Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2024-07-03 12:21:48
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 29011.75 | 626.33 | 626.33 |
Net Site Energy | 29011.75 | 626.33 | 626.33 |
Total Source Energy | 88916.01 | 1919.59 | 1919.59 |
Net Source Energy | 88916.01 | 1919.59 | 1919.59 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1423.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1481.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3220.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 353.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2566.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2449.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 344.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 531.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3453.74 |
Humidification | 1464.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 544.92 |
Heat Recovery | 39.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 459.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 27588.71 | 1423.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6278.83 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1423.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1481.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 3220.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 353.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5334.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 55.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 2505.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2449.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 344.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 531.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3453.74 |
Humidification | General | 1464.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 544.92 |
Heat Recovery | General | 39.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 459.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1423.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 1481.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 3220.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 353.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 14676.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 2566.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2449.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 344.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 531.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3453.74 |
Humidification | Unassigned | 1464.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 544.92 |
Heat Recovery | Unassigned | 39.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 459.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 77.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 145.36 | 30.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Other | 373.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 595.61 | 30.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 77.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 145.36 | 30.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Other | 373.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 595.61 | 30.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 27588.705 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 27588.705 | 100.00 |
Total On-Site and Utility Electric Sources | 27588.705 | 100.00 |
Total Electricity End Uses | 27588.705 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 112.12 | 6.49 |
Air to Air Heat Recovery for Heating | 1614.90 | 93.51 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 1727.02 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 6278.83 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 6278.83 | 100.00 |
Total Water End Uses | 6278.83 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 71.83 |
Time Setpoint Not Met During Occupied Cooling | 1093.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5937.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | CAV_BAS FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 CHILLER1 PUMP | COOLSYS1 CHILLER2 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 4635.80 | 1390.74 | 927.16 | 1390.74 | 927.16 |
Gross Window-Wall Ratio [%] | 38.05 | 38.05 | 38.05 | 38.05 | 38.05 |
Above Ground Window-Wall Ratio [%] | 40.00 | 40.00 | 40.00 | 40.00 | 40.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 8.6849 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.6849 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 115.90 | 115.90 | 8.6849 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 77.26 | 77.26 | 8.6849 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.9016 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 8.6849 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 8.7339 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 4635.80 | 4635.80 | 8.7339 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 8.6849 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 8.6849 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 8.6849 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 8.6849 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 8.6849 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 8.6849 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 8.6849 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 13.9016 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 8.6849 | 18.58 | 484.4232 | |
Total | 46320.38 | 8.7339 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 8.7339 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.6845 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 15-AUG-14:39 | 02-JAN-05:10 | - | - | - | - | - | - | - | - | - | - | 04-AUG-12:50 |
Heating | 0.00 | 1657705.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 535338.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 280450.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 778371.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 233151.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 217976.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 50798.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 88748.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 25538.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2210375.60 | 1657705.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1657705.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 535338.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 280450.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3430.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 112.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 217976.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 50798.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 88748.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 25538.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1542.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 4693.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 10198.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1118.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 46480.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 8128.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7758.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1091.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1684.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 4639.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 123.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 1456.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 87373.43 | 1542.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 33.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 101.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 220.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 24.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 167.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 23.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 36.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 100.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 2.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 31.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1886.28 | 33.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 33.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 101.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 220.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 24.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1003.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 175.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 167.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 23.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 36.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 100.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 2.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 31.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1886.28 | 33.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
AirTerminal:SingleDuct:VAV:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | |
BASEMENT PSZ-VAV DIFFUSER | 5.65 | 0.375163 | 0.000000 | 0.000000 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.97 | 0.318832 | 0.326000 | 1.94 | 0.850219 | 0.500000 | 0.001195 | 0.000192 | 1.94 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 56.16 | 0.338671 | 0.339000 | 19.04 | 0.903123 | 0.500000 | 0.001125 | 0.004099 | 19.04 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.57 | 0.341492 | 0.350000 | 1.95 | 0.910646 | 0.500000 | 0.001116 | 0.000813 | 2.84 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.989071 | 0.241459 | 0.247000 | 0.244301 | 0.643892 | 0.500000 | 0.001578 | 0.000143 | 0.501074 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.32 | 0.116511 | 0.200000 | 0.264189 | 0.310697 | 0.500000 | 0.003270 | 0.000098 | 0.341354 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.52 | 0.157198 | 0.200000 | 0.303853 | 0.419196 | 0.500000 | 0.002424 | 0.000158 | 0.553839 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.61 | 0.095794 | 0.200000 | 0.321325 | 0.300000 | 0.500000 | 0.003977 | 0.000081 | 0.321325 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 9.23 | 0.258639 | 0.259000 | 2.39 | 0.689703 | 0.500000 | 0.001473 | 0.002145 | 7.50 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 14.05 | 0.109503 | 0.200000 | 2.81 | 0.300000 | 0.500000 | 0.003479 | 0.001404 | 4.91 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 15.05 | 0.158702 | 0.200000 | 3.01 | 0.423205 | 0.500000 | 0.002401 | 0.002145 | 7.50 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 14.73 | 0.104455 | 0.200000 | 2.95 | 0.300000 | 0.500000 | 0.003647 | 0.001366 | 4.78 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.04 | 0.229385 | 0.235000 | 0.244666 | 0.611695 | 0.500000 | 0.001661 | 0.000273 | 0.954350 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.42 | 0.108697 | 0.200000 | 0.283181 | 0.300000 | 0.500000 | 0.003505 | 0.000178 | 0.622346 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.61 | 0.147903 | 0.200000 | 0.322949 | 0.394409 | 0.500000 | 0.002576 | 0.000273 | 0.954358 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.55 | 0.099252 | 0.200000 | 0.310130 | 0.300000 | 0.500000 | 0.003839 | 0.000176 | 0.615085 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | User-Specified Rated Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 21994.33 | 0.000192 | 450.12 | |
CORE_MID VAV BOX REHEAT COIL | 468493.17 | 0.004099 | 11118.36 | |
CORE_TOP VAV BOX REHEAT COIL | 92937.35 | 0.000813 | 2453.24 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 16388.96 | 0.000143 | 432.36 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 11163.32 | 0.000098 | 294.48 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 18110.92 | 0.000158 | 477.74 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 9229.68 | 0.000081 | 230.74 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 245199.78 | 0.002145 | 6465.91 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 160502.02 | 0.001404 | 4232.37 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 245201.20 | 0.002145 | 6465.95 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 156085.60 | 0.001366 | 4115.99 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 31173.38 | 0.000273 | 821.90 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 20328.21 | 0.000178 | 535.96 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 31173.63 | 0.000273 | 821.91 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 20091.20 | 0.000176 | 529.71 | |
VAV_BOT WITH REHEAT HEATING COIL | 83057.43 | 0.000727 | 1312.56 | |
VAV_MID WITH REHEAT HEATING COIL | 849528.09 | 0.007432 | 13282.22 | |
VAV_TOP WITH REHEAT HEATING COIL | 82693.98 | 0.000723 | 1309.62 | |
CAV_BAS HEATING COIL | 289452.60 | 0.000875 | 2622.48 | 100000.00 |
Design Size Maximum Air Flow Rate [m3/s] | |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.502293 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.82 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.489618 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 25.15 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.70 | 3.08 | 11.40 | 3.08 | 9.86 | 9.86 | 0.300000 | 0.312099 | 9.86 |
VAV_MID WITH REHEAT | 54.62 | 30.20 | 109.23 | 36.88 | 92.11 | 92.11 | 0.300000 | 0.400383 | 92.11 |
VAV_TOP WITH REHEAT | 5.60 | 3.11 | 11.19 | 5.98 | 10.01 | 10.01 | 0.300000 | 0.598001 | 10.01 |
CAV_BAS | 0.000000 | 0.000000 | 5.65 | 1.20 | 5.65 | 5.65 | 1.00 | 0.212593 | 5.65 |
AIRLOOP DATACENTER BASEMENT | 25.15 | 25.15 | 25.15 | 25.15 | 25.15 | 25.15 | 1.00 | 0.999994 | 25.15 |
AIRLOOP DATACENTER BOT | 0.502293 | 0.502293 | 0.502293 | 0.502293 | 0.502293 | 0.502293 | 1.00 | 1.00 | 0.502293 |
AIRLOOP DATACENTER MID | 4.82 | 4.82 | 4.82 | 4.82 | 4.82 | 4.82 | 1.00 | 1.00 | 4.82 |
AIRLOOP DATACENTER TOP | 0.489618 | 0.489618 | 0.489618 | 0.489618 | 0.489618 | 0.489618 | 1.00 | 1.00 | 0.489618 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.86 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 92.11 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 10.01 | |
CAV_BAS_OA_CONTROLLER | 5.65 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 25.15 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.502293 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.82 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.489618 | 0.015632 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT OA HEAT RECOVERY | 2.54 |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 25.38 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.54 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 25.67 | 6.67 | 10.91 | 0.010052 | 0.008500 | 220222.50 | 0.006298 | 9.86 |
VAV_MID WITH REHEAT COOLING COIL | 25.83 | 6.67 | 10.90 | 0.010218 | 0.008500 | 2121429.11 | 0.060673 | 92.11 |
VAV_TOP WITH REHEAT COOLING COIL | 25.60 | 6.67 | 10.91 | 0.010022 | 0.008500 | 221698.89 | 0.006341 | 10.01 |
CAV_BAS COOLING COIL | 24.96 | 6.67 | 10.89 | 0.009995 | 0.008500 | 120419.14 | 0.003444 | 5.65 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.86 |
VAV_MID WITH REHEAT FAN | 92.11 |
VAV_TOP WITH REHEAT FAN | 10.01 |
CAV_BAS FAN | 5.65 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.006298 | 0.000076 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000727 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.060673 | 0.000008 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.007432 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.006341 | 0.000075 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000723 | |
CAV_BAS_COOLC_CONTROLLER | 0.003444 | 0.000138 |
CAV_BAS_HEATC_CONTROLLER | 0.000875 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 25.15 | 498220.02 | 350848.69 | 0.012201 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.502293 | 9841.86 | 6962.73 | 0.000241 |
AIRLOOP DATACENTER MID COOLING COIL | 4.82 | 94494.59 | 66803.56 | 0.002314 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.489618 | 9603.56 | 6790.26 | 0.000235 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 25.15 | 25.15 | 25.15 | 25.15 | 498220.02 | 498220.02 | 22473.72 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.502293 | 0.502293 | 0.502293 | 0.502293 | 9841.86 | 9841.86 | 1038.19 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.82 | 4.82 | 4.82 | 4.82 | 94494.59 | 94494.59 | 10381.93 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.489618 | 0.489618 | 0.489618 | 0.489618 | 9603.56 | 9603.56 | 1038.19 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 25.15 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.502293 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.82 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.489618 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 25.15 | 498220.02 | 0.012201 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.502293 | 9841.86 | 0.000241 |
AIRLOOP DATACENTER MID HEATING COIL | 4.82 | 94494.59 | 0.002314 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.489618 | 9603.56 | 0.000235 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 22473.72 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 1038.19 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 10381.93 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 1038.19 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000215 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.076755 | 12531.82 | |
HEATSYS1 PUMP | 0.023300 | 7016.99 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.076755 | 9.21 |
HEATSYS1 | 0.023300 | 2.80 |
COOLSYS1_SUPPLY | 0.076755 | 9.21 |
SINGLE WATER PLANT LOOP | 0.014992 | 1.80 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.076755 | 0.076755 | 322181.23 | 8.33 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2663352.26 | 2663352.26 | 0.023300 |
CENTRAL BOILER | 617531.98 | 605118.17 | 0.014992 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 CHILLER1 PUMP | 0.038378 | 4338.10 |
COOLSYS1 CHILLER2 PUMP | 0.038378 | 4338.10 |
PLANT CIRC PUMP | 0.014992 | 3823.65 |
SWHSYS1 PUMP | 0.000440 | 56.21 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Fluid Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.076755 | 0.038525 | 1347040.94 | 1347040.23 | 0.067830 |
COOLSYS1 CHILLER2 | 0.076755 | 0.038525 | 1347040.94 | 1347040.23 | 0.067830 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | U-factor Times Area Value at High Fan Speed [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/K] | |
CENTRAL TOWER | 0.014992 | 148857.05 | 75356.03 | 74428.53 | 7879.72 | 45213.62 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.135660 | 16.28 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.135660 | 33586.52 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 53.32 | 1612443.64 | 10.66 | 201555.45 |
TOWERWATERSYS COOLTOWER 2 | 53.32 | 1612443.64 | 10.66 | 201555.45 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.069852 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 76.91 | 115.90 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 52.57 | 77.26 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 84.71 | 115.90 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 56.47 | 77.26 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 8.685 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 13.527 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 8.685 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.755 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 13.902 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 229.201 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 8.685 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 493.108 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 24139.153 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 24139.153 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 21678.656 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21678.656 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2721.972 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2721.972 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2722.031 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2722.031 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1754.142 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1754.142 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 6806.209 | 8.685 | 161.356 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6806.209 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 503.275 | 13.902 | 258.275 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 503.275 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.065 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 0.9689 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 0.9235 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.155 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.3263 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8647 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9155 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6987 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.0649134 | 3.0649134 | 3.0649134 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | -0.61082983E-15 | 0.35276446E-16 | -0.14787207E-09 | 0.18036823E-17 |
51 | 8 | 0.21615122E-07 | 0.13022774E-12 | 0.37506347E-03 | -0.24577139E-09 |
52 | 7 | -0.12160115E-01 | 0.67804000E-08 | -0.22968555E-01 | 0.13826493E-03 |
53 | 6 | 0.40313748 | 0.23652218E-05 | 0.47020644 | -0.47216777E-02 |
54 | 5 | -5.1689687 | 0.88520675E-04 | -4.4267872 | 0.62916081E-01 |
55 | 4 | 32.907337 | 0.72566064E-03 | 21.383769 | -0.42085466 |
56 | 3 | -111.02301 | 0.15845227E-02 | -55.512186 | 1.5122587 |
57 | 2 | 196.92983 | 0.89280554E-03 | 77.772262 | -2.8975199 |
58 | 1 | -171.09018 | 0.95459611E-04 | -55.224854 | 2.7442846 |
59 | 0 | 57.057407 | 0.54436501E-06 | 15.563573 | |
60 | 9 | -0.28033836E-14 | 0.31423843E-16 | -0.15000593E-09 | 0.49342508E-16 |
61 | 8 | 0.21915022E-07 | 0.12441777E-12 | 0.37821899E-03 | -0.24918134E-09 |
62 | 7 | -0.12254290E-01 | 0.64567074E-08 | -0.23104155E-01 | 0.13933574E-03 |
63 | 6 | 0.40569641 | 0.22493722E-05 | 0.47238617 | -0.47518414E-02 |
64 | 5 | -5.1939411 | 0.84090406E-04 | -4.4435303 | 0.63225727E-01 |
65 | 4 | 33.017798 | 0.68864468E-03 | 21.449218 | -0.42232128 |
66 | 3 | -111.25804 | 0.15023393E-02 | -55.641580 | 1.5156542 |
67 | 2 | 197.16277 | 0.84581883E-03 | 77.890928 | -2.9012190 |
68 | 1 | -171.17623 | 0.90368420E-04 | -55.259345 | 2.7457926 |
69 | 0 | 57.057407 | 0.51494858E-06 | 15.557864 | |
70 | 9 | 0.16475985E-14 | 0.40698495E-16 | -0.13909959E-09 | -0.62647149E-17 |
71 | 8 | 0.20378875E-07 | 0.15355384E-12 | 0.36189576E-03 | -0.23171482E-09 |
72 | 7 | -0.11766586E-01 | 0.81065314E-08 | -0.22401745E-01 | 0.13379037E-03 |
73 | 6 | 0.39244372 | 0.28436739E-05 | 0.46108386 | -0.45956244E-02 |
74 | 5 | -5.0645996 | 0.10693990E-03 | -4.3566540 | 0.61621961E-01 |
75 | 4 | 32.445620 | 0.88045565E-03 | 21.109484 | -0.41472443 |
76 | 3 | -110.04047 | 0.19299305E-02 | -54.969854 | 1.4980638 |
77 | 2 | 195.95581 | 0.10911488E-02 | 77.275137 | -2.8820526 |
78 | 1 | -170.73031 | 0.11703553E-03 | -55.080813 | 2.7379774 |
79 | 0 | 57.057407 | 0.66971377E-06 | 15.587784 | |
80 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
81 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
82 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
83 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
84 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
85 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
86 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
87 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
88 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
89 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
90 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
91 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
92 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
93 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
94 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
95 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
96 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
97 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
98 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
99 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
100 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
101 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
102 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
103 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
104 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
105 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
106 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
107 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
108 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
109 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
110 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
111 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
112 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
113 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
114 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
115 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
116 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
117 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
118 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
119 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
120 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
121 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
122 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
123 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
124 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
125 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
126 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
127 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.38_SHGC_EAST_0.38 | 35 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.381 | ||
2 | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 36 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.381 | ||
3 | WINDOW_U_0.38_SHGC_WEST_0.38 | 37 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.381 | ||
4 | WINDOW_U_0.38_SHGC_NORTH_0.38 | 38 | 1 | VerySmooth | 2.159 | 2.159 | 1.000 | 0.381 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.45900E-002 | 0.29373 | 0.49855 | 0.49855 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.45900E-002 | 0.29373 | 0.49855 | 0.49855 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.45900E-002 | 0.29373 | 0.49855 | 0.49855 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.45900E-002 | 0.29373 | 0.49855 | 0.49855 | 0.41800 | 0.13582 | 0.17513 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 13.342 | 0.7435 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 5 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.58 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 5 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.58 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.467E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.490E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 5.142E-002 | 1.641E-004 | 2.563E-004 | 0.215 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 3.428E-002 | 1.697E-004 | 2.563E-004 | 0.223 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 2.563E-004 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 7.615E-002 | 2.137E-005 | 1.973E-005 | 6.311E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
2 | Zone DATACENTER_BASEMENT_ZN_6 | 1.1500 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.0077E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.0099E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7433E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.7452E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7854E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7868E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6362E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6370E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.0579E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.2041E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7855E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.9121E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.8210E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9264E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6580E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7133E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1699 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.5774E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1930 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.7514E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1169 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7098E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7658E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.6576E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.0663E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.2474E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7945E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.9595E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.8283E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9547E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6585E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.7149E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.0075E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.0100E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 7.7431E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.7452E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.7853E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.7869E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 2.6361E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 2.6369E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.1911E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.5623E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.9836E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.4024E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.5010E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.6432E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.5073E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.5455E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 7.0401E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.4082E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.7164E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.1592E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.7000E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7813E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.9620E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.8561E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 6.0782E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 6.1871E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.8365E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.9160E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.4567E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 5.4885E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.5074E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.5461E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7962E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7984E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3737E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3755E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0917E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0931E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6363E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6371E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8460E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9728E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4149E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5166E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1258E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2016E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6585E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7150E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.5262E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3892E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4737E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8111E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1211E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.2143E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 4.7658E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6571E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.8437E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.9716E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4117E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.5112E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1201E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1838E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6580E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7133E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.7961E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.7982E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.3736E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.3753E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0916E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0927E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6362E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.6370E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.3975E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.5110E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9768E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.0587E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9372E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.9663E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.5075E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.5462E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.8521E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.9321E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.2257E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.5605E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.7400E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3963E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9620E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.8561E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.4847E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.7563E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 5.0913E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.3824E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9785E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 5.1052E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.5072E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.5454E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1706 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1183 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1884 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1331 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1298 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 6.9574E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 5.8359E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.8866E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.3617E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.8965E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 8.0024E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.6031E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 7.9257E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 4.0845E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.9853E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.9197E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.6105E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 3.7365E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.4191E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.9474E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.0333E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.1997E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 5.8359E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.8862E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 7.0182E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 4.2402E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.3155E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.7761E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 6.8503E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.5738E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.9853E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.9197E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1707 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1185 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1885 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1334 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1300 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 6.9746E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 5.8484E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.8930E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.3678E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.9042E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 8.0094E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.6106E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 7.9379E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 4.0933E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.9978E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.9261E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.6109E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 3.7408E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.4198E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.9508E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.0397E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.2038E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 5.8484E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.8925E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 7.0222E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 4.2463E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.3199E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.7816E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 6.8608E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.5812E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.9978E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.9261E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 76438.78784 | 76438.78784 | 5.64534 | 5.64534 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:50:00 | -16.30000 | 9.24091E-004 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 80779.76162 | 80779.76162 | 5.96566 | 5.96566 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 2935.83766 | 2935.83766 | 0.12820 | 1.07782 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 760672.02682 | 760672.02682 | 56.16199 | 56.16199 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 281608.42557 | 281608.42557 | 12.18195 | 12.18195 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 75437.79785 | 75437.79785 | 5.56980 | 5.56980 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 65081.23701 | 65081.23701 | 2.83785 | 2.83785 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 13271.05345 | 13271.05345 | 0.98907 | 0.98907 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.30000 | 1.33670E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 11474.07146 | 11474.07146 | 0.50107 | 0.50107 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 17724.21778 | 17724.21778 | 1.32095 | 1.32095 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.18500 | 1.33579E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 7814.82677 | 7814.82677 | 0.34135 | 0.34135 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 20385.11826 | 20385.11826 | 1.51926 | 1.51926 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 29.99000 | 1.33664E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 12677.55026 | 12677.55026 | 0.55384 | 0.55384 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 21557.46568 | 21557.46568 | 1.60662 | 1.60662 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.84300 | 1.33644E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 6079.13535 | 6079.13535 | 0.26525 | 0.26525 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 123891.75071 | 123891.75071 | 9.23375 | 9.23375 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 30.30000 | 1.33670E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 171603.56045 | 171603.56045 | 7.50378 | 7.50378 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 188579.91238 | 188579.91238 | 14.05484 | 14.05484 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 25.71200 | 1.33588E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 112326.82718 | 112326.82718 | 4.91195 | 4.91195 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 201914.06095 | 201914.06095 | 15.04871 | 15.04871 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.06750 | 1.33665E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 171604.55249 | 171604.55249 | 7.50382 | 7.50382 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 197693.70607 | 197693.70607 | 14.73407 | 14.73407 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 28.68800 | 1.33641E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 109239.03586 | 109239.03586 | 4.77660 | 4.77660 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 13969.01346 | 13969.01346 | 1.04113 | 1.04113 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30000 | 1.33670E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 21813.21745 | 21813.21745 | 0.95435 | 0.95435 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 18997.61432 | 18997.61432 | 1.41591 | 1.41591 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 25.97550 | 1.33593E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 14224.41692 | 14224.41692 | 0.62235 | 0.62235 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 21665.38448 | 21665.38448 | 1.61474 | 1.61474 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 30.14500 | 1.33667E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 21813.39444 | 21813.39444 | 0.95436 | 0.95436 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 20805.53320 | 20805.53320 | 1.55065 | 1.55065 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.84300 | 1.33644E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 14058.68030 | 14058.68030 | 0.61508 | 0.61508 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8544.99625 | 8544.99625 | 0.50229 | 0.50229 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 26.50250 | 1.33602E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -16.30000 | 9.24091E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 81936.59253 | 81936.59253 | 4.81643 | 4.81643 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 26.50250 | 1.33602E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -16.30000 | 9.24091E-004 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8329.34354 | 8329.34354 | 0.48962 | 0.48962 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 26.50250 | 1.33602E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -16.30000 | 9.24091E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 372094.76296 | 427908.97740 | 21.87223 | 25.15306 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 21.83700 | 1.33520E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:30:00 | -16.30000 | 9.24091E-004 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 145429.30 | 9.86378 | 9.86378 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 87102.96 | 2.73935 | 2.73935 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:40:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1340646.99 | 92.10707 | 92.10707 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 868773.38 | 36.87810 | 36.87810 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 150873.47 | 10.00664 | 10.00664 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 86852.03 | 5.98399 | 5.98399 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:20:00 |
7 | CAV_BAS | Cooling | Sensible | 74609.62 | 5.64534 | 5.64534 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 79706.12 | 1.20016 | 1.20016 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 422116.76 | 25.15322 | 25.15322 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 22473.72 | 0.33839 | 0.33839 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8403.72 | 0.50229 | 0.50229 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 1038.19 | 1.56323E-002 | 1.56323E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 80578.14 | 4.81643 | 4.81643 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 10381.93 | 0.15632 | 0.15632 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8193.68 | 0.48962 | 0.48962 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 1038.19 | 1.56323E-002 | 1.56323E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Maximum Air Flow Rate [m3/s] | 5.64534 |
2 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Constant Minimum Air Flow Fraction | 0.37516 |
3 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | User-Specified Constant Minimum Air Flow Fraction | 0.00000 |
4 | AirTerminal:SingleDuct:VAV:NoReheat | BASEMENT PSZ-VAV DIFFUSER | Design Size Minimum Air Flow Rate [m3/s] | 0.00000 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.96566 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31883 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.32600 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.94480 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.85022 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.19499E-003 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.92416E-004 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.94480 |
14 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
16 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21994.32599 |
17 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.92416E-004 |
18 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 450.11869 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 56.16199 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33867 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33900 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 19.03891 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.90312 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.12499E-003 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.09858E-003 |
27 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 19.03891 |
28 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
29 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
30 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 468493.17308 |
31 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.09858E-003 |
32 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 11118.36087 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.56980 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34149 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.94943 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.91065 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.11569E-003 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.13056E-004 |
41 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.83785 |
42 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
43 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
44 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 92937.34668 |
45 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.13056E-004 |
46 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2453.24020 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.98907 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24146 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24700 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24430 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64389 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.57791E-003 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.43378E-004 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.50107 |
56 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
58 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16388.96010 |
59 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.43378E-004 |
60 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 432.36280 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.32095 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11651 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26419 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31070 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.27007E-003 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.76616E-005 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.34135 |
70 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
72 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11163.32463 |
73 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.76616E-005 |
74 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 294.48472 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.51926 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15720 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.30385 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41920 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.42369E-003 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.58442E-004 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.55384 |
84 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
86 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18110.91991 |
87 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.58442E-004 |
88 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 477.74374 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.60662 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.57941E-002 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.32132 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.97728E-003 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.07453E-005 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.32132 |
98 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
100 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9229.67869 |
101 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.07453E-005 |
102 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 230.73512 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.23375 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25864 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25900 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.39154 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68970 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.47310E-003 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.14511E-003 |
111 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.50378 |
112 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
113 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
114 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 245199.78365 |
115 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.14511E-003 |
116 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6465.90988 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.05484 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10950 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.81097 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.47935E-003 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.40414E-003 |
125 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.91195 |
126 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
127 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
128 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 160502.02454 |
129 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.40414E-003 |
130 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4232.37330 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 15.04871 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15870 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.00974 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42321 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.40073E-003 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.14513E-003 |
139 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 7.50382 |
140 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
141 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
142 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 245201.19833 |
143 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.14513E-003 |
144 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6465.94727 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.73407 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10446 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.94681 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.64750E-003 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.36550E-003 |
153 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.77660 |
154 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
155 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
156 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 156085.60191 |
157 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.36550E-003 |
158 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4115.99035 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.04113 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22939 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23500 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24467 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.61169 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.66096E-003 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.72718E-004 |
167 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.95435 |
168 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
169 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
170 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 31173.37717 |
171 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.72718E-004 |
172 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 821.89903 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.41591 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10870 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28318 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.50515E-003 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.77840E-004 |
181 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.62235 |
182 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
183 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
184 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20328.20587 |
185 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.77840E-004 |
186 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 535.95656 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.61474 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14790 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.32295 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39441 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.57601E-003 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.72721E-004 |
195 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.95436 |
196 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
197 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
198 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 31173.62992 |
199 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.72721E-004 |
200 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 821.90570 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.55065 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.92520E-002 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.31013 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.83871E-003 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.75767E-004 |
209 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.61508 |
210 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
211 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
212 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20091.20004 |
213 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.75767E-004 |
214 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 529.70994 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.50229 |
216 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.81643 |
217 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.48962 |
218 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 25.15306 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.70078 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.07847 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.40156 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.07847 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.86378 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.86378 |
225 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
226 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.31210 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 54.61667 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 30.19798 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 109.23335 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 36.87810 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 92.10707 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 92.10707 |
233 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
234 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.40038 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.59612 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.11036 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 11.19224 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 5.98399 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 10.00664 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 10.00664 |
241 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
242 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.59800 |
243 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.00000 |
244 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.00000 |
245 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.64534 |
246 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 1.20016 |
247 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.64534 |
248 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.64534 |
249 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
250 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 0.21259 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 25.15306 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 25.15306 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 25.15306 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 25.15306 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 25.15322 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 25.15322 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.50229 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.50229 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.50229 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.50229 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.50229 |
264 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.50229 |
265 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
266 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.81643 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.81643 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.81643 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.81643 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.81643 |
272 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.81643 |
273 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
274 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.48962 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.48962 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.48962 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.48962 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.48962 |
280 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.48962 |
281 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
282 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
283 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.86378 |
284 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 92.10707 |
285 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 10.00664 |
286 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.64534 |
287 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 25.15322 |
288 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.50229 |
289 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.81643 |
290 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.48962 |
291 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.86378 |
292 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_BOT WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.66810 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.90944 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.00519E-002 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
298 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 220222.50412 |
299 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.29834E-003 |
300 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.86378 |
301 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 83057.43395 |
302 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.26623E-004 |
303 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1312.56366 |
304 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.86378 |
305 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.29834E-003 |
306 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.56058E-005 |
307 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.26623E-004 |
308 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 92.10707 |
309 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 25.38195 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.83265 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.89991 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.02179E-002 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
315 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2121429.10746 |
316 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.06726E-002 |
317 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 92.10707 |
318 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 849528.09455 |
319 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.43204E-003 |
320 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 13282.21511 |
321 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 92.10707 |
322 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.06726E-002 |
323 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.84853E-006 |
324 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.43204E-003 |
325 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 10.00664 |
326 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.59907 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.90934 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.00224E-002 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
332 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 221698.89324 |
333 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.34056E-003 |
334 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 10.00664 |
335 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 82693.98176 |
336 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.23443E-004 |
337 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1309.62084 |
338 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 10.00664 |
339 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.34056E-003 |
340 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.51023E-005 |
341 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.23443E-004 |
342 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.64534 |
343 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.95901 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.88688 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 9.99483E-003 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
349 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 120419.14243 |
350 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.44397E-003 |
351 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.64534 |
352 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 289452.59992 |
353 | Coil:Heating:Water | CAV_BAS HEATING COIL | User-Specified Rated Capacity [W] | 100000.00000 |
354 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.74844E-004 |
355 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 2622.47617 |
356 | Fan:VariableVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.64534 |
357 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.44397E-003 |
358 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.38268E-004 |
359 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.74844E-004 |
360 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 25.15322 |
361 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
362 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 25.15322 |
363 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 498220.01974 |
364 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 350848.69292 |
365 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.22014E-002 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 25.15322 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 25.15322 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 25.15322 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 25.15322 |
370 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 498220.01974 |
371 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 498220.01974 |
372 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 22473.71574 |
373 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
374 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 25.15322 |
375 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 25.15322 |
376 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 498220.01974 |
377 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.22014E-002 |
378 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 22473.71574 |
379 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 2.15476E-004 |
380 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
381 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
382 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
383 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.50229 |
384 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
385 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.50229 |
386 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9841.85820 |
387 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6962.72783 |
388 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.41026E-004 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.50229 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.50229 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.50229 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.50229 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9841.85820 |
394 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9841.85820 |
395 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1038.19256 |
396 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
397 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.50229 |
398 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.50229 |
399 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9841.85820 |
400 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.41026E-004 |
401 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1038.19256 |
402 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.81643 |
403 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
404 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.81643 |
405 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 94494.59496 |
406 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 66803.56193 |
407 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.31417E-003 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.81643 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.81643 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.81643 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.81643 |
412 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 94494.59496 |
413 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 94494.59496 |
414 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 10381.92564 |
415 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
416 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.81643 |
417 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.81643 |
418 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 94494.59496 |
419 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.31417E-003 |
420 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 10381.92564 |
421 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.48962 |
422 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
423 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48962 |
424 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9603.56062 |
425 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6790.26333 |
426 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.35191E-004 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.48962 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.48962 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.48962 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.48962 |
431 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9603.56062 |
432 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9603.56062 |
433 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1038.19256 |
434 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
435 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.48962 |
436 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48962 |
437 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9603.56062 |
438 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.35191E-004 |
439 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1038.19256 |
440 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 7.67555E-002 |
441 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 12531.82322 |
442 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 7.67555E-002 |
443 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 9.21066 |
444 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 7.67555E-002 |
445 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 7.67555E-002 |
446 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 322181.23016 |
447 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 8.33000 |
448 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.33002E-002 |
449 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 2.79602 |
450 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.33002E-002 |
451 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 7016.98721 |
452 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
453 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2663352.26076 |
454 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 2663352.26000 |
455 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.33002E-002 |
456 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 7.67555E-002 |
457 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 9.21066 |
458 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Flow Rate [m3/s] | 3.83777E-002 |
459 | Pump:ConstantSpeed | COOLSYS1 CHILLER1 PUMP | Design Power Consumption [W] | 4338.10192 |
460 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Flow Rate [m3/s] | 3.83777E-002 |
461 | Pump:ConstantSpeed | COOLSYS1 CHILLER2 PUMP | Design Power Consumption [W] | 4338.10192 |
462 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 7.67555E-002 |
463 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.85252E-002 |
464 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1347040.94113 |
465 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1347040.22500 |
466 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 6.78302E-002 |
467 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 7.67555E-002 |
468 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.85252E-002 |
469 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1347040.94113 |
470 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1347040.22500 |
471 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Fluid Flow Rate [m3/s] | 6.78302E-002 |
472 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.49918E-002 |
473 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.79901 |
474 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.49918E-002 |
475 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3823.64845 |
476 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.49918E-002 |
477 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 148857.05341 |
478 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at High Fan Speed [W/K] | 75356.02839 |
479 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 74428.52670 |
480 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
481 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/K] | 45213.61704 |
482 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 617531.97954 |
483 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 605118.17000 |
484 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.49918E-002 |
485 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
486 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
487 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
488 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 56.20530 |
489 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
490 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.13566 |
491 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 16.27925 |
492 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.13566 |
493 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 33586.52056 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 53.31931 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1612443.63671 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 10.66386 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 201555.45459 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 53.31931 |
499 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1612443.63671 |
500 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 10.66386 |
501 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 201555.45459 |
502 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 6.98525E-002 |
503 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 6.98525E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 20853.84 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 443851.16 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 88070.68 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 15529.06 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 10577.48 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 17160.36 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 8741.82 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 232315.92 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 152068.15 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 232317.26 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 147884.31 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 29534.44 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 19259.42 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 29534.68 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 19034.89 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 58656.67 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 585772.30 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 58676.87 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 94838.35 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 252083.60 | 174349.98 | 77733.62 | 0.69 | 40990.16 | 415.74 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2386286.82 | 1641469.15 | 744817.67 | 0.69 | 384954.34 | 3904.42 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 254921.81 | 176543.04 | 78378.78 | 0.69 | 41571.71 | 421.64 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 141857.42 | 98821.52 | 43035.90 | 0.70 | 23670.12 | 240.08 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:EIR | COOLSYS1 CHILLER1 | 8.97 | 30.62 |
2 | Chiller:Electric:EIR | COOLSYS1 CHILLER2 | 8.97 | 30.62 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 76.91 | 200.61 | 76.91 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.38 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.38 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.38 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.38 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.38 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 0.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 52.57 | 133.74 | 52.57 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.38 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.38 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.38 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 90.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 76.91 | 200.61 | 76.91 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.38 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.38 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.38 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.38 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.38 | N/A | 2.159 | No | 23.18 | 23.18 | 23.18 | 180.00 | 90.00 | 13.65 | 1.70 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 52.57 | 133.74 | 52.57 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.38 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.38 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.38 | N/A | 2.159 | No | 25.75 | 25.75 | 25.75 | 270.00 | 90.00 | 15.43 | 1.67 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.065 | 3.065 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.38 | N/A | 2.159 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.38 | N/A | 2.159 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.38 | N/A | 2.159 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.38 | N/A | 2.159 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 84.71 | 200.61 | 84.71 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_NORTH_0.38 | N/A | 2.159 | No | 115.90 | 115.90 | 115.90 | 0.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 56.47 | 133.74 | 56.47 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_EAST_0.38 | N/A | 2.159 | No | 77.26 | 77.26 | 77.26 | 90.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 84.71 | 200.61 | 84.71 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_SOUTH_0.38 | N/A | 2.159 | No | 115.90 | 115.90 | 115.90 | 180.00 | 90.00 | 73.11 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 56.47 | 133.74 | 56.47 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_WEST_0.38 | N/A | 2.159 | No | 77.26 | 77.26 | 77.26 | 270.00 | 90.00 | 48.74 | 1.59 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.969 | 0.846 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.924 | 0.811 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.155 | 0.985 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.0544495091E-003 | 1.5314350421E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 3.5255040427E-003 | 6.4010792843E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 4.6036562506E-002 | 2.3246520624E-002 | Pass | Pass | 0.4699230241 | 0.4992229267 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 3.1016379104E-002 | 3.6681214356E-002 | Pass | Pass | 21.2222154214 | 51.6123274700 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.8604126128E-002 | 1.4875157001E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 1.8628366394E-002 | 1.5051298538E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 2.2021130192E-002 | 1.9462777702E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 1.9816714015E-002 | 1.7202274102E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2708557493 | 0.2503595620 | Pass | Pass | 35.0747680284 | 92.8413027232 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2711889940 | 0.2537774710 | Pass | Pass | 21.4520142060 | 63.9301099738 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2268963715 | 0.2303089102 | Pass | Pass | 33.3239136039 | 117.2595882997 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1449732274 | 0.1633355092 | Pass | Pass | 17.3973219713 | 56.3240072045 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3842988810 | 0.3825479382 | Pass | Pass | 44.3773174792 | 211.8174383935 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.4131332686 | 0.3972705960 | Pass | Pass | 31.0970302624 | 76.9477066102 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3770832307 | 0.3735274511 | Pass | Pass | 39.9332208999 | 96.7589606876 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3012355504 | 0.3070554698 | Pass | Pass | 20.2385152986 | 48.1655170446 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 3.5493014090E-003 | 2.9283011246E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 4.5375070608E-002 | 2.2390922021E-002 | Pass | Pass | 0.4836424571 | 0.4596096591 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1164988890 | 8.0585948234E-002 | Pass | Pass | 0.4920640311 | 0.4713985862 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.9095061963E-006 | 5.8267974331E-006 | Pass | Pass | 3.9396508672E-003 | 2.8924371336E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 6.1540829778E-003 | 4.0697368377E-003 | Pass | Pass | 1.8116177577E-003 | 1.6479381215E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 8.8574606362E-003 | 6.5409608624E-003 | Pass | Pass | 2.9503266310E-003 | 2.6871527658E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.0952135062E-006 | 2.6482226348E-006 | Pass | Pass | 4.3092531684E-005 | 1.0846875195E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 6700.32 | 144.67 | 0.00 | 27394.25 | 10734.45 | 44973.69 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 44.00 | 33 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 67.00 | 33 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 200.61 | 76.91 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 133.74 | 52.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 200.61 | 76.91 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 133.74 | 52.57 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 2006.06 | 847.11 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 1337.37 | 564.74 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 2006.06 | 847.11 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 1337.37 | 564.74 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 200.61 | 84.71 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 133.74 | 56.47 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 200.61 | 84.71 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 133.74 | 56.47 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.846 | 0.969 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.811 | 0.924 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 0.985 | 1.155 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.38_SHGC_NORTH_0.38 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.38_SHGC_NORTH_0.38 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.38_SHGC_NORTH_0.38 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.38_SHGC_NORTH_0.38 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.38_SHGC_NORTH_0.38 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.38_SHGC_EAST_0.38 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.38_SHGC_EAST_0.38 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.38_SHGC_EAST_0.38 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 23.18 | 0.00 | 0.00 | 23.18 | 23.18 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.38_SHGC_WEST_0.38 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.38_SHGC_WEST_0.38 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.38_SHGC_WEST_0.38 | 25.75 | 0.00 | 0.00 | 25.75 | 25.75 | 2.159 | 0.381 | 0.420 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.38_SHGC_NORTH_0.38 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.159 | 0.381 | 0.420 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.38_SHGC_EAST_0.38 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.159 | 0.381 | 0.420 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 115.90 | 0.00 | 0.00 | 115.90 | 1158.95 | 2.159 | 0.381 | 0.420 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.38_SHGC_WEST_0.38 | 77.26 | 0.00 | 0.00 | 77.26 | 772.63 | 2.159 | 0.381 | 0.420 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.38_SHGC_NORTH_0.38 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.159 | 0.381 | 0.420 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.38_SHGC_EAST_0.38 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.159 | 0.381 | 0.420 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.38_SHGC_SOUTH_0.38 | 115.90 | 0.00 | 0.00 | 115.90 | 115.90 | 2.159 | 0.381 | 0.420 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.38_SHGC_WEST_0.38 | 77.26 | 0.00 | 0.00 | 77.26 | 77.26 | 2.159 | 0.381 | 0.420 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 4635.80 | 2.159 | 0.381 | 0.420 | |||||||||||||||||
North Total or Average | 1390.74 | 2.159 | 0.381 | 0.420 | |||||||||||||||||
