.99 | 01-MAR-00:10 | 0.96 |
April | 0.150851E+10 | 0.96 | 581.99 | 01-APR-00:10 | 0.96 |
May | 0.155879E+10 | 0.95 | 581.99 | 01-MAY-00:03 | 0.96 |
June | 0.150851E+10 | 0.95 | 581.99 | 01-JUN-00:10 | 0.95 |
July | 0.155879E+10 | 0.95 | 581.99 | 01-JUL-00:03 | 0.95 |
August | 0.155879E+10 | 0.95 | 581.99 | 01-AUG-00:03 | 0.95 |
September | 0.150851E+10 | 0.95 | 581.99 | 01-SEP-00:03 | 0.95 |
October | 0.155879E+10 | 0.96 | 581.99 | 01-OCT-00:10 | 0.95 |
November | 0.150851E+10 | 0.96 | 581.99 | 01-NOV-00:10 | 0.96 |
December | 0.155879E+10 | 0.96 | 581.99 | 01-DEC-00:10 | 0.96 |
Annual Sum or Average | 0.183535E+11 | 0.96 | |||
Minimum of Months | 0.140794E+10 | 0.95 | 581.99 | 0.95 | |
Maximum of Months | 0.155879E+10 | 0.96 | 581.99 | 0.96 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.172965E+09 | 0.155669E+09 | 1683.07 | 09-JAN-07:15 | 1514.76 | 1514.76 | 46.06 | 14.85 |
February | 52729178.87 | 47456260.98 | 1123.73 | 14-FEB-06:01 | 1011.36 | 1011.36 | 47.71 | 12.46 |
March | 14395220.53 | 12955698.48 | 1123.23 | 06-MAR-06:01 | 1010.90 | 1010.90 | 46.73 | 12.46 |
April | 1708402.27 | 1537562.04 | 376.12 | 04-APR-05:01 | 338.50 | 338.50 | 38.28 | 7.59 |
May | 44125.38 | 39712.84 | 15.59 | 01-MAY-05:03 | 14.04 | 14.04 | 25.18 | 1.30 |
June | 235.92 | 212.32 | 0.04 | 10-JUN-05:10 | 0.04 | 0.04 | 23.34 | 0.01 |
July | 0.05 | 0.05 | 0.00 | 17-JUL-20:00 | 0.00 | 0.00 | 23.21 | 0.00 |
August | 1311.66 | 1180.49 | 0.46 | 19-AUG-05:10 | 0.41 | 0.41 | 23.03 | 0.07 |
September | 52906.09 | 47615.48 | 2.89 | 23-SEP-06:10 | 2.60 | 2.60 | 20.82 | 0.37 |
October | 1749671.88 | 1574704.70 | 395.69 | 30-OCT-05:01 | 356.12 | 356.12 | 39.17 | 7.77 |
November | 12404339.75 | 11163905.77 | 1082.72 | 28-NOV-06:01 | 974.45 | 974.45 | 43.17 | 12.28 |
December | 99787923.78 | 89809131.40 | 1370.90 | 26-DEC-07:10 | 1233.81 | 1233.81 | 45.75 | 13.60 |
Annual Sum or Average | 0.355839E+09 | 0.320255E+09 | ||||||
Minimum of Months | 0.05 | 0.05 | 0.00 | 0.00 | 0.00 | 20.82 | 0.00 | |
Maximum of Months | 0.172965E+09 | 0.155669E+09 | 1683.07 | 1514.76 | 1514.76 | 47.71 | 14.85 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 8222.50 | 7400.25 | 1.50 | 26-JAN-11:00 | 1.35 | 1.35 | 6.70 | 0.40 |
February | 16861.18 | 15175.06 | 1.56 | 22-FEB-07:17 | 1.40 | 1.40 | 6.70 | 0.42 |
March | 15984.60 | 14386.14 | 4.46 | 23-MAR-06:18 | 4.02 | 4.02 | 6.70 | 1.04 |
April | 16942790.50 | 15248511.45 | 1626.76 | 23-APR-14:11 | 1464.09 | 1464.09 | 6.70 | 32.66 |
May | 0.382681E+09 | 0.344413E+09 | 8796.96 | 17-MAY-12:15 | 7917.26 | 7917.26 | 10.66 | 65.97 |
June | 0.801838E+09 | 0.721654E+09 | 11017.15 | 30-JUN-05:03 | 9915.44 | 9915.44 | 10.36 | 72.12 |
July | 0.128209E+10 | 0.115388E+10 | 11023.77 | 05-JUL-11:00 | 9921.39 | 9921.39 | 12.33 | 72.12 |
August | 0.806915E+09 | 0.726223E+09 | 11015.30 | 09-AUG-05:03 | 9913.77 | 9913.77 | 9.43 | 72.12 |
September | 0.187192E+09 | 0.168473E+09 | 4075.56 | 07-SEP-14:20 | 3668.01 | 3668.01 | 8.19 | 48.28 |
October | 33791944.53 | 30412750.07 | 2208.61 | 19-OCT-14:20 | 1987.75 | 1987.75 | 6.71 | 37.29 |
November | 1064172.25 | 957755.02 | 71.44 | 01-NOV-15:00 | 64.30 | 64.30 | 6.70 | 6.94 |
December | 23651.26 | 21286.14 | 10.40 | 08-DEC-07:19 | 9.36 | 9.36 | 6.70 | 2.00 |
Annual Sum or Average | 0.351258E+10 | 0.316132E+10 | ||||||
Minimum of Months | 8222.50 | 7400.25 | 1.50 | 1.35 | 1.35 | 6.70 | 0.40 | |
Maximum of Months | 0.128209E+10 | 0.115388E+10 | 11023.77 | 9921.39 | 9921.39 | 12.33 | 72.12 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.498410E+09 | 0.448569E+09 | 4273.92 | 02-JAN-15:00 | 3846.53 | 3846.53 | 6.72 | 37.81 |
February | 0.660083E+09 | 0.594075E+09 | 4273.92 | 01-FEB-04:04 | 3846.53 | 3846.53 | 6.72 | 37.81 |
March | 0.610026E+09 | 0.549024E+09 | 4273.92 | 01-MAR-10:40 | 3846.53 | 3846.53 | 6.73 | 37.81 |
April | 0.112985E+10 | 0.101687E+10 | 4273.92 | 03-APR-06:00 | 3846.53 | 3846.53 | 6.72 | 37.81 |
May | 0.412031E+10 | 0.370828E+10 | 4273.92 | 01-MAY-07:17 | 3846.53 | 3846.53 | 6.73 | 37.81 |
June | 0.660003E+10 | 0.594002E+10 | 4273.92 | 01-JUN-04:15 | 3846.53 | 3846.53 | 6.74 | 37.81 |
July | 0.810868E+10 | 0.729782E+10 | 4273.92 | 01-JUL-00:03 | 3846.53 | 3846.53 | 6.75 | 37.81 |
August | 0.777967E+10 | 0.700170E+10 | 4273.92 | 01-AUG-00:03 | 3846.53 | 3846.53 | 6.76 | 37.81 |
September | 0.322755E+10 | 0.290480E+10 | 4273.92 | 01-SEP-00:20 | 3846.53 | 3846.53 | 7.01 | 37.81 |
October | 0.832901E+09 | 0.749611E+09 | 4273.92 | 01-OCT-09:12 | 3846.53 | 3846.53 | 6.74 | 37.81 |
November | 0.417201E+09 | 0.375481E+09 | 4273.92 | 01-NOV-09:50 | 3846.53 | 3846.53 | 6.74 | 37.81 |
December | 0.786103E+09 | 0.707492E+09 | 4273.92 | 01-DEC-07:17 | 3846.53 | 3846.53 | 6.73 | 37.81 |
Annual Sum or Average | 0.347708E+11 | 0.312937E+11 | ||||||
Minimum of Months | 0.417201E+09 | 0.375481E+09 | 4273.92 | 3846.53 | 3846.53 | 6.72 | 37.81 | |
Maximum of Months | 0.810868E+10 | 0.729782E+10 | 4273.92 | 3846.53 | 3846.53 | 7.01 | 37.81 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 6.70 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 6.72 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 6.75 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 6.73 | 0.00 |
May | 0.396192E+09 | 0.356573E+09 | 4273.92 | 16-MAY-14:00 | 3846.53 | 3846.53 | 15.13 | 18.90 |
June | 0.100181E+10 | 0.901626E+09 | 4273.92 | 06-JUN-11:50 | 3846.53 | 3846.53 | 15.20 | 18.90 |
July | 0.154865E+10 | 0.139379E+10 | 4273.92 | 03-JUL-12:10 | 3846.53 | 3846.53 | 14.81 | 18.90 |
August | 0.112319E+10 | 0.101087E+10 | 4273.92 | 07-AUG-13:00 | 3846.53 | 3846.53 | 15.11 | 18.90 |
September | 0.110267E+09 | 99240360.07 | 4273.92 | 01-SEP-09:00 | 3846.53 | 3846.53 | 15.49 | 18.90 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 6.76 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 6.73 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
Annual Sum or Average | 0.418010E+10 | 0.376209E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 | |
Maximum of Months | 0.154865E+10 | 0.139379E+10 | 4273.92 | 3846.53 | 3846.53 | 15.49 | 18.90 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.103805E+11 | 0.934242E+10 | 3875.62 | 01-JAN-00:01 | 3488.06 | 3488.06 | 18.47 | 16.19 |
February | 0.937591E+10 | 0.843832E+10 | 3875.62 | 01-FEB-00:03 | 3488.06 | 3488.06 | 18.87 | 16.19 |
March | 0.103805E+11 | 0.934242E+10 | 3875.62 | 01-MAR-00:10 | 3488.06 | 3488.06 | 19.68 | 16.19 |
April | 0.100456E+11 | 0.904106E+10 | 3875.62 | 01-APR-00:10 | 3488.06 | 3488.06 | 20.39 | 16.19 |
May | 0.103805E+11 | 0.934242E+10 | 3875.62 | 01-MAY-00:03 | 3488.06 | 3488.06 | 18.90 | 16.19 |
June | 0.100456E+11 | 0.904106E+10 | 3875.62 | 01-JUN-00:10 | 3488.06 | 3488.06 | 19.37 | 16.19 |
July | 0.103805E+11 | 0.934242E+10 | 3875.62 | 01-JUL-00:03 | 3488.06 | 3488.06 | 19.94 | 16.19 |
August | 0.103805E+11 | 0.934242E+10 | 3875.62 | 01-AUG-00:03 | 3488.06 | 3488.06 | 25.56 | 16.19 |
September | 0.100456E+11 | 0.904106E+10 | 3875.62 | 01-SEP-00:03 | 3488.06 | 3488.06 | 20.72 | 16.19 |
October | 0.103805E+11 | 0.934242E+10 | 3875.62 | 01-OCT-00:10 | 3488.06 | 3488.06 | 19.38 | 16.19 |
November | 0.100456E+11 | 0.904106E+10 | 3875.62 | 01-NOV-00:10 | 3488.06 | 3488.06 | 19.75 | 16.19 |
December | 0.103805E+11 | 0.934242E+10 | 3875.62 | 01-DEC-00:10 | 3488.06 | 3488.06 | 20.13 | 16.19 |
Annual Sum or Average | 0.122222E+12 | 0.110000E+12 | ||||||
Minimum of Months | 0.937591E+10 | 0.843832E+10 | 3875.62 | 3488.06 | 3488.06 | 18.47 | 16.19 | |
Maximum of Months | 0.103805E+11 | 0.934242E+10 | 3875.62 | 3488.06 | 3488.06 | 25.56 | 16.19 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:01 | 16.86 | 16.86 | 56.98 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:01 | 16.86 | 16.86 | 56.68 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:01 | 16.86 | 16.86 | 56.52 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:03 | 16.86 | 16.86 | 56.39 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:03 | 16.86 | 16.86 | 56.75 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 56.74 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 56.93 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 57.06 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 57.10 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:05 | 16.86 | 16.86 | 56.87 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:03 | 16.86 | 16.86 | 56.88 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:01 | 16.86 | 16.86 | 56.86 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 56.39 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.10 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.191514E+10 | 0.172363E+10 | 16425.64 | 28-JAN-11:00 | 14783.08 | 14783.08 | 21.14 | 66.59 |
February | 0.253315E+10 | 0.227983E+10 | 16425.62 | 06-FEB-20:50 | 14783.06 | 14783.06 | 21.13 | 66.59 |
March | 0.234410E+10 | 0.210969E+10 | 16425.64 | 07-MAR-20:50 | 14783.08 | 14783.08 | 21.14 | 66.59 |
April | 0.434442E+10 | 0.390998E+10 | 16457.18 | 13-APR-15:20 | 14811.46 | 14811.46 | 23.80 | 66.59 |
May | 0.172801E+11 | 0.155521E+11 | 32993.70 | 25-MAY-16:00 | 29694.33 | 29694.33 | 26.84 | 133.18 |
June | 0.290827E+11 | 0.261744E+11 | 33065.93 | 19-JUN-14:20 | 29759.34 | 29759.34 | 29.50 | 133.18 |
July | 0.369273E+11 | 0.332345E+11 | 33065.93 | 03-JUL-13:00 | 29759.34 | 29759.34 | 29.91 | 133.18 |
August | 0.340211E+11 | 0.306190E+11 | 33065.93 | 07-AUG-15:50 | 29759.34 | 29759.34 | 29.45 | 133.18 |
September | 0.128294E+11 | 0.115464E+11 | 32974.23 | 01-SEP-11:00 | 29676.81 | 29676.81 | 26.14 | 133.18 |
October | 0.320280E+10 | 0.288252E+10 | 16467.80 | 19-OCT-14:20 | 14821.02 | 14821.02 | 24.70 | 66.59 |
November | 0.160340E+10 | 0.144306E+10 | 16435.43 | 01-NOV-15:00 | 14791.89 | 14791.89 | 21.96 | 66.59 |
December | 0.302070E+10 | 0.271863E+10 | 16425.64 | 27-DEC-16:40 | 14783.07 | 14783.07 | 21.14 | 66.59 |
Annual Sum or Average | 0.149104E+12 | 0.134194E+12 | ||||||
Minimum of Months | 0.160340E+10 | 0.144306E+10 | 16425.62 | 14783.06 | 14783.06 | 21.13 | 66.59 | |
Maximum of Months | 0.369273E+11 | 0.332345E+11 | 33065.93 | 29759.34 | 29759.34 | 29.91 | 133.18 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 37.34 | 37.34 | 298293.91 | 2231696.65 | 09-JAN-07:15 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 39.35 | 82.00 | 146922.60 | 2039571.54 | 27-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 23.93 | 23.93 | 67485.73 | 1880610.16 | 06-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 29.09 | 29.09 | 13127.19 | 1667562.64 | 04-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.67 | 22.67 | 524.51 | 309660.33 | 01-MAY-05:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 23.34 | 23.34 | 3.60 | 1588.59 | 10-JUN-05:10 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 23.21 | 23.21 | 0.00 | 2.86 | 17-JUL-20:00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.21 | 23.21 | 19.26 | 17490.87 | 19-AUG-05:10 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 22.73 | 22.73 | 783.27 | 95237.26 | 23-SEP-06:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 19.42 | 19.42 | 14525.66 | 1618450.89 | 30-OCT-04:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.94 | 22.94 | 64430.82 | 2057984.80 | 27-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 24.97 | 24.97 | 227555.53 | 2166164.61 | 28-DEC-06:01 |
Annual Sum or Average | 0.00 | 69382.80 | ||||||
Minimum of Months | 0.00 | 0.00 | 19.42 | 19.42 | 0.00 | 2.86 | ||
Maximum of Months | 0.00 | 0.00 | 39.35 | 82.00 | 298293.91 | 2231696.65 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 174.84 | 7457.37 | 26-JAN-11:00 | 6.75 | 6.70 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 297.33 | 13011.99 | 24-FEB-09:20 | 6.78 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 268.66 | 17286.73 | 14-MAR-11:08 | 6.81 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 20481.24 | 728210.04 | 23-APR-16:13 | 11.30 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 171265.43 | 1946582.23 | 17-MAY-12:25 | 12.85 | 6.70 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 385907.81 | 2304630.65 | 19-JUN-15:20 | 13.98 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 495106.71 | 4445176.46 | 05-JUL-11:00 | 20.76 | 12.36 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 368609.21 | 2379867.55 | 31-AUG-12:50 | 14.22 | 6.70 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 87602.12 | 1695616.08 | 01-SEP-11:00 | 12.05 | 6.70 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 15580.34 | 893622.07 | 19-OCT-14:20 | 12.34 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 1484.75 | 205888.61 | 01-NOV-15:00 | 8.00 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 353.77 | 30403.63 | 01-DEC-07:30 | 6.89 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 130040.36 | 0.00 | ||||||
Minimum of Months | 174.84 | 7457.37 | 6.75 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 495106.71 | 4445176.46 | 20.76 | 12.36 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 7.53 | 4502.55 | 26-JAN-11:00 | 9.36 | 6.70 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 51.97 | 12416.76 | 22-FEB-07:17 | 13.79 | 6.70 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 63.50 | 41645.58 | 23-MAR-06:18 | 16.26 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 20104.12 | 1228164.96 | 23-APR-14:11 | 15.69 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 170782.06 | 2186229.16 | 17-MAY-12:15 | 14.62 | 10.76 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 383809.53 | 3373364.11 | 29-JUN-04:12 | 17.88 | 12.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 494021.27 | 4366429.05 | 05-JUL-11:00 | 21.18 | 12.33 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 366469.14 | 2749319.91 | 09-AUG-05:03 | 15.81 | 11.02 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 86979.93 | 1777516.69 | 01-SEP-10:10 | 16.70 | 8.36 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 15314.65 | 900574.87 | 19-OCT-14:20 | 12.47 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 1340.32 | 203238.17 | 01-NOV-15:00 | 13.69 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 89.62 | 71173.78 | 08-DEC-07:19 | 15.19 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 129363.43 | 0.00 | ||||||
Minimum of Months | 7.53 | 4502.55 | 9.36 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 494021.27 | 4366429.05 | 21.18 | 12.33 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 9695.48 | 57035.09 | 27-JAN-16:10 | 19.35 | 18.33 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 42351.23 | 147879.44 | 08-FEB-17:35 | 20.96 | 18.33 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 78391.15 | 252731.47 | 15-MAR-21:02 | 22.82 | 18.33 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 141130.44 | 1389303.86 | 23-APR-16:00 | 42.55 | 30.89 | 0.00 | 0.00 | 01-APR-00:10 |
May | 111473.50 | 961868.09 | 25-MAY-18:00 | 35.22 | 30.92 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 314150.57 | 1542327.62 | 29-JUN-16:00 | 45.15 | 37.69 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 606585.57 | 1867185.70 | 15-JUL-14:10 | 50.63 | 36.31 | 0.00 | 0.00 | 01-JUL-00:03 |
August | 623187.41 | 1846156.71 | 08-AUG-15:10 | 50.28 | 35.85 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 50884.24 | 744039.83 | 01-SEP-15:10 | 31.44 | 27.49 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 57911.53 | 460641.89 | 19-OCT-15:00 | 26.48 | 23.31 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 76561.27 | 238524.31 | 01-NOV-15:00 | 22.57 | 19.40 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 93737.05 | 307669.71 | 12-DEC-22:02 | 23.79 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 185419.35 | 0.00 | ||||||
Minimum of Months | 9695.48 | 57035.09 | 19.35 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 623187.41 | 1867185.70 | 50.63 | 37.69 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 57.78 | 57.78 | 17178.46 | 61748.29 | 31-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 57.11 | 57.11 | 17672.25 | 62342.20 | 24-FEB-12:20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.08 | 57.08 | 18709.63 | 62328.45 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.13 | 57.13 | 17004.36 | 61075.57 | 03-APR-11:40 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 57.81 | 57.81 | 16707.80 | 58692.69 | 01-MAY-12:00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.41 | 57.41 | 16109.70 | 55326.86 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 57.56 | 57.56 | 14048.94 | 52009.01 | 03-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 57.67 | 57.67 | 14953.83 | 49961.48 | 01-AUG-12:00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 57.70 | 57.70 | 14083.48 | 50382.61 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.65 | 57.65 | 14600.01 | 53040.05 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.52 | 57.52 | 15662.82 | 56302.84 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.37 | 57.37 | 15992.62 | 59349.72 | 29-DEC-12:20 |
Annual Sum or Average | 0.00 | 16050.86 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.08 | 57.08 | 14048.94 | 49961.48 | ||
Maximum of Months | 0.00 | 0.00 | 57.81 | 57.81 | 18709.63 | 62342.20 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 15.50 | 9983.12 | 28-JAN-11:00 | 21.14 | 20.27 | 2744.39 | 153804.21 | 26-JAN-20:30 |
February | 14.16 | 9420.92 | 06-FEB-20:50 | 21.13 | 20.26 | 3452.51 | 151678.76 | 28-FEB-07:15 |
March | 28.58 | 9946.26 | 07-MAR-20:50 | 21.14 | 20.27 | 2731.34 | 158527.81 | 06-MAR-07:15 |
April | 21482.10 | 752450.98 | 13-APR-15:20 | 23.80 | 21.10 | 1057.97 | 150618.12 | 20-APR-05:05 |
May | 225507.44 | 3194880.16 | 25-MAY-16:00 | 26.84 | 23.62 | 1215.42 | 105605.59 | 06-MAY-12:30 |
June | 693009.29 | 6012305.97 | 30-JUN-15:20 | 31.90 | 28.10 | 703.37 | 103158.20 | 02-JUN-15:10 |
July | 898294.62 | 7212774.46 | 05-JUL-11:00 | 34.06 | 28.51 | 354.92 | 54059.51 | 31-JUL-03:10 |
August | 611918.85 | 5734355.47 | 31-AUG-12:50 | 31.40 | 26.57 | 795.55 | 66827.09 | 18-AUG-16:10 |
September | 105022.56 | 2802952.04 | 01-SEP-11:00 | 26.14 | 22.72 | 760.45 | 89746.19 | 09-SEP-08:50 |
October | 17063.15 | 1001723.28 | 19-OCT-14:20 | 24.70 | 21.10 | 788.44 | 119610.03 | 17-OCT-09:10 |
November | 1487.47 | 240621.76 | 01-NOV-15:00 | 21.96 | 21.10 | 1148.22 | 143217.61 | 27-NOV-14:40 |
December | 24.66 | 9930.45 | 27-DEC-16:40 | 21.14 | 20.27 | 3503.74 | 158944.83 | 10-DEC-05:02 |
Annual Sum or Average | 216353.08 | 1597.04 | ||||||
Minimum of Months | 14.16 | 9420.92 | 21.13 | 20.26 | 354.92 | 54059.51 | ||
Maximum of Months | 898294.62 | 7212774.46 | 34.06 | 28.51 | 3503.74 | 158944.83 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.332897E+11 | 0.00 | 11185621.17 | 0.371814E+10 | 0.00 | 0.00 |
February | 0.117550E+11 | 0.00 | 9643875.26 | 0.433051E+10 | 0.00 | 0.00 |
March | 0.307396E+10 | 0.00 | 15984459.23 | 0.753553E+10 | 0.00 | 0.00 |
April | 93169878.61 | 0.00 | 0.788600E+10 | 0.159184E+11 | 0.00 | 0.00 |
May | 405558.14 | 0.00 | 0.550303E+11 | 0.193750E+11 | 0.00 | 0.00 |
June | 2.91 | 0.00 | 0.124916E+12 | 0.221591E+11 | 0.00 | 0.00 |
July | 460.77 | 0.00 | 0.169570E+12 | 0.239129E+11 | 0.00 | 0.00 |
August | 713.95 | 0.00 | 0.142467E+12 | 0.242652E+11 | 0.00 | 0.00 |
September | 779.78 | 0.00 | 0.303812E+11 | 0.159344E+11 | 0.00 | 0.00 |
October | 69011606.08 | 0.00 | 0.548083E+10 | 0.127036E+11 | 0.00 | 0.00 |
November | 0.108610E+10 | 0.00 | 0.711087E+09 | 0.970799E+10 | 0.00 | 0.00 |
December | 0.171334E+11 | 0.00 | 15831256.88 | 0.461989E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.665007E+11 | 0.00 | 0.536495E+12 | 0.164181E+12 | 0.00 | 0.00 |
Minimum of Months | 2.91 | 0.00 | 9643875.26 | 0.371814E+10 | 0.00 | 0.00 |
Maximum of Months | 0.332897E+11 | 0.00 | 0.169570E+12 | 0.242652E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.647679E+12 | 0.00 | 17473615.81 | 0.438038E+11 | 0.00 | 0.00 |
February | 0.282808E+12 | 0.00 | 31518254.19 | 0.367246E+11 | 0.00 | 0.00 |
March | 0.144021E+12 | 0.00 | 25462051.29 | 0.427769E+11 | 0.00 | 0.00 |
April | 0.252338E+11 | 0.00 | 0.406221E+11 | 0.520518E+11 | 0.00 | 0.00 |
May | 0.862970E+09 | 0.00 | 0.349254E+12 | 0.828325E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.764954E+12 | 0.101574E+12 | 0.00 | 0.00 |
July | 1713.20 | 0.00 | 0.986641E+12 | 0.112317E+12 | 0.00 | 0.00 |