Non-North Total or Average | 3245.06 | 2.159 | 0.381 | 0.420 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.101 | 3.065 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 8.6849 | 2779.43 | 24139.15 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 216.17 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 8.6849 | 2496.12 | 21678.66 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 194.14 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 8.6849 | 24961.20 | 216786.56 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 1941.36 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 8.6849 | 2496.12 | 21678.66 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 47.71 | 0.0000 | Y | 194.14 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 8.6849 | 313.41 | 2721.97 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.57 | 0.0000 | Y | 14.09 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.32 | 0.0000 | Y | 9.00 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 8.6849 | 313.42 | 2722.03 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.08 | 0.0000 | Y | 13.84 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.30 | 0.0000 | Y | 8.99 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 8.6849 | 3134.13 | 27219.72 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.51 | 0.0000 | Y | 140.57 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 8.6849 | 2019.75 | 17541.42 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.28 | 0.0000 | Y | 89.81 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 8.6849 | 3134.20 | 27220.31 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.05 | 0.0000 | Y | 138.22 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 8.6849 | 2019.75 | 17541.42 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.25 | 0.0000 | Y | 89.72 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 8.6849 | 313.41 | 2721.97 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.51 | 0.0000 | Y | 14.06 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.27 | 0.0000 | Y | 8.98 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 8.6849 | 313.42 | 2722.03 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.05 | 0.0000 | Y | 13.82 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 8.6849 | 201.98 | 1754.14 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 27.24 | 0.0000 | Y | 8.97 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 8.6849 | 783.68 | 6806.21 | LightsWired | LTG_SCH_OFFICE | 50.34 | 168.00 | 49.04 | 0.0000 | Y | 62.65 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 13.9016 | 36.20 | 503.28 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.16 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 13.9016 | 362.03 | 5032.75 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 51.55 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 13.9016 | 36.20 | 503.28 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 5.16 |
Interior Lighting Total | 8.7339 | 46320.38 | 404555.99 | 1014.27 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2722.03 | 1049.89 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2722.03 | 377.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.39 | 2721.97 | 1049.86 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Stepped | 0.14 | 2721.97 | 376.99 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.39 | 1754.14 | 676.57 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Stepped | 0.14 | 1754.14 | 242.95 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 13271.55 | AstronomicalClock | - | 42.04 | 42.04 | 104.74 | |
EXTERIOR_LIGHTS_B | 989.48 | AstronomicalClock | - | 83.67 | 62.85 | 11.67 | |
EXTERIOR_LIGHTS_C | 26594.85 | AstronomicalClock | - | 83.67 | 47.45 | 236.87 | |
Exterior Lighting Total | 40855.88 | 353.28 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2675503.40 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 2663352.26 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:EIR | 1347040.23 | 5.91 | 1339261.74 | 5.88 | 8.97 | 30.62 |
COOLSYS1 CHILLER2 | Chiller:Electric:EIR | 1347040.23 | 5.91 | 1339261.74 | 5.88 | 8.97 | 30.62 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 620361.77 | |||||
CENTRAL BOILER | Boiler:HotWater | 605118.17 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1612443.64 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1612443.64 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 220222.50 | 252083.60 | 174349.98 | 77733.62 | 0.69 | - | 40990.16 | 415.74 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2121429.11 | 2386286.82 | 1641469.15 | 744817.67 | 0.69 | - | 384954.34 | 3904.42 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 221698.89 | 254921.81 | 176543.04 | 78378.78 | 0.69 | - | 41571.71 | 421.64 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 120419.14 | 141857.42 | 98821.52 | 43035.90 | 0.70 | - | 23670.12 | 240.08 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 498220.02 | 350848.69 | 147371.33 | 0.70 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9841.86 | 6962.73 | 2879.13 | 0.71 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 94494.59 | 66803.56 | 27691.03 | 0.71 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9603.56 | 6790.26 | 2813.30 | 0.71 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 21994.33 | 20853.84 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 468493.17 | 443851.16 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 92937.35 | 88070.68 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 16388.96 | 15529.06 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 11163.32 | 10577.48 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 18110.92 | 17160.36 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 9229.68 | 8741.82 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 245199.78 | 232315.92 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 160502.02 | 152068.15 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 245201.20 | 232317.26 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 156085.60 | 147884.31 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 31173.38 | 29534.44 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 20328.21 | 19259.42 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 31173.63 | 29534.68 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 20091.20 | 19034.89 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 83057.43 | 58656.67 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 849528.09 | 585772.30 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 82693.98 | 58676.87 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 100000.00 | 94838.35 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 498220.02 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9841.86 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 94494.59 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9603.56 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 22473.72 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 1038.19 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 10381.93 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 1038.19 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 9.86 | 22406.49 | 2271.59 | 1.00 | 1.12 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 92.11 | 210347.47 | 2283.73 | 1.00 | 1.07 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 10.01 | 22731.02 | 2271.59 | 1.00 | 1.12 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
CAV_BAS FAN | Fan:VariableVolume | 0.60 | 1389.42 | 5.65 | 12975.59 | 2298.46 | 1.00 | 1.13 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 25.15 | 41483.87 | 1649.25 | 1.00 | 1.14 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.50 | 562.62 | 1120.11 | 1.00 | 1.60 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.82 | 5394.93 | 1120.11 | 1.00 | 1.16 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.49 | 548.42 | 1120.11 | 1.00 | 1.62 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 105797.75 | 0.076755 | 12531.82 | 163269.45 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.023300 | 7016.99 | 301156.09 | 0.90 | General |
COOLSYS1 CHILLER1 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.038378 | 4338.10 | 113036.94 | 0.90 | General |
COOLSYS1 CHILLER2 PUMP | Pump:ConstantSpeed | Intermittent | 73247.35 | 0.038378 | 4338.10 | 113036.94 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.014992 | 3823.65 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000440 | 56.21 | 127739.32 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 148556.62 | 0.135660 | 33586.52 | 247577.87 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 1.00 | 13.34 | 0.74 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 76438.79 | 76438.79 | 27.50 | 5.645 | 5.645 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00896 | 23.42 | 0.01335 | 1.200 | 0.00 |
CORE_BOTTOM | 80779.76 | 80779.76 | 32.36 | 5.966 | 5.966 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00889 | 23.42 | 0.01335 | 1.078 | 0.00 |
CORE_MID | 760672.03 | 760672.03 | 304.74 | 56.162 | 56.162 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 23.42 | 0.01335 | 10.778 | 0.00 |
CORE_TOP | 75437.80 | 75437.80 | 30.22 | 5.570 | 5.570 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 23.42 | 0.01335 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 13271.05 | 13271.05 | 42.34 | 0.989 | 0.989 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00885 | 30.30 | 0.01337 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 17724.22 | 17724.22 | 87.75 | 1.321 | 1.321 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00867 | 25.18 | 0.01336 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 20385.12 | 20385.12 | 65.04 | 1.519 | 1.519 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00873 | 29.99 | 0.01337 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 21557.47 | 21557.47 | 106.73 | 1.607 | 1.607 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00864 | 28.84 | 0.01336 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 123891.75 | 123891.75 | 395.30 | 9.234 | 9.234 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00897 | 30.30 | 0.01337 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 188579.91 | 188579.91 | 933.68 | 14.055 | 14.055 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00871 | 25.71 | 0.01336 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 201914.06 | 201914.06 | 644.23 | 15.049 | 15.049 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00879 | 30.07 | 0.01337 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 197693.71 | 197693.71 | 978.80 | 14.734 | 14.734 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 24.00 | 24.00 | 0.00870 | 28.69 | 0.01336 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 13969.01 | 13969.01 | 44.57 | 1.041 | 1.041 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00895 | 30.30 | 0.01337 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 18997.61 | 18997.61 | 94.06 | 1.416 | 1.416 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00872 | 25.98 | 0.01336 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 21665.38 | 21665.38 | 69.13 | 1.615 | 1.615 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00880 | 30.14 | 0.01337 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 20805.53 | 20805.53 | 103.01 | 1.551 | 1.551 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00870 | 28.84 | 0.01336 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8545.00 | 8545.00 | 236.03 | 0.502 | 0.502 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 27.00 | 27.00 | 0.00858 | 26.50 | 0.01336 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 81936.59 | 81936.59 | 2263.27 | 4.816 | 4.816 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 27.00 | 27.00 | 0.00859 | 26.50 | 0.01336 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8329.34 | 8329.34 | 230.07 | 0.490 | 0.490 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 27.00 | 27.00 | 0.00859 | 26.50 | 0.01336 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 372094.76 | 427908.98 | 546.03 | 21.872 | 25.153 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 21.84 | 0.01335 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:50:00 | 21.00 | 22.99 | 0.00092 | -16.30 | 0.00092 | 1.200 | 0.00 |
CORE_BOTTOM | 2935.84 | 2935.84 | 1.18 | 0.128 | 1.078 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00710 | -16.30 | 0.00092 | 1.078 | 0.00 |
CORE_MID | 281608.43 | 281608.43 | 112.82 | 12.182 | 12.182 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 10.778 | 0.00 |
CORE_TOP | 65081.24 | 65081.24 | 26.07 | 2.838 | 2.838 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 11474.07 | 11474.07 | 36.61 | 0.501 | 0.501 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00768 | -16.30 | 0.00092 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 7814.83 | 7814.83 | 38.69 | 0.341 | 0.341 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00771 | -16.30 | 0.00092 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 12677.55 | 12677.55 | 40.45 | 0.554 | 0.554 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -16.30 | 0.00092 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 6079.14 | 6079.14 | 30.10 | 0.265 | 0.265 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00750 | -16.30 | 0.00092 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 171603.56 | 171603.56 | 547.53 | 7.504 | 7.504 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -16.30 | 0.00092 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 112326.83 | 112326.83 | 556.14 | 4.912 | 4.912 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -16.30 | 0.00092 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 171604.55 | 171604.55 | 547.52 | 7.504 | 7.504 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -16.30 | 0.00092 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 109239.04 | 109239.04 | 540.85 | 4.777 | 4.777 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00764 | -16.30 | 0.00092 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 21813.22 | 21813.22 | 69.60 | 0.954 | 0.954 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00767 | -16.30 | 0.00092 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 14224.42 | 14224.42 | 70.43 | 0.622 | 0.622 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00767 | -16.30 | 0.00092 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 21813.39 | 21813.39 | 69.60 | 0.954 | 0.954 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00767 | -16.30 | 0.00092 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 14058.68 | 14058.68 | 69.61 | 0.615 | 0.615 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -16.30 | 0.00092 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 24.95 | 0.00522 | -16.30 | 0.00092 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 22.73 | 0.00148 | -16.30 | 0.00092 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 20.67 | 0.00148 | -16.30 | 0.00092 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:30:00 | 18.00 | 27.00 | 0.00850 | -16.30 | 0.00092 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 9.86 | 9.86 | 2.74 | 2.74 | 9.8638 | 3.0785 | 9.8638 | 0.3121 | 0.3000 |
VAV_MID WITH REHEAT | 92.11 | 92.11 | 36.88 | 36.88 | 92.1071 | 36.8781 | 92.1071 | 0.4004 | 0.3000 |
VAV_TOP WITH REHEAT | 10.01 | 10.01 | 5.98 | 5.98 | 10.0066 | 5.9840 | 10.0066 | 0.5980 | 0.3000 |
CAV_BAS | 5.65 | 5.65 | 1.20 | 1.20 | 5.6453 | 1.2002 | 5.6453 | 0.2126 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 25.15 | 25.15 | 0.34 | 0.34 | 25.1532 | 25.1531 | 25.1532 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.50 | 0.50 | 0.02 | 0.02 | 0.5023 | 0.5023 | 0.5023 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.82 | 4.82 | 0.16 | 0.16 | 4.8164 | 4.8164 | 4.8164 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.49 | 0.49 | 0.02 | 0.02 | 0.4896 | 0.4896 | 0.4896 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 21994.326 | 21994.326 | 1.944805 | 0.00019242 | 450.119 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21994.33 | 21994.33 | 1.944805 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00709795 | 44.7979 | 2935.84 | 0.00 | 22074.78 | 22074.78 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 468493.173 | 468493.173 | 19.038914 | 0.00409858 | 11118.361 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 468493.17 | 468493.17 | 19.038914 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 281608.43 | 0.00 | 470020.83 | 470020.83 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 92937.347 | 92937.347 | 2.837846 | 0.00081306 | 2453.240 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 92937.35 | 92937.35 | 2.837846 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 65081.24 | 0.00 | 93258.35 | 93258.35 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 16388.960 | 16388.960 | 0.501074 | 0.00014338 | 432.363 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 16388.96 | 16388.96 | 0.501074 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00767949 | 48.4269 | 11474.07 | 0.00 | 16443.76 | 16443.76 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 11163.325 | 11163.325 | 0.341354 | 0.00009766 | 294.485 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11163.32 | 11163.32 | 0.341354 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00771429 | 48.6433 | 7814.83 | 0.00 | 11200.51 | 11200.51 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 18110.920 | 18110.920 | 0.553839 | 0.00015844 | 477.744 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 18110.92 | 18110.92 | 0.553839 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00775498 | 48.8963 | 12677.55 | 0.00 | 18171.14 | 18171.14 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 9229.679 | 9229.679 | 0.321325 | 0.00008075 | 230.735 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9229.68 | 9229.68 | 0.321325 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00749529 | 47.2805 | 6079.14 | 0.00 | 9258.45 | 9258.45 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 245199.784 | 245199.784 | 7.503779 | 0.00214511 | 6465.910 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 245199.78 | 245199.78 | 7.503779 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00765855 | 48.2976 | 171603.56 | 0.00 | 245999.53 | 245999.53 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 160502.025 | 160502.025 | 4.911949 | 0.00140414 | 4232.373 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 160502.02 | 160502.02 | 4.911949 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00765345 | 48.2659 | 112326.83 | 0.00 | 161025.09 | 161025.09 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 245201.198 | 245201.198 | 7.503822 | 0.00214513 | 6465.947 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 245201.20 | 245201.20 | 7.503822 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00765856 | 48.2976 | 171604.55 | 0.00 | 246000.95 | 246000.95 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 156085.602 | 156085.602 | 4.776597 | 0.00136550 | 4115.990 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 156085.60 | 156085.60 | 4.776597 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00764220 | 48.1959 | 109239.04 | 0.00 | 156594.82 | 156594.82 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 31173.377 | 31173.377 | 0.954350 | 0.00027272 | 821.899 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 31173.38 | 31173.38 | 0.954350 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00767356 | 48.3918 | 21813.22 | 0.00 | 31274.03 | 31274.03 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 20328.206 | 20328.206 | 0.622346 | 0.00017784 | 535.957 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20328.21 | 20328.21 | 0.622346 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00766672 | 48.3493 | 14224.42 | 0.00 | 20393.80 | 20393.80 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 31173.630 | 31173.630 | 0.954358 | 0.00027272 | 821.906 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 31173.63 | 31173.63 | 0.954358 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00767357 | 48.3918 | 21813.39 | 0.00 | 31274.28 | 31274.28 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 20091.200 | 20091.200 | 0.615085 | 0.00017577 | 529.710 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 20091.20 | 20091.20 | 0.615085 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00766283 | 48.3251 | 14058.68 | 0.00 | 20156.05 | 20156.05 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 220222.504 | -999.000 | 9.863777 | 0.00629834 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 220222.50 | 173660.55 | 9.863777 | 25.67 | 17.98 | 0.01005191 | 10.91 | 10.91 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 25.7324 | 24.00 | 0.00885711 | 46.4585 | 128550.21 | 0.00 | 224272.32 | 170915.11 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 83057.434 | 83057.434 | 2.959133 | 0.00072662 | 1312.564 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:40:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 83057.43 | 83057.43 | 2.959133 | -10.99 | -10.99 | 0.00186031 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 85.7748 | 21.00 | 0.00772549 | 48.7119 | 35074.45 | 0.00 | 70919.90 | 70919.90 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2121429.107 | -999.000 | 92.107065 | 0.06067260 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 2121429.11 | 1640077.83 | 92.107065 | 25.83 | 18.16 | 0.01021790 | 10.90 | 10.90 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 27.5570 | 24.00 | 0.00892501 | 46.8101 | 1170065.33 | 0.00 | 2159534.69 | 1615542.97 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 849528.095 | 849528.095 | 27.632120 | 0.00743204 | 13282.215 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 849528.09 | 849528.09 | 27.632120 | -13.26 | -13.26 | 0.00147577 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 91.8567 | 19.59 | 0.00762032 | 52.4364 | 462919.76 | 0.00 | 708064.22 | 708064.22 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 221698.893 | -999.000 | 10.006643 | 0.00634056 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 221698.89 | 175357.94 | 10.006643 | 25.60 | 17.93 | 0.01002236 | 10.91 | 10.91 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 25.3650 | 24.00 | 0.00888358 | 46.5960 | 134079.24 | 0.00 | 225801.62 | 172549.67 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 82693.982 | 82693.982 | 3.001993 | 0.00072344 | 1309.621 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 82693.98 | 82693.98 | 3.001993 | -10.55 | -10.55 | 0.00195193 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 84.5502 | 17.56 | 0.00755343 | 59.0161 | 55358.28 | 0.00 | 70947.94 | 70947.94 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 120419.142 | -999.000 | 5.645336 | 0.00344397 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 120419.14 | 94710.65 | 5.645336 | 24.96 | 17.70 | 0.00999483 | 10.89 | 10.89 | 0.00850000 | 28.16 | 0.01336316 | 21.21 | 21.2593 | 24.00 | 0.00898461 | 47.1178 | 69796.13 | 0.00 | 122696.48 | 93092.32 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 100000.000 | 100000.000 | 3.116633 | 0.00087484 | 2622.476 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 100000.00 | 100000.00 | 3.116633 | -3.47 | -6.92 | 0.00092409 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 38.5081 | 23.08 | 0.00092409 | 5.1897 | 0.00 | 0.00 | 100076.34 | 100076.34 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 498220.020 | 350848.693 | 25.153218 | 0.01220138 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 462693.83 | 455611.08 | -999.0 | 28.47 | 17.75 | 0.00860721 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | -999.0000 | 27.00 | 0.00854223 | 37.5159 | 371658.74 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9841.858 | 6962.728 | 0.502293 | 0.00024103 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 9122.52 | 8815.15 | -999.0 | 27.95 | 17.68 | 0.00873334 | 12.80 | 11.87 | 0.00850000 | 26.50 | 0.01336023 | 20.72 | -999.0000 | 27.00 | 0.00858472 | 37.6976 | 8545.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 94494.595 | 66803.562 | 4.816433 | 0.00231417 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 87606.47 | 84534.40 | -999.0 | 27.95 | 17.68 | 0.00874318 | 12.80 | 11.87 | 0.00850000 | 26.50 | 0.01336023 | 20.72 | -999.0000 | 27.00 | 0.00858831 | 37.7133 | 81936.59 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9603.561 | 6790.263 | 0.489618 | 0.00023519 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 8903.20 | 8596.04 | -999.0 | 27.96 | 17.68 | 0.00873920 | 12.80 | 11.87 | 0.00850000 | 26.67 | 0.01336053 | 20.77 | -999.0000 | 27.00 | 0.00858676 | 37.7065 | 8328.46 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 498220.020 | 498220.020 | 25.153218 | 0.01220138 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 498220.02 | 498220.02 | 25.153218 | -16.30 | -16.30 | 0.00092409 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 1.3453 | 27.00 | 0.00850000 | 37.3272 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9841.858 | 9841.858 | 0.502293 | 0.00024103 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9841.86 | 9841.86 | 0.502293 | -16.30 | -16.30 | 0.00092409 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 3.1122 | 25.59 | 0.00522445 | 25.0656 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 94494.595 | 94494.595 | 4.816433 | 0.00231417 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 94494.59 | 94494.59 | 4.816433 | -16.30 | -16.30 | 0.00092409 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 3.2456 | 23.88 | 0.00148457 | 7.9344 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9603.561 | 9603.561 | 0.489618 | 0.00023519 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9603.56 | 9603.56 | 0.489618 | -16.30 | -16.30 | 0.00092409 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 3.1928 | 22.66 | 0.00147926 | 8.5099 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 22473.716 | 22473.716 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 22473.72 | 22473.72 | 25.153218 | -0.22 | -0.22 | 0.00839808 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 1.3453 | 27.00 | 0.00850000 | 37.3272 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 1038.193 | 1038.193 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1038.19 | 1038.19 | 0.502293 | -0.51 | -0.51 | 0.00509062 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 3.1122 | 25.59 | 0.00522445 | 25.0656 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 10381.926 | 10381.926 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10381.93 | 10381.93 | 4.816433 | -0.53 | -4.11 | 0.00146638 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 3.2456 | 23.88 | 0.00148457 | 7.9344 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 1038.193 | 1038.193 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1038.19 | 1038.19 | 0.489618 | -0.52 | -4.11 | 0.00146153 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 3.1928 | 22.66 | 0.00147926 | 8.5099 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 21994.326 | 21994.326 | 1.944805 | 0.00019242 | 450.119 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.29779058 | 54.44 | 82.22 | 27.78 | 2716953.28 | 0.8095 | 0.825814 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 21994.33 | 21994.33 | 1.0000 | 2.28305551 | 1.944805 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.19239633 | 60.00 | 32.22 | 27.78 | 0.000 | 21994.33 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.92 | 0.00709795 | 21.00 | 0.00709795 | 44.7979 | 2935.84 | 0.00 | 22074.78 | 22074.78 | 2.28305551 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 22.28 | 15.33 | 0.00800000 | 42728.8 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 468493.173 | 468493.173 | 19.038914 | 0.00409858 | 11118.361 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.29779058 | 54.44 | 82.22 | 27.78 | 2716953.28 | 17.2433 | 17.590357 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 468493.17 | 468493.17 | 1.0000 | 22.35026341 | 19.038914 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 4.09816455 | 60.00 | 32.22 | 27.78 | 0.000 | 468493.17 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 281608.43 | 0.00 | 470020.83 | 470020.83 | 22.35026341 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 33.42 | 19.16 | 0.00800000 | 54089.6 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 92937.347 | 92937.347 | 2.837846 | 0.00081306 | 2453.240 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.29779058 | 54.44 | 82.22 | 27.78 | 2716953.28 | 3.4206 | 3.489488 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 92937.35 | 92937.35 | 1.0000 | 3.33141895 | 2.837846 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.81297351 | 60.00 | 32.22 | 27.78 | 0.000 | 92937.35 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 65081.24 | 0.00 | 93258.35 | 93258.35 | 3.33141895 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.25 | 21.26 | 0.00800000 | 61053.4 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16388.960 | 16388.960 | 0.501074 | 0.00014338 | 432.363 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.29779058 | 54.44 | 82.22 | 27.78 | 2716953.28 | 0.6032 | 0.615351 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 16388.96 | 16388.96 | 1.0000 | 0.58822333 | 0.501074 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.14336315 | 60.00 | 32.22 | 27.78 | 0.000 | 16388.96 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00767949 | 21.00 | 0.00767949 | 48.4269 | 11474.07 | 0.00 | 16443.76 | 16443.76 | 0.58822333 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.25 | 0.00800000 | 61014.8 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11163.325 | 11163.325 | 0.341354 | 0.00009766 | 294.485 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.29779058 | 54.44 | 82.22 | 27.78 | 2716953.28 | 0.4109 | 0.419146 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 11163.32 | 11163.32 | 1.0000 | 0.40072362 | 0.341354 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.09765167 | 60.00 | 32.22 | 27.78 | 0.000 | 11163.32 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00771429 | 21.00 | 0.00771429 | 48.6433 | 7814.83 | 0.00 | 11200.51 | 11200.51 | 0.40072362 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61010.6 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 18110.920 | 18110.920 | 0.553839 | 0.00015844 | 477.744 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.29779058 | 54.44 | 82.22 | 27.78 | 2716953.28 | 0.6666 | 0.680005 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 18110.92 | 18110.92 | 1.0000 | 0.65016570 | 0.553839 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.15842607 | 60.00 | 32.22 | 27.78 | 0.000 | 18110.92 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00775498 | 21.00 | 0.00775498 | 48.8963 | 12677.55 | 0.00 | 18171.14 | 18171.14 | 0.65016570 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61008.3 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9229.679 | 9229.679 | 0.321325 | 0.00008075 | 230.735 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.29779058 | 54.44 | 82.22 | 27.78 | 2716953.28 | 0.3397 | 0.346544 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9229.68 | 9229.68 | 1.0000 | 0.37721124 | 0.321325 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.08073702 | 60.00 | 32.22 | 27.78 | 0.000 | 9229.68 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.91 | 0.00749529 | 21.00 | 0.00749529 | 47.2805 | 6079.14 | 0.00 | 9258.45 | 9258.45 | 0.37721124 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 36.87 | 20.24 | 0.00800000 | 57604.3 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 245199.784 | 245199.784 | 7.503779 | 0.00214511 | 6465.910 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.29779058 | 54.44 | 82.22 | 27.78 | 2716953.28 | 9.0248 | 9.206435 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 245199.78 | 245199.78 | 1.0000 | 8.80887639 | 7.503779 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 2.14489585 | 60.00 | 32.22 | 27.78 | 0.000 | 245199.78 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00765855 | 21.00 | 0.00765855 | 48.2976 | 171603.56 | 0.00 | 245999.53 | 245999.53 | 8.80887639 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60986.2 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 160502.025 | 160502.025 | 4.911949 | 0.00140414 | 4232.373 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.29779058 | 54.44 | 82.22 | 27.78 | 2716953.28 | 5.9074 | 6.026316 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 160502.02 | 160502.02 | 1.0000 | 5.76626136 | 4.911949 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 1.40399849 | 60.00 | 32.22 | 27.78 | 0.000 | 160502.02 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00765345 | 21.00 | 0.00765345 | 48.2659 | 112326.83 | 0.00 | 161025.09 | 161025.09 | 5.76626136 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60985.2 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 245201.198 | 245201.198 | 7.503822 | 0.00214513 | 6465.947 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.29779058 | 54.44 | 82.22 | 27.78 | 2716953.28 | 9.0249 | 9.206488 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 245201.20 | 245201.20 | 1.0000 | 8.80892694 | 7.503822 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 2.14490822 | 60.00 | 32.22 | 27.78 | 0.000 | 245201.20 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00765856 | 21.00 | 0.00765856 | 48.2976 | 171604.55 | 0.00 | 246000.95 | 246000.95 | 8.80892694 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60986.2 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 156085.602 | 156085.602 | 4.776597 | 0.00136550 | 4115.990 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.29779058 | 54.44 | 82.22 | 27.78 | 2716953.28 | 5.7449 | 5.860494 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 156085.60 | 156085.60 | 1.0000 | 5.60736767 | 4.776597 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 1.36536564 | 60.00 | 32.22 | 27.78 | 0.000 | 156085.60 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00764220 | 21.00 | 0.00764220 | 48.1959 | 109239.04 | 0.00 | 156594.82 | 156594.82 | 5.60736767 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60986.4 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 31173.377 | 31173.377 | 0.954350 | 0.00027272 | 821.899 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.29779058 | 54.44 | 82.22 | 27.78 | 2716953.28 | 1.1474 | 1.170456 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 31173.38 | 31173.38 | 1.0000 | 1.12033606 | 0.954350 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.27269048 | 60.00 | 32.22 | 27.78 | 0.000 | 31173.38 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00767356 | 21.00 | 0.00767356 | 48.3918 | 21813.22 | 0.00 | 31274.03 | 31274.03 | 1.12033606 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60974.7 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20328.206 | 20328.206 | 0.622346 | 0.00017784 | 535.957 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.29779058 | 54.44 | 82.22 | 27.78 | 2716953.28 | 0.7482 | 0.763256 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20328.21 | 20328.21 | 1.0000 | 0.73058783 | 0.622346 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.17782187 | 60.00 | 32.22 | 27.78 | 0.000 | 20328.21 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00766672 | 21.00 | 0.00766672 | 48.3493 | 14224.42 | 0.00 | 20393.80 | 20393.80 | 0.73058783 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60974.1 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 31173.630 | 31173.630 | 0.954358 | 0.00027272 | 821.906 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.29779058 | 54.44 | 82.22 | 27.78 | 2716953.28 | 1.1474 | 1.170466 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 31173.63 | 31173.63 | 1.0000 | 1.12034511 | 0.954358 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.27269269 | 60.00 | 32.22 | 27.78 | 0.000 | 31173.63 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00767357 | 21.00 | 0.00767357 | 48.3918 | 21813.39 | 0.00 | 31274.28 | 31274.28 | 1.12034511 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60974.7 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20091.200 | 20091.200 | 0.615085 | 0.00017577 | 529.710 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.29779058 | 54.44 | 82.22 | 27.78 | 2716953.28 | 0.7395 | 0.754358 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 20091.20 | 20091.20 | 1.0000 | 0.72206372 | 0.615085 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.17574865 | 60.00 | 32.22 | 27.78 | 0.000 | 20091.20 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00766283 | 21.00 | 0.00766283 | 48.3251 | 14058.68 | 0.00 | 20156.05 | 20156.05 | 0.72206372 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60974.3 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 220222.504 | -999.000 | 9.863777 | 0.00629834 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.5260 | 1004.8586 | 1.1739 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.863777 | 11.57933786 | 4197.9300 | 999.8980 | 76.74764233 | 15.00 | 6.67 | 8.33 | 2683769.65 | 8.2057 | 8.205716 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 220222.50 | 173660.55 | 1.0000 | 11.57933786 | 9.863777 | 25.67 | 17.98 | 0.01005191 | 51411.2 | 10.91 | 10.91 | 0.00850000 | 32392.6 | 6.29769325 | 6.67 | 15.00 | 8.33 | 22406.490 | 197816.01 | 30.30 | 0.01336696 | 21.83 | 2.53819000 | 25.7324 | 24.00 | 0.00885711 | 24.00 | 0.00885711 | 46.4585 | 128550.21 | 0.00 | 224272.32 | 170915.11 | 11.57933786 | 25.67 | 18.25 | 0.01005191 | 51411.2 | 11.25 | 11.17 | 0.00822469 | 32042.9 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 83057.434 | 83057.434 | 2.959133 | 0.00072662 | 1312.564 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.863777 | 11.57933786 | 4197.9300 | 999.8980 | 23.29779058 | 54.44 | 82.22 | 27.78 | 2716953.28 | 3.0570 | 3.118530 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:40:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 83057.43 | 83057.43 | 1.0000 | 3.47380136 | 2.959133 | -10.99 | -10.99 | 0.00186031 | -6432.8 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 0.72654854 | 60.00 | 32.22 | 27.78 | 0.000 | 83057.43 | -16.30 | 0.00092409 | -16.30 | 2.53819000 | 85.7748 | 21.00 | 0.00750552 | 21.00 | 0.00772549 | 48.7119 | 35074.45 | 0.00 | 70919.90 | 70919.90 | 3.47380136 | 2.80 | -1.40 | 0.00186031 | 7475.8 | 23.05 | 9.50 | 0.00186031 | 27891.4 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2121429.107 | -999.000 | 92.107065 | 0.06067260 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.8346 | 1004.8586 | 1.1739 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 92.107065 | 108.12681542 | 4197.9300 | 999.8980 | 76.74764233 | 15.00 | 6.67 | 8.33 | 2683769.65 | 79.0466 | 79.046617 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 2121429.11 | 1640077.83 | 1.0000 | 108.12681542 | 92.107065 | 25.83 | 18.16 | 0.01021790 | 52002.7 | 10.90 | 10.90 | 0.00850000 | 32382.9 | 60.66641469 | 6.67 | 15.00 | 8.33 | 210347.466 | 1911081.64 | 30.30 | 0.01336696 | 21.83 | 25.38195000 | 27.5570 | 24.00 | 0.00892501 | 24.00 | 0.00892501 | 46.8101 | 1170065.33 | 0.00 | 2159534.69 | 1615542.97 | 108.12681542 | 25.83 | 18.44 | 0.01021790 | 52002.7 | 11.24 | 11.16 | 0.00822290 | 32030.5 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 849528.095 | 849528.095 | 27.632120 | 0.00743204 | 13282.215 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 92.107065 | 108.12681542 | 4197.9300 | 999.8980 | 23.29779058 | 54.44 | 82.22 | 27.78 | 2716953.28 | 31.2677 | 31.896948 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 849528.09 | 849528.09 | 1.0000 | 32.43804462 | 27.632120 | -13.26 | -13.26 | 0.00147577 | -9672.4 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 7.43128422 | 60.00 | 32.22 | 27.78 | 0.000 | 849528.09 | -16.30 | 0.00092409 | -16.30 | 25.38195000 | 91.8567 | 21.00 | 0.00769866 | 19.59 | 0.00762032 | 52.4364 | 462919.76 | 0.00 | 708064.22 | 708064.22 | 32.43804462 | 2.80 | -2.01 | 0.00147577 | 6512.0 | 24.46 | 9.71 | 0.00147577 | 28340.2 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 221698.893 | -999.000 | 10.006643 | 0.00634056 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.4711 | 1004.8586 | 1.1739 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.006643 | 11.74705157 | 4197.9300 | 999.8980 | 76.74764233 | 15.00 | 6.67 | 8.33 | 2683769.65 | 8.2607 | 8.260727 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 221698.89 | 175357.94 | 1.0000 | 11.74705157 | 10.006643 | 25.60 | 17.93 | 0.01002236 | 51265.2 | 10.91 | 10.91 | 0.00850000 | 32392.5 | 6.33991348 | 6.67 | 15.00 | 8.33 | 22731.023 | 198967.87 | 30.30 | 0.01336696 | 21.83 | 2.53819000 | 25.3650 | 24.00 | 0.00888358 | 24.00 | 0.00888358 | 46.5960 | 134079.24 | 0.00 | 225801.62 | 172549.67 | 11.74705157 | 25.60 | 18.20 | 0.01002236 | 51265.2 | 11.25 | 11.17 | 0.00822478 | 32043.2 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 82693.982 | 82693.982 | 3.001993 | 0.00072344 | 1309.621 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 10.006643 | 11.74705157 | 4197.9300 | 999.8980 | 23.29779058 | 54.44 | 82.22 | 27.78 | 2716953.28 | 3.0436 | 3.104883 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:20:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 82693.98 | 82693.98 | 1.0000 | 3.52411547 | 3.001993 | -10.55 | -10.55 | 0.00195193 | -5759.4 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 0.72336923 | 60.00 | 32.22 | 27.78 | 0.000 | 82693.98 | -16.30 | 0.00092409 | -16.30 | 2.53819000 | 84.5502 | 20.91 | 0.00757687 | 17.56 | 0.00755343 | 59.0161 | 55358.28 | 0.00 | 70947.94 | 70947.94 | 3.52411547 | 2.80 | -1.26 | 0.00195193 | 7705.4 | 22.76 | 9.48 | 0.00195193 | 27837.5 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 120419.142 | -999.000 | 5.645336 | 0.00344397 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.4199 | 1004.8586 | 1.1739 | CAV_BAS FAN | Fan:VariableVolume | 5.645336 | 6.62720240 | 4197.9300 | 999.8980 | 76.74764233 | 15.00 | 6.67 | 8.33 | 2683769.65 | 4.4869 | 4.486940 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 120419.14 | 94710.65 | 1.0000 | 6.62720240 | 5.645336 | 24.96 | 17.70 | 0.00999483 | 50540.0 | 10.89 | 10.89 | 0.00850000 | 32369.6 | 3.44362091 | 6.67 | 15.00 | 8.33 | 12975.587 | 107443.56 | 28.16 | 0.01336316 | 21.21 | 1.20015641 | 21.2593 | 24.00 | 0.00898461 | 24.00 | 0.00898461 | 47.1178 | 69796.13 | 0.00 | 122696.48 | 93092.32 | 6.62720240 | 24.96 | 17.97 | 0.00999483 | 50540.0 | 11.23 | 11.16 | 0.00822346 | 32025.9 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 100000.000 | 100000.000 | 3.116633 | 0.00087484 | 2622.476 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | CAV_BAS FAN | Fan:VariableVolume | 5.645336 | 6.62720240 | 4197.9300 | 999.8980 | 23.29779058 | 54.44 | 82.22 | 27.78 | 2716953.28 | 3.6806 | 3.754667 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 100000.00 | 100000.00 | 1.0000 | 3.65869449 | 3.116633 | -3.47 | -6.92 | 0.00092409 | -1176.9 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.87475438 | 60.00 | 32.22 | 27.78 | 0.000 | 100000.00 | -16.30 | 0.00092409 | -16.30 | 1.20015641 | 38.5081 | 0.00 | 0.00092409 | 23.08 | 0.00092409 | 5.1897 | 0.00 | 0.00 | 100076.34 | 100076.34 | 3.65869449 | 12.80 | 1.98 | 0.00000000 | 12887.2 | 40.02 | 14.59 | 0.00000000 | 40240.2 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 498220.020 | 350848.693 | 25.153218 | 0.01220138 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8404 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 462693.83 | 455611.08 | 0.9287 | -999.0 | -999.0 | 28.47 | 17.75 | 0.00860721 | 50590.1 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 462693.83 | 30.30 | 0.01336696 | 21.83 | 0.33839277 | -999.0000 | 27.00 | 0.00854223 | 27.00 | 0.00854223 | 37.5159 | 371658.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9841.858 | 6962.728 | 0.502293 | 0.00024103 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.0748 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | Sensible | 9122.52 | 8815.15 | 0.9269 | -999.0 | -999.0 | 27.95 | 17.68 | 0.00873334 | 50383.8 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9122.52 | 26.50 | 0.01336023 | 20.72 | 0.01563234 | -999.0000 | 27.00 | 0.00858472 | 27.00 | 0.00858472 | 37.6976 | 8545.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 94494.595 | 66803.562 | 4.816433 | 0.00231417 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.0931 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | Sensible | 87606.47 | 84534.40 | 0.9271 | -999.0 | -999.0 | 27.95 | 17.68 | 0.00874318 | 50408.2 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 87606.47 | 26.50 | 0.01336023 | 20.72 | 0.15632344 | -999.0000 | 27.00 | 0.00858831 | 27.00 | 0.00858831 | 37.7133 | 81936.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9603.561 | 6790.263 | 0.489618 | 0.00023519 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.0857 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | Sensible | 8903.20 | 8596.04 | 0.9271 | -999.0 | -999.0 | 27.96 | 17.68 | 0.00873920 | 50403.9 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8903.20 | 26.67 | 0.01336053 | 20.77 | 0.01563234 | -999.0000 | 27.00 | 0.00858676 | 27.00 | 0.00858676 | 37.7065 | 8328.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 498220.020 | 498220.020 | 25.153218 | 0.01220138 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 498220.02 | 498220.02 | 1.0000 | 29.52799968 | 25.153218 | -16.30 | -16.30 | 0.00092409 | -14095.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 498220.02 | -16.30 | 0.00092409 | -16.30 | 0.33839277 | 1.3453 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.3272 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9841.858 | 9841.858 | 0.502293 | 0.00024103 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9841.86 | 9841.86 | 1.0000 | 0.58965471 | 0.502293 | -16.30 | -16.30 | 0.00092409 | -14095.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9841.86 | -16.30 | 0.00092409 | -16.30 | 0.01563234 | 3.1122 | 0.00 | 0.00522445 | 25.59 | 0.00522445 | 25.0656 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 94494.595 | 94494.595 | 4.816433 | 0.00231417 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 94494.59 | 94494.59 | 1.0000 | 5.65413285 | 4.816433 | -16.30 | -16.30 | 0.00092409 | -14095.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 94494.59 | -16.30 | 0.00092409 | -16.30 | 0.15632344 | 3.2456 | 0.00 | 0.00148457 | 23.88 | 0.00148457 | 7.9344 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9603.561 | 9603.561 | 0.489618 | 0.00023519 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9603.56 | 9603.56 | 1.0000 | 0.57477480 | 0.489618 | -16.30 | -16.30 | 0.00092409 | -14095.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9603.56 | -16.30 | 0.00092409 | -16.30 | 0.01563234 | 3.1928 | 0.00 | 0.00147926 | 22.66 | 0.00147926 | 8.5099 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 22473.716 | 22473.716 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 25.153218 | 29.52799968 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 22473.72 | 22473.72 | 1.0000 | 29.52799968 | 25.153218 | -0.22 | -0.22 | 0.00839808 | 20779.3 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22473.72 | -16.30 | 0.00092409 | -16.30 | 0.33839277 | 1.3453 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.3272 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1038.193 | 1038.193 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.502293 | 0.58965471 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1038.19 | 1038.19 | 1.0000 | 0.58965471 | 0.502293 | -0.51 | -0.51 | 0.00509062 | 12216.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1038.19 | -16.30 | 0.00092409 | -16.30 | 0.01563234 | 3.1122 | 0.00 | 0.00522445 | 25.59 | 0.00522445 | 25.0656 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10381.926 | 10381.926 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.816433 | 5.65413285 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 10381.93 | 10381.93 | 1.0000 | 5.65413285 | 4.816433 | -0.53 | -4.11 | 0.00146638 | 3134.3 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10381.93 | -16.30 | 0.00092409 | -16.30 | 0.15632344 | 3.2456 | 0.00 | 0.00148457 | 23.88 | 0.00148457 | 7.9344 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1038.193 | 1038.193 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.489618 | 0.57477480 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1038.19 | 1038.19 | 1.0000 | 0.57477480 | 0.489618 | -0.52 | -4.11 | 0.00146153 | 3130.9 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1038.19 | -16.30 | 0.00092409 | -16.30 | 0.01563234 | 3.1928 | 0.00 | 0.00147926 | 22.66 | 0.00147926 | 8.5099 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 9.86 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 92.11 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 10.01 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 5.65 | - | |||
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | DifferentialDryBulb | 0.34 | 25.15 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2853.67 | 1581.17 | 670.67 |
CORE_BOTTOM | 2497.67 | 1338.33 | 12.50 |
CORE_MID | 1809.33 | 3046.50 | 115.67 |
CORE_TOP | 2430.67 | 3662.67 | 913.83 |
PERIMETER_BOT_ZN_3 | 2302.17 | 3271.33 | 532.83 |
PERIMETER_BOT_ZN_2 | 2542.83 | 3365.33 | 611.83 |
PERIMETER_BOT_ZN_1 | 2737.50 | 2979.50 | 637.67 |
PERIMETER_BOT_ZN_4 | 2847.67 | 2491.50 | 386.67 |
PERIMETER_MID_ZN_3 | 3173.00 | 3964.33 | 1815.50 |
PERIMETER_MID_ZN_2 | 2838.00 | 3336.33 | 1546.83 |
PERIMETER_MID_ZN_1 | 3090.33 | 3413.50 | 1266.17 |
PERIMETER_MID_ZN_4 | 3200.33 | 3850.17 | 1550.17 |
PERIMETER_TOP_ZN_3 | 3596.17 | 4185.67 | 2331.33 |
PERIMETER_TOP_ZN_2 | 3729.83 | 3944.17 | 2174.00 |
PERIMETER_TOP_ZN_1 | 3392.33 | 3705.83 | 1765.67 |
PERIMETER_TOP_ZN_4 | 3515.17 | 4062.50 | 2004.17 |
DATACENTER_BOT_ZN_6 | 5923.50 | 940.50 | 940.50 |
DATACENTER_MID_ZN_6 | 5187.83 | 255.33 | 175.67 |
DATACENTER_TOP_ZN_6 | 4703.33 | 677.50 | 326.67 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5580.00 | 5580.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5937.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 1685.33 | 0.00 | 1006.00 |
CORE_BOTTOM | 0.00 | 4.83 | 0.00 | 0.00 |
CORE_MID | 1.50 | 0.00 | 0.67 | 0.00 |
CORE_TOP | 13.67 | 0.00 | 2.33 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.67 | 7.83 | 0.00 | 5.17 |
PERIMETER_BOT_ZN_2 | 1.33 | 21.17 | 0.00 | 21.17 |
PERIMETER_BOT_ZN_1 | 2.33 | 35.67 | 0.00 | 34.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 81.67 | 0.00 | 36.67 |
PERIMETER_MID_ZN_3 | 70.50 | 0.67 | 17.83 | 0.67 |
PERIMETER_MID_ZN_2 | 38.83 | 21.00 | 0.33 | 21.00 |
PERIMETER_MID_ZN_1 | 30.17 | 31.67 | 0.83 | 31.00 |
PERIMETER_MID_ZN_4 | 25.83 | 30.83 | 0.17 | 16.83 |
PERIMETER_TOP_ZN_3 | 217.00 | 4.00 | 70.83 | 3.17 |
PERIMETER_TOP_ZN_2 | 119.33 | 22.33 | 15.83 | 21.83 |
PERIMETER_TOP_ZN_1 | 105.00 | 26.17 | 10.67 | 25.00 |
PERIMETER_TOP_ZN_4 | 81.83 | 31.33 | 8.83 | 18.17 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 126.83 | 0.00 | 92.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 240.67 | 1799.83 | 71.83 | 1093.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 149.60 | 6779.02 | 1.015 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.50 | 134.35 | 6849.35 | 1.007 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.50 | 134.35 | 6849.35 | 0.745 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.50 | 134.35 | 6849.35 | 0.728 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.97 | 16.87 | 860.00 | 0.968 | 0.027 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.49 | 10.87 | 554.22 | 1.509 | 0.027 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.97 | 16.87 | 860.02 | 1.389 | 0.027 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.49 | 10.87 | 554.22 | 1.973 | 0.028 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.97 | 16.87 | 860.00 | 0.776 | 0.062 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.92 | 10.87 | 554.22 | 1.340 | 0.068 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.97 | 16.87 | 860.02 | 1.259 | 0.062 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.49 | 10.87 | 554.22 | 1.483 | 0.064 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.97 | 16.87 | 860.00 | 0.797 | 0.077 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.49 | 10.87 | 554.22 | 1.467 | 0.080 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.97 | 16.87 | 860.02 | 1.278 | 0.077 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.49 | 10.87 | 554.22 | 1.537 | 0.080 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.43 | 42.18 | 1911.37 | 27.385 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.80 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.50 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.50 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.50 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.97 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.49 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.97 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.49 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.97 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.92 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.97 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.49 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.97 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.49 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.97 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.49 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.43 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 61.80 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.50 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.50 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.50 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.97 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.49 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.97 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.49 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.97 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.92 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.97 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.49 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.97 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.49 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.97 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.49 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.43 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1024.28 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 40028605.23 | 0.00 | 40028605.23 | 0.00 | 40028605.23 | 37848132.68 | 4940.34 | 984.03 | 2835.63 | 0.00 |
CORE_BOTTOM | 42880759.48 | 0.00 | 42880759.48 | 0.00 | 42880759.48 | 33990283.35 | 4544.42 | 41.65 | 4173.93 | 438.87 |
CORE_MID | 0.31E+09 | 0.00 | 0.31E+09 | 0.00 | 0.31E+09 | 0.34E+09 | 6007.43 | 32.70 | 2719.88 | 302.40 |
CORE_TOP | 29917701.99 | 0.00 | 29917701.99 | 0.00 | 29917701.99 | 33990283.35 | 6251.88 | 30.17 | 2477.95 | 402.43 |
PERIMETER_BOT_ZN_3 | 5174451.25 | 0.00 | 5174451.25 | 263099.47 | 5437550.73 | 4267819.30 | 5374.86 | 36.16 | 3348.97 | 438.87 |
PERIMETER_BOT_ZN_2 | 5223648.51 | 0.00 | 5223648.51 | 175399.53 | 5399048.04 | 2750345.05 | 3509.31 | 6.70 | 5243.99 | 438.87 |
PERIMETER_BOT_ZN_1 | 7365309.54 | 0.00 | 7365309.54 | 263099.47 | 7628409.02 | 4267912.63 | 3840.74 | 65.38 | 4853.88 | 438.87 |
PERIMETER_BOT_ZN_4 | 6837812.56 | 0.00 | 6837812.56 | 175399.53 | 7013212.09 | 2750345.05 | 3480.29 | 2.67 | 5277.04 | 438.87 |
PERIMETER_MID_ZN_3 | 40204199.43 | 0.00 | 40204199.43 | 617042.04 | 40821241.47 | 42678193.03 | 5831.05 | 36.83 | 2892.12 | 302.40 |
PERIMETER_MID_ZN_2 | 48623264.38 | 0.00 | 48623264.38 | 411361.08 | 49034625.46 | 27503450.52 | 3891.50 | 6.89 | 4861.61 | 1211.40 |
PERIMETER_MID_ZN_1 | 64754708.92 | 0.00 | 64754708.92 | 617042.04 | 65371750.96 | 42679126.28 | 3974.33 | 6.00 | 4779.67 | 302.40 |
PERIMETER_MID_ZN_4 | 49745822.83 | 0.00 | 49745822.83 | 411361.08 | 50157183.90 | 27503450.52 | 3881.70 | 4.06 | 4874.24 | 302.40 |
PERIMETER_TOP_ZN_3 | 4113059.82 | 0.00 | 4113059.82 | 766123.54 | 4879183.36 | 4267819.30 | 5701.65 | 43.58 | 3014.76 | 402.43 |
PERIMETER_TOP_ZN_2 | 4871442.69 | 0.00 | 4871442.69 | 510748.68 | 5382191.36 | 2750345.05 | 3968.29 | 3.19 | 4788.51 | 402.43 |
PERIMETER_TOP_ZN_1 | 6554893.57 | 0.00 | 6554893.57 | 766123.54 | 7321017.11 | 4267912.63 | 4001.21 | 4.50 | 4754.29 | 402.43 |
PERIMETER_TOP_ZN_4 | 5138888.14 | 0.00 | 5138888.14 | 510748.68 | 5649636.81 | 2750345.05 | 3952.60 | 5.32 | 4802.09 | 402.43 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.43E+09 | 0.00 | 0.43E+09 | 0.00 | 0.43E+09 | 10671554.30 | 19.00 | 123.42 | 8617.58 | 2815.33 |
Total Facility | 0.57E+10 | 0.00 | 0.57E+10 | 23998804.81 | 0.57E+10 | 0.50E+10 | 7011.43 | 4396.57 | 8743.92 | 3724.93 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 1.8710 | 0.0000 | 1.8710 | 0.0000 | 1.8710 | 1.2002 | 2123.34 | 984.03 | 2835.63 |
CORE_BOTTOM | 1.8744 | 0.0000 | 1.8744 | 0.0000 | 1.8744 | 1.0778 | 2090.84 | 39.84 | 3812.32 |
CORE_MID | 13.8729 | 0.0000 | 13.8729 | 0.0000 | 13.8729 | 10.7782 | 3304.15 | 32.56 | 2606.29 |
CORE_TOP | 1.3570 | 0.0000 | 1.3570 | 0.0000 | 1.3570 | 1.0778 | 3530.93 | 30.17 | 2381.90 |
PERIMETER_BOT_ZN_3 | 0.2264 | 0.0000 | 0.2264 | 0.0062 | 0.2327 | 0.1353 | 2919.08 | 33.76 | 2990.16 |
PERIMETER_BOT_ZN_2 | 0.2277 | 0.0000 | 0.2277 | 0.0042 | 0.2319 | 0.0872 | 1096.68 | 5.52 | 4840.80 |
PERIMETER_BOT_ZN_1 | 0.3252 | 0.0000 | 0.3252 | 0.0062 | 0.3315 | 0.1353 | 1407.64 | 64.08 | 4471.28 |
PERIMETER_BOT_ZN_4 | 0.2974 | 0.0000 | 0.2974 | 0.0042 | 0.3016 | 0.0872 | 1075.32 | 2.00 | 4865.68 |
PERIMETER_MID_ZN_3 | 1.8176 | 0.0000 | 1.8176 | 0.0146 | 1.8323 | 1.3533 | 3130.27 | 36.47 | 2776.26 |
PERIMETER_MID_ZN_2 | 2.0252 | 0.0000 | 2.0252 | 0.0103 | 2.0356 | 0.8721 | 1218.63 | 4.35 | 3811.01 |
PERIMETER_MID_ZN_1 | 2.9505 | 0.0000 | 2.9505 | 0.0146 | 2.9651 | 1.3533 | 1279.03 | 5.74 | 4658.24 |
PERIMETER_MID_ZN_4 | 2.2406 | 0.0000 | 2.2406 | 0.0098 | 2.2503 | 0.8721 | 1212.19 | 3.05 | 4727.76 |
PERIMETER_TOP_ZN_3 | 0.1868 | 0.0000 | 0.1868 | 0.0182 | 0.2050 | 0.1353 | 2983.03 | 43.27 | 2916.70 |
PERIMETER_TOP_ZN_2 | 0.2217 | 0.0000 | 0.2217 | 0.0121 | 0.2338 | 0.0872 | 1265.68 | 2.03 | 4675.30 |
PERIMETER_TOP_ZN_1 | 0.2994 | 0.0000 | 0.2994 | 0.0182 | 0.3176 | 0.1353 | 1289.77 | 3.63 | 4649.60 |
PERIMETER_TOP_ZN_4 | 0.2323 | 0.0000 | 0.2323 | 0.0121 | 0.2444 | 0.0872 | 1253.81 | 3.92 | 4685.27 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 14.0641 | 0.0000 | 14.0641 | 0.0000 | 14.0641 | 0.3384 | 17.33 | 123.42 | 5802.25 |
Total Facility | 251.4162 | 0.0000 | 251.4162 | 0.5751 | 251.9913 | 158.4706 | 4194.43 | 4383.21 | 5927.99 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 93000080.03 | 0.00 | 93000080.03 | 48026705.38 | 3521.91 | 2.74 | 5235.36 | 438.87 |
VAV_MID WITH REHEAT | 0.70E+09 | 0.00 | 0.70E+09 | 0.48E+09 | 3934.74 | 5.27 | 4819.99 | 302.40 |
VAV_TOP WITH REHEAT | 69726495.89 | 0.00 | 69726495.89 | 48026705.38 | 3990.31 | 2.41 | 4767.28 | 402.43 |
CAV_BAS | 55163451.34 | 0.00 | 55163451.34 | 37848132.68 | 4929.50 | 0.44 | 3830.06 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.60E+09 | 0.00 | 0.60E+09 | 10671554.30 | 19.00 | 0.00 | 8741.00 | 2815.33 |
AIRLOOP DATACENTER BOT | 336664.50 | 0.00 | 336664.50 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3366645.00 | 0.00 | 3366645.00 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 336664.50 | 0.00 | 336664.50 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 4.0672 | 0.0000 | 4.0672 | 1.5229 | 1104.81 | 2.29 | 4835.90 |
VAV_MID WITH REHEAT | 31.8125 | 0.0000 | 31.8125 | 15.2292 | 1243.74 | 3.39 | 4695.87 |
VAV_TOP WITH REHEAT | 3.1658 | 0.0000 | 3.1658 | 1.5229 | 1280.25 | 1.14 | 4661.61 |
CAV_BAS | 2.5784 | 0.0000 | 2.5784 | 1.2002 | 2112.50 | 0.44 | 3830.06 |
AIRLOOP DATACENTER BASEMENT | 19.3818 | 0.0000 | 19.3818 | 0.3384 | 17.33 | 0.00 | 5925.67 |
AIRLOOP DATACENTER BOT | 0.0157 | 0.0000 | 0.0157 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1574 | 0.0000 | 0.1574 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0157 | 0.0000 | 0.0157 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 1.15 | 3798.01 | 0.00 | 0.00 | 0.00 | 1547.11 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.07 | 3204.81 | 0.00 | 0.00 | 0.00 | 1916.60 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.07 | 3153.17 | 0.00 | 0.00 | 0.00 | 2129.90 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 960.78 | 2856.88 | 0.00 | 32.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 123.42 | 8617.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 15.2924 | 6.0861 | 0.0000 | 0.0000 | 0.0000 | 2.3999 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 49.9489 | 0.0000 | 0.0000 | 0.0000 | 23.0193 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 5.0764 | 0.0000 | 0.0000 | 0.0000 | 2.2797 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.6553 | 4.7965 | 0.0000 | 1.1012 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4679 | 19.8429 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0215 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2155 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0215 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1498 |
Defaulted Fields | 1184 |
Fields with Defaults | 3937 |
Autosized Fields | 337 |
Autosizable Fields | 416 |
Autocalculated Fields | 227 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 27588.71 | 297372.03 | 21-MAY-05:00 | 2210375.60 | 15-AUG-14:40 |
Electricity:Building | 17896.79 | 217189.06 | 07-MAY-17:20 | 1104084.83 | 01-DEC-16:20 |
Electricity:Zone:BASEMENT | 640.57 | 14055.89 | 01-JAN-00:10 | 32859.63 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 17896.79 | 217189.06 | 07-MAY-17:20 | 1104084.83 | 01-DEC-16:20 |
InteriorLights:Electricity | 3220.39 | 9932.90 | 16-APR-17:20 | 325713.14 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:BASEMENT | 216.17 | 598.35 | 01-JAN-00:10 | 19402.09 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 3220.39 | 9932.90 | 16-APR-17:20 | 325713.14 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity | 3220.39 | 9932.90 | 16-APR-17:20 | 325713.14 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 216.17 | 598.35 | 01-JAN-00:10 | 19402.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 3220.39 | 9932.90 | 16-APR-17:20 | 325713.14 | 02-JAN-16:50 |
Electricity:Zone:CORE_BOTTOM | 483.75 | 4990.59 | 01-JAN-00:10 | 34631.07 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4837.49 | 49905.77 | 01-JAN-00:10 | 346310.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1941.37 | 5373.60 | 01-JAN-00:10 | 174244.37 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1941.37 | 5373.60 | 01-JAN-00:10 | 174244.37 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 483.75 | 4990.58 | 01-JAN-00:10 | 34631.00 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 194.14 | 537.36 | 01-JAN-00:10 | 17424.44 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 50.45 | 617.00 | 26-MAR-17:10 | 4348.36 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 14.09 | 57.83 | 01-JAN-11:10 | 2187.81 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 14.09 | 57.83 | 01-JAN-11:10 | 2187.81 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 32.43 | 397.62 | 26-MAR-17:10 | 2802.25 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 9.00 | 37.27 | 01-JAN-09:20 | 1409.91 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 9.00 | 37.27 | 01-JAN-09:20 | 1409.91 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 50.20 | 617.01 | 12-MAR-17:10 | 4348.44 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 13.84 | 57.83 | 01-JAN-09:20 | 2187.86 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 13.84 | 57.83 | 01-JAN-09:20 | 2187.86 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 32.43 | 397.61 | 12-MAR-17:10 | 2802.24 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 8.99 | 37.27 | 01-JAN-10:30 | 1409.91 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 8.99 | 37.27 | 01-JAN-10:30 | 1409.91 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 504.23 | 6169.98 | 26-MAR-17:10 | 43483.64 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 140.57 | 578.27 | 01-JAN-10:50 | 21878.12 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 140.57 | 578.27 | 01-JAN-10:50 | 21878.12 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 324.17 | 3976.17 | 26-MAR-17:10 | 28022.51 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 89.81 | 372.66 | 01-JAN-09:20 | 14099.09 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 89.81 | 372.66 | 01-JAN-09:20 | 14099.09 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 501.88 | 6170.07 | 12-MAR-17:10 | 43484.45 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 138.22 | 578.28 | 01-JAN-09:20 | 21878.60 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 138.22 | 578.28 | 01-JAN-09:20 | 21878.60 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 324.07 | 3976.14 | 12-MAR-17:10 | 28022.42 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 89.72 | 372.66 | 01-JAN-10:20 | 14099.09 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 89.72 | 372.66 | 01-JAN-10:20 | 14099.09 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 50.42 | 617.00 | 26-MAR-17:10 | 4348.36 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 14.06 | 57.83 | 01-JAN-10:50 | 2187.81 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 14.06 | 57.83 | 01-JAN-10:50 | 2187.81 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 32.42 | 397.62 | 26-MAR-17:10 | 2802.25 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 8.98 | 37.27 | 01-JAN-09:20 | 1409.91 | 02-JAN-16:40 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 8.98 | 37.27 | 01-JAN-09:20 | 1409.91 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 50.19 | 617.01 | 12-MAR-17:10 | 4348.44 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 13.82 | 57.83 | 01-JAN-09:20 | 2187.86 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 13.82 | 57.83 | 01-JAN-09:20 | 2187.86 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 32.41 | 397.61 | 12-MAR-17:10 | 2802.24 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 8.97 | 37.27 | 01-JAN-10:20 | 1409.91 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 8.97 | 37.27 | 01-JAN-10:20 | 1409.91 | 02-JAN-16:50 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7557.51 | 95212.03 | 01-JAN-00:10 | 385103.08 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 62.65 | 303.90 | 01-JAN-00:10 | 5470.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 62.65 | 303.90 | 01-JAN-00:10 | 5470.56 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 159.04 | 1973.61 | 01-JAN-00:10 | 8244.54 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1590.36 | 19736.13 | 01-JAN-00:10 | 82445.36 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 51.55 | 250.08 | 01-JAN-00:10 | 4501.14 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 51.55 | 250.08 | 01-JAN-00:10 | 4501.14 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 159.04 | 1973.61 | 01-JAN-00:10 | 8244.54 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 5.16 | 25.01 | 01-JAN-00:10 | 450.11 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 14676.40 | 207256.16 | 01-JAN-00:10 | 778371.69 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5334.97 | 88964.76 | 01-JAN-00:10 | 305206.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 289.61 | 4453.23 | 01-JAN-00:10 | 17206.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 2896.13 | 44532.17 | 01-JAN-00:10 | 172065.63 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 289.61 | 4453.22 | 01-JAN-00:10 | 17206.56 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 363.65 | 5591.71 | 01-JAN-00:10 | 21605.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 234.35 | 3603.51 | 01-JAN-00:10 | 13923.42 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 363.66 | 5591.79 | 01-JAN-00:10 | 21605.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 234.35 | 3603.49 | 01-JAN-00:10 | 13923.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 36.37 | 559.17 | 01-JAN-00:10 | 2160.55 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.34 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 36.37 | 559.18 | 01-JAN-00:10 | 2160.58 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 23.44 | 360.35 | 01-JAN-00:10 | 1392.33 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 1874.69 | 3894.14 | 31-JAN-02:00 | 545803.89 | 05-JUL-16:00 |
HeatRejection:Electricity | 531.95 | 65.03 | 06-JAN-08:00 | 88748.60 | 14-MAR-12:50 |
General:HeatRejection:Electricity | 531.95 | 65.03 | 06-JAN-08:00 | 88748.60 | 14-MAR-12:50 |
Electricity:HVAC | 4952.35 | 54378.83 | 30-SEP-23:00 | 487703.30 | 03-AUG-15:30 |
ExteriorEquipment:Electricity | 2566.60 | 20217.42 | 01-JAN-00:10 | 233439.18 | 01-NOV-07:20 |
Transformer:ExteriorEquipment:Electricity | 55.01 | 979.82 | 01-JAN-00:10 | 3454.84 | 01-DEC-16:30 |
ElectricityPurchased:Facility | 27588.71 | 297372.03 | 21-MAY-05:00 | 2210375.60 | 15-AUG-14:40 |
ElectricityPurchased:Plant | 27588.71 | 297372.03 | 21-MAY-05:00 | 2210375.60 | 15-AUG-14:40 |
Cogeneration:ElectricityPurchased | 27588.71 | 297372.03 | 21-MAY-05:00 | 2210375.60 | 15-AUG-14:40 |
General:Cogeneration:ElectricityPurchased | 27588.71 | 297372.03 | 21-MAY-05:00 | 2210375.60 | 15-AUG-14:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 27588.71 | 297372.03 | 21-MAY-05:00 | 2210375.60 | 15-AUG-14:40 |
ElectricityNet:Plant | 27588.71 | 297372.03 | 21-MAY-05:00 | 2210375.60 | 15-AUG-14:40 |
Cogeneration:ElectricityNet | 27588.71 | 297372.03 | 21-MAY-05:00 | 2210375.60 | 15-AUG-14:40 |
General:Cogeneration:ElectricityNet | 27588.71 | 297372.03 | 21-MAY-05:00 | 2210375.60 | 15-AUG-14:40 |
Fans:Electricity | 2449.74 | 47989.84 | 01-JAN-16:40 | 285019.87 | 09-AUG-15:30 |
General:Fans:Electricity | 2449.74 | 47989.84 | 01-JAN-16:40 | 285019.87 | 09-AUG-15:30 |
ExteriorLights:Electricity | 353.28 | 0.00 | 01-JAN-08:00 | 40855.88 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 353.28 | 0.00 | 01-JAN-08:00 | 40855.88 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 2505.76 | 19200.00 | 01-JAN-00:10 | 229608.34 | 02-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 39.11 | 0.00 | 01-JAN-00:10 | 5613.48 | 02-JAN-07:10 |
General:HeatRecovery:Electricity | 39.11 | 0.00 | 01-JAN-00:10 | 5613.48 | 02-JAN-07:10 |
Cooling:Electricity | 1481.93 | 1755.22 | 14-JAN-18:00 | 535338.99 | 15-AUG-14:40 |
General:Cooling:Electricity | 1481.93 | 1755.22 | 14-JAN-18:00 | 535338.99 | 15-AUG-14:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1464.84 | 0.00 | 11-JAN-13:10 | 100000.00 | 14-FEB-22:10 |
General:Humidifier:Electricity | 1464.84 | 0.00 | 11-JAN-13:10 | 100000.00 | 14-FEB-22:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:Electricity | 459.84 | 0.00 | 01-JAN-00:10 | 56293.71 | 13-FEB-13:00 |
Water Heater:WaterSystems:Electricity | 459.84 | 0.00 | 01-JAN-00:10 | 56293.71 | 13-FEB-13:00 |
Pumps:Electricity | 344.62 | 3823.65 | 01-JAN-00:40 | 53027.04 | 21-SEP-13:10 |
General:Pumps:Electricity | 344.62 | 3823.65 | 01-JAN-00:40 | 53027.04 | 21-SEP-13:10 |
WIRED_LTG_ELECTRICITY | 90.49 | 0.00 | 01-JAN-00:10 | 9152.54 | 02-JAN-17:00 |
WIRED_INT_EQUIP | 5334.97 | 88964.76 | 31-MAR-23:10 | 305206.10 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1423.04 | 0.00 | 01-JAN-00:40 | 1657705.99 | 02-JAN-05:10 |
NaturalGas:Plant | 1423.04 | 0.00 | 01-JAN-00:40 | 1657705.99 | 02-JAN-05:10 |
Heating:NaturalGas | 1423.04 | 0.00 | 01-JAN-00:40 | 1657705.99 | 02-JAN-05:10 |
Boiler:Heating:NaturalGas | 1423.04 | 0.00 | 01-JAN-00:40 | 1657705.99 | 02-JAN-05:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 8873.75 | 3605.00 | 11-JAN-07:30 | 3308511.50 | 15-AUG-14:40 |
PlantLoopCoolingDemand:HVAC | 8873.75 | 3605.00 | 11-JAN-07:30 | 3308511.50 | 15-AUG-14:40 |
CoolingCoils:PlantLoopCoolingDemand | 8873.75 | 3605.00 | 11-JAN-07:30 | 3308511.50 | 15-AUG-14:40 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 6278.83 | 0.00 | 11-MAR-01:00 | 0.00 | 04-AUG-12:50 |
Water:HVAC | 544.92 | 0.00 | 11-JAN-13:10 | 0.00 | 22-FEB-04:10 |
Humidifier:Water | 544.92 | 0.00 | 11-JAN-13:10 | 0.00 | 22-FEB-04:10 |
General:Humidifier:Water | 544.92 | 0.00 | 11-JAN-13:10 | 0.00 | 22-FEB-04:10 |
MainsWater:Facility | 6278.83 | 0.00 | 11-MAR-01:00 | 0.00 | 04-AUG-12:50 |
MainsWater:HVAC | 544.92 | 0.00 | 11-JAN-13:10 | 0.00 | 22-FEB-04:10 |
Humidifier:MainsWater | 544.92 | 0.00 | 11-JAN-13:10 | 0.00 | 22-FEB-04:10 |
General:Humidifier:MainsWater | 544.92 | 0.00 | 11-JAN-13:10 | 0.00 | 22-FEB-04:10 |
Water:Plant | 5733.91 | 0.00 | 01-JAN-00:10 | 0.00 | 04-AUG-12:50 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 5733.91 | 0.00 | 01-JAN-00:10 | 0.00 | 04-AUG-12:50 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 3453.74 | 0.00 | 01-JAN-00:10 | 0.00 | 04-AUG-12:50 |
General:HeatRejection:Water | 3453.74 | 0.00 | 01-JAN-00:10 | 0.00 | 04-AUG-12:50 |
HeatRejection:MainsWater | 3453.74 | 0.00 | 01-JAN-00:10 | 0.00 | 04-AUG-12:50 |
General:HeatRejection:MainsWater | 3453.74 | 0.00 | 01-JAN-00:10 | 0.00 | 04-AUG-12:50 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 44970.91 | 95690.58 | 29-JAN-04:50 | 12422598.95 | 15-AUG-14:40 |
EnergyTransfer:Building | 18311.45 | 88622.46 | 21-JAN-18:10 | 1727001.75 | 09-AUG-15:30 |
EnergyTransfer:Zone:BASEMENT | 573.64 | 0.00 | 01-JAN-00:10 | 106993.19 | 13-JUN-06:10 |
Heating:EnergyTransfer | 727.72 | 0.00 | 01-FEB-00:10 | 1205931.54 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer | 727.72 | 0.00 | 01-FEB-00:10 | 1205931.54 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer | 17583.73 | 85646.53 | 30-JAN-05:40 | 1727001.75 | 09-AUG-15:30 |
Cooling:EnergyTransfer:Zone:BASEMENT | 573.64 | 0.00 | 01-JAN-00:10 | 106993.19 | 13-JUN-06:10 |
General:Cooling:EnergyTransfer | 17583.73 | 85646.53 | 30-JAN-05:40 | 1727001.75 | 09-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 573.64 | 0.00 | 01-JAN-00:10 | 106993.19 | 13-JUN-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 623.15 | 0.00 | 01-JAN-00:10 | 63976.85 | 15-AUG-15:00 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 623.15 | 0.00 | 01-JAN-00:10 | 63976.85 | 15-AUG-15:00 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 623.15 | 0.00 | 01-JAN-00:10 | 63976.85 | 15-AUG-15:00 |
EnergyTransfer:Zone:CORE_MID | 4185.96 | 0.00 | 01-JAN-00:40 | 436470.63 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 8.83 | 0.00 | 01-JAN-00:10 | 436470.63 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 8.83 | 0.00 | 01-JAN-00:10 | 436470.63 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4177.14 | 0.00 | 01-JAN-00:40 | 428336.34 | 21-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4177.14 | 0.00 | 01-JAN-00:40 | 428336.34 | 21-JUL-14:00 |
EnergyTransfer:Zone:CORE_TOP | 384.65 | 0.00 | 01-JAN-00:40 | 69924.19 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 16.47 | 0.00 | 01-JAN-00:40 | 69924.19 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 16.47 | 0.00 | 01-JAN-00:40 | 69924.19 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 368.18 | 0.00 | 01-JAN-00:20 | 50053.05 | 21-JUL-14:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 368.18 | 0.00 | 01-JAN-00:20 | 50053.05 | 21-JUL-14:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 68.79 | 0.00 | 01-JAN-00:10 | 12406.78 | 21-JUL-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 1.03 | 0.00 | 01-JAN-00:10 | 7546.99 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 1.03 | 0.00 | 01-JAN-00:10 | 7546.99 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 67.76 | 0.00 | 01-JAN-00:10 | 12406.78 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 67.76 | 0.00 | 01-JAN-00:10 | 12406.78 | 21-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 65.99 | 0.00 | 01-JAN-00:10 | 15294.78 | 30-JUN-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.94 | 0.00 | 01-JAN-00:10 | 5561.65 | 07-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.94 | 0.00 | 01-JAN-00:10 | 5561.65 | 07-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 65.05 | 0.00 | 01-JAN-00:10 | 15294.78 | 30-JUN-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 65.05 | 0.00 | 01-JAN-00:10 | 15294.78 | 30-JUN-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 101.01 | 0.00 | 01-JAN-00:10 | 21482.50 | 31-OCT-13:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 1.82 | 0.00 | 01-JAN-00:10 | 10040.69 | 07-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 1.82 | 0.00 | 01-JAN-00:10 | 10040.69 | 07-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 99.19 | 0.00 | 01-JAN-00:10 | 21482.50 | 31-OCT-13:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 99.19 | 0.00 | 01-JAN-00:10 | 21482.50 | 31-OCT-13:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 94.99 | 0.00 | 01-JAN-00:10 | 18516.27 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.11 | 0.00 | 01-JAN-00:10 | 2982.21 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.11 | 0.00 | 01-JAN-00:10 | 2982.21 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 94.88 | 0.00 | 01-JAN-00:10 | 18516.27 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 94.88 | 0.00 | 01-JAN-00:10 | 18516.27 | 10-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 583.03 | 0.00 | 01-JAN-00:40 | 128010.27 | 06-FEB-04:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 155.65 | 0.00 | 01-JAN-00:40 | 128010.27 | 06-FEB-04:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 155.65 | 0.00 | 01-JAN-00:40 | 128010.27 | 06-FEB-04:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 427.38 | 0.00 | 01-JAN-00:20 | 100771.34 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 427.38 | 0.00 | 01-JAN-00:20 | 100771.34 | 21-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 599.78 | 0.00 | 01-JAN-00:40 | 157094.18 | 13-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 89.46 | 0.00 | 01-JAN-00:40 | 117400.97 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 89.46 | 0.00 | 01-JAN-00:40 | 117400.97 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 510.32 | 0.00 | 01-JAN-00:20 | 157094.18 | 13-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 510.32 | 0.00 | 01-JAN-00:20 | 157094.18 | 13-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 901.44 | 0.00 | 01-JAN-00:40 | 222502.40 | 31-OCT-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 95.43 | 0.00 | 01-JAN-00:40 | 166112.93 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 95.43 | 0.00 | 01-JAN-00:40 | 166112.93 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 806.01 | 0.00 | 01-JAN-00:20 | 222502.40 | 31-OCT-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 806.01 | 0.00 | 01-JAN-00:20 | 222502.40 | 31-OCT-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 622.57 | 0.00 | 01-JAN-00:40 | 162925.87 | 04-AUG-16:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 70.28 | 0.00 | 01-JAN-00:40 | 109335.96 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 70.28 | 0.00 | 01-JAN-00:40 | 109335.96 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 552.29 | 0.00 | 01-JAN-00:20 | 162925.87 | 04-AUG-16:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 552.29 | 0.00 | 01-JAN-00:20 | 162925.87 | 04-AUG-16:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 73.79 | 0.00 | 01-JAN-00:40 | 15015.79 | 06-FEB-04:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 34.40 | 0.00 | 01-JAN-00:40 | 15015.79 | 06-FEB-04:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 34.40 | 0.00 | 01-JAN-00:40 | 15015.79 | 06-FEB-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 39.39 | 0.00 | 01-JAN-00:10 | 11071.90 | 21-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 39.39 | 0.00 | 01-JAN-00:10 | 11071.90 | 21-JUL-13:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 67.51 | 0.00 | 01-JAN-00:40 | 17406.07 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 19.70 | 0.00 | 01-JAN-00:40 | 17406.07 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 19.70 | 0.00 | 01-JAN-00:40 | 17406.07 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 47.81 | 0.00 | 01-JAN-00:20 | 15277.14 | 30-JUN-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 47.81 | 0.00 | 01-JAN-00:20 | 15277.14 | 30-JUN-09:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 97.89 | 0.00 | 01-JAN-00:40 | 22602.94 | 31-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 23.59 | 0.00 | 01-JAN-00:40 | 21088.79 | 13-FEB-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 23.59 | 0.00 | 01-JAN-00:40 | 21088.79 | 13-FEB-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 74.30 | 0.00 | 01-JAN-00:20 | 22602.94 | 31-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 74.30 | 0.00 | 01-JAN-00:20 | 22602.94 | 31-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 67.99 | 0.00 | 01-JAN-00:40 | 16766.79 | 04-AUG-16:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 15.76 | 0.00 | 01-JAN-00:40 | 16371.68 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 15.76 | 0.00 | 01-JAN-00:40 | 16371.68 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 52.23 | 0.00 | 01-JAN-00:20 | 16766.79 | 04-AUG-16:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 52.23 | 0.00 | 01-JAN-00:20 | 16766.79 | 04-AUG-16:50 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 60.49 | 0.00 | 01-JAN-00:10 | 11505.99 | 31-JUL-08:40 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 3.27 | 0.00 | 01-JAN-00:10 | 4552.98 | 10-DEC-12:40 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 3.27 | 0.00 | 01-JAN-00:10 | 4552.98 | 10-DEC-12:40 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 57.22 | 0.00 | 01-JAN-00:10 | 11505.99 | 31-JUL-08:40 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 57.22 | 0.00 | 01-JAN-00:10 | 11505.99 | 31-JUL-08:40 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 468.72 | 0.00 | 01-JAN-00:40 | 161256.42 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 133.45 | 0.00 | 01-JAN-00:40 | 161256.42 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 133.45 | 0.00 | 01-JAN-00:40 | 161256.42 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 335.27 | 0.00 | 01-JAN-00:10 | 73187.52 | 21-JUL-12:10 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 335.27 | 0.00 | 01-JAN-00:10 | 73187.52 | 21-JUL-12:10 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 100.60 | 0.00 | 01-JAN-00:40 | 29023.33 | 06-FEB-05:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 51.27 | 0.00 | 01-JAN-00:40 | 29023.33 | 06-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 51.27 | 0.00 | 01-JAN-00:40 | 29023.33 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 49.33 | 0.00 | 01-JAN-00:10 | 19110.72 | 21-JUL-12:10 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 49.33 | 0.00 | 01-JAN-00:10 | 19110.72 | 21-JUL-12:10 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 136.55 | 265.36 | 30-JAN-06:00 | 8302.43 | 02-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 136.55 | 265.36 | 30-JAN-06:00 | 8302.43 | 02-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 136.55 | 265.36 | 30-JAN-06:00 | 8302.43 | 02-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1160.76 | 1.72 | 07-JAN-17:00 | 79593.01 | 02-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 5.35 | 0.00 | 03-JAN-07:30 | 5598.81 | 03-JAN-01:20 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 5.35 | 0.00 | 03-JAN-07:30 | 5598.81 | 03-JAN-01:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1155.41 | 0.00 | 01-JAN-00:10 | 79593.01 | 02-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1155.41 | 0.00 | 01-JAN-00:10 | 79593.01 | 02-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 106.19 | 0.08 | 26-FEB-02:20 | 8012.39 | 02-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.90 | 0.00 | 02-JAN-16:40 | 599.25 | 24-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.90 | 0.00 | 02-JAN-16:40 | 599.25 | 24-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 105.29 | 0.00 | 01-JAN-00:10 | 8012.39 | 02-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 105.29 | 0.00 | 01-JAN-00:10 | 8012.39 | 02-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7165.95 | 85336.94 | 30-JAN-05:00 | 376110.93 | 15-AUG-17:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7165.95 | 85336.94 | 30-JAN-05:00 | 376110.93 | 15-AUG-17:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7165.95 | 85336.94 | 30-JAN-05:00 | 376110.93 | 15-AUG-17:00 |
PlantLoopHeatingDemand:Facility | 1481.38 | 0.00 | 01-JAN-00:40 | 1316775.98 | 02-JAN-06:20 |
PlantLoopHeatingDemand:Plant | 454.52 | 0.00 | 01-JAN-00:10 | 56067.89 | 15-FEB-12:20 |
WaterSystems:PlantLoopHeatingDemand | 454.52 | 0.00 | 01-JAN-00:10 | 56067.89 | 15-FEB-12:20 |
General:WaterSystems:PlantLoopHeatingDemand | 454.52 | 0.00 | 01-JAN-00:10 | 56067.89 | 15-FEB-12:20 |
EnergyTransfer:HVAC | 10683.99 | 3329.08 | 01-JAN-04:00 | 3139280.40 | 15-AUG-14:40 |
HeatingCoils:EnergyTransfer | 1026.86 | 0.00 | 01-JAN-00:40 | 1310092.62 | 02-JAN-06:20 |
PlantLoopHeatingDemand:HVAC | 1026.86 | 0.00 | 01-JAN-00:40 | 1310092.62 | 02-JAN-06:20 |
HeatingCoils:PlantLoopHeatingDemand | 1026.86 | 0.00 | 01-JAN-00:40 | 1310092.62 | 02-JAN-06:20 |
CoolingCoils:EnergyTransfer | 7930.10 | 1636.22 | 11-JAN-07:30 | 3139280.40 | 15-AUG-14:40 |
HeatRecoveryForHeating:EnergyTransfer | 1614.90 | 0.00 | 01-JAN-00:10 | 685579.07 | 11-DEC-20:00 |
HeatRecoveryForCooling:EnergyTransfer | 112.12 | 0.00 | 01-JAN-00:10 | 338764.08 | 15-JUL-14:00 |
EnergyTransfer:Plant | 15975.47 | 0.00 | 01-JAN-00:40 | 7760481.62 | 15-AUG-14:40 |
LoopToLoop:EnergyTransfer | 4654.34 | 0.00 | 01-JAN-00:10 | 2508176.00 | 15-AUG-14:40 |
WaterSystems:EnergyTransfer | 454.52 | 0.00 | 01-JAN-00:10 | 56067.89 | 15-FEB-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 454.52 | 0.00 | 01-JAN-00:10 | 56067.89 | 15-FEB-12:20 |
Boilers:EnergyTransfer | 1021.59 | 0.00 | 01-JAN-00:40 | 1379989.35 | 02-JAN-05:10 |
Chillers:EnergyTransfer | 4653.37 | 0.00 | 01-JAN-00:10 | 2438872.45 | 05-JUL-16:00 |
HeatRejection:EnergyTransfer | 5191.65 | 0.00 | 01-JAN-00:10 | 2810030.94 | 05-JUL-16:00 |
General:HeatRejection:EnergyTransfer | 5191.65 | 0.00 | 01-JAN-00:10 | 2810030.94 | 05-JUL-16:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 0.000 | -573.627 | 0.000 | 0.000 | 89.268 | 216.171 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -156.209 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -623.149 | 0.000 | 0.000 | 83.507 | 194.137 | 289.614 | 0.000 | 0.000 | 0.000 | 55.891 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
CORE_MID | 0.000 | 0.000 | 8.827 | -4177.120 | 0.000 | 0.000 | 856.752 | 1941.366 | 2896.128 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1525.954 |