August | 2245776.39 | 0.00 | 0.736072E+12 | 0.949723E+11 | 0.00 | 0.00 |
September | 0.112015E+10 | 0.00 | 0.176214E+12 | 0.610388E+11 | 0.00 | 0.00 |
October | 0.283808E+11 | 0.00 | 0.326185E+11 | 0.417508E+11 | 0.00 | 0.00 |
November | 0.133067E+12 | 0.00 | 0.249864E+10 | 0.345470E+11 | 0.00 | 0.00 |
December | 0.499050E+12 | 0.00 | 16160531.70 | 0.419998E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.176223E+13 | 0.00 | 0.308896E+13 | 0.746389E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 16160531.70 | 0.345470E+11 | 0.00 | 0.00 |
Maximum of Months | 0.647679E+12 | 0.00 | 0.986641E+12 | 0.112317E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.107660E+12 | 0.00 | 1955716.33 | 0.529768E+10 | 0.00 | 0.00 |
February | 0.577317E+11 | 0.00 | 3787443.51 | 0.448228E+10 | 0.00 | 0.00 |
March | 0.337805E+11 | 0.00 | 16005505.04 | 0.449836E+10 | 0.00 | 0.00 |
April | 0.892268E+10 | 0.00 | 0.367565E+10 | 0.449556E+10 | 0.00 | 0.00 |
May | 0.543829E+09 | 0.00 | 0.368646E+11 | 0.737652E+10 | 0.00 | 0.00 |
June | 10366185.56 | 0.00 | 0.802929E+11 | 0.971594E+10 | 0.00 | 0.00 |
July | 4.48 | 0.00 | 0.104781E+12 | 0.108090E+11 | 0.00 | 0.00 |
August | 53246072.03 | 0.00 | 0.757714E+11 | 0.868531E+10 | 0.00 | 0.00 |
September | 0.945022E+09 | 0.00 | 0.166300E+11 | 0.503606E+10 | 0.00 | 0.00 |
October | 0.106290E+11 | 0.00 | 0.291659E+10 | 0.371879E+10 | 0.00 | 0.00 |
November | 0.336355E+11 | 0.00 | 0.234006E+09 | 0.410765E+10 | 0.00 | 0.00 |
December | 0.900499E+11 | 0.00 | 2841429.79 | 0.502084E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.343962E+12 | 0.00 | 0.321191E+12 | 0.732440E+11 | 0.00 | 0.00 |
Minimum of Months | 4.48 | 0.00 | 1955716.33 | 0.371879E+10 | 0.00 | 0.00 |
Maximum of Months | 0.107660E+12 | 0.00 | 0.104781E+12 | 0.108090E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.145088E+11 | 0.00 | 62140555.16 | 0.744233E+10 | 0.00 | 0.00 |
February | 0.510958E+10 | 0.00 | 0.157383E+09 | 0.962823E+10 | 0.00 | 0.00 |
March | 0.775421E+09 | 0.00 | 0.146400E+09 | 0.977242E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 62988757.02 | 0.00 | 21350011.67 | 0.242962E+10 | 0.00 | 0.00 |
December | 0.638926E+10 | 0.00 | 0.254932E+09 | 0.901972E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.268461E+11 | 0.00 | 0.642205E+09 | 0.382923E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145088E+11 | 0.00 | 0.254932E+09 | 0.977242E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.106204E+11 | 0.242926E+12 | 0.00 | 46.55 |
February | 0.00 | 0.00 | 0.163283E+11 | 0.318393E+12 | 0.00 | 78.30 |
March | 0.00 | 0.00 | 0.213143E+11 | 0.388112E+12 | 0.00 | 99.59 |
April | 0.00 | 0.00 | 0.639265E+11 | 0.379128E+12 | 0.00 | 93.81 |
May | 0.00 | 0.00 | 0.393702E+11 | 0.228853E+12 | 0.00 | 38.61 |
June | 0.00 | 0.00 | 0.215359E+12 | 0.207755E+12 | 0.00 | 16.94 |
July | 0.00 | 0.00 | 0.645954E+12 | 0.258215E+12 | 0.00 | 0.29 |
August | 0.00 | 0.00 | 0.787778E+12 | 0.284303E+12 | 0.00 | 0.60 |
September | 0.00 | 0.00 | 0.965217E+10 | 0.156241E+12 | 0.00 | 15.70 |
October | 0.00 | 0.00 | 0.156336E+11 | 0.290259E+12 | 0.00 | 63.72 |
November | 0.00 | 0.00 | 0.207485E+11 | 0.358374E+12 | 0.00 | 89.96 |
December | 0.00 | 0.00 | 0.223450E+11 | 0.388703E+12 | 0.00 | 99.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.186903E+13 | 0.350126E+13 | 0.00 | 643.71 |
Minimum of Months | 0.00 | 0.00 | 0.965217E+10 | 0.156241E+12 | 0.00 | 0.29 |
Maximum of Months | 0.00 | 0.00 | 0.787778E+12 | 0.388703E+12 | 0.00 | 99.64 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.284477E+10 | 0.225289E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.970489E+10 | 0.348258E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.181355E+11 | 0.519321E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.248773E+11 | 0.625977E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.789792E+10 | 0.323183E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.141753E+11 | 0.444148E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.214092E+11 | 0.599231E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.272225E+11 | 0.689776E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.731594E+10 | 0.300566E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.130946E+11 | 0.413670E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.180102E+11 | 0.506811E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.231123E+11 | 0.613844E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.187800E+12 | 0.561007E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.284477E+10 | 0.225289E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.272225E+11 | 0.689776E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.308851E+10 | 0.161540E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.638220E+11 | 0.276825E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.148273E+12 | 0.452332E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.220110E+12 | 0.570178E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.667181E+11 | 0.293292E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.129260E+12 | 0.414438E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.199433E+12 | 0.564756E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.253324E+12 | 0.649256E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.578494E+11 | 0.265848E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.102185E+12 | 0.355146E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.138700E+12 | 0.425548E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.180075E+12 | 0.515520E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.156284E+13 | 0.494468E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.308851E+10 | 0.161540E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.253324E+12 | 0.649256E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.109343E+09 | 0.158526E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.420045E+10 | 0.232924E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.126969E+11 | 0.414323E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.205076E+11 | 0.546782E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.613581E+10 | 0.285083E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.126678E+11 | 0.412299E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.198331E+11 | 0.565827E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.251347E+11 | 0.649009E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.500516E+10 | 0.253116E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.831185E+10 | 0.321749E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.114490E+11 | 0.382222E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.158341E+11 | 0.477591E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.141886E+12 | 0.469945E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.109343E+09 | 0.158526E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.251347E+11 | 0.649009E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.371814E+10 | 11185621.17 | 0.332897E+11 | 0.502951E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.433051E+10 | 9643875.26 | 0.117550E+11 | 0.367462E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.753553E+10 | 15984459.23 | 0.307396E+10 | 0.253374E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.159184E+11 | 0.788600E+10 | 93169878.61 | 0.917984E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.193750E+11 | 0.550303E+11 | 405558.14 | 0.230068E+09 | 0.223292E+09 | 0.00 | 0.00 | 0.00 |
June | 0.221591E+11 | 0.124916E+12 | 2.91 | 16229572.63 | 0.371549E+10 | 0.00 | 0.00 | 0.00 |
July | 0.239129E+11 | 0.169570E+12 | 460.77 | 23047917.36 | 0.471301E+10 | 0.00 | 0.00 | 0.00 |
August | 0.242652E+11 | 0.142467E+12 | 713.95 | 0.00 | 0.244849E+10 | 0.00 | 0.00 | 0.00 |
September | 0.159344E+11 | 0.303812E+11 | 779.78 | 0.00 | 49103989.26 | 0.00 | 0.00 | 0.00 |
October | 0.127036E+11 | 0.548083E+10 | 69011606.08 | 0.368999E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.970799E+10 | 0.711087E+09 | 0.108610E+10 | 0.874344E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.461989E+10 | 15831256.88 | 0.171334E+11 | 0.454886E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164181E+12 | 0.536495E+12 | 0.665007E+11 | 0.168167E+12 | 0.111494E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.371814E+10 | 9643875.26 | 2.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.242652E+11 | 0.169570E+12 | 0.332897E+11 | 0.502951E+11 | 0.471301E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.438038E+11 | 17473615.81 | 0.647679E+12 | 0.538366E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.367246E+11 | 31518254.19 | 0.282808E+12 | 0.432150E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.427769E+11 | 25462051.29 | 0.144021E+12 | 0.365424E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.520518E+11 | 0.406221E+11 | 0.252338E+11 | 0.804384E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.828325E+11 | 0.349254E+12 | 0.862970E+09 | 0.605258E+10 | 0.186814E+10 | 0.00 | 0.00 | 0.00 |
June | 0.101574E+12 | 0.764954E+12 | 0.00 | 0.402615E+09 | 0.360740E+11 | 0.00 | 0.00 | 0.00 |
July | 0.112317E+12 | 0.986641E+12 | 1713.20 | 0.881907E+09 | 0.440039E+11 | 0.00 | 0.00 | 0.00 |
August | 0.949723E+11 | 0.736072E+12 | 2245776.39 | 67745976.35 | 0.213985E+11 | 0.00 | 0.00 | 0.00 |
September | 0.610388E+11 | 0.176214E+12 | 0.112015E+10 | 0.129275E+10 | 0.436883E+09 | 0.00 | 0.00 | 0.00 |
October | 0.417508E+11 | 0.326185E+11 | 0.283808E+11 | 0.586230E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.345470E+11 | 0.249864E+10 | 0.133067E+12 | 0.232457E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.419998E+11 | 16160531.70 | 0.499050E+12 | 0.532223E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.746389E+12 | 0.308896E+13 | 0.176223E+13 | 0.224838E+13 | 0.103781E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.345470E+11 | 16160531.70 | 0.00 | 67745976.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.112317E+12 | 0.986641E+12 | 0.647679E+12 | 0.538366E+12 | 0.440039E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.529768E+10 | 1955716.33 | 0.107660E+12 | 0.534684E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.448228E+10 | 3787443.51 | 0.577317E+11 | 0.447366E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.449836E+10 | 16005505.04 | 0.337805E+11 | 0.405792E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.449556E+10 | 0.367565E+10 | 0.892268E+10 | 0.111066E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.737652E+10 | 0.368646E+11 | 0.543829E+09 | 0.938326E+09 | 0.134608E+09 | 0.00 | 0.00 | 0.00 |
June | 0.971594E+10 | 0.802929E+11 | 10366185.56 | 24846909.51 | 0.322288E+10 | 0.00 | 0.00 | 0.00 |
July | 0.108090E+11 | 0.104781E+12 | 4.48 | 54160572.77 | 0.371319E+10 | 0.00 | 0.00 | 0.00 |
August | 0.868531E+10 | 0.757714E+11 | 53246072.03 | 22755893.81 | 0.165719E+10 | 0.00 | 0.00 | 0.00 |
September | 0.503606E+10 | 0.166300E+11 | 0.945022E+09 | 0.488266E+09 | 16577434.01 | 0.00 | 0.00 | 0.00 |
October | 0.371879E+10 | 0.291659E+10 | 0.106290E+11 | 0.917663E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.410765E+10 | 0.234006E+09 | 0.336355E+11 | 0.272738E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.502084E+10 | 2841429.79 | 0.900499E+11 | 0.545870E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.732440E+11 | 0.321191E+12 | 0.343962E+12 | 0.242456E+12 | 0.874444E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.371879E+10 | 1955716.33 | 4.48 | 22755893.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.108090E+11 | 0.104781E+12 | 0.107660E+12 | 0.545870E+11 | 0.371319E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.744233E+10 | 62140555.16 | 0.145088E+11 | 0.180666E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.962823E+10 | 0.157383E+09 | 0.510958E+10 | 0.930493E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.977242E+10 | 0.146400E+09 | 0.775421E+09 | 0.356886E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.242962E+10 | 21350011.67 | 62988757.02 | 0.409142E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.901972E+10 | 0.254932E+09 | 0.638926E+10 | 0.813814E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.382923E+11 | 0.642205E+09 | 0.268461E+11 | 0.394877E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.977242E+10 | 0.254932E+09 | 0.145088E+11 | 0.180666E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.113227E+12 | 0.606516E+10 | 0.00 | 0.00 | 0.00 | 0.124583E+12 | 0.00 | 0.00 |
February | 0.102269E+12 | 0.106773E+11 | 0.00 | 0.00 | 0.00 | 0.209529E+12 | 0.00 | 0.00 |
March | 0.113227E+12 | 0.141402E+11 | 0.00 | 0.00 | 0.00 | 0.266511E+12 | 0.00 | 0.00 |
April | 0.109574E+12 | 0.465603E+11 | 0.00 | 0.00 | 0.00 | 0.251057E+12 | 0.00 | 0.00 |
May | 0.113227E+12 | 0.275318E+11 | 0.00 | 0.00 | 0.00 | 0.103323E+12 | 0.00 | 0.00 |
June | 0.109574E+12 | 0.162729E+12 | 0.00 | 0.00 | 0.00 | 0.453458E+11 | 0.00 | 0.00 |
July | 0.113227E+12 | 0.501739E+12 | 0.00 | 0.00 | 0.00 | 0.768991E+09 | 0.00 | 0.00 |
August | 0.113227E+12 | 0.618317E+12 | 0.00 | 0.00 | 0.00 | 0.160823E+10 | 0.00 | 0.00 |
September | 0.109574E+12 | 0.518606E+10 | 0.00 | 0.00 | 0.00 | 0.420117E+11 | 0.00 | 0.00 |
October | 0.113227E+12 | 0.989795E+10 | 0.00 | 0.00 | 0.00 | 0.170529E+12 | 0.00 | 0.00 |
November | 0.109574E+12 | 0.137675E+11 | 0.00 | 0.00 | 0.00 | 0.240735E+12 | 0.00 | 0.00 |
December | 0.113227E+12 | 0.147093E+11 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.133316E+13 | 0.143132E+13 | 0.00 | 0.00 | 0.00 | 0.172264E+13 | 0.00 | 0.00 |
Minimum of Months | 0.102269E+12 | 0.518606E+10 | 0.00 | 0.00 | 0.00 | 0.768991E+09 | 0.00 | 0.00 |
Maximum of Months | 0.113227E+12 | 0.618317E+12 | 0.00 | 0.00 | 0.00 | 0.266640E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.159629E+10 | 0.218816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144181E+10 | 0.766412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159629E+10 | 0.145386E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154479E+10 | 0.201623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159629E+10 | 0.626238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154479E+10 | 0.112786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.159629E+10 | 0.170132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.159629E+10 | 0.219210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.154479E+10 | 0.585507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.159629E+10 | 0.105542E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154479E+10 | 0.144869E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159629E+10 | 0.185701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187950E+11 | 0.150495E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.144181E+10 | 0.218816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.159629E+10 | 0.219210E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.153779E+11 | 0.231242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138897E+11 | 0.500291E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153779E+11 | 0.118417E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148818E+11 | 0.177974E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153779E+11 | 0.527668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.148818E+11 | 0.102698E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153779E+11 | 0.158335E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153779E+11 | 0.203776E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.148818E+11 | 0.461465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153779E+11 | 0.820482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148818E+11 | 0.111028E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153779E+11 | 0.143901E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181062E+12 | 0.124943E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.138897E+11 | 0.231242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153779E+11 | 0.203776E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.155879E+10 | 82875228.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140794E+10 | 0.327915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155879E+10 | 0.101125E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150851E+10 | 0.165483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.155879E+10 | 0.484377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.150851E+10 | 0.100533E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155879E+10 | 0.157336E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.155879E+10 | 0.202034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150851E+10 | 0.398251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155879E+10 | 0.665315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150851E+10 | 0.913528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155879E+10 | 0.126170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183535E+11 | 0.113245E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.140794E+10 | 82875228.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.155879E+10 | 0.202034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.371814E+10 | 0.332897E+11 | 11185621.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.433051E+10 | 0.117550E+11 | 9643875.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.753553E+10 | 0.307396E+10 | 15984459.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.159184E+11 | 93169878.61 | 0.788600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.193750E+11 | 405558.14 | 0.550303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.221591E+11 | 2.91 | 0.124916E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.239129E+11 | 460.77 | 0.169570E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.242652E+11 | 713.95 | 0.142467E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159344E+11 | 779.78 | 0.303812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.127036E+11 | 69011606.08 | 0.548083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.970799E+10 | 0.108610E+10 | 0.711087E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.461989E+10 | 0.171334E+11 | 15831256.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164181E+12 | 0.665007E+11 | 0.536495E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.371814E+10 | 2.91 | 9643875.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.242652E+11 | 0.332897E+11 | 0.169570E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.438038E+11 | 0.647679E+12 | 17473615.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.367246E+11 | 0.282808E+12 | 31518254.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.427769E+11 | 0.144021E+12 | 25462051.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.520518E+11 | 0.252338E+11 | 0.406221E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.828325E+11 | 0.862970E+09 | 0.349254E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.101574E+12 | 0.00 | 0.764954E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.112317E+12 | 1713.20 | 0.986641E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.949723E+11 | 2245776.39 | 0.736072E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.610388E+11 | 0.112015E+10 | 0.176214E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.417508E+11 | 0.283808E+11 | 0.326185E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.345470E+11 | 0.133067E+12 | 0.249864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.419998E+11 | 0.499050E+12 | 16160531.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.746389E+12 | 0.176223E+13 | 0.308896E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.345470E+11 | 0.00 | 16160531.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.112317E+12 | 0.647679E+12 | 0.986641E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.529768E+10 | 0.107660E+12 | 1955716.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.448228E+10 | 0.577317E+11 | 3787443.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.449836E+10 | 0.337805E+11 | 16005505.