CORE_TOP | 0.000 | 0.000 | 16.472 | -368.180 | 0.000 | 0.000 | 88.699 | 194.137 | 289.613 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -220.741 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 1.031 | -67.755 | 0.000 | 0.000 | 10.960 | 14.088 | 36.365 | 27.603 | 0.000 | 0.022 | 56.878 | 0.000 | -74.306 | 0.000 | -4.887 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.940 | -65.054 | 0.000 | 0.000 | 7.133 | 8.997 | 23.435 | 53.452 | 0.000 | 0.016 | 19.691 | 0.000 | -45.411 | 0.000 | -3.199 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 1.824 | -99.187 | 0.000 | 0.000 | 10.899 | 13.838 | 36.366 | 99.624 | 0.000 | 0.022 | 8.738 | 0.000 | -67.268 | 0.000 | -4.855 | 0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.115 | -94.880 | 0.000 | 0.000 | 6.960 | 8.990 | 23.435 | 52.612 | 0.000 | 0.014 | 58.144 | 0.000 | -51.890 | 0.000 | -3.500 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 155.654 | -427.375 | 0.000 | 0.000 | 114.300 | 140.574 | 363.654 | 287.227 | 0.000 | 0.514 | 137.319 | 0.000 | -669.686 | 0.000 | -102.181 | -0.006 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 89.460 | -510.317 | 0.000 | 0.000 | 54.085 | 89.813 | 234.352 | 537.699 | 0.000 | 0.346 | 0.021 | 0.000 | -420.681 | 0.000 | -68.831 | -5.927 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 95.431 | -806.000 | 0.000 | 0.000 | 111.432 | 138.217 | 363.660 | 995.611 | 0.000 | 0.475 | 0.003 | 0.000 | -642.770 | 0.000 | -107.350 | -148.706 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 70.275 | -552.288 | 0.000 | 0.000 | 73.828 | 89.721 | 234.351 | 538.651 | 0.000 | 0.329 | 66.541 | 0.000 | -450.485 | 0.000 | -70.923 | -0.004 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 34.403 | -39.386 | 0.000 | 0.000 | 11.586 | 14.055 | 36.365 | 29.209 | 0.000 | 0.058 | 0.000 | 0.000 | -63.431 | 0.000 | -12.077 | -10.783 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 19.701 | -47.809 | 0.000 | 0.000 | 7.405 | 8.980 | 23.435 | 54.120 | 0.000 | 0.040 | 0.000 | 0.000 | -40.024 | 0.000 | -8.168 | -17.680 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 23.586 | -74.299 | 0.000 | 0.000 | 11.321 | 13.821 | 36.366 | 100.241 | 0.000 | 0.056 | 0.000 | 0.000 | -60.844 | 0.000 | -12.636 | -37.612 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 15.756 | -52.232 | 0.000 | 0.000 | 7.471 | 8.971 | 23.435 | 54.064 | 0.000 | 0.039 | 0.000 | 0.000 | -43.029 | 0.000 | -8.426 | -6.048 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -136.551 | 0.000 | 0.000 | 0.950 | 5.155 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -23.434 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 5.353 | -1155.409 | 0.000 | 0.000 | 9.518 | 51.551 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -449.819 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.898 | -105.292 | 0.000 | 0.000 | 0.956 | 5.155 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -55.597 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7165.947 | 0.000 | 0.000 | 20.485 | 62.653 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -412.048 |
GROUNDFLOOR_PLENUM | 3.268 | -57.220 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.038 | 64.358 | 0.000 | 0.000 | 0.000 | -10.444 | 0.000 |
MIDFLOOR_PLENUM | 133.456 | -335.268 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.742 | 375.786 | 0.000 | 0.000 | 0.000 | -174.716 | -0.002 |
TOPFLOOR_PLENUM | 51.274 | -49.326 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.048 | 16.561 | 0.000 | 0.000 | 0.000 | -18.558 | -0.000 |
Total Facility | 187.998 | -441.813 | 539.726 | -17141.856 | 0.000 | 0.000 | 1577.514 | 3220.391 | 14676.396 | 2830.112 | 0.000 | 2.757 | 859.932 | 0.000 | -2629.825 | 0.000 | -610.750 | -3070.571 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 06-JUL-06:11 | 0.00 | 0.00 | 0.00 | -125183.97 | 0.00 | 0.00 | 1388.37 | 6467.36 | 13457.54 | 0.00 | 0.00 | 0.00 | 103870.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 29-AUG-04:13 | 0.00 | 0.00 | 0.00 | -99458.82 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.65 | 0.00 | 0.00 | 0.00 | 92983.81 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 25-JUL-04:12 | 0.00 | 0.00 | 0.00 | -827296.79 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 762546.96 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 19-JUN-04:12 | 0.00 | 0.00 | 0.00 | -81589.50 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 75114.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 06-AUG-15:41 | 0.00 | 0.00 | 0.00 | -16430.29 | 0.00 | 0.00 | 42.59 | 57.83 | 720.18 | 5523.69 | 0.00 | 14.13 | 10071.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-JUL-08:31 | 0.00 | 0.00 | 0.00 | -26281.48 | 0.00 | 0.00 | 18.55 | 37.27 | 464.11 | 20900.26 | 0.00 | 0.00 | 4954.27 | 0.00 | -0.00 | 0.00 | -92.98 | 0.00 |
PERIMETER_BOT_ZN_1 | 10-SEP-12:31 | 0.00 | 0.00 | 0.00 | -28982.93 | 0.00 | 0.00 | 32.46 | 57.83 | 720.19 | 26731.28 | 0.00 | 0.00 | 1610.35 | 0.00 | -0.00 | 0.00 | -169.19 | 0.00 |
PERIMETER_BOT_ZN_4 | 04-SEP-16:51 | 0.00 | 0.00 | 0.00 | -30548.84 | 0.00 | 0.00 | 18.71 | 37.27 | 464.11 | 17618.12 | 0.00 | 0.00 | 12515.95 | 0.00 | -0.00 | 0.00 | -105.32 | 0.00 |
PERIMETER_MID_ZN_3 | 16-JUL-14:32 | 0.00 | 0.00 | 0.00 | -134446.08 | 0.00 | 0.00 | 431.59 | 578.27 | 7201.84 | 53334.34 | 0.00 | 820.94 | 72079.10 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 04-JUL-09:11 | 0.00 | 0.00 | 0.00 | -285676.54 | 0.00 | 0.00 | 170.76 | 372.66 | 4641.14 | 185285.22 | 0.00 | 0.00 | 97117.19 | 0.00 | -0.00 | 0.00 | -1910.42 | 0.00 |
PERIMETER_MID_ZN_1 | 10-SEP-12:21 | 0.00 | 0.00 | 0.00 | -290095.82 | 0.00 | 0.00 | 317.92 | 578.28 | 7201.95 | 267095.52 | 0.00 | 0.00 | 18913.08 | 0.00 | -0.00 | 0.00 | -4010.92 | 0.00 |
PERIMETER_MID_ZN_4 | 11-JUN-16:41 | 0.00 | 0.00 | 0.00 | -297941.29 | 0.00 | 0.00 | 167.89 | 372.66 | 4641.11 | 189279.00 | 0.00 | 0.00 | 104987.01 | 0.00 | -0.00 | 0.00 | -1506.39 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-JUL-14:32 | 0.00 | 0.00 | 0.00 | -17288.49 | 0.00 | 0.00 | 41.05 | 57.83 | 720.18 | 5181.21 | 0.00 | 87.23 | 11201.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 04-JUL-09:22 | 0.00 | 0.00 | 0.00 | -25431.59 | 0.00 | 0.00 | 17.42 | 37.27 | 464.11 | 17800.30 | 0.00 | 0.00 | 7291.77 | 0.00 | -0.00 | 0.00 | -179.27 | 0.00 |
PERIMETER_TOP_ZN_1 | 04-SEP-15:02 | 0.00 | 0.00 | 0.00 | -29122.06 | 0.00 | 0.00 | 34.85 | 57.83 | 720.19 | 14113.70 | 0.00 | 0.00 | 14659.80 | 0.00 | -0.00 | 0.00 | -464.31 | 0.00 |
PERIMETER_TOP_ZN_4 | 18-JUN-17:01 | 0.00 | 0.00 | 0.00 | -30339.85 | 0.00 | 0.00 | 0.00 | 37.27 | 360.35 | 15985.15 | 0.00 | 0.00 | 14234.70 | 0.00 | -0.00 | 0.00 | -277.61 | 0.00 |
DATACENTER_BOT_ZN_6 | 02-AUG-18:40 | 0.00 | 0.00 | 0.00 | -8302.14 | 0.00 | 0.00 | 10.62 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 347.06 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 02-AUG-18:40 | 0.00 | 0.00 | 0.00 | -79590.25 | 0.00 | 0.00 | 106.16 | 1500.36 | 77944.22 | 0.00 | 0.00 | 0.00 | 39.50 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 02-AUG-18:40 | 0.00 | 0.00 | 0.00 | -8012.12 | 0.00 | 0.00 | 10.62 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 57.04 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 15-AUG-16:51 | 0.00 | 0.00 | 0.00 | -381830.94 | 0.00 | 0.00 | 672.45 | 3039.18 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1513.21 |
GROUNDFLOOR_PLENUM | 31-JUL-05:10 | 0.00 | -14459.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14493.10 | 0.00 | -0.00 | 0.00 | -33.16 | 0.00 |
MIDFLOOR_PLENUM | 04-MAR-05:01 | 0.00 | -99421.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111735.12 | 0.00 | -0.00 | 0.00 | -12313.54 | 0.00 |
TOPFLOOR_PLENUM | 21-JUL-12:10 | 0.00 | -19110.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.95 | 19023.77 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 11-AUG-05:03 | 0.00 | -23273.70 | 0.00 | -1799216.12 | 0.00 | 0.00 | 15708.71 | 10917.52 | 616289.16 | 0.00 | 0.00 | 0.00 | 1258471.35 | 0.00 | -76534.48 | 0.00 | -2362.44 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-04:01 | 0.00 | 0.00 | 506135.43 | 0.00 | 0.00 | 0.00 | 0.00 | 5373.60 | 59376.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -570885.26 |
CORE_TOP | 02-JAN-04:01 | 0.00 | 0.00 | 79949.97 | 0.00 | 0.00 | 0.00 | 0.00 | 537.36 | 5937.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -86424.95 |
PERIMETER_BOT_ZN_3 | 06-FEB-05:01 | 0.00 | 0.00 | 12632.78 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7414.36 | 0.00 | -926.90 | -5104.55 |
PERIMETER_BOT_ZN_2 | 07-FEB-05:01 | 0.00 | 0.00 | 12471.10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4849.27 | 0.00 | -634.24 | -7511.54 |
PERIMETER_BOT_ZN_1 | 06-FEB-04:01 | 0.00 | 0.00 | 18808.94 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -7188.36 | 0.00 | -859.50 | -11574.12 |
PERIMETER_BOT_ZN_4 | 06-FEB-05:01 | 0.00 | 0.00 | 9536.45 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5124.76 | 0.00 | -638.14 | -4297.49 |
PERIMETER_MID_ZN_3 | 06-FEB-04:01 | 0.00 | 0.00 | 136691.93 | 0.00 | 0.00 | 0.00 | 0.00 | 674.71 | 7455.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -67055.59 | 0.00 | -18671.44 | -59095.22 |
PERIMETER_MID_ZN_2 | 13-FEB-04:01 | 0.00 | 0.00 | 186611.60 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -34831.77 | 0.00 | -18273.72 | -138745.60 |
PERIMETER_MID_ZN_1 | 13-FEB-04:01 | 0.00 | 0.00 | 219406.34 | 0.00 | 0.00 | 0.00 | 0.00 | 674.72 | 7455.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -54791.46 | 0.00 | -27268.08 | -145477.25 |
PERIMETER_MID_ZN_4 | 06-FEB-04:01 | 0.00 | 0.00 | 185989.79 | 0.00 | 0.00 | 0.00 | 0.00 | 434.81 | 4804.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -45477.52 | 0.00 | -12749.08 | -133002.65 |
PERIMETER_TOP_ZN_3 | 06-FEB-02:52 | 0.00 | 0.00 | 16526.15 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6187.20 | 0.00 | -2669.42 | -8482.56 |
PERIMETER_TOP_ZN_2 | 06-FEB-02:52 | 0.00 | 0.00 | 21774.75 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3987.60 | 0.00 | -1834.93 | -16476.16 |
PERIMETER_TOP_ZN_1 | 06-FEB-03:32 | 0.00 | 0.00 | 25040.52 | 0.00 | 0.00 | 0.00 | 0.00 | 67.47 | 745.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6371.92 | 0.00 | -2384.51 | -17097.14 |
PERIMETER_TOP_ZN_4 | 06-FEB-02:52 | 0.00 | 0.00 | 22861.55 | 0.00 | 0.00 | 0.00 | 0.00 | 43.48 | 480.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4223.28 | 0.00 | -1870.39 | -17291.83 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 03-JAN-01:20 | 0.00 | 0.00 | 5598.81 | 0.00 | 0.00 | 0.00 | 0.00 | 250.08 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25334.94 |
DATACENTER_TOP_ZN_6 | 24-JAN-00:10 | 0.00 | 0.00 | 599.25 | 0.00 | 0.00 | 0.00 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2572.86 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 14-DEC-06:02 | 12068.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -94.26 | -11974.02 |
MIDFLOOR_PLENUM | 02-JAN-06:12 | 184438.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2402.95 | -182035.14 |
TOPFLOOR_PLENUM | 06-FEB-05:12 | 30327.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3546.48 | -26780.72 |
Total Facility | 02-JAN-05:21 | 21877.34 | 108857.57 | 1292737.72 | -108857.57 | 0.00 | 0.00 | 0.00 | 10917.52 | 232425.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -152023.86 | 0.00 | -35436.33 | -1370497.64 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 11.4016 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.8638 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 109.2333 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 92.1071 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 11.1922 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 10.0066 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.6453 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.6453 | 0.2126 | 1.0000 | Not calculated | 1.2002 | 0.2126 | ||
AIRLOOP DATACENTER BASEMENT | 25.1531 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 25.1532 | 0.0135 | 1.0000 | Not calculated | 0.3384 | 0.0135 | ||
AIRLOOP DATACENTER BOT | 0.5023 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5023 | 0.0311 | 1.0000 | Not calculated | 0.0156 | 0.0311 | ||
AIRLOOP DATACENTER MID | 4.8164 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.8164 | 0.0325 | 1.0000 | Not calculated | 0.1563 | 0.0325 | ||
AIRLOOP DATACENTER TOP | 0.4896 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4896 | 0.0319 | 1.0000 | Not calculated | 0.0156 | 0.0319 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.7008 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.0785 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 54.6167 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 30.1980 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.5961 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.1104 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 0.0000 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 0.0000 | 1.0000 | 1.0000 | Not calculated | 1.2002 | |||
AIRLOOP DATACENTER BASEMENT | 25.1531 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 25.1531 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0135 | ||
AIRLOOP DATACENTER BOT | 0.5023 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5023 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0311 | ||
AIRLOOP DATACENTER MID | 4.8164 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.8164 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0325 | ||
AIRLOOP DATACENTER TOP | 0.4896 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4896 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0319 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 5.6453 | 5.6453 | 0.0000 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.9657 | 5.9657 | 1.9448 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 56.1620 | 56.1620 | 19.0389 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.5698 | 5.5698 | 1.9494 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9891 | 0.9891 | 0.2443 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3209 | 1.3209 | 0.2642 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5193 | 1.5193 | 0.3039 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6066 | 1.6066 | 0.3213 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.2337 | 9.2337 | 2.3915 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.0548 | 14.0548 | 2.8110 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 15.0487 | 15.0487 | 3.0097 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.7341 | 14.7341 | 2.9468 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0411 | 1.0411 | 0.2447 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4159 | 1.4159 | 0.2832 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6147 | 1.6147 | 0.3229 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5506 | 1.5506 | 0.3101 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5023 | 0.5023 | 0.5023 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.8164 | 4.8164 | 4.8164 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4896 | 0.4896 | 0.4896 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 25.1531 | 25.1531 | 25.1531 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 11.4016 | 9.8638 | 11.4016 | 3.0785 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 109.2333 | 92.1071 | 109.2333 | 30.1980 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 11.1922 | 10.0066 | 11.1922 | 3.1104 | 0.0000 | 1.0000 |
CAV_BAS | 5.6453 | 5.6453 | 5.6453 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 25.1531 | 25.1532 | 25.1531 | 25.1531 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5023 | 0.5023 | 0.5023 | 0.5023 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.8164 | 4.8164 | 4.8164 | 4.8164 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4896 | 0.4896 | 0.4896 | 0.4896 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:VAV:NOREHEAT | 0.0000 | 0.0000 | 0.0000 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9828 | 2.9828 | 1.9448 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 28.0810 | 28.0810 | 19.0389 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7849 | 2.7849 | 1.9494 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4945 | 0.4945 | 0.2443 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6605 | 0.6605 | 0.2642 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7596 | 0.7596 | 0.3039 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8033 | 0.8033 | 0.3213 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.6169 | 4.6169 | 2.3915 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.0274 | 7.0274 | 2.8110 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.5244 | 7.5244 | 3.0097 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.3670 | 7.3670 | 2.9468 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5206 | 0.5206 | 0.2447 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7080 | 0.7080 | 0.2832 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8074 | 0.8074 | 0.3229 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7753 | 0.7753 | 0.3101 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5023 | 0.5023 | 0.5023 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.8164 | 4.8164 | 4.8164 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4896 | 0.4896 | 0.4896 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 25.1531 | 25.1531 | 25.1531 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.7008 | 3.0785 | 3.0785 | 3.0785 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 54.6167 | 30.1980 | 30.1980 | 30.1980 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.5961 | 3.1104 | 3.1104 | 3.1104 | 0.0000 | 1.0000 |
CAV_BAS | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 25.1531 | 25.1531 | 25.1531 | 25.1531 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5023 | 0.5023 | 0.5023 | 0.5023 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.8164 | 4.8164 | 4.8164 | 4.8164 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4896 | 0.4896 | 0.4896 | 0.4896 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 71.83 |
Number of hours cooling loads not met | 1093.17 |
Number of hours not met | 1130.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1423.04 | 1657705.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1481.93 | 535338.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3220.39 | 325713.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 353.28 | 40855.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5334.97 | 305206.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 55.01 | 3454.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 2505.76 | 229608.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2449.74 | 285019.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 344.62 | 53027.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 531.95 | 88748.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1464.84 | 100000.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 39.11 | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 459.84 | 56293.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 14676.40 | 27588.71 |
Natural Gas | 0.00 | 1423.04 |
Additional | 0.00 | 0.00 |
Total | 14676.40 | 29011.75 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 69.52 |
Space Heating | 0.00 |
Space Cooling | 31.99 |
Fans (All) | 52.89 |
Service Water Heating | 9.93 |
Receptacle Equipment | 316.85 |
Miscellaneous (All) | 595.61 |
Subtotal | 595.61 |
Natural Gas [MJ/m2] | |
Space Heating | 30.72 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 30.72 |
Subtotal | 30.72 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 11.10 |
Space Heating | 4.91 |
Space Cooling | 5.11 |
Fans (All) | 8.44 |
Service Water Heating | 1.58 |
Receptacle Equipment | 50.59 |
Miscellaneous | 18.27 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
ELEVATOR_RUNNING_SCH | 675. | 3744. |
ELEVATOR_STANDBY_SCH | 7740. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2625. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4049. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 7427.50 | 814.83 | 257.33 | 260.33 | 0.00 |
CORE_BOTTOM | 8694.00 | 66.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8733.83 | 26.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8715.50 | 44.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8693.33 | 66.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8397.83 | 362.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8749.83 | 10.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8702.17 | 57.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8694.33 | 65.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8586.83 | 173.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8736.83 | 23.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8700.00 | 60.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8690.50 | 69.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8589.00 | 171.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7831.33 | 928.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7808.83 | 951.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7790.33 | 969.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6643.17 | 2114.83 | 2.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8687.00 | 73.00 | 0.00 | 0.00 | 0.00 |
Min | 6643.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2114.83 | 257.33 | 260.33 | 0.00 |
Average | 8430.96 | 306.44 | 11.28 | 11.32 | 0.00 |
Sum | 193912.17 | 7048.17 | 259.33 | 260.33 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 329736.00 | 15606.83 | 11181.83 | 12091.33 | 0.00 |
CORE_BOTTOM | 330784.00 | 29.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1759.67 | 508.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1744.00 | 524.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1730.33 | 537.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 78841.00 | 24550.00 | 4.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 330813.00 | 24550.00 | 11181.83 | 12091.33 | 0.00 |
Average | 77507.39 | 1815.47 | 486.34 | 525.71 | 0.00 |
Sum | 1782670.00 | 41755.83 | 11185.83 | 12091.33 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 7292.33 | 956.33 | 213.00 | 298.33 | 0.00 |
CORE_BOTTOM | 8150.17 | 609.83 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8272.33 | 487.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8278.83 | 481.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8214.00 | 546.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8401.83 | 358.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8242.67 | 517.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7966.67 | 793.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8287.17 | 472.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8284.67 | 475.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8230.17 | 529.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8142.50 | 617.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8293.67 | 466.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8292.50 | 467.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8245.00 | 515.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8168.50 | 591.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8345.83 | 414.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8324.33 | 435.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8320.17 | 439.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6867.17 | 1892.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8118.67 | 641.33 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8211.33 | 548.67 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7896.67 | 863.33 | 0.00 | 0.00 | 0.00 |
Min | 6867.17 | 358.17 | 0.00 | 0.00 | 0.00 |
Max | 8401.83 | 1892.83 | 213.00 | 298.33 | 0.00 |
Average | 8123.79 | 613.98 | 9.26 | 12.97 | 0.00 |
Sum | 186847.17 | 14121.50 | 213.00 | 298.33 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 328735.83 | 17389.17 | 8817.33 | 13673.67 | 0.00 |
CORE_BOTTOM | 329769.67 | 1043.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330100.00 | 713.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330084.00 | 729.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38924.17 | 0.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38924.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38923.83 | 1.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38924.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1996.17 | 271.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1982.00 | 286.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1977.67 | 290.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 81216.83 | 22178.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 330100.00 | 22178.17 | 8817.33 | 13673.67 | 0.00 |
Average | 77491.68 | 1865.36 | 383.36 | 594.51 | 0.00 |
Sum | 1782308.67 | 42903.33 | 8817.33 | 13673.67 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:48
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Environment
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2016
For: Environment
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Environment
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHPROPOSED
For: Environment
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.392754E+11 | 104004.20 | 17-JAN-07:12 | 7.03 | 3.10 | 0.567147E+10 | 7499.31 | 17-JAN-10:00 | 6.70 | 4.46 |
February | 0.368077E+11 | 104662.17 | 21-FEB-07:03 | -13.9 | -14.7 | 0.514516E+10 | 7499.12 | 17-FEB-10:09 | -13.9 | -14.7 |
March | 0.498627E+11 | 106395.31 | 13-MAR-06:11 | 7.77 | 7.56 | 0.614874E+10 | 7499.43 | 16-MAR-13:00 | 18.90 | 15.16 |
April | 0.495401E+11 | 104915.21 | 03-APR-06:03 | -2.8 | -3.4 | 0.546778E+10 | 7499.31 | 12-APR-13:09 | 11.70 | 10.39 |
May | 0.515041E+11 | 111199.07 | 30-MAY-06:11 | 12.20 | 11.93 | 0.595198E+10 | 9886.77 | 17-MAY-09:00 | 12.20 | 11.93 |
June | 0.473359E+11 | 115230.66 | 22-JUN-06:11 | 13.67 | 12.32 | 0.656607E+10 | 11717.84 | 27-JUN-13:00 | 27.20 | 22.77 |
July | 0.381221E+11 | 125285.22 | 06-JUL-06:11 | 13.33 | 10.63 | 0.673481E+10 | 12320.74 | 21-JUL-13:00 | 31.70 | 21.73 |
August | 0.528148E+11 | 122197.13 | 09-AUG-06:11 | 17.77 | 14.04 | 0.709718E+10 | 12284.18 | 15-AUG-13:00 | 26.10 | 22.23 |
September | 0.515471E+11 | 116976.88 | 11-SEP-06:11 | 11.70 | 9.59 | 0.581951E+10 | 11511.13 | 14-SEP-13:00 | 21.70 | 19.39 |
October | 0.564231E+11 | 116085.22 | 10-OCT-06:11 | 10.20 | 8.82 | 0.569588E+10 | 7499.35 | 27-OCT-13:09 | 9.78 | 7.31 |
November | 0.533189E+11 | 113376.31 | 06-NOV-07:11 | 8.70 | 5.96 | 0.563613E+10 | 7499.38 | 16-NOV-14:09 | 17.20 | 13.27 |
December | 0.470919E+11 | 108613.63 | 26-DEC-07:03 | -12.3 | -13.4 | 0.548464E+10 | 7499.15 | 01-DEC-10:09 | -12.3 | -13.4 |
Annual Sum or Average | 0.573644E+12 | 0.714194E+11 | ||||||||
Minimum of Months | 0.368077E+11 | 104004.20 | -13.9 | -14.7 | 0.514516E+10 | 7499.12 | -13.9 | -14.7 | ||
Maximum of Months | 0.564231E+11 | 125285.22 | 17.77 | 14.04 | 0.709718E+10 | 12320.74 | 31.70 | 22.77 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.326468E+11 | 78888.39 | 19-JAN-06:01 | 1.10 | -0.1 | 0.502030E+10 | 6734.85 | 11-JAN-10:09 | 1.10 | -0.1 |
February | 0.316246E+11 | 81820.17 | 24-FEB-06:02 | -7.2 | -8.2 | 0.456900E+10 | 6734.79 | 17-FEB-10:09 | -7.2 | -8.2 |
March | 0.476464E+11 | 87000.03 | 15-MAR-04:12 | 15.00 | 11.89 | 0.549296E+10 | 6748.05 | 23-MAR-09:39 | -0.4 | -1.6 |
April | 0.517641E+11 | 92449.30 | 10-APR-04:12 | 3.50 | 2.94 | 0.488288E+10 | 6734.82 | 21-APR-13:00 | 14.40 | 8.43 |
May | 0.514918E+11 | 94961.93 | 30-MAY-04:12 | 12.20 | 11.68 | 0.528584E+10 | 6734.89 | 10-MAY-09:09 | 12.20 | 11.68 |
June | 0.641353E+11 | 98442.54 | 28-JUN-04:13 | 17.60 | 15.52 | 0.527004E+10 | 6735.15 | 22-JUN-13:09 | 17.60 | 15.52 |
July | 0.757515E+11 | 98286.23 | 10-JUL-04:13 | 13.70 | 13.03 | 0.489892E+10 | 6741.37 | 24-JUL-09:00 | 23.90 | 17.87 |
August | 0.792696E+11 | 99485.95 | 29-AUG-04:13 | 15.40 | 14.29 | 0.549818E+10 | 6780.40 | 09-AUG-09:00 | 15.40 | 14.29 |
September | 0.544533E+11 | 96598.14 | 15-SEP-04:13 | 18.30 | 16.87 | 0.488399E+10 | 6735.16 | 12-SEP-13:09 | 18.30 | 16.87 |
October | 0.489207E+11 | 91828.77 | 10-OCT-04:11 | 10.00 | 8.72 | 0.507881E+10 | 6734.82 | 03-OCT-09:00 | 10.00 | 8.72 |
November | 0.455547E+11 | 93087.65 | 13-NOV-05:11 | 5.57 | 4.40 | 0.503029E+10 | 6751.78 | 24-NOV-10:50 | 0.82 | -0.8 |
December | 0.398914E+11 | 85722.06 | 18-DEC-05:01 | 1.70 | 0.81 | 0.489038E+10 | 6753.22 | 15-DEC-10:20 | 1.70 | 0.81 |
Annual Sum or Average | 0.623150E+12 | 0.608016E+11 | ||||||||
Minimum of Months | 0.316246E+11 | 78888.39 | -7.2 | -8.2 | 0.456900E+10 | 6734.79 | -7.2 | -8.2 | ||
Maximum of Months | 0.792696E+11 | 99485.95 | 18.30 | 16.87 | 0.549818E+10 | 6780.40 | 23.90 | 17.87 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.218821E+11 | 30685.54 | 06-JAN-11:53 | -3.9 | -5.7 | 0.439388E+10 | 6633.45 | 20-JAN-14:00 | 0.60 | -3.3 |
February | 0.209614E+11 | 26590.15 | 02-FEB-08:10 | -1.2 | -1.6 | 0.405210E+10 | 6721.36 | 17-FEB-14:00 | 3.30 | 1.08 |
March | 0.306061E+11 | 79075.99 | 16-MAR-05:02 | 14.03 | 11.42 | 0.529834E+10 | 6748.25 | 31-MAR-09:50 | 7.12 | 6.62 |
April | 0.323960E+11 | 75225.89 | 27-APR-05:03 | 5.00 | 3.27 | 0.481363E+10 | 6735.21 | 05-APR-09:09 | 5.00 | 3.27 |
May | 0.409996E+11 | 81386.07 | 30-MAY-04:12 | 12.20 | 11.68 | 0.526377E+10 | 6734.88 | 10-MAY-09:09 | 12.20 | 11.68 |
June | 0.471641E+11 | 82426.89 | 30-JUN-04:12 | 16.50 | 15.77 | 0.526031E+10 | 6735.14 | 22-JUN-13:09 | 16.50 | 15.77 |
July | 0.482728E+11 | 82742.20 | 25-JUL-04:12 | 15.00 | 13.80 | 0.489083E+10 | 6734.82 | 03-JUL-13:30 | 15.00 | 13.80 |
August | 0.503447E+11 | 82292.10 | 16-AUG-04:12 | 16.50 | 15.56 | 0.549296E+10 | 6735.21 | 02-AUG-13:09 | 16.50 | 15.56 |
September | 0.413528E+11 | 82718.73 | 18-SEP-04:12 | 10.20 | 9.28 | 0.486642E+10 | 6735.17 | 12-SEP-13:09 | 10.20 | 9.28 |
October | 0.331494E+11 | 78257.56 | 13-OCT-05:03 | 10.50 | 10.16 | 0.501444E+10 | 6734.79 | 10-OCT-09:09 | 10.50 | 10.16 |
November | 0.272080E+11 | 72288.92 | 01-NOV-05:02 | 5.68 | 3.03 | 0.489685E+10 | 6758.63 | 08-NOV-14:50 | 5.60 | 5.28 |
December | 0.233765E+11 | 31122.18 | 08-DEC-20:25 | -4.2 | -4.7 | 0.438968E+10 | 6734.49 | 01-DEC-10:00 | -4.2 | -4.7 |
Annual Sum or Average | 0.417714E+12 | 0.586332E+11 | ||||||||
Minimum of Months | 0.209614E+11 | 26590.15 | -4.2 | -5.7 | 0.405210E+10 | 6633.45 | -4.2 | -4.7 | ||
Maximum of Months | 0.503447E+11 | 82742.20 | 16.50 | 15.77 | 0.549296E+10 | 6758.63 | 16.50 | 15.77 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.148794E+11 | 17266.21 | 12-JAN-16:50 | -6.6 | -8.3 | 0.396605E+10 | 6024.06 | 12-JAN-14:00 | -6.6 | -8.3 |
February | 0.149816E+11 | 17741.35 | 17-FEB-17:00 | 1.10 | 0.20 | 0.367257E+10 | 6147.23 | 17-FEB-14:00 | 1.10 | 0.20 |
March | 0.244444E+11 | 76810.61 | 16-MAR-05:02 | 14.03 | 11.42 | 0.483613E+10 | 6734.88 | 16-MAR-13:00 | 18.90 | 15.16 |
April | 0.268802E+11 | 38714.82 | 21-APR-16:00 | 13.30 | 8.77 | 0.455792E+10 | 6734.76 | 21-APR-13:00 | 13.30 | 8.77 |
May | 0.374484E+11 | 74967.86 | 17-MAY-05:03 | 16.05 | 11.54 | 0.519059E+10 | 6734.88 | 10-MAY-09:09 | 16.05 | 11.54 |
June | 0.478170E+11 | 81604.91 | 19-JUN-04:12 | 16.70 | 15.97 | 0.524659E+10 | 6735.13 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.507459E+11 | 81490.72 | 28-JUL-04:12 | 19.60 | 18.70 | 0.488966E+10 | 6734.78 | 12-JUL-09:00 | 19.60 | 18.70 |
August | 0.508461E+11 | 81041.38 | 11-AUG-04:12 | 18.53 | 15.89 | 0.548512E+10 | 6735.21 | 02-AUG-13:09 | 18.53 | 15.89 |
September | 0.377191E+11 | 79663.09 | 18-SEP-04:12 | 10.20 | 9.28 | 0.481844E+10 | 6735.13 | 12-SEP-13:09 | 10.20 | 9.28 |
October | 0.263444E+11 | 52655.90 | 13-OCT-05:03 | 10.50 | 10.16 | 0.470876E+10 | 6745.55 | 23-OCT-13:00 | 5.60 | 5.10 |
November | 0.201533E+11 | 25310.49 | 01-NOV-16:00 | 9.40 | 6.91 | 0.436581E+10 | 6734.60 | 16-NOV-14:50 | 17.20 | 13.27 |
December | 0.159226E+11 | 18200.08 | 01-DEC-17:00 | 7.20 | 4.89 | 0.387136E+10 | 6269.30 | 01-DEC-14:00 | 7.20 | 4.89 |
Annual Sum or Average | 0.368182E+12 | 0.556090E+11 | ||||||||
Minimum of Months | 0.148794E+11 | 17266.21 | -6.6 | -8.3 | 0.367257E+10 | 6024.06 | -6.6 | -8.3 | ||
Maximum of Months | 0.508461E+11 | 81604.91 | 19.60 | 18.70 | 0.548512E+10 | 6745.55 | 20.60 | 18.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.156707E+10 | 2440.19 | 17-JAN-06:03 | 7.20 | 2.95 | 0.498042E+09 | 772.22 | 17-JAN-14:00 | 6.70 | 5.64 |
February | 0.169749E+10 | 2507.46 | 23-FEB-08:10 | 2.70 | 1.78 | 0.468913E+09 | 791.28 | 22-FEB-14:00 | 2.70 | 1.78 |
March | 0.369880E+10 | 7857.85 | 15-MAR-14:00 | 26.10 | 16.06 | 0.631981E+09 | 845.65 | 16-MAR-13:00 | 18.90 | 15.16 |
April | 0.469853E+10 | 7067.46 | 07-APR-13:30 | 20.00 | 10.05 | 0.598425E+09 | 845.64 | 21-APR-13:00 | 14.40 | 8.43 |
May | 0.615083E+10 | 10196.71 | 31-MAY-05:03 | 13.98 | 11.98 | 0.659026E+09 | 845.64 | 10-MAY-09:09 | 13.98 | 11.98 |
June | 0.978438E+10 | 13302.72 | 30-JUN-04:12 | 16.50 | 15.77 | 0.661862E+09 | 846.22 | 12-JUN-13:39 | 16.50 | 15.77 |
July | 0.121552E+11 | 15535.21 | 16-JUL-16:51 | 27.20 | 20.15 | 0.616044E+09 | 846.65 | 28-JUL-13:20 | 22.40 | 20.39 |
August | 0.117176E+11 | 16431.35 | 06-AUG-15:41 | 27.88 | 18.93 | 0.690630E+09 | 852.30 | 09-AUG-09:00 | 25.60 | 18.67 |
September | 0.654171E+10 | 13833.23 | 15-SEP-04:12 | 18.30 | 16.87 | 0.609544E+09 | 845.68 | 12-SEP-13:09 | 18.30 | 16.87 |
October | 0.427542E+10 | 6042.35 | 12-OCT-12:10 | 17.20 | 13.87 | 0.618756E+09 | 845.63 | 03-OCT-09:00 | 17.20 | 13.87 |
November | 0.321742E+10 | 4755.57 | 27-NOV-12:00 | 15.00 | 10.52 | 0.594018E+09 | 845.64 | 16-NOV-14:09 | 15.00 | 10.52 |
December | 0.225068E+10 | 2814.00 | 01-DEC-13:20 | 12.03 | 10.45 | 0.512399E+09 | 843.07 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.677552E+11 | 0.715964E+10 | ||||||||
Minimum of Months | 0.156707E+10 | 2440.19 | 2.70 | 1.78 | 0.468913E+09 | 772.22 | 2.70 | 1.78 | ||
Maximum of Months | 0.121552E+11 | 16431.35 | 27.88 | 20.15 | 0.690630E+09 | 852.30 | 25.60 | 20.39 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152332E+10 | 2540.74 | 17-JAN-06:03 | 7.20 | 2.95 | 0.317326E+09 | 511.88 | 12-JAN-10:30 | 7.20 | 2.95 |
February | 0.165037E+10 | 6038.29 | 28-FEB-09:35 | -5.2 | -6.5 | 0.301449E+09 | 544.95 | 17-FEB-10:50 | -5.2 | -6.5 |
March | 0.382301E+10 | 9103.65 | 21-MAR-08:55 | 1.70 | -0.5 | 0.407521E+09 | 544.97 | 16-MAR-13:00 | 1.70 | -0.5 |
April | 0.522497E+10 | 13563.26 | 23-APR-09:23 | 12.75 | 5.29 | 0.380018E+09 | 545.12 | 24-APR-09:09 | 6.28 | 2.92 |
May | 0.682160E+10 | 16508.09 | 29-MAY-10:32 | 18.70 | 14.44 | 0.421621E+09 | 545.62 | 31-MAY-09:20 | 17.97 | 13.39 |
June | 0.917102E+10 | 21063.99 | 11-JUN-08:52 | 23.30 | 16.13 | 0.425889E+09 | 546.13 | 30-JUN-09:00 | 20.60 | 14.08 |
July | 0.109144E+11 | 26292.40 | 04-JUL-08:31 | 21.10 | 17.36 | 0.396741E+09 | 546.27 | 18-JUL-09:00 | 23.30 | 19.54 |
August | 0.102213E+11 | 22439.89 | 06-AUG-09:01 | 24.18 | 17.35 | 0.443695E+09 | 552.55 | 09-AUG-09:00 | 25.60 | 18.67 |
September | 0.668613E+10 | 22668.54 | 10-SEP-09:52 | 15.60 | 10.49 | 0.390145E+09 | 544.99 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.426462E+10 | 13062.75 | 09-OCT-10:02 | 10.68 | 6.97 | 0.392761E+09 | 544.97 | 03-OCT-09:00 | 10.68 | 6.97 |
November | 0.299103E+10 | 6451.38 | 03-NOV-08:55 | 3.90 | 1.83 | 0.358196E+09 | 544.95 | 15-NOV-10:30 | 5.55 | 3.27 |
December | 0.176232E+10 | 3523.36 | 04-DEC-09:50 | -1.8 | -3.7 | 0.308275E+09 | 545.30 | 04-DEC-10:20 | -1.5 | -3.6 |
Annual Sum or Average | 0.650541E+11 | 0.454364E+10 | ||||||||
Minimum of Months | 0.152332E+10 | 2540.74 | -5.2 | -6.5 | 0.301449E+09 | 511.88 | -5.2 | -6.5 | ||
Maximum of Months | 0.109144E+11 | 26292.40 | 24.18 | 17.36 | 0.443695E+09 | 552.55 | 25.60 | 19.54 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.287420E+10 | 14639.85 | 12-JAN-13:30 | -6.7 | -9.2 | 0.531061E+09 | 845.64 | 24-JAN-10:39 | -9.5 | -11.1 |
February | 0.323877E+10 | 17298.38 | 28-FEB-13:20 | 0.00 | -2.8 | 0.499323E+09 | 845.79 | 28-FEB-14:20 | 0.00 | -2.9 |
March | 0.719898E+10 | 19279.82 | 15-MAR-13:30 | 25.55 | 15.84 | 0.650786E+09 | 847.38 | 14-MAR-13:00 | 25.55 | 15.84 |
April | 0.760129E+10 | 25600.01 | 23-APR-12:02 | 15.87 | 8.28 | 0.591661E+09 | 846.60 | 21-APR-13:00 | 15.87 | 8.28 |
May | 0.857401E+10 | 25821.19 | 14-MAY-13:52 | 25.00 | 18.14 | 0.653640E+09 | 845.67 | 10-MAY-13:09 | 25.00 | 18.14 |
June | 0.114897E+11 | 25634.49 | 18-JUN-12:32 | 26.10 | 20.49 | 0.660570E+09 | 845.71 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.145470E+11 | 26169.88 | 04-JUL-13:12 | 25.93 | 17.51 | 0.615964E+09 | 847.62 | 18-JUL-13:00 | 27.20 | 19.82 |
August | 0.155432E+11 | 26887.03 | 27-AUG-12:42 | 23.12 | 18.75 | 0.690573E+09 | 854.31 | 09-AUG-09:00 | 23.12 | 18.75 |
September | 0.113840E+11 | 28978.59 | 10-SEP-12:31 | 17.03 | 10.63 | 0.609017E+09 | 878.60 | 21-SEP-13:30 | 25.30 | 16.56 |
October | 0.831881E+10 | 26694.08 | 09-OCT-12:02 | 11.78 | 7.74 | 0.619657E+09 | 898.82 | 31-OCT-13:09 | 15.00 | 10.18 |
November | 0.528267E+10 | 18375.54 | 03-NOV-12:20 | 8.17 | 4.43 | 0.581967E+09 | 846.46 | 15-NOV-14:39 | 11.50 | 6.50 |
December | 0.313541E+10 | 18460.70 | 17-DEC-12:53 | 2.20 | 0.48 | 0.516842E+09 | 846.46 | 04-DEC-10:20 | 2.20 | 0.48 |
Annual Sum or Average | 0.991880E+11 | 0.722106E+10 | ||||||||
Minimum of Months | 0.287420E+10 | 14639.85 | -6.7 | -9.2 | 0.499323E+09 | 845.64 | -9.5 | -11.1 | ||
Maximum of Months | 0.155432E+11 | 28978.59 | 26.10 | 20.49 | 0.690573E+09 | 898.82 | 27.20 | 19.82 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.249902E+10 | 4415.92 | 12-JAN-15:40 | -5.9 | -8.2 | 0.326690E+09 | 543.23 | 12-JAN-14:00 | -5.9 | -8.2 |
February | 0.307130E+10 | 9346.25 | 28-FEB-16:30 | 0.00 | -2.6 | 0.317723E+09 | 544.95 | 28-FEB-14:00 | 0.00 | -2.6 |
March | 0.640498E+10 | 18221.06 | 26-MAR-16:22 | -1.7 | -4.7 | 0.428317E+09 | 545.89 | 20-MAR-13:39 | -1.7 | -4.7 |
April | 0.857105E+10 | 27681.61 | 02-APR-16:12 | 7.77 | 5.85 | 0.394215E+09 | 544.97 | 21-APR-13:00 | 14.40 | 8.43 |
May | 0.842049E+10 | 28225.55 | 14-MAY-14:32 | 25.73 | 17.96 | 0.424343E+09 | 544.97 | 10-MAY-09:09 | 25.73 | 17.96 |
June | 0.124488E+11 | 29198.66 | 11-JUN-16:51 | 25.60 | 17.82 | 0.427360E+09 | 545.00 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.147516E+11 | 30117.46 | 02-JUL-16:41 | 25.00 | 17.06 | 0.397777E+09 | 545.69 | 24-JUL-09:00 | 23.90 | 17.87 |
August | 0.157532E+11 | 29411.09 | 27-AUG-16:41 | 22.38 | 18.89 | 0.446175E+09 | 550.48 | 09-AUG-09:00 | 22.38 | 18.89 |
September | 0.800029E+10 | 30546.89 | 04-SEP-16:51 | 18.30 | 12.88 | 0.392864E+09 | 545.00 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.609724E+10 | 14927.08 | 09-OCT-16:03 | 13.22 | 9.40 | 0.402393E+09 | 544.96 | 03-OCT-09:00 | 13.22 | 9.40 |
November | 0.488192E+10 | 14518.43 | 27-NOV-05:12 | 17.97 | 12.28 | 0.395307E+09 | 544.97 | 16-NOV-14:09 | 17.97 | 12.28 |
December | 0.398014E+10 | 7778.26 | 04-DEC-15:30 | -0.3 | -3.1 | 0.363528E+09 | 544.95 | 01-DEC-10:30 | -0.3 | -3.1 |
Annual Sum or Average | 0.948800E+11 | 0.471669E+10 | ||||||||
Minimum of Months | 0.249902E+10 | 4415.92 | -5.9 | -8.2 | 0.317723E+09 | 543.23 | -5.9 | -8.2 | ||
Maximum of Months | 0.157532E+11 | 30546.89 | 25.73 | 18.89 | 0.446175E+09 | 550.48 | 25.73 | 18.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.155350E+09 | 1611.34 | 11-JAN-16:50 | 11.20 | 9.89 | 0.464820E+09 | 628.39 | 11-JAN-14:00 | 11.20 | 9.89 |
February | 0.242748E+09 | 1637.06 | 17-FEB-15:00 | 3.30 | 1.08 | 0.422585E+09 | 650.64 | 17-FEB-14:00 | 3.30 | 1.08 |
March | 0.179816E+10 | 6055.71 | 15-MAR-14:00 | 26.10 | 16.06 | 0.557221E+09 | 845.64 | 16-MAR-13:00 | 18.90 | 15.16 |
April | 0.265892E+10 | 4589.73 | 07-APR-13:50 | 20.00 | 10.11 | 0.537118E+09 | 845.62 | 21-APR-13:00 | 14.40 | 8.43 |
May | 0.463421E+10 | 7207.92 | 23-MAY-14:40 | 23.90 | 13.32 | 0.643291E+09 | 845.63 | 17-MAY-09:00 | 23.90 | 13.32 |
June | 0.747863E+10 | 11589.88 | 21-JUN-05:03 | 18.30 | 16.18 | 0.659167E+09 | 845.68 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.855364E+10 | 13446.87 | 16-JUL-14:32 | 29.03 | 21.69 | 0.615140E+09 | 845.75 | 20-JUL-13:00 | 30.00 | 23.95 |
August | 0.788011E+10 | 13126.18 | 13-AUG-16:11 | 28.67 | 23.12 | 0.687830E+09 | 845.69 | 02-AUG-13:09 | 28.67 | 23.12 |
September | 0.481532E+10 | 7103.26 | 13-SEP-13:30 | 22.20 | 19.01 | 0.596975E+09 | 845.68 | 12-SEP-13:09 | 22.20 | 19.01 |
October | 0.272059E+10 | 4236.08 | 12-OCT-14:40 | 18.30 | 15.11 | 0.558790E+09 | 845.62 | 12-OCT-13:00 | 18.30 | 15.11 |
November | 0.152736E+10 | 2422.46 | 03-NOV-12:40 | 8.53 | 4.68 | 0.495901E+09 | 798.53 | 16-NOV-14:00 | 17.20 | 13.27 |
December | 0.272729E+09 | 1890.98 | 01-DEC-13:30 | 11.10 | 9.57 | 0.450553E+09 | 698.84 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.427378E+11 | 0.668939E+10 | ||||||||
Minimum of Months | 0.155350E+09 | 1611.34 | 3.30 | 1.08 | 0.422585E+09 | 628.39 | 3.30 | 1.08 | ||
Maximum of Months | 0.855364E+10 | 13446.87 | 29.03 | 23.12 | 0.687830E+09 | 845.75 | 30.00 | 23.95 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.219128E+09 | 2519.29 | 06-JAN-10:05 | -6.9 | -8.5 | 0.219822E+09 | 394.29 | 06-JAN-09:00 | -6.9 | -8.5 |
February | 0.500879E+09 | 3191.04 | 28-FEB-09:55 | -3.9 | -5.5 | 0.202369E+09 | 521.19 | 28-FEB-09:00 | -3.9 | -5.5 |
March | 0.249651E+10 | 6843.79 | 21-MAR-08:55 | 1.70 | -0.5 | 0.271201E+09 | 527.10 | 01-MAR-09:50 | 1.70 | -0.5 |
April | 0.412678E+10 | 23462.72 | 23-APR-09:52 | 14.40 | 6.16 | 0.261525E+09 | 523.17 | 05-APR-08:50 | 14.40 | 6.16 |
May | 0.632354E+10 | 24036.89 | 21-MAY-10:02 | 16.20 | 11.92 | 0.301945E+09 | 521.33 | 31-MAY-08:00 | 17.80 | 13.21 |
June | 0.844882E+10 | 26472.40 | 11-JUN-09:21 | 23.85 | 16.50 | 0.310795E+09 | 521.35 | 23-JUN-08:00 | 15.60 | 11.53 |
July | 0.930709E+10 | 28575.94 | 04-JUL-09:11 | 21.47 | 17.29 | 0.292021E+09 | 521.65 | 10-JUL-08:09 | 20.28 | 17.18 |
August | 0.861526E+10 | 20689.20 | 06-AUG-09:12 | 24.47 | 17.45 | 0.323973E+09 | 522.33 | 02-AUG-08:00 | 24.47 | 17.45 |
September | 0.596312E+10 | 24193.36 | 10-SEP-09:42 | 15.40 | 10.56 | 0.280275E+09 | 521.24 | 12-SEP-12:20 | 20.77 | 15.37 |
October | 0.325792E+10 | 9272.29 | 11-OCT-09:00 | 15.00 | 11.35 | 0.265875E+09 | 521.22 | 03-OCT-10:09 | 15.00 | 11.35 |
November | 0.154697E+10 | 4065.76 | 03-NOV-08:55 | 3.90 | 1.83 | 0.230939E+09 | 521.20 | 03-NOV-10:20 | 5.97 | 3.19 |
December | 0.225916E+09 | 2115.03 | 04-DEC-10:00 | -1.7 | -3.7 | 0.212484E+09 | 421.63 | 04-DEC-09:00 | -1.7 | -3.7 |
Annual Sum or Average | 0.510319E+11 | 0.317322E+10 | ||||||||
Minimum of Months | 0.219128E+09 | 2115.03 | -6.9 | -8.5 | 0.202369E+09 | 394.29 | -6.9 | -8.5 | ||
Maximum of Months | 0.930709E+10 | 28575.94 | 24.47 | 17.45 | 0.323973E+09 | 527.10 | 24.47 | 17.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.178307E+10 | 18067.09 | 15-JAN-14:03 | 5.10 | 2.14 | 0.504920E+09 | 846.18 | 06-JAN-10:00 | 5.10 | 2.14 |
February | 0.225344E+10 | 18248.31 | 28-FEB-13:40 | 0.00 | -2.9 | 0.468317E+09 | 846.19 | 28-FEB-14:09 | 0.00 | -3.0 |
March | 0.593381E+10 | 19486.93 | 01-MAR-13:40 | -0.2 | -2.6 | 0.620974E+09 | 850.40 | 07-MAR-10:39 | -6.5 | -8.7 |
April | 0.603642E+10 | 26147.55 | 23-APR-13:12 | 16.67 | 9.22 | 0.562945E+09 | 846.26 | 21-APR-13:00 | 16.67 | 9.22 |
May | 0.772908E+10 | 25480.39 | 14-MAY-13:32 | 24.63 | 17.99 | 0.641804E+09 | 845.67 | 10-MAY-13:09 | 24.63 | 17.99 |
June | 0.973795E+10 | 25659.87 | 18-JUN-13:02 | 26.02 | 20.50 | 0.656270E+09 | 845.71 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.113684E+11 | 25984.02 | 04-JUL-13:12 | 25.93 | 17.51 | 0.614640E+09 | 846.50 | 31-JUL-13:00 | 25.00 | 19.43 |
August | 0.123155E+11 | 26668.42 | 27-AUG-13:12 | 23.50 | 18.92 | 0.687912E+09 | 846.44 | 03-AUG-13:00 | 23.50 | 18.92 |
September | 0.106453E+11 | 29005.61 | 10-SEP-12:21 | 16.95 | 10.67 | 0.602670E+09 | 903.60 | 21-SEP-13:30 | 25.30 | 16.56 |
October | 0.739010E+10 | 25207.90 | 22-OCT-14:02 | 21.70 | 14.26 | 0.601512E+09 | 942.37 | 31-OCT-13:30 | 15.00 | 10.33 |
November | 0.392555E+10 | 19230.87 | 03-NOV-12:30 | 8.35 | 4.56 | 0.540077E+09 | 846.15 | 15-NOV-14:50 | 11.60 | 6.55 |
December | 0.148201E+10 | 12617.43 | 04-DEC-11:50 | -0.2 | -2.9 | 0.474564E+09 | 845.63 | 11-DEC-14:00 | -8.3 | -9.4 |
Annual Sum or Average | 0.806006E+11 | 0.697661E+10 | ||||||||
Minimum of Months | 0.148201E+10 | 12617.43 | -0.2 | -2.9 | 0.468317E+09 | 845.63 | -8.3 | -9.4 | ||
Maximum of Months | 0.123155E+11 | 29005.61 | 26.02 | 20.50 | 0.687912E+09 | 942.37 | 25.30 | 19.43 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.388318E+09 | 2604.59 | 12-JAN-16:00 | -6.1 | -8.3 | 0.301512E+09 | 475.72 | 12-JAN-16:10 | -6.2 | -8.3 |
February | 0.673696E+09 | 6044.91 | 28-FEB-16:30 | 0.00 | -2.6 | 0.277387E+09 | 521.18 | 28-FEB-16:00 | -0.6 | -3.0 |
March | 0.289929E+10 | 8867.36 | 21-MAR-16:00 | 4.40 | 1.34 | 0.366039E+09 | 544.97 | 16-MAR-13:00 | 4.40 | 1.34 |
April | 0.430377E+10 | 18074.49 | 02-APR-16:52 | 6.70 | 5.17 | 0.344252E+09 | 544.96 | 21-APR-13:00 | 14.40 | 8.43 |
May | 0.656376E+10 | 28366.10 | 07-MAY-16:41 | 15.00 | 5.89 | 0.404660E+09 | 544.96 | 05-MAY-13:09 | 15.00 | 5.89 |
June | 0.931365E+10 | 29793.08 | 11-JUN-16:41 | 25.60 | 17.82 | 0.421521E+09 | 544.99 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.971354E+10 | 27801.75 | 02-JUL-17:01 | 24.82 | 16.94 | 0.395715E+09 | 544.98 | 03-JUL-13:30 | 25.00 | 16.74 |
August | 0.929452E+10 | 26680.84 | 27-AUG-16:31 | 22.57 | 18.97 | 0.441477E+09 | 545.00 | 02-AUG-13:09 | 22.57 | 18.97 |
September | 0.604019E+10 | 26194.60 | 10-SEP-17:42 | 16.10 | 10.54 | 0.377595E+09 | 544.99 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.357424E+10 | 11661.89 | 11-OCT-16:00 | 21.70 | 14.52 | 0.353546E+09 | 544.95 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.194477E+10 | 4872.16 | 15-NOV-15:20 | 11.70 | 6.66 | 0.318815E+09 | 544.93 | 15-NOV-14:00 | 11.70 | 6.66 |
December | 0.519394E+09 | 2684.71 | 04-DEC-15:50 | -0.5 | -3.2 | 0.291480E+09 | 485.99 | 04-DEC-15:00 | -0.6 | -3.3 |
Annual Sum or Average | 0.552292E+11 | 0.429400E+10 | ||||||||
Minimum of Months | 0.388318E+09 | 2604.59 | -6.1 | -8.3 | 0.277387E+09 | 475.72 | -6.2 | -8.3 | ||
Maximum of Months | 0.971354E+10 | 29793.08 | 25.60 | 18.97 | 0.441477E+09 | 545.00 | 25.00 | 18.97 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 31186897.83 | 1471.55 | 14-JAN-17:03 | 3.22 | 2.72 | 0.463078E+09 | 625.91 | 31-JAN-10:50 | -11.2 | -12.3 |
February | 72773154.85 | 1553.19 | 22-FEB-16:30 | 11.15 | 5.29 | 0.419795E+09 | 625.96 | 07-FEB-10:09 | 11.15 | 5.29 |
March | 0.127155E+10 | 6567.31 | 15-MAR-14:30 | 25.85 | 16.15 | 0.538493E+09 | 845.64 | 16-MAR-13:00 | 18.90 | 15.16 |
April | 0.210138E+10 | 4374.39 | 20-APR-15:40 | 14.80 | 10.94 | 0.507721E+09 | 845.62 | 21-APR-13:00 | 14.40 | 8.43 |
May | 0.426514E+10 | 7444.37 | 23-MAY-14:40 | 23.90 | 13.32 | 0.623897E+09 | 845.64 | 10-MAY-13:39 | 23.90 | 13.32 |
June | 0.753534E+10 | 17227.85 | 18-JUN-15:01 | 25.55 | 20.06 | 0.655336E+09 | 845.68 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.887253E+10 | 17294.52 | 16-JUL-14:32 | 29.03 | 21.69 | 0.614681E+09 | 845.84 | 20-JUL-13:39 | 30.00 | 23.72 |
August | 0.796268E+10 | 13670.09 | 06-AUG-16:32 | 27.80 | 18.98 | 0.684752E+09 | 845.69 | 02-AUG-13:09 | 27.80 | 18.98 |
September | 0.445968E+10 | 7459.14 | 15-SEP-14:00 | 25.60 | 21.03 | 0.581869E+09 | 845.68 | 12-SEP-13:09 | 25.60 | 21.03 |
October | 0.201670E+10 | 4145.90 | 12-OCT-15:00 | 18.30 | 15.23 | 0.526148E+09 | 845.62 | 12-OCT-13:00 | 18.30 | 15.23 |
November | 0.711775E+09 | 2167.40 | 16-NOV-16:50 | 18.12 | 13.51 | 0.471129E+09 | 754.68 | 16-NOV-14:00 | 18.12 | 13.51 |
December | 85541762.87 | 1663.63 | 01-DEC-13:30 | 11.10 | 9.57 | 0.446428E+09 | 636.60 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.393863E+11 | 0.653333E+10 | ||||||||
Minimum of Months | 31186897.83 | 1471.55 | 3.22 | 2.72 | 0.419795E+09 | 625.91 | -11.2 | -12.3 | ||
Maximum of Months | 0.887253E+10 | 17294.52 | 29.03 | 21.69 | 0.684752E+09 | 845.84 | 30.00 | 23.72 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 57986783.86 | 1900.32 | 20-JAN-06:04 | -0.7 | -3.0 | 0.298992E+09 | 403.38 | 25-JAN-10:50 | -7.3 | -7.9 |
February | 0.324505E+09 | 2588.85 | 28-FEB-10:15 | -3.3 | -5.1 | 0.273622E+09 | 509.80 | 28-FEB-10:20 | -3.3 | -5.1 |
March | 0.193406E+10 | 5924.13 | 14-MAR-10:40 | 21.27 | 17.29 | 0.360268E+09 | 544.97 | 15-MAR-13:30 | 25.55 | 15.84 |
April | 0.345474E+10 | 10606.68 | 24-APR-09:20 | 6.47 | 3.13 | 0.348113E+09 | 544.96 | 21-APR-13:00 | 6.47 | 3.13 |
May | 0.594044E+10 | 13956.43 | 31-MAY-09:00 | 17.80 | 13.21 | 0.407465E+09 | 544.97 | 10-MAY-13:39 | 17.80 | 13.21 |
June | 0.854288E+10 | 23948.70 | 18-JUN-10:22 | 25.30 | 21.06 | 0.422882E+09 | 546.09 | 20-JUN-09:00 | 23.30 | 16.76 |
July | 0.961949E+10 | 25441.84 | 04-JUL-09:22 | 21.65 | 17.37 | 0.396130E+09 | 546.00 | 14-JUL-09:00 | 23.90 | 16.94 |
August | 0.876586E+10 | 20785.18 | 06-AUG-09:12 | 24.47 | 17.45 | 0.440834E+09 | 545.90 | 04-AUG-09:50 | 24.47 | 17.45 |
September | 0.565574E+10 | 18854.18 | 10-SEP-09:23 | 15.00 | 10.68 | 0.378360E+09 | 544.99 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.258074E+10 | 8099.39 | 11-OCT-09:30 | 15.85 | 11.81 | 0.350437E+09 | 544.96 | 03-OCT-09:00 | 15.85 | 11.81 |
November | 0.844198E+09 | 2685.27 | 03-NOV-09:30 | 4.75 | 2.42 | 0.306000E+09 | 528.28 | 03-NOV-09:00 | 5.60 | 2.99 |
December | 88880243.73 | 1941.13 | 13-DEC-06:04 | 1.20 | 0.92 | 0.288364E+09 | 403.39 | 12-DEC-10:20 | 1.20 | 0.92 |
Annual Sum or Average | 0.478095E+11 | 0.427147E+10 | ||||||||
Minimum of Months | 57986783.86 | 1900.32 | -3.3 | -5.1 | 0.273622E+09 | 403.38 | -7.3 | -7.9 | ||
Maximum of Months | 0.961949E+10 | 25441.84 | 25.30 | 21.06 | 0.440834E+09 | 546.09 | 25.55 | 17.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120909E+10 | 12704.57 | 12-JAN-13:40 | -6.5 | -9.0 | 0.493626E+09 | 845.64 | 04-JAN-14:50 | -6.5 | -9.0 |
February | 0.168020E+10 | 17062.76 | 28-FEB-14:05 | 0.00 | -3.0 | 0.455548E+09 | 846.67 | 28-FEB-14:09 | 0.00 | -3.0 |
March | 0.486683E+10 | 19287.36 | 15-MAR-13:30 | 25.55 | 15.84 | 0.597473E+09 | 846.57 | 15-MAR-13:00 | 26.10 | 16.06 |
April | 0.518353E+10 | 27186.07 | 23-APR-14:22 | 15.30 | 9.71 | 0.538666E+09 | 845.68 | 21-APR-13:50 | 15.30 | 9.71 |
May | 0.727921E+10 | 27689.20 | 14-MAY-14:02 | 25.18 | 18.10 | 0.624172E+09 | 845.69 | 10-MAY-13:39 | 25.18 | 18.10 |
June | 0.987692E+10 | 27681.40 | 18-JUN-13:02 | 26.02 | 20.50 | 0.650589E+09 | 845.71 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.117805E+11 | 27686.68 | 30-JUL-12:32 | 25.60 | 19.52 | 0.612753E+09 | 846.67 | 31-JUL-13:00 | 25.00 | 19.43 |
August | 0.124670E+11 | 27470.94 | 13-AUG-14:22 | 30.00 | 23.06 | 0.683735E+09 | 846.61 | 03-AUG-13:00 | 30.00 | 23.06 |
September | 0.101558E+11 | 29121.07 | 04-SEP-15:02 | 18.80 | 13.13 | 0.591141E+09 | 864.95 | 21-SEP-13:30 | 25.30 | 16.56 |
October | 0.619808E+10 | 22602.94 | 31-OCT-13:30 | 15.00 | 10.33 | 0.575359E+09 | 888.28 | 31-OCT-13:39 | 15.00 | 10.41 |
November | 0.269807E+10 | 17172.03 | 03-NOV-12:40 | 8.53 | 4.68 | 0.512828E+09 | 845.64 | 01-NOV-13:39 | 8.53 | 4.68 |
December | 0.904508E+09 | 10239.79 | 16-DEC-13:30 | 5.60 | 3.03 | 0.462926E+09 | 845.63 | 11-DEC-14:00 | 5.60 | 3.03 |
Annual Sum or Average | 0.742997E+11 | 0.679882E+10 | ||||||||
Minimum of Months | 0.904508E+09 | 10239.79 | -6.5 | -9.0 | 0.455548E+09 | 845.63 | -6.5 | -9.0 | ||
Maximum of Months | 0.124670E+11 | 29121.07 | 30.00 | 23.06 | 0.683735E+09 | 888.28 | 30.00 | 23.06 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.203006E+09 | 2533.55 | 12-JAN-16:00 | -6.1 | -8.3 | 0.299888E+09 | 450.01 | 12-JAN-16:10 | -6.2 | -8.3 |
February | 0.464681E+09 | 5748.67 | 28-FEB-16:30 | 0.00 | -2.6 | 0.275279E+09 | 521.18 | 28-FEB-16:00 | -0.6 | -3.0 |
March | 0.235219E+10 | 8439.66 | 21-MAR-16:00 | 4.40 | 1.34 | 0.356164E+09 | 544.97 | 15-MAR-13:30 | 4.40 | 1.34 |
April | 0.378267E+10 | 12687.50 | 30-APR-16:21 | 15.00 | 12.10 | 0.329950E+09 | 544.96 | 21-APR-13:00 | 15.00 | 12.10 |
May | 0.634740E+10 | 29617.08 | 07-MAY-16:41 | 15.00 | 5.89 | 0.391577E+09 | 544.97 | 10-MAY-13:39 | 25.73 | 17.72 |
June | 0.940146E+10 | 30358.10 | 18-JUN-17:01 | 23.22 | 18.52 | 0.417417E+09 | 544.99 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.998859E+10 | 29206.08 | 02-JUL-17:21 | 24.45 | 16.81 | 0.394147E+09 | 544.96 | 12-JUL-09:00 | 20.60 | 14.64 |
August | 0.940539E+10 | 27171.95 | 06-AUG-16:32 | 27.80 | 18.98 | 0.437855E+09 | 545.01 | 02-AUG-13:09 | 27.80 | 18.98 |
September | 0.583407E+10 | 28993.54 | 04-SEP-17:01 | 18.03 | 12.75 | 0.367035E+09 | 544.99 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.296902E+10 | 11687.89 | 11-OCT-16:00 | 21.70 | 14.52 | 0.338631E+09 | 544.95 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.121341E+10 | 4113.74 | 15-NOV-15:30 | 11.70 | 6.70 | 0.308807E+09 | 544.86 | 15-NOV-14:00 | 11.70 | 6.70 |
December | 0.270844E+09 | 2565.87 | 04-DEC-15:50 | -0.5 | -3.2 | 0.289292E+09 | 453.64 | 04-DEC-15:00 | -0.6 | -3.3 |
Annual Sum or Average | 0.522327E+11 | 0.420604E+10 | ||||||||
Minimum of Months | 0.203006E+09 | 2533.55 | -6.1 | -8.3 | 0.275279E+09 | 450.01 | -6.2 | -8.3 | ||
Maximum of Months | 0.998859E+10 | 30358.10 | 27.80 | 18.98 | 0.437855E+09 | 545.01 | 27.80 | 18.98 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.471177E+09 | 5633.86 | 04-JAN-06:01 | -12.3 | -12.9 | 0.00 | 0.00 | 01-JAN-00:10 | -12.3 | -12.9 |
February | 0.449170E+09 | 7790.74 | 06-FEB-05:01 | -14.8 | -15.7 | 0.00 | 0.00 | 01-FEB-00:10 | -14.8 | -15.7 |
March | 0.233926E+10 | 5658.35 | 16-MAR-05:13 | 13.67 | 11.27 | 0.00 | 0.00 | 01-MAR-00:10 | 13.67 | 11.27 |
April | 0.406959E+10 | 7245.29 | 10-APR-05:15 | 4.07 | 3.41 | 0.00 | 0.00 | 01-APR-00:10 | 4.07 | 3.41 |
May | 0.528268E+10 | 8288.84 | 30-MAY-05:15 | 12.20 | 11.93 | 0.00 | 0.00 | 01-MAY-00:10 | 12.20 | 11.93 |
June | 0.868595E+10 | 11283.38 | 28-JUN-05:15 | 17.20 | 15.14 | 0.00 | 0.00 | 01-JUN-00:10 | 17.20 | 15.14 |
July | 0.108630E+11 | 14461.70 | 31-JUL-05:10 | 17.70 | 16.75 | 0.00 | 0.00 | 01-JUL-00:10 | 17.70 | 16.75 |
August | 0.108288E+11 | 11658.90 | 15-AUG-05:15 | 22.60 | 20.62 | 0.00 | 0.00 | 01-AUG-00:10 | 22.60 | 20.62 |
September | 0.668918E+10 | 10309.72 | 18-SEP-05:15 | 9.60 | 8.73 | 0.00 | 0.00 | 01-SEP-00:10 | 9.60 | 8.73 |
October | 0.400464E+10 | 6722.74 | 23-OCT-05:15 | 11.70 | 10.06 | 0.00 | 0.00 | 01-OCT-00:10 | 11.70 | 10.06 |
November | 0.272325E+10 | 5672.79 | 06-NOV-06:15 | 8.90 | 6.78 | 0.00 | 0.00 | 01-NOV-00:10 | 8.90 | 6.78 |
December | 0.813245E+09 | 4943.13 | 07-DEC-06:01 | -7.9 | -8.2 | 0.00 | 0.00 | 01-DEC-00:10 | -7.9 | -8.2 |
Annual Sum or Average | 0.572200E+11 | 0.00 | ||||||||
Minimum of Months | 0.449170E+09 | 4943.13 | -14.8 | -15.7 | 0.00 | 0.00 | -14.8 | -15.7 | ||
Maximum of Months | 0.108630E+11 | 14461.70 | 22.60 | 20.62 | 0.00 | 0.00 | 22.60 | 20.62 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.229273E+09 | 9343.61 | 24-JAN-04:01 | -11.7 | -13.2 | 0.00 | 0.00 | 01-JAN-00:10 | -11.7 | -13.2 |
February | 0.251069E+09 | 9131.46 | 13-FEB-04:01 | -8.9 | -9.5 | 0.00 | 0.00 | 01-FEB-00:10 | -8.9 | -9.5 |
March | 0.931228E+09 | 9942.29 | 04-MAR-05:01 | -10.1 | -11.1 | 0.00 | 0.00 | 01-MAR-00:10 | -10.1 | -11.1 |
April | 0.157298E+10 | 5502.57 | 17-APR-04:01 | -3.4 | -5.0 | 0.00 | 0.00 | 01-APR-00:10 | -3.4 | -5.0 |
May | 0.330332E+10 | 5214.27 | 18-MAY-05:10 | 8.48 | 5.49 | 0.00 | 0.00 | 01-MAY-00:10 | 8.48 | 5.49 |
June | 0.582790E+10 | 6459.69 | 29-JUN-15:30 | 26.15 | 19.78 | 0.00 | 0.00 | 01-JUN-00:10 | 26.15 | 19.78 |
July | 0.706642E+10 | 7431.58 | 20-JUL-05:02 | 23.90 | 21.99 | 0.00 | 0.00 | 01-JUL-00:10 | 23.90 | 21.99 |
August | 0.695745E+10 | 7963.90 | 07-AUG-05:02 | 20.10 | 18.54 | 0.00 | 0.00 | 01-AUG-00:10 | 20.10 | 18.54 |
September | 0.440610E+10 | 6383.53 | 18-SEP-05:15 | 9.60 | 8.73 | 0.00 | 0.00 | 01-SEP-00:10 | 9.60 | 8.73 |
October | 0.183808E+10 | 6625.28 | 17-OCT-05:01 | -2.8 | -3.4 | 0.00 | 0.00 | 01-OCT-00:10 | -2.8 | -3.4 |
November | 0.803434E+09 | 8084.33 | 24-NOV-05:01 | -3.0 | -3.7 | 0.00 | 0.00 | 01-NOV-00:10 | -3.0 | -3.7 |
December | 0.339751E+09 | 9527.96 | 26-DEC-04:01 | -11.8 | -12.8 | 0.00 | 0.00 | 01-DEC-00:10 | -11.8 | -12.8 |
Annual Sum or Average | 0.335270E+11 | 0.00 | ||||||||
Minimum of Months | 0.229273E+09 | 5214.27 | -11.8 | -13.2 | 0.00 | 0.00 | -11.8 | -13.2 | ||
Maximum of Months | 0.706642E+10 | 9942.29 | 26.15 | 21.99 | 0.00 | 0.00 | 26.15 | 21.99 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.3 | -4.7 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 |
March | 0.722987E+09 | 11606.85 | 15-MAR-14:10 | 26.02 | 16.09 | 0.00 | 0.00 | 01-MAR-00:10 | 26.02 | 16.09 |
April | 0.213206E+10 | 9824.00 | 21-APR-14:00 | 14.40 | 8.43 | 0.00 | 0.00 | 01-APR-00:10 | 14.40 | 8.43 |
May | 0.560140E+10 | 14326.67 | 31-MAY-14:20 | 21.70 | 14.12 | 0.00 | 0.00 | 01-MAY-00:10 | 21.70 | 14.12 |
June | 0.103975E+11 | 18826.71 | 12-JUN-13:50 | 30.40 | 20.15 | 0.00 | 0.00 | 01-JUN-00:10 | 30.40 | 20.15 |
July | 0.125305E+11 | 19110.72 | 21-JUL-12:10 | 30.10 | 21.65 | 0.00 | 0.00 | 01-JUL-00:10 | 30.10 | 21.65 |
August | 0.110325E+11 | 18448.56 | 09-AUG-15:20 | 29.40 | 18.24 | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.24 |
September | 0.559276E+10 | 14141.75 | 21-SEP-15:40 | 26.10 | 17.00 | 0.00 | 0.00 | 01-SEP-00:10 | 26.10 | 17.00 |
October | 0.123622E+10 | 7992.11 | 11-OCT-15:40 | 21.87 | 14.55 | 0.00 | 0.00 | 01-OCT-00:10 | 21.87 | 14.55 |
November | 80614073.15 | 1622.80 | 16-NOV-13:10 | 18.62 | 13.01 | 0.00 | 0.00 | 01-NOV-00:10 | 18.62 | 13.01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 |
Annual Sum or Average | 0.493266E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -3.3 | -4.7 | 0.00 | 0.00 | -3.3 | -4.7 | ||
Maximum of Months | 0.125305E+11 | 19110.72 | 30.40 | 21.65 | 0.00 | 0.00 | 30.40 | 21.65 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.228778E+10 | 2001.94 | 12-JAN-16:40 | -6.5 | -8.3 | 95230015.44 | 126.82 | 12-JAN-10:09 | -6.5 | -8.3 |
February | 0.701956E+10 | 4224.60 | 28-FEB-17:00 | -0.6 | -3.0 | 86396464.26 | 126.82 | 21-FEB-10:09 | -0.6 | -3.0 |
March | 0.139498E+11 | 6998.85 | 31-MAR-24:00 | 4.20 | 3.93 | 0.103237E+09 | 126.83 | 14-MAR-09:00 | 4.20 | 3.93 |
April | 0.188195E+11 | 8181.42 | 02-APR-18:00 | 6.10 | 4.84 | 91605134.74 | 126.82 | 28-APR-13:00 | 10.00 | 9.06 |
May | 0.439670E+10 | 3491.37 | 31-MAY-24:00 | 17.10 | 14.03 | 99236149.78 | 126.85 | 17-MAY-13:00 | 17.10 | 14.03 |
June | 0.950637E+10 | 5395.04 | 30-JUN-24:00 | 16.90 | 13.02 | 98967396.34 | 126.86 | 21-JUN-09:00 | 16.90 | 13.02 |
July | 0.149702E+11 | 7295.82 | 31-JUL-24:00 | 19.10 | 16.93 | 91888857.37 | 126.84 | 05-JUL-13:00 | 19.10 | 16.93 |
August | 0.199428E+11 | 8302.43 | 02-AUG-18:40 | 22.07 | 14.68 | 0.103239E+09 | 126.83 | 30-AUG-09:30 | 18.60 | 17.72 |
September | 0.440120E+10 | 3216.30 | 30-SEP-24:00 | 14.40 | 12.09 | 91611811.04 | 126.85 | 25-SEP-13:00 | 14.40 | 12.09 |
October | 0.917692E+10 | 5162.55 | 31-OCT-24:00 | 6.60 | 4.77 | 95232476.20 | 126.84 | 12-OCT-13:39 | 6.60 | 4.77 |
November | 0.135743E+11 | 5919.65 | 24-NOV-16:20 | 3.87 | 1.42 | 94300311.25 | 126.82 | 06-NOV-10:20 | 3.87 | 1.42 |
December | 0.185062E+11 | 7807.67 | 04-DEC-16:20 | -1.1 | -3.7 | 91880867.13 | 126.82 | 01-DEC-14:09 | -1.1 | -3.7 |
Annual Sum or Average | 0.136551E+12 | 0.114283E+10 | ||||||||
Minimum of Months | 0.228778E+10 | 2001.94 | -6.5 | -8.3 | 86396464.26 | 126.82 | -6.5 | -8.3 | ||
Maximum of Months | 0.199428E+11 | 8302.43 | 22.07 | 16.93 | 0.103239E+09 | 126.86 | 19.10 | 17.72 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.423371E+09 | 1605.22 | 12-JAN-16:50 | -6.6 | -8.3 | 93618270.89 | 126.82 | 12-JAN-10:00 | -6.6 | -8.3 |
February | 0.435743E+10 | 3732.66 | 28-FEB-17:00 | -0.6 | -3.0 | 86396474.24 | 126.82 | 21-FEB-10:09 | -0.6 | -3.0 |
March | 0.116321E+11 | 6151.95 | 31-MAR-23:40 | 4.40 | 4.06 | 0.103237E+09 | 126.83 | 14-MAR-09:00 | 4.40 | 4.06 |
April | 0.168410E+11 | 7706.72 | 24-APR-18:00 | 11.70 | 8.10 | 91605163.53 | 126.82 | 28-APR-13:00 | 10.00 | 9.06 |
May | 0.362921E+10 | 3289.55 | 31-MAY-24:00 | 17.10 | 14.03 | 99235895.00 | 126.85 | 17-MAY-13:20 | 17.10 | 14.03 |
June | 0.877413E+10 | 5150.32 | 30-JUN-24:00 | 16.90 | 13.02 | 98967363.70 | 126.86 | 27-JUN-13:00 | 16.90 | 13.02 |
July | 0.140888E+11 | 7005.63 | 31-JUL-24:00 | 19.10 | 16.93 | 91889990.23 | 126.85 | 05-JUL-13:00 | 19.10 | 16.93 |
August | 0.188260E+11 | 7959.30 | 02-AUG-18:40 | 22.07 | 14.68 | 0.103239E+09 | 126.83 | 30-AUG-13:30 | 19.15 | 18.26 |
September | 0.361476E+10 | 2673.57 | 30-SEP-24:00 | 14.40 | 12.09 | 91609727.51 | 126.85 | 08-SEP-13:39 | 14.40 | 12.09 |
October | 0.745055E+10 | 4457.30 | 31-OCT-23:50 | 6.67 | 4.81 | 95232281.17 | 126.84 | 12-OCT-13:00 | 6.67 | 4.81 |
November | 0.111028E+11 | 5435.81 | 15-NOV-16:30 | 10.55 | 6.20 | 94300327.30 | 126.82 | 10-NOV-14:00 | 10.55 | 6.20 |
December | 0.148008E+11 | 6980.48 | 04-DEC-16:30 | -1.4 | -3.9 | 91880878.12 | 126.82 | 01-DEC-14:09 | -1.4 | -3.9 |
Annual Sum or Average | 0.115541E+12 | 0.114121E+10 | ||||||||
Minimum of Months | 0.423371E+09 | 1605.22 | -6.6 | -8.3 | 86396474.24 | 126.82 | -6.6 | -8.3 | ||
Maximum of Months | 0.188260E+11 | 7959.30 | 22.07 | 16.93 | 0.103239E+09 | 126.86 | 19.15 | 18.26 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.173037E+09 | 1391.04 | 12-JAN-16:40 | -6.5 | -8.3 | 89660141.49 | 127.21 | 19-JAN-10:39 | 1.10 | 0.02 |
February | 0.287165E+10 | 3682.54 | 28-FEB-17:00 | -0.6 | -3.0 | 86396183.81 | 126.82 | 21-FEB-10:09 | -0.6 | -3.0 |
March | 0.101159E+11 | 5739.93 | 31-MAR-23:20 | 4.60 | 4.18 | 0.103237E+09 | 126.83 | 14-MAR-09:00 | 4.60 | 4.18 |
April | 0.158008E+11 | 7702.92 | 24-APR-18:00 | 11.70 | 8.10 | 91605169.04 | 126.82 | 28-APR-13:00 | 10.00 | 9.06 |
May | 0.315094E+10 | 3189.88 | 31-MAY-23:40 | 17.17 | 13.97 | 99236030.38 | 126.84 | 17-MAY-13:20 | 17.17 | 13.97 |
June | 0.866384E+10 | 5075.03 | 30-JUN-23:40 | 17.07 | 12.89 | 98967514.01 | 126.86 | 27-JUN-13:00 | 17.07 | 12.89 |
July | 0.141028E+11 | 6994.28 | 31-JUL-24:00 | 19.10 | 16.93 | 91889997.24 | 126.85 | 05-JUL-13:00 | 19.10 | 16.93 |
August | 0.187629E+11 | 8012.39 | 02-AUG-18:40 | 22.07 | 14.68 | 0.103239E+09 | 126.83 | 30-AUG-13:30 | 19.15 | 18.26 |
September | 0.318387E+10 | 2406.93 | 04-SEP-17:43 | 16.97 | 12.18 | 91609418.28 | 126.85 | 08-SEP-13:00 | 22.80 | 18.10 |
October | 0.614199E+10 | 4093.48 | 11-OCT-17:00 | 21.70 | 14.52 | 95232242.60 | 126.84 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.942128E+10 | 5320.14 | 15-NOV-16:30 | 10.55 | 6.20 | 94300326.87 | 126.82 | 10-NOV-14:00 | 10.55 | 6.20 |
December | 0.129033E+11 | 6658.43 | 04-DEC-16:20 | -1.1 | -3.7 | 91880882.17 | 126.82 | 01-DEC-14:09 | -1.1 | -3.7 |
Annual Sum or Average | 0.105292E+12 | 0.113725E+10 | ||||||||
Minimum of Months | 0.173037E+09 | 1391.04 | -6.5 | -8.3 | 86396183.81 | 126.82 | -1.1 | -3.7 | ||
Maximum of Months | 0.187629E+11 | 8012.39 | 22.07 | 16.93 | 0.103239E+09 | 127.21 | 22.80 | 18.26 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.235083E+12 | 90926.03 | 12-JAN-16:55 | -6.7 | -8.2 | 0.206144E+10 | 2745.29 | 13-JAN-14:00 | 2.80 | -2.4 |
February | 0.432858E+12 | 182642.46 | 23-FEB-17:00 | -0.6 | -1.8 | 0.187023E+10 | 2745.32 | 15-FEB-10:09 | -0.6 | -1.8 |
March | 0.727487E+12 | 358185.38 | 31-MAR-24:00 | 4.20 | 3.93 | 0.223488E+10 | 2749.48 | 14-MAR-13:09 | 4.20 | 3.93 |
April | 0.942200E+12 | 367422.34 | 24-APR-16:00 | 13.30 | 7.63 | 0.198305E+10 | 2748.65 | 28-APR-09:09 | 10.00 | 8.84 |
May | 0.240147E+12 | 176000.86 | 31-MAY-24:00 | 17.10 | 14.03 | 0.214808E+10 | 2745.68 | 10-MAY-13:09 | 17.10 | 14.03 |
June | 0.471194E+12 | 268366.79 | 30-JUN-24:00 | 16.90 | 13.02 | 0.214236E+10 | 2748.71 | 01-JUN-13:00 | 16.90 | 13.02 |
July | 0.733698E+12 | 360669.28 | 31-JUL-24:00 | 19.10 | 16.93 | 0.199635E+10 | 2990.72 | 21-JUL-09:09 | 19.10 | 16.93 |
August | 0.978388E+12 | 381878.01 | 15-AUG-16:51 | 20.60 | 19.08 | 0.231100E+10 | 3743.97 | 15-AUG-13:09 | 20.60 | 19.08 |
September | 0.236397E+12 | 175503.80 | 30-SEP-24:00 | 14.40 | 12.09 | 0.198297E+10 | 2746.44 | 21-SEP-13:09 | 14.40 | 12.09 |
October | 0.486956E+12 | 268374.60 | 31-OCT-24:00 | 6.60 | 4.77 | 0.206144E+10 | 2746.15 | 23-OCT-09:30 | 6.60 | 4.77 |
November | 0.707684E+12 | 276477.20 | 06-NOV-17:00 | 6.10 | 3.25 | 0.204137E+10 | 2746.90 | 16-NOV-14:09 | 17.20 | 13.27 |
December | 0.973861E+12 | 367249.93 | 04-DEC-17:00 | -2.2 | -4.4 | 0.198898E+10 | 2747.39 | 01-DEC-10:00 | -2.2 | -4.4 |
Annual Sum or Average | 0.716595E+13 | 0.248222E+11 | ||||||||
Minimum of Months | 0.235083E+12 | 90926.03 | -6.7 | -8.2 | 0.187023E+10 | 2745.29 | -2.2 | -4.4 | ||
Maximum of Months | 0.978388E+12 | 381878.01 | 20.60 | 19.08 | 0.231100E+10 | 3743.97 | 20.60 | 19.08 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.676251E+09 | 50613.63 | 02-JAN-04:01 | -1.0 |
February | 0.115143E+09 | 41657.15 | 06-FEB-05:01 | -14.8 |
March | 2231309.40 | 37188.49 | 06-MAR-06:01 | -11.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 89059555.70 | 41562.75 | 11-DEC-05:01 | -17.5 |
Annual Sum or Average | 0.882685E+09 | |||
Minimum of Months | 0.00 | 0.00 | -17.5 | |
Maximum of Months | 0.676251E+09 | 50613.63 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.531564E+10 | 79950.09 | 02-JAN-04:01 | -1.0 |
February | 0.435875E+10 | 79582.05 | 06-FEB-04:11 | -15.0 |
March | 0.150720E+10 | 76437.75 | 06-MAR-04:01 | -11.1 |
April | 0.277271E+09 | 71986.24 | 17-APR-04:11 | -3.5 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.273885E+09 | 70328.62 | 30-OCT-04:01 | -0.5 |
November | 0.793021E+09 | 72364.59 | 24-NOV-05:11 | -3.2 |
December | 0.394603E+10 | 79742.15 | 26-DEC-04:11 | -11.9 |
Annual Sum or Average | 0.164718E+11 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.531564E+10 | 79950.09 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.500834E+09 | 12215.23 | 30-JAN-05:01 | -9.5 |
February | 0.349969E+09 | 12632.60 | 06-FEB-05:01 | -14.8 |
March | 51460466.85 | 11565.60 | 07-MAR-06:01 | -13.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.129200E+09 | 12012.97 | 11-DEC-05:01 | -17.5 |
Annual Sum or Average | 0.103146E+10 | |||
Minimum of Months | 0.00 | 0.00 | -17.5 | |
Maximum of Months | 0.500834E+09 | 12632.60 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.386301E+09 | 11988.25 | 30-JAN-05:01 | -9.5 |
February | 0.301115E+09 | 12470.88 | 07-FEB-05:01 | -15.7 |
March | 37456948.44 | 10902.38 | 06-MAR-06:01 | -11.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 49598.75 | 578.65 | 17-OCT-05:04 | -2.8 |
November | 590375.16 | 2165.81 | 24-NOV-06:03 | -3.8 |
December | 0.214455E+09 | 12007.11 | 11-DEC-05:01 | -17.5 |
Annual Sum or Average | 0.939968E+09 | |||
Minimum of Months | 0.00 | 0.00 | -17.5 | |
Maximum of Months | 0.386301E+09 | 12470.88 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.759459E+09 | 18492.57 | 30-JAN-05:01 | -9.5 |
February | 0.643205E+09 | 18808.81 | 06-FEB-04:01 | -15.0 |
March | 84886680.01 | 16763.02 | 06-MAR-05:01 | -11.1 |
April | 2603347.56 | 7055.87 | 17-APR-05:03 | -4.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 943780.02 | 7751.32 | 30-OCT-05:01 | -0.1 |
November | 8449839.90 | 13339.37 | 24-NOV-06:03 | -3.8 |
December | 0.324842E+09 | 17837.60 | 11-DEC-05:01 | -17.5 |
Annual Sum or Average | 0.182439E+10 | |||
Minimum of Months | 0.00 | 0.00 | -17.5 | |
Maximum of Months | 0.759459E+09 | 18808.81 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 79742178.37 | 9051.17 | 30-JAN-05:01 | -9.5 |
February | 33554966.09 | 9536.16 | 06-FEB-05:01 | -14.8 |
March | 53700.73 | 895.01 | 06-MAR-06:01 | -11.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 1222767.61 | 8369.14 | 11-DEC-06:01 | -18.5 |
Annual Sum or Average | 0.114574E+09 | |||
Minimum of Months | 0.00 | 0.00 | -18.5 | |
Maximum of Months | 79742178.37 | 9536.16 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.521479E+10 | 13556.62 | 02-JAN-02:62 | -1.7 |
February | 0.418642E+10 | 13669.16 | 06-FEB-04:01 | -15.0 |
March | 0.141496E+10 | 13120.86 | 06-MAR-04:01 | -11.1 |
April | 0.137640E+09 | 11788.30 | 17-APR-04:01 | -3.4 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.108436E+09 | 11423.48 | 30-OCT-04:01 | -0.5 |
November | 0.476255E+09 | 12062.45 | 24-NOV-05:01 | -3.0 |
December | 0.402688E+10 | 13581.23 | 26-DEC-04:01 | -11.8 |
Annual Sum or Average | 0.155654E+11 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.521479E+10 | 13669.16 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.298215E+10 | 18473.42 | 02-JAN-04:01 | -1.0 |
February | 0.238440E+10 | 18661.10 | 13-FEB-04:01 | -8.9 |
March | 0.590782E+09 | 17962.97 | 06-MAR-04:01 | -11.1 |
April | 66697568.33 | 15663.55 | 17-APR-04:01 | -3.4 |
May | 17051.88 | 142.10 | 01-MAY-05:04 | 1.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 17307.93 | 144.23 | 30-SEP-05:04 | 7.20 |
October | 65615514.48 | 15333.07 | 30-OCT-04:01 | -0.5 |
November | 0.315667E+09 | 16407.94 | 24-NOV-05:01 | -3.0 |
December | 0.254067E+10 | 18563.65 | 26-DEC-04:01 | -11.8 |
Annual Sum or Average | 0.894601E+10 | |||
Minimum of Months | 0.00 | 0.00 | -11.8 | |
Maximum of Months | 0.298215E+10 | 18661.10 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.322924E+10 | 21715.57 | 02-JAN-04:01 | -1.0 |
February | 0.269932E+10 | 21940.58 | 13-FEB-04:01 | -8.9 |
March | 0.576000E+09 | 19932.24 | 06-MAR-04:01 | -11.1 |
April | 95977578.79 | 18205.05 | 17-APR-04:01 | -3.4 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 48475611.69 | 17348.21 | 30-OCT-04:01 | -0.5 |
November | 0.310658E+09 | 19182.88 | 24-NOV-05:01 | -3.0 |
December | 0.258347E+10 | 21864.75 | 26-DEC-04:01 | -11.8 |
Annual Sum or Average | 0.954315E+10 | |||
Minimum of Months | 0.00 | 0.00 | -11.8 | |
Maximum of Months | 0.322924E+10 | 21940.58 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.255678E+10 | 18425.43 | 02-JAN-04:01 | -1.0 |
February | 0.195286E+10 | 18598.90 | 06-FEB-04:01 | -15.0 |
March | 0.438489E+09 | 17319.86 | 06-MAR-04:01 | -11.1 |
April | 30831791.94 | 9063.57 | 17-APR-05:03 | -4.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 35592669.30 | 14208.83 | 30-OCT-05:01 | -0.1 |
November | 0.193935E+09 | 15665.46 | 24-NOV-05:01 | -3.0 |
December | 0.181902E+10 | 18450.12 | 26-DEC-04:01 | -11.8 |
Annual Sum or Average | 0.702751E+10 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.255678E+10 | 18598.90 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.974355E+10 | 16071.57 | 09-JAN-02:62 | -8.5 |
February | 0.826953E+10 | 16526.63 | 06-FEB-02:52 | -13.9 |
March | 0.384815E+10 | 15709.39 | 06-MAR-03:23 | -10.8 |
April | 0.877307E+09 | 14762.38 | 17-APR-03:01 | -2.9 |
May | 28160590.14 | 12033.09 | 01-MAY-05:02 | 1.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 17826993.50 | 12116.30 | 30-SEP-05:02 | 7.20 |
October | 0.789295E+09 | 14865.74 | 30-OCT-03:01 | -0.1 |
November | 0.223790E+10 | 14792.24 | 20-NOV-05:11 | 5.00 |
December | 0.859139E+10 | 16155.70 | 26-DEC-00:52 | -11.1 |
Annual Sum or Average | 0.344031E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.9 | |
Maximum of Months | 0.974355E+10 | 16526.63 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.562054E+10 | 21042.85 | 09-JAN-02:62 | -8.5 |
February | 0.478532E+10 | 21775.21 | 06-FEB-02:52 | -13.9 |
March | 0.175668E+10 | 20691.72 | 06-MAR-04:01 | -11.1 |
April | 0.405799E+09 | 19566.91 | 17-APR-03:01 | -2.9 |
May | 13030988.13 | 11101.88 | 01-MAY-05:02 | 1.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 12464599.63 | 14875.07 | 30-SEP-05:02 | 7.20 |
October | 0.420086E+09 | 19808.03 | 30-OCT-03:01 | -0.1 |
November | 0.131579E+10 | 19751.31 | 20-NOV-05:11 | 5.00 |
December | 0.537147E+10 | 21227.78 | 26-DEC-04:11 | -11.9 |
Annual Sum or Average | 0.197012E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.9 | |
Maximum of Months | 0.562054E+10 | 21775.21 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.664779E+10 | 24124.44 | 29-JAN-22:52 | -8.9 |
February | 0.590861E+10 | 25041.36 | 06-FEB-03:32 | -14.6 |
March | 0.207799E+10 | 23554.59 | 06-MAR-04:01 | -11.1 |
April | 0.657551E+09 | 22518.79 | 17-APR-03:01 | -2.9 |
May | 27705471.75 | 16682.14 | 01-MAY-05:02 | 1.70 |
June | 44415.24 | 222.08 | 14-JUN-05:03 | 6.78 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 11890335.83 | 14907.84 | 30-SEP-05:02 | 7.20 |
October | 0.463225E+09 | 22535.26 | 30-OCT-03:01 | -0.1 |
November | 0.157194E+10 | 22786.83 | 20-NOV-05:11 | 5.00 |
December | 0.621887E+10 | 24505.96 | 26-DEC-00:52 | -11.1 |
Annual Sum or Average | 0.235856E+11 | |||
Minimum of Months | 0.00 | 0.00 | -14.6 | |
Maximum of Months | 0.664779E+10 | 25041.36 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.507396E+10 | 22315.09 | 09-JAN-02:62 | -8.5 |
February | 0.389785E+10 | 22861.77 | 06-FEB-02:52 | -13.9 |
March | 0.136472E+10 | 21759.94 | 06-MAR-04:01 | -11.1 |
April | 0.273707E+09 | 20025.04 | 17-APR-03:01 | -2.9 |
May | 2270240.62 | 5380.47 | 01-MAY-05:02 | 1.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 4753908.83 | 6410.84 | 30-SEP-05:02 | 7.20 |
October | 0.280694E+09 | 20029.63 | 30-OCT-03:01 | -0.1 |
November | 0.898077E+09 | 20733.52 | 24-NOV-04:01 | -3.2 |
December | 0.395984E+10 | 22360.06 | 26-DEC-04:11 | -11.9 |
Annual Sum or Average | 0.157559E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.9 | |
Maximum of Months | 0.507396E+10 | 22861.77 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.960458E+09 | 10750.53 | 11-JAN-06:03 | 5.68 |
February | 0.949994E+09 | 11573.15 | 15-FEB-06:02 | 5.60 |
March | 0.190656E+09 | 11129.90 | 02-MAR-06:01 | 1.10 |
April | 0.110548E+09 | 11184.90 | 20-APR-04:12 | 11.50 |
May | 69974802.28 | 9228.49 | 14-MAY-14:32 | 25.73 |
June | 91634207.98 | 9598.41 | 27-JUN-04:11 | 20.77 |
July | 0.161532E+09 | 9348.08 | 16-JUL-15:32 | 30.20 |
August | 0.135056E+09 | 10544.57 | 13-AUG-15:02 | 29.90 |
September | 75980260.32 | 9672.49 | 14-SEP-04:12 | 20.60 |
October | 75641900.09 | 9643.05 | 10-OCT-04:11 | 10.00 |
November | 73117441.78 | 11902.57 | 27-NOV-05:12 | 17.97 |
December | 0.373439E+09 | 12067.84 | 14-DEC-06:02 | 5.68 |
Annual Sum or Average | 0.326803E+10 | |||
Minimum of Months | 69974802.28 | 9228.49 | 1.10 | |
Maximum of Months | 0.960458E+09 | 12067.84 | 30.20 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.432219E+10 | 18443.85 | 02-JAN-06:12 | -1.1 |
February | 0.331388E+10 | 9024.78 | 06-FEB-06:12 | -13.9 |
March | 0.148687E+10 | 7384.41 | 26-MAR-13:53 | -0.6 |
April | 0.362306E+09 | 7455.80 | 02-APR-16:52 | 6.70 |
May | 53566828.76 | 7696.96 | 21-MAY-14:42 | 19.40 |
June | 57006611.39 | 8520.15 | 11-JUN-14:41 | 26.02 |
July | 70218394.36 | 8547.89 | 16-JUL-15:52 | 30.60 |
August | 45044688.55 | 10009.73 | 13-AUG-15:31 | 29.60 |
September | 56219310.25 | 9736.84 | 04-SEP-15:52 | 18.30 |
October | 0.251390E+09 | 7509.83 | 09-OCT-12:13 | 11.87 |
November | 0.565965E+09 | 6048.61 | 16-NOV-06:02 | 11.78 |
December | 0.276056E+10 | 8181.86 | 11-DEC-06:12 | -18.2 |
Annual Sum or Average | 0.133452E+11 | |||
Minimum of Months | 45044688.55 | 6048.61 | -18.2 | |
Maximum of Months | 0.432219E+10 | 18443.85 | 30.60 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.131376E+11 | 27752.00 | 30-JAN-05:42 | -9.9 |
February | 0.112066E+11 | 30327.23 | 06-FEB-05:12 | -14.6 |
March | 0.556436E+10 | 27920.41 | 06-MAR-06:12 | -11.1 |
April | 0.203539E+10 | 20311.26 | 17-APR-05:03 | -4.0 |
May | 0.542456E+09 | 14806.68 | 16-MAY-05:02 | 11.10 |
June | 0.148992E+09 | 12494.71 | 24-JUN-05:03 | 10.78 |
July | 75402253.61 | 13882.02 | 03-JUL-05:02 | 11.78 |
August | 95694685.60 | 13116.04 | 03-AUG-05:03 | 11.10 |
September | 0.405090E+09 | 13917.56 | 19-SEP-05:03 | 10.60 |
October | 0.190999E+10 | 17442.07 | 30-OCT-05:13 | -0.2 |
November | 0.432145E+10 | 21203.92 | 24-NOV-05:23 | -3.3 |
December | 0.118311E+11 | 29680.59 | 11-DEC-05:31 | -18.3 |
Annual Sum or Average | 0.512741E+11 | |||
Minimum of Months | 75402253.61 | 12494.71 | -18.3 | |
Maximum of Months | 0.131376E+11 | 30327.23 | 11.78 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.535318E+09 | 559.88 | 03-JAN-01:20 | -2.8 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
Annual Sum or Average | 0.535318E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.535318E+09 | 559.88 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.782624E+09 | 599.25 | 24-JAN-00:10 | -11.1 |
February | 0.115069E+09 | 559.68 | 05-FEB-22:30 | -12.8 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 165286.18 | 372.64 | 01-MAY-05:55 | 1.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
Annual Sum or Average | 0.897859E+09 | |||
Minimum of Months | 0.00 | 0.00 | -12.8 | |
Maximum of Months | 0.782624E+09 | 599.25 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:05 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.180249E+11 | 19402.09 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.163527E+11 | 19402.09 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.194806E+11 | 19402.09 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.173504E+11 | 19402.09 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.187528E+11 | 19402.09 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.186803E+11 | 19402.09 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.174228E+11 | 19402.09 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.194803E+11 | 19402.09 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.173504E+11 | 19402.09 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.180252E+11 | 19402.09 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.178272E+11 | 19402.09 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.174231E+11 | 19402.09 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.216171E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.163527E+11 | 19402.09 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.194806E+11 | 19402.09 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243681E+11 | 17206.63 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.63 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253549E+11 | 17206.63 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235306E+11 | 17206.63 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248615E+11 | 17206.63 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244160E+11 | 17206.63 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239708E+11 | 17206.63 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253549E+11 | 17206.63 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235199E+11 | 17206.63 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243735E+11 | 17206.63 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238373E+11 | 17206.63 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239654E+11 | 17206.63 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289614E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.63 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253549E+11 | 17206.63 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.161876E+11 | 17424.44 | 02-JAN-08:09 | 0.243680E+11 | 17206.56 | 02-JAN-08:09 |
February | 0.146859E+11 | 17424.44 | 01-FEB-08:09 | 0.220609E+11 | 17206.56 | 01-FEB-08:09 |
March | 0.174950E+11 | 17424.44 | 01-MAR-08:09 | 0.253548E+11 | 17206.56 | 01-MAR-08:09 |
April | 0.155819E+11 | 17424.44 | 03-APR-07:10 | 0.235305E+11 | 17206.56 | 03-APR-07:10 |
May | 0.168413E+11 | 17424.44 | 01-MAY-07:10 | 0.248614E+11 | 17206.56 | 01-MAY-07:10 |
June | 0.167763E+11 | 17424.44 | 01-JUN-07:10 | 0.244159E+11 | 17206.56 | 01-JUN-07:10 |
July | 0.156469E+11 | 17424.44 | 03-JUL-07:10 | 0.239707E+11 | 17206.56 | 03-JUL-07:10 |
August | 0.174947E+11 | 17424.44 | 01-AUG-07:10 | 0.253548E+11 | 17206.56 | 01-AUG-07:10 |
September | 0.155819E+11 | 17424.44 | 01-SEP-07:10 | 0.235198E+11 | 17206.56 | 01-SEP-07:10 |
October | 0.161879E+11 | 17424.44 | 02-OCT-07:10 | 0.243734E+11 | 17206.56 | 02-OCT-07:10 |
November | 0.160101E+11 | 17424.44 | 01-NOV-07:10 | 0.238372E+11 | 17206.56 | 01-NOV-07:10 |
December | 0.156472E+11 | 17424.44 | 01-DEC-08:09 | 0.239653E+11 | 17206.56 | 01-DEC-08:09 |
Annual Sum or Average | 0.194137E+12 | 0.289613E+12 | ||||
Minimum of Months | 0.146859E+11 | 17424.44 | 0.220609E+11 | 17206.56 | ||
Maximum of Months | 0.174950E+11 | 17424.44 | 0.253548E+11 | 17206.56 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.133168E+10 | 2187.81 | 02-JAN-16:40 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.111908E+10 | 2187.81 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.123761E+10 | 1625.25 | 17-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.105548E+10 | 1524.25 | 12-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.110994E+10 | 1141.96 | 10-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.108781E+10 | 1040.96 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.102105E+10 | 1141.96 | 11-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.115889E+10 | 1141.96 | 21-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.108641E+10 | 1524.25 | 26-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.120305E+10 | 2187.81 | 30-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.133761E+10 | 2187.81 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.133969E+10 | 2187.81 | 01-DEC-16:19 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.140883E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.102105E+10 | 1040.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.133969E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.835495E+09 | 1409.91 | 02-JAN-16:40 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.713137E+09 | 1409.91 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.792001E+09 | 982.28 | 17-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.680346E+09 | 801.02 | 12-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.720028E+09 | 735.93 | 11-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.705871E+09 | 670.83 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.662100E+09 | 735.93 | 17-JUL-15:20 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.750539E+09 | 735.93 | 24-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.697050E+09 | 982.28 | 26-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.761660E+09 | 1228.64 | 23-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.840538E+09 | 1409.91 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.837772E+09 | 1409.91 | 01-DEC-16:19 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.899654E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.662100E+09 | 670.83 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.840538E+09 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.126234E+10 | 2187.86 | 02-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.109120E+10 | 1906.57 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.122366E+10 | 1524.28 | 13-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.105771E+10 | 1524.28 | 12-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.111864E+10 | 1243.00 | 11-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.109620E+10 | 1141.99 | 19-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.102937E+10 | 1141.99 | 11-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.116524E+10 | 1243.00 | 24-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.108038E+10 | 1524.28 | 26-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.117102E+10 | 2187.86 | 30-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.127365E+10 | 2187.86 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.126869E+10 | 2187.86 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.138381E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.102937E+10 | 1141.99 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.127365E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.832172E+09 | 1409.91 | 02-JAN-16:49 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.710069E+09 | 1409.91 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.792992E+09 | 1228.64 | 13-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.681529E+09 | 982.28 | 12-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.716997E+09 | 801.02 | 11-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.702181E+09 | 735.93 | 05-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.660416E+09 | 801.02 | 11-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.748012E+09 | 801.02 | 21-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.699870E+09 | 1228.64 | 26-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.768885E+09 | 1409.91 | 26-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.837734E+09 | 1409.91 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.839111E+09 | 1409.91 | 01-DEC-16:19 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.898997E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.660416E+09 | 735.93 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.839111E+09 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.132653E+10 | 2187.81 | 02-JAN-16:40 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.111574E+10 | 2187.81 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.123488E+10 | 1524.25 | 13-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.105434E+10 | 1524.25 | 12-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.110892E+10 | 1141.96 | 10-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.108711E+10 | 1040.96 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.102067E+10 | 1141.96 | 11-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.115790E+10 | 1141.96 | 21-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.108463E+10 | 1524.25 | 26-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.119977E+10 | 2187.81 | 30-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.133234E+10 | 2187.81 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.133462E+10 | 2187.81 | 01-DEC-16:19 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.140574E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.102067E+10 | 1040.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.133462E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.832903E+09 | 1409.91 | 02-JAN-16:40 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.711938E+09 | 1409.91 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.791081E+09 | 982.28 | 17-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.679822E+09 | 801.02 | 12-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.719190E+09 | 735.93 | 11-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.705346E+09 | 670.83 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.661657E+09 | 735.93 | 17-JUL-15:39 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.749820E+09 | 735.93 | 24-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.696089E+09 | 982.28 | 26-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.760279E+09 | 1228.64 | 23-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.838332E+09 | 1409.91 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.834892E+09 | 1409.91 | 01-DEC-16:19 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.898135E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.661657E+09 | 670.83 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.838332E+09 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.126028E+10 | 2187.86 | 02-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.108923E+10 | 1906.57 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.122241E+10 | 1524.28 | 13-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.105651E+10 | 1524.28 | 12-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.111736E+10 | 1141.99 | 10-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.109524E+10 | 1040.98 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.102833E+10 | 1141.99 | 11-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.116432E+10 | 1141.99 | 21-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.107904E+10 | 1524.28 | 26-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.116996E+10 | 2187.86 | 30-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.127193E+10 | 2187.86 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.126714E+10 | 2187.86 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.138217E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.102833E+10 | 1040.98 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.127193E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.830013E+09 | 1409.91 | 02-JAN-16:49 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.708861E+09 | 1409.91 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.791639E+09 | 1228.64 | 13-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.680475E+09 | 982.28 | 12-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.716196E+09 | 801.02 | 11-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.701681E+09 | 735.93 | 07-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.659792E+09 | 801.02 | 11-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.747278E+09 | 801.02 | 21-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.698645E+09 | 1228.64 | 26-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.766669E+09 | 1409.91 | 26-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.834826E+09 | 1409.91 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.836059E+09 | 1409.91 | 01-DEC-16:19 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.897213E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.659792E+09 | 735.93 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.836059E+09 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.132607E+10 | 2187.81 | 02-JAN-16:40 | 0.305979E+10 | 2160.55 | 02-JAN-08:09 |