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.449556E+10 | 0.892268E+10 | 0.367565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.737652E+10 | 0.543829E+09 | 0.368646E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.971594E+10 | 10366185.56 | 0.802929E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.108090E+11 | 4.48 | 0.104781E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.868531E+10 | 53246072.03 | 0.757714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.503606E+10 | 0.945022E+09 | 0.166300E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.371879E+10 | 0.106290E+11 | 0.291659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.410765E+10 | 0.336355E+11 | 0.234006E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.502084E+10 | 0.900499E+11 | 2841429.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.732440E+11 | 0.343962E+12 | 0.321191E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.371879E+10 | 4.48 | 1955716.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.108090E+11 | 0.107660E+12 | 0.104781E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.744233E+10 | 0.145088E+11 | 62140555.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.962823E+10 | 0.510958E+10 | 0.157383E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.977242E+10 | 0.775421E+09 | 0.146400E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.242962E+10 | 62988757.02 | 21350011.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.901972E+10 | 0.638926E+10 | 0.254932E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.382923E+11 | 0.268461E+11 | 0.642205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.977242E+10 | 0.145088E+11 | 0.254932E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.113227E+12 | 0.00 | 0.106204E+11 | 0.00 | 0.455525E+10 | 0.00 | 0.00 | 0.00 | 0.125144E+12 | 0.00 | 0.00 | 0.00 |
February | 0.102269E+12 | 0.00 | 0.163283E+11 | 0.00 | 0.565103E+10 | 0.00 | 0.00 | 0.00 | 0.210472E+12 | 0.00 | 0.00 | 0.00 |
March | 0.113227E+12 | 0.00 | 0.213143E+11 | 0.00 | 0.717415E+10 | 0.00 | 0.00 | 0.00 | 0.267711E+12 | 0.00 | 0.00 | 0.00 |
April | 0.109574E+12 | 0.00 | 0.639265E+11 | 0.00 | 0.173662E+11 | 0.00 | 0.00 | 0.00 | 0.252187E+12 | 0.00 | 0.00 | 0.00 |
May | 0.113227E+12 | 0.00 | 0.393702E+11 | 0.00 | 0.118384E+11 | 0.00 | 0.00 | 0.00 | 0.103788E+12 | 0.00 | 0.00 | 0.00 |
June | 0.109574E+12 | 0.00 | 0.215359E+12 | 0.00 | 0.526306E+11 | 0.00 | 0.00 | 0.00 | 0.455499E+11 | 0.00 | 0.00 | 0.00 |
July | 0.113227E+12 | 0.00 | 0.645954E+12 | 0.00 | 0.144215E+12 | 0.00 | 0.00 | 0.00 | 0.772453E+09 | 0.00 | 0.00 | 0.00 |
August | 0.113227E+12 | 0.00 | 0.787778E+12 | 0.00 | 0.169461E+12 | 0.00 | 0.00 | 0.00 | 0.161546E+10 | 0.00 | 0.00 | 0.00 |
September | 0.109574E+12 | 0.00 | 0.965217E+10 | 0.00 | 0.446611E+10 | 0.00 | 0.00 | 0.00 | 0.422008E+11 | 0.00 | 0.00 | 0.00 |
October | 0.113227E+12 | 0.00 | 0.156336E+11 | 0.00 | 0.573565E+10 | 0.00 | 0.00 | 0.00 | 0.171296E+12 | 0.00 | 0.00 | 0.00 |
November | 0.109574E+12 | 0.00 | 0.207485E+11 | 0.00 | 0.698107E+10 | 0.00 | 0.00 | 0.00 | 0.241819E+12 | 0.00 | 0.00 | 0.00 |
December | 0.113227E+12 | 0.00 | 0.223450E+11 | 0.00 | 0.763567E+10 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.133316E+13 | 0.00 | 0.186903E+13 | 0.00 | 0.437710E+12 | 0.00 | 0.00 | 0.00 | 0.173040E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.102269E+12 | 0.00 | 0.965217E+10 | 0.00 | 0.446611E+10 | 0.00 | 0.00 | 0.00 | 0.772453E+09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.113227E+12 | 0.00 | 0.787778E+12 | 0.00 | 0.169461E+12 | 0.00 | 0.00 | 0.00 | 0.267840E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.159629E+10 | 0.00 | 0.284477E+10 | 0.00 | 0.656608E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.144181E+10 | 0.00 | 0.970489E+10 | 0.00 | 0.204077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159629E+10 | 0.00 | 0.181355E+11 | 0.00 | 0.359693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154479E+10 | 0.00 | 0.248773E+11 | 0.00 | 0.471497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159629E+10 | 0.00 | 0.789792E+10 | 0.00 | 0.163554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154479E+10 | 0.00 | 0.141753E+11 | 0.00 | 0.289669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.159629E+10 | 0.00 | 0.214092E+11 | 0.00 | 0.439603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.159629E+10 | 0.00 | 0.272225E+11 | 0.00 | 0.530147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.154479E+10 | 0.00 | 0.731594E+10 | 0.00 | 0.146087E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.159629E+10 | 0.00 | 0.130946E+11 | 0.00 | 0.254041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.154479E+10 | 0.00 | 0.180102E+11 | 0.00 | 0.352332E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159629E+10 | 0.00 | 0.231123E+11 | 0.00 | 0.454215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187950E+11 | 0.00 | 0.187800E+12 | 0.00 | 0.373058E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.144181E+10 | 0.00 | 0.284477E+10 | 0.00 | 0.656608E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.159629E+10 | 0.00 | 0.272225E+11 | 0.00 | 0.530147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.153779E+11 | 0.00 | 0.308851E+10 | 0.00 | 0.776089E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.138897E+11 | 0.00 | 0.638220E+11 | 0.00 | 0.137928E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153779E+11 | 0.00 | 0.148273E+12 | 0.00 | 0.298553E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.148818E+11 | 0.00 | 0.220110E+12 | 0.00 | 0.421360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.153779E+11 | 0.00 | 0.667181E+11 | 0.00 | 0.139513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.148818E+11 | 0.00 | 0.129260E+12 | 0.00 | 0.265620E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153779E+11 | 0.00 | 0.199433E+12 | 0.00 | 0.410977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153779E+11 | 0.00 | 0.253324E+12 | 0.00 | 0.495477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.148818E+11 | 0.00 | 0.578494E+11 | 0.00 | 0.117030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.153779E+11 | 0.00 | 0.102185E+12 | 0.00 | 0.201368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148818E+11 | 0.00 | 0.138700E+12 | 0.00 | 0.276729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153779E+11 | 0.00 | 0.180075E+12 | 0.00 | 0.361741E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.181062E+12 | 0.00 | 0.156284E+13 | 0.00 | 0.313406E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.138897E+11 | 0.00 | 0.308851E+10 | 0.00 | 0.776089E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153779E+11 | 0.00 | 0.253324E+12 | 0.00 | 0.495477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.155879E+10 | 0.00 | 0.109343E+09 | 0.00 | 26467462.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.140794E+10 | 0.00 | 0.420045E+10 | 0.00 | 0.921294E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155879E+10 | 0.00 | 0.126969E+11 | 0.00 | 0.258444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.150851E+10 | 0.00 | 0.205076E+11 | 0.00 | 0.395931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.155879E+10 | 0.00 | 0.613581E+10 | 0.00 | 0.129204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.150851E+10 | 0.00 | 0.126678E+11 | 0.00 | 0.261448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.155879E+10 | 0.00 | 0.198331E+11 | 0.00 | 0.409948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.155879E+10 | 0.00 | 0.251347E+11 | 0.00 | 0.493130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.150851E+10 | 0.00 | 0.500516E+10 | 0.00 | 0.102265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155879E+10 | 0.00 | 0.831185E+10 | 0.00 | 0.165870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150851E+10 | 0.00 | 0.114490E+11 | 0.00 | 0.231371E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.155879E+10 | 0.00 | 0.158341E+11 | 0.00 | 0.321712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.183535E+11 | 0.00 | 0.141886E+12 | 0.00 | 0.286410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.140794E+10 | 0.00 | 0.109343E+09 | 0.00 | 26467462.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.155879E+10 | 0.00 | 0.251347E+11 | 0.00 | 0.493130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 77774047.15 | 0.00 | 0.00 | 0.604745E+11 | 0.00 | 0.29 |
February | 0.00 | 0.00 | 0.00 | 0.100613E+09 | 0.00 | 0.00 | 0.554235E+11 | 0.00 | 0.32 |
March | 0.00 | 0.00 | 0.00 | 98817815.81 | 0.00 | 0.00 | 0.484726E+11 | 0.00 | 0.26 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 32592457.19 | 0.00 | 0.00 | 0.138011E+11 | 0.00 | 0.07 |
December | 0.00 | 0.00 | 0.00 | 0.101386E+09 | 0.00 | 0.00 | 0.589637E+11 | 0.00 | 0.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.411183E+09 | 0.00 | 0.00 | 0.237135E+12 | 0.00 | 0.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.101386E+09 | 0.00 | 0.00 | 0.604745E+11 | 0.00 | 0.32 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.186625E+11 | 0.00 | 0.00 | 34198398.71 | 0.00 | 0.00 | 0.254623E+11 | 0.00 | 0.29 |
February | 0.921762E+10 | 0.00 | 0.00 | 56565977.11 | 0.00 | 0.00 | 0.329607E+11 | 0.00 | 0.33 |
March | 0.377351E+10 | 0.00 | 0.00 | 0.104710E+09 | 0.00 | 0.00 | 0.570802E+11 | 0.00 | 0.44 |
April | 0.761675E+10 | 40704.72 | 0.00 | 0.162585E+09 | 3245092.50 | 0.00 | 0.878743E+11 | 0.00 | 0.94 |
May | 0.848829E+10 | 0.241128E+09 | 0.00 | 0.150517E+09 | 0.00 | 0.00 | 0.673338E+11 | 0.00 | 1.27 |
June | 0.725073E+10 | 0.692455E+10 | 0.00 | 0.127633E+09 | 0.651970E+09 | 0.00 | 0.433255E+11 | 0.00 | 1.51 |
July | 0.897995E+10 | 0.107430E+11 | 0.00 | 0.106638E+09 | 0.212306E+10 | 0.00 | 0.296729E+11 | 0.00 | 1.40 |
August | 0.110508E+11 | 0.873107E+10 | 0.00 | 0.144833E+09 | 71841952.91 | 0.00 | 0.475227E+11 | 0.00 | 1.71 |
September | 0.894432E+10 | 0.345724E+09 | 0.00 | 0.148510E+09 | 0.00 | 0.00 | 0.771127E+11 | 0.00 | 1.33 |
October | 0.746153E+10 | 0.00 | 0.00 | 0.156113E+09 | 0.00 | 0.00 | 0.869524E+11 | 0.00 | 0.89 |
November | 0.304467E+10 | 0.00 | 0.00 | 0.139426E+09 | 0.00 | 0.00 | 0.757983E+11 | 0.00 | 0.63 |
December | 0.559464E+10 | 0.00 | 0.00 | 65345486.25 | 0.00 | 0.00 | 0.438826E+11 | 0.00 | 0.33 |
Annual Sum or Average | 0.100085E+12 | 0.269855E+11 | 0.00 | 0.139708E+10 | 0.285012E+10 | 0.00 | 0.674979E+12 | 0.00 | 0.93 |