February | 0.111566E+10 | 2187.81 | 01-FEB-08:09 | 0.277008E+10 | 2160.55 | 01-FEB-08:09 |
March | 0.123455E+10 | 1524.25 | 13-MAR-07:10 | 0.318369E+10 | 2160.55 | 01-MAR-08:09 |
April | 0.105418E+10 | 1524.25 | 12-APR-07:10 | 0.295462E+10 | 2160.55 | 03-APR-07:10 |
May | 0.110883E+10 | 1141.96 | 10-MAY-07:10 | 0.312174E+10 | 2160.55 | 01-MAY-07:10 |
June | 0.108711E+10 | 1040.96 | 01-JUN-07:10 | 0.306580E+10 | 2160.55 | 01-JUN-07:10 |
July | 0.102065E+10 | 1141.96 | 11-JUL-07:10 | 0.300989E+10 | 2160.55 | 03-JUL-07:10 |
August | 0.115787E+10 | 1141.96 | 21-AUG-07:10 | 0.318369E+10 | 2160.55 | 01-AUG-07:10 |
September | 0.108457E+10 | 1524.25 | 26-SEP-07:10 | 0.295328E+10 | 2160.55 | 01-SEP-07:10 |
October | 0.119945E+10 | 2187.81 | 30-OCT-07:10 | 0.306046E+10 | 2160.55 | 02-OCT-07:10 |
November | 0.133192E+10 | 2187.81 | 01-NOV-07:10 | 0.299314E+10 | 2160.55 | 01-NOV-07:10 |
December | 0.133427E+10 | 2187.81 | 01-DEC-16:19 | 0.300922E+10 | 2160.55 | 01-DEC-08:09 |
Annual Sum or Average | 0.140551E+11 | 0.363654E+11 | ||||
Minimum of Months | 0.102065E+10 | 1040.96 | 0.277008E+10 | 2160.55 | ||
Maximum of Months | 0.133427E+10 | 2187.81 | 0.318369E+10 | 2160.55 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.832824E+09 | 1409.91 | 02-JAN-16:40 | 0.197184E+10 | 1392.34 | 02-JAN-08:09 |
February | 0.711932E+09 | 1409.91 | 01-FEB-16:00 | 0.178515E+10 | 1392.34 | 01-FEB-08:09 |
March | 0.791027E+09 | 982.28 | 17-MAR-07:10 | 0.205169E+10 | 1392.34 | 01-MAR-08:09 |
April | 0.679822E+09 | 801.02 | 12-APR-07:10 | 0.190407E+10 | 1392.34 | 03-APR-07:10 |
May | 0.719123E+09 | 735.93 | 11-MAY-07:10 | 0.201177E+10 | 1392.34 | 01-MAY-07:10 |
June | 0.705346E+09 | 670.83 | 01-JUN-07:10 | 0.197572E+10 | 1392.34 | 01-JUN-07:10 |
July | 0.661637E+09 | 735.93 | 17-JUL-15:39 | 0.193969E+10 | 1392.34 | 03-JUL-07:10 |
August | 0.749730E+09 | 735.93 | 24-AUG-07:10 | 0.205169E+10 | 1392.34 | 01-AUG-07:10 |
September | 0.695978E+09 | 982.28 | 26-SEP-07:10 | 0.190321E+10 | 1392.34 | 01-SEP-07:10 |
October | 0.760275E+09 | 1228.64 | 23-OCT-07:10 | 0.197228E+10 | 1392.34 | 02-OCT-07:10 |
November | 0.838170E+09 | 1409.91 | 01-NOV-07:10 | 0.192889E+10 | 1392.34 | 01-NOV-07:10 |
December | 0.834557E+09 | 1409.91 | 01-DEC-16:19 | 0.193926E+10 | 1392.34 | 01-DEC-08:09 |
Annual Sum or Average | 0.898042E+10 | 0.234352E+11 | ||||
Minimum of Months | 0.661637E+09 | 670.83 | 0.178515E+10 | 1392.34 | ||
Maximum of Months | 0.838170E+09 | 1409.91 | 0.205169E+10 | 1392.34 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.126026E+10 | 2187.86 | 02-JAN-16:49 | 0.305983E+10 | 2160.58 | 02-JAN-08:09 |
February | 0.108923E+10 | 1906.57 | 01-FEB-08:09 | 0.277013E+10 | 2160.58 | 01-FEB-08:09 |
March | 0.122222E+10 | 1524.28 | 13-MAR-07:10 | 0.318374E+10 | 2160.58 | 01-MAR-08:09 |
April | 0.105647E+10 | 1524.28 | 12-APR-07:10 | 0.295467E+10 | 2160.58 | 03-APR-07:10 |
May | 0.111734E+10 | 1141.99 | 10-MAY-07:10 | 0.312179E+10 | 2160.58 | 01-MAY-07:10 |
June | 0.109521E+10 | 1040.98 | 01-JUN-07:10 | 0.306585E+10 | 2160.58 | 01-JUN-07:10 |
July | 0.102827E+10 | 1141.99 | 11-JUL-07:10 | 0.300994E+10 | 2160.58 | 03-JUL-07:10 |
August | 0.116425E+10 | 1141.99 | 21-AUG-07:10 | 0.318374E+10 | 2160.58 | 01-AUG-07:10 |
September | 0.107891E+10 | 1524.28 | 26-SEP-07:10 | 0.295333E+10 | 2160.58 | 01-SEP-07:10 |
October | 0.116995E+10 | 2187.86 | 30-OCT-07:10 | 0.306051E+10 | 2160.58 | 02-OCT-07:10 |
November | 0.127164E+10 | 2187.86 | 01-NOV-07:10 | 0.299318E+10 | 2160.58 | 01-NOV-07:10 |
December | 0.126708E+10 | 2187.86 | 01-DEC-16:19 | 0.300927E+10 | 2160.58 | 01-DEC-08:09 |
Annual Sum or Average | 0.138208E+11 | 0.363660E+11 | ||||
Minimum of Months | 0.102827E+10 | 1040.98 | 0.277013E+10 | 2160.58 | ||
Maximum of Months | 0.127164E+10 | 2187.86 | 0.318374E+10 | 2160.58 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.829826E+09 | 1409.91 | 02-JAN-16:49 | 0.197183E+10 | 1392.33 | 02-JAN-08:09 |
February | 0.708861E+09 | 1409.91 | 01-FEB-08:09 | 0.178514E+10 | 1392.33 | 01-FEB-08:09 |
March | 0.791603E+09 | 1228.64 | 13-MAR-07:10 | 0.205168E+10 | 1392.33 | 01-MAR-08:09 |
April | 0.680390E+09 | 982.28 | 12-APR-07:10 | 0.190406E+10 | 1392.33 | 03-APR-07:10 |
May | 0.716118E+09 | 801.02 | 11-MAY-07:10 | 0.201175E+10 | 1392.33 | 01-MAY-07:10 |
June | 0.701625E+09 | 735.93 | 07-JUN-07:10 | 0.197570E+10 | 1392.33 | 01-JUN-07:10 |
July | 0.659787E+09 | 801.02 | 11-JUL-07:10 | 0.193968E+10 | 1392.33 | 03-JUL-07:10 |
August | 0.747239E+09 | 801.02 | 21-AUG-07:10 | 0.205168E+10 | 1392.33 | 01-AUG-07:10 |
September | 0.698643E+09 | 1228.64 | 26-SEP-07:10 | 0.190319E+10 | 1392.33 | 01-SEP-07:10 |
October | 0.766554E+09 | 1409.91 | 26-OCT-07:10 | 0.197226E+10 | 1392.33 | 02-OCT-07:10 |
November | 0.834490E+09 | 1409.91 | 01-NOV-07:10 | 0.192888E+10 | 1392.33 | 01-NOV-07:10 |
December | 0.835978E+09 | 1409.91 | 01-DEC-16:19 | 0.193924E+10 | 1392.33 | 01-DEC-08:09 |
Annual Sum or Average | 0.897112E+10 | 0.234351E+11 | ||||
Minimum of Months | 0.659787E+09 | 735.93 | 0.178514E+10 | 1392.33 | ||
Maximum of Months | 0.835978E+09 | 1409.91 | 0.205168E+10 | 1392.33 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.430130E+09 | 450.11 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.390160E+09 | 450.11 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.463618E+09 | 450.11 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.414106E+09 | 450.11 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.446874E+09 | 450.11 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.444713E+09 | 450.11 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.416266E+09 | 450.11 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.463618E+09 | 450.11 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.414106E+09 | 450.11 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.430130E+09 | 450.11 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.425088E+09 | 450.11 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.416266E+09 | 450.11 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.515507E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.390160E+09 | 450.11 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.463618E+09 | 450.11 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.522764E+10 | 5470.56 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.474186E+10 | 5470.56 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.563465E+10 | 5470.56 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.503289E+10 | 5470.56 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.543115E+10 | 5470.56 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.540489E+10 | 5470.56 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.505915E+10 | 5470.56 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.563465E+10 | 5470.56 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.503289E+10 | 5470.56 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.522764E+10 | 5470.56 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.516637E+10 | 5470.56 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.505915E+10 | 5470.56 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.626529E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.474186E+10 | 5470.56 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.563465E+10 | 5470.56 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.180249E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.163527E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.194806E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.173504E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.187528E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.186803E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.174228E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.194803E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.173504E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.180252E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.178272E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.174231E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.216171E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.163527E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.194806E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238373E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289614E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.161876E+11 | 0.243680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.155819E+11 | 0.235305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.168413E+11 | 0.248614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.167763E+11 | 0.244159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.156469E+11 | 0.239707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.174947E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.155819E+11 | 0.235198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.161879E+11 | 0.243734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.160101E+11 | 0.238372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.156472E+11 | 0.239653E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.194137E+12 | 0.289613E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.146859E+11 | 0.220609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.174950E+11 | 0.253548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.133168E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.773451E+09 |
February | 0.136985E+10 | 0.111908E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.822561E+09 |
March | 0.163685E+10 | 0.123761E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 162086.85 | 0.518805E+09 |
April | 0.145243E+10 | 0.105548E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427988E+09 |
May | 0.157338E+10 | 0.110994E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87716.60 | 0.244206E+09 |
June | 0.156900E+10 | 0.108781E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3849338.11 | 0.138828E+09 |
July | 0.145680E+10 | 0.102105E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9770058.48 | 80148070.76 |
August | 0.163685E+10 | 0.115889E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7520388.68 | 90317963.93 |
September | 0.145243E+10 | 0.108641E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 544482.83 | 0.144569E+09 |
October | 0.150991E+10 | 0.120305E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334902E+09 |
November | 0.149516E+10 | 0.133761E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463567E+09 |
December | 0.145680E+10 | 0.133969E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.847584E+09 |
Annual Sum or Average | 0.181194E+11 | 0.140883E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21934071.53 | 0.488693E+10 |
Minimum of Months | 0.136985E+10 | 0.102105E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80148070.76 |
Maximum of Months | 0.163685E+10 | 0.133969E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9770058.48 | 0.847584E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.835495E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.513952E+09 |
February | 0.882782E+09 | 0.713137E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543698E+09 |
March | 0.105485E+10 | 0.792001E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108272.41 | 0.341937E+09 |
April | 0.936002E+09 | 0.680346E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278296E+09 |
May | 0.101394E+10 | 0.720028E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 105026.13 | 0.162692E+09 |
June | 0.101113E+10 | 0.705871E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2741189.23 | 89912125.58 |
July | 0.938820E+09 | 0.662100E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7164693.92 | 48377509.09 |
August | 0.105485E+10 | 0.750539E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5492541.79 | 54020504.71 |
September | 0.936002E+09 | 0.697050E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 397946.35 | 95106996.41 |
October | 0.973041E+09 | 0.761660E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219974E+09 |
November | 0.963541E+09 | 0.840538E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298934E+09 |
December | 0.938820E+09 | 0.837772E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552070E+09 |
Annual Sum or Average | 0.116768E+11 | 0.899654E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 16009669.84 | 0.319897E+10 |
Minimum of Months | 0.882782E+09 | 0.662100E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48377509.09 |
Maximum of Months | 0.105485E+10 | 0.840538E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7164693.92 | 0.552070E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.126234E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.770283E+09 |
February | 0.136988E+10 | 0.109120E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.811212E+09 |
March | 0.163688E+10 | 0.122366E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 161518.77 | 0.524630E+09 |
April | 0.145246E+10 | 0.105771E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423838E+09 |
May | 0.157341E+10 | 0.111864E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73816.41 | 0.245207E+09 |
June | 0.156904E+10 | 0.109620E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3877834.34 | 0.137238E+09 |
July | 0.145684E+10 | 0.102937E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9810539.03 | 78386759.44 |
August | 0.163688E+10 | 0.116524E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7114183.49 | 90689577.86 |
September | 0.145246E+10 | 0.108038E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 502175.49 | 0.148148E+09 |
October | 0.150994E+10 | 0.117102E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337415E+09 |
November | 0.149520E+10 | 0.127365E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453614E+09 |
December | 0.145684E+10 | 0.126869E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.834114E+09 |
Annual Sum or Average | 0.181198E+11 | 0.138381E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 21540067.52 | 0.485478E+10 |
Minimum of Months | 0.136988E+10 | 0.102937E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78386759.44 |
Maximum of Months | 0.163688E+10 | 0.127365E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9810539.03 | 0.834114E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.832172E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530689E+09 |
February | 0.882782E+09 | 0.710069E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.574212E+09 |
March | 0.105485E+10 | 0.792992E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108054.99 | 0.376654E+09 |
April | 0.936002E+09 | 0.681529E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315758E+09 |
May | 0.101394E+10 | 0.716997E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49212.12 | 0.176314E+09 |
June | 0.101113E+10 | 0.702181E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2453928.96 | 0.103564E+09 |
July | 0.938820E+09 | 0.660416E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6350835.35 | 61176274.53 |
August | 0.105485E+10 | 0.748012E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4630772.54 | 70784775.19 |
September | 0.936002E+09 | 0.699870E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 327162.27 | 0.104179E+09 |
October | 0.973041E+09 | 0.768885E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241129E+09 |
November | 0.963541E+09 | 0.837734E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334189E+09 |
December | 0.938820E+09 | 0.839111E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.611124E+09 |
Annual Sum or Average | 0.116768E+11 | 0.898997E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13919966.22 | 0.349977E+10 |
Minimum of Months | 0.882782E+09 | 0.660416E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61176274.53 |
Maximum of Months | 0.105485E+10 | 0.839111E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6350835.35 | 0.611124E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.132653E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162599E+10 |
February | 0.136985E+10 | 0.111574E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173029E+10 |
March | 0.163685E+10 | 0.123488E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 337499.82 | 0.108734E+10 |
April | 0.145243E+10 | 0.105434E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.890014E+09 |
May | 0.157338E+10 | 0.110892E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 313786.73 | 0.534044E+09 |
June | 0.156900E+10 | 0.108711E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9177787.08 | 0.307075E+09 |
July | 0.145680E+10 | 0.102067E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22216582.74 | 0.180462E+09 |
August | 0.163685E+10 | 0.115790E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18032135.01 | 0.205978E+09 |
September | 0.145243E+10 | 0.108463E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1307936.76 | 0.308759E+09 |
October | 0.150991E+10 | 0.119977E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683915E+09 |
November | 0.149516E+10 | 0.133234E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.927162E+09 |
December | 0.145680E+10 | 0.133462E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173706E+10 |
Annual Sum or Average | 0.181194E+11 | 0.140574E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51385728.14 | 0.102181E+11 |
Minimum of Months | 0.136985E+10 | 0.102067E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180462E+09 |
Maximum of Months | 0.163685E+10 | 0.133462E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22216582.74 | 0.173706E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.832903E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109134E+10 |
February | 0.649041E+09 | 0.711938E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115966E+10 |
March | 0.773965E+09 | 0.791081E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 227807.19 | 0.737575E+09 |
April | 0.688021E+09 | 0.679822E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.603669E+09 |
May | 0.744847E+09 | 0.719190E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 287922.28 | 0.365924E+09 |
June | 0.742030E+09 | 0.705346E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6121885.04 | 0.206991E+09 |
July | 0.690839E+09 | 0.661657E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14860339.68 | 0.120836E+09 |
August | 0.773965E+09 | 0.749820E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12109415.39 | 0.138857E+09 |
September | 0.688021E+09 | 0.696089E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 965677.40 | 0.208815E+09 |
October | 0.715730E+09 | 0.760279E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466535E+09 |
November | 0.708685E+09 | 0.838332E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621339E+09 |
December | 0.690839E+09 | 0.834892E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116153E+10 |
Annual Sum or Average | 0.858171E+10 | 0.898135E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34573046.98 | 0.688307E+10 |
Minimum of Months | 0.649041E+09 | 0.661657E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120836E+09 |
Maximum of Months | 0.773965E+09 | 0.838332E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14860339.68 | 0.116153E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.126028E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169604E+10 |
February | 0.136988E+10 | 0.108923E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178230E+10 |
March | 0.163688E+10 | 0.122241E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 336562.46 | 0.117213E+10 |
April | 0.145246E+10 | 0.105651E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.933538E+09 |
May | 0.157341E+10 | 0.111736E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 158306.30 | 0.556440E+09 |
June | 0.156904E+10 | 0.109524E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8710248.28 | 0.311210E+09 |
July | 0.145684E+10 | 0.102833E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21412854.05 | 0.186565E+09 |
August | 0.163688E+10 | 0.116432E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15785612.93 | 0.220119E+09 |
September | 0.145246E+10 | 0.107904E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1082246.43 | 0.335353E+09 |
October | 0.150994E+10 | 0.116996E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.751686E+09 |
November | 0.149520E+10 | 0.127193E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.983760E+09 |
December | 0.145684E+10 | 0.126714E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180581E+10 |
Annual Sum or Average | 0.181198E+11 | 0.138217E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 47485830.45 | 0.107350E+11 |
Minimum of Months | 0.136988E+10 | 0.102833E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186565E+09 |
Maximum of Months | 0.163688E+10 | 0.127193E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21412854.05 | 0.180581E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.830013E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110490E+10 |
February | 0.882782E+09 | 0.708861E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118092E+10 |
March | 0.105485E+10 | 0.791639E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 247727.71 | 0.766875E+09 |
April | 0.936002E+09 | 0.680475E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.628359E+09 |
May | 0.101394E+10 | 0.716196E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 105542.84 | 0.383030E+09 |
June | 0.101113E+10 | 0.701681E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5808010.58 | 0.223651E+09 |
July | 0.938820E+09 | 0.659792E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14602679.37 | 0.136980E+09 |
August | 0.105485E+10 | 0.747278E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11407015.86 | 0.155938E+09 |
September | 0.936002E+09 | 0.698645E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 736811.56 | 0.218417E+09 |
October | 0.973041E+09 | 0.766669E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474193E+09 |
November | 0.963541E+09 | 0.834826E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.633729E+09 |
December | 0.938820E+09 | 0.836059E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118531E+10 |
Annual Sum or Average | 0.116768E+11 | 0.897213E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 32907787.92 | 0.709229E+10 |
Minimum of Months | 0.882782E+09 | 0.659792E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136980E+09 |
Maximum of Months | 0.105485E+10 | 0.836059E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14602679.37 | 0.118531E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.132607E+10 | 0.305979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195641E+10 |
February | 0.136985E+10 | 0.111566E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208009E+10 |
March | 0.163685E+10 | 0.123455E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 370267.94 | 0.127229E+10 |
April | 0.145243E+10 | 0.105418E+10 | 0.295462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103020E+10 |
May | 0.157338E+10 | 0.110883E+10 | 0.312174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 239776.97 | 0.636179E+09 |
June | 0.156900E+10 | 0.108711E+10 | 0.306580E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10220762.41 | 0.378818E+09 |
July | 0.145680E+10 | 0.102065E+10 | 0.300989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25651467.33 | 0.228638E+09 |
August | 0.163685E+10 | 0.115787E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20489827.66 | 0.256828E+09 |
September | 0.145243E+10 | 0.108457E+10 | 0.295328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1452651.62 | 0.364787E+09 |
October | 0.150991E+10 | 0.119945E+10 | 0.306046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765558E+09 |
November | 0.149516E+10 | 0.133192E+10 | 0.299314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104531E+10 |
December | 0.145680E+10 | 0.133427E+10 | 0.300922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206223E+10 |
Annual Sum or Average | 0.181194E+11 | 0.140551E+11 | 0.363654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58424753.93 | 0.120773E+11 |
Minimum of Months | 0.136985E+10 | 0.102065E+10 | 0.277008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228638E+09 |
Maximum of Months | 0.163685E+10 | 0.133427E+10 | 0.318369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25651467.33 | 0.208009E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.832824E+09 | 0.197184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131045E+10 |
February | 0.882782E+09 | 0.711932E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139500E+10 |
March | 0.105485E+10 | 0.791027E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 247135.49 | 0.862150E+09 |
April | 0.936002E+09 | 0.679822E+09 | 0.190407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.706055E+09 |
May | 0.101394E+10 | 0.719123E+09 | 0.201177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 208884.93 | 0.442084E+09 |
June | 0.101113E+10 | 0.705346E+09 | 0.197572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6992326.56 | 0.257469E+09 |
July | 0.938820E+09 | 0.661637E+09 | 0.193969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17334263.87 | 0.153655E+09 |
August | 0.105485E+10 | 0.749730E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13701186.06 | 0.174291E+09 |
September | 0.936002E+09 | 0.695978E+09 | 0.190321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1066441.36 | 0.250784E+09 |
October | 0.973041E+09 | 0.760275E+09 | 0.197228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530247E+09 |
November | 0.963541E+09 | 0.838170E+09 | 0.192889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.706206E+09 |
December | 0.938820E+09 | 0.834557E+09 | 0.193926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137974E+10 |
Annual Sum or Average | 0.116768E+11 | 0.898042E+10 | 0.234352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39550238.27 | 0.816813E+10 |
Minimum of Months | 0.882782E+09 | 0.661637E+09 | 0.178515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153655E+09 |
Maximum of Months | 0.105485E+10 | 0.838170E+09 | 0.205169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17334263.87 | 0.139500E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.126026E+10 | 0.305983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201327E+10 |
February | 0.136988E+10 | 0.108923E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212264E+10 |
March | 0.163688E+10 | 0.122222E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 367816.71 | 0.136595E+10 |
April | 0.145246E+10 | 0.105647E+10 | 0.295467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108692E+10 |
May | 0.157341E+10 | 0.111734E+10 | 0.312179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 179379.44 | 0.665174E+09 |
June | 0.156904E+10 | 0.109521E+10 | 0.306585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10152193.85 | 0.382117E+09 |
July | 0.145684E+10 | 0.102827E+10 | 0.300994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25207172.32 | 0.233518E+09 |
August | 0.163688E+10 | 0.116425E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18631489.11 | 0.273188E+09 |
September | 0.145246E+10 | 0.107891E+10 | 0.295333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1279321.24 | 0.401217E+09 |
October | 0.150994E+10 | 0.116995E+10 | 0.306051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.857373E+09 |
November | 0.149520E+10 | 0.127164E+10 | 0.299318E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111478E+10 |
December | 0.145684E+10 | 0.126708E+10 | 0.300927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211953E+10 |
Annual Sum or Average | 0.181198E+11 | 0.138208E+11 | 0.363660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 55817372.67 | 0.126357E+11 |
Minimum of Months | 0.136988E+10 | 0.102827E+10 | 0.277013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233518E+09 |
Maximum of Months | 0.163688E+10 | 0.127164E+10 | 0.318374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25207172.32 | 0.212264E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.829826E+09 | 0.197183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132433E+10 |
February | 0.882782E+09 | 0.708861E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141438E+10 |
March | 0.105485E+10 | 0.791603E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 278765.88 | 0.904231E+09 |
April | 0.936002E+09 | 0.680390E+09 | 0.190406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739538E+09 |
May | 0.101394E+10 | 0.716118E+09 | 0.201175E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 119592.39 | 0.460834E+09 |
June | 0.101113E+10 | 0.701625E+09 | 0.197570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6721440.72 | 0.275282E+09 |
July | 0.938820E+09 | 0.659787E+09 | 0.193968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17137132.19 | 0.170577E+09 |
August | 0.105485E+10 | 0.747239E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13459051.22 | 0.193143E+09 |
September | 0.936002E+09 | 0.698643E+09 | 0.190319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 872417.05 | 0.261499E+09 |
October | 0.973041E+09 | 0.766554E+09 | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546192E+09 |
November | 0.963541E+09 | 0.834490E+09 | 0.192888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.731279E+09 |
December | 0.938820E+09 | 0.835978E+09 | 0.193924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140466E+10 |
Annual Sum or Average | 0.116768E+11 | 0.897112E+10 | 0.234351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 38588399.45 | 0.842594E+10 |
Minimum of Months | 0.882782E+09 | 0.659787E+09 | 0.178514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170577E+09 |
Maximum of Months | 0.105485E+10 | 0.835978E+09 | 0.205168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17137132.19 | 0.141438E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.430130E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.390160E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.463618E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.414106E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.446874E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.444713E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.416266E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.463618E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.414106E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.430130E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.425088E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.416266E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.515507E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.390160E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.463618E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.522764E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.474186E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.563465E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.503289E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.543115E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.540489E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.505915E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.563465E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.503289E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.522764E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.516637E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.505915E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.626529E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.474186E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.563465E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167122E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176545E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165753.87 | 0.111314E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.904378E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206563.35 | 0.510045E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6377178.64 | 0.288886E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16352773.70 | 0.168441E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13851211.86 | 0.196118E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 705733.99 | 0.307071E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.711543E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.985619E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182258E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37659215.42 | 0.104445E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168441E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16352773.70 | 0.182258E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276330E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292874E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 481464.02 | 0.188337E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153437E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 743755.45 | 0.885682E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13783755.29 | 0.500111E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30836930.72 | 0.285232E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26950108.94 | 0.340656E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1421196.29 | 0.528873E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120038E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163217E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298870E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74217210.71 | 0.174716E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285232E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30836930.72 | 0.298870E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291087E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309518E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35436.81 | 0.198349E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164173E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35751.73 | 0.101073E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7430320.40 | 0.594240E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22104526.03 | 0.354805E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17363842.07 | 0.403130E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 727125.85 | 0.588357E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123143E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164438E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309919E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47697002.88 | 0.185575E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354805E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22104526.03 | 0.309919E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 19402.09 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 19402.09 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 19402.09 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 19402.09 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 19402.09 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 19402.09 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 19402.09 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 19402.09 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 19402.09 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 19402.09 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 19402.09 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 19402.09 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 19402.09 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 19402.09 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.63 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.63 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.63 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.63 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.63 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.63 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.63 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.63 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.63 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.63 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.63 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.63 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 17424.44 | 02-JAN-08:09 | 17206.56 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 17424.44 | 01-FEB-08:09 | 17206.56 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 17424.44 | 01-MAR-08:09 | 17206.56 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 17424.44 | 03-APR-07:10 | 17206.56 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 17424.44 | 01-MAY-07:10 | 17206.56 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 17424.44 | 01-JUN-07:10 | 17206.56 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 17424.44 | 03-JUL-07:10 | 17206.56 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 17424.44 | 01-AUG-07:10 | 17206.56 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 17424.44 | 01-SEP-07:10 | 17206.56 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 17424.44 | 02-OCT-07:10 | 17206.56 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 17424.44 | 01-NOV-07:10 | 17206.56 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 17424.44 | 01-DEC-08:09 | 17206.56 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2187.81 | 02-JAN-16:40 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1376.99 | 12-JAN-02:00 |
February | 2010.79 | 01-FEB-10:09 | 2187.81 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1420.15 | 13-FEB-05:54 |
March | 2010.79 | 01-MAR-10:09 | 1625.25 | 17-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.95 | 15-MAR-14:00 | 886.71 | 02-MAR-01:00 |
April | 2010.79 | 03-APR-09:09 | 1524.25 | 12-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 850.70 | 16-APR-02:00 |
May | 2010.79 | 01-MAY-09:09 | 1141.96 | 10-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.09 | 14-MAY-15:00 | 473.72 | 29-MAY-14:20 |
June | 2010.79 | 01-JUN-09:09 | 1040.96 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.13 | 17-JUN-17:02 | 425.25 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 1141.96 | 11-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.87 | 21-JUL-03:00 | 322.56 | 06-JUL-02:00 |
August | 2010.79 | 01-AUG-09:09 | 1141.96 | 21-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.91 | 13-AUG-13:10 | 192.81 | 30-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 1524.25 | 26-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.87 | 16-SEP-13:00 | 358.82 | 29-SEP-04:00 |
October | 2010.79 | 02-OCT-09:09 | 2187.81 | 30-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 475.25 | 08-OCT-09:00 |
November | 2010.79 | 01-NOV-09:09 | 2187.81 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 839.85 | 17-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 01-DEC-16:19 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1352.23 | 09-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.81 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 126.91 | 1420.15 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-16:40 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 910.93 | 12-JAN-06:00 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 946.77 | 13-FEB-05:52 |
March | 1295.83 | 01-MAR-10:09 | 982.28 | 17-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.30 | 15-MAR-14:00 | 595.60 | 26-MAR-10:00 |
April | 1295.83 | 03-APR-09:09 | 801.02 | 12-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 550.91 | 16-APR-07:00 |
May | 1295.83 | 01-MAY-09:09 | 735.93 | 11-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.06 | 14-MAY-15:00 | 324.17 | 29-MAY-14:20 |
June | 1295.83 | 01-JUN-09:09 | 670.83 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.15 | 17-JUN-17:02 | 283.34 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 735.93 | 17-JUL-15:20 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.67 | 21-JUL-03:00 | 208.46 | 06-JUL-02:00 |
August | 1295.83 | 01-AUG-09:09 | 735.93 | 24-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.26 | 13-AUG-13:10 | 120.47 | 30-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 982.28 | 26-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.01 | 16-SEP-17:02 | 232.83 | 29-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 1228.64 | 23-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 325.42 | 08-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 541.33 | 17-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-16:19 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 881.30 | 09-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.47 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 93.26 | 946.77 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2187.86 | 02-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1366.41 | 12-JAN-05:52 |
February | 2010.83 | 01-FEB-10:09 | 1906.57 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1420.16 | 13-FEB-05:52 |
March | 2010.83 | 01-MAR-10:09 | 1524.28 | 13-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.81 | 15-MAR-14:00 | 919.16 | 26-MAR-13:00 |
April | 2010.83 | 03-APR-09:09 | 1524.28 | 12-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 809.16 | 16-APR-02:00 |
May | 2010.83 | 01-MAY-09:09 | 1243.00 | 11-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.40 | 10-MAY-14:00 | 499.45 | 29-MAY-14:20 |
June | 2010.83 | 01-JUN-09:09 | 1141.99 | 19-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.48 | 17-JUN-17:02 | 423.34 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 1141.99 | 11-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.64 | 21-JUL-03:00 | 317.01 | 06-JUL-02:00 |
August | 2010.83 | 01-AUG-09:09 | 1243.00 | 24-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.01 | 13-AUG-13:05 | 189.72 | 30-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 1524.28 | 26-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.87 | 16-SEP-13:00 | 347.34 | 29-SEP-04:00 |
October | 2010.83 | 02-OCT-09:09 | 2187.86 | 30-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 469.90 | 08-OCT-09:00 |
November | 2010.83 | 01-NOV-09:09 | 2187.86 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 821.93 | 17-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 2187.86 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1333.26 | 09-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1141.99 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.72 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 122.01 | 1420.16 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-16:49 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 943.92 | 12-JAN-02:00 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 946.77 | 13-FEB-05:58 |
March | 1295.83 | 01-MAR-10:09 | 1228.64 | 13-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7.30 | 15-MAR-14:00 | 658.28 | 02-MAR-01:00 |
April | 1295.83 | 03-APR-09:09 | 982.28 | 12-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 623.50 | 16-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 801.02 | 11-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.60 | 10-MAY-14:00 | 363.73 | 29-MAY-15:00 |
June | 1295.83 | 01-JUN-09:09 | 735.93 | 05-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.62 | 12-JUN-13:00 | 304.17 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 801.02 | 11-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.96 | 21-JUL-03:00 | 241.33 | 06-JUL-02:00 |
August | 1295.83 | 01-AUG-09:09 | 801.02 | 21-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.60 | 13-AUG-13:08 | 167.79 | 27-AUG-16:40 |
September | 1295.83 | 01-SEP-09:09 | 1228.64 | 26-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.58 | 16-SEP-13:00 | 252.69 | 29-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 26-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 342.69 | 08-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 613.12 | 17-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-16:19 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 958.07 | 09-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 735.93 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.79 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 87.60 | 958.07 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2187.81 | 02-JAN-16:40 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3198.33 | 12-JAN-05:45 |
February | 2010.79 | 01-FEB-10:09 | 2187.81 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 3182.03 | 13-FEB-05:50 |
March | 2010.79 | 01-MAR-10:09 | 1524.25 | 13-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.35 | 15-MAR-14:00 | 1840.69 | 02-MAR-05:07 |
April | 2010.79 | 03-APR-09:09 | 1524.25 | 12-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1683.76 | 16-APR-02:00 |
May | 2010.79 | 01-MAY-09:09 | 1141.96 | 10-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.17 | 14-MAY-15:00 | 1057.43 | 29-MAY-14:00 |
June | 2010.79 | 01-JUN-09:09 | 1040.96 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.08 | 17-JUN-17:02 | 900.32 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 1141.96 | 11-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 222.41 | 21-JUL-03:10 | 655.51 | 06-JUL-02:00 |
August | 2010.79 | 01-AUG-09:09 | 1141.96 | 21-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.05 | 13-AUG-13:00 | 418.98 | 30-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 1524.25 | 26-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.39 | 16-SEP-17:02 | 748.07 | 29-SEP-04:00 |
October | 2010.79 | 02-OCT-09:09 | 2187.81 | 30-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 943.96 | 08-OCT-09:00 |
November | 2010.79 | 01-NOV-09:09 | 2187.81 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1686.29 | 17-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 01-DEC-16:19 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2901.88 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 418.98 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 310.05 | 3198.33 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1409.91 | 02-JAN-16:40 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2132.22 | 12-JAN-05:50 |
February | 1239.33 | 01-FEB-08:09 | 1409.91 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2198.19 | 13-FEB-05:51 |
March | 1239.33 | 01-MAR-08:09 | 982.28 | 17-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.23 | 15-MAR-14:00 | 1234.79 | 02-MAR-05:04 |
April | 1239.33 | 03-APR-07:10 | 801.02 | 12-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1129.12 | 16-APR-07:00 |
May | 1239.33 | 01-MAY-07:10 | 735.93 | 11-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.13 | 14-MAY-15:00 | 798.92 | 29-MAY-13:53 |
June | 1239.33 | 01-JUN-07:10 | 670.83 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.17 | 17-JUN-17:02 | 609.05 | 13-JUN-03:00 |
July | 1239.33 | 03-JUL-07:10 | 735.93 | 17-JUL-15:39 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 183.76 | 21-JUL-03:10 | 435.09 | 06-JUL-02:00 |
August | 1239.33 | 01-AUG-07:10 | 735.93 | 24-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.36 | 13-AUG-13:00 | 266.40 | 30-AUG-21:10 |
September | 1239.33 | 01-SEP-07:10 | 982.28 | 26-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.19 | 16-SEP-17:02 | 486.80 | 29-SEP-04:00 |
October | 1239.33 | 02-OCT-07:10 | 1228.64 | 23-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 663.77 | 08-OCT-09:00 |
November | 1239.33 | 01-NOV-07:10 | 1409.91 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1108.72 | 17-NOV-02:00 |
December | 1239.33 | 01-DEC-08:09 | 1409.91 | 01-DEC-16:19 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1920.05 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.40 | |||||
Maximum of Months | 1239.33 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 219.36 | 2198.19 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2187.86 | 02-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3198.35 | 12-JAN-05:43 |
February | 2010.83 | 01-FEB-10:09 | 1906.57 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 3298.16 | 13-FEB-05:51 |
March | 2010.83 | 01-MAR-10:09 | 1524.28 | 13-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.16 | 15-MAR-14:00 | 2063.37 | 26-MAR-13:10 |
April | 2010.83 | 03-APR-09:09 | 1524.28 | 12-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1687.91 | 16-APR-02:00 |
May | 2010.83 | 01-MAY-09:09 | 1141.99 | 10-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.68 | 10-MAY-14:00 | 1185.73 | 29-MAY-14:20 |
June | 2010.83 | 01-JUN-09:09 | 1040.98 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.57 | 17-JUN-17:02 | 913.16 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 1141.99 | 11-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 248.14 | 21-JUL-03:08 | 660.10 | 06-JUL-02:00 |
August | 2010.83 | 01-AUG-09:09 | 1141.99 | 21-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 271.48 | 13-AUG-12:53 | 416.00 | 30-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 1524.28 | 26-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.55 | 16-SEP-13:00 | 751.31 | 29-SEP-04:00 |
October | 2010.83 | 02-OCT-09:09 | 2187.86 | 30-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1011.01 | 08-OCT-09:00 |
November | 2010.83 | 01-NOV-09:09 | 2187.86 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1728.60 | 17-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 2187.86 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2940.28 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.00 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 271.48 | 3298.16 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-16:49 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2132.22 | 12-JAN-05:43 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2201.47 | 13-FEB-05:51 |
March | 1295.83 | 01-MAR-10:09 | 1228.64 | 13-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.23 | 15-MAR-14:00 | 1375.87 | 25-MAR-17:08 |
April | 1295.83 | 03-APR-09:09 | 982.28 | 12-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1141.76 | 16-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 801.02 | 11-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.45 | 10-MAY-14:00 | 807.52 | 29-MAY-15:10 |
June | 1295.83 | 01-JUN-09:09 | 735.93 | 07-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.95 | 12-JUN-13:00 | 625.66 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 801.02 | 11-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 185.59 | 21-JUL-03:10 | 463.64 | 06-JUL-02:00 |
August | 1295.83 | 01-AUG-09:09 | 801.02 | 21-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.01 | 13-AUG-13:00 | 361.42 | 27-AUG-16:30 |
September | 1295.83 | 01-SEP-09:09 | 1228.64 | 26-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.03 | 16-SEP-13:00 | 494.52 | 29-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 26-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 651.50 | 08-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1133.16 | 17-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-16:19 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1961.75 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 735.93 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 361.42 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 230.01 | 2201.47 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2187.81 | 02-JAN-16:40 | 2160.55 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3952.44 | 12-JAN-06:00 |
February | 2010.79 | 01-FEB-10:09 | 2187.81 | 01-FEB-08:09 | 2160.55 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 3758.22 | 13-FEB-05:50 |
March | 2010.79 | 01-MAR-10:09 | 1524.25 | 13-MAR-07:10 | 2160.55 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.58 | 15-MAR-14:00 | 2298.52 | 02-MAR-05:09 |
April | 2010.79 | 03-APR-09:09 | 1524.25 | 12-APR-07:10 | 2160.55 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1877.84 | 04-APR-21:03 |
May | 2010.79 | 01-MAY-09:09 | 1141.96 | 10-MAY-07:10 | 2160.55 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.51 | 14-MAY-14:50 | 1288.65 | 29-MAY-14:00 |
June | 2010.79 | 01-JUN-09:09 | 1040.96 | 01-JUN-07:10 | 2160.55 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.45 | 17-JUN-17:02 | 1099.36 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 1141.96 | 11-JUL-07:10 | 2160.55 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 247.55 | 21-JUL-03:00 | 786.88 | 06-JUL-02:00 |
August | 2010.79 | 01-AUG-09:09 | 1141.96 | 21-AUG-07:10 | 2160.55 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 349.27 | 13-AUG-12:52 | 508.22 | 30-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 1524.25 | 26-SEP-07:10 | 2160.55 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.34 | 16-SEP-17:02 | 823.80 | 29-SEP-04:00 |
October | 2010.79 | 02-OCT-09:09 | 2187.81 | 30-OCT-07:10 | 2160.55 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1035.07 | 30-OCT-04:52 |
November | 2010.79 | 01-NOV-09:09 | 2187.81 | 01-NOV-07:10 | 2160.55 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1979.41 | 17-NOV-06:00 |
December | 2010.79 | 01-DEC-10:09 | 2187.81 | 01-DEC-16:19 | 2160.55 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3479.16 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 508.22 | |||||
Maximum of Months | 2010.79 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 349.27 | 3952.44 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-16:40 | 1392.34 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2673.94 | 12-JAN-05:55 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 01-FEB-16:00 | 1392.34 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2735.50 | 13-FEB-05:50 |
March | 1295.83 | 01-MAR-10:09 | 982.28 | 17-MAR-07:10 | 1392.34 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.05 | 15-MAR-14:00 | 1535.82 | 02-MAR-05:04 |
April | 1295.83 | 03-APR-09:09 | 801.02 | 12-APR-07:10 | 1392.34 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1251.19 | 04-APR-21:03 |
May | 1295.83 | 01-MAY-09:09 | 735.93 | 11-MAY-07:10 | 1392.34 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.49 | 14-MAY-14:50 | 987.58 | 29-MAY-13:53 |
June | 1295.83 | 01-JUN-09:09 | 670.83 | 01-JUN-07:10 | 1392.34 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.81 | 17-JUN-17:02 | 744.99 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 735.93 | 17-JUL-15:39 | 1392.34 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 203.10 | 21-JUL-03:00 | 522.62 | 06-JUL-02:00 |
August | 1295.83 | 01-AUG-09:09 | 735.93 | 24-AUG-07:10 | 1392.34 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 260.47 | 13-AUG-13:10 | 323.49 | 30-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 982.28 | 26-SEP-07:10 | 1392.34 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.30 | 16-SEP-17:02 | 538.67 | 29-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 1228.64 | 23-OCT-07:10 | 1392.34 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 692.29 | 08-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.34 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1319.43 | 17-NOV-06:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-16:19 | 1392.34 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2306.25 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.49 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 260.47 | 2735.50 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2187.86 | 02-JAN-16:49 | 2160.58 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4010.85 | 12-JAN-05:57 |
February | 2010.83 | 01-FEB-10:09 | 1906.57 | 01-FEB-08:09 | 2160.58 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 4053.97 | 13-FEB-05:50 |
March | 2010.83 | 01-MAR-10:09 | 1524.28 | 13-MAR-07:10 | 2160.58 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 28.29 | 15-MAR-14:00 | 2415.68 | 26-MAR-13:00 |
April | 2010.83 | 03-APR-09:09 | 1524.28 | 12-APR-07:10 | 2160.58 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1877.90 | 04-APR-21:03 |
May | 2010.83 | 01-MAY-09:09 | 1141.99 | 10-MAY-07:10 | 2160.58 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.92 | 10-MAY-14:00 | 1449.98 | 29-MAY-14:40 |
June | 2010.83 | 01-JUN-09:09 | 1040.98 | 01-JUN-07:10 | 2160.58 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.16 | 17-JUN-17:02 | 1115.05 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 1141.99 | 11-JUL-07:10 | 2160.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 266.02 | 21-JUL-03:00 | 791.52 | 06-JUL-02:00 |
August | 2010.83 | 01-AUG-09:09 | 1141.99 | 21-AUG-07:10 | 2160.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 331.11 | 13-AUG-13:05 | 502.94 | 30-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 1524.28 | 26-SEP-07:10 | 2160.58 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.35 | 16-SEP-13:00 | 829.59 | 29-SEP-04:00 |
October | 2010.83 | 02-OCT-09:09 | 2187.86 | 30-OCT-07:10 | 2160.58 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1163.61 | 09-OCT-11:56 |
November | 2010.83 | 01-NOV-09:09 | 2187.86 | 01-NOV-07:10 | 2160.58 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1979.53 | 17-NOV-06:00 |
December | 2010.83 | 01-DEC-10:09 | 2187.86 | 01-DEC-16:19 | 2160.58 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3518.07 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 502.94 | |||||
Maximum of Months | 2010.83 | 2187.86 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 331.11 | 4053.97 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1409.91 | 02-JAN-16:49 | 1392.33 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2673.92 | 12-JAN-06:00 |
February | 1295.83 | 01-FEB-10:09 | 1409.91 | 01-FEB-08:09 | 1392.33 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2735.60 | 13-FEB-05:50 |
March | 1295.83 | 01-MAR-10:09 | 1228.64 | 13-MAR-07:10 | 1392.33 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.05 | 15-MAR-14:00 | 1671.15 | 25-MAR-17:10 |
April | 1295.83 | 03-APR-09:09 | 982.28 | 12-APR-07:10 | 1392.33 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1267.64 | 16-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 801.02 | 11-MAY-07:10 | 1392.33 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.61 | 10-MAY-14:00 | 1004.73 | 29-MAY-15:20 |
June | 1295.83 | 01-JUN-09:09 | 735.93 | 07-JUN-07:10 | 1392.33 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.14 | 12-JUN-13:00 | 763.93 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 801.02 | 11-JUL-07:10 | 1392.33 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.60 | 21-JUL-03:00 | 557.84 | 06-JUL-02:00 |
August | 1295.83 | 01-AUG-09:09 | 801.02 | 21-AUG-07:10 | 1392.33 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 276.31 | 13-AUG-13:10 | 461.28 | 27-AUG-16:50 |
September | 1295.83 | 01-SEP-09:09 | 1228.64 | 26-SEP-07:10 | 1392.33 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.57 | 16-SEP-13:00 | 553.81 | 29-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 1409.91 | 26-OCT-07:10 | 1392.33 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 700.31 | 08-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 1409.91 | 01-NOV-07:10 | 1392.33 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1319.50 | 17-NOV-06:00 |
December | 1295.83 | 01-DEC-10:09 | 1409.91 | 01-DEC-16:19 | 1392.33 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2362.77 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 735.93 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 461.28 | |||||
Maximum of Months | 1295.83 | 1409.91 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 276.31 | 2735.60 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 450.11 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 450.11 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 450.11 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 450.11 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 450.11 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 450.11 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 450.11 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 450.11 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 450.11 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 450.11 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 450.11 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 450.11 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 5470.56 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 5470.56 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 5470.56 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 5470.56 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 5470.56 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 5470.56 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 5470.56 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 5470.56 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 5470.56 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 5470.56 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 5470.56 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 5470.56 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 5470.56 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2986.29 | 12-JAN-02:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 3018.52 | 13-FEB-05:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.84 | 15-MAR-14:00 | 1956.72 | 02-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1837.42 | 16-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.94 | 14-MAY-15:00 | 885.27 | 29-MAY-13:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.64 | 17-JUN-17:02 | 868.97 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.18 | 21-JUL-03:00 | 641.98 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.43 | 13-AUG-12:52 | 395.93 | 30-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.11 | 16-SEP-13:00 | 771.56 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 997.14 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1794.40 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2928.92 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 395.93 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.43 | 3018.52 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4997.10 | 12-JAN-05:52 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 4938.49 | 13-FEB-05:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.74 | 15-MAR-14:00 | 3242.78 | 02-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3081.01 | 16-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.15 | 14-MAY-15:00 | 1488.39 | 29-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.86 | 17-JUN-17:02 | 1500.41 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.12 | 21-JUL-02:52 | 1097.56 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 553.40 | 13-AUG-13:00 | 696.60 | 30-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.04 | 16-SEP-17:02 | 1344.13 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1685.76 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3022.08 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4932.67 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 696.60 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 553.40 | 4997.10 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5435.82 | 12-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 5314.21 | 13-FEB-05:51 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.82 | 15-MAR-14:00 | 3307.76 | 02-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2941.99 | 16-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.46 | 10-MAY-15:00 | 2051.28 | 29-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.73 | 17-JUN-17:02 | 1707.52 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.54 | 21-JUL-01:55 | 1207.40 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.36 | 13-AUG-12:52 | 771.89 | 30-AUG-21:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.68 | 16-SEP-13:00 | 1331.15 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1567.17 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3131.01 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5494.31 | 09-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 771.89 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.36 | 5494.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 104004.20 | 17-JAN-07:12 | 21542.70 | 38804.17 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 104662.17 | 21-FEB-07:03 | 14361.80 | 25869.45 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 106395.31 | 13-MAR-06:11 | 25133.15 | 45271.53 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 104915.21 | 03-APR-06:03 | 10771.35 | 19402.09 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 111199.07 | 30-MAY-06:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 115230.66 | 22-JUN-06:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 125285.22 | 06-JUL-06:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 122197.13 | 09-AUG-06:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 116976.88 | 11-SEP-06:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 116085.22 | 10-OCT-06:11 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 113376.31 | 06-NOV-07:11 | 32314.05 | 58206.26 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 108613.63 | 26-DEC-07:03 | 14361.80 | 25869.45 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 104004.20 | 10771.35 | 19402.09 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 125285.22 | 35904.50 | 64673.62 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 78888.39 | 19-JAN-06:01 | 11285.67 | 3761.52 | 53531.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 81820.17 | 24-FEB-06:02 | 12897.91 | 4298.88 | 61179.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 87000.03 | 15-MAR-04:12 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 92449.30 | 10-APR-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 94961.93 | 30-MAY-04:12 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 98442.54 | 28-JUN-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 98286.23 | 10-JUL-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 99485.95 | 29-AUG-04:13 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 96598.14 | 15-SEP-04:13 | 0.00 | 3224.16 | 35625.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 91828.77 | 10-OCT-04:11 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 93087.65 | 13-NOV-05:11 | 0.00 | 5373.60 | 59376.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 85722.06 | 18-DEC-05:01 | 0.00 | 3761.52 | 41563.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 78888.39 | 0.00 | 2686.80 | 29688.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 99485.95 | 12897.91 | 5373.60 | 61179.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 30685.54 | 06-JAN-11:53 | 61265.06 | 69697.75 | 68826.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 26590.15 | 02-FEB-08:10 | 30632.53 | 34848.87 | 34413.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 79075.99 | 16-MAR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 75225.89 | 27-APR-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 81386.07 | 30-MAY-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 82426.89 | 30-JUN-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 82742.20 | 25-JUL-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 82292.10 | 16-AUG-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 82718.73 | 18-SEP-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 78257.56 | 13-OCT-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 72288.92 | 01-NOV-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 31122.18 | 08-DEC-20:25 | 3224.48 | 7744.05 | 15294.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 26590.15 | 0.00 | 2149.44 | 15294.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 82742.20 | 61265.06 | 69697.75 | 68826.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17266.21 | 12-JAN-16:50 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17741.35 | 17-FEB-17:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 76810.61 | 16-MAR-05:02 | 8061.19 | 2686.80 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 38714.82 | 21-APR-16:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 74967.86 | 17-MAY-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 81604.91 | 19-JUN-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 81490.72 | 28-JUL-04:12 | 0.00 | 3224.16 | 35625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 81041.38 | 11-AUG-04:12 | 0.00 | 2149.44 | 23750.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 79663.09 | 18-SEP-04:12 | 0.00 | 2686.80 | 29688.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 52655.90 | 13-OCT-05:03 | 6448.95 | 2149.44 | 30589.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 25310.49 | 01-NOV-16:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18200.08 | 01-DEC-17:00 | 15316.26 | 17424.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 17266.21 | 0.00 | 2149.44 | 17206.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 81604.91 | 15316.26 | 17424.44 | 38236.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2440.19 | 17-JAN-06:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.59 |
February | 2507.46 | 23-FEB-08:10 | 3846.22 | 3250.51 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.24 |
March | 7857.85 | 15-MAR-14:00 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 10.95 | 0.00 |
April | 7067.46 | 07-APR-13:30 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.61 |
May | 10196.71 | 31-MAY-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.26 |
June | 13302.72 | 30-JUN-04:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.49 |
July | 15535.21 | 16-JUL-16:51 | 708.51 | 404.79 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 9.68 | 0.00 |
August | 16431.35 | 06-AUG-15:41 | 708.51 | 404.79 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 14.13 | 0.00 |
September | 13833.23 | 15-SEP-04:12 | 0.00 | 404.83 | 4473.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.93 |
October | 6042.35 | 12-OCT-12:10 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.29 |
November | 4755.57 | 27-NOV-12:00 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.45 |
December | 2814.00 | 01-DEC-13:20 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2440.19 | 0.00 | 269.88 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16431.35 | 3846.22 | 3250.51 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 14.13 | 151.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2540.74 | 17-JAN-06:03 | 521.82 | 173.92 | 2475.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.96 |
February | 6038.29 | 28-FEB-09:35 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.33 |
March | 9103.65 | 21-MAR-08:55 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.59 |
April | 13563.26 | 23-APR-09:23 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.93 |
May | 16508.09 | 29-MAY-10:32 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.72 |
June | 21063.99 | 11-JUN-08:52 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.40 |
July | 26292.40 | 04-JUL-08:31 | 587.05 | 335.39 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.98 |
August | 22439.89 | 06-AUG-09:01 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.43 |
September | 22668.54 | 10-SEP-09:52 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.98 |
October | 13062.75 | 09-OCT-10:02 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.83 |
November | 6451.38 | 03-NOV-08:55 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.90 |
December | 3523.36 | 04-DEC-09:50 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2540.74 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.96 | |
Maximum of Months | 26292.40 | 2478.65 | 1341.67 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14639.85 | 12-JAN-13:30 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 326.50 |
February | 17298.38 | 28-FEB-13:20 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.40 |
March | 19279.82 | 15-MAR-13:30 | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 8.70 | 0.00 |
April | 25600.01 | 23-APR-12:02 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.64 |
May | 25821.19 | 14-MAY-13:52 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.02 |
June | 25634.49 | 18-JUN-12:32 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.93 |
July | 26169.88 | 04-JUL-13:12 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.40 |
August | 26887.03 | 27-AUG-12:42 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.61 |
September | 28978.59 | 10-SEP-12:31 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.19 |
October | 26694.08 | 09-OCT-12:02 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388.87 |
November | 18375.54 | 03-NOV-12:20 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.34 |
December | 18460.70 | 17-DEC-12:53 | 303.66 | 173.48 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 600.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14639.85 | 303.66 | 173.48 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28978.59 | 2010.83 | 1040.98 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 8.70 | 600.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4415.92 | 12-JAN-15:40 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.45 |
February | 9346.25 | 28-FEB-16:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.98 |
March | 18221.06 | 26-MAR-16:22 | 326.14 | 186.33 | 2320.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442.45 |
April | 27681.61 | 02-APR-16:12 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.76 |
May | 28225.55 | 14-MAY-14:32 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.95 |
June | 29198.66 | 11-JUN-16:51 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.15 |
July | 30117.46 | 02-JUL-16:41 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.26 |
August | 29411.09 | 27-AUG-16:41 | 521.82 | 298.13 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.36 |
September | 30546.89 | 04-SEP-16:51 | 521.82 | 298.13 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.32 |
October | 14927.08 | 09-OCT-16:03 | 260.91 | 149.06 | 1856.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.69 |
November | 14518.43 | 27-NOV-05:12 | 0.00 | 217.40 | 2402.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.69 |
December | 7778.26 | 04-DEC-15:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.57 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4415.92 | 0.00 | 149.06 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.15 | |
Maximum of Months | 30546.89 | 1239.33 | 670.83 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1611.34 | 11-JAN-16:50 | 1923.11 | 1906.53 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.76 |
February | 1637.06 | 17-FEB-15:00 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.78 |
March | 6055.71 | 15-MAR-14:00 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 24.35 | 0.00 |
April | 4589.73 | 07-APR-13:50 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.19 |
May | 7207.92 | 23-MAY-14:40 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.14 |
June | 11589.88 | 21-JUN-05:03 | 809.73 | 269.88 | 3840.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.97 |
July | 13446.87 | 16-JUL-14:32 | 404.87 | 231.31 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 82.09 | 0.00 |
August | 13126.18 | 13-AUG-16:11 | 708.51 | 404.79 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 119.82 | 0.00 |
September | 7103.26 | 13-SEP-13:30 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.05 |
October | 4236.08 | 12-OCT-14:40 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.74 |
November | 2422.46 | 03-NOV-12:40 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.63 |
December | 1890.98 | 01-DEC-13:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1611.34 | 404.87 | 231.31 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13446.87 | 2010.79 | 1906.53 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 119.82 | 270.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2519.29 | 06-JAN-10:05 | 0.00 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.19 |
February | 3191.04 | 28-FEB-09:55 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.93 |
March | 6843.79 | 21-MAR-08:55 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.46 |
April | 23462.72 | 23-APR-09:52 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.48 |
May | 24036.89 | 21-MAY-10:02 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.45 |
June | 26472.40 | 11-JUN-09:21 | 456.59 | 260.86 | 3248.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.89 |
July | 28575.94 | 04-JUL-09:11 | 587.05 | 335.39 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.04 |
August | 20689.20 | 06-AUG-09:12 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.29 |
September | 24193.36 | 10-SEP-09:42 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.66 |
October | 9272.29 | 11-OCT-09:00 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.80 |
November | 4065.76 | 03-NOV-08:55 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.76 |
December | 2115.03 | 04-DEC-10:00 | 2478.65 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2115.03 | 0.00 | 186.33 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.80 | |
Maximum of Months | 28575.94 | 2478.65 | 1341.67 | 4177.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18067.09 | 15-JAN-14:03 | 303.66 | 173.48 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1072.43 |
February | 18248.31 | 28-FEB-13:40 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.21 |
March | 19486.93 | 01-MAR-13:40 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 561.61 |
April | 26147.55 | 23-APR-13:12 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 416.88 |
May | 25480.39 | 14-MAY-13:32 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.18 |
June | 25659.87 | 18-JUN-13:02 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.35 |
July | 25984.02 | 04-JUL-13:12 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.73 |
August | 26668.42 | 27-AUG-13:12 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.77 |
September | 29005.61 | 10-SEP-12:21 | 708.53 | 404.80 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 401.09 |
October | 25207.90 | 22-OCT-14:02 | 404.87 | 231.31 | 2880.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 380.39 |
November | 19230.87 | 03-NOV-12:30 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.15 |
December | 12617.43 | 04-DEC-11:50 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 417.64 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12617.43 | 303.66 | 173.48 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.73 | |
Maximum of Months | 29005.61 | 1923.15 | 1040.98 | 5041.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1072.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2604.59 | 12-JAN-16:00 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 434.64 |
February | 6044.91 | 28-FEB-16:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.78 |
March | 8867.36 | 21-MAR-16:00 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.18 |
April | 18074.49 | 02-APR-16:52 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 707.30 |
May | 28366.10 | 07-MAY-16:41 | 521.82 | 298.13 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 367.83 |
June | 29793.08 | 11-JUN-16:41 | 652.28 | 372.66 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.64 |
July | 27801.75 | 02-JUL-17:01 | 0.00 | 260.86 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.11 |
August | 26680.84 | 27-AUG-16:31 | 652.28 | 372.66 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.00 |
September | 26194.60 | 10-SEP-17:42 | 0.00 | 223.59 | 2162.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.88 |
October | 11661.89 | 11-OCT-16:00 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.23 |
November | 4872.16 | 15-NOV-15:20 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.18 |
December | 2684.71 | 04-DEC-15:50 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2604.59 | 0.00 | 223.59 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.23 | |
Maximum of Months | 29793.08 | 1239.33 | 670.83 | 4641.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 707.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1471.55 | 14-JAN-17:03 | 404.87 | 486.14 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.93 |
February | 1553.19 | 22-FEB-16:30 | 1923.11 | 1141.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.69 |
March | 6567.31 | 15-MAR-14:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 20.91 | 0.00 |
April | 4374.39 | 20-APR-15:40 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.84 |
May | 7444.37 | 23-MAY-14:40 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.94 |
June | 17227.85 | 18-JUN-15:01 | 708.51 | 404.79 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.48 |
July | 17294.52 | 16-JUL-14:32 | 404.87 | 231.31 | 2880.74 | 0.00 | 0.00 | 0.00 | 0.00 | 87.23 | 0.00 |
August | 13670.09 | 06-AUG-16:32 | 607.30 | 346.96 | 4321.10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.27 | 0.00 |
September | 7459.14 | 15-SEP-14:00 | 2010.79 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 9.76 | 0.00 |
October | 4145.90 | 12-OCT-15:00 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.09 |
November | 2167.40 | 16-NOV-16:50 | 1923.11 | 2187.81 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.01 |
December | 1663.63 | 01-DEC-13:30 | 1923.11 | 1040.96 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1471.55 | 404.87 | 231.31 | 2160.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17294.52 | 2010.79 | 2187.81 | 5041.29 | 0.00 | 0.00 | 0.00 | 0.00 | 87.23 | 311.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1900.32 | 20-JAN-06:04 | 913.19 | 304.37 | 4331.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.32 |
February | 2588.85 | 28-FEB-10:15 | 2591.66 | 1341.67 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.62 |
March | 5924.13 | 14-MAR-10:40 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.95 |
April | 10606.68 | 24-APR-09:20 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.76 |
May | 13956.43 | 31-MAY-09:00 | 1239.33 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.15 |
June | 23948.70 | 18-JUN-10:22 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.18 |
July | 25441.84 | 04-JUL-09:22 | 391.37 | 223.59 | 2784.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.27 |
August | 20785.18 | 06-AUG-09:12 | 326.14 | 186.33 | 2320.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.10 |
September | 18854.18 | 10-SEP-09:23 | 260.91 | 149.06 | 1856.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.05 |
October | 8099.39 | 11-OCT-09:30 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.71 |
November | 2685.27 | 03-NOV-09:30 | 1295.83 | 670.83 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.73 |
December | 1941.13 | 13-DEC-06:04 | 913.19 | 304.37 | 4331.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.73 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1900.32 | 260.91 | 149.06 | 1392.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.95 | |
Maximum of Months | 25441.84 | 2591.66 | 1341.67 | 4331.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12704.57 | 12-JAN-13:40 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 930.40 |
February | 17062.76 | 28-FEB-14:05 | 4021.67 | 2081.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 397.84 |
March | 19287.36 | 15-MAR-13:30 | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 21.77 | 0.00 |
April | 27186.07 | 23-APR-14:22 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 542.46 |
May | 27689.20 | 14-MAY-14:02 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.33 |
June | 27681.40 | 18-JUN-13:02 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.98 |
July | 27686.68 | 30-JUL-12:32 | 506.09 | 289.14 | 3600.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.22 |
August | 27470.94 | 13-AUG-14:22 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 226.76 | 0.00 |
September | 29121.07 | 04-SEP-15:02 | 607.31 | 346.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 464.31 |
October | 22602.94 | 31-OCT-13:30 | 2010.83 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.84 |
November | 17172.03 | 03-NOV-12:40 | 1923.15 | 1040.98 | 2160.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.01 |
December | 10239.79 | 16-DEC-13:30 | 202.44 | 173.50 | 840.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10239.79 | 202.44 | 173.50 | 840.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29121.07 | 4021.67 | 2081.97 | 4321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 226.76 | 930.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2533.55 | 12-JAN-16:00 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 531.30 |
February | 5748.67 | 28-FEB-16:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.95 |
March | 8439.66 | 21-MAR-16:00 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.46 |
April | 12687.50 | 30-APR-16:21 | 456.59 | 260.86 | 3248.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 384.27 |
May | 29617.08 | 07-MAY-16:41 | 521.82 | 298.13 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.98 |
June | 30358.10 | 18-JUN-17:01 | 0.00 | 335.39 | 3243.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.61 |
July | 29206.08 | 02-JUL-17:21 | 0.00 | 260.86 | 2522.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.19 |
August | 27171.95 | 06-AUG-16:32 | 391.37 | 223.59 | 2784.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.01 |
September | 28993.54 | 04-SEP-17:01 | 0.00 | 298.13 | 2882.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 307.78 |
October | 11687.89 | 11-OCT-16:00 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.08 |
November | 4113.74 | 15-NOV-15:30 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.78 |
December | 2565.87 | 04-DEC-15:50 | 1239.33 | 670.83 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2533.55 | 0.00 | 223.59 | 1392.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.01 | |
Maximum of Months | 30358.10 | 1239.33 | 670.83 | 3712.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 531.30 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5633.86 | 04-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.82 |
February | 7790.74 | 06-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2022.29 |
March | 5658.35 | 16-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.76 |