Minimum of Months | 0.304467E+10 | 0.00 | 0.00 | 34198398.71 | 0.00 | 0.00 | 0.254623E+11 | 0.00 | 0.29 |
Maximum of Months | 0.186625E+11 | 0.107430E+11 | 0.00 | 0.162585E+09 | 0.212306E+10 | 0.00 | 0.878743E+11 | 0.00 | 1.71 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.350511E+12 | 0.00 | 0.00 | 2973692.98 | 0.00 | 0.128260E+11 | 0.430696E+10 | 0.00 | 0.27 |
February | 0.261548E+12 | 0.00 | 0.00 | 28644871.99 | 0.00 | 0.127256E+10 | 0.291613E+11 | 0.00 | 0.28 |
March | 0.209679E+12 | 0.00 | 0.00 | 0.171659E+09 | 0.00 | 0.390070E+09 | 0.131809E+12 | 0.00 | 0.31 |
April | 0.976694E+11 | 0.00 | 0.00 | 0.398189E+09 | 0.974789E+09 | 0.00 | 0.280810E+12 | 0.00 | 0.43 |
May | 0.464830E+11 | 0.960575E+09 | 0.00 | 0.659348E+09 | 0.00 | 0.00 | 0.334146E+12 | 0.00 | 0.68 |
June | 0.214389E+11 | 0.330005E+11 | 0.00 | 0.590185E+09 | 0.430316E+10 | 0.00 | 0.226428E+12 | 0.00 | 0.82 |
July | 0.250200E+11 | 0.500697E+11 | 0.00 | 0.480263E+09 | 0.862295E+10 | 0.00 | 0.150854E+12 | 0.00 | 0.73 |
August | 0.303141E+11 | 0.279407E+11 | 0.00 | 0.572598E+09 | 0.526065E+09 | 0.00 | 0.238320E+12 | 0.00 | 0.85 |
September | 0.539421E+11 | 0.943922E+09 | 0.00 | 0.555145E+09 | 0.00 | 0.00 | 0.348673E+12 | 0.00 | 0.66 |
October | 0.114663E+12 | 0.00 | 0.00 | 0.352412E+09 | 0.00 | 0.00 | 0.251644E+12 | 0.00 | 0.39 |
November | 0.171837E+12 | 0.00 | 0.00 | 0.135851E+09 | 0.00 | 0.112355E+10 | 0.114160E+12 | 0.00 | 0.30 |
December | 0.311177E+12 | 0.00 | 0.00 | 6409908.33 | 0.00 | 0.891643E+10 | 0.771825E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.169428E+13 | 0.112915E+12 | 0.00 | 0.395368E+10 | 0.144270E+11 | 0.245286E+11 | 0.211803E+13 | 0.00 | 0.50 |
Minimum of Months | 0.214389E+11 | 0.00 | 0.00 | 2973692.98 | 0.00 | 0.00 | 0.430696E+10 | 0.00 | 0.27 |
Maximum of Months | 0.350511E+12 | 0.500697E+11 | 0.00 | 0.659348E+09 | 0.862295E+10 | 0.128260E+11 | 0.348673E+12 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.216235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.851744E+10 | 0.00 | 0.00 | 0.25 |
February | 0.184417E+11 | 0.00 | 0.00 | 55081.64 | 0.00 | 0.427221E+10 | 0.181972E+09 | 0.00 | 0.26 |
March | 0.223021E+11 | 0.00 | 0.00 | 1841414.43 | 0.00 | 0.175156E+10 | 0.242072E+10 | 0.00 | 0.29 |
April | 0.155213E+11 | 0.00 | 0.00 | 16409710.49 | 99713786.71 | 0.294096E+09 | 0.144312E+11 | 0.00 | 0.38 |
May | 0.855937E+10 | 97725804.74 | 0.00 | 50278877.51 | 0.00 | 1692873.59 | 0.249557E+11 | 0.00 | 0.65 |
June | 0.369307E+10 | 0.334060E+10 | 0.00 | 49272312.82 | 0.581799E+09 | 0.00 | 0.198002E+11 | 0.00 | 0.82 |
July | 0.311265E+10 | 0.525295E+10 | 0.00 | 40888004.16 | 0.104652E+10 | 0.00 | 0.135186E+11 | 0.00 | 0.75 |
August | 0.439104E+10 | 0.300619E+10 | 0.00 | 46726498.33 | 33158639.51 | 0.00 | 0.197513E+11 | 0.00 | 0.83 |
September | 0.104363E+11 | 72999770.75 | 0.00 | 33232413.65 | 0.00 | 0.00 | 0.227691E+11 | 0.00 | 0.58 |
October | 0.190203E+11 | 0.00 | 0.00 | 8701736.54 | 0.00 | 0.309966E+09 | 0.807226E+10 | 0.00 | 0.34 |
November | 0.189081E+11 | 0.00 | 0.00 | 890785.89 | 28537.87 | 0.163007E+10 | 0.132288E+10 | 0.00 | 0.28 |
December | 0.171018E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.774289E+10 | 0.00 | 0.00 | 0.25 |
Annual Sum or Average | 0.163111E+12 | 0.117705E+11 | 0.00 | 0.248297E+09 | 0.176122E+10 | 0.245199E+11 | 0.127224E+12 | 0.00 | 0.47 |
Minimum of Months | 0.311265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.223021E+11 | 0.525295E+10 | 0.00 | 50278877.51 | 0.104652E+10 | 0.851744E+10 | 0.249557E+11 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.128721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376300E+10 | 0.00 | 0.00 | 0.26 |
February | 0.250498E+10 | 0.00 | 0.00 | 55832.33 | 0.00 | 0.146757E+10 | 70529071.53 | 0.00 | 0.25 |
March | 0.348357E+10 | 0.00 | 0.00 | 1557333.91 | 0.00 | 0.321463E+09 | 0.127899E+10 | 0.00 | 0.30 |
April | 0.194771E+10 | 77518.65 | 0.00 | 9550015.92 | 365216.94 | 0.00 | 0.653918E+10 | 0.00 | 0.72 |
May | 0.123456E+10 | 42841624.62 | 0.00 | 16988566.48 | 0.00 | 0.00 | 0.799492E+10 | 0.00 | 1.35 |
June | 0.983557E+09 | 0.125542E+10 | 0.00 | 16404468.21 | 39203024.76 | 0.00 | 0.601002E+10 | 0.00 | 1.80 |
July | 0.119223E+10 | 0.188635E+10 | 0.00 | 14624032.64 | 0.176680E+09 | 0.00 | 0.410178E+10 | 0.00 | 1.66 |
August | 0.161177E+10 | 0.135593E+10 | 0.00 | 16886423.74 | 6687318.55 | 0.00 | 0.541969E+10 | 0.00 | 1.82 |
September | 0.143928E+10 | 51619556.88 | 0.00 | 12781231.72 | 4045.41 | 0.00 | 0.756809E+10 | 0.00 | 1.19 |
October | 0.184882E+10 | 0.00 | 0.00 | 8077843.68 | 0.00 | 0.00 | 0.582674E+10 | 0.00 | 0.60 |
November | 0.263821E+10 | 0.00 | 0.00 | 3201547.45 | 0.00 | 35842355.00 | 0.262695E+10 | 0.00 | 0.35 |
December | 0.246556E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198330E+10 | 0.00 | 0.00 | 0.24 |
Annual Sum or Average | 0.226374E+11 | 0.459223E+10 | 0.00 | 0.100127E+09 | 0.222939E+09 | 0.757118E+10 | 0.474369E+11 | 0.00 | 0.88 |
Minimum of Months | 0.983557E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.348357E+10 | 0.188635E+10 | 0.00 | 16988566.48 | 0.176680E+09 | 0.376300E+10 | 0.799492E+10 | 0.00 | 1.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.252226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368860E+10 | 0.00 | 0.00 | 0.49 |
February | 0.326798E+10 | 0.00 | 0.00 | 683366.62 | 0.00 | 0.144590E+10 | 0.411815E+09 | 0.00 | 0.50 |
March | 0.401442E+10 | 0.00 | 0.00 | 4302790.22 | 0.00 | 0.450438E+09 | 0.232360E+10 | 0.00 | 0.61 |
April | 0.282975E+10 | 8943.96 | 0.00 | 13183392.31 | 508498.96 | 0.00 | 0.782673E+10 | 0.00 | 1.33 |
May | 0.156981E+10 | 32616609.64 | 0.00 | 19122741.17 | 0.00 | 0.00 | 0.821894E+10 | 0.00 | 2.10 |
June | 0.128943E+10 | 0.988817E+09 | 0.00 | 17182669.71 | 63825556.31 | 0.00 | 0.628498E+10 | 0.00 | 2.72 |
July | 0.169317E+10 | 0.177521E+10 | 0.00 | 12345505.17 | 0.266072E+09 | 0.00 | 0.400651E+10 | 0.00 | 2.63 |
August | 0.214386E+10 | 0.107090E+10 | 0.00 | 16818419.93 | 11440016.27 | 0.00 | 0.465033E+10 | 0.00 | 2.55 |
September | 0.212903E+10 | 52935048.32 | 0.00 | 13044392.51 | 5058.85 | 0.00 | 0.717825E+10 | 0.00 | 1.86 |
October | 0.322614E+10 | 0.00 | 0.00 | 6430981.07 | 0.00 | 0.00 | 0.442593E+10 | 0.00 | 0.92 |
November | 0.393945E+10 | 0.00 | 0.00 | 2035051.22 | 0.00 | 0.145355E+09 | 0.181420E+10 | 0.00 | 0.57 |
December | 0.316048E+10 | 0.00 | 0.00 | 26516.05 | 0.00 | 0.237166E+10 | 27216971.05 | 0.00 | 0.46 |
Annual Sum or Average | 0.317858E+11 | 0.392048E+10 | 0.00 | 0.105176E+09 | 0.341851E+09 | 0.810196E+10 | 0.471685E+11 | 0.00 | 1.40 |
Minimum of Months | 0.128943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.401442E+10 | 0.177521E+10 | 0.00 | 19122741.17 | 0.266072E+09 | 0.368860E+10 | 0.821894E+10 | 0.00 | 2.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.261449E+10 | 0.00 | 0.00 | 5063814.80 | 0.00 | 0.337645E+10 | 0.352026E+10 | 0.00 | 0.48 |
February | 0.260691E+10 | 0.00 | 0.00 | 11184345.92 | 0.00 | 0.151715E+10 | 0.544259E+10 | 0.00 | 0.60 |
March | 0.377381E+10 | 0.00 | 0.00 | 16216839.11 | 0.00 | 0.547840E+09 | 0.756108E+10 | 0.00 | 0.69 |
April | 0.343930E+10 | 1322839.30 | 0.00 | 19948606.16 | 53354.92 | 538627.53 | 0.120898E+11 | 0.00 | 1.40 |
May | 0.237049E+10 | 52630386.19 | 0.00 | 22685517.83 | 0.00 | 0.00 | 0.954958E+10 | 0.00 | 1.79 |
June | 0.171119E+10 | 0.131411E+10 | 0.00 | 16937324.43 | 97501899.45 | 0.00 | 0.585892E+10 | 0.00 | 2.05 |
July | 0.204403E+10 | 0.218496E+10 | 0.00 | 15255534.34 | 0.344498E+09 | 0.00 | 0.407961E+10 | 0.00 | 1.98 |
August | 0.253813E+10 | 0.184673E+10 | 0.00 | 25234780.76 | 9716455.04 | 0.00 | 0.610480E+10 | 0.00 | 2.38 |
September | 0.250622E+10 | 0.120710E+09 | 0.00 | 27076322.73 | 6093.28 | 0.00 | 0.113507E+11 | 0.00 | 1.98 |
October | 0.362926E+10 | 0.00 | 0.00 | 18881777.38 | 0.00 | 20202217.69 | 0.915947E+10 | 0.00 | 1.13 |
November | 0.380939E+10 | 0.00 | 0.00 | 8833664.89 | 0.00 | 0.221491E+09 | 0.606901E+10 | 0.00 | 0.63 |
December | 0.355130E+10 | 0.00 | 0.00 | 3611726.65 | 0.00 | 0.229012E+10 | 0.206740E+10 | 0.00 | 0.42 |
Annual Sum or Average | 0.345945E+11 | 0.552047E+10 | 0.00 | 0.190930E+09 | 0.451775E+09 | 0.797379E+10 | 0.828533E+11 | 0.00 | 1.30 |
Minimum of Months | 0.171119E+10 | 0.00 | 0.00 | 3611726.65 | 0.00 | 0.00 | 0.206740E+10 | 0.00 | 0.42 |
Maximum of Months | 0.380939E+10 | 0.218496E+10 | 0.00 | 27076322.73 | 0.344498E+09 | 0.337645E+10 | 0.120898E+11 | 0.00 | 2.38 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.354911E+10 | 0.00 | 0.00 | 357558.65 | 0.00 | 0.359709E+10 | 0.266223E+09 | 0.00 | 0.59 |
February | 0.437993E+10 | 0.00 | 0.00 | 2250223.38 | 0.00 | 0.592113E+09 | 0.149377E+10 | 0.00 | 0.63 |
March | 0.400207E+10 | 0.00 | 0.00 | 8624068.45 | 0.00 | 4106418.28 | 0.489572E+10 | 0.00 | 0.82 |
April | 0.215521E+10 | 2091548.78 | 0.00 | 17892880.47 | 0.00 | 0.00 | 0.104626E+11 | 0.00 | 1.73 |
May | 0.218111E+10 | 35831146.39 | 0.00 | 20469335.24 | 0.00 | 0.00 | 0.740122E+10 | 0.00 | 2.19 |
June | 0.153569E+10 | 0.107258E+10 | 0.00 | 15667061.23 | 84668049.84 | 0.00 | 0.511972E+10 | 0.00 | 2.74 |
July | 0.165931E+10 | 0.192920E+10 | 0.00 | 17708871.10 | 0.268264E+09 | 0.00 | 0.399505E+10 | 0.00 | 2.78 |
August | 0.199035E+10 | 0.135418E+10 | 0.00 | 22617290.57 | 6551575.58 | 0.00 | 0.591092E+10 | 0.00 | 3.13 |
September | 0.297253E+10 | 48309284.37 | 0.00 | 12107588.20 | 0.00 | 0.00 | 0.630673E+10 | 0.00 | 1.94 |
October | 0.343337E+10 | 0.00 | 0.00 | 7188959.34 | 0.00 | 0.00 | 0.575159E+10 | 0.00 | 1.14 |
November | 0.388596E+10 | 0.00 | 0.00 | 3533584.44 | 0.00 | 1630481.05 | 0.338252E+10 | 0.00 | 0.72 |
December | 0.568658E+10 | 0.00 | 0.00 | 603186.91 | 0.00 | 0.202932E+09 | 0.748044E+09 | 0.00 | 0.55 |
Annual Sum or Average | 0.374312E+11 | 0.444220E+10 | 0.00 | 0.129021E+09 | 0.359483E+09 | 0.439787E+10 | 0.557341E+11 | 0.00 | 1.59 |
Minimum of Months | 0.153569E+10 | 0.00 | 0.00 | 357558.65 | 0.00 | 0.00 | 0.266223E+09 | 0.00 | 0.55 |
Maximum of Months | 0.568658E+10 | 0.192920E+10 | 0.00 | 22617290.57 | 0.268264E+09 | 0.359709E+10 | 0.104626E+11 | 0.00 | 3.13 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.121447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586757E+11 | 0.00 | 0.00 | 0.33 |