April | 7245.29 | 10-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.29 |
May | 8288.84 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.29 |
June | 11283.38 | 28-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.39 |
July | 14461.70 | 31-JUL-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.16 |
August | 11658.90 | 15-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.18 |
September | 10309.72 | 18-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.50 |
October | 6722.74 | 23-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.94 |
November | 5672.79 | 06-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.67 |
December | 4943.13 | 07-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4943.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.18 | |
Maximum of Months | 14461.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2022.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9343.61 | 24-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3532.25 |
February | 9131.46 | 13-FEB-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4727.37 |
March | 9942.29 | 04-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.35 |
April | 5502.57 | 17-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5214.27 | 18-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.41 |
June | 6459.69 | 29-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.56 | 0.00 |
July | 7431.58 | 20-JUL-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.58 |
August | 7963.90 | 07-AUG-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.63 |
September | 6383.53 | 18-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.93 |
October | 6625.28 | 17-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.09 |
November | 8084.33 | 24-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 767.67 |
December | 9527.96 | 26-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3771.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5214.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9942.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.56 | 4727.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 988.02 |
February | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1452.90 |
March | 11606.85 | 15-MAR-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.86 | 0.00 |
April | 9824.00 | 21-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.40 |
May | 14326.67 | 31-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.83 |
June | 18826.71 | 12-JUN-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.78 | 0.00 |
July | 19110.72 | 21-JUL-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.95 | 0.00 |
August | 18448.56 | 09-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.20 | 0.00 |
September | 14141.75 | 21-SEP-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.73 | 0.00 |
October | 7992.11 | 11-OCT-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.42 |
November | 1622.80 | 16-NOV-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.94 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1246.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19110.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.78 | 1452.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2001.94 | 12-JAN-16:40 | 222.14 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4224.60 | 28-FEB-17:00 | 222.14 | 450.11 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6998.85 | 31-MAR-24:00 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8181.42 | 02-APR-18:00 | 0.00 | 50.02 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3491.37 | 31-MAY-24:00 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5395.04 | 30-JUN-24:00 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7295.82 | 31-JUL-24:00 | 0.00 | 50.02 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8302.43 | 02-AUG-18:40 | 23.38 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3216.30 | 30-SEP-24:00 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5162.55 | 31-OCT-24:00 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5919.65 | 24-NOV-16:20 | 222.14 | 450.11 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7807.67 | 04-DEC-16:20 | 222.14 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2001.94 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8302.43 | 222.14 | 450.11 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1605.22 | 12-JAN-16:50 | 222.14 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3732.66 | 28-FEB-17:00 | 222.14 | 450.11 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6151.95 | 31-MAR-23:40 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7706.72 | 24-APR-18:00 | 23.38 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3289.55 | 31-MAY-24:00 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5150.32 | 30-JUN-24:00 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7005.63 | 31-JUL-24:00 | 0.00 | 50.02 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7959.30 | 02-AUG-18:40 | 23.38 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2673.57 | 30-SEP-24:00 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4457.30 | 31-OCT-23:50 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5435.81 | 15-NOV-16:30 | 222.14 | 450.11 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6980.48 | 04-DEC-16:30 | 222.14 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1605.22 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7959.30 | 222.14 | 450.11 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1391.04 | 12-JAN-16:40 | 222.14 | 450.11 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3682.54 | 28-FEB-17:00 | 222.14 | 450.11 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5739.93 | 31-MAR-23:20 | 0.00 | 25.01 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7702.92 | 24-APR-18:00 | 23.38 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3189.88 | 31-MAY-23:40 | 0.00 | 25.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5075.03 | 30-JUN-23:40 | 0.00 | 25.01 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6994.28 | 31-JUL-24:00 | 0.00 | 50.02 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8012.39 | 02-AUG-18:40 | 23.38 | 150.04 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2406.93 | 04-SEP-17:43 | 0.00 | 150.05 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4093.48 | 11-OCT-17:00 | 70.15 | 250.06 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5320.14 | 15-NOV-16:30 | 222.14 | 450.11 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6658.43 | 04-DEC-16:20 | 222.14 | 450.11 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1391.04 | 0.00 | 25.01 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8012.39 | 222.14 | 450.11 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 90926.03 | 12-JAN-16:55 | 9617.36 | 10941.12 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 182642.46 | 23-FEB-17:00 | 4808.68 | 5470.56 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358185.38 | 31-MAR-24:00 | 0.00 | 303.90 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 367422.34 | 24-APR-16:00 | 4808.68 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 176000.86 | 31-MAY-24:00 | 0.00 | 303.90 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 268366.79 | 30-JUN-24:00 | 0.00 | 303.90 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 360669.28 | 31-JUL-24:00 | 0.00 | 607.79 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 381878.01 | 15-AUG-16:51 | 12148.24 | 24313.41 | 3037060.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 175503.80 | 30-SEP-24:00 | 0.00 | 303.90 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 268374.60 | 31-OCT-24:00 | 0.00 | 303.90 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 276477.20 | 06-NOV-17:00 | 4808.68 | 5470.56 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 367249.93 | 04-DEC-17:00 | 4808.68 | 5470.56 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 90926.03 | 0.00 | 303.90 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 381878.01 | 12148.24 | 24313.41 | 3037060.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.167377E+13 | 1229500.65 | 13-JAN-16:00 | 0.439374E+12 | 1657705.99 | 02-JAN-05:10 |
February | 0.189141E+13 | 1325343.19 | 07-FEB-16:00 | 0.344814E+12 | 1268555.32 | 06-FEB-06:19 |
March | 0.247739E+13 | 1792360.15 | 15-MAR-14:20 | 0.131730E+12 | 851227.41 | 06-MAR-06:10 |
April | 0.267743E+13 | 1769920.15 | 07-APR-14:09 | 0.281987E+11 | 572068.75 | 17-APR-05:10 |
May | 0.172744E+13 | 1503064.59 | 23-MAY-14:30 | 0.942484E+09 | 71214.62 | 01-MAY-05:10 |
June | 0.222714E+13 | 1794909.12 | 27-JUN-14:00 | 16090501.96 | 3118.03 | 14-JUN-05:10 |
July | 0.283993E+13 | 2076347.90 | 05-JUL-15:00 | 3350.49 | 5.58 | 27-JUL-05:49 |
August | 0.322625E+13 | 2210375.60 | 15-AUG-14:39 | 327205.08 | 380.13 | 31-AUG-05:49 |
September | 0.168603E+13 | 1595981.95 | 15-SEP-10:39 | 0.764194E+09 | 73537.69 | 30-SEP-05:10 |
October | 0.200736E+13 | 1465092.29 | 11-OCT-15:00 | 0.253330E+11 | 493553.87 | 30-OCT-04:10 |
November | 0.237221E+13 | 1534664.30 | 16-NOV-16:00 | 0.948658E+11 | 634871.92 | 24-NOV-06:10 |
December | 0.278236E+13 | 1639785.26 | 01-DEC-16:00 | 0.357004E+12 | 1302684.26 | 11-DEC-06:10 |
Annual Sum or Average | 0.275887E+14 | 0.142304E+13 | ||||
Minimum of Months | 0.167377E+13 | 1229500.65 | 3350.49 | 5.58 | ||
Maximum of Months | 0.322625E+13 | 2210375.60 | 0.439374E+12 | 1657705.99 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.273673E+12 | 0.418459E+11 | 0.766053E+12 | 0.213344E+12 | 0.172811E+12 | 0.128857E+11 | 0.00 | 0.753076E+10 | 0.417653E+09 | 0.135859E+12 | 0.698401E+10 | 0.423655E+11 | 0.00 |
February | 0.245524E+12 | 0.331640E+11 | 0.978954E+12 | 0.195333E+12 | 0.155428E+12 | 0.113645E+11 | 0.00 | 0.217369E+11 | 0.121434E+10 | 0.203293E+12 | 0.635707E+10 | 0.390356E+11 | 0.00 |
March | 0.289104E+12 | 0.306117E+11 | 0.141687E+13 | 0.226058E+12 | 0.181677E+12 | 0.159046E+11 | 0.00 | 0.560775E+11 | 0.101327E+11 | 0.200491E+12 | 0.517450E+10 | 0.452818E+11 | 0.00 |
April | 0.255993E+12 | 0.239964E+11 | 0.165903E+13 | 0.211501E+12 | 0.186479E+12 | 0.169722E+11 | 0.00 | 0.643720E+11 | 0.118375E+11 | 0.205613E+12 | 0.213537E+10 | 0.395097E+11 | 0.00 |
May | 0.275586E+12 | 0.203868E+11 | 0.774844E+12 | 0.219699E+12 | 0.215988E+12 | 0.298445E+11 | 0.00 | 0.432506E+11 | 0.270254E+11 | 0.807791E+11 | 0.174579E+09 | 0.398582E+11 | 0.00 |
June | 0.273812E+12 | 0.181304E+11 | 0.106252E+13 | 0.217935E+12 | 0.245973E+12 | 0.480255E+11 | 0.00 | 0.185916E+12 | 0.959385E+11 | 0.406784E+11 | 0.108901E+10 | 0.371203E+11 | 0.00 |
July | 0.255688E+12 | 0.192056E+11 | 0.139340E+13 | 0.213265E+12 | 0.263974E+12 | 0.648537E+11 | 0.00 | 0.434273E+12 | 0.156300E+12 | 0.245611E+10 | 0.285826E+10 | 0.336525E+11 | 0.00 |
August | 0.286450E+12 | 0.227669E+11 | 0.173200E+13 | 0.226058E+12 | 0.265641E+12 | 0.608290E+11 | 0.00 | 0.448395E+12 | 0.141278E+12 | 0.452090E+10 | 0.216138E+10 | 0.361460E+11 | 0.00 |
September | 0.257041E+12 | 0.269873E+11 | 0.740713E+12 | 0.211501E+12 | 0.216503E+12 | 0.385927E+11 | 0.00 | 0.871367E+11 | 0.631747E+11 | 0.106548E+11 | 0.327827E+09 | 0.333966E+11 | 0.00 |
October | 0.269436E+12 | 0.340751E+11 | 0.108340E+13 | 0.213343E+12 | 0.194799E+12 | 0.191366E+11 | 0.00 | 0.378252E+11 | 0.127156E+11 | 0.105126E+12 | 0.138054E+10 | 0.361210E+11 | 0.00 |
November | 0.271556E+12 | 0.387231E+11 | 0.135889E+13 | 0.205298E+12 | 0.177131E+12 | 0.133519E+11 | 0.00 | 0.430034E+11 | 0.861240E+10 | 0.214105E+12 | 0.388677E+10 | 0.376514E+11 | 0.00 |
December | 0.266528E+12 | 0.433902E+11 | 0.170972E+13 | 0.213269E+12 | 0.173339E+12 | 0.128560E+11 | 0.00 | 0.524172E+11 | 0.330076E+10 | 0.261264E+12 | 0.658348E+10 | 0.396970E+11 | 0.00 |
Annual Sum or Average | 0.322039E+13 | 0.353283E+12 | 0.146764E+14 | 0.256660E+13 | 0.244974E+13 | 0.344617E+12 | 0.00 | 0.148193E+13 | 0.531948E+12 | 0.146484E+13 | 0.391128E+11 | 0.459836E+12 | 0.00 |
Minimum of Months | 0.245524E+12 | 0.181304E+11 | 0.740713E+12 | 0.195333E+12 | 0.155428E+12 | 0.113645E+11 | 0.00 | 0.753076E+10 | 0.417653E+09 | 0.245611E+10 | 0.174579E+09 | 0.333966E+11 | 0.00 |
Maximum of Months | 0.289104E+12 | 0.433902E+11 | 0.173200E+13 | 0.226058E+12 | 0.265641E+12 | 0.648537E+11 | 0.00 | 0.448395E+12 | 0.156300E+12 | 0.261264E+12 | 0.698401E+10 | 0.452818E+11 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.439374E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.344814E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.131730E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.281987E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.942484E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 16090501.96 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 3350.49 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 327205.08 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.764194E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.253330E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.948658E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.357004E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.142304E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 3350.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.439374E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 325713.14 | 02-JAN-16:49 | 40855.88 | 01-JAN-06:10 | 423497.50 | 02-JAN-08:09 | 233438.11 | 11-JAN-08:20 | 99653.90 | 02-JAN-06:19 | 25424.61 | 09-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 320162.50 | 01-FEB-08:09 | 40855.88 | 01-FEB-06:10 | 541788.89 | 01-FEB-08:09 | 233436.21 | 01-FEB-08:20 | 94821.29 | 28-FEB-15:30 | 25355.32 | 06-FEB-05:10 | 0.00 | 01-FEB-00:10 |
March | 302581.74 | 17-MAR-07:10 | 40855.88 | 01-MAR-06:10 | 660080.29 | 01-MAR-08:09 | 233426.80 | 17-MAR-07:19 | 166382.90 | 15-MAR-14:20 | 26920.71 | 15-MAR-13:30 | 0.00 | 01-MAR-00:10 |
April | 297349.23 | 12-APR-07:10 | 40855.88 | 01-APR-05:10 | 778371.69 | 03-APR-07:10 | 233424.00 | 12-APR-07:19 | 167257.92 | 21-APR-15:20 | 25087.82 | 08-APR-12:00 | 0.00 | 01-APR-00:10 |
May | 285319.03 | 11-MAY-07:10 | 40855.88 | 01-MAY-05:10 | 423497.50 | 01-MAY-07:10 | 233417.58 | 11-MAY-07:19 | 199787.84 | 31-MAY-15:50 | 47261.71 | 10-MAY-14:39 | 0.00 | 01-MAY-00:10 |
June | 281332.73 | 19-JUN-07:10 | 27558.46 | 01-JUN-19:49 | 541788.89 | 01-JUN-07:10 | 233415.46 | 19-JUN-07:19 | 237429.41 | 28-JUN-15:20 | 48827.28 | 27-JUN-07:40 | 0.00 | 01-JUN-00:10 |
July | 284436.93 | 11-JUL-07:10 | 27558.46 | 01-JUL-19:00 | 660080.29 | 03-JUL-07:10 | 233417.11 | 11-JUL-07:19 | 258978.05 | 18-JUL-15:30 | 50486.22 | 18-JUL-08:00 | 0.00 | 01-JUL-00:10 |
August | 285319.03 | 24-AUG-07:10 | 40855.88 | 02-AUG-05:10 | 778371.69 | 01-AUG-07:10 | 233417.58 | 24-AUG-07:19 | 285019.87 | 09-AUG-15:30 | 50798.61 | 15-AUG-14:39 | 0.00 | 01-AUG-00:10 |
September | 302480.73 | 26-SEP-07:10 | 40855.88 | 01-SEP-05:10 | 423497.50 | 01-SEP-07:10 | 233426.74 | 26-SEP-07:19 | 231914.64 | 21-SEP-15:00 | 53027.04 | 21-SEP-13:09 | 0.00 | 01-SEP-00:10 |
October | 322756.84 | 30-OCT-07:10 | 40855.88 | 01-OCT-05:10 | 541788.89 | 02-OCT-07:10 | 233437.60 | 30-OCT-07:19 | 171119.08 | 11-OCT-15:00 | 26221.78 | 11-OCT-12:09 | 0.00 | 01-OCT-00:10 |
November | 325713.14 | 01-NOV-07:10 | 40855.88 | 01-NOV-05:10 | 660080.29 | 01-NOV-07:10 | 233439.18 | 01-NOV-07:19 | 129213.76 | 03-NOV-14:00 | 25016.77 | 16-NOV-11:00 | 0.00 | 01-NOV-00:10 |
December | 325713.14 | 01-DEC-16:19 | 40855.88 | 01-DEC-06:10 | 778371.69 | 01-DEC-08:09 | 233439.18 | 18-DEC-08:20 | 92947.74 | 01-DEC-16:00 | 25121.89 | 11-DEC-06:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 281332.73 | 27558.46 | 423497.50 | 233415.46 | 92947.74 | 25016.77 | 0.00 | |||||||
Maximum of Months | 325713.14 | 40855.88 | 778371.69 | 233439.18 | 285019.87 | 53027.04 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 6825.55 | 12-JAN-16:40 | 686.85 | 11-JAN-15:00 | 79187.13 | 13-JAN-17:00 | 5613.48 | 02-JAN-07:10 | 56183.70 | 31-JAN-12:00 | 0.00 |
February | 13911.72 | 22-FEB-16:00 | 2278.86 | 22-FEB-17:00 | 100000.00 | 14-FEB-22:10 | 5613.48 | 01-FEB-07:10 | 56293.71 | 13-FEB-12:00 | 0.00 |
March | 301538.33 | 15-MAR-13:00 | 88748.60 | 14-MAR-12:50 | 100000.00 | 01-MAR-05:30 | 5613.48 | 01-MAR-07:10 | 56193.46 | 01-MAR-12:00 | 0.00 |
April | 137528.60 | 07-APR-13:00 | 50213.36 | 08-APR-13:39 | 100000.00 | 01-APR-04:19 | 5613.48 | 01-APR-06:10 | 54942.46 | 04-APR-11:30 | 0.00 |
May | 249937.39 | 10-MAY-14:30 | 88748.60 | 10-MAY-14:20 | 100000.00 | 07-MAY-14:09 | 5613.48 | 04-MAY-06:10 | 52289.38 | 01-MAY-11:39 | 0.00 |
June | 399258.25 | 27-JUN-07:40 | 88748.60 | 01-JUN-14:00 | 100000.00 | 03-JUN-16:10 | 5613.48 | 01-JUN-16:49 | 48862.35 | 01-JUN-11:20 | 0.00 |
July | 520460.77 | 05-JUL-15:00 | 88748.60 | 03-JUL-12:30 | 100000.00 | 06-JUL-13:09 | 5613.48 | 03-JUL-14:09 | 46097.08 | 03-JUL-11:39 | 0.00 |
August | 535338.99 | 15-AUG-14:39 | 88748.60 | 01-AUG-14:50 | 89546.10 | 22-AUG-13:00 | 5613.48 | 03-AUG-11:00 | 44705.26 | 01-AUG-11:50 | 0.00 |
September | 304641.06 | 15-SEP-10:00 | 88748.60 | 08-SEP-13:20 | 71117.54 | 19-SEP-13:00 | 5613.48 | 15-SEP-11:50 | 46042.71 | 29-SEP-11:30 | 0.00 |
October | 137444.33 | 11-OCT-14:00 | 53252.43 | 11-OCT-14:00 | 100000.00 | 30-OCT-21:10 | 5613.48 | 03-OCT-06:10 | 48758.30 | 31-OCT-11:20 | 0.00 |
November | 65872.60 | 16-NOV-12:00 | 49808.58 | 16-NOV-16:00 | 100000.00 | 01-NOV-04:30 | 5613.48 | 01-NOV-06:49 | 52161.80 | 30-NOV-12:39 | 0.00 |
December | 37451.85 | 01-DEC-10:00 | 7128.66 | 01-DEC-10:00 | 100000.00 | 01-DEC-22:10 | 5613.48 | 01-DEC-19:30 | 54919.26 | 28-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | ||||||||||
Minimum of Months | 6825.55 | 686.85 | 71117.54 | 5613.48 | 44705.26 | 0.00 | |||||
Maximum of Months | 535338.99 | 88748.60 | 100000.00 | 5613.48 | 56293.71 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1229500.65 | 13-JAN-16:00 | 325713.14 | 423497.50 | 40855.88 | 233323.41 | 74884.60 | 3880.60 | 0.00 | 5600.86 | 402.23 |
February | 1325343.19 | 07-FEB-16:00 | 313895.94 | 541788.89 | 0.00 | 233316.40 | 74459.37 | 3883.51 | 0.00 | 10030.00 | 480.64 |
March | 1792360.15 | 15-MAR-14:20 | 280450.63 | 660080.29 | 0.00 | 233151.79 | 166382.90 | 26568.96 | 0.00 | 298840.62 | 88748.60 |
April | 1769920.15 | 07-APR-14:09 | 280450.63 | 778371.69 | 0.00 | 233151.79 | 139128.35 | 25021.14 | 0.00 | 132701.28 | 49693.39 |
May | 1503064.59 | 23-MAY-14:30 | 280450.63 | 423497.50 | 0.00 | 233151.79 | 198574.21 | 25384.57 | 0.00 | 159774.26 | 53356.23 |
June | 1794909.12 | 27-JUN-14:00 | 280450.63 | 541788.89 | 0.00 | 233151.79 | 230576.58 | 48168.96 | 0.00 | 341376.92 | 88748.60 |
July | 2076347.90 | 05-JUL-15:00 | 280450.63 | 660080.29 | 0.00 | 233302.19 | 207408.63 | 50367.12 | 0.00 | 520460.77 | 88748.60 |
August | 2210375.60 | 15-AUG-14:39 | 280450.63 | 778371.69 | 0.00 | 233151.79 | 217976.71 | 50798.61 | 0.00 | 535338.99 | 88748.60 |
September | 1595981.95 | 15-SEP-10:39 | 280450.63 | 423497.50 | 0.00 | 233151.79 | 196912.13 | 48844.19 | 0.00 | 287429.40 | 88748.60 |
October | 1465092.29 | 11-OCT-15:00 | 280616.72 | 541788.89 | 0.00 | 233302.19 | 171119.08 | 25743.13 | 0.00 | 123379.65 | 52498.78 |
November | 1534664.30 | 16-NOV-16:00 | 325713.14 | 660080.29 | 40855.88 | 233326.38 | 101231.63 | 24974.41 | 0.00 | 59747.93 | 49808.58 |
December | 1639785.26 | 01-DEC-16:00 | 325713.14 | 778371.69 | 40855.88 | 233326.38 | 92947.74 | 3879.91 | 0.00 | 20633.75 | 2160.48 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1229500.65 | 280450.63 | 423497.50 | 0.00 | 233151.79 | 74459.37 | 3879.91 | 0.00 | 5600.86 | 402.23 | |
Maximum of Months | 2210375.60 | 325713.14 | 778371.69 | 40855.88 | 233326.38 | 230576.58 | 50798.61 | 0.00 | 535338.99 | 88748.60 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 1657705.99 | 02-JAN-05:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 1268555.32 | 06-FEB-06:19 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 851227.41 | 06-MAR-06:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 572068.75 | 17-APR-05:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 71214.62 | 01-MAY-05:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 3118.03 | 14-JUN-05:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 5.58 | 27-JUL-05:49 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 380.13 | 31-AUG-05:49 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 73537.69 | 30-SEP-05:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 493553.87 | 30-OCT-04:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 634871.92 | 24-NOV-06:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 1302684.26 | 11-DEC-06:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 5.58 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 1657705.99 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 45.50 | 25.76 | 25.17 | 25.76 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 43.83 | 25.80 | 23.00 | 25.80 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 55.00 | 26.08 | 28.17 | 26.09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 50.00 | 26.33 | 26.00 | 26.33 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 70.83 | 26.55 | 38.00 | 26.51 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 224.17 | 27.65 | 152.83 | 27.65 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 444.33 | 28.24 | 287.33 | 28.22 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 319.00 | 27.99 | 201.50 | 28.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 217.83 | 27.58 | 127.33 | 27.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 82.00 | 26.93 | 37.67 | 26.89 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 76.83 | 26.80 | 33.50 | 26.78 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 56.00 | 26.22 | 25.50 | 26.22 |
Annual Sum or Average | 0.00 | 0.00 | 1685.33 | 27.50 | 1006.00 | 27.52 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 43.83 | 25.76 | 23.00 | 25.76 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 444.33 | 28.24 | 287.33 | 28.22 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.60 | 0.00 | 25.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 25.76 | 0.00 | 25.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 25.67 | 0.00 | 25.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.63 | 0.00 | 25.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.83 | 25.69 | 0.00 | 25.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 25.76 | 0.00 | 25.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 19.38 | 0.67 | 19.56 | 0.00 | 19.56 | 0.00 | 19.56 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.50 | 19.38 | 0.67 | 19.56 | 0.00 | 19.56 | 0.00 | 19.56 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 19.38 | 0.67 | 19.56 | 0.00 | 19.56 | 0.00 | 19.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.17 | 18.66 | 0.67 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
February | 4.00 | 18.97 | 0.83 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
March | 1.00 | 19.19 | 0.17 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
April | 0.17 | 17.95 | 0.00 | 17.95 | 0.00 | 17.95 | 0.00 | 17.95 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
November | 0.50 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 |
December | 3.67 | 18.66 | 0.67 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
Annual Sum or Average | 13.67 | 18.79 | 2.33 | 18.99 | 0.00 | 18.99 | 0.00 | 18.99 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.17 | 19.40 | 0.83 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
February | 0.50 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 26.97 | 3.50 | 27.15 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 26.99 | 1.67 | 27.16 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 19.20 | 0.00 | 19.20 | 7.83 | 26.37 | 5.17 | 26.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 19.44 | 0.00 | 19.44 | 5.67 | 26.99 | 3.50 | 27.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
February | 0.67 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 | 0.00 | 19.12 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.87 | 1.00 | 27.87 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.83 | 2.17 | 27.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.93 | 4.50 | 27.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 28.00 | 8.00 | 28.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.81 | 1.83 | 27.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 28.04 | 3.00 | 28.04 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.53 | 0.67 | 27.53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
Annual Sum or Average | 1.33 | 19.25 | 0.00 | 19.25 | 21.17 | 27.42 | 21.17 | 27.67 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 19.40 | 0.00 | 19.40 | 8.00 | 28.04 | 8.00 | 28.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 19.24 | 0.00 | 19.24 | 0.50 | 22.03 | 0.50 | 23.42 |
February | 1.00 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.51 | 0.83 | 27.51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.75 | 1.83 | 27.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.61 | 2.00 | 27.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.62 | 4.17 | 27.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 27.67 | 8.50 | 27.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.74 | 5.83 | 27.83 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.04 | 5.00 | 28.04 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 26.60 | 4.17 | 26.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.30 | 0.33 | 27.30 |
December | 0.33 | 19.19 | 0.00 | 19.19 | 0.83 | 25.15 | 0.83 | 26.14 |
Annual Sum or Average | 2.33 | 19.12 | 0.00 | 19.12 | 35.67 | 27.07 | 34.00 | 27.35 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.97 | 0.00 | 18.97 |
Maximum of Months | 1.00 | 19.24 | 0.00 | 19.24 | 9.67 | 28.04 | 8.50 | 28.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.86 | 1.50 | 27.89 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 28.16 | 4.33 | 28.21 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.17 | 3.50 | 28.19 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 28.00 | 5.33 | 28.17 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 | 27.70 | 9.50 | 27.87 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 23.50 | 27.54 | 7.83 | 27.74 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.24 | 3.17 | 28.27 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.44 | 0.83 | 27.44 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.31 | 0.67 | 27.31 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 81.67 | 27.79 | 36.67 | 27.95 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 | 28.24 | 9.50 | 28.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 24.67 | 18.20 | 6.00 | 18.55 | 0.00 | 18.55 | 0.00 | 18.55 |
February | 22.83 | 18.10 | 6.50 | 18.48 | 0.00 | 18.48 | 0.00 | 18.48 |
March | 4.50 | 18.87 | 0.67 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
April | 0.17 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.32 | 0.67 | 27.32 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
December | 18.00 | 18.08 | 4.67 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 |
Annual Sum or Average | 70.50 | 18.19 | 17.83 | 18.54 | 0.67 | 18.60 | 0.67 | 18.67 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 24.67 | 19.31 | 6.50 | 19.31 | 0.67 | 27.32 | 0.67 | 27.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.00 | 17.07 | 0.17 | 17.05 | 0.00 | 17.05 | 0.00 | 17.05 |
February | 11.83 | 17.18 | 0.17 | 17.22 | 0.00 | 17.22 | 0.00 | 17.22 |
March | 3.00 | 18.57 | 0.00 | 18.57 | 0.00 | 18.57 | 0.00 | 18.57 |
April | 0.17 | 19.35 | 0.00 | 19.35 | 0.67 | 26.13 | 0.67 | 26.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.86 | 1.83 | 27.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.92 | 5.00 | 27.92 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 28.08 | 8.00 | 28.08 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.81 | 3.00 | 27.81 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.03 | 2.50 | 28.03 |
October | 0.17 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 | 0.00 | 19.41 |
November | 0.33 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
December | 10.33 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 |
Annual Sum or Average | 38.83 | 17.29 | 0.33 | 17.29 | 21.00 | 21.02 | 21.00 | 22.82 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.05 | 0.00 | 17.05 |
Maximum of Months | 13.00 | 19.41 | 0.17 | 19.41 | 8.00 | 28.08 | 8.00 | 28.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.17 | 17.76 | 0.17 | 17.80 | 0.50 | 18.25 | 0.50 | 18.66 |
February | 10.00 | 17.60 | 0.33 | 17.68 | 0.00 | 17.68 | 0.00 | 17.68 |
March | 2.17 | 18.98 | 0.00 | 18.98 | 0.50 | 20.57 | 0.50 | 21.67 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.75 | 1.33 | 27.75 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.67 | 1.67 | 27.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.63 | 3.17 | 27.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.76 | 7.17 | 27.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.87 | 5.33 | 27.89 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.01 | 5.33 | 28.02 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 25.97 | 5.83 | 25.97 |
November | 0.17 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
December | 7.67 | 18.08 | 0.33 | 18.18 | 0.17 | 18.37 | 0.17 | 18.54 |
Annual Sum or Average | 30.17 | 17.89 | 0.83 | 17.95 | 31.67 | 22.76 | 31.00 | 24.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.68 | 0.00 | 17.68 |
Maximum of Months | 10.17 | 19.21 | 0.33 | 19.21 | 7.33 | 28.01 | 7.17 | 28.02 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.67 | 18.18 | 0.00 | 18.18 | 0.00 | 18.18 | 0.00 | 18.18 |
February | 9.17 | 17.62 | 0.17 | 17.67 | 0.00 | 17.67 | 0.00 | 17.67 |
March | 2.33 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.75 | 1.00 | 27.77 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 28.06 | 2.67 | 28.07 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 28.46 | 3.67 | 28.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 28.50 | 4.50 | 28.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.39 | 2.83 | 28.45 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.24 | 2.17 | 28.27 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
December | 6.50 | 18.19 | 0.00 | 18.19 | 0.00 | 18.19 | 0.00 | 18.19 |
Annual Sum or Average | 25.83 | 18.05 | 0.17 | 18.06 | 30.83 | 23.64 | 16.83 | 24.73 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.17 | 19.36 | 0.17 | 19.36 | 8.83 | 28.50 | 4.50 | 28.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 66.00 | 16.90 | 23.83 | 17.13 | 0.00 | 17.13 | 0.00 | 17.13 |
February | 62.50 | 16.83 | 21.00 | 17.15 | 0.00 | 17.15 | 0.00 | 17.15 |
March | 23.17 | 17.60 | 6.50 | 17.93 | 0.00 | 17.93 | 0.00 | 17.93 |
April | 2.50 | 18.56 | 0.33 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.32 | 0.67 | 27.32 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.54 | 1.33 | 27.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.36 | 1.17 | 27.36 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2.50 | 18.74 | 0.33 | 18.93 | 0.00 | 18.93 | 0.00 | 18.93 |
November | 5.83 | 18.76 | 0.50 | 18.86 | 0.00 | 18.86 | 0.00 | 18.86 |
December | 54.50 | 16.88 | 18.33 | 17.15 | 0.00 | 17.15 | 0.00 | 17.15 |
Annual Sum or Average | 217.00 | 17.04 | 70.83 | 17.29 | 4.00 | 17.43 | 3.17 | 17.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 66.00 | 18.76 | 23.83 | 18.93 | 2.00 | 27.54 | 1.33 | 27.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 35.33 | 15.45 | 6.33 | 15.35 | 0.00 | 15.35 | 0.00 | 15.35 |
February | 32.33 | 15.53 | 3.50 | 15.50 | 0.00 | 15.50 | 0.00 | 15.50 |
March | 11.17 | 16.64 | 0.17 | 16.61 | 0.00 | 16.61 | 0.00 | 16.61 |
April | 1.67 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.79 | 1.17 | 27.79 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.78 | 6.33 | 27.78 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 28.10 | 8.50 | 28.11 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.78 | 4.00 | 27.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.80 | 1.83 | 27.80 |
October | 1.67 | 18.51 | 0.00 | 18.51 | 0.00 | 18.51 | 0.00 | 18.51 |
November | 4.17 | 18.30 | 0.00 | 18.30 | 0.00 | 18.30 | 0.00 | 18.30 |
December | 33.00 | 15.62 | 5.83 | 15.53 | 0.00 | 15.53 | 0.00 | 15.53 |
Annual Sum or Average | 119.33 | 15.82 | 15.83 | 15.72 | 22.33 | 17.45 | 21.83 | 18.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.35 | 0.00 | 15.35 |
Maximum of Months | 35.33 | 18.56 | 6.33 | 18.56 | 8.83 | 28.10 | 8.50 | 28.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 31.50 | 15.98 | 3.50 | 15.91 | 0.00 | 15.91 | 0.00 | 15.91 |
February | 32.33 | 16.10 | 3.50 | 16.16 | 0.00 | 16.16 | 0.00 | 16.16 |
March | 8.83 | 17.31 | 0.50 | 17.28 | 0.00 | 17.28 | 0.00 | 17.28 |
April | 1.33 | 18.50 | 0.00 | 18.50 | 0.83 | 22.00 | 0.83 | 23.56 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.61 | 1.83 | 27.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.72 | 3.83 | 27.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.83 | 8.00 | 27.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.99 | 5.17 | 28.02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.13 | 4.67 | 28.13 |
October | 1.17 | 18.39 | 0.00 | 18.39 | 0.67 | 21.74 | 0.67 | 23.30 |
November | 3.67 | 18.66 | 0.00 | 18.66 | 0.00 | 18.66 | 0.00 | 18.66 |
December | 26.17 | 16.24 | 3.17 | 16.27 | 0.00 | 16.27 | 0.00 | 16.27 |
Annual Sum or Average | 105.00 | 16.35 | 10.67 | 16.33 | 26.17 | 18.46 | 25.00 | 19.87 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.91 | 0.00 | 15.91 |
Maximum of Months | 32.33 | 18.66 | 3.50 | 18.66 | 8.67 | 28.13 | 8.00 | 28.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 29.83 | 15.64 | 5.17 | 15.53 | 0.00 | 15.53 | 0.00 | 15.53 |
February | 21.17 | 16.02 | 1.83 | 16.00 | 0.00 | 16.00 | 0.00 | 16.00 |
March | 6.83 | 17.67 | 0.00 | 17.67 | 0.00 | 17.67 | 0.00 | 17.67 |
April | 0.67 | 18.66 | 0.00 | 18.66 | 0.67 | 23.06 | 0.67 | 24.53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.08 | 2.83 | 28.07 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.55 | 3.83 | 28.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 28.52 | 5.33 | 28.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.41 | 3.17 | 28.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.21 | 2.33 | 28.23 |
October | 1.00 | 18.75 | 0.00 | 18.75 | 0.00 | 18.75 | 0.00 | 18.75 |
November | 3.17 | 18.74 | 0.00 | 18.74 | 0.00 | 18.74 | 0.00 | 18.74 |
December | 19.17 | 16.20 | 1.83 | 16.12 | 0.00 | 16.12 | 0.00 | 16.12 |
Annual Sum or Average | 81.83 | 16.22 | 8.83 | 16.12 | 31.33 | 19.27 | 18.17 | 20.46 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.53 | 0.00 | 15.53 |
Maximum of Months | 29.83 | 18.75 | 5.17 | 18.75 | 10.00 | 28.55 | 5.33 | 28.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 28.00 | 28.42 | 14.00 | 28.35 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 98.83 | 29.22 | 78.00 | 29.19 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 126.83 | 29.04 | 92.00 | 29.03 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 98.83 | 29.22 | 78.00 | 29.19 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 308.67 | 24.11 | 43.17 | 24.33 | 13.67 | 24.41 |
February | 243.83 | 24.01 | 26.67 | 24.22 | 0.00 | 24.22 |
March | 160.67 | 24.00 | 122.83 | 24.53 | 0.00 | 24.53 |
April | 22.67 | 24.00 | 130.33 | 25.79 | 0.00 | 25.79 |
May | 17.17 | 24.06 | 220.83 | 25.30 | 0.33 | 25.30 |
June | 132.00 | 27.75 | 391.33 | 26.39 | 132.00 | 26.66 |
July | 255.50 | 28.48 | 493.17 | 27.33 | 255.50 | 27.62 |
August | 178.00 | 28.27 | 489.83 | 26.57 | 178.00 | 26.93 |
September | 88.00 | 27.84 | 409.33 | 25.91 | 88.00 | 26.20 |
October | 1.50 | 26.99 | 255.00 | 25.44 | 1.17 | 25.45 |
November | 28.33 | 24.26 | 165.83 | 25.75 | 2.00 | 25.77 |
December | 144.83 | 24.00 | 105.33 | 24.91 | 0.00 | 24.91 |
Annual Sum or Average | 1581.17 | 25.76 | 2853.67 | 25.86 | 670.67 | 26.16 |
Minimum of Months | 1.50 | 24.00 | 26.67 | 24.22 | 0.00 | 24.22 |
Maximum of Months | 308.67 | 28.48 | 493.17 | 27.33 | 255.50 | 27.62 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 435.17 | 23.80 | 12.50 | 23.83 | 12.50 | 23.85 |
February | 350.17 | 23.85 | 6.00 | 23.88 | 0.00 | 23.88 |
March | 189.50 | 23.95 | 96.67 | 24.20 | 0.00 | 24.20 |
April | 25.33 | 23.98 | 95.83 | 25.10 | 0.00 | 25.10 |
May | 38.00 | 23.96 | 176.83 | 24.58 | 0.00 | 24.58 |
June | 0.00 | 0.00 | 378.17 | 24.33 | 0.00 | 24.33 |
July | 0.00 | 0.00 | 489.50 | 24.33 | 0.00 | 24.33 |
August | 0.00 | 0.00 | 496.17 | 24.26 | 0.00 | 24.26 |
September | 0.17 | 23.63 | 380.50 | 24.43 | 0.00 | 24.43 |
October | 18.50 | 23.92 | 216.17 | 24.75 | 0.00 | 24.75 |
November | 58.67 | 23.96 | 101.67 | 24.99 | 0.00 | 24.99 |
December | 222.83 | 23.91 | 47.67 | 24.19 | 0.00 | 24.19 |
Annual Sum or Average | 1338.33 | 23.87 | 2497.67 | 24.30 | 12.50 | 24.30 |
Minimum of Months | 0.00 | 0.00 | 6.00 | 23.83 | 0.00 | 23.85 |
Maximum of Months | 435.17 | 23.98 | 496.17 | 25.10 | 12.50 | 25.10 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.03 | 62.17 | 21.82 | 62.17 | 21.66 |
February | 454.00 | 22.29 | 27.33 | 22.22 | 27.33 | 22.16 |
March | 421.00 | 23.22 | 31.50 | 23.27 | 2.00 | 23.26 |
April | 296.50 | 23.53 | 7.67 | 23.57 | 0.00 | 23.57 |
May | 151.33 | 23.67 | 127.33 | 24.06 | 0.00 | 24.06 |
June | 33.83 | 23.75 | 295.50 | 24.17 | 0.00 | 24.17 |
July | 0.00 | 0.00 | 477.17 | 24.21 | 0.00 | 24.21 |
August | 0.00 | 0.00 | 442.67 | 24.22 | 0.00 | 24.22 |
September | 43.67 | 23.56 | 260.00 | 24.22 | 0.50 | 24.22 |
October | 256.67 | 23.55 | 52.67 | 23.69 | 0.00 | 23.69 |
November | 397.67 | 23.40 | 1.67 | 23.41 | 0.00 | 23.41 |
December | 489.83 | 22.40 | 23.67 | 22.33 | 23.67 | 22.26 |
Annual Sum or Average | 3046.50 | 22.87 | 1809.33 | 23.30 | 115.67 | 23.24 |
Minimum of Months | 0.00 | 0.00 | 1.67 | 21.82 | 0.00 | 21.66 |
Maximum of Months | 502.00 | 23.75 | 477.17 | 24.22 | 62.17 | 24.22 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.79 | 261.50 | 20.52 | 261.50 | 20.38 |
February | 454.00 | 21.00 | 212.33 | 20.69 | 212.33 | 20.54 |
March | 461.50 | 21.94 | 129.17 | 21.75 | 106.00 | 21.55 |
April | 409.67 | 22.72 | 19.50 | 22.61 | 19.50 | 22.51 |
May | 238.33 | 23.36 | 84.67 | 23.59 | 0.00 | 23.59 |
June | 69.00 | 23.56 | 290.67 | 24.07 | 0.00 | 24.07 |
July | 1.33 | 23.60 | 465.67 | 24.24 | 0.00 | 24.24 |
August | 9.33 | 23.45 | 428.67 | 24.19 | 0.00 | 24.19 |
September | 142.67 | 23.20 | 209.67 | 23.81 | 2.17 | 23.82 |
October | 393.67 | 22.48 | 44.83 | 22.41 | 28.33 | 22.29 |
November | 484.17 | 22.01 | 65.33 | 21.81 | 65.33 | 21.66 |
December | 497.00 | 20.95 | 218.67 | 20.66 | 218.67 | 20.51 |
Annual Sum or Average | 3662.67 | 21.86 | 2430.67 | 22.19 | 913.83 | 21.92 |
Minimum of Months | 1.33 | 20.79 | 19.50 | 20.52 | 0.00 | 20.38 |
Maximum of Months | 502.00 | 23.60 | 465.67 | 24.24 | 261.50 | 24.24 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.21 | 220.50 | 21.07 | 220.50 | 20.99 |
February | 454.00 | 21.48 | 141.00 | 21.31 | 141.00 | 21.21 |
March | 431.83 | 22.43 | 77.33 | 22.40 | 46.17 | 22.27 |
April | 313.83 | 23.32 | 18.83 | 23.42 | 0.00 | 23.42 |
May | 176.50 | 23.59 | 114.83 | 23.98 | 0.00 | 23.98 |
June | 16.00 | 25.13 | 363.17 | 24.40 | 7.50 | 24.44 |
July | 25.17 | 26.72 | 492.17 | 24.56 | 25.17 | 24.66 |
August | 10.83 | 26.57 | 471.83 | 24.36 | 10.17 | 24.41 |
September | 74.83 | 23.46 | 267.50 | 24.16 | 1.50 | 24.17 |
October | 336.00 | 23.23 | 45.17 | 23.38 | 0.00 | 23.38 |
November | 436.67 | 22.91 | 9.00 | 22.96 | 0.00 | 22.96 |
December | 493.67 | 21.79 | 80.83 | 21.64 | 80.83 | 21.53 |
Annual Sum or Average | 3271.33 | 22.39 | 2302.17 | 22.90 | 532.83 | 22.76 |
Minimum of Months | 10.83 | 21.21 | 9.00 | 21.07 | 0.00 | 20.99 |
Maximum of Months | 502.00 | 26.72 | 492.17 | 24.56 | 220.50 | 24.66 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.17 | 210.17 | 21.04 | 210.17 | 20.97 |
February | 450.17 | 21.40 | 139.67 | 21.24 | 139.67 | 21.14 |
March | 425.33 | 22.21 | 68.67 | 22.25 | 34.33 | 22.16 |
April | 302.83 | 22.81 | 69.67 | 23.12 | 2.00 | 23.14 |
May | 174.83 | 23.31 | 200.17 | 23.95 | 9.00 | 24.02 |
June | 48.33 | 24.86 | 388.00 | 24.43 | 20.00 | 24.53 |
July | 43.00 | 26.79 | 487.33 | 24.60 | 43.00 | 24.76 |
August | 35.67 | 24.47 | 442.50 | 24.26 | 13.67 | 24.33 |
September | 114.83 | 23.34 | 311.67 | 24.12 | 10.67 | 24.19 |
October | 328.17 | 22.74 | 83.17 | 23.10 | 0.50 | 23.11 |
November | 443.50 | 22.24 | 13.17 | 22.32 | 0.17 | 22.32 |
December | 496.67 | 21.29 | 128.67 | 21.18 | 128.67 | 21.10 |
Annual Sum or Average | 3365.33 | 22.14 | 2542.83 | 22.79 | 611.83 | 22.69 |
Minimum of Months | 35.67 | 21.17 | 13.17 | 21.04 | 0.17 | 20.97 |
Maximum of Months | 502.00 | 26.79 | 487.33 | 24.60 | 210.17 | 24.76 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 467.00 | 21.36 | 210.33 | 21.17 | 204.17 | 21.04 |
February | 414.83 | 21.59 | 152.33 | 21.37 | 146.83 | 21.22 |
March | 346.33 | 22.42 | 99.33 | 22.64 | 31.17 | 22.53 |
April | 271.17 | 22.96 | 92.67 | 23.32 | 9.17 | 23.33 |
May | 182.33 | 23.36 | 178.00 | 23.94 | 6.67 | 24.00 |
June | 52.50 | 24.54 | 372.17 | 24.38 | 16.50 | 24.47 |
July | 38.67 | 26.87 | 479.83 | 24.64 | 38.67 | 24.79 |
August | 32.67 | 26.07 | 469.50 | 24.46 | 24.50 | 24.57 |
September | 91.33 | 24.06 | 343.33 | 24.39 | 21.33 | 24.52 |
October | 245.17 | 22.94 | 141.00 | 23.53 | 6.83 | 23.59 |
November | 375.83 | 22.46 | 59.33 | 22.74 | 4.67 | 22.72 |
December | 461.67 | 21.60 | 139.67 | 21.50 | 127.17 | 21.37 |
Annual Sum or Average | 2979.50 | 22.35 | 2737.50 | 23.02 | 637.67 | 22.90 |
Minimum of Months | 32.67 | 21.36 | 59.33 | 21.17 | 4.67 | 21.04 |
Maximum of Months | 467.00 | 26.87 | 479.83 | 24.64 | 204.17 | 24.79 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 498.50 | 21.48 | 113.00 | 21.37 | 112.17 | 21.30 |
February | 435.00 | 22.08 | 37.00 | 22.02 | 33.17 | 21.95 |
March | 265.17 | 23.07 | 116.17 | 23.52 | 5.17 | 23.57 |
April | 76.17 | 24.18 | 219.83 | 24.71 | 14.50 | 24.82 |
May | 112.00 | 23.85 | 255.33 | 24.41 | 18.83 | 24.54 |
June | 35.67 | 26.69 | 456.67 | 24.67 | 33.67 | 24.81 |
July | 80.50 | 26.37 | 497.00 | 24.84 | 80.50 | 25.03 |
August | 61.67 | 26.23 | 514.00 | 24.67 | 61.67 | 24.82 |
September | 63.17 | 24.52 | 372.00 | 24.49 | 23.50 | 24.62 |
October | 178.00 | 23.26 | 186.67 | 23.95 | 1.50 | 23.96 |
November | 262.33 | 23.25 | 68.33 | 23.61 | 0.33 | 23.62 |
December | 423.33 | 22.81 | 11.67 | 22.85 | 1.67 | 22.85 |
Annual Sum or Average | 2491.50 | 22.91 | 2847.67 | 23.70 | 386.67 | 23.75 |
Minimum of Months | 35.67 | 21.48 | 11.67 | 21.37 | 0.33 | 21.30 |
Maximum of Months | 498.50 | 26.69 | 514.00 | 24.84 | 112.17 | 25.03 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.10 | 467.83 | 20.07 | 467.83 | 20.06 |
February | 454.00 | 20.23 | 406.67 | 20.18 | 406.67 | 20.17 |
March | 482.83 | 21.14 | 249.33 | 20.97 | 231.83 | 20.83 |
April | 456.50 | 22.13 | 42.67 | 21.97 | 42.67 | 21.84 |
May | 290.17 | 23.12 | 66.50 | 23.34 | 0.17 | 23.34 |
June | 70.83 | 23.82 | 285.33 | 24.18 | 8.50 | 24.22 |
July | 21.67 | 25.65 | 464.33 | 24.44 | 20.17 | 24.49 |
August | 41.67 | 23.57 | 399.83 | 24.20 | 5.33 | 24.21 |
September | 204.50 | 23.11 | 161.83 | 23.60 | 10.00 | 23.66 |
October | 454.17 | 22.00 | 50.67 | 21.90 | 44.33 | 21.79 |
November | 489.00 | 21.17 | 161.67 | 20.98 | 161.67 | 20.87 |
December | 497.00 | 20.23 | 416.33 | 20.15 | 416.33 | 20.12 |
Annual Sum or Average | 3964.33 | 21.35 | 3173.00 | 21.63 | 1815.50 | 21.36 |
Minimum of Months | 21.67 | 20.10 | 42.67 | 20.07 | 0.17 | 20.06 |
Maximum of Months | 502.00 | 25.65 | 467.83 | 24.44 | 467.83 | 24.49 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.06 | 398.83 | 20.03 | 398.83 | 20.02 |
February | 385.00 | 20.25 | 325.17 | 20.16 | 325.17 | 20.13 |
March | 404.83 | 21.28 | 168.00 | 21.12 | 153.17 | 20.98 |
April | 314.83 | 21.85 | 68.33 | 22.03 | 30.67 | 21.93 |
May | 218.50 | 22.83 | 127.50 | 23.51 | 8.83 | 23.59 |
June | 88.67 | 24.03 | 280.17 | 24.35 | 22.67 | 24.49 |
July | 53.17 | 26.37 | 395.33 | 24.74 | 48.67 | 24.93 |
August | 72.17 | 23.92 | 329.33 | 24.30 | 20.17 | 24.41 |
September | 177.33 | 22.94 | 192.00 | 23.75 | 17.17 | 23.87 |
October | 361.83 | 21.85 | 61.50 | 21.95 | 29.67 | 21.86 |
November | 411.00 | 21.09 | 126.83 | 20.92 | 126.83 | 20.82 |
December | 422.00 | 20.15 | 365.00 | 20.09 | 365.00 | 20.07 |
Annual Sum or Average | 3336.33 | 21.36 | 2838.00 | 21.78 | 1546.83 | 21.55 |
Minimum of Months | 53.17 | 20.06 | 61.50 | 20.03 | 8.83 | 20.02 |
Maximum of Months | 427.00 | 26.37 | 398.83 | 24.74 | 398.83 | 24.93 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 477.17 | 20.70 | 336.50 | 20.50 | 330.50 | 20.40 |
February | 422.83 | 20.78 | 267.00 | 20.55 | 261.83 | 20.44 |
March | 379.83 | 21.74 | 154.33 | 21.83 | 95.83 | 21.64 |
April | 339.00 | 22.25 | 91.33 | 22.53 | 26.00 | 22.46 |
May | 236.83 | 23.00 | 149.00 | 23.58 | 6.67 | 23.64 |
June | 98.67 | 23.82 | 322.33 | 24.20 | 19.83 | 24.30 |
July | 62.67 | 25.69 | 461.50 | 24.59 | 47.33 | 24.75 |
August | 61.17 | 24.62 | 428.83 | 24.39 | 25.17 | 24.51 |
September | 144.83 | 23.68 | 299.50 | 24.21 | 29.67 | 24.37 |
October | 310.17 | 22.40 | 137.50 | 22.89 | 27.00 | 22.86 |
November | 404.33 | 21.59 | 128.83 | 21.66 | 88.83 | 21.50 |
December | 476.00 | 20.71 | 313.67 | 20.56 | 307.50 | 20.46 |
Annual Sum or Average | 3413.50 | 21.78 | 3090.33 | 22.32 | 1266.17 | 22.09 |
Minimum of Months | 61.17 | 20.70 | 91.33 | 20.50 | 6.67 | 20.40 |
Maximum of Months | 477.17 | 25.69 | 461.50 | 24.59 | 330.50 | 24.75 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.28 | 426.83 | 20.21 | 426.83 | 20.19 |
February | 451.83 | 20.50 | 337.00 | 20.39 | 337.00 | 20.34 |
March | 453.50 | 21.42 | 160.83 | 21.36 | 134.50 | 21.22 |
April | 379.83 | 22.07 | 75.00 | 22.30 | 22.33 | 22.25 |
May | 258.17 | 22.95 | 163.50 | 23.58 | 14.83 | 23.70 |
June | 90.83 | 23.95 | 362.33 | 24.30 | 23.50 | 24.42 |
July | 51.67 | 25.85 | 467.00 | 24.62 | 41.33 | 24.76 |
August | 62.17 | 24.20 | 434.17 | 24.36 | 20.83 | 24.45 |
September | 203.00 | 23.09 | 226.33 | 23.79 | 22.00 | 23.93 |
October | 422.17 | 21.92 | 66.33 | 22.04 | 26.00 | 21.96 |
November | 478.00 | 21.26 | 110.17 | 21.13 | 110.17 | 21.04 |
December | 497.00 | 20.44 | 370.83 | 20.34 | 370.83 | 20.30 |
Annual Sum or Average | 3850.17 | 21.49 | 3200.33 | 21.98 | 1550.17 | 21.77 |
Minimum of Months | 51.67 | 20.28 | 66.33 | 20.21 | 14.83 | 20.19 |
Maximum of Months | 502.00 | 25.85 | 467.00 | 24.62 | 426.83 | 24.76 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.84 | 489.50 | 19.82 | 489.50 | 19.82 |
February | 454.00 | 19.89 | 433.83 | 19.87 | 433.83 | 19.86 |
March | 487.67 | 20.65 | 324.17 | 20.48 | 309.50 | 20.37 |
April | 472.50 | 21.55 | 126.33 | 21.25 | 126.33 | 21.05 |
May | 333.33 | 22.71 | 64.33 | 22.87 | 10.17 | 22.81 |
June | 98.17 | 23.55 | 278.17 | 24.08 | 12.33 | 24.16 |
July | 39.00 | 25.36 | 455.50 | 24.46 | 29.83 | 24.55 |
August | 74.83 | 23.52 | 377.17 | 24.13 | 11.50 | 24.18 |
September | 261.83 | 22.69 | 146.50 | 23.22 | 12.83 | 23.27 |
October | 476.33 | 21.29 | 134.50 | 20.99 | 129.33 | 20.77 |
November | 489.00 | 20.49 | 298.17 | 20.30 | 298.17 | 20.22 |
December | 497.00 | 19.85 | 468.00 | 19.81 | 468.00 | 19.80 |
Annual Sum or Average | 4185.67 | 20.98 | 3596.17 | 21.23 | 2331.33 | 20.96 |
Minimum of Months | 39.00 | 19.84 | 64.33 | 19.81 | 10.17 | 19.80 |
Maximum of Months | 502.00 | 25.36 | 489.50 | 24.46 | 489.50 | 24.55 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.92 | 493.00 | 19.91 | 493.00 | 19.90 |
February | 454.00 | 20.01 | 396.83 | 19.92 | 396.83 | 19.89 |
March | 480.67 | 20.88 | 250.50 | 20.68 | 229.67 | 20.51 |
April | 371.17 | 21.46 | 111.00 | 21.41 | 79.67 | 21.20 |
May | 249.17 | 22.56 | 159.50 | 23.27 | 11.17 | 23.32 |
June | 101.17 | 23.99 | 348.00 | 24.28 | 29.50 | 24.43 |
July | 66.83 | 26.07 | 467.50 | 24.65 | 57.00 | 24.84 |
August | 86.50 | 23.79 | 404.17 | 24.22 | 24.17 | 24.33 |
September | 204.00 | 22.56 | 241.67 | 23.51 | 17.33 | 23.59 |
October | 442.67 | 21.42 | 114.67 | 21.26 | 92.67 | 21.06 |
November | 489.00 | 20.62 | 274.17 | 20.43 | 274.17 | 20.34 |
December | 497.00 | 19.92 | 468.83 | 19.88 | 468.83 | 19.87 |
Annual Sum or Average | 3944.17 | 21.04 | 3729.83 | 21.47 | 2174.00 | 21.22 |
Minimum of Months | 66.83 | 19.92 | 111.00 | 19.88 | 11.17 | 19.87 |
Maximum of Months | 502.00 | 26.07 | 493.00 | 24.65 | 493.00 | 24.84 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 484.17 | 20.27 | 392.00 | 20.10 | 389.17 | 20.02 |
February | 431.50 | 20.28 | 326.50 | 20.06 | 322.50 | 19.96 |
March | 411.33 | 21.22 | 213.00 | 21.10 | 172.00 | 20.88 |
April | 359.00 | 21.60 | 143.50 | 21.68 | 89.33 | 21.48 |
May | 268.33 | 22.54 | 133.00 | 23.10 | 13.83 | 23.11 |
June | 125.33 | 23.47 | 306.83 | 24.07 | 22.33 | 24.20 |
July | 75.33 | 25.26 | 445.17 | 24.56 | 50.17 | 24.72 |
August | 89.67 | 23.93 | 405.67 | 24.28 | 24.17 | 24.39 |
September | 184.83 | 23.09 | 271.33 | 23.89 | 29.33 | 24.04 |
October | 356.83 | 21.71 | 159.33 | 21.93 | 72.83 | 21.71 |
November | 435.17 | 21.00 | 204.33 | 20.80 | 188.67 | 20.64 |
December | 484.33 | 20.23 | 391.67 | 20.08 | 391.33 | 20.02 |
Annual Sum or Average | 3705.83 | 21.33 | 3392.33 | 21.76 | 1765.67 | 21.50 |
Minimum of Months | 75.33 | 20.23 | 133.00 | 20.06 | 13.83 | 19.96 |
Maximum of Months | 484.33 | 25.26 | 445.17 | 24.56 | 391.33 | 24.72 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.00 | 460.33 | 19.95 | 460.33 | 19.93 |
February | 452.00 | 20.14 | 378.67 | 20.03 | 378.67 | 19.99 |
March | 462.83 | 21.00 | 237.33 | 20.87 | 214.67 | 20.72 |
April | 394.00 | 21.54 | 122.83 | 21.65 | 73.17 | 21.49 |
May | 294.83 | 22.57 | 145.33 | 23.22 | 15.67 | 23.33 |
June | 114.00 | 23.56 | 342.67 | 24.18 | 25.83 | 24.31 |
July | 70.33 | 25.22 | 452.17 | 24.57 | 48.33 | 24.72 |
August | 95.33 | 23.73 | 409.83 | 24.25 | 26.67 | 24.35 |
September | 247.17 | 22.67 | 197.17 | 23.44 | 21.83 | 23.59 |
October | 449.00 | 21.42 | 116.17 | 21.34 | 86.33 | 21.16 |
November | 484.00 | 20.78 | 223.33 | 20.58 | 223.33 | 20.47 |
December | 497.00 | 20.05 | 429.33 | 19.97 | 429.33 | 19.94 |
Annual Sum or Average | 4062.50 | 21.16 | 3515.17 | 21.58 | 2004.17 | 21.34 |
Minimum of Months | 70.33 | 20.00 | 116.17 | 19.95 | 15.67 | 19.93 |
Maximum of Months | 502.00 | 25.22 | 460.33 | 24.57 | 460.33 | 24.72 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 482.50 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 12.17 | 27.00 | 514.00 | 27.00 | 12.17 | 27.00 |
April | 56.50 | 27.00 | 485.00 | 27.00 | 56.50 | 27.00 |
May | 9.33 | 27.00 | 508.00 | 27.00 | 9.33 | 27.00 |
June | 124.33 | 27.00 | 496.00 | 27.00 | 124.33 | 27.00 |
July | 304.17 | 27.00 | 497.00 | 27.00 | 304.17 | 27.00 |
August | 394.33 | 27.00 | 514.00 | 27.00 | 394.33 | 27.00 |
September | 25.67 | 27.00 | 485.00 | 27.00 | 25.67 | 27.00 |
October | 10.83 | 27.00 | 502.00 | 27.00 | 10.83 | 27.00 |
November | 3.17 | 27.00 | 489.00 | 27.00 | 3.17 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 940.50 | 27.00 | 5923.50 | 27.00 | 940.50 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 394.33 | 27.00 | 514.00 | 27.00 | 394.33 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 77.50 | 25.40 | 174.33 | 26.51 | 0.00 | 26.51 |
February | 2.17 | 27.00 | 230.83 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 454.67 | 27.00 | 0.00 | 27.00 |
April | 2.50 | 27.00 | 485.00 | 27.00 | 2.50 | 27.00 |
May | 5.00 | 27.00 | 508.00 | 27.00 | 5.00 | 27.00 |
June | 21.17 | 27.00 | 496.00 | 27.00 | 21.17 | 27.00 |
July | 59.50 | 27.00 | 497.00 | 27.00 | 59.50 | 27.00 |
August | 80.17 | 27.00 | 514.00 | 27.00 | 80.17 | 27.00 |
September | 5.67 | 27.00 | 485.00 | 27.00 | 5.67 | 27.00 |
October | 1.67 | 27.00 | 502.00 | 27.00 | 1.67 | 27.00 |
November | 0.00 | 0.00 | 488.67 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 352.33 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 255.33 | 26.51 | 5187.83 | 26.98 | 175.67 | 26.98 |
Minimum of Months | 0.00 | 0.00 | 174.33 | 26.51 | 0.00 | 26.51 |
Maximum of Months | 80.17 | 27.00 | 514.00 | 27.00 | 80.17 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 248.33 | 24.91 | 112.33 | 25.24 | 26.33 | 25.06 |
February | 67.83 | 27.00 | 144.67 | 27.00 | 0.00 | 27.00 |
March | 14.33 | 27.00 | 364.67 | 27.00 | 0.00 | 27.00 |
April | 3.00 | 27.00 | 469.83 | 27.00 | 3.00 | 27.00 |
May | 6.17 | 27.00 | 508.00 | 27.00 | 6.17 | 27.00 |
June | 56.00 | 27.00 | 496.00 | 27.00 | 56.00 | 27.00 |
July | 113.00 | 27.00 | 497.00 | 27.00 | 113.00 | 27.00 |
August | 109.83 | 27.00 | 514.00 | 27.00 | 109.83 | 27.00 |
September | 10.50 | 27.00 | 485.00 | 27.00 | 10.50 | 27.00 |
October | 1.83 | 27.00 | 470.67 | 27.00 | 1.83 | 27.00 |
November | 0.00 | 0.00 | 413.50 | 27.00 | 0.00 | 27.00 |
December | 46.67 | 27.00 | 227.67 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 677.50 | 26.23 | 4703.33 | 26.88 | 326.67 | 26.87 |
Minimum of Months | 0.00 | 0.00 | 112.33 | 25.24 | 0.00 | 25.06 |
Maximum of Months | 248.33 | 27.00 | 514.00 | 27.00 | 113.00 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 150.83 | 27.00 | 502.00 | 27.00 | 150.83 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 496.17 | 27.00 | 508.00 | 27.00 | 496.17 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.05 | 497.00 | 27.05 | 497.00 | 27.05 |
August | 514.00 | 27.34 | 514.00 | 27.34 | 514.00 | 27.34 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5580.00 | 27.04 | 5943.00 | 27.04 | 5580.00 | 27.04 |
Minimum of Months | 150.83 | 27.00 | 454.00 | 27.00 | 150.83 | 27.00 |
Maximum of Months | 514.00 | 27.34 | 514.00 | 27.34 | 514.00 | 27.34 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 16.97403 | 0.65436 | 14.11765 |
February | 454.00000 | 27.00000 | 16.09148 | 0.70025 | 15.41660 |
March | 514.00000 | 27.00007 | 21.75416 | 0.84360 | 20.23148 |
April | 485.00000 | 27.00001 | 26.61896 | 0.94845 | 24.07562 |
May | 508.00000 | 27.00024 | 30.36219 | 0.22810 | 6.22863 |
June | 496.00000 | 27.00086 | 34.77845 | 0.35516 | 7.72898 |
July | 497.00000 | 27.00079 | 37.07340 | 0.43274 | 8.97885 |
August | 514.00000 | 27.00021 | 36.31407 | 0.45917 | 9.48212 |
September | 485.00000 | 27.00061 | 35.83391 | 0.28757 | 6.83101 |
October | 502.00000 | 27.00018 | 30.21175 | 0.90415 | 22.34813 |
November | 489.00000 | 27.00001 | 26.04156 | 0.87885 | 21.39860 |
December | 497.00000 | 27.00000 | 19.02594 | 0.80522 | 18.78309 |
Annual Sum or Average | 5943.00000 | 27.00025 | 27.66604 | 0.62366 | 14.60992 |
Minimum of Months | 454.00000 | 27.00000 | 16.09148 | 0.22810 | 6.22863 |
Maximum of Months | 514.00000 | 27.00086 | 37.07340 | 0.94845 | 24.07562 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.69557 | 17.16894 | 0.46110 | 10.16559 |
February | 454.00000 | 27.00000 | 16.07923 | 0.54397 | 11.35257 |
March | 514.00000 | 27.00006 | 21.74552 | 0.69745 | 15.56282 |
April | 485.00000 | 27.00001 | 26.59604 | 0.80000 | 18.65551 |
May | 508.00000 | 27.00022 | 30.37303 | 0.14559 | 5.65733 |
June | 496.00000 | 27.00086 | 34.79427 | 0.26130 | 6.58356 |
July | 497.00000 | 27.00086 | 37.09396 | 0.32024 | 7.23796 |
August | 514.00000 | 27.00026 | 36.30617 | 0.32579 | 7.33619 |
September | 485.00000 | 27.00046 | 35.96187 | 0.19939 | 6.00045 |
October | 502.00000 | 27.00016 | 30.19723 | 0.79018 | 18.31248 |
November | 489.00000 | 27.00001 | 26.00504 | 0.71703 | 15.95684 |
December | 497.00000 | 27.00000 | 19.00312 | 0.59463 | 12.58466 |
Annual Sum or Average | 5943.00000 | 26.97453 | 27.68654 | 0.48707 | 11.26912 |
Minimum of Months | 454.00000 | 26.69557 | 16.07923 | 0.14559 | 5.65733 |
Maximum of Months | 514.00000 | 27.00086 | 37.09396 | 0.80000 | 18.65551 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 25.88184 | 17.50813 | 0.24715 | 8.49710 |
February | 454.00000 | 27.00014 | 16.07895 | 0.48020 | 10.09463 |
March | 514.00000 | 27.00007 | 21.75369 | 0.63439 | 13.97257 |
April | 485.00000 | 27.00001 | 26.60534 | 0.74879 | 17.11262 |
May | 508.00000 | 27.00030 | 30.40197 | 0.11514 | 5.65648 |
June | 496.00000 | 27.00087 | 34.80362 | 0.26074 | 6.69758 |
July | 497.00000 | 27.00087 | 37.10074 | 0.33009 | 7.44708 |
August | 514.00000 | 27.00028 | 36.31905 | 0.32565 | 7.42395 |
September | 485.00000 | 27.00044 | 36.02373 | 0.16990 | 5.92656 |
October | 502.00000 | 27.00016 | 30.22167 | 0.73041 | 16.52762 |
November | 489.00000 | 27.00001 | 26.02099 | 0.63954 | 13.81320 |
December | 497.00000 | 27.00000 | 19.01211 | 0.52080 | 10.93325 |
Annual Sum or Average | 5943.00000 | 26.90581 | 27.73075 | 0.43265 | 10.33188 |
Minimum of Months | 454.00000 | 25.88184 | 16.07895 | 0.11514 | 5.65648 |
Maximum of Months | 514.00000 | 27.00087 | 37.10074 | 0.74879 | 17.11262 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99998 | 30.03003 | 1.00731 | 26.44243 |
February | 454.00000 | 27.00015 | 29.84002 | 1.17426 | 34.00928 |
March | 514.00000 | 27.00061 | 27.43604 | 1.32484 | 41.57911 |
April | 485.00000 | 27.00076 | 27.10010 | 1.46975 | 49.26584 |
May | 508.00000 | 27.00001 | 32.39818 | 0.49241 | 10.13818 |
June | 496.00000 | 27.00142 | 40.00599 | 0.81117 | 19.05475 |
July | 497.00000 | 27.05122 | 44.35945 | 1.08221 | 29.83389 |
August | 514.00000 | 27.34419 | 38.37627 | 1.31333 | 40.98524 |
September | 485.00000 | 27.00006 | 39.51722 | 0.61855 | 13.22674 |
October | 502.00000 | 27.00015 | 31.39233 | 1.25827 | 38.15778 |
November | 489.00000 | 27.00047 | 28.77258 | 1.36813 | 43.82918 |
December | 497.00000 | 27.00020 | 24.30870 | 1.43656 | 47.47665 |
Annual Sum or Average | 5943.00000 | 27.03437 | 32.81464 | 1.11267 | 32.82410 |
Minimum of Months | 454.00000 | 26.99998 | 24.30870 | 0.49241 | 10.13818 |
Maximum of Months | 514.00000 | 27.34419 | 44.35945 | 1.46975 | 49.26584 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.48099 | 18.52782 | 0.30049 | 7.54277 |
February | 454.00000 | 24.47634 | 16.77973 | 0.28911 | 7.02513 |
March | 514.00000 | 24.47353 | 23.22579 | 0.35388 | 8.02688 |
April | 485.00000 | 24.60293 | 26.68679 | 0.41522 | 9.12285 |
May | 508.00000 | 24.62862 | 31.97404 | -0.3865 | 9.25247 |
June | 496.00000 | 25.52503 | 49.65796 | 0.04337 | 12.91172 |
July | 497.00000 | 26.70650 | 66.34418 | 0.55882 | 23.31034 |
August | 514.00000 | 25.85545 | 56.89048 | 0.22696 | 16.05365 |
September | 485.00000 | 25.26812 | 47.31335 | -0.0472 | 10.61760 |
October | 502.00000 | 24.73375 | 31.89514 | 0.49456 | 10.87435 |
November | 489.00000 | 24.71035 | 25.30481 | 0.43709 | 9.71618 |
December | 497.00000 | 24.61449 | 19.37353 | 0.35584 | 8.13550 |
Annual Sum or Average | 5943.00000 | 25.01031 | 34.63723 | 0.25255 | 11.08373 |
Minimum of Months | 454.00000 | 24.47353 | 16.77973 | -0.3865 | 7.02513 |
Maximum of Months | 514.00000 | 26.70650 | 66.34418 | 0.55882 | 23.31034 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.86872 | 23.01799 | 0.18397 | 6.18896 |
February | 454.00000 | 23.99952 | 20.58171 | 0.20379 | 6.10383 |
March | 514.00000 | 24.21490 | 24.99948 | 0.31936 | 7.46672 |
April | 485.00000 | 24.31716 | 27.77508 | 0.38294 | 8.32910 |
May | 508.00000 | 24.26766 | 33.79166 | -0.4579 | 9.92724 |
June | 496.00000 | 24.26011 | 45.07581 | -0.3377 | 7.85797 |
July | 497.00000 | 24.32860 | 53.11551 | -0.2304 | 6.58527 |
August | 514.00000 | 24.24987 | 50.13204 | -0.2783 | 6.94294 |
September | 485.00000 | 24.33900 | 45.36865 | -0.3315 | 7.96323 |
October | 502.00000 | 24.36806 | 33.91778 | 0.42784 | 9.15113 |
November | 489.00000 | 24.39300 | 27.57437 | 0.38043 | 8.36213 |
December | 497.00000 | 24.26348 | 22.19915 | 0.29233 | 7.05099 |
Annual Sum or Average | 5943.00000 | 24.24015 | 34.06650 | 0.04415 | 7.67072 |
Minimum of Months | 454.00000 | 23.86872 | 20.58171 | -0.4579 | 6.10383 |
Maximum of Months | 514.00000 | 24.39300 | 53.11551 | 0.42784 | 9.92724 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.02658 | 24.40280 | -0.2917 | 8.41229 |
February | 454.00000 | 22.29159 | 24.10260 | -0.2255 | 6.94196 |
March | 514.00000 | 23.36922 | 28.03267 | 0.08888 | 6.17212 |
April | 485.00000 | 23.77829 | 30.27630 | 0.21919 | 6.35452 |
May | 508.00000 | 24.06639 | 34.52718 | -0.5588 | 12.08206 |
June | 496.00000 | 24.11851 | 46.11252 | -0.4337 | 9.33049 |
July | 497.00000 | 24.20223 | 54.83167 | -0.3395 | 7.69487 |
August | 514.00000 | 24.17947 | 51.51216 | -0.3688 | 8.10070 |
September | 485.00000 | 24.12485 | 46.54920 | -0.4449 | 9.67112 |
October | 502.00000 | 23.83790 | 36.13877 | 0.27284 | 6.92022 |
November | 489.00000 | 23.52404 | 31.15888 | 0.14182 | 5.93636 |
December | 497.00000 | 22.42565 | 26.75890 | -0.1718 | 6.68482 |
Annual Sum or Average | 5943.00000 | 23.50382 | 36.29138 | -0.1765 | 7.87017 |
Minimum of Months | 454.00000 | 22.02658 | 24.10260 | -0.5588 | 5.93636 |
Maximum of Months | 514.00000 | 24.20223 | 54.83167 | 0.27284 | 12.08206 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.79087 | 26.27361 | -0.6114 | 15.48534 |
February | 454.00000 | 21.00145 | 25.53436 | -0.5587 | 14.16968 |
March | 514.00000 | 22.15639 | 30.17170 | -0.2158 | 8.96772 |
April | 485.00000 | 22.92692 | 32.26712 | 0.00536 | 6.60931 |
May | 508.00000 | 23.78618 | 35.35428 | -0.6621 | 15.31253 |
June | 496.00000 | 24.06002 | 46.36501 | -0.4452 | 9.78413 |
July | 497.00000 | 24.22056 | 54.64615 | -0.3210 | 7.48329 |
August | 514.00000 | 24.15116 | 51.46337 | -0.3741 | 8.22485 |
September | 485.00000 | 23.84905 | 47.60130 | -0.5453 | 12.42871 |
October | 502.00000 | 22.80949 | 39.10877 | 0.01588 | 6.86885 |
November | 489.00000 | 22.02751 | 34.92368 | -0.2283 | 7.66724 |
December | 497.00000 | 20.94710 | 29.10501 | -0.5495 | 13.64615 |
Annual Sum or Average | 5943.00000 | 22.74060 | 37.82100 | -0.3734 | 10.53467 |
Minimum of Months | 454.00000 | 20.79087 | 25.53436 | -0.6621 | 6.60931 |
Maximum of Months | 514.00000 | 24.22056 | 54.64615 | 0.01588 | 15.48534 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.21175 | 22.31423 | -0.4933 | 10.88339 |
February | 454.00000 | 21.48257 | 21.84461 | -0.4237 | 9.66028 |
March | 514.00000 | 22.69694 | 26.27794 | -0.0763 | 7.32227 |
April | 485.00000 | 23.62269 | 28.35500 | 0.17682 | 6.39932 |
May | 508.00000 | 24.00743 | 33.75251 | -0.5707 | 12.88126 |
June | 496.00000 | 24.28651 | 44.37663 | -0.3188 | 7.96295 |
July | 497.00000 | 24.44599 | 52.22061 | -0.1666 | 6.64778 |
August | 514.00000 | 24.28647 | 49.42837 | -0.2635 | 7.18813 |
September | 485.00000 | 24.10896 | 45.37405 | -0.4405 | 10.14795 |
October | 502.00000 | 23.53503 | 34.80497 | 0.18944 | 6.60465 |
November | 489.00000 | 23.05821 | 28.97474 | 0.01840 | 5.96759 |
December | 497.00000 | 21.79944 | 23.95816 | -0.3262 | 8.25892 |
Annual Sum or Average | 5943.00000 | 23.22339 | 34.40174 | -0.2240 | 8.32385 |
Minimum of Months | 454.00000 | 21.21175 | 21.84461 | -0.5707 | 5.96759 |
Maximum of Months | 514.00000 | 24.44599 | 52.22061 | 0.18944 | 12.88126 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.16533 | 21.57625 | -0.4963 | 10.84654 |
February | 454.00000 | 21.41886 | 21.12367 | -0.4274 | 9.89302 |
March | 514.00000 | 22.53252 | 25.92934 | -0.0812 | 7.31340 |
April | 485.00000 | 23.31180 | 28.32516 | 0.15971 | 7.05595 |
May | 508.00000 | 23.90813 | 33.51628 | -0.5110 | 13.00341 |
June | 496.00000 | 24.24296 | 44.26123 | -0.2487 | 8.07654 |
July | 497.00000 | 24.39261 | 52.18124 | -0.1019 | 6.96588 |
August | 514.00000 | 24.15035 | 49.66032 | -0.2374 | 7.55945 |
September | 485.00000 | 24.01857 | 45.27531 | -0.3869 | 10.55974 |
October | 502.00000 | 23.25553 | 34.77673 | 0.16193 | 7.13344 |
November | 489.00000 | 22.43577 | 29.14445 | -0.1025 | 6.58493 |
December | 497.00000 | 21.29132 | 23.86620 | -0.4400 | 9.73183 |
Annual Sum or Average | 5943.00000 | 23.02196 | 34.23451 | -0.2252 | 8.72221 |
Minimum of Months | 454.00000 | 21.16533 | 21.12367 | -0.5110 | 6.58493 |
Maximum of Months | 514.00000 | 24.39261 | 52.18124 | 0.16193 | 13.00341 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.57804 | 21.50600 | -0.3977 | 11.01062 |
February | 454.00000 | 21.79686 | 20.93435 | -0.3358 | 9.90167 |
March | 514.00000 | 23.00942 | 25.32289 | 0.04057 | 7.86108 |
April | 485.00000 | 23.51288 | 28.07071 | 0.19467 | 7.56744 |
May | 508.00000 | 23.93289 | 33.61181 | -0.5442 | 13.51808 |
June | 496.00000 | 24.23881 | 44.38381 | -0.3018 | 8.39747 |
July | 497.00000 | 24.43590 | 52.11172 | -0.1277 | 6.90911 |
August | 514.00000 | 24.30059 | 49.19068 | -0.1903 | 7.16961 |
September | 485.00000 | 24.21229 | 44.74722 | -0.3052 | 9.48572 |
October | 502.00000 | 23.59923 | 34.02452 | 0.26105 | 8.51985 |
November | 489.00000 | 22.91535 | 28.58425 | 0.01345 | 7.19169 |
December | 497.00000 | 21.81363 | 23.63783 | -0.3178 | 9.33708 |
Annual Sum or Average | 5943.00000 | 23.28972 | 33.94104 | -0.1670 | 8.90453 |
Minimum of Months | 454.00000 | 21.57804 | 20.93435 | -0.5442 | 6.90911 |
Maximum of Months | 514.00000 | 24.43590 | 52.11172 | 0.26105 | 13.51808 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.50071 | 20.92083 | -0.3906 | 9.07124 |
February | 454.00000 | 22.16986 | 19.99007 | -0.2170 | 7.30523 |
March | 514.00000 | 23.65488 | 23.95280 | 0.22436 | 7.87140 |
April | 485.00000 | 24.36327 | 26.25923 | 0.46328 | 10.58114 |
May | 508.00000 | 24.20092 | 32.85759 | -0.3739 | 10.35706 |
June | 496.00000 | 24.46363 | 43.61427 | -0.0936 | 7.14963 |
July | 497.00000 | 24.59207 | 51.48619 | 0.05066 | 7.17448 |
August | 514.00000 | 24.48635 | 48.49127 | 0.00259 | 6.82985 |
September | 485.00000 | 24.27123 | 44.51331 | -0.2693 | 8.60698 |
October | 502.00000 | 23.96501 | 33.06432 | 0.35888 | 8.74079 |
November | 489.00000 | 23.81017 | 26.67886 | 0.24856 | 7.26440 |
December | 497.00000 | 23.04932 | 21.39933 | 0.00998 | 6.20480 |
Annual Sum or Average | 5943.00000 | 23.72038 | 32.86747 | 0.00194 | 8.09865 |
Minimum of Months | 454.00000 | 21.50071 | 19.99007 | -0.3906 | 6.20480 |
Maximum of Months | 514.00000 | 24.59207 | 51.48619 | 0.46328 | 10.58114 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.09912 | 24.05928 | -0.8498 | 22.31164 |
February | 454.00000 | 20.22763 | 23.91502 | -0.8021 | 20.38245 |
March | 514.00000 | 21.31071 | 29.17275 | -0.4402 | 12.36848 |
April | 485.00000 | 22.24197 | 31.45420 | -0.1663 | 7.43649 |
May | 508.00000 | 23.55227 | 35.18231 | -0.7456 | 18.49052 |
June | 496.00000 | 24.10798 | 45.55055 | -0.4167 | 9.62152 |
July | 497.00000 | 24.35217 | 54.02252 | -0.2499 | 7.09659 |
August | 514.00000 | 24.14468 | 50.89051 | -0.3657 | 8.57393 |
September | 485.00000 | 23.64278 | 47.25641 | -0.6257 | 15.11414 |
October | 502.00000 | 22.18844 | 37.99561 | -0.1403 | 7.31536 |
November | 489.00000 | 21.17302 | 32.78515 | -0.4463 | 10.36870 |
December | 497.00000 | 20.22818 | 27.11087 | -0.7797 | 19.77341 |
Annual Sum or Average | 5943.00000 | 22.28875 | 36.70824 | -0.5006 | 13.19502 |
Minimum of Months | 454.00000 | 20.09912 | 23.91502 | -0.8498 | 7.09659 |
Maximum of Months | 514.00000 | 24.35217 | 54.02252 | -0.1403 | 22.31164 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.06183 | 22.88915 | -0.8481 | 22.16627 |
February | 385.00000 | 20.24753 | 22.66922 | -0.7816 | 19.78598 |
March | 433.00000 | 21.44933 | 27.88451 | -0.3755 | 10.72985 |
April | 410.00000 | 22.42233 | 30.01551 | -0.0745 | 7.97040 |
May | 430.00000 | 23.53852 | 34.23812 | -0.6587 | 18.16566 |
June | 418.00000 | 24.13206 | 44.99406 | -0.3175 | 9.87154 |
July | 422.00000 | 24.45762 | 53.33276 | -0.1262 | 7.73813 |
August | 433.00000 | 24.12360 | 50.42035 | -0.2901 | 8.98905 |
September | 410.00000 | 23.63376 | 46.64781 | -0.5476 | 15.16833 |
October | 427.00000 | 22.20953 | 36.73063 | -0.1061 | 7.55969 |
November | 417.00000 | 21.13053 | 31.41371 | -0.4498 | 10.53200 |
December | 422.00000 | 20.15383 | 25.92945 | -0.7964 | 20.16707 |
Annual Sum or Average | 5034.00000 | 22.30979 | 35.67766 | -0.4459 | 13.19848 |
Minimum of Months | 385.00000 | 20.06183 | 22.66922 | -0.8481 | 7.55969 |
Maximum of Months | 433.00000 | 24.45762 | 53.33276 | -0.0745 | 22.16627 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.88252 | 22.80217 | -0.6061 | 16.78593 |
February | 454.00000 | 20.99793 | 22.55749 | -0.5570 | 15.30411 |
March | 514.00000 | 22.39552 | 27.19133 | -0.1155 | 9.36923 |
April | 485.00000 | 22.85196 | 29.69633 | 0.02781 | 8.02477 |
May | 508.00000 | 23.65410 | 34.41945 | -0.6459 | 16.99003 |
June | 496.00000 | 24.07094 | 45.37728 | -0.3826 | 10.07208 |
July | 497.00000 | 24.38156 | 53.63981 | -0.1851 | 7.47394 |
August | 514.00000 | 24.22362 | 50.27231 | -0.2537 | 8.16276 |
September | 485.00000 | 24.01526 | 45.63372 | -0.3804 | 11.59184 |
October | 502.00000 | 23.10601 | 35.35446 | 0.14027 | 8.73399 |
November | 489.00000 | 22.07952 | 30.72403 | -0.1954 | 8.95990 |
December | 497.00000 | 20.87367 | 25.99575 | -0.5851 | 15.19895 |
Annual Sum or Average | 5943.00000 | 22.80874 | 35.40001 | -0.3102 | 11.36818 |
Minimum of Months | 454.00000 | 20.87367 | 22.55749 | -0.6459 | 7.47394 |
Maximum of Months | 514.00000 | 24.38156 | 53.63981 | 0.14027 | 16.99003 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.28351 | 23.00548 | -0.7797 | 19.77955 |
February | 454.00000 | 20.52130 | 22.74238 | -0.6986 | 17.16977 |
March | 514.00000 | 21.74156 | 27.76286 | -0.2879 | 9.97138 |
April | 485.00000 | 22.54287 | 29.97911 | -0.0331 | 7.92581 |
May | 508.00000 | 23.56785 | 34.46681 | -0.6284 | 17.45395 |
June | 496.00000 | 24.12925 | 45.07863 | -0.2800 | 9.46397 |
July | 497.00000 | 24.41317 | 53.43736 | -0.1138 | 7.45565 |
August | 514.00000 | 24.19963 | 50.32172 | -0.2270 | 8.28931 |
September | 485.00000 | 23.64788 | 46.68522 | -0.5263 | 14.47134 |
October | 502.00000 | 22.25722 | 36.88753 | -0.0797 | 7.33304 |
November | 489.00000 | 21.32369 | 31.64616 | -0.3843 | 9.34878 |
December | 497.00000 | 20.43609 | 26.04116 | -0.7040 | 16.89442 |
Annual Sum or Average | 5943.00000 | 22.43755 | 35.76526 | -0.3932 | 12.09633 |
Minimum of Months | 454.00000 | 20.28351 | 22.74238 | -0.7797 | 7.33304 |
Maximum of Months | 514.00000 | 24.41317 | 53.43736 | -0.0331 | 19.77955 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.83841 | 25.37762 | -0.9606 | 27.06059 |
February | 454.00000 | 19.89367 | 24.96111 | -0.9298 | 25.92944 |
March | 514.00000 | 20.81575 | 30.38739 | -0.5950 | 16.83984 |
April | 485.00000 | 21.60979 | 32.82981 | -0.3345 | 10.15521 |
May | 508.00000 | 23.18517 | 36.07598 | -0.8733 | 23.88468 |
June | 496.00000 | 24.01168 | 45.90523 | -0.4428 | 10.85510 |
July | 497.00000 | 24.33680 | 54.04935 | -0.2445 | 7.35615 |
August | 514.00000 | 24.07126 | 51.01491 | -0.3862 | 9.38630 |
September | 485.00000 | 23.29604 | 48.36022 | -0.7463 | 19.96949 |
October | 502.00000 | 21.42235 | 39.91930 | -0.3427 | 10.79330 |
November | 489.00000 | 20.48869 | 34.57448 | -0.6525 | 16.17075 |
December | 497.00000 | 19.84540 | 28.62061 | -0.9236 | 25.84106 |
Annual Sum or Average | 5943.00000 | 21.91844 | 37.76188 | -0.6172 | 16.95935 |
Minimum of Months | 454.00000 | 19.83841 | 24.96111 | -0.9606 | 7.35615 |
Maximum of Months | 514.00000 | 24.33680 | 54.04935 | -0.2445 | 27.06059 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.91550 | 24.66048 | -0.9232 | 25.54729 |
February | 454.00000 | 20.00519 | 24.23534 | -0.8745 | 24.05098 |
March | 514.00000 | 21.07344 | 29.35661 | -0.4878 | 14.26178 |
April | 485.00000 | 22.09360 | 31.22767 | -0.1644 | 9.57904 |
May | 508.00000 | 23.38753 | 34.87060 | -0.7020 | 19.90341 |
June | 496.00000 | 24.06863 | 45.26395 | -0.3109 | 9.92191 |
July | 497.00000 | 24.38448 | 53.38793 | -0.1137 | 7.57703 |
August | 514.00000 | 24.06291 | 50.55680 | -0.2805 | 9.05369 |
September | 485.00000 | 23.44832 | 47.28669 | -0.5995 | 17.03067 |
October | 502.00000 | 21.72261 | 38.47239 | -0.2379 | 9.63661 |
November | 489.00000 | 20.62491 | 33.54399 | -0.6073 | 14.89845 |
December | 497.00000 | 19.91566 | 27.97189 | -0.9004 | 24.78036 |
Annual Sum or Average | 5943.00000 | 22.07543 | 36.82560 | -0.5144 | 15.45860 |
Minimum of Months | 454.00000 | 19.91550 | 24.23534 | -0.9232 | 7.57703 |
Maximum of Months | 514.00000 | 24.38448 | 53.38793 | -0.1137 | 25.54729 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.41718 | 24.30966 | -0.7567 | 21.61046 |
February | 454.00000 | 20.46188 | 23.86440 | -0.7223 | 21.18507 |
March | 514.00000 | 21.78900 | 28.51772 | -0.2908 | 12.32690 |
April | 485.00000 | 22.28074 | 31.01160 | -0.1273 | 9.72426 |
May | 508.00000 | 23.32174 | 35.22992 | -0.7634 | 21.82054 |
June | 496.00000 | 23.93872 | 45.83213 | -0.4181 | 11.66858 |
July | 497.00000 | 24.32364 | 53.80065 | -0.1914 | 7.98717 |
August | 514.00000 | 24.12873 | 50.45612 | -0.2795 | 9.08950 |
September | 485.00000 | 23.73102 | 46.54146 | -0.4822 | 14.99565 |
October | 502.00000 | 22.43168 | 37.04531 | -0.0424 | 9.99856 |
November | 489.00000 | 21.33792 | 32.56848 | -0.4103 | 12.56840 |
December | 497.00000 | 20.32576 | 27.68572 | -0.7615 | 20.93927 |
Annual Sum or Average | 5943.00000 | 22.38992 | 36.49582 | -0.4353 | 14.45024 |
Minimum of Months | 454.00000 | 20.32576 | 23.86440 | -0.7634 | 7.98717 |
Maximum of Months | 514.00000 | 24.32364 | 53.80065 | -0.0424 | 21.82054 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.99685 | 24.45683 | -0.8909 | 24.35889 |
February | 454.00000 | 20.15650 | 23.92011 | -0.8205 | 22.16288 |
March | 514.00000 | 21.31142 | 28.87112 | -0.4203 | 12.92959 |
April | 485.00000 | 22.05650 | 31.14392 | -0.1656 | 9.51233 |
May | 508.00000 | 23.23628 | 35.22318 | -0.7421 | 22.12061 |
June | 496.00000 | 24.00544 | 45.49877 | -0.3125 | 10.88336 |
July | 497.00000 | 24.35112 | 53.61660 | -0.1217 | 7.95618 |
August | 514.00000 | 24.09792 | 50.51784 | -0.2545 | 9.21427 |
September | 485.00000 | 23.32772 | 47.64575 | -0.6351 | 18.53905 |
October | 502.00000 | 21.69576 | 38.36121 | -0.2334 | 9.37230 |
November | 489.00000 | 20.81198 | 33.10048 | -0.5437 | 13.17678 |
December | 497.00000 | 20.04558 | 27.67907 | -0.8368 | 22.32578 |
Annual Sum or Average | 5943.00000 | 22.10760 | 36.75991 | -0.4958 | 15.16252 |
Minimum of Months | 454.00000 | 19.99685 | 23.92011 | -0.8909 | 7.95618 |
Maximum of Months | 514.00000 | 24.35112 | 53.61660 | -0.1217 | 24.35889 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 49535026.71 | 727.38 | 11-JAN-07:30 | 32.97 | 0.483081E+09 | 0.00 | 0.532616E+09 | 0.43 | 9.83 | 19-JAN-09:50 | 0.00 | 0.00 |
February | 41407436.76 | 861.32 | 22-FEB-17:00 | 26.24 | 0.403921E+09 | 0.00 | 0.445328E+09 | 0.38 | 9.83 | 09-FEB-13:30 | 0.00 | 0.00 |
March | 0.719828E+10 | 185462.69 | 15-MAR-14:00 | 72.71 | 0.611500E+11 | 0.00 | 0.683483E+11 | 0.93 | 10.00 | 15-MAR-18:00 | 0.00 | 0.00 |
April | 0.256267E+10 | 49665.68 | 07-APR-14:00 | 91.86 | 0.250431E+11 | 0.00 | 0.276058E+11 | 1.24 | 10.00 | 07-APR-13:20 | 0.00 | 0.00 |
May | 0.231568E+11 | 200933.55 | 10-MAY-14:30 | 256.08 | 0.217074E+12 | 0.00 | 0.240231E+12 | 3.33 | 10.00 | 31-MAY-17:30 | 0.00 | 0.00 |
June | 0.873184E+11 | 203333.40 | 27-JUN-16:50 | 441.21 | 0.762598E+12 | 0.00 | 0.849916E+12 | 5.71 | 10.01 | 02-JUN-04:11 | 0.00 | 0.00 |
July | 0.140083E+12 | 212481.90 | 20-JUL-05:02 | 580.17 | 0.118135E+13 | 0.00 | 0.132143E+13 | 7.02 | 10.02 | 26-JUL-04:11 | 0.00 | 0.00 |
August | 0.123824E+12 | 208265.73 | 15-AUG-05:03 | 567.26 | 0.105483E+13 | 0.00 | 0.117866E+13 | 6.98 | 10.00 | 16-AUG-04:13 | 0.00 | 0.00 |
September | 0.568865E+11 | 198983.63 | 25-SEP-10:30 | 347.58 | 0.506371E+12 | 0.00 | 0.563257E+12 | 4.56 | 10.00 | 09-SEP-05:03 | 0.00 | 0.00 |
October | 0.761662E+10 | 96113.61 | 11-OCT-15:00 | 115.53 | 0.734598E+11 | 0.00 | 0.810764E+11 | 1.51 | 9.99 | 11-OCT-17:00 | 0.00 | 0.00 |
November | 0.101306E+10 | 25987.18 | 16-NOV-13:10 | 43.99 | 0.985069E+10 | 0.00 | 0.108637E+11 | 0.60 | 9.84 | 24-NOV-07:40 | 0.00 | 0.00 |
December | 49302127.69 | 3347.79 | 01-DEC-07:13 | 32.80 | 0.480877E+09 | 0.00 | 0.530179E+09 | 0.43 | 9.83 | 29-DEC-12:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.449800E+12 | 2608.41 | 0.389309E+13 | 0.00 | 0.434289E+13 | 2.78 | 0.00 | 0.00 | ||||
Minimum of Months | 41407436.76 | 727.38 | 26.24 | 0.403921E+09 | 0.00 | 0.445328E+09 | 0.38 | 9.83 | 0.00 | 0.00 | ||
Maximum of Months | 0.140083E+12 | 212481.90 | 580.17 | 0.118135E+13 | 0.00 | 0.132143E+13 | 7.02 | 10.02 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 92844214.37 | 80605.63 | 10-MAY-14:50 | 0.33 | 0.848235E+09 | 0.00 | 0.941079E+09 | 0.00 | 9.17 | 10-MAY-14:40 | 0.00 | 0.00 |
June | 0.151257E+11 | 148256.90 | 27-JUN-07:40 | 50.92 | 0.133690E+12 | 0.00 | 0.148816E+12 | 0.63 | 10.58 | 01-JUN-15:00 | 0.00 | 0.00 |
July | 0.396198E+11 | 212481.90 | 20-JUL-05:02 | 120.62 | 0.336384E+12 | 0.00 | 0.376004E+12 | 1.40 | 10.32 | 13-JUL-12:30 | 0.00 | 0.00 |
August | 0.266993E+11 | 208265.73 | 15-AUG-05:03 | 82.87 | 0.228144E+12 | 0.00 | 0.254843E+12 | 0.97 | 10.65 | 02-AUG-14:10 | 0.00 | 0.00 |
September | 0.695035E+10 | 151550.78 | 21-SEP-13:07 | 23.00 | 0.612069E+11 | 0.00 | 0.681573E+11 | 0.28 | 10.58 | 20-SEP-15:10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.884880E+11 | 277.74 | 0.760273E+12 | 0.00 | 0.848761E+12 | 0.28 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.396198E+11 | 212481.90 | 120.62 | 0.336384E+12 | 0.00 | 0.376004E+12 | 1.40 | 10.65 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.417653E+09 | 744.00 | 686.85 | 11-JAN-16:00 | 31395.84 | 12-JAN-16:40 | 18.55 | 18.33 | 15.97 |
February | 0.121434E+10 | 672.00 | 2278.86 | 22-FEB-18:00 | 67839.77 | 28-FEB-17:00 | 19.09 | 18.33 | 15.97 |
March | 0.927266E+10 | 744.00 | 49248.27 | 12-MAR-13:00 | 506904.52 | 14-MAR-13:10 | 20.18 | 18.56 | 15.97 |
April | 0.118158E+11 | 720.00 | 49248.27 | 07-APR-10:20 | 419163.14 | 08-APR-13:20 | 20.63 | 18.39 | 15.97 |
May | 0.260968E+11 | 744.00 | 49248.27 | 09-MAY-11:50 | 209847.72 | 10-MAY-15:00 | 19.37 | 18.74 | 15.97 |
June | 0.787058E+11 | 720.00 | 49248.27 | 01-JUN-09:50 | 635775.61 | 27-JUN-14:20 | 23.87 | 21.22 | 15.97 |
July | 0.117882E+12 | 744.00 | 49248.27 | 01-JUL-07:00 | 816668.38 | 21-JUL-03:02 | 32.96 | 25.15 | 15.97 |
August | 0.114041E+12 | 744.00 | 49248.27 | 01-AUG-00:03 | 835224.01 | 13-AUG-16:01 | 33.77 | 24.52 | 15.97 |
September | 0.538352E+11 | 720.00 | 49248.27 | 01-SEP-12:50 | 271748.70 | 15-SEP-12:10 | 20.27 | 19.54 | 15.97 |
October | 0.125378E+11 | 744.00 | 49248.27 | 03-OCT-13:10 | 183816.93 | 11-OCT-15:00 | 19.44 | 18.43 | 15.97 |
November | 0.859499E+10 | 720.00 | 49248.27 | 04-NOV-13:50 | 218397.24 | 05-NOV-14:02 | 19.84 | 18.36 | 15.97 |
December | 0.330076E+10 | 744.00 | 7128.66 | 01-DEC-11:00 | 187831.06 | 01-DEC-11:00 | 20.12 | 18.33 | 15.97 |
Annual Sum or Average | 0.437715E+12 | 8760.00 | 22.38 | 19.84 | 15.97 | ||||
Minimum of Months | 0.417653E+09 | 672.00 | 686.85 | 31395.84 | 18.55 | 18.33 | 15.97 | ||
Maximum of Months | 0.117882E+12 | 744.00 | 49248.27 | 835224.01 | 33.77 | 25.15 | 15.97 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 238133.30 | 09-JAN-06:13 | 20.96 | 20.96 | 0.13 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 238168.94 | 28-FEB-09:50 | 20.94 | 20.93 | 0.11 |
March | 0.788972E+09 | 27.56 | 19750.17 | 14-MAR-10:50 | 1409142.92 | 15-MAR-13:30 | 21.04 | 20.95 | 3.36 |
April | 21646376.12 | 18.67 | 965.08 | 08-APR-13:40 | 560304.24 | 07-APR-14:00 | 20.97 | 20.93 | 3.76 |
May | 0.857540E+09 | 152.51 | 19750.17 | 10-MAY-12:10 | 1267397.86 | 10-MAY-16:00 | 21.43 | 21.09 | 18.92 |
June | 0.126927E+11 | 384.83 | 19750.17 | 01-JUN-13:00 | 1402413.29 | 01-JUN-14:50 | 22.86 | 21.68 | 38.99 |
July | 0.269402E+11 | 530.68 | 19750.17 | 01-JUL-14:00 | 1414317.06 | 05-JUL-16:00 | 24.26 | 22.49 | 49.52 |
August | 0.206095E+11 | 484.05 | 19750.17 | 01-AUG-11:50 | 1461876.35 | 16-AUG-13:10 | 23.47 | 21.87 | 47.55 |
September | 0.741145E+10 | 280.22 | 19750.17 | 08-SEP-11:30 | 1361684.92 | 20-SEP-15:50 | 22.35 | 21.56 | 30.46 |
October | 0.177788E+09 | 65.96 | 4004.15 | 11-OCT-15:00 | 959522.84 | 11-OCT-15:00 | 21.17 | 21.05 | 8.15 |
November | 17417057.39 | 13.92 | 560.31 | 16-NOV-17:00 | 292377.52 | 16-NOV-13:10 | 21.02 | 21.00 | 1.96 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 238164.63 | 04-DEC-07:50 | 20.91 | 20.91 | 0.15 |
Annual Sum or Average | 0.695172E+11 | 1958.39 | 21.79 | 21.29 | 17.04 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 238133.30 | 20.91 | 20.91 | 0.11 | ||
Maximum of Months | 0.269402E+11 | 530.68 | 19750.17 | 1461876.35 | 24.26 | 22.49 | 49.52 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 20.96 | 20.96 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 20.94 | 20.94 | 0.00 |
March | 71100600.57 | 1.00 | 19750.17 | 14-MAR-12:50 | 968189.66 | 15-MAR-13:40 | 21.04 | 21.03 | 0.05 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 20.97 | 20.97 | 0.00 |
May | 71100600.57 | 1.00 | 19750.17 | 10-MAY-14:20 | 921062.19 | 10-MAY-14:40 | 21.43 | 21.42 | 0.06 |
June | 0.453993E+10 | 64.00 | 19750.17 | 01-JUN-15:00 | 1203900.59 | 27-JUN-07:40 | 22.86 | 22.55 | 5.30 |
July | 0.114783E+11 | 161.44 | 19750.17 | 03-JUL-12:30 | 1414317.06 | 05-JUL-16:00 | 24.26 | 23.49 | 12.74 |
August | 0.662722E+10 | 93.62 | 19750.17 | 01-AUG-14:50 | 1420107.71 | 15-AUG-14:45 | 23.47 | 23.01 | 7.69 |
September | 0.192801E+10 | 27.12 | 19750.17 | 08-SEP-13:20 | 1185420.35 | 20-SEP-15:20 | 22.35 | 22.22 | 2.32 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 21.17 | 21.17 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.02 | 21.02 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 20.91 | 20.91 | 0.00 |
Annual Sum or Average | 0.247157E+11 | 348.18 | 21.79 | 21.65 | 2.37 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.91 | 20.91 | 0.00 | ||
Maximum of Months | 0.114783E+11 | 161.44 | 19750.17 | 1420107.71 | 24.26 | 23.49 | 12.74 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.322070E+12 | 0.00 | 551.03 | 2161022.68 | 02-JAN-04:01 | 0.00 | 30.59 | 68.38 | 0.64 | 0.00 | 0.05 | 0.81 | 02-JAN-04:01 |
February | 0.251468E+12 | 0.00 | 498.82 | 1700791.47 | 13-FEB-05:01 | 0.00 | 30.32 | 68.33 | 0.56 | 0.00 | 0.04 | 0.64 | 13-FEB-05:01 |
March | 0.916002E+11 | 0.00 | 378.37 | 1661121.65 | 06-MAR-06:01 | 0.00 | 24.73 | 52.86 | 0.17 | 0.00 | 0.01 | 0.62 | 06-MAR-06:01 |
April | 0.187912E+11 | 0.00 | 195.78 | 1125367.52 | 03-APR-05:02 | 0.00 | 23.38 | 39.05 | 0.03 | 0.00 | 0.00 | 0.42 | 03-APR-05:02 |
May | 0.603852E+09 | 0.00 | 38.98 | 104187.33 | 01-MAY-05:02 | 0.00 | 21.56 | 24.71 | 0.00 | 0.00 | 0.00 | 0.04 | 01-MAY-05:02 |
June | 10309221.87 | 0.00 | 2.50 | 2772.39 | 14-JUN-05:10 | 0.00 | 21.05 | 21.26 | 0.00 | 0.00 | 0.00 | 0.00 | 14-JUN-05:10 |
July | 2722.28 | 0.00 | 0.17 | 4.54 | 27-JUL-05:50 | 0.00 | 21.01 | 21.02 | 0.00 | 0.00 | 0.00 | 0.00 | 27-JUL-05:50 |
August | 209751.84 | 0.00 | 0.38 | 243.55 | 31-AUG-05:50 | 0.00 | 21.01 | 21.04 | 0.00 | 0.00 | 0.00 | 0.00 | 31-AUG-05:50 |
September | 0.489621E+09 | 0.00 | 25.39 | 123866.90 | 30-SEP-05:02 | 0.00 | 20.77 | 22.93 | 0.00 | 0.00 | 0.00 | 0.05 | 30-SEP-05:02 |
October | 0.169290E+11 | 0.00 | 183.85 | 1370907.27 | 16-OCT-05:01 | 0.00 | 22.35 | 36.71 | 0.03 | 0.00 | 0.00 | 0.51 | 16-OCT-05:01 |
November | 0.634203E+11 | 0.00 | 349.61 | 1444018.95 | 18-NOV-05:01 | 0.00 | 22.90 | 50.97 | 0.11 | 0.00 | 0.01 | 0.54 | 18-NOV-05:01 |
December | 0.256206E+12 | 0.00 | 525.94 | 1783508.16 | 11-DEC-05:01 | 0.00 | 29.50 | 65.92 | 0.50 | 0.00 | 0.04 | 0.67 | 11-DEC-05:01 |
Annual Sum or Average | 0.102159E+13 | 0.00 | 2750.80 | 0.00 | 24.07 | 40.96 | 0.17 | 0.00 | 0.01 | ||||
Minimum of Months | 2722.28 | 0.00 | 0.17 | 4.54 | 0.00 | 20.77 | 21.02 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.322070E+12 | 0.00 | 551.03 | 2161022.68 | 0.00 | 30.59 | 68.38 | 0.64 | 0.00 | 0.05 | 0.81 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 18.55 | 18.55 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 19.09 | 19.09 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 20.18 | 20.18 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 20.63 | 20.63 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 19.37 | 19.37 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 23.87 | 23.87 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 32.96 | 32.96 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 33.77 | 33.77 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 20.27 | 20.27 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 19.44 | 19.44 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 19.84 | 19.84 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 20.12 | 20.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 22.38 | 22.38 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.55 | 18.55 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.77 | 33.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 8769097.31 | 0.00 | 21.57 | 8769097.31 | 0.00 | 0.00 | 0.00 | 0.00 | 837.51 | 20-JAN-08:50 | 837.51 | 20-JAN-08:50 | 0.00 | 0.00 | 0.00 |
February | 8220567.66 | 0.00 | 14.35 | 8220567.66 | 0.00 | 0.00 | 0.00 | 0.00 | 2498.98 | 21-FEB-13:10 | 2498.98 | 21-FEB-13:10 | 0.00 | 0.00 | 0.00 |
March | 0.610699E+10 | 0.00 | 44.03 | 0.594997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108647.25 | 14-MAR-13:10 | 104814.20 | 15-MAR-14:20 | 0.00 | 0.00 | 0.00 |
April | 0.263212E+10 | 0.00 | 51.16 | 0.263212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54346.80 | 07-APR-14:00 | 54346.80 | 07-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.194026E+11 | 0.00 | 217.86 | 0.191656E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 105257.32 | 14-MAY-13:52 | 93107.09 | 23-MAY-14:30 | 0.00 | 0.00 | 0.00 |
June | 0.894544E+11 | 0.00 | 424.78 | 0.713440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 264369.85 | 27-JUN-07:50 | 134006.75 | 27-JUN-16:00 | 0.00 | 0.00 | 0.00 |
July | 0.167387E+12 | 0.00 | 553.87 | 0.121066E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 299993.96 | 20-JUL-05:02 | 165580.72 | 21-JUL-04:12 | 0.00 | 0.00 | 0.00 |
August | 0.140927E+12 | 0.00 | 544.88 | 0.110160E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 293051.56 | 15-AUG-08:20 | 145956.35 | 08-AUG-16:00 | 0.00 | 0.00 | 0.00 |
September | 0.550567E+11 | 0.00 | 321.52 | 0.436255E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 207989.65 | 14-SEP-04:12 | 112463.58 | 15-SEP-12:30 | 0.00 | 0.00 | 0.00 |
October | 0.732506E+10 | 0.00 | 99.34 | 0.731908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82047.45 | 11-OCT-15:00 | 82047.45 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.118363E+10 | 0.00 | 29.08 | 0.118363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55344.78 | 27-NOV-06:03 | 55344.78 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 |
December | 9810583.93 | 0.00 | 19.04 | 9810583.93 | 0.00 | 0.00 | 0.00 | 0.00 | 2472.16 | 29-DEC-13:10 | 2472.16 | 29-DEC-13:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.489502E+12 | 0.00 | 2341.49 | 0.382473E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 8220567.66 | 0.00 | 14.35 | 8220567.66 | 0.00 | 0.00 | 0.00 | 0.00 | 837.51 | 837.51 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.167387E+12 | 0.00 | 553.87 | 0.121066E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 299993.96 | 165580.72 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 1940318.27 | 0.00 | 15.41 | 1940318.27 | 0.00 | 0.00 | 0.00 | 0.00 | 629.95 | 10-JAN-11:00 | 629.95 | 10-JAN-11:00 | 0.00 | 0.00 | 0.00 |
February | 2555142.24 | 0.00 | 13.34 | 2555142.24 | 0.00 | 0.00 | 0.00 | 0.00 | 632.64 | 24-FEB-09:20 | 632.64 | 24-FEB-09:20 | 0.00 | 0.00 | 0.00 |
March | 0.418203E+11 | 0.00 | 43.64 | 0.407695E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 795489.76 | 15-MAR-14:20 | 795489.76 | 15-MAR-14:20 | 0.00 | 0.00 | 0.00 |
April | 0.171151E+11 | 0.00 | 50.09 | 0.171151E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 374391.07 | 07-APR-14:00 | 374391.07 | 07-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.164502E+12 | 0.00 | 211.76 | 0.162790E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 884519.85 | 10-MAY-14:50 | 837679.28 | 23-MAY-14:30 | 0.00 | 0.00 | 0.00 |
June | 0.677967E+12 | 0.00 | 392.76 | 0.552391E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1824948.83 | 27-JUN-05:03 | 1049964.42 | 12-JUN-15:20 | 0.00 | 0.00 | 0.00 |
July | 0.113901E+13 | 0.00 | 451.23 | 0.854999E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2694563.80 | 20-JUL-05:02 | 1364331.09 | 21-JUL-03:02 | 0.00 | 0.00 | 0.00 |
August | 0.949497E+12 | 0.00 | 435.63 | 0.775263E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2565460.99 | 15-AUG-05:03 | 1161487.15 | 09-AUG-15:30 | 0.00 | 0.00 | 0.00 |
September | 0.426760E+12 | 0.00 | 313.11 | 0.347313E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1576174.26 | 14-SEP-04:12 | 1017762.08 | 21-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.550837E+11 | 0.00 | 98.96 | 0.550577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 655652.35 | 11-OCT-15:00 | 655652.35 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.666324E+10 | 0.00 | 24.59 | 0.666324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 186546.01 | 16-NOV-13:10 | 186546.01 | 16-NOV-13:10 | 0.00 | 0.00 | 0.00 |
December | 3612400.51 | 0.00 | 19.01 | 3612400.51 | 0.00 | 0.00 | 0.00 | 0.00 | 625.12 | 12-DEC-14:10 | 625.12 | 12-DEC-14:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.347843E+13 | 0.00 | 2069.53 | 0.281237E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 1940318.27 | 0.00 | 13.34 | 1940318.27 | 0.00 | 0.00 | 0.00 | 0.00 | 625.12 | 625.12 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.113901E+13 | 0.00 | 451.23 | 0.854999E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2694563.80 | 1364331.09 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 6813845.99 | 0.00 | 13.45 | 6813845.99 | 0.00 | 0.00 | 0.00 | 0.00 | 503.88 | 05-JAN-12:20 | 503.88 | 05-JAN-12:20 | 0.00 | 0.00 | 0.00 |
February | 5549010.19 | 0.00 | 9.78 | 5549010.19 | 0.00 | 0.00 | 0.00 | 0.00 | 728.23 | 17-FEB-11:20 | 728.23 | 17-FEB-11:20 | 0.00 | 0.00 | 0.00 |
March | 0.432231E+10 | 0.00 | 48.95 | 0.431950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96882.47 | 15-MAR-14:20 | 96882.47 | 15-MAR-14:20 | 0.00 | 0.00 | 0.00 |
April | 0.158821E+10 | 0.00 | 50.65 | 0.158821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36544.35 | 07-APR-14:00 | 36544.35 | 07-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.164003E+11 | 0.00 | 208.01 | 0.162754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 102657.23 | 14-MAY-14:02 | 96423.26 | 10-MAY-14:30 | 0.00 | 0.00 | 0.00 |
June | 0.736383E+11 | 0.00 | 388.86 | 0.597074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 303202.15 | 27-JUN-15:00 | 131771.08 | 12-JUN-14:00 | 0.00 | 0.00 | 0.00 |
July | 0.125404E+12 | 0.00 | 449.77 | 0.941735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 290328.39 | 20-JUL-05:02 | 134651.20 | 21-JUL-13:30 | 0.00 | 0.00 | 0.00 |
August | 0.102448E+12 | 0.00 | 429.91 | 0.832417E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 262640.62 | 15-AUG-05:03 | 138600.78 | 09-AUG-15:20 | 0.00 | 0.00 | 0.00 |
September | 0.422136E+11 | 0.00 | 305.98 | 0.342366E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 180286.31 | 15-SEP-12:40 | 118021.97 | 21-SEP-15:50 | 0.00 | 0.00 | 0.00 |
October | 0.471304E+10 | 0.00 | 95.33 | 0.471304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63364.66 | 11-OCT-15:00 | 63364.66 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.600387E+09 | 0.00 | 29.60 | 0.600387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 15330.17 | 16-NOV-13:00 | 15330.17 | 16-NOV-13:00 | 0.00 | 0.00 | 0.00 |
December | 5332230.66 | 0.00 | 18.39 | 5332230.66 | 0.00 | 0.00 | 0.00 | 0.00 | 195.78 | 15-DEC-09:10 | 195.78 | 15-DEC-09:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.371346E+12 | 0.00 | 2048.69 | 0.298874E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 5332230.66 | 0.00 | 9.78 | 5332230.66 | 0.00 | 0.00 | 0.00 | 0.00 | 195.78 | 195.78 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.125404E+12 | 0.00 | 449.77 | 0.941735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 303202.15 | 138600.78 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 44492354.16 | 0.00 | 4.17 | 44492354.16 | 0.00 | 0.00 | 0.00 | 0.00 | 5797.24 | 11-JAN-16:00 | 5797.24 | 11-JAN-16:00 | 0.00 | 0.00 | 0.00 |
February | 41607905.67 | 0.00 | 4.17 | 41607905.67 | 0.00 | 0.00 | 0.00 | 0.00 | 6531.49 | 22-FEB-17:00 | 6531.49 | 22-FEB-17:00 | 0.00 | 0.00 | 0.00 |
March | 0.448173E+10 | 0.00 | 47.35 | 0.383827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67599.62 | 14-MAR-11:00 | 49910.09 | 15-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.241316E+10 | 0.00 | 64.19 | 0.241316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29526.84 | 07-APR-14:00 | 29526.84 | 07-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.131541E+11 | 0.00 | 185.05 | 0.125266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 92945.77 | 24-MAY-06:41 | 57519.57 | 10-MAY-14:00 | 0.00 | 0.00 | 0.00 |
June | 0.308475E+11 | 0.00 | 215.12 | 0.251393E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 135560.50 | 28-JUN-14:20 | 91569.11 | 28-JUN-15:10 | 0.00 | 0.00 | 0.00 |
July | 0.448969E+11 | 0.00 | 179.27 | 0.372942E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 158849.51 | 18-JUL-09:00 | 95651.63 | 31-JUL-12:30 | 0.00 | 0.00 | 0.00 |
August | 0.567412E+11 | 0.00 | 255.98 | 0.466993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 145263.35 | 26-AUG-09:50 | 100427.94 | 09-AUG-14:00 | 0.00 | 0.00 | 0.00 |
September | 0.306227E+11 | 0.00 | 216.37 | 0.248407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 149154.78 | 15-SEP-11:10 | 90912.03 | 15-SEP-12:20 | 0.00 | 0.00 | 0.00 |
October | 0.485575E+10 | 0.00 | 78.63 | 0.465799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78904.57 | 26-OCT-06:14 | 52971.14 | 11-OCT-13:10 | 0.00 | 0.00 | 0.00 |
November | 0.818628E+09 | 0.00 | 17.68 | 0.814456E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 60030.33 | 27-NOV-07:11 | 60030.33 | 27-NOV-07:11 | 0.00 | 0.00 | 0.00 |
December | 3834917.46 | 0.00 | 0.06 | 3623931.72 | 0.00 | 0.00 | 0.00 | 0.00 | 19227.19 | 01-DEC-07:13 | 18143.71 | 01-DEC-07:13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.188922E+12 | 0.00 | 1268.04 | 0.158314E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3834917.46 | 0.00 | 0.06 | 3623931.72 | 0.00 | 0.00 | 0.00 | 0.00 | 5797.24 | 5797.24 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.567412E+11 | 0.00 | 255.98 | 0.466993E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 158849.51 | 100427.94 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.658737E+10 | 0.465368E+10 | 740.25 | 0.658733E+10 | 46765.17 | 0.00 | 0.02 | 13-JAN-18:00 | 0.01 | 11-JAN-18:10 | 3843.46 | 13-JAN-18:00 | 3843.46 | 13-JAN-18:00 | 18.27 | 11-JAN-18:40 | 2122.42 | 13-JAN-18:00 | 0.00 |
February | 0.102941E+11 | 0.549266E+10 | 672.00 | 0.102840E+11 | 10115307.00 | 0.00 | 0.02 | 22-FEB-18:00 | 0.01 | 01-FEB-05:11 | 5069.74 | 15-FEB-00:40 | 5069.74 | 15-FEB-00:40 | 87.39 | 01-FEB-08:00 | 2546.40 | 22-FEB-18:00 | 0.00 |
March | 0.314426E+11 | 0.122868E+11 | 682.57 | 0.283874E+11 | 0.305518E+10 | 0.00 | 0.70 | 14-MAR-13:00 | 0.01 | 13-MAR-04:55 | 314576.80 | 14-MAR-13:00 | 289577.76 | 15-MAR-14:00 | 86498.15 | 14-MAR-11:00 | 94986.99 | 14-MAR-13:00 | 0.00 |
April | 0.361100E+11 | 0.135260E+11 | 688.84 | 0.336622E+11 | 0.244780E+10 | 0.00 | 0.58 | 08-APR-13:00 | 0.01 | 09-APR-08:25 | 233639.85 | 08-APR-14:00 | 227887.93 | 08-APR-13:00 | 33381.93 | 08-APR-17:53 | 70316.04 | 08-APR-13:00 | 0.00 |
May | 0.725831E+10 | 0.515061E+10 | 535.64 | 0.680324E+10 | 0.455072E+09 | 0.00 | 0.30 | 10-MAY-15:00 | 0.01 | 21-MAY-09:22 | 125588.28 | 10-MAY-15:00 | 106052.02 | 10-MAY-15:00 | 19536.26 | 10-MAY-15:00 | 40348.63 | 10-MAY-15:00 | 0.00 |
June | 0.167102E+12 | 0.520588E+11 | 551.17 | 0.118800E+12 | 0.483019E+11 | 0.00 | 0.84 | 27-JUN-14:10 | 0.01 | 24-JUN-05:03 | 434071.22 | 27-JUN-14:10 | 227787.42 | 27-JUN-13:00 | 223943.64 | 27-JUN-15:00 | 121929.27 | 27-JUN-14:10 | 0.00 |
July | 0.711644E+12 | 0.202540E+12 | 694.06 | 0.442713E+12 | 0.268931E+12 | 0.00 | 1.00 | 08-JUL-13:50 | 0.01 | 12-JUL-06:22 | 545825.33 | 20-JUL-22:12 | 334963.82 | 16-JUL-09:21 | 356503.68 | 20-JUL-22:00 | 155016.57 | 21-JUL-02:40 | 0.00 |
August | 0.826267E+12 | 0.233876E+12 | 708.78 | 0.554841E+12 | 0.271426E+12 | 0.00 | 1.00 | 06-AUG-17:42 | 0.01 | 02-AUG-04:53 | 529472.50 | 14-AUG-00:53 | 429750.69 | 10-AUG-12:53 | 327918.57 | 25-AUG-19:00 | 158075.38 | 13-AUG-15:00 | 0.00 |
September | 0.152209E+11 | 0.802671E+10 | 366.30 | 0.113642E+11 | 0.385668E+10 | 0.00 | 0.39 | 15-SEP-12:00 | 0.00 | 18-SEP-09:10 | 179441.56 | 15-SEP-12:00 | 131974.07 | 16-SEP-13:00 | 72085.53 | 15-SEP-12:00 | 53491.42 | 16-SEP-14:30 | 0.00 |
October | 0.854147E+10 | 0.544107E+10 | 579.55 | 0.822276E+10 | 0.318713E+09 | 0.00 | 0.23 | 11-OCT-15:00 | 0.00 | 10-OCT-23:50 | 88604.69 | 11-OCT-15:00 | 82234.33 | 11-OCT-15:00 | 9029.95 | 22-OCT-12:53 | 28066.38 | 11-OCT-15:00 | 0.00 |
November | 0.171312E+11 | 0.774769E+10 | 701.64 | 0.158337E+11 | 0.129745E+10 | 0.00 | 0.27 | 05-NOV-14:00 | 0.01 | 04-NOV-05:00 | 103785.69 | 05-NOV-14:00 | 85014.23 | 05-NOV-14:00 | 19607.15 | 05-NOV-14:30 | 30335.19 | 05-NOV-14:00 | 0.00 |
December | 0.150102E+11 | 0.759881E+10 | 742.56 | 0.146343E+11 | 0.375988E+09 | 0.00 | 0.18 | 01-DEC-11:00 | 0.01 | 01-DEC-07:30 | 66445.31 | 01-DEC-11:00 | 44546.20 | 01-DEC-11:00 | 21899.11 | 01-DEC-11:00 | 19146.96 | 01-DEC-11:00 | 0.00 |
Annual Sum or Average | 0.185261E+13 | 0.558399E+12 | 7663.36 | 0.125213E+13 | 0.600476E+12 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.658737E+10 | 0.465368E+10 | 366.30 | 0.658733E+10 | 46765.17 | 0.00 | 0.02 | 0.00 | 3843.46 | 3843.46 | 18.27 | 2122.42 | 0.00 | ||||||
Maximum of Months | 0.826267E+12 | 0.233876E+12 | 742.56 | 0.554841E+12 | 0.271426E+12 | 0.00 | 1.00 | 0.01 | 545825.33 | 429750.69 | 356503.68 | 158075.38 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.306570E+10 | 0.854306E+09 | 744.00 | 0.306541E+10 | 293963.67 | 0.00 | 0.27 | 15-JAN-16:35 | 0.04 | 30-JAN-07:03 | 2126.38 | 15-JAN-16:35 | 2126.38 | 15-JAN-16:35 | 9.74 | 02-JAN-07:05 | 550.09 | 15-JAN-16:35 | 0.00 |
February | 0.770710E+10 | 0.198803E+10 | 672.00 | 0.770710E+10 | -0.0 | 0.00 | 0.52 | 28-FEB-17:00 | 0.29 | 06-FEB-07:03 | 4275.76 | 28-FEB-17:00 | 4275.76 | 28-FEB-17:00 | 0.00 | 15-FEB-22:20 | 1061.69 | 28-FEB-17:00 | 0.00 |
March | 0.148823E+11 | 0.355832E+10 | 744.00 | 0.148606E+11 | 21722891.11 | 0.00 | 0.81 | 25-MAR-17:53 | 0.57 | 01-MAR-07:03 | 7561.47 | 31-MAR-24:00 | 7561.47 | 31-MAR-24:00 | 267.92 | 16-MAR-15:40 | 1906.83 | 15-MAR-14:10 | 0.00 |
April | 0.198477E+11 | 0.442334E+10 | 720.00 | 0.198449E+11 | 2803663.09 | 0.00 | 0.94 | 02-APR-17:55 | 0.30 | 30-APR-24:00 | 8744.04 | 02-APR-17:55 | 8744.04 | 02-APR-18:00 | 98.40 | 12-APR-16:10 | 2018.82 | 07-APR-14:00 | 0.00 |
May | 0.563968E+10 | 0.142785E+10 | 744.00 | 0.560411E+10 | 35574765.96 | 0.00 | 0.46 | 31-MAY-24:00 | 0.18 | 12-MAY-06:10 | 4054.00 | 31-MAY-24:00 | 4054.00 | 31-MAY-24:00 | 222.73 | 17-MAY-15:20 | 934.82 | 31-MAY-24:00 | 0.00 |
June | 0.109704E+11 | 0.279369E+10 | 720.00 | 0.107882E+11 | 0.182140E+09 | 0.00 | 0.66 | 30-JUN-24:00 | 0.41 | 10-JUN-06:40 | 5957.67 | 30-JUN-24:00 | 5957.67 | 30-JUN-24:00 | 476.71 | 27-JUN-15:00 | 1663.14 | 27-JUN-13:00 | 0.00 |
July | 0.167161E+11 | 0.456079E+10 | 744.00 | 0.164023E+11 | 0.313800E+09 | 0.00 | 0.85 | 31-JUL-23:15 | 0.63 | 07-JUL-06:40 | 7897.95 | 31-JUL-23:55 | 7858.54 | 31-JUL-24:00 | 480.57 | 20-JUL-15:00 | 2376.69 | 21-JUL-14:00 | 0.00 |
August | 0.215668E+11 | 0.560146E+10 | 744.00 | 0.213298E+11 | 0.236916E+09 | 0.00 | 0.99 | 13-AUG-15:55 | 0.29 | 31-AUG-24:00 | 8890.53 | 14-AUG-16:00 | 8806.85 | 04-AUG-18:40 | 474.03 | 14-AUG-10:00 | 2930.00 | 13-AUG-15:21 | 0.00 |
September | 0.578285E+10 | 0.146495E+10 | 720.00 | 0.564988E+10 | 0.132975E+09 | 0.00 | 0.44 | 30-SEP-24:00 | 0.17 | 30-SEP-07:00 | 3778.92 | 30-SEP-24:00 | 3778.92 | 30-SEP-24:00 | 337.47 | 15-SEP-15:30 | 891.62 | 30-SEP-24:00 | 0.00 |
October | 0.103283E+11 | 0.245216E+10 | 744.00 | 0.102978E+11 | 30550024.80 | 0.00 | 0.63 | 31-OCT-24:00 | 0.37 | 17-OCT-06:40 | 5725.17 | 31-OCT-24:00 | 5725.17 | 31-OCT-24:00 | 184.17 | 12-OCT-15:30 | 1283.74 | 31-OCT-24:00 | 0.00 |
November | 0.145532E+11 | 0.337888E+10 | 720.00 | 0.145515E+11 | 1762175.20 | 0.00 | 0.71 | 26-NOV-14:00 | 0.58 | 15-NOV-07:05 | 6158.49 | 15-NOV-16:20 | 6158.49 | 15-NOV-16:20 | 139.78 | 16-NOV-16:20 | 1507.81 | 26-NOV-14:00 | 0.00 |
December | 0.193290E+11 | 0.449078E+10 | 744.00 | 0.193286E+11 | 448048.98 | 0.00 | 0.89 | 04-DEC-16:10 | 0.74 | 11-DEC-07:03 | 7849.76 | 04-DEC-16:10 | 7849.76 | 04-DEC-16:10 | 83.00 | 01-DEC-13:40 | 1796.80 | 04-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.150389E+12 | 0.369945E+11 | 8760.00 | 0.149430E+12 | 0.958986E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.306570E+10 | 0.854306E+09 | 672.00 | 0.306541E+10 | -0.0 | 0.00 | 0.27 | 0.04 | 2126.38 | 2126.38 | 0.00 | 550.09 | 0.00 | ||||||
Maximum of Months | 0.215668E+11 | 0.560146E+10 | 744.00 | 0.213298E+11 | 0.313800E+09 | 0.00 | 0.99 | 0.74 | 8890.53 | 8806.85 | 480.57 | 2930.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.606778E+10 | 0.192531E+10 | 460.25 | 0.606778E+10 | -0.0 | 0.00 | 0.21 | 12-JAN-16:50 | 0.00 | 01-JAN-00:03 | 15233.91 | 12-JAN-16:50 | 15233.91 | 12-JAN-16:50 | 0.00 | 15-JAN-13:48 | 4154.88 | 12-JAN-16:50 | 0.00 |
February | 0.498910E+11 | 0.132863E+11 | 672.00 | 0.498910E+11 | -0.0 | 0.00 | 0.49 | 28-FEB-17:00 | 0.11 | 06-FEB-07:03 | 37607.26 | 28-FEB-17:00 | 37607.26 | 28-FEB-17:00 | 0.00 | 20-FEB-15:20 | 9422.56 | 28-FEB-17:00 | 0.00 |
March | 0.125026E+12 | 0.303296E+11 | 744.00 | 0.124810E+12 | 0.216351E+09 | 0.00 | 0.78 | 25-MAR-17:42 | 0.42 | 06-MAR-07:03 | 66914.47 | 31-MAR-23:40 | 66914.47 | 31-MAR-23:40 | 2638.63 | 16-MAR-15:40 | 18005.90 | 15-MAR-14:10 | 0.00 |
April | 0.178094E+12 | 0.400501E+11 | 720.00 | 0.178064E+12 | 29559171.18 | 0.00 | 0.91 | 22-APR-18:05 | 0.22 | 30-APR-24:00 | 79891.59 | 02-APR-18:00 | 79891.59 | 02-APR-17:55 | 984.34 | 12-APR-16:10 | 19062.19 | 07-APR-14:00 | 0.00 |
May | 0.480971E+11 | 0.122988E+11 | 744.00 | 0.477468E+11 | 0.350356E+09 | 0.00 | 0.45 | 31-MAY-24:00 | 0.12 | 01-MAY-06:05 | 38290.39 | 31-MAY-24:00 | 38290.39 | 31-MAY-24:00 | 2189.67 | 17-MAY-15:20 | 8844.88 | 31-MAY-24:00 | 0.00 |
June | 0.101771E+12 | 0.260286E+11 | 720.00 | 0.999606E+11 | 0.181019E+10 | 0.00 | 0.66 | 30-JUN-24:00 | 0.37 | 14-JUN-06:05 | 56898.13 | 30-JUN-24:00 | 56898.13 | 30-JUN-24:00 | 4729.55 | 27-JUN-15:00 | 15773.56 | 27-JUN-13:00 | 0.00 |
July | 0.157714E+12 | 0.431334E+11 | 744.00 | 0.154590E+12 | 0.312364E+10 | 0.00 | 0.85 | 31-JUL-23:15 | 0.60 | 06-JUL-06:30 | 75836.48 | 31-JUL-23:55 | 75452.12 | 31-JUL-24:00 | 4790.22 | 20-JUL-15:00 | 22420.83 | 19-JUL-15:00 | 0.00 |
August | 0.203873E+12 | 0.530785E+11 | 744.00 | 0.201510E+12 | 0.236259E+10 | 0.00 | 0.98 | 04-AUG-18:40 | 0.23 | 31-AUG-24:00 | 84489.21 | 04-AUG-18:40 | 84489.21 | 04-AUG-18:40 | 4721.58 | 14-AUG-10:00 | 27422.23 | 10-AUG-14:10 | 0.00 |
September | 0.493376E+11 | 0.126369E+11 | 720.00 | 0.480348E+11 | 0.130284E+10 | 0.00 | 0.39 | 30-SEP-24:00 | 0.12 | 30-SEP-07:00 | 32130.58 | 30-SEP-24:00 | 32130.58 | 30-SEP-24:00 | 3331.41 | 15-SEP-15:30 | 8374.90 | 21-SEP-17:00 | 0.00 |
October | 0.854001E+11 | 0.205472E+11 | 744.00 | 0.850951E+11 | 0.305025E+09 | 0.00 | 0.58 | 31-OCT-23:50 | 0.27 | 30-OCT-06:05 | 49967.88 | 31-OCT-23:50 | 49967.88 | 31-OCT-23:50 | 1832.60 | 12-OCT-15:30 | 11937.00 | 11-OCT-17:00 | 0.00 |
November | 0.120220E+12 | 0.283794E+11 | 720.00 | 0.120201E+12 | 19510316.81 | 0.00 | 0.66 | 15-NOV-16:20 | 0.46 | 24-NOV-07:03 | 56756.59 | 15-NOV-16:20 | 56756.59 | 15-NOV-16:20 | 1390.99 | 16-NOV-16:20 | 12954.94 | 15-NOV-16:20 | 0.00 |
December | 0.155618E+12 | 0.369744E+11 | 744.00 | 0.155613E+12 | 5240615.13 | 0.00 | 0.83 | 04-DEC-16:20 | 0.57 | 11-DEC-07:03 | 69957.26 | 04-DEC-16:20 | 69957.26 | 04-DEC-16:20 | 869.70 | 01-DEC-13:30 | 16187.85 | 04-DEC-16:20 | 0.00 |
Annual Sum or Average | 0.128111E+13 | 0.318668E+12 | 8476.25 | 0.127158E+13 | 0.952531E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.606778E+10 | 0.192531E+10 | 460.25 | 0.606778E+10 | -0.0 | 0.00 | 0.21 | 0.00 | 15233.91 | 15233.91 | 0.00 | 4154.88 | 0.00 | ||||||
Maximum of Months | 0.203873E+12 | 0.530785E+11 | 744.00 | 0.201510E+12 | 0.312364E+10 | 0.00 | 0.98 | 0.60 | 84489.21 | 84489.21 | 4790.22 | 27422.23 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.147746E+09 | 47931255.05 | 128.56 | 0.147746E+09 | 0.00 | 0.00 | 0.19 | 12-JAN-16:40 | 0.00 | 01-JAN-00:03 | 1320.07 | 12-JAN-16:40 | 1320.07 | 12-JAN-16:40 | 0.00 | 20-JAN-22:45 | 365.17 | 12-JAN-16:40 | 0.00 |
February | 0.340997E+10 | 0.928499E+09 | 647.03 | 0.340997E+10 | -0.0 | 0.00 | 0.47 | 28-FEB-17:00 | 0.00 | 05-FEB-19:45 | 3719.55 | 28-FEB-17:00 | 3719.55 | 28-FEB-17:00 | 0.00 | 10-FEB-07:10 | 934.40 | 28-FEB-17:00 | 0.00 |
March | 0.110103E+11 | 0.270458E+10 | 744.00 | 0.109888E+11 | 21522564.65 | 0.00 | 0.73 | 25-MAR-17:53 | 0.26 | 06-MAR-04:12 | 6288.36 | 31-MAR-23:20 | 6288.36 | 31-MAR-23:20 | 263.91 | 16-MAR-15:40 | 1823.52 | 15-MAR-14:10 | 0.00 |
April | 0.167924E+11 | 0.380988E+10 | 720.00 | 0.167895E+11 | 2890959.97 | 0.00 | 0.90 | 22-APR-18:15 | 0.15 | 30-APR-24:00 | 7966.24 | 24-APR-18:00 | 7966.24 | 24-APR-18:00 | 97.62 | 12-APR-16:10 | 1916.43 | 07-APR-14:00 | 0.00 |
May | 0.435485E+10 | 0.112379E+10 | 743.86 | 0.432020E+10 | 34652893.07 | 0.00 | 0.44 | 31-MAY-23:40 | 0.00 | 01-MAY-05:55 | 3738.30 | 31-MAY-23:40 | 3738.30 | 31-MAY-23:40 | 218.57 | 17-MAY-15:20 | 866.81 | 31-MAY-23:40 | 0.00 |
June | 0.100900E+11 | 0.259095E+10 | 720.00 | 0.990893E+10 | 0.181035E+09 | 0.00 | 0.64 | 30-JUN-23:40 | 0.32 | 14-JUN-06:05 | 5623.46 | 30-JUN-23:40 | 5623.46 | 30-JUN-23:40 | 475.21 | 27-JUN-15:00 | 1605.82 | 27-JUN-13:00 | 0.00 |
July | 0.158092E+11 | 0.433519E+10 | 744.00 | 0.154969E+11 | 0.312241E+09 | 0.00 | 0.84 | 31-JUL-23:15 | 0.57 | 13-JUL-06:20 | 7581.37 | 31-JUL-23:55 | 7542.80 | 31-JUL-24:00 | 479.07 | 20-JUL-15:00 | 2280.79 | 21-JUL-14:00 | 0.00 |
August | 0.203478E+11 | 0.531613E+10 | 744.00 | 0.201119E+11 | 0.235948E+09 | 0.00 | 0.98 | 04-AUG-18:30 | 0.20 | 31-AUG-24:00 | 8529.34 | 04-AUG-18:40 | 8529.34 | 04-AUG-18:40 | 472.06 | 14-AUG-10:00 | 2792.08 | 13-AUG-15:21 | 0.00 |
September | 0.452527E+10 | 0.117135E+10 | 720.00 | 0.439575E+10 | 0.129518E+09 | 0.00 | 0.35 | 21-SEP-17:30 | 0.04 | 30-SEP-07:00 | 2955.36 | 04-SEP-17:43 | 2955.36 | 04-SEP-17:43 | 334.47 | 15-SEP-15:30 | 859.04 | 21-SEP-17:00 | 0.00 |
October | 0.725508E+10 | 0.176816E+10 | 744.00 | 0.722491E+10 | 30165020.62 | 0.00 | 0.54 | 11-OCT-17:00 | 0.13 | 30-OCT-03:30 | 4609.59 | 11-OCT-17:00 | 4599.00 | 31-OCT-23:20 | 183.62 | 12-OCT-15:30 | 1204.77 | 11-OCT-17:00 | 0.00 |
November | 0.103636E+11 | 0.248439E+10 | 720.00 | 0.103618E+11 | 1836811.00 | 0.00 | 0.64 | 03-NOV-16:00 | 0.30 | 24-NOV-04:15 | 5565.57 | 15-NOV-16:20 | 5565.57 | 15-NOV-16:20 | 135.76 | 16-NOV-16:20 | 1277.02 | 03-NOV-16:00 | 0.00 |
December | 0.136883E+11 | 0.330396E+10 | 744.00 | 0.136878E+11 | 492060.04 | 0.00 | 0.79 | 04-DEC-16:20 | 0.42 | 26-DEC-04:22 | 6685.20 | 04-DEC-16:20 | 6685.20 | 04-DEC-16:20 | 82.19 | 01-DEC-13:40 | 1559.33 | 04-DEC-16:20 | 0.00 |
Annual Sum or Average | 0.117794E+12 | 0.295848E+11 | 8119.45 | 0.116844E+12 | 0.950302E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.147746E+09 | 47931255.05 | 128.56 | 0.147746E+09 | -0.0 | 0.00 | 0.19 | 0.00 | 1320.07 | 1320.07 | 0.00 | 365.17 | 0.00 | ||||||
Maximum of Months | 0.203478E+11 | 0.531613E+10 | 744.00 | 0.201119E+11 | 0.312241E+09 | 0.00 | 0.98 | 0.57 | 8529.34 | 8529.34 | 479.07 | 2792.08 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 128.96 | 0.00 | 128.96 | 0.01 | 887.62 | 0.00 | 0.00 | 0.00 |
February | 196.49 | 0.00 | 196.49 | 4.07 | 835.60 | 0.00 | 0.00 | 0.00 |
March | 238.28 | 0.00 | 238.28 | 59.25 | 616.66 | 0.00 | 0.00 | 0.00 |
April | 303.62 | 1.21 | 302.41 | 135.94 | 443.81 | 0.00 | 0.00 | 0.00 |
May | 352.80 | 14.96 | 337.83 | 259.98 | 266.81 | 0.00 | 0.00 | 0.00 |
June | 424.34 | 36.12 | 388.22 | 444.79 | 170.93 | 0.00 | 0.00 | 0.00 |
July | 393.63 | 25.41 | 368.22 | 478.78 | 120.58 | 0.00 | 0.00 | 0.00 |
August | 340.60 | 5.18 | 335.42 | 390.15 | 158.86 | 0.00 | 0.00 | 0.00 |
September | 259.20 | 0.05 | 259.15 | 223.36 | 264.73 | 0.00 | 0.00 | 0.00 |
October | 193.77 | 0.00 | 193.77 | 75.33 | 441.87 | 0.00 | 0.00 | 0.00 |
November | 130.21 | 0.00 | 130.21 | 15.90 | 595.16 | 0.00 | 0.00 | 0.00 |
December | 120.70 | 0.00 | 120.70 | 0.49 | 874.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 257.13 | 6.94 | 250.19 | 175.06 | 471.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 120.70 | 0.00 | 120.70 | 0.01 | 120.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 424.34 | 36.12 | 388.22 | 478.78 | 887.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 128.96 | 0.00 | 128.96 | 0.01 | 887.62 | 0.00 | 0.00 | 0.00 |
February | 196.49 | 0.00 | 196.49 | 4.07 | 835.60 | 0.00 | 0.00 | 0.00 |
March | 238.28 | 0.00 | 238.28 | 59.25 | 616.66 | 0.00 | 0.00 | 0.00 |
April | 303.62 | 1.21 | 302.41 | 135.94 | 443.81 | 0.00 | 0.00 | 0.00 |
May | 352.79 | 14.96 | 337.83 | 259.98 | 266.81 | 0.00 | 0.00 | 0.00 |
June | 424.34 | 36.12 | 388.22 | 444.79 | 170.93 | 0.00 | 0.00 | 0.00 |
July | 393.63 | 25.41 | 368.22 | 478.78 | 120.57 | 0.00 | 0.00 | 0.00 |
August | 340.60 | 5.18 | 335.42 | 390.15 | 158.86 | 0.00 | 0.00 | 0.00 |
September | 259.20 | 0.05 | 259.15 | 223.36 | 264.73 | 0.00 | 0.00 | 0.00 |
October | 193.77 | 0.00 | 193.77 | 75.33 | 441.87 | 0.00 | 0.00 | 0.00 |
November | 130.21 | 0.00 | 130.21 | 15.90 | 595.16 | 0.00 | 0.00 | 0.00 |
December | 120.70 | 0.00 | 120.70 | 0.49 | 874.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 257.13 | 6.94 | 250.19 | 175.06 | 471.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 120.70 | 0.00 | 120.70 | 0.01 | 120.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 424.34 | 36.12 | 388.22 | 478.78 | 887.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 128.96 | 0.00 | 128.96 | 0.01 | 887.62 | 0.00 | 0.00 | 0.00 |
February | 196.49 | 0.00 | 196.49 | 4.07 | 835.60 | 0.00 | 0.00 | 0.00 |
March | 238.28 | 0.00 | 238.28 | 59.25 | 616.66 | 0.00 | 0.00 | 0.00 |
April | 303.62 | 1.21 | 302.41 | 135.94 | 443.81 | 0.00 | 0.00 | 0.00 |
May | 352.80 | 14.96 | 337.83 | 259.98 | 266.81 | 0.00 | 0.00 | 0.00 |
June | 424.34 | 36.12 | 388.22 | 444.79 | 170.93 | 0.00 | 0.00 | 0.00 |
July | 393.63 | 25.41 | 368.22 | 478.78 | 120.58 | 0.00 | 0.00 | 0.00 |
August | 340.60 | 5.18 | 335.42 | 390.15 | 158.86 | 0.00 | 0.00 | 0.00 |
September | 259.20 | 0.05 | 259.15 | 223.36 | 264.73 | 0.00 | 0.00 | 0.00 |
October | 193.77 | 0.00 | 193.77 | 75.33 | 441.87 | 0.00 | 0.00 | 0.00 |
November | 130.21 | 0.00 | 130.21 | 15.90 | 595.16 | 0.00 | 0.00 | 0.00 |
December | 120.70 | 0.00 | 120.70 | 0.49 | 874.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 257.13 | 6.94 | 250.19 | 175.06 | 471.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 120.70 | 0.00 | 120.70 | 0.01 | 120.58 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 424.34 | 36.12 | 388.22 | 478.78 | 887.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 128.96 | 0.00 | 128.96 | 0.01 | 887.62 | 0.00 | 0.00 | 0.00 |
February | 196.49 | 0.00 | 196.49 | 4.07 | 835.60 | 0.00 | 0.00 | 0.00 |
March | 238.28 | 0.00 | 238.28 | 59.25 | 616.66 | 0.00 | 0.00 | 0.00 |
April | 303.62 | 1.21 | 302.41 | 135.94 | 443.81 | 0.00 | 0.00 | 0.00 |
May | 352.79 | 14.96 | 337.83 | 259.98 | 266.81 | 0.00 | 0.00 | 0.00 |
June | 424.34 | 36.12 | 388.22 | 444.79 | 170.93 | 0.00 | 0.00 | 0.00 |
July | 393.63 | 25.41 | 368.22 | 478.78 | 120.57 | 0.00 | 0.00 | 0.00 |
August | 340.60 | 5.18 | 335.42 | 390.15 | 158.86 | 0.00 | 0.00 | 0.00 |
September | 259.20 | 0.05 | 259.15 | 223.36 | 264.73 | 0.00 | 0.00 | 0.00 |
October | 193.77 | 0.00 | 193.77 | 75.33 | 441.87 | 0.00 | 0.00 | 0.00 |
November | 130.21 | 0.00 | 130.21 | 15.90 | 595.16 | 0.00 | 0.00 | 0.00 |
December | 120.70 | 0.00 | 120.70 | 0.49 | 874.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 257.13 | 6.94 | 250.19 | 175.06 | 471.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 120.70 | 0.00 | 120.70 | 0.01 | 120.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 424.34 | 36.12 | 388.22 | 478.78 | 887.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 128.96 | 0.00 | 128.96 | 0.01 | 887.58 | 0.00 | 0.00 | 0.00 |
February | 196.48 | 0.00 | 196.48 | 4.07 | 835.57 | 0.00 | 0.00 | 0.00 |
March | 238.27 | 0.00 | 238.27 | 59.25 | 616.63 | 0.00 | 0.00 | 0.00 |
April | 303.61 | 1.21 | 302.40 | 135.94 | 443.79 | 0.00 | 0.00 | 0.00 |
May | 352.78 | 14.96 | 337.82 | 259.97 | 266.80 | 0.00 | 0.00 | 0.00 |
June | 424.32 | 36.12 | 388.20 | 444.77 | 170.93 | 0.00 | 0.00 | 0.00 |
July | 393.61 | 25.41 | 368.21 | 478.76 | 120.57 | 0.00 | 0.00 | 0.00 |
August | 340.59 | 5.18 | 335.40 | 390.13 | 158.86 | 0.00 | 0.00 | 0.00 |
September | 259.19 | 0.05 | 259.14 | 223.35 | 264.72 | 0.00 | 0.00 | 0.00 |
October | 193.76 | 0.00 | 193.76 | 75.33 | 441.85 | 0.00 | 0.00 | 0.00 |
November | 130.20 | 0.00 | 130.20 | 15.90 | 595.14 | 0.00 | 0.00 | 0.00 |
December | 120.70 | 0.00 | 120.70 | 0.49 | 874.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 257.12 | 6.94 | 250.18 | 175.05 | 471.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 120.70 | 0.00 | 120.70 | 0.01 | 120.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 424.32 | 36.12 | 388.20 | 478.76 | 887.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 262.22 | 84.55 | 177.66 | 90.81 | 891.71 | 0.00 | 0.00 | 0.00 |
February | 384.75 | 115.46 | 269.30 | 162.25 | 840.46 | 0.00 | 0.00 | 0.00 |
March | 552.11 | 231.22 | 320.89 | 407.33 | 613.62 | 0.00 | 0.00 | 0.00 |
April | 730.75 | 322.89 | 407.87 | 660.26 | 446.47 | 0.00 | 0.00 | 0.00 |
May | 818.71 | 362.16 | 456.55 | 874.12 | 294.40 | 0.00 | 0.00 | 0.00 |
June | 914.36 | 404.10 | 510.26 | 1100.69 | 188.28 | 0.00 | 0.00 | 0.00 |
July | 878.02 | 386.58 | 491.44 | 1138.01 | 127.76 | 0.00 | 0.00 | 0.00 |
August | 792.95 | 332.84 | 460.11 | 1006.33 | 164.25 | 0.00 | 0.00 | 0.00 |
September | 659.87 | 292.69 | 367.18 | 749.95 | 275.33 | 0.00 | 0.00 | 0.00 |
October | 447.78 | 185.21 | 262.57 | 379.56 | 448.13 | 0.00 | 0.00 | 0.00 |
November | 253.99 | 81.48 | 172.51 | 139.60 | 604.03 | 0.00 | 0.00 | 0.00 |
December | 204.47 | 42.25 | 162.22 | 44.55 | 887.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 575.85 | 237.36 | 338.49 | 564.99 | 479.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 204.47 | 42.25 | 162.22 | 44.55 | 127.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 914.36 | 404.10 | 510.26 | 1138.01 | 891.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 262.22 | 84.55 | 177.66 | 90.81 | 891.71 | 0.00 | 0.00 | 0.00 |
February | 384.75 | 115.46 | 269.30 | 162.25 | 840.46 | 0.00 | 0.00 | 0.00 |
March | 552.11 | 231.22 | 320.89 | 407.33 | 613.62 | 0.00 | 0.00 | 0.00 |
April | 730.75 | 322.89 | 407.87 | 660.26 | 446.47 | 0.00 | 0.00 | 0.00 |
May | 818.71 | 362.16 | 456.55 | 874.12 | 294.40 | 0.00 | 0.00 | 0.00 |
June | 914.36 | 404.10 | 510.26 | 1100.69 | 188.28 | 0.00 | 0.00 | 0.00 |
July | 878.02 | 386.58 | 491.44 | 1138.01 | 127.76 | 0.00 | 0.00 | 0.00 |
August | 792.95 | 332.84 | 460.11 | 1006.33 | 164.25 | 0.00 | 0.00 | 0.00 |
September | 659.87 | 292.69 | 367.18 | 749.95 | 275.33 | 0.00 | 0.00 | 0.00 |
October | 447.78 | 185.21 | 262.57 | 379.56 | 448.13 | 0.00 | 0.00 | 0.00 |
November | 253.99 | 81.48 | 172.51 | 139.60 | 604.03 | 0.00 | 0.00 | 0.00 |
December | 204.47 | 42.25 | 162.22 | 44.55 | 887.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 575.85 | 237.36 | 338.49 | 564.99 | 479.99 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 204.47 | 42.25 | 162.22 | 44.55 | 127.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 914.36 | 404.10 | 510.26 | 1138.01 | 891.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 262.21 | 84.55 | 177.66 | 90.81 | 891.70 | 0.00 | 0.00 | 0.00 |
February | 384.75 | 115.45 | 269.29 | 162.24 | 840.45 | 0.00 | 0.00 | 0.00 |
March | 552.10 | 231.22 | 320.88 | 407.33 | 613.61 | 0.00 | 0.00 | 0.00 |
April | 730.74 | 322.88 | 407.86 | 660.25 | 446.46 | 0.00 | 0.00 | 0.00 |
May | 818.69 | 362.15 | 456.54 | 874.11 | 294.39 | 0.00 | 0.00 | 0.00 |
June | 914.34 | 404.09 | 510.25 | 1100.67 | 188.27 | 0.00 | 0.00 | 0.00 |
July | 878.01 | 386.57 | 491.43 | 1137.99 | 127.76 | 0.00 | 0.00 | 0.00 |
August | 792.94 | 332.83 | 460.10 | 1006.31 | 164.25 | 0.00 | 0.00 | 0.00 |
September | 659.86 | 292.69 | 367.17 | 749.93 | 275.33 | 0.00 | 0.00 | 0.00 |
October | 447.77 | 185.21 | 262.56 | 379.55 | 448.12 | 0.00 | 0.00 | 0.00 |
November | 253.98 | 81.47 | 172.51 | 139.60 | 604.02 | 0.00 | 0.00 | 0.00 |
December | 204.47 | 42.25 | 162.22 | 44.55 | 887.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 575.84 | 237.36 | 338.49 | 564.98 | 479.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 204.47 | 42.25 | 162.22 | 44.55 | 127.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 914.34 | 404.09 | 510.25 | 1137.99 | 891.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 554.53 | 323.70 | 230.84 | 430.75 | 733.96 | 0.00 | 0.00 | 0.00 |
February | 633.14 | 305.29 | 327.84 | 481.88 | 719.41 | 0.00 | 0.00 | 0.00 |
March | 772.79 | 434.22 | 338.56 | 735.42 | 545.70 | 0.00 | 0.00 | 0.00 |
April | 639.99 | 255.74 | 384.25 | 634.60 | 436.70 | 0.00 | 0.00 | 0.00 |
May | 560.05 | 162.66 | 397.39 | 612.39 | 287.90 | 0.00 | 0.00 | 0.00 |
June | 544.19 | 115.32 | 428.87 | 667.54 | 186.62 | 0.00 | 0.00 | 0.00 |
July | 555.53 | 134.79 | 420.74 | 755.05 | 129.19 | 0.00 | 0.00 | 0.00 |
August | 623.67 | 202.21 | 421.46 | 835.18 | 166.06 | 0.00 | 0.00 | 0.00 |
September | 725.14 | 353.20 | 371.94 | 895.91 | 264.39 | 0.00 | 0.00 | 0.00 |
October | 693.85 | 396.34 | 297.51 | 733.21 | 405.68 | 0.00 | 0.00 | 0.00 |
November | 496.92 | 280.53 | 216.39 | 452.66 | 526.07 | 0.00 | 0.00 | 0.00 |
December | 463.70 | 239.99 | 223.71 | 336.71 | 736.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 605.10 | 266.86 | 338.25 | 631.82 | 426.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 463.70 | 115.32 | 216.39 | 336.71 | 129.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 772.79 | 434.22 | 428.87 | 895.91 | 736.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 554.53 | 323.70 | 230.84 | 430.75 | 733.96 | 0.00 | 0.00 | 0.00 |
February | 633.14 | 305.29 | 327.84 | 481.88 | 719.41 | 0.00 | 0.00 | 0.00 |
March | 772.79 | 434.22 | 338.56 | 735.42 | 545.70 | 0.00 | 0.00 | 0.00 |
April | 639.99 | 255.74 | 384.25 | 634.60 | 436.70 | 0.00 | 0.00 | 0.00 |
May | 560.05 | 162.66 | 397.39 | 612.39 | 287.90 | 0.00 | 0.00 | 0.00 |
June | 544.19 | 115.32 | 428.87 | 667.54 | 186.62 | 0.00 | 0.00 | 0.00 |
July | 555.52 | 134.79 | 420.74 | 755.05 | 129.19 | 0.00 | 0.00 | 0.00 |
August | 623.67 | 202.21 | 421.46 | 835.18 | 166.06 | 0.00 | 0.00 | 0.00 |
September | 725.14 | 353.20 | 371.94 | 895.91 | 264.39 | 0.00 | 0.00 | 0.00 |
October | 693.85 | 396.34 | 297.51 | 733.21 | 405.68 | 0.00 | 0.00 | 0.00 |
November | 496.92 | 280.53 | 216.39 | 452.65 | 526.07 | 0.00 | 0.00 | 0.00 |
December | 463.70 | 239.99 | 223.71 | 336.71 | 736.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 605.10 | 266.86 | 338.25 | 631.82 | 426.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 463.70 | 115.32 | 216.39 | 336.71 | 129.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 772.79 | 434.22 | 428.87 | 895.91 | 736.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 554.53 | 323.70 | 230.84 | 430.75 | 733.96 | 0.00 | 0.00 | 0.00 |
February | 633.14 | 305.29 | 327.84 | 481.88 | 719.41 | 0.00 | 0.00 | 0.00 |
March | 772.79 | 434.22 | 338.56 | 735.42 | 545.70 | 0.00 | 0.00 | 0.00 |
April | 639.99 | 255.74 | 384.25 | 634.60 | 436.70 | 0.00 | 0.00 | 0.00 |
May | 560.05 | 162.66 | 397.39 | 612.39 | 287.90 | 0.00 | 0.00 | 0.00 |
June | 544.19 | 115.32 | 428.87 | 667.54 | 186.62 | 0.00 | 0.00 | 0.00 |
July | 555.53 | 134.79 | 420.74 | 755.05 | 129.19 | 0.00 | 0.00 | 0.00 |
August | 623.67 | 202.21 | 421.46 | 835.18 | 166.06 | 0.00 | 0.00 | 0.00 |
September | 725.14 | 353.20 | 371.94 | 895.91 | 264.39 | 0.00 | 0.00 | 0.00 |
October | 693.85 | 396.34 | 297.51 | 733.21 | 405.68 | 0.00 | 0.00 | 0.00 |
November | 496.92 | 280.53 | 216.39 | 452.66 | 526.07 | 0.00 | 0.00 | 0.00 |
December | 463.70 | 239.99 | 223.71 | 336.71 | 736.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 605.10 | 266.86 | 338.25 | 631.82 | 426.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 463.70 | 115.32 | 216.39 | 336.71 | 129.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 772.79 | 434.22 | 428.87 | 895.91 | 736.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 554.53 | 323.70 | 230.84 | 430.75 | 733.96 | 0.00 | 0.00 | 0.00 |
February | 633.14 | 305.29 | 327.84 | 481.88 | 719.41 | 0.00 | 0.00 | 0.00 |
March | 772.79 | 434.22 | 338.56 | 735.42 | 545.70 | 0.00 | 0.00 | 0.00 |
April | 639.99 | 255.74 | 384.25 | 634.60 | 436.70 | 0.00 | 0.00 | 0.00 |
May | 560.05 | 162.66 | 397.39 | 612.39 | 287.90 | 0.00 | 0.00 | 0.00 |
June | 544.19 | 115.32 | 428.87 | 667.54 | 186.62 | 0.00 | 0.00 | 0.00 |
July | 555.52 | 134.79 | 420.74 | 755.05 | 129.19 | 0.00 | 0.00 | 0.00 |
August | 623.67 | 202.21 | 421.46 | 835.18 | 166.06 | 0.00 | 0.00 | 0.00 |
September | 725.14 | 353.20 | 371.94 | 895.91 | 264.39 | 0.00 | 0.00 | 0.00 |
October | 693.85 | 396.34 | 297.51 | 733.21 | 405.68 | 0.00 | 0.00 | 0.00 |
November | 496.92 | 280.53 | 216.39 | 452.65 | 526.07 | 0.00 | 0.00 | 0.00 |
December | 463.70 | 239.99 | 223.71 | 336.71 | 736.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 605.10 | 266.86 | 338.25 | 631.82 | 426.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 463.70 | 115.32 | 216.39 | 336.71 | 129.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 772.79 | 434.22 | 428.87 | 895.91 | 736.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 554.51 | 323.68 | 230.83 | 430.73 | 733.93 | 0.00 | 0.00 | 0.00 |
February | 633.11 | 305.28 | 327.83 | 481.86 | 719.38 | 0.00 | 0.00 | 0.00 |
March | 772.76 | 434.21 | 338.55 | 735.39 | 545.68 | 0.00 | 0.00 | 0.00 |
April | 639.96 | 255.73 | 384.23 | 634.58 | 436.68 | 0.00 | 0.00 | 0.00 |
May | 560.02 | 162.65 | 397.37 | 612.36 | 287.88 | 0.00 | 0.00 | 0.00 |
June | 544.16 | 115.31 | 428.85 | 667.51 | 186.62 | 0.00 | 0.00 | 0.00 |
July | 555.50 | 134.78 | 420.72 | 755.02 | 129.18 | 0.00 | 0.00 | 0.00 |
August | 623.64 | 202.20 | 421.44 | 835.15 | 166.05 | 0.00 | 0.00 | 0.00 |
September | 725.11 | 353.18 | 371.93 | 895.87 | 264.37 | 0.00 | 0.00 | 0.00 |
October | 693.82 | 396.33 | 297.50 | 733.18 | 405.67 | 0.00 | 0.00 | 0.00 |
November | 496.90 | 280.52 | 216.38 | 452.64 | 526.05 | 0.00 | 0.00 | 0.00 |
December | 463.68 | 239.98 | 223.71 | 336.70 | 736.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 605.08 | 266.85 | 338.23 | 631.79 | 426.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 463.68 | 115.31 | 216.38 | 336.70 | 129.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 772.76 | 434.21 | 428.85 | 895.87 | 736.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 224.98 | 52.82 | 172.16 | 53.70 | 960.60 | 0.00 | 0.00 | 0.00 |
February | 364.63 | 93.71 | 270.92 | 132.14 | 922.82 | 0.00 | 0.00 | 0.00 |
March | 571.49 | 244.70 | 326.79 | 416.49 | 696.45 | 0.00 | 0.00 | 0.00 |
April | 699.71 | 286.91 | 412.80 | 607.10 | 538.16 | 0.00 | 0.00 | 0.00 |
May | 825.42 | 373.04 | 452.38 | 878.42 | 337.74 | 0.00 | 0.00 | 0.00 |
June | 995.90 | 468.43 | 527.47 | 1200.77 | 231.18 | 0.00 | 0.00 | 0.00 |
July | 890.37 | 390.37 | 500.00 | 1141.79 | 167.16 | 0.00 | 0.00 | 0.00 |
August | 805.29 | 342.42 | 462.87 | 1010.76 | 215.34 | 0.00 | 0.00 | 0.00 |
September | 632.40 | 273.11 | 359.29 | 712.12 | 314.24 | 0.00 | 0.00 | 0.00 |
October | 409.95 | 144.41 | 265.54 | 326.45 | 513.99 | 0.00 | 0.00 | 0.00 |
November | 242.94 | 70.01 | 172.93 | 119.46 | 697.07 | 0.00 | 0.00 | 0.00 |
December | 210.61 | 45.89 | 164.72 | 46.47 | 1009.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 573.75 | 232.82 | 340.93 | 556.11 | 548.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 210.61 | 45.89 | 164.72 | 46.47 | 167.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 995.90 | 468.43 | 527.47 | 1200.77 | 1009.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 224.98 | 52.82 | 172.16 | 53.70 | 960.60 | 0.00 | 0.00 | 0.00 |
February | 364.63 | 93.71 | 270.92 | 132.14 | 922.82 | 0.00 | 0.00 | 0.00 |
March | 571.49 | 244.70 | 326.79 | 416.49 | 696.45 | 0.00 | 0.00 | 0.00 |
April | 699.71 | 286.91 | 412.80 | 607.10 | 538.16 | 0.00 | 0.00 | 0.00 |
May | 825.42 | 373.04 | 452.38 | 878.42 | 337.74 | 0.00 | 0.00 | 0.00 |
June | 995.90 | 468.43 | 527.47 | 1200.77 | 231.18 | 0.00 | 0.00 | 0.00 |
July | 890.37 | 390.37 | 500.00 | 1141.79 | 167.16 | 0.00 | 0.00 | 0.00 |
August | 805.29 | 342.42 | 462.87 | 1010.76 | 215.34 | 0.00 | 0.00 | 0.00 |
September | 632.40 | 273.11 | 359.29 | 712.12 | 314.24 | 0.00 | 0.00 | 0.00 |
October | 409.95 | 144.41 | 265.54 | 326.45 | 513.99 | 0.00 | 0.00 | 0.00 |
November | 242.94 | 70.01 | 172.93 | 119.46 | 697.07 | 0.00 | 0.00 | 0.00 |
December | 210.61 | 45.89 | 164.72 | 46.47 | 1009.92 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 573.75 | 232.82 | 340.93 | 556.11 | 548.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 210.61 | 45.89 | 164.72 | 46.47 | 167.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 995.90 | 468.43 | 527.47 | 1200.77 | 1009.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 224.97 | 52.82 | 172.16 | 53.70 | 960.59 | 0.00 | 0.00 | 0.00 |
February | 364.62 | 93.71 | 270.91 | 132.14 | 922.81 | 0.00 | 0.00 | 0.00 |
March | 571.48 | 244.69 | 326.79 | 416.48 | 696.44 | 0.00 | 0.00 | 0.00 |
April | 699.70 | 286.90 | 412.79 | 607.09 | 538.15 | 0.00 | 0.00 | 0.00 |
May | 825.41 | 373.03 | 452.38 | 878.40 | 337.74 | 0.00 | 0.00 | 0.00 |
June | 995.88 | 468.42 | 527.46 | 1200.75 | 231.17 | 0.00 | 0.00 | 0.00 |
July | 890.35 | 390.36 | 499.99 | 1141.77 | 167.15 | 0.00 | 0.00 | 0.00 |
August | 805.27 | 342.41 | 462.86 | 1010.74 | 215.33 | 0.00 | 0.00 | 0.00 |
September | 632.39 | 273.10 | 359.29 | 712.10 | 314.23 | 0.00 | 0.00 | 0.00 |
October | 409.94 | 144.41 | 265.54 | 326.45 | 513.98 | 0.00 | 0.00 | 0.00 |
November | 242.93 | 70.00 | 172.93 | 119.45 | 697.06 | 0.00 | 0.00 | 0.00 |
December | 210.60 | 45.89 | 164.71 | 46.47 | 1009.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 573.74 | 232.82 | 340.92 | 556.10 | 548.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 210.60 | 45.89 | 164.71 | 46.47 | 167.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 995.88 | 468.42 | 527.46 | 1200.75 | 1009.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 644.80 | 0.00 | 644.80 | 4.09 | 4037.30 | 0.00 | 0.00 | 0.00 |
February | 982.43 | 0.00 | 982.43 | 44.15 | 3792.56 | 0.00 | 0.00 | 0.00 |
March | 1191.41 | 0.00 | 1191.41 | 347.73 | 2773.97 | 0.00 | 0.00 | 0.00 |
April | 1518.10 | 6.06 | 1512.04 | 763.29 | 1979.19 | 0.00 | 0.00 | 0.00 |
May | 1763.95 | 74.80 | 1689.15 | 1333.78 | 1257.15 | 0.00 | 0.00 | 0.00 |
June | 2121.66 | 180.61 | 1941.06 | 2247.47 | 809.58 | 0.00 | 0.00 | 0.00 |
July | 1968.13 | 127.05 | 1841.08 | 2428.81 | 564.06 | 0.00 | 0.00 | 0.00 |
August | 1702.98 | 25.91 | 1677.07 | 1982.97 | 747.69 | 0.00 | 0.00 | 0.00 |
September | 1296.00 | 0.27 | 1295.73 | 1148.70 | 1220.37 | 0.00 | 0.00 | 0.00 |
October | 968.82 | 0.00 | 968.82 | 439.15 | 1961.83 | 0.00 | 0.00 | 0.00 |
November | 651.02 | 0.00 | 651.02 | 119.35 | 2567.11 | 0.00 | 0.00 | 0.00 |
December | 603.51 | 0.00 | 603.51 | 6.63 | 3871.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1285.65 | 34.71 | 1250.94 | 910.79 | 2123.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 603.51 | 0.00 | 603.51 | 4.09 | 564.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2121.66 | 180.61 | 1941.06 | 2428.81 | 4037.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 786.65 | 253.66 | 532.99 | 290.12 | 2452.67 | 0.00 | 0.00 | 0.00 |
February | 1154.25 | 346.36 | 807.89 | 517.65 | 2329.35 | 0.00 | 0.00 | 0.00 |
March | 1656.32 | 693.65 | 962.66 | 1247.46 | 1709.39 | 0.00 | 0.00 | 0.00 |
April | 2192.24 | 968.65 | 1223.59 | 1999.85 | 1249.36 | 0.00 | 0.00 | 0.00 |
May | 2456.09 | 1086.46 | 1369.63 | 2615.46 | 845.37 | 0.00 | 0.00 | 0.00 |
June | 2743.04 | 1212.29 | 1530.75 | 3288.33 | 545.71 | 0.00 | 0.00 | 0.00 |
July | 2634.04 | 1159.73 | 1474.31 | 3404.41 | 377.86 | 0.00 | 0.00 | 0.00 |
August | 2378.83 | 998.50 | 1380.33 | 3005.79 | 493.16 | 0.00 | 0.00 | 0.00 |
September | 1979.60 | 878.07 | 1101.52 | 2250.73 | 775.70 | 0.00 | 0.00 | 0.00 |
October | 1343.32 | 555.63 | 787.69 | 1165.73 | 1231.56 | 0.00 | 0.00 | 0.00 |
November | 761.96 | 244.43 | 517.53 | 448.97 | 1629.05 | 0.00 | 0.00 | 0.00 |
December | 613.41 | 126.74 | 486.67 | 148.63 | 2428.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1727.54 | 712.07 | 1015.47 | 1705.03 | 1333.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 613.41 | 126.74 | 486.67 | 148.63 | 377.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2743.04 | 1212.29 | 1530.75 | 3404.41 | 2452.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2772.63 | 1618.47 | 1154.16 | 2164.01 | 3504.29 | 0.00 | 0.00 | 0.00 |
February | 3165.65 | 1526.45 | 1639.20 | 2421.14 | 3447.06 | 0.00 | 0.00 | 0.00 |
March | 3863.89 | 2171.09 | 1692.79 | 3665.28 | 2624.40 | 0.00 | 0.00 | 0.00 |
April | 3199.91 | 1278.69 | 1921.21 | 3177.04 | 2078.07 | 0.00 | 0.00 | 0.00 |
May | 2800.20 | 813.30 | 1986.91 | 3044.67 | 1399.87 | 0.00 | 0.00 | 0.00 |
June | 2720.89 | 576.57 | 2144.32 | 3330.51 | 895.50 | 0.00 | 0.00 | 0.00 |
July | 2777.59 | 673.93 | 2103.66 | 3776.19 | 620.04 | 0.00 | 0.00 | 0.00 |
August | 3118.30 | 1011.03 | 2107.27 | 4168.23 | 807.20 | 0.00 | 0.00 | 0.00 |
September | 3625.66 | 1765.97 | 1859.69 | 4456.07 | 1280.96 | 0.00 | 0.00 | 0.00 |
October | 3469.22 | 1981.69 | 1487.53 | 3651.80 | 1947.65 | 0.00 | 0.00 | 0.00 |
November | 2484.58 | 1402.63 | 1081.95 | 2273.90 | 2481.01 | 0.00 | 0.00 | 0.00 |
December | 2318.47 | 1199.91 | 1118.56 | 1704.34 | 3463.07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3025.48 | 1334.27 | 1691.21 | 3157.06 | 2038.21 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2318.47 | 576.57 | 1081.95 | 1704.34 | 620.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3863.89 | 2171.09 | 2144.32 | 4456.07 | 3504.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 674.93 | 158.45 | 516.48 | 173.95 | 2594.96 | 0.00 | 0.00 | 0.00 |
February | 1093.87 | 281.13 | 812.74 | 435.85 | 2456.95 | 0.00 | 0.00 | 0.00 |
March | 1714.45 | 734.09 | 980.36 | 1314.65 | 1804.95 | 0.00 | 0.00 | 0.00 |
April | 2099.11 | 860.72 | 1238.39 | 1907.54 | 1360.39 | 0.00 | 0.00 | 0.00 |
May | 2476.24 | 1119.10 | 1357.14 | 2656.14 | 937.64 | 0.00 | 0.00 | 0.00 |
June | 2987.66 | 1405.27 | 1582.39 | 3618.73 | 632.89 | 0.00 | 0.00 | 0.00 |
July | 2671.08 | 1171.09 | 1499.99 | 3455.91 | 451.93 | 0.00 | 0.00 | 0.00 |
August | 2415.83 | 1027.24 | 1388.60 | 3074.32 | 565.85 | 0.00 | 0.00 | 0.00 |
September | 1897.18 | 819.31 | 1077.87 | 2160.90 | 851.41 | 0.00 | 0.00 | 0.00 |
October | 1229.84 | 433.22 | 796.62 | 1043.17 | 1314.97 | 0.00 | 0.00 | 0.00 |
November | 728.81 | 210.02 | 518.79 | 408.50 | 1706.79 | 0.00 | 0.00 | 0.00 |
December | 631.81 | 137.66 | 494.15 | 164.59 | 2525.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1721.24 | 698.46 | 1022.78 | 1708.05 | 1428.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 631.81 | 137.66 | 494.15 | 164.59 | 451.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2987.66 | 1405.27 | 1582.39 | 3618.73 | 2594.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 644.80 | 0.00 | 644.80 | 10.45 | 3887.82 | 0.00 | 0.00 | 0.00 |
February | 982.43 | 0.00 | 982.43 | 60.11 | 3639.48 | 0.00 | 0.00 | 0.00 |
March | 1191.41 | 0.00 | 1191.41 | 376.39 | 2606.69 | 0.00 | 0.00 | 0.00 |
April | 1518.10 | 6.06 | 1512.04 | 812.75 | 1843.20 | 0.00 | 0.00 | 0.00 |
May | 1763.95 | 74.80 | 1689.15 | 1359.51 | 1198.35 | 0.00 | 0.00 | 0.00 |
June | 2121.66 | 180.61 | 1941.06 | 2238.27 | 797.74 | 0.00 | 0.00 | 0.00 |
July | 1968.13 | 127.05 | 1841.08 | 2406.65 | 565.42 | 0.00 | 0.00 | 0.00 |
August | 1702.98 | 25.91 | 1677.07 | 1971.55 | 739.06 | 0.00 | 0.00 | 0.00 |
September | 1296.00 | 0.27 | 1295.73 | 1165.57 | 1157.49 | 0.00 | 0.00 | 0.00 |
October | 968.82 | 0.00 | 968.82 | 489.57 | 1782.81 | 0.00 | 0.00 | 0.00 |
November | 651.02 | 0.00 | 651.02 | 150.10 | 2335.60 | 0.00 | 0.00 | 0.00 |
December | 603.51 | 0.00 | 603.51 | 11.10 | 3678.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1285.65 | 34.71 | 1250.94 | 926.21 | 2011.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 603.51 | 0.00 | 603.51 | 10.45 | 565.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2121.66 | 180.61 | 1941.06 | 2406.65 | 3887.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 786.65 | 253.66 | 532.99 | 301.98 | 2358.65 | 0.00 | 0.00 | 0.00 |
February | 1154.25 | 346.36 | 807.89 | 538.75 | 2236.56 | 0.00 | 0.00 | 0.00 |
March | 1656.32 | 693.65 | 962.66 | 1275.75 | 1607.96 | 0.00 | 0.00 | 0.00 |
April | 2192.24 | 968.65 | 1223.59 | 2029.15 | 1177.43 | 0.00 | 0.00 | 0.00 |
May | 2456.09 | 1086.46 | 1369.63 | 2621.29 | 814.79 | 0.00 | 0.00 | 0.00 |
June | 2743.04 | 1212.29 | 1530.75 | 3276.72 | 541.05 | 0.00 | 0.00 | 0.00 |
July | 2634.04 | 1159.73 | 1474.31 | 3387.22 | 380.51 | 0.00 | 0.00 | 0.00 |
August | 2378.83 | 998.50 | 1380.33 | 2994.10 | 490.51 | 0.00 | 0.00 | 0.00 |
September | 1979.60 | 878.07 | 1101.52 | 2256.69 | 745.16 | 0.00 | 0.00 | 0.00 |
October | 1343.32 | 555.63 | 787.69 | 1201.06 | 1132.52 | 0.00 | 0.00 | 0.00 |
November | 761.96 | 244.43 | 517.53 | 476.78 | 1493.11 | 0.00 | 0.00 | 0.00 |
December | 613.41 | 126.74 | 486.67 | 158.08 | 2309.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1727.54 | 712.07 | 1015.47 | 1716.14 | 1269.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 613.41 | 126.74 | 486.67 | 158.08 | 380.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2743.04 | 1212.29 | 1530.75 | 3387.22 | 2358.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2772.63 | 1618.47 | 1154.16 | 2196.63 | 3346.73 | 0.00 | 0.00 | 0.00 |
February | 3165.65 | 1526.45 | 1639.20 | 2461.87 | 3292.69 | 0.00 | 0.00 | 0.00 |
March | 3863.89 | 2171.09 | 1692.79 | 3710.32 | 2459.11 | 0.00 | 0.00 | 0.00 |
April | 3199.91 | 1278.69 | 1921.21 | 3217.23 | 1948.33 | 0.00 | 0.00 | 0.00 |
May | 2800.20 | 813.30 | 1986.91 | 3055.95 | 1337.70 | 0.00 | 0.00 | 0.00 |
June | 2720.89 | 576.57 | 2144.32 | 3317.04 | 878.98 | 0.00 | 0.00 | 0.00 |
July | 2777.59 | 673.93 | 2103.66 | 3752.84 | 619.10 | 0.00 | 0.00 | 0.00 |
August | 3118.30 | 1011.03 | 2107.27 | 4151.75 | 797.17 | 0.00 | 0.00 | 0.00 |
September | 3625.66 | 1765.97 | 1859.69 | 4461.79 | 1225.53 | 0.00 | 0.00 | 0.00 |
October | 3469.22 | 1981.69 | 1487.53 | 3701.38 | 1789.96 | 0.00 | 0.00 | 0.00 |
November | 2484.58 | 1402.63 | 1081.95 | 2325.40 | 2267.92 | 0.00 | 0.00 | 0.00 |
December | 2318.47 | 1199.91 | 1118.56 | 1741.34 | 3275.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3025.48 | 1334.27 | 1691.21 | 3178.61 | 1929.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 2318.47 | 576.57 | 1081.95 | 1741.34 | 619.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3863.89 | 2171.09 | 2144.32 | 4461.79 | 3346.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 674.93 | 158.45 | 516.48 | 181.00 | 2498.09 | 0.00 | 0.00 | 0.00 |
February | 1093.87 | 281.13 | 812.74 | 447.94 | 2366.33 | 0.00 | 0.00 | 0.00 |
March | 1714.45 | 734.09 | 980.36 | 1330.08 | 1709.65 | 0.00 | 0.00 | 0.00 |
April | 2099.11 | 860.72 | 1238.39 | 1928.33 | 1285.82 | 0.00 | 0.00 | 0.00 |
May | 2476.24 | 1119.10 | 1357.14 | 2661.98 | 900.61 | 0.00 | 0.00 | 0.00 |
June | 2987.66 | 1405.27 | 1582.39 | 3605.94 | 622.87 | 0.00 | 0.00 | 0.00 |
July | 2671.08 | 1171.09 | 1499.99 | 3439.07 | 450.12 | 0.00 | 0.00 | 0.00 |
August | 2415.83 | 1027.24 | 1388.60 | 3063.69 | 559.26 | 0.00 | 0.00 | 0.00 |
September | 1897.18 | 819.31 | 1077.87 | 2166.89 | 816.77 | 0.00 | 0.00 | 0.00 |
October | 1229.84 | 433.22 | 796.62 | 1067.27 | 1222.06 | 0.00 | 0.00 | 0.00 |
November | 728.81 | 210.02 | 518.79 | 426.75 | 1587.42 | 0.00 | 0.00 | 0.00 |
December | 631.81 | 137.66 | 494.15 | 171.83 | 2414.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1721.24 | 698.46 | 1022.78 | 1714.36 | 1364.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 631.81 | 137.66 | 494.15 | 171.83 | 450.12 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2987.66 | 1405.27 | 1582.39 | 3605.94 | 2498.09 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.345409E+09 | 0.00 | 0.345409E+09 | 15554.69 | 0.237740E+10 |
February | 0.475344E+09 | 0.00 | 0.475344E+09 | 9838598.12 | 0.202149E+10 |
March | 0.638221E+09 | 0.00 | 0.638221E+09 | 0.158700E+09 | 0.165166E+10 |
April | 0.786991E+09 | 3140405.62 | 0.783850E+09 | 0.352365E+09 | 0.115036E+10 |
May | 0.944926E+09 | 40070242.05 | 0.904856E+09 | 0.696331E+09 | 0.714635E+09 |
June | 0.109988E+10 | 93627760.75 | 0.100626E+10 | 0.115290E+10 | 0.443059E+09 |
July | 0.105430E+10 | 68057339.32 | 0.986241E+09 | 0.128238E+10 | 0.322948E+09 |
August | 0.912261E+09 | 13878074.16 | 0.898383E+09 | 0.104497E+10 | 0.425499E+09 |
September | 0.671855E+09 | 139582.43 | 0.671716E+09 | 0.578944E+09 | 0.686183E+09 |
October | 0.518982E+09 | 0.00 | 0.518982E+09 | 0.201759E+09 | 0.118350E+10 |
November | 0.337493E+09 | 0.00 | 0.337493E+09 | 41218772.25 | 0.154265E+10 |
December | 0.323292E+09 | 0.00 | 0.323292E+09 | 1315216.04 | 0.234195E+10 |
Annual Sum or Average | 0.810896E+10 | 0.218913E+09 | 0.789004E+10 | 0.552073E+10 | 0.148613E+11 |
Minimum of Months | 0.323292E+09 | 0.00 | 0.323292E+09 | 15554.69 | 0.322948E+09 |
Maximum of Months | 0.109988E+10 | 93627760.75 | 0.100626E+10 | 0.128238E+10 | 0.237740E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.345408E+09 | 0.00 | 0.345408E+09 | 15553.76 | 0.237740E+10 |
February | 0.475343E+09 | 0.00 | 0.475343E+09 | 9838510.29 | 0.202149E+10 |
March | 0.638220E+09 | 0.00 | 0.638220E+09 | 0.158699E+09 | 0.165166E+10 |
April | 0.786990E+09 | 3140401.85 | 0.783850E+09 | 0.352364E+09 | 0.115036E+10 |
May | 0.944925E+09 | 40070193.97 | 0.904855E+09 | 0.696330E+09 | 0.714635E+09 |
June | 0.109988E+10 | 93627648.41 | 0.100626E+10 | 0.115289E+10 | 0.443059E+09 |
July | 0.105430E+10 | 68057257.66 | 0.986241E+09 | 0.128237E+10 | 0.322948E+09 |
August | 0.912260E+09 | 13878057.50 | 0.898382E+09 | 0.104497E+10 | 0.425499E+09 |
September | 0.671855E+09 | 139582.26 | 0.671715E+09 | 0.578944E+09 | 0.686183E+09 |
October | 0.518981E+09 | 0.00 | 0.518981E+09 | 0.201759E+09 | 0.118350E+10 |
November | 0.337493E+09 | 0.00 | 0.337493E+09 | 41218661.36 | 0.154265E+10 |
December | 0.323292E+09 | 0.00 | 0.323292E+09 | 1315207.04 | 0.234195E+10 |
Annual Sum or Average | 0.810895E+10 | 0.218913E+09 | 0.789004E+10 | 0.552072E+10 | 0.148613E+11 |
Minimum of Months | 0.323292E+09 | 0.00 | 0.323292E+09 | 15553.76 | 0.322948E+09 |
Maximum of Months | 0.109988E+10 | 93627648.41 | 0.100626E+10 | 0.128237E+10 | 0.237740E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.345409E+09 | 0.00 | 0.345409E+09 | 15554.69 | 0.237740E+10 |
February | 0.475344E+09 | 0.00 | 0.475344E+09 | 9838598.12 | 0.202149E+10 |
March | 0.638221E+09 | 0.00 | 0.638221E+09 | 0.158700E+09 | 0.165166E+10 |
April | 0.786991E+09 | 3140405.62 | 0.783850E+09 | 0.352365E+09 | 0.115036E+10 |
May | 0.944926E+09 | 40070242.05 | 0.904856E+09 | 0.696331E+09 | 0.714635E+09 |
June | 0.109988E+10 | 93627760.75 | 0.100626E+10 | 0.115290E+10 | 0.443059E+09 |
July | 0.105430E+10 | 68057339.32 | 0.986241E+09 | 0.128238E+10 | 0.322948E+09 |
August | 0.912261E+09 | 13878074.16 | 0.898383E+09 | 0.104497E+10 | 0.425499E+09 |
September | 0.671855E+09 | 139582.43 | 0.671716E+09 | 0.578944E+09 | 0.686183E+09 |
October | 0.518982E+09 | 0.00 | 0.518982E+09 | 0.201759E+09 | 0.118350E+10 |
November | 0.337493E+09 | 0.00 | 0.337493E+09 | 41218772.25 | 0.154265E+10 |
December | 0.323292E+09 | 0.00 | 0.323292E+09 | 1315216.04 | 0.234195E+10 |
Annual Sum or Average | 0.810896E+10 | 0.218913E+09 | 0.789004E+10 | 0.552073E+10 | 0.148613E+11 |
Minimum of Months | 0.323292E+09 | 0.00 | 0.323292E+09 | 15554.69 | 0.322948E+09 |
Maximum of Months | 0.109988E+10 | 93627760.75 | 0.100626E+10 | 0.128238E+10 | 0.237740E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.345408E+09 | 0.00 | 0.345408E+09 | 15553.76 | 0.237740E+10 |
February | 0.475343E+09 | 0.00 | 0.475343E+09 | 9838510.29 | 0.202149E+10 |
March | 0.638220E+09 | 0.00 | 0.638220E+09 | 0.158699E+09 | 0.165166E+10 |
April | 0.786990E+09 | 3140401.85 | 0.783850E+09 | 0.352364E+09 | 0.115036E+10 |
May | 0.944925E+09 | 40070193.97 | 0.904855E+09 | 0.696330E+09 | 0.714635E+09 |
June | 0.109988E+10 | 93627648.41 | 0.100626E+10 | 0.115289E+10 | 0.443059E+09 |
July | 0.105430E+10 | 68057257.66 | 0.986241E+09 | 0.128237E+10 | 0.322948E+09 |
August | 0.912260E+09 | 13878057.50 | 0.898382E+09 | 0.104497E+10 | 0.425499E+09 |
September | 0.671855E+09 | 139582.26 | 0.671715E+09 | 0.578944E+09 | 0.686183E+09 |
October | 0.518981E+09 | 0.00 | 0.518981E+09 | 0.201759E+09 | 0.118350E+10 |
November | 0.337493E+09 | 0.00 | 0.337493E+09 | 41218661.36 | 0.154265E+10 |
December | 0.323292E+09 | 0.00 | 0.323292E+09 | 1315207.04 | 0.234195E+10 |
Annual Sum or Average | 0.810895E+10 | 0.218913E+09 | 0.789004E+10 | 0.552072E+10 | 0.148613E+11 |
Minimum of Months | 0.323292E+09 | 0.00 | 0.323292E+09 | 15553.76 | 0.322948E+09 |
Maximum of Months | 0.109988E+10 | 93627648.41 | 0.100626E+10 | 0.128237E+10 | 0.237740E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.345395E+09 | 0.00 | 0.345395E+09 | 15554.07 | 0.237730E+10 |
February | 0.475324E+09 | 0.00 | 0.475324E+09 | 9838201.58 | 0.202141E+10 |
March | 0.638195E+09 | 0.00 | 0.638195E+09 | 0.158693E+09 | 0.165159E+10 |
April | 0.786959E+09 | 3140279.04 | 0.783819E+09 | 0.352351E+09 | 0.115032E+10 |
May | 0.944888E+09 | 40068627.05 | 0.904819E+09 | 0.696303E+09 | 0.714607E+09 |
June | 0.109984E+10 | 93623987.14 | 0.100622E+10 | 0.115285E+10 | 0.443041E+09 |
July | 0.105426E+10 | 68054596.31 | 0.986201E+09 | 0.128232E+10 | 0.322935E+09 |
August | 0.912224E+09 | 13877514.81 | 0.898347E+09 | 0.104493E+10 | 0.425481E+09 |
September | 0.671828E+09 | 139576.80 | 0.671689E+09 | 0.578921E+09 | 0.686155E+09 |
October | 0.518961E+09 | 0.00 | 0.518961E+09 | 0.201751E+09 | 0.118345E+10 |
November | 0.337480E+09 | 0.00 | 0.337480E+09 | 41217110.96 | 0.154259E+10 |
December | 0.323279E+09 | 0.00 | 0.323279E+09 | 1315163.03 | 0.234186E+10 |
Annual Sum or Average | 0.810863E+10 | 0.218905E+09 | 0.788972E+10 | 0.552051E+10 | 0.148607E+11 |
Minimum of Months | 0.323279E+09 | 0.00 | 0.323279E+09 | 15554.07 | 0.322935E+09 |
Maximum of Months | 0.109984E+10 | 93623987.14 | 0.100622E+10 | 0.128232E+10 | 0.237730E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.702325E+09 | 0.226469E+09 | 0.475856E+09 | 0.243231E+09 | 0.238836E+10 |
February | 0.930796E+09 | 0.279309E+09 | 0.651487E+09 | 0.392507E+09 | 0.203325E+10 |
March | 0.147877E+10 | 0.619301E+09 | 0.859473E+09 | 0.109100E+10 | 0.164353E+10 |
April | 0.189411E+10 | 0.836921E+09 | 0.105719E+10 | 0.171141E+10 | 0.115725E+10 |
May | 0.219282E+10 | 0.970003E+09 | 0.122282E+10 | 0.234125E+10 | 0.788510E+09 |
June | 0.237001E+10 | 0.104743E+10 | 0.132258E+10 | 0.285299E+10 | 0.488016E+09 |
July | 0.235169E+10 | 0.103542E+10 | 0.131628E+10 | 0.304805E+10 | 0.342198E+09 |
August | 0.212384E+10 | 0.891472E+09 | 0.123237E+10 | 0.269535E+10 | 0.439940E+09 |
September | 0.171039E+10 | 0.758663E+09 | 0.951727E+09 | 0.194386E+10 | 0.713659E+09 |
October | 0.119933E+10 | 0.496075E+09 | 0.703254E+09 | 0.101660E+10 | 0.120026E+10 |
November | 0.658336E+09 | 0.211187E+09 | 0.447150E+09 | 0.361855E+09 | 0.156565E+10 |
December | 0.547661E+09 | 0.113159E+09 | 0.434502E+09 | 0.119334E+09 | 0.237641E+10 |
Annual Sum or Average | 0.181601E+11 | 0.748541E+10 | 0.106747E+11 | 0.178175E+11 | 0.151370E+11 |
Minimum of Months | 0.547661E+09 | 0.113159E+09 | 0.434502E+09 | 0.119334E+09 | 0.342198E+09 |
Maximum of Months | 0.237001E+10 | 0.104743E+10 | 0.132258E+10 | 0.304805E+10 | 0.238836E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.702325E+09 | 0.226469E+09 | 0.475856E+09 | 0.243231E+09 | 0.238836E+10 |
February | 0.930796E+09 | 0.279309E+09 | 0.651487E+09 | 0.392507E+09 | 0.203325E+10 |
March | 0.147877E+10 | 0.619301E+09 | 0.859473E+09 | 0.109100E+10 | 0.164353E+10 |
April | 0.189411E+10 | 0.836921E+09 | 0.105719E+10 | 0.171141E+10 | 0.115725E+10 |
May | 0.219282E+10 | 0.970003E+09 | 0.122282E+10 | 0.234125E+10 | 0.788510E+09 |
June | 0.237001E+10 | 0.104743E+10 | 0.132258E+10 | 0.285299E+10 | 0.488016E+09 |
July | 0.235169E+10 | 0.103542E+10 | 0.131628E+10 | 0.304805E+10 | 0.342198E+09 |
August | 0.212384E+10 | 0.891472E+09 | 0.123237E+10 | 0.269535E+10 | 0.439940E+09 |
September | 0.171039E+10 | 0.758663E+09 | 0.951727E+09 | 0.194386E+10 | 0.713659E+09 |
October | 0.119933E+10 | 0.496075E+09 | 0.703254E+09 | 0.101660E+10 | 0.120026E+10 |
November | 0.658336E+09 | 0.211187E+09 | 0.447150E+09 | 0.361855E+09 | 0.156565E+10 |
December | 0.547661E+09 | 0.113159E+09 | 0.434502E+09 | 0.119334E+09 | 0.237641E+10 |
Annual Sum or Average | 0.181601E+11 | 0.748541E+10 | 0.106747E+11 | 0.178175E+11 | 0.151370E+11 |
Minimum of Months | 0.547661E+09 | 0.113159E+09 | 0.434502E+09 | 0.119334E+09 | 0.342198E+09 |
Maximum of Months | 0.237001E+10 | 0.104743E+10 | 0.132258E+10 | 0.304805E+10 | 0.238836E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.702312E+09 | 0.226465E+09 | 0.475847E+09 | 0.243227E+09 | 0.238832E+10 |
February | 0.930779E+09 | 0.279304E+09 | 0.651475E+09 | 0.392500E+09 | 0.203321E+10 |
March | 0.147875E+10 | 0.619290E+09 | 0.859457E+09 | 0.109098E+10 | 0.164350E+10 |
April | 0.189408E+10 | 0.836906E+09 | 0.105717E+10 | 0.171137E+10 | 0.115723E+10 |
May | 0.219278E+10 | 0.969985E+09 | 0.122280E+10 | 0.234121E+10 | 0.788496E+09 |
June | 0.236997E+10 | 0.104741E+10 | 0.132256E+10 | 0.285294E+10 | 0.488007E+09 |
July | 0.235165E+10 | 0.103540E+10 | 0.131625E+10 | 0.304800E+10 | 0.342192E+09 |
August | 0.212380E+10 | 0.891455E+09 | 0.123234E+10 | 0.269530E+10 | 0.439932E+09 |
September | 0.171036E+10 | 0.758649E+09 | 0.951709E+09 | 0.194383E+10 | 0.713646E+09 |
October | 0.119931E+10 | 0.496066E+09 | 0.703242E+09 | 0.101658E+10 | 0.120024E+10 |
November | 0.658324E+09 | 0.211183E+09 | 0.447142E+09 | 0.361849E+09 | 0.156562E+10 |
December | 0.547651E+09 | 0.113156E+09 | 0.434494E+09 | 0.119332E+09 | 0.237637E+10 |
Annual Sum or Average | 0.181598E+11 | 0.748527E+10 | 0.106745E+11 | 0.178171E+11 | 0.151368E+11 |
Minimum of Months | 0.547651E+09 | 0.113156E+09 | 0.434494E+09 | 0.119332E+09 | 0.342192E+09 |
Maximum of Months | 0.236997E+10 | 0.104741E+10 | 0.132256E+10 | 0.304800E+10 | 0.238832E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.148526E+10 | 0.866991E+09 | 0.618271E+09 | 0.115371E+10 | 0.196584E+10 |
February | 0.153169E+10 | 0.738566E+09 | 0.793121E+09 | 0.116577E+10 | 0.174039E+10 |
March | 0.206983E+10 | 0.116303E+10 | 0.906806E+09 | 0.196974E+10 | 0.146160E+10 |
April | 0.165885E+10 | 0.662882E+09 | 0.995970E+09 | 0.164489E+10 | 0.113193E+10 |
May | 0.150003E+10 | 0.435672E+09 | 0.106436E+10 | 0.164022E+10 | 0.771099E+09 |
June | 0.141053E+10 | 0.298898E+09 | 0.111163E+10 | 0.173026E+10 | 0.483730E+09 |
July | 0.148792E+10 | 0.361018E+09 | 0.112690E+10 | 0.202232E+10 | 0.346012E+09 |
August | 0.167043E+10 | 0.541596E+09 | 0.112884E+10 | 0.223695E+10 | 0.444778E+09 |
September | 0.187956E+10 | 0.915488E+09 | 0.964077E+09 | 0.232219E+10 | 0.685287E+09 |
October | 0.185841E+10 | 0.106156E+10 | 0.796852E+09 | 0.196382E+10 | 0.108658E+10 |
November | 0.128802E+10 | 0.727133E+09 | 0.560891E+09 | 0.117328E+10 | 0.136359E+10 |
December | 0.124197E+10 | 0.642778E+09 | 0.599196E+09 | 0.901854E+09 | 0.197298E+10 |
Annual Sum or Average | 0.190825E+11 | 0.841561E+10 | 0.106669E+11 | 0.199250E+11 | 0.134538E+11 |
Minimum of Months | 0.124197E+10 | 0.298898E+09 | 0.560891E+09 | 0.901854E+09 | 0.346012E+09 |
Maximum of Months | 0.206983E+10 | 0.116303E+10 | 0.112884E+10 | 0.232219E+10 | 0.197298E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.148526E+10 | 0.866990E+09 | 0.618270E+09 | 0.115371E+10 | 0.196584E+10 |
February | 0.153169E+10 | 0.738565E+09 | 0.793120E+09 | 0.116577E+10 | 0.174039E+10 |
March | 0.206983E+10 | 0.116302E+10 | 0.906806E+09 | 0.196974E+10 | 0.146160E+10 |
April | 0.165885E+10 | 0.662881E+09 | 0.995969E+09 | 0.164489E+10 | 0.113193E+10 |
May | 0.150003E+10 | 0.435672E+09 | 0.106436E+10 | 0.164022E+10 | 0.771099E+09 |
June | 0.141053E+10 | 0.298898E+09 | 0.111163E+10 | 0.173026E+10 | 0.483730E+09 |
July | 0.148792E+10 | 0.361017E+09 | 0.112690E+10 | 0.202232E+10 | 0.346012E+09 |
August | 0.167043E+10 | 0.541596E+09 | 0.112884E+10 | 0.223695E+10 | 0.444778E+09 |
September | 0.187956E+10 | 0.915487E+09 | 0.964076E+09 | 0.232219E+10 | 0.685286E+09 |
October | 0.185841E+10 | 0.106156E+10 | 0.796851E+09 | 0.196382E+10 | 0.108658E+10 |
November | 0.128802E+10 | 0.727132E+09 | 0.560891E+09 | 0.117328E+10 | 0.136359E+10 |
December | 0.124197E+10 | 0.642777E+09 | 0.599195E+09 | 0.901853E+09 | 0.197298E+10 |
Annual Sum or Average | 0.190825E+11 | 0.841560E+10 | 0.106669E+11 | 0.199250E+11 | 0.134538E+11 |
Minimum of Months | 0.124197E+10 | 0.298898E+09 | 0.560891E+09 | 0.901853E+09 | 0.346012E+09 |
Maximum of Months | 0.206983E+10 | 0.116302E+10 | 0.112884E+10 | 0.232219E+10 | 0.197298E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.148526E+10 | 0.866991E+09 | 0.618271E+09 | 0.115371E+10 | 0.196584E+10 |
February | 0.153169E+10 | 0.738566E+09 | 0.793121E+09 | 0.116577E+10 | 0.174039E+10 |
March | 0.206983E+10 | 0.116303E+10 | 0.906806E+09 | 0.196974E+10 | 0.146160E+10 |
April | 0.165885E+10 | 0.662882E+09 | 0.995970E+09 | 0.164489E+10 | 0.113193E+10 |
May | 0.150003E+10 | 0.435672E+09 | 0.106436E+10 | 0.164022E+10 | 0.771099E+09 |
June | 0.141053E+10 | 0.298898E+09 | 0.111163E+10 | 0.173026E+10 | 0.483730E+09 |
July | 0.148792E+10 | 0.361018E+09 | 0.112690E+10 | 0.202232E+10 | 0.346012E+09 |
August | 0.167043E+10 | 0.541596E+09 | 0.112884E+10 | 0.223695E+10 | 0.444778E+09 |
September | 0.187956E+10 | 0.915488E+09 | 0.964077E+09 | 0.232219E+10 | 0.685287E+09 |
October | 0.185841E+10 | 0.106156E+10 | 0.796852E+09 | 0.196382E+10 | 0.108658E+10 |
November | 0.128802E+10 | 0.727133E+09 | 0.560891E+09 | 0.117328E+10 | 0.136359E+10 |
December | 0.124197E+10 | 0.642778E+09 | 0.599196E+09 | 0.901854E+09 | 0.197298E+10 |
Annual Sum or Average | 0.190825E+11 | 0.841561E+10 | 0.106669E+11 | 0.199250E+11 | 0.134538E+11 |
Minimum of Months | 0.124197E+10 | 0.298898E+09 | 0.560891E+09 | 0.901854E+09 | 0.346012E+09 |
Maximum of Months | 0.206983E+10 | 0.116303E+10 | 0.112884E+10 | 0.232219E+10 | 0.197298E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.148526E+10 | 0.866990E+09 | 0.618270E+09 | 0.115371E+10 | 0.196584E+10 |
February | 0.153169E+10 | 0.738565E+09 | 0.793120E+09 | 0.116577E+10 | 0.174039E+10 |
March | 0.206983E+10 | 0.116302E+10 | 0.906806E+09 | 0.196974E+10 | 0.146160E+10 |
April | 0.165885E+10 | 0.662881E+09 | 0.995969E+09 | 0.164489E+10 | 0.113193E+10 |
May | 0.150003E+10 | 0.435672E+09 | 0.106436E+10 | 0.164022E+10 | 0.771099E+09 |
June | 0.141053E+10 | 0.298898E+09 | 0.111163E+10 | 0.173026E+10 | 0.483730E+09 |
July | 0.148792E+10 | 0.361017E+09 | 0.112690E+10 | 0.202232E+10 | 0.346012E+09 |
August | 0.167043E+10 | 0.541596E+09 | 0.112884E+10 | 0.223695E+10 | 0.444778E+09 |
September | 0.187956E+10 | 0.915487E+09 | 0.964076E+09 | 0.232219E+10 | 0.685286E+09 |
October | 0.185841E+10 | 0.106156E+10 | 0.796851E+09 | 0.196382E+10 | 0.108658E+10 |
November | 0.128802E+10 | 0.727132E+09 | 0.560891E+09 | 0.117328E+10 | 0.136359E+10 |
December | 0.124197E+10 | 0.642777E+09 | 0.599195E+09 | 0.901853E+09 | 0.197298E+10 |
Annual Sum or Average | 0.190825E+11 | 0.841560E+10 | 0.106669E+11 | 0.199250E+11 | 0.134538E+11 |
Minimum of Months | 0.124197E+10 | 0.298898E+09 | 0.560891E+09 | 0.901853E+09 | 0.346012E+09 |
Maximum of Months | 0.206983E+10 | 0.116302E+10 | 0.112884E+10 | 0.232219E+10 | 0.197298E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.148520E+10 | 0.866956E+09 | 0.618246E+09 | 0.115367E+10 | 0.196576E+10 |
February | 0.153163E+10 | 0.738536E+09 | 0.793089E+09 | 0.116572E+10 | 0.174032E+10 |
March | 0.206975E+10 | 0.116298E+10 | 0.906770E+09 | 0.196966E+10 | 0.146154E+10 |
April | 0.165878E+10 | 0.662855E+09 | 0.995929E+09 | 0.164482E+10 | 0.113189E+10 |
May | 0.149997E+10 | 0.435655E+09 | 0.106432E+10 | 0.164016E+10 | 0.771068E+09 |
June | 0.141047E+10 | 0.298886E+09 | 0.111159E+10 | 0.173019E+10 | 0.483711E+09 |
July | 0.148786E+10 | 0.361003E+09 | 0.112686E+10 | 0.202224E+10 | 0.345998E+09 |
August | 0.167037E+10 | 0.541575E+09 | 0.112879E+10 | 0.223686E+10 | 0.444760E+09 |
September | 0.187949E+10 | 0.915451E+09 | 0.964038E+09 | 0.232210E+10 | 0.685259E+09 |
October | 0.185834E+10 | 0.106152E+10 | 0.796820E+09 | 0.196374E+10 | 0.108654E+10 |
November | 0.128797E+10 | 0.727103E+09 | 0.560868E+09 | 0.117324E+10 | 0.136353E+10 |
December | 0.124192E+10 | 0.642752E+09 | 0.599172E+09 | 0.901818E+09 | 0.197290E+10 |
Annual Sum or Average | 0.190818E+11 | 0.841527E+10 | 0.106665E+11 | 0.199242E+11 | 0.134533E+11 |
Minimum of Months | 0.124192E+10 | 0.298886E+09 | 0.560868E+09 | 0.901818E+09 | 0.345998E+09 |
Maximum of Months | 0.206975E+10 | 0.116298E+10 | 0.112879E+10 | 0.232210E+10 | 0.197290E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.602582E+09 | 0.141463E+09 | 0.461119E+09 | 0.143841E+09 | 0.257288E+10 |
February | 0.882108E+09 | 0.226708E+09 | 0.655400E+09 | 0.319674E+09 | 0.223250E+10 |
March | 0.153068E+10 | 0.655400E+09 | 0.875277E+09 | 0.111552E+10 | 0.186537E+10 |
April | 0.181365E+10 | 0.743671E+09 | 0.106998E+10 | 0.157360E+10 | 0.139491E+10 |
May | 0.221081E+10 | 0.999143E+09 | 0.121167E+10 | 0.235275E+10 | 0.904616E+09 |
June | 0.258136E+10 | 0.121417E+10 | 0.136720E+10 | 0.311240E+10 | 0.599206E+09 |
July | 0.238476E+10 | 0.104556E+10 | 0.133920E+10 | 0.305816E+10 | 0.447715E+09 |
August | 0.215688E+10 | 0.917125E+09 | 0.123975E+10 | 0.270723E+10 | 0.576763E+09 |
September | 0.163918E+10 | 0.707890E+09 | 0.931289E+09 | 0.184580E+10 | 0.814501E+09 |
October | 0.109801E+10 | 0.386783E+09 | 0.711230E+09 | 0.874370E+09 | 0.137667E+10 |
November | 0.629697E+09 | 0.181456E+09 | 0.448241E+09 | 0.309629E+09 | 0.180681E+10 |
December | 0.564088E+09 | 0.122908E+09 | 0.441179E+09 | 0.124470E+09 | 0.270496E+10 |
Annual Sum or Average | 0.180938E+11 | 0.734228E+10 | 0.107515E+11 | 0.175374E+11 | 0.172969E+11 |
Minimum of Months | 0.564088E+09 | 0.122908E+09 | 0.441179E+09 | 0.124470E+09 | 0.447715E+09 |
Maximum of Months | 0.258136E+10 | 0.121417E+10 | 0.136720E+10 | 0.311240E+10 | 0.270496E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.602582E+09 | 0.141463E+09 | 0.461119E+09 | 0.143841E+09 | 0.257288E+10 |
February | 0.882108E+09 | 0.226708E+09 | 0.655400E+09 | 0.319674E+09 | 0.223250E+10 |
March | 0.153068E+10 | 0.655400E+09 | 0.875277E+09 | 0.111552E+10 | 0.186537E+10 |
April | 0.181365E+10 | 0.743671E+09 | 0.106998E+10 | 0.157360E+10 | 0.139491E+10 |
May | 0.221081E+10 | 0.999143E+09 | 0.121167E+10 | 0.235275E+10 | 0.904616E+09 |
June | 0.258136E+10 | 0.121417E+10 | 0.136720E+10 | 0.311240E+10 | 0.599206E+09 |
July | 0.238476E+10 | 0.104556E+10 | 0.133920E+10 | 0.305816E+10 | 0.447715E+09 |
August | 0.215688E+10 | 0.917125E+09 | 0.123975E+10 | 0.270723E+10 | 0.576763E+09 |
September | 0.163918E+10 | 0.707890E+09 | 0.931289E+09 | 0.184580E+10 | 0.814501E+09 |
October | 0.109801E+10 | 0.386783E+09 | 0.711230E+09 | 0.874370E+09 | 0.137667E+10 |
November | 0.629697E+09 | 0.181456E+09 | 0.448241E+09 | 0.309629E+09 | 0.180681E+10 |
December | 0.564088E+09 | 0.122908E+09 | 0.441179E+09 | 0.124470E+09 | 0.270496E+10 |
Annual Sum or Average | 0.180938E+11 | 0.734228E+10 | 0.107515E+11 | 0.175374E+11 | 0.172969E+11 |
Minimum of Months | 0.564088E+09 | 0.122908E+09 | 0.441179E+09 | 0.124470E+09 | 0.447715E+09 |
Maximum of Months | 0.258136E+10 | 0.121417E+10 | 0.136720E+10 | 0.311240E+10 | 0.270496E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.602571E+09 | 0.141460E+09 | 0.461111E+09 | 0.143838E+09 | 0.257284E+10 |
February | 0.882092E+09 | 0.226704E+09 | 0.655388E+09 | 0.319668E+09 | 0.223246E+10 |
March | 0.153065E+10 | 0.655388E+09 | 0.875261E+09 | 0.111550E+10 | 0.186533E+10 |
April | 0.181362E+10 | 0.743657E+09 | 0.106996E+10 | 0.157357E+10 | 0.139489E+10 |
May | 0.221077E+10 | 0.999124E+09 | 0.121164E+10 | 0.235271E+10 | 0.904600E+09 |
June | 0.258131E+10 | 0.121414E+10 | 0.136717E+10 | 0.311235E+10 | 0.599195E+09 |
July | 0.238472E+10 | 0.104554E+10 | 0.133918E+10 | 0.305811E+10 | 0.447707E+09 |
August | 0.215684E+10 | 0.917108E+09 | 0.123973E+10 | 0.270718E+10 | 0.576752E+09 |
September | 0.163915E+10 | 0.707877E+09 | 0.931272E+09 | 0.184577E+10 | 0.814486E+09 |
October | 0.109799E+10 | 0.386776E+09 | 0.711217E+09 | 0.874354E+09 | 0.137664E+10 |
November | 0.629686E+09 | 0.181453E+09 | 0.448233E+09 | 0.309623E+09 | 0.180678E+10 |
December | 0.564077E+09 | 0.122906E+09 | 0.441171E+09 | 0.124467E+09 | 0.270492E+10 |
Annual Sum or Average | 0.180935E+11 | 0.734214E+10 | 0.107513E+11 | 0.175371E+11 | 0.172966E+11 |
Minimum of Months | 0.564077E+09 | 0.122906E+09 | 0.441171E+09 | 0.124467E+09 | 0.447707E+09 |
Maximum of Months | 0.258131E+10 | 0.121414E+10 | 0.136717E+10 | 0.311235E+10 | 0.270492E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172702E+10 | 0.00 | 0.172702E+10 | 10960840.69 | 0.108135E+11 |
February | 0.237669E+10 | 0.00 | 0.237669E+10 | 0.106799E+09 | 0.917497E+10 |
March | 0.319106E+10 | 0.00 | 0.319106E+10 | 0.931364E+09 | 0.742980E+10 |
April | 0.393491E+10 | 15701838.22 | 0.391920E+10 | 0.197845E+10 | 0.513006E+10 |
May | 0.472457E+10 | 0.200349E+09 | 0.452422E+10 | 0.357240E+10 | 0.336714E+10 |
June | 0.549936E+10 | 0.468133E+09 | 0.503122E+10 | 0.582543E+10 | 0.209844E+10 |
July | 0.527143E+10 | 0.340283E+09 | 0.493115E+10 | 0.650533E+10 | 0.151079E+10 |
August | 0.456125E+10 | 69389531.73 | 0.449186E+10 | 0.531118E+10 | 0.200261E+10 |
September | 0.335924E+10 | 697903.71 | 0.335854E+10 | 0.297742E+10 | 0.316319E+10 |
October | 0.259488E+10 | 0.00 | 0.259488E+10 | 0.117621E+10 | 0.525458E+10 |
November | 0.168745E+10 | 0.00 | 0.168745E+10 | 0.309349E+09 | 0.665394E+10 |
December | 0.161644E+10 | 0.00 | 0.161644E+10 | 17756882.41 | 0.103696E+11 |
Annual Sum or Average | 0.405443E+11 | 0.109455E+10 | 0.394497E+11 | 0.287227E+11 | 0.669686E+11 |
Minimum of Months | 0.161644E+10 | 0.00 | 0.161644E+10 | 10960840.69 | 0.151079E+10 |
Maximum of Months | 0.549936E+10 | 0.468133E+09 | 0.503122E+10 | 0.650533E+10 | 0.108135E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.210695E+10 | 0.679399E+09 | 0.142755E+10 | 0.777051E+09 | 0.656924E+10 |
February | 0.279236E+10 | 0.837918E+09 | 0.195444E+10 | 0.125230E+10 | 0.563517E+10 |
March | 0.443628E+10 | 0.185789E+10 | 0.257839E+10 | 0.334120E+10 | 0.457842E+10 |
April | 0.568228E+10 | 0.251074E+10 | 0.317154E+10 | 0.518362E+10 | 0.323835E+10 |
May | 0.657840E+10 | 0.290998E+10 | 0.366842E+10 | 0.700524E+10 | 0.226423E+10 |
June | 0.710997E+10 | 0.314226E+10 | 0.396771E+10 | 0.852336E+10 | 0.141448E+10 |
July | 0.705501E+10 | 0.310622E+10 | 0.394879E+10 | 0.911837E+10 | 0.101205E+10 |
August | 0.637145E+10 | 0.267439E+10 | 0.369706E+10 | 0.805071E+10 | 0.132088E+10 |
September | 0.513112E+10 | 0.227597E+10 | 0.285515E+10 | 0.583390E+10 | 0.201062E+10 |
October | 0.359795E+10 | 0.148821E+10 | 0.210974E+10 | 0.312230E+10 | 0.329860E+10 |
November | 0.197499E+10 | 0.633554E+09 | 0.134144E+10 | 0.116374E+10 | 0.422251E+10 |
December | 0.164297E+10 | 0.339472E+09 | 0.130349E+10 | 0.398078E+09 | 0.650356E+10 |
Annual Sum or Average | 0.544797E+11 | 0.224560E+11 | 0.320237E+11 | 0.537699E+11 | 0.420681E+11 |
Minimum of Months | 0.164297E+10 | 0.339472E+09 | 0.130349E+10 | 0.398078E+09 | 0.101205E+10 |
Maximum of Months | 0.710997E+10 | 0.314226E+10 | 0.396771E+10 | 0.911837E+10 | 0.656924E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.742622E+10 | 0.433490E+10 | 0.309132E+10 | 0.579607E+10 | 0.938589E+10 |
February | 0.765834E+10 | 0.369279E+10 | 0.396556E+10 | 0.585722E+10 | 0.833912E+10 |
March | 0.103490E+11 | 0.581506E+10 | 0.453398E+10 | 0.981709E+10 | 0.702920E+10 |
April | 0.829416E+10 | 0.331437E+10 | 0.497979E+10 | 0.823488E+10 | 0.538635E+10 |
May | 0.750006E+10 | 0.217833E+10 | 0.532173E+10 | 0.815485E+10 | 0.374942E+10 |
June | 0.705256E+10 | 0.149447E+10 | 0.555809E+10 | 0.863267E+10 | 0.232113E+10 |
July | 0.743950E+10 | 0.180507E+10 | 0.563443E+10 | 0.101141E+11 | 0.166071E+10 |
August | 0.835207E+10 | 0.270795E+10 | 0.564412E+10 | 0.111642E+11 | 0.216201E+10 |
September | 0.939771E+10 | 0.457738E+10 | 0.482033E+10 | 0.115501E+11 | 0.332025E+10 |
October | 0.929196E+10 | 0.530775E+10 | 0.398421E+10 | 0.978097E+10 | 0.521659E+10 |
November | 0.644004E+10 | 0.363562E+10 | 0.280442E+10 | 0.589395E+10 | 0.643078E+10 |
December | 0.620979E+10 | 0.321385E+10 | 0.299594E+10 | 0.456489E+10 | 0.927549E+10 |
Annual Sum or Average | 0.954114E+11 | 0.420775E+11 | 0.533339E+11 | 0.995611E+11 | 0.642770E+11 |
Minimum of Months | 0.620979E+10 | 0.149447E+10 | 0.280442E+10 | 0.456489E+10 | 0.166071E+10 |
Maximum of Months | 0.103490E+11 | 0.581506E+10 | 0.564412E+10 | 0.115501E+11 | 0.938589E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.180773E+10 | 0.424384E+09 | 0.138334E+10 | 0.465906E+09 | 0.695035E+10 |
February | 0.264630E+10 | 0.680118E+09 | 0.196618E+10 | 0.105441E+10 | 0.594385E+10 |
March | 0.459199E+10 | 0.196618E+10 | 0.262580E+10 | 0.352117E+10 | 0.483438E+10 |
April | 0.544090E+10 | 0.223099E+10 | 0.320991E+10 | 0.494434E+10 | 0.352613E+10 |
May | 0.663236E+10 | 0.299740E+10 | 0.363496E+10 | 0.711420E+10 | 0.251137E+10 |
June | 0.774401E+10 | 0.364246E+10 | 0.410155E+10 | 0.937975E+10 | 0.164045E+10 |
July | 0.715422E+10 | 0.313665E+10 | 0.401756E+10 | 0.925632E+10 | 0.121045E+10 |
August | 0.647057E+10 | 0.275135E+10 | 0.371922E+10 | 0.823425E+10 | 0.151558E+10 |
September | 0.491748E+10 | 0.212365E+10 | 0.279384E+10 | 0.560105E+10 | 0.220685E+10 |
October | 0.329401E+10 | 0.116034E+10 | 0.213367E+10 | 0.279402E+10 | 0.352203E+10 |
November | 0.188907E+10 | 0.544363E+09 | 0.134471E+10 | 0.105883E+10 | 0.442400E+10 |
December | 0.169225E+10 | 0.368721E+09 | 0.132352E+10 | 0.440842E+09 | 0.676306E+10 |
Annual Sum or Average | 0.542809E+11 | 0.220266E+11 | 0.322543E+11 | 0.538651E+11 | 0.450485E+11 |
Minimum of Months | 0.169225E+10 | 0.368721E+09 | 0.132352E+10 | 0.440842E+09 | 0.121045E+10 |
Maximum of Months | 0.774401E+10 | 0.364246E+10 | 0.410155E+10 | 0.937975E+10 | 0.695035E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.172702E+10 | 0.00 | 0.172702E+10 | 27999835.20 | 0.104131E+11 |
February | 0.237669E+10 | 0.00 | 0.237669E+10 | 0.145416E+09 | 0.880464E+10 |
March | 0.319106E+10 | 0.00 | 0.319106E+10 | 0.100814E+10 | 0.698175E+10 |
April | 0.393491E+10 | 15701838.22 | 0.391920E+10 | 0.210666E+10 | 0.477759E+10 |
May | 0.472457E+10 | 0.200349E+09 | 0.452422E+10 | 0.364130E+10 | 0.320967E+10 |
June | 0.549936E+10 | 0.468133E+09 | 0.503122E+10 | 0.580161E+10 | 0.206773E+10 |
July | 0.527143E+10 | 0.340283E+09 | 0.493115E+10 | 0.644598E+10 | 0.151441E+10 |
August | 0.456125E+10 | 69389531.73 | 0.449186E+10 | 0.528060E+10 | 0.197950E+10 |
September | 0.335924E+10 | 697903.71 | 0.335854E+10 | 0.302115E+10 | 0.300021E+10 |
October | 0.259488E+10 | 0.00 | 0.259488E+10 | 0.131127E+10 | 0.477509E+10 |
November | 0.168745E+10 | 0.00 | 0.168745E+10 | 0.389067E+09 | 0.605388E+10 |
December | 0.161644E+10 | 0.00 | 0.161644E+10 | 29726024.25 | 0.985317E+10 |
Annual Sum or Average | 0.405443E+11 | 0.109455E+10 | 0.394497E+11 | 0.292089E+11 | 0.634308E+11 |
Minimum of Months | 0.161644E+10 | 0.00 | 0.161644E+10 | 27999835.20 | 0.151441E+10 |
Maximum of Months | 0.549936E+10 | 0.468133E+09 | 0.503122E+10 | 0.644598E+10 | 0.104131E+11 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.210695E+10 | 0.679399E+09 | 0.142755E+10 | 0.808821E+09 | 0.631742E+10 |
February | 0.279236E+10 | 0.837918E+09 | 0.195444E+10 | 0.130335E+10 | 0.541069E+10 |
March | 0.443628E+10 | 0.185789E+10 | 0.257839E+10 | 0.341697E+10 | 0.430677E+10 |
April | 0.568228E+10 | 0.251074E+10 | 0.317154E+10 | 0.525955E+10 | 0.305190E+10 |
May | 0.657840E+10 | 0.290998E+10 | 0.366842E+10 | 0.702088E+10 | 0.218234E+10 |
June | 0.710997E+10 | 0.314226E+10 | 0.396771E+10 | 0.849327E+10 | 0.140240E+10 |
July | 0.705501E+10 | 0.310622E+10 | 0.394879E+10 | 0.907232E+10 | 0.101915E+10 |
August | 0.637145E+10 | 0.267439E+10 | 0.369706E+10 | 0.801940E+10 | 0.131378E+10 |
September | 0.513112E+10 | 0.227597E+10 | 0.285515E+10 | 0.584935E+10 | 0.193145E+10 |
October | 0.359795E+10 | 0.148821E+10 | 0.210974E+10 | 0.321692E+10 | 0.303334E+10 |
November | 0.197499E+10 | 0.633554E+09 | 0.134144E+10 | 0.123581E+10 | 0.387014E+10 |
December | 0.164297E+10 | 0.339472E+09 | 0.130349E+10 | 0.423411E+09 | 0.618510E+10 |
Annual Sum or Average | 0.544797E+11 | 0.224560E+11 | 0.320237E+11 | 0.541200E+11 | 0.400245E+11 |
Minimum of Months | 0.164297E+10 | 0.339472E+09 | 0.130349E+10 | 0.423411E+09 | 0.101915E+10 |
Maximum of Months | 0.710997E+10 | 0.314226E+10 | 0.396771E+10 | 0.907232E+10 | 0.631742E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.742622E+10 | 0.433490E+10 | 0.309132E+10 | 0.588345E+10 | 0.896387E+10 |
February | 0.765834E+10 | 0.369279E+10 | 0.396556E+10 | 0.595575E+10 | 0.796568E+10 |
March | 0.103490E+11 | 0.581506E+10 | 0.453398E+10 | 0.993772E+10 | 0.658647E+10 |
April | 0.829416E+10 | 0.331437E+10 | 0.497979E+10 | 0.833906E+10 | 0.505007E+10 |
May | 0.750006E+10 | 0.217833E+10 | 0.532173E+10 | 0.818506E+10 | 0.358289E+10 |
June | 0.705256E+10 | 0.149447E+10 | 0.555809E+10 | 0.859776E+10 | 0.227832E+10 |
July | 0.743950E+10 | 0.180507E+10 | 0.563443E+10 | 0.100516E+11 | 0.165821E+10 |
August | 0.835207E+10 | 0.270795E+10 | 0.564412E+10 | 0.111200E+11 | 0.213515E+10 |
September | 0.939771E+10 | 0.457738E+10 | 0.482033E+10 | 0.115650E+11 | 0.317658E+10 |
October | 0.929196E+10 | 0.530775E+10 | 0.398421E+10 | 0.991378E+10 | 0.479422E+10 |
November | 0.644004E+10 | 0.363562E+10 | 0.280442E+10 | 0.602744E+10 | 0.587844E+10 |
December | 0.620979E+10 | 0.321385E+10 | 0.299594E+10 | 0.466399E+10 | 0.877381E+10 |
Annual Sum or Average | 0.954114E+11 | 0.420775E+11 | 0.533339E+11 | 0.100241E+12 | 0.608437E+11 |
Minimum of Months | 0.620979E+10 | 0.149447E+10 | 0.280442E+10 | 0.466399E+10 | 0.165821E+10 |
Maximum of Months | 0.103490E+11 | 0.581506E+10 | 0.564412E+10 | 0.115650E+11 | 0.896387E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.180773E+10 | 0.424384E+09 | 0.138334E+10 | 0.484802E+09 | 0.669090E+10 |
February | 0.264630E+10 | 0.680118E+09 | 0.196618E+10 | 0.108367E+10 | 0.572462E+10 |
March | 0.459199E+10 | 0.196618E+10 | 0.262580E+10 | 0.356249E+10 | 0.457913E+10 |
April | 0.544090E+10 | 0.223099E+10 | 0.320991E+10 | 0.499824E+10 | 0.333285E+10 |
May | 0.663236E+10 | 0.299740E+10 | 0.363496E+10 | 0.712983E+10 | 0.241219E+10 |
June | 0.774401E+10 | 0.364246E+10 | 0.410155E+10 | 0.934659E+10 | 0.161449E+10 |
July | 0.715422E+10 | 0.313665E+10 | 0.401756E+10 | 0.921120E+10 | 0.120560E+10 |
August | 0.647057E+10 | 0.275135E+10 | 0.371922E+10 | 0.820579E+10 | 0.149792E+10 |
September | 0.491748E+10 | 0.212365E+10 | 0.279384E+10 | 0.561658E+10 | 0.211708E+10 |
October | 0.329401E+10 | 0.116034E+10 | 0.213367E+10 | 0.285858E+10 | 0.327318E+10 |
November | 0.188907E+10 | 0.544363E+09 | 0.134471E+10 | 0.110615E+10 | 0.411459E+10 |
December | 0.169225E+10 | 0.368721E+09 | 0.132352E+10 | 0.460218E+09 | 0.646635E+10 |
Annual Sum or Average | 0.542809E+11 | 0.220266E+11 | 0.322543E+11 | 0.540641E+11 | 0.430289E+11 |
Minimum of Months | 0.169225E+10 | 0.368721E+09 | 0.132352E+10 | 0.460218E+09 | 0.120560E+10 |
Maximum of Months | 0.774401E+10 | 0.364246E+10 | 0.410155E+10 | 0.934659E+10 | 0.669090E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.03 | 4438.06 | 644.80 | 0.00 | 644.80 | 0.00 | 0.00 |
February | 20.33 | 4177.98 | 982.43 | 0.00 | 982.43 | 0.00 | 0.00 |
March | 296.26 | 3083.27 | 1191.41 | 0.00 | 1191.41 | 0.00 | 0.00 |
April | 679.71 | 2219.05 | 1518.10 | 6.06 | 1512.04 | 0.00 | 0.00 |
May | 1299.89 | 1334.06 | 1763.96 | 74.80 | 1689.16 | 0.00 | 0.00 |
June | 2223.93 | 854.66 | 2121.67 | 180.61 | 1941.07 | 0.00 | 0.00 |
July | 2393.90 | 602.87 | 1968.13 | 127.05 | 1841.09 | 0.00 | 0.00 |
August | 1950.72 | 794.31 | 1702.98 | 25.91 | 1677.08 | 0.00 | 0.00 |
September | 1116.78 | 1323.64 | 1296.01 | 0.27 | 1295.74 | 0.00 | 0.00 |
October | 376.64 | 2209.32 | 968.82 | 0.00 | 968.82 | 0.00 | 0.00 |
November | 79.51 | 2975.77 | 651.02 | 0.00 | 651.02 | 0.00 | 0.00 |
December | 2.46 | 4371.89 | 603.51 | 0.00 | 603.51 | 0.00 | 0.00 |
Annual Sum or Average | 875.30 | 2356.23 | 1285.66 | 34.71 | 1250.95 | 0.00 | 0.00 |
Minimum of Months | 0.03 | 602.87 | 603.51 | 0.00 | 603.51 | 0.00 | 0.00 |
Maximum of Months | 2393.90 | 4438.06 | 2121.67 | 180.61 | 1941.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 272.43 | 2675.12 | 786.65 | 253.66 | 532.99 | 0.00 | 0.00 |
February | 486.74 | 2521.37 | 1154.25 | 346.36 | 807.89 | 0.00 | 0.00 |
March | 1221.99 | 1840.86 | 1656.32 | 693.66 | 962.67 | 0.00 | 0.00 |
April | 1980.78 | 1339.41 | 2192.25 | 968.65 | 1223.59 | 0.00 | 0.00 |
May | 2622.35 | 883.18 | 2456.10 | 1086.47 | 1369.64 | 0.00 | 0.00 |
June | 3302.06 | 564.83 | 2743.05 | 1212.29 | 1530.76 | 0.00 | 0.00 |
July | 3414.02 | 383.28 | 2634.05 | 1159.74 | 1474.31 | 0.00 | 0.00 |
August | 3018.97 | 492.76 | 2378.84 | 998.51 | 1380.33 | 0.00 | 0.00 |
September | 2249.83 | 825.99 | 1979.61 | 878.08 | 1101.53 | 0.00 | 0.00 |
October | 1138.66 | 1344.37 | 1343.33 | 555.64 | 787.69 | 0.00 | 0.00 |
November | 418.81 | 1812.08 | 761.96 | 244.43 | 517.53 | 0.00 | 0.00 |
December | 133.66 | 2661.73 | 613.42 | 126.74 | 486.67 | 0.00 | 0.00 |
Annual Sum or Average | 1694.95 | 1439.97 | 1727.55 | 712.08 | 1015.47 | 0.00 | 0.00 |
Minimum of Months | 133.66 | 383.28 | 613.42 | 126.74 | 486.67 | 0.00 | 0.00 |
Maximum of Months | 3414.02 | 2675.12 | 2743.05 | 1212.29 | 1530.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2153.72 | 3669.77 | 2772.64 | 1618.47 | 1154.17 | 0.00 | 0.00 |
February | 2409.39 | 3597.01 | 3165.66 | 1526.45 | 1639.21 | 0.00 | 0.00 |
March | 3677.05 | 2728.46 | 3863.90 | 2171.10 | 1692.80 | 0.00 | 0.00 |
April | 3172.99 | 2183.49 | 3199.92 | 1278.70 | 1921.22 | 0.00 | 0.00 |
May | 3061.92 | 1439.46 | 2800.21 | 813.30 | 1986.91 | 0.00 | 0.00 |
June | 3337.67 | 933.11 | 2720.90 | 576.57 | 2144.33 | 0.00 | 0.00 |
July | 3775.20 | 645.93 | 2777.60 | 673.94 | 2103.66 | 0.00 | 0.00 |
August | 4175.87 | 830.30 | 3118.32 | 1011.04 | 2107.28 | 0.00 | 0.00 |
September | 4479.50 | 1321.92 | 3625.67 | 1765.97 | 1859.70 | 0.00 | 0.00 |
October | 3666.00 | 2028.39 | 3469.23 | 1981.69 | 1487.54 | 0.00 | 0.00 |
November | 2263.26 | 2630.35 | 2484.59 | 1402.64 | 1081.96 | 0.00 | 0.00 |
December | 1683.55 | 3683.09 | 2318.48 | 1199.92 | 1118.56 | 0.00 | 0.00 |
Annual Sum or Average | 3159.06 | 2133.07 | 3025.49 | 1334.27 | 1691.21 | 0.00 | 0.00 |
Minimum of Months | 1683.55 | 645.93 | 2318.48 | 576.57 | 1081.96 | 0.00 | 0.00 |
Maximum of Months | 4479.50 | 3683.09 | 3863.90 | 2171.10 | 2144.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 161.11 | 2881.80 | 674.93 | 158.45 | 516.48 | 0.00 | 0.00 |
February | 396.42 | 2768.46 | 1093.88 | 281.13 | 812.74 | 0.00 | 0.00 |
March | 1249.46 | 2089.33 | 1714.46 | 734.09 | 980.37 | 0.00 | 0.00 |
April | 1821.28 | 1614.47 | 2099.12 | 860.72 | 1238.40 | 0.00 | 0.00 |
May | 2635.24 | 1013.23 | 2476.25 | 1119.10 | 1357.14 | 0.00 | 0.00 |
June | 3602.30 | 693.52 | 2987.67 | 1405.28 | 1582.39 | 0.00 | 0.00 |
July | 3425.34 | 501.47 | 2671.09 | 1171.10 | 1499.99 | 0.00 | 0.00 |
August | 3032.27 | 646.01 | 2415.84 | 1027.24 | 1388.60 | 0.00 | 0.00 |
September | 2136.33 | 942.70 | 1897.19 | 819.31 | 1077.87 | 0.00 | 0.00 |
October | 979.35 | 1541.96 | 1229.85 | 433.22 | 796.62 | 0.00 | 0.00 |
November | 358.36 | 2091.20 | 728.81 | 210.02 | 518.79 | 0.00 | 0.00 |
December | 139.41 | 3029.74 | 631.81 | 137.67 | 494.15 | 0.00 | 0.00 |
Annual Sum or Average | 1668.32 | 1645.43 | 1721.24 | 698.46 | 1022.78 | 0.00 | 0.00 |
Minimum of Months | 139.41 | 501.47 | 631.81 | 137.67 | 494.15 | 0.00 | 0.00 |
Maximum of Months | 3602.30 | 3029.74 | 2987.67 | 1405.28 | 1582.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4.09 | 4037.30 | 644.80 | 0.00 | 644.80 | 0.00 | 0.00 |
February | 44.15 | 3792.56 | 982.43 | 0.00 | 982.43 | 0.00 | 0.00 |
March | 347.73 | 2773.97 | 1191.41 | 0.00 | 1191.41 | 0.00 | 0.00 |
April | 763.29 | 1979.19 | 1518.10 | 6.06 | 1512.04 | 0.00 | 0.00 |
May | 1333.78 | 1257.15 | 1763.95 | 74.80 | 1689.15 | 0.00 | 0.00 |
June | 2247.47 | 809.58 | 2121.66 | 180.61 | 1941.06 | 0.00 | 0.00 |
July | 2428.81 | 564.06 | 1968.13 | 127.05 | 1841.08 | 0.00 | 0.00 |
August | 1982.97 | 747.69 | 1702.98 | 25.91 | 1677.07 | 0.00 | 0.00 |
September | 1148.70 | 1220.37 | 1296.00 | 0.27 | 1295.73 | 0.00 | 0.00 |
October | 439.15 | 1961.83 | 968.82 | 0.00 | 968.82 | 0.00 | 0.00 |
November | 119.35 | 2567.11 | 651.02 | 0.00 | 651.02 | 0.00 | 0.00 |
December | 6.63 | 3871.56 | 603.51 | 0.00 | 603.51 | 0.00 | 0.00 |
Annual Sum or Average | 910.79 | 2123.56 | 1285.65 | 34.71 | 1250.94 | 0.00 | 0.00 |
Minimum of Months | 4.09 | 564.06 | 603.51 | 0.00 | 603.51 | 0.00 | 0.00 |
Maximum of Months | 2428.81 | 4037.30 | 2121.66 | 180.61 | 1941.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 290.12 | 2452.67 | 786.65 | 253.66 | 532.99 | 0.00 | 0.00 |
February | 517.65 | 2329.35 | 1154.25 | 346.36 | 807.89 | 0.00 | 0.00 |
March | 1247.46 | 1709.39 | 1656.32 | 693.65 | 962.66 | 0.00 | 0.00 |
April | 1999.85 | 1249.36 | 2192.24 | 968.65 | 1223.59 | 0.00 | 0.00 |
May | 2615.46 | 845.37 | 2456.09 | 1086.46 | 1369.63 | 0.00 | 0.00 |
June | 3288.33 | 545.71 | 2743.04 | 1212.29 | 1530.75 | 0.00 | 0.00 |
July | 3404.41 | 377.86 | 2634.04 | 1159.73 | 1474.31 | 0.00 | 0.00 |
August | 3005.79 | 493.16 | 2378.83 | 998.50 | 1380.33 | 0.00 | 0.00 |
September | 2250.73 | 775.70 | 1979.60 | 878.07 | 1101.52 | 0.00 | 0.00 |
October | 1165.73 | 1231.56 | 1343.32 | 555.63 | 787.69 | 0.00 | 0.00 |
November | 448.97 | 1629.05 | 761.96 | 244.43 | 517.53 | 0.00 | 0.00 |
December | 148.63 | 2428.15 | 613.41 | 126.74 | 486.67 | 0.00 | 0.00 |
Annual Sum or Average | 1705.03 | 1333.97 | 1727.54 | 712.07 | 1015.47 | 0.00 | 0.00 |
Minimum of Months | 148.63 | 377.86 | 613.41 | 126.74 | 486.67 | 0.00 | 0.00 |
Maximum of Months | 3404.41 | 2452.67 | 2743.04 | 1212.29 | 1530.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2164.01 | 3504.29 | 2772.63 | 1618.47 | 1154.16 | 0.00 | 0.00 |
February | 2421.14 | 3447.06 | 3165.65 | 1526.45 | 1639.20 | 0.00 | 0.00 |
March | 3665.28 | 2624.40 | 3863.89 | 2171.09 | 1692.79 | 0.00 | 0.00 |
April | 3177.04 | 2078.07 | 3199.91 | 1278.69 | 1921.21 | 0.00 | 0.00 |
May | 3044.67 | 1399.87 | 2800.20 | 813.30 | 1986.91 | 0.00 | 0.00 |
June | 3330.51 | 895.50 | 2720.89 | 576.57 | 2144.32 | 0.00 | 0.00 |
July | 3776.19 | 620.04 | 2777.59 | 673.93 | 2103.66 | 0.00 | 0.00 |