February | 0.578258E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358195E+11 | 0.00 | 0.00 | 0.29 |
March | 0.195609E+11 | 0.00 | 0.00 | 2352.67 | 0.00 | 0.226332E+11 | 0.111226E+09 | 0.00 | 0.30 |
April | 0.283144E+11 | 0.00 | 0.00 | 8951533.41 | 0.122309E+09 | 0.391100E+10 | 0.785792E+10 | 0.00 | 0.37 |
May | 0.134167E+11 | 0.201496E+09 | 0.00 | 78562481.33 | 0.00 | 18105789.51 | 0.350959E+11 | 0.00 | 0.77 |
June | 0.408498E+10 | 0.714813E+10 | 0.00 | 90194785.35 | 0.501131E+09 | 0.00 | 0.338572E+11 | 0.00 | 1.12 |
July | 0.452243E+10 | 0.100213E+11 | 0.00 | 71860415.36 | 0.104835E+10 | 0.00 | 0.228407E+11 | 0.00 | 1.01 |
August | 0.916055E+10 | 0.493970E+10 | 0.00 | 59253768.16 | 72455050.81 | 0.00 | 0.241607E+11 | 0.00 | 0.96 |
September | 0.213789E+11 | 0.155737E+09 | 0.00 | 35150804.15 | 0.00 | 0.00 | 0.219484E+11 | 0.00 | 0.60 |
October | 0.337024E+11 | 0.00 | 0.00 | 2152892.69 | 0.00 | 0.328343E+10 | 0.217680E+10 | 0.00 | 0.33 |
November | 0.178212E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175740E+11 | 0.00 | 0.00 | 0.29 |
December | 0.171858E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482059E+11 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.160678E+12 | 0.224664E+11 | 0.00 | 0.346129E+09 | 0.174425E+10 | 0.190121E+12 | 0.148049E+12 | 0.00 | 0.56 |
Minimum of Months | 0.121447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.337024E+11 | 0.100213E+11 | 0.00 | 90194785.35 | 0.104835E+10 | 0.586757E+11 | 0.350959E+11 | 0.00 | 1.12 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.675161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.572126E+11 | 0.00 | 0.00 | 0.58 |
February | 0.170691E+11 | 0.00 | 0.00 | 503129.32 | 0.00 | 0.329073E+11 | 0.344549E+09 | 0.00 | 0.58 |
March | 0.277210E+11 | 0.00 | 0.00 | 18733977.50 | 0.00 | 0.209388E+11 | 0.106213E+11 | 0.00 | 0.66 |
April | 0.273983E+11 | 5295030.05 | 0.00 | 70775685.50 | 0.161893E+09 | 0.370068E+10 | 0.409924E+11 | 0.00 | 1.02 |
May | 0.179069E+11 | 0.159002E+09 | 0.00 | 0.129414E+09 | 0.00 | 0.00 | 0.511263E+11 | 0.00 | 1.59 |
June | 0.715478E+10 | 0.672711E+10 | 0.00 | 0.134030E+09 | 0.519726E+09 | 0.00 | 0.494905E+11 | 0.00 | 2.18 |
July | 0.672806E+10 | 0.109912E+11 | 0.00 | 99371943.17 | 0.116276E+10 | 0.00 | 0.342632E+11 | 0.00 | 2.08 |
August | 0.165786E+11 | 0.466964E+10 | 0.00 | 0.115612E+09 | 0.387411E+09 | 0.00 | 0.294262E+11 | 0.00 | 1.89 |
September | 0.323465E+11 | 0.175089E+09 | 0.00 | 62403056.20 | 0.00 | 17864252.98 | 0.322342E+11 | 0.00 | 1.35 |
October | 0.441419E+11 | 0.00 | 0.00 | 11019997.19 | 0.00 | 0.462141E+10 | 0.642407E+10 | 0.00 | 0.73 |
November | 0.256702E+11 | 0.00 | 0.00 | 410808.10 | 0.00 | 0.211244E+11 | 0.468230E+09 | 0.00 | 0.61 |
December | 0.523106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516950E+11 | 0.00 | 0.00 | 0.58 |
Annual Sum or Average | 0.234698E+12 | 0.227273E+11 | 0.00 | 0.642275E+09 | 0.223179E+10 | 0.192218E+12 | 0.255391E+12 | 0.00 | 1.16 |
Minimum of Months | 0.523106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.58 |
Maximum of Months | 0.441419E+11 | 0.109912E+11 | 0.00 | 0.134030E+09 | 0.116276E+10 | 0.572126E+11 | 0.511263E+11 | 0.00 | 2.18 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.193241E+11 | 0.00 | 0.00 | 41544661.85 | 0.00 | 0.450803E+11 | 0.258874E+11 | 0.00 | 0.53 |
February | 0.192974E+11 | 0.00 | 0.00 | 0.100710E+09 | 0.00 | 0.245972E+11 | 0.414435E+11 | 0.00 | 0.65 |
March | 0.267078E+11 | 0.00 | 0.00 | 0.154481E+09 | 0.00 | 0.170206E+11 | 0.598218E+11 | 0.00 | 0.72 |
April | 0.287788E+11 | 0.505915E+09 | 0.00 | 0.127032E+09 | 6427652.88 | 0.323990E+10 | 0.802307E+11 | 0.00 | 1.12 |
May | 0.216108E+11 | 0.282480E+09 | 0.00 | 0.170611E+09 | 0.00 | 0.00 | 0.632874E+11 | 0.00 | 1.37 |
June | 0.127267E+11 | 0.878841E+10 | 0.00 | 0.116981E+09 | 0.729195E+09 | 0.00 | 0.383359E+11 | 0.00 | 1.55 |
July | 0.100901E+11 | 0.143492E+11 | 0.00 | 0.113762E+09 | 0.160020E+10 | 0.00 | 0.284401E+11 | 0.00 | 1.46 |
August | 0.158273E+11 | 0.883797E+10 | 0.00 | 0.171215E+09 | 72783962.17 | 0.00 | 0.391949E+11 | 0.00 | 1.72 |
September | 0.256428E+11 | 0.577071E+09 | 0.00 | 0.217514E+09 | 0.00 | 0.00 | 0.759778E+11 | 0.00 | 1.57 |
October | 0.384163E+11 | 0.00 | 0.00 | 0.138745E+09 | 0.00 | 0.308409E+10 | 0.514065E+11 | 0.00 | 0.92 |
November | 0.290520E+11 | 0.00 | 0.00 | 47822711.12 | 0.00 | 0.153781E+11 | 0.293566E+11 | 0.00 | 0.58 |
December | 0.160726E+11 | 0.00 | 0.00 | 22672561.90 | 0.00 | 0.450941E+11 | 0.109818E+11 | 0.00 | 0.48 |
Annual Sum or Average | 0.263547E+12 | 0.333410E+11 | 0.00 | 0.142309E+10 | 0.240860E+10 | 0.153494E+12 | 0.544364E+12 | 0.00 | 1.06 |
Minimum of Months | 0.100901E+11 | 0.00 | 0.00 | 22672561.90 | 0.00 | 0.00 | 0.109818E+11 | 0.00 | 0.48 |
Maximum of Months | 0.384163E+11 | 0.143492E+11 | 0.00 | 0.217514E+09 | 0.160020E+10 | 0.450941E+11 | 0.802307E+11 | 0.00 | 1.72 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.869456E+10 | 0.00 | 0.00 | 145723.80 | 0.00 | 0.576559E+11 | 0.383418E+09 | 0.00 | 0.61 |
February | 0.182030E+11 | 0.00 | 0.00 | 4629736.10 | 0.00 | 0.321626E+11 | 0.326536E+10 | 0.00 | 0.62 |
March | 0.325663E+11 | 0.00 | 0.00 | 29196497.85 | 0.00 | 0.185157E+11 | 0.143365E+11 | 0.00 | 0.73 |
April | 0.360567E+11 | 14575867.81 | 0.00 | 56935303.64 | 0.166873E+09 | 0.226070E+10 | 0.360490E+11 | 0.00 | 1.11 |
May | 0.203522E+11 | 0.233485E+09 | 0.00 | 0.164124E+09 | 0.00 | 5873808.71 | 0.478776E+11 | 0.00 | 1.70 |
June | 0.109424E+11 | 0.719800E+10 | 0.00 | 0.105927E+09 | 0.623168E+09 | 0.00 | 0.318455E+11 | 0.00 | 2.03 |
July | 0.769744E+10 | 0.118061E+11 | 0.00 | 0.120083E+09 | 0.115711E+10 | 0.00 | 0.242831E+11 | 0.00 | 1.89 |
August | 0.147196E+11 | 0.581089E+10 | 0.00 | 0.102449E+09 | 35352537.19 | 0.00 | 0.276209E+11 | 0.00 | 1.89 |
September | 0.331687E+11 | 0.177148E+09 | 0.00 | 66508700.22 | 0.00 | 0.00 | 0.308791E+11 | 0.00 | 1.42 |
October | 0.451908E+11 | 0.00 | 0.00 | 16998184.35 | 0.00 | 0.324954E+10 | 0.114863E+11 | 0.00 | 0.82 |
November | 0.314967E+11 | 0.00 | 0.00 | 1675446.19 | 0.00 | 0.167093E+11 | 0.151587E+10 | 0.00 | 0.64 |
December | 0.962449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497648E+11 | 0.00 | 0.00 | 0.61 |
Annual Sum or Average | 0.268713E+12 | 0.252402E+11 | 0.00 | 0.668672E+09 | 0.198251E+10 | 0.180324E+12 | 0.229543E+12 | 0.00 | 1.18 |
Minimum of Months | 0.769744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 |
Maximum of Months | 0.451908E+11 | 0.118061E+11 | 0.00 | 0.164124E+09 | 0.115711E+10 | 0.576559E+11 | 0.478776E+11 | 0.00 | 2.03 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 34434564.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.609040E+10 | 0.00 | 0.00 | 0.36 |
February | 0.292616E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361155E+10 | 0.00 | 0.00 | 0.32 |
March | 0.119680E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253499E+10 | 0.00 | 0.00 | 0.32 |
April | 0.245175E+10 | 0.00 | 0.00 | 562684.47 | 13043225.20 | 0.799545E+09 | 0.485542E+09 | 0.00 | 0.37 |
May | 0.167635E+10 | 19982174.96 | 0.00 | 6763462.38 | 0.00 | 47293126.56 | 0.281120E+10 | 0.00 | 0.76 |
June | 0.554746E+09 | 0.714132E+09 | 0.00 | 8130671.73 | 65780375.43 | 0.00 | 0.312007E+10 | 0.00 | 1.11 |
July | 0.494259E+09 | 0.105744E+10 | 0.00 | 6650709.52 | 0.133284E+09 | 0.00 | 0.215521E+10 | 0.00 | 1.03 |
August | 0.105596E+10 | 0.526912E+09 | 0.00 | 5342677.89 | 6345238.43 | 317587.64 | 0.208883E+10 | 0.00 | 0.95 |
September | 0.237933E+10 | 11865999.84 | 0.00 | 2269652.33 | 0.00 | 0.108753E+09 | 0.148118E+10 | 0.00 | 0.57 |
October | 0.248939E+10 | 0.00 | 0.00 | 60059.67 | 0.00 | 0.967844E+09 | 71065747.08 | 0.00 | 0.34 |
November | 0.933860E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210193E+10 | 0.00 | 7908.78 | 0.31 |
December | 37264667.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465221E+10 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.135968E+11 | 0.233033E+10 | 0.00 | 29779917.99 | 0.218453E+09 | 0.209148E+11 | 0.122131E+11 | 7908.78 | 0.57 |
Minimum of Months | 34434564.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.248939E+10 | 0.105744E+10 | 0.00 | 8130671.73 | 0.133284E+09 | 0.609040E+10 | 0.312007E+10 | 7908.78 | 1.11 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.177318E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503059E+10 | 0.00 | 0.00 | 0.53 |
February | 0.984167E+09 | 0.00 | 0.00 | 3595.30 | 0.00 | 0.291619E+10 | 8249796.41 | 0.00 | 0.54 |
March | 0.206868E+10 | 0.00 | 0.00 | 990565.09 | 0.00 | 0.199932E+10 | 0.478686E+09 | 0.00 | 0.61 |
April | 0.219726E+10 | 0.00 | 0.00 | 5438810.18 | 16681110.15 | 0.560501E+09 | 0.328639E+10 | 0.00 | 0.94 |
May | 0.185263E+10 | 15816715.19 | 0.00 | 11119093.60 | 0.00 | 28698047.48 | 0.446911E+10 | 0.00 | 1.57 |
June | 0.601579E+09 | 0.688046E+09 | 0.00 | 12523545.44 | 65502866.34 | 0.00 | 0.488179E+10 | 0.00 | 2.20 |
July | 0.573235E+09 | 0.115304E+10 | 0.00 | 9785850.54 | 0.144098E+09 | 0.00 | 0.343177E+10 | 0.00 | 2.14 |
August | 0.152523E+10 | 0.485883E+09 | 0.00 | 10609525.00 | 37788823.66 | 5145028.48 | 0.281826E+10 | 0.00 | 1.90 |
September | 0.294958E+10 | 11997494.73 | 0.00 | 5203063.26 | 0.00 | 0.119104E+09 | 0.276427E+10 | 0.00 | 1.29 |
October | 0.314048E+10 | 0.00 | 0.00 | 755635.44 | 0.00 | 0.994879E+09 | 0.458805E+09 | 0.00 | 0.70 |
November | 0.158860E+10 | 0.00 | 0.00 | 0.00 | 1762.88 | 0.208959E+10 | 0.00 | 7528.03 | 0.58 |
December | 0.154228E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411879E+10 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.178130E+11 | 0.235478E+10 | 0.00 | 56429683.86 | 0.264072E+09 | 0.178628E+11 | 0.225973E+11 | 7528.03 | 1.13 |
Minimum of Months | 0.154228E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.314048E+10 | 0.115304E+10 | 0.00 | 12523545.44 | 0.144098E+09 | 0.503059E+10 | 0.488179E+10 | 7528.03 | 2.20 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.139629E+10 | 0.00 | 0.00 | 2932918.34 | 0.00 | 0.427267E+10 | 0.165767E+10 | 0.00 | 0.48 |
February | 0.124362E+10 | 0.00 | 0.00 | 7137459.87 | 0.00 | 0.244186E+10 | 0.309948E+10 | 0.00 | 0.59 |