August | 4168.23 | 807.20 | 3118.30 | 1011.03 | 2107.27 | 0.00 | 0.00 |
September | 4456.07 | 1280.96 | 3625.66 | 1765.97 | 1859.69 | 0.00 | 0.00 |
October | 3651.80 | 1947.65 | 3469.22 | 1981.69 | 1487.53 | 0.00 | 0.00 |
November | 2273.90 | 2481.01 | 2484.58 | 1402.63 | 1081.95 | 0.00 | 0.00 |
December | 1704.34 | 3463.07 | 2318.47 | 1199.91 | 1118.56 | 0.00 | 0.00 |
Annual Sum or Average | 3157.06 | 2038.21 | 3025.48 | 1334.27 | 1691.21 | 0.00 | 0.00 |
Minimum of Months | 1704.34 | 620.04 | 2318.47 | 576.57 | 1081.95 | 0.00 | 0.00 |
Maximum of Months | 4456.07 | 3504.29 | 3863.89 | 2171.09 | 2144.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 173.95 | 2594.96 | 674.93 | 158.45 | 516.48 | 0.00 | 0.00 |
February | 435.85 | 2456.95 | 1093.87 | 281.13 | 812.74 | 0.00 | 0.00 |
March | 1314.65 | 1804.95 | 1714.45 | 734.09 | 980.36 | 0.00 | 0.00 |
April | 1907.54 | 1360.39 | 2099.11 | 860.72 | 1238.39 | 0.00 | 0.00 |
May | 2656.14 | 937.64 | 2476.24 | 1119.10 | 1357.14 | 0.00 | 0.00 |
June | 3618.73 | 632.89 | 2987.66 | 1405.27 | 1582.39 | 0.00 | 0.00 |
July | 3455.91 | 451.93 | 2671.08 | 1171.09 | 1499.99 | 0.00 | 0.00 |
August | 3074.32 | 565.85 | 2415.83 | 1027.24 | 1388.60 | 0.00 | 0.00 |
September | 2160.90 | 851.41 | 1897.18 | 819.31 | 1077.87 | 0.00 | 0.00 |
October | 1043.17 | 1314.97 | 1229.84 | 433.22 | 796.62 | 0.00 | 0.00 |
November | 408.50 | 1706.79 | 728.81 | 210.02 | 518.79 | 0.00 | 0.00 |
December | 164.59 | 2525.04 | 631.81 | 137.66 | 494.15 | 0.00 | 0.00 |
Annual Sum or Average | 1708.05 | 1428.48 | 1721.24 | 698.46 | 1022.78 | 0.00 | 0.00 |
Minimum of Months | 164.59 | 451.93 | 631.81 | 137.66 | 494.15 | 0.00 | 0.00 |
Maximum of Months | 3618.73 | 2594.96 | 2987.66 | 1405.27 | 1582.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 10.45 | 3887.82 | 644.80 | 0.00 | 644.80 | 0.00 | 0.00 |
February | 60.11 | 3639.48 | 982.43 | 0.00 | 982.43 | 0.00 | 0.00 |
March | 376.39 | 2606.69 | 1191.41 | 0.00 | 1191.41 | 0.00 | 0.00 |
April | 812.75 | 1843.20 | 1518.10 | 6.06 | 1512.04 | 0.00 | 0.00 |
May | 1359.51 | 1198.35 | 1763.95 | 74.80 | 1689.15 | 0.00 | 0.00 |
June | 2238.27 | 797.74 | 2121.66 | 180.61 | 1941.06 | 0.00 | 0.00 |
July | 2406.65 | 565.42 | 1968.13 | 127.05 | 1841.08 | 0.00 | 0.00 |
August | 1971.55 | 739.06 | 1702.98 | 25.91 | 1677.07 | 0.00 | 0.00 |
September | 1165.57 | 1157.49 | 1296.00 | 0.27 | 1295.73 | 0.00 | 0.00 |
October | 489.57 | 1782.81 | 968.82 | 0.00 | 968.82 | 0.00 | 0.00 |
November | 150.10 | 2335.60 | 651.02 | 0.00 | 651.02 | 0.00 | 0.00 |
December | 11.10 | 3678.75 | 603.51 | 0.00 | 603.51 | 0.00 | 0.00 |
Annual Sum or Average | 926.21 | 2011.38 | 1285.65 | 34.71 | 1250.94 | 0.00 | 0.00 |
Minimum of Months | 10.45 | 565.42 | 603.51 | 0.00 | 603.51 | 0.00 | 0.00 |
Maximum of Months | 2406.65 | 3887.82 | 2121.66 | 180.61 | 1941.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 301.98 | 2358.65 | 786.65 | 253.66 | 532.99 | 0.00 | 0.00 |
February | 538.75 | 2236.56 | 1154.25 | 346.36 | 807.89 | 0.00 | 0.00 |
March | 1275.75 | 1607.96 | 1656.32 | 693.65 | 962.66 | 0.00 | 0.00 |
April | 2029.15 | 1177.43 | 2192.24 | 968.65 | 1223.59 | 0.00 | 0.00 |
May | 2621.29 | 814.79 | 2456.09 | 1086.46 | 1369.63 | 0.00 | 0.00 |
June | 3276.72 | 541.05 | 2743.04 | 1212.29 | 1530.75 | 0.00 | 0.00 |
July | 3387.22 | 380.51 | 2634.04 | 1159.73 | 1474.31 | 0.00 | 0.00 |
August | 2994.10 | 490.51 | 2378.83 | 998.50 | 1380.33 | 0.00 | 0.00 |
September | 2256.69 | 745.16 | 1979.60 | 878.07 | 1101.52 | 0.00 | 0.00 |
October | 1201.06 | 1132.52 | 1343.32 | 555.63 | 787.69 | 0.00 | 0.00 |
November | 476.78 | 1493.11 | 761.96 | 244.43 | 517.53 | 0.00 | 0.00 |
December | 158.08 | 2309.25 | 613.41 | 126.74 | 486.67 | 0.00 | 0.00 |
Annual Sum or Average | 1716.14 | 1269.17 | 1727.54 | 712.07 | 1015.47 | 0.00 | 0.00 |
Minimum of Months | 158.08 | 380.51 | 613.41 | 126.74 | 486.67 | 0.00 | 0.00 |
Maximum of Months | 3387.22 | 2358.65 | 2743.04 | 1212.29 | 1530.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2196.63 | 3346.73 | 2772.63 | 1618.47 | 1154.16 | 0.00 | 0.00 |
February | 2461.87 | 3292.69 | 3165.65 | 1526.45 | 1639.20 | 0.00 | 0.00 |
March | 3710.32 | 2459.11 | 3863.89 | 2171.09 | 1692.79 | 0.00 | 0.00 |
April | 3217.23 | 1948.33 | 3199.91 | 1278.69 | 1921.21 | 0.00 | 0.00 |
May | 3055.95 | 1337.70 | 2800.20 | 813.30 | 1986.91 | 0.00 | 0.00 |
June | 3317.04 | 878.98 | 2720.89 | 576.57 | 2144.32 | 0.00 | 0.00 |
July | 3752.84 | 619.10 | 2777.59 | 673.93 | 2103.66 | 0.00 | 0.00 |
August | 4151.75 | 797.17 | 3118.30 | 1011.03 | 2107.27 | 0.00 | 0.00 |
September | 4461.79 | 1225.53 | 3625.66 | 1765.97 | 1859.69 | 0.00 | 0.00 |
October | 3701.38 | 1789.96 | 3469.22 | 1981.69 | 1487.53 | 0.00 | 0.00 |
November | 2325.40 | 2267.92 | 2484.58 | 1402.63 | 1081.95 | 0.00 | 0.00 |
December | 1741.34 | 3275.76 | 2318.47 | 1199.91 | 1118.56 | 0.00 | 0.00 |
Annual Sum or Average | 3178.61 | 1929.34 | 3025.48 | 1334.27 | 1691.21 | 0.00 | 0.00 |
Minimum of Months | 1741.34 | 619.10 | 2318.47 | 576.57 | 1081.95 | 0.00 | 0.00 |
Maximum of Months | 4461.79 | 3346.73 | 3863.89 | 2171.09 | 2144.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 181.00 | 2498.09 | 674.93 | 158.45 | 516.48 | 0.00 | 0.00 |
February | 447.94 | 2366.33 | 1093.87 | 281.13 | 812.74 | 0.00 | 0.00 |
March | 1330.08 | 1709.65 | 1714.45 | 734.09 | 980.36 | 0.00 | 0.00 |
April | 1928.33 | 1285.82 | 2099.11 | 860.72 | 1238.39 | 0.00 | 0.00 |
May | 2661.98 | 900.61 | 2476.24 | 1119.10 | 1357.14 | 0.00 | 0.00 |
June | 3605.94 | 622.87 | 2987.66 | 1405.27 | 1582.39 | 0.00 | 0.00 |
July | 3439.07 | 450.12 | 2671.08 | 1171.09 | 1499.99 | 0.00 | 0.00 |
August | 3063.69 | 559.26 | 2415.83 | 1027.24 | 1388.60 | 0.00 | 0.00 |
September | 2166.89 | 816.77 | 1897.18 | 819.31 | 1077.87 | 0.00 | 0.00 |
October | 1067.27 | 1222.06 | 1229.84 | 433.22 | 796.62 | 0.00 | 0.00 |
November | 426.75 | 1587.42 | 728.81 | 210.02 | 518.79 | 0.00 | 0.00 |
December | 171.83 | 2414.26 | 631.81 | 137.66 | 494.15 | 0.00 | 0.00 |
Annual Sum or Average | 1714.36 | 1364.44 | 1721.24 | 698.46 | 1022.78 | 0.00 | 0.00 |
Minimum of Months | 171.83 | 450.12 | 631.81 | 137.66 | 494.15 | 0.00 | 0.00 |
Maximum of Months | 3605.94 | 2498.09 | 2987.66 | 1405.27 | 1582.39 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 77770.97 | 0.118869E+11 | 0.172703E+10 | 0.00 | 0.172703E+10 | 0.00 | 0.00 |
February | 49192418.38 | 0.101074E+11 | 0.237670E+10 | 0.00 | 0.237670E+10 | 0.00 | 0.00 |
March | 0.793492E+09 | 0.825823E+10 | 0.319108E+10 | 0.00 | 0.319108E+10 | 0.00 | 0.00 |
April | 0.176181E+10 | 0.575177E+10 | 0.393492E+10 | 15701893.98 | 0.391922E+10 | 0.00 | 0.00 |
May | 0.348162E+10 | 0.357315E+10 | 0.472459E+10 | 0.200349E+09 | 0.452424E+10 | 0.00 | 0.00 |
June | 0.576443E+10 | 0.221528E+10 | 0.549938E+10 | 0.468135E+09 | 0.503124E+10 | 0.00 | 0.00 |
July | 0.641182E+10 | 0.161473E+10 | 0.527145E+10 | 0.340284E+09 | 0.493116E+10 | 0.00 | 0.00 |
August | 0.522482E+10 | 0.212748E+10 | 0.456127E+10 | 69389778.13 | 0.449188E+10 | 0.00 | 0.00 |
September | 0.289470E+10 | 0.343089E+10 | 0.335925E+10 | 697906.18 | 0.335855E+10 | 0.00 | 0.00 |
October | 0.100879E+10 | 0.591745E+10 | 0.259489E+10 | 0.00 | 0.259489E+10 | 0.00 | 0.00 |
November | 0.206092E+09 | 0.771320E+10 | 0.168745E+10 | 0.00 | 0.168745E+10 | 0.00 | 0.00 |
December | 6576009.20 | 0.117097E+11 | 0.161645E+10 | 0.00 | 0.161645E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.276034E+11 | 0.743061E+11 | 0.405444E+11 | 0.109456E+10 | 0.394499E+11 | 0.00 | 0.00 |
Minimum of Months | 77770.97 | 0.161473E+10 | 0.161645E+10 | 0.00 | 0.161645E+10 | 0.00 | 0.00 |
Maximum of Months | 0.641182E+10 | 0.118869E+11 | 0.549938E+10 | 0.468135E+09 | 0.503124E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.729689E+09 | 0.716504E+10 | 0.210696E+10 | 0.679402E+09 | 0.142756E+10 | 0.00 | 0.00 |
February | 0.117751E+10 | 0.609970E+10 | 0.279237E+10 | 0.837922E+09 | 0.195445E+10 | 0.00 | 0.00 |
March | 0.327299E+10 | 0.493056E+10 | 0.443629E+10 | 0.185789E+10 | 0.257840E+10 | 0.00 | 0.00 |
April | 0.513419E+10 | 0.347174E+10 | 0.568231E+10 | 0.251075E+10 | 0.317156E+10 | 0.00 | 0.00 |
May | 0.702371E+10 | 0.236552E+10 | 0.657843E+10 | 0.290999E+10 | 0.366844E+10 | 0.00 | 0.00 |
June | 0.855893E+10 | 0.146404E+10 | 0.710999E+10 | 0.314227E+10 | 0.396773E+10 | 0.00 | 0.00 |
July | 0.914411E+10 | 0.102659E+10 | 0.705504E+10 | 0.310624E+10 | 0.394880E+10 | 0.00 | 0.00 |
August | 0.808601E+10 | 0.131981E+10 | 0.637148E+10 | 0.267440E+10 | 0.369708E+10 | 0.00 | 0.00 |
September | 0.583156E+10 | 0.214096E+10 | 0.513114E+10 | 0.227598E+10 | 0.285516E+10 | 0.00 | 0.00 |
October | 0.304979E+10 | 0.360076E+10 | 0.359797E+10 | 0.148822E+10 | 0.210975E+10 | 0.00 | 0.00 |
November | 0.108556E+10 | 0.469692E+10 | 0.197500E+10 | 0.633556E+09 | 0.134144E+10 | 0.00 | 0.00 |
December | 0.358000E+09 | 0.712919E+10 | 0.164297E+10 | 0.339473E+09 | 0.130350E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.534520E+11 | 0.454108E+11 | 0.544799E+11 | 0.224561E+11 | 0.320239E+11 | 0.00 | 0.00 |
Minimum of Months | 0.358000E+09 | 0.102659E+10 | 0.164297E+10 | 0.339473E+09 | 0.130350E+10 | 0.00 | 0.00 |
Maximum of Months | 0.914411E+10 | 0.716504E+10 | 0.710999E+10 | 0.314227E+10 | 0.396773E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.576851E+10 | 0.982912E+10 | 0.742625E+10 | 0.433492E+10 | 0.309133E+10 | 0.00 | 0.00 |
February | 0.582880E+10 | 0.870188E+10 | 0.765837E+10 | 0.369280E+10 | 0.396557E+10 | 0.00 | 0.00 |
March | 0.984862E+10 | 0.730792E+10 | 0.103491E+11 | 0.581508E+10 | 0.453399E+10 | 0.00 | 0.00 |
April | 0.822439E+10 | 0.565961E+10 | 0.829419E+10 | 0.331438E+10 | 0.497981E+10 | 0.00 | 0.00 |
May | 0.820104E+10 | 0.385546E+10 | 0.750009E+10 | 0.217834E+10 | 0.532175E+10 | 0.00 | 0.00 |
June | 0.865124E+10 | 0.241863E+10 | 0.705258E+10 | 0.149448E+10 | 0.555811E+10 | 0.00 | 0.00 |
July | 0.101115E+11 | 0.173005E+10 | 0.743953E+10 | 0.180507E+10 | 0.563446E+10 | 0.00 | 0.00 |
August | 0.111847E+11 | 0.222387E+10 | 0.835210E+10 | 0.270796E+10 | 0.564414E+10 | 0.00 | 0.00 |
September | 0.116109E+11 | 0.342640E+10 | 0.939774E+10 | 0.457740E+10 | 0.482034E+10 | 0.00 | 0.00 |
October | 0.981903E+10 | 0.543285E+10 | 0.929199E+10 | 0.530776E+10 | 0.398423E+10 | 0.00 | 0.00 |
November | 0.586637E+10 | 0.681787E+10 | 0.644006E+10 | 0.363563E+10 | 0.280443E+10 | 0.00 | 0.00 |
December | 0.450923E+10 | 0.986480E+10 | 0.620982E+10 | 0.321386E+10 | 0.299595E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.996243E+11 | 0.672685E+11 | 0.954118E+11 | 0.420777E+11 | 0.533341E+11 | 0.00 | 0.00 |
Minimum of Months | 0.450923E+10 | 0.173005E+10 | 0.620982E+10 | 0.149448E+10 | 0.280443E+10 | 0.00 | 0.00 |
Maximum of Months | 0.116109E+11 | 0.986480E+10 | 0.103491E+11 | 0.581508E+10 | 0.564414E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.431520E+09 | 0.771861E+10 | 0.180774E+10 | 0.424385E+09 | 0.138335E+10 | 0.00 | 0.00 |
February | 0.959015E+09 | 0.669745E+10 | 0.264631E+10 | 0.680121E+09 | 0.196619E+10 | 0.00 | 0.00 |
March | 0.334654E+10 | 0.559606E+10 | 0.459200E+10 | 0.196619E+10 | 0.262581E+10 | 0.00 | 0.00 |
April | 0.472076E+10 | 0.418471E+10 | 0.544092E+10 | 0.223100E+10 | 0.320993E+10 | 0.00 | 0.00 |
May | 0.705822E+10 | 0.271383E+10 | 0.663238E+10 | 0.299741E+10 | 0.363497E+10 | 0.00 | 0.00 |
June | 0.933715E+10 | 0.179761E+10 | 0.774404E+10 | 0.364248E+10 | 0.410156E+10 | 0.00 | 0.00 |
July | 0.917443E+10 | 0.134314E+10 | 0.715425E+10 | 0.313667E+10 | 0.401758E+10 | 0.00 | 0.00 |
August | 0.812163E+10 | 0.173028E+10 | 0.647059E+10 | 0.275136E+10 | 0.371923E+10 | 0.00 | 0.00 |
September | 0.553738E+10 | 0.244349E+10 | 0.491751E+10 | 0.212366E+10 | 0.279385E+10 | 0.00 | 0.00 |
October | 0.262309E+10 | 0.412998E+10 | 0.329402E+10 | 0.116034E+10 | 0.213368E+10 | 0.00 | 0.00 |
November | 0.928880E+09 | 0.542039E+10 | 0.188908E+10 | 0.544366E+09 | 0.134471E+10 | 0.00 | 0.00 |
December | 0.373406E+09 | 0.811484E+10 | 0.169225E+10 | 0.368723E+09 | 0.132353E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.526120E+11 | 0.518904E+11 | 0.542811E+11 | 0.220267E+11 | 0.322544E+11 | 0.00 | 0.00 |
Minimum of Months | 0.373406E+09 | 0.134314E+10 | 0.169225E+10 | 0.368723E+09 | 0.132353E+10 | 0.00 | 0.00 |
Maximum of Months | 0.933715E+10 | 0.811484E+10 | 0.774404E+10 | 0.364248E+10 | 0.410156E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 10960840.69 | 0.108135E+11 | 0.172702E+10 | 0.00 | 0.172702E+10 | 0.00 | 0.00 |
February | 0.106799E+09 | 0.917497E+10 | 0.237669E+10 | 0.00 | 0.237669E+10 | 0.00 | 0.00 |
March | 0.931364E+09 | 0.742980E+10 | 0.319106E+10 | 0.00 | 0.319106E+10 | 0.00 | 0.00 |
April | 0.197845E+10 | 0.513006E+10 | 0.393491E+10 | 15701838.22 | 0.391920E+10 | 0.00 | 0.00 |
May | 0.357240E+10 | 0.336714E+10 | 0.472457E+10 | 0.200349E+09 | 0.452422E+10 | 0.00 | 0.00 |
June | 0.582543E+10 | 0.209844E+10 | 0.549936E+10 | 0.468133E+09 | 0.503122E+10 | 0.00 | 0.00 |
July | 0.650533E+10 | 0.151079E+10 | 0.527143E+10 | 0.340283E+09 | 0.493115E+10 | 0.00 | 0.00 |
August | 0.531118E+10 | 0.200261E+10 | 0.456125E+10 | 69389531.73 | 0.449186E+10 | 0.00 | 0.00 |
September | 0.297742E+10 | 0.316319E+10 | 0.335924E+10 | 697903.71 | 0.335854E+10 | 0.00 | 0.00 |
October | 0.117621E+10 | 0.525458E+10 | 0.259488E+10 | 0.00 | 0.259488E+10 | 0.00 | 0.00 |
November | 0.309349E+09 | 0.665394E+10 | 0.168745E+10 | 0.00 | 0.168745E+10 | 0.00 | 0.00 |
December | 17756882.41 | 0.103696E+11 | 0.161644E+10 | 0.00 | 0.161644E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.287227E+11 | 0.669686E+11 | 0.405443E+11 | 0.109455E+10 | 0.394497E+11 | 0.00 | 0.00 |
Minimum of Months | 10960840.69 | 0.151079E+10 | 0.161644E+10 | 0.00 | 0.161644E+10 | 0.00 | 0.00 |
Maximum of Months | 0.650533E+10 | 0.108135E+11 | 0.549936E+10 | 0.468133E+09 | 0.503122E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.777051E+09 | 0.656924E+10 | 0.210695E+10 | 0.679399E+09 | 0.142755E+10 | 0.00 | 0.00 |
February | 0.125230E+10 | 0.563517E+10 | 0.279236E+10 | 0.837918E+09 | 0.195444E+10 | 0.00 | 0.00 |
March | 0.334120E+10 | 0.457842E+10 | 0.443628E+10 | 0.185789E+10 | 0.257839E+10 | 0.00 | 0.00 |
April | 0.518362E+10 | 0.323835E+10 | 0.568228E+10 | 0.251074E+10 | 0.317154E+10 | 0.00 | 0.00 |
May | 0.700524E+10 | 0.226423E+10 | 0.657840E+10 | 0.290998E+10 | 0.366842E+10 | 0.00 | 0.00 |
June | 0.852336E+10 | 0.141448E+10 | 0.710997E+10 | 0.314226E+10 | 0.396771E+10 | 0.00 | 0.00 |
July | 0.911837E+10 | 0.101205E+10 | 0.705501E+10 | 0.310622E+10 | 0.394879E+10 | 0.00 | 0.00 |
August | 0.805071E+10 | 0.132088E+10 | 0.637145E+10 | 0.267439E+10 | 0.369706E+10 | 0.00 | 0.00 |
September | 0.583390E+10 | 0.201062E+10 | 0.513112E+10 | 0.227597E+10 | 0.285515E+10 | 0.00 | 0.00 |
October | 0.312230E+10 | 0.329860E+10 | 0.359795E+10 | 0.148821E+10 | 0.210974E+10 | 0.00 | 0.00 |
November | 0.116374E+10 | 0.422251E+10 | 0.197499E+10 | 0.633554E+09 | 0.134144E+10 | 0.00 | 0.00 |
December | 0.398078E+09 | 0.650356E+10 | 0.164297E+10 | 0.339472E+09 | 0.130349E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.537699E+11 | 0.420681E+11 | 0.544797E+11 | 0.224560E+11 | 0.320237E+11 | 0.00 | 0.00 |
Minimum of Months | 0.398078E+09 | 0.101205E+10 | 0.164297E+10 | 0.339472E+09 | 0.130349E+10 | 0.00 | 0.00 |
Maximum of Months | 0.911837E+10 | 0.656924E+10 | 0.710997E+10 | 0.314226E+10 | 0.396771E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.579607E+10 | 0.938589E+10 | 0.742622E+10 | 0.433490E+10 | 0.309132E+10 | 0.00 | 0.00 |
February | 0.585722E+10 | 0.833912E+10 | 0.765834E+10 | 0.369279E+10 | 0.396556E+10 | 0.00 | 0.00 |
March | 0.981709E+10 | 0.702920E+10 | 0.103490E+11 | 0.581506E+10 | 0.453398E+10 | 0.00 | 0.00 |
April | 0.823488E+10 | 0.538635E+10 | 0.829416E+10 | 0.331437E+10 | 0.497979E+10 | 0.00 | 0.00 |
May | 0.815485E+10 | 0.374942E+10 | 0.750006E+10 | 0.217833E+10 | 0.532173E+10 | 0.00 | 0.00 |
June | 0.863267E+10 | 0.232113E+10 | 0.705256E+10 | 0.149447E+10 | 0.555809E+10 | 0.00 | 0.00 |
July | 0.101141E+11 | 0.166071E+10 | 0.743950E+10 | 0.180507E+10 | 0.563443E+10 | 0.00 | 0.00 |
August | 0.111642E+11 | 0.216201E+10 | 0.835207E+10 | 0.270795E+10 | 0.564412E+10 | 0.00 | 0.00 |
September | 0.115501E+11 | 0.332025E+10 | 0.939771E+10 | 0.457738E+10 | 0.482033E+10 | 0.00 | 0.00 |
October | 0.978097E+10 | 0.521659E+10 | 0.929196E+10 | 0.530775E+10 | 0.398421E+10 | 0.00 | 0.00 |
November | 0.589395E+10 | 0.643078E+10 | 0.644004E+10 | 0.363562E+10 | 0.280442E+10 | 0.00 | 0.00 |
December | 0.456489E+10 | 0.927549E+10 | 0.620979E+10 | 0.321385E+10 | 0.299594E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.995611E+11 | 0.642770E+11 | 0.954114E+11 | 0.420775E+11 | 0.533339E+11 | 0.00 | 0.00 |
Minimum of Months | 0.456489E+10 | 0.166071E+10 | 0.620979E+10 | 0.149447E+10 | 0.280442E+10 | 0.00 | 0.00 |
Maximum of Months | 0.115501E+11 | 0.938589E+10 | 0.103490E+11 | 0.581506E+10 | 0.564412E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.465906E+09 | 0.695035E+10 | 0.180773E+10 | 0.424384E+09 | 0.138334E+10 | 0.00 | 0.00 |
February | 0.105441E+10 | 0.594385E+10 | 0.264630E+10 | 0.680118E+09 | 0.196618E+10 | 0.00 | 0.00 |
March | 0.352117E+10 | 0.483438E+10 | 0.459199E+10 | 0.196618E+10 | 0.262580E+10 | 0.00 | 0.00 |
April | 0.494434E+10 | 0.352613E+10 | 0.544090E+10 | 0.223099E+10 | 0.320991E+10 | 0.00 | 0.00 |
May | 0.711420E+10 | 0.251137E+10 | 0.663236E+10 | 0.299740E+10 | 0.363496E+10 | 0.00 | 0.00 |
June | 0.937975E+10 | 0.164045E+10 | 0.774401E+10 | 0.364246E+10 | 0.410155E+10 | 0.00 | 0.00 |
July | 0.925632E+10 | 0.121045E+10 | 0.715422E+10 | 0.313665E+10 | 0.401756E+10 | 0.00 | 0.00 |
August | 0.823425E+10 | 0.151558E+10 | 0.647057E+10 | 0.275135E+10 | 0.371922E+10 | 0.00 | 0.00 |
September | 0.560105E+10 | 0.220685E+10 | 0.491748E+10 | 0.212365E+10 | 0.279384E+10 | 0.00 | 0.00 |
October | 0.279402E+10 | 0.352203E+10 | 0.329401E+10 | 0.116034E+10 | 0.213367E+10 | 0.00 | 0.00 |
November | 0.105883E+10 | 0.442400E+10 | 0.188907E+10 | 0.544363E+09 | 0.134471E+10 | 0.00 | 0.00 |
December | 0.440842E+09 | 0.676306E+10 | 0.169225E+10 | 0.368721E+09 | 0.132352E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.538651E+11 | 0.450485E+11 | 0.542809E+11 | 0.220266E+11 | 0.322543E+11 | 0.00 | 0.00 |
Minimum of Months | 0.440842E+09 | 0.121045E+10 | 0.169225E+10 | 0.368721E+09 | 0.132352E+10 | 0.00 | 0.00 |
Maximum of Months | 0.937975E+10 | 0.695035E+10 | 0.774401E+10 | 0.364246E+10 | 0.410155E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 27999835.20 | 0.104131E+11 | 0.172702E+10 | 0.00 | 0.172702E+10 | 0.00 | 0.00 |
February | 0.145416E+09 | 0.880464E+10 | 0.237669E+10 | 0.00 | 0.237669E+10 | 0.00 | 0.00 |
March | 0.100814E+10 | 0.698175E+10 | 0.319106E+10 | 0.00 | 0.319106E+10 | 0.00 | 0.00 |
April | 0.210666E+10 | 0.477759E+10 | 0.393491E+10 | 15701838.22 | 0.391920E+10 | 0.00 | 0.00 |
May | 0.364130E+10 | 0.320967E+10 | 0.472457E+10 | 0.200349E+09 | 0.452422E+10 | 0.00 | 0.00 |
June | 0.580161E+10 | 0.206773E+10 | 0.549936E+10 | 0.468133E+09 | 0.503122E+10 | 0.00 | 0.00 |
July | 0.644598E+10 | 0.151441E+10 | 0.527143E+10 | 0.340283E+09 | 0.493115E+10 | 0.00 | 0.00 |
August | 0.528060E+10 | 0.197950E+10 | 0.456125E+10 | 69389531.73 | 0.449186E+10 | 0.00 | 0.00 |
September | 0.302115E+10 | 0.300021E+10 | 0.335924E+10 | 697903.71 | 0.335854E+10 | 0.00 | 0.00 |
October | 0.131127E+10 | 0.477509E+10 | 0.259488E+10 | 0.00 | 0.259488E+10 | 0.00 | 0.00 |
November | 0.389067E+09 | 0.605388E+10 | 0.168745E+10 | 0.00 | 0.168745E+10 | 0.00 | 0.00 |
December | 29726024.25 | 0.985317E+10 | 0.161644E+10 | 0.00 | 0.161644E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.292089E+11 | 0.634308E+11 | 0.405443E+11 | 0.109455E+10 | 0.394497E+11 | 0.00 | 0.00 |
Minimum of Months | 27999835.20 | 0.151441E+10 | 0.161644E+10 | 0.00 | 0.161644E+10 | 0.00 | 0.00 |
Maximum of Months | 0.644598E+10 | 0.104131E+11 | 0.549936E+10 | 0.468133E+09 | 0.503122E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.808821E+09 | 0.631742E+10 | 0.210695E+10 | 0.679399E+09 | 0.142755E+10 | 0.00 | 0.00 |
February | 0.130335E+10 | 0.541069E+10 | 0.279236E+10 | 0.837918E+09 | 0.195444E+10 | 0.00 | 0.00 |
March | 0.341697E+10 | 0.430677E+10 | 0.443628E+10 | 0.185789E+10 | 0.257839E+10 | 0.00 | 0.00 |
April | 0.525955E+10 | 0.305190E+10 | 0.568228E+10 | 0.251074E+10 | 0.317154E+10 | 0.00 | 0.00 |
May | 0.702088E+10 | 0.218234E+10 | 0.657840E+10 | 0.290998E+10 | 0.366842E+10 | 0.00 | 0.00 |
June | 0.849327E+10 | 0.140240E+10 | 0.710997E+10 | 0.314226E+10 | 0.396771E+10 | 0.00 | 0.00 |
July | 0.907232E+10 | 0.101915E+10 | 0.705501E+10 | 0.310622E+10 | 0.394879E+10 | 0.00 | 0.00 |
August | 0.801940E+10 | 0.131378E+10 | 0.637145E+10 | 0.267439E+10 | 0.369706E+10 | 0.00 | 0.00 |
September | 0.584935E+10 | 0.193145E+10 | 0.513112E+10 | 0.227597E+10 | 0.285515E+10 | 0.00 | 0.00 |
October | 0.321692E+10 | 0.303334E+10 | 0.359795E+10 | 0.148821E+10 | 0.210974E+10 | 0.00 | 0.00 |
November | 0.123581E+10 | 0.387014E+10 | 0.197499E+10 | 0.633554E+09 | 0.134144E+10 | 0.00 | 0.00 |
December | 0.423411E+09 | 0.618510E+10 | 0.164297E+10 | 0.339472E+09 | 0.130349E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.541200E+11 | 0.400245E+11 | 0.544797E+11 | 0.224560E+11 | 0.320237E+11 | 0.00 | 0.00 |
Minimum of Months | 0.423411E+09 | 0.101915E+10 | 0.164297E+10 | 0.339472E+09 | 0.130349E+10 | 0.00 | 0.00 |
Maximum of Months | 0.907232E+10 | 0.631742E+10 | 0.710997E+10 | 0.314226E+10 | 0.396771E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.588345E+10 | 0.896387E+10 | 0.742622E+10 | 0.433490E+10 | 0.309132E+10 | 0.00 | 0.00 |
February | 0.595575E+10 | 0.796568E+10 | 0.765834E+10 | 0.369279E+10 | 0.396556E+10 | 0.00 | 0.00 |
March | 0.993772E+10 | 0.658647E+10 | 0.103490E+11 | 0.581506E+10 | 0.453398E+10 | 0.00 | 0.00 |
April | 0.833906E+10 | 0.505007E+10 | 0.829416E+10 | 0.331437E+10 | 0.497979E+10 | 0.00 | 0.00 |
May | 0.818506E+10 | 0.358289E+10 | 0.750006E+10 | 0.217833E+10 | 0.532173E+10 | 0.00 | 0.00 |
June | 0.859776E+10 | 0.227832E+10 | 0.705256E+10 | 0.149447E+10 | 0.555809E+10 | 0.00 | 0.00 |
July | 0.100516E+11 | 0.165821E+10 | 0.743950E+10 | 0.180507E+10 | 0.563443E+10 | 0.00 | 0.00 |
August | 0.111200E+11 | 0.213515E+10 | 0.835207E+10 | 0.270795E+10 | 0.564412E+10 | 0.00 | 0.00 |
September | 0.115650E+11 | 0.317658E+10 | 0.939771E+10 | 0.457738E+10 | 0.482033E+10 | 0.00 | 0.00 |
October | 0.991378E+10 | 0.479422E+10 | 0.929196E+10 | 0.530775E+10 | 0.398421E+10 | 0.00 | 0.00 |
November | 0.602744E+10 | 0.587844E+10 | 0.644004E+10 | 0.363562E+10 | 0.280442E+10 | 0.00 | 0.00 |
December | 0.466399E+10 | 0.877381E+10 | 0.620979E+10 | 0.321385E+10 | 0.299594E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.100241E+12 | 0.608437E+11 | 0.954114E+11 | 0.420775E+11 | 0.533339E+11 | 0.00 | 0.00 |
Minimum of Months | 0.466399E+10 | 0.165821E+10 | 0.620979E+10 | 0.149447E+10 | 0.280442E+10 | 0.00 | 0.00 |
Maximum of Months | 0.115650E+11 | 0.896387E+10 | 0.103490E+11 | 0.581506E+10 | 0.564412E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.484802E+09 | 0.669090E+10 | 0.180773E+10 | 0.424384E+09 | 0.138334E+10 | 0.00 | 0.00 |
February | 0.108367E+10 | 0.572462E+10 | 0.264630E+10 | 0.680118E+09 | 0.196618E+10 | 0.00 | 0.00 |
March | 0.356249E+10 | 0.457913E+10 | 0.459199E+10 | 0.196618E+10 | 0.262580E+10 | 0.00 | 0.00 |
April | 0.499824E+10 | 0.333285E+10 | 0.544090E+10 | 0.223099E+10 | 0.320991E+10 | 0.00 | 0.00 |
May | 0.712983E+10 | 0.241219E+10 | 0.663236E+10 | 0.299740E+10 | 0.363496E+10 | 0.00 | 0.00 |
June | 0.934659E+10 | 0.161449E+10 | 0.774401E+10 | 0.364246E+10 | 0.410155E+10 | 0.00 | 0.00 |
July | 0.921120E+10 | 0.120560E+10 | 0.715422E+10 | 0.313665E+10 | 0.401756E+10 | 0.00 | 0.00 |
August | 0.820579E+10 | 0.149792E+10 | 0.647057E+10 | 0.275135E+10 | 0.371922E+10 | 0.00 | 0.00 |
September | 0.561658E+10 | 0.211708E+10 | 0.491748E+10 | 0.212365E+10 | 0.279384E+10 | 0.00 | 0.00 |
October | 0.285858E+10 | 0.327318E+10 | 0.329401E+10 | 0.116034E+10 | 0.213367E+10 | 0.00 | 0.00 |
November | 0.110615E+10 | 0.411459E+10 | 0.188907E+10 | 0.544363E+09 | 0.134471E+10 | 0.00 | 0.00 |
December | 0.460218E+09 | 0.646635E+10 | 0.169225E+10 | 0.368721E+09 | 0.132352E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.540641E+11 | 0.430289E+11 | 0.542809E+11 | 0.220266E+11 | 0.322543E+11 | 0.00 | 0.00 |
Minimum of Months | 0.460218E+09 | 0.120560E+10 | 0.169225E+10 | 0.368721E+09 | 0.132352E+10 | 0.00 | 0.00 |
Maximum of Months | 0.934659E+10 | 0.669090E+10 | 0.774401E+10 | 0.364246E+10 | 0.410155E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.4 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.66 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.66 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.47 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.39 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.39 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.42 | 11.22 | 4.10 | 7.08 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.36 | 4.97 | 4.79 | 0.13 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.70 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.33 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.4 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.39 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.14 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.18 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.06 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.43 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.84 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.23 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.73 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.24 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.53 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.14 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.85 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.41 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.18 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.73 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.3 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.4 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.5 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.83 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.78 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.19 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.75 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.42 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.23 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.96 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.41 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.97 | 4.80 | 10.50 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.97 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.423657E+11 | -0.419189E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -446722971.5 | 60.05 | 0.00 | 0.00 |
February | 0.390359E+11 | -0.386325E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -403421236.8 | 60.05 | 0.00 | 0.00 |
March | 0.452816E+11 | -0.448357E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -445940215.7 | 60.05 | 0.00 | 0.00 |
April | 0.395094E+11 | -0.390803E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -429124049.1 | 60.05 | 0.00 | 0.00 |
May | 0.398582E+11 | -0.394149E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -443349562.0 | 60.05 | 0.00 | 0.00 |
June | 0.371206E+11 | -0.367014E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -419165234.0 | 60.05 | 0.00 | 0.00 |
July | 0.336522E+11 | -0.332332E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -419014723.6 | 60.05 | 0.00 | 0.00 |
August | 0.361461E+11 | -0.357176E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -428481166.7 | 60.05 | 0.00 | 0.00 |
September | 0.333964E+11 | -0.329757E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -420734792.2 | 60.05 | 0.00 | 0.00 |
October | 0.361212E+11 | -0.356802E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -440996998.6 | 60.05 | 0.00 | 0.00 |
November | 0.376513E+11 | -0.372240E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -427313420.2 | 60.05 | 0.00 | 0.00 |
December | 0.396969E+11 | -0.392532E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -443634410.9 | 60.05 | 0.00 | 0.00 |
Annual Sum or Average | 0.459836E+12 | -0.454668E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.516790E+10 | 60.05 | 0.00 | 0.00 |
Minimum of Months | 0.333964E+11 | -0.448357E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -446722971.5 | 60.05 | 0.00 | 0.00 |
Maximum of Months | 0.452816E+11 | -0.329757E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -403421236.8 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.50 | 0.48 | 01-JAN-09:20 | 4444.62 | 32.96 | 239.17 | 251.50 | 3542.34 | 33.92 | 243.83 | 224.17 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-09:00 | 5588.07 | 33.12 | 251.83 | 256.83 | 1796.87 | 26.27 | 228.33 | 233.83 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-07:40 | 7970.60 | 30.48 | 270.17 | 327.67 | 1477.30 | 22.63 | 234.17 | 293.83 |
April | 371.17 | 0.51 | 0.48 | 01-APR-07:10 | 2119.22 | 20.46 | 153.17 | 347.33 | 1170.68 | 21.84 | 252.83 | 312.33 |
May | 332.17 | 0.51 | 0.48 | 01-MAY-06:49 | 1938.37 | 20.50 | 121.17 | 385.67 | 1127.10 | 21.93 | 253.00 | 339.83 |
June | 430.67 | 0.51 | 0.48 | 01-JUN-06:19 | 1752.69 | 20.27 | 142.17 | 394.67 | 997.75 | 21.68 | 287.17 | 355.00 |
July | 439.00 | 0.51 | 0.48 | 01-JUL-06:30 | 1833.54 | 20.32 | 164.17 | 402.50 | 1028.44 | 21.73 | 281.00 | 356.33 |
August | 406.00 | 0.51 | 0.48 | 01-AUG-06:30 | 2161.12 | 20.82 | 203.33 | 378.33 | 1183.05 | 22.21 | 292.00 | 338.50 |
September | 289.17 | 0.51 | 0.48 | 01-SEP-07:40 | 3054.01 | 22.26 | 175.33 | 325.83 | 1540.20 | 22.86 | 257.00 | 293.50 |
October | 314.33 | 0.50 | 0.48 | 01-OCT-07:30 | 6450.77 | 32.65 | 283.67 | 298.83 | 1566.32 | 23.32 | 231.17 | 277.17 |
November | 258.33 | 0.51 | 0.48 | 01-NOV-07:49 | 4190.47 | 32.79 | 243.50 | 241.67 | 1677.76 | 28.46 | 232.67 | 217.33 |
December | 230.67 | 0.50 | 0.48 | 01-DEC-08:09 | 3760.41 | 32.05 | 219.50 | 239.50 | 2905.64 | 33.28 | 227.17 | 208.67 |
Annual Sum or Average | 3928.50 | 0.51 | 3572.36 | 25.58 | 2467.17 | 3850.33 | 1549.86 | 24.30 | 3020.33 | 3450.50 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1752.69 | 20.27 | 121.17 | 239.50 | 997.75 | 21.68 | 227.17 | 208.67 | |
Maximum of Months | 439.00 | 0.51 | 0.48 | 7970.60 | 33.12 | 283.67 | 402.50 | 3542.34 | 33.92 | 292.00 | 356.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.52 | 0.48 | 01-JAN-09:20 | 1553.95 | 23.05 | 97.50 | 238.33 | 768.02 | 23.05 | 136.33 | 190.83 |
February | 262.50 | 0.51 | 0.48 | 01-FEB-09:00 | 2144.60 | 24.06 | 130.17 | 249.17 | 1101.24 | 24.26 | 176.17 | 219.00 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-07:19 | 2908.89 | 24.70 | 148.00 | 321.50 | 1258.00 | 24.02 | 193.00 | 288.17 |
April | 371.17 | 0.51 | 0.48 | 01-APR-06:30 | 3146.05 | 24.14 | 139.33 | 352.17 | 1758.81 | 24.65 | 220.17 | 318.83 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-05:30 | 4173.81 | 24.85 | 108.33 | 394.17 | 1764.38 | 24.14 | 212.50 | 351.17 |
June | 430.67 | 0.51 | 0.48 | 01-JUN-05:00 | 3799.97 | 24.10 | 142.83 | 404.67 | 1664.95 | 23.86 | 231.83 | 375.33 |
July | 439.00 | 0.51 | 0.48 | 01-JUL-05:10 | 3599.05 | 24.30 | 146.33 | 411.67 | 1575.85 | 23.86 | 248.67 | 375.33 |
August | 406.00 | 0.51 | 0.48 | 01-AUG-05:49 | 3345.68 | 24.57 | 151.33 | 381.33 | 1469.28 | 24.09 | 259.33 | 347.50 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3379.48 | 25.09 | 124.83 | 326.50 | 1841.63 | 25.32 | 206.33 | 289.83 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-07:10 | 2170.64 | 23.97 | 126.17 | 291.00 | 1146.44 | 24.13 | 186.00 | 256.83 |
November | 258.33 | 0.53 | 0.48 | 01-NOV-07:40 | 1562.96 | 23.30 | 105.67 | 231.83 | 847.98 | 23.47 | 138.17 | 180.83 |
December | 230.67 | 0.51 | 0.48 | 01-DEC-08:09 | 1346.90 | 22.88 | 90.67 | 227.17 | 670.21 | 23.08 | 125.83 | 175.67 |
Annual Sum or Average | 3928.50 | 0.51 | 2914.47 | 24.16 | 1511.17 | 3829.50 | 1380.36 | 24.03 | 2334.33 | 3369.33 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1346.90 | 22.88 | 90.67 | 227.17 | 670.21 | 23.05 | 125.83 | 175.67 | |
Maximum of Months | 439.00 | 0.53 | 0.48 | 4173.81 | 25.09 | 151.33 | 411.67 | 1841.63 | 25.32 | 259.33 | 375.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.54 | 0.48 | 01-JAN-11:09 | 679.52 | 17.66 | 0.00 | 222.83 | 378.21 | 19.06 | 0.67 | 143.33 |
February | 262.50 | 0.52 | 0.48 | 01-FEB-12:39 | 892.47 | 18.64 | 0.00 | 243.00 | 494.48 | 19.98 | 51.50 | 195.00 |
March | 339.33 | 0.51 | 0.48 | 01-MAR-08:30 | 950.29 | 19.15 | 0.00 | 316.00 | 554.64 | 20.58 | 87.33 | 267.67 |
April | 371.17 | 0.51 | 0.48 | 01-APR-07:10 | 1100.80 | 19.65 | 7.33 | 350.83 | 642.41 | 20.97 | 174.17 | 317.00 |
May | 332.17 | 0.49 | 0.48 | 01-MAY-06:10 | 1321.31 | 21.71 | 91.17 | 403.00 | 794.11 | 22.90 | 251.50 | 363.50 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-06:10 | 1469.93 | 23.03 | 175.33 | 413.67 | 827.10 | 22.18 | 310.00 | 385.67 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-05:30 | 1398.90 | 22.71 | 160.33 | 419.83 | 812.85 | 22.99 | 315.17 | 389.33 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-05:00 | 1241.06 | 20.35 | 58.67 | 388.33 | 733.02 | 21.69 | 270.17 | 354.00 |
September | 289.17 | 0.51 | 0.48 | 01-SEP-07:49 | 1043.71 | 19.87 | 1.17 | 322.83 | 641.86 | 21.29 | 149.83 | 274.00 |
October | 314.33 | 0.53 | 0.48 | 01-OCT-08:09 | 831.96 | 18.42 | 0.00 | 282.50 | 476.81 | 19.83 | 36.00 | 226.17 |
November | 258.33 | 0.55 | 0.48 | 01-NOV-08:39 | 658.88 | 17.10 | 0.00 | 218.83 | 365.08 | 18.43 | 1.50 | 131.67 |
December | 230.67 | 0.54 | 0.48 | 01-DEC-12:09 | 682.50 | 17.58 | 0.00 | 209.00 | 371.49 | 18.91 | 1.83 | 122.83 |
Annual Sum or Average | 3928.50 | 0.51 | 1074.10 | 20.00 | 494.00 | 3790.67 | 621.83 | 20.99 | 1649.67 | 3170.17 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 658.88 | 17.10 | 0.00 | 209.00 | 365.08 | 18.43 | 0.67 | 122.83 | |
Maximum of Months | 439.00 | 0.55 | 0.48 | 1469.93 | 23.03 | 175.33 | 419.83 | 827.10 | 22.99 | 315.17 | 389.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.52 | 0.48 | 01-JAN-10:30 | 1458.16 | 23.32 | 105.17 | 238.00 | 785.84 | 23.64 | 142.50 | 192.00 |
February | 262.50 | 0.51 | 0.48 | 01-FEB-10:39 | 2004.59 | 23.89 | 127.17 | 249.17 | 1051.65 | 24.24 | 177.83 | 218.33 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-08:30 | 2857.93 | 24.53 | 143.33 | 324.67 | 1606.83 | 24.95 | 204.33 | 289.83 |
April | 371.17 | 0.51 | 0.48 | 01-APR-07:30 | 3345.62 | 23.27 | 131.50 | 348.33 | 1410.28 | 22.82 | 194.67 | 315.00 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-06:00 | 3597.41 | 21.21 | 52.67 | 392.67 | 1969.09 | 21.26 | 178.00 | 356.33 |
June | 430.67 | 0.51 | 0.48 | 01-JUN-06:40 | 3787.37 | 21.00 | 64.67 | 403.00 | 1622.83 | 21.24 | 215.83 | 371.83 |
July | 439.00 | 0.51 | 0.48 | 01-JUL-06:30 | 3385.23 | 21.03 | 75.17 | 409.17 | 1530.17 | 21.37 | 219.33 | 373.17 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-06:49 | 3173.28 | 22.58 | 119.67 | 384.50 | 1706.85 | 23.20 | 235.33 | 349.67 |
September | 289.17 | 0.51 | 0.48 | 01-SEP-07:00 | 3503.64 | 24.83 | 117.33 | 323.50 | 1516.86 | 24.01 | 199.33 | 292.33 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-08:20 | 2037.61 | 23.76 | 126.00 | 290.17 | 1069.49 | 24.03 | 182.33 | 256.33 |
November | 258.33 | 0.53 | 0.48 | 01-NOV-08:39 | 1495.25 | 22.88 | 102.67 | 230.83 | 788.52 | 23.04 | 135.00 | 184.50 |
December | 230.67 | 0.52 | 0.48 | 01-DEC-11:50 | 1404.23 | 22.84 | 91.83 | 223.67 | 735.51 | 23.23 | 130.00 | 175.50 |
Annual Sum or Average | 3928.50 | 0.51 | 2818.93 | 22.78 | 1257.17 | 3817.67 | 1377.40 | 22.95 | 2214.50 | 3374.83 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1404.23 | 21.00 | 52.67 | 223.67 | 735.51 | 21.24 | 130.00 | 175.50 | |
Maximum of Months | 439.00 | 0.53 | 0.48 | 3787.37 | 24.83 | 143.33 | 409.17 | 1969.09 | 24.95 | 235.33 | 373.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.50 | 0.48 | 01-JAN-09:20 | 4459.19 | 32.13 | 233.00 | 251.67 | 3630.38 | 33.13 | 231.83 | 226.50 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-09:50 | 5607.73 | 32.41 | 241.50 | 257.00 | 1945.02 | 24.30 | 106.50 | 239.50 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-07:30 | 8016.83 | 28.61 | 229.17 | 327.83 | 1593.01 | 18.09 | 11.50 | 297.17 |
April | 371.17 | 0.51 | 0.48 | 01-APR-07:10 | 2152.99 | 14.11 | 0.00 | 347.83 | 1251.46 | 17.55 | 1.67 | 317.67 |
May | 332.17 | 0.51 | 0.48 | 01-MAY-06:40 | 1977.27 | 14.44 | 0.00 | 386.17 | 1206.07 | 17.97 | 0.00 | 344.00 |
June | 430.67 | 0.51 | 0.48 | 01-JUN-06:19 | 1782.31 | 14.31 | 0.00 | 395.17 | 1064.92 | 17.77 | 0.00 | 360.67 |
July | 439.00 | 0.51 | 0.48 | 01-JUL-06:19 | 1862.95 | 14.25 | 0.00 | 403.00 | 1097.39 | 17.71 | 0.00 | 362.17 |
August | 406.00 | 0.51 | 0.48 | 01-AUG-06:19 | 2192.08 | 14.64 | 0.00 | 378.33 | 1262.36 | 18.08 | 0.67 | 342.50 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3099.79 | 16.29 | 17.00 | 326.50 | 1649.14 | 18.61 | 7.33 | 296.33 |
October | 314.33 | 0.50 | 0.48 | 01-OCT-07:19 | 6483.18 | 31.62 | 269.67 | 299.17 | 1754.60 | 18.83 | 25.50 | 279.50 |
November | 258.33 | 0.51 | 0.48 | 01-NOV-07:49 | 4201.36 | 32.10 | 237.50 | 241.50 | 2040.81 | 27.52 | 160.50 | 220.50 |
December | 230.67 | 0.50 | 0.48 | 01-DEC-08:09 | 3758.28 | 30.71 | 203.67 | 239.50 | 2986.52 | 32.61 | 216.00 | 211.00 |
Annual Sum or Average | 3928.50 | 0.51 | 3601.39 | 21.59 | 1431.50 | 3853.67 | 1664.76 | 20.91 | 761.50 | 3497.50 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1782.31 | 14.11 | 0.00 | 239.50 | 1064.92 | 17.55 | 0.00 | 211.00 | |
Maximum of Months | 439.00 | 0.51 | 0.48 | 8016.83 | 32.41 | 269.67 | 403.00 | 3630.38 | 33.13 | 231.83 | 362.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.51 | 0.48 | 01-JAN-09:20 | 1579.85 | 20.22 | 70.17 | 239.33 | 805.40 | 20.91 | 67.33 | 197.00 |
February | 262.50 | 0.51 | 0.48 | 01-FEB-09:50 | 2181.71 | 21.39 | 83.00 | 250.00 | 1150.33 | 22.18 | 70.17 | 221.83 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-07:19 | 2960.12 | 22.03 | 115.33 | 321.83 | 1319.43 | 21.68 | 61.50 | 291.33 |
April | 371.17 | 0.51 | 0.48 | 01-APR-06:30 | 3179.05 | 20.40 | 104.00 | 352.50 | 1830.38 | 22.36 | 87.50 | 322.33 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-05:30 | 4227.85 | 21.90 | 103.50 | 395.67 | 1850.76 | 21.53 | 55.83 | 354.33 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-05:00 | 3848.49 | 21.16 | 132.67 | 405.00 | 1744.64 | 21.29 | 75.83 | 378.00 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-05:10 | 3646.60 | 21.38 | 135.83 | 413.00 | 1654.40 | 21.31 | 75.50 | 377.67 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-05:49 | 3398.28 | 21.64 | 122.67 | 382.50 | 1544.00 | 21.53 | 67.50 | 351.67 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3441.71 | 22.25 | 86.50 | 326.83 | 1918.14 | 23.08 | 63.50 | 294.33 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-07:10 | 2211.89 | 21.19 | 91.67 | 291.83 | 1198.84 | 21.98 | 66.17 | 261.17 |
November | 258.33 | 0.53 | 0.48 | 01-NOV-07:40 | 1587.83 | 20.61 | 86.83 | 232.83 | 883.45 | 21.51 | 73.83 | 186.50 |
December | 230.67 | 0.51 | 0.48 | 01-DEC-07:00 | 1365.50 | 19.50 | 59.67 | 228.17 | 703.05 | 21.03 | 60.83 | 181.33 |
Annual Sum or Average | 3928.50 | 0.51 | 2957.42 | 21.20 | 1191.83 | 3839.50 | 1444.76 | 21.69 | 825.50 | 3417.50 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1365.50 | 19.50 | 59.67 | 228.17 | 703.05 | 20.91 | 55.83 | 181.33 | |
Maximum of Months | 439.00 | 0.53 | 0.48 | 4227.85 | 22.25 | 135.83 | 413.00 | 1918.14 | 23.08 | 87.50 | 378.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.54 | 0.48 | 01-JAN-10:50 | 687.14 | 11.43 | 0.00 | 223.33 | 401.43 | 14.95 | 0.00 | 153.83 |
February | 262.50 | 0.52 | 0.48 | 01-FEB-12:39 | 904.39 | 12.77 | 0.00 | 243.17 | 525.15 | 16.14 | 0.00 | 201.50 |
March | 339.33 | 0.51 | 0.48 | 01-MAR-08:20 | 964.85 | 13.49 | 0.00 | 316.83 | 590.13 | 16.95 | 0.00 | 273.83 |
April | 371.17 | 0.51 | 0.48 | 01-APR-07:10 | 1119.19 | 14.05 | 0.00 | 351.00 | 683.73 | 17.46 | 0.00 | 321.83 |
May | 332.17 | 0.49 | 0.48 | 01-MAY-06:10 | 1348.60 | 16.58 | 26.17 | 403.00 | 849.86 | 19.88 | 29.17 | 368.00 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-06:10 | 1497.48 | 18.35 | 74.33 | 413.83 | 911.09 | 19.97 | 42.17 | 391.83 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-05:30 | 1424.11 | 17.97 | 71.00 | 419.83 | 865.09 | 19.72 | 45.17 | 391.33 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-05:00 | 1262.58 | 14.78 | 0.00 | 388.83 | 780.03 | 18.25 | 3.00 | 357.50 |
September | 289.17 | 0.51 | 0.48 | 01-SEP-07:40 | 1062.53 | 14.72 | 0.00 | 323.00 | 683.86 | 18.17 | 0.00 | 280.17 |
October | 314.33 | 0.52 | 0.48 | 01-OCT-07:00 | 843.45 | 12.58 | 0.00 | 283.17 | 506.82 | 16.02 | 0.00 | 235.67 |
November | 258.33 | 0.55 | 0.48 | 01-NOV-08:30 | 666.30 | 10.96 | 0.00 | 219.17 | 387.55 | 14.34 | 0.00 | 141.50 |
December | 230.67 | 0.54 | 0.48 | 01-DEC-12:09 | 690.08 | 11.30 | 0.00 | 209.67 | 394.14 | 14.76 | 0.00 | 132.83 |
Annual Sum or Average | 3928.50 | 0.51 | 1091.99 | 14.51 | 171.50 | 3794.83 | 665.28 | 17.55 | 119.50 | 3249.83 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 666.30 | 10.96 | 0.00 | 209.67 | 387.55 | 14.34 | 0.00 | 132.83 | |
Maximum of Months | 439.00 | 0.55 | 0.48 | 1497.48 | 18.35 | 74.33 | 419.83 | 911.09 | 19.97 | 45.17 | 391.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.51 | 0.48 | 01-JAN-10:20 | 1481.26 | 20.86 | 85.17 | 239.00 | 819.01 | 21.78 | 76.50 | 196.50 |
February | 262.50 | 0.51 | 0.48 | 01-FEB-10:30 | 2040.21 | 21.20 | 81.67 | 249.67 | 1099.01 | 22.17 | 69.17 | 222.17 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-08:20 | 2886.81 | 21.02 | 102.17 | 325.00 | 1670.64 | 22.82 | 85.83 | 293.67 |
April | 371.17 | 0.51 | 0.48 | 01-APR-07:30 | 3397.92 | 20.20 | 104.33 | 349.67 | 1478.60 | 20.11 | 49.33 | 319.33 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-06:49 | 3636.67 | 17.26 | 43.00 | 394.00 | 2055.62 | 17.90 | 0.00 | 359.00 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-06:40 | 3836.79 | 17.01 | 52.50 | 404.00 | 1706.98 | 17.86 | 0.00 | 374.00 |
July | 439.00 | 0.51 | 0.48 | 01-JUL-06:30 | 3433.14 | 17.09 | 54.50 | 409.83 | 1607.96 | 18.08 | 3.67 | 377.00 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-06:40 | 3221.99 | 19.17 | 85.17 | 384.83 | 1781.29 | 20.51 | 53.67 | 353.50 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:00 | 3528.17 | 21.94 | 84.67 | 324.50 | 1592.68 | 21.47 | 41.67 | 295.17 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-08:09 | 2075.01 | 20.93 | 89.50 | 291.00 | 1118.89 | 21.85 | 64.33 | 261.00 |
November | 258.33 | 0.53 | 0.48 | 01-NOV-08:30 | 1519.09 | 20.34 | 87.00 | 231.17 | 822.41 | 21.07 | 69.00 | 190.67 |
December | 230.67 | 0.52 | 0.48 | 01-DEC-11:50 | 1427.35 | 20.17 | 63.83 | 225.50 | 768.63 | 21.23 | 66.33 | 179.50 |
Annual Sum or Average | 3928.50 | 0.51 | 2857.09 | 19.52 | 933.50 | 3828.17 | 1441.33 | 20.34 | 579.50 | 3421.50 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1427.35 | 17.01 | 43.00 | 225.50 | 768.63 | 17.86 | 0.00 | 179.50 | |
Maximum of Months | 439.00 | 0.53 | 0.48 | 3836.79 | 21.94 | 104.33 | 409.83 | 2055.62 | 22.82 | 85.83 | 377.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.50 | 0.48 | 01-JAN-09:20 | 4460.96 | 32.13 | 233.00 | 251.67 | 3632.61 | 33.13 | 231.83 | 226.50 |
February | 262.50 | 0.50 | 0.48 | 01-FEB-09:50 | 5610.76 | 32.40 | 241.33 | 257.00 | 1947.93 | 24.29 | 106.50 | 239.50 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-07:30 | 8020.22 | 28.59 | 229.00 | 328.00 | 1595.35 | 18.07 | 11.33 | 297.17 |
April | 371.17 | 0.51 | 0.48 | 01-APR-07:10 | 2156.21 | 14.08 | 0.00 | 347.83 | 1253.42 | 17.54 | 1.33 | 317.83 |
May | 332.17 | 0.51 | 0.48 | 01-MAY-06:40 | 1979.85 | 14.41 | 0.00 | 386.17 | 1207.71 | 17.95 | 0.00 | 344.50 |
June | 430.67 | 0.51 | 0.48 | 01-JUN-06:19 | 1784.72 | 14.28 | 0.00 | 395.17 | 1066.45 | 17.75 | 0.00 | 360.67 |
July | 439.00 | 0.51 | 0.48 | 01-JUL-06:19 | 1865.58 | 14.22 | 0.00 | 403.00 | 1099.02 | 17.69 | 0.00 | 362.50 |
August | 406.00 | 0.51 | 0.48 | 01-AUG-06:19 | 2195.37 | 14.61 | 0.00 | 378.33 | 1264.36 | 18.07 | 0.67 | 342.67 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3103.53 | 16.26 | 17.00 | 326.67 | 1651.62 | 18.60 | 7.17 | 296.67 |
October | 314.33 | 0.50 | 0.48 | 01-OCT-07:19 | 6486.00 | 31.61 | 269.67 | 299.17 | 1850.71 | 19.09 | 29.50 | 279.67 |
November | 258.33 | 0.51 | 0.48 | 01-NOV-07:49 | 4203.32 | 32.09 | 237.50 | 241.67 | 2310.88 | 29.23 | 186.50 | 220.83 |
December | 230.67 | 0.50 | 0.48 | 01-DEC-08:09 | 3760.02 | 30.70 | 203.67 | 239.50 | 2988.76 | 32.60 | 216.00 | 211.17 |
Annual Sum or Average | 3928.50 | 0.51 | 3604.15 | 21.57 | 1431.17 | 3854.17 | 1691.94 | 21.04 | 790.83 | 3499.67 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1784.72 | 14.08 | 0.00 | 239.50 | 1066.45 | 17.54 | 0.00 | 211.17 | |
Maximum of Months | 439.00 | 0.51 | 0.48 | 8020.22 | 32.40 | 269.67 | 403.00 | 3632.61 | 33.13 | 231.83 | 362.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.51 | 0.48 | 01-JAN-09:20 | 1581.17 | 20.19 | 70.17 | 239.33 | 806.56 | 20.90 | 66.83 | 197.33 |
February | 262.50 | 0.51 | 0.48 | 01-FEB-09:50 | 2183.61 | 21.36 | 83.00 | 250.17 | 1151.89 | 22.17 | 70.00 | 221.83 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-07:19 | 2931.81 | 21.02 | 103.33 | 321.83 | 1320.93 | 21.67 | 61.50 | 291.50 |
April | 371.17 | 0.51 | 0.48 | 01-APR-06:30 | 3181.05 | 20.38 | 104.00 | 352.50 | 1832.04 | 22.35 | 87.50 | 322.33 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-05:30 | 4229.85 | 21.88 | 103.50 | 395.67 | 1852.53 | 21.51 | 55.83 | 354.33 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-05:00 | 3850.61 | 21.14 | 132.67 | 405.33 | 1746.41 | 21.28 | 75.83 | 378.00 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-05:10 | 3648.69 | 21.36 | 135.83 | 413.00 | 1656.14 | 21.29 | 75.50 | 378.17 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-05:49 | 3400.45 | 21.61 | 122.67 | 382.50 | 1545.83 | 21.52 | 67.50 | 351.67 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:40 | 3443.51 | 22.23 | 86.50 | 327.00 | 1919.95 | 23.06 | 63.33 | 294.50 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-07:10 | 2213.46 | 21.16 | 91.67 | 291.83 | 1200.20 | 21.97 | 66.17 | 261.17 |
November | 258.33 | 0.53 | 0.48 | 01-NOV-07:40 | 1589.14 | 20.59 | 86.83 | 233.00 | 884.55 | 21.50 | 73.83 | 186.83 |
December | 230.67 | 0.51 | 0.48 | 01-DEC-07:00 | 1366.90 | 19.47 | 59.67 | 228.33 | 704.18 | 21.02 | 60.83 | 181.50 |
Annual Sum or Average | 3928.50 | 0.51 | 2956.67 | 21.09 | 1179.83 | 3840.50 | 1446.33 | 21.68 | 824.67 | 3419.17 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1366.90 | 19.47 | 59.67 | 228.33 | 704.18 | 20.90 | 55.83 | 181.50 | |
Maximum of Months | 439.00 | 0.53 | 0.48 | 4229.85 | 22.23 | 135.83 | 413.00 | 1919.95 | 23.06 | 87.50 | 378.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.54 | 0.48 | 01-JAN-10:50 | 688.00 | 11.40 | 0.00 | 223.33 | 402.07 | 14.94 | 0.00 | 154.17 |
February | 262.50 | 0.52 | 0.48 | 01-FEB-12:39 | 905.58 | 12.74 | 0.00 | 243.17 | 526.00 | 16.12 | 0.00 | 201.67 |
March | 339.33 | 0.51 | 0.48 | 01-MAR-08:20 | 965.92 | 13.46 | 0.00 | 317.00 | 590.96 | 16.93 | 0.00 | 274.17 |
April | 371.17 | 0.51 | 0.48 | 01-APR-07:10 | 1120.46 | 14.02 | 0.00 | 351.17 | 684.69 | 17.44 | 0.00 | 322.33 |
May | 332.17 | 0.49 | 0.48 | 01-MAY-06:10 | 1349.71 | 16.55 | 26.17 | 403.00 | 850.87 | 19.86 | 28.83 | 368.33 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-06:10 | 1498.92 | 18.32 | 74.33 | 414.00 | 912.27 | 19.96 | 41.33 | 391.83 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-05:30 | 1425.54 | 17.95 | 71.00 | 420.00 | 866.24 | 19.71 | 45.00 | 391.50 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-05:00 | 1263.92 | 14.75 | 0.00 | 388.83 | 781.09 | 18.23 | 2.67 | 357.50 |
September | 289.17 | 0.51 | 0.48 | 01-SEP-07:40 | 1063.39 | 14.68 | 0.00 | 323.00 | 684.70 | 18.15 | 0.00 | 280.33 |
October | 314.33 | 0.52 | 0.48 | 01-OCT-07:00 | 844.42 | 12.55 | 0.00 | 283.33 | 507.57 | 16.01 | 0.00 | 235.67 |
November | 258.33 | 0.55 | 0.48 | 01-NOV-08:30 | 667.16 | 10.93 | 0.00 | 219.50 | 388.17 | 14.33 | 0.00 | 141.67 |
December | 230.67 | 0.54 | 0.48 | 01-DEC-12:09 | 691.01 | 11.27 | 0.00 | 209.67 | 394.80 | 14.74 | 0.00 | 133.33 |
Annual Sum or Average | 3928.50 | 0.51 | 1093.14 | 14.48 | 171.50 | 3796.00 | 666.19 | 17.54 | 117.83 | 3252.50 | ||
Minimum of Months | 230.67 | 0.49 | 0.48 | 667.16 | 10.93 | 0.00 | 209.67 | 388.17 | 14.33 | 0.00 | 133.33 | |
Maximum of Months | 439.00 | 0.55 | 0.48 | 1498.92 | 18.32 | 74.33 | 420.00 | 912.27 | 19.96 | 45.00 | 391.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.51 | 0.48 | 01-JAN-10:20 | 1482.58 | 20.84 | 85.17 | 239.00 | 820.11 | 21.77 | 76.17 | 196.50 |
February | 262.50 | 0.51 | 0.48 | 01-FEB-10:30 | 2042.09 | 21.18 | 81.67 | 249.67 | 1100.56 | 22.16 | 68.83 | 222.17 |
March | 339.33 | 0.50 | 0.48 | 01-MAR-08:20 | 2888.58 | 21.00 | 102.00 | 325.00 | 1672.18 | 22.81 | 85.83 | 293.67 |
April | 371.17 | 0.51 | 0.48 | 01-APR-07:30 | 3399.96 | 20.17 | 104.33 | 349.67 | 1480.27 | 20.10 | 49.33 | 319.50 |
May | 332.17 | 0.50 | 0.48 | 01-MAY-06:49 | 3638.57 | 17.23 | 43.00 | 394.00 | 2057.34 | 17.88 | 0.00 | 359.33 |
June | 430.67 | 0.50 | 0.48 | 01-JUN-06:40 | 3838.90 | 16.98 | 52.50 | 404.00 | 1708.83 | 17.84 | 0.00 | 374.17 |
July | 439.00 | 0.50 | 0.48 | 01-JUL-06:30 | 3435.34 | 17.06 | 54.50 | 409.83 | 1609.77 | 18.06 | 3.67 | 377.17 |
August | 406.00 | 0.50 | 0.48 | 01-AUG-06:40 | 3224.27 | 19.14 | 85.17 | 384.83 | 1783.16 | 20.49 | 53.67 | 353.67 |
September | 289.17 | 0.50 | 0.48 | 01-SEP-07:00 | 3529.91 | 21.91 | 84.67 | 324.50 | 1594.36 | 21.45 | 41.67 | 295.17 |
October | 314.33 | 0.51 | 0.48 | 01-OCT-08:09 | 2076.64 | 20.90 | 89.50 | 291.17 | 1120.28 | 21.84 | 64.33 | 261.00 |
November | 258.33 | 0.53 | 0.48 | 01-NOV-08:30 | 1520.41 | 20.32 | 87.00 | 231.33 | 823.49 | 21.06 | 68.50 | 191.17 |
December | 230.67 | 0.52 | 0.48 | 01-DEC-11:50 | 1428.75 | 20.15 | 63.67 | 225.50 | 769.77 | 21.22 | 66.17 | 180.00 |
Annual Sum or Average | 3928.50 | 0.51 | 2858.95 | 19.50 | 933.17 | 3828.50 | 1442.91 | 20.33 | 578.17 | 3423.50 | ||
Minimum of Months | 230.67 | 0.50 | 0.48 | 1428.75 | 16.98 | 43.00 | 225.50 | 769.77 | 17.84 | 0.00 | 180.00 | |
Maximum of Months | 439.00 | 0.53 | 0.48 | 3838.90 | 21.91 | 104.33 | 409.83 | 2057.34 | 22.81 | 85.83 | 377.17 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.126013E+09 | 5709.60 | 18-JAN-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157800E+09 | 8553.67 | 28-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.214490E+09 | 17251.11 | 24-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 41509138.38 | 12079.54 | 17-APR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3400175.00 | 2637.77 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 25162801.87 | 12455.66 | 17-OCT-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 82177032.14 | 12923.52 | 24-NOV-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.272374E+09 | 15045.82 | 26-DEC-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.922925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.272374E+09 | 17251.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.131391E+10 | 15468.26 | 21-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.906203E+09 | 15540.56 | 24-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174460E+09 | 15550.52 | 08-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 361136.84 | 125.99 | 25-NOV-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.447752E+09 | 15474.12 | 26-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.284269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.131391E+10 | 15550.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.139584E+10 | 15084.62 | 21-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109366E+10 | 15108.63 | 24-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.225285E+09 | 15121.76 | 04-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5364549.65 | 1807.52 | 17-APR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 8978094.88 | 2448.33 | 17-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 74742170.83 | 4612.87 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.989563E+09 | 15141.16 | 05-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.379343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.139584E+10 | 15141.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.172783E+10 | 21145.77 | 19-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137312E+10 | 21134.43 | 02-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.258744E+09 | 21186.82 | 20-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17275531.45 | 9993.70 | 17-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 19980812.93 | 10965.60 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 76697596.29 | 18958.82 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.980712E+09 | 21179.53 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.445436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.172783E+10 | 21186.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.767162E+09 | 13126.95 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.286093E+09 | 13134.70 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3044023.76 | 2923.09 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19380141.77 | 13114.11 | 11-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.107568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.767162E+09 | 13134.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.758894E+10 | 320427.35 | 12-JAN-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.503978E+10 | 289029.39 | 21-FEB-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.549564E+10 | 306617.95 | 06-MAR-20:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145170E+10 | 133368.30 | 03-APR-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3078677.26 | 2987.52 | 01-MAY-06:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2464.37 | 3.46 | 14-JUN-20:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3003.26 | 5.01 | 27-JUL-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 577.89 | 3.85 | 13-AUG-19:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12660858.94 | 11379.87 | 06-SEP-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.996516E+09 | 167312.97 | 17-OCT-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.293976E+10 | 182539.96 | 24-NOV-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.589265E+10 | 307566.50 | 26-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.294207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 577.89 | 3.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.758894E+10 | 320427.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.188992E+11 | 543678.18 | 03-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.623274E+10 | 543223.78 | 21-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.230549E+09 | 540036.91 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.435805E+10 | 542857.95 | 11-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.297205E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.188992E+11 | 543678.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.744087E+11 | 134777.54 | 04-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.611483E+11 | 134777.83 | 27-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.245496E+11 | 134576.33 | 21-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.353183E+10 | 145714.38 | 14-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5755744.10 | 12451.05 | 01-MAY-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 21408597.45 | 4726.97 | 30-SEP-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.294827E+10 | 134650.90 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.121886E+11 | 134628.99 | 21-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.605501E+11 | 134738.71 | 26-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.239353E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.744087E+11 | 145714.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.543122E+11 | 185943.08 | 10-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.435347E+11 | 185959.81 | 14-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151347E+11 | 185989.09 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.303798E+10 | 185495.07 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 73479494.46 | 21490.29 | 01-MAY-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.122899E+09 | 21489.85 | 30-SEP-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.347625E+10 | 185470.89 | 30-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139024E+11 | 185771.70 | 24-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.493119E+11 | 185945.07 | 26-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.182906E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.543122E+11 | 185989.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.511177E+11 | 219658.59 | 04-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.414734E+11 | 219659.07 | 27-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.114545E+11 | 218943.79 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.302301E+10 | 217972.38 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 10662233.09 | 4310.60 | 01-MAY-05:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11211117.65 | 3743.50 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.170347E+10 | 216970.06 | 16-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.901008E+10 | 218283.36 | 24-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.447746E+11 | 219592.99 | 26-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162579E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.511177E+11 | 219659.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.497097E+11 | 187152.06 | 10-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.389312E+11 | 187167.91 | 14-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130655E+11 | 186763.29 | 08-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.235186E+10 | 115980.55 | 17-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 39556921.76 | 9422.31 | 12-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 79078834.24 | 8567.08 | 29-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.254812E+10 | 186555.26 | 16-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.106555E+11 | 186512.50 | 24-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.405075E+11 | 187153.95 | 26-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157888E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.497097E+11 | 187167.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.157645E+10 | 13170.68 | 30-JAN-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154403E+10 | 17468.27 | 06-FEB-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.305834E+09 | 9401.63 | 06-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 44569828.32 | 6000.75 | 12-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3925932.15 | 3129.21 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 399767.00 | 532.55 | 14-JUN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 72221.81 | 64.20 | 06-SEP-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 28731485.73 | 3603.83 | 23-OCT-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 33414982.06 | 4226.93 | 14-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.125060E+10 | 16237.05 | 11-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.478803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.157645E+10 | 17468.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.118983E+11 | 81317.03 | 17-JAN-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.974087E+10 | 81123.15 | 04-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.365474E+10 | 81128.06 | 20-MAR-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.577789E+09 | 80945.99 | 17-APR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.690482E+09 | 81344.91 | 30-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.223797E+10 | 81165.16 | 13-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.962520E+10 | 81323.42 | 18-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.384254E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.118983E+11 | 81344.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.123694E+11 | 15218.79 | 02-JAN-04:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.106023E+11 | 15219.78 | 01-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.549498E+10 | 15212.24 | 01-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153623E+10 | 15217.32 | 03-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.104582E+09 | 15145.47 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 67851588.01 | 15103.69 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147228E+10 | 15261.18 | 30-OCT-04:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.381929E+10 | 15220.11 | 13-NOV-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110618E+11 | 15223.76 | 21-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.465288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.123694E+11 | 15261.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.830479E+10 | 20629.52 | 18-JAN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.700070E+10 | 20640.98 | 04-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.314765E+10 | 20560.95 | 08-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.980582E+09 | 20557.56 | 05-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 98834248.90 | 14177.64 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 226587.38 | 263.24 | 31-AUG-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 72108303.73 | 18969.94 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108622E+10 | 20556.99 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.307989E+10 | 20652.43 | 13-NOV-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.798422E+10 | 20635.44 | 06-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.317552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.830479E+10 | 20652.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.920598E+10 | 23588.85 | 19-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.799674E+10 | 23592.14 | 18-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.326534E+10 | 23523.62 | 21-MAR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.131582E+10 | 23495.32 | 03-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.160160E+09 | 21312.95 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7206846.52 | 2296.92 | 14-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 46809431.15 | 19061.95 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.100460E+10 | 23660.62 | 16-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.298938E+10 | 23592.60 | 29-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.884235E+10 | 23591.01 | 20-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.348344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.920598E+10 | 23660.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.783084E+10 | 21886.95 | 21-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.621026E+10 | 21894.04 | 01-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.279660E+10 | 21883.40 | 08-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.906924E+09 | 21855.21 | 17-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.100970E+09 | 7352.02 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3281240.57 | 1261.30 | 14-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 58883787.42 | 8380.80 | 30-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.992617E+09 | 21837.41 | 30-OCT-03:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.257554E+10 | 21871.94 | 21-NOV-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.661531E+10 | 21892.87 | 06-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.280912E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.783084E+10 | 21894.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.111506E+11 | 29218.88 | 31-JAN-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.954878E+10 | 33198.93 | 06-FEB-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.263946E+10 | 30096.07 | 07-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 66276173.32 | 10425.10 | 17-APR-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 973256.34 | 1688.68 | 04-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 87.78 | 0.88 | 10-JUN-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 237889.35 | 792.96 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2184927.73 | 7282.70 | 17-OCT-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 75907958.52 | 12474.78 | 24-NOV-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.399649E+10 | 31695.20 | 11-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.274809E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.111506E+11 | 33198.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 8769097.31 | 8769097.31 | 837.51 | 20-JAN-08:50 | 837.51 | 0.00 |
February | 0.00 | 0.00 | 8220567.66 | 8220567.66 | 2498.98 | 21-FEB-13:10 | 2498.98 | 0.00 |
March | 0.00 | 0.00 | 0.610699E+10 | 0.594997E+10 | 108647.25 | 14-MAR-13:10 | 94440.98 | 0.04 |
April | 0.00 | 0.00 | 0.263212E+10 | 0.263212E+10 | 54346.80 | 07-APR-14:00 | 54346.80 | 0.02 |
May | 0.00 | 0.00 | 0.194026E+11 | 0.191656E+11 | 105257.32 | 14-MAY-13:52 | 81563.55 | 0.14 |
June | 0.00 | 0.00 | 0.894544E+11 | 0.713440E+11 | 264369.85 | 27-JUN-07:50 | 114090.36 | 0.50 |
July | 0.00 | 0.00 | 0.167387E+12 | 0.121066E+12 | 299993.96 | 20-JUL-05:02 | 120284.74 | 0.73 |
August | 0.00 | 0.00 | 0.140927E+12 | 0.110160E+12 | 293051.56 | 15-AUG-08:20 | 126873.66 | 0.72 |
September | 0.00 | 0.00 | 0.550567E+11 | 0.436255E+11 | 207989.65 | 14-SEP-04:12 | 90656.66 | 0.41 |
October | 0.00 | 0.00 | 0.732506E+10 | 0.731908E+10 | 82047.45 | 11-OCT-15:00 | 82047.45 | 0.10 |
November | 0.00 | 0.00 | 0.118363E+10 | 0.118363E+10 | 55344.78 | 27-NOV-06:03 | 55344.78 | 0.03 |
December | 0.00 | 0.00 | 9810583.93 | 9810583.93 | 2472.16 | 29-DEC-13:10 | 2472.16 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.489502E+12 | 0.382473E+12 | 0.23 | |||
Minimum of Months | 0.00 | 0.00 | 8220567.66 | 8220567.66 | 837.51 | 837.51 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.167387E+12 | 0.121066E+12 | 299993.96 | 126873.66 | 0.73 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1940318.27 | 1940318.27 | 629.95 | 10-JAN-11:00 | 629.95 | 0.00 |
February | 0.00 | 0.00 | 2555142.24 | 2555142.24 | 632.64 | 24-FEB-09:20 | 632.64 | 0.00 |
March | 0.00 | 0.00 | 0.418203E+11 | 0.407695E+11 | 795489.76 | 15-MAR-14:20 | 795489.76 | 0.04 |
April | 0.00 | 0.00 | 0.171151E+11 | 0.171151E+11 | 374391.07 | 07-APR-14:00 | 374391.07 | 0.02 |
May | 0.00 | 0.00 | 0.164502E+12 | 0.162790E+12 | 884519.85 | 10-MAY-14:50 | 798342.68 | 0.14 |
June | 0.00 | 0.00 | 0.677967E+12 | 0.552391E+12 | 1824948.83 | 27-JUN-05:03 | 786454.82 | 0.46 |
July | 0.00 | 0.00 | 0.113901E+13 | 0.854999E+12 | 2694563.80 | 20-JUL-05:02 | 1078105.37 | 0.60 |
August | 0.00 | 0.00 | 0.949497E+12 | 0.775263E+12 | 2565460.99 | 15-AUG-05:03 | 1088449.77 | 0.58 |
September | 0.00 | 0.00 | 0.426760E+12 | 0.347313E+12 | 1576174.26 | 14-SEP-04:12 | 681443.38 | 0.39 |
October | 0.00 | 0.00 | 0.550837E+11 | 0.550577E+11 | 655652.35 | 11-OCT-15:00 | 655652.35 | 0.10 |
November | 0.00 | 0.00 | 0.666324E+10 | 0.666324E+10 | 186546.01 | 16-NOV-13:10 | 186546.01 | 0.02 |
December | 0.00 | 0.00 | 3612400.51 | 3612400.51 | 625.12 | 12-DEC-14:10 | 625.12 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.347843E+13 | 0.281237E+13 | 0.20 | |||
Minimum of Months | 0.00 | 0.00 | 1940318.27 | 1940318.27 | 625.12 | 625.12 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.113901E+13 | 0.854999E+12 | 2694563.80 | 1088449.77 | 0.60 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 6813845.99 | 6813845.99 | 503.88 | 05-JAN-12:20 | 503.88 | 0.00 |
February | 0.00 | 0.00 | 5549010.19 | 5549010.19 | 728.23 | 17-FEB-11:20 | 728.23 | 0.00 |
March | 0.00 | 0.00 | 0.432231E+10 | 0.431950E+10 | 96882.47 | 15-MAR-14:20 | 96882.47 | 0.05 |
April | 0.00 | 0.00 | 0.158821E+10 | 0.158821E+10 | 36544.35 | 07-APR-14:00 | 36544.35 | 0.02 |
May | 0.00 | 0.00 | 0.164003E+11 | 0.162754E+11 | 102657.23 | 14-MAY-14:02 | 81322.07 | 0.13 |
June | 0.00 | 0.00 | 0.736383E+11 | 0.597074E+11 | 303202.15 | 27-JUN-15:00 | 127317.38 | 0.45 |
July | 0.00 | 0.00 | 0.125404E+12 | 0.941735E+11 | 290328.39 | 20-JUL-05:02 | 116214.13 | 0.59 |
August | 0.00 | 0.00 | 0.102448E+12 | 0.832417E+11 | 262640.62 | 15-AUG-05:03 | 111211.42 | 0.57 |
September | 0.00 | 0.00 | 0.422136E+11 | 0.342366E+11 | 180286.31 | 15-SEP-12:40 | 99671.73 | 0.39 |
October | 0.00 | 0.00 | 0.471304E+10 | 0.471304E+10 | 63364.66 | 11-OCT-15:00 | 63364.66 | 0.10 |
November | 0.00 | 0.00 | 0.600387E+09 | 0.600387E+09 | 15330.17 | 16-NOV-13:00 | 15330.17 | 0.03 |
December | 0.00 | 0.00 | 5332230.66 | 5332230.66 | 195.78 | 15-DEC-09:10 | 195.78 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.371346E+12 | 0.298874E+12 | 0.19 | |||
Minimum of Months | 0.00 | 0.00 | 5332230.66 | 5332230.66 | 195.78 | 195.78 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.125404E+12 | 0.941735E+11 | 303202.15 | 127317.38 | 0.59 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 44492354.16 | 44492354.16 | 5797.24 | 11-JAN-16:00 | 5797.24 | 0.01 |
February | 0.00 | 0.00 | 41607905.67 | 41607905.67 | 6531.49 | 22-FEB-17:00 | 6531.49 | 0.00 |
March | 0.00 | 0.00 | 0.448173E+10 | 0.383827E+10 | 67599.62 | 14-MAR-11:00 | 40560.94 | 0.05 |
April | 0.00 | 0.00 | 0.241316E+10 | 0.241316E+10 | 29526.84 | 07-APR-14:00 | 29526.84 | 0.02 |
May | 0.00 | 0.00 | 0.131541E+11 | 0.125266E+11 | 92945.77 | 24-MAY-06:41 | 45139.30 | 0.12 |
June | 0.00 | 0.00 | 0.308475E+11 | 0.251393E+11 | 135560.50 | 28-JUN-14:20 | 83288.12 | 0.23 |
July | 0.00 | 0.00 | 0.448969E+11 | 0.372942E+11 | 158849.51 | 18-JUL-09:00 | 63786.41 | 0.23 |
August | 0.00 | 0.00 | 0.567412E+11 | 0.466993E+11 | 145263.35 | 26-AUG-09:50 | 74037.02 | 0.33 |
September | 0.00 | 0.00 | 0.306227E+11 | 0.248407E+11 | 149154.78 | 15-SEP-11:10 | 78366.29 | 0.27 |
October | 0.00 | 0.00 | 0.485575E+10 | 0.465799E+10 | 78904.57 | 26-OCT-06:14 | 37037.31 | 0.08 |
November | 0.00 | 0.00 | 0.818628E+09 | 0.814456E+09 | 60030.33 | 27-NOV-07:11 | 60030.33 | 0.02 |
December | 0.00 | 0.00 | 3834917.46 | 3623931.72 | 19227.19 | 01-DEC-07:13 | 18143.71 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.188922E+12 | 0.158314E+12 | 0.12 | |||
Minimum of Months | 0.00 | 0.00 | 3834917.46 | 3623931.72 | 5797.24 | 5797.24 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.567412E+11 | 0.466993E+11 | 158849.51 | 83288.12 | 0.33 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.658737E+10 | 0.658733E+10 | 3843.46 | 13-JAN-18:00 | 3843.46 | 0.00 |
February | 0.00 | 0.00 | 0.102941E+11 | 0.102840E+11 | 5069.74 | 15-FEB-00:40 | 5069.74 | 0.00 |
March | 0.00 | 0.00 | 0.314426E+11 | 0.283874E+11 | 314576.80 | 14-MAR-13:00 | 255576.98 | 0.00 |
April | 0.00 | 0.00 | 0.361100E+11 | 0.336622E+11 | 233639.85 | 08-APR-14:00 | 212054.62 | 0.00 |
May | 0.00 | 0.00 | 0.725831E+10 | 0.680324E+10 | 125588.28 | 10-MAY-15:00 | 106052.02 | 0.00 |
June | 0.00 | 0.00 | 0.167102E+12 | 0.118800E+12 | 434071.22 | 27-JUN-14:10 | 226942.85 | 0.00 |
July | 0.00 | 0.00 | 0.711644E+12 | 0.442713E+12 | 545825.33 | 20-JUL-22:12 | 192413.66 | 0.00 |
August | 0.00 | 0.00 | 0.826267E+12 | 0.554841E+12 | 529472.50 | 14-AUG-00:53 | 211325.00 | 0.00 |
September | 0.00 | 0.00 | 0.152209E+11 | 0.113642E+11 | 179441.56 | 15-SEP-12:00 | 107356.03 | 0.00 |
October | 0.00 | 0.00 | 0.854147E+10 | 0.822276E+10 | 88604.69 | 11-OCT-15:00 | 82234.33 | 0.00 |
November | 0.00 | 0.00 | 0.171312E+11 | 0.158337E+11 | 103785.69 | 05-NOV-14:00 | 85014.23 | 0.00 |
December | 0.00 | 0.00 | 0.150102E+11 | 0.146343E+11 | 66445.31 | 01-DEC-11:00 | 44546.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.185261E+13 | 0.125213E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.658737E+10 | 0.658733E+10 | 3843.46 | 3843.46 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.826267E+12 | 0.554841E+12 | 545825.33 | 255576.98 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.306570E+10 | 0.306541E+10 | 2126.38 | 15-JAN-16:35 | 2126.38 | 0.00 |
February | 0.00 | 0.00 | 0.770710E+10 | 0.770710E+10 | 4275.76 | 28-FEB-17:00 | 4275.76 | 0.00 |
March | 0.00 | 0.00 | 0.148823E+11 | 0.148606E+11 | 7561.47 | 31-MAR-24:00 | 7561.47 | 0.00 |
April | 0.00 | 0.00 | 0.198477E+11 | 0.198449E+11 | 8744.04 | 02-APR-17:55 | 8744.04 | 0.00 |
May | 0.00 | 0.00 | 0.563968E+10 | 0.560411E+10 | 4054.00 | 31-MAY-24:00 | 4054.00 | 0.00 |
June | 0.00 | 0.00 | 0.109704E+11 | 0.107882E+11 | 5957.67 | 30-JUN-24:00 | 5957.67 | 0.00 |
July | 0.00 | 0.00 | 0.167161E+11 | 0.164023E+11 | 7897.95 | 31-JUL-23:55 | 7858.36 | 0.00 |
August | 0.00 | 0.00 | 0.215668E+11 | 0.213298E+11 | 8890.53 | 14-AUG-16:00 | 8552.42 | 0.00 |
September | 0.00 | 0.00 | 0.578285E+10 | 0.564988E+10 | 3778.92 | 30-SEP-24:00 | 3778.92 | 0.00 |
October | 0.00 | 0.00 | 0.103283E+11 | 0.102978E+11 | 5725.17 | 31-OCT-24:00 | 5725.17 | 0.00 |
November | 0.00 | 0.00 | 0.145532E+11 | 0.145515E+11 | 6158.49 | 15-NOV-16:20 | 6158.49 | 0.00 |
December | 0.00 | 0.00 | 0.193290E+11 | 0.193286E+11 | 7849.76 | 04-DEC-16:10 | 7849.76 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.150389E+12 | 0.149430E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.306570E+10 | 0.306541E+10 | 2126.38 | 2126.38 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.215668E+11 | 0.213298E+11 | 8890.53 | 8744.04 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.606778E+10 | 0.606778E+10 | 15233.91 | 12-JAN-16:50 | 15233.91 | 0.00 |
February | 0.00 | 0.00 | 0.498910E+11 | 0.498910E+11 | 37607.26 | 28-FEB-17:00 | 37607.26 | 0.00 |
March | 0.00 | 0.00 | 0.125026E+12 | 0.124810E+12 | 66914.47 | 31-MAR-23:40 | 66914.47 | 0.00 |
April | 0.00 | 0.00 | 0.178094E+12 | 0.178064E+12 | 79891.59 | 02-APR-18:00 | 79891.59 | 0.00 |
May | 0.00 | 0.00 | 0.480971E+11 | 0.477468E+11 | 38290.39 | 31-MAY-24:00 | 38290.39 | 0.00 |
June | 0.00 | 0.00 | 0.101771E+12 | 0.999606E+11 | 56898.13 | 30-JUN-24:00 | 56898.13 | 0.00 |
July | 0.00 | 0.00 | 0.157714E+12 | 0.154590E+12 | 75836.48 | 31-JUL-23:55 | 75450.25 | 0.00 |
August | 0.00 | 0.00 | 0.203873E+12 | 0.201510E+12 | 84489.21 | 04-AUG-18:40 | 84489.21 | 0.00 |
September | 0.00 | 0.00 | 0.493376E+11 | 0.480348E+11 | 32130.58 | 30-SEP-24:00 | 32130.58 | 0.00 |
October | 0.00 | 0.00 | 0.854001E+11 | 0.850951E+11 | 49967.88 | 31-OCT-23:50 | 49967.88 | 0.00 |
November | 0.00 | 0.00 | 0.120220E+12 | 0.120201E+12 | 56756.59 | 15-NOV-16:20 | 56756.59 | 0.00 |
December | 0.00 | 0.00 | 0.155618E+12 | 0.155613E+12 | 69957.26 | 04-DEC-16:20 | 69957.26 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.128111E+13 | 0.127158E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.606778E+10 | 0.606778E+10 | 15233.91 | 15233.91 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.203873E+12 | 0.201510E+12 | 84489.21 | 84489.21 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.147746E+09 | 0.147746E+09 | 1320.07 | 12-JAN-16:40 | 1320.07 | 0.00 |
February | 0.00 | 0.00 | 0.340997E+10 | 0.340997E+10 | 3719.55 | 28-FEB-17:00 | 3719.55 | 0.00 |
March | 0.00 | 0.00 | 0.110103E+11 | 0.109888E+11 | 6288.36 | 31-MAR-23:20 | 6288.36 | 0.00 |
April | 0.00 | 0.00 | 0.167924E+11 | 0.167895E+11 | 7966.24 | 24-APR-18:00 | 7966.24 | 0.00 |
May | 0.00 | 0.00 | 0.435485E+10 | 0.432020E+10 | 3738.30 | 31-MAY-23:40 | 3738.30 | 0.00 |
June | 0.00 | 0.00 | 0.100900E+11 | 0.990893E+10 | 5623.46 | 30-JUN-23:40 | 5623.46 | 0.00 |
July | 0.00 | 0.00 | 0.158092E+11 | 0.154969E+11 | 7581.37 | 31-JUL-23:55 | 7542.61 | 0.00 |
August | 0.00 | 0.00 | 0.203478E+11 | 0.201119E+11 | 8529.34 | 04-AUG-18:40 | 8529.34 | 0.00 |
September | 0.00 | 0.00 | 0.452527E+10 | 0.439575E+10 | 2955.36 | 04-SEP-17:43 | 2955.36 | 0.00 |
October | 0.00 | 0.00 | 0.725508E+10 | 0.722491E+10 | 4609.59 | 11-OCT-17:00 | 4542.92 | 0.00 |
November | 0.00 | 0.00 | 0.103636E+11 | 0.103618E+11 | 5565.57 | 15-NOV-16:20 | 5565.57 | 0.00 |
December | 0.00 | 0.00 | 0.136883E+11 | 0.136878E+11 | 6685.20 | 04-DEC-16:20 | 6685.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.117794E+12 | 0.116844E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.147746E+09 | 0.147746E+09 | 1320.07 | 1320.07 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.203478E+11 | 0.201119E+11 | 8529.34 | 8529.34 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 120247.13 | 2161022.68 | 02-JAN-04:01 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 103946.68 | 1700791.47 | 13-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 34199.59 | 1661121.65 | 06-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7249.70 | 1125367.52 | 03-APR-05:02 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 225.45 | 104187.33 | 01-MAY-05:02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 3.98 | 2772.39 | 14-JUN-05:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 4.54 | 27-JUL-05:50 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.08 | 243.55 | 31-AUG-05:50 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 188.90 | 123866.90 | 30-SEP-05:02 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 6320.58 | 1370907.27 | 16-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 24467.72 | 1444018.95 | 18-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 95656.44 | 1783508.16 | 11-DEC-05:01 |
Annual Sum or Average | 0.00 | 32394.37 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 4.54 | ||
Maximum of Months | 0.00 | 0.00 | 120247.13 | 2161022.68 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 180.36 | 7119.04 | 11-JAN-07:30 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 166.96 | 8404.40 | 22-FEB-17:00 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 22830.81 | 1276273.37 | 15-MAR-13:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 9661.71 | 496362.72 | 07-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 81362.94 | 1467344.24 | 10-MAY-14:50 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 350565.29 | 2123844.82 | 27-JUN-07:40 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 574398.64 | 2765884.56 | 20-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 485050.81 | 2793450.63 | 15-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 221978.19 | 2273898.01 | 21-SEP-13:07 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 27426.74 | 849377.74 | 11-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 3800.42 | 252523.58 | 16-NOV-13:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 179.54 | 32560.86 | 01-DEC-07:13 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 149367.58 | 0.00 | ||||
Minimum of Months | 166.96 | 7119.04 | 0.00 | 0.00 | ||
Maximum of Months | 574398.64 | 2793450.63 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 7.53 | 4011.47 | 11-JAN-07:30 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 14.51 | 4567.90 | 22-FEB-17:00 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 22483.54 | 1276130.00 | 15-MAR-13:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 9168.11 | 493489.95 | 07-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 80101.87 | 1361488.97 | 10-MAY-14:40 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 348262.27 | 3283121.79 | 27-JUN-05:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 572440.35 | 4017525.26 | 20-JUL-03:02 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 484683.06 | 3813715.04 | 14-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 221578.62 | 3074080.70 | 16-SEP-05:03 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 26839.69 | 847276.77 | 11-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 3562.48 | 256338.81 | 16-NOV-11:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 7.39 | 40921.01 | 01-DEC-07:12 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 148660.32 | 0.00 | ||||
Minimum of Months | 7.39 | 4011.47 | 0.00 | 0.00 | ||
Maximum of Months | 572440.35 | 4017525.26 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 12152.82 | 31395.84 | 12-JAN-16:40 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 41911.14 | 67839.77 | 28-FEB-17:00 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 102771.79 | 1091130.35 | 15-MAR-14:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 127516.30 | 717036.94 | 08-APR-13:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 57505.32 | 718700.76 | 10-MAY-15:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 309913.01 | 1335211.67 | 27-JUN-14:20 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 823581.27 | 1699851.56 | 21-JUL-02:40 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 869967.57 | 1780937.22 | 13-AUG-15:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 107865.16 | 834953.38 | 16-SEP-14:30 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 61644.94 | 463728.80 | 11-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 83866.07 | 350505.58 | 05-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 99191.34 | 187831.06 | 01-DEC-11:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 227067.38 | 0.00 | ||||
Minimum of Months | 12152.82 | 31395.84 | 0.00 | 0.00 | ||
Maximum of Months | 869967.57 | 1780937.22 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 15565.49 | 55761.22 | 31-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 15883.48 | 55957.88 | 15-FEB-13:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 16653.06 | 55779.79 | 01-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 14992.80 | 54071.95 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 14631.73 | 51559.64 | 01-MAY-11:30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14076.09 | 48363.93 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 12326.76 | 45521.89 | 03-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 13253.10 | 44047.85 | 01-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12640.59 | 45462.26 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 13239.12 | 48280.13 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 14277.44 | 51375.00 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14571.55 | 54008.42 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 14333.73 | ||||
Minimum of Months | 0.00 | 0.00 | 12326.76 | 44047.85 | ||
Maximum of Months | 0.00 | 0.00 | 16653.06 | 55957.88 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 7.09 | 12243.84 | 11-JAN-15:00 | 2440.12 | 146466.49 | 28-JAN-07:03 |
February | 6.48 | 8684.76 | 28-FEB-09:50 | 1813.65 | 160223.64 | 17-FEB-05:01 |
March | 29688.59 | 2038868.76 | 14-MAR-13:10 | 1950.10 | 140094.87 | 27-MAR-10:20 |
April | 8533.39 | 560304.24 | 07-APR-14:00 | 2250.34 | 126529.01 | 17-APR-06:03 |
May | 91280.29 | 2734960.74 | 10-MAY-14:40 | 1713.50 | 98522.51 | 06-MAY-10:50 |
June | 577790.30 | 5526515.13 | 27-JUN-07:40 | 506.36 | 84360.95 | 05-JUN-19:30 |
July | 1149899.42 | 6073603.75 | 05-JUL-16:00 | 183.33 | 53612.42 | 06-JUL-22:20 |
August | 836177.24 | 6108767.57 | 14-AUG-10:20 | 672.19 | 70926.18 | 31-AUG-08:70 |
September | 333140.86 | 4664626.85 | 15-SEP-11:00 | 464.38 | 69404.85 | 06-SEP-08:50 |
October | 29731.30 | 959522.84 | 11-OCT-15:00 | 873.64 | 119092.28 | 17-OCT-10:00 |
November | 3919.34 | 292377.52 | 16-NOV-13:10 | 1289.24 | 142347.73 | 24-NOV-07:03 |
December | 10.46 | 12439.49 | 01-DEC-10:50 | 2134.02 | 155815.42 | 07-DEC-07:03 |
Annual Sum or Average | 257376.23 | 1356.34 | ||||
Minimum of Months | 6.48 | 8684.76 | 183.33 | 53612.42 | ||
Maximum of Months | 1149899.42 | 6108767.57 | 2440.12 | 160223.64 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.354026E+10 | 0.31 | 13580.01 | 03-JAN-06:01 | 1.40 |
February | 0.349881E+10 | 0.32 | 13580.01 | 03-FEB-06:01 | 1.40 |
March | 0.629173E+10 | 0.41 | 14568.51 | 15-MAR-14:20 | 1.44 |
April | 0.790977E+10 | 0.47 | 15480.71 | 24-APR-15:20 | 1.51 |
May | 0.818533E+10 | 0.47 | 14626.20 | 24-MAY-05:03 | 1.45 |
June | 0.132760E+11 | 0.65 | 22397.53 | 12-JUN-05:02 | 1.89 |
July | 0.169317E+11 | 0.76 | 22397.53 | 18-JUL-10:10 | 1.89 |
August | 0.171006E+11 | 0.78 | 22397.53 | 07-AUG-05:02 | 1.89 |
September | 0.949011E+10 | 0.51 | 22397.53 | 15-SEP-04:12 | 1.89 |
October | 0.671499E+10 | 0.41 | 15005.69 | 11-OCT-15:50 | 1.47 |
November | 0.551748E+10 | 0.38 | 11942.49 | 27-NOV-05:12 | 1.28 |
December | 0.439194E+10 | 0.33 | 13580.01 | 08-DEC-06:01 | 1.40 |
Annual Sum or Average | 0.102849E+12 | 0.48 | |||
Minimum of Months | 0.349881E+10 | 0.31 | 11942.49 | 1.28 | |
Maximum of Months | 0.171006E+11 | 0.78 | 22397.53 | 1.89 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.340535E+11 | 0.35 | 55554.04 | 02-JAN-04:01 | 0.86 |
February | 0.303578E+11 | 0.34 | 55554.04 | 06-FEB-05:01 | 0.86 |
March | 0.389138E+11 | 0.35 | 99181.57 | 18-MAR-05:03 | 1.20 |
April | 0.425217E+11 | 0.35 | 112302.45 | 11-APR-05:03 | 1.29 |
May | 0.612237E+11 | 0.42 | 114566.55 | 31-MAY-15:50 | 1.30 |
June | 0.887801E+11 | 0.53 | 210263.33 | 19-JUN-05:02 | 1.90 |
July | 0.100352E+12 | 0.54 | 210263.33 | 05-JUL-05:03 | 1.90 |
August | 0.986252E+11 | 0.54 | 210263.33 | 07-AUG-04:12 | 1.90 |
September | 0.654911E+11 | 0.43 | 210263.33 | 21-SEP-13:03 | 1.90 |
October | 0.414067E+11 | 0.33 | 108382.64 | 18-OCT-05:02 | 1.27 |
November | 0.319081E+11 | 0.31 | 106440.04 | 07-NOV-06:02 | 1.25 |
December | 0.320866E+11 | 0.33 | 55554.04 | 11-DEC-05:01 | 0.86 |
Annual Sum or Average | 0.665720E+12 | 0.40 | |||
Minimum of Months | 0.303578E+11 | 0.31 | 55554.04 | 0.86 | |
Maximum of Months | 0.100352E+12 | 0.54 | 210263.33 | 1.90 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.419892E+10 | 0.41 | 5279.71 | 02-JAN-04:01 | 0.79 |
February | 0.384386E+10 | 0.41 | 5279.71 | 01-FEB-05:11 | 0.79 |
March | 0.395372E+10 | 0.36 | 10270.44 | 15-MAR-14:20 | 1.15 |
April | 0.368872E+10 | 0.33 | 8970.18 | 21-APR-15:20 | 1.07 |
May | 0.535629E+10 | 0.38 | 12446.74 | 31-MAY-16:00 | 1.30 |
June | 0.877077E+10 | 0.49 | 19196.73 | 19-JUN-05:02 | 1.70 |
July | 0.103605E+11 | 0.52 | 22721.93 | 19-JUL-05:02 | 1.89 |
August | 0.969615E+10 | 0.51 | 22721.93 | 14-AUG-04:12 | 1.89 |
September | 0.572195E+10 | 0.39 | 15396.11 | 21-SEP-16:00 | 1.48 |
October | 0.349596E+10 | 0.31 | 8544.10 | 11-OCT-16:00 | 1.04 |
November | 0.300622E+10 | 0.30 | 5279.71 | 13-NOV-05:11 | 0.79 |
December | 0.398109E+10 | 0.39 | 5279.71 | 04-DEC-04:11 | 0.79 |
Annual Sum or Average | 0.660741E+11 | 0.40 | |||
Minimum of Months | 0.300622E+10 | 0.30 | 5279.71 | 0.79 | |
Maximum of Months | 0.103605E+11 | 0.52 | 22721.93 | 1.89 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.248255E+10 | 0.32 | 12970.40 | 02-JAN-07:05 | 1.92 |
February | 0.163019E+10 | 0.29 | 12970.40 | 02-FEB-07:05 | 1.93 |
March | 0.398163E+10 | 0.40 | 12970.40 | 01-MAR-07:03 | 1.94 |
April | 0.796883E+10 | 0.57 | 12970.40 | 01-APR-06:05 | 1.93 |
May | 0.126868E+11 | 0.76 | 12970.40 | 01-MAY-06:05 | 1.93 |
June | 0.107568E+11 | 0.65 | 12970.40 | 01-JUN-06:10 | 1.92 |
July | 0.779399E+10 | 0.44 | 12970.40 | 01-JUL-06:10 | 1.92 |
August | 0.116828E+11 | 0.66 | 12970.40 | 01-AUG-06:10 | 1.91 |
September | 0.114098E+11 | 0.69 | 12970.40 | 01-SEP-06:10 | 1.92 |
October | 0.146452E+11 | 0.84 | 12970.40 | 02-OCT-06:05 | 1.93 |
November | 0.123092E+11 | 0.76 | 12970.40 | 01-NOV-06:05 | 1.93 |