March | 0.179376E+10 | 0.00 | 0.00 | 10537363.83 | 0.00 | 0.187711E+10 | 0.456468E+10 | 0.00 | 0.66 |
April | 0.224028E+10 | 46856600.01 | 0.00 | 10319152.31 | 121864.25 | 0.708448E+09 | 0.727026E+10 | 0.00 | 1.07 |
May | 0.224653E+10 | 26277620.93 | 0.00 | 15201861.50 | 0.00 | 69933731.22 | 0.586017E+10 | 0.00 | 1.37 |
June | 0.136107E+10 | 0.874059E+09 | 0.00 | 11046576.40 | 99803866.86 | 0.00 | 0.387653E+10 | 0.00 | 1.58 |
July | 0.103614E+10 | 0.146509E+10 | 0.00 | 11100592.75 | 0.220231E+09 | 0.00 | 0.292563E+10 | 0.00 | 1.53 |
August | 0.173179E+10 | 0.942361E+09 | 0.00 | 16912640.82 | 9817725.71 | 491379.27 | 0.378243E+10 | 0.00 | 1.77 |
September | 0.270813E+10 | 42397722.55 | 0.00 | 18771525.93 | 0.00 | 0.119969E+09 | 0.681868E+10 | 0.00 | 1.52 |
October | 0.297999E+10 | 0.00 | 0.00 | 10675727.15 | 0.00 | 0.897181E+09 | 0.422218E+10 | 0.00 | 0.89 |
November | 0.195125E+10 | 0.00 | 0.00 | 3640408.06 | 2132.74 | 0.180278E+10 | 0.208435E+10 | 9107.41 | 0.56 |
December | 0.842373E+09 | 0.00 | 0.00 | 1415766.73 | 0.00 | 0.408683E+10 | 0.644329E+09 | 0.00 | 0.44 |
Annual Sum or Average | 0.215312E+11 | 0.339704E+10 | 0.00 | 0.119692E+09 | 0.329977E+09 | 0.162773E+11 | 0.468064E+11 | 9107.41 | 1.04 |
Minimum of Months | 0.842373E+09 | 0.00 | 0.00 | 1415766.73 | 0.00 | 0.00 | 0.644329E+09 | 0.00 | 0.44 |
Maximum of Months | 0.297999E+10 | 0.146509E+10 | 0.00 | 18771525.93 | 0.220231E+09 | 0.427267E+10 | 0.727026E+10 | 9107.41 | 1.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.500753E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510347E+10 | 0.00 | 0.00 | 0.57 |
February | 0.118685E+10 | 0.00 | 0.00 | 365645.07 | 0.00 | 0.285582E+10 | 0.247250E+09 | 0.00 | 0.60 |
March | 0.215654E+10 | 0.00 | 0.00 | 2025168.96 | 0.00 | 0.201201E+10 | 0.118261E+10 | 0.00 | 0.71 |
April | 0.296868E+10 | 2554650.90 | 0.00 | 5050800.34 | 16666393.53 | 0.530188E+09 | 0.337751E+10 | 0.00 | 1.10 |
May | 0.219993E+10 | 20831407.11 | 0.00 | 15199561.60 | 0.00 | 33126662.21 | 0.444434E+10 | 0.00 | 1.72 |
June | 0.113285E+10 | 0.714106E+09 | 0.00 | 10174758.69 | 78788366.58 | 0.00 | 0.322104E+10 | 0.00 | 2.08 |
July | 0.772365E+09 | 0.121003E+10 | 0.00 | 11385077.17 | 0.160739E+09 | 0.00 | 0.244327E+10 | 0.00 | 1.95 |
August | 0.167088E+10 | 0.632254E+09 | 0.00 | 10154354.68 | 13689320.33 | 0.00 | 0.251757E+10 | 0.00 | 1.95 |
September | 0.355687E+10 | 14214353.43 | 0.00 | 5857637.20 | 0.00 | 52519532.37 | 0.253658E+10 | 0.00 | 1.40 |
October | 0.358613E+10 | 0.00 | 0.00 | 1370551.55 | 0.00 | 0.760031E+09 | 0.885239E+09 | 0.00 | 0.81 |
November | 0.191673E+10 | 0.00 | 0.00 | 85790.68 | 1924.20 | 0.197189E+10 | 0.109830E+09 | 5177.14 | 0.63 |
December | 0.423747E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414837E+10 | 0.00 | 0.00 | 0.57 |
Annual Sum or Average | 0.220723E+11 | 0.259399E+10 | 0.00 | 61669345.95 | 0.269885E+09 | 0.174674E+11 | 0.209652E+11 | 5177.14 | 1.18 |
Minimum of Months | 0.423747E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 0.358613E+10 | 0.121003E+10 | 0.00 | 15199561.60 | 0.160739E+09 | 0.510347E+10 | 0.444434E+10 | 5177.14 | 2.08 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 14488804.34 | 0.00 | 0.00 | 2409650.56 | 0.00 | 0.00 | 0.112168E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 8383358.08 | 0.00 | 0.00 | 0.888336E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 16408494.40 | 0.00 | 0.00 | 0.888643E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 18418301.97 | 0.00 | 0.00 | 0.566026E+09 | 0.00 | 0.29 |
May | 0.00 | 4383923.39 | 0.00 | 4147071.21 | 0.00 | 0.00 | 0.328502E+09 | 0.00 | 0.29 |
June | 0.00 | 83812893.67 | 0.00 | 5570354.48 | 0.00 | 0.00 | 0.147328E+09 | 0.00 | 0.31 |
July | 0.00 | 0.117965E+09 | 0.00 | 5384609.24 | 0.00 | 0.00 | 56695046.97 | 0.00 | 0.28 |
August | 0.00 | 78128776.51 | 0.00 | 9903142.26 | 0.00 | 0.00 | 82682406.39 | 0.00 | 0.31 |
September | 0.00 | 1177894.83 | 0.00 | 3977393.10 | 0.00 | 0.00 | 0.351396E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 8463370.93 | 0.00 | 0.00 | 0.563635E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 12627312.74 | 0.00 | 0.00 | 0.695111E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 18017762.05 | 0.00 | 0.00 | 0.102027E+10 | 0.00 | 0.28 |
Annual Sum or Average | 14488804.34 | 0.285469E+09 | 0.00 | 0.113711E+09 | 0.00 | 0.00 | 0.671030E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2409650.56 | 0.00 | 0.00 | 56695046.97 | 0.00 | 0.28 |
Maximum of Months | 14488804.34 | 0.117965E+09 | 0.00 | 18418301.97 | 0.00 | 0.00 | 0.112168E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.672158E+10 | 0.00 | 0.00 | 5662742.69 | 0.00 | 0.00 | 0.442749E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 61546680.76 | 0.00 | 0.00 | 0.890581E+10 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 0.138179E+09 | 0.00 | 0.00 | 0.891280E+10 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 0.165211E+09 | 0.00 | 0.00 | 0.567861E+10 | 0.00 | 0.29 |
May | 0.00 | 42354160.66 | 0.00 | 34732831.30 | 0.00 | 0.00 | 0.329552E+10 | 0.00 | 0.29 |
June | 0.00 | 0.829434E+09 | 0.00 | 51166542.02 | 0.00 | 0.00 | 0.147949E+10 | 0.00 | 0.31 |
July | 0.00 | 0.117326E+10 | 0.00 | 50253761.97 | 0.00 | 0.00 | 0.571410E+09 | 0.00 | 0.28 |
August | 0.00 | 0.777519E+09 | 0.00 | 92495086.71 | 0.00 | 0.00 | 0.834067E+09 | 0.00 | 0.31 |
September | 0.00 | 9662470.11 | 0.00 | 30796612.76 | 0.00 | 0.00 | 0.353572E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 67987249.03 | 0.00 | 0.00 | 0.565212E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.101950E+09 | 0.00 | 0.00 | 0.697466E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.148758E+09 | 0.00 | 0.00 | 0.102339E+11 | 0.00 | 0.28 |
Annual Sum or Average | 0.672158E+10 | 0.283223E+10 | 0.00 | 0.948740E+09 | 0.00 | 0.00 | 0.605016E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 5662742.69 | 0.00 | 0.00 | 0.571410E+09 | 0.00 | 0.28 |
Maximum of Months | 0.672158E+10 | 0.117326E+10 | 0.00 | 0.165211E+09 | 0.00 | 0.00 | 0.102339E+11 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.915383E+09 | 0.00 | 0.00 | 260965.45 | 0.00 | 0.00 | 0.174605E+09 | 0.00 | 0.28 |
February | 363006.15 | 0.00 | 0.00 | 4941152.31 | 0.00 | 0.00 | 0.891343E+09 | 0.00 | 0.28 |
March | 0.00 | 0.00 | 0.00 | 12415707.25 | 0.00 | 0.00 | 0.892666E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 15687845.71 | 0.00 | 0.00 | 0.568710E+09 | 0.00 | 0.29 |
May | 2826614.87 | 4267334.65 | 0.00 | 3211813.23 | 0.00 | 0.00 | 0.327002E+09 | 0.00 | 0.29 |
June | 0.00 | 82851479.24 | 0.00 | 5048548.73 | 0.00 | 0.00 | 0.148222E+09 | 0.00 | 0.31 |
July | 0.00 | 0.117261E+09 | 0.00 | 4980091.95 | 0.00 | 0.00 | 57309651.87 | 0.00 | 0.28 |
August | 0.00 | 77633709.22 | 0.00 | 9147327.18 | 0.00 | 0.00 | 83705872.23 | 0.00 | 0.31 |
September | 0.00 | 963525.37 | 0.00 | 2637485.91 | 0.00 | 0.00 | 0.354911E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 5840167.41 | 0.00 | 0.00 | 0.566319E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 9128482.86 | 0.00 | 0.00 | 0.698624E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 13821107.51 | 0.00 | 0.00 | 0.102445E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.918572E+09 | 0.282977E+09 | 0.00 | 87120695.50 | 0.00 | 0.00 | 0.578787E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 260965.45 | 0.00 | 0.00 | 57309651.87 | 0.00 | 0.28 |
Maximum of Months | 0.915383E+09 | 0.117261E+09 | 0.00 | 15687845.71 | 0.00 | 0.00 | 0.102445E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.846580E+09 | 0.00 | 0.00 | 0.466602E+12 | 0.00 | 5.16 |
February | 0.00 | 0.00 | 0.00 | 0.140106E+10 | 0.00 | 0.00 | 0.735149E+12 | 0.00 | 10.21 |
March | 0.00 | 0.00 | 0.00 | 0.211094E+10 | 0.00 | 0.00 | 0.109361E+13 | 0.00 | 16.64 |
April | 0.00 | 0.00 | 0.00 | 0.277737E+10 | 0.00 | 0.00 | 0.126006E+13 | 0.00 | 31.10 |
May | 0.00 | 0.175700E+09 | 0.00 | 0.712177E+09 | 0.00 | 0.00 | 0.435860E+12 | 0.00 | 19.91 |
June | 0.00 | 0.176032E+11 | 0.00 | 0.131206E+10 | 0.00 | 0.00 | 0.485671E+12 | 0.00 | 35.74 |
July | 0.00 | 0.641088E+11 | 0.00 | 0.202236E+10 | 0.00 | 0.00 | 0.414089E+12 | 0.00 | 43.53 |
August | 0.00 | 0.373082E+11 | 0.00 | 0.313283E+10 | 0.00 | 0.00 | 0.516704E+12 | 0.00 | 48.64 |
September | 0.00 | 0.00 | 0.00 | 0.715930E+09 | 0.00 | 0.00 | 0.387754E+12 | 0.00 | 17.47 |
October | 0.00 | 0.00 | 0.00 | 0.130762E+10 | 0.00 | 0.00 | 0.765650E+12 | 0.00 | 18.69 |
November | 0.00 | 0.00 | 0.00 | 0.187226E+10 | 0.00 | 0.00 | 0.104706E+13 | 0.00 | 19.43 |
December | 0.00 | 0.00 | 0.00 | 0.352214E+10 | 0.00 | 0.00 | 0.133628E+13 | 0.00 | 16.86 |
Annual Sum or Average | 0.00 | 0.119196E+12 | 0.00 | 0.217333E+11 | 0.00 | 0.00 | 0.894449E+13 | 0.00 | 23.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.712177E+09 | 0.00 | 0.00 | 0.387754E+12 | 0.00 | 5.16 |
Maximum of Months | 0.00 | 0.641088E+11 | 0.00 | 0.352214E+10 | 0.00 | 0.00 | 0.133628E+13 | 0.00 | 48.64 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.281175E+12 | 0.237081E+11 | 0.00 | 0.243731E+13 | 0.246939E+12 |
February | 0.392124E+12 | 0.208776E+11 | 0.00 | 0.259471E+13 | 0.222913E+12 |
March | 0.558342E+12 | 0.147975E+11 | 0.00 | 0.328707E+13 | 0.290969E+12 |
April | 0.692925E+12 | 0.135492E+11 | 0.00 | 0.352880E+13 | 0.431441E+12 |
May | 0.796426E+12 | 0.674257E+10 | 0.00 | 0.275537E+13 | 0.695090E+12 |
June | 0.809068E+12 | 0.254867E+10 | 0.00 | 0.199927E+13 | 0.159741E+13 |
July | 0.832678E+12 | 0.116121E+10 | 0.00 | 0.148413E+13 | 0.250491E+13 |
August | 0.695253E+12 | 0.323336E+10 | 0.00 | 0.215776E+13 | 0.234258E+13 |
September | 0.508866E+12 | 0.625846E+10 | 0.00 | 0.267399E+13 | 0.375437E+12 |
October | 0.302892E+12 | 0.974850E+10 | 0.00 | 0.312438E+13 | 0.222935E+12 |
November | 0.165269E+12 | 0.168080E+11 | 0.00 | 0.306382E+13 | 0.278732E+12 |
December | 0.208693E+12 | 0.256215E+11 | 0.00 | 0.329548E+13 | 0.449109E+12 |
Annual Sum or Average | 0.624371E+13 | 0.145055E+12 | 0.00 | 0.324021E+14 | 0.965847E+13 |
Minimum of Months | 0.165269E+12 | 0.116121E+10 | 0.00 | 0.148413E+13 | 0.222913E+12 |
Maximum of Months | 0.832678E+12 | 0.256215E+11 | 0.00 | 0.352880E+13 | 0.250491E+13 |