December | 0.434352E+10 | 0.39 | 12970.40 | 01-DEC-07:10 | 1.93 |
Annual Sum or Average | 0.101691E+12 | 0.57 | |||
Minimum of Months | 0.163019E+10 | 0.29 | 12970.40 | 1.91 | |
Maximum of Months | 0.146452E+11 | 0.84 | 12970.40 | 1.94 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.111110E+12 | 1.38 | 41483.87 | 01-JAN-00:03 | 1.38 |
February | 0.100358E+12 | 1.38 | 41483.87 | 01-FEB-00:05 | 1.38 |
March | 0.111110E+12 | 1.38 | 41483.87 | 01-MAR-00:10 | 1.39 |
April | 0.107526E+12 | 1.38 | 41483.87 | 01-APR-00:10 | 1.38 |
May | 0.111110E+12 | 1.38 | 41483.87 | 01-MAY-00:10 | 1.38 |
June | 0.107526E+12 | 1.37 | 41483.87 | 01-JUN-00:10 | 1.38 |
July | 0.111110E+12 | 1.37 | 41483.87 | 01-JUL-00:10 | 1.38 |
August | 0.111110E+12 | 1.37 | 41483.87 | 01-AUG-00:03 | 1.37 |
September | 0.107526E+12 | 1.38 | 41483.87 | 01-SEP-00:10 | 1.38 |
October | 0.111110E+12 | 1.38 | 41483.87 | 01-OCT-00:10 | 1.38 |
November | 0.107526E+12 | 1.38 | 41483.87 | 01-NOV-00:10 | 1.38 |
December | 0.111110E+12 | 1.39 | 41483.87 | 01-DEC-00:10 | 1.39 |
Annual Sum or Average | 0.130824E+13 | 1.38 | |||
Minimum of Months | 0.100358E+12 | 1.37 | 41483.87 | 1.37 | |
Maximum of Months | 0.111110E+12 | 1.39 | 41483.87 | 1.39 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.150693E+10 | 0.94 | 562.62 | 01-JAN-00:03 | 0.94 |
February | 0.136110E+10 | 0.94 | 562.62 | 01-FEB-00:05 | 0.95 |
March | 0.150693E+10 | 0.94 | 562.62 | 01-MAR-00:10 | 0.94 |
April | 0.145832E+10 | 0.94 | 562.62 | 01-APR-00:10 | 0.94 |
May | 0.150693E+10 | 0.94 | 562.62 | 01-MAY-00:10 | 0.94 |
June | 0.145832E+10 | 0.94 | 562.62 | 01-JUN-00:10 | 0.94 |
July | 0.150693E+10 | 0.94 | 562.62 | 01-JUL-00:10 | 0.94 |
August | 0.150693E+10 | 0.94 | 562.62 | 01-AUG-00:03 | 0.94 |
September | 0.145832E+10 | 0.94 | 562.62 | 01-SEP-00:10 | 0.94 |
October | 0.150693E+10 | 0.94 | 562.62 | 01-OCT-00:10 | 0.94 |
November | 0.145832E+10 | 0.94 | 562.62 | 01-NOV-00:10 | 0.94 |
December | 0.150693E+10 | 0.94 | 562.62 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.177429E+11 | 0.94 | |||
Minimum of Months | 0.136110E+10 | 0.94 | 562.62 | 0.94 | |
Maximum of Months | 0.150693E+10 | 0.94 | 562.62 | 0.95 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.144498E+11 | 0.94 | 5394.93 | 01-JAN-00:03 | 0.94 |
February | 0.130514E+11 | 0.94 | 5394.93 | 01-FEB-00:05 | 0.95 |
March | 0.144498E+11 | 0.94 | 5394.93 | 01-MAR-00:10 | 0.94 |
April | 0.139836E+11 | 0.94 | 5394.93 | 01-APR-00:10 | 0.94 |
May | 0.144498E+11 | 0.94 | 5394.93 | 01-MAY-00:10 | 0.94 |
June | 0.139836E+11 | 0.94 | 5394.93 | 01-JUN-00:10 | 0.94 |
July | 0.144498E+11 | 0.94 | 5394.93 | 01-JUL-00:10 | 0.94 |
August | 0.144498E+11 | 0.94 | 5394.93 | 01-AUG-00:03 | 0.94 |
September | 0.139836E+11 | 0.94 | 5394.93 | 01-SEP-00:10 | 0.94 |
October | 0.144498E+11 | 0.94 | 5394.93 | 01-OCT-00:10 | 0.94 |
November | 0.139836E+11 | 0.94 | 5394.93 | 01-NOV-00:10 | 0.94 |
December | 0.144498E+11 | 0.94 | 5394.93 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.170134E+12 | 0.94 | |||
Minimum of Months | 0.130514E+11 | 0.94 | 5394.93 | 0.94 | |
Maximum of Months | 0.144498E+11 | 0.94 | 5394.93 | 0.95 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.146890E+10 | 0.94 | 548.42 | 01-JAN-00:03 | 0.94 |
February | 0.132675E+10 | 0.94 | 548.42 | 01-FEB-00:05 | 0.95 |
March | 0.146890E+10 | 0.94 | 548.42 | 01-MAR-00:10 | 0.94 |
April | 0.142152E+10 | 0.94 | 548.42 | 01-APR-00:10 | 0.94 |
May | 0.146890E+10 | 0.94 | 548.42 | 01-MAY-00:10 | 0.94 |
June | 0.142152E+10 | 0.94 | 548.42 | 01-JUN-00:10 | 0.94 |
July | 0.146890E+10 | 0.94 | 548.42 | 01-JUL-00:10 | 0.94 |
August | 0.146890E+10 | 0.94 | 548.42 | 01-AUG-00:03 | 0.94 |
September | 0.142152E+10 | 0.94 | 548.42 | 01-SEP-00:10 | 0.94 |
October | 0.146890E+10 | 0.94 | 548.42 | 01-OCT-00:10 | 0.94 |
November | 0.142152E+10 | 0.94 | 548.42 | 01-NOV-00:10 | 0.94 |
December | 0.146890E+10 | 0.94 | 548.42 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.172951E+11 | 0.94 | |||
Minimum of Months | 0.132675E+10 | 0.94 | 548.42 | 0.94 | |
Maximum of Months | 0.146890E+10 | 0.94 | 548.42 | 0.95 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 39542993.82 | 35588694.44 | 1219.73 | 02-JAN-06:01 | 1097.76 | 1097.76 | 49.76 | 11.22 |
February | 28932744.33 | 26039469.89 | 1219.51 | 06-FEB-06:02 | 1097.56 | 1097.56 | 49.68 | 11.22 |
March | 6841836.31 | 6157652.68 | 1178.00 | 06-MAR-06:01 | 1060.20 | 1060.20 | 46.09 | 11.07 |
April | 942834.21 | 848550.79 | 268.45 | 17-APR-05:03 | 241.60 | 241.60 | 39.72 | 5.68 |
May | 15627.53 | 14064.78 | 3.47 | 01-MAY-05:02 | 3.12 | 3.12 | 21.43 | 0.41 |
June | 251.74 | 226.56 | 0.07 | 14-JUN-05:10 | 0.06 | 0.06 | 21.09 | 0.01 |
July | 0.07 | 0.06 | 0.00 | 27-JUL-05:50 | 0.00 | 0.00 | 21.01 | 0.00 |
August | 5.09 | 4.58 | 0.01 | 31-AUG-05:50 | 0.01 | 0.01 | 21.00 | 0.00 |
September | 12978.69 | 11680.82 | 4.30 | 30-SEP-05:02 | 3.87 | 3.87 | 21.02 | 0.49 |
October | 824660.24 | 742194.22 | 387.02 | 30-OCT-05:01 | 348.32 | 348.32 | 37.16 | 6.75 |
November | 3403756.56 | 3063380.91 | 381.82 | 25-NOV-06:01 | 343.64 | 343.64 | 38.78 | 6.70 |
December | 25588745.08 | 23029870.57 | 1211.77 | 11-DEC-06:01 | 1090.60 | 1090.60 | 47.21 | 11.20 |
Annual Sum or Average | 0.106106E+09 | 95495790.29 | ||||||
Minimum of Months | 0.07 | 0.06 | 0.00 | 0.00 | 0.00 | 21.00 | 0.00 | |
Maximum of Months | 39542993.82 | 35588694.44 | 1219.73 | 1097.76 | 1097.76 | 49.76 | 11.22 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 27438.52 | 24694.67 | 22.55 | 11-JAN-07:30 | 20.29 | 20.29 | 6.70 | 3.45 |
February | 10326.25 | 9293.62 | 1.26 | 22-FEB-17:00 | 1.14 | 1.14 | 6.70 | 0.35 |
March | 43851497.10 | 39466347.39 | 1953.11 | 15-MAR-13:30 | 1757.80 | 1757.80 | 6.71 | 35.67 |
April | 6238800.32 | 5614920.29 | 192.94 | 08-APR-13:00 | 173.65 | 173.65 | 6.70 | 11.99 |
May | 96653538.58 | 86988184.72 | 1466.91 | 26-MAY-15:00 | 1320.22 | 1320.22 | 6.71 | 31.47 |
June | 0.635720E+09 | 0.572148E+09 | 11221.32 | 27-JUN-05:03 | 10099.18 | 10099.18 | 9.88 | 73.30 |
July | 0.122090E+10 | 0.109881E+10 | 11227.62 | 22-JUL-05:05 | 10104.85 | 10104.85 | 11.80 | 73.30 |
August | 0.112391E+10 | 0.101152E+10 | 11221.34 | 15-AUG-04:12 | 10099.21 | 10099.21 | 9.90 | 73.30 |
September | 0.460712E+09 | 0.414641E+09 | 12605.76 | 21-SEP-13:03 | 11345.18 | 11345.18 | 11.60 | 76.75 |
October | 45007790.40 | 40507011.36 | 1309.37 | 11-OCT-12:10 | 1178.43 | 1178.43 | 6.71 | 29.93 |
November | 2938819.73 | 2644937.76 | 127.05 | 16-NOV-12:00 | 114.35 | 114.35 | 6.70 | 9.62 |
December | 4037.25 | 3633.52 | 10.56 | 01-DEC-07:13 | 9.50 | 9.50 | 6.70 | 2.03 |
Annual Sum or Average | 0.363598E+10 | 0.327238E+10 | ||||||
Minimum of Months | 4037.25 | 3633.52 | 1.26 | 1.14 | 1.14 | 6.70 | 0.35 | |
Maximum of Months | 0.122090E+10 | 0.109881E+10 | 12605.76 | 11345.18 | 11345.18 | 11.80 | 76.75 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER1 PUMP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.514871E+09 | 0.463384E+09 | 4338.10 | 02-JAN-07:05 | 3904.29 | 3904.29 | 6.72 | 38.37 |
February | 0.409783E+09 | 0.368805E+09 | 4338.10 | 01-FEB-11:30 | 3904.29 | 3904.29 | 6.72 | 38.37 |
March | 0.113552E+10 | 0.102197E+10 | 4338.10 | 01-MAR-07:03 | 3904.29 | 3904.29 | 6.72 | 38.37 |
April | 0.143459E+10 | 0.129113E+10 | 4338.10 | 01-APR-07:35 | 3904.29 | 3904.29 | 6.73 | 38.37 |
May | 0.399923E+10 | 0.359931E+10 | 4338.10 | 01-MAY-16:00 | 3904.29 | 3904.29 | 6.73 | 38.37 |
June | 0.689051E+10 | 0.620146E+10 | 4338.10 | 01-JUN-04:12 | 3904.29 | 3904.29 | 8.23 | 38.37 |
July | 0.906063E+10 | 0.815457E+10 | 4338.10 | 01-JUL-04:12 | 3904.29 | 3904.29 | 7.91 | 38.37 |
August | 0.885907E+10 | 0.797316E+10 | 4338.10 | 01-AUG-00:03 | 3904.29 | 3904.29 | 6.85 | 38.37 |
September | 0.542827E+10 | 0.488544E+10 | 4338.10 | 01-SEP-04:12 | 3904.29 | 3904.29 | 7.62 | 38.37 |
October | 0.180423E+10 | 0.162380E+10 | 4338.10 | 02-OCT-07:00 | 3904.29 | 3904.29 | 6.75 | 38.37 |
November | 0.686938E+09 | 0.618245E+09 | 4338.10 | 01-NOV-09:30 | 3904.29 | 3904.29 | 6.74 | 38.37 |
December | 0.512315E+09 | 0.461084E+09 | 4338.10 | 01-DEC-07:12 | 3904.29 | 3904.29 | 6.81 | 38.37 |
Annual Sum or Average | 0.407359E+11 | 0.366624E+11 | ||||||
Minimum of Months | 0.409783E+09 | 0.368805E+09 | 4338.10 | 3904.29 | 3904.29 | 6.72 | 38.37 | |
Maximum of Months | 0.906063E+10 | 0.815457E+10 | 4338.10 | 3904.29 | 3904.29 | 8.23 | 38.37 |
Report: PumpReportMonthly
For: COOLSYS1 CHILLER2 PUMP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 6.70 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 6.72 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 6.73 | 0.00 |
May | 5205722.30 | 4685150.07 | 4338.10 | 10-MAY-14:40 | 3904.29 | 3904.29 | 15.17 | 19.19 |
June | 0.886274E+09 | 0.797647E+09 | 4338.10 | 01-JUN-15:00 | 3904.29 | 3904.29 | 15.21 | 19.19 |
July | 0.203921E+10 | 0.183529E+10 | 4338.10 | 03-JUL-12:30 | 3904.29 | 3904.29 | 15.57 | 19.19 |
August | 0.139965E+10 | 0.125968E+10 | 4338.10 | 01-AUG-14:50 | 3904.29 | 3904.29 | 17.53 | 19.19 |
September | 0.419061E+09 | 0.377155E+09 | 4338.10 | 08-SEP-13:10 | 3904.29 | 3904.29 | 15.52 | 19.19 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 6.87 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 6.80 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 6.72 | 0.00 |
Annual Sum or Average | 0.474940E+10 | 0.427446E+10 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 | |
Maximum of Months | 0.203921E+10 | 0.183529E+10 | 4338.10 | 3904.29 | 3904.29 | 17.53 | 19.19 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.102413E+11 | 0.921713E+10 | 3823.65 | 01-JAN-00:03 | 3441.28 | 3441.28 | 18.49 | 15.97 |
February | 0.925017E+10 | 0.832515E+10 | 3823.65 | 01-FEB-00:05 | 3441.28 | 3441.28 | 18.94 | 15.97 |
March | 0.102413E+11 | 0.921713E+10 | 3823.65 | 01-MAR-00:10 | 3441.28 | 3441.28 | 19.66 | 15.97 |
April | 0.991090E+10 | 0.891981E+10 | 3823.65 | 01-APR-00:10 | 3441.28 | 3441.28 | 20.32 | 15.97 |
May | 0.102413E+11 | 0.921713E+10 | 3823.65 | 01-MAY-00:10 | 3441.28 | 3441.28 | 18.90 | 15.97 |
June | 0.991090E+10 | 0.891981E+10 | 3823.65 | 01-JUN-00:10 | 3441.28 | 3441.28 | 19.42 | 15.97 |
July | 0.102413E+11 | 0.921713E+10 | 3823.65 | 01-JUL-00:10 | 3441.28 | 3441.28 | 20.05 | 15.97 |
August | 0.102413E+11 | 0.921713E+10 | 3823.65 | 01-AUG-00:03 | 3441.28 | 3441.28 | 31.18 | 15.97 |
September | 0.991090E+10 | 0.891981E+10 | 3823.65 | 01-SEP-00:10 | 3441.28 | 3441.28 | 18.89 | 15.97 |
October | 0.102413E+11 | 0.921713E+10 | 3823.65 | 01-OCT-00:10 | 3441.28 | 3441.28 | 19.26 | 15.97 |
November | 0.991090E+10 | 0.891981E+10 | 3823.65 | 01-NOV-00:10 | 3441.28 | 3441.28 | 19.87 | 15.97 |
December | 0.102413E+11 | 0.921713E+10 | 3823.65 | 01-DEC-00:10 | 3441.28 | 3441.28 | 20.19 | 15.97 |
Annual Sum or Average | 0.120583E+12 | 0.108524E+12 | ||||||
Minimum of Months | 0.925017E+10 | 0.832515E+10 | 3823.65 | 3441.28 | 3441.28 | 18.49 | 15.97 | |
Maximum of Months | 0.102413E+11 | 0.921713E+10 | 3823.65 | 3441.28 | 3441.28 | 31.18 | 15.97 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.112905E+09 | 33871561.48 | 56.21 | 01-JAN-06:03 | 16.86 | 16.86 | 56.88 | 0.44 |
February | 0.101979E+09 | 30593668.43 | 56.21 | 01-FEB-06:02 | 16.86 | 16.86 | 56.79 | 0.44 |
March | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAR-06:01 | 16.86 | 16.86 | 56.93 | 0.44 |
April | 0.109263E+09 | 32778930.46 | 56.21 | 01-APR-05:02 | 16.86 | 16.86 | 56.88 | 0.44 |
May | 0.112905E+09 | 33871561.48 | 56.21 | 01-MAY-05:02 | 16.86 | 16.86 | 57.25 | 0.44 |
June | 0.109263E+09 | 32778930.46 | 56.21 | 01-JUN-05:03 | 16.86 | 16.86 | 57.16 | 0.44 |
July | 0.112905E+09 | 33871561.48 | 56.21 | 01-JUL-05:03 | 16.86 | 16.86 | 57.33 | 0.44 |
August | 0.112905E+09 | 33871561.48 | 56.21 | 01-AUG-05:03 | 16.86 | 16.86 | 57.42 | 0.44 |
September | 0.109263E+09 | 32778930.46 | 56.21 | 01-SEP-05:03 | 16.86 | 16.86 | 57.35 | 0.44 |
October | 0.112905E+09 | 33871561.48 | 56.21 | 01-OCT-05:10 | 16.86 | 16.86 | 57.09 | 0.44 |
November | 0.109263E+09 | 32778930.46 | 56.21 | 01-NOV-05:02 | 16.86 | 16.86 | 57.22 | 0.44 |
December | 0.112905E+09 | 33871561.48 | 56.21 | 01-DEC-06:03 | 16.86 | 16.86 | 56.98 | 0.44 |
Annual Sum or Average | 0.132937E+10 | 0.398810E+09 | ||||||
Minimum of Months | 0.101979E+09 | 30593668.43 | 56.21 | 16.86 | 16.86 | 56.79 | 0.44 | |
Maximum of Months | 0.112905E+09 | 33871561.48 | 56.21 | 16.86 | 16.86 | 57.42 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.197708E+10 | 0.177937E+10 | 16660.98 | 11-JAN-15:00 | 14994.88 | 14994.88 | 21.14 | 67.54 |
February | 0.157359E+10 | 0.141623E+10 | 16660.83 | 28-FEB-09:50 | 14994.75 | 14994.75 | 21.13 | 67.54 |
March | 0.436421E+10 | 0.392779E+10 | 16753.94 | 14-MAR-13:10 | 15078.55 | 15078.55 | 28.32 | 67.54 |
April | 0.551022E+10 | 0.495920E+10 | 16684.25 | 07-APR-14:00 | 15015.83 | 15015.83 | 23.08 | 67.54 |
May | 0.153893E+11 | 0.138503E+11 | 33441.12 | 10-MAY-14:40 | 30097.01 | 30097.01 | 25.94 | 135.08 |
June | 0.295929E+11 | 0.266336E+11 | 33539.50 | 27-JUN-07:30 | 30185.55 | 30185.55 | 30.19 | 135.08 |
July | 0.421788E+11 | 0.379609E+11 | 33539.50 | 05-JUL-10:00 | 30185.55 | 30185.55 | 29.59 | 135.08 |
August | 0.390922E+11 | 0.351830E+11 | 33539.50 | 07-AUG-14:40 | 30185.55 | 30185.55 | 29.64 | 135.08 |
September | 0.222645E+11 | 0.200381E+11 | 33537.16 | 15-SEP-11:00 | 30183.44 | 30183.44 | 29.36 | 135.08 |
October | 0.693240E+10 | 0.623916E+10 | 16701.24 | 11-OCT-15:00 | 15031.12 | 15031.12 | 24.50 | 67.54 |
November | 0.263847E+10 | 0.237463E+10 | 16672.87 | 16-NOV-13:10 | 15005.58 | 15005.58 | 22.14 | 67.54 |
December | 0.196397E+10 | 0.176757E+10 | 16660.99 | 01-DEC-10:50 | 14994.89 | 14994.89 | 21.14 | 67.54 |
Annual Sum or Average | 0.173478E+12 | 0.156130E+12 | ||||||
Minimum of Months | 0.157359E+10 | 0.141623E+10 | 16660.83 | 14994.75 | 14994.75 | 21.13 | 67.54 | |
Maximum of Months | 0.421788E+11 | 0.379609E+11 | 33539.50 | 30185.55 | 30185.55 | 30.19 | 135.08 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 29.53 | 29.53 | 120247.13 | 2161022.68 | 02-JAN-04:01 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 35.57 | 35.57 | 103946.68 | 1700791.47 | 13-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 27.20 | 27.20 | 34199.59 | 1661121.65 | 06-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.84 | 20.84 | 7249.70 | 1125367.52 | 03-APR-05:02 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 20.84 | 20.84 | 225.45 | 104187.33 | 01-MAY-05:02 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 21.10 | 21.10 | 3.98 | 2772.39 | 14-JUN-05:10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 21.01 | 21.01 | 0.00 | 4.54 | 27-JUL-05:50 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 21.01 | 21.01 | 0.08 | 243.55 | 31-AUG-05:50 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 21.00 | 21.00 | 188.90 | 123866.90 | 30-SEP-05:02 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 20.80 | 20.80 | 6320.58 | 1370907.27 | 16-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 22.99 | 22.99 | 24467.72 | 1444018.95 | 18-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 23.73 | 23.73 | 95656.44 | 1783508.16 | 11-DEC-05:01 |
Annual Sum or Average | 0.00 | 32394.37 | ||||||
Minimum of Months | 0.00 | 0.00 | 20.80 | 20.80 | 0.00 | 4.54 | ||
Maximum of Months | 0.00 | 0.00 | 35.57 | 35.57 | 120247.13 | 2161022.68 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 180.36 | 7119.04 | 11-JAN-07:30 | 6.74 | 6.70 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 166.96 | 8404.40 | 22-FEB-17:00 | 6.75 | 6.70 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 22830.81 | 1276273.37 | 15-MAR-13:50 | 14.65 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 9661.71 | 496362.72 | 07-APR-14:00 | 9.79 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 81362.94 | 1467344.24 | 10-MAY-14:50 | 11.26 | 6.70 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 350565.29 | 2123844.82 | 27-JUN-07:40 | 13.31 | 6.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 574398.64 | 2765884.56 | 20-JUL-05:02 | 15.31 | 6.92 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 485050.81 | 2793450.63 | 15-AUG-05:03 | 15.40 | 7.01 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 221978.19 | 2273898.01 | 21-SEP-13:07 | 13.78 | 6.70 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 27426.74 | 849377.74 | 11-OCT-15:00 | 11.98 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 3800.42 | 252523.58 | 16-NOV-13:10 | 8.27 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 179.54 | 32560.86 | 01-DEC-07:13 | 6.90 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 149367.58 | 0.00 | ||||||
Minimum of Months | 166.96 | 7119.04 | 6.74 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 574398.64 | 2793450.63 | 15.40 | 7.01 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 7.53 | 4011.47 | 11-JAN-07:30 | 6.98 | 6.70 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 14.51 | 4567.90 | 22-FEB-17:00 | 9.85 | 6.70 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 22483.54 | 1276130.00 | 15-MAR-13:50 | 15.43 | 6.70 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 9168.11 | 493489.95 | 07-APR-14:00 | 18.93 | 6.70 | 0.00 | 0.00 | 01-APR-00:10 |
May | 80101.87 | 1361488.97 | 10-MAY-14:40 | 17.75 | 9.33 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 348262.27 | 3283121.79 | 27-JUN-05:03 | 17.41 | 11.79 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 572440.35 | 4017525.26 | 20-JUL-03:02 | 19.81 | 12.92 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 484683.06 | 3813715.04 | 14-AUG-05:02 | 19.14 | 12.61 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 221578.62 | 3074080.70 | 16-SEP-05:03 | 16.72 | 11.46 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 26839.69 | 847276.77 | 11-OCT-15:00 | 13.80 | 6.70 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 3562.48 | 256338.81 | 16-NOV-11:30 | 14.74 | 6.70 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 7.39 | 40921.01 | 01-DEC-07:12 | 11.54 | 6.70 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 148660.32 | 0.00 | ||||||
Minimum of Months | 7.39 | 4011.47 | 6.98 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 572440.35 | 4017525.26 | 19.81 | 12.92 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 12152.82 | 31395.84 | 12-JAN-16:40 | 18.90 | 18.33 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 41911.14 | 67839.77 | 28-FEB-17:00 | 19.56 | 18.33 | 0.00 | 0.00 | 01-FEB-00:05 |
March | 102771.79 | 1091130.35 | 15-MAR-14:00 | 37.70 | 29.15 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 127516.30 | 717036.94 | 08-APR-13:10 | 31.14 | 23.65 | 0.00 | 0.00 | 01-APR-00:10 |
May | 57505.32 | 718700.76 | 10-MAY-15:00 | 31.17 | 27.42 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 309913.01 | 1335211.67 | 27-JUN-14:20 | 41.94 | 30.70 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 823581.27 | 1699851.56 | 21-JUL-02:40 | 48.21 | 34.04 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 869967.57 | 1780937.22 | 13-AUG-15:00 | 49.59 | 35.22 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 107865.16 | 834953.38 | 16-SEP-14:30 | 33.22 | 28.59 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 61644.94 | 463728.80 | 11-OCT-15:00 | 26.65 | 23.35 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 83866.07 | 350505.58 | 05-NOV-14:00 | 24.63 | 20.75 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 99191.34 | 187831.06 | 01-DEC-11:00 | 21.72 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 227067.38 | 0.00 | ||||||
Minimum of Months | 12152.82 | 31395.84 | 18.90 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 869967.57 | 1780937.22 | 49.59 | 35.22 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 57.98 | 57.98 | 15565.49 | 55761.22 | 31-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 57.39 | 57.39 | 15883.48 | 55957.88 | 15-FEB-13:00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 57.39 | 57.39 | 16653.06 | 55779.79 | 01-MAR-12:40 |
April | 0.00 | 0.00 | 01-APR-00:10 | 57.46 | 57.46 | 14992.80 | 54071.95 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 58.08 | 58.08 | 14631.73 | 51559.64 | 01-MAY-11:30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.74 | 57.74 | 14076.09 | 48363.93 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.87 | 57.87 | 12326.76 | 45521.89 | 03-JUL-11:20 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 57.95 | 57.95 | 13253.10 | 44047.85 | 01-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.95 | 57.95 | 12640.59 | 45462.26 | 29-SEP-12:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.88 | 57.88 | 13239.12 | 48280.13 | 31-OCT-11:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.75 | 57.75 | 14277.44 | 51375.00 | 30-NOV-13:00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 57.60 | 57.60 | 14571.55 | 54008.42 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 14333.73 | ||||||
Minimum of Months | 0.00 | 0.00 | 57.39 | 57.39 | 12326.76 | 44047.85 | ||
Maximum of Months | 0.00 | 0.00 | 58.08 | 58.08 | 16653.06 | 55957.88 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 7.09 | 12243.84 | 11-JAN-15:00 | 21.14 | 20.66 | 2440.12 | 146466.49 | 28-JAN-07:03 |
February | 6.48 | 8684.76 | 28-FEB-09:50 | 21.13 | 20.29 | 1813.65 | 160223.64 | 17-FEB-05:01 |
March | 29688.59 | 2038868.76 | 14-MAR-13:10 | 28.32 | 22.25 | 1950.10 | 140094.87 | 27-MAR-10:20 |
April | 8533.39 | 560304.24 | 07-APR-14:00 | 23.08 | 21.10 | 2250.34 | 126529.01 | 17-APR-06:03 |
May | 91280.29 | 2734960.74 | 10-MAY-14:40 | 25.94 | 22.68 | 1713.50 | 98522.51 | 06-MAY-10:50 |
June | 577790.30 | 5526515.13 | 27-JUN-07:40 | 30.89 | 26.62 | 506.36 | 84360.95 | 05-JUN-19:30 |
July | 1149899.42 | 6073603.75 | 05-JUL-16:00 | 31.86 | 26.85 | 183.33 | 53612.42 | 06-JUL-22:20 |
August | 836177.24 | 6108767.57 | 14-AUG-10:20 | 31.92 | 27.15 | 672.19 | 70926.18 | 31-AUG-08:70 |
September | 333140.86 | 4664626.85 | 15-SEP-11:00 | 29.36 | 25.21 | 464.38 | 69404.85 | 06-SEP-08:50 |
October | 29731.30 | 959522.84 | 11-OCT-15:00 | 24.50 | 21.10 | 873.64 | 119092.28 | 17-OCT-10:00 |
November | 3919.34 | 292377.52 | 16-NOV-13:10 | 22.14 | 21.10 | 1289.24 | 142347.73 | 24-NOV-07:03 |
December | 10.46 | 12439.49 | 01-DEC-10:50 | 21.14 | 20.75 | 2134.02 | 155815.42 | 07-DEC-07:03 |
Annual Sum or Average | 257376.23 | 1356.34 | ||||||
Minimum of Months | 6.48 | 8684.76 | 21.13 | 20.29 | 183.33 | 53612.42 | ||
Maximum of Months | 1149899.42 | 6108767.57 | 31.92 | 27.15 | 2440.12 | 160223.64 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.533075E+10 | 0.00 | 8769097.31 | 0.354026E+10 | 0.00 | 0.00 |
February | 0.381687E+10 | 0.00 | 8220567.66 | 0.349881E+10 | 0.00 | 0.00 |
March | 0.876023E+09 | 0.00 | 0.610699E+10 | 0.629173E+10 | 0.00 | 0.00 |
April | 64149219.48 | 0.00 | 0.263212E+10 | 0.790977E+10 | 0.00 | 0.00 |
May | 3400175.00 | 0.00 | 0.194026E+11 | 0.818533E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.894544E+11 | 0.132760E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.167387E+12 | 0.169317E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.140927E+12 | 0.171006E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.550567E+11 | 0.949011E+10 | 0.00 | 0.00 |
October | 54121709.69 | 0.00 | 0.732506E+10 | 0.671499E+10 | 0.00 | 0.00 |
November | 0.233978E+09 | 0.00 | 0.118363E+10 | 0.551748E+10 | 0.00 | 0.00 |
December | 0.270978E+10 | 0.00 | 9810583.93 | 0.439194E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.130891E+11 | 0.00 | 0.489502E+12 | 0.102849E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 8220567.66 | 0.349881E+10 | 0.00 | 0.00 |
Maximum of Months | 0.533075E+10 | 0.00 | 0.167387E+12 | 0.171006E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.256036E+12 | 0.00 | 1940318.27 | 0.340535E+11 | 0.00 | 0.00 |
February | 0.196360E+12 | 0.00 | 2555142.24 | 0.303578E+11 | 0.00 | 0.00 |
March | 0.699305E+11 | 0.00 | 0.418203E+11 | 0.389138E+11 | 0.00 | 0.00 |
April | 0.133964E+11 | 0.00 | 0.171151E+11 | 0.425217E+11 | 0.00 | 0.00 |
May | 0.132533E+09 | 0.00 | 0.164502E+12 | 0.612237E+11 | 0.00 | 0.00 |
June | 2464.37 | 0.00 | 0.677967E+12 | 0.887801E+11 | 0.00 | 0.00 |
July | 3003.26 | 0.00 | 0.113901E+13 | 0.100352E+12 | 0.00 | 0.00 |
August | 577.89 | 0.00 | 0.949497E+12 | 0.986252E+11 | 0.00 | 0.00 |
September | 0.247259E+09 | 0.00 | 0.426760E+12 | 0.654911E+11 | 0.00 | 0.00 |
October | 0.116726E+11 | 0.00 | 0.550837E+11 | 0.414067E+11 | 0.00 | 0.00 |
November | 0.486962E+11 | 0.00 | 0.666324E+10 | 0.319081E+11 | 0.00 | 0.00 |
December | 0.205395E+12 | 0.00 | 3612400.51 | 0.320866E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.801867E+12 | 0.00 | 0.347843E+13 | 0.665720E+12 | 0.00 | 0.00 |
Minimum of Months | 577.89 | 0.00 | 1940318.27 | 0.303578E+11 | 0.00 | 0.00 |
Maximum of Months | 0.256036E+12 | 0.00 | 0.113901E+13 | 0.100352E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.511858E+11 | 0.00 | 6813845.99 | 0.419892E+10 | 0.00 | 0.00 |
February | 0.430949E+11 | 0.00 | 5549010.19 | 0.384386E+10 | 0.00 | 0.00 |
March | 0.186652E+11 | 0.00 | 0.432231E+10 | 0.395372E+10 | 0.00 | 0.00 |
April | 0.536191E+10 | 0.00 | 0.158821E+10 | 0.368872E+10 | 0.00 | 0.00 |
May | 0.468471E+09 | 0.00 | 0.164003E+11 | 0.535629E+10 | 0.00 | 0.00 |
June | 10887854.09 | 0.00 | 0.736383E+11 | 0.877077E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.125404E+12 | 0.103605E+11 | 0.00 | 0.00 |
August | 226587.38 | 0.00 | 0.102448E+12 | 0.969615E+10 | 0.00 | 0.00 |
September | 0.245725E+09 | 0.00 | 0.422136E+11 | 0.572195E+10 | 0.00 | 0.00 |
October | 0.527493E+10 | 0.00 | 0.471304E+10 | 0.349596E+10 | 0.00 | 0.00 |
November | 0.147355E+11 | 0.00 | 0.600387E+09 | 0.300622E+10 | 0.00 | 0.00 |
December | 0.453795E+11 | 0.00 | 5332230.66 | 0.398109E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.184423E+12 | 0.00 | 0.371346E+12 | 0.660741E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 5332230.66 | 0.300622E+10 | 0.00 | 0.00 |
Maximum of Months | 0.511858E+11 | 0.00 | 0.125404E+12 | 0.103605E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.111506E+11 | 0.00 | 44492354.16 | 0.248255E+10 | 0.00 | 0.00 |
February | 0.954878E+10 | 0.00 | 41607905.67 | 0.163019E+10 | 0.00 | 0.00 |
March | 0.263946E+10 | 0.00 | 0.448173E+10 | 0.398163E+10 | 0.00 | 0.00 |
April | 66276173.32 | 0.00 | 0.241316E+10 | 0.796883E+10 | 0.00 | 0.00 |
May | 973256.34 | 0.00 | 0.131541E+11 | 0.126868E+11 | 0.00 | 0.00 |
June | 87.78 | 0.00 | 0.308475E+11 | 0.107568E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.448969E+11 | 0.779399E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.567412E+11 | 0.116828E+11 | 0.00 | 0.00 |
September | 237889.35 | 0.00 | 0.306227E+11 | 0.114098E+11 | 0.00 | 0.00 |
October | 2184927.73 | 0.00 | 0.485575E+10 | 0.146452E+11 | 0.00 | 0.00 |
November | 75907958.52 | 0.00 | 0.818628E+09 | 0.123092E+11 | 0.00 | 0.00 |
December | 0.399649E+10 | 0.00 | 3834917.46 | 0.434352E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.274809E+11 | 0.00 | 0.188922E+12 | 0.101691E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 3834917.46 | 0.163019E+10 | 0.00 | 0.00 |
Maximum of Months | 0.111506E+11 | 0.00 | 0.567412E+11 | 0.146452E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.112410E+11 | 0.251623E+12 | 0.00 | 50.54 |
February | 0.00 | 0.00 | 0.157867E+11 | 0.309144E+12 | 0.00 | 75.63 |
March | 0.00 | 0.00 | 0.437293E+11 | 0.323888E+12 | 0.00 | 74.58 |
April | 0.00 | 0.00 | 0.496360E+11 | 0.326666E+12 | 0.00 | 76.49 |
May | 0.00 | 0.00 | 0.124089E+11 | 0.197040E+12 | 0.00 | 30.05 |
June | 0.00 | 0.00 | 0.219160E+12 | 0.200263E+12 | 0.00 | 15.13 |
July | 0.00 | 0.00 | 0.914185E+12 | 0.316107E+12 | 0.00 | 0.91 |
August | 0.00 | 0.00 | 0.106014E+13 | 0.349507E+12 | 0.00 | 1.68 |
September | 0.00 | 0.00 | 0.232476E+11 | 0.126208E+12 | 0.00 | 3.96 |
October | 0.00 | 0.00 | 0.139825E+11 | 0.221677E+12 | 0.00 | 39.11 |
November | 0.00 | 0.00 | 0.248789E+11 | 0.329379E+12 | 0.00 | 79.65 |
December | 0.00 | 0.00 | 0.226091E+11 | 0.379973E+12 | 0.00 | 97.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.241101E+13 | 0.333148E+13 | 0.00 | 544.92 |
Minimum of Months | 0.00 | 0.00 | 0.112410E+11 | 0.126208E+12 | 0.00 | 0.91 |
Maximum of Months | 0.00 | 0.00 | 0.106014E+13 | 0.379973E+12 | 0.00 | 97.19 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.392001E+10 | 0.236123E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.969513E+10 | 0.334912E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.184406E+11 | 0.506525E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.242711E+11 | 0.588166E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.706753E+10 | 0.293478E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.137641E+11 | 0.425201E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.212769E+11 | 0.606771E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.271682E+11 | 0.710839E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.724780E+10 | 0.292326E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.127805E+11 | 0.395909E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.179321E+11 | 0.483720E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.238198E+11 | 0.599770E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.187384E+12 | 0.547374E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.392001E+10 | 0.236123E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.271682E+11 | 0.710839E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.799309E+10 | 0.163751E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.631773E+11 | 0.263377E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.155356E+12 | 0.447793E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.218144E+12 | 0.540337E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.603959E+11 | 0.267485E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.127799E+12 | 0.400123E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.200847E+12 | 0.575832E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.256951E+12 | 0.675282E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.619745E+11 | 0.266205E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.105947E+12 | 0.349970E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.148599E+12 | 0.423630E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.192593E+12 | 0.514241E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.159978E+13 | 0.488803E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.799309E+10 | 0.163751E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.256951E+12 | 0.675282E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.195678E+09 | 0.151683E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.433847E+10 | 0.225525E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.137149E+11 | 0.417348E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.206023E+11 | 0.523140E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.547864E+10 | 0.259269E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.126809E+11 | 0.401247E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.201443E+11 | 0.580409E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.256640E+11 | 0.678503E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.569662E+10 | 0.259286E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.902324E+10 | 0.323706E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.128480E+11 | 0.390591E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.169923E+11 | 0.477286E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.147379E+12 | 0.468799E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.195678E+09 | 0.151683E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.256640E+11 | 0.678503E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.354026E+10 | 8769097.31 | 0.533075E+10 | 0.316043E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.349881E+10 | 8220567.66 | 0.381687E+10 | 0.277995E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.629173E+10 | 0.610699E+10 | 0.876023E+09 | 0.101605E+11 | 357519.88 | 0.00 | 0.00 | 0.00 |
April | 0.790977E+10 | 0.263212E+10 | 64149219.48 | 0.978523E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.818533E+10 | 0.194026E+11 | 3400175.00 | 18054905.23 | 105819.00 | 0.00 | 0.00 | 0.00 |
June | 0.132760E+11 | 0.894544E+11 | 0.00 | 0.139672E+09 | 0.184516E+10 | 0.00 | 0.00 | 0.00 |
July | 0.169317E+11 | 0.167387E+12 | 0.00 | 0.141087E+09 | 0.542000E+10 | 0.00 | 0.00 | 0.00 |
August | 0.171006E+11 | 0.140927E+12 | 0.00 | 0.579459E+09 | 0.216099E+10 | 0.00 | 0.00 | 0.00 |
September | 0.949011E+10 | 0.550567E+11 | 0.00 | 34878578.55 | 0.274157E+09 | 0.00 | 0.00 | 0.00 |
October | 0.671499E+10 | 0.732506E+10 | 54121709.69 | 0.610840E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.551748E+10 | 0.118363E+10 | 0.233978E+09 | 0.233190E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.439194E+10 | 9810583.93 | 0.270978E+10 | 0.213855E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102849E+12 | 0.489502E+12 | 0.130891E+11 | 0.957842E+11 | 0.970077E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.349881E+10 | 8220567.66 | 0.00 | 18054905.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.171006E+11 | 0.167387E+12 | 0.533075E+10 | 0.316043E+11 | 0.542000E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.340535E+11 | 1940318.27 | 0.256036E+12 | 0.382982E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.303578E+11 | 2555142.24 | 0.196360E+12 | 0.351537E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.389138E+11 | 0.418203E+11 | 0.699305E+11 | 0.169864E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.425217E+11 | 0.171151E+11 | 0.133964E+11 | 0.333651E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.612237E+11 | 0.164502E+12 | 0.132533E+09 | 0.947402E+09 | 439472.25 | 0.00 | 0.00 | 0.00 |
June | 0.887801E+11 | 0.677967E+12 | 2464.37 | 0.159374E+10 | 0.183207E+11 | 0.00 | 0.00 | 0.00 |
July | 0.100352E+12 | 0.113901E+13 | 3003.26 | 0.190965E+10 | 0.530332E+11 | 0.00 | 0.00 | 0.00 |
August | 0.986252E+11 | 0.949497E+12 | 577.89 | 0.685869E+10 | 0.206159E+11 | 0.00 | 0.00 | 0.00 |
September | 0.654911E+11 | 0.426760E+12 | 0.247259E+09 | 0.395020E+09 | 0.291985E+10 | 0.00 | 0.00 | 0.00 |
October | 0.414067E+11 | 0.550837E+11 | 0.116726E+11 | 0.169067E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.319081E+11 | 0.666324E+10 | 0.486962E+11 | 0.749627E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.320866E+11 | 3612400.51 | 0.205395E+12 | 0.321683E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.665720E+12 | 0.347843E+13 | 0.801867E+12 | 0.136300E+13 | 0.948901E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.303578E+11 | 1940318.27 | 577.89 | 0.395020E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.100352E+12 | 0.113901E+13 | 0.256036E+12 | 0.382982E+12 | 0.530332E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.419892E+10 | 6813845.99 | 0.511858E+11 | 0.415876E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.384386E+10 | 5549010.19 | 0.430949E+11 | 0.372476E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.395372E+10 | 0.432231E+10 | 0.186652E+11 | 0.202522E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.368872E+10 | 0.158821E+10 | 0.536191E+10 | 0.530872E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.535629E+10 | 0.164003E+11 | 0.468471E+09 | 0.228180E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.877077E+10 | 0.736383E+11 | 10887854.09 | 0.154841E+09 | 0.147598E+10 | 0.00 | 0.00 | 0.00 |
July | 0.103605E+11 | 0.125404E+12 | 0.00 | 0.145299E+09 | 0.435163E+10 | 0.00 | 0.00 | 0.00 |
August | 0.969615E+10 | 0.102448E+12 | 226587.38 | 0.639546E+09 | 0.153106E+10 | 0.00 | 0.00 | 0.00 |
September | 0.572195E+10 | 0.422136E+11 | 0.245725E+09 | 92109554.72 | 0.174267E+09 | 0.00 | 0.00 | 0.00 |
October | 0.349596E+10 | 0.471304E+10 | 0.527493E+10 | 0.316396E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.300622E+10 | 0.600387E+09 | 0.147355E+11 | 0.114193E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.398109E+10 | 5332230.66 | 0.453795E+11 | 0.358723E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.660741E+11 | 0.371346E+12 | 0.184423E+12 | 0.156112E+12 | 0.753293E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.300622E+10 | 5332230.66 | 0.00 | 92109554.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.103605E+11 | 0.125404E+12 | 0.511858E+11 | 0.415876E+11 | 0.435163E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.248255E+10 | 46521054.56 | 0.111506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.163019E+10 | 41607905.67 | 0.954878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.398163E+10 | 0.448474E+10 | 0.263946E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.796883E+10 | 0.241316E+10 | 66276173.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.126868E+11 | 0.131541E+11 | 973256.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107568E+11 | 0.308475E+11 | 87.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.779399E+10 | 0.448969E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116828E+11 | 0.567412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.114098E+11 | 0.306227E+11 | 237889.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146452E+11 | 0.485575E+10 | 2184927.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123092E+11 | 0.818628E+09 | 75907958.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.434352E+10 | 3834917.46 | 0.399649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101691E+12 | 0.188927E+12 | 0.274809E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.163019E+10 | 3834917.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146452E+11 | 0.567412E+11 | 0.111506E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.111110E+12 | 0.658737E+10 | 0.00 | 0.00 | 0.00 | 0.135250E+12 | 0.00 | 0.00 |
February | 0.100358E+12 | 0.102941E+11 | 0.00 | 0.00 | 0.00 | 0.202382E+12 | 0.00 | 0.00 |
March | 0.111110E+12 | 0.314426E+11 | 0.00 | 0.00 | 0.00 | 0.199592E+12 | 0.00 | 0.00 |
April | 0.107526E+12 | 0.361100E+11 | 0.00 | 0.00 | 0.00 | 0.204692E+12 | 0.00 | 0.00 |
May | 0.111110E+12 | 0.725831E+10 | 0.00 | 0.00 | 0.00 | 0.804171E+11 | 0.00 | 0.00 |
June | 0.107526E+12 | 0.167102E+12 | 0.00 | 0.00 | 0.00 | 0.404961E+11 | 0.00 | 0.00 |
July | 0.111110E+12 | 0.711644E+12 | 0.00 | 0.00 | 0.00 | 0.244510E+10 | 0.00 | 0.00 |
August | 0.111110E+12 | 0.826267E+12 | 0.00 | 0.00 | 0.00 | 0.450064E+10 | 0.00 | 0.00 |
September | 0.107526E+12 | 0.152209E+11 | 0.00 | 0.00 | 0.00 | 0.106071E+11 | 0.00 | 0.00 |
October | 0.111110E+12 | 0.854147E+10 | 0.00 | 0.00 | 0.00 | 0.104655E+12 | 0.00 | 0.00 |
November | 0.107526E+12 | 0.171312E+11 | 0.00 | 0.00 | 0.00 | 0.213146E+12 | 0.00 | 0.00 |
December | 0.111110E+12 | 0.150102E+11 | 0.00 | 0.00 | 0.00 | 0.260093E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.130824E+13 | 0.185261E+13 | 0.00 | 0.00 | 0.00 | 0.145828E+13 | 0.00 | 0.00 |
Minimum of Months | 0.100358E+12 | 0.658737E+10 | 0.00 | 0.00 | 0.00 | 0.244510E+10 | 0.00 | 0.00 |
Maximum of Months | 0.111110E+12 | 0.826267E+12 | 0.00 | 0.00 | 0.00 | 0.260093E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.150693E+10 | 0.306570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136110E+10 | 0.770710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150693E+10 | 0.148823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145832E+10 | 0.198477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150693E+10 | 0.563968E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.145832E+10 | 0.109704E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.150693E+10 | 0.167161E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.150693E+10 | 0.215668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.145832E+10 | 0.578285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150693E+10 | 0.103283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145832E+10 | 0.145532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150693E+10 | 0.193290E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177429E+11 | 0.150389E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136110E+10 | 0.306570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.150693E+10 | 0.215668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.144498E+11 | 0.606778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130514E+11 | 0.498910E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144498E+11 | 0.125026E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139836E+11 | 0.178094E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144498E+11 | 0.480971E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139836E+11 | 0.101771E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144498E+11 | 0.157714E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144498E+11 | 0.203873E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139836E+11 | 0.493376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144498E+11 | 0.854001E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139836E+11 | 0.120220E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144498E+11 | 0.155618E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170134E+12 | 0.128111E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130514E+11 | 0.606778E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144498E+11 | 0.203873E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.146890E+10 | 0.147746E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132675E+10 | 0.340997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146890E+10 | 0.110103E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142152E+10 | 0.167924E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146890E+10 | 0.435485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142152E+10 | 0.100900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.146890E+10 | 0.158092E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146890E+10 | 0.203478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142152E+10 | 0.452527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146890E+10 | 0.725508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142152E+10 | 0.103636E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146890E+10 | 0.136883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172951E+11 | 0.117794E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132675E+10 | 0.147746E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146890E+10 | 0.203478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.354026E+10 | 0.533075E+10 | 8769097.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.349881E+10 | 0.381687E+10 | 8220567.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.629173E+10 | 0.876023E+09 | 0.610699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.790977E+10 | 64149219.48 | 0.263212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.818533E+10 | 3400175.00 | 0.194026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.132760E+11 | 0.00 | 0.894544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.169317E+11 | 0.00 | 0.167387E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.171006E+11 | 0.00 | 0.140927E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.949011E+10 | 0.00 | 0.550567E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.671499E+10 | 54121709.69 | 0.732506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.551748E+10 | 0.233978E+09 | 0.118363E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.439194E+10 | 0.270978E+10 | 9810583.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102849E+12 | 0.130891E+11 | 0.489502E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.349881E+10 | 0.00 | 8220567.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.171006E+11 | 0.533075E+10 | 0.167387E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.340535E+11 | 0.256036E+12 | 1940318.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.303578E+11 | 0.196360E+12 | 2555142.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.389138E+11 | 0.699305E+11 | 0.418203E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.425217E+11 | 0.133964E+11 | 0.171151E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.612237E+11 | 0.132533E+09 | 0.164502E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.887801E+11 | 2464.37 | 0.677967E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.100352E+12 | 3003.26 | 0.113901E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.986252E+11 | 577.89 | 0.949497E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.654911E+11 | 0.247259E+09 | 0.426760E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.414067E+11 | 0.116726E+11 | 0.550837E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.319081E+11 | 0.486962E+11 | 0.666324E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.320866E+11 | 0.205395E+12 | 3612400.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.665720E+12 | 0.801867E+12 | 0.347843E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.303578E+11 | 577.89 | 1940318.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.100352E+12 | 0.256036E+12 | 0.113901E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.419892E+10 | 0.511858E+11 | 6813845.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.384386E+10 | 0.430949E+11 | 5549010.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.395372E+10 | 0.186652E+11 | 0.432231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.368872E+10 | 0.536191E+10 | 0.158821E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.535629E+10 | 0.468471E+09 | 0.164003E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.877077E+10 | 10887854.09 | 0.736383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.103605E+11 | 0.00 | 0.125404E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.969615E+10 | 226587.38 | 0.102448E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.572195E+10 | 0.245725E+09 | 0.422136E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.349596E+10 | 0.527493E+10 | 0.471304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.300622E+10 | 0.147355E+11 | 0.600387E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.398109E+10 | 0.453795E+11 | 5332230.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.660741E+11 | 0.184423E+12 | 0.371346E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.300622E+10 | 0.00 | 5332230.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.103605E+11 | 0.511858E+11 | 0.125404E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.248255E+10 | 0.111506E+11 | 44492354.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.163019E+10 | 0.954878E+10 | 41607905.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.398163E+10 | 0.263946E+10 | 0.448173E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.796883E+10 | 66276173.32 | 0.241316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.126868E+11 | 973256.34 | 0.131541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107568E+11 | 87.78 | 0.308475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.779399E+10 | 0.00 | 0.448969E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116828E+11 | 0.00 | 0.567412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.114098E+11 | 237889.35 | 0.306227E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146452E+11 | 2184927.73 | 0.485575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.123092E+11 | 75907958.52 | 0.818628E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.434352E+10 | 0.399649E+10 | 3834917.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.101691E+12 | 0.274809E+11 | 0.188922E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.163019E+10 | 0.00 | 3834917.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146452E+11 | 0.111506E+11 | 0.567412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.111110E+12 | 0.00 | 0.112410E+11 | 0.00 | 0.465368E+10 | 0.00 | 0.00 | 0.00 | 0.135859E+12 | 0.00 | 0.00 | 0.00 |
February | 0.100358E+12 | 0.00 | 0.157867E+11 | 0.00 | 0.549266E+10 | 0.00 | 0.00 | 0.00 | 0.203293E+12 | 0.00 | 0.00 | 0.00 |
March | 0.111110E+12 | 0.00 | 0.437293E+11 | 0.00 | 0.122868E+11 | 0.00 | 0.00 | 0.00 | 0.200491E+12 | 0.00 | 0.00 | 0.00 |
April | 0.107526E+12 | 0.00 | 0.496360E+11 | 0.00 | 0.135260E+11 | 0.00 | 0.00 | 0.00 | 0.205613E+12 | 0.00 | 0.00 | 0.00 |
May | 0.111110E+12 | 0.00 | 0.124089E+11 | 0.00 | 0.515061E+10 | 0.00 | 0.00 | 0.00 | 0.807791E+11 | 0.00 | 0.00 | 0.00 |
June | 0.107526E+12 | 0.00 | 0.219160E+12 | 0.00 | 0.520588E+11 | 0.00 | 0.00 | 0.00 | 0.406784E+11 | 0.00 | 0.00 | 0.00 |
July | 0.111110E+12 | 0.00 | 0.914185E+12 | 0.00 | 0.202540E+12 | 0.00 | 0.00 | 0.00 | 0.245611E+10 | 0.00 | 0.00 | 0.00 |
August | 0.111110E+12 | 0.00 | 0.106014E+13 | 0.00 | 0.233876E+12 | 0.00 | 0.00 | 0.00 | 0.452090E+10 | 0.00 | 0.00 | 0.00 |
September | 0.107526E+12 | 0.00 | 0.232476E+11 | 0.00 | 0.802671E+10 | 0.00 | 0.00 | 0.00 | 0.106548E+11 | 0.00 | 0.00 | 0.00 |
October | 0.111110E+12 | 0.00 | 0.139825E+11 | 0.00 | 0.544107E+10 | 0.00 | 0.00 | 0.00 | 0.105126E+12 | 0.00 | 0.00 | 0.00 |
November | 0.107526E+12 | 0.00 | 0.248789E+11 | 0.00 | 0.774769E+10 | 0.00 | 0.00 | 0.00 | 0.214105E+12 | 0.00 | 0.00 | 0.00 |
December | 0.111110E+12 | 0.00 | 0.226091E+11 | 0.00 | 0.759881E+10 | 0.00 | 0.00 | 0.00 | 0.261264E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130824E+13 | 0.00 | 0.241101E+13 | 0.00 | 0.558399E+12 | 0.00 | 0.00 | 0.00 | 0.146484E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.100358E+12 | 0.00 | 0.112410E+11 | 0.00 | 0.465368E+10 | 0.00 | 0.00 | 0.00 | 0.245611E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.111110E+12 | 0.00 | 0.106014E+13 | 0.00 | 0.233876E+12 | 0.00 | 0.00 | 0.00 | 0.261264E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.150693E+10 | 0.00 | 0.392001E+10 | 0.00 | 0.854306E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136110E+10 | 0.00 | 0.969513E+10 | 0.00 | 0.198803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150693E+10 | 0.00 | 0.184406E+11 | 0.00 | 0.355832E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145832E+10 | 0.00 | 0.242711E+11 | 0.00 | 0.442334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150693E+10 | 0.00 | 0.706753E+10 | 0.00 | 0.142785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.145832E+10 | 0.00 | 0.137641E+11 | 0.00 | 0.279369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.150693E+10 | 0.00 | 0.212769E+11 | 0.00 | 0.456079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.150693E+10 | 0.00 | 0.271682E+11 | 0.00 | 0.560146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.145832E+10 | 0.00 | 0.724780E+10 | 0.00 | 0.146495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150693E+10 | 0.00 | 0.127805E+11 | 0.00 | 0.245216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145832E+10 | 0.00 | 0.179321E+11 | 0.00 | 0.337888E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.150693E+10 | 0.00 | 0.238198E+11 | 0.00 | 0.449078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177429E+11 | 0.00 | 0.187384E+12 | 0.00 | 0.369945E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136110E+10 | 0.00 | 0.392001E+10 | 0.00 | 0.854306E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.150693E+10 | 0.00 | 0.271682E+11 | 0.00 | 0.560146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.144498E+11 | 0.00 | 0.799309E+10 | 0.00 | 0.192531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130514E+11 | 0.00 | 0.631773E+11 | 0.00 | 0.132863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144498E+11 | 0.00 | 0.155356E+12 | 0.00 | 0.303296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139836E+11 | 0.00 | 0.218144E+12 | 0.00 | 0.400501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144498E+11 | 0.00 | 0.603959E+11 | 0.00 | 0.122988E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139836E+11 | 0.00 | 0.127799E+12 | 0.00 | 0.260286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144498E+11 | 0.00 | 0.200847E+12 | 0.00 | 0.431334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144498E+11 | 0.00 | 0.256951E+12 | 0.00 | 0.530785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139836E+11 | 0.00 | 0.619745E+11 | 0.00 | 0.126369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144498E+11 | 0.00 | 0.105947E+12 | 0.00 | 0.205472E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139836E+11 | 0.00 | 0.148599E+12 | 0.00 | 0.283794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144498E+11 | 0.00 | 0.192593E+12 | 0.00 | 0.369744E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170134E+12 | 0.00 | 0.159978E+13 | 0.00 | 0.318668E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130514E+11 | 0.00 | 0.799309E+10 | 0.00 | 0.192531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144498E+11 | 0.00 | 0.256951E+12 | 0.00 | 0.530785E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.146890E+10 | 0.00 | 0.195678E+09 | 0.00 | 47931255.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132675E+10 | 0.00 | 0.433847E+10 | 0.00 | 0.928499E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146890E+10 | 0.00 | 0.137149E+11 | 0.00 | 0.270458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142152E+10 | 0.00 | 0.206023E+11 | 0.00 | 0.380988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.146890E+10 | 0.00 | 0.547864E+10 | 0.00 | 0.112379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142152E+10 | 0.00 | 0.126809E+11 | 0.00 | 0.259095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.146890E+10 | 0.00 | 0.201443E+11 | 0.00 | 0.433519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146890E+10 | 0.00 | 0.256640E+11 | 0.00 | 0.531613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142152E+10 | 0.00 | 0.569662E+10 | 0.00 | 0.117135E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146890E+10 | 0.00 | 0.902324E+10 | 0.00 | 0.176816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142152E+10 | 0.00 | 0.128480E+11 | 0.00 | 0.248439E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146890E+10 | 0.00 | 0.169923E+11 | 0.00 | 0.330396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172951E+11 | 0.00 | 0.147379E+12 | 0.00 | 0.295848E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132675E+10 | 0.00 | 0.195678E+09 | 0.00 | 47931255.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146890E+10 | 0.00 | 0.256640E+11 | 0.00 | 0.531613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 75609108.61 | 0.00 | 0.00 | 0.588033E+11 | 0.00 | 0.34 |
February | 0.00 | 0.00 | 0.00 | 73262634.24 | 0.00 | 0.00 | 0.529756E+11 | 0.00 | 0.33 |
March | 0.00 | 0.162832E+09 | 0.00 | 0.104713E+09 | 0.00 | 0.00 | 0.581491E+11 | 0.00 | 0.50 |
April | 0.00 | 0.00 | 0.00 | 98756974.90 | 0.00 | 0.00 | 0.605465E+11 | 0.00 | 0.69 |
May | 0.00 | 3864920.17 | 0.00 | 0.108453E+09 | 0.00 | 0.00 | 0.569911E+11 | 0.00 | 1.05 |
June | 0.00 | 0.128512E+10 | 0.00 | 0.112120E+09 | 0.00 | 0.00 | 0.358805E+11 | 0.00 | 0.97 |
July | 0.00 | 0.401296E+10 | 0.00 | 92850423.43 | 0.00 | 0.00 | 0.108180E+11 | 0.00 | 0.50 |
August | 0.00 | 0.417593E+10 | 0.00 | 0.118550E+09 | 0.00 | 0.00 | 0.193144E+11 | 0.00 | 0.78 |
September | 0.00 | 0.291963E+10 | 0.00 | 0.125730E+09 | 0.00 | 0.00 | 0.412896E+11 | 0.00 | 1.03 |
October | 0.00 | 0.00 | 0.00 | 0.125406E+09 | 0.00 | 0.00 | 0.720075E+11 | 0.00 | 0.96 |
November | 0.00 | 0.00 | 0.00 | 0.110833E+09 | 0.00 | 0.00 | 0.706377E+11 | 0.00 | 0.70 |
December | 0.00 | 0.00 | 0.00 | 91668078.26 | 0.00 | 0.00 | 0.608842E+11 | 0.00 | 0.38 |
Annual Sum or Average | 0.00 | 0.125603E+11 | 0.00 | 0.123795E+10 | 0.00 | 0.00 | 0.598298E+12 | 0.00 | 0.69 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 73262634.24 | 0.00 | 0.00 | 0.108180E+11 | 0.00 | 0.33 |
Maximum of Months | 0.00 | 0.417593E+10 | 0.00 | 0.125730E+09 | 0.00 | 0.00 | 0.720075E+11 | 0.00 | 1.05 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.106937E+11 | 0.00 | 0.00 | 39311222.39 | 0.00 | 0.00 | 0.269913E+11 | 0.00 | 0.32 |
February | 0.633586E+10 | 0.00 | 0.00 | 44993503.85 | 0.00 | 0.00 | 0.301331E+11 | 0.00 | 0.33 |
March | 0.243593E+10 | 0.00 | 0.00 | 94706454.23 | 0.00 | 0.00 | 0.521431E+11 | 0.00 | 0.51 |
April | 0.425232E+10 | 0.00 | 0.00 | 99148137.37 | 0.00 | 0.00 | 0.587410E+11 | 0.00 | 0.70 |
May | 0.358462E+10 | 11897748.15 | 0.00 | 93148750.83 | 30463776.05 | 0.00 | 0.507685E+11 | 0.00 | 0.90 |
June | 0.246283E+10 | 0.335798E+10 | 0.00 | 90061519.67 | 0.714955E+09 | 0.00 | 0.326060E+11 | 0.00 | 1.11 |
July | 0.393111E+10 | 0.139769E+11 | 0.00 | 56607848.18 | 0.258210E+10 | 0.00 | 0.115776E+11 | 0.00 | 1.04 |
August | 0.599820E+10 | 0.818422E+10 | 0.00 | 90326945.35 | 0.154959E+10 | 0.00 | 0.232772E+11 | 0.00 | 1.21 |
September | 0.322719E+10 | 0.303794E+10 | 0.00 | 88425330.74 | 87848893.80 | 0.00 | 0.367668E+11 | 0.00 | 1.01 |
October | 0.220342E+10 | 0.00 | 0.00 | 97274703.63 | 0.00 | 0.00 | 0.549192E+11 | 0.00 | 0.70 |
November | 0.151183E+10 | 0.00 | 0.00 | 91011365.12 | 0.00 | 0.00 | 0.538233E+11 | 0.00 | 0.54 |
December | 0.231114E+10 | 0.00 | 0.00 | 71406864.39 | 0.00 | 0.00 | 0.443362E+11 | 0.00 | 0.37 |
Annual Sum or Average | 0.489481E+11 | 0.285689E+11 | 0.00 | 0.956423E+09 | 0.496495E+10 | 0.00 | 0.476083E+12 | 0.00 | 0.73 |
Minimum of Months | 0.151183E+10 | 0.00 | 0.00 | 39311222.39 | 0.00 | 0.00 | 0.115776E+11 | 0.00 | 0.32 |
Maximum of Months | 0.106937E+11 | 0.139769E+11 | 0.00 | 99148137.37 | 0.258210E+10 | 0.00 | 0.587410E+11 | 0.00 | 1.21 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.232644E+12 | 0.00 | 0.00 | 11631617.52 | 0.00 | 0.622883E+10 | 0.191981E+11 | 0.00 | 0.29 |
February | 0.216095E+12 | 0.00 | 0.00 | 15815049.77 | 0.00 | 0.157028E+10 | 0.232914E+11 | 0.00 | 0.29 |
March | 0.157095E+12 | 0.00 | 0.00 | 0.266252E+09 | 0.00 | 11193059.23 | 0.184838E+12 | 0.00 | 0.36 |
April | 0.993471E+11 | 0.00 | 0.00 | 0.385048E+09 | 0.00 | 0.00 | 0.286091E+12 | 0.00 | 0.46 |
May | 0.445109E+11 | 65694179.18 | 0.00 | 0.619221E+09 | 0.212296E+09 | 0.00 | 0.380975E+12 | 0.00 | 0.72 |
June | 0.185484E+11 | 0.206373E+11 | 0.00 | 0.608091E+09 | 0.285605E+10 | 0.00 | 0.238900E+12 | 0.00 | 0.82 |
July | 0.124309E+11 | 0.825694E+11 | 0.00 | 0.376343E+09 | 0.992631E+10 | 0.00 | 0.802643E+11 | 0.00 | 0.66 |
August | 0.134592E+11 | 0.448220E+11 | 0.00 | 0.640016E+09 | 0.477205E+10 | 0.00 | 0.166032E+12 | 0.00 | 0.76 |
September | 0.401382E+11 | 0.192172E+11 | 0.00 | 0.552950E+09 | 0.300362E+09 | 0.00 | 0.261226E+12 | 0.00 | 0.78 |
October | 0.875533E+11 | 0.00 | 0.00 | 0.422113E+09 | 0.00 | 0.00 | 0.290443E+12 | 0.00 | 0.49 |
November | 0.125905E+12 | 0.00 | 0.00 | 0.261099E+09 | 0.106840E+09 | 0.00 | 0.193909E+12 | 0.00 | 0.34 |
December | 0.223079E+12 | 0.00 | 0.00 | 34653487.21 | 0.00 | 0.150179E+10 | 0.440097E+11 | 0.00 | 0.29 |
Annual Sum or Average | 0.127081E+13 | 0.167312E+12 | 0.00 | 0.419323E+10 | 0.181739E+11 | 0.931209E+10 | 0.216918E+13 | 0.00 | 0.52 |
Minimum of Months | 0.124309E+11 | 0.00 | 0.00 | 11631617.52 | 0.00 | 0.00 | 0.191981E+11 | 0.00 | 0.29 |
Maximum of Months | 0.232644E+12 | 0.825694E+11 | 0.00 | 0.640016E+09 | 0.992631E+10 | 0.622883E+10 | 0.380975E+12 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.173718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241069E+10 | 0.00 | 0.00 | 0.27 |
February | 0.171339E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202183E+10 | 0.00 | 0.00 | 0.28 |
March | 0.195883E+11 | 0.00 | 0.00 | 9712969.45 | 0.00 | 0.690432E+09 | 0.723267E+10 | 0.00 | 0.35 |
April | 0.159321E+11 | 0.00 | 0.00 | 17372088.76 | 0.00 | 0.110299E+09 | 0.159285E+11 | 0.00 | 0.41 |
May | 0.929656E+10 | 7852470.43 | 0.00 | 44173064.16 | 12057486.10 | 0.00 | 0.299350E+11 | 0.00 | 0.68 |
June | 0.303192E+10 | 0.230093E+10 | 0.00 | 53929347.53 | 0.413780E+09 | 0.00 | 0.226587E+11 | 0.00 | 0.86 |
July | 0.159349E+10 | 0.912250E+10 | 0.00 | 33124728.12 | 0.114724E+10 | 0.00 | 0.777014E+10 | 0.00 | 0.72 |
August | 0.209689E+10 | 0.520393E+10 | 0.00 | 55616993.90 | 0.523904E+09 | 0.00 | 0.147948E+11 | 0.00 | 0.79 |
September | 0.736924E+10 | 0.185564E+10 | 0.00 | 39426692.09 | 37184299.27 | 0.00 | 0.190477E+11 | 0.00 | 0.73 |
October | 0.152935E+11 | 0.00 | 0.00 | 17067821.06 | 0.00 | 0.206940E+09 | 0.142960E+11 | 0.00 | 0.42 |
November | 0.197630E+11 | 0.00 | 2456302.18 | 2709826.85 | 25418039.68 | 0.379798E+09 | 0.364363E+10 | 165.93 | 0.31 |
December | 0.181510E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196487E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.146622E+12 | 0.184909E+11 | 2456302.18 | 0.273134E+09 | 0.215958E+10 | 0.778487E+10 | 0.135307E+12 | 165.93 | 0.51 |
Minimum of Months | 0.159349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.197630E+11 | 0.912250E+10 | 2456302.18 | 55616993.90 | 0.114724E+10 | 0.241069E+10 | 0.299350E+11 | 165.93 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.297665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.901706E+09 | 0.00 | 0.00 | 0.27 |
February | 0.296309E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586318E+09 | 0.00 | 0.00 | 0.26 |
March | 0.316191E+10 | 0.00 | 0.00 | 2409689.79 | 0.00 | 0.119176E+09 | 0.155944E+10 | 0.00 | 0.39 |
April | 0.215957E+10 | 0.00 | 0.00 | 4984703.71 | 0.00 | 0.00 | 0.376867E+10 | 0.00 | 0.56 |
May | 0.122185E+10 | 433067.87 | 0.00 | 8460351.63 | 4477569.65 | 0.00 | 0.507465E+10 | 0.00 | 0.88 |
June | 0.409034E+09 | 0.600311E+09 | 0.00 | 11337874.21 | 83096950.89 | 0.00 | 0.427924E+10 | 0.00 | 1.31 |
July | 0.540077E+09 | 0.234189E+10 | 0.00 | 7740953.77 | 0.311134E+09 | 0.00 | 0.158959E+10 | 0.00 | 1.26 |
August | 0.860156E+09 | 0.131820E+10 | 0.00 | 11350830.71 | 0.193801E+09 | 0.00 | 0.280381E+10 | 0.00 | 1.36 |
September | 0.101139E+10 | 0.437503E+09 | 0.00 | 7224805.35 | 10856302.12 | 0.00 | 0.334255E+10 | 0.00 | 0.98 |
October | 0.209734E+10 | 0.00 | 0.00 | 4158725.83 | 0.00 | 0.00 | 0.309132E+10 | 0.00 | 0.53 |
November | 0.287277E+10 | 0.00 | 0.00 | 1591848.72 | 0.00 | 0.00 | 0.148513E+10 | 0.00 | 0.34 |
December | 0.359431E+10 | 0.00 | 0.00 | 67927.79 | 0.00 | 0.300024E+09 | 90158005.05 | 0.00 | 0.26 |
Annual Sum or Average | 0.238682E+11 | 0.469834E+10 | 0.00 | 59327711.51 | 0.603366E+09 | 0.190722E+10 | 0.270846E+11 | 0.00 | 0.70 |
Minimum of Months | 0.409034E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.359431E+10 | 0.234189E+10 | 0.00 | 11350830.71 | 0.311134E+09 | 0.901706E+09 | 0.507465E+10 | 0.00 | 1.36 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.318892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100547E+10 | 0.00 | 0.00 | 0.44 |
February | 0.293813E+10 | 0.00 | 0.00 | 407224.32 | 0.00 | 0.722943E+09 | 0.218546E+09 | 0.00 | 0.45 |
March | 0.344253E+10 | 0.00 | 0.00 | 3321557.08 | 0.00 | 0.112059E+09 | 0.177139E+10 | 0.00 | 0.63 |
April | 0.251732E+10 | 0.00 | 0.00 | 6482543.80 | 0.00 | 0.00 | 0.433044E+10 | 0.00 | 0.95 |
May | 0.155144E+10 | 1112046.23 | 0.00 | 9887716.79 | 4089710.28 | 0.00 | 0.576253E+10 | 0.00 | 1.52 |
June | 0.583855E+09 | 0.517758E+09 | 0.00 | 10623811.09 | 65165367.22 | 0.00 | 0.457689E+10 | 0.00 | 1.94 |
July | 0.581146E+09 | 0.178979E+10 | 0.00 | 9691311.67 | 0.362209E+09 | 0.00 | 0.193292E+10 | 0.00 | 1.88 |
August | 0.114045E+10 | 0.866021E+09 | 0.00 | 9786945.34 | 0.222138E+09 | 0.00 | 0.263066E+10 | 0.00 | 1.93 |
September | 0.134060E+10 | 0.337245E+09 | 0.00 | 8418856.85 | 13157871.04 | 0.00 | 0.370142E+10 | 0.00 | 1.57 |
October | 0.246895E+10 | 0.00 | 0.00 | 4269953.47 | 0.00 | 292585.86 | 0.294660E+10 | 0.00 | 0.84 |
November | 0.378105E+10 | 0.00 | 0.00 | 931899.31 | 0.00 | 3158500.68 | 0.827456E+09 | 0.00 | 0.55 |
December | 0.356457E+10 | 0.00 | 0.00 | 58336.87 | 0.00 | 0.722694E+09 | 27354564.22 | 0.00 | 0.43 |
Annual Sum or Average | 0.270990E+11 | 0.351193E+10 | 0.00 | 63880156.57 | 0.666760E+09 | 0.256662E+10 | 0.287262E+11 | 0.00 | 1.10 |
Minimum of Months | 0.581146E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.378105E+10 | 0.178979E+10 | 0.00 | 10623811.09 | 0.362209E+09 | 0.100547E+10 | 0.576253E+10 | 0.00 | 1.94 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.303181E+10 | 0.00 | 0.00 | 2375347.48 | 0.00 | 0.111924E+10 | 0.145456E+10 | 0.00 | 0.38 |
February | 0.268385E+10 | 0.00 | 0.00 | 3173341.08 | 0.00 | 0.860750E+09 | 0.201005E+10 | 0.00 | 0.40 |
March | 0.290101E+10 | 0.00 | 0.00 | 10120026.71 | 0.00 | 0.199443E+09 | 0.569223E+10 | 0.00 | 0.66 |
April | 0.257490E+10 | 0.00 | 0.00 | 10226151.76 | 0.00 | 11308315.72 | 0.703514E+10 | 0.00 | 0.93 |
May | 0.182071E+10 | 3458183.12 | 0.00 | 11563104.05 | 3940904.64 | 0.00 | 0.682671E+10 | 0.00 | 1.25 |
June | 0.759116E+09 | 0.655385E+09 | 0.00 | 11902531.46 | 94178616.60 | 0.00 | 0.463473E+10 | 0.00 | 1.53 |
July | 0.691603E+09 | 0.251769E+10 | 0.00 | 9010537.25 | 0.395320E+09 | 0.00 | 0.161746E+10 | 0.00 | 1.43 |
August | 0.113957E+10 | 0.149553E+10 | 0.00 | 14962593.74 | 0.237353E+09 | 0.00 | 0.328149E+10 | 0.00 | 1.71 |
September | 0.121100E+10 | 0.585415E+09 | 0.00 | 17913422.70 | 13680380.53 | 0.00 | 0.615584E+10 | 0.00 | 1.67 |
October | 0.216278E+10 | 0.00 | 0.00 | 12484490.45 | 0.00 | 6121967.28 | 0.731608E+10 | 0.00 | 1.04 |
November | 0.344802E+10 | 0.00 | 0.00 | 5342956.71 | 0.00 | 26542323.78 | 0.377080E+10 | 0.00 | 0.58 |
December | 0.375436E+10 | 0.00 | 0.00 | 2031243.16 | 0.00 | 0.598283E+09 | 0.130518E+10 | 0.00 | 0.36 |
Annual Sum or Average | 0.261787E+11 | 0.525748E+10 | 0.00 | 0.111106E+09 | 0.744473E+09 | 0.282169E+10 | 0.511003E+11 | 0.00 | 1.00 |
Minimum of Months | 0.691603E+09 | 0.00 | 0.00 | 2031243.16 | 0.00 | 0.00 | 0.130518E+10 | 0.00 | 0.36 |
Maximum of Months | 0.375436E+10 | 0.251769E+10 | 0.00 | 17913422.70 | 0.395320E+09 | 0.111924E+10 | 0.731608E+10 | 0.00 | 1.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.463143E+10 | 0.00 | 0.00 | 88444.88 | 0.00 | 0.364265E+09 | 0.107259E+09 | 0.00 | 0.54 |
February | 0.394883E+10 | 0.00 | 0.00 | 827346.77 | 0.00 | 95922614.25 | 0.789552E+09 | 0.00 | 0.55 |
March | 0.208688E+10 | 0.00 | 0.00 | 8507540.45 | 0.00 | 193189.07 | 0.548498E+10 | 0.00 | 0.89 |
April | 0.764309E+09 | 0.00 | 0.00 | 15427807.82 | 0.00 | 0.00 | 0.950433E+10 | 0.00 | 1.52 |
May | 0.113216E+10 | 2539096.74 | 0.00 | 13293466.31 | 4421393.35 | 0.00 | 0.732241E+10 | 0.00 | 1.86 |
June | 0.388298E+09 | 0.653896E+09 | 0.00 | 17736606.32 | 89682469.72 | 0.00 | 0.553405E+10 | 0.00 | 2.56 |
July | 0.534792E+09 | 0.252404E+10 | 0.00 | 13221214.10 | 0.285907E+09 | 0.00 | 0.193887E+10 | 0.00 | 2.28 |
August | 0.791788E+09 | 0.164060E+10 | 0.00 | 18826815.09 | 75961604.37 | 0.00 | 0.396905E+10 | 0.00 | 2.70 |
September | 0.945518E+09 | 0.402204E+09 | 0.00 | 11798269.15 | 11504514.18 | 0.00 | 0.450991E+10 | 0.00 | 1.83 |
October | 0.163469E+10 | 0.00 | 0.00 | 7631850.67 | 0.00 | 0.00 | 0.548902E+10 | 0.00 | 1.16 |
November | 0.194465E+10 | 0.00 | 0.00 | 5020560.83 | 0.00 | 0.00 | 0.428630E+10 | 0.00 | 0.77 |
December | 0.348659E+10 | 0.00 | 0.00 | 1728563.45 | 0.00 | 1913318.30 | 0.188258E+10 | 0.00 | 0.54 |
Annual Sum or Average | 0.222899E+11 | 0.522327E+10 | 0.00 | 0.114108E+09 | 0.467477E+09 | 0.462294E+09 | 0.508183E+11 | 0.00 | 1.44 |
Minimum of Months | 0.388298E+09 | 0.00 | 0.00 | 88444.88 | 0.00 | 0.00 | 0.107259E+09 | 0.00 | 0.54 |
Maximum of Months | 0.463143E+10 | 0.252404E+10 | 0.00 | 18826815.09 | 0.285907E+09 | 0.364265E+09 | 0.950433E+10 | 0.00 | 2.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.446542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297799E+11 | 0.00 | 0.00 | 0.30 |
February | 0.744142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246769E+11 | 0.00 | 0.00 | 0.30 |
March | 0.233497E+11 | 0.00 | 0.00 | 6613820.48 | 0.00 | 0.135015E+11 | 0.315941E+10 | 0.00 | 0.34 |
April | 0.310529E+11 | 0.00 | 0.00 | 7946518.62 | 0.00 | 0.219891E+10 | 0.694009E+10 | 0.00 | 0.38 |
May | 0.178561E+11 | 1548251.55 | 0.00 | 49557210.42 | 29954124.73 | 0.00 | 0.296965E+11 | 0.00 | 0.68 |
June | 0.569062E+10 | 0.411986E+10 | 0.00 | 77005456.07 | 0.360656E+09 | 0.00 | 0.286073E+11 | 0.00 | 0.99 |
July | 0.208716E+10 | 0.154684E+11 | 0.00 | 52739356.82 | 0.122965E+10 | 0.00 | 0.109751E+11 | 0.00 | 0.87 |
August | 0.548037E+10 | 0.799549E+10 | 0.00 | 74995929.55 | 0.575081E+09 | 0.00 | 0.171599E+11 | 0.00 | 0.90 |
September | 0.156578E+11 | 0.277144E+10 | 0.00 | 39455260.94 | 83303945.78 | 0.00 | 0.170635E+11 | 0.00 | 0.74 |
October | 0.308420E+11 | 0.00 | 0.00 | 8455494.78 | 0.00 | 0.165427E+10 | 0.663470E+10 | 0.00 | 0.41 |
November | 0.286715E+11 | 0.00 | 0.00 | 0.00 | 13420568.98 | 0.742471E+10 | 0.00 | 0.00 | 0.31 |
December | 0.736592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276807E+11 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.179961E+12 | 0.303567E+11 | 0.00 | 0.316769E+09 | 0.229207E+10 | 0.106917E+12 | 0.120236E+12 | 0.00 | 0.54 |
Minimum of Months | 0.208716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.310529E+11 | 0.154684E+11 | 0.00 | 77005456.07 | 0.122965E+10 | 0.297799E+11 | 0.296965E+11 | 0.00 | 0.99 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.885829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296400E+11 | 0.00 | 0.00 | 0.52 |
February | 0.124258E+11 | 0.00 | 0.00 | 421719.49 | 0.00 | 0.233949E+11 | 0.220685E+09 | 0.00 | 0.53 |
March | 0.303171E+11 | 0.00 | 0.00 | 14703617.04 | 0.00 | 0.938207E+10 | 0.746123E+10 | 0.00 | 0.62 |
April | 0.282926E+11 | 0.00 | 0.00 | 44625824.26 | 0.00 | 0.169669E+10 | 0.277709E+11 | 0.00 | 0.85 |
May | 0.199774E+11 | 748826.19 | 0.00 | 82811900.50 | 36200017.56 | 5258325.30 | 0.475964E+11 | 0.00 | 1.44 |
June | 0.713910E+10 | 0.407100E+10 | 0.00 | 94766882.97 | 0.238094E+09 | 0.00 | 0.408813E+11 | 0.00 | 1.79 |
July | 0.220257E+10 | 0.137630E+11 | 0.00 | 93869328.18 | 0.166716E+10 | 0.00 | 0.188412E+11 | 0.00 | 1.59 |
August | 0.642494E+10 | 0.633054E+10 | 0.00 | 91351046.31 | 0.847311E+09 | 0.00 | 0.236048E+11 | 0.00 | 1.59 |
September | 0.174284E+11 | 0.230032E+10 | 0.00 | 67972172.79 | 0.309113E+09 | 3894474.94 | 0.284022E+11 | 0.00 | 1.44 |
October | 0.323450E+11 | 0.00 | 0.00 | 19127306.29 | 0.00 | 0.157791E+10 | 0.133941E+11 | 0.00 | 0.76 |
November | 0.328408E+11 | 0.00 | 0.00 | 1219529.03 | 15774254.75 | 0.846558E+10 | 0.113766E+10 | 0.00 | 0.56 |
December | 0.861605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312832E+11 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.206868E+12 | 0.264656E+11 | 0.00 | 0.510869E+09 | 0.311365E+10 | 0.105450E+12 | 0.209310E+12 | 0.00 | 1.02 |
Minimum of Months | 0.220257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.328408E+11 | 0.137630E+11 | 0.00 | 94766882.97 | 0.166716E+10 | 0.312832E+11 | 0.475964E+11 | 0.00 | 1.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.156193E+11 | 0.00 | 0.00 | 17099117.16 | 0.00 | 0.216225E+11 | 0.935614E+10 | 0.00 | 0.40 |
February | 0.164131E+11 | 0.00 | 0.00 | 23668426.25 | 0.00 | 0.176304E+11 | 0.125341E+11 | 0.00 | 0.43 |
March | 0.264810E+11 | 0.00 | 0.00 | 81222860.01 | 0.00 | 0.582913E+10 | 0.418021E+11 | 0.00 | 0.62 |
April | 0.272556E+11 | 0.00 | 0.00 | 75724006.41 | 0.00 | 0.224380E+10 | 0.487670E+11 | 0.00 | 0.79 |
May | 0.210274E+11 | 31436309.35 | 0.00 | 97836148.62 | 20184467.47 | 0.00 | 0.557404E+11 | 0.00 | 1.14 |
June | 0.944034E+10 | 0.465072E+10 | 0.00 | 95705382.70 | 0.453870E+09 | 0.00 | 0.359353E+11 | 0.00 | 1.29 |
July | 0.435720E+10 | 0.182244E+11 | 0.00 | 69921219.62 | 0.147806E+10 | 0.00 | 0.117433E+11 | 0.00 | 1.08 |
August | 0.705650E+10 | 0.101200E+11 | 0.00 | 0.125993E+09 | 0.697947E+09 | 0.00 | 0.247935E+11 | 0.00 | 1.31 |
September | 0.141318E+11 | 0.441738E+10 | 0.00 | 0.170754E+09 | 0.102828E+09 | 0.00 | 0.531234E+11 | 0.00 | 1.56 |
October | 0.228326E+11 | 0.00 | 0.00 | 0.106870E+09 | 0.00 | 0.107081E+10 | 0.581109E+11 | 0.00 | 0.95 |
November | 0.288627E+11 | 1783669.32 | 0.00 | 38424048.38 | 15399480.54 | 0.595972E+10 | 0.259302E+11 | 0.00 | 0.52 |
December | 0.179018E+11 | 0.00 | 0.00 | 10749562.02 | 0.00 | 0.224758E+11 | 0.580937E+10 | 0.00 | 0.39 |
Annual Sum or Average | 0.211379E+12 | 0.374457E+11 | 0.00 | 0.913967E+09 | 0.276829E+10 | 0.768322E+11 | 0.383646E+12 | 0.00 | 0.88 |
Minimum of Months | 0.435720E+10 | 0.00 | 0.00 | 10749562.02 | 0.00 | 0.00 | 0.580937E+10 | 0.00 | 0.39 |
Maximum of Months | 0.288627E+11 | 0.182244E+11 | 0.00 | 0.170754E+09 | 0.147806E+10 | 0.224758E+11 | 0.581109E+11 | 0.00 | 1.56 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.111170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291049E+11 | 0.00 | 0.00 | 0.55 |
February | 0.150825E+11 | 0.00 | 0.00 | 1088367.69 | 0.00 | 0.216864E+11 | 0.997662E+09 | 0.00 | 0.55 |
March | 0.335915E+11 | 0.00 | 0.00 | 16162106.11 | 0.00 | 0.752010E+10 | 0.100418E+11 | 0.00 | 0.66 |
April | 0.332216E+11 | 0.00 | 0.00 | 36804596.26 | 0.00 | 0.133870E+10 | 0.252836E+11 | 0.00 | 0.91 |
May | 0.220501E+11 | 3206387.22 | 0.00 | 88533977.34 | 35719978.86 | 0.00 | 0.449661E+11 | 0.00 | 1.51 |
June | 0.841169E+10 | 0.441356E+10 | 0.00 | 0.114098E+09 | 0.383588E+09 | 0.00 | 0.347892E+11 | 0.00 | 1.90 |
July | 0.352365E+10 | 0.152895E+11 | 0.00 | 78023795.95 | 0.107714E+10 | 0.00 | 0.103028E+11 | 0.00 | 1.47 |
August | 0.684346E+10 | 0.769187E+10 | 0.00 | 94066112.03 | 0.560698E+09 | 0.00 | 0.178138E+11 | 0.00 | 1.55 |
September | 0.186024E+11 | 0.245803E+10 | 0.00 | 73478148.35 | 0.276787E+09 | 0.00 | 0.237814E+11 | 0.00 | 1.44 |
October | 0.364436E+11 | 0.00 | 0.00 | 18143119.09 | 0.00 | 0.131754E+10 | 0.124084E+11 | 0.00 | 0.83 |
November | 0.357797E+11 | 0.00 | 0.00 | 2406176.59 | 16536582.21 | 0.674230E+10 | 0.217321E+10 | 0.00 | 0.59 |
December | 0.163527E+11 | 0.00 | 0.00 | 5875.79 | 0.00 | 0.252532E+11 | 58352428.52 | 0.00 | 0.55 |
Annual Sum or Average | 0.241020E+12 | 0.298562E+11 | 0.00 | 0.522811E+09 | 0.235047E+10 | 0.929631E+11 | 0.182616E+12 | 0.00 | 1.04 |
Minimum of Months | 0.352365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 0.364436E+11 | 0.152895E+11 | 0.00 | 0.114098E+09 | 0.107714E+10 | 0.291049E+11 | 0.449661E+11 | 0.00 | 1.90 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269062E+10 | 0.00 | 0.00 | 0.31 |
February | 0.298893E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240227E+10 | 0.00 | 0.00 | 0.31 |
March | 0.165494E+10 | 0.00 | 0.00 | 558582.85 | 0.00 | 0.162714E+10 | 0.218436E+09 | 0.00 | 0.36 |
April | 0.271483E+10 | 0.00 | 0.00 | 531887.96 | 0.00 | 0.570609E+09 | 0.482530E+09 | 0.00 | 0.38 |
May | 0.202738E+10 | 0.00 | 0.00 | 4042811.05 | 2174403.71 | 50446974.06 | 0.253383E+10 | 0.00 | 0.66 |
June | 0.627434E+09 | 0.465276E+09 | 0.00 | 7613068.20 | 43342936.30 | 0.00 | 0.283886E+10 | 0.00 | 1.04 |
July | 0.273621E+09 | 0.168887E+10 | 0.00 | 5089973.60 | 0.146024E+09 | 0.00 | 0.107552E+10 | 0.00 | 0.94 |
August | 0.577068E+09 | 0.909957E+09 | 0.00 | 7408864.57 | 69063288.20 | 0.00 | 0.166514E+10 | 0.00 | 0.94 |
September | 0.160711E+10 | 0.255369E+09 | 0.00 | 3340900.50 | 19041614.30 | 37565691.86 | 0.142619E+10 | 0.00 | 0.72 |
October | 0.258423E+10 | 0.00 | 0.00 | 485630.70 | 0.00 | 0.543588E+09 | 0.376248E+09 | 0.00 | 0.39 |
November | 0.152932E+10 | 0.00 | 3319494.91 | 0.00 | 331703.37 | 0.149832E+10 | 0.00 | 42996.82 | 0.31 |
December | 0.235128E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256372E+10 | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.142479E+11 | 0.331947E+10 | 3319494.91 | 29071719.44 | 0.279978E+09 | 0.119843E+11 | 0.106168E+11 | 42996.82 | 0.56 |
Minimum of Months | 0.117955E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.271483E+10 | 0.168887E+10 | 3319494.91 | 7613068.20 | 0.146024E+09 | 0.269062E+10 | 0.283886E+10 | 42996.82 | 1.04 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.228467E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269316E+10 | 0.00 | 0.00 | 0.49 |
February | 0.783629E+09 | 0.00 | 0.00 | 259.31 | 0.00 | 0.204105E+10 | 2639412.09 | 0.00 | 0.50 |
March | 0.234366E+10 | 0.00 | 0.00 | 918442.52 | 0.00 | 0.113450E+10 | 0.443969E+09 | 0.00 | 0.62 |
April | 0.234718E+10 | 0.00 | 0.00 | 3437037.86 | 0.00 | 0.393104E+09 | 0.233488E+10 | 0.00 | 0.80 |
May | 0.188453E+10 | 0.00 | 0.00 | 7354290.78 | 2516697.63 | 35518882.88 | 0.454793E+10 | 0.00 | 1.39 |
June | 0.654168E+09 | 0.457625E+09 | 0.00 | 9512559.53 | 28428687.63 | 0.00 | 0.416299E+10 | 0.00 | 1.87 |
July | 0.223017E+09 | 0.153928E+10 | 0.00 | 9240869.47 | 0.189832E+09 | 0.00 | 0.194532E+10 | 0.00 | 1.72 |
August | 0.598643E+09 | 0.719280E+09 | 0.00 | 9548053.13 | 97316719.10 | 0.00 | 0.236376E+10 | 0.00 | 1.68 |
September | 0.156090E+10 | 0.220753E+09 | 0.00 | 6037566.34 | 37403822.41 | 27786906.15 | 0.267157E+10 | 0.00 | 1.41 |
October | 0.283892E+10 | 0.00 | 0.00 | 1199530.71 | 0.00 | 0.449170E+09 | 0.806267E+09 | 0.00 | 0.71 |
November | 0.200158E+10 | 0.00 | 3702399.32 | 12635.89 | 383920.01 | 0.143565E+10 | 18024077.74 | 21890.59 | 0.55 |
December | 0.301061E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266446E+10 | 0.00 | 0.00 | 0.50 |
Annual Sum or Average | 0.157658E+11 | 0.293693E+10 | 3702399.32 | 47261245.54 | 0.355882E+09 | 0.108744E+11 | 0.192973E+11 | 21890.59 | 1.02 |
Minimum of Months | 0.223017E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.283892E+10 | 0.153928E+10 | 3702399.32 | 9548053.13 | 0.189832E+09 | 0.269316E+10 | 0.454793E+10 | 21890.59 | 1.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.898674E+09 | 0.00 | 0.00 | 1025366.71 | 0.00 | 0.221161E+10 | 0.565420E+09 | 0.00 | 0.39 |
February | 0.116399E+10 | 0.00 | 0.00 | 1768611.21 | 0.00 | 0.169913E+10 | 0.972830E+09 | 0.00 | 0.42 |
March | 0.211432E+10 | 0.00 | 0.00 | 6330882.33 | 0.00 | 0.877805E+09 | 0.330488E+10 | 0.00 | 0.62 |
April | 0.249295E+10 | 0.00 | 0.00 | 6097928.22 | 0.00 | 0.501948E+09 | 0.438902E+10 | 0.00 | 0.76 |
May | 0.230887E+10 | 698423.33 | 0.00 | 8963250.22 | 2445467.10 | 80074105.47 | 0.536498E+10 | 0.00 | 1.12 |
June | 0.102630E+10 | 0.546111E+09 | 0.00 | 9695365.35 | 50172510.43 | 489296.06 | 0.377807E+10 | 0.00 | 1.37 |
July | 0.455307E+09 | 0.203878E+10 | 0.00 | 7961995.16 | 0.205632E+09 | 0.00 | 0.134579E+10 | 0.00 | 1.21 |
August | 0.761346E+09 | 0.116396E+10 | 0.00 | 13467587.14 | 84658433.75 | 0.00 | 0.259413E+10 | 0.00 | 1.41 |
September | 0.143059E+10 | 0.412170E+09 | 0.00 | 15502709.59 | 21998681.87 | 33223140.44 | 0.519854E+10 | 0.00 | 1.54 |
October | 0.228567E+10 | 0.00 | 0.00 | 7808682.24 | 0.00 | 0.380346E+09 | 0.464038E+10 | 0.00 | 0.89 |
November | 0.202091E+10 | 0.00 | 1608017.51 | 2533328.40 | 3005649.73 | 0.117322E+10 | 0.169785E+10 | 4107.61 | 0.49 |
December | 0.930779E+09 | 0.00 | 0.00 | 584755.08 | 0.00 | 0.236072E+10 | 0.305362E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.178897E+11 | 0.416171E+10 | 1608017.51 | 81740461.67 | 0.367913E+09 | 0.931857E+10 | 0.341573E+11 | 4107.61 | 0.89 |
Minimum of Months | 0.455307E+09 | 0.00 | 0.00 | 584755.08 | 0.00 | 0.00 | 0.305362E+09 | 0.00 | 0.39 |
Maximum of Months | 0.249295E+10 | 0.203878E+10 | 1608017.51 | 15502709.59 | 0.205632E+09 | 0.236072E+10 | 0.536498E+10 | 4107.61 | 1.54 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.619172E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254902E+10 | 0.00 | 0.00 | 0.53 |
February | 0.107416E+10 | 0.00 | 0.00 | 74620.47 | 0.00 | 0.194313E+10 | 63551034.76 | 0.00 | 0.55 |
March | 0.271199E+10 | 0.00 | 0.00 | 1329066.62 | 0.00 | 0.967363E+09 | 0.780674E+09 | 0.00 | 0.68 |
April | 0.299744E+10 | 0.00 | 0.00 | 3106165.22 | 0.00 | 0.346125E+09 | 0.241007E+10 | 0.00 | 0.91 |
May | 0.244605E+10 | 129643.48 | 0.00 | 8310985.14 | 2626553.06 | 11436389.72 | 0.441918E+10 | 0.00 | 1.52 |
June | 0.907291E+09 | 0.488415E+09 | 0.00 | 12588176.48 | 58820133.01 | 0.00 | 0.365630E+10 | 0.00 | 2.02 |
July | 0.402125E+09 | 0.168426E+10 | 0.00 | 8515525.00 | 0.145358E+09 | 0.00 | 0.109487E+10 | 0.00 | 1.61 |
August | 0.745647E+09 | 0.889105E+09 | 0.00 | 10272380.39 | 66380539.83 | 0.00 | 0.177601E+10 | 0.00 | 1.66 |
September | 0.193261E+10 | 0.221406E+09 | 0.00 | 6668071.56 | 41276826.16 | 24553195.46 | 0.224683E+10 | 0.00 | 1.45 |
October | 0.325922E+10 | 0.00 | 0.00 | 1418274.81 | 0.00 | 0.355133E+09 | 0.103594E+10 | 0.00 | 0.82 |
November | 0.248179E+10 | 0.00 | 219886.87 | 134419.99 | 4214427.63 | 0.116083E+10 | 0.143471E+09 | 168.17 | 0.61 |
December | 0.836863E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237983E+10 | 0.00 | 0.00 | 0.54 |
Annual Sum or Average | 0.204143E+11 | 0.328332E+10 | 219886.87 | 52417685.68 | 0.318676E+09 | 0.973743E+10 | 0.176269E+11 | 168.17 | 1.08 |
Minimum of Months | 0.402125E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.325922E+10 | 0.168426E+10 | 219886.87 | 12588176.48 | 0.145358E+09 | 0.254902E+10 | 0.441918E+10 | 168.17 | 2.02 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 2477877.60 | 0.00 | 0.00 | 0.828923E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7094220.43 | 0.00 | 0.00 | 0.752109E+09 | 0.00 | 0.28 |
March | 0.00 | 341641.65 | 0.00 | 14980952.49 | 0.00 | 0.00 | 0.661956E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 17953960.65 | 0.00 | 0.00 | 0.503215E+09 | 0.00 | 0.29 |
May | 0.00 | 204704.17 | 0.00 | 4222202.92 | 0.00 | 0.00 | 0.361070E+09 | 0.00 | 0.29 |
June | 0.00 | 58160105.15 | 0.00 | 6079628.60 | 0.00 | 0.00 | 0.158978E+09 | 0.00 | 0.30 |
July | 0.00 | 0.162709E+09 | 0.00 | 3592199.68 | 0.00 | 0.00 | 27352863.84 | 0.00 | 0.28 |
August | 0.00 | 83711502.41 | 0.00 | 10975182.68 | 0.00 | 0.00 | 72481405.63 | 0.00 | 0.31 |
September | 0.00 | 23597194.66 | 0.00 | 3412758.70 | 0.00 | 0.00 | 0.195990E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 8746302.55 | 0.00 | 0.00 | 0.443695E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 12601952.15 | 0.00 | 0.00 | 0.563740E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 16869425.42 | 0.00 | 0.00 | 0.760824E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.328724E+09 | 0.00 | 0.109007E+09 | 0.00 | 0.00 | 0.533034E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2477877.60 | 0.00 | 0.00 | 27352863.84 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.162709E+09 | 0.00 | 17953960.65 | 0.00 | 0.00 | 0.828923E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.267548E+10 | 0.00 | 0.00 | 6768476.43 | 0.00 | 0.00 | 0.556209E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 50771303.78 | 0.00 | 0.00 | 0.754143E+10 | 0.00 | 0.28 |
March | 0.00 | 3264517.92 | 0.00 | 0.129009E+09 | 0.00 | 0.00 | 0.664084E+10 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 0.163041E+09 | 0.00 | 0.00 | 0.504705E+10 | 0.00 | 0.29 |
May | 0.00 | 1863674.12 | 0.00 | 35787310.00 | 0.00 | 0.00 | 0.362163E+10 | 0.00 | 0.29 |
June | 0.00 | 0.576149E+09 | 0.00 | 56432028.39 | 0.00 | 0.00 | 0.159346E+10 | 0.00 | 0.30 |
July | 0.00 | 0.162149E+10 | 0.00 | 33866553.24 | 0.00 | 0.00 | 0.275327E+09 | 0.00 | 0.28 |
August | 0.00 | 0.835296E+09 | 0.00 | 0.103970E+09 | 0.00 | 0.00 | 0.728791E+09 | 0.00 | 0.31 |
September | 0.00 | 0.225659E+09 | 0.00 | 28633907.88 | 0.00 | 0.00 | 0.197733E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 73916252.48 | 0.00 | 0.00 | 0.445047E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.106998E+09 | 0.00 | 0.00 | 0.565364E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.141455E+09 | 0.00 | 0.00 | 0.763407E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.267548E+10 | 0.326372E+10 | 0.00 | 0.930649E+09 | 0.00 | 0.00 | 0.507261E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 6768476.43 | 0.00 | 0.00 | 0.275327E+09 | 0.00 | 0.28 |
Maximum of Months | 0.267548E+10 | 0.162149E+10 | 0.00 | 0.163041E+09 | 0.00 | 0.00 | 0.763407E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.566228E+09 | 0.00 | 0.00 | 228807.02 | 0.00 | 0.00 | 0.240853E+09 | 0.00 | 0.28 |
February | 126286.25 | 0.00 | 0.00 | 4241234.87 | 0.00 | 0.00 | 0.754771E+09 | 0.00 | 0.28 |
March | 0.00 | 320094.05 | 0.00 | 11849423.81 | 0.00 | 0.00 | 0.665196E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 15597968.82 | 0.00 | 0.00 | 0.505481E+09 | 0.00 | 0.29 |
May | 183654.12 | 193431.14 | 0.00 | 3228583.88 | 0.00 | 0.00 | 0.362759E+09 | 0.00 | 0.29 |
June | 0.00 | 57664783.95 | 0.00 | 5570988.47 | 0.00 | 0.00 | 0.159555E+09 | 0.00 | 0.30 |
July | 0.00 | 0.162110E+09 | 0.00 | 3363335.38 | 0.00 | 0.00 | 27603160.42 | 0.00 | 0.28 |
August | 0.00 | 83447902.96 | 0.00 | 10349872.13 | 0.00 | 0.00 | 73056982.03 | 0.00 | 0.31 |
September | 0.00 | 22517361.76 | 0.00 | 2555180.17 | 0.00 | 0.00 | 0.198917E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 6540604.84 | 0.00 | 0.00 | 0.446242E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 9614744.09 | 0.00 | 0.00 | 0.566582E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 13101306.67 | 0.00 | 0.00 | 0.764508E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.566538E+09 | 0.326254E+09 | 0.00 | 86242050.15 | 0.00 | 0.00 | 0.476552E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 228807.02 | 0.00 | 0.00 | 27603160.42 | 0.00 | 0.28 |
Maximum of Months | 0.566228E+09 | 0.162110E+09 | 0.00 | 15597968.82 | 0.00 | 0.00 | 0.764508E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.640127E+09 | 0.00 | 0.00 | 0.476271E+12 | 0.00 | 7.19 |
February | 0.00 | 0.00 | 0.00 | 0.120595E+10 | 0.00 | 0.00 | 0.725957E+12 | 0.00 | 11.98 |
March | 0.00 | 0.00 | 0.00 | 0.174762E+10 | 0.00 | 0.00 | 0.100723E+13 | 0.00 | 23.07 |
April | 0.00 | 0.00 | 0.00 | 0.217947E+10 | 0.00 | 0.00 | 0.121810E+13 | 0.00 | 35.09 |
May | 0.00 | 0.00 | 0.00 | 0.543654E+09 | 0.00 | 0.00 | 0.425927E+12 | 0.00 | 18.53 |
June | 0.00 | 0.145605E+11 | 0.00 | 0.110750E+10 | 0.00 | 0.00 | 0.468038E+12 | 0.00 | 38.52 |
July | 0.00 | 0.946582E+11 | 0.00 | 0.154149E+10 | 0.00 | 0.00 | 0.231400E+12 | 0.00 | 43.82 |
August | 0.00 | 0.587437E+11 | 0.00 | 0.212012E+10 | 0.00 | 0.00 | 0.327010E+12 | 0.00 | 45.44 |
September | 0.00 | 0.691631E+09 | 0.00 | 0.570383E+09 | 0.00 | 0.00 | 0.341413E+12 | 0.00 | 24.49 |
October | 0.00 | 0.00 | 0.00 | 0.103374E+10 | 0.00 | 0.00 | 0.695300E+12 | 0.00 | 23.13 |
November | 0.00 | 0.00 | 0.00 | 0.148327E+10 | 0.00 | 0.00 | 0.101184E+13 | 0.00 | 26.08 |
December | 0.00 | 0.00 | 0.00 | 0.258071E+10 | 0.00 | 0.00 | 0.132951E+13 | 0.00 | 23.65 |
Annual Sum or Average | 0.00 | 0.168654E+12 | 0.00 | 0.167540E+11 | 0.00 | 0.00 | 0.825799E+13 | 0.00 | 26.82 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.543654E+09 | 0.00 | 0.00 | 0.231400E+12 | 0.00 | 7.19 |
Maximum of Months | 0.00 | 0.946582E+11 | 0.00 | 0.258071E+10 | 0.00 | 0.00 | 0.132951E+13 | 0.00 | 45.44 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:48
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.251757E+12 | 0.244495E+11 | 0.00 | 0.222031E+13 | 0.151451E+12 |
February | 0.388697E+12 | 0.256403E+11 | 0.00 | 0.235889E+13 | 0.196878E+12 |
March | 0.582359E+12 | 0.160936E+11 | 0.00 | 0.294469E+13 | 0.363467E+12 |
April | 0.704169E+12 | 0.131070E+11 | 0.00 | 0.332710E+13 | 0.374827E+12 |
May | 0.868213E+12 | 0.730561E+10 | 0.00 | 0.244771E+13 | 0.375855E+12 |
June | 0.934500E+12 | 0.303262E+10 | 0.00 | 0.163332E+13 | 0.149813E+13 |
July | 0.867609E+12 | -420172549.1 | 0.00 | 0.395053E+12 | 0.306046E+13 |
August | 0.740108E+12 | 0.126170E+10 | 0.00 | 0.114061E+13 | 0.300027E+13 |
September | 0.559949E+12 | 0.417244E+10 | 0.00 | 0.200183E+13 | 0.817518E+12 |
October | 0.374453E+12 | 0.100499E+11 | 0.00 | 0.283471E+13 | 0.258143E+12 |
November | 0.201341E+12 | 0.139746E+11 | 0.00 | 0.294915E+13 | 0.266419E+12 |
December | 0.227163E+12 | 0.260032E+11 | 0.00 | 0.314085E+13 | 0.371034E+12 |
Annual Sum or Average | 0.670032E+13 | 0.144670E+12 | 0.00 | 0.273942E+14 | 0.107345E+14 |
Minimum of Months | 0.201341E+12 | -420172549.1 | 0.00 | 0.395053E+12 | 0.151451E+12 |
Maximum of Months | 0.934500E+12 | 0.260032E+11 | 0.00 | 0.332710E+13 | 0.306046E+13 |